Frymaster Fryer YSCFC24GSERIES User Manual

Models YSCFC 1824G, 2424G, and 24/24/15 Systems  
with Built-In Filtration  
Frymaster Dean, a member of the Commercial Food Equipment Service Association,  
recommends using CFESA Certified Technicians.  
24-Hour Service Hotline  
PRINTED IN THE USA  
FEBRUARY 2009  
1-800-551-8633  
* 8 1 9 6 4 7 2 *  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DANGER  
The front ledge of the fryer is not a step. Do not stand on the fryer. Serious injury can result  
from slips or contact with the hot oil.  
WARNING  
Drawings and photos used in this manual are intended to illustrate operational, cleaning and  
technical procedures and may not conform to on-site management operational procedures.  
WARNING  
No structural material on the fryer should be altered or removed to accommodate placement of  
the fryer under a hood. Questions? Call the Frymaster Dean Service Hotline at 1-800-551-8633.  
This equipment is to be installed in compliance with the basic plumbing code of The Building  
Officials and Code Administrators International, Inc. (BOCA) and the Food Service Sanitation  
Manual of the Food and Drug Administration.  
COMPUTERS (WHERE APPLICABLE)  
FCC  
This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions:  
1) This device may not cause harmful interference, and 2) This device must accept any interference  
received, including interference that may cause undesired operation. While this device is a verified Class  
A device, it has been shown to meet the Class B limits.  
CANADA  
This digital apparatus does not exceed the Class A or B limits for radio noise emissions as set out by the  
ICES-003 standard of the Canadian Department of Communications.  
Cet appareil numerique n’emet pas de bruits radioelectriques depassany les limites de classe A et B  
prescrites dans la norme NMB-003 edictee par le Ministre des Communcations du Canada.  
DANGER  
THIS PRODUCT CONTAINS CHEMICALS KNOWN TO THE STATE OF CALIFORNIA TO CAUSE  
CANCER AND/OR BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM.  
Operation, installation, and servicing of this product could expose you to airborne particles of  
glasswool or ceramic fibers, crystalline silica, and/or carbon monoxide. Inhalation of airborne  
particles of glasswool or ceramic fibers is known to the State of California to cause cancer.  
Inhalation of carbon monoxide is known to the State of California to cause birth defects or other  
reproductive harm.  
WARNING  
Do not bang fry baskets or other utensils on the fryer’s joiner strip. The strip is present to seal  
the joint between the fry vessels. Banging fry baskets on the strip to dislodge shortening will  
distort the strip, adversely affecting its fit. It is designed for a tight fit and should only be  
removed for cleaning.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC Series Flatbottom Gas Fryers  
Service & Parts Manual  
TABLE OF CONTENTS  
PAGE #  
1.  
SERVICE PROCEDURES  
1–1  
1.1  
Functional Description  
1–1  
1.2  
Accessing Fryers for Servicing  
Cleaning Gas Valve Vent Tube  
Adjusting Burner Manifold Gas Pressure  
Calibrating the Thermatron Temperature Controller  
Replacing Fryer Components  
Remove/Replace Temperature Probe or High-Limit Thermostat  
Removing/Replacing Rocker Switches  
Replacing the Gas Valve  
1–3  
1.3  
1–4  
1.4  
1–4  
1.5  
1–5  
1.6  
1–6  
1.6.1  
1.6.2  
1.6.3  
1.6.4  
1.6.5  
1.6.6  
1.7  
1–6  
1–8  
1–9  
Replacing the Direct Spark Ignitor  
Removing/Replacing Blower Assembly or Air Prover Switch  
Replacing the Frypot  
1–9  
1–10  
1–11  
1–15  
1–16  
1–17  
1–19  
1–19  
1–21  
1–22  
1–22  
1–23  
1–24  
1–24  
1–25  
1–26  
Troubleshooting and Problem Isolation  
Ignition Failures  
1.7.1  
1.7.2  
1.7.3  
1.7.4  
1.7.5  
1.8  
Improper Burner Functioning  
Improper Temperature Control  
Filtration Problems  
Leakage  
Troubleshooting Guides  
1.8.1  
1.8.2  
1.9  
Main Burner Malfunctions  
Indicator Lights  
Wiring Diagrams  
1.9.1  
1.9.2  
1.9.3  
Wiring for Common Cabinet Flatbottom without Boil Out  
24/24 Filter Wiring  
18/24 Common Cabinet Transformer Box  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC Series Flatbottom Gas Fryers  
Service & Parts Manual  
TABLE OF CONTENTS (cont.)  
PAGE #  
2.  
PARTS LIST  
2–1  
2.1  
2.2  
2.3  
2.4  
2.5  
2.6  
2.7  
2.8  
2.9  
2.10  
2.11  
2.12  
Blower Assembly, Combustion Air  
Burner Manifold and Related Components  
Flue Caps, Top Caps, and Related Components  
Cabinetry  
Door Assemblies and Component Parts  
Control Panels, Wireways, and Related Components  
Oil Return and Suction Manifold  
Filter Unit  
Frypot, Drain, and Oil Return Components  
Drain Valve and Components  
Wiring Connectors, Pin Terminals, and Power Cords  
Screws, Nuts, Fasteners  
2–1  
2–2  
2–4  
2–6  
2–8  
2–9  
2–11  
2–13  
2–14  
2–16  
2–17  
2–18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
1.1 Functional Description  
YSCFC Series Flatbottom gas fryers contain a welded steel frypot (mild steel) with heat-transfer  
ducting on the frypot bottom for efficient heating of oil without scorching. A draft inducer draws air  
over the burners for combustion. Air movement directs the combustion products back and forth  
across the frypot bottom by means of a set of baffles, transferring the heat evenly. Cold air is  
prevented from entering the combustion chamber and cooling the oil during the coasting cycle.  
Flames originate from orifices in three tubular burners positioned beneath the frypot. The diameter  
of the orifices differs for Natural (CE:G20/G25) and LP (CE:G31) gas as indicated in the table  
below.  
NON-CE (Altitudes of 2000 feet or less)  
EQUIPMENT  
PRESSURE  
INPUT  
(BTU)  
ORIFICE  
[DRILL SIZE (MM)]  
ORIFICE  
PART #  
MODEL  
GAS TYPE  
QTY  
MBAR  
INCH W.C.  
NAT  
LP  
#34 (2.82)  
#50 (1.78)  
810-2051  
810-2317  
3
3
10  
27.5  
4
11  
1824/24YSCFC  
120  
An electromechanical gas valve regulates gas flow to the manifold. YSCFC Series Flatbottom gas  
fryers are equipped with a 24-volt valve system and an electronic ignition system (direct spark  
ignition).  
Electronic Ignition Configuration  
In units configured for electronic ignition, an ignition module connects to an ignitor assembly. The  
ignition module performs three important functions: it provides an ignition spark, supplies voltage to  
the gas valve, and proofs the burner flame.  
The module contains a time delay circuit and a coil that activates the gas valve. The ignitor  
assembly consists of a spark plug and a flame sensor element.  
At start-up the ON/OFF switch is placed in the "ON" position, supplying 115 VAC or 230 VAC,  
according to system configuration, to the Thermatron interface board. The voltage is stepped down  
via transformer to 24 VAC before entering the ignition module. If resistance in the temperature  
probe indicates the temperature in the frypot is below 150°F (66°C), the current flows through a melt  
cycle circuit where a switch alternately closes for approximately 4 seconds and opens for  
approximately 20 seconds. If the temperature is 150°F (66°C) or above, the current flows through a  
heat circuit, bypassing the timer switch. In either case, current is supplied to the other leg of the heat  
relay coil, which then closes an electronic switch in the 24 VAC circuit to provide current to the  
ignition module.  
Circuitry in the ignition module sends 24 VAC current to the gas valve via a normally closed high-  
limit switch and a drain safety switch. Simultaneously, the module causes the ignitor to spark for up  
1-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
to 11 seconds to light the burner flame. A flame sensor verifies that the burner is lit by measuring  
the flow of microamps through the flame. If the burner does not light (or is extinguished), current to  
the ignition module is interrupted, preventing the main valve from opening, and the ignition module  
"locks out" until the power switch is turned "OFF", then back "ON".  
A temperature probe monitors the temperature in the frypot. When the programmed setpoint  
temperature is reached, resistance in the probe causes the heat cycle circuitry in the controller to  
interrupt current flow through the heat relay. This in turn interrupts the 24 VAC to the ignition  
module, resulting in closure of the gas valve.  
Control Options  
YSCFC Series Flatbottom gas fryers are equipped with Thermatron temperature controller. The  
fryer is turned on and off by means of a rocker switch and the temperature is set by adjusting a  
potentiometer. The Thermatron board is located in the wireway box behind the control panel, or in a  
component box inside the cabinet (depending on fryer configuration).  
The Thermatron temperature controller operates by comparing resistance between the potentiometer  
setting and the temperature probe. If the resistance values don’t match, an on-board relay energizes,  
sending voltage to the gas valve that supplies fuel to the burners. When the resistance values are  
equal, the on-board relay de-energizes, interrupting voltage to the gas valve, which stops the fuel  
flow.  
Depending on the system configuration and destination, 115VAC controller boards are used.  
Line voltage enters the interface  
3 AMP FUSE  
F1  
board at J1. The temperature controls  
(potentiometer) are connected to  
terminals 7, 8 and 9. The sensor  
probe circuit is connected to  
terminals 10 and 11. The high-limit  
and gas valve route through terminal  
12. Terminals 5 and 6 are the melt-  
cycle disable circuit. The melt cycle  
is enabled unless terminals 5 and 6  
are jumped out.  
COM  
NC  
13  
14  
12  
BOIL  
REMOVABLE  
RELAY  
K1  
CCW  
9
8
7
NO  
CT  
EXT POT  
CW  
J1  
11  
10  
PROBE  
COM  
115  
230  
P12  
P13  
5
6
12/24 VAC INPUT  
MELT CYCLE DISABLE  
Thermatron Controller Board  
1-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
Safety Components  
All YSCFC Series Flatbottom gas fryers are equipped with a high-limit thermostat. In the event that  
the fryer fails to properly control the oil temperature, the high-limit thermostat prevents the fryer  
from overheating to flash point. The high-limit thermostat acts as a normally closed power switch  
that opens when exposed to temperatures above 410°F [(210°C) - CE] to 450°F [(232°C) - Non-CE].  
CE and non-CE high-limits are not interchangeable.  
Frying systems with built-in filtration are equipped with drain microswitches that disable the fryer if  
the drain valves are not completely closed. Opening a drain valve (i.e. filtering or draining the fryer)  
automatically opens the reset switch circuit. The drain valve must be fully closed prior to resetting  
the safety switch.  
1.2 Accessing Fryers for Servicing  
DANGER  
Moving a fryer filled with cooking oil/shortening may cause spilling or splattering of  
the hot liquid. Follow the draining instructions included with the fryer before  
attempting to relocate a fryer for servicing.  
NOTE: Perform the following only if the fryer cannot be serviced in its installed location. Some of  
the following service procedures require the fryer to be connected to the gas and/or electrical supply.  
1. Shut off the gas supply to the unit. Unplug the power cords. Remove any attached restraining  
devices.  
2. Disconnect the unit from the gas supply.  
3. Relocate the fryer for service accessibility.  
4. After servicing is complete, reconnect the unit to the gas supply, reattach restraining devices, and  
plug in the electrical cords.  
1-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
1.3 Cleaning the Gas Valve Vent Tube (if applicable)  
1. Set the fryer power switch and the gas valve to the "OFF" position.  
2. Carefully unscrew the vent tube from the gas valve. NOTE: The vent tube may be straightened  
for ease in removal.  
3. Pass a piece of wire through the tube to remove any obstruction. Remove the wire and blow  
through the tube to ensure it is clear.  
4. Reinstall tube and bend so that the opening is pointing downward.  
1.4 Adjusting Burner Manifold Gas Pressure  
WARNING  
This task should be performed by qualified service personnel only.  
1. Ensure that the gas valve knob is in the  
"OFF" position.  
2. Remove the pressure tap plug from the  
burner manifold.  
3. Insert the fitting for a gas pressure-  
measuring device into the pressure tap  
hole.  
Remove pressure tap from burner manifold to  
check burner manifold pressure.  
4. Place the gas valve in the "ON" position then place the fryer power switch in the "ON" position.  
When the burner lights and continues to burn, note gas pressure reading for correct pressure in  
accordance with the table on page 1-1.  
1-4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
5. To adjust burner gas pressure, remove the cap from the gas valve  
regulator and adjust to correct pressure (arrow shown at right).  
6. Place the fryer power switch and the gas valve in the "OFF"  
position. Remove the pressure-measuring device fitting from  
the pressure tap hole and reinstall the pressure tap plug.  
1.5 Calibrating the Thermatron Temperature  
Controller  
1. Ensure the fryer ON/OFF switch is in the "OFF" position. Fill the  
Non-CE Electronic Ignition  
Valve  
frypot to the proper oil-level line with cooking oil/shortening. If  
solid shortening is used, ensure that the shortening is properly  
packed and melted in the frypot before proceeding.  
2. Place the fryer ON/OFF switch in the "ON" position. Set the Thermatron dial to 325°F (162°C).  
3. Allow the oil/shortening to stabilize at setpoint temperature. This is evident when the burners  
have cycled on and off several times.  
4. Insert a thermometer or pyrometer into the frypot within ½ inch (1.25 cm) of the probe tip.  
Ensure the tip of the thermometer/pyrometer does not touch the bottom or sides of the frypot.  
5. If the temperature on the thermometer is  
higher or lower than 325°F (162°C), the  
dial is out of calibration.  
6. Calibrate the dial by first loosening two  
setscrews in the dial (arrows). After loosening  
both setscrews, slowly turn the dial to match  
the temperature reading of the thermometer.  
Tighten each setscrew, ensuring the dial does  
not move on the shaft during tightening.  
7. Allow burners to cycle on and off several  
times, then recheck oil temperature as  
described in step #5. If the Thermatron  
dial temperature matches the thermometer  
temperature, the controller is calibrated.  
If not, repeat step #7.  
8. After calibration is complete, place the fryer  
Loosen two setscrews in dial (arrows) to recalibrate  
power switch in the "OFF" position and  
disconnect the fryer from the electrical supply.  
controller.  
1-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
1.6 Replacing Fryer Components  
1.6.1 Remove/Replace Temperature Probe or High-Limit Thermostat  
1. Disconnect the fryer from the electrical supply.  
2. Allow the frypot to cool for 10 minutes before draining. Drain cooking oil/shortening from the  
frypot. Allow the frypot to cool completely before proceeding.  
3. Remove the fryer door(s) for access to control panel screws. Lift door up, disengage rod from  
lower door bracket, and then remove door. (Current production models have spring-loaded door  
pins. Disengage bottom pin from the hinge, and then remove door.)  
4. Remove the marine edge (where applicable) from the topcap.  
5. Support the control panel and remove  
screws securing the panel to the wireway  
box. Remove the control panel.  
6. On units with indicator lights on the control  
panel, mark and unplug the wiring, and then  
remove the control panel.  
7. Remove screw securing probe/high-limit  
access cover to wireway box. Remove  
access cover and set aside.  
NOTE: Some systems have a wiring terminal  
block mounted on the access cover. Mark  
and disconnect the wiring to the terminal  
block before removing access cover.  
1-6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
8. Remove the sensor bulb guard to access the  
probe and high-limit (pictured above).  
Current production systems have a sensor  
bulb clamp that must be removed prior to  
removing the probe or high-limit from the  
frypot (pictured top right).  
9. On the sensor bulb being removed, loosen  
and unscrew completely the compression  
nut, then the pass-through nut from the  
frypot. Carefully remove the sensor bulb  
from the frypot, being careful not to damage  
the remaining sensor bulb.  
Temperature probe.  
High-limit.  
10. If removing the high-limit, remove the  
screws securing it to the wireway box.  
Mark and remove the wiring from the high-  
limit housing.  
High-limit.  
1-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
11. Reverse steps to install new temperature probe or high-limit. If reinstalling high-limit, ensure the  
capillary tube is properly routed around the temperature probe before tightening (see photo, Step  
#8). Reconnect wiring removed from defective high-limit.  
IMPORTANT (High-Limit): When installing new high-limit, ensure the capillary tube and  
bulb are positioned properly with the mounting hardware installed prior to tightening the  
compression nut. Once tightened, the capillary tube cannot be repositioned.  
IMPORTANT (Temperature Probe):  
When installing new temperature probe,  
ensure probe is positioned properly with the  
mounting hardware installed (current  
production systems), or 1/8" from frypot  
bottom (older systems), prior to tightening  
the compression nut. Once tightened, the  
probe cannot be repositioned.  
In older fryers, ensure probe tip is 1/8" from  
frypot bottom for proper temperature sensing.  
Frypot Bottom  
1.6.2 Removing/Replacing Rocker Switches  
1. Disconnect the fryer from the electrical supply.  
2. The switches are located on a control box inside the unit. Remove the screws securing the front  
panel of the control box. Do not allow the panel to hang by the switch wiring harness wiring;  
use some type of support.  
3. Depress the retaining clips (see illustration below) and push the switch out of the slot. If there is  
a switch-guard present, retain it for installation of the replacement switch.  
When connecting wires to replacement  
switch, pass the wires through the  
switch guard (if applicable) before  
connecting to switch.  
Depress clips on each  
end to remove switch  
from control panel.  
4. Remove wires one at a time from the switch being removed and connect to the replacement  
switch until all wires are transferred.  
1-8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
5. Reverse the above steps for reassembly.  
1.6.3 Replacing the Gas Valve  
DANGER  
Drain the frypot or remove drain valve handle to prevent accidental opening before  
proceeding further.  
1. Disconnect fryer from electrical and gas supplies.  
2. Disconnect the wires from the gas valve terminal block, marking each wire to facilitate  
reconnections.  
3. Remove the high-limit thermostat wire from the gas valve coil (CE only).  
4. Remove gas lines and pipe union collars from the gas valve and remove the valve.  
5. Remove the pipefitting from the old gas valve and install on the replacement valve, using  
Loctite PST567 or equivalent pipe thread sealant on threads. Do not apply sealant to the  
first two pipe threads. Doing so will clog and damage the gas valve.  
6. Reverse steps 1-5 to install the replacement gas valve.  
1.6.4 Replacing Direct-Spark Ignitor Assembly (Units with Electronic Ignition Only)  
1. Remove the burner shield from the  
burner-box slots.  
2. Disconnect sense wire and ignition  
cable from the ignitor.  
3. Remove the mounting screw from the  
ignitor mounting-bracket and remove  
the ignitor.  
4. Reverse the procedure to replace the  
ignitor assembly. Ensure the ignitor  
is properly positioned in relation to  
the center burner before tightening  
mounting screw.  
Ensure ignitor is properly positioned (arrow) over  
NOTE: The above procedure is  
the center burner prior to tightening the mounting  
screw.  
applicable to fryers equipped  
with electronic ignition systems  
only.  
1-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
1.6.5 Removing/Replacing Blower Assembly or Air Prover Switch  
1. Remove back panel. On systems with built-  
in filtration, use care not to damage the oil-  
return heat-tape wiring insulation when  
removing backs (multi-batteried systems after  
02/03 have two-piece back panels; remove  
both to access blower assembly).  
2. Remove blower assembly by removing four  
screws (two screws securing the flue outlet to  
the firebox, and two screws securing the  
blower inlet housing to the firebox). Pull the  
assembly out of the slot and lower to the side.  
Do not remove the electrical connections at  
this time.  
3. Remove junction box cover and mark and  
disconnect wiring to the switch. Unscrew  
Multi-batteried systems after have upper and lower  
fitting connecting sampling tube to air prover  
switch, being careful not to kink the tube.  
Remove two screws from bracket that  
attaches switch to junction box to remove  
switch. Install new air prover switch with  
bracket. Reattach sampling tube and wires  
removed from old switch and replace  
junction box cover.  
back panels, which must be removed to access the  
blower assembly. (fryer at left shown with upper  
back panel removed).  
4. If replacing blower, remove junction box  
cover, mark and disconnect each wire, and  
remove conduit fitting from junction box.  
Reinstall conduit fitting on new blower  
and reconnect wiring. Replace box cover.  
5. Reverse steps 1 – 2 to reinstall blower  
assembly.  
After removing screws (arrows), remove blower  
assembly from firebox by pulling outward.  
1-10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
1.6.6 Replacing the Frypot  
Unit should be at room temperature, disconnected from gas and electrical service, and empty of oil  
or shortening prior to beginning procedure.  
1.6.6.1 Frypot Baffle Inspection  
1. Remove cabinet door(s) by holding door and lifting up on hinge pin. Current production model  
doors have spring-loaded pins that must be disengaged from the control panel and the bottom  
hinge. Remove marine edge (if applicable) by lifting up and off topcap and set aside.  
2. The burner-tube retainer strip and burner tubes must be removed from the frypot/firebox being  
inspected. Remove the burner-tube shield and the burner-tube retainer from the burner-box and  
set aside. Lift the burner tubes up over each orifice and then pull outward to remove.  
3. Disconnect the sense wire and ignition  
cable and remove the direct-spark ignitor  
assembly (with electronic ignition).  
Inspect frypot baffles for signs of burn-  
through or damage. If baffle burn-through  
or damage is visible, proceed to the next  
section. If not, and no further service to  
frypot/firebox is required, reverse the  
above steps to reassemble the fryer.  
Inspect frypot baffles through burner tube opening  
(arrow) for signs of burn-through or damage.  
1-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
1.6.6.2 Frypot/Firebox Removal/Replacement Procedure  
1. Perform Procedure 1.6.5, Removing/Replacing Blower Assembly or Air Prover Switch, Steps 1 –  
4.  
2. Disconnect the union at the gas valve.  
Remove four bolts connecting the burner  
manifold brackets to the burner box.  
Remove the burner manifold assembly  
and set aside.  
3. Mark and disconnect the drain-valve  
Disconnect  
union at gas  
valve and  
remove four  
bolts (two per  
side) to  
microswitch wiring. Remove elbow or  
drain-tee assembly, and then remove the  
drain valve/microswitch assembly.  
remove burner  
manifold.  
Remove drain  
elbow and  
drain valve  
assembly from  
the frypot.  
Disconnect union at gas valve and remove four  
bolts connecting burner manifold brackets to firebox  
and drain valve assembly from frypot.  
4. Remove two screws from control panel and lower, using care not to stretch or distort indicator  
light wiring (if applicable). If control panel is equipped with indicator lights, mark and  
disconnect wiring and set control panel aside.  
If equipped with indicator lights, use a pin-pusher to remove pins from main-harness  
connector, and then remove control panel.  
5. Perform Procedure 1.6.1, Remove/Replace Temperature Probe or High-Limit Thermostat, Steps  
7 – 11.  
1-12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
6. Remove two screws securing topcap to  
wireway box. Remove topcap. Remove  
four screws securing wireway box to fryer  
cabinet (arrows) and carefully lower  
wireway box out of the way. Use care not  
to stretch or distort the wiring.  
7. Remove two screws from the firebox heat  
shield (arrows), remove heat shield and  
set aside.  
NOTE: Steps 8 and 9 must be performed  
prior to frypot removal, especially on  
systems with built-in filtration. Failure  
to perform these steps will make frypot  
removal extremely difficult, and cause  
possible damage to firebox components  
during removal.  
Remove topcap, wireway box and front heat  
shield to access firebox and frypot.  
8. Remove the burner box baffle by pushing  
the baffle up into the burner box until the  
baffle studs are clear of the slots. Tilt the  
baffle at an angle and remove it from the  
burner box.  
9. Remove screws (two) securing the flame  
spreader to the burner box. Allow the  
spreader to drop down to clear the frypot  
baffles.  
After removing burner-box baffle, remove screws  
(two) securing the flame spreader to the burner  
box. Allow the flame spreader to drop down in the  
burner box to clear the frypot baffles. Repeat for  
both sides.  
1-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
10. Remove firebox back, along with  
insulation from back of frypot. From the  
rear of the unit, use a prying bar to  
carefully pry the top assembly from the  
frypot and cabinet frame (single units  
only), and set aside. (The top assembly is  
secured to the frypot with high-temp  
silicone sealant.) On systems, remove  
individual pieces on the frypot being  
removed.  
Use a pry bar to  
remove top  
assembly from  
frypot (single  
units only).  
11. Pull the frypot back and up to remove. On  
fryers with built-in filtration systems,  
ensure the front oil-return inlet is clear of  
the firebox front before lifting frypot out  
of cabinet.  
Remove the  
firebox back and  
insulation from  
back of frypot.  
If the Firebox Requires Replacement:  
12. Remove screws (12) securing the firebox  
to the cabinet braces (arrows). Lift the  
firebox assembly back and up to remove  
from cabinet.  
Remove screws (arrows) securing the firebox to  
the cabinet.  
1-14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
13. Install new firebox into cabinet. Replace  
screws (12) removed during removal of  
the old firebox. Use spray adhesive (Zep  
Aero Tac High-Strength Spray Adhesive  
or equivalent) to install new insulation in  
firebox bottom as shown. The insulation  
must not go above the top of the burner-  
box center flange.  
NOTE: Ensure the strip of insulation is  
properly affixed to the front blower-  
housing flange (arrow) prior to installing  
frypot. Failure to install the insulation  
strip will result in frypot-baffle burnout,  
blower damage and fryer malfunction,  
and will void all applicable warranties.  
Install new insulation in firebox using spray  
adhesive, ensuring good contact between  
insulation and metal surfaces.  
14. Install new frypot, using care not to  
damage the firebox insulation. Ensure  
the blower-housing insulation strip  
remains in place after installing the new  
frypot (arrow).  
Reverse the above steps to reassemble the  
fryer. Use high-temp silicone to re-install  
the top assembly (single fryers) or joiner  
strips, flue caps, etc. (systems).  
Ensure blower-housing insulation strip remains in  
place after installing the new frypot (arrow).  
1.7 Troubleshooting and Problem Isolation  
This section is intended to provide technicians with a general knowledge of the broad problem  
categories associated with this equipment, and the probable causes of each. With this knowledge,  
the technician should be able to isolate and correct any problem encountered.  
Problems you are likely to encounter with YSCFC Series Flatbottom fryers can be grouped into five  
categories:  
1. Ignition failures  
4. Filtration problems  
5. Leakage  
2. Improper burner functioning  
3. Improper temperature control  
1-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
The probable causes of each category are discussed in the following sections. Troubleshooting  
guides are included in Section 1.8 to assist in identifying some of the more common problems.  
1.7.1 Ignition Failures  
Ignition failure occurs when the ignition module fails to sense a flame within the 11-second time  
delay period and locks out. Turn the fryer off, locate and correct the problem, then turn fryer back  
on to clear the module lock.  
There are three primary reasons for ignition failure, listed in order of probability:  
1. Problems related to the gas and/or electrical power supplies.  
2. Problems related to the electronic circuits.  
3. Problems related to the gas valve.  
Problems Related to the Gas and/or Electrical Power Supplies  
The main indicator is that an entire battery of fryers fails to light. Verify that the quick disconnect  
hose is properly connected, the fryer is connected to power, the main gas supply valve is open, and  
the circuit breaker for the fryer electrical supply is not tripped. Some fryers are equipped with a  
fryer reset-switch that must be reset each time the fryer is turned off.  
Problems Related to the Electronic Circuits  
If gas and electrical power are supplied to the fryer, the next most likely cause of ignition failure is a  
problem in the 24 VAC circuit of electronic ignition systems. If the fryer is equipped with a  
filtration system, first verify that the drain valve is fully closed. (The valve is equipped with a  
microswitch that must be closed for power to reach the gas valve. Often, although the valve handle  
appears to be in the closed position, the microswitch is still open.) If the valve is fully closed, or the  
fryer does not have a filtration system, refer to the troubleshooting guides in this chapter.  
Problems Related to the Gas Valve  
If the problem is not in the 24 VAC circuit, it is most likely in the gas valve itself, but before  
replacing the gas valve, refer to the troubleshooting guides in this chapter.  
1-16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
1.7.2 Improper Burner Functioning  
With problems in this category, the burner ignites but exhibits abnormal characteristics such as  
"popping", incomplete lighting of burner, fluctuating flame intensity, and flames "rolling" out of the  
fryer.  
"Popping" indicates delayed ignition. In this condition, the main gas valve is opening but the burner  
is not immediately lighting. When ignition does take place, the excess gas "explodes" into flame,  
rather than smoothly igniting.  
The primary causes of popping are:  
Incorrect or fluctuating gas pressure  
Clogged burner orifices  
Clogged burners  
Inadequate make-up air  
Heat damage to the controller or ignition module  
An out-of-adjustment ignitor or broken ignition wire  
A defective ignition module  
If popping occurs only during peak operating hours, the problem may be incorrect or fluctuating gas  
pressure. Verify that the incoming gas pressure (pressure to the gas valve) is in accordance with the  
appropriate CE or Non-CE requirements listed in the Installation and Operation manual that came  
with the fryer, and that the pressure remains constant throughout all hours of usage. Refer to  
Adjusting Burner Manifold Pressure in Section 1.4 if burner manifold pressure is suspected of  
being incorrect.  
On systems equipped with electronic ignition, verify that the ignitor is properly adjusted (electrode  
tip and ignitor positioned properly over middle burner).  
Clogged burners and burner orifices are also likely causes of delayed ignition. Clogged burners are  
indicated by uneven flame or partial flame on the burner face. Clogged orifices are indicated by no  
flame.  
Another cause of popping is an insufficient air supply or drafts. Check for "negative pressure"  
conditions in the kitchen area. If air is flowing into the kitchen area, more air is being exhausted  
than is being replenished and the burners may be starved for air.  
If the fryer’s gas and air supplies are okay, the problem most likely is with one of the electrical  
components. Examine the ignition module for signs of melting/distortion and/or discoloration due to  
excessive heat build-up in the fryer. (This condition usually indicates improper flue performance.).  
1-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
Also, examine the controller for the same conditions. A melted or distorted ignition module is  
automatically suspect and should be replaced, but unless the condition causing excessive heat in the  
fryer is corrected, the problem is likely to recur.  
Next, ensure the ignition wire is connected properly at both ends and examine it for obvious signs of  
damage. Again, if damage is due to excessive heat in the fryer, that problem must also be corrected.  
DANGER  
MAKE SURE YOU ARE HOLDING THE INSULATED HANDLE OF THE SCREWDRIVER  
AND NOT THE BLADE. THE SPARKING CHARGE IS APPROXIMATELY 25,000  
VOLTS.  
Check for proper operation by disconnecting the wire from the ignitor, inserting the tip of a  
screwdriver into the terminal, and holding it near the frame of the fryer as the power switch is placed  
in the "ON" position. A strong, blue spark should be generated for at least 11 seconds.  
Fluctuating flame intensity is normally caused by either improper or fluctuating incoming gas  
pressure, but may also be the result of variations in the kitchen atmosphere. Verify incoming gas  
pressure in the same way as for "popping", discussed in the preceding paragraphs. Variations in the  
kitchen atmosphere are usually caused by air conditioning and/or ventilation systems starting and  
stopping during the day. As air conditioning/ventilation systems start and stop, the pressure in the  
kitchen may change from positive or neutral to negative, or vice versa. Changes in airflow patterns  
may affect flame intensity.  
Flames "rolling" out of the fryer are usually an indication of negative pressure in the kitchen. Air is  
being sucked out of the fryer enclosure and the flames are literally following the air. If negative  
pressure is not the cause, check for high burner-manifold gas pressure in accordance with the  
procedures in Section 1.4. An obstructed flue or a faulty blower, which prevents the fryer from  
properly exhausting, may also be the cause.  
Excessively noisy burners, especially with flames visible above the flue opening, may indicate that  
the burner gas pressure is too high or the gas valve vent-tube is blocked (if applicable). If the gas  
pressure is correct, and the vent-tube is unobstructed (if applicable), the gas valve regulator is  
probably defective.  
1-18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
1.7.3 Improper Temperature Control  
Temperature control, including the melt cycle, is a function of several interrelated components, each  
of which must operate correctly. The principal component is the temperature probe. Depending  
upon the specific configuration of the fryer, other components may include the Thermatron board,  
the controller itself, and the ignition module.  
Improper temperature control problems can be categorized into melt cycle problems and failure to  
control at setpoint.  
Failure to Control at Setpoint  
In fryers equipped with a Thermatron temperature controller, the problem may be that the  
temperature probe is improperly positioned. Other causes may be the Thermatron board or the  
potentiometer. Possible causes are that the potentiometer is out of calibration, or the temperature  
probe or Thermatron board is defective. Refer to Section 1.5 for instructions on calibrating the  
Thermatron temperature controller.  
1.7.4 Filtration Problems  
Whenever the complaint is "the pump is running, but no oil is being filtered", check the filter paper  
or filter leaf (screen) connections and ensure they are properly connected. Ensure the filter paper or  
filter leaf is not clogged with food debris or sediment and is properly assembled.  
If the pump motor overheats, a circuit breaker in the filter circuit will trip and the motor will not start  
until it is reset. If the pump motor does not start after pressing the circuit breaker, press the red reset  
switch located on the rear of the motor. If the pump then starts, something caused the motor to  
overheat. Maybe several frypots were filtered one after the other and the pump got hot. Letting the  
motor cool down for at least a half-hour is all that is required in this case. More often, the pump  
overheated for one of the following reasons:  
Shortening was solidified in the filter leaf or filter lines.  
The operator attempted to filter unheated oil or shortening. Cold oil and shortening are thicker  
and cause the pump motor to work harder and overheat.  
If the motor runs but the pump does not, there is a blockage in the pump. An incorrectly assembled  
filter leaf allows food particles and sediment to pass through the filter pan and into the pump. When  
sediment enters the pump, the gears bind up causing the motor to overheat, tripping the thermal  
overload. Particles large enough to clog the pump may indicate that the crumb tray is not being used,  
and that the filter leaf is not properly assembled. Solidified shortening in the pump will produce the  
same result.  
1-19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
A pump seized by debris or hard shortening must be disassembled, cleaned and reassembled as  
follows:  
1. Disconnect power to the filter system.  
2. Remove the front cover of the pump to access the gears inside, if the pump is accessible while  
still inside the cabinet. If the front cover is not accessible, the pump must be removed from the  
pump motor (remove input/output plumbing from the pump prior to removing pump). Remove  
setscrews to disengage the pump from the motor.  
3. Prior to reassembly, the inside housing must be clean and free of any sediment or debris. Failure  
to completely clean the inside housing and ring gear will cause gear binding after reassembly.  
4. During reassembly, partially install the housing bolts in a star pattern, leaving a -inch (3 mm)  
gap between the cover and housing flanges. Ensure there is no shortening or oil in the filter pan,  
and that the filter pan is disconnected. With the motor running slowly draw the cover in, evenly  
tightening the housing bolts. When the cover is snug on the housing tighten all bolts to 15 inch-  
lbs (1.7 Nm) ensuring that the pump is working correctly. Turn the motor off.  
The electronics of the SUFF/UFF filtration system are simple and straightforward. Microswitches  
attached to handles for each vat and wired in parallel provide the 24 VAC required to activate the  
pump relay coil. When the handles are moved to the ON position, the activated pump relay coil pulls  
the pump motor switch in, supplying power to the pump motor.  
Filter systems equipped with oil-return heaters are wired into the 120 VAC source, which remains  
energized as long as the unit is plugged in.  
1-20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
1.7.5 Leakage  
Frypot leaks are usually due to improperly sealed high-limit, temperature probe or oil-return and  
drain fittings. When installed or replaced, each of these components must be sealed with Loctite  
PST567 sealant or equivalent to prevent leakage. In very rare cases, a leak may develop along one  
of the welded corners of the frypot. When this occurs, the frypot must be repaired or replaced.  
Frypot locations (indicated by arrows) where potential leaks could occur.  
1-21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
1.8 Troubleshooting Guides  
The following procedures must be performed by an ASA. They are provided as an aid to expedite  
troubleshooting and repair of YSCFC Series frying systems.  
1.8.1 Main Burner Malfunctions  
PROBLEM  
CORRECTIVE ACTION  
1. Check that the combination gas valve is ON.  
Main burner will not  
come on even though  
air blower is in  
2. Check high temperature safety switch. Replace if defective.  
operation; no gas  
pressure at main  
burner.  
3. Check air prover switch. Ensure green prover light is on. If not,  
check for 24 VAC going into and coming out of the air prover  
switch.  
1. Cooked product or other material may have fallen into the flue  
and lodged in the blower wheel, preventing it from turning.  
Clean out flue and blower wheel.  
Air blower is not  
operating, although  
power is present at the  
fryer.  
2. Blower motor may have overheated and shut off. This  
condition will correct itself when motor cools (20 minutes). If  
problems with blower overheating persist, call for service.  
3. If fryer is equipped with a Thermatron controller, the  
temperature probe or the controller board may be defective.  
1. Check gas pressure at the pressure tap of the burner manifold.  
Use a standard water-type U-gauge manometer. With the  
burner in operation, the pressure should be about 4" W.C. on  
natural and 11" W.C. on propane (LP) gases. If not, unscrew  
the cover of the pressure regulator adjustment and turn the  
adjusting screw clockwise to increase gas pressure (or  
counterclockwise to decrease the pressure). Replace cover  
and plug.  
Main burner flames are  
small and appear lazy;  
Oil does not come up  
to temperature quickly.  
1. Check the frypot for excessive build up of debris.  
There are signs of  
excessive frypot  
temperature;  
2. Thermatron controller may be out of calibration. Re-calibrate  
in accordance with instructions in Section 1.5.  
oil becomes  
discolored quickly.  
3. Check gas pressure.  
4. Oil of inferior quality or used too long. Replace with quality oil.  
1-22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
1.8.2 Indicator Lights  
The fryer’s indicator lights serve a diagnostic purpose. All lights are lit when the fryer is working  
properly. The green light on the control panel will cycle on and off as the fryer calls for heat. Use  
the following procedures to isolate problems indicated by light combinations.  
Turn the temperature dial to 400°F (204°C) to ensure the sensor will demand heat. Check all  
indicator lights in the fryer cabinet and on the control panel. [Older units may have power and reset  
switches with different colored lights (orange, amber, red, green, white.). Common Cabinet units  
have a white power light and a green air prover light. Substitute the light color of the correct color  
switch with the respective "green light" switch in the following troubleshooting procedures. The  
control panel light colors haven’t changed.]  
When turning the power switch "ON" and resetting the safety (reset) switch, check for the following:  
LIGHT INDICATION  
PROBABLE CAUSE  
CORRECTIVE ACTION  
GREEN LIGHT/POWER SWITCH IS 1. The drain valve is open.  
"ON"  
1. Ensure the drain valve is  
completely closed, and then  
turn the reset switch to "ON".  
GREEN LIGHT/SAFETY (RESET)  
SWITCH IS "OFF"  
2. The drain switch is defective.  
GREEN LIGHT/CONTROL PANEL IS  
"OFF"  
RED LIGHT/CONTROL PANEL IS  
"OFF"  
GREEN LIGHT/POWER SWITCH IS 1. No power to fryer.  
"OFF"  
1. Check power source, power  
cords and breaker. Ensure that  
electricity is available to the  
fryer.  
GREEN LIGHT/SAFETY (RESET)  
SWITCH IS "OFF"  
2. Fuse is blown.  
2. Replace fuse.  
GREEN LIGHT/ CONTROL PANEL IS  
"OFF"  
3. If fryer does not function after  
resetting the reset switch,  
RED LIGHT/CONTROL PANEL IS  
"OFF"  
3. Reset switch circuit defective.  
contact an ASA for assistance.  
1-23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
1.9 WIRING DIAGRAMS  
NOTE: The diagrams in this section depict wiring as of the date of manual publication. It  
may not reflect design changes made to the equipment after publication. Always refer to  
the wiring diagram affixed to the unit when actually troubleshooting this equipment.  
1.9.1 Wiring for Common Cabinet Flatbottom without Boil Out  
1-24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
1.9.2 24/24 Filter Wiring  
1-25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 1: SERVICE PROCEDURES  
1.9.3 18/24 Common Cabinet Transformer Box  
1-26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 2: PARTS LIST  
2.1 Blower Assembly and Combustion Air  
4
5
1
2
3
ITEM  
PART #  
COMPONENT  
1
2
3
4
5
108-0471SP Motor, Blower Assembly, 120V  
823-3162  
200-1428  
823-3166  
200-1471  
Duct Assembly, Inlet  
Gate, Air Flow  
Duct Assembly, Outlet  
Door, Outlet Duct Access  
* Not illustrated.  
2-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 2: PARTS LIST  
2.2 Burner Manifold and Related Components  
2-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 2: PARTS LIST  
2.2 Burner Manifold and Related Components (cont.)  
ITEM  
PART #  
810-2129  
200-1670  
810-2168  
COMPONENT  
1
2
3
4
Tube, Burner  
Support, Left or Right Manifold  
Burner Manifold Assembly  
Orifice  
810-2827  
810-2830  
813-0154  
813-0174  
813-0300  
813-0066  
813-0112  
813-0168  
2.82mm (#34) Natural Gas  
1.78mm (#50) Propane (LP) Gas  
Plug, " NPT (Manifold Pressure Tap Plug)  
Union, ¾" NPT Pipe  
Nipple, ¾" NPT x 4½"  
Elbow, 90° x ¾" NPT  
Nipple, ¾" NPT x 2"  
Elbow, 90° x ¾" NPT Street  
Valve, Gas  
5
6
7
8
9
10  
11  
807-3555  
807-3690  
106-6553  
813-0763  
813-0022  
813-0173  
813-0165  
813-0265  
813-0062  
813-0845  
813-0608  
813-0475  
813-0460  
813-0421  
813-0418  
813-0275  
813-0266  
813-0247  
813-0087  
813-0031  
810-2898  
24V Natural (G20/G25) Honeywell  
24V Propane (LP) (G31) Honeywell  
Vent Tube  
Bushing, ¾" NPT to ½" NPT  
Nipple, ½" NPT x Close  
Union, ½" NPT Pipe  
Elbow, 90° x ½" NPT Street (for single fryers, use 45° 813-0342)  
Nipple, ½" NPT x 2½"  
Elbow, 90° x ½" NPT  
Nipple, ½" NPT x 29¾" (single fryers, use 24½" 813-0788, 813-0729 23”)  
Coupling, ½" NPT  
Tee, 1" x ½" x ¾"  
Nipple, ½" x 3" NPT  
Nipple, 1" x 18" NPT  
Nipple, ½" x 17" NPT  
Nipple, ½" x 9" NPT  
Elbow, Street, 1" NPT  
Nipple, ½" x 3.5" NPT  
Nipple, ½" x 1.5" NPT  
Bushing, Hex, ¾" NPT x ½"  
Clamp, Pipe, 1"  
*
12  
13  
14  
15  
16  
17  
18  
*
*
*
*
*
*
*
*
*
*
*
Electronic Ignition Components  
Ignitor and Flame Sensor Assembly (does not include flame sensor wire or cable)  
Ignitor Bracket, Flat Style  
19  
*
20  
21  
*
807-3556  
106-4580  
106-3338  
807-3365  
W106C6SP  
Ignition Cable (includes 807-3742 cable and 807-3484 Rajah connector)  
Module, Ignition Spark, Honeywell  
Sensor Cable  
*Not illustrated.  
2-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 2: PARTS LIST  
2.3 Flue Caps, Top Caps, and Related Components  
2-4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 2: PARTS LIST  
2.3 Flue Caps, Top Caps, and Related Components (cont.)  
ITEM  
PART #  
106-3253SP  
106-1638SP  
823-4125  
823-4127  
106-2840SP  
COMPONENT  
1
2
3
4
5
6
Frame, Single Crumb Dump  
Frame, Double Crumb Dump  
Insert, Pan Crumb Dump, ½ Size  
Tray, 12424 Single  
Cover, 1824G Frypot (use 106-2839SP for 2424G Frypot)  
Deflector, Flue Cap Oil  
230-1387  
230-1390  
230-1385  
230-2996  
For use on 2-2424G (2-vat 2424 System)  
For use on 3-2424G (3-vat 2424 System)  
For use on 2-1824G (2-vat 1824 System)  
For use on 2-2424/15R (3-vat 24/15 System)  
Flue Cap  
7
230-0778  
230-1589  
230-2966  
230-0396  
210-4317  
210-4313  
210-4598  
230-3089  
For use on 2-2424G (2-vat 2424 System)  
For use on 2-1824G (2-vat 1824 System)  
For use on 2-2424/15R (3-vat 24/15 System)  
For use on 3-2424G (3-vat 2424 System)  
Edge Strip, Frypot  
Joiner Strip (joins frypots within a system)  
Joiner Strip (joins one fryer system to another)  
Joiner Strip (joins matching cabinet to fryer)  
Marine Edge  
8
9
10  
*
11  
823-5640  
823-5816  
823-5817  
823-5829  
823-5514  
823-5872  
2-vat 2424, Without Notches  
2-vat 2424, Notched Right End  
2-vat 2424, Notched Left End  
2-vat 1824, Notched Left End  
3-vat 2424, Without Notches  
3-vat 2424, Notched Right End  
Frame, Control Panel  
12  
*
106-5875  
106-8395  
106-6504  
106-7947  
803-0293  
224  
324  
1824  
24/24/MC15  
Gloves, Neoprene Hot Oil  
* Not illustrated.  
2-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 2: PARTS LIST  
2.4 Cabinetry  
2-6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 2: PARTS LIST  
2.4 Cabinetry (cont.)  
ITEM  
PART #  
220-0366  
220-0862  
220-2938  
220-0365  
220-0863  
220-2939  
231-0395  
232-0395  
221-0853  
222-0853  
200-1471  
220-0762  
220-0761  
220-0369  
220-0404  
810-0357  
810-0356  
220-3537  
220-3790  
221-0980  
222-0980  
221-4734  
222-4734  
220-4149  
220-4891  
220-0760  
200-9231  
220-3793  
220-3501  
200-9240  
220-2970  
200-9229  
200-3793  
200-9239  
220-2943  
COMPONENT  
1
Back, Upper Cabinet, 2424  
Back, Upper Cabinet, 1824  
Back, Upper Cabinet, MC15  
Back, Lower Cabinet, 2424  
Back, Lower Cabinet, 1824  
Back, Lower Cabinet, MC15  
2
3
*
*
4
5
6
7
8
9
Panel, Left Side, Stainless Steel Cabinet  
Panel, Right Side, Stainless Steel Cabinet  
Panel, Left Side, Stainless Steel Cabinet with Cut-out  
Panel, Right Side, Stainless Steel Cabinet with Cut-out  
Door, Access Duct  
Brace, Firebox  
Brace, Frypot  
Post, Front Cabinet  
Post, Rear Cabinet  
10  
*
Caster, 5" with Brake Swivel (4-hole pattern)  
Caster, 5" without Brake Swivel (4-hole patter)  
Bridge, Filter Pump  
11  
12  
13  
14  
15  
16  
17  
*
Support, Filter Pump Motor  
Guide, Filter Pan, Left  
Guide, Filter Pan, Right  
Rail, Filter Pan, Left  
Rail, Filter Pan, Right  
Stop, Drain Pan, 2424  
Stop, Drain Pan, MC15  
Divider, Frypot  
18  
19  
Brace, Cabinet Front, 224  
Brace, Cabinet Front, 324  
Brace, Cabinet Front, 324, Filter on Right (facing the fryer)  
Brace, Cabinet Front, 1824  
Brace, Cabinet Front, 24/24/15  
Brace, Cabinet Top, 224  
Brace, Cabinet Top, 324  
Brace, Cabinet Top, 1824  
Brace, Cabinet Top, 24/24/15  
Oil Return Manifold  
20  
21  
810-3088  
810-3313  
810-3314  
810-3093  
810-3239  
224  
324, Filter on Left (facing the fryer)  
324, Filter on Right (facing the fryer)  
18/24  
24/24/15  
*
Cabinet Base  
106-5788  
106-8393  
106-8394  
106-6502  
106-7948  
224  
324, Filter on Left (facing the fryer)  
324, Filter on Right (facing the fryer)  
18/24  
24/24/15  
* Not illustrated.  
2-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 2: PARTS LIST  
2.5 Door Assemblies and Component Parts  
5
2
4
1
3
ITEM  
PART #  
824-1912  
824-1958  
824-1954  
220-4128  
220-4742  
220-4666  
106-4067  
810-0275  
210-8077  
COMPONENT  
1
Panel, Door, 2424  
Panel, Door, 1824  
Panel, Door, MC15  
Liner, Door, 2424  
Liner, Door, 1824  
Liner, Door, MC15  
Pin Assembly  
2
3
4
5
Spring  
Handle  
2-8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 2: PARTS LIST  
2.6 Control Panels, Wireways, and Related Components  
2-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 2: PARTS LIST  
2.6 Control Panels, Wireways, and Related Components (cont.)  
ITEM  
1
PART #  
COMPONENT  
106-6060 Plate, Microswitch Adjustment  
807-4114 Relay, Latch/Filter 24VAC Coil  
200-4719 Plate, Interface Board Mounting  
200-9681 Support, High Limit Thermostat  
200-9812 Plate, Component Box Cover  
220-1283 Box, Component Harness  
220-1284 Housing, Thermostat  
2
3
4
5
6
7
8
220-3769 Bracket, Relay  
9
230-1282 Plate, Thermatron Face  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
807-0800 Transformer, 120V 50/60 Hz – 24V, 50 VA  
807-2103 Microswitch, Straight Lever  
807-2469 Bushing, Heyco, 1" ID  
807-3365 Ignition Module, Honeywell  
826-2086 Thermatron Board, 115/230V, Extended Melt Cycle  
807-3574 Switch, Dean Power  
807-3575 Switch, Hole Plug  
807-3576 Switch, Reset-Rocker  
807-3680 Thermostat, 450°F High-Limit w/Manual Reset  
810-0110 Knob, Thermatron Control  
826-2269 Potentiometer, Thermatron  
106-2607 Probe, Thermatron (20" leads)  
816-0220 Insulation, Switch  
823-5765 Component Box  
802-2050 Label, Three-Switch  
802-2052 Label, Thermatron Dial  
200-4719 Harness, Thermostat  
2-10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 2: PARTS LIST  
2.7 Oil Return and Suction Manifolds  
2-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 2: PARTS LIST  
2.7 Oil Return and Suction Manifolds (cont.)  
ITEM  
PART #  
810-3088  
106-5461  
810-2125  
810-3011  
810-3014  
813-0165  
813-0462  
813-0613  
813-0614  
813-0631  
813-0649  
813-0894  
823-5815  
COMPONENT  
1
Oil Return Manifold  
Oil Return Plumbing  
2
3
4
5
6
7
8
9
Drain Valve, " Ball Valve  
Tubing, Drain Valve, Front  
Tubing, Oil Return, Rear  
Elbow, Street, ½" x ½" NPT, 90°  
Coupling, "  
Flare Fitting, ½-37° x ½"  
Flare Fitting, ½-37° x "  
Elbow, " x 90°  
10  
11  
12  
Nipple, Black Tube, " NPT x 2.5"  
Elbow, " NPT x ½-37° Flare  
Oil Return Handle  
Pump and Motor  
13  
14  
*
810-3347  
826-1712  
826-1270  
816-0093  
813-0168  
813-0031  
810-1668  
810-1067  
813-0298  
813-0062  
813-0304  
813-0838  
810-1669  
810-1339  
813-0003  
813-0022  
810-1055  
Pump, Viking 8 GPM  
Motor, 115V 60Hz (gasket included)  
Motor, 230V 50/60Hz (gasket included)  
Gasket, Pump/Motor (included with motor)  
Elbow, ¾" x ¾" NPT, Street, 90°  
Bushing, Hex, ¾" NPT x ½"  
Adapter, Male, " OD x ½"  
Flexline, " OD x 8.5" long  
Nipple, ½" x 2.0" NPT  
Elbow, ½", 90°  
Bushing, ½" x ¼", Flush  
Nipple, ¼" NPT, Close  
Adapter, Female, " OD x ½"  
Flexline, " OD x 4.5" long  
Tee, ½" x ½" x ½"  
Nipple, ½" x Close NPT  
Flexline, " OD x 11.5" long  
*
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
*
106-3470SP Valve, Solenoid, Female Pins  
813-0265  
807-2304  
Nipple, ½" x 2.5" NPT  
Heater Strip, 72", 120V/100W, Silicone  
*
*
806-8004SP Heater Strip, 56", 120V/40W, Silicone  
*
*
807-1105  
807-1420  
220-0965  
220-0973  
809-0601  
813-0087  
106-4006  
Heater Strip, 18", 120V/25W, Silicone  
Heater Strip, 36", 120V/25W, Silicone  
Mount, Handle, Drain Flush  
Handle, Drain Flush  
Clevis Clip  
Nipple, ½" x 1.50" NPT  
Valve, Flush  
29  
30  
31  
32  
33  
* Not illustrated.  
2-12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 2: PARTS LIST  
2.8 Filter Unit  
ITEM  
PART #  
106-8465SP Filter Pan (with 2" casters)  
COMPONENT  
1
2
3
4
5
*
*
*
*
*
*
810-2800  
823-5833  
106-6131  
810-2805  
826-1392  
816-0757  
803-0342  
803-0289  
220-1145  
810-3082  
Filter Leaf  
Crumb Basket  
Lid, Filter Pan  
Caster, 2"  
O-rings (for filter pan pick up tube; qty. 5)  
O-rings (for filter leaf)  
Filter Powder (pack of 25)  
Filter Paper, 22" x 34" (if using paper option)  
Sana Grid Screen (if using paper option)  
Hold Down Ring (if using paper option)  
* Not illustrated.  
2-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 2: PARTS LIST  
2.9 Frypot, Drain, and Oil Return Components  
2-14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 2: PARTS LIST  
2.9 Frypot, Drain, and Oil Return Components (cont.)  
ITEM  
PART #  
826-1823  
826-1821  
823-3934  
823-3174  
823-3190  
210-1409  
COMPONENT  
Frypot Kit, 1824G (insulation included)  
Frypot Kit, 2424G (insulation included)  
Divider, Frypot  
1
2
3
4
5
6
Plug, Frypot Drain  
Baffle, Secondary Air  
Spreader, Side Flame  
Firebox Assembly  
823-5854  
823-5195  
826-2036  
220-3512  
812-1822  
812-1823  
812-2017  
816-0772  
809-0969  
106-5461  
810-2125  
810-3011  
810-3014  
813-0165  
813-0462  
813-0613  
813-0614  
813-0631  
813-0649  
813-0894  
106-4006  
816-0547  
807-2104  
813-1790  
813-0165  
813-0632  
810-2125  
823-5815  
810-3014  
200-4725  
210-1433  
200-4505  
812-1515  
1824 (use with 823-5195 on 1824 units)  
2424 (use with 823-5854 on 1824 units)  
Insulation, Pot FB  
Guard, Firebox, Bottom  
Tube, Drain, RH  
*
7
8
9
Tube, Drain, LH  
10  
11  
12  
13  
Tube, Drain, Center Dump  
Sleeve, Drain Tube Connector  
Clamp, 3" T-bolt  
Oil Return Plumbing (attaches to Item 21, Section 2.4, at the back of the unit)  
Drain Valve, " Ball Valve  
Tubing, Front  
Tubing, Rear  
Elbow, ½" x ½" Street , 90°  
Coupling, "  
Fitting, ½" x ½" 37° Flare  
Fitting, ½" x " 37° Flare  
Elbow, " x 90°  
Nipple, " NPT x 2.50 inch  
Elbow, ½" x " 37° Flare  
14  
*
*
*
*
*
*
*
*
*
*
*
*
Drain Valve with Microswitch, ½"  
Sleeve, Red Valve Handle  
Microswitch, Drain Valve Roller Lever (use 902-2348 for M/S Guard)  
Nipple, 1¼" x 5.85 inch NPT Toe  
Elbow, ½" x 90° NPT Street  
Elbow, " x 90° NPT Street  
Valve, ", Oil Return, Ball (use 200-1143 for Nut Retainer)  
Handle, Oil Return  
Tube, Front Oil Return  
Guard, Probe and High-Limit  
Clamp, Probe and High-Limit Bulb  
Plate, Drain Nipple Closure  
Nipple, " x 2.345" NPT Toe  
* Not illustrated.  
2-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 2: PARTS LIST  
2.10 Drain Valve and Components  
11  
9
7
8
10  
6
5
4
3
2
1
ITEM  
PART #  
810-2867  
200-8867  
106-6020  
816-0220  
807-2103  
220-3517  
826-1366  
809-0988  
200-1257  
823-4883  
816-0547  
COMPONENT  
1
2
3
4
5
6
7
8
Valve, Drain 1¼" (1" Std. Port)  
Strap, 3" Drain  
Bracket Assembly  
Insulation  
Switch, Micro CE Straight Lever  
Cover, Safety Switch  
Nut, 4-40 Keps Hex (Pkg. of 25)  
Washer, 1" OD x .525" ID Teflon  
Retainer, Nut, Drain Valve  
Handle, Drain Valve  
9
10  
11  
Sleeve, Plastic, 1 ¼" Red  
2-16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 2: PARTS LIST  
2.11 Wiring Connectors, Pin Terminals, and Power Cords  
3
1
2
5
4
6
7
8
9
10  
13  
12  
11  
ITEM  
PART #  
COMPONENT  
*
106-7649  
Power Cord Assembly 120V 10’ 16 gauge  
Connectors  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
807-1068  
807-0158  
807-0156  
807-0159  
807-0875  
807-1067  
807-0157  
807-0155  
807-0160  
807-0804  
826-1341  
826-1342  
807-2518  
2-Pin Female  
6-Pin Female  
9-Pin Female  
12-Pin Female  
15-Pin Female  
2-Pin Male  
6-Pin Male  
9-Pin Male  
12-Pin Male  
15-Pin Male  
Terminal, Female Split Pin (Pkg. of 25)  
Terminal, Male Split Pin (Pkg. of 25)  
Plug, Mate-N-Lock (Dummy Pin)  
* Not illustrated.  
2-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
YSCFC SERIES FLATBOTTOM GAS FRYERS  
CHAPTER 2: PARTS LIST  
2.12 Screws, Nuts, and Fasteners  
ITEM  
PART #  
826-1389  
826-1359  
809-0853  
809-0839  
809-0918  
826-1371  
826-1374  
809-0766  
809-0823  
809-0247  
809-0834  
809-0050  
826-1366  
826-1362  
809-0987  
809-0885  
809-0191  
COMPONENT  
Screw, ¼-20 x ¾" (Pkg. of 10)  
Screw, 4-40 x ¾" Slotted Round Head (Pkg. of 25)  
Screw, 10-32 x 1.5" Slotted Pan Head  
Screw, 8-32 x .75" Slotted Pan Head  
Screw, 10-24 x ½"  
Screw, #8 x .50" Slotted Hex Head (Pkg. of 25)  
Screw, #10 - ½" Hex Washer Head (Pkg. of 25)  
Nut, 10-32 Hex Head  
Nut, ¼-20 Nylock  
Nut, 8-32 Keps  
Nut, 8-32 Hex Locknut  
Nut, 8-32 Hex Zinc Plated  
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
Nut, 4-40 Keps (Pkg. of 25) (used to mount microswitch)  
Nut, ¼-20 Hex, Zinc Plated  
Nut, ¼-20 Press, Stainless Steel  
Washer, Flat " x 1" x .083”  
Washer, ¼" Lock  
* Not illustrated.  
2-18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Frymaster/Dean, 8700 Line Avenue, Shreveport, Louisiana 71106  
TEL 1-318-865-1711  
FAX (Parts) 1-318-688-2220  
FAX (Tech Support) 1-318-219-7135  
SERVICE HOTLINE  
1-800-551-8633  
819-6472  
FEB 2009  
PRINTED IN THE UNITED STATES  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Electro Voice Microphone PL37 User Manual
Flymo Trimmer Lawn Trimmer User Manual
FMI Indoor Fireplace VSGF36NRC User Manual
Ford Automobile F Series User Manual
Garland Range C0836 11 User Manual
Genelec Portable Speaker 1030A User Manual
Genius Home Theater System TH P3 User Manual
GE Oven JTP17SCSS User Manual
GE Telephone 15339430 User Manual
Global Machinery Company Drill MX372 User Manual