Honeywell Universal Remote UDC3200 User Manual

UDC3200  
Universal Digital Controller  
Operator Manual  
51-52-25-143  
April 2008  
Honeywell Process Solutions  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Symbol Definitions  
The following table lists those symbols used in this document to denote certain conditions.  
Symbol  
Definition  
This CAUTION symbol on the equipment refers the user to the Product Manual for  
additional information. This symbol appears next to required information in the manual.  
WARNING  
PERSONAL INJURY: Risk of electrical shock. This symbol warns the user of a  
potential shock hazard where HAZARDOUS LIVE voltages greater than 30 Vrms, 42.4  
Vpeak, or 60 VDC may be accessible. Failure to comply with these instructions  
could result in death or serious injury.  
ATTENTION, Electrostatic Discharge (ESD) hazards. Observe precautions for  
handling electrostatic sensitive devices  
Protective Earth (PE) terminal. Provided for connection of the protective earth (green  
or green/yellow) supply system conductor.  
Functional earth terminal. Used for non-safety purposes such as noise immunity  
improvement. NOTE: This connection shall be bonded to protective earth at the source  
of supply in accordance with national local electrical code requirements.  
Earth Ground. Functional earth connection. NOTE: This connection shall be bonded to  
Protective earth at the source of supply in accordance with national and local electrical  
code requirements.  
Chassis Ground. Identifies a connection to the chassis or frame of the equipment shall  
be bonded to Protective Earth at the source of supply in accordance with national and  
local electrical code requirements.  
4/08  
UDC3200 Universal Digital Controller Operator Manual  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
4/08  
UDC3200 Universal Digital Controller Operator Manual  
iv  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1 Introduction  
1.1 Operator Interface  
Figure 1-1 UDC3200 Operator Interface  
1.2 Function of Displays and Keys  
Table 1-1 Function of Displays and Keys  
Display Indicators  
Upper display with 4 large digits shows  
Indicates Control Relay 1 and/or  
2 on.  
OUT  
3200  
Process Variable value (normal operation)  
and special annunciator features. During  
Configuration, the upper display provides  
guidance for the operator through prompts (7  
– characters)  
During normal operation, the lower display  
shows key-selected operating parameters  
such as Output, Setpoints, Inputs, Deviation,  
active Tuning Parameter Set, Timer Status, or  
minutes remaining in a setpoint ramp (4  
digits). During configuration, the lower display  
provides guidance for the operator through  
prompts (8-characters).  
SP 3200  
F
Or  
Indicates either degrees  
Fahrenheit or Centigrade.  
C
Indicates Alarm 1 and/or Alarm 2 conditions  
exist.  
ALM  
DI  
MAN  
Or  
Indicates either Manual or Auto  
mode.  
A
Indicates Digital Input 1 and/or 2 on.  
Indicates Local Setpoint #1.  
Also, a bar is lighted when the  
setpoint being used is shown on  
the lower display.  
SP  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Keys and Functions  
Selects functions within each  
configuration group.  
Selects Manual or Auto mode.  
Man  
Auto  
Function  
Setup  
Scrolls through the configuration  
groups.  
Hold key down to cycle through  
configured setpoints.  
SP  
Select  
Returns Controller to normal display  
from Set Up mode. Toggles various  
operating parameters for display.  
Enables Run/Hold of the SP  
Ramp or Program plus Timer  
start.  
Lower  
Display  
Run  
Hold  
Increases setpoint or output value.  
Increases the configuration values or  
changes functions in Configuration  
mode groups.  
Decreases setpoint or output  
value. Decreases the  
configuration values or changes  
functions in Configuration mode  
groups.  
Infrared transceiver  
NEMA4X and IP66 screw  
attachment (each corner)  
1.3 CE Conformity (Europe)  
This product is in conformity with the protection requirements of the following  
European Council Directives: 73/23/EEC, the Low Voltage Directive, and  
89/336/EEC, the EMC Directive. Conformity of this product with any other “CE  
Mark” Directive(s) shall not be assumed.  
Product Classification: Class I: Permanently connected, panel-mounted Industrial  
Control Equipment with protective earthing (grounding) (EN61010-1).  
Enclosure Rating: This controller must be panel-mounted with the rear terminals  
enclosed within the panel. The front panel of the controller is rated at NEMA4X and  
IP66 when properly installed.  
Installation Category (Overvoltage Category): Category II (EN61010-1)  
Pollution Degree: Pollution Degree 2: Normally non-conductive pollution with  
occasional conductivity caused by condensation. (Ref. IEC 664-1)  
EMC Classification: Group 1, Class A, ISM Equipment (EN61326, emissions),  
Industrial Equipment (EN61326, immunity)  
Method of EMC Assessment: Technical File (TF)  
Declaration of Conformity: 51453663  
Deviation from the installation conditions specified in this manual, and the special  
conditions for CE conformity in Subsection 2, may invalidate this product’s  
conformity with the Low Voltage and EMC Directives.  
2
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ATTENTION  
The emission limits of EN61326 are designed to provide reasonable protection  
against harmful interference when this equipment is operated in an industrial  
environment. Operation of this equipment in a residential area may cause harmful  
interference. This equipment generates, uses, and can radiate radio frequency  
energy and may cause interference to radio and television reception when the  
equipment is used closer than 30 meters (98 feet) to the antenna(e). In special  
cases, when highly susceptible apparatus is used in close proximity, the user may  
have to employ additional mitigating measures to further reduce the  
electromagnetic emissions of this equipment.  
WARNING  
If this equipment is used in a manner not specified by the manufacturer, the  
protection provided by the equipment may be impaired.  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2 Installation  
2.1 Pre-installation Information  
If the controller has not been removed from its shipping carton, inspect the carton for  
damage then remove the controller.  
Inspect the unit for any obvious shipping damage and report any damage due to  
transit to the carrier.  
Make sure a bag containing mounting hardware is included in the carton with the  
controller.  
Check that the model number shown on the inside of the case agrees with what  
you have ordered.  
2.2 Model Number Interpretation  
Write your controller’s model number in the spaces provided below and circle the  
corresponding items in each table. This information will also be useful when you wire your  
controller.  
Instructions  
Select the desired key number. The arrow to the right marks the selection available.  
Make the desired selections from Tables I through VI using the column below the  
proper arrow.  
A dot ( ) denotes availability.  
Key Number  
I
II  
III  
IV  
V
VI  
_ _ _ _ _ _  
-
_ _  
-
_ _ _ _  
-
_ _ _  
-
_ _ _ _ _  
-
_ _  
_
KEY NUMBER - UDC3200 Single Loop Controller  
Description  
Digital Controller for use with 90 to 264Vac Power  
Digital Controller for use with 24Vac/dc Power  
Selection Availability  
DC3200  
DC3201  
TABLE I - Specify Control Output and/or Alarms  
C _  
E _  
A _  
T _  
R _  
_ 0  
_ B  
_ E  
_ A  
_ T  
Current Output (4 to 20ma, 0 to 20 ma)  
Electro Mechanical Relay (5 Amp Form C)  
Solid State Relay (1 Amp)  
Output #1  
Open Collector transistor output  
Dual 2 Amp Relays (Both are Form A) (Heat/Cool Applications)  
No Additional Outputs or Alarms  
One Alarm Relay Only  
Output #2 and Alarm  
#1 or Alarms 1 and 2  
E-M Relay (5 Amp Form C) Plus Alarm 1 (5 Amp Form C Relay)  
Solid State Relay (1 Amp) Plus Alarm 1 (5 Amp Form C Relay)  
Open Collector Plus Alarm 1 (5 Amp Form C Relay)  
TABLE II - Communications and Software Selections  
None  
0 _ _ _  
1 _ _ _  
2 _ _ _  
3 _ _ _  
_ 0 _ _  
_ A _ _  
_ B _ _  
_ C _ _  
_ _ 0 _  
Auxiliary Output/Digital Inputs (1 Aux and 1 DI or 2 DI)  
Communications  
RS-485 Modbus Plus Auxiliary Output/Digital Inputs  
10 Base-T Ethernet (Modbus RTU) Plus Auxiliary Output/Digital Inputs  
Standard Functions, Includes Accutune  
Math Option  
Software Selections  
Set Point Programming (1 Program, 12 Segments)  
Set Point Programming Plus Math  
Reserved  
No Selection  
Infrared interface  
Infrared Interface Included (Can be used with a Pocket PC)  
_ _ _ R  
TABLE III - Input 1 can be changed in the field using external resistors  
TC, RTD, mV, 0-5V, 1-5V  
1 _ _  
2 _ _  
3 _ _  
1 6 0  
_ 00  
_ 10  
_ 20  
_ 40  
TC, RTD, mV, 0-5V, 1-5V, 0-20mA, 4-20mA  
Input 1  
TC, RTD, mV, 0-5V, 1-5V, 0-20mA, 4-20mA, 0-10V  
Carbon, Oxygen or Dewpoint (Requires Input 2)  
None  
TC, RTD, mV, 0-5V, 1-5V, 0-20mA, 4-20mA  
Input 2  
TC, RTD, mV, 0-5V, 1-5V, 0-20mA, 4-20mA, 0-10V  
Slidewire Input (Requires two Relay Outputs)  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TABLE IV - Options  
CE (Standard)  
CE, UL and CSA  
0 _ _ _ _  
1 _ _ _ _  
_ 0 _ _ _  
_ T _ _ _  
_ S _ _ _  
_ _ 0 _ _  
_ _ _ 0 _  
_ _ _ _ 0  
Approvals  
None  
Tags  
Linen Customer ID Tag - 3 lines w/22 characters/line  
Stainless Steel Customer ID Tag - 3 lines w/22 characters/line  
None  
None  
None  
Future Options  
TABLE V - Product Manuals  
Product Information on CD - All Languages  
0 _  
E _  
F _  
G _  
I _  
English Manual  
French Manual  
Manuals  
German Manual  
Italian Manual  
Spanish Manual  
None  
Certificate of Conformance (F3391)  
S _  
_ 0  
_ C  
Certificate  
TABLE VI  
No Selection  
None  
0 _  
Figure 2-1 Model Number Interpretation  
2.3 Control and Alarm Relay Contact Information  
Control Relays  
ATTENTION  
Control relays operate in the standard control mode (that is, energized when output state is on).  
Table 2-1 Control Relay Contact Information  
Unit Power  
Control Relay  
Wiring  
N.O.  
Control Relay  
Contact  
Open  
Output #1 or #2  
Indicator Status  
Off  
On  
Off  
N.C.  
N.O.  
Closed  
Open  
Closed  
Closed  
Open  
Off  
On  
Off  
On  
N.C.  
Alarm Relays  
ATTENTION  
Alarm relays are designed to operate in a failsafe mode (that is, de-energized during alarm  
sate). This results in alarm actuation when power is OFF or when initially applied, until the unit  
completes self-diagnostics. If power is lost to the unit, the alarms will de-energize and thus the  
alarm contacts will close.  
Table 2-2 Alarm Relay Contact Information  
Unit  
Alarm Relay Variable NOT in Alarm State  
Variable in Alarm State  
Power  
Wiring  
Relay  
Contact  
Open  
Closed  
Closed  
Open  
Indicators  
Relay  
Contact  
Open  
Closed  
Open  
Indicators  
N.O.  
N.C.  
N.O.  
N.C.  
Off  
On  
Off  
Off  
Off  
On  
Closed  
6
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2.4 Mounting  
Physical Considerations  
The controller can be mounted on either a vertical or tilted panel using the mounting  
kit supplied. Adequate access space must be available at the back of the panel for  
installation and servicing activities.  
Overall dimensions and panel cutout requirements for mounting the controller are  
The controller’s mounting enclosure must be grounded according to CSA standard  
C22.2 No. 0.4 or Factory Mutual Class No. 3820 paragraph 6.1.5.  
The front panel is moisture rated NEMA3 and IP55 rated and can be easily  
upgraded to NEMA4X and IP66.  
Overall Dimensions  
Max. panel thickness  
19,1  
mm  
inches  
9,0  
.75  
0,35  
90,6  
3,57  
108,6  
4,28  
92,0 + 0,8  
- 0,00  
3,62 + 0,03  
-0,00  
Panel  
Cutout  
92,0 + 0,8  
- 0,00  
3,62 + 0,03  
-0,00  
113,1  
4,45  
17,9  
0,70  
Figure 2-2 Mounting Dimensions (not to scale)  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Mounting Method  
Before mounting the controller, refer to the nameplate on the outside of the case and  
make a note of the model number. It will help later when selecting the proper wiring  
configuration.  
Mounting clips  
Attach screws and  
washers here for  
water protection  
Figure 2-3 Mounting Methods  
Mounting Procedure  
Table 2-3 Mounting Procedure  
Step  
1
Action  
Mark and cut out the controller hole in the panel according to the dimension  
information in Figure 2-2.  
Orient the case properly and slide it through the panel hole from the front.  
2
3
Remove the mounting kit from the shipping container and install the kit as follows:  
For normal installation two mounting clips are required. Insert the prongs of  
the clips into the two holes in the top and bottom center of the case  
For water-protected installation four mounting clips are required. There are  
two options of where to install the mounting clips:  
1) Insert the prongs of the clips into the two holes on the left and right side of the  
top and bottom of the case or  
2) on the center on each of the four sides.  
Tighten screws to 2 lb-inch (22 Ncm) to secure the case against the panel.  
CAUTION: Over tightening will cause distortion and the unit may not seal properly.  
For water-protected installation, install four screws with washers into the four recessed  
areas in the corners of the front bezel (Figure 2-3). Push the point of the screw  
through the center piercing the elastomeric material and then tighten screws to 5 lb-in  
(56 Ncm).  
4
8
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2.5 Wiring  
2.5.1 Electrical Considerations  
Line voltage wiring  
This controller is considered “rack and panel mounted equipment” per EN61010-1,  
Safety Requirements for Electrical Equipment for Measurement, Control, and  
Laboratory Use, Part 1: General Requirements. Conformity with 72/23/EEC, the Low  
Voltage Directive requires the user to provide adequate protection against a shock  
hazard. The user shall install this controller in an enclosure that limits OPERATOR  
access to the rear terminals.  
Mains Power Supply  
This equipment is suitable for connection to 90 to 264 Vac or to 24 Vac/dc 50/60 Hz,  
power supply mains. It is the user’s responsibility to provide a switch and non-time  
delay (North America), quick-acting, high breaking capacity, Type F (Europe), 1/2A,  
250V fuse(s), or circuit-breaker for 90-264 Vac applications; or 1 A, 125 V fuse or  
circuit breaker for 24 Vac/dc applications, as part of the installation. The switch or  
circuit-breaker shall be located in close proximity to the controller, within easy reach  
of the OPERATOR. The switch or circuit-breaker shall be marked as the  
disconnecting device for the controller.  
CAUTION  
Applying 90-264 Vac to an instrument rated for 24 Vac/dc will  
severely damage the instrument and is a fire and smoke hazard.  
When applying power to multiple instruments, make certain that sufficient current is  
supplied. Otherwise, the instruments may not start up normally due to the voltage  
drop caused by the in-rush current.  
Controller Grounding  
PROTECTIVE BONDING (grounding) of this controller and the enclosure in which  
it is installed shall be in accordance with National and Local electrical codes. To  
minimize electrical noise and transients that may adversely affect the system,  
supplementary bonding of the controller enclosure to a local ground, using a No. 12  
(4 mm2) copper conductor, is recommended.  
Control/Alarm Circuit Wiring  
The insulation of wires connected to the Control/Alarm terminals shall be rated for  
the highest voltage involved. Extra Low Voltage (ELV) wiring (input, current output,  
and low voltage Control/Alarm circuits) shall be separated from HAZARDOUS LIVE  
(>30 Vac, 42.4 Vpeak, or 60 Vdc) wiring per Permissible Wiring Bundling, Table  
Electrical Noise Precautions  
Electrical noise is composed of unabated electrical signals which produce undesirable  
effects in measurements and control circuits.  
Digital equipment is especially sensitive to the effects of electrical noise. Your  
controller has built-in circuits to reduce the effect of electrical noise from various  
sources. If there is a need to further reduce these effects:  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Separate External Wiring—Separate connecting wires into bundles  
(See Permissible Wiring Bundling - Table 2-4) and route the individual bundles  
through separate conduit metal trays.  
Use Suppression Devices—For additional noise protection, you may want to add  
suppression devices at the external source. Appropriate suppression devices are  
commercially available.  
ATTENTION  
For additional noise information, refer to document number 51-52-05-01, How to Apply Digital  
Instrumentation in Severe Electrical Noise Environments.  
Permissible Wiring Bundling  
Table 2-4 Permissible Wiring Bundling  
Bundle No.  
1
Wire Functions  
Line power wiring  
Earth ground wiring  
Line voltage control relay output wiring  
Line voltage alarm wiring  
2
3
Analog signal wire, such as:  
Input signal wire (thermocouple, 4 to 20 mA, etc.)  
4-20 mA output signal wiring  
Digital input signals  
Low voltage alarm relay output wiring  
Low voltage wiring to solid state type control circuits  
Low voltage wiring to open collector type control circuits  
2.6 Wiring Diagrams  
Universal Output Functionality and Restrictions  
Instruments with multiple outputs can be configured to perform a variety of output  
types and alarms. For example, an instrument with a current output and two relays  
can be configured to perform any of the following:  
1) Current Simplex with two alarm relays;  
2) Current Duplex 100% with two alarm relays;  
3) Time Simplex with one alarm relay;  
4) Time Duplex with no alarm relays; or  
5) Three Position Step Control with no alarm relays.  
These selections may all be made via the keyboard and by wiring to the appropriate  
output terminals; there are no internal jumpers or switches to change. This flexibility  
allows a customer to stock a single instrument which is able to handle a variety of  
applications.  
Table 2-5 shows what control types and alarms are available based upon the installed  
outputs. In this table, when Duplex Control and Reverse Action are configured,  
“Output 1” is HEAT while “Output 2” is COOL. When Three Position Step Control  
is configured, “Output 1” is OPEN while “Output 2” is CLOSE. The Output 1/2  
option “Single Relay” can be any of the following selections: Electro-Mechanical  
Relay, Solid-State Relay or Open Collector Output.  
Table 2-5 Universal Output Functionality and Restrictions  
10  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Output Algorithm  
Type  
Output 1/2  
Option  
Function of  
Output 1/2  
Function of Other Outputs  
Output #3  
Output #4  
Alarm 1  
Alarm 1  
Alarm 1  
Alarm 1  
Output 1  
Alarm 1  
Auxiliary Output  
Time Simplex  
Single Relay  
Current Output  
Dual Relay  
Output 1  
INU  
Alarm 2  
Output 1  
Alarm 2  
Output 2  
Output 2  
Alarm 2  
Not Needed  
Not Needed  
Not Needed  
Not Needed  
Not Needed  
Not Needed  
Output 1  
Output 1  
INU  
Time Duplex or  
TPSC or Position  
Proportional  
Single Relay  
Current Output  
Dual Relay  
Outputs 1 and  
2
Current Simplex  
Single Relay  
Current Output  
Dual Relay  
INU  
Output 1  
INU  
Alarm 2  
Alarm 2  
Alarm 2  
Alarm 2  
Alarm 2  
Alarm 1  
Alarm 1  
Alarm 1  
Alarm 1  
Alarm 1  
Output 1  
Not Needed  
Output 1  
Current Dup. 100% Single Relay  
Current = COOL  
and HEAT  
INU  
Outputs 1 and 2  
Not Needed  
Current Output Outputs 1 and  
2
Dual Relay  
INU  
N/A  
Alarm 2  
N/A  
Alarm 1  
N/A  
Outputs 1 and 2  
N/A  
Current Duplex  
50%  
Current = HEAT  
Aux Out = COOL  
Single Relay  
Current Output  
Dual Relay  
Output 1  
N/A  
Alarm 2  
N/A  
Alarm 1  
N/A  
Output 2  
N/A  
Current/Time  
Current = COOL  
Time = HEAT  
Single Relay *  
Current Output  
Dual Relay *  
Output 1  
Output 2  
Output 2  
Output 2  
Alarm 2  
Output 2  
Output 2  
Alarm 2  
Alarm 1  
Alarm 1  
Alarm 1  
Alarm 1  
Alarm 1  
Alarm 1  
Output 2  
Not Needed  
Output 2  
Outputs 1 & 2  
Output 1  
Time/Current  
Time = COOL  
Current = HEAT  
Single Relay *  
Current Output  
Dual Relay *  
Output 1  
Output 1  
Not Needed  
Output 1  
Outputs 1 & 2  
TPSC = Three Position Step Control  
N/A = Not Available – This output algorithm type cannot be performed with this Output 1/2  
option.  
INU = Installed, Not Used – The installed Output 1/2 option is not used for the configured  
output algorithm type.  
Not Needed = Auxiliary Output is Not Needed to provide the desired output algorithm and  
can be used for another purpose. With the proper configuration, Auxiliary  
Output could also be used as a substitute for the Current Output.  
* To obtain this output algorithm type with these Output 1/2 Options: 1) Configure the  
OUTALG selection as “TIME D”; 2) Configure Auxiliary Output for “OUTPUT” and; 3)  
Scale the Auxiliary Output as necessary for the desired output algorithm type. For these  
selections, the Output 1 (HEAT) and Output 2 (COOL) signals will be present both on the  
Auxiliary Output and on the two relays normally used for Time Duplex.  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring the Controller  
7
19  
20  
21  
22  
10  
11  
12  
13  
14  
15  
16  
1
2
4
5
6
L1  
L2/N  
4
5
6
7
8
9
23  
24  
25  
26  
27  
3
17  
18  
8
See table for callout details  
Figure 2-4 Composite Wiring Diagram  
Callout  
Details  
1
2
3
4
5
6
7
8
AC/DC Line Voltage Terminals. See Figure 2-5.  
Output 3 Terminals. See Figure 2-8 through Figure 2-14.  
Output 4 Terminals. See Figure 2-8 through Figure 2-14.  
Outputs 1 and 2 Terminals. See Figure 2-8 through Figure 2-14.  
Input #2 Terminals. See Figure 2-7.  
Input #1 Terminals. See Figure 2-6.  
Aux. Output and Digital Inputs Terminals. See Figure 2-17.  
Communications Terminals. See Figure 2-15 and Figure 2-16.  
12  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Earth  
Ground  
1
19  
20  
21  
22  
23  
24  
25  
26  
27  
3
10  
11  
12  
13  
14  
15  
16  
17  
18  
2
Hot  
AC/DC  
Line  
Voltage  
L1  
Neutral  
L2/N  
4
5
6
7
8
9
1
PROTECTIVE BONDING (grounding) of this controller and the enclosure in which it is  
installed, shall be in accordance with National and local electrical codes. To minimize  
electrical noise and transients that may adversely affect the system, supplementary  
bonding of the controller enclosure to local ground using a No. 12 (4 mm2) copper  
conductor is recommended. Before powering the controller, see “Prelimnary Checks”  
in this section of the Product Manual.  
2
3
It is the user’s responsibility to provide a switch and non-time delay (North America),  
quick-acting, high breaking capacity, Type F (Europe), 1/2A, 250V fuse(s), or circuit-  
breaker for 90-264 Vac applications; or 1 A, 125 V fuse or circuit breaker for 24 Vac/dc  
applications, as part of the installation.  
CAUTION Applying 90-264 Vac to an instrument rated for 24 Vac/dc will severely  
damage the instrument and is a fire and smoke hazard.  
Figure 2-5 Mains Power Supply  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Input #1  
Millivolt or Volts  
except 0-10 Volts  
Thermocouple  
RTD  
Use Thermocouple  
extension wire only  
25 R  
25 R  
26 +  
25 R  
26 +  
3
mV or  
Volt  
+
+
26  
source  
27  
27  
27 –  
0-10 Volts  
+
Milliamps  
Thermocouple Differential  
Use Thermocouple  
extension wire only  
25 R  
26 +  
25 R  
26  
25 R  
1
+
100K  
0–10  
Xmitter  
1
2
Volt  
source  
+
4
2
+
1
26  
+
250 Ω  
+
Power  
100K  
3
27  
27 –  
27 –  
+
Supply  
1
2
The 250 ohm resistor for milliamp inputs or the voltage divider for 0-10 Volt inputs are supplied  
with the controller when those inputs are specified. These items must be installed prior to start  
up when the controller is wired. For 0-20 mA applications, the resistor should be located at the  
transmitter terminals if Burnout detection is desired.  
Splice and tape this junction between the two thermocouples. This junction may be located  
anywhere between the thermocouples and the instrument terminals, it does not need to be close  
to the other thermocouple junctions. Both thermocouples must be of the same type. For best  
accuracy, the two thermocouples should be matched or, preferably, made from the same batch  
of wire.  
This controller does not produce a steady current for burnout detection. For that reason, when a  
thermocouple is used in parallel with another instrument, it may be desirable to configure the  
burnout selection for this controller to “NOFS” and use the burnout current from the other  
instrument to also drive this controller.  
3
4
The millivolt values for the Thermocouple Differential Input are for a pair of J thermocouples at  
an ambient temperature mean of 450°F / 232°C.  
Figure 2-6 Input 1 Connections  
14  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Input #2  
Millivolt or Volts  
except 0-10 Volts  
Thermocouple  
RTD  
Use Thermocouple  
extension wire only  
22 R  
23 +  
22 R  
22 R  
23 +  
3
mV or  
Volt  
+
+
23  
source  
24  
24  
24 –  
0-10 Volts  
+
Milliamps  
Thermocouple Differential  
Use Thermocouple  
extension wire only  
22 R  
23 +  
22 R  
22 R  
1
+
100K  
0–10  
Xmitter  
1
2
Volt  
source  
+
+
1
23  
23 +  
24 –  
Ω
250  
Power  
2
100K 3  
24  
+
24 –  
+
Supply  
Slidewire Input  
(for Position Proportional Control or Three Position Step Control)  
4
Open  
22 R  
Wiper  
23 +  
Close  
24  
1
2
The 250 ohm resistor for milliamp inputs or the voltage divider for 0-10 Volt inputs are supplied  
with the controller when those inputs are specified. These items must be installed prior to start  
up when the controller is wired. For 0-20 mA applications, the resistor should be located at the  
transmitter terminals if Burnout detection is desired.  
Splice and tape this junction between the two thermocouples. This junction may be located  
anywhere between the thermocouples and the instrument terminals, it does not need to be close  
to the other thermocouple junctions. Both thermocouples must be of the same type. For best  
accuracy, the two thermocouples should be matched or, preferably, made from the same batch  
of wire.  
This controller does not produce a steady current for burnout detection. For that reason, when a  
thermocouple is used in parallel with another instrument, it may be desirable to configure the  
burnout selection for this controller to “NOFS” and use the burnout current from theother  
instrument to also drive this controller.  
3
4
Input 2 is used to measure the Slidewire Input for Position Proportional Control.  
xxxx  
Figure 2-7 Input 2 Connections  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Time Simplex  
19  
20  
N.C.  
N.O.  
Output  
Relay#1  
Load  
Supply  
Power  
Relay Load  
L1  
L2/N  
4
To terminal  
19 or 21  
21  
22  
23  
24  
25  
26  
27  
2
N.C.  
Load  
Supply  
Power  
Alarm  
Relay#2  
Relay Load  
5
N.O.  
To terminal  
4 or 6  
6
2
2
7
N.C.  
N.O.  
Load  
Supply  
Power  
Alarm  
Relay#1  
Relay Load  
8
To terminal  
7 or 9  
9
Time Duplex  
19  
N.C.  
Load  
Output  
Relay#1  
Relay Load  
20  
Supply  
L1  
L2/N  
4
N.O.  
To terminal  
19 or 21  
Power  
21  
22  
23  
24  
25  
26  
27  
2
N.C.  
Output  
Relay#2  
Load  
Supply  
Power  
Relay Load  
5
N.O.  
1
To terminal  
4 or 6  
6
2
2
7
N.C.  
N.O.  
Alarm  
Load  
Supply  
Power  
Relay Load  
Relay#1  
8
To terminal  
7 or 9  
9
1
2
Alarm #2 is not available with Time Proportional Duplex or Three Position Step Control unless the Dual Relay Option is used.  
Electromechanical relays are rated at 5 Amps @ 120 Vac or 240 Vac or 30 Vdc.  
Customer should size fuses accordingly. Use Fast Blo fuses only.  
Figure 2-8 Electromechanical Relay Output  
See Table 2-5 for relay terminal connections for other Output Algorithm Types.  
16  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Time Simplex  
1
Dummy Resistor  
Relay Load  
2
19  
20  
21  
22  
23  
24  
25  
26  
27  
Output  
Relay#1  
Load  
Supply  
Power  
L1  
L2/N  
4
N.O.  
N.C. Alarm  
Relay#2  
N.O.  
Load  
Supply  
Power  
Relay Load  
5
To terminal  
4 or 6  
6
3
3
7
N.C. Alarm  
Load  
Supply  
Power  
Relay#1  
Relay Load  
8
N.O.  
To terminal  
7 or 9  
9
Time Duplex  
1
Dummy Resistor  
Relay Load  
2
19  
20  
21  
22  
23  
24  
25  
26  
27  
Output  
Relay#1  
Load  
L1  
L2/N  
4
N.O.  
Supply  
Power  
1
Dummy Resistor  
Output  
Relay#2  
N.O.  
Load  
Supply  
Relay Load  
5
Power  
6
2
3
7
N.C. Alarm  
Relay#1  
Load  
Supply  
Power  
Relay Load  
8
N.O.  
To terminal  
7 or 9  
9
If the load current is less than the minimum rated value of 20 mA, then there may be residual voltage across both  
ends of the load even if the relay is turned off. Use a dummy resistor as shown to counteract this. The total  
current through the resistor and the the load must exceed 20 mA. Solid State Relays are zero-crossing type.  
1
Solid State relays are rated at 1 Amp at 25°C and derated linearly to 0.5 Amp at 55°C. Customer should size  
fuse accordingly. Use Fast Blo fuses only.  
2
3
Electromechanical relays are rated at 5 Amps @ 120 Vac or 240 Vac or 30 Vdc.  
Customer should size fuses accordingly. Use Fast Blo fuses only.  
Figure 2-9 Solid State Relay Output  
See Table 2-5 for relay terminal connections for other Output Algorithm Types.  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Time Simplex  
Customer Supplied  
Electromechanical relay  
19  
20  
21  
22  
23  
24  
25  
26  
27  
+
+
L1  
+
Output #1  
L2/N  
1
4
5
6
7
8
9
N.C. Alarm  
Relay#2  
N.O.  
Customer Supplied  
Solid-State relay  
Load  
Supply  
Power  
Relay Load  
To terminal  
4 or 6  
3
3
N.C. Alarm  
Load  
Supply  
Power  
Relay#1  
Relay Load  
N.O.  
To terminal  
7 or 9  
Time Duplex  
Customer Supplied  
Electromechanical relay  
19  
20  
21  
22  
23  
24  
25  
26  
27  
+
+
+
L1  
Output #1  
1
Customer Supplied  
Electromechanical relay  
L2/N  
Customer Supplied  
Solid-State relay  
4
5
6
7
8
9
+
+
+
Output #2  
1
2
Customer Supplied  
Solid-State relay  
N.C. Alarm  
Relay#1  
N.O.  
Load  
Supply  
Power  
Relay Load  
To terminal  
7 or 9  
3
Open collector outputs are internally powered at +30 Vdc. Connecting an external  
power supply will damage the controller.  
1
CAUTION  
2
3
Alarm #2 is not available with Time Proportional Duplex or Three Position Step Control unless the Dual Relay option is used.  
Electromechanical relays are rated at 5 Amps @ 120 Vac or 240 Vac or 30 Vdc.  
Customer should size fuses accordingly. Use Fast Blo fuses only.  
Figure 2-10 Open Collector Output  
See Table 2-5 for relay terminal connections for other Output Algorithm Types.  
18  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Time Duplex with a Dual Relay Board  
Cool Relay Load  
19  
Out Relay#2  
Out Relay#1  
Load  
N.O.  
20  
21  
22  
23  
24  
25  
26  
27  
L1  
Supply  
Power  
N.O.  
Heat Relay Load  
L2/N  
1
4
5
6
7
8
9
N.C.  
N.O.  
Alarm  
Relay#2  
Load  
Supply  
Power  
Relay Load  
To terminal  
4 or 6  
2
2
N.C.  
N.O.  
Alarm  
Relay#1  
Load  
Supply  
Power  
Relay Load  
To terminal  
7 or 9  
Dual Electromechanical relays are rated at 2 Amps @120 Vac or 240 Vac or 30 Vdc. Customer should size  
fuses accordingly. Use Fast Blo fuses only.  
1
Electromechanical relays are rated at 5 Amps @120 Vac or 240 Vac or 30 Vdc.  
Customer should size fuses accordingly. Use Fast Blo fuses only.  
2
Figure 2-11 Dual Electromechanical Relay Option Output  
See Table 2-5 for relay terminal connections for other Output Algorithm Types.  
+
19  
Current Output  
4–20 mA  
Controller Load  
0-1000 ohms  
20  
21  
22  
23  
24  
25  
26  
27  
L1  
L2/N  
4
5
6
7
8
9
N.C.  
N.O.  
Alarm  
Relay#2  
Load  
Supply  
Power  
Relay Load  
To terminal  
4 or 6  
2
N.C. Alarm  
Relay#1  
N.O.  
Load  
Supply  
Power  
Relay Load  
1
To terminal  
7 or 9  
2
1
2
When the instrument has the Current Output as shown, no Alarms are available when using the Time Proportional Duplex or  
Three Position Step Control Output Algorithms, as these outputs require both available relays.  
Electromechanical relays are rated at 5 Amps @120 Vac or 240 Vac or 30 Vdc  
Customer should size fuses accordingly. Use Fast Blo fuses only.  
Figure 2-12 Current Output  
See Table 2-5 for relay terminal connections for other Output Algorithm Types.  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 2-13 Position Proportional or Three Position Step Control  
Connection, Models DC3200-EE or DC3200-AA  
Figure 2-14 Position Proportional or Three Position Step Control  
Connections, Model DC3200-R_  
20  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
COMMUNICATION MASTER  
D+ (B) SHLD D– (A)  
1
2
16 SHLD  
SHLD  
D+  
17 D+ (B)  
18 D– (A)  
D–  
120 OHMS  
Connect shield  
to ground at one  
end only.  
TO OTHER  
COMMUNICATION  
CONTROLLERS  
D–  
D+  
120 OHMS ON LAST LEG  
Do not run the communications lines in the same conduit as AC power.  
Use shielded twisted pair cables (Belden 9271 Twinax or equivalent).  
1
2
Figure 2-15 RS-422/485 Communications Option Connections  
COMMUNICATION MASTER  
3
OR SWITCH  
SHLD TXDTXD+ RXD
RXD  
+
1
14SHLD
15 RXD +  
2
16 RXD  
17TXD+
18TXD
Do not run the communications lines in the same conduit as AC  
power. Correct connections may require the use of an Ethernet  
cross-over cable.  
1
Use Shielded twisted-pair, Category 5 (STP CAT5) Ethernet cable.  
Use Switch rather than Hub to maximize performance.  
2
3
Figure 2-16 Ethernet Communications Option Connections  
Switch utilizing a straight-through cable or for connecting a UDC to a PC utilizing a  
crossover cable.  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Table 2-6 Terminals for connecting a UDC to a MDI Compliant Hub or Switch  
UDC Terminal UDC Signal Name  
RJ45 Socket Pin #  
Switch Signal  
Name  
Position 14  
Position 15  
Position 16  
Position 17  
Position 18  
Shield  
RXD-  
RXD+  
TXD-  
TXD+  
Shield  
Shield  
TXD-  
TXD+  
RXD-  
RXD+  
6
3
2
1
Table 2-7 shows how to connect a UDC directly to a PC utilizing a straight-through  
cable (wiring the UDC cable this way makes the necessary cross-over connections)  
Table 2-7 Terminals for connecting a UDC directly to a PC utilizing a straight-  
through cable  
UDC Terminal UDC Signal Name  
RJ45 Socket Pin #  
PC Signal Name  
Shield  
Position 14  
Position 15  
Position 16  
Position 17  
Position 18  
Shield  
RXD-  
RXD+  
TXD-  
TXD+  
Shield  
2
1
6
3
TXD-  
TXD+  
RXD-  
RXD+  
1
1
Auxiliary Output  
Digital Inputs  
+
+
_
Auxiliary  
Load  
0 - 1000 Ω  
Digital  
Input #1  
10  
11  
12  
13  
_
+
_
12  
13  
Digital  
Input #2  
Connect shield  
to ground at one  
end only.  
Connect shield  
to ground at one  
end only.  
Auxiliary Output and Digital Input 2 are mutually exclusive.  
1
Figure 2-17 Auxiliary Output and Digital Inputs Option Connections  
22  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2 Wire Transmitter  
Configure:  
A2S1TY = NONE  
A2S2TY = NONE  
1
_
+
5 +  
6 -  
26 +  
27 -  
250 Ω  
OUTPUT 3  
INPUT 1  
If necessary, install a zener diode here to reduce voltage at the  
transmitter. A 1N4733 will reduce the voltage at the transmitter to  
approximately 25 Vdc.  
1
Figure 2-18 Transmitter Power for 4-20 mA — 2 wire Transmitter Using Open  
Collector Alarm 2 Output  
2 Wire Transmitter  
Configure:  
AUXOUT = OUT  
Auxiliary Output Calibration  
ZEROVAL = 16383  
1
_
+
SPANVAL = 16383  
12 +  
13 -  
26 +  
27 -  
250 Ω  
AUXILIARY OUTPUT  
INPUT 1  
If necessary, install a zener diode here to reduce voltage at the  
transmitter. A 1N4733 will reduce the voltage at the transmitter to  
approximately 25 Vdc.  
1
Figure 2-19 Transmitter Power for 4-20 mA — 2 Wire Transmitter  
Using Auxiliary Output  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3 Configuration  
3.1 Configuration Prompt Hierarchy  
Set Up  
Group  
Function Prompts  
TUNING  
PROP BD or  
GAIN  
GAINVALn  
RATE MIN  
SECURITY  
RSET MIN or  
RSET RPM  
MAN RSET  
AUTO MAN  
PROPBD2 or  
GAIN 2  
RATE2MIN  
RUN HOLD  
RSET2MIN  
or  
RSET2RPM  
CYC SEC or  
CYC SX3  
CYC2 SEC or  
CYC2 SX3  
LOCKOUT  
SP SEL  
SPRAMP  
SP RAMP  
SP PROG  
KEYRESET  
TIME MIN  
STRT SEG  
HOTSTART  
FINAL SP  
END SEG  
SP RATE  
RAMPUNIT  
SEGx SP*  
EU/HR UP  
EU/HR DN  
SOAK DEV  
EUHRUP2  
EUHRDN2  
STATE  
RECYCLES  
PROG END  
* x = 1 to 12. Program concludes after segment 12  
SEGxRAMP  
or  
SEGxRATE  
ACCUTUNE  
ALGORTHM  
FUZZY  
ACCUTUNE  
DUPLEX  
AT ERROR  
CONT ALG  
CALC LO  
TIMER  
PERIOD  
START  
LOW DISP  
PCT CO  
INP ALG1  
PCT H2  
MATH K  
CALC HI  
ALG1 INA  
ALG1 INB  
ALG1 INC  
ALG1BIAS  
OUT ALG  
INPUT1  
OUT ALG  
RLYSTATE  
XMITTER1  
RLY TYPE  
IN1 HIGH  
CUR OUT  
IN1 LOW  
LOW VAL  
RATIO 1  
HIGH VAL  
BIAS IN1  
CO RANGE  
FILTER 1  
MOTOR TI  
IN1 TYPE  
EMISSIV1  
BURNOUT1  
INPUT2  
IN2 TYPE  
EMISSIV2  
XMITTER2  
IN2 HIGH  
IN2 LOW  
RATIO 2  
BIAS IN2  
FILTER 2  
BURNOUT2  
CONTRL  
PV SOURC  
PWR OUT  
OUTLoLIM  
MAN OUT  
PID SETS  
SP HiLIM  
I Hi LIM  
SW VALUE  
SP LoLIM  
I Lo LIM  
LSP'S  
RSP SRC  
OUT RATE  
DEADBAND  
AUTOBIAS  
PCT/M UP  
OUT HYST  
SP TRACK  
PCT/M DN  
FAILSAFE  
PWR MODE  
OUTHiLIM  
FAILMODE  
ACTION  
DROPOFF  
MINorRPM  
AUTO OUT  
PBorGAIN  
OPTIONS  
COM  
AUX OUT  
LOW VAL  
HIGH VAL  
CORANGE  
DIG1 INP  
DIG1 COM  
DIG2 INP  
SHEDENAB  
DIG2 COM  
SHEDTIME  
Com ADDR  
SHEDMODE  
ComSTATE  
SHEDSP  
IR ENABLE  
UNITS  
BAUD  
TX DELAY  
CSP BIAS  
WSFLOAT  
CSP RATO  
LOOPBACK  
ALARMS  
A1S1TYPE  
A2S1TYPE  
AL HYST  
A1S1 VAL  
A2S1 VAL  
ALM OUT1  
A1S1 H L  
A2S1 H L  
BLOCK  
A1S1 EV  
A2S1 EV  
A1S2 TYPE  
A2S2TYPE  
A1S2 VAL  
A2S2 VAL  
A1S2 H L  
A2S2 H L  
A1S2 EV  
A2S2 EV  
DIAGNOST  
DISPLAY  
CALIB  
DECIMAL  
TEMPUNIT  
PWR FREQ  
RATIO 2  
LANGUAGE  
USED FOR FIELD CALIBRATION  
24  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3.2 Configuration Procedure  
Introduction  
Each of the Set Up groups and their functions are pre-configured at the factory. If you  
want to change any of these selections or values, follow the procedure in Table 3-1.  
This procedure tells you the keys to press to get to any Set Up group and any  
associated Function parameter prompt.  
Procedure  
ATTENTION  
The prompting scrolls at a rate of 2/3 seconds when the SET UP or FUNCTION key is held in.  
Also,  
or  
keys will move group prompts forward or backward at a rate twice as fast.  
Table 3-1 Configuration Procedure  
Step  
1
Operation  
Press  
Result  
Upper Display = SETUP  
Enter Set Up  
Mode  
Setup  
Lower Display = TUNING (This is the first Set Up Group title)  
Sequentially displays the other Set Up group titles. You can also  
Select any Set  
Up Group  
2
3
Setup  
use the  
or  
keys to scan the Set Up groups in both  
directions. Stop at the Set Up group title that describes the group of  
parameters you want to configure. Then proceed to the next step.  
Upper Display = the current value or selection for the first function  
Select a Function  
Parameter  
Function  
prompt of the selected Set Up group.  
Lower Display = the first Function prompt within that Set Up group.  
Sequentially displays the other function prompts of the Set Up  
group you have selected. Stop at the function prompt that you want  
to change, then proceed to the next step.  
Increments or decrements the value or selection that appears for  
the selected function prompt. If you change the value or selection  
of a parameter while in Set Up mode but then decide not to enter it,  
press the MAN/AUTO key once. This will recall the original  
configuration. This “recall” procedure does not work for a Field  
Calibration process. Field Calibration is a one-way operation.  
Change the  
Value or  
Selection  
4
or  
Enters value or selection made into memory after another key is  
pressed.  
Enter the Value  
or Selection  
5
6
Function  
Exits configuration mode and returns controller to the same state it  
was in immediately preceding entry into the Set Up mode. It stores  
any changes you have made.  
Exit Configuration  
Lower  
Display  
If you do not press any keys for 30 seconds, the controller times out  
and reverts to the mode and associated display used prior to entry  
into Set Up mode.  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3.3 Tuning Set Up Group  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
0.1 to 9999 %  
or  
0.001 to 1000  
PROP BD  
or  
PROPORTIONAL BAND (simplex) is the percent of the range of  
the measured variable for which a proportional controller will  
produce a 100 % change in its output.  
GAIN  
GAIN is the ratio of output change (%) over the measured variable  
change (%) that caused it.  
G = 100 / %PB where PB is the proportional band(in %)  
If the PB is 20 %, then the Gain is 5. And, at those settings, a 3 %  
change in the error signal (SP-PV) will result in a 15 % change in  
the controller's output due to proportional action. If the Gain is 2,  
then the PB is 50 %.  
Also defined as "HEAT" Gain on Duplex models for variations of  
Heat/Cool applications.  
The selection of Proportional Band or Gain is made in the  
CONTROL parameter group under prompt PBorGAIN.  
0.00 to 10.00  
minutes  
RATE MIN  
RATE action, in minutes, affects the controller's output whenever  
the deviation is changing; and affects it more when the deviation is  
changing faster.  
0.02 to 50.00  
RSET MIN  
or  
RSET MIN = Reset in Minutes per Repeat  
RSET RPM = Reset in Repeats per Minute  
RSET RPM  
RESET (or Integral Time) adjusts the controller's output in  
accordance with both the size of the deviation (SP–PV) and the  
time that it lasts. The amount of the corrective action depends on  
the value of Gain. The Reset adjustment is measured as how many  
times proportional action is repeated per minute or how many  
minutes before one repeat of the proportional action occurs.  
Used with control algorithm PID-A or PID-B.  
Also defined as "HEAT" Reset on Duplex models for variations of  
Heat/Cool applications.  
ATTENTION The selection of whether Minutes per Repeat or  
Repeats per Minute is used is made in the CONTROL parameters  
group under the prompt MINorRPM.  
–100 to +100  
(in % output)  
MAN RSET  
MANUAL RESET is only applicable if you use control algorithm PD  
WITH MANUAL RESET in the Algorithm Set Up group. Because a  
proportional controller will not necessarily line out at setpoint, there  
will be a deviation (offset) from setpoint. This eliminates the offset  
and lets the PV line out at setpoint.  
ATTENTION Bias is shown on the lower display.  
0.1 to 9999 %  
or  
0.001 to 1000  
PROPBD2  
or  
GAIN 2  
PROPORTIONAL BAND 2 or GAIN 2, RATE 2, and RESET 2  
parameters are the same as previously described for “Heat” except  
that they refer to the cool zone tuning constants on duplex models  
or the second set of PID constants, whichever is pertinent.  
0.00 to 10.00  
minutes  
This is the same as above except that it applies to Duplex models  
for the "COOL" zone of Heat/Cool applications or for the second  
set of PID constants.  
RATE2MIN  
26  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
0.02 to 50.00  
These are the same as above except that they apply to Duplex  
models for the "COOL" zone of Heat/Cool applications or for the  
second set of PID constants.  
RSET2MIN  
RSET2RPM  
1 to 120  
CYC SEC  
or  
CYC SX3  
CYCLE TIME (HEAT) determines the length of one time  
proportional output relay cycle. Defined as "HEAT" cycle time for  
Heat/Cool applications.  
CYC SEC—Electromechanical relays  
CYC SX3—Solid state relays  
ATTENTION Cycle times are in either second or 1/3-second  
increments depending upon the configuration of RLY TYPE in the  
Output Algorithm Set Up group.  
1 to 120  
CYC2 SEC  
or  
CYC2 SX3  
CYCLE TIME 2 (COOL) is the same as above except it applies to  
Duplex models as the cycle time in the "COOL" zone of Heat/Cool  
applications or for the second set of PID constants.  
CYC2 SEC—Electromechanical relays  
CYC2 SX3—Solid state relays  
ATTENTION Cycle times are in either second or 1/3-second  
increments depending upon the configuration of RLY TYPE in the  
Output Algorithm Set Up group.  
0 to 9999  
SECURITY  
SECURITY CODE—The level of keyboard lockout may be  
changed in the Set Up mode. Knowledge of a security code may  
be required to change from one level to another. This configuration  
should be copied and kept in a secure location.  
NOTE: The Security Code is for keyboard entry only and is not  
available via communications.  
ATTENTION Can only be changed if LOCKOUT selection is  
NONE.  
LOCKOUT  
LOCKOUT applies to one of the functional groups: Configuration,  
Calibration, Tuning, Accutune. DO NOT CONFIGURE UNTIL ALL  
CONFIGURATION IS COMPLETE.  
NONE  
CALIB  
NONE—No lockout; all groups are read/write.  
CALIB—All groups are available for read/write except for the  
Calibration and Keyboard Lockout groups.  
+ CONF  
+ CONF—Tuning, SP Ramp, and Accutune groups are read/write.  
All other groups are read only. Calibration and Keyboard Lockout  
groups are not available.  
+ VIEW  
MAX  
+ VIEW—Tuning and Setpoint Ramp parameters are read/write.  
No other parameters are viewable.  
MAX—Tuning and Setpoint Ramp parameters are available for  
read only. No other parameters are viewable.  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
AUTO MAN  
MANUAL/AUTO KEY LOCKOUT—Allows you to disable the  
Manual/Auto key  
DISABLE  
ENABLE  
DISABLE  
ENABLE  
ATTENTION Can only be viewed if LOCKOUT is configured for  
NONE.  
RUN HOLD  
RUN/HOLD KEY LOCKOUT—Allows you to disable the Run/Hold  
key, for either SP Ramp or SP Program. The Run/Hold key is  
never disabled when used to acknowledge a latched alarm 1  
DISABLE  
ENABLE  
DISABLE  
ENABLE  
ATTENTION Can only be viewed if LOCKOUT is configured for  
NONE.  
SP SEL  
SETPOINT SELECT KEY LOCKOUT—Allows you to disable the  
Setpoint Select key  
DISABLE  
ENABLE  
DISABLE  
ENABLE  
ATTENTION Can only be viewed if LOCKOUT is configured for  
NONE.  
28  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.4 SP Ramp Set Up Group  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
SP RAMP  
SINGLE SETPOINT RAMP—Make a selection to enable or disable  
the setpoint ramp function. Make sure you configure a ramp time  
and a final setpoint value.  
SP Program  
must be  
disabled for SP  
Ramp prompts  
to appear  
SP Programming must be disabled.  
DISABLE  
ENABLE  
DISABLE SETPOINT RAMP—Disables the setpoint ramp option.  
ENABLE SETPOINT RAMP—Allows the single setpoint ramp  
prompts to be shown.  
0 to 255 minutes  
TIME MIN  
FINAL SP  
SETPOINT RAMP TIME—Enter the number of minutes desired to  
reach the final setpoint. A ramp time of “0” implies an immediate  
change of setpoint.  
Within setpoint  
limits  
SETPOINT RAMP FINAL SETPOINT—Enter the value desired for  
the final setpoint. The controller will operate at the setpoint set here  
when ramp is ended.  
ATTENTION If the ramp is on HOLD, the held setpoint can be  
changed by the and keys. However, the ramp time remaining  
and original ramp rate is not changed. Therefore, when returning to  
RUN mode, the setpoint will ramp at the same rate as previous to  
the local setpoint change and will stop if the final setpoint is  
reached before the time expires. If the time expires before the final  
setpoint is reached, it will jump to the final setpoint.  
ATTENTION SP RAMP and SP RATE will cause the SP portion  
of Accutune to abort. PV Tune will continue to function normally.  
Ramp is placed into HOLD while tuning (TUNE configuration).  
DISABLE  
ENABLE  
HOTSTART  
SP RATE  
DISABLE—LSP1 is used as the initial ramp setpoint.  
ENABLE—Current PV value is used as the initial ramp setpoint.  
SETPOINT RATE—Lets you configure a specific rate of change for  
any local setpoint change.  
DISABLE  
ENABLE  
DISABLE SETPOINT RATE—Disables the setpoint rate option.  
ENABLE SETPOINT RATE—Allows the SP rate feature.  
SP Rate operates only when both SP Ramp and SP Programing  
are in HOLD mode or when both SP Ramp and SP Programming  
are disabled.  
0 to 9999 in  
engineering units  
per hour  
EU/HR UP  
RATE UP—Rate up value. When making a setpoint change, this is  
the rate at which the controller will change from the original  
setpoint up to the new one. The ramping (current) setpoint can be  
viewed as SPn in the lower display.  
Entering a 0 will imply an immediate step change in Setpoint (i.e.,  
no rate applies).  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
0 to 9999 in  
engineering units  
per hour  
EU/HR DN  
RATE DOWN—Rate down value. When making a setpoint change,  
this is the rate at which the controller will change from the original  
setpoint down to the new one. The ramping (current) setpoint can  
be viewed as SPn in the lower display.  
Entering a 0 will imply an immediate step change in Setpoint (i.e.,  
no rate applies).  
SP PROG  
(optional  
feature)  
SETPOINT RAMP/SOAK PROGRAM—Available only with  
controllers that contain this option.  
SP RAMP must be disabled.  
DISABLE  
ENABLE  
DISABLE—Disables setpoint programming.  
ENABLE—Enables setpoint programming.  
SP Ramp must be disabled for SP Program prompts to appear. If  
SP Rate is enabled, it does not operate while an SP Program is  
running  
1 to 11  
Start Segment Number  
STRT SEG  
END SEG  
2 to 12 even  
numbers  
End Segment Number, always end in a soak segment (2, 4, ... 12)  
RAMPUNIT  
RAMPUNIT—Engineering Units for Ramp Segments  
TIME in hours: minutes  
TIME  
RATE in Enineering units per minute  
RATE in Enineering units per hour  
EU/MIN  
EU/HR  
0 to 99 recycles  
0 to 99  
Number of Program Recycles  
RECYCLES  
SOAK DEV  
Guaranteed Soak Deviation Value  
The number selected will be the PV value (in engineering units)  
above or below the setpoint outside of which the timer halts.  
Program Termination State  
PROG END  
LASTSP  
F SAFE  
Hold at last setpoint in the program  
Manual mode/Failsafe output  
DISABLE  
HOLD  
Program State at Program End  
STATE  
DISABLE  
ToBEGIN  
RERUN  
Reset/Rerun SP Program  
KEYRESET  
DISABLE  
ENABLE  
Hot Start  
HOTSTART  
0-99 hours.0-59  
minutes  
Segment #1 Ramp Time or  
Segment #1 Ramp Rate  
SEG1RAMP or  
SEG1RATE  
Engineering  
units/minute or  
Engineering  
units/hour  
Select TIME, EU/MIN, or EU/HR at prompt RAMPUNIT. All  
ramps will use the same selection.  
Within the Setpoint Segment #2 Soak Setpoint Value  
limits  
SEG2 SP  
30  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
0-99 hours.0-59  
minutes  
Segment #2 Soak Duration  
SEG2TIME  
Selections are  
Same as above  
SEG3RAMP or  
same as above.  
SEG3RATE  
SEG4 SP  
SEG4TIME  
SEG5RAMP or  
SEG5RATE  
SEG6 SP  
SEG6TIME  
SEG7RAMP or  
SEG7RATE  
SEG8 SP  
SEG8TIME  
SEG9RAMP or  
SEG9RATE  
SG10 SP  
SG10TIME  
SG11RAMP or  
SG11RATE  
SG12 SP  
SG12TIME  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.5 Accutune Set Up Group  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
FUZZY  
ACCUTUNE  
DUPLEX  
FUZZY OVERSHOOT SUPPRESSION—Can be enabled or  
disabled independently of whether Demand Tuning or SP Tuning is  
enabled or disabled.  
DISABLE  
ENABLE  
DISABLE—Disables Fuzzy Overshoot Suppression.  
ENABLE—The instrument uses Fuzzy Logic to suppress or  
minimize any overshoot that may occur when PV approaches SP. It  
will not recalculate any new tuning parameters.  
ACCUTUNE III  
DISABLE  
TUNE  
DISABLE —Disables the Accutune function.  
DEMAND TUNING—If TUNE is selected, and tuning is initiated  
through the operator interface or digital input (if configured), the  
algorithm calculates new tuning parameters and enters them into  
the tuning group. This tuning requires no process knowledge and  
does not require line out for initialization.  
DUPLEX ACCUTUNING III – These prompts only appear when a  
duplex output type has been configured.  
This prompt  
only appears  
when a Duplex  
Control  
Algorithm has  
been  
MANUAL  
AUTO  
MANUAL – Tune manually using LSP 1 and LSP 2 values. LSP 1  
is used to derive tuning parameters associated with HEAT (output  
> 50 %). LSP 2 is used to derive tuning parameters associated  
with COOL (output < 50 %).  
configured  
AUTOMATIC – Tuning is performed automatically on both HEAT  
and COOL sequentially. LSP 1 is used for HEAT tuning and LSP 2  
is used for COOL tuning. To initiate tuning, either LSP 1 or LSP 2  
must be in use.  
DISABLE  
DISABLE – The current SetPoint is used to derive a single set of  
blended tuning parameters. This tuning is performed over the  
range of the output limits similar to Simplex Tuning. The Tuning  
Parameters derived are placed into both the HEAT and COOL tune  
sets (PID 1 and PID 2).  
AT ERROR  
ACCUTUNE ERROR STATUS—When an error is detected in the  
(Read Only)  
Accutune process, an error prompt will appear.  
NONE  
NONE—No errors occurred during last Accutune procedure.  
RUNNING  
RUNNING—An Accutune process is still active checking process  
gain, even though “T” is not lit. It does not affect keyboard  
operation.  
ABORT  
SP2  
CURRENT ACCUTUNE PROCESS ABORTED—Caused by one  
of the following conditions: changing to manual mode, digital input  
detected, in heat region of output but a cool output was calculated,  
or vice versa.  
SP2—LSP2 not configured or a Setpoint other than LSP1 or LSP2  
is in use.  
32  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3.6 Algorithm Set Up Group  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
CONT ALG  
The CONTROL ALGORITHM lets you select the type of control  
that is best for your process.  
ON-OFF  
ON/OFF is the simplest control type. The output can be either ON  
(100 %) or OFF (0 %). The Process Variable (PV) is compared with  
the setpoint (SP) to determine the sign of the error (ERROR = PV–  
SP). The ON/OFF algorithm operates on the sign of the error  
signal.  
In Direct Acting Control, when the error signal is positive, the  
output is 100 %; and when the error signal is negative, the output is  
0 %. If the control action is reverse, the opposite is true. An  
adjustable overlap (Hysteresis Band) is provided between the on  
and off states.  
ATTENTION Other prompts affected: OUT HYST  
DUPLEX ON/OFF is an extension of this algorithm when the output  
is configured for a Duplex control algorithm. It allows the operation  
of a second ON/OFF output. There is a deadband between the  
operating ranges of the two inputs and an adjustable overlap  
(hysteresis) of the on and off states of each output. Both Deadband  
and Hysteresis are separately adjustable. With no relay action the  
controller will read 50 %.  
ATTENTION Other prompts affected: OUT HYST and  
DEADBAND  
PID A  
PID A is normally used for three-mode control. This means that the  
output can be adjusted somewhere between 100 % and 0 %. It  
applies all three control actions—Proportional (P), Integral (I), and  
Derivative (D)—to the error signal.  
ATTENTION  
PID A should not  
be used for  
Proportional (Gain)—Regulates the controller’s output in  
proportion to the error signal (the difference between Process  
Variable and Setpoint).  
Proportional only  
action; i.e., no  
integral (reset)  
action. Instead,  
use PD+MR with  
rate set to 0.  
Integral (Reset)—Regulates the controller’s output to the size of  
the error and the time the error has existed. (The amount of  
corrective action depends on the value of proportional Gain.)  
Derivative (Rate)—Regulates the controller’s output in proportion  
to the rate of change of the error. (The amount of corrective action  
depends on the value of proportional Gain.)  
PID B  
PID B—Unlike the PID A equation, the controller gives only an  
integral response to a setpoint change, with no effect on the output  
due to the gain or rate action, and it gives full response to PV  
changes. Otherwise controller action is as described for the PID A  
equation. See note on PID A.  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
PD+MR  
CONT ALG  
(continued)  
PD WITH MANUAL RESET is used whenever integral action is not  
wanted for automatic control. The equation is computed with no  
integral contribution. The MANUAL RESET, which is operator  
adjustable, is then added to the present output to form the  
controller output.  
Switching between manual and automatic mode will be bumpless.  
If you select PD with Manual Reset you can also configure the  
following variations:  
• PD (Two Mode) control,  
• P (Single Mode) control.  
Set Rate (D) to 0.  
ATTENTION Other prompts affected: MAN RSET in the Tuning  
Set Up group  
3PSTEP  
THREE POSITION STEP—The Three Position Step Control  
algorithm allows the control of a valve (or other actuator) with an  
electric motor driven by two controller relay outputs; one to move  
the motor upscale, the other downscale without a feedback  
slidewire linked to the motor shaft. The deadband is adjustable in  
the same manner as the duplex output algorithm.  
The Three Position Step Control algorithm provides an output  
display (OUT) which is an estimated motor position, since the  
motor is not using any slidewire feedback. Although this output  
indication is only an approximation, it is “corrected” each time the  
controller drives the motor to one of its stops (0 % or 100 %). It  
avoids all the control problems associated with the feedback  
slidewire (wear, dirt, noise). When operating in this algorithm, the  
estimated OUT display is shown to the nearest percent (i.e., no  
decimal). This selection forces the Output Algorithm selection to  
“POSITON”.  
Refer to the Operation section for motor position displays.  
As a customer configurable option, when a second input board is  
installed, the motor slidewire can be connected to the controller.  
The actual slidewire position is then shown on the lower display as  
POS. This value is used for display only. It is NOT used in the  
Three Position Step algorithm. To configure this option, set Input  
2 actuation to SLIDEW and then calibrate Input 2.  
ATTENTION Other prompts affected: DEADBAND  
TIMER allows you to enable or disable the timer option.  
DISABLE  
ENABLE  
TIMER  
The timer option allows you to configure a timeout period and to  
select timer start by either the keyboard (RUN/HOLD key) or Alarm  
2. A digital input can also be configured to start the timer.  
When the timer is enabled, it has exclusive control of the alarm 1  
relay; any previous alarm configuration is ignored. At timeout, the  
timer is ready to be re-activated by whatever action has been  
configured. Alarm 1 is activated at the end of the timeout period.  
34  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
0:00 to 99:59  
PERIOD  
START  
PERIOD allows you to configure the length of timeout period (from  
0 to 99 hours: 59 minutes).  
KEY  
START allows you to select whether the timer starts with the  
ALARM 2  
keyboard (Run/Hold key) or Alarm 2.  
TI REM  
E TIME  
LOW DISP  
LOW DISP allows you to select whether time remaining (TI REM)  
or elapsed time (E TIME) is displayed for the timer option.  
The time is shown on the lower display in HH:MM format along with  
a rotating “clock” character.  
• If the “clock” rotation is clockwise, elapsed time is indicated.  
• If the “clock” rotation is counterclockwise, time remaining is  
indicated.  
INPUT MATH ALGORITHMS—Controllers with two inputs are provided with one input algorithm. Unless  
otherwise noted, these selections are provided only as part of the Math Options package. Each algorithm  
can be configured to provide a derived (calculated) PV or a derived Remote Setpoint. Up to three inputs  
may be applied to the calculation. See Inputs A, B, and C for definitions per equation.  
All algorithms operate in engineering units except Feedforward (F FWRD) which operates in percent of  
output units.  
ATTENTION When the Input C configuration is set to NONE, the value of Input C used in the functions  
is automatically set to 1.0, except for the Summer algorithm, where it is set to 0.0.  
INP ALG1  
INPUT ALGORITHM 1 has the following selections from which to  
choose:  
NONE  
NONE—No algorithm configured  
W AVG  
(See Note 2)  
WEIGHTED AVERAGE—When you configure for Weighted  
Average, the controller will compute a PV or SP for the control  
algorithm from the following equation:  
(Standard feature  
on controllers with  
two analog inputs)  
Alg1 = [(InpA x Ratio A + Bias A) + (K x InpB x Ratio B + Bias B)] / (1 + K)] + Alg1Bias  
F FWRD  
FEEDFORWARD SUMMER—Feedforward uses Input A, following  
a Ratio and Bias calculation as a value summed directly with the  
PID computed output value and sent, as an output value, to the  
final control element.  
(Standard feature  
on controllers with  
two analog inputs)  
This algorithm will only function in automatic mode and is not used  
for Three Position Step Control applications.  
The following formula applies:  
Controller Output = PID Output + (Input A x Ratio A + Bias A ) x (100 / Input A Range)  
FFWDMu  
FEEDFORWARD MULTIPLIER—Feedforward uses Input A,  
following a Ratio and Bias calculation as a value multiplied directly  
with the PID computed output value and sent, as an output value,  
to the final control element.  
(Standard feature  
on controllers with  
two analog inputs)  
This algorithm will only function in automatic mode and cannot be  
used for Three Position Step Control applications.  
The following formula applies:  
Controller Output = PID Output x (Input A x Ratio A + Bias A ) / Input A Range  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
SUMMER  
SUMMER WITH RATIO AND BIAS—The following formula  
(See Note 2)  
applies:  
Alg1=(InpAxRatioA+BiasA)+(InpBxRatioB+BiasB)+(InpCxRatioC+BiasC)+Alg1Bias  
HI SEL  
(See Note 2)  
INPUT HIGH SELECT WITH RATIO AND BIAS—This selection  
specifies the PV or SP as the higher of Input 1 or Input 2. The  
following formula applies:  
Alg1 = higher of (Input A x Ratio A + Bias A) or (Input B x Ratio B + Bias B)  
LO SEL  
(See Note 2)  
INPUT LOW SELECT WITH RATIO AND BIAS—This selection  
specifies the PV or SP as the lower of Input 1 or Input 2. The  
following formula applies:  
Alg1 = lower of (Input A x Ratio A + Bias A) or (Input B x Ratio B + Bias B)  
MULTIPLIER DIVIDER WITH SQUARE ROOT—The following  
formula applies:  
MuDIV  
(See Note 1)  
Alg1=K*SqRt{(InpAxRatioA+BiasA)x(InpCxRatioC+BiasC)/(InpB*RatioB+BiasB)}  
x (CalcHi-CalcLo)+Alg1Bias  
MULTIPLIER WITH SQUARE ROOT—The following formula  
applies:  
MULT  
(See Note 1)  
Alg1 =K x Sq.Rt.{(InputA x Ratio A + Bias A) x (InputB x Ratio B + Bias B) x (InputC x Ratio C + Bias C)}  
x (Calc Hi – Calc Lo) + Alg1Bias  
MuDIV  
MULTIPLIER DIVIDER—The following formula applies:  
(See Note 1)  
Alg1 = K x [{(Input A x Ratio A + Bias A) x (Input C x Ratio C + Bias C)} / (Input B x Ratio B + Bias B)]  
x (Calc Hi – Calc Lo) + Alg1Bias  
MULT  
MULTIPLIER—The following formula applies:  
(See Note 1)  
Alg1 = K x [(Input A x Ratio A + Bias A) x (Input C x Ratio C + Bias C) x (Input B x Ratio B + Bias B)]  
x (Calc Hi – Calc Lo) + Alg1Bias  
CARB A  
CARBON POTENTIAL A—Make this selection if you have a  
Cambridge or Marathon monitor type Zirconium Oxide sensor. See  
Note 3.  
CARB B  
CARBON POTENTIAL B—Make this selection if you have a  
Corning type Zirconium Oxide sensor. This algorithm requires a  
temperature range within the region of 1380 to 2000°F. See Note  
3.  
CARB C  
CARB D  
CARBON POTENTIAL C—Make this selection if you have an  
A.A.C.C. type Zirconium Oxide sensor. This algorithm requires a  
temperature range within the region of 1380 °F to 2000 °F. See  
Note 3.  
CARBON POTENTIAL D—Make this selection if you have a  
Barber Coleman, MacDhui, or Bricesco type Zirconium Oxide  
sensor. This algorithm requires a temperature range within the  
region of 1380 to 2000°F. See Note 3.  
36  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
FCC  
CARBON POTENTIAL FCC—Make this selection if you have a  
Furnace Controls Corp Accucarb type Zirconium Oxide sensor.  
This algorithm requires a temperature range within the region of  
1380 °F to 2000 °F. See Note 3.  
DEW PT  
DEWPOINT OF CARBONIZING ATMOSPHERE—Use this  
selection if you are using any Zirconium Oxide Carbon Probe and  
you want to measure the atmosphere in terms of Dewpoint. The  
range is –50 °F to 100 °F or –48 °C to 38 °C. This algorithm  
requires a temperature range within the region of 1000 °F to 2200  
°F and a minimum carbon probe value of 800 millivolts.  
OXYGEN  
PERCENT OXYGEN RANGE—Make this selection if you are using  
a Zirconium Oxide Oxygen Probe to measure Percent of Oxygen in  
a range of 0 to 40 % O2. This algorithm requires a temperature  
range within the region of 800 °F to 3000 °F.  
ATTENTION The Carbon and Dewpoint selections will automatically set the first input actuation to  
Carbon. The Oxygen selection will automatically set the first input actuation to Oxygen. Input 2 can be  
any input actuation, but it is normally a type K, R or S thermocouple input, depending upon the probe type  
selected. All calculations are performed by the Controller with Percent Carbon shown as the PV display.  
The actual value of each analog input may be viewed on the lower display. For all Carbon Types, if the  
value of Percent Carbon falls below 0.1% - such as can happen when the Carbon Probe voltage output  
falls below 900 mVdc – then the Controller will continue to update the PV display, but the accuracy is  
unspecified. Likewise, if the measured temperature falls outside of the specified ranges as noted above  
for the Carbon, Oxygen and Dewpoint input types, then the Controller will continue to update the PV  
display, but the accuracy is unspecified. For the Dewpoint algorithm, if the Carbon Sensor voltage falls  
below 800 mVdc, then the Dew Point is calculated as if the sensor voltage was at 800 mVdc.  
0.001 to 1000  
floating  
MATH K  
CALC HI  
CALC LO  
ALG1 INA  
WEIGHTED AVERAGE RATIO OR MASS FLOW ORIFICE  
CONSTANT (K) FOR MATH SELECTIONS—Only applicable for  
algorithms W AVG or General Math selections MuDIV, MULT,  
MuDIV, or MULT.  
–999. To 9999.  
Floating  
(in engineering  
units)  
CALCULATED VARIABLE HIGH SCALING FACTOR FOR  
INPUT ALGORITHM 1—Used only when either Summer, Input  
Hi/Lo, or one of the General Math functions was selected as the  
Input Algorithm. See Note 2.  
–999. To 9999.  
Floating  
(in engineering  
units)  
CALCULATED VARIABLE LOW SCALING FACTOR FOR INPUT  
ALGORITHM 1—Used only when either Summer, Input Hi/Lo, or  
one of the General Math functions was selected as the Input  
Algorithm. See Note 2.  
ALGORITHM 1, INPUT A SELECTION will represent one of the  
available selections.  
INPUT 1  
INPUT 2  
OUTPUT  
Input 1  
Input 2  
Output – Should not be used for Three Position Step Control  
applications)  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
ALG1 INB  
ALGORITHM 1, INPUT B SELECTION will represent one of the  
available selections.  
INPUT 1  
INPUT 2  
OUTPUT  
Input 1  
Input 2  
Output – Should not be used for Three Position Step Control  
applications)  
ALG1 INC  
ALGORITHM 1, INPUT C SELECTION will represent one of the  
available selections.  
NONE  
None  
INPUT 1  
INPUT 2  
OUTPUT  
Input 1  
Input 2  
Output – Should not be used for Three Position Step Control  
applications)  
0.020 to 0.350  
(fractional percent  
of CO)  
PCT CO  
PERCENT CARBON is only applicable when Carbon Potential is  
selected. Enter the value in percent carbon monoxide that is  
applicable for the enriching gas used in fractional form.  
FOR EXAMPLE:  
Natural Gas = 20.0 % CO, then setting is 0.200  
Propane Gas = 23.0 % CO, setting is 0.230  
-999 to 9999  
floating (in  
engineering units)  
ALG1 BIAS  
PCT H2  
INPUT ALGORITHM 1 BIAS—Does not apply to selections:  
FFWRD, FFWDMU, HISEL or LOSEL.  
1.0 to 99.0 (% H )  
2
HYDROGEN CONTENT FOR DEWPOINT is only applicable when  
Dewpoint is selected. Enter a value for the percentage of Hydrogen  
content that is applicable.  
Math Algorithm Notes:  
1. Calculation ranges for the Math Algorithms are set via CALC HI and CALC LO parameters and  
are between –999. and 9999. The SP High and Low values (SP Range) are independent of  
these settings and can be any value between –999. and 9999.  
2. The CALC HI and CALC LO values determine the range limits for the SP High and Low values  
for the Weighted Average, Summer, Hi Select and Low Select algorithms.  
3. If the Ratio for Input 2 is set to 0.0, then a constant value may be used for the Input 2 value via  
the Input 2 Bias setting. For this configuration, the Input 2 low range and the Sooting diagnostic  
messages are disabled.  
38  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.7 Output Set Up Group  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
OUT ALG  
The OUTPUT ALGORITHM lets you select the type of output you  
want. Not applicable with Control algorithm prompt 3PSTEP.  
Selections are hardware dependent.  
ATTENTION For all Duplex Output forms, PID heat parameters  
apply for controller output greater than 50 %; PID cool parameters  
apply for controller output less than 50 %.  
TIME  
TIME SIMPLEX—This output algorithm uses Digital Output 1 for  
Time Proportional Control. The output is updated per the Loop  
sampling rate selection. Time Proportional Output has a resolution  
of 4.44 msec. Cycle Time is adjustable from 1 to 120 seconds.  
CURRENT  
POSITON  
CURRENT SIMPLEX—Type of output using one 4 mA to 20 mA  
signal that can be fed into a positive or negative grounded load of 0  
to 1000 ohms. This signal can easily be configured for 4-20 mA or  
0-20 mA operation via the CO RANGE configuration, below.  
POSITION PROPORTIONAL—Type of output using two relays  
and a motor that has a 100 to 1000 ohms feedback slidewire.  
This output algorithm selection forces Input 2 to the SLIDEW  
selection when the Control Algorithm is any selection other than  
3PSTEP.  
ATTENTION Other prompts affected: DEADBAND, IN2 TYPE  
TIME D  
CUR D  
TIME DUPLEX—This output algorithm uses Digital Outputs 1 and  
2 for Duplex Time Proportional Control. The outputs are updated  
per the Loop sampling rate selection. Time Proportional Output has  
a resolution of 4.44 msec. Cycle Time is adjustable from 1 second  
to 120 seconds.  
CURRENT DUPLEX is similar to current simplex but uses a  
second current output. The second output is usually scaled so that  
zero and span correspond with 0 % and 50 % output (cool zone).  
When the output is 0 % to 50 %, the controller uses tuning  
parameter set #2, when the output is 50 % to 100 % it uses set #1.  
ATTENTION Other prompts affected: OUT RNG  
CUR TI  
TI CUR  
CURRENT/TIME DUPLEX is a variation of duplex with current  
active for 0 % to 50 % output (tuning set 2) and time is active 50 %  
to 100 % output (tuning set 1).  
Relay controls heat, current controls cool.  
ATTENTION Other prompts affected: OUT RNG  
TIME CURRENT DUPLEX is similar to CUR TI except that current  
is active for 50 % to 100 % and time is active for 0 % to 50 %.  
Relay controls cool, current controls heat.  
ATTENTION Other prompts affected: OUT RNG  
OUT RNG  
CURRENT DUPLEX RANGE ALGORITHM — Used with Output  
Algorithm selections CUR D, CUR TI, or TI CUR.  
50 PCT  
CURRENT DUPLEX RANGE (SPLIT)—This setting should be  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
used for Relay/Current and Current/Relay Duplex Outputs. It can  
also be used for Current Duplex when an Auxiliary Output board is  
present. This enables the normal control current output to provide  
heat control and the auxiliary current output to provide cool control.  
To enable this:  
• AUX OUT in the Options Set Up group must be selected for  
Output.  
• The Auxiliary Current Output is scaled as desired for 0-50 %  
controller output.  
• Deadband for this configuration only applies to the Current  
Output. The Auxiliary Output must have the Deadband scaled in.  
FOR EXAMPLE:  
If a 2 % Deadband is desired, then enter 2.0 for the Deadband  
selection in the Control Algorithm group. This will apply Deadband  
to the Current Output. In the Options group, set the Auxiliary  
Output LOW VAL selection to 49.0 and the HIGH VAL selection to  
0.0.  
100PCT  
CURRENT DUPLEX RANGE (FULL) enables the Current Output  
to provide both heat and cool functions for control over 0-100 % of  
the controller output. The PID heat parameters apply when the  
output is greater than 50 % and the PID cool parameters apply  
when the output is less than 50 %. The second current output is  
not required for this type of duplex operation.  
RLYSTATE  
DIGITAL OUTPUT STATUS AT 0 % OUTPUT allows the following  
selections:  
1OF 2OF  
1ON 2OF  
1OF 2ON  
1ON 2ON  
1OF 2OF  
1ON 2OF  
1OF 2ON  
1ON 2ON  
Output 1 de-energized  
Output 2 de-energized  
Output 1 energized  
Output 2 de-energized  
Output 1 de-energized  
Output 2 energized  
Output 1 energized  
Output 2 energized  
RLY TYPE  
RELAY CYCLE TIME INCREMENT selection is used only for Time  
Simplex and Duplex output configurations. This configuration sets  
the increment size of the relay cycle times in the Tuning and  
Tuning 2 Set Up groups.  
MECHAN  
SOL ST  
ELECTROMECHANICAL RELAY—Cycle time in one-second  
increments.  
SOLID STATE RELAY—Cycle time in 1/3 second increments. This  
is useful for solid state relay applications that require shorter cycle  
times. DO NOT use this setting unless cycle times of less than 1  
second are required.  
ATTENTION The Lockout selection must be set to NONE in order  
to view this selection.  
40  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
5 to 1800 seconds  
MOTOR TI  
MOTOR TIME – Appears only when “POSITON” is selected as the  
Output algorithm. This is the time it takes the motor to travel from 0  
to 100% (fully closed to fully open). This time can usually be found  
on the nameplate of the motor.  
CUR OUT  
CURRENT OUTPUT – If Current Output #1 is not used to perform  
one of the above output algorithms, it may be used to perform an  
Auxiliary Output function.  
DISABLE  
INPUT 1  
INPUT 2  
PV (Process Variable)  
DEVIATION  
OUTPUT  
DISABLE  
INPUT 1  
INPUT 2  
PV  
DEV  
SETPOINT  
LOCAL SETPOINT  
REMOTE  
OUTPUT  
SP  
LSP  
INPUT ALGORITHM 1  
RSP  
IN ALG 1  
Low Scale Value  
within the range of  
the selected  
LOW VAL  
HIGH VAL  
CO RANGE  
CURRENT OUTPUT LOW SCALING FACTOR—Used only when  
CUR OUT is any selection other than DISABLE. This is a value in  
engineering units used to represent all CUR OUT parameters  
except Output.  
variable to  
represent the  
minimun output (0  
or 4 mA)  
For Output, this is a value in percent and can be any value  
between –5 % and +105 %. However, keep in mind that relay  
output types can only be scaled 0 % to 100 %.  
High Scale Value  
within the range of  
the selected  
CURRENT OUTPUT HIGH SCALING FACTOR—Used only when  
CUR OUT is any selection other than DISABLE. This is a value in  
engineering units used to represent all CUR OUT parameters  
except Output.  
variable to  
represent the  
maximum output  
(20 mA)  
For Output, this is a value in percent and can be any value  
between –5 % and +105 %. However, keep in mind that relay  
output types can only be scaled 0 % to 100 %.  
4-20mA  
0-20mA  
CURRENT OUTPUT RANGE allows the user to easily select 4-20  
mA output or 0-20 mA output operation without the need for  
recalibration of the instrument.  
ATTENTION Changing the Current Output Range will result in  
the loss of Field Calibration values and will restore Factory  
Calibration values.  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.8 Input 1 Set Up Group  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
IN1 TYPE  
INPUT 1 ACTUATION TYPE – This selection determines what  
actuation you are going to use for Input 1.  
ATTENTION  
Changing the  
input type will  
result in the  
loss of Field  
Calibration  
values and will  
restore Factory  
Calibration  
DISABLE  
B TC  
DISABLE—Disables Input.  
B TC—B Thermocouple  
E TC H  
E TC L  
J TC H  
J TC M  
J TC L  
K TC H  
K TC M  
K TC L  
NNM H  
NNM L  
NIC H  
E TC H—E Thermocouple High  
E TC L—E Thermocouple Low  
J TC H—J Thermocouple High  
J TC M—J Thermocouple Med  
J TC L—J Thermocouple Low  
K TC H—K Thermocouple High  
K TC M—K Thermocouple Med  
K TC L—K Thermocouple Low  
NNM H—Ni-Ni-Moly Thermocouple High  
NNM L—Ni-Ni-Moly Thermocouple Low  
NIC H—Nicrosil-Nisil Thermocouple High  
NIC L—Nicrosil-Nisil Thermocouple Low  
R TC—R Thermocouple  
values.  
NIC L  
R TC  
S TC  
S TC—S Thermocouple  
T TC H  
T TC L  
W TC H  
W TC L  
100 PT  
100 LO  
200 PT  
500 PT  
RAD RH  
RAD RI  
0-20mA  
4-20mA  
0-10mV  
0-50mV  
0-100mV  
0-5 V  
T TC H—T Thermocouple High  
T TC L—T Thermocouple Low  
W TC H—W5W26 Thermocouple High  
W TC L—W5W26 Thermocouple Low  
100 PT—100 Ohm RTD High  
100 LO—100 Ohm RTD Low  
200 PT—200 Ohm RTD  
500 PT—500 Ohm RTD  
RAD RH—Radiamatic RH  
RAD RI—Radiamatic RI  
0-20mA—0 to 20 Milliamperes  
4-20mA—4 to 20 Milliamperes  
0-10mV—0 to 10 Millivolts  
0-50mV—0 to 50 Millivolts  
0-100mV—0 to 100 Millivolts  
0-5 V—0 to 5 Volts  
1-5 V  
1-5 V—1 to 5 Volts  
0-10 V  
TC DIFF  
CARBON  
OXYGEN  
0-10 V—0 to 10 Volts  
TC DIFF—Thermocouple Differential  
Carbon—Carbon Probe Input  
Oxygen—Oxygen Probe Input  
42  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
B TC  
XMITTER  
TRANSMITTER CHARACTERIZATION—This selection lets you  
instruct the controller to characterize a linear input to represent a  
non-linear one. If characterization is performed by the transmitter  
itself, then select LINEAR.  
E TC H  
E TC L  
J TC H  
J TC M  
J TC L  
K TC H  
K TC M  
K TC L  
NNM H  
NNM L  
NIC H  
ATTENTION Prompt only appears when a linear actuation is  
selected at prompt IN1 TYPE.  
FOR EXAMPLE:  
If input 1 is a 4 to 20 mA signal, but the signal represents a type K  
H thermocouple, then configure K TC H and the controller will  
characterize the 4 to 20 mA signal so that it is treated as a type K  
thermocouple input (high range).  
NIC L  
R TC  
Parameter definitions are the same as in IN1 TYPE.  
S TC  
T TC H  
T TC L  
W TC H  
W TC L  
100 PT  
100 LO  
200 PT  
500 PT  
RAD RH  
RAD RI  
LINEAR  
SQROOT  
–999. To 9999.  
Floating  
(in engineering  
units)  
IN1 HIGH  
INPUT 1 HIGH RANGE VALUE in engineering units is displayed  
for all inputs but can only be configured for linear or square root  
transmitter characterization.  
Scale the #1 input signal to the display value you want for 100 %.  
ATTENTION The control setpoint will be limited by the range of  
units selected here.  
–999. To 9999.  
Floating  
(in engineering  
units)  
IN1 LOW  
INPUT 1 LOW RANGE VALUE in engineering units is displayed  
for all inputs but can only be configured for linear or square root  
transmitter characterization. Scale the #1 input signal to the display  
value you want for 0 %. See example above.  
ATTENTION The control setpoint will be limited by the range of  
units selected here.  
–20.00 to 20.00  
Floats to 3 decimal  
places  
RATIO 1  
BIAS IN1  
FILTER 1  
RATIO ON INPUT 1—Select the Ratio value you want on Input 1.  
–999. to 9999.  
(in engineering  
units)  
BIAS ON INPUT 1 — Bias is used to compensate the input for drift  
of an input value due to deterioration of a sensor, or some other  
cause. Select the bias value you want on Input 1.  
0 to 120 seconds  
No filter = 0  
FILTER FOR INPUT 1—A software digital filter is provided for Input  
1 to smooth the input signal. You can configure the first order lag  
time constant from 1 to 120 seconds. If you do not want filtering,  
enter 0.  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
BURNOUT  
BURNOUT PROTECTION (SENSOR BREAK) provides most input  
types with upscale or downscale protection if the input fails.  
NONE  
UP  
NO BURNOUT—Pre-configured Failsafe output (selected in the  
CONTROL Set up Group) applied if failed input is detected (does  
not apply for an input out of range). Diagnostic message IN1 FAIL  
is intermittently flashed on the lower display.  
UPSCALE BURNOUT will force the Input 1 signal to the full scale  
value when the sensor fails. Diagnostic message IN1 FAIL  
intermittently flashed on the lower display.  
The controller remains in Automatic control mode and adjusts the  
controller output signal in response to the full scale Input 1 signal  
developed by the Burnout circuitry.  
DOWN  
NO FS  
DOWNSCALE BURNOUT will force the Input 1 signal to the lower  
range value when the sensor fails. Diagnostic message IN1 FAIL  
intermittently flashed on the lower display.  
The controller remains in Automatic control mode and adjusts the  
controller output signal in response to the lower range Input 1  
signal developed by the Burnout circuitry.  
NO FAILSAFE— This selection does not provide input failure  
detection and should only be used when a thermocouple input is  
connected to another instrument which supplies the Burnout  
current. (For this selection, no burnout signal is sent to the sensor.)  
ATTENTION For Burnout to function properly on a 0-20 mA input  
type (or a 0-5V type that uses a dropping resistor), the dropping  
resistor must be remotely located (across the transmitter  
terminals). Otherwise, the input at the instrument terminals will  
always be 0 mA (i.e., within the normal operating range) when the  
0-20 mA line is opened.  
0.01 to 1.00  
EMISSIV1  
EMISSIVITY is a correction factor applied to the Radiamatic input  
signal that is the ratio of the actual energy emitted from the target  
to the energy which would be emitted if the target were a perfect  
radiator.  
Available only for Radiamatic inputs.  
44  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.9 Input 2 Set Up Group  
Function Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter  
Definition  
IN2 TYPE  
INPUT 2 ACTUATION TYPE – This selection  
determines what actuation you are going to use for  
Input 2.  
ATTENTION  
Changing the input  
type will result in the  
loss of Field  
DISABLE—Disables Input.  
B TC—B Thermocouple  
DISABLE  
B TC  
E TC H—E Thermocouple High  
E TC L—E Thermocouple Low  
J TC H—J Thermocouple High  
J TC M—J Thermocouple Med  
J TC L—J Thermocouple Low  
K TC H—K Thermocouple High  
K TC M—K Thermocouple Med  
K TC L—K Thermocouple Low  
NNM H—Ni-Ni-Moly Thermocouple High  
NNM L—Ni-Ni-Moly Thermocouple Low  
NIC H—Nicrosil-Nisil Thermocouple High  
NIC L—Nicrosil-Nisil Thermocouple Low  
R TC—R Thermocouple  
Calibration values and E TC H  
E TC L  
J TC H  
J TC M  
J TC L  
K TC H  
K TC M  
K TC L  
NNM H  
NNM L  
NIC H  
will restore Factory  
Calibration values.  
Selecting Position  
Proportional Control in  
the Output Setup  
Group forces Input 2  
to the Slidewire  
Selection.  
NIC L  
R TC  
S TC  
S TC—S Thermocouple  
T TC H—T Thermocouple High  
T TC L—T Thermocouple Low  
W TC H—W5W26 Thermocouple High  
W TC L—W5W26 Thermocouple Low  
100 PT—100 Ohm RTD High  
100 LO—100 Ohm RTD Low  
200 PT—200 Ohm RTD  
500 PT—500 Ohm RTD  
RAD RH—Radiamatic RH  
RAD RI—Radiamatic RI  
0-20mA—0 to 20 Milliamperes  
4-20mA—4 to 20 Milliamperes  
0-10mV—0 to 10 Millivolts  
0-50mV—0 to 50 Millivolts  
0-100mV—0 to 100 Millivolts  
0-5 V—0 to 5 Volts  
1-5 V—1 to 5 Volts  
0-10 V—0 to 10 Volts  
TC DIFF—Thermocouple Differential  
SLIDEW—Slidewire (For Position Proportional  
Applications)  
T TC H  
T TC L  
W TC H  
W TC L  
100 PT  
100 LO  
200 PT  
500 PT  
RAD RH  
RAD RI  
0-20mA  
4-20mA  
0-10mV  
0-50mV  
0-100mV  
0-5 V  
1-5 V  
0-10 V  
TC DIFF  
SLIDEW  
B TC  
S TC  
XMITTER2  
TRANSMITTER CHARACTERIZATION—This  
selection lets you instruct the controller to  
characterize a linear input to represent a non-linear  
one.  
E TC H  
E TC L  
J TC H  
J TC M  
J TC L  
K TC H  
K TC M  
K TC L  
NNM H  
NNM L  
NIC H  
NIC L  
T TC H  
T TC L  
W TC H  
W TC L  
100 PT  
100 LO  
200 PT  
500 PT  
RAD RH  
RAD RI  
LINEAR  
SQROOT  
ATTENTION Prompt only appears when a linear  
actuation is selected at prompt IN2 TYPE.  
Parameter definitions are the same as in IN2 TYPE.  
R TC  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Function Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter  
Definition  
–999. To 9999. Floating  
(in engineering units)  
IN2 HIGH  
INPUT 2 HIGH RANGE VALUE in engineering units  
is displayed for all inputs but can only be configured  
for linear or square root transmitter characterization  
See the example in IN1 HI.  
–999. To 9999. Floating  
(in engineering units)  
IN2 LOW  
INPUT 2 LOW RANGE VALUE in engineering units  
is displayed for all inputs but can only be configured  
for linear or square root transmitter characterization.  
See the example in IN1 HI  
–20.00 to 20.00  
Floats to 3 decimal places  
RATIO 2  
BIAS IN2  
RATIO ON INPUT 2—Select the Ratio value you  
want on Input 1.  
–999. to 9999.  
(in engineering units)  
BIAS ON INPUT 2 — Bias is used to compensate  
the input for drift of an input value due to  
deterioration of a sensor, or some other cause.  
Select the bias value you want on Input 1.  
0 to 120 seconds  
No filter = 0  
FILTER 2  
FILTER FOR INPUT 2—A software digital filter is  
provided for Input 1 to smooth the input signal. You  
can configure the first order lag time constant from 1  
to 120 seconds. If you do not want filtering, enter 0.  
BURNOUT  
BURNOUT PROTECTION (SENSOR BREAK)  
provides most input types with upscale or downscale  
protection if the input fails.  
NONE  
NO BURNOUT—If Input 2 is being used in the  
Control Algorithm (such as the PV or RSP input  
parameter), then the pre-configured Failsafe output  
(selected in the CONTROL Set up Group) is applied  
when a failed input is detected (does not apply for an  
input out of range). Diagnostic message IN2 FAIL is  
intermittently flashed on the lower display.  
UP  
UPSCALE BURNOUT will force the Input 2 signal to  
the full scale value when the sensor fails. Diagnostic  
message IN2 FAIL intermittently flashed on the lower  
display.  
The controller remains in Automatic control mode  
and adjusts the controller output signal in response  
to the full scale Input 2 signal developed by the  
Burnout circuitry.  
DOWN  
DOWNSCALE BURNOUT will force the Input 2  
signal to the lower range value when the sensor  
fails. Diagnostic message IN2 FAIL intermittently  
flashed on the lower display.  
The controller remains in Automatic control mode  
and adjusts the controller output signal in response  
to the lower range Input 2 signal developed by the  
Burnout circuitry.  
46  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Function Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter  
Definition  
NO FS  
NO FAILSAFE—This selection does not provide  
input failure detection and should only be used when  
a thermocouple input is connected to another  
instrument which supplies the Burnout current. (For  
this selection, no burnout signal is sent to the  
sensor.)  
ATTENTION For Burnout to function properly on a  
0-20 mA input type (or a 0-5V type that uses a  
dropping resistor), the dropping resistor must be  
remotely located (across the transmitter terminals).  
Otherwise, the input at the instrument terminals will  
always be 0 mA (i.e., within the normal operating  
range) when the 0-20 mA line is opened.  
0.01 to 1.00  
EMISSIV2  
EMISSIVITY is a correction factor applied to the  
Radiamatic input signal that is the ratio of the actual  
energy emitted from the target to the energy which  
would be emitted if the target were a perfect radiator.  
Available only for Radiamatic inputs.  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.10 Control Set Up Group  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
PV SOURCE  
PROCESS VARIABLE SOURCE —Selects the source of the  
Process Variable.  
INPUT 1  
INPUT 2  
IN ALG1  
INPUT 1  
INPUT 2  
INPUT ALGORITHM 1  
PID SETS  
NUMBER OF TUNING PARAMETER SETS—This selection lets  
you choose one or two sets of tuning constants (gain, rate, and  
reset). NOTE: The Tuning Group is automatically configured to  
have two PID sets when a Duplex Control Algorithm is configured.  
1 ONLY  
ONE SET ONLY—Only one set of tuning parameters is available.  
Configure the values for: Gain (proportional band), Rate, Reset  
Time, and Cycle Time (if time proportional is used).  
2KEYBD  
TWO SETS KEYBOARD SELECTABLE—Two sets of tuning  
parameters can be configured and can be selected at the operator  
interface or by using the Digital Inputs.  
Press this key until you see PID SET1 or PID SET2 then press  
Lower  
or  
to switch between sets. Configure the values for: Gain,  
Display  
Rate, Reset, Cycle Time, Gain #2, Rate #2, Reset #2, Cycle #2  
Time  
2PV SW  
PID SETS  
(continued)  
TWO SETS PV AUTOMATIC SWITCHOVER—When the process  
variable is GREATER than the value set at prompt SW VALUE  
(Switchover Value), the controller will use Gain, Rate, Reset, and  
Cycle Time. The active PID SET can be read in the lower display.  
When the process variable is LESS than the value set at prompt  
SW VALUE, the controller will use Gain#2, Rate#2, Reset#2, and  
Cycle#2 Time. The active PID SET can be read in the lower  
display.  
2SP SW  
TWO SETS SP AUTOMATIC SWITCHOVER—When the setpoint  
is GREATER than the value set at prompt SW VALUE (Switchover  
Value), the controller will use Gain, Rate, Reset, and Cycle. When  
the setpoint is LESS than the value set at prompt SW VALUE, the  
controller will use Gain #2, Rate #2, Reset #2, and Cycle #2.  
ATTENTION Other prompts affected: SW VALUE  
Value in  
SW VALUE  
LSP’S  
AUTOMATIC SWITCHOVER VALUE—This is the value of  
Process Variable or Setpoint at which the controller will switch from  
Tuning Constant Set #2 to Set #1.  
engineering units  
within PV or SP  
range limits  
LOCAL SETPOINT SOURCE—This selection determines what  
your local setpoint source will be.  
1 ONLY  
TWO  
LOCAL SETPOINT—The setpoint entered from the keyboard.  
TWO LOCAL SETPOINTS—This selection lets you switch  
SP  
Select  
between two local setpoints using the  
key.  
THREE  
THREE LOCAL SETPOINTS—This selection lets you switch  
SP  
Select  
between three local setpoints using the  
key  
48  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
RSP SRC  
REMOTE SETPOINT SOURCE—This selection determines what  
your remote setpoint source will be when toggled by the SP Select  
key or Digital Input.  
NONE  
NONE—No remote setpoint.  
INPUT 2  
IN ALG1  
INPUT 2—Remote Setpoint is Input 2.  
IN AL1—Remote Setpoint using Input 1 algorithm.  
ATTENTION To cycle through the available local setpoints and  
SP  
Select  
remote setpoint, press and hold in the  
key. When the key is  
released, the setpoint selection currently displayed will be the new  
setpoint selection.  
AUTOBIAS  
SP TRACK  
AUTOBIAS is used for bumpless transfer when transferring from  
local setpoint to remote setpoint. Auto Bias calculates and adds a  
bias to remote setpoint input each time a transfer is made. Only  
available if no tracking is selected.  
DISABLE—Disables auto bias.  
ENABLE—Enables auto bias.  
DISABLE  
ENABLE  
SETPOINT TRACKING—The local setpoint can be configured to  
track either PV or RSP as listed below. Not configurable when Auto  
Bias is set.  
ATTENTION For selections other than NONE, LSP is stored in  
nonvolatile memory only when there is a mode change; i.e., when  
switching from RSP to LSP or from Manual to Automatic. If power  
is lost, then the current LSP value is also lost.  
NONE  
NO TRACKING—If local setpoint tracking is not configured, the  
LSP will not be altered when transfer from RSP to LSP is made.  
PV  
PV—Local setpoint tracks the PV when in manual.  
RSP  
RSP—Local setpoint tracks remote setpoint when in automatic.  
When the controller transfers out of remote setpoint, the last value  
of the remote setpoint (RSP) is inserted into the local setpoint.  
PWR MODE  
POWER UP CONTROLLER MODE RECALL—This selection  
determines which mode and setpoint the controller will use when  
the controller restarts after a power loss.  
MANUAL  
A LSP  
MANUAL, LSP—At power-up, the controller will use manual mode  
with the local setpoint displayed.  
AUTOMATIC MODE, LAST LSP—At power-up, the controller will  
use automatic mode with the last local setpoint used before power  
down displayed.  
A RSP  
AUTOMATIC MODE, LAST RSP—At power-up, the controller will  
use automatic mode with the last remote setpoint used before  
power down displayed.  
AM SP  
LAST MODE/LAST SETPOINT used before power down.  
LAST MODE/LAST LOCAL SETPOINT on power down.  
AM LSP  
PWR OUT  
THREE POSITION CONTROL STEP OUTPUT START-UP  
MODE—This selection determines what position the motor will be  
in when powered up or in the failsafe position.  
For Three  
Position Step  
Control Only  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
LAST  
(Note 3)  
LAST OUTPUT—At power-up in automatic mode, the motor  
position will be the last one prior to power down. When the unit  
goes into FAILSAFE, it will stay in automatic mode; motor will not  
be driven to the configured failsafe position.  
F’SAFE  
FAILSAFE OUTPUT—At power-up in manual mode, the motor will  
be driven to either the 0 % or 100 % output position, whichever is  
selected at prompt FAILSAFE. For Burnout/None, when the unit  
goes into FAILSAFE, it will go to manual mode; motor will be driven  
to the configured failsafe position.  
0 to 100 % of PV  
span in  
engineering units  
SP HiLIM  
(Note 4)  
SETPOINT HIGH LIMIT—This selection prevents the local and  
remote setpoints from going above the value selected here. The  
setting must be equal or less than the upper range of the PV.  
0 to 100 % of PV  
span in  
engineering units  
SP LoLIM  
(Note 4)  
SET POINT LOW LIMIT—This selection prevents the local and  
remote setpoints from going below the value selected here. The  
setting must be equal or greater than the lower range of the PV.  
ACTION  
CONTROL OUTPUT DIRECTION—Select direct or reverse output  
action.  
DIRECT  
DIRECT ACTING CONTROL—The controller’s output increases  
as the process variable increases.  
REVERSE  
REVERSE ACTING CONTROL—The controller’s output  
decreases as the process variable increases.  
OUT RATE  
OUTPUT CHANGE RATE—Enables or disables the Output  
Change Rate. The maximum rate is set at prompt PCT/M UP or  
PCT/M DN. Only available for PID-A, PID-B, PD+MR control  
algorithms.  
ENABLE  
DISABLE  
ENABLE—Allows output rate.  
DISABLE—Disables output rate.  
0 to 9999 % per  
minute  
PCT/M UP  
PCT/M DN  
OUTHiLIM  
OUTPUT RATE UP VALUE—This selection limits the rate at which  
the output can change upward. Enter a value in percent per  
minute. Appears only if OUT RATE is enabled. “0” means no output  
rate applied.  
0 to 9999 % per  
minute  
OUTPUT RATE DOWN VALUE—This selection limits the rate at  
which the output can change downward. Enter a value in percent  
per minute. Appears only if OUT RATE is enabled. “0” means no  
output rate.  
HIGH OUTPUT LIMIT—This is the highest value of output beyond  
which you do not want the controller automatic output to exceed.  
0 % to 100 %  
–5 % to 105 %  
For relay output types.  
For current output types.  
OUTLoLIM  
LOW OUTPUT LIMIT—This is the lowest value of output below  
which you do not want the controller automatic output to exceed.  
0 % to 100 %  
–5 % to 105 %  
For relay output types.  
For current output types.  
Within the range of  
the output limits  
I Hi LIM  
(Note 5)  
I Lo LIM  
(Note 5)  
DROPOFF  
(Note 5)  
HIGH RESET LIMIT—This is the highest value of output beyond  
which you do not want reset action to occur  
Within the range of  
the output limits  
LOW RESET LIMIT—This is the lowest value of output beyond  
which you do not want reset action to occur.  
–5 to 105 % of  
output  
CONTROLLER DROPOFF VALUE—Output value below which  
the controller output will drop off to the low output limit value set in  
prompt OUTLoLIM.  
50  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
DEADBAND  
DEADBAND is an adjustable gap between the operating ranges of  
output 1 and output 2 in which neither output operates (positive  
value) or both outputs operate (negative value).  
–5.0 to 25.0 %  
0.0 to 25.0 %  
0.5 to 5.0 %  
Time Duplex  
On-Off Duplex  
Position Proportional and Three Position Step  
0.0 to 100.0 % of  
PV span  
OUT HYST  
FAILMODE  
HYSTERESIS (OUTPUT RELAY) is an adjustable overlap of the  
ON/OFF states of each control output. This is the difference  
between the value of the process variable at which the control  
outputs energize and the value at which they de-energize.  
Only applicable for ON/OFF control.  
FAILSAFE MODE  
NoLATCH  
LATCH  
NON LATCHING—Controller stays in last mode that was being  
used (automatic or manual); If unit was in Automatic mode, then  
the output goes to the failsafe value. (NOTE 1, NOTE 2)  
LATCHING—Controller goes to manual mode; If unit was in  
Automatic mode, then the output goes to the failsafe value. (NOTE  
2)  
0 to 100 %  
FAILSAFE  
FAILSAFE OUTPUT VALUE—The value used here will also be  
the output level when you have Communications SHED set to  
failsafe or when NO BURNOUT is configured and Input 1 fails.  
ATTENTION Applies for all output types except Three Position  
Step Control.  
THREE POSITION STEP FAILSAFE OUTPUT  
0 PCT—Motor goes to closed position.  
0 PCT  
100 PCT  
100 PCT—Motor goes to open position.  
Position Proportional motor position when slidewire fails.  
0 PCT—Motor goes to closed position.  
SW FAIL  
0 PCT  
100 PCT  
100 PCT—Motor goes to open position.  
ATTENTION PWR OUT must be configured for FSAFE.  
0 to 100 %  
0 to 100 %  
MAN OUT  
AUTO OUT  
PBorGAIN  
POWER-UP PRESET MANUAL OUTPUT—At power-up, the  
controller will go to manual and the output to the value set here.  
(NOTE 1)  
POWER-UP PRESET AUTOMATIC OUTPUT—At power-up, the  
controller will begin its automatic control at the output value set  
here. (NOTE 1)  
PROPORTIONAL BAND UNITS—Select one of the following for  
the Proportional (P) term of the PID algorithm:  
PB PCT  
GAIN  
PROPORTIONAL BAND selects units of percent proportional band  
for the P term of the PID algorithm.  
Where: PB % = 100 % FS  
GAIN  
GAIN selects the unitless term of gain for the P term of the PID  
algorithm.  
Where: GAIN = 100 % FS  
PB%  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
MINUTESorRP  
M
RESET UNITS—Selects units of minutes per repeat or repeats per  
minute for the I term of the PID algorithm.  
20 Repeats per Minute = 0.05 Minutes per Repeat.  
RPM  
REPEATS PER MINUTE—The number of times per minute that  
the proportional action is repeated by reset.  
MINUTES  
MINUTES PER REPEAT—The time between each repeat of the  
proportional action by reset.  
NOTE 1: Does not apply to Three Position Step Control.  
NOTE 2: If controller is in Manual mode when a failure occurs, then the output will maintain its value.  
NOTE 3:These selections appear when:  
A) Control Algorithm is selected for 3PSTEP.  
B) Control Algorithm is selected for PD+MR and Output Algorithm is selected for Position  
Proportional.  
NOTE 4: The local setpoint will automatically adjust itself to be within the setpoint limit range. For  
example, if SP = 1500 and the SP HiLIM is changed to 1200, the new local setpoint will be 1200.  
NOTE 5: Reset limits and Dropoff are not displayed when Three Position Step Control is configured.  
52  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.11 Options Group  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter  
Definition  
AUX OUT  
AUXILIARY OUTPUT SELECTION  
This selection provides an mA output representing one of several  
control parameters. The display for auxiliary output viewing will be  
in engineering units for all but output. Output will be displayed in  
percent.  
ATTENTION  
Prompts for the  
Auxiliary  
Output  
Selection  
appear only if  
one of the  
ATTENTION Other prompts affected by these selections: 4mA VAL  
and 20mA VAL.  
Auxiliary  
Output boards  
is installed.  
ATTENTION Output cannot be configured when Three Position  
Step Control is used.  
DISABLE  
INPUT 1  
INPUT 2  
PV  
NO AUXILIARY OUTPUT  
INPUT 1—This represents the configured range of input 1.  
INPUT 2 represents the value of the configured range of input 2.  
PROCESS VARIABLE—Represents the value of the Process  
Variable. PV = Input XxRatioX + BiasX  
DEV  
DEVIATION (PROCESS VARIABLE MINUS SETPOINT)—  
Represents –100 % to +100 % of the selected PV span in  
engineering units.  
Zero deviation will produce a center scale (12 mA or 50 %) output.  
A negative deviation equal in magnitude to the Auxiliary Output  
High Scaling Factor will produce a low end output (4 mA or 0 %)  
output. A positive deviation equal in magnitude to the Auxiliary  
Output Low Scaling Factor will produce a high end output (20 mA  
or 100 %).  
OUTPUT  
SP  
OUTPUT—Represents the displayed controller output in percent  
(%). Cannot be used with  
Three Position Step Control.  
SETPOINT—Represents the value of the setpoint currently in use  
(LSP1, LSP2, LSP3, RSP or CSP) and is shown in the same units  
as those used by the PV.  
LSP 1  
RSP  
LOCAL SETPOINT ONE—Auxiliary output represents Local  
Setpoint 1 regardless of active setpoint.  
REMOTE SETPOINT – Represents the configured RSP regardless  
of the active SetPoint.  
IN ALG1  
INPUT ALGORITHM 1 OUTPUT—Represents the output from  
input algorithm 1.  
4-20mA  
0-20mA  
CO RANGE  
AUXILIARY CURRENT OUTPUT RANGE—Allows the user to  
easily select 4-20mA output or 0-20mA output operation without  
the need for recalibration of the instrument.  
ATTENTION Changing the Auxiliary Current Output Range will  
result in the loss of Field Calibration values and will restore Factory  
Calibration values.  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter  
Definition  
Low Scale Value  
within the range of  
the selected  
LOW VAL  
HIGH VAL  
DIG INP1  
AUXILIARY OUTPUT LOW SCALING FACTOR— This is a value  
in engineering units used to represent all AUX OUT parameters  
except Output.  
variable to  
For Output, this is a value in percent and can be any value  
between –5 % and +105 %. However, keep in mind that relay  
output types can only be scaled 0 % to 100 %.  
represent the  
minimun output (0  
or 4 mA)  
High Scale Value  
within the range of  
the selected  
AUXILIARY OUTPUT HIGH SCALING FACTOR— This is a value  
in engineering units used to represent all AUX OUT parameters  
except Output.  
variable to  
For Output, this is a value in percent and can be any value  
between –5 % and +105 %. However, keep in mind that relay  
output types can only be scaled 0 % to 100 %.  
represent the  
maximum output  
(20 mA)  
DIGITAL INPUT 1 SELECTIONS—All selections are available for  
Input 1. The controller returns to its original state when contact  
opens, except when overruled by the keyboard.  
NONE  
NO DIGITAL INPUT SELECTIONS  
TO MAN  
TO MANUAL—Contact closure puts the affected loop into manual  
mode. Contact open returns controller to former mode.  
TO LSP  
TO LOCAL SETPOINT—When a remote setpoint is configured,  
contact closure puts the controller into local setpoint 1. When  
contact opens, the controller returns to former operation—local or  
remote setpoint—unless SP Select key is pressed while digital  
input is active. If this happens, the controller will stay in the local  
setpoint mode when contact opens.  
TO 2SP  
TO 3SP  
TO DIR  
TO LOCAL SETPOINT TWO—Contact closure puts the controller  
into local setpoint 2.  
TO LOCAL SETPOINT THREE—Contact closure puts the  
controller into local setpoint 3.  
TO DIRECT ACTION—Contact closure selects direct controller  
action.  
TO HOLD  
TO HOLD—Contact closure suspends Setpoint Program or  
Setpoint Ramp. When contact reopens, the controller starts from  
the Hold point of the Ramp/Program unless the Ramp/Program  
Run  
Hold  
was not previously started via the  
This selection applies to either loop.  
key.  
TO PID2  
PV 2IN  
TO PID2—Contact closure selects PID Set 2.  
PV=INPUT 2—Contact closure selects PV = Input 2.  
RERUN  
RERUN--Allows the Setpoint Programmer to be reset to the initial  
segment of its current cycle, unit stays in previous mode.  
54  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter  
Definition  
TO RUN  
RUN—Contact closure starts a stopped SP Ramp or Program.  
Upper left character blinks “R”. Reopening the contact puts  
controller in HOLD mode.  
This selection applies to either loop.  
ToBEGIN  
EXTERNAL SP PROGRAM RESET—Contact closure resets SP  
Program back to the beginning of the first segment in the program  
and places the program in the HOLD mode. Program cycle number  
is not affected. Reopening switch has no effect.  
This selection applies to either loop.  
ATTENTION Once the last segment of the setpoint program has  
timed out, the controller enters the mode of action specified in the  
configuration data and the program cannot be reset to the  
beginning of the first segment by digital input closure.  
STOP I  
INHIBIT INTEGRAL (RESET)—Contact closure disables PID  
Integral (Reset) action.  
MAN FS  
MANUAL FAILSAFE OUTPUT—Controller goes to Manual mode,  
output goes to the Failsafe value.  
ATTENTION This will cause a bump in the output when switching  
from Automatic to Manual. The switch back from Manual to  
Automatic is bumpless. When the switch is closed, the output can  
be adjusted from the keyboard.  
TO LOCK  
TO Aout  
KEYBOARD LOCKOUT—Contact closure disables all keys.  
Lower display shows LOCKED if a key is pressed.  
AUTOMATIC OUTPUT—Contact closure sends output to the  
value set at Control prompt AUTO OUT when the controller is in  
the Automatic mode. Reopening the contact returns the controller  
to the normal output.  
ATTENTION Does not apply to Three Position Step Control.  
TIMER  
TIMER—Contact closure starts timer, if enabled. Reopening the  
switch has no effect.  
AM STA  
TO AUTO/MANUAL STATION—Contact closure causes the  
control loop to perform as follows:  
PV = Input 2  
Action = Direct  
Control algorithm = PD+MR  
PID SET = 2  
SP = LSP 2  
TO TUNE  
SP Init  
INITIATE LIMIT CYCLE TUNING—Contact closure starts the  
tuning process. The lower display shows TUNE ON. Opening the  
contact has no effect.  
SETPOINT INITIALIZATION—Contact closure forces the setpoint  
to the current PV value. Opening the contact has no effect.  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter  
Definition  
TRACK  
OUTPUT TRACKS INPUT 2—Contact closure allows Output to  
track Input 2. While the switch is open, the output is in accordance  
with its pre-defined functionality. When the switch is closed, the  
output value (in percent) will track the Input 2 percent of range  
value. When the switch is reopened, the output will start at this last  
output value and normal PID action will then take over control. The  
transfer is bumpless.  
TO RSP  
RST FB  
TO REMOTE SETPOINT—Contact closure selects the Remote  
setpoint.  
EXTERNAL RESET FEEDBACK—Contact closure allows Input 2  
to override the internal reset value.  
To PURGE  
TO PURGE—Contact closure forces the loop to Manual mode with  
the output set to the Output High Limit configuration. MAN lights  
and the Output value is shown on the lower display. Opening the  
switch has no effect.  
ATTENTION Does not apply to Three Position Step Control.  
Lo FIRE  
LOW FIRE—Contact closure forces the loop to Manual mode with  
the output set to the Output Low Limit configuration. MAN lights  
and the Output value is shown on the lower display. Opening the  
switch has no effect.  
ATTENTION Does not apply to Three Position Step Control.  
MAN LAT  
PV Hold  
MANUAL LATCHING—Contact closure transition forces the loop  
to Manual mode. Opening the switch has no effect. If the  
MAN/AUTO key is pressed while the switch is closed, the loop will  
return to Automatic mode.  
PROCESS VARIABLE HOLD—when the switch is closed, PV is  
frozen at last value. When switch opens, PV resumes.  
DIG 1COMB  
DIGITAL INPUT 1 COMBINATION SELECTIONS —This selection  
allows the specified function to occur in addition to the one chosen  
for DIG IN 1.  
DISABLE  
+PID2  
DISABLE—Disables combination function.  
PLUS PID2—Contact closure selects PID Set 2.  
+TO DIR  
PLUS DIRECT ACTION—Contact closure selects direct controller  
action.  
+TO SP2  
+DIS AT  
PLUS SETPOINT 2—Contact closure puts the controller into SP2.  
PLUS DISABLE ADAPTIVE TUNE—Contact closure disables  
Accutune process.  
+TO SP1  
+RUN  
PLUS SETPOINT 1—Contact closure puts the controller into SP1.  
PLUS RUN SETPOINT PROGRAM/RAMP—Contact closure  
starts SP Program/Ramp if enabled.  
Same selections  
as for Digital Inp 1  
DIG INP2  
DIGITAL INPUT 2 SELECTIONS  
Same selections  
as Digital Input 1  
Combinations  
DIG2COMB  
DIGITAL INPUT 2 COMBINATIONS  
56  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.12 Communications Group  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter  
Definition  
1 to 99  
Com ADDR  
COMMUNICATIONS STATION ADDRESS—This is a number that  
is assigned to a controller that is to be used with the  
communications option. This number will be its address.  
ComSTATE  
COMMUNICATIONS SELECTION  
DISABLE  
MODBUS  
DISABLE—Disables RS-485 communications option.  
MODBUS—Enables RS-485 Modbus RTU communication port.  
DISABLE  
ENABLE  
IR ENABLE  
BAUD  
IR ENABLE–Disable/Enables IR communications port.  
ATTENTION If there are no IR communications transactions for  
four minutes, then the IR port automatically shuts down. It can be  
re-enabled by pressing any key on the front panel.  
BAUD RATE is the transmission speed in bits per second. This  
value is used for both RS-485 and IR Communications, but for IR  
Communications, values below 19200 baud are interpreted as  
being 19200 baud.  
4800  
9600  
19200  
38400  
4800 BAUD  
9600 BAUD  
19200 BAUD  
38400 BAUD  
1 to 500  
milliseconds  
TX DELAY  
WS FLOAT  
TX DELAY—Configurable response-delay timer allows you to force  
the instrument to delay its response for a time period of from 1 to  
500 milliseconds compatible with the host system  
hardware/software.  
Defines word/byte order of floating point data for communications.  
Byte values:  
0
1
2
3
seeeeeee emmmmmmm mmmmmmmm mmmmmmmm  
Where:  
s = sign, e = exponent, m = mantissa bit  
FP_B  
FP_BB  
FP_L  
0
1
3
2
1
0
2
3
2
3
1
0
3
2
0
1
FP_LB  
DISABLE  
ENABLE  
SHED ENAB  
SHEDTIME  
SHED ENABLE—Disables/enables shed functionaliy. Applies to  
Modbus protocol only.  
0 to 255  
SHED TIME—The number that represents how many sample  
periods there will be before the controller sheds from  
communications. Each period equals 1/3 seconds; 0 equals No  
shed.  
Note: If ComSTATE is set to MODBUS or MB3K and if  
SHEDENAB is set to DISABL, Shed Time will not be configurable.  
SHEDMODE  
SHED CONTROLLER MODE AND OUTPUT LEVEL—Determines  
the mode of local control you want when the controller is shed from  
the communications link.  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter  
Definition  
LAST  
LAST—SAME MODE AND OUTPUT—The controller will return to  
the same mode (manual or automatic) at the same output level that  
it had before shed.  
TO MAN  
FSAFE  
TO AUTO  
TO MAN—MANUAL MODE, SAME OUTPUT—The controller will  
return to manual mode at the same output level that it had before  
shed.  
FSAFE—MANUAL MODE, FAILSAFE OUTPUT—The controller  
will return to manual mode at the output value selected at Control  
prompt FAILSAFE.  
TO AUTO—AUTOMATIC MODE, LAST SP—The controller will  
return to the automatic mode and the last setpoint used before  
shed.  
SHED SP  
SHED SETPOINT RECALL  
Note: If SHEDENAB=DISABLE, this prompt will not be  
configurable.  
TO LSP  
TO CSP  
TO LSP—Controller will use last local or remote setpoint used.  
TO CSP—When in “slave” mode, the controller will store the last  
host computer setpoint and use it at the Local setpoint. When in  
“monitor” mode, the controller will shed to the last instrument Local  
or Remote setpoint used, and the LSP is unchanged.  
UNITS  
COMPUTER SETPOINT UNITS  
ENG  
ENG — Engineering units  
PERCENT  
–20.0 to 20.0  
PERCENT — Percent of PV range  
COMPUTER SETPOINT RATIO—Computer setpoint ratio.  
CSP RATO  
CSP BIAS  
–999. to 9999.  
COMPUTER SETPOINT BIAS—Computer setpoint bias in  
(engineering units)  
Engineering Units.  
LOOPBACK  
LOCAL LOOPBACK tests the RS-485 communications port. It is  
not used for any other communications port.  
DISABLE  
ENABLE  
DISABLE—Disables the Loopback test.  
ENABLE—Allows loopback test. The instrument goes into  
Loopback mode in which it sends and receives its own message.  
The instrument displays PASS or FAIL status in the upper display  
and LOOPBACK in the lower display while the test is running. The  
instrument will go into manual mode when LOOPBACK is enabled  
with the output at the Failsafe value. The test will run until the  
operator disables it here, or until power is turned off and on.  
ATTENTION The instrument does not have to be connected to  
the external communications link in order to perform this test. If it is  
connected, only one instrument should run the loopback test at a  
time. The host computer should not be transmitting on the link  
while the loopback test is active.  
58  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.13 Alarms Set Up Group  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
Value in  
engineering units  
A1S1 VAL  
ALARM 1 SETPOINT 1 VALUE—This is the value at which you  
want the alarm type chosen in prompt A1S1TYPE to actuate. The  
value depends on what the setpoint has been configured to  
represent. No setpoint is required for alarms configured for  
Communications SHED. For SP Programming the value is the  
segment number for which the event applies.  
This prompt does not appear for “Alarm on Manual” type alarm.  
For example: A1S1TYPE = MANUAL.  
Value in  
engineering units  
A1S2 VAL  
A2S1 VAL  
A2S2 VAL  
A1S1TYPE  
ALARM 1 SETPOINT 2 VALUE—This is the value at which you  
want the alarm type chosen in prompt A1S2TYPE to actuate.  
The details are the same as A1S1 VAL.  
Value in  
engineering units  
ALARM 2 SETPOINT 1 VALUE—This is the value at which you  
want the alarm type chosen in prompt A2S1TYPE to actuate.  
The details are the same as A1S1 VAL.  
Value in  
engineering units  
ALARM 2 SETPOINT 2 VALUE—This is the value at which you  
want the alarm type chosen in prompt A2S2TYPE to actuate.  
The details are the same as A1S1 VAL.  
ALARM 1 SETPOINT 1 TYPE—Select what you want Setpoint 1  
of Alarm 1 to represent. It can represent the Process Variable,  
Deviation, Input 1, Input 2, Output, and if you have a model with  
communications, you can configure the controller to alarm on  
SHED. If you have setpoint programming, you can alarm when a  
segment goes ON or OFF.  
NONE  
NO ALARM  
INPUT 1  
INPUT 2  
PV  
INPUT 1  
INPUT 2  
PROCESS VARIABLE  
DEV  
DEVIATION  
OUTPUT  
SHED  
OUTPUT (NOTE 1)  
SHED FROM COMMUNICATIONS  
EVENT ON (SP PROGRAMMING)  
EVENT OFF (SP PROGRAMMING)  
ALARM ON MANUAL MODE (NOTE 2)  
REMOTE SETPOINT  
EV ON  
EV OFF  
MANUAL  
REM SP  
F SAFE  
PV RATE  
DIG INP 1  
DIG INP 2  
DEV 2  
FAILSAFE  
PV RATE OF CHANGE  
DIGITAL INPUT 1 ACTUATED (NOTE 7)  
DIGITAL INPUT 2 ACTUATED (NOTE 7)  
DEVIATION FROM LSP 2 (NOTE 3)  
LOOP BREAK (NOTE 4)  
THERMOCOUPLE WARNING (NOTE 5)  
THERMOCOUPLE FAIL (NOTE 6)  
PV HOLD  
BREAK  
TCWARN  
TCFAIL  
PVHOLD  
ATTENTION  
NOTE 1. When the controller is configured for Three Position Step Control, alarms set for Output will not  
function.  
NOTE 2. Alarm 1 is not available if the Timer is enabled because Alarm 1 is dedicated to Timer output.  
NOTE 3. This Deviation Alarm is based upon deviation from the 2nd Local Setpoint or Remote SP  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
regardless of whichever SP is active.  
NOTE 4. Loop Break monitors the control loop to determine if it is working. When enabled, the control  
output is checked against the minimum and maximum output limit settings. When the output reaches one  
of these limits, a timer begins. If the timer expires and the output has not caused the PV to move by a pre-  
determined amount, then the alarm activates, thus signalling that the loop is broken. The loop break timer  
value must be configured by the operator as the AxSx VAL entry. This value is in seconds with a range of  
0 to 3600 seconds. A setting of 0 is equivalent to an instantaneous loop break when the output reaches  
one of its limit values.  
The amount of PV Movement required is determined by the “UNITS” setting in the Display Setup Group.  
For the Degrees F configuration, the PV must move by 3° in the desired direction in the time allowed. For  
the Degrees C configuration, the PV must move by 2° in the desired direction in the time allowed. For the  
“NONE” selection, the PV must move 1% of the PV range in the time allowed.  
Loop Break alarms do not have a HIGH/LOW State configuration, they are always assumed to be a HIGH  
state alarm.  
NOTE 5. Thermocouple Warning means that the instrument has detected that the Thermocouple Input is  
starting to fail. Not valid for other input types.  
NOTE 6. Thermocouple Failing means that the instrument has detected that the Thermocouple Input is in  
imminent danger of failing. Not valid for other input types.  
NOTE 7: For the Digital Input selections, DIG INP1 can be either enabled or disabled in the Options  
Group (See Sub-Section 3.11), but DIG INP2 must be enabled in the Options Group for the alarm to  
function properly.  
If Setpoint Programming is disabled or if the Alarm Type is  
not configured for Event On/Off:  
ALARM 1 SETPOINT 1 STATE—Select whether you want the  
alarm type chosen in prompt A1S1TYPE to alarm High or Low.  
A1S1 H L  
HIGH  
LOW  
HIGH ALARM  
LOW ALARM  
If Setpoint Programming is enabled and if the Alarm Type is  
configured for Event On/Off:  
A1S1 EV  
ALARM 1 SEGMENT EVENT 1—Select whether you want the  
alarm type chosen in prompt A1S1TYPE to alarm the beginning  
or end of a segment in setpoint Ramp/Soak programming.  
BEGIN  
END  
BEGINNING OF SEGMENT  
END OF SEGMENT  
ATTENTION Alarms configured for events will not operate on  
Setpoint Program segments of zero length.  
Same as A1S1  
TYPE  
A1S2TYPE  
A1S2 H L  
ALARM 1 SETPOINT 2 TYPE—Select what you want Setpoint 2  
of Alarm 1 to represent.  
The selections are the same as A1S1TYPE.  
HIGH  
LOW  
ALARM 1 SETPOINT 2 STATE—Same as A1S1 H L.  
60  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
BEGIN  
END  
A1S2 EV  
ALARM 1 SEGMENT EVENT 2—Same as A1S1 EV.  
Same as A1S1  
TYPE  
A2S1TYPE  
ALARM 2 SETPOINT 1 TYPE—Select what you want Setpoint 1  
of Alarm 2 to represent.  
The selections are the same as A1S1TYPE.  
ATTENTION Not available with Relay Duplex or Position  
Proportional output types unless using Dual Relay PWA.  
HIGH  
LOW  
A2S1 H L  
A2S1 EV  
ALARM 2 SETPOINT 1 STATE—Same as A1S1 H L.  
BEGIN  
END  
ALARM 2 SEGMENT EVENT 1—Same as A1S1 EV.  
Same as A1S1  
TYPE  
A2S2TYPE  
ALARM 2 SETPOINT 2 TYPE—Select what you want Setpoint 2  
of Alarm 2 to represent.  
The selections are the same as A1S1TYPE.  
ATTENTION Not applicable with Relay Duplex or Position  
Proportional output types unless using Dual Relay PWA.  
HIGH  
LOW  
A2S2 H L  
A2S2 EV  
ALHYST  
ALARM 2 SETPOINT 2 STATE—Same as A1S1 H L.  
BEGIN  
END  
ALARM 2 SEGMENT EVENT 2—Same as  
A1S1 EV.  
0.0 to 100.0 % of  
span or full output  
as appropriate  
ALARM HYSTERESIS—A single adjustable hysteresis is  
provided on alarms such that when the alarm is OFF it activates  
at exactly the alarm setpoint; when the alarm is ON, it will not  
deactivate until the variable is 0.0 % to 100 % away from the  
alarm setpoint.  
Configure the hysteresis of the alarms based on INPUT signals  
as a % of input range span.  
Configure the hysteresis of the alarm based on OUTPUT signals  
as a % of the full scale output range.  
ALM OUT1  
LATCHING ALARM OUTPUT 1—Alarm output 1 can be  
configured to be Latching or Non-latching.  
NoLATCH  
LATCH  
NoLATCH —Non-latching  
LATCH—Latching  
ATTENTION When configured for latching, the alarm will stay  
active after the alarm condition ends until the RUN/HOLD key is  
pressed.  
BLOCK  
ALARM BLOCKING—Prevents nuisance alarms when the  
controller is first powered up. The alarm is suppressed until the  
parameter gets to the non-alarm limit or band. Alarm blocking  
affects both alarm setpoints.  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
DISABLE  
ALARM 1  
ALARM 2  
ALARM12  
DISABLE—Disables blocking  
ALARM 1—Blocks alarm 1 only  
ALARM 2—Blocks alarm 2 only  
ALARM12—Blocks both alarms  
ATTENTION When enabled on power up or initial enabling via  
configuration, the alarm will not activate unless the parameter  
being monitored has not been in an alarm condition for a  
minimum of one control cycle (167 ms).  
DIAGNOST  
DIAGNOSTIC—Monitors the Current Output and/or Auxiliary  
Output for an open circuit condition. If either of these two outputs  
falls below about 3.5 mA, then an Alarm is activated. This  
configuration is in addition to whatever was selected for  
AxSxTYPE.  
DISABLE  
ALARM 1  
ALARM 2  
DISABLE—Disables Diagnostic Alarm  
ALARM 1—Alarm 1 is diagnostic alarm  
ALARM 2—Alarm 2 is diagnostic alarm  
62  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.14 Display Set Up Group  
Function  
Prompt  
Lower Display  
Selections or  
Range of Setting  
Upper Display  
Parameter Definition  
DECIMAL  
DECIMAL POINT LOCATION—This selection determines where  
the decimal point appears in the display.  
NONE  
ONE  
NONE—No Decimal Place—fixed, no auto-ranging  
ONE—One Place  
TWO  
TWO—Two Places  
THREE  
THREE—Three Places  
ATTENTION Auto-ranging will occur for selections of one, two or  
three decimal places. For example, should the instrument be  
configured for two decimal places and the PV exceeds 99.99, then  
the display will change to a single decimal place so that values of  
100.0 and above can be shown.  
TEMP UNIT  
TEMPERATURE UNITS—This selection will affect the indication  
and operation.  
DEG F  
DEG C  
NONE  
DEG F—Degrees Fahrenheit – Degrees F Annunciator lighted  
DEG C—Degrees Centigrade – Degrees C Annunciator lighted  
NONE—No temperature annunciators lighted. Upper and Lower  
Displays will show temperature in Degrees Fahrenheit when inputs  
are configured for Thermocouple or RTD types.  
60 HZ  
50 HZ  
PWR FREQ  
POWER LINE FREQUENCY—Select whether your controller is  
operating at 50 or 60 Hertz.  
ATTENTION For controllers powered by +24 Vdc, this  
configuration should be set to the AC line frequency used to  
produce the +24 Vdc supply.  
Incorrect setting of this parameter may cause normal mode noise  
problems in the input readings.  
RATIO 2  
INPUT 2 RATIO—This enables the Ratio for Input 2 to be set from  
the front panel. Input 2 must be installed and enabled for this  
configuration to operate.  
DISABLE  
ENABLE  
DISABLE—Disables setting Ratio 2 from front panel.  
ENABLE—Allows the Ratio for Input 2 to be set through the  
keyboard.  
LANGUAGE  
LANGUAGE—This selection designates the prompt language.  
ENGLISH  
FRENCH  
GERMAN  
SPANISH  
ITALIAN  
ENGLISH  
FRENCH  
GERMAN  
SPANISH  
ITALIAN  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Download from Www.Somanuals.com. All Manuals Search And Download.  
4 Monitoring and Operating the Controller  
4.1 Operator Interface  
Introduction  
Figure 4-1 Operator Interface  
4.2 Entering a Security Code  
Introduction  
The level of keyboard lockout may be changed in the Set Up mode. However,  
knowledge of a security code number (0 to 9999) may be required to change from one  
level of lockout to another. When a controller leaves the factory, it has a security code  
of 0 which permits changing from one lockout level to another without entering any  
other code number.  
Procedure  
If you require the use of a security code, select a number from 0001 to 9999 and enter  
it when the lockout level is configured as NONE. Thereafter, that selected number  
must be used to change the lockout level from something other than NONE.  
ATTENTION Write the number on the Configuration Record Sheet in the  
configuration section so you will have a permanent record.  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Table 4-1 Procedure to Enter a Security Code  
Step  
1
Operation  
Press  
Result  
Enter Set Up  
Mode  
Upper Display = SET UP  
Lower Display = TUNING  
Setup  
Select any Set  
Up Group  
2
3
Upper Display = 0  
Function  
Lower Display = SECUR  
Security Code  
Entry  
To enter a four digit number in the upper display  
(0001 to 9999)  
or  
This will be your security code.  
4.3 Individual key lockout  
There are three keys that can be disabled to prevent unauthorized changes to the  
parameters associated with these keys. First set the “Lock” prompt to NONE.  
These keys are:  
Run  
Hold  
Key  
Key  
Key  
- you can disable the Run/Hold key for Set Point  
Programming at configuration Set Up group prompt  
“Tuning,” function prompt “RN HLD.”  
Man  
Auto  
- you can disable the Auto/Manual key at configuration  
Set Up, group prompt “Tuning”, function prompt  
“AUTOMA”  
SP  
Select  
- you can disable the Set Point Select function key at  
configuration Set Up group prompt “Tuning,” function  
prompt “SP SEL.”  
See Subsection 3.3 - Tuning Parameters Set Up Group prompts to enable or disable  
these keys.  
Key error  
When a key is pressed and the prompt “Key Error” appears in the lower display, it  
will be for one of the following reasons:  
• Parameter not available or locked out  
• Not in setup mode, press SET UP key first  
• Individual key locked out.  
66  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4.4 Monitoring Your Controller  
4.4.1 Annunciators  
The following annunciator functions have been provided to help monitor the  
controller:  
Table 4-2 Annunciators  
Annunciator  
ALM 1 2  
Indication  
A visual indication of each alarm  
Blinking 1 indicates an alarm latched condition. The blinking will  
continue even after the alarm condition ends until it is acknowledged by  
pressing the RUN/HOLD key.  
OUT 1 2  
A visual indication of the control relays  
A visual indication of each Digital Input  
DI 1 2  
A or MAN  
A visual indication of the mode of the controller)  
A—Automatic Mode  
MAN—Manual Mode  
[None], F or C  
A visual indication of the temperature units  
[None]—No temperature unit annunciator  
F—Degrees Fahrenheit  
C—Degrees Celsius  
A visual Lamp to indicate when the lower display is showing the Active  
Setpoint (Local 1, Local 2, Local 3, Remote Setpoint or Computer  
Setpoint)  
n
The upper left digit of the display is used to show other annunciator  
functions  
T—Accutuning in process  
C—Computer overide active  
O—Output override active  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4.4.2 Viewing the operating parameters  
Press the LOWER DISPLAY key to scroll through the operating parameters. The lower  
display will show only those parameters and their values that apply to your specific  
model.  
Table 4-3 Lower Display Key Parameter Prompts  
Lower Display  
OUT XX.X  
Description  
OUTPUT—Output value is shown in percent with one decimal point for all output  
types except Three Position Step Control (TPSC). For TPSC, when no slidewire is  
connected, this display is an estimated motor position and is shown with no decimal  
point. For Position Proportional Control, if the slidewire fails, then the instrument  
automatically switches over to TPSC and the OUT display changes with it.  
LOCAL SETPOINT #1—Also current setpoint when using SP Ramp.  
LOCAL SETPOINT #2  
SP XXXX  
2SP XXXX  
3SP XXXX  
RSP XXXX  
1IN XXXX  
2IN XXXX  
POS XX  
LOCAL SETPOINT #3  
REMOTE SETPOINT  
INPUT 1—Used only with combinational input algorithms.  
INPUT 2  
SLIDEWIRE POSITION—Used only with TPSC applications that use a slidewire input.  
COMPUTER SETPOINT—When SP is in override.  
DEVIATION—Maximum negative display is –999.9.  
TUNING PARAMETER —where X is either 1 or 2.  
ELAPSED TIME—Time that has elapsed on the Timer in Hours.Minutes.  
CSP XXXX  
DEV XXXX  
PIDSET X  
ET HR.MN  
OTR HR.MN  
TIME REMAINING—Time remaining on the Timer in Hours.Minutes. The “O” is a  
rotating clock face.  
SETPOINT RAMP TIME—Time remaining in the Setpoint Ramp in minutes.  
RAMPXXXM  
SPN XXXX  
SETPOINT NOW—Current Setpoint when SP Rate is enabled. The SP XXXX display  
shows the “target” or final setpoint value.  
RAMP SEGMENT NUMBER AND TIME REMAINING—Set Point Programming  
display. XX is the current segment number and HR.MN is the time remaining for this  
segment in Hours.Minutes.  
XXRAHR.MN  
XXSKHR.MN  
SOAK SEGMENT NUMBER AND TIME REMAINING— Set Point Programming  
display. XX is the current segment number and HR.MN is the time remaining for this  
segment in Hours.Minutes.  
NUMBER OF SP PROGRAM RECYCLES REMAINING  
RECYC XX  
To BEGIN  
RERUN  
RESET SP PROGRAM TO START OF FIRST SEGMENT  
RESET SP PROGRAM TO START OF CURRENT SEGMENT  
AUXILIARY OUTPUT—Displayed only when output algorithm is not Current Duplex.  
BIAS—Displays the manual reset value for algorithm PD+MR.  
AUX XXXX  
BIA XXXX  
TUNE OFF  
LIMIT CYCLE TUNING NOT RUNNING—Appears when Accutune is enabled but not  
operating.  
DO FAST  
DO SLOW  
Limit Cycle Tuning with the objective of producing quarter-damped tuning parameters.  
This tuning may result in PV overshoot of the SP setting.  
Limit Cycle Tuning with the objective of producing damped or Dahlin tuning  
parameters, depending upon the detected process deadtime. The tuning parameters  
calculated by this selection are aimed at reducing PV overshoot of the SP setting.  
68  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4.4.3 Diagnostic Messages  
The UDC3200 performs background tests to verify data and memory integrity. If  
there is a malfunction, a diagnostic message will be shown on the lower display. In  
the case of more than one simultaneous malfunction, only the highest priority  
diagnostic message will be displayed. Table 4-4 shows the error messages in order by  
priority.  
Table 4-4 Diagnostic Messages  
Prompt  
EE FAIL  
Description  
Unable to write to nonvolatile memory. A subsequent successful write to  
nonvolatile memory removes this message.  
This error message appears whenever the controller goes into a failsafe  
mode of operation. Failsafe operation occurs when an analog input fails or  
when configuration is corrupted.  
FAILSAFE  
Two consecutive failures of input 1 integration or input value is outside of  
Out-of-Range limits.  
INP1FAIL  
INP2FAIL  
SW FAIL  
Two consecutive failures of input 2 integration or input value is outside of  
Out-of-Range limits.  
Slidewire input failure. Position Proportional Control automatically switched  
to Three Position Step Control.  
Configuration Errors—Low limit greater than high limit for PV, SP, Reset, or  
Output.  
CONF ERR  
Carbon Potential Problem—Percent Carbon outside of “sooting boundary.”  
SOOTING  
IN1 RNG  
Input 1 Out-of-Range—Input is outside of the High or Low Limits.  
Out-of-range criteria:  
Linear range: ± 10 %  
Characterized range: ± 1 %  
Input 2 Out-of-Range—Same criteria as Input 1.  
IN2 RNG  
PV LIMIT  
PV beyond limits—PV outside of PV Hi/Low Limits.  
PV = (PV source x PV source ratio) + PV source bias  
Failsafe—Check inputs or configuration.  
FAILSAFE  
RV LIMIT  
Remote Variable beyond limits—RSP outside of SP Hi/Low Limits.  
RV = (RV source x RV source ratio) + RV source bias  
Segment Error—SP Program starting segment number is less than ending  
segment number.  
SEG ERR  
Slidewire not calibrated. Perform Slidewire calibration.  
Position Proportional slidewire input failure.  
CAL MTR  
SW FAIL  
The Thermocouple on Input 1 is starting to burnout.  
The Thermocouple on Input 2 is starting to burnout.  
Thermocouple on Input 1 is in imminent danger of burning out.  
Thermocouple on Input 2 is in imminent danger of burning out.  
Current Output is less than 3.5 mA.  
TC1 WARN  
TC2 WARN  
TC1 FAIL  
TC2 FAIL  
OUT1FAIL  
OUT2FAIL  
Current Output 2 is less than 3.5 mA.  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
IN 1  
IN 2  
Ratio  
Bias  
Ratio  
Bias  
1
2
To RSP  
In Alg1  
IN 2  
To RSP  
PV  
Source  
Input 1  
Input 2  
INPUT  
ALGORITHM 1  
INPUT A  
Output 1  
RSP  
Source  
FEEDFORWARD  
INPUT A ONLY  
To RSP  
Input 1  
Input 2  
PV  
INPUT B  
INPUT C  
Output 1  
Remote SP  
SP  
SP  
CONTROL  
ALGORITHM  
Source  
Local SP  
LSP1  
Input 1  
Input 2  
Output 1  
FEEDFO RWARD  
SUMMER OR  
MULTIPLIER  
LSP3  
LSP2  
Manual Mode  
Output  
To Final  
Control  
Element  
OUTPUT  
Figure 4-2 Functional Overview Block Diagram of the UDC3200 Controller  
70  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.5 Accutune III  
Introduction  
Accutune III (TUNE) may be used for self-regulating and single integrating  
processes. This autotuning method is initiated on-demand, typically at initial start-up.  
There are no other requirements necessary, such as prior knowledge to the process  
dynamics or initial or post tune process line-out to setpoint or manual output.  
Also, the setpoint value is not required to change in order to initiate the tuning  
process, but the controller must be in the Automatic mode to start tuning. The process  
need not be in a static (lined out) state and may be dynamic (changing with a steady  
output).  
Configuration check  
Make sure:  
TUNE has been enabled see to Subsection 3.5 - Accutune Set Up Group for  
details.  
Tuning indicators  
A “T” will show in the leftmost alphanumeric of the upper display until tuning is  
completed.  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
The Accutune III algorithm provides user-friendly, on-demand tuning in this  
controller. No knowledge of the process is required at start-up. The operator simply  
initiates the tuning while in the automatic mode.  
Once Accutune III has been enabled in the TUNE setup group, either “SLOW” or  
“FAST” tuning may be used. Which one is used is selected via the lower display  
during normal operation.  
For the SLOW selection, the controller calculates conservative tuning constants with  
the objective of minimizing overshoot. If the controller determines that the process  
has appreciable dead time, it will automatically default to use Dahlin Tuning, which  
produces very conservative tuning constants. The SLOW selection may be useful for  
TPSC and Position Proportional applications, as it reduces “hunt” problems for the  
motor. This selection is also recommended for applications that have significant  
deadtimes.  
For the FAST selection, the controller calculates aggressive tuning constants with the  
objective of producing quarter damped response. Depending upon the process, this  
selection will usually result in some overshoot. For this reason, it may be desireable  
to enable the FUZZY tune selection. See Section 4.6. When Fuzzy tune is enabled, it  
will work to suppress or eliminate any overshoot that may occur as a result of the  
calculated tuning parameters as the PV approaches the setpoint. This selection is best  
suited for processes with a single lag or for those that do not have any appreciable  
deadtime. FUZZY tuning does not work well for processes that have appreciable  
deadtime.  
The Accutune III tuning process will cycle the controller’s output two full cycles  
between the low and high output limits while allowing only a very small Process  
Variable change above and below the SP during each cycle. A “T” shows in the upper  
display until tuning is completed.  
At the end of the tuning process, the controller immediately calculates the tuning  
constants and enters them into the Tuning group, and begins PID control with the  
correct tuning parameters. This works with any process, including integrating type  
processes, and allows retuning at a fixed setpoint.  
4.5.1 Tune for Simplex Outputs  
After “TUNE” has been enabled, you can start Accutune as shown in Table 4-5.  
Table 4-5 Procedure for Starting “TUNE”  
Step  
1
Operation  
Press  
Result  
Configure LSP1  
Until SP (Local Setpoint 1) shows  
in the lower display.  
Lower  
Display  
Until LSP1 is to the desired value.  
2
3
or  
Switch to  
“Automatic” Mode  
Until the “A” indicator is lighted (on  
controllers with Manual option).  
Man  
Auto  
Show Tuning  
Prompt  
Until “TUNE OFF” is shown on  
lower display.  
4
Lower  
Display  
72  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Initiate Tuning  
Select “DO SLOW” or “DO FAST”  
in lower display.  
5
6
Tuning in operation  
Upper display will show a “T” as  
long as ACCUTUNE process is  
operating. When process  
Lower  
Display  
completes, tuning parameters are  
calculated and lower display will  
show “NO TUNE” prompt.  
ATTENTION  
The Accutune process may be aborted at any time by changing the lower display back to “NoTUNE” or  
by switching the controller into Manual Mode.  
4.5.2 Tune for Duplex (Heat/Cool)  
Accutune for applications using Duplex (Heat/Cool) control.  
The controller must be configured to have two local setpoints unless Blended Tuning  
is desired (see below). During tuning, the Accutune III process assumes that Local  
Setpoint 1 will cause a Heating demand (output above 50%), and the tuning  
parameters calculated for that setpoint are automatically entered as PID SET 1.  
Likewise, Accutune III assumes that Local Setpoint 2 will cause a Cooling demand  
(output less than 50%), and the tuning parameters calculated for that setpoint are  
automatically entered as PID SET 2.  
Configuration Check for Duplex  
See Subsection 3.5 - Accutune Set Up Group for details.  
Make sure:  
TUNE has been enabled  
DUPLEX has been configured to Manual, Automatic or Disabled  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4.5.3 Using AUTOMATIC TUNE at start-up for Duplex (Heat/Cool)  
Used when DUPLEX has been configured for AUTOMATIC. This is the preferred  
selection for most Heat/Cool applications when tuning a new chamber. This selection  
will sequentially perform both Heat and Cool tuning without further operator  
intervention.  
Table 4-6 Procedure for Using AUTOMATIC TUNE at Start-up for Duplex  
Control  
Step  
1
Operation  
Press  
Result  
Configure LSP1  
Until SP (Local Setpoint 1) shows  
in the lower display.  
Lower  
Display  
Until LSP1 is a value within the  
Heat Zone (output above 50%).  
2
3
or  
Configure LSP2  
Until 2SP (Local Setpoint 2) shows  
in the lower display.  
Lower  
Display  
Until LSP2 is a value within the  
Cool Zone (output below 50%).  
4
5
or  
Switch to  
“Automatic” Mode  
Until the “A” indicator is lighted (on  
controllers with Manual option).  
Man  
Auto  
Show Tuning  
Prompt  
Until “TUNE OFF” is shown on  
lower display.  
6
7
Lower  
Display  
Initiate Tuning  
Select “DO SLOW” or “DO FAST”  
in lower display.  
Tuning in operation  
Upper display will show a “T” as  
long as ACCUTUNE process is  
operating. When process  
Lower  
Display  
completes, tuning parameters are  
calculated and lower display will  
show “NO TUNE” prompt.  
74  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4.5.4 Using BLENDED TUNE at start-up for Duplex (Heat/Cool)  
When DUPLEX has been configured for DISABLE. This is the preferred selection  
for Heat/Cool applications which use a highly insulated chamber (a chamber which  
will lose heat very slowly unless a cooling device is applied). Only one local setpoint  
(LSP 1) is needed for this selection.  
This selection results in performance tuning over the full range utilizing both Heat  
and Cool outputs to acquire blended tune values that are then applied to both Heat and  
Cool tuning parameters. Both PID sets are set to the same values.  
Table 4-7 Procedure for Using BLENDED TUNE at Start-up for Duplex Control  
Step  
1
Operation  
Press  
Result  
Configure LSP1  
Until SP (Local Setpoint 1) shows  
in the lower display.  
Lower  
Display  
Until the Setpoint is to the desired  
value.  
2
3
or  
Switch to  
“Automatic” Mode  
Until the “A” indicator is lighted (on  
controllers with Manual option).  
Man  
Auto  
Show Tuning  
Prompt  
Until “TUNE OFF” is shown on  
lower display.  
4
Lower  
Display  
Initiate Tuning  
Select “DO SLOW” or “DO FAST”  
in lower display.  
5
6
Tuning in operation  
Upper display will show a “T” as  
long as ACCUTUNE process is  
operating. When process  
Lower  
Display  
completes, tuning parameters are  
calculated and lower display will  
show “NO TUNE” prompt.  
4.5.5 Using MANUAL TUNE at start-up for Duplex (Heat/Cool)  
When DUPLEX has been configured for MANUAL. This selection should be used  
when tuning is needed only for the HEAT zone or only for the COOL zone but not  
both. If Local Setpoint 1 is used, then the controller will perform a HEAT zone tune.  
If Local Setpoint 2 is used, then the controller will perform a COOL zone tune.  
Table 4-8 Procedure for Using MANUAL TUNE for Heat side of Duplex Control  
Step  
1
Operation  
Press  
Result  
Configure LSP1  
Until SP (Local Setpoint 1) shows  
in the lower display.  
Lower  
Display  
Until LSP1 is a value within the  
Heat Zone (output above 50%).  
2
3
or  
Switch to  
“Automatic” Mode  
Until the “A” indicator is lighted (on  
controllers with Manual option).  
Man  
Auto  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Step  
4
Operation  
Press  
Result  
Show Tuning  
Prompt  
Until “TUNE OFF” is shown on  
lower display.  
Lower  
Display  
Initiate Tuning  
Select “DO SLOW” or “DO FAST”  
in lower display.  
5
6
Tuning in operation  
Upper display will show a “T” as  
long as ACCUTUNE process is  
operating. When process  
Lower  
Display  
completes, tuning parameters are  
calculated and lower display will  
show “NO TUNE” prompt.  
Table 4-9 Procedure for Using MANUAL TUNE for Cool side of Duplex Control  
Step  
1
Operation  
Press  
Result  
Configure LSP2  
Until 2SP (Local Setpoint 2) shows  
in the lower display.  
Lower  
Display  
Until LSP2 is a value within the  
Cool Zone (output below 50%).  
2
3
or  
Switch to  
“Automatic” Mode  
Until the “A” indicator is lighted (on  
controllers with Manual option).  
Man  
Auto  
Show Tuning  
Prompt  
Until “TUNE OFF” is shown on  
lower display.  
4
Lower  
Display  
Initiate Tuning  
Select “DO SLOW” or “DO FAST”  
in lower display.  
5
6
Tuning in operation  
Upper display will show a “T” as  
long as ACCUTUNE process is  
operating. When process  
Lower  
Display  
completes, tuning parameters are  
calculated and lower display will  
show “NO TUNE” prompt.  
76  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.5.6 Error Codes  
Table 4-10 Procedure for Accessing Accutune Error Codes  
Step  
1
Operation  
Press  
Result  
Select Accutune  
Set-up Group  
Upper Display = SETUP  
Setup  
Lower Display = ACCUTUNE  
Go to Error Code  
Prompt  
2
Upper Display = (an error code)  
Function  
Lower Display = AT ERROR  
fixes.  
Table 4-11 Accutune Error Codes  
Error Code  
(Upper Display)  
Definition  
Fix  
The Accutune process is still active (Read Only)  
None  
RUNNING  
ACCUTUNE RUNNING  
NONE  
NO ERRORS OCCURRED  
DURING LAST ACCUTUNE  
PROCEDURE  
PROCESS IDENTIFICATION  
FAILURE  
ID FAIL  
Illegal Values  
– try Accutune again.  
Autotune has aborted  
because an illegal value of  
GAIN, RATE, or reset was  
calculated.  
untunable process -- contact local application  
engineer.  
Try Accutune again  
ABORT  
CURRENT ACCUTUNE  
PROCESS ABORTED  
caused by the following  
conditions:  
a. Operator changed to  
Manual mode  
b. Digital Input detected  
c. In Heat region of output  
and a Cool output calculated  
or vice versa.  
Enable LSP2 and configure the desired LSP1 and  
LSP2 setpoints.  
SP2  
LSP2 not enabled or LSP1 or  
LSP2 not in use (only applies  
to Duplex Tuning)  
Aborting Accutune  
To abort Accutune and return to the last previous operation (SP or output level), press  
MAN-AUTO key to abort the Accutune process or increment from the “DO SLOW” or  
“DO FAST” prompt to the “TUNE OFF” prompt.  
Completing Accutune  
When Accutune is complete, the calculated tuning parameters are stored in their  
proper memory location and can be viewed in the TUNING Set up Group, and the  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
controller will control at the local setpoint using these newly calculated tuning  
constants.  
4.6 Fuzzy Overshoot Suppression  
Introduction  
Fuzzy Overshoot Suppression minimizes Process Variable overshoot following a  
setpoint change or a process disturbance. This is especially useful in processes which  
experience load changes or where even a small overshoot beyond the setpoint may  
result in damage or lost product.  
How it works  
The Fuzzy Logic in the controller observes the speed and direction of the PV signal as  
it approaches the setpoint and temporarily modifies the internal controller response  
action as necessary to avoid an overshoot. There is no change to the PID algorithm,  
and the fuzzy logic does not alter the PID tuning parameters. This feature can be  
independently Enabled or Disabled as required by the application to work with the  
Accutune algorithm. Fuzzy Tune should not be enabled for processes that have an  
appreciable amount of deadtime.  
Configuration  
To configure this item, refer to Section 3 - Configuration:  
Set Up Group “ACCUTUNE”  
Function Prompt “FUZZY”  
Select “ENABLE” or “DISABLE” - Use  
or  
.
78  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
5 Troubleshooting/Service  
5.1 Background Tests  
The UDC3200 performs ongoing background tests to verify data and memory integrity. If  
there is a malfunction, a diagnostic message will be displayed (blinking) in the lower  
display. In the case of simultaneous malfunctions, the messages will appear in sequence in  
the lower display.  
Diagnostic messages may be suppressed (stop the blinking) by pressing the RUN/HOLD  
key. The messages will still be available for viewing by pressing the LOWER DISPLAY  
key.  
Table 5-1 Background Tests  
Lower  
Reason for Failure  
How to Correct the Problem  
Display  
Unable to write to non-volatile memory.  
Anytime you change a parameter and it is  
not accepted, you will see E FAIL.  
1. Check the accuracy of the parameter and re-enter.  
2. Try to change something in configuration.  
EE FAIL  
3. Run through Read STATUS tests to re-write to  
EEPROM.  
This error message shows whenever the  
controller goes into a failsafe mode of  
operation. This will happen if:  
• RAM test failed  
1. Run through STATUS check to determine the  
reason for the failure.  
FAILSAFE  
2. Press the SET UP key until STATUS appears in  
the lower display.  
• Configuration test failed  
• Calibration test failed  
• Burnout configured for none and  
the input failed.  
3. Press the FUNCTION key to see whether the tests  
pass or fail, then run through the STATUS codes a  
second time to see if the error cleared.  
Input 1 out of range. The process input is  
outside the range limits.  
1. Make sure the range and actuation are configured  
properly.  
INP1 RNG  
INP1FAIL  
2. Check the input source.  
3. Restore the factory calibration.  
4. Field calibrate.  
Two consecutive failures of input 1  
integration; i.e., cannot make analog to  
digital conversion. This will happen if:  
• Upscale or Downscale burnout is  
selected and the input is open  
1. Make sure the actuation is configured correctly.  
See Section 3 - Configuration.  
2. Make sure the input is correct and that it has not  
burned-out (opened).  
3. Check for gross over-ranging with a multimeter.  
4. Restore factory calibration.  
• Input not configured correctly for the  
sensor being used  
• Input source is grossly out of range.  
Input 2 out of range. The remote input is  
outside the range limits.  
Same as INP1RNG above.  
Same as INP1FAIL above.  
INP2 RNG  
INP2FAIL  
Two consecutive failures of input 2  
integration. i.e., cannot make analog to  
digital conversion.  
• PV low limit is > PV high limit  
• SP low limit is > SP high limit  
• Output low limit > Output high limit  
1. Check the configuration for each item and  
reconfigure if necessary.  
CONF ERR  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Lower  
Reason for Failure  
How to Correct the Problem  
Display  
PV out of range.  
PV = INP1 x RATIO1+ INP1 BIAS  
1. Make sure the input signal is correct.  
PV LIMIT  
2. Make sure the Ratio and Bias settings are correct.  
3. Recheck the calibration. Use Bias of 0.0  
1. Make sure the input signal is correct.  
The result of the formula shown below is  
beyond the range of the remote variable.  
RV LIMIT  
2. Make sure the Ratio2 and Bias2 settings are  
correct.  
RV = INP2 X RATIO + BIAS  
3. Recheck the calibration. Use a Ratio2 of 1.0 and a  
Bias2 of 0.0.  
Setpoint Program start segment number is Check SP Program configuration, subsection 3.4 Set  
SEGERR  
less than ending segment number.  
up Group SPPROG function prompts “STRSEG” and  
“ENDSEG”.  
Slidewire calibration never performed.  
Field Calibrate the slidewire.  
CAL MTR  
SW FAIL  
SOOTING  
Position Proportional slidewire input failure. Check the slidewire.  
Check process for correct operation.  
Percent Carbon falls outside sooting  
boundary  
Thermocouple on Input x (1 or 2) is  
starting to burnout.  
This diagnostic message means that the controller  
has detected that the thermocouple is starting to  
burnout. This error message may also be created if  
the resistance of the wires used to connect the  
thermocouple to the instrument is above 100 ohms.  
TCx WARN  
The Thermocouple on Input x (1 or 2) is in This diagnostic message means that the controller  
TCxFAIL  
imminent danger of burning out.  
has detected that the thermocouple will soon fail. User  
should consider replacing the thermocouple as soon  
as possible. This message will also be generated if the  
resistance of the wires used to connect the  
thermocouple to the instrument is above 180 ohms.  
Current Output is less than 3.5 mA.  
Auxiliary Output is less than 3.5 mA.  
The current output is open circuit. Check the field  
wiring.  
CURFAIL  
AXFAIL  
The auxiliary output is open circuit. Check the field  
wiring.  
80  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.2 Controller Failure Symptoms  
Upper  
Display  
Lower  
Display  
Indicators  
Controller  
Output  
Probable  
Cause  
Blank  
OK  
Blank  
Off  
OK  
None  
Power Failure  
Current  
Proportional Output  
Displayed  
Output  
disagrees  
with Controller  
Output  
Controller  
Output  
disagrees  
with Displayed  
Output  
OK  
OK  
Position  
Proportional or  
TPSC Output  
OK  
OK  
OK  
OK  
OK  
OK  
Time Proportional  
Output  
Current/Time  
Proportional Output  
OK  
External Alarm  
function does  
not operate  
properly  
Malfunction in  
alarm output  
Display does not change when a key is pressed  
Keyboard  
Malfunction  
Controller fails to go into “Slave” operation during communications  
Communications  
Failure  
Controller  
Auxiliary Output  
disagrees  
with Displayed  
Auxiliary Output  
OK  
Displayed  
Output  
disagrees with  
Auxiliary Output  
OK  
Auxiliary Output  
Other symptoms  
If a set of symptoms or prompts other than the one you started with appears while  
troubleshooting, re-evaluate the symptoms. This may lead to a different  
troubleshooting procedure.  
If the symptom still persists, refer to the installation section in this manual to ensure  
proper installation and proper use of the controller in your system.  
04/08  
UDC3200 Universal Digital Controller Operator Manual  
81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
6 Sales and Service  
For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor,  
contact one of the offices below.  
ARGENTINA  
140 21 Prague 4  
Czech Republic  
Tel. : 42 2 6112 3434  
HONEYWELL BV  
Laaderhoogtweg 18  
1101 EA AMSTERDAM  
ZO  
4 th Floor Administrative  
Builiding of AO "Luzhniki"  
Management  
Honeywell S.A.I.C.  
Belgrano 1156  
Buenos Aires  
24 Luzhniki  
Argentina  
Tel. : 54 1 383 9290  
THE NETHERLANDS  
Tel : 31 20 56 56 911  
119048 Moscow  
RUSSIA  
Tel : 7 095 796 98 00/01  
DENMARK  
HONEYWELL A/S  
Automatikvej 1  
DK 2860 Soeborg  
DENMARK  
ASIA PACIFIC  
Honeywell Asia  
Pacific Inc.  
Room 3213-3225  
Sun Kung Kai Centre  
N° 30 Harbour Road  
Wanchai  
NORWAY  
HONEYWELL A/S  
Askerveien 61  
PO Box 263  
N-1371 ASKER  
NORWAY  
SLOVAKIA  
Tel. : 45 39 55 56 58  
HONEYWELL Ltd  
Mlynske nivy 73  
PO Box 75  
820 07 BRATISLAVA 27  
SLOVAKIA  
FINLAND  
HONEYWELL OY  
Ruukintie 8  
Tel. : 47 66 76 20 00  
Hong Kong  
Tel. : 852 829 82 98  
Tel. : 421 7 52 47 400/425  
FIN-02320 ESPOO 32  
FINLAND  
POLAND  
Tel. : 358 0 3480101  
HONEYWELL Sp.z.o.o  
UI Domaniewksa 41  
02-672 WARSAW  
POLAND  
SPAIN  
HONEYWELL S.A  
Factory  
Josefa Valcarcel, 24  
28027 MADRID  
SPAIN  
AUSTRALIA  
Honeywell Limited  
5 Thomas Holt Drive  
North Ryde Sydney  
Nsw Australia 2113  
Tel. : 61 2 353 7000  
FRANCE  
HONEYWELL S.A.  
Bâtiment « le Mercury »  
Parc Technologique de St  
Aubin  
Tel. : 48 22 606 09 00  
Tel. : 34 91 31 3 61 00  
PORTUGAL  
Route de l’Orme  
(CD 128)  
91190 SAINT-AUBIN  
FRANCE  
Tel. from France:  
01 60 19 80 00  
From other countries:  
33 1 60 19 80 00  
HONEYWELL  
AUSTRIA  
Honeywell Austria  
G.M.B.H.  
Handelskai 388  
A1020 Vienna  
Austria  
PORTUGAL LDA  
Edificio Suecia II  
Av. do Forte nr 3 - Piso 3  
2795 CARNAXIDE  
PORTUGAL  
SWEDEN  
HONEYWELL A.B.  
S-127 86 Skarholmen  
STOCKHOLM  
SWEDEN  
Tel. : 46 8 775 55 00  
Tel. : 351 1 424 50 00  
Tel. : 43 1 727 800  
REPUBLIC OF IRELAND SWITZERLAND  
BELGIUM  
GERMANY  
HONEYWELL  
Unit 1  
HONEYWELL A.G.  
Hertistrasse 2  
Honeywell S.A.  
3 Avenue De Bourget  
B-1140 Brussels  
Belgium  
HONEYWELL AG  
Kaiserleistrasse 39  
D-63067 OFFENBACH  
GERMANY  
Robinhood Business  
Park  
8304 WALLISELLEN  
SWITZERLAND  
Robinhood Road  
DUBLIN 22  
Tel. : 41 1 831 02 71  
Tel. : 32 2 728 27 11  
Tel. : 49 69 80 64444  
Republic of Ireland  
Tel. : 353 1 4565944  
TURKEY  
BRAZIL  
HONEYWELL DO  
Brazil  
And Cia  
Rua Jose Alves Da  
Chunha  
Lima 172  
Butanta  
05360.050 Sao Paulo  
Sp  
Brazil  
HUNGARY  
HONEYWELL Kft  
Gogol u 13  
H-1133 BUDAPEST  
HUNGARY  
Tel. : 36 1 451 43 00  
HONEYWELL A.S.  
Caryiryolu Sok No. 7  
Ucgen Plaza, Kat 5-6-7  
Icerenkoy 81120 Instanbul  
Turkey  
REPUBLIC OF  
SINGAPORE  
HONEYWELL PTE LTD  
BLOCK 750E CHAI  
CHEE ROAD  
Tel (90-216) 575 66 00  
ICELAND  
06-01 CHAI CHEE IND.PARK UNITED KINGDOM  
HONEYWELL  
Hataekni .hf  
Armuli 26  
PO Box 8336  
128 reykjavik  
Iceland  
1646 SINGAPORE  
REP. OF SINGAPORE  
Tel. : 65 2490 100  
HONEYWELL  
Honeywell House  
Arlington Business Park  
Bracknell,  
Berkshire  
RG12 1EB  
Tel. : 55 11 819 3755  
REPUBLIC OF SOUTH  
AFRICA  
BULGARIA  
HONEYWELL EOOD  
14, Iskarsko Chausse  
POB 79  
BG- 1592 Sofia  
BULGARIA  
Tel : 359-791512/  
794027/ 792198  
CANADA  
Honeywell Limited  
The Honeywell Centre  
300 Yorkland Blvd.  
Toronto, Ontario  
M2j 1s1  
Tel : 354 588 5000  
Tel: +44 (0) 1344 656000  
HONEYWELL  
Southern Africa  
PO BOX 138  
Milnerton 7435  
REPUBLIC OF SOUTH  
AFRICA  
ITALY  
U.S.A.  
HONEYWELL S.p.A.  
Via P. Gobetti, 2/b  
20063 Cernusco Sul  
Naviglio  
ITALY  
Tel. : 39 02 92146 1  
HONEYWELL INC.  
INDUSTRIAL PROCESS  
CONTROLS  
1100 VIRGINIA DRIVE  
PA 19034-3260  
FT. WASHINGTON  
U.S.A.  
Tel. : 27 11 805 12 01  
ROMANIA  
HONEYWELL Office  
Bucharest  
147 Aurel Vlaicu Str.,  
Sc.Z.,  
Apt 61/62  
R-72921 Bucharest  
ROMANIA  
Tel : 40-1 211 00 76/  
211 79  
Tel. : 1-800-343-0228  
MEXICO  
HONEYWELL S.A. DE  
CV  
AV. CONSTITUYENTES  
900  
COL. LOMAS ALTAS  
11950 MEXICO CITY  
MEXICO  
VENEZUELA  
Canada  
Tel.: 800 461 0013  
Fax:: 416 502 5001  
HONEYWELL CA  
APARTADO 61314  
1060 CARACAS  
VENEZUELA  
CZECH REPUBLIC  
HONEYWELL,  
Spol.S.R.O.  
Tel. : 58 2 239 021  
Tel : 52 5 259 1966  
RUSSIA  
HONEYWELL INC  
Budejovicka 1  
THE NETHERLANDS  
82  
UDC3200 Universal Digital Controller Operator Manual  
04/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Download from Www.Somanuals.com. All Manuals Search And Download.  
Honeywell Process Solutions  
512 Virginia Drive  
Fort Washington, PA 19034  
51-52-25-143 Rev. 1 0408 Printed in USA  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Inc Paint Sprayer 231 353 User Manual
Grizzly Sander H3140 User Manual
Harbor Freight Tools Grinder 95504 User Manual
Hasbro Robotics 83807 User Manual
Hearth and Home Technologies Universal Remote SMART STAT II User Manual
Heat Glo LifeStyle Indoor Fireplace BE 41 User Manual
HP Hewlett Packard Projector ep9010 User Manual
HP Hewlett Packard Server ProLiant Plus User Manual
HP Hewlett Packard Tablet Accessory HP Kayak XM600 User Manual
Ice O Matic Ice Maker ICE0250 Series User Manual