with
CONTENTS
P a g e
Page
Restart Procedure . . . . . . . . . . . . . . . . . . . . . . . ...48
SAFETY CONSIDERATIONS . . . . . . . ,
. , . . , .
l
POWER FAILURE EXTERNAL TO THE UNIT
GENERAL . . . . . . , . . . . , . , . . . , . , . . . . , . , . . . . . . . . 2
Alarm Codes . . . . . . , . . . . . . . , . . . . . . . . . . , . . . . . 49
Compressor Alarm Circuit . . . . . . . . . . . . . . . . 50
Electronic Expansion Valve . . . . . . . . . . . . . . . . , . 56
MAJOR SYSTEM COMPONENTS . . . . . . . . . . . . 2-4
Processor Module . . . . . . . . . . . . . . . . . . . . . . . . ...2
Low-Voltage Relay Module . , . . . . . . , . , . , , . . . . . 2
Electronic Expansion Valve Module . . . . . . . . . . . 2
l
EXV OPERATION
l
CHECKOUT PROCEDURE
Options Module . . . . . . . . . . . . . . . .
. . . . . . . . . . . 2
Thermistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...60
Keypad and Display Module
LOCATION
(Also Called
or LID) . . . . . . . . . . . . . . . . . . 2
l
THERMISTOR REPLACEMENT
T2, T7, T8)
Control Switch . . . . , . . . . . . . . . . . . . . . . . . . . . . . . 2
Electronic Expansion Valve (EXV) . . . , . . . . . . . . 4
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...4
Compressor Protection Control
(Compressor and Cooler)
Pressure Transducers . . . , . . . , . . . . . . . . . . . . . 60
l
TROUBLESHOOTING
l
TRANSDUCER REPLACEMENT
Module (CPCS) . . , . . . . . . . . . . . . . . . . . . . . . . . . . 4
Control Modules . . . . . . . . . . . . . . . . . . . . . . . , . . . . 64
l
PROCESSOR MODULE (PSIO),
MODULE (SIO), LOW-VOLTAGE RELAY
MODULE (DSIO), AND EXV DRIVER MODULE
(DSIO)
OPERATION DATA . . . . . . . . . . . . . , . . . . , . . . . , 5-47
Capacity Control . . . . , , . . . . . . . . . . . . . . . . . . . . . . 5
Head Pressure Control . . . . . . . . . . . . . . . . . . . . 26
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...27
Keypad and Display Module
. RED LED
l
l
l
.
GREEN LED
28
(Also Called
or
PROCESSOR MODULE (PSIO)
LOW-VOLTAGE RELAY MODULE (DSIO)
MODULE (SIO)
ACCESSING FUNCTIONS
SUMMARY DISPLAY
KEYPAD OPERATING INSTRUCTIONS
STATUS FUNCTION
ACCESSORY UNLOADER INSTALLATION
68-7 1
. 68
TEST FUNCTION
Installation . . . . . . . , . . . . . . , . . . . . . . . . . . .
HISTORY FUNCTION
SET POINT FUNCTION
SERVICE FUNCTION
l
040-110, 130 (60 Hz) UNITS
(and associated modular units)
l
130 (50 Hz), 150-210, 225, 250, and 280 UNITS
(and associated modular units)
SCHEDULE FUNCTION
. . . . . . . . . . . . . . . . . . . . . .
TROUBLESHOOTING
48-67
48
48
FIELD WIRING . . . . . . . . . . . . , . . . . . . . . . . . . . . . 71-73
REPLACING DEFECTIVE PROCESSOR
. . . . . . . . . . . . . . . . . . . . .
Checking Display Codes
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Shutoff
MODULE (PSIO)
. . . . . . . . . . . . . . . . .
.
.
. . . . . . . . . . . . . . . . . . . . 48
Complete Unit Stoppage
Single Circuit Stoppage
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...73
. . . . . . . . . . . . . . . . . . . . . 48
Lag Compressor Stoppage . . . . . . . . . . . . . . . . . . 48
SAFETY
CONSIDERATIONS
Installing, starting up, and servicing this equipment can
be hazardous due to system pressures, electrical compo-
nents, and equipment location (roof, elevated structures, etc.).
Only trained, qualified installers and service mechanics should
install, start-up, and service this equipment.
Electrical shock can cause personal injury and death.
Shut off all power to this equipment during installation
and service. There may be more than one disconnect
switch. Tag all disconnect locations to alert others not
When working on this equipment, observe precautions in
the literature, and on tags, stickers, and labels attached to
the equipment, and any other safety precautions that apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use care in handling, rigging, and setting this equipment,
This unit uses a microprocessor-based electronic con-
trol system. Do not use jumpers or other tools to short
out components, or to bypass or otherwise depart from
recommended procedures. Any short-to-ground of the
control board or accompanying wiring may destroy the
electronic modules or electrical components.
and in handling
electrical components.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No.
Printed in S A.
Form
1 - 9 4
Replaces:
T ,
Bo2
T a b
P C 9 0 3
Download from Www.Somanuals.com. All Manuals Search And Download.
The
consists of
a
processor module
GENERAL
a low-voltage relay module (DSIO-LV),
2
an EXV
IMPORTANT: This publication contains controls, op-
driver module (DSIO-EXV), a 6-pack relay board, a key-
pad and display module (also called HSIO or LID), ther-
mistors, and transducers to provide inputs to the
microprocessor. An options module (SIO) is used to pro-
vide additional functions. This module is standard on 30GN
modules and is a field-installed accessory on the 30GT
tronic II units. See Fig. 1.
eration and troubleshooting data for
and
250, and 280
II chillers,
Circuits are identified as circuits
pressors are identified as Al, A2, etc. in circuit A,
B2, etc. in circuit B.
Use this guide in conjunction with separate Instal-
lation Instructions booklet packaged with the
A
and B, and com-
and
The
Series standard Flotronic II chillers feature
MAJOR SYSTEM COMPONENTS
microprocessor-based electronic controls and an electronic
expansion valve (EXV) in each refrigeration circuit.
Processor Module
This module contains the oper-
ating software and controls the operation of the machine. It
continuously monitors information received from the vari-
ous transducers and thermistors and communicates with the
NOTE: The
and 045 chillers with a
installed brine option have thermal expansion valves (TXV)
instead of the EXV.
relay modules and
relay board to increase or de-
Unit sizes 240,270, and 300-420 are modular units which
are shipped as separate sections (modules A and B). Instal-
lation instructions specific to these units are shipped inside
the individual modules. See Table for a listing of unit
crease the active stages of capacity. The processor module
also controls the EXV driver module, commanding it to open
or close each EXV in order to maintain the proper super-
heat entering the cylinders of each lead compressor. Infor-
mation is transmitted between the processor module and re-
lay module, the EXV driver module, and the keypad and
sizes and modular combinations. For modules
and
follow all general instructions as noted for unit sizes
For all remaining modules, follow instructions for unit
sizes 130-210.
display module through
a
3-wire communications bus. When
used, the options module is also connected to the commu-
nications bus.
Table 1
Unit Sizes and Modular Combinations
For the Flotronic II chillers, the processor monitors sys-
tem pressure by means of
6
transducers,
3
in each lead com-
UNIT MODEL
pressor. Compressor suction pressure, discharge pressure,
and oil pressure are sensed. If the processor senses high
discharge pressure or low suction pressure, it immediately
shuts down all compressors in the affected circuit. During
operation, if low oil pressure is sensed for longer than one
minute, all compressors in the affected circuit are shut down.
At start-up, the coil pressure signal is ignored for 2 min-
utes. If shutdown occurs due to any of these pressure faults,
the circuit is locked out and the appropriate fault code is
displayed.
30G
40
45
50
60
70
80
NO45
Low-Voltage Relay Module
This module closes
contacts to energize compressor unloaders and/or compres-
sors. It also senses the status of the safeties for all compres-
sors and transmits this information to the processor.
160
180
200
225
225
250
Electronic Expansion Valve Module
This mod-
I
I
ule receives signals from the processor and operates the elec-
tronic expansion valves.
Options Module
This module allows the use of
00
260
2 8 0
tronic II features such as dual set point, remote reset, de-
mand limit, hot gas bypass, and accessory unloaders. The
285
30
30GNf 70
options module also
activated from a remote 4-20
for reset and demand limit to be
325
350
380
400
signal. The options mod-
ule is installed at the factory on 040-210 and modular 240-
420 units. It is a field-installed accessory for 225, 250 and
280 units.
3 0 G N f
Hz units/50 Hz units.
Keypad and Display Module (also called
or LID)
This device consists of a keypad with 6 func-
tion keys, 5 operative keys, 12 numeric keys, and an al-
phanumeric g-character LCD. Key usage is explained in
Accessing Functions and Subfunctions section on page 28.
The Flotronic II control system cycles compressor un-
loaders and/or compressors to maintain the selected leaving
water temperature set point. It automatically positions the
EXV to maintain the specified refrigerant superheat enter-
ing the compressor cylinders. It also cycles condenser fans
on and off to maintain suitable head pressure for each cir-
cuit. Safeties are continuously monitored to prevent the unit
Control Switch
Control of the chiller is defined by
the position of the LOCAL/ENABLE-STOP-CCN switch.
This is a 3-position manual switch that allows the chiller to
be put under the control of its own Flotronic controls,
from operating under unsafe conditions.
A
scheduling func-
manually stopped, or put under the control of
a
Carrier Corn-
tion, programmed by the user, controls the unit occupied/
unoccupied schedule. The control also operates a test pro-
gram that allows the operator to check output signals and
ensure components are operable.
fort Network (CCN), Switch allows unit operation as shown
in Table 2.
2
Download from Www.Somanuals.com. All Manuals Search And Download.
In the LOCAL/ENABLE position, the chiller is under lo-
cal control and responds to the scheduling configuration and
set point data input at its own local interface device (key-
pad and display module).
Compressor Protection Control Module
Each compressor on models
(50 Hz), 080-
has its own CPCS as standard equip-
and 070 (60 Hz) units feature the
100, and
ment. All
CPCS as an accessory, and CR (control relay) as standard
In the CCN position, the chiller is under remote control
and responds only to CCN network commands. The occupied/
unoccupied conditions are defined by the network. All key-
pad and display functions can be read at the chiller regard-
less of position of the switch.
equipment. See Fig. 2. The
modular units and the
10 and associated
250, and 280 Flotronic II
units have a CR as standard equipment. The CPCS or CR is
used to control and protect the compressors and crankcase
heaters. The CPCS provides the following functions:
CCN run or stop condition is established by a command
from the CCN network. It is not possible to force outputs
from the CCN network, except that an emergency stop com-
mand shuts down the chiller immediately and causes
52” to be displayed.
compressor contactor control
crankcase heater control
compressor ground current protection
status communication to processor board
high-pressure protection
The CR provides all of the same functions as the CPCS
with the exception of compressor ground current protec-
tion. Ground current protection is accomplished by using a
CGF (compressor ground fault) board in conjunction with
the CR. The CGF provides the same ground fault function
as the CPCS for units where the CPCS is not utilized.
Table 2
LOCAL/ENABLE-STOP-CCN
Switch Positions and Operation
CONFIGURATION AND
S W I T C H
P O S I T I O N
U N I T
OPERATION
SET POINT CONTROL
Keypad Control CCN Control
STOP
LOCAL/ENABLE
Unit Cannot Run Read/Write
Read Only
Unit Can Run
Read/Limited Write Read
Unit Cannot Run Read Only
One large relay is located on the CPCS board. This relay
(or CR) controls the crankcase heater and compressor
contactor. The CPCS also provides a set of signal contacts
that the microprocessor monitors to determine the operating
status of the compressor. If the processor board determines
that the compressor is not operating properly through the
signal contacts, it will lock the compressor off by
gizing the proper 24-v control relay on the relay board. The
CPCS board contains logic that can detect if the
Read/Limited
Write
Unit Can Run
R e a d O n l v
Electronic Expansion Valve (EXV)
The micro-
processor controls the EXV through the EXV driver mod-
ule. Inside the expansion valve is a linear actuator stepper
motor.
The lead compressor in each circuit has a thermistor and
a pressure transducer located in the suction manifold after
the compressor motor. The thermistor measures the tem-
perature of the superheated gas entering the compressor cyl-
inders. The pressure transducer measures the refrigerant
pressure in the suction manifold. The microprocessor con-
verts the pressure reading to a saturated temperature. The
difference between the temperature of the superheated gas
and the saturation temperature is the superheat. The micro-
processor controls the position of the electronic expansion
valve stepper motor to maintain 29 F (16 C) superheat.
At initial unit start-up, the EXV position is at zero. After
that, the microprocessor keeps accurate track of the valve
position in order to use this information as input for the
other control functions. The control monitors the superheat
and the rate of change of superheat to control the position
of the valve. The valve stroke is very large, which results
in very accurate control of the superheat.
ground of any compressor winding exceeds 2.5 amps. If
this condition occurs, the CPCS module shuts down the
compressor.
A high-pressure switch with a trip pressure of 426
psig (2936 48
is wired in series with the CPCS.
If this switch opens during operation, the compressor stops
and the failure is detected by the processor when the signal
contacts open. The compressor is locked off. If the lead
compressor in either circuit is shut down by the high pres-
sure switch or ground current protector, all compressors in
the circuit are locked off.
The Flotronic
II chiller control system gath-
Sensors
ers information from sensors to control the operation of the
chiller. The units use 6 standard pressure transducers and
4
standard thermistors to monitor
pressures and tem-
peratures at various points within the chiller. Sensors are
listed in Table 3.
Table 3
Thermistor and Transducer Locations
THERMISTORS
Location
PROTECTION
BOARD
Sensor
Cooler Leaving Water Temp
Cooler Entering Water Temp
Fig. 2
Compressor Protection Control Module
Compressor Suction Gas Temp Circuit A
Compressor Suction Gas Temp Circuit B
Remote Temperature Sensor (Accessory)
Location
Sensor
D P T - A
S P T - A
O P T - A
Compressor Al Discharge Pressure
Compressor Al Suction-Pressure
Compressor Al Oil Pressure
Compressor Bl Discharge Pressure
S P T - B
O P T - B
Compressor
Compressor
Suction Pressure
Oil Pressure
4
Download from Www.Somanuals.com. All Manuals Search And Download.
ically reset by the return temperature reset or space and out-
OPERATION DATA
Capacity Control The control system cycles
door air temperature reset features. It can also be reset from
an external 4-20
network signal.
signal with a loop isolator, or from a
compressor to give capacity control steps as shown in
Tables The unit controls leaving chilled water tem-
The operating sequences shown are some of many pos-
sible loading sequences for the control of the leaving water
temperature. If a circuit has more unloaders than another,
that circuit will always be the lead circuit.
perature. Entering water temperature is used by the micro-
processor in determining the optimum time to add or sub-
tract steps of capacity, but is not a control set point.
The chilled water temperature set point can be automat-
Table 4A Capacity Control Steps, 040-070
LOADING SEQUENCE
LOADING SEQUENCE A
UNIT
3 0 G N
CONTROL
STEPS
%
%
Displacement
Compressors
Displacement
Compressors
A l *
Al
A l *
2 5
5 0
Bl*
2 5
,
Al
1 0 0
Al”
040 (60 Hz)
045 (60 Hz)
Al
1
2 4
040 (50 Hz)
A l &
Al
Al
*
4
5
Al
Al ,Bl
,
1 0 0
1
040 (50
5 3
4
,
1 0 0
A l *
Al
Al
1
045 (50 Hz)
4
Al
3 8
045 (50 Hz)
050 (60 Hz)
*
Al
Al
5
1 0 0
Al
045 (50 Hz)
045 (50 Hz)
5
1 0 0
1 8
Al
1
5 6
Al
Al
6
7
1 0 0
Al ,Bl
1
045 (50 Hz)
4
6 4
7
Al
*Unloaded compressor.
unloader, standard.
**Compressor unloader, accessory.
unloaders, both unloaded.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Capacity Control Steps, 040-070
Table 4A
LOADING SEQUENCE A
LOADING SEQUENCE B
UNIT
3 0 G N
Compressors
Displacement
Compressors
1 8
5 6
7 3
1
2 8
050 (50 Hz)
050 (50 Hz)
Al
B l *
A l %
Al
*
Al
Al
050 (50 Hz)
Al
050 (50 Hz)
6
1
1 5
1 8
1 0 0
Al
Al*
060 (50 Hz)
Al
*
6 6
8 3
1 0 0
Al
Al
Al
060 (50 Hz)
Al
060 (50 Hz)
,
8 3
1 0 0
*Unloaded compressor.
unloader, standard.
unloader, accessory.
unloaders, both unloaded.
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4A
Capacity Control Steps, 040-070
LOADING
S
B
LOADING SEQUENCE
A
%
30GN
Displacement
Displacement
Compressors
. .
1 6
060 (50 Hz)
8 3
1 0 0
1 0 0
6 5
Al
Al
Al
l
,A2,Bl
1 0 0
B l *
l
*
Al
Al
Al
Al
Al
Al
Al
,
Al
1 5
5 7
l
Al
Al
Al
Al
Al
Al
070 (50 Hz)
Al
*Unloaded compressor.
unloader, standard.
**Compressor unloader, accessory.
unloaders, both unloaded.
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4B
Capacity Control Steps, 080-110 and Associated Modular Units
LOADING SEQUENCE A
Compressors
LOADING SEQUENCE B
UNIT
3 0 G N
Displacement
Compressors
A l *
Al
Al
Al
Al
Al
Al
Al
1 0 0
Al”
Al
Al
Al
Al
Al
t t
080 (60 Hz)
Al
Al
Al
Al
Al
Al
A l *
*
Al
Al ,Bl
Al
,
Al
Al
Al
Al
*
Al
Al
t t
A l *
Al
Al
l
Al
t t
*
*
Al
080 (SO Hz)
Al
Al
Al
Al
*Unloaded compressor.
unloader, standard
**Compressor unloader, accessory
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4B
Capacity Control Steps, 080-110 and Associated Modular Units
A
LOADING
LOADING
UNIT
30GN
CONTROL
STEPS
%
%
Displacement
Compressors
Displacement
Compressors
*
Al
Al
Al
Al *,Bl
5 3
Al
Al
Al
l
,B2
Al
Al
Al
Al
Al
Al
9
1
Al
1 0 0
090 (60 Hz)
1
Al
Al
Al
Al
Al
Al
Al
Al
BP’
090 (60 Hz)
Al
Al
8 0
8 2
Al
Al
9
1
Al
A l *
*
Al
Al
Al
Al
Al
Al
Al
Al ,Bl
Al
Al
Al
Al
Al
Al
Al
l
Al
Al
Al
Al
Al
*Unloaded compressor.
unloader, standard.
**Compressor unloader, accessory
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4B
Capacity Control Steps, 080-110 and Associated Modular Units
LOADING
Displacement
LOADING SEQUENCE B
CONTROL
STEPS
UNIT
3 0 G N
Compressors
Displacement
Compressors
7
4 3
6 0
090 (50 Hz)
Al
Al
1 0 0
Al
Al
tt
090 (50 Hz)
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
A l *
*
Al
Al
Al
Al
100, 2408,
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Bl
Al
Al
Al
270B (60 Hz)
Al
Al
Al
Al
Al
Al
270B (60 Hz)
1 0
Al
Al
*Unloaded compressor
unloader, standard.
**Compressor unloader, accessory.
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing
1 0
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 40
Capacity Control Steps, 080-I
and Associated Modular Units
LOADING SEQUENCE A
LOADING EQUENCE B
UNIT
3 0 G N
%
Compressors
Displacement
Compressors
Displacement
8
8
A l *
Al
Al
Al
Al
Al
100, 2406,
270B (60 Hz)
Al
Al
Al
Al
Al
Al
Al
Al
Al
l
l
,BZ
100
1 0 0
A l %
Al
*
2 6
Al
100,
2708 (50 Hz)
Al
Al
Al
Al
Al
Al
.B2
1 0 0
Al
7
t t
A l *
100,
2708 (50 Hz)
9
Al
Al
Al
Al
1 4
Bl*
5
6
100, 2408,
270B (50 Hz)
Al
Al
Al
9
1 2
Al
Al
A l *
Al
Al
tt
100, 2408,
270B (50 Hz)
Al
Al
9
Al
Al
Al
Al
Al
l
,AZ,Bl
Al
1 6
*Unloaded compressor.
unloader, standard
**Compressor unloader, accessory.
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
1 1
Download from Www.Somanuals.com. All Manuals Search And Download.
Table
Capacity Control Steps, 080-110 and Associated Modular Units
LOADING SEQUENCE
A
LOADING SEQUENCE
B
UNIT
30GN
Displacement
Compressors
Displacement
Compressors
1 4
Al
Al
Al
Al
l
, A2, Bl*
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
tt
Al
Al
Al
Al
Al
Al
A l ”
Al
Al
t t
110 (60 Hz)
Al
Al
Al
Al
Al
Al
A-l
Al
Al
Al*
A l %
*
Al
Al
Al
110 (50 Hz)
Al
Al
l
,Bl
Al
l
,A2,Bl
Al ,Bl
Al
Al
Al
Al
Al
Al
Al
100
*Unloaded compressor.
unloader, standard
**Compressor unloader, accessory.
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4B
Capacity Control Steps, 080-110 and Associated Modular Units
LOADING
B
LOADING SEQUENCE A
Displacement Compressors
CONTROL
STEPS
UNIT
3 0 G N
%
Displacement
Compressors
110 (50 Hz)
Al
Al
Al
Al
110 (50 Hz)
Al
Al
Al
a
a
Al;; Bl
Al
Al
110 (50 Hz)
Al
Al
Al
Al
Al
Al
Al
Al
1 2
Al
*Unloaded compressor.
unloader, standard.
**Compressor
unloader,
accessory
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4C
Capacity Control Steps, 130-210 and Associated Modular Units
LOADING EQUENCE A
EQUENCE B
UNI T
30GN
%
%
Displacement
Compressors
Displacement
Compressors
Al
Al
Al
130,
Al lAl ,Bl
Al
,Bl l
,B2
Al
Al
Al
Al
Al
Al
Al
1 0 0
Al
100
Al
130,
Al
*
Al
Al
Al
Al
Al
Al
Al
130,
Al
Al
Al
Al
Al
Al
130,
tt
Al
Al
Al
Al
Al *,Bl
Al
Al
Al
Al
Al l ,A2,Bl
Al
Al
A l *
B l *
*
Al
Al ,Bl
Al
Al
Al
Al
Al
l
Al
Al ,Bl
Al
Al
Al
Al
Al
Al
Al
Al
Al
*Unloaded compressor
unloader, standard.
accessory
unloaders, both unloaded
**Compressor
NOTE: These capacity control steps may vary due to lag compressor sequencing+
1 4
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4C
Capacity Control Steps, 130-210 and Associated Modular Units
LOADING SEQUENCE B
LOADING SEQUENCE A
UNIT
3 0 G N
CONTROL
STEPS
Compressors
Displacement
Compressors
Displacement
6
Al
Al l
,Bl
Al
Al
130,
Al
Al
Al
Al
Al
Al
Al
Al *,Bl
Al ,Bl
Al
Al
Al
Al
Al
Al
Al
Al
*
All ,Bl
Al
Al
Al
Al ,Bl
Al
130,
Al
Al
Al
Al
Al
Al
Al
l
,B2
Al
Al
A l ’
Al
Al
*
Al *,Bl
Al
Al
Al
Al
Al
Al
Al
l
,A2,Bl
Al
Al
l
,B2
Al
l
,A2,Bl
l
,B2
Al
Al
Al
Al
Al l ,A2,A3,Bl
Al
Al
Al
Al
*Unloaded compressor.
unloader, standard.
**Compressor unloader, accessory
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
1 5
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4C
Capacity Control Steps, 130-210 and Associated Modular Units
LOADING EQUENCE A
LOADING EQUENCE
UNIT
3 0 G N
%
%
Displacement
Compressors
Displacement
Compressors
6
Al
Al
4 9
5 3
Al
Al
Al
Al
Al
Al
9 5
1 0 0
tt
*
Al
Al’, Bl
Al
Al
Al
Al
*
Al
Al
Al
Al
Al
Al
Al
Al
150 (60 Hz)
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
B l *
A l %
Al
Al
Al
Al ,Bl
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
t t
A l *
Al*,&
Al
Al
Al
Al
Al
Al
Al
*Unloaded compressor.
unloader, standard
**Compressor unloader, accessory.
unloaders, both unloaded
NOTE: These capacity control steps may vary due to lag compressor sequencing
1 6
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4C
Capacity Control Steps, 130-210 and Associated Modular Units
SEQUENCE B
Compressors
SEQUENCE A
Compressors
Displacement
150 (50 Hz)
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
150 (50 Hz)
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
A l *
A l %
Al
*
Al
Al
Al
Al
Al
Al
Al
Al
170,
Al
Al
l
,B2
Al
Al
Al
Al
,
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
170,
3008,
Al
Al
Al
Al
Al
Al
Al
Al
*Unloaded compressor.
unloader, standard.
**Compressor unloader, accessory
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
1 7
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4C
Capacity Control Steps, 130-210 and Associated Modular Units
LOADING SEQUENCE A
Displacement Compressors
LOADING SEQUENCE B
UNIT
SIZE
Compressors
Al ,Bl
170,
Al
Al
Al
Al
l
,B2
Al
Al
Al
Al
Al
Al
Al
l
,B2,B3
Al
6
t t
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
*
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Hz)
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
*Unloaded compressor.
unloader, standard.
**Compressor unloader, accessory.
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing
1 8
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4C
Capacity Control Steps, 130210 and Associated Modular Units
SEQUENCE B
Compressors
i SEQUENCE A
U N I T
CONTROL
STEPS
%
Compressors
Displacement
Displacement
1 9
Al
Al
3 7
Al
170,
Al
Al
Al
Al
Hz)
Al
7 2
Al
Al
Al
9 6
1 0 0
Al
Al
Al ,Bl
Al .Bl
170,
3008,
Hz)
Al
Al
,
Al
Al
Al
Al
Al
Al
Al
Al l
Al
,Bl
Al
Al
Al
*
Al
3008,
Al
Al
Al
Al
Al
,
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
81
Al
Al
Al
Al
Al
Al
Al
1 0 0
*Unloaded compressor.
unloader, standard
**Compressor unloader, accessory
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
1 9
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4C
Capacity Control Steps,
and Associated Modular Units
SEQUENCE B
Compressors
UNIT
SIZE
%
Compressors
Displacement
41
5 6
Al
Al
Al
Al
Al
Hz)
Al
Al
Al
Al
Al
Al
,
Al
Al
Al
Al
*
Al
Al
190,
,
Al
Al
Al
Al
Al
A l *
Al
Al
Al
l
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al l ,A2,A3,Bl
Al
l
,B2,B3
,B2,B3
Al
Al
Al
Al
l
Al
Al
Al
Al
,A2,A3,Bl*,B2,B3
l
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Hz)
,
A l *
Al
Al
l
,A2,A3,Bi
Al
Al
Al
*Unloaded compressor.
unloader, standard.
**Compressor unloader, accessory.
unloaders, both unloaded
NOTE: These capacity control steps may vary due to lag compressor sequencing
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4C
Capacity Control Steps, 130-210 and Associated Modular Units
SEQUENCE B
LOADING SEQUENCE A
Displacement Compressors
UNIT
SIZE
CONTROL
S T E P S
%
Displacement
Compressors
1
1
*
Al
5 0
61
Al
Al
,
Al
Al
a 3
9 4
Al
l
,82,83
Al
Al*
l
Al
l
Al
Al
,Bl
Al
Al
Al
Al
Al
Al
Al
,
Al
Al
Al
Al
Al
Al
AI
Al
Al
AI
At
t
1 4
Al
Al
Al
Al
Al
Al
Al
Hz)
Al
AI
Al
A l *
Al
Al
l
,A2,Bl
Al
210,
Al l ,A2,Bl
Al
,
Al l ,A2,A3,Bl
At
Al l ,A2,A3,61
Al
Al
Al
l
,A2,A3,A4,Bi
*
Al
210,
At
l
,B2
,B2,B3
Al
Al
l
Al
Al
Al
Al
Al
*Unloaded compressor.
j-Compressor unloader, standard.
**Compressor unloader, accessory.
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
2 1
Download from Www.Somanuals.com. All Manuals Search And Download.
Capacity Control Steps, 130-210 and Associated Modular Units
Table 4C
i SEQUENCE A
Compressors
LOADING SEQUENCE B
UNIT
SIZE
Displacement
Compressors
9
Bl*
*
Al
Al
Al
Al
Al
Al
Al ,Bl
Al
210,
Al
Al l ,A2,Bl
(60
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
210,
Hz)
,
Al”
Al
Al
Al
Al
Al
210,
,
Al
Al
Al
Al
*
Al
Al
Al
Al
Al
Al
210,
,
Al
Al
Al
Al
B l *
*
*
Al
Al
Al
Al
Al
Al
Al
Al l ,A2,Bl
Al l ,A2,Bl
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
*Unloaded compressor
unloader, standard
**Compressor unloader, accessory
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4D
Capacity Control Steps, 225, 250,280
LOAC
SEQUENCE A
LOADING SEQUENCE B
UNIT
30GT
%
Compressors
Compressors
Displacement
Displacement
1 2
1 2
4 6
Al
Al
Al
Al
Al
Al
Al
225 (60 Hz)
Al
Al
Al
Al
Al
Al
Al
Al
Al l ,A2,A3,Bl
Al
Al
Al
Al
Al
Al
A l *
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
l
,A2,A3,Bl
l
,B2,B3
Al
l
,A2,A3,Bl*,B2,B3
Al
Al
Al
Al
Al
Al
Al
Al
Al
At
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
225 (50 Hz)
Al
Al
Al
At
Al
Al
Al
Al
Al
Al
*Unloaded compressor.
unloader, standard.
**Compressor unloader, accessory
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4D
Capacity Control Steps, 225, 250,280
SEQUENCE
A
LOAC
SEQUENCE B
Compressors
Bl*
LOAC
UNIT
30GT
Compressors
*
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
2 2
3 2
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
250 (60 Hz)
A l *
Al
2 9
3 2
Al
Al
5 4
5 7
Al
Al
Al
Al
Al
Al
A l *
*
Al
l
Al
Al ,Bl
Al
Al
Al
Al ,Bl
Al
Al l ,A2,Bl
Al l ,A2,Bl
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
9 6
100
*Unloaded compressor.
standard
**Compressor unloader, accessory
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4D
Capacity Control Steps, 225, 250, 280
SEQUENCE A
LOADING SEQUENCE B
Compressors
UNIT
3 0 G T
CONTROL
S T E P S
Compressors
Al
Al
Al
Al
Al
Al
Al
250 (50 Hz)
280 (60 Hz)
Al
Al
Al
Al”
Al
Al
l
,A2,Bl
Al
Al
Al
Al**
Al
Al
Al
l
,A2,A3,A4,Bi
Al
A l *
*
Al
Al
Al
Al ,Bl
Al
l
,Bl*,B2
Al
Al
Al
Al
Al
Al
Al
Al l ,A2,Bl
Al
Al
Al
Al l ,A2,A3,Bl
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
Al
*Unloaded compressor.
-/-Compressor unloader, standard.
““Compressor unloader, accessory
unloaders, both unloaded
NOTE: These capacity control steps may
due to lag compressor sequencing
2 5
Download from Www.Somanuals.com. All Manuals Search And Download.
As the condensing temperature rises, the EXV closes to
maintain the proper suction superheat. Once the EXV has
closed to 39.5% open (300 steps open), a fan stage is added
after 2 minutes.
During start-up, all the condenser fans are started when
the condensing temperature reaches 95 F (35 C) to prevent
excessive discharge pressure during pulldown. See Table 5
for condenser fan sequence of operation.
Head Pressure Control
The microprocessor con-
trols the condenser fans in order to maintain the lowest con-
densing temperature possible, thus the highest unit efficiency.
Instead of using the conventional head pressure control meth-
ods, the fans are controlled by the position of the EXV and
suction superheat.
As the condensing temperature drops, the EXV opens to
maintain the proper suction superheat. Once the EXV is
fully open, if the condensing temperature continues to drop,
the suction superheat begins to rise. Once the suction super-
heat is greater than 40 F (22.2 C), a fan stage is removed
after 2 minutes,
Table 5
Condenser Fan Sequence
FAN CONTACTOR
CONTROLLED BY
FAN ARRANGEMENT
FAN NUMBER(S)
FC-Al
Compressor Al
Compressor
I
2
3
First Stage
Microprocessor
FC-A2
Second
Stage
4
Compressor Al
Compressor
FC-Al
FC-Al
I
First Stage
Microprocessor
Second
Stage
Microprocessor
Compressor Al
Compressor
1
Compressor Al
Compressor
FC-Al
F C - 8 1
F C - A 2
(and associated modular units)
2
3
First Stage
4
Microprocessor
5, 7,
FC-AS,
Second
Compressor
Stage
3, 4, 5, 6, 7,
FC-A3
FC-B3
,
Third Stage
Microprocessor
FC-Al
Compressor Al
Compressor
(and associated modular units)
7
FC-Bl
FC-A2, FC-A3
FC-Al
Compressor Al
(and associated modular units)
7
I
I
I
6 .
8
I
FC-A2
FC-B2
3,
Frist Stage
Microprocessor
4,
1
,
3, 9, 11
FC-A2,
Second
Stage
2, 4 , 10, 1 2
Microprocessor
*Control box.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 5
Condenser Fan Sequence
FAN NUMBER(S)
CONTROLLED BY
FAN ARRANGEMENT
7,
FC-1
Compressor Al
Compressor
9, 1 0
FC-4
FC-2
FC-5
First Stage
Microprocessor
11, 1 2
2, 3 ,
4
FC-3
FC-6
Second
Microprocessor
Stage
13, 14, 15, 16
2, 3, 4,
11, 12,
6
FC-2, FC-3
FC-5, FC-6
Third Stage
Microprocessor
14, 15, 1 6
7, 8,
FC-1
Compressor
Compressor
(60 Hz)
Al
9, 17, 1 8
FC-4
6
FC-2
FC-5
First Stage
Microprocessor
11, 12, 19
2, 3, 4,
14, 15, 16, 20
Second
Microprocessor
Stage
FC-3, FC-6, FC-7
1
,
2, 3, 4, 5, 6, 11, 12, 13,
Third Stage
14, 15, 16,
19, 2 0
7, 8, 1 0
9,
Microprocessor
FC-1
(50 Hz) AND
Compressor Al
Compressor
17, 1 8
FC-4
FC-2
FC-5
First Stage
Microprocessor
II, 12,
2, 3, 4, 13,
14, 15, 16, 21, 22
Second
Stage
FC-3, FC-6, FC-7
Microprocessor
1, 2, 3, 4, 5, 6, 11, 12, 13,
14, 15, 16, 19, 20, 21, 2 2
FC-2, FC-3, FC-4,
FC-5, FC-6, FC-7
Third Stage
Microprocessor
*Control box.
box.
saturated suction temperature is below -15 F (-26 C). At
this point, the EXV starts to open and continues to open
gradually to provide a controlled start-up to prevent liquid
flood-back to the compressor.
When the lead compressor in each circuit
is started or stopped, that circuit goes through a
cycle to purge the cooler and refrigerant suction lines of
refrigerant.
At shutdown, the
urated suction temperature for that circuit is 10” F (5.5” C)
below the saturated suction temperature when is
initiated, or saturated suction temperature reaches -15 F
(-26 C). At that point, the compressor shuts down and the
EXV continues to move until fully closed.
cycle continues until the sat-
The
cycle starts immediately upon starting the
lead compressor and continues until the saturated suction
temperature is 10” F (5.5” C) below the saturated suction
temperature at start-up, is
F (5.5” C) below the cooler
leaving fluid temperature, or reaches
a
saturated suction tem-
is necessary if the
perature of -15 F (-26 C). No
27
Download from Www.Somanuals.com. All Manuals Search And Download.
The default display is displayed every 2 seconds if there
has been no manual input from the keypad for 10 minutes.
Keypad and Display Module (Also Called
The only function of this module is to allow
the operator to communicate with the processor. It is used
to enter configurations and set points and to read data, per-
or LID)
To return to automatic display, enter a t a n y t i m e .
form tests, and set schedules. This device consists of
a
key-
Table 6
Keypad and Display Module Usage
pad with 6 function keys, 5 operative keys, 12 numeric keys
(0 to 9, and -), and an alphanumeric g-character LCD
FUNCTION
K E Y S
USE
(liquid crystal display). See
key usage.
3. See Table 6 for
STATUS
For displaying diagnostic codes and
STAT
current operating information about the machine.
HISTORY
previous alarms.
SERVICE
tion information.
For displaying run time, cycles and
q
For entering specific unit configura-
TEST
proper
For checking inputs and outputs for
operation.
EST
El
SCHEDULE
schedules for unit operation
For entering occupied/unoccupied
ACCESSING FUNCTIONS AND SUBFUNCTIONS
See
Tables 6 8. Table 7 shows the 6 functions (identified by
name) and the subfunctions (identified by number).
SET POINT
For entering operating set points
S E T
q
and day/time information.
OPERATIVE
USE
For displaying a non-abbreviated ex-
K E Y S
EXPAND
pansion of the display
CLEAR
For clearing the screen of all displays
UP ARROW
position,
DOWN ARROW
position.
For returning to previous display
c
c
l
l
For advancing to next display
ENTER
For entering data
q
KEYPAD OPERATING INSTRUCTIONS (Refer to
Table 9.)
White keys on left side of keypad are shown and oper-
ample: keypad entry means press the
the white key marked
2. The standard display uses abbreviations. Expanded in-
ated in these instructions according to thqe following ex-
, then
.
formation scrolls through the display whenever
is pressed.
q
key
Fig. 3
Keypad and Display Module
3. All functions are made up of a group of subfunctions.
To enter a subfunction, first press subfunction number
desired. Then press the function key in which the sub-
function resides. To move within that subfunction, press
SUMMARY DISPLAY
When keypad has not been used
for 10 minutes, display automatically switches to the rotat-
ing summary display. This display has 4 parts, listed be-
low, which appear in continuous rotating sequence.
the
q
or
arrow. For example, a
the Temperature Information subfunction.
enters
4. At any time, another subfunction may be entered by en-
tering the subfunction number, then the function key.
DISPLAY
TUE
EXPANSION
TODAY IS TUE, TIME IS
PM)
5. Prior to starting unit, check leaving fluid set point for
correct setting. Refer to Set Point Function section on
page 39.
CLOCK ON
UNIT IS ON
CLOCK SCHEDULE
C O O L
1
NUMBER OF STAGES IS 1
ALARMS DETECTED
2
ALARMS
2
6. Depending on system configuration, all displays may not
be shown. All displays are shown unless marked with
the following symbol.
AUTOMATIC DISPLAY OPERATION/DEFAULT DIS-
PLAY In this mode, the keypad displays the current time
format), current operating modes, cooling capac-
ity stages, and total number of alarms.
*Must be configured.
For additional unit start-up procedures, see separate In-
stallation, Start-Up and Service Instructions supplied with
unit.
COOL x
MODE
X
Day of Week
Hour(s)
Minute(s)
DOW
2 8
Download from Www.Somanuals.com. All Manuals Search And Download.
Functions and Subfunctions
Table
FUNCTIONS
Status
Schedule
Service
History
Set Point
Test
TESTl
S
E
T
C
H
D
c
l
c
l
c
Run Time
Set Points
(Chiller Fluid)
Automatic
outputs
Override
Clock Set
Period
Log On and
Log Off
Display
2
3
4
5
Alarm
Display
Compressors
and Unloaders
Version
(Software)
Starts
Reset
Set Points
Factory
Configuration
Alarm
History
Demand
Limit
Set Points
P e r i o d
P e r i o d
2
3
Field
Configuration
Date and
Time
Set Points
(Current Operating)
Service
Configuration
Period
Period
Period
Period
P e r i o d
4
5
6
7
6
Temperatures
Pressures
Analog
7
Inputs
9
1 0
outputs
8
HOLIDAYS
Table 8
Accessing Functions and Subfunctions
KEYPAD
ENTRY
DISPLAY
RESPONSE
DESCRIPTION
OPERATION
I
I
To access a function, press
subfunction no and function
name key. Display shows
function
R E S E T
Reset Set Points
Cooling
Reset
Maximum
Maximum
To move to other elements,
scroll up or down using arrow
keys. NOTE: These
displays do not show if
control is not configured
for reset.
Cooling
Reference xx
c
l
l
Cooling
Reference xx
Minimum
xx
Cooling
Reference xx
Minimum
When the last element in a
subfunction has been
played, the first element is
repeated.
R E S E T
Reset Set
c
c
l
To move to next subfunction
it is not necessary to use
subfunction number Press
function name key to
display through all
DEMAND
D e m a n d S e t
Points
c
SETl
SET l
T I M E
Current Time and
Day of Week
c
subfunctions within a
function and then back
to the first
SET
S E T
Unit Set Points
To move to another function,
either depress function name
key for desired function
(display shows the first
subfunction),
X ALARMS
Rotating Display
Access
ic sub-
function by’using the sub-
function number and the
function name kev.
Capacity Stages
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 9
Keypad Directory
STATUS
DISPLAY
COMMENT
KEYPAD ENTRY
Refer to Automatic Display Operation on page 28
Number of Tripped Alarms
X
A L A R M S
2 ALARMS
ALARM X
ALARM X
ALARM X
ALARM X
ALARM X
Displays Tripped Alarms
Number of Modes in Effect
X MODES
MODE X
MODE X
MODE X
MODE X
3 MODES
Displays Mode in Effect
S T A G E
Capacity
Staging
Information
4 STAGE
Number of Requested Stages
Percent of Total Capacity
Percent Circuit A Capacity
Percent Circuit Capacity
Demand Limit Set Point
S T A G E
C A P T
X
X
X
CAP0 X
L M T X *
LOAD X*
Load Limit Set Point
X
X
Circuit A Compressor Relay Status
Circuit B Compressor Relay Status
S M Z
X
Load/Unload Factor for Compressors
Factor = 1 Unloader Factor = 0 6
S E T P O I N T
Fluid Set Point Information
Set Point
5
SET POINT
x
Modified Set Point = Set Point
Reset
M S P
X
TWX
Cooler Leaving Fluid Temperature
T E M P S
Temperature
Information
6
TEMPERATURE
EWTX
Cooler Entering Fluid Temperature
Cooler Leaving Fluid Temperature
Circuit A Saturated Condenser Temperature
Circuit A Saturated Suction Temperature
Compressor Al Suction Temperature
Circuit A Suction Superheat
L W T
X
S C T A
S S T A
CTA X
SHA X
X
X
LEGEND
*Must be configured
applicable
Carrier Comfort Network
Electronic Expansion Valve
Maximum Operating Pressure
CCN
E X V
M O P
3 0
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 9
Keypad Directory
STATUS
SUBFUNCTION
TEMPERATURE
KEYPADENTRY
cl
DISPLAY
COMMENT
Circuit B Saturated Condenser Temperature
6
SCTB X
Circuit
B
Saturated Suction Temperature
S S T B
X
q
Compressor
Suction Temperature
cl
C T B
X
cl
SHB X
Circuit
B
Suction Superheat
RST X*
Reset Temperature
PRESSURE
Refrigerant System Pressure (psig)
Circuit A Discharge Pressure
Circuit A Suction Pressure
7
PRESSURE
D P A
S P A
X
X
Circuit A Discharge/Suction
Circuit A Oil Pressure Differential
Circuit B Discharge Pressure
x x x x
OPA X
DPB X
S P B
X
Circuit
Suction Pressure
Circuit B Discharge/Suction
x x x x
O P B
X
Circuit B Oil Pressure Differential
8 ANALOG
ANALOG
REF X
L M T X *
RST X*
I N P U T
x*
Status of Analog Inputs
Transducer Supply Voltage
Demand 4-20
Signal
Reset 4-20
Signal
9
Status of Switch Inputs
Dual Set Point Switch
Demand Limit Switch
Demand Limit Switch
1
DL2 X*
2
3 1
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 9
Keypad Directory
STATUS
SUBFUNCTION
10 OUTPUTS
DISPLAY
COMMENT
OUTPUTS
ALMR X
X
Status of Outputs
Alarm Relay K3
Fan Relay
FRA2 X
X
Fan Relay K2
Fan Relay K4
Fan Relay K5
FRB2 X
CHWP X*
X
Cooler Water Pump Relay K6
Unloader Al
ULA2 X*
X
Unloader
Unloader
ULB2 X*
Unloader
E X V A
E X V B
X
EXVA Percent Open
EXVB Percent Open
Hot Gas Bypass Relay Circuit A
Hot Gas Bypass Relay Circuit B
A Output Percent
X
X*
HGBB X
M M A X *
MMB X
Motormaster B Output Percent
TEST
To use Test function, LOCAL/ENABLE-STOP-CCN switch must be in STOP position To operate a test, scroll to desired test
Then, press to start test. Press to stop test.
KEYPAD ENTRY
COMMENT
SUBFUNCTION
OUTPUTS
DISPLAY
OUTPUTS
Test Outputs
8
8
8.8.8 8.8.8
Display Check
ALMR X
X
Energize Alarm Relay K3
Energize Fan Relay Al
Energize Fan Relay A2 K2
FRA2 X
X
Energize Fan Relay
Energize Fan Relay
K4
K5
X
CHWP X*
EXVA X
Energize Cooler Water Pump K6
Enter Desired EXVA Position
E X V B
X
Enter Desired
Position
HGBRA X*
HGBRB X*
M M A X *
Energize Hot Gas Bypass Relay A
Energize Hot Gas
Enter Desired
Relay B
A Output Signal
M M B X *
Enter Desired Motormaster B Output Signal
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Keypad Directory
TEST
Table 9
During compressor test, compressors start and run for
10 seconds. Compressor service valves and liquid line
valves must be open. Energize crankcase heaters 24 hours
prior to performing compressor tests.
KEYPAD ENTRY
DISPLAY
COMMENT
SUBFUNCTION
2 COMPRESSORS AND
UNLOADERS
C O M P
Compressor and Unloader Test
Test Compressor Al
Test Compressor
Test Compressor
CPA1 X
CPA2 X*
CPA3 X*
CPA4 X*
Test Compressor
Test Compressor
Test Compressor
Test Compressor
X
x*
CPB3 X*
CPB4 X*
Test Compressor
X
ULA2 X*
Energize Unloader Al
Energize Unloader
Energize Unloader
Energize Unloader
X
ULB2 X*
SCHEDULE
The Schedule function key
is used to configure the occupancy schedule The clock select subfunction can be used for
unoccupied shutdown or unoccupied setback depending on the cooling set point control configuration. The Schedule function
described is for clock
SUBFUNCTION
1 OVERRIDE
which is the internal clock. Password required for all subfunctions except override.
DISPLAY
OVRD X
COMMENT
1
KEYPAD ENTRY
I
I
Number of Override Hrs (0 4 Hrs)
For example, to extend current occupied mode for 3 hrs, press:
OVRD 3
Extended Occupied Time
2 CLOCK SELECT
CLOCK XX
Type of Clock Control
0 = No Clock, 1 = Clock 1 (Internal)
LEGEND
*Must be configured
applicable.
Carrier Comfort Network
Electronic Expansion Valve
Maximum Operating Pressure
M O P
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Keypad Directory
SCHEDULE
Table 9
DISPLAY
COMMENT
Period Time Schedule
PERIOD
OCC
Occupied
Time
Time
Unoccupied
MON X
M o n d a y F l a g
Tuesday Flag
T U E
X
WED x
THU X
X
Wednesday Flag
Thursday Flag
Friday Flag
S A T
X
Saturday
Sunday
Flag
Flag
SUN X
HOL X
Holiday Flag
To toggle between inputs (Yes/No) Press:
4 PERIOD 2
P
e
r
r
i
o
d PER2IODT2 i
m
e
S
c
h
e
d
u
l
e
5 PERIOD 3 . . . 9 PERIOD 7
P e r i o. d
3
.
e r i o d
7
T i m e S c h e d u l e
P
e
i
o
dPER8IODT8 i
m
e
S
c
h
e
d
u
l
e
10 PERIOD 8
11 HOLIDAYS
HOLIDAYS
DAT
Define Calendar Holidays
Holiday Date
1
New = Unassigned Holiday Date
DAT
NN
Holiday Date 30
For example: To enter July 4th holiday press: 07 04 01
q
.
Display shows Jul 04 For further information on the Schedule function and its
operation, refer to Schedule Function section on page 45.
SERVICE
To view and modify configurations, the password must be entered under the log on subfunction.
KEYPAD ENTRY
DISPLAY
COMMENT
SUBFUNCTION
L O G O N
Enter Password/Disable Password Protection
1 LOG ON AND LOG OFF
(LOGGEDON
log out as follows:
At this time, configurations may be modified. When finished viewing and/or modifying
LOG OFF
Disable Password Protection
E X I T L O G
Logged Off/Enable Password Protection
VERSION
x x x x x x x x
X
Software
Information
2 VERSION
Version No. of Software (CESRXX)
c
l
Language
Options
See legend on page 30
3 4
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 9
Keypad Directory
SERVICE
The next 3 subfunctions provide the ability to modify configurations Refer to separate Installation, Start-Up, and Service Instructions
supplied with unit for further information
on changing configurations.
To change a configuration, enter the new configuration and press
while on the correct configuration.
DISPLAY
COMMENT
KEYPAD ENTRY
3 FACTORY
FACT CFG
Factory Configuration Codes
CONFIGURATION
x x x x x x x x
x x x x x x x x
x x x x x x x x
x x x x x x x x
x x x x x x x x
x x x x x x x x
Configuration Code
Configuration Code
Configuration Code
Configuration Code
Configuration Code
Configuration Code
1
2
3
4
5
6
t
4 FIELD
Adjustable Field Configuration
FLD CFG
X
CONFIGURATION
CCN Element Address
CCN Bus Number
B U S
X
BAUD X
FLUID X
UNITS X
LANG X
NULA X
NULB X
HGB X
CCN Baud Rate
Cooler Fluid Select
t
t
Display Unit Select
Display Language Select
No Circuit A Unloaders
No. Circuit B Unloaders
Hot Gas Bypass Select
Loading Sequence Select
t
t
t
cl
S E Q T
X
t
SEQF X
x
Lead/Lag
Sequence
Select
t
q
Oil Pressure Switch Select
Head Pressure Control Method
Select
t
HEADM X
t
a
M M
X
t
CSPTYP X
CRTYP X
Cooling Set Point Control Select
Cooling Reset Control Select
External Reset Sensor Select
Demand Limit Control Select
Ramp Load Select
t
cl
t
cl
t
E R T Y P
L S T Y P
X
X
q
t
RAMP X
LOCK X
x
cl
Cooler Pump Interlock Select
Cooler Pump Control Select
5 SERVICE
Service Configurations
SRV CFG
CONFIGURATION
x x x x x x x x
x x x x x x x x
X
Configuration Code
Configuration Code
Refrigerant
7
8
cl
t
Pressure Transducer Select
Oil Transducer Set Point
Low Pressure Set Point
Fan Staging Select
t
T D T Y P
x
X
cl
t
cl
LPS x
t
cl
FANTYP X
SH X
cl
q
cl
EXV Superheat Set Point
EXV MOP Set Point
M O P
X
3 5
Download from Www.Somanuals.com. All Manuals Search And Download.
Keypad Directory
Table 9
DISPLAY
COMMENT
KEYPAD ENTRY
SUBFUNCTION
1 RUN TIME
RUN TIME
HR X
Run Time lnformation
Total Hrs Unit Has a Comp Operating
HRA X
HRB X
Circuit
Circuit
A
B
Run Time
Run Time
c
l
Starts
Information
S T A R T S
x
2
STARTS
Cycles from Stage 0 to Stage
Circuit A Starts
c
c
c
l
l
l
CYA X
CYB X
Circuit B Starts
Last 5 Alarms
3 ALARM HISTORY
I
I
I
ALARM X
ALARM X
ALARM X
ALARM X
ALARM X
Alarm Description
J
SET POINT
c h a n g e
value, t h e n
press
a set point, enter new set point
To read a set point, go to proper subfunction and read desired set point To
LOCAL/ENABLE-STOP-CCN switch must be in LOCAL or STOP position,
COMMENT
DISPLAY
SUBFUNCTION
1 SET POINTS
KEYPAD ENTRY
POINT
Jnit Set Point
x
x
Chiller Fluid Set Point
Fluid Set Point
1
2
H S P A
H S P B
X
X
Head
Pressure Set Point Circuit
A
Head Pressure Set Point Circuit B
Limit
CRAMP X
R E S E T
CRST2 X*
CREF2 X*
X*
Reset Set Points
2 RESET SET POINTS
Cooling Max Reset
Max Reset Occurs at X
Cooling Minimum Reset
Min Reset Occurs at X
or Degree
X*
or Degree
DEMAND
X*
Demand Set Points
3 DEMAND SET POINTS
Demand Switch
1
Set Point
DLS2 X*
DMAX X*
RMAX X*
X*
Demand Switch 2 Set Point
4-20
Maximum Demand Limit
Max Demand Limit Occurs at X
4-20
Minimum Demand Limit
Minimum Demand Limit Occurs at X
X*
SHED
CCN
Amount
Date, Time and Day of Week
4 DATE AND TIME
DAY
Day 1 = Mon, 2 = Tues
Hours are displayed in
7
=
Sun
time. Decimal point serves as colon.
MM.DD YR
When entering date, enter a decimal
point between entries. Each entry must be two numbers.
36
Download from Www.Somanuals.com. All Manuals Search And Download.
STATUS FUNCTION This function shows the rotating
display, current status of alarm (diagnostic) codes, capacity
stages, operating modes, chilled water set point, all meas-
ured system temperatures and pressures, superheat values,
pressure switch positions, analog inputs, and switch inputs.
These subfunctions are defined on pages 37 and 38.
Table 10
Operationat and Mode Display Codes
The operating modes are displayed by name or code num-
ber, to indicate the operating status of the unit at a given
time. The modes are:
CODE
Unit is off. LOCAL/ENABLE-STOP-CCN switch is
( R o t a t i n g D i s p l a y )
in OFF position, or LOCAL/ENABLE-STOP-CCN
LOCAL OFF
switch may be in LOCAL position with external ON/
OFF switch in OFF position
(Alarms)
Alarms are messages that one or more
Unit is off due to CCN network command. LOCAL/
CCN OFF
faults have been detected. Each fault is assigned
a
code num-
ENABLE-STOP-CCN switch is in CCN position.
ber which is reported with the alarm. See Table 10 for code
definitions. The codes indicate failures that cause the unit
to shut down, terminate an option (such as reset) or result
in the use of a default value as set point.
Unit is off due to internal clock schedule. LOCAL/
CLOCK OFF
ENABLE-STOP-CCN switch is in LOCAL position.
Unit is on. LOCAL/ENABLE-STOP-CCN switch is
in LOCAL position If external ON/OFF switch is used,
it will be in ON bosition.
LOCAL ON
CCN ON
Up to 5 alarm codes can be stored at once. To view them
to enter the alarm displays
Unit is on due CCN command
STOP-CCN switch is in CCN position.
in sequence, pqress
to move to the individual alarm dis-
Unit is on due to internal clock schedule or
CLOCK ON pied override function.
CCN switch is in LOCAL position.
plays. Press
and then prqess
after
a
code has been displayed. The mean-
Dual set point is in effect In this mode, unit contin-
ues to run in unoccupied condition, but leaving wa-
ter set point is automatically increased to a higher
ing of the code scrolls across the screen. See Example
M O D E
7
level
set
is in SET function)
Example 1
Reading Alarm Codes
Temperature reset is in effect. In this mode, unit is
using temperature reset to adjust leaving water set
point upward, and unit is currently controlling to the
modified set point. The set point can be modified
based on return water, outdoor-air temperature or
space temperature
K E Y P A D
ENTRY
DISPLAY
RESPONSE
MODE 8
COMMENTS
Keypad has not been used for
at least 10 minutes. Alternating
summary display appears on
screen
Demand limit is in effect. This indicates that ca-
pacity of unit is being limited by demand limit con-
trol option Because of this limitation, unit may
not be able to produce the desired leaving water
temperature
0
S T A G E S
2 ALARMS
MODE 9
2
alarms detected
2
A L A R M S
Load limit is in effect. This indicates that capacity of
a system of units is being limited by a CCN
shed command Due to this limitation, unit may
not be able to produce the desired leaving water
temperature.
A L A R M
9
First alarm code
MODE 10
MODE II
COOLER LEAVING
FLUID THERMISTOR Explanation of alarm code
F A I L U R E
Not
Second alarm code Cooler
A L A R M 4 2
freeze
protection
Ramp load (pulldown) limiting is in effect. In this mode,
the
at
leaving water temperature is dropped
COOLER FREEZE
P R O T E C T I O N
Explanation of alarm code
is limited to
a
predetermined value to prevent com-
MODE 12
MODE 13
pressor overloading, See CRAMP set point in the
SET function in Table
modified, if desired, to any rate from 2 F to 2 F
to
9
The
limit can be
When a diagnostic (alarm) code is stored in the display
and the machine automatically resets, the code is deleted.
Codes for safeties which do not automatically reset are not
deleted until the problem is corrected and the machine is
switched to STOP, then back to LOCAL/ENABLE or CCN.
Timed override is in effect This is a 1 to 4 hour
temporary override of the programmed schedule,
forcing unit to occupied mode Override can be im-
plemented with unit under LOCAL or CCN control
Override expires after each use
Low cooler suction protection is in effect In this mode,
circuit capacity is not allowed to increase if cooler
(Modes)
The operating mode codes are dis-
saturated suction temperature is
F
C) for
played to indicate the operating status of the unit at a given
time. See Table 10.
water or 30”
F
(16” C) for brine or more below leav-
MODE 14
ing fluid temperature, and saturated suction tem-
perature is less than 32 F C). If these conditions
persist beyond 10 minutes, circuit is shut down and
fault code 44 or 45 is displayed.
CCN
CarrierComfort Network
To enter the MODES subfunction, depress
and
use the
q
key to determine if more than one mode ap-
plies. See Example 2 to read current mode with expansion.
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Reading Current Operating Modes
Example 2
(Analog Inputs)
analog inputs, if any. Enter
transducer supply voltage, 4-20
This subfunction displays
KEYPAD
ENTRY
DISPLAY
RESPONSE
, then use the
reset signal can be dis-
q
. The
COMMENTS
I
I
Keypad has not been used for at
least 10 minutes Rotating summary
display appears on screen
TUE
played. This is useful for problem diagnosis prior to using
LOCAL ON
the test function.
C O O L
1
0
A L A R M S
( I n p u t s )
This subfunction displays status
There are 2 modes currently in effect
Unit is on by chiller on/off switch
Temperature reset is in effect
2 MODES
(ON/OFF) of input switch where applicable. Status of dual
set point switch, and demand limit switches 1 and 2 can be
displayed. This is useful for problem diagnosis prior to us-
ing the test function.
LOCAL ON
c
c
l
l
M O D E
8
(Outputs)
This function displays ON/OFF sta-
tus of alarm relay, all fan relays, and chilled water pump
relay. It also displays ON/OFF status of compressor unload-
ers (if used). The position of each EXV (in percent open)
can be displayed.
This subfunction displays the capac-
ity stage number. See Tables for compressor load-
(Stage)
and use the
ing sequence. To enqter the STAGE subfunction, press
to display the stage number.
TEST FUNCTION The test function operates the diag-
nostic program. To initiate test function, the LOCAL/
ENABLE-STOP-CCN switch must be in STOP position.
Additional provides the following information:
Percent of total unit capacity being utilized.
Percent of each circuit capacity being utilized.
Demand limit set point in effect (can be any value be-
tween 0% and 100%).
To reach a particular test, enter its subfunction number,
then scroll to desired test by pressing the
key. Press
to terminate or
to start a test. Press
test. Pressing the
q
or
q
or
a
Load limit set point in effect. This is a CCN function for
controlling operation of multiple units between 0% and
100% of total capacity of all units combined.
exit
a
q
key after
test has started ad-
vances system to next test, whether current test is operating
or has timed out, Once in the next step, you may start
Status of each compressor relay. When a compressor is
on, the number of that compressor is displayed. If a com-
pressor is off, a 0 is displayed. For example: In a given
circuit, if compressors 1 and 3 are running, and 2 and 4
are not running, 0301 is displayed for that circuit.
test by pressing
or advance past it by pressing
.
While the unit is in test, you may leave test function and
access another display or function by pressing appropriate
keys. However, a component that is operating when an-
other function is accessed remains operating. You must
Load/Unload factor for compressors. This factor is an in-
dication of when a step of capacity is added or sub-
tracted. Its value can range from slightly less than -1 .O
to slightly more than 1 .O. When load/unload factor
reaches + 1.0, a compressor is added. When the load/
unload factor reaches -1 .O, a compressor is subtracted.
re-enter test function and press the
the component. Components with a timed operating limit
time out normally even if another function is accessed.
key to shut down
Keypad entry
allows the operator to make the
If compressor unloaders are used, at
a compressor is
following checks by using
LID display check.
:
unloaded and at
a compressor is loaded up.
is 8.8.8.8.8.8.8.8 .
Operation of remote alarm.
(Set Point)
This subfunction displays leaving
Operation of condenser fans.
water temperature and leaving chilled water set point. If
unit is programmed for dual set point, the chilled water set
point currently in effect (either occupied or unoccupied) is
displayed. If reset is in effect, the unit operates to the mod-
ified chilled water set point. This means the leaving water
temperature may not equal the chilled water set point The
modified chilled water set point can also be displayed in the
Status function. To enter the set point subfunction, de-
Operation of chilled water pump.
Operation of
To drive EXV fully open, enter
(100% open). To drive EXV fully closed,
(0% open).
ter
Keypad entry.
compressor unloader
accesses the compressor and
tests.
press
and use the
q
to display modified leaving
chilled water set point followed by leaving water set point
and actual cooler leaving fluid temperature.
During compressor operational tests, compressor starts
and runs for 10 seconds. Compressor service valves must
be open. Energize crankcase heaters 24 hours prior to
performing compressor tests.
(Temperature)
The temperature subfunction dis-
plays the readings at temperature sensing thermistors.
Since test function checks only certain outputs, it is good
practice to also check all inputs and outputs accessible
To read a temperature, enter
, then scroll to de-
key. See Table 9 for the
sired temperature using the
order of readouts.
through the status function. These are located at
,
and (see Table 9). If keypad is not used
(Pressure)
This subfunction displays suction,
for 10 minutes, unit automatically leaves test function and
resumes rotating display. See Example 3.
discharge and net oil pressure at lead compressor of each
circuit of unit.
38
Download from Www.Somanuals.com. All Manuals Search And Download.
b. The next value displayed depends on how the sched-
ule function has been programmed. (See pages
47.) If dual set point has been selected, the next set
Example 3
Using Test Function
KEYPAD
ENTRY
DISPLAY
RESPONSE
COMMENTS
I
point after
has been pressed is the unoccupied
C O M P
Factory/field test of compressors
subfunction of test function
chilled water set point. If single set point or inactive
schedule
been selected in the schedule function,
haqs
is pressed, the display shows the
Circuit A, Compressor
test
CPA OFF
CPA ON
then when
modified chilled water set point.
Pressing starts the test:
when the compressor should be running
the display shows CPA1 on
c. The final value displayed when the
q
is pressed
CPA 1 OFF If the test is allowed to time out (10 sec-
onds) the display will show off
is the cooling ramp loading rate. This is the maxi-
mum rate at which the leaving chilled water is al-
lowed to drop, and can be field set from 0.2 to 2.0 F
CPA 2 OFF Pressing the down arrow key advances
the system to Circuit A, compressor 2 test
11” to 1.1”
This value is not displayed
unless the function is enabled (see Adjustable Field
Configurations on page 45).
NOTE: Once a compressor has been run using the
is not allowed to run again for 30 seconds.
function, it
E
l
Reading and
Set Points Example 4 shows how
to read and change the chilled water set point. Other set
points can be changed by following the same procedure.
Refer to Table 9 for the sequence of display of set points in
each subfunction.
HISTORY FUNCTION
sequent
run time for each circuit.
Keystrokes
and sub-
keystrokes display total unit run time and total
Keystrokes
and subsequent
keystrokes dis-
Example 4
Reading and Changing
.
Chilled Water Set Point
play total unit starts and the total starts for each circuit.
and subsequent
alarms along with
q
keystrokes dis-
Keystrokes
play the last
DISPLAY
RESPONSE
KEYPAD
E N T R Y
C O M M E N T S
5
a
description of each alarm.
S E T P O I N T
System set points
SET POINT FUNCTION Set points are entered through
the keypad. Set points can be changed within the upper and
lower limits, which are fixed. The ranges are listed
below.
44.0
Present occupied chilled water
set point is 44 0 F
420
Chilled Water Set Point
chilled water set point is 42 0 F
Water:
Present unoccupied chilled water
set point is 44.0 F
44.0
50.0
38 to 70 F (3.3 to 21 C)
Brine:
Press the D
i
s
p
l
a
y
15 to 70 F (-9.4 to 21 C)
shows new unoccupied chilled
water set point is 50.0 F
Set Point
0.2 to 2.0 F (0.11 to 1.1
R E S E T
Displays the maximum reset and
minimum reset set points The
minimum and maximum reference
reset set points can also be
displayed.
Reset Set Points
Maximum Reset Range:
to 20” F (0” to 11” C)
These set points are not
accessible when reset type has
been configured for NONE in
the service function
Maximum Reset Reference Range:
Return Fluid Reset
to 20” F
(0” to 11”
External Temperature Reset 20 to 125 F
Temperature Reset Based on Return Water
(-6.6 to 51.6
The control system is capable of providing leaving water
temperature reset based on return water temperature. Be-
cause the temperature difference between leaving water tem-
perature and return water temperature is a measure of the
building load, return water temperature reset is essentially
an average building load reset method.
External Signal Reset 4 to 20
Minimum Reset Reference Range:
Return Fluid Reset to 20” F
(0” to 11”
External Temperature Reset 20 to 125 F
(-6.6 to 51.6 C)
External Signal Reset 4 to 20
Under normal operation, the chiller
a constant
leaving water temperature approximately equal to chilled
water set point. As building load drops from 100% down to
entering cooler water temperature drops in proportion
to load. Thus, temperature drop across the cooler drops from
a typical 10 F (5.5 C) at full load to a theoretical F (0” C)
at no load. See Fig. 4.
Demand Limit Set Points
Switch Input:
Step 1
Step 2
0 to 100% Capacity Reduction
0 to 100% Capacity Reduction
External Signal:
Maximum Demand Limit 4 to 20
At partial load, leaving chilled water temperature may be
lower than required. If this is allowed to increase (reset),
the efficiency of the chiller increases. Amount of reset can
Minimum Demand Limit 4 to 20
Set points are grouped in subfunctions as follows:
be defined as
a
function of cooler temperature drop, as shown
Displays chiller water and cooling ramp set points.
in Fig. 4. This is a simple linear function that requires 4
pieces of input data for the set function:
a. The first value shown is the occupied chilled water
set point.
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Example
5
Using Return Water
Maximum Reset Amount (CRST2)
0” to 20” F (0” to 11” C). This is maximum amount leav-
ing chilled water set point is to be increased.
allowable range
Temperature Reset
KEYPAD
ENTRY
DISPLAY
RESPONSE
2. Maximum Reset Reference (CREF2) allowable range
0” to 20” F (0” to 11” C). This is the cooler temperature
drop at which reset reaches its maximum value.
COMMENTS
Field configuration
subfunction of
service function
FLD CFG
3. Minimum Reset Amount
allowable range
C). This is minimum amount leav-
to F (0” to
C S P T Y P
X
Scroll past single/dual
ing chilled water set point is to be increased when reset
is initiated.
Display shows no reset
type has been selected
CRTYP 0
4. Minimum Reset Reference (CREFl)
allowable range
Return water temperature
is selected and activated
0” to 20” F (0” to 11” C). This is the cooler temperature
drop at which reset is at its minimum value. (Reset be-
gins here
C R T Y P
1
S E T P O I N T
44.0
System set points
NOTE: Reset set points are not accessible unless the reset
function is enabled first. This is done as a field configura-
tion. Select one of the 3 choices for type of reset: Return
Fluid Reset, External Temperature Reset, or 4-20
ternal Signal (with a loop isolator) Reset.
Present occupied chilled
water set point
Enter new chilled water
set point
45 6
Ex-
Reset set points
maximum reset
R E S E T
If dual set point control is enabled (see Field Wiring sec-
tion on page 7 1), the amount of reset is applied to which-
ever set point is in effect at the time.
Example 5 demonstrates how to activate reset. Example
6 demonstrates how to change the type of reset. Assume
that reset is to be based on return water temperature, the
desired reset range is to be 2” to 10” F (1” to 5.5” C) and
full load is a 10” F (5.5” C) drop across the cooler. See
Fig. 4.
C R S T 2
0
0
Cooling maximum reset
is 10 F
C R S T 2 1 0
0
Cooling maximum reset
CREF2 0.0
CREF2 1.0
0 0
reference is 0” F
Cooling maximum reset
reference is 1 F
Cooling minimum reset
is
F
Activating reset based on external temperature or
Cooling minimum reset
2.0
4-20
signal is done the same way, except the reference
is 2 F
set point range is 20” to 125” F (-6.6” to 5 1.6” C), or 4 to
Cooling minimum reset
reference is 0” F
CREFl 0.0
8 0
20
depending on which method was selected at the field
configuration step.
Cooling minimum reset
reference is
F
9
8
7
I
q
13
8 0
6 0
0
2
3
4
5
6
7
8
9
RESET REFERENCE TEMPERATURE (COOLER EWT-LWT)
Fig.
4
Cooling Return Water Reset
40
Download from Www.Somanuals.com. All Manuals Search And Download.
Example 6
Changing Reset Type
Temperature Reset Based on External Temperature If de-
sired, temperature reset can be based on an external tem-
perature, such as space or outdoor-air temperature. This re-
To change type of reset, first log on as shown in
Table 11. Also refer to Set Point Function section, page 39,
for information on entering reset set points using reset
feature.
quires a thermistor
Part No.
located in
the space or outdoor air and wired to terminals as follows
(also see Field Wiring section on page 71):
KEYPAD
ENTRY
DISPLAY
RESPONSE
COMMENTS
4 in/4 out Module
and
Field configuration
subfunction of
service function
At the field configuration step, select external tempera-
FLD CFG
ture reset by entering
q
when CRTYP
0
appears. Then
Scroll past single cooling
set point
C S P T Y P
0
enter set points as described previously in Example 5. See
Fig. 5.
No reset has been
selected
CRTYP 0
Temperature Reset Based on 4-20
Signal- If desired,
signal. For
Return water temperature
reset is selected and
activated
CRTYP
1
temperature reset can be based on a 4-20
refer to Field Wiring section on page
proper connections,
71 and Fig. 6.
Reset type is changed to
space or outdoor-air
temperature reset and
activated
CRTYP 2
reset by
entering
At thqe field configuration step, select 4-20
when CRTYP
0
appears. Then enter set points
Reset type is changed to
as described previously in Example 5. See Fig.
CRTYP 3
CRTYP 0
4-20
signal reset
and activated
Demand Limit, 2-Stage Switch Control This control has
Reset is deactivated
been designed to accept demand limit signals from a build-
ing load shedding control. The demand limit function pro-
vides for 2 capacity steps. The keypad is used to set the 2
demand limit set points, which range from 100 to 0% of
capacity. Capacity steps are controlled by 2 field-supplied
relay contacts connected to the designated chiller terminals.
(See Field Wiring section on page 7 1 and Fig. 6.)
RESET REFERENCE TEMPERATURE
AIR OR
Cooling External Temperature Reset
Fig. 5
4 1
Download from Www.Somanuals.com. All Manuals Search And Download.
P O I N T NUMBER OF
FIRST CHANNEL
P
W
R
4
I
RET
DO+
c
D
LIMIT
C O D E 3 1 2
LEGEND
COMM
PWR
SW
Communications Bus
Power
Switch
NOTE: For specific connection points,
see Fig. 24 29.
(ALARM
(MODE
4 IN/4 OUT Options Module Wiring for Reset, Demand Limit,
Dual Set Point
Fig 6
To use Demand Limit, first enable loadshed, then enter
demand limit set points. See Example 7A. Closing the first
stage demand limit contact puts unit on the first demand
limit level, that is, the unit does not exceed the percentage
of capacity entered as demand limit stage 1. Closing con-
tacts on second-stage demand limit relay prevents unit from
exceeding capacity entered as demand limit stage 2. The
demand limit stage that is set to the lowest demand takes
priority if both demand limit inputs are closed.
The demand limit function must be enabled in order to
function and may be turned off when its operation is not
desired. The demand limit relays can, in off condition, re-
main connected without affecting machine operation.
Table 11
Service Functions
To view and modify configurations, the password must
be entered under the log on subfunction.
KEY FAD
E N T R Y
COMMENT
DISPLAY
F U N C T I O N
I
Enter Password/
P A S S W O R D
Disable
Password
LOGGED ON Logged On
NOTE: Configurations may be modified at this time. When
finished viewing and/or modifying configurations, log out
as follows:
-Demand Limit, 4-20
Signal
The controls can also
accept a 4-20
signal for load shedding. Input for the
L O G G E D O N
signal are terminals shown below:
Disable
Protection
Password
Externally powered (loop isolator required)
L O G O F F
Positive lead to
Negative lead to
4 In/4 Out Module
4 In/4 Out Module
Logged Off/
LOG
Enable
Password
Protection
Int erna lly pow ered
Positive lead to
Negative lead to
4 In/4 Out Module
4 In/4 Out Module
Software
Information
V E R S I O N
xxxxxxxx
X
Version
of Software
No
See Field Wiring section on page 71 and Fig. 6.
entering
At fielqd configuration step, select 4-20
when the LSTYP 0 display appears. See
by
Language
Options
Example 7B. Then enter set points as follows. In this ex-
ample, set points are coordinates of the demand limit curve
shown in Fig. 8.
42
Download from Www.Somanuals.com. All Manuals Search And Download.
16
8
6
0
0
2
4
6
8
18
2 0
RESET REFERENCE SIGNAL
-20 MA INPUT)
Fig. 7
4-20
Cooling Temperature Reset
Using Demand Limit (4-20
Example
(First Log On As Shown in Table 11)
Example 7A
(First Log On as Shown in Table 11)
Using Demand Limit
KEYPAD
ENTRY
DISPLAY
RESPONSE
KEYPAD
ENTRY
DISPLAY
RESPONSE
COMMENTS
COMMENTS
Field configuration subfunction
of service function
Field configuration sub-
function of service function
FLD CFG
FLD CFG
ERTYP
LSTYP
Scroll past other elements in
the subfunction
Scroll past other elements
in the subfunction
E R T Y P
LSTYP
LSTYP
0
is not enabled
is now enabled
is not enabled
is now enabled
for 2-stage switch control
2
L S T Y P
1
q ‘n
for 4-20
signal control
Demand Limit set points
subfunction of set point
function
DEMAND
Demand Limit set points
DEMAND
Maximum demand limit is 100%
Maximum demand limit is 90%
D M A X 1 0 0
1 currently set
100
60
a t 1 0 0 %
D M A X 9 0
reset to 60%
Maximum demand limit
reference is 20
RMAX 20
2 currently set
D L S 2 1 0 0
DLS2 40
a t 1 0 0 %
Maximum demand limit
reference is 15
R M A X 1 5
2 reset to 40%
0
Minimum demand limit is 0%
Minimum demand limit is 20%
20
4
To Disable Demand Limit:
Minimum demand limit
reference is 4
KEYPAD
ENTRY
DISPLAY
COMMENTS
RESPONSE
Minimum demand limit
reference is 6
6
Field configuration sub-
function of servicefunction
FLD CFG
Scroll past other elements
E R T Y P
L S T Y P
LSTYP
0
1
in the subfunction
is enabled for
2-stage switch control
is now disabled
0
NOTE: Select 3 for Carrier comfort Network (CCN) load limiting
Select
4
for CCN demand limiting.
43
Download from Www.Somanuals.com. All Manuals Search And Download.
= 90
M A X D E M A N D
DEMAND
SIGNAL (4-20 MA INPUT)
Fig. 8
4-20
Demand Limiting
Off
The service function is
Reading and Changing Time Displav
and displayed in 24-hour time. The day of the week is
tered as a number.
Time is entered
word protected. Therefore, to gain entry to this function,
this password must be entered. Pressing
allows the technician to view, change or enter
tion codes. To log off, perform the following keystrokes:
1 = Mon, 2 = Tue, 7 = Sun, etc.
is used as the colon when entering time. See
8.
The service function is once again
word protected.
Setting Time of Day and
Day of Week
Example 8
Software Information
number of the software that resides in the processor mod-
ule. Press a second time to display the language op-
tions that are available in the field configuration group.
T h e a n d su b f ions are summarized in
Table
displays the version
KEYPAD
ENTRY
DISPLAY
COMMENTS
RESPONSE
Time display sub-
function of set point
function
T I M E
Current setting is
Monday, 4:00
MON 1600
New setting of
Tuesday,
p m
Configuration Codes
allows entry into
TUE 13 05
is entered
and displayed
the factory configuration subfunction. Under this subfunc-
Current date is
Jan. 1, 1990
tion, there are
6
groups of configuration codes that are down-
JAN 01 90
loaded at the factory. Each group is made up of 8 digits. If
processor module is replaced in the field, these 6 groups of
configuration codes must be entered through the keypad and
New setting
April 15, 1990
is entered
APR
90
display module. Factory configuration codes (groups
1
through
and displayed
6) that apply to the particular Flotronic’” II chiller being
serviced are found on a label diagram located inside the
control box cover. See Table 12 for a summary of factory
configuration subfunction keystrokes.
SERVICE FUNCTION
This function allows the
to view and input configuration data. Factory
uration data, field configuration data and service configu-
ration data may be viewed or entered through the keypad
and display module. See Table 9 for a complete listing of
configurable items. Whenever a processor module is re-
placed in the field, the complete list of configuration codes
must be entered.
44
Download from Www.Somanuals.com. All Manuals Search And Download.
Adjustable Field Configurations
Table 13
Factory Configuration Keystrokes
To change a configuration enter the new configuration
Table 12
SERVICE
C O D E
FACTORY
ITEM AND CODES
address
and press
q
while on the correct configuration.
CCN
001
001
(Entered by CCN Technician)
S UB-
F U N C T I O N
DISPLAY
COMMENTS
CCN Bus Number
0 0 0
9 6 0 0
0 0 0
9 6 0 0
(Entered by CCN Technician)
F A C T O R Y
C O D E S
CCN Baud Rate
3 FACTORY
FACT CFG
(Entered by CCN Technician)
C F G
Cooler Fluid Select
=
Standard Models
1
=
Water (38 to 70
F
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
1
to 21 C] Set Point)
Medium Brine (15 to 70
f-9 to 21 C] Set Point)
= Brine Models
2
=
F
Unit Select
English
1 = Metric
0
0
Configuration
C o d e
0
=
3
Display Language Select
Configuration
C o d e
1
1
English
4
No. Circuit
A
Unloaders
=
=
0
=
=
No Unloaders
One Unloader
Two Unloaders
0
1
2
No.
B
Unloaders
190-210';
0
No Unloaders
One Unloader
Two Unloaders
0
0
S E R V I C E
1
S R V C F G
2
=
=
Hot Gas Bypass Select
No Valve
0
0
=
xxxxxxxx
xxxxxxxx
Loading Sequence Select
1
1
=
Equal Circuit Loading
Staged Circuit Loading
2
=
Sequence Select
L1e=adA/Luatgomatic
Pressure Switch Select
Not Used
Air Cooled
0
0
0
0
=
=
Adiustable Field Configurations After logging on, press
to enter subfunction. The subfunction allows oper-
ation of the chiller to be customized to meet the particular
needs of the application. The chiller comes from the fac-
1
Head Pressure Control Type
0
1
=
=
Not Used
Air Cooled
Head Pressure Control Method
1
=
EXV Controlled
2
Set Point Control for
Both Circuits
tory
to meet the needs of most applications.
Each item should be checked to determine which configu-
ration alternative best meets the needs of a particular appli-
cation. See Table 13 for factory loaded configuration codes
and alternative configurations.
3
=
Set Point Control for
Circuit A; EXV Control
1
for Circuit
B
4
=
Set Point Control for
Circuit B; EXV Control
for Circuit
A
If processor module is replaced, the replacement module
is preloaded with factory default configuration codes. Each
configuration code must be checked and, if necessary, re-
configured to meet needs of the application. See
Table 13 for pre-loaded service replacement configuration
codes.
Cooling Set Point
Control Select
0
1
=
=
Single Set Point Control
External Switch
0
0
0
0
Controlled Set Point
Clock Controlled
Set Point
2
Cooling Reset
Select
Control
0
2
3
=
No Reset
to enter the
Service Configuration Codes Press
=
Return Fluid Reset
=
External Temperature
service configuration subfunction. The first 2 items under
this subfunction are 2 groups (8 digits each) of configura-
tion codes that are downloaded at the factory. If processor
module is replaced in the field, the 2 groups of configura-
tion codes must be entered through the keypad and display
module. The 2 groups of configuration codes (groups 7 and
8) that apply to the unit being serviced can be found on a
label diagram inside the control box cover. See Table 12
for keystroke information to enter configuration codes 7
and 8.
Reset
=
4-20
Controlled
Reset
External Reset Sensor Select
0
=
Thermistor Connected to
Options Module
Obtained Through CCN
0
0
0
0
1
=
Demand Limit Control Select
0
=
=
No Demand Limiting
1
Two External Switch Input
0
2
= External 4-20
CCN Load Limiting
(Multi-Unit)
3
4
CCN
Interface
Ramo Load Select
SCHEDULE FUNCTION This function provides a means
to automatically switch chiller from an occupied mode to
an unoccupied mode, When using schedule function, chilled
water pump relay must be used to switch chilled water pump
on and off. Connections for chilled water pump relay are:
1
Enabled
Cooler Pump Interlock Select
0
0
0
1
=
=
No Interlock
With Interlock
and
and
(040-210 and associated modular units)
(225, 250, and 280 units). The chilled
Cooler Pump Control Select
0
1
=
=
Not Controlled
or
ON/OFF Controlled
water pump relay starts chilled water pump but compres-
sors do not run until remote chilled water pump interlock
L E G E N D
Carrier Comfort Network
Electronic Expansion Valve
contacts are between
and associated modular units, or between
on 250, and 280 units are closed and
and
on
and
*And associated modular units
leaving chilled water temperature is above set point. If a
remote chilled water pump interlock is not used, the first
compressor starts (upon a call for cooling) approximately
one minute after chilled water pump is turned on.
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Example
9
The schedule function can be programmed for inactive,
single set point, or dual set point operation.
When schedule is configured for inactive, chilled water
pump relay remains energized continuously but is not used
since chiller is usually controlled by remote chilled water
pump interlock contacts.
Using the Schedule Function
DISPLAY
No
schedule
override
O V R D
O V R D
O V R O
C L O C K
C L O C K
0
3
0
in effect
3
hours override in effect
When unit is configured for single set point operation,
chilled water pump relay is energized whenever chiller is in
occupied mode regardless of whether chiller is running. When
chiller is in unoccupied mode, chilled water pump relay is
not energized.
Override cancelled
0
Schedule function is inactive
Schedule function is enabled
through local unit clock
1
When unit is configured for dual set point, chilled water
pump relay is energized continuously, in both occupied and
unoccupied modes. Occupied mode places occupied chilled
water set point into effect; unoccupied mode places unoc-
cupied chilled water set point into effect.
Schedule function is enabled
throuah CCN clock 65
C L O C K 6 5
Define schedule period
Start of occupied time
1
PERIOD
1
For this example, first
period should stat-t here
so no entry
The schedule consists of from one to
8
occupied time pe-
riods, set by the operator. These time periods can be flagged
to be in effect or not in effect on each day of the week. The
Start of unoccupied time
(end of period) For this
period 1 should
day begins at 00
and ends at 24.00. The machine is in
00.00
unoccupied mode unless a scheduled time period is in ef-
fect, If an occupied period is to extend past midnight, it
must be programmed in the following manner: occupied pe-
end at 3:00
Period ends at 3:00
Monday is now flagged no
a
m.
1
a
m
riod must end at
hours (midnight); a new occupied
period must be programmed to begin at
hours.
for
1 To out
M O N N O
into’ effect on
NOTE: This is true only if the occupied period starts at
(midnight). If the occupied period starts at a time
other than midnight, then the occupied period must end at
hours (midnight) and new occupied period must be
Monday must be flagged
Monday is now fla ged for
period to be in e ect
M O N Y E S
TUE YES
T U E N O
For this example, period
is to be in effect on Monday
only All other days must
checked to be sure that thev
are flagged no. If any day
flagged yes, change to no
programmed to start at
in order for the chiller to stay
in the occupied mode past midnight.
The time schedule can be overridden to keep unit in oc-
cupied mode for one, 2, 3 or 4 hours on a one-time basis.
See Example 9.
Tuesday is now flagged
no for period
All subfunctions of schedule function are password pro-
tected except the override subfunction,
.
P E R I O D
2
Define schedule period
2
word entry into subfunctions through
is done through service function. See page 44, logging on/
logging off.
occ 00 00 Start of occupied
will start
occ 7 00
00.00
Figure 9 shows a schedule for an office building with the
chiller operating on a single set point schedule. The sched-
ule is based on building occupancy with a 3-hour off-peak
cool-down period from midnight to 3 a.m. following the
weekend shutdown. To learn how this sample schedule would
be programmed, see Example 9.
NOTE: This schedule was designed to illustrate the pro-
gramming of the schedule function and is not intended as a
recommended schedule for chiller operation.
Start of unoccupied time
(end of period) For this
example, period 2 should
end at 18:00 (6:00
p
m
)
Period
(6:00
2
m
ends at 18:OO
)
18 00
p
Monday is now flagged no
for period 2 To put period 2
into effect on Monday,
M O N N O
MON YES
Monday must be flagged yes
Monday is now flagged for
period
2
to be in effect
Tuesay is now flagged no
for period 2 To put period 2
into effect on Tuesday,
T U E N O
Tuesday must be flagged
Tuesday is now flagged for
TUE YES
period
2
to be in effect
For this example, period
is to be in effect only on
2
Monday
and
Tuesday
All other days must be
checked to be sure that
they are flagged no. If
W E D Y E S
a
day is flagged yes,
change to no
Wednesday is now flagged
no for period
W E D N O
2
Carrier Comfort Network
Example
CCN
9
continued next page.
4 6
Download from Www.Somanuals.com. All Manuals Search And Download.
Holiday Schedule Function
Example 10
Example 9
Using the Schedule Function
D I S P L A Y
H O L I D A Y
E N T E R
COMMENT
D I S P L A Y
PROGRAMMING PERIOD 3:
JAN01 02 (Includes Jan
and 2nd)
Define
period
schedule
3
P E R I O D
occ
3
Start of occupied
lime
01 (Includes April 17th)
MAY21 01 (Includes May 21 st)
JUL03 01 (Includes July 3rd)
JULO4 01 (Includes July 4th)
SEP07 01 (Includes Sep 7th)
will start
occ 7 00
Start of unoccupied time
(end of period 3). For this
example, period
end at
00 00
21 30
3
should
p m )
Period 3 ends at
p
m
)
Check to be sure that
Monday and Tuesday are
flagged for period
M O N N O
3
02 (Inclu2d7eths) Nov 26th
and
TUE NO
W E D N O
W E D Y E S
T H U R N O
FRI NO
DEC24 02 (Includes
24th
Wednesday
no, change to yes
is
flagged
and 25th)
02 (includes
and
30th
W e d n e s d a y i s n o w
flagged yes for period
3
Check to be sure that all
other days are flagged no
N
E
W
MAY25 01 (Includes May 25th)
SAT NO
SUN NO
N E W
N E W
N E W
Period 4 and 5 can be programmed in the same manner,
flagging Thursday and Friday yes for period 4 and Saturday
yes for period 5 For this example, periods 6, 7, and 8 are
not used: they should be programmed OCC 00.00,
00.00.
NOTE: When a day is flagged yes for 2 overlapping peri-
ods, occupied time will take precedence over unoccupied
time. Occupied times can overlap in the schedule with no
consequence.
N E W
NEW (30TH
NEW indicates a holiday that has not been assigned yet.
To extend an occupied mode beyond its normal termina-
tion for a one-time schedule override, program as shown
below:
I
2 -
3 -
4 -
5 -
8 -
9 -
II
Holidav Schedule
Press
to schedule up to
30 holiday periods. All holidays are entered with numerical
values. First, the month (01 to
then the day (01 to 3
‘ERIO
3
then the duration of the holiday period in days.
Examples: July 24 is
25 26 is 12.25.02
If any of the 30 holiday periods are not used, the display
shows NEW.
1 9
20
See Example 10.
OCCUPIED
UNOCCUPIED
Sample Time Schedule
Fig. 9
47
Download from Www.Somanuals.com. All Manuals Search And Download.
13. Cooler entering or leaving fluid thermistor failure
14. Low transducer supply voltage
TROUBLESHOOTING
The
II control has many features to aid the
technicians in troubleshooting a Flotronic II Chiller. By us-
ing keypad and display module and status function, actual
operating conditions of the chiller are displayed while unit
is running. Test function allows proper operation of com-
15. Loss of communications between processor module and
other control modules
16. Low refrigerant pressure
pressors, compressor unloaders, fans,
and other com-
Single Circuit Stoppage
can be caused by the following:
Single circuit stoppage
ponents to be checked while chiller is stopped. Service function
displays how configurable items are configured. If an op-
erating fault is detected, an alarm is generated and an
1
Low oil pressure in lead compressor
2. Open contacts in lead compressor high-pressure switch
3. Low refrigerant pressure
4. Thermistor failure
alarm code(s) is displayed under the subfunction
,
along with an explanation of the fault. Up to 5 current alarm
codes are stored. For checking specific items, see Table 9.
5. Transducer failure
6. Ground fault in lead compressor indicator (indicator is
Checking Display Codes
To determine how ma-
chine has been programmed to operate, check diagnostic
field-supplied on 040-060, 070
associated modular units)
Hz],
110, and
information
and operating mode displays
If no
ules
follows:
follow procedures in Control Mod-
64. If display is working, continue as
7. High suction superheat
8. Low suction superheat
9. Lead compressor circuit breaker
Stoppage of one
Note all alarm codes displayed,
2. Note all operating mode codes displayed,
3. Note leaving chilled water temperature set point in ef-
fect and current leaving water temperature,
.
circuit by a safety device action does not affect other
circuit. When a safety device trips on a lead compres-
sor, circuit is shut down immediately and EXV closes.
.
10. Ground fault for any circuit compressor
250, 280, and associated modular units).
.
If machine is running, compare the “in effect” leaving
water temperature set point with current water tempera-
ture. Remember, if reset is in effect, the values may be
different because machine is operating to the modified
chilled water set point, If current temperature is equal to
set point, but set point is not the one desired, remember
that if dual set point has been selected in the schedule
Lag Compressor Stoppage
Lag compressor stop-
page can be caused by the following:
Open contacts in high-pressure switch
2. Compressor ground fault (indicator is field-supplied on
040-060, 070
units)
Hz],
110, and associated modular
function, there are
2
set points to which the machine can
3. Compressor circuit breaker trip
be operating. Check the programming of schedule func-
tion to see if occupied or unoccupied set point should be
in effect.
Not required to run to meet cooling load requirement
Unit Shutoff
To shut unit off, move LOCAL/
If stoppage occurs more than once as a result of any of
the above safety devices, determine and correct the cause
before attempting another restart.
ENABLE-STOP-CCN Switch to STOP position. Any re-
frigeration circuit operating at this time continues to com-
plete the
cycle. Lag compressors stop immediately,
and lead compressors run to complete
After cause for stoppage has been
corrected, restart is either automatic or manual, depending
Restart Procedure
Complete Unit Stoppage
page can be caused by any of the following conditions:
Complete unit stop-
on fault. Manual reset requires that
STOP-CCN switch be moved to STOP position, then back
to original operating position. Some typical fault conditions
are described below. For a complete list of fault conditions,
codes, and reset type, see Table 14.
1. Cooling load satisfied
2. Remote ON/OFF contacts open
3. Programmed schedule
4. Emergency stop command from CCN
5. General power failure
POWER FAILURE EXTERNAL TO THE UNIT
restarts automatically when power is restored.
Unit
6. Blown fuse in control power feed disconnect
7. Open control circuit fuse
Typical Stoppage Faults and Reset Types
Chilled Water, Low Flow
Manual reset
8. LOCAL/ENABLE-STOP-CCN switch moved to STOP
Chilled Water, Low Temperature Auto reset first time, manual
position
if repeat
9. Freeze protection trip
10. Low flow protection trip
Chilled Water Pump Interlock
Control Circuit Fuse Blown
High-Pressure Switch Open
Low Refrigerant Pressure
Low Oil Pressure
Manual reset
Unit restarts automatically when
power is restored
11. Open contacts in chilled water flow switch (optional)
12. Open contacts in any auxiliary interlock. Terminals that
Manual reset
Auto reset first time, then manual
if within same day
are
from factory are in series with control
switch. Opening the circuit between these terminals places
unit in stop mode, similar to moving the control switch
to STOP position. Unit cannot start if these contacts
are open. If they open while unit is running, unit pumps
down and stops.
Manual reset
Gas Thermostat Open Manual reset
48
Download from Www.Somanuals.com. All Manuals Search And Download.
pressor, energizes alarm light, and displays a code of
3, 4, 5, 6, 7, or 8 depending on the compressor. Compres-
sor locks off; to reset, use manual reset method.
Alarm Codes
Following is a detailed description of
each alarm code error and possible cause. Manual reset of
an alarm is accomplished by moving
STOP-CCN Switch to STOP position, then back to LO-
CAL or CCN position. See Table 14 for listing of each alarm
code.
If lead compressor in
pressors in the circuit stop and lock off. Only the alarm
mode for lead compressor is displayed.
The microprocessor is also programmed to indicate com-
pressor failure if feedback terminal on DSIO-LV or -EXV
terminal strip receives voltage when compressor is not
supposed to be on.
a
circuit shuts down, the other com-
Code 0
No alarms exist
Codes 1 8 Compressor failure
If DSIO-LV or -EXV relay module control relay feed-
back switch or signal is sensed as open during operation of
a compressor, microprocessor detects this and stops com-
Table 14
Alarm Codes
ACTION TAKEN
B Y C O N T R O L
C K T
D E S C R I P T I O N
No Alarms Exist
PROBABLE CAUSE
DISPLAY
0
1
Compressor Al failure
Circuit
A
shut down
No
Manual
High-pressure switch trip, discharge gas
thermostat trip, or wiring error
Manual
Manual
Manual
CPCS Ground Fault Protection
Compressor A2, A3, A4 failure
Compressor
Circuit
Compressor
shut
down
Yes
2, 3,
5
4
Compressor
Compressor
failure
B
shut down
No
failure
shut
down
7,
9
A u t o
A u t o
A u t o
A u t o
A u t o
Leaving water thermistor failure
Entering water thermistor failure
Compressor Al sensor failure
Unit shut down
Unit shut down
Yes
Yes
Yes
Yes
N o
1 0
1 9
2 0
2 1
Thermistor or transducer failure
or wiring error.
Circuit
Circuit
A
B
shut down
shut down
Compressor
sensor failure
Reset thermistor failure
Normal set point used
Circuit
Circuit
Circuit
Circuit
Circuit
Circuit
A
B
A
B
A
B
shut down
shut down
shut down
shut down
shut down
shut down
Auto.
A u t o
A u t o
Auto.
Auto.
A u t o
2 2
2 3
2 4
2 5
2 6
2 7
Discharge pressure transducer failure, circuit
Discharge pressure transducer failure, circuit
A
B
Yes
N o
N o
N o
N O
Suction pressure transducer failure, circuit
Suction pressure transducer failure, circuit
A
Transducer failure or wiring error
B
Oil pressure transducer failure, circuit
Oil pressure transducer failure, circuit
A
Unit shut down
Unit shut down
N o
N o
A u t o
Unit voltage low or PSI faulty
Chilled water pump inoperative
2 8
2 9
Transducer supply voltage low
Interlock switch oaen
M a n u a l
4-20
reset input failure
Normal set point used
Demand limit ignored
Unit shut down
N o
N o
N o
A u t o
A u t o
Auto.
3 0
demand limit failure
Wiring error or faulty module
3 2
Loss of communication with DSIO-LV
or improper address
code
Unit shut down
Unit shut down
N o
A u t o
A u t o
3 3
3 4
Loss of communication with DSIO-EXV
Loss of communication with
Not used
4
Out module
Yes
3 5
3 6
I
Low refrigerant pressure circuit
A
B
No
No
Low refrigerant charge, plugged filter
drier, faulty EXV
*
3 7
Low refrigerant pressure circuit
Low refri erant charge, plugged filter
drier. fau tv EXV
No
No
Manual
Faulty EXV, transducer, or thermistor
Faultv EXV, transducer, or thermistor.
3 8
3 9
4 0
M a n u a l
oil pressure circuit
oil pressure circuit
A
Circuit
Circuit
A
B
shut down
shut down
N o
Manual
Manual
Low oil level, circuit breaker trip,
faulty EXV, crankcase heater,
or Pressure Transducer
4 1
B
No
Low oil level, circuit breaker trip,
fautty EXV, crankcase heater,
or
transducer
4 2
4 3
Cooler
freeze
protection
Unit shut down
Unit shut down
No
No
Low water flow or faulty thermistor
Low cooler water flow
Manual
Manual
M a n u a l
Chilled water pump failure
or faulty thermistor
No
Faulty EXV or thermistor
4 4
4 5
Low suction temperature circuit
Low suction temperature circuit
A
B
Circuit
A
shut down
after 10 minutes
Circuit
afler
B
shut down
N o
Faulty EXV or thermistor
minutes
4 6
4 7
High suction superheat circuit
High suction superheat circuit
A
B
Circuit
A
shut down
Yes
Yes
Manual
Manual
Low charge, faulty EXV or
thermistor, or plugged filter drier
Low charge, faulty EXV or
thermistor, or plugged filter drier.
Circuit
B
shut down
M a n u a l
Faulty EXV or thermistor
Faultv EXV or thermistor
4 8
4 9
Low suction superheat circuit
Low suction superheat circuit
A
Circuit
A
shut down
Yes
Yes
B
Circuit shut down
Manual
Manual
M a n u a l
C C N
Configuration
Configuration
error
Illegal
configuration
Unit cannot start
Unit cannot start
Unit shut down
omitted
5 1
Initial configuration required
Network
command.
Emergency stop by CCN command
Yes
5 2
L E G E N D
*Reset automatic first time, manual if repeated same day
Compressor Protection Control Module
Power Supply
49
Download from Www.Somanuals.com. All Manuals Search And Download.
and circuit start-up follows normal sequence. Cause of
fault is usually a bad thermistor, wiring error or loose
connection.
Possible causes of failure:
High-Pressure Switch Open High-pressure switch for
each compressor is wired in series with 24-v power that
energizes compressor control relay. If high-pressure switch
opens during operation, compressor stops. This is
detected by microprocessor through the feedback
terminals.
On units with transducers, if the saturated suction tem-
perature is greater than the leaving water temperature plus
10” F (5.5 C) for more than 5 minutes, the affected circuit
shuts down (after going through normal pumpout). The re-
set is automatic if the saturated suction temperature returns
to the acceptable range and start-up follows the normal se-
quence. Cause of this fault is usually a bad transducer, a
wiring error, or a loose connection.
DSIO-LV or DSIO-EXV Module Failure If a DSIO-LV
relay module relay fails open or closed, microprocessor
detects this, locks compressor off and indicates an error.
3 . Wiring Errors If a wiring error exists causing CPCS,
CR, or feedback switch not to function properly, micro-
processor indicates an error.
Code 21 Reset thermistor failure (applies only to installa-
tions having external temperature reset)
If temperature measured by this thermistor is outside range
4. Processor (PSIO) Failure
If hardware that monitors
of
to 240 F (-40 to 116 C), reset function is disabled
feedback switch fails, or processor fails to energize re-
lay module relay to on, an error may be indicated.
and unit controls to normal set point. If temperature returns
to the acceptable range, reset function is automatically en-
abled. Cause of this fault is usually a bad thermistor, wir-
ing error or loose connection.
NOTE: The control does not detect circuit breaker fail-
ures. If a circuit breaker trips on lead compressor in a
circuit, a low oil pressure failure is indicated. On the
other compressors, no failure is indicated.
Code 22 Compressor
A
1
discharge pressure
transducer failure
5 . Ground Fault Module on 130-2 10, 225, 250, 280, and
Code 23 Compressor
B
1
discharge pressure
associated modular units (CGFA or CGFB) Open
ule contacts are in lead compressor circuits, but ground
fault could be in any compressor in affected circuit.
Ground fault of any 040-l 10 and associated modular unit
compressor (field-supplied accessory on 040-060 and 070,
60 Hz units; standard on 070, 50 Hz and 80-l 10 and as-
sociated modular units) will cause a trip.
Mod-
transducer failure
Code 24 Compressor
failure
A
1
suction pressure transducer
suction pressure transducer
Code 25 Compressor
B
1
failure
Code 26 Compressor Al oil pressure transducer failure
Code 27 Compressor Bl oil pressure transducer failure
6. Checkout Procedure
Shut off main power to unit. Turn
then step through subfunc-
on control power,
If output voltage of any of these transducers is greater
than 5 v, affected circuit shuts down without going through
process. Other circuit continues to run. Reset is
automatic if output voltage returns to the acceptable range,
and circuit start-up follows normal sequence. Cause of fault
is usually a bad transducer or a wiring error.
tion
code 5 is compressor
step works correctly, then failure code is caused by:
to proper compressor number (i.e., failure
Next, energize the step. If
l
HPS (high-pressure switch) open
Misplaced feedback wire from and J5 terminals
Ground wire and 24-v feeds reversed on one or more
points on
l
Code 28
Low transducer supply voltage
If transducer supply voltage is less than 4.5 v or greater
than 5.5 v, unit shuts down without going through
process. Reset is automatic if supply voltage returns to the
acceptable range, and circuit start-up follows normal se-
quence. Cause of fault is usually a faulty transformer, or
primary voltage is out of range.
The voltage supplied to the processor is polarized. When
checking for proper voltage supply, be sure to consider this
polarity. If voltage appears to be within acceptable toler-
Compressor Alarm Circuit
alarm circuit, processor closes contacts between
nals 2 and 3 to start compressor. See Fig.
ties shown to left of must be closed in order for power to
reach compressor control relay, and the feedback input ter-
minals on J3.
Failure of power to terminal 1 on
tween 2 and 3 on J4 should be closed, causes a code 1
alarm.
For compressor Al
termi-
Safe-
when contacts be-
ance, check to be sure the transformer supplying
is not
grounded. Grounding the supply transformer can result in
serious damage to the control system.
Terminal 2 on
is the other leg of the compressor Al
Code 29 Chilled water pump interlock switch open
(applies only if unit is configured for use with
a chilled water pump interlock).
feedback channel. It is connected to the 24-v common.
NOTE: Similar connections for each compressor can be
lowed on the unit wiring diagrams located on the unit.
Code can occur under any of these conditions:
Code 9
Leaving water thermistor failure
1. Interlock switch fails to close within o n e minute after
chilled water pump starts
Code 10 Entering water thermistor failure
If temperature measured by these thermistors is outside
range of -40 to 240 F (-40 to 116 C), unit shuts down after
2. Interlock switch opens during unit operation
3. Interlock voltage is detected, but unit is not configured
for interlock
going through a normal
Reset is automatic if tem-
perature returns to the acceptable range, and unit start-up
follows normal sequence. Cause of fault is usually a bad
thermistor, wiring error, or loose connection.
4. Interlock voltage is outside its valid range
If any of these conditions occur, all compressors are dis-
abled and, if running, shutdown occurs without
Chilled water pump also shuts down. Reset is manual, with
LOCAL/ENABLE-STOP-CCN switch. Most probable cause
of this fault is shutdown or failure of chilled water pump to
start. Other possibilities are improper configuration or wir-
ing errors.
Code 19
Code 20
Compressor Al suction sensor failure
Compressor suction sensor failure
On units with thermistors, if temperature measured by
these thermistors is outside the range of -40 to 240 F (-40
to 116 C), affected circuit shuts down after going through a
normal
Other circuit continues to run. Reset is
automatic if temperature returns to the acceptable range,
Download from Www.Somanuals.com. All Manuals Search And Download.
ginning of
or
F (5.5” C) below leaving water
Code 30 Reset input failure (4 to 20
temperature or reaches a saturated suction temperature of
-15 F (-26 C). If appropriate saturated suction temperature
is not met within 3 minutes (on 2 consecutive tries}, circuit
Code 31 Demand limit input failure (4 to 20
These codes apply only if unit is configured for these
functions. If
signal is less than 4 or more than
shuts down without
Reset is manual with LOCAL/
20 reset or demand limit function is disabled and unit
ENABLE-STOP-CCN Switch, and start-up follows normal
functions normally. If
range, function is automatically enabled.
signal returns to the acceptable
sequence.
Possible causes for this alarm are
ducer or a faulty EXV.
a
bad thermistor or trans-
Code 32 Loss of communication with compressor
relay module (DISO-LV)
Code 33 Loss of communication with EXV relay
Code 40 Low oil pressure, Circuit A
Code 41 Low oil pressure, Circuit
module (DSIO-EXV)
If communication is lost with either of these modules,
If oil pressure differential is less than set point for more
than 2 minutes at start-up, or more than one minute during
normal operation, affected circuit shuts down without go-
unit shuts down without
This alarm resets auto-
matically when communication is restored. The unit starts
up normally after alarm condition is reset. Probable cause
of condition is a faulty or improperly connected plug, wir-
ing error, or faulty module.
ing through
process, Reset is manual with LOCAL/
ENABLE-STOP-CCN switch, and start-up follows normal
sequence. Factory configured differential oil pressure is
6 psig.
Loss of communication can be attributed to a grounded
transformer with a secondary voltage of 21
supplying
Possible causes of fault are faulty compressor, EXV, crank-
case heater or transducer, refrigerant overcharge, insuffi-
cient oil charge, or tripped circuit breaker.
the PSIO, DSIO-LV, or 4 IN/4 OUT modules; the
transformer supplying the DSIO-EXV module; or the
transformer supplying PS
1
for the transformers. These
Code 42 Cooler freeze protection
transformers should not be grounded, or serious damage to
If cooler entering or leaving water temperature is below
34 F (1.1 C) for water or more than 8” F (4.4” C) below set
controls can result. Check to be sure the
are
not grounded.
point for brine, unit shuts down without
Chilled
NOTE: If a blank
module is downloaded without be-
water pump continues to run if controlled by chiller con-
ing connected to the modules DSIO, this alarm is
energized.
trols. Reset is automatic when leaving water temperature
reaches
F (3” C) above set point, providing there has
Code 34 Loss of communication with 4 In/4 Out module
This applies only if one or more of the following options
are used:
been no prior occurrence of this fault the same day. If fault
has occurred previously the same day, reset is manual with
LOCAL/ENABLE-STOP-CCN switch.
Possible causes of fault are low water flow or faulty
thermistor.
Code 43 Low water flow
If any compressors are operating and entering water tem-
perature is 3” F (1.7” C) or more below leaving water tem-
perature for more than one minute, unit shuts down without
Chilled water pump also shuts down. Reset is
manual with LOCAL/ENABLE-STOP-CCN switch, and
start-up follows normal sequence.
external temperature reset
l
l
l
l
l
4-20
temperature reset
external switch controlled dual set point
switch controlled demand limit
4-20
demand limit
hot gas bypass
If communication is lost with 4 IN/4 OUT module, the
unit shuts off automatically, after finishing
of alarm is automatic when communication is restored. Start-up
after alarm is remedied follows a normal sequence. Proba-
ble cause of condition is a faulty or improperly connected
plug, wiring error, or faulty module.
Reset
This is a suitable method for sensing low water flow be-
cause entering water thermistor is in the cooler shell and
responds more quickly to compressor operation than the leav-
ing water thermistor in the leaving water nozzle, Possible
causes of fault are faulty chilled water pump, control or
thermistor.
Loss of communication can be attributed to a grounded
transformer with a secondary voltage of 21
the PSIO, DSIO-LV, or 4 IN/4 OUT; the
former supplying the DSIO-EXV module, or the
supplying
trans-
trans-
Code 44 Low cooler suction temperature, Circuit A
Code 45 Low cooler suction temperature, Circuit B
former supplying PS
should
1
for the transformers. These transformers
be grounded, or serious damage to controls can
If saturated suction temperature is less than 32 F (0°C)
result. Check to be sure the transformers are not grounded.
and is 20” F (11” C) for water or 30” F
C) for brine or
Code 36 Low refrigerant pressure, Circuit A
Code 37 Low refrigerant pressure, Circuit B
more below leaving fluid temperature, mode 14 is dis-
played. Unit continues to run, but additional compressors
are not allowed to start, If condition persists for more than
10 minutes, fault code is displayed, and unit shuts down
If suction pressure transducer senses a pressure below set
point for more than 5 minutes at start-up or more than
2 minutes during normal operation, affected circuit shuts
without
Reset is manual with
down without going through the
process. Reset is
STOP-CCN switch, and start-up follows normal sequence.
automatic when pressure reaches 10 psig above set point if
there have been no previous occurrences of this fault on the
same day. If this is a repeat occurrence on same day, then
reset is manual, with LOCAL/ENABLE-STOP-CCN switch,
Factory configured set point is 27 psig for standard chillers
and 12 psig for brine chillers.
Possible causes of fault are low refrigerant charge, faulty
EXV, plugged filter drier, or faulty transducer.
Code 38 Failure to pump out, Circuit A
Code 39 Failure to pump out, Circuit B
Possible causes of fault are low refrigerant charge, plugged
filter drier, or a faulty EXV or thermistor.
Code 46 High suction superheat, Circuit A
Code 47
High suction superheat, Circuit B
If EXV is fully open, suction superheat is greater than
75 F (42 C) and saturated evaporator temperature is less
than MOP (maximum operating pressure) for more than 5
minutes, unit shuts down after normal
process.
Reset is manual with LOCAL/ENABLE-STOP-CCN switch,
and start-up follows normal sequence.
The
process is terminated when saturated suc-
tion temperature is 10” F (5.5” C) below temperature at
51
Download from Www.Somanuals.com. All Manuals Search And Download.
This fault indicates factory configuration has not been
done, and unit is not allowed to start. Refer to unit wiring
label diagrams for factory configuration codes, There are 8
groups of S-digit numbers that must be entered. The first
Possible causes of fault are low refrigerant charge, plugged
filter drier, or a faulty EXV or thermistor.
Code 48 Low suction superheat, Circuit A
Low suction superheat, Circuit B
Code 49
groups must be entered under s u b f u n c t i o n . G r o u p s
If EXV is at minimum position, suction superheat is less
than
F (5.5” C) or saturated evaporator temperature is
7 and 8 must be entered under s u b f u n c t i o n .
greater than MOP (maximum operating pressure) for more
than
5
minutes, affected circuit shuts down after going through
Enter each group, then press the
key. Use the
process, Reset is manual with
down arrow after each group to bring up the next
empty screen. Unit should start after factory and field con-
figurations are correctly entered.
STOP-CCN switch, and start-up follows normal sequence.
Possible causes of fault are faulty EXV or thermistor.
Code 50 Illegal configuration
The usual cause of this fault is replacement of the pro-
cessor module. Refer to instructions accompanying the re-
placement module.
This fault indicates a configuration error. Unit is not al-
lowed to start. Check all configuration data and set points
and correct any errors.
Code 52 Emergency stop by CCN command.
Code 51 Initial configuration required
Unit goes through normal shutdown when this command
is received, and goes through normal start-up when
mand is cancelled.
LEGEND
STANDARD:
040-060 50 Hz
040-070 60 Hz
-
-
-
-
I
-
-
-
-
-
-
STANDARD:
ACCESSORY:
070 50
Contactor
Circuit Breaker
Communications Bus
Compressor Protection
,
040-060 50 Hz
040-070 60 Hz
CR’S
C O M M
Control
Module
CR
D G T
Compressor Contactor Relay
Discharge Gas Thermostat (Optional)
Relay Module (Low Voltage)
HPS
High-Pressure Switch
Low
Plug
P o w e r
S n u b b e r
PWR
SNB
Terminal
Block
TRAN
Transformer
U
Unloader
Fig.
24-V Safety Circuit Wiring (040-070)
52
Download from Www.Somanuals.com. All Manuals Search And Download.
CONTROL
24VAC
I
S
E
C
O N D A R
Y
1
LEGEND
Contactor
Communications Bus
Compressor Protection Control Module
Discharge Gas Thermostat (Optional)
Relay Module (Low Voltage)
l-tigh-Pressure Switch
Low Voltage
DGT
HPS
Plug
PWR
Power
Terminal Block
Transformer
Unloader
U
Fig.
24-V Safety Circuit Wiring (080-110 and Associated Modular Units)
53
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
Ground Fault Module
Communications Bus
Compressor Contactor Relay
Relay Module (Low Voltage)
High-Pressure Switch
Low Voltage
CGF
SNB
Plug
Snubber
Terminal Block
Transformer
TRAN
U
Unloader
24-V Safety Circuit Wiring (130-210 and Associated Modular Units)
Fig.
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
Contactor
Ground Fault Module
C o m m o n
C G F
Control
Relay
Discharge Gas Thermostat (Optional)
Relay Module (Low Voltage)
Electronic Expansion Valve
High-Pressure Switch
D G T
E X V
H P S
Low Volta
Normally
Plug
e
Reset Button
Terminal
Board
TB
24-V Safety Circuit Wiring (225, 250, and 280 Units)
Fig.
5 5
Download from Www.Somanuals.com. All Manuals Search And Download.
CHECKOUT PROCEDURE
agnose and correct EXV problems.
Follow steps below to di-
Electronic Expansion Valve
EXV OPERATION These valves control the flow of liq-
uid refrigerant into the cooler. They are operated by pro-
cessor to maintain a specified superheat at lead compressor
entering gas thermistor (located between compressor motor
and cylinders). There is one EXV per circuit. See Fig. 11.
Check EXV driver outputs. Check EXV output signals
at appropriate terminals on EXV driver module (see
Fig. 12) as follows:
Connect positive test lead to terminal 1 on EXV driver.
Set meter for approximately 20 vdc. Enter outputs
High-pressure liquid refrigerant enters valve through bot-
tom. A series of calibrated slots are located in side of ori-
fice assembly. As refrigerant passes through orifice, pres-
sure drops and refrigerant changes to a 2-phase condition
(liquid and vapor). To control refrigerant flow for different
operating conditions, sleeve moves up and down over ori-
fice, thereby changing orifice size. Sleeve is moved by a
linear stepper motor. Stepper motor moves in increments
and is controlled directly by processor module. As stepper
motor rotates, motion is transferred into linear movement
by lead screw. Through stepper motor and lead screws,
760 discrete steps of motion are obtained. The large num-
ber of steps and long stroke result in very accurate control
of refrigerant flow.
subfunction of test function by pressing
, then
advance to EXVA test by pressing
q
8
times. Press
The driver should drive the circuit
A
EXV
fully open. During next several seconds connect nega-
tive test lead to pins 2, 3, 4 and 5 in succession. Voltage
should rise and fall at each pin. If it remains constant at
a voltage or at zero v, remove connector to valve and
recheck.
Press
to close circuit A EXV. If a problem still
exists, replace EXV driver module. If voltage reading is
correct, expansion valve should be checked. Next, test
EXVB. Connect positive test lead to pin 7 and the neg-
ative test lead to pin 8, 9, 10, 11 in succession during
EXVB test.
The
subfunction shows EXV valve position as
a percent of full open. Position should change constantly
while unit operates. If a valve stops moving for any reason
(mechanical or electrical) other than a processor or ther-
mistor failure, the processor continues to attempt to open or
close the valve to correct the superheat. Once the calcu-
lated valve position reaches 60 (fully closed) for 040-210
and associated modular units, 145 (fully closed) for 225,
250, and 280 units, or 760 (fully open) it remains there. If
EXV position reading remains at 60, 145 or 760, and the
thermistors and pressure transducers are reading correctly,
the EXV is not moving. Follow EXV checkout procedure
below to determine cause.
2. Check EXV wiring, Check wiring to electronic expan-
sion valves from terminal strip on EXV driver. See
Fig. 12.
a. Check color coding and wire connections. Make sure
they are connected to correct terminals at driver and
EXV plug connections.
b. Check for continuity and tight connection at all pin
terminals.
c. Check plug connections at driver and at
sure EXV cables are not crossed.
to be
The EXV is also used to limit cooler suction temperature
to 50 F (10 C). This makes it possible for chiller to start at
higher cooler water temperatures without overloading com-
pressor. This is commonly referred to as MOP (maximum
operating pressure), and serves as a load limiting device to
prevent compressor motor overloading, This MOP or load
E X V D R I V E R
BOARD
J4
I
limiting feature enables the 30G
II chillers to
operate with up to 95 F (35 C) entering water temperatures
during start-up and subsequent pull-down.
STEPPER
‘ D C )
O R I F I C E
ASSEMBLY
(INSIDE
EXV
Electronic Expansion Valve
PISTON
Fig. 12
EXV Cable Connections to
SLEEVE)
EXV Driver Module,
3. Check resistance of EXV motor windings. Remove plug
at terminal strip and check resistance between com-
mon lead (red wire, terminal D) and remaining leads,
A, B , C, and E (see Fig.
25 ohms 2 ohms.
Resistance should be
Control of valve is by microprocessor. A thermistor and
a
pressure transducer located in lead compressor are used
to determine superheat. The thermistor measures tem-
perature of the superheated gas entering the compressor
cylinders. The pressure transducer measures refrigerant
pressure in the suction manifold. The microprocessor con-
verts pressure reading to a saturation temperature. The
difference between temperature of superheated gas and
saturation temperature is the superheat.
Fig. 11
c Expansion Valve (EXV)
56
Download from Www.Somanuals.com. All Manuals Search And Download.
c. Remove screws holding top cover of EXV. Carefully
remove top cover. If EXV plug was disconnected dur-
ing this process, reconnect it after cover is removed.
Because the
are controlled by the processor mod-
ule, it is possible to track valve position. During initial
start-up, EXV is fully closed. After start-up, valve po-
sition is tracked by processor by constantly observing
amount of valve movement.
The processor keeps track of EXV position by counting
the number of open and closed steps it has sent to each
valve. It has no direct physical feedback of valve posi-
tion. Whenever unit is switched from STOP to RUN po-
sition, both valves are initialized, allowing the proces-
sor to send enough closing pulses to the valve to move it
from fully open to fully closed, then reset the position
counter to zero.
When removing top cover, be careful to avoid dam-
aging motor leads.
d. Enter appropriate EXV test step for EXVA or
EXVB in the outputs subfunction of the test function
to initiate test. With
cover lifted off EXV valve body, observe operation
of valve motor and lead screw. The motor should
turn counterclockwise, and the lead screw should move
up out of motor hub until valve is fully open. Lead
screw movement should be smooth and uniform from
4. The EXV test can be used to drive EXV to any desired
position. When EXV opens, the metering slots begin to
provide enough refrigerant for operation at these steps:
step 60 for sizes 040-210 and associated modular units,
fully closed to fully open position. Press
check open to closed operation.
If valve is properly connected to processor and re-
ceiving correct signals, yet does not operate as de-
scribed above, valve should be replaced.
or
for sizes 225, 250, and 280. This is fully closed
position when circuit is operating. The fully open posi-
tion is 760 steps.
5. Check thermistors and pressure transducers that control
EXV. Check thermistors and pressure transducers that
control processor output voltage pulses to
See
Operation of EXV valve can also be checked without
removing top cover. This method depends on oper-
ator’s skill in determining whether or not valve is
moving. To use this method, initiate EXV test and
open valve. Immediately grasp EXV valve body. As
valve drives open, a soft, smooth pulse is felt for ap-
proximately 26 seconds as valve travels from fully
closed to fully open. When valve reaches end of its
Fig, 13 for locations.
Circuit A
ducer SPTA
Circuit B
Thermistor T7, Suction Pressure Trans-
Thermistor T8, Suction Pressure Trans-
ducer SPTB
a. Use temperature subfunction of the status function
to determine if thermistors are reading
correctly.
b. Check thermistor calibration at known temperature
by measuring actual resistance and comparing value
measured with values listed in Tables 15 and 16.
c. Make sure thermistor leads are connected to proper
pin terminals at terminal strip on processor mod-
ule and that thermistor probes are located in proper
position in refrigerant circuit. See Fig. 14 and 15.
opening stroke,
a
hard pulse is felt momentarily. Drive
valve closed and a soft, smooth pulse is felt for the
26 seconds necessary for valve to travel from fully
open to fully closed. When valve reaches end of its
stroke, a hard pulse is again felt as valve overdrives
by 50 steps. Valve should be driven through at least
2 complete cycles to be sure it is operating properly.
If
a
hard pulse is felt for the 26 second duration, valve
is not moving and should be replaced.
The EXV test can be repeated as required by enter-
d. Use the pressure subfunction of the Status function
ing any percentage from 0 (
movement.
to 100 to initiate
(
to determine if pressure transducers are
reading correctly. Connect a calibrated gage to lead
compressor suction or discharge pressure connection
to check transducer reading.
If operating problems persist after reassembly, they
may be due to out-of-calibration thermistor(s) or inter-
mittent connections between processor board terminals
and EXV plug. Recheck all wiring connections and volt-
e. Make sure transducer leads are properly connected in
junction box and at processor board. Check trans-
former 5 output. Check voltage transducer 5 vdc
v.
age
signals,
Other possible causes of improper refrigerant flow con-
trol could be restrictions in liquid line, Check for plugged
filter drier(s) or restricted metering slots in the EXV.
Formation of ice or frost on lower body of electronic ex-
pansion valve is one symptom of restricted metering slots.
However, frost or ice formation is normally expected
when leaving fluid temperature from the cooler is below
40 F. Clean or replace valve if necessary.
NOTE: Frosting of valve is normal during compressor
Test steps and at initial start-up. Frost should dissipate
after 5 to 10 minutes operation in a system that is oper-
ating properly. If valve is to be replaced, wrap valve
with a wet cloth to prevent excessive heat from damag-
ing internal components.
When above checks have been completed, check ac-
tual operation of EXV by using procedures outlined
in Step 5.
6. Check operation of
a. Close liauid line service valve of circuit to be checked,
and run
in that circuit to pump down low side of
Repeat test step 3 ensure all refrigerant
has been pumped from low side.
NOTE: Be sure to allow compressors to run for the
full period.
the test step (
for lead
b. Turn off compressor circuit breaker(s). Close com-
pressor discharge service valves and remove any re-
maining refrigerant from low side of system.
57
Download from Www.Somanuals.com. All Manuals Search And Download.
MUFFLERS
C O M P R E S S O R S
FILTER
D R I E R
I
CIRCUIT
CIRCUIT A
J
LEGEND
Discharge Pressure Transducer
Oil Pressure Transducer
Suction Pressure Transducer
Thermistor Number
DPT
T
Thermistor and Pressure Transducer Locations
Fig. 13
58
Download from Www.Somanuals.com. All Manuals Search And Download.
LEAVING
W A T E R / B R I N E
THERMISTOR
C O O L E R
F L U I D
B A F F L E
ENTERING
W A T E R / B R I N E
C O N N E C T I O N
A I R
VENT
SUCTION
C O N N E C T I O N
D R A I N
C O N N E C T I O N
C O O L E R
TUBE
(TYPICAL)
L E A V I N G
W A T E R / B R I N E
C O N N E C T I O N
ENTERING
W A T E R / B R I N E
THERMISTOR
Fig. 14
Thermistor Locations
(Circuits A and B, Lead Compressor Only)
THERMISTOR
W E L L
JACKETED
C A B L E
S E N S O R
TUBE
JACKETED
COUPLING
A C C E S S O R Y
I
NOTE: BEND
FOR INSERTION
INTO WELL
(76)
6)
F E R R U L E S
INSIDE
(4 8) DIA
(6.4)
COUPLING
OD
REFRIGERANT TEMPERATURE SENSOR (T7, T8 040-210 AND
ASSOCIATED MODULAR UNITS)
WATER-SIDE TEMPERATURE SENSOR (Tl, T2,
(T7, T8 225, 250, 280)
ALL UNITS),
Thermistors
Fig. 15
59
Download from Www.Somanuals.com. All Manuals Search And Download.
Pressure Transducers
TWO
of pressure trans-
a low pres-
All thermistors are identical in their tem-
perature vs. resistance performance. Resistance at various
temperatures are listed in Tables 15 and 16.
Thermistors
ducers are used on 30G
sure transducer and a high pressure transducer. The low
pressure transducer is identified by
a
white dot on the body
LOCATION
shown in Fig. 13.
General location of thermistor sensors are
of the transducer, and the high pressure transducer by a red
dot. See Fig. 16.
Cooler Leaving Water Thermistor
is located in
Three pressure transducers are mounted on each lead com-
pressor: 2 low-pressure transducers to monitor compressor
suction pressure and oil pressure, and a high-pressure trans-
ducer to monitor compressor discharge pressure (see
Fig. 17 for exact locations on compressor). Each transducer
is supplied with 5 vdc power from a rectifier which changes
leaving water nozzle. The probe is immersed directly in the
All thermistor connections are made through a
coupling. See Fig. 15. Actual location is shown in Fig. 13
and 14.
Cooler Entering Water Thermistor
cooler shell in first baffle space near tube bundle. Ther-
mistor connection is made through a coupling. See
T2 is located in
24
to 5 vdc.
TROUBLESHOOTING If transducer is suspected of be-
ing faulty, first check supply voltage to transducer. Supply
Fig. 15. Actual location is shown in Fig. 13 and 14.
Compressor Suction Gas Temperature Thermistors
and
voltage should be 5 vdc
v. If supply voltage is cor-
T7 and
are located in lead compressor in each
rect, compare pressure reading displayed on keypad and dis-
circuit in suction passage between motor and cylinders, above
oil pump. They are well-type thermistors on 040-210 and
associated modular units, or ferrule-type on 225, 250, 280
units. See Fig. 13 and 14.
play module against pressure shown on a calibrated pres-
sure gage. If the
2
pressure readings are not reasonably close,
replace pressure transducer.
TRANSDUCER REPLACEMENT
THERMISTOR REPLACEMENT (Tl , T2, T7,
pressor and Cooler)
(Com-
Transducers are installed directly in the refrigerant cir-
cuit. Relieve all refrigerant pressure using standard re-
frigeration practices before removing.
Thermistors are installed directly in fluid or refrigerant
circuit. Relieve all refrigerant pressure using standard
refrigerant practices or drain fluid before removing.
r
1. Relieve refrigerant pressure using standard refrigeration
practices.
Proceed as follows (see Fig. 15):
2. Disconnect transducer wiring at transducer by pulling
up on locking tab while pulling weather-tight connection
pfug from end of transducer. Do not pull on trans-
ducer wires.
To replace sensors
T2, T7
and
1. Remove and discard original thermistor and coupling.
3. Unscrew transducer from
male flare fitting. When
IMPORTANT: Do not disassemble new coupling.
Install as received.
installing new pressure transducer, do not use thread
sealer. Thread sealer can plug transducer and render it
inoperative.
I
2. Apply pipe sealant to
NPT threads on replace-
4. Insert weathertight wiring plug into end of transducer
until locking tab snaps in place.
ment coupling and install in place of original. Do not
use packing nut to tighten coupling. This damages fer-
rules (see Fig. 15).
5. Check for refrigerant leaks.
3. Insert new thermistor in coupling body to its full depth.
If thermistor bottoms out before full depth is reached,
pull thermistor back out in, before tightening packing
nut. Hand tighten packing nut to position ferrules, then
SAE FEMALE FLARE
finish tightening
turns with a suitable tool. Ferrules
are now attached to thermistor which can be withdrawn
from coupling for unit servicing.
To replace thermistors T7 and
(040-210 and associated
modula r unit s):
Add a small amount of thermal conductive grease to ther-
mistor well. Thermistors are friction-fit thermistors, which
must be slipped into receiver located in the compressor pump
end.
WHITE DOT-LOW PRESSURE TRANSDUCER
RED DOT -HIGH PRESSURE TRANSDUCER
Society of Automotive Engineers
SAE
Fig. 16
Pressure Transducer
60
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1 5
Thermistor Temperature
vs Resistance/Voltage Drop;
II
VOLTAGE
D R O P ( V )
RESISTANCE
(OHMS)
TEMPERATURE
VOLTAGE
D R O P ( V )
RESISTANCE
(OHMS)
TEMPERATURE
VOLTAGE
D R O P ( V )
( O H M S )
4
8
2
1
98010
94707
91522
88449
85486
82627
79871
77212
74648
72175
69790
67490
65272
63133
61070
59081
57162
55311
53526
51804
5 0 1 4 3
48541
46996
45505
44066
42679
4 1 3 3 9
40047
38800
37596
3 6 4 3 5
3 5 3 1 3
34231
3
.
0
9
3
5781
1 6 7
1 6 8
1 6 9
1 7 0
1 7 1
1 7 2
1 7 3
1 7 4
1 7 5
1 7 6
1 7 7
1 7 8
1 7 9
1 8 0
1 8 1
1 8 2
1 8 3
1 8 4
1 8 5
1 8 6
1 8 7
1 8 8
1 8 9
1 9 0
1 9 1
1 9 2
1 9 3
1 9 4
1 9 5
1 9 6
1 9 7
1 9 8
1 9 9
200
201
0
.
8
3
8
7 1 9
- 24. 0
- 23. 0
- 22. 0
- 21. 0
- 20. 0
4818
4814
4806
4. 800
4793
4786
4779
4772
4764
4. 757
4749
4740
4734
4724
4715
4705
4696
4. 688
4676
4666
4657
4648
3. 064
3034
3005
2977
2. 947
2. 917
2884
2857
2. 827
2797
2766
2738
2708
2679
0824
0. 810
0. 797
0. 783
0770
0758
0745
0734
0722
0. 710
0. 700
0. 689
0678
0668
0659
7 0 5
5637
5497
5361
5 2 2 9
5101
4976
4855
4 7 3 7
4622
4511
4403
4 2 9 8
4196
4096
4000
3906
3814
3 7 2 6
3640
3556
3474
3395
3 3 1 8
3243
3170
3099
3031
6 7 7
6 6 3
6 5 0
6 3 8
6 2 6
6 1 4
-18.0
-17.0
-16.0
15.0
14.0
-13.0
-12.0
79
82
6 0 2
5 9 1
5 8 1
5 7 0
5 6 1
5 5 1
5 4 2
5 3 3
5 2 4
5 1 6
5 0 8
5 0 1
4 9 4
487
10.0
-9.0
- 8. 0
- 7. 0
- 6. 0
- 5. 0
- 4. 0
2
650
2622
2593
2563
2533
2505
2. 476
2447
2417
2388
2360
2332
2. 305
2277
0
649
0640
0632
0. 623
0. 615
0607
0600
0592
0. 585
0579
0572
0566
0560
0554
0548
0542
89
-l:o
0 . 0
4' 613
4602
4592
4579
4. 567
4554
4540
4527
4. 514
4. 501
4487
4472
4457
4442
4427
4413
4397
4. 381
4366
4348
4. 330
4313
4. 295
4278
4258
4241
4223
4202
4184
4. 165
4145
4125
4103
4082
4. 059
4037
4017
3994
3. 968
3. 948
3927
3902
3. 878
3854
3828
3805
3781
3757
3729
3705
3. 679
3653
3627
3600
3. 575
3547
3520
3493
3464
3437
3409
3382
3. 353
3. 323
3295
3. 267
3238
3210
9 6
4 6 7
4 6 1
4 5 6
4 5 0
4 4 5
4 3 9
4 3 4
4 2 9
424
4 1 9
4 1 5
4 1 0
4 0 5
4 0 1
3 9 8
3 9 1
3 8 6
3 8 2
3 7 7
3 7 2
3 6 7
361
2964
2898
2835
2773
2713
2655
2597
2542
2488
2436
2
251
5: o
2217
2189
2. 162
2136
2107
2080
2053
2028
1 0 2
8: 0
9. 0
10. 0
1 1 . 0
1 2 . 0
1 3 . 0
14. 0
33185
3 2 1 7 6
31202
1 0 5
1 0 6
0526
0. 520
0515
0. 510
202
2 0 3
204
205
2 0 6
2 0 7
2 0 8
3 0 2 6 0
29351
2 8 4 7 3
2 7 6 2 4
26804
26011
1 0 9
1 1 0
1 1 1
1 1 2
2
001
973
1. 946
919
1
2286
2239
2192
2147
2103
2060
2018
1 9 7 7
1 9 3 7
1 8 9 8
1 8 6 0
1 8 2 2
1 7 8 6
1 7 5 0
1 7 1 5
1 6 8 0
1 6 4 7
0
494
1 6 . 0
1 7 . 0
1 8 . 0
1 9 . 0
20. 0
21. 0
22. 0
23. 0
24. 0
25. 0
26. 0
27. 0
28. 0
29. 0
30. 0
31 .o
32. 0
33. 0
34. 0
35. 0
36. 0
37. 0
38. 0
39. 0
40. 0
41. 0
42. 0
43. 0
44. 0
45. 0
46. 0
47. 0
48. 0
49. 0
50. 0
51. 0
52. 0
53. 0
54. 0
55. 0
56. 0
57. 0
58. 0
59. 0
60. 0
1
0488
2 5 2 4 5
2 4 5 0 5
2 3 7 8 9
2 3 0 9 6
2 2 4 2 7
2 1 7 7 9
2 1 1 5 3
2 0 5 4 7
1 9 9 6 0
1 9 3 9 3
1 8 8 4 3
18311
1 7 7 9 6
1 7 2 9 7
1 6 8 1 4
1 6 3 4 6
1 5 8 9 2
1 5 4 5 3
1 5 0 2 7
1 4 6 1 4
1 4 2 1 4
1 3 8 2 6
1 3 4 4 9
1 3 0 8 4
1 2 7 3 0
1 2 3 8 7
1 2 0 5 3
1897
1870
1.846
1.822
1792
1 1 4
1 1 5
1 1 6
1 1 7
1 1 8
1 1 9
1 2 0
1 2 1
2 1 0
211
0471
0465
2 1 2
213
2 1 4
2 1 5
2 1 6
217
2 1 8
2 1 9
2 2 0
221
0
459
1
771
0. 453
3 5 6
3 5 0
1. 748
1724
1. 702
1676'
1653
0. 446
0439
0432
3 4 4
3 3 8
0. 425
3 3 2
3 2 5
3 1 8
311
3 0 4
2 9 7
2 8 9
2 8 2
1 2 3
1 2 4
1 2 5
1 2 6
127
1 2 8
1 2 9
1 3 0
1 3 1
132
1 3 3
1 3 4
1 3 5
136
1 3 7
1 3 8
139
0417
1
1
630
607
585
0
409
0401
0393
0384
0375
0366
222
2 2 3
224
2 2 5
1562
1538
1
1496
1474
1453
1. 431
408
517
1 5 8 2
1 5 5 0
1 5 1 9
1 4 8 9
459
1 4 3 0
1401
1 3 7 3
1 3 4 5
1 3 1 8
1291
1389
1369
1348
1
327
1308
1291
289
1 1 7 3 0
1 4 0
1 2 6 5
1 1 4 1 6
1 4 1
1 2 4 0
1 1 1 1 2
1 0 8 1 6
1 0 5 2 9
1 0 2 5 0
9 9 7 9
9717
9461
9 2 1 3
8973
8739
8511
1 4 2
1 4 3
1 4 4
1 4 5
1 4 6
147
1 4 6
1 4 9
1 5 0
1 5 1
1 5 2
1 5 3
1 5 4
269
250
1 2 1 4
1 1 9 0
1 1 6 5
1141
1 1 1 8
1 0 9 5
1 0 7 2
1 0 5 0
1 0 2 9
1 0 0 7
986
1230
1
1192
211
1
1
1
155
136
118
100
1. 082
064
965
8291
8076
7 8 6 8
7 6 6 5
7 4 6 8
7277
7091
1
1
047
0 2 9
945
925
156
1 5 7
1 5 8
159
1 6 0
1 6 1
1 6 2
163
1 6 4
1 6 5
166
1. 012
906
0
995
887
62. 0
63. 0
64. 0
65. 0
66. 0
67. 0
68. 0
69. 0
0978
868
0
962
850
6911
0945
832
0
929
6735
6564
6399
6238
6 0 8 1
5929
815
798
782
765
750
734
0914
0
898
3
181
0883
0868
0853
3152
3123
6 1
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 16
Thermistor Temperature
vs Resistance/Voltage Drop; Flotronic’” II
TEMPERATURE
VOLTAGE
DROP (V)
RESISTANCE
(Ohms)
TEMPERATURE
VOLTAGE
DROP (V)
RESISTANCE
(Ohms)
168230
157440
147410
138090
129 410
121 330
113810
106 880
100 260
94165
- 4 0
- 3 9
- 3 8
- 3 7
- 3 6
- 3 5
- 3 4
- 3 3
- 3 2
-31
- 3 0
- 2 9
- 2 8
- 2 7
- 2 6
- 2 5
- 2 4
- 2 3
- 2 2
-21
4.896
1 . 9 4 4
1898
1 . 8 5 2
1 . 8 0 7
1 . 7 6 3
1 . 7 1 9
1 . 6 7 7
1635
1594
1553
1513
1474
1436
1 . 3 9 9
1 . 3 6 3
1 . 3 2 7
1. 291
2
272
2184
4 6
4 7
4 8
4 . 8 7 4
4 . 8 6 6
4
4
4
8 5 7
8 4 8
8 3 8
1
1
1
871
801
734
4.828
4.817
4.806
1670
1609
88 480
1
1
1
1
1
1
1
550
493
439
387
337
290
244
200
158
118
079
041
4
794
83 170
78125
73 580
69 250
4 . 7 8 2
4.769
4.755
4.740
4
725
4710
4.693
4.676
57 875
54 555
5 1 4 5 0
48 536
45 807
43 247
40 845
38 592
38 476
34 489
1 . 2 5 8
6 2
1
4
4
4
4
6 5 7
639
619
5 9 8
- 2 0
- 1 9
- 1 8
- 1 7
- 1 6
- 1 5
- 1 4
- 1 3
- 1 2
-11
1
1
1 . 1 2 9
1006
9 7 1
4 . 5 7 7
1040
1012
0. 984
9 3 8
9 0 6
8 7 6
8 3 6
8 0 5
7 7 5
7 4 7
719
693
6 6 9
645
6 2 3
602
583
5 6 4
547
5 3 1
516
502
4 8 9
477
466
456
446
436
427
4 1 9
4 1 0
402
393
385
376
367
3 5 7
3 4 6
3 3 5
3 2 4
312
4
554
4 . 5 3 1
4 . 5 0 7
4482
4 . 4 5 6
4 . 4 2 8
4400
4371
4341
4310
4. 278
4. 245
4 . 2 1 1
4 . 1 7 6
4 . 1 4 0
4 . 1 0 3
4 . 0 6 5
4026
3. 986
3. 945
3. 903
3860
3816
3 . 7 7 1
3726
32
621
0
949
0. 920
892
30 866
29 216
27 633
26 202
24 827
23 532
22313
21 163
20 079
19 058
18 094
17184
16 325
15515
14749
14026
13 342
12 696
12085
506
0
- 1 0
0. 865
0 . 8 3 8
0813
- 7
0
789
7 8
7 9
8 0
0765
0743
0722
0702
0. 683
0665
0648
0 . 6 3 2
0. 617
0. 603
0. 590
0. 577
0. 566
0555
0545
0. 535
0. 525
0. 515
0 . 5 0 6
0 . 4 9 6
0 . 4 8 6
0 . 4 7 6
0466
0454
0 . 4 4 2
- 2
- 1
0
959
3
1 0 4 4 1
9
949
3
680
3. 633
3. 585
3. 537
3. 487
3438
3387
3 . 3 3 7
3285
3234
3 . 1 8 1
3 . 1 2 9
3. 076
3 . 0 2 3
2. 970
2 . 9 1 7
2 . 8 6 4
2 . 8 1 0
2. 757
2. 704
2 . 6 5 1
2. 598
2. 545
2. 493
2 . 4 4 1
2 . 3 8 9
2337
2 . 2 8 6
2236
2 . 1 8 6
2 . 1 3 7
2087
2 . 0 3 9
1. 991
9485
9
8
8
7
7
7
044
627
231
855
499
161
101
102
6
840
6
6
5
536
246
971
0
429
104
105
106
107
0. 416
0401
0386
0370
5
5
710
461
285
5
5
4
4
225
000
786
583
4389
4
4
3
204
028
861
3
701
3
3
3
549
404
266
3134
3
2
2
2
2
2
2
008
888
773
663
559
459
363
62
Download from Www.Somanuals.com. All Manuals Search And Download.
DISCHARGE
PRESSURE
TRANSDUCER*
THERMISTOR*
ENTERING
CYLINDERS
REFRIGERANT
TEMPERATURE
*Lead compressor only
SUCTION
PRESSURE
EQUALIZER
LINE
OIL
PRESSURE
SIGHT GLASS
(EACH COMPRESSOR)
TRANSDUCER*
TRANSDUCER*
Fig. 17
Lead Compressor Transducer and Thermistor Locations
6 3
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Modules
Turn controller power off before servicing controls. This
ensures safety and prevents damage to controller.
PROCESSOR MODULE
(SIO), LOW-VOLTAGE
4 IN/4 OUT MODULE
(DSIO), AND
EXV DRIVER MODULE (DSIO)
The PSIO, DSIO and
SIO modules all perform continuous diagnostic evaluations
of the condition of the hardware. Proper operation of these
modules is indicated by
front surface of the
(light emitting diodes) on the
and on the top horizontal sur-
face of the
and SIO.
RED LED Blinking continuously at a to
rate
indicates proper operation. Lighted continuously indicates
a problem requiring replacement of module. Off continu-
ously indicates power should be checked. If there is no in-
put power, check fuses. If fuse is bad, check for shorted
secondary of transformer or for bad module. On the
module, if the light is blinking at a rate of twice per sec-
ond, the module should be replaced.
GREEN LED On a
and an SIO, this is the green
LED closest to COMM connectors. The other green LED
on module indicates external communications, when used.
Green LED should always be blinking when power is on. It
indicates modules are communicating properly. If green LED
is not blinking, check red LED. If red LED is normal, check
module address switches. See Fig.
(Processor Module)
Proper addresses are:
01 (different when CCN
connected)
DSIO (Relay Module)
19
DSIO (EXV Driver Module)
(4 In/4 Out Module)
31
59
If
modules indicate communication failure, check COMM
plug on
module for proper seating. If a good connec-
tion is assured and condition persists, replace
module.
ADDRESS
SELECTOR
If only DSIO or
module indicates communication
failure, check COMM plug on that mode for proper seat-
ing. If a good connection is assured and condition persists,
replace DSIO or SIO module.
All system operating intelligence rests in
module ,
the module that controls unit. This module monitors con-
ditions through input and output ports and through DSIO
modules (low-voltage relay module and EXV driver
module).
The machine operator communicates with microproces-
sor through keypad and display module. Communication
between
and other modules is accomplished by
a
3-wire
sensor bus. These 3 wires run in parallel from module to
module.
On sensor bus terminal strips, terminal 1 of
ule is connected to terminal 1 of each of the other modules.
Terminals 2 and 3 are connected in the same manner. See
Fig, 19, If a terminal 2 wire is connected to terminal sys-
tem does not work.
Fig. 18
Selector Switch Locations
Module Address
In
relay module, and keypad and display module are all pow-
ered from a common power source which connects
to terminals 1 and 2 of power input strip on each module. A
separate source of power is used to power options
module through terminals 1 and 2 on power input strip. A
II Chillers, processor module, low-voltage
separate source of 12.5
power is used to power EXV
driver module through terminals 1 and 2 on power input
strip.
64
Download from Www.Somanuals.com. All Manuals Search And Download.
LOW VOLTAGE RELAY MODULE (DSIO) (Fig.
Inputs on strip are discrete inputs (ON/OFF).
power is applied across the 2 terminals in a
Inputs
When
channel it reads as on signal. Zero v reads as an off signal.
Outputs
Terminal strips J4 and
are internal relays whose
signal from micro-
coils are powered-up and powered-off by
a
processor. The relays switch the circuit to which they are
connected. No power is supplied to these connections by
DSIO module.
(LID) (4
DRIVER)
S E N S O R B U S C O N N E C T O R
Sensor Bus Wiring
(Communications)
Fig.
PROCESSOR MODULE (PSIO) (Fig. 20)
Each input channel has 3 terminals; only 2 of the
RED STATUS LIGHT
Inputs
AND
ARE
(C)
terminals are used. Application of machine determines which
terminals are used. Always refer to individual unit wiring
for terminal numbers.
NEL I2
Outputs
Output is 24 vdc. There are 3 terminals, only 2
I
I
of which are used, depending on application. Refer to unit
wiring diagram.
I
I
RELAYS
NOTE: Address switches (see Fig. 20) must be set at 01
(different when CCN connected).
9
C H A S S I S
G R O U N D
8
7
0
-( REAR)
N E T W O R K
COMMON
NO
6
5
(FORWARD)
S E N S O R B U S
A D D R E S S A D J U S T M E N T
(NOT SHOWN) ON UNDERSIDE
0
0
C O N N E C T O R
J8
A D D R E S S
S W I T C H E S
LEGEND
Communications Bus
Normally Closed
Open
Fig. 21
Low-Voltage Relay Module
I-
Power
Fig. 20
Processor Module
6 5
Download from Www.Somanuals.com. All Manuals Search And Download.
4
OUT MODULE (SIO) (Fig. 22)
4 In/4 Out mod-
ule allows the following features to be utilized:
Temperature Reset by outdoor air or space temperature.
A remote thermistor (Part No,
quired.
is also re-
NOTE: This accessory is not required for return water
L
P W R
temperature reset.
I
2. Temperature Reset by remote 4-20
signal.
N
3. Demand Limit by remote 2-stage switch.
P
U
4. Demand Limit by remote 4-20
5. Dual Set Point by remote switch.
The options module is standard on
signal
ADDRESS
S W I T C H E S
J7
T
and
S
associated modular chillers and is available as a
field-installed accessory on
Flotronic II chillers.
250, and 280
Remember to reconfigure the chiller for each feature se-
lected (see Table 13). For temperature reset, demand limit,
and dual set point, desired set points must be entered through
keypad and display module (see Set Point Function section
on page 39).
0
See Table 17 for overall troubleshooting information.
l
l
l
T
P
J6
l
U
T
S
LEGEND
Communications Bus
Power
Fig. 22
4
Out Module
66
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
Table
SYMPTOMS
CAUSE
REMEDY
COMPRESSOR DOES
NOT RUN
Power line open
Reset circuit breaker
Control fuse open
Check control circuit for ground or short.
Replace fuse
High Pressure Switch (HPS)
tripped
Move LOCAL/ENABLE-STOP-CCN switch to STOP
position then back to RUN or CCN position.
Tripped power breaker
Check the controls. Find cause of trip
and reset breaker
Loose terminal connection
Improperly wired controls
Low line voltage
Check connections
Check wiring and rewire.
Check line voltage. Determine location
of voltage drop and remedy deficiency
Compressor motor defective
Check motor winding for open or shot-t.
Replace compressor if necessary.
Seized compressor
Loss of charge
Replace compressor.
Repair leak and recharge
Replace transducer.
COMPRESSOR CYCLES OFF
ON LOW PRESSURE
Bad transducer
Add
refrigerant.
Low refrigerant charge
COMPRESSOR SHUTS DOWN
High-pressure control erratic in action
Compressor discharge valve partially closed
Condenser fan(s) not operating
Replace control
Open
or replace if defective.
Check wiring. Repair or replace motor(s)
if defective.
Condenser coil
or
Clean coil.
UNIT OPERATES LONG OR
CONTINUOUSLY
Low refrigerant charge
Control contacts fused
Add
refrigerant,
Replace control
Clean or replace
plugged or plugged expansion
valve or filter driver
Defective insulation
Service load
Replace or repair.
Keep doors and windows closed.
Check valves. Replace if necessary.
Support piping as required
Piping vibration
SYSTEM NOISES
Expansion valve hissing
Add
refrigerant.
Check for plugged liquid line filter drier.
Check valve plates for valve noise.
Replace compressor (worn bearings).
Check for loose compressor
Compressor noisy
bolts.
Repair leak.
COMPRESSOR LOSES OIL
FROSTED SUCTION LINE
Leak in system
Mechanical damage (blown piston or
broken discharge valve)
Repair damage or replace compressor.
Crankcase heaters not energized
Replace heaters, check wiring and
crankcase heater relay contacts.
durina
shutdown
Check cooler and compressor thermistors.
Test EXV.
Expansion valve admitting excess
refrigerant
Shortaae of refriaerant due to leak
Shutoff valve partially closed or restricted
Burned out coil
Repair leak and recharge
Open valve or remove restriction.
Replace coil
HOT LIQUID LINE
FROSTED LIQUID LINE
COMPRESSOR DOES NOT
UNLOAD
Replace
valve
Defective capacity control valve
Miswired
solenoid
Rewire correctly.
Replace spring
Rewire correctly
Weak, broken, or wrong valve body spring
Miswired
solenoid
DOES NOT
Defective capacity control valve
Replace
valve.
Plugged strainer (high side)
Clean or replace strainer.
Clean or replace the necessary parts.
Stuck or damaged unloader piston or
piston ring(s)
Download from Www.Somanuals.com. All Manuals Search And Download.
Wire the primary side of the transformer in parallel with
TRAN3. See Fig. 23. This supplies transformer with proper
line voltage. Be sure to connect proper tap of the trans-
former to ensure supply of proper secondary voltage.
ACCESSORY UNLOADER INSTALLATION
Some of the 30G II units come standard with
unloader(s), and many permit additional unloader(s) to be
added if desired. See Table 18.
Wire the secondary side of transformer to DSIO-LV
IMPORTANT: Accessory hot gas bypass cannot be
installed with accessory unloaders on units with more
than 4 compressors.
and a jumper from DSIO-LV
Wire the secondary common to
to DSIO-LV
Connect
the transformer ground to ground hole supplied near the
transformer. These connections provide DSIO with nec-
essary power to energize the solenoid coils.
If accessory unloaders are desired, an accessory unloader
package is used. Package includes
a
suction cutoff unloader
3. When all connections are made, check for proper wiring
and tight connections. Replace and secure inner panel.
Restore power to unit.
head package. The 24-v coil in the package can be used for
040-l 10, 130 (60 Hz) and associated modular units. A
115 v or 230 v coil must be used for 130 (50 Hz), 150-210,
225, 250, 280, and associated modular units. Coil voltage
depends on control circuit voltage, Consult current Carrier
price pages for appropriate part numbers.
4. Configure the processor. With the addition of extra un-
loaders, the unit configuration has changed. To change
the configuration of the processor, enter the service func-
tion using the keypad and display module. Before any
changes can be made, the
NOTE: The accessory package will include all necessary
components and wiring with the following exceptions: The
field must provide screws, and on the 130-2 10, 225, 250,
280, and associated modular units, the field must also sup-
CCN switch must be in the STOP position, and the ser-
vicer must log on to the processor.
a. Press
Keypad LCD displays the word
a d LaCD
Keypad LCD
ply a
vdc (part number
unloader relay
PASSWORD.
Enter d
LOGGEDON.
and wire (90” C or equivalent).
i
s
. p K e y p
l
y
s
Table 18 Standard and Accessory Unloaders
I
NO. OF ACCESSORY
To change configuration, press
C.
displays FLD CFG.
d. If an additional unloader was added to compressor
Circuit
A
Circuit
B
or2
Al, press until NULA 1 appears in keypad dis-
1
0
1
1
play. Press for the number of unloaders on
circuit A. Keypad display now reads NULA 2.
0
If an additional unloader was added to compressor
*And associated modular units
B
1, press
q
until NULB
appears in keypad dis-
Installation
1. Be sure all electrical disconnects are open and tagged
before any work begins. Inspect the package contents
for any damage during shipping. File a claim with the
shipper if damage has occurred.
play. Press
for the number of unloaders on
circuit B. Keypad display now reads NULB 2.
Key-
When configuration is complete, press
pad display reads LOGGEDON. Press
until
. Keypad dis-
2. For ease of installation, factory-supplied wiring for the
additional unloader is provided in the compressor
harness.
pad display reads LOG OFF. Press
play reads EXIT LOG.
5. Using test function, check unloaders. Press
Install the additional unloader cylinder head on the lead
3.
Key-
compressor, Al or
according to instructions pro-
vided by the compressor manufacturer in the accessory
pad display reads OUTPUTS. Press
until display
package.
reads ULA
2
OFF. Press
q
.
Relay energizes. Press
until reads
4. Continue installation per either 040-l 10, 130 (60 Hz)
units or 130 (50 Hz), 150-210, 225, 250, and 280 units
section as appropriate.
and relay deenergizes. Press
ULB2 OFF. Press
. Relay energizes. Press
display q
0 4
10, 130 (60 Hz) UNITS (and associated modular units)
and relay deenergizes.
1. Wire the solenoid before any field wiring begins. Wir-
ing between components and control box must be en-
closed in conduit. All local electrical codes and National
Electrical Code (NEC) must be followed. Factory wires
are provided in the compressor harness to connect the
solenoid. These wires are in the compressor control box.
6. When unloader check has been performed, return LOCAL/
ENABLE-STOP-CCN to proper position. Close and se-
cure control box door.
2. Wire the control side. Open the left side control box
door and remove inner panel. Using the holes provided
and field-supplied screws, install field-supplied trans-
former above the DSIO-LV on the control panel.
68
Download from Www.Somanuals.com. All Manuals Search And Download.
SC H E M A T I C
i
FROM
OR
CONTROL SCHEMATIC
TRAN
080-110
Hz) and 130 (60
L E G E N D
Contactor
Compressor Protection Control System
Control Relay
Module
Terminal Block
Transformer
Unloader
Low oltage
U
Fig. 23
Accessory Unloader Control Wiring
69
Download from Www.Somanuals.com. All Manuals Search And Download.
130 (50 Hz), 150-210, 225, 250, AND 280 UNITS (and
To change the configuration, type
keypad LCD will display “FLD CFG.” Press
until either 0” or “NULA is displayed
(depending on the number of unloaders provided as
standard), Then press (for 1 unloader on Al)
or (for 2 unloaders on compressor Al). The
display will now read either “NULA 1” or
‘NULA 2, as appropriate, Press
and the
associated modular units)
Install control wiring. The minimum wire size for
stallation is 16
(American Wire Gage). Refer to
Fig. 24 and 25 for proper wiring. Open the control box
door. Locate unloader relays A and B (URA, URB) in
place of the hot gas bypass relays as shown on the com-
ponent arrangement diagram on the unit. Mount the re-
lays with the field-supplied screws. Be careful not to
damage the components and wiring in the area when mount-
ing the relays.
to get to the
NULB display, and change this setting in the same
manner as with circuit A.
2
Wire the control side. Wire the URA coil in series be-
tween
and
19 of the 4 IN/4 OUT module with
the wires provided. Wire the URB coil in series be-
d. Once the configuration is complete, press
tween
and
of the same module with the wires
and the keypad LCD will display “LOGGEDON,”
provided.
Press
until the keypad LCD display reads “LOG
Locate the black wire in the control harness originating
from labeled HGBPR-A-COM. Connect this wire
to the URA terminal COM. Connect the wire labeled
HGBPR-A-NO to URA-NO. Connect the wire from
OFF.” Press
and the keypad LCD will display
“EXIT LOG.”
5
Once the unloader heads are installed, the unit is checked
for leaks, and the system is prepared for operation per
B,
URA-NO to
For an extra unloader on circuit
connect the wire labeled HGBPR-B-COM to
COM, and the wire labeled HGBPR-B-NO to
NO. Connect the wire from URB-NO to
instructions for the compressor unloader head instal-
lation, check the output of the relays using the test func-
tion as follows:
the
3. Wire in the solenoid valves.
a. Press
and the display will read
NOTE: Wires external to the control box must be run in
conduit
b. Press the
q
to scroll down until the display reads
Terminal blocks are provided for easy field wiring. Use
“CPA1 OFF.”
one of the isolated
(22-mm) holes in the side of
c. Press
, and the compressor should start.
the compressor electrical box with a strain relief to run
the wires to the solenoid coil. Connect URA between
d. Press
,
and the compressor should stop.
a
and
Connect URB between
and
e. Press
f. Press
until the display reads
OFF.”
Check all of the electrical connections for proper
location and tightness, and replace and secure the elec-
trical box of the compressor,
c l
, and the solenoid should energize.
and the solenoid should deenergize.
and keys to check the remainder of
g. Press
q
4. Configure the microprocessor, Once the relays are mounted
in the control box, the microprocessor must be config-
h. Use the
ured for the unloader option. ‘To do so:
the unloader coils.
a. Be sure the LOCAL/ENABLE-STOP-CCN switch is
in the STOP position.
6. Once the check has been performed, return the LOCAL/
ENABLE-STOP-CCN switch to the proper position.
b. Log into the processor and enter the service func-
tion using the keypad and display module.
7. Close and secure the control box door.
8. Start the unit and confirm that the chiller operates
Type
. The keypad LCD will display
properly.
“PASSWORD.” Enter
and the
keypad LCD will display “LOGGEDON.
LEGEND
Terminal Block
Transformer
COM
Communications Bus
Hot Gas Bypass Relay
Unloader
Normally
Open
Unloader Relay
S n u b b e r
II
Unloader Wiring, 130 (50 Hz), 150-210, 225, 250, 280
Fig. 24 - Flotronic’”
70
Download from Www.Somanuals.com. All Manuals Search And Download.
-
-
-
-
-
-
-
-
-
-
-
-
w
-
-
-
m
-
-
I
I
-
-
-
-
-
-
-
-
-
-
-
-
-
-
l
- - - ‘ I
S W I T C H
I
I
I
I
I
-
-
-
-
-
-
-
-
I
-
-
-
-
I
-
!
I
I
I
I
l
I
L
-
-
B
-
-
-
-
-
I
211
I
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
A
-
-
I
I
- - - - - - - - m - w - - - - - - -
- - -OUT-PUT- I - - - - - - - - - - - - - - - - Y - -
4-20
LEGEND
Switch
Transformer
Unloader Relay
Contactor
Circuit Breaker
COMM
Communications Bus UR
Accessory Unloader Control Wiring, 130 (50 Hz),
280
Fig. 25
FIELD WIRING
Refer to Fig, 26 36 for field wiring.
4
O U T
T B 7
T B 7
T B 7
T B 7
M O D U L E
STAGE
1
!
-
-
-
-
-
-
i
t
-
-
-
-
L
- - - - - - - - - - -
STAGE
1
L
e m - - -
- - -
I
H -
r
STAGE2
2
STAGE2
Terminal Block
-
-
-
-
-
-
-
-
-
-
-
u
N O T E S :
NOTE: Contacts must be rated for dry circuit application, capable of
1
Requires accessory options module package.
2 Contacts must be rated for dry circuit application, capable of re-
reliably switching a 5 vdc,
to 20
load
liably switching a 5 vdc, 1
to 20
load
Demand Limit
Two External Switch
Fig. 26A
Inputs,
Two External Switch
250, 280 Units
Demand Limit
Inputs,
Fig. 26B
and Associated Modular Units
71
Download from Www.Somanuals.com. All Manuals Search And Download.
FIELD SUPPLIED
LOOP ISOLATOR
EXTERNAL
EXTERNAL
POWER
AND ASSOCIATED MODULAR UNITS
+
3
AND ASSOCIATED MODULAR
-
-
-
u
+
3
-
u
FIELD SUPPLIED
LOOP ISOLATOR
T B - 7
FLOTRONIC II UNITS
4
l-E-11
-
I
I
I
TB
Terminal Block
FLOTRONIC II UNITS
NOTE: The
sory options module package for this feature
Flotronic’” II units require the acces-
TB
Terminal Block
NOTE: The
Flotronic II units require the acces-
sory options module package for this feature.
Fig. 27
Demand Limit
4-20
Signal
(Externally Powered)
Fig. 30
Remote Reset from 4-20
Signal
(Externally Powered)
4
OUT
MODULE
-
-
SIGNAL
GENERATOR
-
-
-
AND ASSOCIATED MODULAR UNITS
AND ASSOCIATED MODULAR UNITS
4
3
TB-11
TB-7
FLOTRONIC II UNITS
FLOTRONIC II UNITS
TB
Terminal Block
TB
Terminal Block
NOTE: The Flotronic II units require the acces-
sory options module package for this feature
NOTE: The
sory options module package for this feature.
Flotronic II units require the acces-
Demand Limit
(Internally Powered)
4-20
Signal
Fig. 31
Remote Reset from 4-20
Signal
Fig. 28
(Internally Powered)
4
IN/4 OUT
REMOVE JUMPER
CONTACTS
M O D U L E
-
-
6
3
-
-
-
-
-
-
-
-
c
l
-
-
-
-
-
- -
-
4
REMOTE THERMISTOR
-
-
-
-
-
-
-
-
-
-
-
-
AND ASSOCIATED MODULAR UNITS
AND ASSOCIATED MODULAR UNITS
JUMPER
- - - -
g
TB-7
- - - -
10 TE7
6
TB-11
FLOTRONIC I UNITS
FLOTRONIC II UNITS
TB
Terminal Block
TB
Terminal Block
N O T E S :
1 The
Flotronic II units require the accessory op-
tions module for this feature.
2. Contacts must be rated for dry circuit application, capable of
NOTE: The
Flotronic II units require the acces-
sory options module package for this feature.
switching a 5 vdc, 1
to 20
load
Remote Reset from Space or
Outdoor-Air Temperature
Fig. 29
Remote On/Off
Fig. 32
Download from Www.Somanuals.com. All Manuals Search And Download.
(CWFS)
4
OUT
M O D U L E
TB-6
S W I T C H
-
-
-
-
-
-
I - -
-
-
-
-
-
_
_
_
AND ASSOCIATED MODULAR UNITS
AND ASSOCIATED MODULAR UNITS
-
-
-
-
-
7
-
-
-
-
-
-
-
-
8
2
FLOTRONIC
Chilled Water Pump Interlock
Chilled Water Flow Switch (not required
protection is provided by Flotronic II controls)
Terminal Block
I
I
UN ITS
FLOTRONIC’” II UNITS
CWFS
low flow
T B
Terminal Block
T B
NOTE: The
sory options module for this feature
Flotronic II units require the acces-
NOTE: Contacts must be rated for dry circuit application, capable of
reliably switching a 5 vdc,
to 20
load.
Fig. 33
Remote Dual Set Point Control
Fig. 36
Interlocks
REPLACING DEFECTIVE
PROCESSOR MODULE
-
-
-
-
-
3
The replacement part number is printed on a small label
-
c
l
on front of the
module. The model and serial num-
bers are printed on the unit nameplate located on an exte-
rior corner post. The proper software and unit configuration
data is factory installed by Carrier in the replacement mod-
T5-3
AND
MODULAR UNITS
ule. Therefore, when ordering
a
replacement processor mod-
ule (PSIO), specify complete replacement part number,
unit model number, and serial number. If these numbers
are not provided, the replacement module order is config-
ured instead as a generic Flotronic’” 11 replacement mod-
ule. This requires reconfiguration of the module by the
installer.
4
FLOTRONIC II UNITS
Chilled Water Pump
Terminal Block
T B
Electrical shock can cause personal injury, Disconnect
all electrical power before servicing.
NOTE: The maximum load allowed for the chilled water pump circuit
is 125 va sealed, 1250 va inrush at 115 or 230 v
Fig. 34
Chilled Water Pump
Installation
1. Verify the existing
module is defective by using
the procedure described in the Control Modules sec-
tion on page 64.
ALARM
SHUTOFF
2. Refer to Start-Up Checklist for Flotronic II Chiller Sys-
tems (completed at time of original start-up) found in
job folder. This information is needed later in this
S W I T C H
-
-
-
-
-
-
-
a
-
-
-
1
TB-3
I -
I
i
procedure. If checklist does not exist, fill out the
T 8 - 3
c
l
and
configuration code sections on
a
new check-
list. Tailor the various options and configurations as
needed for this particular installation.
AND ASSOCIATED MODULAR UNITS
3 . Check that all power to unit is off. Carefully discon-
nect all wires from defective module by unplugging the
6 connectors. It is not necessary to remove any of the
individual wires from the connectors. Remove the green
ground wire.
2
TB-5
FLOTRONIC II UNITS
TB
Terminal
Block
4 . Remove defective
by removing its mounting screws
with a Phillips screwdriver, and removing the module
from the control box, Save the screws for later use.
NOTE: The maximum load allowed for the alarm circuit is 125 va
sealed, 1250 va inrush at 115 or 230 v
5 . Use a small screwdriver to set address switches and
Fig. 35
Remote Alarm
S2 on the new
module to exactly match the set-
tings on the defective module.
6 . Package the defective module in the carton of the new
module for return to Carrier.
7 . Mount the new module in the unit control box using a
Phillips screwdriver and the screws saved in Step
4
above.
73
Download from Www.Somanuals.com. All Manuals Search And Download.
while displaying CODE 6. The display returns in ap-
proximately 15 seconds.
8. Reinstall all 6 wire connectors and the green ground
wire.
NOTE: Codes with leading zeros in the configuration
will be displayed starting with the first number greater
than zero.
9. Carefully check all wiring connections before restoring
power.
10. Verify the LOCAL/ENABLE-STOP-CCN switch is in
STOP position
14. Press
to verify each item is configured as needed
11. Restore control power. Verify the red and green lights
for this particular installation. Table 9 shows the fac-
tory configuration code default settings. Table 9 also
shows the service replacement code default settings which
are used if no model number was specified when or-
on top of
and front of each DSIO module re-
spond as described in Control Modules section on
page 64. The keypad and display module
or LID)
should also begin its rotating display.
dering the replacement
module. It is strongly sug-
gested that the Start-Up Checklist for
II Chiller
12. Using the keypad and display module, press
Systems (completed at time of original start-up) be used
at this time to verify and/or reprogram the various op-
tions and configurations required for this job.
to verify that the software version number matches the
ER (engineering requirement) number shown on the
label.
After completing the configuration steps outlined above,
13. Press
to verify that the 6 factory configuration
restore main power and perform a unit test as
codes (CODE 1 through CODE 6) exactly match the
codes listed for this unit model on the component ar-
rangement label diagram on the control box door. If
they are different or are all zeros, reenter the codes.
scribed in
and
sections on page 38.
Complete this procedure and restore chiller to normal
operation by returning the
CCN switch to desired position.
If any changes are required, the
display becomes
blank and reconfigures itself after pressing the
key
74
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Copyright
1994
Carrier
Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
B
T a b
P C 9 0 3
Catalog No 563-015
Printed in
U
S
A
Form
Pg 76
l-94
Replaces:
T ,
Download from Www.Somanuals.com. All Manuals Search And Download.
|
Black Box Computer Hardware MediaCento HX Transmitter and Receivers User Manual
Bolens Lawn Mower 112 340A User Manual
Breville Slow Cooker BSC560XL User Manual
Bushnell Weather Radio 950070C User Manual
Cabletron Systems Network Card 9E106 06 User Manual
Carrier Water Dispenser 30HXA User Manual
Casio Watch 1914 User Manual
Casio Watch QW 761 User Manual
Celestron Heat Pump VMC30SB 1 User Manual
Chicago Pneumatic Impact Driver CP8750 User Manual