30RAP010-060
AQUASNAP® Air-Cooled Chillers
with COMFORTLINK™ Controls
Controls, Start-Up, Operation,
Service, and Troubleshooting
Page
CONTENTS
System Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
START-UP AND OPERATION . . . . . . . . . . . . . . . . . . . . 45,46
Actual Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Check Refrigerant Charge. . . . . . . . . . . . . . . . . . . . . . . . . 45
Operating Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . .2
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Conventions Used in this Manual. . . . . . . . . . . . . . . . . . . .3
Basic Controls Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
CONTROLS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-44
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Main Base Board (MBB) . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Energy Management Module (EMM) . . . . . . . . . . . . . . . .19
Current Sensor Board (CSB) . . . . . . . . . . . . . . . . . . . . . . .19
AUX Board (AUX) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Expansion Valve Board (EXV) . . . . . . . . . . . . . . . . . . . . . .19
Enable/Off/Remote Contact Switch . . . . . . . . . . . . . . . . .19
Emergency On/Off Switch . . . . . . . . . . . . . . . . . . . . . . . . . .19
Board Addresses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Control Module Communication . . . . . . . . . . . . . . . . . . . .19
Carrier Comfort Network® (CCN) Interface . . . . . . . . . .19
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
•
•
•
TEMPERATURES
LOW AMBIENT OPERATION
VOLTAGE — ALL UNITS
OPERATION SEQUENCE . . . . . . . . . . . . . . . . . . . . . .46,47
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47-63
Electronic Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
•
CONTROL COMPONENTS
Electronic Expansion Valve (EXV). . . . . . . . . . . . . . . 47
EXV Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . 47
•
•
•
FIELD SERVICING INSTRUCTIONS
VALVE REPLACEMENT
VALVE REASSEMBLY
Compressor Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . 49
Cooler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
•
•
•
COOLER LEAVING FLUID SENSOR
•
BRAZED-PLATE COOLER HEAT EXCHANGER
REPLACEMENT
BRAZED-PLATE COOLER HEAT EXCHANGER
CLEANING
COOLER ENTERING FLUID SENSOR
COMPRESSOR RETURN GAS
•
TEMPERATURE SENSOR
•
•
•
OUTDOOR-AIR TEMPERATURE SENSOR (OAT)
DISCHARGE TEMPERATURE THERMISTOR (DTT)
REMOTE SPACE TEMPERATURE SENSOR OR DUAL
LEAVING WATER TEMPERATURE SENSOR
Oil Charge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Microchannel Heat Exchanger (MCHX)
Condenser Coil Maintenance and Cleaning
Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Check Refrigerant Feed Components . . . . . . . . . . . . . . 50
Energy Management Module . . . . . . . . . . . . . . . . . . . . . . .29
Loss-of-Cooler Flow Protection. . . . . . . . . . . . . . . . . . . . .29
Electronic Expansion Valves (EXV) . . . . . . . . . . . . . . . . .29
Capacity Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
•
•
•
•
FILTER DRIER
MOISTURE-LIQUID INDICATOR
MINIMUM LOAD VALVE
PRESSURE RELIEF DEVICES
•
•
•
•
MINUTES LEFT FOR START
MINUTES OFF TIME
LEAD/LAG DETERMINATION
CAPACITY CONTROL OVERRIDES
Check Unit Safeties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
•
•
•
•
•
HIGH-PRESSURE SWITCH
PRESSURE TRANSDUCERS
COOLER FREEZE-UP PROTECTION
HEATER CABLE
Head Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Operation of Machine Based on Control Method
and Cooling Set Point Selection Settings. . . . . . . . .32
Cooling Set Point Select. . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Low Sound Mode Operation . . . . . . . . . . . . . . . . . . . . . . . .34
Heating Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Service Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Optional Factory-Installed Hydronic Package. . . . . . .34
Cooler Pump Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Cooler Pump Sequence of Operation. . . . . . . . . . . . . . .35
Configuring and Operating Dual Chiller Control . . . .36
Temperature Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Demand Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
WINTER SHUTDOWN
Thermistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Pressure Transducers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Chilled Water Flow Switch. . . . . . . . . . . . . . . . . . . . . . . . . . 53
Strainer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Condenser Fans. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Motormaster® V Controller . . . . . . . . . . . . . . . . . . . . . . . . . 58
•
•
•
•
•
•
GENERAL OPERATION
CONFIGURATION
DRIVE PROGRAMMING
EPM CHIP
LOSS OF CCN COMMUNICATIONS
REPLACING DEFECTIVE MODULES
•
•
DEMAND LIMIT (2-Stage Switch Controlled)
EXTERNALLY POWERED DEMAND LIMIT
(4 to 20 mA Controlled)
Hydronic Package. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63,64
Recommended Maintenance Schedule . . . . . . . . . . . . . 63
Microchannel Heat Exchanger (MCHX)
Condenser Coil Maintenance and Cleaning
Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . 64-73
•
DEMAND LIMIT (CCN Loadshed Controlled)
Cooling Set Point (4 to 20 mA). . . . . . . . . . . . . . . . . . . . . .43
Digital Scroll Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
•
•
DIGITAL SCROLL OPERATION
DIGITAL COMPRESSOR CONFIGURATION
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44,45
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300067-01 Printed in U.S.A. Form 30RAP-2T Pg 1 12-10 Replaces: 30RAP-1T
Download from Www.Somanuals.com. All Manuals Search And Download.
Control System for 30RAP units. The display has up and down
arrow keys, an key, and an key. These
GENERAL
ESCAPE
keys are used to navigate through the different levels of the
display structure. Press the key until the highest
ENTER
This publication contains Controls, Start-Up, Operation,
Service, and Troubleshooting information for the 30RAP
AquaSnap® air-cooled chillers. See Table 1. These chillers are
equipped with ComfortLink™ controls and electronic expan-
sion valves (EXVs).
ESCAPE
operating level is displayed to move through the top 11 mode
levels indicated by LEDs on the left side of the display. See
Fig. 1 and Tables 2-14.
WARNING
Once within a mode or sub-mode, pressing the
ENTER
keys simultaneously will put the scrolling
This unit uses a microprocessor-based electronic control
system. Do not use jumpers or other tools to short out or
bypass components or otherwise depart from recom-
mended procedures. Any short-to-ground of the control
board or accompanying wiring may destroy the board or
electrical component.
and
ESCAPE
marquee display into expanded text mode where the full mean-
ing of all sub-modes, items and their values can be displayed
for the current selection. Press the
and
ESCAPE
ENTER
keys to return the scrolling marquee display to its default menu
of rotating display items (those items in Run StatusVIEW).
In addition, the password will be disabled, requiring that it be
entered again before changes can be made to password protect-
Table 1 — Unit Sizes
UNIT
NOMINAL CAPACITY (TONS)
30RAP010
30RAP015
30RAP018
30RAP020
30RAP025
30RAP030
30RAP035
30RAP040
30RAP045
30RAP050
30RAP055
30RAP060
10
14
16
19
24
28
34
39
43
48
53
56
ed items. Press the
text mode.
key to exit out of the expanded
ESCAPE
NOTE: When the Language Selection (Configuration
DISPLANG), variable is changed, all appropriate display
expansions will immediately change to the new language. No
power-off or control reset is required when reconfiguring
languages.
When a specific item is located, the item name alternates
with the value. Press the
ENTER
and the value will be displayed. Press
key at a changeable item
again and the
ENTER
value will begin to flash indicating that the value can be
changed. Use the up and down arrow keys to change the value,
Conventions Used in This Manual — The follow-
ing conventions for discussing configuration points for the
local display (scrolling marquee or Navigator™ accessory)
will be used in this manual.
and confirm the value by pressing the
key.
ENTER
Point names will be written with the mode name first, then
any sub-modes, then the point name, each separated by an
arrow symbol (. Names will also be shown in bold
and italics. As an example, the Lead/Lag Circuit Select Point,
which is located in the Configuration mode, Option sub-mode,
would be written as Configuration OPTNLLCS.
MODE
Run Status
Service Test
Temperature
Pressures
Setpoints
Alarm Status
Inputs
Outputs
This path name will show the user how to navigate through
the local display to reach the desired configuration. The user
would scroll through the modes and sub-modes using the
Configuration
Time Clock
Operating Modes
Alarms
ESCAPE ENTER
and
keys. The arrow symbol in the path name repre-
to move into the next level of the
Fig. 1 — Scrolling Marquee Display
sents pressing
menu structure.
ENTER
Changing item values or testing outputs is accomplished in
the same manner. Locate and display the desired item. Press
When a value is included as part of the path name, it will be
shown at the end of the path name after an equals sign. If the
value represents a configuration setting, an explanation will
be shown in parenthesis after the value. As an example,
ConfigurationOPTNLLCS = 1 (Circuit A leads).
so that the item value flashes. Use the arrow keys to
ENTER
change the value or state and press the
key to accept
ENTER
key to return to the next higher level of
it. Press the
ESCAPE
structure. Repeat the process as required for other items.
Pressing the
and
keys simultaneously
ESCAPE
ENTER
Items in the Configuration and Service Test modes are pass-
word protected. The words ‘PASS’ and ‘WORD’ will alternate
on the display when required. The default password is 0111.
will scroll an expanded text description of the point name or
value across the display. The expanded description is shown in
the local display tables but will not be shown with the path
names in text.
The CCN (Carrier Comfort Network®) point names are also
referenced in the local display tables for users configuring the
unit with CCN software instead of the local display. The CCN
tables are located in Appendix B of the manual.
Press
ENTER
and the 1111 password will be displayed. Press
ENTER
again and the first digit will begin to flash. Use the
arrow keys to change the number and press
to accept
ENTER
the digit. Continue with the remaining digits of the password.
The password can only be changed through CCN operator in-
terface software such as ComfortWORKS®, ComfortVIEW™
and Service Tool.
Basic Controls Usage
SCROLLING MARQUEE DISPLAY — The scrolling mar-
quee display is the standard interface display to the ComfortLink
See Tables 2-14 and Appendix A for further details.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
ACCESSORY NAVIGATOR™ DISPLAY MODULE —
The Navigator module provides a mobile user interface to the
ComfortLink™ control system, which is only available as a
the Navigator module, press the
play reads, “Select a menu item.” Using the arrow keys move
to the Configuration mode. Press
this mode. The display will read:
key until the dis-
ESCAPE
to obtain access to
ENTER
field-installed accessory. The display has up and down arrow
keys, an
key, and an
key. These keys are
ESCAPE
used to navigate through the different levels of the display
structure. Press the key until ‘Select a Menu Item’
ENTER
> TEST OFF
METR OFF
LANG ENGLISH
ESCAPE
is displayed to move through the top 11 mode levels indicated
by LEDs on the left side of the display. See Fig. 2.
Pressing
will cause the “OFF” to flash. Use the up
ENTER
or down arrow to change “OFF” to “ON”. Pressing
ENTER
will illuminate all LEDs and display all pixels in the view
screen. Pressing and simultaneously
Once within a Mode or sub-mode, a “>” indicates the cur-
rently selected item on the display screen. Pressing the
ESCAPE
ENTER
and
keys simultaneously will put the Nav-
ESCAPE
ENTER
allows the user to adjust the display contrast. Use the up or
down arrows to adjust the contrast. The screen’s contrast will
change with the adjustment. Press
change. The Navigator module will keep this setting as long as
it is plugged in to the LEN bus.
igator module into expanded text mode where the full meaning
of all sub-modes, items and their values can be displayed. Press-
to accept the
ENTER
ing the
and
keys when the display says
ESCAPE
ENTER
‘Select Menu Item’ (Mode LED level) will return the Navigator
module to its default menu of rotating display items (those items
in Run StatusVIEW). In addition, the password will be dis-
abled, requiring that it be entered again before changes can be
Adjusting the Backlight Brightness — The backlight of the
display can be adjusted to suit ambient conditions. The factory
default is set to the highest level. To adjust the backlight of the
made to password protected items. Press the
exit out of the expanded text mode.
key to
ESCAPE
Navigator module, press the
key until the display
ESCAPE
reads, “Select a menu item.” Using the arrow keys move to the
NOTE: When the Language Selection (Configuration
DISPLANG), variable is changed, all appropriate display
expansions will immediately change to the new language. No
power-off or control reset is required when reconfiguring
languages.
Configuration mode. Press
mode. The display will read:
> TEST OFF
to obtain access to this
ENTER
METR OFF
LANG ENGLISH
will cause the “OFF” to flash. Use the up
When a specific item is located, the item name appears on the
left of the display, the value will appear near the middle of the
display and the units (if any) will appear on the far right of the
Pressing
ENTER
or down arrow keys to change “OFF” to “ON”. Pressing
will illuminate all LEDs and display all pixels in the
ENTER
display. Press the
key at a changeable item and the val-
ENTER
ue will begin to flash. Use the up and down arrow keys to change
the value, and confirm the value by pressing the key.
view screen. Pressing the up and down arrow keys simultane-
ously allows the user to adjust the display brightness. Use the
up or down arrow keys to adjust screen brightness. Press
to accept the change. The Navigator module will
keep this setting as long as it is plugged in to the LEN bus.
ENTER
Changing item values or testing outputs is accomplished in
the same manner. Locate and display the desired item. Press
ENTER
so that the item value flashes. Use the arrow keys to
ENTER
change the value or state and press the
key to accept
ENTER
key to return to the next higher level of
Comf
it. Press the
ESCAPE
or
t
Link
structure. Repeat the process as required for other items.
Items in the Configuration and Service Test modes are pass-
word protected. The words Enter Password will be displayed
when required, with 1111 also being displayed. The default
password is 1111. Use the arrow keys to change the number
MODE
Alar
Run Status
m
Status
Ser
vice
Te
s
t
Te
m
per
atur
es
Pressure
Setpoints
Inputs
s
Outputs
Configur
ation
Cloc
k
Tim
e
and press
to enter the digit. Continue with the re-
ESC
ENTER
Oper
ating Modes
Alar
m
s
maining digits of the password. The password can only be
changed through CCN operator interface software such as
ComfortWORKS, ComfortVIEW and Service Tool.
ENTER
Adjusting the Contrast — The contrast of the display can be
adjusted to suit ambient conditions. To adjust the contrast of
Fig. 2 — Accessory Navigator™ Display Module
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2 — Scrolling Marquee Display Menu Structure*
RUN
STATUS
SERVICE
TEST
SET
POINTS
TIME
CLOCK
OPERATING
MODES
MODE
TEMPERATURES PRESSURES
INPUTS OUTPUTS CONFIGURATION
ALARMS
Auto
View of
Run Status
(VIEW)
Service
Test Mode
(TEST)
Ent and Leave Unit
Temps
Pressures
Ckt A
(PRC.A)
Cooling
Setpoints
(COOL)
General
Inputs
(GEN.I)
General
Outputs
(GEN.O)
Display
Configuration
(DISP)
Time of
Day
(TIME)
Modes
(MODE)
Current
(CRNT)
(UNIT)
Unit Run
Hour and
Start
Head
Outputs
Circuit A
EXV
Month,
Date, Day,
and Year
(DATE)
Outputs
and Pumps
(OUTS)
Temperatures
Ckt A
(CIR.A)
Pressures
Ckt B
(PRC.B)
Circuit
Inputs
(CRCT)
Unit
Configuration
(UNIT)
Reset
Alarms
(RCRN)
Pressure
Setpoint
(HEAD)
(RUN)
(A.EXV)
Brine
Freeze
Setpoint
(FRZ)
Outputs
Circuit B
EXV
Daylight
Savings
Time
Compressor Ciruit A Comp
Temperatures
Ckt B
(CIR.B)
4-20mA
Inputs
(4-20)
Unit Options 1
Hardware
(OPT1)
Alarm
History
(HIST)
Run Hours
(HOUR)
Test
(CMPA)
(B.EXV)
(DST)
Local
Holiday
Schedules
(HOL.L)
Compressor Ciruit B Comp
Outputs
Circuit A
(CIR.A)
Unit Options 2
Controls
(OPT2)
Starts
Test
(STRT)
(CMPB)
Local
Occu-
Preventive
Maintenance
(PM)
Outputs
Circuit B
(CIR.B)
CCN Network
Configuration
(CCN)
pancy
Schedule
(SCH.L)
Software
Version
(VERS)
Head Pressure
Comp. Delta
(HP.A)
Head Pressure
Comp. Delta
(HP.B)
Schedule
Override
(OVR)
SUB-MODE
Cir. A EXV
Configuration
(EXV.A)
Cir. B EXV
Configuration
(EXV.B)
Motormaster
Configuration
(MM)
Reset Cool Temp
(RSET)
Set Point and
Ramp Load
(SLCT)
Service
Configuration
(SERV)
Broadcast
Configuration
(BCST)
LEGEND
Ckt — Circuit
*Throughout this text, the location of items in the menu structure will be
described in the following format:
Item Expansion (Mode NameSub-mode NameITEM)
For example, using the language selection item:
Language Selection (ConfigurationDISPLANG)
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 3 — Run Status Mode and Sub-Mode Directory
KEYPAD
ENTRY
ITEM
DISPLAY SUB-ITEM DISPLAY SUB-ITEM DISPLAY
EXPANSION
SUB-MODE
VIEW
ITEM
EWT
LWT
COMMENT
ENTER
XXX.X F
ENTERING FLUID TEMP
LEAVING FLUID TEMP
ACTIVE SETPOINT
CONTROL POINT
XXX.X F
SETP XXX.X F
CTPT XXX.X F
LOD.F
STAT
XXX
X
LOAD/UNLOAD FACTOR
CONTROL MODE
0 = Service Test
1 = Off Local
2 = Off CCN
3 = Off Time
4 = Off Emrgcy
5 = On Local
6 = On CCN
7 = On Time
8 = Ht Enabled
9 = Pump Delay
LD.PM
OCC
LEAD PUMP
OCCUPIED
YES/NO
YES/NO
LS.AC
LOW SOUND ACTIVE
OVERRIDE MODES IN EFFECT
PERCENT TOTAL CAPACITY
REQUESTED STAGE
CURRENT ALARMS & ALERTS
TIME OF DAY
MODE YES/NO
CAP
STGE
ALRM
TIME
XXX %
X
XXX
XX.XX
XX
00.00-23.59
1 = January, 2 = February, etc.
01-31
MNTH
DATE
YEAR
MONTH OF YEAR
XX
DAY OF MONTH
XX
YEAR OF CENTURY
MACHINE OPERATING HOURS
MACHINE STARTS
RUN
ENTER
HRS.U XXXX HRS
STR.U
HR.P1
HR.P2
XXXX
XXXX.X
XXXX.X
PUMP 1 RUN HOURS
PUMP 2 RUN HOURS
CIRCUIT A RUN HOURS
HOUR
ENTER
HRS.A XXXX HRS
HRS.B XXXX HRS
HR.A1 XXXX HRS
HR.A2 XXXX HRS
HR.B1 XXXX HRS
HR.B2 XXXX HRS
CIRCUIT B RUN HOURS
See Note
COMPRESSOR A1 RUN HOURS
COMPRESSOR A2 RUN HOURS
COMPRESSOR B1 RUN HOURS
COMPRESSOR B2 RUN HOURS
COMPRESSOR A1 STARTS
COMPRESSOR A2 STARTS
COMPRESSOR B1 STARTS
COMPRESSOR B2 STARTS
PUMP MAINTENANCE
See Note
See Note
STRT
ENTER
ST.A1
ST.A2
ST.B1
ST.B2
PUMP
XXXX
XXXX
XXXX
XXXX
See Note
See Note
PM
ENTER
ENTER
SI.PM
P.1.DN
P.2.DN
P.1.MN
P.2.MN
XXXX HRS
XXXX HRS
XXXX HRS
YES/NO
PUMP SERVICE INTERVAL
PUMP 1 SERVICE COUNTDOWN
PUMP 2 SERVICE COUNTDOWN
PUMP 1 MAINTENANCE DONE
PUMP 2 MAINTENANCE DONE
Default: 8760
User Entry
User Entry
YES/NO
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 3 — Run Status Mode and Sub-Mode Directory (cont)
KEYPAD
ENTRY
ITEM
DISPLAY SUB-ITEM DISPLAY SUB-ITEM DISPLAY
EXPANSION
SUB-MODE
PM (cont)
ITEM
COMMENT
PMDT
PUMP MAINTENANCE DATES
ENTER
P.1.M0
P.1.M1
P.1.M2
P.1.M3
P.1.M4
P.2.M0
P.2.M1
P.2.M2
P.2.M3
P.2.M4
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
ENTER
ENTER
STRN
STRAINER MAINTENANCE
STRAINER SRVC INTERVAL
STRAINER SRVC COUNTDOWN
STRAINER MAINT. DONE
STRAINER MAINT. DATES
MM/DD/YY HH:MM
SI.ST
S.T.DN
S.T.MN
ST.DT
XXXX HRS
XXXX HRS
YES/NO
Default: 8760
User Entry
ENTER
S.T.M0
S.T.M1
S.T.M2
S.T.M3
S.T.M4
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
ENTER
ENTER
COIL
COIL MAINTENANCE
COIL SRVC INTER
SI.CL
C.L.DN
C.L.MN
CL.DT
XXXX HRS
XXXX HRS
YES/NO
Default: 8760
User Entry
COIL SERVICE COUNTDOWN
COIL MAINT. DONE
COIL MAINTENANCE DATES
MM/DD/YY HH:MM
ENTER
C.L.M0
C.L.M1
C.L.M2
C.L.M3
C.L.M4
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
VERS
ENTER
MBB
EXV
CESR131460-xx-xx
xx-xx is Version number*
xx-xx is Version number*
xx-xx is Version number*
xx-xx is Version number*
xx-xx is Version number*
xx-xx is Version number*
CESR131172-xx-xx
AUX1
EMM
MARQ
NAVI
CESR131333-xx-xx
CESR131174-xx-xx
CESR131171-xx-xx
CESR130227-xx-xx
*Press
ENTER
and
ESCAPE
simultaneously to obtain version number.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4 — Service Test Mode and Sub-Mode Directory
KEYPAD
ENTRY
ITEM
SUB-MODE
TEST
ITEM
DISPLAY
COMMENT
EXPANSION
ON/OFF
SERVICE TEST MODE
To Enable Service Test Mode,
move Enable/Off/Remote
Contact switch to OFF. Change
TEST to ON. Move switch to
ENABLE.
ENTER
OUTS
OUTPUTS AND PUMPS
EXV A % OPEN
ENTER
EXV.A
EXV.B
FAN1
FAN2
FAN3
FAN4
FAN5
FAN6
V.HPA
V.HPB
CLP.1
CLP.2
UL.TM
CL.HT
RMT.A
0 to 100%
0 to 100%
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
0 to 100%
0 to 100%
ON/OFF
ON/OFF
0 to 15
EXV B % OPEN
FAN 1 RELAY
FAN 2 RELAY
FAN 3 RELAY
FAN 4 RELAY
FAN 5 RELAY
FAN 6 RELAY
VAR HEAD PRESS %
VAR HEAD PRESS %
COOLER PUMP 1 RELAY
COOLER PUMP 2 RELAY
COMP A1 UNLOAD TIME
COOLER/PUMP HEATER
REMOTE ALARM RELAY
ON/OFF
ON/OFF
CMPA
CIRCUIT A COMPRESSOR TEST
COMPRESSOR A1 RELAY
ENTER
CC.A1
UL.TM
CC.A2
CC.A3
CC.A4
MLV
ON/OFF
0 to 15
COMP A1 UNLOAD TIME
COMPRESSOR A2 RELAY
COMPRESSOR A3 RELAY
COMPRESSOR A4 RELAY
MINIMUM LOAD VALVE RELAY
ON/OFF
ON/OFF
ON/OFF
ON/OFF
CMPB
CIRCUIT B COMPRESSOR TEST
COMPRESSOR B1 RELAY
See Note
ENTER
CC.B1
CC.B2
CC.B3
CC.B4
ON/OFF
ON/OFF
ON/OFF
ON/OFF
COMPRESSOR B2 RELAY
COMPRESSOR B3 RELAY
COMPRESSOR B4 RELAY
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 5 — Temperature Mode and Sub-Mode Directory
KEYPAD
ENTRY
ITEM
SUB-MODE
UNIT
ITEM
DISPLAY
COMMENT
EXPANSION
ENT AND LEAVE UNIT TEMPS
ENTER
ENTER
ENTER
CEWT
CLWT
OAT
XXX.X F
XXX.X F
XXX.X F
XXX.X F
XXX.X F
COOLER ENTERING FLUID
COOLER LEAVING FLUID
OUTSIDE AIR TEMPERATURE
SPACE TEMPERATURE
SPT
DLWT
LEAD/LAG LEAVING FLUID
CIR.A
TEMPERATURES CIRCUIT A
SCT.A
SST.A
RGT.A
D.GAS
SH.A
XXX.X F
XXX.X F
XXX.X F
XXX.X F
XXX.X ^F
SATURATED CONDENSING TMP
SATURATED SUCTION TEMP
COMPR RETURN GAS TEMP
DISCHARGE GAS TEMP
SUCTION SUPERHEAT TEMP
CIR.B
TEMPERATURES CIRCUIT B
See Note
See Note
SCT.B
SST.B
RGT.B
SH.B
XXX.X F
XXX.X F
XXX.X F
XXX.X ^F
SATURATED CONDENSING TMP
SATURATED SUCTION TEMP
COMPR RETURN GAS TEMP
SUCTION SUPERHEAT TEMP
See Note
See Note
See Note
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
Table 6 — Pressure Mode and Sub-Mode Directory
KEYPAD
ENTRY
ITEM
SUB-MODE
PRC.A
ITEM
DISPLAY
COMMENT
EXPANSION
PRESSURES CIRCUIT A
ENTER
DP.A
SP.A
XXX.X PSIG
XXX.X PSIG
DISCHARGE PRESSURE
SUCTION PRESSURE
PRC.B
PRESSURES CIRCUIT B
DISCHARGE PRESSURE
See Note
See Note
ENTER
DP.B
SP.B
XXX.X PSIG
XXX.X PSIG
SUCTION PRESSURE
See Note
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
Table 7 — Set Points Mode and Sub-Mode Directory
KEYPAD
ENTRY
ITEM
SUB-MODE
COOL
ITEM
DISPLAY
COMMENT
EXPANSION
COOLING SETPOINTS
ENTER
CSP.1
CSP.2
CSP.3
XXX.X F
XXX.X F
XXX.X F
COOLING SETPOINT 1
Default: 44 F
Default: 44 F
Default: 32 F
COOLING SETPOINT 2
ICE SETPOINT
HEAD
HEAD PRESSURE SETPOINTS
HEAD SETPOINT
ENTER
H.DP
F. ON
XXX.X F
XXX.X F
XXX.X F
XXX.X F
XXX.X F
Default: 95 F
Default: 95 F
Default: 72 F
Default: 23 F
Default: 15 F
FAN ON SETPOINT
FAN OFF SETPOINT
F.OFF
B.OFF
F.DLT
BASE FAN OFF DELTA TEMP
FAN STAGE DELTA
FRZ
BRINE FREEZE SETPOINT
BRINE FREEZE POINT
ENTER
BR.FZ
XXX.X F
Default: 34 F
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 8 — Inputs Mode and Sub-Mode Directory
KEYPAD
ENTRY
ITEM
SUB-MODE
GEN.I
ITEM
DISPLAY
COMMENT
EXPANSION
GENERAL INPUTS
ENTER
STST
FLOW
PM.F.1
PM.F.2
HT.RQ
DLS1
STRT/STOP
ON/OFF
START/STOP SWITCH
COOLER FLOW SWITCH
COOLER PUMP 1 INTERLOCK
COOLER PUMP 2 INTERLOCK
HEAT REQUEST
OPEN/CLSE
OPEN/CLSE
ON/OFF
ON/OFF
DEMAND LIMIT SWITCH 1
DEMAND LIMIT SWITCH 2
ICE DONE
DLS2
ON/OFF
ICED
ON/OFF
DUAL
ON/OFF
DUAL SETPOINT SWITCH
CRCT
CIRCUITS INPUTS
ENTER
FKA1
FKA2
FKA3
FKA4
FKB1
FKB2
FKB3
FKB4
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
COMPRESSOR A1 FEEDBACK
COMPRESSOR A2 FEEDBACK
COMPRESSOR A3 FEEDBACK
COMPRESSOR A4 FEEDBACK
COMPRESSOR B1 FEEDBACK
COMPRESSOR B2 FEEDBACK
COMPRESSOR B3 FEEDBACK
COMPRESSOR B4 FEEDBACK
See Note
See Note
See Note
See Note
4-20
4-20 MA INPUTS
ENTER
DMND
RSET
CSP
XX.X MA
XX.X MA
XX.X MA
4-20 MA DEMAND SIGNAL
4-20 MA RESET SIGNAL
4-20 MA COOLING SETPOINT
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
Table 9 — Outputs Mode and Sub-Mode Directory
KEYPAD
ENTRY
ITEM
SUB-MODE
GEN.O
ITEM
DISPLAY
COMMENT
EXPANSION
GENERAL OUTPUTS
ENTER
FAN1
FAN2
FAN3
FAN4
FAN5
FAN6
V.HPA
V.HPB
C.WP1
C.WP2
CLHT
MLV.R
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
FAN 1 RELAY
FAN 2 RELAY
FAN 3 RELAY
FAN 4 RELAY
FAN 5 RELAY
FAN 6 RELAY
FAN SPEED CIRCUIT A
FAN SPEED CIRCUIT B
COOLER PUMP RELAY 1
COOLER PUMP RELAY 2
COOLER/PUMP HEATER
MINIMUM LOAD VALVE RELAY
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 9 — Outputs Mode and Sub-Mode Directory (cont)
KEYPAD
ENTRY
ITEM
SUB-MODE
A.EXV
ITEM
DISPLAY
COMMENT
EXPANSION
OUTPUTS CIRCUIT A EXV
ENTER
EXV.A
APPR
AP.SP
X.SH.R
S.SH.R
SH_R
0 to 100%
ON/OFF
EXV % OPEN
CIRCUIT A APPROACH
APPROACH SETPOINT
SH RESET AT MAX UNL-DIG
DIGLOAD TO START SH RST
AMOUNT OF SH RESET
EXVA OVERRIDE
OVR.A
SPH.A
ASH.S
AMP.S
PLM.A
SPR.1
SUCTION SUPERHEAT TEMP
ACTIVE SUPERHEAT SETPT
ACTIVE MOP SETPT
CIR A EXV POSITION LIMIT
SPARE 1 TEMPERATURE
B.EXV
OUTPUTS CIRCUIT B EXV
EXV % OPEN
ENTER
EXV.B
APPR
AP.SP
OVR.B
SPH.B
ASH.S
AMP.S
PLM.B
SPR.2
0 to 100%
ON/OFF
CIRCUIT B APPROACH
APPROACH SETPOINT
EXVB OVERRIDE
SUCTION SUPERHEAT TEMP
ACTIVE SUPERHEAT SETPT
ACTIVE MOP SETPT
CIR B EXV POSITION LIMIT
SPARE 2 TEMPERATURE
CIR.A
OUTPUTS CIRCUIT A
ENTER
CC.A1
DPE.R
CC.A2
CC.A3
CC.A4
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
COMPRESSOR A1 RELAY
COMP A1 LOAD PERCENT
COMPRESSOR A2 RELAY
COMPRESSOR A3 RELAY
COMPRESSOR A4 RELAY
CIR.B
OUTPUTS CIRCUIT B (See Note)
ENTER
CC.B1
CC.B2
CC.B3
CC.B4
ON/OFF
ON/OFF
ON/OFF
ON/OFF
COMPRESSOR B1 RELAY
COMPRESSOR B2 RELAY
COMPRESSOR B3 RELAY
COMPRESSOR B4 RELAY
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
Table 10 — Configuration Mode and Sub-Mode Directory
KEYPAD
ENTRY
ITEM
SUB-MODE
DISP
ITEM
DISPLAY
COMMENT
EXPANSION
DISPLAY CONFIGURATION
ENTER
TEST
ON/OFF
TEST DISPLAY LEDS
METR
LANG
ON/OFF
X
METRIC DISPLAY
Off = English; On = Metric
Default: 0
0 = English
LANGUAGE SELECTION
1 = Espanol
2 = Francais
3 = Portuguese
PAS.E
PASS
ENBL/DSBL
xxxx
PASSWORD ENABLE
SERVICE PASSWORD
Default: Enable
Default: 1111
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10 — Configuration Mode and Sub-Mode Directory
KEYPAD
ENTRY
ITEM
SUB-MODE
UNIT
ITEM
DISPLAY
COMMENT
EXPANSION
ENTER
UNIT CONFIGURATION
SIZE
SZA.1
SZA.2
SZA.3
SZA.4
SZB.1
SZB.2
SZB.3
SZB.4
SH.SP
FAN.S
XX
XX
UNIT SIZE
COMPRESSOR A1 SIZE
Unit Dependent
Unit Dependent
Unit Dependent
Unit Dependent
Unit Dependent
Unit Dependent
Unit Dependent
Unit Dependent
Default: 9 F
XX
COMPRESSOR A2 SIZE
COMPRESSOR A3 SIZE
COMPRESSOR A4 SIZE
COMPRESSOR B1 SIZE
COMPRESSOR B2 SIZE
COMPRESSOR B3 SIZE
COMPRESSOR B4 SIZE
SUPERHEAT SETPOINT
NUMBER OF FANS
XX
XX
XX
XX
XX
XX
XX.X F
1 = One Fan
2 = Two Fans
3 = Three Fans
4 = Four Fans
Default: Yes
EXV
YES/NO
YES/NO
EXV MODULE INSTALLED?
COMPRESSOR A1 DIGITAL?
Default: No
Yes = A1 Compressor is Digital
Scroll
A1.TY
Default: 7
Max 12 010,015
Max 10 018-060
MAX.T
0 to 12
MAXIMUM A1 UNLOAD TIME
UNIT OPTIONS 1 HARDWARE
COOLER FLUID
OPT1
Default: Water
1 = Water
2 = Medium Temperature
Brine
ENTER
FLUD
X
MLV.S
D.G.EN
CSB.E
CPC
YES/NO
ENBL/DSBL
ENBL/DSBL
ON/OFF
MINIMUM LOAD VALVE SELECT
DISCHARGE GAS TEMP ENABLE
CSB BOARDS ENABLE
Default: No
Default: Off
Default: No
COOLER PUMP CONTROL
COOLER PUMP 1 ENABLE
COOLER PUMP 2 ENABLE
PM1E
PM2E
YES/NO
YES/NO
PM.P.S
PM.SL
YES/NO
X
COOLER PMP PERIODIC STRT
COOLER PUMP SELECT
Default: Automatic
0 = Automatic
1 = Pump 1 Starts first
2 = Pump 2 Starts first
0 to 10 minutes, Default: 1
min.
PM.DY
XX MIN
COOLER PUMP SHUTDOWN DLY
PM.DT
ROT.P
EMM
XXXX HRS
YES/NO
PUMP CHANGEOVER HOURS
ROTATE COOLER PUMPS NOW
EMM MODULE INSTALLED
Default: 500 hours
User Entry
YES/NO
0 = RTPF
1 = MCHX Default MCHX
CND.T
0,1
COND HX
MOPS
APPR
XX
XX
EXV MOP SET POINT
Range: 40 - 80 Default: 50
Range: 5 - 40 Default: 9.0
CONFIG APPROACH SETPOINT
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10 — Configuration Mode and Sub-Mode Directory (cont)
KEYPAD
ITEM
SUB-MODE
OPT2
ITEM
DISPLAY
COMMENT
ENTRY
EXPANSION
UNIT OPTIONS 2 CONTROLS
CONTROL METHOD
CTRL
X
Default: Switch
ENTER
0 = Enable/Off/Remote Switch
2 = Occupancy
3 = CCN Control
LOAD
LLCS
X
X
LOADING SEQUENCE SELECT
LEAD/LAG CIRCUIT SELECT
Default: Equal
1 = Equal
2 = Staged
Default: Automatic
1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
Default: 60
LCWT
DELY
XX.X F
HIGH LCW ALERT LIMIT
MINUTES OFF TIME
Range: 2 to 60 F
Default: 0 Minutes
Range: 0 to 15 Minutes
XX
ENBL/DSBL
X
ICE.M
LS.MD
ICE MODE ENABLE
Default: Disable
LOW SOUND MODE SELECT
Default: 0
0 = Mode Disable
1 = Fan Noise Only
2 = Fan/Compressor Noise
LS.ST
LS.ND
LS.LT
00:00
00:00
LOW SOUND START TIME
LOW SOUND END TIME
Default: 00:00
Default: 00:00
Default: 100%
Range: 0 to 100%
XXX %
LOW SOUND CAPACITY LIMIT
CCN
CCN NETWORK CONFIGURATION
CCN ADDRESS
Default: 1
Range: 1 to 239
CCNA
XXX
ENTER
Default: 0
CCNB
BAUD
XXX
X
CCN BUS NUMBER
CCN BAUD RATE
Range: 0 to 239
Default: 9600
1 = 2400
2 = 4800
3 = 9600
4 = 19,200
5 = 38,400
HP.A
HP.B
HEAD PRESSURE CMP DELTA
SCT DELTA FOR COMP A1
ENTER
A1.DT
A2.DT
XX
XX
Range: 0 - 50 Default: 12
Range: 0 - 50 Default: 12
SCT DELTA FOR COMP A2
HEAD PRESSURE CMP DELTA
SCT DELTA FOR COMP B1
ENTER
B1.DT
B2.DT
XX
XX
Range: 0 - 50 Default: 12
Range: 0 - 50 Default: 12
SCT DELTA FOR COMP B2
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10 — Configuration Mode and Sub-Mode Directory (cont)
KEYPAD
ENTRY
ITEM
SUB-MODE
EXV.A
ITEM
DISPLAY
COMMENT
EXPANSION
CIR A EXV CONFIGURATION
ENTER
STR.A
MIN.A
RNG.A
SPD.A
POF.A
MIN.A
MAX.A
OVR.A
TYP.A
H.SCT
X.PCT
X.PER
A.PCT
M.PCT
S.PCT
DELY
XXX
XXX
EXV CIRC.A START POS
Range: 0 - 100 Default: 30
Range: 0 - 100 Default: 8
Range: 0 - 65535 Default: *
Range: 0 - 65535 Default: 200
Range: 0 - 100 Default: 0
Range: 0 - 65535 Default: 0
Range: 0 - 65535 Default: *
Range: 0 - 65535 Default: 167
EXV CIRC.A MIN POSITION
EXVA STEPS IN RANGE
EXVA STEPS PER SECOND
EXVA FAIL POSITION IN %
EXVA MINIMUM STEPS
XXXXX
XXXXX
XXX
XXXXX
XXXXX
XXX
EXVA MAXIMUM STEPS
EXVA OVERRUN STEPS
EXVA STEPPER TYPE
0 = UNIPOLAR
1 = BIPOLAR Default: 1
0,1
XXX
HIGH SCT THRESHOLD
OPEN EXV X% ON 2ND COMP
MOVE EXV X% ON DISCRSOL
PRE-OPEN EXV - FAN ADDING
PRE-CLOSE EXV - FAN SUB
PRE-CLOSE EXV - LAG SHUT
LAG START DELAY
Range: 50 - 140 Default: 115
Range: 0 - 30 Default: 10
Range: 0 - 30 Default: 5
Range: 0 - 100 Default: 10
Range: 0 - 100 Default: 10
Range: 0 - 100 Default: 10
Range: 0 - 100 Default: 10
XX
XX
XXX
XXX
XXX
XXX
EXV.B
CIR B EXV CONFIGURATION
EXV CIRC.B START POS
ENTER
STR.B
MIN.B
RNG.B
SPD.B
POF.B
MIN.B
MAX.B
OVR.B
TYP.B
XXX
XXX
Range: 0 - 100 Default: 50
Range: 0 - 100 Default: 8
Range: 0 - 65535 Default: *
Range: 0 - 65535 Default: 200
Range: 0 - 100 Default: 0
Range: 0 - 65535 Default: 0
Range: 0 - 65535 Default: *
Range: 0 - 65535 Default: 167
EXV CIRC.B MIN POSITION
EXVB STEPS IN RANGE
EXVB STEPS PER SECOND
EXVB FAIL POSITION IN %
EXVB MINIMUM STEPS
EXVB MAXIMUM STEPS
EXVB OVERRUN STEPS
EXVB STEPPER TYPE
XXXXX
XXXXX
XXX
XXXXX
XXXXX
XXX
0 = UNIPOLAR
1 = BIPOLAR Default: 1
0,1
MM
MOTORMASTER CONFIGURATION
MOTORMASTER SELECT
ENTER
MMR.S
P.GAN
I.GAN
D.GAN
MIN.S
YES/NO
XX
HEAD PRESSURE P GAIN
HEAD PRESSURE I GAIN
HEAD PRESSURE D GAIN
MINIMUM FAN SPEED
Range: -20 - 20 Default: 1.0
Range: -20 - 20 Default: 0.1
Range: -20 - 20 Default: 0.0
Range: 0 - 100 Default: 5.0
XX
XX
XXX
* Sizes 010-020 and 035-045, default is 1596. Sizes 025,030, and 050-060, default is 2500.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10 — Configuration Mode and Sub-Mode Directory (cont)
KEYPAD
ENTRY
ITEM
SUB-MODE
RSET
ITEM
DISPLAY
COMMENT
EXPANSION
RESET COOL TEMP
COOLING RESET TYPE
CRST
X
Default: No Reset
0 = No Reset
ENTER
1 = 4 to 20 mA Input
2 = Outdoor Air Temperature
3 = Return Fluid
4 = Space Temperature
Default: 0.0F
MA.DG
RM.NO
RM.F
XX.X F
XXX.X F
XXX.X F
XX.X F
4-20 - DEGREES RESET
REMOTE - NO RESET TEMP
REMOTE - FULL RESET TEMP
REMOTE - DEGREES RESET
RETURN - NO RESET TEMP
RETURN - FULL RESET TEMP
Range: –30 to 30F
Default: 125F (51.7C)
Range: 0° to 125F
Default: 0.0F (-17.8C)
Range: 0 to 125F
Default: 0.0F
Range: –30 to 30F
RM.DG
RT.NO
RT.F
Default: 10.0F (5.6C)
Range: 0 to 125F COOLER T
XXX.X F
XXX.X F
Default: 0.0F (0.0C)
Range: 0 to 125F COOLER T
Default: 0.0F
RT.DG
DMDC
XX.X F
RETURN - DEGREES RESET
DEMAND LIMIT SELECT
Range: –30 to 30F (–34.4 to -1.1 C)
X
Default: None
0 = None
1 = Switch
2 = 4 to 20 mA Input
3 = CCN Loadshed
Default: 100%
DM20
SHNM
SHDL
SHTM
DLS1
DLS2
LLEN
MSSL
SLVA
XXX %
XXX
DEMAND LIMIT AT 20 MA
LOADSHED GROUP NUMBER
LOADSHED DEMAND DELTA
MAXIMUM LOADSHED TIME
DEMAND LIMIT SWITCH 1
DEMAND LIMIT SWITCH 2
LEAD/LAG CHILLER ENABLE
MASTER/SLAVE SELECT
SLAVE ADDRESS
Range: 0 to 100%
Default: 0
Range: 0 to 99
Default: 0%
Range: 0 to 60%
XXX %
XXX
Default: 60 minutes
Range: 0 to 120 minutes
Default: 80%
Range: 0 to 100%
XXX %
XXX %
ENBL/DSBL
SLVE/MAST
XXX
Default: 50%
Range: 0 to 100%
Default: Disable
Default: Master
Default: 0
Range: 0 to 239
ENTER
Default: Master Leads
0 = Master Leads
1 = Slave Leads
2 = Automatic
LLBL
X
LEAD/LAG BALANCE SELECT
Default: 168 hours
LLBD
LLDY
PARA
XXX
XXX
YES
LEAD/LAG BALANCE DELTA
LAG START DELAY
Range: 40 to 400 hours
Default: 5 minutes
Range: 0 to 30 minutes
PARALLEL CONFIGURATION
Default: YES (CANNOT BE CHANGED)
SLCT
SETPOINT AND RAMP LOAD
COOLING SETPOINT SELECT
CLSP
X
Default: Single
0 = Single
1 = Dual Switch
2 = Dual CCN Occupied
3 = 4 to 20 mA Input (requires
EMM)
ENTER
RL.S
CRMP
SCHD
Z.GN
ENBL/DSBL
RAMP LOAD SELECT
COOLING RAMP LOADING
SCHEDULE NUMBER
Default: Enable
Default: 1.0
Range: 0.2 to 2.0
X.X
XX
Default: 1
Range: 1 to 99
Default: 1.0
Range: 1.0 to 4.0
X.X
DEADBAND MULTIPLIER
SERV
SERVICE CONFIGURATION
ENABLE COMPRESSOR A1
ENTER
EN.A1
EN.A2
EN.B1
EN.B2
ENBL/DSBL
ENBL/DSBL
ENBL/DSBL
ENBL/DSBL
Unit dependent
Unit dependent
Unit dependent
Unit dependent
ENABLE COMPRESSOR A2
ENABLE COMPRESSOR B1
ENABLE COMPRESSOR B2
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10 — Configuration Mode and Sub-Mode Directory (cont)
KEYPAD
ENTRY
ITEM
SUB-MODE
BCST
ITEM
DISPLAY
COMMENT
EXPANSION
BROADCAST CONFIGURATION
ENTER
T.D.BC
OAT.B
ON/OFF
ON/OFF
ON/OFF
ON/OFF
CCN TIME/DATE BROADCAST
CCN OAT BROADCAST
G.S.BC
BC.AK
GLOBAL SCHEDULE BROADCAST
CCN BROADCAST ACK’ER
Table 11 — Time Clock Mode and Sub-Mode Directory
KEYPAD
ENTRY
ITEM
SUB-MODE
TIME
ITEM
DISPLAY
SUB-ITEM
DISPLAY
COMMENT
EXPANSION
TIME OF DAY
ENTER
HH.MM
XX.XX
HOUR AND MINUTE
Military (00:00 – 23:59)
DATE
MONTH,DATE,DAY AND YEAR
MONTH OF YEAR
ENTER
MNTH
DOM
DAY
XX
XX
1-12 (1 = January, 2 = February, etc)
Range: 01-31
DAY OF MONTH
DAY OF WEEK
X
1-7 (1 = Sunday, 2 = Monday, etc)
YEAR
XXXX
YEAR OF CENTURY
DST
DAYLIGHT SAVINGS TIME
MONTH
ENTER
STR.M
STR.W
STR.D
MIN.A
STP.M
STP.W
STP.D
MIN.S
XX
X
Default: 4, Range 1 – 12
Default: 1, Range 1 – 5
Default: 7, Range 1 – 7
Default: 60, Range 0 – 99
Default: 10, Range 1 – 12
Default: 5, Range 1 – 5
Default: 7, Range 1 – 7
Default: 60, Range 0 – 99
WEEK
DAY
X
XX
XX
XX
XX
XX
MINUTES TO ADD
MONTH
WEEK
DAY
MINUTES TO SUBTRACT
HOL.L
LOCAL HOLIDAY SCHEDULES
HOLIDAY START MONTH
HD.01 through HD.30
Range 0 – 12
ENTER
MON
DAY
LEN
XX
XX
START DAY
Range 0 – 31
XX
XX
DURATION (DAYS)
Range 0 - 99
SCH.N
SCH.L
SCHEDULE NUMBER
Default: 1, Range 1 – 99
LOCAL OCCUPANCY SCHEDULE
ENTER
ENTER
PER.1
OCCUPANCY PERIOD 1*
PERIOD OCCUPIED TIME
PERIOD UNOCCUPIED TIME
MONDAY IN PERIOD
OCC.1
UNC.1
MON.1
TUE.1
WED.1
THU.1
FRI.1
XX:XX
XX.XX
Military (00:00 – 23:59)
Military (00:00 – 23:59)
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
TUESDAY IN PERIOD
WEDNESDAY IN PERIOD
THURSDAY IN PERIOD
FRIDAY IN PERIOD
SAT.1
SATURDAY IN PERIOD
SUNDAY IN PERIOD
SUN.1
HOL.1
HOLIDAY IN PERIOD
* Repeats for Occupancy Periods 2 through 8.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 11 — Time Clock Mode and Sub-Mode Directory (cont)
KEYPAD
ENTRY
ITEM
SUB-MODE
OVR
ITEM
DISPLAY
SUB-ITEM
DISPLAY
COMMENT
EXPANSION
SCHEDULE OVERRIDE
ENTER
OVR.T
OVR.L
T.OVR
X
X
TIMED OVERRIDE HOURS
OVERRIDE TIME LIMIT
TIMED OVERRIDE
Default: 0, Range 0-4 hours
Default: 0, Range 0-4 hours
User Entry
YES/NO
Table 12 — Operating Mode and Sub-Mode Directory
KEYPAD
ENTRY
ITEM
SUB-MODE
MODE
ITEM
DISPLAY
COMMENT
EXPANSION
MODES CONTROLLING UNIT
ENTER
MD01
MD02
MD03
MD05
MD06
MD07
MD08
MD09
MD10
MD13
MD14
MD15
MD16
MD17
MD18
MD19
MD20
MD21
MD22
MD23
MD24
MD25
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
CSM CONTROLLING CHILLER
WSM CONTROLLING CHILLER
MASTER/SLAVE CONTROL
RAMP LOAD LIMITED
TIMED OVERRIDE IN EFFECT
LOW COOLER SUCTION TEMPA
LOW COOLER SUCTION TEMPB
SLOW CHANGE OVERRIDE
MINIMUM OFF TIME ACTIVE
DUAL SETPOINT
TEMPERATURE RESET
DEMAND/SOUND LIMITED
COOLER FREEZE PROTECTION
LOW TEMPERATURE COOLING
HIGH TEMPERATURE COOLING
MAKING ICE
STORING ICE
HIGH SCT CIRCUIT A
HIGH SCT CIRCUIT B
MINIMUM COMP ON TIME
PUMP OFF DELAY TIME
LOW SOUND MODE
LEGEND
CSM
SCT
WSM
—
—
—
Chillervisor System Manager
Saturated Condensing Temperature
Water System Manager
Table 13 — Alarms Mode and Sub-Mode Directory
KEYPAD
ENTRY
ITEM
SUB-MODE
CRNT
ITEM
COMMENT
EXPANSION
Alarms are shown as AXXX.
Alerts are shown as TXXX.
ENTER
ENTER
ENTER
AXXX OR TXXX
YES/NO
CURRENTLY ACTIVE ALARMS
RESET ALL CURRENT ALARMS
ALARM HISTORY
RCRN
HIST
Alarms are shown as AXXX.
Alerts are shown as TXXX.
AXXX OR TXXX
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 14 — Operating Modes
MODE
NO.
ITEM EXPANSION
DESCRIPTION
01
02
03
CSM CONTROLLING CHILLER
WSM CONTROLLING CHILLER
MASTER/SLAVE CONTROL
RAMP LOAD LIMITED
Chillervisor System Manager (CSM) is controlling the chiller.
Water System Manager (WSM) is controlling the chiller.
Dual Chiller control is enabled.
Rampload(pull-down)limitingineffect.Inthismode,therateatwhichleavingfluidtemperature
isdroppedislimitedtoapredeterminedvaluetopreventcompressoroverloading.SeeCooling
Ramp Loading (ConfigurationSLCTCRMP). The pull-down limit can be modified, if
desired, to any rate from 0.2° F to 2° F (0.1° to 1° C)/minute.
05
06
TIMED OVERRIDE IN EFFECT
LOW COOLER SUCTION TEMPA
Timed override is in effect. This is a 1 to 4 hour temporary override of the programmed
schedule, forcing unit to Occupied mode. Override can be implemented with unit under
Local (Enable) or CCN (Carrier Comfort Network®) control. Override expires after each use.
Circuit A cooler Freeze Protection mode. At least one compressor must be on, and the Sat-
urated Suction Temperature is not increasing greater than 1.1° F (0.6° C) in 10 seconds. If
the saturated suction temperature is less than the Brine Freeze Point (Set PointsFRZ
BR.FZ) minus 6° F (3.4° C) and less than the leaving fluid temperature minus 14° F
(7.8° C) for 2 minutes, a stage of capacity will be removed from the circuit. Or, If the satu-
rated suction temperature is less than the Brine Freeze Point minus 14° F (7.8° C), for
90 seconds, a stage of capacity will be removed from the circuit. The control will continue to
decrease capacity as long as either condition exists.
07
08
LOW COOLER SUCTION TEMPB
SLOW CHANGE OVERRIDE
Circuit B cooler Freeze Protection mode. At least one compressor must be on, and the Sat-
urated Suction Temperature is not increasing greater than 1.1° F (0.6° C) in 10 seconds. If
the saturated suction temperature is less than the Brine Freeze Point (Set PointsFRZ
BR.FZ) minus 6° F (3.4° C) and less than the leaving fluid temperature minus 14° F
(7.8° C) for 2 minutes, a stage of capacity will be removed from the circuit. Or, If the satu-
rated suction temperature is less than the Brine Freeze Point minus 14° F (7.8° C), for
90 seconds, a stage of capacity will be removed from the circuit. The control will continue to
decrease capacity as long as either condition exists.
Slow change override is in effect. The leaving fluid temperature is close to and moving
towards the control point.
09
10
MINIMUM OFF TIME ACTIVE
DUAL SETPOINT
Chiller is being held off by Minutes Off Time (ConfigurationOPT2DELY).
Dual Set Point mode is in effect. Chiller controls to Cooling Set Point 1 (Set PointsCOOL
CSP.1) during occupied periods and Cooling Set Point 2 (Set PointsCOOLCSP.2)
during unoccupied periods.
13
TEMPERATURE RESET
Temperature reset is in effect. In this mode, chiller is using temperature reset to adjust leav-
ing fluid set point upward and is currently controlling to the modified set point. The set point
can be modified based on return fluid, outdoor-air-temperature, space temperature, or 4 to
20 mA signal.
14
DEMAND/SOUND LIMITED
Demand limit is in effect. This indicates that the capacity of the chiller is being limited by
demand limit control option. Because of this limitation, the chiller may not be able to pro-
duce the desired leaving fluid temperature. Demand limit can be controlled by switch inputs
or a 4 to 20 mA signal.
15
COOLER FREEZE PROTECTION
LOW TEMPERATURE COOLING
HIGH TEMPERATURE COOLING
Cooler fluid temperatures are approaching the Freeze point (see Alarms and Alerts section
for definition). The chiller will be shut down when either fluid temperature falls below the
Freeze point.
16
17
18
Chiller is in Cooling mode and the rate of change of the leaving fluid is negative and
decreasing faster than -0.5° F per minute. Error between leaving fluid and control point
exceeds fixed amount. Control will automatically unload the chiller if necessary.
Chiller is in Cooling mode and the rate of change of the leaving fluid is positive and increasing.
Error between leaving fluid and control point exceeds fixed amount. Control will automatically
load the chiller if necessary to better match the increasing load.
MAKING ICE
STORING ICE
Chiller is in an unoccupied mode and is using Cooling Set Point 3 (Set PointsCOOL
19
20
CSP.3) to make ice. The ice done input to the Energy Management Module (EMM) is open.
ChillerisinanunoccupiedmodeandiscontrollingtoCoolingSetPoint2(SetPointsCOOL
CSP.2). The ice done input to the Energy Management Module (EMM) is closed.
HIGH SCT CIRCUIT A
Chiller is in a Cooling mode and the Saturated Condensing Temperature (SCT) is greater than
the calculated maximum limit. No additional stages of capacity will be added. Chiller capacity
may be reduced if SCT continues to rise to avoid high-pressure switch trips by reducing con-
densing temperature.
21
HIGH SCT CIRCUIT B
Chiller is in a Cooling mode and the Saturated Condensing Temperature (SCT) is greater than
the calculated maximum limit. No additional stages of capacity will be added. Chiller capacity
may be reduced if SCT continues to rise to avoid high-pressure switch trips by reducing con-
densing temperature.
22
23
MINIMUM COMP ON TIME
PUMP OFF DELAY TIME
LOW SOUND MODE
Cooling load may be satisfied, however control continues to operate compressor to ensure
proper oil return. May be an indication of oversized application, low fluid flow rate or low loop
volume.
Cooling load is satisfied, however cooler pump continues to run for the number of minutes set
by the configuration variable Cooler Pump Shutdown Delay (ConfigurationOPT1
PM.DY).
Chiller operates at higher condensing temperature and/or reduced capacity to minimize
overall unit noise during evening/night hours (ConfigurationOPT2LS.MD).
24
25
18
Download from Www.Somanuals.com. All Manuals Search And Download.
set to ‘On’ for these boards. The auxiliary board (AUX) has an
8-position DIP switch. Switches 2, 5, and 7 are set to ‘On.’
CONTROLS
General — The 30RAP air-cooled scroll chillers contain
the ComfortLink™ electronic control system that controls and
monitors all operations of the chiller.
The control system is composed of several components as
listed in the sections below. See Fig. 3-5 for typical control box
drawings. See Fig. 6 and 7 for control schematics.
Control Module Communication
RED LED — Proper operation of the control boards can be
visually checked by looking at the red status LEDs
(light-emitting diodes). When operating correctly, the red status
LEDs should be blinking in unison at a rate of once every
2 seconds. If the red LEDs are not blinking in unison, verify
that correct power is being supplied to all modules. Be sure that
the main base board (MBB) is supplied with the current soft-
ware. If necessary, reload current software. If the problem still
persists, replace the MBB. A red LED that is lit continuously or
blinking at a rate of once per second or faster indicates that the
board should be replaced.
GREEN LED — The MBB has one green LED. The Local
Equipment Network (LEN) LED should always be blinking
whenever power is on. All other boards have a LEN LED
which should be blinking whenever power is on. Check LEN
connections for potential communication errors at the board J3
and/or J4 connectors. Communication between modules is
accomplished by a 3-wire sensor bus. These 3 wires run in
parallel from module to module. The J4 connector on the MBB
provides both power and communication directly to the
marquee display only.
Main Base Board (MBB) — See Fig. 8. The MBB is
the heart of the ComfortLink control system. It contains the
major portion of operating software and controls the operation
of the machine. The MBB continuously monitors input/output
channel information received from its inputs and from all other
modules. The MBB receives inputs from the discharge and
suction pressure transducers and thermistors. See Table 15. The
MBB also receives the feedback inputs from each compressor
current sensor board and other status switches. See Table 16.
The MBB also controls several outputs. Relay outputs con-
trolled by the MBB are shown in Table 17. Information is
transmitted between modules via a 3-wire communication bus
or LEN (Local Equipment Network). The CCN (Carrier Com-
fort Network) bus is also supported. Connections to both LEN
and CCN buses are made at the LVT (low voltage terminal).
See Fig. 8.
Energy Management Module (EMM) — The EMM
module is available as a factory-installed option or as a field-
installed accessory. The EMM module receives 4 to 20 mA
inputs for the leaving fluid temperature reset, cooling set point
and demand limit functions. The EMM module also receives
the switch inputs for the field-installed 2-stage demand limit
and ice done functions. The EMM module communicates the
status of all inputs with the MBB, and the MBB adjusts the
control point, capacity limit, and other functions according to
the inputs received.
YELLOW LED — The MBB has one yellow LED. The
Carrier Comfort Network (CCN) LED will blink during times
of network communication.
Carrier Comfort Network® (CCN) Interface —
The 30RAP chiller units can be connected to the CCN if
desired. The communication bus wiring is a shielded,
3-conductor cable with drain wire and is supplied and installed
in the field. See Table 18. The system elements are connected
to the communication bus in a daisy chain arrangement. The
positive pin of each system element communication connector
must be wired to the positive pins of the system elements on
either side of it. This is also required for the negative and
signal ground pins of each system element. Wiring connections
for CCN should be made at LVT. Consult the CCN Contrac-
tor’s Manual for further information.
NOTE: Conductors and drain wire must be 20 AWG (Ameri-
can Wire Gage) minimum stranded, tinned copper. Individual
conductors must be insulated with PVC, PVC/nylon, vinyl,
Teflon, or polyethylene. An aluminum/polyester 100% foil
shield and an outer jacket of PVC, PVC/nylon, chrome vinyl,
or Teflon with a minimum operating temperature range of
–20 C to 60 C is required. Wire manufactured by Alpha (2413
or 5463), American (A22503), Belden (8772), or Columbia
(02525) meets the above mentioned requirements.
It is important when connecting to a CCN communication
bus that a color coding scheme be used for the entire network
to simplify the installation. It is recommended that red be used
for the signal positive, black for the signal negative, and white
for the signal ground. Use a similar scheme for cables contain-
ing different colored wires.
At each system element, the shields of its communication
bus cables must be tied together. If the communication bus is
entirely within one building, the resulting continuous shield
must be connected to a ground at one point only. If the commu-
nication bus cable exits from one building and enters another,
the shields must be connected to grounds at the lightning
suppressor in each building where the cable enters or exits the
building (one point per building only). To connect the unit to
the network:
Current Sensor Board (CSB) — The CSB is used to
monitor the status of the compressors by measuring current and
providing an analog input to the main base board (MBB) or
compressor expansion module (CXB).
AUX Board (AUX) — The AUX is used with the digital
scroll option and the low ambient head pressure option. It pro-
vides additional inputs and outputs for digital scroll control
along with analog outputs to control head pressure control fan
speeds.
Expansion Valve Board (EXV) — The EXV board
communicates with the MBB and directly controls the expan-
sion valves to maintain the correct compressor superheat.
Enable/Off/Remote Contact Switch — The Enable/
Off/Remote Contact switch is a 3-position switch used to
control the chiller. When switched to the Enable position the
chiller is under its own control. Move the switch to the Off
position to shut the chiller down. Move the switch to the
Remote Contact position and a field-installed dry contact can
be used to start the chiller. The contacts must be capable of
handling a 24 vac, 50-mA load. In the Enable and Remote
Contact (dry contacts closed) positions, the chiller is allowed to
operate and respond to the scheduling configuration, CCN
configuration and set point data. See Fig. 9.
Emergency On/Off Switch — The Emergency On/Off
switch should only be used when it is required to shut the
chiller off immediately. Power to the MBB, EMM, and
marquee display is interrupted when this switch is off and all
outputs from these modules will be turned off.
1. Turn off power to the control box.
Board Addresses — The main base board (MBB) has a
3-position instance jumper that must be set to ‘1.’ The elec-
tronic expansion valve board (EXV) and energy management
board (EMM) have 4-position DIP switches. All switches are
2. Cut the CCN wire and strip the ends of the red (+), white
(ground), and black (–) conductors. (Substitute appropri-
ate colors for different colored cables.)
19
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Connect the red wire to (+) terminal on LVT of the plug,
the white wire to COM terminal, and the black wire to the
(–) terminal.
4. The RJ14 CCN connector on LVT can also be used, but is
only intended for temporary connection (for example, a
laptop computer running Service Tool).
Table 18 — CCN Communication Bus Wiring
PART NO.
MANUFACTURER
Regular Wiring
1895
Plenum Wiring
Alpha
American
Belden
Columbia
Manhattan
Quabik
—
A48301
884421
—
M64430
—
A21451
8205
D6451
M13402
6130
IMPORTANT: A shorted CCN bus cable will prevent some
routines from running and may prevent the unit from start-
ing. If abnormal conditions occur, unplug the connector. If
conditions return to normal, check the CCN connector and
cable. Run new cable if necessary. A short in one section of
the bus can cause problems with all system elements on the
bus.
Sensors — The electronic control uses 4 to 7 thermistors to
sense temperatures for controlling chiller operation. See
Table 15. These sensors are outlined below. Thermistors RG-
TA, RGTB, EWT, LWT, and OAT are identical in temperature
versus resistance and voltage drop performance. The dual chill-
er thermistor is 5 kat 77 F (25 C)thermistor. Space tempera-
ture thermistor is a 10 kat 77 F (25 C). The DTT thermistor
is an 86 kat 77 F (25 C)thermistor. See Thermistors section
for temperature-resistance-voltage drop characteristics.
COOLER LEAVING FLUID SENSOR — The thermistor is
installed in a well in the factory-installed leaving fluid piping
coming from the bottom of the brazed-plate heat exchanger.
COOLER ENTERING FLUID SENSOR —The thermistor is
installed in a well in the factory-installed entering fluid piping
coming from the top of the brazed-plate heat exchanger.
COMPRESSOR RETURN GAS TEMPERATURE SEN-
SOR — These thermistors are installed in a well located in the
suction line of each circuit.
OUTDOOR-AIR TEMPERATURE SENSOR (OAT) —
This sensor is factory installed on a bracket which is inserted
through the base pan of the unit.
Table 15 — Thermistor Designations
PIN
THERMISTOR CONNECTION
POINT
THERMISTOR INPUT
LWT
EWT
J8-13,14 (MBB) Cooler Leaving Fluid
J8-11,12 (MBB) Cooler Entering Fluid
J8-1,2 (MBB)
J8-3,4 (MBB)
J8-7,8 (MBB)
Circuit A Return Gas
Temperature
Circuit B (035-060 only)
Return Gas Temperature
Outdoor-Air Temperature
Sensor
RGTA
RGTB
OAT
J8-5,6 (MBB)
TB5-5,6
Accessory Remote Space
Temperature Sensor or
Dual LWT Sensor
Discharge Temperature
Thermistor
SPT
DTT
J6-1,2 (AUX)
LEGEND
DISCHARGE
TEMPERATURE
THERMISTOR
LWT — Leaving Water Temperature
MBB — Main Base Board
(DTT) — This sensor is only used on units with a digital
compressor. The sensor is mounted on the discharge line close
to the discharge of the digital compressor. It attaches to the dis-
charge line using a spring clip and protects the system from
high discharge gas temperature when the digital compressor is
used. This sensor is a connected to the AUX board.
Table 16 — Status Inputs
STATUS SWITCH
Chilled Water Pump 1
Chilled Water Pump 2
Remote On/Off
Cooler Flow Switch
PIN CONNECTION POINT
J7-1,2
J7-3,4
LVT-13,14
J7-9,10
J9-11,12
J9-5,6
REMOTE SPACE TEMPERATURE SENSOR OR DUAL
LEAVING WATER TEMPERATURE SENSOR — One of
two inputs can be connected to the LVT. See appropriate sen-
sor below.
Remote Space Temperature Sensor — Sensor (part no.
33ZCT55SPT) is an accessory sensor that is remotely mounted
in the controlled space and used for space temperature reset.
The sensor should be installed as a wall-mounted thermostat
would be (in the conditioned space where it will not be sub-
jected to either a cooling or heating source or direct exposure
to sunlight, and 4 to 5 ft above the floor).
Space temperature sensor wires are to be connected to
terminals in the unit main control box. The space temperature
sensor includes a terminal block (SEN) and a RJ11 female
connector. The RJ11 connector is used access into the Carrier
Comfort Network® (CCN) at the sensor.
Compressor Fault Signal, A1
Compressor Fault Signal, A2
Compressor Fault Signal, B1
Compressor Fault Signal, B2
J9-8,9
J9-2,3
Table 17 — Output Relays
RELAY
NO.
DESCRIPTION
Energize Compressor A1 (010-030)
Energize Compressor A1 and Condenser Fan Contac-
tor 3 (055,060)
K1
K2
K3
K4
Energize Compressor A2 (all but 010, 015 60 Hz)
Energize Chilled Water Pump 1 Output
Energize Chilled Water Pump 2 Output
To connect the space temperature sensor (Fig. 10):
Energize Compressor B1 (035-050)
Energize Compressor B1 and Condenser Fan Contac-
tor 3 (055,060)
Energize Compressor B2 (035-060)
Alarm Relay
1. Using a 20 AWG twisted pair conductor cable rated for
the application, connect 1 wire of the twisted pair to one
SEN terminal and connect the other wire to the other
SEN terminal located under the cover of the space
temperature sensor.
2. Connect the other ends of the wires to terminals 5 and 6
on TB5 located in the unit control box.
K5
K6
K7
K8
K9
K10
K11
Cooler/Pump Heater
Energize Condenser Fan Contactor 1 (018-060)
Energize Condenser Fan Contactor 2 (018-060)
Minimum Load Valve
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Units on the CCN can be monitored from the space at the
sensor through the RJ11 connector, if desired. To wire the RJ11
connector into the CCN (Fig. 11):
3. Insert and secure the white (ground) wire to terminal 4 of
the space temperature sensor.
4. Insert and secure the black (–) wire to terminal 2 of the
space temperature sensor.
5. Connect the other end of the communication bus cable to
the remainder of the CCN communication bus.
Dual Leaving Water Temperature Sensor — For dual chiller
applications (parallel only are supported), connect the dual
chiller leaving fluid temperature sensor (refer to Configuring
and Operating Dual Chiller Control section on page 36) to the
space temperature input of the Master chiller. If space tempera-
ture is required for reset applications, connect the sensor to the
Slave chiller and configure the slave chiller to broadcast the
value to the Master chiller.
IMPORTANT: The cable selected for the RJ11 connector
wiring MUST be identical to the CCN communication bus
wire used for the entire network. Refer to Table 18 for
acceptable wiring.
1. Cut the CCN wire and strip ends of the red (+), white
(ground), and black (–) conductors. (If another wire color
scheme is used, strip ends of appropriate wires.)
2. Insert and secure the red (+) wire to terminal 5 of the
space temperature sensor terminal block.
LEGEND FOR FIG. 3-7
ALMR
AUX
BR
— Alarm Relay
— Auxilliary
— Boiler Relay
C
— Contactor, Compressor
— Circuit Breaker
CB
CCB
CH
— Compressor Circuit Breaker
— Crankcase Heater
CHC
COMP
CSB
CWFS
CWP
DGS
DPT
DTT
DUS
EMM
EXV
FB
— Cooler/Pump Heater Contactor
— Compressor
— Current Sensor Board
— Chilled Water Flow Switch
— Chilled Water Pump
— Digital Scroll Compressor
— Discharge Pressure Transducer
— Discharge Temperature Thermistor
— Digital Unloader Solenoid
— Energy Management
— Electronic Expansion Valve
— Fuse Block
FC
— Fan Contactor
FCB
FIOP
FR
— Fan Circuit Breaker
— factory Installed Option
— Fan Relay
GND
HPS
LON
LVT
— Ground
— High-Pressure Switch
— Local Operating Network
— Low Voltage Terminal Block
— Main Base Board
MBB
MLV
MM
MP
MS
— Minimum Load Valve
— Motormaster
— Motor Protector
— Manual Starter
NEC
OAT
OFM
RGT
SCCR
SPT
SW
— National Electrical Code
— Outdoor-Air Thermistor
— Outdoor Fan Motor
— Return Gas Thermistor
— Short Circuit Current Rating
— Suction Pressure Transducer
— Switch
TB
— Terminal Block
TNKR
TRAN
UPC
— Storage Tank Heater Relay
— Transformer
— Unitary Protocol Converter
Terminal Block
Terminal (Unmarked)
Terminal (Marked)
Splice
Factory Wiring
Field Wiring
Accessory or Option Wiring
To indicate common potential only; not to represent wiring.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
LOCATED OVER EMM AND EXV
FB-1
EMM
EXV
CHC
TRAN
CCB
AUX
CSB-A1
UPC
LON
DISCONNECT
OPTION/TB
TB4
TB1
MS- MS-
CWP1CWP2
FAN
1
CWP1 CWP2
C-A1
MM
MBB
A1
COMPRESSOR
CONTROL BOX
a30-4962
Fig. 3 — Typical Control Box for 30RAP010,015
FB-1
EXV
EMM
CHC
TRAN
CCB-2
CCB-1
FB-3
AUX
LON
CSB-A1
CSB-A2
TB1
TB4
UPC
DISCONNECT
OPTION/TB
MS- MS-
CWP1 CWP2
C-A1
FC2
C-A2
CWP1 CWP2
MBB
FC1/MM
Fig. 4 — Typical Control Box for 30RAP018-030
a30-4963
22
Download from Www.Somanuals.com. All Manuals Search And Download.
a30-4964
23
Download from Www.Somanuals.com. All Manuals Search And Download.
STANDARD
TERMINAL
BLOCK
OPTIONAL
DISCONNECT
CH-A1
BLU
BLK
380V,460V,575V
ONLY
CB1A
TB1A
CCB-1
CA1
CSB-A1
1
BLK
BLK
BLK
11
21
22
23
11
21
BLK
YEL
BLU
T1
T2
BLK
YEL
BLU
BLK
11
21
22
1
2
3
12
13
YEL
12
22
23
COMP A1
GRN/YEL
BLU
YEL
13
T3
YEL
YEL
YEL
YEL
12
13
2
3
CH-A2
BLK BLU
BLU BLK
BLU
BLK
CCB-2
BLU
BLU
BLU
CA2
CSB-A2
1
23
11
12
13
21
22
23
BLK
YEL
BLU
11
12
13
21
BLK
YEL
T1
BLK
YEL
BLU
2
3
COMP A2
GRN/YEL
22
23
T2
BLU
T3
EQUIP GND
208/230V ONLY
FU5
FU6
BLK
CHILLED WATER PUMP FIOP
CWP1
MS-CWP1
L1
RED
1
1
HF
BLK
YEL
BLU
T1
T2
T3
L1
L2
L3
T1
T2
T3
BLK
BLK
BLK
L1
L2
L3
CWP1
WATER
PUMP
H4
H3
H2
L2
L3
H1
~
TRAN3
WHT
GRN/YEL
SECONDARY
115V
MS-CWP2
L1
CWP2
X3
X1
FU4
BLK
BLK
BLK
BLK
YEL
BLU
T1
T2
T3
L1
L2
L3
T1
T2
T3
L1
L2
L3
GRN/YEL
XF
CWP2
WATER
PUMP
L2
L3
2
BLK
GFI-CO
GRN/YEL
2
FIOP/ACCESSORY
LINE
BRASS SCREW
FB3
FB1
SILVER SCREW
RESET
TEST
TERMINAL
CONNECTIONS
FOR PRIMARY SIDE
TERMINAL
CONNECTIONS FOR
SECONDARY SIDE
FC1
21
1
2
3
VOLTAGE
SERIES
100
11
12
13
21
22
23
11
12
13
21
11
BLK-1
BLK-2
BLK-3
BLK
YEL
BLU
BLK
YEL
BLU
BLK
575-3-60
H1-H2
H2-H4
H3-H4
H1-H4
XF-X2
XF-X2
XF-X2
XF-X2
22
23
OFM1
GRN/YEL
YEL
BLU
12
13
22
23
230-3-60
208-3-60
460-3-60
400,500
500
GRN-YEL
LOAD
600
FC2
HIGH SCCR
ONLY
1
2
3
11
12
13
21
22
23
BLK-1
BLK-2
BLK-3
BLK
YEL
BLU
OFM2
FUSE
NUMBER
TRAN
SIZE
REPLACE
WITH
GRN/YEL
UNIT VOLTAGE
208/230-3-60
380-3-60
FNQ-R-3.5
FNQ-R-2.5
FNQ-R-2
CHC
CHC
1
YEL
FU1
&
FU2
200VA
BLK
4
2
6
BLK
WHT
BLK
BLK
460-3-60
1
2
575-3-60
FNQ-R-1.5
BLK BLU
380-3-60,460-3-60,575-3-60
208/230-3-60
3
2
FU3 (24V)
200VA
500VA
500VA
NONE
FNM-10
COOLER/PUMP
COOLER/PUMP
HEATERS
(208/230,230V)
HEATERS
460-3-60,575-3-60
208/230-3-60,230-3-60
380-3-60,460-3-60,575-3-60
208/230-3-60
FNQ-R-2.5
FNQ-R-3.5
(380,460,575V)
FU5
&
FU6
8
BLK
WHT
YEL
FU4 (115V)
FNM-6
3
FB1
(NO MM)
FB1
380-3-60,460-3-60,575-3-60
208/230-3-60
LP-CC-20
380-3-60,460-3-60,575-3-60
208/230-3-60
KTK-R-15
KTK-R-20
NONE
(WITH MM)
380-3-60,460-3-60,575-3-60
208/230-3-60
FB2
FB3
NONE
LP-CC-20
LP-CC-20
LOW AMBIENT OPERATION (MOTORMASTER V) FIOP/ACCESSORY
380-3-60,460-3-60,575-3-60
208/230-3-60
NONE
MM-A
FB3
FB1
1
2
3
L1 T1
11
12
13
21
22
23
11
12
13
21
22
23
BLK
YEL
BLU
BLK-1
BLK-2
BLK-3
BLK
YEL
BLU
BLK
YEL
BLU
L2 T2
OFM1
L3 T3
GRN/YEL
YEL
HIGH SCCR
ONLY
2
MMR
14
*
MM SIGNAL CONNECTION
VOLTAGE
*1
VIO 11
TB
1
HZ
60
60
240
1/4W
208/230/460/575
380
RED
25
2
FROM
13A
AUX-J4
BLK
FB2
FC2
1
2
3
11
12
13
21
22
23
11
12
13
21
22
23
BLK-1
BLK-2
BLK-3
BLK
YEL
BLU
BLK
YEL
BLU
OFM2
GRN/YEL
CHC
CHC
1
4
2
6
BLK
WHT
BLK
BLK
BLK
1
2
3
2
COOLER/PUMP
COOLER/PUMP
HEATERS
(208/230,230V)
HEATERS
(380,460,575V)
8
BLK
WHT
YEL
3
TABLE 1
TERMINAL
CONNECTIONS
FOR PRIMARY SIDE
VOLTAGE
SERIES
575-3-60
380-3-60
230-3-60
208-3-60
460-3-60
100
200
500
500
600
H1
H1
H2
H3
H1
&
&
&
&
&
H2
H2
H4
H4
H4
NOTES:
8. IF CHILLED WATER PUMP INTERLOCK IS USED,
REMOVE JUMPER FROM TERMINAL 11 TO 17 AND
WIRE INTERLOCK CONTACT ACROSS TERMINALS 11 & 17.
1. FACTORY WIRING IS IN ACCORDANCE WITH UL 1995 STANDARDS.
ANY FIELD MODIFICATIONS OR ADDITIONS MUST BE IN
COMPLIANCE WITH ALL APPLICABLE CODES.
C MIN WIRE FOR FIELD POWER SUPPLY.
9. MP-A1 NOT USED IN THE FOLLOWING UNITS:
018,020: ALL UNITS
025,030: 460V UNITS WITHOUT DIGITAL SCROLL
3. ALL FIELD INTERLOCK CONTACTS MUST HAVE A MIN RATING OF
2 AMPS @ 24VAC SEALED. SEE FIELD INTERLOCK WIRING.
FU1
FU2
BLK
10. MP-A2 NOT USED IN THE FOLLOWING UNITS:
018-020: ALL UNITS
025,030: 460V UNITS
4. COMPRESSOR AND FAN MOTORS ARE THERMALLY PROTECTED--
THREE PHASE MOTORS PROTECTED AGAINST PRIMARY SINGLE
PHASE CONDITIONS.
YEL
CONNECT FOR
APPROPRIATE
PRIMARY VOLTAGE
SEE TABLE 1
11. JUMPER PLUG REQUIRED WHEN MP NOT USED
5. TERMINALS 13& 14 OF LVT ARE FOR FIELD CONNECTION
OF REMOTE ON-OFF. THE CONTACT MUST BE RATED FOR DRY
CIRCUIT APPLICATION CAPABLE OF HANDLING A 5VDC
1 MA TO 20 MA LOAD.
TRAN1
PRIMARY
H3
6. FOR 500 SERIES UNIT OPERATION AT 208-3-60V LINE VOLTAGE,
TRAN1 PRIMARY CONNECTIONS MUST BE MOVED TO TERMINALS H3 & H4.
H1
X1
H2
H4
7. FOR UNITS WITH LOW AMBIENT MOTOR MASTER V FIOP/ACCESSORY,
FAN CONTACTOR FC1 IS REPLACED WITH MOTORMASTER RELAY MMR.
TB4
5
TB1
C
SECONDARY 24V
TB4
7
RED XF
X2
BRN
C
FU3
RED
BRN
GRN/YEL
TB1
RED
A1
SW2
C1
BRN
B1
3
2
1
3
2
1
J1
EXV
J2
3
2
1
3
2
1
UPC FIOP
BRN
RED
VIO
24VAC
CB3
3.2 AMPS
BRN
VIO
2
1
GND
HOT
TB4
6
UPC
VIO
FIOP/ACCESSORY
J1
DGS FIOP
VIO
3
2
1
3
2
1
3
2
1
3
2
1
J1
MBB
J2
3
2
1
3
2
1
3
2
1
3
2
1
BRN
RED
12
BRN
RED
BRN
VIO
2
1
AUX
J1
EMM
J2
11
a30-4965
BRN
1
3
VIO
BRN
BLU
BRN
CWFS
Fig. 6A — Typical Wiring Schematic, 30RAP018-030 Units — Power Wiring
24
Download from Www.Somanuals.com. All Manuals Search And Download.
CB1
3.2 AMPS
TB4
4
RED
TB1
TRAN1
RED
SEE NOTE
9
A2
B2
CB2
5.2 AMPS
SW2
C2
RED
BRN
BRN
BRN
BRN
BRN
MBB J1-2
UPC GND
CWFS 3
PL1-3
RED
PL1-4
BRN
TB4
7
TB4
5
RED
RED
BRN
BRN
SECONDARY 24V
T2 MP-A1 T1
SEE NOTE 10
XF
X1
X2
RED
RED
FU3
BRN
GRN/YEL
ORN
MBB
ORN
ORN
PL1-7
RED
PL1-8
BRN
J10A
1
2
3
4
5
6
7
8
9
1
2
3
4
5
EXV J1-2
LVT J12-5
T2 MP-A2 T1
1
2
RED
BLK
BRN A2 CHC
BRN A2 CA1
C
RED
RED
GRA
GRA
BRN
RLY 11
GRA
PNK
ORN
A2 CWP1
3
BRN
BRN
MLV-A
4
MLV ACCSY
BRN
5
6
PNK
ORN
A1 FC1 A2
SEE NOTE 7
A2 CA2
A2 FC2
BRN
RLY 9
BRN
7
8
RLY 10
9
A2 FC1
A2 FC3
A1 FC2 A2
BRN
BRN
J10B
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
RLY 5
RLY 6
TB4
RED
RED
4
MAX LOAD-5VA SEALED
10VA INRUSH
6
7
LVT
J11
LVT
J12
RED
RED
ALM
R
1
18
21
5
C
RLY 7
BRN
BRN
TB1
ACCESSORY
STORAGE TANK
HEATER RELAY
8
TNK
R
9
RED
ORN
10
ORN
C
C
TB1
TB1
RLY 8
RLY 1
RLY 2
RLY 3
RLY 4
ORN
A1 CHC A2
A1 CA1 A2
A1 CA2 A2
HPS-A
11
12
BLK
BLK
BLK
BLK
PL1-1
PL1-2
VIO
MP-A1
ORN
GRA
VIO
RED
VIO
VIO
BRN
BRN
M1
M1
M2
M2
ORN
GRA
SEE NOTE 11
PL1-5
13
14
VIO
A2 CA2
A2 CA1
PL1-6
VIO
MP-A2
BRN
15
SEE NOTE 11
VIO
16
17
18
LVT
J12
CWP
1
VIO
BRN
C
TB1
A1
A1
A2
A2
A2 CWP2
A2 CWP1
BRN
BRN
1
2
25
24
CWP
2
RED
FIOP OR
FIELD INSTALLED
OPTION
SEE NOTES ON
PAGE 24.
LVT
J12
6
HEAT
FIELD INSTALLED
MAX LOAD-5VA SEALED
10VA INRUSH
6
5
4
3
2
1
20
19
GRA
GRA
6
5
4
3
2
1
7
J6
HR
ALMR
VIO
BRN
BR
HEAT/BOILER FIELD
INSTALLED WIRING
LVT
J11
2
CWFS
4
2
10
17
BLK
WHT
10
4
3
2
1
1
2
3
4
5
4
3
2
1
EXV
1
2
3
4
5
1
3
4
RED
BLK
WHT
RED
1
2
3
4
CWPI
SEE
2
J3
WHT
J7
3
J3
J4
BLK
NOTE
8
4
9
4
3
2
1
11
11
12
13
14
9
ORN
9
1
1
MARQUEE
DISPLAY
PL-EXVA
BLK
4
3
2
1
RED
RED
1
1
2
3
4
5
6
1
2
3
4
5
2
3
4
5
6
2
1
2
3
4
5
BLK
BLK
WHT
RED
WHT
BLK
2
3
4
5
6
WHT
YEL
J4
3
WHT
BLK
EXV-A
4
J6
GRY
5
GRN
RED
BRN
BRN
RED
6
RED
RED
1
MAIN
BASE
BOARD
1
2
RED
2
3
1
2
3
1
2
3
1
2
3
1
2
CSB
B2
ORN
3
PL50-1
DUS
7
8
8
7
3
BRN
-
7
8
VIO
RED
4
13
14
RED
8
7
AUX
4
RED
5
J2
CH1
6
5
4
3
2
1
BRN
BLK
CSB
A2
SW1
ENABLE
RED
-
G
+
-
G
+
3
2
1
3
2
1
5
ORN
PL50-2
PL50-3
A1
B1
6
6
BRN
7
7
1
2
OFF
RED
DTT
C1
J9
CH11
-
REMOTE
RED
BLK
RED
BLK
1
2
7
RED
ON-OFF
SWITCH
(SEE NOTE
5)
8
CSB
B1
J9
J6
J4
J5
BLK
WHT
RED
8
ORN
9
PL50-4
8
RED
GRA
GRA
9
BRN
DGS OR
MM
FIOP
10
RED
11
1
2
10
11
12
CH9
-
1
2
RED
BLK
CSB
A1
TO MM-A
6
5
4
ORN
12
15
16
6
6
5
4
3
2
1
BRN
ON
J7
1
2
OFF
CH10
-
1
2
5
1
RGTA
1
DARK
2
3
=
4
5
6
7
8
RED
DUAL
SETPOINT
1
2
SWITCH LOCATION
2
BLK
3
4
RED
14
13
CWP2
RED
3
LVT
J12
4
T55
3
2
1
LVT
J10
5
5
BLU
3
23
22
T-55
SEN
1
6
1
2
GRA
GRA
RED
RED
BLU
BLU
17
16
15
14
13
12
11
1
2
3
4
5
6
ACCSY
4
3
2
1
6
BLU
4
2
4
3
2
1
EMM
1
VIO
14
13
CWP1
VIO
OAT
3
ICE DONE
DLS STEP
DLS STEP
7
RED
BLK
WHT
RED
3
SPACE TEMPERATURE
ACCESSORY OR
DUAL CHILLER LWT
J3
J4
4
2
4
8
BLK
5
1
3
4
5
9
6
6
7
2
LVT
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
7
8
1
EVAPORATOR ENTERING
FLUID TEMP
4
3
2
1
J7
J6
RED
8
4
3
2
1
9
J13
10
9
2
9
BLK
WHT
RED
BRN
10
9
BLK
10
11
12
13
14
1
2
3
4
5
6
7
8
BLK
10
11
12
13
14
3
RED
EVAPORATOR LEAVING
FLUID TEMP
J8
RED
8
WHT
RED
BRN
RED
BLK
WHT
RED
8
4
7
RED
BLK
BLK
WHT
RED
7
6
1
2
3
4
5
6
6
WHT
BLK
5
J5
5
10
9
FIOP/
ACCESSORY
4
4
DEMAND
LIMIT
4-20mA
7
8
+
-
3
1
BLK
WHT
RED
3
1
2
8
2
2
2
J1
VIO
BRN
7
1
3
1
3
6
4
UPC
TEMP
RESET
4-20mA
4
5
9
+
-
5
PORT
2
5
ORN
PNK
4
7
B
RED
BLK
1
NET
+
-
6
LON
OPTION
RED
6
3
2
3
4
5
NET
N/C
N/C
+
-
7
C
A
8
COOLING
SETPOINT
4-20mA
J3 GND
NET
7
2
10
+
-
DPTA
GRN
8
8
1
9
9
BLK
J4
1
9
WHT
SIGNAL
10
B
C
A
10
11
12
RED
10
11
12
PORT 1A
2
+
-
11
1
2
3
NET
NET
+
2
SPTA
GRN
12
BLK
SHIELD
UPC OPT
a30-4966
Fig. 6B — Typical Wiring Schematic, 30RAP018-030 Units — Control Wiring
25
Download from Www.Somanuals.com. All Manuals Search And Download.
STANDARD
TERMINAL
BLOCK
CH-A1
OPTIONAL
DISCONNECT
BLU
BLK
380V,460V,575V
ONLY
CCB-1
CB1A
CA1
CSB-A1
TB1A
1
BLK
BLK
BLK
BLK
BLK
11
21
22
23
11
21
BLK
YEL
BLU
T1
T2
BLK
YEL
BLU
BLK
11
21
22
2
3
1
12
13
YEL
12
22
23
COMP A1
GRN/YEL
BLU
YEL
13
T3
YEL
YEL
YEL
YEL
YEL
YEL
12
13
2
3
CH-A2
BLK BLU
BLU BLK
BLU
BLK
CCB-2
BLU
BLU
BLU
BLU
BLU
CA2
CSB-A2
1
11
12
13
21
22
23
BLK
YEL
BLU
11
12
13
21
BLK
YEL
T1
23
BLK
YEL
BLU
2
3
COMP A2
GRN/YEL
22
23
T2
BLU
T3
208/230V ONLY
EQUIP GND
CH-B1
BLU
BLK
380V,460V,575V
ONLY
CSB-B1
CCB-3
CB1
11
FU5
FU6
BLK
1
11
12
13
21
22
23
21
BLK
YEL
BLU
BLK
YEL
BLU
BLK
T1
RED
1
2
3
1
HF
YEL
12
22
23
T2
COMP B1
GRN/YEL
H4
H3
H2
BLU
YEL
13
H1
T3
~
TRAN3
WHT
CH-B2
BLU BLK
SECONDARY
115V
BLU
BLK
X3
X1
FU4
GRN/YEL
CCB-4
XF
CB2
CSB-B2
1
11
12
13
21
22
23
BLK
YEL
BLU
11
12
13
21
BLK
YEL
T1
2
BLK
BLK
YEL
BLU
GFI-CO
2
3
COMP B2
GRN/YEL
22
23
T2
2
FIOP/ACCESSORY
BLU
T3
LINE
208/230V ONLY
BRASS SCREW
SILVER SCREW
RESET
TEST
TERMINAL
CONNECTIONS
FOR PRIMARY SIDE
TERMINAL
CONNECTIONS FOR
SECONDARY SIDE
CHILLED WATER PUMP FIOP
CWP1
VOLTAGE
SERIES
100
MS-CWP1
L1
BLK
BLK
BLK
BLK
YEL
BLU
T1
T2
T3
L1
L2
L3
T1
T2
T3
575-3-60
H1-H2
H2-H4
H3-H4
H1-H4
XF-X2
XF-X2
XF-X2
XF-X2
L1
L2
L3
230-3-60
208-3-60
460-3-60
400,500
500
CWP1
WATER
PUMP
GRN-YEL
L2
L3
LOAD
600
GRN/YEL
MS-CWP2
L1
CWP2
BLK
BLK
BLK
BLK
YEL
BLU
T1
T2
T3
L1
L2
L3
T1
T2
T3
L1
L2
L3
CWP2
WATER
PUMP
FUSE
NUMBER
TRAN
SIZE
REPLACE
WITH
L2
L3
UNIT VOLTAGE
208/230-3-60
380-3-60
FNQ-R-3.5
FNQ-R-2.5
FNQ-R-2
GRN/YEL
FU1
&
FU2
200VA
460-3-60
575-3-60
FNQ-R-1.5
380-3-60,460-3-60,575-3-60
208/230-3-60
FU3 (24V)
200VA
500VA
500VA
NONE
FNM-10
FB3
FB1
460-3-60,575-3-60
208/230-3-60,230-3-60
380-3-60,460-3-60,575-3-60
208/230-3-60
FNQ-R-2.5
FNQ-R-3.5
FC1
21
FU5
&
FU6
1
2
3
11
12
13
21
22
23
11
12
13
21
BLK
YEL
BLU
BLK
YEL
BLU
BLK 11
YEL
BLK-1
BLK-2
BLK-3
FU4 (115V)
FNM-6
22
23
OFM3
GRN/YEL
12
22
23
FB1
(NO MM)
FB1
380-3-60,460-3-60,575-3-60
208/230-3-60
LP-CC-20
380-3-60,460-3-60,575-3-60
208/230-3-60
KTK-R-15
KTK-R-20
LP-CC-20
BLU 13
BLK
NONE
NONE
NONE
(WITH MM)
FB2
575-3-60
HIGH SCCR
ONLY
CHC
CHC
380-3-60,460-3-60,575-3-60
208/230-3-60
FB3
LP-CC-20
4
2
6
BLK
WHT
COOLER/PUMP
HEATERS
BLK
BLK
1
3
2
3
COOLER/PUMP
HEATERS
(208/230,230V)
(380,460,575V)
2
8
BLK
WHT
YEL
NOTES:
SEE NOTE 7
BLK
FCB2/FB2
FC2
21
9. IF CHILLED WATER PUMP INTERLOCK IS USED,
REMOVE JUMPER FROM TERMINAL 11 TO 17 AND
WIRE INTERLOCK CONTACT ACROSS TERMINALS 11 & 17.
1. FACTORY WIRING IS IN ACCORDANCE WITH UL 1995 STANDARDS.
ANY FIELD MODIFICATIONS OR ADDITIONS MUST BE IN
COMPLIANCE WITH ALL APPLICABLE CODES.
1
21
22
23
11
12
13
BLK-1
BLK-2
BLK-3
BLK 11
2
3
2. USE 75 C MIN WIRE FOR FIELD POWER SUPPLY.
10. MP-A1 NOT USED IN THE FOLLOWING UNITS:
035-045: ALL UNITS
050-060: 460V UNITS WITHOUT DIGITAL SCROLL
12
YEL
BLU
22
23
OFM1
YEL
3. ALL FIELD INTERLOCK CONTACTS MUST HAVE A MIN RATING OF
2 AMPS @ 24VAC SEALED. SEE FIELD INTERLOCK WIRING.
13
BLU
GRN/YEL
11. MP-A2 NOT USED IN THE FOLLOWING UNITS:
035-045: ALL UNITS
050-060: 460V UNITS
4. COMPRESSOR AND FAN MOTORS ARE THERMALLY PROTECTED--
THREE PHASE MOTORS PROTECTED AGAINST PRIMARY SINGLE
PHASE CONDITIONS.
1
2
3
BLK-1
BLK-2
BLK-3
12. MP-B1 NOT USED IN THE FOLLOWING UNITS:
035,040: ALL UNITS
045-060: 460V UNITS
13. MP-B2 NOT USED IN THE FOLLOWING UNITS:
035,040: ALL UNITS
045-060: 460V UNITS
5. TERMINALS 13& 14 OF LVT ARE FOR FIELD CONNECTION
OF REMOTE ON-OFF. THE CONTACT MUST BE RATED FOR DRY
CIRCUIT APPLICATION CAPABLE OF HANDLING A 5VDC
1 MA TO 20 MA LOAD.
OFM2
YEL
BLK BLU
6. FOR 500 SERIES UNIT OPERATION AT 208-3-60V LINE VOLTAGE,
TRAN1 PRIMARY CONNECTIONS MUST BE MOVED TO TERMINALS H3
GRN/YEL
& H4.
FC3
14. JUMPER PLUG REQUIRED WHEN MP NOT USED
1
2
3
7. FOR 575-3-60V UNITS, FAN CIRCUIT BREAKER FCB2
IS REPLACED WITH FUSE BLOCK FB2.
11
12
13
21
22
23
BLK-1
BLK-2
BLK-3
BLK
YEL
BLU
8. FOR UNITS WITH LOW AMBIENT MOTOR MASTER V FIOP/ACCESSORY,
030-050: FAN CONTACTOR FC1 IS REPLACED WITH MOTORMASTER RELAY MMR.
055,060: FAN CONTACTOR FC3 IS REPLACED WITH MOTORMASTER RELAY MMR..
OFM4
(055,060 ONLY)
BLK
YEL
GRN/YEL
(055,060 ONLY)
LOW AMBIENT OPERATION (MOTORMASTER V) FIOP/ACCESSORY
TABLE 1
SERIES
TABLE 2
TERMINAL
CONNECTIONS
TERMINAL
CONNECTIONS
MM-A
FB3
FB1
VOLTAGE
VOLTAGE
SERIES
1
2
3
FOR PRIMARY SIDE
FOR PRIMARY SIDE
11
12
13
21
22
23
11
12
13
21
22
23
L1 T1
BLK
YEL
BLU
BLK
YEL
BLU
BLK
YEL
BLU
BLK-1
BLK-2
BLK-3
575-3-60
380-3-60
230-3-60
208-3-60
460-3-60
100
200
500
500
600
H1
H1
H2
H3
H1
&
&
&
&
&
H2
H2
H4
H4
H4
575-3-60
380-3-60
230-3-60
208-3-60
460-3-60
100
200
500
500
600
COM
COM
COM
COM
COM
&
&
&
&
&
575
380
230
208
460
OFM3 (035-050)
OFM4 (055,060)
L2 T2
L3 T3
GRN/YEL
YEL
HIGH SCCR
ONLY
2
MMR
14
*
MM SIGNAL CONNECTION
FU1
FU2
BLK
YEL
*1
VIO 11
TB
1
VOLTAGE
208/230/460/575
380
HZ
60
60
BLK
YEL
240
1/4W
RED
BLK
25
2
FROM
AUX-J4
13A
CONNECT FOR
APPROPRIATE
PRIMARY VOLTAGE
SEE TABLE 1
CONNECT FOR
APPROPRIATE
575
460
400
380
230
PRIMARY VOLTAGE
SEE TABLE 2
CHC
TRAN2
PRIMARY
TRAN1
PRIMARY
4
8
2
6
BLK
WHT
COOLER/PUMP
HEATERS
BLK
BLK
BLK
1
H3
208
H1
X1
H2
H4
COM
3
2
2
3
COOLER/PUMP
HEATERS
(208/230,230V)
CB4
3.2 AMPS
(380,460,575V)
SECONDARY 24V
SECONDARY 24V
TB4
7
CHC
RED XF
X2
BRN
C
RED
FU3
YEL
BLK
WHT
GRN/YEL
TB1
GRN/YEL
RED
SEE NOTE 7
BLK
A1
FCB2/FB2
SW2
RED
FC2
21
BRN
1
11
12
13
21
22
23
11
12
13
BLK-1
BLK-2
BLK-3
BLK
YEL
BLU
C1
BRN
B1
2
3
3
2
1
3
J1
EXV
J2
YEL
BLU
22
23
OFM1
3
2
1
3
2
UPC FIOP
24VAC
BRN
RED
2
1
VIO
1
GRN/YEL
CB3
3.2 AMPS
BRN
VIO
2
1
GND
HOT
TB4
1
2
3
UPC
BLK-1
BLK-2
BLK-3
VIO
6
FIOP/ACCESSORY
J1
OFM2
DGS FIOP
VIO
3
2
1
3
2
1
3
2
3
2
1
J1
MBB
J2
3
2
1
3
2
1
3
2
1
3
GRN/YEL
2
1
BRN
RED
12
2
1
BRN
RED
BRN
VIO
AUX
J1
EMM
J2
FC1
a30-
5283
1
2
3
1
11
BLK
11
12
13
21
22
23
BLK-1
BLK-2
BLK-3
YEL
OFM3
(055,060 ONLY)
BLU
BRN
GRN/YEL
(055,060 ONLY)
1
3
VIO
BRN
BLU
BRN
CWFS
Fig. 7A — Typical Wiring Schematic, 30RAP035-060 Units — Power Wiring
26
Download from Www.Somanuals.com. All Manuals Search And Download.
CB1
3.2 AMPS
TB4
4
a30-5284
RED
TB1
TRAN1
RED
SEE NOTE 10
A2
B2
CB2
5.2 AMPS
SW2
C2
RED
BRN
BRN
BRN
MBB J1-2
UPC GND
CWFS 3
PL1-3
RED
PL1-4
BRN
TB4
7
TB4
5
RED
RED
RED
RED
BRN
BRN
BRN
BRN
SECONDARY 24V
T2 MP-A1 T1
SEE NOTE 11
XF
X1
X2
RED
RED
FU3
BRN
GRN/YEL
ORN
MBB
ORN
ORN
PL1-7
RED
PL1-8
BRN
J10A
1
2
3
4
5
6
7
8
9
1
2
3
4
5
BRN A2 CB1
T2 MP-A2 T1
SEE NOTE 12
1
2
RED
BRN
LVT J12-5
BLK
PL2-3
RED
PL2-4
BRN
BRN A2 CHC
BRN A2 CA1
C
BLU
GRA
T2 MP-B1 T1
SEE NOTE 13
RED
RED
RLY 11
GRA
GRA
BRN
A2 CWP1
3
BRN
BRN
PL2-7
RED
PL2-8
BRN
T2 MP-B2 T1
MLV-A
4
MLV ACCSY
BRN
5
6
PNK
A1 FC1 A2
SEE NOTE 8
A2 CA2
A2 FC2
PNK
BRN
RLY 9
LEGEND
BRN
7
TERMINAL BLOCK
TERMINAL (UNMARKED)
TERMINAL (MARKED)
SPLICE
X
X
8
A2 FC1
A2 FC3
BRN
BRN
FACTORY WIRING
FIELD WIRING
RLY 10
9
ORN
BLK
VIO
ORN
VIO
PNK
A1 FC2 A2
ACCESSORY OR OPTION WIRING
HPS-B
TO INDICATE COMMON POTENTIAL
ONLY,NOT TO REPRESENT WIRING
J10B
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
BLU
BLK
BLU
BRN
BRN
C
TB1
PL2-1
PL2-2
PL2-6
MP-B1
ACCSY
ALMR
AUX
BR
C
CB
CCB
CH
CHC
CO
COMP
CSB
CWFS
CWP
CWPI
DGS
DLS
DPT
DTT
DUS
EMM
EWT
EXV
FB
ACCESSORY
ALARM RELAY
AUXILIARY
BOILER RELAY
CONTACTOR, COMPRESSOR
CIRCUIT BREAKER
VIO
VIO
VIO
A2 CB2
RLY 5
M1
M1
CB1
FR3
M2
M2
A1
1
A2
0
VIO
PNK
BRN
SEE NOTE 14
PL2-5
VIO
(055,060 ONLY)
MP-B2
RLY 6
PNK
RED
VIO
A2 CB1
A1 CB2 A2
BRN
BRN
BRN
COMPRESSOR CIRCUIT BREAKER
CRANKCASE HEATER
COOLER/PUMP HEATER CONTACTOR
CONVENIENCE OUTLET
COMPRESSOR
CURRENT SENSOR BOARD
CHILLED WATER FLOW SWITCH
CHILLED WATER PUMP
CHILLED WATER PUMP INTERLOCK
DIGITAL SCROLL
DEMAND LIMIT SWITCH
DISCHARGE PRESSURE TRANSDUCER
DISCHARGE TEMPERATURE THERMISTOR
DIGITAL UNLOADER SOLENOID
ENERGY MANAGEMENT
ENTERING WATER TEMPERATURE
EXPANSION VALVE CONTROL BOARD
FUSE BLOCK
TB4
4
BRN
SEE NOTE 14
VIO
1
FR4
0
(055,060 ONLY)
LVT
MAX LOAD-5VA SEALED
10VA INRUSH
6
7
LVT
J11
J12
RED
RED
ALM
R
RED
1
18
21
5
C
TB1
RLY 7
ACCESSORY
STORAGE TANK
HEATER RELAY
8
TNK
R
9
RED
ORN
10
ORN
BLK
ORN
C
C
TB1
TB1
RLY 8
RLY 1
RLY 2
RLY 3
RLY 4
ORN
A1 CHC A2
HPS-A
11
12
BLK
BLK
BLK
BRN
BRN
PL1-1
PL1-2
VIO
MP-A1
VIO
VIO
A2 CA2
FC
FAN CONTACTOR
M1
M1
M2
M2
ORN
ORN
A1 CA1 A2
FCB
FIOP
FR
FAN CIRCUIT BREAKER
FACTORY INSTALLED OPTION
FAN RELAY
BRN
BRN
SEE NOTE 14
PL1-5
13
14
VIO
1
FR1
0
(055,060 ONLY)
(055,060 ONLY)
PL1-6
VIO
MP-A2
FU
FUSE
GROUND
GRA
A2 CA1
GRA
GRA
A1 CA2 A2
BRN
GND
HPS
HR
LVT
LWT
MBB
MLV
MM
HIGH PRESSURE SWITCH
HEAT RELAY
LOW VOLTAGE TERMINAL
LEAVING WATER TEMPERATURE
MAIN BASE BOARD
MINIMUM LOAD VALVE
MOTORMASTER
MOTORMASTER RELAY
MODULAR MOTOR PROTECTOR
MANUAL STARTER
15
SEE NOTE 14
VIO
1
FR2
0
16
17
18
VIO
TAN
RED
LVT
J12
CWP
1
VIO
RED
BRN
C
A1
A2
TB1
A2 CWP2
A2 CWP1
BRN
BRN
1
2
25
24
MMR
MP
MS
CWP
2
A1
A2
OAT
OFM
PL
OUTDOOR AIR THERMISTOR
OUTDOOR FAN MOTOR
PLUG
FIOP OR
FIELD INSTALLED
OPTION
FR4
4
2
R
RELAY
LVT
(055,060 ONLY)
RGT
RLY
SAT
SCCR
SPT
SW
RETURN GAS TEMPERATURE
RELAY
SUPPLY AIR TEMPERATURE
SHORT CIRCUIT CURRENT RATING
SUCTION PRESSURE TRANSDUCER
SWITCH
TERMINAL BLOCK
STORAGE TANK HEATER RELAY
TRANSFORMER
PNK
PNK
PNK
TAN
TAN
J12
6
HEAT
FIELD INSTALLED
MAX LOAD-5VA SEALED
10VA INRUSH
6
5
4
3
2
1
FR3
20
19
GRA
GRA
6
5
4
3
2
1
4
2
7
(055,060 ONLY)
TB
J6
FR2
HR
ALMR
TNKR
TRAN
UPC
VIO
BRN
4
BR
2
UNITARY PROTOCOL CONVERTER
(055,060 ONLY)
HEAT/BOILER FIELD
INSTALLED WIRING
TAN
FR1
4
A2 FC2
2
PNK
A1 FC3 A2
BRN
LVT
J11
2
(055,060 ONLY)
CWFS
4
(055,060 ONLY)
SEE NOTE 8
2
10
17
BLK
WHT
10
PL-EXVB
4
3
2
1
1
2
3
4
5
BLK
YEL
4
3
2
1
EXV
BLK
WHT
1
2
3
1
2
3
4
3
4
RED
BLK
WHT
RED
1
2
3
4
CWPI
SEE
J3
EXV-B
WHT
BLK
J7
GRY
RED
J3
J4
NOTE
9
4
5
GRN
RED
9
4
3
2
1
11
11
12
13
14
9
ORN
9
1
2
3
4
5
6
1
2
3
4
5
6
MARQUEE
DISPLAY
PL-EXVA
BLK
4
3
2
1
RED
WHT
BLK
RED
WHT
BLK
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
BLK
YEL
1
2
3
4
5
BLK
WHT
RED
J4
WHT
EXV-A
J6
GRY
RED
GRN
RED
BRN
RED
RED
BRN
1
MAIN
BASE
BOARD
1
2
RED
ORN
BRN
RED
ORN
BRN
RED
ORN
BRN
RED
ORN
BRN
2
2
CSB
B2
3
3
PL50-1
7
8
DUS
DTT
8
7
3
1
-
7
8
VIO
RED
4
13
14
RED
8
7
AUX
4
2
J2
CH1
6
5
4
3
2
1
BRN
BLK
5
CSB
A2
SW1
ENABLE
RED
-
G
+
-
G
+
3
2
1
3
2
1
5
3
PL50-2
PL50-3
A1
B1
6
6
1
7
1
2
OFF
RED
7
C1
J9
CH11
-
REMOTE
RED
BLK
RED
BLK
1
2
7
2
ON-OFF
SWITCH
(SEE NOTE
5)
8
CSB
B1
J9
DGS OR
MM
FIOP
J6
J4
J5
BLK
WHT
RED
8
3
9
PL50-4
8
RED
GRA
GRA
9
1
10
11
12
1
2
10
11
12
2
CH9
-
1
2
RED
BLK
CSB
A1
TO MM-A
6
5
4
3
15
16
6
6
5
4
3
2
1
1
ON
J7
1
2
OFF
CH10
-
1
2
5
1
2
3
4
5
6
1
2
3
4
1
2
3
4
1
2
3
4
5
6
7
RGTA
RGTB
1
DARK
2
3
=
4
5
6
7
8
RED
DUAL
SETPOINT
1
2
SWITCH LOCATION
BLK
RED
RED
14
13
CWP2
RED
3
LVT
J12
4
BLK
BLU
BLU
RED
T55
3
2
1
LVT
J10
5
3
23
22
T-55
SEN
1
1
2
GRA
GRA
RED
RED
BLU
BLU
17
16
15
14
13
12
11
1
2
3
4
5
6
ACCSY
4
3
2
1
6
4
2
4
3
2
1
EMM
VIO
14
13
CWP1
VIO
OAT
3
ICE DONE
DLS STEP
DLS STEP
7
BLK
WHT
RED
3
SPACE TEMPERATURE
ACCESSORY OR
DUAL CHILLER LWT
J3
J4
4
4
8
BLK
5
1
5
9
6
6
7
2
LVT
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
7
8
EVAPORATOR ENTERING
FLUID TEMP
4
3
2
1
J7
RED
8
4
3
2
1
9
J13
10
9
8
7
6
5
4
3
2
1
9
BLK
WHT
RED
BRN
10
9
8
7
6
5
4
3
2
1
BLK
RED
10
11
12
13
14
1
2
3
4
5
6
7
8
BLK
10
11
12
13
14
RED
EVAPORATOR LEAVING
FLUID TEMP
J8
WHT
RED
BRN
RED
BLK
WHT
RED
RED
BLK
RED
BLK
WHT
RED
B
C
A
B
C
A
WHT
BLK
+
J5
10
9
8
7
6
5
4
3
2
1
FIOP/
ACCESSORY
DPTB
GRN
BLK
RED
DEMAND
LIMIT
4-20mA
7
8
+
-
-
1
BLK
WHT
RED
1
2
2
J1
VIO
BRN
+
3
3
SPTB
DPTA
SPTA
GRN
BLK
4
UPC
TEMP
RESET
4-20mA
4
9
+
-
-
5
PORT
2
5
ORN
PNK
B
C
A
RED
BLK
1
NET
+
-
6
LON
OPTION
RED
6
2
3
4
5
NET
N/C
N/C
+
7
8
J6
COOLING
SETPOINT
4-20mA
J3 GND
NET
7
10
+
-
GRN
BLK
8
8
9
-
9
J4
1
9
WHT
SIGNAL
10
B
C
A
10
11
12
RED
10
11
12
PORT 1A
2
+
11
12
1
2
3
NET
NET
+
2
GRN
BLK
-
SHIELD
UPC OPT
Fig. 7B — Typical Wiring Schematic, 30RAP035-060 Units — Control Wiring
27
Download from Www.Somanuals.com. All Manuals Search And Download.
RED LED - STATUS
GREEN LED -
LEN (LOCAL EQUIPMENT NETWORK)
YELLOW LED -
CCN (CARRIER COMFORT NETWORK)
INSTANCE JUMPER
CEPL130346-01
K11
K10
K9
K5
K8
K6
K7
J1
STATUS
J2
J3
J10
LEN
J4
K1
K4
K3
K2
CCN
J5
J6
J7
J8
J9
Fig. 8 — Main Base Board
a30-4967
Fig. 9 — Enable/Off/Remote Contact Switch, and Emergency On/Off Switch Locations
T-55 SPACE
SENSOR
a30-4968
SPT (T10) PART NO. 33ZCT55SPT
SENSOR
6
5
4
3
2
1
CCN+
LVT
TO CCN
CCN GND
SEN
SEN
COMM 1
BUS (PLUG)
AT UNIT
3
CCN-
4
Fig. 10 — Typical Space Temperature
Sensor Wiring
Fig. 11 — CCN Communications Bus Wiring
to Optional Space Sensor RJ11 Connector
28
Download from Www.Somanuals.com. All Manuals Search And Download.
compressor to start next. If no compressors have been running
for more than 30 minutes and the leaving fluid temperature is
greater than the saturated condensing temperature, the wear
factor is still used to determine which compressor to start next.
If the leaving fluid temperature is less than the saturated con-
densing temperature, then the control will start either compres-
sor A1 or compressor B1 first, depending on the user-configu-
rable circuit lead-lag value. For units with the minimum load
control valve, the A circuit with the minimum load valve is al-
ways the lead circuit. The A circuit is also always the lead for
units with the digital compressor option. On units with the dig-
ital scroll option, the A1 compressor operates continuously,
providing close leaving chilled water control. For this reason,
on/off cycling of the unit’s compressors is dramatically re-
duced, which in turn reduces wear associated with compressor
start/stop cycles.
Energy Management Module (Fig. 12) — This
factory-installed option (FIOP) or field-installed accessory is
used for the following types of temperature reset, demand
limit, and/or ice features:
•
•
•
4 to 20 mA leaving fluid temperature reset (requires
field-supplied 4 to 20 mA generator)
4 to 20 mA cooling set point reset (requires field-
supplied 4 to 20 mA generator)
Discrete inputs for 2-step demand limit (requires field-
supplied dry contacts capable of handling a 24 vac,
50 mA load)
4 to 20 mA demand limit (requires field-supplied 4 to
20 mA generator)
•
•
Discrete input for Ice Done switch (requires field-
supplied dry contacts capable of handling a 24 vac,
50 mA load)
The EXVs will provide a controlled start-up. During start-
up, the low pressure logic will be bypassed for 21/2 minutes to
allow for the transient changes during start-up. As additional
stages of compression are required, the processor control will
add them. See Table 19.
See Demand Limit and Temperature Reset sections on
pages 41 and 37 for further details.
CAUTION
Care should be taken when interfacing with other manufac-
turer’s control systems due to possible power supply
differences, full wave bridge versus half wave rectification.
The two different power supplies cannot be mixed.
ComfortLink™ controls use half wave rectification. A
signal isolation device should be utilized if a full wave
bridge signal generating device is used.
If a circuit is to be stopped, the compressor with the lowest
wear factor will be shut off first except when a digital compres-
sor is used. The digital compressor is always the last compres-
sor to shut off.
The capacity control algorithm runs every 30 seconds. The
algorithm attempts to maintain the Control Point at the desired
set point. Each time it runs, the control reads the entering and
leaving fluid temperatures. The control determines the rate at
which conditions are changing and calculates 2 variables based
on these conditions. Next, a capacity ratio is calculated using
the 2 variables to determine whether or not to make any
changes to the current stages of capacity. This ratio value
ranges from –100 to +100%. If the next stage of capacity is a
compressor, the control starts (stops) a compressor when the
ratio reaches +100% (–100%). If installed, the minimum load
valve solenoid will be energized with the first stage of capacity.
Minimum load valve value is a fixed 30% in the total capacity
calculation. The control will also use the minimum load valve
solenoid as the last stage of capacity before turning off the last
compressor. A delay of 90 seconds occurs after each capacity
step change. Refer to Table 19.
Loss-of-Cooler Flow Protection —
A
proof-of-
cooler flow device is factory installed in all chillers. It is recom-
mended that proper operation of the switch be verified on a reg-
ular basis.
Electronic Expansion Valves (EXV) — All units are
equipped from the factory with EXVs. Each refrigeration cir-
cuit is also supplied with a factory-installed liquid line filter
drier and sight glass.
The EXV is set at the factory to maintain 9° F (5.0° C) suc-
tion superheat leaving the cooler by metering the proper
amount of refrigerant into the cooler. The superheat set point is
adjustable, but should not be adjusted unless absolutely
necessary.
MINUTES LEFT FOR START — This value is displayed
only in the network display tables (using Service Tool,
ComfortVIEW™ or ComfortWORKS® software) and
represents the amount of time to elapse before the unit will start
its initialization routine. This value can be zero without the
machine running in many situations. This can include being
unoccupied, ENABLE/OFF/REMOTE CONTACT switch in
the OFF position, CCN not allowing unit to start, Demand
Limit in effect, no call for cooling due to no load, and alarm or
alert conditions present. If the machine should be running and
none of the above are true, a minimum off time (DELY, see
below) may be in effect. The machine should start normally
once the time limit has expired.
The EXV is designed to limit the cooler saturated suction
temperature to 50 F (12.8 C). This makes it possible for unit to
start at high cooler fluid temperatures without overloading the
compressor.
Capacity Control — The control system cycles com-
pressors, digital scroll modulting solenoid (if equipped), and
minimum load valve solenoids (if equipped) to maintain the
user-configured leaving chilled fluid temperature set point. En-
tering fluid temperature is used by the main base board (MBB)
to determine the temperature drop across the cooler and is used
in determining the optimum time to add or subtract capacity
stages. The chilled fluid temperature set point can be automati-
cally reset by the return fluid temperature, space, or outdoor-air
temperature reset features. It can also be reset from an external
4 to 20-mA signal (requires energy management module FIOP
or accessory).
The standard control has an automatic lead-lag feature built
in which determines the wear factor (combination of starts and
run hours) for each compressor. If all compressors are off and
less than 30 minutes has elapsed since the last compressor was
turned off, the wear factor is used to determine which
MINUTES
OFF
TIME
(ConfigurationOPT2
DELY) — This user-configurable time period is used by the
control to determine how long unit operation is delayed after
power is applied/restored to the unit. Typically, this time period
is configured when multiple machines are located on a single
site. For example, this gives the user the ability to prevent all
the units from restarting at once after a power failure. A value
of zero for this variable does not mean that the unit should be
running.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
CEBD430351-0396-01C
J1
J2
LEN
J4
J3
STATUS
J5
J7
J6
TEST 2
GREEN LED -
LEN (LOCAL EQUIPMENT NETWORK)
ADDRESS
DIP SWITCH
RED LED - STATUS
Fig. 12 — Energy Management Module
LEAD/LAG DETERMINATION — This is a configurable
choice and is factory set to be automatic for all units unless the
unit is equipped with a digital scroll compressor or minimum
load, then circuit A is lead (ConfigurationOPT2 LLCS).
The value can be changed to Circuit A or Circuit B leading as
desired. Set at automatic, the control will sum the current num-
ber of logged circuit starts and one-quarter of the current oper-
ating hours for each circuit. The circuit with the lowest sum is
started first. Changes to which circuit is the lead circuit and
which is the lag are also made when total machine capacity is
at 100% or when there is a change in the direction of capacity
(increase or decrease) and each circuit’s capacity is equal.
when the control is attempting to remove the last stage of
capacity.
Slow Change Override — The control prevents the capacity
stages from being changed when the leaving fluid temperature
is close to the set point (within an adjustable deadband) and
moving towards the set point.
Ramp Loading
—
Ramp
loading
(Configura-
tionSLCTCRMP) limits the rate of change of leaving
fluid temperature. If the unit is in a Cooling mode and config-
ured for Ramp Loading, the control makes 2 comparisons be-
fore deciding to change stages of capacity. The control calcu-
lates a temperature difference between the control point and
leaving fluid temperature. If the difference is greater than 4° F
(2.2° C) and the rate of change (°F or °C per minute) is more
than the configured Cooling Ramp Loading value (CRMP),
the control does not allow any changes to the current stage of
capacity.
CAPACITY CONTROL OVERRIDES — The following over-
rides will modify the normal operation of the routine.
Deadband Multiplier — The user configurable Deadband
Multiplier (ConfigurationSLCTZ.GN) has a default val-
ue of 1.0. The range is from 1.0 to 4.0. When set to other than
1.0, this factor is applied to the capacity Load/Unload Factor.
The larger this value is set, the longer the control will delay be-
tween adding or removing stages of capacity. Figure 13 shows
how compressor starts can be reduced over time if the leaving
water temperature is allowed to drift a larger amount above and
below the set point. This value should be set in the range of 3.0
to 4.0 for systems with small loop volumes.
Low Entering Fluid Temperature Unloading — When the
entering fluid temperature is below the control point, the
control will attempt to remove 25% of the current stages being
used. If exactly 25% cannot be removed, the control removes
an amount greater than 25% but no more than necessary. The
lowest stage will not be removed.
Minimum Load Control — If equipped, the minimum load
control valve is energized only when one compressor is run-
ning on circuit A. If the close control feature is enabled the
minimum load control valve may be used as needed to obtain
leaving fluid temperature close to set point.
First Stage Override — If the current capacity stage is zero,
the control will modify the routine with a 1.2 factor on adding
the first stage to reduce cycling. This factor is also applied
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 19 — Part Load Data Percent Displacement, Standard Units with Minimum Load Valve
CAPACITY STEPS
CAPACITY %
CONTROL
STEPS
30RAP UNIT SIZE
% Displacement
Circuit A
100
100
Circuit B
010
015
1
1
100
100
—
—
1
2
3
1
2
3
1
2
3
1
2
3
100
50
018
020
025
030
100
100
100
100
—
—
—
—
20*
100
50
24*
100
50
29*
100
50
32*
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
100
77
50
23
9*
035
040
045
050
055
54
47
47
50
46
50
46
53
53
50
54
50
100
73
50
23
11*
100
74
50
24
12*
100
75
50
25
14*
100
73
50
23
13*
100
75
060
50
25
16*
*Minimum Load Valve energized.
NOTE: These capacity steps may vary due to different capacity
staging sequences.
2 STARTS
DEADBAND EXAMPLE
47
8
7
6
5
46
45
44
43
42
41
0
200
400
600
800
1000
3 STARTS
TIME (SECONDS)
STANDARD
DEADBAND
LEGEND
LWT — Leaving Water Temperature
MODIFIED
DEADBAND
Fig. 13 — Deadband Multiplier
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Cooler Freeze Protection — The control will try to prevent
shutting the chiller down on a Cooler Freeze Protection alarm
by removing stages of capacity. If the cooler fluid selected
is Water, the freeze point is 34 F (1.1 C). If the cooler fluid
selected is Brine, the freeze point is the Brine Freeze Point (Set
PointsFRZBR.FZ). This alarm condition (A207) only
references leaving fluid temperature and NOT Brine Freeze
point. If the cooler leaving fluid temperature is less than the
freeze point plus 2.0° F (1.1° C), the control will immediately
remove one stage of capacity. This can be repeated once every
30 seconds.
Low Saturated Suction Protection — The control will try to
prevent shutting a circuit down due to low saturated suction
conditions by removing stages of capacity. These circuit alert
conditions (T116, T117) compare saturated suction tempera-
ture to the configured Brine Freeze Point (Set
PointsFRZBR.FZ). The Brine Freeze point is a user-
configurable value that must be left at 34 F (1.1 C) for 100%
water systems. A lower value may be entered for systems with
brine solutions, but this value should be set according to the
freeze protection level of the brine mixture. Failure to properly
set this brine freeze point value may permanently damage the
brazed plate heat exchanger. The control will initiate Mode 7
(Circuit A) or Mode 8 (Circuit B) to indicate a circuit’s capaci-
ty is limited and that eventually the circuit may shut down.
be added to the current fan stage. Fan On Set Point (F.ON)
equals Head Set Point (Set PointsHEADH.DP) except
after a fan stage increase when the Head Set Point is increased
by Fan Stage Delta (Set PointsHEADF.DLT). A fan
stage is decreased when the SCTs of both circuits are less than
the Fan Off Set Point (Set PointsHEAD F.OFF) for
two minutes. Table 20 shows the number of fan stages, contac-
tors energized and the fans that are on during the fan stage.
Unit sizes 035 to 060 have common fan control. Figure 14
shows the location of each fan and compressor within the unit.
MOTORMASTER® V OPTION — Motormaster V is stan-
dard on 30RAP010 and 015 size units. For all other units that
need low-ambient operation, the lead fan on a circuit can be
equipped with the Motormaster V head pressure controller op-
tion or accessory. The controller is energized with the first fan
stage and adjusts fan speed to maintain a SCT of 72 F (22.2 C).
The first stage of fan operation is controlled by the Motormas-
ter V controller. Refer to Fig. 15 for condenser fan layout infor-
mation. The Motormaster is configured in the Motormaster Se-
lect (ConfigurationMMMMR.S)
Operation of Machine Based on Control
Method and Cooling Set Point Selection Set-
tings — Machine On/Off control is determined by the
configuration of the Control Method
(Configura-
tionOPT2CTRL) and Cooling Set Point Select (Config-
urationSLCTCLSP) variables. All units are factory
configured with Cooling Set Point Select set to 0 (single set
point). With the control method set to 0, simply switching the
Enable/Off/Remote Contact switch to the Enable or Remote
Contact position (external contacts closed) will put the chiller
in an occupied state. The control mode (Operating
ModesMODE) will be 1 (OFF LOCAL) when the switch is
Off and will be 5 (ON LOCAL) when in the Enable position or
Remote Contact position with external contacts closed.
Head Pressure Control — The main base board
(MBB) controls the condenser fans to maintain the lowest
condensing temperature possible, and thus the highest unit
efficiency. The MBB uses the saturated condensing tempera-
ture input from the discharge pressure transducer and outside
air temperature sensor to control the fans. If OAT is greater
than 70 F before a circuit is starting, then all condenser fan
stages will be energized. A fan stage is increased based on
SCT (saturated condensing temperature). When the highest
SCT is greater than the Fan On Set Point (Set
PointsHEADF.ON), then an additional stage of fan will
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
-30
-20
-10
0
10
20
30
40
50
60
70
80
SST (F)
LEGEND
a30-4969
SCT
SST
—
—
Saturated Condensing Temperature
Saturated Suction Temperature
Fig. 14 — Operating Envelope for R-410A Compressor
32
Download from Www.Somanuals.com. All Manuals Search And Download.
OFM1
OFM2
a30-4970
OFM1
Top View
Sizes 010,015
Top View
Sizes 018-030
OFM1
OFM3
OFM1
OFM3
OFM2
OFM4
OFM2
Top View
Sizes 035-050
Top View
Sizes 055,060
Fig. 15 — 30RAP Condenser Fan Layout
Table 20 — Fan Stages
FAN STAGES
Contactor Energized
30RAP UNIT SIZE
Fan Stage
Fans Operating
010,015
018-030
Stage 1
Stage 1
Stage 2
—
FC1
FC1,2
OFM1
OFM1
OFM1,2
Stage 1
Stage 2
Stage 3
Stage 1
Stage 2
Stage 3
Stage 4
FC1
FC2
OFM3
OFM1,2
OFM1,2,3
OFM4
OFM4,3
OFM4,1,2
OFM1,2,3,4
035-050
055,060
FC1,2
FC3
FC1,3
FC3,2
FC1,2,3
Two other control methods are available for Machine On/
Off control:
OCCUPANCY
CTRL = 2) — The main base board will use the operating
schedules as defined under the Time Clock mode in the scroll-
ing marquee display. These schedules are identical. The sched-
ule number must be set to 1 for local schedule.
The schedule number can be set anywhere from 65 to 99
for operation under a CCN global schedule. The Enable/Off/
Remote Contact must be in the Enable or Remote Contact posi-
tion. The control mode (Operating ModesMODE) will be
1 when the switch is Off. The control mode will be 3 when the
Enable/Off/Remote Contact switch input is On and the time of
day is during an unoccupied period. Similarly, the control
mode will be 7 when the time of day is during an occupied
period.
CCN CONTROL (ConfigurationOPT2CTRL = 3) —
An external CCN device such as Chillervisor System Manager
controls the On/Off state of the machine. This CCN device
forces the variable ‘CHIL_S_S’ between Start/Stop to control
the chiller. The control mode (Operating ModesMODE)
will be 1 when the switch is Off. The control mode will be 2
when the Enable/Off/Remote Contact switch input is On and
the CHIL_S_S variable is ‘Stop.’ Similarly, the control mode
will be 6 when the CHIL_S_S variable is ‘Start.’
Table 20 illustrates how the control method and cooling set
point select variables direct the operation of the chiller and the
set point to which it controls. The illustration also shows the
ON/OFF state of the machine for the given combinations.
SCHEDULE
(ConfigurationOPT2
Cooling Set Point Select
SINGLE — Unit operation is based on Cooling Set Point 1
(Set PointsCOOLCSP.1).
DUAL SWITCH — Unit operation is based on Cooling Set
Point 1 (Set PointsCOOLCSP.1) when the Dual Set
Point switch contacts are open and Cooling Set Point 2 (Set
PointsCOOLCSP.2) when they are closed.
DUAL CCN OCCUPIED — Unit operation is based on
Cooling Set Point 1 (Set PointsCOOLCSP.1) during the
Occupied mode and Cooling Set Point
2
(Set
PointsCOOLCSP.2) during the Unoccupied mode as
configured under the local occupancy schedule accessible only
from CCN. Schedule Number in Table SCHEDOVR (See Ap-
pendix B) must be configured to 1. If the Schedule Number is
set to 0, the unit will operate in a continuous 24-hr Occupied
mode. Control method must be configured to 0 (switch). See
Table 21.
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 21 — Control Methods and Cooling Set Points
COOLING SET POINT SELECT (CLSP)
CONTROL
TYPE
(CTRL)
OCCUPANCY
STATE
0
1
2
3
(single)
(dual, switch)
(dual, occ)
(4 to 20 mA)
Occupied
Unoccupied
Occupied
Unoccupied
Occupied
Unoccupied
ON,CSP1
ON,CSP1
ON,CSP1
OFF
ON,CSP1
ON,CSP1
ON*
ON*
ON*
OFF
ON*
ON*
ON,CSP1
ON,CSP2
Illegal
Illegal
ON,CSP1
ON,CSP2
ON†
ON
ON†
OFF
ON†
ON†
0 (switch)
2 (Occupancy)
3 (CCN)
*Dual set point switch input used. CSP1 used when switch input is open. CSP2 used when switch input is closed.
†Cooling set point determined from 4 to 20 mA input to energy management module (EMM) to terminals TB6-3,5.
4 TO 20 mA INPUT — Unit operation is based on an external
4 to 20 mA signal input to the Energy Management Module
(EMM).
under the COMP mode will stay on for 10 minutes if there is
no keypad activity. Compressors will stay on until they are
turned off by the operator. The Service Test mode will remain
enabled for as long as there is one or more compressors run-
ning. All safeties are monitored during this test and will turn a
compressor, circuit or the machine off if required. Any other
mode or sub-mode can be accessed, viewed, or changed during
the TEST mode. The MODE item (Run StatusVIEW) will
display “0” as long as the Service mode is enabled. The TEST
sub-mode value must be changed back to OFF before the chill-
er can be switched to Enable or Remote contact for normal
operation.
Low Sound Mode Operation — All models are fac-
tory configured with the Low Sound Mode disabled. In the
Configuration mode under sub-mode OPT2, items for Low
Sound Mode Select (ConfigurationOPT2LS.MD), Low
Sound Start Time (ConfigurationOPT2LS.ST), Low
Sound End Time (ConfigurationOPT2LS.ND) and Low
Sound Capacity Limit (ConfigurationOPT2LS.LT) are
factory configured so that the chiller always runs as quietly as
possible. This results in operation at increased saturated con-
densing temperature. As a result, some models may not be able
to achieve rated efficiency. For chiller operation at rated effi-
ciency, disable the low sound mode or adjust the low sound
mode start and stop times accordingly or set both times to
00:00 for rated efficiency operation 24 hours per day. In addi-
tion, the low sound capacity limit can be used to reduce overall
chiller capacity, if required, by limiting the maximum to a user-
configured percentage.
Optional Factory-Installed Hydronic Pack-
age — If the chiller has factory-installed chilled fluid pumps,
specific steps should be followed for proper operation.
The pump(s) in the hydronic package come factory
pre-wired into the main unit power supply/starter. In order to
check proper pump rotation, use the Service Test function to
test the condenser fans and observe them for proper rotation. If
fans turn correctly, the pumps will rotate correctly. Clockwise
rotation of the pump motor cooling fans can also be used to de-
termine that pumps are rotating correctly.
Heating Operation — The chiller can be used for pump
outputs or optional factory-installed hydronic system operation
can be utilized for heating applications. The heating mode is
activated when the control sees a field-supplied closed switch
input to terminal block LVT-19,20. The control locks out cool-
ing when the heat relay input is seen. A field-supplied boiler re-
lay connection is made using heat relay and alarm relay con-
tacts. Factory-installed ‘BOILER’ connections exist in the con-
trol panel near LVT for these applications. Alarms and alerts
A189 through A202 are active during heating operation.
CAUTION
Operation of pump in wrong direction, even for a few
seconds, can cause irreversible damage to pump impeller
and housing. Always verify correct wiring/pump rotation
before operation.
Use Service Test function to test operation of pumps. Verify
that the flow switch input is made when the pump is running.
For dual pump hydronic systems, the control only uses one
pump at a time. Consult the Installation Instructions supplied
with this chiller and use the circuit setter balancing valve
installed in hydronic package to adjust fluid flow rate.
Service Test (See Table 4) — Both main power and
control circuit power must be on.
The Service Test function should be used to verify proper
operation of condenser fan(s), compressors, minimum load
valve solenoid (if installed), cooler pump(s), EXVs, and re-
mote alarm relay. To use the Service Test mode, the Enable/
Off/Remote Contact switch must be in the OFF position. Use
the display keys and Table 4 to enter the mode and display
Cooler Pump Control — The AquaSnap® 30RAP ma-
chines equipped with a factory-installed pump package are
configured with the Cooler Pump Control (Configura-
tionOPT1CPC) = ON.
Machines not equipped with a pump package are config-
ured with the cooler pump control OFF. It is recommended that
the machine control the chilled water pump. If not, a 5-minute
time delay is required after the command to shut the machine
down is sent before the chilled water pump is turned off. This is
required to maintain water flow during the shutdown period of
the machine.
With or without this option enabled, the cooler pump relay
will be energized when the machine enters an ON status (i.e.,
On Local, On CCN, On Time). An A207 - Cooler Freeze
Protection Alarm, will energize the cooler pump relay also, as
an override. The cooler pump relay will remain energized if the
machine is in MODE 10 – Minimum Off Time.
TEST. Press
twice so that OFF flashes. Enter the
ENTER
password if required. Use either arrow key to change the TEST
value to the ON position and press . Press
ENTER
ESCAPE
and the
button to enter the OUTS or COMP sub-mode.
Test the condenser fans, cooler pump(s) and alarm relay by
changing the item values from OFF to ON. These discrete
outputs are then turned off if there is no keypad activity for
10 minutes. Use the arrow keys to select the desired percentage
when testing expansion valves and Motormaster® V controller.
When testing compressors, lead compressor must be started
first. All compressor outputs can be turned on, but the control
will limit the rate by staging one compressor per minute. Com-
pressor unloaders and hot gas bypass relays/solenoids (if in-
stalled) can be tested with the compressors on or off. The relays
34
Download from Www.Somanuals.com. All Manuals Search And Download.
interlock contacts should be rated for dry circuit application
capable of handling 5 vdc at 2 mA.
SINGLE INTEGRAL PUMP CONTROL — With a single
pump, the following options must be configured:
Cooler Pump Sequence of Operation — At any-
time the unit is in an ON status, as defined by the one of the
following conditions, the cooler pump relay will be enabled.
1. The Enable-Off-Remote Switch in ENABLE,
(CTRL=0).
• Cooler Pump Control (ConfigurationOPT1CPC) =
2. Enable-Off-Remote Switch in REMOTE with
a
ON.
Start-Stop remote contact closure (CTRL=0).
• Cooler Pump
PM1E) = YES.
• Cooler Pump
PM2E) = NO.
1
2
Enable (ConfigurationOPT1
Enable (ConfigurationOPT1
3. An Occupied Time Period from an Occupancy Schedule
in combination with items 1 or 2 (CTRL=2).
4. A CCN Start-Stop Command to Start in combination
with items 1 or 2 (CTRL=3).
As stated before, there are certain alarm conditions and
Operating Modes that will turn the cooler pump relay ON. This
sequence will describe the normal operation of the pump
control algorithm.
When the unit cycles from an “On” state to an “Off” state,
the cooler pump output will remain energized for the Cooler
Pump Shutdown Delay (ConfigurationOPT1PM.DY).
This is configurable from 0 to 10 minutes. The factory default
is 1 minute.
NO INTEGRAL PUMP — SINGLE EXTERNAL PUMP
CONTROL — With a single external pump, the following
options must be configured:
With a single integral pump, the Cooler Pump Starter will
be energized when the machine is occupied. As part of the
factory-installed package, an auxiliary set of contacts is wired
to the MBB to serve as Chilled Water Pump Interlock. When
the mechanical cooling is called for, the pump interlock and
flow switch is checked. If the circuits are closed, the machine
starts its capacity routine. If the auxiliary contact interlock does
not close within 25 seconds of the ON command, a T190 —
Cooler Pump 1 Aux Contacts Failed to Close at Start-Up Alert
will be generated and the pump shut down. The unit will not
be allowed to start. If the chilled water flow switch does not
close within one (1) minute, two alarms will be generated. A
T192 — Cooler Pump 1 Failed to Provide Flow at Start-Up
Alert and an A200 — Cooler Flow/Interlock Failed to Close at
Start-Up Alarm will be generated and chiller will not be al-
lowed to start.
• Cooler Pump Control (ConfigurationOPT1CPC) =
OFF.
• Cooler Pump
PM1E) = NO.
• Cooler Pump
PM2E) = NO.
The maximum load allowed for the Chilled Water Pump
Starter is 5 VA sealed, 10 VA inrush at 24 volts. The starter coil
is powered from the chiller control system. The starter should
be wired between LVT-25 and LVT-21. If equipped, the field-
installed chilled water pump starter auxiliary contacts should
be connected in series with the chilled water flow switch.
The Cooler Pump Relay will be energized when the
machine is “On.” The chilled water pump interlock circuit
consists of a chilled water flow switch and a field-installed
chilled water pump interlock. If the chilled water pump inter-
lock circuit does not close within five (5) minutes of starting,
an A200 — Cooler Flow/Interlock Failed to Close at Start-Up
Alarm will be generated and chiller will not be allowed to start.
If the chilled water pump interlock or chilled water flow
switch opens for at least three (3) seconds after initially being
closed, an A201 — Cooler Flow/Interlock Contacts Opened
During Normal Operation Alarm will be generated and the ma-
chine will stop.
1
2
Enable (ConfigurationOPT1
Enable (ConfigurationOPT1
If the chilled water flow switch opens for at least 3 seconds
after initially being closed, a T196 — Flow Lost While Pump 1
Running Alert and an A201 — Cooler Flow/Interlock Contacts
Opened During Normal Operation Alarm will be generated
and the machine will stop.
If the control detects the chilled water pump interlock open
for 25 seconds after initially being closed, a T194 — Cooler
a30-4979
Pump 1 Contacts Opened During Normal Operation Alert is
generated and the unit is shut down.
If the control detects the chilled water flow switch circuit
closed for at least 5 minutes with the pump output OFF, an
A202 — Cooler Pump Interlock Closed When Pump is Off
Alarm will be generated and the unit will not be allowed to
start.
If the control detects that the chilled water pump auxiliary
contacts are closed for at least 25 seconds while the pump is
OFF, a T198 — Cooler Pump 1 Aux Contacts Closed While
Pump Off Alert is generated. The chiller will not be allowed to
start.
If the control starts a pump and the wrong interlock circuit
closes for at least 20 seconds, an A189 — Cooler Pump and
Aux Contact Input Miswire Alarm will be generated. The unit
will be prevented from starting.
As part of a pump maintenance routine, the pump can be
started to maintain lubrication of the pump seal. To utilize this
function, Cooler Pmp Periodic Start (ConfigurationOPT1
PM.P.S) must be set to YES. This option is set to NO as the
factory default. With this feature enabled, if the pump is not op-
erating, it will be started and operated for 2 seconds starting at
14:00 hours. If the pump is operating, this routine is skipped. If
the pump has failed and an Alarm/Alert condition is active, the
pump will not start that day.
NO INTEGRAL PUMP — DUAL EXTERNAL PUMP
CONTROL — With two external pumps, the following
options must be configured:
• Cooler Pump Control (ConfigurationOPT1CPC) =
ON.
• Cooler Pump
PM1E) = YES.
• Cooler Pump
PM2E) = YES.
1
2
Enable (ConfigurationOPT1
Enable (ConfigurationOPT1
The maximum load allowed for the Chilled Water Pump
Starters is 5 VA sealed, 10 VA inrush at 24 volts. The starter
coil is powered from the chiller control system. The starter for
Chilled Water Pump 1 should be wired between LVT-25 and
LVT-21. The starter for Chilled Water Pump 2 should be wired
between LVT-24 and LVT-21. A field-installed chilled water
pump interlock for each pump must be connected to each
pump’s interlock points on the main base board. The chilled
water pump 1 interlock, CWP1, must be connected to MBB-
J7-1 and –2. The chilled water pump 2 interlock, CWP2, must
be connected to MBB-J7-3 and –4. The chilled water pump
DUAL INTEGRAL PUMP CONTROL — With a dual inte-
gral pump package, the following options must be configured:
• Cooler Pump Control (ConfigurationOPT1CPC) =
ON.
• Cooler Pump
PM1E) = YES.
• Cooler Pump
PM2E) = YES.
1
2
Enable (ConfigurationOPT1
Enable (ConfigurationOPT1
Pump Start Selection is a field-configurable choice. Cooler
Pump Select (ConfigurationOPT1PM.SL) is factory
defaulted to 0 (Automatic). This value can be changed to 1
35
Download from Www.Somanuals.com. All Manuals Search And Download.
(Pump 1 Starts First) or 2 (Pump 2 Starts First). If PM.SL is 0
(Automatic), the pump selection is based on two criteria: the
alert status of a pump and the operational hours on the pump. If
a pump has an active Alert condition, it will not be considered
for the lead pump. The pump with the lowest operational hours
will be the lead pump. A pump is selected by the control to start
and continues to be the lead pump until the Pump Changeover
Hours (ConfigurationOPT1PM.DT) is reached. The
Lead Pump (Run StatusVIEWLD.PM) indicates the
pump that has been selected as the lead pump: 1 (Pump 1), 2
(Pump 2), 3 (No Pump). The Pump Changeover Hours is facto-
ry defaulted to 500 hours. Regardless of the Cooler Pump Se-
lection, any pump that has an active alert will not be allowed to
start.
With the dual integral pump package, the Cooler Pump
Starter will be energized when the machine is in an occupied
period. As part of the factory-installed package, an auxiliary set
of contacts is wired to the MBB to serve as Chilled Water Pump
Interlock, one set for each pump to individual channels on the
MBB. With a call for mechanical cooling, the specific pump
interlock and flow switch are checked. If the circuits are closed,
the machine starts its capacity routine. If Pump 1 starts and the
auxiliary contact interlock does not close within 25 seconds of
the ON command, a T190 — Cooler Pump 1 Aux Contacts
Failed to Close at Start-Up Alert will be generated and the
pump shut down. The unit will not be allowed to start. If the
chilled water flow switch does not close within 1 minute, two
alarms will be generated. A T192 — Cooler Pump 1 Failed to
Provide Flow at Start-Up Alert and an A200 — Cooler Flow/
Interlock Failed to Close at Start-Up Alarm will be generated
and chiller will not be allowed to start. In either fault case listed
above, Pump 2 will be commanded to start once Pump 1 has
failed.
If Pump 2 starts and the auxiliary contact interlock does
not close within 25 seconds of the ON command, a T191 —
Cooler Pump 2 Aux Contacts Failed to Close at Start-Up Alert
will be generated and the pump shut down. The unit will not be
allowed to start. If the chilled water flow switch does not close
within one (1) minute, two alarms will be generated. A T193
— Cooler Pump 2 Failed to Provide Flow at Start-Up Alert and
an A200 — Cooler Flow/Interlock Failed to Close at Start-Up
Alarm will be generated and chiller will not be allowed to start.
In either fault case listed above, Pump 1 will be commanded to
start once Pump 2 has failed.
If the chilled water flow switch opens for at least 3 seconds
after initially being closed, a T196 — Flow Lost While Pump 1
Running Alert or T197 — Flow Lost While Pump 2 Running
Alert for the appropriate pump and an A201 — Cooler Flow/
Interlock Contacts Opened During Normal Operation Alarm
will be generated and the machine will stop. If available, the
other pump will be started. If flow is proven, the machine will
be allowed to restart.
If the control starts a pump and the wrong interlock circuit
closes for at least 20 seconds, an A189 – Cooler Pump and Aux
Contact Input Miswire Alarm will be generated. The unit will
be prevented from starting.
The control will allow for pump changeover. Two methods
will change the pump sequence. Before the changeover can
occur, the unit must be at Capacity Stage 0. During changeover
the chilled water flow switch input is ignored for 10 seconds to
avoid a nuisance alarm.
With Cooler Pump Select (ConfigurationOPT1
PM.SL) set to 0 (Automatic) and when the differential time
limit Pump Changeover Hours (ConfigurationOPT1
PM.DT) is reached, the lead pump will be turned OFF. Ap-
proximately one (1) second later, the lag pump will start. Manu-
al changeover can be accomplished by changing Rotate Cooler
Pump Now (ConfigurationOPT1ROT.P) to YES only if
the machine is at Capacity Stage 0 and the differential time limit
Pump Changeover Hours (PM.DT) is reached. If the PM.DT is
not satisfied, the changeover will not occur. With the machine at
Capacity Stage 0, the pumps would rotate automatically as part
of the normal routine.
With Cooler Pump Select (PM.SL) set to 1 (Pump 1 Starts
First) or 2 (Pump 2 Starts First), a manual changeover can be ac-
complished by changing PM.SL only. The machine Remote-
Off-Enable Switch must be in the OFF position to change this
variable. The Rotate Cooler Pump Now (ROT.P) feature does
not work for these configuration options.
As part of a pump maintenance routine, the pumps can be
started to maintain lubrication to the pump seal. To utilize this
function, Cooler Pmp Periodic Start (ConfigurationOPT1
PM.PS) must be set to YES. This option is set to NO as the
factory default. If feature is enabled and the pump(s) are not
operating, then the pumps will be operated every other day for
2 seconds starting at 14:00 hours. If a pump has failed and has
an active Alert condition, it will not be started that day.
Configuring and Operating Dual Chiller Con-
trol — The dual chiller routine is available for the control of
two units supplying chilled fluid on a common loop. This
control algorithm is designed for parallel fluid flow arrangement
only. One chiller must be configured as the master chiller, the
other as the slave. An additional leaving fluid temperature
thermistor (Dual Chiller LWT) must be installed as shown in
Fig. 16 and 17 and connected to the master chiller. Refer to Sen-
sors section, page 20, for wiring. The CCN communication bus
must be connected between the two chillers. Connections can be
made to the CCN screw terminals on LVT. Refer to Carrier
Comfort Network® Interface section, page 19, for wiring infor-
mation. Configuration examples are shown in Tables 22 and 23.
Refer to Table 22 for dual chiller configuration. In this
example the master chiller will be configured at address 1 and
the slave chiller at address 2. The master and slave chillers
must reside on the same CCN bus (ConfigurationCCN
CCNB) but cannot have the same CCN address (Configu-
rationCCNCCNA). Both master and slave chillers must
have Lead/Lag Chiller Enable (ConfigurationRSET
LLEN) configured to ENBL. Master/Slave Select (Config-
urationRSET MSSL) must be configured to MAST for
the master chiller and SLVE for the slave. Also in this example,
the master chiller will be configured to use Lead/Lag Balance
Select (ConfigurationRSETLLBL) and Lead/Lag Bal-
ance Delta (ConfigurationRSETLLBD) to even out the
chiller run-times weekly. The Lag Start Delay (Configura-
tionRSETLLDY) feature will be set to 10 minutes. This
will prevent the lag chiller from starting until the lead chiller
has been at 100% capacity for the length of the delay time. Par-
allel configuration (ConfigurationRSETPARA) can
only be configured to YES. The variables LLBL, LLBD and
LLDY are not used by the slave chiller.
If the chilled water pump interlock opens for 25 seconds
after initially being closed is detected by the control, the appro-
priate T194 — Cooler Pump 1 Contacts Opened During Nor-
mal Operation Alert or T195 — Cooler Pump 2 Contacts
Opened During Normal Operation Alert is generated and the
unit is shut down. If available, the other pump will be started. If
flow is proven, the machine will be allowed to restart.
If the control detects that the chilled water flow switch
circuit is closed for at least 5 minutes with the pump output
OFF, an A202 — Cooler Pump Interlock Closed When Pump
is Off Alarm will be generated and the unit will not be allowed
to start.
If the control detects that the chilled water pump auxiliary
contacts are closed for at least 25 seconds while the pump is
OFF, the appropriate T198 — Cooler Pump 1 Aux Contacts
Closed While Pump Off or Alert T199 — Cooler Pump 2 Aux
Contacts Closed While Pump Off Alert is generated. The
chiller will not be allowed to start.
36
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 22 — Dual Chiller Configuration (Master Chiller Example)
SUB-MODE
DISP
ITEM
KEYPAD ENTRY
DISPLAY
ITEM EXPANSION
COMMENTS
UNIT
OPT1
ENTER
ENTER
ESCAPE
CTRL
0
CONTROL METHOD
SWITCH
OPT2
CTRL
DEFAULT 0
OPT2
CCN
1
CCNA
CCNB
ENTER
CCN ADDRESS
DEFAULT 1
DEFAULT 0
CCNB
0
CCN
ENTER
CCN BUS NUMBER
ESCAPE
CCN
RSET
CRST
LLEN
DSBL
DSBL
ENBL
ENBL
LLEN
MSSL
MAST
MSSL
SLVA
0
PROCEED TO
SUBMODE RESET
ENTER
COOLING RESET TYPE
LEAD/LAG CHILLER ENABLE
15 ITEMS
SCROLLING STOPS
VALUE FLASHES
SELECT ENBL
LLEN
LLEN
MSSL
SLVA
SLVA
LLBL
ENTER
ENTER
ENTER
LEAD/LAG CHILLER ENABLE
CHANGE ACCEPTED
ESCAPE
MASTER /SLAVE SELECT
MASTER /SLAVE SELECT
ENTER
DEFAULT MAST
ESCAPE
RSET
SLAVE ADDRESS
ENTER
ENTER
SCROLLING STOPS
VALUE FLASHES
SELECT 2
0
2
ENTER
2
SLAVE ADDRESS
CHANGE ACCEPTED
ESCAPE
SLVA
LLBL
0
LEAD/LAG BALANCE SELECT
ENTER
ENTER
SCROLLING STOPS
VALUE FLASHES
0
2
SELECT 2 - Automatic
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 22 — Dual Chiller Configuration (Master Chiller Example) (cont)
SUB-MODE
ITEM
KEYPAD ENTRY
DISPLAY
ITEM EXPANSION
COMMENTS
LLBL
ENTER
2
LEAD/LAG BALANCE SELECT
CHANGE ACCEPTED
ESCAPE
LLBL
LLBD
168
LLBD
LLDY
5
LEAD/LAG BALANCE DELTA
LEAD/LAG BALANCE DELTA
LLBD
LLDY
LLDY
PARA
ENTER
DEFAULT 168
ESCAPE
LAG START DELAY
RSET
ENTER
ENTER
SCROLLING STOPS
VALUE FLASHES
SELECT 10
5
10
ENTER
ESCAPE
ESCAPE
ENTER
10
LAG START DELAY
CHANGE ACCEPTED
LLDY
RSET
YES
MASTER COMPLETE
NOTES:
1. Master Control Method (CTRL) can be configured as 0-Switch, 2-Occupancy or 3-CCN.
2. Parallel Configuration (PARA) cannot be changed.
Dual chiller start/stop control is determined by configura-
tion of Control Method (ConfigurationOPT1CTRL) of
the Master chiller. The Slave chiller should always be config-
ured for CTRL=0 (Switch). If the chillers are to be controlled
by Remote Contacts, both Master and Slave chillers should be
enabled together. Two separate relays or one relay with
two sets of contacts may control the chillers. The Enable/Off/
Remote Contact switch should be in the Remote Contact
position on both the Master and Slave chillers. The Enable/Off/
Remote Contact switch should be in the Enable position for
CTRL=2 (Occupancy) or CTRL=3 (CCN Control).
DIMENSIONS in. (mm)
PART
NUMBER
A
B
10HB50106801
10HB50106802
3.10 (78.7)
4.10 (104.1)
1.55 (39.4)
1.28 (32.5)
A
0.505/0.495
0.61
DIA
B
Both chillers will stop if the Master chiller Enable/Off/
Remote Contact switch is in the Off position. If the Emergency
Stop switch is turned off or an alarm is generated on the Master
chiller the Slave chiller will operate in a Stand-Alone mode.
If the Emergency Stop switch is turned off or an alarm is
generated on the Slave chiller the Master chiller will operate in
a Stand-Alone mode.
The master chiller controls the slave chiller by changing its
Control Mode (Run StatusVIEWSTAT) and its operat-
ing setpoint or Control Point (Run StatusVIEWCT.PT).
6” MINIMUM
CLEARANCE FOR
THERMISTOR
REMOVAL
1/4 N.P.T.
Fig. 17 — Dual Leaving Water Thermistor Well
Temperature Reset — The control system is capable of
handling leaving-fluid temperature reset based on return cooler
fluid temperature. Because the change in temperature through
the cooler is a measure of the building load, the return tempera-
ture reset is in effect an average building load reset method.
The control system is also capable of temperature reset based
on outdoor-air temperature (OAT), space temperature (SPT), or
from an externally powered 4 to 20 mA signal. Accessory sen-
sors must be used for SPT reset (33ZCT55SPT). The energy
management module (EMM) must be used for temperature
reset using a 4 to 20 mA signal. See Tables 24 and 25.
THERMISTOR
WIRING*
LEAVING
FLUID
MASTER
CHILLER
RETURN
FLUID
SLAVE
CHILLER
INSTALL DUAL CHILLER LWT
LEAVING FLUID TEMPERATURE
THERMISTOR (T10) HERE
*Depending on piping sizes, use either:
• HH79NZ014 sensor/10HB50106801 well (3-in. sensor/well)
• HH79NZ029 sensor/10HB50106802 well (4-in. sensor/well)
Fig. 16 — Dual Chiller Thermistor Location
38
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 23 — Dual Chiller Configuration (Slave Chiller Example)
SUB-MODE
DISP
ITEM
KEYPAD ENTRY
DISPLAY
ITEM EXPANSION
COMMENTS
UNIT
OPT1
ENTER
CTRL
0
CONTROL METHOD
SWITCH
OPT2
CTRL
DEFAULT 0
ESCAPE
OPT2
CCN
CCNA
1
CCNA
ENTER
ENTER
CCN ADDRESS
SCROLLING STOPS
VALUE FLASHES
1
SELECT 2
(SEE NOTE 1)
2
CCN
CCNA
CCNB
ENTER
ESCAPE
ENTER
2
CCN ADDRESS
CHANGE ACCEPTED
CCN
0
DEFAULT 0
(SEE NOTE 2)
CCN BUS NUMBER
ESCAPE
CCN
RSET
CRST
LLEN
DSBL
DSBL
ENBL
ENBL
LLEN
MSSL
MAST
MAST
SLVE
SLVE
MSSL
RSET
PROCEED TO
SUBMODE RSET
ENTER
COOLING RESET TYPE
LEAD/LAG CHILLER ENABLE
15 ITEMS
SCROLLING STOPS
VALUE FLASHES
SELECT ENBL
LLEN
LLEN
MSSL
MSSL
ENTER
ENTER
ENTER
LEAD/LAG CHILLER ENABLE
MASTER /SLAVE SELECT
CHANGE ACCEPTED
ESCAPE
RSET
ENTER
ENTER
SCROLLING STOPS
VALUE FLASHES
SELECT SLVE
ENTER
ESCAPE
ESCAPE
MASTER /SLAVE SELECT
CHANGE ACCEPTED
SLAVE COMPLETE
NOTES:
1. Slave Control Method (CTRL) must be configured for 0.
2. Slave CCN Address (CCNA) must be different than Master.
3. Slave CCN Bus Number (CCNB) must be the same as Master
4. Slave does not require SLVA, LLBL, LLBD, or LLDY to be configured.
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 24 — 4 to 20 mA Reset
KEYPAD
ENTRY
ITEM
DISPLAY
SUB-MODE
RSET
ITEM
COMMENT
EXPANSION
0 = no reset
1 = 4 to 20 mA input
2 = Outdoor air temp
3 = Return Fluid
COOLING RESET
ENTER
CRST
1
TYPE
4 = Space Temperature
5.0 F
(2.8 C)
DEGREES COOL
RESET
Default: 0° F (0° C) Reset at 20 mA
Range: –30 to 30 F (–16.7 to 16.7 C)
MA.DG
NOTE: The example above shows how to configure the chiller for 4 to 20 mA reset. No reset will
occur at 4.0 mA input, and a 5.0 F reset will occur at 20.0 mA. An EMM is required.
Table 25 — Menu Configuration of 4 to 20 mA Cooling Set Point Control
MODE
(RED LED)
KEYPAD
ENTRY
KEYPAD
ENTRY
ITEM
EXPANSION
SUB-MODE
DISP
ITEM
DISPLAY
COMMENT
ENTER
UNIT
OPT1
OPT2
HP.A
HP.B
EXV.A
EXV.B
M.MST
RSET
DMDC
SLCT
CONFIGURATION
ENTER
ENTER
ENTER
CLSP
0
0
0
4
4
COOLING SETPOINT SELECT
Scrolling Stops
Flashing ‘0’
Select ‘4’
ENTER
Change Accepted
be configured for the type of reset desired. The variable
RM.NO should be set to the temperature that no reset should
occur. The variable RM.F should be set to the temperature that
maximum reset is to occur. The variable RM.DG should be set
to the maximum amount of reset desired. Figures 18 and 19 are
examples of outdoor air and space temperature resets.
To use return reset, four variables must be configured. In the
Configuration mode under the sub-mode RSET, items CRST,
RT.NO, RT.F and RT.DG must be properly set. See Table 26B
— Configuring Return Temperature Reset. This example pro-
vides 5.0 F (2.8 C) chilled water set point reset at 2.0 F (1.1 C)
cooler T and 0° F (0° C) reset at 10.0 F (5.6 C) cooler T. The
variable RT.NO should be set to the cooler temperature differ-
ence (T) where no chilled water temperature reset should oc-
cur. The variable RT.F should be set to the cooler temperature
difference where the maximum chilled water temperature reset
should occur. The variable RM.DG should be set to the maxi-
mum amount of reset desired.
IMPORTANT: Care should be taken when interfacing with
other control systems due to possible power supply differ-
ences: full wave bridge versus half wave rectification. Con-
nection of control devices with different power supplies
may result in permanent damage. ComfortLink™ controls
incorporate power supplies with half wave rectification. A
signal isolation device should be utilized if the signal gen-
erator incorporates a full wave bridge rectifier.
To use outdoor air or space temperature reset, four variables
must be configured. In the Configuration mode under the sub-
mode RSET, items (ConfigurationOPT1CRST), (Con-
figurationOPT1RM.NO),
(ConfigurationOPT1
RM.F), and (ConfigurationOPT1RT.DG) must be
properly set. See Table 26A — Configuring Outdoor Air and
Space Temperature Reset. The outdoor air reset example pro-
vides 0° F (0° C) chilled water set point reset at 85.0 F (29.4 C)
outdoor-air temperature and 15.0 F (8.3 C) reset at 55.0 F
(12.8 C) outdoor-air temperature. The space temperature reset
example provides 0° F (0° C) chilled water set point reset at
72.0 F (22.2 C) space temperature and 6.0 F (3.3 C) reset at
68.0 F (20.0 C) space temperature. The variable CRST should
To verify that reset is functioning correctly proceed to Run
Status mode, sub-mode VIEW, and subtract the active set point
(Run StatusVIEWSETP) from the control point (Run
StatusVIEWCTPT) to determine the degrees reset.
40
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 26A — Configuring Outdoor Air and Space Temperature Reset
DISPLAY
MODE
(RED LED)
KEYPAD
ENTRY
SUB-
MODE
KEYPAD
ENTRY
ITEM
EXPANSION
ITEM
COMMENT
Outdoor
Air
Space
ENTER
DISP
UNIT
OPT1
OPT2
HP.A
HP.B
EXV.A
EXV.B
M.MST
CONFIGURATION
2 = Outdoor-Air Temperature
4 = Space Temperature
(Connect to TB5-5,6)
COOLING RESET
TYPE
RSET
CRST
2
4
ENTER
REMOTE - NO
RESET TEMP
Default: 125.0 F (51.7 C)
Range: 0° to125 F
RM.NO*
RM.F
85 °F
55 °F
72 °F
68 °F
REMOTE - FULL
RESET TEMP
Default: 0.0° F (-17.7 C)
Range: 0° to 125 F
Default: 0° F (0° C)
Range: –30 to 30 F
(–34.4 to -1.1 °C)
REMOTE - DEGREES
RESET
RM.DG
15 °F
6 °F
*4 items skipped in this example.
Table 26B — Configuring Return Temperature Reset
MODE
(RED LED)
KEYPAD
ENTRY
KEYPAD
ENTRY
ITEM
SUB-MODE
DISP
ITEM DISPLAY
COMMENT
EXPANSION
ENTER
ENTER
ENTER
ENTER
ENTER
TEST
TYPE
FLUD
CTRL
ON/OFF
TEST DISPLAY LEDs
UNIT TYPE
UNIT
X
X
X
OPT1
OPT2
HP.A
COOLER FLUID
CONTROL METHOD
HP.B
EXV.A
EXV.B
M.MST
CONFIGURATION
0 = No Reset
1 = 4 to 20 mA Input (EMM required)
(Connect to EMM TB6-2,3)
RSET
CRST
3
COOLING RESET TYPE 2 = Outdoor-Air Temperature
3 = Return Fluid
ENTER
4 = Space Temperature
(Connect to TB5-5,6)
RETURN FLUID - NO
RESET TEMP
Default: 10.0 F (5.6 C)
Range: 0° to10 F COOLER T
RT.NO* 10.0 F
RETURN FLUID - FULL Default: 0 F (–17.8 C)
RT.F
0.0 F
RESET TEMP
Range: 0° to 30 F COOLER T
RETURN - DEGREES
RESET
Default: 0 F (0 C)
Range: –30 to 30°F (–16.7 to 16.7 C)
RT.DG
10.0 F
*4 items skipped in this example.
41
Download from Www.Somanuals.com. All Manuals Search And Download.
Under normal operation, the chiller will maintain a constant
leaving fluid temperature approximately equal to the chilled
fluid set point. As the cooler load varies, the entering cooler
fluid will change in proportion to the load as shown in Fig. 20.
Usually the chiller size and leaving-fluid temperature set point
are selected based on a full-load condition. At part load, the flu-
id temperature set point may be colder than required. If the
leaving fluid temperature was allowed to increase at part load,
the efficiency of the machine would increase.
Return temperature reset allows for the leaving temperature
set point to be reset upward as a function of the return fluid
temperature or, in effect, the building load.
Demand Limit — Demand limit is a feature that allows
the unit capacity to be limited during periods of peak energy us-
age. There are 3 types of demand limiting that can be config-
ured. The first type is through 2-stage switch control, which will
reduce the maximum capacity to 2 user-configurable percentag-
es. The second type is by 4 to 20 mA signal input which will re-
duce the maximum capacity linearly between 100% at a 4 mA
input signal (no reduction) down to the user-configurable level
at a 20 mA input signal. The third type uses the CCN Loadshed
module and has the ability to limit the current operating capaci-
ty to maximum and further reduce the capacity if required.
LEGEND
EWT — Entering Water (Fluid) Temperature
LWT
—
Leaving Water (Fluid) Temperature
Fig. 20 — Standard Chilled Fluid
Temperature Control — No Reset
To use demand limit, select the type of demand limiting to
use. Then configure the demand limit set points based on the
type selected.
NOTE: The 2-stage switch control and 4 to 20-mA input sig-
nal types of demand limiting require the energy management
module (EMM).
DEMAND LIMIT (2-Stage Switch Controlled) — To con-
figure demand limit for 2-stage switch control set the Demand
Limit Select (ConfigurationRSETDMDC) to 1. Then
configure the 2 Demand Limit Switch points (Configura-
tionRSETDLS1) and (ConfigurationRSETDLS2)
to the desired capacity limit. See Table 27. Capacity steps are
controlled by 2 relay switch inputs field wired to TB6 as shown
in Fig. 6 and 7.
For demand limit by 2-stage switch control, closing the first
stage demand limit contact will put the unit on the first demand
limit level. The unit will not exceed the percentage of capacity
entered as Demand Limit Switch 1 set point (DLS1). Closing
contacts on the second demand limit switch prevents the unit
from exceeding the capacity entered as Demand Limit Switch
2 set point. The demand limit stage that is set to the lowest de-
mand takes priority if both demand limit inputs are closed. If
the demand limit percentage does not match unit staging, the
unit will limit capacity to the closest capacity stage.
LEGEND
To disable demand limit configure DMDC to 0. See
Table 27.
LWT — Leaving Water (Fluid) Temperature
Fig. 18 — Outdoor-Air Temperature Reset
EXTERNALLY POWERED DEMAND LIMIT (4 to
20 mA Controlled) — To configure demand limit for 4 to 20
mA control set the Demand Limit Select (Configura-
tionRSETDMDC) to 2. Then configure the Demand
Limit at 20 mA (ConfigurationRSETDM20) to the
maximum loadshed value desired. Connect the output from an
externally powered 4 to 20 mA signal to terminal block TB6,
terminals 1 and 5. Refer to the unit wiring diagram for these
connections to the optional/accessory energy management
module and terminal block. The control will reduce allowable
capacity to this level for the 20 mA signal. See Table 27 and
Fig. 21.
CAUTION
Care should be taken when interfacing with other manufac-
turer’s control systems, due to possible power supply
differences, full wave bridge versus half wave rectification.
The two different power supplies cannot be mixed.
ComfortLink™ controls use half wave rectification. A sig-
nal isolation device should be utilized if a full wave bridge
signal generating device is used.
LEGEND
LWT — Leaving Water (Fluid) Temperature
Fig. 19 — Space Temperature Reset
42
Download from Www.Somanuals.com. All Manuals Search And Download.
DEMAND LIMIT (CCN Loadshed Controlled) — To con-
figure Demand Limit for CCN Loadshed control set the De-
mand Limit Select (ConfigurationRSETDMDC) to 3.
Then configure the Loadshed Group Number (Configura-
tionRSETSHNM), Loadshed Demand Delta (Configu-
rationRSETSHDL), and Maximum Loadshed Time
(ConfigurationRSETSHTM). See Table 27.
The Loadshed Group number is established by the CCN
system designer. The ComfortLink controls will respond to a
Redline command from the Loadshed control. When the
Redline command is received, the current stage of capacity is
set to the maximum stages available. Should the loadshed con-
trol send a Loadshed command, the ComfortLink controls will
reduce the current stages by the value entered for Loadshed
Demand delta. The Maximum Loadshed Time is the maximum
length of time that a loadshed condition is allowed to exist. The
control will disable the Redline/Loadshed command if no
Cancel command has been received within the configured
maximum loadshed time limit.
Cooling Set Point (4 to 20 mA) — A field supplied
and generated, externally powered 4 to 20 mA signal can be
used to provide the leaving fluid temperature set point. Connect
the signal to LVT7,8 (+,–). See Table 27 for instructions to
enable the function. Figure 22 shows how the 4 to 20 mA sig-
nal is linearly calculated on an overall 10 F to 80 F range for
fluid types (ConfigurationOPT1FLUD) 1 or 2. The set
point will be limited by the fluid (FLUD) type. Be sure that the
chilled water loop is protected at the lowest temperature.
100
50% CAPACITY AT 20 mA
80
60
100% CAPACITY AT 4 mA
40
75% CAPACITY AT 12 mA
20
0
0
2
6
8
12
16
18
4
20
10
14
DEMAND LIMIT SIGNAL – 4 - 20 mA INPUT
Fig. 21 — 4 to 20-mA Demand Limiting
100
(38)
90
(32)
80
(27)
70
(21)
MAXIMUM
SET POINT
70 F (21.1 C)
60
(15)
50
(10)
40
(4.4)
(FLUD = 1) MINIMUM
SET POINT 38 F (3.3 C)
30
(-1)
20
(-7)
(FLUD = 2) MINIMUM
SET POINT 14 F (-10 C)
10
(-12)
0
(-17)
4
6.3
8.6
10.9
13.1
15.4
17.7
20
4 TO 20 mA SIGNAL TO EMM
EMM — Energy Management Module
Fig. 22 — Cooling Set Point (4 to 20 mA)
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 27 — Configuring Demand Limit
KEYPAD
ENTRY
KEYPAD
MODE
SUB-MODE
DISP
ITEM
TEST
TYPE
FLUD
CTRL
DISPLAY
ITEM EXPANSION
Test Display LEDs
Unit Type
COMMENT
ENTRY
CONFIGURATION
ENTER
ENTER
ON/OFF
ENTER
ENTER
ENTER
UNIT
X
X
X
OPT1
Cooler Fluid
OPT2
Control Method
HP.A
HP.B
EXV.A
EXV.B
M.MST
RSET
ENTER
CRST
X
X
Cooling Reset Type
Demand Limit Select
Demand Limit at 20 mA
Default: 0
0 = None
DMDC*
1 = Switch
2 = 4 to 20 mA Input
3 = CCN Loadshed
Default: 100%
Range: 0 to 100
DM20
SHNM
SHDL
SHTM
DLS1
DLS2
XXX %
XXX
Loadshed Group
Number
Default: 0
Range: 0 to 99
Loadshed Demand
Delta
Default: 0%
Range: 0 to 60%
XXX%
XXX MIN
XXX %
XXX %
Maximum Loadshed
Time
Default: 60 min.
Range: 0 to 120 min.
Demand Limit
Switch 1
Default: 80%
Range: 0 to 100%
Demand Limit
Switch 2
Default: 50%
Range: 0 to 100%
*Seven items skipped in this example.
(DTT) is installed along with the AUX board for control of the
DUS.
Digital Scroll Option — The 30RAP units have a
factory-installed option for a digital scroll compressor which
provides additional stages of unloading for the unit. The digital
compressor is always installed in the A1 compressor location.
When a digital compressor is installed, a digital unloader sole-
noid (DUS) is used on the digital compressor.
DIGITAL SCROLL OPERATION — A digital scroll oper-
ates in two stages - the "loaded state" when the solenoid valve
is normally closed and the "unloaded state" when the solenoid
valve is open. During the loaded state, the compressor operates
like a standard scroll and delivers full capacity and mass flow.
DIGITAL COMPRESSOR CONFIGURATION — When a
digital compressor is installed, the configuration parameter
(ConfigurationUNITA1TY) is configured to YES.
There is also a maximum unload time configuration, (Config-
urationUNITMAX.T) that is set to 7 seconds, which in-
dicates the maximum unloading for the digital compressor is
47%. This is done to optimize efficiency of the system.
PRE-START-UP
However, during the unloaded state, there is no capacity
and no mass flow through the compressor. The capacity of the
system is varied by varying the time the compressor operates
in an unloaded and loaded state during a 15-second period. If
the DUS is energized for 7 seconds, the compressor will be
operating at 47% capacity. If the DUS is energized for 10 sec-
onds, the compressor will be operating at approximately 33%
of its capacity. Capacity is the time averaged summation of
loaded and unloaded states, and its range is continuous from
the minimum configured capacity to 100%. Regardless of
capacity, the compressor always rotates with constant speed.
As the compressor transitions from a loaded to unloaded state,
the discharge and suction pressures will fluctuate and the com-
pressor sound will change.
IMPORTANT: Before beginning Pre-Start-Up or Start-Up,
complete Start-Up Checklist for 30RAP Liquid Chiller at
end of this publication (pages CL-1 to CL-10). The check-
list assures proper start-up of a unit, and provides a record
of unit condition, application requirements, system infor-
mation, and operation at initial start-up.
Do not attempt to start the chiller until following checks
have been completed.
System Check
1. Check all auxiliary components, such as chilled fluid
pumps, air-handling equipment, or other equipment to
which the chiller supplies liquid. Consult manufacturer's
instructions. Verify that any pump interlock contacts have
been properly installed. If the unit If the unit has
field-installed accessories, be sure all are properly in-
stalled and wired correctly. Refer to unit wiring diagrams.
The ComfortLink controller controls and integrates the op-
eration of the DUS into the compressor staging routine to
maintain temperature control. When a digital compressor is in-
stalled, an additional discharge gas temperature thermistor
44
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Use the scrolling marquee display to adjust the Cooling
Set Point.
START-UP AND OPERATION
NOTE: Refer to Start-Up Checklist on pages CL-1 to CL-10.
3. Fill chilled fluid circuit with clean water (with recom-
mended inhibitor added) or other non-corrosive fluid to
be cooled. Bleed all air out of the high points of the sys-
tem. If chilled water is to be maintained at a temperature
below 40 F (4.4 C) or outdoor temperatures are expected
to be below 32 F (0° C), a brine of sufficient concentra-
tion must be used to prevent freeze-up at anticipated
suction temperatures. See Table 28.
Actual Start-Up — Actual start-up should be done only
under supervision of a qualified refrigeration mechanic.
1. Be sure all service valves are open.
2. Using the scrolling marquee display, set leaving-fluid set
point (Set PointsCOOLCSP.1). No cooling range
adjustment is necessary.
3. Start chilled fluid pump (if not configured for cooler
pump control).
4. Check tightness of all electrical connections.
5. Oil should be visible in the compressor sightglass(es).
See Fig. 23. An acceptable oil level in the compressors is
4. Turn ENABLE/OFF/REMOTE CONTACT switch to
ENABLE position.
1
3
from /8 to /8 of sight glass. Adjust the oil level as re-
quired. See Oil Charge section on page 50 for Carrier ap-
proved oils.
5. Allow unit to operate and confirm that everything is func-
tioning properly. Check to see that leaving fluid tempera-
ture agrees with leaving set point (Set PointsCOOL
CSP.1) or (Set PointsCOOLCSP.2), or if reset is
used, with the control point (Run StatusVIEW
CTPT).
6. Check the cooler leaving chilled water temperature to see
that it remains well above 32 F (0° C), or the brine freez-
ing point if the unit is a medium temperature brine unit.
6. Electrical power source must agree with unit nameplate.
7. All condenser fan and factory installed hydronic package
pump motors are three phase. Check for proper rotation
of condenser fans first BEFORE attempting to start
pumps or compressors. To reverse rotation, interchange
any two of the main incoming power leads.
8. Be sure system is fully charged with refrigerant (see
Check Refrigerant Charge section on this page).
7. Recheck compressor oil level (see Oil Charge section).
9. If unit is a brine unit, check to ensure proper brine con-
centration is used to prevent freezing.
Check Refrigerant Charge — All 30RAP units are
shipped with a complete operating charge of R-410A and
should be under sufficient pressure to conduct a leak test after
installation. If there is no system pressure, admit nitrogen until
a pressure is observed and then proceed to test for leaks. After
leaks are repaired, the system must be dehydrated.
10. Verify proper operation of cooler and hydronic package
heaters (if installed). Heaters operate at the same voltage
as the main incoming power supply and are single phase.
Heater current is approximately 0.4 amps for 460 and
575 v units. Heater current is approximately 0.8 amps for
230 v units.
All refrigerant charging should be done through the ¼-in.
Schraeder connection on the liquid line. Do NOT add refriger-
ant charge through the low-pressure side of the system. If com-
plete charging is required, weigh in the appropriate charge for
the circuit as shown on the unit nameplate. If partial charging is
required, operate circuit at full load and use an accurate tem-
perature sensor on the liquid line as it enters the EXV. Use the
Temperatures mode on the scrolling marquee display to show
the circuit saturated condensing temperature (Tempera-
a30-4978
turesCIR.ASCT.A)
or
(TemperaturesCIR.B
SCT.B). Charging is most accurate at saturated discharge
temperatures of 120 to 125 F (49 to 52 C). Block condenser air-
flow as required to reach this temperature range. Add refriger-
ant until the system subcooling (SCT.A or SCT.B minus liquid
line temperature entering EXV) is approximately 15 to 17 F
(–9.4 to –8.3 C). Refrigerant VAPOR only may be added to a
circuit through the 1/4-in. suction Schraeder connection on the
suction line.
OIL SIGHTGLASS
Fig. 23 — Sight Glass Location
Table 28 — Minimum Cooler Flow Rates and Minimum Loop Volume
30RAP
SIZE
MINIMUM COOLER FLOW MAXIMUM COOLER FLOW MINIMUM COOLER FLOW MAXIMUM COOLER FLOW
RATE (gpm)
RATE (gpm)
50
RATE (l/s)
0.8
RATE (l/s)
3.2
010
015
018
020
025
030
035
040
045
050
055
060
13
17
20
23
28
33
41
47
53
57
63
68
66
78
91
1.1
1.3
1.5
1.8
2.1
2.6
3.0
3.3
4.2
4.9
5.7
7.1
112
133
164
186
209
228
251
270
8.4
10.3
11.7
13.2
14.4
15.8
17.0
3.6
4.0
4.3
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Unbalanced 3-Phase Supply Voltage — Never operate a motor
where a phase imbalance between phases is greater than 2%.
To determine percent voltage imbalance:
CAUTION
max voltage deviation
Never charge liquid into low-pressure side of system. Do
not overcharge. Overcharging results in higher discharge
pressure, possible compressor damage, and higher power
consumption. During charging or removal of refrigerant, be
sure water is continuously circulating through the cooler to
prevent freezing.
from avg voltage
% Voltage Imbalance = 100 x
average voltage
The maximum voltage deviation is the largest difference
between a voltage measurement across 2 legs and the average
across all 3 legs.
Example: Supply voltage is 240-3-60.
AB = 243 v
Operating Limitations
TEMPERATURES (See Table 29 for 30RAP standard tem-
perature limits).
BC = 236 v
AC = 238 v
CAUTION
1. Determine average voltage:
Do not operate with cooler leaving chiller water (fluid)
temperature (LCWT) below 40 F (4.4 C) for the standard
units, or below 15 F (–9.4 C) for units factory built for
medium temperature brine.
243 + 236 + 238
Averagevoltage =
3
717
=
3
High Cooler Leaving Chilled Water (Fluid) Temperatures
(LCWT) — During start-up with cooler LCWT above approx-
imately 60 F (16 C), the unit expansion valve will limit suction
pressure to approximately 90 psig (620 kPa) to avoid overload-
ing the compressor.
Low Cooler LCWT — For standard units, the LCWT must be
no lower than 40 F (4.4 C). If the unit is the factory-installed
optional medium temperature brine unit, the cooler LCWT can
go down to 15 F (–9.4 C).
= 239
2. Determine maximum deviation from average voltage:
(AB) 243 – 239 = 4 v
(BC) 239 – 236 = 3 v
(AC) 239 – 238 = 1 v
Maximum deviation is 4 v.
3. Determine percent voltage imbalance:
Table 29 — Temperature Limits for
Standard 30RAP Units
4
% Voltage Imbalance = 100 x
239
UNIT SIZE 30RA
Temperature
010-030
035-060
= 1.7%
F
C
F
C
This voltage imbalance is satisfactory as it is below the
maximum allowable of 2%.
Maximum Ambient
Temperature
Minimum Ambient
Temperature
Maximum Cooler EWT*
Maximum Cooler LWT
Minimum Cooler LWT†
120
45
49
120
32
49
7
0
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately. Do not operate unit until imbalance condition
is corrected.
95
70
40
35
21
4.4
95
70
40
35
21
4.4
LEGEND
Entering Fluid (Water) Temperature
LWT — Leaving Fluid (Water) Temperature
Control Circuit Power — Power for the control circuit is
supplied from the main incoming power through a factory-
installed control power transformer (TRAN1) for all models.
Field wiring connections are made to the LVT.
EWT
—
*For sustained operation, EWT should not exceed 85 F (29.4 C).
†Unit requires modification below this temperature.
LOW-AMBIENT OPERATION — If operating temperatures
below 45 F (7 C) on size 018-030 units, and 32 F (0° C) on size
035-060 units are expected, accessory Motormaster® V con-
trol must be installed. Operating temperatures can go as low as
–20 F (–29 C) on size 010 and 015 units, as standard. Installa-
tion of wind baffles is also required. Refer to separate installa-
tion instructions for operation using this accessory. Contact
your Carrier representative for details.
OPERATION SEQUENCE
During unit off cycle, the control monitors the outdoor air
temperature. If the ambient temperature drops below 40 F
(4.4 C), cooler and hydronic system heaters (if either are facto-
ry installed) are energized. If power is maintained to the chiller
and the EMERGENCY ON/OFF switch is left in the OFF po-
sition, these heaters are also energized.
The unit is started by putting the ENABLE/OFF/REMOTE
CONTACT switch in the ENABLE or REMOTE CONTACT
position. When the unit receives a call for cooling (either from
the internal control or CCN network command or remote con-
tact closure), the unit stages up in capacity to maintain the leav-
ing fluid set point. The first compressor starts 11/2 to 3 minutes
after the call for cooling.
CAUTION
Brine duty application (below 40 F [4.4 C] LCWT) for
chiller normally requires factory modification. Contact
your Carrier representative for applicable LCWT range for
standard water-cooled chiller in a specific application.
The lead circuit can be specifically designated on all models
or selected based on compressor run hours and starts depend-
ing on field configuration. The unit control will override this
selection under certain starting conditions to properly maintain
oil return to the compressors. In general, on dual compressor
VOLTAGE — ALL UNITS
Main Power Supply — Minimum and maximum acceptable
supply voltages are listed in the Installation Instructions.
46
Download from Www.Somanuals.com. All Manuals Search And Download.
circuits, the control will most often start the A1 or B1 compres-
sor first, especially after long off periods. The MBB controls
fan stages to maintain the head pressure set point and will auto-
matically adjust unit capacity as required to keep compressors
from operating outside of the specified envelope. There are no
pumpout or pumpdown sequences on these chillers.
For all units, if temperature reset is being used, the unit con-
trols to a higher leaving-fluid temperature as the building load
reduces. If demand limit is used, the unit may temporarily be
unable to maintain the desired leaving-fluid temperature be-
cause of imposed power limitations.
determines the saturated temperature of suction gas. The differ-
ence between the temperature of the superheated gas and the
saturated suction temperature is the superheat. The EXV board
controls the position of the electronic expansion valve stepper
motor to maintain superheat set point.
The MBB controls the superheat leaving cooler to approxi-
mately 9° F (5° C). Because EXV status is communicated to
the main base board (MBB) and is controlled by the EXV
boards, it is possible to track the valve position. The unit is then
protected against loss of charge and a faulty valve. Just prior to
compressor start, the EXV will open. At low ambient tempera-
tures the EXV is closed at start up. After initialization period,
valve position is tracked by the EXV board by constantly mon-
itoring the amount of valve movement.
SERVICE
The EXV is also used to limit cooler saturated suction tem-
perature to 50 F (10 C). This makes it possible for the chiller to
start at higher cooler fluid temperatures without overloading
the compressor. This is commonly referred to as MOP (maxi-
mum operating pressure). At ambient temperatures above
110 F, MOP is bypassed at start-up to prevent charge backup in
the condenser.
WARNING
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during service. There may
be more than one disconnect switch. Tag all disconnect
locations to alert others not to restore power until work is
completed.
If it appears that the EXV module is not properly control-
ling circuit operation to maintain correct superheat, there are a
number of checks that can be made using test functions and
initialization features built into the microprocessor control. See
the EXV Troubleshooting Procedure section to test EXVs.
Electronic Components
CONTROL COMPONENTS — Unit uses an advanced elec-
tronic control system that normally does not require service.
For details on controls refer to Operating Data section.
Access to the compressors is through latched panels from
beneath the control box on all models or from opposite the coil
side (sizes 010-030 only). The front door(s) provide access to
the compressor(s) and all components of the refrigeration sys-
tem. For size 010-030 units, access to the controls is through
the upper latched outer door above the compressor access door.
Similarly, the upper center latched door on sizes 035-060 gives
access to the controls. Inner panels are secured in place and
should not be removed unless all power to the chiller is off.
EXV Troubleshooting Procedure — Follow steps
below to diagnose and correct EXV/economizer problems.
Check EXV motor operation first. Switch the Enable/Off/
ESCAPE
Remote Contact (EOR) switch to the Off position. Press
on the Navigator™ display until ‘Select a menu item’ appears
on the display. Use the arrow keys to select the Service Test
ENTER
mode. Press
. The display will be:
> TEST
OFF
Electronic Expansion Valve (EXV) — See Fig. 24
for a cutaway view of the EXV. High-pressure liquid refriger-
ant enters valve through the top. As refrigerant passes through
the orifice, pressure drops and refrigerant changes to a 2-phase
condition (liquid and vapor). The electronic expansion valve
operates through an electronically controlled activation of a
stepper motor. The stepper motor stays in position, unless
power pulses initiate the two discrete sets of motor stator wind-
ings for rotation in either direction. The direction depends on
the phase relationship of the power pulses.
The motor directly operates the spindle, which has rotating
movements that are transformed into linear motion by the
transmission in the cage assembly. The valve includes a posi-
tive shut-off when closed.
OUTS
COMP
ENTER
Press
(password entry may be required) and use
to change ‘OFF’ to ‘ON’. Switch the EOR switch to
Enable. The Service Test mode is now enabled. Move the
pointer down to the OUTS sub-mode and press
ENTER
. Move the
ENTER
pointer to item EXV.A or EXV.B as needed. Press
and
the valve position will flash. Use
position (hold
to select 100% valve
ENTER
for quick movement) and press
.
The technician should be able to feel the actuator moving by
placing a hand on the EXV. A sight glass is located on the valve
body to verify that the sleeve is moving to expose/cover slots in
the orifice. A hard knocking should be felt from the actuator
when it reaches the top of its stroke (can be heard if surround-
ings are relatively quiet). Press
There are two different EXVs. See Table 30 for number of
steps. The EXV motor moves at 200 steps per second. Com-
manding the valve to either 0% or 100% will add extra steps to
the move, to ensure the value is open or closed completely.
ENTER
again twice if necessary to
ENTER
confirm this. To close the valve, press
, select 0% with
Table 30 — EXV Steps
ENTER
and press
. The actuator should knock when it reaches
UNIT SIZE 30RAP
010-020
EXV STEPS
1596
the bottom of its stroke. If it is believed that the valve is not
working properly, continue with the checkout procedure
below:
025,030
2500
035-045
1596
050-060
2500
Check the EXV output signals at appropriate terminals on
the EXV module (see Fig. 25). Connect positive test lead to red
wire (EXV-J6 terminal 3 for Circuit A, EXV-J7 terminal 3 for
Circuit B). Set meter to approximately 20 vdc. Using the
Service Test procedure above, move the valve output under test
to 100%. DO NOT short meter leads together or pin 3 to any
other pin as board damage will occur.
The EXV board controls the valve. Each circuit has a
thermistor located in a well in the suction manifold before the
compressor. Suction pressure as measured by the suction pres-
sure transducer is converted to a saturated suction temperature.
The thermistor measures the temperature of the superheated
gas entering the compressor and the pressure transducer
47
Download from Www.Somanuals.com. All Manuals Search And Download.
INCLUDED IN CABLE KIT
CABLE
CABLE
CABLE RETAINER
MOTOR AND
ADAPTER
ASSEMBLY
MOTOR ADAPTER
ASSEMBLY
CABLE
RETAINER
GASKET
MOTOR ADAPTER
ASSEMBLY
SIGHTGLASS
SPORLAN
FLOW
DIRECTION
NORMAL
FLOW
DIRECTION
a30-4971
Fig. 24 — Electronic Expansion Valve Details
During the next several seconds, carefully connect the nega-
tive test lead to pins 1,2,4 and 5 in succession (plug J6 for Cir-
cuit A, plug J7 for Circuit B). Digital voltmeters will average
this signal and display approximately 6 vdc. If it remains con-
stant at a voltage other than 6 VDC or shows 0 volts, remove
the connector to the valve and recheck.
FIELD SERVICING INSTRUCTIONS — The EXV valves
on sizes 025, 030, 050-060 can be serviced. The EXV valves
on all other sizes are hermetic and cannot be disassembled for
installation or during service, however, the cable and retainer
may be replaced if necessary. Motor kits for the EXV valve are
available as replacement parts.
To remove the valve from the system, perform the follow-
ing procedure:
1. Be sure the refrigerant has been recovered from the
circuit.
2. Disconnect the line voltage to the valve controller. Dis-
connect the valve wires from the controller.
3. If the motor fails to operate properly, check the resistance
of each motor phase. Resistance between black and white
leads or between the red and green leads should be ap-
proximately 100 ohms. Differences of more than 10% be-
tween phases indicate a defective motor. Resistance be-
tween black and red, or any lead and piping, should be in-
finite or “open”. Any resistance reading will indicate a
shorted winding and the valve will need to be replaced.
ENTER
Press
and select 0% to close the valve. Check the 4 po-
sition DIP switch on the board (all switches should be set to
On). If a problem still exists, replace the EXV module. If the
reading is correct, the expansion valve and EXV wiring should
be checked. Check the EXV terminal strip and interconnecting
wiring.
1. Check color coding and wire connections. Make sure
they are connected to the correct terminals at the EXV
driver and EXV plug and that the cables are not crossed.
2. Check for continuity and tight connection at all pin
terminals.
3. Check the resistance of the EXV motor windings. Re-
move the EXV module plug (J6 for Circuit A, J7 for Cir-
cuit B) and check the resistance of the two windings be-
tween pins 1 and 2 for one winding and pins 4 and 5 for
the other winding (see Fig. 25). The resistance should be
100 ohms ± 10 ohms.
4. The output of the controller to the valve can be tested
with the following procedure:
a. Disconnect supply voltage to the controller.
48
Download from Www.Somanuals.com. All Manuals Search And Download.
CAUTION
BLK
WHT
If the existing motor has been removed for inspection or
cleaning, be sure that the piston is fully retracted into the
motor assembly before installation on the valve. Failure to
do so will permanently damage the drive and motor.
Replacement motor assemblies are shipped in the retracted
position and may be installed as received.
GRN
RED
Compressor Replacement (Refer to Fig. 26
and 27) — All models contain scroll compressors and have
from one to four compressors. The size 010-030 units are a sin-
gle refrigeration circuit while sizes 035-060 are dual circuit. A
compressor is most easily removed from the front of the unit,
depending on where clearance space was allowed during unit
installation.
Remove the junction box cover bolts and disconnect the
compressor power and ground connections. Remove the cable
from the compressor junction box. Remove the connections
from the high-pressure switch. Knock the same holes out of the
new compressor junction box and install the cable connectors
from the old compressor.
BLK
WHT
GRN
RED
a30-4972
Fig. 25 — EXV Cable Connections to EXV Module
b. Place a digital voltmeter, on 20-volt AC scale,
across the black and white terminals on the con-
troller. Restore power to the controller. For at least
7 seconds, the voltmeter should read approxi-
mately 12 to 14 volts. Significant differences mean
the controller is defective or not properly config-
ured for the EXV valve.
c. Repeat the procedure in Step b above using the red
and green terminals on the controller. If the con-
troller responds properly, then the wiring may be
damaged or the valve may be plugged with debris
or otherwise obstructed.
The compressors are bolted to rails, which are in turn bolted
to the unit basepan for all sizes except 010 and 015 which are
directly bolted to the basepan. Remove the 4 bolts holding the
compressor to the rail on the basepan. Save the mounting hard-
ware for use with the new compressor. Carefully cut the com-
pressor suction and discharge lines with a tubing cutter as close
to the compressor as feasible. Remove high-pressure switch
and pressure transducer(s) if required for compressor removal.
Lift one corner of the compressor at a time and remove all the
rubber mounting grommets (single compressor circuits) or
steel spacers (dual compressor circuits). Remove the old com-
pressor from the unit.
Slide the new compressor in place on the basepan. Lifting
one side of the compressor at a time, replace all of the compres-
sor mounting grommets. Using new tubing as required, recon-
nect compressor suction and discharge lines. Using hardware
saved, reinstall the mounting bolts and washers through the
compressor feet. Using proper techniques, braze suction and
discharge lines and check for leaks. Reconnect oil equalization
line on dual compressor circuit models.
Reconnect the compressor power connections and high-
pressure switch wiring as on the old compressor. Refer to
Fig. 26 and 27. Following the installation of the new compres-
sor, tighten all hardware to the following specifications. (See
Table 31.)
d. The EXV valves on sizes 025, 030, 050-060 may
be disassembled for cleaning, inspection or motor
assembly replacement.
VALVE REPLACEMENT — The valve may be replaced by
unsoldering or cutting the piping. A tubing cutter must be used
to prevent creating contaminants in the piping.
VALVE REASSEMBLY — Perform the following procedure
to reassemble the EXV valve:
1. Use Service Test to open the EXV to 100%. This will re-
tract the white polyester driver/piston fully into the driver
guide. Remove power from the valve or controller.
2. Lightly oil the threads, and gasket or knife-edge on the
new motor adaptor. Carefully seat the adaptor on the
valve body or engage and tighten the lock nut if used.
Lock nuts should be torqued to approximately 45 ft-lb.
One eighth turn more than hand tight is sufficient to
achieve a leak proof seal on knife-edge joints.
Table 31 — Unit Torque Specification
FASTENER
RECOMMENDED TORQUE
Compressor Mounting
Bolts
7 to 10 ft-lb (9.5 to 13.5 N-m)
3. After the motor is tightened, the cable should be replaced
on the valve. Care should be taken to ensure engagement
of the alignment key. Snap on the cable retainer.
Compressor Power
Connections
Compressor Ground
Terminal Connections
24 to 28 in.-lb (2.7- to 3.2 N-m)
14 to 18 in.-lb (1.6 to 2.0 N-m)
4. Pressurize the system and check for leaks.
5. Reapply power to the ComfortLink™ controller. Since,
during service, valve position as calculated by the con-
troller will be lost, the controller should be initialized at
least twice. In some instances, cycling power to the con-
troller will accomplish this.
Cooler
BRAZED-PLATE COOLER HEAT EXCHANGER RE-
PLACEMENT — Brazed-plate heat exchangers cannot be
repaired if they develop a leak. If a leak (refrigerant or water)
develops, the heat exchanger must be replaced. To replace a
brazed-plate heat exchanger:
1. Check that the replacement heat exchanger is the same as
the original heat exchanger. The unit insulation covers the
manufacturer’s part number. Make sure the depths of the
replacement and original cooler heat exchangers are the
same.
49
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Disconnect the liquid-in and liquid-out connections at the
heat exchanger.
3. Recover the refrigerant from the system, and unsolder the
refrigerant-in and refrigerant-out connections.
Mobil . . . . . . . . . . . . . . . . . . . . . . . . . . .EAL Arctic 32-3MA
Uniqema . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RL32-3MAF
Do not reuse oil that has been drained out, or oil that has
been exposed to atmosphere.
4. Remove the old heat exchanger. The replacement heat ex-
changer is supplied fully insulated. It also includes a cool-
er heater. Use of the heater is not required unless the orig-
inal cooler contained a factory installed heater.
Microchannel Heat Exchanger (MCHX) Con-
denser Coil Maintenance and Cleaning
Recommendations
5. Install the replacement heat exchanger in the unit and at-
tach the mounting bracket hardware to the fan uprights
(sizes 010-030) or to the bottom bracket (sizes 035-060)
using the hardware removed in Step 4. Reconnect the
cooler heater if required. For sizes 010-025, torque the
bolts to 7-10 ft-lb. For sizes 030-060, torque the bolts to
30-50 ft-lb.
6. Carefully braze the refrigerant lines to the connections on
the heat exchanger. Lines should be soldered using silver
as the soldering material with a minimum of 45% silver.
Keep the temperature below 1472 F (800 C) under nor-
mal soldering conditions (no vacuum) to prevent the cop-
per solder of the brazed plate heat exchanger from chang-
ing its structure. Failure to do so can result in internal
or external leakage at the connections which cannot be re-
paired. Braze the liquid lines with a heat sink around the
expansion valve to protect it from excess heat.
CAUTION
Do not apply any chemical cleaners to MCHX condenser
coils. These cleaners can accelerate corrosion and damage
the coil.
Routine cleaning of coil surfaces is essential to maintain
proper operation of the unit. Elimination of contamination and
removal of harmful residues will greatly increase the life of the
coil and extend the life of the unit. The following steps should
be taken to clean MCHX condenser coils:
1. Remove any foreign objects or debris attached to the
coreface or trapped within the mounting frame and
brackets.
2. Put on personal protective equipment including safety-
glasses and/or face shield, waterproof clothing and
gloves. It is recommended to use full coverage clothing.
7. Reconnect the water/brine lines.
3. Start high pressure water sprayer and purge any soap or
industrial cleaners from sprayer before cleaning condens-
er coils. Only clean, potable water is authorized for clean-
ing condenser coils.
4. Clean condenser face by spraying the core steady and
uniformly from top to bottom while directing the spray
straight toward the core. Do not exceed 900 psig or 30 de-
gree angle. The nozzle must be at least 12 in. from the
core face. Reduce pressure and use caution to prevent
damage to air centers.
8. Dehydrate and recharge the unit. Check for leaks.
BRAZED-PLATE COOLER HEAT EXCHANGER
CLEANING — Brazed-plate heat exchangers must be
cleaned chemically. A professional cleaning service skilled in
chemical cleaning should be used. Use a weak acid (5% phos-
phoric acid, or if the heat exchanger is cleaned frequently, 5%
oxalic acid). Pump the cleaning solution through the
exchanger, preferably in a backflush mode. After cleaning,
rinse with large amounts of fresh water to dispose of all the
acid. Cleaning materials must be disposed of properly.
The factory-installed strainer screen in front of the water/
brine inlets of the heat exchangers should be cleaned periodi-
cally, depending on condition of the chiller water/brine.
CAUTION
Excessive water pressure will fracture the braze between
air centers and refrigerant tubes.
Oil Charge
Check Refrigerant Feed Components
CAUTION
FILTER DRIER — The function of the filter drier is to main-
tain a clean, dry system. The moisture indicator (described
below) indicates any need to change the filter drier. The filter
drier is a sealed-type drier. When the drier needs to be
changed, the entire filter drier must be replaced.
NOTE: Dual circuit (035-060 sizes) units have 1 filter drier per
circuit.
The compressor in a Puron® refigerant (R-410A) system
uses a polyol ester (POE) oil. This is extremely hygro-
scopic, meaning it absorbs water readily. POE oils can
absorb 15 times as much water as other oils designed for
HCFC and CFC refrigerants. Take all necessary precau-
tions to avoid exposure of the oil to the atmosphere. Failure
to do so could result in possible equipment damage.
MOISTURE-LIQUID INDICATOR —The indicator is located
immediately ahead of the TXV to provide an indication of the
refrigerant moisture content. It also provides a sight glass for
refrigerant liquid. Clear flow of liquid refrigerant (at full unit
loading) indicates sufficient charge in the system. Bubbles in the
sight glass (at full unit loading) indicate an undercharged system
or the presence of noncondensables. Moisture in the system,
measured in parts per million (ppm), changes the color of the
indicator as follows:
Green (safe) —Moisture is below 75 ppm
Yellow-Green (caution) — 75 to 150 ppm
Yellow (wet) — above 150 ppm
The unit must be in operation at least 12 hours before the
moisture indicator gives an accurate reading, and must be in
contact with liquid refrigerant. At the first sign of moisture in
the system, change the corresponding filter drier.
Puron refrigerant systems use a polyol ester (POE) oil. Use
only Carrier approved compressor oil. Oil should be visible in
compressor oil sight glass. An acceptable oil level is from 1/8 to
3/8 of sight glass. All compressors must be off when checking
oil level. Recommended oil level adjustment method is as
follows:
ADD OIL — Recover charge from the unit. Add oil to suction
line Schrader valve on tandem compressors sets and the com-
pressor Schrader on the trio's and single compressor circuits.
(See Fig. 26 and 27.) When oil can be seen at the bottom of the
sight glass, add oil in 5 oz increments which is approximately
1/8 in oil level. Run all compressors for 20 minutes then shut off
to check oil level. Repeat procedure until acceptable oil level is
present.
NOTE: Use only Carrier approved compressor oil. Approved
sources are:
NOTE: Dual circuit (035-060 sizes) units have one indicator
per circuit.
Totaline . . . . . . . . . . . . . . . . . . . . . .3MAF POE, P903-1601
50
Download from Www.Somanuals.com. All Manuals Search And Download.
DPT HPS
SUCTION
ACCESS
EWT VALVE
SPT
RGT
COMPRESSOR A2
COMPRESSOR A1
LWT
DTT
a30-4973
a30-4974
FLOW
SWITCH
Fig. 26 — Compressor Location — 30RAP010-030
SPT RGT
SUCTION
RGT
SPT
ACCESS
VALVE
HPS
DPT
DISCHARGE
ACCESS
VALVE
EWT
DTT
A1
A2
B1
B2
OIL
SIGHTGLASS
LWT
DISCHARGE
ACCESS
DPT
FLOW
SWITCH
VALVE
HPS
Fig. 27 — Compressor Location — 30RAP035-060
LEGEND FOR FIG. 26 AND 27
DPT
DTT
EWT
HPS
LWT
RGT
SPT
— Discharge Pressure Thermostat
— Discharge Temperature Thermistor
— Entering Water Thermistor
— High Pressure Switch
— Leaving Water Thermistor
— Return Gas Thermistor
— Suction Pressure Transducer
51
Download from Www.Somanuals.com. All Manuals Search And Download.
MINIMUM LOAD VALVE — On units equipped with the
factory-installed capacity reduction option, a solenoid valve
and discharge bypass valve (minimum load valve) are located
between the discharge line and the cooler entering-refrigerant
line. The MBB cycles the solenoid to perform minimum load
valve function and the discharge bypass valve modulates to the
suction pressure set point and the valve.
The amount of capacity reduction achieved by the mini-
mum load valve is not adjustable. The total unit capacity with
the minimum load valve is shown in Table 19.
HEATER CABLE — Optional factory-installed cooler and/or
hydronic package heaters are cycled based on the input from
the outside-air temperature sensor. These heaters, when in-
stalled, are designed to protect the cooler and/or hydronic pack-
age from freezing down to –20 F (–29 C). Power for these heat-
ers is supplied from the main unit power.
The input from the low pressure transducer provides a back-
up cooler freeze protection package. The MBB shuts down the
unit when a low pressure condition exists that could cause the
cooler to freeze up.
PRESSURE RELIEF DEVICES — All units have one pres-
sure relief device per circuit located in the liquid line which re-
lieves at 210 F (100 C).
CAUTION
Do not disconnect main unit power when servicing com-
pressor(s) if ambient temperature is below 40 F (4.4 C).
The compressors have either a single circuit breaker or
multiple circuit breakers which can be used to shut off
power to the compressors. If power to the unit must be off
for a prolonged period, drain the cooler, hydronic package
(if installed) and internal piping. Add glycol according to
Winter Shutdown Step 2 below.
Check Unit Safeties
HIGH-PRESSURE SWITCH — A high-pressure switch is
provided to protect each compressor and refrigeration system
from unsafe high pressure conditions. See Table 32 for high-
pressure switch settings.
The high-pressure switch is mounted in the discharge line of
each circuit. If an unsafe, high-pressure condition should exist,
the switch opens and shuts off the affected circuit. The CSB
senses the compressor feedback signal and generates an appro-
priate alarm. The MBB prevents the circuit from restarting un-
til the alert condition is reset. The switch should open at the
pressure corresponding to the appropriate switch setting as
shown in Table 32.
WINTER SHUTDOWN — At the end of the cooling season:
1. Drain the fluid from the cooler, hydronic package (if in-
stalled) and internal piping.
2. Fill the cooler and hydronic package with at least 2 gal-
lons (7.6 L) of inhibited propylene glycol or other suit-
able inhibited antifreeze solution to prevent any residual
water in the cooler and hydronic package/piping from
freezing.
Table 32 — Factory Settings, High-Pressure
Switch (Fixed)
CUTOUT
CUT-IN
3. At the beginning of the next cooling season, refill the
cooler and add the recommended inhibitor.
UNIT
30RA
Psig
650
kPa
4482
Psig
500
kPa
3447
Thermistors — Electronic control uses up to five 5 k
thermistors to sense temperatures used to control operation of
the chiller. Thermistors EWT, LWT, RGTA, RGTB, and OAT
are identical in their temperature and voltage drop perfor-
mance. The SPT space temperature thermistor has a 10 k in-
put channel and it has a different set of temperature vs. resis-
tance and voltage drop performance. Resistance at various tem-
peratures are listed in Tables 33-37. For dual chiller operation,
a dual chiller sensor is required which is a 5 k thermistor.
When a digital compressor is used, a DTT (digital temperature
thermistor) is used. The DTT is an 86 k thermistor.
REPLACING THERMISTORS (EWT, LWT, RGT) — Add
a small amount of thermal conductive grease to the thermistor
well and end of probe. For all probes, tighten the retaining nut
¼ turn past finger tight. See Fig. 28.
THERMISTOR/TEMPERATURE SENSOR CHECK — A
high quality digital volt-ohmmeter is required to perform this
check.
Clear the alarm using the scrolling marquee display as de-
scribed on page 63. The unit should restart after the compressor
anti-short-cycle delay, built into the unit control module,
expires.
PRESSURE TRANSDUCERS — Each refrigerant circuit is
equipped with a suction and discharge pressure transducer.
These inputs to the MBB are not only used to monitor the sta-
tus of the unit, but to also maintain operation of the chiller
within the compressor manufacturer's specified limits. The in-
put to the MBB from the suction pressure transducer is also
used to protect the compressor from operating at low pressure
conditions and low superheat conditions. In some cases, the
unit may not be able to run at full capacity. The control module
will automatically reduce the capacity of a circuit as needed to
maintain specified maximum/minimum operating pressures.
COOLER FREEZE-UP PROTECTION
1. Connect the digital voltmeter across the appropriate the-
mistor terminals at the J8 terminal strip on the Main Base
Board (see Fig. 29).
2. Using the voltage reading obtained, read the sensor tem-
perature from Tables 33-37.
3. To check thermistor accuracy, measure temperature at
probe location with an accurate thermocouple-type tem-
perature measuring instrument. Insulate thermocouple to
avoid ambient temperatures from influencing reading.
Temperature measured by thermocouple and temperature
determined from thermistor voltage reading should be
close, ± 5° F (3° C) if care was taken in applying thermo-
couple and taking readings.
WARNING
On medium temperature brine units, the anti-freeze solu-
tion must be properly mixed to prevent freezing at a tem-
perature of at least 15 F (8.3 C) below the leaving-fluid
temperature set point. Failure to provide the proper anti-
freeze solution mixture is considered abuse and may impair
or otherwise negatively impact the Carrier warranty.
The main base board (MBB) monitors leaving fluid temper-
ature at all times. The MBB will rapidly remove stages of ca-
pacity as necessary to prevent freezing conditions due to the
rapid loss of load or low cooler fluid flow.
If a more accurate check is required, unit must be shut down
and thermistor removed and checked at a known temperature
(freezing point or boiling point of water) using either voltage
drop measured across thermistor at the J8 terminal, by deter-
mining the resistance with chiller shut down and thermistor
When the cooler is exposed to lower ambient temperatures
(34 F [1° C] or below), freeze-up protection is required using
inhibited ethylene or propylene glycol.
52
Download from Www.Somanuals.com. All Manuals Search And Download.
disconnected from J8. Compare the values determined with the
value read by the control in the Temperatures mode using the
scrolling marquee display.
necessary, build-up (e.g., lime) can be removed with a common
vinegar cleansing agent.
The flow sensor cable is provided with (3) LEDs that indi-
cate if 24 vac power is present and also status of the switch
contacts. The LEDs are as follows:
• Green LED ON – 24 vac present
• One Yellow LED ON – Flow sensor switch OPEN
• Two Yellow LED ON – Flow sensor switch CLOSED
Pressure Transducers — The suction and discharge
transducers are different part numbers and can be distinguished
by the color of the transducer body, suction (yellow) and dis-
charge (red). No pressure transducer calibration is required.
The transducers operate on a 5 vdc supply, which is generated
by the main base board (MBB). See Fig. 29 for transducer con-
nections to the J8 connector on the MBB.
If nuisance trips of the sensor are occurring, follow the
steps below to correct the situation:
TROUBLESHOOTING — If a transducer is suspected of be-
ing faulty, first check supply voltage to the transducer. Supply
voltage should be 5 vdc ± 0.2 v. If supply voltage is correct,
compare pressure reading displayed on the scrolling marquee
display module against pressure shown on a calibrated pressure
gauge. Pressure readings should be within ± 15 psig. If the
two readings are not reasonably close, replace the pressure
transducer.
1. Check to confirm that the factory installed strainer is
clean. Use the blow-down valve provided or remove the
screen and clean it. For the case of VFD controlled
pumps, ensure that the minimum speed setting has not
been changed.
2. Measure the pressure drop across the cooler or cooler/
pump system and compare this to the system requirements.
3. Verify that cable connections at the switch and at the ter-
minal block are secure.
4. For factory-installed hydronic systems, verify that:
• All air has been purged from the system.
• Circuit setter balance valve has been correctly set.
5. Pump impeller has been improperly trimmed and is not
providing sufficient flow.
6. Wrong pump motor rotation. Pump must rotate clockwise
when viewed from motor end of pump.
Chilled Water Flow Switch — A factory-installed
flow switch is installed in the leaving fluid piping for all units
without the factory-installed hydronic package. See Fig. 30.
Units with the optional hydronic package have the flow switch
installed in the entering fluid piping. This is a thermal-disper-
sion flow switch with no field adjustments. The switch is set
for approximately 0.5 ft/sec of flow. The sensor tip houses two
thermistors and a heater element. One thermistor is located in
the sensor tip, closest to the flowing fluid. This thermistor is
used to detect changes in the flow velocity of the liquid. The
second thermistor is bonded to the cylindrical wall and is af-
fected only by changes in the temperature of the liquid. The
thermistors are positioned to be in close contact with the wall
of the sensor probe and, at the same time, to be kept separated
from each other within the confines of the probe.
In order to sense flow, it is necessary to heat one of the
thermistors in the probe. When power is applied, the tip of the
probe is heated. As the fluid starts to flow, heat will be carried
away from the sensor tip. Cooling of the first thermistor is a
function of how fast heat is conducted away by the flowing
liquid.
Strainer — Periodic factory-installed strainer cleaning is
required. Pressure drop across strainer in excess of 3 psi
(21 kPa) indicates the need for cleaning. Normal (clean) pres-
sure drop is approximately 1 psi (6.9 kPa). Open the factory-
installed blowdown valve to clean the strainer. If required, shut
the chiller down and remove the strainer screen to clean. When
strainer has been cleaned, enter ‘YES’ for Strainer Mainte-
nance Done (Run StatusPMS.T.MN).
Condenser Fans — Each fan is supported by a formed
wire mount bolted to a fan deck and covered with a wire guard.
METAL FANS — The exposed end of fan motor shaft is pro-
tected from weather by grease and a rubber boot. If fan motor
must be removed for service or replacement, be sure to re-
grease fan shaft and reinstall fan guard. For proper perfor-
mance with the value sound fan option, fan web should be
0.32 in. (8 mm) below top of orifice on the fan deck to top of
the fan hub. (See Fig. 31.) Tighten set screws to 15 ± 1 ft-lb
(20 ± 1.3 N-m).
The difference in temperature between the two thermistors
provides a measurement of fluid velocity past the sensor probe.
When fluid velocity is high, more heat will be carried away
from the heated thermistor and the temperature differential will
be small. As fluid velocity decreases, less heat will be taken
from the heated thermistor and there will be an increase in tem-
perature differential.
When unit flow rate is above the minimum flow rate, then
the output is switched on, sending 24 vac to the MBB to prove
flow has been established.
For recommended maintenance, check the sensor tip for
build-up every 6 months. Clean the tip with a soft cloth. If
IMPORTANT: Check for proper fan rotation (clockwise
when viewed from above). If necessary, switch any
2 power leads to reverse fan rotation.
5/8 in. HEX
1/4-18 NPT
6" MINIMUM
CLEARANCE FOR
THERMISTOR
REMOVAL
Fig. 28 — Thermistor Well
53
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 33 — 5K Thermistor Temperatures (°F) vs. Resistance/Voltage Drop
(Voltage Drop for EWT, LWT, RGT, and OAT)
VOLTAGE
DROP
(V)
VOLTAGE
DROP
(V)
VOLTAGE
DROP
(V)
TEMP
(F)
RESISTANCE
(Ohms)
TEMP
(F)
RESISTANCE
(Ohms)
TEMP
(F)
RESISTANCE
(Ohms)
59
60
1.982
1.956
1.930
1.905
1.879
1.854
1.829
1.804
1.779
1.754
1.729
1.705
1.681
1.656
1.632
1.609
1.585
1.562
1.538
1.516
1.493
1.470
1.448
1.426
1.404
1.382
1.361
1.340
1.319
1.298
1.278
1.257
1.237
1.217
1.198
1.179
1.160
1.141
1.122
1.104
1.086
1.068
1.051
1.033
1.016
0.999
0.983
0.966
0.950
0.934
0.918
0.903
0.888
0.873
0.858
0.843
0.829
0.815
0.801
0.787
0.774
0.761
0.748
0.735
0.723
0.710
0.698
0.686
0.674
0.663
0.651
0.640
0.629
0.618
0.608
0.597
0.587
0.577
0.567
0.557
0.548
0.538
0.529
0.520
7,686
7,665
7,468
7,277
7,091
6,911
6,735
6,564
6,399
6,238
6,081
5,929
5,781
5,637
5,497
5,361
5,229
5,101
4,976
4,855
4,737
4,622
4,511
4,403
4,298
4,196
4,096
4,000
3,906
3,814
3,726
3,640
3,556
3,474
3,395
3,318
3,243
3,170
3,099
3,031
2,964
2,898
2,835
2,773
2,713
2,655
2,597
2,542
2,488
2,436
2,385
2,335
2,286
2,239
2,192
2,147
2,103
2,060
2,018
1,977
1,937
1,898
1,860
1,822
1,786
1,750
1,715
1,680
1,647
1,614
1,582
1,550
1,519
1,489
1,459
1,430
1,401
1,373
1,345
1,318
1,291
1,265
1,240
1,214
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
0.511
0.502
0.494
0.485
0.477
0.469
0.461
0.453
0.445
0.438
0.430
0.423
0.416
0.408
0.402
0.395
0.388
0.381
0.375
0.369
0.362
0.356
0.350
0.344
0.339
0.333
0.327
0.322
0.317
0.311
0.306
0.301
0.296
0.291
0.286
0.282
0.277
0.272
0.268
0.264
0.259
0.255
0.251
0.247
0.243
0.239
0.235
0.231
0.228
0.224
0.220
0.217
0.213
0.210
0.206
0.203
0.200
0.197
0.194
0.191
0.188
0.185
0.182
0.179
0.176
0.173
0.171
0.168
0.165
0.163
0.160
0.158
0.155
0.153
0.151
0.148
0.146
0.144
0.142
0.140
0.138
0.135
0.133
1,190
1,165
1,141
1,118
1,095
1,072
1,050
1,029
1,007
986
965
945
925
906
887
868
850
832
815
798
782
765
750
734
719
705
690
677
663
650
638
626
614
602
591
581
570
561
551
542
533
524
516
508
501
494
487
480
473
467
461
456
450
445
439
434
429
424
419
415
410
405
401
396
391
386
382
377
372
367
361
356
350
344
338
332
325
318
311
304
297
289
282
–25
–24
–23
–22
–21
–20
–19
–18
–17
–16
–15
–14
–13
–12
–11
–10
–9
–8
–7
–6
–5
–4
–3
–2
–1
0
3.699
3.689
3.679
3.668
3.658
3.647
3.636
3.624
3.613
3.601
3.588
3.576
3.563
3.550
3.536
3.523
3.509
3.494
3.480
3.465
3.450
3.434
3.418
3.402
3.386
3.369
3.352
3.335
3.317
3.299
3.281
3.262
3.243
3.224
3.205
3.185
3.165
3.145
3.124
3.103
3.082
3.060
3.038
3.016
2.994
2.972
2.949
2.926
2.903
2.879
2.856
2.832
2.808
2.784
2.759
2.735
2.710
2.685
2.660
2.634
2.609
2.583
2.558
2.532
2.506
2.480
2.454
2.428
2.402
2.376
2.349
2.323
2.296
2.270
2.244
2.217
2.191
2.165
2.138
2.112
2.086
2.060
2.034
2.008
98,010
94,707
91,522
88,449
85,486
82,627
79,871
77,212
74,648
72,175
69,790
67,490
65,272
63,133
61,070
59,081
57,162
55,311
53,526
51,804
50,143
48,541
46,996
45,505
44,066
42,679
41,339
40,047
38,800
37,596
36,435
35,313
34,231
33,185
32,176
31,202
30,260
29,351
28,473
27,624
26,804
26,011
25,245
24,505
23,789
23,096
22,427
21,779
21,153
20,547
19,960
19,393
18,843
18,311
17,796
17,297
16,814
16,346
15,892
15,453
15,027
14,614
14,214
13,826
13,449
13,084
12,730
12,387
12,053
11,730
11,416
11,112
10,816
10,529
10,250
9,979
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
1
86
2
87
3
88
4
89
5
90
6
91
7
92
8
93
9
94
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
9,717
9,461
9,213
8,973
8,739
8,511
8,291
8,076
54
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 34 — 5K Thermistor Temperatures (°C) vs. Resistance/Voltage Drop
(Voltage Drop for EWT, LWT, RGT, and OAT)
VOLTAGE
DROP
(V)
VOLTAGE
DROP
(V)
VOLTAGE
DROP
(V)
TEMP
(C)
RESISTANCE
(Ohms)
TEMP
(C)
RESISTANCE
(Ohms)
TEMP
(C)
RESISTANCE
(Ohms)
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
1.982
1.935
1.889
1.844
1.799
1.754
1.710
1.666
1.623
1.580
1.538
1.497
1.457
1.417
1.378
1.340
1.302
1.265
1.229
1.194
1.160
1.126
1.093
1.061
1.030
0.999
0.969
0.940
0.912
0.885
0.858
0.832
0.807
0.782
0.758
0.735
0.713
0.691
0.669
0.649
0.629
0.610
0.591
0.573
0.555
0.538
0.522
7,855
7,499
7,161
6,840
6,536
6,246
5,971
5,710
5,461
5,225
5,000
4,786
4,583
4,389
4,204
4,028
3,861
3,701
3,549
3,404
3,266
3,134
3,008
2,888
2,773
2,663
2,559
2,459
2,363
2,272
2,184
2,101
2,021
1,944
1,871
1,801
1,734
1,670
1,609
1,550
1,493
1,439
1,387
1,337
1,290
1,244
1,200
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
0.506
0.490
0.475
0.461
0.447
0.433
0.420
0.407
0.395
0.383
0.371
0.360
0.349
0.339
0.329
0.319
0.309
0.300
0.291
0.283
0.274
0.266
0.258
0.251
0.244
0.237
0.230
0.223
0.217
0.211
0.204
0.199
0.193
0.188
0.182
0.177
0.172
0.168
0.163
0.158
0.154
0.150
0.146
0.142
0.138
0.134
1,158
1,118
1,079
1,041
1,006
971
938
906
876
836
805
775
747
719
693
669
645
623
602
583
564
547
531
516
502
489
477
466
456
446
436
427
419
410
402
393
385
376
367
357
346
335
324
312
299
285
–32
3.705
3.687
3.668
3.649
3.629
3.608
3.586
3.563
3.539
3.514
3.489
3.462
3.434
3.406
3.376
3.345
3.313
3.281
3.247
3.212
3.177
3.140
3.103
3.065
3.025
2.985
2.945
2.903
2.860
2.817
2.774
2.730
2.685
2.639
2.593
2.547
2.500
2.454
2.407
2.360
2.312
2.265
2.217
2.170
2.123
2.076
2.029
100,260
94,165
88,480
83,170
78,125
73,580
69,250
65,205
61,420
57,875
54,555
51,450
48,536
45,807
43,247
40,845
38,592
38,476
34,489
32,621
30,866
29,216
27,633
26,202
24,827
23,532
22,313
21,163
20,079
19,058
18,094
17,184
16,325
15,515
14,749
14,026
13,342
12,696
12,085
11,506
10,959
10,441
9,949
–31
–30
–29
–28
–27
–26
–25
–24
–23
–22
–21
–20
–19
–18
–17
–16
–15
–14
–13
–12
–11
–10
–9
–8
–7
–6
–5
–4
–3
–2
–1
0
1
2
3
4
5
6
7
8
9
10
11
9,485
12
9,044
13
8,627
14
8,231
55
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 35 — 10K Thermistor Temperature (°F) vs. Resistance/Voltage Drop
(For SPT)
VOLTAGE
DROP
(V)
VOLTAGE
DROP
(V)
VOLTAGE
DROP
(V)
TEMP
(F)
RESISTANCE
(Ohms)
TEMP
(F)
RESISTANCE
(Ohms)
TEMP
(F)
RESISTANCE
(Ohms)
–25
–24
–23
–22
–21
–20
–19
–18
–17
–16
–15
–14
–13
–12
–11
–10
–9
–8
–7
–6
–5
–4
–3
–2
–1
0
4.758
4.750
4.741
4.733
4.724
4.715
4.705
4.696
4.686
4.676
4.665
4.655
4.644
4.633
4.621
4.609
4.597
4.585
4.572
4.560
4.546
4.533
4.519
4.505
4.490
4.476
4.461
4.445
4.429
4.413
4.397
4.380
4.363
4.346
4.328
4.310
4.292
4.273
4.254
4.235
4.215
4.195
4.174
4.153
4.132
4.111
4.089
4.067
4.044
4.021
3.998
3.975
3.951
3.927
3.903
3.878
3.853
3.828
3.802
3.776
3.750
3.723
3.697
3.670
3.654
3.615
3.587
3.559
3.531
3.503
3.474
3.445
3.416
3.387
3.357
3.328
3.298
3.268
3.238
3.208
3.178
3.147
3.117
3.086
3.056
3.025
196,453
189,692
183,300
177,000
171,079
165,238
159,717
154,344
149,194
144,250
139,443
134,891
130,402
126,183
122,018
118,076
114,236
110,549
107,006
103,558
100,287
97,060
94,020
91,019
88,171
85,396
82,729
80,162
77,662
75,286
72,940
70,727
68,542
66,465
64,439
62,491
60,612
58,781
57,039
55,319
53,693
52,086
50,557
49,065
47,627
46,240
44,888
43,598
42,324
41,118
39,926
38,790
37,681
36,610
35,577
34,569
33,606
32,654
31,752
30,860
30,009
29,177
28,373
27,597
26,838
26,113
25,396
24,715
24,042
23,399
22,770
22,161
21,573
20,998
20,447
19,903
19,386
18,874
18,384
17,904
17,441
16,991
16,552
16,131
15,714
15,317
61
62
2.994
2.963
2.932
2.901
2.870
2.839
2.808
2.777
2.746
2.715
2.684
2.653
2.622
2.592
2.561
2.530
2.500
2.470
2.439
2.409
2.379
2.349
2.319
2.290
2.260
2.231
2.202
2.173
2.144
2.115
2.087
2.059
2.030
2.003
1.975
1.948
1.921
1.894
1.867
1.841
1.815
1.789
1.763
1.738
1.713
1.688
1.663
1.639
1.615
1.591
1.567
1.544
1.521
1.498
1.475
1.453
1.431
1.409
1.387
1.366
1.345
1.324
1.304
1.284
1.264
1.244
1.225
1.206
1.187
1.168
1.150
1.132
1.114
1.096
1.079
1.062
1.045
1.028
1.012
0.996
0.980
0.965
0.949
0.934
0.919
0.905
14,925
14,549
14,180
13,824
13,478
13,139
12,814
12,493
12,187
11,884
11,593
11,308
11,031
10,764
10,501
10,249
10,000
9,762
9,526
9,300
9,078
8,862
8,653
8,448
8,251
8,056
7,869
7,685
7,507
7,333
7,165
6,999
6,838
6,683
6,530
6,383
6,238
6,098
5,961
5,827
5,698
5,571
5,449
5,327
5,210
5,095
4,984
4,876
4,769
4,666
4,564
4,467
4,370
4,277
4,185
4,096
4,008
3,923
3,840
3,759
3,681
3,603
3,529
3,455
3,383
3,313
3,244
3,178
3,112
3,049
2,986
2,926
2,866
2,809
2,752
2,697
2,643
2,590
2,539
2,488
2,439
2,391
2,343
2,297
2,253
2,209
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
0.890
0.876
0.862
0.848
0.835
0.821
0.808
0.795
0.782
0.770
0.758
0.745
0.733
0.722
0.710
0.699
0.687
0.676
0.666
0.655
0.645
0.634
0.624
0.614
0.604
0.595
0.585
0.576
0.567
0.558
0.549
0.540
0.532
0.523
0.515
0.507
0.499
0.491
0.483
0.476
0.468
0.461
0.454
0.447
0.440
0.433
0.426
0.419
0.413
0.407
0.400
0.394
0.388
0.382
0.376
0.370
0.365
0.359
0.354
0.349
0.343
0.338
0.333
0.328
0.323
0.318
0.314
0.309
0.305
0.300
0.296
0.292
0.288
0.284
0.279
0.275
0.272
0.268
0.264
2,166
2,124
2,083
2,043
2,003
1,966
1,928
1,891
1,855
1,820
1,786
1,752
1,719
1,687
1,656
1,625
1,594
1,565
1,536
1,508
1,480
1,453
1,426
1,400
1,375
1,350
1,326
1,302
1,278
1,255
1,233
1,211
1,190
1,169
1,148
1,128
1,108
1,089
1,070
1,052
1,033
1,016
998
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
1
87
2
88
3
89
4
90
5
91
6
92
7
93
8
94
9
95
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
981
964
947
931
915
900
885
870
855
841
827
814
800
787
774
762
749
737
725
714
702
691
680
670
659
649
639
629
620
610
601
592
583
574
566
557
56
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 36 — 10K Thermistor Temperature (°C) vs. Resistance/Voltage Drop
(For SPT)
VOLTAGE
DROP
(V)
VOLTAGE
DROP
(V)
VOLTAGE
DROP
(V)
TEMP
(C)
RESISTANCE
(Ohms)
TEMP
(C)
RESISTANCE
(Ohms)
TEMP
(C)
RESISTANCE
(Ohms)
–32
–31
–30
–29
–28
–27
–26
–25
–24
–23
–22
–21
–20
–19
–18
–17
–16
–15
–14
–13
–12
–11
–10
–9
4.762
4.748
4.733
4.716
4.700
4.682
4.663
4.644
4.624
4.602
4.580
4.557
4.533
4.508
4.482
4.455
4.426
4.397
4.367
4.335
4.303
4.269
4.235
4.199
4.162
4.124
4.085
4.044
4.003
3.961
3.917
3.873
3.828
3.781
3.734
3.686
3.637
3.587
3.537
3.485
3.433
3.381
3.328
3.274
3.220
3.165
3.111
200,510
188,340
177,000
166,342
156,404
147,134
138,482
130,402
122,807
115,710
109,075
102,868
97,060
91,588
86,463
81,662
77,162
72,940
68,957
65,219
61,711
58,415
55,319
52,392
49,640
47,052
44,617
42,324
40,153
38,109
36,182
34,367
32,654
31,030
29,498
28,052
26,686
25,396
24,171
23,013
21,918
20,883
19,903
18,972
18,090
17,255
16,464
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
3.056
3.000
2.944
2.889
2.833
2.777
2.721
2.666
2.610
2.555
2.500
2.445
2.391
2.337
2.284
2.231
2.178
2.127
2.075
2.025
1.975
1.926
1.878
1.830
1.784
1.738
1.692
1.648
1.605
1.562
1.521
1.480
1.439
1.400
1.362
1.324
1.288
1.252
1.217
1.183
1.150
1.117
1.086
1.055
1.025
0.996
0.968
15,714
15,000
14,323
13,681
13,071
12,493
11,942
11,418
10,921
10,449
10,000
9,571
9,164
8,776
8,407
8,056
7,720
7,401
7,096
6,806
6,530
6,266
6,014
5,774
5,546
5,327
5,117
4,918
4,727
4,544
4,370
4,203
4,042
3,889
3,743
3,603
3,469
3,340
3,217
3,099
2,986
2,878
2,774
2,675
2,579
2,488
2,400
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
0.940
0.913
0.887
0.862
0.837
0.813
0.790
0.767
0.745
0.724
0.703
0.683
0.663
0.645
0.626
0.608
0.591
0.574
0.558
0.542
0.527
0.512
0.497
0.483
0.470
0.457
0.444
0.431
0.419
0.408
0.396
0.386
0.375
0.365
0.355
0.345
0.336
0.327
0.318
0.310
0.302
0.294
0.287
0.279
0.272
0.265
2,315
2,235
2,157
2,083
2,011
1,943
1,876
1,813
1,752
1,693
1,637
1,582
1,530
1,480
1,431
1,385
1,340
1,297
1,255
1,215
1,177
1,140
1,104
1,070
1,037
1,005
974
–8
–7
–6
–5
944
–4
915
–3
889
–2
861
–1
836
0
811
1
787
2
764
3
742
4
721
5
700
6
680
7
661
8
643
9
626
10
609
11
592
12
576
13
561
14
Table 37 — 86K Thermistor vs Resistance (DTT)
TEMP
(C)
TEMP
(F)
RESISTANCE
(Ohms)
TEMP
(C)
TEMP
(F)
RESISTANCE
(Ohms)
-40
-40
-31
-22
-13
-4
2,889,600
2,087,220
1,522,200
1,121,440
834,720
627,280
475,740
363,990
280,820
218,410
171,170
135,140
107,440
86,000
75
80
167
176
185
194
203
212
221
230
239
248
257
266
275
284
293
302
311
320
329
338
347
356
12,730
10,790
9,200
7,870
6,770
5,850
5,090
4,450
3,870
3,350
2,920
2,580
2,280
2,020
1,800
1,590
1,390
1,250
1,120
1,010
920
-35
-30
-25
-20
-15
-10
-5
85
90
95
5
100
105
110
115
120
125
130
135
140
145
150
155
160
165
170
175
180
14
23
0
5
32
41
10
15
20
25
30
35
40
45
50
55
60
70
50
59
68
77
86
69,280
95
56,160
104
113
122
131
140
158
45,810
37,580
30,990
25,680
21,400
15,070
830
57
Download from Www.Somanuals.com. All Manuals Search And Download.
LOW SOUND FAN — A shroud and a wire guard provide
protection from the rotating fan. The exposed end of the fan
motor shaft is protected from weather by grease. If fan motor
must be removed for service or replacement, be sure to re-
grease fan shaft and reinstall fan guard. The fan motor has a
step in the motor shaft. For proper performance, fan should be
positioned such that it is securely seated on this step. Tighten
the bolt to 15 ± 1 ft-lb (20 ± 1.3 N·m).
1
2
3
4
5
6
1
2
3
4
1
2
3
4
1
2
3
4
5
6
7
RGTA
RGTB
RED
1
2
BLK
RED
3
LVT
T55
4
BLK
BLU
BLU
RED
J12
3
5
23
22
T-55
ACCSY
SEN
6
4
OAT
7
IMPORTANT: Check for proper fan rotation (counter-
clockwise when viewed from above). If necessary, switch
any 2 power leads to reverse fan rotation.
SPACE TEMPERATURE
ACCESSORY OR
DUAL CHILLER LWT
8
BLK
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
Motormaster® V Controller — The Motormaster V
controller is standard on size 010 and 015 units. For other sizes,
the optional or accessory Motormaster V controller uses an in-
put signal from the AUX board. See Fig. 32. The controller is
factory configured and requires no field programming. If a situ-
ation arises where the drive does not function properly, the in-
formation provided below and in Table 38 can be used to trou-
bleshoot the drive.
EVAPORATOR ENTERING
FLUID TEMP
RED
BLK
RED
EVAPORATOR LEAVING
FLUID TEMP
J8
BLK
RED
B
C
A
B
C
A
+
DPTB
GRN
BLK
RED
-
+
WARNING
SPTB
DPTA
SPTA
GRN
BLK
-
Hazard of electrical shock. Wait three minutes after discon-
necting incoming power before servicing drive. Capacitors
retain charge after power is removed. Drive assembly
includes externally mounted current limiting resistors. Use
extreme caution when servicing the drive. Failure to com-
ply could result in possible personal injury.
B
C
A
RED
+
8
GRN
BLK
9
-
10
B
C
A
RED
+
11
12
GRN
BLK
-
a30-4975
WARNING
LEGEND
ACCSY — Accessory
When configured as shown in this literature, this equip-
ment is designed to start when it receives line power.
Ensure that all personnel are clear of fans and guards are
installed before applying power. Failure to comply could
result in possible personal injury.
DPT
LWT
LVT
OAT
RGT
SEN
SPT
— Discharge Pressure Transducer
— Leaving Water Temperature Sensor
— Low Voltage Terminal
— Outdoor Air Temperature Sensor
— Return Gas Temperature Sensor
— Sensor Terminal Block
— Space Temperature Sensor
CAUTION
Fig. 29 — Thermistor Connections to
Main Base Board, J8 Connector
DO NOT connect incoming AC power to output terminals
T1, T2, and T3. Severe damage to the drive will result. Do
not continuously cycle input power to the drive more than
once every two minutes. Damage to the drive will result.
CAUTION
If input power has not been applied to the drive for a period
of time exceeding three years (due to storage, etc.), the
electrolytic DC bus capacitors within the drive can change
internally, resulting in excessive leakage current. This can
result in premature failure of the capacitors if the drive is
operated after such a long period of inactivity or storage. In
order to reform the capacitors and prepare the drive for
operation after a long period of inactivity, apply input
power to the drive for 8 hours prior to actually operating
the motor. Before attempting to operate the drive, motor,
and driven equipment, be sure all procedures pertaining to
installation and wiring have been properly followed. Fail-
ure to comply could result in equipment damage.
a30-499
Fig. 30 — Chilled Water Flow Switch
GENERAL OPERATION — The speed varies in proportion
to a 4 to 20 mA signal produced by the ComfortLink™ con-
trols. The MMV output speed is displayed in Hz.
The ComfortLink controls must be configured for MMV
operation in order for it to operate. This is configured under the
Configuration menu (ConfigurationMMMMR.S) and
a30-4976
Fig. 31 — Mounted Fan Position
58
Download from Www.Somanuals.com. All Manuals Search And Download.
selecting “YES”. This configuration menu also contains the
gains and minimum speed for the Motormaster control logic.
VFD. It should not be removed with power applied to the
VFD.
CONFIGURATION — The MMV is configured for 1 of 12
operation modes based on the inputs to the control terminal
block. The 30RAP units use operating modes 5-8. In these con-
figurations, the MMV follows a 4 to 20 mA speed reference
signal present on terminals 25 (+) and 2 (-). One additional
jumper is required to configure the drive for 50/60 Hz opera-
tion and input voltage. See Table 39 for proper inputs. Once the
drive is powered, it will change to the mode selected according
to the inputs. See Fig. 33.
LOSS OF CCN COMMUNICATIONS — Carrier Comfort
Network® (CCN) communications with external control
systems can be affected by high frequency electrical noise gen-
erated by the Motormaster V control. Ensure unit is well
grounded to eliminate ground currents along communication
lines.
If communications are lost only while Motormaster V con-
trol is in operation, order a signal isolator (CEAS420876-2)
and power supplies (CEAS221045-01, 2 required) for the CCN
communication line.
DRIVE PROGRAMMING
Fault Codes — The drive is programmed to automatically re-
start after a fault and will attempt to restart three times after a
fault (the drive will not restart after CF, cF, GF, F1, F2-F9, or
Fo faults). If all three restart attempts are unsuccessful, the
drive will trip into FAULT LOCKOUT (LC), which requires a
manual reset.
CAUTION
It is strongly recommended that the user NOT change any
programming without consulting Carrier service personnel.
Unit damage may occur from improper programming.
Manual Reset — If fault condition has been removed, cycle
power to the chiller to reset the VFD.
To enter password and change program values:
1. Press Mode.
2. Upper right decimal point blinks.
3. Display reads “00”. To enter the PROGRAM mode to ac-
cess the parameters, press the Mode button. This will ac-
tivate the PASSWORD prompt (if the password has not
been disabled). The display will read “00” and the upper
right-hand decimal point will be blinking. (See Fig. 33.)
Troubleshooting — Troubleshooting the Motormaster®
V
control requires a combination of observing system operation
and VFD information. The drive provides 2 kinds of trouble-
shooting modes: a status matrix using the 3-digit display
(P57, P58) and real time monitoring of key inputs and outputs.
The collective group is displayed through parameters
50-60 and all values are read-only.
•
•
•
P50: FAULT HISTORY — Last 8 faults
P51: SOFTWARE version
4. Use the
and
buttons to scroll to the password
value (the factory default password is “1111”) and press
the Mode button. Once the correct password value is
entered, the display will read “P01”, which indicates that
the PROGRAM mode has been accessed at the beginning
of the parameter menu (P01 is the first parameter).
P52: DC BUS VOLTAGE — in percent of nominal.
Usually rated input voltage x 1.4
•
•
•
•
P53: MOTOR VOLAGE — in percent of rated output
voltage
P54: LOAD — in percent of drives rated output current
rating
P55: VDC INPUT — in percent of maximum input:
100 will indicate full scale which is 5 v
P56: 4-20 mA INPUT — in percent of maximum input.
20% = 4 mA, 100% = 20 mA
NOTE: If the display flashes “Er”, the password was incorrect,
and the process to enter the password must be repeated.
5. Press Mode to display present parameter number.
Upper right decimal point blinks.
Use the
parameter number.
and
buttons to scroll to the desired
Manual Starter Trip — If the VFD manual starter (MS-FC-
HS, MS-FC-A1 or MS-FC-B1 depending on model) trips,
locate the inrush current protectors (3 round black disks per
motor) and verify their resistance. For units operating at 208 v
or 230 v, these devices should measure approximately 7 ohms.
For all other voltages, they should measure approximately
20 ohms. Check value with mating plug disconnected, power
to chiller off and at ambient temperature (not hot immediately
after stopping VFD). These are standard resistances at 77 F
(25 C). Resistance values decrease at higher temperatures and
increase at lower temperatures.
REPLACING DEFECTIVE MODULES — The Comfort-
Link™ replacement modules are shown in Table 40. If the main
base board (MBB) has been replaced, verify that all configura-
tion data is correct. Follow the Configuration mode table and
verify that all items under sub-modes UNIT, OPT1 and OPT2
are correct. Any additional field-installed accessories or op-
tions (RSET, SLCT sub-modes) should also be verified as well
as any specific time and maintenance schedules.
Once the desired parameter number is found, press the
Mode button to display the present parameter setting. The up-
per right-hand decimal point will begin blinking, indicating
that the present parameter setting is being displayed, and that it
can be changed by using the up and down buttons. Use
and
to change setting. Press Mode to store new setting.
Pressing the Mode will store the new setting and also exit
the PROGRAM mode. To change another parameter, press the
Mode key again to re-enter the PROGRAM mode (the param-
eter menu will be accessed at the parameter that was last
viewed or changed before exiting). If the Mode key is pressed
within two minutes of exiting the PROGRAM mode, the pass-
word is not required to access the parameters. After two min-
utes, the password must be entered in order to access the pa-
rameters again.
To change password: first enter the current password then
change parameter P44 to the desired password.
To disable automatic control mode and enter manual speed
control mode:
Refer to the Start-Up Checklist for 30RAP Liquid Chillers
(completed at time of original start-up) found in the job folder.
This information is needed later in this procedure. If the check-
list does not exist, fill out the current information in the Config-
uration mode on a new checklist. Tailor the various options and
configurations as needed for this particular installation.
1. Change P05 to ‘01- keypad’.
2. Push UP and DOWN arrow key to set manual speed.
3. Set P05 to ‘04 - 4-20mA control’ to restore 4 to 20 mA
control.
EPM CHIP — The drive uses a electronic programming mod-
ule (EPM) chip to store the program parameters. This is an
EEPROM memory chip and is accessible from the front of the
59
Download from Www.Somanuals.com. All Manuals Search And Download.
LOW AMBIENT OPERATION (MOTORMASTER V) FIOP/ACCESSORY
MM-A
FB3
FB1
1
2
3
L1 T1
11
12
13
21
22
23
11
12
13
21
22
23
BLK-1
BLK-2
BLK-3
BLK
YEL
BLU
BLK
YEL
BLU
BLK
YEL
BLU
L2 T2
OFM1
L3 T3
GRN/YEL
YEL
HIGH SCCR
ONLY
2
MMR
14
* MM SIGNAL CONNECTION
VOLTAGE
*1
VIO 11
TB
1
HZ
60
60
240
1/4W
208/230/460/575
380
RED
25
2
FROM
13A
AUX-J4
BLK
FB2
FC2
1
2
3
11
12
13
21
22
23
11
12
13
21
22
23
BLK-1
BLK-2
BLK-3
BLK
YEL
BLU
BLK
YEL
BLU
OFM2
GRN/YEL
CHC
CHC
1
4
2
6
BLK
WHT
BLK
BLK
BLK
1
2
3
2
COOLER/PUMP
COOLER/PUMP
HEATERS
(208/230,230V)
HEATERS
(380,460,575V)
a30-4977
8
BLK
WHT
YEL
3
LEGEND
AUX — Auxiliary
CONFIGURATION TABLE
CONTROL INPUT
FB
— Fuse Block
MODE
NOMINAL VOLTAGE
Hz
START JUMPER
(PINS 25, 2)
MM — Motormaster
OFM — Outdoor Fan Motor
5
6
208/230/460/575*
208/380
60
60
External control 4-20 mA
External control 4-20 mA
TB1-TB2
TB13A-TB2
TB
— Terminal Block
*208-v can run in mode 5 or 6.
Fig. 32 — Typical Motormaster Wiring
L1
L2
L3
EPM
Mode
DANGER
MMV
TERMINAL
BLOCK
T1
T3
B+
T2
B-
DISPLAY
BUTTONS
Mode
Fig. 33 — Motormaster® V Mode Buttons and Mode Display
60
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 38 — Fault Codes
FAULT CODE
DESCRIPTION
SOLUTION
AF
CF
cF
High Temperature Fault: Ambient temperature is too high;
Cooling fan has failed (if equipped).
Control Fault: A blank EPM, or an EPM with corrupted data Perform a factory reset using Parameter 48 —
has been installed. PROGRAM SELECTION.
Incompatibility Fault: An EPM with an incompatible parame- Either remove the EPM or perform a factory
ter version has been installed.
Check cooling fan operation
reset (Parameter 48) to change the parameter
version of the EPM to match the parameter
version of the drive.
CL
CURRENT LIMIT: The output current has exceeded the
CURRENT LIMIT setting (Parameter 25) and the drive is
Check for loose electrical connections.
Check for faulty condenser fan motor.
reducing the output frequency to reduce the output current. Check Parameter P25 from Table 39 is set
If the drive remains in CURRENT LIMIT too long, it can trip correctly.
into a CURRENT OVERLOAD fault (PF).
GF
HF
JF
Data Fault: User data and OEM defaults in the EPM are
corrupted.
High DC Bus Voltage Fault: Line voltage is too high; Decel- Check line voltage — set P01 appropriately
eration rate is too fast; Overhauling load.
Serial Fault: The watchdog timer has timed out, indicating
that the serial link has been lost.
Restore factory defaults P48, see section
above. If that does not work, replace EPM.
Check serial connection (computer)
Check settings for PXX.
Check settings in communication software to
match PXX.
LF
Low DC Bus Voltage Fault: Line voltage is too low.
Check line voltage — set P01 appropriately
OF
Output Transistor Fault: Phase to phase or phase to ground Reduce boost or increase acceleration values.
short circuit on the output; Failed output transistor; Boost
settings are too high; Acceleration rate is too fast.
If unsuccessful, replace drive.
PF
SF
Current Overload Fault: VFD is undersized for the applica- Check line voltage — set P01 appropriately
tion; Mechanical problem with the driven equipment.
Check for dirty coils
Check for motor bearing failure
Single-phase Fault: Single-phase input power has been
applied to a three-phase drive.
Check input power phasing
F1
EPM Fault: The EPM is missing or damaged.
F2-F9, Fo
Internal Faults: The control board has sensed a problem
Consult factory
Drive display = 60.0 even though it Feedback signal is above set point
is cold outside and it should be run-
ning slower
Check for proper set point
Check liquid line pressure
Drive display = ‘---’ even though
drive should be running
Start jumper is missing
Replace start jumper. See section above
Drive display = 8.0 even though fan Feedback signal is below set point and fan is at minimum
Check for proper set point
Check liquid line pressure
should be running faster
VFD flashes 57 and LCS
speed
Feedback or speed signal lost. Drive will operate at 57 Hz In stand alone mode: Check transducer wiring
until reset or loss of start command. Resetting requires
cycling start command (or power).
and feedback voltage. Feedback voltage dis-
played on P-69. Pin 6 should be 5 v output.
Pin 5 (feedback) should be somewhere
between 0 and 5 v.
LEGEND
EPM
LCS
OEM
VFD
— Electronic Programming Module
— Lost Control Signal
— Outside Equipment Manufacturer
— Variable Frequency Drive
61
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 39 — Motormaster® V Program Parameters for Operating Modes
MODE
5
MODE
6
MODE
7
MODE
8
PARAMETERS
DESCRIPTION
P01
P02
P03
P04
Line Voltage: 01 = low line, 02 = high line
Carrier Freq: 01 = 4 kHz, 02 = 6 kHz, 03 = 8 kHz
Startup mode: flying restart
01
01
06
01
02
01
06
01
01
01
06
01
02
01
06
01
Stop mode: coast to stop
Standard Speed source: 01= keypad,
04=4-20mA (NO PI), 05= R22, 06=R134a
P05
04
04
04
04
P06
P08
P09
P10
P11
P12
P13
P14
P15
P16
P17
P19
P20
P21
P22
P23
P24
P25
P26
P27
P28
P29
P30
P31
P32
P33
TB-14 output: 01 = none
TB-30 output: 01 = none
TB-31 Output: 01 = none
TB-13A function sel: 01 = none
TB-13B function sel: 01 = none
TB-13C function sel: 01 = none
TB-15 output: 01 = none
Control: 01 = Terminal strip
Serial link: 02 = enabled 9600,8,N,2 with timer
Units editing: 02 = whole units
Rotation: 01 = forward only, 03 = reverse only
Acceleration time: 10 sec
Deceleration time: 10 sec
DC brake time: 0
DC BRAKE VOLTAGE 0%
Min freq = 8 Hz ~ 100 – 160 rpm
Max freq
Current limit: (%)
Motor overload: 100
Base freq: 60 or 50 Hz
Fixed boost: 0.5% at low frequencies
Accel boost: 0%
Slip compensation: 0%
Preset spd #1: speed if loss of control signal
Preset spd #2: 0
01
01
01
01
01
01
01
01
02
02
01
10
10
0
01
01
01
01
01
01
01
01
02
02
01
10
10
0
01
01
01
01
01
01
01
01
02
02
01
10
10
0
01
01
01
01
01
01
01
01
02
02
01
10
10
0
0
8
0
8
0
8
0
8
60
125
100
60
0.5
0
0
57
0
60
110
100
60
0.5
0
0
57
0
50
125
100
50
0.5
0
0
47
0
50
110
100
50
0.5
0
0
47
0
Preset spd #3: 0
0
0
0
0
Preset spd 4 default — R22 set point.
TB12-2 open
Preset spd 5 default — R134a set point.
TB12-2 closed
P34
P35
18.0
12.6
18.0
12.6
18.0
12.6
18.0
12.6
P36
P37
P38
P39
P40
P41
P42
P43
P44
Preset spd 6 default
Preset spd 7 default
Skip bandwidth
Speed scaling
Frequency scaling 50 or 60 Hz
Load scaling: default (not used so NA)
Accel/decel #2: default (not used so NA)
Serial address
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
60
200
60
1
60
200
60
1
50
200
60
1
50
200
60
1
Password:111
111
111
111
111
Speed at min signal: 8 Hz; used when PID
mode is disabled and 4-20mA input is at 4 mA
Speed at max feedback: 60 or 50 Hz. Used
when PID disabled and 4-20mA input is at 20 mA
P45
P46
8
8
8
8
60
60
50
50
P47
P48
P61
P62
P63
P64
P65
P66
P67
P68
Clear history? 01 = maintain. (set to 02 to clear)
Program selection: Program 1 – 12
PI Mode: 05= reverse, 0-5V, 01 = no PID
Min feedback = 0 (0V *10)
Max feedback = 50 (5V * 10)
Proportional gain = 4%
Integral gain = .2
PI acell/decel (set point change filter) = 5
Min alarm
01
05
01
0
50
4
.2
5
0
01
06
01
0
50
4
.2
5
0
01
07
01
0
50
4
.2
5
0
01
08
01
0
50
4
.2
5
0
Max alarm
0
0
0
0
LEGEND
NA — Not Applicable
PID — Proportional Integral Derivative
TB — Terminal Block
62
Download from Www.Somanuals.com. All Manuals Search And Download.
uncommon for actual pump duty to be different than what was
anticipated at time of selection. In many cases, it may be desir-
able to make some field modifications to obtain optimum
pump performance.
Before any pump modifications are made, it is recommend-
ed that actual pump performance be verified and compared to
the applicable pump curve. See base unit installation instruc-
tions. This can be done in a variety of ways:
WARNING
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all discon-
nect locations to alert others not to restore power until work
is completed.
1. If pump impeller diameter is known:
1. Check that all power to unit is off. Carefully disconnect
all wires from the defective module by unplugging its
connectors.
a. Connect a differential pressure gage across the
pump at the ports provided on the pump volutes.
b. Read GPM from applicable impeller curve.
2. If pump impeller diameter is not known:
2. Remove the defective module by removing its mounting
screws with a Phillips screwdriver, and removing the
module from the control box. Save the screws later use.
3. Verify that the instance jumper (MBB) or address switch-
es (all other modules) exactly match the settings of the
defective module.
NOTE: Handle boards by mounting standoffs only to
avoid electrostatic discharge.
4. Package the defective module in the carton of the new
module for return to Carrier.
If pump impeller diameter has been trimmed and the size
is not known, it is necessary to determine which impeller
curve to read.
The easiest way to confirm pump performance is to
“dead-head” the pump and read the differential pressure
across the pressure ports on the pump. “Dead-heading”
can be done by shutting the circuit setter valve on the dis-
charge side of the pump.
NOTE: Although not all pumps can be safely “dead-
headed”, centrifugal pumps (such as on the 30RAP units)
can be “dead-headed” for short amounts of time. It is rec-
ommended to keep the time short due to excessive heat
build-up in the pump.
5. Mount the new module in the unit’s control box using a
Phillips screwdriver and the screws saved in Step 2.
6. Reinstall all module connectors. For accessory Navigator
replacement, make sure the plug is installed at TB3 in the
LEN connector.
Since the “dead-head” condition is a no-flow condition,
the head will correspond to the intersection of an impel-
ler curve with the vertical axis of the pump chart. The
correct impeller diameter is that which corresponds to the
measured head.
7. Carefully check all wiring connections before restoring
power.
8. Verify the ENABLE/OFF/REMOTE CONTACT switch
is in the OFF position.
9. Restore control power. Verify that all module red LEDs
blink in unison. Verify that all green LEDs are blinking
and that the scrolling marquee or Navigator™ display is
communicating correctly.
10. Verify all configuration information, settings, set points
and schedules. Return the ENABLE/OFF/REMOTE
CONTACT switch to its previous position.
3. Once the impeller diameter is known, proceed as in
Step 1.
4. Water flow rate can be determined by using a differential
pressure gage with the Bell & Gossett circuit setter bal-
ance valve calculator. (This information is also provided
in the installation instructions.) This method will not di-
rectly measure pressure differential seen by the pump, but
can be used to “double-check” the pump measurement.
5. Verify that cable connections at the switch and at the ter-
minal block are secure.
6. For factory-installed hydronic system, verify that:
Table 40 — Replacement Modules
REPLACEMENT
PART NO. (with
Software)
REPLACEMENT PART
NO. (without Software)
MODULE
Main Base
• All air has been purged from the system.
30RA502134
HK50AA029
Board (MBB)
• Circuit setter balance valve has been correctly set.
Scrolling
Marquee
Display
7. Pump impeller has been improperly trimmed and is not
providing sufficient flow.
HK50AA031
HK50AA030
Energy
Management
Module
8. Wrong pump motor rotation. Pump must rotate clockwise
when viewed from motor end of pump.
PUMP MODIFICATIONS AND IMPELLER TRIMMING
— See applicable section in the Installation instructions.
RESET OF CHILLER WATER FLOW — See applicable sec-
tion in the Installation instructions.
CHANGING OF PUMP SEALS — See Bell & Gossett ser-
vice instruction manual provided with the hydronic package.
30GT515218
HK50AA033
HK50AA028
N/A
(EMM)
Navigator
Display
EXV
AUX
30GT515217
32GB500442E
HK50AA026
N/A
Hydronic Package — If the unit is equipped with a
factory-installed hydronic package, consult the information be-
low for proper maintenance and service. In addition to this
information, each factory-installed hydronic package is sup-
plied with a packet of information supplied by the manufactur-
er, Bell & Gossett. Carrier Corporation strongly recommends
that this information be thoroughly reviewed prior to operation
of the chiller.
PUMP PERFORMANCE CHECK — The factory-installed
pumps in the 30RAP units are shipped with a single impeller
size available for that pump. The pump was selected based on
the flow and head requirements as provided to Carrier. It is not
MAINTENANCE
Recommended Maintenance Schedule — The fol-
lowing are only recommended guidelines. Jobsite conditions
may dictate that maintenance schedule is performed more often
than recommended.
Routine:
For machines with e-coat condenser coils:
•
Periodic clean water rinse, especially in coastal and
industrial applications.
63
Download from Www.Somanuals.com. All Manuals Search And Download.
•
Check condenser coils for debris, clean as necessary.
Every month:
Check moisture indicating sight glass for possible refrig-
erant loss and presence of moisture.
Every 3 months (for all machines):
core face. Reduce pressure and use caution to prevent
damage to air centers.
•
CAUTION
Excessive water pressure will fracture the braze between
air centers and refrigerant tubes.
•
•
Check refrigerant charge.
Check all refrigerant joints and valves for refrigerant
leaks, repair as necessary.
•
•
•
Check chilled water flow switch operation.
Check all condenser fans for proper operation.
Check compressor oil level.
TROUBLESHOOTING
Complete Unit Stoppage and Restart — Possi-
ble causes for unit stoppage and reset methods are shown be-
low and in Table 41. Refer to Fig. 3-7 for component arrange-
ment and control wiring diagrams.
GENERAL POWER FAILURE — After power is restored,
restart is automatic through normal MBB start-up.
UNIT ENABLE-OFF-REMOTE CONTACT SWITCH IS
OFF — When the switch is OFF, the unit will stop immediate-
ly. Place the switch in the ENABLE position for local switch
control or in the REMOTE CONTACT position for control
through remote contact closure.
CHILLED FLUID PROOF-OF-FLOW SWITCH OPEN —
After the problem causing the loss of flow has been corrected,
reset is manual by resetting the alarm with the scrolling mar-
quee as shown in Table 42.
OPEN 24-V CONTROL CIRCUIT BREAKER(S) — De-
termine the cause of the failure and correct. Reset circuit break-
er(s). Restart is automatic after MBB start-up cycle is
complete.
COOLING LOAD SATISFIED — Unit shuts down when
cooling load has been satisfied. Unit restarts when required to
satisfy leaving fluid temperature set point.
Every 12 months (for all machines):
•
•
•
Check all electrical connections, tighten as necessary.
Inspect all contactors and relays, replace as necessary.
Check accuracy of thermistors, replace if greater than
± 2° F (1.2° C) variance from calibrated thermometer.
Obtain and test an oil sample. Change oil only if
necessary.
Check to be sure that the proper concentration of anti-
freeze is present in the chilled water loop, if applicable.
Verify that the chilled water loop is properly treated.
Check refrigerant filter driers for excessive pressure
drop, replace as necessary.
Check chilled water strainers, clean as necessary.
Check cooler heater operation, if equipped.
Check condition of condenser fan blades and that they
are securely fastened to the motor shaft.
Perform Service Test to confirm operation of all
components.
•
•
•
•
•
•
•
•
•
Check for excessive cooler approach (Leaving Chilled
Water Temperature — Saturated Suction Temperature)
which may indicate fouling. Clean cooler vessel if
necessary.
THERMISTOR FAILURE — If a thermistor fails in either an
open or shorted condition, the unit will be shut down. Replace
EWT, LWT, or OAT as required. Unit restarts automatically,
but must be reset manually by resetting the alarm with the
scrolling marquee as shown in Table 42.
Microchannel Heat Exchanger (MCHX) Con-
denser Coil Maintenance and Cleaning
Recommendations
CAUTION
CAUTION
Do not apply any chemical cleaners to MCHX condenser
coils. These cleaners can accelerate corrosion and damage
the coil.
If unit stoppage occurs more than once as a result of any of
the safety devices listed, determine and correct cause
before attempting another restart.
Routine cleaning of coil surfaces is essential to maintain
proper operation of the unit. Elimination of contamination and
removal of harmful residues will greatly increase the life of the
coil and extend the life of the unit. The following steps should
be taken to clean MCHX condenser coils:
1. Remove any foreign objects or debris attached to the
coreface or trapped within the mounting frame and
brackets.
2. Put on personal protective equipment including safety
glasses and/or face shield, waterproof clothing and
gloves. It is recommended to use full coverage clothing.
3. Start high pressure water sprayer and purge any soap or
industrial cleaners from sprayer before cleaning condens-
er coils. Only clean, potable water is authorized for clean-
ing condenser coils.
LOW SATURATED SUCTION — Several conditions can
lead to low saturated suction alarms and the chiller controls
have several override modes built in which will attempt to keep
the chiller from shutting down. Low fluid flow, low refrigerant
charge and plugged filter driers are the main causes for this
condition. To avoid permanent damage and potential freezing
of the system, do NOT repeatedly reset these alert and/or alarm
conditions without identifying and correcting the cause(s).
COMPRESSOR SAFETIES — The 30RAP units with Com-
fortLink™ controls include a compressor protection board that
protects the operation of each of the compressors. Each board
senses the presence or absence of current to each compressor.
If there is a command for a compressor to run and there is
no current, then one of the following safeties or conditions
have turned the compressor off:
Compressor Overcurrent — All compressors have internal
line breaks or a motor protection device located in the com-
pressor electrical box.
4. Clean condenser face by spraying the core steady and
uniformly from top to bottom while directing the spray
straight toward the core. Do not exceed 900 psig or 30 de-
gree angle. The nozzle must be at least 12 in. from the
Compressor Short Circuit — There will not be current if the
compressor circuit breaker that provides short circuit protection
has tripped.
Compressor Motor Over Temperature — The internal line-
break or over temperature switch has opened.
64
Download from Www.Somanuals.com. All Manuals Search And Download.
High-Pressure Switch Trip — The high pressure switch has
opened. Below are the factory settings for the fixed high pres-
sure switch.
reset automatically before the motor protector resets, which
may take up to 2 hours.
High Discharge Gas Temperature Protection — Units
equipped with digital compressors have an additional thermis-
tor located on the discharge line, If discharge temperature ex-
ceeds 265 F (129.4 C), the digital compressor will be shut off.
CUTOUT
CUT-IN
30RAP UNIT
SIZE
psig
kPa
psig
kPa
010-060
650
4482
500
3447
Alarms will also occur if the current sensor board malfunc-
tions or is not properly connected to its assigned digital input. If
the compressor is commanded OFF and the current sensor
reads ON, an alert is generated. This will indicate that a com-
pressor contactor has failed closed. In this case, a special mode,
Compressor Stuck on Control, will be enabled and all other
compressors will be turned off. An alarm will then be enabled
to indicate that service is required. Outdoor fans will continue
to operate. The first outdoor fan stage is turned on immediately.
The other stages of fan will be turned on as required by SCT.
ASTP Protection Trip — All non-digital Copeland compres-
sors are equipped with an advanced scroll temperature protec-
tion (ASTP). A label located above the terminal box identifies
models that contain this technology. See Fig. 34.
Alarms and Alerts — These are warnings of abnormal
or fault conditions, and may cause either one circuit or the
whole unit to shut down. They are assigned code numbers as
described in Table 42.
Automatic alarms will reset without operator intervention if
the condition corrects itself. The following method must be
used to reset manual alarms:
Before resetting any alarm, first determine the cause of the
alarm and correct it. Enter the Alarms mode indicated by the
LED on the side of the scrolling marquee display. Press
Fig. 34 — Advanced Scroll Temperature
Protection Label
Advanced scroll temperature protection is a form of inter-
nal discharge temperature protection that unloads the scroll
compressor when the internal temperature reaches approxi-
mately 300 F. At this temperature, an internal bi-metal disk
valve opens and causes the scroll elements to separate, which
stops compression. Suction and discharge pressures balance
while the motor continues to run. The longer the compressor
runs unloaded, the longer it must cool before the bi-metal disk
resets. See Fig. 35 for approximate reset times.
and
until the sub-menu item RCRN “RESET
ENTER
ALL CURRENT ALARMS” is displayed. Press
.
ENTER
The control will prompt the user for a password, by displaying
PASS and WORD. Press to display the default pass-
ENTER
for each character. If the password
word, 1111. Press
ENTER
has been changed, use the arrow keys to change each individu-
To manually reset ASTP, the compressor should be stopped
and allowed to cool. If the compressor is not stopped, the motor
will run until the motor protector trips, which occurs up to
90 minutes later. Advanced scroll temperature protection will
al character. Toggle the display to “YES” and press
The alarms will be reset.
.
ENTER
120
110
100
90
80
70
60
50
40
30
20
10
0
0
10
20
30
40
50
60
70
80
90
Compressor Unloaded Run Time (Minutes)
*Times are approximate.
NOTE: Various factors, including high humidity, high ambient temperature,
and the presence of a sound blanket will increase cool-down times.
Fig. 35 — Recommended Minimum Cool Down Time After Compressor is Stopped*
65
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 41 — Troubleshooting
SYMPTOMS
CAUSE
REMEDY
Cooler Circulating Pump Does
Not Run
Power line open
Reset circuit breaker.
Control fuse or circuit breaker open
Check control circuit for ground or short. Reset breaker and
replace fuse.
Tripped power breaker
Loose terminal connection
Improperly wired controls
Low line voltage
Check the controls. Find the cause of trip and reset breaker.
Check connections.
Check wiring and rewire if necessary.
Check line voltage — determine location of
voltage drop and remedy deficiency.
Pump motor defective
Check motor winding for open or short.
Replace compressor if necessary.
Pump seized
Replace pump.
Compressor Cycles
Off on Loss of Charge
Low refrigerant charge
Repair leak and recharge.
Compressor Cycles Off on Cooler
Freeze Protection
Thermistor failure
Replace thermistor.
System load was reduced faster than controller could
remove stages
Unit will restart after fluid temperature rises back into the
control band. Avoid rapidly removing system load.
Compressor Shuts Down on
High-Pressure Control
High-pressure control acting erratically
Noncondensables in system
Condenser dirty
Replace control.
Evacuate and recharge.
Clean condenser.
Fans not operating
Repair or replace if defective.
Reduce charge.
System overcharged with refrigerant
Low refrigerant charge
Unit Operates Too Long
or Continuously
Add refrigerant.
Control contacts fused
Replace control.
Partially plugged or plugged expansion valve or filter drier
Defective insulation
Clean or replace as needed.
Replace or repair as needed.
Check compressor and replace if necessary.
Support piping as required.
Check for loose pipe connections or damaged compressor
Replace compressor (worn bearings).
Check for loose compressor holddown bolts.
Repair leak.
Damaged compressor
Unusual or Loud System
Noises
Piping vibration
Compressor noisy
Compressor Loses Oil
Leak in system
Mechanical damage (Failed seals or broken scrolls)
Oil trapped in line
Replace compressor.
Check piping for oil traps.
Repair leak and recharge.
Replace filter drier.
Hot Liquid Line
Shortage of refrigerant due to leak
Restricted filter drier
Frosted Liquid Line
Frosted Suction Line
Expansion valve admitting excess refrigerant (note: this is a Replace valve if defective.
normal condition for brine applications)
Stuck EXV
Replace valve if defective.
Freeze-Up
Improper charging
Make sure a full quantity of fluid is flowing through the cooler
while charging, and suction pressure in cooler is equal to or
greater than pressure corresponding to 32 F (0° C).
System not drained for winter shutdown
Loose Thermistor
Recommended that system be filled with an appropriate gly-
col mixture to prevent freezing of pumps and fluid tubing.
Verify thermistors are fully inserted in wells.
66
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 42 — Alarm and Alert Codes
ALARM/ ALARM
WHY WAS THIS
ACTION TAKEN
BY CONTROL
RESET
METHOD
PROBABLE
CAUSE
ALERT
CODE
OR
DESCRIPTION
ALARM
ALERT
GENERATED?
High-pressure switch open,
faulty CSB, loss of condenser
Manual air, filter drier plugged, non-
condensables, operation
beyond capability.
Circuit A, Compressor 1
Failure
Compressor feedback signal
does not match relay state
Compressor A1 shut
down.
T051
A051
T052
A052
T055
A055
T056
A056
Alert
Alarm
Alert
Respective current sensor
board (CSB) feedback signal
is ON when the compressor
should be off
Circuit A, Compressor 1
Failure
Welded compressor contac-
Manual
Unit shut down
tor, CSB wiring error.
High-pressure switch open,
faulty CSB, loss of condenser
Manual air, filter drier plugged, non-
condensables, operation
Circuit A, Compressor 2
Failure
Compressor feedback signal
does not match relay state
Compressor A2 shut
down.
beyond capability.
Respective current sensor
board (CSB) feedback signal
is ON when the compressor
should be off
Circuit A, Compressor 2
Failure
Welded compressor contac-
Manual
Alarm
Alert
Unit shut down
tor, CSB wiring error.
High-pressure switch open,
faulty CSB, loss of condenser
Manual air, filter drier plugged, non-
condensables, operation
Circuit B, Compressor 1
Failure
Compressor feedback signal
does not match relay state
Compressor B1 shut
down.
beyond capability.
Respective current sensor
board (CSB) feedback signal
is ON when the compressor
should be off
Circuit B, Compressor 1
Failure
Welded compressor contac-
Manual
Alarm
Alert
Unit shut down
tor, CSB wiring error.
High-pressure switch open,
faulty CSB, loss of condenser
Manual air, filter drier plugged, non-
condensables, operation
Circuit B, Compressor 2
Failure
Compressor feedback signal
does not match relay state
Compressor B2 shut
down.
beyond capability.
Respective current sensor
board (CSB) feedback signal
is ON when the compressor
should be off
Circuit B, Compressor 2
Failure
Welded compressor contac-
Manual
Alarm
Unit shut down
tor, CSB wiring error.
Cooler Leaving Fluid
Thermistor Failure
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
Chiller shut down
immediately
Thermistor failure, damaged
Automatic
A060
A061
Alarm
Alarm
cable/wire or wiring error.
Cooler Entering Fluid
Thermistor Failure
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
Chiller shut down
immediately
Thermistor failure, damaged
Automatic
cable/wire or wiring error.
If return gas sensors are
enabled (RG.EN) and
Thermistor failure, damaged
Automatic
T068
T069
None
None
Circuit A Return Gas Thermistor Failure
Circuit B Return Gas Thermistor Failure
Circuit A shut down
Circuit B shut down
thermistor is outside range of
–40 to 245 F (–40 to 118 C)
cable/wire or wiring error.
If return gas sensors are
enabled (RG.EN) and
thermistor is outside range of
–40 to 245 F –40 to 118 C)
Thermistor failure, damaged
Automatic
cable/wire or wiring error.
Temperature reset
disabled. Chiller runs
under normal control/set
points. When capacity
reaches 0, cooler/pump
heaters are energized.
Outside Air Thermistor
Failure
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
Thermistor failure, damaged
Automatic
T073
Alert
cable/wire or wiring error.
Temperature reset
disabled. Chiller runs
under normal control/set
points.
Space Temperature/Dual Chiller
Thermistor Failure
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
Thermistor failure, damaged
Automatic
T074
T077
T078
Alert
Alert
Alert
cable/wire or wiring error.
Circuit A Saturated
Suction Temperature
exceeds Cooler Leaving
Fluid Temperature
Faulty expansion valve or
Faulty expansion valve,
suction pressure transducer
or leaving fluid thermistor.
Circuit A shutdown after
pumpdown complete.
suction pressure transducer
Automatic
or leaving fluid
thermistor.
Circuit B Saturated
Suction Temperature
exceeds Cooler Leaving
Fluid Temperature
Faulty expansion valve or
Faulty expansion valve,
suction pressure transducer
or leaving fluid thermistor.
Circuit B shutdown after
pumpdown complete
suction pressure transducer
Automatic
or leaving fluid
thermistor.
Dual LWT thermistor failure,
Automatic damaged cable/wire or
wiring error.
Lead/Lag LWT
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
Chiller runs as a stand
alone machine
T079
T090
T091
T092
Alert
Alert
Alert
Alert
Thermistor Failure
Transducer failure, poor
Automatic connection to MBB, or wiring
damage/error.
Circuit A Discharge
Pressure Transducer Failure
Outside of range (0 to
667 psig)
Circuit A shut down
Circuit B shut down
Circuit A shut down
Circuit B shut down
Transducer failure, poor
Automatic connection to MBB, or wiring
damage/error.
Circuit B Discharge
Pressure Transducer Failure
Outside of range (0 to
667 psig)
Transducer failure, poor
Automatic connection to MBB, or wiring
damage/error.
Circuit A Suction
Pressure Transducer Failure
Outside of range (0 to 420
psig)
Circuit B Suction
Pressure Transducer
Failure
Transducer failure, poor
Automatic connection to MBB, or wiring
damage/error.
Outside of range (0 to
420 psig)
T093
T094
Alert
Alert
Discharge Gas
Thermistor Failure
Discharge thermistor (DTT) is Digital compressor shut
either open or shorted
Thermistor failure, damaged
Automatic
down.
cable/wire or wiring error.
67
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 42 — Alarm and Alert Codes (cont)
ALARM/
ALERT
CODE
ALARM
OR
ALERT
WHY WAS THIS
ACTION TAKEN
ALARM
RESET
METHOD
PROBABLE
CAUSE
DESCRIPTION
BY CONTROL
GENERATED?
If the compressors are off
and discharge pressure
reading is < 26 psig for
30 sec.
Circuit not allowed to
start.
Refrigerant leak or
transducer failure
T110
T111
T112
T113
Alert
Alert
Alert
Alert
Circuit A Loss of Charge
Manual
Manual
Manual
Manual
If the compressors are off
and discharge pressure
reading is < 26 psig for
30 sec.
Circuit not allowed to
start.
Refrigerant leak or
transducer failure
Circuit B Loss of Charge
Circuit saturated suction
temperature pressure
transducer > 70 F (21.1 C)
for 5 minutes
Faulty Expansion valve,
faulty suction pressure
transducer or high entering
fluid temperature.
Circuit A High Saturated
Suction Temperature
Circuit shut down
Circuit shut down
Circuit saturated suction
temperature pressure
transducer > 70 F (21.1 C)
for 5 minutes
Faulty Expansion valve,
faulty suction pressure
transducer or high entering
fluid temperature.
Circuit B High Saturated
Suction Temperature
Automatic restart Faulty expansion valve,
Suction superheat is
less than 5° F (2.8 C) for 5
minutes.
after first daily
occurrence.
Manual restart
thereafter.
faulty suction pressure
transducer, faulty suction gas
thermistor, circuit
Circuit A Low Suction
Superheat
T114
T115
T116
T117
Alert
Alert
Alert
Alert
Circuit A shut down.
Circuit B shut down.
Circuit shut down
Circuit shut down
overcharged
Automatic restart Faulty expansion valve,
Suction superheat is
less than 5° F (2.8 C) for 5
minutes.
after first daily
occurrence.
Manual restart
thereafter.
faulty suction pressure
transducer, faulty suction
gas thermistor, circuit
overcharged
Circuit B Low Suction
Superheat
Mode 7 caused the com-
pressor to unload 6 consecu-
tive times with less than a
30-minute interval between
each circuit shutdown.
Faulty expansion valve, low
refrigerant charge, plugged
filter drier, faulty suction
pressure transducer, low
cooler fluid flow
Circuit A Low Cooler
Suction Temperature
Manual
Manual
Mode 8 caused the com-
pressor to unload 6 consecu-
tive times with less than a
30-minute interval between
each circuit shutdown.
Faulty expansion valve, low
refrigerant charge, plugged
filter drier, faulty suction
pressure transducer, low
cooler fluid flow
Circuit B Low Cooler
Suction Temperature
Refrigerant charge, plugged
filter drier, head pressure
control.
High Discharge Gas
Temperature Alert
Discharge Thermistor (DTT) Compressor A1 shut
reading is greater than 250 F down
T118
A118
Alert
Automatic
Manual
3 Discharge Gas Tempera-
Compressor A1 shut
ture alarms occur within a
down
Refrigerant charge, plugged
filter drier, head pressure
control.
High Discharge Gas
Temperature
Alarm
day
Automatic, only
after first 3 daily
occurrences.
Faulty transducer/high
pressure switch, low/
restricted condenser
airflow
Manual reset
Circuit A High
Compressor operation out-
Circuit shut down
T126
T127
Alert
Alert
thereafter. Read-
ing from OAT sen-
sor must drop 5 F
(2.8 C) before
restart
Discharge Pressure
side of operating envelope.
Automatic, only
after first 3 daily
occurrences. Man- Faulty transducer/high
ual reset thereafter. pressure switch, low/
Reading from OAT restricted condenser
Circuit B High
Discharge Pressure
Compressor operation out-
Circuit shut down
side of operating envelope.
sensor must drop
5 F (2.8 C) before
restart
airflow
Automatic
Suction pressure below
restart after first
daily occurrence.
Manual restart
thereafter.
Faulty or sticking EXV, low
refrigerant charge, plugged
filter drier.
Circuit A Low Suction
Pressure
T133
T134
Alert
Alert
34 psig for 8 seconds or
below 23 psig
Circuit shut down
Circuit shut down
Automatic
Suction pressure below
34 psig for 8 seconds or
below 23 psig
restart after first
daily occurrence.
Manual restart
thereafter.
Faulty or sticking EXV, low
refrigerant charge, plugged
filter drier.
Circuit B Low Suction
Pressure
Reverse any two incoming
power leads to correct. Check
for correct fan rotation first.
Reverse Rotation
Detected
Incoming chiller power leads Chiller not allowed to
A140
A150
A151
Alert
Alarm
Alarm
Manual
not phased correctly
start.
Automatic once
Chiller shutdown
without going through
pumpdown.
CCN emergency stop
command received
CCN command for CCN Network
EMSTOP returns to command.
normal
Emergency Stop
Manual once
configuration errors
are corrected
One or more illegal
configurations exists.
Chiller is not allowed to
start.
Configuration error.
Check unit settings.
Illegal Configuration
Automatic once
alarms/alerts are
cleared that pre-
Alarm notifies user
that chiller is 100%
Unit Down Due to
Failure
Both circuits are down due
to alarms/alerts.
Chiller is unable
to run.
A152
Alarm
vent the chiller from down.
starting.
68
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 42 — Alarm and Alert Codes (cont)
ALARM/
ALERT
CODE
ALARM
OR
ALERT
WHY WAS THIS
ACTION TAKEN
ALARM
RESET
METHOD
PROBABLE
CAUSE
DESCRIPTION
BY CONTROL
GENERATED?
Occupancy schedule
Automatic when
correct clock control
restarts.
Time/Date/Month/
Day/Year not
properly set.
Real Time Clock
Hardware Failure
will not be used. Chiller
T153
A154
Alert
Internal clock on MBB fails
defaults to Local On
mode.
Serial EEPROM
Hardware Failure
Chiller is unable
Hardware failure with MBB
to run.
Main Base Board
failure.
Alarm
Manual
Potential failure of
MBB. Download
current operating
software. Replace
MBB if error occurs
again.
Serial EEPROM
Storage Failure
Configuration/storage
No Action
T155
Alert
Manual
failure with MBB
Critical Serial EEPROM
Storage Failure
Configuration/storage
failure with MBB
Chiller is not allowed
to run.
Main Base Board
failure.
A156
A157
Alarm
Alarm
Manual
Manual
Hardware failure with
peripheral device
Chiller is not allowed
to run.
Main Base Board
failure.
A/D Hardware Failure
Wiring error, faulty
wiring or failed
EXV board.
Loss of Communication
with EXV Board
MBB loses communication
with EXV board
Chiller is not allowed
to run.
A172
Alarm
Automatic
4 to 20 mA
temperature reset
disabled. Demand
Limit set to 100%. 4 to
20 mA set point
disabled.
Wiring error, faulty
wiring or failed
Energy Manage-
ment Module (EMM).
Loss of Communication
with EMM
MBB loses communication
with EMM
T173
Alert
Automatic
If configured with EMM and
input less than 2 mA or
greater than 22 mA
Set point function
disabled. Chiller
controls to CSP1.
Faulty signal
4 to 20 mA Cooling Set
Point Input Failure
T174
T175
Alert
Alert
Automatic
Automatic
generator, wiring
error, or faulty EMM.
Wiring error, faulty
wiring or failed
AUX board.
Loss of Communication
with the AUX Board
MBB loses communication
with AUX Board.
Reset function
4 to 20 mA
If configured with EMM
and input less than 2 mA or
greater than 22 mA
Faulty signal
disabled. Chiller
returns to normal set
point control.
T176
T177
Alert
Alert
Temperature Reset
Input Failure
Automatic
Automatic
generator, wiring
error, or faulty EMM.
Demand limit function
disabled. Chiller
returns to 100%
demand limit
If configured with EMM and
input less than 2 mA or
greater than 22 mA
Faulty signal
generator, wiring
error, or faulty EMM.
4 to 20 mA Demand
Limit Input Failure
control.
Pump 1 Auxiliary Contacts
are closed when Pump 2
output is energized or if
Pump 2 Auxiliary Contacts
are closed when Pump 1
output is energized.
Wiring error, faulty
pump contactor
auxiliary contacts.
Cooler Pump Auxiliary
Contact Inputs Miswired
Both pump outputs
are turned off.
A189
Alarm
Manual
Pump 1 Auxiliary Contacts
did not close within
26 seconds after pump
was started
Cooler Pump 1 Aux
Contacts Failed to Close
at Start-Up
Pump 1 turned off.
Pump 2 will be started
if available.
Wiring error, faulty
contacts on pump
contactor
T190
T191
T192
T193
Alert
Alert
Alert
Alert
Manual
Manual
Manual
Manual
Pump 2 Auxiliary Contacts
did not close within
26 seconds after pump
was started
Cooler Pump 2 Aux
Contacts Failed to Close
at Start-Up
Pump 2 turned off.
Pump 1 will be started
if available.
Wiring error, faulty
contacts on pump
contactor
Wiring error, pump
circuit breaker
tripped, contactor
failure
Cooler Pump 1 Failed
to Provide Flow at
Start-Up
Pump 1 did not provide
flow to close flow switch
within 60 seconds
Pump 1 turned off.
Pump 2 will be started
if available.
Wiring error, pump
circuit breaker
tripped, contactor
failure
Cooler Pump 2 Failed
to Provide Flow at
Start-Up
Pump 2 did not provide
flow to close flow switch
within 60 seconds
Pump 1 turned off.
Pump 2 will be started
if available.
Pump 1 Auxiliary Contacts
open for 26 seconds after
initially made. All
Pump 2 will be started
if available. Chiller
allowed to run if
Pump 2 successfully
starts.
Cooler Pump 1 Aux
Contacts Opened
During Normal
Operation
Wiring error, faulty
contacts on pump
contactor
T194
T195
Alert
Alert
Manual
Manual
compressors shut down.
Pump 1 turned off.
Pump 2 Auxiliary Contacts
open for 26 seconds after
initially made. All
compressors shut down.
Pump 2 turned off.
Pump 1 will be started
if available. Chiller
allowed to run if
Pump 1 successfully
starts.
Cooler Pump 2 Aux
Contacts Opened
During Normal
Operation
Wiring error, faulty
contacts on pump
contactor
All compressors
shut down. Pump 1
turned off. Pump 2 will
be started if available.
Chiller allowed to run if
Pump 2 successfully
starts and flow switch
is closed.
Wiring error, pump
circuit breaker
tripped, contactor
failure
Cooler flow switch contacts
open for 3 seconds after
initially made
Flow Lost While Pump 1
Running
T196
Alert
Manual
69
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 42 — Alarm and Alert Codes (cont)
ALARM/
ALERT
CODE
ALARM
OR
ALERT
WHY WAS THIS
ACTION TAKEN
ALARM
RESET
METHOD
PROBABLE
CAUSE
DESCRIPTION
BY CONTROL
GENERATED?
All compressors shut
down. Pump 2 turned
off. Pump 1 will be
Wiring error, pump
circuit breaker
tripped, contactor
failure
Cooler flow switch contacts
open for 3 seconds after
initially made
Flow Lost While Pump 2
Running
started if available.
Chiller allowed to run if
Pump 1 successfully
starts and flow switch
is closed.
T197
Alert
Manual
Cooler Pump 1 Aux
Contacts Closed While
Pump Off
Pump 1 Auxiliary Contacts
closed for 26 seconds
when pump state is off
Wiring error, faulty
pump contactor
Chiller not allowed to
start
Automatic when
T198
T199
Alert
Alert
aux contacts open
(welded contacts)
Cooler Pump 2 Aux
Contacts Closed While
Pump Off
Pump 2 Auxiliary Contacts
closed for 26 seconds
when pump state is off
Wiring error, faulty
pump contactor
(welded contacts)
Chiller not allowed to
start
Automatic when
aux contacts open
Cooler flow switch contacts
failed to close within
Chiller not allowed to
start. For models with
dual pumps, the
Wiring error, pump
circuit breaker
tripped, contactor
failure, faulty flow
switch or interlock
Cooler Flow/Interlock
Contacts Failed to Close
at Start-Up
1 minute (if cooler pump
control is enabled) or
within 5 minutes (if cooler
pump control is not
T200
Alert
Manual
Manual
second pump will be
started if available
enabled) after start-up
All compressors shut
down. For models with
dual pumps, the
second pump will be
started if available
Cooler pump failure,
faulty flow switch or
interlock, pump
circuit breaker
tripped
Cooler Flow/Interlock
Contacts Opened
During Normal
Operation
Flow switch opens for at
least 3 seconds after
being initially closed
A201
A202
Alarm
Alarm
If configured for cooler
pump control and flow
switch input is closed for
5 minutes while pump
output(s) are off
Cooler Pump Interlock
Closed When Pump is
Off
Wiring error, faulty
pump contactor
(welded contacts)
Automatic when
aux contacts open
Chiller shut down
Wiring error, faulty
wiring, failed Slave
chiller MBB module,
power loss at slave
chiller, wrong slave
address.
Dual chiller control
disabled. Chiller runs
as a stand-alone
machine.
Master chiller MBB
loses communication
with slave chiller MBB
Loss of Communication
with Slave Chiller
T203
T204
Alert
Alert
Automatic
Automatic
Wiring error, faulty
wiring, failed master
chiller MBB module,
power loss at Master
chiller.
Dual chiller control
disabled. Chiller runs
as a stand-alone
machine
Slave chiller MBB loses
communication with
master chiller MBB
Loss of Communication
with Master Chiller
CCN Address for
both chillers is the
same. Must be
different. Check
CCN.A under the
OPT2 sub-mode in
Configuration at both
chillers.
Dual chiller routine
disabled. Master/slave
run as stand-alone
chillers.
Master and slave chiller
have the same CCN
address (CCN.A)
Master and Slave Chiller
with Same Address
T205
T206
A207
Alert
Alert
Automatic
Building load greater
than unit capacity,
low water/brine flow
or compressor fault.
Check for other
LWT read is greater than
LCW Alert Limit, Total
capacity is 100% and LWT
is greater than LWT
High Leaving Chilled
Water Temperature
Alert only. No action
taken.
Automatic
reading one minute ago
alarms/alerts.
Both EWT and LWT
must be at least 6 F
(3.3 C) above Brine
Freeze point
Chiller shutdown
without going through
pumpdown. Cooler
pump continues to
run a minimum of
5 minutes (if control
enabled).
Cooler Freeze
Protection
Cooler EWT or LWT is less
than Brine Freeze (BR.FZ)
Faulty thermistor,
low water flow.
Alarm
(BR.FZ).
Automatic for first,
Manual reset thereaf-
ter.
Cooler EWT is less than
LWT by 3° F (1.7° C) for
1 minute after a circuit is
started
Faulty cooler pump,
low water flow,
plugged fluid
strainer.
Chiller shutdown.
EWT or LWT
A208
T300
Alarm
Alert
Cooler pump shut off
(if control enabled).
Manual
Thermistor failure
Pump 1 Service
Countdown (P.1.DN)
expired. Complete pump 1
maintenance and enter
'YES' for Pump 1
Cooler Pump 1
Scheduled
Maintenance Due
Routine pump
maintenance
required
None
None
Automatic
Maintenance Done
(P.1.MN) item.
Pump 2 Service
Countdown (P.2.DN)
expired. Complete pump 2
maintenance and
Cooler Pump 2
Scheduled
Maintenance Due
Routine pump
maintenance
required
T301
Alert
Automatic
enter 'YES' for Pump 1
Maintenance Done
(P.2.MN) item.
70
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 42 — Alarm and Alert Codes (cont)
ALARM/
ALERT
CODE
ALARM
OR
ALERT
WHY WAS THIS
ACTION TAKEN
ALARM
RESET
METHOD
PROBABLE
CAUSE
DESCRIPTION
BY CONTROL
GENERATED?
Strainer Service
Countdown (S.T.DN)
Strainer Blowdown
Scheduled
Routine strainer
maintenance
required
expired. Complete strainer
T302
T303
Alert
Alert
None
Automatic
Automatic
blowdown and enter 'YES'
for Strainer Maintenance
Done (S.T.MN) item.
Maintenance Due
Coil Service Countdown
(C.L.DN) expired.
Routine condenser
coil maintenance
required
Condenser Coil
Maintenance Due
Complete condenser coil
None
cleaning and enter 'YES'
for Coil Maintenance Done
(C.L.MN) item.
Current Sensor Board
A1 Failure
Alert occurs when CSB out-
put is a constant high value
Compressor A1 shut
down
CSB failure.
Wiring error.
T500
T501
T502
T503
T504
Alert
Alert
Alert
Alert
Alert
Automatic
Automatic
Automatic
Automatic
Automatic
Current Sensor Board
A2 Failure
Alert occurs when CSB out-
put is a constant high value
Compressor A2 shut
down
CSB failure.
Wiring error.
Current Sensor Board
A3 Failure
Alert occurs when CSB out-
put is a constant high value
Compressor A3 shut
down
CSB failure.
Wiring error.
Current Sensor Board
B1 Failure
Alert occurs when CSB out-
put is a constant high value
Compressor B1 shut
down
CSB failure.
Wiring error.
Current Sensor Board
B2 Failure
Alert occurs when CSB out-
put is a constant high value
Compressor B2 shut
down
CSB failure.
Wiring error.
Current Sensor Board
B3 Failure
Alert occurs when CSB out-
put is a constant high value
Compressor B3 shut
down
CSB failure.
Wiring error.
T505
T950
Alert
Alert
Automatic
Automatic
Loss of Communication
with Water System
Manager
No communications have
been received by the MBB
within 5 minutes of last
transmission
WSM forces removed.
Chiller runs under own
control
Failed module, wiring
error, failed
transformer, loose
connection plug,
wrong address
T951
T952
Alert
Alert
Loss of Communication
with Chillervisor System
Manager
No communications have
been received by the MBB
within 5 minutes of last
transmission
CSM forces removed.
Chiller runs under own
control
Automatic
Automatic
Failed module, wiring
error, failed
transformer, loose
connection plug,
wrong address
Loss of Communication
with Hydronic System
Manager
No communications have
been received by the MBB
within 5 minutes of last
transmission
HSM forces removed.
Chiller runs under own
control
Failed module, wiring
error, failed
transformer, loose
connection plug,
wrong address
LEGEND FOR TABLE 42
CCN
—
—
—
—
—
—
—
—
—
—
—
—
—
Carrier Comfort Network
Current Sensor Board
CSB
EEPROM
EMM
EWT
EXV
Electronic Eraseable Programmable Read Only Memory
Energy Management Module
Entering Fluid Temperature
Electronic Expansion Valve
Hydronic System Manager
Leaving Chilled Water
HSM
LCW
LWT
Leaving Fluid Temperature
Main Base Board
MBB
OAT
Outdoor-Air Temperature
SCT
Saturated Condensing Temperature
Water System Manager
WSM
COMPRESSOR FAILURE ALERTS
T051, T052 (Circuit A Compresser Failures)
Low Refrigerant Charge — If the compressor operates for an
extended period of time with low refrigerant charge, the com-
pressor ASTP device will open, which will cause the compres-
sor to trip on its overload protection device.
Circuit Breaker Trip — The compressors are protected from
short circuit by a breaker in the control box.
T055, T056 (Circuit B Compressor Failures) — Alert codes
051, 052, 055, and 056 are for compressors A1, A2, B1, and
B2 respectively. These alerts occur when the current sensor
(CS) does not detect compressor current during compressor op-
eration. When this occurs, the control turns off the compressor.
If the current sensor board reads OFF while the compressor
relay has been commanded ON, an alert is generated.
Wiring Error — A wiring error might not allow the compres-
sor to start.
To check out alerts T051-T056:
POSSIBLE CAUSES
1. Turn on the compressor in question using Service Test
mode. If the compressor does not start, then most likely
the problem is one of the following: HPS open, open in-
ternal protection, circuit breaker trip, incorrect safety wir-
ing, or incorrect compressor wiring.
2. If the compressor does start, verify it is rotating in the cor-
rect direction.
Compressor Overload — Either the compressor internal over-
load protector is open or the external overload protector (Kri-
wan module) has activated. The external overload protector
modules are mounted in the compressor wiring junction box.
Temperature sensors embedded in the compressor motor wind-
ings are the inputs to the module. The module is powered with
24 vac from the units main control box. The module output is a
normally closed contact that is wired in series with the com-
pressor contactor coil. In a compressor motor overload condi-
tion, contact opens, deenergizing the compressor contactor.
IMPORTANT: Prolonged operation in the wrong direction
can damage the compressor. Correct rotation can be veri-
fied by a gage set and looking for a differential pressure
rise on start-up.
71
Download from Www.Somanuals.com. All Manuals Search And Download.
of –40 to 245 F (–40 to 118 C). Failure of this thermistor will
disable any elements of the control which requires its use. The
cause of the alert is usually a faulty thermistor in the T55, or
T58 device, a shorted or open thermistor caused by a wiring er-
ror, or a loose connection.
IMPORTANT: If the CS is always detecting current, verify
that the compressor is on. If the compressor is on, check
the contactor and the relay on the MBB. If the compressor
is off and there is no current, verify the CSB wiring and
replace if necessary.
T090 (Circuit A Discharge Pressure Transducer Failure)
IMPORTANT: Return to Normal mode and observe com-
pressor operation to verify that compressor current sensor
is working and condenser fans are energized.
T091 (Circuit B Discharge Pressure Transducer Failure) —
Alert codes 090 and 091 are for circuits A and B respectively.
These alerts occur when the pressure is outside the range of 0.0
to 667.0 psig. A circuit cannot run when this alert is active. Use
the scrolling marquee to reset the alert. The cause of the alert is
usually a faulty transducer, faulty 5-v power supply, or a loose
connection.
COMPRESSOR STUCK ON FAILURE ALARMS
Circuit A A051, A052
Circuit B A055, A056 — Alarm codes 051, 052, 055, and
056 are for compressors A1, A2, B1, and B2. These alarms oc-
cur when the CSB detects current when the compressor should
be off. When this occurs, the control turns off the compressor.
If the current sensor board reads ON while the compressor
relay has been commanded OFF for a period of 4 continuous
seconds, an alarm is generated. These alarms are only moni-
tored for a period of 10 seconds after the compressor relay has
been commanded OFF. This is done to facilitate a service tech-
nician forcing a relay to test a compressor.
In addition, if a compressor stuck failure occurs and the cur-
rent sensor board reports the compressor and the request off,
certain diagnostics will take place as follows:
T092 (Circuit A Suction Pressure Transducer Failure)
T093 (Circuit B Suction Pressure Transducer Failure)
—
Alert codes 092 and 093 are for circuits A and B respectively.
These alerts occur when the pressure is outside the range of 0.0
to 420.0 psig. A circuit cannot run when this alert is active. Use
the scrolling marquee to reset the alert. The cause of the alert is
usually a faulty transducer, faulty 5-v power supply, or a loose
connection.
T094 (Discharge Gas Thermistor Failure) — This alert oc-
curs for units which have the digital compressor installed on
circuit A. If discharge gas temperature is open or shorted, the
circuit will be shutoff. The alert will reset itself when discharge
temperature is less than 250 F (121.1 C). The cause of the alert
is usually low refrigerant charge or a faulty thermistor.
1. If any of the compressors are diagnosed as stuck on and
the current sensor board is on and the request is off, the
control will command the condenser fans to maintain
normal head pressure.
T110 (Circuit A Loss of Charge)
T111 (Circuit B Loss of Charge) — Alert codes 110 and 111
are for circuits A and B respectively. These alerts occur when
the compressor is OFF and the discharge pressure is less than
26 psig.
2. The control will shut-off all other compressors.
The possible causes include welded contactor or frozen
compressor relay on the MBB.
To check out alarms A051-A056:
T112 (Circuit A High Saturated Suction Temperature)
T113 (Circuit B High Saturated Suction Temperature)
—
1. Place the unit in Service Test mode. All compressors
should be off.
2. Verify that there is not 24-v at the contactor coil. If there
is 24 v at the contactor, check relay on MBB and wiring.
Alert codes 112 and 113 occur when compressors in a circuit
have been running for at least 5 minutes and the circuit saturat-
ed suction temperature is greater than 70 F (21.1 C). The high
saturated suction alert is generated and the circuit is shut down.
3. Check for welded contactor.
4. Verify CSB wiring.
5. Return to Normal mode and observe compressor opera-
tion to verify that compressor current sensor is working
and condenser fans are energized.
T114 (Circuit A Low Superheat)
T115 (Circuit B Low Superheat) — Alert codes 114 and 115
occur when the superheat of a circuit is less than 5 F (2.8 C) for
5 continuous minutes. The low superheat alert is generated and
the circuit is shut down.
T116 (Circuit A Low Cooler Suction Temperature)
A060 (Cooler Leaving Fluid Thermistor Failure)
—
The
T117 (Circuit B Low Cooler Suction Temperature) — Alert
codes 116 and 117 are for circuits A and B respectively. These
alerts are generated if the capacity stages are reduced three
times without a 30 minute interval between capacity reductions
due to operating mode 7 or mode 8.
sensor reading is outside the range of –40 to 245 F (–40 to
118 C) then the alarm will occur. The cause of the alarm is usu-
ally a faulty thermistor, a shorted or open thermistor caused by
a wiring error, or a loose connection. Failure of this thermistor
will shut down the entire unit.
T118 (High Discharge Gas Temperature Alert)
A118 (High Discharge Gas Temperature Alarm)
A061 (Cooler Entering Thermistor Failure) — If the sensor
reading is outside the range of –40 to 240 F (–40 to116 C) then
the alarm will occur. The cause of the alarm is usually a faulty
thermistor, a shorted or open thermistor caused by a wiring er-
ror, or a loose connection. Failure of this thermistor will shut
down the entire unit.
T068, T69 (Circuit A,B Compressor Return Gas Tempera-
ture Thermistor Failure) — This alert occurs when the com-
pressor return gas temperature sensor is outside the range of
–40 to 240 F (–40 to 116 C). Failure of this thermistor will shut
down the appropriate circuit.
—
This
alert or alarm occurs for units which have the digital compres-
sor installed on circuit A. If discharge gas temperature is great-
er than 268 F (131.1 C), the circuit will be shut off. The alert
will reset itself when discharge temperature is less than 250 F
(121.1 C). If this alert occurs 3 times within a day, the A118
alarm will be generated and the alarm must be reset manually.
The cause of the alert is usually low refrigerant charge or a
faulty thermistor.
T126 (Circuit A High Head Pressure)
T073 (Outside Air Temperature Thermistor Failure) — This
alert occurs when the outside air temperature sensor is outside
the range of –40 to 240 F (–40 to 116 C). Failure of this therm-
istor will disable any elements of the control which requires its
use.
T074 (Space Temperature Thermistor Failure) — This alert
occurs when the space temperature sensor is outside the range
T127 (Circuit B High Head Pressure) — Alert codes 126 and
127 are for circuits A and B respectively. These alerts occur
when the appropriate saturated condensing temperature is
greater than the operating envelope shown in Fig 14. Prior to
the alert, the control will shut down one compressor on a circuit
if that circuit's saturated condensing temperature is greater than
the maximum SCT minus 5° F (2.7° C). If SCT continues to
72
Download from Www.Somanuals.com. All Manuals Search And Download.
rise to greater than the maximum SCT, the alert will occur and
the circuit's remaining compressor will shut down. The cause
of the alarm is usually an overcharged system, high outdoor
ambient temperature coupled with dirty outdoor coil, plugged
filter drier, or a faulty high-pressure switch.
T153 (Real Time Clock Hardware Failure) — A problem
has been detected with MBB real time clock hardware. Try re-
setting the power and check the indicator lights. If the alarm
continues, the board should be replaced.
A154 (Serial EEPROM Hardware Failure) — A problem
has been detected with the EEPROM on the MBB. Try
resetting the power and check the indicator lights. If the alarm
continues, the board should be replaced.
T155 (Serial EEPROM Storage Failure Error) — A problem
has been detected with the EEPROM storage on the MBB. Try
resetting the power and check the indicator lights. If the alert
continues, the board should be replaced.
A156 (Critical Serial EEPROM Storage Failure Error) — A
problem has been detected with the EEPROM storage on the
MBB. Try resetting the power and check the indicator lights. If
the alarm continues, the board should be replaced.
T133 (Circuit A Low Suction Pressure)
T134 (Circuit B Low Suction Pressure) — Alert codes 133
and 134 are for circuits A and B respectively. These alerts are
generated if one of the two following conditions is satisfied:
the circuit suction pressure is below 34 psig (234.4 kPa) for 8
seconds, or the suction pressure is below 23 psig (158.6 kPa).
The cause of this alert may be low refrigerant charge, plugged
liquid line filter drier, or sticking EXV. Check head pressure
operation. If not equipped, consider adding low ambient tem-
perature head pressure control.
Add wind baffles if required.
A140 (Reverse Rotation Detected) — A test is made once, on
power up, for suction pressure change on the first activated cir-
cuit. The unit control determines failure as follows:
1. The suction pressure of both circuits is sampled 5 seconds
before the compressor is brought on, right when the com-
pressor is brought on and 5 seconds afterwards.
2. The rate of suction pressure change from 5 seconds be-
fore the compressor is brought on to when the compres-
sor is brought on is calculated.
3. The rate of suction pressure change from when the
compressor is brought on to 5 seconds afterwards is
calculated.
A157 (A/D Hardware Failure) — A problem has been detect-
ed with A/D conversion on the boards. Try resetting the power
and check the indicator lights. If the alarm continues, the board
should be replaced.
A172 (Loss of Communication with the EXV Board)
—
This alarm indicates that there are communications problems
with the EXV board. The alarm will automatically reset.
T173 (Energy Management Module Communication Fail-
ure) — This alert indicates that there are communications
problems with the energy management. All functions per-
formed by the EMM will stop, which can include demand lim-
it, reset and capacity input. The alarm will automatically reset.
T174 (4 to 20 mA Cooling Set Point Input Failure) — This
alert indicates a problem has been detected with cooling set
point 4 to 20 mA input. The input value is either less than 2 mA
or greater than 22 mA.
T175 (Loss of Communication with the AUX Board) —
This alarm indicates that there are communications problems
with the AUX board. All functions performed by the AUX
board will stop, which can include digital scroll unloader oper-
ation and low ambient head pressure control. The alarm will
automatically reset.
4. With the above information, the test for reverse rotation is
made. If the suction pressure change 5 seconds after com-
pression is greater than the suction pressure change 5 sec-
onds before compression – 1.25, then there is a reverse
rotation error.
This alarm will disable mechanical cooling and will require
manual reset.
A150 (Unit is in Emergency Stop) — If the CCN emergency
stop command is received, the alarm is generated and the unit
will be immediately stopped.
If the CCN point name "EMSTOP" in the system table is set
to emergency stop, the unit will shut down immediately and
broadcast an alarm back to the CCN, indicating that the unit is
down. This alarm will clear when the variable is set back to
"enable."
T176 (4 to 20 mA Reset Input Failure) — This alert indi-
cates a problem has been detected with reset 4 to 20 mA input.
The input value is either less than 2 mA or greater than 22 mA.
The reset function will be disabled when this occurs.
T177 (4 to 20 mA Demand Limit Input Failure)
—
This
alert indicates a problem has been detected with demand limit
4 to 20 mA input. The input value is either less than 2 mA or
greater than 22 mA. The reset function will be disabled when
this occurs.
A151 (Illegal Configuration) — An A151 alarm indicates an
invalid configuration has been entered. The following are ille-
gal configurations.
• Invalid unit size has been entered.
T500, T501 (Current Sensor Board Failure — A xx Circuit
A)
• Dual thermostat configured for single-circuit unit.
• Dual thermostat and switch demand limit configure
• AUX board incorrect revision.
T503, T504 (Current Sensor Board Failure — B xx Circuit
B) — Alert codes 500, 501, 503, and 504 are for compressors
A1, A2, B1, and B2 respectively. These alerts occur when the
output of the CSB is a constant high value. These alerts reset
automatically. If the problem cannot be resolved, the CSB must
be replaced.
• Unit configuration set to invalid type.
A152 (Unit Down Due to Failure) — Both circuits are off
due to alerts and/or alarms. Reset is automatic when all alarms
are cleared. This alarm indicates the unit is at 0% capacity.
73
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — DISPLAY TABLES
Run Status Mode and Sub-Mode Directory
SUB-MODE
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
AUTO VIEW OF RUN STATUS
EWT
LWT
SETP
CTPT
LOD.F
xxx.x ºF
xxx.x ºF
xxx.x ºF
xxx.x ºF
xxx
Entering Fluid Temp
Leaving Fluid Temp
Active Set Point
Control Point
Load/Unload Factor
0=Service Test
1=Off Local
2=Off CCN
3=Off Time
4=Off Emrgcy
5=On Local
6=On CCN
7=On Time
STAT
Control Mode
VIEW
LD.PM
OCC
LS.AC
MODE
CAP
STGE
ALRM
TIME
Lead Pump
Occupied
YES/NO
YES/NO
YES/NO
xxx
x
xxx
Low Sound Active
Override Modes in Effect
Percent Total Capacity
Requested Stage
Current Alarms & Alerts
Time of Day
xx.xx
00:00-23:59
1 - 12 (1 = January,
2 = February, etc.)
MNTH
xx
Month of Year
DATE
YEAR
xx
xx
Day of Month
Year of Century
01-31
UNIT RUN HOUR AND START
HRS.U
STR.U
HR.P1
HR.P2
xxxx HRS
xxxx
xxxx HRS
xxxx HRS
Machine Operating Hours
Machine Starts
RUN
Pump 1 Run Hours
Pump 2 Run Hours
CIRC AND COMP RUN HOURS
HRS.A
HRS.B
HR.A1
HR.A2
HR.B1
HR.B2
xxxx HRS
xxxx HRS
xxxx HRS
xxxx HRS
xxxx HRS
xxxx HRS
Circuit A Run Hours
Circuit B Run Hours
Compressor A1 Run Hours
Compressor A2 Run Hours
Compressor B1 Run Hours
Compressor B2 Run Hours
HOUR
74
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — DISPLAY TABLES (cont)
Run Status Mode and Sub-Mode Directory (cont)
SUB-MODE
STRT
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
COMPRESSOR STARTS
ST.A1
ST.A2
ST.B1
ST.B2
xxxx
xxxx
xxxx
xxxx
Compressor A1 Starts
Compressor A2 Starts
Compressor B1 Starts
Compressor B2 Starts
PREVENTIVE MAINTENANCE
PUMP
SI.PM
PUMP MAINTENANCE
Pump Service Interval
Pump 1 Service Countdown
Pump 2 Service Countdown
Pump 1 Maintenance Done
Pump 2 Maintenance Done
PUMP MAINTENANCE DATES
MM/DD/YY HH:MM
xxxx HRS
xxxx HRS
xxxx HRS
YES/NO
YES/NO
P.1.DN
P.2.DN
P.1.MN
P.2.MN
PMDT
P.1.M0
P.1.M1
P.1.M2
P.1.M3
P.1.M4
P.2.M0
P.2.M1
P.2.M2
P.2.M3
P.2.M4
STRN
User Entry
User Entry
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
STRAINER MAINTENANCE
Strainer Srvc Interval
Strainer Srvc Countdown
Strainer Maint. Done
STRAINER MAINTENANCE DATES
MM/DD/YY HH:MM
PM
SI.ST
xxxx HRS
xxxx HRS
YES/NO
S.T.DN
S.T.MN
ST.DT
S.T.M0
S.T.M1
S.T.M2
S.T.M3
S.T.M4
COIL
User Entry
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
COIL MAINTENANCE
Coil Cleaning Srvc Int
Coil Service Countdown
Coil Cleaning Maint.Done
COIL MAINTENANCE DATES
MM/DD/YY HH:MM
SI.CL
xxxx HRS
xxxx HRS
YES/NO
C.L.DN
C.L.MN
CL.DT
C.L.M0
C.L.M1
C.L.M2
C.L.M3
C.L.M4
User Entry
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
SOFTWARE VERSION NUMBERS
CESR131460-XXXXX
MBB
EXV
AUX1
EMM
MARQ
NAVI
CESR131172-XXXXX
CESR131333-XXXXX
CESR131174-XXXXX
CESR131171-XXXXX
CESR130227-XXXXX
VERS
75
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — DISPLAY TABLES (cont)
Service Test Mode and Sub-Mode Directory
SUB-MODE
TEST
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
To enable Service Test mode, move
Enable/Off/Remote contact switch to
OFF. Change TEST to ON.
Service Test Mode
Move switch to ENABLE
OUTPUTS
EXV % Open
EXV % Open
Fan 1 Relay
Fan 2 Relay
Fan 3 Relay
Fan 4 Relay
Fan 5 Relay
Fan 6 Relay
EXV.A
EXV.B
FAN1
FAN2
FAN3
FAN4
FAN5
FAN6
V.HPA
V.HPB
CLP.1
CLP.2
UL.TM
CL.HT
RMT.A
xxx%
xxx%
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
xx
OUTS
Var Head Press %
Var Head Press %
Cooler Pump Relay 1
Cooler Pump Relay 2
Comp A1 Unload Time
Cooler/Pump Heater
Remote Alarm Relay
CIRCUIT A COMPRESSOR TEST
Compressor A1 Relay
Comp A1 Unload Time
Compressor A2 Relay
Minimum Load Valve Relay
CIRCUIT B COMPRESSOR TEST
Compressor B1 Relay
Compressor B2 Relay
xx
ON/OFF
ON/OFF
xx
ON/OFF
ON/OFF
CC.A1
UL.TM
CC.A2
MLV
ON/OFF
xx
ON/OFF
ON/OFF
CMPA
CMPB
CC.B1
CC.B2
ON/OFF
ON/OFF
Temperature Mode and Sub-Mode Directory
SUB-MODE
UNIT
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
ENTERING AND LEAVING UNIT TEMPERATURES
CEWT
CLWT
OAT
SPT
DLWT
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x °F
Cooler Entering Fluid
Cooler Leaving Fluid
Outside Air Temperature
Space Temperature
Lead/Lag Leaving Fluid
TEMPERATURES CIRCUIT A
Saturated Condensing Tmp
Saturated Suction Temp
Compr Return Gas Temp
Discharge Gas Temp
Suction Superheat Temp
TEMPERATURES CIRCUIT B
Saturated Condensing Tmp
Saturated Suction Temp
Compr Return Gas Temp
Suction Superheat Temp
SCT.A
SST.A
RGT.A
D.GAS
SH.A
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x ΔF
CIR.A
CIR.B
SCT.B
SST.B
RGT.B
SH.B
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x ΔF
Pressures Mode and Sub-Mode Directory
SUB-MODE
PRC.A
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
PRESSURES CIRCUIT A
xxx.x PSIG
xxx.x PSIG
DP.A
SP.A
Discharge Pressure
Suction Pressure
PRESSURES CIRCUIT B
PRC.B
DP.B
SP.B
xxx.x PSIG
xxx.x PSIG
Discharge Pressure
Suction Pressure
76
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — DISPLAY TABLES (cont)
Set Points Mode and Sub-Mode Directory
SUB-MODE
COOL
ITEM
DISPLAY
ITEM DESCRIPTION
COOLING SET POINTS
Cooling Set Point 1
RANGE
COMMENT
CSP.1
CSP.2
CSP.3
xxx.x °F
xxx.x °F
xxx.x °F
–20 to 70
–20 to 70
–20 to 32
Default: 44 F
Default: 44 F
Default: 32 F
Cooling Set Point 2
ICE Set Point
HEAD PRESSURE SET POINTS
Head Set Point
H.DP
F.ON
F.OFF
B.OFF
F.DLT
xxx.x °F
xxx.x °F
xxx.x °F
xx.x
85 to 120
Default: 95 F
Default: 95 F
Default: 72 F
Default: 23 F
Default: 15 F
Fan On Set Point
Fan Off Set Point
Base Fan Off Delta Temp
Fan Stage Delta
HEAD
FRZ
10 to 50
0 to 50
xxx
BRINE FREEZE SET POINT
Brine Freeze Point
BR.FZ
xx.x °F
–20 to 34
Default: 34 F
Inputs Mode and Sub-Mode Directory
SUB-MODE
ITEM
DISPLAY
ITEM DESCRIPTION
GENERAL INPUTS
Start/Stop Switch
COMMENT
STST
FLOW
PM.F.1
PM.F.2
HT.RQ
DLS1
DLS2
ICED
DUAL
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Cooler Flow Switch
Cooler Pump 1 Interlock
Cooler Pump 2 Interlock
Heat Request
Demand Limit Switch 1
Demand Limit Switch 2
Ice Done
GEN.I
Dual Set Point Switch
CIRCUIT INPUTS
FKA1
FKA2
FKA3
FKA4
FKB1
FKB2
FKB3
FKB4
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Compressor A1 Feedback
Compressor A2 Feedback
Compressor A3 Feedback
Compressor A4 Feedback
Compressor B1 Feedback
Compressor B2 Feedback
Compressor B3 Feedback
Compressor B4 Feedback
CRCT
4-20
4-20 MA INPUTS
DMND
RSET
CSP
xx.x
xx.x
xx.x
4-20 ma Demand Signal
4-20 ma Reset Signal
4-20 ma Cooling Set Point
77
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — DISPLAY TABLES (cont)
Outputs Mode and Sub-Mode Directory
SUB-MODE
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
GENERAL OUTPUTS
FAN1
FAN2
FAN3
FAN4
FAN5
FAN6
V.HPA
V.HPB
C.WP1
C.WP2
CLHT
MLV.R
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Fan 1 Relay
Fan 2 Relay
Fan 3 Relay
Fan 4 Relay
Fan 5 Relay
GEN.O
Fan 6 Relay
Fan Speed Circuit A
Fan Speed Circuit B
Cooler Pump Relay 1
Cooler Pump Relay 2
Cooler/Pump Heater
Minimum Load Valve Relay
OUTPUTS CIRCUIT A EXV
EXV.A
APPR
AP.SP
X.SH.R
S.SH.R
SH_R
OVR.A
SPH.A
ASH.S
AMP.S
PLM.A
SPR.1
ON/OFF
ON/OFF
ON/OFF
EXV % Open
Circuit A Approach
Approach Setpoint
SH Reset at Max Unl-Dig
Digload to Start SH RST
Amount of SH Reset
EXVA Override
Suction Superheat Temp
Active Superheat Setpt
Active Mop Setpt
A.EXV
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Cir A EXV Position Limit
Spare 1 Temperature
OUTPUTS CIRCUIT A EXV
EXV.B
APPR
AP.SP
OVR.B
SPH.B
ASH.S
AMP.S
PLM.B
SPR.2
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
EXV % Open
Circuit B Approach
Approach Setpoint
EXVB Override
B.EXV
Suction Superheat Temp
Active Superheat Setpt
Active Mop Setpt
Cir B EXV Position Limit
Spare 2 Temperature
OUTPUTS CIRCUIT A
CC.A1
DPE.R
CC.A2
CC.A3
CC.A4
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Compressor A1 Relay
Comp A1 Load Percent
Compressor A2 Relay
Compressor A3 Relay
Compressor A4 Relay
CIR.A
CIR.B
OUTPUTS CIRCUIT B
CC.B1
CC.B2
CC.B3
CC.B4
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Compressor B1 Relay
Compressor B2 Relay
Compressor B3 Relay
Compressor B4 Relay
78
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory
SUB-MODE
DISP
ITEM
DISPLAY
ITEM DESCRIPTION
DISPLAY CONFIGURATION
Test Display LEDs
COMMENT
TEST
METR
ON/OFF
ON/OFF
Metric Display
Off = English On = Metric
Default: 0
0 = English
1 = Espanol
2 = Francais
3 = Portuguese
LANG
X
Language Selection
PAS.E
PASS
ENBL/DSBL
XXXX
Password Enable
Service Password
UNIT CONFIGURATION
Unit Size
SIZE
SZA.1
SZA.2
SZA.3
SZA.4
SZB.1
SZB.2
SZB.3
SZB.4
SH.SP
FAN.S
EXV
XX
XX
XX
XX
XX
XX
XX
XX
XX
Compressor A1 Size
Compressor A2 Size
Compressor A3 Size
Compressor A4 Size
Compressor B1 Size
Compressor B2 Size
Compressor B3 Size
Compressor B4 Size
Suction Superheat Setpt
Number of Fans
UNIT
X
Default: 5
YES/NO
YES/NO
EXV Module Installed
Compressor A1 Digital
A1.TY
Default: No
Default: 7
MAX.T
FLUD
XX
Maximum A1 Unload Time
Max = 12 (010,015)
Max = 10 (018-060)
UNIT OPTIONS 1 HARDWARE
Cooler Fluid
X
Default: Water
1 = Water
2 = Medium Temperature Brine
MLV.S
CSB.E
CPC
PM1E
PM2E
PM.P.S
PM.SL
YES/NO
ENBL/DSBL
ON/OFF
YES/NO
YES/NO
YES/NO
X
Minimum Load Valve Select
Csb Boards Enable
Default: Enable
Default: Off
Cooler Pump Control
Cooler Pump 1 Enable
Cooler Pump 2 Enable
Cooler Pmp Periodic Strt
Cooler Pump Select
Default: No
OPT1
Default: Automatic
0 = Automatic
1 = Pump 1 Starts first
2 = Pump 2 Starts first
PM.DY
PM.DT
ROT.P
EMM
CND.T
MOPS
APPR
XX MIN
XXXX HRS
YES/NO
YES/NO
X
Cooler Pump Shutdown Dly
Pump Changeover Hours
Rotate Cooler Pumps Now
EMM Module Installed
Cnd HX Typ:0=RTPF 1=MCHX
EXV MOP Set Point
0 to 10 minutes, Default: 1 min.
Default: 500 hours
User Entry
XX
XX
Config Approach Set Point
79
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
UNIT OPTIONS 2 CONTROLS
Default: 0
0 = Enable/Off/Remote Switch
2 = Occupancy
CTRL
LOAD
LLCS
X
X
X
Control Method
3 = CCN Control
Default: 1
1 = Equal
2 = Staged
Loading Sequence Select
Lead/Lag Circuit Select
Default: 1
1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
Default: 60
OPT2
LCWT
DELY
XX
XX
High LCW Alert Limit
Minutes Off Time
Range: 2 to 60 F
Default: 0 Minutes
Range: 0 to 15 Minutes
ICE.M
LS.MD
ENBL/DSBL
X
Ice Mode Enable
Low Sound Mode Select
Default: Disable
Default: 0
0 = Mode Disable
1 = Fan Noise Only
2 = Fan/Compressor Noise
LS.ST
LS.ND
00:00
00:00
Low Sound Start Time
Low Sound End Time
Default: 00:00
Default: 00:00
Default: 100%
LS.LT
XXX %
Low Sound Capacity Limit
CCN NETWORK CONFIGS
CCN Address
Range: 0 to 100%
Default: 1
Range: 0 to 239
Default: 1
Range: 0 to 239
CCNA
CCNB
XXX
XXX
CCN Bus Number
CCN
Default: 3
1 = 2400
2 = 4800
3 = 9600
4 =19,200
5 =38,400
BAUD
X
CCN Baud Rate
HEAD PRESSURE CMP. DELTA
SCT Delta For Comp A1
Default:12
A1.DT
A2.DT
XX
XX
HP.A
HP.B
Range: 0 to 50
Default:12
Range: 0 to 50
SCT Delta For Comp A2
HEAD PRESSURE CMP. DELTA
SCT Delta For Comp B1
Default:12
Range: 0 to 50
Default:12
Range: 0 to 50
B1.DT
B2.DT
XX
XX
SCT Delta For Comp B2
80
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
CIR A EXV CONFIGURATION
Default: 50
0 to 100
STR.A
XXX
EXV CIrc.A Start Pos
Default: 8
0 to 100
0 to 65535
Default: 200
0 to 65535
MIN.A
RNG.A
SPD.A
XXX
EXV Circ.A Min Position
EXVA Steps In Range
EXVA STeps Per Second
XXXXX
XXXXX
Default: 0
0 to 100
POF.A
XXX
EXVA Fail Position In %
Default: 0
MIN.A
MAX.A
OVR.A
XXXXX
XXXXX
XXX
EXVA Minimum Steps
EXVA Maximum Steps
EXVA Overrun Steps
0 to 65535
0 to 65535
Default: 167
0 to 65535
Default: 1
0 = UNIPOLAR
1 = BIPOLAR
EXV.A
TYP.A
0,1
EXVA Stepper Type
Default: 115
50 to 140
Default: 10
0 to 30
Default: 5
0 to 30
Default: 10
0 to 100
Default: 10
0 to 100
Default: 10
0 to 100
Default: 10
0 to 100
H.SCT
X.PCT
X.PER
A.PCT
M.PCT
S.PCT
DELY
XXX
XX
High SCT Threshold
Open EXV X% On 2nd Comp
Move EXV X% On DISCRSOL
Pre-open EXV - Fan Adding
Pre-close EXV - Fan Sub
Pre-close EXV - Lag Shut
XX
XXX
XXX
XXX
XXX
Lag Start Delay
CIR B EXV CONFIGURATION
EXV CIrc.B Start Pos
Default: 50
0 to 100
STR.B
XXX
Default: 8
0 to 100
0 to 65535
Default: 200
0 to 65535
MIN.B
RNG.B
SPD.B
XXX
EXV Circ.B Min Position
EXVB Steps In Range
EXVB STeps Per Second
XXXXX
XXXXX
Default: 0
0 to 100
EXV.B
POF.B
XXX
EXVB Fail Position In %
Default: 0
MIN.B
MAX.B
OVR.B
XXXXX
XXXXX
XXX
EXVB Minimum Steps
EXVB Maximum Steps
EXVB Overrun Steps
0 to 65535
0 to 65535
Default: 167
0 to 65535
Default: 1
0 = UNIPOLAR
1 = BIPOLAR
TYP.B
0,1
EXVB Stepper Type
81
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE
MM
ITEM
DISPLAY
ITEM DESCRIPTION
MOTORMASTER
COMMENT
MMR.S
P.GAN
YES/NO
XX
Motormaster Select
Default: NO
Default: 1
Range: 1 to 4
Default: 0.1
Range: -20 to 20
Head Pressure P Gain
I.GAN
XX.X
Head Pressure I Gain
Default: 0.0
D.GAN
MIN.S
XX.X
XX
Head Pressure D Gain
Minimum Fan Speed
Range: -20 to 20
Default: 5
RESET COOL TEMP
Default: 0
0 = No Reset
1 = 4 to 20 mA Input
2 = Outdoor Air Temperature
3 = Return Fluid
CRST
X
Cooling Reset Type
4 = Space Temperature
Default: 0.0 ΔF
MA.DG
RM.NO
RM.F
XX.XΔF
XXX.X °F
XXX.X °F
XX.X °F
XXX.XΔF
XXX.XΔF
XX.X °F
4-20 - Degrees Reset
Remote - No Reset Temp
Remote - Full Reset Temp
Remote - Degrees Reset
Return - No Reset Temp
Return - Full Reset Temp
Return - Degrees Reset
Range: -30 to 30 ΔF
Default: 125 F
Range: 0° to125 F
Default: 0 F
Range: 0° to125 F
Default: 0.0 ΔF
Range: -30 to 30 ΔF
Default: 10.0 ΔF
Range: 0° to125 F
Default: 0 ΔF
Range: 0° to125 F
Default: 0.0 ΔF
Range: -30 to 30 ΔF
RM.DG
RT.NO
RT.F
RT.DG
Default: 0
0 = None
DMDC
X
Demand Limit Select
1 = Switch
2 - 4 to 20 mA Input
3 = CCN Loadshed
Default: 100%
RSET
DM20
SHNM
SHDL
SHTM
DLS1
DLS2
XXX%
XXX
Demand Limit at 20 mA
Loadshed Group Number
Loadshed Demand Delta
Maximum Loadshed Time
Demand Limit Switch 1
Demand Limit Switch 2
Range: 0 to 100%
Default: 0
Range: 0 to 99
Default: 0%
Range: 0 to 60%
XXX%
XXX
Default: 60 minutes
Range: 0 to 120 minutes
Default: 80%
Range: 0 to 100%
Default: 50%
Range: 0 to 100%
XXX%
XXX%
LLEN
MSSL
SLVA
ENBL/DSBL
SLVE/MAST
XXX
Lead/Lag Chiller Enable
Master/Slave Select
Slave Address
Default: Disable
Default: Master
Default: 2
Range: 0 to 239
Default: Master Leads
0 = Master Leads
1 = Slave Leads
2 = Automatic
LLBL
X
Lead/Lag Balance Select
Default: 168 hours
LLBD
LLDY
PARA
XXX
XXX
YES
Lead/Lag Balance Delta
Lag Start Delay
Range: 40 to 400 hours
Default: 5 minutes
Range: 0 to 30 minutes
Default: YES (CANNOT BE
CHANGED)
Parallel Configuration
82
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
SETPOINT AND RAMP LOAD
Default: Single
0 = Single
1 = Dual Switch
CLSP
X
Cooling Set Point Select
2 = Dual CCN Occupied
3 = 4 to 20 mA
Input (requires EMM)
SLCT
RL.S
ENBL/DSBL
ENBL/DSBL
Ramp Load Select
Default: Enable
Default: 1.0
Range: 0.3 to 2
CRMP
Cooling Ramp Loading
Default: 1
SCHD
Z.GN
XX
Schedule Number
Range: 1 to 99
Default: 1
Range: 1 to 4
X.X
Deadband Multiplier
SERVICE CONFIGURATION
Enable Compressor A1
Enable Compressor A2
Enable Compressor B1
Enable Compressor B2
BROADCAST CONFIGURATION
CCN Time/Date Broadcast
CCN OAT Broadcast
EN.A1
EN.A2
EN.B1
EN.B2
YES/NO
YES/NO
YES/NO
YES/NO
SERV
BCST
T.D.B
OAT.B
G.S.BC
BC.AK
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Global Schedule Broadcst
CCN Broadcast Ack'er
83
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — DISPLAY TABLES (cont)
Time Clock Mode and Sub-Mode Directory
SUB-MODE
TIME
ITEM
DISPLAY
ITEM DESCRIPTION
TIME OF DAY
Hour and Minute
COMMENT
HH.MM
XX.XX
Military (00:00 - 23:59)
MONTH, DATE, DAY, AND YEAR
1 - 12 (1 = January,
2 = February, etc.)
Range: 01 -31
1 - 7 (1 = Sunday,
2 = Monday, etc.)
MNTH
DOM
DAY
XX
XX
Month of Year
DATE
Day of Month
Day of Week
X
YEAR
XXXX
Year of Century
DAYLIGHT SAVINGS TIME
STR.M
STR.W
STR.D
MIN.A
STP.M
STP.W
STP.D
MIN.S
XX
X
X
XX
XX
XX
XX
XX
Month
Week
Day
Default: 4 Range 1- 12
Default: 1 Range 1- 5
Default: 7 Range 1- 7
Default: 60 Range 0 - 99
Default: 10 Range 1- 12
Default: 5 Range 1- 5
Default: 7 Range 1- 7
Default: 60 Range 0 - 99
DST
Minutes to Add
Month
Week
Day
Minutes to Subtract
HOL.L
HD.01
LOCAL HOLIDAY SCHEDULES
HOLIDAY SCHEDULE 01
MON
DAY
LEN
XX
XX
XX
Holiday Start Month
Start Day
Duration (days)
HOLIDAY SCHEDULE 02
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
HD.02
HD.03
HD.04
HD.05
HD.06
HD.07
HD.08
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 03
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 04
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 05
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 06
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 07
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 08
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
01-31
84
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — DISPLAY TABLES (cont)
Time Clock Mode and Sub-Mode Directory (cont)
SUB-MODE
HD.09
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
HOLIDAY SCHEDULE 09
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
01-31
HOLIDAY SCHEDULE 10
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
HD.10
HD.11
HD.12
HD.13
HD.14
HD.15
HD.16
HD.17
HD.18
HD.19
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 11
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 12
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 13
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 14
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 15
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 16
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 17
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 18
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 19
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
01-31
85
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — DISPLAY TABLES (cont)
Time Clock Mode and Sub-Mode Directory (cont)
SUB-MODE
HD.20
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
HOLIDAY SCHEDULE 20
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
01-31
HOLIDAY SCHEDULE 21
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
HD.21
HD.22
HD.23
HD.24
HD.25
HD.26
HD.27
HD.28
HD.29
HD.30
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 22
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 23
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 24
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 25
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 26
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 27
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 28
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 29
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
HOLIDAY SCHEDULE 30
01-31
1 - 12 (1 = January,
2 = February, etc.)
MON
XX
Holiday Start Month
DAY
LEN
XX
XX
Start Day
Duration (days)
01-31
86
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — DISPLAY TABLES (cont)
Time Clock Mode and Sub-Mode Directory (cont)
SUB-MODE
SCH.N
ITEM
DISPLAY
ITEM DESCRIPTION
Schedule Number 0
COMMENT
SCH.L
LOCAL OCCUPANCY SCHEDULE
OCCUPANCY PERIOD 1
OCC.1
UNC.1
MON.1
TUE.1
WED.1
THU.1
FRI.1
SAT.1
SUN.1
HOL.1
XX:XX
XX:XX
Period Occupied Time
Military (00:00 - 23:59)
Military (00:00 - 23:59)
Period Unoccupied Time
Monday In Period
Tuesday In Period
Wednesday In Period
Thursday In Period
Friday In Period
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
PER.1
PER.2
PER.3
PER.4
PER.5
Saturday In Period
Sunday In Period
Holiday In Period
OCCUPANCY PERIOD 2
XX:XX
XX:XX
OCC.2
UNC.2
MON.2
TUE.2
WED.2
THU.2
FRI.2
SAT.2
SUN.2
HOL.2
Period Occupied Time
Period Unoccupied Time
Monday In Period
Tuesday In Period
Wednesday In Period
Thursday In Period
Friday In Period
Military (00:00 - 23:59)
Military (00:00 - 23:59)
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
Saturday In Period
Sunday In Period
Holiday In Period
OCCUPANCY PERIOD 3
XX:XX
XX:XX
OCC.3
UNC.3
MON.3
TUE.3
WED.3
THU.3
FRI.3
SAT.3
SUN.3
HOL.3
Period Occupied Time
Period Unoccupied Time
Monday In Period
Tuesday In Period
Wednesday In Period
Thursday In Period
Friday In Period
Military (00:00 - 23:59)
Military (00:00 - 23:59)
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
Saturday In Period
Sunday In Period
Holiday In Period
OCCUPANCY PERIOD 4
XX:XX
XX:XX
OCC.4
UNC.4
MON.4
TUE.4
WED.4
THU.4
FRI.4
SAT.4
SUN.4
HOL.4
Period Occupied Time
Period Unoccupied Time
Monday In Period
Tuesday In Period
Wednesday In Period
Thursday In Period
Friday In Period
Military (00:00 - 23:59)
Military (00:00 - 23:59)
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
Saturday In Period
Sunday In Period
Holiday In Period
OCCUPANCY PERIOD 5
XX:XX
XX:XX
OCC.5
UNC.5
MON.5
TUE.5
WED.5
THU.5
FRI.5
SAT.5
SUN.5
HOL.5
Period Occupied Time
Period Unoccupied Time
Monday In Period
Tuesday In Period
Wednesday In Period
Thursday In Period
Friday In Period
Military (00:00 - 23:59)
Military (00:00 - 23:59)
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
Saturday In Period
Sunday In Period
Holiday In Period
87
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — DISPLAY TABLES (cont)
Time Clock Mode and Sub-Mode Directory (cont)
SUB-MODE
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
OCCUPANCY PERIOD 6
OCC.6
UNC.6
MON.6
TUE.6
WED.6
THU.6
FRI.6
SAT.6
SUN.6
HOL.6
XX:XX
XX:XX
Period Occupied Time
Period Unoccupied Time
Monday In Period
Tuesday In Period
Wednesday In Period
Thursday In Period
Friday In Period
Military (00:00 - 23:59)
Military (00:00 - 23:59)
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
PER.6
Saturday In Period
Sunday In Period
Holiday In Period
OCCUPANCY PERIOD 7
OCC.7
UNC.7
MON.7
TUE.7
WED.7
THU.7
FRI.7
SAT.7
SUN.7
HOL.7
XX:XX
XX:XX
Period Occupied Time
Period Unoccupied Time
Monday In Period
Tuesday In Period
Wednesday In Period
Thursday In Period
Friday In Period
Military (00:00 - 23:59)
Military (00:00 - 23:59)
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
PER.7
Saturday In Period
Sunday In Period
Holiday In Period
OCCUPANCY PERIOD 8
OCC.8
UNC.8
MON.8
TUE.8
WED.8
THU.8
FRI.8
SAT.8
SUN.8
HOL.8
XX:XX
XX:XX
Period Occupied Time
Period Unoccupied Time
Monday In Period
Tuesday In Period
Wednesday In Period
Thursday In Period
Friday In Period
Military (00:00 - 23:59)
Military (00:00 - 23:59)
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
PER.8
Saturday In Period
Sunday In Period
Holiday In Period
SCHEDULE OVERRIDE
OVR.T
OVR.L
T.OVR
X
X
Timed Override Hours
Override Time Limit
Timed Override
Default: 0 Range 0-4 hours
Default: 0 Range 0-4 hours
User Entry
OVR
YES/NO
88
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A — DISPLAY TABLES (cont)
Operating Mode and Sub-Mode Directory
SUB-MODE
ITEM
DISPLAY
ITEM DESCRIPTION
MODES CONTROLLING UNIT
CSM Controlling Chiller
WSM Controlling Chiller
Master/Slave Control
Ramp Load Limited
COMMENT
MD01
MD02
MD03
MD05
MD06
MD07
MD08
MD09
MD10
MD13
MD14
MD15
MD16
MD17
MD18
MD19
MD20
MD21
MD22
MD23
MD24
MD25
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Timed Override in effect
Low Cooler Suction TempA
Low Cooler Suction TempB
Slow Change Override
Minimum OFF time active
Dual Set Point
Temperature Reset
Demand Limited
Cooler Freeze Protection
Low Temperature Cooling
High Temperature Cooling
Making Ice
MODE
Storing Ice
High SCT Circuit A
High SCT Circuit B
Minimum Comp. On Time
Pump Off Delay Time
Low Sound Mode
Alarms Mode and Sub-Mode Directory
SUB-MODE
CRNT
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
CURRENTLY ACTIVE ALARMS
AXXX
TXXX
PXXX
Alarms are hown as AXXX
Alerts are shown as TXXX
Current Alarms 1-25
RCRN
YES/NO
Reset All Current Alarms
ALARM HISTORY
AXXX
TXXX
PXXX
HIST
Alarms are shown as AXXX
Alerts are shown as TXXX
Alarm History 1-20
89
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX B — CCN TABLES
CCN DISPLAY TABLES — A_UNIT (General Unit Parameters)
DESCRIPTION
Control Mode
VALUE
UNITS
POINT NAME
STAT
FORCIBLE
0 = Test
N
1 = Local Off
2 = CCN Off
3 = Clock Off
4 = Emergency Stop
5 = Local On
6 = CCN On
7 = Clock On
8 = Heat Enabled
9 = Pump Delay
Occupied
CCN Chiller
Low Sound Active
Alarm State
Active Demand Limit
Override Modes in Effect
Percent Total Capacity
Requested Stage
Active Set Point
No/Yes
Start/Stop
No/Yes
Normal/Alert/Alarm
0 to 100
No/Yes
0 to 100
0 to 99
–20 to 70
–20 to 70
snnn.n
OCC
N
Y
N
N
Y
N
N
N
N
Y
N
N
Y
N
CHIL_S_S
LSACTIVE
ALM
DEM_LIM
MODE
CAP_T
STAGE
SP
CTRL_PNT
EWT
%
%
F
F
F
F
Enable
minutes
Control Point
Entering Fluid Temp
Leaving Fluid Temp
Emergency Stop
Minutes Left for Start
PUMPS
snnn.n
Enable/Emstop
00:00 to 15:00
LWT
EMSTOP
MIN_LEFT
Cooler Pump Relay 1
Cooler Pump Relay 2
Cooler Pump 1 Interlock
Cooler Pump 2 Interlock
Cooler Flow Switch
Lead Pump
Off/On
Off/On
Open/Close
Open/Close
Open/Close
COOLPMP1
COOLPMP2
PMP1_FBK
PMP2_FBK
COOLFLOW
LEADPUMP
ROT_PUMP
N
N
N
N
N
Y
Y
Rotate Cooler Pumps Now
No/Yes
Heat/Cool Select
Heat/Cool
HC_SEL
N
CCN DISPLAY TABLES — CIRCA_AN (Circuit A Analog Parameters)
DESCRIPTION
CIRCUIT A ANALOG VALUES
Percent Total Capacity
Percent Available Cap.
Discharge Pressure
VALUE
UNITS
POINT NAME
FORCIBLE
0-100
%
%
CAPA_T
CAPA_A
DP_A
SP_A
HSP
TMP_SCTA
TMP_SSTA
EXV_A
VHP_ACT
TMP_RGTA
DISGAS
SH_A
N
0-100
nnn.n
nnn.n
nnn.n
snnn.n
snnn.n
nnn
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
N
N
N
N
N
N
N
N
N
N
N
N
PSIG
PSIG
°F
F
F
Suction Pressure
Head Setpoint
Saturated Condensing Tmp
Saturated Suction Temp
EXV % Open
Var Head Press Output
Compr Return Gas Temp
Discharge Gas Temp
Suction Superheat Temp
Spare 1 Temperature
%
milliamps
F
°F
F
°F
SPR1_TMP
90
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX B — CCN TABLES (cont)
CCN DISPLAY TABLES — CIRCADIO (Circuit A Discrete Inputs/Outputs)
DESCRIPTION
CIRC. A DISCRETE OUTPUTS
Compressor A1 Relay
Compressor A2 Relay
Minimum Load Valve Relay
VALUE
UNITS
POINT NAME
FORCIBLE
On/Off
On/Off
On/Off
K_A1_RLY
K_A2_RLY
MLV_RLY
N
N
N
CIRC. A DISCRETE INPUTS
Compressor A1 Feedback
Compressor A2 Feedback
On/Off
On/Off
K_A1_FBK
K_A2_FBK
N
N
CCN DISPLAY TABLES — CIRCB_AN (Circuit B Analog Parameters)
DESCRIPTION
CIRCUIT B ANALOG VALUES
Percent Total Capacity
Percent Available Cap.
Discharge Pressure
VALUE
UNITS
POINT NAME
FORCIBLE
0-100
%
%
CAPB_T
CAPB_A
DP_B
SP_B
HSP
TMP_SCTB
TMP_SSTB
EXV_B
VHP_ACT
TMP_RGTB
SH_B
N
N
N
N
N
N
N
N
N
N
N
N
0-100
nnn.n
nnn.n
nnn.n
snnn.n
snnn.n
nnn
nnn.n
nnn.n
nnn.n
nnn.n
PSIG
PSIG
°F
F
F
Suction Pressure
Head Setpoint
Saturated Condensing Tmp
Saturated Suction Temp
EXV % Open
Var Head Press Output
Compr Return Gas Temp
Suction Superheat Temp
Spare 2 Temperature
%
milliamps
F
F
°F
SPR2_TMP
CCN DISPLAY TABLES — CIRCBDIO (Circuit B Discrete Inputs/Outputs)
DESCRIPTION
CIRC. B DISCRETE OUTPUTS
Compressor B1 Relay
Compressor B2 Relay
Minimum Load Valve Relay
VALUE
UNITS
POINT NAME
FORCIBLE
On/Off
On/Off
On/Off
K_B1_RLY
K_B2_RLY
MLV_RLY
N
N
N
CIRC. B DISCRETE INPUTS
Compressor B1 Feedback
Compressor B2 Feedback
On/Off
On/Off
K_B1_FBK
K_B2_FBK
N
N
91
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX B — CCN TABLES (cont)
CCN DISPLAY TABLES — OPTIONS (Unit Parameters)
DESCRIPTION
VALUE
UNITS
POINT NAME
FORCIBLE
FANS
Fan 1 Relay
Fan 2 Relay
Cooler/Pump Heater
Off/On
Off/On
Off/On
FAN_1
FAN_2
COOL_HTR
N
N
N
UNIT ANALOG VALUES
Cooler Entering Fluid
Cooler Leaving Fluid
Lead/Lag Leaving Fluid
snnn.n
snnn.n
snnn.n
F
F
F
COOL_EWT
COOL_LWT
DUAL_LWT
N
N
N
TEMPERATURE RESET
4-20 mA Reset Signal
Outside Air Temperature
Space Temperature
nn.n
snnn.n
snnn.n
mA
F
F
RST_MA
OAT
SPT
N
Y
Y
DEMAND LIMIT
4-20 mA Demand Signal
Demand Limit Switch 1
Demand Limit Switch 2
CCN Loadshed Signal
nn.n
Off/On
Off/On
0 = Normal
1 = Redline
2 = Loadshed
mA
LMT_MA
N
N
N
N
DMD_SW1
DMD_SW2
DL_STAT
MISCELLANEOUS
Heat Request
Dual Setpoint Switch
Cooler LWT Setpoint
Ice Done
Off/On
Off/On
snnn.n
Off/On
HEAT_REQ
DUAL_IN
LWT_SP
N
N
N
N
F
ICE_DONE
CCN CONFIGURATION TABLES — UNIT (Unit Configuration)
DESCRIPTION
Unit Size
VALUE
DEFAULT
UNITS
tons
tons
tons
tons
POINT NAME
SIZE
nnn
nnn
nnn
nnn
nnn
nn.n
n
Compressor A1 Size
Compressor A2 Size
Compressor B1 Size
Compressor B2 Size
Suction Superheat Setpt
Number of Fans
SIZE_A1
SIZE_A2
SIZE_B1
SIZE_B2
SH_SP
FAN_TYPE
CPA1TYPE
MAXULTME
tons
F
9.0
Compressor A1 Digital?
Maximum A1 Unload Time
No/Yes
nn
No
12
sec
CCN CONFIGURATION TABLES — OPTIONS1 (Options 1 Configuration)
DESCRIPTION
Cooler Fluid
VALUE
DEFAULT
1
UNITS
POINT NAME
FLUIDTYP
1 = Water
2 = Med. Brine
No/Yes
Dsable/Enable
Off/On
No/Yes
No/Yes
No/Yes
0 = Automatic, 1 =
Pump 1, 2 = Pump 2
Minimum Load Vlv Select
CSB Board Enable
No
MLV_FLG
CSB_ENA
CPC
PMP1_ENA
PMP2_ENA
PUMP_PST
PMP_SLCT
Enable
Off
No
No
No
Cooler Pump Control
Cooler Pump 1 Enable
Cooler Pump 2 Enable
Cooler Pmp Periodic Strt
Cooler Pump Select
0
Cooler Pump Shutdown Dly
Pump Changeover Hours
EMM Module Installed
Cnd HX Typ: 0=RTPF 1=MCHX
EXV MOP Set Point
0 to 10
10 to 2000
No/Yes
0/1
nn.n
nn.n
1
minutes
hours
PUMP_DLY
PMP_DLTA
EMM_BRD
COILTYPE
MOP_SP
100
No
1
°F
°F
Config Approach Setpoint
IAPPROSP
92
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX B — CCN TABLES (cont)
CCN CONFIGURATION TABLES — OPTIONS2 (Options 2 Configuration)
DESCRIPTION
Control Method
VALUE
DEFAULT
0
UNITS
POINT NAME
CONTROL
0 = Switch
2 = Occupancy
3 = CCN
Loading Sequence Select
Lead/Lag Circuit Select
1 = Equal Loading
2 = Staged Loading
1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
1
1
SEQ_TYP
LEAD_TYP
Cooling Setpoint Select
0 = Single
0
CLSP_TYP
1 = Dual, remote switch controlled
2 = Dual CCN occupancy
3 = 4-20 mA input
Ramp Load Select
Heat Cool Select
High LCW Alert Limit
Minutes off time
Enable/Dsable
Cool/Heat
2 to 60
Enable
Cool
60.0
0
RAMP_EBL
HEATCOOL
LCW_LMT
DELAY
F
min
0 to 15
Deadband Multiplier
Ice Mode Enable
Low Sound Mode Select
1.0 to 4.0
Enable/Dsable
1.0
Dsable
0
Z_GAIN
ICE_CNFG
LS_MODE
0 = Disabled
1 = Fan only
2 = Capacity/Fans
Low Sound Start Time
Low Sound End Time
Low Sound Capacity Limit
00:00 to 23:59
00:00 to 23:59
0 to 100
00:00
00:00
100
LS_START
LS_END
LS_LIMIT
%
CCN CONFIGURATION TABLES — SCHEDOVR (Timed Override Setup)
DESCRIPTION
Schedule Number
Override Time Limit
Timed Override Hours
Timed Override
VALUE
0 to 99
0 to 4
0 to 4
No/Yes
DEFAULT
1
0
0
UNITS
POINT NAME
SCHEDNUM
OTL
OVR_EXT
TIMEOVER
hours
hours
No
CCN CONFIGURATION TABLES — RESETCON (Temperature Reset and Demand Limit)
DESCRIPTION
COOLING RESET
VALUE
DEFAULT
UNITS
POINT NAME
Cooling Reset Type
0 = No Reset
0
CRST_TYP
1 = 4-20 mA input
2 = External temp – OAT
3 = Return Fluid
4 = External temp - SPT
4-20 MA RESET
4-20 – Degrees Reset
–30 to 30
0.0
F
420_DEG
REMOTE RESET
Remote – No Reset Temp
Remote – Full Reset Temp
Remote – Degrees Reset
0 to 125
0 to 125
–30 to 30
125.0
0.0
0.0
F
F
F
REM_NO
REM_FULL
REM_DEG
RETURN TEMPERATURE RESET
Return – No Reset Temp
Return – Full Reset Temp
Return – Degrees Reset
0 to 125
0 to 125
–30 to 30
10.0
0.0
0.0
F
F
F
RTN_NO
RTN_FULL
RTN_DEG
DEMAND LIMIT
Demand Limit Select
0 = None
0
DMD_CTRL
1 = External switch input
2 = 4-20 mA input
3 = Loadshed
Demand Limit at 20 mA
Loadshed Group Number
Loadshed Demand Delta
Maximum Loadshed Time
Demand Limit Switch 1
Demand Limit Switch 2
0 to 100
0 to 99
0 to 60
0 to 120
0 to 100
0 to 100
100
0
0
60
80
50
%
DMT20MA
SHED_NUM
SHED_DEL
SHED_TIM
DLSWSP1
DLSWSP2
%
minutes
%
%
93
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX B — CCN TABLES (cont)
CCN CONFIGURATION TABLES — DUALCHIL (Dual Chiller Configuration Settings)
DESCRIPTION
LEAD/LAG
VALUE
DEFAULT
UNITS
POINT NAME
Lead/Lag Chiller Enable
Master/Slave Select
Slave Address
Lead/Lag Balance Select
Lead/Lag Balance Delta
Lag Start Delay
Enable/Dsable
Master/Slave
0 to 239
0 = None
40 to 400
0 to 30
Dsable
Master
2
0
168
5
Yes
LL_ENA
MS_SEL
SLV_ADDR
LL_BAL
LL_BAL_D
LL_DELAY
PARALLEL
hours
minutes
Parallel Configuration
Yes
CCN CONFIGURATION TABLES — DISPLAY (Marquee Display SETUP)
DESCRIPTION
Service Password
Password Enable
Metric Display
VALUE
DEFAULT
1111
Enable
Off
UNITS
POINT NAME
PASSWORD
PASS_EBL
DISPUNIT
nnnn
Enable/Disable
Off/On
Language Selection
0 = ENGLISH
0
LANGUAGE
1 = FRANCAIS
2 = ESPANOL
3 = PORTUGUES
CCN CONFIGURATION TABLES — EXVACONF (EXV Circuit A Configuration)
DESCRIPTION
VALUE
nnn.n
DEFAULT
UNITS
%
%
steps
steps
%
steps
steps
steps
POINT NAME
EXVASTRT
EXVAMINP
EVXARANG
EXVARATE
EXVAPOSF
EXVAMINS
EXVAMAXS
EXVAOVRS
EXVATYPE
HIGH_SCT
EXV_HSCT
EXVDISCR
EXV_AFAN
EXV_MFAN
EXV_SLAG
DELAYLAG
EXV Circ. A Start Pos
EXV Circ. A Min Position
EXVA Steps in Range
EXVA Steps Per Second
EXVA Fail Position in %
EXVA Minimum Steps
EXVA Maximum Steps
EXVA Overrun Steps
50.0
8.0
1596/2500
nnn.n
nnnnn
nnnnn
nnnn.nn
nnnnn
nnnnn
nnnnn
nnn
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn
200
0
0
1596/2500
167
Bipolar
115
10
EXVA Stepper Type
High SCT Threshold
°F
%
%
%
%
Open EXV X% on 2nd Comp
Open EXV X% on DISCRSOL
Pre-Open EXV - Fan Adding
Pre-Close EXV - Fan Sub
Pre-Close EXV - Lag Shut
Lag Start Delay
5
10
10
10
%
secs
10
CCN CONFIGURATION TABLES — EXVBCONF (EXV Circuit B Configuration)
DESCRIPTION
EXV Circ. B Start Pos
VALUE
nnn.n
DEFAULT
50.0
8.0
1596/2500
200
UNITS
%
%
steps
steps
%
steps
steps
steps
POINT NAME
EXVBSTRT
EXVBMINP
EVXBRANG
EXVBRATE
EXVBPOSF
EXVBMINS
EXVBMAXS
EXVBOVRS
EXVBTYPE
EXV Circ. B Min Position
EXVB Steps in Range
EXVB Steps Per Second
EXVB Fail Position in %
EXVB Minimum Steps
EXVB Maximum Steps
EXVB Overrun Steps
EXVB Stepper Type
nnn.n
nnnnn
nnnnn
nnnn.nn
nnnnn
nnnnn
nnnnn
nnn
0
0
1596/2500
167
Bipolar
CCN CONFIGURATION TABLES — MM_CONF (Motormaster Configuration)
DESCRIPTION
Motormaster Select
Head Pressure P Gain
Head Pressure I Gain
Head Pressure D Gain
Minimum Fan Speed
VALUE
No/Yes
nnn.n
nnn.n
nnn.n
nnn.n
DEFAULT
No
UNITS
POINT NAME
MM_SLCT
HP_PGAIN
HP_IGAIN
HP_DGAIN
MIN_VHP
1.0
0.1
0.0
5.0
%
94
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX B — CCN TABLES (cont)
CCN SERVICE TABLES — SERVICE
DESCRIPTION
SERVICE
Brine Freeze Point
Pump Service Interval
COMPRESSOR ENABLE
Enable Compressor A1
Enable Compressor A2
Enable Compressor B1
Enable Compressor B2
VALUE
DEFAULT
UNITS
F
POINT NAME
nnn.n
nnnnn
BRN_FRZ
SI_PUMPS
hours
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
ENABLEA1
ENABLEA2
ENABLEB1
ENABLEB2
CCN SETPOINT TABLES — SETPOINT
DESCRIPTION
COOLING
VALUE
DEFAULT
UNITS
POINT NAME
Cooling Setpoint 1
Cooling Setpoint 2
ICE Setpoint
–20 to 70
–20 to 70
–20 to 32
44.0
44.0
32.0
F
F
F
CSP1
CSP2
CSP3
RAMP LOADING
Cooling Ramp Loading
0.2 to 2.0
–20 to 34
1.0
CRAMP
Brine Freeze Point
Head Setpoint
Fan On Set Point
Fan Off Set Point
Fan Stage Delta
34.0
F
F
F
F
F
F
BRN_FRZ
HSP
FANONSP
FANOFFSP
FSTGDLTA
B_FANOFF
Base Fan Off Delta Temp
CCN MAINTENANCE TABLES — CIRA_EXV
DESCRIPTION
EXV % Open
VALUE
nnn
DEFAULT
UNITS
%
POINT NAME
EXV_A
Circuit A Approach
Approach Setpoint
EXVA Override
Suction Superheat Temp
Active Superheat Setpt
Active MOP Setpt
nnn.n
nnn.n
nnnnn
nnn.n
nn.n
delta F
delta F
CIRA_APP
APPRA_SP
EXVAOVRR
SH_A
ACTSH_SP
ACMOP_SP
PLMA
delta F
delta F
delta F
%
nn.n
nnn
Cir A EXV Position Limit
95
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX B — CCN TABLES (cont)
CCN MAINTENANCE TABLES — CIRB_EXV
DESCRIPTION
EXV % Open
VALUE
nnn
DEFAULT
UNITS
%
POINT NAME
EXV_B
Circuit B Approach
Approach Setpoint
EXVB Override
Suction Superheat Temp
Active Superheat Setpt
Active MOP Setpt
nnn.n
nnn.n
nnnnn
nnn.n
nn.n
delta F
delta F
CIRB_APP
APPRB_SP
EXVBOVRR
SH_B
ACTSH_SP
ACMOP_SP
PLMB
delta F
delta F
delta F
%
nn.n
nnn
Cir B EXV Position Limit
CCN MAINTENANCE TABLES — STRTHOUR
DESCRIPTION
Machine Operating Hours
Machine Starts
VALUE
nnnnnn
nnnnnn
UNITS
hours
POINT NAME
HR_MACH
CY_MACH
Circuit A Run Hours
nnnnnn
nnnnnn
nnnnnn
nnnnnn
nnnnnn
nnnnnn
hours
hours
hours
hours
hours
hours
HR_CIRA
HR_A1
HR_A2
HR_CIRB
HR_B1
HR_B2
Compressor A1 Run Hours
Compressor A2 Run Hours
Circuit B Run Hours
Compressor B1 Run Hours
Compressor B2 Run Hours
Circuit A Starts
nnnnnn
nnnnnn
nnnnnn
nnnnnn
nnnnnn
nnnnnn
CY_CIRA
CY_A1
CY_A2
CY_CIRB
CY_B1
CY_B2
Compressor A1 Starts
Compressor A2 Starts
Circuit B Starts
Compressor B1 Starts
Compressor B2 Starts
PUMP HOURS
Pump 1 Run Hours
Pump 2 Run Hours
nnnnnn
nnnnnn
hours
hours
HR_PUMP1
HR_PUMP2
CCN MAINTENANCE TABLES — CURRMODS
DESCRIPTION
CSM controlling Chiller
WSM controlling Chiller
Master/Slave control
Ramp Load Limited
Timed Override in effect
Low Cooler Suction TempA
Low Cooler Suction TempB
Slow Change Override
Minimum OFF time active
Dual Setpoint
VALUE
POINT NAME
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
MODE_1
MODE_2
MODE_3
MODE_5
MODE_6
MODE_7
MODE_8
MODE_9
MODE_10
MODE_13
MODE_14
MODE_15
MODE_16
MODE_17
MODE_18
MODE_19
MODE_20
MODE_21
MODE_22
MODE_23
MODE_24
MODE_25
Temperature Reset
Demand/Sound Limited
Cooler Freeze Protection
Low Temperature Cooling
High Temperature Cooling
Making ICE
Storing ICE
High SCT Circuit A
High SCT Circuit B
Minimum Comp. On Time
Pump Off Delay Time
Low Sound Mode
96
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX B — CCN TABLES (cont)
CCN MAINTENANCE TABLES — ALARMS
DESCRIPTION
Active Alarm #1
VALUE
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
Axxx or Txxx
POINT NAME
ALARM01C
Active Alarm #2
Active Alarm #3
Active Alarm #4
Active Alarm #5
Active Alarm #6
Active Alarm #7
Active Alarm #8
Active Alarm #9
Active Alarm #10
Active Alarm #11
Active Alarm #12
Active Alarm #13
Active Alarm #14
Active Alarm #15
Active Alarm #16
Active Alarm #17
Active Alarm #18
Active Alarm #19
Active Alarm #20
Active Alarm #21
Active Alarm #22
Active Alarm #23
Active Alarm #24
Active Alarm #25
ALARM02C
ALARM03C
ALARM04C
ALARM05C
ALARM06C
ALARM07C
ALARM08C
ALARM09C
ALARM10C
ALARM11C
ALARM12C
ALARM13C
ALARM14C
ALARM15C
ALARM16C
ALARM17C
ALARM18C
ALARM19C
ALARM20C
ALARM21C
ALARM22C
ALARM23C
ALARM24C
ALARM25C
CCN MAINTENANCE TABLES — VERSIONS
DESCRIPTION
VERSION
CESR131172-
CESR131333-
CESR131460-
CESR131174-
CESR131171-
CESR130227-
VALUE
EXV
AUX
MBB
EMM
MARQUEE
NAVIGATOR
nn-nn
nn-nn
nn-nn
nn-nn
nn-nn
nn-nn
CCN MAINTENANCE TABLES — LOADFACT
DESCRIPTION
VALUE
UNITS
POINT NAME
CAPACITY CONTROL
Load/Unload Factor
Control Point
Entering Fluid Temp
Leaving Fluid Temp
snnn.n
SMZ
CTRL_PNT
EWT
snnn.n
snnn.n
snnn.n
F
F
F
LWT
Ramp Load Limited
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
MODE_5
MODE_9
MODE_16
MODE_17
MODE_18
MODE_23
Slow Change Override
Cooler Freeze Protection
Low Temperature Cooling
High Temperature Cooling
Minimum Comp. On Time
97
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX B — CCN TABLES (cont)
CCN MAINTENANCE TABLES — PM-PUMP
DESCRIPTION
Pump Service Interval
VALUE
nnnnnn
nnnnnn
Yes/No
nnnnnn
Yes/No
UNITS
hours
hours
POINT NAME
SI_PUMPS
Pump 1 Service Countdown
Pump 1 Maintenance Done
Pump 2 Service Countdown
Pump 2 Maintenance Done
Pump 1 Maintenance Date
Pump 1 Maintenance Date
Pump 1 Maintenance Date
Pump 1 Maintenance Date
Pump 1 Maintenance Date
Pump 2 Maintenance Date
Pump 2 Maintenance Date
Pump 2 Maintenance Date
Pump 2 Maintenance Date
Pump 2 Maintenance Date
P1_CDOWN
P1_MAINT
P2_CDOWN
P2_MAINT
PMP1_PM0
PMP1_PM1
PMP1_PM2
PMP1_PM3
PMP1_PM4
PMP2_PM0
PMP2_PM1
PMP2_PM2
PMP2_PM3
PMP2_PM4
hours
mm/dd/yy hh:mm
mm/dd/yy hh:mm
mm/dd/yy hh:mm
mm/dd/yy hh:mm
mm/dd/yy hh:mm
mm/dd/yy hh:mm
mm/dd/yy hh:mm
mm/dd/yy hh:mm
mm/dd/yy hh:mm
mm/dd/yy hh:mm
CCN MAINTENANCE TABLES — PM-STRN
DESCRIPTION
Strainer Srvc Interval
Strainer Srvc Countdown
Strainer Maint. Done
Strainer Maint. Date
Strainer Maint. Date
Strainer Maint. Date
Strainer Maint. Date
Strainer Maint. Date
VALUE
nnnnnn
nnnnnn
UNITS
hours
hours
POINT NAME
SI_STRNR
ST_CDOWN
ST_MAINT
STRN_PM0
STRN_PM1
STRN_PM2
STRN_PM3
STRN_PM4
Yes/No
mm/dd/yy hh:mm
mm/dd/yy hh:mm
mm/dd/yy hh:mm
mm/dd/yy hh:mm
mm/dd/yy hh:mm
CCN MAINTENANCE TABLES — PM-COIL
DESCRIPTION
Coil Cleaning Srvc Inter
Coil Service Countdown
Coil Cleaning Maint.Done
Coil Cleaning Maint.Date
Coil Cleaning Maint.Date
Coil Cleaning Maint.Date
Coil Cleaning Maint.Date
Coil Cleaning Maint.Date
VALUE
nnnnnn
nnnnnn
UNITS
hours
hours
POINT NAME
SI_COIL
CL_CDOWN
CL_MAINT
COIL_PM0
COIL_PM1
COIL_PM2
COIL_PM3
COIL_PM4
Yes/No
mm/dd/yy hh:mm
mm/dd/yy hh:mm
mm/dd/yy hh:mm
mm/dd/yy hh:mm
mm/dd/yy hh:mm
CCN MAINTENANCE TABLES — TESTMODE
DESCRIPTION
Service Test Mode
Compressor A1 Relay
Compressor A2 Relay
Compressor B1 Relay
Compressor B2 Relay
Fan 1 Relay
VALUE
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
nn
UNITS
POINT NAME
NET_CTRL
S_A1_RLY
S_A2_RLY
S_B1_RLY
S_B2_RLY
S_FAN_1
S_FAN_2
S_CLPMP1
S_CLPMP2
S_A1ULTM
S_MLV
Fan 2 Relay
Cooler Pump Relay 1
Cooler Pump Relay 2
Comp A1 Unload Time
Minimum Load Valve Relay
Remote Alarm Relay
EXV % Open
sec
On/Off
On/Off
nn
S_ALM
S_EXV_A
S_EXV_B
%
%
EXV % Open
nn
98
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX B — CCN TABLES (cont)
CCN MAINTENANCE TABLES — RUNTEST
DESCRIPTION
Percent Total Capacity
VALUE
nnn
UNITS
POINT NAME
CAPA_T
%
Percent Available Cap.
Discharge Pressure
Suction Pressure
nnn
%
CAPA_A
DP_A
SP_A
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
On/Off
On/Off
On/Off
On/Off
On/Off
nnn
psig
psig
F
F
F
F
F
^F
Head Setpoint
HSP
Saturated Condensing Tmp
Saturated Suction Temp
Compr Return Gas Temp
Discharge Gas Temp
Suction Superheat Temp
Compressor A1 Relay
Compressor A2 Relay
Minimum Load Valve Relay
Compressor A1 Feedback
Compressor A2 Feedback
Percent Total Capacity
Percent Available Cap.
Discharge Pressure
TMP_SCTA
TMP_SSTA
TMP_RGTA
DISGAS
SH_A
K_A1_RLY
K_A2_RLY
MLV_RLY
K_A1_FBK
K_A2_FBK
CAPB_T
CAPB_A
DP_B
%
%
psig
psig
F
F
F
F
^F
nnn
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
On/Off
On/Off
On/Off
Suction Pressure
Head Setpoint
SP_B
HSP
Saturated Condensing Tmp
Saturated Suction Temp
Compr Return Gas Temp
Suction Superheat Temp
Compressor B1 Relay
Compressor B2 Relay
Minimum Load Valve Relay
TMP_SCTB
TMP_SSTB
TMP_RGTB
SH_B
K_B1_RLY
K_B2_RLY
MLV_RLY
Compressor B1 Feedback
Compressor B2 Feedback
Fan 1 Relay
On/Off
On/Off
On/Off
On/Off
K_B1_FBK
K_B2_FBK
FAN_1
Fan 2 Relay
FAN_2
Outside Air Temperature
Space Temperature
Cooler Pump Relay 1
Cooler Pump Relay 2
Cooler Pump 1 Interlock
Cooler Pump 2 Interlock
Cooler Entering Fluid
Cooler Leaving Fluid
Compressor A1 Size
Compressor A2 Size
Compressor B1 Size
Compressor B2 Size
Cooler Flow Switch
nnn.n
nnn.n
F
F
OAT
SPT
On/Off
On/Off
Open/Closed
Open/Closed
nnn.n
COOLPMP1
COOLPMP2
PMP1_FBK
PMP2_FBK
COOL_EWT
COOL_LWT
SIZE_A1
SIZE_A2
SIZE_B1
SIZE_B2
COOLFLOW
F
F
tons
tons
tons
tons
nnn.n
nnn
nnn
nnn
nnn
On/Off
99
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX B — CCN TABLES (cont)
CCN MAINTENANCE TABLES — DUALCHIL
DESCRIPTION
Dual Chiller Link Good?
VALUE
Yes/No
UNITS
POINT NAME
DC_LINK
Master Chiller Role
Stand Alone,
Lead Chiller,
Lag Chiller
Stand Alone,
Lead Chiller,
Lag Chiller
MC_ROLE
SC_ROLE
Slave Chiller Role
Lead Chiller Ctrl Point
Lag Chiller Ctrl Point
Control Point
snnn.n
snnn.n
snnn.n
F
F
F
LEAD_CP
LAG_CP
CTRL_PNT
Cool EnteringFluid-Slave
Cool Leaving Fluid-Slave
Cooler Entering Fluid
Cooler Leaving Fluid
snnn.n
snnn.n
snnn.n
snnn.n
snnn.n
F
F
F
F
F
COOLEWTS
COOLLWTS
COOL_EWT
COOL_LWT
DUAL_LWT
Lead/Lag Leaving Fluid
Percent Avail.Capacity
Percent Avail.Cap.Slave
0-100
0-100
%
%
CAP_A
CAP_A_S
Lag Start Delay Time
Load/Unload Factor
Load/Unload Factor-Slave
Lead SMZ Clear Commanded
Lag SMZ Clear Commanded
Lag Commanded Off?
hh:mm
snnn.n
snnn.n
Yes/No
Yes/No
Yes/No
LAGDELAY
SMZ
SMZSLAVE
LEADSMZC
LAG_SMZC
LAG_OFF
Dual Chill Lead CapLimit
Dual Chill Lag CapLimit
0-100
0-100
%
%
DCLDCAPL
DCLGCAPL
100
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX C — FACTORY SETTINGS FOR PUMP AND MANUAL STARTERS
UNIT VOLTAGE
V-Hz (3 Ph)
OVERLOAD
SETTING
PUMP OPTION
PUMP SIZE
208/230-60
380-60
4.0
2.0
1.6
2.4
1, 8
1.0 HP
460-60
575-60
208/230-60
380-60
5.4
2.7
2.2
3.3
6.6
3.3
2.6
4.0
8.8
4.4
3.5
5.3
14.0
7.0
5.6
8.5
2, 9
3, B
1.5 HP
2.0 HP
3.0 HP
5.0 HP
7.5 HP
460-60
575-60
208/230-60
380-60
460-60
575-60
208/230-60
380-60
460-60
575-60
208/230-60
380-60
460-60
575-60
208/230-60
380-60
460-60
575-60
4, C
5, 6, D, F
7, G
22.8
11.4
9.1
13.8
101
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING
Optional BACnet Communications Wiring —
0
The following section is used to configure the UPC Open con-
troller which is used when the BACnet communications option
is selected. The UPC Open controller is mounted in the main
control box per unit components arrangement diagrams.
1
9
2
8
7
3
10's
1's
5 4
6
0
1
9
TO ADDRESS THE UPC OPEN CONTROLLER — The
user must give the UPC Open controller an address that is
unique on the BACnet* network. Perform the following proce-
dure to assign an address:
1. If the UPC Open controller is powered, pull the screw ter-
minal connector from the controller's power terminals la-
beled Gnd and HOT. The controller reads the address
each time power is applied to it.
2. Using the rotary switches (see Fig. A and B), set the con-
troller's address. Set the Tens (10's) switch to the tens dig-
it of the address, and set the Ones (1's) switch to the ones
digit.
As an example in Fig. B, if the controller’s address is 25,
point the arrow on the Tens (10's) switch to 2 and the arrow on
the Ones (1's) switch to 5.
2
8
7
3
5 4
6
Fig. B — Address Rotary Switches
BACNET DEVICE INSTANCE ADDRESS — The UPC
Open controller also has a BACnet Device Instance address.
This Device Instance MUST be unique for the complete BAC-
net system in which the UPC Open controller is installed. The
Device Instance is auto generated by default and is derived by
adding the MAC address to the end of the Network Number.
The Network Number of a new UPC Open controller is 16101,
but it can be changed using i-Vu® Tools or BACView device.
By default, a MAC address of 20 will result in a Device In-
stance of 16101 + 20 which would be a Device Instance of
1610120.
BT485
TERMINATOR
BACNET
CONNECTION
(BAS PORT)
POWER LED
Tx1 LED
Rx1 LED
Tx2 LED
Rx2 LED
BACNET
BAUD RATE
DIP SWITCHES
EIA-485
JUMPERS
ADDRESS
ROTARY
SWITCHES
RUN LED
ERROR LED
Fig. A — UPC Open Controller
* Sponsored by ASHRAE (American Society of Heating, Refrigerat-
ing, and Air Conditioning Engineers).
102
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
CONFIGURING THE BAS PORT FOR BACNET MS/
TP — Use the same baud rate and communication settings for
all controllers on the network segment. The UPC Open con-
troller is fixed at 8 data bits, No Parity, and 1 Stop bit for this
protocol's communications.
If the UPC Open controller has been wired for power, pull
the screw terminal connector from the controller's power termi-
nals labeled Gnd and HOT. The controller reads the DIP
Switches and jumpers each time power is applied to it.
Set the BAS Port DIP switch DS3 to “enable.” Set the BAS
Port DIP switch DS4 to “E1-485.” Set the BMS Protocol DIP
switches DS8 through DS5 to “MSTP.” See Table A.
Fig. C — DIP Switches
Table A — SW3 Protocol Switch Settings
for MS/TP
Wire the controllers on an MS/TP network segment in a dai-
sy-chain configuration. Wire specifications for the cable are
22 AWG (American Wire Gage) or 24 AWG, low-capacitance,
twisted, stranded, shielded copper wire. The maximum length
is 2000 ft.
Install a BT485 terminator on the first and last controller on
a network segment to add bias and prevent signal distortions
due to echoing. See Fig. A, D, and E.
DS8
DS7
DS6
DS5
DS4
DS3
Off
Off
Off
Off
On
Off
Verify that the EIA-485 jumpers below the CCN Port are set
to EIA-485 and 2W.
The example in Fig. C shows the BAS Port DIP Switches
set for 76.8k (Carrier default) and MS/TP.
Set the BAS Port DIP Switches DS2 and DS1 for the appro-
priate communications speed of the MS/TP network (9600,
19.2k, 38.4k, or 76.8k bps). See Fig. D and Table B.
To wire the UPC Open controller to the BAS network:
1. Pull the screw terminal connector from the controller's
BAS Port.
Table B — Baud Selection Table
2. Check the communications wiring for shorts and
grounds.
3. Connect the communications wiring to the BAS port’s
screw terminals labeled Net +, Net -, and Shield.
NOTE: Use the same polarity throughout the network
segment.
4. Insert the power screw terminal connector into the UPC
Open controller's power terminals if they are not current-
ly connected.
5. Verify communication with the network by viewing a
module status report. To perform a module status report
using the BACview keypad/display unit, press and hold
the “FN” key then press the “.” Key.
BAUD RATE
9,600
DS2
Off
On
Off
On
DS1
Off
Off
On
On
19,200
38,400
76,800
WIRING THE UPC OPEN CONTROLLER TO THE MS/
TP NETWORK — The UPC Open controller communicates
using BACnet on an MS/TP network segment communications
at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps.
Fig. D — Network Wiring
103
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Fig. E — BT485 Terminator Installation
To install a BT485 terminator, push the BT485 terminator
temperature rating specifications list two acceptable alterna-
tives. The Halar specification has a higher temperature rating
and a tougher outer jacket than the SmokeGard specification,
and it is appropriate for use in applications where the user is
concerned about abrasion. The Halar jacket is also less likely to
crack in extremely low temperatures.
on to the BT485 connector located near the BACnet connector.
NOTE: The BT485 terminator has no polarity associated with
it.
To order a BT485 terminator, consult Commercial Products
i-Vu Open Control System Master Prices.
MS/TP WIRING RECOMMENDATIONS — Recommen-
dations are shown in Tables C and D. The wire jacket and UL
NOTE: Use the specified type of wire and cable for maximum
signal integrity.
Table C — MS/TP Wiring Recommendations
SPECIFICATION
RECOMMMENDATION
Cable
Single twisted pair, low capacitance, CL2P, 22 AWG (7x30), TC foam FEP, plenum rated cable
22 or 24 AWG stranded copper (tin plated)
Foamed FEP 0.015 in. (0.381 mm) wall 0.060 in. (1.524 mm) O.D.
Black/White
2 in. (50.8 mm) lay on pair 6 twists/foot (20 twists/meter) nominal
Aluminum/Mylar shield with 24 AWG TC drain wire
Conductor
Insulation
Color Code
Twist Lay
Shielding
SmokeGard Jacket (SmokeGard PVC) 0.021 in. (0.5334 mm) wall 0.175 in. (4.445 mm) O.D.
Halar Jacket (E-CTFE) 0.010 in. (0.254 mm) wall 0.144 in. (3.6576 mm) O.D.
Jacket
DC Resistance
Capacitance
Characteristic Impedance
Weight
15.2 Ohms/1000 feet (50 Ohms/km) nominal
12.5 pF/ft (41 pF/meter) nominal conductor to conductor
100 Ohms nominal
12 lb/1000 feet (17.9 kg/km)
SmokeGard 167°F (75°C)
Halar -40 to 302°F (-40 to 150°C)
UL Temperature Rating
Voltage
Listing
300 Vac, power limited
UL: NEC CL2P, or better
LEGEND
AWG
CL2P
DC
— American Wire Gage
— Class 2 Plenum Cable
— Direct Current
FEP
NEC
O.D.
TC
— Fluorinated Ethylene Polymer
— National Electrical Code
— Outside Diameter
— Tinned Copper
— Underwriters Laboratories
UL
104
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Table D — Open System Wiring Specifications and Recommended Vendors
WIRING SPECIFICATIONS
Description
RECOMMENDED VENDORS AND PART NUMBERS
Connect Air
International
Contractors
Wire and Cable
Wire Type
Belden RMCORP
22 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide for
specifications.
24 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide
for specifications.
W221P-22227
W241P-2000F
—
25160PV
CLP0520LC
MS/TP
Network (RS-485)
82841 25120-OR
21450
—
Rnet
4 conductor, unshielded, CMP, 18 AWG, plenum rated.
W184C-2099BLB 6302UE
CLP0442
LEGEND
— American Wire Gage
— Class 2 Plenum Cable
— Communications Plenum Rated
— Fluorinated Ethylene Polymer
— Tinned Copper
AWG
CL2P
CMP
FEP
TC
LOCAL ACCESS TO THE UPC OPEN CONTROL-
LER — The user can use a BACview6 handheld keypad dis-
play unit or the Virtual BACview software as a local user inter-
face to an Open controller. These items let the user access the
controller network information. These are accessory items and
do not come with the UPC Open controller.
The BACview6 unit connects to the local access port on the
UPC Open controller. See Fig. F. The BACview software must
be running on a laptop computer that is connected to the local
access port on the UPC Open controller. The laptop will re-
quire an additional USB link cable for connection.
ber and CCN Bus number. The factory default settings for
CCN Element and CCN Bus number are 1 and 0 respectively.
If modifications to the default Element and Bus number are
required, both the ComfortLink and UPC Open configurations
must be changed.
The following configurations are used to set the CCN Ad-
dress and Bus number in the ComfortLink control. These con-
figurations can be changed using the scrolling marquee display
or accessory Navigator handheld device.
Configuration→CCN→CCN.A (CCN Address)
Configuration→CCN→CCN.B (CCN Bus Number)
The following configurations are used to set the CCN Ad-
dress and Bus Number in the UPC Open controller. These con-
figurations can be changed using the accessory BACview6 dis-
play.
See the BACview Installation and User Guide for instruc-
tions on connecting and using the BACview6 device.
To order a BACview6 Handheld (BV6H), consult Commer-
cial Products i-Vu Open Control System Master Prices.
CONFIGURING THE UPC OPEN CONTROLLER'S
PROPERTIES — The UPC Open device and ComfortLink
control must be set to the same CCN Address (Element) num-
Navigation: BACview→CCN
Home: Element Comm Stat
Element: 1
Bus: 0
Fig. F — BACview6 Device Connection
105
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
If the UPC Open is used with the chiller application of
traffic based on the baud rate set. The higher the baud rate the
more solid the LEDs become. See Fig. A for location of LEDs
on UPC Open module.
REPLACING THE UPC OPEN BATTERY — The UPC
Open controller's 10-year lithium CR2032 battery provides a
minimum of 10,000 hours of data retention during power out-
ages.
Lead/Lag/Standby, all chillers and UPC Open's CCN element
numbers must be changed to a unique number in order to fol-
low CCN specifications. In this application, there can only be a
maximum of 3 UPC Open controllers on a CCN bus.
For the CCN Alarm Acknowledger configuration, the UPC
Open defaults to CCN Acknowledger. If a Chiller Lead/Lag/
Standby application is being used, then the Carrier technician
must change the configuration to only one CCN Acknowledger
on the CCN bus.
For the CCN Time Broadcaster configuration, the UPC
Open defaults to CCN Time Broadcaster. If the Chiller Lead/
Lag/Standby application is used, then the Carrier technician
must change the configuration to only one CCN Time Broad-
caster on the CCN bus.
TROUBLESHOOTING — If there are problems wiring or
addressing the UPC Open controller, contact Carrier Technical
Support.
COMMUNICATION LEDS — The LEDs indicate if the
controller is communicating with the devices on the network.
See Tables E and F. The LEDs should reflect communication
IMPORTANT: Power must be ON to the UPC Open when
replacing the battery, or the date, time, and trend data will
be lost.
Remove the battery from the controller, making note of the
battery's polarity. Insert the new battery, matching the battery's
polarity with the polarity indicated on the UPC Open
controller.
NETWORK POINTS LIST — The points list for the control-
ler is shown in Table G.
Refer to Appendix B for additional information on CCN
point name.
Table E — LED Status Indicators
LED
STATUS
Lights when power is being supplied to the controller. The UPC Open controller is protected by internal solid-state polyswitches on
the incoming power and network connections. These polyswitches are not replaceable and will reset themselves if the condition
that caused the fault returns to normal.
Power
Rx
Tx
Run
Error
Lights when the controller receives data from the network segment; there is an Rx LED for Ports 1 and 2.
Lights when the controller transmits data to the network segment; there is an Rx LED for Ports 1 and 2.
Lights based on controller status. See Table F.
Lights based on controller status. See Table F.
Table F — Run and Error LEDs Controller and Network Status Indication
RUN LED
ERROR LED
STATUS
2 flashes per second
2 flashes per second
2 flashes per second
2 flashes per second
2 flashes per second
5 flashes per second
5 flashes per second
7 flashes per second
Off
Normal
2 flashes, alternating with Run LED
3 flashes, then off
1 flash per second
On
On
Off
Five minute auto-restart delay after system error
Controller has just been formatted
Controller is alone on the network
Exec halted after frequent system errors or control programs halted
Exec start-up aborted, Boot is running
Firmware transfer in progress, Boot is running
Ten second recovery period after brownout
7 flashes per second, alternating with Run LED
14 flashes per second 14 flashes per second, alternating with Run LED Brownout
106
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Table G — Network Points List
CCN POINT READ/
DEFAULT
VALUE
BACNET
BACNET
POINT DESCRIPTION
UNITS
RANGE
NAME
LMT_MA
RST_MA
DEM_LIM
SP
WRITE
OBJECT ID
OBJECT NAME
4-20 ma Demand Signal
4-20 ma Reset Signal
Active Demand Limit
Active Setpoint
R
R
R/W
R
mA
°F
%
AV:36
AV:33
AV:2
lmt_ma_1
rst_ma_1
dem_lim_1
sp_1
100
0 - 100
°F
AV:4
1 = Normal
2 = Alert
3 = Alarm
Alarm State
ALM
R
MSV:1
alm_msv_1
CCN Chiller
CCN Loadshed Signal
Circuit A Run Hours
Circuit A Starts
Circuit B Run Hours
CHIL_S_S
DL_STAT
HR_CIRA
CY_CIRA
HR_CIRB
CY_CIRB
CL_MAINT
SI_COIL
CL_CDOWN
A1UNLTME
TMP_RGTA
TMP_RGTB
K_A1_FBK
K_A1_RLY
HR_A1
R/W
R
R
R
R
Start
Start/Stop
BV:4
AV:37
AV:59
AV:65
AV:62
AV:68
BV:54
AV:50
AV:49
AV:73
AV:20
AV:28
BV:16
BV:13
AV:60
AV:66
BV:17
BV:14
AV:61
AV:67
BV:20
BV:18
AV:63
AV:69
BV:21
BV:19
AV:64
AV:70
chil_s_s_1
dl_stat_1
hr
hr
hr_cira_1
cy_cira_1
hr_cirb_1
cy_cirb_1
cl_maint_1
si_coil_1
cl_cdown_1
a1unltme_1
tmp_rgta_1
tmp_rgtb_1
k_a1_fbk_1
k_a1_rly_1
hr_a1_1
Circuit B Starts
R
Coil Cleaning Maint.Done
Coil Cleaning Srvc Inter
Coil Service Countdown
Comp A1 Unload Time
Compr Return Gas Temp
Compr Return Gas Temp
Compressor A1 Feedback
Compressor A1 Relay
Compressor A1 Run Hours
Compressor A1 Starts
Compressor A2 Feedback
Compressor A2 Relay
Compressor A2 Run Hours
Compressor A2 Starts
Compressor B1 Feedback
Compressor B1 Relay
Compressor B1 Run Hours
Compressor B1 Starts
Compressor B2 Feedback
Compressor B2 Relay
Compressor B2 Run Hours
Compressor B2 Starts
R/W
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
No
8760
Yes/No
0 - 65535
hr
hr
°F
°F
hr
hr
hr
hr
CY_A1
cy_a1_1
K_A2_FBK
K_A2_RLY
HR_A2
k_a2_fbk_1
k_a2_rly_1
hr_a2_1
CY_A2
cy_a2_1
K_B1_FBK
K_B1_RLY
HR_B1
k_b1_fbk_1
k_b1_rly_1
hr_b1_1
CY_B1
R
R
R
R
cy_b1_1
K_B2_FBK
K_B2_RLY
HR_B2
k_b2_fbk_1
k_b2_rly_1
hr_b2_1
CY_B2
R
cy_b2_1
1 = Test
2 = Local Off
3 = CCN Off
4 = Clock Off
5 = Emergency Stop
6= Local On
Control Mode
CONTROL
R
MSV:2
stat_msv_1
7 = CCN On
8 = Clock On
9 = Heat Enabled
10 = Pump Delay
Control Point
Cooler Entering Fluid
Cooler Flow Switch
CTRL_PNT
COOL_EWT
COOLFLOW
MODE_16
COOL_LWT
LWT_SP
PMP1_FBK
PMP2_FBK
COOLPMP1
COOLPMP2
PMP_SLCT
PUMP_DLY
COOL_HTR
CRAMP
R/W
R
R
R
R
R
R
R
R
R
R
R/W
R
R/W
R/W
°F
°F
44.0
-20 - 70
AV:5
AV:30
BV:11
BV:42
AV:31
AV:38
BV:9
BV:10
BV:7
BV:8
AV:40
AV:41
BV:24
AV:56
AV:53
ctrl_pnt_1
cool_ewt_1
coolflow_1
mode_16_1
cool_lwt_1
lwt_sp_1
pmp1_fbk_1
pmp2_fbk_1
coolpmp1_1
coolpmp2_1
pmp_slct_1
pump_dly_1
cool_htr_1
cramp_1
Cooler Freeze Protection
Cooler Leaving Fluid
Cooler LWT Setpoint
Cooler Pump 1 Interlock
Cooler Pump 2 Interlock
Cooler Pump Relay 1
Cooler Pump Relay 2
Cooler Pump Select
Cooler Pump Shutdown Dly
Cooler/Pump Heater
Cooling Ramp Loading
Cooling Setpoint 1
°F
°F
min
°F
1
0 - 10
1.0
44.0
0.2 - 2.0
-20 - 70
CSP1
csp1_1
LEGEND
R
W
— Read
— Write
107
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Table G — Network Points List (cont)
READ/
WRITE
DEFAULT
VALUE
BACNET
OBJECT ID
BACNET
OBJECT NAME
POINT DESCRIPTION
POINT NAME
UNITS
RANGE
Cooling Setpoint 2
CSM Controlling Chiller
Demand Level 1
Demand Level 2
Demand Level 3
Demand Limit Switch 1
Demand Limit Switch 2
Demand/Sound Limited
Discharge Gas Temp
Discharge Pressure
Discharge Pressure
Dual Setpoint
CSP2
MODE_1
R/W
R
R
R
R
R
R
R
R
R
R
R
R
°F
44.0
-20 - 70
AV:54
BV:30
AV:75
AV:76
AV:77
BV:25
BV:26
BV:41
AV:15
AV:13
AV:23
BV:39
BV:29
BV:2999
csp2_1
mode_1_1
%
%
%
dmv_lvl_1_perct_1
dmv_lvl_2_perct_1
dmv_lvl_3_perct_1
dmd_sw1_1
dmd_sw2_1
mode_15_1
disgas_1
dp_a_1
dp_b_1
mode_13_1
dual_in_1
element_stat_1
DMD_SW1
DMD_SW2
MODE_15
DISGAS
DP_A
DP_B
MODE_13
DUAL_IN
°F
psig
psig
Dual Setpoint Switch
Element Comm Status
R
Element Communications
Alarm
R
BV:58
comm_lost_alm_1
Emergency Stop
Entering Fluid Temp
EXV % Open
EXV % Open
Fan 1 Relay
Fan 2 Relay
Head Setpoint
Heat Request
High SCT Circuit A
High SCT Circuit B
High Temperature Cooling
Ice Done
EMSTOP
EWT
EXV_A
EXV_B
FAN_1
R/W
R
R
R
R
R
R
R
R
R
R
R
R/W
Enabled
Enabled/Emstop
BV:6
AV:6
emstop_1
ewt_1
exv_a_1
exv_b_1
fan_1_1
°F
%
%
AV:18
AV:27
BV:22
BV:23
AV:29
BV:28
BV:47
BV:48
BV:44
BV:27
AV:55
FAN_2
HSP
fan_2_1
hsp_1
°F
HEAT_REQ
MODE_21
MODE_22
MODE_18
ICE_DONE
CSP3
heat_req_1
mode_21_1
mode_22_1
mode_18_1
ice_done_1
csp3_1
Ice Setpoint
°F
32.0
1
-20 - 32
1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
Lead/Lag Circuit Select
LEAD_TYP
R/W
AV:43
lead_typ_1
Lead/Lag Circuit Select
Lead/Lag Leaving Fluid
Leadpump
Leaving Fluid Temp - Prime
Variable
LEAD_TYP
DUAL_LWT
LEADPUMP
R
R
R
MSV:6
AV:32
MSV:9
lead_typ_msv_1
dual_lwt_1
leadpump_msv_1
°F
°F
LWT
R
AV:7
lwt_1
Loading Sequence Select
Local Schedule
Low Cooler Suction Temp A
Low Cooler Suction Temp B
Low Sound Active
SEQ_TYPE
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W
R
R
R
AV:74
BV:1
BV:35
BV:36
BV:2
BV:51
BV:43
AV:57
AV:58
BV:45
BV:32
BV:49
BV:15
BV:38
AV:42
BV:3
seq_type_1
schedule_1
mode_7_1
mode_8_1
lsactive_1
mode_25_1
mode_17_1
hr_mach_1
cy_mach_1
mode_19_1
mode_3_1
mode_23_1
mlv_rly_1
mode_10_1
delay_1
MODE_7
MODE_8
LSACTIVE
MODE_25
MODE_17
HR_MACH
CY_MACH
MODE_19
MODE_3
MODE_23
MLV_RLY
MODE_10
DELAY
Low Sound Mode
Low Temperature Cooling
Machine Operating Hours
Machine Starts
hr
Making ICE
Master/Slave Control
Minimum Comp. On Time
Minimum Load Valve Relay
Minimum OFF Time Active
Minutes Off Time
min
°F
0
0 - 15
Occupied
OCC
OAT
MODE
CAP_A
occ_1
oat_1
mode_1
capa_a_1
capb_a_1
Outside Air Temperature
Override Modes in Effect
Percent Available Cap.
Percent Available Cap.
AV:34
BV:5
AV:12
AV:22
R
R
%
%
CAPB_A
LEGEND
R
W
— Read
— Write
108
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Table G — Network Points List (cont)
READ/
WRITE
DEFAULT
VALUE
BACNET
OBJECT ID
BACNET
OBJECT NAME
POINT DESCRIPTION
POINT NAME
UNITS
RANGE
Percent Total Capacity
Percent Total Capacity
Percent Total Capacity
Pump 1 Maintenance Done
Pump 1 Run Hours
Pump 1 Service Countdown
Pump 2 Maintenance Done
Pump 2 Run Hours
Pump 2 Service Countdown
Pump Changeover Hours
Pump Off Delay Time
Pump Service Interval
Ramp Load Limited
CAP_T
CAPA_T
CAPB_T
R
R
R
R/W
R
R
R/W
R
R
R/W
R
R/W
R
%
%
%
AV:3
AV:11
AV:21
BV:52
AV:71
AV:46
BV:53
AV:72
AV:47
AV:39
BV:50
AV:48
BV:33
AV:9
cap_t_1
capa_t_1
capb_t_1
P1_MAINT
HR_PUMP1
P1_CDOWN
P2_MAINT
HR_PUMP2
P2_CDOWN
PMP_DLTA
MODE_24
SI_PUMPS
MODE_5
STAGE
No
No
Yes/No
Yes/No
p1_maint_1
hr_pump1_1
p1_cdown_1
p2_maint_1
hr_pump2_1
p2_cdown_1
pmp_dlta_1
mode_24_1
si_pumps_1
mode_5_1
stage_1
hr
hr
hr
hr
hr
500
10 - 2000
0 - 65535
hr
8760
Requested Stage
R
Rotate Cooler Pumps Now
Saturated Condensing Tmp
Saturated Condensing Tmp
Saturated Suction Temp
Saturated Suction Temp
Slow Change Override
Space Temperature
ROT_PUMP
TMP_SCTA
TMP_SCTB
TMP_SSTA
TMP_SSTB
MODE_9
SPT
MODE_20
ST_MAINT
ST_CDOWN
SI_STRNR
SP_A
R/W
R
R
R
R
R
R/W
R
R/W
R
R/W
R
No
No/Yes
BV:12
AV:16
AV:25
AV:17
AV:26
BV:37
AV:35
BV:46
BV:55
AV:52
AV:51
AV:14
AV:24
AV:44
AV:45
rot_pump_1
tmp_scta_1
tmp_sctb_1
tmp_ssta_1
tmp_sstb_1
mode_9_1
spt_1
mode_20_1
st_maint_1
st_cdown_1
si_strnr_1
sp_a_1
°F
°F
°F
°F
°F
8760
No
-40.0 - 245
Yes/No
Storing ICE
Strainer Maint. Done
Strainer Srvc Countdown
Strainer Srvc Interval
Suction Pressure
Suction Pressure
Suction Superheat Temp
Suction Superheat Temp
hr
hr
psig
psig
°^F
°^F
8760
0 - 65535
SP_B
SH_A
SH_B
R
R
R
sp_b_1
sh_a_1
sh_b_1
System Cooling Demand
Level
R
AV:9006
cool_demand_level_1
System Demand Limiting
Temperature Reset
R
R
R
BV:57
BV:40
BV:34
dem_lmt_act_1
mode_14_1
mode_6_1
MODE_14
MODE_6
Timed Override In Effect
User Defined Analog 1
User Defined Analog 2
User Defined Analog 3
User Defined Analog 4
User Defined Analog 5
User Defined Binary 1
User Defined Binary 2
User Defined Binary 3
User Defined Binary 4
User Defined Binary 5
Var Head Press Output
WSM Controlling Chiller
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
sq m
sq m
sq m
sq m
sq m
sq m
sq m
sq m
sq m
sq m
mA
AV:2901
AV:2902
AV:2903
AV:2904
AV:2905
BV:2911
BV:2912
BV:2913
BV:2914
BV:2915
AV:19
user_analog_1_1
user_analog_2_1
user_analog_3_1
user_analog_4_1
user_analog_5_1
user_binary_1_1
user_binary_2_1
user_binary_3_1
user_binary_4_1
user_binary_5_1
vhp_act_1
VHP_ACT
MODE_2
R
BV:31
mode_2_1
LEGEND
R
W
— Read
— Write
109
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS
30RAP Maintenance Interval Requirements
WEEKLY
Compressor
Cooler
Check oil level.
None.
Economizer
Controls
Starter
None.
Review Alarm/Alert History.
None.
Condenser
None.
MONTHLY
Compressor
Cooler
Check oil level.
None.
Economizer
Controls
Starter
None.
Inspect sight glass for moisture and refrigerant level.
None.
Condenser
None.
QUARTERLY
Economizer
Compressor
Cooler
Check oil level
None.
Check refrigerant charge. Check all connec-
tions for leaks.
Perform an Automated Controls test. Run all compressors
and ensure proper operation.
Controls
Condenser
None.
Starter
Ensure operation of units flow switch.
ANNUALLY
Check Oil Level. Obtain and test an oil
sample.
Check refrigerant charge. Check all connec-
tions for leaks. Check approach on unit to
determine if tubes need cleaning. Check for
temperature drop across filter drier to deter-
mine if filter needs replacement.
Compressor
Cooler
Economizer
Verify proper operation of EXVs and TXVs
Perform an Automated Controls test. Run all compressors
and ensure proper operation. Ensure operation of unit flow
switch.
Controls
Inspect all coils and clean. Check condenser
approach to determine if tubes need to be
cleaned.
Inspect all electrical connections and tighten as needed.
Measure current to each compressor and inspect contac-
tors.
Condenser
Starter
NOTE: Equipment failures caused by lack of adherence to the Main-
tenance Interval Requirements are not covered under warranty.
110
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS (cont)
30RAP Weekly Maintenance Log
Plant ___________________________
Machine Model No. ________________
CHECK ALARMS
/ FAULTS
OPERATOR
INITIALS
DATE
OIL LEVEL
REMARKS
NOTE: Equipment failures caused by lack of adherence to the Main-
tenance Interval Requirements are not covered under warranty.
111
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS (cont)
30RAP Monthly Maintenance Log
Month
Date
1
2
3
4
5
6
7
8
9
10
/
11
/
12
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
Operator
UNIT SECTION
Compressor
ACTION
UNIT
yes/no
yes/no
ppm
ENTRY
Check Oil Level
Send Oil Sample Out for Analysis
Leak Test
Annually
Inspect and Clean Cooler
Inspect Cooler Heater
yes/no
amps
Every 3 - 5 Years
Cooler
Leak Test
yes/no
PSI
yes/no
ppm
Record Water Pressure Differential (PSI)
Inspect Water Pumps
Leak Test
Condenser
Controls
Starter
Inspect and Clean Condenser Coil
General Cleaning and Tightening Connections
Check Pressure Transducers
Confirm Accuracy of Thermistors
General Tightening & Cleaning Connections
Inspect All Contactors
Check Refrigerant Charge
Verify Operation Of EXVs And Record Position
Record System Super Heat
yes/no
yes/no
yes/no
yes/no
yes/no
yes/no
yes/no
0-100%
deg. F
Annually
Annually
Annually
System
NOTE: Equipment failures caused by lack of adherence to the Maintenance Interval Requirements
are not covered under warranty.
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS (cont)
30RAP Seasonal Shutdown Log
Month
Date
1
2
3
/
4
5
/
6
/
7
/
8
/
9
/
10
/
11
/
12
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
Operator
UNIT SECTION
Cooler
ACTION
Isolate and Drain Cooler
Add Glycol for Freeze Protection
Do Not Disconnect Control Power
ENTRY
Controls
NOTE: Equipment failures caused by lack of adherence to the Maintenance Interval Requirements
are not covered under warranty.
Download from Www.Somanuals.com. All Manuals Search And Download.
Copyright 2010 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300067-01
Printed in U.S.A.
Form 30RAP-2T
Pg 114
12-10
Replaces: 30RAP-1T
Download from Www.Somanuals.com. All Manuals Search And Download.
START-UP CHECKLIST FOR 30RAP LIQUID CHILLER
(Remove and use for Job File)
I. Project Information
JOB NAME ______________________________________________________________________________
ADDRESS _______________________________________________________________________________
CITY ____________________________________________ STATE _______________ ZIP______________
INSTALLING CONTRACTOR ________________________________________________________________
SALES OFFICE ___________________________________________________________________________
START-UP PERFORMED BY ________________________________________________________________
Design Information
CAPACITY
CEAT
EWT
LWT
FLUID TYPE
FLOW RATE
P.D.
UNIT MODEL ______________________________ SERIAL ________________________________
II. Preliminary Equipment Check
IS THERE ANY PHYSICAL DAMAGE?
YES NO
DESCRIPTION ____________________________________________________________________________
________________________________________________________________________________________
1. UNIT IS INSTALLED LEVEL AS PER THE INSTALLATION INSTRUCTIONS.
2. POWER SUPPLY AGREES WITH THE UNIT NAMEPLATE.
3. ELECTRICAL POWER WIRING IS INSTALLED PROPERLY.
4. UNIT IS PROPERLY GROUNDED.
YES NO
YES NO
YES NO
YES NO
5. ELECTRICAL CIRCUIT PROTECTION HAS BEEN SIZED AND INSTALLED PROPERLY. YES NO
6. ALL TERMINALS ARE TIGHT.
YES NO
YES NO
YES NO
YES NO
7. ALL PLUG ASSEMBLIES ARE TIGHT.
8. ALL CABLES AND THERMISTORS HAVE BEEN INSPECTED FOR CROSSED WIRES.
9. ALL THERMISTORS ARE FULLY INSERTED INTO WELLS.
Chilled Water System Check
1. ALL CHILLED WATER VALVES ARE OPEN.
YES NO
YES NO
YES NO
YES NO
2. ALL PIPING IS CONNECTED PROPERLY.
3. ALL AIR HAS BEEN PURGED FROM THE SYSTEM.
4. CHILLED WATER PUMP IS OPERATING WITH THE CORRECT ROTATION.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300067-01 Printed in U.S.A. Form 30RAP-2T Pg CL-1 12-10 Replaces: 30RAP-1T
Download from Www.Somanuals.com. All Manuals Search And Download.
5. CHILLED WATER PUMP STARTER INTERLOCKED WITH CHILLER.
6. CHILLED WATER FLOW SWITCH IS OPERATIONAL.
YES NO
YES NO
YES NO
YES NO
7. WATER LOOP VOLUME GREATER THAN MINIMUM REQUIREMENTS. (See Table 40).
8. PROPER LOOP FREEZE PROTECTION PROVIDED TO _____ °F (°C).
ANTIFREEZE TYPE _____________________ CONCENTRATION __________%.
IF OUTDOOR AMBIENT IS BELOW 32 F (0° C) THEN ITEMS 9-11 HAVE TO BE
COMPLETED TO PROVIDE COOLER FREEZE PROTECTION TO –20 F (–29 C). (REFER
TO WINTER SHUTDOWN FOR PROPER COOLER WINTERIZATION PROCEDURE.)
9. OUTDOOR PIPING WRAPPED WITH ELECTRIC HEATER TAPE,
INSULATED AND OPERATIONAL.
YES NO
10. COOLER HEATERS INSTALLED AND OPERATIONAL.
11. CHILLED WATER PUMP CONTROLLED BY CHILLER.
YES NO
YES NO
III. Unit Start-Up
1. COMPRESSOR OIL LEVEL IS CORRECT.
YES NO
YES NO
YES NO
YES NO
YES NO
2. VERIFY COMPRESSOR MOUNTING BOLT TORQUE IS 7-10 FT-LB. (9.5-13.5 N-M).
3. LEAK CHECK UNIT. LOCATE, REPAIR AND REPORT ANY REFRIGERANT LEAKS.
4. VOLTAGE IS WITHIN UNIT NAMEPLATE RANGE.
5. CONTROL TRANSFORMER PRIMARY CONNECTION SET FOR PROPER VOLTAGE.
6. CONTROL TRANSFORMER SECONDARY VOLTAGE =
7. CHECK VOLTAGE IMBALANCE:
AVERAGE VOLTAGE =
A-B
A-C
B-C
(A-B + A-C + B-C)/3
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =
VOLTAGE IMBALANCE = ____________% (MAX. DEVIATION/AVERAGE VOLTAGE) X 100
VOLTAGE IMBALANCE LESS THAN 2%.
(DO NOT START CHILLER IF VOLTAGE IMBALANCE IS GREATER THAN 2%.
CONTACT LOCAL UTILITY FOR ASSISTANCE.)
YES NO
YES NO
8. VERIFY COOLER FLOW RATE.
PRESSURE ENTERING COOLER
PRESSURE LEAVING COOLER
COOLER PRESSURE DROP
Psig X 2.31 ft./psi =
________ psig (kPa)
________ psig (kPa)
________ psig (kPa)
________ ft of water
________ m of water
kPa X 0.334 m/psi
COOLER FLOW RATE
________ gpm (l/s) (See Cooler Pressure
Drop Curves from
Installation Instructions)
Start and Operate Machine. Complete the Following:
1. COMPLETE COMPONENT TEST.
YES NO
YES NO
2. CHECK REFRIGERANT AND OIL CHARGE.
3. RECORD COMPRESSOR MOTOR CURRENT.
4. RECORD CONFIGURATION SETTINGS.
YES NO
YES NO
5. RECORD OPERATING TEMPERATURES AND PRESSURES.
6. PROVIDE OPERATING INSTRUCTIONS TO OWNER’S PERSONNEL.
YES NO
Instruction Time ________ hours.
CL-2
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATING DATA:
RECORD THE FOLLOWING INFORMATION FROM THE PRESSURES AND TEMPERATURES MODES WHEN
MACHINE IS IN A STABLE OPERATING CONDITION:
PRESSURE/TEMPERATURE
CIRCUIT A
CIRCUIT B
DISCHARGE PRESSURE
DP.A
DP.B
SUCTION PRESSURE
SP.A
SP.B
SATURATED CONDENSING TEMP
SATURATED SUCTION TEMP
RETURN GAS TEMPERATURE
LIQUID LINE TEMPERATURE*
DISCHARGE LINE TEMPERATURE*
*Readings taken with a digital thermometer.
SCT.A
SST.A
RGT.A
SCT.B
SST.B
RGT.B
COOLER EWT
EWT
LWT
COOLER LWT
OUTDOOR-AIR TEMPERATURE
CONTROL POINT
OAT
CTPT
CAP
PERCENT TOTAL CAPACITY
LEAD/LAG LEAVING FLUID
DLWT
(Dual Chiller Control Only)
Compressor Running Current — All readings taken at full load.
COMPRESSOR MOTOR CURRENT
COMPRESSOR A1
L1
L1
L1
L2
L2
L2
L3
COMPRESSOR A2
COMPRESSOR B1
COMPRESSOR B2
CONDENSER FAN MOTOR CURRENT
FAN MOTOR 1
L3
FAN MOTOR 2
FAN MOTOR 3
FAN MOTOR 4
COOLER PUMP MOTOR CURRENT
COOLER PUMP 1
L3
COOLER PUMP 2
CL-3
Download from Www.Somanuals.com. All Manuals Search And Download.
Record Software Versions
MODE — RUN STATUS
SUB-MODE
VERS
ITEM
DISPLAY
ITEM
EXPANSION
MBB
AUX1
EXV
EMM
MARQUEE
NAVIGATOR
CESR-131460- _ _-_ _
CESR-131333- _ _-_ _
CESR-131172- _ _-_ _
CESR-131174- _ _-_ _
CESR-131171- _ _-_ _
CESR-131227- _ _-_ _
(PRESS ENTER AND ESCAPE SIMULTANEOUSLY TO OBTAIN
SOFTWARE VERSIONS)
COMMENTS:
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
SIGNATURES:
START-UP
CUSTOMER
TECHNICIAN _____________________________
REPRESENTATIVE _____________________________
DATE ___________________________________
DATE ________________________________________
CL-4
Download from Www.Somanuals.com. All Manuals Search And Download.
III. Unit Start-Up (cont)
RECORD CONFIGURATION SETTINGS
UNIT (Configuration Settings)
SUBMODE
ITEM
ITEM EXPANSION
UNIT CONFIGURATION
UNIT SIZE
DISPLAY
ENTRY
SIZE
SZA.1
SZA.2
SZA.3
SZA.4
SZB.1
SZB.2
SZB.3
SZB.4
SH.SP
FAN.S
EXV
XXX
XX
COMPRESSOR A1 SIZE
COMPRESSOR A2 SIZE
COMPRESSOR A3 SIZE
COMPRESSOR A4 SIZE
COMPRESSOR B1 SIZE
COMPRESSOR B2 SIZE
COMPRESSOR B3 SIZE
COMPRESSOR B4 SIZE
SUPERHEAT SETPOINT
FAN STAGING SELECT
EXV MODULE INSTALLED
COMPRESSOR A1 DIGITAL?
MAXIMUM A1 UNLOAD TIME
XX
XX
XX
XX
UNIT
XX
XX
XX
XX.X F
X
YES/NO
YES/NO
XX
A1.TY
MAX.T
PRESS ESCAPE KEY TO DISPLAY ‘UNIT’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT1’.
PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW:
OPTIONS1 (Options Configuration)
SUBMODE
ITEM
ITEM EXPANSION
UNIT OPTIONS 1 HARDWARE
COOLER FLUID
DISPLAY
ENTRY
FLUD
MLV.S
D.G.EN
CSB.E
CPC
X
YES/NO
ENBL/DSBL
ENBL/DSBL
ON/OFF
YES/NO
YES/NO
YES/NO
X
MINIMUM LOAD VALVE SELECT
DISCHARGE GAS TEMP ENABLE
CSB BOARDS ENABLE
COOLER PUMP CONTROL
COOLER PUMP 1 ENABLE
COOLER PUMP 2 ENABLE
COOLER PMP PERIODIC STRT
COOLER PUMP SELECT
PM1E
PM2E
PM.P.S
PM.SL
PM.DY
PM.DT
ROT.P
EMM
OPT1
COOLER PUMP SHUTDOWN DLY
PUMP CHANGEOVER HOURS
ROTATE COOLER PUMPS NOW
EMM MODULE INSTALLED
CND HX TYP 0=RTPF 1=MCHX
EXV MOP SET POINT
XX MIN
XXXX HRS
YES/NO
YES/NO
0/1
CND.T
MOPS
APPR
XX
CONFIG APPROACH SETPOINT
XX
CL-5
Download from Www.Somanuals.com. All Manuals Search And Download.
III. Unit Start-Up (cont)
PRESS ESCAPE KEY TO DISPLAY ‘OPT1’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT2’.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.
OPTIONS2 (Options Configuration)
SUBMODE
ITEM
ITEM EXPANSION
UNIT OPTIONS 2 CONTROLS
CONTROL METHOD
DISPLAY
ENTRY
CTRL
LOAD
LLCS
X
LOADING SEQUENCE SELECT
LEAD/LAG CIRCUIT SELECT
HIGH LCW ALERT LIMIT
MINUTES OFF TIME
X
X
LCWT
DELY
XX.X F
XX
ICE.M
CLS.C
LS.MD
LS.ST
LS.ND
LS.LT
CTRL
CCNA
CCNB
ICE MODE ENABLE
ENBL/DSBL
ENBL/DSBL
X
OPT2
CLOSE CONTROL SELECT
LOW SOUND MODE SELECT
LOW SOUND START TIME
LOW SOUND END TIME
LOW SOUND CAPACITY LIMIT
CONTROL METHOD
00:00
00:00
XXX %
X
CCN ADDRESS
XXX
CCN BUS NUMBER
XXX
PRESS ESCAPE KEY TO DISPLAY ‘OPT2’. PRESS DOWN ARROW KEY TO DISPLAY ‘CCN’.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.
CCN (CCN Network Configuration)
SUB-MODE
CCN
ITEM
CCNA
CCNB
BAUD
ITEM EXPANSION
CCN ADDRESS
DISPLAY
XXX
ENTRY
CCN BUS NUMBER
CCN BAUD RATE
XXX
X
PRESS ESCAPE KEY TO DISPLAY ‘CCN’. PRESS DOWN ARROW KEY TO DISPLAY ‘HP.A’.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.
HP.A (Head Pressure Cmp. Delta Configuration)
SUB-MODE
HP.A
ITEM
A1.DT
A2.DT
ITEM EXPANSION
DISPLAY
XX
ENTRY
SCT DELTA FOR COMP A1
SCT DELTA FOR COMP A2
XX
PRESS ESCAPE KEY TO DISPLAY ‘HP.A’. PRESS DOWN ARROW KEY TO DISPLAY ‘HP.B’.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.
HP.B (Head Pressure Cmp. Delta Configuration)
SUB-MODE
HP.B
ITEM
B1.DT
B2.DT
ITEM EXPANSION
DISPLAY
XX
ENTRY
SCT DELTA FOR COMP B1
SCT DELTA FOR COMP B2
XX
CL-6
Download from Www.Somanuals.com. All Manuals Search And Download.
III. Unit Start-Up (cont)
PRESS ESCAPE KEY TO DISPLAY ‘HP.B’. PRESS DOWN ARROW KEY TO DISPLAY ‘EXV.A’.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.
EXV.A (Circuit A EXV Configuration)
SUB-MODE
ITEM
STR.A
MIN.A
RNG.A
SPD.A
POF.A
MIN.A
MAX.A
OVR.A
TYP.A
H.SCT
X.PCT
X.PER
A.PCT
M.PCT
S.PCT
DELY
ITEM EXPANSION
EXV CIRC.A START POS
EXV CIRC.A MIN POSITION
EXVA STEPS IN RANGE
EXVA STEPS PER SECOND
EXVA FAIL POSITION IN %
EXVA MINIMUM STEPS
DISPLAY
XXX
ENTRY
XXX
XXXXX
XXXXX
XXX
XXXXX
XXXXX
XXX
EXVA MAXIMUM STEPS
EXVA OVERRUN STEPS
EXVA STEPPER TYPE
EXV.A
0,1
HIGH SCT THRESHOLD
OPEN EXV X% ON 2ND COMP
MOVE EXV X% ON DISCRSOL
PRE-OPEN EXV - FAN ADDING
PRE-CLOSE EXV - FAN SUB
PRE-CLOSE EXV - LAG SHUT
LAG START DELAY
XXX
XX
XX
XXX
XXX
XXX
XXX
PRESS ESCAPE KEY TO DISPLAY ‘EXV.A’. PRESS DOWN ARROW KEY TO DISPLAY ‘EXV.B’.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.
EXV.B (Circuit B EXV Configuration)
SUB-MODE
ITEM
STR.B
MIN.B
RNG.B
SPD.B
POF.B
MIN.B
MAX.B
OVR.AB
TYP.B
ITEM EXPANSION
EXV CIRC.B START POS
EXV CIRC.B MIN POSITION
EXVB STEPS IN RANGE
EXVB STEPS PER SECOND
EXVB FAIL POSITION IN %
EXVB MINIMUM STEPS
EXVB MAXIMUM STEPS
EXVB OVERRUN STEPS
EXVB STEPPER TYPE
DISPLAY
XXX
ENTRY
XXX
XXXXX
XXXXX
XXX
EXV.B
XXXXX
XXXXX
XXX
0,1
PRESS ESCAPE KEY TO DISPLAY ‘EXV.B’. PRESS DOWN ARROW KEY TO DISPLAY ‘MM’.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.
MM (Motormaster Configuration Settings)
SUB-MODE
MM
ITEM
MMR.S
P.GAN
I.GAN
D.GAN
MIN.S
ITEM EXPANSION
DISPLAY
YES/NO
XX
ENTRY
MOTORMASTER SELECT
HEAD PRESSURE P GAIN
HEAD PRESSURE I GAIN
HEAD PRESSURE D GAIN
MINIMUM FAN SPEED
XX.X
XX.X
XX
CL-7
Download from Www.Somanuals.com. All Manuals Search And Download.
III. Unit Start-Up (cont)
PRESS ESCAPE KEY TO DISPLAY ‘MM’. PRESS DOWN ARROW KEY TO DISPLAY ‘RSET’.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.
RSET (Reset Configuration Settings)
SUBMODE
ITEM
ITEM EXPANSION
RESET COOL TEMP
DISPLAY
ENTRY
RSET
CRST
MA.DG
RM.NO
RM.F
COOLING RESET TYPE
X
XX.X °F
XXX.X °F
XXX.X °F
XX.X °F
XXX.X °F
XXX.X °F
XX.X °F
X
4-20 - DEGREES RESET
REMOTE - NO RESET TEMP
REMOTE - FULL RESET TEMP
REMOTE - DEGREES RESET
RETURN - NO RESET TEMP
RETURN - FULL RESET TEMP
RETURN - DEGREES RESET
DEMAND LIMIT SELECT
DEMAND LIMIT AT 20 MA
LOADSHED GROUP NUMBER
LOADSHED DEMAND DELTA
MAXIMUM LOADSHED TIME
DEMAND LIMIT SWITCH 1
DEMAND LIMIT SWITCH 2
LEAD/LAG CHILLER ENABLE
MASTER/SLAVE SELECT
SLAVE ADDRESS
RM.DG
RT.NO
RT.F
RT.DG
DMDC
DM20
SHNM
SHDL
SHTM
DLS1
DLS2
LLEN
MSSL
SLVA
XXX %
XXX
XXX %
XXX
XXX %
XXX %
ENBL/DSBL
SLVE/MAST
XXX
LLBL
LEAD/LAG BALANCE SELECT
LEAD/LAG BALANCE DELTA
LAG START DELAY
X
LLBD
LLDY
XXX
XXX
PARA
PARALLEL CONFIGURATION
YES/NO
PRESS ESCAPE KEY TO DISPLAY ‘RSET’. PRESS DOWN ARROW KEY TO DISPLAY ‘SLCT’.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW:
SLCT (Setpoint and Ramp Load Configuration)
SUBMODE
ITEM
ITEM EXPANSION
SETPOINT AND RAMP LOAD
COOLING SETPOINT SELECT
RAMP LOAD SELECT
DISPLAY
ENTRY
SLCT
CLSP
RL.S
X
ENBL/DSBL
X.X
CRMP
SCHD
Z.GN
COOLING RAMP LOADING
SCHEDULE NUMBER
XX
DEADBAND MULTIPLIER
X.X
CL-8
Download from Www.Somanuals.com. All Manuals Search And Download.
III. Unit Start-Up (cont)
PRESS ESCAPE KEY SEVERAL TIMES TO GET TO THE MODE LEVEL (BLANK DISPLAY). USE THE
ARROW KEYS TO SCROLL TO THE SET POINT LED. PRESS ENTER TO DISPLAY SETPOINTS.
RECORD CONFIGURATION INFORMATION BELOW:
SETPOINT
SUBMODE
ITEM
ITEM EXPANSION
COOLING SETPOINTS
COOLING SETPOINT 1
COOLING SETPOINT 2
ICE SETPOINT
DISPLAY
ENTRY
COOL
CSP.1
CSP.2
CSP.3
XXX.X °F
XXX.X °F
XXX.X °F
HEAD PRESSURE SETPOINTS
HEAD SET POINT
H.DP
F.ON
XXX.X °F
XXX.X °F
XXX.X °F
XX.X °F
FAN ON SET POINT
HEAD
FRZ
F.OFF
B.OFF
F.DLT
FAN OFF SET POINT
BASE FAN OFF DELTA TEMP
FAN STAGE DELTA
XX.X °F
BRINE FREEZE SETPOINT
BRINE FREEZE POINT
BR.FZ
XXX.X °F
CL-9
Download from Www.Somanuals.com. All Manuals Search And Download.
III. Unit Start-Up (cont)
COMPONENT TEST
USE ESCAPE/ARROW KEYS TO ILLUMINATE CONFIGURATION LED. PRESS ENTER TO DISPLAY ‘DISP’.
PRESS ENTER AGAIN TO DISPLAY ‘TEST’ FOLLOWED BY ‘OFF’. PRESS ENTER TO STOP DISPLAY AT
‘OFF’ AND ENTER AGAIN SO ‘OFF’ DISPLAY FLASHES. ‘PASS’ AND ‘WORD’ WILL FLASH IF PASSWORD
NEEDS TO BE ENTERED. PRESS ENTER TO DISPLAY PASSWORD FIELD AND USE THE ENTER KEY FOR
EACH OF THE FOUR PASSWORD DIGITS. USE ARROW KEYS IF PASSWORD IS OTHER THAN STANDARD.
AT FLASHING ‘OFF’ DISPLAY, PRESS THE UP ARROW KEY TO DISPLAY ‘ON’ AND PRESS ENTER. ALL LED
SEGMENTS AND MODE LEDS WILL LIGHT UP. PRESS ESCAPE TO STOP THE TEST. PRESS ESCAPE TO
RETURN TO THE ‘DISP’ DISPLAY. PRESS THE ESCAPE KEY AGAIN AND USE THE ARROW KEYS TO ILLU-
MINATE THE SERVICE TEST LED. PRESS ENTER TO DISPLAY ‘TEST’. PRESS ENTER TO STOP DISPLAY
AT ‘OFF’ AND ENTER AGAIN SO ‘OFF’ FLASHES. PRESS THE UP ARROW KEY AND ENTER TO ENABLE
THE MANUAL MODE. PRESS ESCAPE AND DISPLAY NOW SAYS ‘TEST’ ‘ON’. REFER TO THE TABLE
BELOW.
Service Test Mode and Sub-Mode Directory
KEYPAD
ENTRY
ITEM
Completed
(Yes/No)
SUB-MODE
TEST
ITEM DISPLAY
COMMENT
EXPANSION
ON/OFF
SERVICE TEST MODE
To Enable Service Test Mode,
move Enable/Off/Remote
Contact switch to OFF. Change
TEST to ON. Move switch to
ENABLE.
ENTER
OUTPUTS AND PUMPS
FAN 1 RELAY
ENTER
FAN1
FAN2
FAN3
FAN4
FAN5
FAN6
V.HPA
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
XXX%
Condenser fan contactor 1
Condenser fan contactor 2
Condenser fan contactor 3
Condenser fan contactor 4
Condenser fan contactor 5
Condenser fan contactor 6
FAN 2 RELAY
FAN 3 RELAY
FAN 4 RELAY
FAN 5 RELAY
FAN 6 RELAY
VAR HEAD PRESS %
OUTS
VAR HEAD PRESS %
V.HPB
CLP.1
CLP.2
XXX%
ON/OFF
ON/OFF
COOLER PUMP 1 RELAY
COOLER PUMP 2 RELAY
COOLER/PUMP HEATER
REMOTE ALARM RELAY
CL.HT ON/OFF
RMT.A ON/OFF
CIRCUIT A COMPRESSOR TEST
COMPRESSOR A1 RELAY
ENTER
CC.A1 ON/OFF
UL.TM
0 to 15
COMP A1 UnLOAD TIME
COMPRESSOR A2 RELAY
COMPRESSOR A3 RELAY
COMPRESSOR A4 RELAY
MINIMUM LOAD VALVE RELAY
CC.A2 ON/OFF
CC.A3 ON/OFF
CC.A4 ON/OFF
CMPA
MLV
ON/OFF
CIRCUIT B COMPRESSOR TEST
COMPRESSOR B1 RELAY
ENTER
CC.B1 ON/OFF
CC.B2 ON/OFF
CC.B3 ON/OFF
CC.B4 ON/OFF
See Note
See Note
See Note
See Note
COMPRESSOR B2 RELAY
COMPRESSOR B3 RELAY
COMPRESSOR B4 RELAY
CMPB
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
Copyright 2010 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300067-01 Printed in U.S.A. Form 30RAP-2T Pg CL-10 12-10 Replaces: 30RAP-1T
Download from Www.Somanuals.com. All Manuals Search And Download.
|
Billy Goat Lawn Mower CR550HCV User Manual
Black Decker Iron BDCMTS User Manual
Black Decker Vacuum Cleaner 90521333 User Manual
Boss Audio Systems Stereo Amplifier CH550 User Manual
Brother Printer 5140 User Manual
Cannon Scanner MS 300 User Manual
Canon Fax Machine FAX L800 User Manual
Casio Watch MA0804 EC User Manual
Cavalry Storage Washer Dryer CAXR SERIES User Manual
Chevrolet Automobile 50061011 User Manual