GE Power Hammer AK 50 User Manual

DEH–40028A Installation Instructions  
ProTrip™ Conversion Kits  
g
For GE Types AK-50, AKU-50, AKS-50,  
AKT-50, AK-75, and AK-100 Low-Voltage  
Power Circuit Breakers  
INTRODUCTION  
GE Conversion Kits are designed for upgrading  
existing GE low-voltage power circuit breakers,  
rather than replacing the entire breaker. The Con-  
version Kits include ProTrip™ Trip Units, the latest  
technological advance in GE trip system s.  
ProTrip Conversion Kits are designed and tested to  
conform to ANSI Standard C37.59, allowing the  
retrofitter to properly install the kit and acceptance  
test the breaker.  
This publication covers installation of ProTrip Con-  
version Kits on GE types AK-50, AKU-50, AKS-50,  
AKT-50, AK-75, and AK-100 low-voltage power circuit  
breakers. Each Conversion Kit contains all the  
com ponents needed to convert from an existing GE  
type EC trip system .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIST OF FIGURES  
1. Relocation and rem ounting of the W and X relays................................................................................. 5  
2. New X and W relay m ounting brackets................................................................................................... 5  
3. Flux shifter assem bly. .............................................................................................................................. 6  
4. Pattern for flux shifter m ounting holes in the side fram e ...................................................................... 6  
5. Flux shifter assem bly m ounted to the side fram e. ................................................................................. 6  
6. Location of new hole in the flux shifter base.......................................................................................... 7  
7. Locations of new holes for m ounting the OFLO term inal block. ........................................................... 7  
8. Existing trip paddles to be rem oved. ...................................................................................................... 8  
9. Installing the new trip paddle. ................................................................................................................. 8  
10. Adjusting the flux shifter. ........................................................................................................................ 8  
11. Mounting hole drill pattern for the trip unit m ounting plate. ................................................................ 9  
12. Trip unit m ounting plate attached to the breaker front channel. ........................................................... 9  
13. Trip unit m ounting bracket attached to the m ounting plate. ............................................................... 10  
14. Actuator bracket attached to the left pole link. ..................................................................................... 11  
15. Drill pattern for actuator bracket m ounting holes. ............................................................................... 11  
16. Existing EC trip devices before rem oval. .............................................................................................. 12  
17. Rem oval of EC trip devices.................................................................................................................... 12  
18. Parts provided for CT installation per pole. .......................................................................................... 13  
19. CT post m ounted in the breaker back fram e......................................................................................... 13  
20. CT installation com pleted.. .................................................................................................................... 13  
21. Phase sensor installation on AK-75 & AK-100 breakers........................................................................ 14  
22. Attaching the trip unit to the m ounting plate ....................................................................................... 15  
23. Trip unit m ounted on the breaker. ........................................................................................................ 15  
24. Fourth-wire term inal board installation on AK-50 & AKS-50 stationary breakers............................... 16  
25. Fourth-wire disconnect installed on AK-50 & AKS-50 draw-out breakers. .......................................... 17  
26. Fourth-wire disconnect assem bly for AKD-5 or AKD-6 equipm ent...................................................... 17  
27. Fourth-wire disconnect assem bly for AKD equipm ent......................................................................... 17  
28. K-75 & AK-100 back fram e conversion. ................................................................................................. 18  
29. Outline of the neutral sensor for AK-50 breakers.................................................................................. 19  
30. Outline of the neutral sensor for AK-75 and AK-100 breakers.............................................................. 20  
31. AK-50 & AKS-50 fourth-wire disconnect for AKD. ................................................................................ 21  
32. AK-75 & AK-100 fourth-wire disconnect for AKD-5 & AKD-6. .............................................................. 21  
33. AK-100 fourth-wire disconnect for AKD. ............................................................................................... 21  
34. AK-50 & AKS-50 fourth-wire disconnect for AKD. ................................................................................ 22  
35. Fourth-wire disconnect for AKD-5 & AKD-6. ......................................................................................... 22  
36. Cabling diagram for ProTrip™ trip units with ground fault on four-wire loads. ................................ 25  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 1. GENERAL INFORMATION SECTION 2. BEFORE INSTALLATION  
GE Conversion Kit installation is straightforward, but  
does require careful workm anship and attention to  
these instructions. Fam iliarity with the breaker is  
highly desirable. The general approach is to first  
rem ove the existing trip devices from the breaker,  
then install the ProTrip com ponents. Following this  
procedure, the converted breaker is perform ance  
tested before it is returned to service.  
Before starting any work, turn off and lock out all  
power sources leading to the breaker, both prim ary  
and secondary. Rem ove the breaker to a clean, well-  
lighted work area.  
WARNING: Low-voltage power circuit breakers use  
high-speed, stored-energy spring operating  
m echanism s. The breakers and their enclosures  
contain interlocks and safety features intended to  
provide safe, proper operating sequences. For  
m axim um personnel protection during installation,  
operation, and m aintenance of these breakers, the  
following procedures m ust be followed. Failure to  
follow these procedures m ay result in personal  
injury or property dam age.  
The m ajority of trip unit kit installations do not  
require any custom ized assem bly work. However,  
som e conversions m ay involve unusual m ounting  
conditions or accessory com binations that require  
m inor m odifications and/or relocation of com po-  
nents. In m ost instances, this supplem entary work  
can be done on site.  
Only qualified persons, as defined in the  
National Electrical Code, who are fam iliar with  
the installation and m aintenance of low-voltage  
power circuit breakers and switchgear assem -  
blies, should perform any work on these break-  
ers.  
In preparation for the conversion, the installer should  
verify that the appropriate current sensors and trip  
unit have been furnished. Whenever a ProTrip kit is  
installed on a breaker with a four-wire system , an  
associated neutral sensor (CT) is required for  
separate m ounting in the equipm ent. Ensure that  
retrofitted breakers are applied within their short-  
circuit ratings. For exam ple, if the previous trip unit  
provided long-tim e instantaneous protection, the  
short-tim e rating of the ProTrip Trip Unit will govern  
the application.  
Com pletely read and understand all instructions  
before attem pting any breaker installation,  
operation, m aintenance, or m odification.  
Turn off and lock out the power source feeding  
the breaker before attem pting any installation,  
m aintenance, or m odification. Follow all lock-  
out and tag-out rules of the National Electrical  
Code and all other applicable codes.  
As a service-related consideration, the installation of  
a ProTrip kit provides an excellent opportunity to  
perform norm al m aintenance on the breaker, par-  
ticularly when the front and back fram es are sepa-  
rated. Such procedures are described in the instal-  
lation and m aintenance m anuals supplied with the  
breaker and equipm ent.  
Do not work on a closed breaker or a breaker  
with the closing springs charged. Trip an OPEN  
breaker and be sure the stored-energy springs  
are discharged, thus rem oving the possibility  
that the breaker m ay trip OPEN or the closing  
springs discharge and cause injury.  
Trip the breaker OPEN, then rem ove the breaker  
to a well-lighted work area before beginning  
work.  
Do not perform any m aintenance that includes  
breaker charging, closing, tripping, or any other  
function that could cause significant m ovem ent  
of a draw-out breaker while it is on the draw-out  
extension rails.  
Do not leave the breaker in an interm ediate  
position in the switchgear com partm ent. Always  
leave it in the CONNECTED, TEST, or  
DISCONNECTED position. Failure to do so could  
lead to im proper positioning of the breaker and  
flashback.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 3. FRONT FRAME BREAKER  
CONVERSION  
Front fram e conversion consists of the following  
steps:  
1. Separation of the front and back breaker fram es  
for AK-50, AKU-50, AKS-50, and AKT-50 breakers.  
(Fram e separation is not necessary for AK-75 and  
AK-100 breakers.) Refer to the appropriate  
installation and m aintenance m anuals supplied  
with the breakers and equipm ent for instructions  
on fram e separation. Copies of these publications  
m ay be obtained from your local GE sales office.  
2. Relocation and rem ounting the W and X relays  
on AK-50, AK-75, and AK-100 electrically operated  
breakers with EC trip devices.  
3. Installation of the flux shifter assem bly and trip  
paddle.  
4. Installation of the trip unit m ounting bracket.  
5. Installation of the trip unit wiring harness.  
Relocating and Rem ounting the W and X  
Relays  
This step is necessary on electrically operated  
breakers with EC trip devices. Figure 1 illustrates this  
process. Figure 2 shows the new m ounting brackets  
supplied with the kit.  
1. Rem ove the W relay and install the m ounting  
bracket supplied with the conversion kit to the  
upper left side of the fram e  
2. Rem ove the X relay and its m ounting bracket.  
Use the new bracket supplied with the conver-  
sion kit to rem ount the X relay in its existing  
position.  
Figure 1. Relocation and remounting of the W and X relays.  
W Relay  
X Relay  
Figure 2. New X and W relay mounting brackets.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the Flux Shifter Assem bly  
The installation procedure for the flux shifter  
assem bly, illustrated in Figure 3, varies depending  
on the type of breaker and existing trip device. In  
som e cases, m ounting holes m ust be added, term i-  
nal blocks relocated, or breaker side rails rem oved.  
Breakers w ith EC or Pow er Sensor Trip System s  
1. Drill the flux shifter m ounting holes in the left  
side of the breaker fram e. The m ounting hole  
pattern is illustrated in Figure 4. A full-size tem -  
plate is provided in the Appendix.  
2. Mount the new flux shifter to the inside of the  
side fram e with the three screws, lock washers,  
flat washers, and nuts supplied, as shown in  
Figure 5. Insert the screws from the outside of  
the side fram e.  
Figure 4. Pattern for flux shifter mounting holes in the side frame.  
Mounting  
Screws  
Flux Shifter  
Assembly  
Figure 5. Flux shifter assembly mounted to the side frame.  
Figure 3. Flux shifter assembly.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Breakers w ith a Side Bracket  
1. Drill a 3 4” diam eter hole into the flux shifter  
assem bly m ounting base to provide the neces-  
sary clearance for the bracket. The location of the  
new hole is shown in Figure 6.  
2. Rem ove the side bracket from the fram e and drill  
the holes according to the pattern in Figure 4. A  
full-size tem plate is provided in the Appendix.  
After the holes are drilled, return the side bracket  
to its original location.  
3. Mount the new flux shifter to the inside of the  
side fram e with the three screws, lock washers,  
flat washers, and nuts supplied, as shown in  
Figure 5. The upper two screws are inserted from  
the outside of the fram e, while the lower screw  
m ust be inserted from the inside.  
Figure 6. Location of new hole in the flux shifter base.  
AKU-50 Breakers Only  
For easier installation of the new flux shifter  
assem bly on AKU-50 breakers, the open-fuse lockout  
(OFLO) m ay be rem oved from the breaker.  
1. Rem ove the three bolts attaching the OFLO to the  
base of the breaker.  
2. The OFLO term inal block m ust be relocated on  
the upper left side of the breaker. Som e parts and  
tool, not provided with the kit, are necessary for  
this task:  
Six strips of 14 AWG wire  
Wire splice  
12 butt splices  
Wire labels  
Drill and size F bit  
5/16-18 tap  
Figure 7. Locations of new holes for mounting the OFLO terminal  
block.  
Flathead screw driver  
5
Two /16-18 bolts and lock washers  
5
3. Drill and tap two holes for the /16-18 bolts. Fig-  
ure 7 shows the hole locations.  
4. Rem ove the three bolts securing the OFLO to the  
breaker and lift off the OFLO device.  
5. Rem ove the wires that connect the OFLO device  
to the term inal block.  
6. Cut the wires that connect to the coils where they  
join and label the wires. Attach butt splices to all  
twelve open ends.  
7. Connect the strands of wire to the OFLO. Mount  
the term inal block in its new location. DO NOT  
com plete the wire connections until the flux  
shifter is installed.  
8. Install the new flux shifter assem bly as described  
above and shown in Figure 5.  
9. Connect the cables attached to the term inal block  
and tie them together.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Breakers w ith ECS or SST Trip System s  
1. Rem ove the ECS or SST trip unit.  
2. Rem ove the existing flux shifter device and the  
trip unit control harness.  
3. Install the new flux shifter assem bly as described  
above and shown in Figure 5.  
Installing the Trip Paddle  
For breakers equipped with an ECS or SST trip sys-  
tem , the existing trip paddle is used with the new  
flux shifter.  
Trip Paddles  
For all other breakers, the existing trip paddles m ust  
be rem oved and the new trip paddle installed as  
follows:  
1. Rem ove and discard the three trip paddles on the  
trip actuator bar, as shown in Figure 8.  
Figure 8. Existing trip paddles to be removed.  
2. Assem ble the trip paddle and the threaded back  
3
plate by inserting two of the 10-32 x  
4" screws  
1”  
and lock washers provided along the top edge.  
3. Slip the trip paddle over the trip actuator bar  
approxim ately one inch from the side fram e, as  
shown in Figure 9. Insert the rem aining 10-32 x  
3
4" screw and tighten the other screws to  
secure the trip paddle in place.  
Adjusting the Flux Shifter  
After the flux shifter and trip paddle are installed and  
the breaker fram es are reassem bled, the following  
adjustm ents m ust be m ade.  
Trip  
Paddle  
1. With the breaker OPEN and the m echanism  
charged, set the gap between the trip paddle and  
the end of the flux shifter rod at 0.10 inch, as  
shown in Figure 10. Use a 0.10-inch diam eter rod.  
Set the adjuster end of the trip rod and lock it in  
place with the jam nut. Note that rem oval of the  
buffer stud will m ake the trip paddle easier to  
install and adjust.  
Figure 9. Installing the new trip paddle.  
2. As the crossbar travels between the breaker  
CLOSED and OPEN positions, the tang of the  
actuator bracket m ust clear the buffer stud. If  
there is insufficient clearance, loosen the two  
m ounting screws and rotate the bracket clock-  
wise to take up m ounting hole slack. Retighten  
the screws.  
3. Optional Test – The flux shifter m ay be tested by  
closing the breaker and applying a 9 Vdc power  
source to the flux shifter leads (the red wire is  
positive). The breaker should trip.  
Figure 10. Adjusting the flux shifter.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the Trip Unit Mounting Bracket  
The new ProTrip trip unit m ounts to the left side of  
the front channel. A m ounting bracket is shock--  
m ounted to a plate that is assem bled to the front  
channel.  
EC or Pow er Sensor Trip System  
1. The holes for the new m ounting plate m ay have  
to be added to the front channel. The drill pattern  
is shown in Figure 11, with a full-size tem plate in  
1
the Appendix. Tap the holes for /4-20 screws.  
2. Attach the new m ounting plate, as shown in  
1
Figure 12, with two short /4-20 screws and lock  
1
washers on the top and the single long /4-20  
screw and lock washer on the bottom . Be sure to  
insert the spacer between the m ounting plate and  
the breaker channel, as shown.  
3. Attach the trip unit m ounting bracket to the plate  
with two screws, lock washers, and flat washers,  
as shown in Figure 13.  
ECS or SST Trip System  
Figure 11. Mounting hole drill pattern for the trip unit mounting  
plate.  
Rem ove the existing m ounting plate and bracket.  
Install the new m ounting plate and bracket, using the  
holes closest to the front of the breaker, as described  
in steps 2 and 3 above.  
If the m anual indicator assem bly busing on AK-50  
m anual breakers interferes with the m ounting  
bracket installation, then the bracket m ust be m odi-  
fied. Cut off a 3/4 x 11/2 inch section from the right  
front of the plate to provide clearance.  
Figure 12. Trip unit mounting plate attached to the breaker front  
channel.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 13. Trip unit mounting bracket attached to the mounting  
plate.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 4. BACK FRAME  
CONVERSION  
Left Pole  
Link  
The back fram e conversion consists of the following  
operations:  
1. Modification of the crossbar assem bly for the  
flux shifter installation.  
2. Rem oval of the existing trip devices.  
3. Installation of the phase sensors.  
4. Installation of the back fram e harness.  
Actuator  
Bracket  
Crossbar Modification  
The flux shifter reset linkage is driven by the actuator  
bracket, as shown in Figure 3. The actuator bracket  
m ust be assem bled to the left side link of the left  
pole, as shown in Figure 14.  
Figure 14. Actuator bracket attached to the left pole link.  
If the actuator bracket m ounting holes are not in the  
left side link, the holes m ust be added. Drill and tap  
two /16-18 holes using the pattern in Figure 15. A  
5
full-size tem plate is provided in the Appendix.  
Figure 15. Drill pattern for actuator bracket mounting holes.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Coil Mounting  
Bolts  
Rem oving the Existing Trip Devices  
AK-50 & AKS-50 Breakers w ith EC or Pow er Sensor  
Trip System s  
1. Rem ove and discard the two screws at the base  
of each trip device, as shown in Figure 16. Dis-  
card the m etal m ounting brackets.  
2. Rem ove and discard the sm all Philips-head  
screw at the top of each trip device.  
5
3. Rem ove and discard the four  
16" Allen-head  
bolts securing each trip coil. The coil can then be  
lifted off and rem oved. Figure 17 shows one trip  
com pletely rem oved, one with the cover  
rem oved, and one still in place.  
Cover Screws  
and Clamps  
Figure 16. Existing EC trip devices before removal.  
AK-50 & AKS-50 Breakers w ith SST Trip System s  
Rem ove the existing SST phase sensors in prepara-  
tion for installing the new sensors.  
AK-75 & AK-100 Breakers w ith EC or Pow er Sensor  
Trip System s  
Rem ove the existing trip devices and harnesses and  
discard.  
AK-75 & AK-100 Breakers w ith SST Trip System s  
The new ProTrip phase sensors are visually identical  
to the SST sensors. Rem ove the existing sensors and  
discard.  
Figure 17. Removal of EC trip devices.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the Phase Sensors  
AK-50 & AKS-50 Breakers  
Figure 18 shows the parts provided for assem bly of  
the CT on each pole.  
1. Mount the new copper CT post to the back fram e  
3
with the two  
8-16 x 11 2" bolts, flat washers,  
and lock washers provided, as shown in Figure  
19.  
2. Fasten the three sm all insulated wire fasteners to  
Figure 18. Parts provided for CT installation for one pole.  
1
the back fram e with the  
4-20 x 13 4" screws  
provided, as shown in Figure 20. One fastener is  
m ounted under each CT.  
3. Place a CT over each copper post, first applying a  
sm all am ount of RTV or sim ilar adhesive to  
prevent the CTs from rotating.  
4. Mount the top copper bus over each CT and  
1
secure with the  
2-13 x 11 2" Allen-head bolts,  
lock washers, and flat washers provided.  
3
5. Insert two  
8-16 x 11 2" bolts, lock washers, and  
flat washers through each top copper bus into  
the contact arm assem bly.  
3
1
6. Tighten the  
8-16 bolts to 200 in-lb and the  
2-  
13 bolts to 300 in-lb.  
WARNING: Step 6 ensures critical electrical integrity  
connections. The designated bolts m ust be correctly  
tightened for proper operation. Failure to tighten  
these bolts properly will cause a breaker failure,  
resulting in property dam age and/or personal  
injury.  
Figure 19. CT post mounted in the breaker back frame.  
Top Copper  
Bus  
1
2-13  
Bolt  
3
8-16  
Bolts  
Wire  
Fastener  
Wire  
Harness  
Figure 20. CT installation completed..  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AK-75 & AK-100 Breakers  
1. The ProTrip phase sensors m ount on the upper  
breaker studs, as shown in Figure 21. The sen-  
sors held on the stud with locking rings. Leave  
enough of the stud exposed for the prim ary fin-  
gers to engage. Engage the sensors antiturn lugs  
with the notch in the locking ring. Before  
tightening the locking rings, position each sensor  
so that its leads exit between the pole bases, as  
shown.  
2. Mount the three sensor term inal boards to the  
rear of the back fram e using the hardware pro-  
vided.  
3. Form each sensors leads downward between the  
pole bases.  
Figure 21. Phase sensor installation on AK-75 & AK-100 breakers.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 5. INSTALLING THE TRIP  
UNIT  
1. Rem ove the large screw from the rear of the trip  
unit. Place the trip unit in position on the m ount-  
ing plate, with the 50-pin connector aligned with  
the opening in the plate. Secure with the large  
screw, as shown in Figure 22.  
Trip Unit  
Mounting  
Plate  
2. Insert the 50-pin fem ale connector on the wiring  
harness into the trip unit connector through the  
rear of the m ounting plate. Secure to the m ount-  
ing plate with the two sm all screws provided, as  
shown in Figure 22.  
Trip  
Unit  
3. Place the trip unit and m ounting plate in position  
on the support bracket m ounted on the breaker.  
Secure with the three screws, lock washers, and  
flat washers through the holes in the m ounting  
plate into the tapped holes in the bracket, as  
shown in Figure 23.  
Trip Unit  
Mounting  
Screw  
Wiring  
Harness  
Connector  
Configuring the Trip Unit  
See DEH-40034 for detailed instructions for setting  
up ProTrip trip units.  
Figure 22. Attaching the trip unit to the mounting plate.  
Figure 23. Trip unit mounted on the breaker.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 6 FOUR-WIRE GROUND  
FAULT OPTION  
The ground fault option for four-wire installations  
requires the installation of an additional current  
sensor on the neutral bus in the equipm ent. The  
sensor is connected to the trip unit through the  
connector provided in the wiring harness.  
Installing the Fourth-Wire Disconnect  
AK-50 & AKS-50 Stationary Breakers  
The fourth-wire disconnect for stationary breakers  
consists of a term inal board m ounted to the lower  
front channel, as shown in Figure 24.  
If the term inal board is already present on the  
breaker, just replace the control harness. Main-  
tain the following color code: white wire to  
com m on, black wire to the tap.  
If the term inal board m ust be added, m ount it as  
shown in Figure 24. The m ounting holes m ay  
have to be added to the front channel.  
Figure 24. Fourth-wire terminal board installation on AK-50 &  
AKS-50 stationary breakers.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AK-50 & AKS-50 Draw -Out Breakers  
The fourth-wire disconnect for AK-50 and AKS-50  
draw-out breakers m ounts to the lower back fram e,  
as shown in Figure 25.  
If the term inal board is already present on the  
breaker, just replace the control harness. Main-  
tain the following color code: white wire to  
com m on, black wire to the tap.  
If the disconnect m ust be added, m ount it as  
shown in Figure 25.  
AK-75 & AK-100 Draw -Out Breakers  
Figure 25. Fourth-wire disconnect installed on AK-50 & AKS-50  
draw-out breakers.  
There are two fourth-wire disconnect designs used  
with these breakers. One design is used on breakers  
for GE type AKD switchgear, while the other applies  
to breakers for GE types AKD-5 and AKD-6  
equipm ent. The only difference is the bracket used  
for m ounting the disconnect to the breaker. Figures  
26 and 27 show these two designs.  
The conversion kit contains an assem bled, ready-to-  
install m ounting block and bracket for AKD-5 and  
AKD-6 installation, plus an addition bracket only for  
type AKD equipm ent installations. For AKD equip-  
m ent, rem ove the bracket from the assem bled dis-  
connect and replace it with the AKD bracket.  
Figure 26. Fourth-wire disconnect assembly for AKD-5 or AKD-6  
equipment.  
The fourth-wire disconnect for AK-75 and AK-100  
draw-out breakers m ounts to the lower back fram e  
as shown in Figure 28.  
If the term inal board is already present on the  
breaker, just replace the control harness. Main-  
tain the following color code: white wire to  
com m on, black wire to the tap.  
If the disconnect m ust be added, m ount it as  
shown in Figure 28.  
Figure 27. Fourth-wire disconnect assembly for AKD equipment.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 28. AK-75 & AK-100 back frame conversion.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the Neutral Sensor  
The neutral sensor is an electrical duplicate of the  
phase sensor, including the taps. Therefore, when  
taps (if provided) are changed on the phase sensors,  
the taps on the neutral sensor m ust be sim ilarly  
changed. For kits with fixed phase sensors, be sure  
to use the corresponding tap on the neutral sensor.  
Mount the neutral sensor on the outgoing neutral  
lead, norm ally in the equipm ent bus or cable com -  
partm ent. Figure 29 shows m ounting details for the  
neutral sensor for AK-50 breakers, while Figure 30  
covers AK-75 and AK-100 breakers.  
Figure 29. Outline of the neutral sensor for AK-50 breakers.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 30. Outline of the neutral sensor for AK-75 and AK-100 breakers  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 7. EQUIPMENT  
CONVERSION  
Installing Mounting Brackets  
The equipm ent com partm ent contains the m ating  
portions of the fourth-wire disconnect and the neu-  
tral sensor. The sam e disconnect assem bly is used  
for types AKD, AKD-5, and AKD-6 switchgear.  
Mounting brackets for AKD, AKD-5, AKD-6, and  
AKD-8 switchgear applications are included in the  
conversion kit. Figures 31, 32, 33, 34, and 35 are  
m ounting diagram s for the various applications.  
Table 1 is a key to the num bers used in these figures  
to indicate various hardware item s.  
Figure 31. AK-50 & AKS-50 fourth-wire disconnect for AKD.  
Legend Description  
225 Breaker portion of fourth-wire disconnect  
226 Equipm ent portion of fourth-wire disconnect  
Mounting bracket for AK-100 for AKD  
com partm ents  
229  
230 10-32 x 1.375 inch m ounting screw  
231 Insulation  
232 # 10 lock washer  
233 # 10 flat washer  
235 1/8-20 flat washer  
236 1/8-20 lock washer  
237 1/4-20 nut  
Figure 32. AK-75 & AK-100 fourth-wire disconnect for AKD-5 &  
AKD-6.  
238 1/4-20 x 1.25 inch m ounting screw  
239 Bracket  
Table 1. Legend for number symbols appearing in Figures 31–  
35.  
Figure 33. AK-100 fourth-wire disconnect for AKD.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 34. AK-50 & AKS-50 fourth-wire disconnect for AKD.  
Figure 35. Fourth-wire disconnect for AKD-5 & AKD-6.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ter or m illivolt tester. If the resistance differs  
considerably from phase to phase, the electrical  
connections m ay not be properly tightened or it  
could also indicate im proper contact wipe.  
SECTION 8. TESTING AND TROUBLE-  
SHOOTING  
WARNING: Do not change taps on the current sen-  
sors or adjust the trip unit settings while the  
breaker is carrying current. Failure to adhere to  
these instructions will void all warranties.  
4. To verify that the breaker has been properly  
retrofitted, perform a prim ary injection test on  
each phase. This test will check the CTs, bus,  
wiring harness, flux shifter, and trip unit as a  
com plete system .  
Testing  
a. A high-current, low-voltage power supply  
should be connected across each line and load  
term inal to sim ulate an overcurrent fault.  
Before installing a converted breaker back into  
service, perform the following steps:  
b. Set the long-tim e trip at 0.5 to m inim ize the  
1. Verify that the trip unit is securely installed by  
perform ing a continuity test on the CT wiring and  
the trip unit.  
breaker stress.  
c. When ground fault is installed, the test can be  
perform ed by wiring two adjacent poles in  
series or by using the GE Digital Test Kit, cat.  
no. TVRMS2. This will prevent the breaker  
from tripping because of an unbalanced cur-  
rent flow.  
a. Disconnect the black CT wires at each phase  
sensor.  
b. Check for continuity with a continuity tester or  
VOM from the white lead of the phase A CT to  
the white lead of the phase B CT.  
c. Repeat this continuity test for the white leads  
CAUTION: Do not attem pt to use GE Test Kit cat. no.  
TVTS1 or TVRMS on this trip unit.  
of the phase A and phase C CTs.  
d. Measure the resistance across each phase  
sensor and com pare the values m easured to  
the values listed in Table 1.  
Trouble-Shooting  
e. Reconnect the black CT leads to all of the  
phase sensors. Ensure that this is done before  
continuing with perform ance testing of the  
breaker.  
When m alfunctioning is suspected, first exam ine the  
breaker and its power system for abnorm al condi-  
tions such as the following:  
The breaker is not tripping in response to over-  
current conditions or incipient ground faults.  
CAUTION: In addition to the continuity test described  
in Step 1 and before perform ance testing of the  
converted breaker, each phase of the breaker  
should be prim ary injected with a current level of  
about 10%, but no m ore than 20%, of the CT rating.  
During the application of test current, activate the  
trip unit screen by depressing the battery button on  
the trip unit face and check that the test current is  
displayed on the screen for each phase tested. If the  
trip unit fails to display the test current, stop the  
test im m ediately and verify the installation of the  
trip unit and wire harness before proceeding with  
any additional testing.  
The breaker is rem aining in a trip-free state  
because of m echanical interference along its trip  
shaft.  
The shunt trip (if present) is activating im prop-  
erly.  
Nuisance Tripping on Ground Fault-Equipped  
Breakers  
When nuisance tripping occurs on breakers equipped  
with ground fault trip, a probable cause is the  
existence of a false ground signal. Each phase sensor  
is connected to sum m ing circuitry in the trip unit.  
Under no-fault conditions on three-wire load circuits,  
the currents add to zero and no ground signal is  
developed. This current sum is zero only if all three  
sensors have the sam e electrical characteristics. If  
one sensor differs from the others (such as by a  
different rating or wrong tap setting), the circuitry  
can produce an output sufficient to trip the breaker.  
Sim ilarly, a discontinuity between any sensor and  
the trip unit can cause a false trip signal.  
WARNING: If the converted breaker is energized or  
tested by prim ary injection with a sufficiently high  
test current with a loose or open circuit between the  
CTs and the trip unit, dam age will occur to the trip  
unit, wire harness, 36-pin trip unit connector, and  
CTs. Failure to adhere to these instructions will void  
all warranties.  
The sensors and their connections should be closely  
exam ined if nuisance tripping is encountered on any  
breaker whose ProTrip trip unit has previously  
dem onstrated satisfactory perform ance. After dis-  
2. Check the insulation on the prim ary circuit with a  
1,000-volt Meggar.  
3. Measure the resistance across the line and load  
term inals for each phase using a m icro-ohm m e-  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
connecting the breaker from all power sources, per-  
form the following procedure:  
Breaker  
CT Rating, A  
Resistance, ohms  
300  
400  
600  
20–24  
27–32  
42–50  
1. Check that all phase sensors are the sam e type  
(current range).  
AK-50  
AKS-50  
2. Verify that the tap settings on all three phase sen-  
800  
58–68  
1200  
1600  
93–109  
130–154  
sors are identical.  
3. Verify that the wiring harness connections to the  
sensors have the proper polarity (white lead to  
com m on, black lead to tap), as shown in the  
cabling diagram in Figure 36.  
1200  
1600  
2000  
3000  
20–24  
28–34  
37–44  
61–72  
AK-75  
4. On ground fault breakers serving four-wire loads,  
check that the neutral sensor is properly con-  
nected, as indicated in Figure 36. In particular,  
check the following:  
1600  
2000  
3000  
4000  
36–43  
47–55  
75–88  
AK-100  
108–127  
a. Verify that the neutral sensor has the sam e rat-  
Table 2. CT resistance values.  
ing and tap setting as the phase sensors.  
b. Verify continuity between the neutral sensor  
and its equipm ent-m ounted secondary discon-  
nect block. Also check for continuity from the  
breaker-m ounted neutral secondary discon-  
nect block through to the trip unit wiring har-  
ness connector.  
c. If the breakers lower studs connect to the  
power source, then the neutral sensor m ust  
have its load end connected to the source.  
d. Verify that the neutral conductor is carrying  
only the neutral current associated with the  
breakers load current (the neutral is not  
shared with other loads).  
5. If the preceding steps fail to identify the problem ,  
then m easure the sensor resistances. The appro-  
priate values are listed in Table 2. Since the  
phase and neutral sensors are electrically  
identical, their resistances should agree closely.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 36. Cabling diagram for ProTrip™ trip units with ground fault on four-wire loads.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX – DRILL TEMPLATES  
Appendix 1. Drill Tem plate for Flux Shifter Mounting  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix 2. Drill Tem plate for Trip Unit Mounting  
Appendix 3. Drill Tem plate for Flux Shifter Mounting  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
These instructions do not cover all details or variations in equipm ent nor do they provide for every possible  
contingency that m ay be m et in connection with installation, operation, or m aintenance. Should further  
inform ation be desired or should particular problem s arise that are not covered sufficiently for the purchasers  
purposes, the m atter should be referred to the GE Com pany.  
g
GE Industrial System s  
General Electric Company  
41 Woodford Ave., Plainville, CT 06062  
DEH40028 R02
 
1198  
© 1998 General Electric Company  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Extron electronic Scanner SRI 200 User Manual
Extron electronic Universal Remote TLP 1000MV User Manual
Fisher Price Baby Accessories P0278 User Manual
Frigidaire Dishwasher 154881701 User Manual
Garmin Marine GPS System 4008 User Manual
GE Freezer FCM9DAWH User Manual
GE Monogram Range ZDP48L6RHSS6 User Manual
Gianni Industries Door AD 425S User Manual
Giant Bicycle GFR Series User Manual
Gigabyte Personal Computer GA K8N51GMF 9 RH User Manual