Bryant 569D User Manual

Models 566D, 566E, 569D,  
569F, 576C  
COMMERCIAL AIR-COOLED  
CONDENSING UNITS WITH  
524A AIR-HANDLING UNITS  
with 524A  
6 to 20 Tons  
569D072-120  
576C120  
569F120  
524A072-300  
566D150-240  
566E150-240  
pressures. A low-pressure switch protects the system from  
low-pressure conditions, including loss of charge.  
FEATURES/BENEFITS  
These dependable split systems match Bryant’s indoor-air han-  
dlers and direct-expansion coils with outdoor condensing units  
for a wide selection of commercial cooling solutions.  
The 569F120 and 566E150-240 units feature 2 scroll compres-  
sors and 2 refrigerant circuits that provide continuous air  
conditioning and design flexibility. These units also include  
Cycle-LOC™ anti-short-cycling protection which helps to  
protect the units against compressor failure.  
CONSTRUCTED FOR LONG LIFE — The 569D (single cir-  
cuit, scroll compressor), 576C (single circuit semi-hermetic  
compressor), 569F/566E (dual circuit, scroll compressor) and  
566D (semi-hermetic compressor) models are designed and  
built to last. The copper tube-aluminum fin outdoor coil  
construction provides years of trouble-free operation. Where  
conditions require them, E-coated coils and pre-coated fin coils  
are also available. Cabinets are constructed of prepainted  
galvanized steel, delivering unparalleled protection from the  
environment. Inside and outside surfaces are protected to  
ensure long life, good looks, and reliable operation. Safety con-  
trols are used for enhanced system protection and reliability.  
All units include a crankcase heater to eliminate liquid slugging  
at start-up. Units with semi-hermetic compressors are also  
equipped with an oil-level sight glass.  
Latest safety standards are assured through UL and UL  
Canada approvals.  
INNOVATIVE BRYANT PACKAGED AIR HANDLERS ARE  
CUSTOM MATCHED TO THE CONDENSING UNITS — The  
524A Series has excellent fan performance, efficient direct-  
expansion (DX) coils, a unique combination of indoor-air qual-  
ity features, and easy installation. Its versatility and state-of-  
the-art features help to ensure that your split system provides  
economical performance now and in the future.  
EFFICIENT OPERATION — Building owners will appreciate  
the high unit EERs (Energy Efficiency Ratios) offered by these  
condensing units. These units provide greater efficiency than  
similar units in the marketplace, which translates into year-  
round operating savings.  
Indoor-Air Quality (IAQ) Features — The unique combination  
of IAQ features in the 524A Series air handlers help to ensure  
that only clean, fresh, conditioned air is delivered to the occu-  
pied space.  
CONTROLS FOR PERFORMANCE DEPENDABILITY — The  
condensing units offer the building owner operating controls  
and components designed for performance dependability. The  
highly efficient hermetic and semi-hermetic compressors are  
engineered for long life and durability. The compressors  
include overload protection and vibration isolation for enhance-  
ment of quiet operation. The high-pressure switch protects the  
entire refrigeration system from abnormally high operating  
Direct-expansion (DX) cooling coils prevent the build-up of  
humidity in the room, even during part-load conditions. Unit  
sizes of 10 tons and above feature dual-circuit coils for  
improved temperature control.  
Standard 2-in. disposable filters remove dust and airborne par-  
ticles from the occupied space for cleaner air.  
Form No. PDS 569D.72.2  
ARI* CAPACITY RATINGS  
SYSTEM†  
Net Cap.  
CONDENSING UNIT ONLY**  
AIR  
HANDLER/  
INDOOR COIL  
CONDENSING  
UNIT  
Gross Cap.  
EER  
IPLV  
EER  
IPLV  
(Btuh)  
(Btuh)  
524A-B072††  
524A-C072††  
524A-B090  
69,000  
72,000  
71,000  
74,000  
11.0  
11.2  
10.8  
11.0  
N/A  
N/A  
N/A  
N/A  
569D072  
569D090  
569D120  
576C120  
569F120  
566D150  
72,000  
12.4  
N/A  
524A-C090††  
524A-B072  
87,000  
91,000  
90,000  
94,000  
10.6  
11.3  
10.6  
11.2  
N/A  
N/A  
N/A  
N/A  
524A-C072††  
524A-B090  
100,000  
133,000  
124,000  
123,000  
150,000  
12.7  
12.4  
12.0  
12.3  
12.1  
N/A  
N/A  
524A-C090††  
524A-B120  
524A-C120  
524A-B150  
524A-C150  
118,000  
125,000  
123,000  
130,000  
10.3  
10.4  
10.4  
10.4  
N/A  
N/A  
N/A  
N/A  
524A-B120  
524A-C120  
524A-B150  
524A-C150  
114,000  
119,000  
118,000  
125,000  
10.3  
10.3  
10.4  
10.3  
13.1  
13.6  
14.1  
14.5  
16.5  
16.0  
15.8  
524A-B120  
524A-C120  
524A-B150  
524A-C150  
113,000  
118,000  
118,000  
124,000  
10.3  
10.5  
10.5  
10.9  
11.7  
12.4  
12.8  
13.2  
524A-B150  
524A-C150  
524A-B180  
524A-C180  
138,000  
144,000  
144,000  
146,000  
10.4  
10.6  
10.6  
10.8  
12.7  
13.0  
11.6  
13.1  
524A-B120  
524A-C120  
524A-B150  
524A-C150  
524A-B180  
524A-C180  
135,000  
143,000  
145,000  
153,000  
152,000  
161,000  
9.7  
10.2  
10.5  
11.1  
10.8  
11.3  
9.9  
10.3  
10.9  
11.5  
11.0  
11.5  
566E150  
566D180  
566E180  
158,000  
198,000  
204,000  
12.5  
11  
15.1  
14.9  
13.9  
524A-B180  
524A-C180  
524A-B240  
524A-C240  
176,000  
182,000  
184,000  
196,000  
9.8  
9.7  
12.3  
12.1  
12.2  
12.5  
9.8  
10.0  
524A-B150  
524A-C150  
524A-B180  
524A-C180  
524A-B240  
524A-C240  
176,000  
185,000  
187,000  
198,000  
194,000  
204,000  
10.0  
10.3  
10.2  
10.6  
10.1  
10.4  
10.4  
10.8  
10.5  
10.9  
10.2  
10.4  
11.9  
566D240  
566E240  
524A-C300  
244,000  
9.5  
11.8  
248,000  
259,000  
10.5  
11.2  
13.9  
13.1  
524A-C240  
524A-B300  
524A-C300  
243,000  
242,000  
252,000  
9.6  
9.6  
9.7  
9.8  
9.9  
9.9  
LEGEND  
EER — Energy Efficiency Ratio  
IPLV — Integrated Part Load Value  
N/A  
Not Applicable  
SST — Saturated Suction Temperature  
*Air Conditioning and Refrigeration Institute.  
†Ratings in accordance with latest ARI Standard revisions.  
**Condensing unit only ratings are at 45 F SST and 95 F entering-air temperature.  
††ENERGY STAR® compliant combination of condensing unit and air handler/  
indoor coil.  
SOUND LEVELS, dB — 569D/576C/566D,E  
OCTAVE BANDS  
250 500 1000 2000 4000 8000  
SOUND RATING  
(60 Hz) dB (A)  
UNIT  
63  
125  
072  
569D 090  
120  
80.0  
84.0  
85.0  
43.8 61.4 66.2 70.8 73.8  
58.5 67.3 71.3 75.4 77.2  
63.7 67.6 72.5 77.0 80.4  
75.2  
75.8  
77.5  
73.0  
76.5  
74.7  
62.7  
71.3  
65.9  
576C 120  
150  
83.0  
52.5 66.1 75.1 75.4 78.3  
73.5  
71.0  
64.2  
86.2  
86.2  
90.0  
93.0 86.0 83.0 80.0  
93.0 86.0 83.0 80.0  
78.0  
78.0  
82.5  
73.0  
73.0  
76.5  
71.0  
71.0  
61.5  
566D  
180  
240  
83.5 81.5 88.5 86.5 85.5  
150  
566E 180  
240  
86.9  
87.5  
88.0  
90.9 86.1 83.1 84.0  
90.9 86.1 83.4 84.5  
90.9 86.1 83.8 84.5  
73.5  
76.6  
79.2  
71.7  
73.2  
74.3  
66.7  
63.5  
65.5  
ESTIMATED SOUND POWER LEVELS (Lw) — 524A072-300  
OCTAVE BAND CENTER FREQUENCY  
UNIT  
CFM  
dB(A)  
63  
125  
89.2  
91.3  
94.6  
93.3  
94.9  
98.6  
98.5  
250  
85.2  
87.3  
90.6  
89.3  
90.9  
94.6  
94.5  
500  
84.2  
86.3  
89.6  
90.3  
91.9  
95.6  
95.5  
1000  
80.2  
82.3  
85.6  
84.3  
85.9  
89.6  
89.5  
2000  
78.2  
80.3  
83.6  
82.3  
83.9  
87.6  
87.5  
4000  
74.2  
76.3  
79.6  
78.3  
79.9  
83.6  
83.5  
524A072  
524A090  
524A120  
524A150  
524A180  
524A240  
524A300  
2,400  
3,000  
4,000  
5,000  
6,000  
8,000  
10,000  
86.3  
88.3  
91.6  
91.1  
92.7  
96.4  
96.2  
93.2  
95.3  
98.6  
97.3  
98.9  
102.6  
102.5  
NOTE: Since this data is calculated, these sound power levels may be different than the actual  
sound power levels. The accoustic center of the unit is located at geometric center of the unit.  
3
OPTIONS AND ACCESSORIES  
566D, 566E, 569D, 569F, 576C FACTORY-INSTALLED  
Non-Fused Disconnect Switch (566E, 569D, 569F, 576C  
Only) to remove power locally at the condensing unit. This  
switch also includes a power lockout capability to protect the  
service person. This lockout switch saves the service person  
time and effort because there is no need to access a distant dis-  
connect switch while servicing the unit.  
OPTIONS  
Dura-Shield Condenser Coils offer several options to match  
coil protection to site conditions for optimum durability. See  
table below. Consult your Bryant representative for further  
information.  
FIELD-INSTALLED ACCESSORIES  
E-Coated Aluminum-Fin Coils have a flexible and durable  
epoxy coating uniformly applied to all coil surfaces. Unlike brittle  
phenolic dip and bake coatings, E-coating provides superior  
protection with unmatched flexibility, edge coverage, metal  
adhesion, thermal performance, and most importantly, corro-  
sion resistance.  
Electric Unloader Package (576C120 Only) includes hard-  
ware and solenoid valve to convert a pressure-operated  
unloader to electric unloading.  
–20 F Low-Ambient Temperature Accessory Kit (Motormas-  
ter) controls outdoor-fan motor operation to maintain the correct  
head pressure at low outdoor ambient temperatures.  
E-coated coils provide this protection since all coil surfaces are  
completely encapsulated from environmental contamination.  
This coating is especially suitable in industrial environments.  
Condenser Coil Grille Package protects condensing unit coil  
from impact by large objects and vandalism.  
Pre-Coated Fin Coils provide protection in mild coastal  
environments.  
Bryant’s Line of Thermostats provide both programmable and  
non-programmable capability with the new Debonair® line of  
commercial programmable thermostats. The Commercial  
Electronic thermostats provide 7-day programmable capability  
for economical applications.  
–20 F Low-Ambient Temperature Kit Option (Motormaster®)  
(566E, 569D, 569F, 576C Only) controls outdoor-fan motor  
operation to maintain the correct head pressure at low outdoor  
ambient temperatures.  
Hail Guard Package protects against damage from flying  
debris and hail.  
115-v Convenience Outlet (566E, 569D, 569F, 576C Only) to  
power up electric drills, lights, and refrigerant recovery  
machines. This means you are no longer required to run a sep-  
arate 115-v power supply.  
Gage Panel Package provides a suction and discharge pres-  
sure gage for the refrigerant circuit.  
CONDENSER COIL OPTIONS  
ENVIRONMENT  
COPPER-TUBE COILS  
WITH DURA-SHIELD  
OPTION  
Mild  
Coastal  
Industrial/  
Coastal  
Standard  
Al Fins (Standard Coils)  
Al Fins, E-Coated  
X
X
Al Fins, Pre-Coated  
X
LEGEND  
Al — Aluminum  
LOW AMBIENT CONTROL  
(FACTORY-INSTALLED OR  
FIELD-INSTALLED)  
FACTORY-INSTALLED  
DURA-SHIELD  
COIL PROTECTION  
FACTORY-INSTALLED  
CONVENIENCE OUTLET  
FACTORY-INSTALLED  
DISCONNECT SWITCH  
Options and Accessories  
4
OPTIONS AND ACCESSORIES (cont)  
Return-Air Grille provides a protective barrier over the return-  
524A-B, C FACTORY-INSTALLED OPTIONS  
air opening and gives a finished appearance to units installed in  
the occupied space. Accessory is available unpainted or  
painted.  
Alternate Fan Motors and Drives are available to provide the  
widest possible range of performance.  
High-Capacity 4-Row Coils are available to provide increased  
latent and sensible capacities (524A-C).  
Subbase provides a stable, raised platform and room for con-  
densate drain trap connection for vertical floor-mounted units.  
Accessory is available unpainted or painted.  
Prepainted Steel Units are available from the factory for appli-  
cations that require painted units. Units are painted with Ameri-  
can Sterling Gray color.  
Overhead Suspension Package includes necessary brackets  
to support units in horizontal ceiling installations.  
FIELD-INSTALLED ACCESSORIES  
Two-Row Hot Water Coils have copper tubes mechanically  
bonded to aluminum plate fins and non-ferrous headers.  
Bryant’s Line of Thermostats provide both programmable and  
non-programmable capability. The Commercial Electronic  
thermostats provide 7-day programmable capability for eco-  
nomical applications.  
One-Row Steam Coil has copper tubes and aluminum fins.  
The Inner Distributing Tube (IDT) design provides uniform  
temperatures across the coil face. The steam coil has a broad  
operating pressure range; up to 20 psig (138 kPag) at 260 F  
(127 C). The IDT steam coils are especially suited to applica-  
tions where sub-freezing air enters the unit.  
Condensate Drain Trap includes an overflow shutoff switch  
that can be wired to turn off the unit if the trap becomes  
plugged. Kit also includes a wire harness that can be connected  
to an alarm if desired. The transparent trap is designed for easy  
service and maintenance.  
Electric Resistance Heat Coils have an open-wire design and  
are mounted in a rigid frame. Safety cutouts for high tempera-  
ture conditions are standard. Terminal block for single-point  
power connection is included.  
UV-C Germicidal Lamps kill mold and fungus, which may grow  
on evaporator coil and condensate pan surfaces. The use of  
UV-C germicidal lamps eliminates the foul odors that result from  
this growth of mold and fungus. It also provides a self-cleaning  
function for the evaporator coil and drain pan.  
Economizer (Enthalpy Controlled) provides ventilation air  
and “free” cooling if outside ambient temperature and humidity  
are suitable.  
Discharge Plenum directs the air discharge directly into the  
occupied space integral horizontal and vertical louvers enable  
redirection of airflow. Accessory is available unpainted or  
painted. Field assembly required.  
Commercial Programmable  
and Non-Programmable Thermostat  
5
OPTIONS AND ACCESSORIES (cont)  
HOT WATER OR  
STEAM COIL  
DISCHARGE  
PLENUM  
RETURN-AIR  
GRILLE  
SUBBASE  
FAN  
COIL  
UNIT  
FAN COIL  
UNIT  
524A with Discharge Plenum,  
Return Grille, and Subbase  
524A with Hot Water or Steam Coil  
ECONOMIZER  
FAN COIL UNIT  
524A with Economizer  
524A with Condensate Trap  
6
SELECTION PROCEDURE  
To determine combination ratings for 569D/F, 576C and 566D/E  
units matched with 524A Series air handlers, follow these steps:  
III DETERMINE SIZES OF LIQUID AND SUCTION LINES.  
Enter Refrigerant Piping Sizes table. The sizes shown are  
based on an equivalent length of pipe. This equivalent  
length is equal to the linear length of pipe indicated at the  
top of each sizing column, plus a 50% allowance for fitting  
losses. (For a more accurate determination of actual  
equivalent length in place of using the estimated 50%  
value, refer to a standard refrigeration piping practice.) For  
this example, note in the linear length column that the  
I DETERMINE COOLING LOAD, EVAPORATOR-AIR  
TEMPERATURE, AND QUANTITY.  
Given:  
Total Cooling Capacity  
Required (TC). . . . . . . . . . . . . . . . . . . . . . 127,000 Btuh  
Sensible Heat Capacity  
Required (SHC) . . . . . . . . . . . . . . . . . . . . . 95,000 Btuh  
Compressor Type . . . . . . . . . . . . . . . . . . . . . . . . . . .Scroll  
Temperature Air Entering Condenser (Edb). . . . . . . . 95 F  
Temperature Air Entering  
Evaporator (db/wb). . . . . . . . . . . . . . . .80 F db, 67 F wb  
Evaporator Air Quantity . . . . . . . . . . . . . . . . . . . 4,000 cfm  
External Static Pressure . . . . . . . . . . . . . . . . . . 0.4 in. wg  
Length of Interconnecting  
Refrigerant Piping . . . . . . . . . . . . . . . . . . . 25 ft (Linear)  
Power Supply (V-Ph-Hz) . . . . . . . . . . . . . . . 208/230-3-60  
1
proper pipe size is /2 in. for the liquid line and 13/8 in. for  
the suction line.  
IV DETERMINE FAN RPM AND BHP (BRAKE  
HORSEPOWER).  
At the Air Handler Fan Performance table enter at 524A-  
C120 with high capacity coil at 4000 cfm and move to the  
External Static Pressure (ESP) column. Note that the con-  
ditions require 803 rpm at 1.77 bhp.  
V DETERMINE MOTOR AND DRIVE.  
II SELECT  
CONDENSING  
UNIT  
AIR-HANDLER  
Enter the Fan Motor Data tables and find the standard  
motor for 524A-C120 unit rated at 2.4 Hp. Since the bhp  
required is 1.77, a standard motor satisfies the require-  
ment and should be used.  
COMBINATION.  
For this example, select a 569D120 matched with a  
524A-C120 with high-capacity 4-row coil This 569D120/  
524A-C120 condensing unit air-handler combination  
provides 130,000 Btuh of total cooling capacity and  
98,200 Btuh of sensible capacity at the given conditions. If  
other temperatures or airflow values are required, interpo-  
late the values from the combination ratings.  
Next, find the type of drive that satisfies the 803 rpm  
requirement in the Drive Data tables. For the 524A-C120  
unit, the Standard Drive table on shows an rpm range of  
666-863. Since the rpm required is 803, the standard drive  
satisfies the requirement and should be used. Select the  
standard motor and standard drive combination (option  
code GC or ED).  
7
CONTROLS  
the cooling continues to decrease, stage one of the thermostat  
OPERATING SEQUENCES  
opens causing compressor no. 1 and outdoor-fan motor no. 1 to  
shut down. The LLS valve for each compressor will close when  
the associated compressor stops, minimizing the potential for  
refrigerant migration during the off cycle.  
569D072-120, 576C120 — At start-up, the thermostat calls for  
cooling. With all safety devices satisfied, the compressor  
contactor and fan contactor energize, causing the compressor  
and outdoor-fan motor to operate. Thermostat contacts  
energize, allowing the field-supplied and field-installed indoor-  
fan contactor to function. A field-supplied and field-installed liq-  
uid line valve also opens, allowing the system to function in  
Cooling mode. As cooling demand is satisfied, the thermostat  
contacts break, deenergizing the contactor and causing the  
system to shut off. The liquid line solenoid valve closes, mini-  
mizing the potential for refrigerant migration. The compressor  
does not restart until the thermostat again calls for cooling. The  
system is protected with a safety circuit so that the system will  
not start if a fault exists (i.e., high or low pressure fault). To reset  
the safety circuit, set the thermostat to eliminate the cooling  
demand, then return to original set point. This should be done  
only once, and if system shuts down due to the same fault,  
determine the problem before attempting to restart the system.  
The indoor-fan motor will stop if the thermostat is set to AUTO  
and will continue to operate if the thermostat is set to CONT.  
Each compressor is protected with a Cycle-LOCTM device so  
that the compressor will not operate if there is a high-pressure  
fault, low pressure fault, or a compressor is off due to internal  
line break overcurrent/overtemperature protection. To reset the  
Cycle-LOC device, set the thermostat higher to remove the  
cooling demand, then return to the original set point. This  
should be done only once. If the system shuts down with the  
same fault, the cause for the fault should be determined and  
corrected before the a Cycle-LOC device is reset again.  
566E150-240 — At start-up, when the thermostat calls for first  
stage cooling and all safety devices are satisfied, the compres-  
sor contactor (C1) energizes causing compressor no. 1 and fan  
motor no. 1 to start. Fan motor no. 2 will start when the fan  
cycling pressure switch (FCPS) closes as discharge pressure  
builds (refer to physical data table for FCPS specifications).  
With the indoor-fan contactor wired to TB2-4 and TB2-9  
contacts on the terminal block, the indoor fan will also start with  
the compressor. The liquid line solenoid (LLS) valve will open  
when compressor no. 1 starts, allowing refrigerant to flow in the  
system.  
566D150-240 — When the first stage of cooling thermostat  
closes, the timer starts. After approximately 3 seconds, the  
timer activates the compressor and fan motor no. 1 contactors.  
When the liquid pressure builds to approximately 257 psig, fan  
motor no. 2 is energized.  
When there is demand for additional cooling capacity, the  
second stage of the cooling thermostat closes, energizing a  
field-supplied liquid line solenoid (LLS) valve, which opens. This  
increases the suction pressure, causing the compressor to  
operate at higher capacity (compressor loads).  
When the thermostat calls for stage two cooling, compressor  
contactor no. 2 (C2) energizes causing compressor no. 2 to  
start. As the cooling demand decreases, stage two on the  
thermostat opens, causing compressor no. 2 to shut down. As  
the cooling continues to decrease, stage one of the thermostat  
opens causing compressor no. 1 and outdoor-fan motor to shut  
down. The LLS valve for each compressor will close when the  
associated compressor stops, minimizing the potential for  
refrigerant migration during the off cycle.  
When the fan switch is set at AUTO, the indoor-air fan cycles  
with the compressor. When the switch is set at CONT, the  
indoor-air fan runs continuously.  
At shutdown, the Time Guard II timer prevents the compressor  
from restarting for approximately 5 minutes.  
In addition, an LLS valve wired in parallel with the compressor  
contactor coil shuts off the liquid line to prevent refrigerant  
migration back to the compressor during the off cycle.  
The indoor-fan motor will stop if the thermostat is set to AUTO  
and will continue to operate if the thermostat is set on CONT.  
Each compressor is controlled by the thermostat so they will not  
start until there is a demand from the thermostat. Each  
compressor is protected with a Cycle-LOC device so that the  
compressor will not operate if there is a high-pressure fault,  
low-pressure fault, or compressor is off due to internal line  
break overcurrent/overtemperature protection. To reset the a  
Cycle-LOC device, set the thermostat higher to remove the  
cooling demand, then return to the original set point. This  
should be done only once. If the system shuts down with the  
same fault, the cause for the fault should be determined and  
corrected before the a Cycle-LOC device is reset again.  
569F120 — When the thermostat calls for stage one cooling at  
start-up, and all safety devices are satisfied, the compressor  
contactor no. 1 (C1) energizes causing compressor no. 1 and  
outdoor-fan motor no. 1 to start (the indoor-fan contactor should  
be wired to start at the same time as the compressor). The  
liquid line solenoid (LLS) valve will open when compressor no. 1  
starts, allowing refrigerant to flow in the system.  
When the thermostat calls for stage two cooling, compressor  
contactor no. 2 (C2) energizes causing compressor no. 2 and  
outdoor-fan motor no. 2 to start. As the cooling demand  
decreases, stage two on the thermostat opens, causing  
compressor no. 2 and outdoor-fan motor no. 2 to shut down. As  
8
TYPICAL WIRING SCHEMATICS  
NOTES:  
1. If any of the original wire furnished must be  
replaced, it must be replaced with type 90° C  
wire or its equivalent.  
2. Thermostat: HH07AT170, 172, 174  
2783  
&
P272-  
Subbase: HH93AZ176, 178 & P272-1882, 1883  
or HH93AZ177 & 179.  
3. Sealed VA for IFC and LLSV is not to exceed  
22.  
4. Use copper conductors only.  
5. TRAN is wired for 230 v unit. If unit is to be run  
with 200 v power supply, disconnect BLK wire  
from 230 v tap and connect to 200 v tap.  
6. If TRAN is wired for 460-3-60 v and unit is to be  
run with 400-3-50 v power supply, disconnect  
BLK wire from 460 v tap and connect to 400 v  
tap.  
7. Three-phase motors are protected under pri-  
mary single phasing conditions.  
CB  
MUST  
TRIP  
AMPS  
VOLTAGE  
RATING  
Mfg. Part No.  
Potter & Brumfield  
W28X-1024-3.2  
24 V  
3.2  
LEGEND  
AHA  
C
Adjustable Heat Anticipator  
Contactor, Compressor  
Capacitor  
LLSV  
LPS  
NEC  
OFM  
QT  
Liquid Line Solenoid Valve  
Low-Pressure Switch  
National Electrical Code  
Outdoor-Fan Motor  
Quadruple Terminal  
Terminal Block  
Thermostat-Cooling  
Thermostat-Heating  
Transformer  
Terminal (Marked)  
Terminal (Unmarked)  
Terminal Block  
CAP  
CB  
Circuit Breaker  
CC  
CH  
Cooling Compensator  
Crankcase Heater  
Compressor Lockout  
Compressor Motor  
Discharge Gas Thermostat  
Equipment  
Ground  
High-Pressure Switch  
Indoor-Fan Contactor  
Splice  
Factory Wiring  
Field Control Wiring  
Field Power Wiring  
Accessory or Optional Wiring  
TB  
CLO  
COMP  
DGT  
EQUIP  
GND  
HPS  
IFC  
TC  
TH  
— —  
TRAN  
Field Splice  
Marked Wire  
To Indicate Common Potential  
Only, Not Represent Wiring  
569D090, 208/230-3-360 and 460-3-60 Units  
9
TYPICAL WIRING SCHEMATICS (cont)  
LEGEND  
AHA  
C
Adjustable Heat  
Anticipator  
Contactor,  
Compressor  
Capacitor  
CAP  
CB  
Circuit Breaker  
Cooling Compensator  
Crankcase Heater  
Compressor Motor  
Compressor Over  
Temperature Protection  
Equipment  
CC  
CH  
COMP  
COTP  
EQUIP  
GND  
HPS  
IFC  
LLSV  
Ground  
High-Pressure Switch  
Indoor-Fan Contactor  
Liquid Line Solenoid  
Valve  
LPS  
NEC  
OFM  
OL  
Low-Pressure Switch  
National Electrical Code  
Outdoor-Fan Motor  
Overload Relay  
Relay  
Terminal Block  
Thermostat-Cooling  
Thermostat-Heating  
Transformer  
R
TB  
TC  
TH  
TRAN  
Field Splice  
Marked Wire  
Terminal (Marked)  
Terminal (Unmarked)  
Terminal Block  
Splice  
Factory Wiring  
Field Control Wiring  
Field Power Wiring  
— —  
Accessory or  
Optional Wiring  
To Indicates Common  
Potential Only, Not  
Represent Wiring  
576C120, 208/230-3-60 and 460-3-60 Units  
10  
MODEL NUMBER NOMENCLATURE  
569D 072 000 – –  
P
X
569D Commercial Air-Cooled Condensing  
Unit With Scroll Compressor  
Factory-Installed Options*  
569F Dual Circuit Commercial Air-Cooled  
Condensing Unit With Scroll Compressor  
Voltage Designation  
E — 460-3-60  
P — 208/230-3-60  
T
— 575-3-60  
Heating  
X — None  
Nominal Tons Cooling  
072 — 6 (569D Only)  
090 — 7-1/2 (569D Only)  
120 — 10 (569D, 569F)  
Heating Capacity  
000 — No Heat  
576C  
P
X
120 000 – –  
576C Commercial Air-Cooled Condensing  
Factory-Installed Options*  
Unit With Semi-Hermetic Compressor  
Heating Capacity  
000 — No Heat  
Voltage Designation  
E — 460-3-60  
P — 208/230-3-60  
T — 575-3-60  
Nominal Tons Cooling  
120 — 10  
Heating  
X — None  
*Contact your local representative for more details.  
Quality Assurance  
Certified to ISO 9001:2000  
11  
PHYSICAL DATA  
569D072-120, 576C120, 569F120 UNITS  
UNIT  
569D072  
569D090  
71/2  
569D120  
576C120  
569F120  
NOMINAL CAPACITY (tons)  
6
10  
10  
10  
OPERATING WEIGHT (lb)  
Aluminum Coils (Standard)  
Copper Coils (Optional)  
300  
352  
383  
484  
430  
531  
575  
676  
488  
589  
R-22  
22  
2.0  
RREFRIGERANT TYPE*  
Operating Charge, Typical (lb)†  
Shipping Charge (lb)  
12  
2.0  
20  
2.0  
24  
2.0  
11/Circuit  
2.0  
COMPRESSOR  
Type  
Qty...Model  
Oil Charge (oz)  
No. Cylinders  
Speed (rpm)  
Scroll  
1...SR_94  
90  
Reciprocating  
Scroll  
2...SR_60  
72 (ea)  
N/A  
1...SR_68  
88  
1...ZR125  
110  
1...06DH824  
128  
6
1750  
N/A  
3500  
3500  
CONDENSER FAN  
Qty...Rpm  
2...850  
2...1100  
2...1100  
2...1100  
2...1100  
1
/
1
/
1
/
1
/
1
/
Motor HP (rpm)  
Diameter  
8
22  
5400  
340  
4
4
4
22  
6500  
570  
4
22  
6500  
570  
22  
6500  
570  
Nominal Airflow (Cfm Total)  
Watts (Total)  
CONDENSER COIL (Qty)  
Face Area (sq ft total)  
Rows...Fins/in.  
2
2
29.2  
2...17  
17.1 (ea)  
29.2  
2...17  
34.2  
29.2  
2...17  
34.2  
1...17  
17.3  
2...17  
34.2  
Storage Capacity (lb)**  
CONTROLS  
Pressurestat Settings (psig)  
High Cutout  
Cut-in  
Low Cutout  
Cut-in  
428 10  
320 20  
428 10  
320 20  
428 10  
320 20  
27  
44  
3
5
27  
44  
3
5
27  
44  
3
5
DISCHARGE GAS THERMOSTAT (°F)  
Cutout  
Cut-in  
2
2
270  
9
190 13  
PRESSURE RELIEF  
Location  
Temperature (F)  
Suction Line  
200  
PIPING CONNECTIONS (in. ODM)  
Qty...Suction  
Qty...Liquid  
1...11/8  
1...3/8  
1...11/8  
1...3/8  
1...13/8  
1...1/2  
1...13/8  
1...1/2  
2...11/8  
2...3/8  
*Unit is factory-supplied with holding charge only.  
NOTE: Unit 576C120 has one step of unloading. Full load is at 100% of  
capacity, and one step of unloading is 67% capacity. Unit 576C120 has  
the following unloader settings: load is 70 1 psig and unload is 60  
2 psig.  
Typical operating charge with 25 ft of interconnecting piping.  
**Storage capacity of condenser coil with coil 80% full of liquid R-22 at  
95 F.  
12  
DIMENSIONS  
ALUMINUM COIL  
Standard Unit Weight Corner W Corner X Corner Y Corner Z  
ELECTRICAL  
UNIT  
CHARACTERISTICS  
UNIT  
Center of Gravity  
lb kg X mm [in.] Y mm [in.]  
569D072  
569D090  
569D120  
576C120  
208/230-3-60, 460-3-60, 575-3-60  
208/230-3-60, 460-3-60, 575-3-60  
208/230-3-60, 460-3-60, 575-3-60  
208/230-3-60, 460-3-60, 575-3-60  
lb  
kg  
lb  
kg  
lb kg lb kg  
569D072  
569D090  
569D120  
576C120  
300  
383  
430  
575  
136  
174  
195  
261  
62 28 103 47 62 28  
86 39 123 56 85 39  
72 33 831.9 [32.75] 641.4 [25.25]  
89 40 822.3 [32.38] 635.0 [25.00]  
84 38 166 75 66 30 114 52 812.8 [32.00] 676.3 [26.63]  
55 25 265 120 88 40 167 76 927.1 [36.50] 647.7 [25.50]  
SERVICE VALVE CONNECTIONS  
Suction  
Liquid  
Unit  
mm [in.]  
mm [in.]  
9.5 [3/8]  
569D072  
569D090  
569D120  
576C120  
28.6 [11/8]  
28.6 [11/8]  
34.9 [13/8]  
34.9 [13/8]  
9.5 [3/8]  
12.7 [1/2]  
12.7 [1/2]  
569D072-120, 576C120  
13  
DIMENSIONS (cont)  
OUTDOOR COIL  
CORNER “A”  
CORNER “B”  
1162.7  
[45.78]  
Y
OUTDOOR COIL  
CORNER “C”  
X
CORNER “D”  
ACCESS PANEL  
ELECTRICAL DISCONNECT  
LOCATION  
TOP VIEW  
O 34.5 [1.36]  
LIQUID  
POWER ENTRY  
CONNECTION  
(SEE CHART  
FOR SIZE)  
WITH 50.0/58.0/65.0 K.O.  
CONTROL BOX  
ACCESS PANEL  
CONVENIENCE  
OUTLET LOCATION  
OUTDOOR  
COIL  
SUCTION  
CONNECTION  
(SEE CHART  
FOR SIZE)  
OUTDOOR  
COIL  
OUTDOOR  
COIL  
ACCESS  
PANEL  
872.8  
[34.36]  
582.5  
[22.93]  
BOTTOM  
OF UNIT  
341.5  
287.8  
226.9  
[13.45]  
167.5  
[6.59]  
172.9  
[6.81]  
[11.33]  
[8.93]  
637.9  
LIQUID CONNECTION  
(SEE CHART FOR SIZE)  
111.7  
116.7  
[4.59]  
[25.11]  
644.6  
[25.38]  
RIGHT SIDE VIEW  
FORK TRUCK SLOTS  
(3 SIDES ONLY)  
[4.40]  
O 22.0 [0.87] FIELD  
ENTRY SERVICE PORT  
1509.3  
[59.42]  
FRONT VIEW  
LEFT SIDE VIEW  
OUTDOOR  
COIL  
COMPRESSOR  
ACCESS PANEL  
(in.)  
(in.)  
569F120  
REAR VIEW  
ALUMINUM COIL  
Std. Unit  
Wt.  
Corner  
A
Corner  
B
Corner  
C
Corner  
Center of  
Gravity  
ELECTRICAL  
CHARACTERISTICS  
UNIT  
D
X
Y
lb  
kg  
lb kg lb kg lb kg lb kg  
mm [in.]  
mm [in.]  
208/230-3-60,  
400/460-3-50/60,  
575-3-60  
873.8  
[34.4]  
591.8  
[23.3]  
569F120  
488 221 102 46 143 65 139 63 104 47  
569F120  
14  
PERFORMANCE DATA  
CONDENSING UNIT RATINGS  
569D072  
SST (F)  
576C120  
Air Temperature Entering Condenser (F)  
Air Temperature Entering Condenser (F)  
SST (F)  
80  
85  
95  
100  
105  
115  
80  
85  
95  
100  
105  
115  
TC  
53.6  
4.24  
101.0  
59.1  
4.33  
102.0  
64.9  
4.42  
104.0  
71.0  
4.53  
106.0  
77.4  
4.65  
107.0  
84.2  
4.78  
109.0  
52.3  
4.49  
106.0  
49.4  
5.02  
115.0  
48.0  
5.31  
120.0  
46.5  
5.60  
125.0  
43.6  
6.24  
135.0  
48.3  
6.33  
136.0  
53.4  
6.43  
138.0  
58.7  
6.55  
139.0  
64.3  
6.68  
141.0  
70.2  
6.81  
142.0  
TC  
89.0  
7.52  
103.0  
85.1  
7.79  
108.0  
77.4  
8.29  
118.0  
73.6  
8.49  
123.0  
69.7  
8.70  
128.0  
62.2  
9.02  
138.0  
25  
30  
kW  
SDT  
25  
30  
35  
40  
45  
50  
kW  
SDT  
TC  
kW  
SDT  
57.6  
4.57  
107.0  
54.6  
5.10  
117.0  
53.0  
5.39  
122.0  
51.5  
5.69  
126.0  
TC  
kW  
SDT  
101.0  
7.76  
104.0  
96.6  
8.07  
108.0  
88.5  
8.64  
118.0  
84.4  
8.89  
123.0  
80.3  
9.14  
128.0  
72.2  
9.55  
138.0  
TC  
kW  
SDT  
63.3  
4.67  
109.0  
60.1  
5.20  
118.0  
58.4  
5.49  
123.0  
56.7  
5.79  
128.0  
TC  
kW  
SDT  
113.0  
8.01  
105.0  
109.0  
8.36  
109.0  
100.0  
8.99  
119.0  
95.8  
9.28  
124.0  
91.5  
9.55  
128.0  
83.0  
10.05  
138.0  
35  
TC  
kW  
SDT  
69.3  
4.77  
110.0  
65.8  
5.31  
120.0  
64.1  
5.60  
125.0  
62.3  
5.90  
129.0  
40  
TC  
kW  
SDT  
125.0  
8.29  
106.0  
121.0  
8.66  
111.0  
112.0  
9.35  
120.0  
107.0  
9.65  
125.0  
103.0  
9.95  
129.0  
94.1  
10.55  
139.0  
TC  
kW  
SDT  
75.6  
4.89  
112.0  
71.9  
5.43  
122.0  
70.1  
5.72  
126.0  
68.2  
6.02  
131.0  
45  
TC  
kW  
SDT  
138.0  
8.57  
108.0  
133.0  
8.97  
113.0  
124.0  
9.75  
122.0  
119.0  
10.05  
127.0  
115.0  
10.50  
131.0  
106.0  
11.05  
140.0  
TC  
kW  
SDT  
82.3  
5.03  
114.0  
78.4  
5.56  
123.0  
76.4  
5.86  
128.0  
74.3  
6.16  
133.0  
50  
TC  
kW  
SDT  
152.0  
8.85  
111.0  
147.0  
9.28  
115.0  
137.0  
10.15  
124.0  
132.0  
10.45  
129.0  
127.0  
10.90  
133.0  
117.0  
11.55  
142.0  
569D090  
Air Temperature Entering Condenser (F)  
SST (F)  
569F120  
80  
85  
95  
100  
105  
115  
TC  
73.9  
5.81  
98.6  
82.0  
5.88  
99.6  
90.4  
5.98  
101.0  
99.2  
6.09  
103.0  
109.0  
6.22  
104.0  
71.7  
6.14  
67.0  
6.84  
64.6  
7.21  
62.1  
7.58  
57.0  
8.36  
Air Temperature Entering Condenser (F)  
SST (F)  
25  
30  
kW  
SDT  
80  
85  
95  
100  
105  
115  
104.0  
114.0  
118.0  
123.0  
133.0  
TC  
90.5  
7.75  
100.0  
87.9  
8.17  
105.0  
82.6  
9.05  
115.0  
79.8  
9.52  
120.0  
76.9  
10.00  
125.0  
71.1  
11.00  
135.0  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
79.7  
6.21  
104.0  
88.0  
6.31  
106.0  
96.7  
6.43  
107.0  
106.0  
6.56  
109.0  
74.9  
6.90  
114.0  
83.0  
7.02  
115.0  
91.4  
7.14  
117.0  
100.0  
7.28  
119.0  
72.4  
7.28  
119.0  
80.4  
7.40  
120.0  
88.7  
7.53  
122.0  
97.4  
7.68  
123.0  
69.9  
7.65  
124.0  
77.8  
7.78  
125.0  
85.9  
7.92  
126.0  
94.5  
8.07  
128.0  
64.7  
8.46  
134.0  
72.4  
8.59  
135.0  
80.3  
8.74  
136.0  
88.6  
8.91  
138.0  
25  
30  
35  
40  
45  
50  
kW  
SDT  
TC  
kW  
SDT  
100.0  
7.79  
101.0  
97.8  
8.21  
106.0  
92.2  
9.09  
116.0  
89.3  
9.57  
120.0  
86.3  
10.10  
125.0  
80.2  
11.10  
135.0  
35  
TC  
kW  
SDT  
111.0  
7.89  
102.0  
108.0  
8.30  
107.0  
102.0  
9.18  
116.0  
99.0  
9.66  
121.0  
96.0  
10.10  
126.0  
89.7  
11.20  
136.0  
40  
TC  
kW  
SDT  
122.0  
8.01  
104.0  
119.0  
8.42  
108.0  
112.0  
9.31  
118.0  
109.0  
9.79  
123.0  
106.0  
10.30  
127.0  
99.4  
11.30  
137.0  
45  
TC  
kW  
SDT  
118.0  
6.36  
106.0  
116.0  
6.70  
111.0  
110.0  
7.43  
120.0  
107.0  
7.83  
125.0  
104.0  
8.23  
130.0  
97.2  
9.09  
139.0  
TC  
kW  
SDT  
133.0  
8.15  
105.0  
130.0  
8.57  
110.0  
123.0  
9.46  
120.0  
120.0  
9.95  
124.0  
116.0  
10.40  
129.0  
109.0  
11.50  
138.0  
50  
TC  
kW  
SDT  
145.0  
8.30  
107.0  
141.0  
8.72  
112.0  
134.0  
9.63  
121.0  
131.0  
10.10  
126.0  
127.0  
10.60  
131.0  
120.0  
11.70  
140.0  
569D120  
Air Temperature Entering Condenser (F)  
SST (F)  
80  
85  
95  
100  
105  
115  
LEGEND  
TC  
102.0  
8.04  
99.3  
8.38  
93.8  
9.13  
90.9  
9.55  
88.1  
9.95  
81.9  
10.85  
136.0  
kW  
Compressor Power  
25  
30  
35  
40  
45  
50  
kW  
SDT  
SDT  
SST  
TC  
Saturated Discharge Temperature at Compressor (F)  
Saturated Suction Temperature (F)  
101.0  
106.0  
116.0  
121.0  
126.0  
Gross Cooling Capacity (1000 Btuh)  
TC  
kW  
SDT  
112.0  
8.26  
103.0  
109.0  
8.60  
107.0  
103.0  
9.31  
117.0  
99.8  
9.65  
12.02  
96.7  
10.05  
127.0  
90.3  
10.95  
136.0  
TC  
kW  
SDT  
122.0  
8.52  
104.0  
119.0  
8.85  
109.0  
113.0  
9.55  
118.0  
109.0  
9.95  
123.0  
106.0  
10.35  
128.0  
99.0  
11.15  
137.0  
TC  
kW  
SDT  
133.0  
8.81  
106.0  
130.0  
9.15  
110.0  
123.0  
9.85  
120.0  
119.0  
10.25  
125.0  
115.0  
10.55  
129.0  
108.0  
11.35  
139.0  
TC  
kW  
SDT  
144.0  
9.12  
108.0  
141.0  
9.45  
112.0  
133.0  
10.15  
122.0  
130.0  
10.55  
126.0  
126.0  
10.85  
131.0  
118.0  
11.65  
140.0  
TC  
kW  
SDT  
156.0  
9.45  
109.0  
152.0  
9.85  
114.0  
145.0  
10.55  
123.0  
141.0  
10.85  
128.0  
137.0  
11.25  
133.0  
128.0  
12.05  
142.0  
15  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS*  
UNIT 569D072  
569D072/524A-C072 WITH HIGH-CAPACITY 4-ROW COIL  
Evaporator Air — Cfm  
2400  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
1800  
3000  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
66.0  
66.0  
4.45  
65.1  
65.1  
4.72  
68.6  
60.9  
4.49  
67.5  
60.3  
4.76  
74.3  
51.0  
4.60  
73.1  
50.5  
4.87  
80.7  
40.8  
4.71  
79.3  
40.3  
4.99  
72.0  
72.0  
4.55  
71.0  
71.0  
4.83  
72.6  
70.5  
4.57  
71.4  
69.8  
4.84  
77.7  
58.6  
4.66  
76.3  
58.1  
4.93  
84.1  
45.5  
4.78  
82.6  
45.0  
5.05  
76.2  
76.2  
4.63  
75.0  
75.0  
4.91  
76.2  
76.2  
4.63  
75.1  
75.1  
4.90  
79.9  
65.7  
4.70  
78.5  
65.2  
4.97  
86.2  
50.0  
4.82  
84.6  
49.5  
5.09  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
63.3  
63.3  
5.26  
65.2  
59.2  
5.30  
70.6  
49.4  
5.41  
76.7  
39.3  
5.53  
68.9  
68.9  
5.37  
69.1  
68.3  
5.38  
73.6  
57.0  
5.47  
79.7  
44.0  
5.60  
72.8  
72.8  
5.45  
72.8  
72.8  
5.45  
75.7  
64.0  
5.51  
81.6  
48.5  
5.64  
95  
TC  
62.3  
62.3  
5.57  
61.3  
61.3  
5.88  
59.3  
59.3  
6.51  
64.0  
58.6  
5.61  
62.8  
58.0  
5.91  
60.5  
56.8  
6.53  
69.2  
48.9  
5.71  
67.9  
48.3  
6.02  
65.2  
47.2  
6.63  
75.2  
38.8  
5.84  
73.8  
38.2  
6.15  
70.9  
37.2  
6.77  
67.7  
67.7  
5.68  
66.6  
66.6  
5.99  
64.4  
64.4  
6.61  
67.9  
67.4  
5.68  
66.7  
66.6  
5.99  
64.3  
64.3  
6.61  
72.2  
56.5  
5.78  
70.7  
55.9  
6.08  
67.8  
54.8  
6.70  
78.2  
43.5  
5.90  
76.6  
42.9  
6.21  
73.5  
41.9  
6.83  
71.5  
71.5  
5.76  
70.3  
70.3  
6.07  
67.9  
67.9  
6.69  
71.5  
71.5  
5.76  
70.3  
70.3  
6.08  
67.9  
67.9  
6.70  
74.2  
63.4  
5.82  
72.7  
62.8  
6.12  
69.7  
61.6  
6.74  
80.0  
47.9  
5.95  
78.4  
47.4  
6.26  
75.2  
46.4  
6.88  
100  
105  
115  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
569D072/524A-B072 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
2400  
Evaporator Air — Ewb (F)  
1800  
3000  
Air Entering  
Condenser  
(Edb)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
63.4  
63.4  
4.40  
62.5  
62.5  
4.67  
66.1  
58.4  
4.45  
65.1  
57.9  
4.72  
71.7  
49.0  
4.55  
70.5  
48.5  
4.82  
77.8  
39.2  
4.66  
76.6  
38.8  
4.93  
69.0  
69.0  
4.50  
68.0  
68.0  
4.77  
69.8  
67.2  
4.52  
68.7  
66.6  
4.79  
74.9  
56.0  
4.60  
73.6  
55.5  
4.88  
81.1  
43.6  
4.72  
79.7  
43.1  
4.99  
72.9  
72.9  
4.57  
71.9  
71.9  
4.84  
72.9  
72.9  
4.57  
71.9  
71.9  
4.84  
76.9  
62.5  
4.64  
75.6  
62.0  
4.91  
83.1  
47.6  
4.76  
81.7  
47.2  
5.03  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
60.8  
60.8  
5.22  
62.9  
56.8  
5.26  
68.2  
47.5  
5.36  
74.1  
37.9  
5.48  
66.1  
66.1  
5.32  
66.5  
65.2  
5.33  
71.1  
54.6  
5.42  
77.0  
42.2  
5.54  
69.7  
69.7  
5.39  
69.8  
69.8  
5.39  
73.1  
60.9  
5.46  
78.9  
46.2  
5.58  
95  
TC  
59.9  
59.9  
5.53  
59.0  
59.0  
5.84  
57.1  
57.1  
6.46  
61.8  
56.3  
5.56  
60.7  
55.7  
5.87  
58.4  
54.6  
6.48  
67.0  
47.0  
5.67  
65.7  
46.5  
5.98  
63.3  
45.5  
6.59  
72.8  
37.4  
5.79  
71.4  
36.9  
6.10  
68.7  
35.9  
6.72  
65.1  
65.1  
5.63  
64.0  
64.0  
5.94  
61.9  
61.9  
6.57  
65.4  
64.4  
5.63  
64.2  
63.7  
5.94  
61.9  
61.9  
6.56  
69.8  
54.0  
5.73  
68.5  
53.5  
6.03  
65.8  
52.4  
6.65  
75.6  
41.7  
5.85  
74.1  
41.2  
6.16  
71.3  
40.2  
6.78  
68.6  
68.6  
5.70  
67.5  
67.5  
6.01  
65.2  
65.2  
6.64  
68.6  
68.6  
5.70  
67.5  
67.5  
6.01  
65.2  
65.2  
6.63  
71.7  
60.4  
5.76  
70.3  
59.8  
6.07  
67.4  
58.7  
6.68  
77.4  
45.7  
5.89  
75.9  
45.2  
6.20  
72.9  
44.2  
6.82  
100  
105  
115  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
*Combinations on this page are ENERGY STAR® compliant.  
16  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS (cont)  
UNIT 569D072 (cont)  
569D072/524A-C090 WITH HIGH-CAPACITY 4-ROW COIL*  
Evaporator Air — Cfm  
3000  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
2400  
3750  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
71.9  
71.9  
4.55  
70.9  
70.9  
4.83  
72.9  
69.5  
4.57  
71.7  
68.8  
4.84  
78.3  
57.7  
4.67  
76.9  
57.2  
4.94  
84.8  
45.1  
4.79  
83.3  
44.6  
5.07  
77.7  
77.7  
4.66  
76.5  
76.5  
4.93  
77.7  
77.7  
4.66  
76.5  
76.5  
4.93  
81.3  
67.0  
4.73  
79.8  
66.4  
5.00  
87.6  
50.9  
4.85  
86.1  
50.3  
5.12  
81.6  
81.6  
4.73  
80.3  
80.3  
5.01  
81.6  
81.6  
4.73  
80.3  
80.3  
5.01  
83.4  
75.2  
4.77  
81.9  
74.6  
5.04  
89.4  
56.4  
4.89  
87.8  
55.9  
5.16  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
68.8  
68.8  
5.37  
69.3  
67.5  
5.38  
74.2  
56.1  
5.48  
80.4  
43.5  
5.61  
74.1  
74.1  
5.48  
74.1  
74.1  
5.48  
76.9  
65.2  
5.54  
82.9  
49.3  
5.66  
77.7  
77.7  
5.55  
77.8  
77.8  
5.56  
79.0  
73.3  
5.58  
84.5  
54.8  
5.70  
95  
TC  
67.7  
67.7  
5.68  
66.5  
66.5  
5.99  
64.3  
64.3  
6.61  
68.0  
66.8  
5.69  
66.8  
66.0  
6.00  
64.3  
64.3  
6.61  
72.8  
55.5  
5.79  
71.3  
54.9  
6.09  
68.4  
53.8  
6.71  
78.8  
43.0  
5.92  
77.3  
42.5  
6.23  
74.2  
41.4  
6.85  
72.8  
72.8  
5.79  
71.6  
71.6  
6.10  
69.0  
69.0  
6.73  
72.9  
72.9  
5.79  
71.6  
71.6  
6.10  
69.1  
69.1  
6.73  
75.4  
64.6  
5.85  
73.9  
64.0  
6.15  
70.8  
62.8  
6.77  
81.3  
48.8  
5.97  
79.6  
48.2  
6.28  
76.2  
47.1  
6.90  
76.4  
76.4  
5.87  
75.0  
75.0  
6.18  
72.3  
72.3  
6.81  
76.4  
76.4  
5.87  
75.0  
75.0  
6.18  
72.3  
72.3  
6.8  
77.4  
72.5  
5.89  
75.9  
71.8  
6.20  
72.7  
70.3  
6.81  
82.8  
54.3  
6.01  
81.1  
53.7  
6.32  
77.7  
52.6  
6.94  
100  
105  
115  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
569D072/524A-B090 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
3000  
Evaporator Air — Ewb (F)  
2400  
3750  
Air Entering  
Condenser  
(Edb)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
68.4  
68.4  
4.49  
67.4  
67.4  
4.76  
69.5  
65.8  
4.51  
68.4  
65.2  
4.78  
74.8  
54.8  
4.61  
73.6  
54.3  
4.88  
81.0  
42.9  
4.72  
79.7  
42.4  
5.00  
73.6  
73.6  
4.58  
72.6  
72.6  
4.86  
73.6  
73.6  
4.58  
72.6  
72.6  
4.86  
77.6  
63.1  
4.65  
76.3  
62.6  
4.93  
83.8  
48.1  
4.77  
82.4  
47.6  
5.05  
77.3  
77.3  
4.65  
76.1  
76.1  
4.92  
77.3  
77.3  
4.65  
76.1  
76.1  
4.92  
79.5  
70.4  
4.69  
78.2  
69.8  
4.96  
85.5  
52.9  
4.81  
84.0  
52.4  
5.08  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
65.5  
65.5  
5.31  
66.2  
64.0  
5.32  
71.1  
53.3  
5.42  
77.1  
41.5  
5.54  
70.4  
70.4  
5.40  
70.5  
70.5  
5.40  
73.7  
61.5  
5.47  
79.5  
46.6  
5.59  
73.8  
73.8  
5.47  
73.8  
73.8  
5.47  
75.5  
68.7  
5.51  
81.1  
51.4  
5.62  
95  
TC  
64.5  
64.5  
5.62  
63.4  
63.4  
5.93  
61.4  
61.4  
6.55  
65.1  
63.3  
5.63  
63.9  
62.5  
5.94  
61.6  
61.1  
6.55  
69.7  
52.8  
5.72  
68.4  
52.2  
6.03  
65.8  
51.2  
6.64  
75.6  
41.0  
5.85  
74.1  
40.5  
6.16  
71.2  
39.4  
6.78  
69.3  
69.3  
5.71  
68.1  
68.1  
6.03  
65.9  
65.9  
6.65  
69.3  
69.3  
5.72  
68.1  
68.1  
6.03  
65.8  
65.8  
6.65  
72.3  
60.9  
5.78  
70.9  
60.4  
6.08  
68.0  
59.2  
6.70  
78.0  
46.1  
5.90  
76.5  
45.6  
6.21  
73.4  
44.6  
6.83  
72.6  
72.6  
5.78  
71.4  
71.4  
6.10  
68.9  
68.9  
6.72  
72.6  
72.6  
5.78  
71.4  
71.4  
6.10  
68.9  
68.9  
6.73  
74.0  
68.0  
5.82  
72.6  
67.3  
6.12  
69.7  
66.0  
6.74  
79.5  
50.9  
5.93  
77.9  
50.4  
6.24  
74.8  
49.4  
6.86  
100  
105  
115  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
*This combination is ENERGY STAR® compliant.  
17  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS (cont)  
UNIT 569D090  
569D090/524A-C072 WITH HIGH-CAPACITY 4-ROW COIL*  
Evaporator Air — Cfm  
2400  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
1800  
3000  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
78.9  
77.9  
5.75  
77.6  
77.0  
6.10  
85.1  
69.0  
5.78  
83.6  
68.3  
6.13  
92.8  
59.0  
5.85  
91.3  
58.3  
6.20  
101.0  
48.7  
5.94  
99.3  
48.0  
6.30  
87.0  
87.0  
5.79  
85.7  
85.7  
6.14  
90.7  
79.9  
5.83  
89.2  
79.1  
6.18  
98.3  
66.9  
5.91  
96.6  
66.3  
6.26  
106.0  
53.6  
6.01  
105.0  
52.9  
6.37  
93.0  
93.0  
5.85  
91.6  
91.6  
6.20  
94.7  
89.3  
5.87  
93.1  
88.4  
6.22  
102.0  
74.2  
5.96  
100.0  
73.5  
6.31  
110.0  
58.0  
6.06  
108.0  
57.4  
6.41  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
75.1  
75.1  
6.80  
80.8  
66.8  
6.82  
88.3  
56.9  
6.90  
96.1  
46.7  
7.00  
83.2  
83.2  
6.85  
86.1  
77.6  
6.87  
93.3  
64.9  
6.96  
101.0  
51.6  
7.08  
88.9  
88.9  
6.91  
89.9  
86.7  
6.92  
96.5  
72.2  
7.01  
104.0  
56.1  
7.12  
95  
TC  
73.9  
73.8  
7.20  
72.6  
72.6  
7.59  
70.1  
70.1  
8.38  
79.2  
66.0  
7.21  
77.6  
65.3  
7.60  
74.5  
63.7  
8.38  
86.6  
56.2  
7.29  
85.0  
55.5  
7.68  
81.7  
54.0  
8.47  
94.4  
46.1  
7.40  
92.6  
45.4  
7.79  
89.1  
44.0  
8.58  
81.8  
81.8  
7.24  
80.4  
80.4  
7.64  
77.7  
77.7  
8.43  
84.4  
76.7  
7.26  
82.7  
75.9  
7.66  
79.4  
74.3  
8.44  
91.4  
64.1  
7.36  
89.6  
63.4  
7.75  
86.0  
61.9  
8.53  
99.2  
50.9  
7.47  
97.3  
50.2  
7.87  
93.5  
48.8  
8.66  
87.4  
87.4  
7.30  
85.9  
85.9  
7.70  
82.9  
82.9  
8.48  
88.2  
85.7  
7.31  
86.5  
84.7  
7.71  
83.1  
82.7  
8.49  
94.5  
71.4  
7.40  
92.6  
70.7  
7.80  
88.8  
69.2  
8.58  
102.0  
55.3  
7.52  
100.0  
54.6  
7.92  
96.2  
53.2  
8.71  
100  
105  
115  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
569D090/524A-B072 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
1800  
2400  
3000  
Air Entering  
Condenser  
(Edb)  
Evaporator Air — Ewb (F)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
75.3  
74.3  
5.77  
74.2  
73.4  
6.12  
81.2  
65.8  
5.82  
79.8  
65.2  
6.18  
88.5  
56.3  
5.91  
87.1  
55.6  
6.27  
96.1  
46.4  
6.00  
94.6  
45.8  
6.37  
82.5  
82.5  
5.84  
81.3  
81.3  
6.20  
86.4  
75.7  
5.88  
84.9  
75.0  
6.24  
93.6  
63.5  
5.97  
92.0  
62.8  
6.33  
101.0  
50.9  
6.07  
99.5  
50.2  
6.44  
88.0  
88.0  
5.90  
86.7  
86.7  
6.26  
89.9  
84.1  
5.93  
88.4  
83.3  
6.28  
96.8  
70.0  
6.01  
95.2  
69.4  
6.38  
104.0  
54.9  
6.12  
103.0  
54.3  
6.48  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
71.8  
71.6  
6.83  
77.2  
63.8  
6.89  
84.2  
54.3  
6.98  
91.6  
44.6  
7.10  
79.0  
79.0  
6.91  
82.0  
73.6  
6.95  
88.8  
61.5  
7.05  
96.2  
49.0  
7.17  
84.1  
84.1  
6.99  
85.4  
81.7  
7.00  
91.9  
68.1  
7.10  
99.2  
53.0  
7.22  
95  
TC  
70.6  
70.5  
7.22  
69.4  
69.4  
7.61  
67.0  
67.0  
8.39  
75.7  
63.1  
7.28  
74.2  
62.4  
7.67  
71.3  
60.9  
8.45  
82.6  
53.6  
7.38  
81.1  
53.0  
7.78  
78.0  
51.6  
8.59  
89.9  
43.9  
7.50  
88.3  
43.3  
7.91  
85.0  
41.9  
8.73  
77.7  
77.7  
7.31  
76.4  
76.4  
7.70  
73.8  
73.8  
8.49  
80.4  
72.8  
7.35  
78.8  
72.0  
7.75  
75.6  
70.5  
8.54  
87.1  
60.8  
7.45  
85.4  
60.1  
7.86  
82.0  
58.7  
8.66  
94.4  
48.3  
7.58  
92.6  
47.7  
7.99  
89.0  
46.4  
8.80  
82.7  
82.7  
7.39  
81.3  
81.3  
7.79  
78.5  
78.5  
8.59  
83.8  
80.7  
7.40  
82.2  
79.8  
7.80  
78.9  
77.9  
8.60  
90.0  
67.4  
7.51  
88.2  
66.7  
7.91  
84.6  
65.3  
8.71  
97.3  
52.3  
7.63  
95.4  
51.7  
8.04  
91.7  
50.3  
8.86  
100  
105  
115  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
*This combination is ENERGY STAR® compliant.  
18  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS (cont)  
UNIT 569D090 (cont)  
569D090/524A-C090 WITH HIGH-CAPACITY 4-ROW COIL*  
Evaporator Air — Cfm  
3000  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
2205  
3750  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
86.0  
86.0  
5.78  
84.8  
84.8  
6.14  
90.4  
78.0  
5.83  
88.9  
77.3  
6.18  
98.0  
65.6  
5.91  
96.4  
64.9  
6.26  
106.0  
52.8  
6.01  
104.0  
52.2  
6.37  
94.1  
94.1  
5.86  
92.7  
92.7  
6.22  
95.7  
90.3  
5.88  
94.1  
89.4  
6.23  
103.0  
75.0  
5.97  
101.0  
74.2  
6.32  
111.0  
58.5  
6.07  
109.0  
57.8  
6.42  
96.9  
96.9  
5.90  
95.4  
95.4  
6.25  
97.8  
94.8  
5.91  
96.2  
93.7  
6.26  
104.0  
79.3  
5.98  
102.0  
78.5  
6.34  
112.0  
61.1  
6.09  
110.0  
60.5  
6.44  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
82.3  
82.3  
6.85  
85.8  
75.8  
6.88  
93.1  
63.5  
6.96  
101.0  
50.9  
7.07  
90.0  
90.0  
6.92  
90.9  
87.7  
6.93  
97.3  
72.8  
7.02  
105.0  
56.5  
7.13  
92.6  
92.6  
6.96  
93.1  
91.4  
6.96  
98.7  
77.1  
7.04  
106.0  
59.2  
7.15  
95  
TC  
81.0  
81.0  
7.24  
79.6  
79.6  
7.63  
77.0  
77.0  
8.41  
84.2  
75.0  
7.26  
82.5  
74.1  
7.65  
79.2  
72.5  
8.42  
91.3  
62.8  
7.36  
89.6  
62.1  
7.75  
86.0  
60.6  
8.53  
99.1  
50.2  
7.47  
97.2  
49.5  
7.87  
93.5  
48.1  
8.66  
88.5  
88.5  
7.32  
87.0  
87.0  
7.71  
83.9  
83.9  
8.50  
89.2  
86.7  
7.33  
87.5  
85.7  
7.72  
84.1  
83.7  
8.50  
95.4  
72.1  
7.41  
93.5  
71.4  
7.81  
89.8  
69.9  
8.60  
103.0  
55.8  
7.53  
101.0  
55.2  
7.93  
97.2  
53.8  
8.73  
91.0  
91.0  
7.35  
89.5  
89.5  
7.75  
86.3  
86.3  
8.54  
91.4  
90.1  
7.36  
89.7  
88.8  
7.75  
86.4  
86.2  
8.54  
96.8  
76.4  
7.43  
94.9  
75.6  
7.83  
91.0  
74.1  
8.62  
104.0  
58.5  
7.55  
102.0  
57.8  
7.95  
98.3  
56.4  
8.75  
100  
105  
115  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
569D090/524A-B090 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
2205  
3000  
3750  
Air Entering  
Condenser  
(Edb)  
Evaporator Air — Ewb (F)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
81.7  
81.7  
5.83  
80.6  
80.6  
6.19  
85.9  
74.2  
5.88  
84.5  
73.5  
6.23  
93.2  
62.4  
5.97  
91.6  
61.7  
6.33  
101.0  
50.2  
6.07  
99.2  
49.6  
6.43  
89.0  
89.0  
5.92  
87.7  
87.7  
6.28  
90.8  
85.2  
5.94  
89.3  
84.5  
6.30  
97.5  
70.9  
6.02  
95.8  
70.2  
6.39  
105.0  
55.4  
6.12  
103.0  
54.8  
6.49  
91.6  
91.6  
5.95  
90.2  
90.2  
6.31  
92.6  
89.4  
5.96  
91.1  
88.4  
6.32  
98.8  
74.7  
6.04  
97.1  
74.1  
6.40  
106.0  
57.7  
6.14  
105.0  
57.1  
6.51  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
78.3  
78.3  
6.90  
81.7  
72.1  
6.95  
88.5  
60.4  
7.05  
95.9  
48.4  
7.17  
85.2  
85.2  
7.00  
86.3  
82.9  
7.02  
92.5  
69.0  
7.11  
99.9  
53.6  
7.23  
87.6  
87.6  
7.04  
88.2  
86.4  
7.05  
93.8  
72.8  
7.13  
101.0  
55.9  
7.25  
95  
TC  
77.0  
77.0  
7.30  
75.7  
75.7  
7.69  
73.2  
73.2  
8.48  
80.1  
71.3  
7.34  
78.6  
70.6  
7.74  
75.4  
69.0  
8.53  
86.9  
59.8  
7.45  
85.2  
59.1  
7.86  
81.9  
57.7  
8.67  
94.2  
47.7  
7.57  
92.4  
47.0  
7.98  
88.8  
45.7  
8.79  
83.7  
83.7  
7.40  
82.3  
82.3  
7.80  
79.5  
79.5  
8.61  
84.7  
81.9  
7.42  
83.0  
80.9  
7.82  
79.8  
79.0  
8.61  
90.7  
68.3  
7.52  
88.9  
67.6  
7.92  
85.3  
66.1  
8.73  
98.0  
52.9  
7.64  
96.1  
52.2  
8.05  
92.3  
50.9  
8.87  
86.1  
86.1  
7.44  
84.6  
84.6  
7.84  
81.7  
81.7  
8.65  
86.6  
85.2  
7.45  
85.0  
83.9  
7.85  
81.8  
81.4  
8.65  
91.9  
72.1  
7.54  
90.1  
71.4  
7.94  
86.4  
70.0  
8.75  
99.1  
55.2  
7.66  
97.2  
54.6  
8.07  
93.3  
53.2  
8.89  
100  
105  
115  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
*This combination is ENERGY STAR® compliant.  
19  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS (cont)  
UNIT 569D120  
569D120/524A-C120 WITH HIGH-CAPACITY 4-ROW COIL  
Evaporator Air — Cfm  
4000  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
3000  
5000  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
117.0  
117.0  
8.34  
115.0  
115.0  
8.72  
122.0  
106.0  
8.48  
120.0  
104.0  
8.85  
132.0  
88.4  
8.74  
129.0  
87.5  
9.11  
142.0  
70.9  
9.02  
140.0  
70.0  
9.40  
127.0  
127.0  
8.61  
125.0  
125.0  
8.99  
129.0  
122.0  
8.66  
127.0  
121.0  
9.04  
138.0  
101.0  
8.89  
135.0  
100.0  
9.27  
148.0  
78.6  
9.18  
145.0  
77.6  
9.56  
134.0  
134.0  
8.81  
132.0  
132.0  
9.19  
134.0  
134.0  
8.80  
132.0  
132.0  
9.19  
141.0  
113.0  
9.00  
139.0  
112.0  
9.38  
151.0  
85.9  
9.28  
148.0  
84.9  
9.67  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
112.0  
112.0  
9.49  
116.0  
102.0  
9.60  
125.0  
85.5  
9.86  
135.0  
68.2  
10.20  
121.0  
121.0  
9.76  
122.0  
119.0  
9.79  
130.0  
98.2  
10.00  
140.0  
75.8  
10.30  
128.0  
128.0  
9.96  
128.0  
128.0  
9.95  
134.0  
110.0  
10.10  
143.0  
83.1  
10.40  
95  
TC  
110.0  
110.0  
9.90  
108.0  
108.0  
10.30  
104.0  
104.0  
11.10  
113.0  
101.0  
10.00  
111.0  
100.0  
10.40  
106.0  
97.7  
11.20  
122.0  
84.4  
132.0  
67.1  
119.0  
119.0  
10.20  
117.0  
117.0  
10.60  
112.0  
112.0  
11.40  
120.0  
117.0  
10.20  
117.0  
116.0  
10.60  
112.0  
112.0  
11.40  
127.0  
97.1  
137.0  
74.8  
125.0  
125.0  
10.40  
123.0  
123.0  
10.80  
118.0  
118.0  
11.60  
125.0  
125.0  
10.40  
123.0  
123.0  
10.80  
118.0  
118.0  
11.60  
131.0  
109.0  
10.50  
128.0  
108.0  
10.90  
122.0  
105.0  
11.70  
140.0  
82.1  
100  
105  
115  
SHC  
kW  
10.30  
10.60  
10.40  
10.70  
10.80  
TC  
SHC  
kW  
TC  
SHC  
kW  
120.0  
83.3  
10.70  
114.0  
81.2  
11.50  
129.0  
66.1  
11.00  
124.0  
64.0  
11.70  
125.0  
96.0  
10.80  
119.0  
93.8  
11.60  
134.0  
73.7  
11.10  
128.0  
71.7  
11.90  
137.0  
81.0  
11.20  
131.0  
78.9  
12.00  
569D120/524A-B120 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
3000  
4000  
5000  
Air Entering  
Condenser  
(Edb)  
Evaporator Air — Ewb (F)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
110.0  
110.0  
8.19  
108.0  
108.0  
8.57  
115.0  
99.4  
8.32  
113.0  
98.4  
8.70  
124.0  
83.3  
8.55  
122.0  
82.4  
8.93  
134.0  
66.8  
8.82  
132.0  
66.0  
9.20  
119.0  
119.0  
8.41  
117.0  
117.0  
8.80  
121.0  
114.0  
8.48  
119.0  
113.0  
8.85  
130.0  
94.6  
8.70  
128.0  
93.7  
9.08  
139.0  
73.6  
8.96  
137.0  
72.8  
9.35  
126.0  
126.0  
8.59  
124.0  
124.0  
8.97  
126.0  
125.0  
8.60  
124.0  
123.0  
8.98  
133.0  
105.0  
8.80  
131.0  
104.0  
9.17  
143.0  
79.9  
9.06  
140.0  
79.0  
9.44  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
105.0  
105.0  
9.34  
110.0  
96.6  
9.45  
118.0  
80.7  
9.69  
127.0  
64.3  
9.96  
114.0  
114.0  
9.57  
115.0  
111.0  
9.61  
123.0  
91.9  
9.83  
132.0  
71.1  
10.10  
120.0  
120.0  
9.73  
120.0  
120.0  
9.74  
126.0  
102.0  
9.93  
135.0  
77.3  
10.20  
95  
TC  
104.0  
104.0  
9.76  
102.0  
102.0  
10.20  
98.4  
98.4  
11.00  
107.0  
95.5  
9.86  
105.0  
94.4  
10.30  
101.0  
92.2  
11.10  
116.0  
79.7  
125.0  
63.4  
112.0  
112.0  
9.98  
110.0  
110.0  
10.40  
106.0  
106.0  
11.20  
113.0  
109.0  
10.00  
111.0  
108.0  
10.40  
106.0  
105.0  
11.20  
121.0  
90.9  
130.0  
70.2  
118.0  
118.0  
10.10  
116.0  
116.0  
10.60  
111.0  
111.0  
11.40  
118.0  
118.0  
10.10  
116.0  
116.0  
10.60  
111.0  
111.0  
11.40  
124.0  
101.0  
10.30  
121.0  
100.0  
10.70  
116.0  
97.9  
11.50  
132.0  
76.4  
100  
105  
115  
SHC  
kW  
10.10  
10.40  
10.20  
10.50  
10.60  
TC  
SHC  
kW  
TC  
SHC  
kW  
114.0  
78.7  
10.5  
109.0  
76.7  
11.30  
122.0  
62.4  
10.80  
117.0  
60.5  
11.60  
118.0  
89.9  
10.60  
113.0  
87.8  
11.40  
127.0  
69.2  
10.90  
122.0  
67.3  
11.70  
130.0  
75.5  
11.00  
124.0  
73.6  
11.80  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
20  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS (cont)  
UNIT 569D120 (cont)  
569D120/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL  
Evaporator Air — Cfm  
5000  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
3750  
6250  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
126.0  
126.0  
8.60  
124.0  
124.0  
8.98  
129.0  
119.0  
8.68  
127.0  
118.0  
9.05  
138.0  
98.7  
8.94  
136.0  
97.7  
9.31  
149.0  
77.4  
9.23  
146.0  
76.5  
9.61  
136.0  
136.0  
8.87  
134.0  
134.0  
9.25  
136.0  
135.0  
8.87  
134.0  
133.0  
9.25  
143.0  
114.0  
9.08  
141.0  
113.0  
9.46  
153.0  
86.5  
9.37  
151.0  
85.6  
9.76  
142.0  
142.0  
9.06  
140.0  
140.0  
9.44  
142.0  
142.0  
9.05  
140.0  
140.0  
9.44  
147.0  
127.0  
9.18  
144.0  
126.0  
9.56  
156.0  
95.0  
9.46  
154.0  
94.1  
9.84  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
120.0  
120.0  
9.74  
122.0  
116.0  
9.80  
131.0  
95.7  
10.10  
141.0  
74.6  
10.40  
129.0  
129.0  
10.00  
129.0  
129.0  
10.00  
136.0  
111.0  
10.20  
145.0  
83.8  
10.50  
136.0  
136.0  
10.20  
136.0  
136.0  
10.20  
139.0  
124.0  
10.30  
148.0  
92.3  
10.60  
95  
TC  
118.0  
118.0  
10.20  
116.0  
116.0  
10.60  
112.0  
112.0  
11.40  
120.0  
114.0  
10.20  
117.0  
113.0  
10.60  
112.0  
110.0  
11.40  
128.0  
94.6  
138.0  
73.6  
127.0  
127.0  
10.40  
125.0  
125.0  
10.80  
120.0  
120.0  
11.60  
127.0  
127.0  
10.40  
125.0  
125.0  
10.80  
120.0  
120.0  
11.70  
133.0  
109.0  
10.60  
130.0  
108.0  
11.00  
124.0  
106.0  
11.80  
142.0  
82.7  
133.0  
133.0  
10.60  
130.0  
130.0  
11.00  
125.0  
125.0  
11.80  
133.0  
133.0  
10.60  
130.0  
130.0  
11.00  
125.0  
125.0  
11.80  
136.0  
123.0  
10.70  
133.0  
121.0  
11.10  
127.0  
119.0  
11.90  
145.0  
91.2  
100  
105  
115  
SHC  
kW  
10.50  
10.80  
10.90  
11.00  
TC  
SHC  
kW  
TC  
SHC  
kW  
126.0  
93.5  
10.90  
120.0  
91.4  
11.70  
135.0  
72.6  
11.20  
129.0  
70.5  
12.00  
139.0  
81.6  
11.30  
133.0  
79.5  
12.10  
142.0  
90.1  
11.40  
135.0  
87.9  
12.20  
569D120/524A-B150 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
3750  
5000  
6250  
Air Entering  
Condenser  
(Edb)  
Evaporator Air — Ewb (F)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
119.0  
119.0  
8.42  
118.0  
118.0  
8.80  
123.0  
112.0  
8.51  
121.0  
111.0  
8.89  
132.0  
93.2  
8.77  
130.0  
92.3  
9.14  
142.0  
73.4  
9.05  
140.0  
72.5  
9.43  
128.0  
128.0  
8.66  
126.0  
126.0  
9.05  
129.0  
127.0  
8.68  
127.0  
126.0  
9.06  
137.0  
106.0  
8.90  
135.0  
105.0  
9.28  
147.0  
81.4  
9.18  
144.0  
80.5  
9.56  
135.0  
135.0  
8.84  
133.0  
133.0  
9.22  
135.0  
135.0  
8.84  
133.0  
133.0  
9.22  
140.0  
118.0  
8.99  
138.0  
117.0  
9.37  
150.0  
88.6  
9.27  
147.0  
87.8  
9.65  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
114.0  
114.0  
9.57  
116.0  
109.0  
9.64  
125.0  
90.4  
9.89  
135.0  
70.7  
10.20  
122.0  
122.0  
9.81  
123.0  
122.0  
9.81  
130.0  
103.0  
10.00  
139.0  
78.7  
10.30  
128.0  
128.0  
9.99  
128.0  
128.0  
9.99  
133.0  
115.0  
10.10  
142.0  
86.0  
10.40  
95  
TC  
112.0  
112.0  
9.98  
110.0  
110.0  
10.40  
106.0  
106.0  
11.20  
114.0  
108.0  
10.00  
112.0  
106.0  
10.40  
107.0  
104.0  
11.20  
123.0  
89.3  
132.0  
69.7  
120.0  
120.0  
10.20  
118.0  
118.0  
10.60  
114.0  
114.0  
11.40  
120.0  
120.0  
10.20  
118.0  
118.0  
10.60  
113.0  
113.0  
11.40  
127.0  
102.0  
10.40  
124.0  
101.0  
10.80  
119.0  
99.1  
11.60  
136.0  
77.7  
126.0  
126.0  
10.40  
123.0  
123.0  
10.80  
119.0  
119.0  
11.60  
126.0  
126.0  
10.40  
123.0  
123.0  
10.80  
119.0  
119.0  
11.60  
130.0  
114.0  
10.50  
127.0  
113.0  
10.90  
121.0  
110.0  
11.70  
139.0  
85.0  
100  
105  
115  
SHC  
kW  
10.30  
10.60  
10.70  
10.80  
TC  
SHC  
kW  
TC  
SHC  
kW  
120.0  
88.2  
10.70  
115.0  
86.1  
11.50  
129.0  
68.7  
11.00  
124.0  
66.6  
11.80  
133.0  
76.7  
11.10  
127.0  
74.6  
11.90  
136.0  
84.0  
11.20  
130.0  
81.9  
12.00  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
21  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS (cont)  
UNIT 576C120  
576C120/524A-C120 WITH HIGH-CAPACITY 4-ROW COIL  
Evaporator Air — Cfm  
4000  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
3000  
5000  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
113.0  
113.0  
8.00  
111.0  
111.0  
8.39  
118.0  
104.0  
8.12  
115.0  
102.0  
8.51  
129.0  
87.4  
8.35  
126.0  
86.1  
8.76  
141.0  
70.5  
8.61  
137.0  
69.3  
9.05  
124.0  
124.0  
8.26  
122.0  
122.0  
8.67  
126.0  
121.0  
8.29  
123.0  
119.0  
8.69  
135.0  
101.0  
8.49  
132.0  
99.5  
8.91  
147.0  
78.8  
8.75  
144.0  
77.6  
9.20  
132.0  
132.0  
8.43  
129.0  
129.0  
8.86  
132.0  
132.0  
8.43  
129.0  
129.0  
8.86  
139.0  
113.0  
8.58  
136.0  
112.0  
9.01  
151.0  
86.6  
8.82  
148.0  
85.4  
9.28  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
106.0  
106.0  
9.17  
110.0  
99.8  
9.28  
120.0  
83.7  
9.58  
131.0  
66.9  
9.93  
117.0  
117.0  
9.49  
117.0  
116.0  
9.51  
125.0  
96.9  
9.76  
137.0  
75.1  
10.10  
124.0  
124.0  
9.72  
124.0  
124.0  
9.72  
129.0  
109.0  
9.88  
140.0  
82.9  
10.20  
95  
TC  
104.0  
104.0  
9.55  
102.0  
102.0  
9.93  
97.2  
97.2  
10.70  
107.0  
98.4  
9.65  
104.0  
97.0  
10.00  
98.6  
94.2  
10.80  
117.0  
82.4  
9.98  
114.0  
81.1  
10.40  
107.0  
78.6  
11.20  
128.0  
65.7  
114.0  
114.0  
9.90  
112.0  
112.0  
10.30  
106.0  
106.0  
11.10  
114.0  
114.0  
9.90  
112.0  
112.0  
10.30  
106.0  
106.0  
11.10  
122.0  
95.6  
133.0  
73.9  
121.0  
121.0  
10.10  
118.0  
118.0  
10.60  
113.0  
113.0  
11.40  
121.0  
121.0  
10.10  
118.0  
118.0  
10.60  
113.0  
113.0  
11.40  
126.0  
108.0  
10.30  
122.0  
106.0  
10.70  
116.0  
104.0  
11.50  
137.0  
81.7  
100  
105  
115  
SHC  
kW  
10.40  
10.20  
10.50  
10.60  
TC  
SHC  
kW  
TC  
SHC  
kW  
124.0  
64.5  
10.80  
118.0  
62.1  
11.60  
119.0  
94.3  
10.60  
112.0  
91.7  
11.40  
130.0  
72.7  
11.00  
122.0  
70.2  
11.80  
133.0  
80.5  
11.10  
125.0  
78.0  
12.00  
576C120/524A-B120 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
3000  
4000  
5000  
Air Entering  
Condenser  
(Edb)  
Evaporator Air — Ewb (F)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
107.0  
107.0  
7.91  
105.0  
105.0  
8.29  
112.0  
98.8  
8.03  
110.0  
97.5  
8.40  
123.0  
83.3  
8.25  
120.0  
82.2  
8.65  
134.0  
67.2  
8.49  
131.0  
66.1  
8.92  
118.0  
118.0  
8.14  
115.0  
115.0  
8.54  
119.0  
114.0  
8.18  
117.0  
113.0  
8.57  
129.0  
95.5  
8.38  
126.0  
94.3  
8.79  
140.0  
74.8  
8.62  
137.0  
73.7  
9.06  
125.0  
125.0  
8.30  
122.0  
122.0  
8.71  
125.0  
125.0  
8.30  
122.0  
122.0  
8.71  
133.0  
107.0  
8.46  
129.0  
105.0  
8.88  
144.0  
81.8  
8.71  
141.0  
80.6  
9.15  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
101.0  
101.0  
9.04  
105.0  
95.0  
9.15  
114.0  
79.8  
9.44  
125.0  
63.9  
9.78  
111.0  
111.0  
9.34  
111.0  
109.0  
9.36  
120.0  
92.0  
9.61  
131.0  
71.4  
9.94  
117.0  
117.0  
9.54  
117.0  
117.0  
9.54  
123.0  
103.0  
9.72  
134.0  
78.4  
10.00  
95  
TC  
98.9  
98.9  
9.41  
96.8  
96.8  
9.78  
92.5  
92.5  
10.50  
102.0  
93.7  
9.51  
99.4  
92.3  
9.87  
94.1  
89.7  
10.60  
111.0  
78.7  
9.83  
108.0  
77.5  
10.0  
103.0  
75.1  
11.00  
122.0  
62.8  
108.0  
108.0  
9.73  
106.0  
106.0  
10.10  
101.0  
101.0  
10.90  
109.0  
108.0  
9.74  
106.0  
106.0  
10.10  
101.0  
101.0  
10.90  
117.0  
90.8  
127.0  
70.3  
115.0  
115.0  
9.94  
112.0  
112.0  
10.30  
107.0  
107.0  
11.20  
115.0  
115.0  
9.95  
112.0  
112.0  
10.30  
107.0  
107.0  
11.20  
120.0  
102.0  
10.10  
117.0  
100.0  
10.50  
110.0  
97.7  
11.30  
131.0  
77.3  
100  
105  
115  
SHC  
kW  
10.20  
10.00  
10.40  
10.50  
TC  
SHC  
kW  
TC  
SHC  
kW  
119.0  
61.6  
10.60  
113.0  
59.4  
11.40  
113.0  
89.5  
10.40  
107.0  
87.1  
11.20  
124.0  
69.2  
10.80  
117.0  
67.0  
11.60  
127.0  
76.1  
10.90  
120.0  
73.9  
11.80  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
22  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS (cont)  
UNIT 576C120 (cont)  
576C120/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL  
Evaporator Air — Cfm  
5000  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
3750  
6250  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
122.0  
122.0  
8.23  
120.0  
120.0  
8.64  
125.0  
117.0  
8.28  
122.0  
116.0  
8.69  
135.0  
97.7  
8.51  
132.0  
96.5  
8.94  
147.0  
77.1  
8.77  
144.0  
76.0  
9.22  
133.0  
133.0  
8.47  
130.0  
130.0  
8.90  
133.0  
133.0  
8.47  
130.0  
130.0  
8.90  
141.0  
113.0  
8.64  
138.0  
112.0  
9.07  
153.0  
86.9  
8.88  
149.0  
85.6  
9.35  
141.0  
141.0  
8.62  
138.0  
138.0  
9.07  
141.0  
141.0  
8.62  
138.0  
138.0  
9.07  
145.0  
127.0  
8.72  
142.0  
126.0  
9.16  
157.0  
96.0  
8.95  
153.0  
94.7  
9.42  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
115.0  
115.0  
9.46  
116.0  
113.0  
9.50  
126.0  
93.9  
9.78  
137.0  
73.6  
10.10  
125.0  
125.0  
9.76  
125.0  
125.0  
9.76  
131.0  
109.0  
9.95  
142.0  
83.2  
10.30  
132.0  
132.0  
9.97  
132.0  
132.0  
9.97  
135.0  
123.0  
10.10  
145.0  
92.3  
10.40  
95  
TC  
113.0  
113.0  
9.86  
110.0  
110.0  
10.30  
105.0  
105.0  
11.10  
113.0  
111.0  
9.89  
111.0  
109.0  
10.30  
105.0  
105.0  
11.10  
123.0  
92.6  
134.0  
72.4  
122.0  
122.0  
10.20  
119.0  
119.0  
10.60  
114.0  
114.0  
11.50  
122.0  
122.0  
10.20  
119.0  
119.0  
10.60  
114.0  
114.0  
11.50  
128.0  
108.0  
10.40  
124.0  
107.0  
10.80  
117.0  
104.0  
11.60  
139.0  
82.0  
129.0  
129.0  
10.40  
126.0  
126.0  
10.80  
120.0  
120.0  
11.70  
129.0  
129.0  
10.40  
126.0  
126.0  
10.80  
120.0  
120.0  
11.70  
131.0  
121.0  
10.50  
128.0  
120.0  
10.90  
121.0  
117.0  
11.80  
141.0  
91.1  
100  
105  
115  
SHC  
kW  
10.20  
10.60  
10.70  
10.80  
TC  
SHC  
kW  
TC  
SHC  
kW  
119.0  
91.4  
10.60  
113.0  
88.8  
11.40  
130.0  
71.1  
11.00  
123.0  
68.7  
11.90  
135.0  
80.8  
11.20  
127.0  
78.4  
12.10  
138.0  
89.9  
11.30  
130.0  
87.4  
12.20  
576C120/524A-B150 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
3750  
5000  
6250  
Air Entering  
Condenser  
(Edb)  
Evaporator Air — Ewb (F)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
115.0  
115.0  
8.08  
113.0  
113.0  
8.47  
118.0  
110.0  
8.14  
116.0  
109.0  
8.53  
129.0  
92.3  
8.37  
126.0  
91.1  
8.78  
140.0  
73.1  
8.62  
137.0  
71.9  
9.06  
125.0  
125.0  
8.30  
123.0  
123.0  
8.71  
126.0  
125.0  
8.30  
123.0  
123.0  
8.72  
134.0  
106.0  
8.48  
131.0  
105.0  
8.91  
146.0  
81.7  
8.74  
142.0  
80.5  
9.18  
132.0  
132.0  
8.45  
130.0  
130.0  
8.88  
132.0  
132.0  
8.45  
130.0  
130.0  
8.88  
138.0  
119.0  
8.57  
134.0  
117.0  
8.99  
149.0  
89.6  
8.81  
146.0  
88.5  
9.26  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
109.0  
109.0  
9.25  
110.0  
106.0  
9.31  
120.0  
88.7  
9.60  
131.0  
69.6  
9.94  
118.0  
118.0  
9.54  
118.0  
118.0  
9.54  
124.0  
102.0  
9.75  
136.0  
78.2  
10.10  
124.0  
124.0  
9.73  
124.0  
124.0  
9.74  
128.0  
114.0  
9.85  
139.0  
86.1  
10.20  
95  
TC  
106.0  
106.0  
9.64  
104.0  
104.0  
10.00  
99.2  
99.2  
10.80  
108.0  
104.0  
9.68  
105.0  
103.0  
10.10  
99.3  
99.3  
10.80  
116.0  
87.5  
9.99  
113.0  
86.2  
10.40  
107.0  
83.7  
11.20  
127.0  
68.5  
115.0  
115.0  
9.95  
112.0  
112.0  
10.40  
107.0  
107.0  
11.20  
115.0  
115.0  
9.95  
113.0  
113.0  
10.40  
107.0  
107.0  
11.20  
121.0  
101.0  
10.10  
118.0  
99.7  
10.60  
111.0  
97.1  
11.40  
132.0  
77.0  
121.0  
121.0  
10.20  
118.0  
118.0  
10.60  
113.0  
113.0  
11.40  
121.0  
121.0  
10.20  
118.0  
118.0  
10.60  
113.0  
113.0  
11.40  
124.0  
113.0  
10.30  
121.0  
111.0  
10.70  
114.0  
108.0  
11.50  
135.0  
84.9  
100  
105  
115  
SHC  
kW  
10.40  
10.50  
10.60  
TC  
SHC  
kW  
TC  
SHC  
kW  
124.0  
67.3  
10.80  
117.0  
64.9  
11.60  
129.0  
75.8  
10.90  
121.0  
73.5  
11.80  
131.0  
83.8  
11.00  
124.0  
81.4  
11.90  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
23  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS (cont)  
UNIT 569F120  
569F120/524A-C120 WITH HIGH-CAPACITY 4-ROW COIL  
Evaporator Air — Cfm  
4000  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
3000  
5000  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
112.0  
112.0  
7.90  
110.0  
110.0  
8.35  
116.0  
102.0  
7.94  
114.0  
102.0  
8.39  
126.0  
85.9  
8.06  
123.0  
85.0  
8.51  
136.0  
68.8  
8.19  
134.0  
67.9  
8.65  
122.0  
122.0  
8.01  
120.0  
120.0  
8.46  
123.0  
119.0  
8.03  
121.0  
118.0  
8.47  
131.0  
98.8  
8.13  
129.0  
97.9  
8.58  
142.0  
76.7  
8.27  
140.0  
75.8  
8.72  
129.0  
129.0  
8.10  
127.0  
127.0  
8.55  
129.0  
129.0  
8.10  
127.0  
127.0  
8.55  
135.0  
111.0  
8.18  
133.0  
110.0  
8.63  
146.0  
84.2  
8.32  
143.0  
83.3  
8.77  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
107.0  
107.0  
9.24  
110.0  
99.6  
9.28  
119.0  
83.2  
9.40  
130.0  
66.3  
9.56  
116.0  
116.0  
9.36  
117.0  
115.0  
9.37  
124.0  
96.1  
9.48  
135.0  
74.1  
9.63  
123.0  
123.0  
9.46  
123.0  
123.0  
9.46  
128.0  
108.0  
9.53  
138.0  
81.6  
9.69  
95  
TC  
105.0  
105.0  
9.74  
103.0  
103.0  
10.20  
99.7  
99.7  
11.20  
108.0  
98.6  
9.78  
106.0  
97.5  
10.30  
102.0  
95.5  
11.30  
117.0  
82.3  
9.91  
115.0  
81.3  
10.40  
110.0  
79.5  
11.40  
127.0  
65.4  
114.0  
114.0  
9.87  
112.0  
112.0  
10.40  
108.0  
108.0  
11.40  
115.0  
114.0  
9.87  
113.0  
112.0  
10.40  
108.0  
108.0  
11.40  
122.0  
95.1  
9.98  
119.0  
94.1  
10.50  
115.0  
92.2  
11.50  
132.0  
73.2  
121.0  
121.0  
9.97  
119.0  
119.0  
10.50  
115.0  
115.0  
11.50  
121.0  
121.0  
9.97  
119.0  
119.0  
10.50  
114.0  
114.0  
11.50  
125.0  
107.0  
10.00  
123.0  
106.0  
10.50  
118.0  
104.0  
11.60  
135.0  
80.7  
100  
105  
115  
SHC  
kW  
10.10  
10.10  
10.20  
TC  
SHC  
kW  
TC  
SHC  
kW  
125.0  
64.4  
10.60  
120.0  
62.6  
11.60  
129.0  
72.3  
10.70  
124.0  
70.5  
11.70  
132.0  
79.8  
10.70  
127.0  
78.0  
11.70  
569F120/524A-B120 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
3000  
4000  
5000  
Air Entering  
Condenser  
(Edb)  
Evaporator Air — Ewb (F)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
106.0  
106.0  
7.83  
104.0  
104.0  
8.28  
110.0  
97.2  
7.89  
108.0  
96.3  
8.33  
119.0  
81.5  
7.98  
117.0  
80.7  
8.43  
130.0  
65.3  
8.11  
127.0  
64.5  
8.56  
115.0  
115.0  
7.94  
113.0  
113.0  
8.38  
116.0  
112.0  
7.95  
114.0  
111.0  
8.40  
125.0  
93.2  
8.05  
123.0  
92.3  
8.49  
135.0  
72.4  
8.17  
133.0  
71.7  
8.63  
121.0  
121.0  
8.01  
120.0  
120.0  
8.46  
121.0  
121.0  
8.01  
120.0  
120.0  
8.46  
128.0  
104.0  
8.09  
126.0  
103.0  
8.54  
138.0  
79.0  
8.22  
136.0  
78.2  
8.67  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
101.0  
101.0  
9.18  
105.0  
94.5  
9.21  
114.0  
79.1  
9.33  
123.0  
63.0  
9.47  
110.0  
110.0  
9.28  
111.0  
108.0  
9.29  
118.0  
90.7  
9.39  
128.0  
70.2  
9.54  
116.0  
116.0  
9.36  
116.0  
116.0  
9.36  
122.0  
101.0  
9.44  
131.0  
76.7  
9.58  
95  
TC  
99.7  
99.7  
9.67  
98.1  
98.1  
10.20  
94.9  
94.9  
11.20  
103.0  
93.6  
9.71  
101.0  
92.6  
10.20  
97.1  
90.6  
11.20  
111.0  
78.3  
9.83  
109.0  
77.4  
10.30  
105.0  
75.7  
11.30  
121.0  
62.2  
9.97  
119.0  
61.3  
10.50  
114.0  
59.7  
11.50  
108.0  
108.0  
9.78  
106.0  
106.0  
10.30  
103.0  
103.0  
11.30  
109.0  
107.0  
9.79  
107.0  
106.0  
10.30  
103.0  
103.0  
11.30  
116.0  
89.8  
9.90  
114.0  
89.0  
10.40  
110.0  
87.3  
11.40  
126.0  
69.3  
114.0  
114.0  
9.87  
112.0  
112.0  
10.40  
108.0  
108.0  
11.40  
114.0  
114.0  
9.87  
112.0  
112.0  
10.40  
108.0  
108.0  
11.40  
119.0  
100.0  
9.94  
117.0  
99.3  
10.40  
112.0  
97.5  
11.50  
129.0  
75.9  
10.1  
126.0  
75.1  
10.60  
121.0  
73.4  
11.60  
100  
105  
115  
SHC  
kW  
10.00  
TC  
SHC  
kW  
TC  
SHC  
kW  
123.0  
68.5  
10.60  
119.0  
66.8  
11.60  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
24  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS (cont)  
UNIT 569F120 (cont)  
569F120/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL  
Evaporator Air — Cfm  
5000  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
3750  
6250  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
121.0  
121.0  
8.00  
119.0  
119.0  
8.45  
123.0  
116.0  
8.03  
121.0  
115.0  
8.48  
132.0  
96.4  
8.14  
130.0  
95.5  
8.59  
143.0  
75.6  
8.29  
141.0  
74.8  
8.74  
131.0  
131.0  
8.12  
129.0  
129.0  
8.58  
131.0  
131.0  
8.12  
129.0  
129.0  
8.58  
138.0  
112.0  
8.21  
135.0  
111.0  
8.67  
148.0  
85.1  
8.36  
146.0  
84.3  
8.82  
140.0  
140.0  
8.24  
138.0  
138.0  
8.70  
138.0  
138.0  
8.22  
137.0  
137.0  
8.68  
143.0  
127.0  
8.28  
140.0  
126.0  
8.73  
153.0  
94.5  
8.42  
150.0  
93.6  
8.88  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
115.0  
115.0  
9.35  
117.0  
112.0  
9.37  
125.0  
93.7  
9.50  
136.0  
73.1  
9.66  
125.0  
125.0  
9.49  
125.0  
125.0  
9.49  
131.0  
109.0  
9.57  
141.0  
82.5  
9.73  
134.0  
134.0  
9.62  
133.0  
133.0  
9.60  
135.0  
124.0  
9.64  
145.0  
91.9  
9.80  
95  
TC  
113.0  
113.0  
9.86  
112.0  
112.0  
10.40  
108.0  
108.0  
11.40  
115.0  
111.0  
9.87  
113.0  
110.0  
10.40  
108.0  
107.0  
11.40  
123.0  
92.8  
10.0  
121.0  
91.8  
10.50  
116.0  
89.9  
11.50  
133.0  
72.1  
123.0  
123.0  
10.00  
121.0  
121.0  
10.50  
116.0  
116.0  
11.50  
123.0  
123.0  
9.99  
121.0  
121.0  
10.50  
116.0  
116.0  
11.50  
128.0  
108.0  
10.10  
125.0  
107.0  
10.60  
120.0  
105.0  
11.60  
138.0  
81.6  
131.0  
131.0  
10.10  
129.0  
129.0  
10.60  
124.0  
124.0  
11.70  
131.0  
131.0  
10.10  
129.0  
129.0  
10.60  
124.0  
123.0  
11.70  
132.0  
123.0  
10.10  
130.0  
122.0  
10.70  
124.0  
120.0  
11.70  
142.0  
91.0  
100  
105  
115  
SHC  
kW  
10.20  
10.20  
10.30  
TC  
SHC  
kW  
TC  
SHC  
kW  
131.0  
71.2  
10.70  
126.0  
69.4  
11.70  
135.0  
80.7  
10.80  
130.0  
78.9  
11.80  
139.0  
90.0  
10.80  
133.0  
88.2  
11.90  
569F120/524A-B150 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
3750  
5000  
6250  
Air Entering  
Condenser  
(Edb)  
Evaporator Air — Ewb (F)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
114.0  
114.0  
7.93  
113.0  
113.0  
8.37  
117.0  
109.0  
7.96  
115.0  
108.0  
8.40  
126.0  
91.1  
8.07  
124.0  
90.2  
8.51  
137.0  
71.7  
8.20  
134.0  
70.8  
8.65  
124.0  
124.0  
8.03  
122.0  
122.0  
8.49  
124.0  
124.0  
8.04  
122.0  
122.0  
8.49  
131.0  
105.0  
8.13  
129.0  
104.0  
8.58  
142.0  
80.0  
8.27  
139.0  
79.2  
8.72  
132.0  
132.0  
8.14  
130.0  
130.0  
8.59  
130.0  
130.0  
8.12  
129.0  
129.0  
8.57  
136.0  
118.0  
8.19  
133.0  
117.0  
8.64  
146.0  
88.2  
8.33  
144.0  
87.4  
8.78  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
109.0  
109.0  
9.27  
111.0  
106.0  
9.29  
120.0  
88.5  
9.41  
130.0  
69.2  
9.56  
118.0  
118.0  
9.39  
118.0  
118.0  
9.39  
124.0  
102.0  
9.48  
135.0  
77.6  
9.63  
126.0  
126.0  
9.51  
125.0  
125.0  
9.48  
129.0  
115.0  
9.55  
139.0  
85.8  
9.70  
95  
TC  
107.0  
107.0  
9.77  
106.0  
106.0  
10.30  
102.0  
102.0  
11.30  
109.0  
105.0  
9.79  
107.0  
103.0  
10.30  
103.0  
101.0  
11.30  
117.0  
87.6  
9.91  
115.0  
86.7  
10.40  
110.0  
84.8  
11.40  
127.0  
68.3  
116.0  
116.0  
9.90  
114.0  
114.0  
10.40  
110.0  
110.0  
11.40  
116.0  
116.0  
9.89  
114.0  
114.0  
10.40  
110.0  
110.0  
11.40  
122.0  
101.0  
9.99  
119.0  
100.0  
10.50  
114.0  
98.1  
11.50  
132.0  
76.7  
124.0  
124.0  
10.00  
122.0  
122.0  
10.50  
118.0  
118.0  
11.50  
123.0  
123.0  
9.99  
121.0  
121.0  
10.50  
117.0  
117.0  
11.50  
126.0  
114.0  
10.10  
124.0  
113.0  
10.60  
118.0  
111.0  
11.60  
136.0  
84.9  
100  
105  
115  
SHC  
kW  
10.10  
10.10  
10.20  
TC  
SHC  
kW  
TC  
SHC  
kW  
125.0  
67.4  
10.60  
120.0  
65.7  
11.60  
129.0  
75.8  
10.70  
124.0  
74.1  
11.70  
133.0  
84.0  
10.70  
128.0  
82.3  
11.70  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
25  
ELECTRICAL DATA  
569D072-120, 576C120, 569F120 UNITS  
NOMINAL  
VOLTAGE  
V-Ph-Hz  
VOLTAGE  
RANGE*  
MIN MAX  
FAN MOTORS  
(Qty 2)  
POWER  
SUPPLY  
FACTORY-  
INSTALLED  
OPTION  
COMPRESSOR  
UNIT  
SIZE  
RLA  
LRA  
FLA (ea)  
LRA (ea)  
MCA  
MOCP  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
25.8  
30.6  
12.8  
15.0  
10.2  
12.0  
35.0  
39.8  
17.4  
19.6  
13.8  
15.5  
50.3  
55.1  
22.9  
25.1  
17.8  
19.5  
48.0  
52.8  
23.9  
26.1  
18.6  
20.3  
39.0  
43.8  
19.4  
21.6  
15.8  
17.5  
35  
35  
20  
20  
15  
15  
60  
60  
30  
30  
20  
20  
60  
70  
30  
30  
25  
25  
60  
70  
35  
35  
30  
30  
50  
50  
25  
25  
20  
20  
208/230-3-60  
187  
418  
523  
187  
418  
523  
187  
418  
523  
187  
418  
523  
187  
418  
523  
254  
506  
632  
254  
506  
632  
254  
506  
632  
254  
506  
632  
254  
506  
632  
19.2  
146  
0.9  
1.6  
072  
090  
460-3-60  
575-3-60  
9.6  
7.7  
25.6  
12.8  
10.2  
37.8  
17.2  
13.4  
36  
73  
58.4  
190  
95  
0.4  
0.4  
1.5  
0.7  
0.7  
1.5  
0.7  
0.7  
1.5  
0.7  
0.7  
1.5  
0.7  
0.7  
0.9  
0.9  
3.1  
1.9  
1.9  
3.1  
1.9  
1.9  
3.1  
1.9  
1.9  
3.1  
1.9  
1.9  
208/230-3-60  
460-3-60  
569D  
575-3-60  
76  
208/230-3-60  
460-3-60  
239  
125  
80  
120  
575-3-60  
208/230-3-60  
460-3-60  
198  
99  
576C 120  
569F 120  
18  
575-3-60  
14  
79  
208/230-3-60  
460-3-60  
16  
125  
66.5  
50  
8
575-3-60  
6.4  
LEGEND  
FLA — Full Load Amps  
LRA — Locked Rotor Amps  
MCA — Minimum Circuit Amps  
MOCP — Maximum Overcurrent Protection  
NEC — National Electrical Code  
RLA — Rated Load Amps  
*Units are suitable for use on electrical systems where voltage supplied  
to the unit terminals is not below or above the listed limits.  
NOTES:  
1. The MCA and MOCP values are calculated in accordance with the  
NEC, Article 440.  
2. Motor RLA and LRA values are established in accordance with  
Underwriters’ Laboratories (UL), Standard 1995.  
3. The 575-v units are UL, Canada-listed only.  
4. Convenience outlet is available as either a factory-installed option  
or a field-installed accessory and is 115-v, 1 ph, 60 Hz.  
26  
APPLICATION DATA — 569D072-120, 576C090-120, 569F120  
OPERATING LIMITS MINIMUM OUTDOOR-AIR OPERATING  
TEMPERATURE  
Maximum Cooling Outdoor  
115 F  
MINIMUM  
OUTDOOR TEMP  
(F)  
See Minimum Outdoor-Air  
Operating Temperature  
table at right.  
COND  
TEMP  
(F)  
Minimum Outdoor Ambient  
UNIT  
SIZE  
COMPR  
CAPACITY  
With  
Minimum Return-Air  
Temperature  
Std  
Motormaster®  
Control  
55 F  
Maximum Return-Air  
Temperature  
Normal Acceptable Saturation  
Suction Temperature Range  
Maximum Discharge  
Temperature  
Minimum Discharge Superheat  
072  
090  
120  
100%  
100%  
100%  
100%  
67%  
90  
90  
90  
90  
80  
35  
35  
35  
35  
35  
95 F  
569D  
25 to 55 F  
–20  
576C  
569F  
120*  
120  
275 F  
60 F  
100%  
90  
35  
*Unit has one step of unloading.  
NOTES:  
1. Select air handler at no less than 300 cfm/ton (nominal condens-  
ing unit capacity).  
REFRIGERANT PIPING SIZES  
2. Total combined draw of the field-supplied liquid line solenoid valve  
and air handler fan contactor must not exceed 22 va. If the speci-  
fied va must be exceeded, use a remote relay to control the load.  
LINEAR LENGTH OF PIPING — FT  
25-50 50-75  
Line Size (in. OD)  
0-25  
75-100  
UNIT  
SIZE  
1. LIQUID LINE — For applications with liquid lift greater than  
L
S
L
S
L
S
L
S
3
5
20 ft, use 1/2-in. liquid line where /8 in. is shown; use /8-in.  
3
3
3
3
072  
/
/
/
/
11/8  
11/8  
13/8  
13/8  
/
/
/
/
11/8  
11/8  
13/8  
13/8  
/
8
/
2
/
2
/
2
11/8  
11/8  
13/8  
13/8  
/
/
/
/
11/8  
11/8  
13/8  
13/8  
8
8
2
2
8
2
2
2
8
2
2
2
1
liquid line where /2 in. is shown. The maximum liquid lift is  
3
1
1
1
1
1
1
1
1
1
1
1
569D 090  
120  
60 ft.  
576C 120  
MAXIMUM REFRIGERANT CHARGE  
569F 120 (2) 3/8 (2) 11/8 (2) 3/8 (2) 11/8 (2) 3/8 (2) 11/8 (2) 3/8 (2) 11/8  
UNIT  
R-22 (lb)  
SIZE  
LEGEND  
L — Liquid Line  
S — Suction Line  
072  
090  
120  
120  
120  
17.3  
34.2  
34.2  
34.2  
(2) 17.1  
569D  
NOTES:  
1. Pipe sizes are based on a 2° F loss for liquid and suction lines.  
2. Pipe sizes are based on the maximum linear length, shown for  
each column, plus a 50% allowance for fittings.  
576C  
569F  
3. Charge units with R-22 in accordance with unit installation  
instructions.  
2. REFRIGERANT PIPING — It is recommended that the  
refrigerant piping for all commercial split systems include a  
liquid line solenoid valve, a liquid line filter drier, and a sight  
glass.  
For refrigerant lines longer than 75 lineal ft, a liquid line  
solenoid valve and a suction accumulator are required.  
Refer to the Refrigerant Specialties table.  
REFRIGERANT SPECIALTIES PART NUMBERS  
LIQUID LINE  
SIZE (in.)  
LIQUID LINE  
SOLENOID VALVE (LLSV)  
LLSV  
COIL  
SIGHT  
GLASS  
FILTER  
DRIER  
SUCTION LINE  
ACCUMULATOR  
UNIT  
3
569D072  
/
200RB5T3M  
200RB5T3M  
200RB5T4M  
200RB6T4M  
200RB6T4M  
AMG/24V  
AMG/24V  
AMG/24V  
AMG/24V  
AMG/24V  
AMI-1TT3  
AMI-1TT3  
AMI-1TT4  
AMI-1TT4  
AMI-1TT4  
P502-8304S*  
P502-8304S*  
P502-8304S  
P502-8307S*  
P502-8307S*  
S-7063S*  
S-7063S*  
S-7063S*  
S-7063  
S-7063  
S-7061 Qty 2  
8
3
/
1
8
569D090  
569D120  
576C120  
/
2
1
/
1
2
/
2
3
/
200RB5T3M Qty 2  
AMG/24V Qty 2  
AMI-1TT3 Qty 2  
P502-8304S* Qty 2  
8
*Bushings required.  
27  
TYPICAL PIPING AND WIRING  
WEATHERPROOF  
FUSED DISCONNECT*  
PER NEC  
CONDENSING  
MOISTURE  
UNIT  
ELECTRIC  
HEATER  
ACCESSORY  
INDICATOR  
SIGHT GLASS*  
FIELD  
SUPPLIED  
POWER  
POWER WIRES  
LLSV*  
PITCH  
LIQUID  
LINE  
FILTER  
DRIER*  
INSULATED  
VAPOR  
LINE  
524A  
UNIT  
CONTROL  
WIRES  
CONDENSATE DRAIN  
POWER WIRES  
INDOOR  
THERMOSTAT†  
FUSED DISCONNECT  
PER NEC  
TO OPEN SIGHT  
DRAIN  
NOTES:  
LEGEND  
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System  
Design Manual for details.  
LLSV — Liquid Line Solenoid Valve  
NEC — National Electrical Code  
TXV — Thermostatic Expansion Valve  
2. All wiring must comply with the applicable local and national codes.  
3. Wiring and piping shown are general points-of-connection guides only and are not  
intended for, or to include all details for, a specific installation.  
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refriger-  
ant migration to the compressor.  
*Field supplied.  
†Accessory item.  
5. Internal factory-supplied TXVs not shown.  
Rooftop Installation — 569D072-120, 576C120  
28  
GUIDE SPECIFICATIONS — 569D072-120, 576C120  
COMMERCIAL AIR-COOLED CONDENSING UNITS D. Compressor:  
1. Compressor shall be of the scroll type (569D) or  
HVAC GUIDE SPECIFICATIONS  
semi-hermetic reciprocating type (576C).  
SIZE RANGE: 6 TO 10 TONS, NOMINAL  
2. Compressors shall be mounted on vibration  
isolators.  
BRYANT MODEL NUMBERS: 569D, SIZES 072-120  
576C, SIZE 120  
3. Compressors shall include overload protection.  
PART 1 — GENERAL  
4. Compressors shall be equipped with a crankcase  
heater.  
1.01 SYSTEM DESCRIPTION  
Outdoor-mounted, air-cooled condensing unit suitable for  
on-the-ground or rooftop installation. Unit shall consist of a  
reciprocating air-conditioning compressor assembly  
(576C) or scroll compressor (569D), an air-cooled coil,  
propeller-type condenser fan, and a control box. Unit shall  
discharge supply air upward as shown on contract draw-  
ings. Unit shall be used in a refrigeration circuit matched  
with a packaged air-handling unit.  
5. Compressor shall be equipped with internal high dis-  
charge temperature protection (569D072 and 120  
only).  
6. Compressor shall unload using suction cutoff unload-  
ing (576C120 only). Electric solenoid unloading  
available as an accessory.  
E. Condenser Coil:  
1.02 QUALITY ASSURANCE  
1. Condenser coil shall be air-cooled and circuited for  
integral subcooler.  
A. Unit shall be rated in accordance with ARI latest  
revisions.  
2. Coil shall be constructed of aluminum fins (copper  
fins optional) mechanically bonded to internally  
grooved seamless copper tubes which are then  
cleaned, dehydrated, and sealed.  
B. Unit construction shall comply with ANSI/ASHRAE 15  
safety code latest revision and comply with NEC.  
C. Unit shall be constructed in accordance with UL 1995  
standard and shall carry the UL and UL, Canada label.  
F. Refrigeration Components:  
D. Unit cabinet shall be capable of withstanding 500-hour  
salt spray exposure per ASTM B117 (scribed specimen).  
Refrigeration circuit components shall include liquid line  
service valve, suction line service valve, liquid filter drier,  
a full charge of compressor oil, and a holding charge of  
refrigerant. Unit 569D120 shall include an accumulator.  
Units with semi-hermetic compressors (576C) shall have  
oil-level sight glass and all units shall have crankcase  
heater.  
E. Air-cooled condenser coils for semi-hermetic compressor  
units (576C) shall be leak tested at 150 psig and pressure  
tested at 480 psig. Air-cooled condenser coils for scroll  
compressor units (569D) shall be leak tested at 200 psig,  
and pressure tested at 428 psig.  
G. Controls and Safeties:  
F. Unit shall be manufactured in a facility registered to  
ISO 9001:2000 manufacturing quality standard.  
1. Minimum control functions shall include:  
a. Control wire terminal blocks.  
1.03 DELIVERY, STORAGE, AND HANDLING  
Unit shall be shipped as single package only, and shall be  
stored and handled according to unit manufacturer’s  
recommendations.  
b. Compressor lockout on auto-reset safety until  
reset from thermostat.  
2. Minimum safety devices which are equipped with  
automatic reset (after resetting first at thermostat),  
shall include:  
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING  
ENGINEER.)  
PART 2 — PRODUCTS  
2.01 EQUIPMENT  
A. General:  
a. High discharge pressure cutout.  
b. Low Pressure cutout.  
c. High discharge temperature cutout (569D090  
only).  
Factory-assembled, single piece, air-cooled condensing  
unit. Contained within the unit enclosure shall be all  
factory wiring, piping, controls, compressor, holding  
charge (R-22), and special features required prior to field  
start-up.  
H. Operating Characteristics:  
1. The capacity of the condensing unit shall meet or  
exceed Btuh at a suction temperature of ______ F.  
The power consumption at full load shall not exceed  
______ kW.  
B. Unit Cabinet:  
1. Unit cabinet shall be constructed of galvanized steel,  
bonderized and coated with a prepainted baked  
enamel finish.  
2. The combination of the condensing unit and the  
evaporator or fan coil unit shall have a total net cool-  
ing capacity of ______ Btuh or greater at conditions  
of ______ cfm entering-air temperature at the evapo-  
rator at ______ F wet bulb and ______ F dry bulb,  
and air entering the condensing unit at ______ F.  
2. A heavy-gage roll-formed perimeter base rail with  
forklift slots and lifting holes shall be provided to facil-  
itate rigging.  
3. The system shall have an EER of ______ Btuh/Watt  
or greater at standard ARI conditions.  
C. Fans:  
1. Condenser fans shall be direct driven, propeller-type,  
discharging air vertically upward.  
I. Electrical Requirements:  
1. Nominal unit electrical characteristics shall be  
______ v, 3-ph, 60 Hz. The unit shall be capable of  
satisfactory operation within voltage limits of  
______ v to ______ v.  
2. Fan blades shall be balanced.  
3. Condenser fan discharge openings shall be  
equipped with PVC coated steel wire safety guards.  
4. Condenser fan and motor shaft shall be corrosion  
resistant.  
2. Unit electrical power shall be single-point connection.  
3. Unit control circuit shall contain a 24-v transformer  
for unit control.  
29  
GUIDE SPECIFICATIONS — 569D072-120, 576C120 (cont)  
shall be aluminum-fins mechanically bonded to  
J. Special Features:  
copper tubes.  
1. Low-Ambient Temperature Control Accessory:  
3. Thermostat Control Accessory:  
Low-ambient control shall be available as a factory-  
installed option or a field-installed accessory and  
shall regulate speed of condenser-fan motor in  
response to the saturated condensing temperature  
of the unit. The control shall maintain correct con-  
densing pressure at outdoor temperatures down to  
–20 F (fan motor change required for 569D and  
576C units).  
a. Commercial Electronic Thermostat with 7-day  
timeclock, auto-changeover, multi-stage capabil-  
ity, and large LCD temperature display.  
b. Commercial Electronic Non-programmable Ther-  
mostat with auto-changeover, multi-stage capacity,  
and large LCD display.  
4. Hail Guard Accessory:  
2. Optional Condenser Coil Materials:  
a. Pre-Coated Aluminum-Fin Coils:  
Hail guard package shall protect coils against dam-  
age from hail and other flying debris.  
Shall have a durable epoxy-phenolic coating to  
provide protection in mildly corrosive coastal envi-  
ronments. Coating shall be applied to the alumi-  
num fin stock prior to the fin stamping process to  
create an inert barrier between the aluminum  
fin and copper tube. Epoxy-phenolic barrier shall  
minimize galvanic action between dissimilar  
metals.  
5. Condenser Coil Grille Accessory:  
Grille shall add decorative appearance to unit and  
protect condenser coil after installation.  
6. Electric Solenoid Unloader Accessory:  
Electric unloader valve piston, coil, and hardware  
shall be supplied to convert the pressure-operated  
compressor unloader to electric unloading (576C120  
only).  
b. E-Coated Aluminum-Fin Coils:  
7. Unit-Mounted, Non-Fused Disconnect Switch:  
Shall have a flexible epoxy polymer coating uni-  
formly applied to all coil surface areas without  
material bridging between fins. Coating process  
shall ensure complete coil encapsulation. Color  
shall be high gloss black with gloss requirements  
of 60° of 65-90% per ASTM D523-89. Uniform dry  
film thickness from 0.8 to 1.2 mil on all surface  
areas including fin edges. Superior hardness char-  
acteristics of 2H per ASTM D3363-92A and cross  
hatch adhesion of 4B-5B per ASTM D3359-93.  
Impact resistance shall be up to 160 in./lb (ASTM  
D2794-93). Humidity and water immersion resis-  
tance shall be up to a minimum of 1000 and  
250 hours respectively (ASTM-D2247-92 and  
ASTM D870-92). Corrosion durability shall be con-  
firmed through testing to no less than 1000 hours  
salt spray per ASTM B117-90. Coil construction  
Shall be factory-installed, internally mounted. NEC  
and UL approved non-fused switch shall provide unit  
power shutoff. Shall be accessible from outside the  
unit and shall provide power off lockout capability.  
Not to be used when rooftop electrical rating  
exceeds 80 amperes.  
8. Convenience Outlet:  
Shall be factory-installed and internally mounted  
with easily accessible 115-v female receptacle. Shall  
include 15 amp GFI receptacle with independent  
fuse protection. Voltage required to operate conve-  
nience outlet shall be provided by a factory-installed  
step-down transformer. Shall be accessible from out-  
side the unit.  
30  
GUIDE SPECIFICATIONS — 569F120  
4. Compressors shall be equipped with a crankcase  
COMMERCIAL AIR-COOLED CONDENSING UNITS  
heater.  
HVAC GUIDE SPECIFICATIONS  
SIZE RANGE: 10 TONS, NOMINAL  
BRYANT MODEL NUMBER: 569F, SIZE 120  
PART 1 — GENERAL  
5. Compressors shall be equipped with high discharge  
temperature protection.  
E. Condenser Coil:  
1. Condenser coil shall be air-cooled and circuited for  
integral subcooler.  
1.01 SYSTEM DESCRIPTION  
Outdoor-mounted, air-cooled condensing unit suitable for  
on-the-ground or rooftop installation. Unit shall have  
2 independent refrigeration circuits. Unit shall consist of  
dual scroll compressors, air-cooled coils, propeller-type  
condenser fans, and a control box. Unit shall discharge  
supply air upward as shown on contract drawings. Unit  
shall be used in a refrigeration circuit matched with a pack-  
aged air-handling unit.  
2. Coil shall be constructed of aluminum fins (copper  
fins optional) mechanically bonded to internally  
grooved seamless copper tubes which are then  
cleaned, dehydrated, and sealed.  
F. Refrigeration Components:  
Refrigeration circuit components shall include liquid  
line service valve, suction line service valve, a full  
charge of compressor oil, and a holding charge of  
refrigerant.  
1.02 QUALITY ASSURANCE  
A. Unit shall be rated in accordance with ARI Standard 210/  
240, latest revision.  
G. Controls and Safeties:  
B. Unit construction shall comply with ANSI/ASHRAE 15  
safety code latest revision and comply with NEC.  
1. Minimum control functions shall include:  
a. Control wire terminal blocks.  
C. Unit shall be constructed in accordance with UL 1995  
standard and shall carry the UL and UL, Canada label.  
b. Compressor lockout on auto-reset safety until  
reset from thermostat.  
D. Unit cabinet shall be capable of withstanding 500-hour  
salt spray exposure per ASTM B117 (scribed specimen).  
2. Minimum safety devices which are equipped with  
automatic reset (after resetting first at thermostat),  
shall include:  
E. Air-cooled condenser coils shall be leak tested at  
200 psig, and pressure tested at 428 psig.  
a. High discharge pressure cutout.  
b. Low pressure cutout.  
F. Unit shall be manufactured in a facility registered to ISO  
9001:2000 manufacturing quality standard.  
H. Operating Characteristics:  
1.03 DELIVERY, STORAGE, AND HANDLING  
1. The capacity of the condensing unit shall meet or  
exceed _____ Btuh at a suction temperature of  
_____ F. The power consumption at full load shall not  
exceed _____ kW.  
Unit shall be shipped as single package only, and shall be  
stored and handled according to unit manufacturer’s  
recommendations.  
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING  
ENGINEER.)  
2. The combination of the condensing unit and the  
evaporator or fan coil unit shall have a total net cool-  
ing capacity of _____ Btuh or greater at conditions of  
_____ cfm entering-air temperature at the evaporator  
at _____ F wet bulb and _____ F dry bulb, and air  
entering the condensing unit at _____ F.  
PART 2 — PRODUCTS  
2.01 EQUIPMENT  
A. General:  
Factory-assembled, single piece, air-cooled condensing  
unit. Contained within the unit enclosure shall be all  
factory wiring, piping, controls, compressor, holding  
charge (R-22), and special features required prior to field  
start-up.  
3. The system shall have an EER of _____ Btuh/ Watt  
or greater at standard ARI conditions.  
I. Electrical Requirements:  
1. Nominal unit electrical characteristics shall be _____  
v, 3-ph, 60 Hz. The unit shall be capable of satisfac-  
tory operation within voltage limits of _____ v to  
_____ v.  
B. Unit Cabinet:  
1. Unit cabinet shall be constructed of galvanized steel,  
bonderized and coated with a prepainted baked  
enamel finish.  
2. Unit electrical power shall be single-point connection.  
3. Unit control circuit shall contain a 24-v transformer  
for unit control.  
2. A heavy-gage roll-formed perimeter base rail with  
forklift slots and lifting holes shall be provided to facil-  
itate rigging.  
J. Special Features:  
C. Fans:  
1. Low-Ambient Temperature Control:  
1. Condenser fans shall be direct driven, propeller-type,  
discharging air vertically upward.  
A low-ambient temperature control shall be available  
as a factory-installed option or as a field-installed  
accessory. This low-ambient control shall regulate  
speed of the condenser-fan motors in response to  
the saturated condensing temperature of the unit.  
The control shall maintain correct condensing pres-  
sure at outdoor temperatures down to –20 F.  
2. Fan blades shall be balanced.  
3. Condenser fan discharge openings shall be  
equipped with PVC coated steel wire safety guards.  
4. Condenser fan and motor shaft shall be corrosion  
resistant.  
2. Gage Panel Package:  
D. Compressor:  
Gage panel package shall include a suction and dis-  
charge pressure gage.  
1. Compressors shall be of the hermetic scroll type.  
2. Compressors shall be mounted on vibration isolators.  
3. Compressors shall include overload protection.  
31  
GUIDE SPECIFICATIONS — 569F120 (cont)  
3. Optional Condenser Coil Materials:  
4. Thermostat Controls:  
a. Pre-Coated Aluminum-Fin Coils:  
a. Programmable multi-stage thermostat with 7-day  
clock, holiday scheduling, large backlit display,  
remote sensor capability, and Title 24 compliance.  
Shall have a durable epoxy-phenolic coating to  
provide protection in mildly corrosive coastal  
environments. Coating shall be applied to the  
aluminum fin stock prior to the fin stamping  
process to create an inert barrier between the  
aluminum fin and copper tube. Epoxy-phenolic  
barrier shall minimize galvanic action between  
dissimilar metals.  
b. Commercial Electronic Thermostat with 7-day  
timeclock, auto-changeover, multi-stage capabil-  
ity, and large LCD temperature display.  
5. Hail Guard Package:  
Hail guard package shall protect coils against dam-  
age from hail and other flying debris.  
b. E-Coated Aluminum-Fin Coils:  
6. Condenser Coil Grille:  
Shall have a flexible epoxy polymer coating  
uniformly applied to all coil surface areas without  
material bridging between fins. Coating process  
shall ensure complete coil encapsulation. Color  
shall be high gloss black with gloss requirements  
of 60° of 65 to 90% per ASTM D523-89. Uniform  
dry film thickness from 0.8 to 1.2 mil on all surface  
areas including fin edges. Superior hardness  
characteristics of 2H per ASTM D3363-92A  
and cross hatch adhesion of 4B-5B per ASTM  
D3359-93. Impact resistance shall be up to  
160 in./lb (ASTM D2794-93). Humidity and water  
immersion resistance shall be up to a minimum  
of 1000 and 250 hours respectively (ASTM  
D2247-92 and ASTM D870-92). Corrosion dura-  
bility shall be confirmed through testing to no less  
than 1000 hours salt spray per ASTM B117-90.  
Coil construction shall be aluminum fins mechani-  
cally bonded to copper tubes.  
Grille shall add decorative appearance to unit and  
protect condenser coil after installation.  
7. Unit-Mounted, Non-Fused Disconnect Switch:  
Shall be factory-installed, internally mounted. NEC  
and UL approved non-fused switch shall provide unit  
power shutoff. Shall be accessible from outside the  
unit and shall provide power off lockout capability.  
8. Convenience Outlet:  
Shall be factory-installed and internally mounted with  
easily accessible 115-v female receptacle. Shall  
include 15 amp GFI receptacle with independent  
fuse protection. Voltage required to operate conve-  
nience outlet shall be provided by a factory-installed  
step-down transformer. Shall be accessible from out-  
side the unit.  
32  
MODEL NUMBER NOMENCLATURE  
566D 150 000 – –  
E
X
566D Commercial Air-Cooled Condensing  
Unit With Semi-Hermetic Compressor  
Factory-Installed Options*  
566E Dual Circuit Commercial Air-Cooled  
Condensing Unit With Scroll Compressors  
Heating Capacity  
000 — No Heat  
Voltage Designation  
E — 460-3-60  
P — 208/230-3-60  
T — 575-3-60  
Nominal Tons Cooling  
150 — 12-1/2  
180 — 15  
Heating  
X — None  
240 — 20  
*Contact your local representative for more details.  
Quality Assurance  
Certified to ISO 9001:2000  
33  
PHYSICAL DATA  
566D150-240 UNITS  
UNIT  
566D150  
121/2  
566D180  
566D240  
NOMINAL CAPACITY (tons)  
15  
20  
OPERATING WEIGHTS (lb)  
Aluminum-Fin Coil (Standard)  
Copper-Fin Coil (Optional)  
779  
919  
789  
929  
929  
1040  
REFRIGERANT TYPE*  
Operating Charge, Typical (lb)†  
Shipping Charge (lb)  
R-22  
23  
3.1  
23  
3.1  
28  
3.1  
COMPRESSOR  
Qty...Model  
Reciprocating, Semi-Hermetic  
1...06DD328  
1...06DD537  
1...06E4250  
No. Cylinders  
Speed (rpm)  
Oil Charge (pt)  
Capacity Steps  
Accessory  
6
6
4
1750  
10  
1750  
10  
1750  
15.5  
33**, 66, 100  
66, 100  
33**, 66, 100  
66, 100  
50, 100  
Standard  
Unloader Setting (psig)  
Load  
70  
60  
125  
1
2
Unload  
Crankcase Heater Watts  
CONDENSER FANS  
Qty...Rpm  
Axial Flow, Direct Drive  
2...1075  
Diameter (in.)  
26  
1
/
Nominal Hp  
Nominal Airflow (cfm, total)  
Watts (total)  
2
11,000  
1460  
CONDENSER COIL  
Rows...Fins/in.  
Copper Tubes, Aluminum Fins  
3...15  
29.2  
48  
3...15  
29.2  
48  
3...15  
29.2  
38  
Face Area (sq ft)  
Storage Capacity (lb)††  
CONTROLS  
Pressurestat (psig)  
High Pressure  
Cutout  
395 10  
295 20  
Cut-in  
Low Pressure  
Cutout  
Cut-in  
27  
67  
4
7
FAN CYCLING CONTROLS  
Operating Pressure (psig)  
No. 2 Fan, Close  
255 10  
160 10  
Open  
PRESSURE RELIEF  
Location  
Temperature (F)  
Liquid Line  
200  
PIPING CONNECTIONS (in. ODM)  
Suction  
13/8  
13/8  
15/8  
5
/
Liquid  
8
3
/
Hot Gas Stub  
8
*Unit is factory-supplied with holding charge only.  
Typical operating charge with 25 ft of interconnecting piping. Operating charge is approximate for maximum system  
capacity.  
**Indicates capacity step (%) with electric unloader accessory.  
††Storage capacity is measured at liquid saturated temperatures of 120 F.  
34  
PHYSICAL DATA (cont)  
566E150-240 UNITS  
UNIT  
566E150  
121/2  
566E180  
566E240  
NOMINAL CAPACITY (tons)  
OPERATING WEIGHTS (lb)  
15  
20  
Aluminum-Fin Coil (Standard)  
Copper-Fin Coil (Optional)  
676  
822  
740  
886  
764  
904  
REFRIGERANT TYPE*  
R-22  
Operating Charge, Typical (lb)†  
Shipping Charge (lb)  
23  
3.1  
23  
3.1  
28  
3.1  
COMPRESSOR  
Scroll  
Qty...Model  
2...ZR72  
3500  
60 (ea)  
2...ZR94  
3500  
85 (ea)  
70  
2...ZR125  
3500  
110 (ea)  
Speed (rpm)  
Oil Charge (oz)  
Crankcase Heater Watts  
CONDENSER FANS  
Qty...Rpm  
2...1075  
26  
Diameter (in.)  
1
/
Nominal Hp  
Nominal Airflow (cfm, total)  
Watts (total)  
2
11,000  
1460  
CONDENSER COIL  
Rows...Fins/in.  
Face Area (sq ft)  
Storage Capacity (lb)**  
3...15  
29.2  
48  
CONTROLS  
Pressurestat (psig)  
High Pressure  
Cutout  
426  
7
Cut-in  
320 20  
Low Pressure  
Cutout  
Cut-in  
27  
67  
4
7
FAN CYCLING CONTROLS  
Operating Pressure (psig)  
No. 2 Fan, Close  
Open  
255 10  
160 10  
PRESSURE RELIEF  
Location  
Temperature (F)  
Liquid Line  
200  
PIPING CONNECTIONS (in. ODM)  
Suction  
(2) 13/8  
(2) 1/2  
Liquid  
3
/
Hot Gas Stub  
8
*Unit is factory-supplied with holding charge only.  
Typical operating charge with 25 ft of interconnecting piping. Operating charge is approximate for  
maximum system capacity.  
**Storage capacity is measured at liquid saturated temperatures of 120 F.  
35  
DIMENSIONS  
NOTES:  
1. Service clearances are as follows:  
Side (compressor) — 31/2 ft  
Side (opposite compressor) — 3 ft  
Ends — 2 ft  
Top — 5 ft  
2. See page 38 for corner weights and  
unit center of gravity.  
566D150-240  
36  
DIMENSIONS (cont)  
NOTES:  
1. Service clearances are as follows:  
Side (compressor) — 31/2 ft (1067 mm)  
Side (opposite compressor) — 3 ft (914 mm)  
Ends — 2 ft (610 mm)  
Top — 5 ft (1524 mm)  
2. See page 38 for corner weights and unit  
center of gravity.  
566E150-240  
37  
DIMENSIONS (cont)  
566D150-240  
ALUMINUM COIL  
UNIT  
566D  
Standard  
Weight  
(lb)  
Operational Weight Points (lb)  
A
B
C
D
E
F
150  
180  
240  
779  
789  
900  
70  
70  
84  
177  
180  
234  
68  
69  
82  
100  
101  
108  
261  
265  
310  
103  
104  
111  
CENTER OF GRAVITY (in.)  
Aluminum Coil  
UNIT  
566D  
X
Y
150  
180  
240  
38  
38  
37  
16  
16  
17  
566E150-240  
ALUMINUM COIL  
Operational Weight Points (lb)  
UNIT  
566E  
Standard  
Weight  
(lb)  
A
B
C
D
E
F
150  
180  
240  
676  
740  
764  
84  
86  
87  
168  
186  
192  
72  
71  
72  
78  
82  
85  
183  
216  
226  
91  
99  
102  
CENTER OF GRAVITY (in.)  
Aluminum Coil  
UNIT  
566E  
X
Y
150  
180  
240  
35  
35  
35  
19  
18  
18  
NOTES:  
1. Corner weights are approximate.  
2. Actual support weights depend on level of unit and evenness of support posts.  
3. Total weights represent approximate unit weights without shipping package.  
4. Bottom or top skid is NOT included in the weights.  
566D150-240, 566E150-240  
38  
PERFORMANCE DATA  
CONDENSING UNIT RATINGS  
566E150  
566D150  
SST (F)  
Air Temperature Entering Condenser (F)  
Air Temperature Entering Condenser (F)  
SST (F)  
80  
85  
95  
100  
105  
115  
80  
85  
95  
100  
105  
115  
TC  
101.0  
8.56  
94.6  
97.6  
8.90  
99.4  
90.0  
9.55  
86.0  
9.85  
82.2  
10.20  
119.0  
74.7  
10.70  
129.0  
TC  
102.0  
9.04  
99.1  
9.58  
93.2  
10.80  
118.0  
90.3  
11.40  
123.0  
87.3  
12.10  
128.0  
81.1  
13.50  
138.0  
25  
30  
kW  
SDT  
20  
kW  
109.0  
114.0  
SDT  
103.0  
108.0  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
118.0  
8.80  
96.6  
113.0  
9.17  
101.0  
105.0  
9.90  
111.0  
101.0  
10.20  
116.0  
96.7  
10.60  
121.0  
88.5  
11.20  
131.0  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
114.0  
9.09  
103.0  
111.0  
9.64  
108.0  
105.0  
10.90  
118.0  
102.0  
11.50  
123.0  
98.8  
12.20  
128.0  
92.2  
13.60  
138.0  
25  
30  
35  
40  
45  
134.0  
9.03  
98.6  
129.0  
9.44  
103.0  
120.0  
10.20  
113.0  
116.0  
10.60  
117.0  
111.0  
11.00  
122.0  
102.0  
11.70  
132.0  
127.0  
9.14  
103.0  
124.0  
9.70  
108.0  
117.0  
10.90  
118.0  
114.0  
11.50  
123.0  
110.0  
12.20  
128.0  
103.0  
13.70  
138.0  
35  
150.0  
9.26  
101.0  
145.0  
9.71  
105.0  
135.0  
10.60  
115.0  
130.0  
11.00  
119.0  
126.0  
11.40  
124.0  
116.0  
12.20  
134.0  
140.0  
9.19  
103.0  
137.0  
9.75  
108.0  
130.0  
11.00  
118.0  
126.0  
11.60  
123.0  
123.0  
12.30  
128.0  
115.0  
13.70  
138.0  
40  
166.0  
9.50  
103.0  
161.0  
9.98  
107.0  
150.0  
10.90  
116.0  
145.0  
11.40  
121.0  
140.0  
11.80  
126.0  
130.0  
12.70  
135.0  
155.0  
9.26  
103.0  
151.0  
9.81  
108.0  
144.0  
11.00  
118.0  
140.0  
11.70  
123.0  
136.0  
12.30  
128.0  
128.0  
13.80  
138.0  
45  
TC  
kW  
SDT  
182.0  
9.73  
105.0  
177.0  
10.30  
109.0  
166.0  
11.30  
118.0  
160.0  
11.70  
123.0  
155.0  
12.20  
127.0  
144.0  
13.10  
136.0  
TC  
kW  
SDT  
170.0  
9.37  
103.0  
166.0  
9.90  
108.0  
158.0  
11.10  
118.0  
154.0  
11.70  
123.0  
150.0  
12.40  
128.0  
141.0  
13.90  
138.0  
50  
TC  
186.0  
9.55  
182.0  
10.10  
109.0  
173.0  
11.30  
119.0  
169.0  
11.90  
124.0  
164.0  
12.60  
129.0  
155.0  
14.00  
139.0  
566D180  
50  
kW  
SDT  
104.0  
Air Temperature Entering Condenser (F)  
SST (F)  
80  
85  
95  
100  
105  
115  
566E180  
TC  
139.0  
12.30  
99.5  
134.0  
12.70  
104.0  
126.0  
13.60  
114.0  
121.0  
14.00  
118.0  
117.0  
14.40  
123.0  
108.0  
15.10  
133.0  
Air Temperature Entering Condenser (F)  
25  
30  
35  
40  
45  
kW  
SDT  
SST (F)  
80  
85  
95  
100  
105  
115  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
159.0  
12.90  
102.0  
154.0  
13.40  
107.0  
144.0  
14.30  
116.0  
139.0  
14.70  
121.0  
134.0  
15.20  
125.0  
125.0  
16.00  
135.0  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
141.0  
12.01  
101.0  
137.0  
12.60  
105.0  
129.0  
13.70  
115.0  
124.0  
14.30  
120.0  
120.0  
14.90  
125.0  
110.0  
16.10  
135.0  
20  
25  
30  
35  
40  
45  
179.0  
13.50  
105.0  
173.0  
14.00  
109.0  
163.0  
15.00  
119.0  
157.0  
15.50  
123.0  
152.0  
16.00  
128.0  
142.0  
16.90  
137.0  
156.0  
12.40  
102.0  
152.0  
12.90  
107.0  
143.0  
14.00  
116.0  
138.0  
14.60  
121.0  
133.0  
15.20  
126.0  
123.0  
16.40  
136.0  
198.0  
14.00  
108.0  
192.0  
14.60  
112.0  
181.0  
15.70  
121.0  
175.0  
16.30  
125.0  
170.0  
16.80  
130.0  
158.0  
17.80  
139.0  
171.0  
12.70  
104.0  
166.0  
13.20  
108.0  
157.0  
14.30  
118.0  
152.0  
14.90  
123.0  
147.0  
15.50  
127.0  
136.0  
16.70  
137.0  
218.0  
14.60  
110.0  
212.0  
15.20  
115.0  
199.0  
16.50  
124.0  
193.0  
17.00  
128.0  
187.0  
17.60  
132.0  
175.0  
18.70  
141.0  
187.0  
13.10  
105.0  
182.0  
13.60  
110.0  
172.0  
14.70  
119.0  
166.0  
15.30  
12.04  
161.0  
15.90  
129.0  
150.0  
17.10  
138.0  
TC  
kW  
SDT  
237.0  
15.20  
113.0  
231.0  
15.90  
117.0  
218.0  
17.20  
126.0  
211.0  
17.80  
130.0  
205.0  
18.40  
135.0  
192.0  
19.60  
144.0  
203.0  
13.50  
107.0  
198.0  
14.00  
112.0  
187.0  
15.10  
121.0  
181.0  
15.70  
126.0  
176.0  
16.30  
130.0  
164.0  
17.50  
140.0  
50  
221.0  
13.90  
109.0  
215.0  
14.50  
114.0  
204.0  
15.60  
123.0  
198.0  
16.10  
127.0  
192.0  
16.70  
132.0  
179.0  
17.90  
141.0  
566D240  
Air Temperature Entering Condenser (F)  
SST (F)  
239.0  
14.40  
111.0  
233.0  
14.90  
116.0  
221.0  
16.10  
125.0  
215.0  
16.70  
129.0  
208.0  
17.20  
134.0  
195.0  
18.40  
143.0  
80  
85  
95  
100  
105  
115  
50  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
175.0  
16.30  
104.0  
169.0  
16.80  
108.0  
157.0  
17.70  
117.0  
151.0  
18.20  
122.0  
145.0  
18.60  
126.0  
134.0  
19.40  
135.0  
25  
30  
35  
40  
45  
50  
566E240  
200.0  
17.20  
107.0  
193.0  
17.80  
111.0  
180.0  
18.80  
120.0  
173.0  
19.30  
125.0  
166.0  
19.80  
129.0  
154.0  
20.70  
138.0  
Air Temperature Entering Condenser (F)  
SST (F)  
80  
85  
95  
100  
105  
115  
224.0  
18.20  
110.0  
217.0  
18.80  
115.0  
202.0  
19.90  
123.0  
195.0  
20.50  
128.0  
188.0  
21.00  
132.0  
175.0  
22.00  
141.0  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
TC  
kW  
SDT  
184.0  
16.20  
105.0  
179.0  
17.00  
110.0  
170.0  
18.50  
119.0  
165.0  
19.40  
124.0  
160.0  
20.20  
129.0  
148.0  
21.70  
139.0  
20  
25  
30  
35  
40  
45  
50  
249.0  
19.10  
114.0  
241.0  
19.80  
118.0  
225.0  
21.00  
126.0  
218.0  
21.60  
131.0  
210.0  
22.20  
135.0  
195.0  
23.30  
144.0  
202.0  
16.80  
107.0  
197.0  
17.50  
112.0  
186.0  
19.00  
121.0  
181.0  
19.80  
126.0  
176.0  
20.60  
131.0  
163.0  
22.20  
140.0  
273.0  
20.10  
117.0  
265.0  
20.80  
121.0  
248.0  
22.10  
129.0  
240.0  
22.70  
134.0  
232.0  
23.40  
138.0  
216.0  
24.60  
146.0  
220.0  
17.30  
109.0  
214.0  
18.00  
113.0  
203.0  
19.50  
123.0  
197.0  
20.30  
127.0  
191.0  
21.10  
132.0  
179.0  
22.70  
141.0  
297.0  
21.00  
120.0  
289.0  
21.80  
124.0  
271.0  
23.20  
132.0  
262.0  
23.90  
137.0  
253.0  
24.60  
141.0  
236.0  
25.90  
149.0  
239.0  
18.00  
111.0  
233.0  
18.60  
116.0  
220.0  
20.10  
125.0  
214.0  
20.80  
129.0  
208.0  
21.60  
134.0  
194.0  
23.20  
143.0  
259.0  
18.70  
113.0  
253.0  
19.30  
118.0  
239.0  
20.70  
127.0  
232.0  
21.50  
131.0  
225.0  
22.20  
136.0  
211.0  
23.80  
145.0  
LEGEND  
Compressor Power  
kW  
SDT — Saturated Discharge Temperature at Compressor (F)  
SST — Saturated Suction Temperature (F)  
280.0  
19.40  
116.0  
273.0  
20.10  
120.0  
259.0  
21.50  
129.0  
252.0  
22.20  
134.0  
244.0  
22.90  
138.0  
229.0  
24.50  
147.0  
TC  
Gross Cooling Capacity (1000 Btuh)  
302.0  
20.20  
118.0  
295.0  
20.90  
123.0  
280.0  
22.30  
132.0  
272.0  
23.00  
136.0  
264.0  
23.70  
140.0  
247.0  
25.20  
149.0  
39  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS  
UNIT 566D150  
566D150/524A-C150 WITH HIGH CAPACITY 4-ROW COIL  
Evaporator Air — Cfm  
5000  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
3750  
6250  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
133.0  
133.0  
9.00  
131.0  
131.0  
9.44  
139.0  
123.0  
9.07  
136.0  
122.0  
9.54  
151.0  
103.0  
9.27  
148.0  
102.0  
9.75  
165.0  
83.1  
9.48  
161.0  
81.9  
9.99  
146.0  
146.0  
9.18  
143.0  
143.0  
9.66  
147.0  
142.0  
9.20  
144.0  
140.0  
9.69  
158.0  
119.0  
9.38  
155.0  
117.0  
9.88  
172.0  
92.7  
9.59  
169.0  
91.3  
10.10  
154.0  
154.0  
9.32  
152.0  
152.0  
9.82  
154.0  
154.0  
9.32  
151.0  
151.0  
9.81  
163.0  
133.0  
9.45  
160.0  
131.0  
9.96  
177.0  
101.0  
9.66  
173.0  
100.0  
10.20  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
126.0  
126.0  
10.40  
130.0  
119.0  
10.50  
142.0  
99.5  
10.70  
155.0  
79.3  
11.00  
138.0  
138.0  
10.60  
138.0  
137.0  
10.60  
148.0  
115.0  
10.90  
161.0  
88.8  
11.20  
146.0  
146.0  
10.80  
146.0  
146.0  
10.80  
153.0  
128.0  
11.00  
165.0  
97.5  
11.30  
95  
TC  
123.0  
123.0  
10.80  
121.0  
121.0  
11.30  
116.0  
116.0  
12.20  
127.0  
117.0  
10.90  
124.0  
116.0  
11.40  
118.0  
113.0  
12.30  
138.0  
98.2  
151.0  
78.0  
135.0  
135.0  
11.10  
132.0  
132.0  
11.60  
127.0  
127.0  
12.50  
135.0  
134.0  
11.10  
132.0  
132.0  
11.60  
127.0  
127.0  
12.50  
145.0  
113.0  
11.30  
141.0  
112.0  
11.80  
134.0  
109.0  
12.80  
157.0  
87.5  
143.0  
143.0  
11.30  
140.0  
140.0  
11.80  
134.0  
134.0  
12.80  
143.0  
143.0  
11.30  
140.0  
140.0  
11.80  
134.0  
134.0  
12.80  
149.0  
127.0  
11.50  
145.0  
125.0  
12.00  
138.0  
122.0  
12.90  
161.0  
96.2  
100  
105  
115  
SHC  
kW  
11.20  
11.50  
11.70  
11.80  
TC  
SHC  
kW  
TC  
SHC  
kW  
135.0  
96.8  
11.70  
129.0  
94.1  
12.60  
148.0  
76.8  
12.00  
141.0  
74.2  
13.00  
154.0  
86.1  
12.20  
146.0  
83.5  
13.20  
157.0  
94.8  
12.30  
149.0  
92.2  
13.30  
566D150/524A-B150 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
3750  
5000  
6250  
Air Entering  
Condenser  
(Edb)  
Evaporator Air — Ewb (F)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
127.0  
127.0  
8.93  
125.0  
125.0  
9.37  
134.0  
118.0  
9.01  
131.0  
117.0  
9.45  
146.0  
99.4  
9.19  
143.0  
98.2  
9.67  
160.0  
80.2  
9.40  
156.0  
78.9  
9.90  
140.0  
140.0  
9.09  
137.0  
137.0  
9.55  
142.0  
136.0  
9.12  
139.0  
134.0  
9.58  
153.0  
114.0  
9.31  
150.0  
112.0  
9.79  
167.0  
89.0  
9.51  
163.0  
87.6  
10.00  
148.0  
148.0  
9.22  
145.0  
145.0  
9.70  
148.0  
148.0  
9.22  
145.0  
145.0  
9.71  
158.0  
126.0  
9.37  
154.0  
125.0  
9.87  
172.0  
96.9  
9.58  
168.0  
95.6  
10.10  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
121.0  
121.0  
10.30  
125.0  
114.0  
10.30  
137.0  
95.6  
10.60  
150.0  
76.4  
10.90  
132.0  
132.0  
10.50  
133.0  
130.0  
10.50  
143.0  
110.0  
10.70  
156.0  
85.1  
11.00  
140.0  
140.0  
10.70  
140.0  
140.0  
10.70  
147.0  
122.0  
10.80  
160.0  
93.0  
11.10  
95  
TC  
118.0  
118.0  
10.70  
116.0  
116.0  
11.20  
111.0  
111.0  
12.00  
122.0  
112.0  
10.80  
119.0  
111.0  
11.20  
113.0  
108.0  
12.10  
134.0  
94.3  
146.0  
75.2  
129.0  
129.0  
11.00  
127.0  
127.0  
11.40  
121.0  
121.0  
12.40  
130.0  
128.0  
11.00  
127.0  
126.0  
11.40  
121.0  
121.0  
12.40  
140.0  
108.0  
11.20  
136.0  
107.0  
11.70  
129.0  
104.0  
12.60  
152.0  
83.8  
137.0  
137.0  
11.20  
134.0  
134.0  
11.60  
128.0  
128.0  
12.60  
137.0  
137.0  
11.20  
134.0  
134.0  
11.60  
128.0  
128.0  
12.60  
144.0  
121.0  
11.30  
140.0  
119.0  
11.80  
133.0  
116.0  
12.80  
156.0  
91.7  
100  
105  
115  
SHC  
kW  
11.10  
11.40  
11.60  
11.70  
TC  
SHC  
kW  
TC  
SHC  
kW  
131.0  
92.9  
11.50  
124.0  
90.3  
12.50  
143.0  
73.9  
11.90  
136.0  
71.4  
12.90  
149.0  
82.5  
12.10  
141.0  
79.9  
13.10  
153.0  
90.4  
12.20  
145.0  
87.8  
13.20  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
40  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS (cont)  
UNIT 566D150 (cont)  
566D150/524A-C180 WITH HIGH CAPACITY 4-ROW COIL  
Evaporator Air — Cfm  
6000  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
4500  
7500  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
142.0  
142.0  
9.13  
140.0  
140.0  
9.60  
145.0  
136.0  
9.17  
142.0  
134.0  
9.65  
157.0  
114.0  
9.37  
154.0  
112.0  
9.86  
171.0  
89.6  
9.57  
168.0  
88.3  
10.10  
154.0  
154.0  
9.31  
151.0  
151.0  
9.81  
154.0  
154.0  
9.32  
151.0  
151.0  
9.81  
164.0  
131.0  
9.47  
160.0  
129.0  
9.97  
178.0  
100.0  
9.66  
174.0  
99.1  
10.20  
163.0  
163.0  
9.44  
160.0  
160.0  
9.96  
163.0  
163.0  
9.45  
160.0  
160.0  
9.96  
168.0  
146.0  
9.53  
165.0  
145.0  
10.00  
182.0  
110.0  
9.72  
178.0  
109.0  
10.30  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
134.0  
134.0  
10.50  
136.0  
131.0  
10.60  
147.0  
109.0  
10.80  
160.0  
85.7  
11.20  
146.0  
146.0  
10.80  
146.0  
146.0  
10.80  
153.0  
127.0  
11.00  
166.0  
96.4  
11.30  
153.0  
153.0  
11.00  
153.0  
153.0  
11.00  
157.0  
142.0  
11.10  
170.0  
106.0  
11.40  
95  
TC  
132.0  
132.0  
11.00  
129.0  
129.0  
11.50  
124.0  
124.0  
12.40  
133.0  
129.0  
11.10  
130.0  
127.0  
11.50  
124.0  
123.0  
12.50  
144.0  
108.0  
11.30  
140.0  
107.0  
11.80  
133.0  
104.0  
12.80  
157.0  
84.4  
143.0  
143.0  
11.30  
140.0  
140.0  
11.80  
134.0  
134.0  
12.80  
143.0  
143.0  
11.30  
140.0  
140.0  
11.80  
134.0  
134.0  
12.80  
150.0  
125.0  
11.50  
146.0  
124.0  
12.00  
139.0  
121.0  
13.00  
162.0  
95.1  
150.0  
150.0  
11.50  
147.0  
147.0  
12.00  
140.0  
140.0  
13.00  
150.0  
150.0  
11.50  
147.0  
147.0  
12.00  
140.0  
140.0  
13.00  
154.0  
140.0  
11.60  
150.0  
138.0  
12.10  
142.0  
135.0  
13.10  
166.0  
105.0  
11.90  
162.0  
104.0  
12.40  
153.0  
101.0  
13.50  
100  
105  
115  
SHC  
kW  
11.70  
11.80  
TC  
SHC  
kW  
TC  
SHC  
kW  
153.0  
83.1  
12.20  
146.0  
80.5  
13.20  
158.0  
93.8  
12.30  
150.0  
91.0  
13.40  
566D150/524A-B180 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
4500  
6000  
7500  
Air Entering  
Condenser  
(Edb)  
Evaporator Air — Ewb (F)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
140.0  
140.0  
9.09  
137.0  
137.0  
9.56  
144.0  
134.0  
9.14  
140.0  
132.0  
9.61  
156.0  
112.0  
9.34  
152.0  
110.0  
9.84  
170.0  
88.3  
9.55  
166.0  
87.0  
10.10  
152.0  
152.0  
9.28  
149.0  
149.0  
9.78  
152.0  
152.0  
9.28  
149.0  
149.0  
9.77  
162.0  
128.0  
9.44  
159.0  
127.0  
9.94  
176.0  
98.7  
9.65  
172.0  
97.3  
10.20  
160.0  
160.0  
9.41  
157.0  
157.0  
9.92  
160.0  
160.0  
9.41  
157.0  
157.0  
9.92  
167.0  
143.0  
9.51  
163.0  
142.0  
10.00  
181.0  
108.0  
9.71  
176.0  
107.0  
10.20  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
132.0  
132.0  
10.50  
134.0  
129.0  
10.50  
146.0  
107.0  
10.80  
159.0  
84.4  
11.10  
143.0  
143.0  
10.70  
143.0  
143.0  
10.70  
151.0  
124.0  
10.90  
165.0  
94.6  
11.20  
151.0  
151.0  
10.90  
151.0  
151.0  
10.90  
155.0  
138.0  
11.00  
168.0  
104.0  
11.30  
95  
TC  
130.0  
130.0  
11.00  
127.0  
127.0  
11.40  
121.0  
121.0  
12.40  
131.0  
127.0  
11.00  
128.0  
125.0  
11.50  
122.0  
121.0  
12.40  
142.0  
106.0  
11.30  
139.0  
105.0  
11.80  
131.0  
102.0  
12.70  
155.0  
83.1  
140.0  
140.0  
11.30  
137.0  
137.0  
11.70  
131.0  
131.0  
12.70  
140.0  
140.0  
11.20  
137.0  
137.0  
11.70  
131.0  
131.0  
12.70  
148.0  
123.0  
11.40  
144.0  
12.01  
11.90  
136.0  
118.0  
12.90  
161.0  
93.3  
148.0  
148.0  
11.40  
145.0  
145.0  
11.90  
138.0  
138.0  
12.90  
148.0  
148.0  
11.40  
145.0  
145.0  
11.90  
138.0  
138.0  
12.90  
152.0  
137.0  
11.50  
148.0  
135.0  
12.00  
140.0  
132.0  
13.00  
164.0  
103.0  
11.80  
160.0  
101.0  
12.40  
152.0  
98.7  
13.40  
100  
105  
115  
SHC  
kW  
11.60  
11.80  
TC  
SHC  
kW  
TC  
SHC  
kW  
151.0  
81.7  
12.10  
144.0  
79.0  
13.10  
157.0  
91.9  
12.30  
148.0  
89.2  
13.30  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
41  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS (cont)  
UNIT 566D180  
566D180/524A-C180 WITH HIGH-CAPACITY 4-ROW COIL  
Evaporator Air — Cfm  
6000  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
4500  
7500  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
167.0  
167.0  
13.10  
165.0  
165.0  
13.70  
177.0  
152.0  
13.40  
174.0  
150.0  
14.00  
192.0  
128.0  
13.90  
189.0  
127.0  
14.50  
209.0  
104.0  
14.40  
205.0  
102.0  
15.00  
183.0  
183.0  
13.60  
180.0  
180.0  
14.20  
187.0  
175.0  
13.70  
184.0  
174.0  
14.30  
202.0  
146.0  
14.10  
198.0  
145.0  
14.80  
219.0  
115.0  
14.70  
214.0  
113.0  
15.30  
194.0  
194.0  
13.90  
191.0  
191.0  
14.60  
195.0  
193.0  
13.90  
192.0  
191.0  
14.60  
208.0  
163.0  
14.30  
204.0  
161.0  
15.00  
225.0  
125.0  
14.80  
220.0  
124.0  
15.50  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
160.0  
160.0  
14.90  
167.0  
147.0  
15.20  
182.0  
123.0  
15.70  
197.0  
99.3  
16.40  
174.0  
174.0  
15.50  
177.0  
170.0  
15.60  
190.0  
141.0  
16.10  
206.0  
110.0  
16.70  
185.0  
185.0  
15.90  
185.0  
185.0  
15.90  
196.0  
158.0  
16.30  
211.0  
120.0  
16.90  
95  
TC  
157.0  
157.0  
15.50  
154.0  
154.0  
16.00  
148.0  
148.0  
17.30  
164.0  
145.0  
15.80  
160.0  
144.0  
16.30  
153.0  
140.0  
17.50  
178.0  
122.0  
16.40  
174.0  
120.0  
17.00  
166.0  
117.0  
18.20  
193.0  
97.8  
171.0  
171.0  
16.10  
168.0  
168.0  
16.70  
162.0  
162.0  
18.00  
173.0  
168.0  
16.20  
169.0  
165.0  
16.80  
162.0  
161.0  
18.00  
186.0  
140.0  
16.70  
182.0  
138.0  
17.40  
174.0  
135.0  
18.60  
202.0  
109.0  
17.40  
197.0  
107.0  
18.10  
188.0  
104.0  
19.40  
181.0  
181.0  
16.50  
178.0  
178.0  
17.20  
171.0  
171.0  
18.50  
181.0  
181.0  
16.50  
178.0  
178.0  
17.20  
171.0  
171.0  
18.50  
191.0  
156.0  
17.00  
187.0  
154.0  
17.60  
178.0  
151.0  
18.90  
207.0  
119.0  
17.60  
202.0  
117.0  
18.30  
193.0  
114.0  
19.70  
100  
105  
115  
SHC  
kW  
17.00  
TC  
SHC  
kW  
TC  
SHC  
kW  
189.0  
96.3  
17.70  
181.0  
93.2  
19.00  
566D180/524A-B180 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
4500  
6000  
7500  
Air Entering  
Condenser  
(Edb)  
Evaporator Air — Ewb (F)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
165.0  
165.0  
13.00  
162.0  
162.0  
13.60  
175.0  
149.0  
13.30  
171.0  
148.0  
13.90  
190.0  
126.0  
13.80  
187.0  
125.0  
14.40  
207.0  
102.0  
14.30  
203.0  
101.0  
15.00  
180.0  
180.0  
13.50  
177.0  
177.0  
14.10  
185.0  
172.0  
13.60  
181.0  
170.0  
14.20  
200.0  
143.0  
14.10  
196.0  
142.0  
14.70  
217.0  
113.0  
14.60  
213.0  
112.0  
15.30  
191.0  
191.0  
13.80  
188.0  
188.0  
14.50  
193.0  
190.0  
13.90  
189.0  
187.0  
14.50  
206.0  
159.0  
14.30  
202.0  
158.0  
14.90  
223.0  
123.0  
14.80  
218.0  
121.0  
15.50  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
157.0  
157.0  
14.80  
165.0  
144.0  
15.10  
179.0  
121.0  
15.70  
195.0  
97.9  
16.30  
171.0  
171.0  
15.30  
174.0  
166.0  
15.50  
188.0  
139.0  
16.00  
204.0  
108.0  
16.60  
182.0  
182.0  
15.80  
182.0  
181.0  
15.80  
193.0  
154.0  
16.20  
209.0  
118.0  
16.90  
95  
TC  
154.0  
154.0  
15.30  
151.0  
151.0  
15.90  
146.0  
146.0  
17.10  
161.0  
143.0  
15.70  
158.0  
141.0  
16.20  
151.0  
137.0  
17.40  
176.0  
120.0  
16.30  
172.0  
118.0  
16.90  
164.0  
115.0  
18.10  
191.0  
96.3  
168.0  
168.0  
16.00  
165.0  
165.0  
16.60  
159.0  
159.0  
17.80  
170.0  
164.0  
16.10  
167.0  
162.0  
16.70  
160.0  
157.0  
17.90  
184.0  
137.0  
16.70  
180.0  
135.0  
17.30  
171.0  
132.0  
18.50  
199.0  
107.0  
17.30  
195.0  
105.0  
18.00  
186.0  
102.0  
19.30  
178.0  
178.0  
16.40  
175.0  
175.0  
17.00  
168.0  
168.0  
18.30  
178.0  
178.0  
16.40  
175.0  
175.0  
17.00  
168.0  
168.0  
18.30  
189.0  
153.0  
16.90  
185.0  
151.0  
17.50  
176.0  
147.0  
18.80  
205.0  
117.0  
17.50  
200.0  
115.0  
18.20  
191.0  
112.0  
19.50  
100  
105  
115  
SHC  
kW  
17.00  
TC  
SHC  
kW  
TC  
SHC  
kW  
187.0  
94.8  
17.60  
179.0  
91.7  
18.90  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
42  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS (cont)  
UNIT 566D180 (cont)  
566D180/524A-C240 WITH HIGH-CAPACITY 4-ROW COIL  
Evaporator Air — Cfm  
8,000  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
6,000  
10,000  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
196.0  
196.0  
13.90  
193.0  
193.0  
14.60  
200.0  
188.0  
14.00  
196.0  
186.0  
14.70  
215.0  
156.0  
14.50  
211.0  
154.0  
15.20  
234.0  
123.0  
15.00  
229.0  
121.0  
15.70  
212.0  
212.0  
14.40  
209.0  
209.0  
15.10  
212.0  
212.0  
14.40  
209.0  
209.0  
15.10  
224.0  
181.0  
14.70  
220.0  
179.0  
15.40  
242.0  
138.0  
15.20  
237.0  
136.0  
16.00  
223.0  
223.0  
14.70  
219.0  
219.0  
15.40  
224.0  
224.0  
14.70  
220.0  
220.0  
15.40  
230.0  
203.0  
14.90  
225.0  
201.0  
15.60  
247.0  
152.0  
15.30  
242.0  
151.0  
16.10  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
186.0  
186.0  
15.90  
188.0  
182.0  
16.00  
203.0  
151.0  
16.50  
219.0  
118.0  
17.10  
201.0  
201.0  
16.50  
201.0  
201.0  
16.50  
210.0  
175.0  
16.80  
227.0  
133.0  
17.40  
211.0  
211.0  
16.80  
211.0  
211.0  
16.80  
216.0  
197.0  
17.00  
231.0  
147.0  
17.60  
95  
TC  
183.0  
183.0  
16.50  
179.0  
179.0  
17.20  
172.0  
172.0  
18.50  
184.0  
179.0  
16.60  
180.0  
177.0  
17.20  
172.0  
172.0  
18.50  
198.0  
149.0  
17.20  
193.0  
147.0  
17.80  
184.0  
144.0  
19.10  
215.0  
116.0  
17.90  
210.0  
114.0  
18.60  
200.0  
111.0  
20.00  
197.0  
197.0  
17.20  
193.0  
193.0  
17.80  
185.0  
185.0  
19.20  
197.0  
197.0  
17.10  
193.0  
193.0  
17.80  
185.0  
185.0  
19.20  
205.0  
173.0  
17.50  
201.0  
171.0  
18.20  
191.0  
168.0  
19.50  
222.0  
131.0  
18.10  
216.0  
129.0  
18.90  
206.0  
126.0  
20.30  
207.0  
207.0  
17.60  
203.0  
203.0  
18.30  
194.0  
194.0  
19.70  
207.0  
207.0  
17.50  
203.0  
203.0  
18.30  
194.0  
194.0  
19.70  
211.0  
195.0  
17.70  
206.0  
192.0  
18.40  
196.0  
188.0  
19.80  
226.0  
146.0  
18.30  
221.0  
144.0  
19.00  
210.0  
140.0  
20.50  
100  
105  
115  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
566D180/524A-B240 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
6,000  
8,000  
10,000  
Air Entering  
Condenser  
(Edb)  
Evaporator Air — Ewb (F)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
186.0  
186.0  
13.70  
183.0  
183.0  
14.30  
190.0  
178.0  
13.80  
186.0  
176.0  
14.40  
205.0  
148.0  
14.20  
200.0  
147.0  
14.90  
222.0  
117.0  
14.70  
217.0  
115.0  
15.40  
201.0  
201.0  
14.10  
197.0  
197.0  
14.80  
201.0  
201.0  
14.10  
197.0  
197.0  
14.80  
212.0  
171.0  
14.50  
208.0  
169.0  
15.10  
230.0  
130.0  
15.00  
225.0  
129.0  
15.70  
211.0  
211.0  
14.40  
207.0  
207.0  
15.10  
211.0  
211.0  
14.40  
207.0  
207.0  
15.10  
218.0  
190.0  
14.60  
213.0  
188.0  
15.30  
235.0  
143.0  
15.10  
230.0  
142.0  
15.80  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
176.0  
176.0  
15.50  
179.0  
172.0  
15.60  
192.0  
143.0  
16.20  
208.0  
112.0  
16.80  
190.0  
190.0  
16.10  
190.0  
190.0  
16.10  
199.0  
165.0  
16.50  
215.0  
125.0  
17.10  
199.0  
199.0  
16.50  
199.0  
199.0  
16.50  
204.0  
184.0  
16.70  
220.0  
138.0  
17.30  
95  
TC  
173.0  
173.0  
16.20  
170.0  
170.0  
16.80  
163.0  
163.0  
18.10  
175.0  
170.0  
16.20  
171.0  
167.0  
16.90  
164.0  
163.0  
18.10  
188.0  
142.0  
16.80  
184.0  
140.0  
17.50  
175.0  
136.0  
18.70  
204.0  
110.0  
17.50  
199.0  
108.0  
18.20  
190.0  
105.0  
19.50  
186.0  
186.0  
16.80  
183.0  
183.0  
17.40  
175.0  
175.0  
18.70  
186.0  
186.0  
16.70  
183.0  
183.0  
17.40  
175.0  
175.0  
18.70  
195.0  
163.0  
17.10  
190.0  
162.0  
17.80  
181.0  
158.0  
19.10  
211.0  
124.0  
17.80  
206.0  
122.0  
18.50  
196.0  
119.0  
19.80  
195.0  
195.0  
17.10  
191.0  
191.0  
17.80  
183.0  
183.0  
19.20  
195.0  
195.0  
17.10  
191.0  
191.0  
17.80  
183.0  
183.0  
19.10  
200.0  
182.0  
17.30  
195.0  
180.0  
18.00  
186.0  
175.0  
19.30  
215.0  
137.0  
18.00  
210.0  
135.0  
18.70  
199.0  
132.0  
20.00  
100  
105  
115  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
43  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS (cont)  
UNIT 566D240  
566D240/524A-C300 WITH HIGH-CAPACITY 4-ROW COIL  
Evaporator Air — Cfm  
10,000  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
7,500  
12,500  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
244.0  
244.0  
18.90  
239.0  
239.0  
19.70  
249.0  
233.0  
19.20  
244.0  
231.0  
19.90  
268.0  
194.0  
19.90  
263.0  
192.0  
20.70  
291.0  
152.0  
20.80  
284.0  
150.0  
21.60  
264.0  
264.0  
19.70  
259.0  
259.0  
20.50  
264.0  
264.0  
19.70  
259.0  
259.0  
20.50  
279.0  
224.0  
20.30  
273.0  
222.0  
21.10  
301.0  
171.0  
21.20  
294.0  
169.0  
22.00  
278.0  
278.0  
20.30  
272.0  
272.0  
21.10  
278.0  
278.0  
20.30  
272.0  
272.0  
21.10  
286.0  
252.0  
20.60  
280.0  
249.0  
21.40  
307.0  
189.0  
21.40  
300.0  
187.0  
22.30  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
230.0  
230.0  
21.30  
233.0  
225.0  
21.40  
251.0  
187.0  
22.20  
272.0  
146.0  
23.20  
249.0  
249.0  
22.10  
249.0  
249.0  
22.10  
260.0  
217.0  
22.70  
281.0  
164.0  
23.70  
261.0  
261.0  
22.70  
261.0  
261.0  
22.70  
267.0  
243.0  
23.00  
286.0  
182.0  
23.90  
95  
TC  
226.0  
226.0  
22.00  
221.0  
221.0  
22.80  
212.0  
212.0  
24.30  
228.0  
222.0  
22.10  
222.0  
219.0  
22.80  
212.0  
211.0  
24.30  
245.0  
184.0  
23.00  
239.0  
182.0  
23.70  
226.0  
177.0  
25.20  
265.0  
143.0  
24.00  
259.0  
141.0  
24.80  
245.0  
136.0  
26.40  
244.0  
244.0  
22.90  
238.0  
238.0  
23.70  
227.0  
227.0  
25.30  
244.0  
244.0  
22.90  
238.0  
238.0  
23.70  
227.0  
227.0  
25.30  
254.0  
214.0  
23.50  
247.0  
212.0  
24.20  
235.0  
206.0  
25.80  
274.0  
162.0  
24.50  
267.0  
160.0  
25.30  
253.0  
155.0  
26.90  
256.0  
256.0  
23.60  
250.0  
250.0  
24.40  
238.0  
238.0  
26.00  
256.0  
256.0  
23.60  
250.0  
250.0  
24.40  
238.0  
238.0  
26.00  
260.0  
240.0  
23.80  
254.0  
237.0  
24.60  
240.0  
231.0  
26.10  
279.0  
180.0  
24.80  
272.0  
177.0  
25.60  
257.0  
172.0  
27.20  
100  
105  
115  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
566D240/524A-B300 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
10,000  
Evaporator Air — Ewb (F)  
7,500  
12,500  
Air Entering  
Condenser  
(Edb)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
230.0  
230.0  
18.40  
226.0  
226.0  
19.20  
236.0  
219.0  
18.60  
231.0  
217.0  
19.40  
255.0  
183.0  
19.40  
250.0  
181.0  
20.20  
277.0  
144.0  
20.20  
271.0  
142.0  
21.00  
249.0  
249.0  
19.10  
244.0  
244.0  
19.90  
249.0  
248.0  
19.20  
244.0  
244.0  
19.90  
266.0  
209.0  
19.80  
259.0  
207.0  
20.60  
287.0  
161.0  
20.60  
281.0  
159.0  
21.50  
262.0  
262.0  
19.60  
256.0  
256.0  
20.40  
262.0  
262.0  
19.60  
256.0  
256.0  
20.40  
272.0  
233.0  
20.10  
266.0  
231.0  
20.80  
293.0  
176.0  
20.90  
287.0  
174.0  
21.70  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
218.0  
218.0  
20.60  
221.0  
211.0  
20.80  
239.0  
176.0  
21.70  
259.0  
138.0  
22.60  
235.0  
235.0  
21.50  
235.0  
235.0  
21.50  
248.0  
203.0  
22.10  
268.0  
154.0  
23.10  
246.0  
246.0  
22.00  
246.0  
246.0  
22.00  
254.0  
226.0  
22.40  
273.0  
169.0  
23.30  
95  
TC  
214.0  
214.0  
21.40  
209.0  
209.0  
22.10  
201.0  
201.0  
23.60  
217.0  
208.0  
21.50  
212.0  
206.0  
22.20  
202.0  
199.0  
23.70  
233.0  
174.0  
22.40  
228.0  
172.0  
23.10  
216.0  
167.0  
24.60  
253.0  
136.0  
23.40  
247.0  
133.0  
24.20  
235.0  
129.0  
25.80  
230.0  
230.0  
22.20  
225.0  
225.0  
23.00  
215.0  
215.0  
24.60  
230.0  
230.0  
22.20  
225.0  
225.0  
23.00  
215.0  
215.0  
24.50  
242.0  
200.0  
22.90  
236.0  
198.0  
23.60  
224.0  
193.0  
25.10  
261.0  
152.0  
23.80  
255.0  
150.0  
24.60  
242.0  
145.0  
26.20  
241.0  
241.0  
22.80  
236.0  
236.0  
23.60  
226.0  
226.0  
25.20  
241.0  
241.0  
22.80  
236.0  
236.0  
23.60  
226.0  
226.0  
25.20  
248.0  
223.0  
23.20  
242.0  
220.0  
23.90  
229.0  
214.0  
25.40  
266.0  
167.0  
24.10  
260.0  
165.0  
24.90  
246.0  
160.0  
26.50  
100  
105  
115  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
44  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS (cont)  
UNIT 566E150  
566E150/524A-C120 WITH HIGH-CAPACITY 4-ROW COIL  
Evaporator Air — Cfm  
4000  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
3000  
5000  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
126.0  
126.0  
9.13  
125.0  
125.0  
9.68  
135.0  
112.0  
9.18  
133.0  
111.0  
9.72  
148.0  
95.4  
9.22  
146.0  
94.5  
9.79  
161.0  
78.5  
9.31  
159.0  
77.5  
9.87  
140.0  
140.0  
9.19  
138.0  
138.0  
9.74  
144.0  
130.0  
9.20  
142.0  
129.0  
9.77  
156.0  
109.0  
9.26  
154.0  
108.0  
9.82  
170.0  
87.0  
9.37  
168.0  
86.0  
9.92  
149.0  
149.0  
9.22  
147.0  
147.0  
9.78  
151.0  
146.0  
9.23  
148.0  
144.0  
9.80  
162.0  
122.0  
9.30  
159.0  
121.0  
9.85  
176.0  
94.8  
9.43  
173.0  
93.8  
9.98  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
121.0  
121.0  
10.90  
129.0  
109.0  
11.00  
141.0  
92.4  
11.00  
154.0  
75.6  
11.10  
134.0  
134.0  
11.00  
137.0  
127.0  
11.00  
149.0  
106.0  
11.00  
162.0  
84.0  
11.10  
143.0  
143.0  
11.00  
144.0  
141.0  
11.00  
154.0  
118.0  
11.10  
167.0  
91.8  
11.20  
95  
TC  
119.0  
119.0  
11.60  
118.0  
118.0  
12.30  
114.0  
114.0  
13.70  
127.0  
108.0  
11.60  
124.0  
107.0  
12.30  
120.0  
104.0  
13.80  
138.0  
91.4  
151.0  
74.6  
132.0  
132.0  
11.60  
130.0  
130.0  
12.30  
126.0  
126.0  
13.80  
135.0  
126.0  
11.60  
132.0  
124.0  
12.30  
127.0  
122.0  
13.80  
146.0  
105.0  
11.70  
143.0  
104.0  
12.40  
137.0  
101.0  
13.80  
159.0  
82.9  
141.0  
141.0  
11.60  
138.0  
138.0  
12.30  
134.0  
134.0  
13.80  
141.0  
140.0  
11.70  
139.0  
138.0  
12.40  
134.0  
134.0  
13.80  
151.0  
117.0  
11.70  
148.0  
116.0  
12.40  
142.0  
114.0  
13.90  
164.0  
90.7  
100  
105  
115  
SHC  
kW  
11.70  
11.70  
11.80  
11.80  
TC  
SHC  
kW  
TC  
SHC  
kW  
136.0  
90.3  
12.40  
131.0  
88.0  
13.80  
149.0  
73.5  
12.40  
143.0  
71.4  
13.90  
156.0  
81.9  
12.50  
150.0  
79.6  
13.90  
161.0  
89.6  
12.50  
154.0  
87.4  
14.00  
566E150/524A-B120 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
3000  
4000  
5000  
Air Entering  
Condenser  
(Edb)  
Evaporator Air — Ewb (F)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
119.0  
119.0  
9.09  
118.0  
118.0  
9.66  
128.0  
106.0  
9.15  
126.0  
105.0  
9.72  
140.0  
90.4  
9.18  
138.0  
89.5  
9.75  
153.0  
74.3  
9.23  
151.0  
73.4  
9.81  
131.0  
131.0  
9.15  
130.0  
130.0  
9.72  
136.0  
122.0  
9.16  
134.0  
121.0  
9.72  
148.0  
103.0  
9.21  
146.0  
102.0  
9.77  
161.0  
82.0  
9.30  
159.0  
81.2  
9.87  
140.0  
140.0  
9.19  
138.0  
138.0  
9.75  
142.0  
136.0  
9.19  
140.0  
135.0  
9.75  
153.0  
114.0  
9.25  
151.0  
113.0  
9.80  
166.0  
89.0  
9.33  
164.0  
88.1  
9.89  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
115.0  
115.0  
10.90  
122.0  
103.0  
10.90  
134.0  
87.7  
11.00  
146.0  
71.7  
11.00  
126.0  
126.0  
10.90  
130.0  
119.0  
10.90  
141.0  
99.9  
11.00  
154.0  
79.3  
11.10  
134.0  
134.0  
11.00  
136.0  
132.0  
11.00  
146.0  
111.0  
11.00  
158.0  
86.3  
11.10  
95  
TC  
113.0  
113.0  
11.60  
111.0  
111.0  
12.20  
108.0  
108.0  
13.70  
120.0  
102.0  
11.60  
118.0  
101.0  
12.30  
114.0  
99.0  
13.70  
131.0  
86.7  
144.0  
70.8  
124.0  
124.0  
11.60  
122.0  
122.0  
12.30  
118.0  
118.0  
13.70  
128.0  
118.0  
11.60  
125.0  
117.0  
12.30  
121.0  
114.0  
13.80  
139.0  
98.9  
151.0  
78.4  
132.0  
132.0  
11.60  
130.0  
130.0  
12.30  
126.0  
126.0  
13.80  
133.0  
131.0  
11.60  
131.0  
129.0  
12.30  
126.0  
126.0  
13.80  
143.0  
110.0  
11.70  
140.0  
109.0  
12.40  
135.0  
107.0  
13.80  
156.0  
85.3  
100  
105  
115  
SHC  
kW  
11.60  
11.70  
11.60  
11.70  
11.80  
TC  
SHC  
kW  
TC  
SHC  
kW  
129.0  
85.7  
12.30  
124.0  
83.7  
13.80  
141.0  
69.8  
12.40  
136.0  
67.8  
13.90  
136.0  
97.9  
12.30  
131.0  
95.8  
13.80  
148.0  
77.5  
12.40  
143.0  
75.4  
13.90  
153.0  
84.3  
12.40  
147.0  
82.3  
13.90  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
45  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS (cont)  
UNIT 566E150 (cont)  
566E150/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL  
Evaporator Air — Cfm  
5000  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
3750  
6250  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
139.0  
139.0  
9.18  
137.0  
137.0  
9.74  
145.0  
127.0  
9.21  
143.0  
126.0  
9.76  
158.0  
107.0  
9.27  
155.0  
106.0  
9.84  
172.0  
86.2  
9.38  
169.0  
85.3  
9.95  
152.0  
152.0  
9.25  
150.0  
150.0  
9.80  
154.0  
148.0  
9.24  
151.0  
146.0  
9.82  
165.0  
123.0  
9.33  
163.0  
122.0  
9.90  
180.0  
96.1  
9.48  
177.0  
95.1  
10.00  
161.0  
161.0  
9.29  
159.0  
159.0  
9.86  
161.0  
161.0  
9.31  
159.0  
159.0  
9.87  
170.0  
138.0  
9.37  
168.0  
137.0  
9.93  
185.0  
105.0  
9.54  
182.0  
104.0  
10.10  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
133.0  
133.0  
11.00  
138.0  
124.0  
11.00  
150.0  
104.0  
11.10  
164.0  
83.3  
11.20  
146.0  
146.0  
11.00  
147.0  
144.0  
11.00  
157.0  
120.0  
11.10  
171.0  
93.1  
11.20  
154.0  
154.0  
11.10  
154.0  
154.0  
11.10  
162.0  
134.0  
11.10  
175.0  
102.0  
11.30  
95  
TC  
131.0  
131.0  
11.60  
129.0  
129.0  
12.30  
125.0  
125.0  
13.80  
136.0  
123.0  
11.60  
133.0  
121.0  
12.30  
128.0  
119.0  
13.80  
148.0  
103.0  
11.70  
145.0  
102.0  
12.40  
139.0  
99.4  
13.90  
161.0  
82.2  
143.0  
143.0  
11.70  
141.0  
141.0  
12.40  
136.0  
136.0  
13.80  
144.0  
142.0  
11.70  
142.0  
140.0  
12.40  
136.0  
136.0  
13.90  
154.0  
119.0  
11.80  
152.0  
118.0  
12.50  
145.0  
115.0  
13.90  
168.0  
92.1  
152.0  
152.0  
11.70  
149.0  
149.0  
12.40  
144.0  
144.0  
13.90  
152.0  
152.0  
11.70  
149.0  
149.0  
12.40  
144.0  
144.0  
13.90  
159.0  
133.0  
11.80  
156.0  
132.0  
12.50  
150.0  
129.0  
13.90  
172.0  
101.0  
11.90  
169.0  
100.0  
12.60  
162.0  
97.9  
14.10  
100  
105  
115  
SHC  
kW  
11.80  
11.90  
TC  
SHC  
kW  
TC  
SHC  
kW  
158.0  
81.1  
12.50  
152.0  
78.9  
14.00  
165.0  
90.9  
12.60  
158.0  
88.7  
14.00  
566E150/524A-B150 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
3750  
5000  
6250  
Air Entering  
Condenser  
(Edb)  
Evaporator Air — Ewb (F)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
130.0  
130.0  
9.14  
129.0  
129.0  
9.70  
137.0  
120.0  
9.18  
135.0  
119.0  
9.73  
150.0  
101.0  
9.22  
147.0  
100.0  
9.78  
163.0  
81.6  
9.32  
161.0  
80.7  
9.88  
143.0  
143.0  
9.20  
141.0  
141.0  
9.76  
145.0  
138.0  
9.20  
143.0  
137.0  
9.76  
157.0  
115.0  
9.27  
154.0  
114.0  
9.82  
171.0  
90.5  
9.38  
168.0  
89.5  
9.93  
151.0  
151.0  
9.24  
149.0  
149.0  
9.79  
151.0  
151.0  
9.23  
149.0  
149.0  
9.79  
162.0  
128.0  
9.30  
159.0  
127.0  
9.85  
176.0  
98.5  
9.43  
173.0  
97.5  
9.98  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
125.0  
125.0  
10.90  
131.0  
117.0  
11.00  
143.0  
98.0  
11.00  
156.0  
78.7  
11.10  
137.0  
137.0  
11.00  
138.0  
134.0  
11.00  
149.0  
112.0  
11.00  
162.0  
87.5  
11.10  
145.0  
145.0  
11.00  
145.0  
145.0  
11.00  
154.0  
125.0  
11.10  
167.0  
95.6  
11.20  
95  
TC  
123.0  
123.0  
11.60  
122.0  
122.0  
12.30  
118.0  
118.0  
13.80  
128.0  
115.0  
11.60  
126.0  
114.0  
12.30  
121.0  
112.0  
13.80  
140.0  
97.0  
153.0  
77.7  
135.0  
135.0  
11.60  
132.0  
132.0  
12.30  
128.0  
128.0  
13.80  
136.0  
132.0  
11.70  
133.0  
131.0  
12.30  
128.0  
128.0  
13.80  
146.0  
111.0  
11.70  
144.0  
110.0  
12.40  
138.0  
108.0  
13.90  
160.0  
86.5  
143.0  
143.0  
11.70  
140.0  
140.0  
12.30  
135.0  
135.0  
13.80  
143.0  
143.0  
11.70  
140.0  
140.0  
12.40  
135.0  
135.0  
13.80  
151.0  
124.0  
11.70  
148.0  
123.0  
12.40  
142.0  
120.0  
13.90  
164.0  
94.5  
100  
105  
115  
SHC  
kW  
11.70  
11.70  
11.80  
11.80  
TC  
SHC  
kW  
TC  
SHC  
kW  
137.0  
95.9  
12.30  
132.0  
93.6  
13.80  
150.0  
76.7  
12.40  
144.0  
74.5  
13.90  
157.0  
85.4  
12.50  
150.0  
83.3  
14.00  
161.0  
93.5  
12.50  
154.0  
91.3  
14.00  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
46  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS (cont)  
UNIT 566E150 (cont)  
566E150/524A-C180 WITH HIGH-CAPACITY 4-ROW COIL  
Evaporator Air — Cfm  
6000  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
4500  
7500  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
152.0  
152.0  
9.24  
150.0  
150.0  
9.80  
156.0  
145.0  
9.26  
154.0  
144.0  
9.82  
169.0  
121.0  
9.35  
166.0  
120.0  
9.92  
183.0  
95.4  
9.53  
181.0  
94.4  
10.10  
166.0  
166.0  
9.33  
164.0  
164.0  
9.89  
166.0  
166.0  
9.33  
164.0  
164.0  
9.89  
176.0  
140.0  
9.43  
173.0  
139.0  
9.99  
190.0  
107.0  
9.63  
187.0  
106.0  
10.20  
175.0  
175.0  
9.42  
173.0  
173.0  
9.98  
175.0  
175.0  
9.43  
173.0  
173.0  
9.99  
181.0  
157.0  
9.49  
178.0  
156.0  
10.00  
195.0  
119.0  
9.69  
191.0  
118.0  
10.20  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
146.0  
146.0  
11.00  
148.0  
141.0  
11.10  
161.0  
117.0  
11.10  
175.0  
92.2  
11.30  
159.0  
159.0  
11.10  
159.0  
159.0  
11.10  
167.0  
136.0  
11.20  
181.0  
104.0  
11.40  
167.0  
167.0  
11.20  
167.0  
167.0  
11.20  
172.0  
154.0  
11.20  
185.0  
115.0  
11.40  
95  
TC  
144.0  
144.0  
11.70  
141.0  
141.0  
12.40  
137.0  
137.0  
13.90  
146.0  
140.0  
11.70  
143.0  
138.0  
12.40  
138.0  
135.0  
13.90  
158.0  
116.0  
11.80  
155.0  
115.0  
12.50  
148.0  
112.0  
13.90  
171.0  
91.1  
156.0  
156.0  
11.80  
154.0  
154.0  
12.50  
148.0  
148.0  
13.90  
156.0  
156.0  
11.80  
154.0  
154.0  
12.50  
148.0  
148.0  
14.00  
164.0  
135.0  
11.90  
161.0  
134.0  
12.50  
154.0  
131.0  
14.00  
178.0  
103.0  
12.00  
174.0  
102.0  
12.70  
167.0  
99.5  
14.20  
165.0  
165.0  
11.80  
162.0  
162.0  
12.50  
156.0  
156.0  
14.00  
165.0  
165.0  
11.90  
162.0  
162.0  
12.50  
156.0  
156.0  
14.00  
169.0  
152.0  
11.90  
165.0  
151.0  
12.60  
159.0  
148.0  
14.00  
181.0  
114.0  
12.10  
178.0  
113.0  
12.80  
170.0  
111.0  
14.20  
100  
105  
115  
SHC  
kW  
11.90  
TC  
SHC  
kW  
TC  
SHC  
kW  
168.0  
90.0  
12.60  
162.0  
87.6  
14.10  
566E150/524A-B180 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
4500  
6000  
7500  
Air Entering  
Condenser  
(Edb)  
Evaporator Air — Ewb (F)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
143.0  
143.0  
9.19  
141.0  
141.0  
9.75  
147.0  
136.0  
9.22  
145.0  
134.0  
9.77  
160.0  
113.0  
9.28  
157.0  
112.0  
9.85  
174.0  
89.9  
9.42  
171.0  
89.0  
9.98  
155.0  
155.0  
9.27  
153.0  
153.0  
9.82  
156.0  
155.0  
9.26  
153.0  
153.0  
9.82  
166.0  
130.0  
9.34  
164.0  
129.0  
9.90  
180.0  
100.0  
9.49  
178.0  
99.5  
10.00  
164.0  
164.0  
9.31  
162.0  
162.0  
9.87  
164.0  
164.0  
9.33  
162.0  
162.0  
9.89  
171.0  
146.0  
9.37  
168.0  
144.0  
9.93  
185.0  
110.0  
9.54  
182.0  
109.0  
10.10  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
137.0  
137.0  
11.00  
140.0  
132.0  
11.00  
152.0  
110.0  
11.10  
165.0  
86.9  
11.20  
149.0  
149.0  
11.00  
149.0  
149.0  
11.00  
158.0  
127.0  
11.10  
172.0  
97.4  
11.20  
157.0  
157.0  
11.10  
157.0  
157.0  
11.10  
162.0  
142.0  
11.10  
175.0  
107.0  
11.30  
95  
TC  
135.0  
135.0  
11.60  
133.0  
133.0  
12.30  
129.0  
129.0  
13.80  
138.0  
131.0  
11.60  
135.0  
129.0  
12.30  
130.0  
126.0  
13.80  
149.0  
109.0  
11.70  
146.0  
108.0  
12.40  
140.0  
106.0  
13.90  
162.0  
85.8  
146.0  
146.0  
11.70  
144.0  
144.0  
12.40  
139.0  
139.0  
13.90  
146.0  
146.0  
11.70  
144.0  
144.0  
12.40  
139.0  
139.0  
13.90  
155.0  
126.0  
11.80  
152.0  
125.0  
12.50  
146.0  
122.0  
13.90  
168.0  
96.3  
154.0  
154.0  
11.70  
152.0  
152.0  
12.40  
146.0  
146.0  
13.90  
154.0  
154.0  
11.80  
152.0  
152.0  
12.50  
146.0  
146.0  
13.90  
159.0  
141.0  
11.80  
156.0  
139.0  
12.50  
150.0  
137.0  
13.90  
172.0  
106.0  
11.90  
169.0  
105.0  
12.60  
162.0  
103.0  
14.10  
100  
105  
115  
SHC  
kW  
11.80  
11.90  
TC  
SHC  
kW  
TC  
SHC  
kW  
159.0  
84.7  
12.50  
153.0  
82.5  
14.00  
165.0  
95.2  
12.60  
158.0  
92.9  
14.10  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
47  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS (cont)  
UNIT 566E180  
566E180/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL  
Evaporator Air — Cfm  
5000  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
3750  
6250  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
163.0  
161.0  
12.60  
160.0  
159.0  
13.10  
175.0  
142.0  
12.80  
172.0  
141.0  
13.40  
190.0  
121.0  
13.20  
187.0  
120.0  
13.80  
206.0  
99.8  
179.0  
179.0  
12.90  
176.0  
176.0  
13.50  
186.0  
164.0  
13.10  
183.0  
163.0  
13.70  
201.0  
138.0  
13.40  
198.0  
136.0  
14.00  
217.0  
110.0  
13.80  
214.0  
109.0  
14.40  
191.0  
191.0  
13.20  
188.0  
188.0  
13.80  
194.0  
184.0  
13.30  
190.0  
182.0  
13.80  
208.0  
153.0  
13.60  
204.0  
151.0  
14.20  
224.0  
119.0  
14.00  
220.0  
118.0  
14.60  
80  
85  
SHC  
kW  
13.60  
TC  
SHC  
kW  
203.0  
98.5  
14.20  
TC  
SHC  
kW  
155.0  
155.0  
14.30  
166.0  
138.0  
14.60  
180.0  
117.0  
15.00  
196.0  
95.6  
15.40  
170.0  
170.0  
14.70  
176.0  
159.0  
14.80  
190.0  
133.0  
15.20  
206.0  
106.0  
15.70  
181.0  
181.0  
15.00  
183.0  
178.0  
15.00  
196.0  
148.0  
15.40  
212.0  
115.0  
15.80  
95  
TC  
152.0  
152.0  
14.90  
150.0  
150.0  
15.60  
144.0  
144.0  
16.90  
163.0  
136.0  
15.20  
159.0  
134.0  
15.80  
152.0  
131.0  
17.10  
177.0  
115.0  
15.60  
173.0  
114.0  
16.20  
165.0  
110.0  
17.50  
192.0  
94.0  
167.0  
167.0  
15.30  
164.0  
164.0  
16.00  
158.0  
158.0  
17.30  
172.0  
158.0  
15.50  
168.0  
156.0  
16.10  
161.0  
152.0  
17.40  
186.0  
131.0  
15.80  
182.0  
130.0  
16.50  
173.0  
126.0  
17.80  
201.0  
104.0  
16.30  
197.0  
102.0  
16.90  
188.0  
99.0  
18.20  
178.0  
178.0  
15.60  
175.0  
175.0  
16.30  
168.0  
168.0  
17.60  
180.0  
176.0  
15.60  
176.0  
173.0  
16.30  
168.0  
167.0  
17.60  
192.0  
146.0  
16.00  
188.0  
145.0  
16.60  
178.0  
141.0  
17.90  
208.0  
113.0  
16.50  
203.0  
112.0  
17.10  
193.0  
108.0  
18.40  
100  
105  
115  
SHC  
kW  
16.00  
TC  
SHC  
kW  
TC  
SHC  
kW  
188.0  
92.4  
16.60  
179.0  
89.1  
18.00  
566E180/524A-B150 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
3750  
5000  
6250  
Air Entering  
Condenser  
(Edb)  
Evaporator Air — Ewb (F)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
154.0  
152.0  
12.40  
152.0  
150.0  
12.90  
166.0  
134.0  
12.60  
163.0  
133.0  
13.20  
181.0  
115.0  
13.00  
178.0  
113.0  
13.50  
196.0  
94.7  
168.0  
168.0  
12.70  
166.0  
166.0  
13.20  
176.0  
154.0  
12.90  
173.0  
153.0  
13.40  
191.0  
129.0  
13.20  
188.0  
128.0  
13.80  
206.0  
104.0  
13.60  
203.0  
102.0  
14.20  
179.0  
179.0  
12.90  
176.0  
176.0  
13.50  
183.0  
171.0  
13.00  
180.0  
169.0  
13.60  
197.0  
143.0  
13.40  
194.0  
141.0  
13.90  
213.0  
112.0  
13.70  
210.0  
111.0  
14.30  
80  
85  
SHC  
kW  
13.30  
TC  
SHC  
kW  
193.0  
93.4  
13.90  
TC  
SHC  
kW  
147.0  
146.0  
14.10  
157.0  
130.0  
14.40  
171.0  
111.0  
14.70  
186.0  
90.6  
15.10  
160.0  
160.0  
14.40  
167.0  
149.0  
14.60  
180.0  
125.0  
15.00  
196.0  
99.7  
15.40  
171.0  
171.0  
14.70  
173.0  
166.0  
14.80  
187.0  
138.0  
15.10  
202.0  
108.0  
15.50  
95  
TC  
144.0  
144.0  
14.80  
141.0  
141.0  
15.40  
136.0  
136.0  
16.80  
154.0  
128.0  
15.00  
151.0  
127.0  
15.60  
144.0  
124.0  
16.90  
168.0  
109.0  
15.30  
164.0  
107.0  
16.00  
157.0  
104.0  
17.30  
182.0  
89.1  
158.0  
158.0  
15.10  
155.0  
155.0  
15.70  
149.0  
149.0  
17.10  
163.0  
148.0  
15.20  
160.0  
146.0  
15.80  
152.0  
142.0  
17.20  
177.0  
123.0  
15.60  
173.0  
122.0  
16.20  
165.0  
118.0  
17.50  
191.0  
98.1  
167.0  
167.0  
15.30  
164.0  
164.0  
16.00  
158.0  
158.0  
17.30  
170.0  
163.0  
15.40  
166.0  
161.0  
16.00  
159.0  
156.0  
17.30  
182.0  
137.0  
15.70  
178.0  
135.0  
16.40  
170.0  
132.0  
17.70  
197.0  
106.0  
16.20  
193.0  
105.0  
16.80  
183.0  
101.0  
18.10  
100  
105  
115  
SHC  
kW  
15.70  
16.00  
TC  
SHC  
kW  
TC  
SHC  
kW  
179.0  
87.6  
16.40  
170.0  
84.4  
17.70  
187.0  
96.5  
16.60  
178.0  
93.3  
17.90  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
48  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS (cont)  
UNIT 566E180 (cont)  
566E180/524A-C180 WITH HIGH-CAPACITY 4-ROW COIL  
Evaporator Air — Cfm  
6000  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
4500  
7500  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
180.0  
180.0  
12.90  
177.0  
177.0  
13.50  
190.0  
162.0  
13.20  
187.0  
160.0  
13.80  
206.0  
136.0  
13.60  
203.0  
135.0  
14.20  
223.0  
110.0  
14.00  
220.0  
109.0  
14.60  
197.0  
197.0  
13.30  
194.0  
194.0  
13.90  
201.0  
188.0  
13.40  
198.0  
186.0  
14.00  
216.0  
156.0  
13.80  
212.0  
154.0  
14.40  
233.0  
122.0  
14.20  
229.0  
121.0  
14.80  
209.0  
209.0  
13.60  
206.0  
206.0  
14.20  
210.0  
208.0  
13.70  
206.0  
206.0  
14.20  
222.0  
174.0  
14.00  
219.0  
173.0  
14.60  
239.0  
134.0  
14.40  
235.0  
132.0  
15.00  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
172.0  
172.0  
14.70  
180.0  
157.0  
14.90  
195.0  
132.0  
15.40  
212.0  
106.0  
15.80  
188.0  
188.0  
15.20  
190.0  
182.0  
15.20  
204.0  
151.0  
15.60  
221.0  
118.0  
16.10  
199.0  
199.0  
15.50  
199.0  
199.0  
15.50  
210.0  
169.0  
15.80  
226.0  
129.0  
16.20  
95  
TC  
169.0  
169.0  
15.40  
166.0  
166.0  
16.00  
159.0  
159.0  
17.30  
176.0  
155.0  
15.60  
172.0  
153.0  
16.20  
164.0  
149.0  
17.50  
191.0  
130.0  
16.00  
187.0  
128.0  
16.60  
178.0  
124.0  
17.90  
207.0  
104.0  
16.40  
203.0  
102.0  
17.10  
193.0  
98.8  
18.40  
184.0  
184.0  
15.80  
181.0  
181.0  
16.40  
173.0  
173.0  
17.80  
186.0  
180.0  
15.80  
182.0  
178.0  
16.50  
174.0  
172.0  
17.80  
200.0  
149.0  
16.20  
195.0  
147.0  
16.90  
185.0  
144.0  
18.10  
216.0  
116.0  
16.70  
211.0  
115.0  
17.40  
201.0  
111.0  
18.60  
195.0  
195.0  
16.10  
191.0  
191.0  
16.70  
183.0  
183.0  
18.10  
195.0  
195.0  
16.10  
191.0  
191.0  
16.80  
183.0  
183.0  
18.10  
205.0  
168.0  
16.40  
201.0  
166.0  
17.00  
191.0  
162.0  
18.30  
221.0  
128.0  
16.90  
216.0  
126.0  
17.50  
205.0  
122.0  
18.80  
100  
105  
115  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
566E180/524A-B180 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
4500  
6000  
7500  
Air Entering  
Condenser  
(Edb)  
Evaporator Air — Ewb (F)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
169.0  
169.0  
12.70  
167.0  
167.0  
13.30  
180.0  
152.0  
12.90  
177.0  
151.0  
13.50  
195.0  
128.0  
13.30  
192.0  
127.0  
13.90  
211.0  
104.0  
13.70  
208.0  
103.0  
14.30  
185.0  
185.0  
13.10  
182.0  
182.0  
13.60  
190.0  
175.0  
13.20  
186.0  
173.0  
13.70  
204.0  
146.0  
13.50  
201.0  
144.0  
14.10  
221.0  
115.0  
13.90  
217.0  
113.0  
14.50  
196.0  
196.0  
13.30  
193.0  
193.0  
13.90  
197.0  
193.0  
13.30  
194.0  
191.0  
13.90  
211.0  
162.0  
13.70  
207.0  
160.0  
14.30  
227.0  
125.0  
14.10  
223.0  
123.0  
14.70  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
161.0  
161.0  
14.50  
170.0  
147.0  
14.70  
184.0  
124.0  
15.10  
200.0  
99.8  
15.50  
176.0  
176.0  
14.80  
179.0  
169.0  
14.90  
193.0  
141.0  
15.30  
209.0  
111.0  
15.70  
186.0  
186.0  
15.10  
187.0  
186.0  
15.10  
199.0  
157.0  
15.50  
215.0  
120.0  
15.90  
95  
TC  
159.0  
159.0  
15.10  
156.0  
156.0  
15.70  
150.0  
150.0  
17.10  
166.0  
145.0  
15.30  
163.0  
144.0  
15.90  
155.0  
140.0  
17.20  
181.0  
122.0  
15.70  
177.0  
120.0  
16.30  
168.0  
117.0  
17.60  
196.0  
98.2  
173.0  
173.0  
15.50  
169.0  
169.0  
16.10  
163.0  
163.0  
17.50  
176.0  
167.0  
15.50  
172.0  
165.0  
16.20  
164.0  
160.0  
17.50  
189.0  
139.0  
15.90  
185.0  
138.0  
16.50  
175.0  
134.0  
17.80  
204.0  
109.0  
16.40  
200.0  
107.0  
17.00  
190.0  
104.0  
18.30  
183.0  
183.0  
15.70  
179.0  
179.0  
16.40  
172.0  
172.0  
17.70  
183.0  
183.0  
15.70  
179.0  
179.0  
16.40  
172.0  
172.0  
17.70  
194.0  
155.0  
16.10  
190.0  
153.0  
16.70  
180.0  
150.0  
18.00  
210.0  
119.0  
16.50  
205.0  
117.0  
17.20  
195.0  
114.0  
18.50  
100  
105  
115  
SHC  
kW  
16.10  
TC  
SHC  
kW  
TC  
SHC  
kW  
192.0  
96.6  
16.80  
183.0  
93.2  
18.10  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
49  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS (cont)  
UNIT 566E180 (cont)  
566E180/524A-C240 WITH HIGH-CAPACITY 4-ROW COIL  
Evaporator Air — Cfm  
8,000  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
6,000  
10,000  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
201.0  
201.0  
13.40  
198.0  
198.0  
14.00  
205.0  
191.0  
13.50  
202.0  
190.0  
14.10  
220.0  
159.0  
13.90  
216.0  
157.0  
14.50  
238.0  
125.0  
14.40  
234.0  
123.0  
15.00  
217.0  
217.0  
13.80  
214.0  
214.0  
14.40  
217.0  
217.0  
13.80  
214.0  
214.0  
14.40  
229.0  
184.0  
14.10  
225.0  
182.0  
14.70  
246.0  
140.0  
14.60  
242.0  
139.0  
15.20  
228.0  
228.0  
14.10  
225.0  
225.0  
14.70  
228.0  
228.0  
14.10  
225.0  
225.0  
14.70  
234.0  
207.0  
14.30  
230.0  
205.0  
14.90  
251.0  
155.0  
14.70  
247.0  
154.0  
15.30  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
191.0  
191.0  
15.30  
194.0  
186.0  
15.30  
208.0  
154.0  
15.70  
225.0  
120.0  
16.20  
207.0  
207.0  
15.70  
207.0  
207.0  
15.70  
216.0  
179.0  
15.90  
232.0  
136.0  
16.40  
217.0  
217.0  
16.00  
217.0  
217.0  
16.00  
221.0  
201.0  
16.10  
237.0  
150.0  
16.60  
95  
TC  
188.0  
188.0  
15.90  
184.0  
184.0  
16.50  
176.0  
176.0  
17.90  
190.0  
183.0  
15.90  
185.0  
181.0  
16.60  
177.0  
176.0  
17.90  
204.0  
152.0  
16.30  
199.0  
150.0  
17.00  
189.0  
146.0  
18.30  
220.0  
118.0  
16.80  
215.0  
117.0  
17.50  
205.0  
113.0  
18.80  
202.0  
202.0  
16.30  
198.0  
198.0  
17.00  
190.0  
190.0  
18.30  
203.0  
203.0  
16.30  
198.0  
198.0  
17.00  
190.0  
190.0  
18.30  
211.0  
177.0  
16.60  
206.0  
175.0  
17.20  
196.0  
171.0  
18.50  
227.0  
134.0  
17.10  
222.0  
132.0  
17.70  
211.0  
128.0  
19.00  
213.0  
213.0  
16.60  
208.0  
208.0  
17.30  
199.0  
199.0  
18.60  
213.0  
213.0  
16.60  
208.0  
208.0  
17.30  
199.0  
199.0  
18.60  
216.0  
199.0  
16.70  
211.0  
197.0  
17.40  
201.0  
192.0  
18.70  
232.0  
149.0  
17.20  
226.0  
147.0  
17.80  
214.0  
143.0  
19.10  
100  
105  
115  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
566E180/524A-B240 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
6,000  
8,000  
10,000  
Air Entering  
Condenser  
(Edb)  
Evaporator Air — Ewb (F)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
190.0  
190.0  
13.20  
187.0  
187.0  
13.80  
194.0  
181.0  
13.30  
191.0  
179.0  
13.90  
209.0  
150.0  
13.60  
205.0  
149.0  
14.20  
226.0  
118.0  
14.00  
222.0  
117.0  
14.60  
205.0  
205.0  
13.50  
202.0  
202.0  
14.10  
205.0  
204.0  
13.50  
202.0  
201.0  
14.10  
217.0  
173.0  
13.80  
213.0  
171.0  
14.40  
233.0  
132.0  
14.20  
229.0  
131.0  
14.80  
215.0  
215.0  
13.80  
211.0  
211.0  
14.40  
215.0  
215.0  
13.80  
211.0  
211.0  
14.40  
222.0  
193.0  
14.00  
218.0  
191.0  
14.50  
238.0  
145.0  
14.40  
234.0  
144.0  
15.00  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
181.0  
181.0  
15.00  
184.0  
175.0  
15.00  
197.0  
146.0  
15.40  
213.0  
114.0  
15.90  
195.0  
195.0  
15.30  
195.0  
195.0  
15.30  
204.0  
168.0  
15.60  
220.0  
128.0  
16.10  
204.0  
204.0  
15.60  
204.0  
204.0  
15.60  
209.0  
187.0  
15.80  
225.0  
141.0  
16.20  
95  
TC  
178.0  
178.0  
15.60  
174.0  
174.0  
16.20  
167.0  
167.0  
17.60  
180.0  
173.0  
15.70  
176.0  
171.0  
16.30  
168.0  
166.0  
17.60  
193.0  
144.0  
16.00  
188.0  
142.0  
16.60  
179.0  
138.0  
18.00  
209.0  
112.0  
16.50  
204.0  
110.0  
17.10  
194.0  
107.0  
18.40  
191.0  
191.0  
16.00  
187.0  
187.0  
16.60  
179.0  
179.0  
17.90  
191.0  
191.0  
16.00  
187.0  
187.0  
16.60  
179.0  
179.0  
17.90  
200.0  
166.0  
16.20  
195.0  
164.0  
16.90  
185.0  
160.0  
18.10  
216.0  
126.0  
16.70  
210.0  
124.0  
17.30  
200.0  
121.0  
18.60  
200.0  
200.0  
16.20  
196.0  
196.0  
16.90  
187.0  
187.0  
18.20  
200.0  
200.0  
16.20  
196.0  
196.0  
16.90  
187.0  
187.0  
18.20  
205.0  
185.0  
16.40  
200.0  
183.0  
17.00  
190.0  
178.0  
18.30  
220.0  
139.0  
16.80  
215.0  
137.0  
17.50  
203.0  
133.0  
18.70  
100  
105  
115  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
50  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS (cont)  
UNIT 566E240  
566E240/524A-C240 WITH HIGH-CAPACITY 4-ROW COIL  
Evaporator Air — Cfm  
8,000  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
6,000  
10,000  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
228.0  
228.0  
17.60  
225.0  
225.0  
18.40  
239.0  
207.0  
18.00  
235.0  
205.0  
18.70  
258.0  
174.0  
18.70  
254.0  
172.0  
19.40  
279.0  
139.0  
19.40  
274.0  
137.0  
20.10  
248.0  
248.0  
18.30  
245.0  
245.0  
19.10  
252.0  
240.0  
18.40  
248.0  
237.0  
19.20  
269.0  
199.0  
19.10  
265.0  
197.0  
19.80  
290.0  
155.0  
19.80  
285.0  
153.0  
20.60  
262.0  
262.0  
18.80  
258.0  
258.0  
19.60  
262.0  
262.0  
18.80  
258.0  
258.0  
19.60  
277.0  
222.0  
19.30  
272.0  
220.0  
20.10  
297.0  
169.0  
20.10  
291.0  
167.0  
20.80  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
218.0  
218.0  
20.00  
227.0  
201.0  
20.30  
244.0  
168.0  
21.00  
263.0  
134.0  
21.70  
236.0  
236.0  
20.70  
238.0  
232.0  
20.70  
254.0  
193.0  
21.30  
274.0  
149.0  
22.10  
249.0  
249.0  
21.10  
249.0  
249.0  
21.10  
261.0  
216.0  
21.60  
280.0  
163.0  
22.40  
95  
TC  
214.0  
214.0  
20.90  
211.0  
211.0  
21.70  
203.0  
203.0  
23.50  
222.0  
199.0  
21.10  
217.0  
196.0  
22.00  
207.0  
192.0  
23.70  
239.0  
166.0  
21.70  
234.0  
163.0  
22.60  
223.0  
159.0  
24.30  
258.0  
132.0  
22.50  
252.0  
130.0  
23.30  
241.0  
125.0  
25.00  
232.0  
232.0  
21.50  
228.0  
228.0  
22.40  
219.0  
219.0  
24.10  
234.0  
229.0  
21.50  
229.0  
226.0  
22.40  
219.0  
219.0  
24.10  
249.0  
190.0  
22.10  
243.0  
188.0  
22.90  
231.0  
184.0  
24.60  
268.0  
147.0  
22.90  
262.0  
145.0  
23.70  
249.0  
140.0  
25.40  
245.0  
245.0  
22.00  
240.0  
240.0  
22.80  
230.0  
230.0  
24.60  
245.0  
245.0  
22.00  
240.0  
240.0  
22.80  
230.0  
230.0  
24.60  
255.0  
213.0  
22.40  
249.0  
211.0  
23.20  
237.0  
206.0  
24.90  
274.0  
161.0  
23.10  
267.0  
159.0  
23.90  
254.0  
155.0  
25.60  
100  
105  
115  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
566E240/524A-B240 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
6,000  
8,000  
10,000  
Air Entering  
Condenser  
(Edb)  
Evaporator Air — Ewb (F)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
219.0  
219.0  
17.30  
216.0  
216.0  
18.10  
229.0  
199.0  
17.70  
226.0  
197.0  
18.40  
248.0  
167.0  
18.30  
243.0  
165.0  
19.00  
267.0  
134.0  
19.00  
263.0  
132.0  
19.70  
237.0  
237.0  
17.90  
234.0  
234.0  
18.70  
241.0  
228.0  
18.10  
237.0  
226.0  
18.80  
259.0  
190.0  
18.70  
254.0  
188.0  
19.40  
278.0  
148.0  
19.40  
273.0  
146.0  
20.10  
250.0  
250.0  
18.40  
246.0  
246.0  
19.10  
251.0  
250.0  
18.40  
247.0  
246.0  
19.10  
265.0  
211.0  
18.90  
261.0  
209.0  
19.70  
285.0  
161.0  
19.60  
280.0  
159.0  
20.40  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
209.0  
209.0  
19.70  
217.0  
192.0  
20.00  
234.0  
161.0  
20.60  
253.0  
128.0  
21.30  
226.0  
226.0  
20.30  
228.0  
221.0  
20.40  
244.0  
184.0  
20.90  
263.0  
142.0  
21.70  
238.0  
238.0  
20.70  
238.0  
238.0  
20.70  
250.0  
205.0  
21.20  
269.0  
155.0  
21.90  
95  
TC  
206.0  
206.0  
20.60  
202.0  
202.0  
21.40  
195.0  
195.0  
23.30  
213.0  
190.0  
20.80  
209.0  
188.0  
21.70  
200.0  
184.0  
23.40  
230.0  
159.0  
21.40  
225.0  
157.0  
22.20  
215.0  
153.0  
24.00  
248.0  
126.0  
22.10  
242.0  
124.0  
22.90  
232.0  
120.0  
24.60  
222.0  
222.0  
21.10  
218.0  
218.0  
22.00  
210.0  
210.0  
23.80  
224.0  
218.0  
21.20  
219.0  
215.0  
22.00  
210.0  
209.0  
23.80  
239.0  
182.0  
21.70  
233.0  
180.0  
22.60  
223.0  
175.0  
24.30  
257.0  
140.0  
22.50  
251.0  
138.0  
23.30  
239.0  
134.0  
25.00  
234.0  
234.0  
21.50  
229.0  
229.0  
22.40  
220.0  
220.0  
24.20  
234.0  
234.0  
21.50  
229.0  
229.0  
22.40  
220.0  
220.0  
24.20  
245.0  
202.0  
22.00  
239.0  
200.0  
22.80  
228.0  
196.0  
24.50  
263.0  
153.0  
22.70  
257.0  
151.0  
23.50  
244.0  
147.0  
25.20  
100  
105  
115  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
51  
PERFORMANCE DATA (cont)  
COMBINATION RATINGS (cont)  
UNIT 566E240 (cont)  
566E240/524A-C300 WITH HIGH-CAPACITY 4-ROW COIL  
Evaporator Air — Cfm  
10,000  
Evaporator Air — Ewb (F)  
Temp (F)  
Air Entering  
Condenser  
(Edb)  
7,500  
12,500  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
249.0  
249.0  
18.30  
245.0  
245.0  
19.10  
254.0  
236.0  
18.50  
249.0  
234.0  
19.20  
272.0  
196.0  
19.20  
267.0  
194.0  
19.90  
293.0  
154.0  
19.90  
288.0  
152.0  
20.70  
268.0  
268.0  
19.00  
263.0  
263.0  
19.80  
268.0  
268.0  
19.00  
263.0  
263.0  
19.80  
282.0  
226.0  
19.50  
277.0  
224.0  
20.30  
303.0  
172.0  
20.30  
297.0  
170.0  
21.00  
281.0  
281.0  
19.50  
276.0  
276.0  
20.20  
281.0  
281.0  
19.50  
276.0  
276.0  
20.20  
289.0  
253.0  
19.80  
283.0  
251.0  
20.50  
309.0  
190.0  
20.50  
303.0  
188.0  
21.30  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
237.0  
237.0  
20.70  
240.0  
229.0  
20.80  
257.0  
190.0  
21.40  
277.0  
148.0  
22.20  
254.0  
254.0  
21.30  
254.0  
254.0  
21.30  
266.0  
220.0  
21.80  
285.0  
166.0  
22.60  
266.0  
266.0  
21.80  
266.0  
266.0  
21.80  
272.0  
246.0  
22.00  
290.0  
184.0  
22.80  
95  
TC  
232.0  
232.0  
21.50  
228.0  
228.0  
22.30  
219.0  
219.0  
24.10  
235.0  
226.0  
21.60  
230.0  
223.0  
22.40  
219.0  
217.0  
24.10  
251.0  
187.0  
22.20  
246.0  
185.0  
23.00  
234.0  
180.0  
24.70  
271.0  
145.0  
23.00  
265.0  
143.0  
23.80  
252.0  
139.0  
25.50  
249.0  
249.0  
22.20  
244.0  
244.0  
23.00  
234.0  
234.0  
24.70  
250.0  
250.0  
22.10  
245.0  
245.0  
23.00  
234.0  
234.0  
24.70  
260.0  
217.0  
22.60  
254.0  
215.0  
23.40  
241.0  
210.0  
25.00  
279.0  
164.0  
23.40  
272.0  
162.0  
24.20  
259.0  
157.0  
25.80  
261.0  
261.0  
22.60  
256.0  
256.0  
23.50  
244.0  
244.0  
25.20  
261.0  
261.0  
22.60  
256.0  
256.0  
23.40  
244.0  
244.0  
25.20  
266.0  
244.0  
22.80  
260.0  
241.0  
23.60  
247.0  
235.0  
25.30  
284.0  
182.0  
23.60  
277.0  
180.0  
24.40  
263.0  
175.0  
26.00  
100  
105  
115  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
566E240/524A-B300 WITH STANDARD 3-ROW COIL  
Temp (F)  
Evaporator Air — Cfm  
10,000  
Evaporator Air — Ewb (F)  
7,500  
12,500  
Air Entering  
Condenser  
(Edb)  
57  
62  
67  
72  
57  
62  
67  
72  
57  
62  
67  
72  
TC  
236.0  
236.0  
17.90  
233.0  
233.0  
18.70  
242.0  
223.0  
18.10  
238.0  
221.0  
18.80  
260.0  
185.0  
18.70  
256.0  
184.0  
19.50  
280.0  
146.0  
19.50  
275.0  
144.0  
20.20  
254.0  
254.0  
18.50  
250.0  
250.0  
19.30  
254.0  
252.0  
18.50  
250.0  
249.0  
19.30  
269.0  
212.0  
19.10  
265.0  
210.0  
19.80  
290.0  
162.0  
19.80  
285.0  
161.0  
20.60  
266.0  
266.0  
18.90  
262.0  
262.0  
19.70  
266.0  
266.0  
18.90  
262.0  
262.0  
19.70  
276.0  
236.0  
19.30  
271.0  
234.0  
20.00  
296.0  
178.0  
20.00  
290.0  
176.0  
20.80  
80  
85  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
225.0  
225.0  
20.30  
229.0  
216.0  
20.40  
246.0  
179.0  
21.00  
265.0  
140.0  
21.80  
242.0  
242.0  
20.90  
242.0  
242.0  
20.90  
255.0  
206.0  
21.40  
273.0  
157.0  
22.10  
253.0  
253.0  
21.30  
253.0  
253.0  
21.30  
260.0  
230.0  
21.60  
279.0  
172.0  
22.30  
95  
TC  
221.0  
221.0  
21.10  
217.0  
217.0  
22.00  
209.0  
209.0  
23.80  
225.0  
214.0  
21.20  
220.0  
211.0  
22.10  
211.0  
206.0  
23.80  
241.0  
178.0  
21.80  
236.0  
175.0  
22.60  
225.0  
171.0  
24.40  
260.0  
138.0  
22.50  
254.0  
136.0  
23.40  
242.0  
132.0  
25.10  
237.0  
237.0  
21.70  
233.0  
233.0  
22.50  
223.0  
223.0  
24.30  
237.0  
237.0  
21.70  
233.0  
233.0  
22.50  
223.0  
223.0  
24.30  
249.0  
204.0  
22.10  
243.0  
202.0  
23.00  
232.0  
197.0  
24.60  
268.0  
155.0  
22.90  
262.0  
153.0  
23.70  
249.0  
148.0  
25.40  
248.0  
248.0  
22.10  
243.0  
243.0  
22.90  
233.0  
233.0  
24.70  
248.0  
248.0  
22.10  
243.0  
243.0  
22.90  
233.0  
233.0  
24.70  
255.0  
227.0  
22.40  
249.0  
225.0  
23.20  
237.0  
219.0  
24.90  
273.0  
170.0  
23.10  
266.0  
168.0  
23.90  
253.0  
164.0  
25.60  
100  
105  
115  
SHC  
kW  
TC  
SHC  
kW  
TC  
SHC  
kW  
LEGEND  
Edb — Entering Dry Bulb  
Ewb — Entering Wet Bulb  
kW — Compressor Motor Power Input  
SHC — Sensible Heat Capacity (1000 Btuh) Gross  
TC — Total Capacity (1000 Btuh) Gross  
52  
ELECTRICAL DATA  
566D150-240  
COMPRESSOR  
FAN MOTORS (Qty 2)  
FLA (ea)  
POWER SUPPLY  
MOCP†  
VOLTAGE  
RANGE*  
NOMINAL  
VOLTAGE  
(3-Ph, 60 Hz)  
UNIT  
SIZE  
Fan No.  
RLA  
LRA  
kW  
MCA  
ICF  
Min  
Max  
1
2
208/230  
460  
187  
414  
518  
253  
528  
660  
49.3  
22.1  
17.9  
191  
80  
4.3  
2.3  
1.8  
3.7  
1.9  
1.8  
69.6  
31.7  
25.6  
100  
50  
199  
84  
150  
180  
240  
1.41  
1.41  
1.41  
575  
69  
40  
73  
208/230  
460  
575  
187  
414  
518  
253  
528  
660  
63.6  
29.3  
23.8  
266  
120  
96  
4.3  
2.3  
1.8  
3.7  
1.9  
1.8  
87.5  
40.7  
33.0  
125  
60  
50  
274  
124  
100  
566D  
208/230  
460  
575  
187  
414  
518  
254  
508  
632  
67.9  
34.7  
28.8  
345  
173  
120  
4.3  
2.3  
1.8  
3.7  
1.9  
1.8  
93.4  
48.1  
40.1  
150  
80  
60  
353  
177  
124  
LEGEND  
Full Load Amps  
*Units are suitable for use on electrical systems where voltage supplied to the  
unit terminals is not below or above the listed limits.  
†Fuse or HACR circuit breaker.  
FLA  
HACR  
Heating, Air Conditioning and  
Refrigeration  
NOTES:  
1. The MCA and MOCP values are calculated in accordance with the National  
Electrical Code (NEC), Article 440.  
ICF  
Maximum Instantaneous Current Flow  
During Start-Up (LRA of compressor  
plus total FLA of fan motors)  
Total Fan Motor Input (kilowatts)  
Locked Rotor Amps  
Minimum Circuit Amps per NEC,  
Section 430-24  
Maximum Overcurrent Protection (amps)  
Rated Load Amps (compressor)  
2. Motor RLA and LRA values are established in accordance with Underwrit-  
ers’ Laboratories (UL), Standard 1995.  
kW  
LRA  
MCA  
3. The 575-v units are UL, Canada-listed only.  
MOCP  
RLA  
566E150-240  
FAN MOTORS  
Qty 2)  
VOLTAGE  
RANGE*  
POWER  
SUPPLY  
FACTORY-  
INSTALLED  
OPTION  
NOMINAL  
COMPRESSOR 1  
COMPRESSOR 2  
UNIT  
SIZE  
VOLTAGE  
FLA (ea)  
(3 Ph, 60 Hz)  
Fan No.  
kW  
Min Max  
RLA  
LRA  
RLA  
LRA  
1
2
MCA MOCP† ICF  
55.6  
63.5  
27.7  
31.3  
23.1  
25.9  
81.2  
89.2  
42.1  
45.7  
31.6  
34.5  
94.1  
102.0  
48.4  
52.0  
35.7  
38.5  
70  
80  
186  
194  
90  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
208/230  
460  
187 253  
20.7  
156  
20.7  
156  
4.3 3.7 1.41  
2.3 1.9 1.41  
1.8 1.8 1.41  
4.3 3.7 1.41  
2.3 1.9 1.41  
1.8 1.8 1.41  
4.3 3.7 1.41  
2.3 1.9 1.41  
1.8 1.8 1.41  
35  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
150  
414 528  
518 660  
187 253  
414 528  
518 660  
187 253  
414 528  
518 660  
10.0  
8.2  
75  
54  
10.0  
8.2  
75  
54  
40  
94  
30  
67  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
575  
30  
70  
100  
100  
50  
236  
244  
117  
120  
97  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
208/230  
460  
32.1  
16.4  
12.0  
37.8  
19.2  
13.8  
195  
95  
32.1  
16.4  
12.0  
37.8  
19.2  
13.8  
195  
95  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
566E 180  
60  
40  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
575  
80  
80  
40  
99  
125  
150  
60  
286  
294  
149  
153  
98  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
208/230  
460  
239  
125  
80  
239  
125  
80  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
240  
70  
45  
NONE OR DISCONNECT  
CONVENIENCE OUTLET  
575  
50  
101  
LEGEND  
Full Load Amps  
Heating, Air Conditioning and  
Refrigeration  
Maximum Instantaneous Current Flow  
During Start-Up (LRA of compressor  
plus total FLA of fan motors)  
Total Fan Motor Input (kilowatts)  
Locked Rotor Amps  
Minimum Circuit Amps per NEC,  
Section 430-24  
Maximum Overcurrent Protection (amps)  
Rated Load Amps (compressor)  
*Units are suitable for use on electrical systems where voltage supplied to the  
unit terminals is not below or above the listed limits.  
†Fuse or HACR circuit breaker.  
FLA  
HACR  
NOTES:  
1. The MCA and MOCP values are calculated in accordance with the National  
Electrical Code (NEC), Article 440.  
ICF  
2. Motor RLA and LRA values are established in accordance with Underwrit-  
ers’ Laboratories (UL), Standard 1995.  
kW  
LRA  
MCA  
3. The 575-v units are UL, Canada-listed only.  
4. Convenience outlet is available as either a factory-installed option or a field-  
installed accessory and is 115-v, 1ph, 60 Hz.  
MOCP  
RLA  
53  
APPLICATION DATA — 566D150-240, 566E150-240  
1. INSTALLATION — Select equipment to match or to be  
slightly less than peak load. This provides better humidity  
control, less unit cycling, and less part-load operation.  
MINIMUM OUTDOOR-AIR OPERATING  
TEMPERATURE — 566E150-240 UNITS  
MINIMUM  
When selecting vapor line sizes, oil return must be evalu-  
ated, particularly at part-load conditions.  
OUTDOOR-AIR  
FULL LOAD  
CAPACITY  
(%)  
TEMPERATURE (F)  
UNIT  
566E  
SATURATED COND  
TEMPERATURE (F)  
With  
The indoor fan must always be operating when outdoor unit  
is operating.  
Base  
Low-Ambient  
Unit  
Control  
Ductwork should be sized according to unit size, not build-  
ing load.  
150  
180  
240  
100/50  
90  
50  
–20  
To minimize the possibility of air recirculation, avoid the use  
of concentric supply/return grilles.  
LIQUID LINE DATA — 566D150-240 UNITS  
Indoor equipment should be selected at no less than  
300 cfm/ton.  
LIQUID LINE  
MAX  
ALLOW.  
LIFT  
Max Allow.  
Pressure  
Drop  
Max Allow.  
Temp  
UNIT  
566D  
OPERATING LIMITS  
Loss  
(°F)  
(ft)  
Maximum Outdoor  
115 F  
(psi)  
See Minimum Outdoor-Air  
Operating Temperature  
table below.  
150  
180  
240  
67  
82  
87  
7
2
Minimum Outdoor Ambient  
Minimum Return-Air  
Temperature  
Maximum Return-Air  
Temperature  
55 F  
NOTE: Data above is for units operating at 45 F saturated suction and  
95 F entering air.  
95 F  
LIQUID LINE DATA — 566E150-240 UNITS  
Normal Acceptable Saturation  
Suction Temperature Range  
Maximum Discharge  
Temperature  
25 to 55 F  
LIQUID LINE  
MAX  
Max Allow.  
Pressure  
Drop  
Max Allow.  
Temp  
UNIT  
566E  
ALLOW.  
LIFT  
295 F  
60 F  
Loss  
(°F)  
(ft)  
Minimum Discharge Superheat  
(psi)  
150  
180  
240  
60  
7
2
MINIMUM OUTDOOR-AIR OPERATING  
TEMPERATURE — 566D150-240 UNITS  
MINIMUM  
2. REFRIGERANT PIPING — It is recommended that the  
refrigerant piping for all commercial split systems include a  
liquid line solenoid valve, a liquid line filter drier, and a sight  
glass.  
OUTDOOR-AIR  
OPERATING  
FULL LOAD  
CAPACITY  
(%)  
UNIT  
566D  
NO. OF  
CYLINDERS  
TEMPERATURE (F)  
With  
Low-Ambient  
Control  
Base  
Unit  
For refrigerant lines longer than 75 lineal ft, a liquid line  
solenoid valve and a suction accumulator are required.  
Refer to the Refrigerant Specialties table.  
6
4
100  
67  
20  
31  
40  
20  
33  
47  
15  
20  
150  
2*  
6
4
33*  
100  
67  
–20  
180  
240  
2*  
4
2
33*  
100  
50  
*Requires field-installed unloader.  
REFRIGERANT SPECIALTIES PART NUMBERS  
LIQUID LINE  
UNIT  
LIQUID LINE  
SOLENOID VALVE (LLSV)  
LLSV  
COIL  
SIGHT  
GLASS  
FILTER  
DRIER  
SUCTION LINE  
ACCUMULATOR  
SIZE (in.)  
1
/
200RB7T4M  
200RA8T5M  
AMG/24V  
AMG/24V  
AMI-1TT4  
AMI-1TT5  
P502-8757S*  
P502-8757S*  
S-7063  
S-7063  
2
566D150  
5
/
8
1
/
2
200RB7T4M  
AMG/24V  
AMI-1TT4  
P502-8757S*  
S-7721  
5
566D180  
/
8
/
8
/
8
/
8
/
2
/
2
/
8
/
2
/
8
200RA8T5M  
200RA8T7M  
200RA9T5M  
200RA9T7M  
AMG/24V  
AMG/24V  
AMG/24V  
AMG/24V  
AMI-1TT5  
AMI-1TT7  
AMI-1TT5  
AMI-1TT7  
P502-8757S*  
P502-8757S  
P502-8757S*  
P502-8757S  
P502-8304S Qty 2  
P502-8304S Qty 2  
P502-8304S Qty 2  
P502-8307S*  
S-7721  
S-7721  
S-7721  
S-7721  
7
5
7
1
1
5
1
5
566D240  
566E150  
566E180  
200RB5T4M Qty 2  
200RB5T4M Qty 2  
200RB5T5M Qty 2  
200RB6T4M Qty 2  
200RB6T5M Qty 2  
AMG/24V Qty 2  
AMG/24V Qty 2  
AMG/24V Qty 2  
AMG/24V Qty 2  
AMG/24V Qty 2  
AMI-1TT4 Qty 2  
AMI-1TT4 Qty 2  
AMI-1TT5 Qty 2  
AMI-1TT5 Qty 2  
AMI-1TT5 Qty 2  
S-7063S* Qty 2  
S-7063S Qty 2  
S-7063S Qty 2  
S-7063S Qty 2  
S-7063S Qty 2  
566E240  
P502-8307S*  
*Bushings required.  
54  
APPLICATION DATA — 566D150-240, 566E150-240 (cont)  
REFRIGERANT PIPING SIZES  
LINEAR LENGTH OF INTERCONNECTING PIPING (FT)  
0-15  
16-25  
26-50  
Line Size (in. OD)  
51-75  
76-100  
UNIT  
566D  
L
S
L
S
L
S
L
S
L
S
1
1
5
5
7
150  
180  
240  
/
2
/
2
/
8
11/8  
13/8  
15/8  
/
2
/
8
/
8
13/8  
13/8  
15/8  
/
8
/
8
/
8
13/8  
15/8  
15/8  
/
8
/
8
/
8
15/8*  
15/8  
21/8  
/
8
/
8
/
8
15/8*  
21/8*  
21/8  
1
5
5
5
5
7
7
7
7
7
LINEAR LENGTH OF INTERCONNECTING PIPING (FT)  
0-25 25-50 50-75 75-100  
Line Size (in. OD)  
UNIT  
566E  
TXV — Thermostatic  
L
S
L
S
L
S
L
S
Expansion Valve  
1
1
1
1
150  
180  
240  
/
2
/
2
/
2
11/8  
13/8  
13/8  
/
2
/
2
/
2
11/8  
13/8  
13/8  
/
/
/
11/8  
13/8  
13/8  
/
/
/
11/8  
13/8  
13/8  
2
2
8
2
8
8
1
1
1
1
1
5
5
5
Location of One Liquid Line Solenoid  
Valve Serving 2 Coil Circuits  
(Solenoid Drop Control)  
LEGEND  
L
S
Liquid  
Suction  
Close-coupled.  
*Requires a double suction riser if 2 unloaders are used and the evaporator is  
below the condensing unit. See Refrigerant Piping Sizes — Double Suction Ris-  
ers table and Suction Line Piping figure below for more information.  
NOTES:  
1. Pipe sizes are based on a 2° F loss for liquid lines and a 1.5° F loss for suc-  
tion lines.  
2. Pipe sizes are based on an equivalent length equal to the maximum length  
of interconnecting piping plus 50% for fittings. A more accurate estimate  
may result in smaller sizes.  
REFRIGERANT PIPING SIZES —  
DOUBLE SUCTION RISERS  
LINEAR LENGTH OF INTERCONNECTING PIPING (FT)  
51-75  
76-100  
UNIT  
566D  
Line Size (in. OD)  
A
B
C
A
B
C
150  
180  
11/8  
13/8  
15/8  
11/8  
13/8  
15/8  
15/8  
13/8  
21/8  
NOTES:  
1. See Suction Line Piping figure below for “A,” “B,” and “C” dimensions.  
2. No double suction risers are needed for unit size 240.  
TXV — Thermostatic  
Expansion Valve  
Face-Split Coil Suction and  
Liquid Line Piping  
LEGEND  
Suction Riser Without Trap  
Suction Riser With Trap  
A
B
C
D
Suction Line to Condensing Unit  
Short Vertical Riser Into Condensing Unit:  
566D150,180 — 13/8 in. OD  
Suction Line Piping  
55  
APPLICATION DATA — 566D150-240, 566E150-240 (cont)  
MULTIPLE CONDENSING UNIT ARRANGEMENTS*  
566D, 566E150-240  
566D, 566E150-240  
566D, 566E150-240  
Space for Service and Airflow  
*For clearances between controls and grounded surfaces,  
check local codes.  
566D,566E  
150-240  
DIMENSIONS (ft)  
A
B
4
4
56  
TYPICAL PIPING AND WIRING  
NOTES:  
LEGEND  
1. All piping must follow standard refrigerant piping techniques.  
NEC  
TXV  
National Electrical Code  
Thermostatic Expansion Valve  
Piping  
2. All wiring must comply with the applicable local and national  
codes.  
3. Wiring and piping shown are general points-of-connection  
guides only and are not intended for, or to include all details for, a  
specific installation.  
*Field supplied.  
4. Liquid line solenoid valve (solenoid drop control) is recom-  
mended to prevent refrigerant migration to the compressor.  
5. Internal factory-supplied TXVs not shown.  
Rooftop Installation — 566D150-240  
57  
TYPICAL PIPING AND WIRING (cont)  
NOTES:  
LEGEND  
1. All piping must follow standard refrigerant piping techniques.  
NEC  
National Electrical Code  
Thermostatic Expansion Valve  
Piping  
2. All wiring must comply with the applicable local and national  
codes.  
3. Wiring and piping shown are general points-of-connection  
guides only and are not intended for, or to include all details for, a  
specific installation.  
TXV  
*Field supplied.  
4. Liquid line solenoid valve (solenoid drop control) is recom-  
mended to prevent refrigerant migration to the compressor.  
5. Internal factory-supplied TXVs not shown.  
Ground Level Installation — 566D150-240  
58  
GUIDE SPECIFICATIONS — 566D150-240, 566E150-240  
COMMERCIAL AIR-COOLED CONDENSING UNITS  
HVAC GUIDE SPECIFICATIONS  
SIZE RANGE: 121/2 TO 20 TONS, NOMINAL  
b. Compressor shall be equipped with an automati-  
cally reversible oil pump, operating oil charge,  
suction and discharge shutoff valves, and an  
insert-type, factory-sized crankcase heater to  
control oil dilution.  
BRYANT MODEL NUMBER: 566D, SIZES 150-240  
566E, SIZES 150-240  
c. Compressor shall be mounted on spring vibration  
isolators with an isolation efficiency of no less  
than 95%.  
PART 1 — GENERAL  
1.01 SYSTEM DESCRIPTION  
d. Compressor speed shall not exceed 1750 rpm.  
Outdoor-mounted, air-cooled condensing unit suitable for  
on-the-ground or rooftop installation. Unit shall consist of a  
semi-hermetic reciprocating compressor (566D) or scroll  
compressor (566E), an air-cooled coil, propeller-type con-  
denser fans, and a control box. Unit shall discharge supply  
air upward as shown on contract drawings. Unit shall be  
used in a refrigeration circuit to match a packaged fan coil  
unit.  
e. Compressor shall unload using suction cutoff  
unloading (electrical solenoid unloading shall be  
available as an accessory).  
f. Compressor shall include overload protection.  
g. Compressor shall be equipped with internal high  
discharge temperature protection (566E180 and  
240 only).  
1.02 QUALITY ASSURANCE  
2. 566E150-240 Units:  
A. Unit shall be rated in accordance with ARI latest revisions  
and shall be certified and listed in the latest ARI directory.  
a. Compressors shall be of the hermetic scroll type.  
b. Compressors shall be mounted on vibration  
isolators.  
c. Compressors shall include overload protection.  
d. Compressors shall be equipped with a crankcase  
heater.  
B. Unit shall be manufactured in a facility registered to ISO  
9001:2000 manufacturing quality standard.  
C. Unit construction shall comply with latest edition of ANSI/  
ASHRAE and with NEC.  
D. Unit shall be constructed in accordance with UL  
standards and shall carry the UL and UL, Canada label.  
E. Condenser Coil:  
1. Condenser coil shall be air cooled, circuited for inte-  
gral subcooler.  
E. Unit cabinet shall be capable of withstanding 500-hour  
salt spray exposure per ASTM B117 (scribed specimen).  
2. Coil shall be constructed of aluminum fins mechani-  
cally bonded to copper tubes which are then  
cleaned, dehydrated, and sealed. Copper fins shall  
be available as an option.  
F. Air-cooled condenser coils shall be leak tested at  
150 psig and pressure tested at 480 psig.  
1.03 DELIVERY, STORAGE, AND HANDLING  
Unit shall be shipped as a single package only, and  
shall be stored and handled per manufacturer’s  
recommendations.  
F. Refrigeration Components:  
1. Refrigeration circuit components for 566D units shall  
include hot gas muffler, high-side pressure relief  
device, liquid line shutoff valve, suction and dis-  
charge shutoff valves, holding charge of refrigerant  
R-22, and compressor oil.  
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING  
ENGINEER.)  
PART 2 — PRODUCTS  
2.01 EQUIPMENT  
A. General:  
2. Refrigeration circuit components for 566E units shall  
include liquid line service valve, suction line service  
valve, a full charge of compressor oil, and a holding  
charge of refrigerant.  
Factory assembled, single piece, air-cooled condensing  
unit. Contained within the unit enclosure shall be all  
factory wiring, piping, controls, compressor, holding  
charge (R-22), and special features required prior to field  
start-up.  
G. Controls and Safeties:  
1. Minimum control functions shall include:  
a. Power and control terminal blocks.  
B. Unit Cabinet:  
b. Compressor cycle delay protection prevents the  
compressor from restarting for a minimum of  
5 minutes after shutdown.  
c. Capacity control on the compressor shall be by  
suction cutoff unloader in response to compres-  
sor suction pressure. Electric solenoid unloading  
shall be available as an accessory (566D unit).  
d. Head pressure control by fan cycling. One con-  
denser fan shall be cycled by discharge pressure  
to maintain proper head pressure.  
Unit cabinet shall be constructed of G-90 galvanized  
steel, bonderized and coated with a prepainted, baked  
enamel finish.  
C. Fans:  
1. Condenser fans shall be direct-drive propeller type,  
discharging air vertically upward.  
2. Condenser-fan motor no. 1 shall be ball bearing type  
compatible with accessory low-ambient control.  
3. Shafts shall have inherent corrosion resistance.  
2. Minimum safety devices shall include:  
Automatic reset (after resetting first at thermostat)  
a. High discharge-pressure cutout.  
4. Fan blades shall be statically and dynamically  
balanced.  
5. Condenser fan openings shall be equipped with  
PVC-coated steel wire safety guards.  
b. Low suction pressure cutout.  
c. Condenser-fan motors to be protected against  
overload condition by internal overloads.  
D. Compressors:  
1. 566D150-240 Units:  
a. Compressor shall be serviceable, reciprocating,  
semi-hermetic type.  
59  
GUIDE SPECIFICATIONS — 566D150-240, 566E150-240 (cont)  
Manual reset at the unit  
b. E-Coated Aluminum-Fin Coils:  
Electrical overload protection through the use of def-  
inite-purpose contactors and calibrated, ambient  
compensated, magnetic trip circuit breakers. Circuit  
breakers shall open all 3 phases in the event of an  
overload in any one of the phases or a single-phase  
condition.  
Shall have a flexible epoxy polymer coating uni-  
formly applied to all coil surface areas without  
material bridging between fins. Coating process  
shall ensure complete coil encapsulation. Color  
shall be high gloss black with gloss requirements  
of 60° of 65-90% per ASTM D523-89. Uniform dry  
film thickness from 0.8 to 1.2 mil on all surface  
areas including fin edges. Superior hardness  
characteristics of 2H per ASTM D3363-92A and  
cross hatch adhesion of 4B-5B per ASTM D3359-  
93. Impact resistance shall be up to 160 in./lb  
(ASTM D2794-93). Humidity and water immersion  
resistance shall be up to a minimum of 1000 and  
250 hours respectively (ASTM-D2247-92 and  
ASTM D870-92). Corrosion durability shall be  
confirmed through testing to no less than 1000  
hours salt spray per ASTM B117-90. Coil con-  
struction shall be aluminum-fins mechanically  
bonded to copper tubes.  
H. Operating Characteristics:  
1. The capacity of the condensing unit shall meet or  
exceed_____Btuh at a suction temperature of_____ F.  
The power consumption at full load shall not  
exceed_____ kW.  
2. The combination of the condensing unit and the  
evaporator or fan coil unit shall have a total net cool-  
ing capacity of _____ Btuh or greater at conditions of  
_____ cfm entering-air temperature at the evaporator  
at _____ F wet bulb and _____ F dry bulb, and air  
entering the condensing unit at _____ F.  
3. The system shall have an EER of _____ Btuh/Watt or  
greater at standard ARI conditions.  
6. Thermostat Control Accessory:  
I. Electrical Requirements:  
a. Commercial Electronic Thermostat with 7-day  
timeclock, auto-changeover, multi-stage capabil-  
ity, and large LCD temperature display.  
1. Nominal unit electrical characteristics shall be _____ v,  
3-ph, 60 Hz. The unit shall be capable of satisfactory  
operation within voltage limits of _____ v to _____ v.  
b. Commercial Electronic Non-programmable Ther-  
mostat with auto-changeover, multi-stage capabil-  
ity, and large LCD temperature display.  
2. Unit electrical power shall be single point connection.  
3. Unit control circuit shall contain a 24-v transformer  
for unit control, with capacity to operate an indoor fan  
interlock.  
7. Unit-Mounted, Non-Fused Disconnect Switch:  
Shall be factory-installed, internally mounted. NEC  
and UL approved non-fused switch shall provide unit  
power shutoff. Shall be accessible from outside the  
unit and shall provide power off lockout capability.  
Not to be used when rooftop electrical rating  
exceeds 80 amperes.  
J. Special Features:  
1. Low-Ambient Temperature Control (Factory-Installed  
Option or Field-Installed Accessory):  
Control shall regulate fan motor speed in response  
to the saturated condensing temperature of the unit.  
The control shall allow the unit to operate down to an  
ambient temperature of –20 F.  
8. Convenience Outlet:  
Shall be factory-installed and internally mounted  
with easily accessible 115-v female receptacle. Shall  
include 15 amp GFI receptacle with independent  
fuse protection. Voltage required to operate conve-  
nience outlet shall be provided by a factory-installed  
step-down transformer. Shall be accessible from out-  
side the unit.  
2. Electric Solenoid Unloader Accessory:  
Unloader valve piston, coil, and hardware shall be  
supplied to convert the pressure-operated compres-  
sor unloader to electric unloading.  
3. Hail Guard Package:  
Hail guard package shall protect coil against hail and  
other flying debris.  
4. Condenser Coil Grille Package:  
Grilles shall protect the condenser coils after unit  
installation.  
5. Optional Condenser Coil Materials:  
a. Pre-Coated Aluminum-Fin Coils:  
Shall have a durable epoxy-phenolic coating to  
provide protection in mildly corrosive coastal envi-  
ronments. Coating shall be applied to the alumi-  
num fin stock prior to the fin stamping process to  
create an inert barrier between the aluminum fin  
and copper tube. Epoxy-phenolic barrier shall  
minimize galvanic action between dissimilar  
metals.  
60  
MODEL NUMBER NOMENCLATURE  
524A 120 000 GC  
P
B
Factory-Installed Options  
GC Unpainted, Standard Motor  
and Standard Drive  
HC Unpainted, Standard Motor  
and Medium-Static Drive  
(not available for 300 sizes)  
TC Unpainted, Alternate Motor  
and Medium-Static Drive  
(300 size only)  
YC Unpainted, Alternate Motor  
and High-Static Drive*  
ED Painted, Standard Motor  
and Standard Drive  
524A Fan Coil  
Voltage  
E 460-3-60†  
J 208/230-1-60 (Sizes 072, 090 Only)  
P 208/230-3-60  
T 575-3-60  
Coil Option  
B DX Cooling Coil With TXVs  
C DX High Capacity Cooling Coil With TXVs  
FD Painted, Standard Motor  
and Medium-Static Drive  
(not available for 300 size)  
RD Painted, Alternate Motor  
and Medium-Static Drive  
(300 size only)  
Nominal Cooling (Tons)  
072 6  
090 7-1/2  
120 10  
150 12-1/2  
180 15  
WD Painted, Alternate Motor  
and High-Static Drive*  
240 20  
300 25  
Nominal Heating (Btuh)  
000 Not applicable (524A-B and 524A-C Cooling-Only Units)  
Quality Assurance  
Certified to ISO 9001:2000  
LEGEND  
DX Direct Expansion  
TXV — Thermostatic Expansion Valve  
*The YC and WD option codes for all 090 size units with 208/230-1-60 voltage designate standard motor and high-static drive.  
†All 524A072-150 units with an “E” voltage designation are triple voltage (i.e., 208/230/460-3-60). Size 524A180 is also triple voltage in the “E” con-  
figuration unless the alternate motor (YC or WD) option is used.  
61  
PHYSICAL DATA  
524A-B,C UNITS  
UNIT 524A  
072  
090  
120  
150  
180  
240  
300  
NOMINAL CAPACITY (Tons)  
6
71/2  
10  
121/2  
15  
20  
25  
OPERATING WEIGHT (lb)  
Base Unit with TXV (3 Row/4 Row)  
Plenum  
381/399  
175  
385/404  
175  
405/425  
175  
670/695  
225  
685/713  
225  
690/730  
225  
1020/1050  
325  
Economizer  
185  
185  
185  
340  
340  
340  
340  
Hot Water Coil  
Steam Coil  
195  
215  
195  
215  
195  
215  
285  
340  
285  
340  
285  
340  
345  
405  
FANS  
Qty...Diam. (in.)  
1...15  
2400  
1...15  
3000  
1...15  
4000  
2...15  
5000  
2...15  
6000  
2...15  
8000  
2...18  
10,000  
Nominal Airflow (cfm)  
Airflow Range (cfm)  
Nominal Motor Hp (Standard Motor)*  
208/230-1-60  
1800-3000  
2250-3750  
3000-5000  
3750-6250  
4500-7500  
6000-10,000  
7500-12,500  
1.3  
2.4  
1.0  
2.4  
2.4  
2.0  
2.4  
2.0  
2.9  
3.0  
3.7  
3.0  
5.0  
5.0  
7.5  
7.5  
208/230-3-60 and 460-3-60  
575-3-60  
Motor Speed (rpm)  
208/230-1-60  
208/230-3-60 and 460-3-60  
575-3-60  
1725  
1725  
1725  
1725  
1725  
1725  
1725  
1725  
1725  
1725  
1725  
1725  
1745  
1745  
1745  
1755  
REFRIGERANT  
R-22  
Operating charge (lb)  
(approx per circuit)†  
3.0  
3.0  
1.5/1.5  
2.0/2.0  
2.5/2.5  
3.5/3.5  
4.5/4.5  
DIRECT-EXPANSION COIL  
Max Working Pressure (psig)  
Face Area (sq ft)  
Enhanced Copper Tubes, Aluminum Sine-Wave Fins  
435  
6.67  
1
8.33  
1
10.01  
2
13.25  
2
17.67  
19.88  
2
24.86  
2
No. of Splits  
2
Split Type...Percentage  
No. of Circuits per Split (3 Row/4 Row)  
Fins/in.  
Face...50/50  
12/16  
15  
12/12  
15  
15/15  
15  
9/9  
17  
9/12  
15  
13/18  
17  
15/20  
15  
STEAM COIL  
Max Working Pressure (psig at 400 F)  
Total Face Area (sq ft)  
Rows...Fins/in.  
175  
13.33  
1...10  
6.67  
1...9  
6.67  
1...9  
6.67  
1...9  
13.33  
1...10  
13.33  
1...10  
15.0  
1...10  
HOT WATER COIL  
Max Working Pressure (psig)  
Total Face Area (sq ft)  
Rows...Fins/in.  
Water Volume  
(gal)  
150  
6.67  
2...8.5  
6.67  
6.67  
2...8.5  
13.33  
13.33  
13.33  
2...8.5  
15.0  
2...8.5  
2...8.5  
2...8.5  
2...12.5  
8.3  
1.1  
13.9  
1.85  
14.3  
1.90  
(ft3)  
PIPING CONNECTIONS  
Quantity...Size (in.)  
DX Coil — Suction (ODF)  
DX Coil — Liquid Refrigerant (ODF)  
Steam Coil, In (MPT)  
1...11/8  
1...11/8  
2...11/8  
2...11/8  
2...11/8  
2...5/8  
2...1 1  
/
8
2...13/8  
1...5/8  
1...21/2  
1...11/2  
1...11/2  
1...11/2  
1...21/2  
1...11/2  
Steam Coil, Out (MPT)  
Hot Water Coil, In (MPT)  
Hot Water Coil, Out (MPT)  
Condensate (PVC)  
1...11/2  
1...11/2  
1...2  
1...2  
1...11/4 ODM/1 IDF  
FILTERS  
Throwaway — Factory Supplied  
4...16 x 20 x 2  
4...20 x 24 x 2  
4...20 x 25 x 2  
Quantity...Size (in.)  
Access Location  
4...16 x 24 x 2  
4...16 x 24 x 2  
Right or Left Side  
LEGEND  
DX  
TXV  
Direct Expansion  
Thermostatic Expansion Valve  
*Refer to Alternate Fan Motor Data table, page 80, for alternate motor data.  
†Units are shipped without refrigerant charge.  
62  
DIMENSIONS  
UNIT WEIGHT  
(lb)  
UNIT  
524A-B072  
524A-B090  
524A-B120  
524A-C072  
524A-C090  
524A-C120  
381  
385  
405  
399  
404  
425  
LEGEND  
TXV  
Thermostatic Expansion Valve  
NOTES:  
1. Dimensions in [ ] are in millimeters.  
2. Direction of airflow.  
3. Recommended clearance:  
• Rear: 3(76.2 mm) (2-6[762 mm]  
with electric heat accessory)  
• Front: 2-6(762 mm)  
• Right Side: 2-6(762 mm)  
• Left Side: 2-6(762 mm)  
• Local codes or jurisdiction may prevail.  
4. Liquid piping not supplied by Bryant.  
5. Duct flange is factory supplied and field  
installed.  
524A-B,C072-120  
63  
DIMENSIONS (cont)  
.
UNIT  
WEIGHT  
(lb)  
UNIT  
524A  
B150  
B180  
B240  
C150  
C180  
C240  
670  
685  
690  
695  
713  
730  
LEGEND  
Thermostatic Expansion Valve  
TXV  
NOTES:  
1. Dimensions in [ ] are in millimeters.  
2. Direction of airflow.  
3. Recommended clearance:  
• Rear: 3(76.2 mm) (2-6[762 mm]  
with electric heat accessory)  
• Front: 2-6(762 mm)  
• Right Side: 2-6(762 mm)  
• Left Side: 2-6(762 mm)  
• Local codes or jurisdiction may prevail.  
4. Liquid piping not supplied by Bryant.  
5. Duct flange is factory supplied and field  
installed.  
524A-B,C150-240  
64  
DIMENSIONS (cont)  
UNIT  
WEIGHT  
(lb)  
UNIT  
524A  
CONTROL BOX  
B300  
C300  
1020  
1050  
ALTERNATE  
ACCESS  
FOR FILTERS  
ALTERNATE  
ACCESS FOR  
MOTOR/BELT  
RETURN AIR  
OPENING  
CONTROL BOX  
LEGEND  
Thermostatic Expansion Valve  
TXV  
NOTES:  
1. Dimensions in [ ] are in millimeters.  
2. Direction of airflow.  
3. Recommended clearance:  
• Rear: 3(76.2 mm) (2-6[762 mm]  
with electric heat accessory)  
• Front: 2-6(762 mm)  
• Right Side: 2-6(762 mm)  
• Left Side: 2-6(762 mm)  
• Local codes or jurisdiction may prevail.  
4. Liquid piping not supplied by Bryant.  
5. Duct flange is factory supplied and field  
installed.  
524A-B,C300  
65  
PERFORMANCE DATA  
524A-B FAN PERFORMANCE DATA — 0.0-1.2 in. wg ESP  
EXTERNAL STATIC PRESSURE (in. wg)  
UNIT  
AIRFLOW  
0.0  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
524A-B  
(Cfm)  
Rpm  
399  
446  
498  
544  
594  
Bhp  
0.19  
0.28  
0.40  
0.55  
0.73  
Rpm  
454  
497  
541  
588  
635  
Bhp  
0.24  
0.34  
0.47  
0.63  
0.82  
Rpm  
548  
583  
622  
663  
707  
Bhp  
0.35  
0.46  
0.60  
0.78  
0.99  
Rpm  
634  
660  
693  
730  
770  
Bhp  
0.47  
0.59  
0.74  
0.93  
1.15  
Rpm  
713  
733  
760  
792  
828  
Bhp  
0.60  
0.73  
0.89  
1.09  
1.32  
Rpm  
785  
802  
824  
851  
883  
Bhp  
0.74  
0.88  
1.05  
1.26  
1.50  
Rpm  
850  
867  
885  
909  
937  
Bhp  
0.89  
1.05  
1.22  
1.44  
1.69  
1,800  
2,100  
2,400  
2,700  
3,000  
072  
090  
120  
150  
180  
240  
300  
2,250  
2,600  
3,000  
3,400  
3,750  
273  
322  
552  
615  
671  
0.08  
0.15  
0.65  
0.91  
1.20  
493  
540  
595  
653  
706  
0.37  
0.52  
0.73  
1.01  
1.31  
580  
622  
673  
726  
773  
0.49  
0.66  
0.91  
1.21  
1.53  
656  
693  
740  
789  
834  
0.62  
0.81  
1.07  
1.40  
1.74  
727  
757  
800  
846  
889  
0.76  
0.96  
1.24  
1.59  
1.95  
794  
819  
856  
899  
940  
0.92  
1.12  
1.41  
1.78  
2.16  
858  
878  
910  
950  
988  
1.08  
1.29  
1.60  
1.97  
2.37  
3,000  
3,500  
4,000  
4,500  
5,000  
399  
604  
680  
756  
834  
0.29  
0.92  
1.33  
1.86  
2.51  
573  
641  
713  
787  
861  
0.69  
1.02  
1.45  
1.99  
2.67  
654  
714  
778  
845  
914  
0.86  
1.22  
1.68  
2.26  
2.96  
722  
780  
839  
901  
966  
1.03  
1.42  
1.91  
2.52  
3.25  
784  
838  
896  
955  
1180  
1.19  
1.61  
2.14  
2.78  
3.54  
841  
892  
947  
1005  
1064  
1.37  
1.81  
2.36  
3.03  
3.82  
896  
942  
995  
1051  
1109  
1.55  
2.01  
2.58  
3.28  
4.11  
3,750  
4,300  
5,000  
5,700  
6,250  
394  
436  
492  
550  
596  
0.40  
0.57  
0.86  
1.23  
1.59  
453  
487  
535  
587  
630  
0.52  
0.70  
0.99  
1.37  
1.74  
558  
586  
623  
664  
700  
0.80  
1.00  
1.31  
1.71  
2.09  
643  
670  
704  
740  
770  
1.10  
1.34  
1.69  
2.11  
2.51  
717  
742  
775  
809  
837  
1.39  
1.67  
2.08  
2.55  
2.97  
785  
806  
838  
872  
899  
1.71  
2.01  
2.47  
2.99  
3.45  
848  
867  
896  
929  
955  
2.04  
2.36  
2.86  
3.43  
3.94  
4,500  
5,300  
6,000  
6,800  
7,500  
428  
488  
542  
604  
660  
0.59  
0.92  
1.29  
1.83  
2.42  
475  
528  
578  
637  
690  
0.70  
1.04  
1.43  
1.99  
2.59  
570  
609  
649  
700  
747  
0.99  
1.34  
1.74  
2.32  
2.95  
656  
689  
721  
763  
804  
1.33  
1.71  
2.11  
2.70  
3.34  
730  
762  
791  
826  
861  
1.68  
2.11  
2.55  
3.15  
3.79  
796  
827  
855  
888  
919  
2.02  
2.51  
3.00  
3.64  
4.29  
856  
886  
914  
946  
975  
2.38  
2.92  
3.46  
4.15  
4.83  
6,000  
7,000  
8,000  
9,000  
10,000  
532  
608  
686  
764  
843  
1.25  
1.93  
2.83  
3.97  
5.38  
569  
641  
716  
791  
868  
1.39  
2.09  
3.01  
4.18  
5.62  
639  
702  
770  
841  
914  
1.69  
2.42  
3.38  
4.59  
6.09  
711  
763  
823  
888  
957  
2.06  
2.80  
3.77  
5.02  
6.55  
781  
824  
876  
935  
1000  
2.48  
3.23  
4.21  
5.47  
7.02  
846  
885  
930  
982  
1042  
2.93  
3.71  
4.70  
5.96  
7.53  
905  
943  
983  
1030  
1084  
3.39  
4.23  
5.24  
6.51  
8.08  
7,500  
8,750  
10,000  
11,250  
12,500  
456  
521  
587  
653  
720  
1.29  
1.98  
2.88  
4.03  
5.46  
490  
551  
614  
678  
743  
1.47  
2.18  
3.11  
4.29  
5.75  
556  
608  
664  
724  
785  
1.85  
2.61  
3.59  
4.82  
6.33  
621  
664  
714  
768  
825  
2.25  
3.07  
4.09  
5.37  
6.93  
678  
720  
763  
812  
865  
2.64  
3.53  
4.62  
5.95  
7.55  
729  
770  
812  
856  
904  
3.06  
3.99  
5.15  
6.54  
8.20  
778  
816  
857  
899  
944  
3.60  
4.45  
5.68  
7.14  
8.86  
See Legend and Notes on page 67.  
66  
PERFORMANCE DATA (cont)  
524A-B FAN PERFORMANCE DATA — 1.4-2.4 in. wg ESP  
EXTERNAL STATIC PRESSURE (in. wg)  
UNIT  
AIRFLOW  
1.4  
1.6  
1.8  
2.0  
2.2  
2.4  
524A-B  
(Cfm)  
Rpm  
910  
927  
944  
964  
989  
Bhp  
1.04  
1.21  
1.41  
1.63  
1.89  
Rpm  
965  
983  
999  
1018  
1039  
Bhp  
1.20  
1.38  
1.59  
1.82  
2.10  
Rpm  
1180  
1035  
1052  
1069  
1089  
Bhp  
1.36  
1.56  
1.78  
2.03  
2.31  
Rpm  
1065  
1084  
1101  
1118  
1136  
Bhp  
1.52  
1.74  
1.98  
2.24  
2.53  
Rpm  
1111  
1131  
1149  
1165  
1183  
Bhp  
1.69  
1.92  
2.18  
2.45  
2.76  
Rpm  
1155  
1175  
1193  
Bhp  
1.86  
2.11  
2.38  
1,800  
2,100  
2,400  
2,700  
3,000  
072  
090  
120  
150  
180  
240  
300  
2,250  
2,600  
3,000  
3,400  
3,750  
918  
936  
963  
998  
1360  
1.26  
1.48  
1.79  
2.18  
2.58  
975  
991  
1150  
1045  
1078  
1.43  
1.67  
1.99  
2.39  
2.80  
1029  
1044  
1064  
1092  
1122  
1.62  
1.87  
2.20  
2.61  
3.03  
1079  
1094  
1113  
1137  
1164  
1.80  
2.07  
2.42  
2.83  
3.27  
1126  
1142  
1159  
1182  
1.99  
2.28  
2.64  
3.07  
1172  
1188  
2.18  
2.49  
3,000  
3,500  
4,000  
4,500  
5,000  
949  
990  
1040  
1094  
1151  
1.74  
2.21  
2.80  
3.53  
4.39  
1000  
1037  
1084  
1136  
1191  
1.93  
2.42  
3.03  
3.78  
4.66  
1050  
1083  
1126  
1176  
2.14  
2.64  
3.26  
4.03  
1099  
1128  
1167  
2.36  
2.86  
3.50  
1147  
1172  
2.58  
3.10  
1192  
2.81  
3,750  
4,300  
5,000  
5,700  
6,250  
909  
925  
950  
981  
1072  
2.37  
2.73  
3.26  
3.88  
4.42  
968  
980  
1002  
1031  
1057  
2.74  
3.11  
3.67  
4.33  
4.91  
1026  
1360  
1052  
1079  
1103  
3.12  
3.52  
4.09  
4.79  
5.40  
1080  
1084  
1101  
1125  
1148  
3.51  
3.92  
4.53  
5.25  
5.90  
1131  
1135  
1148  
1169  
1191  
3.92  
4.35  
4.98  
5.73  
6.40  
1181  
1184  
1190  
4.32  
4.78  
5.44  
4,500  
5,300  
6,000  
6,800  
7,500  
912  
940  
968  
1000  
1300  
2.75  
3.33  
3.92  
4.67  
5.39  
967  
992  
1018  
1050  
1078  
3.13  
3.75  
4.38  
5.19  
5.97  
1019  
1041  
1066  
1097  
1125  
3.52  
4.18  
4.85  
5.71  
6.54  
1070  
1088  
1112  
1142  
1170  
3.92  
4.61  
5.32  
6.23  
7.11  
1120  
1134  
1156  
1185  
4.35  
5.06  
5.80  
6.76  
1168  
1179  
1198  
4.79  
5.52  
6.29  
6,000  
7,000  
8,000  
9,000  
10,000  
954  
990  
1300  
1073  
1126  
3.83  
4.74  
5.79  
7.11  
8.75  
1005  
1040  
1078  
1120  
1166  
4.27  
5.24  
6.38  
7.72  
9.37  
1052  
1090  
1130  
1169  
4.72  
5.80  
7.00  
8.37  
1098  
1135  
1173  
5.22  
6.30  
7.60  
1142  
1176  
5.67  
6.84  
7,500  
8,750  
10,000  
11,250  
12,500  
831  
859  
900  
941  
984  
4.41  
4.97  
6.20  
7.73  
9.53  
870  
901  
939  
980  
1022  
5.10  
5.59  
6.74  
8.32  
10.19  
913  
944  
976  
1017  
1058  
5.90  
6.42  
7.33  
8.90  
10.84  
950  
980  
1013  
1052  
1093  
6.88  
7.20  
8.00  
9.51  
11.49  
985  
1020  
1050  
1086  
7.70  
8.10  
8.82  
10.16  
LEGEND  
NOTES:  
1. Maximum allowable fan speed is 1100 rpm for unit size 300;  
1200 rpm for all other sizes.  
Bhp — Brake Horsepower Input to Fan  
ESP — External Static Pressure  
2. Fan performance is based on deductions for wet coil, clean 2-in.  
filters, and unit casing. See table on page 70 for factory-supplied  
filter pressure drop.  
3. The medium-static drive and standard motor combination is not  
available for 300 size. Use alternate motor if medium-static drive is  
required for these sizes.  
Bold indicates field-supplied drive is required.  
Plain type indicates standard motor and standard drive.  
Underline indicates a different motor and drive combination other than  
the standard motor and standard drive combination is required. Refer to  
fan motor and drive tables, pages 79-81, to complete selection.  
67  
PERFORMANCE DATA (cont)  
FAN PERFORMANCE DATA — 524A-C WITH HIGH CAPACITY COIL —  
0.0-1.2 in. wg ESP  
UNIT  
EXTERNAL STATIC PRESSURE (in. wg)  
524A-C  
AIRFLOW  
(Cfm)  
0.0  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
(High-Capacity  
4-Row Coil)  
Rpm Bhp Rpm Bhp Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
1,800  
2,100  
2,400  
2,700  
3,000  
419  
471  
524  
578  
633  
0.21  
0.31  
0.44  
0.61  
0.81  
471  
519  
568  
619  
671  
0.26  
0.37  
0.51  
0.69  
0.90  
564  
602  
645  
690  
738  
0.37  
0.49  
0.64  
0.84  
1.07  
649  
679  
715  
755  
799  
0.49  
0.62  
0.79  
0.99  
1.24  
727  
751  
781  
816  
856  
0.63  
0.77  
0.94  
1.15  
1.41  
797  
819  
844  
875  
910  
0.77  
0.92  
1.11  
1.33  
1.60  
862  
882  
905  
932  
963  
0.92  
1.09  
1.28  
1.51  
1.79  
072  
090  
120  
150  
180  
240  
300  
2,250  
2,600  
3,000  
3,400  
3,750  
290  
349  
579  
646  
705  
0.10  
0.19  
0.70  
0.99  
1.31  
510  
561  
621  
683  
739  
0.39  
0.55  
0.79  
1.09  
1.42  
594  
640  
695  
752  
804  
0.51  
0.70  
0.96  
1.29  
1.63  
669  
709  
759  
813  
862  
0.65  
0.84  
1.12  
1.48  
1.85  
739  
773  
818  
869  
915  
0.79  
1.00  
1.30  
1.67  
2.05  
806  
834  
874  
920  
964  
0.95  
1.16  
1.47  
1.86  
870  
893  
928  
970  
1.12  
1.34  
1.66  
2.06  
2.48  
2.26 1011  
3,000  
3,500  
4,000  
4,500  
5,000  
421  
626  
706  
786  
867  
0.35  
0.98  
1.42  
1.99  
2.70  
592  
664  
738  
815  
893  
0.73  
1.08  
1.54  
2.12  
2.84  
670  
735  
803  
873  
946  
0.90  
1.28  
1.77  
2.39  
3.14  
737  
798  
862  
929  
997  
1.06  
1.48  
2.00  
2.65  
797  
855  
917  
980  
1.23  
1.67  
2.23  
2.90 1300  
3.72 1092  
854  
908  
967  
1.41  
1.87  
2.45 1150  
3.16 1073  
4.00 1135  
908  
958  
1.59  
2.07  
2.67  
3.41  
4.28  
3.43 1046  
3,750  
4,300  
5,000  
5,700  
6,250  
410  
455  
514  
575  
624  
0.43  
0.62  
0.92  
1.32  
1.71  
467  
504  
556  
612  
657  
0.55  
0.74  
1.06  
1.47  
1.87  
567  
599  
641  
686  
725  
0.83  
1.05  
1.39  
1.82  
2.24  
649  
679  
718  
759  
793  
1.12  
1.38  
1.76  
2.23  
2.66  
721  
748  
786  
825  
856  
1.41  
1.70  
2.14  
2.66  
3.12  
788  
811  
847  
884  
915  
1.72  
2.04  
2.52  
3.09  
3.59  
851  
871  
903  
939  
969  
2.05  
2.39  
2.91  
3.52  
4.06  
4,500  
5,300  
6,000  
6,800  
7,500  
437  
499  
555  
620  
677  
0.61  
0.95  
1.34  
1.91  
2.52  
483  
538  
590  
651  
706  
0.72  
1.07  
1.48  
2.06  
2.69  
576  
617  
659  
712  
761  
1.01  
1.37  
1.79  
2.39  
3.04  
660  
696  
730  
774  
817  
1.35  
1.74  
2.17  
2.78  
3.44  
732  
767  
798  
836  
873  
1.69  
2.13  
2.59  
3.22  
3.89  
797  
830  
860  
896  
929  
2.03  
2.53  
3.04  
3.71  
4.39  
856  
888  
918  
952  
984  
2.38  
2.94  
3.49  
4.21  
4.93  
6,000  
7,000  
8,000  
9,000  
10,000  
542  
620  
700  
781  
862  
1.29  
1.99  
2.92  
4.10  
5.56  
577  
652  
728  
806  
885  
1.42  
2.15  
3.10  
4.30  
5.79  
646  
711  
781  
854  
929  
1.72  
2.48  
3.46  
4.71  
6.24  
716  
771  
833  
900  
971  
2.09  
2.85  
3.85  
5.13  
785  
831  
885  
946  
2.51  
3.28  
4.29  
5.58  
849  
890  
938  
993  
2.95  
3.76  
4.78  
6.08 1039  
7.69 1096  
907  
947  
990  
3.40  
4.27  
5.32  
6.62  
8.24  
6.70 1120  
7.18 1054  
7,500  
8,750  
10,000  
11,250  
12,500  
476  
545  
615  
685  
756  
1.39  
2.14  
3.12  
4.37  
5.92  
510  
574  
641  
709  
778  
1.58  
2.35  
3.36  
4.64  
6.22  
579  
633  
692  
754  
819  
1.99  
2.81  
3.87  
5.20  
6.83  
644  
691  
743  
800  
860  
2.40  
3.29  
4.41  
5.79  
7.47  
701  
747  
794  
845  
901  
2.81  
3.77  
4.96  
6.40  
8.14  
752  
797  
843  
891  
942  
3.29  
4.25  
5.51  
7.02  
8.83  
804  
842  
888  
935  
983  
3.96  
4.76  
6.05  
7.64  
9.52  
See Legend and Notes on page 69.  
68  
PERFORMANCE DATA (cont)  
FAN PERFORMANCE DATA — 524A-C  
WITH HIGH CAPACITY COIL — 1.4-2.4 in. wg ESP  
UNIT  
EXTERNAL STATIC PRESSURE (in. wg)  
1.8 2.0  
524A-C  
AIRFLOW  
(Cfm)  
1.4  
1.6  
2.2  
2.4  
(High-Capacity  
4-Row Coil)  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
1,800  
2,100  
2,400  
2,700  
3,000  
921  
942  
963  
987  
1015  
1.07  
1.26  
1.47  
1.71  
1.99  
975  
997  
1017  
1039  
1065  
1.23  
1.43  
1.66  
1.91  
2.20  
1026  
1048  
1069  
1090  
1113  
1.39  
1.61  
1.85  
2.12  
2.42  
1074  
1097  
1118  
1138  
1161  
1.55  
1.79  
2.05  
2.33  
2.65  
1120  
1143  
1164  
1185  
1.72  
1.97  
2.25  
2.55  
1164  
1186  
1.90  
2.16  
072  
090  
120  
150  
180  
240  
300  
2,250  
2,600  
3,000  
3,400  
3,750  
930  
950  
980  
1018  
1057  
1.29  
1.53  
1.86  
2.26  
2.69  
986  
1005  
1031  
1065  
1101  
1.47  
1.72  
2.06  
2.48  
2.92  
1039  
1057  
1081  
1111  
1144  
1.65  
1.92  
2.27  
2.70  
3.15  
1089  
1107  
1129  
1156  
1186  
1.84  
2.13  
2.49  
2.93  
3.39  
1136  
1154  
1175  
2.03  
2.33  
2.72  
1181  
2.22  
3,000  
3,500  
4,000  
4,500  
5,000  
961  
1005  
1058  
1116  
1176  
1.78  
2.27  
2.90  
3.66  
4.56  
1120  
1052  
1101  
1157  
1.98  
2.49  
3.13  
3.91  
1062  
1098  
1143  
1196  
2.19  
2.71  
3.36  
4.16  
1111  
1142  
1184  
2.41  
2.94  
3.60  
1158  
1186  
2.64  
3.18  
3,750  
4,300  
5,000  
5,700  
6,250  
912  
928  
956  
990  
1019  
2.39  
2.75  
3.30  
3.96  
4.54  
971  
982  
1072  
1039  
1067  
2.76  
3.13  
3.71  
4.40  
5.02  
1300  
1036  
1056  
1086  
1112  
3.14  
3.53  
4.13  
4.85  
5.50  
1083  
1087  
1104  
1130  
1156  
3.54  
3.94  
4.56  
5.31  
5.99  
1135  
1138  
1151  
1174  
1198  
3.95  
4.37  
5.00  
5.78  
6.49  
1185  
1187  
1196  
4.36  
4.81  
5.46  
4,500  
5,300  
6,000  
6,800  
7,500  
912  
942  
971  
1005  
1036  
2.75  
3.34  
3.95  
4.72  
5.48  
967  
992  
1020  
1054  
1084  
3.12  
3.76  
4.40  
5.23  
6.04  
1019  
1041  
1067  
1101  
1131  
3.52  
4.18  
4.86  
5.75  
6.61  
1070  
1088  
1112  
1145  
1174  
3.92  
4.61  
5.33  
6.27  
7.17  
1120  
1134  
1156  
1187  
4.35  
5.06  
5.81  
6.79  
1168  
1179  
1198  
4.79  
5.52  
6.29  
6,000  
7,000  
8,000  
9,000  
10,000  
961  
1000  
1041  
1086  
1138  
3.86  
4.79  
5.88  
7.21  
8.83  
1011  
1050  
1090  
1133  
1240  
4.31  
5.32  
6.47  
7.82  
9.46  
1058  
1097  
1137  
1178  
4.77  
5.85  
7.07  
8.47  
1104  
1142  
1181  
5.24  
6.38  
7.67  
1147  
1184  
5.71  
6.91  
7,500  
8,750  
10,000  
11,250  
12,500  
874  
886  
930  
976  
1023  
5.33  
5.36  
6.60  
8.25  
10.20  
897  
930  
969  
1150  
1061  
5.91  
6.13  
7.20  
8.86  
10.88  
940  
982  
1072  
1051  
1097  
6.80  
7.32  
7.89  
9.49  
11.56  
990  
1020  
1045  
1086  
7.50  
8.10  
8.71  
10.17  
LEGEND  
NOTES:  
1. Maximum allowable fan speed is 1100 rpm for unit size 300;  
1200 rpm for all other sizes.  
Bhp — Brake Horsepower Input to Fan  
ESP — External Static Pressure  
2. Fan performance is based on deductions for wet coil, clean 2-in.  
filters, and unit casing. See table on page 70 for factory-supplied  
filter pressure drop.  
3. The medium-static drive and standard motor combination is not  
available for 300 size. Use alternate motor if medium-static drive is  
required for these sizes.  
Bold indicates field-supplied drive is required.  
Plain type indicates standard motor and standard drive.  
Underline indicates a different motor and drive combination other than  
the standard motor and standard drive combination is required. Refer to  
fan motor and drive tables, pages 79-81, to complete selection.  
69  
PERFORMANCE DATA (cont)  
FACTORY-SUPPLIED FILTER PRESSURE DROP ACCESSORY PLENUM AIR THROW DATA  
UNIT  
VANE DEFLECTION  
UNIT  
524A  
AIRFLOW  
AIRFLOW  
PRESSURE DROP  
(in. wg)  
524A-B  
524A-C  
(Cfm)  
(Cfm)  
Straight  
21½°  
33  
45°  
24  
28  
30  
33  
28  
31  
37  
47  
072  
090  
102  
120  
150  
180  
240  
300  
2,400  
3,000  
3,400  
4,000  
5,000  
6,000  
8,000  
10,000  
39  
45  
49  
55  
45  
50  
60  
76  
1,800  
2,400  
3,000  
2,250  
3,000  
3,750  
3,000  
4,000  
5,000  
3,750  
5,000  
6,250  
4,500  
6,000  
7,500  
6,000  
8,000  
10,000  
0.05  
0.08  
0.11  
0.07  
0.11  
0.15  
0.11  
0.17  
0.23  
0.06  
0.10  
0.13  
0.08  
0.12  
0.17  
0.12  
0.19  
0.26  
0.15  
0.22  
0.30  
072  
090  
120  
150  
180  
240  
300  
38  
41  
46  
38  
43  
51  
65  
Throw distances shown are for 75 fpm terminal velocity. Use the follow-  
ing multipliers to determine throw values for other terminal velocities.  
TERMINAL VELOCITY  
THROW FACTOR  
(Fpm)  
50  
100  
150  
X 1.50  
X 0.75  
X 0.50  
7,500  
10,000  
12,500  
ACCESSORY PRESSURE DROP (in. wg)  
HEATING COILS  
Steam  
UNIT  
524A  
AIRFLOW  
(Cfm)  
DISCHARGE  
PLENUM  
RETURN AIR  
GRILLE  
ECONOMIZER  
Hot Water  
Electric  
1,800  
2,400  
3,000  
2,250  
3,000  
3,750  
2,550  
3,400  
4,250  
3,000  
4,000  
5,000  
3,750  
5,000  
6,250  
4,500  
6,000  
7,500  
6,000  
8,000  
10,000  
0.06  
0.10  
0.14  
0.09  
0.14  
0.21  
0.11  
0.17  
0.24  
0.14  
0.22  
0.32  
0.07  
0.12  
0.17  
0.10  
0.16  
0.23  
0.16  
0.26  
0.37  
0.15  
0.24  
0.34  
0.01  
0.01  
0.02  
0.01  
0.02  
0.03  
0.02  
0.03  
0.04  
0.02  
0.04  
0.06  
0.01  
0.02  
0.02  
0.01  
0.02  
0.03  
0.02  
0.04  
0.06  
0.02  
0.03  
0.05  
0.10  
0.16  
0.23  
0.15  
0.23  
0.35  
0.18  
0.28  
0.41  
0.23  
0.37  
0.53  
0.11  
0.17  
0.25  
0.15  
0.23  
0.33  
0.23  
0.37  
0.53  
0.28  
0.44  
0.63  
0.10  
0.16  
0.23  
0.15  
0.23  
0.35  
0.18  
0.28  
0.41  
0.23  
0.37  
0.53  
0.11  
0.17  
0.25  
0.15  
0.23  
0.33  
0.23  
0.37  
0.53  
0.28  
0.44  
0.63  
0.04  
0.06  
0.10  
0.06  
0.10  
0.15  
0.07  
0.12  
0.19  
0.10  
0.17  
0.26  
0.04  
0.07  
0.11  
0.06  
0.10  
0.15  
0.10  
0.17  
0.26  
0.09  
0.16  
0.24  
0.05  
0.07  
0.09  
0.06  
0.09  
0.15  
0.07  
0.13  
0.19  
0.09  
0.17  
0.28  
0.05  
0.07  
0.11  
0.06  
0.09  
0.15  
0.09  
0.17  
0.28  
0.06  
0.09  
0.14  
072  
090  
102  
120  
150  
180  
240  
300  
7,500  
10,000  
12,500  
70  
PERFORMANCE DATA (cont)  
HYDRONIC HEATING CAPACITIES  
1-ROW  
STEAM*  
2-ROW  
HOT WATER COIL†  
UNIT  
524A-B  
524A-C  
AIRFLOW  
(Cfm)  
Water  
Cap.  
Ldb  
Cap.  
Ldb  
Flow  
PD  
(Gpm)  
1,800  
2,400  
3,000  
2,250  
3,000  
3,750  
3,000  
4,000  
5,000  
3,750  
5,000  
6,250  
146  
173  
209  
168  
209  
240  
209  
243  
279  
370  
425  
465  
402  
458  
479  
458  
487  
499  
511  
575  
626  
134  
126  
123  
129  
123  
117  
123  
115  
111  
150  
137  
128  
141  
129  
118  
129  
115  
105  
122  
112  
106  
156.0  
183.0  
206.0  
174.0  
206.0  
238.0  
299.0  
275.0  
316.0  
362.0  
409.0  
456.0  
412.0  
471.0  
529.0  
506.0  
584.0  
652.0  
649.0  
752.0  
842.0  
140  
131  
124  
133  
124  
118  
152  
124  
119  
149  
136  
128  
145  
133  
125  
138  
128  
120  
140  
130  
122  
15.6  
18.3  
20.6  
17.4  
20.6  
23.8  
29.9  
27.5  
31.6  
36.2  
40.9  
45.6  
41.2  
47.1  
52.9  
50.6  
58.4  
65.2  
64.9  
75.2  
84.2  
3.4  
4.3  
5.2  
4.0  
5.2  
6.5  
5.0  
6.6  
8.2  
4.2  
5.1  
6.0  
4.5  
5.5  
6.6  
5.1  
6.3  
7.5  
5.7  
7.1  
8.5  
072  
090  
120  
150  
180  
240  
300  
4,500  
6,000  
7,500  
6,000  
8,000  
10,000  
7,500  
10,000  
12,500  
LEGEND  
NOTES:  
1. Maximum operating limits for heating coils: 20 psig at 260 F.  
Cap. — Capacity (Btuh in thousands)  
Capacity (Btuh)  
Lab  
PD  
Leaving-Air Dry-Bulb Temp (F)  
Pressure Drop (ft water)  
2. Leaving db = ent db (F) +  
1.1 x cfm  
3. See Heating Correction Factors table.  
*Based on 5 psig steam, 60 F entering-air temperature. All steam coils  
are non-freeze type.  
†Based on 200 F entering water, 20 F water temperature drop, 60 F  
entering-air temperature.  
HEATING CORRECTION FACTORS  
HOT WATER COIL  
Water Temp  
Drop  
Ent Water  
Temp  
(F)  
Entering-Air Temp (F)  
60  
40  
50  
70  
80  
(F)  
140  
160  
240  
200  
220  
140  
160  
240  
200  
220  
140  
160  
240  
200  
220  
0.72  
0.89  
1.06  
1.22  
1.39  
0.64  
0.81  
0.98  
1.15  
1.32  
0.56  
0.74  
0.91  
1.08  
1.25  
0.64  
0.81  
0.98  
1.15  
1.32  
0.57  
0.74  
0.91  
1.08  
1.25  
0.49  
0.66  
0.83  
1.00  
1.18  
0.57  
0.74  
0.90  
1.07  
1.24  
0.49  
0.66  
0.83  
1.00  
1.17  
0.41  
0.58  
0.76  
0.93  
1.10  
0.49  
0.66  
0.83  
1.00  
1.17  
0.41  
0.58  
0.75  
0.93  
1.10  
0.33  
0.51  
0.68  
0.85  
1.03  
0.41  
0.58  
0.75  
0.92  
1.09  
0.33  
0.51  
0.68  
0.85  
1.02  
0.24  
0.43  
0.60  
0.78  
0.95  
10  
20  
30  
STEAM COIL  
50  
Entering-Air Temp (F)  
60  
Steam Pressure  
(psig)  
40  
70  
80  
0
2
5
1.06  
1.09  
1.13  
0.98  
1.02  
1.06  
0.91  
0.95  
1.00  
0.85  
0.89  
0.93  
0.78  
0.82  
0.87  
NOTE: Multiply capacity given in the Hydronic Heating Capacities table by the correction factor for conditions at which unit is actually  
operating. Correct leaving-air temperature using formula in Note 2 of Hydronic Heating Capacities table.  
71  
ELECTRICAL DATA  
524A-B,C STANDARD MOTORS  
FAN MOTOR  
POWER SUPPLY  
Minimum Circuit  
UNIT  
524A-B  
524A-C  
VOLTAGE  
V*-PH-Hz  
LIMITS  
Hp (kW)  
FLA  
MOCP  
Amps  
208/230-1-60  
208/230-3-60  
460-3-60  
187-253  
187-253  
414-506  
518-632  
187-253  
187-253  
414-506  
518-632  
187-253  
414-506  
518-632  
187-253  
414-506  
518-632  
187-253  
414-506  
518-632  
187-253  
414-506  
518-632  
187-253  
414-506  
518-632  
1.3 (0.97)  
2.4 (1.79)  
2.4 (1.79)  
1.0 (0.75)  
2.4 (1.79)  
2.4 (1.79)  
2.4 (1.79)  
2.0 (1.49)  
2.4 (1.79)  
2.4 (1.79)  
2.0 (1.49)  
2.9 (2.16)  
2.9 (2.16)  
3.0 (2.24)  
3.7 (2.76)  
3.7 (2.76)  
3.0 (2.24)  
5.0 (3.73)  
5.0 (3.73)  
5.0 (3.73)  
7.5 (5.59)  
7.5 (5.59)  
7.5 (5.59)  
7.6  
5.2  
2.6  
1.4  
11.0  
5.2  
2.6  
2.3  
5.2  
2.6  
9.5  
6.5  
3.3  
1.8  
13.8  
6.5  
3.3  
2.9  
6.5  
3.3  
2.9  
9.4  
4.3  
4.8  
12.8  
6.0  
4.8  
18.3/16.0  
8.0  
15  
15  
15  
15  
20  
15  
15  
15  
15  
15  
15  
15  
15  
15  
20  
15  
15  
072  
090  
575-3-60  
208/230-1-60  
208/230-3-60  
460-3-60  
575-3-60  
208/230-3-60  
460-3-60  
575-3-60  
208/230-3-60  
460-3-60  
575-3-60  
208/230-3-60  
460-3-60  
575-3-60  
208/230-3-60  
460-3-60  
575-3-60  
208/230-3-60  
460-3-60  
120  
150  
180  
240  
300  
2.3  
7.5  
3.4  
3.8  
10.2  
4.8  
3.8  
14.6/12.8  
6.4  
5.1  
21.5/19.4  
9.7  
30/25  
15  
15  
45/40  
20  
15  
6.4  
26.9/24.3  
12.1  
9.8  
575-3-60  
7.8  
See Legend and Notes on page 73.  
72  
ELECTRICAL DATA (cont)  
524A-B,C ALTERNATE MOTORS  
FAN MOTOR  
POWER SUPPLY  
Minimum Circuit  
UNIT  
VOLTAGE  
524A-B  
524A-C  
V*-PH-Hz  
LIMITS  
Hp (kW)  
FLA  
MOCP  
Amps  
13.8  
9.4  
4.3  
2.9  
13.8  
9.4  
4.3  
4.8  
12.8  
6.0  
4.8  
12.7  
6.0  
6.4  
18.3/16.0  
8.0  
208/230-1-60  
208/230-3-60  
460-3-60  
187-253  
187-253  
414-506  
518-632  
187-253  
187-253  
414-506  
518-632  
187-253  
414-506  
518-632  
187-253  
414-506  
518-632  
187-253  
414-506  
518-632  
187-253  
414-506  
518-632  
187-253  
414-506  
518-632  
2.4 (1.79)  
2.9 (2.16)  
2.9 (2.16)  
2.0 (1.49)  
2.4 (1.79)  
2.9 (2.16)  
2.9 (2.16)  
3.0 (2.24)  
3.7 (2.76)  
3.7 (2.76)  
3.0 (2.24)  
3.7 (2.76)  
3.7 (2.76)  
5.0 (3.73)  
5.0 (3.73)  
5.0 (3.73)  
5.0 (3.73)  
7.5 (5.59)  
7.5 (5.59)  
7.5 (5.59)  
10.0 (7.46)  
10.0 (7.46)  
10.0 (7.46)  
11.0  
7.5  
3.4  
2.3  
11.0  
7.5  
3.4  
3.8  
10.2  
4.8  
3.8  
10.2  
4.8  
5.1  
14.6/12.8  
6.4  
5.1  
21.5/19.4  
9.7  
20  
15  
15  
15  
15  
15  
15  
15  
20  
15  
15  
20  
15  
15  
30/25  
15  
15  
45/40  
20  
072  
090  
575-3-60  
208/230-1-60  
208/230-3-60  
460-3-60  
575-3-60  
208/230-3-60  
460-3-60  
575-3-60  
208/230-3-60  
460-3-60  
575-3-60  
208/230-3-60  
460-3-60  
575-3-60  
208/230-3-60  
460-3-60  
575-3-60  
208/230-3-60  
460-3-60  
120  
150  
180  
240  
300  
6.4  
26.9/24.3  
12.1  
9.8  
35.3/33.5  
16.8  
12.9  
7.8  
15  
60/60  
30  
28.2/26.8  
13.4  
10.3  
575-3-60  
20  
LEGEND  
Full Load Amps  
Determine maximum deviation from average voltage.  
(AB) 397 – 393 = 4 v  
FLA  
(BC) 403 – 397 = 6 v  
MOCP — Maximum Overcurrent Protection  
(AC) 397 – 396 = 1 v  
*Motors are designed for satisfactory operation within 10% of nominal  
voltages shown. Voltages should not exceed the limits shown in the  
Voltage Limits column.  
Maximum deviation is 6 v.  
Determine percent of voltage imbalance.  
6
% Voltage Imbalance = 100 x  
NOTES:  
397  
1. Minimum circuit amps (MCA) and MOCP values are calculated in  
accordance with NEC (National Electrical Code) Article 440.  
2. Motor FLA values are established in accordance with UL (Under-  
writers’ Laboratories) Standard 1995.  
= 1.5%  
This amount of phase imbalance is satisfactory as it is below the  
maximum allowable 2%.  
IMPORTANT: If the supply voltage phase imbalance is more than  
2%, contact your local electric utility company immediately.  
3. Unbalanced 3-Phase Supply Voltage  
Never operate a motor where a phase imbalance in supply voltage  
is greater than 2%. Use the following formula to determine the per-  
centage of voltage imbalance.  
% Voltage Imbalance  
max voltage deviation from average voltage  
= 100 x  
average voltage  
Example: Supply voltage is 460-3-60.  
AB = 393 v  
BC = 403 v  
AC = 396 v  
393 + 403 + 396  
Average Voltage =  
3
1192  
3
=
= 397  
73  
ELECTRICAL DATA (cont)  
ELECTRIC HEATER DATA  
ELECTRIC HEATER(S)  
FAN MOTOR  
Nominal  
HEATER PART NO.  
CAELHEAT001A00  
UNIT  
V-PH-Hz  
Actual Capacity (kW)  
Stage 1 Stage 2 Total  
MCA* MOCP*  
FLA  
Capacity (kW)  
Hp  
kW FLA  
7.6  
1.3† 0.97  
2.4† 1.79 11.0  
2.4  
2.9  
3.7  
5
5
5
5
5
3.8  
3.8  
3.8  
3.8  
3.8  
3.8 10.4 22.5  
3.8 10.4 26.8  
3.8 10.4 19.5  
3.8 10.4 22.4  
3.8 10.4 25.8  
25  
35  
20  
25  
30  
208-3-60  
1.79  
2.16  
5.2  
7.5  
2.76 10.2  
1.3† 0.97  
7.6  
5
5
5
5
5
5.0  
5.0  
5.0  
5.0  
5.0  
5.0 12.0 24.5  
5.0 12.0 28.8  
5.0 12.0 21.5  
5.0 12.0 24.4  
5.0 12.0 27.8  
25  
35  
25  
25  
30  
2.4† 1.79 11.0  
240-3-60  
2.4  
2.9  
3.7  
1.79  
2.16  
2.76 10.2  
5.2  
7.5  
2.4  
2.9  
3.7  
1.0  
2.0  
3.0  
1.79  
2.16  
2.76  
0.75  
1.49  
2.24  
2.6  
3.4  
4.8  
1.4  
2.3  
3.8  
5
5
5
5
5
5
5.0  
5.0  
5.0  
5.0  
5.0  
5.0  
5.0 6.00 10.8  
5.0 6.00 11.8  
5.0 6.00 13.5  
15  
15  
15  
15  
15  
15  
CAELHEAT002A00  
CAELHEAT003A00  
480-3-60  
575-3-60  
5.0 5.00  
5.0 5.00  
8.0  
9.2  
5.0 5.00 11.0  
1.3† 0.97  
7.6  
10  
10  
10  
10  
10  
7.5  
7.5  
7.5  
7.5  
7.5  
7.5 20.8 35.6  
7.5 20.8 39.8  
7.5 20.8 32.6  
7.5 20.8 35.4  
7.5 20.8 38.8  
40  
40  
35  
40  
40  
2.4† 1.79 11.0  
208-3-60  
240-3-60  
2.4  
2.9  
3.7  
1.79  
2.16  
2.76 10.2  
5.2  
7.5  
CAELHEAT004A00  
1.3† 0.97  
7.6  
10  
10  
10  
10  
10  
10.0  
10.0  
10.0  
10.0  
10.0  
10.0 24.1 39.6  
10.0 24.1 43.8  
10.0 24.1 36.6  
10.0 24.1 39.4  
10.0 24.1 42.8  
40  
50  
40  
40  
50  
2.4† 1.79 11.0  
524A-B072-120  
524A-C072-120  
2.4  
2.9  
3.7  
1.79  
2.16  
2.76 10.2  
5.2  
7.5  
2.4  
2.9  
3.7  
1.0  
2.0  
3.0  
1.79  
2.16  
2.76  
0.75  
1.49  
2.24  
2.6  
3.4  
4.8  
1.4  
2.3  
3.8  
10  
10  
10  
10  
10  
10  
10.0  
10.0  
10.0  
10.0  
10.0  
10.0  
10.0 12.0 18.3  
10.0 12.0 19.3  
10.0 12.0 21.0  
10.0 10.0 14.3  
10.0 10.0 15.4  
10.0 10.0 17.3  
20  
20  
25  
15  
20  
20  
CAELHEAT005A00  
CAELHEAT006A00  
480-3-60  
575-3-60  
1.3† 0.97  
7.6  
15  
15  
15  
15  
15  
11.3  
11.3  
11.3  
11.3  
11.3  
11.3 31.3 48.6  
11.3 31.3 52.9  
11.3 31.3 45.6  
11.3 31.3 48.5  
11.3 31.3 51.9  
50  
60  
50  
50  
60  
2.4† 1.79 11.0  
208-3-60  
240-3-60  
2.4  
2.9  
3.7  
1.79  
2.16  
2.76 10.2  
5.2  
7.5  
CAELHEAT007A00  
1.3† 0.97  
7.6  
15  
15  
15  
15  
15  
15.0  
15.0  
15.0  
15.0  
15.0  
15.0 36.1 54.6  
15.0 36.1 58.9  
15.0 36.1 51.6  
15.0 36.1 54.5  
15.0 36.1 57.9  
60  
60  
60  
60  
60  
2.4† 1.79 11.0  
2.4  
2.9  
3.7  
1.79  
2.16  
2.76 10.2  
5.2  
7.5  
2.4  
2.9  
3.7  
1.0  
2.0  
3.0  
1.79  
2.16  
2.76  
0.75  
1.49  
2.24  
2.6  
3.4  
4.8  
1.4  
2.3  
3.8  
15  
15  
15  
15  
15  
15  
15.0  
15.0  
15.0  
15.0  
15.0  
15.0  
15.0 18.0 25.8  
15.0 18.0 26.8  
15.0 18.0 28.6  
15.0 15.1 20.6  
15.0 15.1 21.7  
15.0 15.1 23.6  
30  
30  
30  
25  
25  
25  
CAELHEAT008A00  
CAELHEAT009A00  
480-3-60  
575-3-60  
See Legend and Notes on page 75.  
74  
ELECTRICAL DATA (cont)  
ELECTRIC HEATER DATA (cont)  
ELECTRIC HEATER(S)  
FAN MOTOR  
Hp kW FLA  
HEATER PART NO.  
CAELHEAT010A00  
UNIT  
V-PH-Hz  
Actual Capacity (kW)  
MCA* MOCP*  
Nominal  
FLA  
Capacity (kW)  
Stage 1 Stage 2 Total  
1.3† 0.97  
7.6  
25  
25  
25  
25  
25  
25  
25  
25  
25  
25  
11.3  
11.3  
11.3  
11.3  
11.3  
15.0  
15.0  
15.0  
15.0  
15.0  
7.5  
7.5  
7.5  
7.5  
7.5  
10.0  
10.0  
10.0  
10.0  
10.0  
18.8 52.1  
18.8 52.1  
18.8 52.1  
18.8 52.1  
18.8 52.1  
25.0 60.1  
25.0 60.1  
25.0 60.1  
25.0 60.1  
25.0 60.1  
74.7  
78.9  
71.7  
74.5  
77.9  
80  
80  
80  
80  
80  
2.4† 1.79 11.0  
208-3-60  
2.4  
2.9  
3.7  
1.79  
2.16  
2.76 10.2  
5.2  
7.5  
1.3† 0.97  
2.4† 1.79 11.0  
7.6  
84.7  
88.9  
81.7  
84.6  
87.9  
90  
90  
90  
90  
90  
240-3-60  
2.4  
2.9  
3.7  
1.79  
2.16  
2.76 10.2  
5.2  
7.5  
2.4  
2.9  
3.7  
1.0  
2.0  
3.0  
1.79  
2.16  
2.76  
0.75  
1.49  
2.24  
2.6  
3.4  
4.8  
1.4  
2.3  
3.8  
25  
25  
25  
25  
25  
25  
15.0  
15.0  
15.0  
15.0  
15.0  
15.0  
10.0  
10.0  
10.0  
10.0  
10.0  
10.0  
25.0 30.1  
25.0 30.1  
25.0 30.1  
25.0 25.1  
25.0 25.1  
25.0 25.1  
40.8  
41.8  
43.6  
33.1  
34.3  
36.1  
50  
50  
50  
35  
35  
40  
CAELHEAT011A00  
CAELHEAT012A00  
480-3-60  
575-3-60  
524A-B072-120  
524A-C072-120  
2.4† 1.79 11.0  
35  
35  
35  
35  
15.0  
15.0  
15.0  
15.0  
11.3  
11.3  
11.3  
11.3  
26.3 73.0 105.0  
110  
100  
110  
110  
2.4  
2.9  
3.7  
1.79  
2.16  
5.2  
7.5  
26.3 73.0  
97.7  
208-3-60  
240-3-60  
26.3 73.0 100.6  
26.3 73.0 104.0  
2.76 10.2  
CAELHEAT013A00  
2.4† 1.79 11.0  
35  
35  
35  
35  
20.0  
20.0  
20.0  
20.0  
15.0  
15.0  
15.0  
15.0  
35.0 84.2 119.0  
35.0 84.2 111.7  
35.0 84.2 114.6  
35.0 84.2 118.0  
125  
125  
125  
125  
2.4  
2.9  
3.7  
1.79  
2.16  
5.2  
7.5  
2.76 10.2  
2.4  
2.9  
3.7  
2.0  
3.0  
1.79  
2.16  
2.76  
1.49  
2.24  
2.6  
3.4  
4.8  
2.3  
3.8  
35  
35  
35  
35  
35  
20.0  
20.0  
20.0  
20.0  
20.0  
15.0  
15.0  
15.0  
15.0  
15.0  
35.0 42.1  
35.0 42.1  
35.0 42.1  
35.0 35.1  
35.0 35.1  
55.9  
56.9  
58.6  
46.8  
48.7  
60  
60  
60  
50  
50  
CAELHEAT014A00  
CAELHEAT015A00  
480-3-60  
575-3-60  
LEGEND  
FLA — Full Load Amps  
Hp — Horsepower  
MCA — Minimum Circuit Amps  
MOCP — Maximum Overcurrent Protection (Amps)  
2. The following equation converts kW of heat energy to Btuh:  
kW x 3,412 = Btuh.  
3. Heater contactor coils are 24 v and require 8 va holding current.  
4. Electric heaters are tested and ETL approved at maximum total  
external static pressure of 1.9 in. wg.  
5. MCA and MOCP values apply to both standard and alternate fac-  
tory-supplied motors.  
6. Approximate shipping weight for CAELHEAT001A00-015A00 is  
55 lb each, CAELHEAT016A00-027A00 is 60 lb each, and  
CAELHEAT028A00-039A00 is 75 lb each.  
*Values shown are for single-point connection of electric heat acces-  
sory and air handler.  
†Single-phase motors. All other motors are 3-phase.  
NOTES:  
1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To  
determine heater capacity (kW) at unit nameplate multiply the  
240-v, 480-v, or 575-v capacity (kW) by the factor shown in the  
table below for the unit voltage.  
HEATER  
RATING  
VOLTAGE  
ACTUAL HEATER VOLTAGE  
200 208 230 240 400 440 460 480 550 575 600  
240  
480  
575  
0.694 0.751 0.918  
1
1
1
0.694 0.84 0.918  
0.915  
1.089  
75  
ELECTRICAL DATA (cont)  
ELECTRIC HEATER DATA (cont)  
ELECTRIC HEATER(S)  
FAN MOTOR  
HEATER PART NO.  
CAELHEAT016A00  
UNIT  
V-PH-Hz  
Actual Capacity (kW)  
MCA*  
MOCP*  
Nominal  
FLA  
Capacity (kW)  
Hp kW  
2.9 2.16  
FLA  
7.5  
Stage 1 Stage 2 Total  
10  
10  
10  
10  
7.5  
7.5  
7.5  
7.5  
7.5 20.8  
7.5 20.8  
7.5 20.8  
7.5 20.8  
35.4  
38.8  
41.3  
52.9  
39.4  
42.8  
46.1  
54.4  
40  
40  
50  
60  
40  
50  
50  
60  
3.7 2.76 10.2  
5.0 3.73 14.6  
7.5 5.59 21.5  
208-3-60  
2.9 2.16  
7.5  
10  
10  
10  
10  
10.0  
10.0  
10.0  
10.0  
10.0 24.1  
10.0 24.1  
10.0 24.1  
10.0 24.1  
3.7 2.76 10.2  
5.0 3.73 12.8  
7.5 5.59 19.4  
240-3-60  
2.9 2.16  
3.7 2.76  
5.0 3.73  
7.5 5.59  
3.0 2.24  
5.0 3.73  
7.5 5.59  
3.4  
4.8  
6.4  
9.7  
3.8  
5.1  
7.8  
10  
10  
10  
10  
10  
10  
10  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
30  
30  
30  
30  
30  
30  
30  
30  
10.0  
10.0  
10.0  
10.0  
10.0  
10.0  
10.0  
14.9  
14.9  
14.9  
14.9  
19.9  
19.9  
19.9  
19.9  
20.0  
20.0  
20.0  
20.0  
20.0  
20.0  
20.0  
15.0  
15.0  
15.0  
15.0  
20.0  
20.0  
20.0  
20.0  
7.5  
7.5  
7.5  
7.5  
10.0  
10.0  
10.0  
10.0  
10.0 12.0  
10.0 12.0  
10.0 12.0  
10.0 12.0  
10.0 10.0  
10.0 10.0  
10.0 10.0  
14.9 41.5  
14.9 41.5  
14.9 41.5  
14.9 41.5  
19.9 47.9  
19.9 47.9  
19.9 47.9  
19.9 47.9  
20.0 24.1  
20.0 24.1  
20.0 24.1  
20.0 24.1  
20.0 20.1  
20.0 20.1  
20.0 20.1  
22.5 62.5  
22.5 62.5  
22.5 62.5  
22.5 62.5  
30.0 72.2  
30.0 72.2  
30.0 72.2  
30.0 72.2  
19.3  
21.0  
23.0  
27.2  
17.3  
19.6  
22.1  
51.2  
64.6  
70.1  
78.7  
69.2  
72.6  
75.8  
84.1  
34.3  
36.1  
39.1  
43.2  
29.9  
31.5  
34.9  
20  
25  
25  
30  
20  
20  
25  
70  
70  
80  
80  
70  
80  
80  
80  
35  
40  
40  
50  
30  
35  
35  
90  
100  
100  
110  
100  
110  
110  
125  
CAELHEAT017A00  
CAELHEAT018A00  
480-3-60  
575-3-60  
208-3-60  
2.9 2.16  
7.5  
3.7 2.76 10.2  
5.0 3.73 14.6  
7.5 5.59 21.5  
CAELHEAT019A00  
2.9 2.16  
7.5  
3.7 2.76 10.2  
5.0 3.73 12.8  
7.5 5.59 19.4  
240-3-60  
524A-B150-240  
524A-C150-240  
2.9 2.16  
3.7 2.76  
5.0 3.73  
7.5 5.59  
3.0 2.24  
5.0 3.73  
7.5 5.59  
3.4  
4.8  
6.4  
9.7  
3.8  
5.1  
7.8  
CAELHEAT020A00  
CAELHEAT021A00  
480-3-60  
575-3-60  
208-3-60  
2.9 2.16  
7.5  
87.5  
90.9  
3.7 2.76 10.2  
5.0 3.73 14.6  
7.5 5.59 21.5  
96.4  
105.0  
CAELHEAT022A00  
2.9 2.16  
7.5  
99.6  
103.0  
106.2  
114.5  
3.7 2.76 10.2  
5.0 3.73 12.8  
7.5 5.59 19.4  
240-3-60  
2.9 2.16  
3.7 2.76  
5.0 3.73  
7.5 5.59  
3.0 2.24  
5.0 3.73  
7.5 5.59  
3.4  
4.8  
6.4  
9.7  
3.8  
5.1  
7.8  
30  
30  
30  
30  
30  
30  
30  
20.0  
20.0  
20.0  
20.0  
20.0  
20.0  
20.0  
10.0  
10.0  
10.0  
10.0  
10.0  
10.0  
10.0  
30.0 36.1  
30.0 36.1  
30.0 36.1  
30.0 36.1  
30.0 30.1  
30.0 30.1  
30.0 30.1  
49.4  
51.1  
53.1  
57.2  
42.4  
44.0  
47.4  
50  
60  
60  
60  
50  
50  
50  
CAELHEAT023A00  
CAELHEAT024A00  
480-3-60  
575-3-60  
See Legend and Notes on page 77.  
76  
ELECTRICAL DATA (cont)  
ELECTRIC HEATER DATA (cont)  
ELECTRIC HEATER(S)  
FAN MOTOR  
HEATER PART NO.  
CAELHEAT025A00  
UNIT  
V-PH-Hz  
Actual Capacity (kW)  
FLA MCA* MOCP*  
Nominal  
Capacity (kW)  
Hp  
kW FLA  
Stage 1 Stage 2 Total  
3.7 2.76 10.2  
5.0 3.73 14.6  
7.5 5.59 21.5  
3.7 2.76 10.2  
5.0 3.73 12.8  
7.5 5.59 19.4  
50  
50  
50  
50  
50  
50  
50  
50  
50  
50  
50  
50  
22.6  
22.6  
22.6  
30.0  
30.0  
30.0  
30.0  
30.0  
30.0  
30.0  
30.0  
30.0  
15.0  
15.0  
15.0  
20.0  
20.0  
20.0  
20.0  
20.0  
20.0  
20.0  
20.0  
20.0  
37.6 104.3 143.1  
37.6 104.3 148.6  
37.6 104.3 157.2  
150  
150  
175  
208-3-60  
240-3-60  
480-3-60  
575-3-60  
50.0 120.3 163.1  
50.0 120.3 166.4  
50.0 120.3 174.6  
175  
175  
200  
524A-B180,240  
524A-C180,240  
3.7 2.76  
5.0 3.73  
7.5 5.59  
4.8  
6.4  
9.7  
50.0  
50.0  
50.0  
50.0  
50.0  
50.0  
60.1  
60.1  
60.1  
81.2  
83.2  
87.3  
90  
90  
90  
CAELHEAT026A00  
CAELHEAT027A00  
3.0 2.24  
5.0 3.73  
7.5 5.59  
3.8  
5.1  
7.8  
50.2  
50.2  
50.2  
67.5  
69.1  
72.5  
70  
70  
80  
7.5 5.59 19.8  
10.0 7.46 28.2  
7.5 5.59 19.4  
10.0 7.46 26.8  
20  
20  
20  
20  
20  
20  
20  
20  
40  
40  
40  
40  
40  
40  
40  
40  
14.9  
14.9  
19.9  
19.9  
20.0  
20.0  
20.0  
20.0  
15.0  
15.0  
20.0  
20.0  
20.0  
20.0  
20.0  
20.0  
15.0  
15.0  
20.0  
20.0  
20.0  
20.0  
20.0  
20.0  
14.9  
14.9  
19.9  
19.9  
20.0  
20.0  
20.0  
20.0  
30.0  
30.0  
40.0  
40.0  
40.0  
40.0  
40.0  
40.0  
41.5  
41.5  
47.9  
47.9  
24.1  
24.1  
20.1  
20.1  
83.4  
83.4  
96.2  
96.2  
47.9  
47.9  
40.2  
40.2  
78.7  
87.1  
81.4  
93.3  
42.2  
46.8  
34.9  
38.0  
131.1  
139.5  
144.5  
153.8  
71.9  
76.6  
60.0  
63.1  
80  
208-3-60  
240-3-60  
480-3-60  
575-3-60  
208-3-60  
240-3-60  
480-3-60  
575-3-60  
100  
CAELHEAT028A00  
90  
110  
50  
50  
35  
40  
150  
150  
150  
175  
80  
80  
60  
70  
7.5 5.59  
9.7  
CAELHEAT029A00  
CAELHEAT030A00  
10.0 7.46 13.4  
7.5 5.59  
7.8  
524A-B300  
524A-C300  
10.0 7.46 10.3  
7.5 5.59 19.8  
10.0 7.46 28.0  
7.5 5.59 19.4  
10.0 7.46 26.8  
CAELHEAT031A00  
7.5 5.59  
9.7  
CAELHEAT032A00  
CAELHEAT033A00  
10.0 7.46 13.4  
7.5 5.59 7.8  
10.0 7.46 10.3  
LEGEND  
FLA — Full Load Amps  
Hp — Horsepower  
MCA — Minimum Circuit Amps  
MOCP— Maximum Overcurrent Protection (Amps)  
2. The following equation converts kW of heat energy to Btuh:  
kW x 3,412 = Btuh.  
3. Heater contactor coils are 24 v and require 8 va holding current.  
4. Electric heaters are tested and ETL approved at maximum total  
external static pressure of 1.9 in. wg.  
5. MCA and MOCP values apply to both standard and alternate fac-  
tory-supplied motors.  
6. Approximate shipping weight for CAELHEAT001A00-015A00 is  
55 lb each, CAELHEAT016A00-027A00 is 60 lb each, and  
CAELHEAT028A00-039A00 is 75 lb each.  
*Values shown are for single-point connection of electric heat acces-  
sory and air handler.  
NOTES:  
1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To  
determine heater capacity (kW) at unit nameplate multiply the  
240-v, 480-v, or 575-v capacity (kW) by the factor shown in the  
table below for the unit voltage.  
HEATER  
RATING  
VOLTAGE  
ACTUAL HEATER VOLTAGE  
200 208 230 240 400 440 460 480 550 575 600  
240  
480  
575  
0.694 0.751 0.918  
1
1
0.915  
1
1.089  
0.694 0.84 0.918  
77  
ELECTRICAL DATA (cont)  
ELECTRIC HEATER DATA (cont)  
ELECTRIC HEATER(S)  
FAN MOTOR  
HEATER PART NO.  
CAELHEAT034A00  
UNIT  
V-PH-Hz  
Actual Capacity (kW)  
MCA* MOCP*  
Nominal Capacity (kW)  
FLA  
Hp kW FLA  
Stage 1 Stage 2 Total  
7.5 5.59 19.8  
10.0 7.46 28.0  
7.5 5.59 19.4  
10.0 7.46 26.8  
7.5 5.59 9.7  
10.0 7.46 13.4  
7.5 5.59 7.8  
10.0 7.46 10.3  
7.5 5.59 19.8  
10.0 7.46 28.0  
7.5 5.59 19.4  
10.0 7.46 26.8  
7.5 5.59 9.7  
10.0 7.46 13.4  
7.5 5.59 7.8  
10.0 7.46 10.3  
50  
50  
50  
50  
50  
50  
50  
50  
70  
70  
70  
70  
70  
70  
70  
70  
22.6  
22.6  
30.0  
30.0  
30.0  
30.0  
30.0  
30.0  
30.0  
30.0  
40.0  
40.0  
40.0  
40.0  
40.0  
40.0  
15.0  
15.0  
20.0  
20.0  
20.0  
20.0  
20.0  
20.0  
22.6  
22.6  
30.0  
30.0  
30.0  
30.0  
30.0  
30.0  
37.6 104.3 157.2  
37.6 104.3 165.6  
175  
175  
208-3-60  
240-3-60  
480-3-60  
575-3-60  
208-3-60  
240-3-60  
480-3-60  
575-3-60  
50.0 120.3 174.6  
50.0 120.3 183.9  
200  
200  
50.0  
50.0  
50.0  
50.0  
60.1  
60.1  
50.2  
50.2  
87.3  
91.9  
90  
100  
CAELHEAT035A00  
CAELHEAT036A00  
72.5  
75.6  
80  
80  
524A-B300  
524A-C300  
52.6 145.9 172.8  
52.6 145.9 181.2  
175  
200  
CAELHEAT037A00  
70.0 168.4 192.6  
70.0 168.4 201.9  
200  
225  
70.0  
70.0  
70.0  
70.0  
84.2  
96.3  
84.2 100.9  
100  
110  
CAELHEAT038A00  
CAELHEAT039A00  
70.3  
70.3  
80.0  
83.2  
90  
90  
LEGEND  
FLA — Full Load Amps  
Hp — Horsepower  
MCA — Minimum Circuit Amps  
MOCP — Maximum Overcurrent Protection (Amps)  
2. The following equation converts kW of heat energy to Btuh:  
kW x 3,412 = Btuh.  
3. Heater contactor coils are 24 v and require 8 va holding current.  
4. Electric heaters are tested and ETL approved at maximum total  
external static pressure of 1.9 in. wg.  
5. MCA and MOCP values apply to both standard and alternate fac-  
tory-supplied motors.  
6. Approximate shipping weight for CAELHEAT001A00-015A00 is  
55 lb each, CAELHEAT016A00-027A00 is 60 lb each, and  
CAELHEAT028A00-039A00 is 75 lb each.  
*Values shown are for single-point connection of electric heat acces-  
sory and air handler.  
NOTES:  
1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To  
determine heater capacity (kW) at unit nameplate multiply the  
240-v, 480-v, or 575-v capacity (kW) by the factor shown in the  
table below for the unit voltage.  
HEATER  
RATING  
VOLTAGE  
ACTUAL HEATER VOLTAGE  
200 208 230 240 400 440 460 480 550 575 600  
240  
480  
575  
0.694 0.751 0.918  
1
1
0.915  
1
1.089  
0.694 0.84 0.918  
78  
APPLICATION DATA — 524A  
The air handler fan must always be operating when the con-  
1. OPERATING LIMITS  
densing unit is operating.  
Maximum fan speed — 524A-B,C072-240 . . . . . . . .1200rpm  
Maximum fan speed — 524A-B,C300 . . . 1100 rpm (18.3 r/s)  
Ductwork should be sized according to unit size, not build-  
ing load. For larger units with two fans, a split duct transition  
is recommended at the fan outlets, but a plenum can  
be used with slight reduction in external static pressure  
capability.  
2. GENERAL — Select equipment to match or to be slightly  
less than peak load. This provides better humidity control,  
less unit cycling, and less part-load operation. Equipment  
should be selected to perform at no less than 300 cfm/ton.  
FACTORY-INSTALLED NOZZLE AND DISTRIBUTOR DATA  
FEEDER TUBES  
PER DISTRIBUTOR  
Qty...Size (in.)  
COIL  
TYPE  
TXV  
Qty...Part No.*  
DISTRIBUTOR  
Qty...Part No.†  
NOZZLE  
Qty...Part No.  
UNIT  
524A-B,C 072  
524A-B,C 090  
524A-B,C 120  
524A-B 150  
524A-C 150  
524A-B 180  
524A-C 180  
524A-B 240  
524A-C 240  
524A-B 300  
524A-C 300  
3, 4 Row  
3, 4 Row  
3, 4 Row  
3 Row  
4 Row  
3 Row  
4 Row  
3 Row  
4 Row  
3 Row  
1...TDEBX8  
1...TDEBX8  
2...TDEX6  
1...1116  
1...1126  
2...1115  
2...1115  
2...1115  
2...1116  
2...1126  
2...1116  
2...1126  
2...1126  
2...1126  
12...1/4  
15...1/4  
9...1/4  
1...E5  
1...C6  
2...E4  
2...E5  
2...E5  
2...E6  
2...C6  
2...E8  
2...C8  
2...C10  
2...C15  
2...TDEBX8  
2...TDEBX8  
2...TDEBX8  
2...TDEBX8  
2...TDEBX11  
2...TDEBX11  
2...TDEBX11  
2...TDEBX11  
9...1/4  
12...3/16  
12...1/4  
16...1/4  
13...1/4  
18...3/16  
15...1/4  
20...3/16  
4 Row  
*Danfoss part numbers shown.  
†Sporlan Valve Co. part numbers shown.  
NOTE: Hot gas bypass applications require field-supplied auxiliary side  
connector.  
FAN MOTOR DATA  
STANDARD MOTOR  
UNIT SIZE 524A  
208/230-1-60  
Speed (rpm)  
Hp  
Frame (NEMA)  
Shaft Dia (in.)  
208/230-3-60 and 460-3-60  
Speed (rpm)  
Hp  
072  
090  
120  
150  
180  
240  
300  
1725  
1.3  
56Y  
1725  
2.4  
56Y  
5
5
/
/
8
8
1725  
2.4  
1725  
2.4  
1725  
2.4  
1725  
2.9  
1725  
3.7  
1745  
5.0  
1745  
7.5  
Frame (NEMA)  
Shaft Dia (in.)  
575-3-60  
56Y  
56Y  
56Y  
56Y  
56Y  
S184T  
11/8  
S213T  
13/8  
5
5
5
7
7
/
/
8
/
8
/
/
8
8
8
Speed (rpm)  
Hp  
1725  
1.0  
1725  
2.0  
1725  
2.0  
1725  
3.0  
1725  
3.0  
1745  
5.0  
1755  
7.5  
Frame (NEMA)  
Shaft Dia (in.)  
56  
56HZ  
56HZ  
56HZ  
56HZ  
184T  
11/8  
S213T  
13/8  
5
7
7
7
7
/
/
8
/
8
/
/
8
8
8
LEGEND  
NEMA — National Electrical Manufacturers Association  
79  
APPLICATION DATA — 524A (cont)  
FAN MOTOR DATA (cont)  
ALTERNATE MOTOR  
UNIT SIZE 524A  
208/230-1-60  
072  
090  
120  
150  
180  
240  
300  
Speed (rpm)  
Hp  
1725  
2.4  
56Y  
1725  
2.4  
56Y  
Frame (NEMA)  
Shaft Dia (in.)  
230-3-60 and 460-3-60  
Speed (rpm)  
Hp  
5
5
/
/
8
8
1725  
2.9  
1725  
2.9  
1725  
3.7  
1725  
3.7  
1725  
5.0  
1745  
7.5  
1745  
10.0  
Frame (NEMA)  
Shaft Dia (in.)  
575-3-60  
56Y  
56Y  
Y56Y  
Y56Y  
S184T  
11/8  
S213T  
13/8  
S215T  
13/8  
7
7
7
7
/
/
/
8
/
8
8
8
Speed (rpm)  
Hp  
1725  
2.0  
1725  
3.0  
1725  
3.0  
1745  
5.0  
1745  
5.0  
1755  
7.5  
1750  
10.0  
Frame (NEMA)  
Shaft Dia (in.)  
56HZ  
56HZ  
56HZ  
184T  
11/8  
184T  
11/8  
S213T  
13/8  
D215T  
13/8  
7
7
7
/
/
/
8
8
8
LEGEND  
NEMA — National Electrical Manufacturers Association  
STANDARD DRIVE DATA  
UNIT SIZE 524A  
072  
090  
120  
150  
180  
240  
300  
MOTOR DRIVE  
Motor Pulley Pitch Diameter (in.)  
Pulley Factory Setting  
Full Turns Open  
2.4-3.4  
2.5  
2.8-3.8  
2.5  
3.4-4.4  
2.5  
2.8-3.8  
2.5  
2.8-3.8  
2.5  
3.7-4.7  
3.0  
4.3-5.3  
3.0  
FAN DRIVE  
Pulley Pitch Dia (in.)  
Pulley Bore (in.)  
Belt No. — Section  
8.8  
1
1—A  
8.8  
1
1—A  
8.8  
1
1—A  
9.0  
17/16  
1—A  
9.0  
17/16  
1—A  
9.4  
17/16  
1—B  
11.0  
115  
/
16  
2—B*  
(2) 42.8  
(2) 43.8  
Belt Pitch (in.)  
40.3  
41.3  
42.3  
42.3  
632  
537-728  
1200  
42.3  
41.8  
FAN SPEEDS (rpm)  
Factory Settings  
Range  
568  
470-666  
1200  
647  
549-745  
1200  
764  
666-863  
1200  
632  
537-728  
1200  
771  
679-863  
1200  
752  
682-841  
1100  
Max Allowable Speed (rpm)  
Change per 1/2 turn of  
Moveable Motor Pulley  
Flange  
19.6  
19.6  
19.7  
19.1  
19.1  
15.3  
13.1  
MAX FULL TURNS FROM  
CLOSED POSITION  
5
5
5
5
5
6
6
10.44-  
12.32  
10.44-  
12.32  
10.44-  
12.32  
10.44-  
12.32  
10.44-  
12.32  
9.12-  
10.99  
6.67-  
9.43  
SHAFTS CENTER DISTANCE (in.)  
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.  
80  
APPLICATION DATA — 524A (cont)  
MEDIUM-STATIC DRIVE DATA  
UNIT SIZE 524A  
072  
090  
120  
150  
180  
240  
300  
MOTOR DRIVE  
Motor Pulley Pitch Diameter (in.)  
Pulley Factory Setting  
Full Turns Open  
3.4-4.4  
2.5  
3.4-4.4  
2.5  
3.4-4.4  
2.5  
3.4-4.4  
2.5  
3.7-4.7  
3.0  
4.3-5.3  
3.0  
4.3-5.3  
3.0  
FAN DRIVE  
Pulley Pitch Dia (in.)  
Pulley Bore (in.)  
Belt No. — Section  
8.8  
1
1—A  
8.0  
1
1—A  
8.0  
1
1—A  
8.2  
17/16  
1—A  
8.6  
17/16  
1—B  
9.4  
17/16  
2—B  
9.4  
115  
/
16  
2—B*  
(2) 38.8  
(2) 39.8  
Belt Pitch (in.)  
42.3  
40.3  
40.3  
41.3  
41.8  
41.8  
FAN SPEEDS (rpm)  
Factory Setting  
Range  
764  
666-863  
1200  
841  
733-949  
1200  
841  
733-949  
1200  
820  
715-926  
1200  
842  
742-943  
1200  
881  
798-984  
1200  
881  
798-984  
1100  
Max Allowable Speed (rpm)  
Change per 1/2 Turn of  
Moveable Motor Pulley  
Flange  
19.7  
21.6  
21.6  
21.1  
16.7  
15.3  
15.3  
MAX FULL TURNS FROM  
CLOSED POSITION  
5
5
5
5
6
6
6
10.44-  
12.32  
10.44-  
12.32  
10.44-  
12.32  
10.44-  
12.32  
10.44-  
12.32  
9.16-  
10.99  
6.67-  
9.43  
SHAFTS CENTER DISTANCE (in.)  
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.  
HIGH-STATIC DRIVE DATA  
UNIT SIZE 524A  
MOTOR DRIVE  
072  
090  
120  
150  
180  
240  
300  
Motor Pulley Pitch Diameter (in.)  
Pulley Factory Setting  
Full Turns Open  
3.4-4.4  
2.5  
3.4-4.4  
2.5  
3.4-4.4  
2.5  
3.7-4.7  
3.0  
4.3-5.3  
3.0  
4.3-5.3  
3.0  
4.3-5.3  
3.0  
FAN DRIVE  
Pulley Pitch Dia (in.)  
Pulley Bore (in.)  
Belt No. — Section  
Belt Pitch (in.)  
7.0  
1
1—A  
41.3  
6.0*  
1
1—A  
37.3  
6.0  
1
1—A  
37.3  
7.4  
7.9  
7.4  
8.6  
17/16  
1—B  
39.8  
17/16  
1—B  
39.8  
17/16  
2—B  
36.8  
115  
/
16  
2—B  
37.8  
FAN SPEEDS (rpm)  
Factory Setting  
961  
1121  
1121  
979  
1060  
1118  
1024  
838-  
1084  
978-  
1200*†  
978-  
1200†  
873-  
1096  
950-  
1171  
1014-  
1200†  
873-  
1075  
Range  
Max Allowable Speed (rpm)  
1200  
24.6  
1200  
28.7  
1200  
28.7  
1200  
19.4  
1200  
18.4  
1200  
1100  
16.7  
Change per 1/2 Turn of  
Moveable Motor Pulley  
Flange  
19.4  
MAX FULL TURNS FROM  
CLOSED POSITION  
5
5
5
6
6
6
6
10.44-  
12.32  
10.44-  
12.32  
10.44-  
12.32  
10.44-  
12.32**  
9.16-  
10.99  
8.16-  
10.02  
6.67-  
9.43  
SHAFTS CENTER DISTANCE (in.)  
*Values for 3-phase motor shown. For single-phase motor, pulley pitch diameter is 7 in.  
and resulting fan speed is 837-1096 rpm.  
†It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT  
exceed 1200 rpm.  
**575-v unit has a center distance of 9.16-10.99.  
81  
GUIDE SPECIFICATIONS — 524A  
COMMERCIAL PACKAGED AIR-HANDLING UNIT  
HVAC GUIDE SPECIFICATIONS  
4. Unit shall have factory-supplied 2-in. throwaway-type  
filters installed upstream from the cooling coil. Filter  
access shall be from either the right or left side of the  
unit.  
SIZE RANGE: 1,800 to 12,500 CFM, NOMINAL AIRFLOW 6 TO  
25 TONS, NOMINAL COOLING  
B. Coils:  
BRYANT MODEL NUMBERS: 524A-B (DIRECT-EXPANSION  
COIL), 524A-C (HIGH-CAPACITY 4-ROW DIRECT-EXPANSION  
COIL)  
Coils shall consist of 3 rows (524A-B) or 4 rows (524A-C)  
of copper tubes with sine-wave aluminum fins bonded to  
the tubes by mechanical expansion. Suction and liquid  
line connections or supply and discharge connections  
shall be made on the same side of the coil.  
PART 1 — GENERAL  
1.01 SYSTEM DESCRIPTION  
A. Indoor, packaged air-handling unit for use in commercial  
split systems. Unit shall have a multiposition design and  
shall be capable of horizontal or vertical installation on a  
floor or in a ceiling, with or without ductwork. (Only verti-  
cal units are to be applied without ductwork.)  
1. Direct-expansion coils shall feature factory-installed  
thermostatic expansion valves (TXVs) for refrigerant  
control. The TXVs shall be capable of external  
adjustment. Coil tubing shall be internally rifled to  
maximize heat transfer.  
B. Unit with direct-expansion coil shall be used in a refriger-  
ant circuit with a matching air-cooled condensing unit.  
2. High-Capacity Coil:  
The high-capacity 4-row coil consists of 4 rows of  
3/8-in. copper tubes with sine-wave aluminum fins  
bonded to the tubes by mechanical expansion. Coil  
tubing shall be internally rifled to maximize heat  
transfer. Suction and liquid line connections shall be  
made on the same side of the coil. Direct-expansion  
coils shall feature factory-installed thermostatic  
expansion valves (TXVs) for refrigerant control. The  
TXVs shall be capable of external adjustment.  
1.02 QUALITY ASSURANCE  
A. Coils shall be designed and tested in accordance with  
ASHRAE 15 Safety Code for Mechanical Refrigeration,  
latest edition.  
B. Unit shall be constructed in accordance with ETL and  
ETL, Canada, standards and shall carry the ETL and  
ETL, Canada, labels.  
C. Unit insulation and adhesive shall comply with NFPA-90A  
requirements for flame spread and smoke generation.  
Insulation shall contain an EPA-registered immobilized  
antimicrobial agent to effectively resist the growth of  
bacteria and fungi as proven by tests in accordance with  
ASTM standards G21 and 22.  
C. Operating Characteristics:  
Unit shall be capable of providing  
external static pressure of  
cfm airflow at an  
in. wg.  
D. Motor:  
Fan motor of the size and electrical characteristics speci-  
fied on the equipment schedule shall be factory supplied  
and installed.  
D. Unit shall be manufactured in a facility registered to the  
ISO 9001:2000 manufacturing quality standard.  
E. Direct-expansion coils shall be burst and leak tested at  
435 psi.  
Motors rated at 1.3 through 3.7 hp shall have internal  
thermal overload protection. Motors rated at 5, 71/2, and  
10 hp shall be protected by a circuit breaker.  
1.03 DELIVERY AND STORAGE  
Units shall be stored and handled per manufacturer’s  
recommendations.  
E. Special Features:  
1. Alternate Motor and Drive:  
PART 2 — PRODUCTS  
2.01 EQUIPMENT  
An alternate motor and/or medium-static or high-  
static drive shall be available to meet the airflow and  
external static pressure requirements specified on  
the equipment schedule.  
Indoor mounted, draw-thru, packaged air-handling unit  
that can be used in a suspended horizontal configuration  
or a vertical configuration. Unit shall consist of forward-  
curved belt-driven centrifugal fan(s), motor and drive  
assembly, prewired fan motor contactor, factory-installed  
refrigerant metering devices (direct-expansion coil units),  
cooling coil, 2-in. disposable air filters, and condensate  
drain pans for vertical or horizontal configurations.  
2. External Paint:  
Where conditions require, units shall be painted with  
an American Sterling Gray finish.  
3. Hot Water Coil:  
Coil shall be 2-row, U-bend coil with copper tubes  
and aluminum plate fins bonded to the tubes by  
mechanical expansion. Coil shall be mounted in a  
galvanized steel housing that shall be fastened to the  
unit’s fan deck for blow-thru heating operation. Coil  
shall have maximum working pressure of 150 psig.  
A. Base Unit:  
1. Cabinet shall be constructed of mill-galvanized steel.  
2. Cabinet panels shall be fully insulated with 1/2-in.  
fire-retardant material. Insulation shall contain an  
EPA-registered immobilized antimicrobial agent to  
effectively resist the growth of bacteria and fungi as  
proven by tests in accordance with ASTM standards  
G21 and 22.  
4. Steam Distributing Coil:  
Coil shall consist of one row of copper tubes with  
aluminum plate fins, and shall have inner steam dis-  
tributing tubes. Coil shall be mounted in a galvanized  
steel housing and shall be fastened to the unit’s fan  
deck for blow-thru heating operation. Coil shall have  
maximum working pressure of 20 psig at 260 F.  
3. Unit shall contain non-corroding condensate drain  
pans for both vertical and horizontal applications.  
Drain pans shall have connections on right and left  
sides of unit to facilitate field connection. Drain pans  
shall have the ability to be sloped toward the right or  
left side of the unit to prevent standing water from  
accumulating in pans.  
82  
GUIDE SPECIFICATIONS — 524A (cont)  
5. Electric Heaters:  
11. Overhead Suspension Package:  
Heaters for nominal 240, 480, or 575-volt, 3-phase,  
60 Hz power supply shall be factory-supplied for field  
installation as shown on the equipment drawings.  
Electric heat assembly shall be ETL and ETL, Can-  
ada, agency approved, and shall have single-point  
power wiring. Heater assembly shall include contac-  
tors with 24-v coils, power wiring, 24-v control wiring  
terminal blocks, and a hinged access panel. Electric  
heaters shall not be used with air discharge plenum.  
Package shall include necessary brackets to support  
units in a horizontal ceiling installation.  
12. Condensate Drain Trap:  
Trap shall have transparent, serviceable design for  
easy cleaning. Kit shall include overflow shutoff  
switch and wiring harness for connection to an alarm  
if desired.  
13. UV-C Germicidal Lamps:  
UV-C emitters and fixtures shall be specifically  
designed for use inside an HVAC system. An ASME  
nozzled test apparatus using a 45 F airstream mov-  
ing at not less than 400 fpm shall measure individual  
lamp output. Lamp output at 253.7 nm shall not be  
less than 10µW/cm2 per inch of arc length measured  
at a distance of one meter.  
6. Air Discharge Plenum:  
Plenum shall be factory supplied to provide free-blow  
air distribution for vertical floor-mounted units. A  
grille with moveable vanes for horizontal or vertical  
airflow adjustment shall be included. Plenum shall  
be field-assembled and field-installed on the unit’s  
fan deck for blow-thru air distribution. Plenum shall  
not be used with electric heaters.  
a. UV-C power supplies shall be high efficiency,  
electric type which are matched to the emitters  
and are capable of producing the specified output  
intensity with an input power no more than  
80 watts.  
7. Return-Air Grille:  
Grille shall be factory supplied for field installation on  
the unit’s return air opening.  
8. Unit Subbase:  
b. Emitters and fixtures shall be installed in sufficient  
quantity and arranged so as to provide an equal  
distribution of UV-C energy on the coil and drain  
fan.  
Subbase assembly shall be factory supplied for field  
installation. Subbase shall elevate floor-mounted  
vertical units to provide access for correct conden-  
sate drain connection.  
c. The minimum UV-C energy striking the leading  
edge of the coil fins shall be not less than  
820 µW/cm2 at the closest point and through  
placement, not less than 60% of that value at the  
farthest point. Equal amounts are to strike the  
drain pan, either directly or indirectly through  
reflection.  
9. Economizer:  
Economizer for ventilation or “free” cooling shall be  
factory provided for field installation on either return  
air opening of air handler. For free cooling applica-  
tions, economizer shall be compatible with separate  
thermostat; economizer dampers shall open when  
outdoor air enthalpy is suitable for free cooling.  
Economizer shall include enthalpy control and  
damper actuator. Economizer shall be compatible  
with accessory CO2 sensor. Economizer damper  
shall open when indoor CO2 level rises above prede-  
termined set point.  
d. Emitters and fixtures shall be installed at right  
angles to the conforming lines of the coil fins,  
such that through incident angle reflection, UV-C  
energy strikes all target surfaces of the coil, drain  
pan, and the available line of sight airstream.  
14. CO2 Sensor:  
A 2 to 10 vdc actuator adapter must be field-supplied  
and installed on economizer for demand control ven-  
tilation using the CO2 sensor accessory.  
The field-installed CO2 ventilation sensor measures  
the amount of ventilation needed by the space and a  
proportional integral derivative loop (PID) calculation  
makes adjustments to the economizer minimum  
position during occupied operation. The indoor CO2  
will be compared to an outdoor CO2 reference before  
making adjustments to the economizer minimum  
position.  
10. Thermostat Controls:  
a. Commercial Electronic Thermostat with 7-day  
timeclock, auto-changeover, multi-stage capabil-  
ity, and large LCD temperature display.  
b. Commercial Electronic Non-programmable Ther-  
mostat with auto-changeover, multi-stage capac-  
ity, and large LCD display.  
83  
INDEX  
Motormaster® options  
569D/F072-120, 576C120 11-32  
566D/E150-240 33-60  
4
Operating sequence  
8
524A072-300 61-83  
Options and accessories 4-6  
Alternate motors and drives 5, 73, 80, 81  
Application data  
569D/F, 576C, 566D/E  
524A 5, 6  
4
569D/F072-120, 576C120 27  
566D/E150-240 54-56  
Performance data  
569D/F072-120, 576C120 15-25  
566D/F150-240 39-52  
524A072-300 66-71  
524A072-300 79-81  
ARI capacity ratings  
CO2 sensor 83  
3
Physical data  
Combination ratings  
569D/F072-120, 576C120 12  
566D/E150-240 34, 35  
524A072-300 62  
566D150-240/524A 40-44  
566E150-240/524A 45-52  
569D072-120/524A 16-21  
569F120/524A 24, 25  
576C/524A 22, 23  
Piping and wiring  
569D072-120, 576C120 28  
566D150-240 57, 58  
Refrigerant charge 27  
Refrigerant piping 27, 54, 55  
Return-air grille 5, 6  
Condenser coil grille  
Condensing unit ratings 15, 39  
Controls  
4
8
Convenience outlet  
Dimensions  
4
Selection procedure  
Sound data  
7
3
Base unit  
569D/F072-120, 576C120 13, 14  
Static pressure drop  
Filter 70  
566D/E150-240 36-38  
Economizer  
70  
524A072-300 63-65  
Discharge plenum 5, 6  
Heating coil 70  
Plenum 70  
Dura-Shield options  
E-coated coils  
Economizer 5, 6  
4
Steam coil 5, 6, 71  
Subbase 5, 6  
Thermostat 4, 5  
4
Electrical data  
Thermostatic expansion  
569D/F072-120, 576C120 26  
566D/E150-240 53  
valve (TXV) 79  
Unloader package  
4
524A072-300 72-78  
Electric heat 5, 74-78  
Fan performance tables  
524A072-300 66-69  
Features/Benefits 1, 2  
Unit-mounted non-fused disconnect  
4
UV-C germicidal lamps  
5
Wiring 9, 10  
Gage panel  
4
Guide specifications  
569D072-120, 576C120 29, 30  
569F120  
31, 32  
566D/E150-240 59, 60  
524A072-300 82, 83  
Hail guard  
4
Hot water coil 5, 6, 71  
Hydronic heat 71  
Indoor-air quality (IAQ)  
Liquid line piping 27, 55  
1
Low ambient controls  
4
Maximum temperature 27, 54  
Minimum ambient operating  
temperature 27, 54  
Minimum temperature 27, 54  
Model number nomenclature  
569D/E072-120, 576C120 11  
566D/E150-240 33  
524A072-300 61  
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE  
UNIT MUST BE INSTALLED IN ACCORDANCE  
WITH INSTALLATION INSTRUCTIONS  
Copyright 2004 Bryant Heating & Cooling Systems  
Printed in U.S.A.  
7/04  
Catalog No. 5256-904  

Bowens EXPLORER 1500 User Manual
Briggs Stratton 421400 User Manual
Brother MFC 5890CN User Manual
Carrier 50EE User Manual
Central Hydraulics Automobile Accessories 3 ton floor hack User Manual
Crown Audio ADDENDUM 28M User Manual
Dakota Digital 3X User Manual
Friedrich CP15F10A User Manual
Heat Controller Inc Air Conditioner HMG__F1E User Manual
HP Hewlett Packard CHASSIS PARTS 1150Cse User Manual