Goodman Mfg Heat Pump RT6332013r1 User Manual

TECHNICAL MANUAL  
GPH 13 M Series Multi Position  
Package Heat Pump Units  
with R410A  
Refer to Service Manual RS6300008 for installation, operation, and troubleshooting information.  
All safety information must be followed as provided in the Service Manual.  
Refer to the appropriate Parts Catalog for part number information.  
Models listed on page 3.  
This manual is to be used by qualified, professionally trained HVAC technicians only.  
Goodman does not assume any responsibility for property damage or personal injury due to  
improper service procedures or services performed by an unqualified person.  
RT6332013r1  
November2010  
Copyright © 2010 Goodman Manufacturing Company, L.P.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT IDENTIFICATION  
The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please  
use these numbers when requesting service or parts information.  
GPH1324M41AB  
GPH1330M41AB  
GPH1336M41AB  
GPH1342M41AB  
GPH1348M41AB  
GPH1360M41AB  
The United States Environmental Protection Agency (“EPA”) has issued various regulations re-  
garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow  
WARNING  
these regulations may harm the environment and can lead to the imposition of substantial fines.  
These regulations may vary by jurisdiction. Should questions arise, contact your local EPA office.  
Do not connect or use any device  
To prevent the risk of property  
WARNING  
WARNING  
that is not design certified by  
Goodman for use with this unit.  
damage, personal injury, or death,  
do not store combustible materials or use gasoline or  
other flammable liquids or vapors in the vicinity of this  
appliance.  
Serious property damage, personal injury, reduced unit  
performance and/or hazardous conditions may result  
from the use of such non-approved devices.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT DESIGN  
GPH13 (M Series) Package Units are designed for outdoor  
installations only in either residential or light commercial ap-  
plications and are available in 2, 2.5, 3, 3.5, 4 & 5 ton sizes.  
Air for condensing (cooling cycle) or evaporation (heating  
cycle) is drawn through the outdoor coil by a propeller fan,  
and is discharged vertically out the top of the unit. The out-  
They are designed for 208/230 volt single phase applications. door coil is designed for .0 static. No additional restriction  
(ductwork) shall be applied.  
The connecting ductwork (Supply and Return) can be con-  
Conditioned air is drawn through the filter(s), field installed,  
across the coil and back into the conditioned space by the  
indoor blower.  
nected for either horizontal or vertical airflow. In the vertical  
application, a matching Roof Curb is recommended and a  
horizontal duct cover kit is required.  
Package Heat Pump indoor sections are designed to accept  
optional components such as auxiliary electric heaters and  
circuit breakers. Provisions for these components have been  
made at time of manufacture.  
A return air filter must be installed behind the return air grille(s)  
or provision must be made for a filter in an accessible loca-  
tion within the return air duct. The minimum filter area should  
not be less than those sizes listed in the Specification Sec-  
tion. Under no circumstances should the unit be operated  
without return air filters.  
GPH13 series package units use the Compliant Scroll com-  
pressor; there are a number of design characteristics which  
are different from the traditional reciprocating compressor.  
A 3/4" pipe is provided for removal of condensate water from  
the indoor coil. A trap must be provided to have proper con-  
densate drainage. (Do not reduce the drain line size).  
- Due to their design Scroll compressors are inherently more  
tolerant of liquid refrigerant. NOTE: Even though the com-  
pressor section of a Scroll compressor is more tolerant of  
liquid refrigerant, continued flood back or flooded start condi-  
Refrigerant flow control is achieved by use of restrictor ori-  
fices.  
All heat pump models also have a suction line accumulator tions may wash oil from the bearing surfaces causing prema-  
installed between the reversing valve and the compressor.  
The object of the accumulator is to:  
ture bearing failure.  
- These Scroll compressors use "POE" or polyolester oil which  
is NOT compatible with mineral oil based lubricants like 3GS.  
"POE" oil must be used if additional oil is required.  
1. Provide a liquid refrigerant storage vessel during prolonged  
system off cycles.  
2. Store excess liquid refrigerant not needed by the system  
while running.  
- Compliant scroll compressors perform “quiet” shutdowns  
that allow the compressor to restart immediately without the  
need for a time delay. This compressor will restart even if the  
system has not equalized.  
3. Return oil and saturated vapor to the compressor at a  
controlled rate.  
4. Retain stored excess refrigerant during a sudden system  
pressure fluctuation such as seen in defrost cycles.  
- Operating pressures and amp draws may differ from stan-  
dard reciprocating compressors. This information may be  
found in the “Cooling Performance Data” section.  
Refrigerant flow control is achieved by use of restrictor  
orifices. These models use the FasTest Access Fitting  
System, with a saddle that is either soldered to the suction  
andliquidlinesorisfastenedwithalockingnuttotheaccess  
fitting box (core) and then screwed into the saddle. Do not  
remove the core from the saddle until the refrigerant  
charge has been removed. Failure to do so could result  
in property damage or personal injury.  
LocationandClearances  
NOTE: To ensure proper condensate drainage, unit must be  
installed in a level position.  
The single phase units use permanent split capacitor (PSC)  
design compressors. Starting components are not required  
for these units. A low microfarad run capacitor assists the  
compressor to start and remains in the circuit during opera-  
tion.  
The outdoor fan motors are single phase capacitor type mo-  
tors. Some models use PSC type indoor blower motors while  
others use EEM type blower motors. EEM motors are ener-  
gized by a 24V signal from the thermostat and are constant  
torque motors with very low power consumption.  
The EEM features an integral control module.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT DESIGN  
In installations where the unit is installed above ground level  
and not serviceable from the ground (Example: roof top in-  
stallations) the installer must provide service platform for ser-  
vice person with rails or guards in accordance with local codes  
or ordinances, or, in their absence, with the latest edition of  
the Uniform Mechanical Code Section 305.  
NOTE: Unit can also use roof curb (and platform for leveling,  
where necessary) to utilize bottom discharge.  
WARNING  
TO PREVENT POSSIBLE PROPERTY DAMAGE, THE  
UNIT SHOULD REMAIN IN AN UPRIGHT POSITION  
DURING ALL RIGGING AND MOVING OPERATIONS.  
TO FACILITATE LIFTING AND MOVING IF A CRANE IS  
USED, PLACE THE UNIT IN AN ADEQUATE CABLE  
SLING.  
OutsideSlabInstallation-Multi-positional(M)  
IMPORTANT: If using bottom discharge with roof curb,  
ductwork should be attached to the curb prior to installing  
the unit.  
NOTE: Roof overhang should be no more than 36" and provi-  
sions made to deflect the warm discharge air out from the  
overhang.  
NOTE: Single phase models require installation of horizontal  
duct kit #20464501PDGK (medium chassis) and  
#20464502PDGK (large chassis) when using bottom dis-  
charge.  
Minimum clearances are required to avoid air recirculation  
and keep the unit operating at peak efficiency.  
Refer to Roof curb Installation Instructions for proper curb  
installation. Curbing must be installed in compliance with the  
National Roofing Contractors Association Manual.  
Roof Curb  
Rooftop Installation - -Multi-positional (M)  
NOTE: To ensure proper condensate drainage, unit must be  
installed in a level position.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT DESIGN  
GPH13[24-60]M41*  
HKR ELECTRICAL DATA  
Circuit #1  
Circuit #2  
Maximum  
Overcurrent  
Protection (amps)  
at 208 / 240V  
Maximum  
Actual  
kW & BTU  
at 240V  
Minimum Circuit  
Ampacity  
at 208 / 240V  
Minimum Circuit  
Ampacity  
at 208 / 240V  
Overcurrent  
Protection (amps)  
at 208 / 240V  
GPH1324M41*  
HKR05A,CA  
HKR08A,CA  
HKR10A,CA  
24 / 27  
33 / 28  
45 / 51  
30 / 30  
40 / 40  
60 / 60  
----  
----  
----  
----  
----  
----  
4.75 / 16,200  
7.00 / 23,800  
9.50 / 32,400  
GPH1330M41*  
HKR05A,CA  
24 / 27  
34 / 39  
45 / 52  
45 / 52  
30 / 30  
40 / 40  
60 / 60  
60 / 60  
--  
--  
--  
--  
4.75 / 16,200  
7.0 / 23,800  
9.5 / 32,400  
14.25 / 48,600  
HKR08A,CA  
HKR10A,CA  
HKR15A,CA  
GPH1336M41*  
HKR05A,CA  
HKR08A,CA  
HKR10A,CA  
HKR15A,CA  
GPH1342M41*  
HKR05A,CA  
HKR08A,CA  
HKR10A,CA  
HKR15A,CA  
GPH1348M41*  
HKR05A,CA  
HKR08A,CA  
HKR10A,CA  
HKR15A,CA  
HKR20A,CA  
GPH1360M41*  
HKR05A,CA  
HKR08A,CA  
HKR10A,CA  
HKR15A,CA  
HKR20A,CA  
--  
--  
22 / 25  
30 / 30  
24 / 27  
34 / 39  
30 / 30  
40 / 40  
----  
----  
----  
----  
4.75 / 16,200  
7.00 / 23,800  
45 / 52  
45 / 52  
60 / 60  
60 / 60  
----  
22 / 25  
----  
30 / 30  
9.50 / 32,400  
14.25 / 48,600  
24 / 27  
34 / 39  
45 / 52  
45 / 52  
30 / 30  
40 / 40  
60 / 60  
60 / 60  
--  
--  
--  
--  
4.75 / 16,200  
7.0 / 23,800  
9.5 / 32,400  
14.25 / 48,600  
--  
--  
22 / 25  
30 / 30  
25 / 28  
34 / 40  
46 / 53  
30 / 30  
40 / 40  
60 / 60  
----  
----  
----  
----  
----  
----  
4.75 / 16,200  
7.00 / 23,800  
9.50 / 32,400  
46 / 52  
46 / 52  
60 / 60  
60 / 60  
22 / 25  
43 / 49  
30 / 30  
60 / 60  
14.25 / 48,600  
19.50 / 66,500  
26 / 30  
36 / 40  
48 / 54  
48 / 54  
48 / 54  
30 / 30  
40 / 40  
60 / 60  
60 / 60  
60 / 60  
----  
----  
----  
----  
4.75 / 16,200  
7.00 / 23,800  
9.50 / 32,400  
14.25 / 48,600  
19.50 / 66,500  
----  
----  
22 / 25  
43 / 49  
30 / 30  
60 / 60  
IMPORTANT NOTE: A separate power supply is required for the HKR heater kit.  
Heating kW Correction Factor  
Supply Votage  
240  
1.0  
230  
220  
210  
208  
Correction Factor  
0.93  
0.85  
0.78  
0.76  
Multiply rated kW by correction factor to get actual kW  
All wires and overcurrent protection devices are sized for use with electric heaters only and without  
refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See  
PACKAGE UNIT SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent pro-  
tection during refrigeration cycle.  
WARNING  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT DIMENSIONS  
GPH13[24-60]M41*  
47  
51  
POWER  
WIRE  
ENTRANCE  
A
16  
4 1/8  
2 1/8  
1 3/8  
5 ½  
16  
6 ½  
8
B
2 34  
RETURN  
B
SUCTION/LIQUID  
PRESSURE PORT  
SUPPLY  
3
CONDENSATE  
DRAIN  
CONNECTION  
3/4” NPT FEMALE  
CONTROL  
WIRE  
ENTRANCE  
18 7/8  
BLOWER  
ACCESS PANEL  
MEDIUM CHASSIS  
GPH1324M41*  
GPH1330M41*  
GPH1336M41*  
GPH1342M41*  
LARGE CHASSIS  
GPH1348M41*  
GPH1360M41*  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
PACKAGE HEAT PUMP SPECIFICATIONS GPH13[24-36]M41AB  
GPH1324M41*  
GPH1330M41*  
GPH1336M41*  
COOLING  
CAPACITY  
HEATING  
RATING  
COOLING CAPACITY, BTUH  
SEER / EER  
24,000  
13/11  
23000  
12600  
7.7  
29,000  
13/10.8  
28800  
17000  
7.7  
34600  
13/10.9  
34200  
19000  
7.7  
BTU/h (47°)  
BTU/h (17°)  
HSPF  
VOLTAGE (NAMEPLATE)  
AMPS  
208/230-60-1  
15.8  
208/230-60-1  
19.0  
208/230-60-1  
21.3  
UNIT  
ELECTRICAL  
SPECIFICATION  
MIN CIRCUIT AMPACITY  
19.0  
23.0  
25.4  
MAX OVERCURRENT PROTECTION(1 )  
TYPE  
30  
35  
40  
SCROLL  
12.8  
SCROLL  
16.0  
SCROLL  
16.7  
COMPRESSOR  
RATED LOAD AMPS  
LOCKED ROTOR AMPS  
HORSEPOWER  
58.3  
77  
79  
1/4  
1/4  
1/4  
CONDENSER  
FAN MOTOR  
RPM  
830  
830  
830  
FULL LOAD AMPS  
LOCKED ROTOR AMPS  
1.5  
1.5  
1.5  
3
3
3
BLADE DIAMETER (INCHES)  
NUMBER OF BLADES  
CONDENSER FAN  
22/3  
22/3  
22/4  
CONDENSER  
COIL  
FACE AREA (SQ. FT.)  
17.02  
1
17.02  
1
16.83  
1
NUMBER OF ROWS  
FINS PER INCH  
24  
24  
22  
HORSEPOWER - NUMBER OF SPEEDS  
FULL LOAD AMPS  
1/4 - 3  
1.5  
1/3 - 3  
1.5  
1/3 - 3  
3.06  
4.1  
EVAPORATOR  
BLOWER  
LOCKED ROTOR AMPS  
MOTOR SPEED TAP - COOLING X-13  
RPM  
2.13  
High  
952  
3.2  
MOTOR  
High  
869  
High  
910  
DIAMETER X WIDTH (INCHES)  
RATED SCFM COOLING  
MAX EXTERNAL STATIC PRESS ("w.c.)  
FACE AREA (SQ. FT.)  
10 x 9  
825  
10 x 9  
1050  
0.5  
10 x 9  
1150  
0.5  
EVAPORATOR  
BLOWER  
0.5  
EVAPORATOR  
COIL  
4.52  
4.52  
4
4.52  
4
NUMBER OF ROWS  
4
FINS PER INCH  
16  
16  
14  
GENERAL  
FILTER SIZE *  
25 x 25 x 1  
3/4"  
25 x 25 x 1  
3/4"  
25 x 25 x 1  
3/4"  
DRAIN SIZE (INCHES)  
INFORM ATION  
EXPANSION DEVICE (ID/OD)  
REFRIGERANT CHARGE R410A (OZS.)  
0.057/0.045  
110  
0.070/0.055  
115  
0.071/0.057  
135  
POWER SUPPLY  
CONDUIT KNOCKOUT SIZE (INCHES)  
3/4, 1, 1-1/4  
1/2  
3/4, 1, 1-1/4  
1/2  
3/4, 1, 1-1/4  
1/2  
LOW VOLTAGE  
CONDUIT KNOCKOUT SIZE (INCHES)  
LO PRESSURE SWITCH  
OPENS / CLOSES PSIG  
22 / 50  
22 / 50  
22 / 50  
HI PRESSURE SWITCH - OPENS PSIG  
OPENS / CLOSES PSIG  
660 / 420  
405  
660 / 420  
410  
660 / 420  
435  
SHIPPING WEIGHT (LBS.)  
OPERATING WEIGHT (LBS.)  
395  
400  
425  
(1)  
*
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.  
Calculated external filter size based on air velocity of 300 ft/min.  
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.  
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers  
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
PACKAGE HEAT PUMP SPECIFICATIONS  
GPH13[42-60]M41AB  
GPH1342M41*  
GPH1348M41*  
GPH1360M41*  
COOLING  
CAPACITY  
HEATING  
RATING  
COOLING CAPACITY, BTUH  
SEER / EER  
40000  
13/11  
40000  
21000  
7.7  
46500  
13/11  
45500  
26000  
8.0  
56000  
13/10.9  
55500  
31200  
8.0  
BTU/h (47°)  
BTU/h (17°)  
HSPF  
VOLTAGE (NAMEPLATE)  
AMPS  
208/230-60-1  
22.4  
208/230-60-1  
29.0  
208/230-60-1  
35.4  
UNIT  
ELECTRICAL  
SPECIFICATION  
MIN CIRCUIT AMPACITY  
26.8  
34.5  
42.0  
MAX OVERCURRENT PROTECTION(1)  
TYPE  
40  
50  
60  
SCROLL  
17.9  
SCROLL  
21.8  
SCROLL  
26.4  
COMPRESSOR  
RATED LOAD AMPS  
LOCKED ROTOR AMPS  
HORSEPOWER  
112  
117  
134  
1/4  
1/4  
1/4  
CONDENSER  
FAN MOTOR  
RPM  
1075  
1.4  
1075  
1.4  
1075  
FULL LOAD AMPS  
LOCKED ROTOR AMPS  
1.4  
2.9  
2.9  
2.9  
BLADE DIAMETER (INCHES)  
NUMBER OF BLADES  
CONDENSER FAN  
22/3  
22/3  
22/3  
CONDENSER  
COIL  
FACE AREA (SQ. FT.)  
16.83  
2
19.24  
21.04  
NUMBER OF ROWS  
2
16  
2
16  
FINS PER INCH  
16  
HORSEPOWER - NUMBER OF SPEEDS  
FULL LOAD AMPS  
1/3 - 3  
3.06  
3/4 - 5  
5.8  
1 - 5  
7.6  
EVAPORATOR  
BLOWER  
LOCKED ROTOR AMPS  
MOTOR SPEED TAP - COOLING X-13  
RPM  
4.1  
---  
---  
MOTOR  
High  
910  
T2/T3  
1050  
10 x 9  
1720  
0.5  
T2/T3  
1050  
10 x 9  
1800  
0.5  
DIAMETER X WIDTH (INCHES)  
RATED SCFM COOLING  
MAX EXTERNAL STATIC PRESS ("w.c.)  
FACE AREA (SQ. FT.)  
10 x 9  
1300  
0.5  
EVAPORATOR  
BLOWER  
EVAPORATOR  
COIL  
4.52  
6.17  
6.17  
NUMBER OF ROWS  
4
4
4
FINS PER INCH  
14  
14  
14  
GENERAL  
FILTER SIZE *  
25 x 25 x 1  
3/4"  
(2) 20 x 20 x 1  
3/4"  
(2) 20 x 20 x 1  
3/4"  
DRAIN SIZE (INCHES)  
INFORM ATION  
EXPANSION DEVICE (ID/OD)  
REFRIGERANT CHARGE R410A (OZS.)  
0.072/0.063  
180  
0.080/0.065  
190  
0.084/0.076  
220  
POWER SUPPLY  
CONDUIT KNOCKOUT SIZE (INCHES)  
3/4, 1, 1-1/4  
1/2  
3/4, 1, 1-1/4  
1/2  
3/4, 1, 1-1/4  
1/2  
LOW VOLTAGE  
CONDUIT KNOCKOUT SIZE (INCHES)  
LO PRESSURE SWITCH  
OPENS / CLOSES PSIG  
22 / 50  
22 / 50  
22 / 50  
HI PRESSURE SWITCH - OPENS PSIG  
OPENS / CLOSES PSIG  
660 / 420  
440  
660 / 420  
520  
660 / 420  
533  
SHIPPING WEIGHT (LBS.)  
OPERATING WEIGHT (LBS.)  
430  
510  
523  
(1)  
*
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.  
Calculated external filter size based on air velocity of 300 ft/min.  
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.  
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers  
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
GPH13[24-60]M41*  
ACCESSORIES - GPC/GPH****M MODELS  
Description  
Part Number  
OT18-60A  
Outdoor Thermostat Kit w/Lockout Stat  
Emergency Heat Relay Kit  
OT/EHR18-60  
HKR  
Electric Heat Kit  
PGC101/102/103  
PEHH101/102  
PEHH103  
Roof Curb  
Horizontal Economizer For Heat Pump, Small and Medium Chassis  
Horizontal Economizer For Heat Pump, Large Chassis  
Horizontal Economizer For A/C, Small and Medium Chassis  
Horizontal Economizer For A/C, Large Chassis  
PEHC101/102  
PEHC103  
PGMDD101/102  
PGMDD103  
Manual 25% Fresh Air Damper Downflow Application, Small and Medium Chassis  
Manual 25% Fresh Air Damper Downflow Application, Large Chassis  
Manual 25% Fresh Air Damper Horizontal Application, Medium Chassis  
Manual 25% Fresh Air Damper Horizontal Application, Large Chassis  
Motorized 25% Fresh Air Damper Downflow Application,Small and Medium Chassis  
Motorized 25% Fresh Air Downflow Application, Large Chassis  
Motorized 25% Fresh Air Damper Horizontal Application, Medium Chassis  
Motorized 25% Fresh Air Damper Horizontal Application, Large Chassis  
Downflow Economizer For A/C, Medium Chassis  
PGMDH102  
PGMDH103  
PGMDMD101/102  
PGMDMD103  
PGMDMH102  
PGMDMH103  
GPC13MED102  
GPC13MED103  
GPH13MED102  
GPH13MED103  
GPH13MFR102  
GPH13MFR103  
GPGHFR101-103  
SQRPG101/102  
SQRPG103  
Downflow Economizer For A/C, Large Chassis  
Downflow Economizer For Heat Pump, Medium Chassis  
Downflow Economizer For Heat Pump, Large Chassis  
Internal Filter Rack, Medium Chassis  
Internal Filter Rack, Large Chassis  
External Horizontal Filter Rack for Goodman/Amana Gas/Electric and Multi-position Package Units All Chassis  
Square to Round Adapter w/ 16" Round Downflow Application, Medium Chassis  
Square to Round Adapter w/ 18" Round Downflow Application, Large Chassis  
Square to Round Adapter w/ 16" Round Horizontal Application, Medium Chassis  
Square to Round Adapter w/ 18" Round Horizontal Application, Large Chassis  
Flush Mount Concentric Duct Kit  
SQRPGH101/102  
SQRPGH103  
CDK36  
CDK36515  
Flush Mount Concentric Duct Kit w/ Filter  
CDK36530  
Step Down Concentric Duct Kit  
CDK36535  
Step Down Concentric Duct Kit w/ Filter  
CDK4872  
Flush Mount Concentric Duct Kit  
CDK4872515  
CDK4872530  
CDK4872535  
Flush Mount Concentric Duct Kit w/ Filter  
Step Down Concentric Duct Kit  
Step Down Concentric Duct Kit w/ Filter  
NOTE: Complete lineup of thermostats can be found in the Thermostat Specification Sheets.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GPH13[24-60]M41*  
BLOWER PERFORMANCE DATA  
Dry Coil Data  
E.S.P (In. of H2O)  
0.4 0.5  
Model  
Speed  
Low  
Med  
High  
Low  
Med  
High  
Low  
Med  
High  
Low  
Med  
High  
Volts  
CFM  
0.1  
0.2  
0.3  
0.6  
0.7  
0.8  
667  
153  
596  
150  
-------- -------- -------- -------- -------- --------  
-------- -------- -------- -------- -------- --------  
230  
230  
230  
230  
230  
230  
230  
230  
230  
230  
230  
230  
WATTS  
CFM  
897  
841  
784  
224  
713  
217  
610  
207  
982  
333  
901  
305  
1033  
356  
1194  
446  
915  
300  
1119  
399  
1230  
477  
915  
300  
1119  
399  
1230  
477  
-------- -------- --------  
-------- -------- --------  
WATTS  
CFM  
233  
229  
1242  
373  
1181  
364  
1122  
354  
1057  
344  
883  
318  
818  
290  
952  
342  
1106  
427  
804  
283  
1041  
382  
1144  
461  
804  
283  
1041  
382  
1144  
461  
719  
298  
648  
271  
777  
313  
1008  
410  
687  
264  
935  
363  
1055  
442  
687  
264  
935  
363  
1055  
442  
617  
284  
562  
257  
670  
297  
864  
382  
558  
250  
748  
330  
939  
420  
558  
250  
748  
330  
939  
WATTS  
CFM  
1097  
337  
1059  
330  
1016  
324  
959  
WATTS  
CFM  
315  
1253  
397  
1204  
388  
1148  
379  
1097  
369  
WATTS  
CFM  
1448  
499  
1380  
483  
1323  
472  
1258  
459  
WATTS  
CFM  
1122  
338  
1078  
330  
1032  
321  
972  
WATTS  
CFM  
310  
1387  
456  
1331  
440  
1264  
428  
1209  
412  
WATTS  
CFM  
1521  
534  
1454  
521  
1388  
510  
1311  
490  
WATTS  
CFM  
1122  
338  
1078  
330  
1032  
321  
972  
WATTS  
CFM  
310  
1387  
456  
1331  
440  
1264  
428  
1209  
412  
WATTS  
CFM  
1521  
534  
1454  
521  
1388  
510  
1311  
490  
WATTS  
CFM  
420  
1,130  
1,440 1,395 1,360 1,310 1,265 1,235 1,190  
275 285 295 315 325 335 345  
1,795 1,765 1,715 1,695 1,650 1,600 1,500  
475 490 505 520 530 535 510  
1,860 1,820 1,785 1,745 1,700 1,625 1,515  
515 530 545 565 570 550 535  
1,755 1,720 1,685 1,645 1,615 1,570 1,530  
420 435 455 460 475 490 500  
1,850 1,820 1,775 1,735 1,705 1,675 1,610  
480 500 515 525 535 555 545  
2,180 2,125 2,050 1,975 1,875 1,800 1,655  
770 755 725 700 675 640 575  
T1 (G) 230  
355  
1,375  
475  
WATTS  
CFM  
T2 / T3  
230  
(W2)  
WATTS  
CFM  
1,395  
485  
T4 / T5  
230  
(Y)  
WATTS  
CFM  
1,465  
500  
T1 (G) 230  
WATTS  
CFM  
1,495  
520  
T2 / T3  
230  
W2  
WATTS  
CFM  
1,530  
540  
T4 / T5  
230  
Y
WATTS  
NOTES:  
Data shown is Dry Coil. Wet Coil Pressure Drop is approximate. 0.1" H2O, for 2 row indoor coil; 0.2” H2O, for 3 row indoor  
coil; and 0.3” H2O, for 4 row indoor coil.  
Data shown does not include filter pressure drop, approx. 0.08” H2O.  
ALL MODELS SHOULD RUN NO LESS THAN 350 CFM / TON.  
Reduce airflow by 2% for 208V operation.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLOWER PERFORMANCE DATA  
S E R E I R U  
M P T E E R A T  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPH1324M41*  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPH1324M41*  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPH1330M41*  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPH1330M41*  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPH1336M41*  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPH1336M41*  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPH1342M41*  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPH1342M41*  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPH1348M41*  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPH1348M41*  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GPH1360M41*  
COOLING PERFORMANCE DATA  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GPH1360M41*  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HEATING PERFORMANCE DATA  
GPH13[24-42]M41*  
EXPANDED PERFORMANCE DATA  
MODEL: GPH1324M41*  
HEATING OPERATION  
Outdoor Ambient Temperature  
65  
60  
55  
50  
47  
45  
22.3  
25.0  
1.97  
8.4  
3.30  
11.3  
320  
98  
40  
20.7  
23.2  
1.94  
8.0  
3.13  
10.7  
308  
90  
35  
30  
16.7  
18.8  
2.32  
7.4  
2.11  
7.2  
283  
73  
25  
15.4  
17.3  
2.26  
7.1  
1.99  
6.8  
270  
65  
20  
14.2  
15.9  
2.21  
6.9  
1.88  
6.4  
260  
57  
17  
13.4  
15.1  
2.18  
6.7  
1.80  
6.2  
253  
53  
15  
12.9  
14.5  
2.16  
6.7  
1.75  
6.0  
249  
51  
10  
11.6  
13.0  
2.10  
6.4  
1.61  
5.5  
239  
43  
5
0
9.0  
-5  
7.6  
8.6  
-10  
6.3  
7.0  
MBh  
Delta T  
KW  
AMPS  
COP  
EER  
HI PR  
LO PR  
28.9  
32.4  
2.14  
10.4  
3.96  
13.5  
379  
135  
27.4  
30.7  
2.10  
9.8  
3.82  
13.1  
364  
126  
25.8  
28.9  
2.06  
9.2  
3.67  
12.5  
350  
24.1  
27.0  
2.01  
8.8  
3.50  
12.0  
334  
23.0  
25.8  
1.99  
8.5  
3.38  
11.5  
326  
19.1  
21.4  
1.89  
7.7  
2.95  
10.1  
295  
80  
10.3  
11.5  
2.05  
6.1  
1.47  
5.0  
10.1  
2.00  
5.8  
1.31  
4.5  
1.95  
5.5  
1.15  
3.9  
213  
27  
1.89  
5.1  
0.97  
3.3  
205  
22  
230  
37  
221  
31  
118  
108  
102  
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.  
MODEL: GPH1330M41*  
HEATING OPERATION  
Outdoor Ambient Temperature  
65  
60  
55  
50  
47  
45  
40  
35  
30  
21.2  
18.7  
2.29  
9.6  
2.71  
9.2  
280  
70  
25  
19.6  
17.3  
2.24  
9.2  
2.55  
8.7  
267  
63  
20  
18.0  
15.9  
2.19  
8.9  
2.40  
8.2  
256  
55  
17  
17.0  
15.0  
2.17  
8.7  
2.30  
7.9  
250  
51  
15  
16.4  
14.4  
2.15  
8.6  
2.23  
7.6  
246  
49  
10  
14.7  
13.0  
2.10  
8.2  
2.05  
7.0  
236  
42  
5
0
-5  
9.7  
-10  
7.9  
MBh  
Delta T  
KW  
AMPS  
COP  
EER  
HI PR  
LO PR  
36.2  
31.9  
2.74  
13.6  
3.87  
13.2  
375  
131  
34.3  
30.2  
2.68  
12.7  
3.74  
12.8  
359  
32.3  
28.4  
2.63  
12.0  
3.59  
12.3  
346  
30.2  
26.6  
2.58  
11.4  
3.42  
11.7  
330  
28.8  
25.4  
2.55  
11.1  
3.30  
11.3  
323  
27.9  
24.6  
2.53  
10.9  
3.23  
11.0  
316  
25.9  
22.9  
2.48  
10.4  
3.06  
10.5  
304  
23.9  
21.1  
2.43  
9.9  
2.88  
9.8  
13.0  
11.5  
2.05  
7.8  
1.86  
6.4  
11.4  
10.0  
2.00  
7.5  
1.66  
5.7  
8.6  
1.95  
7.0  
1.46  
5.0  
210  
27  
7.0  
1.90  
6.5  
1.22  
4.2  
203  
21  
292  
78  
227  
36  
218  
30  
122  
114  
105  
99  
95  
88  
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.  
MODEL: GPH1336M41*  
HEATING OPERATION  
Outdoor Ambient Temperature  
65  
60  
55  
50  
47  
45  
40  
35  
30  
25  
20  
20.8  
16.7  
2.26  
9.9  
17  
19.6  
15.8  
2.24  
9.7  
15  
18.9  
15.2  
2.22  
9.6  
10  
17.0  
13.6  
2.17  
9.2  
5
0
-5  
11.2  
9.0  
2.02  
7.8  
-10  
9.2  
7.4  
1.97  
7.2  
MBh  
Delta T  
KW  
AMPS  
COP  
EER  
HI PR  
LO PR  
43.0  
34.6  
3.10  
15.4  
4.06  
13.9  
403  
137  
40.7  
32.8  
3.04  
14.4  
3.92  
13.4  
386  
38.3  
30.8  
2.98  
13.6  
3.76  
12.8  
371  
35.8  
28.8  
2.92  
12.9  
3.58  
12.2  
355  
34.2  
27.5  
2.89  
12.5  
3.46  
11.8  
347  
33.1  
26.7  
2.86  
12.3  
3.39  
11.6  
340  
30.8  
24.8  
2.81  
11.7  
3.21  
11.0  
327  
28.4  
22.9  
2.75  
11.1  
3.02  
10.3  
314  
24.4  
19.7  
2.36  
10.7  
3.03  
10.4  
300  
73  
22.6  
18.2  
2.31  
10.3  
2.86  
9.8  
15.0  
12.1  
2.12  
8.7  
13.1  
10.6  
2.07  
8.3  
2.69  
9.2  
276  
58  
2.57  
8.8  
269  
54  
2.50  
8.5  
264  
52  
2.29  
7.8  
254  
44  
2.08  
7.1  
244  
38  
1.85  
6.3  
234  
32  
1.62  
5.5  
226  
28  
1.36  
4.6  
218  
22  
287  
66  
127  
119  
109  
103  
99  
91  
81  
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.  
MODEL: GPH1342M41*  
HEATING OPERATION  
Outdoor Ambient Temperature  
65  
60  
55  
50  
47  
45  
40  
35  
30  
25  
20  
17  
15  
10  
19.1  
13.6  
2.14  
10.6  
2.61  
8.9  
5
-5  
12.6  
9.0  
2.01  
9.0  
1.84  
6.3  
181  
29  
-10  
10.3  
7.3  
1.96  
8.3  
1.54  
5.3  
175  
22  
MBh  
Delta T  
KW  
AMPS  
COP  
EER  
HI PR  
LO PR  
50.3  
35.8  
3.58  
17.6  
4.11  
14.0  
323  
141  
47.6  
33.9  
3.52  
16.5  
3.96  
13.5  
310  
44.8  
31.9  
3.45  
15.6  
3.80  
13.0  
298  
41.9  
29.8  
3.38  
14.8  
3.62  
12.4  
285  
40.0  
28.5  
3.34  
14.3  
3.50  
12.0  
278  
38.8  
27.6  
3.31  
14.1  
3.42  
11.7  
273  
36.0  
25.6  
3.25  
13.4  
3.24  
11.1  
262  
33.2  
23.6  
3.18  
12.8  
3.05  
10.4  
252  
27.5  
19.6  
2.31  
12.3  
3.48  
11.9  
241  
75  
25.4  
18.1  
2.27  
11.9  
3.27  
11.2  
230  
67  
23.4  
16.7  
2.23  
11.4  
3.07  
10.5  
221  
59  
22.1  
15.7  
2.20  
11.2  
2.94  
10.0  
216  
55  
21.3  
15.1  
2.18  
11.1  
2.85  
9.7  
16.9  
12.0  
2.09  
10.0  
2.36  
8.1  
14.8  
10.5  
2.05  
9.6  
2.11  
7.2  
212  
53  
204  
45  
196  
39  
188  
33  
131  
122  
112  
106  
102  
94  
84  
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.  
PERFORMANCE TEST  
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor  
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:  
If conditions vary from this, results will change as follows:  
1. As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low  
and high side pressures and power will not change.  
2. As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will  
occur in low and high side pressures and power.  
A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.  
A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.  
A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.  
A properly operating unit should be within plus or minus 3 Amps of the typical value shown.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HEATING PERFORMANCE DATA  
GPH13[48-60]M41*  
EXPANDED PERFORMANCE DATA  
MODEL: GPH1348M41*  
HEATING OPERATION  
Outdoor Ambient Temperature  
65  
60  
55  
50  
47  
45  
40  
35  
30  
25  
20  
17  
15  
10  
22.7  
12.2  
2.29  
11.2  
2.91  
9.9  
5
-5  
15.0  
8.1  
2.14  
9.5  
2.05  
7.0  
209  
26  
-10  
12.3  
6.6  
2.09  
8.7  
1.72  
5.9  
202  
21  
MBh  
Delta T  
KW  
AMPS  
COP  
EER  
HI PR  
LO PR  
57.2  
30.8  
3.90  
19.0  
4.29  
14.7  
372  
130  
54.1  
29.1  
3.83  
17.7  
4.14  
14.1  
357  
121  
51.0  
27.4  
3.75  
16.7  
3.97  
13.6  
343  
47.6  
25.6  
3.68  
15.8  
3.79  
13.0  
328  
45.5  
24.5  
3.63  
15.3  
3.66  
12.5  
320  
44.1  
23.7  
3.60  
15.0  
3.58  
12.2  
314  
41.0  
22.0  
3.53  
14.3  
3.39  
11.6  
302  
37.8  
20.3  
3.46  
13.7  
3.20  
10.9  
290  
32.8  
17.6  
2.48  
13.1  
3.86  
13.2  
278  
70  
30.2  
16.3  
2.43  
12.6  
3.64  
12.4  
265  
62  
27.8  
15.0  
2.38  
12.1  
3.42  
11.7  
255  
55  
26.3  
14.2  
2.36  
11.9  
3.27  
11.2  
249  
51  
25.3  
13.6  
2.34  
11.8  
3.17  
10.8  
244  
49  
20.1  
10.8  
2.24  
10.6  
2.63  
9.0  
17.6  
9.5  
2.19  
10.1  
2.35  
8.0  
235  
42  
226  
36  
217  
30  
113  
104  
98  
95  
87  
77  
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.  
MODEL: GPH1360M41*  
HEATING OPERATION  
Outdoor Ambient Temperature  
65  
60  
55  
50  
47  
45  
40  
35  
30  
25  
20  
17  
15  
10  
5
-5  
17.9  
9.2  
2.12  
12.0  
2.47  
8.4  
216  
27  
-10  
14.7  
7.5  
2.08  
11.0  
2.06  
7.1  
MBh  
Delta T  
KW  
AMPS  
COP  
EER  
HI PR  
LO PR  
69.8  
35.9  
4.80  
24.1  
4.25  
14.5  
385  
134  
66.0  
34.0  
4.71  
22.5  
4.10  
14.0  
369  
124  
62.2  
32.0  
4.62  
21.2  
3.94  
13.5  
354  
58.1  
29.9  
4.53  
20.1  
3.76  
12.8  
339  
55.5  
28.5  
4.47  
19.4  
3.63  
12.4  
331  
53.8  
27.7  
4.44  
19.1  
3.55  
12.1  
325  
50.0  
25.7  
4.35  
18.1  
3.36  
11.5  
312  
46.1  
23.7  
4.26  
17.3  
3.17  
10.8  
300  
39.1  
20.1  
2.41  
16.7  
4.76  
16.3  
287  
72  
36.1  
18.6  
2.36  
16.0  
4.47  
15.3  
274  
64  
33.3  
17.1  
2.32  
15.4  
4.19  
14.3  
263  
56  
31.4  
16.2  
2.30  
15.0  
4.00  
13.7  
257  
52  
30.3  
15.6  
2.28  
14.9  
3.88  
13.2  
252  
50  
27.1  
14.0  
2.24  
14.2  
3.54  
12.1  
243  
24.1  
12.4  
2.20  
13.4  
3.20  
10.9  
233  
37  
21.0  
10.8  
2.16  
12.8  
2.84  
9.7  
224  
31  
208  
21  
116  
107  
101  
97  
89  
80  
43  
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.  
PERFORMANCE TEST  
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor  
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:  
If conditions vary from this, results will change as follows:  
1. As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low  
and high side pressures and power will not change.  
2. As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will  
occur in low and high side pressures and power.  
A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.  
A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.  
A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.  
A properly operating unit should be within plus or minus 3 Amps of the typical value shown.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING DIAGRAMS  
GPH13[24-42]M41AB  
LPS  
SEE NOTE #8  
SEE NOTE #7  
YL/PK  
YL/PK  
PU  
SEE NOTE 4  
PU  
PU  
BK  
BK  
2
RD  
GR  
1
C
3
240  
BL  
PU  
208  
RD  
BK  
2
0
8
-
2
4
0
/
G
BL  
YL  
L2  
T2  
T1  
EBTDR  
RD  
24V  
BL  
BK  
RD  
NO  
R
K1  
SEE NOTE  
#6  
1
3
4
C
BL  
XFMR-R  
YL  
L1  
BK  
COM  
NC  
BL  
2
K1  
RD  
RD  
BK  
PU  
C
PU  
BR  
SPEED  
UP  
RD  
M1 M2  
BL  
BK  
BK  
1
/
GND  
PU  
6
0
OR  
PU  
BK  
BK  
C
C
Y
Y
C
OR  
RD  
C-RV  
BL/PK  
PU  
YL  
BL/PK  
LVJB  
PU  
BK  
CNT  
O
DC  
R-PS1  
PS2  
RD  
BK  
YL  
H
BR  
O-RV  
W
PU  
CCR  
LVDR  
HPS  
T
WH  
PU  
RD  
WH  
PLF  
3
2
1
H
E
R
M
O
S
T
YL  
RD  
GR  
WH  
OR  
BR  
BL  
Y
RD  
YL  
R
R
R
G
W1  
O
W2  
C
6
5
4
9
8
C
F
HVDR  
DF1  
R-DFT  
DFT  
DF2  
BR  
RD  
RCCF  
SA  
A
T
7
RD  
++  
PU  
BR  
BL  
CONTROL  
BOX  
BK  
BK  
SEE NOTE #5  
PU  
PU  
RD  
SEE NOTE #3  
BK  
RD  
RD  
C
(TRANS240V)  
CH  
GR  
BK  
RD  
BK  
BR  
RD  
PU (M1)  
LOW  
RD  
YL  
BL  
PU  
BK  
BR  
CM  
S
R
(COM)BK  
HIGH  
BR  
PU  
EM  
RD  
EM  
3 SPEED  
BR  
DFT  
2 SPEED  
OPTIONAL  
BK  
COMP  
FC  
CHS  
FC  
BK  
BK  
RVC  
SEE NOTE #3  
L1  
L2  
SUPPLY VOLTAGE  
208-240/1/60  
SEE NOTE 3  
CHS  
COMPONENT LEGEND  
FACTORY WIRING  
LINE VOLTAGE  
LOW VOLTAGE  
OPTIONAL HIGH  
VOLTAGE  
CH  
BR  
C
BLOWER INTERLOCK RELAY  
CONTACTOR  
T2  
C
C
R
C
CCR  
CH  
CHS  
CM  
COMPRESSOR CONTACTOR RELAY  
CRANKCASE HEATER  
CRANKCASE HEATER SWITCH  
CONDENSER MOTOR  
T1  
COMP  
C
RCCF  
S
H
HVDR  
CM  
BR  
2 POLE ONLY  
SEE NOTE 7  
FIELD WIRING  
HIGH VOLTAGE  
LOW VOLTAGE  
F
COMP COMPRESSOR  
S.A.  
DC  
DEFROST CONTROL  
DEFROST THERMOSTAT  
DFT  
EBTDR ELECTRONIC BLOWER TIME DELAY RELAY  
SEE NOTE 5  
P
L
F
3
1
EM  
FC  
EVAPORATOR MOTOR  
FAN CAPACITOR  
1
3
4
GND  
HPS  
EQUIPMENT GROUND  
HIGH PRESSURE SWITCH  
HVDR HIGH VOLTAGE DEFROST RELAY  
WIRE CODE  
BK BLACK  
BL BLUE  
BR BROWN  
GR GREEN  
OR ORANGE  
PU PURPLE  
RD RED  
WH WHITE  
YL YELLOW  
2
LOW PRESSURE SWITCH  
LPS  
LVDR  
LVJB  
PLF  
LOW VOLTAGE DEFROST RELAY  
LOW VOLTAGE JUNCTION BOX  
FEMALE PLUG / CONNECTOR  
REVERSING VALVE COIL  
EBTDRM1  
M2  
SEE  
NOTE 2  
EBTDR  
NC  
COM  
EM  
RVC  
RCCF RUN CAPACITOR FOR  
FC  
COMPRESSOR AND FAN  
START ASSIST  
TRANSFORMER  
208-240  
2
SA  
TR  
SEE NOTE 4  
1
3
TR  
24V  
G
EBTDR  
R
NOTES:  
C
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS  
ORIGINAL (AT LEAST 105°C) USE COPPER CONDUCTOR ONLY.  
2. TO CHANGE EVAPORATOR MOTOR SPEED REPLACE LEAD ON EBTDR  
"COM" WITH LEAD ON EBTDR "M1" OR "M2".  
DFT  
3. CRANKCASE HEATER AND CRANKCASE HEATER SWITCH FACTORY  
EQUIPPED WHEN REQUIRED.  
4. FOR 208 VOLT TRANSFORMER OPERATION MOVE PURPLE WIRES  
FROM TERMINAL 3 TERMINAL 2 ON TRANSFORMER.  
5. START ASSIST FACTORY EQUIPPED WHEN REQUIRED.  
6. USE COPPER CONDUCTORS ONLY ++ USE N.E.C. CLASS 2 WIRE.  
7. DOUBLE POLE CONTACTOR SHOWN. SINGLE POLE CONTACTOR  
COULD BE FACTORY EQUIPPEDAS AN ALTERNATE CONFIGURATION.  
8. COMMON SIDE OF CONTACTOR CAN NOT BE GROUNDED OR  
CONNECTED TO ANY OTHER COMMON (24V).  
RVC  
C-RV  
O-RV  
R
R-DFT  
DFT  
R
C
DC  
Y
O
W
R-PS1  
LPS  
PS2  
CNT  
4
5
6
P
L
F
C
HPS  
SEE UNIT RATING PLATE FORTYPE AND SIZE  
OF OVER CURRENT PROTECTION  
R
W2  
O
W1  
Y
G
C
208-240/1/60 0140G01745-A  
THERMOSTAT  
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING DIAGRAMS  
GPH13[48-60]M41AB  
SEE NOTE 8  
SEE NOTE 3  
SEE NOTE 7  
PU  
LPS  
BK  
2
PU  
PU  
BK  
1
C
BL  
3
208  
240  
YL/PK  
YL/PK  
PU  
2
BL  
BL  
0
8
-
2
4
0
/
T2  
T1  
L2  
C
RD  
24V  
RD  
YL  
BL  
SEE NOTE 5  
BL  
L1  
BK  
BK  
PU  
YL  
BK  
BL  
PU  
1
/
RD  
BK  
PU  
GND  
GR  
GR  
60  
C
Y
Y
C
C
OR  
RD  
C-RV  
RD  
PU  
OR  
PU  
BK  
CNT  
O
DC  
R-PS1  
PS2  
PU  
RD  
RD  
RD  
YL  
BR  
O-RV  
W
PU  
WH  
CCR  
LVDR  
LVJB  
GR  
T
H
E
R
M
O
S
T
WH  
PLF  
WH  
YL  
RD  
GR  
WH  
OR  
BR  
BL  
R
R
BL  
R
G
W1  
O
W2  
C
YL  
BL  
BK  
WH  
3
6
5
4
9
8
7
H
C
F
HVDR  
DF1  
GR  
R-DFT  
DFT  
DF2  
2
1
BR  
RCCF  
RD  
RD  
A
T
YL  
RD  
YL  
++  
PU  
BR  
BK  
BK  
BK  
PU  
PU  
SA  
RD  
SEE NOTE 4  
PU  
YL  
SEE  
NOTE 6  
WH  
PU  
RD  
BL/PK  
BL/PK  
BK  
CH  
GR  
CONTROL  
BOX  
BR  
CM  
YL  
RD RD  
RD  
BK  
RD  
GR  
CHS  
C
1
L
2
G
3
N
S
C
R
4
5
DFT  
RVC  
BKBK  
HPS  
BK  
SEE NOTE 6  
BK  
EM  
COMP  
SEE NOTE 2  
L1  
L2  
SUPPLY VOLTAGE  
208-240/1/60  
COMPONENT LEGEND  
CONTACTOR  
FACTORY WIRING  
LINE VOLTAGE  
LOW VOLTAGE  
OPTINAL HIGH  
VOLTAGE  
C
T2  
C
CCR  
COMPRESSOR CONTACTOR RELAY  
R
COMP  
C
T1  
CH  
CRANKCASE HEATER  
C
C
CHS  
CM  
CRANKCASE HEATER SWITCH  
CONDENSER MOTOR  
RCCF  
S
H
HVDR  
CM  
COMP  
COMPRESSOR  
2 POLE ONLY  
SEE NOTE 7  
FIELD WIRING  
HIGH VOLTAGE  
LOW VOLTAGE  
F
DC  
DEFROST CONTROL  
S.A.  
SEE NOTE 4  
DFT  
EM  
DEFROST THERMOSTAT  
EVAPORATOR MOTOR  
GND  
HVDR  
LPS  
LVDR  
LVJB  
PLF  
EQUIPMENT GROUND  
HIGH VOLTAGE DEFROST RELAY  
LOW PRESSURE SWITCH  
LOW VOLTAGE DEFROST RELAY  
LOW VOLTAGE JUNCTION BOX  
FEMALE PLUG / CONNECTOR  
REVERSING VAVLE COIL  
RUN CAPACITOR FOR  
WIRE CODE  
BK BLACK  
BL BLUE  
BR BROWN  
GR GREEN  
OR ORANGE  
PU PURPLE  
RD RED  
SEE NOTE 6  
CHS  
RVC  
RCCF  
CH  
SEE NOTE 2  
EM  
L
N
COMPRESSOR AND FAN  
START ASSIST  
3
2
SA  
WH WHITE  
YL YELLOW  
TR  
TRANSFORMER  
G
1
HPS  
HIGH PRESSURE SWITCH  
208-240  
2
SEE NOTE 3  
1
3
NOTES:  
TR  
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS  
ORIGINAL (AT LEAST 105°C) USE COPPER CONDUCTOR ONLY.  
2. TO CHANGE EVAPORATOR MOTO R SPEED MOVE WHITE AND YELLOW  
LEADS FROM EM"2" AND "3" TO "4" AND "5". IF BOTH LEADS ARE  
ENERGIZED, THE HIGHER SPEED SETTING IS USED.  
24V  
DFT  
RVC  
O-RV  
R
C-RV  
R-DFT  
R-PS1  
DFT  
R
C
3
FOR 208 VOLT TRANSFORMER OPERATION MOVE PURPLE WIRES FROM  
DC  
Y
TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.  
4. START ASSIST FACTORY EQUIPPED WHEN REQUIRED  
5. USE COPPER CONDUCTORS ONLY  
++ USE N.E.C. CLASS 2 WIRE  
6. CRANKCASE HEATER AND CRANKCASE HEATER SWITCH FACTORY  
EQUIPPED WHEN REQUIRED.  
7. DOUBLE POLE CONTACTOR SHOWN. SINGLE POLE CONTACTOR  
COULD BE FACTORY EQUIPPED AS AN ALTERNATE CONFIGURATION.  
8. COMMON SIDE OF CONTACTOR CAN NOT BE GROUNDED OR  
CONNECTED TO ANY OTHER COMMON (24V).  
O
W
PS2  
CNT  
LPS  
HPS  
2
3
C
EM  
1
4
5
6
SEE NOTE 2  
PLF  
SEE UNIT RATING PLATE FOR TYPE AND SIZE  
OF OVER CURRENT PROTECTION  
C
R
O
W1  
Y
G
C
W2  
THERMOSTAT  
208-240/1/60 0140G01640-A  
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Everpure Water System EV9325 04 User Manual
Fisher Price Baby Toy x3189 User Manual
Foundations Baby Furniture 100 SSE User Manual
Fundex Games Games Billionaire User Manual
Gefen TV Cables EXT DVIRS232 1FO User Manual
Gemini CD Player CD 9500 User Manual
Genesis ICE Cordless Drill GCD18BK User Manual
GE Range 10 95 CG User Manual
Gianni Industries Door DG 15LD User Manual
Goodman Mfg Air Conditioner goodman High Efficiency 2 to 5 Ton Split System Air Conditioner User Manual