Greenheck Fan Ventilation Hood GGH20 User Manual

Part #473380  
Grease Grabber™ H O  
2
®
Auto-Cleaning Hood  
Installation,OperationandMaintenanceManual  
Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the  
product described. Protect yourself and others by observing all safety information. Failure to comply with instructions  
could result in personal injury and/or property damage! Retain instructions for future reference.  
Model GGH2O  
General Safety Information  
Only qualified personnel should install this unit.  
Personnel should have a clear understanding of these  
instructions and should be aware of general safety  
precautions. Improper installation can result in electric  
shock, possible injury due to coming in contact with  
moving parts, as well as other potential hazards. Other  
considerations may be required if seismic activity  
is present. If more information is needed, contact a  
licensed professional engineer before moving forward.  
1. Follow all local electrical and safety codes, as well  
as the National Electrical Code (NEC), the National  
Fire Protection Agency (NFPA), where applicable.  
Follow the Canadian Electric Code (CEC) in  
Canada.  
DANGER  
Always disconnect power before working on or  
near a unit. Lock and tag the disconnect switch or  
breaker to prevent accidental power up.  
CAUTION  
When servicing the unit, motor may be hot enough  
to cause pain or injury. Allow motor to cool before  
servicing.  
Model GGH20 Grease Grabber Auto-Cleaning Hood  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
®
Table of Contents  
Grease Grabber™ H2O System  
Function  
Greenheck GGH2O hoods are designed for three  
primary functions:  
Grease Grabber™ H O System Function.................... 3  
2
Cleaning Cycle  
Manual and Automatic Engagement........................ 4  
Fire Mode...................................................................... 4  
System Components  
• Capture and contain the effluent produced by the  
cooking process.  
• Remove grease and other contaminants from the  
airstream with two stages of mechanical filters  
(Primary Grease X-Tractor filters and secondary  
Grease Grabber filters).  
Hood .......................................................................... 5  
Grease Grabber H O Control Cabinet...................... 5  
2
Graphic Keypad ........................................................ 5  
Unpacking..................................................................... 6  
Hood Widths and Base Weights.................................. 6  
Installation Overview  
• Wash the filters and other surfaces within the  
exhaust plenum to remove contaminants.  
Filler Panels............................................................... 7  
Back Supply Plenum................................................. 7  
Hood Hanging Height................................................ 8  
Double Island Style ................................................... 8  
Installing U-Channel Strip...................................... 8  
Continuous Capture Plenum ................................. 8  
Ductwork ................................................................... 9  
External Supply Plenums.....................................9-10  
Supply Plenum Clip ............................................... 9  
Uni-Strut............................................................... 10  
Threaded Rod ...................................................... 10  
Supply Duct Collar .................................................. 10  
UL Listed Fastener.................................................. 11  
Back Supply Plenum..........................................11-12  
Supply Duct Collar............................................... 11  
Hanging the Back Supply Plenum .................11-12  
Hanging the Hood................................................ 12  
Air Diffusers............................................................. 12  
Enclosure Panels..................................................... 13  
End Skirts ................................................................ 13  
Backsplash Panels.................................................. 14  
Duct Collar............................................................... 15  
Plumbing  
NOTE  
The wash sequence of the hood is not designed for  
fire suppression and will not engage in the event of  
a fire.  
NOTE  
The functions listed above require the control center  
to be wired to the exhaust fan(s) and the hood  
plumbed.  
NOTE  
For a complete list of functions, please refer to the  
sequence of operations.  
Normal Exhaust Operation and  
Contaminant Collection  
The system’s exhaust fan is manually controlled by  
a press-button switch (FAN ON/OFF) on the graphic  
keypad (included with hood). The exhaust system  
operates until the FAN ON/OFF button is pressed. The  
wash cycle can be manually engaged to run on a pre-  
programmed control sequence by pressing the CLEAN  
HOOD button or automatically engaged to run at the  
same time each day through a programmable timer.  
Pump Installation .................................................... 16  
Connections ............................................................ 16  
Detergent Tank........................................................ 17  
Electrical  
Wiring....................................................................... 17  
Timer Programming – 24 Hour / 7 Day  
Programming / Operation....................................... 18  
Initial System Start-Up............................................... 19  
Sequence of Operation .............................................. 20  
Airflow Testing Procedure.......................................... 21  
Wiring Schematic  
Amerex®.................................................................. 22  
Ansul® ..................................................................... 23  
Wiring Diagram........................................................ 24  
Maintenance  
Filters....................................................................... 25  
Floats....................................................................... 25  
Troubleshooting.......................................................... 26  
Replacement Parts..................................................... 26  
Grease Grabber H O Start-Up Checklist................... 27  
2
Maintenance Log...........................................Backcover  
Warranty.........................................................Backcover  
Model GGH2O  
3
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Cleaning Cycle  
Manual Engagement  
The wash function is triggered by pressing the Clean  
Hood button after the exhaust fans are shut down at  
the end of each day’s cooking operations (pressing  
the Fans On/Off button).  
Fire Mode  
In the event of a fire, the hood exhaust fan(s) will turn  
on at full power and the supply fan will turn off (default  
setting controlled by others) regardless of current fan  
operation. If the hood is in a wash cycle, the hood will  
drain and the fans will turn on.  
Hot water and detergent will fill the hood reservoir.  
The soapy water will then be cycled through the hood  
by the attached recirculation pump, cleaning both the  
filter banks and the exhaust plenum area on a timed  
cycle.  
NOTE  
The wash sequence of the hood is not designed for  
fire suppression and will not engage in the event of  
a fire.  
When the cleaning cycle is complete, the water  
is purged from the reservoir by the pump and the  
reservoir will again fill with clean hot water.  
A rinse cycle will then run on a timed cycle and the  
water will again be purged by the pump.  
When the cycle is complete, the controller runs the  
exhaust fans briefly to remove steam and excess  
moisture from the exhaust system.  
Automatic Engagement  
The hood is equipped with an automatic timer. The  
timer will automatically initiate the wash sequence  
at the programmed time each day. All other washing  
functionality will be the same as the manual  
engagement sequencing.  
Model GGH2O  
4
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Graphic Keypad  
System Components  
The graphic keypad is the interface between the  
control functions of the GGH2O hood and the user.  
This keypad is typically mounted on the Grease  
Hood  
The hood is shipped from the factory pre-piped and  
ready to install. All wash components within the hood  
are complete and ready for connection to hot water,  
sanitary sewer drain and the electrical sources. Wiring  
from the control panel to the hood (for lights) is by  
Greenheck. All plumbing and wiring must conform to  
plumbing and electrical codes. Duct collars are factory  
mounted unless specified otherwise.  
Grabber H O control cabinet, but can also be shipped  
2
loose for remote mounting. The keypad consists  
of three main buttons: hood lights, fan on/off and  
clean hood. The keypad also has system fault and fill  
detergent indicator lights to alert of any fault in the  
system or when the detergent tank is low.  
NOTE  
HOOD  
LIGHTS  
FAN  
ON/OFF  
HOOD  
LIGHTS  
FAN  
ON/OFF  
Filters are shipped loose with the hood and installed  
in the field. See page 25 for installation details.  
FAN  
100%  
CLEAN  
HOOD  
CLEAN  
HOOD  
Grease Grabber H O Control Cabinet  
2
FILL  
DETERGENT  
SYSTEM  
FAULT  
FILL  
DETERGENT  
SYSTEM  
FAULT  
The control cabinet contains all of the water and  
electrical components, and connections including  
the Programmable Logic Controller (PLC), that  
controls the wash sequencing and operations. The  
control cabinet also includes the detergent reservoir,  
detergent pump, recirculation pump, solenoid valves  
and other water piping.  
After pressing “CLEAN HOOD”, Fans will automatically stop.  
472619  
After pressing “CLEAN HOOD”, Fans will automatically stop.  
472620  
In case of emergency, the wash cycle can be stopped by pressing “CLEAN HOOD”.  
In case of emergency, the wash cycle can be stopped by pressing “CLEAN HOOD”.  
GGH2O Keypad  
GGH2O and Vari-Flow Keypad  
NOTE  
If the GGH2O is being used with the Vari-Flow Air  
Management system, there will be an additional  
FAN 100% button for sending fan speeds to 100%.  
For detailed information on the Vari-Flow Air  
Management system, please refer to the Greenheck  
NOTE  
The recirculation pump is shipped loose with the  
hood. See pages 16 for installation details.  
LIGHTS  
LUCES  
FANS  
100%  
RESET  
VENTILADORES  
CLEAN  
HOOD  
CLEAN  
FAULT  
SETUP  
FILL  
SYSTEM  
FAULT  
DETERGENT  
HOOD  
After pressing “CLEAN HOOD”, Fans will automatically stop.  
In case of emergency, the wash cycle can be stopped by pressing “CLEAN HOOD”.  
Listed 33  
x
7
Melink Customer Service USA: 877-477-4190  
GGH2O and Melink® Intelli-Hood® Keypad  
NOTE  
If the GGH2O is being used with the Melink Intelli-  
Hood system, there will be two keypads. The Melink  
Keypad will control the fans and lights. The GGH2O  
Keypad will control the wash system.  
NOTE  
For information on PLC programming, please  
consult the factory.  
Model GGH2O  
5
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unpacking  
Hood Width and Base Weights  
Front Lifting  
Skid  
Base Weight  
Base Weight  
Hood Width  
without Water  
with Water  
inches  
lbs.  
lbs.  
(cm)  
(kg)  
(kg)  
Remove side, back  
and top lumber.  
Remove 3-inch  
lag screws while  
holding the front  
lifting skid in place.  
48  
(121.92)  
440  
(199.58)  
488  
(221.35)  
51  
(129.54)  
449  
(203.66)  
497  
(225.44)  
54  
(137.16)  
457  
(207.29)  
505  
(229.06)  
57  
(144.78)  
465  
(210.92)  
513  
(232.69)  
Profile of Hood  
60  
474  
522  
(152.40)  
(215.00)  
(236.78)  
63  
483  
531  
(160.02)  
(219.09)  
(240.86)  
66  
(167.64)  
491  
(222.71)  
539  
(244.49)  
When front lifting  
skid is detached,  
position it in front  
of bottom skid.  
69  
(175.26)  
499  
(226.34)  
547  
(248.12)  
72  
508  
556  
(182.88)  
(230.43)  
(252.20)  
Base weight is based on 48 inches (121.92 cm) hood  
length. For each additional foot of hood in length, add  
55 lb/ft (24.95 kg/m) in weight of hood and 67 lb/ft  
(30.39 kg/m) in weight of hood filled with water.  
Profile of Hood  
Example of a 10 foot hood:  
Dry:  
48 inch width x 120 inch length  
= 440 lbs. + (6 ft. x 55 lb/ft)  
= 440 lbs. + 330 lbs.  
= 770 lbs.  
Carefully rotate  
the hood as  
shown.  
With Water: 48 inch width x 120 inch length  
= 488 lbs. + (6 ft. x 67 lb/ft)  
= 488 lbs. + 402 lbs.  
= 890 lbs.  
Profile of Hood  
DANGER  
The maximum weight (weight with water) should be  
used for the maximum weight of the hood to ensure  
the ceiling structure can support the weight of the  
hood when filled with water.  
Carefully slide the  
hood onto the lifting  
skid. The lifting skid  
should be used to lift  
the hood into its final  
position. If the lifting  
skid is not used,  
CAUTION  
To ensure proper structural support, all hanger  
brackets must be used for hanging the hood.  
the hood will be  
damaged during the  
installation process.  
Profile of Hood  
Model GGH2O  
6
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Overview  
NOTE  
Filler Panels  
1. Unpack the hood and lay it on the lifting skid.  
If you have a Back Supply Plenum (BSP), this must  
be installed before the hood. Refer to page 11 for  
instructions on installing the BSP.  
2. Bolt the filler panels together with 5/16 in. bolts  
provided in the hardware package.  
NOTE  
All hanger brackets must be used and the hood  
must be properly supported while lifting to prevent  
damage or distortion to the hood. The hood must be  
hung level to operate properly.  
3. Position the filler panels to the hood back, and  
tack-weld them into place.  
4. To allow for ease of cleaning, caulk the external  
seams with NSF Approved silicone caulk  
(GE SCS1000, or its equivalent). The caulk is not  
provided.  
After the hood is secured, make the exhaust duct  
connections. The fire system distributor must be  
contacted at this time. After the fire system has been  
installed, mount the enclosures, then the supply  
plenums. If an Horizontal Supply Plenum is provided,  
it should be installed before the enclosures. The hood  
and accessories are now installed.  
Hood  
Hood  
Finally, make the electrical connections from the  
controls to the fans and complete the fire system  
circuits as required by the job specification (job  
specific wiring diagram located inside the cabinet  
cover).  
Hood  
Right Filler Panel  
Tack-welded to  
hood back  
Bottom Filler Panel  
5/16 inch x 3/4 inch bolts  
with washers and nuts  
Model GGH2O  
7
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hood Hanging Height  
NOTE  
The hood hanging height is critical. Hanging the hood  
at the incorrect height may significantly reduce the  
ability for the hood to function properly and may be in  
violation of codes. The hood hanging height (typically,  
78 in. (198.12 cm) above the finished floor) is given on  
the UL label located on the inside of the hood on the  
end panel. The hood must be hung level to operate  
properly.  
The installation of the canopy hoods shall be  
in accordance with NFPA 96 (latest edition),  
Standard for Ventilation Control & Fire Protection of  
Commercial Cooking Operations.  
NOTE  
Greenheck does not recommend walking or  
standing on the hood top as damage can result. If  
you must walk on the hood top, protect the hood  
with additional support or planks for flooring.  
NOTE  
Before hanging the hoods, please verify the hood  
marks to make sure the correct hood is hung on the  
correct side.  
Continuous Capture Plenum Hoods  
Remove the support angles on the open end panels.  
Use the installation procedure described for single  
island hoods; install and level both hoods. After  
leveling, secure the hoods together by tack-welding  
and/or bolting the top angles. Fasten the hoods  
together using u-clips and bolts. Caulk this joint with  
NSF Approved silicone caulk (GE SCS1000 or its  
equivalent). The caulk is not provided.  
Double Island Style Hoods  
A double island hood is created by installing two  
wall style hoods back to back. Use the installation  
procedure for single island hoods; install and level  
both hoods. After leveling, secure the hoods together  
by tack-welding and/or bolting the rear mounting  
brackets. Caulk this joint with NSF Approved silicone  
caulk (GE SCS1000 or its equivalent). The caulk is not  
provided.  
Installing U-Channel Strip  
1. After the hood is hung in position and leveled,  
apply caulk to the inside edge of the double island  
clip.  
2. Position and install the clip by tapping into  
position along clip (friction fit).  
Hood  
3. Caulk edges to seal out grease and allow for ease  
of cleaning. Caulk with NSF Approved silicone  
caulk, GE SCS1000, or its equivalent. The caulk is  
not provided.  
Caulk  
U-Clip  
Bolt  
Acorn Nut  
NOTE  
For multiple hood systems that have more than  
14 lights total (incandescent or fluorescent), the  
hood lights must be wired to multiple circuits.  
Each circuit must have less than 14 lights total.  
Hood-1A  
Hood-1B  
• Light bulbs are not provided. Standard light bulbs  
up to 100 watts may be used.  
Double Island Clip  
Silicone Caulk  
Double Island Clip  
Model GGH2O  
8
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ductwork  
Installing External Supply Plenums  
Exhaust  
Option #2  
Uni-Strut supplied by others  
As specified in NFPA 96, Ch. 7.5 (latest edition),  
exhaust duct systems must be constructed in the  
following manner:  
TOP VIEW  
HOOD  
Materials: Ducts shall be constructed of and  
supported by carbon steel not less than 1.37 mm  
(0.054 in.) (No. 16 MSG) in thickness or stainless steel  
not less than 1.09 mm (0.043 in.) (No. 18 MSG)  
in thickness.  
Option #1  
For plenums < than or = 96 inches  
Two (2) clips are needed.  
For plenums > than 96 inches  
Three (3) clips are needed.  
UTILITY  
CABINET  
The third clip is located in the  
center of the plenum length.  
Installation: All seams, joints, penetrations, and duct  
to hood collar connections shall have a liquid-tight  
external weld. If you have an Automatic Fire Damper  
please refer to that manual for installation instructions  
now.  
Option #1  
Attach hanging clip to hood  
standing seam with the  
supplied ‘C’ clamps.  
Optional: Drill and bolt a  
1/4-20 SS bolt through the  
clip and hood standing seam  
Supply  
Supply ductwork (where applicable) should be  
connected to the hood in a manner approved by the  
local code authorities.  
11.5  
TOP VIEW  
For proper installation of duct collars when they are  
shipped unattached see Installing Duct Collars on  
page 10.  
23.5  
SUPPLY PLENUM  
Hanger Bracket  
NOTE  
Option #1  
For hoods with fire dampers in the exhaust and  
supply duct collars, an access panel for cleaning  
and inspection shall be provided in the duct. This  
panel shall be as close to the hood as possible but  
should not exceed 18 in. (45.72 cm).  
Hanging clip could be 23.5 inches from end if there is a utility cabinet on the  
end of the hood.  
Using the Supply Plenum Clip - Option #1  
1. Bolt the hanging clip to the supply plenum. Two  
clips are needed for plenums less than 96 in.  
(243.84 cm) long and three for plenums greater  
than 96 in. (243.84 cm). The  
third clip is located in the  
center of the plenum length.  
If there is a utility cabinet,  
the hanging clip should be  
23.5 in. (59.69 cm) from the  
end to the hood.  
Supply Plenum Clip  
2. Using the c-clamps provided, clamp the supply  
plenum hanging clip to the hood standing seam.  
Option: Drill and bolt a 1/4-20 SS bolt through the  
clip and hood standing seam.  
Option #1 : Hanging Clip  
‘C’ Clamp  
Hood Standing Seam  
Hanging Clip bolted to plenum shell  
Hanging Clip  
HOOD FRONT  
SUPPLY PLENUM SHELL  
NOTE  
The supply plenum is provided with plenum clips  
that assist in hanging the plenum. The plenum  
should not be hung only with the plenum clips;  
threaded rod or uni-strut must also be used.  
Model GGH2O  
9
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Using the Uni-Strut - Option #2  
Using the Threaded Rod - Option #3  
1. The uni-strut (supplied by others) that holds the  
hood up cantilevers over the end of the hood and  
is mounted to the supply plenum hanger brackets.  
1. Insert 1/2 in. (12.7 mm) diameter threaded rod (by  
others) into hanger brackets on the supply plenum  
top. Raise and hang the external supply plenum  
from adequate roof or ceiling supports.  
Option #3  
Threaded Rod  
supplied by others  
Threaded Rod  
2. The external supply plenum should be resting  
lightly against the hood. The hood is used to  
position the plenum only, it is not intended to  
support the plenum. All hanger brackets must be  
used and the plenum must be properly supported  
while lifting to prevent damage or distortion. The  
supply plenum must be hung level to operate  
properly.  
Option #2  
The uni-strut (U channel) that holds the hood up,  
cantilevers over the end of the hood and is  
mounted to the Air Curtain Supply Plenum (ASP)  
hanger brackets  
(Optional fastening of supply plenum to hood. See  
directions).  
END VIEW  
3. It is recommended that caulk be applied at the  
mating seams and surfaces of the plenum, the  
hood, and the wall. If the supply plenum is next  
to a wall, you will also need to caulk around the  
surface next to the wall. Caulk the joints with  
NSF Approved silicone caulk (GE SCS1000, or its  
equivalent). The caulk is not provided.  
Hood  
Installing the Supply Duct Collar to the  
Plenum  
1. Place the duct collar(s) over the opening, fastening  
with tack-welds at 1 to 2 in. (2.54 to 5.08 cm)  
intervals, or sheet metal screws at 3 to 6 in.  
(7.62 to 15.24 cm) intervals.  
Variable Supply Plenum  
(HSP or VSP)  
Supply Duct  
Connection  
Supply duct connection to be  
tack-welded with 1 to 2 inch  
tacks or sheet metal screws  
at 3 to 6 inch spacing to hood.  
Air Curtain Supply Plenum  
(ASP)  
External Supply Plenum Weights, Dimensions and Supply Rates  
Length per  
section  
Weight  
Width  
(mm)  
152.4 Variable Variable 3 to 16  
Height  
External Supply  
Plenum Type  
Recommended  
Supply Rate  
(lbs/ft) (kg/ft)  
(in)  
6
(in)  
(mm)  
(ft)  
(m)  
.91 to  
4.88  
145 cfm/ft  
Back Supply  
35.0 15.878  
3
(246.36 m /hr)  
Air Curtain Supply  
• 14 inch  
.91 to  
4.88  
110 cfm/ft  
9.5  
4.31  
5.67  
14  
24  
355.6  
609.6  
10  
10  
254  
254  
3 to 16  
3 to 16  
3
(186.89 m /hr)  
Air Curtain Supply  
• 24 inch  
.91 to  
4.88  
145 cfm/ft  
12.5  
3
(246.36 m /hr)  
0-80 cfm/ft  
curtain  
face  
3
(0-135.92 m /hr)  
.91 to  
4.88  
Variable Supply  
16.0  
14.0  
7.26  
6.35  
12  
12  
304.8  
304.8  
18  
18  
457.20 3 to 16  
457.20 3 to 16  
80-160 cfm/ft  
(135.92 -271.84 m /hr)  
3
.91 to  
4.88  
150 cfm/ft  
Horizontal Supply  
3
(254.85 m /hr)  
Model GGH2O  
10  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. If the back supply plenum is greater than 9 ft.  
10 in. (299.72 cm) long, divide the length of the  
back supply by four. This will give you the center  
of each half. Cut openings at the suggested  
location, centering the duct collar over the center  
measurement of each half.  
Using the UL Listed Fastener Provided  
1. Drill a 9/32 in. hole for the 1/4 in. bolt from the  
inside of the supply plenum to inside the hood.  
Fasteners are to be located max. 6 in. (15.24 cm)  
from the end of the hood with max. spacing  
between bolts 36 in. (91.44 cm)  
DO NOT iNcluDe uTiliTy cabiNeTs Or fillers wheN  
figuriNg bOlT placemeNT.  
DO NOT bOlT The supply pleNum TO a fire/uTiliTy  
cabiNeT.  
L (MODULE LENGTH)  
L/4  
2. Push bolt through hole, attach the washer and nut.  
L/2  
3. Hand tighten; then use a wrench until fully  
tightened. Caulk around bolts from inside of hood  
as necessary.  
L/4  
Hood  
1/4 - 20 UNC - 2A  
SS Bolt  
1/4 inch SS Nut  
SS Flat Washer  
4. Place the duct collar(s) over the opening, fastening  
with screws or tack-welds every 4 to 6 in. (10.16 to  
15.24 cm).  
Installing the Back Supply Plenum  
Installing the Supply Duct Collar  
1. Find the center of the back supply plenum.  
2. If the back supply plenum is less than 9 ft. 10 in.  
(299.72 cm) long, cut opening at the suggested  
location, centering the opening over the center of  
the back supply plenum.  
The 4 in. (10.16 cm)  
high duct collar is to  
be attached to the  
back supply.  
L (MODULE LENGTH)  
L/2  
L/2  
Hanging the Back Supply Plenum  
5. Hang the back supply plenum from the ceiling.  
The back supply plenum needs to be mounted  
31.25 in. (79.375 cm) above the floor (based  
upon a canopy hood that will be hung at 78 in.  
(198.12 cm) above the finished floor. This is  
measured from the lowest rear edge of the back  
supply plenum to the finished floor. Leave 6 to  
10 inches (15.24 to 25.4 cm) of space below the  
plenum for access to the air diffusers.  
Model GGH2O  
11  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Fasten the back supply to the wall, going through  
the lower back supply wall.  
5. Connect the remaining ductwork for the back  
supply and the hood. It is recommended that  
caulk be applied at the mating seams and  
surfaces of the back supply, the hood, and the  
wall.  
• These fasteners are to help maintain the location  
of the Back Supply, and are not intended to hold  
the weight of the back supply unit.  
• The fasteners should not interfere with the  
removable air diffusers.  
Air Diffusers  
The air diffusers, located at the bottom of the back  
supply, will need to be cleaned as often as the  
application dictates. Inspect periodically to determine  
the cleaning schedule.  
• The 31.25 in. (79.375 cm) height is based upon  
the canopy hood hanging height of 78 in.  
(198.12 cm)  
1. To clean the air diffusers, unfasten the screws.  
Remove the air diffusers from the back supply  
unit, and wash in the sink or dishwasher.  
STEP 3  
2. Insert the air diffusers at an angle from the bottom,  
and rotate so the forms are downward. Rest the  
diffuser on the internal angles.  
3. Refasten with the stainless steel screws.  
Fasteners holding the  
back supply to the wall  
31.25 in.  
Critical  
Dimension  
Hanging the Hood  
Before hanging the hood according to the hood  
installation instructions, please check the following:  
1. Make sure the back supply plenum is properly  
secured, as described in steps 5 and 6.  
2. If the ductwork for the back supply plenum will not  
interfere with the hood installation, it should be  
connected now.  
Removable Air Diffusers  
3. Any filler panels should be attached to the hood  
before the hood installation.  
4. Lift the hood, and position it so the filler panels  
are resting lightly on the top outside edges of the  
back supply. The back supply is used to position  
the hood only. It is not intended to hold any hood  
weight.  
Model GGH2O  
12  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing Enclosure Panels  
Installing End Skirts  
Before installing the enclosure panels, make sure  
the hood is hung in position with all the ductwork  
attached, electrical connections and fire system  
connections completed.  
1. After the hood is hung in position, slide the  
hemmed form on top of the end skirt onto the end  
panels of the hood.  
2. Drill a hole in the hood end panel to line up with  
the hole in the end skirt. Attach the end skirt with  
a 1/4 in. bolt and cap nut to the inside of the hood,  
or tack-weld the end skirt to the hood.  
1. Position the end enclosure panels on the hood,  
and clamp into place with clamps provided or  
tack-weld the panels into place.  
2. Fasten the end enclosure panels to the wall,  
method depends on wall construction. (Fasteners  
are not provided).  
3. Position the end skirt against the wall and attach.  
The method depends on the wall construction.  
(Fasteners for this are not provided).  
If the hood is a double island, bolt the end  
enclosure panels together. (Fasteners are not  
provided).  
4. Caulk the internal joint formed by the end skirt and  
the hood end panel with NSF Approved silicone  
caulk (GE SCS1000 or its equivalent). The caulk is  
not provided.  
3. Position the front enclosure panel(s) on the hood,  
and bolt to the end enclosure panels with the  
5/16 in. bolts provided in the hardware package.  
5. To allow for ease in cleaning, also caulk all the  
external seams.  
4. Tack-weld or clamp the front enclosure panel(s)  
to the hood. If clamps are used, they must be  
positioned 4 in. (100 mm) from the ends, and in the  
center of the front enclosure panel.  
5. To allow for ease of cleaning, caulk the external  
seams with NSF Approved silicone caulk  
(GE SCS1000, or its equivalent). The caulk is not  
provided.  
Note: Installation instructions may not be applicable  
for concrete ceilings.  
Exploded  
view  
Bolt panels together with 5/16-inch bolts.  
Supplied by mfg.  
below  
Full End Skirt  
Hemmed Edge  
Clamp panels to hood standing seam with hardware.  
Supplied by mfg.  
Attach to wall  
Fasteners by others  
End Enclosure  
Panel  
Front Enclosure Panel  
Exploded View  
Holes drilled by installer  
End Enclosure  
Panel  
1/4-inch bolt and cap nut  
Supplied by mfg.  
Attach to wall.  
Fasteners by others  
Model GGH2O  
13  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. After the hood is hung in position, slide the flat  
flange of the backsplash panel behind the back of  
the hood.  
Installing Backsplash Panels  
Flat backsplash panel  
Material gauge – Stainless  
Note: If the backsplash panel length is greater  
than 45 in. (114.3 cm), it will be shipped in multiple  
pieces.  
Wall  
2. After the backsplash panel has been positioned,  
drill holes in the panel and fasten to the wall.  
(Fasteners provided by others).  
Heigth  
Note: The holes should be spaced to adequately  
secure the panel to the wall.  
3. Caulk the joints between the hood and the  
backsplash panel with NSF Approved silicone  
caulk (GE SCS1000, or its equivalent). The caulk is  
not provided.  
Length  
4. Caulk the joint between the backsplash panels  
when multiple panels are required, with NSF  
Approved silicone caulk (GE SCS1000, or its  
equivalent). The caulk is not provided.  
NOTE  
Hood Front Panel  
Hood End Panel  
Panels up to 47 inches (119.4 cm) wide ship in one  
piece. Over 47 inches (119.4 cm) in multiple pieces.  
Insulated backsplash panel  
Material gauge – Stainless  
Insulation – 1 inch (25.4 mm)  
1 inch (25.4 mm)  
Wall  
Slide flange  
behind back  
of the hood.  
Height  
Backsplash Panel  
Section view of  
backsplash panel  
overlap  
Holes should be spaced  
to adequately secure the  
panel to the wall studs.  
(Hole spacing and fasteners  
provided by others).  
Length  
NOTE  
Panels up to 45 inches (114.3 cm) wide ship in one  
piece. Over 45 inches (114.3 cm) in multiple pieces.  
Model GGH2O  
14  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing Duct Collar  
Overview of exhaust and supply plenum locations  
TOP VIEW  
Hanger Bracket  
3.0  
Exhaust Plenum  
14.0  
Hood  
Width  
Duct cut out area  
3.0  
Front of Hood  
8.0  
8.0  
Hood Length  
BACK VIEW  
8.0  
1.0  
8.0  
Top of Hood  
12.0  
Exhaust Plenum  
Duct cut out area  
Dimensions are shown in inches.  
1. The exhaust duct connection needs to be located  
within 48 in. (121.92 cm) from the center of the  
hood length to the center of the duct connection.  
2. The exhaust duct connection is to be a continuous  
liquid-tight weld. Weld with a non-ferrous filler  
wire, such as silicon bronze or stainless steel filler  
wire. Protect all stainless steel areas from weld  
splatter.  
Model GGH2O  
15  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Plumbing Connections  
Plumbing  
Once the hood is hung, the recirculation pump and  
detergent tank (both shipped loose) must be installed  
in the controls cabinet.  
A
E
Pump Installation  
A
B
• Remove bolts from pump mounting plate in cabinet.  
• Place the pump on the isolators located on the  
mounting plate with the bolts removed.  
• Secure the pump to the mounting plate with the four  
previously removed bolts.  
• Wire pump motor to the control cabinet per wiring  
diagram on the cabinet.  
D
C
• The wires to power the motor are already connected  
to the pump motor. It only needs to be wired to the  
control cabinet.  
A. One-inch unions  
B. Detergent tank  
C. Mounting plate  
D. Isolators (qty of four)  
E. Detergent pump  
Position pump on  
(4) isolators and attach  
using provided nuts.  
1. Connect the inlet and outlet piping on the  
recirculation pump to the respective piping in the  
cabinet via the threaded 1 in. unions.  
Connect to control  
cabinet per  
Wiring Diagram  
in panel  
2. Bring the inlet water piping to the connection  
located on the top of the hood and connect to the  
threaded connection on the 3/4 in. solenoid valve.  
A ball valve needs to be placed in the connection  
line before the 3/4 in. solenoid valve. Depending  
on water pressure, the inlet valve might need to  
be closed slightly to reduce water pressure. Water  
temperature should be 140°F.  
Field  
connect  
1-inch  
unions  
1-inch female NPT  
Connect to drain  
Inlet Solenoid  
Connection  
3. Bring the drain piping connection to the 1 in.  
solenoid valve in the control cabinet and connect  
to the threaded connection. This is a pressurized  
drain system and needs a properly sized drain to  
accommodate the pressurized drain water.  
NOTE  
As the suggested detergent is non-caustic and  
biodegradable, waste water from the hood can be  
drained in any typical grease trap.  
Model GGH2O  
16  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Detergent Tank Installation  
Electrical  
The detergent tank is located as shown in the photo.  
When installing the detergent tank, the low detergent  
indicator float and the detergent pump inlet tubing will  
need to be lifted. Once the tank is in position, the low  
detergent indicator float and detergent inlet tube must  
be lowered into place inside the tank.  
A. One-inch unions  
Electrical Wiring  
All wiring must be done according to NEC (National  
Electrical Code NFPA #70) and local building codes.  
Two sources of power need to be brought into  
the electrical control cabinet. A 120 volt, 30 amp  
service with 12 gauge wire needs to be connected  
to terminals L1 on the disconnect switch and N. A  
120 volt, 15 amp service with 14 gauge wire needs to  
be brought into the electrical cabinet and connected  
to terminal L2 on the disconnect switch and N1.  
B. Detergent tank  
C. Mounting plate  
D. Isolators (qty of four)  
E. Detergent pump  
NOTE  
Detergent Requirements  
The wash control station will provide a dry contact  
for a fan starter so the fans can be controlled by the  
PLC. The fan starter is not provided with the wash  
control station.  
The detergent brand Formula G-510 (by 2010  
Products, Inc.) is recommended by Greenheck for use  
in the wash system. Use Formula G-510 full strength.  
This product is biodegradable, non-caustic, and safe  
for kitchen staff to use. If G-510 detergent is not  
used, the cleanliness of the exhaust plenum and filters  
cannot be guaranteed.  
The main recirculating pump needs to be wired after it  
is installed in the hood. There are three 12 gauge wires  
in flexible conduit wired to the pump. Wiring to the  
pump is complete from the factory. The whip from the  
pump needs to be wired into the control cabinet.  
Preventative Maintenance  
The following practices will prolong the life of the  
detergent pump:  
• Keep detergent tank filled.  
• Avoid spilling detergent on the exterior of the  
pump.  
• Clean the detergent tank at least every six  
months.  
• Clean the detergent line strainer at least every six  
months.  
• Check tightness of all fittings periodically.  
The detergent pump motor has sealed bearings which  
do not require lubrication.  
NOTE  
G-510 is manufactured by 2010 Products, Inc., Food  
Service Division, Salem, Oregon 97303. For details  
and ordering information, call 800-286-2010.  
Model GGH2O  
17  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Timer Programming –  
24 Hour / 7 Day  
Reviewing Events Programmed  
In your current time display, press the PROG (program)  
button repeatedly to check your settings.  
Setting the Clock  
1. Press and hold the CLOCK button.  
2. Press and hold the DAY button until the display  
shows the current day.  
When finished, press the CLOCK button to return the  
display to the time of day.  
3. Press the HOUR button until the display shows the  
current hour.  
4. Press the MIN (minute) button until the display  
shows the current minute.  
Clearing (Deleting an Event)  
1. Press the PROG (program) button as many times  
as necessary to locate the setting you want to  
clear.  
Setting the Programs  
2. Press and hold the MODE button.  
3. Press the PROG button to clear the setting.  
4. When finished, press the CLOCK button to return  
the display to the time of day.  
1. Press the PROG (program) button once. You will  
now set the time in which you want the wash to  
start. The number 1 in the lower left hand corner  
indicates that you are now programming Event 1.  
2. Press the DAY button repeatedly until the display  
shows the day(s) when you want the timer to turn  
on. The options are:  
Operating the Time Switch  
Press the MODE button repeatedly to set the timer to  
Automatic, Random or Manual mode.  
- Days of the week  
NOTE  
MO, TU, WE, TH, FR, SA, SU  
For the time switch to run programmed events, it  
must be set to AUTO mode.  
-
-
-
Individual days of the week  
MO etc.  
Weekdays only  
MO, TU, WE, TH, FR  
AUTO runs all events automatically according to the  
schedule you have set. The word AUTO appears in  
the display.  
Weekends only  
SA, SU  
RND (random) runs all events in a RANDOM mode.  
This is a security feature in which ON and OFF  
times randomly differ +/- 15 minutes from the  
programmed times, creating a more “lived-in” look.  
The word RND appears on the display.  
3. Press the HOUR and MIN (minute) buttons to set  
the time when you want the timer to turn on.  
4. Press the PROG (program) button again.  
5. Repeat steps 2-4 to set the OFF time for Event 1.  
This should be set one minute after the ON time.  
6. When programming is complete, press the CLOCK  
button to display the current time.  
NOTE  
Do NOT set this timer to RND mode. It will not wash  
at the exact time you programmed.  
Things you should know about programming events:  
You can repeat the ON and OFF programming  
procedures outlined above for up to seven (7)  
events as needed.  
MANUAL turns ON and OFF only when the user  
presses the ON or OFF button. The display is blank,  
showing neither RND or AUTO.  
NOTE  
Overriding Timer Settings  
The ON or OFF buttons override the current  
While setting events, the timer may prematurely turn  
programmed events. To override the current program  
(either ON or OFF), press the ON or OFF button.  
on the load, if you press the MODE button.  
• Three kinds of settings can cause the timer to  
work in an unexpected way:  
a. Set up events in progressive order of time, for  
example:  
8:00 pm ON, 9:00 pm ON, 10:00 pm ON  
Not 8:00 pm ON, 10:00 pm ON, 9:00 pm ON  
b. Do not overlap event times, for example:  
8:00 pm ON / 12:00 pm OFF and  
9:00 pm ON / 11:00 pm OFF  
c. Set the OFF time for one minute after the ON  
time.  
Model GGH2O  
18  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Daily Operation of the GGH2O Hood  
Pressing the FAN ON/OFF button will start/stop the  
exhaust and supply fans if interlocked.  
Initial System Start-Up  
1. Check electrical power (see wiring diagram)  
• Correct supply voltage  
Pressing the HOOD LIGHTS button will turn on/off the  
hood lights.  
• Proper connections to fire  
suppression system  
Initiating the wash cycle:  
2. Check to make sure the  
disconnect switch on the  
electrical control cabinet is  
switched to the “ON” position.  
The Grease Grabber H O has an automatic timer  
2
that can be set to control the wash schedule and  
automatically start the cycle. See Timer Programming  
on page 18.  
3. Prime the recirculation pump. Remove the plug on  
top of pump and use a funnel to add water to the  
pump. This only needs to be done one time prior to  
initial start-up.  
4. Add detergent to the detergent tank in the cabinet.  
5. Clean the control cabinet of any debris that may  
have entered the cabinet during installation.  
6. Close the cabinet doors and press the Fan On/Off  
button.  
7. Check the exhaust and supply air volumes.  
8. Press the Fan On/Off button to turn the fans off.  
9. Press the Clean Hood button.  
When the hood is filling, check to ensure water is not  
leaking through the edges of the access doors. If so,  
the inlet water pressure is too high. Slowly close ball  
valve located before the inlet solenoid on the hood top  
until no water leaks pasT the access doors.  
To initiate the wash cycle manually, press the CLEAN  
HOOD button on the keypad. If you press this button  
while the fans are running, the system will stop the  
fans and then start the wash cycle. When the wash is  
completed, the system will automatically reset itself.  
If the fans are controlled by a building management  
system (BMS), the steps above still apply unless a  
special program is requested to bypass having to  
initiate the wash cycle by pushing the FAN ON/OFF  
and CLEAN HOOD buttons.  
Refer to the Grease Grabber™ H O Hood checklist  
on page 27 for detailed instructions on start-up  
operations.  
2
After the hood fills with water and starts washing the  
primary filters, open water valve slowly until water  
mist is felt above equipment. Then slowly close valve  
until water mist is no longer felt above equipment.  
Once the valve is set it will not need to be moved  
again.  
Verify the Grease Grabber H O sequence of operation  
2
(see the diagram of wash sequence on page 20)  
during the detergent pump cycle.  
C
E
D
A
B
Interior of Cabinet  
A. Recirculating pump  
B. Detergent tank  
C. Water valve to adjust front primary filter nozzles  
D. Pump plug for priming  
E. Detergent pump  
Model GGH2O  
19  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Sequence of Operation - Grease Grabber™ H O  
2
WASH  
RINSE  
DRY  
Hot Water Recovery:  
(0 min.) Adjustable  
Stage 7:  
Fill hood tank (hot water)  
Turn ON exhaust fan(s)  
20 minute dry time  
Shut OFF exhaust fan(s)  
Stage 8:  
Rinse primary filters  
Detergent pump OFF  
Turn OFF exhaust fan(s)  
Stage 1:  
Fill hood tank (hot water)  
Spray for 5 minutes  
Wash, rinse & dry complete  
Stage 2:  
Wash primary filters  
Detergent pump ON  
Stage 9:  
Rinse secondary filters  
Detergent pump OFF  
Spray for 5 minutes  
Spray for 5 minutes  
Stage 3:  
Wash secondary filters  
Detergent pump ON  
Stage 10:  
Drain rinse water  
Spray for 5 minutes  
2 minute delay for  
water settling  
Stage 4:  
Wash primary filters  
Detergent pump OFF  
Spray for 5 minutes  
Stage 5:  
Wash secondary filters  
Detergent pump OFF  
Spray for 5 minutes  
Stage 6:  
Drain soapy/dirty water  
Normal Fan Operation  
Exhaust Mode in Fire -- RUN  
Exhaust Mode in Fire -- STOP  
Temperature Interlock  
START FAN  
START FAN  
Fan(s) OFF  
Fan(s) will run  
No  
Fan(s) will run  
No  
Temperature  
> 95°F.  
(Adjustable)  
FIRE  
Yes  
FIRE  
Yes  
Exhaust Fan(s)  
will turn ON  
Exhaust  
Fan(s) remain  
ON  
Exhaust  
Fan(s) will  
turn OFF  
Model GGH2O  
20  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Airflow Testing Procedure  
After the appropriate number of readings have been  
taken from the inlet slot of the hood, an average  
reading can be calculated by summing the velocity  
readings and dividing the total value by the number of  
readings taken.  
Sum of Velocity Readings  
Average Velocity  
=
Number of Readings  
Next calculate the total hood airflow volume (CFM) by  
using the following equation:  
Hood CFM = [(Length of Hood in inches x 4.846) x  
(Average inlet slot velocity x 2.47)] 144  
NOTE  
The constants 4.846 and 2.47 are factory derived for  
use with the Grease Grabber™ H O.  
2
Calculation Example:  
Five (5) inlet slot velocity readings (minimum)  
Hood Length  
96 inches  
27  
Short Ridge Meter Components  
Test Location  
(off left; in inches)  
6
48  
69  
90  
For measuring exhaust airflow rates (cubic feet per  
minute = CFM), use a short ridge meter to measure  
velocities along the inlet slot of the hood. To ensure  
accurate data, all appliances should be on. Multiple  
locations need to be tested as outlined below to  
ensure an accurate reading.  
Velocity Reading (fpm) 175 210 250 190 160  
Average Velocity (FPM) =  
(175 + 210 + 250 + 190 + 160) 5 = 197 FPM  
Hood Exhaust Rate (CFM) =  
48 to 72 72 to 120 120 to 192  
Hood Length  
inches  
3
inches  
5
inches  
7
[(96 x 4.846) x (197 x 2.47)] 144 = 1572 CFM  
Minimum Number  
of Test Locations  
To take velocity readings along the length of the hood,  
the edge of the short ridge meter must start/stop six  
(6) inches from the end of the hood. Vertical placement  
of the short ridge meter along the inlet is shown.  
Model GGH2O  
21  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Amerex® Wiring Plan View  
POWER SOURCE  
MANUAL RESET RELAY  
PRM  
ELECTRIC GAS VALVE  
MICROSWITCH  
INSTALLER PROVIDED JUNCTION BOXES  
BASIC WIRING DIAGRAM  
POWER SOURCE  
MANUAL RESET RELAY  
RED (COMMON)  
YELLOW (N.O)  
BLACK (N.C.)  
GAS VALVE  
NOTE: DO NOT USE YELLOW WIRE ON MICROSWITCH IN NORMAL  
INSTALLATION. THE YELLOW WIRE IS TO BE USED ONLY FOR  
EXTINGUISHER ALARM, LIGHTS, CIRCUITS, ETC.  
MICROSWITCH  
BASIC WIRING DIAGRAM  
MANUAL RESET RELAY  
L1  
RED (COMMON)  
120V/60HZ  
L2  
K1  
Ka  
PUSHBUTTON SWITCH  
YELLOW (N.O)  
K1b  
BLACK (N.C.)  
MICROSWITCH  
CURRENT DRAW MAX:  
8A RESISTIVE  
8A INDUCTIVE  
120VAC  
GAS VALVE  
SEE NOTE 3  
NOTES:  
1.  
2.  
DENOTES FIELD INSTALLATION  
DENOTES FACTORY INSTALLATION  
3. GAS VALVE: UL LISTED ELECTRICALLY-OPERATED SAFETY VALVE FOR NATURAL OR LP GAS AS NEEDED OF  
APPROPRIATE PRESSURE AND TEMPERATURE RATING, 110V/60HZ OR AMEREX GAS VALVES, PN 12870, 12871,  
12872, 12873, 12874, 12875 and 12876.  
4. K1a and K1b ARE N.0. WHEN K1 IS DE-ENERGIZED.  
Model GGH2O  
22  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ansul® Wiring Plan View  
BLACK  
RED  
ANSUL SNAP-ACTION SWITCH  
(SWITCH CONTACTS SHOWN WITH ANSUL  
AUTOMAN IN THE COCKED POSITION)  
BROWN  
RESET  
POWER  
INDICATOR  
GND  
SCREW  
RED  
A
B
5
4
3
2
1
L2 NEUTRAL  
L1 HOT  
110V/60HZ  
RELAY COIL  
6
9
3
4
7
1
MANUAL RESET RELAY  
PART NO. 426151  
ELECTRICAL RATING  
1/3 HP, 10 AMP, 120 VAC  
1/2 HP, 10 AMP, 240 VAC  
13 AMP, 28 VDC  
NOTE:  
1.  
2.  
DENOTES FIELD INSTALLATION  
DENOTES FACTORY INSTALLATION  
3. GAS VALVES: "UL LISTED ELECTRICALLY-OPERATED SAFETY VALVE FOR NATURAL, OR LP GAS AS NEEDED OF APPROPRIATE PRESSURE AND  
TEMPERATURE RATING, 110V/60HZ OR ANSUL GAS VALVES, PART NUMBERS 13707, 13708, 13709, 13710. AND 17643.  
4. DO NOT USE BLACK WIRE ON SNAP-ACTION SWITCH IN NORMAL INSTALLATION. (USED ONLY FOR EXTRANEOUS ALARM, LIGHT CIRCUITS, ETC.  
BLACK  
ANSUL SNAP-ACTION SWITCH  
(SWITCH CONTACTS SHOWN WITH ANSUL  
RED  
AUTOMAN IN THE COCKED POSITION)  
BROWN  
RESET  
POWER  
INDICATOR  
GND  
SCREW  
RED  
A
B
5
4
3
2
1
L2 NEUTRAL  
L1 HOT  
110V/60HZ  
RELAY COIL  
6
9
3
4
7
1
MANUAL RESET RELAY  
PART NO. 426151  
SWITCH OR  
THERMOSTAT  
(CUSTOMER  
SUPPLIED)  
ELECTRICAL RATING  
1/3 HP, 10 AMP, 120 VAC  
1/2 HP, 10 AMP, 240 VAC  
13 AMP, 28 VDC  
CONTACTOR  
(CUSTOMER SUPPLIED)  
TO POWER SUPPLY  
220V/440V  
TO HEATING  
ELEMENT LOAD  
NOTE:  
1.  
2.  
DENOTES FIELD INSTALLATION  
DENOTES FACTORY INSTALLATION  
3. GAS VALVES: "UL LISTED ELECTRICALLY-OPERATED SAFETY VALVE FOR NATURAL, OR LP GAS AS NEEDED OF APPROPRIATE PRESSURE  
AND TEMPERATURE RATING, 110V/60HZ OR ANSUL GAS VALVES, PART NUMBERS 13707, 13708, 13709, 13710. AND 17643.  
4. DO NOT USE BLACK WIRE ON SNAP-ACTION SWITCH IN NORMAL INSTALLATION. (USED ONLY FOR EXTRANEOUS ALARM, LIGHT CIRCUITS, ETC.  
Model GGH2O  
23  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagram  
Wiring diagram is located on the inside cover of the control cabinet located on the end of the hood.  
AR  
3POLE 32 AMPS  
BK  
L1  
C
NO  
120VAC 1PH. 30 AMPS  
SUPPLY POWER  
WATER WASH  
DISC  
BK  
14 GA  
(H)  
L2  
H1  
WHT  
N1  
H1  
RD  
N
L1  
Hood Lights  
Hood Lights  
Hood Lights  
H1  
WHT  
120VAC 1PH. 15AMPS  
SUPPLY POWER  
HOOD LIGHTS  
BK  
L2  
L3  
R5 120 VAC  
R1  
21  
24  
PR  
E1  
E1  
E2  
FAN INTERLOCK  
CONTACT  
E1  
E2  
A1  
12 GA  
A2  
PR  
Fan  
Interlock  
14 GA  
N1  
Hood Lights  
LED Relay  
18 GA  
12 GA  
L1  
TR1  
FU2  
(N)  
120VAC  
(H)  
BK  
PR  
BL  
BK  
18 GA  
5 AMP  
18 GA  
YW  
41  
18 GA  
18 GA  
24VAC  
83  
U1 (FX-14)  
BL  
BK  
83  
41  
YW  
RD  
82  
83 - 24V (H)  
82 - 24V (C)  
S1 120 VAC  
WHT  
WHT  
N
N
42 - DO1  
S1  
N
N
41 - DO1 COM  
42  
Fill  
S2 120 VAC  
RD  
45  
BK  
BK  
41  
41  
45 - DO2  
48 - DO3  
52 - DO4  
S2  
44 - DO2  
COM  
Nozzle 1  
S3 120 VAC  
N
WHT  
RD  
48  
S3  
N
47 - DO3 COM  
51 - DO4 COM  
Nozzle 2  
PR  
51  
Melink Fan  
Stop Common  
PR  
52  
Melink Fan Stop  
M2  
M1  
S4 120 VAC  
Drain  
BK  
BK  
N
WHT  
RD  
55  
41  
55 - DO5  
58 - DO6  
S4  
N
54 - DO5 COM  
57 - DO6 COM  
C1 120 VAC  
C1  
WHT  
Recirc Pump  
95  
96  
N
RD  
58  
62  
65  
95  
41  
83  
83  
67  
A1  
A2  
Overload  
82  
R1 24 VAC  
Fan  
BL  
YW  
YW  
BL  
62 - DO7  
65 - DO8  
61 - DO7  
A2  
A1  
COM  
R2 24 VAC  
Detergent Pump  
BL  
82  
BL  
64 - DO8 COM  
67 - DO9 COM  
3 - Ext V  
A2  
A1  
L3  
OR  
RD  
68  
68 - DO9  
5
Clean Hood  
Indicator  
OR  
PR  
BR  
1
67  
25  
1 - AI COM  
21 - DI  
PR  
PR  
21  
25 - DI  
COM  
COM  
PB3  
PB2  
FL1  
Clean Hood  
Tank Full  
WHT  
PR  
27  
PR  
28  
23 - DI2  
27 - DI5  
10  
13  
SC  
F1  
F2  
23  
24  
WHT  
FL2  
FL3  
Start-Stop Fan  
11  
PR  
PR  
Tank Low  
RD  
24 - DI3  
22 - DI1  
28 - DI6  
RD  
R6  
14  
PR  
22  
21  
21  
PR  
36  
Safety  
BK  
36 - DI12  
72 - AO1  
73 - AO COM  
2 - AI1  
F3  
V1  
VC  
TS  
11  
BK  
Wash Timer  
R4  
OR  
72  
GGH20/VAV Fan Mode  
Interlock Connection  
0VDC - Fan Auto  
5VDC - Fan OFF  
10VDC - Fan On for Dry  
+VDC  
PR  
PR  
26  
26 - DI4  
32 - DI9  
24  
21  
BR  
73  
COM  
Fire Mode  
R3  
OR  
2
24  
21  
PR  
PR  
32  
21  
Temp Sensor  
(Freeze  
Protection)  
(If used)  
Det Low  
BR  
4
OR  
5
4 - AI COM  
5 - AI2  
TC  
I1  
OR  
7
I2  
IC  
7 - AI3  
Temp Sensor  
(IMC Interlock)  
(If used)  
Temp Sensor  
(IMC Interlock)  
(If used)  
BR  
6
6 - AI COM  
BR  
6
6 - AI COM  
IC  
81 - Earth  
L2  
1
R1  
14  
11  
OR  
67  
60  
OR  
1
6
Fan Indicator  
R5  
R3  
L1  
14  
14  
11  
11  
OR  
OR  
67  
67  
OR  
OR  
20  
30  
2
Lights Indicator  
L4  
3
Low Det Indicator  
R3 24 VAC  
FL4  
Det Low  
BL  
BL  
YW  
YW  
83  
83  
82  
YW  
F4  
F4  
C
A1  
A2  
Det Low  
Fire System  
R4 24 VAC  
YW  
FS  
82  
82  
FS  
FC  
A2  
A1  
Fire Mode  
AR 24 VAC  
2
BL  
BL  
YW  
83  
83  
3
PB1  
6
BL  
14  
14  
15  
Lights On/O”  
Timer  
Contact  
R6 120 VAC  
A2  
BK  
N
BK  
RD  
RD  
T2  
N
WHT  
41  
N
T2  
T1  
A1  
Wash Timer  
Relay  
P2  
R2  
FU3  
18 GA  
L1  
14 11  
BK  
BK  
BK  
DP  
12 GA  
12 GA  
L1  
L1  
LF3  
BK  
WHT  
N
N
WHT  
WHT  
DP  
N
N
3 AMP  
Detergent  
Pump  
Motor  
C1 120VAC  
L2 T2 T2  
P1  
FU1  
T1 T1  
L3  
T3  
T3  
BK  
BK  
BK  
RP  
WHT  
25 AMP  
RP  
Recirculating  
Pump  
Contactor  
Recirculating  
Pump  
Motor  
LF1  
12 GA  
FIELD INSTALLED WIRING  
MOLEX PLUG FOR KEYPAD  
Brown  
Recirculating Pump  
Motor Wiring  
White  
Blue  
(IF KEYPAD IS REMOTE MOUNTED, PLUG IS FIELD CONNECTED)  
Recirculating Pump Size  
FLA  
17  
22  
1.0 HP  
1.5 HP  
RP  
Orange  
Yellow  
N
Model GGH2O  
24  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Capture Tank  
Floats  
The interior surfaces of the hood capture tank should  
be wiped down weekly.  
The floats need to be  
inspected two weeks after  
start-up and then once a  
month thereafter.  
Filters  
The Grease Grabber filters (bead filters) require  
visually inspection (not removed from hood) two  
weeks after start-up, then once a month thereafter to  
make certain the filters are positioned correctly in the  
plenum. Positioned correctly means there are no gaps  
between the filters.  
The float can be inspected  
by first turning the  
Access Panel Door  
disconnect switch on the  
control cabinet to the ‘OFF’  
position. Then remove the  
large access panel door.  
Once the access panel  
is removed, you will have  
access to the floats.  
To inspect the bead filters, remove the fasteners  
holding the access doors; each door has five (5)  
fasteners. Remove every other door to inspect the  
filters.  
After inspecting the filters, put the access doors  
back on and put the fasteners back in. Be careful not  
to over-tighten or cross thread the fasteners when  
putting them back in.  
Float Installed  
Slide each float (Low Float,  
High Float and Safety Float)  
up the stem to its stop with  
your finger and let go. If float  
slides freely down the stem  
with minimal resistance, the  
float is operating as it should.  
Put the access panel back  
on and turn the disconnect  
switch to the ‘ON’ position.  
The Grease Grabber filters  
(bead filters) need to be  
removed from the hood  
once every three months to  
visually inspect and ensure  
the filters are structurally  
sound.  
Safety Float  
High Float  
Remove all the doors  
and remove the filters for  
inspection. Depending on  
the equipment under the  
hood, it will probably be  
easier to remove the filters  
from the right side of each  
hood. Slide the other filters  
down to the end access  
door for removal.  
Low Float  
If the float does not slide  
freely down the stem, the  
stem and floats are dirty  
and need to be wiped off with a clean cloth. Cleaning  
the stem involves removing all the clips (stops). Slide  
floats up and down on the shaft as required to access  
and clean the entire length of the shaft. Return floats  
to their location and reinstall stops.  
After inspecting the filters,  
place them back in the  
hood. Be careful to install  
the filters with the handles  
up and make sure not to  
hit the fire detection line  
when removing or installing  
the filters. Ensure no gaps  
are between filters after  
installation.  
Make sure all float stops are securely located in their  
grooves and floats are located in their designated  
spots.  
If for some reason the floats  
get taken off the stem, the  
stamped circle on the top  
side of the float needs to  
face up.  
If any filter appears damaged, consult factory for  
replacement.  
NOTE  
Be careful when handling the float stops. These are  
small clips and can easily be dropped. If you loose  
one of these clips, consult factory for a replacement.  
Model GGH2O  
25  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Replacement Parts  
When ordering parts, please be prepared to provide  
us with your cabinet and hood system model  
number, and serial number from labels on the hood  
and cabinet. See the chart below to identify the  
replacement parts needed.  
Hood is not cleaning  
If the hood does not seem to be adequately cleaned,  
look for the following:  
Detergent tank — is it empty or filled with wrong  
detergent?  
Greenheck Grainger®  
Detergent pump — is the detergent pump running?  
Is there power to the pump? Is the detergent level  
low? If the hood plenum area is not sufficiently  
cleaning, consult factory for information on  
increasing duration of wash cycle and detergent  
pump.  
Part  
Part  
Number  
Number  
Wash Nozzles  
Above GG Filters  
Below GG Filters  
Before First Stage Filters  
Repair Kits  
472806  
472795  
472805  
Nozzles — are any of them clogged? If so, they can  
be removed and cleared using a small wire.  
Solenoid Model 1A579  
Solenoid Model 1A578  
K-1180  
K-1172  
Water temperature — is it at least 140°F.  
Hardness of water — test water for hardness level.  
It is recommended that soft water be used.  
Hood not draining properly — plugged drain.  
Ensure all floats have stamped circles facing up.  
Water leaks — water leaking through the access  
panels when filling. Ensure access panels are securely  
in place. If leak persists, partially close inlet water ball  
valve (by others) upstream of fill solenoid to reduce  
water pressure.  
Condensation in the hood — large amounts of  
condensation while hood is washing. Hood should  
be washed after the hood and equipment is warm,  
not hot. The warm equipment helps reduce the  
condensation that forms in the hood.  
Approved wash detergent  
Formula G-510 from 2010 Products, Inc.  
Phone: 800-286-2010  
(Not provided by Greenheck).  
Model GGH2O  
26  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Grease Grabber™ H O Start-Up  
2
Checklist  
Check boxes when item has been verified and gone  
over with customer.  
o Wash Mode  
• See sequence of operations on page 20.  
• If using 24 hour / 7 day timer, wash cycle will start  
at scheduled time after “Fan On/Off” push button  
has been pressed. (Refer to page 18 for details on  
programming 24 hour / 7 day timer). If 24 hour / 7  
day timer is not being used, press “Clean Hood”  
push button after pressing “Fan On/Off” push  
button.  
Hook-Up  
o Electrical Connected  
• 120V/1 30A to terminals L1 and N for wash  
controls  
• 120V/1 15A to terminals L2 and N1 for hood lights  
• Fans to terminals E1 and E2 (dry contact)  
If using variable volume controls, Melink will also  
require connection to terminals M1 and M2, Vari-  
Flow will only require connection to terminals V1  
and VC.  
• Clean hood LED indicator should be lit.  
_________ Record water pressure  
(Should be between 30-50 psi)  
_________ Record water temperature  
(Should be between 140-160°F.)  
• Fire system microswitch to terminals FS and FC.  
• Recirculating pump wired to cabinet terminals  
RP and N.  
o Stop Mode  
• At end of wash cycle, system returns to Fan On  
for 20 minutes dry cycle.  
• If keypad is shipped loose, connection completed  
between keypad and cabinet with supplied cable.  
If additional cable is required, consult factory for  
ordering.  
• System resets to stop mode.  
• Hood lights off. Deactivate “Hood Lights” push  
button.  
o Plumbing Connected  
• All lights on face of keypad(s) should be off.  
Two 1-inch unions to recirculating pump  
connected.  
o Fire Mode  
• Hot water supply line, 3/4-inch connection.  
Trip fire system microswitch or remove wire  
from terminal FS or FC. (Water will not spray in  
fire mode, fans will run. If wash cycle is running  
during fire system trip, hood will drain and fan(s)  
will run).  
• Pressurized drain connection, 1-inch connection.  
• Hot water supply ball valve open. Located up  
stream of the inlet water solenoid valve.  
o Detergent  
• System fault LED indicator should be on.  
• Fan LED indicator should be lit.  
• Suction tubing and strainer to bottom of detergent  
tank.  
o Low Detergent Mode  
• Low detergent sensor in bottom of detergent tank.  
• Detergent tank filled with proper detergent.  
• Fill detergent tank with appropriate detergent.  
• Low detergent LED indicator should go off.  
o Timer, 24 hours / 7 day  
• Programmed - see instructions on page 18.  
Miscellaneous  
o Hood Access  
Start-Up  
o Cooking Mode  
• Panels should fit tightly to prevent water spraying  
out.  
• See sequence of operations on page 20.  
• When front nozzles are washing, adjust ball valve  
in cabinet to reduce water pressure and minimize  
overspray.  
• Hood lights on. Activate “Hood Lights” push  
button.  
• Hood light LED indicator should be lit.  
o Cleaning  
• Fans on. Hold “Fan On/Off” push button for one-  
half second.  
• Is the hood cleaning properly?  
• If not, refer to troubleshooting guide on page 26.  
• Fan LED indicator should be lit.  
• Appliances on (gas and/or electric).  
o Stop Mode  
• See sequence of operations on page 20.  
• Fans off. Hold “Fan On/Off” push button for one-  
half second.  
• LED indicator turns off.  
Model GGH2O  
27  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance Log  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Warranty  
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from  
the shipment date. Any units or parts which prove defective during the warranty period will be replaced at our option  
when returned to our factory, transportation prepaid. Motors are warranted by the motor manufacturer for a period of  
one year. Should motors furnished by Greenheck prove defective during this period, they should be returned to the  
nearest authorized motor service station. Greenheck will not be responsible for any removal or installation costs.  
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications  
without notice.  
Greenheck catalog GGH2O provides additional information  
describing the equipment, fan performance, available  
accessories, and specification data.  
AMCA Publication 410-96, Safety Practices for Users and  
Installers of Industrial and Commercial Fans, provides  
additional safety information. This publication can be  
®
473380 • Grease Grabber™ H2O Auto Cleaning Hood, Rev. 1, August 2010  
Copyright 2010 © Greenheck Fan Corporation  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Grandstream Networks Network Card GSM gateway User Manual
Grundig Automobile Accessories VCH 3610 User Manual
Hamilton Beach Blender Single Serve Blender User Manual
Hamilton Electronics Cassette Player HA 802 User Manual
Honeywell DVR VRX180 User Manual
Honeywell Electric Heater HHF360V User Manual
HP Hewlett Packard Computer Keyboard 460105 001 User Manual
HP Hewlett Packard Stereo System 44425A User Manual
Humminbird Fish Finder PIRANHAMAX10 User Manual
Husqvarna Trimmer 965966701 User Manual