Cooper Lighting Switch S260 75 1 User Manual

Oil- and Vacuum-Break  
Switches  
Service Information  
Type S Automatic Load-Transfer Control  
Installation, Operation, and Maintenance Instructions S260-75-1  
Grounding the Control . . . . . . . . . . . . . . . . . . . . .6  
Before Placing the Control and Switchgear  
in Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6  
Equipment Required . . . . . . . . . . . . . . . . . . . . . . .6  
Customer Connections . . . . . . . . . . . . . . . . . . . . .8  
Interconnecting Cables . . . . . . . . . . . . . . . . . . . . .13  
Operating Instructions . . . . . . . . . . . . . . . . . . . . .16  
Initial Operation . . . . . . . . . . . . . . . . . . . . . . . . . .16  
Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . .17  
Theory of Operation—Basic S Control . . . . . . . . .17  
Voltage Sensing . . . . . . . . . . . . . . . . . . . . . . . . . .17  
Automatic Transfer, Preferred to Alternate . . . . . .18  
Return Transfer, Parallel Transition . . . . . . . . . . . .18  
Return Transfer, Non-Parallel Transition . . . . . . . .18  
No Preference Mode . . . . . . . . . . . . . . . . . . . . . .19  
Preferred Source II Mode . . . . . . . . . . . . . . . . . . .19  
Control Mode Switch, S5 . . . . . . . . . . . . . . . . . . .19  
Manual Control . . . . . . . . . . . . . . . . . . . . . . . . . . .19  
Indicating Lamps . . . . . . . . . . . . . . . . . . . . . . . . .19  
Remove the Control from Service . . . . . . . . . . . . .20  
Troubleshooting—Basic S Control . . . . . . . . . . . .20  
020076KM  
Figure 1.  
Kyle® Type S automatic load-transfer control.  
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20  
Basic Troubleshooting . . . . . . . . . . . . . . . . . . . . .20  
Advanced Troubleshooting . . . . . . . . . . . . . . . . . .21  
Fault Block Accessory . . . . . . . . . . . . . . . . . . . . .28  
General Description . . . . . . . . . . . . . . . . . . . . . . .28  
Accessory Settings . . . . . . . . . . . . . . . . . . . . . . . .28  
Operating Instructions . . . . . . . . . . . . . . . . . . . . .29  
Theory of Operation—Fault Block Accessory . . . .29  
Overcurrent Sensing . . . . . . . . . . . . . . . . . . . . . .29  
Phase Fault Operation . . . . . . . . . . . . . . . . . . . . .29  
Ground Fault Operation . . . . . . . . . . . . . . . . . . . .32  
Reset Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . .32  
Inrush Restraint Feature . . . . . . . . . . . . . . . . . . . .32  
Testing Fault Block Operation . . . . . . . . . . . . . . . .33  
Returning the Control to Service . . . . . . . . . . . . . .35  
Wiring Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36  
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . .40  
Front Panel—Replacement Parts List . . . . . . . . . .41  
Back Panel—Replacement Parts List . . . . . . . . . .42  
Fault Block Accessory—Replacement Parts List . .43  
Contents  
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . .2  
Hazard Statement Definitions . . . . . . . . . . . . . . . .2  
Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . .2  
Product Information . . . . . . . . . . . . . . . . . . . . . . .3  
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
Acceptance and Initial Inspection . . . . . . . . . . . . .3  
Handling and Storage . . . . . . . . . . . . . . . . . . . . . .3  
ANSI Standards . . . . . . . . . . . . . . . . . . . . . . . . . .3  
Quality Standards . . . . . . . . . . . . . . . . . . . . . . . . .3  
Description of Operation . . . . . . . . . . . . . . . . . . . .4  
Time Delay Selection . . . . . . . . . . . . . . . . . . . . . .4  
Pre-Installation Check . . . . . . . . . . . . . . . . . . . . . .5  
Pre-lnstallation . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
Installation Instructions . . . . . . . . . . . . . . . . . . . .6  
Initial Programming . . . . . . . . . . . . . . . . . . . . . . .6  
Mounting the Control . . . . . . . . . . . . . . . . . . . . . .6  
October 2002 • Supersedes 1/90  
Printed in USA  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
SAFETY  
FOR LIFE  
S260-75-1  
PRODUCT INFORMATION  
Introduction  
Handling and Storage  
Service Information S260-75-1 provides installation,  
operation, and maintenance instructions for the Kyle®  
Type S automatic load-transfer control.  
Use care during handling and storage of the control. If  
the control is to be stored for any length of time prior to  
installation, provide a clean, dry storage area to mini-  
mize the possibility of mechanical damage.  
Read This Manual First  
Read and understand the contents of this manual and  
follow all locally approved procedures and safety prac-  
tices before installing or operating this equipment.  
ANSI Standards  
Kyle reclosers are designed and tested in accordance  
with ANSI standards C37.60 and C37.85 and ANSI  
guideline C37.61.  
Additional Information  
These instructions cannot cover all details or variations in  
the equipment, procedures, or process described, nor to  
provide directions for meeting every possible contin-  
gency during installation, operation, or maintenance. For  
additional information, contact your Cooper Power  
Systems representative.  
Quality Standards  
The Quality System at the Cooper Power Systems, Kyle  
Distribution Switchgear plant is ISO 9001 certified.  
ISO 9001  
CAN/CSA ISO 9001  
BS EN ISO 9001  
ANSI/ASQC Q9001  
Acceptance and Initial  
Inspection  
Each Type S control is completely assembled, tested,  
and inspected at the factory. It is carefully calibrated,  
adjusted, and in good condition when accepted by the  
carrier for shipment.  
Upon receipt, inspect the carton for signs of damage.  
Unpack the control and inspect it thoroughly for damage  
incurred during shipment. If damage is discovered, file a  
claim with the carrier immediately.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions  
Description of Operation  
IMPORTANT: If Control Mode Switch S3 is placed in  
the “AUTO” position, the S-control will place the high-  
voltage transfer switches into the configuration that is  
currently selected by the Source Preference Switch  
S4. This may result in an unintended transfer. Make  
sure the desired state of the high-voltage transfer  
switches match the setting of S4 before returning S3 to  
the “AUTO” position.  
The Type S control is designed for use primarily with Kyle  
Type VR, VLR, VRV, TSC, and C three-phase, load-break  
switches in automatic load-transfer schemes. In a typical  
scheme, service to a critical load is normally supplied from  
a preferred source. It is automatically switched to an alter-  
nate, standby source if the preferred source voltage is lost  
for any reason for a preset period of time. Upon restora-  
tion of the preferred source voltage, the load is automati-  
cally switched back to the preferred source, again after a  
predetermined time delay.  
Manual Operation of the S control. The Source I and  
Source II high-voltage switches can be opened and  
closed independently to effect manual transfer from  
one source to the other. (Accomplished by setting  
OPERATION SELECTOR switch, S3, to MANUAL and  
operating MANUAL OPER. SOURCE I (S1) and MAN-  
UAL OPER. SOURCE II (S2) switches as required.)  
Typical Automatic Load-transfer  
Sequence using the Type S Control  
The load is transferred to the alternate source after a  
preset time delay, when the preferred source voltage  
is lost and normal voltage is present on the alternate  
source. Either Source I or Source II can be selected  
as the preferred source by a setting on the SOURCE  
PREFERENCE Switch, S4.  
In addition, a factory-installed fault block accessory will  
Block Transfer if loss of voltage is due to a fault on the  
load side of the high-voltage switches. When preferred  
source voltage is lost (due to the opening of the backup  
protective device)—and after the preset time delay—the  
preferred source switch will open and the fault block  
accessory will disable the S control to prevent closing  
either high-voltage switch into the fault. The S control  
must be manually reset before service to the load can be  
restored. The fault block option is a factory-installed  
accessory. The accessory is activated by over-current  
signals supplied by load-sensing current transformers  
built into special factory-modified Type VR, VLR, VRV,  
TSC, and CS high-voltage switches. It is also compatible  
with the PST-6 switchgear. The PST-9 switchgear does  
not require fault block.  
The load is transferred back to the preferred source—  
after another preset time delay—when normal volt-  
age is restored to the preferred source. The return  
transfer (from Source II to Source I) can be either  
non-parallel (alternate-source switch opens before  
preferred-source switch closes) or parallel (preferred-  
source switch closes before alternate-source switch  
opens). With parallel return the second interruption is  
eliminated; however, both sources must be in syn-  
chronism. The return transfer mode is selected by a  
setting on the SOURCE PREFERENCE switch, S4.  
Variations in the Operation  
of the Type S Control  
Time Delay Selection  
The time delay setting for preferred to alternate source  
transfer must be long enough to allow discrimination  
between permanent loss of voltage and temporary loss of  
voltage due to transient effects or reclosing intervals of  
backup protective reclosers or breakers. The time-delay  
required to override reclosing intervals is difficult to deter-  
mine since voltage may be subnormal during the retard-  
ed timing operations of the backup device due to the  
presence of the fault. It is recommended that the time  
delay before transfer from preferred to alternate source is  
set to exceed the maximum cumulative time to lockout of  
the backup protective device. This approach assures that  
the transfer switch will not interrupt the current of a fault  
occurring on the load side of the switch.  
No-Preference Operation. When either source is  
acceptable for continuous critical load supply. Upon  
loss of Source I voltage—and after a preset time  
delay—the load is automatically transferred to Source  
II, provided normal voltage is present on Source II.  
However, the load is not transferred back to Source I  
when voltage is restored, but remains on Source II  
until such time as Source II voltage is lost. Then an  
automatic nonparallel transfer to Source I is per-  
formed. (Accomplished by setting SOURCE PREF-  
ERENCE switch, S4, to NO PREF position.)  
Hold on Alternate Source. When placed to the  
HOLD ON ALTERNATE position, the S control will not  
automatically return to the preferred feeder. If the pre-  
ferred feeder is energized, the S control can be man-  
ually transferred to the preferred feeder by momen-  
tarily moving S3 to the NORMAL position.  
The time delay for return from alternate to preferred source  
upon restoration of preferred source voltage should be set  
for an interval long enough to assure that service on the  
preferred source has been permanently restored.  
When the control is programmed to operate in the “no-  
preference” mode, there are no preferred or alternate  
sources. Time delay intervals for transfer from Source I to  
Source II are governed by the left-hand Preferred to  
Alternate timer and for transfer from Source II to Source  
I by the right-hand Alternate to Preferred Timer. Settings  
of the two timers may be different because of difference  
in backup protection on the two sources.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
SAFETY  
FOR LIFE  
S260-75-1  
PRE-INSTALLATION CHECK  
between terminal 15 of TB1 and ground. Similarly,  
when MANUAL OPER. SOURCE II switch (S2) is in  
the CLOSE position there should be 120 Vac  
between terminal 25 of TB1 and ground.  
Pre-Installation  
WARNING: This equipment is not intended to  
!
protect human life. Follow all locally approved pro-  
cedures and safety practices when installing or operat-  
ing this equipment. Failure to comply can result in  
death, several personal injury and equipment damage.  
G102.1  
5. To check the response of the latching relay to auto-  
matic operation, proceed as follows:  
A. Set OPERATION SELECTOR switch (S3) to AUTO.  
B. Select the desired source preference and return  
mode with switch S4.  
WARNING: Hazardous voltage. Never rely on  
C. After waiting for a time in excess of the maximum  
transfer delay timer setting (to make sure the con-  
trol is at rest), simulate a “lost” phase by unscrew-  
ing one of the preferred source fuses. Listen for  
relay clatter to recognize breaking the circuit.  
!
the open position of the operating handle or the  
contact position indicator; it does not ensure that the  
line is deenergized. Follow all locally approved safety  
practices. Failure to comply can result in contact with  
high voltage, which will cause death or severe person-  
al injury.  
G123.1  
D. As soon as phase voltage is lost, the PREFERRED  
TO ALTERNATE TIMER will start to run. Verify the  
LED timer is illuminated during operation.  
The Type S automatic load-transfer control is pro-  
grammed to customer’s specifications and thoroughly  
tested before shipment from the factory. Perform the fol-  
lowing pre-installation test setup and procedure to verify  
the operation of the standard S control.  
E. When timing is complete, the latching relay (R1)  
will operate. Its position can be checked by the  
presence of 120 Vac at test terminals T-1 or T-2 on  
the front panel. 120 Vac between T-2 and T-3  
(ground) means the latching relay has moved to  
that position which would connect the load to  
Source II if HV switches were connected to the  
control. 120 Vac at T-1 means the load would be  
connected to Source I.  
Note: This procedure does not test complete control opera-  
tion. This can be done only on a complete installation  
basis with the S control operating the high-voltage  
transfer switches.  
Test Set–up  
1. Connect a 120 Vac, 60 Hz power supply to terminals Z  
and G2 of TB2 being absolutely certain that the  
grounded side of the power supply is connected to G2.  
F. Replace the removed fuse to restore preferred  
source power, observe operation of the ALTER-  
NATE TO PREFERRED TIMER, and check the  
status of the latching relay (R1) when timing is  
completed.  
2. Jumper terminal Z to Y to X to C to B to A.  
Note: SOURCE PREFERENCE switch S4 cannot be  
3. When the 120 Vac power supply is turned on, all six  
in NO PREF position for this test.  
phases are energized.  
G. Other modes of transfer can be checked by pro-  
gramming the control for the desired sequence,  
simulating loss of source voltage, observing resul-  
tant control operation, and checking the final posi-  
tion of the latching relay (R1).  
4. To simulate loss of voltage on any phase of either  
source, simply unscrew the appropriate fuse “FU” in  
the control.  
Test Procedure  
6. Timer settings can be verified with a watch while per-  
1. Check the indicating lamps by depressing the LAMP  
TEST switch (S6). All lamps on the front panel of the  
control (including fault block accessory if installed)  
should light with equal brilliance.  
forming the checks in preceding Step 5.  
7. Switch I and Switch II position indicating lamps will  
not operate during this preinstallation check since the  
high-voltage transfer switches are not connected to  
the control.  
2. With phase Y and/or phase B energized, terminals 11  
and 21 of TB1 will always show 120 Vac to ground  
(G or G ).  
Their operation can be verified by connecting a 100  
ohm, 1 watt, resistor from TB1 terminals to ground  
as follows:  
1
2
3. With OPERATIONS SELECTOR switch (S3) set to  
MANUAL, terminal 13 of TB1 will respond to the  
operation of MANUAL OPER. SOURCE I switch (S1)  
showing 120 Vac to ground when S1 is in the open  
position and 10 Vac, or less, when S1 is in the OFF  
and CLOSE positions. Terminal 23 of TB1 will show  
similar voltages to ground in response to the opera-  
tion of MANUAL OPER.  
SWITCH I OPEN lamp—terminal 15 to ground  
SWITCH I CLOSED lamp—terminal 24 to ground  
SWITCH II OPEN lamp—terminal 25 to ground  
SWITCH II CLOSED lamp—terminal 14 to ground  
4. When MANUAL OPER. SOURCE I switch (S1) is in  
the CLOSE position there should be 120 Vac  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions  
INSTALLATION INSTRUCTIONS  
A typical automatic transfer scheme is illustrated in Figure 2.  
Before Placing the Control and  
Switchgear into Service  
Initial Programming  
CAUTION: Equipment misoperation. Do not  
The control must be programmed with all necessary  
operating settings prior to operation with energized  
switchgear. For the desired settings refer to the  
Operating Instructions section in this manual.  
!
energize this equipment until all control settings  
have been properly programmed and verified. Refer to  
the Control Programming and Operation section of this  
manual for programming procedures. Failure to com-  
ply can result in misoperation (unintended operation),  
Mounting the Control  
equipment damage, and personal injury.  
G118.1  
Mount the S control in a convenient, accessible location.  
Maximum distances between the high-voltage transfer  
switches and potential sensing transformers and the con-  
trol depends upon the size of the control cable wire and  
the length of various cable combinations. (See the  
Interconnecting Cables section in this manual.) Keep in  
mind that the longer the cable lengths, the greater the  
susceptibility to surge damage. Therefore, for optimum  
reliability and economy, locate the switches and trans-  
formers as near as possible to the control.  
Prior to placing the control and switchgear into service,  
the following installation procedures must be properly  
completed and verified:  
1. Control properly mounted for the installation.  
2. Equipment installed according to all locally approved  
standards and practices.  
3. Control and switchgear properly grounded in accor-  
dance with guidelines in this manual.  
Mounting dimensions are provided in Figure 3.  
4. AC power connected to the control.  
For pole-mounted installation, a hole and keyway in  
the control mounting bracket accommodates a 5/8”  
bolt.  
5. All control programming entered and verified by  
appropriate personnel.  
For substation installation, the control is factory  
installed. Leveling is not required.  
Equipment Required  
The following equipment is required for a load-transfer  
installation:  
Grounding the Control  
Type S Load-Transfer Control  
WARNING: Hazardous voltage. Solidly ground  
!
all equipment. Failure to comply can result in  
The control, with or without the fault block accessory, is  
housed in a cabinet whose outline and mounting dimen-  
sions are shown in Figure 3. The control cabinet can be  
mounted on a pole or substation structure. Leveling is not  
required. Both the cabinet door and the hinged front  
panel are equipped with hold-open latches to prevent  
them from swinging in the open position.  
death, severe personal injury, and equipment damage.  
T223.2  
The control cabinet must be grounded. A grounding con-  
nector on the underside of the cabinet will accommodate  
No. 14 solid through No. 4 stranded conductors.  
For efffective surge protection all control and power con-  
ductors for the S control must be routed parallel to a cor-  
responding ground path. For example, the AC power  
supply for the control should be parallel to and equal in  
length to the transformer ground path. The control cable  
should be parallel to and routed close to the switchgear  
ground path.  
Motor Operated Switches  
The three-phase, load break switches require a special  
wiring accessory for operation with the Type S control. In  
addition, if fault block is provided, the switches must be  
equipped with 1000:1 ratio current transformers also  
available as a factory-installed switch accessory. See the  
switch installation manual for overall and mounting  
dimensions and for wiring diagrams.  
Potential Transformers  
Three-phase voltage sensing is required for control oper-  
ation. Transformer connections and voltages for various  
distribution system connections are shown in Figure 5.  
The voltage sensing relays of the Type S control drop out  
on a decreasing voltage at 75 volts (min) and pick up on  
an increasing voltage at 97 volts (max). The control  
requires 120 Vac, 60 Hz, 500 VA (min) to operate the  
transformer switches. Quiescent power dissipation at  
120 Vac is 18 watts.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
SAFETY  
FOR LIFE  
S260-75-1  
LOAD  
SOURCE II  
H.V.  
SWITCH  
II  
SOURCE I  
H.V.  
SWITCH  
I
POTENTIAL  
SENSING  
TRANSFORMERS  
POTENTIAL  
SENSING  
TRANSFORMERS  
TYPE  
S
CONTROL  
Figure 2.  
Typical Type S control load-transfer scheme.  
MTG HOLES (2) FOR  
5/8" MAX BOLT DIA  
16"  
8"  
12 13/16"  
1 1/2"  
20 1/8"  
MTG DIM  
17 7/8"  
22 5/32"  
5/8" HOLE PROVIDED  
FOR CUSTOMER LOCK  
GROUNDING  
TERMINAL LUG  
(14 TO 4 STRANDED)  
11"  
1 3/16"  
13 1/2"  
2 1/2" 2 1/2"  
2 1/2" 2 1/2"  
1 5/8" DIA HOLES  
5 1/4"  
STD CONTROL  
CONTROL WITH FAULT BLOCK  
Figure 3.  
Outline and mounting dimensions.  
TABLE 1  
Reaction and Transition Times of Cooper Power Systems Motor-Operated Switches  
Direction of  
Transfer  
(Source to  
Source)  
First Switch  
Reaction Time*  
Transition  
Time**  
Switch  
Type of Transition  
No paralleling of sources  
VR, VLR, VRV (standard)  
VR, VLR, VRV (standard)  
VR, VLR, VRV (standard)  
2.5 to 3.5 cycles 10 sec (approx)  
2.5 to 3.5 cycles 10 sec (approx)  
10 sec (approx) 1.0 to 1.5 cycles  
I to II  
II to I  
II to I  
No paralleling of sources  
Paralleling of sources on return to preferred source  
VR, VLR, VRV (quick close) 2.5 to 3.5 cycles 6 to 7 cycles  
VR, VLR, VRV (quick close) 2.5 to 3.5 cycles 6 to 7 cycles  
VR, VLR, VRV (quick close) 4.0 to 5.5 cycles 1.0 to 1.5 cycles  
I to II  
II to I  
II to I  
No paralleling of sources  
No paralleling of sources  
Paralleling of sources on return to preferred source  
TSC  
TSC  
TSC  
7 to 8 sec  
7 to 8 sec  
7 to 8 sec  
7 to 8 sec  
7 to 8 sec  
7 to 8 sec  
I to II  
II to I  
II to I  
No paralleling of sources  
No paralleling of sources  
Paralleling of sources on return to preferred source  
PST-6, PST-9  
PST-6, PST-9  
PST-6, PST-9  
2.0 to 3.0 cycles 5.0 to 6.0 cycles  
2.0 to 3.0 cycles 5.0 to 6.0 cycles  
5.0 to 6.0 cycles 2.0 to 3.0 cycles  
I to II  
II to I  
II to I  
No paralleling of sources  
No paralleling of sources  
Paralleling of sources on return to preferred source  
*
Time from expiration of time delay to first opening (or closing) of high-voltage switch. Add approximately one cycle to the  
values shown to allow for Type S control relay operating time.  
** Time-load tap is disconnected or paralleled depending on type of transition used.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions  
LOAD  
C
A
D
H.V.  
H.V.  
SWITCH  
SWITCH  
SOURCE  
FEEDER  
B
S
CONT  
Phase Voltage at the Three-Phase Sensing Type S Load Transfer Control as Related to System and Sensing Transformer Connections  
%
*
Assuming no feedback from the load  
** Bank operates open wye-delta; requires two primary phases open for sensing  
Voltage may vary from 87 to 58% depending on load  
Figure 4.  
Phase voltage at the three-phase sensing Type S load-transfer control.  
the internal wiring between the terminal blocks and the  
Customer Connections  
Connection Diagram  
input and output receptacles on the control (available as  
an accessory) and the external wiring between the con-  
trol, transfer switches, and potential transformers. If the  
control is not equipped with the plugs and receptacles  
accessory, the cables are wired directly to the terminal  
blocks in the control. For the physical location of terminal  
blocks, refer to Figure 27.  
CAUTION: Equipment Damage. Do not drill connec-  
tion holes into the top of the cabinet. Connection holes in  
the top of the cabinet will allow moisture to seep into the  
control and damage the components or cause control  
misoperation. Failure to comply will void the controls fac-  
Note: Internally wired receptacles and mating plugs for the  
switch operators and current sensing transformers on  
the switch end of the cables are provided as standard  
with the switches.  
tory warranty.  
T249.0  
Diagrams for interconnecting the load-transfer control  
with the high-voltage switches and potential transformers  
are shown in Figures 5 through 8. The diagrams show  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
SAFETY  
FOR LIFE  
S260-75-1  
Figure 5.  
Connection diagram for Type S load-transfer control (with fault block accessory) operating a Type VR, VLR, or  
VRV three-phase switch. (The transformer cutouts, tap fuses, reclosers, and arresters are not shown.)  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions  
O P E N  
C L O S E  
O P E N  
C L O S E  
Figure 6.  
Connection diagram for Type S load-transfer control (with fault block accessory) operating the Type TSC  
three-phase switch. (The transformer cutouts, tap fuses, reclosers, and arresters are not shown.)  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
SAFETY  
FOR LIFE  
S260-75-1  
Figure 7.  
Connection diagram for Type S load-transfer control operating the Type PST-6 switch. (The transformer cutouts,  
tap fuses, reclosers, and arresters are not shown.)  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions  
Figure 8.  
Connection diagram for Type S load-transfer control operating the Type PST-9 switch. (The transformer cutouts,  
tap fuses, reclosers, and arresters are not shown.)  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
SAFETY  
FOR LIFE  
S260-75-1  
Interconnecting Cables  
Interconnecting cable conductor size is dependent upon  
the distance between the control, switches, and potential  
transformers. Maximum lengths of various cable combi-  
nations for No. 18 through No. 12 AWG conductors are  
shown in Table 2. The longest combination for the partic-  
ular installation will determine the minimum conductor  
size. All cables are to be the same conductor size.  
Note: If the control is equipped with the fault block accesso-  
ry, see Table 3 for additional cable length limitations.  
On the switch end, the cables are wired to connector  
plugs provided as standard with the switches. On the S  
control end, the cables are wired either directly to termi-  
nal blocks in the control or to connector plugs provided  
with the Plugs and Receptacles accessory. Figure 9  
shows the location of the accessory plugs and recepta-  
cles in the bottom of the control cabinet. See the appro-  
priate switch installation manual for the location of the  
plugs and receptacles on the switch.  
020079KM  
Figure 9.  
Plugs and receptacles accessory.  
Switch Cable  
KEYWAY  
A conductor cable is required between the S control and  
each high-voltage switch to operate the switches. This  
cable is wired to a socket plug at the switch end and to  
either a plug or TB1 at the control end. Pin identification,  
and cable OD and maximum conductor size accommo-  
dated by the plugs are shown in Figures 10 and 11.  
PIN INSERT CONNECTIONS INTO CONTROL  
PIN F  
A
VIEW A-A  
RUBBER GROMMET  
ACCOMMODATES  
1/2" TO 5/8" DIA. CABLE  
A
Potential Transformer Cable  
MAX. WIRE SIZE NO.16 AWG  
A four-conductor cable is required between the S control  
and the potential transformers to transmit source voltage  
intelligence and to supply operating power for the control.  
This cable is wired to a five-pin socket plug or TB2 at the  
control end. Pin socket identification, cable OD, and  
maximum conductor size accommodated by the plugs  
are shown in Figure 12.  
Figure 10.  
Switch cable plug for VR, VLR, VRV, and TSC.  
PST-6 8, 7, & 19 PIN RECEPTACLES  
PST-9 8 & 19 PIN RECEPTACLES  
Note: Connectors are not supplied for the transformer end of  
KEYWAY  
PIN INSERT CONNECTIONS INTO CONTROL  
PIN F  
the cable.  
A
M
A
L
T
F
A
C
A
G
N
B
C
D
K
J
U
TABLE 2  
Maximum Control Cable Lengths  
B
C
E
F
G
B
H
V
P
R
H
S
E
D
D
G
E
F
LOAD  
8 PIN  
7 PIN  
19 PIN  
A
HV  
SW  
2
HV  
SW  
1
VIEW A-A  
Figure 11.  
Switch cable plugs for PST-6 and PST-9.  
S CONTROL  
D
B
A
C
KEYWAY  
SOCKET E  
SOCKET INSERT CONNECTS INTO CONTROL  
Maximum Length of  
Control Cable Combinations (ft.)  
A
Cable Wire  
Size  
(AWG)  
VR, VLR, or VRV Switches TSC Switch  
A+B+D or C+B+D  
A+B or A+D  
or C+B or C+D  
18  
16  
14  
12  
1450  
2300  
3700  
5900  
1250  
2000  
3200  
5050  
A
RUBBER GROMMET  
ACCOMMODATES  
3/8" TO 1/2" DIA. CABLE  
MAX. WIRE SIZE NO.12 AWG  
Note: The control cable lengths are not applicable for the C  
Figure 12.  
PT cable plug.  
switch and the PST switch.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions  
Fault Block Shielded Cable  
Table 3 shows the maximum distance between the con-  
TABLE 3  
Fault Block Cable Limitations  
trol and the high-voltage switches for a range of conduc-  
tor sizes and fault-block settings. The table is based on  
conductor voltage drop and saturation of the current  
sensing transformers in the switch. Lower actuating lev-  
els and lower multipliers could allow longer lines.  
However, the limitation on switch control cable lengths,  
Table 2, preclude their use.  
Max. Distance in Feet  
Between Switch and  
S Control  
Phase  
Actuating  
Current  
Level  
Con-  
ductor  
Size  
For X 8  
Multi-  
plier  
For X 6  
Multi-  
plier  
For X 4  
Multi-  
plier  
(Amps)  
(AWG)  
640  
640  
640  
640  
18  
16  
14  
12  
600  
950  
1500  
2400  
1000  
1600  
2550  
4000  
1800  
2900  
4600  
7300  
Shielded cable is required between the transfer switches  
and the S control for operating the fault block accessory.  
448  
448  
448  
448  
320  
320  
320  
320  
18  
16  
14  
12  
18  
16  
14  
12  
1100  
1800  
2800  
4500  
1800  
2900  
4600  
7300  
1700  
2700  
4300  
6850  
IMPORTANT: Only shielded cable is to be used on fault  
block accessory and is mandatory to validate the  
Cooper Power Systems warranty. Use of a non-shielded  
cable could result in misoperation.  
The shield must be grounded to the equipment housing  
at both the switch and control ends. Shield connections  
are made at connector plug pin or socket as shown in  
Figure 13. This pin mates with the receptacle pin or sock-  
et which is grounded in the switch and in the control as  
shown in Figures 6 and 8.  
SOLDER #16 AWG JUMPER WIRE  
FROM SHIELD TO PIN G TO  
COMPLETE SHIELD CONNECTION  
RUBBER GROMMET  
ACCOMMODATES  
KEYWAY  
KEYWAY  
.50 TO .56 DIA. CABLE  
PIN G  
SOCKET A  
A
A
CONTROL END  
SWITCH END  
STRIP JACKET TO EXPOSE SHIELDING  
Figure 13.  
Fault block cable plug.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
SAFETY  
FOR LIFE  
S260-75-1  
6
7
8
5
4
9
3
2
10  
11  
1
12  
13  
14  
15  
020076KM  
Figure 14.  
Type S control front panel.  
TABLE 4  
Description and Use of Operating Controls and Indicators  
Index No.  
Figure 2  
Description  
Purpose and Use  
1
SOURCE PREFERENCE AND RETURN MODE  
Switch (S4) (See Note A)  
Selects either Source I (PREF I) or Source II (PREF II) as the  
preferred source, or no preference (NO PREF). Also selected  
parallel (P) or non-parallel (NP) return mode.  
2
3
4
SOURCE I ENERGIZED lamp  
OPERATION SELECTOR Switch (S3)  
PREFERRED TO ALTERNATE TIMER  
Indicates all three phases of Source I are energized.  
Programs control for either AUTOmatic or MANUAL operation.  
Determines time delay before transfer to alternate source when  
preferred source voltage is lost.  
5
6
7
SWITCH I OPEN and CLOSED lamps  
LAMP TEST switch (S6)  
LATCH RELAY STATUS TEST terminals  
(T1T2T3)  
Indicates status of Source I high voltage switch.  
Tests all indicating lamps on front panel.  
Provides electrical access to both sides of latch relay to  
determine if control is in Source I or Source II mode.  
8
9
SWITCH II OPEN and CLOSED lamps  
ALTERNATE TO PREFERRED TIMER  
Indicates status of Source II high voltage switch.  
Determines the time delay before transfer to preferred source  
when preferred source voltage is restored.  
10  
MANUAL OPER. SOURCE I and MANUAL OPER. Provides means to OPEN and CLOSE Source I and Source II  
SOURCE II switches (S1 and S2)  
transfer switch upon manual command, when S3 is in MANUAL  
position.  
11  
12  
SOURCE II ENERGIZED lamp  
CONTROL MODE switch (S5)  
Indicates all three phases of Source II are energized.  
Blocks automatic return transfer to preferred sources (HOLD ON  
ALTERNATE); also enables control to be operated without  
operating the high voltage transfer switches (TEST).  
13  
14  
FAULT-BLOCK OPERATED lamp  
RESET switch (S7)  
Indicates fault-block has operated (part of fault-block accessory).  
Resets the control after a fault block operation (part of fault-block  
accessory). S3 must be in MANUAL position.  
15  
Fuses  
Voltage input of all three phases of both Source I and Source II  
are fused for 10A-125 vac; white button shows on front of fuse if  
fuse blows.  
Note A Tab provided to lock switch knob in set position; stop screw prevents inadvertent selection of parallel return transfer mode.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions  
OPERATING INSTRUCTIONS  
1. The switches on the front panel should be positioned  
DANGER: Hazardous voltage. Contact with haz-  
as follows:  
!
ardous voltage will cause death or severe person-  
A. S1 (MANUAL OPER. SOURCEI) OFF  
B. S2 (MANUAL OPER. SOURCE II) OFF  
C. S3 (OPERATlON SELECTOR) MANUAL  
al injury. Follow all locally approved safety procedures  
when working around high and low voltage lines and  
equipment.  
G103.3  
D. S4 (SOURCE PREFERENCE AND RETURN  
MODE) set to the desired mode of operation.  
WARNING: Hazardous voltage. Never rely on  
!
the open position of the operating handle or the  
E. S5 (CONTROL MODE) NORMAL  
contact position indicator; it does not ensure that the  
line is deenergized. Follow all locally approved safety  
practices. Failure to comply can result in contact with  
high voltage, which wil cause death or severe person-  
2. Set the PREFERRED TO ALTERNATE TIMER and  
ALTERNATE TO PREFERRED TIMER as required.  
(See Time Delay section in this manual.)  
al injury.  
G123.1  
3. Check that all installation connections are complete  
as shown in the appropriate connection diagram  
Figures 5 through 8.  
Before energizing the installation, an understanding of  
the functions of the operating controls and indicating  
lights is essential. (See Table 4 and Figure 14).  
4. Make sure both high-voltage transfer switches are open.  
5. With all six fuses in place, energize both power  
Initial Operation  
sources to the control.  
To place the automatic transfer scheme into service, pro-  
ceed as follows:  
A. SOURCE I ENERGIZED lamp should be on.  
B. SOURCE II ENERGIZED lamp should be on.  
C. SWITCH I OPEN lamp should be on.  
CAUTION: Equipment misoperation. Source I and  
Source II high voltage switches can be paralleled in the  
manual operation mode even if SOURCE PREFER-  
ENCE switch, S4, is set for NP (non-parallel opera-  
tion). Make sure both sources are in synchronism if a  
manual parallel operation is to be performed. Failure to  
comply can result in misoperation (unintended opera-  
D. SWITCH II OPEN lamp should be on.  
6. Depending upon which source is the preferred  
source, momentarily operate either S1 or S2 to the  
CLOSE position. The appropriate switch will close to  
energize the load and its status indicating lights will  
transfer from OPEN to CLOSED.  
tion) and equipment damage.  
T304.0  
7. Place the OPERATION SELECTOR SWITCH (S3) to  
AUTO. The S control is in service. No further opera-  
tion will occur until the preferred source voltage is lost.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
SAFETY  
FOR LIFE  
S260-75-1  
Out Indicator  
Timer Settings  
The out indicator briefly lights to signal completion of a  
timing interval and confirm that the timer has operated.  
IMPORTANT: Put control in manual mode prior to  
changing timer setting. There is no fault current pro-  
tection when in manual mode. Failure to comply can  
cause unintended operation.  
Normal Operation  
The control will react to ongoing line voltage conditions  
and operate automatically as programmed. If equipped  
with the fault block accessory, transfer to the alternate  
source may be prevented when loss of voltage is due to  
The two digital timers are identical. One timer controls the  
time required to transfer from the preferred source to the  
alternate source, the other timer controls the time to trans-  
fer from the alternate source to the preferred source.  
a
load-side fault. See Fault Block Operating  
Instructions section for procedure to restore service.  
OUT Indicator  
THEORY OF OPERATION  
—BASIC S CONTROL  
OUT  
Digital Time  
Thumb-Wheel  
Time Setting  
3.45  
9
3 49  
5
Refer to Figures 16 and 17 for the following sections:  
Display  
Voltage Sensing  
The S control will transfer the load to an alternate source  
when one or more phases of the preferred source is lost,  
provided normal voltage is present on all three phases of  
the alternate source. To perform this function, the control  
requires three-phase, low-voltage (120 Vac) input from  
both the preferred and alternate sources of power. Input  
from Source I is connected to terminals A, B, C and G1  
of TB2, and input from Source II is connected to termi-  
nals X, Y, Z and G2.  
9 9 9  
Decimal Point  
Indicator  
S
Time Range  
Selector  
Figure 15.  
Digital Timer and Time Ranges.  
The two digital timers feature the following informational  
indicators and adjustment controls:  
Each of the three input phase leads for both Source I and  
Source II is shunted to ground by a capacitorvaristor  
combination to provide surge protection to the control.  
On the preferred source side of the voltage sensing cir-  
cuitry, the input lines then pass through 10 Amp fuses to  
the voltage sensing relays: R2 (Phase A), R9 (Phase B)  
and R10 (Phase C). R9 and R10 are connected directly  
to the input while N.O. contacts of R9 and R10 are in  
series with the R2 coil. Thus, R2 can be energized only if  
all three incoming phase voltages are above a predeter-  
mined value (approximately 97 volts). A similar arrange-  
ment is used for the alternate source sensing relays. R6  
can be energized only if R7 and R8 are energized. The  
transfer bus across the top of the schematic diagram),  
which provides the operating power for the control is nor-  
mally energized from Phase Y. If R7 drops out, due to  
loss of Phase Y, R11 will be energized from Phase B  
(through N.C. contact of R7) to re-energize the transfer  
bus. The contacts of R7 and R11 are so connected that  
the transfer bus can never be simultaneously energized  
from both B and Y phases.  
Digital Time Display  
LED displays the time count. The timer counts up until it  
reaches the time delay setting of the thumbwheel switch.  
Time Range Selector  
The time range selector switch can be set to six different  
positions with a flat screwdriver. Each position indicates a  
time range. See chart below. The time range selector is  
preset to the time range of 0.1 to 99.9 seconds.  
9.99  
99.9 999  
99.9  
999  
99.9  
S
M
H
S
S
M
Indication  
0.1  
to  
0.1  
to  
1
to  
1
to  
0.1  
to  
99.9  
min  
0.01  
to  
9.99  
sec  
Time  
Range  
99.9  
hours  
99.9 999  
sec sec  
999  
min  
Thumbwheel Time Setting  
IMPORTANT: Thumb-wheel time setting must be  
securely turned. Incomplete setting may cause timer  
malfunction and control misoperation.  
Set the desired time delay setting by rotating the thumb-  
wheel switch. For example, if the thumbwheel time set-  
ting is 345 the timer will time out in 34.5 seconds based  
off the time range selector setting of 0.1 to 99.9 seconds.  
Note: The thumb-wheel time setting, which does not turn  
infinitely, should not be turned beyond the limit.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions  
The transfer of R1 energizes the close coil of SW-I as follows:  
Automatic Transfer, Preferred to  
Alternate  
Transfer bus voltage passes through terminals 5-1 of S3,  
contacts 9-6 of latched R1, and terminals 5-6 of S5. It is  
then impressed on N.C. contact 7-2 of R5 and passes  
through deck A of S4 to output terminal 15 of TB-1. This  
activates the close coil in SW-I. When SW-I closes, its  
auxiliary contact acloses to energize R5 (via TB1-24  
and deck E of S4). Contact 7-5 of R5 closes to energize  
TB1-23 through deck D of S4. Voltage at TB1-23 will  
actuate the trip coil of SW-II to open the Source II high-  
voltage transfer switch.  
The following assumptions are made:  
OPERATION SELECTOR switch (S3) is in AUTO.  
SOURCE PREFERENCE and RETURN MODE  
switch (S4) is in PREF l-P (Terminal 2 of each deck  
connected).  
CONTROL MODE switch (S5) is in NORMAL.  
S control is in a quiescent state.  
Note: The Source I high-voltage switch (SW-I) closes before  
the Source II high-voltage switch (SW-II) opens to  
effect a parallel return transition. SW-I will now remain  
closed and SW-II open until Source I voltage is lost or  
a change of control settings is made.  
Source I high-voltage transfer switch (SW-I) is closed  
and Source II high voltage transfer switch (SW-II) is  
open.  
Note: The actuators of both high-voltage transfer switch-  
es are shown in the switch open position on the  
schematic diagram. Following each opening opera-  
tion, the motor recharges the actuator springs and  
the cutout switch returns to the position shown in  
the schematic. However, when the high voltage  
transfer switch is closed, the selector switch of the  
actuator mechanism is opposite to that shown in  
the schematic.  
Return Transfer, Non-Parallel  
Transition  
The following assumptions are made:  
SOURCE PREFERENCE and RETURN MODE  
switch (S4) is in PREF l-NP (Terminal 3 of each  
deck connected).  
If one or more phases of the preferred source (Source I)  
are lost, R2 will drop out and the SOURCE I ENER-  
GIZED lamp (L1) will go out. N.C. contacts 1-7 of R2  
close completing the circuit to the PREFERRED TO  
ALTERNATE TlMER (TM1) through 4-7 of R6 (which is  
energized), 7-4 of R1, and deck J of S4. When TM1 times  
out, its 5-6 contacts close to energize the coil of R1 in the  
reset direction causing R1 to transfer. Diodes in the cir-  
cuit of this single-coil magnetically held relay determine  
whether latchingor resettingoccurs.  
Source I has lost one or more phases and the load  
has been transferred to Source II as previously  
described (SW-I open and SW-II closed).  
Control is in a quiescent state with latching relay R1  
in the reset position (contacts 9-3 and 8-2 closed)  
and R2 is deenergized.  
When Source I power is restored on all three phases, R2  
will pick up, closing its contact 9-6, and energize the  
ALTERNATE TO PREFERRED TIMER (TM-2) through  
contact 8-2 of R1, and deck K of S4. After TM-2 times  
out, its 5-6 contact closes to energize the coiI of R1  
through diode DL in the latching direction causing R1 to  
transfer, closing its 6-9 contact.  
The transfer of R1 energizes the trip coil of Source I high-  
voltage transfer switch (SW-I) as follows:  
Transfer bus voltage passes through terminals 5-1 of S3,  
contact 9-3 of energized R1, and terminals 4-3 of S5. It  
is then impressed on N.C. contact 7-2 of R4 and passes  
through deck B of S4 to output terminal 13 of TB-1.  
Terminal 13 is connected to the internal selector switch in  
the actuator of SW-I (which is closed when SW-I is  
closed), through the trip coil to ground (terminal G).  
In this case, the trip coil of SW-II is immediately ener-  
gized through the following circuit:  
Terminals 5-1 of S3, N.C. contact 9-6 of R1, terminals 5-  
6 of S5, N.C. contact 7-2 of R5, and deck D of S4 to out-  
put terminal TB1-23 to activate the trip coil of SW-I I and  
open to Source II high-voltage transfer switch.  
After SW-I has opened, the selector transfers to connect  
terminal 3 to terminal 4, which energizes terminal 16 of  
TB1. In turn contacts 2-6 of S3, deck C of S4, and termi-  
nal 25 of TB-1 are energized to operate the close coil of  
SW-II and close the switch.  
When SW-II opens, its selector switch transfers to  
impress the voltage at TB1-23 onto TB1-26 which, in turn,  
energizes TB1-15 through terminals 3-7 of S3 and deck A  
of S4. Voltage at TB-15 will actuate the quick-close coil of  
SW-I to close the Source I high-voltage switch.  
SW-I will now remain open and SW-II closed until Source  
I voltage is restored.  
Note: In this instance, the Source II high voltage switch (SW-  
II) opens before the Source I high voltage switch clos-  
es, to effect a non-parallel return transition. SW-I will  
now remain closed and SW-II open until Source I volt-  
age is lost or a change is made in the control settings.  
Return Transfer, Parallel Transition  
When Source I power is restored on all three phases, R2  
will pick up and Source I Energized lamp (L1) will light.  
Contact 9-6 of R2 closes to energize ALTERNATE TO  
PREFERRED TIMER (TM-2) through contact 8-2 of R1,  
and deck K of S4. After TM2 times out, its contacts 5-6  
close to energize the coil of R1 through diode DL in the  
latching direction causing R1 to transfer.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
SAFETY  
FOR LIFE  
S260-75-1  
No Preference Mode  
Manual Control  
Assume the Source I high-voltage switch (SW-I) is  
closed and Source II high-voltage switch is open. With  
the SOURCE PREFERENCE and RETURN MODE  
switch (S4) in NO PREF-NP (Terminal 4 of S4 connect-  
ed), loss of Source I voltage on one or more phases will  
open the Source I high-voltage switch (SW-I) as  
described in the Automatic Transfer, Preferred to  
Alternate section of this discussion.  
When the OPERATION SELECTOR switch (S3) is  
placed in MANUAL, it connects the MANUAL OPER.  
SOURCE I switch (S1) and the MANUAL OPER.  
SOURCE II switch (S2) to the transfer bus. Power can  
then be supplied to either the close or trip coils of either  
SW-I or SW-II. Contacts 3-7 and 2-6 of S3 are opened in  
the MANUAL position so that opening of one high-volt-  
age transfer switch does not cause automatic closing of  
the other. In the manual mode of operation, it is possible  
to have both high-voltage switches open, either switch  
closed, or both switches closed.  
Upon restoration of Source I voltage, R2 is re-ener-  
gized. However, due to the positioning of decks G and  
H of S4, neither timer can be energized since both the  
N.C. contacts 1-7 of R2, and 9-3 of R6 are open (both  
relays are energized).  
Indicating Lamps  
The LAMP TEST switch (S6) is provided for checking the  
various incandescent indicators on the front panel of the  
S control. In the closed position, all the lamps will be  
energized through a diode network to check their condi-  
tion.  
The S control is now in a quiescent state with SW-II  
closed and SW-I open. This condition will continue until  
either Source II is lost or a change is made in the control  
settings. If Source II is lost, delay in transfer to Source I  
will be timed by TM-2.  
In the open position, the diode network isolates the  
lamps from the test switch so that it has no effect on nor-  
mal circuit operation.  
Preferred Source II Mode  
With the SOURCE PREFERENCE and MODE switch  
(S4) in either PREF II-P (Terminal 6 of S4 connected), or  
PREF II-NP (Terminal 5 of S4 connected) the description  
of operation is similar to the Automatic Transfer,  
Preferred to Alternateand Return Transfer, Parallel  
Transitionor Return Transfer, Non-Paralleled  
Transitionas previously described except that Source II  
is the preferred source (controlled by SW-II) and Source  
I is the alternate source (controlled by SW-I).  
Control Mode Switch, S5  
If S5 is placed in the center-off TEST position, there is no  
circuit to either the close or trip coils of either high-volt-  
age transfer switch. This position of S5 is used to check  
sensing circuitry, timers, and the latching relay without  
affecting the status of the high-voltage switches.  
If S5 is placed in the HOLD ON ALTERNATE position,  
return transfer will not occur after preferred source volt-  
age is restored. Assume the S3 is in AUTO, S4 is in  
PREF l-P, and the S control is in the quiescent state with  
Source I high voltage (SWI) closed and Source II high-  
voltage switch (SW-II) open. Upon loss of Source I, R2  
will again initiate a transfer of the latching relay R1 as  
previously described, followed by the opening of SW-I  
and the closing of SW-2. The S control is now in a qui-  
escent state in which SW-2 will remain closed and SW-I  
will remain open even when Source I power is restored.  
When Source I is reenergized, R1 will transfer back to  
the latch position and close its contact 9-6. However,  
because deck L of S4 is open, power cannot be provided  
to the trip coil of SW-II or the close coil of SW-I.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions  
TROUBLESHOOTINGBASIC S CONTROL  
CAUTION: Equipment misoperation. Do not  
Basic Troubleshooting  
!
energize this equipment until all control settings  
A quick check of the basic transfer operation while the con-  
have been properly programmed and verified. Refer to  
the Control Programming and Operation section of this  
manual for programming procedures. Failure to com-  
ply can result in misoperation (unintended operation),  
trol is in service can be made using the following procedure:  
Source I or Source II Preferred  
Operation  
equipment damage, and personal injury.  
G118.1  
1. Set CONTROL MODE switch (S5) to TEST. This wilI  
remove the control from service and allow it to operate  
without operating the high-voltage transfer switches.  
WARNING: Hazardous voltage. Solidly ground  
!
all equipment. Failure to comply can result in  
2. Check LATCH RELAY STATUS TEST terminals (T-1,  
T-2) to ground (T-3). 120 Vac at T-1 indicates the con-  
trol is in Source I mode; 120 Vac at T-2 indicates the  
control is in Source II mode. Check if this agrees with  
the SOURCE PREFERENCE switch setting.  
death, severe personal injury, and equipment damage.  
T223.2  
General  
3. Remove preferred source voltage by unscrewing one  
of the phase fuses from the applicable source. The  
PREFERRED TO ALTERNATE TIMER will start.  
This troubleshooting guide is intended to assist in localiz-  
ing problems that may be encountered in the operation of  
the load-transfer scheme. After the problem area has  
been localized, general troubleshooting and circuit tracing  
techniques can be used to pinpoint the cause. A funda-  
mental understanding of the basic operation is essential  
in carrying out these troubleshooting procedures. (See  
Theory of Operation section.)  
4. When the timer runs out, the latch relay (R1) will  
transfer; indicated by a transfer of the 120 Vac signal  
at the test terminals.  
5. Replace the removed fuse to re-energize the pre-  
ferred source. The ALTERNATE TO PREFERRED  
TIMER will start.  
Schematic diagrams, Figures 16 and 17, are used as  
references throughout this guide. The physical location  
of the various circuit components and terminals are  
identified in Figure 27.  
IMPORTANT: If Control Mode Switch S5 is placed in  
the Normalposition, the S-control will place the high-  
voltage transfer switches into the configuration that is  
currently selected by the Source Preference Switch  
S4. This may result in an unintended transfer. Make  
sure the desired state of the high-voltage transfer  
switches match the setting of S4 before returning S5 to  
the Normalposition.  
Remove the Control from Service  
DANGER: Hazardous voltage. Contact with haz-  
!
ardous voltage will cause death or severe per-  
sonal injury. Follow all locally approved safety proce-  
dures when working around high and low voltage lines  
6. When the timer runs out, the latch relay (R1) will  
and equipment.  
G103.3  
transfer back to its original operating position.  
7. Return the CONTROL MODE switch (S5) to NOR-  
The following warning only applies to controls  
equipped with the Fault Block Accessory:  
MAL to return the control to service.  
WARNING: Hazardous Voltage. De-energize  
!
switchgear before attempting to disconnect con-  
trol cable from control. Failure to do so may result in  
contact with high voltage pulse (300V peak) from the  
CT protection circuit. Failure to de-energize switchgear  
can result in contact with high voltage, which will cause  
death or severe personal injury.  
G124.0  
1. De-energize Source I and Source II voltage.  
2. Disconnect cables from the control.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
SAFETY  
FOR LIFE  
S260-75-1  
No Preference Operation  
Indicating Lamps  
Although not essential to control operation, the indicating  
lamps provide useful operating information. All lamps are  
120 Vac operated half-wave through diodes.  
1. Set CONTROL MODE switch S5 to the TEST posi-  
tion. This will remove the control from service and  
allow operation without operating the high-voltage  
transfer switches.  
For a quick check of the lamp diodes, depress the LAMP  
TEST switch, S6. The two OPEN and two CLOSE lamps  
should glow with equal brilliance, the green appearing  
slightly less intense, and the SOURCE I ENERGIZED  
and SOURCE II ENERGIZED lamps should noticeably  
increase in brilliance (these lamps are energized from  
two phases, 120 degrees apart, instead of a single bus).  
2. Check the setting of the SOURCE PREFERENCE  
switch (S4). It should be in the center No Preference  
position.  
3. Check LATCH RELAY STATUS TEST terminals (T-1,  
T-2) to ground (T-3). 120 Vac at T-1 indicates the con-  
trol is in the Source I mode. 120 Vac at T-2 indicates  
the control is in the Source II mode.  
Note: The OPEN lamp circuit includes the impedance of  
the close coil or motor of the high-voltage switch  
actuator.  
4. Remove source voltage by unscrewing one of the  
phase fuses from Source I if T-1 is energized or from  
Source II if T-2 is energized. If a Source I fuse is  
removed, the PREFERRED TO ALTERNATE TIMER  
will start. If a Source II fuse is removed, the ALTER-  
NATE TO PREFERRED TIMER will start.  
Verification of Fuses  
Fuses can be checked on the front panel of the control.  
If the fuses are blown and require replacement, the white  
buttons on the front panel will show. Refer to item 15 in  
Figure 13 and Table 4.  
5. When the timer runs out, the latch relay (R1) will  
transfer as indicated by a transfer of the 120 Vac sig-  
nal at the test terminals.  
Advanced Troubleshooting  
IMPORTANT: The control should be removed from  
service prior to conducting the advanced troubleshoot-  
ing procedures.  
6. Replace the removed fuse to re-energize the power  
source. No timers will start and latch relay (R1) will  
not transfer.  
7. Unscrew one of the phase fuses from the other  
source. If a Source II fuse is removed, the ALTER-  
NATE TO PREFERRED TIMER will start. If a Source  
II phase fuse is removed, the PREFERRED TO  
ALTERNATE TIMER will start.  
Use the output of the control procedure to determine if  
the problem lies in the control or the high-voltage switch-  
es. If the conditions of the output procedure are satisfac-  
tory, test the high-voltage switch. If the conditions of the  
output procedure are unsatisfactory, test the manual con-  
trol functions. If the conditions of the manual control func-  
tions procedure are satisfactory, test the automatic con-  
trol functions.  
8. When the timer runs out, the latch relay (R1) will  
transfer back to its original operating position, again  
indicated by a transfer of the 120 Vac signal at the  
test terminals.  
9. Replace the removed fuse to re-energize the power  
source. No timers will start and latch relay (R1) will  
not transfer.  
10. Place the CONTROL MODE switch (S5) to the normal  
position. If switch S5 is left in the TEST position, the S  
control will be inoperative on automatic operation.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions  
Output of the Control  
TABLE 5  
Continuity Check of High-Voltage Switches  
To determine if the problem is in the control or the high-  
voltage transfer switch, proceed as follows:  
Switch  
Ohmmeter Reading  
Receptacle  
Pin  
Type VR, VLR, VRV Standard Operator  
1. Disconnect the switches from the control.  
Switch Open  
Switch Closed  
2. Place OPERATION SELECTOR switch (S3) to  
MANUAL.  
B to C  
B to D  
B to E  
D to F  
Motor  
0
Trip Coil  
3. Place SOURCE PREFERENCE and RETURN  
0
0
MODE switch (S4) to NO PREF.  
4. With the control energized, check the voltage to  
ground at the Transfer Switch Operatorsterminal  
board, TB1, per Table 6.  
Type VR, VLR, VRV Quick Close Operator  
A to D  
B to C  
B to D  
B to E  
D to F  
*
Quick Close Coil  
0
Trip Coil  
5. If these output voltages are obtained, check the high-  
voltage switch. If the output voltages are not  
obtained, check the manual control functions.  
0
0
Type TSC  
B to C  
B to F  
B to E  
D to F  
Motor  
Motor  
0
High-Voltage Switch  
0
Normal control output at TB1 but failure to operate sug-  
gests a malfunctioning switch.  
Type PST-6 with C Interrupter #1  
1. With an ohmmeter, check the resistance between  
E to R  
M to N  
P to E  
S to V  
T to U  
Close Coil  
points of the high-voltage switch actuator per Table 5.  
*
0
0
2. If the control circuit of the switch operator checks out,  
the trouble may be mechanical. Refer to the mainte-  
nance manual for the switch.  
Trip Coil  
Type PST-6 with C Interrupter #2  
B to C  
D to E  
E to F  
G to K  
H to J  
0
*
Close Coil  
0
Trip Coil  
Type PST-9 with C Interrupter #1  
E to F  
A to C  
C to E  
B to C  
C to D  
Type PST-9 with C Interrupter #2  
L to M  
G to J  
J to L  
H to J  
J to K  
0
0
*
Trip Coil  
Close Coil  
* Will read motor resistance if closing spring is not charged, will  
read infinity if closing spring is charged.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
SAFETY  
FOR LIFE  
S260-75-1  
Manual Control Functions  
Automatic Control Functions  
Abnormal output readings at TB1 indicate a malfunctioning  
control. This procedure describes the terminal functions  
under manual direction and suggests areas for investigation.  
The control may operate properly by manual direction but  
malfunction in its automatic mode. The automatic section  
responds to the positions of R2 and R6 in conjunction  
with the selected operating mode as set on S4, the  
SOURCE PREFERENCE and RETURN MODE switch.  
Its output is the single-coil latching relay, R1.  
1. Terminals 11 and 21 provide the power to charge the  
springs in the switch actuator and are constantly  
energized. If terminals 11 and 21 are not energized,  
the transfer bus is not energized.  
1. R2 is energized from phase A of Source I through  
N.O. contacts of R9 in phase B and R10 in phase C.  
The action of R2 can be observed through its trans-  
parent cover and can be checked electrically across  
tabs 31 and 32 on the relay tie board which connect to  
a N.C. contact of the relay.  
A. Make sure that either phase B of the preferred  
source or phase Y of the alternate source is ener-  
gized. These phases supply the transfer bus.  
Measure beyond the fuses.  
B. Relays R7 and R11 control power to the transfer  
bus. Relay R7 picks up when phase Y is ener-  
gized; Relay R11 picks up if phase B is energized  
and phase Y is deenergized.  
2. R6 is similarly energized from phase X of Source II  
through R7 in phase Y, and R8 in phase Z. Tabs 41  
and 42 connect to a N.C. contact of R6.  
3. Operation of the appropriate time delay relay can be  
2. Terminals 15 and 25 provide 120 Vac closing power  
(15 closes Source I switch, and 25 closes Source II  
switch). Terminals 13 and 23 provide 120 Vac open-  
ing power (13 opens Source I switch and 23 opens  
Source II switch).  
checked by verifying that the LED timer is illuminated.  
4. The single-coil latching relay (R1) is electrically oper-  
ated and magnetically held. It is latched directly from  
the 120 Vac transfer bus through diode DL in the auto-  
matic mode or diode DL1 in the manual mode. It is  
reset through the 15 K ohm resistor and either diodes  
DR or DR1.  
A. Terminals 13, 23, 15 and 25 are energized from  
the transfer bus through the MANUAL OPER.  
switches, S1 and S2.  
5. With the control in an automatic mode of operation,  
the position of the latching relay can be determined at  
the Latching Relay Test jacks (T1, T2, T3) on the front  
panel of the control.  
(1) If the control is equipped with the fault block  
accessory, normally closed contacts of the fault  
block relay (RY1) are connected between tabs  
FP and FR of the relay tie board to complete the  
circuit to terminal 15 and between tabs FS and  
FT to complete the circuit to terminal 25.  
A. When 120 Vac is present between T1 and T3, the  
relay is in the latchedposition and the control  
seeks to connect the load to Source I.  
(2) If the control does not use the fault block  
accessory, jumpers are provided between tabs  
FP and FR and FS and FT of the relay tie board  
to complete the closing power circuits to the  
transfer switches.  
B. When 120 Vac is present between T2 and T3, the  
relay is in the resetposition and the control seeks  
to connect the load to Source II.  
C. If the latching relay assumes the expected position  
after the proper time delay, the automatic section  
of the control is functioning properly.  
3. Terminals 14 and 24 are grounded by an acontact  
(N.O.) in the H.V. transfer switches to energize relays  
R4 and R5 respectively during the openinghalf of a  
parallel return transfer.  
4. Terminals 16 and 26 are energized (120  
TABLE 6  
Voltage Readings on TB1  
Vac) on the closinghalf of a non-parallel  
return transfer. They are energized from a  
bcontact (N.C.) in the H.V. transfer switch-  
es; 16 is energized from Source I high- volt-  
age switch and 26 is energized from Source  
II high-voltage switch.  
Voltage to Ground  
MANUAL OPER.  
SOURCE I  
MANUAL OPER.  
SOURCE II  
Term  
on  
Switch (S1)  
Switch (S2)  
TB1  
Quiescent  
Close  
Open  
Close  
Open  
11  
15  
14  
13  
16  
120 Vac  
170 Vdc*  
170 Vdc*  
0
120 Vac  
120 Vac  
120 Vac  
120 Vac  
120 Vac 170 Vdc* 170 Vdc* 170 Vdc*  
170 Vdc* 170 Vdc* 170 Vdc* 170 Vdc*  
0
0
120 Vac  
0
0
0
0
0
0
26  
23  
24  
25  
21  
0
0
0
0
0
0
0
0
0
120 Vac  
170 Vdc*  
170 Vdc*  
120 Vac  
170 Vdc* 170 Vdc* 170 Vdc* 170 Vdc*  
170 Vdc* 170 Vdc* 120 Vac 170 Vdc*  
120 Vac  
120 Vac  
120 Vac  
120 Vac  
* Rectified 120 Vac impressed on capacitor. Drops to 0 if LAMP TEST  
switch (S6) is depressed.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions  
SAFETY  
FOR LIFE  
Figure 16a.  
Schematic diagram basic S control operating Types VR, VLR, VRV, TSC, or PST-9 switchgear (page 1 of 2).  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
SAFETY  
FOR LIFE  
S260-75-1  
Figure 16b.  
Schematic diagram basic S control operating Types VR, VLR, VRV, TSC, or PST-9 switchgear (page 2 of 2).  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions  
Figure 17a.  
Schematic diagram for Type S control operating Type PST-6 switchgear (page 1 of 2).  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
SAFETY  
FOR LIFE  
S260-75-1  
Figure 17a.  
Schematic diagram for Type S control operating Type PST-6 switchgear (page 2 of 2).  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions  
FAULT BLOCK ACCESSORY  
(Applicable to VR, VLR, VRV, TSC, CS, and PST-6 switchgear.)  
The fault block accessory is mounted in the upper right  
corner of the back panel of the control, Figure 18. Controls  
and instructions for operating the accessory are located  
on the front panel above the input fuses, Figure 19.  
To prevent the fault block accessory from being activated  
due to inrush current that may occur as a result of the  
backup opening and closing, an inrush restraint feature is  
built into the accessory logic. Upon loss of the preferred  
source voltage, the inrush restraint operates to increase  
the phase fault actuating level by a predetermined multi-  
ple for a predetermined time after voltage is restored.  
Simultaneously, ground fault current detection is blocked  
completely for the same time interval. When the time runs  
out, both the phase and ground current actuating levels  
return to their normal values.  
General Description  
In response to fault current above preselected phase or  
ground levels, the accessory is activated and latched to  
disable both high-voltage switches. Thus a load-side fault  
followed by loss of potential will result in partial load  
transfer opening the connected source but not closing  
the faulted load into the alternate feeder.  
To operate the fault block accessory, the Source I and  
Source II high-voltage switches must be equipped with  
1000:1 ratio current transformers to monitor the magni-  
tude of the line current and an auxiliary acontact. The  
bushing current transformers and associated wiring are  
provided as a factory-installed accessory to the high-volt-  
age switch.  
The accessory must be manually reset at the control  
panel to restore service to the load. If activation of the  
fault block accessory is due to a temporary fault (pre-  
ferred source voltage is restored before the transfer delay  
timer runs out), line current of 5 Amps, or more, flowing  
through the high-voltage switch will automatically reset  
the accessory in approximately 10 to 15 seconds.  
Accessory Settings  
The selected phase and ground fault  
ACTUATING LEVEL PRINTED  
CIRCUIT CARD (FIGURE 18)  
actuating levels should be greater  
than any peak load phase current or  
zero-sequence (ground) current, but  
less than the trip setting of the back-  
up protective device. A general rec-  
ommendation is to set the phase  
and ground actuating levels to  
approximately 80% of the phase and  
ground trip levels of the backup.  
TERMINAL BLOCK FOR  
EXTERNAL CONNECTIONS  
The phase fault current minimum  
actuating level is determined by a  
plug-in circuit card, Figure 20.  
Cards are available for 80, 112,  
160, 224, 320 and 448 Amp actuat-  
ing levels. The ground fault current  
minimum actuating level is deter-  
mined by a resistor cartridge that  
clips on to the phase card.  
Cartridges are available for 10, 14,  
20, 28, 40, 56, 80, 112, 160, 224,  
320 and 448 Amp actuating levels.  
RAISED FAULT LEVEL  
DURATION TIMER  
020080KM  
Figure 18.  
Fault block accessory mounted in upper-right corner of the back panel.  
INSTRUCTION LABEL  
Provides instructions  
for resetting the  
fault block accessory.  
FAULT BLOCK  
RESET SWITCH (S7)  
Reactivates the S control  
after a fault block operation.  
OPERATED SWITCH  
Indicates that the fault block  
accessory has operated.  
020077KM  
Figure 19.  
Fault block accessory controls and operating instructions plate.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
SAFETY  
FOR LIFE  
S260-75-1  
The actuating level multiplier for the inrush restraint fea-  
ture for phase faults is set by a jumper wire connected  
to a tab on the circuit card. Tabs are provided for X1, X2,  
X4, X6, X8 and BLOCK settings. The duration of the  
raised level is set by a knob on the top of the timer  
(Figure 18). The timer is infinitely adjustable 0.1 to 5.0  
seconds. No settings are required for ground inrush  
since it is automatically blocked for the duration the  
phase level is raised.  
Theory of Operation  
Fault Block Accessory  
The fault block accessory prevents automatic closure  
into the alternate source when loss of preferred source  
results from a fault on the load tap. The schematic dia-  
gram for the fault block accessory, Figure 21, is used as  
reference throughout this discussion.  
Overcurrent Sensing  
Operating Instructions  
The output of bushing current transformers in both the  
Source I and Source II high voltage switches are applied  
to the fault block accessory via terminals lA, IB, IC, IN  
and IX, IY, IZ, IN respectively. When the load current  
through the switch exceeds the phase or ground actuat-  
ing level selected, the relay contacts in the fault block  
accessory (contacts 7-8 and 10-11 of relay RY1-B),  
located in the closing circuits of both high voltage switch-  
es, are opened. Subsequent closing of either switch is  
blocked in either the automatic or manual mode of the S  
control until the fault block accessory circuitry is reset.  
The FAULT BLOCK OPERATED lamp on the front panel  
of the control, Figure 19, will light when the fault block  
accessory is activated. To reset the accessory:  
1. Move the OPERATION SELECTOR switch (S3) to  
MANUAL.  
2. Depress and hold the RESET switch (S7) until the  
lamp goes out, (approximately 6-10 seconds) indicat-  
ing the accessory has reset.  
3. To restore service, return the OPERATION SELEC-  
TOR switch (S3) to AUTOMATIC; the preferred  
source high voltage switch will close.  
Phase Fault Operation  
Referring to the accessory schematic diagram, Figure  
21, the phase currents are rectified by the diode bridges  
D103 through D116. Current out of the positive side of  
the bridge passes through diode D127 and divides into  
two parallel circuits. One circuit consists of zener D123  
and the minimum phase actuating resistor R301 to the  
other side of the bridge. The other circuit consists of nor-  
mally closed contact (1516) of latching relay RY1, diode  
D201, and capacitor C201 to the other side of the bridge.  
C201, charged by load or fault current, provides tripping  
energy for RY1.  
OR  
Operate either the MANUAL OPER. SOURCE I switch  
(S1) or the MANUAL OPER. SOURCE II Switch (S2),  
as applicable, to restore service manually.  
Note: Instructions for operating the fault block accessory  
also are printed on the front panel of the control  
(Figure 19).  
The current through R301 produces a voltage drop pro-  
portional to the line current which is impressed across  
the series resistor string R101, R102, and R103. A por-  
tion of this voltage is applied through diode D120 to the  
base of transistor Q201.  
When this voltage exceeds the break-down voltage of  
zener D212 and the base emitter junctions of Q201 and  
Q202, Q201 will conduct causing Q204 to conduct. In  
turn, Q204 provides the gating current to turn on the SCR  
(Q206) to discharge capacitor C201 through the trip coil  
of the latching relay RY1. Contacts 10-11 and 7-8 of RY1  
(in series with the close coils of the high voltage switch-  
es) open to prevent the high voltage switches from clos-  
ing until the fault block circuitry is reset.  
PHASE CURRENT LEVEL  
MULTIPLIER SETTING FOR  
INRUSH CURRENT RESTRAINT.  
An important feature of this accessory is that a trip signal  
cannot be initiated until there is sufficient charge on C201  
to activate the trip coil of RY1. Transistors Q201 and  
Q204, effectively in series across C201, cannot conduct  
until the voltage across C201 is sufficient to break-down  
zener diodes D211 and D212.  
GROUND-  
ACTUATING  
CURRENT  
RESISTOR  
CLIPS TO THE  
PHASE CARD  
020078KM  
Figure 20.  
Phase fault current actuating level printed circuit card.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions  
SOURCE I  
H.V. SWITCH  
AØ  
BØ  
CØ  
AØ  
BØ  
CØ  
SOURCE II  
H.V. SWITCH  
PART OF  
RESISTOR BOARD  
+
GROUND ACTUATING  
RESISTOR  
R306  
a2  
SOURCE II  
H.V. SWITCH  
a1  
SOURCE I  
H.V. SWITCH  
Figure 21a.  
Schematic diagram fault block accessory (page 1 of 2).  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
SAFETY  
FOR LIFE  
S260-75-1  
MANUAL  
12  
S3  
8
V103  
4
AUTO  
11  
M
D26  
RY1  
(120V BUS)  
TRIP RESET BOARD  
14  
12  
RY1  
D201  
15  
17  
16  
F
D
N
FN  
TB4-1  
1
D203  
B
E
18  
1
R209  
47K  
+
R216  
47K  
L7  
C201  
150  
RY1  
TRIP  
COIL  
R210  
1K  
2
TB4-2  
2
Q204  
2N2905  
D
H
D202  
C210  
0.1  
D201  
D211  
6.8V  
1N4736A  
+
2
C203  
5.6  
R204  
10K  
Q201  
TB4-3  
R211  
100K  
Q206  
C5V  
R218  
1K  
120V IN MANUAL  
Q202  
3
C208  
0.1  
200V  
1
3
5
TB4-4  
4
D209  
+
S7  
RESET  
3PST  
2
D212  
5.1V  
C204  
3.0  
+
C207  
1.0  
35V  
R203  
3.3K  
R208  
3.9K  
1N4733A  
MOMENTARY  
TM1-2  
TM1-3  
V
A
R214  
56K  
4
C205  
0.1  
R213  
1.8K  
R205  
100  
R212  
3.3MEG  
C206  
12  
+
Q203  
TM2-2  
TM2-3  
Q205  
2N6119  
Y
W
L
1
6
C209  
0.1  
200V  
D208  
R217  
47K  
RY1  
RESET  
COIL  
C202  
150  
R215  
47K  
R206  
68K  
R207  
680K  
+
D207  
T
19  
R202  
470  
D206  
D204  
FG  
G
R201  
6.8K-2W  
D205  
RY1  
RY1  
RY1  
LEGEND  
4
3
5
7
8
10  
11  
ACCESSORY TERMINAL BLOCK (TB5)  
ACCESSORY TIEBOARD TERMINAL  
RELAY PIN (RY1 & RY2)  
V
W
U
T
R
S
P
NO CONNECTIONS  
EDGE CONNECTOR TERMINAL  
(DIODE BOARD)  
FT  
FS  
FR  
FP  
(RESISTOR BOARD)  
(TRIP-RESET BOARD)  
TAB ON RELAY BOARD OF S CONTROL  
NOTE  
LATCH RELAY CONTACTS (RY1) SHOWN WITH  
RESET COIL LAST ENERGIZED  
UNLESS OTHERWISE NOTED:  
DIODES ARE 1N4004  
TB4 TERMINAL STRIP OF S CONTROL  
S3 & S7 TERMINALS  
TRANSISTORS ARE 2N2102  
RESISTORS ARE 1/2 WATT  
RESISTOR VALUES ARE IN OHMS  
CAPACITOR VALUES ARE IN MICRO-FARADS  
TM1 (PREFERRED TO ALTERNATE TIMER) AND  
TM2 (ALTERNATE TO PREFERRED TIMER) TERMINALS  
Figure 21b.  
Schematic diagram fault block accessory (page 2 of 2).  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions  
Ground Fault Operation  
Inrush Restraint Feature  
The ground current (the vector sum of the phase cur-  
rents) flows through the ground actuating resistor, R306,  
to produce a voltage across the primary of input trans-  
former TR1, proportional to the ground current. This volt-  
age is stepped-up, rectified, and impressed across the  
series resistor string R104, R105, R106 and R107. A por-  
tion of this voltage is applied to the base of Q201 through  
diode D119. From this point, ground and phase opera-  
tions use common circuitry described in the preceding  
Phase Fault operationdiscussion.  
The inrush restraint feature raises the actuating level of  
the fault block accessory by a multiple (or blocks its oper-  
ation entirely) for a period following restoration of source  
voltage or an automatic open transition transfer operation,  
to prevent inrush currents from activating the fault block.  
Relay RY2 is normally energized by the phase B or  
phase Y voltages from the S control via the aauxiliary  
contacts in the two high-voltage switches. When both B  
and Y phase voltages are lost due to operation of a back-  
up device or opening of the high-voltage switches, the  
coil of RY2 is de-energized, closing its contacts. Contact  
1-4 closes to insert a paralleling resistor across the  
phase actuating resistor R301, reducing its effective  
value and increasing the line current necessary to actu-  
ate Q201. Contact 5-8 of RY2 closes to short-out the sec-  
ondary of TR1, rendering the ground section operative.  
Reset Circuits  
Once actuated, the fault block accessory can be reset in  
either of two ways.  
ManuallyActuating the Reset Switch, S7, on the  
front panel of the S control, will apply 120 Vac to ter-  
minal G of the fault block accessory tie board. This  
voltage is rectified by diode D205 and applied to the  
reset timing circuit, which consists of R201, C206,  
and the programmable uni-junction (PUT) Q205. This  
voltage is also applied to capacitor C202, which pro-  
vides energy to the reset coil of latching relay RY1.  
When the voltage across C206 reaches the break-  
down voltage of the PUT, transistor Q203 is then  
turned on causing C202 to discharge through the  
reset coil of RY1. The relay transfers and the fault  
block accessory is now reset.  
Upon re-energization of either Phase B or Phase Y  
through closing of the backup devices or the closing of the  
high-voltage transfer switches, relay RY2 is energized.  
RY2 has a built-in time delay programmable by means of  
a knob in the top of the relay case. After the selected time  
delay has elapsed, N.C. contacts 1-4 and 5-6 open,  
returning the fauIt block accessory to normal operation.  
Note: S7 is energized only when the Operation Selector  
switch is in MANUAL.  
Automaticallyby load current  
below the minimum actuating  
level flowing through the high-  
voltage switch. The voltage  
developed by the load current is  
applied through contact 16-17 of  
RY1 to the reset timing circuit  
R207, C206, and Q205.When  
the voltage across C206 reach-  
es the breakdown voltage of the  
PUT, Q203 is then turned on  
causing C202 to discharge  
through the reset coil of RY1.  
The latching relay transfers and  
the fault block accessory is  
reset.  
Note: If the load current is above  
the actuating level of the  
accessory, both manual and  
automatic reset is defeated  
by Q202 which conducts to  
short-out the reset timing  
capacitor C206 through  
resistor R205.  
Figure 22.  
Test circuit for testing and troubleshooting the fault block accessory.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
SAFETY  
FOR LIFE  
S260-75-1  
Test Procedure and Troubleshooting  
Phase Minimum Actuating Current  
Testing Fault Block Operation  
WARNING: Hazardous voltage caused by back-  
!
feeding transformers. Isolate potential transform-  
IMPORTANT: When checking the phase minimum  
actuating current the ground fault sensing portion of  
the accessory must be disabled. Testing on an individ-  
ual phase basis without disabling ground fault sensing  
will cause the accessory to activate at the ground fault  
level.  
ers from source bushings using potential transformer  
dead-break disconnect switches located on the  
source-side panel. Failure to do so will result in risk of  
possible contact with high voltage at the source bush-  
ings, which may cause death or severe personal injury.  
T273.0  
1. Disable the ground sensing circuit by shorting the  
The operation of the fault block accessory can be  
checked by backfeeding a 500:5 (or other available ratio)  
current transformer, located in the primary loop of one  
phase of the preferred source high-voltage switch, from a  
variable 120 Vac source. The 500:5 ratio provides approx-  
imately 1 Amp of output test current for every 10 mA of  
input current. However, to eliminate error due to CT satu-  
ration, a separate metering CT and meter should be used  
to read the actual test current.  
ground fault resistor (Figure 22).  
2. Set the inrush current multiplier at X1.  
3. Close test circuit switches SW2 and SW3 to apply  
voltage to the control.  
The preferred source high-voltage switch (HV1) will  
close.  
4. Close test switch SW1 and slowly raise the test current  
until the FAULT BLOCK OPERATED light goes on.  
Test Circuit and Equipment  
The test current should be within the limits specified in  
Table 7. If FAULT BLOCK OPERATED light fails to come  
on at the expected level, proceed as follows:  
A suggested test setup is shown in Figure 22. If the con-  
trol is equipped with the plug and receptacle accessory,  
use the existing cables to interconnect the motor opera-  
tors of both high-voltage switches and the CT sensing  
circuits of the preferred source switch to the S control. If  
plugs and receptacles are not provided, wire the switch-  
es directly to the appropriate terminal blocks as shown in  
Figures 6 or 8.  
A. Check lamp with LAMP TEST switch (S6).  
B. Recheck calculations for proper meter reading.  
C. Is ground resistor cleanly shorted out?  
D. Did latch relay R1 transfer position?lamp is only  
an outward indication of relay position.  
E. Are all cable connections secure?  
F. Voltage from Accessory Tie Board, Tab D to  
Ground, Tab L, should be approximately 15 Vdc,  
average, at actuating level. If observed voltage is  
approximately 6 volts too low, trouble is probably in  
the Trip Reset Board; if voltage is too high, trouble  
is probably in either Diode or Resistor Boards.  
G. AC rms voltage from INto IA(or whatever  
phase is energized) should be about 17 V at actu-  
ating level. If correct voltage is observed, the CT  
input is correct.  
TABLE 7  
Test Current Values for Fault Block Accessory  
Actuating  
Current  
Setting  
Actuating Current Limits  
(Amps)  
(Amps)  
Minimum  
Maximum  
020082KM  
10  
14  
20  
9
12.6  
18  
11  
15.4  
22  
Figure 23.  
Disabling ground sensing circuit.  
28  
40  
56  
25.2  
36  
50.4  
50.8  
44  
61.6  
80  
112  
160  
72  
101  
144  
88  
123  
176  
274  
320  
448  
247  
250  
403  
301  
352  
493  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions  
5. Open SW1 and SW2 to simulate a backup clearing  
10. Repeat step 8 and 9 for the other high-voltage switch  
the fault.  
to complete checking all six CTs, their connections  
and polarity.  
The PREFERRED TO ALTERNATE TIMER will start  
and the preferred source high-voltage switch (HV1)  
will open when the timer runs out, but the alternate  
source high-voltage switch (HV2) will not close.  
11. Remove the shorting jumper from the ground fault  
resistor upon completion of phase testing.  
Ground Minimum Actuating Current  
If alternate source switch (HV2) closes and the latch  
relay (R1) contacts are not opening, check for open  
contact between Accessory Tie Board tabs P and R  
(Source I HV switch) and tabs S and T (Source II HV  
switch).  
When checking the ground minimum actuating current,  
the phase fault sensing portion of the accessory circuit  
must be disabled to prevent the possibility of erroneous  
test results. Proceed as follows:  
1. Disable the phase sensing circuit by placing a short-  
ing jumper from the BLOCK tab on the phase resistor  
card to tab L on the accessory tie-board (Figure 26).  
6. Place OPERATION SELECTOR SWITCH (S3) to  
manual, and operate MANUAL OPER SOURCE I  
switch (S1) and MANUAL OPER SOURCE II switch  
(S2) to CLOSE.  
2. Repeat steps 2 through 7 of the Phase Minimum  
Actuating Current test procedure.  
HV switch (HV1 or HV2) will not close.  
Automatic Reset of Fault Block  
If either switch closes and the latch relay (R1) con-  
tacts are not opening, check for open contact  
between Accessory Tie Board tabs P and R (Source  
I HV switch) and tabs S and T (Source II HV switch).  
1. Close test switches SW2 and SW3 to supply voltage  
to the control.  
The preferred source high-voltage switch (HV1) will  
close.  
7. Close test switch SW2 to restore preferred source  
voltage to the control. After the ALTERNATE TO  
PREFERRED TIMER runs out, reset the fault block  
accessory per instructions on the front panel.  
2. Close SW1 and raise the test current until the FAULT  
BLOCK OPERATED lamp lights indicating that fault  
block has been activated.  
The FAULT BLOCK OPERATED light will go out and  
the preferred source high-voltage switch will close.  
3. Open SW2 to simulate the back-up device opening  
and simultaneously open SW1 to clear the fault.  
If the FAULT BLOCK OPERATED light does not go  
out, the problem is most likely in the TRIP RESET  
BOARD.  
The PREFERRED TO ALTERNATE TIMER will start  
to run.  
4. Close SW2 to simulate reclosing of Source 1 back-  
up device. Quickly close SW1 and raise the test cur-  
rent to greater than 5 Amps but less than ground  
actuating level.  
Follow steps 8 through 11 to conduct a complete check  
involving all the phases of both high-voltage switches.  
8. Connect the phases in series as shown in Figure 24  
The FAULT BLOCK OPERATED lamp will go out in  
about 10-15 seconds indicating the accessory has  
reset.  
and retest.  
Because of the series hook-up, pickup should occur  
at 1/2 the actuating current setting.  
If FAULT BLOCK OPERATED lamp does not go out,  
the trouble is most likely in the Trip-Reset board  
(assuming the previous tests had passed).  
If pickup current is other than 1/2 of setting, the polar-  
ity of a CT could be reversed.  
9. Connect another two phases in series as shown in  
Figure 25 and retest.  
Results should be the same as in preceding step 8.  
JUMPER  
A
A
JUMPER  
Figure 24.  
Test Connections for Step 8.  
Figure 25.  
Test Connections for Step 9.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
SAFETY  
FOR LIFE  
S260-75-1  
Inrush Restraint  
If FAULT BLOCK OPERATED lamp does not light  
immediately, then  
The inrush-restraint feature prevents inrush currents  
above the minimum actuating level from actuating the  
accessory. This is accomplished by raising the phase  
actuating level by some multiple for a predetermined time  
after service is restored. Ground actuating level detection  
is blocked for the duration of the raised phase actuating  
level. Proceed as follows:  
A. Recalculate expected current.  
B. Verify that jumper on resistor board is on correct  
tab.  
If FAULT BLOCK OPERATED lamp still does not  
light immediately, the resistor board may be defec-  
tive. Contact your Cooper Power Systems represen-  
tative.  
1. Disable the ground sensing circuit by shorting the  
ground fault resistor (Figure 26).  
13. Remove the shorting jumper from the ground fault  
2. Set the inrush-restraining multiplier on the phase actu-  
ating card and the raised fault-level duration on the  
timer to the values at which they are to be checked.  
actuating cartridge upon completion of the test.  
3. With the preferred source high-voltage switch (HV1)  
closed, close test switch SW1 and raise the equiva-  
lent test current to a value above the maximum actu-  
ating level for the setting, but below the multiplied set-  
ting. (See Table 7 for maximum current test values.)  
BLOCKTAB  
4. Without disturbing this current setting, open SW1.  
5. Close test circuit switches SW2 and SW3 to apply  
voltage to the control.  
6. Momentarily close and open SW1 before the raised  
duration timer runs out, to simulate an inrush current.  
The FAULT BLOCK OPERATED lamp will not light.  
If the FAULT BLOCK OPERATED lamp does light,  
proceed as follows:  
A. Recheck current calculations. (Test current should  
LTAB  
exceed actuation level but be less than inrush level.)  
020083KM  
Figure 26.  
Disabling phase sensing.  
B. Check if momentary faults were applied before  
timer elapsed.  
Return the Control to Service  
C. Check if timing relay picked up after either HV1 or  
HV2 was closed. Check presence or absence of 120  
Vac at Accessory Tie Board terminal 17 when HV1  
operates and terminal 28 when HV2 operates.  
CAUTION: Equipment misoperation. Do not  
!
energize this equipment until all control settings  
have been properly programmed and verified. Refer to  
the Control Programming and Operation section of this  
manual for programming procedures. Failure to com-  
ply can result in misoperation (unintended operation),  
D. Check for trouble in delay relay contacts or resis-  
tor board.  
7. Close SW1 and leave closed to simulate a perma-  
equipment damage, and personal injury.  
G118.1  
nent fault on the load side.  
The FAULT BLOCK OPERATED lamp will light after  
the raised duration timer runs out.  
CAUTION: Equipment misoperation. Source I and  
Source II high voltage switches can be paralleled in the  
manual operation mode even if SOURCE PREFER-  
ENCE switch, S4, is set for NP (non-parallel opera-  
tion). Make sure both sources are in synchronism if a  
manual parallel operation is to be performed. Failure to  
comply can result in misoperation (unintended opera-  
If FAULT BLOCK OPERATED lamp does not light,  
the problems are similar to step 6 above.  
8. Open switches SW2 and SW3 to remove voltage  
from the accessory.  
9. Raise the test current to a value just above the raised  
tion) and equipment damage.  
T304.0  
multiple value.  
10. Without disturbing this current setting, open SW1.  
1. The control must be programmed with all the neces-  
sary operating settings and verified by the appropri-  
ate personnel prior to operation with energized  
switchgear.  
11. Again close switches SW2 and SW3 to apply voltage  
to the control.  
12. Close SW1 to simulate a high-level fault on the load  
2. Verify status of high voltage switches according to  
side of the switch.  
system requirements.  
The FAULT BLOCK OPERATED lamp will light imme-  
diately indicating the fault is greater than the inrush  
current restraining setting.  
3. Reconnect cables and ground the control.  
4. Apply Source I and Source II voltage to the control.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions  
WIRING TABLES  
Tables 21 through 40 identify the  
point-to-point wiring between  
circuit components.  
Tables 3640 apply to S Controls  
with the Fault Block Accessory.  
The physical location of the cir-  
cuit components and their termi-  
nals identification are shown in  
Figure 27.  
Figure 27.  
Location of circuit components wiring terminal identification.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
SAFETY  
FOR LIFE  
S260-75-1  
TABLE 8  
TABLE 10  
TABLE 12  
A”  
Surge Protector Circuit Board  
TB1  
Output Terminal Block  
TB3  
Terminal Strip  
To  
From  
To  
Color  
BRN  
ORG  
GRN  
WHT  
From  
To  
Color  
From  
1
Color  
Motor Lead  
YEL  
Motor Lead  
WHT  
Motor Lead  
GRY  
A
B
C
G
FU-A-1  
FU-B-1  
FU-C-1  
Stud on  
Cabinet  
TB1-G2  
Screw on  
Back Panel  
TB1-G1  
TB2-G2  
WHT  
WHT  
TM2-8  
S6-4  
TM2-7  
S4(K-8)  
TM1-7  
S4(J-4)  
TM1-8  
S6-4  
G1  
G2  
2
3
4
WHT  
WHT  
R-1  
TB1-21  
A-11  
BLK  
BLK  
BRN  
X
Y
Z
11  
13  
14  
FU-X-1  
FU-Y-1  
FU-Z-1  
TB1-11  
TB1-13  
VIO  
WHT  
BRN/WHT  
BRN  
11  
Motor Lead  
GRN  
S1-3  
A-13  
R-47  
S4(F-C)  
A-14  
BLK  
YEL  
BLK  
RED  
ORG  
13  
14  
TABLE 13  
YEL  
ORG  
ORG  
TB1-14  
RA(B-7)*  
TB4  
Terminal Strip  
R-FR  
D-15  
A-15  
S3-2  
A-16  
TB1-11  
A-21  
S2-3  
A-23  
BLU  
BLU  
RED  
YEL  
GRN  
BLK  
BLK  
WHT  
VIO  
BRN  
GRY  
15  
16  
21  
23  
24  
TB1-15  
TB1-16  
TB1-21  
TB1-23  
TB1-24  
RA(A-7)*  
RED  
GRN  
BLK  
VIO  
GRY  
GRY  
From  
To  
Color  
15  
16  
21  
23  
24  
D-L7  
R-FN  
L7-1*  
T3  
L7-2*  
S3-8*  
S1-2  
S7-1*  
R-FG  
S7-2*  
ORG  
GRN  
BRN  
BRN  
RED  
ORG  
BRN  
BRN  
YEL  
RED  
1
2
3
4
25  
26  
TB1-25  
TB1-26  
WHT  
BLU  
S4(E-C)  
A-24  
R-FT  
A-25  
D-25  
S3-3  
A-26  
GRN  
WHT  
GRN  
ORG  
BLU  
TABLE 9  
25  
26  
*Fault Block Accessory Connections  
D”  
Diodes Circuit Board  
TABLE 14  
From  
I
II  
G
To  
S6-1  
S6-10  
S6-7  
L3-2  
L4-2  
Color  
RED  
BRN  
BRN  
BRN  
RED  
ORG  
YEL  
ORG  
RED  
YEL  
FU-A  
Source I Phase A Fuse  
TABLE 11  
From  
1
To  
A-A  
TB2-A  
Color  
BRN  
RED  
TB2  
L3  
L4  
L5  
L6  
L7  
11  
14  
15  
24  
25  
Input Terminal Block  
2
R-A  
BRN  
From  
To  
Color  
L5-2  
L6-2  
A
B
C
FU-A-1  
FU-B-1  
FU-C-1  
RED  
YEL  
BLU  
TB4-1  
S6-5  
S4(F-C)  
TB1-15  
S4(E-C)  
TB1-25  
TABLE 15  
FU-B  
G1  
C-2  
TB2-G2  
WHT  
WHT  
Source I Phase B Fuse  
BLU  
GRN  
GRN  
From  
1
To  
A-B  
TB2-B  
Color  
ORG  
YEL  
G2  
TB1-G2  
TB2-G1  
WHT  
WHT  
X
Y
Z
FU-X-1  
FU-Y-1  
FU-Z-1  
GRY  
BLK  
RED/WHT  
2
R-B  
RED  
TABLE 16  
FU-C  
Source I Phase C Fuse  
From  
To  
Color  
1
A-C  
TB2-C  
GRN  
BLU  
2
R-C  
ORG  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions  
TABLE 22  
TABLE 23  
TABLE 17  
R”  
S5  
CONTROL MODE Switch  
FU-X  
Source II Phase X Fuse  
Relay Tie Board  
From  
A
B
To  
FU-A-2  
FU-B-2  
TB-5-18*  
FU-C-2  
S4(B-8)  
TB2(G-1)  
T-3  
FB-L*  
Color  
BRN  
RED  
BRN  
ORG  
ORG  
WHT  
ORG  
RED  
GRY  
BLU  
RED  
BLU  
RED  
YEL  
YEL  
VIO  
VIO  
YEL  
GRN  
RED  
BLU  
YEL  
BRN  
GRN  
YEL  
BRN  
BLK  
GRN  
BLU  
BLK  
BLU  
GRN  
BLK  
VIO  
From  
To  
S4(L-6)  
S4(M-8)  
R-4  
T-2  
T-1  
Color  
From  
To  
Color  
1
2
3
4
5
6
RED  
GRN  
RED  
ORG  
RED  
BRN  
1
A-X  
TB2-X  
VIO  
GRY  
2
R-X  
YEL  
C
D
TABLE 18  
G
R-5  
FU-Y  
Source II Phase Y Fuse  
J
K
L
L1  
M
P
S4(F-12)  
S4(D-8)  
TM1-3  
TABLE 24  
From  
To  
Color  
1
A-Y  
TB2-Y  
WHT  
BLK  
S6  
LAMP TEST Switch  
S1-4  
2
R-Y  
GRN  
From  
To  
D-I  
L1-1  
R-I  
Color  
RED  
BRN  
S4(D-12)  
S4(B-12)  
TM1-6  
S2-4  
S4(E-2)  
FU-X-2  
FU-Y-2  
TB5-27*  
FU-Z-2  
TB4-4  
FB-G*  
TB4-1  
FB-N*  
S4(A-C)  
R-FR**  
FB-P*  
TB1-15  
R-FP**  
FB-R  
S4(C-C)  
R-FT**  
FB-S*  
1
2
3
R
TABLE 19  
BRN/WHT  
R1  
W
X
FU-Z  
T-3  
TB3-4  
TB3-1  
ORG  
GRN  
YEL  
Source II Phase Z Fuse  
4
From  
To  
Color  
Y
1
A-Z  
TB2-Z  
BRN/WHT  
RED/WHT  
5
6
D-11  
RED  
Z
FG  
2
R-Z  
BLU  
7
8
9
D-G  
SW3-5  
BRN  
BLU  
FN  
FP  
FR  
FS  
FT  
TABLE 20  
10  
11  
12  
D-II  
L2-1  
R-II  
BRN  
RED  
GRY  
TM1  
PREFERRED TO ALTERNATE TIMER  
From  
To  
Color  
1
R-33  
TM2-6  
ORG  
ORG  
TABLE 25  
L1  
2
3
TB3-4  
R-R  
TM2-8  
BLK  
YEL  
YEL  
SOURCE I ENERGIZED Lamp  
From  
1
2
To  
S6-2  
L2-2  
Color  
BRN  
ORG  
4
5
TB1-25  
R-FS**  
FB-T*  
GRN  
BLK  
GRY  
R-43  
TM2-1  
S7-8*  
BRN  
BRN  
BLU  
J1  
J2  
J3  
J4  
I
II  
4
Used with  
6
7
8
TABLE 26  
capacitor  
voltage sensing  
accessory  
L2  
TB3-3  
BLK  
SOURCE II ENERGIZED Lamp  
TB2-3  
R-L  
S7-7*  
RED  
RED  
GRN  
S6-3  
S6-12  
S5-3  
S5-6  
S3-5  
TB1-11  
FB-M*  
L3-1  
BRN/WHT  
From  
To  
Color  
GRY  
RED  
BRN  
RED  
BLK  
ORG  
VIO  
BRN  
BLK  
WHT  
ORG  
ORG  
GRN  
1
2
R-II  
L1-2  
T3  
GRY  
ORG  
YEL  
5
* Fault Block Accessory Connections  
11  
TABLE 21  
TABLE 27  
12  
22  
31  
32  
33  
34  
35  
41  
42  
43  
44  
45  
47  
48  
TM2  
L3  
S3-1  
ALTERNATE TO PREFERRED TIMER  
SWITCH I OPEN Lamp  
S4(G-6)  
S4(G-2)  
TM1-5  
S4(J-C)  
S4(L-C)  
S4(H-8) BRN/WHT  
S4(H-12) RED/WHT  
TM1-2  
S4(K-C)  
S4(M-C)  
TB1-13  
S4(C-6)  
From  
To  
TM16  
TB3-1  
TM1-8  
Color  
BRN  
BLK  
RED  
From  
To  
Color  
1
2
3
4
5
6
1
R-12  
L4-1  
VIO  
VIO  
2
D-L3  
BRN  
TABLE 28  
BRN  
YEL  
BLU  
BLK  
GRY  
L4  
TM1-1  
S7-4*  
ORG  
ORG  
SWITCH I CLOSED Lamp  
From  
To  
Color  
7
8
TB3-2  
TM1-3  
S7-5*  
BLK  
YEL  
YEL  
1
L5-1  
L3-1  
VIO  
VIO  
* Fault Block Accessory Connections  
** Omit jumpers if fault block included.  
2
D-L4  
RED  
* Fault Block Accessory Connections  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
SAFETY  
FOR LIFE  
S260-75-1  
TABLE 29  
TABLE 30  
S4  
L5  
SWITCH II OPEN Lamp  
SOURCE PREFERENCE & RETURN MODE Switch  
From  
A-C  
To  
Color  
BRN  
BRN  
VIO  
From  
G-4  
G-5  
G-6  
H-C  
To  
R-32  
R-31  
Color  
WHT  
BLK  
From  
1
To  
L6-1  
L4-1  
Color  
VIO  
VIO  
R-FP  
S1-1  
R-38  
A-2  
A-3  
A-4  
A-5  
A-6  
B-C  
B-8  
B-9  
B-10  
B-11  
B-12  
C-C  
2
D-L5  
ORG  
S3-5  
S4(G-C)  
R-41  
VIO  
Bare  
BRN/WHT  
TABLE 31  
H-8  
H-9  
H-10  
H-11  
H-12  
J-C  
J-2  
J-3  
J-4  
L6  
SWITCH II CLOSED Lamp  
From  
1
2
S1-3  
R-D  
ORG  
ORG  
To  
L5-1  
D-L6  
Color  
VIO  
YEL  
R-42  
RED/WHT  
R-34  
S4(K-12)  
ORG  
Bare  
R-P  
R-FS  
S2-1  
YEL  
GRN  
YEL  
TABLE 32  
S4(K-12)  
TB3-3  
S4(K-10)  
Bare  
GRY  
Bare  
S1  
MANUAL OPER. SOURCE I Switch  
C-2  
C-3  
J-5  
J-6  
From  
To  
Color  
1
S3-7  
VIO  
C-4  
C-5  
C-6  
D-C  
D-8  
K-C  
K-8  
K-9  
K-10  
K-11  
K-12  
L-C  
L-2  
L-3  
L-4  
L-5  
L-6  
R-44  
TB3-2  
YEL  
WHT  
S4(A-C)  
BRN  
S2-2  
TB4-3  
S1-5  
TB1-13  
S4(B-C)  
R-L1  
S2-6  
S1-2  
S2-4  
RED  
BRN  
Bare  
BLK  
ORG  
BLU  
YEL  
Bare  
YEL  
R-48  
S2-3  
R-K  
GRY  
BLU  
BLU  
2
3
4
S4(J-6)  
S4(J-2)  
Bare  
Bare  
D-9  
D-10  
D-11  
D-12  
E-C  
R-M  
RED  
R-35  
GRN  
5
6
D-24  
TB1-24  
R-W  
D-14  
TB1-14  
R-J  
GRN  
BRN  
VIO  
YEL  
RED  
GRY  
Bare  
WHT  
S5-1  
RED  
E-2  
F-C  
M-C  
R-45  
T-2  
BLU  
BRN  
TABLE 33  
T1-T2-T3  
F-12  
G-C  
G-2  
G-3  
M-8  
M-9  
M-10  
LATCH RELAY STATUS TEST Terminal  
From  
T1  
S4(H-C)  
R-32  
S5-2  
GRN  
To  
S4(L-C)  
S5-5  
Color  
RED  
RED  
T2  
T3  
S4(M-C)  
S5-4  
L2-2  
S6-4  
TB4-2  
R-G  
BRN  
ORG  
YEL  
ORG  
BRN  
ORG  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions  
TABLE 38  
TABLE 34  
TABLE 36  
TB5”  
S2  
MANUAL OPER. SOURCE II Switch  
FB”  
Fault Block Accessory Tie Board  
Fault Block Accessory  
Terminal Block  
From  
To  
Color  
From  
IA  
IB  
IC  
IX  
IY  
IZ  
G
To  
Color  
BRN  
RED  
ORG  
YEL  
GRN  
BLU  
BRN  
BLK  
VIO  
From  
To  
FB-17  
RA(A-1)  
R-B  
RA(A-6)  
FB-IA  
FB-IB  
FB-IC  
FB-IN  
IN2  
Color  
1
S4(C-C)  
S3-6  
YEL  
BLU  
TB5-IA  
TB5-IB  
TB5-IC  
TB5-IX  
TB5-IY  
TB5-IZ  
R-FG  
S3-12  
TB5-IN  
17  
GRY  
GRN  
S1-2  
S2-5  
S3-9  
TB1-23  
S4(D-C)  
RED  
Bare  
GRN  
WHT  
BLU  
18  
BRN  
BRN  
2
3
4
IA  
IB  
IC  
BRN  
RED  
ORG  
R-R1  
S1-6  
VIO  
YEL  
D
IN1  
VIO  
BLK  
5
6
S2-2  
S1-4  
Bare  
YEL  
IN  
W
U
IN2  
IX  
IY  
IN1  
BLK  
YEL  
GRN  
BLU  
FB-IX  
FB-IY  
FB-IZ  
R-Y  
RA(B-6)  
TABLE 35  
S
P
R-FS  
R-FP  
VIO  
GRN  
IZ  
S3  
27  
RED  
RED  
OPERATION SELECTOR SWITCH  
M
R-11  
RA(A-2)  
ORG  
BLK  
From  
To  
R-22  
TB1-16  
TB1-26  
Color  
BRN  
YEL  
ORG  
28  
FB-28  
RA(B-1)  
WHT  
WHT  
17  
28  
V
TB5-17  
TB5-28  
GRY  
WHT  
1
2
3
4
TABLE 39  
T
R-FT  
R-FR  
R-FN  
R-G  
GRY  
BLU  
YEL  
RED  
R
N
L
S7  
R-11  
S4(H-C)  
S6-8  
RED  
VIO  
BLU  
Fault Block RESET Switch  
5
From  
To  
Color  
BRN  
RED  
ORG  
YEL  
6
7
8
S2-1  
S1-1  
TB4-2*  
S2-2  
BLU  
VIO  
ORG  
GRN  
1
2
4
5
7
8
TB4-3  
TB4-4  
TM2-6  
TM2-8  
TM1-8  
TM1-6  
TABLE 37  
L7  
9
FAULT BLOCK OPERATED  
10  
11  
12  
GRN  
BLU  
From  
1
2
To  
TB4-1  
TB4-2  
Color  
BRN  
RED  
BLK  
FB-D*  
* Fault Block Accessory Connections  
TABLE 40  
RA”  
Fault Block Accessory Relay  
From  
A1  
A2  
To  
TB5-17  
FB-M  
Color  
GRN  
BLK  
A6  
A7  
B1  
B6  
TB5-18  
A-24  
TB5-28  
TB5-27  
A-14  
BRN  
GRY  
WHT  
RED  
ORG  
B7  
To assure correct receipt of any parts order, always  
include the control type and serial number. Because of  
Cooper Power Systemscontinuous improvement policy,  
there may be instances where parts furnished may not  
look exactly the same as the parts ordered.  
REPLACEMENT PARTS  
Parts listed and illustrated include only those parts and  
assemblies usually furnished for repair. Because of the  
ease, faster receipt, and greater economy of local  
acquisition, the wiring, wire end terminations, and  
common hardware parts are not included in the  
replacement parts listing.  
However, they will be completely interchangeable without  
any rework of the control. All parts carry the same war-  
ranty as the original control, i.e., against failure due to  
defects in material or workmanship within one year from  
date of shipment.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
SAFETY  
FOR LIFE  
S260-75-1  
1, 2, 3, 5  
1, 2, 3, 4  
8
10  
8
1, 2, 3, 5  
1, 2, 3, 4  
9
12  
11  
11  
13  
14  
14  
1, 2, 3, 6  
1, 2, 3, 6  
15  
1, 2, 3, 7  
22  
16, 17  
18, 19, 20  
23  
20, 21  
020076KM  
Figure 28.  
Front panel replacement parts identification.  
Front Panel Replacement Parts List  
Index  
No.  
12  
13  
14  
15  
Catalog  
Index  
No.  
1
2
3
4
5
6
7
8
Catalog  
Number  
Description  
Number  
Qty.  
1
1
Description  
Lamp socket  
Socket fastener  
Lamp  
Lens, red (L4, L6)  
Lens, green (L3, L5)  
Lens, clear (L1, L2)  
Lens, amber (L7)  
Qty.  
Diode circuit board assembly KCN120SA  
Toggle switch, 4PDT (S3) KP2124A16  
Toggle switch, DPDT (S1, S2) KP2124A6  
Intermediate terminal strip  
KP2361A1  
KP2005A10  
KP2276A3  
KP2277A2  
KP2277A5  
KP2277A3  
KP2277A4  
6
6
6
2
2
2
1
2
1
1
2
(TB3, TB4)  
Rotary selector switch (S4)  
Switch knob  
Knob lock  
Lock backing  
Self tapping screw,  
6-32 x 1/2, stl  
Spacer  
Toggle switch, DPDT (35)  
Toggle switch, 3PST (S7)  
KP432ME  
KCN199S  
KCN149S1  
KP107RS  
KP497ME  
2
1
1
1
1
16  
17  
18  
19  
20  
Terminal post, black (T1, T2) KP2081A2  
9
10  
11  
Terminal post, white (T3)  
Toggle switch, 4PST (S6)  
Digital timer  
(TM1, TM2)  
KP2081A1  
KP2124A26  
K751515106050A  
KP3004A59  
KP2124A21  
KP2124A43  
2
1
1
1
21  
22  
23  
0.01 sec. to 99.9 hrs. range KP2159A2  
2
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions  
4, 6  
2, 6  
2, 6  
7
2, 6  
2, 6  
3, 6  
4, 6  
4, 6  
3, 6  
1, 5  
8
9
10  
11, 12  
020080KM  
Figure 29.  
Back panel replacement parts identification.  
Back Panel Replacement Parts List  
Index  
Catalog  
Number  
KP978ME  
No.  
Description  
Qty.  
1
1
Relay (R1)  
2
3
Relay (R8, R9, R10, R11)  
Relay (R4, R5)  
KP978ME  
KP978ME  
6
2
4
Relay (R2, R6, R7)  
KP978ME  
1
5
6
7
8
Relay retainer  
Relay retainer  
Relay tie board subassembly  
Surge protector board assembly  
K999904310339A  
K999904310339A  
KCN203S900  
KCN125SA  
1
9
1
1
9
Terminal block (TB2) (Consists  
of the following components)  
Terminal section  
KP999904150097A 12  
End piece  
KP999904150064A  
KP2076A50  
1
1
Marker strip  
10  
Terminal block (TB1) (Consists  
of the following components)  
Terminal section  
KP999904150097A 16  
End piece  
KP999904150064A  
KP2076A50  
1
1
Marker strip  
11  
12  
Fuse holder  
Fuse  
KP124S  
KP125S  
6
6
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
SAFETY  
FOR LIFE  
S260-75-1  
12  
13  
11  
6
4
5
14  
2
7
8
15  
10  
3
9
1
020081KM  
Figure 30.  
Fault block accessory replacement parts identification.  
Fault Block Accessory Replacement Parts List  
Index  
No.  
Catalog  
Number  
KCN144S1  
KCN141S1  
K881215332010Z  
KP2020A1  
Description  
Relay retainer bar  
Circuit board retainer bar  
Wing nut, 10-32, stl  
Elastic stop nut  
Phase actuating current circuit  
board (add proper current value to  
complete catalog number: 80, 112,  
160, 224, 320, 448, 640)  
Qty.  
1
1
1
1
1
2
3
4
5
KCN116S___  
1
6
Ground actuating  
current resistor  
KCN142S___  
1
(add proper current  
value to complete  
catalog number: 10, 14,  
20, 28, 40, 56, 80, 112,  
160, 224, 320, 448)  
Diode board  
Trip-reset board  
Relay (RY1)  
Time-delay relay (RY2)  
Transformer  
Zener diode  
7
8
9
10  
11  
12  
13  
14  
KCN114SA  
KCN112SA  
KP978ME  
K999904310339A  
KA234ME  
1
1
1
1
1
1
1
1
KP4011A12  
KCN110SA  
Tie board  
Terminal block (TB5)  
(Consists of the  
following components)  
Terminal section  
End piece  
KP999904150097A  
KP999904150064A  
KP2076A50  
16  
1
1
Marker strip  
15  
Barrier  
KCN167S1  
1
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions  
!
SAFETY  
FOR LIFE  
P.O. Box 1640  
©2002 Cooper Industries, Inc.  
Waukesha, WI 53187  
Kyle® is a registered trademark of Cooper Industries, Inc.  
KDL  
10/02  
KA2048-291 Rev: 02  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Clarion CD Player DRX9675z User Manual
Creative Saw WS 6613 User Manual
Dacor Microwave Oven DMT2420R User Manual
Danby Microwave Oven DMW7700WDB User Manual
Dell Server FE655WI User Manual
Dyson Vacuum Cleaner DCO1 User Manual
Everpure Water System A 11 User Manual
Exmark Lawn Aerator OCDWB01 User Manual
GE Monogram Refrigerator ZIRS360NXRH User Manual
GE Oven JKP16 User Manual