Carrier Air Conditioner 30RAP010 060 User Manual

30RAP010-060  
AQUASNAP® Air-Cooled Chillers  
with COMFORTLINK™ Controls  
Controls, Start-Up, Operation,  
Service, and Troubleshooting  
Page  
CONTENTS  
System Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44  
START-UP AND OPERATION . . . . . . . . . . . . . . . . . . . . 45,46  
Actual Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45  
Check Refrigerant Charge. . . . . . . . . . . . . . . . . . . . . . . . . 45  
Operating Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46  
Page  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . .2  
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18  
Conventions Used in this Manual. . . . . . . . . . . . . . . . . . . .3  
Basic Controls Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
CONTROLS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-44  
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19  
Main Base Board (MBB) . . . . . . . . . . . . . . . . . . . . . . . . . . . .19  
Energy Management Module (EMM) . . . . . . . . . . . . . . . .19  
Current Sensor Board (CSB) . . . . . . . . . . . . . . . . . . . . . . .19  
AUX Board (AUX) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19  
Expansion Valve Board (EXV) . . . . . . . . . . . . . . . . . . . . . .19  
Enable/Off/Remote Contact Switch . . . . . . . . . . . . . . . . .19  
Emergency On/Off Switch . . . . . . . . . . . . . . . . . . . . . . . . . .19  
Board Addresses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19  
Control Module Communication . . . . . . . . . . . . . . . . . . . .19  
Carrier Comfort Network® (CCN) Interface . . . . . . . . . .19  
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20  
TEMPERATURES  
LOW AMBIENT OPERATION  
VOLTAGE — ALL UNITS  
OPERATION SEQUENCE . . . . . . . . . . . . . . . . . . . . . .46,47  
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47-63  
Electronic Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47  
CONTROL COMPONENTS  
Electronic Expansion Valve (EXV). . . . . . . . . . . . . . . 47  
EXV Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . 47  
FIELD SERVICING INSTRUCTIONS  
VALVE REPLACEMENT  
VALVE REASSEMBLY  
Compressor Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . 49  
Cooler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49  
COOLER LEAVING FLUID SENSOR  
BRAZED-PLATE COOLER HEAT EXCHANGER  
REPLACEMENT  
BRAZED-PLATE COOLER HEAT EXCHANGER  
CLEANING  
COOLER ENTERING FLUID SENSOR  
COMPRESSOR RETURN GAS  
TEMPERATURE SENSOR  
OUTDOOR-AIR TEMPERATURE SENSOR (OAT)  
DISCHARGE TEMPERATURE THERMISTOR (DTT)  
REMOTE SPACE TEMPERATURE SENSOR OR DUAL  
LEAVING WATER TEMPERATURE SENSOR  
Oil Charge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50  
Microchannel Heat Exchanger (MCHX)  
Condenser Coil Maintenance and Cleaning  
Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50  
Check Refrigerant Feed Components . . . . . . . . . . . . . . 50  
Energy Management Module . . . . . . . . . . . . . . . . . . . . . . .29  
Loss-of-Cooler Flow Protection. . . . . . . . . . . . . . . . . . . . .29  
Electronic Expansion Valves (EXV) . . . . . . . . . . . . . . . . .29  
Capacity Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29  
FILTER DRIER  
MOISTURE-LIQUID INDICATOR  
MINIMUM LOAD VALVE  
PRESSURE RELIEF DEVICES  
MINUTES LEFT FOR START  
MINUTES OFF TIME  
LEAD/LAG DETERMINATION  
CAPACITY CONTROL OVERRIDES  
Check Unit Safeties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52  
HIGH-PRESSURE SWITCH  
PRESSURE TRANSDUCERS  
COOLER FREEZE-UP PROTECTION  
HEATER CABLE  
Head Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32  
Operation of Machine Based on Control Method  
and Cooling Set Point Selection Settings. . . . . . . . .32  
Cooling Set Point Select. . . . . . . . . . . . . . . . . . . . . . . . . . . .33  
Low Sound Mode Operation . . . . . . . . . . . . . . . . . . . . . . . .34  
Heating Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34  
Service Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34  
Optional Factory-Installed Hydronic Package. . . . . . .34  
Cooler Pump Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34  
Cooler Pump Sequence of Operation. . . . . . . . . . . . . . .35  
Configuring and Operating Dual Chiller Control . . . .36  
Temperature Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38  
Demand Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42  
WINTER SHUTDOWN  
Thermistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52  
Pressure Transducers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53  
Chilled Water Flow Switch. . . . . . . . . . . . . . . . . . . . . . . . . . 53  
Strainer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53  
Condenser Fans. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53  
Motormaster® V Controller . . . . . . . . . . . . . . . . . . . . . . . . . 58  
GENERAL OPERATION  
CONFIGURATION  
DRIVE PROGRAMMING  
EPM CHIP  
LOSS OF CCN COMMUNICATIONS  
REPLACING DEFECTIVE MODULES  
DEMAND LIMIT (2-Stage Switch Controlled)  
EXTERNALLY POWERED DEMAND LIMIT  
(4 to 20 mA Controlled)  
Hydronic Package. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63  
MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63,64  
Recommended Maintenance Schedule . . . . . . . . . . . . . 63  
Microchannel Heat Exchanger (MCHX)  
Condenser Coil Maintenance and Cleaning  
Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64  
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . 64-73  
DEMAND LIMIT (CCN Loadshed Controlled)  
Cooling Set Point (4 to 20 mA). . . . . . . . . . . . . . . . . . . . . .43  
Digital Scroll Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44  
DIGITAL SCROLL OPERATION  
DIGITAL COMPRESSOR CONFIGURATION  
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44,45  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Catalog No. 04-53300067-01 Printed in U.S.A. Form 30RAP-2T Pg 1 12-10 Replaces: 30RAP-1T  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control System for 30RAP units. The display has up and down  
arrow keys, an key, and an key. These  
GENERAL  
ESCAPE  
keys are used to navigate through the different levels of the  
display structure. Press the key until the highest  
ENTER  
This publication contains Controls, Start-Up, Operation,  
Service, and Troubleshooting information for the 30RAP  
AquaSnap® air-cooled chillers. See Table 1. These chillers are  
equipped with ComfortLinkcontrols and electronic expan-  
sion valves (EXVs).  
ESCAPE  
operating level is displayed to move through the top 11 mode  
levels indicated by LEDs on the left side of the display. See  
Fig. 1 and Tables 2-14.  
WARNING  
Once within a mode or sub-mode, pressing the  
ENTER  
keys simultaneously will put the scrolling  
This unit uses a microprocessor-based electronic control  
system. Do not use jumpers or other tools to short out or  
bypass components or otherwise depart from recom-  
mended procedures. Any short-to-ground of the control  
board or accompanying wiring may destroy the board or  
electrical component.  
and  
ESCAPE  
marquee display into expanded text mode where the full mean-  
ing of all sub-modes, items and their values can be displayed  
for the current selection. Press the  
and  
ESCAPE  
ENTER  
keys to return the scrolling marquee display to its default menu  
of rotating display items (those items in Run StatusVIEW).  
In addition, the password will be disabled, requiring that it be  
entered again before changes can be made to password protect-  
Table 1 — Unit Sizes  
UNIT  
NOMINAL CAPACITY (TONS)  
30RAP010  
30RAP015  
30RAP018  
30RAP020  
30RAP025  
30RAP030  
30RAP035  
30RAP040  
30RAP045  
30RAP050  
30RAP055  
30RAP060  
10  
14  
16  
19  
24  
28  
34  
39  
43  
48  
53  
56  
ed items. Press the  
text mode.  
key to exit out of the expanded  
ESCAPE  
NOTE: When the Language Selection (Configuration  
DISPLANG), variable is changed, all appropriate display  
expansions will immediately change to the new language. No  
power-off or control reset is required when reconfiguring  
languages.  
When a specific item is located, the item name alternates  
with the value. Press the  
ENTER  
and the value will be displayed. Press  
key at a changeable item  
again and the  
ENTER  
value will begin to flash indicating that the value can be  
changed. Use the up and down arrow keys to change the value,  
Conventions Used in This Manual — The follow-  
ing conventions for discussing configuration points for the  
local display (scrolling marquee or Navigator™ accessory)  
will be used in this manual.  
and confirm the value by pressing the  
key.  
ENTER  
Point names will be written with the mode name first, then  
any sub-modes, then the point name, each separated by an  
arrow symbol (. Names will also be shown in bold  
and italics. As an example, the Lead/Lag Circuit Select Point,  
which is located in the Configuration mode, Option sub-mode,  
would be written as Configuration OPTNLLCS.  
MODE  
Run Status  
Service Test  
Temperature  
Pressures  
Setpoints  
Alarm Status  
Inputs  
Outputs  
This path name will show the user how to navigate through  
the local display to reach the desired configuration. The user  
would scroll through the modes and sub-modes using the  
Configuration  
Time Clock  
Operating Modes  
Alarms  
ESCAPE ENTER  
and  
keys. The arrow symbol in the path name repre-  
to move into the next level of the  
Fig. 1 — Scrolling Marquee Display  
sents pressing  
menu structure.  
ENTER  
Changing item values or testing outputs is accomplished in  
the same manner. Locate and display the desired item. Press  
When a value is included as part of the path name, it will be  
shown at the end of the path name after an equals sign. If the  
value represents a configuration setting, an explanation will  
be shown in parenthesis after the value. As an example,  
ConfigurationOPTNLLCS = 1 (Circuit A leads).  
so that the item value flashes. Use the arrow keys to  
ENTER  
change the value or state and press the  
key to accept  
ENTER  
key to return to the next higher level of  
it. Press the  
ESCAPE  
structure. Repeat the process as required for other items.  
Pressing the  
and  
keys simultaneously  
ESCAPE  
ENTER  
Items in the Configuration and Service Test modes are pass-  
word protected. The words ‘PASS’ and ‘WORD’ will alternate  
on the display when required. The default password is 0111.  
will scroll an expanded text description of the point name or  
value across the display. The expanded description is shown in  
the local display tables but will not be shown with the path  
names in text.  
The CCN (Carrier Comfort Network®) point names are also  
referenced in the local display tables for users configuring the  
unit with CCN software instead of the local display. The CCN  
tables are located in Appendix B of the manual.  
Press  
ENTER  
and the 1111 password will be displayed. Press  
ENTER  
again and the first digit will begin to flash. Use the  
arrow keys to change the number and press  
to accept  
ENTER  
the digit. Continue with the remaining digits of the password.  
The password can only be changed through CCN operator in-  
terface software such as ComfortWORKS®, ComfortVIEW™  
and Service Tool.  
Basic Controls Usage  
SCROLLING MARQUEE DISPLAY — The scrolling mar-  
quee display is the standard interface display to the ComfortLink  
See Tables 2-14 and Appendix A for further details.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORY NAVIGATOR™ DISPLAY MODULE —  
The Navigator module provides a mobile user interface to the  
ComfortLink™ control system, which is only available as a  
the Navigator module, press the  
play reads, “Select a menu item.” Using the arrow keys move  
to the Configuration mode. Press  
this mode. The display will read:  
key until the dis-  
ESCAPE  
to obtain access to  
ENTER  
field-installed accessory. The display has up and down arrow  
keys, an  
key, and an  
key. These keys are  
ESCAPE  
used to navigate through the different levels of the display  
structure. Press the key until ‘Select a Menu Item’  
ENTER  
> TEST OFF  
METR OFF  
LANG ENGLISH  
ESCAPE  
is displayed to move through the top 11 mode levels indicated  
by LEDs on the left side of the display. See Fig. 2.  
Pressing  
will cause the “OFF” to flash. Use the up  
ENTER  
or down arrow to change “OFF” to “ON”. Pressing  
ENTER  
will illuminate all LEDs and display all pixels in the view  
screen. Pressing and simultaneously  
Once within a Mode or sub-mode, a “>” indicates the cur-  
rently selected item on the display screen. Pressing the  
ESCAPE  
ENTER  
and  
keys simultaneously will put the Nav-  
ESCAPE  
ENTER  
allows the user to adjust the display contrast. Use the up or  
down arrows to adjust the contrast. The screen’s contrast will  
change with the adjustment. Press  
change. The Navigator module will keep this setting as long as  
it is plugged in to the LEN bus.  
igator module into expanded text mode where the full meaning  
of all sub-modes, items and their values can be displayed. Press-  
to accept the  
ENTER  
ing the  
and  
keys when the display says  
ESCAPE  
ENTER  
‘Select Menu Item’ (Mode LED level) will return the Navigator  
module to its default menu of rotating display items (those items  
in Run StatusVIEW). In addition, the password will be dis-  
abled, requiring that it be entered again before changes can be  
Adjusting the Backlight Brightness — The backlight of the  
display can be adjusted to suit ambient conditions. The factory  
default is set to the highest level. To adjust the backlight of the  
made to password protected items. Press the  
exit out of the expanded text mode.  
key to  
ESCAPE  
Navigator module, press the  
key until the display  
ESCAPE  
reads, “Select a menu item.” Using the arrow keys move to the  
NOTE: When the Language Selection (Configuration  
DISPLANG), variable is changed, all appropriate display  
expansions will immediately change to the new language. No  
power-off or control reset is required when reconfiguring  
languages.  
Configuration mode. Press  
mode. The display will read:  
> TEST OFF  
to obtain access to this  
ENTER  
METR OFF  
LANG ENGLISH  
will cause the “OFF” to flash. Use the up  
When a specific item is located, the item name appears on the  
left of the display, the value will appear near the middle of the  
display and the units (if any) will appear on the far right of the  
Pressing  
ENTER  
or down arrow keys to change “OFF” to “ON”. Pressing  
will illuminate all LEDs and display all pixels in the  
ENTER  
display. Press the  
key at a changeable item and the val-  
ENTER  
ue will begin to flash. Use the up and down arrow keys to change  
the value, and confirm the value by pressing the key.  
view screen. Pressing the up and down arrow keys simultane-  
ously allows the user to adjust the display brightness. Use the  
up or down arrow keys to adjust screen brightness. Press  
to accept the change. The Navigator module will  
keep this setting as long as it is plugged in to the LEN bus.  
ENTER  
Changing item values or testing outputs is accomplished in  
the same manner. Locate and display the desired item. Press  
ENTER  
so that the item value flashes. Use the arrow keys to  
ENTER  
change the value or state and press the  
key to accept  
ENTER  
key to return to the next higher level of  
Comf  
it. Press the  
ESCAPE  
or  
t
Link  
structure. Repeat the process as required for other items.  
Items in the Configuration and Service Test modes are pass-  
word protected. The words Enter Password will be displayed  
when required, with 1111 also being displayed. The default  
password is 1111. Use the arrow keys to change the number  
MODE  
Alar  
Run Status  
m
Status  
Ser  
vice  
Te  
s
t
Te  
m
per  
atur  
es  
Pressure  
Setpoints  
Inputs  
s
Outputs  
Configur  
ation  
Cloc  
k
Tim  
e
and press  
to enter the digit. Continue with the re-  
ESC  
ENTER  
Oper  
ating Modes  
Alar  
m
s
maining digits of the password. The password can only be  
changed through CCN operator interface software such as  
ComfortWORKS, ComfortVIEW and Service Tool.  
ENTER  
Adjusting the Contrast — The contrast of the display can be  
adjusted to suit ambient conditions. To adjust the contrast of  
Fig. 2 — Accessory Navigator™ Display Module  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 2 — Scrolling Marquee Display Menu Structure*  
RUN  
STATUS  
SERVICE  
TEST  
SET  
POINTS  
TIME  
CLOCK  
OPERATING  
MODES  
MODE  
TEMPERATURES PRESSURES  
INPUTS OUTPUTS CONFIGURATION  
ALARMS  
Auto  
View of  
Run Status  
(VIEW)  
Service  
Test Mode  
(TEST)  
Ent and Leave Unit  
Temps  
Pressures  
Ckt A  
(PRC.A)  
Cooling  
Setpoints  
(COOL)  
General  
Inputs  
(GEN.I)  
General  
Outputs  
(GEN.O)  
Display  
Configuration  
(DISP)  
Time of  
Day  
(TIME)  
Modes  
(MODE)  
Current  
(CRNT)  
(UNIT)  
Unit Run  
Hour and  
Start  
Head  
Outputs  
Circuit A  
EXV  
Month,  
Date, Day,  
and Year  
(DATE)  
Outputs  
and Pumps  
(OUTS)  
Temperatures  
Ckt A  
(CIR.A)  
Pressures  
Ckt B  
(PRC.B)  
Circuit  
Inputs  
(CRCT)  
Unit  
Configuration  
(UNIT)  
Reset  
Alarms  
(RCRN)  
Pressure  
Setpoint  
(HEAD)  
(RUN)  
(A.EXV)  
Brine  
Freeze  
Setpoint  
(FRZ)  
Outputs  
Circuit B  
EXV  
Daylight  
Savings  
Time  
Compressor Ciruit A Comp  
Temperatures  
Ckt B  
(CIR.B)  
4-20mA  
Inputs  
(4-20)  
Unit Options 1  
Hardware  
(OPT1)  
Alarm  
History  
(HIST)  
Run Hours  
(HOUR)  
Test  
(CMPA)  
(B.EXV)  
(DST)  
Local  
Holiday  
Schedules  
(HOL.L)  
Compressor Ciruit B Comp  
Outputs  
Circuit A  
(CIR.A)  
Unit Options 2  
Controls  
(OPT2)  
Starts  
Test  
(STRT)  
(CMPB)  
Local  
Occu-  
Preventive  
Maintenance  
(PM)  
Outputs  
Circuit B  
(CIR.B)  
CCN Network  
Configuration  
(CCN)  
pancy  
Schedule  
(SCH.L)  
Software  
Version  
(VERS)  
Head Pressure  
Comp. Delta  
(HP.A)  
Head Pressure  
Comp. Delta  
(HP.B)  
Schedule  
Override  
(OVR)  
SUB-MODE  
Cir. A EXV  
Configuration  
(EXV.A)  
Cir. B EXV  
Configuration  
(EXV.B)  
Motormaster  
Configuration  
(MM)  
Reset Cool Temp  
(RSET)  
Set Point and  
Ramp Load  
(SLCT)  
Service  
Configuration  
(SERV)  
Broadcast  
Configuration  
(BCST)  
LEGEND  
Ckt — Circuit  
*Throughout this text, the location of items in the menu structure will be  
described in the following format:  
Item Expansion (Mode NameSub-mode NameITEM)  
For example, using the language selection item:  
Language Selection (ConfigurationDISPLANG)  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 3 — Run Status Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
DISPLAY SUB-ITEM DISPLAY SUB-ITEM DISPLAY  
EXPANSION  
SUB-MODE  
VIEW  
ITEM  
EWT  
LWT  
COMMENT  
ENTER  
XXX.X F  
ENTERING FLUID TEMP  
LEAVING FLUID TEMP  
ACTIVE SETPOINT  
CONTROL POINT  
XXX.X F  
SETP XXX.X F  
CTPT XXX.X F  
LOD.F  
STAT  
XXX  
X
LOAD/UNLOAD FACTOR  
CONTROL MODE  
0 = Service Test  
1 = Off Local  
2 = Off CCN  
3 = Off Time  
4 = Off Emrgcy  
5 = On Local  
6 = On CCN  
7 = On Time  
8 = Ht Enabled  
9 = Pump Delay  
LD.PM  
OCC  
LEAD PUMP  
OCCUPIED  
YES/NO  
YES/NO  
LS.AC  
LOW SOUND ACTIVE  
OVERRIDE MODES IN EFFECT  
PERCENT TOTAL CAPACITY  
REQUESTED STAGE  
CURRENT ALARMS & ALERTS  
TIME OF DAY  
MODE YES/NO  
CAP  
STGE  
ALRM  
TIME  
XXX %  
X
XXX  
XX.XX  
XX  
00.00-23.59  
1 = January, 2 = February, etc.  
01-31  
MNTH  
DATE  
YEAR  
MONTH OF YEAR  
XX  
DAY OF MONTH  
XX  
YEAR OF CENTURY  
MACHINE OPERATING HOURS  
MACHINE STARTS  
RUN  
ENTER  
HRS.U XXXX HRS  
STR.U  
HR.P1  
HR.P2  
XXXX  
XXXX.X  
XXXX.X  
PUMP 1 RUN HOURS  
PUMP 2 RUN HOURS  
CIRCUIT A RUN HOURS  
HOUR  
ENTER  
HRS.A XXXX HRS  
HRS.B XXXX HRS  
HR.A1 XXXX HRS  
HR.A2 XXXX HRS  
HR.B1 XXXX HRS  
HR.B2 XXXX HRS  
CIRCUIT B RUN HOURS  
See Note  
COMPRESSOR A1 RUN HOURS  
COMPRESSOR A2 RUN HOURS  
COMPRESSOR B1 RUN HOURS  
COMPRESSOR B2 RUN HOURS  
COMPRESSOR A1 STARTS  
COMPRESSOR A2 STARTS  
COMPRESSOR B1 STARTS  
COMPRESSOR B2 STARTS  
PUMP MAINTENANCE  
See Note  
See Note  
STRT  
ENTER  
ST.A1  
ST.A2  
ST.B1  
ST.B2  
PUMP  
XXXX  
XXXX  
XXXX  
XXXX  
See Note  
See Note  
PM  
ENTER  
ENTER  
SI.PM  
P.1.DN  
P.2.DN  
P.1.MN  
P.2.MN  
XXXX HRS  
XXXX HRS  
XXXX HRS  
YES/NO  
PUMP SERVICE INTERVAL  
PUMP 1 SERVICE COUNTDOWN  
PUMP 2 SERVICE COUNTDOWN  
PUMP 1 MAINTENANCE DONE  
PUMP 2 MAINTENANCE DONE  
Default: 8760  
User Entry  
User Entry  
YES/NO  
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 3 — Run Status Mode and Sub-Mode Directory (cont)  
KEYPAD  
ENTRY  
ITEM  
DISPLAY SUB-ITEM DISPLAY SUB-ITEM DISPLAY  
EXPANSION  
SUB-MODE  
PM (cont)  
ITEM  
COMMENT  
PMDT  
PUMP MAINTENANCE DATES  
ENTER  
P.1.M0  
P.1.M1  
P.1.M2  
P.1.M3  
P.1.M4  
P.2.M0  
P.2.M1  
P.2.M2  
P.2.M3  
P.2.M4  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
ENTER  
ENTER  
STRN  
STRAINER MAINTENANCE  
STRAINER SRVC INTERVAL  
STRAINER SRVC COUNTDOWN  
STRAINER MAINT. DONE  
STRAINER MAINT. DATES  
MM/DD/YY HH:MM  
SI.ST  
S.T.DN  
S.T.MN  
ST.DT  
XXXX HRS  
XXXX HRS  
YES/NO  
Default: 8760  
User Entry  
ENTER  
S.T.M0  
S.T.M1  
S.T.M2  
S.T.M3  
S.T.M4  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
ENTER  
ENTER  
COIL  
COIL MAINTENANCE  
COIL SRVC INTER  
SI.CL  
C.L.DN  
C.L.MN  
CL.DT  
XXXX HRS  
XXXX HRS  
YES/NO  
Default: 8760  
User Entry  
COIL SERVICE COUNTDOWN  
COIL MAINT. DONE  
COIL MAINTENANCE DATES  
MM/DD/YY HH:MM  
ENTER  
C.L.M0  
C.L.M1  
C.L.M2  
C.L.M3  
C.L.M4  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
VERS  
ENTER  
MBB  
EXV  
CESR131460-xx-xx  
xx-xx is Version number*  
xx-xx is Version number*  
xx-xx is Version number*  
xx-xx is Version number*  
xx-xx is Version number*  
xx-xx is Version number*  
CESR131172-xx-xx  
AUX1  
EMM  
MARQ  
NAVI  
CESR131333-xx-xx  
CESR131174-xx-xx  
CESR131171-xx-xx  
CESR130227-xx-xx  
*Press  
ENTER  
and  
ESCAPE  
simultaneously to obtain version number.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4 — Service Test Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
TEST  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
ON/OFF  
SERVICE TEST MODE  
To Enable Service Test Mode,  
move Enable/Off/Remote  
Contact switch to OFF. Change  
TEST to ON. Move switch to  
ENABLE.  
ENTER  
OUTS  
OUTPUTS AND PUMPS  
EXV A % OPEN  
ENTER  
EXV.A  
EXV.B  
FAN1  
FAN2  
FAN3  
FAN4  
FAN5  
FAN6  
V.HPA  
V.HPB  
CLP.1  
CLP.2  
UL.TM  
CL.HT  
RMT.A  
0 to 100%  
0 to 100%  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
0 to 100%  
0 to 100%  
ON/OFF  
ON/OFF  
0 to 15  
EXV B % OPEN  
FAN 1 RELAY  
FAN 2 RELAY  
FAN 3 RELAY  
FAN 4 RELAY  
FAN 5 RELAY  
FAN 6 RELAY  
VAR HEAD PRESS %  
VAR HEAD PRESS %  
COOLER PUMP 1 RELAY  
COOLER PUMP 2 RELAY  
COMP A1 UNLOAD TIME  
COOLER/PUMP HEATER  
REMOTE ALARM RELAY  
ON/OFF  
ON/OFF  
CMPA  
CIRCUIT A COMPRESSOR TEST  
COMPRESSOR A1 RELAY  
ENTER  
CC.A1  
UL.TM  
CC.A2  
CC.A3  
CC.A4  
MLV  
ON/OFF  
0 to 15  
COMP A1 UNLOAD TIME  
COMPRESSOR A2 RELAY  
COMPRESSOR A3 RELAY  
COMPRESSOR A4 RELAY  
MINIMUM LOAD VALVE RELAY  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
CMPB  
CIRCUIT B COMPRESSOR TEST  
COMPRESSOR B1 RELAY  
See Note  
ENTER  
CC.B1  
CC.B2  
CC.B3  
CC.B4  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
COMPRESSOR B2 RELAY  
COMPRESSOR B3 RELAY  
COMPRESSOR B4 RELAY  
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5 — Temperature Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
UNIT  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
ENT AND LEAVE UNIT TEMPS  
ENTER  
ENTER  
ENTER  
CEWT  
CLWT  
OAT  
XXX.X F  
XXX.X F  
XXX.X F  
XXX.X F  
XXX.X F  
COOLER ENTERING FLUID  
COOLER LEAVING FLUID  
OUTSIDE AIR TEMPERATURE  
SPACE TEMPERATURE  
SPT  
DLWT  
LEAD/LAG LEAVING FLUID  
CIR.A  
TEMPERATURES CIRCUIT A  
SCT.A  
SST.A  
RGT.A  
D.GAS  
SH.A  
XXX.X F  
XXX.X F  
XXX.X F  
XXX.X F  
XXX.X ^F  
SATURATED CONDENSING TMP  
SATURATED SUCTION TEMP  
COMPR RETURN GAS TEMP  
DISCHARGE GAS TEMP  
SUCTION SUPERHEAT TEMP  
CIR.B  
TEMPERATURES CIRCUIT B  
See Note  
See Note  
SCT.B  
SST.B  
RGT.B  
SH.B  
XXX.X F  
XXX.X F  
XXX.X F  
XXX.X ^F  
SATURATED CONDENSING TMP  
SATURATED SUCTION TEMP  
COMPR RETURN GAS TEMP  
SUCTION SUPERHEAT TEMP  
See Note  
See Note  
See Note  
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.  
Table 6 — Pressure Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
PRC.A  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
PRESSURES CIRCUIT A  
ENTER  
DP.A  
SP.A  
XXX.X PSIG  
XXX.X PSIG  
DISCHARGE PRESSURE  
SUCTION PRESSURE  
PRC.B  
PRESSURES CIRCUIT B  
DISCHARGE PRESSURE  
See Note  
See Note  
ENTER  
DP.B  
SP.B  
XXX.X PSIG  
XXX.X PSIG  
SUCTION PRESSURE  
See Note  
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.  
Table 7 — Set Points Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
COOL  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
COOLING SETPOINTS  
ENTER  
CSP.1  
CSP.2  
CSP.3  
XXX.X F  
XXX.X F  
XXX.X F  
COOLING SETPOINT 1  
Default: 44 F  
Default: 44 F  
Default: 32 F  
COOLING SETPOINT 2  
ICE SETPOINT  
HEAD  
HEAD PRESSURE SETPOINTS  
HEAD SETPOINT  
ENTER  
H.DP  
F. ON  
XXX.X F  
XXX.X F  
XXX.X F  
XXX.X F  
XXX.X F  
Default: 95 F  
Default: 95 F  
Default: 72 F  
Default: 23 F  
Default: 15 F  
FAN ON SETPOINT  
FAN OFF SETPOINT  
F.OFF  
B.OFF  
F.DLT  
BASE FAN OFF DELTA TEMP  
FAN STAGE DELTA  
FRZ  
BRINE FREEZE SETPOINT  
BRINE FREEZE POINT  
ENTER  
BR.FZ  
XXX.X F  
Default: 34 F  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8 — Inputs Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
GEN.I  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
GENERAL INPUTS  
ENTER  
STST  
FLOW  
PM.F.1  
PM.F.2  
HT.RQ  
DLS1  
STRT/STOP  
ON/OFF  
START/STOP SWITCH  
COOLER FLOW SWITCH  
COOLER PUMP 1 INTERLOCK  
COOLER PUMP 2 INTERLOCK  
HEAT REQUEST  
OPEN/CLSE  
OPEN/CLSE  
ON/OFF  
ON/OFF  
DEMAND LIMIT SWITCH 1  
DEMAND LIMIT SWITCH 2  
ICE DONE  
DLS2  
ON/OFF  
ICED  
ON/OFF  
DUAL  
ON/OFF  
DUAL SETPOINT SWITCH  
CRCT  
CIRCUITS INPUTS  
ENTER  
FKA1  
FKA2  
FKA3  
FKA4  
FKB1  
FKB2  
FKB3  
FKB4  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
COMPRESSOR A1 FEEDBACK  
COMPRESSOR A2 FEEDBACK  
COMPRESSOR A3 FEEDBACK  
COMPRESSOR A4 FEEDBACK  
COMPRESSOR B1 FEEDBACK  
COMPRESSOR B2 FEEDBACK  
COMPRESSOR B3 FEEDBACK  
COMPRESSOR B4 FEEDBACK  
See Note  
See Note  
See Note  
See Note  
4-20  
4-20 MA INPUTS  
ENTER  
DMND  
RSET  
CSP  
XX.X MA  
XX.X MA  
XX.X MA  
4-20 MA DEMAND SIGNAL  
4-20 MA RESET SIGNAL  
4-20 MA COOLING SETPOINT  
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.  
Table 9 — Outputs Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
GEN.O  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
GENERAL OUTPUTS  
ENTER  
FAN1  
FAN2  
FAN3  
FAN4  
FAN5  
FAN6  
V.HPA  
V.HPB  
C.WP1  
C.WP2  
CLHT  
MLV.R  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
FAN 1 RELAY  
FAN 2 RELAY  
FAN 3 RELAY  
FAN 4 RELAY  
FAN 5 RELAY  
FAN 6 RELAY  
FAN SPEED CIRCUIT A  
FAN SPEED CIRCUIT B  
COOLER PUMP RELAY 1  
COOLER PUMP RELAY 2  
COOLER/PUMP HEATER  
MINIMUM LOAD VALVE RELAY  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9 — Outputs Mode and Sub-Mode Directory (cont)  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
A.EXV  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
OUTPUTS CIRCUIT A EXV  
ENTER  
EXV.A  
APPR  
AP.SP  
X.SH.R  
S.SH.R  
SH_R  
0 to 100%  
ON/OFF  
EXV % OPEN  
CIRCUIT A APPROACH  
APPROACH SETPOINT  
SH RESET AT MAX UNL-DIG  
DIGLOAD TO START SH RST  
AMOUNT OF SH RESET  
EXVA OVERRIDE  
OVR.A  
SPH.A  
ASH.S  
AMP.S  
PLM.A  
SPR.1  
SUCTION SUPERHEAT TEMP  
ACTIVE SUPERHEAT SETPT  
ACTIVE MOP SETPT  
CIR A EXV POSITION LIMIT  
SPARE 1 TEMPERATURE  
B.EXV  
OUTPUTS CIRCUIT B EXV  
EXV % OPEN  
ENTER  
EXV.B  
APPR  
AP.SP  
OVR.B  
SPH.B  
ASH.S  
AMP.S  
PLM.B  
SPR.2  
0 to 100%  
ON/OFF  
CIRCUIT B APPROACH  
APPROACH SETPOINT  
EXVB OVERRIDE  
SUCTION SUPERHEAT TEMP  
ACTIVE SUPERHEAT SETPT  
ACTIVE MOP SETPT  
CIR B EXV POSITION LIMIT  
SPARE 2 TEMPERATURE  
CIR.A  
OUTPUTS CIRCUIT A  
ENTER  
CC.A1  
DPE.R  
CC.A2  
CC.A3  
CC.A4  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
COMPRESSOR A1 RELAY  
COMP A1 LOAD PERCENT  
COMPRESSOR A2 RELAY  
COMPRESSOR A3 RELAY  
COMPRESSOR A4 RELAY  
CIR.B  
OUTPUTS CIRCUIT B (See Note)  
ENTER  
CC.B1  
CC.B2  
CC.B3  
CC.B4  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
COMPRESSOR B1 RELAY  
COMPRESSOR B2 RELAY  
COMPRESSOR B3 RELAY  
COMPRESSOR B4 RELAY  
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.  
Table 10 — Configuration Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
DISP  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
DISPLAY CONFIGURATION  
ENTER  
TEST  
ON/OFF  
TEST DISPLAY LEDS  
METR  
LANG  
ON/OFF  
X
METRIC DISPLAY  
Off = English; On = Metric  
Default: 0  
0 = English  
LANGUAGE SELECTION  
1 = Espanol  
2 = Francais  
3 = Portuguese  
PAS.E  
PASS  
ENBL/DSBL  
xxxx  
PASSWORD ENABLE  
SERVICE PASSWORD  
Default: Enable  
Default: 1111  
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 10 — Configuration Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
UNIT  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
ENTER  
UNIT CONFIGURATION  
SIZE  
SZA.1  
SZA.2  
SZA.3  
SZA.4  
SZB.1  
SZB.2  
SZB.3  
SZB.4  
SH.SP  
FAN.S  
XX  
XX  
UNIT SIZE  
COMPRESSOR A1 SIZE  
Unit Dependent  
Unit Dependent  
Unit Dependent  
Unit Dependent  
Unit Dependent  
Unit Dependent  
Unit Dependent  
Unit Dependent  
Default: 9 F  
XX  
COMPRESSOR A2 SIZE  
COMPRESSOR A3 SIZE  
COMPRESSOR A4 SIZE  
COMPRESSOR B1 SIZE  
COMPRESSOR B2 SIZE  
COMPRESSOR B3 SIZE  
COMPRESSOR B4 SIZE  
SUPERHEAT SETPOINT  
NUMBER OF FANS  
XX  
XX  
XX  
XX  
XX  
XX  
XX.X F  
1 = One Fan  
2 = Two Fans  
3 = Three Fans  
4 = Four Fans  
Default: Yes  
EXV  
YES/NO  
YES/NO  
EXV MODULE INSTALLED?  
COMPRESSOR A1 DIGITAL?  
Default: No  
Yes = A1 Compressor is Digital  
Scroll  
A1.TY  
Default: 7  
Max 12 010,015  
Max 10 018-060  
MAX.T  
0 to 12  
MAXIMUM A1 UNLOAD TIME  
UNIT OPTIONS 1 HARDWARE  
COOLER FLUID  
OPT1  
Default: Water  
1 = Water  
2 = Medium Temperature  
Brine  
ENTER  
FLUD  
X
MLV.S  
D.G.EN  
CSB.E  
CPC  
YES/NO  
ENBL/DSBL  
ENBL/DSBL  
ON/OFF  
MINIMUM LOAD VALVE SELECT  
DISCHARGE GAS TEMP ENABLE  
CSB BOARDS ENABLE  
Default: No  
Default: Off  
Default: No  
COOLER PUMP CONTROL  
COOLER PUMP 1 ENABLE  
COOLER PUMP 2 ENABLE  
PM1E  
PM2E  
YES/NO  
YES/NO  
PM.P.S  
PM.SL  
YES/NO  
X
COOLER PMP PERIODIC STRT  
COOLER PUMP SELECT  
Default: Automatic  
0 = Automatic  
1 = Pump 1 Starts first  
2 = Pump 2 Starts first  
0 to 10 minutes, Default: 1  
min.  
PM.DY  
XX MIN  
COOLER PUMP SHUTDOWN DLY  
PM.DT  
ROT.P  
EMM  
XXXX HRS  
YES/NO  
PUMP CHANGEOVER HOURS  
ROTATE COOLER PUMPS NOW  
EMM MODULE INSTALLED  
Default: 500 hours  
User Entry  
YES/NO  
0 = RTPF  
1 = MCHX Default MCHX  
CND.T  
0,1  
COND HX  
MOPS  
APPR  
XX  
XX  
EXV MOP SET POINT  
Range: 40 - 80 Default: 50  
Range: 5 - 40 Default: 9.0  
CONFIG APPROACH SETPOINT  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 10 — Configuration Mode and Sub-Mode Directory (cont)  
KEYPAD  
ITEM  
SUB-MODE  
OPT2  
ITEM  
DISPLAY  
COMMENT  
ENTRY  
EXPANSION  
UNIT OPTIONS 2 CONTROLS  
CONTROL METHOD  
CTRL  
X
Default: Switch  
ENTER  
0 = Enable/Off/Remote Switch  
2 = Occupancy  
3 = CCN Control  
LOAD  
LLCS  
X
X
LOADING SEQUENCE SELECT  
LEAD/LAG CIRCUIT SELECT  
Default: Equal  
1 = Equal  
2 = Staged  
Default: Automatic  
1 = Automatic  
2 = Circuit A Leads  
3 = Circuit B Leads  
Default: 60  
LCWT  
DELY  
XX.X F  
HIGH LCW ALERT LIMIT  
MINUTES OFF TIME  
Range: 2 to 60 F  
Default: 0 Minutes  
Range: 0 to 15 Minutes  
XX  
ENBL/DSBL  
X
ICE.M  
LS.MD  
ICE MODE ENABLE  
Default: Disable  
LOW SOUND MODE SELECT  
Default: 0  
0 = Mode Disable  
1 = Fan Noise Only  
2 = Fan/Compressor Noise  
LS.ST  
LS.ND  
LS.LT  
00:00  
00:00  
LOW SOUND START TIME  
LOW SOUND END TIME  
Default: 00:00  
Default: 00:00  
Default: 100%  
Range: 0 to 100%  
XXX %  
LOW SOUND CAPACITY LIMIT  
CCN  
CCN NETWORK CONFIGURATION  
CCN ADDRESS  
Default: 1  
Range: 1 to 239  
CCNA  
XXX  
ENTER  
Default: 0  
CCNB  
BAUD  
XXX  
X
CCN BUS NUMBER  
CCN BAUD RATE  
Range: 0 to 239  
Default: 9600  
1 = 2400  
2 = 4800  
3 = 9600  
4 = 19,200  
5 = 38,400  
HP.A  
HP.B  
HEAD PRESSURE CMP DELTA  
SCT DELTA FOR COMP A1  
ENTER  
A1.DT  
A2.DT  
XX  
XX  
Range: 0 - 50 Default: 12  
Range: 0 - 50 Default: 12  
SCT DELTA FOR COMP A2  
HEAD PRESSURE CMP DELTA  
SCT DELTA FOR COMP B1  
ENTER  
B1.DT  
B2.DT  
XX  
XX  
Range: 0 - 50 Default: 12  
Range: 0 - 50 Default: 12  
SCT DELTA FOR COMP B2  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 10 — Configuration Mode and Sub-Mode Directory (cont)  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
EXV.A  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
CIR A EXV CONFIGURATION  
ENTER  
STR.A  
MIN.A  
RNG.A  
SPD.A  
POF.A  
MIN.A  
MAX.A  
OVR.A  
TYP.A  
H.SCT  
X.PCT  
X.PER  
A.PCT  
M.PCT  
S.PCT  
DELY  
XXX  
XXX  
EXV CIRC.A START POS  
Range: 0 - 100 Default: 30  
Range: 0 - 100 Default: 8  
Range: 0 - 65535 Default: *  
Range: 0 - 65535 Default: 200  
Range: 0 - 100 Default: 0  
Range: 0 - 65535 Default: 0  
Range: 0 - 65535 Default: *  
Range: 0 - 65535 Default: 167  
EXV CIRC.A MIN POSITION  
EXVA STEPS IN RANGE  
EXVA STEPS PER SECOND  
EXVA FAIL POSITION IN %  
EXVA MINIMUM STEPS  
XXXXX  
XXXXX  
XXX  
XXXXX  
XXXXX  
XXX  
EXVA MAXIMUM STEPS  
EXVA OVERRUN STEPS  
EXVA STEPPER TYPE  
0 = UNIPOLAR  
1 = BIPOLAR Default: 1  
0,1  
XXX  
HIGH SCT THRESHOLD  
OPEN EXV X% ON 2ND COMP  
MOVE EXV X% ON DISCRSOL  
PRE-OPEN EXV - FAN ADDING  
PRE-CLOSE EXV - FAN SUB  
PRE-CLOSE EXV - LAG SHUT  
LAG START DELAY  
Range: 50 - 140 Default: 115  
Range: 0 - 30 Default: 10  
Range: 0 - 30 Default: 5  
Range: 0 - 100 Default: 10  
Range: 0 - 100 Default: 10  
Range: 0 - 100 Default: 10  
Range: 0 - 100 Default: 10  
XX  
XX  
XXX  
XXX  
XXX  
XXX  
EXV.B  
CIR B EXV CONFIGURATION  
EXV CIRC.B START POS  
ENTER  
STR.B  
MIN.B  
RNG.B  
SPD.B  
POF.B  
MIN.B  
MAX.B  
OVR.B  
TYP.B  
XXX  
XXX  
Range: 0 - 100 Default: 50  
Range: 0 - 100 Default: 8  
Range: 0 - 65535 Default: *  
Range: 0 - 65535 Default: 200  
Range: 0 - 100 Default: 0  
Range: 0 - 65535 Default: 0  
Range: 0 - 65535 Default: *  
Range: 0 - 65535 Default: 167  
EXV CIRC.B MIN POSITION  
EXVB STEPS IN RANGE  
EXVB STEPS PER SECOND  
EXVB FAIL POSITION IN %  
EXVB MINIMUM STEPS  
EXVB MAXIMUM STEPS  
EXVB OVERRUN STEPS  
EXVB STEPPER TYPE  
XXXXX  
XXXXX  
XXX  
XXXXX  
XXXXX  
XXX  
0 = UNIPOLAR  
1 = BIPOLAR Default: 1  
0,1  
MM  
MOTORMASTER CONFIGURATION  
MOTORMASTER SELECT  
ENTER  
MMR.S  
P.GAN  
I.GAN  
D.GAN  
MIN.S  
YES/NO  
XX  
HEAD PRESSURE P GAIN  
HEAD PRESSURE I GAIN  
HEAD PRESSURE D GAIN  
MINIMUM FAN SPEED  
Range: -20 - 20 Default: 1.0  
Range: -20 - 20 Default: 0.1  
Range: -20 - 20 Default: 0.0  
Range: 0 - 100 Default: 5.0  
XX  
XX  
XXX  
* Sizes 010-020 and 035-045, default is 1596. Sizes 025,030, and 050-060, default is 2500.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 10 — Configuration Mode and Sub-Mode Directory (cont)  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
RSET  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
RESET COOL TEMP  
COOLING RESET TYPE  
CRST  
X
Default: No Reset  
0 = No Reset  
ENTER  
1 = 4 to 20 mA Input  
2 = Outdoor Air Temperature  
3 = Return Fluid  
4 = Space Temperature  
Default: 0.0F  
MA.DG  
RM.NO  
RM.F  
XX.X F  
XXX.X F  
XXX.X F  
XX.X F  
4-20 - DEGREES RESET  
REMOTE - NO RESET TEMP  
REMOTE - FULL RESET TEMP  
REMOTE - DEGREES RESET  
RETURN - NO RESET TEMP  
RETURN - FULL RESET TEMP  
Range: –30 to 30F  
Default: 125F (51.7C)  
Range: 0° to 125F  
Default: 0.0F (-17.8C)  
Range: 0to 125F  
Default: 0.0F  
Range: –30 to 30F  
RM.DG  
RT.NO  
RT.F  
Default: 10.0F (5.6C)  
Range: 0to 125F COOLER T  
XXX.X F  
XXX.X F  
Default: 0.0F (0.0C)  
Range: 0to 125F COOLER T  
Default: 0.0F  
RT.DG  
DMDC  
XX.X F  
RETURN - DEGREES RESET  
DEMAND LIMIT SELECT  
Range: –30 to 30F (–34.4 to -1.1 C)  
X
Default: None  
0 = None  
1 = Switch  
2 = 4 to 20 mA Input  
3 = CCN Loadshed  
Default: 100%  
DM20  
SHNM  
SHDL  
SHTM  
DLS1  
DLS2  
LLEN  
MSSL  
SLVA  
XXX %  
XXX  
DEMAND LIMIT AT 20 MA  
LOADSHED GROUP NUMBER  
LOADSHED DEMAND DELTA  
MAXIMUM LOADSHED TIME  
DEMAND LIMIT SWITCH 1  
DEMAND LIMIT SWITCH 2  
LEAD/LAG CHILLER ENABLE  
MASTER/SLAVE SELECT  
SLAVE ADDRESS  
Range: 0 to 100%  
Default: 0  
Range: 0 to 99  
Default: 0%  
Range: 0 to 60%  
XXX %  
XXX  
Default: 60 minutes  
Range: 0 to 120 minutes  
Default: 80%  
Range: 0 to 100%  
XXX %  
XXX %  
ENBL/DSBL  
SLVE/MAST  
XXX  
Default: 50%  
Range: 0 to 100%  
Default: Disable  
Default: Master  
Default: 0  
Range: 0 to 239  
ENTER  
Default: Master Leads  
0 = Master Leads  
1 = Slave Leads  
2 = Automatic  
LLBL  
X
LEAD/LAG BALANCE SELECT  
Default: 168 hours  
LLBD  
LLDY  
PARA  
XXX  
XXX  
YES  
LEAD/LAG BALANCE DELTA  
LAG START DELAY  
Range: 40 to 400 hours  
Default: 5 minutes  
Range: 0 to 30 minutes  
PARALLEL CONFIGURATION  
Default: YES (CANNOT BE CHANGED)  
SLCT  
SETPOINT AND RAMP LOAD  
COOLING SETPOINT SELECT  
CLSP  
X
Default: Single  
0 = Single  
1 = Dual Switch  
2 = Dual CCN Occupied  
3 = 4 to 20 mA Input (requires  
EMM)  
ENTER  
RL.S  
CRMP  
SCHD  
Z.GN  
ENBL/DSBL  
RAMP LOAD SELECT  
COOLING RAMP LOADING  
SCHEDULE NUMBER  
Default: Enable  
Default: 1.0  
Range: 0.2 to 2.0  
X.X  
XX  
Default: 1  
Range: 1 to 99  
Default: 1.0  
Range: 1.0 to 4.0  
X.X  
DEADBAND MULTIPLIER  
SERV  
SERVICE CONFIGURATION  
ENABLE COMPRESSOR A1  
ENTER  
EN.A1  
EN.A2  
EN.B1  
EN.B2  
ENBL/DSBL  
ENBL/DSBL  
ENBL/DSBL  
ENBL/DSBL  
Unit dependent  
Unit dependent  
Unit dependent  
Unit dependent  
ENABLE COMPRESSOR A2  
ENABLE COMPRESSOR B1  
ENABLE COMPRESSOR B2  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 10 — Configuration Mode and Sub-Mode Directory (cont)  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
BCST  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
BROADCAST CONFIGURATION  
ENTER  
T.D.BC  
OAT.B  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
CCN TIME/DATE BROADCAST  
CCN OAT BROADCAST  
G.S.BC  
BC.AK  
GLOBAL SCHEDULE BROADCAST  
CCN BROADCAST ACK’ER  
Table 11 — Time Clock Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
TIME  
ITEM  
DISPLAY  
SUB-ITEM  
DISPLAY  
COMMENT  
EXPANSION  
TIME OF DAY  
ENTER  
HH.MM  
XX.XX  
HOUR AND MINUTE  
Military (00:00 – 23:59)  
DATE  
MONTH,DATE,DAY AND YEAR  
MONTH OF YEAR  
ENTER  
MNTH  
DOM  
DAY  
XX  
XX  
1-12 (1 = January, 2 = February, etc)  
Range: 01-31  
DAY OF MONTH  
DAY OF WEEK  
X
1-7 (1 = Sunday, 2 = Monday, etc)  
YEAR  
XXXX  
YEAR OF CENTURY  
DST  
DAYLIGHT SAVINGS TIME  
MONTH  
ENTER  
STR.M  
STR.W  
STR.D  
MIN.A  
STP.M  
STP.W  
STP.D  
MIN.S  
XX  
X
Default: 4, Range 1 – 12  
Default: 1, Range 1 – 5  
Default: 7, Range 1 – 7  
Default: 60, Range 0 – 99  
Default: 10, Range 1 – 12  
Default: 5, Range 1 – 5  
Default: 7, Range 1 – 7  
Default: 60, Range 0 – 99  
WEEK  
DAY  
X
XX  
XX  
XX  
XX  
XX  
MINUTES TO ADD  
MONTH  
WEEK  
DAY  
MINUTES TO SUBTRACT  
HOL.L  
LOCAL HOLIDAY SCHEDULES  
HOLIDAY START MONTH  
HD.01 through HD.30  
Range 0 – 12  
ENTER  
MON  
DAY  
LEN  
XX  
XX  
START DAY  
Range 0 – 31  
XX  
XX  
DURATION (DAYS)  
Range 0 - 99  
SCH.N  
SCH.L  
SCHEDULE NUMBER  
Default: 1, Range 1 – 99  
LOCAL OCCUPANCY SCHEDULE  
ENTER  
ENTER  
PER.1  
OCCUPANCY PERIOD 1*  
PERIOD OCCUPIED TIME  
PERIOD UNOCCUPIED TIME  
MONDAY IN PERIOD  
OCC.1  
UNC.1  
MON.1  
TUE.1  
WED.1  
THU.1  
FRI.1  
XX:XX  
XX.XX  
Military (00:00 – 23:59)  
Military (00:00 – 23:59)  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
TUESDAY IN PERIOD  
WEDNESDAY IN PERIOD  
THURSDAY IN PERIOD  
FRIDAY IN PERIOD  
SAT.1  
SATURDAY IN PERIOD  
SUNDAY IN PERIOD  
SUN.1  
HOL.1  
HOLIDAY IN PERIOD  
* Repeats for Occupancy Periods 2 through 8.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 11 — Time Clock Mode and Sub-Mode Directory (cont)  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
OVR  
ITEM  
DISPLAY  
SUB-ITEM  
DISPLAY  
COMMENT  
EXPANSION  
SCHEDULE OVERRIDE  
ENTER  
OVR.T  
OVR.L  
T.OVR  
X
X
TIMED OVERRIDE HOURS  
OVERRIDE TIME LIMIT  
TIMED OVERRIDE  
Default: 0, Range 0-4 hours  
Default: 0, Range 0-4 hours  
User Entry  
YES/NO  
Table 12 — Operating Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
MODE  
ITEM  
DISPLAY  
COMMENT  
EXPANSION  
MODES CONTROLLING UNIT  
ENTER  
MD01  
MD02  
MD03  
MD05  
MD06  
MD07  
MD08  
MD09  
MD10  
MD13  
MD14  
MD15  
MD16  
MD17  
MD18  
MD19  
MD20  
MD21  
MD22  
MD23  
MD24  
MD25  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
CSM CONTROLLING CHILLER  
WSM CONTROLLING CHILLER  
MASTER/SLAVE CONTROL  
RAMP LOAD LIMITED  
TIMED OVERRIDE IN EFFECT  
LOW COOLER SUCTION TEMPA  
LOW COOLER SUCTION TEMPB  
SLOW CHANGE OVERRIDE  
MINIMUM OFF TIME ACTIVE  
DUAL SETPOINT  
TEMPERATURE RESET  
DEMAND/SOUND LIMITED  
COOLER FREEZE PROTECTION  
LOW TEMPERATURE COOLING  
HIGH TEMPERATURE COOLING  
MAKING ICE  
STORING ICE  
HIGH SCT CIRCUIT A  
HIGH SCT CIRCUIT B  
MINIMUM COMP ON TIME  
PUMP OFF DELAY TIME  
LOW SOUND MODE  
LEGEND  
CSM  
SCT  
WSM  
Chillervisor System Manager  
Saturated Condensing Temperature  
Water System Manager  
Table 13 — Alarms Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
CRNT  
ITEM  
COMMENT  
EXPANSION  
Alarms are shown as AXXX.  
Alerts are shown as TXXX.  
ENTER  
ENTER  
ENTER  
AXXX OR TXXX  
YES/NO  
CURRENTLY ACTIVE ALARMS  
RESET ALL CURRENT ALARMS  
ALARM HISTORY  
RCRN  
HIST  
Alarms are shown as AXXX.  
Alerts are shown as TXXX.  
AXXX OR TXXX  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 14 — Operating Modes  
MODE  
NO.  
ITEM EXPANSION  
DESCRIPTION  
01  
02  
03  
CSM CONTROLLING CHILLER  
WSM CONTROLLING CHILLER  
MASTER/SLAVE CONTROL  
RAMP LOAD LIMITED  
Chillervisor System Manager (CSM) is controlling the chiller.  
Water System Manager (WSM) is controlling the chiller.  
Dual Chiller control is enabled.  
Rampload(pull-down)limitingineffect.Inthismode,therateatwhichleavingfluidtemperature  
isdroppedislimitedtoapredeterminedvaluetopreventcompressoroverloading.SeeCooling  
Ramp Loading (ConfigurationSLCTCRMP). The pull-down limit can be modified, if  
desired, to any rate from 0.2° F to 2° F (0.1° to 1° C)/minute.  
05  
06  
TIMED OVERRIDE IN EFFECT  
LOW COOLER SUCTION TEMPA  
Timed override is in effect. This is a 1 to 4 hour temporary override of the programmed  
schedule, forcing unit to Occupied mode. Override can be implemented with unit under  
Local (Enable) or CCN (Carrier Comfort Network®) control. Override expires after each use.  
Circuit A cooler Freeze Protection mode. At least one compressor must be on, and the Sat-  
urated Suction Temperature is not increasing greater than 1.1° F (0.6° C) in 10 seconds. If  
the saturated suction temperature is less than the Brine Freeze Point (Set PointsFRZ  
BR.FZ) minus 6° F (3.4° C) and less than the leaving fluid temperature minus 14° F  
(7.8° C) for 2 minutes, a stage of capacity will be removed from the circuit. Or, If the satu-  
rated suction temperature is less than the Brine Freeze Point minus 14° F (7.8° C), for  
90 seconds, a stage of capacity will be removed from the circuit. The control will continue to  
decrease capacity as long as either condition exists.  
07  
08  
LOW COOLER SUCTION TEMPB  
SLOW CHANGE OVERRIDE  
Circuit B cooler Freeze Protection mode. At least one compressor must be on, and the Sat-  
urated Suction Temperature is not increasing greater than 1.1° F (0.6° C) in 10 seconds. If  
the saturated suction temperature is less than the Brine Freeze Point (Set PointsFRZ  
BR.FZ) minus 6° F (3.4° C) and less than the leaving fluid temperature minus 14° F  
(7.8° C) for 2 minutes, a stage of capacity will be removed from the circuit. Or, If the satu-  
rated suction temperature is less than the Brine Freeze Point minus 14° F (7.8° C), for  
90 seconds, a stage of capacity will be removed from the circuit. The control will continue to  
decrease capacity as long as either condition exists.  
Slow change override is in effect. The leaving fluid temperature is close to and moving  
towards the control point.  
09  
10  
MINIMUM OFF TIME ACTIVE  
DUAL SETPOINT  
Chiller is being held off by Minutes Off Time (ConfigurationOPT2DELY).  
Dual Set Point mode is in effect. Chiller controls to Cooling Set Point 1 (Set PointsCOOL  
CSP.1) during occupied periods and Cooling Set Point 2 (Set PointsCOOLCSP.2)  
during unoccupied periods.  
13  
TEMPERATURE RESET  
Temperature reset is in effect. In this mode, chiller is using temperature reset to adjust leav-  
ing fluid set point upward and is currently controlling to the modified set point. The set point  
can be modified based on return fluid, outdoor-air-temperature, space temperature, or 4 to  
20 mA signal.  
14  
DEMAND/SOUND LIMITED  
Demand limit is in effect. This indicates that the capacity of the chiller is being limited by  
demand limit control option. Because of this limitation, the chiller may not be able to pro-  
duce the desired leaving fluid temperature. Demand limit can be controlled by switch inputs  
or a 4 to 20 mA signal.  
15  
COOLER FREEZE PROTECTION  
LOW TEMPERATURE COOLING  
HIGH TEMPERATURE COOLING  
Cooler fluid temperatures are approaching the Freeze point (see Alarms and Alerts section  
for definition). The chiller will be shut down when either fluid temperature falls below the  
Freeze point.  
16  
17  
18  
Chiller is in Cooling mode and the rate of change of the leaving fluid is negative and  
decreasing faster than -0.5° F per minute. Error between leaving fluid and control point  
exceeds fixed amount. Control will automatically unload the chiller if necessary.  
Chiller is in Cooling mode and the rate of change of the leaving fluid is positive and increasing.  
Error between leaving fluid and control point exceeds fixed amount. Control will automatically  
load the chiller if necessary to better match the increasing load.  
MAKING ICE  
STORING ICE  
Chiller is in an unoccupied mode and is using Cooling Set Point 3 (Set PointsCOOL  
19  
20  
CSP.3) to make ice. The ice done input to the Energy Management Module (EMM) is open.  
ChillerisinanunoccupiedmodeandiscontrollingtoCoolingSetPoint2(SetPointsCOOL  
CSP.2). The ice done input to the Energy Management Module (EMM) is closed.  
HIGH SCT CIRCUIT A  
Chiller is in a Cooling mode and the Saturated Condensing Temperature (SCT) is greater than  
the calculated maximum limit. No additional stages of capacity will be added. Chiller capacity  
may be reduced if SCT continues to rise to avoid high-pressure switch trips by reducing con-  
densing temperature.  
21  
HIGH SCT CIRCUIT B  
Chiller is in a Cooling mode and the Saturated Condensing Temperature (SCT) is greater than  
the calculated maximum limit. No additional stages of capacity will be added. Chiller capacity  
may be reduced if SCT continues to rise to avoid high-pressure switch trips by reducing con-  
densing temperature.  
22  
23  
MINIMUM COMP ON TIME  
PUMP OFF DELAY TIME  
LOW SOUND MODE  
Cooling load may be satisfied, however control continues to operate compressor to ensure  
proper oil return. May be an indication of oversized application, low fluid flow rate or low loop  
volume.  
Cooling load is satisfied, however cooler pump continues to run for the number of minutes set  
by the configuration variable Cooler Pump Shutdown Delay (ConfigurationOPT1  
PM.DY).  
Chiller operates at higher condensing temperature and/or reduced capacity to minimize  
overall unit noise during evening/night hours (ConfigurationOPT2LS.MD).  
24  
25  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
set to ‘On’ for these boards. The auxiliary board (AUX) has an  
8-position DIP switch. Switches 2, 5, and 7 are set to ‘On.’  
CONTROLS  
General — The 30RAP air-cooled scroll chillers contain  
the ComfortLink™ electronic control system that controls and  
monitors all operations of the chiller.  
The control system is composed of several components as  
listed in the sections below. See Fig. 3-5 for typical control box  
drawings. See Fig. 6 and 7 for control schematics.  
Control Module Communication  
RED LED — Proper operation of the control boards can be  
visually checked by looking at the red status LEDs  
(light-emitting diodes). When operating correctly, the red status  
LEDs should be blinking in unison at a rate of once every  
2 seconds. If the red LEDs are not blinking in unison, verify  
that correct power is being supplied to all modules. Be sure that  
the main base board (MBB) is supplied with the current soft-  
ware. If necessary, reload current software. If the problem still  
persists, replace the MBB. A red LED that is lit continuously or  
blinking at a rate of once per second or faster indicates that the  
board should be replaced.  
GREEN LED — The MBB has one green LED. The Local  
Equipment Network (LEN) LED should always be blinking  
whenever power is on. All other boards have a LEN LED  
which should be blinking whenever power is on. Check LEN  
connections for potential communication errors at the board J3  
and/or J4 connectors. Communication between modules is  
accomplished by a 3-wire sensor bus. These 3 wires run in  
parallel from module to module. The J4 connector on the MBB  
provides both power and communication directly to the  
marquee display only.  
Main Base Board (MBB) — See Fig. 8. The MBB is  
the heart of the ComfortLink control system. It contains the  
major portion of operating software and controls the operation  
of the machine. The MBB continuously monitors input/output  
channel information received from its inputs and from all other  
modules. The MBB receives inputs from the discharge and  
suction pressure transducers and thermistors. See Table 15. The  
MBB also receives the feedback inputs from each compressor  
current sensor board and other status switches. See Table 16.  
The MBB also controls several outputs. Relay outputs con-  
trolled by the MBB are shown in Table 17. Information is  
transmitted between modules via a 3-wire communication bus  
or LEN (Local Equipment Network). The CCN (Carrier Com-  
fort Network) bus is also supported. Connections to both LEN  
and CCN buses are made at the LVT (low voltage terminal).  
See Fig. 8.  
Energy Management Module (EMM) — The EMM  
module is available as a factory-installed option or as a field-  
installed accessory. The EMM module receives 4 to 20 mA  
inputs for the leaving fluid temperature reset, cooling set point  
and demand limit functions. The EMM module also receives  
the switch inputs for the field-installed 2-stage demand limit  
and ice done functions. The EMM module communicates the  
status of all inputs with the MBB, and the MBB adjusts the  
control point, capacity limit, and other functions according to  
the inputs received.  
YELLOW LED — The MBB has one yellow LED. The  
Carrier Comfort Network (CCN) LED will blink during times  
of network communication.  
Carrier Comfort Network® (CCN) Interface —  
The 30RAP chiller units can be connected to the CCN if  
desired. The communication bus wiring is a shielded,  
3-conductor cable with drain wire and is supplied and installed  
in the field. See Table 18. The system elements are connected  
to the communication bus in a daisy chain arrangement. The  
positive pin of each system element communication connector  
must be wired to the positive pins of the system elements on  
either side of it. This is also required for the negative and  
signal ground pins of each system element. Wiring connections  
for CCN should be made at LVT. Consult the CCN Contrac-  
tor’s Manual for further information.  
NOTE: Conductors and drain wire must be 20 AWG (Ameri-  
can Wire Gage) minimum stranded, tinned copper. Individual  
conductors must be insulated with PVC, PVC/nylon, vinyl,  
Teflon, or polyethylene. An aluminum/polyester 100% foil  
shield and an outer jacket of PVC, PVC/nylon, chrome vinyl,  
or Teflon with a minimum operating temperature range of  
–20 C to 60 C is required. Wire manufactured by Alpha (2413  
or 5463), American (A22503), Belden (8772), or Columbia  
(02525) meets the above mentioned requirements.  
It is important when connecting to a CCN communication  
bus that a color coding scheme be used for the entire network  
to simplify the installation. It is recommended that red be used  
for the signal positive, black for the signal negative, and white  
for the signal ground. Use a similar scheme for cables contain-  
ing different colored wires.  
At each system element, the shields of its communication  
bus cables must be tied together. If the communication bus is  
entirely within one building, the resulting continuous shield  
must be connected to a ground at one point only. If the commu-  
nication bus cable exits from one building and enters another,  
the shields must be connected to grounds at the lightning  
suppressor in each building where the cable enters or exits the  
building (one point per building only). To connect the unit to  
the network:  
Current Sensor Board (CSB) — The CSB is used to  
monitor the status of the compressors by measuring current and  
providing an analog input to the main base board (MBB) or  
compressor expansion module (CXB).  
AUX Board (AUX) — The AUX is used with the digital  
scroll option and the low ambient head pressure option. It pro-  
vides additional inputs and outputs for digital scroll control  
along with analog outputs to control head pressure control fan  
speeds.  
Expansion Valve Board (EXV) — The EXV board  
communicates with the MBB and directly controls the expan-  
sion valves to maintain the correct compressor superheat.  
Enable/Off/Remote Contact Switch — The Enable/  
Off/Remote Contact switch is a 3-position switch used to  
control the chiller. When switched to the Enable position the  
chiller is under its own control. Move the switch to the Off  
position to shut the chiller down. Move the switch to the  
Remote Contact position and a field-installed dry contact can  
be used to start the chiller. The contacts must be capable of  
handling a 24 vac, 50-mA load. In the Enable and Remote  
Contact (dry contacts closed) positions, the chiller is allowed to  
operate and respond to the scheduling configuration, CCN  
configuration and set point data. See Fig. 9.  
Emergency On/Off Switch — The Emergency On/Off  
switch should only be used when it is required to shut the  
chiller off immediately. Power to the MBB, EMM, and  
marquee display is interrupted when this switch is off and all  
outputs from these modules will be turned off.  
1. Turn off power to the control box.  
Board Addresses — The main base board (MBB) has a  
3-position instance jumper that must be set to ‘1.’ The elec-  
tronic expansion valve board (EXV) and energy management  
board (EMM) have 4-position DIP switches. All switches are  
2. Cut the CCN wire and strip the ends of the red (+), white  
(ground), and black (–) conductors. (Substitute appropri-  
ate colors for different colored cables.)  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Connect the red wire to (+) terminal on LVT of the plug,  
the white wire to COM terminal, and the black wire to the  
(–) terminal.  
4. The RJ14 CCN connector on LVT can also be used, but is  
only intended for temporary connection (for example, a  
laptop computer running Service Tool).  
Table 18 — CCN Communication Bus Wiring  
PART NO.  
MANUFACTURER  
Regular Wiring  
1895  
Plenum Wiring  
Alpha  
American  
Belden  
Columbia  
Manhattan  
Quabik  
A48301  
884421  
M64430  
A21451  
8205  
D6451  
M13402  
6130  
IMPORTANT: A shorted CCN bus cable will prevent some  
routines from running and may prevent the unit from start-  
ing. If abnormal conditions occur, unplug the connector. If  
conditions return to normal, check the CCN connector and  
cable. Run new cable if necessary. A short in one section of  
the bus can cause problems with all system elements on the  
bus.  
Sensors — The electronic control uses 4 to 7 thermistors to  
sense temperatures for controlling chiller operation. See  
Table 15. These sensors are outlined below. Thermistors RG-  
TA, RGTB, EWT, LWT, and OAT are identical in temperature  
versus resistance and voltage drop performance. The dual chill-  
er thermistor is 5 kat 77 F (25 C)thermistor. Space tempera-  
ture thermistor is a 10 kat 77 F (25 C). The DTT thermistor  
is an 86 kat 77 F (25 C)thermistor. See Thermistors section  
for temperature-resistance-voltage drop characteristics.  
COOLER LEAVING FLUID SENSOR — The thermistor is  
installed in a well in the factory-installed leaving fluid piping  
coming from the bottom of the brazed-plate heat exchanger.  
COOLER ENTERING FLUID SENSOR The thermistor is  
installed in a well in the factory-installed entering fluid piping  
coming from the top of the brazed-plate heat exchanger.  
COMPRESSOR RETURN GAS TEMPERATURE SEN-  
SOR — These thermistors are installed in a well located in the  
suction line of each circuit.  
OUTDOOR-AIR TEMPERATURE SENSOR (OAT) —  
This sensor is factory installed on a bracket which is inserted  
through the base pan of the unit.  
Table 15 — Thermistor Designations  
PIN  
THERMISTOR CONNECTION  
POINT  
THERMISTOR INPUT  
LWT  
EWT  
J8-13,14 (MBB) Cooler Leaving Fluid  
J8-11,12 (MBB) Cooler Entering Fluid  
J8-1,2 (MBB)  
J8-3,4 (MBB)  
J8-7,8 (MBB)  
Circuit A Return Gas  
Temperature  
Circuit B (035-060 only)  
Return Gas Temperature  
Outdoor-Air Temperature  
Sensor  
RGTA  
RGTB  
OAT  
J8-5,6 (MBB)  
TB5-5,6  
Accessory Remote Space  
Temperature Sensor or  
Dual LWT Sensor  
Discharge Temperature  
Thermistor  
SPT  
DTT  
J6-1,2 (AUX)  
LEGEND  
DISCHARGE  
TEMPERATURE  
THERMISTOR  
LWT — Leaving Water Temperature  
MBB — Main Base Board  
(DTT) — This sensor is only used on units with a digital  
compressor. The sensor is mounted on the discharge line close  
to the discharge of the digital compressor. It attaches to the dis-  
charge line using a spring clip and protects the system from  
high discharge gas temperature when the digital compressor is  
used. This sensor is a connected to the AUX board.  
Table 16 — Status Inputs  
STATUS SWITCH  
Chilled Water Pump 1  
Chilled Water Pump 2  
Remote On/Off  
Cooler Flow Switch  
PIN CONNECTION POINT  
J7-1,2  
J7-3,4  
LVT-13,14  
J7-9,10  
J9-11,12  
J9-5,6  
REMOTE SPACE TEMPERATURE SENSOR OR DUAL  
LEAVING WATER TEMPERATURE SENSOR — One of  
two inputs can be connected to the LVT. See appropriate sen-  
sor below.  
Remote Space Temperature Sensor — Sensor (part no.  
33ZCT55SPT) is an accessory sensor that is remotely mounted  
in the controlled space and used for space temperature reset.  
The sensor should be installed as a wall-mounted thermostat  
would be (in the conditioned space where it will not be sub-  
jected to either a cooling or heating source or direct exposure  
to sunlight, and 4 to 5 ft above the floor).  
Space temperature sensor wires are to be connected to  
terminals in the unit main control box. The space temperature  
sensor includes a terminal block (SEN) and a RJ11 female  
connector. The RJ11 connector is used access into the Carrier  
Comfort Network® (CCN) at the sensor.  
Compressor Fault Signal, A1  
Compressor Fault Signal, A2  
Compressor Fault Signal, B1  
Compressor Fault Signal, B2  
J9-8,9  
J9-2,3  
Table 17 — Output Relays  
RELAY  
NO.  
DESCRIPTION  
Energize Compressor A1 (010-030)  
Energize Compressor A1 and Condenser Fan Contac-  
tor 3 (055,060)  
K1  
K2  
K3  
K4  
Energize Compressor A2 (all but 010, 015 60 Hz)  
Energize Chilled Water Pump 1 Output  
Energize Chilled Water Pump 2 Output  
To connect the space temperature sensor (Fig. 10):  
Energize Compressor B1 (035-050)  
Energize Compressor B1 and Condenser Fan Contac-  
tor 3 (055,060)  
Energize Compressor B2 (035-060)  
Alarm Relay  
1. Using a 20 AWG twisted pair conductor cable rated for  
the application, connect 1 wire of the twisted pair to one  
SEN terminal and connect the other wire to the other  
SEN terminal located under the cover of the space  
temperature sensor.  
2. Connect the other ends of the wires to terminals 5 and 6  
on TB5 located in the unit control box.  
K5  
K6  
K7  
K8  
K9  
K10  
K11  
Cooler/Pump Heater  
Energize Condenser Fan Contactor 1 (018-060)  
Energize Condenser Fan Contactor 2 (018-060)  
Minimum Load Valve  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Units on the CCN can be monitored from the space at the  
sensor through the RJ11 connector, if desired. To wire the RJ11  
connector into the CCN (Fig. 11):  
3. Insert and secure the white (ground) wire to terminal 4 of  
the space temperature sensor.  
4. Insert and secure the black (–) wire to terminal 2 of the  
space temperature sensor.  
5. Connect the other end of the communication bus cable to  
the remainder of the CCN communication bus.  
Dual Leaving Water Temperature Sensor — For dual chiller  
applications (parallel only are supported), connect the dual  
chiller leaving fluid temperature sensor (refer to Configuring  
and Operating Dual Chiller Control section on page 36) to the  
space temperature input of the Master chiller. If space tempera-  
ture is required for reset applications, connect the sensor to the  
Slave chiller and configure the slave chiller to broadcast the  
value to the Master chiller.  
IMPORTANT: The cable selected for the RJ11 connector  
wiring MUST be identical to the CCN communication bus  
wire used for the entire network. Refer to Table 18 for  
acceptable wiring.  
1. Cut the CCN wire and strip ends of the red (+), white  
(ground), and black (–) conductors. (If another wire color  
scheme is used, strip ends of appropriate wires.)  
2. Insert and secure the red (+) wire to terminal 5 of the  
space temperature sensor terminal block.  
LEGEND FOR FIG. 3-7  
ALMR  
AUX  
BR  
Alarm Relay  
Auxilliary  
Boiler Relay  
C
Contactor, Compressor  
Circuit Breaker  
CB  
CCB  
CH  
Compressor Circuit Breaker  
Crankcase Heater  
CHC  
COMP  
CSB  
CWFS  
CWP  
DGS  
DPT  
DTT  
DUS  
EMM  
EXV  
FB  
Cooler/Pump Heater Contactor  
Compressor  
Current Sensor Board  
Chilled Water Flow Switch  
Chilled Water Pump  
Digital Scroll Compressor  
Discharge Pressure Transducer  
Discharge Temperature Thermistor  
Digital Unloader Solenoid  
Energy Management  
Electronic Expansion Valve  
Fuse Block  
FC  
Fan Contactor  
FCB  
FIOP  
FR  
Fan Circuit Breaker  
factory Installed Option  
Fan Relay  
GND  
HPS  
LON  
LVT  
Ground  
High-Pressure Switch  
Local Operating Network  
Low Voltage Terminal Block  
Main Base Board  
MBB  
MLV  
MM  
MP  
MS  
Minimum Load Valve  
Motormaster  
Motor Protector  
Manual Starter  
NEC  
OAT  
OFM  
RGT  
SCCR  
SPT  
SW  
National Electrical Code  
Outdoor-Air Thermistor  
Outdoor Fan Motor  
Return Gas Thermistor  
Short Circuit Current Rating  
Suction Pressure Transducer  
Switch  
TB  
Terminal Block  
TNKR  
TRAN  
UPC  
Storage Tank Heater Relay  
Transformer  
Unitary Protocol Converter  
Terminal Block  
Terminal (Unmarked)  
Terminal (Marked)  
Splice  
Factory Wiring  
Field Wiring  
Accessory or Option Wiring  
To indicate common potential only; not to represent wiring.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LOCATED OVER EMM AND EXV  
FB-1  
EMM  
EXV  
CHC  
TRAN  
CCB  
AUX  
CSB-A1  
UPC  
LON  
DISCONNECT  
OPTION/TB  
TB4  
TB1  
MS- MS-  
CWP1CWP2  
FAN  
1
CWP1 CWP2  
C-A1  
MM  
MBB  
A1  
COMPRESSOR  
CONTROL BOX  
a30-4962  
Fig. 3 — Typical Control Box for 30RAP010,015  
FB-1  
EXV  
EMM  
CHC  
TRAN  
CCB-2  
CCB-1  
FB-3  
AUX  
LON  
CSB-A1  
CSB-A2  
TB1  
TB4  
UPC  
DISCONNECT  
OPTION/TB  
MS- MS-  
CWP1 CWP2  
C-A1  
FC2  
C-A2  
CWP1 CWP2  
MBB  
FC1/MM  
Fig. 4 — Typical Control Box for 30RAP018-030  
a30-4963  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
a30-4964  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STANDARD  
TERMINAL  
BLOCK  
OPTIONAL  
DISCONNECT  
CH-A1  
BLU  
BLK  
380V,460V,575V  
ONLY  
CB1A  
TB1A  
CCB-1  
CA1  
CSB-A1  
1
BLK  
BLK  
BLK  
11  
21  
22  
23  
11  
21  
BLK  
YEL  
BLU  
T1  
T2  
BLK  
YEL  
BLU  
BLK  
11  
21  
22  
1
2
3
12  
13  
YEL  
12  
22  
23  
COMP A1  
GRN/YEL  
BLU  
YEL  
13  
T3  
YEL  
YEL  
YEL  
YEL  
12  
13  
2
3
CH-A2  
BLK BLU  
BLU BLK  
BLU  
BLK  
CCB-2  
BLU  
BLU  
BLU  
CA2  
CSB-A2  
1
23  
11  
12  
13  
21  
22  
23  
BLK  
YEL  
BLU  
11  
12  
13  
21  
BLK  
YEL  
T1  
BLK  
YEL  
BLU  
2
3
COMP A2  
GRN/YEL  
22  
23  
T2  
BLU  
T3  
EQUIP GND  
208/230V ONLY  
FU5  
FU6  
BLK  
CHILLED WATER PUMP FIOP  
CWP1  
MS-CWP1  
L1  
RED  
1
1
HF  
BLK  
YEL  
BLU  
T1  
T2  
T3  
L1  
L2  
L3  
T1  
T2  
T3  
BLK  
BLK  
BLK  
L1  
L2  
L3  
CWP1  
WATER  
PUMP  
H4  
H3  
H2  
L2  
L3  
H1  
~
TRAN3  
WHT  
GRN/YEL  
SECONDARY  
115V  
MS-CWP2  
L1  
CWP2  
X3  
X1  
FU4  
BLK  
BLK  
BLK  
BLK  
YEL  
BLU  
T1  
T2  
T3  
L1  
L2  
L3  
T1  
T2  
T3  
L1  
L2  
L3  
GRN/YEL  
XF  
CWP2  
WATER  
PUMP  
L2  
L3  
2
BLK  
GFI-CO  
GRN/YEL  
2
FIOP/ACCESSORY  
LINE  
BRASS SCREW  
FB3  
FB1  
SILVER SCREW  
RESET  
TEST  
TERMINAL  
CONNECTIONS  
FOR PRIMARY SIDE  
TERMINAL  
CONNECTIONS FOR  
SECONDARY SIDE  
FC1  
21  
1
2
3
VOLTAGE  
SERIES  
100  
11  
12  
13  
21  
22  
23  
11  
12  
13  
21  
11  
BLK-1  
BLK-2  
BLK-3  
BLK  
YEL  
BLU  
BLK  
YEL  
BLU  
BLK  
575-3-60  
H1-H2  
H2-H4  
H3-H4  
H1-H4  
XF-X2  
XF-X2  
XF-X2  
XF-X2  
22  
23  
OFM1  
GRN/YEL  
YEL  
BLU  
12  
13  
22  
23  
230-3-60  
208-3-60  
460-3-60  
400,500  
500  
GRN-YEL  
LOAD  
600  
FC2  
HIGH SCCR  
ONLY  
1
2
3
11  
12  
13  
21  
22  
23  
BLK-1  
BLK-2  
BLK-3  
BLK  
YEL  
BLU  
OFM2  
FUSE  
NUMBER  
TRAN  
SIZE  
REPLACE  
WITH  
GRN/YEL  
UNIT VOLTAGE  
208/230-3-60  
380-3-60  
FNQ-R-3.5  
FNQ-R-2.5  
FNQ-R-2  
CHC  
CHC  
1
YEL  
FU1  
&
FU2  
200VA  
BLK  
4
2
6
BLK  
WHT  
BLK  
BLK  
460-3-60  
1
2
575-3-60  
FNQ-R-1.5  
BLK BLU  
380-3-60,460-3-60,575-3-60  
208/230-3-60  
3
2
FU3 (24V)  
200VA  
500VA  
500VA  
NONE  
FNM-10  
COOLER/PUMP  
COOLER/PUMP  
HEATERS  
(208/230,230V)  
HEATERS  
460-3-60,575-3-60  
208/230-3-60,230-3-60  
380-3-60,460-3-60,575-3-60  
208/230-3-60  
FNQ-R-2.5  
FNQ-R-3.5  
(380,460,575V)  
FU5  
&
FU6  
8
BLK  
WHT  
YEL  
FU4 (115V)  
FNM-6  
3
FB1  
(NO MM)  
FB1  
380-3-60,460-3-60,575-3-60  
208/230-3-60  
LP-CC-20  
380-3-60,460-3-60,575-3-60  
208/230-3-60  
KTK-R-15  
KTK-R-20  
NONE  
(WITH MM)  
380-3-60,460-3-60,575-3-60  
208/230-3-60  
FB2  
FB3  
NONE  
LP-CC-20  
LP-CC-20  
LOW AMBIENT OPERATION (MOTORMASTER V) FIOP/ACCESSORY  
380-3-60,460-3-60,575-3-60  
208/230-3-60  
NONE  
MM-A  
FB3  
FB1  
1
2
3
L1 T1  
11  
12  
13  
21  
22  
23  
11  
12  
13  
21  
22  
23  
BLK  
YEL  
BLU  
BLK-1  
BLK-2  
BLK-3  
BLK  
YEL  
BLU  
BLK  
YEL  
BLU  
L2 T2  
OFM1  
L3 T3  
GRN/YEL  
YEL  
HIGH SCCR  
ONLY  
2
MMR  
14  
*
MM SIGNAL CONNECTION  
VOLTAGE  
*1  
VIO 11  
TB  
1
HZ  
60  
60  
240  
1/4W  
208/230/460/575  
380  
RED  
25  
2
FROM  
13A  
AUX-J4  
BLK  
FB2  
FC2  
1
2
3
11  
12  
13  
21  
22  
23  
11  
12  
13  
21  
22  
23  
BLK-1  
BLK-2  
BLK-3  
BLK  
YEL  
BLU  
BLK  
YEL  
BLU  
OFM2  
GRN/YEL  
CHC  
CHC  
1
4
2
6
BLK  
WHT  
BLK  
BLK  
BLK  
1
2
3
2
COOLER/PUMP  
COOLER/PUMP  
HEATERS  
(208/230,230V)  
HEATERS  
(380,460,575V)  
8
BLK  
WHT  
YEL  
3
TABLE 1  
TERMINAL  
CONNECTIONS  
FOR PRIMARY SIDE  
VOLTAGE  
SERIES  
575-3-60  
380-3-60  
230-3-60  
208-3-60  
460-3-60  
100  
200  
500  
500  
600  
H1  
H1  
H2  
H3  
H1  
&
&
&
&
&
H2  
H2  
H4  
H4  
H4  
NOTES:  
8. IF CHILLED WATER PUMP INTERLOCK IS USED,  
REMOVE JUMPER FROM TERMINAL 11 TO 17 AND  
WIRE INTERLOCK CONTACT ACROSS TERMINALS 11 & 17.  
1. FACTORY WIRING IS IN ACCORDANCE WITH UL 1995 STANDARDS.  
ANY FIELD MODIFICATIONS OR ADDITIONS MUST BE IN  
COMPLIANCE WITH ALL APPLICABLE CODES.  
C MIN WIRE FOR FIELD POWER SUPPLY.  
9. MP-A1 NOT USED IN THE FOLLOWING UNITS:  
018,020: ALL UNITS  
025,030: 460V UNITS WITHOUT DIGITAL SCROLL  
3. ALL FIELD INTERLOCK CONTACTS MUST HAVE A MIN RATING OF  
2 AMPS @ 24VAC SEALED. SEE FIELD INTERLOCK WIRING.  
FU1  
FU2  
BLK  
10. MP-A2 NOT USED IN THE FOLLOWING UNITS:  
018-020: ALL UNITS  
025,030: 460V UNITS  
4. COMPRESSOR AND FAN MOTORS ARE THERMALLY PROTECTED--  
THREE PHASE MOTORS PROTECTED AGAINST PRIMARY SINGLE  
PHASE CONDITIONS.  
YEL  
CONNECT FOR  
APPROPRIATE  
PRIMARY VOLTAGE  
SEE TABLE 1  
11. JUMPER PLUG REQUIRED WHEN MP NOT USED  
5. TERMINALS 13& 14 OF LVT ARE FOR FIELD CONNECTION  
OF REMOTE ON-OFF. THE CONTACT MUST BE RATED FOR DRY  
CIRCUIT APPLICATION CAPABLE OF HANDLING A 5VDC  
1 MA TO 20 MA LOAD.  
TRAN1  
PRIMARY  
H3  
6. FOR 500 SERIES UNIT OPERATION AT 208-3-60V LINE VOLTAGE,  
TRAN1 PRIMARY CONNECTIONS MUST BE MOVED TO TERMINALS H3 & H4.  
H1  
X1  
H2  
H4  
7. FOR UNITS WITH LOW AMBIENT MOTOR MASTER V FIOP/ACCESSORY,  
FAN CONTACTOR FC1 IS REPLACED WITH MOTORMASTER RELAY MMR.  
TB4  
5
TB1  
C
SECONDARY 24V  
TB4  
7
RED XF  
X2  
BRN  
C
FU3  
RED  
BRN  
GRN/YEL  
TB1  
RED  
A1  
SW2  
C1  
BRN  
B1  
3
2
1
3
2
1
J1  
EXV  
J2  
3
2
1
3
2
1
UPC FIOP  
BRN  
RED  
VIO  
24VAC  
CB3  
3.2 AMPS  
BRN  
VIO  
2
1
GND  
HOT  
TB4  
6
UPC  
VIO  
FIOP/ACCESSORY  
J1  
DGS FIOP  
VIO  
3
2
1
3
2
1
3
2
1
3
2
1
J1  
MBB  
J2  
3
2
1
3
2
1
3
2
1
3
2
1
BRN  
RED  
12  
BRN  
RED  
BRN  
VIO  
2
1
AUX  
J1  
EMM  
J2  
11  
a30-4965  
BRN  
1
3
VIO  
BRN  
BLU  
BRN  
CWFS  
Fig. 6A — Typical Wiring Schematic, 30RAP018-030 Units — Power Wiring  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CB1  
3.2 AMPS  
TB4  
4
RED  
TB1  
TRAN1  
RED  
SEE NOTE  
9
A2  
B2  
CB2  
5.2 AMPS  
SW2  
C2  
RED  
BRN  
BRN  
BRN  
BRN  
BRN  
MBB J1-2  
UPC GND  
CWFS 3  
PL1-3  
RED  
PL1-4  
BRN  
TB4  
7
TB4  
5
RED  
RED  
BRN  
BRN  
SECONDARY 24V  
T2 MP-A1 T1  
SEE NOTE 10  
XF  
X1  
X2  
RED  
RED  
FU3  
BRN  
GRN/YEL  
ORN  
MBB  
ORN  
ORN  
PL1-7  
RED  
PL1-8  
BRN  
J10A  
1
2
3
4
5
6
7
8
9
1
2
3
4
5
EXV J1-2  
LVT J12-5  
T2 MP-A2 T1  
1
2
RED  
BLK  
BRN A2 CHC  
BRN A2 CA1  
C
RED  
RED  
GRA  
GRA  
BRN  
RLY 11  
GRA  
PNK  
ORN  
A2 CWP1  
3
BRN  
BRN  
MLV-A  
4
MLV ACCSY  
BRN  
5
6
PNK  
ORN  
A1 FC1 A2  
SEE NOTE 7  
A2 CA2  
A2 FC2  
BRN  
RLY 9  
BRN  
7
8
RLY 10  
9
A2 FC1  
A2 FC3  
A1 FC2 A2  
BRN  
BRN  
J10B  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
RLY 5  
RLY 6  
TB4  
RED  
RED  
4
MAX LOAD-5VA SEALED  
10VA INRUSH  
6
7
LVT  
J11  
LVT  
J12  
RED  
RED  
ALM  
R
1
18  
21  
5
C
RLY 7  
BRN  
BRN  
TB1  
ACCESSORY  
STORAGE TANK  
HEATER RELAY  
8
TNK  
R
9
RED  
ORN  
10  
ORN  
C
C
TB1  
TB1  
RLY 8  
RLY 1  
RLY 2  
RLY 3  
RLY 4  
ORN  
A1 CHC A2  
A1 CA1 A2  
A1 CA2 A2  
HPS-A  
11  
12  
BLK  
BLK  
BLK  
BLK  
PL1-1  
PL1-2  
VIO  
MP-A1  
ORN  
GRA  
VIO  
RED  
VIO  
VIO  
BRN  
BRN  
M1  
M1  
M2  
M2  
ORN  
GRA  
SEE NOTE 11  
PL1-5  
13  
14  
VIO  
A2 CA2  
A2 CA1  
PL1-6  
VIO  
MP-A2  
BRN  
15  
SEE NOTE 11  
VIO  
16  
17  
18  
LVT  
J12  
CWP  
1
VIO  
BRN  
C
TB1  
A1  
A1  
A2  
A2  
A2 CWP2  
A2 CWP1  
BRN  
BRN  
1
2
25  
24  
CWP  
2
RED  
FIOP OR  
FIELD INSTALLED  
OPTION  
SEE NOTES ON  
PAGE 24.  
LVT  
J12  
6
HEAT  
FIELD INSTALLED  
MAX LOAD-5VA SEALED  
10VA INRUSH  
6
5
4
3
2
1
20  
19  
GRA  
GRA  
6
5
4
3
2
1
7
J6  
HR  
ALMR  
VIO  
BRN  
BR  
HEAT/BOILER FIELD  
INSTALLED WIRING  
LVT  
J11  
2
CWFS  
4
2
10  
17  
BLK  
WHT  
10  
4
3
2
1
1
2
3
4
5
4
3
2
1
EXV  
1
2
3
4
5
1
3
4
RED  
BLK  
WHT  
RED  
1
2
3
4
CWPI  
SEE  
2
J3  
WHT  
J7  
3
J3  
J4  
BLK  
NOTE  
8
4
9
4
3
2
1
11  
11  
12  
13  
14  
9
ORN  
9
1
1
MARQUEE  
DISPLAY  
PL-EXVA  
BLK  
4
3
2
1
RED  
RED  
1
1
2
3
4
5
6
1
2
3
4
5
2
3
4
5
6
2
1
2
3
4
5
BLK  
BLK  
WHT  
RED  
WHT  
BLK  
2
3
4
5
6
WHT  
YEL  
J4  
3
WHT  
BLK  
EXV-A  
4
J6  
GRY  
5
GRN  
RED  
BRN  
BRN  
RED  
6
RED  
RED  
1
MAIN  
BASE  
BOARD  
1
2
RED  
2
3
1
2
3
1
2
3
1
2
3
1
2
CSB  
B2  
ORN  
3
PL50-1  
DUS  
7
8
8
7
3
BRN  
-
7
8
VIO  
RED  
4
13  
14  
RED  
8
7
AUX  
4
RED  
5
J2  
CH1  
6
5
4
3
2
1
BRN  
BLK  
CSB  
A2  
SW1  
ENABLE  
RED  
-
G
+
-
G
+
3
2
1
3
2
1
5
ORN  
PL50-2  
PL50-3  
A1  
B1  
6
6
BRN  
7
7
1
2
OFF  
RED  
DTT  
C1  
J9  
CH11  
-
REMOTE  
RED  
BLK  
RED  
BLK  
1
2
7
RED  
ON-OFF  
SWITCH  
(SEE NOTE  
5)  
8
CSB  
B1  
J9  
J6  
J4  
J5  
BLK  
WHT  
RED  
8
ORN  
9
PL50-4  
8
RED  
GRA  
GRA  
9
BRN  
DGS OR  
MM  
FIOP  
10  
RED  
11  
1
2
10  
11  
12  
CH9  
-
1
2
RED  
BLK  
CSB  
A1  
TO MM-A  
6
5
4
ORN  
12  
15  
16  
6
6
5
4
3
2
1
BRN  
ON  
J7  
1
2
OFF  
CH10  
-
1
2
5
1
RGTA  
1
DARK  
2
3
=
4
5
6
7
8
RED  
DUAL  
SETPOINT  
1
2
SWITCH LOCATION  
2
BLK  
3
4
RED  
14  
13  
CWP2  
RED  
3
LVT  
J12  
4
T55  
3
2
1
LVT  
J10  
5
5
BLU  
3
23  
22  
T-55  
SEN  
1
6
1
2
GRA  
GRA  
RED  
RED  
BLU  
BLU  
17  
16  
15  
14  
13  
12  
11  
1
2
3
4
5
6
ACCSY  
4
3
2
1
6
BLU  
4
2
4
3
2
1
EMM  
1
VIO  
14  
13  
CWP1  
VIO  
OAT  
3
ICE DONE  
DLS STEP  
DLS STEP  
7
RED  
BLK  
WHT  
RED  
3
SPACE TEMPERATURE  
ACCESSORY OR  
DUAL CHILLER LWT  
J3  
J4  
4
2
4
8
BLK  
5
1
3
4
5
9
6
6
7
2
LVT  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
7
8
1
EVAPORATOR ENTERING  
FLUID TEMP  
4
3
2
1
J7  
J6  
RED  
8
4
3
2
1
9
J13  
10  
9
2
9
BLK  
WHT  
RED  
BRN  
10  
9
BLK  
10  
11  
12  
13  
14  
1
2
3
4
5
6
7
8
BLK  
10  
11  
12  
13  
14  
3
RED  
EVAPORATOR LEAVING  
FLUID TEMP  
J8  
RED  
8
WHT  
RED  
BRN  
RED  
BLK  
WHT  
RED  
8
4
7
RED  
BLK  
BLK  
WHT  
RED  
7
6
1
2
3
4
5
6
6
WHT  
BLK  
5
J5  
5
10  
9
FIOP/  
ACCESSORY  
4
4
DEMAND  
LIMIT  
4-20mA  
7
8
+
-
3
1
BLK  
WHT  
RED  
3
1
2
8
2
2
2
J1  
VIO  
BRN  
7
1
3
1
3
6
4
UPC  
TEMP  
RESET  
4-20mA  
4
5
9
+
-
5
PORT  
2
5
ORN  
PNK  
4
7
B
RED  
BLK  
1
NET  
+
-
6
LON  
OPTION  
RED  
6
3
2
3
4
5
NET  
N/C  
N/C  
+
-
7
C
A
8
COOLING  
SETPOINT  
4-20mA  
J3 GND  
NET  
7
2
10  
+
-
DPTA  
GRN  
8
8
1
9
9
BLK  
J4  
1
9
WHT  
SIGNAL  
10  
B
C
A
10  
11  
12  
RED  
10  
11  
12  
PORT 1A  
2
+
-
11  
1
2
3
NET  
NET  
+
2
SPTA  
GRN  
12  
BLK  
SHIELD  
UPC OPT  
a30-4966  
Fig. 6B — Typical Wiring Schematic, 30RAP018-030 Units — Control Wiring  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STANDARD  
TERMINAL  
BLOCK  
CH-A1  
OPTIONAL  
DISCONNECT  
BLU  
BLK  
380V,460V,575V  
ONLY  
CCB-1  
CB1A  
CA1  
CSB-A1  
TB1A  
1
BLK  
BLK  
BLK  
BLK  
BLK  
11  
21  
22  
23  
11  
21  
BLK  
YEL  
BLU  
T1  
T2  
BLK  
YEL  
BLU  
BLK  
11  
21  
22  
2
3
1
12  
13  
YEL  
12  
22  
23  
COMP A1  
GRN/YEL  
BLU  
YEL  
13  
T3  
YEL  
YEL  
YEL  
YEL  
YEL  
YEL  
12  
13  
2
3
CH-A2  
BLK BLU  
BLU BLK  
BLU  
BLK  
CCB-2  
BLU  
BLU  
BLU  
BLU  
BLU  
CA2  
CSB-A2  
1
11  
12  
13  
21  
22  
23  
BLK  
YEL  
BLU  
11  
12  
13  
21  
BLK  
YEL  
T1  
23  
BLK  
YEL  
BLU  
2
3
COMP A2  
GRN/YEL  
22  
23  
T2  
BLU  
T3  
208/230V ONLY  
EQUIP GND  
CH-B1  
BLU  
BLK  
380V,460V,575V  
ONLY  
CSB-B1  
CCB-3  
CB1  
11  
FU5  
FU6  
BLK  
1
11  
12  
13  
21  
22  
23  
21  
BLK  
YEL  
BLU  
BLK  
YEL  
BLU  
BLK  
T1  
RED  
1
2
3
1
HF  
YEL  
12  
22  
23  
T2  
COMP B1  
GRN/YEL  
H4  
H3  
H2  
BLU  
YEL  
13  
H1  
T3  
~
TRAN3  
WHT  
CH-B2  
BLU BLK  
SECONDARY  
115V  
BLU  
BLK  
X3  
X1  
FU4  
GRN/YEL  
CCB-4  
XF  
CB2  
CSB-B2  
1
11  
12  
13  
21  
22  
23  
BLK  
YEL  
BLU  
11  
12  
13  
21  
BLK  
YEL  
T1  
2
BLK  
BLK  
YEL  
BLU  
GFI-CO  
2
3
COMP B2  
GRN/YEL  
22  
23  
T2  
2
FIOP/ACCESSORY  
BLU  
T3  
LINE  
208/230V ONLY  
BRASS SCREW  
SILVER SCREW  
RESET  
TEST  
TERMINAL  
CONNECTIONS  
FOR PRIMARY SIDE  
TERMINAL  
CONNECTIONS FOR  
SECONDARY SIDE  
CHILLED WATER PUMP FIOP  
CWP1  
VOLTAGE  
SERIES  
100  
MS-CWP1  
L1  
BLK  
BLK  
BLK  
BLK  
YEL  
BLU  
T1  
T2  
T3  
L1  
L2  
L3  
T1  
T2  
T3  
575-3-60  
H1-H2  
H2-H4  
H3-H4  
H1-H4  
XF-X2  
XF-X2  
XF-X2  
XF-X2  
L1  
L2  
L3  
230-3-60  
208-3-60  
460-3-60  
400,500  
500  
CWP1  
WATER  
PUMP  
GRN-YEL  
L2  
L3  
LOAD  
600  
GRN/YEL  
MS-CWP2  
L1  
CWP2  
BLK  
BLK  
BLK  
BLK  
YEL  
BLU  
T1  
T2  
T3  
L1  
L2  
L3  
T1  
T2  
T3  
L1  
L2  
L3  
CWP2  
WATER  
PUMP  
FUSE  
NUMBER  
TRAN  
SIZE  
REPLACE  
WITH  
L2  
L3  
UNIT VOLTAGE  
208/230-3-60  
380-3-60  
FNQ-R-3.5  
FNQ-R-2.5  
FNQ-R-2  
GRN/YEL  
FU1  
&
FU2  
200VA  
460-3-60  
575-3-60  
FNQ-R-1.5  
380-3-60,460-3-60,575-3-60  
208/230-3-60  
FU3 (24V)  
200VA  
500VA  
500VA  
NONE  
FNM-10  
FB3  
FB1  
460-3-60,575-3-60  
208/230-3-60,230-3-60  
380-3-60,460-3-60,575-3-60  
208/230-3-60  
FNQ-R-2.5  
FNQ-R-3.5  
FC1  
21  
FU5  
&
FU6  
1
2
3
11  
12  
13  
21  
22  
23  
11  
12  
13  
21  
BLK  
YEL  
BLU  
BLK  
YEL  
BLU  
BLK 11  
YEL  
BLK-1  
BLK-2  
BLK-3  
FU4 (115V)  
FNM-6  
22  
23  
OFM3  
GRN/YEL  
12  
22  
23  
FB1  
(NO MM)  
FB1  
380-3-60,460-3-60,575-3-60  
208/230-3-60  
LP-CC-20  
380-3-60,460-3-60,575-3-60  
208/230-3-60  
KTK-R-15  
KTK-R-20  
LP-CC-20  
BLU 13  
BLK  
NONE  
NONE  
NONE  
(WITH MM)  
FB2  
575-3-60  
HIGH SCCR  
ONLY  
CHC  
CHC  
380-3-60,460-3-60,575-3-60  
208/230-3-60  
FB3  
LP-CC-20  
4
2
6
BLK  
WHT  
COOLER/PUMP  
HEATERS  
BLK  
BLK  
1
3
2
3
COOLER/PUMP  
HEATERS  
(208/230,230V)  
(380,460,575V)  
2
8
BLK  
WHT  
YEL  
NOTES:  
SEE NOTE 7  
BLK  
FCB2/FB2  
FC2  
21  
9. IF CHILLED WATER PUMP INTERLOCK IS USED,  
REMOVE JUMPER FROM TERMINAL 11 TO 17 AND  
WIRE INTERLOCK CONTACT ACROSS TERMINALS 11 & 17.  
1. FACTORY WIRING IS IN ACCORDANCE WITH UL 1995 STANDARDS.  
ANY FIELD MODIFICATIONS OR ADDITIONS MUST BE IN  
COMPLIANCE WITH ALL APPLICABLE CODES.  
1
21  
22  
23  
11  
12  
13  
BLK-1  
BLK-2  
BLK-3  
BLK 11  
2
3
2. USE 75 C MIN WIRE FOR FIELD POWER SUPPLY.  
10. MP-A1 NOT USED IN THE FOLLOWING UNITS:  
035-045: ALL UNITS  
050-060: 460V UNITS WITHOUT DIGITAL SCROLL  
12  
YEL  
BLU  
22  
23  
OFM1  
YEL  
3. ALL FIELD INTERLOCK CONTACTS MUST HAVE A MIN RATING OF  
2 AMPS @ 24VAC SEALED. SEE FIELD INTERLOCK WIRING.  
13  
BLU  
GRN/YEL  
11. MP-A2 NOT USED IN THE FOLLOWING UNITS:  
035-045: ALL UNITS  
050-060: 460V UNITS  
4. COMPRESSOR AND FAN MOTORS ARE THERMALLY PROTECTED--  
THREE PHASE MOTORS PROTECTED AGAINST PRIMARY SINGLE  
PHASE CONDITIONS.  
1
2
3
BLK-1  
BLK-2  
BLK-3  
12. MP-B1 NOT USED IN THE FOLLOWING UNITS:  
035,040: ALL UNITS  
045-060: 460V UNITS  
13. MP-B2 NOT USED IN THE FOLLOWING UNITS:  
035,040: ALL UNITS  
045-060: 460V UNITS  
5. TERMINALS 13& 14 OF LVT ARE FOR FIELD CONNECTION  
OF REMOTE ON-OFF. THE CONTACT MUST BE RATED FOR DRY  
CIRCUIT APPLICATION CAPABLE OF HANDLING A 5VDC  
1 MA TO 20 MA LOAD.  
OFM2  
YEL  
BLK BLU  
6. FOR 500 SERIES UNIT OPERATION AT 208-3-60V LINE VOLTAGE,  
TRAN1 PRIMARY CONNECTIONS MUST BE MOVED TO TERMINALS H3  
GRN/YEL  
& H4.  
FC3  
14. JUMPER PLUG REQUIRED WHEN MP NOT USED  
1
2
3
7. FOR 575-3-60V UNITS, FAN CIRCUIT BREAKER FCB2  
IS REPLACED WITH FUSE BLOCK FB2.  
11  
12  
13  
21  
22  
23  
BLK-1  
BLK-2  
BLK-3  
BLK  
YEL  
BLU  
8. FOR UNITS WITH LOW AMBIENT MOTOR MASTER V FIOP/ACCESSORY,  
030-050: FAN CONTACTOR FC1 IS REPLACED WITH MOTORMASTER RELAY MMR.  
055,060: FAN CONTACTOR FC3 IS REPLACED WITH MOTORMASTER RELAY MMR..  
OFM4  
(055,060 ONLY)  
BLK  
YEL  
GRN/YEL  
(055,060 ONLY)  
LOW AMBIENT OPERATION (MOTORMASTER V) FIOP/ACCESSORY  
TABLE 1  
SERIES  
TABLE 2  
TERMINAL  
CONNECTIONS  
TERMINAL  
CONNECTIONS  
MM-A  
FB3  
FB1  
VOLTAGE  
VOLTAGE  
SERIES  
1
2
3
FOR PRIMARY SIDE  
FOR PRIMARY SIDE  
11  
12  
13  
21  
22  
23  
11  
12  
13  
21  
22  
23  
L1 T1  
BLK  
YEL  
BLU  
BLK  
YEL  
BLU  
BLK  
YEL  
BLU  
BLK-1  
BLK-2  
BLK-3  
575-3-60  
380-3-60  
230-3-60  
208-3-60  
460-3-60  
100  
200  
500  
500  
600  
H1  
H1  
H2  
H3  
H1  
&
&
&
&
&
H2  
H2  
H4  
H4  
H4  
575-3-60  
380-3-60  
230-3-60  
208-3-60  
460-3-60  
100  
200  
500  
500  
600  
COM  
COM  
COM  
COM  
COM  
&
&
&
&
&
575  
380  
230  
208  
460  
OFM3 (035-050)  
OFM4 (055,060)  
L2 T2  
L3 T3  
GRN/YEL  
YEL  
HIGH SCCR  
ONLY  
2
MMR  
14  
*
MM SIGNAL CONNECTION  
FU1  
FU2  
BLK  
YEL  
*1  
VIO 11  
TB  
1
VOLTAGE  
208/230/460/575  
380  
HZ  
60  
60  
BLK  
YEL  
240  
1/4W  
RED  
BLK  
25  
2
FROM  
AUX-J4  
13A  
CONNECT FOR  
APPROPRIATE  
PRIMARY VOLTAGE  
SEE TABLE 1  
CONNECT FOR  
APPROPRIATE  
575  
460  
400  
380  
230  
PRIMARY VOLTAGE  
SEE TABLE 2  
CHC  
TRAN2  
PRIMARY  
TRAN1  
PRIMARY  
4
8
2
6
BLK  
WHT  
COOLER/PUMP  
HEATERS  
BLK  
BLK  
BLK  
1
H3  
208  
H1  
X1  
H2  
H4  
COM  
3
2
2
3
COOLER/PUMP  
HEATERS  
(208/230,230V)  
CB4  
3.2 AMPS  
(380,460,575V)  
SECONDARY 24V  
SECONDARY 24V  
TB4  
7
CHC  
RED XF  
X2  
BRN  
C
RED  
FU3  
YEL  
BLK  
WHT  
GRN/YEL  
TB1  
GRN/YEL  
RED  
SEE NOTE 7  
BLK  
A1  
FCB2/FB2  
SW2  
RED  
FC2  
21  
BRN  
1
11  
12  
13  
21  
22  
23  
11  
12  
13  
BLK-1  
BLK-2  
BLK-3  
BLK  
YEL  
BLU  
C1  
BRN  
B1  
2
3
3
2
1
3
J1  
EXV  
J2  
YEL  
BLU  
22  
23  
OFM1  
3
2
1
3
2
UPC FIOP  
24VAC  
BRN  
RED  
2
1
VIO  
1
GRN/YEL  
CB3  
3.2 AMPS  
BRN  
VIO  
2
1
GND  
HOT  
TB4  
1
2
3
UPC  
BLK-1  
BLK-2  
BLK-3  
VIO  
6
FIOP/ACCESSORY  
J1  
OFM2  
DGS FIOP  
VIO  
3
2
1
3
2
1
3
2
3
2
1
J1  
MBB  
J2  
3
2
1
3
2
1
3
2
1
3
GRN/YEL  
2
1
BRN  
RED  
12  
2
1
BRN  
RED  
BRN  
VIO  
AUX  
J1  
EMM  
J2  
FC1  
a30-  
5283  
1
2
3
1
11  
BLK  
11  
12  
13  
21  
22  
23  
BLK-1  
BLK-2  
BLK-3  
YEL  
OFM3  
(055,060 ONLY)  
BLU  
BRN  
GRN/YEL  
(055,060 ONLY)  
1
3
VIO  
BRN  
BLU  
BRN  
CWFS  
Fig. 7A — Typical Wiring Schematic, 30RAP035-060 Units — Power Wiring  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CB1  
3.2 AMPS  
TB4  
4
a30-5284  
RED  
TB1  
TRAN1  
RED  
SEE NOTE 10  
A2  
B2  
CB2  
5.2 AMPS  
SW2  
C2  
RED  
BRN  
BRN  
BRN  
MBB J1-2  
UPC GND  
CWFS 3  
PL1-3  
RED  
PL1-4  
BRN  
TB4  
7
TB4  
5
RED  
RED  
RED  
RED  
BRN  
BRN  
BRN  
BRN  
SECONDARY 24V  
T2 MP-A1 T1  
SEE NOTE 11  
XF  
X1  
X2  
RED  
RED  
FU3  
BRN  
GRN/YEL  
ORN  
MBB  
ORN  
ORN  
PL1-7  
RED  
PL1-8  
BRN  
J10A  
1
2
3
4
5
6
7
8
9
1
2
3
4
5
BRN A2 CB1  
T2 MP-A2 T1  
SEE NOTE 12  
1
2
RED  
BRN  
LVT J12-5  
BLK  
PL2-3  
RED  
PL2-4  
BRN  
BRN A2 CHC  
BRN A2 CA1  
C
BLU  
GRA  
T2 MP-B1 T1  
SEE NOTE 13  
RED  
RED  
RLY 11  
GRA  
GRA  
BRN  
A2 CWP1  
3
BRN  
BRN  
PL2-7  
RED  
PL2-8  
BRN  
T2 MP-B2 T1  
MLV-A  
4
MLV ACCSY  
BRN  
5
6
PNK  
A1 FC1 A2  
SEE NOTE 8  
A2 CA2  
A2 FC2  
PNK  
BRN  
RLY 9  
LEGEND  
BRN  
7
TERMINAL BLOCK  
TERMINAL (UNMARKED)  
TERMINAL (MARKED)  
SPLICE  
X
X
8
A2 FC1  
A2 FC3  
BRN  
BRN  
FACTORY WIRING  
FIELD WIRING  
RLY 10  
9
ORN  
BLK  
VIO  
ORN  
VIO  
PNK  
A1 FC2 A2  
ACCESSORY OR OPTION WIRING  
HPS-B  
TO INDICATE COMMON POTENTIAL  
ONLY,NOT TO REPRESENT WIRING  
J10B  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
BLU  
BLK  
BLU  
BRN  
BRN  
C
TB1  
PL2-1  
PL2-2  
PL2-6  
MP-B1  
ACCSY  
ALMR  
AUX  
BR  
C
CB  
CCB  
CH  
CHC  
CO  
COMP  
CSB  
CWFS  
CWP  
CWPI  
DGS  
DLS  
DPT  
DTT  
DUS  
EMM  
EWT  
EXV  
FB  
ACCESSORY  
ALARM RELAY  
AUXILIARY  
BOILER RELAY  
CONTACTOR, COMPRESSOR  
CIRCUIT BREAKER  
VIO  
VIO  
VIO  
A2 CB2  
RLY 5  
M1  
M1  
CB1  
FR3  
M2  
M2  
A1  
1
A2  
0
VIO  
PNK  
BRN  
SEE NOTE 14  
PL2-5  
VIO  
(055,060 ONLY)  
MP-B2  
RLY 6  
PNK  
RED  
VIO  
A2 CB1  
A1 CB2 A2  
BRN  
BRN  
BRN  
COMPRESSOR CIRCUIT BREAKER  
CRANKCASE HEATER  
COOLER/PUMP HEATER CONTACTOR  
CONVENIENCE OUTLET  
COMPRESSOR  
CURRENT SENSOR BOARD  
CHILLED WATER FLOW SWITCH  
CHILLED WATER PUMP  
CHILLED WATER PUMP INTERLOCK  
DIGITAL SCROLL  
DEMAND LIMIT SWITCH  
DISCHARGE PRESSURE TRANSDUCER  
DISCHARGE TEMPERATURE THERMISTOR  
DIGITAL UNLOADER SOLENOID  
ENERGY MANAGEMENT  
ENTERING WATER TEMPERATURE  
EXPANSION VALVE CONTROL BOARD  
FUSE BLOCK  
TB4  
4
BRN  
SEE NOTE 14  
VIO  
1
FR4  
0
(055,060 ONLY)  
LVT  
MAX LOAD-5VA SEALED  
10VA INRUSH  
6
7
LVT  
J11  
J12  
RED  
RED  
ALM  
R
RED  
1
18  
21  
5
C
TB1  
RLY 7  
ACCESSORY  
STORAGE TANK  
HEATER RELAY  
8
TNK  
R
9
RED  
ORN  
10  
ORN  
BLK  
ORN  
C
C
TB1  
TB1  
RLY 8  
RLY 1  
RLY 2  
RLY 3  
RLY 4  
ORN  
A1 CHC A2  
HPS-A  
11  
12  
BLK  
BLK  
BLK  
BRN  
BRN  
PL1-1  
PL1-2  
VIO  
MP-A1  
VIO  
VIO  
A2 CA2  
FC  
FAN CONTACTOR  
M1  
M1  
M2  
M2  
ORN  
ORN  
A1 CA1 A2  
FCB  
FIOP  
FR  
FAN CIRCUIT BREAKER  
FACTORY INSTALLED OPTION  
FAN RELAY  
BRN  
BRN  
SEE NOTE 14  
PL1-5  
13  
14  
VIO  
1
FR1  
0
(055,060 ONLY)  
(055,060 ONLY)  
PL1-6  
VIO  
MP-A2  
FU  
FUSE  
GROUND  
GRA  
A2 CA1  
GRA  
GRA  
A1 CA2 A2  
BRN  
GND  
HPS  
HR  
LVT  
LWT  
MBB  
MLV  
MM  
HIGH PRESSURE SWITCH  
HEAT RELAY  
LOW VOLTAGE TERMINAL  
LEAVING WATER TEMPERATURE  
MAIN BASE BOARD  
MINIMUM LOAD VALVE  
MOTORMASTER  
MOTORMASTER RELAY  
MODULAR MOTOR PROTECTOR  
MANUAL STARTER  
15  
SEE NOTE 14  
VIO  
1
FR2  
0
16  
17  
18  
VIO  
TAN  
RED  
LVT  
J12  
CWP  
1
VIO  
RED  
BRN  
C
A1  
A2  
TB1  
A2 CWP2  
A2 CWP1  
BRN  
BRN  
1
2
25  
24  
MMR  
MP  
MS  
CWP  
2
A1  
A2  
OAT  
OFM  
PL  
OUTDOOR AIR THERMISTOR  
OUTDOOR FAN MOTOR  
PLUG  
FIOP OR  
FIELD INSTALLED  
OPTION  
FR4  
4
2
R
RELAY  
LVT  
(055,060 ONLY)  
RGT  
RLY  
SAT  
SCCR  
SPT  
SW  
RETURN GAS TEMPERATURE  
RELAY  
SUPPLY AIR TEMPERATURE  
SHORT CIRCUIT CURRENT RATING  
SUCTION PRESSURE TRANSDUCER  
SWITCH  
TERMINAL BLOCK  
STORAGE TANK HEATER RELAY  
TRANSFORMER  
PNK  
PNK  
PNK  
TAN  
TAN  
J12  
6
HEAT  
FIELD INSTALLED  
MAX LOAD-5VA SEALED  
10VA INRUSH  
6
5
4
3
2
1
FR3  
20  
19  
GRA  
GRA  
6
5
4
3
2
1
4
2
7
(055,060 ONLY)  
TB  
J6  
FR2  
HR  
ALMR  
TNKR  
TRAN  
UPC  
VIO  
BRN  
4
BR  
2
UNITARY PROTOCOL CONVERTER  
(055,060 ONLY)  
HEAT/BOILER FIELD  
INSTALLED WIRING  
TAN  
FR1  
4
A2 FC2  
2
PNK  
A1 FC3 A2  
BRN  
LVT  
J11  
2
(055,060 ONLY)  
CWFS  
4
(055,060 ONLY)  
SEE NOTE 8  
2
10  
17  
BLK  
WHT  
10  
PL-EXVB  
4
3
2
1
1
2
3
4
5
BLK  
YEL  
4
3
2
1
EXV  
BLK  
WHT  
1
2
3
1
2
3
4
3
4
RED  
BLK  
WHT  
RED  
1
2
3
4
CWPI  
SEE  
J3  
EXV-B  
WHT  
BLK  
J7  
GRY  
RED  
J3  
J4  
NOTE  
9
4
5
GRN  
RED  
9
4
3
2
1
11  
11  
12  
13  
14  
9
ORN  
9
1
2
3
4
5
6
1
2
3
4
5
6
MARQUEE  
DISPLAY  
PL-EXVA  
BLK  
4
3
2
1
RED  
WHT  
BLK  
RED  
WHT  
BLK  
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
BLK  
YEL  
1
2
3
4
5
BLK  
WHT  
RED  
J4  
WHT  
EXV-A  
J6  
GRY  
RED  
GRN  
RED  
BRN  
RED  
RED  
BRN  
1
MAIN  
BASE  
BOARD  
1
2
RED  
ORN  
BRN  
RED  
ORN  
BRN  
RED  
ORN  
BRN  
RED  
ORN  
BRN  
2
2
CSB  
B2  
3
3
PL50-1  
7
8
DUS  
DTT  
8
7
3
1
-
7
8
VIO  
RED  
4
13  
14  
RED  
8
7
AUX  
4
2
J2  
CH1  
6
5
4
3
2
1
BRN  
BLK  
5
CSB  
A2  
SW1  
ENABLE  
RED  
-
G
+
-
G
+
3
2
1
3
2
1
5
3
PL50-2  
PL50-3  
A1  
B1  
6
6
1
7
1
2
OFF  
RED  
7
C1  
J9  
CH11  
-
REMOTE  
RED  
BLK  
RED  
BLK  
1
2
7
2
ON-OFF  
SWITCH  
(SEE NOTE  
5)  
8
CSB  
B1  
J9  
DGS OR  
MM  
FIOP  
J6  
J4  
J5  
BLK  
WHT  
RED  
8
3
9
PL50-4  
8
RED  
GRA  
GRA  
9
1
10  
11  
12  
1
2
10  
11  
12  
2
CH9  
-
1
2
RED  
BLK  
CSB  
A1  
TO MM-A  
6
5
4
3
15  
16  
6
6
5
4
3
2
1
1
ON  
J7  
1
2
OFF  
CH10  
-
1
2
5
1
2
3
4
5
6
1
2
3
4
1
2
3
4
1
2
3
4
5
6
7
RGTA  
RGTB  
1
DARK  
2
3
=
4
5
6
7
8
RED  
DUAL  
SETPOINT  
1
2
SWITCH LOCATION  
BLK  
RED  
RED  
14  
13  
CWP2  
RED  
3
LVT  
J12  
4
BLK  
BLU  
BLU  
RED  
T55  
3
2
1
LVT  
J10  
5
3
23  
22  
T-55  
SEN  
1
1
2
GRA  
GRA  
RED  
RED  
BLU  
BLU  
17  
16  
15  
14  
13  
12  
11  
1
2
3
4
5
6
ACCSY  
4
3
2
1
6
4
2
4
3
2
1
EMM  
VIO  
14  
13  
CWP1  
VIO  
OAT  
3
ICE DONE  
DLS STEP  
DLS STEP  
7
BLK  
WHT  
RED  
3
SPACE TEMPERATURE  
ACCESSORY OR  
DUAL CHILLER LWT  
J3  
J4  
4
4
8
BLK  
5
1
5
9
6
6
7
2
LVT  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
7
8
EVAPORATOR ENTERING  
FLUID TEMP  
4
3
2
1
J7  
RED  
8
4
3
2
1
9
J13  
10  
9
8
7
6
5
4
3
2
1
9
BLK  
WHT  
RED  
BRN  
10  
9
8
7
6
5
4
3
2
1
BLK  
RED  
10  
11  
12  
13  
14  
1
2
3
4
5
6
7
8
BLK  
10  
11  
12  
13  
14  
RED  
EVAPORATOR LEAVING  
FLUID TEMP  
J8  
WHT  
RED  
BRN  
RED  
BLK  
WHT  
RED  
RED  
BLK  
RED  
BLK  
WHT  
RED  
B
C
A
B
C
A
WHT  
BLK  
+
J5  
10  
9
8
7
6
5
4
3
2
1
FIOP/  
ACCESSORY  
DPTB  
GRN  
BLK  
RED  
DEMAND  
LIMIT  
4-20mA  
7
8
+
-
-
1
BLK  
WHT  
RED  
1
2
2
J1  
VIO  
BRN  
+
3
3
SPTB  
DPTA  
SPTA  
GRN  
BLK  
4
UPC  
TEMP  
RESET  
4-20mA  
4
9
+
-
-
5
PORT  
2
5
ORN  
PNK  
B
C
A
RED  
BLK  
1
NET  
+
-
6
LON  
OPTION  
RED  
6
2
3
4
5
NET  
N/C  
N/C  
+
7
8
J6  
COOLING  
SETPOINT  
4-20mA  
J3 GND  
NET  
7
10  
+
-
GRN  
BLK  
8
8
9
-
9
J4  
1
9
WHT  
SIGNAL  
10  
B
C
A
10  
11  
12  
RED  
10  
11  
12  
PORT 1A  
2
+
11  
12  
1
2
3
NET  
NET  
+
2
GRN  
BLK  
-
SHIELD  
UPC OPT  
Fig. 7B — Typical Wiring Schematic, 30RAP035-060 Units — Control Wiring  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RED LED - STATUS  
GREEN LED -  
LEN (LOCAL EQUIPMENT NETWORK)  
YELLOW LED -  
CCN (CARRIER COMFORT NETWORK)  
INSTANCE JUMPER  
CEPL130346-01  
K11  
K10  
K9  
K5  
K8  
K6  
K7  
J1  
STATUS  
J2  
J3  
J10  
LEN  
J4  
K1  
K4  
K3  
K2  
CCN  
J5  
J6  
J7  
J8  
J9  
Fig. 8 — Main Base Board  
a30-4967  
Fig. 9 — Enable/Off/Remote Contact Switch, and Emergency On/Off Switch Locations  
T-55 SPACE  
SENSOR  
a30-4968  
SPT (T10) PART NO. 33ZCT55SPT  
SENSOR  
6
5
4
3
2
1
CCN+  
LVT  
TO CCN  
CCN GND  
SEN  
SEN  
COMM 1  
BUS (PLUG)  
AT UNIT  
3
CCN-  
4
Fig. 10 — Typical Space Temperature  
Sensor Wiring  
Fig. 11 — CCN Communications Bus Wiring  
to Optional Space Sensor RJ11 Connector  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
compressor to start next. If no compressors have been running  
for more than 30 minutes and the leaving fluid temperature is  
greater than the saturated condensing temperature, the wear  
factor is still used to determine which compressor to start next.  
If the leaving fluid temperature is less than the saturated con-  
densing temperature, then the control will start either compres-  
sor A1 or compressor B1 first, depending on the user-configu-  
rable circuit lead-lag value. For units with the minimum load  
control valve, the A circuit with the minimum load valve is al-  
ways the lead circuit. The A circuit is also always the lead for  
units with the digital compressor option. On units with the dig-  
ital scroll option, the A1 compressor operates continuously,  
providing close leaving chilled water control. For this reason,  
on/off cycling of the unit’s compressors is dramatically re-  
duced, which in turn reduces wear associated with compressor  
start/stop cycles.  
Energy Management Module (Fig. 12) This  
factory-installed option (FIOP) or field-installed accessory is  
used for the following types of temperature reset, demand  
limit, and/or ice features:  
4 to 20 mA leaving fluid temperature reset (requires  
field-supplied 4 to 20 mA generator)  
4 to 20 mA cooling set point reset (requires field-  
supplied 4 to 20 mA generator)  
Discrete inputs for 2-step demand limit (requires field-  
supplied dry contacts capable of handling a 24 vac,  
50 mA load)  
4 to 20 mA demand limit (requires field-supplied 4 to  
20 mA generator)  
Discrete input for Ice Done switch (requires field-  
supplied dry contacts capable of handling a 24 vac,  
50 mA load)  
The EXVs will provide a controlled start-up. During start-  
up, the low pressure logic will be bypassed for 21/2 minutes to  
allow for the transient changes during start-up. As additional  
stages of compression are required, the processor control will  
add them. See Table 19.  
See Demand Limit and Temperature Reset sections on  
pages 41 and 37 for further details.  
CAUTION  
Care should be taken when interfacing with other manufac-  
turer’s control systems due to possible power supply  
differences, full wave bridge versus half wave rectification.  
The two different power supplies cannot be mixed.  
ComfortLink™ controls use half wave rectification. A  
signal isolation device should be utilized if a full wave  
bridge signal generating device is used.  
If a circuit is to be stopped, the compressor with the lowest  
wear factor will be shut off first except when a digital compres-  
sor is used. The digital compressor is always the last compres-  
sor to shut off.  
The capacity control algorithm runs every 30 seconds. The  
algorithm attempts to maintain the Control Point at the desired  
set point. Each time it runs, the control reads the entering and  
leaving fluid temperatures. The control determines the rate at  
which conditions are changing and calculates 2 variables based  
on these conditions. Next, a capacity ratio is calculated using  
the 2 variables to determine whether or not to make any  
changes to the current stages of capacity. This ratio value  
ranges from –100 to +100%. If the next stage of capacity is a  
compressor, the control starts (stops) a compressor when the  
ratio reaches +100% (–100%). If installed, the minimum load  
valve solenoid will be energized with the first stage of capacity.  
Minimum load valve value is a fixed 30% in the total capacity  
calculation. The control will also use the minimum load valve  
solenoid as the last stage of capacity before turning off the last  
compressor. A delay of 90 seconds occurs after each capacity  
step change. Refer to Table 19.  
Loss-of-Cooler Flow Protection —  
A
proof-of-  
cooler flow device is factory installed in all chillers. It is recom-  
mended that proper operation of the switch be verified on a reg-  
ular basis.  
Electronic Expansion Valves (EXV) — All units are  
equipped from the factory with EXVs. Each refrigeration cir-  
cuit is also supplied with a factory-installed liquid line filter  
drier and sight glass.  
The EXV is set at the factory to maintain 9° F (5.0° C) suc-  
tion superheat leaving the cooler by metering the proper  
amount of refrigerant into the cooler. The superheat set point is  
adjustable, but should not be adjusted unless absolutely  
necessary.  
MINUTES LEFT FOR START — This value is displayed  
only in the network display tables (using Service Tool,  
ComfortVIEW™ or ComfortWORKS® software) and  
represents the amount of time to elapse before the unit will start  
its initialization routine. This value can be zero without the  
machine running in many situations. This can include being  
unoccupied, ENABLE/OFF/REMOTE CONTACT switch in  
the OFF position, CCN not allowing unit to start, Demand  
Limit in effect, no call for cooling due to no load, and alarm or  
alert conditions present. If the machine should be running and  
none of the above are true, a minimum off time (DELY, see  
below) may be in effect. The machine should start normally  
once the time limit has expired.  
The EXV is designed to limit the cooler saturated suction  
temperature to 50 F (12.8 C). This makes it possible for unit to  
start at high cooler fluid temperatures without overloading the  
compressor.  
Capacity Control — The control system cycles com-  
pressors, digital scroll modulting solenoid (if equipped), and  
minimum load valve solenoids (if equipped) to maintain the  
user-configured leaving chilled fluid temperature set point. En-  
tering fluid temperature is used by the main base board (MBB)  
to determine the temperature drop across the cooler and is used  
in determining the optimum time to add or subtract capacity  
stages. The chilled fluid temperature set point can be automati-  
cally reset by the return fluid temperature, space, or outdoor-air  
temperature reset features. It can also be reset from an external  
4 to 20-mA signal (requires energy management module FIOP  
or accessory).  
The standard control has an automatic lead-lag feature built  
in which determines the wear factor (combination of starts and  
run hours) for each compressor. If all compressors are off and  
less than 30 minutes has elapsed since the last compressor was  
turned off, the wear factor is used to determine which  
MINUTES  
OFF  
TIME  
(ConfigurationOPT2  
DELY) — This user-configurable time period is used by the  
control to determine how long unit operation is delayed after  
power is applied/restored to the unit. Typically, this time period  
is configured when multiple machines are located on a single  
site. For example, this gives the user the ability to prevent all  
the units from restarting at once after a power failure. A value  
of zero for this variable does not mean that the unit should be  
running.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CEBD430351-0396-01C  
J1  
J2  
LEN  
J4  
J3  
STATUS  
J5  
J7  
J6  
TEST 2  
GREEN LED -  
LEN (LOCAL EQUIPMENT NETWORK)  
ADDRESS  
DIP SWITCH  
RED LED - STATUS  
Fig. 12 — Energy Management Module  
LEAD/LAG DETERMINATION — This is a configurable  
choice and is factory set to be automatic for all units unless the  
unit is equipped with a digital scroll compressor or minimum  
load, then circuit A is lead (ConfigurationOPT2LLCS).  
The value can be changed to Circuit A or Circuit B leading as  
desired. Set at automatic, the control will sum the current num-  
ber of logged circuit starts and one-quarter of the current oper-  
ating hours for each circuit. The circuit with the lowest sum is  
started first. Changes to which circuit is the lead circuit and  
which is the lag are also made when total machine capacity is  
at 100% or when there is a change in the direction of capacity  
(increase or decrease) and each circuit’s capacity is equal.  
when the control is attempting to remove the last stage of  
capacity.  
Slow Change Override — The control prevents the capacity  
stages from being changed when the leaving fluid temperature  
is close to the set point (within an adjustable deadband) and  
moving towards the set point.  
Ramp Loading  
Ramp  
loading  
(Configura-  
tionSLCTCRMP) limits the rate of change of leaving  
fluid temperature. If the unit is in a Cooling mode and config-  
ured for Ramp Loading, the control makes 2 comparisons be-  
fore deciding to change stages of capacity. The control calcu-  
lates a temperature difference between the control point and  
leaving fluid temperature. If the difference is greater than 4° F  
(2.2° C) and the rate of change (°F or °C per minute) is more  
than the configured Cooling Ramp Loading value (CRMP),  
the control does not allow any changes to the current stage of  
capacity.  
CAPACITY CONTROL OVERRIDES — The following over-  
rides will modify the normal operation of the routine.  
Deadband Multiplier — The user configurable Deadband  
Multiplier (ConfigurationSLCTZ.GN) has a default val-  
ue of 1.0. The range is from 1.0 to 4.0. When set to other than  
1.0, this factor is applied to the capacity Load/Unload Factor.  
The larger this value is set, the longer the control will delay be-  
tween adding or removing stages of capacity. Figure 13 shows  
how compressor starts can be reduced over time if the leaving  
water temperature is allowed to drift a larger amount above and  
below the set point. This value should be set in the range of 3.0  
to 4.0 for systems with small loop volumes.  
Low Entering Fluid Temperature Unloading — When the  
entering fluid temperature is below the control point, the  
control will attempt to remove 25% of the current stages being  
used. If exactly 25% cannot be removed, the control removes  
an amount greater than 25% but no more than necessary. The  
lowest stage will not be removed.  
Minimum Load Control — If equipped, the minimum load  
control valve is energized only when one compressor is run-  
ning on circuit A. If the close control feature is enabled the  
minimum load control valve may be used as needed to obtain  
leaving fluid temperature close to set point.  
First Stage Override — If the current capacity stage is zero,  
the control will modify the routine with a 1.2 factor on adding  
the first stage to reduce cycling. This factor is also applied  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 19 — Part Load Data Percent Displacement, Standard Units with Minimum Load Valve  
CAPACITY STEPS  
CAPACITY %  
CONTROL  
STEPS  
30RAP UNIT SIZE  
% Displacement  
Circuit A  
100  
100  
Circuit B  
010  
015  
1
1
100  
100  
1
2
3
1
2
3
1
2
3
1
2
3
100  
50  
018  
020  
025  
030  
100  
100  
100  
100  
20*  
100  
50  
24*  
100  
50  
29*  
100  
50  
32*  
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
100  
77  
50  
23  
9*  
035  
040  
045  
050  
055  
54  
47  
47  
50  
46  
50  
46  
53  
53  
50  
54  
50  
100  
73  
50  
23  
11*  
100  
74  
50  
24  
12*  
100  
75  
50  
25  
14*  
100  
73  
50  
23  
13*  
100  
75  
060  
50  
25  
16*  
*Minimum Load Valve energized.  
NOTE: These capacity steps may vary due to different capacity  
staging sequences.  
2 STARTS  
DEADBAND EXAMPLE  
47  
8
7
6
5
46  
45  
44  
43  
42  
41  
0
200  
400  
600  
800  
1000  
3 STARTS  
TIME (SECONDS)  
STANDARD  
DEADBAND  
LEGEND  
LWT — Leaving Water Temperature  
MODIFIED  
DEADBAND  
Fig. 13 — Deadband Multiplier  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Cooler Freeze Protection — The control will try to prevent  
shutting the chiller down on a Cooler Freeze Protection alarm  
by removing stages of capacity. If the cooler fluid selected  
is Water, the freeze point is 34 F (1.1 C). If the cooler fluid  
selected is Brine, the freeze point is the Brine Freeze Point (Set  
PointsFRZBR.FZ). This alarm condition (A207) only  
references leaving fluid temperature and NOT Brine Freeze  
point. If the cooler leaving fluid temperature is less than the  
freeze point plus 2.0° F (1.1° C), the control will immediately  
remove one stage of capacity. This can be repeated once every  
30 seconds.  
Low Saturated Suction Protection — The control will try to  
prevent shutting a circuit down due to low saturated suction  
conditions by removing stages of capacity. These circuit alert  
conditions (T116, T117) compare saturated suction tempera-  
ture to the configured Brine Freeze Point (Set  
PointsFRZBR.FZ). The Brine Freeze point is a user-  
configurable value that must be left at 34 F (1.1 C) for 100%  
water systems. A lower value may be entered for systems with  
brine solutions, but this value should be set according to the  
freeze protection level of the brine mixture. Failure to properly  
set this brine freeze point value may permanently damage the  
brazed plate heat exchanger. The control will initiate Mode 7  
(Circuit A) or Mode 8 (Circuit B) to indicate a circuit’s capaci-  
ty is limited and that eventually the circuit may shut down.  
be added to the current fan stage. Fan On Set Point (F.ON)  
equals Head Set Point (Set PointsHEADH.DP) except  
after a fan stage increase when the Head Set Point is increased  
by Fan Stage Delta (Set PointsHEADF.DLT). A fan  
stage is decreased when the SCTs of both circuits are less than  
the Fan Off Set Point (Set PointsHEAD F.OFF) for  
two minutes. Table 20 shows the number of fan stages, contac-  
tors energized and the fans that are on during the fan stage.  
Unit sizes 035 to 060 have common fan control. Figure 14  
shows the location of each fan and compressor within the unit.  
MOTORMASTER® V OPTION — Motormaster V is stan-  
dard on 30RAP010 and 015 size units. For all other units that  
need low-ambient operation, the lead fan on a circuit can be  
equipped with the Motormaster V head pressure controller op-  
tion or accessory. The controller is energized with the first fan  
stage and adjusts fan speed to maintain a SCT of 72 F (22.2 C).  
The first stage of fan operation is controlled by the Motormas-  
ter V controller. Refer to Fig. 15 for condenser fan layout infor-  
mation. The Motormaster is configured in the Motormaster Se-  
lect (ConfigurationMMMMR.S)  
Operation of Machine Based on Control  
Method and Cooling Set Point Selection Set-  
tings — Machine On/Off control is determined by the  
configuration of the Control Method  
(Configura-  
tionOPT2CTRL) and Cooling Set Point Select (Config-  
urationSLCTCLSP) variables. All units are factory  
configured with Cooling Set Point Select set to 0 (single set  
point). With the control method set to 0, simply switching the  
Enable/Off/Remote Contact switch to the Enable or Remote  
Contact position (external contacts closed) will put the chiller  
in an occupied state. The control mode (Operating  
ModesMODE) will be 1 (OFF LOCAL) when the switch is  
Off and will be 5 (ON LOCAL) when in the Enable position or  
Remote Contact position with external contacts closed.  
Head Pressure Control — The main base board  
(MBB) controls the condenser fans to maintain the lowest  
condensing temperature possible, and thus the highest unit  
efficiency. The MBB uses the saturated condensing tempera-  
ture input from the discharge pressure transducer and outside  
air temperature sensor to control the fans. If OAT is greater  
than 70 F before a circuit is starting, then all condenser fan  
stages will be energized. A fan stage is increased based on  
SCT (saturated condensing temperature). When the highest  
SCT is greater than the Fan On Set Point (Set  
PointsHEADF.ON), then an additional stage of fan will  
170  
160  
150  
140  
130  
120  
110  
100  
90  
80  
70  
60  
50  
40  
30  
-30  
-20  
-10  
0
10  
20  
30  
40  
50  
60  
70  
80  
SST (F)  
LEGEND  
a30-4969  
SCT  
SST  
Saturated Condensing Temperature  
Saturated Suction Temperature  
Fig. 14 — Operating Envelope for R-410A Compressor  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OFM1  
OFM2  
a30-4970  
OFM1  
Top View  
Sizes 010,015  
Top View  
Sizes 018-030  
OFM1  
OFM3  
OFM1  
OFM3  
OFM2  
OFM4  
OFM2  
Top View  
Sizes 035-050  
Top View  
Sizes 055,060  
Fig. 15 — 30RAP Condenser Fan Layout  
Table 20 — Fan Stages  
FAN STAGES  
Contactor Energized  
30RAP UNIT SIZE  
Fan Stage  
Fans Operating  
010,015  
018-030  
Stage 1  
Stage 1  
Stage 2  
FC1  
FC1,2  
OFM1  
OFM1  
OFM1,2  
Stage 1  
Stage 2  
Stage 3  
Stage 1  
Stage 2  
Stage 3  
Stage 4  
FC1  
FC2  
OFM3  
OFM1,2  
OFM1,2,3  
OFM4  
OFM4,3  
OFM4,1,2  
OFM1,2,3,4  
035-050  
055,060  
FC1,2  
FC3  
FC1,3  
FC3,2  
FC1,2,3  
Two other control methods are available for Machine On/  
Off control:  
OCCUPANCY  
CTRL = 2) — The main base board will use the operating  
schedules as defined under the Time Clock mode in the scroll-  
ing marquee display. These schedules are identical. The sched-  
ule number must be set to 1 for local schedule.  
The schedule number can be set anywhere from 65 to 99  
for operation under a CCN global schedule. The Enable/Off/  
Remote Contact must be in the Enable or Remote Contact posi-  
tion. The control mode (Operating ModesMODE) will be  
1 when the switch is Off. The control mode will be 3 when the  
Enable/Off/Remote Contact switch input is On and the time of  
day is during an unoccupied period. Similarly, the control  
mode will be 7 when the time of day is during an occupied  
period.  
CCN CONTROL (ConfigurationOPT2CTRL = 3) —  
An external CCN device such as Chillervisor System Manager  
controls the On/Off state of the machine. This CCN device  
forces the variable ‘CHIL_S_S’ between Start/Stop to control  
the chiller. The control mode (Operating ModesMODE)  
will be 1 when the switch is Off. The control mode will be 2  
when the Enable/Off/Remote Contact switch input is On and  
the CHIL_S_S variable is ‘Stop.’ Similarly, the control mode  
will be 6 when the CHIL_S_S variable is ‘Start.’  
Table 20 illustrates how the control method and cooling set  
point select variables direct the operation of the chiller and the  
set point to which it controls. The illustration also shows the  
ON/OFF state of the machine for the given combinations.  
SCHEDULE  
(ConfigurationOPT2  
Cooling Set Point Select  
SINGLE — Unit operation is based on Cooling Set Point 1  
(Set PointsCOOLCSP.1).  
DUAL SWITCH — Unit operation is based on Cooling Set  
Point 1 (Set PointsCOOLCSP.1) when the Dual Set  
Point switch contacts are open and Cooling Set Point 2 (Set  
PointsCOOLCSP.2) when they are closed.  
DUAL CCN OCCUPIED — Unit operation is based on  
Cooling Set Point 1 (Set PointsCOOLCSP.1) during the  
Occupied mode and Cooling Set Point  
2
(Set  
PointsCOOLCSP.2) during the Unoccupied mode as  
configured under the local occupancy schedule accessible only  
from CCN. Schedule Number in Table SCHEDOVR (See Ap-  
pendix B) must be configured to 1. If the Schedule Number is  
set to 0, the unit will operate in a continuous 24-hr Occupied  
mode. Control method must be configured to 0 (switch). See  
Table 21.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 21 — Control Methods and Cooling Set Points  
COOLING SET POINT SELECT (CLSP)  
CONTROL  
TYPE  
(CTRL)  
OCCUPANCY  
STATE  
0
1
2
3
(single)  
(dual, switch)  
(dual, occ)  
(4 to 20 mA)  
Occupied  
Unoccupied  
Occupied  
Unoccupied  
Occupied  
Unoccupied  
ON,CSP1  
ON,CSP1  
ON,CSP1  
OFF  
ON,CSP1  
ON,CSP1  
ON*  
ON*  
ON*  
OFF  
ON*  
ON*  
ON,CSP1  
ON,CSP2  
Illegal  
Illegal  
ON,CSP1  
ON,CSP2  
ON†  
ON  
ON†  
OFF  
ON†  
ON†  
0 (switch)  
2 (Occupancy)  
3 (CCN)  
*Dual set point switch input used. CSP1 used when switch input is open. CSP2 used when switch input is closed.  
†Cooling set point determined from 4 to 20 mA input to energy management module (EMM) to terminals TB6-3,5.  
4 TO 20 mA INPUT — Unit operation is based on an external  
4 to 20 mA signal input to the Energy Management Module  
(EMM).  
under the COMP mode will stay on for 10 minutes if there is  
no keypad activity. Compressors will stay on until they are  
turned off by the operator. The Service Test mode will remain  
enabled for as long as there is one or more compressors run-  
ning. All safeties are monitored during this test and will turn a  
compressor, circuit or the machine off if required. Any other  
mode or sub-mode can be accessed, viewed, or changed during  
the TEST mode. The MODE item (Run StatusVIEW) will  
display “0” as long as the Service mode is enabled. The TEST  
sub-mode value must be changed back to OFF before the chill-  
er can be switched to Enable or Remote contact for normal  
operation.  
Low Sound Mode Operation — All models are fac-  
tory configured with the Low Sound Mode disabled. In the  
Configuration mode under sub-mode OPT2, items for Low  
Sound Mode Select (ConfigurationOPT2LS.MD), Low  
Sound Start Time (ConfigurationOPT2LS.ST), Low  
Sound End Time (ConfigurationOPT2LS.ND) and Low  
Sound Capacity Limit (ConfigurationOPT2LS.LT) are  
factory configured so that the chiller always runs as quietly as  
possible. This results in operation at increased saturated con-  
densing temperature. As a result, some models may not be able  
to achieve rated efficiency. For chiller operation at rated effi-  
ciency, disable the low sound mode or adjust the low sound  
mode start and stop times accordingly or set both times to  
00:00 for rated efficiency operation 24 hours per day. In addi-  
tion, the low sound capacity limit can be used to reduce overall  
chiller capacity, if required, by limiting the maximum to a user-  
configured percentage.  
Optional Factory-Installed Hydronic Pack-  
age — If the chiller has factory-installed chilled fluid pumps,  
specific steps should be followed for proper operation.  
The pump(s) in the hydronic package come factory  
pre-wired into the main unit power supply/starter. In order to  
check proper pump rotation, use the Service Test function to  
test the condenser fans and observe them for proper rotation. If  
fans turn correctly, the pumps will rotate correctly. Clockwise  
rotation of the pump motor cooling fans can also be used to de-  
termine that pumps are rotating correctly.  
Heating Operation — The chiller can be used for pump  
outputs or optional factory-installed hydronic system operation  
can be utilized for heating applications. The heating mode is  
activated when the control sees a field-supplied closed switch  
input to terminal block LVT-19,20. The control locks out cool-  
ing when the heat relay input is seen. A field-supplied boiler re-  
lay connection is made using heat relay and alarm relay con-  
tacts. Factory-installed ‘BOILER’ connections exist in the con-  
trol panel near LVT for these applications. Alarms and alerts  
A189 through A202 are active during heating operation.  
CAUTION  
Operation of pump in wrong direction, even for a few  
seconds, can cause irreversible damage to pump impeller  
and housing. Always verify correct wiring/pump rotation  
before operation.  
Use Service Test function to test operation of pumps. Verify  
that the flow switch input is made when the pump is running.  
For dual pump hydronic systems, the control only uses one  
pump at a time. Consult the Installation Instructions supplied  
with this chiller and use the circuit setter balancing valve  
installed in hydronic package to adjust fluid flow rate.  
Service Test (See Table 4) Both main power and  
control circuit power must be on.  
The Service Test function should be used to verify proper  
operation of condenser fan(s), compressors, minimum load  
valve solenoid (if installed), cooler pump(s), EXVs, and re-  
mote alarm relay. To use the Service Test mode, the Enable/  
Off/Remote Contact switch must be in the OFF position. Use  
the display keys and Table 4 to enter the mode and display  
Cooler Pump Control — The AquaSnap® 30RAP ma-  
chines equipped with a factory-installed pump package are  
configured with the Cooler Pump Control (Configura-  
tionOPT1CPC) = ON.  
Machines not equipped with a pump package are config-  
ured with the cooler pump control OFF. It is recommended that  
the machine control the chilled water pump. If not, a 5-minute  
time delay is required after the command to shut the machine  
down is sent before the chilled water pump is turned off. This is  
required to maintain water flow during the shutdown period of  
the machine.  
With or without this option enabled, the cooler pump relay  
will be energized when the machine enters an ON status (i.e.,  
On Local, On CCN, On Time). An A207 - Cooler Freeze  
Protection Alarm, will energize the cooler pump relay also, as  
an override. The cooler pump relay will remain energized if the  
machine is in MODE 10 – Minimum Off Time.  
TEST. Press  
twice so that OFF flashes. Enter the  
ENTER  
password if required. Use either arrow key to change the TEST  
value to the ON position and press . Press  
ENTER  
ESCAPE  
and the  
button to enter the OUTS or COMP sub-mode.  
Test the condenser fans, cooler pump(s) and alarm relay by  
changing the item values from OFF to ON. These discrete  
outputs are then turned off if there is no keypad activity for  
10 minutes. Use the arrow keys to select the desired percentage  
when testing expansion valves and Motormaster® V controller.  
When testing compressors, lead compressor must be started  
first. All compressor outputs can be turned on, but the control  
will limit the rate by staging one compressor per minute. Com-  
pressor unloaders and hot gas bypass relays/solenoids (if in-  
stalled) can be tested with the compressors on or off. The relays  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
interlock contacts should be rated for dry circuit application  
capable of handling 5 vdc at 2 mA.  
SINGLE INTEGRAL PUMP CONTROL — With a single  
pump, the following options must be configured:  
Cooler Pump Sequence of Operation — At any-  
time the unit is in an ON status, as defined by the one of the  
following conditions, the cooler pump relay will be enabled.  
1. The Enable-Off-Remote Switch in ENABLE,  
(CTRL=0).  
• Cooler Pump Control (ConfigurationOPT1CPC) =  
2. Enable-Off-Remote Switch in REMOTE with  
a
ON.  
Start-Stop remote contact closure (CTRL=0).  
• Cooler Pump  
PM1E) = YES.  
• Cooler Pump  
PM2E) = NO.  
1
2
Enable (ConfigurationOPT1  
Enable (ConfigurationOPT1  
3. An Occupied Time Period from an Occupancy Schedule  
in combination with items 1 or 2 (CTRL=2).  
4. A CCN Start-Stop Command to Start in combination  
with items 1 or 2 (CTRL=3).  
As stated before, there are certain alarm conditions and  
Operating Modes that will turn the cooler pump relay ON. This  
sequence will describe the normal operation of the pump  
control algorithm.  
When the unit cycles from an “On” state to an “Off” state,  
the cooler pump output will remain energized for the Cooler  
Pump Shutdown Delay (ConfigurationOPT1PM.DY).  
This is configurable from 0 to 10 minutes. The factory default  
is 1 minute.  
NO INTEGRAL PUMP — SINGLE EXTERNAL PUMP  
CONTROL — With a single external pump, the following  
options must be configured:  
With a single integral pump, the Cooler Pump Starter will  
be energized when the machine is occupied. As part of the  
factory-installed package, an auxiliary set of contacts is wired  
to the MBB to serve as Chilled Water Pump Interlock. When  
the mechanical cooling is called for, the pump interlock and  
flow switch is checked. If the circuits are closed, the machine  
starts its capacity routine. If the auxiliary contact interlock does  
not close within 25 seconds of the ON command, a T190 —  
Cooler Pump 1 Aux Contacts Failed to Close at Start-Up Alert  
will be generated and the pump shut down. The unit will not  
be allowed to start. If the chilled water flow switch does not  
close within one (1) minute, two alarms will be generated. A  
T192 — Cooler Pump 1 Failed to Provide Flow at Start-Up  
Alert and an A200 — Cooler Flow/Interlock Failed to Close at  
Start-Up Alarm will be generated and chiller will not be al-  
lowed to start.  
• Cooler Pump Control (ConfigurationOPT1CPC) =  
OFF.  
• Cooler Pump  
PM1E) = NO.  
• Cooler Pump  
PM2E) = NO.  
The maximum load allowed for the Chilled Water Pump  
Starter is 5 VA sealed, 10 VA inrush at 24 volts. The starter coil  
is powered from the chiller control system. The starter should  
be wired between LVT-25 and LVT-21. If equipped, the field-  
installed chilled water pump starter auxiliary contacts should  
be connected in series with the chilled water flow switch.  
The Cooler Pump Relay will be energized when the  
machine is “On.” The chilled water pump interlock circuit  
consists of a chilled water flow switch and a field-installed  
chilled water pump interlock. If the chilled water pump inter-  
lock circuit does not close within five (5) minutes of starting,  
an A200 — Cooler Flow/Interlock Failed to Close at Start-Up  
Alarm will be generated and chiller will not be allowed to start.  
If the chilled water pump interlock or chilled water flow  
switch opens for at least three (3) seconds after initially being  
closed, an A201 — Cooler Flow/Interlock Contacts Opened  
During Normal Operation Alarm will be generated and the ma-  
chine will stop.  
1
2
Enable (ConfigurationOPT1  
Enable (ConfigurationOPT1  
If the chilled water flow switch opens for at least 3 seconds  
after initially being closed, a T196 — Flow Lost While Pump 1  
Running Alert and an A201 — Cooler Flow/Interlock Contacts  
Opened During Normal Operation Alarm will be generated  
and the machine will stop.  
If the control detects the chilled water pump interlock open  
for 25 seconds after initially being closed, a T194 — Cooler  
a30-4979  
Pump 1 Contacts Opened During Normal Operation Alert is  
generated and the unit is shut down.  
If the control detects the chilled water flow switch circuit  
closed for at least 5 minutes with the pump output OFF, an  
A202 — Cooler Pump Interlock Closed When Pump is Off  
Alarm will be generated and the unit will not be allowed to  
start.  
If the control detects that the chilled water pump auxiliary  
contacts are closed for at least 25 seconds while the pump is  
OFF, a T198 — Cooler Pump 1 Aux Contacts Closed While  
Pump Off Alert is generated. The chiller will not be allowed to  
start.  
If the control starts a pump and the wrong interlock circuit  
closes for at least 20 seconds, an A189 — Cooler Pump and  
Aux Contact Input Miswire Alarm will be generated. The unit  
will be prevented from starting.  
As part of a pump maintenance routine, the pump can be  
started to maintain lubrication of the pump seal. To utilize this  
function, Cooler Pmp Periodic Start (ConfigurationOPT1  
PM.P.S) must be set to YES. This option is set to NO as the  
factory default. With this feature enabled, if the pump is not op-  
erating, it will be started and operated for 2 seconds starting at  
14:00 hours. If the pump is operating, this routine is skipped. If  
the pump has failed and an Alarm/Alert condition is active, the  
pump will not start that day.  
NO INTEGRAL PUMP — DUAL EXTERNAL PUMP  
CONTROL — With two external pumps, the following  
options must be configured:  
• Cooler Pump Control (ConfigurationOPT1CPC) =  
ON.  
• Cooler Pump  
PM1E) = YES.  
• Cooler Pump  
PM2E) = YES.  
1
2
Enable (ConfigurationOPT1  
Enable (ConfigurationOPT1  
The maximum load allowed for the Chilled Water Pump  
Starters is 5 VA sealed, 10 VA inrush at 24 volts. The starter  
coil is powered from the chiller control system. The starter for  
Chilled Water Pump 1 should be wired between LVT-25 and  
LVT-21. The starter for Chilled Water Pump 2 should be wired  
between LVT-24 and LVT-21. A field-installed chilled water  
pump interlock for each pump must be connected to each  
pump’s interlock points on the main base board. The chilled  
water pump 1 interlock, CWP1, must be connected to MBB-  
J7-1 and –2. The chilled water pump 2 interlock, CWP2, must  
be connected to MBB-J7-3 and –4. The chilled water pump  
DUAL INTEGRAL PUMP CONTROL — With a dual inte-  
gral pump package, the following options must be configured:  
• Cooler Pump Control (ConfigurationOPT1CPC) =  
ON.  
• Cooler Pump  
PM1E) = YES.  
• Cooler Pump  
PM2E) = YES.  
1
2
Enable (ConfigurationOPT1  
Enable (ConfigurationOPT1  
Pump Start Selection is a field-configurable choice. Cooler  
Pump Select (ConfigurationOPT1PM.SL) is factory  
defaulted to 0 (Automatic). This value can be changed to 1  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(Pump 1 Starts First) or 2 (Pump 2 Starts First). If PM.SL is 0  
(Automatic), the pump selection is based on two criteria: the  
alert status of a pump and the operational hours on the pump. If  
a pump has an active Alert condition, it will not be considered  
for the lead pump. The pump with the lowest operational hours  
will be the lead pump. A pump is selected by the control to start  
and continues to be the lead pump until the Pump Changeover  
Hours (ConfigurationOPT1PM.DT) is reached. The  
Lead Pump (Run StatusVIEWLD.PM) indicates the  
pump that has been selected as the lead pump: 1 (Pump 1), 2  
(Pump 2), 3 (No Pump). The Pump Changeover Hours is facto-  
ry defaulted to 500 hours. Regardless of the Cooler Pump Se-  
lection, any pump that has an active alert will not be allowed to  
start.  
With the dual integral pump package, the Cooler Pump  
Starter will be energized when the machine is in an occupied  
period. As part of the factory-installed package, an auxiliary set  
of contacts is wired to the MBB to serve as Chilled Water Pump  
Interlock, one set for each pump to individual channels on the  
MBB. With a call for mechanical cooling, the specific pump  
interlock and flow switch are checked. If the circuits are closed,  
the machine starts its capacity routine. If Pump 1 starts and the  
auxiliary contact interlock does not close within 25 seconds of  
the ON command, a T190 — Cooler Pump 1 Aux Contacts  
Failed to Close at Start-Up Alert will be generated and the  
pump shut down. The unit will not be allowed to start. If the  
chilled water flow switch does not close within 1 minute, two  
alarms will be generated. A T192 — Cooler Pump 1 Failed to  
Provide Flow at Start-Up Alert and an A200 — Cooler Flow/  
Interlock Failed to Close at Start-Up Alarm will be generated  
and chiller will not be allowed to start. In either fault case listed  
above, Pump 2 will be commanded to start once Pump 1 has  
failed.  
If Pump 2 starts and the auxiliary contact interlock does  
not close within 25 seconds of the ON command, a T191 —  
Cooler Pump 2 Aux Contacts Failed to Close at Start-Up Alert  
will be generated and the pump shut down. The unit will not be  
allowed to start. If the chilled water flow switch does not close  
within one (1) minute, two alarms will be generated. A T193  
— Cooler Pump 2 Failed to Provide Flow at Start-Up Alert and  
an A200 — Cooler Flow/Interlock Failed to Close at Start-Up  
Alarm will be generated and chiller will not be allowed to start.  
In either fault case listed above, Pump 1 will be commanded to  
start once Pump 2 has failed.  
If the chilled water flow switch opens for at least 3 seconds  
after initially being closed, a T196 — Flow Lost While Pump 1  
Running Alert or T197 — Flow Lost While Pump 2 Running  
Alert for the appropriate pump and an A201 — Cooler Flow/  
Interlock Contacts Opened During Normal Operation Alarm  
will be generated and the machine will stop. If available, the  
other pump will be started. If flow is proven, the machine will  
be allowed to restart.  
If the control starts a pump and the wrong interlock circuit  
closes for at least 20 seconds, an A189 – Cooler Pump and Aux  
Contact Input Miswire Alarm will be generated. The unit will  
be prevented from starting.  
The control will allow for pump changeover. Two methods  
will change the pump sequence. Before the changeover can  
occur, the unit must be at Capacity Stage 0. During changeover  
the chilled water flow switch input is ignored for 10 seconds to  
avoid a nuisance alarm.  
With Cooler Pump Select (ConfigurationOPT1  
PM.SL) set to 0 (Automatic) and when the differential time  
limit Pump Changeover Hours (ConfigurationOPT1  
PM.DT) is reached, the lead pump will be turned OFF. Ap-  
proximately one (1) second later, the lag pump will start. Manu-  
al changeover can be accomplished by changing Rotate Cooler  
Pump Now (ConfigurationOPT1ROT.P) to YES only if  
the machine is at Capacity Stage 0 and the differential time limit  
Pump Changeover Hours (PM.DT) is reached. If the PM.DT is  
not satisfied, the changeover will not occur. With the machine at  
Capacity Stage 0, the pumps would rotate automatically as part  
of the normal routine.  
With Cooler Pump Select (PM.SL) set to 1 (Pump 1 Starts  
First) or 2 (Pump 2 Starts First), a manual changeover can be ac-  
complished by changing PM.SL only. The machine Remote-  
Off-Enable Switch must be in the OFF position to change this  
variable. The Rotate Cooler Pump Now (ROT.P) feature does  
not work for these configuration options.  
As part of a pump maintenance routine, the pumps can be  
started to maintain lubrication to the pump seal. To utilize this  
function, Cooler Pmp Periodic Start (ConfigurationOPT1  
PM.PS) must be set to YES. This option is set to NO as the  
factory default. If feature is enabled and the pump(s) are not  
operating, then the pumps will be operated every other day for  
2 seconds starting at 14:00 hours. If a pump has failed and has  
an active Alert condition, it will not be started that day.  
Configuring and Operating Dual Chiller Con-  
trol — The dual chiller routine is available for the control of  
two units supplying chilled fluid on a common loop. This  
control algorithm is designed for parallel fluid flow arrangement  
only. One chiller must be configured as the master chiller, the  
other as the slave. An additional leaving fluid temperature  
thermistor (Dual Chiller LWT) must be installed as shown in  
Fig. 16 and 17 and connected to the master chiller. Refer to Sen-  
sors section, page 20, for wiring. The CCN communication bus  
must be connected between the two chillers. Connections can be  
made to the CCN screw terminals on LVT. Refer to Carrier  
Comfort Network® Interface section, page 19, for wiring infor-  
mation. Configuration examples are shown in Tables 22 and 23.  
Refer to Table 22 for dual chiller configuration. In this  
example the master chiller will be configured at address 1 and  
the slave chiller at address 2. The master and slave chillers  
must reside on the same CCN bus (ConfigurationCCN  
CCNB) but cannot have the same CCN address (Configu-  
rationCCNCCNA). Both master and slave chillers must  
have Lead/Lag Chiller Enable (ConfigurationRSET  
LLEN) configured to ENBL. Master/Slave Select (Config-  
urationRSET MSSL) must be configured to MAST for  
the master chiller and SLVE for the slave. Also in this example,  
the master chiller will be configured to use Lead/Lag Balance  
Select (ConfigurationRSETLLBL) and Lead/Lag Bal-  
ance Delta (ConfigurationRSETLLBD) to even out the  
chiller run-times weekly. The Lag Start Delay (Configura-  
tionRSETLLDY) feature will be set to 10 minutes. This  
will prevent the lag chiller from starting until the lead chiller  
has been at 100% capacity for the length of the delay time. Par-  
allel configuration (ConfigurationRSETPARA) can  
only be configured to YES. The variables LLBL, LLBD and  
LLDY are not used by the slave chiller.  
If the chilled water pump interlock opens for 25 seconds  
after initially being closed is detected by the control, the appro-  
priate T194 — Cooler Pump 1 Contacts Opened During Nor-  
mal Operation Alert or T195 — Cooler Pump 2 Contacts  
Opened During Normal Operation Alert is generated and the  
unit is shut down. If available, the other pump will be started. If  
flow is proven, the machine will be allowed to restart.  
If the control detects that the chilled water flow switch  
circuit is closed for at least 5 minutes with the pump output  
OFF, an A202 — Cooler Pump Interlock Closed When Pump  
is Off Alarm will be generated and the unit will not be allowed  
to start.  
If the control detects that the chilled water pump auxiliary  
contacts are closed for at least 25 seconds while the pump is  
OFF, the appropriate T198 — Cooler Pump 1 Aux Contacts  
Closed While Pump Off or Alert T199 — Cooler Pump 2 Aux  
Contacts Closed While Pump Off Alert is generated. The  
chiller will not be allowed to start.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 22 — Dual Chiller Configuration (Master Chiller Example)  
SUB-MODE  
DISP  
ITEM  
KEYPAD ENTRY  
DISPLAY  
ITEM EXPANSION  
COMMENTS  
UNIT  
OPT1  
ENTER  
ENTER  
ESCAPE  
CTRL  
0
CONTROL METHOD  
SWITCH  
OPT2  
CTRL  
DEFAULT 0  
OPT2  
CCN  
1
CCNA  
CCNB  
ENTER  
CCN ADDRESS  
DEFAULT 1  
DEFAULT 0  
CCNB  
0
CCN  
ENTER  
CCN BUS NUMBER  
ESCAPE  
CCN  
RSET  
CRST  
LLEN  
DSBL  
DSBL  
ENBL  
ENBL  
LLEN  
MSSL  
MAST  
MSSL  
SLVA  
0
PROCEED TO  
SUBMODE RESET  
ENTER  
COOLING RESET TYPE  
LEAD/LAG CHILLER ENABLE  
15 ITEMS  
SCROLLING STOPS  
VALUE FLASHES  
SELECT ENBL  
LLEN  
LLEN  
MSSL  
SLVA  
SLVA  
LLBL  
ENTER  
ENTER  
ENTER  
LEAD/LAG CHILLER ENABLE  
CHANGE ACCEPTED  
ESCAPE  
MASTER /SLAVE SELECT  
MASTER /SLAVE SELECT  
ENTER  
DEFAULT MAST  
ESCAPE  
RSET  
SLAVE ADDRESS  
ENTER  
ENTER  
SCROLLING STOPS  
VALUE FLASHES  
SELECT 2  
0
2
ENTER  
2
SLAVE ADDRESS  
CHANGE ACCEPTED  
ESCAPE  
SLVA  
LLBL  
0
LEAD/LAG BALANCE SELECT  
ENTER  
ENTER  
SCROLLING STOPS  
VALUE FLASHES  
0
2
SELECT 2 - Automatic  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 22 — Dual Chiller Configuration (Master Chiller Example) (cont)  
SUB-MODE  
ITEM  
KEYPAD ENTRY  
DISPLAY  
ITEM EXPANSION  
COMMENTS  
LLBL  
ENTER  
2
LEAD/LAG BALANCE SELECT  
CHANGE ACCEPTED  
ESCAPE  
LLBL  
LLBD  
168  
LLBD  
LLDY  
5
LEAD/LAG BALANCE DELTA  
LEAD/LAG BALANCE DELTA  
LLBD  
LLDY  
LLDY  
PARA  
ENTER  
DEFAULT 168  
ESCAPE  
LAG START DELAY  
RSET  
ENTER  
ENTER  
SCROLLING STOPS  
VALUE FLASHES  
SELECT 10  
5
10  
ENTER  
ESCAPE  
ESCAPE  
ENTER  
10  
LAG START DELAY  
CHANGE ACCEPTED  
LLDY  
RSET  
YES  
MASTER COMPLETE  
NOTES:  
1. Master Control Method (CTRL) can be configured as 0-Switch, 2-Occupancy or 3-CCN.  
2. Parallel Configuration (PARA) cannot be changed.  
Dual chiller start/stop control is determined by configura-  
tion of Control Method (ConfigurationOPT1CTRL) of  
the Master chiller. The Slave chiller should always be config-  
ured for CTRL=0 (Switch). If the chillers are to be controlled  
by Remote Contacts, both Master and Slave chillers should be  
enabled together. Two separate relays or one relay with  
two sets of contacts may control the chillers. The Enable/Off/  
Remote Contact switch should be in the Remote Contact  
position on both the Master and Slave chillers. The Enable/Off/  
Remote Contact switch should be in the Enable position for  
CTRL=2 (Occupancy) or CTRL=3 (CCN Control).  
DIMENSIONS in. (mm)  
PART  
NUMBER  
A
B
10HB50106801  
10HB50106802  
3.10 (78.7)  
4.10 (104.1)  
1.55 (39.4)  
1.28 (32.5)  
A
0.505/0.495  
0.61  
DIA  
B
Both chillers will stop if the Master chiller Enable/Off/  
Remote Contact switch is in the Off position. If the Emergency  
Stop switch is turned off or an alarm is generated on the Master  
chiller the Slave chiller will operate in a Stand-Alone mode.  
If the Emergency Stop switch is turned off or an alarm is  
generated on the Slave chiller the Master chiller will operate in  
a Stand-Alone mode.  
The master chiller controls the slave chiller by changing its  
Control Mode (Run StatusVIEWSTAT) and its operat-  
ing setpoint or Control Point (Run StatusVIEWCT.PT).  
6” MINIMUM  
CLEARANCE FOR  
THERMISTOR  
REMOVAL  
1/4 N.P.T.  
Fig. 17 — Dual Leaving Water Thermistor Well  
Temperature Reset — The control system is capable of  
handling leaving-fluid temperature reset based on return cooler  
fluid temperature. Because the change in temperature through  
the cooler is a measure of the building load, the return tempera-  
ture reset is in effect an average building load reset method.  
The control system is also capable of temperature reset based  
on outdoor-air temperature (OAT), space temperature (SPT), or  
from an externally powered 4 to 20 mA signal. Accessory sen-  
sors must be used for SPT reset (33ZCT55SPT). The energy  
management module (EMM) must be used for temperature  
reset using a 4 to 20 mA signal. See Tables 24 and 25.  
THERMISTOR  
WIRING*  
LEAVING  
FLUID  
MASTER  
CHILLER  
RETURN  
FLUID  
SLAVE  
CHILLER  
INSTALL DUAL CHILLER LWT  
LEAVING FLUID TEMPERATURE  
THERMISTOR (T10) HERE  
*Depending on piping sizes, use either:  
• HH79NZ014 sensor/10HB50106801 well (3-in. sensor/well)  
• HH79NZ029 sensor/10HB50106802 well (4-in. sensor/well)  
Fig. 16 — Dual Chiller Thermistor Location  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 23 — Dual Chiller Configuration (Slave Chiller Example)  
SUB-MODE  
DISP  
ITEM  
KEYPAD ENTRY  
DISPLAY  
ITEM EXPANSION  
COMMENTS  
UNIT  
OPT1  
ENTER  
CTRL  
0
CONTROL METHOD  
SWITCH  
OPT2  
CTRL  
DEFAULT 0  
ESCAPE  
OPT2  
CCN  
CCNA  
1
CCNA  
ENTER  
ENTER  
CCN ADDRESS  
SCROLLING STOPS  
VALUE FLASHES  
1
SELECT 2  
(SEE NOTE 1)  
2
CCN  
CCNA  
CCNB  
ENTER  
ESCAPE  
ENTER  
2
CCN ADDRESS  
CHANGE ACCEPTED  
CCN  
0
DEFAULT 0  
(SEE NOTE 2)  
CCN BUS NUMBER  
ESCAPE  
CCN  
RSET  
CRST  
LLEN  
DSBL  
DSBL  
ENBL  
ENBL  
LLEN  
MSSL  
MAST  
MAST  
SLVE  
SLVE  
MSSL  
RSET  
PROCEED TO  
SUBMODE RSET  
ENTER  
COOLING RESET TYPE  
LEAD/LAG CHILLER ENABLE  
15 ITEMS  
SCROLLING STOPS  
VALUE FLASHES  
SELECT ENBL  
LLEN  
LLEN  
MSSL  
MSSL  
ENTER  
ENTER  
ENTER  
LEAD/LAG CHILLER ENABLE  
MASTER /SLAVE SELECT  
CHANGE ACCEPTED  
ESCAPE  
RSET  
ENTER  
ENTER  
SCROLLING STOPS  
VALUE FLASHES  
SELECT SLVE  
ENTER  
ESCAPE  
ESCAPE  
MASTER /SLAVE SELECT  
CHANGE ACCEPTED  
SLAVE COMPLETE  
NOTES:  
1. Slave Control Method (CTRL) must be configured for 0.  
2. Slave CCN Address (CCNA) must be different than Master.  
3. Slave CCN Bus Number (CCNB) must be the same as Master  
4. Slave does not require SLVA, LLBL, LLBD, or LLDY to be configured.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 24 — 4 to 20 mA Reset  
KEYPAD  
ENTRY  
ITEM  
DISPLAY  
SUB-MODE  
RSET  
ITEM  
COMMENT  
EXPANSION  
0 = no reset  
1 = 4 to 20 mA input  
2 = Outdoor air temp  
3 = Return Fluid  
COOLING RESET  
ENTER  
CRST  
1
TYPE  
4 = Space Temperature  
5.0 F  
(2.8 C)  
DEGREES COOL  
RESET  
Default: 0° F (0° C) Reset at 20 mA  
Range: –30 to 30 F (–16.7 to 16.7 C)  
MA.DG  
NOTE: The example above shows how to configure the chiller for 4 to 20 mA reset. No reset will  
occur at 4.0 mA input, and a 5.0 F reset will occur at 20.0 mA. An EMM is required.  
Table 25 — Menu Configuration of 4 to 20 mA Cooling Set Point Control  
MODE  
(RED LED)  
KEYPAD  
ENTRY  
KEYPAD  
ENTRY  
ITEM  
EXPANSION  
SUB-MODE  
DISP  
ITEM  
DISPLAY  
COMMENT  
ENTER  
UNIT  
OPT1  
OPT2  
HP.A  
HP.B  
EXV.A  
EXV.B  
M.MST  
RSET  
DMDC  
SLCT  
CONFIGURATION  
ENTER  
ENTER  
ENTER  
CLSP  
0
0
0
4
4
COOLING SETPOINT SELECT  
Scrolling Stops  
Flashing ‘0’  
Select ‘4’  
ENTER  
Change Accepted  
be configured for the type of reset desired. The variable  
RM.NO should be set to the temperature that no reset should  
occur. The variable RM.F should be set to the temperature that  
maximum reset is to occur. The variable RM.DG should be set  
to the maximum amount of reset desired. Figures 18 and 19 are  
examples of outdoor air and space temperature resets.  
To use return reset, four variables must be configured. In the  
Configuration mode under the sub-mode RSET, items CRST,  
RT.NO, RT.F and RT.DG must be properly set. See Table 26B  
— Configuring Return Temperature Reset. This example pro-  
vides 5.0 F (2.8 C) chilled water set point reset at 2.0 F (1.1 C)  
cooler T and 0° F (0° C) reset at 10.0 F (5.6 C) cooler T. The  
variable RT.NO should be set to the cooler temperature differ-  
ence (T) where no chilled water temperature reset should oc-  
cur. The variable RT.F should be set to the cooler temperature  
difference where the maximum chilled water temperature reset  
should occur. The variable RM.DG should be set to the maxi-  
mum amount of reset desired.  
IMPORTANT: Care should be taken when interfacing with  
other control systems due to possible power supply differ-  
ences: full wave bridge versus half wave rectification. Con-  
nection of control devices with different power supplies  
may result in permanent damage. ComfortLink™ controls  
incorporate power supplies with half wave rectification. A  
signal isolation device should be utilized if the signal gen-  
erator incorporates a full wave bridge rectifier.  
To use outdoor air or space temperature reset, four variables  
must be configured. In the Configuration mode under the sub-  
mode RSET, items (ConfigurationOPT1CRST), (Con-  
figurationOPT1RM.NO),  
(ConfigurationOPT1  
RM.F), and (ConfigurationOPT1RT.DG) must be  
properly set. See Table 26A — Configuring Outdoor Air and  
Space Temperature Reset. The outdoor air reset example pro-  
vides 0° F (0° C) chilled water set point reset at 85.0 F (29.4 C)  
outdoor-air temperature and 15.0 F (8.3 C) reset at 55.0 F  
(12.8 C) outdoor-air temperature. The space temperature reset  
example provides 0° F (0° C) chilled water set point reset at  
72.0 F (22.2 C) space temperature and 6.0 F (3.3 C) reset at  
68.0 F (20.0 C) space temperature. The variable CRST should  
To verify that reset is functioning correctly proceed to Run  
Status mode, sub-mode VIEW, and subtract the active set point  
(Run StatusVIEWSETP) from the control point (Run  
StatusVIEWCTPT) to determine the degrees reset.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 26A — Configuring Outdoor Air and Space Temperature Reset  
DISPLAY  
MODE  
(RED LED)  
KEYPAD  
ENTRY  
SUB-  
MODE  
KEYPAD  
ENTRY  
ITEM  
EXPANSION  
ITEM  
COMMENT  
Outdoor  
Air  
Space  
ENTER  
DISP  
UNIT  
OPT1  
OPT2  
HP.A  
HP.B  
EXV.A  
EXV.B  
M.MST  
CONFIGURATION  
2 = Outdoor-Air Temperature  
4 = Space Temperature  
(Connect to TB5-5,6)  
COOLING RESET  
TYPE  
RSET  
CRST  
2
4
ENTER  
REMOTE - NO  
RESET TEMP  
Default: 125.0 F (51.7 C)  
Range: 0° to125 F  
RM.NO*  
RM.F  
85 °F  
55 °F  
72 °F  
68 °F  
REMOTE - FULL  
RESET TEMP  
Default: 0.0° F (-17.7 C)  
Range: 0° to 125 F  
Default: 0° F (0° C)  
Range: –30 to 30 F  
(–34.4 to -1.1 °C)  
REMOTE - DEGREES  
RESET  
RM.DG  
15 °F  
6 °F  
*4 items skipped in this example.  
Table 26B — Configuring Return Temperature Reset  
MODE  
(RED LED)  
KEYPAD  
ENTRY  
KEYPAD  
ENTRY  
ITEM  
SUB-MODE  
DISP  
ITEM DISPLAY  
COMMENT  
EXPANSION  
ENTER  
ENTER  
ENTER  
ENTER  
ENTER  
TEST  
TYPE  
FLUD  
CTRL  
ON/OFF  
TEST DISPLAY LEDs  
UNIT TYPE  
UNIT  
X
X
X
OPT1  
OPT2  
HP.A  
COOLER FLUID  
CONTROL METHOD  
HP.B  
EXV.A  
EXV.B  
M.MST  
CONFIGURATION  
0 = No Reset  
1 = 4 to 20 mA Input (EMM required)  
(Connect to EMM TB6-2,3)  
RSET  
CRST  
3
COOLING RESET TYPE 2 = Outdoor-Air Temperature  
3 = Return Fluid  
ENTER  
4 = Space Temperature  
(Connect to TB5-5,6)  
RETURN FLUID - NO  
RESET TEMP  
Default: 10.0 F (5.6 C)  
Range: 0° to10 F COOLER T  
RT.NO* 10.0 F  
RETURN FLUID - FULL Default: 0 F (–17.8 C)  
RT.F  
0.0 F  
RESET TEMP  
Range: 0° to 30 F COOLER T  
RETURN - DEGREES  
RESET  
Default: 0 F (0 C)  
Range: –30 to 30°F (–16.7 to 16.7 C)  
RT.DG  
10.0 F  
*4 items skipped in this example.  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Under normal operation, the chiller will maintain a constant  
leaving fluid temperature approximately equal to the chilled  
fluid set point. As the cooler load varies, the entering cooler  
fluid will change in proportion to the load as shown in Fig. 20.  
Usually the chiller size and leaving-fluid temperature set point  
are selected based on a full-load condition. At part load, the flu-  
id temperature set point may be colder than required. If the  
leaving fluid temperature was allowed to increase at part load,  
the efficiency of the machine would increase.  
Return temperature reset allows for the leaving temperature  
set point to be reset upward as a function of the return fluid  
temperature or, in effect, the building load.  
Demand Limit — Demand limit is a feature that allows  
the unit capacity to be limited during periods of peak energy us-  
age. There are 3 types of demand limiting that can be config-  
ured. The first type is through 2-stage switch control, which will  
reduce the maximum capacity to 2 user-configurable percentag-  
es. The second type is by 4 to 20 mA signal input which will re-  
duce the maximum capacity linearly between 100% at a 4 mA  
input signal (no reduction) down to the user-configurable level  
at a 20 mA input signal. The third type uses the CCN Loadshed  
module and has the ability to limit the current operating capaci-  
ty to maximum and further reduce the capacity if required.  
LEGEND  
EWT — Entering Water (Fluid) Temperature  
LWT  
Leaving Water (Fluid) Temperature  
Fig. 20 — Standard Chilled Fluid  
Temperature Control — No Reset  
To use demand limit, select the type of demand limiting to  
use. Then configure the demand limit set points based on the  
type selected.  
NOTE: The 2-stage switch control and 4 to 20-mA input sig-  
nal types of demand limiting require the energy management  
module (EMM).  
DEMAND LIMIT (2-Stage Switch Controlled) — To con-  
figure demand limit for 2-stage switch control set the Demand  
Limit Select (ConfigurationRSETDMDC) to 1. Then  
configure the 2 Demand Limit Switch points (Configura-  
tionRSETDLS1) and (ConfigurationRSETDLS2)  
to the desired capacity limit. See Table 27. Capacity steps are  
controlled by 2 relay switch inputs field wired to TB6 as shown  
in Fig. 6 and 7.  
For demand limit by 2-stage switch control, closing the first  
stage demand limit contact will put the unit on the first demand  
limit level. The unit will not exceed the percentage of capacity  
entered as Demand Limit Switch 1 set point (DLS1). Closing  
contacts on the second demand limit switch prevents the unit  
from exceeding the capacity entered as Demand Limit Switch  
2 set point. The demand limit stage that is set to the lowest de-  
mand takes priority if both demand limit inputs are closed. If  
the demand limit percentage does not match unit staging, the  
unit will limit capacity to the closest capacity stage.  
LEGEND  
To disable demand limit configure DMDC to 0. See  
Table 27.  
LWT — Leaving Water (Fluid) Temperature  
Fig. 18 — Outdoor-Air Temperature Reset  
EXTERNALLY POWERED DEMAND LIMIT (4 to  
20 mA Controlled) — To configure demand limit for 4 to 20  
mA control set the Demand Limit Select (Configura-  
tionRSETDMDC) to 2. Then configure the Demand  
Limit at 20 mA (ConfigurationRSETDM20) to the  
maximum loadshed value desired. Connect the output from an  
externally powered 4 to 20 mA signal to terminal block TB6,  
terminals 1 and 5. Refer to the unit wiring diagram for these  
connections to the optional/accessory energy management  
module and terminal block. The control will reduce allowable  
capacity to this level for the 20 mA signal. See Table 27 and  
Fig. 21.  
CAUTION  
Care should be taken when interfacing with other manufac-  
turer’s control systems, due to possible power supply  
differences, full wave bridge versus half wave rectification.  
The two different power supplies cannot be mixed.  
ComfortLink™ controls use half wave rectification. A sig-  
nal isolation device should be utilized if a full wave bridge  
signal generating device is used.  
LEGEND  
LWT — Leaving Water (Fluid) Temperature  
Fig. 19 — Space Temperature Reset  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DEMAND LIMIT (CCN Loadshed Controlled) — To con-  
figure Demand Limit for CCN Loadshed control set the De-  
mand Limit Select (ConfigurationRSETDMDC) to 3.  
Then configure the Loadshed Group Number (Configura-  
tionRSETSHNM), Loadshed Demand Delta (Configu-  
rationRSETSHDL), and Maximum Loadshed Time  
(ConfigurationRSETSHTM). See Table 27.  
The Loadshed Group number is established by the CCN  
system designer. The ComfortLink controls will respond to a  
Redline command from the Loadshed control. When the  
Redline command is received, the current stage of capacity is  
set to the maximum stages available. Should the loadshed con-  
trol send a Loadshed command, the ComfortLink controls will  
reduce the current stages by the value entered for Loadshed  
Demand delta. The Maximum Loadshed Time is the maximum  
length of time that a loadshed condition is allowed to exist. The  
control will disable the Redline/Loadshed command if no  
Cancel command has been received within the configured  
maximum loadshed time limit.  
Cooling Set Point (4 to 20 mA) — A field supplied  
and generated, externally powered 4 to 20 mA signal can be  
used to provide the leaving fluid temperature set point. Connect  
the signal to LVT7,8 (+,–). See Table 27 for instructions to  
enable the function. Figure 22 shows how the 4 to 20 mA sig-  
nal is linearly calculated on an overall 10 F to 80 F range for  
fluid types (ConfigurationOPT1FLUD) 1 or 2. The set  
point will be limited by the fluid (FLUD) type. Be sure that the  
chilled water loop is protected at the lowest temperature.  
100  
50% CAPACITY AT 20 mA  
80  
60  
100% CAPACITY AT 4 mA  
40  
75% CAPACITY AT 12 mA  
20  
0
0
2
6
8
12  
16  
18  
4
20  
10  
14  
DEMAND LIMIT SIGNAL – 4 - 20 mA INPUT  
Fig. 21 — 4 to 20-mA Demand Limiting  
100  
(38)  
90  
(32)  
80  
(27)  
70  
(21)  
MAXIMUM  
SET POINT  
70 F (21.1 C)  
60  
(15)  
50  
(10)  
40  
(4.4)  
(FLUD = 1) MINIMUM  
SET POINT 38 F (3.3 C)  
30  
(-1)  
20  
(-7)  
(FLUD = 2) MINIMUM  
SET POINT 14 F (-10 C)  
10  
(-12)  
0
(-17)  
4
6.3  
8.6  
10.9  
13.1  
15.4  
17.7  
20  
4 TO 20 mA SIGNAL TO EMM  
EMM — Energy Management Module  
Fig. 22 — Cooling Set Point (4 to 20 mA)  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 27 — Configuring Demand Limit  
KEYPAD  
ENTRY  
KEYPAD  
MODE  
SUB-MODE  
DISP  
ITEM  
TEST  
TYPE  
FLUD  
CTRL  
DISPLAY  
ITEM EXPANSION  
Test Display LEDs  
Unit Type  
COMMENT  
ENTRY  
CONFIGURATION  
ENTER  
ENTER  
ON/OFF  
ENTER  
ENTER  
ENTER  
UNIT  
X
X
X
OPT1  
Cooler Fluid  
OPT2  
Control Method  
HP.A  
HP.B  
EXV.A  
EXV.B  
M.MST  
RSET  
ENTER  
CRST  
X
X
Cooling Reset Type  
Demand Limit Select  
Demand Limit at 20 mA  
Default: 0  
0 = None  
DMDC*  
1 = Switch  
2 = 4 to 20 mA Input  
3 = CCN Loadshed  
Default: 100%  
Range: 0 to 100  
DM20  
SHNM  
SHDL  
SHTM  
DLS1  
DLS2  
XXX %  
XXX  
Loadshed Group  
Number  
Default: 0  
Range: 0 to 99  
Loadshed Demand  
Delta  
Default: 0%  
Range: 0 to 60%  
XXX%  
XXX MIN  
XXX %  
XXX %  
Maximum Loadshed  
Time  
Default: 60 min.  
Range: 0 to 120 min.  
Demand Limit  
Switch 1  
Default: 80%  
Range: 0 to 100%  
Demand Limit  
Switch 2  
Default: 50%  
Range: 0 to 100%  
*Seven items skipped in this example.  
(DTT) is installed along with the AUX board for control of the  
DUS.  
Digital Scroll Option — The 30RAP units have a  
factory-installed option for a digital scroll compressor which  
provides additional stages of unloading for the unit. The digital  
compressor is always installed in the A1 compressor location.  
When a digital compressor is installed, a digital unloader sole-  
noid (DUS) is used on the digital compressor.  
DIGITAL SCROLL OPERATION — A digital scroll oper-  
ates in two stages - the "loaded state" when the solenoid valve  
is normally closed and the "unloaded state" when the solenoid  
valve is open. During the loaded state, the compressor operates  
like a standard scroll and delivers full capacity and mass flow.  
DIGITAL COMPRESSOR CONFIGURATION — When a  
digital compressor is installed, the configuration parameter  
(ConfigurationUNITA1TY) is configured to YES.  
There is also a maximum unload time configuration, (Config-  
urationUNITMAX.T) that is set to 7 seconds, which in-  
dicates the maximum unloading for the digital compressor is  
47%. This is done to optimize efficiency of the system.  
PRE-START-UP  
However, during the unloaded state, there is no capacity  
and no mass flow through the compressor. The capacity of the  
system is varied by varying the time the compressor operates  
in an unloaded and loaded state during a 15-second period. If  
the DUS is energized for 7 seconds, the compressor will be  
operating at 47% capacity. If the DUS is energized for 10 sec-  
onds, the compressor will be operating at approximately 33%  
of its capacity. Capacity is the time averaged summation of  
loaded and unloaded states, and its range is continuous from  
the minimum configured capacity to 100%. Regardless of  
capacity, the compressor always rotates with constant speed.  
As the compressor transitions from a loaded to unloaded state,  
the discharge and suction pressures will fluctuate and the com-  
pressor sound will change.  
IMPORTANT: Before beginning Pre-Start-Up or Start-Up,  
complete Start-Up Checklist for 30RAP Liquid Chiller at  
end of this publication (pages CL-1 to CL-10). The check-  
list assures proper start-up of a unit, and provides a record  
of unit condition, application requirements, system infor-  
mation, and operation at initial start-up.  
Do not attempt to start the chiller until following checks  
have been completed.  
System Check  
1. Check all auxiliary components, such as chilled fluid  
pumps, air-handling equipment, or other equipment to  
which the chiller supplies liquid. Consult manufacturer's  
instructions. Verify that any pump interlock contacts have  
been properly installed. If the unit If the unit has  
field-installed accessories, be sure all are properly in-  
stalled and wired correctly. Refer to unit wiring diagrams.  
The ComfortLink controller controls and integrates the op-  
eration of the DUS into the compressor staging routine to  
maintain temperature control. When a digital compressor is in-  
stalled, an additional discharge gas temperature thermistor  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Use the scrolling marquee display to adjust the Cooling  
Set Point.  
START-UP AND OPERATION  
NOTE: Refer to Start-Up Checklist on pages CL-1 to CL-10.  
3. Fill chilled fluid circuit with clean water (with recom-  
mended inhibitor added) or other non-corrosive fluid to  
be cooled. Bleed all air out of the high points of the sys-  
tem. If chilled water is to be maintained at a temperature  
below 40 F (4.4 C) or outdoor temperatures are expected  
to be below 32 F (0° C), a brine of sufficient concentra-  
tion must be used to prevent freeze-up at anticipated  
suction temperatures. See Table 28.  
Actual Start-Up — Actual start-up should be done only  
under supervision of a qualified refrigeration mechanic.  
1. Be sure all service valves are open.  
2. Using the scrolling marquee display, set leaving-fluid set  
point (Set PointsCOOLCSP.1). No cooling range  
adjustment is necessary.  
3. Start chilled fluid pump (if not configured for cooler  
pump control).  
4. Check tightness of all electrical connections.  
5. Oil should be visible in the compressor sightglass(es).  
See Fig. 23. An acceptable oil level in the compressors is  
4. Turn ENABLE/OFF/REMOTE CONTACT switch to  
ENABLE position.  
1
3
from /8 to /8 of sight glass. Adjust the oil level as re-  
quired. See Oil Charge section on page 50 for Carrier ap-  
proved oils.  
5. Allow unit to operate and confirm that everything is func-  
tioning properly. Check to see that leaving fluid tempera-  
ture agrees with leaving set point (Set PointsCOOL  
CSP.1) or (Set PointsCOOLCSP.2), or if reset is  
used, with the control point (Run StatusVIEW  
CTPT).  
6. Check the cooler leaving chilled water temperature to see  
that it remains well above 32 F (0° C), or the brine freez-  
ing point if the unit is a medium temperature brine unit.  
6. Electrical power source must agree with unit nameplate.  
7. All condenser fan and factory installed hydronic package  
pump motors are three phase. Check for proper rotation  
of condenser fans first BEFORE attempting to start  
pumps or compressors. To reverse rotation, interchange  
any two of the main incoming power leads.  
8. Be sure system is fully charged with refrigerant (see  
Check Refrigerant Charge section on this page).  
7. Recheck compressor oil level (see Oil Charge section).  
9. If unit is a brine unit, check to ensure proper brine con-  
centration is used to prevent freezing.  
Check Refrigerant Charge — All 30RAP units are  
shipped with a complete operating charge of R-410A and  
should be under sufficient pressure to conduct a leak test after  
installation. If there is no system pressure, admit nitrogen until  
a pressure is observed and then proceed to test for leaks. After  
leaks are repaired, the system must be dehydrated.  
10. Verify proper operation of cooler and hydronic package  
heaters (if installed). Heaters operate at the same voltage  
as the main incoming power supply and are single phase.  
Heater current is approximately 0.4 amps for 460 and  
575 v units. Heater current is approximately 0.8 amps for  
230 v units.  
All refrigerant charging should be done through the ¼-in.  
Schraeder connection on the liquid line. Do NOT add refriger-  
ant charge through the low-pressure side of the system. If com-  
plete charging is required, weigh in the appropriate charge for  
the circuit as shown on the unit nameplate. If partial charging is  
required, operate circuit at full load and use an accurate tem-  
perature sensor on the liquid line as it enters the EXV. Use the  
Temperatures mode on the scrolling marquee display to show  
the circuit saturated condensing temperature (Tempera-  
a30-4978  
turesCIR.ASCT.A)  
or  
(TemperaturesCIR.B  
SCT.B). Charging is most accurate at saturated discharge  
temperatures of 120 to 125 F (49 to 52 C). Block condenser air-  
flow as required to reach this temperature range. Add refriger-  
ant until the system subcooling (SCT.A or SCT.B minus liquid  
line temperature entering EXV) is approximately 15 to 17 F  
(–9.4 to –8.3 C). Refrigerant VAPOR only may be added to a  
circuit through the 1/4-in. suction Schraeder connection on the  
suction line.  
OIL SIGHTGLASS  
Fig. 23 — Sight Glass Location  
Table 28 — Minimum Cooler Flow Rates and Minimum Loop Volume  
30RAP  
SIZE  
MINIMUM COOLER FLOW MAXIMUM COOLER FLOW MINIMUM COOLER FLOW MAXIMUM COOLER FLOW  
RATE (gpm)  
RATE (gpm)  
50  
RATE (l/s)  
0.8  
RATE (l/s)  
3.2  
010  
015  
018  
020  
025  
030  
035  
040  
045  
050  
055  
060  
13  
17  
20  
23  
28  
33  
41  
47  
53  
57  
63  
68  
66  
78  
91  
1.1  
1.3  
1.5  
1.8  
2.1  
2.6  
3.0  
3.3  
4.2  
4.9  
5.7  
7.1  
112  
133  
164  
186  
209  
228  
251  
270  
8.4  
10.3  
11.7  
13.2  
14.4  
15.8  
17.0  
3.6  
4.0  
4.3  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unbalanced 3-Phase Supply Voltage — Never operate a motor  
where a phase imbalance between phases is greater than 2%.  
To determine percent voltage imbalance:  
CAUTION  
max voltage deviation  
Never charge liquid into low-pressure side of system. Do  
not overcharge. Overcharging results in higher discharge  
pressure, possible compressor damage, and higher power  
consumption. During charging or removal of refrigerant, be  
sure water is continuously circulating through the cooler to  
prevent freezing.  
from avg voltage  
% Voltage Imbalance = 100 x  
average voltage  
The maximum voltage deviation is the largest difference  
between a voltage measurement across 2 legs and the average  
across all 3 legs.  
Example: Supply voltage is 240-3-60.  
AB = 243 v  
Operating Limitations  
TEMPERATURES (See Table 29 for 30RAP standard tem-  
perature limits).  
BC = 236 v  
AC = 238 v  
CAUTION  
1. Determine average voltage:  
Do not operate with cooler leaving chiller water (fluid)  
temperature (LCWT) below 40 F (4.4 C) for the standard  
units, or below 15 F (–9.4 C) for units factory built for  
medium temperature brine.  
243 + 236 + 238  
Averagevoltage =  
3
717  
=
3
High Cooler Leaving Chilled Water (Fluid) Temperatures  
(LCWT) — During start-up with cooler LCWT above approx-  
imately 60 F (16 C), the unit expansion valve will limit suction  
pressure to approximately 90 psig (620 kPa) to avoid overload-  
ing the compressor.  
Low Cooler LCWT — For standard units, the LCWT must be  
no lower than 40 F (4.4 C). If the unit is the factory-installed  
optional medium temperature brine unit, the cooler LCWT can  
go down to 15 F (–9.4 C).  
= 239  
2. Determine maximum deviation from average voltage:  
(AB) 243 – 239 = 4 v  
(BC) 239 – 236 = 3 v  
(AC) 239 – 238 = 1 v  
Maximum deviation is 4 v.  
3. Determine percent voltage imbalance:  
Table 29 — Temperature Limits for  
Standard 30RAP Units  
4
% Voltage Imbalance = 100 x  
239  
UNIT SIZE 30RA  
Temperature  
010-030  
035-060  
= 1.7%  
F
C
F
C
This voltage imbalance is satisfactory as it is below the  
maximum allowable of 2%.  
Maximum Ambient  
Temperature  
Minimum Ambient  
Temperature  
Maximum Cooler EWT*  
Maximum Cooler LWT  
Minimum Cooler LWT†  
120  
45  
49  
120  
32  
49  
7
0
IMPORTANT: If the supply voltage phase imbalance is  
more than 2%, contact your local electric utility company  
immediately. Do not operate unit until imbalance condition  
is corrected.  
95  
70  
40  
35  
21  
4.4  
95  
70  
40  
35  
21  
4.4  
LEGEND  
Entering Fluid (Water) Temperature  
LWT — Leaving Fluid (Water) Temperature  
Control Circuit Power — Power for the control circuit is  
supplied from the main incoming power through a factory-  
installed control power transformer (TRAN1) for all models.  
Field wiring connections are made to the LVT.  
EWT  
*For sustained operation, EWT should not exceed 85 F (29.4 C).  
†Unit requires modification below this temperature.  
LOW-AMBIENT OPERATION — If operating temperatures  
below 45 F (7 C) on size 018-030 units, and 32 F (0° C) on size  
035-060 units are expected, accessory Motormaster® V con-  
trol must be installed. Operating temperatures can go as low as  
–20 F (–29 C) on size 010 and 015 units, as standard. Installa-  
tion of wind baffles is also required. Refer to separate installa-  
tion instructions for operation using this accessory. Contact  
your Carrier representative for details.  
OPERATION SEQUENCE  
During unit off cycle, the control monitors the outdoor air  
temperature. If the ambient temperature drops below 40 F  
(4.4 C), cooler and hydronic system heaters (if either are facto-  
ry installed) are energized. If power is maintained to the chiller  
and the EMERGENCY ON/OFF switch is left in the OFF po-  
sition, these heaters are also energized.  
The unit is started by putting the ENABLE/OFF/REMOTE  
CONTACT switch in the ENABLE or REMOTE CONTACT  
position. When the unit receives a call for cooling (either from  
the internal control or CCN network command or remote con-  
tact closure), the unit stages up in capacity to maintain the leav-  
ing fluid set point. The first compressor starts 11/2 to 3 minutes  
after the call for cooling.  
CAUTION  
Brine duty application (below 40 F [4.4 C] LCWT) for  
chiller normally requires factory modification. Contact  
your Carrier representative for applicable LCWT range for  
standard water-cooled chiller in a specific application.  
The lead circuit can be specifically designated on all models  
or selected based on compressor run hours and starts depend-  
ing on field configuration. The unit control will override this  
selection under certain starting conditions to properly maintain  
oil return to the compressors. In general, on dual compressor  
VOLTAGE — ALL UNITS  
Main Power Supply — Minimum and maximum acceptable  
supply voltages are listed in the Installation Instructions.  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
circuits, the control will most often start the A1 or B1 compres-  
sor first, especially after long off periods. The MBB controls  
fan stages to maintain the head pressure set point and will auto-  
matically adjust unit capacity as required to keep compressors  
from operating outside of the specified envelope. There are no  
pumpout or pumpdown sequences on these chillers.  
For all units, if temperature reset is being used, the unit con-  
trols to a higher leaving-fluid temperature as the building load  
reduces. If demand limit is used, the unit may temporarily be  
unable to maintain the desired leaving-fluid temperature be-  
cause of imposed power limitations.  
determines the saturated temperature of suction gas. The differ-  
ence between the temperature of the superheated gas and the  
saturated suction temperature is the superheat. The EXV board  
controls the position of the electronic expansion valve stepper  
motor to maintain superheat set point.  
The MBB controls the superheat leaving cooler to approxi-  
mately 9° F (5° C). Because EXV status is communicated to  
the main base board (MBB) and is controlled by the EXV  
boards, it is possible to track the valve position. The unit is then  
protected against loss of charge and a faulty valve. Just prior to  
compressor start, the EXV will open. At low ambient tempera-  
tures the EXV is closed at start up. After initialization period,  
valve position is tracked by the EXV board by constantly mon-  
itoring the amount of valve movement.  
SERVICE  
The EXV is also used to limit cooler saturated suction tem-  
perature to 50 F (10 C). This makes it possible for the chiller to  
start at higher cooler fluid temperatures without overloading  
the compressor. This is commonly referred to as MOP (maxi-  
mum operating pressure). At ambient temperatures above  
110 F, MOP is bypassed at start-up to prevent charge backup in  
the condenser.  
WARNING  
Electrical shock can cause personal injury and death. Shut  
off all power to this equipment during service. There may  
be more than one disconnect switch. Tag all disconnect  
locations to alert others not to restore power until work is  
completed.  
If it appears that the EXV module is not properly control-  
ling circuit operation to maintain correct superheat, there are a  
number of checks that can be made using test functions and  
initialization features built into the microprocessor control. See  
the EXV Troubleshooting Procedure section to test EXVs.  
Electronic Components  
CONTROL COMPONENTS — Unit uses an advanced elec-  
tronic control system that normally does not require service.  
For details on controls refer to Operating Data section.  
Access to the compressors is through latched panels from  
beneath the control box on all models or from opposite the coil  
side (sizes 010-030 only). The front door(s) provide access to  
the compressor(s) and all components of the refrigeration sys-  
tem. For size 010-030 units, access to the controls is through  
the upper latched outer door above the compressor access door.  
Similarly, the upper center latched door on sizes 035-060 gives  
access to the controls. Inner panels are secured in place and  
should not be removed unless all power to the chiller is off.  
EXV Troubleshooting Procedure — Follow steps  
below to diagnose and correct EXV/economizer problems.  
Check EXV motor operation first. Switch the Enable/Off/  
ESCAPE  
Remote Contact (EOR) switch to the Off position. Press  
on the Navigator™ display until ‘Select a menu item’ appears  
on the display. Use the arrow keys to select the Service Test  
ENTER  
mode. Press  
. The display will be:  
> TEST  
OFF  
Electronic Expansion Valve (EXV) — See Fig. 24  
for a cutaway view of the EXV. High-pressure liquid refriger-  
ant enters valve through the top. As refrigerant passes through  
the orifice, pressure drops and refrigerant changes to a 2-phase  
condition (liquid and vapor). The electronic expansion valve  
operates through an electronically controlled activation of a  
stepper motor. The stepper motor stays in position, unless  
power pulses initiate the two discrete sets of motor stator wind-  
ings for rotation in either direction. The direction depends on  
the phase relationship of the power pulses.  
The motor directly operates the spindle, which has rotating  
movements that are transformed into linear motion by the  
transmission in the cage assembly. The valve includes a posi-  
tive shut-off when closed.  
OUTS  
COMP  
ENTER  
Press  
(password entry may be required) and use  
to change ‘OFF’ to ‘ON’. Switch the EOR switch to  
Enable. The Service Test mode is now enabled. Move the  
pointer down to the OUTS sub-mode and press  
ENTER  
. Move the  
ENTER  
pointer to item EXV.A or EXV.B as needed. Press  
and  
the valve position will flash. Use  
position (hold  
to select 100% valve  
ENTER  
for quick movement) and press  
.
The technician should be able to feel the actuator moving by  
placing a hand on the EXV. A sight glass is located on the valve  
body to verify that the sleeve is moving to expose/cover slots in  
the orifice. A hard knocking should be felt from the actuator  
when it reaches the top of its stroke (can be heard if surround-  
ings are relatively quiet). Press  
There are two different EXVs. See Table 30 for number of  
steps. The EXV motor moves at 200 steps per second. Com-  
manding the valve to either 0% or 100% will add extra steps to  
the move, to ensure the value is open or closed completely.  
ENTER  
again twice if necessary to  
ENTER  
confirm this. To close the valve, press  
, select 0% with  
Table 30 — EXV Steps  
ENTER  
and press  
. The actuator should knock when it reaches  
UNIT SIZE 30RAP  
010-020  
EXV STEPS  
1596  
the bottom of its stroke. If it is believed that the valve is not  
working properly, continue with the checkout procedure  
below:  
025,030  
2500  
035-045  
1596  
050-060  
2500  
Check the EXV output signals at appropriate terminals on  
the EXV module (see Fig. 25). Connect positive test lead to red  
wire (EXV-J6 terminal 3 for Circuit A, EXV-J7 terminal 3 for  
Circuit B). Set meter to approximately 20 vdc. Using the  
Service Test procedure above, move the valve output under test  
to 100%. DO NOT short meter leads together or pin 3 to any  
other pin as board damage will occur.  
The EXV board controls the valve. Each circuit has a  
thermistor located in a well in the suction manifold before the  
compressor. Suction pressure as measured by the suction pres-  
sure transducer is converted to a saturated suction temperature.  
The thermistor measures the temperature of the superheated  
gas entering the compressor and the pressure transducer  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INCLUDED IN CABLE KIT  
CABLE  
CABLE  
CABLE RETAINER  
MOTOR AND  
ADAPTER  
ASSEMBLY  
MOTOR ADAPTER  
ASSEMBLY  
CABLE  
RETAINER  
GASKET  
MOTOR ADAPTER  
ASSEMBLY  
SIGHTGLASS  
SPORLAN  
FLOW  
DIRECTION  
NORMAL  
FLOW  
DIRECTION  
a30-4971  
Fig. 24 — Electronic Expansion Valve Details  
During the next several seconds, carefully connect the nega-  
tive test lead to pins 1,2,4 and 5 in succession (plug J6 for Cir-  
cuit A, plug J7 for Circuit B). Digital voltmeters will average  
this signal and display approximately 6 vdc. If it remains con-  
stant at a voltage other than 6 VDC or shows 0 volts, remove  
the connector to the valve and recheck.  
FIELD SERVICING INSTRUCTIONS — The EXV valves  
on sizes 025, 030, 050-060 can be serviced. The EXV valves  
on all other sizes are hermetic and cannot be disassembled for  
installation or during service, however, the cable and retainer  
may be replaced if necessary. Motor kits for the EXV valve are  
available as replacement parts.  
To remove the valve from the system, perform the follow-  
ing procedure:  
1. Be sure the refrigerant has been recovered from the  
circuit.  
2. Disconnect the line voltage to the valve controller. Dis-  
connect the valve wires from the controller.  
3. If the motor fails to operate properly, check the resistance  
of each motor phase. Resistance between black and white  
leads or between the red and green leads should be ap-  
proximately 100 ohms. Differences of more than 10% be-  
tween phases indicate a defective motor. Resistance be-  
tween black and red, or any lead and piping, should be in-  
finite or “open”. Any resistance reading will indicate a  
shorted winding and the valve will need to be replaced.  
ENTER  
Press  
and select 0% to close the valve. Check the 4 po-  
sition DIP switch on the board (all switches should be set to  
On). If a problem still exists, replace the EXV module. If the  
reading is correct, the expansion valve and EXV wiring should  
be checked. Check the EXV terminal strip and interconnecting  
wiring.  
1. Check color coding and wire connections. Make sure  
they are connected to the correct terminals at the EXV  
driver and EXV plug and that the cables are not crossed.  
2. Check for continuity and tight connection at all pin  
terminals.  
3. Check the resistance of the EXV motor windings. Re-  
move the EXV module plug (J6 for Circuit A, J7 for Cir-  
cuit B) and check the resistance of the two windings be-  
tween pins 1 and 2 for one winding and pins 4 and 5 for  
the other winding (see Fig. 25). The resistance should be  
100 ohms ± 10 ohms.  
4. The output of the controller to the valve can be tested  
with the following procedure:  
a. Disconnect supply voltage to the controller.  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION  
BLK  
WHT  
If the existing motor has been removed for inspection or  
cleaning, be sure that the piston is fully retracted into the  
motor assembly before installation on the valve. Failure to  
do so will permanently damage the drive and motor.  
Replacement motor assemblies are shipped in the retracted  
position and may be installed as received.  
GRN  
RED  
Compressor Replacement (Refer to Fig. 26  
and 27) — All models contain scroll compressors and have  
from one to four compressors. The size 010-030 units are a sin-  
gle refrigeration circuit while sizes 035-060 are dual circuit. A  
compressor is most easily removed from the front of the unit,  
depending on where clearance space was allowed during unit  
installation.  
Remove the junction box cover bolts and disconnect the  
compressor power and ground connections. Remove the cable  
from the compressor junction box. Remove the connections  
from the high-pressure switch. Knock the same holes out of the  
new compressor junction box and install the cable connectors  
from the old compressor.  
BLK  
WHT  
GRN  
RED  
a30-4972  
Fig. 25 — EXV Cable Connections to EXV Module  
b. Place a digital voltmeter, on 20-volt AC scale,  
across the black and white terminals on the con-  
troller. Restore power to the controller. For at least  
7 seconds, the voltmeter should read approxi-  
mately 12 to 14 volts. Significant differences mean  
the controller is defective or not properly config-  
ured for the EXV valve.  
c. Repeat the procedure in Step b above using the red  
and green terminals on the controller. If the con-  
troller responds properly, then the wiring may be  
damaged or the valve may be plugged with debris  
or otherwise obstructed.  
The compressors are bolted to rails, which are in turn bolted  
to the unit basepan for all sizes except 010 and 015 which are  
directly bolted to the basepan. Remove the 4 bolts holding the  
compressor to the rail on the basepan. Save the mounting hard-  
ware for use with the new compressor. Carefully cut the com-  
pressor suction and discharge lines with a tubing cutter as close  
to the compressor as feasible. Remove high-pressure switch  
and pressure transducer(s) if required for compressor removal.  
Lift one corner of the compressor at a time and remove all the  
rubber mounting grommets (single compressor circuits) or  
steel spacers (dual compressor circuits). Remove the old com-  
pressor from the unit.  
Slide the new compressor in place on the basepan. Lifting  
one side of the compressor at a time, replace all of the compres-  
sor mounting grommets. Using new tubing as required, recon-  
nect compressor suction and discharge lines. Using hardware  
saved, reinstall the mounting bolts and washers through the  
compressor feet. Using proper techniques, braze suction and  
discharge lines and check for leaks. Reconnect oil equalization  
line on dual compressor circuit models.  
Reconnect the compressor power connections and high-  
pressure switch wiring as on the old compressor. Refer to  
Fig. 26 and 27. Following the installation of the new compres-  
sor, tighten all hardware to the following specifications. (See  
Table 31.)  
d. The EXV valves on sizes 025, 030, 050-060 may  
be disassembled for cleaning, inspection or motor  
assembly replacement.  
VALVE REPLACEMENT — The valve may be replaced by  
unsoldering or cutting the piping. A tubing cutter must be used  
to prevent creating contaminants in the piping.  
VALVE REASSEMBLY — Perform the following procedure  
to reassemble the EXV valve:  
1. Use Service Test to open the EXV to 100%. This will re-  
tract the white polyester driver/piston fully into the driver  
guide. Remove power from the valve or controller.  
2. Lightly oil the threads, and gasket or knife-edge on the  
new motor adaptor. Carefully seat the adaptor on the  
valve body or engage and tighten the lock nut if used.  
Lock nuts should be torqued to approximately 45 ft-lb.  
One eighth turn more than hand tight is sufficient to  
achieve a leak proof seal on knife-edge joints.  
Table 31 — Unit Torque Specification  
FASTENER  
RECOMMENDED TORQUE  
Compressor Mounting  
Bolts  
7 to 10 ft-lb (9.5 to 13.5 N-m)  
3. After the motor is tightened, the cable should be replaced  
on the valve. Care should be taken to ensure engagement  
of the alignment key. Snap on the cable retainer.  
Compressor Power  
Connections  
Compressor Ground  
Terminal Connections  
24 to 28 in.-lb (2.7- to 3.2 N-m)  
14 to 18 in.-lb (1.6 to 2.0 N-m)  
4. Pressurize the system and check for leaks.  
5. Reapply power to the ComfortLink™ controller. Since,  
during service, valve position as calculated by the con-  
troller will be lost, the controller should be initialized at  
least twice. In some instances, cycling power to the con-  
troller will accomplish this.  
Cooler  
BRAZED-PLATE COOLER HEAT EXCHANGER RE-  
PLACEMENT — Brazed-plate heat exchangers cannot be  
repaired if they develop a leak. If a leak (refrigerant or water)  
develops, the heat exchanger must be replaced. To replace a  
brazed-plate heat exchanger:  
1. Check that the replacement heat exchanger is the same as  
the original heat exchanger. The unit insulation covers the  
manufacturer’s part number. Make sure the depths of the  
replacement and original cooler heat exchangers are the  
same.  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Disconnect the liquid-in and liquid-out connections at the  
heat exchanger.  
3. Recover the refrigerant from the system, and unsolder the  
refrigerant-in and refrigerant-out connections.  
Mobil . . . . . . . . . . . . . . . . . . . . . . . . . . .EAL Arctic 32-3MA  
Uniqema . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RL32-3MAF  
Do not reuse oil that has been drained out, or oil that has  
been exposed to atmosphere.  
4. Remove the old heat exchanger. The replacement heat ex-  
changer is supplied fully insulated. It also includes a cool-  
er heater. Use of the heater is not required unless the orig-  
inal cooler contained a factory installed heater.  
Microchannel Heat Exchanger (MCHX) Con-  
denser Coil Maintenance and Cleaning  
Recommendations  
5. Install the replacement heat exchanger in the unit and at-  
tach the mounting bracket hardware to the fan uprights  
(sizes 010-030) or to the bottom bracket (sizes 035-060)  
using the hardware removed in Step 4. Reconnect the  
cooler heater if required. For sizes 010-025, torque the  
bolts to 7-10 ft-lb. For sizes 030-060, torque the bolts to  
30-50 ft-lb.  
6. Carefully braze the refrigerant lines to the connections on  
the heat exchanger. Lines should be soldered using silver  
as the soldering material with a minimum of 45% silver.  
Keep the temperature below 1472 F (800 C) under nor-  
mal soldering conditions (no vacuum) to prevent the cop-  
per solder of the brazed plate heat exchanger from chang-  
ing its structure. Failure to do so can result in internal  
or external leakage at the connections which cannot be re-  
paired. Braze the liquid lines with a heat sink around the  
expansion valve to protect it from excess heat.  
CAUTION  
Do not apply any chemical cleaners to MCHX condenser  
coils. These cleaners can accelerate corrosion and damage  
the coil.  
Routine cleaning of coil surfaces is essential to maintain  
proper operation of the unit. Elimination of contamination and  
removal of harmful residues will greatly increase the life of the  
coil and extend the life of the unit. The following steps should  
be taken to clean MCHX condenser coils:  
1. Remove any foreign objects or debris attached to the  
coreface or trapped within the mounting frame and  
brackets.  
2. Put on personal protective equipment including safety-  
glasses and/or face shield, waterproof clothing and  
gloves. It is recommended to use full coverage clothing.  
7. Reconnect the water/brine lines.  
3. Start high pressure water sprayer and purge any soap or  
industrial cleaners from sprayer before cleaning condens-  
er coils. Only clean, potable water is authorized for clean-  
ing condenser coils.  
4. Clean condenser face by spraying the core steady and  
uniformly from top to bottom while directing the spray  
straight toward the core. Do not exceed 900 psig or 30 de-  
gree angle. The nozzle must be at least 12 in. from the  
core face. Reduce pressure and use caution to prevent  
damage to air centers.  
8. Dehydrate and recharge the unit. Check for leaks.  
BRAZED-PLATE COOLER HEAT EXCHANGER  
CLEANING — Brazed-plate heat exchangers must be  
cleaned chemically. A professional cleaning service skilled in  
chemical cleaning should be used. Use a weak acid (5% phos-  
phoric acid, or if the heat exchanger is cleaned frequently, 5%  
oxalic acid). Pump the cleaning solution through the  
exchanger, preferably in a backflush mode. After cleaning,  
rinse with large amounts of fresh water to dispose of all the  
acid. Cleaning materials must be disposed of properly.  
The factory-installed strainer screen in front of the water/  
brine inlets of the heat exchangers should be cleaned periodi-  
cally, depending on condition of the chiller water/brine.  
CAUTION  
Excessive water pressure will fracture the braze between  
air centers and refrigerant tubes.  
Oil Charge  
Check Refrigerant Feed Components  
CAUTION  
FILTER DRIER — The function of the filter drier is to main-  
tain a clean, dry system. The moisture indicator (described  
below) indicates any need to change the filter drier. The filter  
drier is a sealed-type drier. When the drier needs to be  
changed, the entire filter drier must be replaced.  
NOTE: Dual circuit (035-060 sizes) units have 1 filter drier per  
circuit.  
The compressor in a Puron® refigerant (R-410A) system  
uses a polyol ester (POE) oil. This is extremely hygro-  
scopic, meaning it absorbs water readily. POE oils can  
absorb 15 times as much water as other oils designed for  
HCFC and CFC refrigerants. Take all necessary precau-  
tions to avoid exposure of the oil to the atmosphere. Failure  
to do so could result in possible equipment damage.  
MOISTURE-LIQUID INDICATOR The indicator is located  
immediately ahead of the TXV to provide an indication of the  
refrigerant moisture content. It also provides a sight glass for  
refrigerant liquid. Clear flow of liquid refrigerant (at full unit  
loading) indicates sufficient charge in the system. Bubbles in the  
sight glass (at full unit loading) indicate an undercharged system  
or the presence of noncondensables. Moisture in the system,  
measured in parts per million (ppm), changes the color of the  
indicator as follows:  
Green (safe) —Moisture is below 75 ppm  
Yellow-Green (caution) — 75 to 150 ppm  
Yellow (wet) — above 150 ppm  
The unit must be in operation at least 12 hours before the  
moisture indicator gives an accurate reading, and must be in  
contact with liquid refrigerant. At the first sign of moisture in  
the system, change the corresponding filter drier.  
Puron refrigerant systems use a polyol ester (POE) oil. Use  
only Carrier approved compressor oil. Oil should be visible in  
compressor oil sight glass. An acceptable oil level is from 1/8 to  
3/8 of sight glass. All compressors must be off when checking  
oil level. Recommended oil level adjustment method is as  
follows:  
ADD OIL — Recover charge from the unit. Add oil to suction  
line Schrader valve on tandem compressors sets and the com-  
pressor Schrader on the trio's and single compressor circuits.  
(See Fig. 26 and 27.) When oil can be seen at the bottom of the  
sight glass, add oil in 5 oz increments which is approximately  
1/8 in oil level. Run all compressors for 20 minutes then shut off  
to check oil level. Repeat procedure until acceptable oil level is  
present.  
NOTE: Use only Carrier approved compressor oil. Approved  
sources are:  
NOTE: Dual circuit (035-060 sizes) units have one indicator  
per circuit.  
Totaline . . . . . . . . . . . . . . . . . . . . . .3MAF POE, P903-1601  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DPT HPS  
SUCTION  
ACCESS  
EWT VALVE  
SPT  
RGT  
COMPRESSOR A2  
COMPRESSOR A1  
LWT  
DTT  
a30-4973  
a30-4974  
FLOW  
SWITCH  
Fig. 26 — Compressor Location — 30RAP010-030  
SPT RGT  
SUCTION  
RGT  
SPT  
ACCESS  
VALVE  
HPS  
DPT  
DISCHARGE  
ACCESS  
VALVE  
EWT  
DTT  
A1  
A2  
B1  
B2  
OIL  
SIGHTGLASS  
LWT  
DISCHARGE  
ACCESS  
DPT  
FLOW  
SWITCH  
VALVE  
HPS  
Fig. 27 — Compressor Location — 30RAP035-060  
LEGEND FOR FIG. 26 AND 27  
DPT  
DTT  
EWT  
HPS  
LWT  
RGT  
SPT  
Discharge Pressure Thermostat  
Discharge Temperature Thermistor  
Entering Water Thermistor  
High Pressure Switch  
Leaving Water Thermistor  
Return Gas Thermistor  
Suction Pressure Transducer  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MINIMUM LOAD VALVE — On units equipped with the  
factory-installed capacity reduction option, a solenoid valve  
and discharge bypass valve (minimum load valve) are located  
between the discharge line and the cooler entering-refrigerant  
line. The MBB cycles the solenoid to perform minimum load  
valve function and the discharge bypass valve modulates to the  
suction pressure set point and the valve.  
The amount of capacity reduction achieved by the mini-  
mum load valve is not adjustable. The total unit capacity with  
the minimum load valve is shown in Table 19.  
HEATER CABLE — Optional factory-installed cooler and/or  
hydronic package heaters are cycled based on the input from  
the outside-air temperature sensor. These heaters, when in-  
stalled, are designed to protect the cooler and/or hydronic pack-  
age from freezing down to –20 F (–29 C). Power for these heat-  
ers is supplied from the main unit power.  
The input from the low pressure transducer provides a back-  
up cooler freeze protection package. The MBB shuts down the  
unit when a low pressure condition exists that could cause the  
cooler to freeze up.  
PRESSURE RELIEF DEVICES — All units have one pres-  
sure relief device per circuit located in the liquid line which re-  
lieves at 210 F (100 C).  
CAUTION  
Do not disconnect main unit power when servicing com-  
pressor(s) if ambient temperature is below 40 F (4.4 C).  
The compressors have either a single circuit breaker or  
multiple circuit breakers which can be used to shut off  
power to the compressors. If power to the unit must be off  
for a prolonged period, drain the cooler, hydronic package  
(if installed) and internal piping. Add glycol according to  
Winter Shutdown Step 2 below.  
Check Unit Safeties  
HIGH-PRESSURE SWITCH — A high-pressure switch is  
provided to protect each compressor and refrigeration system  
from unsafe high pressure conditions. See Table 32 for high-  
pressure switch settings.  
The high-pressure switch is mounted in the discharge line of  
each circuit. If an unsafe, high-pressure condition should exist,  
the switch opens and shuts off the affected circuit. The CSB  
senses the compressor feedback signal and generates an appro-  
priate alarm. The MBB prevents the circuit from restarting un-  
til the alert condition is reset. The switch should open at the  
pressure corresponding to the appropriate switch setting as  
shown in Table 32.  
WINTER SHUTDOWN — At the end of the cooling season:  
1. Drain the fluid from the cooler, hydronic package (if in-  
stalled) and internal piping.  
2. Fill the cooler and hydronic package with at least 2 gal-  
lons (7.6 L) of inhibited propylene glycol or other suit-  
able inhibited antifreeze solution to prevent any residual  
water in the cooler and hydronic package/piping from  
freezing.  
Table 32 — Factory Settings, High-Pressure  
Switch (Fixed)  
CUTOUT  
CUT-IN  
3. At the beginning of the next cooling season, refill the  
cooler and add the recommended inhibitor.  
UNIT  
30RA  
Psig  
650  
kPa  
4482  
Psig  
500  
kPa  
3447  
Thermistors — Electronic control uses up to five 5 k  
thermistors to sense temperatures used to control operation of  
the chiller. Thermistors EWT, LWT, RGTA, RGTB, and OAT  
are identical in their temperature and voltage drop perfor-  
mance. The SPT space temperature thermistor has a 10 kin-  
put channel and it has a different set of temperature vs. resis-  
tance and voltage drop performance. Resistance at various tem-  
peratures are listed in Tables 33-37. For dual chiller operation,  
a dual chiller sensor is required which is a 5 kthermistor.  
When a digital compressor is used, a DTT (digital temperature  
thermistor) is used. The DTT is an 86 kthermistor.  
REPLACING THERMISTORS (EWT, LWT, RGT) — Add  
a small amount of thermal conductive grease to the thermistor  
well and end of probe. For all probes, tighten the retaining nut  
¼ turn past finger tight. See Fig. 28.  
THERMISTOR/TEMPERATURE SENSOR CHECK — A  
high quality digital volt-ohmmeter is required to perform this  
check.  
Clear the alarm using the scrolling marquee display as de-  
scribed on page 63. The unit should restart after the compressor  
anti-short-cycle delay, built into the unit control module,  
expires.  
PRESSURE TRANSDUCERS — Each refrigerant circuit is  
equipped with a suction and discharge pressure transducer.  
These inputs to the MBB are not only used to monitor the sta-  
tus of the unit, but to also maintain operation of the chiller  
within the compressor manufacturer's specified limits. The in-  
put to the MBB from the suction pressure transducer is also  
used to protect the compressor from operating at low pressure  
conditions and low superheat conditions. In some cases, the  
unit may not be able to run at full capacity. The control module  
will automatically reduce the capacity of a circuit as needed to  
maintain specified maximum/minimum operating pressures.  
COOLER FREEZE-UP PROTECTION  
1. Connect the digital voltmeter across the appropriate the-  
mistor terminals at the J8 terminal strip on the Main Base  
Board (see Fig. 29).  
2. Using the voltage reading obtained, read the sensor tem-  
perature from Tables 33-37.  
3. To check thermistor accuracy, measure temperature at  
probe location with an accurate thermocouple-type tem-  
perature measuring instrument. Insulate thermocouple to  
avoid ambient temperatures from influencing reading.  
Temperature measured by thermocouple and temperature  
determined from thermistor voltage reading should be  
close, ± 5° F (3° C) if care was taken in applying thermo-  
couple and taking readings.  
WARNING  
On medium temperature brine units, the anti-freeze solu-  
tion must be properly mixed to prevent freezing at a tem-  
perature of at least 15 F (8.3 C) below the leaving-fluid  
temperature set point. Failure to provide the proper anti-  
freeze solution mixture is considered abuse and may impair  
or otherwise negatively impact the Carrier warranty.  
The main base board (MBB) monitors leaving fluid temper-  
ature at all times. The MBB will rapidly remove stages of ca-  
pacity as necessary to prevent freezing conditions due to the  
rapid loss of load or low cooler fluid flow.  
If a more accurate check is required, unit must be shut down  
and thermistor removed and checked at a known temperature  
(freezing point or boiling point of water) using either voltage  
drop measured across thermistor at the J8 terminal, by deter-  
mining the resistance with chiller shut down and thermistor  
When the cooler is exposed to lower ambient temperatures  
(34 F [1° C] or below), freeze-up protection is required using  
inhibited ethylene or propylene glycol.  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
disconnected from J8. Compare the values determined with the  
value read by the control in the Temperatures mode using the  
scrolling marquee display.  
necessary, build-up (e.g., lime) can be removed with a common  
vinegar cleansing agent.  
The flow sensor cable is provided with (3) LEDs that indi-  
cate if 24 vac power is present and also status of the switch  
contacts. The LEDs are as follows:  
• Green LED ON – 24 vac present  
• One Yellow LED ON – Flow sensor switch OPEN  
• Two Yellow LED ON – Flow sensor switch CLOSED  
Pressure Transducers — The suction and discharge  
transducers are different part numbers and can be distinguished  
by the color of the transducer body, suction (yellow) and dis-  
charge (red). No pressure transducer calibration is required.  
The transducers operate on a 5 vdc supply, which is generated  
by the main base board (MBB). See Fig. 29 for transducer con-  
nections to the J8 connector on the MBB.  
If nuisance trips of the sensor are occurring, follow the  
steps below to correct the situation:  
TROUBLESHOOTING — If a transducer is suspected of be-  
ing faulty, first check supply voltage to the transducer. Supply  
voltage should be 5 vdc ± 0.2 v. If supply voltage is correct,  
compare pressure reading displayed on the scrolling marquee  
display module against pressure shown on a calibrated pressure  
gauge. Pressure readings should be within ± 15 psig. If the  
two readings are not reasonably close, replace the pressure  
transducer.  
1. Check to confirm that the factory installed strainer is  
clean. Use the blow-down valve provided or remove the  
screen and clean it. For the case of VFD controlled  
pumps, ensure that the minimum speed setting has not  
been changed.  
2. Measure the pressure drop across the cooler or cooler/  
pump system and compare this to the system requirements.  
3. Verify that cable connections at the switch and at the ter-  
minal block are secure.  
4. For factory-installed hydronic systems, verify that:  
• All air has been purged from the system.  
• Circuit setter balance valve has been correctly set.  
5. Pump impeller has been improperly trimmed and is not  
providing sufficient flow.  
6. Wrong pump motor rotation. Pump must rotate clockwise  
when viewed from motor end of pump.  
Chilled Water Flow Switch A factory-installed  
flow switch is installed in the leaving fluid piping for all units  
without the factory-installed hydronic package. See Fig. 30.  
Units with the optional hydronic package have the flow switch  
installed in the entering fluid piping. This is a thermal-disper-  
sion flow switch with no field adjustments. The switch is set  
for approximately 0.5 ft/sec of flow. The sensor tip houses two  
thermistors and a heater element. One thermistor is located in  
the sensor tip, closest to the flowing fluid. This thermistor is  
used to detect changes in the flow velocity of the liquid. The  
second thermistor is bonded to the cylindrical wall and is af-  
fected only by changes in the temperature of the liquid. The  
thermistors are positioned to be in close contact with the wall  
of the sensor probe and, at the same time, to be kept separated  
from each other within the confines of the probe.  
In order to sense flow, it is necessary to heat one of the  
thermistors in the probe. When power is applied, the tip of the  
probe is heated. As the fluid starts to flow, heat will be carried  
away from the sensor tip. Cooling of the first thermistor is a  
function of how fast heat is conducted away by the flowing  
liquid.  
Strainer — Periodic factory-installed strainer cleaning is  
required. Pressure drop across strainer in excess of 3 psi  
(21 kPa) indicates the need for cleaning. Normal (clean) pres-  
sure drop is approximately 1 psi (6.9 kPa). Open the factory-  
installed blowdown valve to clean the strainer. If required, shut  
the chiller down and remove the strainer screen to clean. When  
strainer has been cleaned, enter ‘YES’ for Strainer Mainte-  
nance Done (Run StatusPMS.T.MN).  
Condenser Fans — Each fan is supported by a formed  
wire mount bolted to a fan deck and covered with a wire guard.  
METAL FANS — The exposed end of fan motor shaft is pro-  
tected from weather by grease and a rubber boot. If fan motor  
must be removed for service or replacement, be sure to re-  
grease fan shaft and reinstall fan guard. For proper perfor-  
mance with the value sound fan option, fan web should be  
0.32 in. (8 mm) below top of orifice on the fan deck to top of  
the fan hub. (See Fig. 31.) Tighten set screws to 15 ± 1 ft-lb  
(20 ± 1.3 N-m).  
The difference in temperature between the two thermistors  
provides a measurement of fluid velocity past the sensor probe.  
When fluid velocity is high, more heat will be carried away  
from the heated thermistor and the temperature differential will  
be small. As fluid velocity decreases, less heat will be taken  
from the heated thermistor and there will be an increase in tem-  
perature differential.  
When unit flow rate is above the minimum flow rate, then  
the output is switched on, sending 24 vac to the MBB to prove  
flow has been established.  
For recommended maintenance, check the sensor tip for  
build-up every 6 months. Clean the tip with a soft cloth. If  
IMPORTANT: Check for proper fan rotation (clockwise  
when viewed from above). If necessary, switch any  
2 power leads to reverse fan rotation.  
5/8 in. HEX  
1/4-18 NPT  
6" MINIMUM  
CLEARANCE FOR  
THERMISTOR  
REMOVAL  
Fig. 28 — Thermistor Well  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 33 — 5K Thermistor Temperatures (°F) vs. Resistance/Voltage Drop  
(Voltage Drop for EWT, LWT, RGT, and OAT)  
VOLTAGE  
DROP  
(V)  
VOLTAGE  
DROP  
(V)  
VOLTAGE  
DROP  
(V)  
TEMP  
(F)  
RESISTANCE  
(Ohms)  
TEMP  
(F)  
RESISTANCE  
(Ohms)  
TEMP  
(F)  
RESISTANCE  
(Ohms)  
59  
60  
1.982  
1.956  
1.930  
1.905  
1.879  
1.854  
1.829  
1.804  
1.779  
1.754  
1.729  
1.705  
1.681  
1.656  
1.632  
1.609  
1.585  
1.562  
1.538  
1.516  
1.493  
1.470  
1.448  
1.426  
1.404  
1.382  
1.361  
1.340  
1.319  
1.298  
1.278  
1.257  
1.237  
1.217  
1.198  
1.179  
1.160  
1.141  
1.122  
1.104  
1.086  
1.068  
1.051  
1.033  
1.016  
0.999  
0.983  
0.966  
0.950  
0.934  
0.918  
0.903  
0.888  
0.873  
0.858  
0.843  
0.829  
0.815  
0.801  
0.787  
0.774  
0.761  
0.748  
0.735  
0.723  
0.710  
0.698  
0.686  
0.674  
0.663  
0.651  
0.640  
0.629  
0.618  
0.608  
0.597  
0.587  
0.577  
0.567  
0.557  
0.548  
0.538  
0.529  
0.520  
7,686  
7,665  
7,468  
7,277  
7,091  
6,911  
6,735  
6,564  
6,399  
6,238  
6,081  
5,929  
5,781  
5,637  
5,497  
5,361  
5,229  
5,101  
4,976  
4,855  
4,737  
4,622  
4,511  
4,403  
4,298  
4,196  
4,096  
4,000  
3,906  
3,814  
3,726  
3,640  
3,556  
3,474  
3,395  
3,318  
3,243  
3,170  
3,099  
3,031  
2,964  
2,898  
2,835  
2,773  
2,713  
2,655  
2,597  
2,542  
2,488  
2,436  
2,385  
2,335  
2,286  
2,239  
2,192  
2,147  
2,103  
2,060  
2,018  
1,977  
1,937  
1,898  
1,860  
1,822  
1,786  
1,750  
1,715  
1,680  
1,647  
1,614  
1,582  
1,550  
1,519  
1,489  
1,459  
1,430  
1,401  
1,373  
1,345  
1,318  
1,291  
1,265  
1,240  
1,214  
143  
144  
145  
146  
147  
148  
149  
150  
151  
152  
153  
154  
155  
156  
157  
158  
159  
160  
161  
162  
163  
164  
165  
166  
167  
168  
169  
170  
171  
172  
173  
174  
175  
176  
177  
178  
179  
180  
181  
182  
183  
184  
185  
186  
187  
188  
189  
190  
191  
192  
193  
194  
195  
196  
197  
198  
199  
200  
201  
202  
203  
204  
205  
206  
207  
208  
209  
210  
211  
212  
213  
214  
215  
216  
217  
218  
219  
220  
221  
222  
223  
224  
225  
0.511  
0.502  
0.494  
0.485  
0.477  
0.469  
0.461  
0.453  
0.445  
0.438  
0.430  
0.423  
0.416  
0.408  
0.402  
0.395  
0.388  
0.381  
0.375  
0.369  
0.362  
0.356  
0.350  
0.344  
0.339  
0.333  
0.327  
0.322  
0.317  
0.311  
0.306  
0.301  
0.296  
0.291  
0.286  
0.282  
0.277  
0.272  
0.268  
0.264  
0.259  
0.255  
0.251  
0.247  
0.243  
0.239  
0.235  
0.231  
0.228  
0.224  
0.220  
0.217  
0.213  
0.210  
0.206  
0.203  
0.200  
0.197  
0.194  
0.191  
0.188  
0.185  
0.182  
0.179  
0.176  
0.173  
0.171  
0.168  
0.165  
0.163  
0.160  
0.158  
0.155  
0.153  
0.151  
0.148  
0.146  
0.144  
0.142  
0.140  
0.138  
0.135  
0.133  
1,190  
1,165  
1,141  
1,118  
1,095  
1,072  
1,050  
1,029  
1,007  
986  
965  
945  
925  
906  
887  
868  
850  
832  
815  
798  
782  
765  
750  
734  
719  
705  
690  
677  
663  
650  
638  
626  
614  
602  
591  
581  
570  
561  
551  
542  
533  
524  
516  
508  
501  
494  
487  
480  
473  
467  
461  
456  
450  
445  
439  
434  
429  
424  
419  
415  
410  
405  
401  
396  
391  
386  
382  
377  
372  
367  
361  
356  
350  
344  
338  
332  
325  
318  
311  
304  
297  
289  
282  
–25  
–24  
–23  
–22  
–21  
–20  
–19  
–18  
–17  
–16  
–15  
–14  
–13  
–12  
–11  
–10  
–9  
–8  
–7  
–6  
–5  
–4  
–3  
–2  
–1  
0
3.699  
3.689  
3.679  
3.668  
3.658  
3.647  
3.636  
3.624  
3.613  
3.601  
3.588  
3.576  
3.563  
3.550  
3.536  
3.523  
3.509  
3.494  
3.480  
3.465  
3.450  
3.434  
3.418  
3.402  
3.386  
3.369  
3.352  
3.335  
3.317  
3.299  
3.281  
3.262  
3.243  
3.224  
3.205  
3.185  
3.165  
3.145  
3.124  
3.103  
3.082  
3.060  
3.038  
3.016  
2.994  
2.972  
2.949  
2.926  
2.903  
2.879  
2.856  
2.832  
2.808  
2.784  
2.759  
2.735  
2.710  
2.685  
2.660  
2.634  
2.609  
2.583  
2.558  
2.532  
2.506  
2.480  
2.454  
2.428  
2.402  
2.376  
2.349  
2.323  
2.296  
2.270  
2.244  
2.217  
2.191  
2.165  
2.138  
2.112  
2.086  
2.060  
2.034  
2.008  
98,010  
94,707  
91,522  
88,449  
85,486  
82,627  
79,871  
77,212  
74,648  
72,175  
69,790  
67,490  
65,272  
63,133  
61,070  
59,081  
57,162  
55,311  
53,526  
51,804  
50,143  
48,541  
46,996  
45,505  
44,066  
42,679  
41,339  
40,047  
38,800  
37,596  
36,435  
35,313  
34,231  
33,185  
32,176  
31,202  
30,260  
29,351  
28,473  
27,624  
26,804  
26,011  
25,245  
24,505  
23,789  
23,096  
22,427  
21,779  
21,153  
20,547  
19,960  
19,393  
18,843  
18,311  
17,796  
17,297  
16,814  
16,346  
15,892  
15,453  
15,027  
14,614  
14,214  
13,826  
13,449  
13,084  
12,730  
12,387  
12,053  
11,730  
11,416  
11,112  
10,816  
10,529  
10,250  
9,979  
61  
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
72  
73  
74  
75  
76  
77  
78  
79  
80  
81  
82  
83  
84  
85  
1
86  
2
87  
3
88  
4
89  
5
90  
6
91  
7
92  
8
93  
9
94  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
95  
96  
97  
98  
99  
100  
101  
102  
103  
104  
105  
106  
107  
108  
109  
110  
111  
112  
113  
114  
115  
116  
117  
118  
119  
120  
121  
122  
123  
124  
125  
126  
127  
128  
129  
130  
131  
132  
133  
134  
135  
136  
137  
138  
139  
140  
141  
142  
9,717  
9,461  
9,213  
8,973  
8,739  
8,511  
8,291  
8,076  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 34 — 5K Thermistor Temperatures (°C) vs. Resistance/Voltage Drop  
(Voltage Drop for EWT, LWT, RGT, and OAT)  
VOLTAGE  
DROP  
(V)  
VOLTAGE  
DROP  
(V)  
VOLTAGE  
DROP  
(V)  
TEMP  
(C)  
RESISTANCE  
(Ohms)  
TEMP  
(C)  
RESISTANCE  
(Ohms)  
TEMP  
(C)  
RESISTANCE  
(Ohms)  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
1.982  
1.935  
1.889  
1.844  
1.799  
1.754  
1.710  
1.666  
1.623  
1.580  
1.538  
1.497  
1.457  
1.417  
1.378  
1.340  
1.302  
1.265  
1.229  
1.194  
1.160  
1.126  
1.093  
1.061  
1.030  
0.999  
0.969  
0.940  
0.912  
0.885  
0.858  
0.832  
0.807  
0.782  
0.758  
0.735  
0.713  
0.691  
0.669  
0.649  
0.629  
0.610  
0.591  
0.573  
0.555  
0.538  
0.522  
7,855  
7,499  
7,161  
6,840  
6,536  
6,246  
5,971  
5,710  
5,461  
5,225  
5,000  
4,786  
4,583  
4,389  
4,204  
4,028  
3,861  
3,701  
3,549  
3,404  
3,266  
3,134  
3,008  
2,888  
2,773  
2,663  
2,559  
2,459  
2,363  
2,272  
2,184  
2,101  
2,021  
1,944  
1,871  
1,801  
1,734  
1,670  
1,609  
1,550  
1,493  
1,439  
1,387  
1,337  
1,290  
1,244  
1,200  
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
72  
73  
74  
75  
76  
77  
78  
79  
80  
81  
82  
83  
84  
85  
86  
87  
88  
89  
90  
91  
92  
93  
94  
95  
96  
97  
98  
99  
100  
101  
102  
103  
104  
105  
106  
107  
0.506  
0.490  
0.475  
0.461  
0.447  
0.433  
0.420  
0.407  
0.395  
0.383  
0.371  
0.360  
0.349  
0.339  
0.329  
0.319  
0.309  
0.300  
0.291  
0.283  
0.274  
0.266  
0.258  
0.251  
0.244  
0.237  
0.230  
0.223  
0.217  
0.211  
0.204  
0.199  
0.193  
0.188  
0.182  
0.177  
0.172  
0.168  
0.163  
0.158  
0.154  
0.150  
0.146  
0.142  
0.138  
0.134  
1,158  
1,118  
1,079  
1,041  
1,006  
971  
938  
906  
876  
836  
805  
775  
747  
719  
693  
669  
645  
623  
602  
583  
564  
547  
531  
516  
502  
489  
477  
466  
456  
446  
436  
427  
419  
410  
402  
393  
385  
376  
367  
357  
346  
335  
324  
312  
299  
285  
–32  
3.705  
3.687  
3.668  
3.649  
3.629  
3.608  
3.586  
3.563  
3.539  
3.514  
3.489  
3.462  
3.434  
3.406  
3.376  
3.345  
3.313  
3.281  
3.247  
3.212  
3.177  
3.140  
3.103  
3.065  
3.025  
2.985  
2.945  
2.903  
2.860  
2.817  
2.774  
2.730  
2.685  
2.639  
2.593  
2.547  
2.500  
2.454  
2.407  
2.360  
2.312  
2.265  
2.217  
2.170  
2.123  
2.076  
2.029  
100,260  
94,165  
88,480  
83,170  
78,125  
73,580  
69,250  
65,205  
61,420  
57,875  
54,555  
51,450  
48,536  
45,807  
43,247  
40,845  
38,592  
38,476  
34,489  
32,621  
30,866  
29,216  
27,633  
26,202  
24,827  
23,532  
22,313  
21,163  
20,079  
19,058  
18,094  
17,184  
16,325  
15,515  
14,749  
14,026  
13,342  
12,696  
12,085  
11,506  
10,959  
10,441  
9,949  
–31  
–30  
–29  
–28  
–27  
–26  
–25  
–24  
–23  
–22  
–21  
–20  
–19  
–18  
–17  
–16  
–15  
–14  
–13  
–12  
–11  
–10  
–9  
–8  
–7  
–6  
–5  
–4  
–3  
–2  
–1  
0
1
2
3
4
5
6
7
8
9
10  
11  
9,485  
12  
9,044  
13  
8,627  
14  
8,231  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 35 — 10K Thermistor Temperature (°F) vs. Resistance/Voltage Drop  
(For SPT)  
VOLTAGE  
DROP  
(V)  
VOLTAGE  
DROP  
(V)  
VOLTAGE  
DROP  
(V)  
TEMP  
(F)  
RESISTANCE  
(Ohms)  
TEMP  
(F)  
RESISTANCE  
(Ohms)  
TEMP  
(F)  
RESISTANCE  
(Ohms)  
–25  
–24  
–23  
–22  
–21  
–20  
–19  
–18  
–17  
–16  
–15  
–14  
–13  
–12  
–11  
–10  
–9  
–8  
–7  
–6  
–5  
–4  
–3  
–2  
–1  
0
4.758  
4.750  
4.741  
4.733  
4.724  
4.715  
4.705  
4.696  
4.686  
4.676  
4.665  
4.655  
4.644  
4.633  
4.621  
4.609  
4.597  
4.585  
4.572  
4.560  
4.546  
4.533  
4.519  
4.505  
4.490  
4.476  
4.461  
4.445  
4.429  
4.413  
4.397  
4.380  
4.363  
4.346  
4.328  
4.310  
4.292  
4.273  
4.254  
4.235  
4.215  
4.195  
4.174  
4.153  
4.132  
4.111  
4.089  
4.067  
4.044  
4.021  
3.998  
3.975  
3.951  
3.927  
3.903  
3.878  
3.853  
3.828  
3.802  
3.776  
3.750  
3.723  
3.697  
3.670  
3.654  
3.615  
3.587  
3.559  
3.531  
3.503  
3.474  
3.445  
3.416  
3.387  
3.357  
3.328  
3.298  
3.268  
3.238  
3.208  
3.178  
3.147  
3.117  
3.086  
3.056  
3.025  
196,453  
189,692  
183,300  
177,000  
171,079  
165,238  
159,717  
154,344  
149,194  
144,250  
139,443  
134,891  
130,402  
126,183  
122,018  
118,076  
114,236  
110,549  
107,006  
103,558  
100,287  
97,060  
94,020  
91,019  
88,171  
85,396  
82,729  
80,162  
77,662  
75,286  
72,940  
70,727  
68,542  
66,465  
64,439  
62,491  
60,612  
58,781  
57,039  
55,319  
53,693  
52,086  
50,557  
49,065  
47,627  
46,240  
44,888  
43,598  
42,324  
41,118  
39,926  
38,790  
37,681  
36,610  
35,577  
34,569  
33,606  
32,654  
31,752  
30,860  
30,009  
29,177  
28,373  
27,597  
26,838  
26,113  
25,396  
24,715  
24,042  
23,399  
22,770  
22,161  
21,573  
20,998  
20,447  
19,903  
19,386  
18,874  
18,384  
17,904  
17,441  
16,991  
16,552  
16,131  
15,714  
15,317  
61  
62  
2.994  
2.963  
2.932  
2.901  
2.870  
2.839  
2.808  
2.777  
2.746  
2.715  
2.684  
2.653  
2.622  
2.592  
2.561  
2.530  
2.500  
2.470  
2.439  
2.409  
2.379  
2.349  
2.319  
2.290  
2.260  
2.231  
2.202  
2.173  
2.144  
2.115  
2.087  
2.059  
2.030  
2.003  
1.975  
1.948  
1.921  
1.894  
1.867  
1.841  
1.815  
1.789  
1.763  
1.738  
1.713  
1.688  
1.663  
1.639  
1.615  
1.591  
1.567  
1.544  
1.521  
1.498  
1.475  
1.453  
1.431  
1.409  
1.387  
1.366  
1.345  
1.324  
1.304  
1.284  
1.264  
1.244  
1.225  
1.206  
1.187  
1.168  
1.150  
1.132  
1.114  
1.096  
1.079  
1.062  
1.045  
1.028  
1.012  
0.996  
0.980  
0.965  
0.949  
0.934  
0.919  
0.905  
14,925  
14,549  
14,180  
13,824  
13,478  
13,139  
12,814  
12,493  
12,187  
11,884  
11,593  
11,308  
11,031  
10,764  
10,501  
10,249  
10,000  
9,762  
9,526  
9,300  
9,078  
8,862  
8,653  
8,448  
8,251  
8,056  
7,869  
7,685  
7,507  
7,333  
7,165  
6,999  
6,838  
6,683  
6,530  
6,383  
6,238  
6,098  
5,961  
5,827  
5,698  
5,571  
5,449  
5,327  
5,210  
5,095  
4,984  
4,876  
4,769  
4,666  
4,564  
4,467  
4,370  
4,277  
4,185  
4,096  
4,008  
3,923  
3,840  
3,759  
3,681  
3,603  
3,529  
3,455  
3,383  
3,313  
3,244  
3,178  
3,112  
3,049  
2,986  
2,926  
2,866  
2,809  
2,752  
2,697  
2,643  
2,590  
2,539  
2,488  
2,439  
2,391  
2,343  
2,297  
2,253  
2,209  
147  
148  
149  
150  
151  
152  
153  
154  
155  
156  
157  
158  
159  
160  
161  
162  
163  
164  
165  
166  
167  
168  
169  
170  
171  
172  
173  
174  
175  
176  
177  
178  
179  
180  
181  
182  
183  
184  
185  
186  
187  
188  
189  
190  
191  
192  
193  
194  
195  
196  
197  
198  
199  
200  
201  
202  
203  
204  
205  
206  
207  
208  
209  
210  
211  
212  
213  
214  
215  
216  
217  
218  
219  
220  
221  
222  
223  
224  
225  
0.890  
0.876  
0.862  
0.848  
0.835  
0.821  
0.808  
0.795  
0.782  
0.770  
0.758  
0.745  
0.733  
0.722  
0.710  
0.699  
0.687  
0.676  
0.666  
0.655  
0.645  
0.634  
0.624  
0.614  
0.604  
0.595  
0.585  
0.576  
0.567  
0.558  
0.549  
0.540  
0.532  
0.523  
0.515  
0.507  
0.499  
0.491  
0.483  
0.476  
0.468  
0.461  
0.454  
0.447  
0.440  
0.433  
0.426  
0.419  
0.413  
0.407  
0.400  
0.394  
0.388  
0.382  
0.376  
0.370  
0.365  
0.359  
0.354  
0.349  
0.343  
0.338  
0.333  
0.328  
0.323  
0.318  
0.314  
0.309  
0.305  
0.300  
0.296  
0.292  
0.288  
0.284  
0.279  
0.275  
0.272  
0.268  
0.264  
2,166  
2,124  
2,083  
2,043  
2,003  
1,966  
1,928  
1,891  
1,855  
1,820  
1,786  
1,752  
1,719  
1,687  
1,656  
1,625  
1,594  
1,565  
1,536  
1,508  
1,480  
1,453  
1,426  
1,400  
1,375  
1,350  
1,326  
1,302  
1,278  
1,255  
1,233  
1,211  
1,190  
1,169  
1,148  
1,128  
1,108  
1,089  
1,070  
1,052  
1,033  
1,016  
998  
63  
64  
65  
66  
67  
68  
69  
70  
71  
72  
73  
74  
75  
76  
77  
78  
79  
80  
81  
82  
83  
84  
85  
86  
1
87  
2
88  
3
89  
4
90  
5
91  
6
92  
7
93  
8
94  
9
95  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
96  
97  
98  
99  
100  
101  
102  
103  
104  
105  
106  
107  
108  
109  
110  
111  
112  
113  
114  
115  
116  
117  
118  
119  
120  
121  
122  
123  
124  
125  
126  
127  
128  
129  
130  
131  
132  
133  
134  
135  
136  
137  
138  
139  
140  
141  
142  
143  
144  
145  
146  
981  
964  
947  
931  
915  
900  
885  
870  
855  
841  
827  
814  
800  
787  
774  
762  
749  
737  
725  
714  
702  
691  
680  
670  
659  
649  
639  
629  
620  
610  
601  
592  
583  
574  
566  
557  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 36 — 10K Thermistor Temperature (°C) vs. Resistance/Voltage Drop  
(For SPT)  
VOLTAGE  
DROP  
(V)  
VOLTAGE  
DROP  
(V)  
VOLTAGE  
DROP  
(V)  
TEMP  
(C)  
RESISTANCE  
(Ohms)  
TEMP  
(C)  
RESISTANCE  
(Ohms)  
TEMP  
(C)  
RESISTANCE  
(Ohms)  
–32  
–31  
–30  
–29  
–28  
–27  
–26  
–25  
–24  
–23  
–22  
–21  
–20  
–19  
–18  
–17  
–16  
–15  
–14  
–13  
–12  
–11  
–10  
–9  
4.762  
4.748  
4.733  
4.716  
4.700  
4.682  
4.663  
4.644  
4.624  
4.602  
4.580  
4.557  
4.533  
4.508  
4.482  
4.455  
4.426  
4.397  
4.367  
4.335  
4.303  
4.269  
4.235  
4.199  
4.162  
4.124  
4.085  
4.044  
4.003  
3.961  
3.917  
3.873  
3.828  
3.781  
3.734  
3.686  
3.637  
3.587  
3.537  
3.485  
3.433  
3.381  
3.328  
3.274  
3.220  
3.165  
3.111  
200,510  
188,340  
177,000  
166,342  
156,404  
147,134  
138,482  
130,402  
122,807  
115,710  
109,075  
102,868  
97,060  
91,588  
86,463  
81,662  
77,162  
72,940  
68,957  
65,219  
61,711  
58,415  
55,319  
52,392  
49,640  
47,052  
44,617  
42,324  
40,153  
38,109  
36,182  
34,367  
32,654  
31,030  
29,498  
28,052  
26,686  
25,396  
24,171  
23,013  
21,918  
20,883  
19,903  
18,972  
18,090  
17,255  
16,464  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
3.056  
3.000  
2.944  
2.889  
2.833  
2.777  
2.721  
2.666  
2.610  
2.555  
2.500  
2.445  
2.391  
2.337  
2.284  
2.231  
2.178  
2.127  
2.075  
2.025  
1.975  
1.926  
1.878  
1.830  
1.784  
1.738  
1.692  
1.648  
1.605  
1.562  
1.521  
1.480  
1.439  
1.400  
1.362  
1.324  
1.288  
1.252  
1.217  
1.183  
1.150  
1.117  
1.086  
1.055  
1.025  
0.996  
0.968  
15,714  
15,000  
14,323  
13,681  
13,071  
12,493  
11,942  
11,418  
10,921  
10,449  
10,000  
9,571  
9,164  
8,776  
8,407  
8,056  
7,720  
7,401  
7,096  
6,806  
6,530  
6,266  
6,014  
5,774  
5,546  
5,327  
5,117  
4,918  
4,727  
4,544  
4,370  
4,203  
4,042  
3,889  
3,743  
3,603  
3,469  
3,340  
3,217  
3,099  
2,986  
2,878  
2,774  
2,675  
2,579  
2,488  
2,400  
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
72  
73  
74  
75  
76  
77  
78  
79  
80  
81  
82  
83  
84  
85  
86  
87  
88  
89  
90  
91  
92  
93  
94  
95  
96  
97  
98  
99  
100  
101  
102  
103  
104  
105  
106  
107  
0.940  
0.913  
0.887  
0.862  
0.837  
0.813  
0.790  
0.767  
0.745  
0.724  
0.703  
0.683  
0.663  
0.645  
0.626  
0.608  
0.591  
0.574  
0.558  
0.542  
0.527  
0.512  
0.497  
0.483  
0.470  
0.457  
0.444  
0.431  
0.419  
0.408  
0.396  
0.386  
0.375  
0.365  
0.355  
0.345  
0.336  
0.327  
0.318  
0.310  
0.302  
0.294  
0.287  
0.279  
0.272  
0.265  
2,315  
2,235  
2,157  
2,083  
2,011  
1,943  
1,876  
1,813  
1,752  
1,693  
1,637  
1,582  
1,530  
1,480  
1,431  
1,385  
1,340  
1,297  
1,255  
1,215  
1,177  
1,140  
1,104  
1,070  
1,037  
1,005  
974  
–8  
–7  
–6  
–5  
944  
–4  
915  
–3  
889  
–2  
861  
–1  
836  
0
811  
1
787  
2
764  
3
742  
4
721  
5
700  
6
680  
7
661  
8
643  
9
626  
10  
609  
11  
592  
12  
576  
13  
561  
14  
Table 37 — 86K Thermistor vs Resistance (DTT)  
TEMP  
(C)  
TEMP  
(F)  
RESISTANCE  
(Ohms)  
TEMP  
(C)  
TEMP  
(F)  
RESISTANCE  
(Ohms)  
-40  
-40  
-31  
-22  
-13  
-4  
2,889,600  
2,087,220  
1,522,200  
1,121,440  
834,720  
627,280  
475,740  
363,990  
280,820  
218,410  
171,170  
135,140  
107,440  
86,000  
75  
80  
167  
176  
185  
194  
203  
212  
221  
230  
239  
248  
257  
266  
275  
284  
293  
302  
311  
320  
329  
338  
347  
356  
12,730  
10,790  
9,200  
7,870  
6,770  
5,850  
5,090  
4,450  
3,870  
3,350  
2,920  
2,580  
2,280  
2,020  
1,800  
1,590  
1,390  
1,250  
1,120  
1,010  
920  
-35  
-30  
-25  
-20  
-15  
-10  
-5  
85  
90  
95  
5
100  
105  
110  
115  
120  
125  
130  
135  
140  
145  
150  
155  
160  
165  
170  
175  
180  
14  
23  
0
5
32  
41  
10  
15  
20  
25  
30  
35  
40  
45  
50  
55  
60  
70  
50  
59  
68  
77  
86  
69,280  
95  
56,160  
104  
113  
122  
131  
140  
158  
45,810  
37,580  
30,990  
25,680  
21,400  
15,070  
830  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LOW SOUND FAN — A shroud and a wire guard provide  
protection from the rotating fan. The exposed end of the fan  
motor shaft is protected from weather by grease. If fan motor  
must be removed for service or replacement, be sure to re-  
grease fan shaft and reinstall fan guard. The fan motor has a  
step in the motor shaft. For proper performance, fan should be  
positioned such that it is securely seated on this step. Tighten  
the bolt to 15 ± 1 ft-lb (20 ± 1.3 N·m).  
1
2
3
4
5
6
1
2
3
4
1
2
3
4
1
2
3
4
5
6
7
RGTA  
RGTB  
RED  
1
2
BLK  
RED  
3
LVT  
T55  
4
BLK  
BLU  
BLU  
RED  
J12  
3
5
23  
22  
T-55  
ACCSY  
SEN  
6
4
OAT  
7
IMPORTANT: Check for proper fan rotation (counter-  
clockwise when viewed from above). If necessary, switch  
any 2 power leads to reverse fan rotation.  
SPACE TEMPERATURE  
ACCESSORY OR  
DUAL CHILLER LWT  
8
BLK  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
Motormaster® V Controller — The Motormaster V  
controller is standard on size 010 and 015 units. For other sizes,  
the optional or accessory Motormaster V controller uses an in-  
put signal from the AUX board. See Fig. 32. The controller is  
factory configured and requires no field programming. If a situ-  
ation arises where the drive does not function properly, the in-  
formation provided below and in Table 38 can be used to trou-  
bleshoot the drive.  
EVAPORATOR ENTERING  
FLUID TEMP  
RED  
BLK  
RED  
EVAPORATOR LEAVING  
FLUID TEMP  
J8  
BLK  
RED  
B
C
A
B
C
A
+
DPTB  
GRN  
BLK  
RED  
-
+
WARNING  
SPTB  
DPTA  
SPTA  
GRN  
BLK  
-
Hazard of electrical shock. Wait three minutes after discon-  
necting incoming power before servicing drive. Capacitors  
retain charge after power is removed. Drive assembly  
includes externally mounted current limiting resistors. Use  
extreme caution when servicing the drive. Failure to com-  
ply could result in possible personal injury.  
B
C
A
RED  
+
8
GRN  
BLK  
9
-
10  
B
C
A
RED  
+
11  
12  
GRN  
BLK  
-
a30-4975  
WARNING  
LEGEND  
ACCSY — Accessory  
When configured as shown in this literature, this equip-  
ment is designed to start when it receives line power.  
Ensure that all personnel are clear of fans and guards are  
installed before applying power. Failure to comply could  
result in possible personal injury.  
DPT  
LWT  
LVT  
OAT  
RGT  
SEN  
SPT  
Discharge Pressure Transducer  
Leaving Water Temperature Sensor  
Low Voltage Terminal  
Outdoor Air Temperature Sensor  
Return Gas Temperature Sensor  
Sensor Terminal Block  
Space Temperature Sensor  
CAUTION  
Fig. 29 — Thermistor Connections to  
Main Base Board, J8 Connector  
DO NOT connect incoming AC power to output terminals  
T1, T2, and T3. Severe damage to the drive will result. Do  
not continuously cycle input power to the drive more than  
once every two minutes. Damage to the drive will result.  
CAUTION  
If input power has not been applied to the drive for a period  
of time exceeding three years (due to storage, etc.), the  
electrolytic DC bus capacitors within the drive can change  
internally, resulting in excessive leakage current. This can  
result in premature failure of the capacitors if the drive is  
operated after such a long period of inactivity or storage. In  
order to reform the capacitors and prepare the drive for  
operation after a long period of inactivity, apply input  
power to the drive for 8 hours prior to actually operating  
the motor. Before attempting to operate the drive, motor,  
and driven equipment, be sure all procedures pertaining to  
installation and wiring have been properly followed. Fail-  
ure to comply could result in equipment damage.  
a30-499  
Fig. 30 — Chilled Water Flow Switch  
GENERAL OPERATION — The speed varies in proportion  
to a 4 to 20 mA signal produced by the ComfortLink™ con-  
trols. The MMV output speed is displayed in Hz.  
The ComfortLink controls must be configured for MMV  
operation in order for it to operate. This is configured under the  
Configuration menu (ConfigurationMMMMR.S) and  
a30-4976  
Fig. 31 — Mounted Fan Position  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
selecting “YES”. This configuration menu also contains the  
gains and minimum speed for the Motormaster control logic.  
VFD. It should not be removed with power applied to the  
VFD.  
CONFIGURATION — The MMV is configured for 1 of 12  
operation modes based on the inputs to the control terminal  
block. The 30RAP units use operating modes 5-8. In these con-  
figurations, the MMV follows a 4 to 20 mA speed reference  
signal present on terminals 25 (+) and 2 (-). One additional  
jumper is required to configure the drive for 50/60 Hz opera-  
tion and input voltage. See Table 39 for proper inputs. Once the  
drive is powered, it will change to the mode selected according  
to the inputs. See Fig. 33.  
LOSS OF CCN COMMUNICATIONS — Carrier Comfort  
Network® (CCN) communications with external control  
systems can be affected by high frequency electrical noise gen-  
erated by the Motormaster V control. Ensure unit is well  
grounded to eliminate ground currents along communication  
lines.  
If communications are lost only while Motormaster V con-  
trol is in operation, order a signal isolator (CEAS420876-2)  
and power supplies (CEAS221045-01, 2 required) for the CCN  
communication line.  
DRIVE PROGRAMMING  
Fault Codes — The drive is programmed to automatically re-  
start after a fault and will attempt to restart three times after a  
fault (the drive will not restart after CF, cF, GF, F1, F2-F9, or  
Fo faults). If all three restart attempts are unsuccessful, the  
drive will trip into FAULT LOCKOUT (LC), which requires a  
manual reset.  
CAUTION  
It is strongly recommended that the user NOT change any  
programming without consulting Carrier service personnel.  
Unit damage may occur from improper programming.  
Manual Reset — If fault condition has been removed, cycle  
power to the chiller to reset the VFD.  
To enter password and change program values:  
1. Press Mode.  
2. Upper right decimal point blinks.  
3. Display reads “00”. To enter the PROGRAM mode to ac-  
cess the parameters, press the Mode button. This will ac-  
tivate the PASSWORD prompt (if the password has not  
been disabled). The display will read “00” and the upper  
right-hand decimal point will be blinking. (See Fig. 33.)  
Troubleshooting — Troubleshooting the Motormaster®  
V
control requires a combination of observing system operation  
and VFD information. The drive provides 2 kinds of trouble-  
shooting modes: a status matrix using the 3-digit display  
(P57, P58) and real time monitoring of key inputs and outputs.  
The collective group is displayed through parameters  
50-60 and all values are read-only.  
P50: FAULT HISTORY — Last 8 faults  
P51: SOFTWARE version  
4. Use the  
and  
buttons to scroll to the password  
value (the factory default password is “1111”) and press  
the Mode button. Once the correct password value is  
entered, the display will read “P01”, which indicates that  
the PROGRAM mode has been accessed at the beginning  
of the parameter menu (P01 is the first parameter).  
P52: DC BUS VOLTAGE — in percent of nominal.  
Usually rated input voltage x 1.4  
P53: MOTOR VOLAGE — in percent of rated output  
voltage  
P54: LOAD — in percent of drives rated output current  
rating  
P55: VDC INPUT — in percent of maximum input:  
100 will indicate full scale which is 5 v  
P56: 4-20 mA INPUT — in percent of maximum input.  
20% = 4 mA, 100% = 20 mA  
NOTE: If the display flashes “Er”, the password was incorrect,  
and the process to enter the password must be repeated.  
5. Press Mode to display present parameter number.  
Upper right decimal point blinks.  
Use the  
parameter number.  
and  
buttons to scroll to the desired  
Manual Starter Trip — If the VFD manual starter (MS-FC-  
HS, MS-FC-A1 or MS-FC-B1 depending on model) trips,  
locate the inrush current protectors (3 round black disks per  
motor) and verify their resistance. For units operating at 208 v  
or 230 v, these devices should measure approximately 7 ohms.  
For all other voltages, they should measure approximately  
20 ohms. Check value with mating plug disconnected, power  
to chiller off and at ambient temperature (not hot immediately  
after stopping VFD). These are standard resistances at 77 F  
(25 C). Resistance values decrease at higher temperatures and  
increase at lower temperatures.  
REPLACING DEFECTIVE MODULES — The Comfort-  
Linkreplacement modules are shown in Table 40. If the main  
base board (MBB) has been replaced, verify that all configura-  
tion data is correct. Follow the Configuration mode table and  
verify that all items under sub-modes UNIT, OPT1 and OPT2  
are correct. Any additional field-installed accessories or op-  
tions (RSET, SLCT sub-modes) should also be verified as well  
as any specific time and maintenance schedules.  
Once the desired parameter number is found, press the  
Mode button to display the present parameter setting. The up-  
per right-hand decimal point will begin blinking, indicating  
that the present parameter setting is being displayed, and that it  
can be changed by using the up and down buttons. Use  
and  
to change setting. Press Mode to store new setting.  
Pressing the Mode will store the new setting and also exit  
the PROGRAM mode. To change another parameter, press the  
Mode key again to re-enter the PROGRAM mode (the param-  
eter menu will be accessed at the parameter that was last  
viewed or changed before exiting). If the Mode key is pressed  
within two minutes of exiting the PROGRAM mode, the pass-  
word is not required to access the parameters. After two min-  
utes, the password must be entered in order to access the pa-  
rameters again.  
To change password: first enter the current password then  
change parameter P44 to the desired password.  
To disable automatic control mode and enter manual speed  
control mode:  
Refer to the Start-Up Checklist for 30RAP Liquid Chillers  
(completed at time of original start-up) found in the job folder.  
This information is needed later in this procedure. If the check-  
list does not exist, fill out the current information in the Config-  
uration mode on a new checklist. Tailor the various options and  
configurations as needed for this particular installation.  
1. Change P05 to ‘01- keypad’.  
2. Push UP and DOWN arrow key to set manual speed.  
3. Set P05 to ‘04 - 4-20mA control’ to restore 4 to 20 mA  
control.  
EPM CHIP — The drive uses a electronic programming mod-  
ule (EPM) chip to store the program parameters. This is an  
EEPROM memory chip and is accessible from the front of the  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LOW AMBIENT OPERATION (MOTORMASTER V) FIOP/ACCESSORY  
MM-A  
FB3  
FB1  
1
2
3
L1 T1  
11  
12  
13  
21  
22  
23  
11  
12  
13  
21  
22  
23  
BLK-1  
BLK-2  
BLK-3  
BLK  
YEL  
BLU  
BLK  
YEL  
BLU  
BLK  
YEL  
BLU  
L2 T2  
OFM1  
L3 T3  
GRN/YEL  
YEL  
HIGH SCCR  
ONLY  
2
MMR  
14  
* MM SIGNAL CONNECTION  
VOLTAGE  
*1  
VIO 11  
TB  
1
HZ  
60  
60  
240  
1/4W  
208/230/460/575  
380  
RED  
25  
2
FROM  
13A  
AUX-J4  
BLK  
FB2  
FC2  
1
2
3
11  
12  
13  
21  
22  
23  
11  
12  
13  
21  
22  
23  
BLK-1  
BLK-2  
BLK-3  
BLK  
YEL  
BLU  
BLK  
YEL  
BLU  
OFM2  
GRN/YEL  
CHC  
CHC  
1
4
2
6
BLK  
WHT  
BLK  
BLK  
BLK  
1
2
3
2
COOLER/PUMP  
COOLER/PUMP  
HEATERS  
(208/230,230V)  
HEATERS  
(380,460,575V)  
a30-4977  
8
BLK  
WHT  
YEL  
3
LEGEND  
AUX — Auxiliary  
CONFIGURATION TABLE  
CONTROL INPUT  
FB  
Fuse Block  
MODE  
NOMINAL VOLTAGE  
Hz  
START JUMPER  
(PINS 25, 2)  
MM — Motormaster  
OFM — Outdoor Fan Motor  
5
6
208/230/460/575*  
208/380  
60  
60  
External control 4-20 mA  
External control 4-20 mA  
TB1-TB2  
TB13A-TB2  
TB  
Terminal Block  
*208-v can run in mode 5 or 6.  
Fig. 32 — Typical Motormaster Wiring  
L1  
L2  
L3  
EPM  
Mode  
DANGER  
MMV  
TERMINAL  
BLOCK  
T1  
T3  
B+  
T2  
B-  
DISPLAY  
BUTTONS  
Mode  
Fig. 33 — Motormaster® V Mode Buttons and Mode Display  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 38 — Fault Codes  
FAULT CODE  
DESCRIPTION  
SOLUTION  
AF  
CF  
cF  
High Temperature Fault: Ambient temperature is too high;  
Cooling fan has failed (if equipped).  
Control Fault: A blank EPM, or an EPM with corrupted data Perform a factory reset using Parameter 48 —  
has been installed. PROGRAM SELECTION.  
Incompatibility Fault: An EPM with an incompatible parame- Either remove the EPM or perform a factory  
ter version has been installed.  
Check cooling fan operation  
reset (Parameter 48) to change the parameter  
version of the EPM to match the parameter  
version of the drive.  
CL  
CURRENT LIMIT: The output current has exceeded the  
CURRENT LIMIT setting (Parameter 25) and the drive is  
Check for loose electrical connections.  
Check for faulty condenser fan motor.  
reducing the output frequency to reduce the output current. Check Parameter P25 from Table 39 is set  
If the drive remains in CURRENT LIMIT too long, it can trip correctly.  
into a CURRENT OVERLOAD fault (PF).  
GF  
HF  
JF  
Data Fault: User data and OEM defaults in the EPM are  
corrupted.  
High DC Bus Voltage Fault: Line voltage is too high; Decel- Check line voltage — set P01 appropriately  
eration rate is too fast; Overhauling load.  
Serial Fault: The watchdog timer has timed out, indicating  
that the serial link has been lost.  
Restore factory defaults P48, see section  
above. If that does not work, replace EPM.  
Check serial connection (computer)  
Check settings for PXX.  
Check settings in communication software to  
match PXX.  
LF  
Low DC Bus Voltage Fault: Line voltage is too low.  
Check line voltage — set P01 appropriately  
OF  
Output Transistor Fault: Phase to phase or phase to ground Reduce boost or increase acceleration values.  
short circuit on the output; Failed output transistor; Boost  
settings are too high; Acceleration rate is too fast.  
If unsuccessful, replace drive.  
PF  
SF  
Current Overload Fault: VFD is undersized for the applica- Check line voltage — set P01 appropriately  
tion; Mechanical problem with the driven equipment.  
Check for dirty coils  
Check for motor bearing failure  
Single-phase Fault: Single-phase input power has been  
applied to a three-phase drive.  
Check input power phasing  
F1  
EPM Fault: The EPM is missing or damaged.  
F2-F9, Fo  
Internal Faults: The control board has sensed a problem  
Consult factory  
Drive display = 60.0 even though it Feedback signal is above set point  
is cold outside and it should be run-  
ning slower  
Check for proper set point  
Check liquid line pressure  
Drive display = ‘---’ even though  
drive should be running  
Start jumper is missing  
Replace start jumper. See section above  
Drive display = 8.0 even though fan Feedback signal is below set point and fan is at minimum  
Check for proper set point  
Check liquid line pressure  
should be running faster  
VFD flashes 57 and LCS  
speed  
Feedback or speed signal lost. Drive will operate at 57 Hz In stand alone mode: Check transducer wiring  
until reset or loss of start command. Resetting requires  
cycling start command (or power).  
and feedback voltage. Feedback voltage dis-  
played on P-69. Pin 6 should be 5 v output.  
Pin 5 (feedback) should be somewhere  
between 0 and 5 v.  
LEGEND  
EPM  
LCS  
OEM  
VFD  
Electronic Programming Module  
Lost Control Signal  
Outside Equipment Manufacturer  
Variable Frequency Drive  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 39 — Motormaster® V Program Parameters for Operating Modes  
MODE  
5
MODE  
6
MODE  
7
MODE  
8
PARAMETERS  
DESCRIPTION  
P01  
P02  
P03  
P04  
Line Voltage: 01 = low line, 02 = high line  
Carrier Freq: 01 = 4 kHz, 02 = 6 kHz, 03 = 8 kHz  
Startup mode: flying restart  
01  
01  
06  
01  
02  
01  
06  
01  
01  
01  
06  
01  
02  
01  
06  
01  
Stop mode: coast to stop  
Standard Speed source: 01= keypad,  
04=4-20mA (NO PI), 05= R22, 06=R134a  
P05  
04  
04  
04  
04  
P06  
P08  
P09  
P10  
P11  
P12  
P13  
P14  
P15  
P16  
P17  
P19  
P20  
P21  
P22  
P23  
P24  
P25  
P26  
P27  
P28  
P29  
P30  
P31  
P32  
P33  
TB-14 output: 01 = none  
TB-30 output: 01 = none  
TB-31 Output: 01 = none  
TB-13A function sel: 01 = none  
TB-13B function sel: 01 = none  
TB-13C function sel: 01 = none  
TB-15 output: 01 = none  
Control: 01 = Terminal strip  
Serial link: 02 = enabled 9600,8,N,2 with timer  
Units editing: 02 = whole units  
Rotation: 01 = forward only, 03 = reverse only  
Acceleration time: 10 sec  
Deceleration time: 10 sec  
DC brake time: 0  
DC BRAKE VOLTAGE 0%  
Min freq = 8 Hz ~ 100 – 160 rpm  
Max freq  
Current limit: (%)  
Motor overload: 100  
Base freq: 60 or 50 Hz  
Fixed boost: 0.5% at low frequencies  
Accel boost: 0%  
Slip compensation: 0%  
Preset spd #1: speed if loss of control signal  
Preset spd #2: 0  
01  
01  
01  
01  
01  
01  
01  
01  
02  
02  
01  
10  
10  
0
01  
01  
01  
01  
01  
01  
01  
01  
02  
02  
01  
10  
10  
0
01  
01  
01  
01  
01  
01  
01  
01  
02  
02  
01  
10  
10  
0
01  
01  
01  
01  
01  
01  
01  
01  
02  
02  
01  
10  
10  
0
0
8
0
8
0
8
0
8
60  
125  
100  
60  
0.5  
0
0
57  
0
60  
110  
100  
60  
0.5  
0
0
57  
0
50  
125  
100  
50  
0.5  
0
0
47  
0
50  
110  
100  
50  
0.5  
0
0
47  
0
Preset spd #3: 0  
0
0
0
0
Preset spd 4 default — R22 set point.  
TB12-2 open  
Preset spd 5 default — R134a set point.  
TB12-2 closed  
P34  
P35  
18.0  
12.6  
18.0  
12.6  
18.0  
12.6  
18.0  
12.6  
P36  
P37  
P38  
P39  
P40  
P41  
P42  
P43  
P44  
Preset spd 6 default  
Preset spd 7 default  
Skip bandwidth  
Speed scaling  
Frequency scaling 50 or 60 Hz  
Load scaling: default (not used so NA)  
Accel/decel #2: default (not used so NA)  
Serial address  
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
60  
200  
60  
1
60  
200  
60  
1
50  
200  
60  
1
50  
200  
60  
1
Password:111  
111  
111  
111  
111  
Speed at min signal: 8 Hz; used when PID  
mode is disabled and 4-20mA input is at 4 mA  
Speed at max feedback: 60 or 50 Hz. Used  
when PID disabled and 4-20mA input is at 20 mA  
P45  
P46  
8
8
8
8
60  
60  
50  
50  
P47  
P48  
P61  
P62  
P63  
P64  
P65  
P66  
P67  
P68  
Clear history? 01 = maintain. (set to 02 to clear)  
Program selection: Program 1 – 12  
PI Mode: 05= reverse, 0-5V, 01 = no PID  
Min feedback = 0 (0V *10)  
Max feedback = 50 (5V * 10)  
Proportional gain = 4%  
Integral gain = .2  
PI acell/decel (set point change filter) = 5  
Min alarm  
01  
05  
01  
0
50  
4
.2  
5
0
01  
06  
01  
0
50  
4
.2  
5
0
01  
07  
01  
0
50  
4
.2  
5
0
01  
08  
01  
0
50  
4
.2  
5
0
Max alarm  
0
0
0
0
LEGEND  
NA — Not Applicable  
PID — Proportional Integral Derivative  
TB — Terminal Block  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
uncommon for actual pump duty to be different than what was  
anticipated at time of selection. In many cases, it may be desir-  
able to make some field modifications to obtain optimum  
pump performance.  
Before any pump modifications are made, it is recommend-  
ed that actual pump performance be verified and compared to  
the applicable pump curve. See base unit installation instruc-  
tions. This can be done in a variety of ways:  
WARNING  
Electrical shock can cause personal injury and death. Shut  
off all power to this equipment during installation. There  
may be more than one disconnect switch. Tag all discon-  
nect locations to alert others not to restore power until work  
is completed.  
1. If pump impeller diameter is known:  
1. Check that all power to unit is off. Carefully disconnect  
all wires from the defective module by unplugging its  
connectors.  
a. Connect a differential pressure gage across the  
pump at the ports provided on the pump volutes.  
b. Read GPM from applicable impeller curve.  
2. If pump impeller diameter is not known:  
2. Remove the defective module by removing its mounting  
screws with a Phillips screwdriver, and removing the  
module from the control box. Save the screws later use.  
3. Verify that the instance jumper (MBB) or address switch-  
es (all other modules) exactly match the settings of the  
defective module.  
NOTE: Handle boards by mounting standoffs only to  
avoid electrostatic discharge.  
4. Package the defective module in the carton of the new  
module for return to Carrier.  
If pump impeller diameter has been trimmed and the size  
is not known, it is necessary to determine which impeller  
curve to read.  
The easiest way to confirm pump performance is to  
“dead-head” the pump and read the differential pressure  
across the pressure ports on the pump. “Dead-heading”  
can be done by shutting the circuit setter valve on the dis-  
charge side of the pump.  
NOTE: Although not all pumps can be safely “dead-  
headed”, centrifugal pumps (such as on the 30RAP units)  
can be “dead-headed” for short amounts of time. It is rec-  
ommended to keep the time short due to excessive heat  
build-up in the pump.  
5. Mount the new module in the unit’s control box using a  
Phillips screwdriver and the screws saved in Step 2.  
6. Reinstall all module connectors. For accessory Navigator  
replacement, make sure the plug is installed at TB3 in the  
LEN connector.  
Since the “dead-head” condition is a no-flow condition,  
the head will correspond to the intersection of an impel-  
ler curve with the vertical axis of the pump chart. The  
correct impeller diameter is that which corresponds to the  
measured head.  
7. Carefully check all wiring connections before restoring  
power.  
8. Verify the ENABLE/OFF/REMOTE CONTACT switch  
is in the OFF position.  
9. Restore control power. Verify that all module red LEDs  
blink in unison. Verify that all green LEDs are blinking  
and that the scrolling marquee or Navigator™ display is  
communicating correctly.  
10. Verify all configuration information, settings, set points  
and schedules. Return the ENABLE/OFF/REMOTE  
CONTACT switch to its previous position.  
3. Once the impeller diameter is known, proceed as in  
Step 1.  
4. Water flow rate can be determined by using a differential  
pressure gage with the Bell & Gossett circuit setter bal-  
ance valve calculator. (This information is also provided  
in the installation instructions.) This method will not di-  
rectly measure pressure differential seen by the pump, but  
can be used to “double-check” the pump measurement.  
5. Verify that cable connections at the switch and at the ter-  
minal block are secure.  
6. For factory-installed hydronic system, verify that:  
Table 40 — Replacement Modules  
REPLACEMENT  
PART NO. (with  
Software)  
REPLACEMENT PART  
NO. (without Software)  
MODULE  
Main Base  
• All air has been purged from the system.  
30RA502134  
HK50AA029  
Board (MBB)  
• Circuit setter balance valve has been correctly set.  
Scrolling  
Marquee  
Display  
7. Pump impeller has been improperly trimmed and is not  
providing sufficient flow.  
HK50AA031  
HK50AA030  
Energy  
Management  
Module  
8. Wrong pump motor rotation. Pump must rotate clockwise  
when viewed from motor end of pump.  
PUMP MODIFICATIONS AND IMPELLER TRIMMING  
— See applicable section in the Installation instructions.  
RESET OF CHILLER WATER FLOW — See applicable sec-  
tion in the Installation instructions.  
CHANGING OF PUMP SEALS — See Bell & Gossett ser-  
vice instruction manual provided with the hydronic package.  
30GT515218  
HK50AA033  
HK50AA028  
N/A  
(EMM)  
Navigator  
Display  
EXV  
AUX  
30GT515217  
32GB500442E  
HK50AA026  
N/A  
Hydronic Package — If the unit is equipped with a  
factory-installed hydronic package, consult the information be-  
low for proper maintenance and service. In addition to this  
information, each factory-installed hydronic package is sup-  
plied with a packet of information supplied by the manufactur-  
er, Bell & Gossett. Carrier Corporation strongly recommends  
that this information be thoroughly reviewed prior to operation  
of the chiller.  
PUMP PERFORMANCE CHECK — The factory-installed  
pumps in the 30RAP units are shipped with a single impeller  
size available for that pump. The pump was selected based on  
the flow and head requirements as provided to Carrier. It is not  
MAINTENANCE  
Recommended Maintenance Schedule — The fol-  
lowing are only recommended guidelines. Jobsite conditions  
may dictate that maintenance schedule is performed more often  
than recommended.  
Routine:  
For machines with e-coat condenser coils:  
Periodic clean water rinse, especially in coastal and  
industrial applications.  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Check condenser coils for debris, clean as necessary.  
Every month:  
Check moisture indicating sight glass for possible refrig-  
erant loss and presence of moisture.  
Every 3 months (for all machines):  
core face. Reduce pressure and use caution to prevent  
damage to air centers.  
CAUTION  
Excessive water pressure will fracture the braze between  
air centers and refrigerant tubes.  
Check refrigerant charge.  
Check all refrigerant joints and valves for refrigerant  
leaks, repair as necessary.  
Check chilled water flow switch operation.  
Check all condenser fans for proper operation.  
Check compressor oil level.  
TROUBLESHOOTING  
Complete Unit Stoppage and Restart Possi-  
ble causes for unit stoppage and reset methods are shown be-  
low and in Table 41. Refer to Fig. 3-7 for component arrange-  
ment and control wiring diagrams.  
GENERAL POWER FAILURE — After power is restored,  
restart is automatic through normal MBB start-up.  
UNIT ENABLE-OFF-REMOTE CONTACT SWITCH IS  
OFF — When the switch is OFF, the unit will stop immediate-  
ly. Place the switch in the ENABLE position for local switch  
control or in the REMOTE CONTACT position for control  
through remote contact closure.  
CHILLED FLUID PROOF-OF-FLOW SWITCH OPEN —  
After the problem causing the loss of flow has been corrected,  
reset is manual by resetting the alarm with the scrolling mar-  
quee as shown in Table 42.  
OPEN 24-V CONTROL CIRCUIT BREAKER(S) — De-  
termine the cause of the failure and correct. Reset circuit break-  
er(s). Restart is automatic after MBB start-up cycle is  
complete.  
COOLING LOAD SATISFIED — Unit shuts down when  
cooling load has been satisfied. Unit restarts when required to  
satisfy leaving fluid temperature set point.  
Every 12 months (for all machines):  
Check all electrical connections, tighten as necessary.  
Inspect all contactors and relays, replace as necessary.  
Check accuracy of thermistors, replace if greater than  
± 2° F (1.2° C) variance from calibrated thermometer.  
Obtain and test an oil sample. Change oil only if  
necessary.  
Check to be sure that the proper concentration of anti-  
freeze is present in the chilled water loop, if applicable.  
Verify that the chilled water loop is properly treated.  
Check refrigerant filter driers for excessive pressure  
drop, replace as necessary.  
Check chilled water strainers, clean as necessary.  
Check cooler heater operation, if equipped.  
Check condition of condenser fan blades and that they  
are securely fastened to the motor shaft.  
Perform Service Test to confirm operation of all  
components.  
Check for excessive cooler approach (Leaving Chilled  
Water Temperature — Saturated Suction Temperature)  
which may indicate fouling. Clean cooler vessel if  
necessary.  
THERMISTOR FAILURE — If a thermistor fails in either an  
open or shorted condition, the unit will be shut down. Replace  
EWT, LWT, or OAT as required. Unit restarts automatically,  
but must be reset manually by resetting the alarm with the  
scrolling marquee as shown in Table 42.  
Microchannel Heat Exchanger (MCHX) Con-  
denser Coil Maintenance and Cleaning  
Recommendations  
CAUTION  
CAUTION  
Do not apply any chemical cleaners to MCHX condenser  
coils. These cleaners can accelerate corrosion and damage  
the coil.  
If unit stoppage occurs more than once as a result of any of  
the safety devices listed, determine and correct cause  
before attempting another restart.  
Routine cleaning of coil surfaces is essential to maintain  
proper operation of the unit. Elimination of contamination and  
removal of harmful residues will greatly increase the life of the  
coil and extend the life of the unit. The following steps should  
be taken to clean MCHX condenser coils:  
1. Remove any foreign objects or debris attached to the  
coreface or trapped within the mounting frame and  
brackets.  
2. Put on personal protective equipment including safety  
glasses and/or face shield, waterproof clothing and  
gloves. It is recommended to use full coverage clothing.  
3. Start high pressure water sprayer and purge any soap or  
industrial cleaners from sprayer before cleaning condens-  
er coils. Only clean, potable water is authorized for clean-  
ing condenser coils.  
LOW SATURATED SUCTION — Several conditions can  
lead to low saturated suction alarms and the chiller controls  
have several override modes built in which will attempt to keep  
the chiller from shutting down. Low fluid flow, low refrigerant  
charge and plugged filter driers are the main causes for this  
condition. To avoid permanent damage and potential freezing  
of the system, do NOT repeatedly reset these alert and/or alarm  
conditions without identifying and correcting the cause(s).  
COMPRESSOR SAFETIES — The 30RAP units with Com-  
fortLink™ controls include a compressor protection board that  
protects the operation of each of the compressors. Each board  
senses the presence or absence of current to each compressor.  
If there is a command for a compressor to run and there is  
no current, then one of the following safeties or conditions  
have turned the compressor off:  
Compressor Overcurrent — All compressors have internal  
line breaks or a motor protection device located in the com-  
pressor electrical box.  
4. Clean condenser face by spraying the core steady and  
uniformly from top to bottom while directing the spray  
straight toward the core. Do not exceed 900 psig or 30 de-  
gree angle. The nozzle must be at least 12 in. from the  
Compressor Short Circuit — There will not be current if the  
compressor circuit breaker that provides short circuit protection  
has tripped.  
Compressor Motor Over Temperature — The internal line-  
break or over temperature switch has opened.  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
High-Pressure Switch Trip — The high pressure switch has  
opened. Below are the factory settings for the fixed high pres-  
sure switch.  
reset automatically before the motor protector resets, which  
may take up to 2 hours.  
High Discharge Gas Temperature Protection — Units  
equipped with digital compressors have an additional thermis-  
tor located on the discharge line, If discharge temperature ex-  
ceeds 265 F (129.4 C), the digital compressor will be shut off.  
CUTOUT  
CUT-IN  
30RAP UNIT  
SIZE  
psig  
kPa  
psig  
kPa  
010-060  
650  
4482  
500  
3447  
Alarms will also occur if the current sensor board malfunc-  
tions or is not properly connected to its assigned digital input. If  
the compressor is commanded OFF and the current sensor  
reads ON, an alert is generated. This will indicate that a com-  
pressor contactor has failed closed. In this case, a special mode,  
Compressor Stuck on Control, will be enabled and all other  
compressors will be turned off. An alarm will then be enabled  
to indicate that service is required. Outdoor fans will continue  
to operate. The first outdoor fan stage is turned on immediately.  
The other stages of fan will be turned on as required by SCT.  
ASTP Protection Trip — All non-digital Copeland compres-  
sors are equipped with an advanced scroll temperature protec-  
tion (ASTP). A label located above the terminal box identifies  
models that contain this technology. See Fig. 34.  
Alarms and Alerts — These are warnings of abnormal  
or fault conditions, and may cause either one circuit or the  
whole unit to shut down. They are assigned code numbers as  
described in Table 42.  
Automatic alarms will reset without operator intervention if  
the condition corrects itself. The following method must be  
used to reset manual alarms:  
Before resetting any alarm, first determine the cause of the  
alarm and correct it. Enter the Alarms mode indicated by the  
LED on the side of the scrolling marquee display. Press  
Fig. 34 — Advanced Scroll Temperature  
Protection Label  
Advanced scroll temperature protection is a form of inter-  
nal discharge temperature protection that unloads the scroll  
compressor when the internal temperature reaches approxi-  
mately 300 F. At this temperature, an internal bi-metal disk  
valve opens and causes the scroll elements to separate, which  
stops compression. Suction and discharge pressures balance  
while the motor continues to run. The longer the compressor  
runs unloaded, the longer it must cool before the bi-metal disk  
resets. See Fig. 35 for approximate reset times.  
and  
until the sub-menu item RCRN “RESET  
ENTER  
ALL CURRENT ALARMS” is displayed. Press  
.
ENTER  
The control will prompt the user for a password, by displaying  
PASS and WORD. Press to display the default pass-  
ENTER  
for each character. If the password  
word, 1111. Press  
ENTER  
has been changed, use the arrow keys to change each individu-  
To manually reset ASTP, the compressor should be stopped  
and allowed to cool. If the compressor is not stopped, the motor  
will run until the motor protector trips, which occurs up to  
90 minutes later. Advanced scroll temperature protection will  
al character. Toggle the display to “YES” and press  
The alarms will be reset.  
.
ENTER  
120  
110  
100  
90  
80  
70  
60  
50  
40  
30  
20  
10  
0
0
10  
20  
30  
40  
50  
60  
70  
80  
90  
Compressor Unloaded Run Time (Minutes)  
*Times are approximate.  
NOTE: Various factors, including high humidity, high ambient temperature,  
and the presence of a sound blanket will increase cool-down times.  
Fig. 35 — Recommended Minimum Cool Down Time After Compressor is Stopped*  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 41 — Troubleshooting  
SYMPTOMS  
CAUSE  
REMEDY  
Cooler Circulating Pump Does  
Not Run  
Power line open  
Reset circuit breaker.  
Control fuse or circuit breaker open  
Check control circuit for ground or short. Reset breaker and  
replace fuse.  
Tripped power breaker  
Loose terminal connection  
Improperly wired controls  
Low line voltage  
Check the controls. Find the cause of trip and reset breaker.  
Check connections.  
Check wiring and rewire if necessary.  
Check line voltage — determine location of  
voltage drop and remedy deficiency.  
Pump motor defective  
Check motor winding for open or short.  
Replace compressor if necessary.  
Pump seized  
Replace pump.  
Compressor Cycles  
Off on Loss of Charge  
Low refrigerant charge  
Repair leak and recharge.  
Compressor Cycles Off on Cooler  
Freeze Protection  
Thermistor failure  
Replace thermistor.  
System load was reduced faster than controller could  
remove stages  
Unit will restart after fluid temperature rises back into the  
control band. Avoid rapidly removing system load.  
Compressor Shuts Down on  
High-Pressure Control  
High-pressure control acting erratically  
Noncondensables in system  
Condenser dirty  
Replace control.  
Evacuate and recharge.  
Clean condenser.  
Fans not operating  
Repair or replace if defective.  
Reduce charge.  
System overcharged with refrigerant  
Low refrigerant charge  
Unit Operates Too Long  
or Continuously  
Add refrigerant.  
Control contacts fused  
Replace control.  
Partially plugged or plugged expansion valve or filter drier  
Defective insulation  
Clean or replace as needed.  
Replace or repair as needed.  
Check compressor and replace if necessary.  
Support piping as required.  
Check for loose pipe connections or damaged compressor  
Replace compressor (worn bearings).  
Check for loose compressor holddown bolts.  
Repair leak.  
Damaged compressor  
Unusual or Loud System  
Noises  
Piping vibration  
Compressor noisy  
Compressor Loses Oil  
Leak in system  
Mechanical damage (Failed seals or broken scrolls)  
Oil trapped in line  
Replace compressor.  
Check piping for oil traps.  
Repair leak and recharge.  
Replace filter drier.  
Hot Liquid Line  
Shortage of refrigerant due to leak  
Restricted filter drier  
Frosted Liquid Line  
Frosted Suction Line  
Expansion valve admitting excess refrigerant (note: this is a Replace valve if defective.  
normal condition for brine applications)  
Stuck EXV  
Replace valve if defective.  
Freeze-Up  
Improper charging  
Make sure a full quantity of fluid is flowing through the cooler  
while charging, and suction pressure in cooler is equal to or  
greater than pressure corresponding to 32 F (0° C).  
System not drained for winter shutdown  
Loose Thermistor  
Recommended that system be filled with an appropriate gly-  
col mixture to prevent freezing of pumps and fluid tubing.  
Verify thermistors are fully inserted in wells.  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 42 — Alarm and Alert Codes  
ALARM/ ALARM  
WHY WAS THIS  
ACTION TAKEN  
BY CONTROL  
RESET  
METHOD  
PROBABLE  
CAUSE  
ALERT  
CODE  
OR  
DESCRIPTION  
ALARM  
ALERT  
GENERATED?  
High-pressure switch open,  
faulty CSB, loss of condenser  
Manual air, filter drier plugged, non-  
condensables, operation  
beyond capability.  
Circuit A, Compressor 1  
Failure  
Compressor feedback signal  
does not match relay state  
Compressor A1 shut  
down.  
T051  
A051  
T052  
A052  
T055  
A055  
T056  
A056  
Alert  
Alarm  
Alert  
Respective current sensor  
board (CSB) feedback signal  
is ON when the compressor  
should be off  
Circuit A, Compressor 1  
Failure  
Welded compressor contac-  
Manual  
Unit shut down  
tor, CSB wiring error.  
High-pressure switch open,  
faulty CSB, loss of condenser  
Manual air, filter drier plugged, non-  
condensables, operation  
Circuit A, Compressor 2  
Failure  
Compressor feedback signal  
does not match relay state  
Compressor A2 shut  
down.  
beyond capability.  
Respective current sensor  
board (CSB) feedback signal  
is ON when the compressor  
should be off  
Circuit A, Compressor 2  
Failure  
Welded compressor contac-  
Manual  
Alarm  
Alert  
Unit shut down  
tor, CSB wiring error.  
High-pressure switch open,  
faulty CSB, loss of condenser  
Manual air, filter drier plugged, non-  
condensables, operation  
Circuit B, Compressor 1  
Failure  
Compressor feedback signal  
does not match relay state  
Compressor B1 shut  
down.  
beyond capability.  
Respective current sensor  
board (CSB) feedback signal  
is ON when the compressor  
should be off  
Circuit B, Compressor 1  
Failure  
Welded compressor contac-  
Manual  
Alarm  
Alert  
Unit shut down  
tor, CSB wiring error.  
High-pressure switch open,  
faulty CSB, loss of condenser  
Manual air, filter drier plugged, non-  
condensables, operation  
Circuit B, Compressor 2  
Failure  
Compressor feedback signal  
does not match relay state  
Compressor B2 shut  
down.  
beyond capability.  
Respective current sensor  
board (CSB) feedback signal  
is ON when the compressor  
should be off  
Circuit B, Compressor 2  
Failure  
Welded compressor contac-  
Manual  
Alarm  
Unit shut down  
tor, CSB wiring error.  
Cooler Leaving Fluid  
Thermistor Failure  
Thermistor outside range of  
–40 to 245 F (–40 to 118 C)  
Chiller shut down  
immediately  
Thermistor failure, damaged  
Automatic  
A060  
A061  
Alarm  
Alarm  
cable/wire or wiring error.  
Cooler Entering Fluid  
Thermistor Failure  
Thermistor outside range of  
–40 to 245 F (–40 to 118 C)  
Chiller shut down  
immediately  
Thermistor failure, damaged  
Automatic  
cable/wire or wiring error.  
If return gas sensors are  
enabled (RG.EN) and  
Thermistor failure, damaged  
Automatic  
T068  
T069  
None  
None  
Circuit A Return Gas Thermistor Failure  
Circuit B Return Gas Thermistor Failure  
Circuit A shut down  
Circuit B shut down  
thermistor is outside range of  
–40 to 245 F (–40 to 118 C)  
cable/wire or wiring error.  
If return gas sensors are  
enabled (RG.EN) and  
thermistor is outside range of  
–40 to 245 F –40 to 118 C)  
Thermistor failure, damaged  
Automatic  
cable/wire or wiring error.  
Temperature reset  
disabled. Chiller runs  
under normal control/set  
points. When capacity  
reaches 0, cooler/pump  
heaters are energized.  
Outside Air Thermistor  
Failure  
Thermistor outside range of  
–40 to 245 F (–40 to 118 C)  
Thermistor failure, damaged  
Automatic  
T073  
Alert  
cable/wire or wiring error.  
Temperature reset  
disabled. Chiller runs  
under normal control/set  
points.  
Space Temperature/Dual Chiller  
Thermistor Failure  
Thermistor outside range of  
–40 to 245 F (–40 to 118 C)  
Thermistor failure, damaged  
Automatic  
T074  
T077  
T078  
Alert  
Alert  
Alert  
cable/wire or wiring error.  
Circuit A Saturated  
Suction Temperature  
exceeds Cooler Leaving  
Fluid Temperature  
Faulty expansion valve or  
Faulty expansion valve,  
suction pressure transducer  
or leaving fluid thermistor.  
Circuit A shutdown after  
pumpdown complete.  
suction pressure transducer  
Automatic  
or leaving fluid  
thermistor.  
Circuit B Saturated  
Suction Temperature  
exceeds Cooler Leaving  
Fluid Temperature  
Faulty expansion valve or  
Faulty expansion valve,  
suction pressure transducer  
or leaving fluid thermistor.  
Circuit B shutdown after  
pumpdown complete  
suction pressure transducer  
Automatic  
or leaving fluid  
thermistor.  
Dual LWT thermistor failure,  
Automatic damaged cable/wire or  
wiring error.  
Lead/Lag LWT  
Thermistor outside range of  
–40 to 245 F (–40 to 118 C)  
Chiller runs as a stand  
alone machine  
T079  
T090  
T091  
T092  
Alert  
Alert  
Alert  
Alert  
Thermistor Failure  
Transducer failure, poor  
Automatic connection to MBB, or wiring  
damage/error.  
Circuit A Discharge  
Pressure Transducer Failure  
Outside of range (0 to  
667 psig)  
Circuit A shut down  
Circuit B shut down  
Circuit A shut down  
Circuit B shut down  
Transducer failure, poor  
Automatic connection to MBB, or wiring  
damage/error.  
Circuit B Discharge  
Pressure Transducer Failure  
Outside of range (0 to  
667 psig)  
Transducer failure, poor  
Automatic connection to MBB, or wiring  
damage/error.  
Circuit A Suction  
Pressure Transducer Failure  
Outside of range (0 to 420  
psig)  
Circuit B Suction  
Pressure Transducer  
Failure  
Transducer failure, poor  
Automatic connection to MBB, or wiring  
damage/error.  
Outside of range (0 to  
420 psig)  
T093  
T094  
Alert  
Alert  
Discharge Gas  
Thermistor Failure  
Discharge thermistor (DTT) is Digital compressor shut  
either open or shorted  
Thermistor failure, damaged  
Automatic  
down.  
cable/wire or wiring error.  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 42 — Alarm and Alert Codes (cont)  
ALARM/  
ALERT  
CODE  
ALARM  
OR  
ALERT  
WHY WAS THIS  
ACTION TAKEN  
ALARM  
RESET  
METHOD  
PROBABLE  
CAUSE  
DESCRIPTION  
BY CONTROL  
GENERATED?  
If the compressors are off  
and discharge pressure  
reading is < 26 psig for  
30 sec.  
Circuit not allowed to  
start.  
Refrigerant leak or  
transducer failure  
T110  
T111  
T112  
T113  
Alert  
Alert  
Alert  
Alert  
Circuit A Loss of Charge  
Manual  
Manual  
Manual  
Manual  
If the compressors are off  
and discharge pressure  
reading is < 26 psig for  
30 sec.  
Circuit not allowed to  
start.  
Refrigerant leak or  
transducer failure  
Circuit B Loss of Charge  
Circuit saturated suction  
temperature pressure  
transducer > 70 F (21.1 C)  
for 5 minutes  
Faulty Expansion valve,  
faulty suction pressure  
transducer or high entering  
fluid temperature.  
Circuit A High Saturated  
Suction Temperature  
Circuit shut down  
Circuit shut down  
Circuit saturated suction  
temperature pressure  
transducer > 70 F (21.1 C)  
for 5 minutes  
Faulty Expansion valve,  
faulty suction pressure  
transducer or high entering  
fluid temperature.  
Circuit B High Saturated  
Suction Temperature  
Automatic restart Faulty expansion valve,  
Suction superheat is  
less than 5° F (2.8 C) for 5  
minutes.  
after first daily  
occurrence.  
Manual restart  
thereafter.  
faulty suction pressure  
transducer, faulty suction gas  
thermistor, circuit  
Circuit A Low Suction  
Superheat  
T114  
T115  
T116  
T117  
Alert  
Alert  
Alert  
Alert  
Circuit A shut down.  
Circuit B shut down.  
Circuit shut down  
Circuit shut down  
overcharged  
Automatic restart Faulty expansion valve,  
Suction superheat is  
less than 5° F (2.8 C) for 5  
minutes.  
after first daily  
occurrence.  
Manual restart  
thereafter.  
faulty suction pressure  
transducer, faulty suction  
gas thermistor, circuit  
overcharged  
Circuit B Low Suction  
Superheat  
Mode 7 caused the com-  
pressor to unload 6 consecu-  
tive times with less than a  
30-minute interval between  
each circuit shutdown.  
Faulty expansion valve, low  
refrigerant charge, plugged  
filter drier, faulty suction  
pressure transducer, low  
cooler fluid flow  
Circuit A Low Cooler  
Suction Temperature  
Manual  
Manual  
Mode 8 caused the com-  
pressor to unload 6 consecu-  
tive times with less than a  
30-minute interval between  
each circuit shutdown.  
Faulty expansion valve, low  
refrigerant charge, plugged  
filter drier, faulty suction  
pressure transducer, low  
cooler fluid flow  
Circuit B Low Cooler  
Suction Temperature  
Refrigerant charge, plugged  
filter drier, head pressure  
control.  
High Discharge Gas  
Temperature Alert  
Discharge Thermistor (DTT) Compressor A1 shut  
reading is greater than 250 F down  
T118  
A118  
Alert  
Automatic  
Manual  
3 Discharge Gas Tempera-  
Compressor A1 shut  
ture alarms occur within a  
down  
Refrigerant charge, plugged  
filter drier, head pressure  
control.  
High Discharge Gas  
Temperature  
Alarm  
day  
Automatic, only  
after first 3 daily  
occurrences.  
Faulty transducer/high  
pressure switch, low/  
restricted condenser  
airflow  
Manual reset  
Circuit A High  
Compressor operation out-  
Circuit shut down  
T126  
T127  
Alert  
Alert  
thereafter. Read-  
ing from OAT sen-  
sor must drop 5 F  
(2.8 C) before  
restart  
Discharge Pressure  
side of operating envelope.  
Automatic, only  
after first 3 daily  
occurrences. Man- Faulty transducer/high  
ual reset thereafter. pressure switch, low/  
Reading from OAT restricted condenser  
Circuit B High  
Discharge Pressure  
Compressor operation out-  
Circuit shut down  
side of operating envelope.  
sensor must drop  
5 F (2.8 C) before  
restart  
airflow  
Automatic  
Suction pressure below  
restart after first  
daily occurrence.  
Manual restart  
thereafter.  
Faulty or sticking EXV, low  
refrigerant charge, plugged  
filter drier.  
Circuit A Low Suction  
Pressure  
T133  
T134  
Alert  
Alert  
34 psig for 8 seconds or  
below 23 psig  
Circuit shut down  
Circuit shut down  
Automatic  
Suction pressure below  
34 psig for 8 seconds or  
below 23 psig  
restart after first  
daily occurrence.  
Manual restart  
thereafter.  
Faulty or sticking EXV, low  
refrigerant charge, plugged  
filter drier.  
Circuit B Low Suction  
Pressure  
Reverse any two incoming  
power leads to correct. Check  
for correct fan rotation first.  
Reverse Rotation  
Detected  
Incoming chiller power leads Chiller not allowed to  
A140  
A150  
A151  
Alert  
Alarm  
Alarm  
Manual  
not phased correctly  
start.  
Automatic once  
Chiller shutdown  
without going through  
pumpdown.  
CCN emergency stop  
command received  
CCN command for CCN Network  
EMSTOP returns to command.  
normal  
Emergency Stop  
Manual once  
configuration errors  
are corrected  
One or more illegal  
configurations exists.  
Chiller is not allowed to  
start.  
Configuration error.  
Check unit settings.  
Illegal Configuration  
Automatic once  
alarms/alerts are  
cleared that pre-  
Alarm notifies user  
that chiller is 100%  
Unit Down Due to  
Failure  
Both circuits are down due  
to alarms/alerts.  
Chiller is unable  
to run.  
A152  
Alarm  
vent the chiller from down.  
starting.  
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 42 — Alarm and Alert Codes (cont)  
ALARM/  
ALERT  
CODE  
ALARM  
OR  
ALERT  
WHY WAS THIS  
ACTION TAKEN  
ALARM  
RESET  
METHOD  
PROBABLE  
CAUSE  
DESCRIPTION  
BY CONTROL  
GENERATED?  
Occupancy schedule  
Automatic when  
correct clock control  
restarts.  
Time/Date/Month/  
Day/Year not  
properly set.  
Real Time Clock  
Hardware Failure  
will not be used. Chiller  
T153  
A154  
Alert  
Internal clock on MBB fails  
defaults to Local On  
mode.  
Serial EEPROM  
Hardware Failure  
Chiller is unable  
Hardware failure with MBB  
to run.  
Main Base Board  
failure.  
Alarm  
Manual  
Potential failure of  
MBB. Download  
current operating  
software. Replace  
MBB if error occurs  
again.  
Serial EEPROM  
Storage Failure  
Configuration/storage  
No Action  
T155  
Alert  
Manual  
failure with MBB  
Critical Serial EEPROM  
Storage Failure  
Configuration/storage  
failure with MBB  
Chiller is not allowed  
to run.  
Main Base Board  
failure.  
A156  
A157  
Alarm  
Alarm  
Manual  
Manual  
Hardware failure with  
peripheral device  
Chiller is not allowed  
to run.  
Main Base Board  
failure.  
A/D Hardware Failure  
Wiring error, faulty  
wiring or failed  
EXV board.  
Loss of Communication  
with EXV Board  
MBB loses communication  
with EXV board  
Chiller is not allowed  
to run.  
A172  
Alarm  
Automatic  
4 to 20 mA  
temperature reset  
disabled. Demand  
Limit set to 100%. 4 to  
20 mA set point  
disabled.  
Wiring error, faulty  
wiring or failed  
Energy Manage-  
ment Module (EMM).  
Loss of Communication  
with EMM  
MBB loses communication  
with EMM  
T173  
Alert  
Automatic  
If configured with EMM and  
input less than 2 mA or  
greater than 22 mA  
Set point function  
disabled. Chiller  
controls to CSP1.  
Faulty signal  
4 to 20 mA Cooling Set  
Point Input Failure  
T174  
T175  
Alert  
Alert  
Automatic  
Automatic  
generator, wiring  
error, or faulty EMM.  
Wiring error, faulty  
wiring or failed  
AUX board.  
Loss of Communication  
with the AUX Board  
MBB loses communication  
with AUX Board.  
Reset function  
4 to 20 mA  
If configured with EMM  
and input less than 2 mA or  
greater than 22 mA  
Faulty signal  
disabled. Chiller  
returns to normal set  
point control.  
T176  
T177  
Alert  
Alert  
Temperature Reset  
Input Failure  
Automatic  
Automatic  
generator, wiring  
error, or faulty EMM.  
Demand limit function  
disabled. Chiller  
returns to 100%  
demand limit  
If configured with EMM and  
input less than 2 mA or  
greater than 22 mA  
Faulty signal  
generator, wiring  
error, or faulty EMM.  
4 to 20 mA Demand  
Limit Input Failure  
control.  
Pump 1 Auxiliary Contacts  
are closed when Pump 2  
output is energized or if  
Pump 2 Auxiliary Contacts  
are closed when Pump 1  
output is energized.  
Wiring error, faulty  
pump contactor  
auxiliary contacts.  
Cooler Pump Auxiliary  
Contact Inputs Miswired  
Both pump outputs  
are turned off.  
A189  
Alarm  
Manual  
Pump 1 Auxiliary Contacts  
did not close within  
26 seconds after pump  
was started  
Cooler Pump 1 Aux  
Contacts Failed to Close  
at Start-Up  
Pump 1 turned off.  
Pump 2 will be started  
if available.  
Wiring error, faulty  
contacts on pump  
contactor  
T190  
T191  
T192  
T193  
Alert  
Alert  
Alert  
Alert  
Manual  
Manual  
Manual  
Manual  
Pump 2 Auxiliary Contacts  
did not close within  
26 seconds after pump  
was started  
Cooler Pump 2 Aux  
Contacts Failed to Close  
at Start-Up  
Pump 2 turned off.  
Pump 1 will be started  
if available.  
Wiring error, faulty  
contacts on pump  
contactor  
Wiring error, pump  
circuit breaker  
tripped, contactor  
failure  
Cooler Pump 1 Failed  
to Provide Flow at  
Start-Up  
Pump 1 did not provide  
flow to close flow switch  
within 60 seconds  
Pump 1 turned off.  
Pump 2 will be started  
if available.  
Wiring error, pump  
circuit breaker  
tripped, contactor  
failure  
Cooler Pump 2 Failed  
to Provide Flow at  
Start-Up  
Pump 2 did not provide  
flow to close flow switch  
within 60 seconds  
Pump 1 turned off.  
Pump 2 will be started  
if available.  
Pump 1 Auxiliary Contacts  
open for 26 seconds after  
initially made. All  
Pump 2 will be started  
if available. Chiller  
allowed to run if  
Pump 2 successfully  
starts.  
Cooler Pump 1 Aux  
Contacts Opened  
During Normal  
Operation  
Wiring error, faulty  
contacts on pump  
contactor  
T194  
T195  
Alert  
Alert  
Manual  
Manual  
compressors shut down.  
Pump 1 turned off.  
Pump 2 Auxiliary Contacts  
open for 26 seconds after  
initially made. All  
compressors shut down.  
Pump 2 turned off.  
Pump 1 will be started  
if available. Chiller  
allowed to run if  
Pump 1 successfully  
starts.  
Cooler Pump 2 Aux  
Contacts Opened  
During Normal  
Operation  
Wiring error, faulty  
contacts on pump  
contactor  
All compressors  
shut down. Pump 1  
turned off. Pump 2 will  
be started if available.  
Chiller allowed to run if  
Pump 2 successfully  
starts and flow switch  
is closed.  
Wiring error, pump  
circuit breaker  
tripped, contactor  
failure  
Cooler flow switch contacts  
open for 3 seconds after  
initially made  
Flow Lost While Pump 1  
Running  
T196  
Alert  
Manual  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 42 — Alarm and Alert Codes (cont)  
ALARM/  
ALERT  
CODE  
ALARM  
OR  
ALERT  
WHY WAS THIS  
ACTION TAKEN  
ALARM  
RESET  
METHOD  
PROBABLE  
CAUSE  
DESCRIPTION  
BY CONTROL  
GENERATED?  
All compressors shut  
down. Pump 2 turned  
off. Pump 1 will be  
Wiring error, pump  
circuit breaker  
tripped, contactor  
failure  
Cooler flow switch contacts  
open for 3 seconds after  
initially made  
Flow Lost While Pump 2  
Running  
started if available.  
Chiller allowed to run if  
Pump 1 successfully  
starts and flow switch  
is closed.  
T197  
Alert  
Manual  
Cooler Pump 1 Aux  
Contacts Closed While  
Pump Off  
Pump 1 Auxiliary Contacts  
closed for 26 seconds  
when pump state is off  
Wiring error, faulty  
pump contactor  
Chiller not allowed to  
start  
Automatic when  
T198  
T199  
Alert  
Alert  
aux contacts open  
(welded contacts)  
Cooler Pump 2 Aux  
Contacts Closed While  
Pump Off  
Pump 2 Auxiliary Contacts  
closed for 26 seconds  
when pump state is off  
Wiring error, faulty  
pump contactor  
(welded contacts)  
Chiller not allowed to  
start  
Automatic when  
aux contacts open  
Cooler flow switch contacts  
failed to close within  
Chiller not allowed to  
start. For models with  
dual pumps, the  
Wiring error, pump  
circuit breaker  
tripped, contactor  
failure, faulty flow  
switch or interlock  
Cooler Flow/Interlock  
Contacts Failed to Close  
at Start-Up  
1 minute (if cooler pump  
control is enabled) or  
within 5 minutes (if cooler  
pump control is not  
T200  
Alert  
Manual  
Manual  
second pump will be  
started if available  
enabled) after start-up  
All compressors shut  
down. For models with  
dual pumps, the  
second pump will be  
started if available  
Cooler pump failure,  
faulty flow switch or  
interlock, pump  
circuit breaker  
tripped  
Cooler Flow/Interlock  
Contacts Opened  
During Normal  
Operation  
Flow switch opens for at  
least 3 seconds after  
being initially closed  
A201  
A202  
Alarm  
Alarm  
If configured for cooler  
pump control and flow  
switch input is closed for  
5 minutes while pump  
output(s) are off  
Cooler Pump Interlock  
Closed When Pump is  
Off  
Wiring error, faulty  
pump contactor  
(welded contacts)  
Automatic when  
aux contacts open  
Chiller shut down  
Wiring error, faulty  
wiring, failed Slave  
chiller MBB module,  
power loss at slave  
chiller, wrong slave  
address.  
Dual chiller control  
disabled. Chiller runs  
as a stand-alone  
machine.  
Master chiller MBB  
loses communication  
with slave chiller MBB  
Loss of Communication  
with Slave Chiller  
T203  
T204  
Alert  
Alert  
Automatic  
Automatic  
Wiring error, faulty  
wiring, failed master  
chiller MBB module,  
power loss at Master  
chiller.  
Dual chiller control  
disabled. Chiller runs  
as a stand-alone  
machine  
Slave chiller MBB loses  
communication with  
master chiller MBB  
Loss of Communication  
with Master Chiller  
CCN Address for  
both chillers is the  
same. Must be  
different. Check  
CCN.A under the  
OPT2 sub-mode in  
Configuration at both  
chillers.  
Dual chiller routine  
disabled. Master/slave  
run as stand-alone  
chillers.  
Master and slave chiller  
have the same CCN  
address (CCN.A)  
Master and Slave Chiller  
with Same Address  
T205  
T206  
A207  
Alert  
Alert  
Automatic  
Building load greater  
than unit capacity,  
low water/brine flow  
or compressor fault.  
Check for other  
LWT read is greater than  
LCW Alert Limit, Total  
capacity is 100% and LWT  
is greater than LWT  
High Leaving Chilled  
Water Temperature  
Alert only. No action  
taken.  
Automatic  
reading one minute ago  
alarms/alerts.  
Both EWT and LWT  
must be at least 6 F  
(3.3 C) above Brine  
Freeze point  
Chiller shutdown  
without going through  
pumpdown. Cooler  
pump continues to  
run a minimum of  
5 minutes (if control  
enabled).  
Cooler Freeze  
Protection  
Cooler EWT or LWT is less  
than Brine Freeze (BR.FZ)  
Faulty thermistor,  
low water flow.  
Alarm  
(BR.FZ).  
Automatic for first,  
Manual reset thereaf-  
ter.  
Cooler EWT is less than  
LWT by 3° F (1.7° C) for  
1 minute after a circuit is  
started  
Faulty cooler pump,  
low water flow,  
plugged fluid  
strainer.  
Chiller shutdown.  
EWT or LWT  
A208  
T300  
Alarm  
Alert  
Cooler pump shut off  
(if control enabled).  
Manual  
Thermistor failure  
Pump 1 Service  
Countdown (P.1.DN)  
expired. Complete pump 1  
maintenance and enter  
'YES' for Pump 1  
Cooler Pump 1  
Scheduled  
Maintenance Due  
Routine pump  
maintenance  
required  
None  
None  
Automatic  
Maintenance Done  
(P.1.MN) item.  
Pump 2 Service  
Countdown (P.2.DN)  
expired. Complete pump 2  
maintenance and  
Cooler Pump 2  
Scheduled  
Maintenance Due  
Routine pump  
maintenance  
required  
T301  
Alert  
Automatic  
enter 'YES' for Pump 1  
Maintenance Done  
(P.2.MN) item.  
70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 42 — Alarm and Alert Codes (cont)  
ALARM/  
ALERT  
CODE  
ALARM  
OR  
ALERT  
WHY WAS THIS  
ACTION TAKEN  
ALARM  
RESET  
METHOD  
PROBABLE  
CAUSE  
DESCRIPTION  
BY CONTROL  
GENERATED?  
Strainer Service  
Countdown (S.T.DN)  
Strainer Blowdown  
Scheduled  
Routine strainer  
maintenance  
required  
expired. Complete strainer  
T302  
T303  
Alert  
Alert  
None  
Automatic  
Automatic  
blowdown and enter 'YES'  
for Strainer Maintenance  
Done (S.T.MN) item.  
Maintenance Due  
Coil Service Countdown  
(C.L.DN) expired.  
Routine condenser  
coil maintenance  
required  
Condenser Coil  
Maintenance Due  
Complete condenser coil  
None  
cleaning and enter 'YES'  
for Coil Maintenance Done  
(C.L.MN) item.  
Current Sensor Board  
A1 Failure  
Alert occurs when CSB out-  
put is a constant high value  
Compressor A1 shut  
down  
CSB failure.  
Wiring error.  
T500  
T501  
T502  
T503  
T504  
Alert  
Alert  
Alert  
Alert  
Alert  
Automatic  
Automatic  
Automatic  
Automatic  
Automatic  
Current Sensor Board  
A2 Failure  
Alert occurs when CSB out-  
put is a constant high value  
Compressor A2 shut  
down  
CSB failure.  
Wiring error.  
Current Sensor Board  
A3 Failure  
Alert occurs when CSB out-  
put is a constant high value  
Compressor A3 shut  
down  
CSB failure.  
Wiring error.  
Current Sensor Board  
B1 Failure  
Alert occurs when CSB out-  
put is a constant high value  
Compressor B1 shut  
down  
CSB failure.  
Wiring error.  
Current Sensor Board  
B2 Failure  
Alert occurs when CSB out-  
put is a constant high value  
Compressor B2 shut  
down  
CSB failure.  
Wiring error.  
Current Sensor Board  
B3 Failure  
Alert occurs when CSB out-  
put is a constant high value  
Compressor B3 shut  
down  
CSB failure.  
Wiring error.  
T505  
T950  
Alert  
Alert  
Automatic  
Automatic  
Loss of Communication  
with Water System  
Manager  
No communications have  
been received by the MBB  
within 5 minutes of last  
transmission  
WSM forces removed.  
Chiller runs under own  
control  
Failed module, wiring  
error, failed  
transformer, loose  
connection plug,  
wrong address  
T951  
T952  
Alert  
Alert  
Loss of Communication  
with Chillervisor System  
Manager  
No communications have  
been received by the MBB  
within 5 minutes of last  
transmission  
CSM forces removed.  
Chiller runs under own  
control  
Automatic  
Automatic  
Failed module, wiring  
error, failed  
transformer, loose  
connection plug,  
wrong address  
Loss of Communication  
with Hydronic System  
Manager  
No communications have  
been received by the MBB  
within 5 minutes of last  
transmission  
HSM forces removed.  
Chiller runs under own  
control  
Failed module, wiring  
error, failed  
transformer, loose  
connection plug,  
wrong address  
LEGEND FOR TABLE 42  
CCN  
Carrier Comfort Network  
Current Sensor Board  
CSB  
EEPROM  
EMM  
EWT  
EXV  
Electronic Eraseable Programmable Read Only Memory  
Energy Management Module  
Entering Fluid Temperature  
Electronic Expansion Valve  
Hydronic System Manager  
Leaving Chilled Water  
HSM  
LCW  
LWT  
Leaving Fluid Temperature  
Main Base Board  
MBB  
OAT  
Outdoor-Air Temperature  
SCT  
Saturated Condensing Temperature  
Water System Manager  
WSM  
COMPRESSOR FAILURE ALERTS  
T051, T052 (Circuit A Compresser Failures)  
Low Refrigerant Charge — If the compressor operates for an  
extended period of time with low refrigerant charge, the com-  
pressor ASTP device will open, which will cause the compres-  
sor to trip on its overload protection device.  
Circuit Breaker Trip — The compressors are protected from  
short circuit by a breaker in the control box.  
T055, T056 (Circuit B Compressor Failures) — Alert codes  
051, 052, 055, and 056 are for compressors A1, A2, B1, and  
B2 respectively. These alerts occur when the current sensor  
(CS) does not detect compressor current during compressor op-  
eration. When this occurs, the control turns off the compressor.  
If the current sensor board reads OFF while the compressor  
relay has been commanded ON, an alert is generated.  
Wiring Error — A wiring error might not allow the compres-  
sor to start.  
To check out alerts T051-T056:  
POSSIBLE CAUSES  
1. Turn on the compressor in question using Service Test  
mode. If the compressor does not start, then most likely  
the problem is one of the following: HPS open, open in-  
ternal protection, circuit breaker trip, incorrect safety wir-  
ing, or incorrect compressor wiring.  
2. If the compressor does start, verify it is rotating in the cor-  
rect direction.  
Compressor Overload — Either the compressor internal over-  
load protector is open or the external overload protector (Kri-  
wan module) has activated. The external overload protector  
modules are mounted in the compressor wiring junction box.  
Temperature sensors embedded in the compressor motor wind-  
ings are the inputs to the module. The module is powered with  
24 vac from the units main control box. The module output is a  
normally closed contact that is wired in series with the com-  
pressor contactor coil. In a compressor motor overload condi-  
tion, contact opens, deenergizing the compressor contactor.  
IMPORTANT: Prolonged operation in the wrong direction  
can damage the compressor. Correct rotation can be veri-  
fied by a gage set and looking for a differential pressure  
rise on start-up.  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
of –40 to 245 F (–40 to 118 C). Failure of this thermistor will  
disable any elements of the control which requires its use. The  
cause of the alert is usually a faulty thermistor in the T55, or  
T58 device, a shorted or open thermistor caused by a wiring er-  
ror, or a loose connection.  
IMPORTANT: If the CS is always detecting current, verify  
that the compressor is on. If the compressor is on, check  
the contactor and the relay on the MBB. If the compressor  
is off and there is no current, verify the CSB wiring and  
replace if necessary.  
T090 (Circuit A Discharge Pressure Transducer Failure)  
IMPORTANT: Return to Normal mode and observe com-  
pressor operation to verify that compressor current sensor  
is working and condenser fans are energized.  
T091 (Circuit B Discharge Pressure Transducer Failure) —  
Alert codes 090 and 091 are for circuits A and B respectively.  
These alerts occur when the pressure is outside the range of 0.0  
to 667.0 psig. A circuit cannot run when this alert is active. Use  
the scrolling marquee to reset the alert. The cause of the alert is  
usually a faulty transducer, faulty 5-v power supply, or a loose  
connection.  
COMPRESSOR STUCK ON FAILURE ALARMS  
Circuit A A051, A052  
Circuit B A055, A056 — Alarm codes 051, 052, 055, and  
056 are for compressors A1, A2, B1, and B2. These alarms oc-  
cur when the CSB detects current when the compressor should  
be off. When this occurs, the control turns off the compressor.  
If the current sensor board reads ON while the compressor  
relay has been commanded OFF for a period of 4 continuous  
seconds, an alarm is generated. These alarms are only moni-  
tored for a period of 10 seconds after the compressor relay has  
been commanded OFF. This is done to facilitate a service tech-  
nician forcing a relay to test a compressor.  
In addition, if a compressor stuck failure occurs and the cur-  
rent sensor board reports the compressor and the request off,  
certain diagnostics will take place as follows:  
T092 (Circuit A Suction Pressure Transducer Failure)  
T093 (Circuit B Suction Pressure Transducer Failure)  
Alert codes 092 and 093 are for circuits A and B respectively.  
These alerts occur when the pressure is outside the range of 0.0  
to 420.0 psig. A circuit cannot run when this alert is active. Use  
the scrolling marquee to reset the alert. The cause of the alert is  
usually a faulty transducer, faulty 5-v power supply, or a loose  
connection.  
T094 (Discharge Gas Thermistor Failure) — This alert oc-  
curs for units which have the digital compressor installed on  
circuit A. If discharge gas temperature is open or shorted, the  
circuit will be shutoff. The alert will reset itself when discharge  
temperature is less than 250 F (121.1 C). The cause of the alert  
is usually low refrigerant charge or a faulty thermistor.  
1. If any of the compressors are diagnosed as stuck on and  
the current sensor board is on and the request is off, the  
control will command the condenser fans to maintain  
normal head pressure.  
T110 (Circuit A Loss of Charge)  
T111 (Circuit B Loss of Charge) — Alert codes 110 and 111  
are for circuits A and B respectively. These alerts occur when  
the compressor is OFF and the discharge pressure is less than  
26 psig.  
2. The control will shut-off all other compressors.  
The possible causes include welded contactor or frozen  
compressor relay on the MBB.  
To check out alarms A051-A056:  
T112 (Circuit A High Saturated Suction Temperature)  
T113 (Circuit B High Saturated Suction Temperature)  
1. Place the unit in Service Test mode. All compressors  
should be off.  
2. Verify that there is not 24-v at the contactor coil. If there  
is 24 v at the contactor, check relay on MBB and wiring.  
Alert codes 112 and 113 occur when compressors in a circuit  
have been running for at least 5 minutes and the circuit saturat-  
ed suction temperature is greater than 70 F (21.1 C). The high  
saturated suction alert is generated and the circuit is shut down.  
3. Check for welded contactor.  
4. Verify CSB wiring.  
5. Return to Normal mode and observe compressor opera-  
tion to verify that compressor current sensor is working  
and condenser fans are energized.  
T114 (Circuit A Low Superheat)  
T115 (Circuit B Low Superheat) — Alert codes 114 and 115  
occur when the superheat of a circuit is less than 5 F (2.8 C) for  
5 continuous minutes. The low superheat alert is generated and  
the circuit is shut down.  
T116 (Circuit A Low Cooler Suction Temperature)  
A060 (Cooler Leaving Fluid Thermistor Failure)  
The  
T117 (Circuit B Low Cooler Suction Temperature) — Alert  
codes 116 and 117 are for circuits A and B respectively. These  
alerts are generated if the capacity stages are reduced three  
times without a 30 minute interval between capacity reductions  
due to operating mode 7 or mode 8.  
sensor reading is outside the range of –40 to 245 F (–40 to  
118 C) then the alarm will occur. The cause of the alarm is usu-  
ally a faulty thermistor, a shorted or open thermistor caused by  
a wiring error, or a loose connection. Failure of this thermistor  
will shut down the entire unit.  
T118 (High Discharge Gas Temperature Alert)  
A118 (High Discharge Gas Temperature Alarm)  
A061 (Cooler Entering Thermistor Failure) — If the sensor  
reading is outside the range of –40 to 240 F (–40 to116 C) then  
the alarm will occur. The cause of the alarm is usually a faulty  
thermistor, a shorted or open thermistor caused by a wiring er-  
ror, or a loose connection. Failure of this thermistor will shut  
down the entire unit.  
T068, T69 (Circuit A,B Compressor Return Gas Tempera-  
ture Thermistor Failure) — This alert occurs when the com-  
pressor return gas temperature sensor is outside the range of  
–40 to 240 F (–40 to 116 C). Failure of this thermistor will shut  
down the appropriate circuit.  
This  
alert or alarm occurs for units which have the digital compres-  
sor installed on circuit A. If discharge gas temperature is great-  
er than 268 F (131.1 C), the circuit will be shut off. The alert  
will reset itself when discharge temperature is less than 250 F  
(121.1 C). If this alert occurs 3 times within a day, the A118  
alarm will be generated and the alarm must be reset manually.  
The cause of the alert is usually low refrigerant charge or a  
faulty thermistor.  
T126 (Circuit A High Head Pressure)  
T073 (Outside Air Temperature Thermistor Failure) — This  
alert occurs when the outside air temperature sensor is outside  
the range of –40 to 240 F (–40 to 116 C). Failure of this therm-  
istor will disable any elements of the control which requires its  
use.  
T074 (Space Temperature Thermistor Failure) — This alert  
occurs when the space temperature sensor is outside the range  
T127 (Circuit B High Head Pressure) — Alert codes 126 and  
127 are for circuits A and B respectively. These alerts occur  
when the appropriate saturated condensing temperature is  
greater than the operating envelope shown in Fig 14. Prior to  
the alert, the control will shut down one compressor on a circuit  
if that circuit's saturated condensing temperature is greater than  
the maximum SCT minus 5° F (2.7° C). If SCT continues to  
72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
rise to greater than the maximum SCT, the alert will occur and  
the circuit's remaining compressor will shut down. The cause  
of the alarm is usually an overcharged system, high outdoor  
ambient temperature coupled with dirty outdoor coil, plugged  
filter drier, or a faulty high-pressure switch.  
T153 (Real Time Clock Hardware Failure) — A problem  
has been detected with MBB real time clock hardware. Try re-  
setting the power and check the indicator lights. If the alarm  
continues, the board should be replaced.  
A154 (Serial EEPROM Hardware Failure) — A problem  
has been detected with the EEPROM on the MBB. Try  
resetting the power and check the indicator lights. If the alarm  
continues, the board should be replaced.  
T155 (Serial EEPROM Storage Failure Error) — A problem  
has been detected with the EEPROM storage on the MBB. Try  
resetting the power and check the indicator lights. If the alert  
continues, the board should be replaced.  
A156 (Critical Serial EEPROM Storage Failure Error) — A  
problem has been detected with the EEPROM storage on the  
MBB. Try resetting the power and check the indicator lights. If  
the alarm continues, the board should be replaced.  
T133 (Circuit A Low Suction Pressure)  
T134 (Circuit B Low Suction Pressure) — Alert codes 133  
and 134 are for circuits A and B respectively. These alerts are  
generated if one of the two following conditions is satisfied:  
the circuit suction pressure is below 34 psig (234.4 kPa) for 8  
seconds, or the suction pressure is below 23 psig (158.6 kPa).  
The cause of this alert may be low refrigerant charge, plugged  
liquid line filter drier, or sticking EXV. Check head pressure  
operation. If not equipped, consider adding low ambient tem-  
perature head pressure control.  
Add wind baffles if required.  
A140 (Reverse Rotation Detected) — A test is made once, on  
power up, for suction pressure change on the first activated cir-  
cuit. The unit control determines failure as follows:  
1. The suction pressure of both circuits is sampled 5 seconds  
before the compressor is brought on, right when the com-  
pressor is brought on and 5 seconds afterwards.  
2. The rate of suction pressure change from 5 seconds be-  
fore the compressor is brought on to when the compres-  
sor is brought on is calculated.  
3. The rate of suction pressure change from when the  
compressor is brought on to 5 seconds afterwards is  
calculated.  
A157 (A/D Hardware Failure) — A problem has been detect-  
ed with A/D conversion on the boards. Try resetting the power  
and check the indicator lights. If the alarm continues, the board  
should be replaced.  
A172 (Loss of Communication with the EXV Board)  
This alarm indicates that there are communications problems  
with the EXV board. The alarm will automatically reset.  
T173 (Energy Management Module Communication Fail-  
ure) — This alert indicates that there are communications  
problems with the energy management. All functions per-  
formed by the EMM will stop, which can include demand lim-  
it, reset and capacity input. The alarm will automatically reset.  
T174 (4 to 20 mA Cooling Set Point Input Failure) — This  
alert indicates a problem has been detected with cooling set  
point 4 to 20 mA input. The input value is either less than 2 mA  
or greater than 22 mA.  
T175 (Loss of Communication with the AUX Board) —  
This alarm indicates that there are communications problems  
with the AUX board. All functions performed by the AUX  
board will stop, which can include digital scroll unloader oper-  
ation and low ambient head pressure control. The alarm will  
automatically reset.  
4. With the above information, the test for reverse rotation is  
made. If the suction pressure change 5 seconds after com-  
pression is greater than the suction pressure change 5 sec-  
onds before compression – 1.25, then there is a reverse  
rotation error.  
This alarm will disable mechanical cooling and will require  
manual reset.  
A150 (Unit is in Emergency Stop) — If the CCN emergency  
stop command is received, the alarm is generated and the unit  
will be immediately stopped.  
If the CCN point name "EMSTOP" in the system table is set  
to emergency stop, the unit will shut down immediately and  
broadcast an alarm back to the CCN, indicating that the unit is  
down. This alarm will clear when the variable is set back to  
"enable."  
T176 (4 to 20 mA Reset Input Failure) — This alert indi-  
cates a problem has been detected with reset 4 to 20 mA input.  
The input value is either less than 2 mA or greater than 22 mA.  
The reset function will be disabled when this occurs.  
T177 (4 to 20 mA Demand Limit Input Failure)  
This  
alert indicates a problem has been detected with demand limit  
4 to 20 mA input. The input value is either less than 2 mA or  
greater than 22 mA. The reset function will be disabled when  
this occurs.  
A151 (Illegal Configuration) — An A151 alarm indicates an  
invalid configuration has been entered. The following are ille-  
gal configurations.  
• Invalid unit size has been entered.  
T500, T501 (Current Sensor Board Failure — A xx Circuit  
A)  
• Dual thermostat configured for single-circuit unit.  
• Dual thermostat and switch demand limit configure  
• AUX board incorrect revision.  
T503, T504 (Current Sensor Board Failure — B xx Circuit  
B) — Alert codes 500, 501, 503, and 504 are for compressors  
A1, A2, B1, and B2 respectively. These alerts occur when the  
output of the CSB is a constant high value. These alerts reset  
automatically. If the problem cannot be resolved, the CSB must  
be replaced.  
• Unit configuration set to invalid type.  
A152 (Unit Down Due to Failure) — Both circuits are off  
due to alerts and/or alarms. Reset is automatic when all alarms  
are cleared. This alarm indicates the unit is at 0% capacity.  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — DISPLAY TABLES  
Run Status Mode and Sub-Mode Directory  
SUB-MODE  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
COMMENT  
AUTO VIEW OF RUN STATUS  
EWT  
LWT  
SETP  
CTPT  
LOD.F  
xxx.x ºF  
xxx.x ºF  
xxx.x ºF  
xxx.x ºF  
xxx  
Entering Fluid Temp  
Leaving Fluid Temp  
Active Set Point  
Control Point  
Load/Unload Factor  
0=Service Test  
1=Off Local  
2=Off CCN  
3=Off Time  
4=Off Emrgcy  
5=On Local  
6=On CCN  
7=On Time  
STAT  
Control Mode  
VIEW  
LD.PM  
OCC  
LS.AC  
MODE  
CAP  
STGE  
ALRM  
TIME  
Lead Pump  
Occupied  
YES/NO  
YES/NO  
YES/NO  
xxx  
x
xxx  
Low Sound Active  
Override Modes in Effect  
Percent Total Capacity  
Requested Stage  
Current Alarms & Alerts  
Time of Day  
xx.xx  
00:00-23:59  
1 - 12 (1 = January,  
2 = February, etc.)  
MNTH  
xx  
Month of Year  
DATE  
YEAR  
xx  
xx  
Day of Month  
Year of Century  
01-31  
UNIT RUN HOUR AND START  
HRS.U  
STR.U  
HR.P1  
HR.P2  
xxxx HRS  
xxxx  
xxxx HRS  
xxxx HRS  
Machine Operating Hours  
Machine Starts  
RUN  
Pump 1 Run Hours  
Pump 2 Run Hours  
CIRC AND COMP RUN HOURS  
HRS.A  
HRS.B  
HR.A1  
HR.A2  
HR.B1  
HR.B2  
xxxx HRS  
xxxx HRS  
xxxx HRS  
xxxx HRS  
xxxx HRS  
xxxx HRS  
Circuit A Run Hours  
Circuit B Run Hours  
Compressor A1 Run Hours  
Compressor A2 Run Hours  
Compressor B1 Run Hours  
Compressor B2 Run Hours  
HOUR  
74  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — DISPLAY TABLES (cont)  
Run Status Mode and Sub-Mode Directory (cont)  
SUB-MODE  
STRT  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
COMMENT  
COMPRESSOR STARTS  
ST.A1  
ST.A2  
ST.B1  
ST.B2  
xxxx  
xxxx  
xxxx  
xxxx  
Compressor A1 Starts  
Compressor A2 Starts  
Compressor B1 Starts  
Compressor B2 Starts  
PREVENTIVE MAINTENANCE  
PUMP  
SI.PM  
PUMP MAINTENANCE  
Pump Service Interval  
Pump 1 Service Countdown  
Pump 2 Service Countdown  
Pump 1 Maintenance Done  
Pump 2 Maintenance Done  
PUMP MAINTENANCE DATES  
MM/DD/YY HH:MM  
xxxx HRS  
xxxx HRS  
xxxx HRS  
YES/NO  
YES/NO  
P.1.DN  
P.2.DN  
P.1.MN  
P.2.MN  
PMDT  
P.1.M0  
P.1.M1  
P.1.M2  
P.1.M3  
P.1.M4  
P.2.M0  
P.2.M1  
P.2.M2  
P.2.M3  
P.2.M4  
STRN  
User Entry  
User Entry  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
STRAINER MAINTENANCE  
Strainer Srvc Interval  
Strainer Srvc Countdown  
Strainer Maint. Done  
STRAINER MAINTENANCE DATES  
MM/DD/YY HH:MM  
PM  
SI.ST  
xxxx HRS  
xxxx HRS  
YES/NO  
S.T.DN  
S.T.MN  
ST.DT  
S.T.M0  
S.T.M1  
S.T.M2  
S.T.M3  
S.T.M4  
COIL  
User Entry  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
COIL MAINTENANCE  
Coil Cleaning Srvc Int  
Coil Service Countdown  
Coil Cleaning Maint.Done  
COIL MAINTENANCE DATES  
MM/DD/YY HH:MM  
SI.CL  
xxxx HRS  
xxxx HRS  
YES/NO  
C.L.DN  
C.L.MN  
CL.DT  
C.L.M0  
C.L.M1  
C.L.M2  
C.L.M3  
C.L.M4  
User Entry  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
MM/DD/YY HH:MM  
SOFTWARE VERSION NUMBERS  
CESR131460-XXXXX  
MBB  
EXV  
AUX1  
EMM  
MARQ  
NAVI  
CESR131172-XXXXX  
CESR131333-XXXXX  
CESR131174-XXXXX  
CESR131171-XXXXX  
CESR130227-XXXXX  
VERS  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — DISPLAY TABLES (cont)  
Service Test Mode and Sub-Mode Directory  
SUB-MODE  
TEST  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
COMMENT  
To enable Service Test mode, move  
Enable/Off/Remote contact switch to  
OFF. Change TEST to ON.  
Service Test Mode  
Move switch to ENABLE  
OUTPUTS  
EXV % Open  
EXV % Open  
Fan 1 Relay  
Fan 2 Relay  
Fan 3 Relay  
Fan 4 Relay  
Fan 5 Relay  
Fan 6 Relay  
EXV.A  
EXV.B  
FAN1  
FAN2  
FAN3  
FAN4  
FAN5  
FAN6  
V.HPA  
V.HPB  
CLP.1  
CLP.2  
UL.TM  
CL.HT  
RMT.A  
xxx%  
xxx%  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
xx  
OUTS  
Var Head Press %  
Var Head Press %  
Cooler Pump Relay 1  
Cooler Pump Relay 2  
Comp A1 Unload Time  
Cooler/Pump Heater  
Remote Alarm Relay  
CIRCUIT A COMPRESSOR TEST  
Compressor A1 Relay  
Comp A1 Unload Time  
Compressor A2 Relay  
Minimum Load Valve Relay  
CIRCUIT B COMPRESSOR TEST  
Compressor B1 Relay  
Compressor B2 Relay  
xx  
ON/OFF  
ON/OFF  
xx  
ON/OFF  
ON/OFF  
CC.A1  
UL.TM  
CC.A2  
MLV  
ON/OFF  
xx  
ON/OFF  
ON/OFF  
CMPA  
CMPB  
CC.B1  
CC.B2  
ON/OFF  
ON/OFF  
Temperature Mode and Sub-Mode Directory  
SUB-MODE  
UNIT  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
COMMENT  
ENTERING AND LEAVING UNIT TEMPERATURES  
CEWT  
CLWT  
OAT  
SPT  
DLWT  
xxx.x °F  
xxx.x °F  
xxx.x °F  
xxx.x °F  
xxx.x °F  
Cooler Entering Fluid  
Cooler Leaving Fluid  
Outside Air Temperature  
Space Temperature  
Lead/Lag Leaving Fluid  
TEMPERATURES CIRCUIT A  
Saturated Condensing Tmp  
Saturated Suction Temp  
Compr Return Gas Temp  
Discharge Gas Temp  
Suction Superheat Temp  
TEMPERATURES CIRCUIT B  
Saturated Condensing Tmp  
Saturated Suction Temp  
Compr Return Gas Temp  
Suction Superheat Temp  
SCT.A  
SST.A  
RGT.A  
D.GAS  
SH.A  
xxx.x °F  
xxx.x °F  
xxx.x °F  
xxx.x °F  
xxx.x ΔF  
CIR.A  
CIR.B  
SCT.B  
SST.B  
RGT.B  
SH.B  
xxx.x °F  
xxx.x °F  
xxx.x °F  
xxx.x ΔF  
Pressures Mode and Sub-Mode Directory  
SUB-MODE  
PRC.A  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
COMMENT  
PRESSURES CIRCUIT A  
xxx.x PSIG  
xxx.x PSIG  
DP.A  
SP.A  
Discharge Pressure  
Suction Pressure  
PRESSURES CIRCUIT B  
PRC.B  
DP.B  
SP.B  
xxx.x PSIG  
xxx.x PSIG  
Discharge Pressure  
Suction Pressure  
76  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — DISPLAY TABLES (cont)  
Set Points Mode and Sub-Mode Directory  
SUB-MODE  
COOL  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
COOLING SET POINTS  
Cooling Set Point 1  
RANGE  
COMMENT  
CSP.1  
CSP.2  
CSP.3  
xxx.x °F  
xxx.x °F  
xxx.x °F  
–20 to 70  
–20 to 70  
–20 to 32  
Default: 44 F  
Default: 44 F  
Default: 32 F  
Cooling Set Point 2  
ICE Set Point  
HEAD PRESSURE SET POINTS  
Head Set Point  
H.DP  
F.ON  
F.OFF  
B.OFF  
F.DLT  
xxx.x °F  
xxx.x °F  
xxx.x °F  
xx.x  
85 to 120  
Default: 95 F  
Default: 95 F  
Default: 72 F  
Default: 23 F  
Default: 15 F  
Fan On Set Point  
Fan Off Set Point  
Base Fan Off Delta Temp  
Fan Stage Delta  
HEAD  
FRZ  
10 to 50  
0 to 50  
xxx  
BRINE FREEZE SET POINT  
Brine Freeze Point  
BR.FZ  
xx.x °F  
–20 to 34  
Default: 34 F  
Inputs Mode and Sub-Mode Directory  
SUB-MODE  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
GENERAL INPUTS  
Start/Stop Switch  
COMMENT  
STST  
FLOW  
PM.F.1  
PM.F.2  
HT.RQ  
DLS1  
DLS2  
ICED  
DUAL  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
Cooler Flow Switch  
Cooler Pump 1 Interlock  
Cooler Pump 2 Interlock  
Heat Request  
Demand Limit Switch 1  
Demand Limit Switch 2  
Ice Done  
GEN.I  
Dual Set Point Switch  
CIRCUIT INPUTS  
FKA1  
FKA2  
FKA3  
FKA4  
FKB1  
FKB2  
FKB3  
FKB4  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
Compressor A1 Feedback  
Compressor A2 Feedback  
Compressor A3 Feedback  
Compressor A4 Feedback  
Compressor B1 Feedback  
Compressor B2 Feedback  
Compressor B3 Feedback  
Compressor B4 Feedback  
CRCT  
4-20  
4-20 MA INPUTS  
DMND  
RSET  
CSP  
xx.x  
xx.x  
xx.x  
4-20 ma Demand Signal  
4-20 ma Reset Signal  
4-20 ma Cooling Set Point  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — DISPLAY TABLES (cont)  
Outputs Mode and Sub-Mode Directory  
SUB-MODE  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
COMMENT  
GENERAL OUTPUTS  
FAN1  
FAN2  
FAN3  
FAN4  
FAN5  
FAN6  
V.HPA  
V.HPB  
C.WP1  
C.WP2  
CLHT  
MLV.R  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
Fan 1 Relay  
Fan 2 Relay  
Fan 3 Relay  
Fan 4 Relay  
Fan 5 Relay  
GEN.O  
Fan 6 Relay  
Fan Speed Circuit A  
Fan Speed Circuit B  
Cooler Pump Relay 1  
Cooler Pump Relay 2  
Cooler/Pump Heater  
Minimum Load Valve Relay  
OUTPUTS CIRCUIT A EXV  
EXV.A  
APPR  
AP.SP  
X.SH.R  
S.SH.R  
SH_R  
OVR.A  
SPH.A  
ASH.S  
AMP.S  
PLM.A  
SPR.1  
ON/OFF  
ON/OFF  
ON/OFF  
EXV % Open  
Circuit A Approach  
Approach Setpoint  
SH Reset at Max Unl-Dig  
Digload to Start SH RST  
Amount of SH Reset  
EXVA Override  
Suction Superheat Temp  
Active Superheat Setpt  
Active Mop Setpt  
A.EXV  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
Cir A EXV Position Limit  
Spare 1 Temperature  
OUTPUTS CIRCUIT A EXV  
EXV.B  
APPR  
AP.SP  
OVR.B  
SPH.B  
ASH.S  
AMP.S  
PLM.B  
SPR.2  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
EXV % Open  
Circuit B Approach  
Approach Setpoint  
EXVB Override  
B.EXV  
Suction Superheat Temp  
Active Superheat Setpt  
Active Mop Setpt  
Cir B EXV Position Limit  
Spare 2 Temperature  
OUTPUTS CIRCUIT A  
CC.A1  
DPE.R  
CC.A2  
CC.A3  
CC.A4  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
Compressor A1 Relay  
Comp A1 Load Percent  
Compressor A2 Relay  
Compressor A3 Relay  
Compressor A4 Relay  
CIR.A  
CIR.B  
OUTPUTS CIRCUIT B  
CC.B1  
CC.B2  
CC.B3  
CC.B4  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
Compressor B1 Relay  
Compressor B2 Relay  
Compressor B3 Relay  
Compressor B4 Relay  
78  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — DISPLAY TABLES (cont)  
Configuration Mode and Sub-Mode Directory  
SUB-MODE  
DISP  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
DISPLAY CONFIGURATION  
Test Display LEDs  
COMMENT  
TEST  
METR  
ON/OFF  
ON/OFF  
Metric Display  
Off = English On = Metric  
Default: 0  
0 = English  
1 = Espanol  
2 = Francais  
3 = Portuguese  
LANG  
X
Language Selection  
PAS.E  
PASS  
ENBL/DSBL  
XXXX  
Password Enable  
Service Password  
UNIT CONFIGURATION  
Unit Size  
SIZE  
SZA.1  
SZA.2  
SZA.3  
SZA.4  
SZB.1  
SZB.2  
SZB.3  
SZB.4  
SH.SP  
FAN.S  
EXV  
XX  
XX  
XX  
XX  
XX  
XX  
XX  
XX  
XX  
Compressor A1 Size  
Compressor A2 Size  
Compressor A3 Size  
Compressor A4 Size  
Compressor B1 Size  
Compressor B2 Size  
Compressor B3 Size  
Compressor B4 Size  
Suction Superheat Setpt  
Number of Fans  
UNIT  
X
Default: 5  
YES/NO  
YES/NO  
EXV Module Installed  
Compressor A1 Digital  
A1.TY  
Default: No  
Default: 7  
MAX.T  
FLUD  
XX  
Maximum A1 Unload Time  
Max = 12 (010,015)  
Max = 10 (018-060)  
UNIT OPTIONS 1 HARDWARE  
Cooler Fluid  
X
Default: Water  
1 = Water  
2 = Medium Temperature Brine  
MLV.S  
CSB.E  
CPC  
PM1E  
PM2E  
PM.P.S  
PM.SL  
YES/NO  
ENBL/DSBL  
ON/OFF  
YES/NO  
YES/NO  
YES/NO  
X
Minimum Load Valve Select  
Csb Boards Enable  
Default: Enable  
Default: Off  
Cooler Pump Control  
Cooler Pump 1 Enable  
Cooler Pump 2 Enable  
Cooler Pmp Periodic Strt  
Cooler Pump Select  
Default: No  
OPT1  
Default: Automatic  
0 = Automatic  
1 = Pump 1 Starts first  
2 = Pump 2 Starts first  
PM.DY  
PM.DT  
ROT.P  
EMM  
CND.T  
MOPS  
APPR  
XX MIN  
XXXX HRS  
YES/NO  
YES/NO  
X
Cooler Pump Shutdown Dly  
Pump Changeover Hours  
Rotate Cooler Pumps Now  
EMM Module Installed  
Cnd HX Typ:0=RTPF 1=MCHX  
EXV MOP Set Point  
0 to 10 minutes, Default: 1 min.  
Default: 500 hours  
User Entry  
XX  
XX  
Config Approach Set Point  
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — DISPLAY TABLES (cont)  
Configuration Mode and Sub-Mode Directory (cont)  
SUB-MODE  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
COMMENT  
UNIT OPTIONS 2 CONTROLS  
Default: 0  
0 = Enable/Off/Remote Switch  
2 = Occupancy  
CTRL  
LOAD  
LLCS  
X
X
X
Control Method  
3 = CCN Control  
Default: 1  
1 = Equal  
2 = Staged  
Loading Sequence Select  
Lead/Lag Circuit Select  
Default: 1  
1 = Automatic  
2 = Circuit A Leads  
3 = Circuit B Leads  
Default: 60  
OPT2  
LCWT  
DELY  
XX  
XX  
High LCW Alert Limit  
Minutes Off Time  
Range: 2 to 60 F  
Default: 0 Minutes  
Range: 0 to 15 Minutes  
ICE.M  
LS.MD  
ENBL/DSBL  
X
Ice Mode Enable  
Low Sound Mode Select  
Default: Disable  
Default: 0  
0 = Mode Disable  
1 = Fan Noise Only  
2 = Fan/Compressor Noise  
LS.ST  
LS.ND  
00:00  
00:00  
Low Sound Start Time  
Low Sound End Time  
Default: 00:00  
Default: 00:00  
Default: 100%  
LS.LT  
XXX %  
Low Sound Capacity Limit  
CCN NETWORK CONFIGS  
CCN Address  
Range: 0 to 100%  
Default: 1  
Range: 0 to 239  
Default: 1  
Range: 0 to 239  
CCNA  
CCNB  
XXX  
XXX  
CCN Bus Number  
CCN  
Default: 3  
1 = 2400  
2 = 4800  
3 = 9600  
4 =19,200  
5 =38,400  
BAUD  
X
CCN Baud Rate  
HEAD PRESSURE CMP. DELTA  
SCT Delta For Comp A1  
Default:12  
A1.DT  
A2.DT  
XX  
XX  
HP.A  
HP.B  
Range: 0 to 50  
Default:12  
Range: 0 to 50  
SCT Delta For Comp A2  
HEAD PRESSURE CMP. DELTA  
SCT Delta For Comp B1  
Default:12  
Range: 0 to 50  
Default:12  
Range: 0 to 50  
B1.DT  
B2.DT  
XX  
XX  
SCT Delta For Comp B2  
80  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — DISPLAY TABLES (cont)  
Configuration Mode and Sub-Mode Directory (cont)  
SUB-MODE  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
COMMENT  
CIR A EXV CONFIGURATION  
Default: 50  
0 to 100  
STR.A  
XXX  
EXV CIrc.A Start Pos  
Default: 8  
0 to 100  
0 to 65535  
Default: 200  
0 to 65535  
MIN.A  
RNG.A  
SPD.A  
XXX  
EXV Circ.A Min Position  
EXVA Steps In Range  
EXVA STeps Per Second  
XXXXX  
XXXXX  
Default: 0  
0 to 100  
POF.A  
XXX  
EXVA Fail Position In %  
Default: 0  
MIN.A  
MAX.A  
OVR.A  
XXXXX  
XXXXX  
XXX  
EXVA Minimum Steps  
EXVA Maximum Steps  
EXVA Overrun Steps  
0 to 65535  
0 to 65535  
Default: 167  
0 to 65535  
Default: 1  
0 = UNIPOLAR  
1 = BIPOLAR  
EXV.A  
TYP.A  
0,1  
EXVA Stepper Type  
Default: 115  
50 to 140  
Default: 10  
0 to 30  
Default: 5  
0 to 30  
Default: 10  
0 to 100  
Default: 10  
0 to 100  
Default: 10  
0 to 100  
Default: 10  
0 to 100  
H.SCT  
X.PCT  
X.PER  
A.PCT  
M.PCT  
S.PCT  
DELY  
XXX  
XX  
High SCT Threshold  
Open EXV X% On 2nd Comp  
Move EXV X% On DISCRSOL  
Pre-open EXV - Fan Adding  
Pre-close EXV - Fan Sub  
Pre-close EXV - Lag Shut  
XX  
XXX  
XXX  
XXX  
XXX  
Lag Start Delay  
CIR B EXV CONFIGURATION  
EXV CIrc.B Start Pos  
Default: 50  
0 to 100  
STR.B  
XXX  
Default: 8  
0 to 100  
0 to 65535  
Default: 200  
0 to 65535  
MIN.B  
RNG.B  
SPD.B  
XXX  
EXV Circ.B Min Position  
EXVB Steps In Range  
EXVB STeps Per Second  
XXXXX  
XXXXX  
Default: 0  
0 to 100  
EXV.B  
POF.B  
XXX  
EXVB Fail Position In %  
Default: 0  
MIN.B  
MAX.B  
OVR.B  
XXXXX  
XXXXX  
XXX  
EXVB Minimum Steps  
EXVB Maximum Steps  
EXVB Overrun Steps  
0 to 65535  
0 to 65535  
Default: 167  
0 to 65535  
Default: 1  
0 = UNIPOLAR  
1 = BIPOLAR  
TYP.B  
0,1  
EXVB Stepper Type  
81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — DISPLAY TABLES (cont)  
Configuration Mode and Sub-Mode Directory (cont)  
SUB-MODE  
MM  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
MOTORMASTER  
COMMENT  
MMR.S  
P.GAN  
YES/NO  
XX  
Motormaster Select  
Default: NO  
Default: 1  
Range: 1 to 4  
Default: 0.1  
Range: -20 to 20  
Head Pressure P Gain  
I.GAN  
XX.X  
Head Pressure I Gain  
Default: 0.0  
D.GAN  
MIN.S  
XX.X  
XX  
Head Pressure D Gain  
Minimum Fan Speed  
Range: -20 to 20  
Default: 5  
RESET COOL TEMP  
Default: 0  
0 = No Reset  
1 = 4 to 20 mA Input  
2 = Outdoor Air Temperature  
3 = Return Fluid  
CRST  
X
Cooling Reset Type  
4 = Space Temperature  
Default: 0.0 ΔF  
MA.DG  
RM.NO  
RM.F  
XX.XΔF  
XXX.X °F  
XXX.X °F  
XX.X °F  
XXX.XΔF  
XXX.XΔF  
XX.X °F  
4-20 - Degrees Reset  
Remote - No Reset Temp  
Remote - Full Reset Temp  
Remote - Degrees Reset  
Return - No Reset Temp  
Return - Full Reset Temp  
Return - Degrees Reset  
Range: -30 to 30 ΔF  
Default: 125 F  
Range: 0° to125 F  
Default: 0 F  
Range: 0° to125 F  
Default: 0.0 ΔF  
Range: -30 to 30 ΔF  
Default: 10.0 ΔF  
Range: 0° to125 F  
Default: 0 ΔF  
Range: 0° to125 F  
Default: 0.0 ΔF  
Range: -30 to 30 ΔF  
RM.DG  
RT.NO  
RT.F  
RT.DG  
Default: 0  
0 = None  
DMDC  
X
Demand Limit Select  
1 = Switch  
2 - 4 to 20 mA Input  
3 = CCN Loadshed  
Default: 100%  
RSET  
DM20  
SHNM  
SHDL  
SHTM  
DLS1  
DLS2  
XXX%  
XXX  
Demand Limit at 20 mA  
Loadshed Group Number  
Loadshed Demand Delta  
Maximum Loadshed Time  
Demand Limit Switch 1  
Demand Limit Switch 2  
Range: 0 to 100%  
Default: 0  
Range: 0 to 99  
Default: 0%  
Range: 0 to 60%  
XXX%  
XXX  
Default: 60 minutes  
Range: 0 to 120 minutes  
Default: 80%  
Range: 0 to 100%  
Default: 50%  
Range: 0 to 100%  
XXX%  
XXX%  
LLEN  
MSSL  
SLVA  
ENBL/DSBL  
SLVE/MAST  
XXX  
Lead/Lag Chiller Enable  
Master/Slave Select  
Slave Address  
Default: Disable  
Default: Master  
Default: 2  
Range: 0 to 239  
Default: Master Leads  
0 = Master Leads  
1 = Slave Leads  
2 = Automatic  
LLBL  
X
Lead/Lag Balance Select  
Default: 168 hours  
LLBD  
LLDY  
PARA  
XXX  
XXX  
YES  
Lead/Lag Balance Delta  
Lag Start Delay  
Range: 40 to 400 hours  
Default: 5 minutes  
Range: 0 to 30 minutes  
Default: YES (CANNOT BE  
CHANGED)  
Parallel Configuration  
82  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — DISPLAY TABLES (cont)  
Configuration Mode and Sub-Mode Directory (cont)  
SUB-MODE  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
COMMENT  
SETPOINT AND RAMP LOAD  
Default: Single  
0 = Single  
1 = Dual Switch  
CLSP  
X
Cooling Set Point Select  
2 = Dual CCN Occupied  
3 = 4 to 20 mA  
Input (requires EMM)  
SLCT  
RL.S  
ENBL/DSBL  
ENBL/DSBL  
Ramp Load Select  
Default: Enable  
Default: 1.0  
Range: 0.3 to 2  
CRMP  
Cooling Ramp Loading  
Default: 1  
SCHD  
Z.GN  
XX  
Schedule Number  
Range: 1 to 99  
Default: 1  
Range: 1 to 4  
X.X  
Deadband Multiplier  
SERVICE CONFIGURATION  
Enable Compressor A1  
Enable Compressor A2  
Enable Compressor B1  
Enable Compressor B2  
BROADCAST CONFIGURATION  
CCN Time/Date Broadcast  
CCN OAT Broadcast  
EN.A1  
EN.A2  
EN.B1  
EN.B2  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
SERV  
BCST  
T.D.B  
OAT.B  
G.S.BC  
BC.AK  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
Global Schedule Broadcst  
CCN Broadcast Ack'er  
83  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — DISPLAY TABLES (cont)  
Time Clock Mode and Sub-Mode Directory  
SUB-MODE  
TIME  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
TIME OF DAY  
Hour and Minute  
COMMENT  
HH.MM  
XX.XX  
Military (00:00 - 23:59)  
MONTH, DATE, DAY, AND YEAR  
1 - 12 (1 = January,  
2 = February, etc.)  
Range: 01 -31  
1 - 7 (1 = Sunday,  
2 = Monday, etc.)  
MNTH  
DOM  
DAY  
XX  
XX  
Month of Year  
DATE  
Day of Month  
Day of Week  
X
YEAR  
XXXX  
Year of Century  
DAYLIGHT SAVINGS TIME  
STR.M  
STR.W  
STR.D  
MIN.A  
STP.M  
STP.W  
STP.D  
MIN.S  
XX  
X
X
XX  
XX  
XX  
XX  
XX  
Month  
Week  
Day  
Default: 4 Range 1- 12  
Default: 1 Range 1- 5  
Default: 7 Range 1- 7  
Default: 60 Range 0 - 99  
Default: 10 Range 1- 12  
Default: 5 Range 1- 5  
Default: 7 Range 1- 7  
Default: 60 Range 0 - 99  
DST  
Minutes to Add  
Month  
Week  
Day  
Minutes to Subtract  
HOL.L  
HD.01  
LOCAL HOLIDAY SCHEDULES  
HOLIDAY SCHEDULE 01  
MON  
DAY  
LEN  
XX  
XX  
XX  
Holiday Start Month  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 02  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
HD.02  
HD.03  
HD.04  
HD.05  
HD.06  
HD.07  
HD.08  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 03  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 04  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 05  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 06  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 07  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 08  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
01-31  
84  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — DISPLAY TABLES (cont)  
Time Clock Mode and Sub-Mode Directory (cont)  
SUB-MODE  
HD.09  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
COMMENT  
HOLIDAY SCHEDULE 09  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
01-31  
HOLIDAY SCHEDULE 10  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
HD.10  
HD.11  
HD.12  
HD.13  
HD.14  
HD.15  
HD.16  
HD.17  
HD.18  
HD.19  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 11  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 12  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 13  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 14  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 15  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 16  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 17  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 18  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 19  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
01-31  
85  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — DISPLAY TABLES (cont)  
Time Clock Mode and Sub-Mode Directory (cont)  
SUB-MODE  
HD.20  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
COMMENT  
HOLIDAY SCHEDULE 20  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
01-31  
HOLIDAY SCHEDULE 21  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
HD.21  
HD.22  
HD.23  
HD.24  
HD.25  
HD.26  
HD.27  
HD.28  
HD.29  
HD.30  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 22  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 23  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 24  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 25  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 26  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 27  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 28  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 29  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
HOLIDAY SCHEDULE 30  
01-31  
1 - 12 (1 = January,  
2 = February, etc.)  
MON  
XX  
Holiday Start Month  
DAY  
LEN  
XX  
XX  
Start Day  
Duration (days)  
01-31  
86  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — DISPLAY TABLES (cont)  
Time Clock Mode and Sub-Mode Directory (cont)  
SUB-MODE  
SCH.N  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
Schedule Number 0  
COMMENT  
SCH.L  
LOCAL OCCUPANCY SCHEDULE  
OCCUPANCY PERIOD 1  
OCC.1  
UNC.1  
MON.1  
TUE.1  
WED.1  
THU.1  
FRI.1  
SAT.1  
SUN.1  
HOL.1  
XX:XX  
XX:XX  
Period Occupied Time  
Military (00:00 - 23:59)  
Military (00:00 - 23:59)  
Period Unoccupied Time  
Monday In Period  
Tuesday In Period  
Wednesday In Period  
Thursday In Period  
Friday In Period  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
PER.1  
PER.2  
PER.3  
PER.4  
PER.5  
Saturday In Period  
Sunday In Period  
Holiday In Period  
OCCUPANCY PERIOD 2  
XX:XX  
XX:XX  
OCC.2  
UNC.2  
MON.2  
TUE.2  
WED.2  
THU.2  
FRI.2  
SAT.2  
SUN.2  
HOL.2  
Period Occupied Time  
Period Unoccupied Time  
Monday In Period  
Tuesday In Period  
Wednesday In Period  
Thursday In Period  
Friday In Period  
Military (00:00 - 23:59)  
Military (00:00 - 23:59)  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
Saturday In Period  
Sunday In Period  
Holiday In Period  
OCCUPANCY PERIOD 3  
XX:XX  
XX:XX  
OCC.3  
UNC.3  
MON.3  
TUE.3  
WED.3  
THU.3  
FRI.3  
SAT.3  
SUN.3  
HOL.3  
Period Occupied Time  
Period Unoccupied Time  
Monday In Period  
Tuesday In Period  
Wednesday In Period  
Thursday In Period  
Friday In Period  
Military (00:00 - 23:59)  
Military (00:00 - 23:59)  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
Saturday In Period  
Sunday In Period  
Holiday In Period  
OCCUPANCY PERIOD 4  
XX:XX  
XX:XX  
OCC.4  
UNC.4  
MON.4  
TUE.4  
WED.4  
THU.4  
FRI.4  
SAT.4  
SUN.4  
HOL.4  
Period Occupied Time  
Period Unoccupied Time  
Monday In Period  
Tuesday In Period  
Wednesday In Period  
Thursday In Period  
Friday In Period  
Military (00:00 - 23:59)  
Military (00:00 - 23:59)  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
Saturday In Period  
Sunday In Period  
Holiday In Period  
OCCUPANCY PERIOD 5  
XX:XX  
XX:XX  
OCC.5  
UNC.5  
MON.5  
TUE.5  
WED.5  
THU.5  
FRI.5  
SAT.5  
SUN.5  
HOL.5  
Period Occupied Time  
Period Unoccupied Time  
Monday In Period  
Tuesday In Period  
Wednesday In Period  
Thursday In Period  
Friday In Period  
Military (00:00 - 23:59)  
Military (00:00 - 23:59)  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
Saturday In Period  
Sunday In Period  
Holiday In Period  
87  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — DISPLAY TABLES (cont)  
Time Clock Mode and Sub-Mode Directory (cont)  
SUB-MODE  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
COMMENT  
OCCUPANCY PERIOD 6  
OCC.6  
UNC.6  
MON.6  
TUE.6  
WED.6  
THU.6  
FRI.6  
SAT.6  
SUN.6  
HOL.6  
XX:XX  
XX:XX  
Period Occupied Time  
Period Unoccupied Time  
Monday In Period  
Tuesday In Period  
Wednesday In Period  
Thursday In Period  
Friday In Period  
Military (00:00 - 23:59)  
Military (00:00 - 23:59)  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
PER.6  
Saturday In Period  
Sunday In Period  
Holiday In Period  
OCCUPANCY PERIOD 7  
OCC.7  
UNC.7  
MON.7  
TUE.7  
WED.7  
THU.7  
FRI.7  
SAT.7  
SUN.7  
HOL.7  
XX:XX  
XX:XX  
Period Occupied Time  
Period Unoccupied Time  
Monday In Period  
Tuesday In Period  
Wednesday In Period  
Thursday In Period  
Friday In Period  
Military (00:00 - 23:59)  
Military (00:00 - 23:59)  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
PER.7  
Saturday In Period  
Sunday In Period  
Holiday In Period  
OCCUPANCY PERIOD 8  
OCC.8  
UNC.8  
MON.8  
TUE.8  
WED.8  
THU.8  
FRI.8  
SAT.8  
SUN.8  
HOL.8  
XX:XX  
XX:XX  
Period Occupied Time  
Period Unoccupied Time  
Monday In Period  
Tuesday In Period  
Wednesday In Period  
Thursday In Period  
Friday In Period  
Military (00:00 - 23:59)  
Military (00:00 - 23:59)  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
YES/NO  
PER.8  
Saturday In Period  
Sunday In Period  
Holiday In Period  
SCHEDULE OVERRIDE  
OVR.T  
OVR.L  
T.OVR  
X
X
Timed Override Hours  
Override Time Limit  
Timed Override  
Default: 0 Range 0-4 hours  
Default: 0 Range 0-4 hours  
User Entry  
OVR  
YES/NO  
88  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — DISPLAY TABLES (cont)  
Operating Mode and Sub-Mode Directory  
SUB-MODE  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
MODES CONTROLLING UNIT  
CSM Controlling Chiller  
WSM Controlling Chiller  
Master/Slave Control  
Ramp Load Limited  
COMMENT  
MD01  
MD02  
MD03  
MD05  
MD06  
MD07  
MD08  
MD09  
MD10  
MD13  
MD14  
MD15  
MD16  
MD17  
MD18  
MD19  
MD20  
MD21  
MD22  
MD23  
MD24  
MD25  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
Timed Override in effect  
Low Cooler Suction TempA  
Low Cooler Suction TempB  
Slow Change Override  
Minimum OFF time active  
Dual Set Point  
Temperature Reset  
Demand Limited  
Cooler Freeze Protection  
Low Temperature Cooling  
High Temperature Cooling  
Making Ice  
MODE  
Storing Ice  
High SCT Circuit A  
High SCT Circuit B  
Minimum Comp. On Time  
Pump Off Delay Time  
Low Sound Mode  
Alarms Mode and Sub-Mode Directory  
SUB-MODE  
CRNT  
ITEM  
DISPLAY  
ITEM DESCRIPTION  
COMMENT  
CURRENTLY ACTIVE ALARMS  
AXXX  
TXXX  
PXXX  
Alarms are hown as AXXX  
Alerts are shown as TXXX  
Current Alarms 1-25  
RCRN  
YES/NO  
Reset All Current Alarms  
ALARM HISTORY  
AXXX  
TXXX  
PXXX  
HIST  
Alarms are shown as AXXX  
Alerts are shown as TXXX  
Alarm History 1-20  
89  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — CCN TABLES  
CCN DISPLAY TABLES — A_UNIT (General Unit Parameters)  
DESCRIPTION  
Control Mode  
VALUE  
UNITS  
POINT NAME  
STAT  
FORCIBLE  
0 = Test  
N
1 = Local Off  
2 = CCN Off  
3 = Clock Off  
4 = Emergency Stop  
5 = Local On  
6 = CCN On  
7 = Clock On  
8 = Heat Enabled  
9 = Pump Delay  
Occupied  
CCN Chiller  
Low Sound Active  
Alarm State  
Active Demand Limit  
Override Modes in Effect  
Percent Total Capacity  
Requested Stage  
Active Set Point  
No/Yes  
Start/Stop  
No/Yes  
Normal/Alert/Alarm  
0 to 100  
No/Yes  
0 to 100  
0 to 99  
–20 to 70  
–20 to 70  
snnn.n  
OCC  
N
Y
N
N
Y
N
N
N
N
Y
N
N
Y
N
CHIL_S_S  
LSACTIVE  
ALM  
DEM_LIM  
MODE  
CAP_T  
STAGE  
SP  
CTRL_PNT  
EWT  
%
%
F  
F  
F  
F  
Enable  
minutes  
Control Point  
Entering Fluid Temp  
Leaving Fluid Temp  
Emergency Stop  
Minutes Left for Start  
PUMPS  
snnn.n  
Enable/Emstop  
00:00 to 15:00  
LWT  
EMSTOP  
MIN_LEFT  
Cooler Pump Relay 1  
Cooler Pump Relay 2  
Cooler Pump 1 Interlock  
Cooler Pump 2 Interlock  
Cooler Flow Switch  
Lead Pump  
Off/On  
Off/On  
Open/Close  
Open/Close  
Open/Close  
COOLPMP1  
COOLPMP2  
PMP1_FBK  
PMP2_FBK  
COOLFLOW  
LEADPUMP  
ROT_PUMP  
N
N
N
N
N
Y
Y
Rotate Cooler Pumps Now  
No/Yes  
Heat/Cool Select  
Heat/Cool  
HC_SEL  
N
CCN DISPLAY TABLES — CIRCA_AN (Circuit A Analog Parameters)  
DESCRIPTION  
CIRCUIT A ANALOG VALUES  
Percent Total Capacity  
Percent Available Cap.  
Discharge Pressure  
VALUE  
UNITS  
POINT NAME  
FORCIBLE  
0-100  
%
%
CAPA_T  
CAPA_A  
DP_A  
SP_A  
HSP  
TMP_SCTA  
TMP_SSTA  
EXV_A  
VHP_ACT  
TMP_RGTA  
DISGAS  
SH_A  
N
0-100  
nnn.n  
nnn.n  
nnn.n  
snnn.n  
snnn.n  
nnn  
nnn.n  
nnn.n  
nnn.n  
nnn.n  
nnn.n  
N
N
N
N
N
N
N
N
N
N
N
N
PSIG  
PSIG  
°F  
F  
F  
Suction Pressure  
Head Setpoint  
Saturated Condensing Tmp  
Saturated Suction Temp  
EXV % Open  
Var Head Press Output  
Compr Return Gas Temp  
Discharge Gas Temp  
Suction Superheat Temp  
Spare 1 Temperature  
%
milliamps  
F  
°F  
F  
°F  
SPR1_TMP  
90  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — CCN TABLES (cont)  
CCN DISPLAY TABLES — CIRCADIO (Circuit A Discrete Inputs/Outputs)  
DESCRIPTION  
CIRC. A DISCRETE OUTPUTS  
Compressor A1 Relay  
Compressor A2 Relay  
Minimum Load Valve Relay  
VALUE  
UNITS  
POINT NAME  
FORCIBLE  
On/Off  
On/Off  
On/Off  
K_A1_RLY  
K_A2_RLY  
MLV_RLY  
N
N
N
CIRC. A DISCRETE INPUTS  
Compressor A1 Feedback  
Compressor A2 Feedback  
On/Off  
On/Off  
K_A1_FBK  
K_A2_FBK  
N
N
CCN DISPLAY TABLES — CIRCB_AN (Circuit B Analog Parameters)  
DESCRIPTION  
CIRCUIT B ANALOG VALUES  
Percent Total Capacity  
Percent Available Cap.  
Discharge Pressure  
VALUE  
UNITS  
POINT NAME  
FORCIBLE  
0-100  
%
%
CAPB_T  
CAPB_A  
DP_B  
SP_B  
HSP  
TMP_SCTB  
TMP_SSTB  
EXV_B  
VHP_ACT  
TMP_RGTB  
SH_B  
N
N
N
N
N
N
N
N
N
N
N
N
0-100  
nnn.n  
nnn.n  
nnn.n  
snnn.n  
snnn.n  
nnn  
nnn.n  
nnn.n  
nnn.n  
nnn.n  
PSIG  
PSIG  
°F  
F  
F  
Suction Pressure  
Head Setpoint  
Saturated Condensing Tmp  
Saturated Suction Temp  
EXV % Open  
Var Head Press Output  
Compr Return Gas Temp  
Suction Superheat Temp  
Spare 2 Temperature  
%
milliamps  
F  
F  
°F  
SPR2_TMP  
CCN DISPLAY TABLES — CIRCBDIO (Circuit B Discrete Inputs/Outputs)  
DESCRIPTION  
CIRC. B DISCRETE OUTPUTS  
Compressor B1 Relay  
Compressor B2 Relay  
Minimum Load Valve Relay  
VALUE  
UNITS  
POINT NAME  
FORCIBLE  
On/Off  
On/Off  
On/Off  
K_B1_RLY  
K_B2_RLY  
MLV_RLY  
N
N
N
CIRC. B DISCRETE INPUTS  
Compressor B1 Feedback  
Compressor B2 Feedback  
On/Off  
On/Off  
K_B1_FBK  
K_B2_FBK  
N
N
91  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — CCN TABLES (cont)  
CCN DISPLAY TABLES — OPTIONS (Unit Parameters)  
DESCRIPTION  
VALUE  
UNITS  
POINT NAME  
FORCIBLE  
FANS  
Fan 1 Relay  
Fan 2 Relay  
Cooler/Pump Heater  
Off/On  
Off/On  
Off/On  
FAN_1  
FAN_2  
COOL_HTR  
N
N
N
UNIT ANALOG VALUES  
Cooler Entering Fluid  
Cooler Leaving Fluid  
Lead/Lag Leaving Fluid  
snnn.n  
snnn.n  
snnn.n  
F  
F  
F  
COOL_EWT  
COOL_LWT  
DUAL_LWT  
N
N
N
TEMPERATURE RESET  
4-20 mA Reset Signal  
Outside Air Temperature  
Space Temperature  
nn.n  
snnn.n  
snnn.n  
mA  
F  
F  
RST_MA  
OAT  
SPT  
N
Y
Y
DEMAND LIMIT  
4-20 mA Demand Signal  
Demand Limit Switch 1  
Demand Limit Switch 2  
CCN Loadshed Signal  
nn.n  
Off/On  
Off/On  
0 = Normal  
1 = Redline  
2 = Loadshed  
mA  
LMT_MA  
N
N
N
N
DMD_SW1  
DMD_SW2  
DL_STAT  
MISCELLANEOUS  
Heat Request  
Dual Setpoint Switch  
Cooler LWT Setpoint  
Ice Done  
Off/On  
Off/On  
snnn.n  
Off/On  
HEAT_REQ  
DUAL_IN  
LWT_SP  
N
N
N
N
F  
ICE_DONE  
CCN CONFIGURATION TABLES — UNIT (Unit Configuration)  
DESCRIPTION  
Unit Size  
VALUE  
DEFAULT  
UNITS  
tons  
tons  
tons  
tons  
POINT NAME  
SIZE  
nnn  
nnn  
nnn  
nnn  
nnn  
nn.n  
n
Compressor A1 Size  
Compressor A2 Size  
Compressor B1 Size  
Compressor B2 Size  
Suction Superheat Setpt  
Number of Fans  
SIZE_A1  
SIZE_A2  
SIZE_B1  
SIZE_B2  
SH_SP  
FAN_TYPE  
CPA1TYPE  
MAXULTME  
tons  
F  
9.0  
Compressor A1 Digital?  
Maximum A1 Unload Time  
No/Yes  
nn  
No  
12  
sec  
CCN CONFIGURATION TABLES — OPTIONS1 (Options 1 Configuration)  
DESCRIPTION  
Cooler Fluid  
VALUE  
DEFAULT  
1
UNITS  
POINT NAME  
FLUIDTYP  
1 = Water  
2 = Med. Brine  
No/Yes  
Dsable/Enable  
Off/On  
No/Yes  
No/Yes  
No/Yes  
0 = Automatic, 1 =  
Pump 1, 2 = Pump 2  
Minimum Load Vlv Select  
CSB Board Enable  
No  
MLV_FLG  
CSB_ENA  
CPC  
PMP1_ENA  
PMP2_ENA  
PUMP_PST  
PMP_SLCT  
Enable  
Off  
No  
No  
No  
Cooler Pump Control  
Cooler Pump 1 Enable  
Cooler Pump 2 Enable  
Cooler Pmp Periodic Strt  
Cooler Pump Select  
0
Cooler Pump Shutdown Dly  
Pump Changeover Hours  
EMM Module Installed  
Cnd HX Typ: 0=RTPF 1=MCHX  
EXV MOP Set Point  
0 to 10  
10 to 2000  
No/Yes  
0/1  
nn.n  
nn.n  
1
minutes  
hours  
PUMP_DLY  
PMP_DLTA  
EMM_BRD  
COILTYPE  
MOP_SP  
100  
No  
1
°F  
°F  
Config Approach Setpoint  
IAPPROSP  
92  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — CCN TABLES (cont)  
CCN CONFIGURATION TABLES — OPTIONS2 (Options 2 Configuration)  
DESCRIPTION  
Control Method  
VALUE  
DEFAULT  
0
UNITS  
POINT NAME  
CONTROL  
0 = Switch  
2 = Occupancy  
3 = CCN  
Loading Sequence Select  
Lead/Lag Circuit Select  
1 = Equal Loading  
2 = Staged Loading  
1 = Automatic  
2 = Circuit A Leads  
3 = Circuit B Leads  
1
1
SEQ_TYP  
LEAD_TYP  
Cooling Setpoint Select  
0 = Single  
0
CLSP_TYP  
1 = Dual, remote switch controlled  
2 = Dual CCN occupancy  
3 = 4-20 mA input  
Ramp Load Select  
Heat Cool Select  
High LCW Alert Limit  
Minutes off time  
Enable/Dsable  
Cool/Heat  
2 to 60  
Enable  
Cool  
60.0  
0
RAMP_EBL  
HEATCOOL  
LCW_LMT  
DELAY  
F  
min  
0 to 15  
Deadband Multiplier  
Ice Mode Enable  
Low Sound Mode Select  
1.0 to 4.0  
Enable/Dsable  
1.0  
Dsable  
0
Z_GAIN  
ICE_CNFG  
LS_MODE  
0 = Disabled  
1 = Fan only  
2 = Capacity/Fans  
Low Sound Start Time  
Low Sound End Time  
Low Sound Capacity Limit  
00:00 to 23:59  
00:00 to 23:59  
0 to 100  
00:00  
00:00  
100  
LS_START  
LS_END  
LS_LIMIT  
%
CCN CONFIGURATION TABLES — SCHEDOVR (Timed Override Setup)  
DESCRIPTION  
Schedule Number  
Override Time Limit  
Timed Override Hours  
Timed Override  
VALUE  
0 to 99  
0 to 4  
0 to 4  
No/Yes  
DEFAULT  
1
0
0
UNITS  
POINT NAME  
SCHEDNUM  
OTL  
OVR_EXT  
TIMEOVER  
hours  
hours  
No  
CCN CONFIGURATION TABLES — RESETCON (Temperature Reset and Demand Limit)  
DESCRIPTION  
COOLING RESET  
VALUE  
DEFAULT  
UNITS  
POINT NAME  
Cooling Reset Type  
0 = No Reset  
0
CRST_TYP  
1 = 4-20 mA input  
2 = External temp – OAT  
3 = Return Fluid  
4 = External temp - SPT  
4-20 MA RESET  
4-20 – Degrees Reset  
–30 to 30  
0.0  
F  
420_DEG  
REMOTE RESET  
Remote – No Reset Temp  
Remote – Full Reset Temp  
Remote – Degrees Reset  
0 to 125  
0 to 125  
–30 to 30  
125.0  
0.0  
0.0  
F  
F  
F  
REM_NO  
REM_FULL  
REM_DEG  
RETURN TEMPERATURE RESET  
Return – No Reset Temp  
Return – Full Reset Temp  
Return – Degrees Reset  
0 to 125  
0 to 125  
–30 to 30  
10.0  
0.0  
0.0  
F  
F  
F  
RTN_NO  
RTN_FULL  
RTN_DEG  
DEMAND LIMIT  
Demand Limit Select  
0 = None  
0
DMD_CTRL  
1 = External switch input  
2 = 4-20 mA input  
3 = Loadshed  
Demand Limit at 20 mA  
Loadshed Group Number  
Loadshed Demand Delta  
Maximum Loadshed Time  
Demand Limit Switch 1  
Demand Limit Switch 2  
0 to 100  
0 to 99  
0 to 60  
0 to 120  
0 to 100  
0 to 100  
100  
0
0
60  
80  
50  
%
DMT20MA  
SHED_NUM  
SHED_DEL  
SHED_TIM  
DLSWSP1  
DLSWSP2  
%
minutes  
%
%
93  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — CCN TABLES (cont)  
CCN CONFIGURATION TABLES — DUALCHIL (Dual Chiller Configuration Settings)  
DESCRIPTION  
LEAD/LAG  
VALUE  
DEFAULT  
UNITS  
POINT NAME  
Lead/Lag Chiller Enable  
Master/Slave Select  
Slave Address  
Lead/Lag Balance Select  
Lead/Lag Balance Delta  
Lag Start Delay  
Enable/Dsable  
Master/Slave  
0 to 239  
0 = None  
40 to 400  
0 to 30  
Dsable  
Master  
2
0
168  
5
Yes  
LL_ENA  
MS_SEL  
SLV_ADDR  
LL_BAL  
LL_BAL_D  
LL_DELAY  
PARALLEL  
hours  
minutes  
Parallel Configuration  
Yes  
CCN CONFIGURATION TABLES — DISPLAY (Marquee Display SETUP)  
DESCRIPTION  
Service Password  
Password Enable  
Metric Display  
VALUE  
DEFAULT  
1111  
Enable  
Off  
UNITS  
POINT NAME  
PASSWORD  
PASS_EBL  
DISPUNIT  
nnnn  
Enable/Disable  
Off/On  
Language Selection  
0 = ENGLISH  
0
LANGUAGE  
1 = FRANCAIS  
2 = ESPANOL  
3 = PORTUGUES  
CCN CONFIGURATION TABLES — EXVACONF (EXV Circuit A Configuration)  
DESCRIPTION  
VALUE  
nnn.n  
DEFAULT  
UNITS  
%
%
steps  
steps  
%
steps  
steps  
steps  
POINT NAME  
EXVASTRT  
EXVAMINP  
EVXARANG  
EXVARATE  
EXVAPOSF  
EXVAMINS  
EXVAMAXS  
EXVAOVRS  
EXVATYPE  
HIGH_SCT  
EXV_HSCT  
EXVDISCR  
EXV_AFAN  
EXV_MFAN  
EXV_SLAG  
DELAYLAG  
EXV Circ. A Start Pos  
EXV Circ. A Min Position  
EXVA Steps in Range  
EXVA Steps Per Second  
EXVA Fail Position in %  
EXVA Minimum Steps  
EXVA Maximum Steps  
EXVA Overrun Steps  
50.0  
8.0  
1596/2500  
nnn.n  
nnnnn  
nnnnn  
nnnn.nn  
nnnnn  
nnnnn  
nnnnn  
nnn  
nnn.n  
nnn.n  
nnn.n  
nnn.n  
nnn.n  
nnn.n  
nnn  
200  
0
0
1596/2500  
167  
Bipolar  
115  
10  
EXVA Stepper Type  
High SCT Threshold  
°F  
%
%
%
%
Open EXV X% on 2nd Comp  
Open EXV X% on DISCRSOL  
Pre-Open EXV - Fan Adding  
Pre-Close EXV - Fan Sub  
Pre-Close EXV - Lag Shut  
Lag Start Delay  
5
10  
10  
10  
%
secs  
10  
CCN CONFIGURATION TABLES — EXVBCONF (EXV Circuit B Configuration)  
DESCRIPTION  
EXV Circ. B Start Pos  
VALUE  
nnn.n  
DEFAULT  
50.0  
8.0  
1596/2500  
200  
UNITS  
%
%
steps  
steps  
%
steps  
steps  
steps  
POINT NAME  
EXVBSTRT  
EXVBMINP  
EVXBRANG  
EXVBRATE  
EXVBPOSF  
EXVBMINS  
EXVBMAXS  
EXVBOVRS  
EXVBTYPE  
EXV Circ. B Min Position  
EXVB Steps in Range  
EXVB Steps Per Second  
EXVB Fail Position in %  
EXVB Minimum Steps  
EXVB Maximum Steps  
EXVB Overrun Steps  
EXVB Stepper Type  
nnn.n  
nnnnn  
nnnnn  
nnnn.nn  
nnnnn  
nnnnn  
nnnnn  
nnn  
0
0
1596/2500  
167  
Bipolar  
CCN CONFIGURATION TABLES — MM_CONF (Motormaster Configuration)  
DESCRIPTION  
Motormaster Select  
Head Pressure P Gain  
Head Pressure I Gain  
Head Pressure D Gain  
Minimum Fan Speed  
VALUE  
No/Yes  
nnn.n  
nnn.n  
nnn.n  
nnn.n  
DEFAULT  
No  
UNITS  
POINT NAME  
MM_SLCT  
HP_PGAIN  
HP_IGAIN  
HP_DGAIN  
MIN_VHP  
1.0  
0.1  
0.0  
5.0  
%
94  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — CCN TABLES (cont)  
CCN SERVICE TABLES — SERVICE  
DESCRIPTION  
SERVICE  
Brine Freeze Point  
Pump Service Interval  
COMPRESSOR ENABLE  
Enable Compressor A1  
Enable Compressor A2  
Enable Compressor B1  
Enable Compressor B2  
VALUE  
DEFAULT  
UNITS  
F  
POINT NAME  
nnn.n  
nnnnn  
BRN_FRZ  
SI_PUMPS  
hours  
Disable/Enable  
Disable/Enable  
Disable/Enable  
Disable/Enable  
ENABLEA1  
ENABLEA2  
ENABLEB1  
ENABLEB2  
CCN SETPOINT TABLES — SETPOINT  
DESCRIPTION  
COOLING  
VALUE  
DEFAULT  
UNITS  
POINT NAME  
Cooling Setpoint 1  
Cooling Setpoint 2  
ICE Setpoint  
–20 to 70  
–20 to 70  
–20 to 32  
44.0  
44.0  
32.0  
F  
F  
F  
CSP1  
CSP2  
CSP3  
RAMP LOADING  
Cooling Ramp Loading  
0.2 to 2.0  
–20 to 34  
1.0  
CRAMP  
Brine Freeze Point  
Head Setpoint  
Fan On Set Point  
Fan Off Set Point  
Fan Stage Delta  
34.0  
F  
F  
F  
F  
F  
F  
BRN_FRZ  
HSP  
FANONSP  
FANOFFSP  
FSTGDLTA  
B_FANOFF  
Base Fan Off Delta Temp  
CCN MAINTENANCE TABLES — CIRA_EXV  
DESCRIPTION  
EXV % Open  
VALUE  
nnn  
DEFAULT  
UNITS  
%
POINT NAME  
EXV_A  
Circuit A Approach  
Approach Setpoint  
EXVA Override  
Suction Superheat Temp  
Active Superheat Setpt  
Active MOP Setpt  
nnn.n  
nnn.n  
nnnnn  
nnn.n  
nn.n  
delta F  
delta F  
CIRA_APP  
APPRA_SP  
EXVAOVRR  
SH_A  
ACTSH_SP  
ACMOP_SP  
PLMA  
delta F  
delta F  
delta F  
%
nn.n  
nnn  
Cir A EXV Position Limit  
95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — CCN TABLES (cont)  
CCN MAINTENANCE TABLES — CIRB_EXV  
DESCRIPTION  
EXV % Open  
VALUE  
nnn  
DEFAULT  
UNITS  
%
POINT NAME  
EXV_B  
Circuit B Approach  
Approach Setpoint  
EXVB Override  
Suction Superheat Temp  
Active Superheat Setpt  
Active MOP Setpt  
nnn.n  
nnn.n  
nnnnn  
nnn.n  
nn.n  
delta F  
delta F  
CIRB_APP  
APPRB_SP  
EXVBOVRR  
SH_B  
ACTSH_SP  
ACMOP_SP  
PLMB  
delta F  
delta F  
delta F  
%
nn.n  
nnn  
Cir B EXV Position Limit  
CCN MAINTENANCE TABLES — STRTHOUR  
DESCRIPTION  
Machine Operating Hours  
Machine Starts  
VALUE  
nnnnnn  
nnnnnn  
UNITS  
hours  
POINT NAME  
HR_MACH  
CY_MACH  
Circuit A Run Hours  
nnnnnn  
nnnnnn  
nnnnnn  
nnnnnn  
nnnnnn  
nnnnnn  
hours  
hours  
hours  
hours  
hours  
hours  
HR_CIRA  
HR_A1  
HR_A2  
HR_CIRB  
HR_B1  
HR_B2  
Compressor A1 Run Hours  
Compressor A2 Run Hours  
Circuit B Run Hours  
Compressor B1 Run Hours  
Compressor B2 Run Hours  
Circuit A Starts  
nnnnnn  
nnnnnn  
nnnnnn  
nnnnnn  
nnnnnn  
nnnnnn  
CY_CIRA  
CY_A1  
CY_A2  
CY_CIRB  
CY_B1  
CY_B2  
Compressor A1 Starts  
Compressor A2 Starts  
Circuit B Starts  
Compressor B1 Starts  
Compressor B2 Starts  
PUMP HOURS  
Pump 1 Run Hours  
Pump 2 Run Hours  
nnnnnn  
nnnnnn  
hours  
hours  
HR_PUMP1  
HR_PUMP2  
CCN MAINTENANCE TABLES — CURRMODS  
DESCRIPTION  
CSM controlling Chiller  
WSM controlling Chiller  
Master/Slave control  
Ramp Load Limited  
Timed Override in effect  
Low Cooler Suction TempA  
Low Cooler Suction TempB  
Slow Change Override  
Minimum OFF time active  
Dual Setpoint  
VALUE  
POINT NAME  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
MODE_1  
MODE_2  
MODE_3  
MODE_5  
MODE_6  
MODE_7  
MODE_8  
MODE_9  
MODE_10  
MODE_13  
MODE_14  
MODE_15  
MODE_16  
MODE_17  
MODE_18  
MODE_19  
MODE_20  
MODE_21  
MODE_22  
MODE_23  
MODE_24  
MODE_25  
Temperature Reset  
Demand/Sound Limited  
Cooler Freeze Protection  
Low Temperature Cooling  
High Temperature Cooling  
Making ICE  
Storing ICE  
High SCT Circuit A  
High SCT Circuit B  
Minimum Comp. On Time  
Pump Off Delay Time  
Low Sound Mode  
96  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — CCN TABLES (cont)  
CCN MAINTENANCE TABLES — ALARMS  
DESCRIPTION  
Active Alarm #1  
VALUE  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
Axxx or Txxx  
POINT NAME  
ALARM01C  
Active Alarm #2  
Active Alarm #3  
Active Alarm #4  
Active Alarm #5  
Active Alarm #6  
Active Alarm #7  
Active Alarm #8  
Active Alarm #9  
Active Alarm #10  
Active Alarm #11  
Active Alarm #12  
Active Alarm #13  
Active Alarm #14  
Active Alarm #15  
Active Alarm #16  
Active Alarm #17  
Active Alarm #18  
Active Alarm #19  
Active Alarm #20  
Active Alarm #21  
Active Alarm #22  
Active Alarm #23  
Active Alarm #24  
Active Alarm #25  
ALARM02C  
ALARM03C  
ALARM04C  
ALARM05C  
ALARM06C  
ALARM07C  
ALARM08C  
ALARM09C  
ALARM10C  
ALARM11C  
ALARM12C  
ALARM13C  
ALARM14C  
ALARM15C  
ALARM16C  
ALARM17C  
ALARM18C  
ALARM19C  
ALARM20C  
ALARM21C  
ALARM22C  
ALARM23C  
ALARM24C  
ALARM25C  
CCN MAINTENANCE TABLES — VERSIONS  
DESCRIPTION  
VERSION  
CESR131172-  
CESR131333-  
CESR131460-  
CESR131174-  
CESR131171-  
CESR130227-  
VALUE  
EXV  
AUX  
MBB  
EMM  
MARQUEE  
NAVIGATOR  
nn-nn  
nn-nn  
nn-nn  
nn-nn  
nn-nn  
nn-nn  
CCN MAINTENANCE TABLES — LOADFACT  
DESCRIPTION  
VALUE  
UNITS  
POINT NAME  
CAPACITY CONTROL  
Load/Unload Factor  
Control Point  
Entering Fluid Temp  
Leaving Fluid Temp  
snnn.n  
SMZ  
CTRL_PNT  
EWT  
snnn.n  
snnn.n  
snnn.n  
F  
F  
F  
LWT  
Ramp Load Limited  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
MODE_5  
MODE_9  
MODE_16  
MODE_17  
MODE_18  
MODE_23  
Slow Change Override  
Cooler Freeze Protection  
Low Temperature Cooling  
High Temperature Cooling  
Minimum Comp. On Time  
97  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — CCN TABLES (cont)  
CCN MAINTENANCE TABLES — PM-PUMP  
DESCRIPTION  
Pump Service Interval  
VALUE  
nnnnnn  
nnnnnn  
Yes/No  
nnnnnn  
Yes/No  
UNITS  
hours  
hours  
POINT NAME  
SI_PUMPS  
Pump 1 Service Countdown  
Pump 1 Maintenance Done  
Pump 2 Service Countdown  
Pump 2 Maintenance Done  
Pump 1 Maintenance Date  
Pump 1 Maintenance Date  
Pump 1 Maintenance Date  
Pump 1 Maintenance Date  
Pump 1 Maintenance Date  
Pump 2 Maintenance Date  
Pump 2 Maintenance Date  
Pump 2 Maintenance Date  
Pump 2 Maintenance Date  
Pump 2 Maintenance Date  
P1_CDOWN  
P1_MAINT  
P2_CDOWN  
P2_MAINT  
PMP1_PM0  
PMP1_PM1  
PMP1_PM2  
PMP1_PM3  
PMP1_PM4  
PMP2_PM0  
PMP2_PM1  
PMP2_PM2  
PMP2_PM3  
PMP2_PM4  
hours  
mm/dd/yy hh:mm  
mm/dd/yy hh:mm  
mm/dd/yy hh:mm  
mm/dd/yy hh:mm  
mm/dd/yy hh:mm  
mm/dd/yy hh:mm  
mm/dd/yy hh:mm  
mm/dd/yy hh:mm  
mm/dd/yy hh:mm  
mm/dd/yy hh:mm  
CCN MAINTENANCE TABLES — PM-STRN  
DESCRIPTION  
Strainer Srvc Interval  
Strainer Srvc Countdown  
Strainer Maint. Done  
Strainer Maint. Date  
Strainer Maint. Date  
Strainer Maint. Date  
Strainer Maint. Date  
Strainer Maint. Date  
VALUE  
nnnnnn  
nnnnnn  
UNITS  
hours  
hours  
POINT NAME  
SI_STRNR  
ST_CDOWN  
ST_MAINT  
STRN_PM0  
STRN_PM1  
STRN_PM2  
STRN_PM3  
STRN_PM4  
Yes/No  
mm/dd/yy hh:mm  
mm/dd/yy hh:mm  
mm/dd/yy hh:mm  
mm/dd/yy hh:mm  
mm/dd/yy hh:mm  
CCN MAINTENANCE TABLES — PM-COIL  
DESCRIPTION  
Coil Cleaning Srvc Inter  
Coil Service Countdown  
Coil Cleaning Maint.Done  
Coil Cleaning Maint.Date  
Coil Cleaning Maint.Date  
Coil Cleaning Maint.Date  
Coil Cleaning Maint.Date  
Coil Cleaning Maint.Date  
VALUE  
nnnnnn  
nnnnnn  
UNITS  
hours  
hours  
POINT NAME  
SI_COIL  
CL_CDOWN  
CL_MAINT  
COIL_PM0  
COIL_PM1  
COIL_PM2  
COIL_PM3  
COIL_PM4  
Yes/No  
mm/dd/yy hh:mm  
mm/dd/yy hh:mm  
mm/dd/yy hh:mm  
mm/dd/yy hh:mm  
mm/dd/yy hh:mm  
CCN MAINTENANCE TABLES — TESTMODE  
DESCRIPTION  
Service Test Mode  
Compressor A1 Relay  
Compressor A2 Relay  
Compressor B1 Relay  
Compressor B2 Relay  
Fan 1 Relay  
VALUE  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
nn  
UNITS  
POINT NAME  
NET_CTRL  
S_A1_RLY  
S_A2_RLY  
S_B1_RLY  
S_B2_RLY  
S_FAN_1  
S_FAN_2  
S_CLPMP1  
S_CLPMP2  
S_A1ULTM  
S_MLV  
Fan 2 Relay  
Cooler Pump Relay 1  
Cooler Pump Relay 2  
Comp A1 Unload Time  
Minimum Load Valve Relay  
Remote Alarm Relay  
EXV % Open  
sec  
On/Off  
On/Off  
nn  
S_ALM  
S_EXV_A  
S_EXV_B  
%
%
EXV % Open  
nn  
98  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — CCN TABLES (cont)  
CCN MAINTENANCE TABLES — RUNTEST  
DESCRIPTION  
Percent Total Capacity  
VALUE  
nnn  
UNITS  
POINT NAME  
CAPA_T  
%
Percent Available Cap.  
Discharge Pressure  
Suction Pressure  
nnn  
%
CAPA_A  
DP_A  
SP_A  
nnn.n  
nnn.n  
nnn.n  
nnn.n  
nnn.n  
nnn.n  
nnn.n  
nnn.n  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
nnn  
psig  
psig  
F  
F  
F  
F  
F  
^F  
Head Setpoint  
HSP  
Saturated Condensing Tmp  
Saturated Suction Temp  
Compr Return Gas Temp  
Discharge Gas Temp  
Suction Superheat Temp  
Compressor A1 Relay  
Compressor A2 Relay  
Minimum Load Valve Relay  
Compressor A1 Feedback  
Compressor A2 Feedback  
Percent Total Capacity  
Percent Available Cap.  
Discharge Pressure  
TMP_SCTA  
TMP_SSTA  
TMP_RGTA  
DISGAS  
SH_A  
K_A1_RLY  
K_A2_RLY  
MLV_RLY  
K_A1_FBK  
K_A2_FBK  
CAPB_T  
CAPB_A  
DP_B  
%
%
psig  
psig  
F  
F  
F  
F  
^F  
nnn  
nnn.n  
nnn.n  
nnn.n  
nnn.n  
nnn.n  
nnn.n  
nnn.n  
On/Off  
On/Off  
On/Off  
Suction Pressure  
Head Setpoint  
SP_B  
HSP  
Saturated Condensing Tmp  
Saturated Suction Temp  
Compr Return Gas Temp  
Suction Superheat Temp  
Compressor B1 Relay  
Compressor B2 Relay  
Minimum Load Valve Relay  
TMP_SCTB  
TMP_SSTB  
TMP_RGTB  
SH_B  
K_B1_RLY  
K_B2_RLY  
MLV_RLY  
Compressor B1 Feedback  
Compressor B2 Feedback  
Fan 1 Relay  
On/Off  
On/Off  
On/Off  
On/Off  
K_B1_FBK  
K_B2_FBK  
FAN_1  
Fan 2 Relay  
FAN_2  
Outside Air Temperature  
Space Temperature  
Cooler Pump Relay 1  
Cooler Pump Relay 2  
Cooler Pump 1 Interlock  
Cooler Pump 2 Interlock  
Cooler Entering Fluid  
Cooler Leaving Fluid  
Compressor A1 Size  
Compressor A2 Size  
Compressor B1 Size  
Compressor B2 Size  
Cooler Flow Switch  
nnn.n  
nnn.n  
F  
F  
OAT  
SPT  
On/Off  
On/Off  
Open/Closed  
Open/Closed  
nnn.n  
COOLPMP1  
COOLPMP2  
PMP1_FBK  
PMP2_FBK  
COOL_EWT  
COOL_LWT  
SIZE_A1  
SIZE_A2  
SIZE_B1  
SIZE_B2  
COOLFLOW  
F  
F  
tons  
tons  
tons  
tons  
nnn.n  
nnn  
nnn  
nnn  
nnn  
On/Off  
99  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B — CCN TABLES (cont)  
CCN MAINTENANCE TABLES — DUALCHIL  
DESCRIPTION  
Dual Chiller Link Good?  
VALUE  
Yes/No  
UNITS  
POINT NAME  
DC_LINK  
Master Chiller Role  
Stand Alone,  
Lead Chiller,  
Lag Chiller  
Stand Alone,  
Lead Chiller,  
Lag Chiller  
MC_ROLE  
SC_ROLE  
Slave Chiller Role  
Lead Chiller Ctrl Point  
Lag Chiller Ctrl Point  
Control Point  
snnn.n  
snnn.n  
snnn.n  
F  
F  
F  
LEAD_CP  
LAG_CP  
CTRL_PNT  
Cool EnteringFluid-Slave  
Cool Leaving Fluid-Slave  
Cooler Entering Fluid  
Cooler Leaving Fluid  
snnn.n  
snnn.n  
snnn.n  
snnn.n  
snnn.n  
F  
F  
F  
F  
F  
COOLEWTS  
COOLLWTS  
COOL_EWT  
COOL_LWT  
DUAL_LWT  
Lead/Lag Leaving Fluid  
Percent Avail.Capacity  
Percent Avail.Cap.Slave  
0-100  
0-100  
%
%
CAP_A  
CAP_A_S  
Lag Start Delay Time  
Load/Unload Factor  
Load/Unload Factor-Slave  
Lead SMZ Clear Commanded  
Lag SMZ Clear Commanded  
Lag Commanded Off?  
hh:mm  
snnn.n  
snnn.n  
Yes/No  
Yes/No  
Yes/No  
LAGDELAY  
SMZ  
SMZSLAVE  
LEADSMZC  
LAG_SMZC  
LAG_OFF  
Dual Chill Lead CapLimit  
Dual Chill Lag CapLimit  
0-100  
0-100  
%
%
DCLDCAPL  
DCLGCAPL  
100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX C — FACTORY SETTINGS FOR PUMP AND MANUAL STARTERS  
UNIT VOLTAGE  
V-Hz (3 Ph)  
OVERLOAD  
SETTING  
PUMP OPTION  
PUMP SIZE  
208/230-60  
380-60  
4.0  
2.0  
1.6  
2.4  
1, 8  
1.0 HP  
460-60  
575-60  
208/230-60  
380-60  
5.4  
2.7  
2.2  
3.3  
6.6  
3.3  
2.6  
4.0  
8.8  
4.4  
3.5  
5.3  
14.0  
7.0  
5.6  
8.5  
2, 9  
3, B  
1.5 HP  
2.0 HP  
3.0 HP  
5.0 HP  
7.5 HP  
460-60  
575-60  
208/230-60  
380-60  
460-60  
575-60  
208/230-60  
380-60  
460-60  
575-60  
208/230-60  
380-60  
460-60  
575-60  
208/230-60  
380-60  
460-60  
575-60  
4, C  
5, 6, D, F  
7, G  
22.8  
11.4  
9.1  
13.8  
101  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING  
Optional BACnet Communications Wiring —  
0
The following section is used to configure the UPC Open con-  
troller which is used when the BACnet communications option  
is selected. The UPC Open controller is mounted in the main  
control box per unit components arrangement diagrams.  
1
9
2
8
7
3
10's  
1's  
5 4  
6
0
1
9
TO ADDRESS THE UPC OPEN CONTROLLER — The  
user must give the UPC Open controller an address that is  
unique on the BACnet* network. Perform the following proce-  
dure to assign an address:  
1. If the UPC Open controller is powered, pull the screw ter-  
minal connector from the controller's power terminals la-  
beled Gnd and HOT. The controller reads the address  
each time power is applied to it.  
2. Using the rotary switches (see Fig. A and B), set the con-  
troller's address. Set the Tens (10's) switch to the tens dig-  
it of the address, and set the Ones (1's) switch to the ones  
digit.  
As an example in Fig. B, if the controller’s address is 25,  
point the arrow on the Tens (10's) switch to 2 and the arrow on  
the Ones (1's) switch to 5.  
2
8
7
3
5 4  
6
Fig. B — Address Rotary Switches  
BACNET DEVICE INSTANCE ADDRESS — The UPC  
Open controller also has a BACnet Device Instance address.  
This Device Instance MUST be unique for the complete BAC-  
net system in which the UPC Open controller is installed. The  
Device Instance is auto generated by default and is derived by  
adding the MAC address to the end of the Network Number.  
The Network Number of a new UPC Open controller is 16101,  
but it can be changed using i-Vu® Tools or BACView device.  
By default, a MAC address of 20 will result in a Device In-  
stance of 16101 + 20 which would be a Device Instance of  
1610120.  
BT485  
TERMINATOR  
BACNET  
CONNECTION  
(BAS PORT)  
POWER LED  
Tx1 LED  
Rx1 LED  
Tx2 LED  
Rx2 LED  
BACNET  
BAUD RATE  
DIP SWITCHES  
EIA-485  
JUMPERS  
ADDRESS  
ROTARY  
SWITCHES  
RUN LED  
ERROR LED  
Fig. A — UPC Open Controller  
* Sponsored by ASHRAE (American Society of Heating, Refrigerat-  
ing, and Air Conditioning Engineers).  
102  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)  
CONFIGURING THE BAS PORT FOR BACNET MS/  
TP — Use the same baud rate and communication settings for  
all controllers on the network segment. The UPC Open con-  
troller is fixed at 8 data bits, No Parity, and 1 Stop bit for this  
protocol's communications.  
If the UPC Open controller has been wired for power, pull  
the screw terminal connector from the controller's power termi-  
nals labeled Gnd and HOT. The controller reads the DIP  
Switches and jumpers each time power is applied to it.  
Set the BAS Port DIP switch DS3 to “enable.” Set the BAS  
Port DIP switch DS4 to “E1-485.” Set the BMS Protocol DIP  
switches DS8 through DS5 to “MSTP.” See Table A.  
Fig. C — DIP Switches  
Table A — SW3 Protocol Switch Settings  
for MS/TP  
Wire the controllers on an MS/TP network segment in a dai-  
sy-chain configuration. Wire specifications for the cable are  
22 AWG (American Wire Gage) or 24 AWG, low-capacitance,  
twisted, stranded, shielded copper wire. The maximum length  
is 2000 ft.  
Install a BT485 terminator on the first and last controller on  
a network segment to add bias and prevent signal distortions  
due to echoing. See Fig. A, D, and E.  
DS8  
DS7  
DS6  
DS5  
DS4  
DS3  
Off  
Off  
Off  
Off  
On  
Off  
Verify that the EIA-485 jumpers below the CCN Port are set  
to EIA-485 and 2W.  
The example in Fig. C shows the BAS Port DIP Switches  
set for 76.8k (Carrier default) and MS/TP.  
Set the BAS Port DIP Switches DS2 and DS1 for the appro-  
priate communications speed of the MS/TP network (9600,  
19.2k, 38.4k, or 76.8k bps). See Fig. D and Table B.  
To wire the UPC Open controller to the BAS network:  
1. Pull the screw terminal connector from the controller's  
BAS Port.  
Table B — Baud Selection Table  
2. Check the communications wiring for shorts and  
grounds.  
3. Connect the communications wiring to the BAS port’s  
screw terminals labeled Net +, Net -, and Shield.  
NOTE: Use the same polarity throughout the network  
segment.  
4. Insert the power screw terminal connector into the UPC  
Open controller's power terminals if they are not current-  
ly connected.  
5. Verify communication with the network by viewing a  
module status report. To perform a module status report  
using the BACview keypad/display unit, press and hold  
the “FN” key then press the “.” Key.  
BAUD RATE  
9,600  
DS2  
Off  
On  
Off  
On  
DS1  
Off  
Off  
On  
On  
19,200  
38,400  
76,800  
WIRING THE UPC OPEN CONTROLLER TO THE MS/  
TP NETWORK — The UPC Open controller communicates  
using BACnet on an MS/TP network segment communications  
at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps.  
Fig. D — Network Wiring  
103  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)  
Fig. E — BT485 Terminator Installation  
To install a BT485 terminator, push the BT485 terminator  
temperature rating specifications list two acceptable alterna-  
tives. The Halar specification has a higher temperature rating  
and a tougher outer jacket than the SmokeGard specification,  
and it is appropriate for use in applications where the user is  
concerned about abrasion. The Halar jacket is also less likely to  
crack in extremely low temperatures.  
on to the BT485 connector located near the BACnet connector.  
NOTE: The BT485 terminator has no polarity associated with  
it.  
To order a BT485 terminator, consult Commercial Products  
i-Vu Open Control System Master Prices.  
MS/TP WIRING RECOMMENDATIONS — Recommen-  
dations are shown in Tables C and D. The wire jacket and UL  
NOTE: Use the specified type of wire and cable for maximum  
signal integrity.  
Table C — MS/TP Wiring Recommendations  
SPECIFICATION  
RECOMMMENDATION  
Cable  
Single twisted pair, low capacitance, CL2P, 22 AWG (7x30), TC foam FEP, plenum rated cable  
22 or 24 AWG stranded copper (tin plated)  
Foamed FEP 0.015 in. (0.381 mm) wall 0.060 in. (1.524 mm) O.D.  
Black/White  
2 in. (50.8 mm) lay on pair 6 twists/foot (20 twists/meter) nominal  
Aluminum/Mylar shield with 24 AWG TC drain wire  
Conductor  
Insulation  
Color Code  
Twist Lay  
Shielding  
SmokeGard Jacket (SmokeGard PVC) 0.021 in. (0.5334 mm) wall 0.175 in. (4.445 mm) O.D.  
Halar Jacket (E-CTFE) 0.010 in. (0.254 mm) wall 0.144 in. (3.6576 mm) O.D.  
Jacket  
DC Resistance  
Capacitance  
Characteristic Impedance  
Weight  
15.2 Ohms/1000 feet (50 Ohms/km) nominal  
12.5 pF/ft (41 pF/meter) nominal conductor to conductor  
100 Ohms nominal  
12 lb/1000 feet (17.9 kg/km)  
SmokeGard 167°F (75°C)  
Halar -40 to 302°F (-40 to 150°C)  
UL Temperature Rating  
Voltage  
Listing  
300 Vac, power limited  
UL: NEC CL2P, or better  
LEGEND  
AWG  
CL2P  
DC  
American Wire Gage  
Class 2 Plenum Cable  
Direct Current  
FEP  
NEC  
O.D.  
TC  
Fluorinated Ethylene Polymer  
National Electrical Code  
Outside Diameter  
Tinned Copper  
Underwriters Laboratories  
UL  
104  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)  
Table D — Open System Wiring Specifications and Recommended Vendors  
WIRING SPECIFICATIONS  
Description  
RECOMMENDED VENDORS AND PART NUMBERS  
Connect Air  
International  
Contractors  
Wire and Cable  
Wire Type  
Belden RMCORP  
22 AWG, single twisted shielded pair, low capacitance, CL2P,  
TC foam FEP, plenum rated. See MS/TP Installation Guide for  
specifications.  
24 AWG, single twisted shielded pair, low capacitance, CL2P,  
TC foam FEP, plenum rated. See MS/TP Installation Guide  
for specifications.  
W221P-22227  
W241P-2000F  
25160PV  
CLP0520LC  
MS/TP  
Network (RS-485)  
82841 25120-OR  
21450  
Rnet  
4 conductor, unshielded, CMP, 18 AWG, plenum rated.  
W184C-2099BLB 6302UE  
CLP0442  
LEGEND  
American Wire Gage  
Class 2 Plenum Cable  
Communications Plenum Rated  
Fluorinated Ethylene Polymer  
Tinned Copper  
AWG  
CL2P  
CMP  
FEP  
TC  
LOCAL ACCESS TO THE UPC OPEN CONTROL-  
LER — The user can use a BACview6 handheld keypad dis-  
play unit or the Virtual BACview software as a local user inter-  
face to an Open controller. These items let the user access the  
controller network information. These are accessory items and  
do not come with the UPC Open controller.  
The BACview6 unit connects to the local access port on the  
UPC Open controller. See Fig. F. The BACview software must  
be running on a laptop computer that is connected to the local  
access port on the UPC Open controller. The laptop will re-  
quire an additional USB link cable for connection.  
ber and CCN Bus number. The factory default settings for  
CCN Element and CCN Bus number are 1 and 0 respectively.  
If modifications to the default Element and Bus number are  
required, both the ComfortLink and UPC Open configurations  
must be changed.  
The following configurations are used to set the CCN Ad-  
dress and Bus number in the ComfortLink control. These con-  
figurations can be changed using the scrolling marquee display  
or accessory Navigator handheld device.  
ConfigurationCCNCCN.A (CCN Address)  
ConfigurationCCNCCN.B (CCN Bus Number)  
The following configurations are used to set the CCN Ad-  
dress and Bus Number in the UPC Open controller. These con-  
figurations can be changed using the accessory BACview6 dis-  
play.  
See the BACview Installation and User Guide for instruc-  
tions on connecting and using the BACview6 device.  
To order a BACview6 Handheld (BV6H), consult Commer-  
cial Products i-Vu Open Control System Master Prices.  
CONFIGURING THE UPC OPEN CONTROLLER'S  
PROPERTIES — The UPC Open device and ComfortLink  
control must be set to the same CCN Address (Element) num-  
Navigation: BACviewCCN  
Home: Element Comm Stat  
Element: 1  
Bus: 0  
Fig. F — BACview6 Device Connection  
105  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)  
If the UPC Open is used with the chiller application of  
traffic based on the baud rate set. The higher the baud rate the  
more solid the LEDs become. See Fig. A for location of LEDs  
on UPC Open module.  
REPLACING THE UPC OPEN BATTERY — The UPC  
Open controller's 10-year lithium CR2032 battery provides a  
minimum of 10,000 hours of data retention during power out-  
ages.  
Lead/Lag/Standby, all chillers and UPC Open's CCN element  
numbers must be changed to a unique number in order to fol-  
low CCN specifications. In this application, there can only be a  
maximum of 3 UPC Open controllers on a CCN bus.  
For the CCN Alarm Acknowledger configuration, the UPC  
Open defaults to CCN Acknowledger. If a Chiller Lead/Lag/  
Standby application is being used, then the Carrier technician  
must change the configuration to only one CCN Acknowledger  
on the CCN bus.  
For the CCN Time Broadcaster configuration, the UPC  
Open defaults to CCN Time Broadcaster. If the Chiller Lead/  
Lag/Standby application is used, then the Carrier technician  
must change the configuration to only one CCN Time Broad-  
caster on the CCN bus.  
TROUBLESHOOTING — If there are problems wiring or  
addressing the UPC Open controller, contact Carrier Technical  
Support.  
COMMUNICATION LEDS — The LEDs indicate if the  
controller is communicating with the devices on the network.  
See Tables E and F. The LEDs should reflect communication  
IMPORTANT: Power must be ON to the UPC Open when  
replacing the battery, or the date, time, and trend data will  
be lost.  
Remove the battery from the controller, making note of the  
battery's polarity. Insert the new battery, matching the battery's  
polarity with the polarity indicated on the UPC Open  
controller.  
NETWORK POINTS LIST — The points list for the control-  
ler is shown in Table G.  
Refer to Appendix B for additional information on CCN  
point name.  
Table E — LED Status Indicators  
LED  
STATUS  
Lights when power is being supplied to the controller. The UPC Open controller is protected by internal solid-state polyswitches on  
the incoming power and network connections. These polyswitches are not replaceable and will reset themselves if the condition  
that caused the fault returns to normal.  
Power  
Rx  
Tx  
Run  
Error  
Lights when the controller receives data from the network segment; there is an Rx LED for Ports 1 and 2.  
Lights when the controller transmits data to the network segment; there is an Rx LED for Ports 1 and 2.  
Lights based on controller status. See Table F.  
Lights based on controller status. See Table F.  
Table F — Run and Error LEDs Controller and Network Status Indication  
RUN LED  
ERROR LED  
STATUS  
2 flashes per second  
2 flashes per second  
2 flashes per second  
2 flashes per second  
2 flashes per second  
5 flashes per second  
5 flashes per second  
7 flashes per second  
Off  
Normal  
2 flashes, alternating with Run LED  
3 flashes, then off  
1 flash per second  
On  
On  
Off  
Five minute auto-restart delay after system error  
Controller has just been formatted  
Controller is alone on the network  
Exec halted after frequent system errors or control programs halted  
Exec start-up aborted, Boot is running  
Firmware transfer in progress, Boot is running  
Ten second recovery period after brownout  
7 flashes per second, alternating with Run LED  
14 flashes per second 14 flashes per second, alternating with Run LED Brownout  
106  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)  
Table G — Network Points List  
CCN POINT READ/  
DEFAULT  
VALUE  
BACNET  
BACNET  
POINT DESCRIPTION  
UNITS  
RANGE  
NAME  
LMT_MA  
RST_MA  
DEM_LIM  
SP  
WRITE  
OBJECT ID  
OBJECT NAME  
4-20 ma Demand Signal  
4-20 ma Reset Signal  
Active Demand Limit  
Active Setpoint  
R
R
R/W  
R
mA  
°F  
%
AV:36  
AV:33  
AV:2  
lmt_ma_1  
rst_ma_1  
dem_lim_1  
sp_1  
100  
0 - 100  
°F  
AV:4  
1 = Normal  
2 = Alert  
3 = Alarm  
Alarm State  
ALM  
R
MSV:1  
alm_msv_1  
CCN Chiller  
CCN Loadshed Signal  
Circuit A Run Hours  
Circuit A Starts  
Circuit B Run Hours  
CHIL_S_S  
DL_STAT  
HR_CIRA  
CY_CIRA  
HR_CIRB  
CY_CIRB  
CL_MAINT  
SI_COIL  
CL_CDOWN  
A1UNLTME  
TMP_RGTA  
TMP_RGTB  
K_A1_FBK  
K_A1_RLY  
HR_A1  
R/W  
R
R
R
R
Start  
Start/Stop  
BV:4  
AV:37  
AV:59  
AV:65  
AV:62  
AV:68  
BV:54  
AV:50  
AV:49  
AV:73  
AV:20  
AV:28  
BV:16  
BV:13  
AV:60  
AV:66  
BV:17  
BV:14  
AV:61  
AV:67  
BV:20  
BV:18  
AV:63  
AV:69  
BV:21  
BV:19  
AV:64  
AV:70  
chil_s_s_1  
dl_stat_1  
hr  
hr  
hr_cira_1  
cy_cira_1  
hr_cirb_1  
cy_cirb_1  
cl_maint_1  
si_coil_1  
cl_cdown_1  
a1unltme_1  
tmp_rgta_1  
tmp_rgtb_1  
k_a1_fbk_1  
k_a1_rly_1  
hr_a1_1  
Circuit B Starts  
R
Coil Cleaning Maint.Done  
Coil Cleaning Srvc Inter  
Coil Service Countdown  
Comp A1 Unload Time  
Compr Return Gas Temp  
Compr Return Gas Temp  
Compressor A1 Feedback  
Compressor A1 Relay  
Compressor A1 Run Hours  
Compressor A1 Starts  
Compressor A2 Feedback  
Compressor A2 Relay  
Compressor A2 Run Hours  
Compressor A2 Starts  
Compressor B1 Feedback  
Compressor B1 Relay  
Compressor B1 Run Hours  
Compressor B1 Starts  
Compressor B2 Feedback  
Compressor B2 Relay  
Compressor B2 Run Hours  
Compressor B2 Starts  
R/W  
R/W  
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
No  
8760  
Yes/No  
0 - 65535  
hr  
hr  
°F  
°F  
hr  
hr  
hr  
hr  
CY_A1  
cy_a1_1  
K_A2_FBK  
K_A2_RLY  
HR_A2  
k_a2_fbk_1  
k_a2_rly_1  
hr_a2_1  
CY_A2  
cy_a2_1  
K_B1_FBK  
K_B1_RLY  
HR_B1  
k_b1_fbk_1  
k_b1_rly_1  
hr_b1_1  
CY_B1  
R
R
R
R
cy_b1_1  
K_B2_FBK  
K_B2_RLY  
HR_B2  
k_b2_fbk_1  
k_b2_rly_1  
hr_b2_1  
CY_B2  
R
cy_b2_1  
1 = Test  
2 = Local Off  
3 = CCN Off  
4 = Clock Off  
5 = Emergency Stop  
6= Local On  
Control Mode  
CONTROL  
R
MSV:2  
stat_msv_1  
7 = CCN On  
8 = Clock On  
9 = Heat Enabled  
10 = Pump Delay  
Control Point  
Cooler Entering Fluid  
Cooler Flow Switch  
CTRL_PNT  
COOL_EWT  
COOLFLOW  
MODE_16  
COOL_LWT  
LWT_SP  
PMP1_FBK  
PMP2_FBK  
COOLPMP1  
COOLPMP2  
PMP_SLCT  
PUMP_DLY  
COOL_HTR  
CRAMP  
R/W  
R
R
R
R
R
R
R
R
R
R
R/W  
R
R/W  
R/W  
°F  
°F  
44.0  
-20 - 70  
AV:5  
AV:30  
BV:11  
BV:42  
AV:31  
AV:38  
BV:9  
BV:10  
BV:7  
BV:8  
AV:40  
AV:41  
BV:24  
AV:56  
AV:53  
ctrl_pnt_1  
cool_ewt_1  
coolflow_1  
mode_16_1  
cool_lwt_1  
lwt_sp_1  
pmp1_fbk_1  
pmp2_fbk_1  
coolpmp1_1  
coolpmp2_1  
pmp_slct_1  
pump_dly_1  
cool_htr_1  
cramp_1  
Cooler Freeze Protection  
Cooler Leaving Fluid  
Cooler LWT Setpoint  
Cooler Pump 1 Interlock  
Cooler Pump 2 Interlock  
Cooler Pump Relay 1  
Cooler Pump Relay 2  
Cooler Pump Select  
Cooler Pump Shutdown Dly  
Cooler/Pump Heater  
Cooling Ramp Loading  
Cooling Setpoint 1  
°F  
°F  
min  
°F  
1
0 - 10  
1.0  
44.0  
0.2 - 2.0  
-20 - 70  
CSP1  
csp1_1  
LEGEND  
R
W
Read  
Write  
107  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)  
Table G — Network Points List (cont)  
READ/  
WRITE  
DEFAULT  
VALUE  
BACNET  
OBJECT ID  
BACNET  
OBJECT NAME  
POINT DESCRIPTION  
POINT NAME  
UNITS  
RANGE  
Cooling Setpoint 2  
CSM Controlling Chiller  
Demand Level 1  
Demand Level 2  
Demand Level 3  
Demand Limit Switch 1  
Demand Limit Switch 2  
Demand/Sound Limited  
Discharge Gas Temp  
Discharge Pressure  
Discharge Pressure  
Dual Setpoint  
CSP2  
MODE_1  
R/W  
R
R
R
R
R
R
R
R
R
R
R
R
°F  
44.0  
-20 - 70  
AV:54  
BV:30  
AV:75  
AV:76  
AV:77  
BV:25  
BV:26  
BV:41  
AV:15  
AV:13  
AV:23  
BV:39  
BV:29  
BV:2999  
csp2_1  
mode_1_1  
%
%
%
dmv_lvl_1_perct_1  
dmv_lvl_2_perct_1  
dmv_lvl_3_perct_1  
dmd_sw1_1  
dmd_sw2_1  
mode_15_1  
disgas_1  
dp_a_1  
dp_b_1  
mode_13_1  
dual_in_1  
element_stat_1  
DMD_SW1  
DMD_SW2  
MODE_15  
DISGAS  
DP_A  
DP_B  
MODE_13  
DUAL_IN  
°F  
psig  
psig  
Dual Setpoint Switch  
Element Comm Status  
R
Element Communications  
Alarm  
R
BV:58  
comm_lost_alm_1  
Emergency Stop  
Entering Fluid Temp  
EXV % Open  
EXV % Open  
Fan 1 Relay  
Fan 2 Relay  
Head Setpoint  
Heat Request  
High SCT Circuit A  
High SCT Circuit B  
High Temperature Cooling  
Ice Done  
EMSTOP  
EWT  
EXV_A  
EXV_B  
FAN_1  
R/W  
R
R
R
R
R
R
R
R
R
R
R
R/W  
Enabled  
Enabled/Emstop  
BV:6  
AV:6  
emstop_1  
ewt_1  
exv_a_1  
exv_b_1  
fan_1_1  
°F  
%
%
AV:18  
AV:27  
BV:22  
BV:23  
AV:29  
BV:28  
BV:47  
BV:48  
BV:44  
BV:27  
AV:55  
FAN_2  
HSP  
fan_2_1  
hsp_1  
°F  
HEAT_REQ  
MODE_21  
MODE_22  
MODE_18  
ICE_DONE  
CSP3  
heat_req_1  
mode_21_1  
mode_22_1  
mode_18_1  
ice_done_1  
csp3_1  
Ice Setpoint  
°F  
32.0  
1
-20 - 32  
1 = Automatic  
2 = Circuit A Leads  
3 = Circuit B Leads  
Lead/Lag Circuit Select  
LEAD_TYP  
R/W  
AV:43  
lead_typ_1  
Lead/Lag Circuit Select  
Lead/Lag Leaving Fluid  
Leadpump  
Leaving Fluid Temp - Prime  
Variable  
LEAD_TYP  
DUAL_LWT  
LEADPUMP  
R
R
R
MSV:6  
AV:32  
MSV:9  
lead_typ_msv_1  
dual_lwt_1  
leadpump_msv_1  
°F  
°F  
LWT  
R
AV:7  
lwt_1  
Loading Sequence Select  
Local Schedule  
Low Cooler Suction Temp A  
Low Cooler Suction Temp B  
Low Sound Active  
SEQ_TYPE  
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W  
R
R
R
AV:74  
BV:1  
BV:35  
BV:36  
BV:2  
BV:51  
BV:43  
AV:57  
AV:58  
BV:45  
BV:32  
BV:49  
BV:15  
BV:38  
AV:42  
BV:3  
seq_type_1  
schedule_1  
mode_7_1  
mode_8_1  
lsactive_1  
mode_25_1  
mode_17_1  
hr_mach_1  
cy_mach_1  
mode_19_1  
mode_3_1  
mode_23_1  
mlv_rly_1  
mode_10_1  
delay_1  
MODE_7  
MODE_8  
LSACTIVE  
MODE_25  
MODE_17  
HR_MACH  
CY_MACH  
MODE_19  
MODE_3  
MODE_23  
MLV_RLY  
MODE_10  
DELAY  
Low Sound Mode  
Low Temperature Cooling  
Machine Operating Hours  
Machine Starts  
hr  
Making ICE  
Master/Slave Control  
Minimum Comp. On Time  
Minimum Load Valve Relay  
Minimum OFF Time Active  
Minutes Off Time  
min  
°F  
0
0 - 15  
Occupied  
OCC  
OAT  
MODE  
CAP_A  
occ_1  
oat_1  
mode_1  
capa_a_1  
capb_a_1  
Outside Air Temperature  
Override Modes in Effect  
Percent Available Cap.  
Percent Available Cap.  
AV:34  
BV:5  
AV:12  
AV:22  
R
R
%
%
CAPB_A  
LEGEND  
R
W
Read  
Write  
108  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)  
Table G — Network Points List (cont)  
READ/  
WRITE  
DEFAULT  
VALUE  
BACNET  
OBJECT ID  
BACNET  
OBJECT NAME  
POINT DESCRIPTION  
POINT NAME  
UNITS  
RANGE  
Percent Total Capacity  
Percent Total Capacity  
Percent Total Capacity  
Pump 1 Maintenance Done  
Pump 1 Run Hours  
Pump 1 Service Countdown  
Pump 2 Maintenance Done  
Pump 2 Run Hours  
Pump 2 Service Countdown  
Pump Changeover Hours  
Pump Off Delay Time  
Pump Service Interval  
Ramp Load Limited  
CAP_T  
CAPA_T  
CAPB_T  
R
R
R
R/W  
R
R
R/W  
R
R
R/W  
R
R/W  
R
%
%
%
AV:3  
AV:11  
AV:21  
BV:52  
AV:71  
AV:46  
BV:53  
AV:72  
AV:47  
AV:39  
BV:50  
AV:48  
BV:33  
AV:9  
cap_t_1  
capa_t_1  
capb_t_1  
P1_MAINT  
HR_PUMP1  
P1_CDOWN  
P2_MAINT  
HR_PUMP2  
P2_CDOWN  
PMP_DLTA  
MODE_24  
SI_PUMPS  
MODE_5  
STAGE  
No  
No  
Yes/No  
Yes/No  
p1_maint_1  
hr_pump1_1  
p1_cdown_1  
p2_maint_1  
hr_pump2_1  
p2_cdown_1  
pmp_dlta_1  
mode_24_1  
si_pumps_1  
mode_5_1  
stage_1  
hr  
hr  
hr  
hr  
hr  
500  
10 - 2000  
0 - 65535  
hr  
8760  
Requested Stage  
R
Rotate Cooler Pumps Now  
Saturated Condensing Tmp  
Saturated Condensing Tmp  
Saturated Suction Temp  
Saturated Suction Temp  
Slow Change Override  
Space Temperature  
ROT_PUMP  
TMP_SCTA  
TMP_SCTB  
TMP_SSTA  
TMP_SSTB  
MODE_9  
SPT  
MODE_20  
ST_MAINT  
ST_CDOWN  
SI_STRNR  
SP_A  
R/W  
R
R
R
R
R
R/W  
R
R/W  
R
R/W  
R
No  
No/Yes  
BV:12  
AV:16  
AV:25  
AV:17  
AV:26  
BV:37  
AV:35  
BV:46  
BV:55  
AV:52  
AV:51  
AV:14  
AV:24  
AV:44  
AV:45  
rot_pump_1  
tmp_scta_1  
tmp_sctb_1  
tmp_ssta_1  
tmp_sstb_1  
mode_9_1  
spt_1  
mode_20_1  
st_maint_1  
st_cdown_1  
si_strnr_1  
sp_a_1  
°F  
°F  
°F  
°F  
°F  
8760  
No  
-40.0 - 245  
Yes/No  
Storing ICE  
Strainer Maint. Done  
Strainer Srvc Countdown  
Strainer Srvc Interval  
Suction Pressure  
Suction Pressure  
Suction Superheat Temp  
Suction Superheat Temp  
hr  
hr  
psig  
psig  
°^F  
°^F  
8760  
0 - 65535  
SP_B  
SH_A  
SH_B  
R
R
R
sp_b_1  
sh_a_1  
sh_b_1  
System Cooling Demand  
Level  
R
AV:9006  
cool_demand_level_1  
System Demand Limiting  
Temperature Reset  
R
R
R
BV:57  
BV:40  
BV:34  
dem_lmt_act_1  
mode_14_1  
mode_6_1  
MODE_14  
MODE_6  
Timed Override In Effect  
User Defined Analog 1  
User Defined Analog 2  
User Defined Analog 3  
User Defined Analog 4  
User Defined Analog 5  
User Defined Binary 1  
User Defined Binary 2  
User Defined Binary 3  
User Defined Binary 4  
User Defined Binary 5  
Var Head Press Output  
WSM Controlling Chiller  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R
sq m  
sq m  
sq m  
sq m  
sq m  
sq m  
sq m  
sq m  
sq m  
sq m  
mA  
AV:2901  
AV:2902  
AV:2903  
AV:2904  
AV:2905  
BV:2911  
BV:2912  
BV:2913  
BV:2914  
BV:2915  
AV:19  
user_analog_1_1  
user_analog_2_1  
user_analog_3_1  
user_analog_4_1  
user_analog_5_1  
user_binary_1_1  
user_binary_2_1  
user_binary_3_1  
user_binary_4_1  
user_binary_5_1  
vhp_act_1  
VHP_ACT  
MODE_2  
R
BV:31  
mode_2_1  
LEGEND  
R
W
Read  
Write  
109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS  
30RAP Maintenance Interval Requirements  
WEEKLY  
Compressor  
Cooler  
Check oil level.  
None.  
Economizer  
Controls  
Starter  
None.  
Review Alarm/Alert History.  
None.  
Condenser  
None.  
MONTHLY  
Compressor  
Cooler  
Check oil level.  
None.  
Economizer  
Controls  
Starter  
None.  
Inspect sight glass for moisture and refrigerant level.  
None.  
Condenser  
None.  
QUARTERLY  
Economizer  
Compressor  
Cooler  
Check oil level  
None.  
Check refrigerant charge. Check all connec-  
tions for leaks.  
Perform an Automated Controls test. Run all compressors  
and ensure proper operation.  
Controls  
Condenser  
None.  
Starter  
Ensure operation of units flow switch.  
ANNUALLY  
Check Oil Level. Obtain and test an oil  
sample.  
Check refrigerant charge. Check all connec-  
tions for leaks. Check approach on unit to  
determine if tubes need cleaning. Check for  
temperature drop across filter drier to deter-  
mine if filter needs replacement.  
Compressor  
Cooler  
Economizer  
Verify proper operation of EXVs and TXVs  
Perform an Automated Controls test. Run all compressors  
and ensure proper operation. Ensure operation of unit flow  
switch.  
Controls  
Inspect all coils and clean. Check condenser  
approach to determine if tubes need to be  
cleaned.  
Inspect all electrical connections and tighten as needed.  
Measure current to each compressor and inspect contac-  
tors.  
Condenser  
Starter  
NOTE: Equipment failures caused by lack of adherence to the Main-  
tenance Interval Requirements are not covered under warranty.  
110  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS (cont)  
30RAP Weekly Maintenance Log  
Plant ___________________________  
Machine Model No. ________________  
CHECK ALARMS  
/ FAULTS  
OPERATOR  
INITIALS  
DATE  
OIL LEVEL  
REMARKS  
NOTE: Equipment failures caused by lack of adherence to the Main-  
tenance Interval Requirements are not covered under warranty.  
111  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS (cont)  
30RAP Monthly Maintenance Log  
Month  
Date  
1
2
3
4
5
6
7
8
9
10  
/
11  
/
12  
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
Operator  
UNIT SECTION  
Compressor  
ACTION  
UNIT  
yes/no  
yes/no  
ppm  
ENTRY  
Check Oil Level  
Send Oil Sample Out for Analysis  
Leak Test  
Annually  
Inspect and Clean Cooler  
Inspect Cooler Heater  
yes/no  
amps  
Every 3 - 5 Years  
Cooler  
Leak Test  
yes/no  
PSI  
yes/no  
ppm  
Record Water Pressure Differential (PSI)  
Inspect Water Pumps  
Leak Test  
Condenser  
Controls  
Starter  
Inspect and Clean Condenser Coil  
General Cleaning and Tightening Connections  
Check Pressure Transducers  
Confirm Accuracy of Thermistors  
General Tightening & Cleaning Connections  
Inspect All Contactors  
Check Refrigerant Charge  
Verify Operation Of EXVs And Record Position  
Record System Super Heat  
yes/no  
yes/no  
yes/no  
yes/no  
yes/no  
yes/no  
yes/no  
0-100%  
deg. F  
Annually  
Annually  
Annually  
System  
NOTE: Equipment failures caused by lack of adherence to the Maintenance Interval Requirements  
are not covered under warranty.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS (cont)  
30RAP Seasonal Shutdown Log  
Month  
Date  
1
2
3
/
4
5
/
6
/
7
/
8
/
9
/
10  
/
11  
/
12  
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
Operator  
UNIT SECTION  
Cooler  
ACTION  
Isolate and Drain Cooler  
Add Glycol for Freeze Protection  
Do Not Disconnect Control Power  
ENTRY  
Controls  
NOTE: Equipment failures caused by lack of adherence to the Maintenance Interval Requirements  
are not covered under warranty.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Copyright 2010 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Catalog No. 04-53300067-01  
Printed in U.S.A.  
Form 30RAP-2T  
Pg 114  
12-10  
Replaces: 30RAP-1T  
Download from Www.Somanuals.com. All Manuals Search And Download.  
START-UP CHECKLIST FOR 30RAP LIQUID CHILLER  
(Remove and use for Job File)  
I. Project Information  
JOB NAME ______________________________________________________________________________  
ADDRESS _______________________________________________________________________________  
CITY ____________________________________________ STATE _______________ ZIP______________  
INSTALLING CONTRACTOR ________________________________________________________________  
SALES OFFICE ___________________________________________________________________________  
START-UP PERFORMED BY ________________________________________________________________  
Design Information  
CAPACITY  
CEAT  
EWT  
LWT  
FLUID TYPE  
FLOW RATE  
P.D.  
UNIT MODEL ______________________________ SERIAL ________________________________  
II. Preliminary Equipment Check  
IS THERE ANY PHYSICAL DAMAGE?  
YES NO  
DESCRIPTION ____________________________________________________________________________  
________________________________________________________________________________________  
1. UNIT IS INSTALLED LEVEL AS PER THE INSTALLATION INSTRUCTIONS.  
2. POWER SUPPLY AGREES WITH THE UNIT NAMEPLATE.  
3. ELECTRICAL POWER WIRING IS INSTALLED PROPERLY.  
4. UNIT IS PROPERLY GROUNDED.  
YES NO  
YES NO  
YES NO  
YES NO  
5. ELECTRICAL CIRCUIT PROTECTION HAS BEEN SIZED AND INSTALLED PROPERLY. YES NO  
6. ALL TERMINALS ARE TIGHT.  
YES NO  
YES NO  
YES NO  
YES NO  
7. ALL PLUG ASSEMBLIES ARE TIGHT.  
8. ALL CABLES AND THERMISTORS HAVE BEEN INSPECTED FOR CROSSED WIRES.  
9. ALL THERMISTORS ARE FULLY INSERTED INTO WELLS.  
Chilled Water System Check  
1. ALL CHILLED WATER VALVES ARE OPEN.  
YES NO  
YES NO  
YES NO  
YES NO  
2. ALL PIPING IS CONNECTED PROPERLY.  
3. ALL AIR HAS BEEN PURGED FROM THE SYSTEM.  
4. CHILLED WATER PUMP IS OPERATING WITH THE CORRECT ROTATION.  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Catalog No. 04-53300067-01 Printed in U.S.A. Form 30RAP-2T Pg CL-1 12-10 Replaces: 30RAP-1T  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. CHILLED WATER PUMP STARTER INTERLOCKED WITH CHILLER.  
6. CHILLED WATER FLOW SWITCH IS OPERATIONAL.  
YES NO  
YES NO  
YES NO  
YES NO  
7. WATER LOOP VOLUME GREATER THAN MINIMUM REQUIREMENTS. (See Table 40).  
8. PROPER LOOP FREEZE PROTECTION PROVIDED TO _____ °F (°C).  
ANTIFREEZE TYPE _____________________ CONCENTRATION __________%.  
IF OUTDOOR AMBIENT IS BELOW 32 F (0° C) THEN ITEMS 9-11 HAVE TO BE  
COMPLETED TO PROVIDE COOLER FREEZE PROTECTION TO –20 F (–29 C). (REFER  
TO WINTER SHUTDOWN FOR PROPER COOLER WINTERIZATION PROCEDURE.)  
9. OUTDOOR PIPING WRAPPED WITH ELECTRIC HEATER TAPE,  
INSULATED AND OPERATIONAL.  
YES NO  
10. COOLER HEATERS INSTALLED AND OPERATIONAL.  
11. CHILLED WATER PUMP CONTROLLED BY CHILLER.  
YES NO  
YES NO  
III. Unit Start-Up  
1. COMPRESSOR OIL LEVEL IS CORRECT.  
YES NO  
YES NO  
YES NO  
YES NO  
YES NO  
2. VERIFY COMPRESSOR MOUNTING BOLT TORQUE IS 7-10 FT-LB. (9.5-13.5 N-M).  
3. LEAK CHECK UNIT. LOCATE, REPAIR AND REPORT ANY REFRIGERANT LEAKS.  
4. VOLTAGE IS WITHIN UNIT NAMEPLATE RANGE.  
5. CONTROL TRANSFORMER PRIMARY CONNECTION SET FOR PROPER VOLTAGE.  
6. CONTROL TRANSFORMER SECONDARY VOLTAGE =  
7. CHECK VOLTAGE IMBALANCE:  
AVERAGE VOLTAGE =  
A-B  
A-C  
B-C  
(A-B + A-C + B-C)/3  
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =  
VOLTAGE IMBALANCE = ____________% (MAX. DEVIATION/AVERAGE VOLTAGE) X 100  
VOLTAGE IMBALANCE LESS THAN 2%.  
(DO NOT START CHILLER IF VOLTAGE IMBALANCE IS GREATER THAN 2%.  
CONTACT LOCAL UTILITY FOR ASSISTANCE.)  
YES NO  
YES NO  
8. VERIFY COOLER FLOW RATE.  
PRESSURE ENTERING COOLER  
PRESSURE LEAVING COOLER  
COOLER PRESSURE DROP  
Psig X 2.31 ft./psi =  
________ psig (kPa)  
________ psig (kPa)  
________ psig (kPa)  
________ ft of water  
________ m of water  
kPa X 0.334 m/psi  
COOLER FLOW RATE  
________ gpm (l/s) (See Cooler Pressure  
Drop Curves from  
Installation Instructions)  
Start and Operate Machine. Complete the Following:  
1. COMPLETE COMPONENT TEST.  
YES NO  
YES NO  
2. CHECK REFRIGERANT AND OIL CHARGE.  
3. RECORD COMPRESSOR MOTOR CURRENT.  
4. RECORD CONFIGURATION SETTINGS.  
YES NO  
YES NO  
5. RECORD OPERATING TEMPERATURES AND PRESSURES.  
6. PROVIDE OPERATING INSTRUCTIONS TO OWNER’S PERSONNEL.  
YES NO  
Instruction Time ________ hours.  
CL-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATING DATA:  
RECORD THE FOLLOWING INFORMATION FROM THE PRESSURES AND TEMPERATURES MODES WHEN  
MACHINE IS IN A STABLE OPERATING CONDITION:  
PRESSURE/TEMPERATURE  
CIRCUIT A  
CIRCUIT B  
DISCHARGE PRESSURE  
DP.A  
DP.B  
SUCTION PRESSURE  
SP.A  
SP.B  
SATURATED CONDENSING TEMP  
SATURATED SUCTION TEMP  
RETURN GAS TEMPERATURE  
LIQUID LINE TEMPERATURE*  
DISCHARGE LINE TEMPERATURE*  
*Readings taken with a digital thermometer.  
SCT.A  
SST.A  
RGT.A  
SCT.B  
SST.B  
RGT.B  
COOLER EWT  
EWT  
LWT  
COOLER LWT  
OUTDOOR-AIR TEMPERATURE  
CONTROL POINT  
OAT  
CTPT  
CAP  
PERCENT TOTAL CAPACITY  
LEAD/LAG LEAVING FLUID  
DLWT  
(Dual Chiller Control Only)  
Compressor Running Current — All readings taken at full load.  
COMPRESSOR MOTOR CURRENT  
COMPRESSOR A1  
L1  
L1  
L1  
L2  
L2  
L2  
L3  
COMPRESSOR A2  
COMPRESSOR B1  
COMPRESSOR B2  
CONDENSER FAN MOTOR CURRENT  
FAN MOTOR 1  
L3  
FAN MOTOR 2  
FAN MOTOR 3  
FAN MOTOR 4  
COOLER PUMP MOTOR CURRENT  
COOLER PUMP 1  
L3  
COOLER PUMP 2  
CL-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Record Software Versions  
MODE — RUN STATUS  
SUB-MODE  
VERS  
ITEM  
DISPLAY  
ITEM  
EXPANSION  
MBB  
AUX1  
EXV  
EMM  
MARQUEE  
NAVIGATOR  
CESR-131460- _ _-_ _  
CESR-131333- _ _-_ _  
CESR-131172- _ _-_ _  
CESR-131174- _ _-_ _  
CESR-131171- _ _-_ _  
CESR-131227- _ _-_ _  
(PRESS ENTER AND ESCAPE SIMULTANEOUSLY TO OBTAIN  
SOFTWARE VERSIONS)  
COMMENTS:  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
_________________________________________________________________________________________  
SIGNATURES:  
START-UP  
CUSTOMER  
TECHNICIAN _____________________________  
REPRESENTATIVE _____________________________  
DATE ___________________________________  
DATE ________________________________________  
CL-4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
III. Unit Start-Up (cont)  
RECORD CONFIGURATION SETTINGS  
UNIT (Configuration Settings)  
SUBMODE  
ITEM  
ITEM EXPANSION  
UNIT CONFIGURATION  
UNIT SIZE  
DISPLAY  
ENTRY  
SIZE  
SZA.1  
SZA.2  
SZA.3  
SZA.4  
SZB.1  
SZB.2  
SZB.3  
SZB.4  
SH.SP  
FAN.S  
EXV  
XXX  
XX  
COMPRESSOR A1 SIZE  
COMPRESSOR A2 SIZE  
COMPRESSOR A3 SIZE  
COMPRESSOR A4 SIZE  
COMPRESSOR B1 SIZE  
COMPRESSOR B2 SIZE  
COMPRESSOR B3 SIZE  
COMPRESSOR B4 SIZE  
SUPERHEAT SETPOINT  
FAN STAGING SELECT  
EXV MODULE INSTALLED  
COMPRESSOR A1 DIGITAL?  
MAXIMUM A1 UNLOAD TIME  
XX  
XX  
XX  
XX  
UNIT  
XX  
XX  
XX  
XX.X F  
X
YES/NO  
YES/NO  
XX  
A1.TY  
MAX.T  
PRESS ESCAPE KEY TO DISPLAY UNIT’. PRESS DOWN ARROW KEY TO DISPLAY OPT1’.  
PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW:  
OPTIONS1 (Options Configuration)  
SUBMODE  
ITEM  
ITEM EXPANSION  
UNIT OPTIONS 1 HARDWARE  
COOLER FLUID  
DISPLAY  
ENTRY  
FLUD  
MLV.S  
D.G.EN  
CSB.E  
CPC  
X
YES/NO  
ENBL/DSBL  
ENBL/DSBL  
ON/OFF  
YES/NO  
YES/NO  
YES/NO  
X
MINIMUM LOAD VALVE SELECT  
DISCHARGE GAS TEMP ENABLE  
CSB BOARDS ENABLE  
COOLER PUMP CONTROL  
COOLER PUMP 1 ENABLE  
COOLER PUMP 2 ENABLE  
COOLER PMP PERIODIC STRT  
COOLER PUMP SELECT  
PM1E  
PM2E  
PM.P.S  
PM.SL  
PM.DY  
PM.DT  
ROT.P  
EMM  
OPT1  
COOLER PUMP SHUTDOWN DLY  
PUMP CHANGEOVER HOURS  
ROTATE COOLER PUMPS NOW  
EMM MODULE INSTALLED  
CND HX TYP 0=RTPF 1=MCHX  
EXV MOP SET POINT  
XX MIN  
XXXX HRS  
YES/NO  
YES/NO  
0/1  
CND.T  
MOPS  
APPR  
XX  
CONFIG APPROACH SETPOINT  
XX  
CL-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
III. Unit Start-Up (cont)  
PRESS ESCAPE KEY TO DISPLAY OPT1’. PRESS DOWN ARROW KEY TO DISPLAY OPT2’.  
PRESS ENTER KEY.  
RECORD CONFIGURATION INFORMATION BELOW.  
OPTIONS2 (Options Configuration)  
SUBMODE  
ITEM  
ITEM EXPANSION  
UNIT OPTIONS 2 CONTROLS  
CONTROL METHOD  
DISPLAY  
ENTRY  
CTRL  
LOAD  
LLCS  
X
LOADING SEQUENCE SELECT  
LEAD/LAG CIRCUIT SELECT  
HIGH LCW ALERT LIMIT  
MINUTES OFF TIME  
X
X
LCWT  
DELY  
XX.X F  
XX  
ICE.M  
CLS.C  
LS.MD  
LS.ST  
LS.ND  
LS.LT  
CTRL  
CCNA  
CCNB  
ICE MODE ENABLE  
ENBL/DSBL  
ENBL/DSBL  
X
OPT2  
CLOSE CONTROL SELECT  
LOW SOUND MODE SELECT  
LOW SOUND START TIME  
LOW SOUND END TIME  
LOW SOUND CAPACITY LIMIT  
CONTROL METHOD  
00:00  
00:00  
XXX %  
X
CCN ADDRESS  
XXX  
CCN BUS NUMBER  
XXX  
PRESS ESCAPE KEY TO DISPLAY OPT2’. PRESS DOWN ARROW KEY TO DISPLAY CCN’.  
PRESS ENTER KEY.  
RECORD CONFIGURATION INFORMATION BELOW.  
CCN (CCN Network Configuration)  
SUB-MODE  
CCN  
ITEM  
CCNA  
CCNB  
BAUD  
ITEM EXPANSION  
CCN ADDRESS  
DISPLAY  
XXX  
ENTRY  
CCN BUS NUMBER  
CCN BAUD RATE  
XXX  
X
PRESS ESCAPE KEY TO DISPLAY CCN’. PRESS DOWN ARROW KEY TO DISPLAY HP.A’.  
PRESS ENTER KEY.  
RECORD CONFIGURATION INFORMATION BELOW.  
HP.A (Head Pressure Cmp. Delta Configuration)  
SUB-MODE  
HP.A  
ITEM  
A1.DT  
A2.DT  
ITEM EXPANSION  
DISPLAY  
XX  
ENTRY  
SCT DELTA FOR COMP A1  
SCT DELTA FOR COMP A2  
XX  
PRESS ESCAPE KEY TO DISPLAY HP.A’. PRESS DOWN ARROW KEY TO DISPLAY HP.B’.  
PRESS ENTER KEY.  
RECORD CONFIGURATION INFORMATION BELOW.  
HP.B (Head Pressure Cmp. Delta Configuration)  
SUB-MODE  
HP.B  
ITEM  
B1.DT  
B2.DT  
ITEM EXPANSION  
DISPLAY  
XX  
ENTRY  
SCT DELTA FOR COMP B1  
SCT DELTA FOR COMP B2  
XX  
CL-6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
III. Unit Start-Up (cont)  
PRESS ESCAPE KEY TO DISPLAY HP.B’. PRESS DOWN ARROW KEY TO DISPLAY EXV.A’.  
PRESS ENTER KEY.  
RECORD CONFIGURATION INFORMATION BELOW.  
EXV.A (Circuit A EXV Configuration)  
SUB-MODE  
ITEM  
STR.A  
MIN.A  
RNG.A  
SPD.A  
POF.A  
MIN.A  
MAX.A  
OVR.A  
TYP.A  
H.SCT  
X.PCT  
X.PER  
A.PCT  
M.PCT  
S.PCT  
DELY  
ITEM EXPANSION  
EXV CIRC.A START POS  
EXV CIRC.A MIN POSITION  
EXVA STEPS IN RANGE  
EXVA STEPS PER SECOND  
EXVA FAIL POSITION IN %  
EXVA MINIMUM STEPS  
DISPLAY  
XXX  
ENTRY  
XXX  
XXXXX  
XXXXX  
XXX  
XXXXX  
XXXXX  
XXX  
EXVA MAXIMUM STEPS  
EXVA OVERRUN STEPS  
EXVA STEPPER TYPE  
EXV.A  
0,1  
HIGH SCT THRESHOLD  
OPEN EXV X% ON 2ND COMP  
MOVE EXV X% ON DISCRSOL  
PRE-OPEN EXV - FAN ADDING  
PRE-CLOSE EXV - FAN SUB  
PRE-CLOSE EXV - LAG SHUT  
LAG START DELAY  
XXX  
XX  
XX  
XXX  
XXX  
XXX  
XXX  
PRESS ESCAPE KEY TO DISPLAY EXV.A’. PRESS DOWN ARROW KEY TO DISPLAY EXV.B’.  
PRESS ENTER KEY.  
RECORD CONFIGURATION INFORMATION BELOW.  
EXV.B (Circuit B EXV Configuration)  
SUB-MODE  
ITEM  
STR.B  
MIN.B  
RNG.B  
SPD.B  
POF.B  
MIN.B  
MAX.B  
OVR.AB  
TYP.B  
ITEM EXPANSION  
EXV CIRC.B START POS  
EXV CIRC.B MIN POSITION  
EXVB STEPS IN RANGE  
EXVB STEPS PER SECOND  
EXVB FAIL POSITION IN %  
EXVB MINIMUM STEPS  
EXVB MAXIMUM STEPS  
EXVB OVERRUN STEPS  
EXVB STEPPER TYPE  
DISPLAY  
XXX  
ENTRY  
XXX  
XXXXX  
XXXXX  
XXX  
EXV.B  
XXXXX  
XXXXX  
XXX  
0,1  
PRESS ESCAPE KEY TO DISPLAY EXV.B’. PRESS DOWN ARROW KEY TO DISPLAY MM’.  
PRESS ENTER KEY.  
RECORD CONFIGURATION INFORMATION BELOW.  
MM (Motormaster Configuration Settings)  
SUB-MODE  
MM  
ITEM  
MMR.S  
P.GAN  
I.GAN  
D.GAN  
MIN.S  
ITEM EXPANSION  
DISPLAY  
YES/NO  
XX  
ENTRY  
MOTORMASTER SELECT  
HEAD PRESSURE P GAIN  
HEAD PRESSURE I GAIN  
HEAD PRESSURE D GAIN  
MINIMUM FAN SPEED  
XX.X  
XX.X  
XX  
CL-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
III. Unit Start-Up (cont)  
PRESS ESCAPE KEY TO DISPLAY MM’. PRESS DOWN ARROW KEY TO DISPLAY RSET’.  
PRESS ENTER KEY.  
RECORD CONFIGURATION INFORMATION BELOW.  
RSET (Reset Configuration Settings)  
SUBMODE  
ITEM  
ITEM EXPANSION  
RESET COOL TEMP  
DISPLAY  
ENTRY  
RSET  
CRST  
MA.DG  
RM.NO  
RM.F  
COOLING RESET TYPE  
X
XX.X °F  
XXX.X °F  
XXX.X °F  
XX.X °F  
XXX.X °F  
XXX.X °F  
XX.X °F  
X
4-20 - DEGREES RESET  
REMOTE - NO RESET TEMP  
REMOTE - FULL RESET TEMP  
REMOTE - DEGREES RESET  
RETURN - NO RESET TEMP  
RETURN - FULL RESET TEMP  
RETURN - DEGREES RESET  
DEMAND LIMIT SELECT  
DEMAND LIMIT AT 20 MA  
LOADSHED GROUP NUMBER  
LOADSHED DEMAND DELTA  
MAXIMUM LOADSHED TIME  
DEMAND LIMIT SWITCH 1  
DEMAND LIMIT SWITCH 2  
LEAD/LAG CHILLER ENABLE  
MASTER/SLAVE SELECT  
SLAVE ADDRESS  
RM.DG  
RT.NO  
RT.F  
RT.DG  
DMDC  
DM20  
SHNM  
SHDL  
SHTM  
DLS1  
DLS2  
LLEN  
MSSL  
SLVA  
XXX %  
XXX  
XXX %  
XXX  
XXX %  
XXX %  
ENBL/DSBL  
SLVE/MAST  
XXX  
LLBL  
LEAD/LAG BALANCE SELECT  
LEAD/LAG BALANCE DELTA  
LAG START DELAY  
X
LLBD  
LLDY  
XXX  
XXX  
PARA  
PARALLEL CONFIGURATION  
YES/NO  
PRESS ESCAPE KEY TO DISPLAY RSET’. PRESS DOWN ARROW KEY TO DISPLAY SLCT’.  
PRESS ENTER KEY.  
RECORD CONFIGURATION INFORMATION BELOW:  
SLCT (Setpoint and Ramp Load Configuration)  
SUBMODE  
ITEM  
ITEM EXPANSION  
SETPOINT AND RAMP LOAD  
COOLING SETPOINT SELECT  
RAMP LOAD SELECT  
DISPLAY  
ENTRY  
SLCT  
CLSP  
RL.S  
X
ENBL/DSBL  
X.X  
CRMP  
SCHD  
Z.GN  
COOLING RAMP LOADING  
SCHEDULE NUMBER  
XX  
DEADBAND MULTIPLIER  
X.X  
CL-8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
III. Unit Start-Up (cont)  
PRESS ESCAPE KEY SEVERAL TIMES TO GET TO THE MODE LEVEL (BLANK DISPLAY). USE THE  
ARROW KEYS TO SCROLL TO THE SET POINT LED. PRESS ENTER TO DISPLAY SETPOINTS.  
RECORD CONFIGURATION INFORMATION BELOW:  
SETPOINT  
SUBMODE  
ITEM  
ITEM EXPANSION  
COOLING SETPOINTS  
COOLING SETPOINT 1  
COOLING SETPOINT 2  
ICE SETPOINT  
DISPLAY  
ENTRY  
COOL  
CSP.1  
CSP.2  
CSP.3  
XXX.X °F  
XXX.X °F  
XXX.X °F  
HEAD PRESSURE SETPOINTS  
HEAD SET POINT  
H.DP  
F.ON  
XXX.X °F  
XXX.X °F  
XXX.X °F  
XX.X °F  
FAN ON SET POINT  
HEAD  
FRZ  
F.OFF  
B.OFF  
F.DLT  
FAN OFF SET POINT  
BASE FAN OFF DELTA TEMP  
FAN STAGE DELTA  
XX.X °F  
BRINE FREEZE SETPOINT  
BRINE FREEZE POINT  
BR.FZ  
XXX.X °F  
CL-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
III. Unit Start-Up (cont)  
COMPONENT TEST  
USE ESCAPE/ARROW KEYS TO ILLUMINATE CONFIGURATION LED. PRESS ENTER TO DISPLAY DISP’.  
PRESS ENTER AGAIN TO DISPLAY TEST’ FOLLOWED BY ‘OFF’. PRESS ENTER TO STOP DISPLAY AT  
‘OFF’ AND ENTER AGAIN SO ‘OFF’ DISPLAY FLASHES. ‘PASS’ AND ‘WORD’ WILL FLASH IF PASSWORD  
NEEDS TO BE ENTERED. PRESS ENTER TO DISPLAY PASSWORD FIELD AND USE THE ENTER KEY FOR  
EACH OF THE FOUR PASSWORD DIGITS. USE ARROW KEYS IF PASSWORD IS OTHER THAN STANDARD.  
AT FLASHING ‘OFF’ DISPLAY, PRESS THE UP ARROW KEY TO DISPLAY ON’ AND PRESS ENTER. ALL LED  
SEGMENTS AND MODE LEDS WILL LIGHT UP. PRESS ESCAPE TO STOP THE TEST. PRESS ESCAPE TO  
RETURN TO THE ‘DISP’ DISPLAY. PRESS THE ESCAPE KEY AGAIN AND USE THE ARROW KEYS TO ILLU-  
MINATE THE SERVICE TEST LED. PRESS ENTER TO DISPLAY TEST’. PRESS ENTER TO STOP DISPLAY  
AT OFF’ AND ENTER AGAIN SO ‘OFF’ FLASHES. PRESS THE UP ARROW KEY AND ENTER TO ENABLE  
THE MANUAL MODE. PRESS ESCAPE AND DISPLAY NOW SAYS ‘TEST’ ‘ON’. REFER TO THE TABLE  
BELOW.  
Service Test Mode and Sub-Mode Directory  
KEYPAD  
ENTRY  
ITEM  
Completed  
(Yes/No)  
SUB-MODE  
TEST  
ITEM DISPLAY  
COMMENT  
EXPANSION  
ON/OFF  
SERVICE TEST MODE  
To Enable Service Test Mode,  
move Enable/Off/Remote  
Contact switch to OFF. Change  
TEST to ON. Move switch to  
ENABLE.  
ENTER  
OUTPUTS AND PUMPS  
FAN 1 RELAY  
ENTER  
FAN1  
FAN2  
FAN3  
FAN4  
FAN5  
FAN6  
V.HPA  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
ON/OFF  
XXX%  
Condenser fan contactor 1  
Condenser fan contactor 2  
Condenser fan contactor 3  
Condenser fan contactor 4  
Condenser fan contactor 5  
Condenser fan contactor 6  
FAN 2 RELAY  
FAN 3 RELAY  
FAN 4 RELAY  
FAN 5 RELAY  
FAN 6 RELAY  
VAR HEAD PRESS %  
OUTS  
VAR HEAD PRESS %  
V.HPB  
CLP.1  
CLP.2  
XXX%  
ON/OFF  
ON/OFF  
COOLER PUMP 1 RELAY  
COOLER PUMP 2 RELAY  
COOLER/PUMP HEATER  
REMOTE ALARM RELAY  
CL.HT ON/OFF  
RMT.A ON/OFF  
CIRCUIT A COMPRESSOR TEST  
COMPRESSOR A1 RELAY  
ENTER  
CC.A1 ON/OFF  
UL.TM  
0 to 15  
COMP A1 UnLOAD TIME  
COMPRESSOR A2 RELAY  
COMPRESSOR A3 RELAY  
COMPRESSOR A4 RELAY  
MINIMUM LOAD VALVE RELAY  
CC.A2 ON/OFF  
CC.A3 ON/OFF  
CC.A4 ON/OFF  
CMPA  
MLV  
ON/OFF  
CIRCUIT B COMPRESSOR TEST  
COMPRESSOR B1 RELAY  
ENTER  
CC.B1 ON/OFF  
CC.B2 ON/OFF  
CC.B3 ON/OFF  
CC.B4 ON/OFF  
See Note  
See Note  
See Note  
See Note  
COMPRESSOR B2 RELAY  
COMPRESSOR B3 RELAY  
COMPRESSOR B4 RELAY  
CMPB  
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.  
Copyright 2010 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Catalog No. 04-53300067-01 Printed in U.S.A. Form 30RAP-2T Pg CL-10 12-10 Replaces: 30RAP-1T  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Billy Goat Lawn Mower CR550HCV User Manual
Black Decker Iron BDCMTS User Manual
Black Decker Vacuum Cleaner 90521333 User Manual
Boss Audio Systems Stereo Amplifier CH550 User Manual
Brother Printer 5140 User Manual
Cannon Scanner MS 300 User Manual
Canon Fax Machine FAX L800 User Manual
Casio Watch MA0804 EC User Manual
Cavalry Storage Washer Dryer CAXR SERIES User Manual
Chevrolet Automobile 50061011 User Manual