Oil- and Vacuum-Break
Switches
Service Information
Type S Automatic Load-Transfer Control
Installation, Operation, and Maintenance Instructions S260-75-1
Grounding the Control . . . . . . . . . . . . . . . . . . . . .6
Before Placing the Control and Switchgear
in Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Equipment Required . . . . . . . . . . . . . . . . . . . . . . .6
Customer Connections . . . . . . . . . . . . . . . . . . . . .8
Interconnecting Cables . . . . . . . . . . . . . . . . . . . . .13
Operating Instructions . . . . . . . . . . . . . . . . . . . . .16
Initial Operation . . . . . . . . . . . . . . . . . . . . . . . . . .16
Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . .17
Theory of Operation—Basic S Control . . . . . . . . .17
Voltage Sensing . . . . . . . . . . . . . . . . . . . . . . . . . .17
Automatic Transfer, Preferred to Alternate . . . . . .18
Return Transfer, Parallel Transition . . . . . . . . . . . .18
Return Transfer, Non-Parallel Transition . . . . . . . .18
No Preference Mode . . . . . . . . . . . . . . . . . . . . . .19
Preferred Source II Mode . . . . . . . . . . . . . . . . . . .19
Control Mode Switch, S5 . . . . . . . . . . . . . . . . . . .19
Manual Control . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Indicating Lamps . . . . . . . . . . . . . . . . . . . . . . . . .19
Remove the Control from Service . . . . . . . . . . . . .20
Troubleshooting—Basic S Control . . . . . . . . . . . .20
020076KM
Figure 1.
Kyle® Type S automatic load-transfer control.
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Basic Troubleshooting . . . . . . . . . . . . . . . . . . . . .20
Advanced Troubleshooting . . . . . . . . . . . . . . . . . .21
Fault Block Accessory . . . . . . . . . . . . . . . . . . . . .28
General Description . . . . . . . . . . . . . . . . . . . . . . .28
Accessory Settings . . . . . . . . . . . . . . . . . . . . . . . .28
Operating Instructions . . . . . . . . . . . . . . . . . . . . .29
Theory of Operation—Fault Block Accessory . . . .29
Overcurrent Sensing . . . . . . . . . . . . . . . . . . . . . .29
Phase Fault Operation . . . . . . . . . . . . . . . . . . . . .29
Ground Fault Operation . . . . . . . . . . . . . . . . . . . .32
Reset Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Inrush Restraint Feature . . . . . . . . . . . . . . . . . . . .32
Testing Fault Block Operation . . . . . . . . . . . . . . . .33
Returning the Control to Service . . . . . . . . . . . . . .35
Wiring Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . .40
Front Panel—Replacement Parts List . . . . . . . . . .41
Back Panel—Replacement Parts List . . . . . . . . . .42
Fault Block Accessory—Replacement Parts List . .43
Contents
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . .2
Hazard Statement Definitions . . . . . . . . . . . . . . . .2
Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . .2
Product Information . . . . . . . . . . . . . . . . . . . . . . .3
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Acceptance and Initial Inspection . . . . . . . . . . . . .3
Handling and Storage . . . . . . . . . . . . . . . . . . . . . .3
ANSI Standards . . . . . . . . . . . . . . . . . . . . . . . . . .3
Quality Standards . . . . . . . . . . . . . . . . . . . . . . . . .3
Description of Operation . . . . . . . . . . . . . . . . . . . .4
Time Delay Selection . . . . . . . . . . . . . . . . . . . . . .4
Pre-Installation Check . . . . . . . . . . . . . . . . . . . . . .5
Pre-lnstallation . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Installation Instructions . . . . . . . . . . . . . . . . . . . .6
Initial Programming . . . . . . . . . . . . . . . . . . . . . . .6
Mounting the Control . . . . . . . . . . . . . . . . . . . . . .6
October 2002 • Supersedes 1/90
Printed in USA
1
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S260-75-1
PRODUCT INFORMATION
Introduction
Handling and Storage
Service Information S260-75-1 provides installation,
operation, and maintenance instructions for the Kyle®
Type S automatic load-transfer control.
Use care during handling and storage of the control. If
the control is to be stored for any length of time prior to
installation, provide a clean, dry storage area to mini-
mize the possibility of mechanical damage.
Read This Manual First
Read and understand the contents of this manual and
follow all locally approved procedures and safety prac-
tices before installing or operating this equipment.
ANSI Standards
Kyle reclosers are designed and tested in accordance
with ANSI standards C37.60 and C37.85 and ANSI
guideline C37.61.
Additional Information
These instructions cannot cover all details or variations in
the equipment, procedures, or process described, nor to
provide directions for meeting every possible contin-
gency during installation, operation, or maintenance. For
additional information, contact your Cooper Power
Systems representative.
Quality Standards
The Quality System at the Cooper Power Systems, Kyle
Distribution Switchgear plant is ISO 9001 certified.
ISO 9001
CAN/CSA ISO 9001
BS EN ISO 9001
ANSI/ASQC Q9001
Acceptance and Initial
Inspection
Each Type S control is completely assembled, tested,
and inspected at the factory. It is carefully calibrated,
adjusted, and in good condition when accepted by the
carrier for shipment.
Upon receipt, inspect the carton for signs of damage.
Unpack the control and inspect it thoroughly for damage
incurred during shipment. If damage is discovered, file a
claim with the carrier immediately.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions
Description of Operation
IMPORTANT: If Control Mode Switch S3 is placed in
the “AUTO” position, the S-control will place the high-
voltage transfer switches into the configuration that is
currently selected by the Source Preference Switch
S4. This may result in an unintended transfer. Make
sure the desired state of the high-voltage transfer
switches match the setting of S4 before returning S3 to
the “AUTO” position.
The Type S control is designed for use primarily with Kyle
Type VR, VLR, VRV, TSC, and C three-phase, load-break
switches in automatic load-transfer schemes. In a typical
scheme, service to a critical load is normally supplied from
a preferred source. It is automatically switched to an alter-
nate, standby source if the preferred source voltage is lost
for any reason for a preset period of time. Upon restora-
tion of the preferred source voltage, the load is automati-
cally switched back to the preferred source, again after a
predetermined time delay.
• Manual Operation of the S control. The Source I and
Source II high-voltage switches can be opened and
closed independently to effect manual transfer from
one source to the other. (Accomplished by setting
OPERATION SELECTOR switch, S3, to MANUAL and
operating MANUAL OPER. SOURCE I (S1) and MAN-
UAL OPER. SOURCE II (S2) switches as required.)
Typical Automatic Load-transfer
Sequence using the Type S Control
• The load is transferred to the alternate source after a
preset time delay, when the preferred source voltage
is lost and normal voltage is present on the alternate
source. Either Source I or Source II can be selected
as the preferred source by a setting on the SOURCE
PREFERENCE Switch, S4.
In addition, a factory-installed fault block accessory will
Block Transfer if loss of voltage is due to a fault on the
load side of the high-voltage switches. When preferred
source voltage is lost (due to the opening of the backup
protective device)—and after the preset time delay—the
preferred source switch will open and the fault block
accessory will disable the S control to prevent closing
either high-voltage switch into the fault. The S control
must be manually reset before service to the load can be
restored. The fault block option is a factory-installed
accessory. The accessory is activated by over-current
signals supplied by load-sensing current transformers
built into special factory-modified Type VR, VLR, VRV,
TSC, and CS high-voltage switches. It is also compatible
with the PST-6 switchgear. The PST-9 switchgear does
not require fault block.
• The load is transferred back to the preferred source—
after another preset time delay—when normal volt-
age is restored to the preferred source. The return
transfer (from Source II to Source I) can be either
non-parallel (alternate-source switch opens before
preferred-source switch closes) or parallel (preferred-
source switch closes before alternate-source switch
opens). With parallel return the second interruption is
eliminated; however, both sources must be in syn-
chronism. The return transfer mode is selected by a
setting on the SOURCE PREFERENCE switch, S4.
Variations in the Operation
of the Type S Control
Time Delay Selection
The time delay setting for preferred to alternate source
transfer must be long enough to allow discrimination
between permanent loss of voltage and temporary loss of
voltage due to transient effects or reclosing intervals of
backup protective reclosers or breakers. The time-delay
required to override reclosing intervals is difficult to deter-
mine since voltage may be subnormal during the retard-
ed timing operations of the backup device due to the
presence of the fault. It is recommended that the time
delay before transfer from preferred to alternate source is
set to exceed the maximum cumulative time to lockout of
the backup protective device. This approach assures that
the transfer switch will not interrupt the current of a fault
occurring on the load side of the switch.
• No-Preference Operation. When either source is
acceptable for continuous critical load supply. Upon
loss of Source I voltage—and after a preset time
delay—the load is automatically transferred to Source
II, provided normal voltage is present on Source II.
However, the load is not transferred back to Source I
when voltage is restored, but remains on Source II
until such time as Source II voltage is lost. Then an
automatic nonparallel transfer to Source I is per-
formed. (Accomplished by setting SOURCE PREF-
ERENCE switch, S4, to NO PREF position.)
• Hold on Alternate Source. When placed to the
HOLD ON ALTERNATE position, the S control will not
automatically return to the preferred feeder. If the pre-
ferred feeder is energized, the S control can be man-
ually transferred to the preferred feeder by momen-
tarily moving S3 to the NORMAL position.
The time delay for return from alternate to preferred source
upon restoration of preferred source voltage should be set
for an interval long enough to assure that service on the
preferred source has been permanently restored.
When the control is programmed to operate in the “no-
preference” mode, there are no preferred or alternate
sources. Time delay intervals for transfer from Source I to
Source II are governed by the left-hand Preferred to
Alternate timer and for transfer from Source II to Source
I by the right-hand Alternate to Preferred Timer. Settings
of the two timers may be different because of difference
in backup protection on the two sources.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S260-75-1
PRE-INSTALLATION CHECK
between terminal 15 of TB1 and ground. Similarly,
when MANUAL OPER. SOURCE II switch (S2) is in
the CLOSE position there should be 120 Vac
between terminal 25 of TB1 and ground.
Pre-Installation
WARNING: This equipment is not intended to
!
protect human life. Follow all locally approved pro-
cedures and safety practices when installing or operat-
ing this equipment. Failure to comply can result in
death, several personal injury and equipment damage.
G102.1
5. To check the response of the latching relay to auto-
matic operation, proceed as follows:
A. Set OPERATION SELECTOR switch (S3) to AUTO.
B. Select the desired source preference and return
mode with switch S4.
WARNING: Hazardous voltage. Never rely on
C. After waiting for a time in excess of the maximum
transfer delay timer setting (to make sure the con-
trol is at rest), simulate a “lost” phase by unscrew-
ing one of the preferred source fuses. Listen for
relay clatter to recognize breaking the circuit.
!
the open position of the operating handle or the
contact position indicator; it does not ensure that the
line is deenergized. Follow all locally approved safety
practices. Failure to comply can result in contact with
high voltage, which will cause death or severe person-
al injury.
G123.1
D. As soon as phase voltage is lost, the PREFERRED
TO ALTERNATE TIMER will start to run. Verify the
LED timer is illuminated during operation.
The Type S automatic load-transfer control is pro-
grammed to customer’s specifications and thoroughly
tested before shipment from the factory. Perform the fol-
lowing pre-installation test setup and procedure to verify
the operation of the standard S control.
E. When timing is complete, the latching relay (R1)
will operate. Its position can be checked by the
presence of 120 Vac at test terminals T-1 or T-2 on
the front panel. 120 Vac between T-2 and T-3
(ground) means the latching relay has moved to
that position which would connect the load to
Source II if HV switches were connected to the
control. 120 Vac at T-1 means the load would be
connected to Source I.
Note: This procedure does not test complete control opera-
tion. This can be done only on a complete installation
basis with the S control operating the high-voltage
transfer switches.
Test Set–up
1. Connect a 120 Vac, 60 Hz power supply to terminals Z
and G2 of TB2 being absolutely certain that the
grounded side of the power supply is connected to G2.
F. Replace the removed fuse to restore preferred
source power, observe operation of the ALTER-
NATE TO PREFERRED TIMER, and check the
status of the latching relay (R1) when timing is
completed.
2. Jumper terminal Z to Y to X to C to B to A.
Note: SOURCE PREFERENCE switch S4 cannot be
3. When the 120 Vac power supply is turned on, all six
in NO PREF position for this test.
phases are energized.
G. Other modes of transfer can be checked by pro-
gramming the control for the desired sequence,
simulating loss of source voltage, observing resul-
tant control operation, and checking the final posi-
tion of the latching relay (R1).
4. To simulate loss of voltage on any phase of either
source, simply unscrew the appropriate fuse “FU” in
the control.
Test Procedure
6. Timer settings can be verified with a watch while per-
1. Check the indicating lamps by depressing the LAMP
TEST switch (S6). All lamps on the front panel of the
control (including fault block accessory if installed)
should light with equal brilliance.
forming the checks in preceding Step 5.
7. Switch I and Switch II position indicating lamps will
not operate during this preinstallation check since the
high-voltage transfer switches are not connected to
the control.
2. With phase Y and/or phase B energized, terminals 11
and 21 of TB1 will always show 120 Vac to ground
(G or G ).
Their operation can be verified by connecting a 100
ohm, 1 watt, resistor from TB1 terminals to ground
as follows:
1
2
3. With OPERATIONS SELECTOR switch (S3) set to
MANUAL, terminal 13 of TB1 will respond to the
operation of MANUAL OPER. SOURCE I switch (S1)
showing 120 Vac to ground when S1 is in the open
position and 10 Vac, or less, when S1 is in the OFF
and CLOSE positions. Terminal 23 of TB1 will show
similar voltages to ground in response to the opera-
tion of MANUAL OPER.
SWITCH I OPEN lamp—terminal 15 to ground
SWITCH I CLOSED lamp—terminal 24 to ground
SWITCH II OPEN lamp—terminal 25 to ground
SWITCH II CLOSED lamp—terminal 14 to ground
4. When MANUAL OPER. SOURCE I switch (S1) is in
the CLOSE position there should be 120 Vac
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions
INSTALLATION INSTRUCTIONS
A typical automatic transfer scheme is illustrated in Figure 2.
Before Placing the Control and
Switchgear into Service
Initial Programming
CAUTION: Equipment misoperation. Do not
The control must be programmed with all necessary
operating settings prior to operation with energized
switchgear. For the desired settings refer to the
Operating Instructions section in this manual.
!
energize this equipment until all control settings
have been properly programmed and verified. Refer to
the Control Programming and Operation section of this
manual for programming procedures. Failure to com-
ply can result in misoperation (unintended operation),
Mounting the Control
equipment damage, and personal injury.
G118.1
Mount the S control in a convenient, accessible location.
Maximum distances between the high-voltage transfer
switches and potential sensing transformers and the con-
trol depends upon the size of the control cable wire and
the length of various cable combinations. (See the
Interconnecting Cables section in this manual.) Keep in
mind that the longer the cable lengths, the greater the
susceptibility to surge damage. Therefore, for optimum
reliability and economy, locate the switches and trans-
formers as near as possible to the control.
Prior to placing the control and switchgear into service,
the following installation procedures must be properly
completed and verified:
1. Control properly mounted for the installation.
2. Equipment installed according to all locally approved
standards and practices.
3. Control and switchgear properly grounded in accor-
dance with guidelines in this manual.
Mounting dimensions are provided in Figure 3.
4. AC power connected to the control.
• For pole-mounted installation, a hole and keyway in
the control mounting bracket accommodates a 5/8”
bolt.
5. All control programming entered and verified by
appropriate personnel.
• For substation installation, the control is factory
installed. Leveling is not required.
Equipment Required
The following equipment is required for a load-transfer
installation:
Grounding the Control
Type S Load-Transfer Control
WARNING: Hazardous voltage. Solidly ground
!
all equipment. Failure to comply can result in
The control, with or without the fault block accessory, is
housed in a cabinet whose outline and mounting dimen-
sions are shown in Figure 3. The control cabinet can be
mounted on a pole or substation structure. Leveling is not
required. Both the cabinet door and the hinged front
panel are equipped with hold-open latches to prevent
them from swinging in the open position.
death, severe personal injury, and equipment damage.
T223.2
The control cabinet must be grounded. A grounding con-
nector on the underside of the cabinet will accommodate
No. 14 solid through No. 4 stranded conductors.
For efffective surge protection all control and power con-
ductors for the S control must be routed parallel to a cor-
responding ground path. For example, the AC power
supply for the control should be parallel to and equal in
length to the transformer ground path. The control cable
should be parallel to and routed close to the switchgear
ground path.
Motor Operated Switches
The three-phase, load break switches require a special
wiring accessory for operation with the Type S control. In
addition, if fault block is provided, the switches must be
equipped with 1000:1 ratio current transformers also
available as a factory-installed switch accessory. See the
switch installation manual for overall and mounting
dimensions and for wiring diagrams.
Potential Transformers
Three-phase voltage sensing is required for control oper-
ation. Transformer connections and voltages for various
distribution system connections are shown in Figure 5.
The voltage sensing relays of the Type S control drop out
on a decreasing voltage at 75 volts (min) and pick up on
an increasing voltage at 97 volts (max). The control
requires 120 Vac, 60 Hz, 500 VA (min) to operate the
transformer switches. Quiescent power dissipation at
120 Vac is 18 watts.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S260-75-1
LOAD
SOURCE II
H.V.
SWITCH
II
SOURCE I
H.V.
SWITCH
I
POTENTIAL
SENSING
TRANSFORMERS
POTENTIAL
SENSING
TRANSFORMERS
TYPE
S
CONTROL
Figure 2.
Typical Type S control load-transfer scheme.
MTG HOLES (2) FOR
5/8" MAX BOLT DIA
16"
8"
12 13/16"
1 1/2"
20 1/8"
MTG DIM
17 7/8"
22 5/32"
5/8" HOLE PROVIDED
FOR CUSTOMER LOCK
GROUNDING
TERMINAL LUG
(14 TO 4 STRANDED)
11"
1 3/16"
13 1/2"
2 1/2" 2 1/2"
2 1/2" 2 1/2"
1 5/8" DIA HOLES
5 1/4"
STD CONTROL
CONTROL WITH FAULT BLOCK
Figure 3.
Outline and mounting dimensions.
TABLE 1
Reaction and Transition Times of Cooper Power Systems Motor-Operated Switches
Direction of
Transfer
(Source to
Source)
First Switch
Reaction Time*
Transition
Time**
Switch
Type of Transition
No paralleling of sources
VR, VLR, VRV (standard)
VR, VLR, VRV (standard)
VR, VLR, VRV (standard)
2.5 to 3.5 cycles 10 sec (approx)
2.5 to 3.5 cycles 10 sec (approx)
10 sec (approx) 1.0 to 1.5 cycles
I to II
II to I
II to I
No paralleling of sources
Paralleling of sources on return to preferred source
VR, VLR, VRV (quick close) 2.5 to 3.5 cycles 6 to 7 cycles
VR, VLR, VRV (quick close) 2.5 to 3.5 cycles 6 to 7 cycles
VR, VLR, VRV (quick close) 4.0 to 5.5 cycles 1.0 to 1.5 cycles
I to II
II to I
II to I
No paralleling of sources
No paralleling of sources
Paralleling of sources on return to preferred source
TSC
TSC
TSC
7 to 8 sec
7 to 8 sec
7 to 8 sec
7 to 8 sec
7 to 8 sec
7 to 8 sec
I to II
II to I
II to I
No paralleling of sources
No paralleling of sources
Paralleling of sources on return to preferred source
PST-6, PST-9
PST-6, PST-9
PST-6, PST-9
2.0 to 3.0 cycles 5.0 to 6.0 cycles
2.0 to 3.0 cycles 5.0 to 6.0 cycles
5.0 to 6.0 cycles 2.0 to 3.0 cycles
I to II
II to I
II to I
No paralleling of sources
No paralleling of sources
Paralleling of sources on return to preferred source
*
Time from expiration of time delay to first opening (or closing) of high-voltage switch. Add approximately one cycle to the
values shown to allow for Type S control relay operating time.
** Time-load tap is disconnected or paralleled depending on type of transition used.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions
LOAD
C
A
D
H.V.
H.V.
SWITCH
SWITCH
SOURCE
FEEDER
B
S
CONT
Phase Voltage at the Three-Phase Sensing Type S Load Transfer Control as Related to System and Sensing Transformer Connections
%
*
Assuming no feedback from the load
** Bank operates open wye-delta; requires two primary phases open for sensing
† Voltage may vary from 87 to 58% depending on load
Figure 4.
Phase voltage at the three-phase sensing Type S load-transfer control.
the internal wiring between the terminal blocks and the
Customer Connections
Connection Diagram
input and output receptacles on the control (available as
an accessory) and the external wiring between the con-
trol, transfer switches, and potential transformers. If the
control is not equipped with the plugs and receptacles
accessory, the cables are wired directly to the terminal
blocks in the control. For the physical location of terminal
blocks, refer to Figure 27.
CAUTION: Equipment Damage. Do not drill connec-
tion holes into the top of the cabinet. Connection holes in
the top of the cabinet will allow moisture to seep into the
control and damage the components or cause control
misoperation. Failure to comply will void the control’s fac-
Note: Internally wired receptacles and mating plugs for the
switch operators and current sensing transformers on
the switch end of the cables are provided as standard
with the switches.
tory warranty.
T249.0
Diagrams for interconnecting the load-transfer control
with the high-voltage switches and potential transformers
are shown in Figures 5 through 8. The diagrams show
8
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S260-75-1
Figure 5.
Connection diagram for Type S load-transfer control (with fault block accessory) operating a Type VR, VLR, or
VRV three-phase switch. (The transformer cutouts, tap fuses, reclosers, and arresters are not shown.)
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions
O P E N
C L O S E
O P E N
C L O S E
Figure 6.
Connection diagram for Type S load-transfer control (with fault block accessory) operating the Type TSC
three-phase switch. (The transformer cutouts, tap fuses, reclosers, and arresters are not shown.)
10
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S260-75-1
Figure 7.
Connection diagram for Type S load-transfer control operating the Type PST-6 switch. (The transformer cutouts,
tap fuses, reclosers, and arresters are not shown.)
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions
Figure 8.
Connection diagram for Type S load-transfer control operating the Type PST-9 switch. (The transformer cutouts,
tap fuses, reclosers, and arresters are not shown.)
12
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S260-75-1
Interconnecting Cables
Interconnecting cable conductor size is dependent upon
the distance between the control, switches, and potential
transformers. Maximum lengths of various cable combi-
nations for No. 18 through No. 12 AWG conductors are
shown in Table 2. The longest combination for the partic-
ular installation will determine the minimum conductor
size. All cables are to be the same conductor size.
Note: If the control is equipped with the fault block accesso-
ry, see Table 3 for additional cable length limitations.
On the switch end, the cables are wired to connector
plugs provided as standard with the switches. On the S
control end, the cables are wired either directly to termi-
nal blocks in the control or to connector plugs provided
with the Plugs and Receptacles accessory. Figure 9
shows the location of the accessory plugs and recepta-
cles in the bottom of the control cabinet. See the appro-
priate switch installation manual for the location of the
plugs and receptacles on the switch.
020079KM
Figure 9.
Plugs and receptacles accessory.
Switch Cable
KEYWAY
A conductor cable is required between the S control and
each high-voltage switch to operate the switches. This
cable is wired to a socket plug at the switch end and to
either a plug or TB1 at the control end. Pin identification,
and cable OD and maximum conductor size accommo-
dated by the plugs are shown in Figures 10 and 11.
PIN INSERT CONNECTIONS INTO CONTROL
PIN F
A
VIEW A-A
RUBBER GROMMET
ACCOMMODATES
1/2" TO 5/8" DIA. CABLE
A
Potential Transformer Cable
MAX. WIRE SIZE – NO.16 AWG
A four-conductor cable is required between the S control
and the potential transformers to transmit source voltage
intelligence and to supply operating power for the control.
This cable is wired to a five-pin socket plug or TB2 at the
control end. Pin socket identification, cable OD, and
maximum conductor size accommodated by the plugs
are shown in Figure 12.
Figure 10.
Switch cable plug for VR, VLR, VRV, and TSC.
PST-6 8, 7, & 19 PIN RECEPTACLES
PST-9 8 & 19 PIN RECEPTACLES
Note: Connectors are not supplied for the transformer end of
KEYWAY
PIN INSERT CONNECTIONS INTO CONTROL
PIN F
the cable.
A
M
A
L
T
F
A
C
A
G
N
B
C
D
K
J
U
TABLE 2
Maximum Control Cable Lengths
B
C
E
F
G
B
H
V
P
R
H
S
E
D
D
G
E
F
LOAD
8 PIN
7 PIN
19 PIN
A
HV
SW
2
HV
SW
1
VIEW A-A
Figure 11.
Switch cable plugs for PST-6 and PST-9.
S CONTROL
D
B
A
C
KEYWAY
SOCKET E
SOCKET INSERT – CONNECTS INTO CONTROL
Maximum Length of
Control Cable Combinations (ft.)
A
Cable Wire
Size
(AWG)
VR, VLR, or VRV Switches TSC Switch
A+B+D or C+B+D
A+B or A+D
or C+B or C+D
18
16
14
12
1450
2300
3700
5900
1250
2000
3200
5050
A
RUBBER GROMMET
ACCOMMODATES
3/8" TO 1/2" DIA. CABLE
MAX. WIRE SIZE – NO.12 AWG
Note: The control cable lengths are not applicable for the C
Figure 12.
PT cable plug.
switch and the PST switch.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions
Fault Block Shielded Cable
Table 3 shows the maximum distance between the con-
TABLE 3
Fault Block Cable Limitations
trol and the high-voltage switches for a range of conduc-
tor sizes and fault-block settings. The table is based on
conductor voltage drop and saturation of the current
sensing transformers in the switch. Lower actuating lev-
els and lower multipliers could allow longer lines.
However, the limitation on switch control cable lengths,
Table 2, preclude their use.
Max. Distance in Feet
Between Switch and
S Control
Phase
Actuating
Current
Level
Con-
ductor
Size
For X 8
Multi-
plier
For X 6
Multi-
plier
For X 4
Multi-
plier
(Amps)
(AWG)
640
640
640
640
18
16
14
12
600
950
1500
2400
1000
1600
2550
4000
1800
2900
4600
7300
Shielded cable is required between the transfer switches
and the S control for operating the fault block accessory.
448
448
448
448
320
320
320
320
18
16
14
12
18
16
14
12
1100
1800
2800
4500
1800
2900
4600
7300
1700
2700
4300
6850
–
–
–
–
–
–
–
–
–
–
–
–
IMPORTANT: Only shielded cable is to be used on fault
block accessory and is mandatory to validate the
Cooper Power Systems warranty. Use of a non-shielded
cable could result in misoperation.
The shield must be grounded to the equipment housing
at both the switch and control ends. Shield connections
are made at connector plug pin or socket as shown in
Figure 13. This pin mates with the receptacle pin or sock-
et which is grounded in the switch and in the control as
shown in Figures 6 and 8.
SOLDER #16 AWG JUMPER WIRE
FROM SHIELD TO PIN G TO
COMPLETE SHIELD CONNECTION
RUBBER GROMMET
ACCOMMODATES
KEYWAY
KEYWAY
.50 TO .56 DIA. CABLE
PIN G
SOCKET A
A
A
CONTROL END
SWITCH END
STRIP JACKET TO EXPOSE SHIELDING
Figure 13.
Fault block cable plug.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S260-75-1
6
7
8
5
4
9
3
2
10
11
1
12
13
14
15
020076KM
Figure 14.
Type S control front panel.
TABLE 4
Description and Use of Operating Controls and Indicators
Index No.
Figure 2
Description
Purpose and Use
1
SOURCE PREFERENCE AND RETURN MODE
Switch (S4) (See Note A)
Selects either Source I (PREF I) or Source II (PREF II) as the
preferred source, or no preference (NO PREF). Also selected
parallel (P) or non-parallel (NP) return mode.
2
3
4
SOURCE I ENERGIZED lamp
OPERATION SELECTOR Switch (S3)
PREFERRED TO ALTERNATE TIMER
Indicates all three phases of Source I are energized.
Programs control for either AUTOmatic or MANUAL operation.
Determines time delay before transfer to alternate source when
preferred source voltage is lost.
5
6
7
SWITCH I OPEN and CLOSED lamps
LAMP TEST switch (S6)
LATCH RELAY STATUS TEST terminals
(T1—T2—T3)
Indicates status of Source I high voltage switch.
Tests all indicating lamps on front panel.
Provides electrical access to both sides of latch relay to
determine if control is in Source I or Source II mode.
8
9
SWITCH II OPEN and CLOSED lamps
ALTERNATE TO PREFERRED TIMER
Indicates status of Source II high voltage switch.
Determines the time delay before transfer to preferred source
when preferred source voltage is restored.
10
MANUAL OPER. SOURCE I and MANUAL OPER. Provides means to OPEN and CLOSE Source I and Source II
SOURCE II switches (S1 and S2)
transfer switch upon manual command, when S3 is in MANUAL
position.
11
12
SOURCE II ENERGIZED lamp
CONTROL MODE switch (S5)
Indicates all three phases of Source II are energized.
Blocks automatic return transfer to preferred sources (HOLD ON
ALTERNATE); also enables control to be operated without
operating the high voltage transfer switches (TEST).
13
14
FAULT-BLOCK OPERATED lamp
RESET switch (S7)
Indicates fault-block has operated (part of fault-block accessory).
Resets the control after a fault block operation (part of fault-block
accessory). S3 must be in MANUAL position.
15
Fuses
Voltage input of all three phases of both Source I and Source II
are fused for 10A-125 vac; white button shows on front of fuse if
fuse blows.
Note A — Tab provided to lock switch knob in set position; stop screw prevents inadvertent selection of parallel return transfer mode.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions
OPERATING INSTRUCTIONS
1. The switches on the front panel should be positioned
DANGER: Hazardous voltage. Contact with haz-
as follows:
!
ardous voltage will cause death or severe person-
A. S1 (MANUAL OPER. SOURCEI) — OFF
B. S2 (MANUAL OPER. SOURCE II) — OFF
C. S3 (OPERATlON SELECTOR) — MANUAL
al injury. Follow all locally approved safety procedures
when working around high and low voltage lines and
equipment.
G103.3
D. S4 (SOURCE PREFERENCE AND RETURN
MODE) — set to the desired mode of operation.
WARNING: Hazardous voltage. Never rely on
!
the open position of the operating handle or the
E. S5 (CONTROL MODE) — NORMAL
contact position indicator; it does not ensure that the
line is deenergized. Follow all locally approved safety
practices. Failure to comply can result in contact with
high voltage, which wil cause death or severe person-
2. Set the PREFERRED TO ALTERNATE TIMER and
ALTERNATE TO PREFERRED TIMER as required.
(See Time Delay section in this manual.)
al injury.
G123.1
3. Check that all installation connections are complete
as shown in the appropriate connection diagram
Figures 5 through 8.
Before energizing the installation, an understanding of
the functions of the operating controls and indicating
lights is essential. (See Table 4 and Figure 14).
4. Make sure both high-voltage transfer switches are open.
5. With all six fuses in place, energize both power
Initial Operation
sources to the control.
To place the automatic transfer scheme into service, pro-
ceed as follows:
A. SOURCE I ENERGIZED lamp should be on.
B. SOURCE II ENERGIZED lamp should be on.
C. SWITCH I OPEN lamp should be on.
CAUTION: Equipment misoperation. Source I and
Source II high voltage switches can be paralleled in the
manual operation mode even if SOURCE PREFER-
ENCE switch, S4, is set for NP (non-parallel opera-
tion). Make sure both sources are in synchronism if a
manual parallel operation is to be performed. Failure to
comply can result in misoperation (unintended opera-
D. SWITCH II OPEN lamp should be on.
6. Depending upon which source is the preferred
source, momentarily operate either S1 or S2 to the
CLOSE position. The appropriate switch will close to
energize the load and its status indicating lights will
transfer from OPEN to CLOSED.
tion) and equipment damage.
T304.0
7. Place the OPERATION SELECTOR SWITCH (S3) to
AUTO. The S control is in service. No further opera-
tion will occur until the preferred source voltage is lost.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S260-75-1
Out Indicator
Timer Settings
The out indicator briefly lights to signal completion of a
timing interval and confirm that the timer has operated.
IMPORTANT: Put control in manual mode prior to
changing timer setting. There is no fault current pro-
tection when in manual mode. Failure to comply can
cause unintended operation.
Normal Operation
The control will react to ongoing line voltage conditions
and operate automatically as programmed. If equipped
with the fault block accessory, transfer to the alternate
source may be prevented when loss of voltage is due to
The two digital timers are identical. One timer controls the
time required to transfer from the preferred source to the
alternate source, the other timer controls the time to trans-
fer from the alternate source to the preferred source.
a
load-side fault. See Fault Block Operating
Instructions section for procedure to restore service.
OUT Indicator
THEORY OF OPERATION
—BASIC S CONTROL
OUT
Digital Time
Thumb-Wheel
Time Setting
3.45
9
3 49
5
Refer to Figures 16 and 17 for the following sections:
Display
Voltage Sensing
The S control will transfer the load to an alternate source
when one or more phases of the preferred source is lost,
provided normal voltage is present on all three phases of
the alternate source. To perform this function, the control
requires three-phase, low-voltage (120 Vac) input from
both the preferred and alternate sources of power. Input
from Source I is connected to terminals A, B, C and G1
of TB2, and input from Source II is connected to termi-
nals X, Y, Z and G2.
9 9 9
Decimal Point
Indicator
S
Time Range
Selector
Figure 15.
Digital Timer and Time Ranges.
The two digital timers feature the following informational
indicators and adjustment controls:
Each of the three input phase leads for both Source I and
Source II is shunted to ground by a capacitor–varistor
combination to provide surge protection to the control.
On the preferred source side of the voltage sensing cir-
cuitry, the input lines then pass through 10 Amp fuses to
the voltage sensing relays: R2 (Phase A), R9 (Phase B)
and R10 (Phase C). R9 and R10 are connected directly
to the input while N.O. contacts of R9 and R10 are in
series with the R2 coil. Thus, R2 can be energized only if
all three incoming phase voltages are above a predeter-
mined value (approximately 97 volts). A similar arrange-
ment is used for the alternate source sensing relays. R6
can be energized only if R7 and R8 are energized. The
transfer bus across the top of the schematic diagram),
which provides the operating power for the control is nor-
mally energized from Phase Y. If R7 drops out, due to
loss of Phase Y, R11 will be energized from Phase B
(through N.C. contact of R7) to re-energize the transfer
bus. The contacts of R7 and R11 are so connected that
the transfer bus can never be simultaneously energized
from both B and Y phases.
Digital Time Display
LED displays the time count. The timer counts up until it
reaches the time delay setting of the thumbwheel switch.
Time Range Selector
The time range selector switch can be set to six different
positions with a flat screwdriver. Each position indicates a
time range. See chart below. The time range selector is
preset to the time range of 0.1 to 99.9 seconds.
9.99
99.9 999
99.9
999
99.9
S
M
H
S
S
M
Indication
0.1
to
0.1
to
1
to
1
to
0.1
to
99.9
min
0.01
to
9.99
sec
Time
Range
99.9
hours
99.9 999
sec sec
999
min
Thumbwheel Time Setting
IMPORTANT: Thumb-wheel time setting must be
securely turned. Incomplete setting may cause timer
malfunction and control misoperation.
Set the desired time delay setting by rotating the thumb-
wheel switch. For example, if the thumbwheel time set-
ting is 345 the timer will time out in 34.5 seconds based
off the time range selector setting of 0.1 to 99.9 seconds.
Note: The thumb-wheel time setting, which does not turn
infinitely, should not be turned beyond the limit.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions
The transfer of R1 energizes the close coil of SW-I as follows:
Automatic Transfer, Preferred to
Alternate
Transfer bus voltage passes through terminals 5-1 of S3,
contacts 9-6 of latched R1, and terminals 5-6 of S5. It is
then impressed on N.C. contact 7-2 of R5 and passes
through deck A of S4 to output terminal 15 of TB-1. This
activates the close coil in SW-I. When SW-I closes, its
auxiliary contact “a” closes to energize R5 (via TB1-24
and deck E of S4). Contact 7-5 of R5 closes to energize
TB1-23 through deck D of S4. Voltage at TB1-23 will
actuate the trip coil of SW-II to open the Source II high-
voltage transfer switch.
The following assumptions are made:
• OPERATION SELECTOR switch (S3) is in AUTO.
• SOURCE PREFERENCE and RETURN MODE
switch (S4) is in PREF l-P (Terminal 2 of each deck
connected).
• CONTROL MODE switch (S5) is in NORMAL.
• S control is in a quiescent state.
Note: The Source I high-voltage switch (SW-I) closes before
the Source II high-voltage switch (SW-II) opens to
effect a parallel return transition. SW-I will now remain
closed and SW-II open until Source I voltage is lost or
a change of control settings is made.
• Source I high-voltage transfer switch (SW-I) is closed
and Source II high voltage transfer switch (SW-II) is
open.
Note: The actuators of both high-voltage transfer switch-
es are shown in the switch open position on the
schematic diagram. Following each opening opera-
tion, the motor recharges the actuator springs and
the cutout switch returns to the position shown in
the schematic. However, when the high voltage
transfer switch is closed, the selector switch of the
actuator mechanism is opposite to that shown in
the schematic.
Return Transfer, Non-Parallel
Transition
The following assumptions are made:
• SOURCE PREFERENCE and RETURN MODE
switch (S4) is in PREF l-NP (Terminal 3 of each
deck connected).
If one or more phases of the preferred source (Source I)
are lost, R2 will drop out and the SOURCE I ENER-
GIZED lamp (L1) will go out. N.C. contacts 1-7 of R2
close completing the circuit to the PREFERRED TO
ALTERNATE TlMER (TM1) through 4-7 of R6 (which is
energized), 7-4 of R1, and deck J of S4. When TM1 times
out, its 5-6 contacts close to energize the coil of R1 in the
reset direction causing R1 to transfer. Diodes in the cir-
cuit of this single-coil magnetically held relay determine
whether “latching” or “resetting” occurs.
• Source I has lost one or more phases and the load
has been transferred to Source II as previously
described (SW-I open and SW-II closed).
• Control is in a quiescent state with latching relay R1
in the reset position (contacts 9-3 and 8-2 closed)
and R2 is deenergized.
When Source I power is restored on all three phases, R2
will pick up, closing its contact 9-6, and energize the
ALTERNATE TO PREFERRED TIMER (TM-2) through
contact 8-2 of R1, and deck K of S4. After TM-2 times
out, its 5-6 contact closes to energize the coiI of R1
through diode DL in the latching direction causing R1 to
transfer, closing its 6-9 contact.
The transfer of R1 energizes the trip coil of Source I high-
voltage transfer switch (SW-I) as follows:
Transfer bus voltage passes through terminals 5-1 of S3,
contact 9-3 of energized R1, and terminals 4-3 of S5. It
is then impressed on N.C. contact 7-2 of R4 and passes
through deck B of S4 to output terminal 13 of TB-1.
Terminal 13 is connected to the internal selector switch in
the actuator of SW-I (which is closed when SW-I is
closed), through the trip coil to ground (terminal G).
In this case, the trip coil of SW-II is immediately ener-
gized through the following circuit:
Terminals 5-1 of S3, N.C. contact 9-6 of R1, terminals 5-
6 of S5, N.C. contact 7-2 of R5, and deck D of S4 to out-
put terminal TB1-23 to activate the trip coil of SW-I I and
open to Source II high-voltage transfer switch.
After SW-I has opened, the selector transfers to connect
terminal 3 to terminal 4, which energizes terminal 16 of
TB1. In turn contacts 2-6 of S3, deck C of S4, and termi-
nal 25 of TB-1 are energized to operate the close coil of
SW-II and close the switch.
When SW-II opens, its selector switch transfers to
impress the voltage at TB1-23 onto TB1-26 which, in turn,
energizes TB1-15 through terminals 3-7 of S3 and deck A
of S4. Voltage at TB-15 will actuate the quick-close coil of
SW-I to close the Source I high-voltage switch.
SW-I will now remain open and SW-II closed until Source
I voltage is restored.
Note: In this instance, the Source II high voltage switch (SW-
II) opens before the Source I high voltage switch clos-
es, to effect a non-parallel return transition. SW-I will
now remain closed and SW-II open until Source I volt-
age is lost or a change is made in the control settings.
Return Transfer, Parallel Transition
When Source I power is restored on all three phases, R2
will pick up and Source I Energized lamp (L1) will light.
Contact 9-6 of R2 closes to energize ALTERNATE TO
PREFERRED TIMER (TM-2) through contact 8-2 of R1,
and deck K of S4. After TM2 times out, its contacts 5-6
close to energize the coil of R1 through diode DL in the
latching direction causing R1 to transfer.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S260-75-1
No Preference Mode
Manual Control
Assume the Source I high-voltage switch (SW-I) is
closed and Source II high-voltage switch is open. With
the SOURCE PREFERENCE and RETURN MODE
switch (S4) in NO PREF-NP (Terminal 4 of S4 connect-
ed), loss of Source I voltage on one or more phases will
open the Source I high-voltage switch (SW-I) as
described in the Automatic Transfer, Preferred to
Alternate section of this discussion.
When the OPERATION SELECTOR switch (S3) is
placed in MANUAL, it connects the MANUAL OPER.
SOURCE I switch (S1) and the MANUAL OPER.
SOURCE II switch (S2) to the transfer bus. Power can
then be supplied to either the close or trip coils of either
SW-I or SW-II. Contacts 3-7 and 2-6 of S3 are opened in
the MANUAL position so that opening of one high-volt-
age transfer switch does not cause automatic closing of
the other. In the manual mode of operation, it is possible
to have both high-voltage switches open, either switch
closed, or both switches closed.
Upon restoration of Source I voltage, R2 is re-ener-
gized. However, due to the positioning of decks G and
H of S4, neither timer can be energized since both the
N.C. contacts 1-7 of R2, and 9-3 of R6 are open (both
relays are energized).
Indicating Lamps
The LAMP TEST switch (S6) is provided for checking the
various incandescent indicators on the front panel of the
S control. In the closed position, all the lamps will be
energized through a diode network to check their condi-
tion.
The S control is now in a quiescent state with SW-II
closed and SW-I open. This condition will continue until
either Source II is lost or a change is made in the control
settings. If Source II is lost, delay in transfer to Source I
will be timed by TM-2.
In the open position, the diode network isolates the
lamps from the test switch so that it has no effect on nor-
mal circuit operation.
Preferred Source II Mode
With the SOURCE PREFERENCE and MODE switch
(S4) in either PREF II-P (Terminal 6 of S4 connected), or
PREF II-NP (Terminal 5 of S4 connected) the description
of operation is similar to the “Automatic Transfer,
Preferred to Alternate” and “Return Transfer, Parallel
Transition” or “Return Transfer, Non-Paralleled
Transition” as previously described except that Source II
is the preferred source (controlled by SW-II) and Source
I is the alternate source (controlled by SW-I).
Control Mode Switch, S5
If S5 is placed in the center-off TEST position, there is no
circuit to either the close or trip coils of either high-volt-
age transfer switch. This position of S5 is used to check
sensing circuitry, timers, and the latching relay without
affecting the status of the high-voltage switches.
If S5 is placed in the HOLD ON ALTERNATE position,
return transfer will not occur after preferred source volt-
age is restored. Assume the S3 is in AUTO, S4 is in
PREF l-P, and the S control is in the quiescent state with
Source I high voltage (SWI) closed and Source II high-
voltage switch (SW-II) open. Upon loss of Source I, R2
will again initiate a transfer of the latching relay R1 as
previously described, followed by the opening of SW-I
and the closing of SW-2. The S control is now in a qui-
escent state in which SW-2 will remain closed and SW-I
will remain open even when Source I power is restored.
When Source I is reenergized, R1 will transfer back to
the latch position and close its contact 9-6. However,
because deck L of S4 is open, power cannot be provided
to the trip coil of SW-II or the close coil of SW-I.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions
TROUBLESHOOTING—BASIC S CONTROL
CAUTION: Equipment misoperation. Do not
Basic Troubleshooting
!
energize this equipment until all control settings
A quick check of the basic transfer operation while the con-
have been properly programmed and verified. Refer to
the Control Programming and Operation section of this
manual for programming procedures. Failure to com-
ply can result in misoperation (unintended operation),
trol is in service can be made using the following procedure:
Source I or Source II Preferred
Operation
equipment damage, and personal injury.
G118.1
1. Set CONTROL MODE switch (S5) to TEST. This wilI
remove the control from service and allow it to operate
without operating the high-voltage transfer switches.
WARNING: Hazardous voltage. Solidly ground
!
all equipment. Failure to comply can result in
2. Check LATCH RELAY STATUS TEST terminals (T-1,
T-2) to ground (T-3). 120 Vac at T-1 indicates the con-
trol is in Source I mode; 120 Vac at T-2 indicates the
control is in Source II mode. Check if this agrees with
the SOURCE PREFERENCE switch setting.
death, severe personal injury, and equipment damage.
T223.2
General
3. Remove preferred source voltage by unscrewing one
of the phase fuses from the applicable source. The
PREFERRED TO ALTERNATE TIMER will start.
This troubleshooting guide is intended to assist in localiz-
ing problems that may be encountered in the operation of
the load-transfer scheme. After the problem area has
been localized, general troubleshooting and circuit tracing
techniques can be used to pinpoint the cause. A funda-
mental understanding of the basic operation is essential
in carrying out these troubleshooting procedures. (See
Theory of Operation section.)
4. When the timer runs out, the latch relay (R1) will
transfer; indicated by a transfer of the 120 Vac signal
at the test terminals.
5. Replace the removed fuse to re-energize the pre-
ferred source. The ALTERNATE TO PREFERRED
TIMER will start.
Schematic diagrams, Figures 16 and 17, are used as
references throughout this guide. The physical location
of the various circuit components and terminals are
identified in Figure 27.
IMPORTANT: If Control Mode Switch S5 is placed in
the “Normal” position, the S-control will place the high-
voltage transfer switches into the configuration that is
currently selected by the Source Preference Switch
S4. This may result in an unintended transfer. Make
sure the desired state of the high-voltage transfer
switches match the setting of S4 before returning S5 to
the “Normal” position.
Remove the Control from Service
DANGER: Hazardous voltage. Contact with haz-
!
ardous voltage will cause death or severe per-
sonal injury. Follow all locally approved safety proce-
dures when working around high and low voltage lines
6. When the timer runs out, the latch relay (R1) will
and equipment.
G103.3
transfer back to its original operating position.
7. Return the CONTROL MODE switch (S5) to NOR-
The following warning only applies to controls
equipped with the Fault Block Accessory:
MAL to return the control to service.
WARNING: Hazardous Voltage. De-energize
!
switchgear before attempting to disconnect con-
trol cable from control. Failure to do so may result in
contact with high voltage pulse (300V peak) from the
CT protection circuit. Failure to de-energize switchgear
can result in contact with high voltage, which will cause
death or severe personal injury.
G124.0
1. De-energize Source I and Source II voltage.
2. Disconnect cables from the control.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S260-75-1
No Preference Operation
Indicating Lamps
Although not essential to control operation, the indicating
lamps provide useful operating information. All lamps are
120 Vac operated half-wave through diodes.
1. Set CONTROL MODE switch S5 to the TEST posi-
tion. This will remove the control from service and
allow operation without operating the high-voltage
transfer switches.
For a quick check of the lamp diodes, depress the LAMP
TEST switch, S6. The two OPEN and two CLOSE lamps
should glow with equal brilliance, the green appearing
slightly less intense, and the SOURCE I ENERGIZED
and SOURCE II ENERGIZED lamps should noticeably
increase in brilliance (these lamps are energized from
two phases, 120 degrees apart, instead of a single bus).
2. Check the setting of the SOURCE PREFERENCE
switch (S4). It should be in the center No Preference
position.
3. Check LATCH RELAY STATUS TEST terminals (T-1,
T-2) to ground (T-3). 120 Vac at T-1 indicates the con-
trol is in the Source I mode. 120 Vac at T-2 indicates
the control is in the Source II mode.
Note: The OPEN lamp circuit includes the impedance of
the close coil or motor of the high-voltage switch
actuator.
4. Remove source voltage by unscrewing one of the
phase fuses from Source I if T-1 is energized or from
Source II if T-2 is energized. If a Source I fuse is
removed, the PREFERRED TO ALTERNATE TIMER
will start. If a Source II fuse is removed, the ALTER-
NATE TO PREFERRED TIMER will start.
Verification of Fuses
Fuses can be checked on the front panel of the control.
If the fuses are blown and require replacement, the white
buttons on the front panel will show. Refer to item 15 in
Figure 13 and Table 4.
5. When the timer runs out, the latch relay (R1) will
transfer as indicated by a transfer of the 120 Vac sig-
nal at the test terminals.
Advanced Troubleshooting
IMPORTANT: The control should be removed from
service prior to conducting the advanced troubleshoot-
ing procedures.
6. Replace the removed fuse to re-energize the power
source. No timers will start and latch relay (R1) will
not transfer.
7. Unscrew one of the phase fuses from the other
source. If a Source II fuse is removed, the ALTER-
NATE TO PREFERRED TIMER will start. If a Source
II phase fuse is removed, the PREFERRED TO
ALTERNATE TIMER will start.
Use the output of the control procedure to determine if
the problem lies in the control or the high-voltage switch-
es. If the conditions of the output procedure are satisfac-
tory, test the high-voltage switch. If the conditions of the
output procedure are unsatisfactory, test the manual con-
trol functions. If the conditions of the manual control func-
tions procedure are satisfactory, test the automatic con-
trol functions.
8. When the timer runs out, the latch relay (R1) will
transfer back to its original operating position, again
indicated by a transfer of the 120 Vac signal at the
test terminals.
9. Replace the removed fuse to re-energize the power
source. No timers will start and latch relay (R1) will
not transfer.
10. Place the CONTROL MODE switch (S5) to the normal
position. If switch S5 is left in the TEST position, the S
control will be inoperative on automatic operation.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions
Output of the Control
TABLE 5
Continuity Check of High-Voltage Switches
To determine if the problem is in the control or the high-
voltage transfer switch, proceed as follows:
Switch
Ohmmeter Reading
Receptacle
Pin
Type VR, VLR, VRV — Standard Operator
1. Disconnect the switches from the control.
Switch Open
Switch Closed
2. Place OPERATION SELECTOR switch (S3) to
MANUAL.
B to C
B to D
B to E
D to F
Motor
∞
∞
∞
0
Trip Coil
3. Place SOURCE PREFERENCE and RETURN
0
0
MODE switch (S4) to NO PREF.
4. With the control energized, check the voltage to
ground at the “Transfer Switch Operators” terminal
board, TB1, per Table 6.
Type VR, VLR, VRV — Quick Close Operator
A to D
B to C
B to D
B to E
D to F
*
∞
Quick Close Coil
∞
∞
∞
0
Trip Coil
5. If these output voltages are obtained, check the high-
voltage switch. If the output voltages are not
obtained, check the manual control functions.
0
0
Type TSC
B to C
B to F
B to E
D to F
Motor
∞
Motor
0
High-Voltage Switch
∞
∞
0
Normal control output at TB1 but failure to operate sug-
gests a malfunctioning switch.
∞
Type PST-6 with C Interrupter #1
1. With an ohmmeter, check the resistance between
E to R
M to N
P to E
S to V
T to U
Close Coil
∞
points of the high-voltage switch actuator per Table 5.
∞
*
0
∞
0
∞
∞
2. If the control circuit of the switch operator checks out,
the trouble may be mechanical. Refer to the mainte-
nance manual for the switch.
Trip Coil
Type PST-6 with C Interrupter #2
B to C
D to E
E to F
G to K
H to J
∞
0
*
∞
Close Coil
∞
∞
0
∞
Trip Coil
Type PST-9 with C Interrupter #1
E to F
A to C
C to E
B to C
C to D
∞
∞
∞
∞
∞
Type PST-9 with C Interrupter #2
L to M
G to J
J to L
H to J
J to K
∞
0
0
∞
∞
*
Trip Coil
∞
∞
Close Coil
* Will read motor resistance if closing spring is not charged, will
read infinity if closing spring is charged.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S260-75-1
Manual Control Functions
Automatic Control Functions
Abnormal output readings at TB1 indicate a malfunctioning
control. This procedure describes the terminal functions
under manual direction and suggests areas for investigation.
The control may operate properly by manual direction but
malfunction in its automatic mode. The automatic section
responds to the positions of R2 and R6 in conjunction
with the selected operating mode as set on S4, the
SOURCE PREFERENCE and RETURN MODE switch.
Its output is the single-coil latching relay, R1.
1. Terminals 11 and 21 provide the power to charge the
springs in the switch actuator and are constantly
energized. If terminals 11 and 21 are not energized,
the transfer bus is not energized.
1. R2 is energized from phase A of Source I through
N.O. contacts of R9 in phase B and R10 in phase C.
The action of R2 can be observed through its trans-
parent cover and can be checked electrically across
tabs 31 and 32 on the relay tie board which connect to
a N.C. contact of the relay.
A. Make sure that either phase B of the preferred
source or phase Y of the alternate source is ener-
gized. These phases supply the transfer bus.
Measure beyond the fuses.
B. Relays R7 and R11 control power to the transfer
bus. Relay R7 picks up when phase Y is ener-
gized; Relay R11 picks up if phase B is energized
and phase Y is deenergized.
2. R6 is similarly energized from phase X of Source II
through R7 in phase Y, and R8 in phase Z. Tabs 41
and 42 connect to a N.C. contact of R6.
3. Operation of the appropriate time delay relay can be
2. Terminals 15 and 25 provide 120 Vac closing power
(15 closes Source I switch, and 25 closes Source II
switch). Terminals 13 and 23 provide 120 Vac open-
ing power (13 opens Source I switch and 23 opens
Source II switch).
checked by verifying that the LED timer is illuminated.
4. The single-coil latching relay (R1) is electrically oper-
ated and magnetically held. It is latched directly from
the 120 Vac transfer bus through diode DL in the auto-
matic mode or diode DL1 in the manual mode. It is
reset through the 15 K ohm resistor and either diodes
DR or DR1.
A. Terminals 13, 23, 15 and 25 are energized from
the transfer bus through the MANUAL OPER.
switches, S1 and S2.
5. With the control in an automatic mode of operation,
the position of the latching relay can be determined at
the Latching Relay Test jacks (T1, T2, T3) on the front
panel of the control.
(1) If the control is equipped with the fault block
accessory, normally closed contacts of the fault
block relay (RY1) are connected between tabs
FP and FR of the relay tie board to complete the
circuit to terminal 15 and between tabs FS and
FT to complete the circuit to terminal 25.
A. When 120 Vac is present between T1 and T3, the
relay is in the “latched” position and the control
seeks to connect the load to Source I.
(2) If the control does not use the fault block
accessory, jumpers are provided between tabs
FP and FR and FS and FT of the relay tie board
to complete the closing power circuits to the
transfer switches.
B. When 120 Vac is present between T2 and T3, the
relay is in the “reset” position and the control seeks
to connect the load to Source II.
C. If the latching relay assumes the expected position
after the proper time delay, the automatic section
of the control is functioning properly.
3. Terminals 14 and 24 are grounded by an “a” contact
(N.O.) in the H.V. transfer switches to energize relays
R4 and R5 respectively during the “opening” half of a
parallel return transfer.
4. Terminals 16 and 26 are energized (120
TABLE 6
Voltage Readings on TB1
Vac) on the “closing” half of a non-parallel
return transfer. They are energized from a
“b” contact (N.C.) in the H.V. transfer switch-
es; 16 is energized from Source I high- volt-
age switch and 26 is energized from Source
II high-voltage switch.
Voltage to Ground
MANUAL OPER.
SOURCE I
MANUAL OPER.
SOURCE II
Term
on
Switch (S1)
Switch (S2)
TB1
Quiescent
Close
Open
Close
Open
11
15
14
13
16
120 Vac
170 Vdc*
170 Vdc*
0
120 Vac
120 Vac
120 Vac
120 Vac
120 Vac 170 Vdc* 170 Vdc* 170 Vdc*
170 Vdc* 170 Vdc* 170 Vdc* 170 Vdc*
0
0
120 Vac
0
0
0
0
0
0
26
23
24
25
21
0
0
0
0
0
0
0
0
0
120 Vac
170 Vdc*
170 Vdc*
120 Vac
170 Vdc* 170 Vdc* 170 Vdc* 170 Vdc*
170 Vdc* 170 Vdc* 120 Vac 170 Vdc*
120 Vac
120 Vac
120 Vac
120 Vac
* Rectified 120 Vac impressed on capacitor. Drops to 0 if LAMP TEST
switch (S6) is depressed.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
!
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions
SAFETY
FOR LIFE
Figure 16a.
Schematic diagram basic S control operating Types VR, VLR, VRV, TSC, or PST-9 switchgear (page 1 of 2).
24
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S260-75-1
Figure 16b.
Schematic diagram basic S control operating Types VR, VLR, VRV, TSC, or PST-9 switchgear (page 2 of 2).
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions
Figure 17a.
Schematic diagram for Type S control operating Type PST-6 switchgear (page 1 of 2).
26
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S260-75-1
Figure 17a.
Schematic diagram for Type S control operating Type PST-6 switchgear (page 2 of 2).
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions
FAULT BLOCK ACCESSORY
(Applicable to VR, VLR, VRV, TSC, CS, and PST-6 switchgear.)
The fault block accessory is mounted in the upper right
corner of the back panel of the control, Figure 18. Controls
and instructions for operating the accessory are located
on the front panel above the input fuses, Figure 19.
To prevent the fault block accessory from being activated
due to inrush current that may occur as a result of the
backup opening and closing, an inrush restraint feature is
built into the accessory logic. Upon loss of the preferred
source voltage, the inrush restraint operates to increase
the phase fault actuating level by a predetermined multi-
ple for a predetermined time after voltage is restored.
Simultaneously, ground fault current detection is blocked
completely for the same time interval. When the time runs
out, both the phase and ground current actuating levels
return to their normal values.
General Description
In response to fault current above preselected phase or
ground levels, the accessory is activated and latched to
disable both high-voltage switches. Thus a load-side fault
followed by loss of potential will result in partial load
transfer opening the connected source but not closing
the faulted load into the alternate feeder.
To operate the fault block accessory, the Source I and
Source II high-voltage switches must be equipped with
1000:1 ratio current transformers to monitor the magni-
tude of the line current and an auxiliary “a” contact. The
bushing current transformers and associated wiring are
provided as a factory-installed accessory to the high-volt-
age switch.
The accessory must be manually reset at the control
panel to restore service to the load. If activation of the
fault block accessory is due to a temporary fault (pre-
ferred source voltage is restored before the transfer delay
timer runs out), line current of 5 Amps, or more, flowing
through the high-voltage switch will automatically reset
the accessory in approximately 10 to 15 seconds.
Accessory Settings
The selected phase and ground fault
ACTUATING LEVEL PRINTED
CIRCUIT CARD (FIGURE 18)
actuating levels should be greater
than any peak load phase current or
zero-sequence (ground) current, but
less than the trip setting of the back-
up protective device. A general rec-
ommendation is to set the phase
and ground actuating levels to
approximately 80% of the phase and
ground trip levels of the backup.
TERMINAL BLOCK FOR
EXTERNAL CONNECTIONS
The phase fault current minimum
actuating level is determined by a
plug-in circuit card, Figure 20.
Cards are available for 80, 112,
160, 224, 320 and 448 Amp actuat-
ing levels. The ground fault current
minimum actuating level is deter-
mined by a resistor cartridge that
clips on to the phase card.
Cartridges are available for 10, 14,
20, 28, 40, 56, 80, 112, 160, 224,
320 and 448 Amp actuating levels.
RAISED FAULT LEVEL
DURATION TIMER
020080KM
Figure 18.
Fault block accessory mounted in upper-right corner of the back panel.
INSTRUCTION LABEL
Provides instructions
for resetting the
fault block accessory.
FAULT BLOCK
RESET SWITCH (S7)
Reactivates the S control
after a fault block operation.
OPERATED SWITCH
Indicates that the fault block
accessory has operated.
020077KM
Figure 19.
Fault block accessory controls and operating instructions plate.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S260-75-1
The actuating level multiplier for the inrush restraint fea-
ture for phase faults is set by a jumper wire connected
to a tab on the circuit card. Tabs are provided for X1, X2,
X4, X6, X8 and BLOCK settings. The duration of the
raised level is set by a knob on the top of the timer
(Figure 18). The timer is infinitely adjustable 0.1 to 5.0
seconds. No settings are required for ground inrush
since it is automatically blocked for the duration the
phase level is raised.
Theory of Operation
—Fault Block Accessory
The fault block accessory prevents automatic closure
into the alternate source when loss of preferred source
results from a fault on the load tap. The schematic dia-
gram for the fault block accessory, Figure 21, is used as
reference throughout this discussion.
Overcurrent Sensing
Operating Instructions
The output of bushing current transformers in both the
Source I and Source II high voltage switches are applied
to the fault block accessory via terminals lA, IB, IC, IN
and IX, IY, IZ, IN respectively. When the load current
through the switch exceeds the phase or ground actuat-
ing level selected, the relay contacts in the fault block
accessory (contacts 7-8 and 10-11 of relay RY1-B),
located in the closing circuits of both high voltage switch-
es, are opened. Subsequent closing of either switch is
blocked in either the automatic or manual mode of the S
control until the fault block accessory circuitry is reset.
The FAULT BLOCK OPERATED lamp on the front panel
of the control, Figure 19, will light when the fault block
accessory is activated. To reset the accessory:
1. Move the OPERATION SELECTOR switch (S3) to
MANUAL.
2. Depress and hold the RESET switch (S7) until the
lamp goes out, (approximately 6-10 seconds) indicat-
ing the accessory has reset.
3. To restore service, return the OPERATION SELEC-
TOR switch (S3) to AUTOMATIC; the preferred
source high voltage switch will close.
Phase Fault Operation
Referring to the accessory schematic diagram, Figure
21, the phase currents are rectified by the diode bridges
D103 through D116. Current out of the positive side of
the bridge passes through diode D127 and divides into
two parallel circuits. One circuit consists of zener D123
and the minimum phase actuating resistor R301 to the
other side of the bridge. The other circuit consists of nor-
mally closed contact (1516) of latching relay RY1, diode
D201, and capacitor C201 to the other side of the bridge.
C201, charged by load or fault current, provides tripping
energy for RY1.
OR
Operate either the MANUAL OPER. SOURCE I switch
(S1) or the MANUAL OPER. SOURCE II Switch (S2),
as applicable, to restore service manually.
Note: Instructions for operating the fault block accessory
also are printed on the front panel of the control
(Figure 19).
The current through R301 produces a voltage drop pro-
portional to the line current which is impressed across
the series resistor string R101, R102, and R103. A por-
tion of this voltage is applied through diode D120 to the
base of transistor Q201.
When this voltage exceeds the break-down voltage of
zener D212 and the base emitter junctions of Q201 and
Q202, Q201 will conduct causing Q204 to conduct. In
turn, Q204 provides the gating current to turn on the SCR
(Q206) to discharge capacitor C201 through the trip coil
of the latching relay RY1. Contacts 10-11 and 7-8 of RY1
(in series with the close coils of the high voltage switch-
es) open to prevent the high voltage switches from clos-
ing until the fault block circuitry is reset.
PHASE CURRENT LEVEL
MULTIPLIER SETTING FOR
INRUSH CURRENT RESTRAINT.
An important feature of this accessory is that a trip signal
cannot be initiated until there is sufficient charge on C201
to activate the trip coil of RY1. Transistors Q201 and
Q204, effectively in series across C201, cannot conduct
until the voltage across C201 is sufficient to break-down
zener diodes D211 and D212.
GROUND-
ACTUATING
CURRENT
RESISTOR
CLIPS TO THE
PHASE CARD
020078KM
Figure 20.
Phase fault current actuating level printed circuit card.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions
SOURCE I
H.V. SWITCH
AØ
BØ
CØ
AØ
BØ
CØ
SOURCE II
H.V. SWITCH
PART OF
RESISTOR BOARD
+
GROUND ACTUATING
RESISTOR
R306
a2
SOURCE II
H.V. SWITCH
a1
SOURCE I
H.V. SWITCH
Figure 21a.
Schematic diagram – fault block accessory (page 1 of 2).
30
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S260-75-1
MANUAL
12
S3
8
V103
4
AUTO
11
M
D26
RY1
(120V BUS)
TRIP RESET BOARD
14
12
RY1
D201
15
17
16
F
D
N
FN
TB4-1
1
D203
B
E
18
1
R209
47K
+
R216
47K
L7
C201
150
RY1
TRIP
COIL
R210
1K
2
TB4-2
2
Q204
2N2905
D
H
D202
C210
0.1
D201
D211
6.8V
1N4736A
+
2
C203
5.6
R204
10K
Q201
TB4-3
R211
100K
Q206
C5V
R218
1K
120V IN MANUAL
Q202
3
C208
0.1
200V
1
3
5
TB4-4
4
D209
+
S7
RESET
3PST
2
D212
5.1V
C204
3.0
+
C207
1.0
35V
R203
3.3K
R208
3.9K
1N4733A
MOMENTARY
TM1-2
TM1-3
V
A
R214
56K
4
C205
0.1
R213
1.8K
R205
100
R212
3.3MEG
C206
12
+
Q203
TM2-2
TM2-3
Q205
2N6119
Y
W
L
1
6
C209
0.1
200V
D208
R217
47K
RY1
RESET
COIL
C202
150
R215
47K
R206
68K
R207
680K
+
D207
T
19
R202
470
D206
D204
FG
G
R201
6.8K-2W
D205
RY1
RY1
RY1
LEGEND
4
3
5
7
8
10
11
ACCESSORY TERMINAL BLOCK (TB5)
ACCESSORY TIEBOARD TERMINAL
RELAY PIN (RY1 & RY2)
V
W
U
T
R
S
P
NO CONNECTIONS
EDGE CONNECTOR TERMINAL
(DIODE BOARD)
FT
FS
FR
FP
(RESISTOR BOARD)
(TRIP-RESET BOARD)
TAB ON RELAY BOARD OF S CONTROL
NOTE
LATCH RELAY CONTACTS (RY1) SHOWN WITH
RESET COIL LAST ENERGIZED
UNLESS OTHERWISE NOTED:
DIODES ARE 1N4004
TB4 TERMINAL STRIP OF S CONTROL
S3 & S7 TERMINALS
TRANSISTORS ARE 2N2102
RESISTORS ARE 1/2 WATT
RESISTOR VALUES ARE IN OHMS
CAPACITOR VALUES ARE IN MICRO-FARADS
TM1 (PREFERRED TO ALTERNATE TIMER) AND
TM2 (ALTERNATE TO PREFERRED TIMER) TERMINALS
Figure 21b.
Schematic diagram – fault block accessory (page 2 of 2).
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions
Ground Fault Operation
Inrush Restraint Feature
The ground current (the vector sum of the phase cur-
rents) flows through the ground actuating resistor, R306,
to produce a voltage across the primary of input trans-
former TR1, proportional to the ground current. This volt-
age is stepped-up, rectified, and impressed across the
series resistor string R104, R105, R106 and R107. A por-
tion of this voltage is applied to the base of Q201 through
diode D119. From this point, ground and phase opera-
tions use common circuitry described in the preceding
“Phase Fault operation” discussion.
The inrush restraint feature raises the actuating level of
the fault block accessory by a multiple (or blocks its oper-
ation entirely) for a period following restoration of source
voltage or an automatic open transition transfer operation,
to prevent inrush currents from activating the fault block.
Relay RY2 is normally energized by the phase B or
phase Y voltages from the S control via the “a” auxiliary
contacts in the two high-voltage switches. When both B
and Y phase voltages are lost due to operation of a back-
up device or opening of the high-voltage switches, the
coil of RY2 is de-energized, closing its contacts. Contact
1-4 closes to insert a paralleling resistor across the
phase actuating resistor R301, reducing its effective
value and increasing the line current necessary to actu-
ate Q201. Contact 5-8 of RY2 closes to short-out the sec-
ondary of TR1, rendering the ground section operative.
Reset Circuits
Once actuated, the fault block accessory can be reset in
either of two ways.
• Manually—Actuating the Reset Switch, S7, on the
front panel of the S control, will apply 120 Vac to ter-
minal G of the fault block accessory tie board. This
voltage is rectified by diode D205 and applied to the
reset timing circuit, which consists of R201, C206,
and the programmable uni-junction (PUT) Q205. This
voltage is also applied to capacitor C202, which pro-
vides energy to the reset coil of latching relay RY1.
When the voltage across C206 reaches the break-
down voltage of the PUT, transistor Q203 is then
turned on causing C202 to discharge through the
reset coil of RY1. The relay transfers and the fault
block accessory is now reset.
Upon re-energization of either Phase B or Phase Y
through closing of the backup devices or the closing of the
high-voltage transfer switches, relay RY2 is energized.
RY2 has a built-in time delay programmable by means of
a knob in the top of the relay case. After the selected time
delay has elapsed, N.C. contacts 1-4 and 5-6 open,
returning the fauIt block accessory to normal operation.
Note: S7 is energized only when the Operation Selector
switch is in MANUAL.
• Automatically—by load current
below the minimum actuating
level flowing through the high-
voltage switch. The voltage
developed by the load current is
applied through contact 16-17 of
RY1 to the reset timing circuit
R207, C206, and Q205.When
the voltage across C206 reach-
es the breakdown voltage of the
PUT, Q203 is then turned on
causing C202 to discharge
through the reset coil of RY1.
The latching relay transfers and
the fault block accessory is
reset.
Note: If the load current is above
the actuating level of the
accessory, both manual and
automatic reset is defeated
by Q202 which conducts to
short-out the reset timing
capacitor C206 through
resistor R205.
Figure 22.
Test circuit for testing and troubleshooting the fault block accessory.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S260-75-1
Test Procedure and Troubleshooting
Phase Minimum Actuating Current
Testing Fault Block Operation
WARNING: Hazardous voltage caused by back-
!
feeding transformers. Isolate potential transform-
IMPORTANT: When checking the phase minimum
actuating current the ground fault sensing portion of
the accessory must be disabled. Testing on an individ-
ual phase basis without disabling ground fault sensing
will cause the accessory to activate at the ground fault
level.
ers from source bushings using potential transformer
dead-break disconnect switches located on the
source-side panel. Failure to do so will result in risk of
possible contact with high voltage at the source bush-
ings, which may cause death or severe personal injury.
T273.0
1. Disable the ground sensing circuit by shorting the
The operation of the fault block accessory can be
checked by backfeeding a 500:5 (or other available ratio)
current transformer, located in the primary loop of one
phase of the preferred source high-voltage switch, from a
variable 120 Vac source. The 500:5 ratio provides approx-
imately 1 Amp of output test current for every 10 mA of
input current. However, to eliminate error due to CT satu-
ration, a separate metering CT and meter should be used
to read the actual test current.
ground fault resistor (Figure 22).
2. Set the inrush current multiplier at X1.
3. Close test circuit switches SW2 and SW3 to apply
voltage to the control.
The preferred source high-voltage switch (HV1) will
close.
4. Close test switch SW1 and slowly raise the test current
until the FAULT BLOCK OPERATED light goes on.
Test Circuit and Equipment
The test current should be within the limits specified in
Table 7. If FAULT BLOCK OPERATED light fails to come
on at the expected level, proceed as follows:
A suggested test setup is shown in Figure 22. If the con-
trol is equipped with the plug and receptacle accessory,
use the existing cables to interconnect the motor opera-
tors of both high-voltage switches and the CT sensing
circuits of the preferred source switch to the S control. If
plugs and receptacles are not provided, wire the switch-
es directly to the appropriate terminal blocks as shown in
Figures 6 or 8.
A. Check lamp with LAMP TEST switch (S6).
B. Recheck calculations for proper meter reading.
C. Is ground resistor cleanly shorted out?
D. Did latch relay R1 transfer position?—lamp is only
an outward indication of relay position.
E. Are all cable connections secure?
F. Voltage from Accessory Tie Board, Tab D to
Ground, Tab L, should be approximately 15 Vdc,
average, at actuating level. If observed voltage is
approximately 6 volts too low, trouble is probably in
the Trip Reset Board; if voltage is too high, trouble
is probably in either Diode or Resistor Boards.
G. AC rms voltage from “IN” to “IA” (or whatever
phase is energized) should be about 17 V at actu-
ating level. If correct voltage is observed, the CT
input is correct.
TABLE 7
Test Current Values for Fault Block Accessory
Actuating
Current
Setting
Actuating Current Limits
(Amps)
(Amps)
Minimum
Maximum
020082KM
10
14
20
9
12.6
18
11
15.4
22
Figure 23.
Disabling ground sensing circuit.
28
40
56
25.2
36
50.4
50.8
44
61.6
80
112
160
72
101
144
88
123
176
274
320
448
247
250
403
301
352
493
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions
5. Open SW1 and SW2 to simulate a backup clearing
10. Repeat step 8 and 9 for the other high-voltage switch
the fault.
to complete checking all six CTs, their connections
and polarity.
The PREFERRED TO ALTERNATE TIMER will start
and the preferred source high-voltage switch (HV1)
will open when the timer runs out, but the alternate
source high-voltage switch (HV2) will not close.
11. Remove the shorting jumper from the ground fault
resistor upon completion of phase testing.
Ground Minimum Actuating Current
If alternate source switch (HV2) closes and the latch
relay (R1) contacts are not opening, check for open
contact between Accessory Tie Board tabs P and R
(Source I HV switch) and tabs S and T (Source II HV
switch).
When checking the ground minimum actuating current,
the phase fault sensing portion of the accessory circuit
must be disabled to prevent the possibility of erroneous
test results. Proceed as follows:
1. Disable the phase sensing circuit by placing a short-
ing jumper from the BLOCK tab on the phase resistor
card to tab L on the accessory tie-board (Figure 26).
6. Place OPERATION SELECTOR SWITCH (S3) to
manual, and operate MANUAL OPER SOURCE I
switch (S1) and MANUAL OPER SOURCE II switch
(S2) to CLOSE.
2. Repeat steps 2 through 7 of the Phase Minimum
Actuating Current test procedure.
HV switch (HV1 or HV2) will not close.
Automatic Reset of Fault Block
If either switch closes and the latch relay (R1) con-
tacts are not opening, check for open contact
between Accessory Tie Board tabs P and R (Source
I HV switch) and tabs S and T (Source II HV switch).
1. Close test switches SW2 and SW3 to supply voltage
to the control.
The preferred source high-voltage switch (HV1) will
close.
7. Close test switch SW2 to restore preferred source
voltage to the control. After the ALTERNATE TO
PREFERRED TIMER runs out, reset the fault block
accessory per instructions on the front panel.
2. Close SW1 and raise the test current until the FAULT
BLOCK OPERATED lamp lights indicating that fault
block has been activated.
The FAULT BLOCK OPERATED light will go out and
the preferred source high-voltage switch will close.
3. Open SW2 to simulate the back-up device opening
and simultaneously open SW1 to clear the fault.
If the FAULT BLOCK OPERATED light does not go
out, the problem is most likely in the TRIP RESET
BOARD.
The PREFERRED TO ALTERNATE TIMER will start
to run.
4. Close SW2 to simulate reclosing of Source 1 back-
up device. Quickly close SW1 and raise the test cur-
rent to greater than 5 Amps but less than ground
actuating level.
Follow steps 8 through 11 to conduct a complete check
involving all the phases of both high-voltage switches.
8. Connect the phases in series as shown in Figure 24
The FAULT BLOCK OPERATED lamp will go out in
about 10-15 seconds indicating the accessory has
reset.
and retest.
Because of the series hook-up, pickup should occur
at 1/2 the actuating current setting.
If FAULT BLOCK OPERATED lamp does not go out,
the trouble is most likely in the Trip-Reset board
(assuming the previous tests had passed).
If pickup current is other than 1/2 of setting, the polar-
ity of a CT could be reversed.
9. Connect another two phases in series as shown in
Figure 25 and retest.
Results should be the same as in preceding step 8.
JUMPER
A
A
JUMPER
Figure 24.
Test Connections for Step 8.
Figure 25.
Test Connections for Step 9.
34
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S260-75-1
Inrush Restraint
If FAULT BLOCK OPERATED lamp does not light
immediately, then
The inrush-restraint feature prevents inrush currents
above the minimum actuating level from actuating the
accessory. This is accomplished by raising the phase
actuating level by some multiple for a predetermined time
after service is restored. Ground actuating level detection
is blocked for the duration of the raised phase actuating
level. Proceed as follows:
A. Recalculate expected current.
B. Verify that jumper on resistor board is on correct
tab.
If FAULT BLOCK OPERATED lamp still does not
light immediately, the resistor board may be defec-
tive. Contact your Cooper Power Systems represen-
tative.
1. Disable the ground sensing circuit by shorting the
ground fault resistor (Figure 26).
13. Remove the shorting jumper from the ground fault
2. Set the inrush-restraining multiplier on the phase actu-
ating card and the raised fault-level duration on the
timer to the values at which they are to be checked.
actuating cartridge upon completion of the test.
3. With the preferred source high-voltage switch (HV1)
closed, close test switch SW1 and raise the equiva-
lent test current to a value above the maximum actu-
ating level for the setting, but below the multiplied set-
ting. (See Table 7 for maximum current test values.)
“BLOCK” TAB
4. Without disturbing this current setting, open SW1.
5. Close test circuit switches SW2 and SW3 to apply
voltage to the control.
6. Momentarily close and open SW1 before the raised
duration timer runs out, to simulate an inrush current.
The FAULT BLOCK OPERATED lamp will not light.
If the FAULT BLOCK OPERATED lamp does light,
proceed as follows:
A. Recheck current calculations. (Test current should
“L” TAB
exceed actuation level but be less than inrush level.)
020083KM
Figure 26.
Disabling phase sensing.
B. Check if momentary faults were applied before
timer elapsed.
Return the Control to Service
C. Check if timing relay picked up after either HV1 or
HV2 was closed. Check presence or absence of 120
Vac at Accessory Tie Board terminal 17 when HV1
operates and terminal 28 when HV2 operates.
CAUTION: Equipment misoperation. Do not
!
energize this equipment until all control settings
have been properly programmed and verified. Refer to
the Control Programming and Operation section of this
manual for programming procedures. Failure to com-
ply can result in misoperation (unintended operation),
D. Check for trouble in delay relay contacts or resis-
tor board.
7. Close SW1 and leave closed to simulate a perma-
equipment damage, and personal injury.
G118.1
nent fault on the load side.
The FAULT BLOCK OPERATED lamp will light after
the raised duration timer runs out.
CAUTION: Equipment misoperation. Source I and
Source II high voltage switches can be paralleled in the
manual operation mode even if SOURCE PREFER-
ENCE switch, S4, is set for NP (non-parallel opera-
tion). Make sure both sources are in synchronism if a
manual parallel operation is to be performed. Failure to
comply can result in misoperation (unintended opera-
If FAULT BLOCK OPERATED lamp does not light,
the problems are similar to step 6 above.
8. Open switches SW2 and SW3 to remove voltage
from the accessory.
9. Raise the test current to a value just above the raised
tion) and equipment damage.
T304.0
multiple value.
10. Without disturbing this current setting, open SW1.
1. The control must be programmed with all the neces-
sary operating settings and verified by the appropri-
ate personnel prior to operation with energized
switchgear.
11. Again close switches SW2 and SW3 to apply voltage
to the control.
12. Close SW1 to simulate a high-level fault on the load
2. Verify status of high voltage switches according to
side of the switch.
system requirements.
The FAULT BLOCK OPERATED lamp will light imme-
diately indicating the fault is greater than the inrush
current restraining setting.
3. Reconnect cables and ground the control.
4. Apply Source I and Source II voltage to the control.
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions
WIRING TABLES
Tables 21 through 40 identify the
point-to-point wiring between
circuit components.
Tables 36–40 apply to S Controls
with the Fault Block Accessory.
The physical location of the cir-
cuit components and their termi-
nals identification are shown in
Figure 27.
Figure 27.
Location of circuit components wiring terminal identification.
36
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S260-75-1
TABLE 8
TABLE 10
TABLE 12
“A”
Surge Protector Circuit Board
TB1
Output Terminal Block
TB3
Terminal Strip
To
From
To
Color
BRN
ORG
GRN
WHT
From
To
Color
From
1
Color
Motor Lead
YEL
Motor Lead
WHT
Motor Lead
GRY
A
B
C
G
FU-A-1
FU-B-1
FU-C-1
Stud on
Cabinet
TB1-G2
Screw on
Back Panel
TB1-G1
TB2-G2
WHT
WHT
TM2-8
S6-4
TM2-7
S4(K-8)
TM1-7
S4(J-4)
TM1-8
S6-4
G1
G2
2
3
4
WHT
WHT
R-1
TB1-21
A-11
BLK
BLK
BRN
X
Y
Z
11
13
14
FU-X-1
FU-Y-1
FU-Z-1
TB1-11
TB1-13
VIO
WHT
BRN/WHT
BRN
11
Motor Lead
GRN
S1-3
A-13
R-47
S4(F-C)
A-14
BLK
YEL
BLK
RED
ORG
13
14
TABLE 13
YEL
ORG
ORG
TB1-14
RA(B-7)*
TB4
Terminal Strip
R-FR
D-15
A-15
S3-2
A-16
TB1-11
A-21
S2-3
A-23
BLU
BLU
RED
YEL
GRN
BLK
BLK
WHT
VIO
BRN
GRY
15
16
21
23
24
TB1-15
TB1-16
TB1-21
TB1-23
TB1-24
RA(A-7)*
RED
GRN
BLK
VIO
GRY
GRY
From
To
Color
15
16
21
23
24
D-L7
R-FN
L7-1*
T3
L7-2*
S3-8*
S1-2
S7-1*
R-FG
S7-2*
ORG
GRN
BRN
BRN
RED
ORG
BRN
BRN
YEL
RED
1
2
3
4
25
26
TB1-25
TB1-26
WHT
BLU
S4(E-C)
A-24
R-FT
A-25
D-25
S3-3
A-26
GRN
WHT
GRN
ORG
BLU
TABLE 9
25
26
*Fault Block Accessory Connections
“D”
Diodes Circuit Board
TABLE 14
From
I
II
G
To
S6-1
S6-10
S6-7
L3-2
L4-2
Color
RED
BRN
BRN
BRN
RED
ORG
YEL
ORG
RED
YEL
FU-A
Source I – Phase A Fuse
TABLE 11
From
1
To
A-A
TB2-A
Color
BRN
RED
TB2
L3
L4
L5
L6
L7
11
14
15
24
25
Input Terminal Block
2
R-A
BRN
From
To
Color
L5-2
L6-2
A
B
C
FU-A-1
FU-B-1
FU-C-1
RED
YEL
BLU
TB4-1
S6-5
S4(F-C)
TB1-15
S4(E-C)
TB1-25
TABLE 15
FU-B
G1
C-2
TB2-G2
WHT
WHT
Source I – Phase B Fuse
BLU
GRN
GRN
From
1
To
A-B
TB2-B
Color
ORG
YEL
G2
TB1-G2
TB2-G1
WHT
WHT
X
Y
Z
FU-X-1
FU-Y-1
FU-Z-1
GRY
BLK
RED/WHT
2
R-B
RED
TABLE 16
FU-C
Source I – Phase C Fuse
From
To
Color
1
A-C
TB2-C
GRN
BLU
2
R-C
ORG
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions
TABLE 22
TABLE 23
TABLE 17
“R”
S5
CONTROL MODE Switch
FU-X
Source II – Phase X Fuse
Relay Tie Board
From
A
B
To
FU-A-2
FU-B-2
TB-5-18*
FU-C-2
S4(B-8)
TB2(G-1)
T-3
FB-L*
Color
BRN
RED
BRN
ORG
ORG
WHT
ORG
RED
GRY
BLU
RED
BLU
RED
YEL
YEL
VIO
VIO
YEL
GRN
RED
BLU
YEL
BRN
GRN
YEL
BRN
BLK
GRN
BLU
BLK
BLU
GRN
BLK
VIO
From
To
S4(L-6)
S4(M-8)
R-4
T-2
T-1
Color
From
To
Color
1
2
3
4
5
6
RED
GRN
RED
ORG
RED
BRN
1
A-X
TB2-X
VIO
GRY
2
R-X
YEL
C
D
TABLE 18
G
R-5
FU-Y
Source II – Phase Y Fuse
J
K
L
L1
M
P
S4(F-12)
S4(D-8)
TM1-3
TABLE 24
From
To
Color
1
A-Y
TB2-Y
WHT
BLK
S6
LAMP TEST Switch
S1-4
2
R-Y
GRN
From
To
D-I
L1-1
R-I
Color
RED
BRN
S4(D-12)
S4(B-12)
TM1-6
S2-4
S4(E-2)
FU-X-2
FU-Y-2
TB5-27*
FU-Z-2
TB4-4
FB-G*
TB4-1
FB-N*
S4(A-C)
R-FR**
FB-P*
TB1-15
R-FP**
FB-R
S4(C-C)
R-FT**
FB-S*
1
2
3
R
TABLE 19
BRN/WHT
R1
W
X
FU-Z
T-3
TB3-4
TB3-1
ORG
GRN
YEL
Source II – Phase Z Fuse
4
From
To
Color
Y
1
A-Z
TB2-Z
BRN/WHT
RED/WHT
5
6
D-11
–
RED
–
Z
FG
2
R-Z
BLU
7
8
9
D-G
SW3-5
–
BRN
BLU
–
FN
FP
FR
FS
FT
TABLE 20
10
11
12
D-II
L2-1
R-II
BRN
RED
GRY
TM1
PREFERRED TO ALTERNATE TIMER
From
To
Color
1
R-33
TM2-6
ORG
ORG
TABLE 25
L1
2
3
TB3-4
R-R
TM2-8
BLK
YEL
YEL
SOURCE I ENERGIZED Lamp
From
1
2
To
S6-2
L2-2
Color
BRN
ORG
4
5
–
–
–
–
TB1-25
R-FS**
FB-T*
GRN
BLK
GRY
R-43
TM2-1
S7-8*
BRN
BRN
BLU
J1
J2
J3
J4
I
II
4
Used with
6
7
8
TABLE 26
capacitor
voltage sensing
accessory
L2
TB3-3
BLK
SOURCE II ENERGIZED Lamp
TB2-3
R-L
S7-7*
RED
RED
GRN
S6-3
S6-12
S5-3
S5-6
S3-5
TB1-11
FB-M*
L3-1
BRN/WHT
From
To
Color
GRY
RED
BRN
RED
BLK
ORG
VIO
BRN
BLK
WHT
ORG
ORG
GRN
1
2
R-II
L1-2
T3
GRY
ORG
YEL
5
* Fault Block Accessory Connections
11
TABLE 21
TABLE 27
12
22
31
32
33
34
35
41
42
43
44
45
47
48
TM2
L3
S3-1
ALTERNATE TO PREFERRED TIMER
SWITCH I OPEN Lamp
S4(G-6)
S4(G-2)
TM1-5
S4(J-C)
S4(L-C)
S4(H-8) BRN/WHT
S4(H-12) RED/WHT
TM1-2
S4(K-C)
S4(M-C)
TB1-13
S4(C-6)
From
To
TM1–6
TB3-1
TM1-8
–
Color
BRN
BLK
RED
–
From
To
Color
1
2
3
4
5
6
1
R-12
L4-1
VIO
VIO
2
D-L3
BRN
TABLE 28
–
–
BRN
YEL
BLU
BLK
GRY
L4
TM1-1
S7-4*
ORG
ORG
SWITCH I CLOSED Lamp
From
To
Color
7
8
TB3-2
TM1-3
S7-5*
BLK
YEL
YEL
1
L5-1
L3-1
VIO
VIO
* Fault Block Accessory Connections
** Omit jumpers if fault block included.
2
D-L4
RED
* Fault Block Accessory Connections
38
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S260-75-1
TABLE 29
TABLE 30
S4
L5
SWITCH II OPEN Lamp
SOURCE PREFERENCE & RETURN MODE Switch
From
A-C
To
Color
BRN
BRN
VIO
From
G-4
G-5
G-6
H-C
To
R-32
R-31
Color
WHT
BLK
From
1
To
L6-1
L4-1
Color
VIO
VIO
R-FP
S1-1
R-38
A-2
A-3
A-4
A-5
A-6
B-C
B-8
B-9
B-10
B-11
B-12
C-C
2
D-L5
ORG
S3-5
S4(G-C)
R-41
VIO
Bare
BRN/WHT
TABLE 31
H-8
H-9
H-10
H-11
H-12
J-C
J-2
J-3
J-4
L6
SWITCH II CLOSED Lamp
From
1
2
S1-3
R-D
ORG
ORG
To
L5-1
D-L6
Color
VIO
YEL
R-42
RED/WHT
R-34
S4(K-12)
ORG
Bare
R-P
R-FS
S2-1
YEL
GRN
YEL
TABLE 32
S4(K-12)
TB3-3
S4(K-10)
Bare
GRY
Bare
S1
MANUAL OPER. SOURCE I Switch
C-2
C-3
J-5
J-6
From
To
Color
1
S3-7
VIO
C-4
C-5
C-6
D-C
D-8
K-C
K-8
K-9
K-10
K-11
K-12
L-C
L-2
L-3
L-4
L-5
L-6
R-44
TB3-2
YEL
WHT
S4(A-C)
BRN
S2-2
TB4-3
S1-5
TB1-13
S4(B-C)
R-L1
S2-6
S1-2
S2-4
RED
BRN
Bare
BLK
ORG
BLU
YEL
Bare
YEL
R-48
S2-3
R-K
GRY
BLU
BLU
2
3
4
S4(J-6)
S4(J-2)
Bare
Bare
D-9
D-10
D-11
D-12
E-C
R-M
RED
R-35
–
–
GRN
–
–
5
6
D-24
TB1-24
R-W
D-14
TB1-14
R-J
GRN
BRN
VIO
YEL
RED
GRY
Bare
WHT
S5-1
RED
E-2
F-C
M-C
R-45
T-2
BLU
BRN
TABLE 33
T1-T2-T3
F-12
G-C
G-2
G-3
M-8
M-9
M-10
LATCH RELAY STATUS TEST Terminal
From
T1
S4(H-C)
R-32
S5-2
GRN
To
S4(L-C)
S5-5
Color
RED
RED
T2
T3
S4(M-C)
S5-4
L2-2
S6-4
TB4-2
R-G
BRN
ORG
YEL
ORG
BRN
ORG
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions
TABLE 38
TABLE 34
TABLE 36
“TB5”
S2
MANUAL OPER. SOURCE II Switch
“FB”
Fault Block Accessory Tie Board
Fault Block Accessory
Terminal Block
From
To
Color
From
IA
IB
IC
IX
IY
IZ
G
To
Color
BRN
RED
ORG
YEL
GRN
BLU
BRN
BLK
VIO
–
From
To
FB-17
RA(A-1)
R-B
RA(A-6)
FB-IA
FB-IB
FB-IC
FB-IN
IN2
Color
1
S4(C-C)
S3-6
YEL
BLU
TB5-IA
TB5-IB
TB5-IC
TB5-IX
TB5-IY
TB5-IZ
R-FG
S3-12
TB5-IN
–
17
GRY
GRN
S1-2
S2-5
S3-9
TB1-23
S4(D-C)
RED
Bare
GRN
WHT
BLU
18
BRN
BRN
2
3
4
IA
IB
IC
BRN
RED
ORG
R-R1
S1-6
VIO
YEL
D
IN1
VIO
BLK
5
6
S2-2
S1-4
Bare
YEL
IN
W
U
IN2
IX
IY
IN1
BLK
YEL
GRN
BLU
FB-IX
FB-IY
FB-IZ
R-Y
RA(B-6)
–
–
TABLE 35
S
P
R-FS
R-FP
VIO
GRN
IZ
S3
27
RED
RED
OPERATION SELECTOR SWITCH
M
R-11
RA(A-2)
ORG
BLK
From
To
R-22
TB1-16
TB1-26
–
Color
BRN
YEL
ORG
–
28
FB-28
RA(B-1)
WHT
WHT
17
28
V
TB5-17
TB5-28
–
GRY
WHT
–
1
2
3
4
TABLE 39
T
R-FT
R-FR
R-FN
R-G
GRY
BLU
YEL
RED
R
N
L
S7
R-11
S4(H-C)
S6-8
RED
VIO
BLU
Fault Block RESET Switch
5
From
To
Color
BRN
RED
ORG
YEL
6
7
8
S2-1
S1-1
TB4-2*
S2-2
–
BLU
VIO
ORG
GRN
–
1
2
4
5
7
8
TB4-3
TB4-4
TM2-6
TM2-8
TM1-8
TM1-6
TABLE 37
L7
9
FAULT BLOCK OPERATED
10
11
12
GRN
BLU
From
1
2
To
TB4-1
TB4-2
Color
BRN
RED
–
–
BLK
FB-D*
* Fault Block Accessory Connections
TABLE 40
“RA”
Fault Block Accessory Relay
From
A1
A2
To
TB5-17
FB-M
Color
GRN
BLK
A6
A7
B1
B6
TB5-18
A-24
TB5-28
TB5-27
A-14
BRN
GRY
WHT
RED
ORG
B7
To assure correct receipt of any parts order, always
include the control type and serial number. Because of
Cooper Power Systems’ continuous improvement policy,
there may be instances where parts furnished may not
look exactly the same as the parts ordered.
REPLACEMENT PARTS
Parts listed and illustrated include only those parts and
assemblies usually furnished for repair. Because of the
ease, faster receipt, and greater economy of local
acquisition, the wiring, wire end terminations, and
common hardware parts are not included in the
replacement parts listing.
However, they will be completely interchangeable without
any rework of the control. All parts carry the same war-
ranty as the original control, i.e., against failure due to
defects in material or workmanship within one year from
date of shipment.
40
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S260-75-1
1, 2, 3, 5
1, 2, 3, 4
8
10
8
1, 2, 3, 5
1, 2, 3, 4
9
12
11
11
13
14
14
1, 2, 3, 6
1, 2, 3, 6
15
1, 2, 3, 7
22
16, 17
18, 19, 20
23
20, 21
020076KM
Figure 28.
Front panel – replacement parts identification.
Front Panel Replacement Parts List
Index
No.
12
13
14
15
Catalog
Index
No.
1
2
3
4
5
6
7
8
Catalog
Number
Description
Number
Qty.
1
1
Description
Lamp socket
Socket fastener
Lamp
Lens, red (L4, L6)
Lens, green (L3, L5)
Lens, clear (L1, L2)
Lens, amber (L7)
Qty.
Diode circuit board assembly KCN120SA
Toggle switch, 4PDT (S3) KP2124A16
Toggle switch, DPDT (S1, S2) KP2124A6
Intermediate terminal strip
KP2361A1
KP2005A10
KP2276A3
KP2277A2
KP2277A5
KP2277A3
KP2277A4
6
6
6
2
2
2
1
2
1
1
2
(TB3, TB4)
Rotary selector switch (S4)
Switch knob
Knob lock
Lock backing
Self tapping screw,
6-32 x 1/2, stl
Spacer
Toggle switch, DPDT (35)
Toggle switch, 3PST (S7)
KP432ME
KCN199S
KCN149S1
KP107RS
KP497ME
2
1
1
1
1
16
17
18
19
20
Terminal post, black (T1, T2) KP2081A2
9
10
11
Terminal post, white (T3)
Toggle switch, 4PST (S6)
Digital timer
(TM1, TM2)
KP2081A1
KP2124A26
K751515106050A
KP3004A59
KP2124A21
KP2124A43
2
1
1
1
21
22
23
0.01 sec. to 99.9 hrs. range KP2159A2
2
41
Download from Www.Somanuals.com. All Manuals Search And Download.
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions
4, 6
2, 6
2, 6
7
2, 6
2, 6
3, 6
4, 6
4, 6
3, 6
1, 5
8
9
10
11, 12
020080KM
Figure 29.
Back panel – replacement parts identification.
Back Panel Replacement Parts List
Index
Catalog
Number
KP978ME
No.
Description
Qty.
1
1
Relay (R1)
2
3
Relay (R8, R9, R10, R11)
Relay (R4, R5)
KP978ME
KP978ME
6
2
4
Relay (R2, R6, R7)
KP978ME
1
5
6
7
8
Relay retainer
Relay retainer
Relay tie board subassembly
Surge protector board assembly
K999904310339A
K999904310339A
KCN203S900
KCN125SA
1
9
1
1
9
Terminal block (TB2) (Consists
of the following components)
Terminal section
KP999904150097A 12
End piece
KP999904150064A
KP2076A50
1
1
Marker strip
10
Terminal block (TB1) (Consists
of the following components)
Terminal section
KP999904150097A 16
End piece
KP999904150064A
KP2076A50
1
1
Marker strip
11
12
Fuse holder
Fuse
KP124S
KP125S
6
6
42
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S260-75-1
12
13
11
6
4
5
14
2
7
8
15
10
3
9
1
020081KM
Figure 30.
Fault block accessory – replacement parts identification.
Fault Block Accessory Replacement Parts List
Index
No.
Catalog
Number
KCN144S1
KCN141S1
K881215332010Z
KP2020A1
Description
Relay retainer bar
Circuit board retainer bar
Wing nut, 10-32, stl
Elastic stop nut
Phase actuating current circuit
board (add proper current value to
complete catalog number: 80, 112,
160, 224, 320, 448, 640)
Qty.
1
1
1
1
1
2
3
4
5
KCN116S___
1
6
Ground actuating
current resistor
KCN142S___
1
(add proper current
value to complete
catalog number: 10, 14,
20, 28, 40, 56, 80, 112,
160, 224, 320, 448)
Diode board
Trip-reset board
Relay (RY1)
Time-delay relay (RY2)
Transformer
Zener diode
7
8
9
10
11
12
13
14
KCN114SA
KCN112SA
KP978ME
K999904310339A
KA234ME
1
1
1
1
1
1
1
1
KP4011A12
KCN110SA
Tie board
Terminal block (TB5)
(Consists of the
following components)
Terminal section
End piece
KP999904150097A
KP999904150064A
KP2076A50
16
1
1
Marker strip
15
Barrier
KCN167S1
1
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions
!
SAFETY
FOR LIFE
P.O. Box 1640
©2002 Cooper Industries, Inc.
Waukesha, WI 53187
Kyle® is a registered trademark of Cooper Industries, Inc.
KDL
10/02
KA2048-291 Rev: 02
Download from Www.Somanuals.com. All Manuals Search And Download.
|