Honeywell Video Gaming Accessories W7750A User Manual

Excel 10  
W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
SYSTEM ENGINEERING  
Contents  
LONMARK® Functional Profile ..................................................................... 17  
LONWORKS® Bus Layout ................................................................................ 30  
® U.S. Registered Trademark  
Copyright © 2000 Honeywell Inc. • All Rights Reserved  
74-2958-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
List of Figures  
Fig. 1. Typical system overview. ................................................................................................................................................  
Fig. 2. Typical W7750 control application. .................................................................................................................................  
6
7
Fig. 3. Excel 10 W7750A Constant Volume AHU Controller. ..................................................................................................... 12  
Fig. 4. W7750A construction in in. (mm). ................................................................................................................................... 13  
Fig. 5. Excel 10 W7750B Constant Volume AHU Controller. ..................................................................................................... 14  
Fig. 6. Excel 10 W7750C Constant Volume AHU Controller. .................................................................................................... 15  
Fig. 7. W7750B,C construction in in. (mm). W7750C (shown) has three 4 to 20 mA analog outputs.) ..................................... 16  
Fig. 8. DIN rail adapters. ............................................................................................................................................................ 17  
Fig. 9. Functional profile of LONMARK® RTU object details (variables not implemented in Excel 10 CVAHU  
are greyed)........................................................................................................................................................................ 18  
Fig. 10. T7770A,B,C,D construction in in. (mm). ....................................................................................................................... 20  
Fig. 11. T7560A,B construction in in. (mm). ............................................................................................................................... 21  
Fig. 12. C7770A construction in in. (mm). .................................................................................................................................. 21  
Fig. 13. Fan with two stages of heating and two stages  
of cooling........................................................................................................................................................................... 24  
Fig. 14. Fan, modulating heating and modulating cooling. ......................................................................................................... 24  
Fig. 15. Heat pump with two compressors and auxiliary heat stage(s)....................................................................................... 25  
Fig. 16. Economizer control. ...................................................................................................................................................... 25  
Fig. 17. Modulating heat with pneumatic valve actuator............................................................................................................. 26  
Fig. 18. Connecting the portable operator terminal  
to the LONWORKS® Bus..................................................................................................................................................... 29  
Fig. 19. Wiring layout for one doubly terminated daisy-chain LONWORKS® Bus segment. ........................................................ 31  
Fig. 20. Wiring layout for two singly terminated LONWORKS® Bus segments............................................................................. 32  
Fig. 21. NEMA class 2 transformer voltage output limits............................................................................................................ 34  
Fig. 22. Power wiring details for one Excel 10 per transformer. ................................................................................................. 34  
Fig. 23. Power wiring details for two or more Excel 10s per transformer. .................................................................................. 34  
Fig. 24. Transformer power wiring details for one Excel 10 used in UL 1995 equipment (U.S. only)......................................... 35  
Fig. 25. Attaching two or more wires at terminal blocks.............................................................................................................. 36  
Fig. 27. Typical W7750A Controller AHU application wiring diagram. (For more information on note 2,  
refer to Fig. 25.)................................................................................................................................................................ 38  
Fig. 28. Typical W7750A Controller with separate transformer application wiring diagram.  
(For more information on note 2, refer to Fig. 25.) ............................................................................................................ 38  
Fig. 29. W7750A Controller floating economizer damper wiring diagram. (For more information on note 2, refer to Fig. 25.)... 39  
Fig. 30. Typical W7750B Controller with staged heating and cooling wiring diagram. (For more information on note 2, refer to Fig.  
25.).................................................................................................................................................................................... 40  
Fig. 31. W7750B Controller with floating heating, cooling and economizer wiring diagram. (For more information on note 2, refer  
to Fig. 25.)......................................................................................................................................................................... 40  
Fig. 32. W7750B,C Controller PWM damper actuator wiring diagram. (For more information on note 2, refer to  
Fig. 25.)............................................................................................................................................................................. 41  
Fig. 33. W7750B,C wiring diagram with 4 to 20 mA enthalpy sensors and digital inputs. (For more information on note 2, refer to  
Fig. 25.)............................................................................................................................................................................. 41  
Fig. 34. W7750B,C wiring diagram with C7600C 4 to 20 mA solid state humidity sensor. (For more information on note 2, refer to  
Fig. 25.)............................................................................................................................................................................. 42  
18. The AOs can be set to be reverse acting. (For more information on note 2, refer to Fig. 25.).................................... 42  
(B shown, see triangle note 4). ......................................................................................................................................... 43  
Fig. 37. RP7517,B pneumatic transducer to W7750C................................................................................................................ 43  
Fig. 38. Typical doubly terminated daisy-chain LONWORKS® Bus segment termination module wiring diagram. ..................... 44  
Fig. 39. LONWORKS® Bus termination wiring options. ............................................................................................................... 45  
Fig. 40. Temperature sensor resistance plots............................................................................................................................. 49  
Fig. 41. Location of the Service Pin Button................................................................................................................................. 50  
Fig. 42. LED location on W7750................................................................................................................................................. 51  
Fig. 43. The T7770C,D Wall Modules LED and Bypass pushbutton locations........................................................................... 51  
Fig. 44. The T7560A,B Digital Wall Module Bypass pushbutton location................................................................................... 51  
3
74-29581  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
74-29581  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
List of Tables  
Table 2. List of Differences in W7750A and W7750B,C Controllers........................................................................................... 11  
Table 3. Common Configuration Options Summary For W7750A,B,C Controllers..................................................................... 22  
Table 7. LONWORKS® Bus Configuration Rules And Device Node Numbers............................................................................. 30  
Table 8. VA Ratings For Transformer Sizing. ............................................................................................................................. 33  
Table 9. Field Wiring Reference Table (Honeywell listed as AK#### or equivalent).................................................................. 36  
Table 14. Common Configuration Options Summary For W7750A,B,C Controllers................................................................... 53  
Table 18. Excel 10 W7750 Controller User  
Table 26. LONMARK®/Open System Points. ............................................................................................................................... 97  
5
74-29581  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excel 10 W7750A,B,C Constant Volume AHU Controller  
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
LONWORKS network (LONWORKS Bus) for communications,  
and conforms with the LONMARK HVAC Interoperability  
standard for Roof Top Unit Controllers (see Fig. 9).  
INTRODUCTION  
Description of Devices  
The T7770 or T7560 direct-wired Wall Modules are used in  
conjunction with W7750 Controllers. The zone controlled by  
the W7750 Controller typically can use a T7770A through D or  
a T7560A,B Wall Module. Additional features available in  
T7770A through D models include analog setpoint input knob,  
override digital input pushbutton, override status LED and  
LONWORKS Bus network access jack. Additional features  
available in T7560A,B models include analog setpoint input  
knob, override digital input pushbutton, humidity sensor  
(T7650B model), override status LCD and digital display.  
The W7750 is the Constant Volume Air Handling Unit  
(CVAHU) Controller in the Excel 10 product line family. The  
CVAHU is a LONMARK compliant device designed to control  
single zone and heat pump air handlers. W7750 systems  
control the space temperature in a given zone by regulating  
the heating and cooling equipment in the air handler that  
delivers air to that space. The W7750 air handler is typically  
an all-in-one constant air volume packaged unit, located on  
the roof of the building. In addition to standard heating and  
cooling control, the W7750 provides many options and  
advanced system features that allow state-of-the-art  
commercial building control. The W7750 Controller is capable  
of stand-alone operation; however, optimum functional  
benefits are achieved when the network communication  
The Q7750A Excel 10 Zone Manager is a communications  
interface that allows devices on the LONWORKS Bus network  
to communicate with devices on the standard EXCEL 5000  
System C-Bus. Fig. 1 shows an overview of a typical system  
layout. The Q7750A also provides some control and  
monitoring functions.  
capabilities are used. The W7750 utilizes the Echelon  
Q7752A  
C-BUS COMMUNICATION NETWORK  
LONWORKS BUS  
SERIAL  
ADAPTER  
EXCEL 10  
Q7750A  
PERSONAL COMPUTER TOOLS  
E-VISION  
CARE  
ZONE  
MANAGER  
EXCEL 500  
EXCEL BUILDING SUPERVISOR  
C-BUS TO LONWORKS BUS  
INTERFACE DEVICE  
Q7740A  
2-WAY  
LONWORKS-BUS COMMUNICATIONS NETWORK  
LONWORKS BUS COMMUNICATIONS NETWORK  
REPEATER  
31  
30  
29  
28  
27  
26  
25  
24  
23  
22  
21  
20  
19  
18  
17  
16  
EXCEL 10  
W7750B  
CVAHU  
EXCEL 10 W7751F  
PANEL PLENUM  
MOUNT VERSION  
VARIABLE AIR VOLUME  
CONTROLLER  
CONTROLLER  
1
2
3
4
5
6
7
8
9
10  
Q7751A  
11  
12  
13  
14  
1
5
J3  
FTT  
LONWORKS BUS  
ROUTER  
EXCEL 10 T7770  
WALL MODULE  
EXCEL 10 T7560A, B  
WALL MODULE  
M17487  
Fig. 1. Typical system overview.  
74-29581  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
The W7750 can control staged or modulating heating and  
cooling coils, mixed air economizer dampers, and the system  
fan. Control of heat pump units, where the compressor(s) is  
used for both cooling and heating, is also provided. The zone  
the W7750 services can use a T7770 or T7650 for space  
temperature sensing and an LONWORKS Bus network access  
for users. Fig. 2 shows a typical W7750 control application.  
Control Application  
W7750 systems in commercial buildings typically incorporate  
a packaged air handler system that delivers a constant  
volume of air at preconditioned temperatures to the zone  
being served. Each zone is usually serviced by a separate  
AHU; however, sometimes two or more AHUs service the  
same zone. Note that the W7750 is not designed to control  
Variable Air Volume (VAV) air handlers or Multi-Zone air  
handlers, where one air handler simultaneously controls the  
space temperature in many zones.  
OA TEMP  
HEAT  
COIL  
COOL  
COIL  
FILTER  
FAN  
OUTDOOR  
AIR  
+
-
M
EXCEL 10  
W7750  
CVAHU  
DA TEMP  
RA TEMP  
ROOF  
CEILING  
OCCUPANCY  
SENSOR  
RETURN  
AIR  
DISCHARGE  
AIR  
T7770 OR T7560A,B  
M17488  
WINDOW CONTACT  
Fig. 2. Typical W7750 control application.  
one of ten strategies based on the inputs. For more details,  
see Appendix BSequences of Operation. When the  
economizer position is controlled from the W7750, the  
minimum position setting (for ventilation requirements) can be  
adjusted based on indoor air quality (IAQ) needs in the space.  
Control Provided  
The W7750 Controller is designed to control a single air  
handler to maintain the units space temperature at the current  
setpoint. Heating and cooling control is provided for either  
staged or modulating equipment. Up to four stages of  
mechanical cooling and up to four stages of heating are  
allowed. Modulating outputs can be either floating type such  
as a Series 60 control, or Pulse Width Modulated (PWM  
W7750B,C only) control.  
IAQ monitoring is provided through either a CO sensor or a  
2
digital input from a space-mounted IAQ limit switch.  
For heat pump configurations, up to four compressors can be  
controlled, along with up to four stages of auxiliary heat, and a  
heat/cool change over valve. Including the supply fan, the  
combination of these items may not exceed eight outputs if a  
W7750B,C is used, or six outputs for a W7750A. (The eight  
outputs on the W7750C consist of five digital and three analog  
outputs.)  
The economizer dampers can be controlled directly with  
floating or PWM outputs, or indirectly using a digital output as  
an enable/disable signal to a packaged economizer controller.  
The economizer enable function, which decides when to allow  
outdoor air to be used for free cooling, can be configured to  
7
74-29581  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Like the W7751 VAV Box Controller, the W7750 Controller can  
monitor a space-mounted occupancy sensor, and a door/  
window contact. These inputs affect the operational mode of  
the controller (see Table 5 for a list of all possible modes of  
operation).  
Form No.  
Title  
74-2956  
74-2697  
74-3097  
74-2950  
Excel 10 W7750A,B,C Controller Specification  
Data  
Excel 10 T7770A,B,C,D,E,F,G Wall Module  
Specification Data  
The W7750 Controller allows other controllers in the system to  
use the W7750s physical inputs and outputs. A digital input  
and an analog input can be configured to read switch states  
and voltage sensor values, respectively, and send them out  
over the LONWORKS Bus network. The Q7750A Zone  
Manager can use these values in custom control strategies.  
Additionally, two of the W7750 digital outputs are available for  
control program use. These outputs only respond to signals  
sent over the network, and are not controlled by the W7750  
internal control algorithms.  
T7560A,B Digital Wall Module Specification  
Data  
Excel 10 Q7750A, Zone Manager Specification  
Data  
74-2952  
74-2954  
Excel 10 Q7751A,B Router Specification Data  
Excel 10 Q7752A Serial Interface Specification  
Data  
Products Covered  
This System Engineering Guide describes how to apply the  
Excel 10 family of W7750 CVAHU Controllers and related  
accessories to typical applications. The specific devices  
covered include:  
74-3067  
74-2858  
74-2951  
95-7521  
95-7538  
95-7620  
95-7509  
95-7510  
95-7511  
95-7613  
95-7555  
95-7554  
Q7752B PCMCIA LONWORKS PCC-10 Card  
Specification Data  
Excel 10 Q7740A,B FTT Repeaters  
Specification Data  
W7750A,B,C Controllers.  
T7770A through D Wall Modules.  
T7560A,B Wall Modules.  
Q7750A Excel 10 Zone Manager.  
Q7751A,B Router (FTT to FTT and TPT to FTT).  
Q7752A Serial Interface.  
Q7740A,B Repeaters (2-way and 4-way).  
209541B FTT Termination Module.  
Excel 10 Q7750A Zone Manager Checkout  
and Test Manual  
Excel 10 W7750A,B,C Controller Installation  
Instructions  
Excel 10 T7770A,B,C,D,E,F,G Wall Module  
Installation Instructions  
Organization of Manual  
T7560A,B Digital Wall Module Installation  
Instructions  
This manual is divided into three basic parts: the Introduction,  
the Application Steps, and the Appendices that provide  
supporting information. The Introduction and Application  
Steps 1 through 5 provide the information needed to make  
accurate material ordering decisions. Application Step 6 and  
the Appendices include configuration engineering that can be  
started using Excel E-Vision PC Software after the devices  
and accessories are ordered. Application Step 7 is  
troubleshooting.  
Excel 10 Q7750A Zone Manager Installation  
Instructions  
Excel 10 Q7751A,B Router Installation  
Instructions  
Excel 10 Q7752A Serial Interface Installation  
Instructions  
The organization of the manual assumes a project is being  
engineered from start to finish. If an operator is adding to, or is  
changing an existing system, the Table of Contents can  
provide the relevant information.  
Q7752B PCMCIA LONWORKS PCC-10 Card  
Installation Instructions  
Excel 10 Q7740A,B FTT Repeaters Installation  
Instructions  
Applicable Literature  
The following list of documents contains information related to  
the Excel 10 W7750 CVAHU Controller and the EXCEL 5000  
OPEN SYSTEM in general.  
Excel 10 209541B Termination Module  
Installation Instructions  
74-2588  
74-5587  
74-1392  
74-5577  
74-2039  
74-5018  
Excel E-Vision Users Guide  
CARE Users Manual  
CARE Excel 10 Zone Manager Users Guide  
CARE Icon Guide  
XBS Users Manual  
XBS Application Guide  
74-29581  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
NOTE: The T7770B,C Models are available with a absolute  
55 to 85°F (10 to 85°C) or a relative scale plate  
adjustable in E-Vision to ± 18°F (± 5°C).  
Product Names  
The W7750 Controller is available in three models:  
W7750A Constant Volume AHU Controller - W7750A  
Version.  
W7750B Constant Volume AHU Controller - W7750B  
Version.  
W7750C Constant Volume AHU Controller - W7750C  
Version.  
The T7560A,B Wall Module is available in two models:  
T7560A Wall Module displays and provides space  
temperature, setpoint, Occ/Unocc override, override status  
LCD and digital display.  
T7560B Wall Module displays and provides space  
temperature, humidity sensor, setpoint, Occ/Unocc  
override, override status LCD and digital display.  
The T7770 Wall Module is available in four models. The  
T7770 Wall Modules will work with all Excel 5000 and Excel  
10 Controllers (except the W7751A,C,E,G):  
Other products:  
T7770A1xxx Wall Module with nonlinearized 20 Kohm  
NTC sensor only.  
T7770A2xxx Wall Module with nonlinearized 20 Kohm  
NTC sensor and LONWORKS Bus jack.  
T7770B1xxx Wall Module with nonlinearized 20 Kohm  
NTC sensor, 10 Kohm setpoint, and LONWORKS Bus jack.  
T7770C1xxx Wall Module with nonlinearized 20 Kohm  
NTC sensor, 10 Kohm setpoint, bypass button and LED,  
and LONWORKS Bus jack.  
T7770D1xxx Wall Module with nonlinearized 20 Kohm  
NTC sensor, bypass button and LED, and LONWORKS Bus  
jack.  
Q7750A Excel 10 Zone Manager.  
Q7751A,B Bus Router.  
Q7752A Serial Adapter.  
Q7740A,B FTT Repeaters.  
209541B FTT Termination Module.  
Refer to Table 11 in Application Step 5. Order Equipment for a  
complete listing of all available part numbers.  
NOTE: The Q7750A Zone Manager is referred to as (E-Link)  
in internal software and CARE.  
Agency Listings  
Table 1 provides information on agency listings for Excel 10  
products. Be sure to always follow Local Electrical Codes.  
Table 1. Agency Listing.  
Device  
Agency  
Comments  
W7750A,B,C Controllers  
UL  
Tested and listed under UL916 (file number E87741). The CVAHU W7750A,B,C  
Controllers are UL94-5V listed and suitable for plenum mounting.  
cUL  
CE  
Listed (E87741).  
General Immunity per European Consortium Standards EN50081-1 (CISPR 22, Class B)  
and EN 50082-1:1992 (based on Residential, Commercial, and Light Industrial).  
EN 61000-4-2:  
IEC 1000-4-2 (IEC 801-2) Electromagnetic Discharge.  
EN 50140, EN 50204: IEC 1000-4-3 (IEC 801-3) Radiated Electromagnetic Field.  
EN 61000-4-4:  
IEC 1000-4-4 (IEC 801-4)  
Electrical Fast Transient (Burst). Radiated Emissions and  
Conducted Emissions:  
1987 Class B.  
1985.  
EN 55022:  
CISPR-22:  
FCC Complies with requirements in FCC Part 15 rules for a Class B Computing Device.  
Operation in a residential area can cause interference to radio or TV reception and require  
the operator to take steps necessary to correct the interference.  
T7770A,B,C,D and  
UL  
(Not applicable.)  
T7560A,B Wall Modules  
cUL  
(Not applicable.)  
FCC (Not applicable.)  
Q7750A Excel 10  
Zone Manager  
UL  
Tested and listed under UL916, file number S4804 (QVAX, PAZY).  
CSA Listing pending.  
FCC Complies with requirements in FCC Part 15 rules for a Class A Computing Device.  
Operation in a residential area can cause interference to radio or TV reception and require  
the operator to take steps necessary to correct the interference.  
Q7740A,B FTT  
UL  
UL1784.  
Repeaters, Q7751A,B  
Routers and  
Q7752A Serial Adapter  
CSA Listed.  
FCC Complies with requirements in FCC Part 15 rules for a Class B Computing Device.  
9
74-29581  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Excel 10 Zone Manager A controller that is used to  
interface between the C-Bus and the LONWORKS Bus.  
The Excel 10 Zone Manager also has the functionality  
of an Excel 100 Controller, but has no physical I/O  
points.  
Abbreviations and Definitions  
AHU Air Handling Unit; the central fan system that includes  
the blower, heating equipment, cooling equipment,  
ventilation air equipment, and other related equipment.  
CO Carbon Monoxide. Occasionally used as a measure of  
NOTE: The Q7750A Zone Manager can be referred to as  
E-Link in the internal software, CARE.  
indoor air quality.  
CO2 Carbon Dioxide. Often used as a measure of indoor air  
E-Vision User interface software used with devices that  
operate via the FTT LONWORKS Bus communications  
protocol.  
quality.  
CARE Computer Aided Regulation Engineering; the PC  
based tool used to configure C-Bus and LONWORKS Bus  
devices.  
Firmware Software stored in a nonvolatile memory medium  
such as an EPROM.  
C-Bus Honeywell proprietary Control Bus for  
communications between EXCEL 5000 System  
controllers and components.  
Floating Control Refers to Series 60 Modulating Control of  
a valve or damper. Floating Control utilizes one digital  
output to pulse the actuator open, and another digital  
output to pulse it closed.  
CPU Central Processing Unit; an EXCEL 5000 OPEN  
SYSTEM controller module.  
FTT Free Topology Transceiver.  
cUL Underwriters Laboratories Canada  
IAQ Indoor Air Quality. Refers to the quality of the air in the  
conditioned space, as it relates to occupant health and  
comfort.  
CVAHU Constant Volume AHU; refers to a type of air  
handler with a single-speed fan that provides a constant  
amount of supply air to the space it serves.  
I/O Input/Output; the physical sensors and actuators  
connected to a controller.  
DDF Delta Degrees Fahrenheit.  
I x R I times R or current times resistance; refers to Ohms  
D/X Direct Expansion; refers to a type of mechanical cooling  
Law: V = I x R.  
where refrigerant is (expanded) to its cold state, within a  
heat-exchanging coil that is mounted in the air stream  
supplied to the conditioned space.  
K
Degrees Kelvin.  
Level IV Refers to a classification of digital communication  
wire. Formerly known as UL Level IV, but not equivalent  
to Category IV cable. If there is any question about wire  
compatibility, use Honeywell-approved cables (see Step  
5 Order Equipment section).  
Echelon The company that developed the LONWORKS Bus  
and the Neuron chips used to communicate on the  
LONWORKS Bus.  
Economizer Refers to the mixed-air dampers that regulate  
the quantity of outdoor air that enters the building. In  
cool outdoor conditions, fresh air can be used to  
supplement the mechanical cooling equipment.  
Because this action saves energy, the dampers are  
often referred to as economizer dampers.  
LONWORKS Bus Echelons LONWORKS network for  
communication among Excel 10 Controllers.  
LONWORKS Bus Segment An LONWORKS Bus section  
containing no more than 60 Excel 10s. Two segments  
can be joined together using a router.  
EMI Electromagnetic Interference; electrical noise that can  
cause problems with communications signals.  
NEC National Electrical Code; the body of standards for  
safe field-wiring practices.  
E-Link Refers to the Q7750A Zone Manager. This name is  
used in internal software and in CARE software.  
NEMA National Electrical Manufacturers Association; the  
standards developed by an organization of companies  
for safe field wiring practices.  
EMS Energy Management System; refers to the controllers  
and algorithms responsible for calculating optimum  
operational parameters for maximum energy savings in  
the building.  
Node A Communications Connection on a network; an  
Excel 10 Controller is one node on the LONWORKS Bus  
network.  
EEPROM Electrically Erasable Programmable Read Only  
Memory; the variable storage area for saving user  
setpoint values and factory calibration information.  
NV Network Variable; an Excel 10 parameter that can be  
viewed or modified over the LONWORKS Bus network.  
Enthalpy The energy content of air measured in BTUs per  
PC An Personal Computer with Pentium processor capable  
pound (KiloJoules per Kilogram).  
of running Microsoft Windows 95.  
EPROM Erasable Programmable Read Only Memory; the  
firmware that contains the control algorithms for the  
Excel 10 Controller.  
Pot Potentiometer. A variable resistance electronic  
component located on the T7770B,C or T7560A,B Wall  
Modules; used to allow user-adjusted setpoints to be  
input into the Excel 5000 or Excel 10 Controllers.  
74-29581  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
PWM Pulse Width Modulated output; allows analog  
modulating control of equipment using a digital output  
on the controller.  
Construction  
Controllers  
RTD Resistance Temperature Detector; refers to a type of  
temperature sensor whose resistance output changes  
according to the temperature change of the sensing  
element.  
The Excel 10 W7750 Controller is available in three different  
models. The W7750A Model, which is a low cost controller  
made for simple single zone air handlers and heat pump  
controls. The W7750B,C Models are intended for more  
complex applications.  
Subnet A LONWORKS Bus segment that is separated by a  
router from its Q7750A Zone Manager.  
The W7750B,C Models use Triacs for their digital outputs,  
where as the W7750A Model uses dry-contact relays. The  
W7750C Model also has three analog outputs available on  
terminals 16, 17 and 18.  
TOD Time-Of-Day; the scheduling of Occupied and  
Unoccupied times of operation.  
TPT Twisted Pair Transceiver.  
All wiring connections to the controller are made at screw  
terminal blocks. Connection for operator access to the  
LONWORKS Bus is provided by plugging the SLTA connector  
cable into the LONWORKS Bus communications jack.  
VA Volt Amperes; a measure of electrical power output or  
consumption as applies to an ac device.  
Vac Voltage alternating current; ac voltage rather than dc  
The W7750A,B,C Models consist of a single circuit board that  
is mounted in a sheet metal subbase and protected by a  
factory snap-on cover. The three controllers have the same  
physical appearance except for terminals 16 through 20  
(W7750A) and different labels next to the wiring terminals  
(see Fig. 3, 5 or 6). Wires are attached to the screw terminal  
blocks on both sides of the controller. The controllers mount  
with two screws (see Fig. 4 or 7). The W7750 can also be  
mounted using DIN rail. To mount the W7750 on DIN rail,  
purchase two DIN rail adapters (obtain locally) part number  
TKAD, from Thomas and Betts, see Fig. 8, then snap onto  
standard EN 50 022 35 mm by 7.5 mm (1-3/8 in. by 5/16 in.)  
DIN rail. DIN rail is available through local suppliers.  
voltage.  
VAV Variable Air Volume; refers to either a type of air  
distribution system, or to the W7751 Excel 10 VAV Box  
Controller that controls a single zone in a variable air  
volume delivery system.  
VOC Volatile Organic Compound; refers to a class of  
common pollutants sometimes found in buildings.  
Sources include out-gassing of construction materials,  
production-line by-products, and general cleaning  
solvents. A VOC is occasionally used as a measure of  
indoor air quality.  
W7750 The model number of the Excel 10 CVAHU  
A channel in the cover allows the controller status LED to be  
visible when the cover is in place. There are no field-  
serviceable parts on the circuit board and, therefore, it is  
intended that the cover never be removed.  
Controllers (also see CVAHU).  
W7751 The model number of the Excel 10 VAV Box  
Controllers (also see VAV).  
The W7750A,B,C can be mounted in any orientation.  
Ventilation openings were designed into the cover to allow  
proper heat dissipation regardless of the mounting orientation.  
See Fig. 4 and 7.  
Wall Module The Excel 10 Space Temperature Sensor and  
other optional controller inputs are contained in the  
T7770 or the T7560A,B Wall Modules. See Application  
Step 5. Order Equipment for details on the various  
models of Wall Modules.  
The input/output and control differences between the two  
models are summarized in Table 2. The I/O points in Table 2  
are the free I/O points that are not reserved for Wall Module  
use.  
XBS Excel Building Supervisor; a PC based tool for  
monitoring and changing parameters in C-Bus devices.  
Table 2. List of Differences in W7750A and W7750B,C Controllers.  
W7750A Model  
W7750B,C Models  
Digital Outputs  
Digital Inputs  
Wall Module  
Analog Outputs  
Analog Inputs  
DC Power  
Six Relay Outputs  
Eight Triac Outputs  
Two  
Four  
One*  
None  
One*  
Three 4 to 20 mA Outputs (W7750C only)  
One (Resistive Input Only) Four (Two Resistive and two Voltage/Current Inputs)  
None  
20 Vdc available to power optional sensors  
Heating, Cooling, and/or Economizer  
Heating, Cooling, and/or Economizer  
Floating (Series 60) Control Economizer Only  
PWM Control  
None  
*The T7770 or the T7560 Wall Modules includes I/O points for  
two analog inputs for the space temperature and the setpoint  
knob, a digital input for the Bypass pushbutton, and a digital  
output for the LED Bypass Indicator. These W7750 I/O  
points are configurable, but are normally used for the Wall  
Module.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
74-29581  
     
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
W7750A  
31  
30  
29  
28  
27  
26  
25  
24  
23  
22  
21  
24  
20  
W1  
19  
W
2
NETW  
18  
Y1  
ORK  
DO  
17  
Y2  
16  
G
24  
NO  
Rc  
VA  
C
T
Rh  
NO  
T
NO  
VA  
C
NO  
T
T
NO  
T
USED  
COM  
USED  
USED  
USED  
USED  
E
GND  
LED  
BYP  
ASS  
SNSR  
GND  
SET PT  
AI-1  
OHM  
GND  
DI-1  
GND  
GND  
DI-2  
NO  
USED  
T
1
L
ON  
W
ORKS  
2
L
JA  
3
ON  
4
5
6
BU  
S
7
8
C
K
9
10  
11  
12  
13  
14  
15  
J3  
Fig. 3. Excel 10 W7750A Constant Volume AHU Controller.  
74-29581  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
2-1/8  
(54)  
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16  
5-5/8  
(143)  
NEYWORK  
DO  
24  
VAC  
COM  
24  
NOT  
NOT  
NOT  
NOT  
NOT  
WI  
W2  
Y1  
Y2  
G
Rc  
Rh  
VAC  
USED  
USED  
USED  
USED  
USED  
E
GND  
LED  
BYPASS  
SNSR  
GND  
SET PT  
AI-1  
OHM  
GND  
DI-1  
GND  
GND  
DI-2  
NOT  
USED  
LON  
JACK  
LONWORKS  
BUS  
3-1/16  
(77)  
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 J3  
5-3/16 (132)  
6 (152)  
M10098B  
Fig. 4. W7750A construction in in. (mm).  
Special Note for the W7750B,C Unit:  
PERFORMANCE SPECIFICATIONS  
The individual Triac outputs incorporate an internal common  
connection with the input power transformer. The Triacs  
provide a switched path from the hot side (R) of the  
transformer through the load to the common of the  
transformer. The W7750B,C Controller design must use the  
same power transformer for any loads connected to that  
controller; see Fig. 30.  
Power:  
24 Vac with a minimum of 20 Vac and a maximum of 30 Vac at  
either 50 or 60 Hz. The W7750A power consumption is 6 VA  
maximum at 50 or 60 Hz. The W7750B,C power consumption  
is 12 VA maximum at 50 or 60 Hz.The W7750A,B,C is a NEC  
Class 2 rated device. This listing imposes limits on the amount  
of power the product can consume or directly control to a total  
of 100 VA.  
Each individual Triac is rated 1A at 30 Vac maximum. Under  
all operating conditions, the maximum load/source power  
budget for the W7750B,C Controller is 100 VA. Actual  
allowable Triac current is 500 mA MAX.  
13  
74-29581  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
31  
30  
29  
28  
27  
26  
25  
24  
23  
22  
21  
20  
DI-4  
DI  
GND  
19  
VA  
24  
C
18  
DI-3  
17  
DI  
GND  
DI-2  
VA  
C
24  
16  
DI-1  
1
OUT  
2
OUT  
COM  
3
OUT  
4
OUT  
5
OUT  
6
OUT  
7
OUT  
8
OUT  
E
GND  
LED  
BYP  
ASS  
SNSR  
AI  
GND  
SET PT  
AI-1  
OHM  
AI  
GND  
A1-2  
OHM  
AI-3  
V/mA  
AI  
GND  
AI-4  
V/mA  
20VDC  
OUT  
1
LON  
BU  
WORKS  
S
2
3
LON  
4
5
6
JA  
C
K
7
8
9
10  
11  
12  
13  
14  
15  
J3  
M6854B  
Fig. 5. Excel 10 W7750B Constant Volume AHU Controller.  
CPU:  
Specified Space Temperature Sensing Range:  
45 to 99°F (7 to 37°C) with an allowable control setpoint range  
from 50 to 90°F (10 to 32°C) when initiated from the network  
and 55 to 85°F (13 to 29°C) when configured and connected  
to T7770 or T7560 Wall Modules.  
Motorola or Toshiba 3150 Neuron processor, containing three  
eight-bit CPUs. Each Neuron has a unique 48-bit network  
identification number.  
Memory Capacity:  
64K ROM/PROM (6K reserved for network operations, 58K  
usable for control algorithm code).  
512 bytes EEPROM.  
2K RAM.  
74-29581  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
31  
30  
29  
28  
27  
26  
25  
24  
23  
22  
21  
20  
DI-4  
DI  
19  
VA  
24  
C
18  
DI-3  
G
17  
ND  
DI  
GND  
DI-2  
VA  
C
24  
16  
DI-1  
1
OUT  
2
OUT  
COM  
3
OUT  
4
OUT  
5
OUT  
A0  
1
A0  
2
A0  
3
E
GND  
LED  
BYP  
ASS  
SNSR  
AI  
GND  
SET PT  
AI-1  
OHM  
AI  
GND  
A1-2  
OHM  
AI-3  
V/mA  
AI  
GND  
AI-4  
V/mA  
20VDC  
OUT  
1
LON  
BU  
WORKS  
S
2
3
LON  
4
5
6
JA  
C
K
7
8
9
10  
11  
12  
13  
14  
15  
J3  
M17489  
Fig. 6. Excel 10 W7750C Constant Volume AHU Controller.  
15  
74-29581  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
2-1/8  
(54)  
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16  
VAC  
24  
5-5/8  
(143)  
3
OUT  
2
OUT  
4
OUT  
A0  
1
VAC  
24 COM OUT  
1
5
OUT  
A0  
2
A0  
3
DI  
GND  
DI  
GND  
DI-4  
DI-3 DI-2  
DI-1  
E
GND  
BYPASS SNSR AI  
SET PT AI-1 AI AI-2 AI-3  
AI AI-4 20VDC LONWORKS  
GND  
LED  
L
JACK  
ON  
GND  
GND  
OHM  
OHM V/mA  
V/mA OUT  
BUS  
3-1/16  
(77)  
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 J3  
5-3/16 (132)  
6 (152)  
M17490  
Fig. 7. W7750B,C construction in in. (mm). W7750C (shown) has three 4 to 20 mA analog outputs.)  
Communications:  
Approved cable types for LONWORKS Bus communications  
wiring is Level IV 22 AWG (0.34 mm2) plenum or nonplenum  
rated unshielded, twisted pair, solid conductor wire. For  
nonplenum areas, use Level IV 22 AWG (0.34 mm2) such as  
U.S. part AK3781 (one pair) or U.S. part AK3782 (two pair). In  
plenum areas, use plenum-rated Level IV, 22 AWG (0.34  
mm2) such as U.S. part AK3791 (one pair) or U.S. part  
AK3792 (two pair). (See Tables 9 and 11 for part numbers.)  
Contact Echelon Corp. Technical Support for the  
The W7750A,B,C Controller uses a Free Topology  
Transceiver (FTT) transformer-coupled communications port  
running at 78 kilobits per second (kbps). Using the  
transformer-coupled communications interface offers a much  
higher degree of common-mode noise rejection while  
ensuring dc isolation.  
recommended vendors of Echelon approved cables.  
74-29581  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
2
3
1
M6857  
Fig. 8. DIN rail adapters.  
The FTT supports polarity insensitive free topology wiring.  
This frees the system installer from wiring using a specific bus  
topology. T-tap, star, loop, and mixed wiring topologies are all  
supported by this architecture. The maximum LONWORKS Bus  
length when using a combination of T-tap, star, loop, and bus  
wiring (singly terminated) is 1640 ft. (500m) with the maximum  
node-to-node length of 1312 ft. (400m). In the event that the  
total wire length is exceeded, then a Q7740A 2-Way Repeater  
or a Q7740B 4-Way Repeater can be used to allow the  
number of devices to be spread out as well as increasing the  
length of wire over which they communicate. The maximum  
number of repeaters per segment is one (on either side of the  
router). A Q7751A,B LONWORKS Bus Router can also be used  
to effectively double the maximum LONWORKS Bus length.  
The advantage of using the router is that it segregates traffic  
to a segment while when using the repeater, all traffic is  
repeated on each segment. When utilizing a doubly  
chain with no stubs or taps from the main backbone, The  
maximum LONWORKS Bus length is 4593 ft. (1400m) with the  
maximum node-to-node length of 3773 ft. (1150m).  
FTT networks are very flexible and convenient to install and  
maintain, but it is imperative to carefully plan the network  
layout and create and maintain accurate documentation. This  
aids in compliance verification and future expansion of the  
FTT network. This also keeps unknown or inaccurate wire run  
lengths, node-to-node (device-to-device) distances, node  
counts, total wire length, inaccurate repeater/router locations,  
and misplaced or missing terminations minimized. Refer to  
LONWORKS Bus Wiring Guidelines form, 74-2865 for complete  
description of network topology rules.  
LONMARK® FUNCTIONAL PROFILE  
W7750 Controllers support the LONMARK Functional Profile  
number 8030 Roof Top Unit Controller, version 1.0  
(see Fig. 9).  
terminated LONWORKS Bus structure, use a continuous daisy-  
17  
74-29581  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Inputs/Outputs:  
The W7750A Unit supports the following hardware features:  
Hardware  
Output  
Three 20 Kohm NTC (1000 through 150,000 ohm) or  
PT3000 (250 through 12,000 ohm) resistive analog inputs  
(one reserved for space temperature and one reserved for  
the setpoint knob).  
Roof Top Unit  
Controller number 8030  
Three dry contact digital inputs (one reserved for the  
Bypass pushbutton).  
LED digital output (only for the wall module LED) 2.5V at 3  
mA.  
Six 24 Vac relay digital outputs (1.5A relays rated at 7.5A  
inrush current).  
nvoSpaceTemp  
SNVT_ temp_p  
nviSpaceTemp  
SNVT_temp_p  
nv1  
nv2  
nv3  
nv4  
Mandatory  
Network  
Variables  
nvoUnitStatus  
SNVT_hvac_status  
nviSetPoint  
SNVT_temp_p  
nviApplicMode  
SNVT_hvac_mode  
nvoEffectSetPt  
SNVT_ temp_p  
The W7750B,C Units support the following hardware features:  
nv5  
nv6  
nv10  
nv11  
Four 20 Kohm NTC (1000 through 150,000 ohm) or  
PT3000 (250 through 12,000 ohm) resistive analog inputs  
(one reserved for space temperature and one reserved for  
the setpoint knob).  
nviOccCmd  
SNVT_occupancy  
nvoOutsideTemp  
SNVT_ temp_p  
Optional  
Network  
Variables  
nviSetPtOffset  
SNVT_ temp_p  
nvoOutsideRH  
SNVT_ lev_percent  
nv7  
nv8  
nv12  
nv16  
Two 0.2 to 10 VDC or 2 to 20 mA (user selectable) analog  
inputs.  
Five dry contact digital inputs (one reserved for the Bypass  
nviOutsideTemp  
SNVT_ temp_p  
nvoCO  
SNVT_ppm  
2
pushbutton).  
Eight on the W7750B (five on the W7750C) 24 Vac Triac  
digital outputs (500 mA MAX). The W7750C Unit also  
supports three 4 to 20 mA analog outputs.  
LED digital output (only for the wall module LED, T7770  
models or LCD, T7560A,B) 2.5V at 3 mA.  
One 20 Vdc power supply for auxiliary devices with a  
maximum current of 50 mA.  
nviOutsideRH  
SNVT_lev_percent  
nv9  
nviSpaceRH  
SNVT_ lev_percent  
nv13  
nviCO  
2
SNVT_ppm  
nv14  
nv15  
ANALOG INPUTS:  
nviEmergCmd  
SNVT_hvac_emerg  
NOTE: Only one of each type of input is allowed. For  
example, only one Outdoor Air Temperature sensor  
is allowed. No duplicate Outdoor Air Temperature  
sensors are usable on the same controller.  
Configuration Properties  
nc49 - Send Heartbeat  
nc60 - Occupancy Temperature Setpoints (mandatory)  
(mandatory)  
Space Temperature:  
nc48 - Maximum Receive Time  
nc17 - Location  
(optional)  
(optional)  
(mandatory)  
Type: RTD.  
Supported Sensors: T7770A,B,C,D; T7560A,B.  
nc42 - CO Limit  
2
Discharge Air Temperature:  
Manufacturer  
Defined  
Type: RTD.  
Supported Sensors: C7100A1015*, C7770A1006,  
C7031B1033, C7031C1031, C7031D1062, C7031F1018  
(W7750B,C only), C7031J1050, C7031K1017.  
Section  
Hardware  
Input  
M11580  
Outdoor Air Temperature:  
Type: RTD.  
Fig. 9. Functional profile of LONMARK® RTU object details  
(variables not implemented in Excel 10 CVAHU  
are greyed).  
Supported Sensors: C7170A1002.  
Return Air Temperature:  
Type: RTD.  
Environmental:  
Supported Sensors: C7100A1015*, C7770A1006,  
C7031B1033, C7031C1031, C7031D1062, C7031F1018  
(W7750B,C only), C7031J1050, C7031K1017.  
*The PT3000 sensor is not recommended for floating control  
(real time - discharge or return configured as space sensor).  
The PT3000 sensor is intended for monitoring or differential  
(staged) control  
Operating Temperature: -40 to 150°F (-40 to 65.5°C).  
Shipping Temperature:  
-40 to 150°F (-40 to 65.5°C).  
Relative Humidity:  
5% to 95% noncondensing.  
Vibration:  
Rated V2 level compliant.  
74-29581  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Outdoor Air Humidity (W7750B,C only):  
Type: Voltage/Current.  
Dirty Filter:  
Contact Closed = Dirty Filter  
Shutdown Signal:  
Contact Closed = Shut off all equipment  
Occupancy Switch:  
Supported Sensors: C7600B1000 and C7600B1018  
(2 to 10V), C7600C1008 (4 to 20mA).  
Contact Closed = Room is Occupied; Contact Open =  
Room is Unoccupied  
Window Monitor:  
Contact Closed = Window is Closed  
Coil Freeze Stat: (Only use this DI when using E-Vision.)  
Contact Closed = Coil Freeze condition sensed  
Wall Module Bypass Pushbutton:  
Momentary DI (See Appendix BSequences of Operation  
for bypass details.)  
Return Air Humidity (W7750B,C only):  
Type: Voltage/Current.  
Supported Sensors: C7600B1000 and C7600B1018  
(2 to 10V), C7600C1008 (4 to 20mA).  
Outdoor Air Enthalpy (W7750B,C only):  
Type: Current.  
Supported Sensors: C7400A1004 (4 to 20mA).  
Return Air Enthalpy (W7750B,C only):  
Type: Current.  
TRIAC OUTPUTS ON THE (W7750B,C MODELS ONLY):  
Power ratings: 20 Vac to 30 Vac at 25 mA MIN to 500 mA  
MAX current for any voltage.  
Supported Sensors: C7400A1004 (4 to 20mA).  
Air Filter Differential Pressure (W7750B,C only):  
Type: Voltage.  
CAUTION  
When any device is energized by a Triac, the device  
must be able to sink a minimum of 25 mA.  
Supported Sensors: Third party 2 to 10V, 0 to 5 inw  
(1.25 kPa) differential pressure sensors.  
CO2 Sensor (W7750B,C only):  
Type: Voltage.  
NOTE: Triacs sink current to the 24 Vac common (COM  
terminal on the W7750B,C Models); see Fig. 30 for  
wiring example.  
Supported Sensors: Third party 0 to 10V, 0 to 2000 ppm  
CO2 sensors.  
Monitor Sensor for network use (W7750B,C only):  
Type: Voltage.  
IMPORTANT  
If non-Honeywell motors, actuators, or transducers  
are to be used with Excel 10 Controllers, Triac com-  
patibility must be verified (see previous NOTE).  
Supported Sensors: Third party 2 to 10V, 2 to 10 volts  
displayed.  
DIGITAL OUTPUTS:  
DIGITAL INPUTS:  
COOL STAGE 1  
COOL STAGE 2  
NOTE: Only one of each type of input is allowed. For  
example, only one Smoke Monitor is allowed. No  
duplicate Smoke Monitors are usable on the same  
controller.  
COOL STAGE 3  
COOL STAGE 4  
HEAT STAGE 1  
HEAT STAGE 2  
HEAT STAGE 3  
Dry-contact inputs are sensed using a 9 milliamp at 4.8 volts  
detection circuit. It is very important that the device used  
contains high quality, noncorroding contacts with resistivity  
that does not degrade; that is, increase over time. Use noble  
metal (such as gold or silver), or pimpled or sealed contacts to  
assure consistent, long-term operation.  
HEAT STAGE 4  
CHANGE OVER RELAY  
FAN  
AUX ECON  
OCCUPANCY STATUS  
ECON OPEN  
ECON CLOSE  
COOL OPEN  
Two of the following Digital Inputs (DIs) can be configured  
when using the W7750A, and four of the following when using  
the W7750B,C:  
COOL CLOSE  
HEAT OPEN  
HEAT CLOSE  
HEAT COOL STAGE 1  
HEAT COOL STAGE 2  
Fan Status:  
Contact Closed = Fan on  
IAQ Switch:  
Contact Closed = Poor Air Quality  
Time Clock:  
Contact Closed = Occupied Mode; Contact Open =  
Unoccupied Mode  
Schedule Master:  
Contact Closed = Local time clock is used as master time  
clock  
Economizer Enable Signal:  
Contact Closed = Economizer Enabled for cooling use  
Smoke Monitor:  
HEAT COOL STAGE 3  
HEAT COOL STAGE 4  
FREE1 (NOTE: Free1, Free1 Pulse On and Free1 Pulse Off  
are three separate and unique digital output points. Because  
they are not related, they all can be configured in a CVAHU  
controller at the same time.)  
FREE2  
FREE1 PULSE ON  
FREE1 PULSE OFF  
ECON PWM  
HEAT PWM  
COOL PWM  
UNUSED  
Contact Closed = Smoke Detected  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
74-29581  
     
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
size (see Product Names section for differences). The models  
T7560A1016 and T7560B1018 are shown in Fig. 11. The  
T7560A,B are the same physical size.  
Wall Modules  
The T7770 or T7560 Wall Modules for the Excel 5000 and  
Excel 10 Controllers are available in a variety of  
configurations. The models T7770A1006 and T7770C1002  
are shown in Fig. 10. The T7770B,D are the same physical  
Duct Sensor  
The dimensions of the C7770A duct-mounted sensor are  
shown in Fig. 12.  
KNOCKOUTS FOR EUROPEAN  
APPLICATIONS  
KNOCKOUTS FOR EUROPEAN  
APPLICATIONS  
70  
75  
80  
85  
65  
60  
5-1/16  
(128)  
5-1/16  
(128)  
55  
29/32  
(23)  
1-1/4  
(32)  
3-5/32 (80)  
2-3/8 (60)  
3-5/32 (80)  
2-3/8 (60)  
2-3/8  
(60)  
2-3/8  
(60)  
9
8
7
6
5
4
3
2
1
STANDARD  
UTILITY  
STANDARD  
UTILITY  
CONDUIT  
BOX (2 X 4)  
MOUNTING  
HOLES  
CONDUIT  
BOX (2 X 4)  
MOUNTING  
HOLES  
M15119  
Fig. 10. T7770A,B,C,D construction in in. (mm).  
74-29581  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
3-7/16  
(86)  
4
(100)  
1 2 3 4 5 6 7 8  
2-11/16 (68)  
3-7/8 (97)  
4-1/8  
(104)  
3-15/16 (99)  
1-3/16 (30)  
M17479  
Fig. 11. T7560A,B construction in in. (mm).  
1-1/2 (38)  
3/4 (19)  
8-1/2 (216)  
1/2 (13)  
3/8 IN. (10)  
DIAMETER  
1/2 IN. (13)  
DIAMETER  
7/8  
(22)  
3-1/2 (89)  
6-5/32 (156)  
1/4 (6)  
DIAMETER (2 HOLES)  
1/2 (13)  
M7724  
Fig. 12. C7770A construction in in. (mm).  
21  
74-29581  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Configurations  
CAUTION  
For floating control, the Excel 10 W7750 Controller is  
designed to work only with Series 60 valve and  
damper actuators. Full stroke actuator drive-time must  
be between 20 and 240 seconds (0.25 to 4.0 minutes).  
General  
Tables 3 and 4 provide an overview of the Excel 10 W7750  
configuration options. All W7750s are assumed to have a  
supply fan digital output. Additionally, Tables 3 and 4 list the  
general mechanical equipment options available with the  
W7750 Controller. See Application Step 6. Configure  
Controllers, for further information on configurations.  
Table 3. Common Configuration Options Summary For W7750A,B,C Controllers.  
Option  
Possible Configurations Common To All W7750 Models  
Supply Fan  
1. Mandatory Digital Output.  
Type of Air Handler  
1. Conventional.  
2. Heat Pump.  
Occupancy Sensor  
Window Sensor  
1. None.  
2. Connected: Contacts closed equals Occupied.  
3. Network (Occ/Unocc signal received via the LONWORKS Bus network).  
1. None.  
2. Physically Connected: Contacts closed equals window closed.  
3. Network (Window Open/Closed signal received via the LONWORKS Bus).  
1. Local (direct wired to the controller).  
Wall Module Option  
(The T77560A,B has no LONWORKS Bus access) 2. Network (sensor value received via the LONWORKS Bus).  
Wall Module Type  
1. Sensor only.  
(All wall modules have a LONWORKS Bus access  
jack except T7560A,B)  
2. Sensor and Setpoint adjust.  
3. Sensor, Setpoint adjust and Bypass.  
4. Sensor and Bypass.  
Smoke Emergency Initiation  
1. None.  
2. Physically Connected: Contacts closed equals smoke detected.  
3. Network (Emergency/Normal signal received via the LONWORKS Bus).  
74-29581  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Table 4. Configuration Options Summary For W7750A,B,C Controllers.  
Possible Configurations for the  
W7750A Model  
Option  
Type of  
Possible Configurations for the W7750B,C Models  
1. One stage.  
1. One stage.  
2. Two stages.  
3. Three stages.  
4. Four stages.  
5. None.  
Heating  
2. Two stages.  
3. Three stages.  
4. Four stages.  
5. Series 60 Modulating electric valve, or pneumatic via transducer.  
6. Pulse Width Modulating electric valve, or pneumatic via transducer.  
7. None.  
Type of  
Cooling  
1. One stage.  
2. Two stages.  
3. Three stages.  
4. Four stages.  
5. None.  
1. One stage.  
2. Two stages.  
3. Three stages.  
4. Four stages.  
5. Series 60 Modulating electric valve, or pneumatic via transducer.  
6. Pulse Width Modulating electric valve, or pneumatic via transducer.  
7. None.  
Type of  
Economizer  
1. Digital Output Enable/Disable  
signal for controlling an external  
economizer package.  
1. Digital Output Enable/Disable signal for controlling an external  
economizer package.  
2. Series 60 Modulating electric  
damper motor, or pneumatic via  
transducer.  
2. Series 60 Modulating electric damper motor, or pneumatic via  
transducer.  
3. None.  
3. Pulse Width Modulating electric damper motor, or pneumatic via  
transducer.  
4. None.  
1. None.  
IAQ Option  
1. None.  
2. Local IAQ Digital Inputdirectly  
wired to the controller. (Contacts  
closed means poor IAQ is  
detected.)  
2. Local IAQ Digital Inputdirectly wired to the controller. (Contacts  
closed means poor IAQ is detected.)  
3. Network (IAQ Override signal  
received via the LONWORKS Bus).  
3. Network (IAQ Override signal received via the LONWORKS Bus).  
4. Local CO2 Analog Inputdirectly wired to the controller. (The sensor  
must be a 0 to 10V device representing 0 to 2000 PPM CO2.)  
Coil Freeze  
Stat Option  
1. None.  
1. None.  
2. Local Coil Freeze Stat Digital  
2. Local Coil Freeze Stat Digital Inputdirectly wired to the controller.  
Inputdirectly wired to the controller. (Contacts closed means that coil freeze condition is sensed.)  
(Contacts closed means that coil  
freeze condition is sensed.)  
Filter Monitor 1. None.  
1. None.  
Option  
2. Local Dirty Filter Digital  
2. Local Dirty Filter Digital Inputdirectly wired to the controller.  
Inputdirectly wired to the  
controller. (Contacts closed means  
that the filter is dirty.)  
(Contacts closed means that the filter is dirty.)  
3. Local Analog Input for Differential Pressure across the Filter (directly  
wired to the controller). The sensor must be a 2 to 10V device  
representing 0 to 5 inw (1.25 kPa).  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
74-29581  
 
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
positions the actuator based on the length, in seconds, of the  
pulse from the digital output. For PWM, the controller outputs  
a pulse whose length consists of two parts, a minimum and a  
maximum. The minimum pulse time represents the analog  
value of 0 percent and the maximum pulse length that  
represents an analog value of 100 percent. If the analog value  
is greater than 0 percent, an additional time is added to the  
minimum pulse time. The length of time added is directly  
proportional to the magnitude of the analog value. The PWM  
actuator will begin to use the analog value at the end of the  
pulse and will continue to use this value until a new pulse is  
received. Refer to Appendix B under PWM Control for an  
example. Series 60 actuators are generally less expensive  
than those for PWM, but the trade-off is that PWM requires  
only a single controller digital output while floating control  
uses two DOs. Refer to Appendix B under Series 60  
Allowable Heating and Cooling Equipment  
Configurations  
Each W7750 device can control a variety of different types of  
mechanical cooling and heating equipment within roof top air  
handlers. See Fig. 13 through 17 for a conceptual overview of  
some typical configurations. For specific wiring details, see  
the Prepare Wiring Diagrams section.  
STAGED HEATING/COOLING CONTROL  
Staged equipment control is available for up to four stages of  
heating or four stages of cooling. On the W7750, the stages  
are activated through digital outputs (Triacs on the W7750B,C  
and dry-contact relays on the W7750A) one for each stage  
wired to 24 Vac contactors (see Fig. 27 and 30 in Step 4.  
Prepare Wiring Diagrams section for wiring details). Note that  
the number of physical Digital Outputs (DOs) on the controller  
limits the total number of stages that can be controlled. For  
example, the W7750A Model has six digital outputs, and  
because one is used for the supply fan, there are five DOs  
available for any combination of heating and cooling stages  
(with a maximum of four stages of heating and four stages for  
cooling). The W7750B Model offers two additional DOs, for a  
total of eight. The W7750C offers five DOs and three Analog  
Outputs (AOs). Fig. 13 shows a typical application of two  
stages of heat and two stages of cooling.  
Modulating Control for an example. Fig. 14 illustrates a  
system with modulating heating and cooling (see Fig. 29 and  
31 in Step 4. Prepare Wiring Diagrams section.  
COOL  
COIL  
HEAT  
COIL  
DISCHARGE  
AIR  
MIXED  
AIR  
FAN  
+
-
HOT  
WATER  
VALVE  
COOL  
COIL  
HEAT  
COIL  
CHILLED  
WATER  
VALVE  
FAN  
STARTER  
DISCHARGE  
AIR  
MIXED  
AIR  
FAN  
+
-
COMPRESSORS  
FAN  
STARTER  
T7560A,B OR T7770  
EXCEL 10  
CVAHU  
W7750A,B,C  
Y1  
Y2  
GAS COMBUSTION  
CONTROLS  
W1 W2  
M17492  
Fig. 14. Fan, modulating heating and modulating cooling.  
NOTE: Pneumatically actuated valves can be controlled  
using a pneumatic transducer device. See Fig. 17.  
Also, transducer devices are available from third  
party vendors to convert PWM outputs to a voltage  
or current signal if desired.  
T7560A,B OR T7770  
EXCEL 10  
CVAHU  
W7750A,B,C  
HEAT PUMP CONTROL  
The W7750 Controller handles heat pump applications  
similarly to staged heating/cooling control. Heat pump  
applications are supported by providing outputs for up to four  
compressor stages, a change-over relay for the refrigerant  
reversing valve, and up to four stages of auxiliary heat. Note  
that the W7750A Model has six digital outputs, and therefore,  
with one DO used for the supply fan and one for the change-  
over relay, there are four outputs available for any  
combination of compressors and auxiliary heat stages. The  
W7750B Model offers two additional DOs for a total of eight,  
while the W7750C Model offers five DOs and 3 AOs. Fig. 15  
illustrates a typical heat pump system with auxiliary heat.  
M17491  
Fig. 13. Fan with two stages of heating and two stages  
of cooling.  
MODULATING HEATING/COOLING CONTROL  
The W7750 Controller provides modulating equipment control  
for heating and cooling equipment (and economizer dampers,  
see Fig. 16) using either Series 60 Floating Control or Pulse  
Width Modulated (PWM) control, (PWM control is available on  
the W7750B,C only). The Series 60 Modulating Control is  
provided through two Relay digital outputs on the W7750A or  
two Triac digital outputs on the W7750B,C (one to pulse the  
valve actuator open and one to pulse it closed). PWM control  
74-29581  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
ECONOMIZER CONTROL  
AUXILIARY  
HEAT  
SHARED  
HEAT AND  
COOL COIL  
Economizer control is available concurrently with any  
configuration in the W7750 when DOs are not all used by the  
heating and cooling equipment. Two types of economizer  
controls are supported by the W7750 Controller, modulating  
control and enable/disable control. Modulating control can be  
either Series 60 Floating Control or PWM control (PWM  
control is available on the W7750B,C only). A discharge air  
temperature sensor is required for modulating economizer  
damper control. Enable/disable control is provided to emulate  
the Honeywell T7300 thermostat economizer operation,  
where a DO tracks the occupancy status of the controller. An  
external packaged economizer control then modulates the  
dampers. For modulating control, the economizer is enabled  
or disabled based on one of ten available strategies (see  
Appendix BSequences of OperationEconomizer Enable/  
Disable Control section, for further details). Fig. 16 illustrates  
a system with modulating economizer dampers (see Fig. 29,  
31, 32 and 35 in Step 4. Prepare Wiring Diagrams section, for  
wiring details).  
STAGE(S)  
DISCHARGE  
AIR  
MIXED  
AIR  
FAN  
+
FAN  
STARTER  
COMPRESSOR AND  
CHANGEOVER VALVE  
COMP 1  
COMP 2  
CHANGEOVER  
RELAY  
EXCEL 10  
CVAHU  
W7750A,B,C  
T7560A,B OR T7770  
M17493  
Fig. 15. Heat pump with two compressors and auxiliary  
heat stage(s).  
COOL  
COIL  
HEAT  
COIL  
DISCHARGE  
AIR  
OUTDOOR  
AIR  
FAN  
+
-
M
DISCHARGE  
FAN  
STARTER  
TEMPERATURE  
SENSOR REQUIRED  
FOR ECONOMIZER  
CONTROL  
PWM OR  
SERIES 60  
FLOATING  
MOTOR  
RETURN  
AIR  
T7560A,B OR T7770  
EXCEL 10  
CVAHU  
W7750A,B,C  
M17494  
Fig. 16. Economizer control.  
PNEUMATIC ACTUATOR CONTROL  
Control to modulate cooling valves, heating valves and  
economizers. There are no PWM outputs configurable on the  
W7750A model.  
The W7750B,C Controller can control pneumatic actuators for  
any or all of the three modulating outputs provided by the  
control algorithm (heat, cool and economizer). Control of  
pneumatic water/steam valves and damper actuators is  
provided through a transducer device using either Series 60  
Floating Control or PWM DOs. A floating-to-pneumatic, or a  
PWM-to-pneumatic transducer is required for each output  
signal. The W7750A Controller can drive Series 60 Floating  
For projects with existing pneumatically actuated reheat  
valves, the Excel 10 W7750 Controller output must be  
converted to a pneumatic signal using a transducer device  
developed for use with Excel 10 Controllers. The transducer is  
25  
74-29581  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
available through Honeywell, or directly from the  
manufacturer, Mamac Systems (see Table 11 for ordering  
information).  
then the Effective Occupancy mode is STANDBY. The  
temperature control algorithm is then controlled to the  
STANDBY Cooling and Heating Setpoints.  
Fig. 17 depicts a typical W7750 System with modulating  
heating valve using a pneumatic valve actuator. Also see Fig.  
36 for wiring an MMC325 Pneumatic Transducer to a  
W7750A,B,C Controller and Fig. 37 for wiring a RP7517B  
Pneumatic Transducer to a W7750C Controller.  
If the occupancy sensor is not configured, a local controller  
can be put in the STANDBY mode only by either a one-to-one  
association of the occupancy sensor from another Excel 10  
Controller to the local controller, or by receiving the STANDBY  
mode signal via the LONWORKS Bus.  
NOTE: The Excel 10 Controller has limited power available  
(only 9 mA at 4.8 volts) for checking the digital inputs  
for contact closures. It is very important that the  
device used contains high quality, noncorroding  
contacts with resistivity that does not degrade; that  
is, increase over time. Use noble metal (such as gold  
or silver), or pimpled or sealed contacts to assure  
consistent, long-term operation.  
NOTE: When choosing the pneumatic pressure range, make  
sure that the close-off pressure is 2 to 3 psi greater  
than that of the spring range. When using a spring  
range of 5 to 10 psi with 10 psi as the closed posi-  
tion, do not use the 0 to 10 psi model of the MMC325  
Transducer; use the 0 to 20 psi transducer as the  
recommended selection.  
The recommended devices for use with the Excel 10 W7750  
Controllers are the EL7628A1007 Ceiling Mounted Infrared or  
the EL7680A1008 Wall Mounted Wide View Infrared  
Occupancy Sensors. If ultrasonic sensors are required, the  
EL7611A1003 and the EL7612A1001 Occupancy Sensors are  
recommended. An EL76XX Power Supply/Control Unit is  
required for use with these occupancy sensors. The  
EL7630A1003 can power up to four sensors, and is multi-  
tapped for several line voltages. The EL7621A1002 can  
power three sensors and it connects to 120 Vac line voltage.  
The EL7621A1010 can also power three sensors but it  
connects to 277 Vac line voltage.  
HEAT  
COIL  
MIXED  
AIR  
DISCHARGE  
AIR  
FAN  
+
PNEUMATIC  
ACTUATOR  
FAN  
STARTER  
VALVE  
1
T7560A,B OR T7770  
Window Open/Closed Digital Input  
M
A digital input is also provided for detecting whether a window  
in the space was opened. The Excel 10 W7750 Controller can  
be connected to a dry contact (see the following NOTE and  
Fig. 27 through 35 in Application Step 4. Prepare Wiring  
Diagrams, for details) or a set of contacts wired in series (for  
monitoring multiple windows) to verify that the window(s) are  
closed. The algorithm expects a contact closure to indicate  
the window is closed. If an open window is detected, the  
algorithm changes the mode of operation to  
MMC325  
PNEUMATIC  
TRANSDUCER  
1
PNEUMATIC MAIN OR BRANCH LINE MUST BE 1/4 IN. (6 MM)  
OR LARGER TUBING. A MINIMUM OF 6 FT (1.8M) OF TUBING  
IS NEEDED IN A BRANCH LINE.  
M17495  
Fig. 17. Modulating heat with pneumatic valve actuator.  
FREEZE_PROTECT, which shuts down the control functions,  
and watches for low space temperature conditions. The frost  
protection setpoint is 46.4°F (8°C), and the frost alarm occurs  
at 42.8°F (6°C).  
NOTE: (This is the same NOTE as in the Occupancy Sensor  
section.) The Excel 10 has limited power available  
(only 9 mA at 4.8 volts) for checking the digital inputs  
for contact closures. It is very important that the  
MIXED-OUTPUT-TYPE CONTROL  
The W7750B,C Controller provides control for mixed-output-  
types of applications such as PWM heating and staged  
cooling control occurring simultaneously with Series 60  
Floating Economizer Damper Control.  
Occupancy Sensor  
device used contains high quality, noncorroding  
Excel 10 W7750 Controllers provide a digital input for  
connection to an occupancy sensor. This is a device, such as  
a passive infrared motion detector, that contains a dry contact  
(see following NOTE) closure to indicate whether or not  
people are present in the space. The Excel 10 W7750  
Controller expects a contact closure to indicate the space is  
Occupied. See Fig. 27 through 35 in Application Step 4,  
Prepare Wiring Diagrams, for details on wiring connections.  
contacts with resistivity that does not degrade; that  
is, increase over time. Use noble metal (such as gold  
or silver), or pimpled or sealed contacts to assure  
consistent, long-term operation.  
Wall Module Options  
As previously discussed, there are four basic varieties of the  
T7770 Wall Modules and two of the T7560 Digital Wall Module  
(see the Product Names and the Construction sections). Also,  
a T7770 and T7560 Wall Modules can be shared among two  
or more W7750s. The control algorithm must be given this  
wall module information when configuring the W7750 (see  
Excel E-Vision Users Guide, form 74-2588).  
The control algorithm in the Excel 10 Controller uses the  
occupancy sensor, if configured, to determine the Effective  
Occupancy (see Table 5) mode of operation. If the Time Of  
Day (TOD) schedule indicates an Occupied state, and the  
occupancy sensor contact is closed, the Effective Occupancy  
mode is Occupied. However, if the TOD schedule indicates an  
Occupied state and the occupancy sensor contact is open,  
74-29581  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
IAQ Override is initiated. The IAQSetpt hysteresis is 50 PPM,  
IAQ Override is deactivated at a CO2 level less than 50 PPM  
below setpoint.  
Dirty Filter Monitor  
The air filter in the air handler can be monitored by the W7750  
and an alarm is issued when the filter media needs  
replacement. The two methods of monitoring the filter are:  
1. Connecting a differential pressure switch to a digital  
input on the W7750A or W7750B,C.  
The effect of initiating the IAQ Override mode is that the  
economizer dampers are allowed to open above the standard  
minimum position setting to allow more fresh air to enter the  
building. See Appendix BSequences of Operation, for  
further control details.  
2. Wiring a 2 to 10V differential pressure sensor to a  
voltage input on the W7750B,C. If the analog input  
sensor is used, its measured value 0 to 5 inw (0 to 1.25  
kPa) is compared to a user-selectable setpoint  
(FltrPressStPtvalid range: 0 to 5 inw (0 to 1.25 kPa)),  
and the Dirty Filter alarm is issued when the pressure  
drop across the filter exceeds the setpoint.  
Smoke Control  
The Excel 10 W7750 Controller supports smoke-related  
control strategies that are initiated either via a network  
command (DestEmergCmd) or from a local (physically  
connected) smoke detector digital input. The details of the  
W7750 smoke-related control operation are described in  
Appendix BSequences of Operation.  
Indoor Air Quality (IAQ) Override  
The Excel 10 W7750 Controller provides IAQ ventilation  
control using one of two different methods of detecting poor  
air quality. The first is with an IAQ switch device connected to  
a digital input on the W7750 Controller, where a contact  
closure indicates poor air quality, and initiates the IAQ  
Override mode. The device can detect poor air quality using  
any desired measure such as CO2, VOC, CO, etc. The  
second method, which is only available on the W7750B,C, is  
through an analog input that connects to a CO2 sensor (2 to  
10V). The measured value of CO2 from this sensor (0 to 2000  
PPM) is compared to the setpoint (IAQSetpt). When the CO2  
level is higher than the setpoint (800 PPM adjustable), the  
Freeze Stat  
A freeze stat can be monitored by the W7750 and issue a  
freeze stat alarm indicating the CVAHU is in danger of  
freezing its coil. The details of the W7750 freeze stat related  
control operation are described in Appendix BSequences of  
Operation.  
Modes of Operation  
The possible modes of operation for the W7750 Controller are  
listed in Table 5.  
Table 5. Modes Of Operation For The Excel 10 W7750 Controller .  
Mode  
Description  
Events causing a controller to switch to this mode  
Effective Occupancy (User Address: StatusOcc)  
OCCUPIED  
STANDBY  
Controller is in Occupied mode  
Any of the following: Network input (DestSchedOcc) containing a  
time-of-day schedule flag from either the Excel 10 Zone Manager or an  
LONWORKS Bus Controller; Time Clock DI, Occupancy Sensor DI; or  
from Network input (DestManMode) for manual override to OCC mode.  
DestManMode has the highest priority, followed by the Time Clock DI,  
and then DestSchedOcc.  
Controller is in Standby mode  
Either: (A) Network input (DestSchedOcc) containing a time-of-day  
schedule flag from the Excel 10 Zone Manager or other LONWORKS  
Bus node is STANDBY, or (B) Network input (DestSchedOcc) is  
OCCUPIED and the Occupancy Sensor DI is UNOCCUPIED.  
UNOCCUPIED Controller is in Unoccupied mode  
Network input (DestSchedOcc) containing a time-of-day schedule flag  
from the Excel 10 Zone Manager or LONWORKS Bus, or the network  
input DestManOcc has a value of UNOCCUPIED.  
BYPASS  
Controller is in Occupied mode through This mode is derived from the schedule occupancy (DestSchedOcc)  
OCCUPIED  
a Bypass command  
having a state of UNOCCUPIED and a manual request for occupancy  
from one of three sources. Two of these are signals originated external  
to the unit, and received by DestManOcc and DestBypass. The third  
source for an occupancy request is from an override button located on  
a wall module. These three sources are arbitrated in a scheme  
determined by the configuration parameter (Network Wins or Last-in  
Wins from OvrdPriority).  
Override Modes (User Address: StatusOvrd)  
OCCUPIED  
Controller occupancy mode was  
overridden to Occupied mode  
Network input (DestManOcc) containing a time-of-day schedule  
override signal of OCCUPIED from the Excel 10 Zone Manager or  
other LONWORKS Bus device.  
STANDBY  
Controller occupancy mode was  
overridden to Standby mode  
Network input (DestManOcc) containing a time-of-day schedule  
override signal of STANDBY from the Excel 10 Zone Manager or other  
LONWORKS Bus device.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
74-29581  
           
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Table 5. Modes Of Operation For The Excel 10 W7750 Controller (Continued).  
Description Events causing a controller to switch to this mode  
Mode  
UNOCCUPIED Controller occupancy mode was  
Network input (DestManOcc) containing a time-of-day schedule  
override signal of UNOCCUPIED from the Excel 10 Zone Manager or  
other LONWORKS Bus device.  
overridden to Unoccupied mode  
BYPASS  
Controller occupancy mode was  
overridden to Bypass the current  
Unoccupied mode  
DI (Bypass) was pressed, and the Bypass duration timer has not yet  
expired, or the network input DestManOcc has a value of BYPASS.  
NOT  
No Bypass action  
No Override input received.  
ASSIGNED  
Operational Modes (User Address: StatusMode)  
START-UP  
AND WAIT  
On power-up, provides a staggered  
start sequence to evenly apply the load controller from the configuration tool. Temperature control loops are  
This mode occurs on controller power-up, and after downloading to the  
to the electrical system. disabled.  
COOLING  
HEATING  
The Excel 10 is controlling the Cooling Space temperature has risen above the current cooling setpoint, or the  
mode. network input (DestHvacMode) is COOL.  
The Excel 10 is controlling the Heating Space temperature has fallen below the current heating setpoint, or the  
mode.  
network input (DestHvacMode) is HEAT.  
EMERGENCY Compressors are disabled and only  
The network input (DestManHvacMode) is EMERG_HEAT.  
HEAT  
Auxiliary Heat stages are allowed to  
operate.  
OFF MODE  
The heat/cool control is turned off  
Network input (DestManMode) containing AHU operational mode  
immediately. The node is not running its information from C-Bus has value of MORNING WARM-UP.  
normal temperature control.  
DISABLED  
MODE  
The heat/cool control and frost  
protection are turned off immediately.  
The node is not running its normal  
temperature control.  
SMOKE  
The node has entered a smoke  
Network input (DestEmergCmd) containing smoke control signal from  
EMERGENCY emergency. The fan and dampers are another LONWORKS Bus device has value of SMOKE_EMERG.  
then set to the conditions configured by  
SmkCtlMode. The control remains in  
SMOKE_ EMERGENCY until power is  
cycled or the node receives  
DestEmergCmd set to  
EMERG_NORMAL.  
FREEZE  
PROTECT  
The temperature control is set to HEAT The Window digital input detects an open window.  
with the setpoint set to the frost limit  
setpoint 46.4°F (8°C).  
MANUAL  
The physical outputs are being  
Typically this is done by the user through E-Vision or XBS by setting  
POSITION  
controlled manually. The temperature the point DestManMode to MANUAL mode.  
control loop is turned off.  
FAN ONLY  
DISABLED  
Control algorithm is disabled, except  
that the fan is turned on.  
The space temperature sensor has failed, or the network input  
(DestHvacMode) is FAN ONLY.  
Control algorithm is shut off.  
Network input (DestManMode) containing AHU operational mode  
information from an operator or the network that has a value of  
DISABLED.  
NOTE: During all modes all digital and analog physical  
inputs are periodically read, the diagnostic output  
network variables can be polled, the input network  
variables are received, and the output network  
variables are sent periodically.  
74-29581  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
APPLICATION STEPS  
EXCEL 10  
W7750  
CVAHU  
Overview  
CONTROLLER  
The seven application steps shown in Table 6 are planning  
considerations for engineering an Excel 10 W7750 System.  
These steps are guidelines intended to aid understanding of  
the product I/O options, bus arrangement choices,  
NOTEBOOK PC  
configuration options and the Excel 10 W7750 Controller role  
in the overall EXCEL 5000 OPEN SYSTEM architecture.  
SHIELDED  
INTERFACE  
CABLE  
EIA-232  
SERIAL  
PORT  
Table 6. Application Steps.  
Q7752A  
SLTA  
Step No.  
Description  
1
2
3
4
5
6
7
Plan The System  
CABLE  
PART  
NO. 205979  
LONWORKS BUS  
PORT  
Determine Other Bus Devices Required  
Lay Out Communications and Power Wiring  
Prepare Wiring Diagrams  
Order Equipment  
M15120A  
Fig. 18. Connecting the portable operator terminal  
to the LONWORKS® Bus.  
Configure Controllers  
Troubleshooting  
The FTT communication wiring, (LONWORKS Bus) between  
controllers is a free topology scheme that supports T-tap, star,  
loop, and mixed wiring architecture. Refer to the LONWORKS  
Bus Wiring Guidelines form, 74-2865 for complete description  
of network topology rules. See Application Step 3. Lay Out  
Communications and Power Wiring, for more information on  
bus wiring layout, and see Fig. 27 through 35 in Application  
Step 4. Prepare Wiring Diagrams, for wiring details.  
Step 1. Plan the System  
Plan the use of the W7750 Controllers according to the job  
requirements. Determine the location, functionality and sensor  
or actuator usage. Verify the sales estimate of the number of  
W7750 Controllers, T7770 and T7560 Wall Modules required  
for each model type. Also check the number and type of  
output actuators and other required accessories.  
The application engineer must review the Direct Digital  
Control (DDC) job requirements. This includes the Sequences  
of Operation for the W7750 units, and for the system as a  
whole. Usually there are variables that must be passed  
between the W7750 Controllers and other zone controller(s),  
or central plant controller(s) that are required for optimum  
system-wide operation. Typical examples are the TOD Occ/  
Unocc signal, the outdoor air temperature, the demand limit  
control signal, and the smoke control mode signal.  
When planning the system layout, consider potential  
expansion possibilities to allow for future growth. Planning is  
very important to be prepared for adding HVAC systems and  
controllers in future projects.  
T7560 Wall Modules can only be hard-wired, they have no  
LONWORKS Bus access. T7770 Wall Modules can be installed  
as either hard-wired I/O-only devices or additional wiring can  
be run to them (for the LONWORKS Bus network) to allow a  
CARE/E-Vision operator terminal to have access to the  
LONWORKS Bus. The application engineer needs to determine  
how many wall modules, T7770s and T7560s are required. All  
T7770 Wall Modules, except the T7770A1006 and the  
T7770A1014, can be connected via the LONWORKS Bus jack.  
Also the application engineer needs to know how many  
T7770s without LONWORKS Bus network connections are  
being installed on the job, and then clearly document which  
wall modules (if any) have network access. This information is  
required during installation to ensure that the proper number  
and type of wires are pulled to the wall modules, and the  
building operators are informed about where they can plug in  
to the LONWORKS Bus network with a portable operator  
terminal (see Fig. 18, 19 and 20). Refer to Step 4. Prepare  
Wiring Diagrams for details, about the about the wiring  
differences between the two types.  
It is important to understand these interrelationships early in  
the job engineering process to ensure implemention when  
configuring the controllers. (See Application Step 6. Configure  
Controllers, for information on the various Excel 10  
parameters and on Excel 10 point mapping.)  
Step 2. Determine Other Bus Devices  
Required  
A maximum of 62 nodes can communicate on a single  
LONWORKS Bus segment. Each W7750 (CVAHU) Controller  
constitutes one node. If more nodes are required, a Q7751A,B  
Router is necessary. Using a router allows up to 125 nodes,  
divided between two LONWORKS Bus segments. The router  
accounts for two of these nodes (one node on each side of the  
router); a Q7750A Excel 10 Zone Manager takes one node  
and two nodes are available for operator terminal nodes,  
leaving 120 nodes available for Excel 10 Controllers. All 120  
controllers are able to talk to each other through the router. A  
Q7750A Excel 10 Zone Manager is required to connect the  
LONWORKS Bus to the standard EXCEL 5000 OPEN  
System C-Bus. Each Excel 10 Zone Manager supports up to  
120 Excel 10 Controllers. This limit is set in the Excel 10 Zone  
Manager database as an absolute maximum.  
29  
74-29581  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Each LONWORKS Bus segment is set up with two unused  
nodes to allow for a CARE/E-Vision operator terminal to be  
connected to the LONWORKS Bus. Multiple CARE/E-Vision  
terminals can be connected to the LONWORKS Bus at the  
same time. Table 7 summarizes the LONWORKS Bus segment  
configuration rules.  
Table 7. LONWORKS® Bus Configuration Rules And Device Node Numbers.  
One LONWORKS Bus Segment Example  
One Q7750A Excel 10 Zone Manager 1 node  
Maximum Number of Nodes Equals 62  
Port for operator terminal access (CARE/E-Vision) 1 node  
Maximum number of Excel 10s 60 nodes  
Total 62 nodes  
Two LONWORKS Bus Segments Example  
Maximum Number of Nodes Equals 125  
One Q7750A Excel 10 Zone Manager 1 node  
One Q7751A,B Router 2 nodes (1 in each Bus Segment)  
Ports for operator terminal access (two CARE/E-Vision 2 nodes (1 in each Bus Segment)  
terminals)  
Maximum number of Excel 10s in segment number one 60 nodes  
Maximum number of Excel 10s in segment number two 60 nodes  
Total 125 nodes  
Refer to the LONWORKS Bus Wiring Guidelines form, 74-2865  
for complete description of network topology rules and the  
maximum wire length limitations. If longer runs are required, a  
Q7740A 2-Way or Q7740B 4-Way Repeater can be added to  
extend the length of the LONWORKS Bus. A Q7751A,B Router  
can be added to partition the system into two segments and  
effectively double the length of the LONWORKS Bus. Only one  
router is allowed with each Excel 10 Zone Manager, and each  
network segment can have a maximum of one repeater.  
pair, solid conductor wire. For nonplenum areas, use Level IV  
22 AWG (0.325 mm2), such as U.S. part AK3781 (one pair) or  
U.S. part AK3782 (two pair). In plenum areas, use plenum-  
rated Level IV, 22 AWG (0.325 mm2) such as U.S. part  
AK3791 (one pair) or U.S. part AK3792 (two pair). See Tables  
9 and 11 for part numbers. Contact Echelon Corp. Technical  
Support for the recommended vendors of Echelon approved  
cables. The FTT communications bus, LONWORKS Bus,  
supports a polarity insensitive, free topology wiring scheme  
that supports T-tap, star, loop, and mixed bus wiring.  
In addition, all LONWORKS Bus segments require the  
installation of a 209541B Termination Module for a singly  
terminated LONWORKS Bus or two 209541B Termination  
Modules for a doubly terminated LONWORKS Bus. For more  
details on LONWORKS Bus termination, refer to the LONWORKS  
Bus Wiring Guidelines form, 74-2865, or see Application Step  
3. Lay Out Communications and Power Wiring, and the  
LONWORKS Bus Termination Module subsection in Application  
Step 4.  
LONWORKS Bus networks can be configured in a variety of  
ways, so refer to the LONWORKS Bus Wiring Guidelines form,  
74-2865 for complete description of network topology rules  
and Table 7. Fig. 19 and 20 depict two typical LONWORKS Bus  
network topologies; One has only one doubly terminated  
LONWORKS Bus segment that has 60 nodes or less, and one  
showing two singly terminated LONWORKS Bus segments that  
has 120 nodes or less (60 MAX per each segment). The bus  
configuration is set up using the Network Manager tool from  
within CARE (see the CARE Excel 10 Zone Manager Users  
Guide, form 74-1392).  
Step 3. Lay Out Communications and Power  
Wiring  
NOTE: For wiring details see the LONWORKS Bus  
Termination Module subsection in Step 4. For wall  
module wiring, U.S. part AK3782 (non-plenum) or  
U.S. part AK3792 (plenum) can be used. For a  
LONWORKS Bus that is a doubly terminated daisy-  
chain, these cables contain two twisted pairs (one for  
the run down to the wall module, and one for the run  
back up to the controller) for ease of installation.  
LONWORKS® Bus Layout  
The communications bus, LONWORKS Bus, is a 78-kilobits per  
second (kbps) serial link that uses transformer isolation and  
differential Manchester encoding. Approved cable types for  
LONWORKS Bus communications wiring is Level IV 22 AWG  
(0.34 mm2) plenum or non-plenum rated unshielded, twisted  
74-29581  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
EXCEL 10  
CVAHU  
T7770  
209541B  
TERMINATION MODULES  
(AT ENDS OF  
LONWORKS BUS  
DAISY-CHAIN)  
LONWORKS BUS  
EXCEL 10  
CVAHU  
EXCEL 10  
VAV  
EXCEL 10  
VAV  
EXCEL 10  
VAV  
EXCEL 10  
CVAHU  
EXCEL 10  
Q7750A  
ZONE  
MANAGER  
T7770s  
WITH  
NO  
LONWORKS BUS  
ACCESS  
UP TO 60  
TOTAL NODES  
LONWORKS BUS  
TO C-BUS  
(SEE FIG. 1)  
EXCEL 10  
VAV  
EXCEL 10  
VAV  
EXCEL 10  
EXCEL 10  
CVAHU  
CVAHU  
T7770  
T7770  
JACK FOR  
OPERATOR  
TERMINAL  
T7770  
LONWORKS BUS  
I/O CONNECTIONS  
M17496  
T7770 OR T7560A,B  
Fig. 19. Wiring layout for one doubly terminated daisy-chain LONWORKS® Bus segment.  
31  
74-29581  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Do not use different wire types or gauges on the  
same LONWORKS Bus segment. The step change in  
line impedance characteristics causes unpredictable  
reflections on the bus. When using different types is  
unavoidable, use a Q7751A,B Router at the junction.  
In noisy (high EMI) environments, avoid wire runs  
parallel to noisy power cables, or lines containing  
lighting dimmer switches, and keep at least 3 in.  
(76 mm) of separation between noisy lines and the  
LONWORKS Bus cable.  
LONWORKS BUS  
SEGMENT NUMBER 1  
T7770  
EXCEL 10  
VAV  
EXCEL 10  
CVAHU  
EXCEL 10  
CVAHU  
Make sure that neither of the LONWORKS Bus wires  
is grounded.  
LONWORKS  
BUS  
ACCESS  
209541B  
TERMINATION  
MODULE  
209541B  
TERMINATION  
MODULE  
Power Wiring  
A power budget must be calculated for each Excel 10 W7750  
Controller to determine the required transformer size for  
proper operation. A power budget is simply the summing of  
the maximum power draw ratings (in VA) of all the devices to  
be controlled by an Excel 10 W7750 Controller. This includes  
the controller itself, the equipment actuators (ML6161, or  
other motors) and various contactors and transducers, as  
appropriate, for the Excel 10 configuration.  
LONWORKS BUS  
SEGMENT NUMBER 2  
Q7751A  
FTT  
LONWORKS  
BUS  
EXCEL 10  
VAV  
EXCEL 10  
VAV  
ROUTER  
EXCEL 10  
Q7750A  
ZONE  
TO C-BUS  
(SEE FIG. 1)  
MANAGER  
POWER BUDGET CALCULATION EXAMPLE  
The following is an example power budget calculation for a  
typical Excel 10 W7750B Controller.  
LONWORKS BUS  
SEGMENT NUMBER 2  
T7560A,B  
Assume a W7750 unit with a fan, two stages of D/X cooling,  
modulating steam valve for heating, and modulating  
economizer dampers. The power requirements are:  
EXCEL 10  
CVAHU  
EXCEL 10  
CVAHU  
EXCEL 10  
CVAHU  
DeviceVA  
Information Obtained from  
Excel 10 W7750B,C 12.0  
Controller  
W7750 Specification Data  
M17497  
Fig. 20. Wiring layout for two singly terminated  
ML6161  
Damper Actuator  
2.2  
21.0  
0.0  
TRADELINE  
Catalog  
LONWORKS® Bus segments.  
NOTE: See the LONWORKS Bus Termination Module section  
for wiring details.  
R8242A  
Contactor for fan  
TRADELINE  
Catalog in-rush rating  
IMPORTANT  
D/X Stages  
Notes on communications wiring:  
All field wiring must conform to local codes and ordi-  
nances or as specified on installation wiring dia-  
grams.  
NOTE: For this example, assume the cooling stage outputs  
are wired into a compressor control circuit and,  
therefore, have no impact on the power budget.)  
Approved cable types for LONWORKS Bus communi-  
cations wiring is Level IV 22 AWG (0.34 mm2) ple-  
num or non-plenum rated unshielded, twisted pair,  
solid conductor wire. For nonplenum areas, use  
Level IV 22 AWG (0.34 mm2), such as U.S. part  
AK3781 (one pair) or U.S. part AK3782 (two pair). In  
plenum areas, use plenum-rated Level IV, 22 AWG  
(0.34 mm2) such as U.S. part AK3791 (one pair) or  
U.S. part AK3792 (two pair). See Tables 9 and 11 for  
part numbers. Contact Echelon Corp. Technical Sup-  
port for the recommended vendors of Echelon  
approved cables.  
M6410A Steam  
Heating Coil Valve  
0.7  
TRADELINE  
Catalog, 0.32A at 24 Vac  
TOTAL:  
35.9 VA  
The Excel 10 System example requires 35.9 VA of peak  
power; therefore, a 40 VA AT72D Transformer is able to  
provide ample power for this controller and its accessories.  
Alternatively, a 75 VA AT88A Transformer could be used to  
power two Excel 10 Systems of this type, or a 100 VA AT92A  
Transformer could be used to power two of these Excel 10  
Systems and meet NEC Class 2 restrictions (no greater than  
100 VA). See Fig. 22 and 23 for illustrations of power wiring  
details. See Table 8 for VA ratings of various devices.  
Unswitched 24 Vac power wiring can be run in the  
same conduit as the LONWORKS Bus cable.  
74-29581  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Table 8. VA Ratings For Transformer Sizing.  
controller) and, therefore, has a secondary voltage of 22.9  
volts. (Use the lower edge of the shaded zone in Fig. 21 that  
represents the worst case conditions.) When the I x R loss of  
four volts is subtracted, only 18.9 volts reaches the controller,  
which is not enough voltage for proper operation.  
Device  
Description  
VA  
W7750A  
Excel 10 W7750 Controller  
Excel 10 W7750 Controllers  
6.0  
12.0  
2.2  
W7750B,C  
ML6161A/B Damper Actuator, 35 lb-in.  
In this situation, the engineer basically has three alternatives:  
1. Use a larger transformer; for example, if an 80 VA  
model is used, see Fig. 21, an output of 24.4 volts  
minus the four volt line loss supplies 20.4V to the  
controller. Although acceptable, the four-volt line-loss in  
this example is higher than recommended. See the  
following IMPORTANT.  
2. Use heavier gauge wire for the power run. 14 AWG (2.0  
mm2) wire has a resistance of 2.57 ohms per 1000 ft.  
which, using the preceding formula, gives a line-loss of  
only 1.58 volts (compared with 4.02 volts). This would  
allow a 40 VA transformer to be used. 14 AWG (2.0  
mm2) wire is the recommended wire size for 24 Vac  
wiring.  
3. Locate the transformer closer to the controller, thereby  
reducing the length of the wire run, and the line loss.  
The issue of line-loss is also important in the case of the  
output wiring connected to the Triac digital outputs. The  
same formula and method are used. The rule to  
remember is to keep all power and output wire runs as  
short as practical. When necessary, use heavier gauge  
wire, a bigger transformer, or install the transformer  
closer to the controller.  
R8242A  
M6410A  
MMC325  
ML684  
Contactor  
21.0  
0.7  
Valve Actuator  
Pneumatic Transducer  
Versadrive Valve Actuator  
Damper Actuator, 66 lb-in.  
Damper Actuator, 132 lb-in.  
Damper Actuator SR 50 lb-in.  
PWM Valve Actuator  
5.0  
12.0  
3.0  
ML6464  
ML6474  
ML6185  
ML7984B  
3.0  
12.0  
6.0  
For contactors and similar devices, the in-rush power ratings  
should be used as the worst case values when performing  
power budget calculations. Also, the application engineer  
must consider the possible combinations of simultaneously  
energized outputs and calculate the VA ratings accordingly.  
The worst case, that uses the largest possible VA load, should  
be determined when sizing the transformer.  
LINE LOSS  
Excel 10 Controllers must receive a minimum supply voltage  
of 20 Vac. If long power or output wire runs are required, a  
voltage drop due to Ohms Law (I x R) line loss must be  
considered. This line loss can result in a significant increase in  
total power required and thereby affect transformer sizing.  
The following example is an I x R line-loss calculation for a  
200 ft. (61m) run from the transformer to a W7750 Controller  
drawing 37 VA using two 18 AWG (1.0 mm2) wires.  
IMPORTANT  
No installation should be designed where the line  
loss is greater than two volts to allow for nominal  
operation if the primary voltage drops to 102 Vac  
(120 Vac minus 15 percent).  
To meet the National Electrical Manufacturers Association  
(NEMA) standards, a transformer must stay within the NEMA  
limits. The chart in Fig. 21 shows the required limits at various  
loads.  
The formula is:  
Loss = [length of round-trip wire run (ft.)] X [resistance in  
wire (ohms per ft.)] X [current in wire (amperes)]  
From specification data:  
18 AWG twisted pair wire has 6.52 ohms per 1000 feet.  
Loss = [(400 ft.) X (6.52/1000 ohms per ft.)] X  
[(37 VA)/(24V)] = 4.02 volts  
With 100 percent load, the transformer secondary must  
supply between 23 and 25 volts to meet the NEMA standard.  
When a purchased transformer meets the NEMA standard  
DC20-1986, the transformer voltage-regulating ability can be  
considered reliable. Compliance with the NEMA standard is  
voluntary.  
This means that four volts are going to be lost between the  
transformer and the controller; therefore, to assure the  
controller receives at least 20 volts, the transformer must  
output more than 24 volts. Because all transformer output  
voltage levels depend on the size of the connected load, a  
larger transformer outputs a higher voltage than a smaller one  
for a given load. Fig. 21 shows this voltage load dependence.  
The following Honeywell transformers meet this NEMA  
standard:  
Transformer Type  
AT20A  
VA Rating  
20  
AT40A  
AT72D  
AT87A  
40  
40  
50  
100  
In the preceding I x R loss example, even though the  
controller load is only 37 VA, a standard 40 VA transformer is  
not sufficient due to the line loss. From Fig. 21, a 40 VA  
transformer is just under 100 percent loaded (for the 37 VA  
AK3310 Assembly  
33  
74-29581  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
27  
26  
25  
24  
23  
22  
OUTPUT  
DEVICE  
POWER  
TRIAC LINES  
TO ACTUATORS  
AND CONTACTORS  
TRANSFORMER  
21  
20  
19  
18  
17  
16  
15  
14  
W7750B,C  
CONNECT POWER TO  
TERMINALS 24 AND 25  
2524 22 20  
200  
0
50  
100  
150  
% OF LOAD  
M993  
1
Fig. 21. NEMA class 2 transformer voltage output limits.  
Attach earth ground to W7750 Controller terminal 1. See Fig.  
22, 23 and 24, 27 through 35.  
EARTH  
M10089B  
GROUND  
Fig. 22. Power wiring details for one Excel 10 per  
transformer.  
See Fig. 23. for wiring more than one Excel 10 per  
transformer.  
TRANSFORMER  
24 VAC  
120/240 VAC  
W7750B,C  
W7750B,C  
W7750B,C  
2524  
2524  
2524  
1
1
1
M10090A  
EARTH  
GROUND  
EARTH  
GROUND  
EARTH  
GROUND  
Fig. 23. Power wiring details for two or more Excel 10s per transformer.  
IMPORTANT  
If the W7750 Controller is used on Heating and  
Cooling Equipment (UL 1995 U.S. only) devices  
and the transformer primary power is more than 150  
volts, connect the transformer secondary to earth  
ground, see Fig. 24.  
74-29581  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
To minimize EMI noise, do not run Triac output wires  
in the same conduit as the input wires or the LON-  
WORKS Bus communications wiring.  
24 VAC  
W7750  
Unswitched 24 Vac power wiring can be run in the  
same conduit as the LONWORKS Bus cable.  
Make earth ground connections with the shortest  
possible wire run using 14 AWG (2.0 mm2) wire. A  
good earth ground is essential for W7750 operation.  
Ideally, connect the earth ground to the ground bus  
at a motor control center or circuit breaker panel.  
However, if the nearest ideal earth ground is inac-  
cessible, consider an alternate source for earth  
ground. Metal water pipe is generally a good ground,  
but do not use sprinkler pipe if prohibited by local  
codes. Attention must be given when duct work, con-  
duit, or rebar are to be considered as ground  
sources. It is the responsibility of the installer to  
assure that these structures are tied back to a known  
earth ground.  
TRANSFORMER  
1
LINE VOLTAGE  
GREATER  
THAN 150 VAC  
EARTH  
GROUND  
1
EARTH  
GROUND  
1
IF THE W7750 CONTROLLER IS USED IN UL 1995 EQUIPMENT AND THE  
PRIMARY POWER IS MORE THAN 150 VOLTS, GROUND 24 VAC COM  
SIDE OF TRANSFORMER SECONDARY.  
M10088A  
Fig. 24. Transformer power wiring details for one Excel 10  
used in UL 1995 equipment (U.S. only).  
Step 4. Prepare Wiring Diagrams  
IMPORTANT  
Notes on power wiring:  
General Considerations  
All field wiring must conform to local codes and ordi-  
nances or as specified on installation wiring dia-  
grams.  
To maintain NEC Class 2 and UL ratings, the instal-  
lation must use transformers of 100 VA or less  
capacity.  
For multiple controllers operating from a single trans-  
former, the same side of the transformer secondary  
must be connected to the same input terminal in  
each controller (21 on the W7750A and 24 on the  
W7750B,C) and the ground terminals must be con-  
nected to a verified earth ground for each controller  
in the group. See Fig. 23. (Controller configurations  
are not necessarily limited to three devices per trans-  
former.)  
For the W7750B,C Controller (which has Triac out-  
puts), all output devices must be powered from the  
same transformer as the one powering the Excel 10  
W7750 Controller.  
The purpose of this step is to assist the application engineer in  
developing job drawings to meet job specifications. Wiring  
details are included for the W7750A,B,C Controllers and the  
T7770 and T7560A,B Wall Modules. The drawings detail I/O,  
power, and LONWORKS Bus communication wiring  
connections.  
NOTE: For field wiring, when two or more wires, other than  
14 AWG (2.0 mm2) are to be attached to the same  
connector block terminal, be sure to twist them  
together. Deviation from this rule can result in  
improper electrical contact. See Fig. 25.  
The connector block terminals on the W7750 Controllers and  
on the T7770 Wall Modules accept 14 through 22 AWG (2.0 to  
0.34 mm2) wire. The connector block terminals on the  
T7560A,B Wall Modules accept 18 through 22 AWG (1.0 to  
0.34 mm2) wire. Table 9 lists wiring types, sizes, and length  
restrictions for Excel 10 products.  
Use the heaviest gauge wire available, up to 14  
AWG (2.0 mm2) with a minimum of 18 AWG (1.0  
mm2) for all power and earth ground connections.  
35  
74-29581  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Table 9. Field Wiring Reference Table (Honeywell listed as AK#### or equivalent).  
Recommended  
Minimum Wire  
Specification  
or  
Requirement  
Wire  
Maximum Length ft.  
(m)  
Function Size AWG (mm2)  
Construction  
Vendor Wire Type  
Honeywell  
LONWORKS 22 AWG  
Twisted pair solid  
Level IV  
Refer to LONWORKS Bus  
(0.34 mm2)  
Bus  
(Plenum)  
conductor, nonshielded 140°F (60°C) AK3791 (one twisted pair) Wiring Guidelines for  
or Echelon approved  
rating  
AK3792 (two twisted pairs) maximum length  
cable.  
LONWORKS 22 AWG  
Bus (Non-  
Plenum)  
Twisted pair solid  
Level IV  
Honeywell Refer to LONWORKS Bus  
(0.34 mm2)  
conductor, nonshielded 140°F (60°C) AK3781 (one twisted pair) Wiring Guidelines for  
or Echelon approved  
cable.  
rating  
AK3782 (two twisted pairs) maximum length  
Input  
Wiring  
Sensors  
Contacts  
18 to 22 AWG  
Multiconductor (usually 140°F (60°C) Standard thermostat wire 1000 ft. (305m) for 18  
(1.0 to 0.34 mm2)  
five-wire cable bundle). rating  
For runs >200 ft. (61m)  
in noisy EMI areas, use  
shielded cable.  
AWG 200 ft. (61m) for 22  
AWG  
14 AWG (2.0 mm2)  
18 AWG (1.0 mm2)  
acceptable for  
Output  
Wiring  
Actuators  
Relays  
Any pair nonshielded  
(use heavier wire for  
longer runs).  
NEC Class 2 Honeywell  
140°F (60°C) AK3702 (18 AWG)  
Limited by line-loss  
effects on power  
consumption. (See Line  
Loss subsection.)  
rating  
AK3712 (16 AWG)  
AK3754 (14 AWG)  
short runs)  
14 AWG (2.0 mm2)  
Power  
Wiring  
Any pair nonshielded  
(use heavier wire for  
longer runs).  
NEC Class 2 Honeywell  
140°F (60°C) AK3754 (14 AWG) twisted effects on power  
Limited by line-loss  
rating  
pair AK3909 (14 AWG)  
consumption. (See Line  
single conductor  
Loss subsection.)  
W7750 Controllers  
JUMPER  
2
Fig. 27 through 35 illustrate W7750A,B,C Controller wiring for  
various configurations. Connections to the wall module  
terminals (2 through 6) and the communications terminals (14  
and 15) are made at terminal blocks. Connection for access to  
the LONWORKS Bus is provided by plugging the connector into  
the communications jack.  
Q38  
TERMINAL 24  
1
U3  
1.STRIP 1/2 IN. (13 MM)  
1/2  
(13)  
FROM WIRES TO  
BE ATTACHED AT  
ONE TERMINAL.  
J2  
2. TWIST WIRES  
TOGETHER WITH  
PLIERS (A MINIMUM  
OF THREE TURNS).  
1
2
J2 IS LOCATED NEAR TERMINAL 24 (COVER REMOVED).  
W7750B IS FACTORY-DELIVERED WITH JUMPER ON HIGH-SIDE  
(PINS CLOSEST TO TERMINAL BLOCK). LOW-SIDE PINS ARE TWO  
M16418A  
PINS CLOSEST TO Q38.  
Fig. 26. W7750B High-Side/Low-Side selectable switching  
and jumper location.  
3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM)  
BEFORE INSERTING INTO TERMINAL AND  
TIGHTENING SCREW. THEN PULL ON EACH  
WIRE IN ALL TERMINALS TO CHECK FOR  
NOTE: If an Excel 10 W7750A,B,C Controller or Zone  
Manager is not connected to a good earth ground,  
the controller internal transient protection circuitry is  
compromised and the function of protecting the  
controller from noise and power line spikes cannot  
be fulfilled. This can result in a damaged circuit  
board and require replacing the controller.  
GOOD MECHANICAL CONNECTION.  
M17207  
Fig. 25. Attaching two or more wires at terminal blocks.  
The W7750B provides a jumper to select High-Side or Low-  
Side switching of the digital outputs. Fig. 26 shows the  
W7750B High-Side/Low-Side selectable switching. (See  
wiring diagrams, Figs. 30 through 34.)  
See Table 10 for a description of the W7750A terminals.  
74-29581  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Table 10. W7750A Version I/O Description.  
Description  
Heat 1 (or Reversing Valve for a Heat Pump)  
Terminal  
DO6(W1)  
DO5(W2)  
DO4(Y1)  
DO3(Y2)  
DO2(G)  
DO1NET  
DO1NET  
Rc  
Terminal Number  
31  
30  
Heat 2 (or Aux. Heat for a Heat Pump)  
Cool 1 (or Compressor 1 for a Heat Pump)  
Cool 2 (or Compressor 2 for a Heat Pump)  
Fan  
29  
28  
27  
26  
Network Digital Output  
25  
Network Digital Output (connect to terminal number 22 +24Vac)  
Control power for relay contacts DO2 (G), DO3 (Y1) and DO4 (Y2)  
Control power for relay contacts DO5 (W1) and DO6 (W2)  
Power for the controller  
24  
Rh  
23  
+24Vac (H)  
COM (N)  
E-Bus  
22  
21  
Return for power to controller  
14 and 15  
Echelon communications (LONWORKS Bus) screw terminals  
Digital Input 2  
DI - 2  
12  
11  
10  
9
DGND  
Digital Ground  
DGND  
Digital Ground  
DI - 1  
Digital Input 1  
AGND  
8
Analog ground  
AI - 1 OHM  
SET PT  
GROUND  
SENSOR  
BYPASS  
LED  
7
Analog Input 1 (used for Discharge Air Temperature Sensor)  
Space temperature setpoint potentiometer  
Wall Module  
6
5
4
Space temperature sensor  
3
Space override button  
2
Space LED for indication of manual occupancy status  
Earth Ground  
EARTH GND 1  
IMPORTANT  
(OUT 5) DO5HEAT_STAGE_2  
If the W7750A controller is configured by E-Vision,  
the outputs may be assigned in different order than  
(OUT 6) DO6HEAT_STAGE_1  
DO7UNUSED  
the factory defaults. Use the Custom Wiring function  
of E-Vision to re-assign the outputs to the desired  
terminals.  
DO8UNUSED  
The Wall Module terminals are identical for the W7750A,B,C  
Models.  
The W7750B,C Versions are preconfigured with the same  
factory default setup as the W7750A Model; however, some  
terminals for wiring connections differ on the W7750B,C  
Models. See Fig. 30 for the terminal names on the W7750B  
Model and Fig. 35 for the terminal names on the W7750C  
Model. The factory default configuration of the digital output  
points on the W7750B,C Models follow (terminal names are  
from the W7750A):  
The W7750B,C Models offers two voltage/current sensor  
input terminals. When current-type sensors (4 to 20 mA) are  
configured, the W7750B,C automatically switches a 249 ohm  
resistor into the sensing circuit; so no external resistor is  
required. The W7750A Model does not support voltage or  
current inputs.  
NOTE: If using factory defaults, DI-2 input is configured for  
ScheduleMaster (nvoIO.SchedMaster). For a  
stand-alone unit, either connect an external time  
clock to terminals 9 and 10 or put a jumper on  
terminals 9 and 10 (using a jumper puts the  
controller in continuous occupied mode).  
FACTORY DEFAULT DIGITAL OUTPUTS:  
FREE 1 (OUT 1) DO1NETWORK DO  
(OUT 2) DO2SUPPLY FAN START/STOP  
(OUT 3) DO3COOL_STAGE_2  
(OUT 4) DO4COOL_STAGE_1  
37  
74-29581  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
HEAT 1  
HEAT 2  
COMP 1 COMP2  
HEAT 1 HEAT 2  
COMP 1  
COMP2  
LOAD AND  
CONTROLLER  
POWER  
3
LOAD POWER  
C
FAN  
FAN  
+
24 VAC  
24 VAC  
LINE AC  
-
H
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16  
CONTROLLER POWER  
NOT USED  
+
24 VAC  
-
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16  
NOT USED  
W7750A  
CONSTANT  
VOLUME AHU  
CONTROLLER  
W7750A  
CONSTANT  
VOLUME AHU  
CONTROLLER  
WALL MODULE  
1
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 J3  
2
WALL MODULE  
TIME CLOCK  
1
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 J3  
2
DISCHARGE  
AIR TEMP  
TIME CLOCK  
DISCHARGE  
AIR TEMP  
2
9
8
7
6
5
4
3
2
1
JACK FOR  
LONWORKS-BUS  
NETWORK  
ACCESS  
2
9
8
7
6
5
4
3
2
1
T7770C  
WALL  
MODULE  
JACK FOR  
LONWORKS-BUS  
NETWORK  
ACCESS  
1
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.  
USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2)  
WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.  
T7770C  
WALL  
MODULE  
2
3
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED  
TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.  
LOAD POWER WIRE CAN BE CONNECTED TO TERMINAL 22.  
M10085C  
1
2
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.  
USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2)  
WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.  
Fig. 27. Typical W7750A Controller AHU application  
wiring diagram. (For more information on note 2,  
refer to Fig. 25.)  
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED  
TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.  
M10084C  
Fig. 28. Typical W7750A Controller with separate  
transformer application wiring diagram.  
(For more information on note 2, refer to Fig. 25.)  
74-29581  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
NOTE: Digital outputs are configurable. The terminal  
locations for each function are user-selectable. The  
Network DO is configured to be economizer float  
close in this figure and W2 is configured to be  
economizer float open. Physical output terminal  
features are done in E-Vision by the custom wiring  
function.  
ML6161 FLOATING  
ACTUATOR  
CW COM CCW  
LOAD AND  
CONTROLLER  
POWER  
3
HEAT 1  
+
24 VAC  
-
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16  
NOT USED  
W7750A  
CONSTANT  
VOLUME AHU  
CONTROLLER  
WALL MODULE  
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 J3  
2
TIME CLOCK  
1
DISCHARGE  
AIR TEMP  
2
9
8
7
6
5
4
3
2
1
JACK FOR  
LONWORKS-BUS  
NETWORK  
ACCESS  
T7770C  
WALL  
MODULE  
1
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.  
USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2)  
WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.  
2
3
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED  
TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.  
LOAD POWER WIRE CAN BE CONNECTED TO TERMINAL 22.  
M10083C  
Fig. 29. W7750A Controller floating economizer damper  
wiring diagram. (For more information on note 2, refer to  
Fig. 25.)  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
74-29581  
 
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
TWO - OR THREE-WAY  
CHILLER WATER VALVE  
TWO - OR THREE-WAY  
HOT WATER/STEAM VALVE  
ECONOMIZER  
DAMPER  
HEAT  
STAGE 2 STAGE 1  
HEAT  
COOL  
COOL  
COOL  
COOL  
FAN  
STAGE 4 STAGE 3 STAGE 2 STAGE 1  
SERIES 60  
SERIES 60  
VALVE ACTUATOR  
VALVE ACTUATOR  
STEM  
DOWN  
STEM  
DOWN  
STEM  
UP  
STEM  
UP  
SERIES 60  
ACTUATOR  
COM  
COM  
4
CW COM CCW  
+
24 VAC  
-
+
24 VAC  
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16  
-
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16  
3
3
TRIAC EQUIVALENT CIRCUIT  
W7750B CONSTANT  
VOLUME AHU  
TRIAC EQUIVALENT CIRCUIT  
W7750B CONSTANT  
VOLUME AHU  
CONTROLLER  
WALL MODULE  
CONTROLLER  
WALL MODULE  
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 J3  
2
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 J3  
2
1
1
DISCHARGE  
AIR TEMP  
2
9
8
7
6
5
4
3
2
1
JACK FOR  
LONWORKS-BUS  
NETWORK  
ACCESS  
2
9
8
7
6
5
4
3
2
1
T7770C  
WALL  
MODULE  
JACK FOR  
LONWORKS-BUS  
NETWORK  
ACCESS  
1
2
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.  
T7770C  
WALL  
MODULE  
USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2)  
WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.  
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED  
TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.  
WIRING DIAGRAM SHOWS JUMPER (FOR J2) IN FACTORY DEFAULT  
HIGH-SIDE POSITION.  
3
4
1
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.  
USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2)  
WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.  
ISOLATING RELAYS MUST BE USED WHEN CONNECTING TO STAGED  
HEAT/COOL EQUIPMENT.  
2
3
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED  
TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.  
M10082D  
WIRING DIAGRAM SHOWS JUMPER (FOR J2) IN FACTORY DEFAULT  
M10081C  
HIGH-SIDE POSITION.  
Fig. 30. Typical W7750B Controller with staged heating  
and cooling wiring diagram. (For more information on  
note 2, refer to Fig. 25.)  
Fig. 31. W7750B Controller with floating heating, cooling  
and economizer wiring diagram. (For more information on  
note 2, refer to Fig. 25.)  
74-29581  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
WINDOWS CONTACTS  
(CONTACTS CLOSED  
EQUALS WINDOW  
CLOSED)  
ECONOMIZER  
DAMPER  
OCCUPANCY SENSOR  
(CONTACTS CLOSED  
EQUALS OCCUPIED)  
PWM ACTUATOR  
POWER  
4
SIGNAL  
SIG  
+
24V COM 24V  
24 VAC  
-
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16  
+
24 VAC  
-
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16  
3
TRIAC EQUIVALENT CIRCUIT  
W7750B CONSTANT  
VOLUME AHU  
3
TRIAC EQUIVALENT CIRCUIT  
W7750B CONSTANT  
VOLUME AHU  
CONTROLLER  
WALL MODULE  
CONTROLLER  
WALL MODULE  
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 J3  
2
1
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 J3  
2
DISCHARGE  
AIR TEMP  
1
OUTDOOR  
ENTHALPY RETURN  
ENTHALPY  
DISCHARGE  
AIR TEMP  
2
9
8
7
6
5
4
3
2
1
JACK FOR  
LONWORKS-BUS  
NETWORK  
ACCESS  
2
9
8
7
6
5
4
3
2
1
JACK FOR  
LONWORKS-BUS  
NETWORK  
ACCESS  
T7770C  
WALL  
MODULE  
T7770C  
WALL  
MODULE  
1
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.  
USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2)  
WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.  
1
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.  
USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2)  
WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.  
2
3
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED  
TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.  
2
3
4
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED  
TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.  
WIRING DIAGRAM SHOWS JUMPER (FOR J2) IN FACTORY DEFAULT  
HIGH-SIDE POSITION.  
M10079C  
WIRING DIAGRAM SHOWS JUMPER (FOR J2) IN FACTORY DEFAULT  
HIGH-SIDE POSITION.  
FOR WIRING DETAILS FOR PWM DEVICES, REFER TO DOCUMENTATION  
Fig. 33. W7750B,C wiring diagram with 4 to 20 mA  
enthalpy sensors and digital inputs. (For more  
information on note 2, refer to Fig. 25.)  
INCLUDED WITH PWM DEVICES.  
M10080C  
Fig. 32. W7750B,C Controller PWM damper actuator  
wiring diagram. (For more information on note 2, refer to  
Fig. 25.)  
41  
74-29581  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
WINDOWS CONTACTS  
(CONTACTS CLOSED  
EQUALS WINDOW  
CLOSED)  
TWO - OR  
TWO - OR  
ECONOMIZER  
DAMPER  
THREE-WAY  
HOT WATER/  
STEAM VALVE  
THREE-WAY  
CHILLER  
WATER VALVE  
OCCUPANCY SENSOR  
(CONTACTS CLOSED  
EQUALS OCCUPIED)  
FAN  
+
-
SERIES 70  
VALVE  
ACTUATOR  
SERIES 70  
VALVE  
ACTUATOR  
24 VAC  
ML7161  
3
24  
Vac  
T1  
2-10 4-20  
COM  
T2  
24  
IN-  
24  
IN-  
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16  
V
mA  
Vac COM PUT  
Vac COM PUT  
+
+
-
+
24 Vac  
-
3
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16  
TRIAC EQUIVALENT CIRCUIT  
W7750B CONSTANT  
VOLUME AHU  
CONTROLLER  
TRIAC EQUIVALENT  
CIRCUIT  
WALL MODULE  
W7750C CONSTANT  
VOLUME AHU  
CONTROLLER  
WALL MODULE  
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 J3  
2
HUMIDITY  
(4 TO 20 MA)  
1
C7600C  
+
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 J3  
DISCHARGE  
AIR TEMP  
2
1
2
2
9
8
7
6
5
4
3
2
1
9
8
7
6
5
4
3
2
1
JACK FOR  
LONWORKS-BUS  
NETWORK  
ACCESS  
JACK FOR  
LONWORKS-BUS  
NETWORK  
ACCESS  
T7770C  
WALL  
MODULE  
T7770C  
WALL  
MODULE  
1
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.  
USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2)  
WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.  
1
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.  
USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2)  
WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.  
2
3
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED  
TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.  
2
3
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED  
TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.  
IF AN ANALOG OUTPUT DEVICE HAS A SIGNAL COM (-) TERMINAL,  
CONNECT IT TO THE 24 VAC COM TERMINAL NUMBER 24.  
M16417B  
WIRING DIAGRAM SHOWS JUMPER (FOR J2) IN FACTORY DEFAULT  
HIGH-SIDE POSITION.  
Fig. 35. W7750C Controller with 4-to-20 mA heating,  
cooling and economizer wiring diagram. AOs must use  
terminals 16, 17 or 18. The AOs can be set to be reverse  
acting. (For more information on note 2, refer to Fig. 25.)  
M11619B  
Fig. 34. W7750B,C wiring diagram with C7600C 4 to 20 mA  
solid state humidity sensor. (For more information on  
note 2, refer to Fig. 25.)  
See Fig. 36 or 37 to wire a pneumatic transducer to a  
W7750B or W7750C.  
74-29581  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
MMC325 PNEUMATIC  
TRANSDUCER  
RP7517B PNEUMATIC TRANSDUCER  
M
PNEUMATIC  
VALVE  
ACTUATOR  
2
M
3
RP7517B  
B
500  
M
PNEUMATIC  
VALVE  
1
1
2
24 VAC  
+
-
+
-
24 VAC  
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16  
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16  
3
W7750C CONSTANT  
VOLUME AHU  
CONTROLLER  
4
W7750B,C CONSTANT  
VOLUME AHU  
CONTROLLER  
1
MAKE SURE ALL TRANSFORMER/POWER WIRING IS AS SHOWN;  
REVERSING TERMINATIONS RESULTS IN EQUIPMENT  
MALFUNCTION.  
1
ANALOG OUTPUTS FROM W7750C ARE 4 TO 20 mA SIGNALS. A 500 OHM  
1% TOLERANCE (OR BETTER) PRECISION RESISTOR IS REQUIRED TO  
DRIVE THIS (RP7517B) AND OTHER 2 TO 10V DEVICES. PLACE THIS  
RESISTOR AS CLOSE AS POSSIBLE TO THE DRIVEN DEVICE.  
2
3
OPTIONAL 24 VAC WIRING TO NEXT CONTROLLER.  
2
3
USE 1/4 IN (6 MM) PNEUMATIC TUBING. MINIMUM BRANCH LINE  
MUST BE 6 FT. (1.8M) OR LONGER.  
USE 1/4 IN (6 MM) PNEUMATIC TUBING. MINIMUM BRANCH LINE  
MUST BE 6 FT. (1.8M) OR LONGER.  
TERMINALS 16 TO 18 ARE ANALOG OUTPUTS (W7750C ONLY).  
M17368  
4
TERMINALS 16,17, 18 ARE ANALOG OUTPUTS (W7750C ONLY).  
M10078C  
Fig. 37. RP7517,B pneumatic transducer to W7750C.  
Fig. 36. Pneumatic transducer to W7750B,C  
(B shown, see triangle note 4).  
LONWORKS® Bus Termination Module  
To use the analog outputs on the W7750C with 2-to-10V  
actuators or transducers, a 500 ohm (1 percent or better  
tolerance) resistor must be placed across the 2-to-10V  
devices input and ground terminal. See Fig. 37. for an  
example. The resistor converts a 4 to 20 mA signal into a 2-to-  
10V signal.  
One 209541B Excel 10 FTT Termination Module is required  
for a singly terminated LONWORKS Bus segment. Two  
209541B Excel 10 FTT Termination Modules are required for  
a doubly terminated daisy-chain LONWORKS Bus segment  
(see Fig. 38). Refer to LONWORKS Bus Wiring Guidelines  
form, 74-2865 for termination module placement rules.  
NOTE: Wire the 500 ohm resistor physically as close as  
possible to the driven device. If the resistor is located  
far away from the driven device, it is possible that  
noise will be added onto the 2-to-10V signal to  
ground line. This noise could cause an actuator to re-  
position (jitter) and reduce the actuators life.  
For 209541B Excel 10 FTT Termination module placement  
and wiring options, see Fig. 39.  
43  
74-29581  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
W7750B, C  
W7750B, C  
W7750B, C  
1415  
1415  
1415  
ORANGE  
BROWN  
BROWN  
PART NO. 209541B  
TERMINATION  
MODULE  
PART NO. 209541B  
TERMINATION  
MODULE  
ORANGE  
M10519A  
Fig. 38. Typical doubly terminated daisy-chain LONWORKS® Bus segment termination module wiring diagram.  
74-29581  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
SINGLY  
TERMINATED SEGMENT  
TERMINAL BLOCK  
FOR Q7750A  
ZONE MANAGER  
W7750  
FIELD INSTALLED  
JUMPER  
3
INTERNAL  
4
PART NO. 209541B  
TERMINATION  
MODULE  
TERMINATION  
USE FOR DOUBLY  
LONWORKS BUS  
LONWORKS BUS  
5
6
7
8
NETWORK  
TERMINATED  
DAISY-CHAIN  
SEGMENT  
INTERNAL  
TERMINATION  
NETWORK  
FIELD INSTALLED JUMPER  
(A) Enabling Internal Termination Network using  
jumpers in the Q7750A Zone Manager  
LONWORKS BUS  
(B) Installing LONWORKS Bus  
Termination Module at W7750  
SEGMENTS  
LONWORKS BUS  
SWITCHES ON SIDE, UNDER  
Q7740A,B CIRCUIT BOARD.  
USE SMALL FLAT OBJECT TO  
MOVE THE SWITCHES  
A
C
B
D
AS NEEDED FROM  
PART NO. 209541B  
TERMINATION  
MODULE  
POSITION O (NO TERMINATION)  
POSITION I (SINGLY TERMINATED)  
POSITION II (DOUBLY TERMINATED)  
INSERT INTO TERMINALS 1 AND 2 WITH THE  
LONWORKS BUS WIRE. TERMINATION MODULE IS  
PHYSICALLY LOCATED BEHIND THE T7770  
INSIDE THE 2 X 4 OR 60 MM BOX.  
LABEL ON Q7740B 4 WAY REPEATER  
NOTE: Q7740B 4 WAY REPEATER SHOWN,  
Q7740A 2 WAY REPEATER HAS TWO SWITCHES.  
(D) LONWORKS Bus Termination network  
switches in the Q7740A, B Repeaters  
(C) LONWORKS Bus Termination Module installed  
at 2 x 4 or 60 mm box-mounted T7770  
Q7751A LONWORKS BUS  
ROUTER  
PART NO.  
209541B  
TERMINATION  
MODULE  
LONWORKS  
BUS  
RJ-45  
PLUG  
NTE2  
PART NO.  
209541B  
WIRE NUTS  
TERMINATION MODULE  
LONWORKS BUS  
(E) Installing LONWORKS Bus Termination  
Module at W7751H (terminals 11 and 12)  
(F) Twist wires and attach wire nuts to RJ-45 Adapter  
cables, LONWORKS Bus segment wires and Termination  
M11618A  
Module to connect to a Q7751A,B Router  
Fig. 39. LONWORKS® Bus termination wiring options.  
Step 5. Order Equipment  
After compiling a bill of materials through completion of the  
previous application steps, refer to Table 11 for ordering  
information. Contact Honeywell for information about  
Controllers and Wall Modules with no logo. See Table 11.  
Excel 10 W7750 Controller Ordering Information.  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
74-29581  
   
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Table 11. Excel 10 W7750 Controller Ordering Information.  
Product Description  
Part Number  
Comments  
Excel 10 W7750 Controllers:  
W7750A2005  
Constant Volume AHU Controller (W7750A)  
Three Analog Inputs, Three Digital Inputs and  
Six 24 Vac Relay Outputs  
W7750B2011  
W7750C2001  
Constant Volume AHU Controller (W7750B)  
Constant Volume AHU Controller (W7750C)  
Six Analog Inputs, Five Digital Inputs and Eight  
(High-side Low-side switchable)Triac Outputs  
Six Analog Inputs, Five Digital Inputs, Five Triac  
Outputs and Three Analog Outputs  
T7770 and T7560 Wall Modules:  
Sensor with Honeywell Logo  
Sensor with No Logo  
T7770A1006  
T7770A1014  
T7770A2004  
T7770A2012  
T7770B1004  
Used with Excel 5000 and Excel 10 Controllers  
Used with Excel 5000 and Excel 10 Controllers  
Sensor, LONWORKS Jack and Honeywell Logo Used with Excel 5000 and Excel 10 Controllers  
Sensor with LONWORKS Jack and No Logo  
Used with Excel 5000 and Excel 10 Controllers  
Degrees F Absolute  
Sensor with Setpoint and LONWORKS Jack,  
Honeywell Logo  
T7770B1046  
T7770B1012  
T7770B1020  
T7770B1053  
T7770B1038  
T7770C1002  
T7770C1044  
T7770C1010  
T7770C1028  
T7770C1051  
T7770C1036  
T7770D1000  
T7770D1018  
T7560A1018  
T7560A1016  
Sensor with Setpoint and LONWORKS Jack,  
Honeywell Logo  
Relative Setpoint  
Sensor with Setpoint and LONWORKS Jack, No Degrees F Absolute  
Logo  
Sensor with Setpoint and LONWORKS Jack,  
Honeywell Logo  
Degrees C Absolute  
Sensor with Setpoint and LONWORKS Jack, No Relative Setpoint  
Logo  
Sensor with Setpoint and LONWORKS Jack, No Degrees C Absolute  
Logo  
Sensor with Setpoint, Bypass/LED and  
LONWORKS Jack, Honeywell Logo  
Degrees F Absolute  
Sensor with Setpoint, Bypass/LED and  
LONWORKS Jack, Honeywell Logo  
Relative Setpoint  
Sensor with Setpoint, Bypass/LED and  
LONWORKS Jack, No Logo  
Degrees F Absolute  
Degrees C Absolute  
Relative Setpoint  
Sensor with Setpoint, Bypass/LED and  
LONWORKS Jack, Honeywell Logo  
Sensor with Setpoint, Bypass/LED and  
LONWORKS Jack, No Logo  
Sensor with Setpoint, Bypass/LED and  
LONWORKS Jack, No Logo  
Degrees C Absolute  
Sensor with Bypass/LED and LONWORKS Jack, Degrees F Absolute  
Honeywell Logo  
Sensor with Bypass/LED and LONWORKS Jack, Degrees C Absolute  
No Logo  
Digital Wall Module with Sensor, Setpoint and  
Bypass/LCD, Honeywell Logo  
Digital Wall Module with Sensor, Setpoint,  
Bypass/LCD and Humidity, Honeywell Logo  
Sensors:  
C7770A1006  
C7031J1050  
C7031B1033  
Air Temperature Sensor. 20 Kohm NTC  
nonlinearized  
Duct-mounted sensor that functions as a  
primary and/or secondary sensor.  
Averaging Discharge/Return Air Temperature Duct element cord length 12 ft. (3.7m).  
Sensor. 20 Kohm NTC  
Discharge Air or Hot Water Temperature  
Sensor. 20 Kohm NTC  
Use 112622AA Immersion Well.  
74-29581  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Table 11. Excel 10 W7750 Controller Ordering Information. (Continued)  
Part Number  
C7031C1031  
Product Description  
Comments  
18 in. (457mm) insertion length.  
Duct Discharge/Return Air Sensor. 20 Kohm  
C7031D1062  
C7031F1018  
C7031K1017  
C7100A1015  
C7170A1002  
Hot or chilled Water Temperature Sensor. 20  
Kohm NTC  
Outside Air Temperature Sensor. 20 Kohm  
NTC  
W7750B,C only  
Strap-on  
Hot or chilled Water Temperature Sensor. 20  
Kohm NTC  
Averaging Discharge/Return Air Temperature 13 in. (330mm) insertion length.  
Sensor. PT3000  
Outdoor Air Temperature Sensor. PT3000  
Echelon Based Components and Parts:  
Excel 10 Zone Manager  
Router  
Q7750A2003  
Q7751A2002  
Q7751B2000  
Q7752A2001  
Q7752A2009  
Q7740A1008  
Free Topology Tranceiver (FTT)  
(FTT)  
Router  
Twisted Pair Tranceiver (78 kbps) to FTT  
Serial Interface  
(FTT)  
(FTT)  
Serial Interface (PCMCIA card)  
Excel 10 2-Way Repeater  
Used to extend the length of the LONWORKS  
Bus. Contains built in termination modules.  
Q7740B1006  
Excel 10 4-Way Repeater  
Used to extend the length of the LONWORKS  
Bus. Contains built in termination modules.  
XD 505A  
XD 508  
Standard C-Bus Communications Submodule  
C-Bus Communications Submodule (1 megabit  
baud rate)  
209541B  
205979  
Termination Module  
One/two required per LONWORKS Bus segment  
Serial interface to wall module or controller  
Operator Terminal Cable for LONWORKS Bus  
Accessories (Sensors):  
EL7680A1008  
EL7628A1007  
Wall Mounted Wide View Infrared Occupancy  
Sensor  
Ceiling Mounted Infrared Occupancy Sensor  
EL7611A1003, EL7612A1001 Ultrasonic Occupancy Sensors  
EL7630A1003,  
EL7621A1002,  
EL7621A1010  
Power Supply/Control Units for Occupancy  
sensors  
C7242A1006  
CO Sensor/Monitor  
Use to measure the levels of carbon dioxide  
2
C7400A1004  
C7600B1000  
C7600C1008  
C7600C1018  
Solid State Enthalpy Sensor (4 to 20 mA)  
Solid State Humidity Sensor (2 to 10 V)  
Solid State Humidity Sensor (4 to 20 mA)  
Solid State Humidity Sensor (2 to 10 V)  
Accessories:  
For outdoor and return air enthalpy  
For outdoor and return air humidity  
For outdoor and return air humidity  
For outdoor and return air humidity  
MMC325-010, MMC325-020 Pneumatic Retrofit Transducers. Select  
pressure range: (010) 0 to 10 psi (68.97 kPa) or  
(020) 0 to 20 psi (137.93 kPa).  
Use to control Pneumatic reheat valves.  
MMCA530  
DIN rail adapter for MMC325 Transducers  
Metal enclosure for MMC325 Transducers  
MMCA540  
ML7984B3000  
ML6161B1000  
M6410A  
Valve Actuator Pulse Width Modulation (PWM) Use with V5011 or V5013 F and G Valves  
Damper Actuator Series 60  
Valve Actuator Series 60  
Use with V5852/V5853/V5862/V5863 Valves  
ML684A1025  
Versadrive Valve Actuator with linkage, Series Use with V5011 and V5013 Valves  
60  
47  
74-29581  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Table 11. Excel 10 W7750 Controller Ordering Information. (Continued)  
Product Description Comments  
Part Number  
ML6464A1009  
Direct Coupled Actuator, 66 lb-in. torque,  
Series 60  
ML6474A1008  
Direct Coupled Actuator, 132 lb-in. torque,  
Series 60  
ML6185A1000  
Direct Coupled Actuator, 50 lb-in. spring return Series 60  
V5852A/V5862A  
Two-way terminal unit water valve; 0.19, 0.29, Use with M6410 Valve Actuator. Close-off rating  
0.47, 0.74, 1.2, and 1.9 C 1/2 in. npt (13 mm) for 0.19 to 1.9 C is 65 psi; for 2.9 and 4.9, C is  
v
v
v
or 2.9 and 4.9 C 3/4 in. npt (19 mm)  
45 psi. (Coefficient of volume or capacity index  
v
C = gallons per minute divided by the square  
v
root of the pressure drop across the valve.)  
V5853A/V5863A  
R8242A  
Three-way mixing terminal unit hot water valve; Use with M6410 Valve Actuator. Close-off rating  
0.19, 0.29, 0.47, 0.74, 1.2, and 1.9 C 1/2 in. for 0.19 to 0.74 C is 55 psi; 1.2 and 1.9 C is 22  
v
v
v
npt (13 mm) or 2.9 and 4.9 C 3/4 in. npt (19  
psi; 2.9 and 4.9 C is 26 psi.  
v
v
mm)  
Contactor, 24 Vac coil, DPDT  
AT72D, AT88A, AK3310, etc. Transformers  
EN 50 022  
DIN rail 35 mm by 7.5 mm (1-3/8 in. by 5/16 in.) Obtain locally: Each controller requires 5 in.  
Two DIN rail adapters  
Obtain locally: Part number TKAD, from Thomas  
and Betts, two for each controller.  
Cabling:  
Serial Interface Cable, male DB-9 to female  
DB-9 or female DB-25.  
Obtain locally from any computer hardware  
vendor.  
LONWORKS Bus (plenum): 22 AWG (0.34 mm2)  
twisted pair solid conductor, nonshielded or  
Echelon approved cable.  
Honeywell  
AK3791 (one twisted pair)  
AK3792 (two twisted pairs)  
Level IV 140°F (60°C) rating  
Honeywell AK3781 (one  
twisted pair) AK3782 (two  
twisted pairs)  
LONWORKS Bus (nonplenum): 22 AWG (0.34  
mm2) twisted pair solid conductor, nonshielded  
or Echelon approved cable.  
Level IV 140°F (60°C) rating  
Inputs: 18 AWG (1.0 mm2) five wire cable  
bundle  
Outputs/Power: 14 to 18 AWG (2.0 to 1.0 mm2)  
Honeywell AK3725  
Standard thermostat wire  
NEC Class 2 140°F (60°C) rating  
Non-plenum  
Honeywell AK3752 (typical or  
equivalent)  
18 AWG (1.0 mm2) twisted pair  
Honeywell AK3702 (typical or  
equivalent)  
16 AWG (1.3 mm2) twisted pair  
Honeywell AK3712 (typical or  
equivalent)  
Non-plenum  
14 AWG (2.0 mm2) two conductor  
Honeywell AK3754 (typical or  
equivalent)  
Non-plenum  
is printed on the terminal labels. Also see the wiring details in  
Fig. 27 in Step 4, Prepare Wiring Diagrams. The labeled I/O  
terminals are defined in Table 10.  
Step 6. Configure Controllers  
Excel E-Vision PC Software is used to configure W7750  
Controllers to match their intended application. The E-Vision  
User Guide, form number 74-2588 provides details for  
operating the PC software.  
Step 7. Troubleshooting  
W7750 Controllers are shipped from the factory with a default  
hardware configuration. On power-up, the controller  
configuration parameters are set to the default values listed in  
Table 20 in Appendix C. The controller can operate normally  
in this mode (if the equipment and wiring match the default  
setup), and given valid sensor inputs, the outputs are  
Troubleshooting Excel 10 Controllers and Wall  
Modules  
In addition to the following information, refer to the Installation  
Instructions and Checkout and Test manual for each product.  
Most products have a Checkout and Test section in their  
Installation Instructions manual. If not, look for a separate  
Checkout and Test manual. See the Applicable Literature  
section for form numbers.  
controlled appropriately to maintain space temperature at the  
default setpoint. The default I/O arrangement for the W7750A  
74-29581  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
1. Check the version numbers of the controller firmware,  
E-Vision and the E-Vision script.  
2. Check the wiring to the power supply and make sure  
there is a good earth ground to the controller.  
3. Check the occupancy and HVAC modes.  
4. Compare the current actual setpoint with the actual  
space temperature.  
5. Check the desired configuration settings.  
6. Check the network wiring and type of wire used.  
7. Check the Zone Manager mapping and referred points.  
80K  
70K  
60K  
50K  
40K  
30K  
20K OHM AT  
20K  
77oF (25oC)  
NOTE: If the fan shuts off periodically for no specific reason  
and the controller restarts the fan by itself after about  
20 to 60 seconds, the cause could be a bad Air Flow  
switch. If the controller has a digital input assigned  
as a Proof of Air Flow input, try unconfiguring this  
digital input to see if these shutdowns continue. If  
not, adjust or replace the Air Flow switch to get it  
working.  
10K  
110 oF  
40  
80  
100  
30  
0
40  
50  
10  
TEMPERATURE (DEGREES)  
60  
70  
90  
oC  
20  
30  
AIR TEMPERATURE SENSOR  
10K OHM SETPOINT POT  
RESISTANCE VALUES  
M11620  
Temperature Sensor and Setpoint Potentiometer  
Resistance Ranges  
Fig. 40. Temperature sensor resistance plots.  
The T7770 or T7560A,B Wall Modules or the C7770A Air  
Temperature Sensor has the following specified calibration  
points, which are plotted in Fig. 40:  
Alarms  
When an Excel 10 has an alarm condition, it reports it to the  
central node on the LONWORKS Bus (typically, the Excel 10  
Zone Manager). See Table 12. Information contained in an  
alarm message is:  
Temperature (°F)  
Resistance Value (ohms)  
98  
80  
70  
60  
42  
11755  
18478  
24028  
31525  
52675  
Subnet Number:  
LONWORKS Bus subnet that contains the Excel 10 node  
that has the alarm condition. Subnet 1 is on the Zone  
Manager side of the router; Subnet 2 is on the other  
side.  
The T7770 Wall Module setpoint potentiometers have the  
following calibration points:  
Node Number:  
Temperature (°F)  
Resistance Value (ohms)  
Excel 10 node that has the alarm condition (see  
Network Alarm).  
Alarm Type:  
85  
70  
55  
1290  
5500  
9846  
Specific alarm being issued. An Excel 10 can provide  
the alarm types listed in Table 12.  
.
Table 12. Excel 10 Alarms.  
Alarm type  
number  
Name of alarm or error bit  
Meaning of alarm code or error bit  
RETURN_TO_NORMAL  
128U  
Return to no alarm after being in an alarm condition. This code is added  
numerically to another alarm code to indicate that the alarm condition has  
returned to normal.  
ALARM_NOTIFY_DISABLED  
255U  
The alarm reporting was turned off by DestManMode. No more alarms are  
reported until DestManMode turns on alarm reporting or on application restart.  
NO_ALARM  
0
1
No alarms presently detected.  
INPUT_NV_FAILURE  
One or more NV inputs have failed in receiving an update within their specified  
FAILURE_DETECT_TIME.  
NODE_DISABLED  
2
The control algorithm has stopped because the controller is in  
DISABLED_MODE, MANUAL or FACTORY_TEST mode. No more alarms are  
reported when the controller is in the DISABLED_MODE. Alarms continue to be  
reported if the controller is in the MANUAL or FACTORY_TEST mode.  
SENSOR_FAILURE  
3
4
One or more sensors have failed.  
FROST_PROTECTION_ALARM  
The space temperature is below the frost alarm limit 42.8°F (6°C) when the  
mode is FREEZE_PROTECT. The alarm condition remains until the temperature  
exceeds the alarm limit plus hysterisis.  
INVALID_SET_POINT  
5
One of the setpoints is not in the valid range.  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
74-29581  
       
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Table 12. Excel 10 Alarms. (Continued)  
Alarm type  
number  
Name of alarm or error bit  
Meaning of alarm code or error bit  
LOSS_OF_AIR_FLOW  
6
The Fan Status DI indicates that there is no air flow when the node is  
commanding the fan to run. The control is shut down and disabled until power is  
cycled or the node is reset. See NOTE below. The alarm is not issued until  
FanFailTime seconds have elapsed since the loss-of-flow condition was first  
reported  
DIRTY_FILTER  
SMOKE_ALARM  
IAQ_OVERRIDE  
7
8
9
The pressure drop across the filter exceeds the limit and the filter requires  
maintenance. The control runs normally.  
The smoke detector has detected smoke and the node has entered an  
emergency state.  
The indoor air quality sensor has detected that the indoor air quality is less than  
the desired standard and additional outdoor air is being brought into the  
conditioned space.  
LOW_LIM_ECON_CLOSE  
10  
The economizer has to close beyond the minimum position to prevent the  
discharge air temperature from going below the discharge temperature low limit.  
NOTE: The node can be reset by switching the node to  
MANUAL and then to the normal operating mode  
(see Fan Operation in Appendix B).  
The commissioning tool is used to perform the ID Assignment  
task (see the E-Vision Users Guide, form 74-2588).  
Also, the Excel 10 variables, AlarmLogX where X is 1 through  
5, that store the last five alarms to occur in the controller, are  
available. These points can be viewed through XBS or  
E-Vision.  
SERVICE  
PIN  
BUTTON  
Certain alarm conditions are suppressed conditionally as  
follows:  
Broadcasting the Service Message  
The Service Message allows a device on the LONWORKS Bus  
to be positively identified. The Service Message contains the  
controller ID number and, therefore, can be used to confirm  
the physical location of a particular Excel 10 in a building.  
There are three methods of broadcasting the Service  
Message from an Excel 10 W7750 Controller. One uses a  
hardware service pin button on the side of the controller (see  
Fig. 41). The second uses the wall module pushbutton (see  
Fig. 43 and 44). By pressing the wall module pushbutton for  
more than four seconds, the controller sends out the Service  
Message. The third involves using the PC Configuration tool,  
as follows.  
M10094  
Fig. 41. Location of the Service Pin Button.  
W7750 Controller Status LED  
When an Assign ID command is issued from the  
commissioning tool, the node goes into the  
The LED on the front and center of a W7750 Controller  
provides a visual indication of the status of the device. See  
Fig. 42. When the W7750 receives power, the LED should  
appear in one of the following allowable states:  
SERVICE_MESSAGE mode for five minutes. In the  
SERVICE_MESSAGE mode, pressing the Occupancy  
Override button on the remote wall module (refer to Fig. 43  
and 44 for override button location) causes the Service  
Message to be broadcast on the network. All other functions  
are normal in the SERVICE_MESSAGE mode. Even if an  
Excel 10 W7750 Controller does not have an Override button  
connected, it can broadcast the Service Message on the  
network by temporarily shorting the Controller Bypass Input  
terminal to the Sensor Ground terminal on the W7750A,B,C  
(short terminals 3 and 5).  
1. Offno power to the processor.  
2. Continuously Onprocessor is in initialized state.  
3. Slow Blinkcontrolling, normal state.  
4. Fast Blinkwhen the Excel 10 has an alarm condition.  
74-29581  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Press and release the bypass pushbutton, located on the  
T7560A,B Digital Wall Modules in Fig. 44 for more than one  
second to cause the sun symbol on the bottom right side of  
the LCD display to appear. Pressing the bypass pushbutton  
for more than four seconds causes the controller, hard-wired  
to the T7560A,B, to go into continuous unoccupied override.  
The T7560A,B displays the moon symbol.  
W7750  
31  
3
0
2
9
2
8
2
7
2
6
2
5
2
VA  
24  
COM  
4
C
2
3
2
2
2
1
2
0
DI-4  
D
GN  
I
D
1
9
1
8
DI  
-3  
1
7
DI-2  
DI  
GN  
VA  
C
1
6
DI-1  
D
1
OUT  
24  
2
3
OUT  
4
OUT  
OUT  
5
OUT  
6
OUT  
7
OUT  
8
OUT  
BYPASS  
PUSHBUTTON  
E
GND  
LED  
BYP  
ASS  
SNSR  
AI  
GN  
SET PT  
AI-1  
OHM  
D
AI  
A1-2  
OHM  
AI-3  
V/mA  
GN  
D
AI  
AI-4  
V/mA  
20VDC  
OUT  
GN  
D
1
LO  
NW  
OR  
KS  
2
3
LO  
N
4
5
6
-B  
US  
JA  
CK  
7
8
9
1
0
1
1
1
2
1
3
1
4
1
5
J
3
STATUS  
LED  
M10095A  
Fig. 42. LED location on W7750.  
M17500  
T7770C,D Wall Module Bypass Pushbutton and  
Override LED  
Fig. 44. The T7560A,B Digital Wall Module Bypass  
pushbutton location.  
Pressing the bypass pushbutton, located on the T7770C,D  
Wall Modules in Fig. 43, causes the override LED to display  
the Manual Override mode of the controller. The modes are:  
APPENDICES  
Appendix A. Using E-Vision to Commission a  
W7750 Controller.  
T7770C  
T7770D  
NOTE: When commissioning a CVAHU W7750 Controller,  
E-Vision first checks that the actual hardware model  
(such as W7750A,B,C) is the same type which was  
selected from the Application Selection/Output tab. If  
the types do not match, the download does not occur  
and the user-entered values in the Application  
6
5
7
0
6
0
7
5
OVERRIDE  
LED  
OVERRIDE  
LED  
5
5
8
0
8
5
BYPASS  
PUSHBUTTON  
Selection screens all revert back to default values.  
Sensor Calibration  
The space temperature, the optional resistive and voltage/  
current (W7750B,C only) inputs can all be calibrated. The wall  
module setpoint potentiometer can not be calibrated.  
BYPASS  
PUSHBUTTON  
M11617  
Perform the sensor calibration by adding an offset value  
(either positive or negative) to the sensed value using  
E-Vision menus (see E-Vision user guide, form number  
74-2588).  
Fig. 43. The T7770C,D Wall Modules LED and Bypass  
pushbutton locations.  
1. LED = Off. No override active.  
2. LED = Continuously on. Bypass mode (timed Occupied  
override).  
3. LED = One flash per second. Continuous Unoccupied  
override.  
4. LED = Two flashes per second. Remote only, continu-  
ous Occupied override.  
When calibrating voltage/current sensors on the (W7750B,C),  
the offset amount entered by the user is in volts, regardless of  
the inputs actual engineering units. See Appendix E for  
information on how to derive the proper voltage value to enter  
as an offset during calibration.  
Setting the Pid Parameters  
T7560A,B Digital Wall Module Bypass Pushbutton  
and LCD Display Occupancy Symbols  
See Fig. 44 for the T7560A,B Digital Wall Module bypass  
pushbutton location.  
The W7750 is designed to control a wide variety of  
mechanical systems in many types of buildings. With this  
flexibility, it is necessary to verify the stability of the  
temperature control in each different type of application.  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
74-29581  
                 
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Occasionally, the PID parameters require tuning to optimize  
comfort and smooth equipment operation. This applies to the  
W7750A,B,C Controllers.  
lists some recommended values to use as a starting point.  
These recommended values are based on past experience  
with the applications and in most cases do not require further  
adjustment.  
CVAHU Controllers are configured by E-Vision with default  
values of PID parameters as shown in Appendix C Table 21. If  
different values for these parameters are desired, Table 13  
Table 13. Recommended Values For PID Parameters.  
Heat Heat  
Prop. Integ.  
Gain Gain  
Heat  
Deriv.  
Gain  
Heat  
Control Prop.  
Band  
Cool  
Cool  
Integ.  
Cool  
Deriv.  
Gain  
Cool  
Control Control  
Band  
10  
Econ  
Equipment Configuration  
Single Stage  
Gain  
Gain  
3000  
2000  
1500  
1000  
750  
Band  
10  
2
3
3000  
2000  
1500  
1000  
750  
0
0
0
0
0
0
10  
2
0
0
0
0
0
0
Two Stages  
10  
3
10  
10  
Three Stages  
4.5  
6
10  
4.5  
6
10  
10  
Four Stages  
10  
10  
10  
Series 60 Modulating (Floating)  
PWM Modulating  
2
10  
2
10  
10  
2
900  
10  
2
900  
10  
10  
If the PID parameters require adjustment away from these  
values, use caution to ensure that equipment problems do not  
arise (see CAUTION below). If any change to PID control  
parameters is made, the adjustments should be gradual. After  
each change, the system should be allowed to stabilize so the  
effects of the change can be accurately observed. Then  
further refinements can made, as needed, until the system is  
operating as desired.  
The Derivative Gain (also called Derivative Time)  
determines how much impact the error rate has on the  
output signal. The error rate is how fast the error value is  
changing. It can also be the direction the space  
temperature is going, either toward or away from the  
setpoint, and its speedquickly or slowly. A decrease in  
Derivative Gain causes a given error rate to have a larger  
effect on the output signal.  
The Control Band is used only for discharge temperature  
control of modulating outputs, which includes controlling  
the economizer dampers, and heating and cooling valves  
using Cascade Control. The Control Band dictates the  
span through which the discharge temperature must travel  
to cause the output signal to go from fully closed to fully  
open. Also, 10 percent of the Control Band value is the size  
of the deadband around the setpoint where no actuator  
motion occurs. For example, if controlling a cooling valve  
with Cascade Control enabled and with the discharge  
temperature within 0.1 X DaTempClCtrlBd of the discharge  
setpoint, there is no change in the current valve position.  
The smaller the Control Band, the more responsive the  
control output. A larger Control Band causes more sluggish  
control. Be careful not to set the Control Band too low and  
cause large over or under shoots (hunting). This can  
happen if the space or discharge sensors or wiring are in  
noisy environments and the value reported to the controller  
is not stable (such that it bounces). The Control Band is  
used only in modulating control, and has no purpose when  
staged control is configured.  
CAUTION  
If large or frequent changes to PID control parameters  
are made, it is possible to cause equipment problems  
such as short cycling compressors (if the stage  
minimum run times were disabled in User Addresses  
DisMinClTime or DisMinHtTime). Other problems that  
can occur include wide swings in space temperature  
and excessive overdriving of modulating outputs.  
If adjustment of PID parameters is required, use the following.  
In the items that follow, the term, error, refers to the difference  
between the measured space temperature and the current  
actual space temperature setpoint.  
The Proportional Gain (also called Throttling Range)  
determines how much impact the error has on the output  
signal. Decreasing the Proportional Gain amplifies the  
effect of the error; that is, for a given error, a small  
Proportional Gain causes a higher output signal value.  
The Integral Gain (also called Integral Time) determines  
how much impact the error-over-time has on the output  
signal. Error-over-time has two components making up its  
value: the amount of time the error exists; and the size of  
the error. The higher the Integral Gain, the slower the  
control response. In other words, a decrease in Integral  
Gain causes a more rapid response in the output signal.  
Appendix B. Sequences of Operation.  
This Appendix provides the control sequences of operation for  
the models of the Excel 10 W7750 CVAHU Controller. The  
W7750A,B,C Controllers can be configured to control a wide  
variety of possible equipment arrangements. Table 14 and 15  
(copied from Tables 3 and 4) summarize the available options.  
This Appendix provides a more detailed discussion of these  
options.  
74-29581  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
NOTE: Each W7750 Controller must have a space  
temperature sensor input either wired directly to the  
controller, or shared from another LONWORKS Bus  
device, and must have a digital output configured for  
controlling the supply fan. In addition, if modulating  
economizer control is desired, a discharge air  
temperature sensor must be physically connected to  
the Excel 10 W7750 Controller. A discharge  
Common Operations  
The Excel 10 W7750 Controller applications have many  
common operations that are applicable regardless of the type  
of heating, cooling, or economizer equipment configuration.  
These operations are available to the W7750A and the  
W7750B,C Versions of the CVAHU Controller, and the I/O and  
network configurations for them are summarized in Table 14.  
temperature signal cannot be brought into the  
controller through the LONWORKS Bus network.  
Available input options are from the wall module and the  
hard-wired analog and digital inputs. Each application can  
have only a subset of these devices configured based on the  
number of physical I/O points available. However, some of the  
inputs are available over the LONWORKS Bus network.  
Table 14. Common Configuration Options Summary For W7750A,B,C Controllers.  
Option  
Possible Configurations Common To All W7750 Models  
1. Mandatory Digital Output.  
1. Conventional.  
Supply Fan  
Type of Air Handler  
2. Heat Pump.  
Occupancy Sensor  
Window Sensor  
1. None.  
2. Connected: Contacts closed equals Occupied.  
3. Network (Occ/Unocc signal received via the LONWORKS Bus network).  
1. None.  
2. Physically Connected: Contacts closed equals window closed.  
3. Network (Window Open/Closed signal received via the LONWORKS Bus).  
1. Local (direct wired to the controller).  
Wall Module Option  
(The T77560A,B has no LONWORKS Bus access) 2. Network (sensor value received via the LONWORKS Bus).  
Wall Module Type  
1. Sensor only.  
(All wall modules have a LONWORKS Bus access  
jack except T7560A,B)  
2. Sensor and Setpoint adjust.  
3. Sensor, Setpoint adjust and Bypass.  
4. Sensor and Bypass.  
Smoke Emergency Initiation  
1. None.  
2. Physically Connected: Contacts closed equals smoke detected.  
3. Network (Emergency/Normal signal received via the LONWORKS Bus).  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
74-29581  
   
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Table 15. Configuration Options Summary For W7750A,B,C Controllers.  
Possible Configurations for the  
W7750A Model  
Option  
Type of  
Possible Configurations for the W7750B,C Models  
1. One stage.  
1. One stage.  
2. Two stages.  
3. Three stages.  
4. Four stages.  
5. None.  
Heating  
2. Two stages.  
3. Three stages.  
4. Four stages.  
5. Series 60 Modulating electric valve, or pneumatic via transducer.  
6. Pulse Width Modulating electric valve, or pneumatic via transducer.  
7. None.  
Type of  
Cooling  
1. One stage.  
2. Two stages.  
3. Three stages.  
4. Four stages.  
5. None.  
1. One stage.  
2. Two stages.  
3. Three stages.  
4. Four stages.  
5. Series 60 Modulating electric valve, or pneumatic via transducer.  
6. Pulse Width Modulating electric valve, or pneumatic via transducer.  
7. None.  
Type of  
Economizer  
1. Digital Output Enable/Disable  
signal for controlling an external  
economizer package.  
1. Digital Output Enable/Disable signal for controlling an external  
economizer package.  
2. Series 60 Modulating electric  
damper motor, or pneumatic via  
transducer.  
2. Series 60 Modulating electric damper motor, or pneumatic via  
transducer.  
3. None.  
3. Pulse Width Modulating electric damper motor, or pneumatic via  
transducer.  
4. None.  
1. None.  
IAQ Option  
1. None.  
2. Local IAQ Digital Inputdirectly  
wired to the controller. (Contacts  
closed means poor IAQ is  
detected.)  
2. Local IAQ Digital Inputdirectly wired to the controller. (Contacts  
closed means poor IAQ is detected.)  
3. Network (IAQ Override signal  
received via the LONWORKS Bus).  
3. Network (IAQ Override signal received via the LONWORKS Bus).  
4. Local CO2 Analog Inputdirectly wired to the controller. (The sensor  
must be a 0 to 10V device representing 0 to 2000 PPM CO2.)  
Coil Freeze  
Stat Option  
1. None.  
1. None.  
2. Local Coil Freeze Stat Digital  
2. Local Coil Freeze Stat Digital Inputdirectly wired to the controller.  
Inputdirectly wired to the controller. (Contacts closed means that coil freeze condition is sensed.)  
(Contacts closed means that coil  
freeze condition is sensed.)  
Filter Monitor 1. None.  
1. None.  
Option  
2. Local Dirty Filter Digital  
2. Local Dirty Filter Digital Inputdirectly wired to the controller.  
Inputdirectly wired to the  
controller. (Contacts closed means  
that the filter is dirty.)  
(Contacts closed means that the filter is dirty.)  
3. Local Analog Input for Differential Pressure across the Filter (directly  
wired to the controller). The sensor must be a 2 to 10V device  
representing 0 to 5 inw (1.25 kPa).  
ROOM TEMPERATURE SENSOR (RmTemp)  
LONWORKS Bus device. If no valid room temperature value is  
available to the W7750 Controller, the temperature control  
algorithm in the controller is disabled, causing the heating,  
cooling, and economizer control outputs to be turned off. If the  
W7750 Controller is configured for Continuous Fan (rather  
This is the room space temperature sensor. This sensor is the  
T7770 or the T7560A,B Wall Module. When it is configured, it  
provides the temperature input for the W7750 temperature  
control loop. If it is not configured, it is required that a room  
temperature sensor value be transmitted from another  
74-29581  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
than Intermittent Fan (see Fan Operation in this Appendix),  
and the mode is Occupied when the RmTemp value becomes  
invalid, the fan continues to run.  
OverrideType  
OverrideType specifies the behavior of the override button on  
the wall module. There are three possible states that have the  
following meanings:  
REMOTE SETPOINT (RmtStptPot)  
This is the Setpoint Potentiometer contained in the T7770 or  
the T7560A,B Wall Module. When configured, this occupant  
value is set to calculate the actual cooling or heating  
Occupied Setpoint. There are two options for how to calculate  
the actual setpoint to be used by the temperature control  
algorithm: (Offset) and (Absolute Middle). When SetPtKnob is  
set to Offset, the Wall Module setpoint knob represents a  
number from -9° to +9°F (-5° to +5°C) which is added to the  
software occupied setpoints for the heat and the cool modes  
(CoolOccSpt and HeatOccSpt). When SetPtKnob is set to  
Absolute Middle, the setpoint knob becomes the center of the  
Zero Energy Band (ZEB) between the cooling and heating  
occupied setpoints. The size of the ZEB is found by taking the  
difference between the software heating and cooling occupied  
setpoints; therefore, for Absolute Middle, the actual setpoints  
are found as follows:  
NONE disables the override button.  
NORMAL causes the override button to set the OverRide  
state to OC_BYPASS for BypassTime (default 180  
minutes), when the override button has been pressed  
for approximately 1 to 4 seconds, or to set the OverRide  
state to UNOCC when the button has been pressed for  
approximately 4 to 7 seconds. When the button is  
pressed longer than approximately 7 seconds, then the  
OverRide state is set to OC_NUL (no manual override is  
active).  
BYPASS_ONLY causes the override button to set the  
OverRide state to OC_BYPASS for BypassTime (default  
180 minutes), on the first press (1 to 7 seconds). On the  
next press, the OverRide state is set to OC_NUL (no  
manual over ride is active).  
OverridePriority  
ActualCoolSpt = RmtStptPot +  
(CoolOccSpt - HeatOccSpt) / 2  
ActualHeatSpt = RmtStptPot -  
OverridePriority configures the override arbitration between  
nviManOcc, nviBypass.state, and the wall module override  
button. There are two possible states which have the following  
meanings:  
(CoolOccSpt - HeatOccSpt) / 2  
During Standby and Unoccupied times, the remote setpoint  
pot is not referenced, and the software setpoints for those  
modes are used instead.  
LAST specifies that the last command received from either  
the wall module or nviManOcc determines the effective  
override state.  
SETPOINT LIMITS (LoSetptLim AND HiSetptLim)  
NET specifies that when nviManOcc is not OC_NUL, then  
the effective occupancy is nviManOcc regardless of the  
wall module override state.  
Remote setpoint pot limits are provided by LoSetptLim and  
HiSetptLim. The occupied setpoints used in the control  
algorithms are limited by these parameters. When the setpoint  
knob is configured to be of type Absolute Middle, the lowest  
actual setpoint allowed is equal to LoSetptLim, and the  
highest actual setpoint allowed is equal to HiSetptLim. When  
the setpoint knob is configured to be an Offset type, the lowest  
actual setpoint allowed is equal to HeatOccSpt - LoSetptLim,  
and the highest allowed is equal to CoolOccSpt + HiSetptLim.  
CYCLES PER HOUR (ubHeatCph AND ubCoolCph)  
ubHeatCph specifies the mid-load number of on / off cycles  
per hour (default is 6), when the mode is HEAT. ubCoolCph  
specifies the mid-load number of on / off cycles per hour  
(default is 3), when the mode is COOL. This is to protect the  
mechanical equipment against short cycling causing  
excessive wear. In addition the cycle rate specifies the  
minimum on and off time according to Table 17.  
BYPASS MODE (StatusOvrd AND StatusLed)  
During Unoccupied periods, the facility occupant can request  
that Occupied temperature control setpoints be observed by  
depressing the Bypass pushbutton on the wall module. When  
activated, the controller remains in Bypass mode until:  
1. Bypass Duration Setting has timed out (BypTime), or  
2. User again presses the Wall Module pushbutton to  
switch off Bypass mode, or  
T7770C,D OR T7560A,B WALL MODULE BYPASS PUSHBUTTON  
OPERATION  
The Wall Module Bypass pushbutton is located on both the  
T7770C,D or the T7560A,B Wall Modules, see Fig. 43 and 44.  
The bypass pushbutton can change the controller into various  
occupancy modes, see Table 16.  
3. Occupancy schedule (DestSchedOcc network input or  
TimeClckOcc digital input) switches the mode to  
Occupied.  
4. User sets the DestManOcc network point to Not  
Assigned.  
The LED on the T7770 Wall Module (Override LED) indicates  
the current bypass mode status (see the T7770C,D Wall  
Module Bypass Pushbutton and Override LED section). The  
LCD on the T7560 Digital Wall Module indicates the current  
bypass mode status (see the T7560A,B Digital Wall Module  
Bypass Pushbutton and LCD Occupancy Symbols section).  
Table 16. Bypass Pushbutton Operation.  
If the pushbutton is But for not  
held down for  
Less than 1 second  
1 second  
more than The resulting mode is  
No Override is active  
4 seconds Bypass (a timed Occupied  
Override)  
4 seconds  
7 seconds Continuous Unoccupied  
Override  
NOTES: If the pushbutton is held down for longer than seven  
seconds, the controller reverts back to No Override  
and repeats the cycle above. See Fig. 45.  
Continuous Occupied override mode can only be  
initiated remotely; that is, over the LONWORKS Bus  
network.  
BypassTime  
BypassTime is the time between the pressing of the override  
button at the wall module (or initiating OC_BYPASS via  
nviManOcc) and the return to the original occupancy state.  
When the bypass state has been activated, the bypass timer  
is set to BypassTime (default of 180 minutes).  
55  
74-29581  
Download from Www.Somanuals.com. All Manuals Search And Download.  
                 
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
RESET  
NOT ASSIGNED  
(LED OFF)  
PRESS FOR LESS  
THAN ONE SECOND  
BYPASS  
TIMEOUT  
PRESS FOR ONE  
TO FOUR SECONDS  
BYPASS OCCUPIED  
(LED ON)  
PRESS FOR FOUR  
TO SEVEN SECONDS  
PRESS FOR LESS THAN ONE SECOND  
UNOCCUPIED  
(LED BLINK)  
PRESS FOR MORE THAN SEVEN SECONDS  
M8483A  
Fig. 45. LED and Bypass pushbutton operation.  
STANDBY MODE (StatusOcySen)  
OCCUPANCY MODE AND MANUAL OVERRIDE ARBITRATION  
The W7750 has multiple sources for occupancy schedule  
information and, therefore, it employs an arbitration scheme to  
determine the current actual mode. Time-of-day (TOD)  
schedule status comes from two sources, a configured digital  
input for OccTimeClock or the DestSchedOcc network input  
received from a central control. If the digital input source is  
configured, it has highest priority and determines the  
Occupancy mode. This digital input is either ON (shorted =  
occupied), OFF (open = unoccupied), or not active (not  
configured); otherwise, the status is determined by the  
DestSchedOcc input from the network source. The  
DestSchedOcc has three possible states, occupied,  
unoccupied or standby.  
The digital input for an occupancy sensor (usually a motion  
detector or possibly a time clock) provides the controller with a  
means to enter an energy-saving Standby mode whenever  
people are not in the room. Standby mode occurs when the  
scheduled occupancy is Occupied, and the occupancy sensor  
detects no people currently in the room (digital input contacts  
Closed means people are in the room, and contacts Open  
means the room is Unoccupied). When in Standby mode, the  
Excel 10 W7750 Controller uses the Standby Cooling Setpoint  
for cooling (CoolStbySpt), or the Standby Heating Setpoint for  
Heating (HeatStbySpt) as the Actual Space Temperature  
Setpoint. The occupancy sensor signal can also be a network  
input from another LONWORKS Bus device, so that no physical  
sensor is required at the receiving W7750 Controller.  
Manual Override Status can be derived from three sources  
and governed by two selectable arbitration schemes. The two  
schemes are:  
IMPORTANT  
When the W7750 Controller is in Standby mode, the  
economizer minimum position setting is not  
observed. This means the fresh air dampers will go  
fully closed if there is no call for cooling.  
Network Wins or Last-in Wins, as set in OvrdPriority.  
The three sources of manual override status are:  
DestManOcc -  
Has possible states: Occupied,  
CONTINUOUS UNOCCUPIED MODE  
Unoccupied, Bypass, Standby and Not  
Assigned (not active). This input source  
has the highest priority in determining  
manual override status for a Network  
Wins arbitration scheme, and in the  
event there is more than one source  
change at a time in the Last-in Wins  
arbitration scheme. Here, bypass  
initiates a self-timed bypass of the  
control unit and expires upon  
completion of the defined timed period.  
The controller then treats the bypass  
status of this input as Not Assigned until  
the next change in status.  
This mode is entered when a wall module is configured with a  
Bypass pushbutton that was pressed for four to seven  
seconds causing the wall module LED/LCD to blink. This  
mode can also be entered via a network command  
(ManualOcc set to Unoccupied). If the controller is in this  
mode, it reverts to the Unoccupied setpoints for temperature  
control, and the economizer does not observe its minimum  
position setting. The controller remains in this mode  
indefinitely until the Bypass pushbutton is pressed to exit the  
mode or a network command is sent to clear the mode. A  
configuration parameter is available to disable wall-module  
initiation of Continuous Unoccupied mode (OvrdType).  
74-29581  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
DestBypass -  
Has possible states: Bypass On,  
SETPOINT RAMPING  
Bypass Off or Not Assigned (not active).  
This input places the controller in an  
untimed bypass state or turns off the  
bypass mode. This source is second in  
priority to DestManOcc under the same  
arbitration schemes mentioned above.  
The W7750 Controller incorporates a ramping feature that  
gradually changes the space setpoints between occupancy  
modes. This feature is only operational if the network variable  
inputs DestSchedOcc, TodEventNext, and Time Until Next  
Change Of State (TUNCOS) are being used to change the  
W7750 Occupancy mode. The applicable Setpoints are  
OaTempMinHtRamp, OaTempMaxHtRamp, MinHtRamp and  
MaxHtRamp (for HEAT mode operation), and  
Override Button -The wall module Override pushbutton  
can command status of Bypass,  
OaTempMinClRamp, OaTempMaxClRamp, MinClRamp and  
MaxClRamp (for the COOL mode operation). See Fig. 46 for a  
pictorial representation of how these setpoints interact.  
Continuous Unoccupied and Not  
Assigned. This source has the lowest  
priority status in the above mentioned  
schemes. The above mention sources  
of override must be either Not Assigned  
or Off before the Override pushbutton  
affects the manual override status in the  
Network Wins scheme. All actions, in  
this case, taken from the Override  
pushbutton are locked out.  
During recovery operation, the setpoint changes at a rate in  
degrees per hour depending on the outdoor air temperature. If  
there is no outdoor air temperature sensor available, then  
MinHtRamp is used as the recovery rate.  
HEAT RECOVERY  
RAMP RATE  
(DEGREES/HOUR)  
Bypass status is a controller-timed  
event whose duration is set in BypTime.  
Upon expiration of the timer, the status  
returns to Not Assigned. The status of  
this input can be overridden with the  
receipt of Not Assigned from  
MaxHtRam  
DestManOcc. This, in effect, cancels a  
timed bypass or a continuous  
unoccupied mode.  
MinHtRam  
The Override pushbutton can be  
configured as Normal (all of the above  
mentioned states are possible), Bypass  
Only (Bypass and Not Assigned only) or  
None (effectively Disabling the Override  
pushbutton).  
OUTDOOR AIR  
TEMPERATURE  
OaTempMinHtRa  
OaTempMaxHtRam  
M10109  
Fig. 46. Setpoint ramping parameters with ramp rate  
calculation.  
TIME CLOCK (Occ_Time_Clock)  
NOTE: Recovery ramping applies between scheduled  
heating or cooling setpoint changes from  
OccTimeClock is the state of the digital input configured and  
wired to a time clock. When the digital input is detected to be  
Closed (Occupied), the scheduled occupancy will be  
OC_OCCUPIED. If the detected state of the digital input is  
Open (Unoccupied), then the scheduled occupancy will be  
OC_UNOCCUPIED. If the Occ_Time_Clock is not configured,  
then either the DestSchedOcc network input received from a  
central control or the time clock that is broadcast from a  
Sched_Master configured W7750, controls the occupied  
mode.  
UNOCCUPIED to STANDBY, UNOCCUPIED to  
OCCUPIED, and STANDBY to OCCUPIED.  
Scheduled setpoint changes from OCCUPIED to  
UNOCCUPIED or OCCUPIED to STANDBY do not  
use a ramped setpoint but instead use a step change  
in setpoint. Recovery ramps begin before the next  
scheduled occupancy time and are ramped from the  
setpoint for the existing scheduled occupancy state  
to the setpoint for the next occupancy state.  
SCHEDULE MASTER (Sched_Master)  
RECOVERY RAMPING FOR HEAT PUMP SYSTEMS  
Sched_Master is the state of a digital input that is configured  
and wired to the W7750. If the Sched_Master input is closed  
(input shorted), the node is the schedule master and the state  
of the locally connected time clock will be broadcast out over  
the LONWORKS Bus to the other W7750 controllers. If the  
Sched_Master input is open, then the node is not a schedule  
master and the local time clock will not be sent out over the  
LONWORKS Bus even if the time clock input is configured.  
However, the DestSchedOcc network input received from a  
central control has a higher priority than the local time clock,  
and therefore overrides the local time clock. The W7750  
controllers automatically bind without the need for a  
configuration tool.  
When the node is controlling heat pump equipment, during the  
recovery ramps, the heating setpoint is split into a heat pump  
setpoint (for compressors) and an auxiliary heat setpoint (for  
auxiliary heat stages). The heat pump setpoint is a step  
change at the recovery time prior to the OCCUPIED time.  
Recovery time is computed from the configured heat recovery  
ramp rate. The recovery time is calculated:  
Recovery time = (OCC setpoint - current setpoint)/ramp rate  
See Fig. 47 for the various setpoints.  
57  
74-29581  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Standby or Unoccupied modes, the fan cycles on with a call  
for cooling (or heating if the FanOnHtMode parameter is set).  
In Intermittent Fan mode, the fan cycles on with a call for  
cooling (or heating if the FanOnHtMode parameter is set), and  
cycles off when the space temperature control is satisfied.  
HEAT PUMP  
SETPOINT  
(FOR COMPRESSORS)  
OCC setpoint  
AUX HEAT  
SETPOINT  
The fan control supports an optional (Proof of Air Flow) digital  
input, that allows monitoring of the supply fans status. If the  
fan is commanded on, the Proof of Air Flow digital input is  
checked up to three times to verify that the fan is running after  
an initial delay of FanOnDelay seconds (user-settable). If the  
fan fails to start the CVAHU must be reset by first cycling  
CVAHU power. If this does not work, set DestManMode to  
Manual and then back to Enable. After a reset the application  
restartsall outputs switch off and auto control is enabled.  
UN_OCC setpoint  
OR  
STANDBY setpoint  
RECOVERY TIME  
OCCUPIED TIME  
M10110  
Also, the W7750 Controller provides fan-run-on operation that  
keeps the fan running for a short time after heating or cooling  
shuts off. The amount of time that the fan continues to run is  
set in FanRunOnHeat for heating mode and FanRunOnCool  
for cooling mode.  
Fig. 47. Setpoint ramping parameters with setpoint  
calculation.  
During the COOL recovery period, the setpoint changes at a  
rate in degrees per hour relative to the outdoor air  
temperature. If there is no outdoor air temperature sensor  
available, the MinClRamp is used as the recovery rate.  
WINDOW SENSOR (StatusWndw)  
The digital input for a window contact provides the algorithm  
with a means to disable its temperature control activities if  
someone has opened a window or door in the room. When a  
window is detected to be Open (digital input contacts Open  
equals window open), the normal temperature control is  
disabled, and the W7750 Controller enters the Freeze Protect  
mode. Freeze Protect mode sets the space setpoint to 46.4 °F  
(8°C) and brings on the fan and heat if the space temperature  
falls below this setpoint. Normal temperature control resumes  
on window closure. The Window sensor signal can also be a  
network input from another LONWORKS Bus device, so that no  
physical sensor is required at the receiving W7750 Controller.  
See Fig. 48 for the various setpoints.  
COOL RECOVERY  
RAMP RATE  
(DEGREES/HOUR)  
MaxClRam  
SMOKE CONTROL  
The Excel 10 W7750 Controller supports three smoke-related  
control strategies:  
MinClRam  
1. Emergency Shutdown (all outputs off).  
2. Depressurize (fan on, outdoor air damper closed).  
3. Pressurize (fan on, outdoor air damper open).  
OUTDOOR AIR  
TEMPERATURE  
OaTempMinClRa  
OaTempMaxClRam  
M10111  
Fig. 48. Setpoint ramping parameters with ramp rate  
calculation.  
The controller is placed in one of these three control states  
whenever the W7750 mode becomes  
SMOKE_EMERGENCY, which can be initiated via a network  
command (DestEmergCmd) or from a local (physically  
connected) smoke detector digital input. When in  
SMOKE_EMERGENCY mode, the W7750 Controller uses the  
control strategy found in SmkCtlMode (one of the three listed  
above), and the normal temperature control function is  
disabled. If a W7750 local smoke detector trips, the SrcEmerg  
network variable (for other LONWORKS Bus devices to receive)  
is set to the Emergency state.  
NOTES: The setpoint used during the COOL recovery period  
is similar to the heat mode in Fig. 46, except the  
slope of the line reverses for cooling.  
Recovery ramping applies between scheduled heat-  
ing or cooling setpoint changes from UNOCCUPIED  
to STANDBY, UNOCCUPIED to OCCUPIED, and  
STANDBY to OCCUPIED. Scheduled setpoint  
changes from OCCUPIED to UNOCCUPIED or  
OCCUPIED to STANDBY do not use a ramped set-  
point, but instead, use a step change in setpoint.  
Recovery ramps begin before the next scheduled  
occupancy time and are ramped from the setpoint for  
the existing scheduled occupancy state to the set-  
point for the next occupancy state.  
DEMAND LIMIT CONTROL (DLC)  
When The LONWORKS Bus network receives a high-electrical-  
demand signal, the controller applies a DlcBumpTemp amount  
to the current actual space temperature setpoint value. The  
setpoint is always adjusted in the energy-saving direction.  
This means that if the W7750 Controller is in Cooling mode,  
the DLC offset bumps the control point up, and when in  
Heating mode, bumps the control point down.  
FAN OPERATION  
The W7750 supply fan can be controlled in one of two  
different ways. In Continuous Fan mode, the fan runs  
whenever the controller is in Occupied mode. When in  
74-29581  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
DIRTY FILTER MONITOR  
the START_UP_WAIT mode for a pseudo-random period  
(depending on neuron_id) between 12 and 22 seconds and  
then transitions to one of the operating modes, depending on  
the inputs that are read from the physical and network inputs.  
The pseudo random period prevents multiple controllers from  
simultaneously starting major electrical loads when power is  
restored to a building.  
The air filter in the air handler can be monitored by the W7750  
and an alarm issued when the filter media needs replacement.  
The two methods of monitoring the filter are:  
1. A differential pressure switch whose contacts are con-  
nected to a digital input on the W7750A or W7750B,C;  
and  
2. A 2-to-10V differential pressure sensor wired to a  
current input on the W7750B,C. If the analog input  
sensor is used, its measured value 0 to 5 inw  
(0 to 1.25 kPa) is compared to a user-selectable  
setpoint (FltrPressStPtvalid range: 0 to 5 inw  
(0 to 1.25 kPa)), and the Dirty Filter alarm is issued  
when the pressure drop across the filter exceeds the  
setpoint.  
NOTES: After a controller download via Care/E-Vision, the  
delayed reset time is bypassed and the controller  
starts after a 40-second initialization.  
Not all network inputs can be received during the  
START_UP_WAIT period because many network  
variables are updated at a slower rate; therefore  
some control decisions can be considered tempo-  
rarily inappropriate.  
START-UP  
START_UP_WAIT is the first mode after application restart or  
power-up. During START_UP_WAIT, the analog and digital  
inputs are being read for the first time, no control algorithms  
are active, and the physical outputs (fan and heat/cooling  
stages) are in the de-energized position. The node remains in  
Temperature Control Operations  
See Fig. 49 for a diagram of a typical W7750 Unit.  
OA TEMP  
HEAT  
COIL  
COOL  
COIL  
FILTER  
FAN  
OUTDOOR  
AIR  
+
-
M
EXCEL 10  
W7750  
CVAHU  
DA TEMP  
RA TEMP  
ROOF  
CEILING  
OCCUPANCY  
SENSOR  
RETURN  
AIR  
DISCHARGE  
AIR  
T7770 OR T7560A,B  
M17488  
WINDOW CONTACT  
Fig. 49. Schematic diagram for a typical W7750B Unit.  
59  
74-29581  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
STAGED COOLING CONTROL  
calculates a PID error signal. This error signal causes the  
cooling stage outputs to be cycled as required to drive the  
space temperature back to the setpoint. Fig. 50 illustrates the  
relationship between PID error and staged output activity. As  
the error signal increases and the space temperature is  
getting farther away from setpoint, or is remaining above  
setpoint as time elapses, additional stages of cooling are  
energized until, if PID error reaches 100 percent, all  
configured stages are on.  
The Excel 10 W7750 Controller supports up to four stages of  
D/X cooling. As space temperature rises above the current  
Cooling Setpoint, the controllers mode of operation is  
switched to the COOL mode. When in the COOL mode, all  
heating outputs are driven closed or off (with the exception  
that occurs during IAQ Override Operation, see above), and  
the staged cooling outputs are enabled for use. When in the  
COOL mode, the PID cooling control algorithm compares the  
current space temperature to the EffectiveCoolSetPt, and  
PID  
ERROR  
NO. STAGES  
0%  
25% 33%  
50%  
66% 75%  
100%  
> 100%  
CONFIGURED  
ALL STAGES  
LOCKED ON  
ONE STAGE  
CYCLING  
STAGE 1  
CYCLING  
STAGE 1 LOCKED ON  
STAGE 2 CYCLING  
ALL STAGES  
LOCKED ON  
TWO STAGES  
STAGE 1  
CYCLING  
STAGE 1 LOCKED ON  
STAGE 2 CYCLING  
STAGE 1,2 LOCKED ON  
STAGE 3 CYCLING  
ALL STAGES  
LOCKED ON  
THREE STAGES  
FOUR STAGES  
STAGE 1  
STAGE 1,2  
LOCKED ON  
STAGE 3  
STAGE 1,2,3  
LOCKED ON  
STAGE 4  
STAGE 1  
CYCLING  
LOCKED ON  
STAGE 2  
ALL STAGES  
LOCKED ON  
CYCLING  
CYCLING  
CYCLING  
M10112  
Fig. 50. Staged output control versus PID Error.  
If economizer dampers are configured, and the outdoor air is  
suitable for free cooling, the economizer operates as the first  
stage of cooling. For example, if a controller was configured  
with two stages of mechanical cooling and an economizer, the  
application should be viewed in Fig. 50 as a three-stage  
system.  
Table 17. Interstage Minimum Times  
Cycles/Hour Selection  
Minimum On/Off time (Min.)  
2
3
8.5  
5.5  
4.0  
3.5  
3.0  
2.5  
2.0  
2.0  
2.0  
1.5  
1.5  
4
Setpoints for the PID gains allow for unit-by-unit adjustment of  
the control loop, if required; however, any change from the  
default values should be minimal.  
5
6
7
The PID control algorithm used to control staged cooling is  
anticipator-driven, and is similar to the algorithm used in the  
T7300 commercial thermostat. All staging events are subject  
to a minimum interstage time delay, which is based on the  
cycles per hour user setting (CoolCycHr). The minimum  
interstage time delay ranges from 90 seconds (at 12 cycles  
per hour) to 8.5 minutes (at two cycles per hour), see Table  
17. The user has the option to disable the minimum run timer  
(DisMinClTimer for cooling). If the minimum run timer is  
disabled, the interstage time delay is fixed at 20 seconds. The  
cycling rate is separately selectable for heating and cooling  
between 2 and 12 cycles per hour (cph).  
8
9
10  
11  
12  
STAGED HEATING CONTROL  
The Excel 10 W7750B,C Controller supports up to four stages  
of heating. As space temperature falls below the current  
Cooling Setpoint, the controller mode of operation is switched  
to the HEAT mode. When in the HEAT mode, all cooling  
outputs are driven closed or off, and the staged heating  
outputs are enabled for use. When in the HEAT mode, the PID  
74-29581  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
cooling control algorithm compares the current space  
temperature to the EffectiveHeatSetPt, and calculates a PID  
error signal. This error signal causes the heating stage  
outputs to be cycled, as required, to drive the space  
temperature back to the Setpoint. Fig. 50 illustrates the  
relationship between PID error and staged output activity.  
actuator based on the length, in seconds, of the pulse from  
the digital output. The controller outputs a pulse whose length  
consists of two parts, a minimum and a maximum. The  
minimum pulse time represents the analog value of zero  
percent (also indicates a signal presence) and the maximum  
pulse length that represents an analog value of 100 percent. If  
the analog value is greater than zero percent, an additional  
time is added to the minimum pulse time. The length of time  
added is directly proportional to the magnitude of the analog  
value. If PWM control is used, the configuration parameters  
for the PWM operation must be specified. These are  
As the error signal increases, the space temperature gets  
further away from the setpoint, or is remaining below the  
setpoint as time elapses, additional stages of heating are  
energized until, if PID error reaches 100 percent, all  
configured stages are on.  
PwmPeriod, PwmZeroScale, and PwmFullScale. These three  
parameters are shared by all configured PWM outputs; this  
means the heating, cooling, and economizer actuators must  
be configured to accept the same style of PWM signal.  
The PID control algorithm used to control staged heating is  
anticipator-driven, and is similar to the algorithm used in the  
T7300 commercial thermostat. All staging events are subject  
to a minimum interstage time delay, that is based on the  
cycles per hour user setting (HeatCycHr). The minimum  
interstage time delay ranges from 90 seconds (at 12 cycles  
per hour) to eight minutes (at two cycles per hour). See Table  
17. The user has the option to disable the minimum run timer  
for heating (DisMinHtTimer). If the minimum run timer is  
disabled, the interstage time delay is fixed at 20 seconds. The  
cycling rate is separately selectable for heating and cooling  
between two and 12 cycles per hour (cph).  
Example: To find the pulse width of a valve actuator (for  
example stroke mid position - 50 percent) with the  
PwmZeroScale = 0.1 seconds, PwmFullScale = 25.5  
seconds, and the PwmPeriod = 25.6 seconds. There are 256  
increments available, so the number of increments required  
for 50 percent would be (0.5 X 256) or 128. The time for each  
increment for this industry standard pulse time is 0.1 seconds.  
The pulse width is the minimum time (0.1 second) + the  
number of increments (128 times the (0.1 second) plus 0. 1) =  
12.9 seconds. The W7750B,C Controllers would command  
the valve output on for 12.9 seconds for the PwmPeriod of  
25.6 seconds to maintain the valve position at 50 percent.  
Setpoints for the PID gains allow for unit-by-unit adjustment of  
the control loop, if required; however, any change from the  
default values should be minimal.  
OUTDOOR AIR LOCKOUT OF HEATING/COOLING  
CASCADE CONTROL OF MODULATING COOLING/HEATING  
The Excel 10 W7750 Controller supports modulating cooling  
and heating valves. These valves can be controlled directly  
from the space temperature (like the staged control) or, if the  
CascCtrl flag is set, they are modulated to maintain the  
discharge air temperature at its setpoint. The discharge air  
setpoint is calculated based on the space temperature  
deviation from the space setpoint. This is commonly called  
cascade control. In the W7750 Controller, cascade control is  
available for use with PWM (W7750B,C only) and Series 60  
modulating heating and cooling, but not for use with staged  
heating/cooling.  
A mechanism is provided in the W7750 to disable the heating  
equipment if the outdoor air temperature rises above the  
OaTempHtLkOut setpoint. Similarly, the cooling equipment is  
disabled if the outdoor air temperature falls below the  
OaTempClLkOut setpoint. The algorithm supplies a fixed 2°F  
(1.1°C) hysteresis with the lock-out control to prevent short  
cycling of the equipment.  
ECONOMIZER DAMPER CONTROL  
A mixed-air economizer damper package can be controlled to  
assist mechanical cooling in maintaining the discharge air at  
setpoint. Therefore, if modulating economizer damper control  
is desired, a discharge air temperature sensor is required. If  
the outdoor air is not currently suitable for cooling use (see the  
Economizer Enable/Disable Control section), the outdoor air  
damper is held at the user-settable minimum position  
(EconMinPos) for ventilation purposes.  
Setpoints for the PID gains and for the control band allow for  
unit-by-unit adjustment of the control loops, if required;  
however, any change from the default values should be  
minimal. Also, the W7750 Controller uses an adaptive  
algorithm (patent pending) to continuously assess the validity  
of the calculated discharge setpoint, and adjust it, as needed,  
to ensure precise, accurate control.  
Because the outdoor air can be used to supplement  
mechanical cooling, the economizer operates as if it were the  
first stage of cooling. So, if the outdoor air is suitable for  
cooling use, the mechanical cooling (either staged or  
modulating) is held off until the economizer has reached its  
fully open position. Then, if the discharge temperature  
continues to be above setpoint, the mechanical cooling is  
allowed to come on. If the outdoor air is not suitable for  
cooling use, the economizer is set to its minimum position,  
and mechanical cooling is allowed to come on immediately.  
SERIES 60 MODULATING CONTROL  
Series 60 Control is also commonly referred to as Floating  
Control. The Excel 10 W7750A,B,C Controllers can drive  
Series 60 type actuators to control a modulating cooling valve,  
a heating valve, and economizer dampers. When floating  
control is used, the full-stroke motor drive time of the actuator  
must be entered into the configuration parameter CoolMtrSpd  
(for cooling), HeatMtrSpd (for heating), or EconMtrSpd (for the  
economizer dampers).  
When the controller is in the Heat mode, the economizer is  
held at the minimum position setting (EconMinPos). The  
minimum position setting is only used during Occupied mode  
operation. When in Standby or Unoccupied modes, the  
outdoor air dampers are allowed to fully close if there is no call  
for cooling, or if the outside air is not suitable for cooling use.  
PULSE WIDTH MODULATING (PWM) CONTROL  
The Excel 10 W7750B,C Controllers can drive a PWM-type  
actuator to control a modulating cooling valve, a heating  
valve, and economizer dampers. PWM control positions the  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
74-29581  
         
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
INDOOR AIR QUALITY (IAQ) OVERRIDE  
6. Outdoor Enthalpy, Type Dwhen the outdoor  
enthalpy meets the H205 type D requirements, the  
outdoor air is suitable to augment cooling.  
7. Differential Temperaturethe difference between  
outdoor temperature and return air temperature is  
compared to DiffEconEnTemp to determine whether  
outdoor air or return air is more suitable for use to  
augment mechanical cooling.  
8. Single Calculated Enthalpythe calculated outdoor  
enthalpy in btu/lb is compared to the enthalpy setpoint  
(OaEnthEn) in btu/lb, and the outdoor temperature is  
compared to the outdoor temperature limit setpoint  
(OaEconEnTemp) for a high limit. The compared  
difference determines whether outdoor air is suitable for  
use to augment mechanical cooling.  
9. Differential Enthalpy, Either Sensed or Calculated—  
the difference between outdoor enthalpy and return air  
enthalpy determines whether outdoor air or return air is  
more suitable to augment mechanical cooling. When  
enthalpy sensors are configured, they are used for  
comparing enthalpy. If no enthalpy sensors are  
available, then enthalpy is calculated using outdoor and  
return air humidity and temperature sensors. The  
switching differential is fixed at 1.0 mA for enthalpy  
sensors, and 0.25 btu/lb for calculated enthalpy.  
The Excel 10 W7750 Controller supports an IAQ override  
feature that upon detection of poor air quality in the space,  
allows the economizer dampers to be opened above the  
standard minimum position setting to a value set in  
EconIAQPos. Two different methods of detecting poor air  
quality are supported, The first is by using an IAQ switch  
device connected to a digital input on the W7750 Controller,  
where a contact closure indicates poor air quality and initiates  
the IAQ override mode. The second, which is only available  
on the W7750B,C is through an analog input that connects to  
a CO2 Sensor (0 to 10V). The measured value of CO2 from  
this sensor (0 to 2000 ppm) is compared to the setpoint  
IAQSetpt. When the CO2 level is higher than the setpoint (800  
PPM), the IAQ override is initiated. The IAQSetpt hysteresis is  
50 PPM, IAQ override is deactivated at a CO2 level less than  
750 PPM.  
When the W7750 Controller is in the COOL mode during an  
IAQ override, it is possible for the heating outputs to be  
activated. This can occur if the outdoor air temperature is cold  
enough to cause the discharge air temperature to drop below  
the DaTempLoLim setpoint when the dampers open to the  
EconIAQPos position, and the IaqUseHeat flag is set. If this  
situation occurs, the heating is controlled to maintain the  
discharge air temperature at 1°F (0.65°C) above the  
DaTempLoLim setpoint.  
NOTE: If no return temperature sensor is configured,  
space temperature is used to calculate return  
air enthalpy.  
FREEZE STAT  
Upon receiving a contact closure, the W7750 control  
algorithm will close the outdoor air damper and open the hot  
water and chilled water valves (if available) to the full open  
position as a safety precaution. If manual-reset operation is  
desired, the Freeze Stat device must provide the physical  
pushbutton, which the operator presses, to reset the system  
after a freeze condition has occurred.  
10. Network Enabledthe network input DestEconEnable  
controls the enabling and disabling of the economizer.  
When using the network input, select Econo Enable  
Type: No Economizer in E-Vision. The network input  
has priority over the other nine economizer control  
selections.  
DISCHARGE AIR LOW LIMIT CONTROL  
Appendix C. Complete List of Excel 10  
W7750 Controller User Addresses.  
If the discharge air temperature falls below the user-settable  
discharge air low limit setpoint (DaTempLoLim), an alarm is  
issued, and the outdoor air damper is driven below the  
minimum position setting until the discharge temperature is up  
to the low limit. If necessary, the damper can go completely  
closed even during Occupied mode operation. As the  
discharge temperature warms up, the economizer modulates  
open until the minimum position setting is reached. At this  
point, the low limit alarm is cleared.  
See Table 18 for W7750 Controller User Address table  
numbers and point types.  
The User Address Index following Table 18 lists the User  
Addresses alphabetically and gives the page number where  
the Address is located in each Table Number/Point Type.  
After Table 18 there is an alphabetical list of Mappable User  
Addresses and Table Numbers. Following this is an  
alphabetical list of Failure Detect User Addresses and Table  
Numbers.  
ECONOMIZER ENABLE/DISABLE CONTROL  
The W7750 Controller has inputs to determine if the outdoor  
air is suitable to augment cooling. The economizer dampers  
can be enabled/disabled for using outdoor air as the first  
stage of cooling based on one of ten allowable strategies:  
1. Digital Input Enable/Disablecontact closure enables  
economizer.  
2. Outdoor Temperaturewhen the outdoor temperature  
is less than OaEconEnTemp, then the outdoor air is  
suitable to augment cooling.  
3. Outdoor Enthalpy, Type Awhen the outdoor  
enthalpy meets the H205 type A requirements, the  
outdoor air is suitable to augment cooling.  
4. Outdoor Enthalpy, Type Bwhen the outdoor  
enthalpy meets the H205 type B requirements, the  
outdoor air is suitable to augment cooling.  
Table 18. Excel 10 W7750 Controller User  
Address Point Types.  
Table Number  
Table 20  
Table 21  
Table 22  
Table 23  
Table 24  
Table 25  
Table 26  
Table 27  
Table 28  
Point Types  
Input/Output  
Control Parameters  
Energy Management Points  
Status Points  
Calibration Points  
Configuration Parameters  
LONMARK/Open System Points  
Direct Access and Special Manual Points  
Data Share Points  
5. Outdoor Enthalpy, Type Cwhen the outdoor  
enthalpy meets the H205 type C requirements, the  
outdoor air is suitable to augment cooling.  
74-29581  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
User Address Indexes (all in alphabetical order)  
Table 20. Input Output Points.  
Address  
Page  
Table 22. Energy Management Points.  
Address  
Page  
Table 23. Status Points.  
Address  
Page  
Table 21. Control Parameters.  
Address  
Page  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
74-29581  
 
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Table 27. Direct Access and Special Manual Points.  
Address  
Page  
Table 24. Calibration Points.  
Page 93  
Table 25. Configuration Parameters.  
Address  
Page  
Table 28. Data Share Points.  
Address  
Page  
Mappable User Addresses and Table Number  
User Address Table Number  
BypTime 21  
BypTimer 23  
CascCntrl 25  
Table 26. LONMARK/Open System Points.  
CO2Sen 23  
Address  
Page  
CoolCycHr 25  
CoolMtrSpd 25  
CoolOccSpt 26  
CoolPos 23  
CoolStbySpt 26  
CoolStgsOn 23  
CoolUnoccSpt 26  
DaSetpt 23  
DaTemp 23  
DaTempClCtrlBd 21  
DaTempEcCtrlBd 21  
DaTempHiLim 21  
DaTempHtCtrlBd 21  
DaTempLoLim 21  
DestDlcShed 22  
DestEmergCmd 26  
DestHvacMode 26  
DestManMode 27  
DestSchedOcc 22  
74-29581  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
DiffEconEnTemp 21  
DisMinHtTime 25  
DisMinClTime 25  
DlcBumpTemp 21  
EconIAQPos 21  
EconMinPos 21  
EconMtrSpd 25  
EconPos 23  
RaEnthCalc 23  
RaHum 23  
RaTemp 23  
RmTempActSpt 23  
RmTempCal 25  
RmtStptPot 20  
SaFan 23  
SaFanStatus 23  
SetPtKnob 25  
ShutDown 23  
EconMode 25  
FanFailTime 25  
FanMode 25  
FanOnHtMode 25  
FanRunOnCool 25  
FanRunOnHeat 25  
FilterPress 23  
FltrPressStPt 21  
Free1Stat 23  
Free2Stat 23  
GainCoolDer 21  
GainCoolInt 21  
GainCoolProp 21  
GainHeatDer 21  
GainHeatInt 21  
GainHeatProp 21  
HeatCycHr 25  
HeatMtrSpd 25  
HeatOccSpt 26  
HeatPos 23  
HeatStbySpt 26  
HeatStgsOn 23  
HeatUnoccSpt 26  
IAQSetpt 21  
SmkCtlMode 25  
StatFreezeStat 23  
StatusAlmTyp 23  
StatusEconEn 23  
StatusEconOut 23  
StatusFilter 23  
StatusIaqOvr 23  
StatusManOcc 23  
StatusMode 23  
StatusOcc 23  
StatusOcySen 23  
StatusOvrd 23  
StatusSched 23  
StatusSmoke 23  
StatusWndw 23  
StptKnobHiLim 21  
StptKnobLowLim 21  
TimeClckOcc 23  
UseRaTempCtl 25  
UseWallModStpt 25  
WSHPEnable 23  
IaqUseHeat 25  
MaxClRamp 21  
MinClRamp 21  
MaxHtRamp 21  
MinHtRamp 21  
MonitorSens 23  
MonitorSw 23  
Failure Detect User Addresses and Table Number  
User Address Table Number  
DestBypass 22  
DestDlcShed 22  
DestEconEnable 26  
DestFree1 22  
OaEconEnTemp 21  
OaEnth 23  
DestFree2 22  
OaEnthCalc 23  
OaEnthEn 21  
OaHum 23  
OaTemp 23  
DestHvacMode 26  
DestIaqOvrd 28  
DestOaEnth 28  
DestOaHum 26  
DestOaTemp 26  
DestOccSensor 26  
DestRmTemp 26  
DestSchedOcc 22  
DestSptOffset 26  
DestTimeClk 22  
DestWndw 26  
OaTempClLkOut 21  
OaTempHtLkOut 21  
OaTempMaxClRp 21  
OaTempMinClRp 21  
OaTempMaxHtRp 21  
OaTempMinHtRp 21  
OccStatOut 23  
OvrdPriority 25  
OvrdType 25  
PwmFullScale 21  
PwmPeriod 21  
PwmZeroScale 21  
RaEnth 23  
DestWSHPEnable 22  
Table 19 lists the applicable Engineering Units for the analog  
points found in the W7750.  
Table 19. Engineering Units For Analog Points.  
English Units (Inch-Pound)  
Description  
Standard International Units (SI)  
Measured Item  
Temperature  
Abbreviation  
Description  
Degrees Celsius  
Degrees Kelvin  
Percent  
Abbreviation  
Degrees Fahrenheit  
F
C
Relative Temperature Delta Degrees Fahrenheit  
DDF  
%
K
Relative Humidity  
Air Flow  
Percent  
%
Cubic Feet per Minute  
Parts Per Million  
CFM  
PPM  
btu/lb  
inw  
Meters Cubed per Hour m3h  
CO2 Concentration  
Enthalpy  
Parts Per Million  
kiloJoules/kilogram  
kiloPascal  
PPM  
kj/kg  
kPa  
British Thermal Units per Pound of Air  
Inches of Water Column  
Differential Pressure  
65  
74-29581  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
All of the NvName values that are stored in EEPROM memory  
have a prefix of nci.  
Hardware  
Config.—  
These are points that involve controller I/O  
configuration. Any change to Hardware Config.  
points causes the W7750 to perform an  
application reset; therefore, these points can  
only be modified off-line.  
NOTE: These parameters are stored in EEPROM and are  
limited to 10,000 writes. Do NOT use them as  
outputs from Control Strategies,Time Programs, or  
Switching Tables. If these points are changed more  
than 10,000 times, irreversible hardware failure  
results  
Manual  
Config.—  
These points are used to set the controller  
outputs when in manual mode. The W7750 is  
placed in manual mode through a menu  
selection in the E-Vision Controller Monitor  
screen.  
Tables 20 through 28 provide point attributes as follows:  
Engineering  
Units—  
Test—  
These points can be controlled in E-Visions test  
mode that is used for field checkout/ debuging.  
This field indicates the point valid range and  
displayed Engineering Unit. For digital points,  
the valid states and the corresponding  
enumerated values are shown.  
The value or state of the point on controller  
start-up.  
Failure Detect  
Input PointThese points need an update periodically or a  
communication alarm is generated. The failure  
detect mechanism is only active when the NV is  
bound (bindings are configured using Refer  
Excel 10 points). The time between the updates  
is user settable.  
Default—  
E-Vision  
(M) MonitorThese points are viewable within the E-Vision  
Controller Monitoring on-line screen.  
(P) ParameterThese points refer to control parameters  
settable in the Application Selection dialog  
boxes in E-Vision.  
Non-Failure Detect  
Input PointThese points (which are NVs that are bound or  
unbound) do not check for an update  
(S) SchematicThese points appear in E-Vision monitor  
mode graphics.  
ShareableThese points can be set up for data sharing in  
Command Multiple Points, Read Multiple  
Points, or Refer Excel 10 Points as either a  
data source or a destination.  
MappableThese points can be converted into a C-Bus  
point used by C-Bus devices. A mappable point  
has a one-to-one relationship with a C-Bus  
User Address.  
periodically and do not generate an alarm.  
NOTES:  
1. Mapped points can be viewed and changed, if  
needed, on the XI581, XI582 and XI584 C-Bus  
devices and on an XBS central and on E-Vision.  
2. All Excel 10 points, mappable and calibration,  
configuration and internal data sharing points, can  
be viewed and changed, as allowed, via Direct  
Access (DA) mode in the XBS subsystem menu  
or via XI584.  
Direct  
Access—  
These points are accessible through the  
Subsystem Points mechanism in XBS.  
74-29581  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 20. Input/Output Points.  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
nciIoSelect  
Field Name  
CorOnMode  
Default  
Comments  
CORMode  
COR_ON_HEAT  
COR_ON_COOL  
0
1
COR_ON_COOL  
P
X
CorOnMode specifies the mode when the Change Over Relay (COR) is  
energized.  
nciIoSelect  
nciIoSelect  
nciIoSelect  
ResistiveIn[0]  
ResistiveIn[1]  
VoltageIn[0]  
DISCHARGE_TEMP_PT3000  
OUTDOOR_TEMP_PT3000  
RETURN_TEMP_PT3000  
DISCHARGE_TEMP_20KNTC  
RETURN_TEMP_20KNTC  
UNUSED_RAI  
0
UNUSED_RAI  
X
X
X
ResistiveIn[0] specifies which logical sensor is assigned to each physical  
analog input sensor channel according to the enumerated list that is shown  
in the Engineering Units/States column. ResistiveIn[0] is the only input  
available in the W7750A controller.  
1
2
3
4
255  
DISCHARGE_TEMP_PT3000  
OUTDOOR_TEMP_PT3000  
RETURN_TEMP_PT3000  
DISCHARGE_TEMP_20KNTC  
RETURN_TEMP_20KNTC  
UNUSED_RAI  
0
UNUSED_RAI  
UNUSED_VAI  
ResistiveIn[1] specifies which logical sensor is assigned to each physical  
analog input sensor channel according to the enumerated list that is shown  
in the Engineering Units/States column. ResistiveIn[0] is the only input  
available in the W7750A controller.  
1
2
3
4
255  
RTN_HUM_C7600C  
RETURN_ENTHALPY  
OD_HUM_C7600C  
OUTDOOR_ENTHALPY  
FILTER_STATIC_PRESS_DIFF  
SPACE_CO2  
MONITOR_SENSOR1  
RTN_HUM_C7600B  
OD_HUM_C7600B  
UNUSED_VAI  
0
VoltageIn[0] specifies which logical sensor is assigned to each physical  
analog input sensor channel according to the enumerated list that is shown  
in the Engineering Units/States column. (Voltage inputs are not available in  
the W7750A controller.)  
1
E
2
3
4
5
6
7
7
8
255  
nciIoSelect  
nciIoSelect  
VoltageIn[1]  
DigitalIn[0]  
RTN_HUM_C7600C  
RETURN_ENTHALPY  
OD_HUM_C7600C  
OUTDOOR_ENTHALPY  
FILTER_STATIC_PRESS_DIFF  
SPACE_CO2  
MONITOR_SENSOR1  
RTN_HUM_C7600B  
OD_HUM_C7600B  
UNUSED_VAI  
0
UNUSED_VAI  
X
VoltageIn[1] specifies which logical sensor is assigned to each physical  
analog input sensor channel according to the enumerated list that is shown  
in the Engineering Units/States column. (Voltage inputs are not available in  
the W7750A controller.)  
B
1
,
2
3
4
NST  
5
6
7
NTV  
8
255  
OCC_SENSOR  
OCC_TIME_CLOCK  
PROOF_AIR_FLOW  
ECON_ENABLE  
IAQ_OVERRIDE  
SMOKE_MONITOR  
DIRTY_FILTER  
SHUT_DOWN  
2
3
OCC_TIME_CLOCK_IN  
X
DigitalIn[0] specifies which logical switch type is connected to the flexible  
digital input switch channel according to the enumerated list that is shown in  
the Engineering Units/States column. DigitalIn[0] and DigitalIn[1] are the  
only inputs available in the W7750A controller. The controller is configured  
at the factory with this user address configured to OCC_TIME_CLOCK_IN.  
4
5
AHUCO  
6
7
8
9
WINDOW_OPEN  
MONITOR  
10  
11  
12  
255  
N
SCHED_MASTER  
UNUSED_DI  
R
E
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
E
Table 20. Input/Output Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
W
Engineering Units: English  
User Address  
NvName  
nciIoSelect  
Field Name  
DigitalIn[1]  
(Metric) or States plus Range  
Default  
Comments  
OCC_SENSOR  
OCC_TIME_CLOCK  
PROOF_AIR_FLOW  
ECON_ENABLE  
IAQ_OVERRIDE  
SMOKE_MONITOR  
DIRTY_FILTER  
SHUT_DOWN  
2
SHCED_MASTER_IN  
X
DigitalIn[1] specifies which logical switch type is connected to the flexible  
digital input switch channel according to the enumerated list that is shown in  
the Engineering Units/States column. DigitalIn[0] and DigitalIn[1] are the  
only inputs available in the W7750A controller. The controller is configured  
at the factory with this user address configured to SCHED_MASTER_IN.  
,
3
4
5
NST  
6
7
8
NTV  
9
WINDOW_OPEN  
MONITORS  
CHED_MASTER  
UNUSED_DI  
10  
11  
12  
255  
MEAHUCO  
nciIoSelect  
DigitalIn[2]  
OCC_SENSOR  
OCC_TIME_CLOCK  
PROOF_AIR_FLOW  
ECON_ENABLE  
IAQ_OVERRIDE  
SMOKE_MONITOR  
DIRTY_FILTER  
SHUT_DOWN  
2
UNUSED_DI  
X
DigitalIn[2] specifies which logical switch type is connected to the flexible  
digital input switch channel according to the enumerated list that is shown in  
the Engineering Units/States column. DigitalIn[0] and DigitalIn[1] are the  
only inputs available in the W7750A controller.  
3
4
5
6
N
7
8
R
9
WINDOW_OPEN  
MONITOR  
10  
11  
12  
255  
E
SCHED_MASTER  
UNUSED_DI  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 20. Input/Output Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
Engineering Units: English  
User Address  
NvName  
nciIoSelect  
Field Name  
DigitalOut[0]  
(Metric) or States plus Range  
Default  
Comments  
COOL_STAGE_1  
COOL_STAGE_2  
COOL_STAGE_3  
COOL_STAGE_4  
HEAT_STAGE_1  
HEAT_STAGE_2  
HEAT_STAGE_3  
HEAT_STAGE_4  
CHANGE_OVER_RELAY  
FAN_OUT  
1
NETWORK DO(FREE1)  
(Value of State is 25)  
X
DigitalOut[0] specifies which logical digital output function is assigned to the  
digital physical output according to the enumerated list that is shown in the  
Engineering Units/States column. The W7750 Controllers are configured at  
the factory with the enumerated value in the Default column. Only  
DigitalOut[0] through DigitalOut[5] are available in the W7750A model  
which can configure staged outputs. The W7750A Controller can drive  
Series 60 Floating Control to modulate cooling valves, heating valves and  
economizers. (No PWM outputs are allowed in the W7750A model.) The  
controller is configured at the factory with the enumerated value in the  
Default column. The eight outputs on the W7750B are all digital outputs.  
The eight outputs on the W7750C consist of five digital and three analog  
outputs.  
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
25  
26  
27  
28  
29  
30  
31  
255  
AUX_ECON  
OCCUPANCY_STATUS  
ECON_OPEN  
ECON_CLOSE  
COOL_OPEN  
COOL_CLOSE  
HEAT_OPEN  
HEAT_CLOSE  
HEAT_COOL_STAGE_1  
HEAT_COOL_STAGE_2  
HEAT_COOL_STAGE_3  
HEAT_COOL_STAGE_4  
FREE1  
C
FREE2  
FREE1_PULSE_ON  
FREE1_PULSE_OFF  
ECON_PWM  
W
HEAT_PWM  
COOL_PWM  
,
UNUSED  
C
nciIoSelect  
nciIoSelect  
nciIoSelect  
nciIoSelect  
nciIoSelect  
nciIoSelect  
nciIoSelect  
nciIoSelect  
DigitalOut[1]  
DigitalOut[2]  
DigitalOut[3]  
DigitalOut[4]  
DigitalOut[5]  
DigitalOut[6]  
DigitalOut[7]  
HtPump  
See DigitalOut[0] enumerated  
values  
1-31 FAN_OUT  
X
X
X
X
X
X
X
See DigitalOut[0] for enumerated names. The W7750 Controllers are  
configured at the factory with the enumerated value in the Default column.  
,255 (Value of State is 10)  
NST  
See DigitalOut[0] enumerated  
values  
1-31 COOL_STAGE_2  
,255 (Value of State is 2)  
See DigitalOut[0] for enumerated names. The W7750 Controllers are  
configured at the factory with the enumerated value in the Default column.  
NTV  
See DigitalOut[0] enumerated  
values  
1-31 HEAT_STAGE_1  
,255 (Value of State is 1)  
See DigitalOut[0] for enumerated names. The W7750 Controllers are  
configured at the factory with the enumerated value in the Default column.  
See DigitalOut[0] enumerated  
values  
1-31 HEAT_STAGE_2  
,255 (Value of State is 3)  
See DigitalOut[0] for enumerated names. The W7750 Controllers are  
configured at the factory with the enumerated value in the Default column.  
See DigitalOut[0] enumerated  
values  
1-31 HEAT_STAGE_1  
,255 (Value of State is 5)  
See DigitalOut[0] for enumerated names. The W7750 Controllers are  
configured at the factory with the enumerated value in the Default column.  
AHUCO  
See DigitalOut[0] enumerated  
values  
1-31 UNUSED  
,255 (Value of State is 255)  
See DigitalOut[0] for enumerated names. The W7750 Controllers are  
configured at the factory with the enumerated value in the Default column.  
See DigitalOut[0] enumerated  
values  
1-31 UNUSED  
,255 (Value of State is 255)  
See DigitalOut[0] for enumerated names. The W7750 Controllers are  
configured at the factory with the enumerated value in the Default column.  
N
R
CONV  
HP  
0
1
CONV  
P
X
HtPump specifies the type of equipment being controlled. When HtPump is  
0 (CONV), the node is controlling conventional gas or electric heat. When  
HtPump is 1 (HP), the node is controlling a heat pump.  
R
Download from Www.Somanuals.com. All Manuals Search And Download.  
E
Table 20. Input/Output Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
W
Engineering Units: English  
User Address  
NvName  
nciIoSelect  
Field Name  
FiftySixtyHz  
(Metric) or States plus Range  
Default  
Comments  
SIXTYFIFTY  
01 SIXTY  
P
X
X
FiftySixtyHz specifies the frequency of the main power input for the  
controller. Correctly selecting the FiftySixtyHz decreases the noise picked  
up by analog switch wiring from the power mains. When FiftySixtyHz is 0  
(SIXTY is the default), the mains frequency is sixty Hz and when  
FiftySixtyHz is 1 (FIFTY), the mains frequency is fifty Hz.  
O
NST  
nciIoSelect  
nvoIO  
SpaceSensorType  
siSetPointTempS7  
T7770  
0
T7770  
X
SpaceSensorType specifies the type of space temperature sensor  
connected to the node. When SpaceSensorType is 0, a T7770 sensor is  
connected to the sensor terminals. No other options are currently valid.  
NTV  
RmtStptPot  
Degrees F  
-9 to 85  
Degrees C  
(-23 to 29)  
SI_INVALID  
M,  
S
X
X
SetPointTemp is the wall module setpoint temperature. When  
nciConfig.SetPointTemp is ABSOLUTE_COOL or ABSOLUTE_MIDDLE,  
the reported value is the absolute setpoint temperature. When  
Config.SetPntKnob is OFFSET, the reported value is the offset (from the  
current active TempSetPts) temperature. If the input is not configured or  
has failed, the value is SI_INVALID.  
MEAHUCO  
RmTempSensr nvoIO  
siSpaceTempS7  
Degrees F  
40 to 100  
Degrees C  
(4 to 38)  
SI_INVALID  
M,  
S
SpaceTemp is the measured space temperature. If the sensor is not  
configured or has failed, the value is SI_INVALID.NOTE: The reported  
temperatures includes the offset correction provided by  
Config.ResistiveOffsetCal.  
N
R
DaTempSensr nvoIO  
RaTempSensr nvoIO  
siDischargeTempS7 Degrees F  
30 to 122  
Degrees C  
(-1 to 50)  
SI_INVALID  
SI_INVALID  
SI_INVALID  
DischargeTemp is the measured discharge air temperature. If the sensor is  
not configured or has failed, the value is SI_INVALID. Refer to the note on  
SpaceTemp.  
E
siReturnTempS7  
ReturnHumidity  
Degrees F  
30 to 122  
Degrees C  
(-1 to 50)  
ReturnTemp is the measured return air temperature. If the sensor is not  
configured or has failed, the value is SI_INVALID. Refer to the note on  
SpaceTemp.  
RaHumSensr  
RaEnthSensr  
nvoIO  
nvoIO  
Percentage  
10 to 90  
ReturnHumidity is the measured return air humidity. If the sensor is not  
configured or has failed, the value is UB_INVALID.NOTE: The reported  
temperatures includes the offset correction provided by  
Config.VoltageOffsetCal.  
siReturnEnthalpyS7 mA  
4 to 20  
SI_INVALID  
ReturnEnthalpy is the measured return air enthalpy. If the sensor is not  
configured or has failed, the value is SI_INVALID. Since the C7400 reports  
comfort due to enthalpy (btu/lb) in milliamps, enthalpy is also reported in  
milliamps. Refer to the NOTE on ReturnHumidity.  
OaTempSensr nvoIO  
siOutdoorTempS7  
OutdoorHumidity  
Degrees F  
-40 to 122  
Degrees C  
(-40 to 50)  
SI_INVALID  
SI_INVALID  
SI_INVALID  
M,  
S
OutdoorTemp is the measured outdoor air temperature. If the sensor is not  
configured or has failed, the value is SI_INVALID. Refer to the NOTE on  
ReturnHumidity.  
OaHumSensr  
OaEnthSensr  
nvoIO  
nvoIO  
Percentage  
10 to 90  
M,  
S
OutdoorHumidity is the measured outdoor air humidity. If the sensor is not  
configured or has failed, the value is UB_INVALID. Refer to the NOTE on  
ReturnHumidity.  
siOutdoorEnthalpyS7 mA  
4 to 20  
M,  
S
OutdoorEnthalpy is the measured outdoor air enthalpy. If the sensor is not  
configured or has failed, the value is SI_INVALID. Since the C7400 reports  
comfort due to enthalpy (btu/lb) in milliamps, enthalpy is also reported in  
milliamps. Refer to the NOTE on ReturnHumidity.  
FltrPressSensr nvoIO  
siFilterPressureS10 inw (kPa)  
0 to 5 (0 to 1.25)  
SI_INVALID  
FilterPressure is the measured differential pressure across the return air  
filter. If the sensor is not configured or has failed, the value is the  
SI_INVALID. Refer to the NOTE on ReturnHumidity.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
                   
Table 20. Input/Output Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
nvoIO  
Field Name  
Default  
SI_INVALID  
Comments  
CO2Sensr  
siSpaceCo2S0  
PPM  
150 to 2000  
SpaceCo2 is the measured CO2 in the conditioned air space. If the sensor  
is not configured or has failed, the value is SI_INVALID. Refer to the NOTE  
on ReturnHumidity.  
MonitorSensr  
StatusDO1  
nvoIO  
nvoIO  
siMonitorS10  
volts  
SI_INVALID  
FALSE  
Monitor is the voltage applied at the monitor inputs terminals. If the sensor  
is not configured or has failed, the value is SI_INVALID. Refer to the NOTE  
on ReturnHumidity.  
1 to 10  
ubOut  
FALSE  
TRUE  
0
1
DigitalOut1 is a byte with a bit for every physical digital output. On is a 1  
(TRUE) and off is a 0 (FALSE).  
Byte Offset = 24  
Bit Offset =  
0(DigitalOut1)  
StatusDO2  
StatusDO3  
StatusDO4  
StatusDO5  
StatusDO6  
StatusDO7  
StatusDO8  
StatusDI1  
StatusDI2  
nvoIO  
nvoIO  
nvoIO  
nvoIO  
nvoIO  
nvoIO  
nvoIO  
nvoIO  
nvoIO  
ubOut  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
DigitalOut2 is a byte with a bit for every physical digital output. On is a 1  
Byte Offset = 24  
Bit Offset =  
1(DigitalOut2)  
(TRUE) and off is a 0 (FALSE).  
ubOut  
FALSE  
TRUE  
0
1
DigitalOut3 is a byte with a bit for every physical digital output. On is a 1  
(TRUE) and off is a 0 (FALSE).  
Byte Offset = 24  
Bit Offset =  
2(DigitalOut3)  
E
ubOut  
FALSE  
TRUE  
0
1
DigitalOut4 is a byte with a bit for every physical digital output. On is a 1  
(TRUE) and off is a 0 (FALSE).  
Byte Offset = 24  
Bit Offset =  
3(DigitalOut4)  
W
ubOut  
FALSE  
TRUE  
0
1
DigitalOut5 is a byte with a bit for every physical digital output. On is a 1  
(TRUE) and off is a 0 (FALSE).  
Byte Offset = 24  
Bit Offset =  
4(DigitalOut5)  
,
,
ubOut  
FALSE  
TRUE  
0
1
DigitalOut6 is a byte with a bit for every physical digital output. On is a 1  
(TRUE) and off is a 0 (FALSE).  
Byte Offset = 24  
Bit Offset =  
5(DigitalOut6)  
NST  
ubOut  
FALSE  
TRUE  
0
1
DigitalOut7 is a byte with a bit for every physical digital output. On is a 1  
(TRUE) and off is a 0 (FALSE).  
NTV  
Byte Offset = 24  
Bit Offset =  
6(DigitalOut7)  
ubOut  
FALSE  
TRUE  
0
1
DigitalOut8 is a byte with a bit for every physical digital output. On is a 1  
(TRUE) and off is a 0 (FALSE).  
Byte Offset = 24  
Bit Offset =  
7(DigitalOut8)  
AHUCO  
ubDigitalIn  
FALSE  
TRUE  
0
1
DigitalIn1 is a byte with a bit for every physical digital input. If the input is  
shorted to ground, the bit is a zero or FALSE. If the input is open, the bit is  
one or TRUE.  
Byte Offset = 25  
Bit Offset =  
N
7(DigitalIn1)  
R
ubDigitalIn  
Byte Offset = 25  
Bit Offset =  
FALSE  
TRUE  
0
1
DigitalIn2 is a byte with a bit for every physical digital input. If the input is  
shorted to ground, the bit is a zero or FALSE. If the input is open, the bit is  
one or TRUE.  
E
6(DigitalIn2)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
                       
E
Table 20. Input/Output Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
W
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
nvoIO  
Field Name  
ubDigitalIn  
Byte Offset = 25  
Bit Offset =  
5(DigitalIn3)  
Default  
Comments  
StatusDI3  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
FALSE  
DigitalIn3 is a byte with a bit for every physical digital input. If the input is  
shorted to ground, the bit is a zero or FALSE. If the input is open, the bit is  
one or TRUE.  
,
NST  
StatusDI4  
Model  
nvoIO  
nvoIO  
ubDigitalIn  
FALSE  
TRUE  
0
1
DigitalIn4 is a byte with a bit for every physical digital input. If the input is  
shorted to ground, the bit is a zero or FALSE. If the input is open, the bit is  
one or TRUE.  
Byte Offset = 25  
Bit Offset =  
NTV  
4(DigitalIn4)  
ubDigitalIn  
FALSE  
TRUE  
0
1
X
ExtenedModelIn is a byte with a bit for every physical digital input. If the  
input is shorted to ground, the bit is a zero or FALSE. If the input is open,  
the bit is one or TRUE.  
Byte Offset = 25  
Bit Offset = 3  
MEAHUCO  
(ExtenedModelIn)  
OvrdSw  
nvoIO  
nvoIO  
OverRide  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
OverRide indicates the status of the wall module override pushbutton. It is 1  
(TRUE) if the button is pressed, and is 0 (FALSE) if it isn't pressed.  
OccSensr  
OccupancySensor  
FALSE  
TRUE  
0
1
M,  
S
OccupancySensor is the state of the digital input configured and wired to  
the local occupancy sensor. 1 means that occupancy is being sensed (input  
circuit shorted) and 0 means that no occupancy is being sensed (input  
circuit open).  
N
R
TimeClkSw  
nvoIO  
OccTimeClock  
FALSE  
TRUE  
0
1
FALSE  
M,  
S
OccTimeClock is the state of the digital input configured and wired to a time  
clock. 1 (input shorted) means that the scheduled occupancy is  
OC_OCCUPIED, and 0 (input open circuited) means that the scheduled  
occupancy is OC_UNOCCUPIED.  
E
StatusAirFlow nvoIO  
ProofAirFlow  
EconEnableIn  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
ProofAirFlow is the state of the digital input configured and wired to the  
proof of air flow switch. 1 (input shorted) means that air flow is detected and  
0 (input open circuited) means that air flow is not detected.  
EconEnSw  
IaqOvrSw  
nvoIO  
nvoIO  
FALSE  
TRUE  
0
1
M,  
S
EconEnableIn is the state of the digital input configured and wired to the  
outdoor air sensor that determines the suitably of outdoor air for free  
cooling. 1 (input shorted) means that the outdoor air is suitable for cooling,  
and 0 (input open) means that the outdoor air in not suitable for cooling.  
IaqOverRide  
FALSE  
TRUE  
0
1
FALSE  
M,  
S
IaqOverRide is the state of the digital input configured and wired to the  
indoor air quality sensor. 1 (input shorted) means that the indoor air quality  
is poor, and 0 (input open) means that the indoor air quality is acceptable.  
This input is used to cause the economizer to open to a predetermined  
position when poor indoor air quality is detected.  
SmokeMonSw nvoIO  
SmokeMonitor  
DirtyFilter  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
FALSE  
M,  
S
SmokeMonitor is the state of the digital input configured and wired to the  
indoor smoke sensor. 1 (input shorted) means that smoke is detected, and  
0 (input open) means that no smoke is detected.  
DrtyFilterSw  
nvoIO  
nvoIO  
FALSE  
TRUE  
0
1
M,  
S
DirtyFilter is the state of the digital input configured and wired to the dirty  
filter sensor. 1 (input shorted) means that filter is dirty, and 0 (input open)  
means that the filter is not dirty.  
ShutDownSw  
ShutDown  
FALSE  
TRUE  
0
1
ShutDown is the state of the digital input configured and wired to the shut  
down switch. 1 (input shorted) means that equipment should be shut down,  
and 0 (input open) means that the equipment should be running.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
                   
Table 20. Input/Output Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
nvoIO  
Field Name  
WindowOpen  
Default  
Comments  
WindowSw  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
FALSE  
M,  
S
WindowOpen is the state of the digital input configured and wired to a  
window open sensor switch. 1 (input open circuit) means that the window is  
open, and 0 (input shorted) means that the window is closed.  
MonitorSw  
ModelSw  
nvoIO  
nvoIO  
MonSwitch  
Model  
FALSE  
TRUE  
0
1
MonSwitch is the state of the digital input configured and wired to a general  
purpose monitor switch. 1 (input shorted) means that switch is closed, and  
0 (input open) means that the switch is open.  
FALSE  
TRUE  
0
1
X
X
Model indicates the Model of the node. One of the digital inputs is  
connected to a printed wiring board trace to let the embedded software  
know what kind of hardware is present. If Model is 1 (input held high), the  
hardware is the W7750B Model. If Model is 0 (input shorted to ground), the  
hardware is the W7750A Model.  
nvoIO  
SchedMaster  
FALSE  
TRUE  
0
1
FALSE  
M
If ScheduleMaster is 1 (input shorted), the node is the schedule master and  
the locally connected time clock will be sent via TimeClk to other nodes on  
the network. If ScheduleMaster is 0, (input open), the node is not a  
schedule master and nvoTimeClk will not be sent on the network even if the  
time clock input is configured. If the ScheduleMaster input is not configured  
by Select, TimeClk reports the state of the locally connected time clock.  
L
Table 21. Control Parameters.  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
W
Engineering Units: English  
(Metric) or States plus Range  
,
User Address  
NvName  
Field Name  
Default  
Comments  
,
DaTempLoLim  
nciAux1SetPt  
siLowLimitDischAirTempS7 Degrees F  
45  
P
X
X
When the discharge air temperature falls below  
0 to 60  
LowLimitDischAirTemp, the outdoor air dampers are closed to a  
position that corrects the low temperature problem. If mechanical  
cooling is active when the discharge air falls below  
LowLimitDischAirTemp, the mechanical cooling cycles off after the  
minimum run times are obeyed to allow the dampers to return open  
and provide free cooling.  
NST  
Degrees C  
(-1 to 16)  
NTV  
DaTempHiLim  
DlcBumpTemp  
nciAux1SetPt  
nciAux1SetPt  
siMaxDisAirTempHeatS7 Degrees F  
65 to 135  
Degrees C  
(18 to 57)  
100  
3
P
P
P
X
X
X
X
X
X
When the mode is HEAT, and the CascadeControl is enabled, the  
discharge air temperature is controlled to a value not to exceed  
MaxDisAirTempHeat.  
siDlcBumpTempS7  
Degrees F  
0 to +10  
Degrees C  
(-18 to -12)  
When DlcShed is not 0 then the setpoint is shifted by DlcBumpTemp  
in the energy saving direction. When DlcShed changes from 1 to 0,  
the setpoint shift ramps back to 0 over a 30 minute interval.  
AHUCO  
OaTempHtLkOut nciAux1SetPt  
ubOdHtLockOutTempS0 Degrees F  
0 to 90  
Degrees C  
(-18 to 32)  
70  
When the outdoor air temperature is greater than  
OdHtLockOutTemp, the heating is disabled.  
N
R
E
Download from Www.Somanuals.com. All Manuals Search And Download.  
               
E
Table 21. Control Parameters. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
W
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
Field Name  
Default  
Comments  
MaxHtRamp  
nciAux1SetPt  
ubMaxHtRampS0  
Degrees F/Hr  
0 to 20  
8
P
X
X
MaxHtRamp is the maximum heat recovery ramp rate in degrees F  
per hour. This value is used to control the adaptive recovery ramp  
rate during the HEAT recovery period. The setpoint is changed at a  
rate in degrees F per hour depending on the outdoor air temperature  
andtheMinHtRamp,OdTempMaxHtRamp, andOaTempMinHtRamp  
parameters. If there is no outdoor air temperature sensor available,  
then ubMinHtRamp is used as the recovery rate.NOTE: Recovery  
ramping applies between scheduled heating or cooling setpoint  
changes from OC_UNOCCUPIED to OC_STANDBY,  
,
Degrees C/Hr  
(0 to 11)  
NST  
NTV  
OC_UNOCCUPIED to OC_OCCUPIED, and OC_STANDBY to  
OC_OCCUPIED. Scheduled setpoint changes from OC_OCCUPIED  
to OC_UNOCCUPIED or OC_OCCUPIED to OC_STANDBY do not  
use a ramped setpoint but instead use a step change in setpoint.  
Recovery ramps begin before the next scheduled occupancy time  
and are ramped from the setpoint for the existing scheduled  
occupancy state to the setpoint for the next occupancy state.  
MEAHUCO  
MinHtRamp  
nciAux1SetPt  
ubMinHtRampS0  
Degrees F/Hr  
0 to 20  
Degrees C/Hr  
(0 to 11)  
3
P
P
X
X
X
X
MinHtRamp is the minimum heat recovery ramp rate in degrees F  
per hour. This value is used to control the adaptive recovery ramp  
rate during the HEAT recovery period. The setpoint is changed at a  
rate in degrees F per hour depending on the outdoor air temperature  
and the MaxHtRamp, OdTempMaxHtRamp, and  
OdTempMinHtRamp parameters. If there is no outdoor air  
temperature sensor available, then MinHtRamp is used as the  
recovery rate. Refer to the NOTE in the comments column for  
MaxHtRamp for the conditions that recovery ramping applies to.  
N
R
E
OaTempMaxHtRp nciAux1SetPt  
OaTempMinHtRp nciAux1SetPt  
OaTempClLkOut nciAux1SetPt  
ubOdTempMaxHtRampS0 Degrees F  
40  
OdTempMaxHtRamp is the maximum outdoor air temperature  
parameter that is used to calculate the heat recovery ramp rate  
setpoint. This value is used to control the adaptive recovery ramp  
rate during the HEAT recovery period. The setpoint is changed at a  
rate in degrees F per hour depending on the outdoor air temperature  
and the MaxHtRamp, MinHtRamp, and OdTempMinHtRamp  
parameters. If there is no outdoor air temperature sensor available,  
then MinHtRamp is used as the recovery rate. Refer to the NOTE in  
the comments column for MaxHtRamp for what conditions that  
recovery ramping applies to.  
0 to 100  
Degrees C  
(-18 to 38)  
ubOdTempMinHtRampS0 Degrees F  
0
P
X
X
OdTempMinHtRamp is the minimum outdoor air temperature  
parameter that is used to calculate the heat recovery ramp rate  
setpoint. This value is used to control the adaptive recovery ramp  
rate during the HEAT recovery period. The setpoint is changed at a  
rate in degrees F per hour depending on the outdoor air temperature  
and the MaxHtRamp, MinHtRamp, and OdTempMaxHtRamp  
parameters. If there is no outdoor air temperature sensor available,  
then MinHtRamp is used as the recovery rate. Refer to the NOTE in  
the comments column for MaxHtRamp for what conditions that  
recovery ramping applies to.  
0 to 100  
Degrees C  
(-18 to 38)  
ubOdClLockOutTempS0 Degrees F  
0 to 90  
Degrees C  
(-18 to 32)  
50  
P
X
X
When the outdoor air temperature is less than OdClLockOutTemp,  
the cooling is disabled.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Table 21. Control Parameters. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
Field Name  
Default  
Comments  
MaxClRamp  
nciAux1SetPt  
ubMaxClRampS0  
Degrees F/Hr  
0 to 20  
Degrees C/Hr  
(0 to 11)  
6
P
P
P
X
X
X
X
X
X
MaxClRamp is the maximum cool recovery ramp rate in degrees F  
per hour. This value is used to control the adaptive recovery ramp  
rate during the COOL recovery period. The setpoint is changed at a  
rate in degrees F per hour depending on the outdoor air temperature  
and the MinClRamp, OdTempMaxClRamp, and OdTempMinClRamp  
parameters. If there is no outdoor air temperature sensor available,  
then MinClRamp is used as the recovery rate. Refer to the NOTE in  
the comments column for MaxHtRamp for the conditions that  
recovery ramping applies to.  
MinClRamp  
nciAux1SetPt  
ubMinClRampS0  
Degrees F/Hr  
0 to 20  
Degrees C/Hr  
(0 to 11)  
2
MinClRamp is the minimum cool recovery ramp rate in degrees F  
per hour. This value is used to control the adaptive recovery ramp  
rate during the COOL recovery period. The setpoint is changed at a  
rate in degrees F per hour depending on the outdoor air temperature  
and the MaxClRamp, OdTempMaxClRamp, and  
OdTempMinClRamp parameters. If there is no outdoor air  
temperature sensor available, then MinClRamp is used as the  
recovery rate. Refer to the NOTE in the comments column for  
MaxHtRamp for the conditions that recovery ramping applies to.  
L
OaTempMaxClRp nciAux1SetPt  
OaTempMinClRp nciAux1SetPt  
ubOdTempMaxClRampS0 Degrees F  
70  
OdTempMaxClRamp is the maximum outdoor air temperature  
parameter that is used to calculate the cool recovery ramp rate  
setpoint. This value is used to control the adaptive recovery ramp  
rate during the COOL recovery period. The setpoint is changed at a  
rate in degrees F per hour depending on the outdoor air temperature  
and the MaxClRamp, MinClRamp, and OdTempMinClRamp  
parameters. If there is no outdoor air temperature sensor available,  
then MinClRamp is used as the recovery rate. Refer to the NOTE in  
the comments column for MaxHtRamp for the conditions that  
recovery ramping applies to.  
0 to 100  
Degrees C  
(-18 to 38)  
7
,
,
ubOdTempMinClRampS0 Degrees F  
90  
P
X
X
OdTempMinClRamp is the minimum outdoor air temperature  
parameter that is used to calculate the cool recovery ramp rate  
setpoint. This value is used to control the adaptive recovery ramp  
rate during the COOL recovery period. The setpoint is changed at a  
rate in degrees F per hour depending on the outdoor air temperature  
and the MaxClRamp, MinClRamp, and OdTempMaxClRamp  
parameters. If there is no outdoor air temperature sensor available,  
then MinClRamp is used as the recovery rate. Refer to the NOTE in  
the comments column for MaxHtRamp for the conditions that  
recovery ramping applies to.  
0 to 100  
Degrees C  
(-18 to 38)  
NST  
NTV  
OaEconEnTemp nciAux1SetPt  
DiffEconEnTemp nciAux1SetPt  
ubOdEconEnableTempS0 Degrees F  
70  
P
P
X
X
X
X
If Config.EconEnable is OD_TEMP, and the outdoor temperature is  
less than OdEconEnableTemp, then outdoor air is judged suitable to  
augment mechanical cooling. If Config.EconEnable is  
SINGLE_ENTH and outdoor temperate is less than  
ubOdEconEnableTemp (high limit), then outdoor air may be judged  
suitable to augment mechanical cooling depending on the  
relationship between calculated outdoor enthalpy and  
OdEnthalpyEnable.  
0 to 90  
AHUCO  
Degrees C  
(-18 to 32)  
N
R
ubDiffEconEnableTempS0 Degrees F  
0 to 90  
Degrees C  
(-18 to 32)  
4
If Config.EconEnable is DIFF_TEMP, and return air temperature  
minus outdoor air temperature is greater than DiffEconEnableTemp,  
then outdoor air is judged suitable to augment mechanical cooling.  
R
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
E
Table 21. Control Parameters. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
W
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
Field Name  
Default  
Comments  
OaEnthEn  
nciAux1SetPt  
ubOdEnthalpyEnableS2  
btu/lb  
0 to 65  
25  
P
X
X
If Config.EconEnable is SINGLE_ENTH, and calculated outdoor  
enthalpy is less than OdEnthalpyEnable, and outdoor temperature is  
less than OdEconEnableTemp, then outdoor air is judged suitable to  
augment mechanical cooling.  
,
NST  
EconMinPos  
EconIAQPos  
IAQSetpt  
nciAux1SetPt  
nciAux1SetPt  
nciAux1SetPt  
ubEconMinPosS0  
ubEconIaqPosS0  
siCO2IaqLimitS0  
Percentage  
0 to 100  
0
P
P
P
X
X
X
X
X
X
The minimum allowed position of the economizer damper for HEAT  
and COOL is EconMinPos.  
NTV  
Percentage  
0 to 100  
80  
800  
The control overrides the economizer damper to EconIaqPos when  
poor indoor air quality is detected.  
PPM  
0 to 2000  
When an analog CO2 sensor is configured and the sensed CO2 is  
greater than CO2IaqLimit, then poor indoor air quality is detected  
and Data1.OverRide is set to 1. When the sensed CO2 is less than  
CO2IaqLimit, then the indoor air quality is considered acceptable  
and Data1.IaqOverRide is set to 0. oData1.IaqOverRide is used to  
set the economizer damper to Aux1SetPt. EconIaqPos and to  
possibly turn on the heat according to the state of  
MEAHUCO  
Config.IaqUseHeat.  
T
PwmPeriod  
PwmZeroScale  
PwmFullScale  
BypTime  
nciAux1SetPt  
nciAux1SetPt  
nciAux1SetPt  
nciAux2SetPt  
siPwmPeriodS4  
siPwm0pcntS4  
siPwm100pcntS4  
uiBypassTime  
100  
1
P
P
P
P
X
X
X
X
X
X
X
X
When pulse width modulation is used, the period of one pulse width  
modulation cycle is PwmPeriod seconds. The smallest resolution is  
0.1 seconds.  
R
E
Seconds  
0 to 2047  
When pulse width modulation is used, the period of a pulse for zero  
percent output (damper or valve at open position) is Pwm0pcntS4  
seconds. The smallest resolution is 0.1 seconds.  
Seconds  
0 to 2047  
99  
When pulse width modulation is used, the period of a pulse for full  
scale output (damper or valve at open position) is Pwm100pcnt  
seconds. The smallest resolution is 0.1 seconds.  
minutes  
0 to 1080  
180  
uiBypassTime is the time between the pressing of the override  
button at the wall module (or initiating OC_BYPASS via ManOcc)  
and the return to the original occupancy state. When the bypass  
state has been activated, the bypass timer is set to BypassTime.  
FltrPressStPt  
nciAux2SetPt  
ubFilterPressStPtS5  
siLowStPtS7  
inw (kPa)  
0.5  
55  
P
P
X
X
X
X
If a filter pressure sensor is configured by IoSelect and the filter  
pressure reported in Data1 FilterPressure exceeds FilterPressStPt,  
then a DIRTY_FILTER alarm is generated and Data1.DirtyFilter is  
set to 1.  
0 to 5 (0 to 1.25)  
StptKnobLowLim nciAux2SetPt  
Degrees F  
-9 to 90  
Degrees C  
(-23 to 32)  
LowStPt is the lowest value reported for the setpoint knob.  
Dependent on the configuration of the setpoint knob (see  
Config.SetPntKnob) this setting is either absolute [degree  
Fahrenheit (50 to 90)] in case of absolute setpoint knob configuration  
or relative [delta degree Fahrenheit (-9 to +9)] in case of relative  
setpoint knob configuration.  
StptKnobHiLim  
nciAux2SetPt  
siHighStPtS7  
Degrees F  
-9 to 90  
Degrees C  
(-23 to 32)  
85  
P
X
X
HighStPt is the highest value reported for the setpoint knob.  
Dependent on the configuration of the setpoint knob (see  
Config.SetPntKnob) this setting is either absolute [degree  
Fahrenheit (50 to 90)] in case of absolute setpoint knob configuration  
or relative [delta degree Fahrenheit (-9 to +9)] in case of relative  
setpoint knob configuration.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
                     
Table 21. Control Parameters. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
Field Name  
ubKpCoolS2  
Default  
Comments  
GainCoolProp  
nciAux2SetPt  
Degrees F  
2 to 30  
Degrees C  
(1 to 30)  
5
P
P
P
P
P
P
P
P
P
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
This is the throttling range for the proportional portion of the PID loop  
gain for the cooling control loop.  
GainHeatProp  
GainCoolInt  
GainHeatInt  
GainCoolDer  
GainHeatDer  
nciAux2SetPt  
nciAux2SetPt  
nciAux2SetPt  
nciAux2SetPt  
nciAux2SetPt  
ubKpHeatS2  
siKiCoolS0  
Degrees F  
2 to 30  
Degrees C  
(1 to 17)  
5
This is the throttling range for the proportional portion of the PID loop  
gain for the heating control loop.  
Seconds  
0 to 5000  
2050  
2050  
0
This is the integral portion of the PID loop gain for the cooling control  
loop.  
siKiHeatS0  
Seconds  
0 to 5000  
This is the integral portion of the PID loop gain for the heating control  
loop.  
siKdCoolS0  
Seconds  
0 to 9000  
This is the derivative portion of the PID loop gain for the cooling  
control loop.  
siKdHeatS0  
Seconds  
0 to 9000  
0
This is the derivative portion of the PID loop gain for the heating  
control loop.  
DaTempClCtrlBd nciAux2SetPt  
DaTempHtCtrlBd nciAux2SetPt  
DaTempEcCtrlBd nciAux2SetPt  
ubDisCbCoolS0  
ubDisCbHeatS0  
ubDisCbEconS0  
Degrees F  
5 to 30  
Degrees C  
(3 to 17)  
10  
10  
10  
DisCbCool is the throttling range used for the cooling portion of the  
discharge air temperature cascade control loop.  
Degrees F  
5 to 30  
Degrees C  
(3 to 17)  
DisCbHeat is the throttling range used for the heating portion of the  
discharge air temperature cascade control loop.  
E
Degrees F  
5 to 30  
Degrees C  
(3 to 17  
DisCbEcon is the throttling range used for the economizer control  
loop.  
7
,
,
NST  
NTV  
AHUCO  
N
R
E
Download from Www.Somanuals.com. All Manuals Search And Download.  
                 
E
Table 22. Energy Management Points.  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
W
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
nviDlcShed  
Field Name  
Default  
Comments  
,
DestDlcShed  
0 to 1  
0
M X X  
M X X  
X
X
X
X
X DlcShed is an input from an energy management system. When DlcShed is  
0, the temperature control algorithm operates in a normal mode. When  
DlcShed is non-zero, the setpoint is shifted by Aux1SetPt.DlcBumpTemp in  
the energy saving direction.  
NST  
DestSchedOcc  
nviTodEvent  
CurrentState  
OC_OCCUPIED  
OC_UNOCCUPIED  
OC_BYPASS  
OC_STANDBY  
OC_NUL  
0
OC_OCCUPIED  
X CurrentState indicates the current scheduled occupancy state to the node.  
CurrentState is used along with other occupancy inputs to calculate the  
effective occupancy of the node. The valid states and meaning are as  
follows: OC_OCCUPIED means the energy management system is  
specifying occupied. OC_UNOCCUPIED means the energy management  
system is specifying that the space is presently unoccupied. OC_BYPASS  
states that the energy management system is in bypass. OC_STANDBY  
states that the energy management system has the space presently is  
between occupied and unoccupied. OC_NUL states that no occupancy  
state has been specified.  
NTV  
1
2
3
255  
MEAHUCO  
TodEventNext  
Tuncos  
nviTodEvent  
NextState  
OC_OCCUPIED  
OC_UNOCCUPIED  
OC_BYPASS  
OC_STANDBY  
OC_NUL  
0
OC_OCCUPIED  
M
M
X
X
X
X
NextState indicates the next scheduled occupancy state to the node. This  
information is required by the Excel 10 to perform the optimum start  
strategy. The space expected effective occupancy will be NextState in  
uiTimeToNextState minutes. The valid states and meaning are the same as  
for CurrentState.  
T
1
2
3
255  
R
E
nviTodEvent  
nviBypass  
uiTimeToNextState minutes  
0 to 2880  
0
0
TimeToNextState is the time in minutes until the next change of scheduled  
occupancy state.  
value  
0 to 100  
Bypass.value:The bypass state of one node may be shared with the bypass  
state of another node using nviBypass and nvoBypass. This allows a wall  
module at one node to be used to over ride the scheduled occupancy of  
another node. The node with Bypass bound normally does not have a wall  
module. See the Data1.EffectOcc and Data1.OverRide for more details.  
The valid states are as follows: If the state is SW_ON and the value is not  
zero then the node should bypass the time of day schedule (subject to  
occupancy arbitration logic). If the state is SW_NUL, the input is not  
available because it is not bound, the input is no longer being updated by  
the sender, or OC_BYPASS is no longer being called. This means that the  
same as SW_OFF. If the state is SW_OFF or other and the value is don’t  
care, the node should not bypass the time of day schedule. If the state is  
SW_ON and the value is 0, then the node should not bypass the time of day  
schedule. If the node receives this combination of state and value, then  
state is set to SW_OFF.  
DestBypass  
SrcBypCt  
nviBypass  
nvoBypass  
state  
value  
SW_OFF  
SW_ON  
SW_NUL  
0
SW_NUL  
0
M X  
X
X
X
X Refer to nviBypass.value.  
1
255  
0 to 100  
nvoBypass.value:nvoBypass is the current occupancy state of the node for  
bypass schedule. The states have the following meanings: If the state is  
SW_OFF and the value is 0, then Data1.EffectOcc is not OC_BYPASS. If  
the state is SW_ON and the value is 100 percent, then Data1.EffectOcc is  
OC_BYPASS.  
SrcBypass  
nvoBypass  
state  
SW_OFF  
SW_ON  
SW_NUL  
0
1
255  
SW_NUL  
M X  
Refer to nvoBypass.value.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
               
Table 22. Energy Management Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
nviFree1  
Field Name  
value  
Default  
Comments  
0 to 100  
0
Free1.value network variable controls the spare or Free digital output for  
auxiliary functions. nviFree1 controls the FREE1_OUT,  
FREE1_OUT_PULSE_ON, and FREE1_OUT_PULSE_OFF outputs (only  
one of these DO selections per controller is allowed). The states have the  
following meaning: If the state is SW_OFF, the corresponding free logical  
output (and therefore the physical output, if configured) is off. If the state is  
SW_ON and the value is 0, then the corresponding free logical output (and  
therefore the physical output, if configured) is off. If the node receives this  
combination of state and value, then state is set to SW_OFF. If the state is  
SW_ON and the value is not zero, then the corresponding free logical  
output (and therefore the physical output, if configured) is on. If the state is  
SW_NUL or other, then the network variable is not bound, the  
communications path from the sending node has failed, or the sending node  
has failed. The corresponding free logical output does not change if the  
network variable input fails.  
DestFree1  
DestFree2  
nviFree1  
state  
SW_OFF  
SW_ON  
SW_NUL  
0
SW_NUL  
M X  
M X  
X
X
X
X
X Refer to Free1.value.  
1
255  
X
nviFree2  
nviFree2  
value  
state  
0 to 100  
0
Free2.value behaves the same as Free 1 value.  
X Refer to Free2.value.  
SW_OFF  
SW_ON  
SW_NUL  
0
1
SW_NUL  
255  
W
nviWSHPEnable value  
0 to 100  
0
WSHPEnable.value is used to enable the compressor stages in heat pump  
applications. Typically nviWSHPEnable is bound to a water flow sensor that  
detects heating/cooling water supplied to the heat pump. If there is no water  
flowing the compressor is disabled. If the state is SW_OFF, the compressor  
is disabled in heat pump applications. If the state is SW_ON and the value  
is 0, the compressor is disabled in heat pump applications. If the node  
receives this combination of state and value, then state is set to SW_OFF. If  
the state is SW_ON and the value is not zero, the compressor is enabled in  
heat pump applications. If the state is SW_NUL or other, the network  
variable is not bound and is ignored.  
,
C
NST  
DestWSHPEnable nviWSHPEnable state  
SW_OFF  
SW_ON  
SW_NUL  
0
SW_NUL  
X Refer to WSHPEnable.value.  
NTV  
1
255  
AHUCO  
N
R
E
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
E
Table 22. Energy Management Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
W
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
nviTimeClk  
Field Name  
value  
Default  
Comments  
0 to 100  
0
nviTimeClk.value:nviTimeClk allows a time clock at one node to be shared  
with other nodes over the network. nviTimeClk is ORed with the local time  
clock sensor and the results are placed in Data1.OccTimeClock. TimeClk is  
received from another node and may have the following values: If the state  
is SW_OFF, the space is scheduled to be unoccupied. If the state is  
SW_ON and the value is 0, the space is scheduled to be unoccupied. If the  
node receives this combination of state and value, then state is set to  
SW_OFF. If the state is SW_ON and the value is not zero, the space is  
scheduled to be occupied. If the state is SW_NUL or other and the value is  
dont care, the network variable is not bound and is ignored.  
,
NST  
NTV  
DestTimeClk  
SrcTimeClkCt  
nviTimeClk  
nvoTimeClk  
state  
value  
SW_OFF  
SW_ON  
SW_NUL  
0
SW_NUL  
0
X Refer to nviTimeClk.value.  
MEAHUCO  
1
255  
0 to 100  
nvoTimeClk reports the current state of the physical time clock input. The  
output values have the following meanings: If the state is SW_OFF and the  
value is 0, the time clock input is configured and the input is open circuit. If  
SCHEDULE_MASTER_IN is configured, then the schedule master input  
must be shorted to ground to reach this state. If the state is SW_ON and the  
value is 100 precent, the time clock input is configured and the input is a  
closed circuit. If SCHEDULE_MASTER_IN is configured, then the schedule  
master input must be shorted to ground to reach this state. If the state is  
SW_NUL and the value is 0, the time clock input is not configured by Select  
or the SCHEDULE_MASTER_IN physical input is configured and the input  
is open (nvoIO.ScheduleMaster = 0).  
N
O
E
SrcTimeClk  
nvoTimeClk  
state  
SW_OFF  
SW_ON  
SW_NUL  
0
SW_NUL  
Refer to nvoTimeClk.value.  
1
255  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Table 23. Status Points.  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
nroPgmVer  
Field Name  
Default  
Comments  
id[  
RTU1  
R A four byte ASCII string indicating the type of node (model).  
O
M
nroPgmVer  
nroPgmVer  
nroPgmVer  
nroPgmVer  
major_ver  
minor_ver  
bug_ver  
1
0
0
1
R Software version.  
O
M
R Software version.  
O
M
R Software version.  
O
M
node_type  
R The NodeType is a numeric identifier that is stored in EPROM that identifies  
O the Excel 10 node type. Whenever a new software version or upgrade is  
M issued, this is reflected in nroPgmVer which typically is read by a network  
management node to identify the node type. The contents of nroPgmVer  
contain compatible model type information and is fixed at the time when the  
node software is compiled.  
E
SrcEmerg  
nvoEmerg  
EMERG_NORMAL  
EMERG_PRESSURIZE  
EMERG_DEPRESSURIZE  
EMERG_PURGE  
EMERG_SHUTDOWN  
EMERG_NUL  
0
EMERG_NORMAL  
M X  
X
Emerg is an emergency output reflecting the state of the locally wired  
smoke detector. If Emerg is EMERG_NORMAL, then no smoke is being  
detected by the local sensor or that the smoke detector input is not  
configured. If Emerg is EMERG_PURGE, the locally wired smoke sensor is  
indicating a smoke condition.EMERG_PRESSURIZE,  
EMERG_DEPRESSURIZE, and EMERG_SHUTDOWN are not supported  
by Emerg. If Emerg is not configured then it is set to EMERG_NUL  
1
W
2
3
4
255  
B
,
ON ORKS  
subnet number (in domain entry 1 of the nodes  
nvoAlarm  
nvoAlarm  
nvoAlarm  
subnet  
node  
type  
1 to 255  
0 to 127  
0 to 255  
0
0
0
subnet is the L  
W
domain table) to which the node is assigned.  
ON ORKS  
node number (in domain entry 1 of the nodes  
node is the L  
W
NST  
domain table) assigned to the node.  
type is the alarm type being issued. When an alarm condition is no longer  
TRUE, type is set to the sum of the alarm conditions numeric value and the  
RETURN_TO_NORMAL numeric value. The type also is recorded in  
AlarmLog. When a new alarm is detected, just the corresponding numeric  
value for the alarm is reported. Refer to Table 12 (Excel 10 Alarms) in the  
System Engineering Guide for all the error conditions that may be reported.  
NTV  
StatusAlmTyp  
nvoAlarmStatus alarm_bit[0]  
Byte Offset = 0  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
X
X
alarm_bit[0]Byte Offset = 0Bit Offset = 0(InputNVFailAlrm)alarm_bit [n]  
contains a bit for every possible alarm condition. Each alarm type has a  
corresponding bit in alarm_bit[n] (Alarm.type: 1.24, without  
RETURN_TO_NORMAL).  
AHUCO  
Bit Offset =  
0(InputNVFailAlrm)  
nvoAlarmStatus alarm_bit[0]  
Byte Offset = 0  
FALSE  
TRUE  
0
1
alarm_bit[0]  
N
Byte Offset = 0  
Bit Offset = 1  
R
Bit Offset = 1  
(NodeDisableAlrm)  
(NodeDisableAlrm)  
R
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
E
Table 23. Status Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
W
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
Field Name  
Default  
Comments  
nvoAlarmStatus alarm_bit[0]  
Byte Offset = 0  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
alarm_bit[0]  
O
Byte Offset = 0  
Bit Offset = 2  
Bit Offset = 2  
(SensorFailAlrm)  
(SensorFailAlrm)  
NST  
nvoAlarmStatus alarm_bit[0]  
Byte Offset = 0  
FALSE  
TRUE  
0
1
alarm_bit[0]  
Byte Offset = 0  
Bit Offset = 3  
NTV  
Bit Offset = 3  
(FrostProtectAlrm)  
(FrostProtectAlrm)  
nvoAlarmStatus alarm_bit[0]  
Byte Offset = 0  
FALSE  
TRUE  
0
1
alarm_bit[0]  
Byte Offset = 0  
Bit Offset = 4  
MEAHUCO  
Bit Offset = 4  
(InvalidSetPtAlrm)  
(InvalidSetPtAlrm)  
nvoAlarmStatus alarm_bit[0]  
Byte Offset = 0  
FALSE  
TRUE  
0
1
alarm_bit[0]  
Byte Offset = 0  
Bit Offset = 5  
Bit Offset = 5  
(LossAirFlowAlrm)  
(LossAirFlowAlrm)  
N
nvoAlarmStatus alarm_bit[0]  
Byte Offset = 0  
FALSE  
TRUE  
0
1
alarm_bit[0]  
O
Byte Offset = 0  
Bit Offset = 6  
(DirtyFilterAlrm)  
Bit Offset = 6  
(DirtyFilterAlrm)  
E
nvoAlarmStatus alarm_bit[0]  
Byte Offset = 0  
FALSE  
TRUE  
0
1
alarm_bit[0]  
Byte Offset = 0  
Bit Offset = 7  
(SmokeAlrm)  
Bit Offset = 7  
(SmokeAlrm)  
nvoAlarmStatus alarm_bit[1]  
Byte Offset = 1  
FALSE  
TRUE  
0
1
alarm_bit[1]  
Byte Offset = 1  
Bit Offset = 0  
Bit Offset = 0  
(IaqOverRideAlrm)  
(IaqOverRideAlrm)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 23. Status Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
Engineering Units: English  
User Address  
NvName  
Field Name  
(Metric) or States plus Range  
Default  
NO_ALARM  
Comments  
AlarmLog1  
nvoAlarmLog  
type[0]  
0 to 255  
(AlarmTypeLog0)  
(AlarmTypeLog1)  
(AlarmTypeLog2)  
(AlarmTypeLog3)  
(AlarmTypeLog4)  
NO_ALARM  
INPUT_NV_FAILURE  
NODE_DISABLED  
SENSOR_FAILURE  
FROST_PROTECTION  
INVALID_SET_POINT  
LOSS_OF_AIR_FLOW  
DIRTY_FILTER  
0
X
ype[0]  
1
0 to 255  
2
(AlarmTypeLog0)  
3
(AlarmTypeLog1)  
4
(AlarmTypeLog2)  
5
(AlarmTypeLog3)  
6
(AlarmTypeLog4)  
7
A supervisory node may poll the AlarmLog output for a short alarm history.  
The last five alarm reports sent via nvoAlarm are reported via AlarmLog.  
When ALARM_NOTIFY_DISABLED is entered into the log, further alarms  
or return to normals are not entered into the log, until alarm reporting is  
again enabled. If Alarm is bound and not being acknowledged, the last  
alarm report entered into AlarmLog is the one that was not  
acknowledged.See Alarm and AlarmStatus for related subjects.type [n]  
specifies the alarm that was issued via Alarm. See Alarm for the alarm  
types used in AlarmLog. The newest alarm is reported in type[0] and the  
oldest is reported in type[4]. When a new entry is made to the log, the  
oldest entry is lost.  
SMOKE_ALARM  
IAQ_OVERRIDE  
8
9
LOW_LIM_ECON_CLOSE  
rINPUT_NV_FAILURE  
rNODE_DISABLED  
rSENSOR_FAILURE  
rFROST_PROTECTION  
rINVALID_SET_POINT  
rLOSS_OF_AIR_FLOW  
rDIRTY_FILTER  
rSMOKE_ALARM  
rIAQ_OVERRIDE  
rLOW_LIM_ECON_CLOSE  
ALARM_NOTIFY_DISABLED  
10  
129  
130  
131  
132  
133  
134  
135  
136  
137  
138  
255  
L
nvoData1  
(nvoCtlDataG1)  
FieldNo  
UPDATE_ALL_FIELDS  
MODE_FIELD  
EFFECT_OCC_FIELD  
OVERRIDE_FIELD  
SCHED_OCC_FIELD  
OCC_TIME_CLOCK_FIELD  
NET_MAN_OCC_FIELD  
SEN_OCC_FIELD  
ECON_ENABLE_FIELD  
PROOF_AIR_FLOW_FIELD  
0
1
2
3
4
5
6
7
8
9
UPDATE_ALL_FIELDS  
FieldNo: nvoData1 and nvoCtlDataG1 are output network variables  
indicating the node status. The information contained in these network  
variables are typically used to display the node status on an operator  
terminal, used in a trend log, or used in a control process. The information  
contained in nvoCtlDataG1 and nvoData1 are identical. nvoCtlDataG1 uses  
the SGPUC mechanism to update the status or values. The fields in  
nvoData are updated when network variables are polled by the receiver.  
Then every six seconds the difference between the field in nvoData and  
nvoCtlDataG is calculated. If the difference is significant the field is updated  
according to the SGPUC mechanism. FieldNo indicates which other data  
field in the SGPUC network variable has changed since the last time it was  
sent on the network according to the SGPUC mechanism. If FieldNo is  
UPDATE_ALL_FIELDS, then all fields have been updated. If FieldNo is  
UPDATE_NO_FIELDS, then no fields have been updated recently.  
W
,
,
CALC_OD_ENTHALPY_FIELD 10  
CALC_RA_ENTHALPY_FIELD 11  
NST  
HEAT_STAGES_ON_FIELD  
COOL_STAGES_ON_FIELD  
FREE1_OUT_FIELD  
12  
13  
14  
15  
16  
17  
18  
NTV  
FREE2_OUT_FIELD  
OCC_STATUS_OUT_FIELD  
FAN_ON_FIELD  
AUX_ECON_OUT_FIELD  
ECON_FLOAT_SYNCH_FIELD 19  
AHUCO  
DLC_SHED_FIELD  
20  
21  
22  
23  
24  
25  
26  
27  
127  
IAQ_OVERRIDE_FIELD  
SMOKE_MONITOR_FIELD  
WINDOW_OPEN_FIELD  
DIRTY_FILTER_FIELD  
SHUTDOWN_FIELD  
N
R
MON_SWITCH_FIELD  
WSHP_ENABLE_FIELD  
UPDATE_NO_FIELDS  
E
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
E
Table 23. Status Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
W
Engineering Units: English  
User Address  
NvName  
Field Name  
Mode  
(Metric) or States plus Range  
Default  
Comments  
StatusMode  
nvoData1  
(nvoCtlDataG1)  
START_UP_WAIT  
HEAT  
COOL  
OFF_MODE  
DISABLED_MODE  
EMERG_HEAT  
SMOKE_EMERGENCY  
FREEZE_PROTECT  
MANUAL  
FACTORY_TEST  
FAN_ONLY  
0
1
2
3
4
5
6
7
8
9
10  
START_UP_WAIT  
X
Mode: The result of the controller determining which mode of operation it  
currently is in. At each power-up, the controller remains in the Start-Up and  
Wait mode (a random time from 0 to 20 minutes that is based on the units  
network number). After that period, the mode changes to initialize actuators  
that will fully close the damper and valve actuators to insure full travel when  
under program control. The various other modes are due to normal  
operation as well as manual and network commands.  
O
NST  
NTV  
MEAHUCO  
StatusOcc  
nvoData1  
EffectOcc  
Override  
OC_OCCUPIED  
OC_UNOCCUPIED  
OC_BYPASS  
OC_STANDBY  
OC_NUL  
0
OC_NUL  
OC_NUL  
OC_NUL  
X
X
X
EffectOcc: Result of controller supervising the various Occupied controlling  
inputs and deciding which one to use. See StatusinOcy, DestSchedOcc,  
ManualOcc and StatusOvrd.  
(nvoCtlDataG1)  
1
2
3
255  
StatusOvrd  
StatusSched  
nvoData1  
(nvoCtlDataG1)  
OC_OCCUPIE  
DOC_UNOCCUPIED  
OC_BYPASS  
OC_STANDBY  
OC_NUL  
0
Override: Is the effective manual override state arbitrated from NetManOcc,  
the wall module override button and the Bypass Timer.  
N
1
O
2
3
255  
E
nvoData1  
(nvoCtlDataG1)  
SchedOcc  
OC_OCCUPIED  
OC_UNOCCUPIED  
OC_BYPASS  
OC_STANDBY  
OC_NUL  
0
DestSchedOcc: DestSchedOcc is calculated from OccTimeClock and  
nviTodEvent.CurrentState using the following logic: If  
nviTodEvent.CurrentState is OC_OCCUPIED and OccTimeClock is  
ST_NUL, then DestSchedOcc is OC_OCCUPIED. If  
nviTodEvent.CurrentState is OC_UNOCCUPIED and OccTimeClock is  
ST_NUL, then DestSchedOcc is OC_UNOCCUPIED. If  
nviTodEvent.CurrentState is OC_STANDBY and OccTimeClock is  
ST_NUL, then DestSchedOcc is OC_STANDBY. If  
1
2
3
255  
nviTodEvent.CurrentState is dont care and OccTimeClock is ST_ON, then  
DestSchedOcc is OC_OCCUPIED. If nviTodEvent.CurrentState is dont  
care and OccTimeClock is ST_OFF, then DestSchedOcc is  
OC_UNOCCUPIED. OC_OCCUPIED means the space is scheduled to be  
occupied. OC_UNOCCUPIED means the space is scheduled to be  
unoccupied. OC_STANDBY means the space is scheduled to be in a  
standby state somewhere between OC_OCCUPIED and  
OC_UNOCCUPIED.  
TimeClckOcc  
nvoData1  
(nvoCtlDataG1)  
OccTimeClock  
ST_OFF  
ST_LOW  
ST_MED  
ST_HIGH  
ST_ON  
0
ST_NUL  
X
OccTimeClock: OccTimeClock shows the state of the physical time clock  
input via nvoIO.OccTimeClock ORed with nviTimeClk. Valid enumerated  
values are: ST_OFF means OC_UNOCCUPIED when either the time clock  
input is configured and nvoIO.OccTimeClock is 0 and nviTimeClk is not  
SW_ON or nviTimeClk.state is SW_OFF and nvoIO.OccTImeClock is not 1.  
ST_ON means OC_OCCUPIED when either the time clock input is  
configured and nvoIO.OccTimeClock is 1 or nviTimeClk.state is SW_ON.  
ST_NUL means that the local time clock input is not configured by  
nciIoSelect and nviTimeClk.state is SW_NUL. There is no time clock  
configured or bound to the node.  
1
2
3
4
ST_NUL  
255  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Table 23. Status Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
Engineering Units: English  
User Address  
NvName  
Field Name  
NetManOcc  
(Metric) or States plus Range  
Default  
OC_NUL  
Comments  
StatusManOcc  
nvoData1  
(nvoCtlDataG1)  
OC_OCCUPIED  
OC_UNOCCUPIED  
OC_BYPASS  
OC_STANDBY  
OC_NUL  
0
X
X
NetManOcc: NetManOcc reports the network manual occupancy state from  
nviManOcc. The valid enumerated states are: OC_OCCUPIED indicates  
occupied OC_UNOCCUPIED indicates not occupied OC_BYPASS  
indicates that the space is bypass occupied for  
nciAux2SetPt.uiBypassTime seconds after nviManOcc is first set to  
OC_BYPASS OC_STANDBY indicates that the space is standby. OC_NUL  
means that no manual override is active.  
1
2
3
255  
StatusOcySen  
StatusEconEn  
nvoData1  
(nvoCtlDataG1)  
SenOcc  
OC_OCCUPIED  
OC_UNOCCUPIED  
OC_BYPASS  
OC_STANDBY  
OC_NUL  
0
OC_NUL  
ST_NUL  
SenOcc: SenOcc indicates the current state of the sensed occupancy and  
is calculated from nviSensorOcc and the local occupancy sensor via  
nvoIO.OccupancySensor. The local sensor and nviSensorOcc are ORed  
together. If either the local sensor or nviSensorOcc shows occupancy, then  
SenOcc shows occupancy. The valid enumerated values are:  
OC_OCCUPIED means that occupancy is sensed by one or more  
sensor.OC_UNOCCUPIED means that no occupancy is sensed by any  
sensors.OC_NUL means no local sensor is configured and nviSensorOcc  
has failed to be received periodically (bound or not bound).  
1
2
3
255  
nvoData1  
(nvoCtlDataG1)  
EconEnable  
ST_OFF  
ST_LOW  
ST_MED  
ST_HIGH  
ST_ON  
0
X
EconEnable: EconEnable indicates the current suitability of outdoor air for  
use in cooling used by the control process EconEnable is periodically  
calculated either from the sensor(s) specified by nciConfig.EconEnable or  
from nviEcon. When nviEcon.state is not SW_NUL, then the local inputs  
are ignored and nviEcon.state is used instead. See nciConfig.EconEnable.  
The valid enumerated values are: ST_OFF means the outdoor air is not  
suitable to augment cooling. ST_ON means the outdoor air is suitable to  
augment cooling.ST_NUL means no local sensor is selected by  
nciConfig.EconEnable, or the selected local sensor has failed or has not  
been configured by nciIoSelect, and that nviEcon.state is SW_NUL. The  
outdoor air is considered unsuitable for cooling.  
1
E
2
3
4
ST_NUL  
255  
W
,
SaFanStatus  
OaEnthCalc  
nvoData1  
ProofAirFlow  
ST_OFF  
ST_LOW  
ST_MED  
ST_HIGH  
ST_ON  
0
ST_NUL  
X
X
ProofAirFlow: ProofAirFlow indicates the current state of the ProofAirFlow  
switch used by the control process and is read by the local sensor via  
nvoIO.ProofAirFlow. The valid enumerated values are: ST_OFF means air  
flow is not detected. ST_ON means air flow is detected. ST_NUL means no  
air flow switch is configured.  
C
(nvoCtlDataG1)  
1
2
3
NST  
4
ST_NUL  
255  
nvoData1  
(nvoCtlDataG1)  
siCalcODEnthalpyS7 btu/lb  
0 to 100  
SI_INVALID  
siCalcODEnthalpyS7: siCalcODEnthalpyS7 is the calculated outdoor air  
enthalpy in btu / lb calculated from the siOutdoorTempS7 and  
ubOutdoorHumidityS1. siCalcODEnthalpyS7 is used to determine the  
suitability of outside air for cooling when nciConfig.EconEnable is  
SINGLE_ENTH and both outdoor temperature and humidity sensors are  
present. siCalcODEnthalpyS7 is compared to the enthalpy setpoint stored  
in nciAux1SetPts.ubOdEnthalpyEnableS2.  
NTV  
AHUCO  
RaEnthCalc  
nvoData1  
(nvoCtlDataG1)  
siCalcRAEnthalpyS7 btu/lb  
0 to 100  
SI_INVALID  
X
siCalcRAEnthalpyS7: siCalcRAEnthalpyS7 is the calculated return air  
enthalpy in btu / lb calculated from the siReturnTempS7 and  
ubReturnHumidityS1. siCalcRAEnthalpyS7 is used to determine the  
suitability of outside air for cooling when nciConfig.EconEnable is  
DIFF_ENTH and both outdoor and return (or space) temperature sensors  
and humidity sensors are present. Sensors may be physically connected to  
the node or available over the network.  
N
R
E
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
E
Table 23. Status Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
W
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
Field Name  
Default  
Comments  
HeatStgsOn  
nvoData1  
HeatStagesOn  
0 to 4  
0
0
X
X
HeatStagesOn: HeatStagesOn indicates how many heating stages are on.  
If the node is controlling a heat pump, HeatStagesOn indicates how many  
auxiliary heating stages are turned on.  
O
(nvoCtlDataG1)  
NST  
CoolStgsOn  
nvoData1  
(nvoCtlDataG1)  
CoolStagesOn  
0 to 4  
CoolStagesOn: CoolStagesOn indicates how many compressor stages are  
on. If the node is controlling a heat pump, compressor stages are turned on  
for both heating or cooling.  
NTV  
Free1Stat  
Free2Stat  
OccStatOut  
nvoData1  
Free1Out  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
FALSE  
X
X
X
Free1Out: Free1Out indicates the state of FREE1_OUT digital output. 1  
means on, and 0 means off.  
(nvoCtlDataG1)  
nvoData1  
(nvoCtlDataG1)  
Free2Out  
FALSE  
TRUE  
0
1
Free2Out: Free2Out indicates the state of FREE2_OUT digital output. 1  
means on, and 0 means off.  
MEAHUCO  
nvoData1  
(nvoCtlDataG1)  
OccStatusOut  
FALSE  
TRUE  
0
1
OccStatusOut: OccStatusOut indicates the state of the  
OCCUPANCY_STATUS_OUT digital output. 1 means on (not  
OC_UNOCCUPIED), and 0 means off (OC_UNOCCUPIED).  
SaFan  
nvoData1  
FanOn  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
X
X
FanOn: FanOn indicates the state of the FAN_OUT digital output. 1 means  
on, and 0 means off.  
(nvoCtlDataG1)  
N
StatusEconOut  
nvoData1  
(nvoCtlDataG1)  
AuxEconOut  
FALSE  
TRUE  
0
1
AuxEconOut: AuxEconOut indicates the state of the AUX_ECON_OUT  
digital output. 1 means that the packaged economizer is enabled, and 0  
means the economizer is disabled. A packaged economizer is always  
treated as the first stage of cooling when an economizer is configured by  
nciIoSelect.  
R
E
nvoData1  
EconFloatSynch  
DlcShed  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
EconFloatSynch: EconFloatSynch indicates that the economizer damper  
motor is being synchronized with the reported economizer position by  
driving the damper for a period longer than it takes to fully close the  
damper. The reported economizer position is synchronized whenever an  
endpoint is reached (full open or full close).and when the elapsed time  
since the last synchronization is 24 hours.  
(nvoCtlDataG1)  
DlcShed  
nvoData1  
(nvoCtlDataG1)  
FALSE  
TRUE  
0
1
DlcShed: DlcShed indicates the state of nviDlcShed. When DlcShed is 1,  
demand limit control set by an energy management node is active. If the  
effective occupancy is OC_OCCUPIED or OC_STANDBY when demand  
limit control is active, then the setpoint is shifted by  
nciAux1SetPt.siDlcBumpTempS7 in the energy saving direction. When  
DlcShed is 0, demand limit control is inactive. If nviDlcShed fails to be  
received periodically or nviDlcShed becomes 0, then the setpoint is ramped  
back to the original setpoint over a 30 minute interval.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
               
Table 23. Status Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
Engineering Units: English  
User Address  
NvName  
Field Name  
IaqOverRide  
(Metric) or States plus Range  
Default  
Comments  
StatusIaqOvr  
nvoData1  
(nvoCtlDataG1)  
FALSE  
TRUE  
0
1
FALSE  
X
IaqOverRide: When an economizer is configured, IaqOverRide indicates  
the current state of the indoor air quality, an is used by the control process  
to open the economizer damper to let in more outside air. 1 means poor  
indoor air quality, and 0 means indoor air quality is OK. When IaqOverRide  
is 1, the IAQ_OVERRIDE alarm is initiated. IaqOverRide indicates poor air  
quality if the analog sensor OR a digital sensor (local or via network) shows  
poor air quality. Specifically, if nvoData2.siSpaceCo2S0 is not SI_INVALID,  
and exceeds nciAux1SetPt.siCO2IaqLimitS0, then poor air quality is  
detected. Also if nviIaqOvr.state is SW_ON, then poor air quality is  
detected. Or if a local digital input is configured as IAQ_OVERRIDE_IN and  
nvoIO.IaqOverRide is 1 then poor air quality is also detected. When poor air  
quality is detected, the economizer minimum position is set to  
nciAux1SetPts.ubEconIaqPosS0, instead of  
nciAux1SetPts.ubEconMinPosS0.When an economizer is not configured,  
IaqOverRide is 0.  
StatusSmoke  
StatusWndw  
StatusFilter  
nvoData1  
SmokeMonitor  
WindowOpen  
DirtyFilter  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
FALSE  
X
X
X
SmokeMonitor: SmokeMonitor indicates the current state of the  
SmokeMonitor input used by the control process and is read from another  
node via nviEmerg or the local sensor via nvoIO.SmokeMonitor. If either  
nviEmerg is not EMERG_NORMAL or nvoIO.SmokeMonitor is 1, then  
SmokeMonitor is 1 meaning that smoke is detected. Otherwise  
SmokeMonitor is 0, meaning smoke is not detected. When smoke monitor  
is 1, the algorithm controls as per the settings found in  
(nvoCtlDataG1)  
X
nciConfig.SmokeControl.  
W
nvoData1  
(nvoCtlDataG1)  
FALSE  
TRUE  
0
1
WindowOpen: WindowOpen indicates the current state of the window  
sensors and is calculated from nviWindow state and the local occupancy  
sensor via nvoIO.WindowOpen. The local sensor and nviWindow are ORed  
together. If either the local sensor or nviWindow shows that the window is  
open (nvoIO.WindowOpen = 1 or nviWindow.state = SW_ON), then  
WindowOpen shows that the window is open. 1 means that the window is  
open and 0 means that the window is closed. When the window is open, the  
controller mode is switched to FREEZE_PROTECT.  
,
,
NST  
nvoData1  
(nvoCtlDataG1)  
FALSE  
TRUE  
0
1
DirtyFilter: DirtyFilter indicates the state of the air filter via the  
nvoIO.DirtyFilter digital input or the nvoData1.siFilterPressureS10 analog  
input. If nvoData1.siFilterPressureS10 exceeds  
NTV  
nciAux2SetPt.ubFilterPressStPtS5, a dirty filter is indicated. DirtyFilter is set  
to 1 when a dirty filter has been detected by either method for one minute.  
DirtyFilter is set to 0 when a dirty filter has not been detected by either  
method for one minute. When DirtyFilter is 1, a DIRTY_FILTER alarm is  
generated.  
ShutDown  
nvoData1  
ShutDown  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
FALSE  
X
X
X
ShutDown: ShutDown indicates the state of the ShutDown input via  
nvoIO.ShutDown. 1 means a ShutDown is being commanded and 0 means  
normal operation.  
AHUCO  
(nvoCtlDataG1)  
StatFreezeStat  
MonitorSw  
nvoData1  
(nvoCtlDataG1)  
CoilFreezeStat  
MonSwitch  
FALSE  
TRUE  
0
1
M
X
StatFreezeStat: StatFreezeStat gives the state of the cooling coil controlled  
by the CVAHU. False (0) it is not freezing or True (1) it is freezing.  
NOTE: Only use this User Address when using E-Vision.  
T
R
nvoData1  
(nvoCtlDataG1)  
FALSE  
TRUE  
0
1
MonSwitch: MonSwitch is the state of the digital input wired to a general  
purpose monitor switch via nvoIO.MonSwitch. 1 means that the switch is  
closed and 0 means that the switch is open.  
R
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
E
Table 23. Status Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
W
Engineering Units: English  
User Address  
NvName  
Field Name  
WSHPEnable  
(Metric) or States plus Range  
Default  
Comments  
WSHPEnable  
nvoData1  
(nvoCtlDataG1)  
FALSE  
TRUE  
0
1
FALSE  
X
WSHPEnable: WSHPEnable reports the state of the current state of  
nviWSHPEnable. The states for nviWSHPEnable are as follows: If  
nviWSHPEnable.state is SW_OFF and the nviWSHPEnable.value is 0,  
then WSHPEnable is 0 (Disable Water Source Heat Pump). If  
nviWSHPEnable.state is SW_ON and the nviWSHPEnable.value is 0, then  
WSHPEnable is 0 (Disable Water Source Heat Pump). If  
,
NST  
nviWSHPEnable.state is SW_ON and the nviWSHPEnable.value is not 0,  
then WSHPEnable is 1 (Enable Water Source Heat Pump). If  
nviWSHPEnable.state is SW_NUL and the nviWSHPEnable.value is any  
value, then WSHPEnable is 1 (Enable Water Source Heat Pump when  
nviWSHPEnable is not bound to another node).  
NTV  
MEAHUCO  
nvoData2  
(nvoCtlDataG2)  
FieldNo  
UPDATE_ALL_FIELDS  
UPDATE_ALL_FIELDS  
nvoData2. FieldNo: nvoData2 and nvoCtlDataG2 are output network  
variables indicating the node status. The information contained in these  
network variables are typically used to display the node status on an  
operator terminal, used in a trend log, or used in a control process. The  
information contained in nvoCtlDataG2 and nvoData2 are identical.  
nvoData2 is a polled network variable and must be polled by the receiver.  
nvoCtlDataG2 uses the SGPUC mechanism. FieldNo indicates which other  
data field in the SGPUC network variable has changed since the last time it  
was sent on the network according to the SGPUC mechanism.  
BYPASS_TIMER_FIELD  
TEMP_CONTROL_PT_FIELD  
SPACE_TEMP_FIELD  
DISCHARGE_TEMP_FIELD  
DISCHARGE_SET_PT_FIELD  
RETURN_TEMP_FIELD  
RETURN_HUMIDITY_FIELD  
RETURN_ENTHALPY_FIELD  
OUTDOOR_TEMP_FIELD  
OUTDOOR_HUMIDITY_FIELD  
OUTDOOR_ENTHALPY_FIELD  
FILTER_PRESSURE_FIELD  
SPACE_CO2_FIELD  
N
R
E
MONITOR_VOLTS_FIELD  
COOL_POS_FIELD  
HEAT_POS_FIELD  
ECON_POS_FIELD  
UPDATE_NO_FIELDS  
BypTimer  
nvoData2  
uiBypassTimer  
minutes  
0
X
X
uiBypassTimer: The time left in the bypass timer is uiBypassTimer minutes.  
If uiBypassTimer is zero, then the bypass timer is not running. If  
uiBypassTimer is not zero, it is decremented every minute.  
(nvoCtlDataG2)  
0 to 2880  
RmTempActSpt  
nvoData2  
(nvoCtlDataG2)  
siTempControlPtS7  
Degrees F  
50 to 85  
Degrees C  
(10 to 29)  
SI_INVALID  
siTempControlPtS7: The current temperature control point (such that, the  
current actual space temperature setpoint which the controller is presently  
trying to maintain in the conditioned space) is calculated from the various  
Setpoints, operating modes, network variable inputs, and optimum start-up  
parameters. The final result is stored in siTempControlPtS7.  
RmTemp  
nvoData2  
(nvoCtlDataG2)  
siSpaceTempS7  
Degrees F  
40 to 100  
Degrees C  
(4 to 38)  
SI_INVALID  
siSpaceTempS7: siSpaceTempS7 is the space temperature used by the  
control process and is read from another node via nviSpaceTemp or a local  
sensor via nvoIO.siSpaceTempS7 or nvoIO.siReturnTempS7. If the network  
input is not SI_INVALID, then the network input has priority. The local  
sensor is selected by nciConfig.ControlUsesRtnAirTemp. When  
nciConfig.ControlUsesRtnAirTemp is 0, then the space temperature sensor  
is selected. When nciConfig.ControlUsesRtnAirTemp is 1, then the return  
temperature sensor is selected. If the network input and the selected local  
sensor has failed or are not configured, siSpaceTempS7 is SI_INVALID.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Table 23. Status Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
Engineering Units: English  
User Address  
NvName  
Field Name  
(Metric) or States plus Range  
Default  
SI_INVALID  
Comments  
DaTemp  
nvoData2  
(nvoCtlDataG2)  
siDischargeTempS7  
Degrees F  
30 to 122  
Degrees C  
(-1 to 50)  
X
X
X
X
X
X
siDischargeTempS7: siDischargeTempS7 is the discharge air temperature  
used by the control process and is read from the local sensor via  
nvoIO.siDischargeTempS7. If the sensor has failed or is not configured,  
siDischargeTempS7 is SI_INVALID.  
DaSetpt  
RaTemp  
RaHum  
RaEnth  
OaTemp  
nvoData2  
(nvoCtlDataG2)  
siDischargeSetPtS7  
siReturnTempS7  
Degrees F  
30 to 122  
Degrees C  
(-1 to 50)  
SI_INVALID  
SI_INVALID  
UB_INVALID  
SI_INVALID  
SI_INVALID  
siDischargeSetPtS7: siDischargeSetPtS7 is the calculated desired  
discharge air temperature when cascade control is being used.  
nvoData2  
(nvoCtlDataG2)  
Degrees F  
30 to 122  
Degrees C  
(-1 to 50)  
siReturnTempS7: siReturnTempS7 is the return air temperature used by the  
control process read from the local sensor via nvoIO.siReturnTempS7. If  
the sensor has failed or is not configured, siReturnTempS7 is SI_INVALID.  
nvoData2  
(nvoCtlDataG2)  
ubReturnHumidityS1 Percentage  
10 to 90  
ubReturnHumidityS1: ubReturnHumidityS1 is the return air humidity used  
by the control process and is read from the local sensor via  
nvoIO.ReturnHumidity. If the sensor has failed or is not configured  
ubReturnHumidityS1 is UB_INVALID.  
nvoData2  
(nvoCtlDataG2)  
siReturnEnthalpyS7  
siOutdoorTempS7  
mA  
4 to 20  
siReturnEnthalpyS7: siReturnEnthalpyS7 is the return air enthalpy used by  
the control process and is read from the local sensor via  
nvoIO.siReturnEnthalpyS7. If the sensor has failed or is not configured,  
siReturnEnthalpyS7 is SI_INVALID.  
E
nvoData2  
(nvoCtlDataG2)  
Degrees F  
-40 to 122  
Degrees C  
(-40 to 43)  
siOutdoorTempS7: siOutdoorTempS7 is the outdoor air temperature used  
by the control process and is read from another node via nviOdTemp or the  
local sensor via nvoIO.siOutdoorTempS7. If the network input is not  
SI_INVALID, then the network input has priority. If both the network input  
and the local sensor have failed or are not configured, siOutdoorTempS7 is  
SI_INVALID.  
W
,
,
OaHum  
OaEnth  
nvoData2  
ubOutdoorHumidityS1 Percentage  
10 to 90  
UB_INVALID  
SI_INVALID  
X
X
ubOutdoorHumidityS1: ubOutdoorHumidityS1 is the outdoor air humidity  
used by the control process and is read from another node via nviOdHum  
or the local sensor via nvoIO.OutdoorHumidity. If the network is not  
SI_INVALID, then the network input has priority. If both the network input  
and the local sensor have failed or are not configured,  
(nvoCtlDataG2)  
NST  
ubOutdoorHumidityS1 is UB_INVALID.  
NTV  
nvoData2  
(nvoCtlDataG2)  
siOutdoorEnthalpyS7 mA  
4 to 20  
siOutdoorEnthalpyS7: siOutdoorEnthalpyS7 is the outdoor air enthalpy  
used by the control process and is read from another node via  
nviOdEnthS7 or the local sensor via nvoIO.siOutdoorEnthalpyS7. If the  
network input is not SI_INVALID, then the network input has priority. If both  
the network input and the local sensor have failed or are not configured,  
siOutdoorEnthalpyS7 is SI_INVALID.  
AHUCO  
FilterPress  
CO2Sens  
nvoData2  
siFilterPressureS10  
siSpaceCo2S0  
inw (kPa)  
SI_INVALID  
SI_INVALID  
X
X
siFilterPressureS10: siFilterPressureS10 is air pressure across the air filter  
used by the control process and is read from the local sensor via  
nvoIO.siFilterPressureS10. If the local sensor has failed or is not  
configured, siFilterPressureS10 is SI_INVALID.  
(nvoCtlDataG2)  
0 to 5 (0 to 1.25)  
N
nvoCtlDataG2  
PPM  
150 to 2000  
siSpaceCo2S0: siSpaceCo2S0 is the indoor air CO content used by the  
2
R
control process and read the local sensor via nvoIO.siSpaceCo2S0. If the  
local sensor has failed or is not configured, siSpaceCo2S0 is SI_INVALID.  
R
Download from Www.Somanuals.com. All Manuals Search And Download.  
                   
E
Table 23. Status Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
W
Engineering Units: English  
User Address  
NvName  
Field Name  
siMonitor1S10  
(Metric) or States plus Range  
Default  
SI_INVALID  
Comments  
MonitorSens  
nvoCtlDataG2  
volts  
1 to 10  
X
siMonitor1S10: siMonitor1S10 is the voltage applied at the monitor input  
terminals. If the sensor is not configured or has failed, the value is  
SI_INVALID.  
O
NST  
CoolPos  
HeatPos  
EconPos  
nvoCtlDataG2  
nvoCtlDataG2  
nvoCtlDataG2  
sbCoolPosS0  
sbHeatPosS0  
sbEconPosS0  
Percentage  
0 to 100  
0
0
0
X
X
X
sbCoolPosS0: If the node is configured for modulating cool, sbCoolPosS0  
shows the current position of the cooling modulating output.  
Percentage  
0 to 100  
sbHeatPosS0: If the node is configured for modulating heat, sbHeatPosS0  
shows the current position of the heating modulating output.  
NTV  
Percentage  
0 to 100  
sbEconPosS0: If the node is configured for modulating economizer,  
sbEconPosS0 shows the current position of the economizer modulating  
output.  
MEAHUCO  
StatusError  
nvoError  
error_bit[0]  
FALSE  
TRUE  
0
1
FALSE  
X
For SpaceTempError, a value of 1 (TRUE) indicates that data was not  
available from the sensor and will result in a SENSOR_FAILURE alarm. A  
value of 0 (FALSE) indicates a normal condition. The heating and cooling  
control loops will be turned off it there is a space temp sensor failure. The  
fan will remain under normal control.  
Byte Offset = 0  
Bit Offset = 0  
(SpaceTempError)  
N
nvoError  
nvoError  
nvoError  
nvoError  
nvoError  
nvoError  
nvoError  
error_bit[0]  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
For SetPtError, see preceding. Upon a failure of the local setpoint, the  
control loop will use the default occupied setpoints to control space  
temperature.  
O
Byte Offset = 0  
Bit Offset = 1  
(SetPtError)  
E
error_bit[0]  
FALSE  
TRUE  
0
1
For OdTempError, see preceding. All control functions associated with the  
failed sensor are disabled as if the sensor was not configured.  
Byte Offset = 0  
Bit Offset = 2  
(OdTempError)  
error_bit[0]  
FALSE  
TRUE  
0
1
For OdHumError, see preceding. A value of 0 (FALSE) indicates a normal  
condition. All control functions associated with the failed sensor are  
disabled as if the sensor was not configured.  
Byte Offset = 0  
Bit Offset = 3  
(OdHumError)  
error_bit[0]  
FALSE  
TRUE  
0
1
OdEnthalpyError: All control functions associated with the failed sensor are  
disabled as if the sensor was not configured.  
Byte Offset = 0  
Bit Offset = 4  
(OdEnthalpyError)  
error_bit[0]  
FALSE  
TRUE  
0
1
DischgTempError: All control functions associated with the failed sensor are  
disabled as if the sensor was not configured.  
Byte Offset = 0  
Bit Offset = 5  
(DischgTempError)  
error_bit[0]  
FALSE  
TRUE  
0
1
RtnTempError: All control functions associated with the failed sensor are  
disabled as if the sensor was not configured.  
Byte Offset = 0  
Bit Offset = 6  
RtnTempError)  
error_bit[0]  
FALSE  
TRUE  
0
1
RtnHumError: All control functions associated with the failed sensor are  
disabled as if the sensor was not configured.  
Byte Offset = 0  
Bit Offset = 7  
(RtnHumError)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Table 23. Status Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
Engineering Units: English  
User Address  
NvName  
nvoError  
Field Name  
error_bit[1]  
Byte Offset = 1  
Bit Offset = 0  
(RtnEnthalpyError)  
(Metric) or States plus Range  
Default  
Comments  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
RtnEnthalpyError: All control functions associated with the failed sensor are  
disabled as if the sensor was not configured.  
nvoError  
nvoError  
nvoError  
nvoError  
nvoError  
nvoError  
nvoError  
nvoError  
nvoError  
nvoError  
error_bit[1]  
FALSE  
TRUE  
0
1
MonitorSensorError: All control functions associated with the failed sensor  
are disabled as if the sensor was not configured.  
Byte Offset = 1  
Bit Offset = 1  
(MonitorSensorError)  
error_bit[1]  
FALSE  
TRUE  
0
1
SpaceCO2Error: All control functions associated with the failed sensor are  
disabled as if the sensor was not configured.  
Byte Offset = 1  
Bit Offset = 2  
(SpaceCO2Error)  
error_bit[1]  
FALSE  
TRUE  
0
1
FilterStaticPresError: All control functions associated with the failed sensor  
are disabled as if the sensor was not configured.  
Byte Offset = 1  
Bit Offset = 3  
(FilterStaticPresError)  
error_bit[1]  
FALSE  
TRUE  
0
1
ADCalError: All control functions associated with the failed sensor are  
disabled as if the sensor was not configured.  
E
Byte Offset = 1  
Bit Offset = 4  
(ADCalError)  
error_bit[1]  
FALSE  
TRUE  
0
1
ApplModeError: All control functions associated with the failed NV are  
disabled as if the NV was not configured.  
Byte Offset = 1  
Bit Offset = 7  
W
(nvApplModeError)  
error_bit[2]  
FALSE  
TRUE  
0
1
SetPtOffsetError: All control functions associated with the failed NV are  
disabled as if the NV was not configured.  
,
Byte Offset = 2  
Bit Offset = 0  
O
(nvSetPtOffsetError)  
error_bit[2]  
FALSE  
TRUE  
0
1
SpaceTempError: All control functions associated with the failed NV are  
disabled as if the NV was not configured.  
NST  
Byte Offset = 2  
Bit Offset = 1  
(nvSpaceTempError)  
NTV  
error_bit[2]  
FALSE  
TRUE  
0
1
OdTempError: All control functions associated with the failed NV are  
disabled as if the NV was not configured.  
Byte Offset = 2  
Bit Offset = 2  
(nvOdTempError)  
error_bit[2]  
FALSE  
TRUE  
0
1
OdHumError: All control functions associated with the failed NV are  
disabled as if the NV was not configured.  
AHUCO  
Byte Offset = 2  
Bit Offset = 3  
(nvOdHumError)  
error_bit[2]  
FALSE  
TRUE  
0
1
SensorOccError: All control functions associated with the failed NV are  
disabled as if the NV was not configured.  
N
Byte Offset = 2  
Bit Offset = 4  
R
(nvSensorOccError)  
E
Download from Www.Somanuals.com. All Manuals Search And Download.  
E
Table 23. Status Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
W
Engineering Units: English  
User Address  
NvName  
nvoError  
Field Name  
error_bit[2]  
Byte Offset = 2  
Bit Offset = 5  
(nvWindowError)  
(Metric) or States plus Range  
Default  
Comments  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
WindowError: All control functions associated with the failed NV are  
disabled as if the NV was not configured.  
,
NST  
nvoError  
nvoError  
nvoError  
nvoError  
nvoError  
nvoError  
nvoError  
error_bit[2]  
FALSE  
TRUE  
0
1
DlcShedError: All control functions associated with the failed NV are  
disabled as if the NV was not configured.  
Byte Offset = 2  
Bit Offset = 6  
(nvDlcShedError)  
NTV  
error_bit[2]  
FALSE  
TRUE  
0
1
TodEventError: All control functions associated with the failed NV are  
disabled as if the NV was not configured.  
Byte Offset = 2  
Bit Offset = 7  
(nvTodEventError)  
MEAHUCO  
error_bit[3]  
FALSE  
TRUE  
0
1
ByPassError: All control functions associated with the failed NV are  
disabled as if the NV was not configured.  
Byte Offset = 3  
Bit Offset = 0  
(nvByPassError)  
T
error_bit[3]  
FALSE  
TRUE  
0
1
OdEnthalpyError: All control functions associated with the failed NV are  
disabled as if the NV was not configured.  
R
Byte Offset = 3  
Bit Offset = 1  
(nvOdEnthalpyError)  
R
error_bit[3]  
FALSE  
TRUE  
0
1
EconError: All control functions associated with the failed NV are disabled  
as if the NV was not configured.  
Byte Offset = 3  
Bit Offset = 2  
(nvEconError)  
error_bit[3]  
FALSE  
TRUE  
0
1
IaqOverrideError: All control functions associated with the failed NV are  
disabled as if the NV was not configured.  
Byte Offset = 3  
Bit Offset = 3  
(nvIaqOverrideError)  
error_bit[3]  
FALSE  
TRUE  
0
1
Free1Error: All control functions associated with the failed NV are disabled  
as if the NV was not configured.  
Byte Offset = 3  
Bit Offset = 4  
(nvFree1Error)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 23. Status Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
Engineering Units: English  
User Address  
NvName  
nvoError  
Field Name  
error_bit[3]  
Byte Offset = 3  
Bit Offset = 5  
(nvFree2Error)  
(Metric) or States plus Range  
Default  
Comments  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
FALSE  
Free2Error: All control functions associated with the failed NV are disabled  
as if the NV was not configured.  
nvoError  
error_bit[3]  
FALSE  
TRUE  
0
1
TimeClockError: All control functions associated with the failed NV are  
disabled as if the NV was not configured.  
Byte Offset = 3  
Bit Offset = 6  
(nvTimeClockError)  
nvoError  
error_bit[3]  
FALSE  
TRUE  
0
1
WSHPEnError: All control functions associated with the failed NV are  
disabled as if the NV was not configured.  
Byte Offset = 3  
Bit Offset = 7  
(nvWSHPEnError)  
NetConfig  
nciNetConfig  
CFG_LOCAL  
CFG_EXTERNAL  
CFG_NUL  
0
CFG_LOCAL  
All nodes that support self-installation provide a configuration variable to  
allow a network management tool to also install the node. nciNetConfig is  
only used by a network management tool and may have the following  
values: CFG_LOCAL - Node will use self installation functions to set its own  
network image. CFG_EXTERNAL - The nodes network image has been set  
by an external source.  
1
255  
L
Table 24. Calibration Points.  
W
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
,
Engineering Units: English  
(Metric) or States plus Range  
,
User Address  
NvName  
Field Name  
Default  
Comments  
nvoRaw  
K1Raw  
K2Raw  
Counts  
0 to 65535  
0
raw_data contains the analog to digital converter counts measured from the  
analog input channel.  
NST  
Ai1Resistive  
Ai2Resistive  
Ai3Voltage  
Ai4Voltage  
RawSpaceTemp  
RawSetPoint  
NTV  
AHUCO  
N
R
R
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
E
Table 25. Configuration Parameters.  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
NOTE: Physical I/O points that are configurable are in Table 20.  
Comments  
W
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
Field Name  
Default  
ASCII Blanks  
,
nciDeviceName  
DeviceName is an 18 character field used to identify the node uniquely as  
one object at the site or project. The contents of the DeviceName is  
maintained by a management node. If DeviceName is all ASCII blanks, it is  
considered unconfigured.  
NST  
nciApplVer  
nciApplVer  
nciApplVer  
application_type  
version_no  
time  
0 to 255  
0 to 255  
Seconds  
0
0
0
ApplicationType identifies the current application number of the Excel 10.  
VersionNumber identifies the version number of the Excel 10 application.  
NTV  
The time stamp of the last change to the Excel 10 application  
configuration. Time meets the ANSI C time stamp requirement specifying  
the number of seconds elapsed since midnight (0:00:00), January 1, 1970.  
It is represented in the Intel Format.  
MEAHUCO  
FanMode  
nciConfig  
nciConfig  
FanMode  
AUTO_FAN  
0
1
AUTO_FAN  
ECON_NUL  
P
P
X
X
X
X
FanMode specifies the operation of the fan. If the FanMode is 0  
(AUTO_FAN), then the fan cycles on and off with demand for cooling and  
may cycle with heating if FanOnHeat is TRUE. If the FanMode is 1  
(CONTINUOUS_FAN), then the fan runs continuously when the effective  
occupancy is OC_OCCUPIED or OC_BYPASS. The fan cycles on and off  
with demand for cooling and may cycle with heating if FanOnHeat is TRUE  
during the OC_UNOCCUPIED or OC_STANDBY modes.  
CONTINUOUS_FAN  
N
R
EconMode  
EconEnable  
DIGITAL_IN  
OD_TEMP  
OD_ENTH_A_TYPE  
OD_ENTH_B_TYPE  
OD_ENTH_C_TYPE  
OD_ENTH_D_TYPE  
DIFF_TEMP  
SINGLE_ENTH  
DIFF_ENTH  
ECON_NUL  
0
EconEnable specifies the method used to determine when outside air is  
suitable for use to augment cooling. The valid values are according to the  
enumerated list that is shown in the Engineering Units/States column.  
E
1
2
3
4
5
6
7
8
255  
SmkCtlMode  
HeatCycHr  
nciConfig  
nciConfig  
SmokeControl  
ubHeatCph  
FAN_OFF_DAMPER_CLOSED  
FAN_ON_DAMPER_OPEN  
FAN_ON_DAMPER_CLOSED  
0
1
2
FAN_OFF_DAMPER_  
CLOSED  
P
P
X
X
X
X
SmokeControl specifies the operation of the economizer damper and the  
fan when the mode is SMOKE_EMERGENCY.  
2 to 12  
6
HeatCph specifies the mid-load number of on/off cycles per hour when the  
mode is HEAT. In addition the cycle rate specifies the minimum on and off  
time. Refer to Table 17 Interstage Minimum Times of the System  
Engineering Guide for the actual values.  
CoolCycHr  
nciConfig  
ubCoolCph  
2 to 12  
3
P
X
X
CoolCph specifies the mid-load number of on/off cycles per hour when the  
mode is COOL. In addition the cycle rate specifies the minimum on and off  
time. Refer to Table 17 Interstage Minimum Times of the System  
Engineering Guide for the actual values.  
FanRunOnCool nciConfig  
FanRunOnHeat nciConfig  
ubFanRunonCoolS0  
ubFanRunonHeatS0  
Seconds  
0 to 120  
0
0
P
P
X
X
X
X
FanRunonCool specifies how long the fan runs after all the cooling stages  
have turned off. The fan is turned off FanRunonCool seconds after all the  
cooling demand has turned off.  
Seconds  
0 to 120  
FanRunonHeat specifies how long the fan runs after all the heating stages  
have turned off. The fan is turned off FanRunonHeat seconds after all the  
heating demand has turned off.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
               
Table 25. Configuration Parameters. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
NOTE: Physical I/O points that are configurable are in Table 20.  
Comments  
Engineering Units: English  
User Address  
NvName  
nciConfig  
Field Name  
(Metric) or States plus Range  
Default  
EconMtrSpd  
ubEconMtrTimeS0  
Seconds  
20 to 240  
90  
90  
90  
10  
P
P
P
P
X
X
X
X
X
X
X
X
EconMtrTime specifies how long it takes the economizer damper motor to  
travel from fully closed to fully open. This time is used to calculate the  
reported position of the damper and to determine the length of over drive  
time required to assure the damper is fully closed or open.  
CoolMtrSpd  
HeatMtrSpd  
FanFailTime  
nciConfig  
nciConfig  
nciConfig  
ubCoolMtrTimeS0  
ubHeatMtrTimeS0  
ubFanFailTimeS0  
Seconds  
20 to 240  
CoolMtrTime specifies how long it takes the cooling damper or valve motor  
to travel from fully closed to fully open. This time is used to calculate the  
reported position of the cooling damper or valve and to determine the  
length of over drive time required to assure that it is fully closed or open.  
Seconds  
20 to 240  
HeatMtrTime specifies how long it takes the heating damper or valve motor  
to travel from fully closed to fully open. This time is used to calculate the  
reported position of the heating damper or valve and to determine the  
length of over drive time required to assure that it is fully closed or open.  
Seconds  
1 to 255  
Each time FAN_OUT is energized, then the node waits for FanFailTime  
seconds to sample the ProofAirFlow input. If ProofAirFlow shows that the  
fan is not running for FanFailTime consecutive seconds, then the control is  
shut down for the minimum off time. Then the control (including the fan) is  
restarted and ProofAirFlow is again tested. If ProofAirFlow shows air flow,  
then the control continues to operate, but if ProofAirFlow fails to show air  
flow, then the control is again shut down for the minimum off time. After  
three unsuccessful restarts, a LOSS_OF_AIR_FLOW alarm is issued and  
the control stays in the DISABLED mode with the FAN_OUT off.  
L
RmTempCal  
nciConfig  
nciConfig  
nciConfig  
nciConfig  
siSpaceTempZeroCalS7 Degrees F  
-5 to 5 (-3 to 3)  
0
0
0
0
X
X
SpaceTempZeroCal provides offset calibration for the space analog sensor  
input and is added to the sensed value. The range of SpaceTempZeroCal  
is between -5 and 5 degrees F.  
7
TempOffstCal1  
TempOffstCal2  
VoltOffstCal1  
siResistiveOffsetCalS7[0] Degrees F  
-15 to 15 (-9 to 9)  
ResistiveOffsetCal[0] provides offset calibration for the resistive analog  
sensor input and is added to the sensed value. The range of  
ResistiveOffsetCal[0] is between -15 and 15 degrees F.  
,
O
siResistiveOffsetCalS7[1] Degrees F  
-15 to 15 (-9 to 9)  
ResistiveOffsetCal[1] provides offset calibration for the resistive analog  
sensor input and is added to the sensed value. The range of  
ResistiveOffsetCal[1] is between -15 and 15 degrees F.  
NST  
siVoltageOffsetCalS12[0] volts  
-1 to 1  
VoltageOffsetCal[0] provides offset calibration for the voltage/current  
analog sensor input and is added to the sensed value. The current analog  
sensor is converted to a voltage by a 249 ohm resister wired across the  
input terminals. The range of VoltageOffsetCal[0] is between -1 and 1 volt.  
Voltage offsets are new in engineering units (not volts).  
NTV  
VoltOffstCal2  
nciConfig  
nciConfig  
siVoltageOffsetCalS12[1] volts  
-1 to 1  
0
VoltageOffsetCal[1] provides offset calibration for the voltage/current  
analog sensor input and is added to the sensed value. The current analog  
sensor is converted to a voltage by a 249 ohm resister wired across the  
input terminals. The range of VoltageOffsetCal[1] is between -1 and 1 volt.  
Voltage offsets are new in engineering units (not volts).  
AHUCO  
FanOnHtMode  
FanOnHeat  
FALSE  
TRUE  
0
1
TRUE  
P
X
X
FanOnHeat specifies the operation of the fan during HEAT mode. If  
FanOnHeat is 1(TRUE), then the fan is on when the mode is HEAT. If  
FanOnHeat is a 0 (FALSE) the fan is never turned on when the mode is  
HEAT, and typically a thermostatically controlled switch sensing heated air  
temperature turns on the fan.  
N
R
R
Download from Www.Somanuals.com. All Manuals Search And Download.  
                   
E
Table 25. Configuration Parameters. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
NOTE: Physical I/O points that are configurable are in Table 20.  
Comments  
W
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
nciConfig  
Field Name  
Default  
DisMinHtTime  
DisableHeatMinTime  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
FALSE  
P
P
P
X
X
X
X
X
X
If DisableHeatMinTime is 0 (FALSE), the heating stages are on or off for a  
minimum time determined by ubHeatCph (Refer to Table 17 Interstage  
Minimum Times of the System Engineering Guide). If DisableHeatMinTime  
is 1 (TRUE), the heating stages are on or off for a 30 second minimum  
time.  
,
NST  
DisMinClTime  
CascCntrl  
nciConfig  
nciConfig  
DisableCoolMinTime  
CascadeControl  
FALSE  
TRUE  
0
1
If DisableCoolMinTime is 0 (FALSE), the cooling stages are on or off for a  
minimum time determined by CoolCph (Refer to Table 17 Interstage  
Minimum Times of the System Engineering Guide). If DisableCoolMinTime  
is 1 (TRUE), the cooling stages are on or off for a 30 second minimum  
time.  
NTV  
MEAHUCO  
FALSE  
TRUE  
0
1
When CascadeControl is 0 (FALSE), then the discharge air temperature is  
not directly controlled and heating and cooling equipment are modulated to  
maintain space temperature. When CascadeControl is 1 (TRUE), then the  
discharge air temperature is controlled by an additional control loop based  
on the error signal from the space temperature control loop. Cascade  
Control is applicable to modulating heating/cooling only (not staged).  
N
UseRaTempCtl nciConfig  
ControlUsesRtnAirTemp FALSE  
TRUE  
0
1
FALSE  
FALSE  
P
P
X
X
X
X
If ControlUsesRtnAirTemp is a 0 (FALSE), then Data2.SpaceTemp is set  
equal either the space temperature sensor (IO.siSpaceTemp) or  
SpaceTemp depending on the value of SpaceTemp. When  
ControlUsesRtnAirTemp is 1 (TRUE) and SpaceTemp is SI_INVALID, then  
Data2.SpaceTemp is set equal to return air sensor (IO.ReturnTemp) and  
the control uses the return air sensor to control heating or cooling. When  
ControlUsesRtnAirTemp is 1 (TRUE) and SpaceTemp is not SI_INVALID,  
then Data2.siSpaceTemp is set equal to SpaceTemp and the control uses  
SpaceTemp to control heating or cooling.  
R
E
IaqUseHeat  
nciConfig  
IaqUseHeat  
FALSE  
TRUE  
0
1
When the effective occupancy is OC_OCCUPIED and IaqUseHeat is 0  
(FALSE), then no heating stages or modulating heating are turned when  
the discharge air temperature goes below the low limit. Energy has priority  
over ventilation. When the effective occupancy is OC_OCCUPIED and  
IaqUseHeat is 1 (TRUE), then the heating stages or modulating heating  
are turned on to prevent the discharge air temperature from going below  
the discharge air temperature low limit. Ventilation has priority over energy  
cost.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Table 25. Configuration Parameters. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
NOTE: Physical I/O points that are configurable are in Table 20.  
Comments  
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
nciConfig  
Field Name  
OverridePriority  
Default  
OvrdPriority  
LAST  
NET  
0
1
NET  
P
X
X
OverridePriority configures the override arbitration between ManOcc,  
Bypass.state, and the wall module override button. If OverridePriority is 0  
(LAST), then the last command received from either the wall module or  
iManOcc determines the effective override state. If OverridePriority is 1  
(NET), this specifies that when ManOcc is not OC_NUL, that the effective  
occupancy is ManOcc regardless of the wall module override state.  
UseWallModStpt nciConfig  
UseWallModStPt  
SetPntKnob  
FALSE  
TRUE  
0
1
TRUE  
P
P
X
X
X
X
UseWallModStpt specifies the OC_OCCUPIED temperature setpoint  
source. If UseWallModStpt is 0 (FALSE), then the occupied TempSetPts  
are used when the effective occupancy is OC_OCCUPIED. If  
UseWallModStpt is 1 (TRUE), then the wall modules setpoint knob is used  
when the effective occupancy is OC_OCCUPIED. SetPt overrides all.  
SetPtKnob  
OvrdType  
nciConfig  
nciConfig  
OFFSET  
ABSOLUTE_MIDDLE  
0
1
ABSOLUTE_MIDDLE  
NORMAL  
SetPntKnob specifies the usage of the setpoint knob when  
UseWallModStPt is TRUE. When SetPntKnob is 0 (ABSOLUTE_MIDDLE),  
the setpoint knob directly determines the center point of between the  
OC_OCCUPIED cooling and heating setpoints. When SetPntKnob is 1  
(OFFSET), the effective setpoint is calculated by adding the remote  
setpoint potentiometer value (center scale = 0) to the appropriate value of  
TempSetPts.  
E
OverrideType  
NONE  
0
1
2
P
X
X
OverrideType specifies the behavior of the override button. If the  
OverrideType is 0 (NONE) then the override button is disabled. An  
OverrideType of 1 (NORMAL), causes the override button to set the  
OverRide state to OC_BYPASS for Aux2SetPt.BypassTime seconds when  
the override button has been pressed for approximately 1 to 4 seconds, or  
to set the OverRide state to UNOCC when the button has been pressed for  
approximately 4 to 7 seconds. When the button is pressed longer than  
approximately 7 seconds, then the OverRide state is set to OC_NUL. If the  
OverrideType is 2 (BYPASS_ONLY), the override button sets the OverRide  
state to OC_BYPASS for Aux2SetPt.BypassTime seconds on the first  
press. On the next press, the OverRide state is set to OC_NUL.  
NORMAL  
BYPASS_ONLY  
W
,
C
NST  
Table 26. LONMARK®/Open System Points.  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
NTV  
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
Field Name  
Default  
Comments  
AHUCO  
nciNodeSendT  
Seconds  
0
0
The maximum time between updates of network variable outputs from the  
node object.  
(SNVT_time_sec)  
nciRtuSendT  
(SNVT_time_sec)  
Seconds  
The SGPUC and SGPU time (heart beat time) between updates of network  
variable outputs.NOTE: RtuSendT should be set to 55 seconds by a  
management node to be compatible with a Honeywell system.  
T
R
nciRtuRcvT  
(SNVT_time_sec)  
Seconds  
0
This is the failure detection time for network SGPUC and SGPU variables  
outputs.NOTE: RtuRcvT should be set to 300 seconds by a management  
node to be compatible with a Honeywell system.  
R
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
E
Table 26. LONMARK®/Open System Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
W
Engineering Units: English  
User Address  
NvName  
Field Name  
occupied_cool  
(Metric) or States plus Range  
Default  
Comments  
CoolOccSpt  
nciTempSetPts  
(SNVT_temp_setpt)  
Degrees F  
50 to 95  
Degrees C  
(10 to 35)  
23  
25  
P,  
X
X
X
X
The Cooling Occupied Setpoint is used if no wall module setpoint pot is  
configured as the standard Occupied Cooling Setpoint. Actual Cooling  
Setpoint can be affected by various control parameters (such as DlcShed,  
SrcRmtTempSpt, etc.). Actual room temperature Setpoint is reflected in  
RmTempActSpt. Overridden by nviSetPt. Used to compute ZEB.  
,
M
NST  
CoolStbySpt  
nciTempSetPts  
(SNVT_temp_setpt)  
standby_cool  
Degrees F  
50 to 95  
Degrees C  
(10 to 35)  
P,  
M
When the controller is in the Standby mode (typically via an occupancy  
sensor), the base Cooling Setpoint is determined by the Cooling Standby  
Setpoint value. Also, when a wall module setpoint pot is configured, this  
value serves as the upper limit on the user adjustable remote setpoint pot  
(wall module).  
NTV  
MEAHUCO  
CoolUnoccSpt  
HeatOccSpt  
HeatStbySpt  
nciTempSetPts  
unoccupied_cool  
occupied_heat  
standby_heat  
Degrees F  
50 to 95  
Degrees C  
(10 to 35)  
28  
21  
19  
P,  
X
X
X
X
X
X
When the controller is in the Unoccupied mode, the unit responds to a call  
for cooling based on the Cooling Unoccupied Setpoint.  
(SNVT_temp_setpt)  
M
nciTempSetPts  
(SNVT_temp_setpt)  
Degrees F  
50 to 95  
Degrees C  
(10 to 35)  
P,  
M
When the controller is in the Occupied mode, if the space temperature  
drops below the Heating Occupied Setpoint, the unit switches to the  
Heating mode. This Setpoint is used only when there is no wall module  
setpoint pot configured. Overridden by nviSetPt. Used to compute ZEB.  
N
R
nciTempSetPts  
(SNVT_temp_setpt)  
Degrees F  
50 to 95  
P,  
M
When the controller is in the Standby mode (typically via an occupancy  
sensor), the base Heating Setpoint is determined by the Heating Standby  
Setpoint value. Also, when a wall module setpoint pot is configured, this  
value serves as the lower limit on the user adjustable remote setpoint pot  
(wall module).  
E
Degrees C  
(10 to 35)  
HeatUnoccSpt  
nciTempSetPts  
unoccupied_heat  
object_id  
Degrees F  
50 to 95  
16  
1
P,  
M
X
X
When the controller is in the Unoccupied mode, the unit responds to a call  
for heating based on the Heating Unoccupied Setpoint.  
(SNVT_temp_setpt)  
Degrees C  
(10 to 35)  
nviRequest  
(SNVT_obj_request)  
0 to 65535  
Request provides the mechanism to request a particular status report (via  
Status) for a particular object within this node. Object_id selects the object  
being referenced by nviRequest. The only valid value of object_id is 1 for  
the RTU object and all others are invalid.  
nviRequest  
(SNVT_obj_request)  
object_request  
RQ_NORMAL  
0
RQ_NORMAL  
When object_request is RQ_NORMAL or RQ_UPDATE_STATUS then the  
status (via Status) will be reported for the object addressed by object_id.  
When object_request is RQ_REPORT_MASK then the status bits will be  
reported that are supported in nvoStatus by the object addressed by  
object_id. Bits that are supported by the object are set to one. All other  
object_request items are not supported at this time and will return an  
invalid_request (Status) in the object status.  
RQ_DISABLED  
1
RQ_UPDATE_STATUS  
RQ_SELF_TEST  
RQ_UPDATE_ALARM  
RQ_REPORT_MASK  
RQ_OVERRIDE  
2
3
4
5
6
RQ_ENABLE  
7
RQ_RMV_OVERRIDE  
RQ_CLEAR_STATUS  
RQ_CLEAR_ALARM  
RQ_NUL  
8
9
10  
255  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Table 26. LONMARK®/Open System Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
Field Name  
Default  
Comments  
DestHvacMode  
nviApplMode  
(SNVT_hvac_mode)  
HVAC_AUTO  
0
HVAC_AUTO  
M X X  
X
X
X ApplMode is an input that coordinates the roof top unit controller operation  
HVAC_HEAT  
1
with other controllers. HVAC_NIGHT_PURGE  
HVAC_MRNG_WRMUP  
HVAC_COOL  
2
HVAC_PRE_COOL  
3
HVAC_MRNG_WRMUP  
HVAC_NIGHT_PURGE  
HVAC_PRE_COOL  
HVAC_OFF  
4
HVAC_NUL  
5
HVAC_TEST are not supported and will default to the HVAC_AUTO setting  
if received.  
6
HVAC_TEST  
7
HVAC_EMERG_HEAT  
HVAC_FAN_ONLY  
HVAC_NUL  
8
9
255  
DestManOcc  
nviManOcc  
(SNVT_occupancy)  
OC_OCCUPIED  
OC_UNOCCUPIED  
OC_BYPASS  
OC_STANDBY  
OC_NUL  
0
OC_NUL  
X
X
X
ManOcc is an input from a network connected operator interface or other  
node that indicates the state of a manual occupancy control thus over  
riding the scheduled occupancy state. ManOcc is used along with other  
occupancy inputs to calculate the effective occupancy of the node. See the  
Data1.EffectOcc and Data1.NetManOcc for more details.The valid  
enumerated values have the following meanings: OC_OCCUPIED  
indicates occupied. OC_UNOCCUPIED indicates not occupied.  
OC_BYPASS indicates that the space is occupied for  
1
2
3
255  
E
Aux2SetPt.BypassTime seconds after ManOcc is first set to OC_BYPASS.  
The timing is done by the bypass timer in this node. If ManOcc changes to  
another value the timer is stopped.OC_STANDBY indicates that the space  
is in standby mode.OC_NUL and all unspecified values means that no  
manual occupancy control is requested. When ManOcc changes from  
OC_OCCUPIED, OC_UNOCCUPIED, OC_BYPASS, or OC_STANDBY to  
OC_NUL, any bypass condition is canceled.  
W
DestRmTempSpt  
DestSptOffset  
nviSetPoint  
Degrees F  
50 to 95  
SI_INVALID  
0
X
X
X
X
X
X
X
X
SetPoint is an input network variable used to determine the temperature  
control point of the node. If SetPoint is not SI_INVALID, then it is used to  
determine the control point of the node. If SetPoint is SI_INVALID, then  
other means are used to determine the control point. See  
(SNVT_temp_p)  
B
Degrees C  
(10 to 35)  
,
Data2.TempControlPt for more information.  
NST  
nviSetPtOffset  
(SNVT_temp_p)  
Degrees F  
-18 to 18  
Degrees C  
-10 to 10  
X SetPtOffset is input from an operator terminal or from an energy  
management system used to shift the effective temperature setpoint by  
adding SetPtOffset to the otherwise calculated setpoint. If the value is  
outside the allowed range of -10 to +10 degrees C (-18 to 18 degrees F),  
then the node uses the value of the nearest range limit.  
NTV  
SrcRmTempActSpt nvoEffectSetPt  
(SNVT_temp_p)  
Degrees F  
50 to 95  
Degrees C  
(10 to 35)  
SI_INVALID  
EffectSetPt is the current temperature control point (such that the current  
actual space temperature setpoint which the controller is presently trying to  
maintain in the conditioned space). See Data2.TempControlPt for more  
details. EffectSetPt is updated according to the SGPU mechanism where a  
significant change is plus or minus 0.07 degrees C (0.13 degrees F).  
AHUCO  
N
R
E
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
E
Table 26. LONMARK®/Open System Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
W
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
Field Name  
Default  
Comments  
DestRmTemp  
nviSpaceTemp  
(SNVT_temp_p)  
Degrees F  
14 to 122  
Degrees C  
(-10 to 50)  
SI_INVALID  
X
X
X
X SpaceTemp is the space temperature sensed by another node and is  
typically bound to SpaceTemp of another node having a space temperature  
sensor. If SpaceTemp has a value other than SI_INVALID it is used as the  
sensed space temperature by the node rather than using any local hard-  
wired sensor. If the value is outside the allowed range of -10 to 50 degrees  
C (-18 to 90 degrees F), then the node uses the value of the nearest range  
limit. When SpaceTemp is not bound to another node, SpaceTemp may be  
used to fix the sensed temperature. A management node may write a value  
other than SI_INVALID, causing the node to use SpaceTemp instead of the  
hard-wired sensor. An application restart or power failure causes the fixed  
sensor value to be forgotten and SpaceTemp to be returned to  
SI_INVALID.  
,
NST  
NTV  
MEAHUCO  
SrcRmTemp  
DestOaTemp  
nvoSpaceTemp  
(SNVT_temp_p)  
Degrees F  
14 to 122  
Degrees C  
(-10 to 50)  
SI_INVALID  
SI_INVALID  
X
X
X
SpaceTemp is the sensed space temperature from the locally wired sensor.  
SpaceTemp is typically bound to SpaceTemp of another node which may  
not have its own space temperature sensor but control the same space.  
The reported space temperature includes the offset correction  
Config.SpaceTempZeroCal. If the space temperature sensor is not  
connected or is shorted, or if SpaceTemp is bound to another node, then  
SpaceTemp is set to SI_INVALID.  
N
R
nviOdTemp  
(SNVT_temp_p)  
Degrees F  
-40 to 122  
Degrees C  
(-40 to 50)  
M X  
X
X OdTemp allows one outside air temperature sensor at a node to be shared  
by many other nodes. When OdTemp is not SI_INVALID, then any local  
sensor is ignored by the local control algorithm and OdTemp is used  
instead. If the value is outside the allowed range of -40 to 50 degrees C (-  
72 to 90 degrees F), then the node uses the value of the nearest range  
limit.  
E
SrcOaTemp  
DestOaHum  
SrcOaHum  
nvoOdTemp  
Degrees F  
-40 to 122  
Degrees C  
(-40 to 50)  
SI_INVALID  
SI_INVALID  
SI_INVALID  
M X  
M X  
M X  
X
X
X
OdTemp allows the local outdoor temperature sensor to be shared with  
other nodes and is typically bound to OdTemp on other nodes. If the local  
sensor is configured by Select, OdTemp is periodically sent on the network.  
If the local sensor is not configured or currently showing an error, the value  
is SI_INVALID.  
(SNVT_temp_p)  
nviOdHum  
(SNVT_lev_percent)  
Percentage  
10 to 90  
X
X OdHum allows one outdoor humidity sensor at a node to be shared by  
many other nodes. When nviOdHum is not SI_INVALID, then the local  
sensor, is ignored by the local control algorithm and OdHum is used  
instead. If the value is outside the allowed range (10 to 90 percent), then  
the node uses the value of the nearest range limit.  
nvoOdHum  
(SNVT_lev_percent)  
Percentage  
10 to 90  
OdHum allows the local outdoor humidity sensor to be shared with other  
nodes and is typically bound to OdHum on other nodes. If the local sensor  
is configured by Select, OdHum is periodically sent on the network. If the  
local sensor is not configured or currently showing an error, the value is  
SI_INVALID.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Table 26. LONMARK®/Open System Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
Field Name  
Default  
Comments  
DestEmergCmd  
nviEmerg  
(SNVT_hvac_emerg)  
EMERG_NORMAL  
EMERG_PRESSURIZE  
EMERG_DEPRESSURIZE  
EMERG_PURGE  
EMERG_SHUTDOWN  
EMERG_NUL  
0
EMERG_NORMAL M X X  
X
X
Emerg is an emergency input from a device that determines the correct  
action during a given emergency (such as a fire). If Emerg is  
EMERG_NORMAL the fan and economizer damper are controlled by the  
heating and cooling control algorithm. If Emerg is EMERG_PRESSURIZE,  
then the fan is controlled on and the economizer damper is open. If Emerg  
is EMERG_DEPRESSURIZE, then the fan is controlled on and the  
economizer damper is closed. If Emerg is EMERG_SHUTDOWN, then the  
fan is controlled off and the economizer damper is closed. If Emerg is  
EMERG_PURGE, the fan and damper go to the state specified by  
Config.SmokeControl. If Emerg is not configured then it is set to  
EMERG_NUL.  
1
2
3
4
255  
SrcUnitStatus  
nvoUnitStatus  
(SNVT_hvac_status)  
mode  
HVAC_AUTO  
0
HVAC_NUL  
M X  
X
Mode is set according to the Data1.mode. If Data1.mode is  
HVAC_HEAT  
1
START_UP_WAIT, SMOKE_EMERGENCY, or FREEZE_PROTECT, mode  
is set to HVAC_NUL which indicates that the node is in a mode not  
supported by the SNVT_hvac_mode data type. If Data1.mode is HEAT,  
then mode is set to HVAC_HEAT which indicates that heating energy is  
being supplied to the controlled space. If Data1.mode is COOL, then mode  
is set to HVAC_COOL, which indicates that cooling energy is being  
supplied to the controlled space. If Data1.mode is OFF_MODE or  
DISABLED_MODE, then mode is set to HVAC_OFF which indicates that  
the node is not running its normal temperature control and the outputs are  
not turned off. If Data1.mode is EMERG_HEAT, mode is set to  
HVAC_MRNG_WRMUP  
HVAC_COOL  
2
3
HVAC_NIGHT_PURGE  
HVAC_PRE_COOL  
HVAC_OFF  
4
5
6
HVAC_TEST  
7
L
HVAC_EMERG_HEAT  
HVAC_FAN_ONLY  
HVAC_NUL  
8
9
255  
HVAC_EMERG_HEAT where, in a heat pump application, the compressor  
stages are disabled and only auxiliary heating stages are turned on. If  
Data1.mode is MANUAL or FACTORY_TEST, mode is set to HVAC_TEST  
which indicates that the node is in a manual or test mode. If Data1.mode is  
FAN_ONLY, mode is set to HVAC_FAN_ONLY which indicates that the fan  
is running but the space temperature control is turned off.  
W
,
nvoUnitStatus  
heat_output_primary  
Percentage  
0 to 100  
0
0
0
heat_output_primary reports the current percentage of heating stages or  
modulating heat turned on. If the node is controlling a heat pump,  
heat_output_primary reports the current percentage of compressor stages  
turned on when the node is in the HVAC_HEAT mode.  
,
(SNVT_hvac_status)  
NST  
nvoUnitStatus  
(SNVT_hvac_status)  
heat_output_secondary Percentage  
0 to 100  
If the node is controlling a heat pump, heat_output_secondary reports the  
current percentage of auxiliary heating stages turned on when the node is  
in the HVAC_HEAT or HVAC_EMERG_HEAT mode. If the node is not  
controlling a heat pump, heat_output_secondary is set to zero.  
NTV  
nvoUnitStatus  
(SNVT_hvac_status)  
cool_output  
Percentage  
0 to 100  
cool_output reports the current percentage of cooling stages or modulating  
cool turned on. If the node is controlling a heat pump, cool_output reports  
the current percentage of compressor stages turned on when the node is in  
the HVAC_COOL mode.  
AHUCO  
nvoUnitStatus  
econ_output  
fan_output  
Percentage  
0 to 100  
0
0
If there is a modulating economizer configured, econ_output reports the  
percentage that the economizer damper is opened. If no economizer is  
configured, econ_output reports 0.  
(SNVT_hvac_status)  
nvoUnitStatus  
(SNVT_hvac_status)  
Percentage  
0 to 100  
When the fan is running, fan_output is 100 percent, and when the fan is not  
running, fan_output is 0 percent.  
N
R
R
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
E
Table 26. LONMARK®/Open System Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
W
Engineering Units: English  
User Address  
NvName  
Field Name  
in_alarm  
(Metric) or States plus Range  
Default  
FALSE  
Comments  
nvoUnitStatus  
(SNVT_hvac_status)  
FALSE  
TRUE  
0
1
When there is an alarm reported by AlarmStatus, then in_alarm is set to 1  
(TRUE), else in_alarm is set to 0 (FALSE). If alarms reporting is  
suppressed via ManualMode, then in_alarm is set to  
ALARM_NOTIFY_DISABLED.  
,
ALARM_NOTIFY_DISABLED 255  
NST  
nviInUse(unsigned  
long)  
0 To 65535  
0 to FFFF  
InUse is used by a management node to indicate to all other management  
nodes that it is logged on to the Excel 10 node and that they should not try  
to interact with any of the Excel 10s network variables. Before the  
management node reads or writes any network variables, the management  
node checks nviInUse for a zero value meaning no other management  
nodes are already logged on and that a management node may log on to  
the node. Then the management node writes a number, 1 through 65534,  
to nviInUse and periodically writes the same value to indicate that the  
management node is still logged on. If there are no writes made to  
nviInUse for approximately 60 seconds, then the Excel 10 resets nviInUse  
to zero to automatically log off the management node. Before interacting  
with any network variables, the management node verifies that the  
nviInUse has not changed. The management node logs off by writing 0 to  
nviInUse.During power up, an application restart, or return to on-line from  
off-line, the Excel 10 sets InUse to 65535 to indicate to the management  
node that it has returned to on-line.  
NTV  
MEAHUCO  
N
O
nvoStatus  
object_id  
0 to 65535  
0
M
X
object_id is set to the current value of nviRequest.object_id  
E
(SNVT_obj_request)  
nvoStatus  
invalid_id  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
FALSE  
If Request.Object_id is not a valid object, invalid_id is set to 1 (TRUE)  
otherwise it is set to 0 (FALSE).  
(SNVT_obj_request)  
nvoStatus  
(SNVT_obj_request)  
invalid_request  
disabled  
FALSE  
TRUE  
0
1
If Request.object_request is not a valid request for the object addressed,  
invalid_request is set to 1 (TRUE) otherwise it is set to 0 (FALSE).  
nvoStatus  
(SNVT_obj_request)  
FALSE  
TRUE  
0
1
The disabled field is not supported and is set to 0 (FALSE) unless  
Request.object_request is RQ_REPORT_MASK, then disabled and  
in_alarm are set to 1 (TRUE) to indicate that these functions are supported  
while all other fields are set to 0 (FALSE).  
nvoStatus  
out_of_limits  
open_circuit  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
The out_of_limits field is not supported and is set to 0 (FALSE).  
The open_circuit field is not supported and is set to 0 (FALSE).  
The out_of_service field is not supported and is set to 0 (FALSE).  
The mechanical_fault field is not supported and is set to 0 (FALSE).  
The feedback_failure field is not supported and is set to 0 (FALSE).  
The over_range field is not supported and is set to 0 (FALSE).  
The under_range field is not supported and is set to 0 (FALSE).  
(SNVT_obj_request)  
nvoStatus  
(SNVT_obj_request)  
FALSE  
TRUE  
0
1
nvoStatus  
(SNVT_obj_request)  
out_of_service  
mechanical_fault  
feedback_failure  
over_range  
FALSE  
TRUE  
0
1
nvoStatus  
(SNVT_obj_request)  
FALSE  
TRUE  
0
1
nvoStatus  
(SNVT_obj_request)  
FALSE  
TRUE  
0
1
nvoStatus  
(SNVT_obj_request)  
FALSE  
TRUE  
0
1
nvoStatus  
(SNVT_obj_request)  
under_range  
FALSE  
TRUE  
0
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 26. LONMARK®/Open System Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
Engineering Units: English  
User Address  
NvName  
Field Name  
electrical_fault  
(Metric) or States plus Range  
Default  
FALSE  
Comments  
nvoStatus  
(SNVT_obj_request)  
FALSE  
TRUE  
0
1
The electrical_fault field is not supported and is set to 0 (FALSE).  
nvoStatus  
unable_to_measure  
comm_failure  
fail_self_test  
FALSE  
TRUE  
0
1
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
FALSE  
The unable_to_measure field is not supported and is set to 0 (FALSE).  
The comm_failure field is not supported and is set to 0 (FALSE).  
The fail_self_test field is not supported and is set to 0 (FALSE).  
The self_test_in_progress field is not supported and is set to 0 (FALSE).  
The locked_out field is not supported and is set to 0 (FALSE).  
The manual_control field is not supported and is set to 0 (FALSE).  
(SNVT_obj_request)  
nvoStatus  
(SNVT_obj_request)  
FALSE  
TRUE  
0
1
nvoStatus  
(SNVT_obj_request)  
FALSE  
TRUE  
0
1
nvoStatus  
(SNVT_obj_request)  
self_test_in_progress  
locked_out  
FALSE  
TRUE  
0
1
nvoStatus  
(SNVT_obj_request)  
FALSE  
TRUE  
0
1
nvoStatus  
(SNVT_obj_request)  
manual_control  
in_alarm  
FALSE  
TRUE  
0
1
nvoStatus  
(SNVT_obj_request)  
FALSE  
TRUE  
0
1
If there are currently any active alarms reported by SrcUnitStatus.in_alarm  
or SrcUnitStatus.in_alarm is set to ALARM_NOTIFY_DISABLED,in_alarm  
is set to 1 (TRUE), otherwise in_alarm is set to 0 (FALSE). When  
Request.object_request is RQ_REPORT_MASK, then disabled and  
in_alarm are set to 1 (TRUE) to indicate that these functions are supported  
while all other fields are set to 0 (FALSE).  
E
W
nvoStatus  
(SNVT_obj_request)  
in_override  
FALSE  
TRUE  
0
1
FALSE  
The in_override field is not supported and is set to 0 (FALSE).  
DestOccSensor  
nviSensorOcc  
(SNVT_occupancy)  
OC_OCCUPIED  
OC_UNOCCUPIED  
OC_BYPASS  
OC_STANDBY  
OC_NUL  
0
OC_NUL  
M X  
X
X
X nviSensorOcc allows an occupancy sensor at another node to be used as  
the occupancy sensor for this node and is typically bound to SensorOcc of  
another node. The nviSensorOcc input must show OC_UNOCCUPIED for  
300 seconds before it is used by the controller for triggering UN_OC  
operation. This makes it possible for several occupancy sensors to be  
ORed together by binding them all to nviSensorOcc. If any one bound  
occupancy sensor shows occupancy, then SensorOcc shows occupancy  
for up to 300 seconds after the last sensor shows OC_OCCUPIED. The  
valid states have the following meanings: OC_OCCUPIED indicates  
occupied. OC_BYPASS, OC_STANDBY, and all unspecified values  
indicates the same as OC_OCCUPIED. OC_UNOCCUPIED or OC_NUL  
indicates not occupied.  
,
1
C
2
3
255  
NST  
NTV  
SrcOccSensor  
nvoSensorOcc  
(SNVT_occupancy)  
OC_OCCUPIED  
OC_UNOCCUPIED  
OC_BYPASS  
OC_STANDBY  
OC_NUL  
0
OC_NUL  
M X  
X
nvoSensorOcc is an output showing the current state of the hard wired  
occupancy sensor. The valid states are as follows: OC_OCCUPIED  
indicates that the space is occupied. OC_UNOCCUPIED indicates that the  
space is not occupied. OC_NUL means no output is available because it is  
not configured.  
1
AHUCO  
2
3
255  
N
R
E
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
E
Table 26. LONMARK®/Open System Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
W
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
Field Name  
Default  
Comments  
nviWindow  
(SNVT_switch)  
value  
0 to 100  
0
Window allows the window sensor from another node to be used as the  
window sensor and is typically bound to nvoWindow of another node.  
Window must show that the window is closed for 300 seconds before  
Window is used as window closed. This makes it possible for several  
window sensors to be ORed together by binding them all to nviWindow. If  
any one bound window sensor shows window open, then Window shows  
window open for up to 300 seconds after the last sensor shows window  
closed. If the state is SW_OFF or SW_NUL, then the result is Window  
Closed. If the state is SW_ON and the value is 0, then the result is Window  
Closed. If the node receives this combination of state and value, then state  
is set to SW_OFF. If the state is SW_ON and the value is not zero, then the  
result is Window Open. NOTE: nviWindow is called nviEnergyHoldOff in  
O
NST  
NTV  
MEAHUCO  
ON ARK  
compliance profile.  
the L  
M
DestWndw  
nviWindow  
state  
SW_OFF  
SW_ON  
SW_NUL  
0
SW_NUL  
M X  
X
X
X
X See the preceding.  
(SNVT_switch)  
1
255  
SrcWndwCt  
SrcWndw  
nvoWindow  
(SNVT_switch)  
value  
state  
0 to 100  
0
X
See the preceding.NOTE: nvoWindow is called nviEnergyHoldOff in the  
LonMark compliance profile.  
N
O
nvoWindow  
(SNVT_switch)  
SW_OFF  
SW_ON  
SW_NUL  
0
1
255  
SW_NUL  
M X  
Window allows the hard wired window sensor to be used by other nodes on  
the network. The valid states are as follows: If the state is SW_OFF and the  
value is 0 then the result is Window Closed. If the state is SW_ON and the  
value is 100 percent, the result is Window Open. If the state is SW_NUL  
and the value is 0, the result is Window Sensor Not Configured. NOTE:  
nvoWindow is called nviEnergyHoldOff in the LonMark compliance profile.  
R
nviEcon  
(SNVT_switch)  
value  
0 to 100  
0
nviEcon allows one controller to determine the suitability of outdoor air for  
free cooling and share this with many other nodes. When Econ.state is not  
SW_NUL, then the local sensor selected by Config.EconEnable is ignored  
and Econ is used instead. The inputs states have the following meanings: If  
the state is SW_OFF or other and the value is dont care, then the outdoor  
air is not suitable for free cooling. If the state is SW_ON and the value is 0,  
then the outdoor air is not suitable for free cooling. If the node receives this  
combination of state and value, then state is set to SW_OFF. If the state is  
SW_ON and the value is not zero, then outdoor is suitable for free cooling.  
If the state is SW_NUL, then the network variable is not bound, the  
communications path from the sending node has failed, or the sending  
node has failed. Outdoor air is not suitable for free cooling.  
DestEconEnable  
nviEcon  
(SNVT_switch)  
state  
SW_OFF  
SW_ON  
SW_NUL  
0
SW_NUL  
M X  
X
X
X For nviEcon.state, refer to nviEcon.value.  
1
255  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Table 26. LONMARK®/Open System Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
Field Name  
Default  
Comments  
SrcEconEnCt  
nvoEcon  
(SNVT_switch)  
value  
0 to 100  
0
X
nvoEcon allows one controller to determine the suitability of outdoor air for  
free cooling and share this with other nodes and is typically bound to Econ  
on other nodes. If the economizer function is configured by  
Config.EconEnable, Econ is periodically calculated from the local sensor  
specified by Config.EconEnable and is sent on the network. Econ does not  
affect Econ. The output has the following states: If the state is SW_OFF  
and the value is 0, then the outdoor air is not suitable for free cooling. If the  
state is SW_ON and the value is 100 percent, then the outdoor air is  
suitable for free cooling. If the state is SW_NUL and the value is 0, the  
corresponding economizer function is not enabled because  
Config.EconEnable is ECON_NUL, DIFF_TEMP, or DIFF_ENTH or  
because the selected sensor has failed.  
SrcEconEnable  
nvoEcon  
(SNVT_switch)  
state  
SW_OFF  
SW_ON  
SW_NUL  
0
SW_NUL  
M X  
X
For nvoEcon.state, refer to nvoEcon.value.  
1
255  
E
W
,
O
NST  
NTV  
AHUCO  
N
R
R
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
E
Table 27. Direct Access And Special Points.  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
W
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
Field Name  
Default  
Comments  
O
DestManMode  
nviManualMode  
MODE_ENABLE  
0
1
2
3
4
MODE_ENABLE  
X X  
X
ManualMode is an input which is used to disable the Excel 10s control algorithms  
and to manually set the physical outputs. ManualMode remains unchanged until  
another mode has been commanded or an application restart has been performed.  
See the Data1.mode for more details.The valid enumerated values are:  
MODE_ENABLE enables the node so that the control algorithm determines the  
operating mode, and controls the physical outputs. MODE_ENABLE is the default  
state after power restore or application restart. If the mode was MANUAL and  
nviManualMode is set to MODE_ENABLE, the node then goes through  
application_restart.MODE_DISABLE sets the node to the DISABLED_MODE. The  
alarm NODE_DISABLED is initiated, all control loops are disabled, and the physical  
outputs are turned off. The physical inputs, network variable inputs, and network  
variable outputs are still functioning when the node is in the DISABLED_MODE.  
MODE_MANUAL sets the node into the MANUAL mode. If MANUAL is selected, the  
controller enters Test Mode (manual override of outputs). The alarm  
MODE_DISABLE  
MODE_MANUAL  
SUPPRESS_ALARMS  
UNSUPPRESS_ALARMS  
NST  
NTV  
MEAHUCO  
NODE_DISABLED is initiated, all control loops are disabled, and the physical  
outputs are controlled manually as commanded by nviManValue. The nodes  
configuration variables and nviManValue are used to set valves, dampers, and / or  
digital output to the desired manual positions or state(s). The physical inputs,  
network variable inputs, and network variable outputs are still functioning when the  
node is in the MANUAL mode.SUPPRESS_ALARMS causes nvoAlarm.type to be  
set to ALARM_NOTIFY_DISABLED, and AlarmLog to no longer record alarms. If  
alarms are suppressed, UNSUPPRESS_ALARMS causes Alarm.type and  
AlarmLog to be returned to reporting alarms. See Alarm for more details. All  
unspecified values are the same as MODE_ENABLE.  
N
R
E
TestMode  
nviManValue  
OutDrive  
NORMAL_OP  
OUT_1_ON  
OUT_2_ON  
OUT_3_ON  
OUT_4_ON  
OUT_5_ON  
OUT_6_ON  
OUT_7_ON  
OUT_8_ON  
ALL_OUT_OFF  
ALL_OUT_ON  
DISABLE_OUT  
0
NORMAL_OP  
OutDrive ManValue is used for Factory Testing only.  
1
2
3
4
5
6
7
8
9
10  
11  
TestHCPos  
nviManValue  
nviManValue  
sbManHeatCoolPosS0 percentage  
-127 to 127  
0
0
X During MANUAL mode, ManHeatCoolPos sets the modulating position of the  
heating or cooling motor (if configured) to the specified position. If ManHeatCoolPos  
is less than 0 or greater than 100, the motor is overdriven for a period longer than  
the motor time to ensure that it is at the end of travel. The heat motor is driven when  
HeatCoolMode is 1 and the cool motor is driven when HeatCoolMode is 0. At the  
moment when the node transfers to MANUAL_MODE or HeatCoolMode is changed,  
ManHeatCoolPos is set the current motor position.  
TestEconPos  
sbManEconPosS0  
Percentage  
-127 to 127  
X During MANUAL mode, ManEconPos sets the modulating position of the  
economizer motor (if configured) to the specified position. If ManEconPos is less  
than 0 or greater than 100, the motor is overdriven for a period longer than the motor  
time to ensure that it is at the end of travel. At the moment when the node transfers  
to MANUAL_MODE, ManEconPos is set the current motor position.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Table 27. Direct Access And Special Points. (Continued)  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
Field Name  
Default  
Comments  
TestHtClStg1  
nviManValue  
HeatCoolStage1  
OFF  
ON  
0
1
OFF  
X During MANUAL mode, HeatCoolStage1 parameters turn the corresponding heat,  
or cool stage to on (1) or off (0). When HeatCoolMode is 0, then cooling loads are  
controlled. When HeatCoolMode is 1 and the node is controlling conventional  
equipment, then heating loads are controlled. When HeatCoolMode is 1 and the  
node is controlling a heat pump, then cooling loads are controlled.  
TestHtClStg2  
TestHtClStg3  
TestHtClStg4  
TestAuxHt1  
nviManValue  
nviManValue  
nviManValue  
nviManValue  
HeatCoolStage2  
HeatCoolStage3  
HeatCoolStage4  
AuxHeatCoolStage1  
OFF  
ON  
0
1
OFF  
OFF  
OFF  
OFF  
X For HeatCoolStage2, refer to HeatCoolStage1.  
X For HeatCoolStage3, refer to HeatCoolStage1.  
X For HeatCoolStage4. refer to HeatCoolStage1.  
OFF  
ON  
0
1
OFF  
ON  
0
1
OFF  
ON  
0
1
X AuxHeatCoolStage1During MANUAL mode when the node is configured to  
control a heat pump and HeatCoolMode is 1, these parameters turn the  
corresponding auxiliary heat stage on (1) or off (0).  
TestAuxHt2  
TestAuxHt3  
TestAuxHt4  
TestHtClMode  
nviManValue  
nviManValue  
nviManValue  
nviManValue  
AuxHeatCoolStage2  
AuxHeatCoolStage3  
AuxHeatCoolStage4  
HeatCoolMode  
OFF  
ON  
0
1
OFF  
OFF  
OFF  
OFF  
X AuxHeatCoolStage2During MANUAL mode when the node is configured to  
control a heat pump and HeatCoolMode is 1, these parameters turn the  
corresponding auxiliary heat stage on (1) or off (0).  
E
OFF  
ON  
0
1
X AuxHeatCoolStage3During MANUAL mode when the node is configured to  
control a heat pump and HeatCoolMode is 1, these parameters turn the  
corresponding auxiliary heat stage on (1) or off (0).  
OFF  
ON  
0
1
X AuxHeatCoolStage4During MANUAL mode when the node is configured to  
control a heat pump and HeatCoolMode is 1, these parameters turn the  
corresponding auxiliary heat stage on (1) or off (0).  
W
OFF  
ON  
0
1
X During MANUAL mode, HeatCoolMode determines whether heating or cooling  
outputs are turned on or off manually. When HeatCoolMode is 0, then cooling loads  
are controlled. When HeatCoolMode is 1 and the node is controlling conventional  
equipment, then heating loads are controlled. When HeatCoolMode is 1 and the  
node is controlling a heat pump, then cooling loads are controlled by Heat / Cool  
stages and heating stages are controlled by auxiliary heat stages. The  
CHANGE_OVER_RELAY_OUT is affected by HeatCoolMode as configured in  
Select.  
,
O
NST  
NTV  
TestSaFan  
TestAuxEcon  
TestOccStat  
TestFree1  
nviManValue  
nviManValue  
nviManValue  
nviManValue  
nviManValue  
FanOut  
OFF  
ON  
0
1
OFF  
OFF  
OFF  
OFF  
OFF  
X During MANUAL mode, FanOut turns the fan on (1) or off (0).  
AuxEconOut  
OccStatusOut  
Free1Out  
OFF  
ON  
0
1
X During MANUAL mode, AuxEconOut turns the AUX_ECON_OUT on(1) or off(0).  
OFF  
ON  
0
1
X During MANUAL mode, OccStatusOut turns the OCCUPANCY_STATUS_OUT to  
on(1 = not OC_UNOCCUPIED) or off (0).  
AHUCO  
OFF  
ON  
0
1
X During MANUAL mode, Free1Out turns the FREE1_OUT on(1) or off(0).  
TestFree2  
Free2Out  
OFF  
ON  
0
1
X During MANUAL mode, Free2Out turns the FREE2_OUT on(1) or off(0).  
N
R
E
Download from Www.Somanuals.com. All Manuals Search And Download.  
                           
E
Table 28. Data Share Points.  
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic  
W
Engineering Units: English  
(Metric) or States plus Range  
User Address  
NvName  
Field Name  
Default  
Comments  
DestOaEnth  
nviOdEnthS7  
mA  
4 to 20  
SI_INVALID  
X
X
X nviOdEnth allows one outdoor enthalpy sensor at a node to be shared by many  
other nodes. When nviOdEnth is not SI_INVALID then any local sensor is  
ignored by the local control algorithm and OdEnth is used instead. If the value is  
outside the allowed range (4 to 20 mA), then the node uses the value of the  
nearest range limit.  
,
NST  
SrcOaEnth  
nvoOdEnthS7  
nvoMonSw  
mA  
SI_INVALID  
0
M X  
X
X
nvoOdEnth allows the local outdoor enthalpy sensor to be shared with other  
nodes and is typically bound to OdEnth on other nodes. If the local sensor is  
configured by Select, nviOdEnth is periodically sent on the network. If the local  
sensor is not configured or currently showing an error, the value is SI_INVALID.  
4 to 20  
NTV  
SrcMonSwCt  
value  
0 to 100  
MonSw value allows the monitor switch to be shared with another node. MonSw  
is typically bound to an SBC to indicate a user defined alarm condition. The  
output values have the following meanings: If the state is SW_OFF and the  
value is 0, then the monitor switch is open. If the state is SW_ON and the value  
is 100 percent, then the monitor switch is closed. If the state is SW_NUL and  
the value is 0, then the monitor switch is not configured by Select.  
MEAHUCO  
SrcMonSw  
nvoMonSw  
nviIaqOvr  
state  
value  
SW_OFF  
SW_ON  
SW_NUL  
0
SW_NUL  
0
M
X
For MonSw.state, refer to MonSw.value.  
1
T
255  
R
0 to 100  
IaqOvr allows an indoor air quality sensor to be shared by many other nodes.  
The states are follows: If the state is SW_OFF and the value is dont care, then  
the indoor air quality is acceptable. If the state is SW_ON and the value is 0,  
then the indoor air quality is acceptable. If the node receives this combination of  
state and value, then state is set to SW_OFF. If the state is SW_ON and the  
value is not zero, then the indoor air quality is not acceptable and additional  
outdoor air is needed to bring it back to acceptable. If the state is SW_NUL and  
the value is dont care, then the indoor air quality is acceptable. If the state is  
other, then the network variable is not bound, the communications path from the  
sending node has failed, or the sending node has failed. The indoor air quality is  
acceptable.  
E
DestIaqOvrd  
SrcIaqOvrCt  
nviIaqOvr  
nvoIaqOvr  
state  
value  
SW_OFF  
SW_ON  
SW_NUL  
0
SW_NUL  
0
M X  
X X  
X X X For IaqOvr.state, refer to IaqOvr.value.  
1
255  
0 to 100  
IaqOvr allows an indoor air quality sensor to be shared with other nodes and is  
typically bound to IaqOvr on other nodes. If Data2.siSpaceCo2 is not  
SI_INVALID, and exceeds Aux1SetPt.CO2IaqLimit, then poor air quality is  
detected. In addition, if a local digital input is configured for IAQ_OVERRIDE_IN  
and IO.IaqOverRide is 1 (TRUE) then poor air quality is also detected. The state  
has the following meanings: If the state is SW_OFF and the value is 0, then the  
indoor air quality is acceptable. If the state is SW_ON and the value is 100  
percent, then the indoor air quality is not acceptable and additional outdoor air is  
needed to bring it back to an acceptable state. If the state is SW_NUL and the  
value is 0, then the economizer for this node has not been configured or there is  
no sensor (via IO.SpaceDo2 or IO.IaqOverRide) configured or the only  
configured sensor (via IO.SpaceCo2) has failed.  
SrcIaqOvr  
nvoIaqOvr  
state  
SW_OFF  
SW_ON  
SW_NUL  
0
SW_NUL  
M X  
X
For IaqOvr.State, refer to IaqOvr.value.  
1
255  
Download from Www.Somanuals.com. All Manuals Search And Download.  
               
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Approximate Memory Size Estimating Procedure.  
Appendix D. Q7750A Excel 10 Zone Manager  
Point Estimating Guide.  
1. Determine the number of points per controller required  
at the Central (for example, XBS).  
Memory size approximation is shown below: (all sizes in  
bytes)  
NOTE: All remaining points that are not mapped can  
be accessed through the Direct Access  
feature.  
When memory size is less than 110,000 bytes, the size is OK.  
When memory size is between 110,000 and 128,000 bytes,  
the application may be too large. The user must expect to  
reduce the application complexity, reduce the number of  
attached Excel 10s or distribute the Excel 10s over more than  
one Zone Manager.  
2. Calculate the number of Excel 10 Zone Manager pro-  
gram points that are used in control logic and in the  
switching table.  
3. Estimate the program complexity of the Zone Manager  
(one of three levels).  
a. No time programs, control logic, or switching tables.  
b. 10K of control logic (one time program, five  
switching tables, and five control loops).  
c. 20K of control logic (multiple time programs, ten  
switching tables, and ten control loops).  
Use Fig. 51 to determine the number of Excel 10s that  
can be connected to the Zone Manager.  
NOTE: More than 60 Excel 10s requires a Router.  
4. Repeat for each Q7750A Excel 10 Zone Manager in a  
project.  
When memory size is greater than 128,000, the size is too  
large. The application size must be reduced as described  
above.  
(A) NO TIME PROGRAM,  
NO CONTROL LOOPS,  
NO SWITCHING TABLES.  
920  
900  
900  
895  
(B) 10K CONTROL PROGRAM  
(FOR EXAMPLE,  
1 TIME PROGRAM,  
5 CONTROL LOOPS,  
800  
800  
5 SWITCHING TABLES.)  
765  
NUMBER OF  
C-BUS POINTS  
(EXCEL 10  
MAPPED  
NUMBER OF  
C-BUS POINTS  
(EXCEL 10  
MAPPED  
POINTS  
740  
700  
700  
POINTS  
PLUS ZONE  
MANAGER  
POINTS)  
PLUS ZONE  
MANAGER  
POINTS)  
(C) 20K CONTROL PROGRAM  
(I.E., MULTIPLE TIME PROGRAMS,  
10 CONTROL LOOPS,  
10 SWITCHING TABLES.)  
610  
600  
600  
585  
20  
(OR LESS)  
60  
(ADD ROUTER)  
120  
M8729  
NUMBER OF EXCEL 10s  
Fig. 51. Point capacity estimate for Zone Manager.  
The exact equation for calculating memory size follows:  
Memory size = 21,780  
Excel 10 units =number of attached Excel 10s.  
C-Bus points = including mapped points and others; for  
example, remote points.  
+ 4096 (in case of a time program).  
+ CARE Control Program.  
Mapped points = number of mapped points per Excel 10,  
+ 14 x time points x Excel 10 units.  
+ 50 x Excel 10 units.  
including One-to-Many and  
Many-to-One mechanism.  
+ map complexity x Excel 10 units x mapped points.  
+ 57 x C-Bus points.  
+ 7488 x Excel 10 types.  
Excel 10 types = number of different Excel 10 types  
(currently three)  
Map complexity=  
20 =using One-to-Many and not using points  
Where:  
with read/write.  
Time points = number of switch points in time program  
per Excel 10.  
30 = average.  
45 = many points with read/write ability.  
109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
74-29581  
     
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Sensor Use:  
Return Air, Discharge Air Temperature  
Appendix E. Sensor Data for Calibration.  
Resistance Sensors.  
Table 30 lists the points for Sensor Resistance versus  
Temperature. Fig. 53 shows the graph of these points.  
Sensor Type:  
C7100A, (and C7170A)  
Table 30. Sensor Resistance Versus Temperature.  
°F  
30  
Resistance Ohms  
1956.79  
1935.79  
1914.79  
1893.79  
1872.79  
1851.79  
1830.79  
1809.79  
1788.79  
1767.79  
1746.79  
1725.79  
1704.78  
1683.78  
1662.78  
1641.78  
1620.78  
1599.78  
1578.78  
Sensor Use:  
Discharge air, Outdoor air  
35  
Table 29 lists the points for Sensor Resistance versus  
Temperature. Fig. 52 shows the graph of these points.  
40  
45  
Table 29. Sensor Resistance Versus Temperature.  
50  
°F  
-40  
-30  
-20  
-10  
0
Resistance Ohms  
2916.08  
2964.68  
3013.28  
3061.88  
3110.48  
3159.08  
3207.68  
3256.28  
3304.88  
3353.48  
3402.08  
3450.68  
3499.28  
3547.88  
3596.48  
3645.08  
3693.68  
55  
60  
65  
70  
75  
80  
10  
85  
20  
90  
30  
95  
40  
100  
105  
110  
115  
120  
50  
60  
70  
80  
90  
100  
110  
120  
SENSOR RESISTANCE VERSUS TEMPERATURE  
2000  
1950  
1900  
1850  
1800  
1750  
1700  
1650  
1600  
1550  
1500  
SENSOR RESISTANCE VERSUS TEMPERATURE  
3750  
3700  
3650  
3600  
3550  
3500  
3450  
3400  
3350  
3300  
3250  
3200  
3150  
3100  
3050  
3000  
2950  
2900  
30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105110 115120  
M11614  
DEGREES F  
Fig. 53. Graph of Sensor Resistance versus Temperature.  
Sensor Type:  
T7770A,B,C,D the T7560A,B and C7770A  
-40 -30 -20 -10  
0
10 20 30 40 50 60 70 80 90 100 110 120  
M11615  
Sensor Use:  
DEGREES F  
Space Temperature and Discharge/Return Air Temperature  
Fig. 52. Graph of Sensor Resistance versus Temperature.  
Table 31 lists the points for Sensor Resistance versus  
Temperature. Fig. 54 shows the graph of these points.  
Sensor Type:  
C7031B1033, C7031C1031 C7031D1062, C7031F1018  
(W7750B,C only), C7031J1050, C7031K1017  
74-29581  
110  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Table 31. Sensor Resistance Versus Temperature.  
°F Above and Below Setpoint  
Resistance Ohms  
8651.06  
8605.79  
8560.52  
8515.25  
8469.98  
8424.71  
8379.45  
8334.18  
8288.91  
8243.64  
8198.37  
8153.10  
8107.83  
8062.56  
°F  
40  
45  
50  
55  
60  
65  
70  
75  
80  
85  
90  
95  
100  
Resistance Ohms  
9961.09  
9700.90  
9440.72  
9180.53  
8920.35  
8660.16  
8399.98  
8139.79  
7879.61  
7619.42  
7359.24  
7099.06  
6838.87  
-4  
-3  
-2  
-1  
0
1
2
3
4
5
6
7
8
9
80K  
70K  
60K  
SENSOR RESISTANCE VERSUS TEMPERATURE  
8900  
8800  
8700  
8600  
8500  
8400  
8300  
50K  
40K  
30K  
20K  
20K OHM AT  
77oF (25oC)  
8200  
8100  
10K  
8000  
-9 -8 -7 -6 -5 -4 -3 -2 -1  
0
1
2
3
4
5
6
7
8
9
80  
30  
0
40  
50  
10  
TEMPERATURE (DEGREES)  
60  
70  
90  
100  
110 oF  
M11609  
DEGREES F  
oC  
20  
40  
30  
M5874A  
Fig. 55. Graph of Sensor Resistance versus Temperature.  
Fig. 54. Graph of Sensor Resistance versus Temperature.  
Sensor Type:  
T7770B,C 10 K ohm setpoint potentiometer (Absolute)  
Sensor Type:  
T7770B,C 10K ohm setpoint potentiometer (Relative)  
Sensor Use:  
Direct Setpoint Temperature  
Sensor Use:  
Offset Setpoint Temperature  
Table 33 lists the points for Sensor Resistance versus  
Temperature. Fig. 56 shows the graph of these points.  
Table 32 lists the points for Sensor Resistance versus  
Temperature. Fig. 55 shows the graph of these points.  
Table 33. Sensor Resistance Versus Temperature.  
Table 32. Sensor Resistance Versus Temperature.  
°F  
55  
60  
65  
70  
75  
80  
85  
Resistance Ohms  
8877.42  
°F Above and Below Setpoint  
Resistance Ohms  
8877.41  
8741.62  
-9  
-8  
-7  
-6  
-5  
8605.82  
8832.14  
8470.02  
8786.87  
8334.22  
8741.60  
8198.42  
8696.33  
8062.62  
111  
Download from Www.Somanuals.com. All Manuals Search And Download.  
74-29581  
         
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
SENSOR RESISTANCE VERSUS TEMPERATURE  
SENSOR VOLTAGE VERSUS HUMIDITY PERCENTAGE  
10.00  
9.50  
8900  
8800  
8700  
8600  
8500  
8400  
8300  
9.00  
8.50  
8.00  
7.50  
7.00  
6.50  
6.00  
5.50  
5.00  
4.50  
8200  
8100  
4.00  
3.50  
3.00  
2.50  
8000  
55  
60  
65  
70  
75  
80  
85  
10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90  
M11610  
M11608  
DEGREES F  
PERCENTAGE  
Fig. 56. Graph of Sensor Resistance versus Temperature.  
Fig. 57. Graph of Sensor Voltage versus Humidity.  
Sensor Type:  
Voltage/Current Sensors.  
C7600C (4 to 20 mA)  
Sensor Type:  
C7600B1000 2 to 10V (Decorative Wall Mount)  
Sensor Use:  
Humidity  
Sensor Use:  
Humidity  
Table 35 lists the points for Sensor Voltage versus Humidity.  
Fig. 58 shows the graph of these points.  
Table 34 lists the points for Sensor Voltage versus Humidity.  
Fig. 57 shows the graph of these points.  
Table 35. Sensor Voltage Versus Humidity.  
Relative Humidity Percentage  
Sensor Voltage  
Table 34. Sensor Voltage Versus Humidity.  
10  
20  
30  
40  
50  
60  
70  
80  
90  
5.6  
7.2  
Humidity Percentage  
Sensor Voltage  
2.67  
10  
15  
20  
25  
30  
35  
40  
45  
50  
55  
60  
65  
70  
75  
80  
85  
90  
8.8  
3.08  
10.4  
12.0  
13.6  
15.2  
16.8  
18.4  
3.48  
3.88  
4.28  
4.68  
5.08  
5.48  
5.88  
20  
18  
16  
14  
12  
10  
RH (%) I (mA)  
6.28  
10  
20  
30  
40  
50  
60  
70  
80  
90  
5.6  
7.2  
8.8  
10.4  
12.0  
13.6  
15.2  
16.8  
18.4  
6.69  
7.09  
7.49  
7.89  
8
8.29  
6
4
8.69  
9.09  
0
10 20 30 40 50 60 70 80 90 100  
HUMIDITY IN PERCENT RELATIVE HUMIDITY  
M3131B  
Fig. 58. C7600C output current vs. humidity.  
Sensor Type:  
T7400A1004  
Sensor Use:  
Enthalpy  
74-29581  
112  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Table 36 lists the points for Sensor Current versus Enthalpy  
(volts). Fig. 59 shows the graph of these points.  
SENSOR CURRENT VERSUS ENTHALPY (VOLTS)  
5.00  
4.75  
4.50  
Table 36. Sensor Current Versus Enthalpy (volts).  
4.25  
4.00  
Enthalpy (mA)  
Sensor Current  
1
3.75  
3.50  
3.25  
3.00  
2.75  
2.50  
4
5
1.25  
6
1.49  
7
1.74  
2.25  
2.00  
8
1.99  
1.75  
1.50  
1.25  
1.00  
9
2.24  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
2.49  
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20  
M11607  
(MA)  
2.74  
2.99  
Fig. 59. Graph of Sensor Current versus Enthalpy (volts).  
3.24  
See Fig. 60 for partial psychometric chart for a C7400A Solid  
State Enthalpy Sensor.  
3.49  
3.74  
3.98  
4.23  
4.48  
4.73  
4.98  
113  
Download from Www.Somanuals.com. All Manuals Search And Download.  
74-29581  
   
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
85  
90  
95 100 105 110  
(29) (32) (35) (38) (41) (43)  
CONTROL CONTROL POINT  
CURVE  
APPROX. °F (°C)  
80  
(27)  
AT 50% RH  
A
B
C
D
73 (23)  
70 (21)  
67 (19)  
63 (17)  
75  
(24)  
70  
(21)  
65  
(18)  
60  
(16)  
A
55  
(13)  
B
50  
(10)  
C
45  
(7)  
D
40  
(4)  
35  
(2)  
1
A
B
C
D
35  
40  
45  
50  
55  
60  
65  
70  
75  
80  
85  
90  
95 100 105 110  
(2)  
(4) (7) (10) (13) (16) (18) (21) (24) (27) (29) (32) (35) (38) (41) (43)  
APPROXIMATE DRY BULB TEMPERATURE°F (°C)  
HIGH LIMIT CURVE FOR W6210D,W7210D.  
M11160  
1
Fig. 60. Partial psychometric chart for a C7400A Solid State Enthalpy Sensor.  
C7400A OUTPUT CURRENT  
100  
See Fig. 61 for a C7400A Solid State Enthalpy Sensor output  
current vs. relative humidity.  
90  
80  
70  
60  
50  
40  
D = 17 MA  
C = 15.5 MA  
B = 13.5 MA  
A = 11 MA  
30  
20  
10  
B
70  
(21)  
A
D
C
40  
(4)  
50  
(10)  
60  
(16)  
80  
(27)  
90  
(32)  
100  
(38)  
TEMPERATURE °F (°C)  
M11605  
Fig. 61. C7400A Solid State Enthalpy Sensor output  
current vs. relative humidity.  
Sensor Type:  
T7242 or equivalent  
74-29581  
114  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Sensor Use:  
CO2 concentration  
Table 38 lists the points for Sensor Voltage versus input  
Voltage to A/D. Fig. 63 shows the graph of these points.  
Table 37 lists the points for Sensor Voltage versus CO2  
concentration. Fig. 62 shows the graph of these points.  
Table 38. Sensor Voltage Versus Input Voltage To A/D.  
Voltage to A/D  
0.00  
Sensor Voltage  
0.00  
Table 37. Sensor Voltage Versus CO2 Concentration.  
0.50  
0.25  
CO2 Concentration PPM  
Sensor Voltage  
0.00  
1.00  
0.50  
0
1.50  
0.75  
100  
0.50  
2.00  
1.00  
200  
1.00  
2.50  
1.25  
300  
1.50  
3.00  
1.50  
400  
2.00  
3.50  
1.75  
500  
2.50  
4.00  
2.00  
600  
3.00  
4.50  
2.25  
700  
3.50  
5.00  
2.50  
800  
4.00  
5.50  
2.75  
900  
4.50  
6.00  
3.00  
1000  
1100  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
5.00  
6.50  
3.25  
5.50  
7.00  
3.50  
6.00  
7.50  
3.75  
6.50  
8.00  
4.00  
7.00  
8.50  
4.25  
7.50  
9.00  
4.50  
8.00  
9.50  
4.75  
8.50  
10.00  
5.00  
9.00  
9.50  
SENSOR VOLTAGE VERSUS INPUT VOLTAGE TO A/D  
10.00  
5.00  
4.50  
4.00  
3.50  
3.00  
2.50  
SENSOR VOLTAGE VERSUS CO2 CONCENTRATION  
10  
9
8
7
6
5
2.00  
1.50  
1.00  
0.50  
0
4
3
2
1
0
600  
800  
0
100  
200  
300  
400  
500  
VOLTS  
700  
900 1000  
M11612  
Fig. 63. Graph of Sensor Voltage versus input Voltage to  
A/D.  
100  
200  
300  
400  
500  
600  
700 900 1100 1300 1500 1700 1900  
800 1000 1200 1400 1600 1800 2000  
M11611  
PPM  
Sensor Type:  
Third party  
Fig. 62. Graph of Sensor Voltage versus CO2  
concentration.  
Sensor Use:  
Sensor Type:  
Third party (2 to 10V)  
Sensor Voltage (Vdc) /Pressure (Inw) 2 to 10V, 0 to 5 inw  
(1.25 kPa)  
Sensor Use:  
Monitor voltage  
Table 39 lists the points for Sensor Voltage (Vdc) versus  
Pressure (Inw). Fig. 64 shows the graph of these points.  
115  
Download from Www.Somanuals.com. All Manuals Search And Download.  
74-29581  
       
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER  
Table 39. Sensor Voltage (Vdc) Versus Pressure (Inw).  
SENSOR VOLTAGE VERSUS PRESSURE  
Pressure Inw (kPa)  
0.00 (0.00)  
0.50.(0.13)  
1.00 (0.25)  
1.50 (0.37)  
2.00 (0.5)  
Sensor Voltage (Vdc)  
10.00  
9.00  
8.00  
7.00  
6.00  
5.00  
4.00  
3.00  
2.00  
2.00  
2.80  
3.60  
4.40  
5.20  
6.00  
6.80  
7.60  
8.40  
9.20  
10.00  
2.50 (0.62)  
3.00 (0.75)  
3.50 (0.87)  
4.00 (1.00)  
4.50 (1.12)  
5.00 (1.25)  
0
0.50  
1.00  
1.50 2.00  
2.50  
INW  
3.00  
3.50  
4.00  
4.50  
M11606  
5.00  
Fig. 64. Graph of Sensor Voltage (Vdc) versus Pressure  
(Inw).  
LON , Neuron , and LONWORKS are registered trademarks  
of Echelon Corporation. LONMARK and LONMARK logo are  
registered trademarks of the LONMARK Interoperability  
Association.  
Home and Building Control  
Honeywell Inc.  
Honeywell Plaza  
P.O. Box 524  
Minneapolis, MN 55408-0524  
Home and Building Control  
Home and Building Control Products  
Honeywell AG  
Böblinger Straße 17  
D-71101 Schönaich  
Phone (49-7031) 637-01  
Fax (49-7031) 637-493  
Honeywell Limited-Honeywell Limitée  
155 Gordon Baker Road  
North York Ontario  
M2H 3N7  
Printed in U.S.A. on recycled  
paper containing at least 10%  
post-consumer paper fibers.  
74-29581 J.D. Rev. 3-00  
www.honeywell.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   

Grizzly Sander G5394 User Manual
Harbor Freight Tools Fan 67118 User Manual
Hatteras Hammocks Indoor Furnishings Tri Beam User Manual
Hayter Mowers Lawn Mower 401R User Manual
Heat Glo LifeStyle Indoor Fireplace RED60 2159 900 User Manual
Honeywell Network Router 800 08340V1 User Manual
Hotpoint Refrigerator HTS18ICP User Manual
HP Hewlett Packard Network Card DA 10852 User Manual
Hypertec Carrying Case N12308NHY User Manual
Image Treadmill IMTL396063 User Manual