Carrier Furnace 58HDV User Manual

58HDV  
Direct Vent 4---Way Multipoise  
Condensing Gas Furnace  
95% Downflow / Horizontal Orientations  
93.5% Upflow Orientation  
Installation Instructions  
Special Venting Requirements for Installations in Canada  
Consignes spéciales pour l’installation de ventillation au Canada  
L’installation faite au Canada doit se conformer aux exigences du  
code CSA B149. Ce systême de ventillation doit se composer de  
tuyaux, raccords, ciments et apprêts conformes au ULC S636. La  
tuyauterie de ventillation des gaz, ses accessoires, le terminal  
concentrique mural ainsi que l’ensemble du drain de condensat  
extérieur ont été certifiés ULCS 636 pour l’application des  
composantes IPEX PVC qui sont certifiées à ce standard. Au  
Canada l’apprêt et le ciment doivent être du même manufacturier  
que le systême de ventillation -- IPEX Système 636, Apprêt  
PVC/CPVC. Mauve Violette pour conduit en évacuation des gaz et  
IPEX Système 636, ciment pour PVC pour conduit en évacuation  
des gaz, évalué CLASSE IIA, 65 deg. C. doit ëtre utilisé avec ce  
systèeme d’évacuation -- ne pas mélanger l’apprêt et le ciment d’un  
manufacturier avec le systême de ventillation d’un autre  
manufacturier. Bien suivre les indications du manufacturier lors de  
l’utilisation de l’apprêt et du ciment et ne pas utiliser ceux--ci si la  
date d’expiration est atteinte.  
L’opération sécuritaire, tel que définit par ULC S636, du système  
de ventilation est basé sur les instructions d’installation suivantes,  
ainsi que l’usage approprié de l’apprêt et ciment. Tout arrët feu et  
solin de toit utilisés avec ce système doivent être des matériaux  
listés UL. L’acceptation du standard Canadien CSA B419 est  
directement relié à l’installation conforme aux instructions ci-- haut  
mentionnées. Le standard Canadien recommande l’ inspection par  
un personel qualifié et ce, une fois par année.  
Installation in Canada must conform to the requirements of CSA  
B149 code. Vent systems must be composed of pipe, fittings,  
cements, and primers listed to ULC S636. The special vent fittings  
and accessory concentric vent termination kits and accessory  
external drain trap have been certified to ULC S636 for use with  
those IPEX PVC vent components which have been certified to this  
standard. In Canada, the primer and cement must be of the same  
manufacturer as the vent system -- IPEX System 636, PVC/CPVC  
Primer, Purple Violet for Flue Gas Venting and IPEX System 636,  
PVC Cement for Flue Gas Venting, rated Class IIA, 65 deg C. must  
be used with this venting system -- do not mix primers and cements  
from one manufacturer with a vent system from a different  
manufacturer. Follow the manufacturer’s instructions in the use of  
primer and cement and never use primer or cement beyond its  
expiration date.  
The safe operation, as defined by ULC S636, of the vent system is  
based on following these installation instructions, the vent system  
manufacturer’s installation instructions, and proper use of primer  
and cement. All fire stop and roof flashing used with this system  
must be UL listed material. Acceptability under Canadian standard  
CSA B149 is dependent upon full compliance with all installation  
instructions. Under this standard, it is recommended that the vent  
system be checked once a year by qualified service personnel.  
The authority having jurisdiction (gas inspection authority,  
municipal building department, fire department, etc) should be  
consulted before installation to determine the need to obtain a  
permit.  
Les autoritées ayant juridiction (inspecteurs de gas, inspecteurs en  
bâtiments, département des incendies, etc) devraient être consultées  
avant l’installation afin de déterminer si un permis est requis.  
TABLE OF CONTENTS  
PAGE  
IMPORTANT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . 2  
SAFE INSTALLATION REQUIREMENTS . . . . . . . . . . . . . . . 3  
COMBUSTION & VENTILATION AIR . . . . . . . . . . . . . . . . . . 8  
CONCENTRIC TERMINATION . . . . . . . . . . . . . . . . . . . . . . . 31  
GAS SUPPLY & PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33  
ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37  
DUCTWORK & FILTER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39  
CHECKS & ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . 42  
FURNACE MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . 44  
SEQUENCE OF OPERATION & DIAGNOSTICS . . . . . . . . . 46  
ama  
CERTIFIED  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: Read the entire instruction manual before starting the  
installation.  
suggestions which will result in enhanced installation, reliability, or  
operation.  
NOTE: Please retain these instructions with the furnace after  
installation for future reference.  
!
CAUTION  
CUT HAZARD  
SAFETY CONSIDERATIONS  
Failure to follow this caution may result in personal injury.  
Sheet metal parts may have sharp edges or burrs. Use care  
and wear appropriate protective clothing and gloves when  
handling parts.  
!
CAUTION  
FURNACE RELIABILITY HAZARD  
Improper installation or misapplication of furnace may  
require excessive servicing or cause premature component  
failure.  
SAFE INSTALLATION REQUIREMENTS  
Application of this furnace should be indoors with special  
attention given to vent sizing and material combustion air  
requirements, gas input rate, air temperature rise, unit  
leveling, and unit sizing.  
!
WARNING  
FIRE, EXPLOSION, AND ASPHYXIATION HAZARD  
Failure to follow this warning could result in personal injury  
or death.  
!
Improper adjustment, alteration, service, maintenance or  
installation could cause personal injury, death and/or property  
damage.  
WARNING  
FIRE, EXPLOSION, ELECTRICAL SHOCK AND  
CARBON MONOXIDE POISONING HAZARD  
Installation or repairs made by unqualified persons could result  
in hazards to you and others. Installation MUST conform to  
local codes or, in the absence of local codes, with codes of all  
governmental authorities having jurisdiction.  
Failure to follow this warning could result in personal  
injury, death, or property damage.  
Improper installation, adjustment, alteration, service,  
maintenance, or use can cause carbon monoxide poisoning,  
explosion, fire, electrical shock, or other conditions which  
may cause personal injury or property damage. Consult a  
qualified installer, service agency, local gas supplier, or your  
distributor or branch for information or assistance. The  
qualified installer or agency must use only  
factory--authorized and listed kits or accessories when  
modifying this product.  
The information contained in this manual is intended for use  
by a qualified service agency that is experienced in such work,  
is familiar with all precautions and safety procedures required  
in such work, and is equipped with the proper tools and test  
instruments.  
NOTE: This furnace is design--certified by the CSA International  
(formerly AGA and CGA) for installation in the United States and  
Canada. Refer to the appropriate codes, along with this manual, for  
proper installation.  
Installing and servicing heating equipment can be hazardous due to  
gas and electrical components. Only trained and qualified  
personnel should install, repair, or service heating equipment.  
Untrained personnel can perform basic maintenance functions such  
as cleaning and replacing air filters. All other operations must be  
performed by trained service personnel. When working on heating  
equipment, observe precautions in literature, on tags, and on labels  
attached to or shipped with unit and other safety precautions that  
may apply.  
S Use only the type of gas approved for this furnace (see Rating  
Plate on unit). Overfiring will result in failure of heat exchanger  
and cause dangerous operation. (Furnaces can be converted to  
Propane gas with approved kit.)  
S Install this furnace only in a location and position as specified in  
Installation” of these instructions.  
S Provide adequate combustion and ventilation air to the furnace as  
specified in “ Combustion and Ventilation Air” of these  
instructions.  
These instructions cover the minimum requirements and conform to  
existing national standards and safety codes. In some instances,  
these instructions exceed certain local codes and ordinances,  
especially those that may not have kept up with changing  
residential construction practices. We require these instructions as a  
minimum for a safe installation.  
S Combustion products must be discharged outdoors. Connect this  
furnace to an approved vent system only, as specified in “Vent  
and Combustion Air Piping” of these instructions.  
S Never test for gas leaks with an open flame. Use a commercially  
available soap solution made specifically for the detection of  
leaks to check all connections, as specified in “Gas Supply and  
Piping, Final Check” of these instructions.  
Wear safety glasses and work gloves. Have a fire extinguisher  
available during start--up and adjustment procedures and service  
calls.  
Recognize safety information. This is the safety--alert symbol  
.
When you see this symbol on the furnace and in instructions or  
manuals, be alert to the potential for personal injury.  
S Always install furnace to operate within the furnace’s intended  
temperature--rise range with a duct system which has an external  
static pressure within the allowable range, as specified in  
Technical Support Manual” of these instructions. See furnace  
rating plate.  
Understand the signal words DANGER, WARNING, and  
CAUTION. These words are used with the safety--alert symbol.  
DANGER identifies the most serious hazards which will result in  
severe personal injury or death. WARNING signifies a hazard  
which could result in personal injury or death. CAUTION is used  
to identify unsafe practices which may result in minor personal  
injury or product and property damage. NOTE is used to highlight  
S When a furnace is installed so that supply ducts carry air  
circulated by the furnace to areas outside the space containing the  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
furnace, the return air shall also be handled by a duct(s) sealed to  
the furnace casing and terminating outside the space containing  
the furnace.  
3. Never obstruct the vent grilles, or any ducts that provide  
air to the unit. Air must be provided for proper combustion  
and ventilation of flue gases.  
Frozen Water Pipe Hazard  
S A gas--fired furnace for installation in a residential garage must  
be installed as specified in “Installation” of these instructions.  
S This furnace is not to be used for temporary heating of buildings  
or structures under construction.  
!
CAUTION  
WATER DAMAGE TO PROPERTY HAZARD  
S This furnace is NOT approved for installation in mobile  
homes, trailers or recreation vehicles.  
Failure to follow this caution may result in property damage.  
S Seal around supply and return air ducts.  
Do not leave your home unattended for long periods during  
freezing weather without turning off water supply and  
draining water pipes or otherwise protecting against the risk of  
frozen pipes and resultant damage.  
S Install correct filter type and size.  
S Unit MUST be installed so electrical components are protected  
from direct contact with water.  
Safety Rules  
Your furnace is designed solely to provide a safe and comfortable  
living environment. The furnace is NOT designed to ensure that  
water pipes will not freeze. It is equipped with several safety  
devices that are designed to turn the furnace off and prevent it from  
restarting in the event of various potentially unsafe conditions.  
Your unit is built to provide many years of safe and dependable  
service providing it is properly installed and maintained. However,  
abuse and/or improper use can shorten the life of the unit and create  
hazards for you, the owner.  
The U.S. Consumer Product Safety Commission encourages  
installation of carbon monoxide alarms. There can be various  
sources of carbon monoxide in a building or dwelling. The sources  
could be gas--fired clothes dryers, gas cooking stoves, water heaters,  
furnaces, gas--fired fireplaces, wood fireplaces.  
If your furnace remains off for an extended time, the pipes in your  
home could freeze and burst, resulting in water damage.  
If the structure will be unattended during cold weather you should  
take these precautions.  
1. Turn off the water supply to the structure and drain the water  
lines if possible and add an antifreeze for potable water to  
drain traps and toilet tanks. Open faucets in appropriate  
areas.  
Carbon monoxide can cause bodily injury and/or death. Carbon  
monoxide or “CO” is a colorless and odorless gas produced when  
fuel is not burned completely or when the flame does not receive  
sufficient oxygen.  
-- o r --  
Therefore, to help alert people of potentially dangerous carbon  
monoxide levels, you should have a commercially available carbon  
monoxide alarm that is listed by a nationally recognized testing  
agency in accordance with Underwriters Laboratories Inc. Standard  
for Single and Multiple Station Carbon Monoxide Alarms,  
ANSI/UL 2034 or the CSA 6.19--01 Residential Carbon Alarming  
Devices installed and maintained in the building or dwelling  
concurrently with the gas--fired furnace installation (see Note  
below). The alarm should be installed as recommended by the  
alarm manufacturer’s installation instructions.  
2. Have someone check the structure frequently during cold  
weather to make sure it is warm enough to prevent pipes  
from freezing. Instruct them on a service agency to call to  
provide service, if required.  
-- o r --  
3. Install a reliable remote sensing device that will notify some-  
body of freezing conditions within the home.  
Winter Shutdown  
There can be numerous sources of fire or smoke in a building or  
dwelling. Fire or smoke can cause bodily injury, death, and/or  
property damage. Therefore, in order to alert people of potentially  
dangerous fire or smoke, you should have fire extinguisher and  
smoke alarms listed by Underwriters Laboratories installed and  
maintained in the building or dwelling (see Note below).  
If you go away during the winter months and do not leave the heat  
on in your home, the plastic transition box and the condensate trap  
on the furnace must be protected from freeze damage. (See Fig. 10  
through Fig. 17)  
5
1. Disconnect the / OD rubber hose from the vent drain fit-  
8
ting that is located downstream of the combustion blower.  
Insert a funnel into the hose and pour four(4) ounces of san-  
itary type (RV) antifreeze into the condensate trap. Recon-  
NOTE: The manufacturer of your furnace does not test any alarms  
and makes no representations regarding any brand or type of  
alarms.  
5
nect the / OD rubber hose to the stub on the vent drain  
8
fitting. Secure with the hose clamp.  
To ensure safe and efficient operation of your unit, you should do  
the following:  
3
2. Disconnect the / OD rubber hose from the condensate  
4
trap. Insert a funnel into the hose and and pour four(4)  
ounces of sanitary type (RV) antifreeze into the plastic  
1. Thoroughly read this manual and labels on the unit. This  
will help you understand how your unit operates and the  
hazards involved with gas and electricity.  
2. Do not use this unit if any part has been under water.  
Immediately call a qualified service technician to inspect the  
unit and to replace any part of the control system and any  
gas control which has been under water.  
Transition box. Squeeze the hose together near the end and  
3
quickly reconnect the / OD rubber hose to the stub on the  
4
condensate trap. Secure with the hose clamp.  
When you return home, your furnace will be ready to start, as it is  
not necessary to drain the antifreeze from the furnace.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Aluminum or non--rusting shield recommended.  
(See Vent Termination Shielding for dimensions).  
INSTALLATION  
*8(203.2mm) Min.  
20(6.1m) Max.  
in same  
atmospheric  
zone  
Coupling on ends of  
exhaust pipe. Total  
pipe & coupling out-  
side structure = 8″  
(203.2mm)  
!
WARNING  
Inlet Pipe  
(not used on  
Single Pipe  
model)  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow this warning could result in personal injury  
or death.  
This furnace can NOT be common vented or connected to any  
type B, BW or L vent or vent connector, nor to any portion of  
a factory--built or masonry chimney. If this furnace is replacing  
a previously common-vented furnace, it may be necessary to  
resize the existing vent and chimney to prevent oversizing  
Vent Pipes MUST be  
supported  
Horizontally and  
Vertically  
*8(203.2mm) Min.  
20(6.1m) Max.  
insameatmospheric zone  
problems  
for  
the  
other  
remaining appliance(s). See Venting and Combustion Air  
Check in Gas Vent Installation section. This furnace MUST be  
vented to the outside.  
* Increase minimum from 8(203.2mm) to 18(457.2mm) for cold climates (sus-  
tained temperatures 0° F (-17° C) and below for 24 or more consecutive hours).  
2 5 -- 2 3 -- 3 3  
Installation Positions  
This furnace can be installed in an upflow, horizontal (either left or  
right) or downflow airflow position. DO NOT install this furnace  
on its back. For the upflow position, the return air ductwork can be  
attached to either the left or right side panel and/or the bottom. For  
horizontal and downflow positions, the return air ductwork must be  
attached to the bottom. The return air ductwork must never be  
attached to the back of the furnace.  
A07700  
Fig. 1 -- Typical Upflow Installation  
See Vent Termination  
Shielding in Vent Section.  
Coupling on inside  
and outside of wall to  
restrain vent pipe  
*8Min. (203 mm)  
Inlet Pipe  
(not used on  
Single Pipe  
model)  
20Max. in same (6 M)  
atmosphericzone  
8Min. (203 mm)  
Location and Clearances  
1. Refer to Fig. 1 for typical installation and basic connecting  
parts required. Refer to Fig. 4 for typical horizontal direct  
vent installation and basic connecting parts required. Supply  
and return air plenums and duct are also required.  
Vent Pipes MUST  
be supported Horizon-  
tally and Vertically  
*8Min. (203 mm)  
20Max. (6.1 M)  
in same  
2. If furnace is a replacement, it is usually best to install the fur-  
nace where the old one was. Choose the location or evaluate  
the existing location based upon the minimum clearance and  
furnace dimensions (Fig. 2).  
atmospheric zone  
!
CAUTION  
25--23--33a  
FROZEN AND BURST PIPE HAZARD  
*
Increase minimum from 8to 18(203 to 457 mm) for cold climates (sustained temperatures  
0°F ( - 1 8 °C ) and ) below for 24 or more consecutive hours).  
Failure to follow this caution may result in property damage.  
A07762  
Special precautions MUST be made is installing furnace in an  
area which may drop below freezing. This can cause improper  
operation or damage to equipment. If furnace environment  
has the potential of freezing, the drain trap and drain line must  
be protected. The use of electric heat tape or RV antifreeze is  
recommended for these installations. (See “Condensate Trap  
Freeze Protection Section”)  
Fig. 2 -- Typical Downflow Installation  
Installation Requirements  
1. Install furnace level.  
2. This furnace is NOT to be used for temporary heat of  
buildings or structures under construction.  
3. Install furnace as centralized as practical with respect to the  
heat distribution system.  
4. Install the vent pipes as short as practical, and in accordance  
to these instructions. (See Vent and Combustion Air Piping  
section).  
5. Maintain clearance for fire safety and servicing. A front  
clearance of 24(609.6mm) required and 30(762mm)  
recommended for access to the burner, controls and filter.  
See clearance requirements in Fig. 4.  
6. Use a raised base for upflow furnace if the floor is damp or  
wet at times.  
7. For downflow installations, non combustible subbase must  
be used under the furnace unless installation is on a non  
combustible floor surface. This requirement applies even  
when a coil box or cabinet is used.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. For horizontal installations, line contact is permissible only  
between lines formed by intersection of back and two sides  
of furnace jacket, and building joists, studs or framing.  
Furnace Installation Considerations  
The installation of the furnace for a given application will dictate  
the position of the furnace, the airflow, ductwork connections, vent  
and combustion air piping. Consideration must be given to the  
following:  
9. Residential garage installations require:  
S Burners and ignition sources installed at least 18(457.2mm)  
above the floor.  
Condensate Trap and Drain Lines  
S Located or physically protected from possible damage by a  
The supplied condensate trap must be attached to the furnace side  
panel on either the left or right side. For horizontal installations, the  
drain trap is vertically attached to the side panel below the furnace.  
A minimum clearance of 6(152.4mm) below the furnace is  
required for the condensate trap. Downward slope of the  
condensate drain line from the condensate trap to the drain location  
must be provided. Adequate freeze protection of the drain trap and  
the drain line must be provided. See “Condensate Drain Trap”  
section for further details.  
vehicle.  
10. Local codes may require a drain pan under the entire furnace  
and condensate trap when the furnace is installed in attic  
application.  
This furnace may be used for construction heat provided that all the  
following conditions are met:  
S The furnace is permanently installed with all electrical wiring,  
piping, venting and ducting installed according to these  
installation instructions. A return air duct is provided, sealed to  
the furnace casing, and terminated outside the space containing  
the furnace. This prevents a negative pressure condition as  
created by the circulating air blower, causing a flame rollout  
and/or drawing combustion products into the structure.  
S The furnace is controlled by a thermostat. It may not be “hot  
wired” to provide heat continuously to the structure without  
thermostatic control.  
Leveling  
Proper leveling of the furnace must be provided to insure proper  
drainage of the condensate from the furnace. The furnace must be  
level to within / (6.4mm) from front to back and from side to  
side for upflow and downflow installations or top to bottom for  
horizontal installations.  
1
4
Vent and Combustion Air Connections  
the complete model and serial number of the furnace.  
On the Dual Certified furnace, the vent and combustion air pipes  
attach to the furnace through the top panel for the upflow and  
horizontal installations. For the downflow installation, the vent and  
combustion air pipes attach to the furnace through the alternate  
locations on the furnace side panels.  
S Clean outside air is provided for combustion. This is to  
minimize the corrosive effects of adhesives, sealers and other  
construction materials. It also prevents the entrainment of  
drywall dust into combustion air, which can cause fouling and  
plugging of furnace components.  
NOTE: On the Direct Vent furnace, the vent pipe attaches to the  
furnace through the side panels. The combustion air pipe attaches to  
the top panel or to the alternate location on the side panel.  
On the Single Pipe furnace, the vent pipe attaches to the furnace  
through the furnace side panels.  
S The temperature of the return air to the furnace is maintained  
between 55° F (13° C) and 80° F (27° C) , with no evening  
setback or shutdown. The use of the furnace while the structure  
is under construction is deemed to be intermittent operation per  
our installation instructions.  
NOTE: Repositioning of the combustion blower is required for the  
vent pipe connection to the furnace through the “right side” panel.  
See “Vent and Combustion Air Piping” section for further details.  
S The air temperature rise is within the rated rise range on the  
furnace rating plate, and the firing rate has been set to the rating  
plate value.  
Horizontal Furnace Installation  
Inlet Pipe (not used on Single Pipe model)  
S The filters used to clean the circulating air during the  
construction process must be either changed or thoroughly  
cleaned prior to occupancy.  
Vent  
Pipe  
S The furnace, ductwork and filters are cleaned as necessary to  
remove drywall dust and construction debris from all HVAC  
system components after construction is completed.  
S After construction is complete, verify furnace operating  
conditions including ignition, input rate, temperature rise and  
venting according to these instructions.  
Condensate  
Trap  
!
WARNING  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow this warning could result in personal injury  
or death.  
NOTE: 6bottom clearance required for condensate trap.  
A07703  
Do NOT operate furnace in a corrosive atmosphere containing  
chlorine, fluorine or any other damaging chemicals, which  
could shorten furnace life.  
Fig. 3 -- Typical Horizontal Installation  
This furnace can be installed horizontally in an attic, basement,  
crawl space, alcove, or suspended from a ceiling in a basement or  
utility room (See Fig. 3). Do not install furnace on its back as safety  
control operation will be adversely affected.  
Refer to Combustion & Ventilation Air section, Contaminated  
Combustion Air for combustion air evaluation and remedy.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
F
MINIMUM CLEARANCES TO COMBUSTIBLE  
MATERIALS FOR ALL UNITS -- in (mm)  
AIR INTAKE  
VENT  
A
B
REAR  
0
TOP  
FRONT (combustion air openings in 3(76.2)  
furnace and in structure)  
H
Required For Service  
ALL SIDES Of SUPPLY PLENUM  
SIDES  
*
24(609.6)  
G
FRONT  
1(25.4)  
E
0
11  
(177.5)  
ELECTRICAL  
1
(318)  
VENT  
0
LEFT SIDE  
6
/
16  
1 /  
4
TOP OF FURNACE  
1(25.4)  
TRAP (KO) (COUNTERFLOW)  
*
30(762mm) clearance recommended for furnace removal.  
GAS  
VENT  
1
(27)  
16  
1 /  
Horizontal position: Line contact is permissible only between  
lines formed by intersections of top and two sides of furnace  
jacket, and building joists, studs or framing.  
11  
(347.7)  
13  
/
16  
AIR INTAKE (KO)  
11  
(804.9)  
13  
(ALTERNATE)  
31  
/
4
/
16  
16  
(34.9)  
(122.2)  
TRAP (KO)  
NOTE: Evaporator “A” coil drain pan dimensions may  
vary from furnace duct opening size. Always consult  
evaporator specifications for duct size requirements.  
(758.8)  
3
1 /  
8
UPFLOW/HORIZONTAL  
7
29 /  
8
3
28 /  
7
4
1
THERMOSTAT  
(57.2)  
2 /  
(730.3)  
4
(177.8)  
1
Furnace is designed for bottom return or side return.  
24 /  
16  
(611.2)  
5
13  
Return air through back of furnace is NOT allowed.  
17 /  
19  
/
16  
16  
1
13 /  
(439.7)  
4
1
(503.2)  
1 /  
4
(336.6)  
11  
1
/
(31.7)  
16  
(42.9)  
(KO)  
5
21 /  
8
7
4 /  
8
7
2 /  
8
1
28 /  
(549.3)  
2
(123.8)  
7
1 /  
5
(109.5)  
8
(73)  
(723.9)  
4 /  
3
24  
(19.1)  
16  
1
/
4
(47.6 )  
18 /  
2
(609.6)  
(469.9)  
TYPE  
Drawing is representative,  
but some models may vary  
3
(60.3 )  
(27)  
2 /  
8
1
1 /  
16  
RIGHT SIDE  
TRAP (KO)  
(COUNTERFLOW)  
GAS (KO)  
BOTTOM  
D
ELECTRICAL (KO)  
AIR INTAKE (KO)  
(ALTERNATE)  
C
1
23 /  
7
8
3 /  
8
ALL DIMENSIONS: in (mm)  
13  
(587.4)  
(98.4)  
4
/
16  
3
1 /  
16  
(122.2)  
40  
(30.2)  
VENT (KO)  
(1016)  
TRAP (KO)  
1
(27)  
1 /  
UPFLOW/HORIZONTAL  
16  
7
29 /  
8
(758.8)  
1
2 /  
4
7
3
27 /  
16  
(57.2)  
(177.8)  
(690.6)  
5
THERMOSTAT  
21 /  
8
13  
(249.2)  
9
/
16  
(549.3)  
1
13 /  
5
4
17 /  
16  
(336.6)  
(KO)  
11  
(855.7)  
(439.7)  
33  
/
16  
11  
1
/
16  
(42.9)  
5
21 /  
7
8
4 /  
7
8
1 /  
KO = KnockOut  
8
(549.3)  
(123.8)  
(47.6)  
24  
(609.6)  
Cabinet  
Bottom  
Top  
Unit  
Capacity  
C
2 /  
A
B
D
E
4 /  
(111.1)  
3
4 /  
8
(111.1)  
3
4 /  
8
(111.1)  
3
4 /  
8
F
4 /  
(114.3)  
1
4 /  
2
(114.3)  
1
4 /  
2
(114.3)  
1
4 /  
2
G
2 /  
H
1
5
1
3
3
1
1
1
19 /  
8
17 /  
14 /  
9 /  
8
8
4
8
2
2
2
58HDV040---1--12/  
359BAV036040  
58HDV060---1--12/  
359BAV036060  
(485.8)  
(447.7)  
(54)  
(374.7)  
(63.5)  
(241.3)  
1
9 /  
2
(241.3)  
3
11 /  
8
(288.9)  
1
12 /  
4
1
19 /  
8
5
17 /  
8
1
3
14 /  
4
1
2 /  
2
2 /  
8
(485.8)  
(447.7)  
(54)  
15  
(374.7)  
3
18 /  
4
(63.5)  
3
22 /  
4
1
21 /  
4
5
2 /  
8
1
/
58HDV080---1--12/  
359BAV060080  
58HDV100---1--20/  
359BAV060100  
16  
(577.9)  
(539.8)  
(49.2)  
(476.3)  
(66.7)  
1
24 /  
2
7
1
2 /  
4
23  
/
23  
16  
(622.3)  
(584.2)  
(11.1)  
(584.2)  
(111.1)  
(114.3)  
(57.2)  
(311.2)  
2 5 -- 2 3 -- 3 6 b  
Specifications are subject to change without notice.  
A09192  
Fig. 4 -- Dimensions and Clearances  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
If the furnace is to be suspended from the floor joists in a crawl  
space or the rafters in an attic, it is necessary to use steel pipe straps  
or an angle iron frame to rigidly attach the furnace to prevent  
movement. These straps should be attached to the furnace bottom  
side with sheet metal screws and to the rafters or joists with bolts.  
The preferred method is to use an angle iron frame bolted to the  
rafters or joists.  
If the furnace is to be installed in a crawl space, consult local codes.  
A suitable concrete pad or blocks are recommended for crawl space  
installation on the ground.  
COMBUSTION & VENTILATION  
AIR  
For Single Pipe Installation  
!
WARNING  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow this warning could result in personal injury  
or death.  
NOTE: 6(152.4mm) bottom clearance required for condensate  
trap.  
Use methods described here to provide combustion and  
ventilation air.  
24(609.6mm) inches between the front of the furnace and  
adjacent construction or other appliances MUST be maintained for  
service clearance. [30(762mm) inches is required to remove  
furnace].  
Keep all insulating materials clear from louvered door. Insulating  
materials may be combustible.  
The horizontal furnaces may be installed directly on combustible  
wood flooring or supports as long as all required furnace clearances  
are met. See Fig. 3.  
Furnaces require ventilation openings to provide sufficient air for  
proper combustion and ventilation of flue gases. All duct or  
openings for supplying combustion and ventilation air must  
comply with the gas codes, or in the absence of local codes, the  
applicable national codes.  
Combustion and ventilation air must be supplied in accordance  
with one of the following:  
This furnace MUST NOT be installed directly on carpeting or tile  
or other combustible material other than wood flooring or supports.  
NOTE: The Combustion & Ventilation Air Section in this  
document, uses tables and information from the ANSI  
Z223.1/NFPA 54. For use in Canada, use CSA B149.1 for this  
information.  
For horizontal installation over a finished living space. A field  
fabricated auxiliary drain pan with drain pipe is required to prevent  
damage by overflow due to blocked condensate drain.  
1. Section 9.3, Air for Combustion and Ventilation, of the Na-  
tional Fuel Gas Code, (NFGC), ANSI Z223.1--2006/NFPA  
54--2006 in the U.S.,  
Knock Outs  
2. Sections 8.2, 8.3, 8.5, 8.6, 8.7, and 8.8 of National Standard  
of Canada, Natural Gas and Propane Installation Code  
(NSCNGPIC), CSA B149.1--05 in Canada,  
3. Applicable provisions of the local building code.  
This furnace can NOT be common vented or connected to any type  
B, BW or L vent or vent connector, nor to any portion of a  
factory--built or masonry chimney. Multistory common venting is  
NOT permitted. If this furnace is replacing  
a
previously  
common-vented furnace, it may be necessary to resize the existing  
vent and chimney to prevent oversizing problems for the other  
remaining appliance(s). See Venting and Combustion Air Check”  
in this section. This furnace MUST be vented to the outside.  
A07702  
When the installation is complete, check that all appliances have  
adequate combustion air and are venting properly. See Venting And  
Combustion Air Check in “Gas Vent Installation” Section in this  
manual.  
Fig. 5 -- Hammer and Screwdriver used for Knockout  
!
CAUTION  
Outdoor Combustion Air Method  
CUT HAZARD  
A space having less than 50 cubic feet per 1,000 BTUH input rating  
for all gas appliances installed in the space requires outdoor air for  
combustion and ventilation.  
Failure to follow this caution may result in personal injury.  
Sheet metal parts may have sharp edges or burrs. Use care and  
wear appropriate clothing, safety glasses and gloves when  
handling parts and servicing furnaces.  
Air Openings and Connecting Ducts  
1. Total input rating for all gas appliances in the space MUST  
be considered when determining free area of openings.  
2. Connect ducts or openings directly to the outdoors.  
Use a hammer and screwdriver to strike a sharp blow (See Fig. 5)  
directly to the knockout tie points or use a hammer in the upper left  
corner of the desired knockout. Remove any burrs and sharp edges.  
3. When screens are used to cover openings, the openings  
1
MUST be no smaller than / (6.35 mm) mesh.  
4
4. The minimum dimension of air ducts MUST NOT be less  
than 3(76.2 mm).  
NOTE: If a knockout does not come out after two sharp blows,  
pull and snip as needed to remove the knockout.  
5. When sizing a grille, louver, or screen use the free area of  
opening. If free area is NOT stamped or marked on grill or  
louver, assume a 20% free area for wood and 60% for metal.  
1
Screens shall have a mesh size not smaller than / (6.35  
4
mm) .  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
a. One opening MUST commence within 12(304.8mm)  
of the floor and the second opening MUST commence  
within 12(304.8mm) of the ceiling.  
Confined Space Installation  
NOTE: A confined space is defined as an area with less than 50  
3
2
cubic feet (1.4 M)per 1,000 BTUH (2.33 cm /kW) input rating for  
all gas appliances installed in the area.  
b. Size openings and ducts per Table 1.  
c. Horizontal duct openings require 1 square inch of free  
2
area per 2,000 BTUH (11 cm /kW) of combined input  
Requirements  
for all gas appliances in the space (see Table 1).  
1. Provide the space with sufficient air for proper combustion  
and ventilation of flue gases using horizontal or vertical  
ducts or openings.  
d. Vertical duct openings or openings directly  
communicating with the outdoors require 1 square inch  
2
of free area per 4,000 BTUH (5.5 cm /kW) for  
2. Fig. 6 illustrates how to provide combustion and ventilation  
air. A minimum of two permanent openings, one inlet and  
one outlet, are required.  
combined input of all gas appliances in the space (see  
Table 1).  
This installation NOT approved in Canada  
Gas Vent  
Gable Vent  
Gas Vent  
Ventilated Attic  
Top Above Insulation  
Gable Vent  
Alternate Inlet Air (1)  
Gas Vent  
Outlet  
Air (1)  
Outlet  
Air (2)  
Ventilated Attic  
Soffit Vent  
Outlet Air (1)  
Top Above Insulation  
Inlet  
Air (1)  
OutletAir (1)  
Soffit Vent  
Inlet  
Air (2)  
Minimum One Inlet and One Outlet Air Supply is Required  
May be in any Combination Shown  
Inlet  
Air (2)  
Inlet Air Opening Must be Within12of floor  
Outlet Air Opening Must be Within12of ceiling  
(1) 1 Square Inch per 4000 BTUH  
Inlet  
Air (1)  
Ventilated Crawl Space  
alternate Inlet Air (1)  
(2) 1 Square Inch per 2000 BTUH  
A07704  
Fig. 6 -- Outside Air  
(This is ONLY a guide. Subject to codes of country having jurisdiction).  
3. One opening MUST be within 12(304.8mm) of the floor b. Outdoor openings located as required in the Outdoor  
and the second opening within 12(304.8mm) of the  
Combustion Air Method above and  
ceiling.  
c. Outdoor openings sized as follows.  
2
a. 1 sq. in of free area per 3,000 BTUH (7 cm /kW) for  
combined input of all gas appliances in the space (see  
Table 1) and  
(1.) Calculate the Ratio of all Indoor Space volume  
divided by required volume for Indoor  
Combustion Air Method.  
b. not less than the sum of the areas of all vent connectors  
in the space.  
(2.) Outdoor opening size reduction Factor is 1 minus  
the Ratio in 1) above.  
The opening shall commence within 12(304.8mm) of the top of  
the enclosure. Appliances shall have clearances of at least 1″  
(25.4mm) from the sides and back and 6(152.4mm) from the  
front. The opening shall directly communicate with the outdoors or  
shall communicate through a vertical or horizontal duct to the  
outdoors or spaces (crawl or attic) that freely communicate with the  
outdoors.  
(3.) Minimum size of Outdoor openings shall be the  
size required in Outdoor Combustion Air Method  
above multiplied by reduction Factor.  
5. Horizontal duct openings require 1 square inch of free area  
per 2,000 BTUH of combined input for all gas appliances in  
area (see Table 1).  
6. Vertical duct openings or openings directly to outside  
require 1 square inch of free area per 4,000 BTUH (5.5  
4. Size openings and ducts per Table 1.  
a. Indoor openings that comply with the Indoor  
Combustion Air Method below and  
2
cm /kW) for combined input of all gas appliances in area  
(see Table 1).  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1  
Free Area  
Minimum Free Area Required for Each Opening or Duct to Outdoors  
Two Vertical Ducts or  
Round Duct  
BTUH (kW)  
sq.  
BTUH (kW)  
Input Rating  
Two Horizontal Ducts  
BTUH (kW)  
Single Opening  
Openings  
BTUH (kW)  
BTUH (kW)  
2
2
sq. in./2,000(1 cm /.09)  
sq. in./3,000 (1 cm /.135)  
2
2
sq. in./4,000(1 cm /.18)  
in./4,000(6.5cm /.18)  
2
2
2
40,000 (11.72)  
50,000 (14.65)  
60,000 (17.58)  
75,000 (21.98)  
80,000 (23.45)  
100,000 (29.31)  
125,000 (36.63)  
20 sq. in. (129 cm )  
13.34 sq. in. (86 cm )  
10 sq. in. (65 cm )  
4(101.6mm)  
4(101.6mm)  
5(127mm)  
5(127mm)  
5(127mm)  
6(152.4mm)  
7(177.8mm)  
2
2
2
25 sq. in. (161 cm )  
16.7 sq. in. (108 cm )  
12.5 sq. in. (81 cm )  
2
2
2
30 sq. in. (194 cm )  
20 sq. in. (129 cm )  
15 sq. in. (97 cm )  
2
2
2
37.5 sq. in. (242 cm )  
25 sq. in. (161 cm )  
18.75 sq. in. (121 cm )  
2
2
2
40 sq. in. (258 cm )  
26.7 sq. in. (172 cm )  
20 sq. in. (129 cm )  
2
2
2
50 sq. in. (322 cm )  
33.3 sq. in. (215 cm )  
25 sq. in. (161 cm )  
2
2
2
62.50 sq. in. (403 cm )  
41.7 sq. in. (269 cm )  
31.25 sq. in. (202 cm )  
EXAMPLE: Determining Free Area  
Furnace  
Water Heater  
Total Input  
100,000  
29.31  
Furnace  
100,000  
29.31  
+
+
30,000  
8.8  
Water Heater  
=
=
(130,000 ÷ 4,000)  
(38.11 ÷ .18)  
Total Input  
(130,000 ÷ 2,000)  
(38.11 ÷ .09)  
=
=
32.5 Sq. In. Vertical  
210 cm Vertical  
2
30,000  
8.8  
=
=
65 Sq. In. Horizontal  
2
423 cm Horizontal  
appliances installed in the space. The standard method permits  
indoor air to be used for combustion and ventilation air.  
Indoor Combustion Air (Unconfined Space)  
The Known Air Infiltration Rate Method shall be used if the  
infiltration rate is known to be less than 0.40 air changes per hour  
(ACH) and equal to or greater than 0.10 ACH. Infiltration rates  
greater than 0.60 ACH shall not be used. The minimum required  
volume of the space varies with the number of ACH and shall be  
determined per Table 2 or Equations 1 and 2. Determine the  
minimum required volume for each appliance in the space, and add  
the volumes together to get the total minimum required volume for  
the space.  
!
WARNING  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow this warning could result in personal injury  
or death.  
Most homes will require additional air from outdoors for  
combustion and ventilation. A space with at least 50 cubic feet  
(1.4 M) per 1,000 (2.33 cm /kW) Btuh Input rating or homes  
with tight construction may need outdoor air, supplied through  
ducts, to supplement air infiltration for proper combustion and  
ventilation of flue gasses.  
3
2
!
WARNING  
CARBON MONOXIDE POISONING HAZARD  
Failure to supply additional air by means of ventilation grilles  
or ducts could result in personal injury or death.  
Standard and Known- Air- Infiltration Rate Methods  
© NFPA & AGA  
An unconfined space or homes with tight construction may  
not have adequate air infiltration for proper combustion and  
ventilation of flue gasses. Most homes will require additional  
air.  
Indoor air is permitted for combustion and ventilation, if the  
Standard or Known--Air--Infiltration Rate Method is used.  
The Standard Method may be used, if the space has no less  
volume than 50 cubic feet per 1,000 BTUH input rating for all gas  
MINIMUM SPACE VOLUME FOR 100% COMBUSTION AND VENTILATION AIR FROM INDOORS  
Table 2  
Other Than Fan- Assisted Total  
Fan- assisted Total  
30,000 BTU  
(8,790 kW)  
40,000 BTU  
(11,720 kW)  
50,000 BTU  
(14,650 kW)  
50,000 BTU  
(14,650 kW)  
75,000  
(21,975 kW)  
100,000 BTU  
(29,300 kW)  
125,000 BTU  
(36,625 kW)  
ACH  
3
ft3 (m )  
0.60  
0.50  
0.40  
0.30  
0.20  
0.10  
0.00  
1,050 (29.7)  
1,260 (35.3)  
1,575 (44.1)  
2,100 (58.8)  
3,150 (88.2)  
6,300 (176.4)  
NP  
1,400 (39.2)  
1,680 (47.04)  
2,100 (58.8)  
2,800 (78.4)  
4,200 (117.6)  
8,400 (235.2)  
NP  
1,750 (49)  
2,100 (58.8)  
2,625 (73.5)  
3,500 (98)  
5,250 (147)  
10,500 (294)  
NP  
1,250 (35)  
1,500 (42)  
1,875 (52.5)  
2,500 (70)  
3,750 (105)  
7,500 (210)  
NP  
1,875 (52.5)  
2,250 (63)  
2,813 (78.8)  
3,750 (105)  
5,625 (157.5)  
11,250 (315)  
NP  
2,500 (70)  
3,000 (84)  
3,750 (105)  
5,000 (140)  
7,500 (210)  
15,000 (420)  
NP  
3,125 (87.5)  
3,750 (105)  
4,688 (131.3)  
6,250 (175)  
9,375 (262.5)  
18,750 (525)  
NP  
ACH = Air Changes per Hour  
NP = Not Permitted  
Tab le 2 Minimum Space Volumes were determined by using the following equations from the National Fuel Gas Code ANSI Z223.1/NFPA 54---2006, 9.3.2.2:  
1. For appliances other than fan--assisted appliances (such as  
a draft hood--equipped water heater), calculate using the fol-  
lowing equation:  
I other  
21 ft3  
(
Required Volume  
)
²
other  
1000 Btu / hr  
ACH  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. For fan--assisted appliances (such as this furnace), calcu-  
using the methods described in section titled Outdoor  
Combustion Air Method:  
late using the following equation:  
S Unusually tight construction is defined as Construction with:  
I fan  
15 ft3  
ACH  
1. Walls and ceilings exposed to the outdoors have a continu-  
ous, sealed vapor barrier. Openings are gasketed or sealed  
and  
(
)
Required Volume  
²
fan  
1000 Btu / hr  
where:  
2. Doors and openable windows are weather stripped and  
I
= all appliances other than fan--assisted input in Btu  
other  
3. Other openings are caulked or sealed. These include joints  
around window and door frames, between sole plates and  
floors, between wall--ceiling joints, between wall panels, at  
penetrations for plumbing, electrical and gas lines, etc.  
per hour  
I
=
fan--assisted appliance input in Btu per hour  
fan  
ACH =air change per hour (percent of volume of space exchanged  
per hour, expressed as a decimal)  
Ventilation Air  
3. For purposes of this calculation, an infiltration rate greater  
than 0.60 ACH shall not be used in the equations above.  
Some provincial codes and local municipalities require ventilation  
or make--up air be brought into the conditioned space as  
replacement air. Whichever method is used, the mixed return air  
temperature across the heat exchanger MUST not fall below 60° so  
that flue gases will not condense excessively in the heat exchanger.  
Excessive condensation will shorten the life of the heat exchanger  
and possibly void your warranty.  
The following requirements apply to the Standard Method and to  
the Known Air Infiltration Rate Method.  
S Adjoining rooms can be considered part of a space, if there are  
no closeable doors between rooms.  
S Combining spaces on the same story. Each opening shall have a  
2
minimum free area of at least 1 in. /1,000 BTUH (2,200  
Venting and Combustion Air Check  
2
mm /kW) of the total input rating of all appliances in the space  
NOTE: If this installation replaces an existing furnace from a  
commonly vented system, the original venting system may no  
longer be sized to properly vent the attached appliances. An  
improperly sized venting system may cause the formation of  
condensate in the vent and the leakage or spillage of vent gases. To  
make sure there is adequate combustion air for all appliances,  
MAKE THE FOLLOWING CHECK.  
2
2
but not less than 100 in. (0.06 m ). One opening shall  
commence within 12 in. (304.8 mm) of the top, and one opening  
shall commence within 12 in. (304.8 mm) of the bottom, of the  
enclosure. The minimum dimension of air openings shall not be  
less than 3 in. (76.2 mm).  
S Combining spaces in different stories. The volumes of spaces on  
different stories shall be considered as communicating spaces  
where such spaces are connected by one or more openings in  
2
Vent Pipe  
Draft Hood  
doors or floors having a total minimum free area of 2 in. /1,000  
2
BTUH (4,400 mm /kW) of total input rating of all appliances.  
Typical Gas  
Water Heater  
S An attic or crawl space may be considered a space that freely  
communicates with the outdoors provided there are adequate  
ventilation openings directly to outdoors. Openings MUST  
remain open and NOT have any means of being closed off.  
Ventilation openings to outdoors MUST be at least 1 square inch  
Match  
A07688  
Fig. 7 -- Vent Check  
2
of free area per 4,000 BTUH (550 mm /kW) of total input rating  
for all gas appliances in the space.  
The following information is supplied to allow the installer to make  
adjustments to the setup of existing appliances, IF REQUIRED,  
based on good trade practices, local codes, and good judgement of  
the installer. Manufacturer does NOT take responsibility for  
modifications made to existing equipment.  
S In spaces that use the Indoor Combustion Air Method,  
infiltration should be adequate to provide air for combustion,  
ventilation and dilution of flue gases. However, in buildings with  
unusually tight construction, additional air MUST be provided  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENT AND COMBUSTION AIR  
PIPING  
!
WARNING  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow the steps outlined below for each  
appliance connected to the venting system being  
placed into operation, could result in carbon monoxide  
poisoning or death:  
!
WARNING  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow this warning could result in personal injury  
or death.  
The following steps shall be followed for each  
appliance connected to the venting system being  
placed into operation, while all other appliances  
connected to the venting system are not in operation:  
Use methods described here to provide combustion and  
ventilation air.  
1. Seal any unused openings in the venting system.  
Dual Certified  
2. Inspect the venting system for proper size and  
horizontal pitch, as required in the National Fuel Gas  
Code, ANSI Z223.1/NFPA 54 or CSA B149.1, Natural  
Gas and Propane Installation Code and these  
instructions. Determine that there is no blockage or  
restriction, leakage, corrosion and other deficiencies  
which could cause an unsafe condition.  
3. As far as practical, close all building doors and  
windows and all doors between the space in which the  
appliance(s) connected to the venting system are  
located and other spaces of the building.  
Direct or Non-Direct Vent  
This furnace is certified as a Category IV furnace. This furnace can  
be installed as a direct vent furnace using outside air for combustion  
or the furnace can use air from inside the structure for combustion.  
The INLET air pipe is optional. If combustion air comes from  
inside the structure, adequate make up air MUST be provided to  
compensate for oxygen burned. See Confined Space Installation  
in the Combustion and Ventilation Air chapter. If combustion air is  
drawn from outside the structure, it MUST be taken from the same  
atmospheric pressure zone as the vent pipe.  
4. Close fireplace dampers.  
Contaminated Combustion Air  
5. Turn on clothes dryers and any appliance not connected  
to the venting system. Turn on any exhaust fans, such  
as range hoods and bathroom exhausts, so they are  
operating at maximum speed. Do not operate a summer  
exhaust fan.  
6. Follow the lighting instructions. Place the appliance  
being inspected into operation. Adjust the thermostat so  
appliance is operating continuously.  
Installations in certain areas or types of structures will increase the  
exposure to chemicals or halogens that may harm the furnace.  
The following areas or types of structures may contain or have  
exposure to the substances listed below. The installation must be  
evaluated carefully as it may be necessary to provide outside air for  
combustion.  
S Commercial buildings.  
7. Test for spillage from draft hood equipped appliances at  
the draft hood relief opening after 5 minutes of main  
burner operation. Use the flame of a match or candle.  
(Fig. 6)  
8. If improper venting is observed, during any of the  
above tests, the venting system must be corrected in  
accordance with the National Fuel Gas Code, ANSI  
Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and  
Propane Installation Code.  
9. After it has been determined that each appliance  
connected to the venting system properly vents when  
tested as outlined above, return doors, windows,  
exhaust fans, fireplace dampers and any other gas--fired  
burning appliance to their previous conditions of use.  
S Buildings with indoor pools.  
S Furnaces installed in laundry rooms.  
S Furnaces installed in hobby or craft rooms.  
S Furnaces installed near chemical storage areas.  
S Permanent wave solutions for hair.  
S Chlorinated waxes and cleaners.  
S Chlorine based swimming pool chemicals.  
S Water softening chemicals.  
S De--icing salts or chemicals.  
S Carbon tetrachloride.  
S Halogen type refrigerants.  
S Cleaning solvents (such as perchloroethylene).  
S Printing inks, paint removers, varnishes, etc.  
S Hydrochloric acid.  
S Sulfuric Acid.  
For Two Pipe Installation (Direct Vent)  
S Solvent cements and glues.  
S Antistatic fabric softeners for clothes dryers.  
This furnace can NOT be common vented or connected to any type  
B, BW or L vent or vent connector, nor to any portion of a  
factory--built or masonry chimney. If this furnace is replacing a  
previously common-vented furnace, it may be necessary to resize  
the existing vent and chimney to prevent oversizing problems for  
the other remaining appliance(s). See Venting and Combustion Air  
Check” in this section. This furnace MUST be vented to the  
outside.  
S Masonry acid washing materials.  
Vent and Combustion Air Piping Guidelines  
This furnace is approved for venting with Schedule 40 PVC,  
CPVC, ABS fittings, and Cellular Core and SDR--26 PVC pipe.  
(1.) NOTE: In Canada, all pipe, fittings & cements  
must conform to applicable CSA standards or to  
local codes having jurisdiction.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
both the inlet and exhaust pipes 5(1.5m) for each additional  
elbow used. (See Table 3 or Table 4).  
13. The minimum vent length is 5(1.5m) of PVC.  
Applicable ASTM Standards for Vent Materials  
Cell  
Core  
Pipe  
Materi-  
als  
Sch. 40  
Pipe  
SDR  
Pipe  
Solv.  
Fittings  
Primer  
-- --  
Cement  
14. The piping can be run in the same chase or adjacent to  
supply or vent pipe for water supply or waste plumbing. It  
can also be run in the same chase with a vent from another  
90+ furnace.  
D2468  
&
D2661  
ABS  
D1527  
__  
F628  
F891  
D2235  
D2564  
NOTE: In NO case can the piping be run in a chase where  
temperatures can exceed 140° F (60° C). or where radiated heat  
from adjacent surfaces would exceed 140° F(60° C).  
D2466  
&
D2665  
PVC  
D1785 D2241  
F656  
CPVC  
F441  
-- --  
F442  
-- --  
-- --  
-- --  
F438  
-- --  
-- --  
-- --  
F493  
15. The vent outlet MUST be installed to terminate in the same  
atmospheric pressure zone as the combustion air inlet.  
ABS to  
PVC  
D3138  
16. The vent system can be installed in an existing unused  
chimney provided that:  
S Both the exhaust vent and air intake run the length of the  
(2.) Only use solvent cements that are marked for use  
with the specific venting material.  
chimney.  
(3.) ABS to PVC transition joints REQUIRE a special  
solvent cement that meets the requirements of  
ASTM D3138.  
S No other gas fired appliance or fireplace (solid fuel) is vented  
into the chimney.  
S The top of the chimney MUST be sealed flush or crowned up to  
seal against rain or melting snow so ONLY the piping protrudes.  
S The termination clearances shown in Fig. 8 are maintained.  
(4.) Refer to ASTM D2855 for general procedure to use  
for cementing plastic pipe and fittings.  
NOTE: In order to create a seal that allows future removal of pipe,  
RTV sealant MUST be used on the inlet pipe where it joins to the  
furnace.  
17. Furnace applications with vertical vents requiring vent  
diameter increaser fittings must have increaser fittings  
installed in vertical portion of the vent. Condensate will be  
trapped in the vent if the vent diameter is increased prior to  
having an elbow turned upward. This could cause nuisance  
tripping of the pressure switch.  
NOTE: All vent piping MUST be installed in compliance with  
local codes or ordinances, these instructions, good trade practices,  
and codes of country having jurisdiction.  
1. Determine the best routing and termination for the vent pipe  
and air inlet pipe by referring to all of the instructions and  
guidelines in this Section.  
Combustion Air and Vent Piping Insulation  
Guidelines  
2. Determine the size required for the vent pipe and air inlet  
pipe.  
NOTE: Use closed cell, neoprene insulation or equivalent. If  
Fiberglass or equivalent insulation is used it must have a vapor  
barrier. Use R values of 7 up to 10(3.1m), R--11 if exposure  
exceeds 10(3.1m). If Fiberglass insulation is used, exterior to the  
structure, the pipe MUST be boxed in and sealed against moisture.  
3. Loosely assemble all venting parts without adhesive (pipe  
joint cement) for correct fit before final assembly.  
4. Furnace shall be installed so as to prevent the accumulation  
of condensate.  
5. Use of vertical piping is preferred because there will be some  
moisture in the flue gases that may condense as it leaves the  
vent pipe (See Instructions for Horizontal Vents).  
1. When the vent or combustion air pipe height above the roof  
exceeds 30(76.2mm), or if an exterior vertical riser is used  
on a horizontal vent to get above snow levels, the exterior  
portion MUST be insulated.  
2. When combustion air inlet piping is installed above a  
suspended ceiling, the pipe MUST be insulated with  
moisture resistant insulation such as Armaflex or other  
equivalent type of insulation.  
6. The vertical vent pipe MUST be supported so that no  
weight is allowed to rest on the combustion blower.  
7. Exhaust vent piping or air inlet piping diameter MUST  
NOT be reduced.  
8. All exhaust vent piping from the furnace to termination  
3. Insulate combustion air inlet piping when run in warm,  
humid spaces.  
1
MUST slope upwards. A minimum of / (6.4mm) per foot  
4
(304.8mm) of run is required to properly return condensate  
to the furnace drain system.  
Sizing Combustion Air and Vent Pipe  
Consult Table 3 or Table 4 to select the proper diameter exhaust and  
combustion air piping. Exhaust and combustion air piping is sized  
for each furnace Btuh size based on total lineal vent length (on inlet  
or outlet side), and number of 90° elbows required.  
9. Use DWV type long radius elbows whenever possible, as  
they provide for the minimum slope on horizontal runs and  
they provide less resistance in the vent system. If DWV  
elbows cannot be used, use two, 45° elbows when possible.  
On horizontal runs the elbows can be slightly misaligned to  
provide the correct slope.  
10. All horizontal pipe runs MUST be supported at least every  
five feet (1.5 M) with galvanized strap or other rust resistant  
material. NO sags or dips are permitted.  
1. Double Pipe Installation--If installing as a direct--vent  
appliance, consult Table 4 to select the proper diameter  
exhaust and combustion air piping. Exhaust and combustion  
air piping is sized for each furnace Btuh size based on total  
lineal vent length (on inlet or outlet side), and number of  
90° elbows required.  
11. All vertical pipe runs MUST be supported every six feet  
2. Single Pipe Installation--If installing as a non--direct vent  
appliance, (single outlet pipe and no inlet pipe) refer to  
Table 3. The table shows the maximum number of elbows  
allowed with any given pipe diameter and length of run.  
3. Use of Elbows--Two 45° elbows can be substituted for one  
90° elbow. The elbow or elbows used for vent termination  
outside the structure ARE counted, including elbows needed  
to bring termination above expected snow levels.  
(4.8 M) where accessible.  
12. The maximum pipe length is 40(12.2m) total in the inlet or  
outlet side of the system. Up to five, 90° elbows can be used  
on the inlet or the outlet. With the Concentric Vent  
Termination Kits (KGAVT0701CVT or KGAVT0801CVT),  
the maximum pipe length is 35(10.7m) with four 90°  
elbows. If more elbows are required, reduce the length of  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If more than five elbows are required, reduce the length of both  
the inlet and exhaust pipes 5(1.5m) for each additional elbow  
used. If less than five elbow are required, the length can be  
INCREASED by 5(1.5m) for each additional elbow NOT  
used.  
Pipe Diameter Table  
Single Piping ONLY  
40,000, 50,000, 60,000 & 75,000 Btuh Furnaces  
Table 3  
40(12.2m) & (5) 90° elbows with 2(50.8mm) PVC pipe  
* Feet (M) of pipe is whichever pipe run is the longest, either  
inlet or outlet side.  
80,000 & 100,000 Btuh Furnace  
40(12.2m) & (5) 90° elbows with 3(76.2mm) PVC pipe  
For venting table, see“Concentric Termination Kit” in  
this manual.  
125,000 Btuh Furnace  
40(12.2m) & (5) 90° elbows with 3(76.2mm) PVC pipe  
Vent Termination Clearances  
The minimum vent length is 5’ (1.5m) of PVC. Elbows are  
DWV Long Radius Type for 2” (50.8mm) and 3” (76.2mm)  
vents.  
!
WARNING  
If more than five elbows are required, reduce the length of both  
the inlet and exhaust pipes 5(1.5m) for each additional elbow  
used. If less than five elbow are required, the length can be  
INCREASED by 5(1.5m) for each additional elbow NOT  
used.  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow this warning could result in personal injury  
or death.  
Inlet and outlet pipes may NOT be vented directly above each  
other.  
NOTE: It is allowable to use larger diameter pipe and fitting than  
shown in the tables but not smaller diameters than shown.  
1. Determine termination locations based on clearances  
specified in following steps and as shown in Fig. 8, 9, and  
22 through 30.  
Pipe Diameter Table  
Table 4  
Dual Piping ONLY  
40,000, 50,000, 60,000 & 75,000 Btuh Furnaces  
40(12.2m) & (5) 90° elbows with 2(50.8mm) PVC pipe  
For “Concentric Termination Kit” clearances, see Fig. 32, 33, 34,  
35 and 36 in this manual.  
80,000 & 100,000 Btuh Furnace  
40(12.2m) & (5) 90° elbows with 3(76.2mm) PVC pipe  
2. This furnace is Dual Certified and can be installed as a single  
pipe appliance (all combustion from inside the structure) or  
as a direct vent appliance where all combustion air is taken  
from outside the structure.  
3. For Direct Vent installation, refer to Fig. 8 for vent  
termination.  
125,000 Btuh Furnace  
40(12.2m) & (5) 90° elbows with 3(76.2mm) PVC pipe  
The minimum vent length is 5’ (1.5m) of PVC. Elbows are  
DWV Long Radius Type for 2” (50.8mm) and 3” (76.2mm)  
vents.  
4. For Single Pipe installation refer to Fig. 9 for vent  
termination clearances.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
V
V
12 inches (30 cm) for applieances >10,000 Btuh(3 kW)  
and < 100,000 Btuh(30kW), 36 inches (91cm) for  
appliances > 100,000 Btuh(30kW)  
A08600  
Fig. 8 -- Direct Vent Termination Clearance  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A08601  
Fig. 9 -- Other than Direct Vent Termination Clearance  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DO NOT trap the drain line in any other location than at the  
condensate drain trap supplied with the furnace.  
If possible, DO NOT route the drain line where it may freeze. The  
drain line must terminate at an inside drain to prevent freezing of  
the condensate and possible property damage.  
Condensate Drain Trap  
This furnace removes both sensible and latent heat from the  
products of combustion. Removal of the latent heat results in  
condensation of the water vapor. The condensate is removed from  
the furnace through the drains in the plastic transition and the vent  
fitting. The drains connect to the factory installed internally  
mounted condensate drain trap on the left or right side of the  
furnace.  
1. A condensate sump pump MUST be used if required by  
local codes, or if no indoor floor drain is available. The  
condensate pump must be approved for use with acidic  
condensate.  
The startup of a new furnace will involve a cycle or two of the  
furnace to properly prime the condensate trap with water. Until the  
trap is fully primed, some condensate will be pulled into the  
combustion blower. The furnace may cycle on the pressure switch  
connected to the plastic transition box due to condensate buildup.  
After the trap is primed, the condensate will start draining from the  
furnace. The combustion blower will clear out any remaining  
condensate in the blower housing through the vent fitting  
2. A plugged condensate drain line or a failed condensate  
pump will allow condensate to spill. If the furnace is  
installed where a condensate spill could cause damage, it is  
recommended that an auxiliary safety switch be installed to  
prevent operation of the equipment in the event of pump  
failure or plugged drain line. If used, an auxiliary safety  
switch should be installed in the R circuit (low voltage)  
ONLY.  
3. If the auxiliary switch in the condensate pump is used, the  
furnace may shut down due to a blocked condensate line or  
failed pump. To prevent frozen water pipes see the “Frozen  
Water Pipe Hazard” section of this manual.  
downstream of the blower. Note that the condensate trap can also be  
1
primed by pouring water into the / (12.7mm) drain hose.  
2
1
Remove the / (12.7mm) ID drain hose from either the gutter or  
2
the white PVC tee trap. Using a funnel pour eight (8) ounces (30  
1
ml) of water into / (12.7mm) ID drain hose. Water will flow  
2
through the drain hose and into the condensate drain trap. This will  
prime both the vent and the transition sides of the trap. Reconnect  
!
CAUTION  
1
the / (12.7mm) ID drain hose to the original component, either  
2
the gutter or the PVC tee trap.  
FROZEN AND BURST WATER PIPE HAZARD  
The condensate drain trap supplied with the furnace MUST be  
used. The drain connection on the condensate drain trap is sized for  
Failure to follow this caution may result in property damage.  
3
1
If a condensate pump is installed, a plugged condensate drain  
or a failed pump may cause the furnace to shut down. Do not  
leave the home unattended during freezing weather without  
turning off water supply and draining water pipes or otherwise  
protecting against the risk of frozen pipes.  
/ (19.1mm) PVC or CPVC pipe, however alternate / ″  
4
2
5
(12.7mm) CPVC [nominal / (15.9mm) O.D.] or vinyl tubing  
with a minimum inner diameter (I.D.) of / (15.9mm) may also be  
8
5
8
used, as allowed by local codes. Alternate drain pipes and hoses  
may be used as allowed by local codes.  
1
The drain line must maintain a / (6.4mm) per foot (304.8mm)  
4
1
downward slope toward the drain. / (6.4mm) per foot  
4
Condensate Drain Trap Freeze Protection  
(304.8mm) is recommended. Installation of an overflow line is  
1
recommended when the / (6.4mm) per foot (304.8mm) slope to  
4
Special precautions MUST be made if installing furnace in an area  
which may drop below freezing. This can cause improper operation  
or damage to the equipment. If the the furnace environment has the  
potential of freezing, the drain trap and drain line must be protected.  
Use 3 to 6 watt per foot at 115 volt, 40° F (4°C) self--regulating  
shielded and waterproof heat tape. Wrap the drain trap and drain  
line with the heat tape and secure with the ties. Follow the heat tape  
manufacturer’s recommendations. Prime the trap before furnace  
operation.  
the condensate drain cannot be maintained. A drain tube clip is  
included in the furnace to prevent kinking/buckling of the drain  
tube. The clip should remain in the furnace (between the door  
switch plate and the blower shelf, Fig. 10) during operation. See  
Fig. 20 for proper routing and installation of the overflow.  
Drain Tube  
Clip  
Blower  
Door  
Shelf  
Switch  
Representative drawing only, some models may vary in appearance.  
A07705  
Fig. 10 -- Drain Tube Clip Location  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
On Some Models  
ONLY  
Plastic Caps (2)  
Yellow or black  
Coupling & Clamps  
(Optional)  
Vent Drain  
& Clamps  
V
E
N
T
Single Pressure Switch  
Relief Tube  
ON  
OFF  
Dual Pressure Switch Detail  
3
Black Rubber /  
(4.8mm) ID  
16  
Drain Tee  
Drain Tube  
Black Rubber  
1
/ (12.7mm) ID &  
2
Clamps  
Drain Tube  
Street Elbow  
1
Corrugated  
/ (12.7mm) CPVC  
2
5
/ (15.9mm) ID &  
8
(Loose parts bag)  
Clamps  
Drain Connector Black PVC  
3
1
/ (18.1mm) PVC X / ″  
4
2
(12.7mm) CPVC (Loose  
parts bag)  
Casing Grommet  
Black Rubber  
(15.9mm) ID  
(Loose parts bag)  
3
Drain Line Vent Tee / ″  
4
5
Drain Tube Black Rubber / (15.9mm) ID &  
8
1
(18.1mm) PVC or / (12.7mm)  
CPVC (Field supplied)  
2
Clamps, Cut length to fit (Loose parts bag)  
2 5 -- 2 4 -- 6 7  
Representative drawing only, some models may vary in appearance.  
A07706  
Fig. 11 -- Upflow Installations Top Vent  
Upflow Installations Top Vent (See Fig. 11)  
Remove knockout from the side of the furnace casing where drain  
Glue the CPVC street elbow to the trap using appropriate cleaner  
and solvent cement.  
tube will exit.  
5
3
1
Install casing grommet [black rubber / (15.9mm) ID grommet --  
The field supplied / (18.1mm) PVC or / (12.7mm) CPVC  
8
4
2
in loose parts bag].  
drain line vent tee must vent outside the furnace cabinet (see  
exploded view above).  
1
Install the / (12.7mm) CPVC street elbow on discharge of trap  
2
3
1
Note: It is recommended that all PVC piping and fitting  
connections be fit up and inspected before final cementing. Trap  
must be primed before operation. Verify all condensate drain  
connections are securely clamped. A coupling and clamps (in loose  
part bag) may be installed as shown for future servicing of the vent  
system.  
Install the black PVC tube connector [ / (18.1mm) PVC x / ″  
(12.7mm) CPVC from loose parts bag] as shown in the illustration  
above.  
4
2
5
Cut the black drain tube [ / (15.9mm) ID -- in loose parts bag] to  
length to fit between trap and tube connector through grommet.  
Clamp both ends of the drain tube using clamps provided.  
8
NOTE: “PVC” is used as a generic term. Pipe and fitting materials used must be acceptable to the local code officials hav-  
ing jurisdiction.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Plastic Cap  
Yellow or black  
On Some Models  
ONLY  
2(50.8mm) PVC  
Coupling  
Coupling & Clamps  
(Optional)  
Vent Drain  
& Clamps  
Either: The PVC  
Drain Tee or a field  
supplied 2″  
V
E
N
T
Single Pressure Switch  
ON  
(50.8mm) PVC Tee  
OFF  
Dual Pressure Switch Detail  
Relief Tube  
Black Rubber /  
(4.8mm) ID  
3
16  
Tee Trap White PVC  
(loose parts bag)  
Drain Tube  
Black Rubber  
1
/ (12.7mm) ID  
2
Drain Tube  
& Clamps  
Corrugated  
5
/ (15.9mm) ID  
8
& Clamps  
Drain Connector Black PVC  
/ (19.1mm) PVC X / ″  
3
1
4
2
SIDE VIEW  
(12.7mm) CPVC  
(Loose parts bag)  
Rotate downward  
5° to 10°  
Casing Grommet  
Black Rubber  
5
/ (15.9mm) ID  
8
(Loose parts bag)  
NOTE: Built--in channel will  
be angled 5° to 10° also.  
3
1
Drain Line Vent Tee / (18.1mm) PVC or / ″  
4
2
(12.7mm) CPVC (Field supplied)  
2 5 -- 2 4 -- 6 7 a  
Representative drawing only, some models may vary in appearance.  
A07707  
Fig. 12 -- Upflow Installations Vent through Left Side  
Upflow Installations Vent through Left--Side (See Fig. 12)  
5
Remove drain tee from inducer discharge and remove black drain  
Cut the black drain tube [ / (15.9mm) ID -- in loose parts bag] to  
8
1
tube / (12.7mm) ID from bottom of drain tee.  
length to fit between trap and tube connector through grommet.  
2
Install Vent Pipe grommet in side of casing.  
Clamp both ends of the drain tube using clamps provided.  
Cut an appropriate length of 2(50.8mm) PVC pipe long enough  
to exit the cabinet and connect the vent drain to either:  
Glue the CPVC street elbow to the trap using appropriate cleaner  
and solvent cement.  
S A 2(50.8mm) PVC coupling fastened onto the drain tee  
Connect the tee trap and the main drain line exiting the casing as  
shown in Fig. 12  
Install tee trap into bottom of tee.  
Note: It is recommended that all PVC piping and fitting  
connections be fit up and inspected before final cementing. Both  
the internal trap and the external tee trap must be primed  
before operation. Verify all condensate drain connections are  
securely clamped. A coupling and clamps (in loose part bag) may  
be installed as shown for future servicing of the vent system.  
Remove knockout from the side of the furnace casing where drain  
tube will exit.  
1
Install the / (12.7mm) CPVC street elbow on discharge of trap  
2
3
1
Install the black PVC drain connector [ / (19.1mm) PVC x / ″  
4
2
CPVC from loose parts bag] as shown in the illustration above.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Plastic Cap  
Yellow or black  
On Some Models  
ONLY  
Dual Pressure Switch  
Either: The PVC Drain  
Tee or a field supplied  
2(50.8mm) PVC Tee  
Vent Drain  
& Clamps  
Relief Tube  
Black Rubber  
3
/ ″ ⟨4.8mm) ID  
16  
V
E
N
T
Single Pressure Switch Details  
ON  
OFF  
2(50.8mm)  
PVC  
Coupling  
Drain Tube  
Corrugated  
5
/ (15.9mm) ID &  
8
Tee Trap White PVC  
(loose parts bag)  
Clamps  
Elbow Tubes (2) Black Rubber  
1
/ (12.7mm) ID & Clamps  
2
(loose parts bag)  
1
3
Barbed Coupling, / (12.7mm) OD  
2
Drain Line Vent Tee / ″  
4
1
(loose parts bag)  
(18.1mm) PVC or / ″  
2
(12.7mm) CPVC (Field sup-  
plied)  
SIDE VIEW  
Rotate  
downward  
5° to 10°  
Drain Connector Black PVC  
3
1
/ (19.1mm) PVC X / ″  
4
2
(12.7mm) CPVC  
(Loose parts bag)  
Casing Grommet  
NOTE: Built--in channel will  
be angled 5° to 10° also.  
5
Black Rubber / (15.9mm) CPVC  
8
2 5 -- 2 4 -- 6 8  
(Loose parts bag)  
A07708  
Fig. 13 -- All Models Vent Through Right Side  
All Models Vent through Right--Side (See Fig. 13)  
Disconnect the black drain tube between the drain vent and the trap.  
1
Install the / (12.7mm) CPVC street elbow on discharge of trap.  
2
3
1
Rotate the inducer 180° for a right side vent after loosening the four  
(4) inducer attachment screws. Reinstall and retighten the inducer  
screws to 20 in. lb. (2.3Nm) torque.  
Install the black PVC tube connector [ / (19.1mm) PVC x / ″  
4
2
(12.7mm) CPVC from loose parts bag] as shown in the illustration  
above.  
1
5
Using the / (12.7mm) OD barbed coupling in the loose parts bag  
Cut the black drain tube [ / (15.9mm) ID -- in loose parts bag] to  
length to fit between trap and tube connector through grommet.  
2
8
1
connect together with the two short / (12.7mm) ID elbow tubes  
2
and connect the lower discharge port of the vent drain to the trap.  
Secure all connections with clamps.  
Clamp both ends of the drain tube using clamps provided.  
Glue the CPVC street elbow to the trap using appropriate cleaner  
and solvent cement.  
Install the vent pipe grommet into the casing  
Cut an appropriate length of 2(50.8mm) PVC pipe long enough  
to exit the cabinet and connect the vent drain to either:  
S A 2(50.8mm) PVC coupling fastened onto the drain tee  
Connect the tee trap and the main drain line exiting the casing as  
shown in Fig. 13  
NOTE: It is recommended that all PVC piping and fitting  
connections be fit up and inspected before final cementing. Both  
the internal trap and the external tee trap must be primed  
before operation. Verify all condensate drain connections are  
securely clamped. A coupling and clamps (in loose part bag) may  
be installed as shown for future servicing of the vent system.  
Install tee trap into bottom section of tee.  
Remove knockout from the side of the furnace casing where drain  
tube will exit.  
5
Install casing grommet black rubber [ / (15.9mm) ID grommet --  
8
in loose parts bag]  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SIDE VIEW  
Plastic Cap  
Yellow or black  
Rotate downward  
5° to 10°  
Coupling & Clamps  
(Optional)  
2(51 mm) PVC Coupling  
NOTE: Built--in channel will  
be angled 5° to 10° also.  
Vent Drain  
& Clamps  
Either: The PVC  
Drain Tee or a field  
supplied 2(51 mm)  
PVC Tee  
Relief Tube  
3
Dual Pressure Switch  
Black Rubber / (5 mm) ID  
16  
Single Pressure Switch Detail  
On Some Models  
ONLY  
INLET  
Drain Tube  
Flexible Tubing Connector,  
3
Tee Trap White PVC  
(loose parts bag)  
Black Rubber  
/
16  
(5 mm) OD (loose parts bag)  
1
/ ID (13 mm) & Clamps  
2
Elbow Tube Black Rubber  
Relief Tube,  
1
/ ID (13 mm) & Clamps  
2
Extension Black Rubber,  
(Loose Parts Bag)  
3
/ (5 mm) ID Cut to fit  
16  
F
O F  
(loose parts bag)  
WARNING  
O N  
Move Caps to  
top of trap  
Trap Connection  
“Clamp ears”  
Pointed OUT  
5
Drain Tube Black, / (16 mm) ID Corrugated  
8
Cut at straight section  
1
Barbed Coupling / (13 mm) OD  
2
(loose parts bag)  
Preassemble &  
insert into furnace  
Cut Here  
Leave room for clamp  
25--24--69  
A07767  
Fig. 14 -- Downflow Left--Side Vent and Trap  
Downflow Left--Side Vent and Trap (See Fig. 14).  
Remove the inducer mounting screws, rotate the inducer 180° and  
retighten the inducer screws to 20pounds torque.  
Disconnect the hoses from the trap assembly, and remove trap and  
trap mounting bracket from the blower compartment. Using cover  
plate and gasket provided in the loose parts bag, cover the hole  
from the burner compartment to the blower compartment and  
secure with screws.  
some cases, additional hose length will be needed. Use the clear  
3
plastic / (4.8mm) OD flexible tubing connector and a suitable  
16  
3
length of extra / (4.8mm) ID hose to make this connection.  
16  
Install the vent pipe grommet into the casing  
Cut an appropriate length of 2(50.8mm) PVC pipe long , enough  
to exit the cabinet and connect the vent drain to either:  
S A 2(50.8mm) PVC coupling fastened onto the drain tee  
Move the caps to the top of the trap and mount the trap externally  
to the left side of the unit using the two(2) screws provided.  
Install tee trap into bottom section of tee and glue pipe.  
Remove knockout from the side of the furnace casing where drain  
tube will exit.  
Connect the tee trap and the main drain line exiting the casing as  
shown in Fig. 14.  
5
Cut the / (15.9mm) ID corrugated hose as shown above and  
8
fasten the 90° bend end to the trap and fasten the straight end to the  
transition drain. Secure both connections with clamps.  
1
Reconnect the / (12.7mm) ID drain hose from the vent drain to  
2
NOTE: It is recommended that all PVC piping and fitting  
connections be fit up and inspected before final cementing. Both  
the external trap and the external tee trap must be primed  
before operation. Verify all condensate drain connections are  
securely clamped. A coupling and clamps (in loose part bag) may  
be installed as shown for future servicing of the vent system.  
the trap and secure with a clamp. In some cases, additional length  
1
will be required for this hose. Use the Black plastic / (12.7mm)  
2
1
OD barbed coupling and a suitable section of / (12.7mm) ID  
2
hose to make the connection. Secure all connections with clamps  
3
Connect the / (4.8mm) ID relief tube from the small port on the  
16  
trap to the top port of the transition as shown in the picture. In  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Plastic Cap  
Yellow or black  
Trap Connection  
“Clamp ears”  
Pointed OUT  
Elbow Tube Black Rubber  
Vent Drain  
& Clamps  
1
/ (13 mm) ID & Clamps  
Relief Tube  
2
Preassemble &  
insert into furnace  
(Loose Parts Bag)  
Black Rubber  
3
SIDE VIEW  
/ (5 mm) ID  
16  
Coupling & Clamps  
(Optional)  
Barbed Coupling  
1
Rotate downward  
5° to 10°  
/ (13 mm) OD  
2
(Loose Parts Bag)  
Drain Hose  
Black Rubber  
1
/ (13 mm) ID Cut to  
2
Dual Pressure Switch  
Fit & Clamps  
NOTE: Built--in channel will  
be angled 5° to 10° also.  
On Some  
Models  
ONLY  
2(51 mm) PVC Coupling  
Either: The PVC  
Single Pressure Switch Detail  
Drain Tee or a field  
supplied 2(51 mm) PVC Tee  
Tee Trap White PVC  
(loose parts bag)  
Drain Tube Corrugated  
5
Black, / (16 mm)  
Drain Connector Black  
3
8
F
O F  
ID & Clamps  
PVC / ″  
(19 mm)  
4
WARNING  
Move Caps to  
top of trap  
1
O N  
PVC X / ″  
(13 mm)″  
2
CPVC (Loose parts bag)  
Drain Tube Black Rubber,  
5
/ ID (16 mm) Cut to fit & Clamps  
8
(loose parts bag)  
A07768  
Fig. 15 -- Downflow Right--Side Vent and Trap  
Downflow Right--Side Vent and Trap (See Fig. 15)  
Remove the drain tee if installed.  
Install the vent pipe grommet into the casing  
Disconnect the hoses from the trap assembly, and remove trap and  
trap mounting bracket from the blower compartment. Using cover  
plate and gasket provided in the loose parts bag, cover the hole  
from the burner compartment to the blower compartment and  
secure with screws.  
Cut an appropriate length of 2(50.8mm) PVC pipe long , enough  
to exit the cabinet and connect the vent drain to either:  
S A 2(50.8mm) PVC coupling fastened onto the drain tee  
Install tee trap into bottom section of tee and glue pipe.  
Remove knockout from the side of the furnace casing where drain  
tube will exit.  
Move the caps to the top of the trap and mount the trap externally  
to the right side of the unit using the two(2) screws provided.  
Connect the tee trap and the main drain line exiting the casing as  
shown in Fig. 15.  
Connect the corrugated drain tube from the transition box to the  
trap as shown. If an extension is required, use the black PVC tube  
NOTE: Note: It is recommended that all PVC piping and fitting  
connections be fit up and inspected before final cementing. Both  
the external trap and the external tee trap must be primed  
before operation. Verify all condensate drain connections are  
securely clamped. A coupling and clamps (in loose part bag) may  
be installed as shown for future servicing of the vent system.  
5
connector and the black / (15.9mm) ID drain tube in the loose  
8
parts bag. Cut tube to length. Secure all connections with clamps.  
Connect the drain hose from the Vent Drain to the trap. If an  
1
extension is required, use the black / (12.7mm) OD barbed  
2
1
coupling, connect a black / (12.7mm) ID elbow tube and a  
2
1
suitable section of a / (12.7mm) ID drain tube to make  
2
connection from the vent drain to the trap. Secure all connections  
with clamps.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Single Pressure Switch Detail  
Vent Drain  
& Clamps  
Plastic Caps  
Yellow or black  
Trap Connection  
“Clamp ears”  
Pointed OUT  
W
O
L F  
A I R  
Preassemble &  
insert into furnace  
Alternate Orientation  
Relief Tube Black Rubber  
3
/ (4.8mm) ID  
16  
Dual Pressure Switch  
Flexible tubing connector  
3
/
(4.8mm) OD (Loose  
16  
Parts Bag)  
Relief Tube Extension  
3
Black Rubber  
/
(4.8mm) ID  
16  
W O F L R A I  
Cut to Fit (Loose Parts Bag)  
Drain Tube Corrugated  
5
/ (15.9mm) ID & Clamps  
8
Remove KO before  
mounting Trap  
Cut at straight section  
Drain Tube  
Field  
Supplied Tee  
Black Rubber  
Coupling & Clamps  
(Optional)  
1
/ (12.7mm) ID  
2
& Clamps  
Tee Trap White PVC  
(loose parts bag)  
Cap and Clamp  
Open End  
Leave room for clamp  
Cut Here  
2 5 -- 2 4 -- 7 0  
Representative drawing only, some models may vary in appearance.  
A07709  
Fig. 16 -- Horizontal Left through Top  
Horizontal Left through Top (See Fig. 16)  
Disconnect the hoses from the trap assembly, and remove trap and  
trap mounting bracket from the blower compartment. Using cover  
plate and gasket provided in the loose parts bag, cover the hole  
from the burner compartment to the blower compartment and  
secure with screws.  
3
Connect the / (4.8mm) ID relief tube to the middle port on the  
16  
3
trap. If an extension is required, use the / (4.8mm) OD flexible  
tubing connector and the black / (4.8mm) ID relief tube in the  
loose parts bag. Cut tube to length. Secure all connections with  
clamps.  
16  
3
16  
Remove knockout from the side of the furnace casing where drain  
tube will exit.  
Cut an appropriate length of 2(50.8mm) PVC pipe, long enough  
to exit the cabinet and connect the vent drain to either:  
S A 2(50.8mm) PVC coupling fastened onto the drain tee  
Mount the trap externally to the bottom side of the unit using the  
two screws provided in the location shown.  
Install tee trap into bottom section of tee and glue pipe.  
Cut the corrugated tube as shown in the illustration above. Connect  
the corrugated hose from the transition to the trap. Secure  
connections with clamps.  
Connect the tee trap and the main drain line exiting the casing as  
shown in Fig. 16.  
NOTE: It is recommended that all PVC piping and fitting  
connections be fit up and inspected before final cementing. Both  
the external trap and the external tee trap must be primed  
before operation. Verify all condensate drain connections are  
securely clamped. A coupling and clamps (in loose part bag) may  
be installed as shown for future servicing of the vent system.  
1
Remove the black / (12.7mm) ID drain tube from the drain tee.  
2
Install a yellow cap and clamp over the open drain port of the drain  
tee.  
1
Connect the black / (12.7mm) ID drain tube from the Vent Drain  
2
to the trap. Secure connections with clamps.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Single Pressure Switch Detail  
Alternate Orientation  
Yellow or black  
Plastic Cap  
Field  
Supplied Tee  
Level or Sloped towards Tee  
Dual Pressure Switch  
Vent Drain  
& Clamps  
Relief Tube Black Rub-  
3
ber  
/
16  
(4.8mm) ID  
1
Elbow Tube Black Rubber / (12.7mm)  
2
AIR FLOW  
ID & Clamps (Loose Parts Bag)  
1
Barbed Coupling / (12.7mm) OD  
2
(Loose Parts Bag)  
Tee Trap White PVC  
(loose parts bag)  
Drain Tube Black Rubber  
1
/ (12.7mm) ID & Clamps  
2
On Some  
Models ONLY  
Drain Tube Corrugated  
5
/ (15.9mm) ID & Clamps  
8
3
Flexible Tube Connector  
/
16  
(4.8mm) OD (Loose Parts Bag)  
Cut at straight section  
Relief Tubing Extension  
3
Black Rubber  
/
16  
(4.8mm) ID  
WARNING  
Move Caps to  
top of trap  
Cut to Fit (Loose Parts Bag)  
Leave room for clamp  
Cut Here  
25--24--70a  
Representative drawing only, some models may vary in appearance.  
A07710  
Fig. 17 -- Horizontal Left--Side Vent  
Horizontal Left--Side Vent (See Fig. 17)  
3
Remove the drain tee from the Vent Drain if installed.  
Connect the / (4.8mm) ID relief tube to the middle port on the  
16  
3
trap. If an extension is required, use the / (4.8mm) OD flexible  
tubing connector and the black / (4.8mm) ID relief tube in the  
loose parts bag. Cut tube to length.  
16  
Rotate the inducer 180° for a side vent after loosening the 4 inducer  
attachment screws. Reinstall and retighten the inducer screws to 20  
in. lbs. (2.3 Nm) torque.  
3
16  
Cut an appropriate length of 2(50.8mm) PVC pipe, fittings and  
extension pipe long enough to exit the cabinet and connect the vent  
drain to either:  
Disconnect the hoses from the trap assembly, and remove trap and  
trap mounting bracket from the blower compartment. Using cover  
plate and gasket provided in the loose parts bag, cover the hole  
from the burner compartment to the blower compartment and  
secure with screws.  
S A 2(50.8mm) PVC coupling fastened onto the drain tee  
Install tee trap into bottom section of tee and glue pipe.  
Remove knockout from the side of the furnace casing where drain  
tube will exit.  
Important: The pipe to the tee trap must be level or sloping towards  
the tee trap  
Mount the trap externally to the bottom side of the unit using the  
two screws provided in the location shown.  
Connect the tee trap and the main drain line exiting the casing as  
shown in Fig. 17.  
Cut the corrugated tube as shown in the illustration above. Connect  
the corrugated hose from the transition to the trap. Secure  
connections with clamps.  
NOTE: It is recommended that all PVC piping and fitting  
connections be fit up and inspected before final cementing. Both  
the external trap and the external tee trap must be primed before  
operation. Verify all condensate drain connections are securely  
clamped. A coupling and clamps (in loose part bag) may be  
installed as shown for future servicing of the vent system.  
1
Connect the black / (12.7mm) ID drain tube from the Vent Drain  
2
1
to the trap. If an extension is required, use the black / (12.7mm)  
OD flexible tubing connector and the black / (12.7mm) ID drain  
2
1
2
tube in the loose parts bag. Cut tube to length. Secure connections  
with clamps.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Alternate Orientation  
Single Pressure Switch Detail  
Trap Connection  
“Clamp ears”  
Pointed OUT  
3
/
(4.8mm) ID Rub-  
16  
ber Tube  
Plastic Cap  
Yellow or black  
AIRFLOW  
Coupling & Clamps  
(Optional)  
Preassemble &  
insert into furnace  
Drain Tube Black  
1
Vent Drain  
& Clamps  
Rubber / (12.7mm)  
2
ID & Clamps  
Field  
Supplied Tee  
WARNING  
Add Cap and Clamp  
Relief Tube Black Rub-  
3
ber / (4.8mm) ID  
16  
Flexible Tubing Connector  
3
/
(4.8mm) OD (Loose  
16  
Parts Bag)  
Tee Trap White PVC  
(loose parts bag)  
Relief Tube Extension  
3
Black Rubber / (4.8mm) ID  
16  
INLET  
Cut to Fit (Loose Parts Bag)  
On Some Models  
ONLY  
Dual Pressure Switch  
1
Barbed Coupling / (12.7mm)  
2
OD (Loose Parts Bag)  
5
Drain Tube Corrugated / (15.9mm) ID &  
Clamps Cut at straight section  
8
Drain Tube Black Rubber  
1
/ (12.7mm) ID & Clamps  
2
Remove KO before  
mounting Trap  
Cut Here  
Leave room for clamp  
2 5 -- 2 4 -- 7 0 b  
Representative drawing only, some models may vary in appearance.  
A07711  
Fig. 18 -- Horizontal Right through Top  
Horizontal Right through Top (See Fig. 18)  
3
Disconnect the hoses from the trap assembly, and remove trap and  
trap mounting bracket from the blower compartment. Using cover  
plate and gasket provided in the loose parts bag, cover the hole  
from the burner compartment to the blower compartment and  
secure with screws.  
Connect the / (4.8mm) ID relief tube to the middle port on the  
16  
3
trap. If an extension is required, use the clear  
flexible tubing connector and the black / (4.8mm) ID relief tube  
in the loose parts bag. Cut tube to length.  
Cut an appropriate length of 2(50.8mm) PVC pipe, fittings and  
extension pipe long enough to exit the cabinet and connect the vent  
drain to a standard field supplied 2(50.8mm) PVC tee  
/
16  
(4.8mm) OD  
3
16  
Remove knockout from the side of the furnace casing where drain  
tube will exit.  
S A 2(50.8mm) PVC coupling fastened onto the drain tee  
Mount the trap externally to the bottom side of the unit using the  
two(2) screws provided in the location shown.  
Install tee trap into bottom section of tee and glue pipe.  
Cut the corrugated tube as shown in the illustration above. Connect  
the corrugated hose from the transition to the trap. Secure  
connections with clamps.  
Connect the tee trap and the main drain line exiting the casing as  
shown in Fig. 18.  
NOTE: It is recommended that all PVC piping and fitting  
connections be fit up and inspected before final cementing. Both  
the external trap and the external tee trap must be primed  
before operation. Verify all condensate drain connections are  
securely clamped. A coupling and clamps (in loose part bag) may  
be installed as shown for future servicing of the vent system.  
1
Connect the black / (12.7mm) ID drain tube from the Vent Drain  
2
1
to the trap. If an extension is required, use the black / (12.7mm)  
2
1
OD barbed coupling and the black / (12.7mm) ID drain tube in  
2
the loose parts bag. Cut tube to length. Secure connections with  
clamps.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Plastic Cap  
Yellow or black  
Coupling & Clamps  
(Optional)  
Single Pressure Switch Detail  
AIR FLOW  
Field  
Supplied Tee  
Vent Drain  
& Clamps  
Level or Sloped  
towards Tee  
Tee Trap  
White PVC  
(loose parts bag)  
Elbow Tube Black Rubber  
Relief Tube  
Black Rubber  
(4.8mm) ID  
1
/ (12.7mm) ID & Clamps  
3
2
/ ″  
16  
(Loose Parts Bag)  
On Some Models  
ONLY  
3
Flexible Tubing Connector /  
16  
INLET  
(4.8mm) OD (Loose Parts Bag)  
Relief Tube Extension  
3
Alternate Orientation  
Black Rubber / (4.8mm) ID  
16  
Cut to Fit (Loose Parts Bag)  
Remove KO before  
mounting Trap  
Dual Pressure Switch  
5
Drain Tube Black, / (15.9mm) ID & Clamps  
8
Drain Tube  
1
Corrugated Cut at straight section  
Barbed Coupling / (12.7mm)  
2
Black Rubber  
OD (Loose Parts Bag)  
1
/ (12.7mm) ID  
2
& Clamps  
Leave room for clamp  
2 5 -- 2 4 -- 7 0 c  
Cut Here  
Representative drawing only, some models may vary in appearance.  
A07712  
Fig. 19 -- Horizontal Right Side Vent  
Horizontal Right -Side Vent (See Fig. 19)  
Disconnect drain tee if installed  
Cut an appropriate length of 2(50.8mm) PVC pipe, fittings and  
extension pipe long enough to exit the cabinet and connect the vent  
drain to either:  
Disconnect the hoses from the trap assembly, and remove trap and  
trap mounting bracket from the blower compartment. Using cover  
plate and gasket provided in the loose parts bag, cover the hole  
from the burner compartment to the blower compartment and  
secure with screws.  
S A 2(50.8mm) PVC coupling fastened onto the drain tee  
Install tee trap into bottom section of tee and glue pipe.  
Important: The pipe to the tee trap must be level or sloping towards  
the tee trap  
Remove knockout from the side of the furnace casing where drain  
tube will exit.  
Connect the tee trap and the main drain line exiting the casing as  
shown in Fig. 19.  
Mount the trap externally to the bottom side of the unit using the  
two(2) screws provided in the location shown.  
Cut the corrugated tube as shown in the illustration above. Connect  
the corrugated hose from the transition to the trap. Secure  
connections with clamps.  
NOTE: It is recommended that all PVC piping and fitting  
connections be fit up and inspected before final cementing. Both  
the external trap and the external tee trap must be primed  
before operation. Verify all condensate drain connections are  
securely clamped. A coupling and clamps (in loose part bag) may  
be installed as shown for future servicing of the vent system.  
1
Connect the black / (12.7mm) ID drain tube from the Vent Drain  
2
1
to the trap. If an extension is required, use the / (12.7mm) OD  
2
1
barbed coupling and the black / (12.7mm) ID drain tube in the  
2
loose parts bag. Cut tube to length. Secure connections with  
clamps.  
3
Connect the / (4.8mm) ID relief tube to the middle port on the  
trap. If an extension is required, use the clear  
splice connector and the black / (4.8mm) ID relief tube in the  
16  
3
/
16  
(4.8mm) OD  
3
16  
loose parts bag. Cut tube to length.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connecting Vent and Combustion Air Piping  
!
WARNING  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow this warning could result in personal injury  
or death.  
V
E
N
T
ON  
Cement or mechanically seal all joints, fittings, etc. to prevent  
leakage of flue gasses.  
Open Tee  
OFF  
Refer to Fig. 11 through Fig. 19 that corresponds to the installation  
position of the furnace for the application.  
Preassemble the vent and combustion air piping from the furnace to  
the vent termination. Do not cement the pipe joints until the pipe  
preassembly process is complete.  
Tee Trap  
Combustion Air Pipe Connection (Direct Vent)  
Install the air intake coupling and gasket to the furnace with the  
four(4) screws.  
Evaporator  
Coil  
Drain Line  
(Optional)  
Note: The air intake coupling and gasket can be installed to the top  
panel to the alternate air intake locations on either the left or right  
side panels of the furnace.  
For downflow installation, the air intake coupling and gasket must  
be installed to the alternate air intake location on either the left or  
right side panels. Remove the 3(76.2mm) hole plug from the  
furnace accessory bag and relocate to the open hole in the furnace  
Main  
Drain  
Line  
panel. Use four screws to seal the four mounting holes in the top  
7
panel next to the hole plug. Drill four / (2.8mm) diameter holes  
64  
Condensate  
Trap  
in the casing using the air intake coupling as the template.  
The air intake coupling is sized for 2(50.8mm) PVC pipe.  
Representative drawing only, some models may vary in appearance.  
Install the combustion air pipe to the air intake coupling using RTV  
sealant to provide for future serviceability.  
A07713  
Fig. 20 -- Connecting Tee Trap to Condensate Trap and Main  
Drain Line  
Vent Pipe Connection  
Install the vent pipe grommet to the furnace panel. Locate the  
grommet in the furnace panel at a location directly away from the  
vent fitting on the combustion blower. The grommet snaps into the  
3(76.2mm) hole from the furnace panel. NOTE: Depending on  
the installation position, the vent pipe grommet will be installed to  
the top panel or to the alternate location on the side panels. If  
needed, remove the 3(76.2mm) hole plug from the loose parts bag  
and install it in the open hole in the furnace panel. (See Fig. 11 or  
Fig. 20)  
The tee trap must be connected to the main condensate drain line as  
conceptually shown above. Different installations may require  
slightly different orientations. The following steps apply to all  
installations.  
1. The tee trap should be installed as close to the side or top of  
the furnace as practical. Minimize the distance between the  
inducer and the tee trap as much as possible.  
2. An open tee is to be used at the tee trap discharge. The top  
end of the tee should be open to the atmosphere to eliminate  
potential air lock problems.  
3. The drain line from the tee trap is to be connected to the  
furnace condensate trap drain line as shown above.  
Install the vent pipe to the rubber coupling, the vent fitting or the  
PVC vent extension pipe. Securely attach using the clamp or PVC  
cement as required.  
NOTE: The vent fitting MUST be installed with the air flow  
marking arrow pointed toward the vent pipe. (See Fig. 21).  
Some installations require the vent fitting to be installed with a  
5° to 10° downward slope. (See Fig. 11 thru Fig. 20)  
4. Condensate drain lines from a cooling coil may be  
connected downstream of the connection point of the tee  
trap and furnace condensate trap.  
Important: Prime both traps with water before operation.  
Failure to prime the traps may result in discharge of flue gases from  
the condensate drain line and open tee for a period of time, and may  
result in temporary lockout of the furnace upon start up. Main drain  
line construction is left to the discretion of the installer. It may be  
made of either ridged pipe or flexible tube. Tube ID should NOT  
1
be less than / (12.7mm).  
2
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connecting Vent Pipes and Termination  
Vent Pipe  
(Top Panel Exit)  
Rubber Coupling  
& Clamps  
NOTE: Combustion air intake and vent MUST terminate in the  
same atmospheric pressure zone. If installation is in a cold climate  
(sustained temperatures 0°F (--17°C) and below for 24 or more  
consecutive hours), increase the minimum distance between vent  
pipe and air intake from 8(203.2mm) to 18(457.2mm).  
NOTE: The 90° elbow is approved  
for use inside the furnace ONLY.  
Vent Pipe  
Vent Fitting  
& Clamps  
90° Elbow  
!
WARNING  
Combustion  
Blower  
CARBON MONOXIDE POISONING HAZARD  
Failure to properly vent this furnace could result in personal  
injury or death.  
Maintain a minimum of 36(914.4mm) between  
combustion air inlet and clothes dryer vent. Terminate  
the combustion air intake as far as possible from any  
air conditioner, heat pump, swimming pool,  
swimming pool pumping, chlorinator or filtration unit.  
Vent Extension  
Pipe (Side Panel  
Exit)  
SIDE VIEW  
Rotate downward  
5° to 10°  
Tee  
1. Install all couplings, nipples and elbows using proper  
procedures for Joining Pipe and Fittings and maintain  
spacing between vent and combustion air piping as indicated  
in Fig. 22through 30.  
NOTE: Built--in channel will be angled 5° to 10° also.  
A07714  
Fig. 21 -- Proper Sealing Procedure for Combustion Blower  
8” (203.2mm)* MIN.  
20’ (6.1m) MAX  
*18(457.2mm) Minimum for  
cold climates [sustained 0_F  
(-17_C) and below for 24 or  
more consecutive hours]  
Joining Pipe and Fittings  
SEE VENT AND COMBUSTION AIR PIPING, Vent and  
Combustion Air Piping Guidelines in this manual for applicable  
ASTM Standards for vent materials.  
8” (203.2mm) MIN.  
!
WARNING  
12 ” (304.8mm) MIN.  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow this warning could result in personal injury  
or death.  
GRADE LEVEL  
OR  
SNOW LEVEL  
25--00--05F  
Do NOT use solvent cement that has become curdled, lumpy  
or thickened and do NOT thin. Observe precautions printed  
on containers. For applications below 32_F (0_C), use only  
low temperature type solvent cement. Poor joints may lead to  
disconnected or leaking vent pipe joints allowing carbon  
monoxide to enter the living space.  
A07715  
Fig. 22 -- Sidewall Termination 12” (304.8 mm) or More Above  
Snow Level or Grade Level  
Horizontal Termination  
1
1. Cut two holes. 2 / (63.5mm) for 2(50.mm) pipe, 3″  
2
1. Cut pipe end square, remove ragged edges and burrs.  
Chamfer end of pipe, then clean fitting, socket and pipe joint  
of all dirt, grease, or moisture.  
1
1
(76.2mm) for 2 / (63.5mm) pipe, or 3 / (88.9mm) for 3″  
2
2
(76.2mm) pipe. Do NOT make the holes oversized, or it will  
be necessary to add a sheet metal or plywood plate on the  
outside with the correct size hole in it.  
NOTE: Stir the solvent cement frequently while using. Use a  
natural bristle brush or the dauber supplied with the cement. The  
proper brush size is one inch.  
2. Check hole sizes by making sure it is smaller than the  
couplings or elbows that will be installed on the outside. The  
couplings or elbows MUST prevent the pipe from being  
pushed back through the wall.  
2. After checking pipe and socket for proper fit, wipe socket  
and pipe with cleaner-primer. Apply a liberal coat of primer  
to inside surface of socket and outside of pipe. Do NOT  
allow primer to dry before applying cement.  
3. Apply a thin coat of cement evenly in the socket. Quickly  
apply a heavy coat of cement to the pipe end and insert pipe  
into fittings with a slight twisting movement until it bottoms  
out.  
3. Extend vent pipe and combustion air pipe through the wall  
3
/ (19.1mm) to 1(25.4mm) and seal area between pipe  
4
and wall.  
4. Install the couplings, nipple and termination elbows as  
shown and maintain spacing between vent and combustion  
air piping as indicated in Fig. 22 and Fig. 23.  
NOTE: Cement MUST be fluid while inserting pipe. If NOT,  
recoat pipe.  
A metal shield is recommended 18x 18(457.2mm x 457.2mm)  
min. or 18(457.2mm) min. diameter around the vent termination  
at the exterior wall to protect the house exterior materials from flue  
product or condensation (freezing) damage.  
4. Hold the pipe in the fitting for 30 seconds to prevent the  
tapered socket from pushing the pipe out of the fitting.  
5. Wipe all excess cement from the joint with a rag. Allow 15  
minutes before handling. Cure time varies according to fit,  
temperature and humidity.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Using Exterior Risers  
OVERHANG  
12(304.8mm) MIN.  
1. Install elbows and pipe to form riser as shown in Fig. 23  
EXHAUST  
2. Secure vent pipe to wall with galvanized strap or other rust  
resistant material to restrain pipe from moving.  
3. Insulate pipe with Armaflex or equivalent moisture resistant  
closed cell foam insulation or Fiberglass insulation if boxed  
in and sealed against moisture.  
90°  
INLET  
Vertical Termination  
12(304.8mm) MIN. Ground  
1. Fig. 25 shows the proper installation and clearances for  
vertical vent termination. The vertical roof termination  
should be sealed with a plumbing roof boot or equivalent  
flashing. The inlet of the intake pipe and end of the exhaust  
vent must be terminated no less than 12(307.8mm) above  
the roof or snow accumulation level, and 12(307.8mm)  
away from a vertical wall or other protrusion.  
Level OR Snow Level  
25-23-73  
SIDE VIEW  
FRONT VIEW  
2. If the vent system is installed in an existing chimney make  
sure clearances shown in Fig. 25 are maintained. Horizontal  
section before the termination elbow can be extended on the  
inlet air to provide necessary clearance.  
12(304.8mm) MIN.  
Vent Termination Shielding  
Same Joist  
Space  
Under certain wind conditions some building materials may be  
affected by flue products expelled in close proximity to unprotected  
surfaces. Sealing or shielding of the exposed surfaces with a  
corrosion resistant material (such as aluminum sheeting) may be  
required to prevent staining or deterioration. The protective material  
should be attached and sealed (if necessary) to the building before  
attaching the vent terminal.  
A07699  
Fig. 24 -- Recommended Alternate Installation  
for Sustained Cold Weather  
(0_F (--17_C) & below for 24 or more consecutive hours)  
Multi Vent Termination Clearances  
When two (2) or more furnaces are vented near each other, each  
furnace must be individually vented.  
B
Two (2) vent terminations may be installed as shown in Fig. 26, 27,  
28, 29, and 30 but the next vent termination must be at least 36″  
(914.4mm) away from first two terminations. It is important that  
vent terminations be made as shown to avoid recirculation of flue  
gases.  
A
*18(457.2mm) Minimum for  
cold climates [sustained 0_F  
(-17_C) and below for 24 or  
more consecutive hours]  
8” (203.2mm)* MIN.  
20’ (6.1m) MAX  
A
8” (203.2mm)  
MIN.  
2 5 -- 0 0 -- 0 6  
A = 12(304.8mm) Above roof or snow accumulation level  
B = 8(203.2mm) Min., 20(6.1m) Maximum, except in areas  
with extreme cold temperatures [sustained 0°F(--17°C) and  
below for 24 or more consecutive hours], the 18(457.2mm)  
Min.  
12 ” (304.8mm)  
MIN.  
A07717  
Fig. 25 -- Rooftop Termination  
GRADE LEVEL  
OR  
SNOW LEVEL  
25--00--04F  
A07716  
Fig. 23 -- Sidewall Termination with Exterior Risers to Get  
Above Snow Level or Grade Level  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2” (50.8mm) Max  
36” Min  
(914.4mm)  
Exhaust  
“A”  
8Min.  
Exhaust  
“A”  
Inlet  
OR  
36”Min  
(914.4mm)  
12(304.8mm)  
Min. Grade or  
Snow Level  
8(457.2mm) Min.  
20(6.1m) Max.  
Combustion  
Air  
12(304.8mm) Min.  
Grade or Snow Level  
18(457.2mm) Min. for Cold Climates  
[Sustained 0°F(-17°C) and below for  
24 hours or more consecutive hours]  
Dimension “A” is touching or 2(50.8mm) maximum separation.  
A07718  
A07696  
Fig. 26 -- Concentric Vent and Combustion--Air  
Roof Termination  
Fig. 28 -- Sidewall Inlet Vent and Exhaust--Air Termination  
8(203.2mm) Min.  
8(203.2mm) Min.  
20(6.1m) Max.  
1(25.4mm)  
Maximum  
Combustion Air  
Exhaust  
12(457.2mm)  
Min. Grade or  
Snow Level  
Vent  
Inlet  
“A”  
“A”  
18(457.2mm) Min. for Cold Climates  
[Sustained 0°F(-17°C) and below for  
24 hours or more consecutive hours]  
Exhaust  
Vent  
2 5 -- 2 2 -- 0 2 d  
“A”  
Dimension “A” is touching or 2(50.8mm) maximum separation.  
Dimension “A” is touching or 2(50.8mm) maximum separation.  
A07695  
A07697  
Fig. 27 -- Concentric Vent and Combustion Air  
Sidewall Termination  
Fig. 29 -- Sidewall Inlet Vent and Exhaust--Air Termination  
with Exterior Risers  
8(203.2mm) Min.  
20(6.1m) Max.  
Inlet  
12(304.8mm)  
Min. Grade or  
Snow Level  
Exhaust  
18(457.2mm) Min. for Cold Climates  
[Sustained 0°F(-17°C) and below for  
24 hours or more consecutive hours]  
25--22--43  
A07698  
Fig. 30 -- Rooftop Inlet Vent and Exhaust--Air Termination  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Determine the best location for the termination kit. See Fig.  
32 for vertical termination or Fig. 35 and 36 for horizontal  
termination. Roof termination is preferred since it is less  
susceptible to damage, has reduced intake contaminants and  
less visible vent vapor. For side wall termination,  
consideration should be given to: 1) possible damage from  
the vapors to plants/shrubs, other equipment and building  
materials, 2) possible damage to the terminal from foreign  
objects, 3) wind effects that may cause recirculation of flue  
products, debris or light snow and 4) visible vent vapor.  
CONCENTRIC VENT  
TERMINATION  
Vent Termination Clearances  
!
WARNING  
CARBON MONOXIDE POISONING, FIRE AND  
EXPLOSION HAZARD  
Kit Contents:  
Failure to follow this warning could result in personal injury,  
death, or property damage.  
3(76.2) Rain Cap or 2(50.8) Rain Cap  
1
3(76.2) Diameter SDR--26 Pipe, 19 / (495.3) Long or  
2
4(101.6) Diameter SDR--26 Pipe, 24(609.6) Long,  
Inlet and outlet pipes may NOT be vented directly above each  
other (standard vent terminals).  
5
2(50.8) Diameter SDR--26 Pipe, 31 / (803.3) Long or  
8
1
1
2 / (63.5) Diameter SDR--26 Pipe, 37 / (973) Long,  
2
8
2(50.8) or 3″  
(76.2) Dia.  
Rain Cap  
3(76.2) Y Concentric Fitting or 2(50.8) Y Concentric Fitting  
Nominal 3(76.2) or 4″  
(101.6) Dia. SDR--26 Pipe  
1. Determine termination locations based on clearances  
specified in following steps and as shown in Fig. 8, 31  
through 36  
2. The vent termination must be located at least 12(304.8mm)  
above ground or normally expected snow accumulation  
levels.  
3. Do NOT terminate over public walkways. Avoid areas  
where condensate may cause problems such as above  
planters, patios, or adjacent to windows where steam may  
cause fogging.  
2(50.8) or 3(76.2) Dia.  
1
2 (50.8) or 2 / (63.5)  
2
Y Concentric Fitting  
Dia. SDR--26 Pipe  
2 5 -- 2 2 -- 0 3  
A07719  
Fig. 31 -- Kit Components  
Maintain 12(304.8mm)  
min. clearance above high-  
est anticipated snow level.  
Max. of 24(609.6mm)  
above roof.  
Vent  
4. The vent termination shall be located at least 4(1.2m)  
horizontally from any electric meter, gas meter, gas  
regulator, and any relief equipment. These distances apply  
ONLY to U.S. installations.  
5. The vent termination is to be located at least 3(.91m) above  
any forced air inlet located within 10(3m); and at least 10′  
(3m) from a combustion air intake of another appliance,  
except another direct vent furnace intake.  
Combustion  
Air  
Roof Boot/  
Flashing  
(Field Supplied)  
6. In Canada, the Canadian Fuel Gas Code takes precedence  
Support  
(Field Supplied)  
over the preceding termination instructions.  
Concentric Vent Termination  
Kit # KGAVT0701CVT & KGAVT0801CVT  
45° Elbow  
(Field Supplied)  
These kits are for vertical or horizontal termination of the  
combustion air inlet and the exhaust vent pipes on Category IV  
gas--fired condensing furnaces. The KGAVT0701CVT kit can be  
used for 2(50.8mm) diameter pipe systems. The  
KGAVT0801CVT kit can be used for 3(76.2mm)diameter pipe  
system. Refer to Table 5 for the correct pipe size for the furnace.  
Both the combustion air inlet and the exhaust vent pipes must  
attach to the termination kit. The termination kit must terminate  
outside the structure and must be installed per the instructions  
outlined below for vertical or horizontal termination. Vertical  
termination is preferred. Field supplied pipe and fittings are  
required to complete the installation.  
Vent  
Combustion  
Air  
25--22--02  
Note:  
Support must be field installed to secure termination kit to structure.  
A07720  
Fig. 32 -- Concentric Vent Roof Installation  
3. Cut one 5(127mm)diameter hole through the structure for  
the KGAVT0701CVT Kit or one 4(101.6mm)diameter  
hole for the KGAVT0801CVT Kit .  
4. Dimension D may be lengthened to 60(1524mm)max. or  
shortened by cutting the pipes to 12(304.8mm) min.  
Dimension A will change according to D dimension. (See  
Fig. 33.)  
Vertical & Horizontal Termination  
1. Determine the pipe diameters required for the installation  
from Table 5 and Fig. 33  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Drill clearance hole in rain  
cap and pilot hole in vent pipe.  
B PVC  
Vent/Exhaust  
C
D
Stainless steel screw  
(Field supplied)  
1
1 / ″  
2
(38 mm)  
A07722  
B
PVC Intake/Combustion Air  
Fig. 34 -- Rain Cap to Vent Pipe Assembly  
A
Model  
A*  
B
C
D**  
!
WARNING  
7
1
1
KGAVT0801CVT  
KGAVT0701CVT  
38 /  
3
2
4 /  
21 /  
8
8
2
2
8
3
1
5
33 /  
3 /  
16 /  
8
CARBON MONOXIDE POISONING HAZARD  
* = Dimension will change accordingly as dimension D is lengthened  
or shortened.  
**= Dimension D may be lengthened to 60may also be shortened by  
cutting the pipes provided in the kit to 12minimum.  
Failure to follow this warning could result in personal injury  
or death.  
When using the alternate screw assembly method, drill a  
clearance hole in the rain cap and a pilot hole in the vent pipe  
for the screw size being used. Failure to drill adequate holes  
may cause cracking of the PVC components, allowing flue  
gasses to be recirculated.  
A09195  
Fig. 33 -- Concentric Vent Dimensional Drawing  
Concentric Termination Kit  
KGAVT0701CVT & KGAVT0801CVT  
Venting Table Dual Piping ONLY  
Table 5  
6. Install the Y concentric fitting and the pipe assembly  
through the structure’s hole. For vertical termination, install  
the parts through the field supplied roof boot/flashing.  
NOTE: Do not allow insulation or other materials to  
accumulate inside the pipe assembly when installing through  
the structure’s hole.  
40,000, 50,000, 60,000, & 75,000 Btuh Furnaces  
KGAVT0701CVT - 35(10.7m) & (4) 90° elbows  
with 2(50.8mm) PVC pipe  
80,000, 100,000 & 125,000 Btuh Furnaces  
KGAVT0801CVT - 35(10.7m) & (4) 90° elbows  
with 3(76.2mm) PVC pipe  
!
WARNING  
1. Do not include the field supplied 45° elbow in the  
total elbow count.  
2. If more than four elbows are required, reduce the  
length of both the inlet and the exhaust pipes five feet  
for each additional elbow used.  
3. Elbows are DWV long radius type for 2(50.8mm)  
and 3(76.2mm) vents.  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow this warning could result in personal injury  
or death.  
Do not operate the furnace with the rain cap removed as  
recirculating of the flue gasses may occur. Water may also  
collect inside the larger combustion air pipe and flow to the  
burner enclosure.  
If more than four elbows are required, reduce the length of both  
the inlet and exhaust pipes 5(1.5m)for each additional elbow  
used.  
* Feet of pipe is whichever pipe run is the longest, either inlet or  
outlet side.  
7. Secure the assembly to the structure as shown in Fig. 32 or  
Fig. 36 using field supplied metal strapping or equivalent  
material.  
If assembly needs to be extended to meet height or side wall  
thickness requirement, the two pipes supplied in the kit may be  
replaced by using the same diameter solid, single (no coupling  
connections) field supplied SDR--26 PVC (ASTM D2241) pipes.  
Do not extend dimension D more than 60(1524mm). (See Fig.  
33.)  
Do not use field supplied couplings to extend the pipes. Airflow  
restriction will occur and the furnace pressure switch may cause  
intermittent operation.  
NOTE: Ensure the termination height is above the roof surface or  
anticipated snow level as shown in Fig. 32 for vertical termination.  
Ensure the termination location clearance dimensions are as shown  
in Fig. 35 and Fig. 36 for horizontal termination.  
8. Install the rain cap and the small diameter pipe assembly in  
the Y concentric fitting and the large pipe assembly. Ensure  
that the small diameter pipe is bottomed out and securely  
cemented in the Y concentric fitting.  
9. Cement the furnace combustion air and vent pipes to the  
concentric vent termination assembly. See Fig. 32 or Fig. 36  
for proper pipe attachment.  
10. Operate the furnace through one heat cycle to ensure  
combustion air and vent pipes are properly connected to the  
concentric termination connections.  
5. Partially assemble the concentric vent termination kit. Clean  
and cement the parts using the procedures for Joining Pipe  
and Fittings section of the manual.  
a. Cement the Y Concentric fitting to the longest of the  
two straight kit pipes. See Fig. 34.  
b. Cement the rain cap to the shortest of the straight kit  
parts. (See Fig. 34.)  
NOTE: A field supplied stainless steel screw may be used to  
secure the rain cap to the pipe instead of cementing when field  
disassembly is desired for cleaning (See Fig. 34.)  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(See Propane Gas Conversion Kit instruction manual for furnaces  
converted to Propane gas)  
Roof Overhang  
S Use only the Type of gas approved for this furnace. See rating  
plate for approved gas type.  
1
S A / NPT plugged tapping, accessible for a test gauge  
8
12(304.8mm) min.  
connection,must be installed immediately upstream of the gas  
supply connection to furnace.  
1(25.4mm) max.  
Combustion  
S Gas supply pressure should be within minimum and maximum  
values listed on rating plate. Pressures are usually set by gas  
suppliers.  
Air  
Vent  
S Gas input must not exceed the rated input shown on the rating  
plate. Overfiring will result in failure of heat exchanger and cause  
dangerous operation.  
Maintain 12(304.8mm) clearance  
above highest anticipated snow level  
or grade whichever is greater.  
25--22--02  
S Do not allow minimum supply pressure to vary downward.  
Doing so will decrease input to furnace. Refer to Table 6 for Gas  
supply. Refer to Tables 7 through 10 for manifold pressures.  
A07736  
Fig. 35 -- Concentric Vent and Combustion--Air  
Side Termination  
Table 6  
Gas Pressures  
Strap  
(Field Supplied)  
Supply Pressure  
Combustion  
Air  
Gas Type  
Natural  
Recommended  
Max.  
Min.  
7 in wc  
(1744 Pa)  
14 in wc  
(3487 Pa)  
4.5 in wc  
(1121 Pa)  
Vent  
11 in wc  
(2740 Pa)  
14 in wc  
(3487 Pa)  
11 in wc  
(2740 Pa)  
Vent  
Propane  
Flush to  
1(25.4mm)  
Combustion  
Air  
Gas Piping Requirements  
max.  
45° Elbow  
(Field Supplied)  
NOTE: The gas supply line must be installed by a qualified service  
25--22--02  
technician in accordance with all building codes.  
Note:  
NOTE: In the state of Massachusetts.  
Securing strap must be field installed to prevent movement of termina-  
tion kit in side wall.  
a. Gas supply connections MUST be performed by a  
licensed plumber or gas fitter.  
A07723  
Fig. 36 -- Concentric Vent Sidewall Attachment  
b. When flexible connectors are used, the maximum length  
shall not exceed 36(915 mm).  
c. When lever handle type manual equipment shutoff  
valves are used, they shall be T--handle valves.  
GAS SUPPLY AND PIPING  
d. The use of copper tubing for gas piping is NOT  
approved by the state of Massachusetts.  
!
WARNING  
1. Install gas piping in accordance with local codes, or in the  
absence of local codes, the applicable national codes. Refer  
to NFPA 54/ANSI Z223.1 for proper gas pipe size.  
2. It is recommended that a manual equipment shutoff valve be  
installed in the gas supply line outside the furnace. Locate  
valve as close to the furnace as possible where it is readily  
accessible. Refer to Fig. 37.  
FIRE AND EXPLOSION HAZARD  
Failure to follow this warning could result in personal injury,  
death, and/or property damage.  
Models designated for Natural Gas are to be used with Natural  
Gas ONLY, unless properly converted to use with Propane gas.  
3. Use black iron or steel pipe and fittings or other pipe  
approved by local code.  
NOTE: The rating plate is stamped with the model number, gas  
type and gas input rating. In addition, models manufactured for sale  
in Canada have orifice size information stamped on the rating plate.  
4. Use pipe thread compound which is resistant to natural and  
Propane gases.  
5. Use ground joint unions and install a drip leg no less than 3″  
(76.2mm) long to trap dirt and moisture before it can enter  
gas controlvalve inside furnace.  
Gas Supply Requirements  
!
WARNING  
6. Use two pipe wrenches when making connections to prevent  
gas valve from turning.  
7. Install a manual shut--off valve external to furnace casing  
and tighten all joints securely.  
8. If local codes allow the use of flexible gas appliance  
connectors, always use a new listed connector.  
Do not use a connector which has previously serviced  
another gas appliance.  
FIRE HAZARD  
Failure to follow this warning could result in personal injury  
or death.  
Do NOT set input rating above that shown on rating plate.  
Gas supply pressure should be within minimum and maximum  
values listed on rating plate. Pressures are usually set by gas  
suppliers.  
9. Flexible corrugated metal gas connector may NOT be used  
inside the furnace or be secured or supported by the furnace  
or ductwork.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10. Properly size gas pipe to handle combined appliance load or  
run gas pipe directly from gas meter or Propane gas  
regulator.  
!
WARNING  
NOTE: Refer to Fig. 37 or Fig. 38 for the general layout at the  
furnace. The rules listed apply to natural and Propane gas pipe  
installations.  
ELECTRICAL OPERATION HAZARD  
Failure to follow this warning could result in personal injury  
or death.  
NOTE: On the Dual Certified or Direct Vent models, install the  
gas pipe grommet to the furnace side panel with the gas pipe entry.  
If needed, remove the 2(50.8mm) hole plug from the plastic  
accessory bag and relocate to the open hole in the furnace side  
panel.  
Failure to properly install metal gas connector could  
result in personal injury, death, and/or property  
damage.  
A flexible corrugated metal gas connector must be  
properly installed, shall not extend through the side of  
the furnace,and shall not be used inside the furnace.  
11. Install correct pipe size for run length and furnace rating.  
12. Measure pipe length from gas meter or Propane second stage  
regulator to determine gas pipe size.  
Black iron pipe shall be installed at the furnace gas  
control valve and extend a minimum of 2(50.8mm)  
outside furnace casing.  
Vent Pipe Grommet  
(Single Pipe)  
Manual shut-off  
valve  
Drip Leg and Union, Union* should be outside the  
cabinet. Manual shut--off valve MUST be upstream of  
dripleg, union, and furnace.  
3(76.2mm)  
pipe nipple  
Use elbows and 3(76.2mm) pipe nipple  
to connect valve to piping when using  
right side gas pipe entry.  
Propane low pressure switch.  
Alternative  
installation  
* Union may be installed inside the cabinet when necessary because of clearances.  
Representative drawing only, some models may vary in appearance.  
2 5 -- 2 5 -- 4 5  
A09196  
Fig. 37 -- Typical Gas Piping for Upflow  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Use elbows and 3(76 mm) pipe nipple to connect valve to  
piping when using left side gas pipe entry.  
Propane low pressure  
switch.  
Manual shut- off  
valve  
Alternative  
installation  
Drip Leg and Union, Union* should be outside the cabinet.  
Manual shut--off valve MUST be upstream of dripleg, union,  
and furnace.  
Gas Pipe Grommet  
(Single Pipe)  
*Union may be installed inside the cabinet when necessary  
because of clearances.  
A09206  
Fig. 38 -- Typical Gas Piping for Downflow  
3. For operation with Propane gas, gas orifices MUST be  
changed and manifold pressure MUST be maintained as  
Additional Propane Connection Requirements  
1. Have a licensed Propane gas dealer make all connections at  
storage tank and check all connections from tank to furnace.  
per  
Table 8. Orifices can be ordered through your  
distributor. See Fig. 39.  
2. If copper tubing is used, it MUST comply with limitation  
4. In cases where Table 7 is not applicable, eg. alternate input  
rate application, refer to above table for required high  
altitude input rate.  
set in National Fuel Gas Code or CGA codes.  
3. Two--stage regulation of Propane gas is recommended.  
High Altitude Input Rate =  
Propane Conversion  
Nameplate Sea Level Input Rate x (Multiplier)*{  
An accessory kit shall be used to convert to propane gas use, see the  
furnace rating plate for the Propane conversion accessory kit part  
number.  
High Altitude Multiplier  
Natural Gas Propane Gas  
Elevation  
ft (m)  
2001- 3000′  
(609.9 -- 914.4){  
0.95  
0.90  
!
WARNING  
3001- 4000′  
0.93  
0.91  
0.89  
0.87  
0.85  
0.86  
0.82  
0.78  
0.74  
0.70  
(914.7 -- 1219.2)  
FIRE, EXPLOSION HAZARD  
4001- 5000′  
(1219.5 -- 1524)  
Failure to follow this warning could result in personal injury  
or death.  
5001- 6000′  
(1524.3 -- 1828.8)  
A
Propane conversion accessory kit is required when  
operating the furnace with Propane gas.  
6001- 7000′  
(1829.1 -- 2133.6)  
7001- 8000′  
(2133.9 -- 2438.4)  
General Derating Rules  
1. These furnaces may be used at full input rating when  
installed at altitudes up to 2,000(609.6m). When installed  
above 2,000(609.6m), the input must be decreased 2%  
(Natural) or 4% (Propane) for each 1000above sea level in  
the USA. In Canada, the input rating must be derated 5%  
(Natural Gas) and 10% (Propane Gas) for altitudes 2000to  
4500(609.6 to 1371.6m) above sea level.  
High Altitude Air Pressure Switch  
Altitudes over 4,000(1219.2m) may require a different air pressure  
switch than the one installed at the factory. Check parts list for  
pressure switch and consult your distributor for part number and  
availability. In Canada, provincial codes may govern installation of  
switch. Check with governing authorities.  
2. For operation with natural gas at altitudes above 2,000′  
(609.6m), orifice change and/or manifold pressure  
adjustments may be required for the gas supplied. First  
consult your local gas supplier, then refer to or Table 7 for  
required pressure change and/or orifice change for high  
altitudes.  
* In the USA, derating of these furnaces at 2% (Natural Gas) and  
4% (Propane Gas) has been tested and design--certified by CSA.  
{In Canada, the input rating must be derated 5% (Natural Gas)  
and 10% (Propane Gas) for altitudes of 2,000 to 4,500 (609.6 to  
1371.6m) above sea level. Use the 2001 to 3000 (609.9 to 914.4  
m) column in Table 7 and Table 8.  
* Based on mid --- r an ge of el evation .  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NATURAL GAS MANIFOLD PRESSURE (in wc) 20,000 BTU per burner  
Table 7  
MEAN ELEVATION ABOVE SEA LEVEL ft(m)  
0 to 2000  
(0 to 609.6)  
3001 to 4000  
(914.7 to 1219.2)  
4001 to 5000  
(1219.5 to 1524)  
5001 to 6000  
(1524.3 to 1828.8)  
6001 to 7000  
(1829.1 to 2133.6)  
7001 to 8000  
(2133.9 to 2438.4)  
2001 to 3000{  
(609.9 to 914.4){  
HEATING  
VALUE at  
ALTITUDE  
BTU/CU.  
FT.  
Orifice  
Manifold  
Pressure  
Orifice  
No.  
Manifold  
Pressure  
Orifice  
No.  
Manifold  
Pressure  
Orifice  
No.  
Manifold  
Pressure  
Orifice  
No.  
Manifold  
Pressure  
Orifice  
No.  
Manifold  
Pressure  
Orifice  
No.  
Manifold  
Pressure  
No.  
HI  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
LO  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
HI  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
3.5  
3.3  
3.2  
3.6  
3.6  
3.4  
3.5  
3.7  
LO  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
1.7  
1.6  
1.5  
1.8  
1.8  
1.7  
1.7  
1.8  
HI  
-- --  
-- --  
-- --  
-- --  
LO  
-- --  
-- --  
-- --  
-- --  
-- --  
1.8  
1.7  
1.6  
1.8  
1.8  
1.7  
1.9  
1.8  
1.8  
1.7  
HI  
-- --  
LO  
-- --  
HI  
-- --  
LO  
-- --  
HI  
-- --  
LO  
-- --  
HI  
LO  
1.8  
1.7  
1.6  
1.9  
1.7  
1.9  
1.7  
1.9  
1.8  
1.7  
1.9  
1.8  
1.7  
-- --  
700  
725  
750  
775  
800  
825  
850  
875  
900  
925  
950  
975  
1000  
1050  
1100  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
44  
44  
44  
44  
46  
47  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
44  
44  
44  
45  
46  
46  
47  
48  
-- --  
-- --  
-- --  
-- --  
-- --  
44  
44  
44  
45  
46  
46  
47  
47  
48  
48  
-- --  
-- --  
-- --  
-- --  
44  
44  
44  
46  
46  
46  
47  
47  
48  
48  
49  
-- --  
-- --  
-- --  
44  
44  
45  
46  
46  
47  
47  
47  
48  
48  
49  
-- --  
-- --  
44  
44  
44  
45  
46  
46  
47  
47  
48  
48  
48  
49  
-- --  
-- --  
44  
44  
44  
46  
46  
47  
47  
48  
48  
48  
49  
49  
49  
-- --  
-- --  
3.7  
3.4  
3.2  
3.8  
3.6  
3.8  
3.6  
3.8  
3.6  
3.4  
3.8  
3.6  
3.4  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
-- --  
3.7  
3.5  
3.2  
3.7  
3.6  
3.4  
3.7  
3.5  
3.7  
3.5  
3.4  
3.8  
-- --  
1.8  
1.7  
1.6  
1.8  
1.8  
1.7  
1.8  
1.7  
1.8  
1.7  
1.6  
1.8  
-- --  
3.5  
3.3  
3.8  
3.7  
3.5  
3.8  
3.6  
3.4  
3.7  
3.5  
3.7  
-- --  
1.7  
1.6  
1.8  
1.8  
1.7  
1.8  
1.8  
1.7  
1.8  
1.7  
1.8  
-- --  
-- --  
3.6  
3.4  
3.2  
3.8  
3.6  
3.4  
3.7  
3.5  
3.8  
3.4  
3.7  
1.8  
1.7  
1.6  
1.9  
1.8  
1.7  
1.8  
1.7  
1.8  
1.7  
1.8  
3.7  
3.5  
3.3  
3.7  
3.7  
3.5  
3.8  
3.6  
3.7  
3.4  
-- --  
-- --  
-- --  
3.7  
3.5  
3.3  
3.2  
3.6  
3.8  
1.8  
1.7  
1.6  
1.6  
1.8  
1.8  
-- --  
-- --  
-- --  
-- --  
Conversion: 1 in wc = 249 Pa  
Bold- indicates factory orifice size.  
NOTE: Propane data is based on 1.53 specific gravity. For fuels with different specific gravity consult the National Fuel Gas Code ANSI  
Z223.1--2006/NFPA 54--2006 or National Standard of Canada, Natural Gas and Propane Installation Code CSA B149.1--05.  
In the USA, derating of these furnaces at 2% (Natural Gas) and 4% (Propane Gas) has been tested and design--certified by CSA.  
{
In Canada, the input rating must be derated 5% (Natural Gas) and 10% (Propane Gas) for altitudes of 2,000 to 4,500 (609.6 to 1371.6m)  
above sea level. Use the 2001 to 3000 (609.9 to 914.4m) column in Table 7 and Table 8.  
Table 8  
PROPANE GAS MANIFOLD PRESSURE (in wc) 20,000 BTU per burner  
MEAN ELEVATION FEET ABOVE SEA LEVEL ft(m)  
HEATING VALUE  
at ALTITUDE  
BTU/CU. FT.  
0 to 2000  
(0 to 609.6)  
3001 to 3999  
(914.7 to  
1219.2)  
4001 to 5000  
(1219.5 to 1524)  
5001 to 6000  
(1524.3 to  
1828.8)  
6001 to 7000  
(1829.1 to  
2133.6)  
7001 to 8000  
(2133.9 to  
2438.4)  
2001 to 3000{  
(609.9 to  
914.4){  
Hi  
Lo  
Hi  
Lo  
Hi  
Lo  
Hi  
Lo  
Hi  
Lo  
Hi  
Lo  
Hi  
Lo  
2500  
10.0  
4.9  
8.9  
4.4  
8.4  
4.1  
10.0  
4.9  
10.0  
4.9  
10.0  
4.9  
10.0  
4.9  
Orifice Size  
#55  
#55  
#55  
#56  
#56  
#56  
#56  
Conversion: 1 in wc = 249 Pa  
NOTE: Propane data is based on 1.53 specific gravity. For fuels with different specific gravity consult the National Fuel Gas Code ANSI  
Z223.1 -2006/NFPA 54 -2006 or National Standard of Canada, Natural Gas and Propane Installation Code CSA B149.1 -05.  
In the USA, derating of these furnaces at 2% (Natural Gas) and 4% (Propane Gas) has been tested and design--certified by CSA.  
{
In Canada, the input rating must be derated 5% (Natural Gas) and 10% (Propane Gas) for altitudes of 2,000 to 4,500 (609.6 to 1371.6m)  
above sea level. Use the 2001 to 3000 (609.9 to 914.4m) column in Table 7 and Table 8.  
The burner orifice part numbers are as follows:  
Changing Orifices for High Altitude  
Orifice  
41  
Part #  
Orifice  
42  
Part #  
!
WARNING  
333730--701  
333730--703  
333730--705  
333730--710  
333730--712  
333730--707  
333730--702  
333730--704  
333730--709  
333730--711  
333730--706  
333730--708  
43  
44  
ELECTRICAL SHOCK, FIRE OR EXPLOSION  
HAZARD  
45  
46  
Failure to follow this warning could result in personal injury,  
death, and/or property damage.  
47  
48  
49  
54  
Turn OFF electric power (at disconnect) and gas supply (at  
manual valve in gas line) when installing orifices. Installation  
of orifices requires a qualified service technician.  
55  
56  
NOTE: Main burner orifices can be changed for high altitudes.  
1. Disconnect gas line from gas valve.  
2. Remove manifold from furnace.  
3. Remove the orifices from the manifold and replace them  
with properly sized orifices.  
4. Tighten orifices so it is seated and gas tight. (See Fig. 39.)  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Measure from face of ori-  
fice to the back side of the  
manifold.  
ELECTRICAL WIRING  
1.11(28.2mm)  
1.21(30.8mm)  
!
WARNING  
ELECTRICAL OPERATION HAZARD  
Failure to follow this warning could result in personal injury  
or death.  
Turn OFF electrical power at fuse box or service panel  
before making any electrical connections and ensure a  
proper ground connection is made before connecting  
line voltage.  
A07725  
Fig. 39 -- Changing Orifices  
5. Reinstall manifold. Ensure burners do NOT bind on new  
Power Supply Wiring  
orifices.  
The furnace MUST be electrically wired and grounded in  
accordance with local codes, or in the absence of local codes with  
the latest edition of The National Electric Code, ANSI NFPA 70  
and/or The Canadian Electric Code CSA C22.1.  
Final Gas Piping Check  
1. The furnace and the equipment shut off valve must be  
disconnected from the gas supply piping system during any  
pressure testing of that system at test pressures in excess of  
Field wiring connections must be made inside the furnace  
connection box. A suitable strain relief should be used at the point  
the wires exit the furnace casing.  
1
/2PSIG. Close the manual shut--off valve before testing at  
such pressures.  
2. The furnace must be isolated from the gas supply system by  
closing the equipment shut off valve during any pressure  
testing of the gas supply system at test pressure equal to or  
NOTE: Furnace will not have normal operation is line polarity is  
reversed. Check ALL field and control connections prior to  
operation.  
1
less than /2PSI.  
Copper conductors shall be used. Line voltage wires should  
conform to temperature limitation of 35° C rise and be sized for the  
unit maximum amps stated on the rating plate. Add the full load  
amps for potential field--installed accessories such as electronic air  
cleaners and humidifiers that would receive power from the furnace  
control board. The furnace control board is rated for a maximum of  
1.0 amps combined for EAC and HUM. Consult NEC or local  
codes for proper wire and circuit sizing.  
3. When installation is complete, test all pipe connections for  
1
leaks with the gas pressure less than /2PSIG to the gas  
valve.  
4. Apply a commercial soap solution to all joints to test for  
leaks. Correct any leaks indicated by bubbles.  
5. Correct even the smallest leak at once.  
6. Check for leaks at gas valve and orifice connections to the  
burner manifold along with the pilot tube connections to the  
valve and pilot assembly while the furnace is operating.  
Junction Box (J-Box) Relocation  
The J--Box is installed on left side of casing. An alternate J--Box  
location on right side can be used.  
!
WARNING  
1. Remove bag containing two hole plugs and two self tapping  
screws from loose parts bag in blower compartment.  
2. Remove two screws holding J--Box to casing.  
FIRE OR EXPLOSION HAZARD  
Failure to follow this warning could result in personal injury,  
death, and/or property damage.  
3. Install large hole plug from loose furnace accessory bag into  
the left J--Box location.  
Never test for gas leaks with an open flame. Use a  
commercially available soap solution made specifically for the  
detection of leaks to check all connections. A fire or explosion  
could result causing property damage, personal injury and/or  
loss of life.  
4. Clip wire tie holding J--Box wires.  
5. Move J--Box to alternate location and attach using two self  
tapping screws from bag.  
6. Apply two hole plugs from bag at left J--Box location.  
Thermostat  
!
Heating  
AVERTISSEMENT  
The two--stage furnace control board will operate with either a  
single stage or a two--stage heating thermostat and will provide  
two--stage heating operation.  
RISQUE D‘INDENDIE OU D‘EXPLOSION  
Le non--respect des avertissements de sécurité pourrait  
d‘entrainer des blessures graves, la mort ou des dommages  
matériels.  
For single--stage thermostat installations, the R and W wires from  
the thermostat connect to the R and W1 connections on the furnace  
control board. (See Fig. 40and wiring diagram)  
NOTE: The TT (Thermostat Type) SW1 DIP switch #3 should be  
in the OFF position for the furnace to operate properly with a  
single--stage thermostat. Failure to change DIP switch with  
single--stage thermostat will result in Low Heat operation ONLY.  
Ne jamais utiliser une flamme nue por vérifier la présence des  
fuites de gaz. Pour la vérification de tous les joints, utiliser  
plutôt une solution savonneuse commerciale fabriquée  
spécifiquement pur la détection des fuites de gaz. Un incendie  
ou une explosion peut entrainer des dommages matériels, des  
blessures ou la mort.  
During operation, the furnace will operate on Low Heat for up to12  
minutes. If the heat request exists for more than 12 minutes, the  
furnace will automatically shift to the High Heat mode for the  
remaining duration of the heating cycle.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
For two--stage thermostat installations, the R, W1 and W2 wires  
from the thermostat connect to the R, W1 and W2 connections on  
the furnace control board. Set TT SW1 DIP switch #3 to ON  
position. During operation, the furnace will shift from Low Heat to  
High Heat as requested by the thermostat. (See Fig. 40 and wiring  
diagram)  
Dehumidification  
The furnace control board has a dehumidification feature which  
reduces cooling airflow by 20% when the DEHUM terminal ( / ”  
male quick connect) is energized by 24VAC and there is a cooling  
call. DEHUM may be operated by a thermostat dehumidify  
(24VAC for dehumidify) command or a dehumidistat (switch closes  
on call for dehumidification) with one terminal connected to (Y1  
for two--stage cooling or Y/Y2 for single--speed cooling  
applications) and the other terminal connected to DEHUM.  
1
4
Heat anticipator setting will need to be measured if 24VAC  
humidifier is installed. Measure current in series from R to W1 at  
the thermostat. Be sure 24VAC humidifier is operating during this  
check. Allow furnace to operate for 2 minutes before recording the  
AC amperage reading. Set anticipator on thermostat to recorded  
value.  
Furnace Control Fuse  
The 24V circuit contains a 5--amp, automotive--type fuse located on  
furnace control board. (See Fig. 41) Any electrical shorts of 24V  
wiring during installation, service, or maintenance may cause fuse  
to blow. If fuse replacement is required, use only a fuse of identical  
size (5 amp.)  
Thermostat location has an important effect on the operation of the  
furnace. Follow instructions included with thermostat for correct  
mounting and wiring.  
Low voltage connections to furnace must be made on terminal  
board to furnace control board. (See Fig. 41)  
Cooling  
If single--speed cooling is used, the Y and G from the thermostat  
must be connected to the control board Y/Y2 and G to energize  
cooling blower speed.  
If two--stage cooling is used, the Y1, Y2, G of the thermostat must  
be connected to Y1 of tap select interface board for low cooling,  
Y/Y2 of the furnace control board for high cooling and G of the  
furnace control board for continuous fan speed.  
115V. 60 Hz.  
W
BK  
G
Connection  
Box  
Ground  
Optional Equipment  
R
All wiring from furnace to optional equipment MUST conform to  
local codes or, in the absence of local codes with the latest edition  
of The National Electric Code, ANSI NFPA 70 and/or The  
Canadian Electric Code CSA C22.1. Install wiring in accordance  
with manufacturer’s instructions. The wiring MUST have a  
minimum temperature rating of 105° C.  
LowVoltage  
C
TerminalBoard  
W2  
W1  
Y/Y2  
G
W
G
R
SingleStage  
Thermostat  
Humidifier/Electronic Air Cleaner  
The furnace is wired for humidifier and/or electronic air cleaner  
connection.  
R
C
LowVoltage  
TerminalBoard  
W2  
W1  
Y/Y2  
G
HUMIDIFIER -- The HUM (24V) terminal is energized when the  
low pressure switch closes on a call for heat. The HUM (115V) is  
energized when the inducer is energized.  
ELECTRONIC AIR CLEANER -- EAC terminal is energized  
when there is a blower speed call, except it is NOT energized when  
blower operates in the hard--wired continuous fan mode.  
W2  
W1  
G
TwoStage  
Thermostat  
R
NOTE:115VAC/60Hz/single----phase  
Operatingvoltagerange*:127VACmax,104VACmin.  
!
CAUTION  
* Permissible limits of voltage at which unit will operate satisfactorily  
A07779  
REDUCED FURNACE LIFE HAZARD  
Fig. 40 -- Electrical Connections  
Failure to follow this caution may result in reduced furnace  
life.  
Do NOT exceed 115V/1.0 amp. maximum current load for  
both the EAC terminal and the HUM terminal combined.  
Tap Select Interface Board  
The Tap Select Interface Board is used with the Variable Speed  
motor. There are DIP switches (SW2) for continuous blower adjust,  
heating blower adjust, cooling blower adjust and cooling on/off  
delay profiles. There is a jumper (J1) for slight blower adjustment,  
increase (+)/no change (NOM)/decrease (--). There is a jumper (J2)  
for airflow selection of Heat Pump EFFICIENCY or COMFORT.  
(EFFICIENCY provides no airflow reduction in airflow whether  
O is energized or not. COMFORT provides a 10% reduction in  
airflow when O is not energized with a cooling call).  
Furnace Control Board  
The furnace control board has a fixed blower ON delay of 30  
seconds for High Heat calls and 45 seconds for Low Heat calls. The  
blower OFF timing is factory preset at 140 seconds. If desired, the  
fan OFF delay can be reset to obtain the longest delay times while  
still maintaining comfort levels. See “Furnace Wiring Diagram”.  
The O terminal is available for use for Heat Pump applications, if  
desired.  
The Y1 terminal (if a two--stage Air Conditioner or two--stage Heat  
Pump is used) will provide low cooling blower speed when  
energized. (Only Y/Y2 on the furnace control board is used if a  
single--stage Air Conditioner or Heat Pump is installed)  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
WARNING  
Diagnostic Light  
CARBON MONOXIDE POISONING HAZARD  
Dip Switch  
Failure to follow this warning could result in personal injury  
or death.  
See “Wiring  
Diagram”  
for switch settings  
Cool air passing over heat exchanger can cause condensate to  
form resulting in heat exchanger failure.  
24 VAC  
HUM  
115  
VAC  
HUM  
Connections  
NOTE: Return air can enter through either side, both sides, the  
bottom or a side and the bottom. Return air can not enter through  
rear of the furnace. When the furnace is located in an area near or  
adjacent to the living area, the system should be carefully designed  
with returns to minimize noise transmission through the return  
grille. Any blower moving a high volume of air will produce  
audible noise which could be objectionable to when the unit is  
located very close to living areas. It is advisable to route the return  
air ducts under the floor or through the attic.  
EAC  
FUSE  
DEHUM  
A07780  
Fig. 41 -- Control Connections  
1. For side connections using a 16x 25(406.4 x 635mm)  
filter, cut out the embossed area shown in Fig. 42. This will  
1
1
DUCTWORK AND FILTER  
provide a 14 / x 22 / (368.3 x 571.5mm) approximate  
2
2
opening.  
!
A = 14 / (368.3mm) Height of Cutout for 16x 25(406.4 x 635mm) Filter  
2
WARNING  
1
B = 22 / (571.5mm) Width of Cutout for 16x 25(406.4 x 635mm) Filter  
2
CARBON MONOXIDE POISONING HAZARD  
Failure to follow this warning could result in personal injury  
or death.  
B
Do NOT draw return air from inside a closet or utility room  
where furnace is located. Return air duct MUST be sealed to  
furnace casing.  
Embossed Area  
on Side of Furnace  
A
Furnace  
Installation  
Bottom  
NOTE: Design and install the air distribution system to comply  
with Air Conditioning Contractors of America manuals and/or  
NFPA pamphlets 90A and 90B or other approved methods that  
conform to local codes and good trade practices.  
A07728  
Fig. 42 -- Side Return Air Cutout  
1. When furnace supply ducts carry air outside furnace area,  
seal return air duct to furnace casing and terminate duct  
outside furnace space.  
NOTE: Furnaces with 5 TONS cooling capacity may require  
two(2) side returns or one side return with bottom return.  
2. Bottom returns can be made by removing the knockout  
panel in the furnace base. Do NOT remove knock-out  
except for a bottom return.  
2. Install air conditioning cooling coil (evaporator) on outlet  
side of furnace.  
3. For furnaces installed without  
a
cooling coil, it is  
3. Installation of locking-type dampers are recommended in all  
branches, or in individual ducts to balance system’s air flow.  
recommended that the outlet duct be provided with a  
removable access panel. This panel should be accessible  
when the furnace is installed so the exterior of the heat  
exchanger can be viewed for inspections. The access panel  
MUST be sealed to prevent leaks.  
4. Non-combustible,  
flexible  
duct  
connectors  
are  
recommended for return and supply connections to furnace.  
5. If air return grille is located close to the fan inlet, install at  
least one, 90° air turn between fan and inlet grille to reduce  
noise.  
4. If separate evaporator and blower units are used, install good  
sealing dampers for air flow control. Chilled air going  
through the furnace could cause condensation and shorten  
the furnace life.  
NOTE: To further reduce noise, install acoustical air turning vanes  
and/or line the inside of duct with acoustical material.  
NOTE: Dampers (field supplied) can be either automatic or  
manual. Manually operated dampers MUST be equipped with a  
means to prevent furnace or air conditioning operation unless  
damper is in the full heat or cool position.  
Sizing  
Existing or new ductwork MUST be sized to handle the correct  
amount of airflow for either heating only or heating and air  
conditioning.  
Insulation  
1. Insulate ductwork installed in attics or other areas exposed to  
outside temperatures with a minimum of 2(50.8mm)  
insulation and vapor barrier.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Insulate ductwork in indoor unconditioned areas with a  
minimum of 1(25.4mm) insulation with indoor type vapor  
barrier.  
1
1 / ″  
2
(38.1)  
3″  
(76.2)  
Filters  
A filter must be used:  
Filters are supplied with these furnaces, and additional filters may  
be purchased from your distributor.  
1
(31.8)  
1 / ″  
4
Use either filter type:  
S
S
S
Washable, high velocity filters are based on a maximum  
air flow rating of 600 FPM.  
26 Ga. Galvanized Steel  
11  
/
FAST part number 1008482  
16  
(27)  
Disposable, low velocity filters are based on a maximum  
air flow of 300 FPM when used with filter grille.  
A07730  
Fig. 45 -- Filter Clip Construction  
See Service & Maintenance Manual, Circulation Air  
Blower Data for additional data.  
Refer to Fig. 46 and for guidelines to install filters. Furnaces which  
require larger filter media and have limited clearances on one side  
of furnace, require a standoff filter rack, see Fig. 46, available from  
your distributor.  
NOTE: If filters are only suitable for heating application,  
advise homeowner that filter size may need to be increased if  
air conditioning is added.  
NOTE: Disposable, low velocity filters may be replaced with  
washable, high velocity filter providing they meet the minimum  
size areas. Washable, high velocity filters can be replaced ONLY  
with same type and size.  
Using Optional  
Standoff Filter  
Rack  
A07729  
Fig. 43 -- Side Mounted Filter Rack  
Filter Installation using Filter Rack  
When installing or removing a bottom mounted filter, slide the two  
side filter clips to the back of the furnace BEFORE installing or  
removing. This will allow the filter to clear the front raised edge of  
the furnace. Insert filter into side clips first and push filter back until  
it is fully engaged into back clip. When filter is in place, slide clips  
back into place midway on filter as shown in Fig. 44 or Fig. 45  
A07731  
Fig. 46 -- Standoff Filter Rack  
Center Clip  
s i d e -- t o -- s i d e  
Addition Of Air Conditioning  
When a refrigeration coil is used in conjunction with this unit, it  
must be installed parallel with or on the discharge side of the unit to  
avoid condensation on the heat exchanger. All furnaces are  
designed with a break--away duct flange on the supply air side of  
the furnace. This allows for installation in the horizontal right or  
downflow applications. The coil installation instructions must be  
consulted for proper coil location and installation procedures. With  
a parallel flow arrangement, dampers must be installed to prevent  
chilled air from entering the furnace. If manually operated dampers  
are used, they must be equipped with a means to prevent operation  
of either unit unless the damper is in full heat or full cool position.  
A 3clearance is required on the right side of the furnace in order to  
run the condensate drain line. Copper or plastic tubing may be used  
for the condensate drain line.  
9(152.4mm)  
25--24--18--1  
Slide filter clips towards back before removing  
A07691  
Downflow Furnace Installation  
Fig. 44 -- Bottom Mounted Filter Rack  
Non-Combustible Floor Installation  
Fabricate a plenum to the dimensions given in Fig. 47, for the  
3
furnace outlet. Plenum should be flanged, approximately / ″  
4
(19.1mm) for support.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Note: The three(3) screws in the top panel of the furnace next to the  
duct flange MUST be removed to provide serviceability of the  
primary heat exchangers in the downflow installation  
Note: When using the subbase for combustible floors, the discharge  
air duct flanges on the furnace MUST be broken down to provide  
proper fit up to the subbase. Use duct pliers to bend the duct flanges  
flat onto the furnace casing. DO NOT bend the duct flanges inward  
(toward the heat exchangers) as air flow restrictions may occur.  
The Subbase for Combustible Floors MUST be used when a  
downflow furnace is set on a combustible floor, even when the  
furnace is installed on a coil box.  
1. Position plenum through the floor and set the furnace over  
the opening in the floor. If necessary, grout around the base  
to seal air leaks between the base and the floor.  
Combustible Floor Installation  
1. Cut the opening in the floor according to Table 9. The hole  
in the floor must be cut to the dimensions listed in Table 9  
since the base is equipped with locating tabs that center the  
base over the opening.  
!
WARNING  
FIRE HAZARD  
1
1
The opening in the base is 1 / (31.8mm) shorter and 1 / ″  
4
8
Failure to install unit on noncombustible subbase could  
result in personal injury, death, and/or property  
damage.  
(28.6mm) narrower than the recommended size of the opening in  
the floor. This is done to maintain clearance between the floor and  
the plenum.  
Place furnace on noncombustible subbase on  
downflow applications, unless installing on non-  
combustible flooring. The noncombustible subbase  
also must be used on downflow applications in  
addition to a coil box installation.  
2. Fabricate the plenum to the dimensions given in Table 9.  
Note that the dimensions given are outside dimensions.  
3. Set the base over the opening in the floor, centering it over  
the opening. Fasten the base to the floor with screws or nails.  
See Fig. 47, 48, and 49.  
4. Drop the plenum through the opening in the base. The  
flange of the plenum should rest on top of the subbase.  
Subbase for Combustible Floor  
NOTE: The three(3) screws in the top panel of the furnace next to  
the duct flange MUST be removed to provide serviceability of the  
primary heat exchangers in the downflow installation  
Table 9  
Subbases for Combustible Floors Dimensions -- in(mm)  
Sub -base for Combustible  
Floor Dimensions  
Opening In  
Typical Plenum  
Dimensions  
Sub -base for  
Combustible Floors  
Part Number  
Opening In Floor  
Base For Plenum  
*
H
J*  
K**  
L
M
N
P
R
S
T
Furnace Only  
5
3
3
1
1
1
1
19 /  
28 /  
18 /  
16 /  
18 /  
17 /  
17 /  
16  
4
16  
4
4
8
8
KGASB0301P01  
16(406.4)  
16(406.4)  
16(406.4)  
15 (381)  
15 (381)  
15 (381)  
15 (381)  
15 (381)  
15 (381)  
(490.5)  
15  
(730.3)  
(462)  
(412.8)  
(463.6)  
(435.6)  
(435.6)  
3
13  
1
7
3
3
22  
/
28 /  
21 /  
16 /  
21 /  
19 /  
19 /  
4
16  
4
16  
4
8
4
KGASB0401P02  
(582.6)  
11  
(730.3)  
3
(554)  
9
(412.8)  
1
(555.6)  
5
(501.7)  
1
(501.7)  
1
24 /  
28 /  
23 /  
16 /  
23 /  
22 /  
22 /  
2
16  
4
16  
4
8
2
KGASB0801P06  
Subbase for Coil Box  
KGASB0501P03  
(627.1)  
(730.3)  
(598.5)  
(412.8)  
(600.1)  
(571.5)  
(571.5)  
3
9
3
1
1
1
1
1
19 /  
20 /  
18 /  
16 /  
16 /  
18 /  
17 /  
17 /  
8
16  
16  
16  
4
4
8
8
15 (381)  
15 (381)  
15 (381)  
15 (381)  
15 (381)  
15 (381)  
(181.1)  
(522.3)  
9
(462)  
13  
(408)  
1
(412.8)  
1
(463.6)  
7
(435.6)  
3
(435.6)  
3
20 /  
21 /  
16 /  
16 /  
21 /  
19 /  
19 /  
4
16  
16  
16  
4
8
4
KGASB0601P04  
KGASB0701P05  
23 (284.2)  
3
(522.3)  
9
(554)  
9
(408)  
1
(412.8)  
1
(555.6)  
5
(501.7)  
1
(501.7)  
1
24 /  
20 /  
23 /  
16 /  
(408)  
16 /  
23 /  
22 /  
22 /  
2
4
16  
16  
16  
4
8
2
(628.7)  
(522.3)  
(598.5)  
(412.8)  
(600.1)  
(571.5)  
(571.5)  
*
Outside Dimension  
Base Spacer Side To Side  
**  
Conversion: 1 in = 25.4 mm  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S
A = 4 1/4” (108mm) Minimum  
clearance from back of hole  
to wall or other obstruction.  
T
Plenum  
H
J
2(50.8mm)  
1(25.4mm)  
K
R
P
2″  
L
(50.8mm)  
M
N
Hole in  
Floor  
A07784  
25--20--46  
A
Fig. 50 -- Condensate Line Raised by Base  
A07781  
CHECKS AND ADJUSTMENTS  
Fig. 47 -- Exploded View of Subbase for Furnace Only  
NOTE: Verify the input rate of the furnace.  
!
WARNING  
FIRE OR EXPLOSION HAZARD  
Failure to follow this warning could result in personal injury,  
death and /or property damage.  
1
Turn OFF gas at shut off before connecting manometer.  
2 /2(63.5mm)  
1
1 /2(38.1mm)  
Startup  
NOTE: Refer to the start--up procedures in the “Users Information  
Manual” or to the “Operating Instructions Label” on the furnace.  
!
WARNING  
ELECTRICAL OPERATION HAZARD  
A09182  
Failure to follow this warning could result in personal injury,  
death, and/or property damage.  
Fig. 48 -- Exploded View of Base for Downflow Cased Coil  
If any sparks, odors or unusual noises occur, immediately shut  
OFF power to the furnace. Check for wiring errors or  
obstruction to blower.  
5. Position furnace or coil cabinet and furnace on subbase so it  
aligns between the locating tabs.  
Furnace  
Installation of  
Combustible  
Floor Base  
Gas Supply Pressure  
Gas supply pressure should be within minimum and maximum  
values listed on rating plate. Pressures are usually set by gas  
suppliers.  
Manifold Gas Pressure Adjustments  
Wood Floor  
Plenum  
(High and Low Heat)  
NOTE: Make adjustment to manifold pressure with burners  
operating.  
A07783  
Fig. 49 -- Setting the Subbase  
!
WARNING  
This subbase for combustible floors has been designed so that the  
height of the subbase raises the downflow coil off the floor to allow  
easy installation of the condensate drain. See Fig. 50  
FIRE OR EXPLOSION HAZARD  
Failure to follow this warning could result in personal injury,  
death and /or property damage.  
Turn OFF gas at shut off before connecting manometer.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. With gas OFF, connect manometer to manifold pressure tap  
on the outlet of gas control valve. See Fig. 51Use a  
manometer with a 0 to 12 inches of water column range.  
Example (BTUH)  
Natural Gas  
BTU Content  
per cu. foot  
No. of  
Seconds  
Per Hour  
Time Per  
Cubic Foot in  
Seconds  
BTU Per  
Hour  
2. Turn gas ON. Operate the furnace on High Heat by using a  
jumper wire on the R to W1 & W2 thermostat connections  
on the furnace control board.  
1,000  
3,600  
48  
75,000  
1,000 x 3,600 ÷ 48 = 75,000 BTUH  
3. Remove manifold pressure adjustment screw cover on  
3
To Determine the appliance kW input rate from a .05m test dial  
that has been clocked at 80 seconds for one complete revolution.  
furnace gas control valve.  
Turn adjusting screw  
counterclockwise to decrease the manifold pressure and  
clockwise to increase pressure. See Fig. 51  
Example (kW)  
NOTE: Adjustment screw cover MUST be replaced on gas control  
valve before reading manifold pressure and operating furnace.  
Number of  
Number of  
seconds per  
hour  
Size of test  
dial  
(.05m )  
seconds per  
complete  
rotation  
3
kW m /h  
3
Regulator  
Adjustment  
Under Cap  
3,600  
80  
.05  
2.25  
3
3,600 ÷ 80 x .05 = 7.2 m /h  
HONEYWELL  
HI  
3
3
2.25m /h x 10.35 kWh/m = 23.28 kW  
23.28 x 3.412 = 79,431 BTU  
LO  
4. Remove jumper wire from R to W1 and W2.  
5. Relight all appliances and ensure all pilots are operating.  
ON  
Main Burner Flame Check  
Allow the furnace to run approximately 10 minutes then inspect the  
main burner and pilot flames. See Fig. 52.  
INLET  
OFF  
Pressure  
OUTLET  
Pressure  
1
Tap --  
/
25--24--98a8  
1
Tap --  
/
Check for the following (Fig. 52:  
8
Stable and blue flames. Dust may cause orange tips  
or wisps of yellow, but flames MUST NOT have solid,  
yellow tips.  
A07792  
Fig. 51 -- Typical Gas Control Valve (Honeywell)  
Flames extending directly from burner into heat ex-  
4. Set manifold pressure to value shown in Table 7,or Table 8.  
changer.  
5. Operate the furnace on Low Heat by using a jumper wire on  
the R to W1 thermostat connections on the furnace control  
board.  
Flames do NOT touch sides of heat exchanger.  
If any problems with main burner flames are noted, it may be  
necessary to adjust gas pressures, or check for drafts.  
NOTE: The SW1 DIP switch #3 should be in the ON position to  
set the Low Heat manifold pressure. (See wiring diagram.)  
Burner Face  
6. Repeat steps 3 and 4 for Low Heat operation.  
7. When the manifold pressures are properly set, replace the  
adjustment screw covers on the gas control valve.  
8. Remove the jumper wires from the thermostat connections  
on the furnace control board. Remove manometer  
connection from manifold pressure tap, and replace plug in  
gas valve.  
9. Return SW1 DIP switch #3 to previous setting.  
10. Check for leaks at plug.  
A07734  
Fig. 52 -- Main Burner  
Natural Gas Input Rating Check  
NOTE: The gas meter can be used to measure input to furnace.  
Rating is based on a natural gas BTU content of 1,000 BTU’s per  
cubic foot. Check with gas supplier for actual BTU content.  
NOTE: For Igniter location see Fig. 53.  
1/  
2
(52.4)  
16  
5
1
/
16  
(8)  
/ (6.4)  
4
1. Turn OFF gas supply to all appliances and start furnace. Use  
jumper wire on R to W1 and W2 for High Heat.  
2. Time how many seconds it takes the smallest dial on the gas  
meter to make one complete revolution. Refer to Example.  
3. Repeat steps 1 and 2 with jumper wire on R to W1 for Low  
Heat.  
NOTE: If meter uses a 2 cubic foot dial, divide results (seconds)  
A07735  
by two.  
Fig. 53 -- Igniter Location  
NOTE: SW1 DIP switch #3 must be in ON position. (See Furnace  
Wiring Diagram). Return SW1 DIP switch #3 to previous setting  
after check.  
Temperature Rise Check  
The blower speed MUST be set to give the correct air temperature  
rise through the furnace as marked on the rating plate for both High  
Heat and Low Heat operation. Temperature rise is the difference  
between supply and return air temperatures.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To check temperature rise,use the following procedure:  
Switches #7 and #8 adjust the cooling speed on/off delay  
profiles. See the “Technical Support Manual” for the  
switch settings for the desired airflow rates for the  
installation.  
The jumper J1 is used to slightly increase (+) or decrease  
(--) or not change (NOM) the blower speed selected from  
SW2. J1 effects BOTH cooling and heating airflow.  
Continuous blower selection DIP 10 and 11 will cause  
the blower to run in high cooling speed for all low  
cooling (Y1) calls. Continuous blower DIP settings of 00  
and 01 will allow low cooling (Y1) calls to operate  
normally.  
1. Place thermometers in supply and return air registers as close  
to furnace as possible, avoiding direct radiant heat from heat  
exchangers.  
2. Operate furnace on High Heat for 10 minutes with all the  
registers and duct dampers open by using a jumper wire on  
R to W1 and W2 thermostat connections on the furnace  
control board.  
S
Note: The SW1 DIP switch #3 should be in the on position.  
(See furnace wiring diagram)  
3. Take readings and compare with range specified on rating  
plate.  
4. If the temperature rise is not in the correct range, the blower  
speed must be changed. A higher blower speed will lower  
the temperature rise. A lower blower speed will increase the  
temperature rise.  
Continuous-Fan using “G”  
Energizing the ”G” terminal on the furnace control board provides  
continuous fan operation. This is done by connecting the G  
terminal of the thermostat to the G terminal on the furnace control  
board. When the FAN switch is turned from auto to ON the fan  
will operate continuously at airflow selected by DIP SW2 switch #1  
and DIP SW2 switch #2. EAC will be energized in this mode.  
5. Repeat steps 2 thru 4 with the furnace operating on Low  
Heat for 10 minutes by using a jumper wire on the R to W1  
thermostat connections on the furnace control board.  
6. Remove the jumper wire after the adjustments are complete.  
Return SW1 DIP switch #3 to previous setting.  
NOTE: In heating, the fan will not turn off during furnace ignition  
and warm up.  
Blower Adjustments  
Hard Wired Continuous Fan Operation  
Not available for variable speed models.  
Changing Blower Speed  
FURNACE MAINTENANCE  
!
WARNING  
!
WARNING  
ELECTRICAL SHOCK HAZARD  
Failure to follow this warning could result in personal injury  
or death.  
FIRE, EXPLOSION, OR CARBON MONOXIDE  
HAZARDS  
Turn OFF power to furnace before changing blower speed.  
Failure to follow this warning could result in personal injury,  
death and/or property damage.  
It is recommended that the furnace be inspected and serviced  
on an annual basis (before the heating season) by a qualified  
service technician.  
NOTE: The blower speeds that the manufacturer sets from the  
factory for this product are based on a nominal 400 CFM (189 L/s)  
per ton cooling and the mid range on the temperature rise for  
heating.  
Since the manufacturer cannot predict the static pressure that  
will be applied to the furnace, it is the responsibility of the  
installing dealer/contractor to select the proper speeds for the  
application when the furnace is installed.  
!
WARNING  
ELECTRICAL SHOCK, FIRE OR EXPLOSION  
HAZARD  
If it is necessary to change speeds, refer to steps below.  
Failure to follow this warning could result in personal injury,  
death, and/or property damage.  
1. The 115 VAC power supply to the furnace must be turned  
OFF before making adjustments to the motor.  
Before servicing, disconnect all electrical power to furnace.  
NOTE: Allow at least 1 minute before restoring power to  
the furnace after making Blower Control changes.  
When servicing controls, label all wires prior to disconnecting.  
Reconnect wires correctly.  
2. The heating, cooling and continuous blower speeds can be  
adjusted by changing the SW2 DIP switch settings that are  
located on the Tap Select Interface Board (See Fig. 54).  
Verify proper operation after servicing.  
S
Switches #1 and #2 adjust the continuous blower speeds.  
Switches #3 and #4 adjust the heating speed.  
Switches #5 and #6 adjust the cooling speed.  
See “User’s Information Manual” and the “Service  
Manual”.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ON  
=
=
1
0
1
8
OFF  
A09197  
Fig. 54 -- Variable Speed Tap Select Interface Board  
Diagnostic Light  
DIP Switch  
See “Wiring  
Diagram”  
for switch settings  
24 VAC  
HUM  
115  
VAC  
HUM  
EAC  
FUSE  
DEHUM  
A09198  
Fig. 55 -- Control Board  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SEQUENCE OF OPERATION & DIAGNOSTICS  
The following is the normal operating sequence at factory default settings (SW1 OFF/ON/OFF, SW2 all OFF)  
NOTE: SW1 DIP switches (G, Y/Y2, W1, W2 thermostat terminals) and DEHUM (1/4” male quick connect terminal) are located on the  
FCB.  
SW2 DIP switches and Y1 and O thermostat terminals are located on the TSIB.  
Low Cooling (Y1) Request:  
24VAC signals applied to Y1 & G terminals of TSIB (Tap Select Interface Board) and FCB (Furnace Control Board), respectively.  
S Low Cooling motor speed is energized after 5 second Cool Fan On Delay time.  
Y1 & G signals removed from TSIB and FCB  
S Low Cooling motor speed is de--energized after 90 second Cool Fan Off Delay time. Cooling (Y1) and dehumidification (DEHUM)  
requests:  
S 24 VAC signals applied to Y1, DEHUM & G terminals of TSIB and FCB.  
S Same operation as the cooling (Y1) request, except the cooling airflow is reduced 20% to compensate for high humidity conditions during  
cooling operation. The low cooling airflow returns to the normal setting after the DEHUM signal is removed.  
High Cooling (Y1 & Y/Y2) or (Y/Y2) Request:  
24VAC signals applied to Y1 & Y/Y2 & G or Y/Y2 & G terminals of FCB (Furnace Control Board).  
S High Cooling motor speed is energized after 5 second Cool Fan On Delay time.  
Y1 & Y/Y2 & G or Y/Y2 & G signals removed from TSIB and FCB  
S High Cooling motor speed is de--energized after 90 second Cool Fan Off Delay time.  
High Cooling (Y1 & Y/Y2 or Y/Y2) and dehumidification (DEHUM) requests:  
S 24 VAC signals applied to Y1 & Y/Y2 or Y/Y2, DEHUM, & G terminals of TSIB and FCB.  
S Same operation as the high cooling (Y1 & Y/Y2 or Y/Y2) request, except the cooling airflow is reduced 20% to compensate for high  
humidity conditions during cooling operation. The high cooling airflow returns to the normal setting after the DEHUM signal is removed.  
Low or high cooling and O terminal (Heat Pump mode):  
S If the J2 jumper is in the AC/HP EFFICIENCY position, there will be no change in blower airflow regardless of the O terminal being  
energized or de--energized.  
S If the J2 jumper is in the HP COMFORT position, then there will be a 10% reduction in airflow when the O terminal is de--energized (HP  
heating) and no airflow reduction when O is energized (HP cooling).  
NOTE 1) The motor has been set up to recognize the O terminal as energized during cooling calls (reversing valve energized for cooling).  
Continuous Circulating Fan (G) Request:  
24VAC signal applied to G terminal of FCB.  
S Continuous fan speed is energized without delay.  
G signal removed from FCB.  
S Continuous fan speed is de--energized after 5 second delay.  
NOTE 2) Heat or Cooling requests received during a Fan request, cause the fan speed to change to the appropriate heat or cool speed after the  
Fan On Delay time expires. The fan returns to continuous circulating speed after the selected Fan Off Delay time expires following loss of the  
Heating or Cooling request.  
NOTE 3) Hard--wire option not available for variable speed models.  
NOTE 4) Continuous blower selection DIP 10 and 11 will cause the blower to run in high cooling speed for all low cooling (Y1) calls.  
Continuous blower DIP settings of 00 and 01 will allow low cooling (Y1) calls to operate normally.  
Heating (W1) Request (single stage thermostat operation, SW1 DIP switch #3 on the FCB  
must be in OFF position) (see furnace wiring diagram):  
24VAC signal applied to W1 terminal of FCB.  
S Inducer motor turns on at high speed.  
S Following a 15 second prepurge delay after the low pressure switch closes, the igniter begins a 17 second warm up.  
S The gas valve is energized, the main burners light at Low Heat rate.  
S The igniter is de--energized, and the inducer drops to low speed after the main burners ignite.  
S The FCB will delay Low Heat blower operation for the 45--second Low Heat Fan On Delay time timed from the opening of the gas valve.  
S If the W1 request is still present after 12 minutes, timed from the opening of the gas valve, the inducer switches to high speed, closing the  
high pressure switch, then the High Heat solenoid energizes, and the fan switches to High Heat speed.  
W1 signal removed from FCB.  
S The gas valve de--energizes and the main burners go out.  
S The inducer runs at its present speed for a 15 second postpurge period.  
S The fan runs at its present speed.  
S The blower de--energizes after the selected Heat Fan Off Delay time expires timed from the gas valve de--energizing.  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE 5) If a new Heating request arrives while the control is waiting for the Heat Fan Off Delay time to expire, the FCB will wait for the  
selected Heat Fan Off Delay, and then start a new heating cycle.  
Heating (W1 & W2) Request (two-stage thermostat operation, SW1 DIP switch #3 must be in  
ON position) (see furnace wiring diagram):  
24VAC signals applied to W1 terminal of FCB.  
S Same response as single stage thermostat operation described above except the burners, inducer, and blower will not go to high heat rate,  
and High Heat Fan speed unless a W2 signal is applied.  
24VAC signal applied to W1 and W2 terminals of FCB.  
S Same light--off routine as described for the signal stage thermostat operation except burners light at High Heat rate, the inducer remains on  
high speed after ignition, and the FCB will delay High Heat blower operation for the 30--second High Heat Fan On Delay.  
NOTE 6) The FCB responds without delay to the presence or loss of W2 (with W1 constant). W1 & W2 result in high inducer, High Heat  
rate, and High Heat Fan speed. W1 only results in low speed inducer, Low Heat rate, and Low Heat Fan speed.  
Heating Request with Gas Shut Off:  
24 VAC signals applied to W1 terminal of FCB.  
The FCB will attempt 4 cycles for ignition then go to soft lockout for 3 hours, and then try for ignition again as long as the heat call remains.  
Power reset will clear lockout.  
S Inducer motor turns on at high speed.  
S Following a 15 second prepurge delay after the low pressure switch closes, the igniter begins warm up.  
S The igniter glows red--hot for 22 seconds, then turns off. The FCB flashes error code 6.  
S The igniter stays off for 17 seconds, then begins to warm up again.  
S The igniter glows red hot for 22 seconds then turns off. The FCB continues flashing error code 6.  
S The igniter stays off for 17 seconds, then begins to warm up again.  
S The igniter glows red hot for 22 seconds then turns off. The FCB continues flashing error code 6.  
S The igniter stays off for 17 seconds, then begins to warm up again.  
S The igniter glows red hot for 22 seconds then turns off. The FCB proceeds to soft lockout. Stops flashing error code 6, and begins flashing  
error code 6 + 1.  
S The inducer motor de--energizes 15 seconds after error code 6 + 1 starts flashing.  
Furnace Control Board Diagnostic Codes (See Fig. 55):  
OFF  
=
=
=
24VAC or 115VAC is off, fuse is open  
Heartbeat  
ON SOLID  
Normal operation or no previous Diagnostic Code  
Soft Lockout - Furnace Control Error (1 hr delay) If code repeats immediately following  
power reset then replace control  
1 Flash  
=
=
=
=
=
=
=
=
Not used  
2 Flashes  
3 Flashes  
4 Flashes  
5 Flashes  
6 Flashes  
6 + 1 Flashes  
7 Flashes  
Pressure switch(es) closed when should be open  
Low pressure switch open when should be closed  
Limit or flame roll-out switch open (less than 2 minutes)  
Flame sensed out of sequence  
Failure to ignite or flame sense lost while running  
Soft Lockout - Max of four trials for ignition reached (3 hr delay)  
Limit or flame roll-out switch open longer than 2 minutes (1 hr delay) (roll-out switch  
requires manual reset)  
8 Flashes  
=
Permanent Lockout - Gas valve relay contact stuck closed or miswired gas valve (power  
reset only)  
9 Flashes  
=
=
High pressure switch open when should be closed  
10 Flashes  
Improper transformer phasing on twinned applications or improper line voltage polarity.  
* If status code recall is needed, briefly (2--3 seconds) remove then reconnect one limit switch wire (main or rollout) to display last stored  
status code. Do not remove power or blower door before initiating status code recall or code will be lost. Code is automatically cleared after  
72 hours or upon power reset.  
* Proper flame sense microamps: 0.7 microamps D.C. minimum, 2.0 -- 4.0 microamps nominal  
NOTE 7) Continuous blower selection DIP 10 and 11 will cause the blower to run in high cooling speed for all low cooling (Y1) calls.  
Continuous blower DIP settings of 00 and 01 will allow low cooling (Y1) calls to operate normally.  
S
HUMIDIFIER -- The 24VAC HUM is energized when the low pressure switch closes on a call for heat. The 115V HUM (called  
HUM on Control) is energized when the inducer is energized.  
S
ELECTRONIC AIR CLEANER -- EAC is energized when there is a blower speed call. It is NOT energized when blower operates  
in the hard--wired continuous fan mode.  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING DIAGRAM  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. 24V HUM terminal on furnace control is used to  
power a humidifier (on call for heat and pressure  
switch closed) if no HUM thermostat option is  
available.  
9. DEHUM provides a 20% reduction in airflow (when  
Y1 or Y1 + Y2 is energized) when the furnace  
control DEHUM terminal is energized with 24V.  
10. If no DEHUM thermostat option is available, a  
dehumidistat that has closed contacts on a call for  
dehumidify may be used  
11. O provides a 10% reduction in airflow when Y1 or  
Y1 + Y2 is energized and O is NOT energized. (J2  
jumper on TSIB must be in HP COMFORT position  
to get this function. AC/HP EFFICIENCY position  
results in no reduction of airflow for Y1 or Y1 + Y2  
calls regardless of O being energized or not.)  
Thermostat Wiring Guide  
1. These diagrams are for reference. See thermostat  
wiring  
instructions  
for  
specific  
terminal  
assignments, connections or operation.  
2. Humidifier/humidistat is optional and not included  
with the furnace.  
3. Dehumidify feature requires thermostat with  
DEHUM feature or a separate dehumidistat to get  
the dehumidification operation. Dehumidistat is  
optional and not included with the furnace.  
4. Underlined terminal indicates intended use for  
multiple function terminals.  
5. TSIB terminals only available on 58HDV/359BAV  
models.  
6. Two-stage Air Conditioning or two-stage Heat  
Pump compatible.  
7. W2 furnace operation is from furnace control  
algorithm SW1 DIP switch #3 (TT) set to OFF.  
Furnace runs in Low Heat for 12 minutes then  
switches to High Heat if heating call still exists.  
12. For Heat Pump/Furnace systems, refer to Fossil Fuel  
Kit or Dual Fuel Thermostat Installation Instructions  
for wiring.  
TSIB NOTE 5  
NO CONNECTION  
NO CONNECTION  
Y1  
O
NOTE 11  
TWO-STAGE or VS  
FURNACE  
CONTROL  
SINGLE-STAGE  
THERMOSTAT  
W2  
NOTE 7  
SINGLE-STAGE  
W
Y
W1  
Y/Y2  
G
AIR CONDITIONER  
Y
G
R
R
DEHUM  
DEHUM  
NOTE 3, 9, 10  
C
COM  
C
24V HUM  
HUM  
OPTIONAL  
HUMIDIFIER  
24V in  
COM  
NOTE 2  
A07787  
Fig. 56 -- HUM and DEHUM Terminal available from Thermostat. Humidifier Wiring Models and Dehumidify Wiring  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TSIB NOTE 5  
Y1  
NO CONNECTION  
NO CONNECTION  
O
NOTE 11  
TWO-STAGE or VS  
FURNACE  
CONTROL  
SINGLE-STAGE  
THERMOSTAT  
W2  
NOTE 7  
SINGLE-STAGE  
OPTIONAL  
DEHUMIDISTAT  
W
Y
W1  
Y/Y2  
G
AIR CONDITIONER  
Y
1
2
G
R
R
Connect 1 to Y/Y2 for  
1-stage AC/ HP  
applications  
NOTE 3  
DEHUM  
C
COM  
C
24V HUM  
OPTIONAL  
HUMIDIFIER  
OPTIONAL  
HUMIDISTAT  
H-STAT  
24V in  
COM  
NOTE 2  
A09202  
Fig. 57 -- No HUM and/or DEHUM Terminal available from Thermostat. HuNmOiTdEif2ier Wiring Models  
and Dehumidify Wiring  
TSIB NOTE 5  
Y1  
NO CONNECTION  
O
NOTE 11  
NO CONNECTION  
(HP may use O)  
TWO-STAGE or VS  
FURNACE  
CONTROL  
SINGLE-STAGE  
THERMOSTAT  
W2  
NOTE 7  
SINGLE-STAGE  
OPTIONAL  
W
Y
W1  
Y/Y2  
G
AIR CONDITIONER  
DEHUMIDISTAT  
Y
1
2
G
R
R
Connect 1 to Y/Y2 for  
1-stage AC/ HP  
applications  
NOTE 3  
DEHUM  
C
COM  
C
24V HUM  
OPTIONAL  
HUMIDIFIER  
OPTIONAL  
HUMIDISTAT  
H-STAT  
24V in  
COM  
NOTE 2  
NOTE 2  
A09203  
Fig. 58 -- Single--Stage Thermostat with Variable Speed Furnace Models  
and Single--Stage Air Conditioner  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TWO-STAGE  
TSIB NOTE 5  
Y1  
THERMOSTAT  
Y1  
O
NOTE 11  
SINGLE STAGE  
AIR CONDITIONER  
VS FURNACE  
CONTROL  
OPTIONAL  
DEHUMIDISTAT  
If no DEHUM from  
thermostat available  
W2  
W2  
W1  
Y2  
G
NOTE 7  
W1  
Y/Y2  
G
1
2
Y
Connect 1 to Y1 for 2-  
stage AC-HP  
applications.  
R
R
NOTE 3, 9, 10  
DEHUM  
DEHUM  
OR  
Connect 1 to Y/Y2 for  
1-stage AC- HP  
applications  
C
COM  
C
24V HUM  
OPTIONAL  
HUMIDIFIER  
HUM  
24V in  
COM  
NOTE 2  
A09204  
Fig. 59 -- Two--Stage Thermostat with Variable Speed Furnace Models  
and Single--Stage Air Conditioner  
TSIBNOTE 5  
Y1  
THERMOSTAT  
Y1  
O
NOTE 11  
TWO-STAGE  
AIR CONDITIONER  
OPTIONAL  
DEHUMIDISTAT  
VS FURNACE  
CONTROL  
If no DEHUM from  
thermostat available  
Y1  
Y2  
W2  
W1  
Y2  
G
W2  
W1  
Y/Y2  
G
1
2
Connect 1 to Y1 for 2-  
stage AC-HP  
applications.  
R
R
NOTE 3, 9, 10  
DEHUM  
DEHUM  
OR  
Connect 1 to Y/Y2 for  
1-stage AC- HP  
applications  
C
COM  
C
24V HUM  
OPTIONAL  
HUMIDIFIER  
HUM  
24V in  
COM  
NOTE 2  
A09205  
Fig. 60 -- Two--Stage Thermostat with Variable Speed Furnace and Two--Stage Air Conditioner  
and Single--Stage Air Conditioner  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Catalog No: 58HDV---01SI  
Copyright 2009 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231  
Printed in U.S.A.  
Edition Date: 04/09  
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.  
Replaces: NEW  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Belkin Network Card F5U252 User Manual
Black Decker Saw FS1300CS User Manual
Black Decker Vacuum Cleaner FHV1080 User Manual
Bosch Appliances Home Security System D1265 User Manual
Brother Sewing Machine LS 2125 User Manual
Bushnell Camera Accessories 780050 User Manual
Cadco Convection Oven XAL 195 User Manual
Cannon Digital Camera PS1025 User Manual
Canon All in One Printer 5259B007AA User Manual
Cateye Watch Q3A User Manual