Carrier Air Conditioner 040 420 User Manual

with  
CONTENTS  
P a g e  
Page  
Restart Procedure . . . . . . . . . . . . . . . . . . . . . . . ...48  
SAFETY CONSIDERATIONS . . . . . . . ,  
. , . . , .  
l
POWER FAILURE EXTERNAL TO THE UNIT  
GENERAL . . . . . . , . . . . , . , . . . , . , . . . . , . , . . . . . . . . 2  
Alarm Codes . . . . . . , . . . . . . . , . . . . . . . . . . , . . . . . 49  
Compressor Alarm Circuit . . . . . . . . . . . . . . . . 50  
Electronic Expansion Valve . . . . . . . . . . . . . . . . , . 56  
MAJOR SYSTEM COMPONENTS . . . . . . . . . . . . 2-4  
Processor Module . . . . . . . . . . . . . . . . . . . . . . . . ...2  
Low-Voltage Relay Module . , . . . . . . , . , . , , . . . . . 2  
Electronic Expansion Valve Module . . . . . . . . . . . 2  
l
EXV OPERATION  
l
CHECKOUT PROCEDURE  
Options Module . . . . . . . . . . . . . . . .  
. . . . . . . . . . . 2  
Thermistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...60  
Keypad and Display Module  
LOCATION  
(Also Called  
or LID) . . . . . . . . . . . . . . . . . . 2  
l
THERMISTOR REPLACEMENT  
T2, T7, T8)  
Control Switch . . . . , . . . . . . . . . . . . . . . . . . . . . . . . 2  
Electronic Expansion Valve (EXV) . . . , . . . . . . . . 4  
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...4  
Compressor Protection Control  
(Compressor and Cooler)  
Pressure Transducers . . . , . . . , . . . . . . . . . . . . . 60  
l
TROUBLESHOOTING  
l
TRANSDUCER REPLACEMENT  
Module (CPCS) . . , . . . . . . . . . . . . . . . . . . . . . . . . . 4  
Control Modules . . . . . . . . . . . . . . . . . . . . . . . , . . . . 64  
l
PROCESSOR MODULE (PSIO),  
MODULE (SIO), LOW-VOLTAGE RELAY  
MODULE (DSIO), AND EXV DRIVER MODULE  
(DSIO)  
OPERATION DATA . . . . . . . . . . . . . , . . . . , . . . . , 5-47  
Capacity Control . . . . , , . . . . . . . . . . . . . . . . . . . . . . 5  
Head Pressure Control . . . . . . . . . . . . . . . . . . . . 26  
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...27  
Keypad and Display Module  
. RED LED  
l
l
l
.
GREEN LED  
28  
(Also Called  
or  
PROCESSOR MODULE (PSIO)  
LOW-VOLTAGE RELAY MODULE (DSIO)  
MODULE (SIO)  
ACCESSING FUNCTIONS  
SUMMARY DISPLAY  
KEYPAD OPERATING INSTRUCTIONS  
STATUS FUNCTION  
ACCESSORY UNLOADER INSTALLATION  
68-7 1  
. 68  
TEST FUNCTION  
Installation . . . . . . . , . . . . . . , . . . . . . . . . . . .  
HISTORY FUNCTION  
SET POINT FUNCTION  
SERVICE FUNCTION  
l
040-110, 130 (60 Hz) UNITS  
(and associated modular units)  
l
130 (50 Hz), 150-210, 225, 250, and 280 UNITS  
(and associated modular units)  
SCHEDULE FUNCTION  
. . . . . . . . . . . . . . . . . . . . . .  
TROUBLESHOOTING  
48-67  
48  
48  
FIELD WIRING . . . . . . . . . . . . , . . . . . . . . . . . . . . . 71-73  
REPLACING DEFECTIVE PROCESSOR  
. . . . . . . . . . . . . . . . . . . . .  
Checking Display Codes  
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Unit Shutoff  
MODULE (PSIO)  
. . . . . . . . . . . . . . . . .  
.
.
. . . . . . . . . . . . . . . . . . . . 48  
Complete Unit Stoppage  
Single Circuit Stoppage  
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...73  
. . . . . . . . . . . . . . . . . . . . . 48  
Lag Compressor Stoppage . . . . . . . . . . . . . . . . . . 48  
SAFETY  
CONSIDERATIONS  
Installing, starting up, and servicing this equipment can  
be hazardous due to system pressures, electrical compo-  
nents, and equipment location (roof, elevated structures, etc.).  
Only trained, qualified installers and service mechanics should  
install, start-up, and service this equipment.  
Electrical shock can cause personal injury and death.  
Shut off all power to this equipment during installation  
and service. There may be more than one disconnect  
switch. Tag all disconnect locations to alert others not  
When working on this equipment, observe precautions in  
the literature, and on tags, stickers, and labels attached to  
the equipment, and any other safety precautions that apply.  
Follow all safety codes. Wear safety glasses and work gloves.  
Use care in handling, rigging, and setting this equipment,  
This unit uses a microprocessor-based electronic con-  
trol system. Do not use jumpers or other tools to short  
out components, or to bypass or otherwise depart from  
recommended procedures. Any short-to-ground of the  
control board or accompanying wiring may destroy the  
electronic modules or electrical components.  
and in handling  
electrical components.  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Catalog No.  
Printed in S A.  
Form  
1 - 9 4  
Replaces:  
T ,  
Bo2  
T a b  
P C 9 0 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The  
consists of  
a
processor module  
GENERAL  
a low-voltage relay module (DSIO-LV),  
2
an EXV  
IMPORTANT: This publication contains controls, op-  
driver module (DSIO-EXV), a 6-pack relay board, a key-  
pad and display module (also called HSIO or LID), ther-  
mistors, and transducers to provide inputs to the  
microprocessor. An options module (SIO) is used to pro-  
vide additional functions. This module is standard on 30GN  
modules and is a field-installed accessory on the 30GT  
tronic II units. See Fig. 1.  
eration and troubleshooting data for  
and  
250, and 280  
II chillers,  
Circuits are identified as circuits  
pressors are identified as Al, A2, etc. in circuit A,  
B2, etc. in circuit B.  
Use this guide in conjunction with separate Instal-  
lation Instructions booklet packaged with the  
A
and B, and com-  
and  
The  
Series standard Flotronic II chillers feature  
MAJOR SYSTEM COMPONENTS  
microprocessor-based electronic controls and an electronic  
expansion valve (EXV) in each refrigeration circuit.  
Processor Module  
This module contains the oper-  
ating software and controls the operation of the machine. It  
continuously monitors information received from the vari-  
ous transducers and thermistors and communicates with the  
NOTE: The  
and 045 chillers with a  
installed brine option have thermal expansion valves (TXV)  
instead of the EXV.  
relay modules and  
relay board to increase or de-  
Unit sizes 240,270, and 300-420 are modular units which  
are shipped as separate sections (modules A and B). Instal-  
lation instructions specific to these units are shipped inside  
the individual modules. See Table for a listing of unit  
crease the active stages of capacity. The processor module  
also controls the EXV driver module, commanding it to open  
or close each EXV in order to maintain the proper super-  
heat entering the cylinders of each lead compressor. Infor-  
mation is transmitted between the processor module and re-  
lay module, the EXV driver module, and the keypad and  
sizes and modular combinations. For modules  
and  
follow all general instructions as noted for unit sizes  
For all remaining modules, follow instructions for unit  
sizes 130-210.  
display module through  
a
3-wire communications bus. When  
used, the options module is also connected to the commu-  
nications bus.  
Table 1  
Unit Sizes and Modular Combinations  
For the Flotronic II chillers, the processor monitors sys-  
tem pressure by means of  
6
transducers,  
3
in each lead com-  
UNIT MODEL  
pressor. Compressor suction pressure, discharge pressure,  
and oil pressure are sensed. If the processor senses high  
discharge pressure or low suction pressure, it immediately  
shuts down all compressors in the affected circuit. During  
operation, if low oil pressure is sensed for longer than one  
minute, all compressors in the affected circuit are shut down.  
At start-up, the coil pressure signal is ignored for 2 min-  
utes. If shutdown occurs due to any of these pressure faults,  
the circuit is locked out and the appropriate fault code is  
displayed.  
30G  
40  
45  
50  
60  
70  
80  
NO45  
Low-Voltage Relay Module  
This module closes  
contacts to energize compressor unloaders and/or compres-  
sors. It also senses the status of the safeties for all compres-  
sors and transmits this information to the processor.  
160  
180  
200  
225  
225  
250  
Electronic Expansion Valve Module  
This mod-  
I
I
ule receives signals from the processor and operates the elec-  
tronic expansion valves.  
Options Module  
This module allows the use of  
00  
260  
2 8 0  
tronic II features such as dual set point, remote reset, de-  
mand limit, hot gas bypass, and accessory unloaders. The  
285  
30  
30GNf 70  
options module also  
activated from a remote 4-20  
for reset and demand limit to be  
325  
350  
380  
400  
signal. The options mod-  
ule is installed at the factory on 040-210 and modular 240-  
420 units. It is a field-installed accessory for 225, 250 and  
280 units.  
3 0 G N f  
Hz units/50 Hz units.  
Keypad and Display Module (also called  
or LID)  
This device consists of a keypad with 6 func-  
tion keys, 5 operative keys, 12 numeric keys, and an al-  
phanumeric g-character LCD. Key usage is explained in  
Accessing Functions and Subfunctions section on page 28.  
The Flotronic II control system cycles compressor un-  
loaders and/or compressors to maintain the selected leaving  
water temperature set point. It automatically positions the  
EXV to maintain the specified refrigerant superheat enter-  
ing the compressor cylinders. It also cycles condenser fans  
on and off to maintain suitable head pressure for each cir-  
cuit. Safeties are continuously monitored to prevent the unit  
Control Switch  
Control of the chiller is defined by  
the position of the LOCAL/ENABLE-STOP-CCN switch.  
This is a 3-position manual switch that allows the chiller to  
be put under the control of its own Flotronic controls,  
from operating under unsafe conditions.  
A
scheduling func-  
manually stopped, or put under the control of  
a
Carrier Corn-  
tion, programmed by the user, controls the unit occupied/  
unoccupied schedule. The control also operates a test pro-  
gram that allows the operator to check output signals and  
ensure components are operable.  
fort Network (CCN), Switch allows unit operation as shown  
in Table 2.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
In the LOCAL/ENABLE position, the chiller is under lo-  
cal control and responds to the scheduling configuration and  
set point data input at its own local interface device (key-  
pad and display module).  
Compressor Protection Control Module  
Each compressor on models  
(50 Hz), 080-  
has its own CPCS as standard equip-  
and 070 (60 Hz) units feature the  
100, and  
ment. All  
CPCS as an accessory, and CR (control relay) as standard  
In the CCN position, the chiller is under remote control  
and responds only to CCN network commands. The occupied/  
unoccupied conditions are defined by the network. All key-  
pad and display functions can be read at the chiller regard-  
less of position of the switch.  
equipment. See Fig. 2. The  
modular units and the  
10 and associated  
250, and 280 Flotronic II  
units have a CR as standard equipment. The CPCS or CR is  
used to control and protect the compressors and crankcase  
heaters. The CPCS provides the following functions:  
CCN run or stop condition is established by a command  
from the CCN network. It is not possible to force outputs  
from the CCN network, except that an emergency stop com-  
mand shuts down the chiller immediately and causes  
52” to be displayed.  
compressor contactor control  
crankcase heater control  
compressor ground current protection  
status communication to processor board  
high-pressure protection  
The CR provides all of the same functions as the CPCS  
with the exception of compressor ground current protec-  
tion. Ground current protection is accomplished by using a  
CGF (compressor ground fault) board in conjunction with  
the CR. The CGF provides the same ground fault function  
as the CPCS for units where the CPCS is not utilized.  
Table 2  
LOCAL/ENABLE-STOP-CCN  
Switch Positions and Operation  
CONFIGURATION AND  
S W I T C H  
P O S I T I O N  
U N I T  
OPERATION  
SET POINT CONTROL  
Keypad Control CCN Control  
STOP  
LOCAL/ENABLE  
Unit Cannot Run Read/Write  
Read Only  
Unit Can Run  
Read/Limited Write Read  
Unit Cannot Run Read Only  
One large relay is located on the CPCS board. This relay  
(or CR) controls the crankcase heater and compressor  
contactor. The CPCS also provides a set of signal contacts  
that the microprocessor monitors to determine the operating  
status of the compressor. If the processor board determines  
that the compressor is not operating properly through the  
signal contacts, it will lock the compressor off by  
gizing the proper 24-v control relay on the relay board. The  
CPCS board contains logic that can detect if the  
Read/Limited  
Write  
Unit Can Run  
R e a d O n l v  
Electronic Expansion Valve (EXV)  
The micro-  
processor controls the EXV through the EXV driver mod-  
ule. Inside the expansion valve is a linear actuator stepper  
motor.  
The lead compressor in each circuit has a thermistor and  
a pressure transducer located in the suction manifold after  
the compressor motor. The thermistor measures the tem-  
perature of the superheated gas entering the compressor cyl-  
inders. The pressure transducer measures the refrigerant  
pressure in the suction manifold. The microprocessor con-  
verts the pressure reading to a saturated temperature. The  
difference between the temperature of the superheated gas  
and the saturation temperature is the superheat. The micro-  
processor controls the position of the electronic expansion  
valve stepper motor to maintain 29 F (16 C) superheat.  
At initial unit start-up, the EXV position is at zero. After  
that, the microprocessor keeps accurate track of the valve  
position in order to use this information as input for the  
other control functions. The control monitors the superheat  
and the rate of change of superheat to control the position  
of the valve. The valve stroke is very large, which results  
in very accurate control of the superheat.  
ground of any compressor winding exceeds 2.5 amps. If  
this condition occurs, the CPCS module shuts down the  
compressor.  
A high-pressure switch with a trip pressure of 426  
psig (2936 48  
is wired in series with the CPCS.  
If this switch opens during operation, the compressor stops  
and the failure is detected by the processor when the signal  
contacts open. The compressor is locked off. If the lead  
compressor in either circuit is shut down by the high pres-  
sure switch or ground current protector, all compressors in  
the circuit are locked off.  
The Flotronic  
II chiller control system gath-  
Sensors  
ers information from sensors to control the operation of the  
chiller. The units use 6 standard pressure transducers and  
4
standard thermistors to monitor  
pressures and tem-  
peratures at various points within the chiller. Sensors are  
listed in Table 3.  
Table 3  
Thermistor and Transducer Locations  
THERMISTORS  
Location  
PROTECTION  
BOARD  
Sensor  
Cooler Leaving Water Temp  
Cooler Entering Water Temp  
Fig. 2  
Compressor Protection Control Module  
Compressor Suction Gas Temp Circuit A  
Compressor Suction Gas Temp Circuit B  
Remote Temperature Sensor (Accessory)  
Location  
Sensor  
D P T - A  
S P T - A  
O P T - A  
Compressor Al Discharge Pressure  
Compressor Al Suction-Pressure  
Compressor Al Oil Pressure  
Compressor Bl Discharge Pressure  
S P T - B  
O P T - B  
Compressor  
Compressor  
Suction Pressure  
Oil Pressure  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
ically reset by the return temperature reset or space and out-  
OPERATION DATA  
Capacity Control The control system cycles  
door air temperature reset features. It can also be reset from  
an external 4-20  
network signal.  
signal with a loop isolator, or from a  
compressor to give capacity control steps as shown in  
Tables The unit controls leaving chilled water tem-  
The operating sequences shown are some of many pos-  
sible loading sequences for the control of the leaving water  
temperature. If a circuit has more unloaders than another,  
that circuit will always be the lead circuit.  
perature. Entering water temperature is used by the micro-  
processor in determining the optimum time to add or sub-  
tract steps of capacity, but is not a control set point.  
The chilled water temperature set point can be automat-  
Table 4A Capacity Control Steps, 040-070  
LOADING SEQUENCE  
LOADING SEQUENCE A  
UNIT  
3 0 G N  
CONTROL  
STEPS  
%
%
Displacement  
Compressors  
Displacement  
Compressors  
A l *  
Al  
A l *  
2 5  
5 0  
Bl*  
2 5  
,
Al  
1 0 0  
Al”  
040 (60 Hz)  
045 (60 Hz)  
Al  
1
2 4  
040 (50 Hz)  
A l &  
Al  
Al  
*
4
5
Al  
Al ,Bl  
,
1 0 0  
1
040 (50  
5 3  
4
,
1 0 0  
A l *  
Al  
Al  
1
045 (50 Hz)  
4
Al  
3 8  
045 (50 Hz)  
050 (60 Hz)  
*
Al  
Al  
5
1 0 0  
Al  
045 (50 Hz)  
045 (50 Hz)  
5
1 0 0  
1 8  
Al  
1
5 6  
Al  
Al  
6
7
1 0 0  
Al ,Bl  
1
045 (50 Hz)  
4
6 4  
7
Al  
*Unloaded compressor.  
unloader, standard.  
**Compressor unloader, accessory.  
unloaders, both unloaded.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Capacity Control Steps, 040-070  
Table 4A  
LOADING SEQUENCE A  
LOADING SEQUENCE B  
UNIT  
3 0 G N  
Compressors  
Displacement  
Compressors  
1 8  
5 6  
7 3  
1
2 8  
050 (50 Hz)  
050 (50 Hz)  
Al  
B l *  
A l %  
Al  
*
Al  
Al  
050 (50 Hz)  
Al  
050 (50 Hz)  
6
1
1 5  
1 8  
1 0 0  
Al  
Al*  
060 (50 Hz)  
Al  
*
6 6  
8 3  
1 0 0  
Al  
Al  
Al  
060 (50 Hz)  
Al  
060 (50 Hz)  
,
8 3  
1 0 0  
*Unloaded compressor.  
unloader, standard.  
unloader, accessory.  
unloaders, both unloaded.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4A  
Capacity Control Steps, 040-070  
LOADING  
S
B
LOADING SEQUENCE  
A
%
30GN  
Displacement  
Displacement  
Compressors  
. .  
1 6  
060 (50 Hz)  
8 3  
1 0 0  
1 0 0  
6 5  
Al  
Al  
Al  
l
,A2,Bl  
1 0 0  
B l *  
l
*
Al  
Al  
Al  
Al  
Al  
Al  
Al  
,
Al  
1 5  
5 7  
l
Al  
Al  
Al  
Al  
Al  
Al  
070 (50 Hz)  
Al  
*Unloaded compressor.  
unloader, standard.  
**Compressor unloader, accessory.  
unloaders, both unloaded.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4B  
Capacity Control Steps, 080-110 and Associated Modular Units  
LOADING SEQUENCE A  
Compressors  
LOADING SEQUENCE B  
UNIT  
3 0 G N  
Displacement  
Compressors  
A l *  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
1 0 0  
Al”  
Al  
Al  
Al  
Al  
Al  
t t  
080 (60 Hz)  
Al  
Al  
Al  
Al  
Al  
Al  
A l *  
*
Al  
Al ,Bl  
Al  
,
Al  
Al  
Al  
Al  
*
Al  
Al  
t t  
A l *  
Al  
Al  
l
Al  
t t  
*
*
Al  
080 (SO Hz)  
Al  
Al  
Al  
Al  
*Unloaded compressor.  
unloader, standard  
**Compressor unloader, accessory  
unloaders, both unloaded.  
NOTE: These capacity control steps may vary due to lag compressor sequencing.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4B  
Capacity Control Steps, 080-110 and Associated Modular Units  
A
LOADING  
LOADING  
UNIT  
30GN  
CONTROL  
STEPS  
%
%
Displacement  
Compressors  
Displacement  
Compressors  
*
Al  
Al  
Al  
Al *,Bl  
5 3  
Al  
Al  
Al  
l
,B2  
Al  
Al  
Al  
Al  
Al  
Al  
9
1
Al  
1 0 0  
090 (60 Hz)  
1
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
BP’  
090 (60 Hz)  
Al  
Al  
8 0  
8 2  
Al  
Al  
9
1
Al  
A l *  
*
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al ,Bl  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
l
Al  
Al  
Al  
Al  
Al  
*Unloaded compressor.  
unloader, standard.  
**Compressor unloader, accessory  
unloaders, both unloaded.  
NOTE: These capacity control steps may vary due to lag compressor sequencing.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4B  
Capacity Control Steps, 080-110 and Associated Modular Units  
LOADING  
Displacement  
LOADING SEQUENCE B  
CONTROL  
STEPS  
UNIT  
3 0 G N  
Compressors  
Displacement  
Compressors  
7
4 3  
6 0  
090 (50 Hz)  
Al  
Al  
1 0 0  
Al  
Al  
tt  
090 (50 Hz)  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
A l *  
*
Al  
Al  
Al  
Al  
100, 2408,  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Bl  
Al  
Al  
Al  
270B (60 Hz)  
Al  
Al  
Al  
Al  
Al  
Al  
270B (60 Hz)  
1 0  
Al  
Al  
*Unloaded compressor  
unloader, standard.  
**Compressor unloader, accessory.  
unloaders, both unloaded.  
NOTE: These capacity control steps may vary due to lag compressor sequencing  
1 0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 40  
Capacity Control Steps, 080-I  
and Associated Modular Units  
LOADING SEQUENCE A  
LOADING EQUENCE B  
UNIT  
3 0 G N  
%
Compressors  
Displacement  
Compressors  
Displacement  
8
8
A l *  
Al  
Al  
Al  
Al  
Al  
100, 2406,  
270B (60 Hz)  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
l
l
,BZ  
100  
1 0 0  
A l %  
Al  
*
2 6  
Al  
100,  
2708 (50 Hz)  
Al  
Al  
Al  
Al  
Al  
Al  
.B2  
1 0 0  
Al  
7
t t  
A l *  
100,  
2708 (50 Hz)  
9
Al  
Al  
Al  
Al  
1 4  
Bl*  
5
6
100, 2408,  
270B (50 Hz)  
Al  
Al  
Al  
9
1 2  
Al  
Al  
A l *  
Al  
Al  
tt  
100, 2408,  
270B (50 Hz)  
Al  
Al  
9
Al  
Al  
Al  
Al  
Al  
l
,AZ,Bl  
Al  
1 6  
*Unloaded compressor.  
unloader, standard  
**Compressor unloader, accessory.  
unloaders, both unloaded.  
NOTE: These capacity control steps may vary due to lag compressor sequencing.  
1 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table  
Capacity Control Steps, 080-110 and Associated Modular Units  
LOADING SEQUENCE  
A
LOADING SEQUENCE  
B
UNIT  
30GN  
Displacement  
Compressors  
Displacement  
Compressors  
1 4  
Al  
Al  
Al  
Al  
l
, A2, Bl*  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
tt  
Al  
Al  
Al  
Al  
Al  
Al  
A l ”  
Al  
Al  
t t  
110 (60 Hz)  
Al  
Al  
Al  
Al  
Al  
Al  
A-l  
Al  
Al  
Al*  
A l %  
*
Al  
Al  
Al  
110 (50 Hz)  
Al  
Al  
l
,Bl  
Al  
l
,A2,Bl  
Al ,Bl  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
100  
*Unloaded compressor.  
unloader, standard  
**Compressor unloader, accessory.  
unloaders, both unloaded.  
NOTE: These capacity control steps may vary due to lag compressor sequencing  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4B  
Capacity Control Steps, 080-110 and Associated Modular Units  
LOADING  
B
LOADING SEQUENCE A  
Displacement Compressors  
CONTROL  
STEPS  
UNIT  
3 0 G N  
%
Displacement  
Compressors  
110 (50 Hz)  
Al  
Al  
Al  
Al  
110 (50 Hz)  
Al  
Al  
Al  
a
a
Al;; Bl  
Al  
Al  
110 (50 Hz)  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
1 2  
Al  
*Unloaded compressor.  
unloader, standard.  
**Compressor  
unloader,  
accessory  
unloaders, both unloaded.  
NOTE: These capacity control steps may vary due to lag compressor sequencing  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4C  
Capacity Control Steps, 130-210 and Associated Modular Units  
LOADING EQUENCE A  
EQUENCE B  
UNI T  
30GN  
%
%
Displacement  
Compressors  
Displacement  
Compressors  
Al  
Al  
Al  
130,  
Al lAl ,Bl  
Al  
,Bl l  
,B2  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
1 0 0  
Al  
100  
Al  
130,  
Al  
*
Al  
Al  
Al  
Al  
Al  
Al  
Al  
130,  
Al  
Al  
Al  
Al  
Al  
Al  
130,  
tt  
Al  
Al  
Al  
Al  
Al *,Bl  
Al  
Al  
Al  
Al  
Al l ,A2,Bl  
Al  
Al  
A l *  
B l *  
*
Al  
Al ,Bl  
Al  
Al  
Al  
Al  
Al  
l
Al  
Al ,Bl  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
*Unloaded compressor  
unloader, standard.  
accessory  
unloaders, both unloaded  
**Compressor  
NOTE: These capacity control steps may vary due to lag compressor sequencing+  
1 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4C  
Capacity Control Steps, 130-210 and Associated Modular Units  
LOADING SEQUENCE B  
LOADING SEQUENCE A  
UNIT  
3 0 G N  
CONTROL  
STEPS  
Compressors  
Displacement  
Compressors  
Displacement  
6
Al  
Al l  
,Bl  
Al  
Al  
130,  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al *,Bl  
Al ,Bl  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
*
All ,Bl  
Al  
Al  
Al  
Al ,Bl  
Al  
130,  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
l
,B2  
Al  
Al  
A l ’  
Al  
Al  
*
Al *,Bl  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
l
,A2,Bl  
Al  
Al  
l
,B2  
Al  
l
,A2,Bl  
l
,B2  
Al  
Al  
Al  
Al  
Al l ,A2,A3,Bl  
Al  
Al  
Al  
Al  
*Unloaded compressor.  
unloader, standard.  
**Compressor unloader, accessory  
unloaders, both unloaded.  
NOTE: These capacity control steps may vary due to lag compressor sequencing.  
1 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4C  
Capacity Control Steps, 130-210 and Associated Modular Units  
LOADING EQUENCE A  
LOADING EQUENCE  
UNIT  
3 0 G N  
%
%
Displacement  
Compressors  
Displacement  
Compressors  
6
Al  
Al  
4 9  
5 3  
Al  
Al  
Al  
Al  
Al  
Al  
9 5  
1 0 0  
tt  
*
Al  
Al’, Bl  
Al  
Al  
Al  
Al  
*
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
150 (60 Hz)  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
B l *  
A l %  
Al  
Al  
Al  
Al ,Bl  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
t t  
A l *  
Al*,&  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
*Unloaded compressor.  
unloader, standard  
**Compressor unloader, accessory.  
unloaders, both unloaded  
NOTE: These capacity control steps may vary due to lag compressor sequencing  
1 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4C  
Capacity Control Steps, 130-210 and Associated Modular Units  
SEQUENCE B  
Compressors  
SEQUENCE A  
Compressors  
Displacement  
150 (50 Hz)  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
150 (50 Hz)  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
A l *  
A l %  
Al  
*
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
170,  
Al  
Al  
l
,B2  
Al  
Al  
Al  
Al  
,
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
170,  
3008,  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
*Unloaded compressor.  
unloader, standard.  
**Compressor unloader, accessory  
unloaders, both unloaded.  
NOTE: These capacity control steps may vary due to lag compressor sequencing.  
1 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4C  
Capacity Control Steps, 130-210 and Associated Modular Units  
LOADING SEQUENCE A  
Displacement Compressors  
LOADING SEQUENCE B  
UNIT  
SIZE  
Compressors  
Al ,Bl  
170,  
Al  
Al  
Al  
Al  
l
,B2  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
l
,B2,B3  
Al  
6
t t  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
*
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Hz)  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
*Unloaded compressor.  
unloader, standard.  
**Compressor unloader, accessory.  
unloaders, both unloaded.  
NOTE: These capacity control steps may vary due to lag compressor sequencing  
1 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4C  
Capacity Control Steps, 130210 and Associated Modular Units  
SEQUENCE B  
Compressors  
i SEQUENCE A  
U N I T  
CONTROL  
STEPS  
%
Compressors  
Displacement  
Displacement  
1 9  
Al  
Al  
3 7  
Al  
170,  
Al  
Al  
Al  
Al  
Hz)  
Al  
7 2  
Al  
Al  
Al  
9 6  
1 0 0  
Al  
Al  
Al ,Bl  
Al .Bl  
170,  
3008,  
Hz)  
Al  
Al  
,
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al l  
Al  
,Bl  
Al  
Al  
Al  
*
Al  
3008,  
Al  
Al  
Al  
Al  
Al  
,
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
81  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
1 0 0  
*Unloaded compressor.  
unloader, standard  
**Compressor unloader, accessory  
unloaders, both unloaded.  
NOTE: These capacity control steps may vary due to lag compressor sequencing.  
1 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4C  
Capacity Control Steps,  
and Associated Modular Units  
SEQUENCE B  
Compressors  
UNIT  
SIZE  
%
Compressors  
Displacement  
41  
5 6  
Al  
Al  
Al  
Al  
Al  
Hz)  
Al  
Al  
Al  
Al  
Al  
Al  
,
Al  
Al  
Al  
Al  
*
Al  
Al  
190,  
,
Al  
Al  
Al  
Al  
Al  
A l *  
Al  
Al  
Al  
l
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al l ,A2,A3,Bl  
Al  
l
,B2,B3  
,B2,B3  
Al  
Al  
Al  
Al  
l
Al  
Al  
Al  
Al  
,A2,A3,Bl*,B2,B3  
l
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Hz)  
,
A l *  
Al  
Al  
l
,A2,A3,Bi  
Al  
Al  
Al  
*Unloaded compressor.  
unloader, standard.  
**Compressor unloader, accessory.  
unloaders, both unloaded  
NOTE: These capacity control steps may vary due to lag compressor sequencing  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4C  
Capacity Control Steps, 130-210 and Associated Modular Units  
SEQUENCE B  
LOADING SEQUENCE A  
Displacement Compressors  
UNIT  
SIZE  
CONTROL  
S T E P S  
%
Displacement  
Compressors  
1
1
*
Al  
5 0  
61  
Al  
Al  
,
Al  
Al  
a 3  
9 4  
Al  
l
,82,83  
Al  
Al*  
l
Al  
l
Al  
Al  
,Bl  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
,
Al  
Al  
Al  
Al  
Al  
Al  
AI  
Al  
Al  
AI  
At  
t
1 4  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Hz)  
Al  
AI  
Al  
A l *  
Al  
Al  
l
,A2,Bl  
Al  
210,  
Al l ,A2,Bl  
Al  
,
Al l ,A2,A3,Bl  
At  
Al l ,A2,A3,61  
Al  
Al  
Al  
l
,A2,A3,A4,Bi  
*
Al  
210,  
At  
l
,B2  
,B2,B3  
Al  
Al  
l
Al  
Al  
Al  
Al  
Al  
*Unloaded compressor.  
j-Compressor unloader, standard.  
**Compressor unloader, accessory.  
unloaders, both unloaded.  
NOTE: These capacity control steps may vary due to lag compressor sequencing.  
2 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Capacity Control Steps, 130-210 and Associated Modular Units  
Table 4C  
i SEQUENCE A  
Compressors  
LOADING SEQUENCE B  
UNIT  
SIZE  
Displacement  
Compressors  
9
Bl*  
*
Al  
Al  
Al  
Al  
Al  
Al  
Al ,Bl  
Al  
210,  
Al  
Al l ,A2,Bl  
(60  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
210,  
Hz)  
,
Al”  
Al  
Al  
Al  
Al  
Al  
210,  
,
Al  
Al  
Al  
Al  
*
Al  
Al  
Al  
Al  
Al  
Al  
210,  
,
Al  
Al  
Al  
Al  
B l *  
*
*
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al l ,A2,Bl  
Al l ,A2,Bl  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
*Unloaded compressor  
unloader, standard  
**Compressor unloader, accessory  
unloaders, both unloaded.  
NOTE: These capacity control steps may vary due to lag compressor sequencing.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4D  
Capacity Control Steps, 225, 250,280  
LOAC  
SEQUENCE A  
LOADING SEQUENCE B  
UNIT  
30GT  
%
Compressors  
Compressors  
Displacement  
Displacement  
1 2  
1 2  
4 6  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
225 (60 Hz)  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al l ,A2,A3,Bl  
Al  
Al  
Al  
Al  
Al  
Al  
A l *  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
l
,A2,A3,Bl  
l
,B2,B3  
Al  
l
,A2,A3,Bl*,B2,B3  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
At  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
225 (50 Hz)  
Al  
Al  
Al  
At  
Al  
Al  
Al  
Al  
Al  
Al  
*Unloaded compressor.  
unloader, standard.  
**Compressor unloader, accessory  
unloaders, both unloaded.  
NOTE: These capacity control steps may vary due to lag compressor sequencing  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4D  
Capacity Control Steps, 225, 250,280  
SEQUENCE  
A
LOAC  
SEQUENCE B  
Compressors  
Bl*  
LOAC  
UNIT  
30GT  
Compressors  
*
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
2 2  
3 2  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
250 (60 Hz)  
A l *  
Al  
2 9  
3 2  
Al  
Al  
5 4  
5 7  
Al  
Al  
Al  
Al  
Al  
Al  
A l *  
*
Al  
l
Al  
Al ,Bl  
Al  
Al  
Al  
Al ,Bl  
Al  
Al l ,A2,Bl  
Al l ,A2,Bl  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
9 6  
100  
*Unloaded compressor.  
standard  
**Compressor unloader, accessory  
unloaders, both unloaded.  
NOTE: These capacity control steps may vary due to lag compressor sequencing.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4D  
Capacity Control Steps, 225, 250, 280  
SEQUENCE A  
LOADING SEQUENCE B  
Compressors  
UNIT  
3 0 G T  
CONTROL  
S T E P S  
Compressors  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
250 (50 Hz)  
280 (60 Hz)  
Al  
Al  
Al  
Al”  
Al  
Al  
l
,A2,Bl  
Al  
Al  
Al  
Al**  
Al  
Al  
Al  
l
,A2,A3,A4,Bi  
Al  
A l *  
*
Al  
Al  
Al  
Al ,Bl  
Al  
l
,Bl*,B2  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al l ,A2,Bl  
Al  
Al  
Al  
Al l ,A2,A3,Bl  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
Al  
*Unloaded compressor.  
-/-Compressor unloader, standard.  
““Compressor unloader, accessory  
unloaders, both unloaded  
NOTE: These capacity control steps may  
due to lag compressor sequencing  
2 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
As the condensing temperature rises, the EXV closes to  
maintain the proper suction superheat. Once the EXV has  
closed to 39.5% open (300 steps open), a fan stage is added  
after 2 minutes.  
During start-up, all the condenser fans are started when  
the condensing temperature reaches 95 F (35 C) to prevent  
excessive discharge pressure during pulldown. See Table 5  
for condenser fan sequence of operation.  
Head Pressure Control  
The microprocessor con-  
trols the condenser fans in order to maintain the lowest con-  
densing temperature possible, thus the highest unit efficiency.  
Instead of using the conventional head pressure control meth-  
ods, the fans are controlled by the position of the EXV and  
suction superheat.  
As the condensing temperature drops, the EXV opens to  
maintain the proper suction superheat. Once the EXV is  
fully open, if the condensing temperature continues to drop,  
the suction superheat begins to rise. Once the suction super-  
heat is greater than 40 F (22.2 C), a fan stage is removed  
after 2 minutes,  
Table 5  
Condenser Fan Sequence  
FAN CONTACTOR  
CONTROLLED BY  
FAN ARRANGEMENT  
FAN NUMBER(S)  
FC-Al  
Compressor Al  
Compressor  
I
2
3
First Stage  
Microprocessor  
FC-A2  
Second  
Stage  
4
Compressor Al  
Compressor  
FC-Al  
FC-Al  
I
First Stage  
Microprocessor  
Second  
Stage  
Microprocessor  
Compressor Al  
Compressor  
1
Compressor Al  
Compressor  
FC-Al  
F C - 8 1  
F C - A 2  
(and associated modular units)  
2
3
First Stage  
4
Microprocessor  
5, 7,  
FC-AS,  
Second  
Compressor  
Stage  
3, 4, 5, 6, 7,  
FC-A3  
FC-B3  
,
Third Stage  
Microprocessor  
FC-Al  
Compressor Al  
Compressor  
(and associated modular units)  
7
FC-Bl  
FC-A2, FC-A3  
FC-Al  
Compressor Al  
(and associated modular units)  
7
I
I
I
6 .  
8
I
FC-A2  
FC-B2  
3,  
Frist Stage  
Microprocessor  
4,  
1
,
3, 9, 11  
FC-A2,  
Second  
Stage  
2, 4 , 10, 1 2  
Microprocessor  
*Control box.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5  
Condenser Fan Sequence  
FAN NUMBER(S)  
CONTROLLED BY  
FAN ARRANGEMENT  
7,  
FC-1  
Compressor Al  
Compressor  
9, 1 0  
FC-4  
FC-2  
FC-5  
First Stage  
Microprocessor  
11, 1 2  
2, 3 ,  
4
FC-3  
FC-6  
Second  
Microprocessor  
Stage  
13, 14, 15, 16  
2, 3, 4,  
11, 12,  
6
FC-2, FC-3  
FC-5, FC-6  
Third Stage  
Microprocessor  
14, 15, 1 6  
7, 8,  
FC-1  
Compressor  
Compressor  
(60 Hz)  
Al  
9, 17, 1 8  
FC-4  
6
FC-2  
FC-5  
First Stage  
Microprocessor  
11, 12, 19  
2, 3, 4,  
14, 15, 16, 20  
Second  
Microprocessor  
Stage  
FC-3, FC-6, FC-7  
1
,
2, 3, 4, 5, 6, 11, 12, 13,  
Third Stage  
14, 15, 16,  
19, 2 0  
7, 8, 1 0  
9,  
Microprocessor  
FC-1  
(50 Hz) AND  
Compressor Al  
Compressor  
17, 1 8  
FC-4  
FC-2  
FC-5  
First Stage  
Microprocessor  
II, 12,  
2, 3, 4, 13,  
14, 15, 16, 21, 22  
Second  
Stage  
FC-3, FC-6, FC-7  
Microprocessor  
1, 2, 3, 4, 5, 6, 11, 12, 13,  
14, 15, 16, 19, 20, 21, 2 2  
FC-2, FC-3, FC-4,  
FC-5, FC-6, FC-7  
Third Stage  
Microprocessor  
*Control box.  
box.  
saturated suction temperature is below -15 F (-26 C). At  
this point, the EXV starts to open and continues to open  
gradually to provide a controlled start-up to prevent liquid  
flood-back to the compressor.  
When the lead compressor in each circuit  
is started or stopped, that circuit goes through a  
cycle to purge the cooler and refrigerant suction lines of  
refrigerant.  
At shutdown, the  
urated suction temperature for that circuit is 10” F (5.5” C)  
below the saturated suction temperature when is  
initiated, or saturated suction temperature reaches -15 F  
(-26 C). At that point, the compressor shuts down and the  
EXV continues to move until fully closed.  
cycle continues until the sat-  
The  
cycle starts immediately upon starting the  
lead compressor and continues until the saturated suction  
temperature is 10” F (5.5” C) below the saturated suction  
temperature at start-up, is  
F (5.5” C) below the cooler  
leaving fluid temperature, or reaches  
a
saturated suction tem-  
is necessary if the  
perature of -15 F (-26 C). No  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The default display is displayed every 2 seconds if there  
has been no manual input from the keypad for 10 minutes.  
Keypad and Display Module (Also Called  
The only function of this module is to allow  
the operator to communicate with the processor. It is used  
to enter configurations and set points and to read data, per-  
or LID)  
To return to automatic display, enter a t a n y t i m e .  
form tests, and set schedules. This device consists of  
a
key-  
Table 6  
Keypad and Display Module Usage  
pad with 6 function keys, 5 operative keys, 12 numeric keys  
(0 to 9, and -), and an alphanumeric g-character LCD  
FUNCTION  
K E Y S  
USE  
(liquid crystal display). See  
key usage.  
3. See Table 6 for  
STATUS  
For displaying diagnostic codes and  
STAT  
current operating information about the machine.  
HISTORY  
previous alarms.  
SERVICE  
tion information.  
For displaying run time, cycles and  
q
For entering specific unit configura-  
TEST  
proper  
For checking inputs and outputs for  
operation.  
EST  
El  
SCHEDULE  
schedules for unit operation  
For entering occupied/unoccupied  
ACCESSING FUNCTIONS AND SUBFUNCTIONS  
See  
Tables 6 8. Table 7 shows the 6 functions (identified by  
name) and the subfunctions (identified by number).  
SET POINT  
For entering operating set points  
S E T  
q
and day/time information.  
OPERATIVE  
USE  
For displaying a non-abbreviated ex-  
K E Y S  
EXPAND  
pansion of the display  
CLEAR  
For clearing the screen of all displays  
UP ARROW  
position,  
DOWN ARROW  
position.  
For returning to previous display  
c
c
l
l
For advancing to next display  
ENTER  
For entering data  
q
KEYPAD OPERATING INSTRUCTIONS (Refer to  
Table 9.)  
White keys on left side of keypad are shown and oper-  
ample: keypad entry means press the  
the white key marked  
2. The standard display uses abbreviations. Expanded in-  
ated in these instructions according to thqe following ex-  
, then  
.
formation scrolls through the display whenever  
is pressed.  
q
key  
Fig. 3  
Keypad and Display Module  
3. All functions are made up of a group of subfunctions.  
To enter a subfunction, first press subfunction number  
desired. Then press the function key in which the sub-  
function resides. To move within that subfunction, press  
SUMMARY DISPLAY  
When keypad has not been used  
for 10 minutes, display automatically switches to the rotat-  
ing summary display. This display has 4 parts, listed be-  
low, which appear in continuous rotating sequence.  
the  
q
or  
arrow. For example, a  
the Temperature Information subfunction.  
enters  
4. At any time, another subfunction may be entered by en-  
tering the subfunction number, then the function key.  
DISPLAY  
TUE  
EXPANSION  
TODAY IS TUE, TIME IS  
PM)  
5. Prior to starting unit, check leaving fluid set point for  
correct setting. Refer to Set Point Function section on  
page 39.  
CLOCK ON  
UNIT IS ON  
CLOCK SCHEDULE  
C O O L  
1
NUMBER OF STAGES IS 1  
ALARMS DETECTED  
2
ALARMS  
2
6. Depending on system configuration, all displays may not  
be shown. All displays are shown unless marked with  
the following symbol.  
AUTOMATIC DISPLAY OPERATION/DEFAULT DIS-  
PLAY In this mode, the keypad displays the current time  
format), current operating modes, cooling capac-  
ity stages, and total number of alarms.  
*Must be configured.  
For additional unit start-up procedures, see separate In-  
stallation, Start-Up and Service Instructions supplied with  
unit.  
COOL x  
MODE  
X
Day of Week  
Hour(s)  
Minute(s)  
DOW  
2 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Functions and Subfunctions  
Table  
FUNCTIONS  
Status  
Schedule  
Service  
History  
Set Point  
Test  
TESTl  
S
E
T
C
H
D
c
l
c
l
c
Run Time  
Set Points  
(Chiller Fluid)  
Automatic  
outputs  
Override  
Clock Set  
Period  
Log On and  
Log Off  
Display  
2
3
4
5
Alarm  
Display  
Compressors  
and Unloaders  
Version  
(Software)  
Starts  
Reset  
Set Points  
Factory  
Configuration  
Alarm  
History  
Demand  
Limit  
Set Points  
P e r i o d  
P e r i o d  
2
3
Field  
Configuration  
Date and  
Time  
Set Points  
(Current Operating)  
Service  
Configuration  
Period  
Period  
Period  
Period  
P e r i o d  
4
5
6
7
6
Temperatures  
Pressures  
Analog  
7
Inputs  
9
1 0  
outputs  
8
HOLIDAYS  
Table 8  
Accessing Functions and Subfunctions  
KEYPAD  
ENTRY  
DISPLAY  
RESPONSE  
DESCRIPTION  
OPERATION  
I
I
To access a function, press  
subfunction no and function  
name key. Display shows  
function  
R E S E T  
Reset Set Points  
Cooling  
Reset  
Maximum  
Maximum  
To move to other elements,  
scroll up or down using arrow  
keys. NOTE: These  
displays do not show if  
control is not configured  
for reset.  
Cooling  
Reference xx  
c
l
l
Cooling  
Reference xx  
Minimum  
xx  
Cooling  
Reference xx  
Minimum  
When the last element in a  
subfunction has been  
played, the first element is  
repeated.  
R E S E T  
Reset Set  
c
c
l
To move to next subfunction  
it is not necessary to use  
subfunction number Press  
function name key to  
display through all  
DEMAND  
D e m a n d S e t  
Points  
c
SETl  
SET l  
T I M E  
Current Time and  
Day of Week  
c
subfunctions within a  
function and then back  
to the first  
SET  
S E T  
Unit Set Points  
To move to another function,  
either depress function name  
key for desired function  
(display shows the first  
subfunction),  
X ALARMS  
Rotating Display  
Access  
ic sub-  
function by’using the sub-  
function number and the  
function name kev.  
Capacity Stages  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9  
Keypad Directory  
STATUS  
DISPLAY  
COMMENT  
KEYPAD ENTRY  
Refer to Automatic Display Operation on page 28  
Number of Tripped Alarms  
X
A L A R M S  
2 ALARMS  
ALARM X  
ALARM X  
ALARM X  
ALARM X  
ALARM X  
Displays Tripped Alarms  
Number of Modes in Effect  
X MODES  
MODE X  
MODE X  
MODE X  
MODE X  
3 MODES  
Displays Mode in Effect  
S T A G E  
Capacity  
Staging  
Information  
4 STAGE  
Number of Requested Stages  
Percent of Total Capacity  
Percent Circuit A Capacity  
Percent Circuit Capacity  
Demand Limit Set Point  
S T A G E  
C A P T  
X
X
X
CAP0 X  
L M T X *  
LOAD X*  
Load Limit Set Point  
X
X
Circuit A Compressor Relay Status  
Circuit B Compressor Relay Status  
S M Z  
X
Load/Unload Factor for Compressors  
Factor = 1 Unloader Factor = 0 6  
S E T P O I N T  
Fluid Set Point Information  
Set Point  
5
SET POINT  
x
Modified Set Point = Set Point  
Reset  
M S P  
X
TWX  
Cooler Leaving Fluid Temperature  
T E M P S  
Temperature  
Information  
6
TEMPERATURE  
EWTX  
Cooler Entering Fluid Temperature  
Cooler Leaving Fluid Temperature  
Circuit A Saturated Condenser Temperature  
Circuit A Saturated Suction Temperature  
Compressor Al Suction Temperature  
Circuit A Suction Superheat  
L W T  
X
S C T A  
S S T A  
CTA X  
SHA X  
X
X
LEGEND  
*Must be configured  
applicable  
Carrier Comfort Network  
Electronic Expansion Valve  
Maximum Operating Pressure  
CCN  
E X V  
M O P  
3 0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9  
Keypad Directory  
STATUS  
SUBFUNCTION  
TEMPERATURE  
KEYPADENTRY  
cl  
DISPLAY  
COMMENT  
Circuit B Saturated Condenser Temperature  
6
SCTB X  
Circuit  
B
Saturated Suction Temperature  
S S T B  
X
q
Compressor  
Suction Temperature  
cl  
C T B  
X
cl  
SHB X  
Circuit  
B
Suction Superheat  
RST X*  
Reset Temperature  
PRESSURE  
Refrigerant System Pressure (psig)  
Circuit A Discharge Pressure  
Circuit A Suction Pressure  
7
PRESSURE  
D P A  
S P A  
X
X
Circuit A Discharge/Suction  
Circuit A Oil Pressure Differential  
Circuit B Discharge Pressure  
x x x x  
OPA X  
DPB X  
S P B  
X
Circuit  
Suction Pressure  
Circuit B Discharge/Suction  
x x x x  
O P B  
X
Circuit B Oil Pressure Differential  
8 ANALOG  
ANALOG  
REF X  
L M T X *  
RST X*  
I N P U T  
x*  
Status of Analog Inputs  
Transducer Supply Voltage  
Demand 4-20  
Signal  
Reset 4-20  
Signal  
9
Status of Switch Inputs  
Dual Set Point Switch  
Demand Limit Switch  
Demand Limit Switch  
1
DL2 X*  
2
3 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9  
Keypad Directory  
STATUS  
SUBFUNCTION  
10 OUTPUTS  
DISPLAY  
COMMENT  
OUTPUTS  
ALMR X  
X
Status of Outputs  
Alarm Relay K3  
Fan Relay  
FRA2 X  
X
Fan Relay K2  
Fan Relay K4  
Fan Relay K5  
FRB2 X  
CHWP X*  
X
Cooler Water Pump Relay K6  
Unloader Al  
ULA2 X*  
X
Unloader  
Unloader  
ULB2 X*  
Unloader  
E X V A  
E X V B  
X
EXVA Percent Open  
EXVB Percent Open  
Hot Gas Bypass Relay Circuit A  
Hot Gas Bypass Relay Circuit B  
A Output Percent  
X
X*  
HGBB X  
M M A X *  
MMB X  
Motormaster B Output Percent  
TEST  
To use Test function, LOCAL/ENABLE-STOP-CCN switch must be in STOP position To operate a test, scroll to desired test  
Then, press to start test. Press to stop test.  
KEYPAD ENTRY  
COMMENT  
SUBFUNCTION  
OUTPUTS  
DISPLAY  
OUTPUTS  
Test Outputs  
8
8
8.8.8 8.8.8  
Display Check  
ALMR X  
X
Energize Alarm Relay K3  
Energize Fan Relay Al  
Energize Fan Relay A2 K2  
FRA2 X  
X
Energize Fan Relay  
Energize Fan Relay  
K4  
K5  
X
CHWP X*  
EXVA X  
Energize Cooler Water Pump K6  
Enter Desired EXVA Position  
E X V B  
X
Enter Desired  
Position  
HGBRA X*  
HGBRB X*  
M M A X *  
Energize Hot Gas Bypass Relay A  
Energize Hot Gas  
Enter Desired  
Relay B  
A Output Signal  
M M B X *  
Enter Desired Motormaster B Output Signal  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Keypad Directory  
TEST  
Table 9  
During compressor test, compressors start and run for  
10 seconds. Compressor service valves and liquid line  
valves must be open. Energize crankcase heaters 24 hours  
prior to performing compressor tests.  
KEYPAD ENTRY  
DISPLAY  
COMMENT  
SUBFUNCTION  
2 COMPRESSORS AND  
UNLOADERS  
C O M P  
Compressor and Unloader Test  
Test Compressor Al  
Test Compressor  
Test Compressor  
CPA1 X  
CPA2 X*  
CPA3 X*  
CPA4 X*  
Test Compressor  
Test Compressor  
Test Compressor  
Test Compressor  
X
x*  
CPB3 X*  
CPB4 X*  
Test Compressor  
X
ULA2 X*  
Energize Unloader Al  
Energize Unloader  
Energize Unloader  
Energize Unloader  
X
ULB2 X*  
SCHEDULE  
The Schedule function key  
is used to configure the occupancy schedule The clock select subfunction can be used for  
unoccupied shutdown or unoccupied setback depending on the cooling set point control configuration. The Schedule function  
described is for clock  
SUBFUNCTION  
1 OVERRIDE  
which is the internal clock. Password required for all subfunctions except override.  
DISPLAY  
OVRD X  
COMMENT  
1
KEYPAD ENTRY  
I
I
Number of Override Hrs (0 4 Hrs)  
For example, to extend current occupied mode for 3 hrs, press:  
OVRD 3  
Extended Occupied Time  
2 CLOCK SELECT  
CLOCK XX  
Type of Clock Control  
0 = No Clock, 1 = Clock 1 (Internal)  
LEGEND  
*Must be configured  
applicable.  
Carrier Comfort Network  
Electronic Expansion Valve  
Maximum Operating Pressure  
M O P  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Keypad Directory  
SCHEDULE  
Table 9  
DISPLAY  
COMMENT  
Period Time Schedule  
PERIOD  
OCC  
Occupied  
Time  
Time  
Unoccupied  
MON X  
M o n d a y F l a g  
Tuesday Flag  
T U E  
X
WED x  
THU X  
X
Wednesday Flag  
Thursday Flag  
Friday Flag  
S A T  
X
Saturday  
Sunday  
Flag  
Flag  
SUN X  
HOL X  
Holiday Flag  
To toggle between inputs (Yes/No) Press:  
4 PERIOD 2  
P
e
r
r
i
o
d PER2IODT2 i  
m
e
S
c
h
e
d
u
l
e
5 PERIOD 3 . . . 9 PERIOD 7  
P e r i o. d  
3
.
e r i o d  
7
T i m e S c h e d u l e  
P
e
i
o
dPER8IODT8 i  
m
e
S
c
h
e
d
u
l
e
10 PERIOD 8  
11 HOLIDAYS  
HOLIDAYS  
DAT  
Define Calendar Holidays  
Holiday Date  
1
New = Unassigned Holiday Date  
DAT  
NN  
Holiday Date 30  
For example: To enter July 4th holiday press: 07 04 01  
q
.
Display shows Jul 04 For further information on the Schedule function and its  
operation, refer to Schedule Function section on page 45.  
SERVICE  
To view and modify configurations, the password must be entered under the log on subfunction.  
KEYPAD ENTRY  
DISPLAY  
COMMENT  
SUBFUNCTION  
L O G O N  
Enter Password/Disable Password Protection  
1 LOG ON AND LOG OFF  
(LOGGEDON  
log out as follows:  
At this time, configurations may be modified. When finished viewing and/or modifying  
LOG OFF  
Disable Password Protection  
E X I T L O G  
Logged Off/Enable Password Protection  
VERSION  
x x x x x x x x  
X
Software  
Information  
2 VERSION  
Version No. of Software (CESRXX)  
c
l
Language  
Options  
See legend on page 30  
3 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9  
Keypad Directory  
SERVICE  
The next 3 subfunctions provide the ability to modify configurations Refer to separate Installation, Start-Up, and Service Instructions  
supplied with unit for further information  
on changing configurations.  
To change a configuration, enter the new configuration and press  
while on the correct configuration.  
DISPLAY  
COMMENT  
KEYPAD ENTRY  
3 FACTORY  
FACT CFG  
Factory Configuration Codes  
CONFIGURATION  
x x x x x x x x  
x x x x x x x x  
x x x x x x x x  
x x x x x x x x  
x x x x x x x x  
x x x x x x x x  
Configuration Code  
Configuration Code  
Configuration Code  
Configuration Code  
Configuration Code  
Configuration Code  
1
2
3
4
5
6
t
4 FIELD  
Adjustable Field Configuration  
FLD CFG  
X
CONFIGURATION  
CCN Element Address  
CCN Bus Number  
B U S  
X
BAUD X  
FLUID X  
UNITS X  
LANG X  
NULA X  
NULB X  
HGB X  
CCN Baud Rate  
Cooler Fluid Select  
t
t
Display Unit Select  
Display Language Select  
No Circuit A Unloaders  
No. Circuit B Unloaders  
Hot Gas Bypass Select  
Loading Sequence Select  
t
t
t
cl  
S E Q T  
X
t
SEQF X  
x
Lead/Lag  
Sequence  
Select  
t
q
Oil Pressure Switch Select  
Head Pressure Control Method  
Select  
t
HEADM X  
t
a
M M  
X
t
CSPTYP X  
CRTYP X  
Cooling Set Point Control Select  
Cooling Reset Control Select  
External Reset Sensor Select  
Demand Limit Control Select  
Ramp Load Select  
t
cl  
t
cl  
t
E R T Y P  
L S T Y P  
X
X
q
t
RAMP X  
LOCK X  
x
cl  
Cooler Pump Interlock Select  
Cooler Pump Control Select  
5 SERVICE  
Service Configurations  
SRV CFG  
CONFIGURATION  
x x x x x x x x  
x x x x x x x x  
X
Configuration Code  
Configuration Code  
Refrigerant  
7
8
cl  
t
Pressure Transducer Select  
Oil Transducer Set Point  
Low Pressure Set Point  
Fan Staging Select  
t
T D T Y P  
x
X
cl  
t
cl  
LPS x  
t
cl  
FANTYP X  
SH X  
cl  
q
cl  
EXV Superheat Set Point  
EXV MOP Set Point  
M O P  
X
3 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Keypad Directory  
Table 9  
DISPLAY  
COMMENT  
KEYPAD ENTRY  
SUBFUNCTION  
1 RUN TIME  
RUN TIME  
HR X  
Run Time lnformation  
Total Hrs Unit Has a Comp Operating  
HRA X  
HRB X  
Circuit  
Circuit  
A
B
Run Time  
Run Time  
c
l
Starts  
Information  
S T A R T S  
x
2
STARTS  
Cycles from Stage 0 to Stage  
Circuit A Starts  
c
c
c
l
l
l
CYA X  
CYB X  
Circuit B Starts  
Last 5 Alarms  
3 ALARM HISTORY  
I
I
I
ALARM X  
ALARM X  
ALARM X  
ALARM X  
ALARM X  
Alarm Description  
J
SET POINT  
c h a n g e  
value, t h e n  
press  
a set point, enter new set point  
To read a set point, go to proper subfunction and read desired set point To  
LOCAL/ENABLE-STOP-CCN switch must be in LOCAL or STOP position,  
COMMENT  
DISPLAY  
SUBFUNCTION  
1 SET POINTS  
KEYPAD ENTRY  
POINT  
Jnit Set Point  
x
x
Chiller Fluid Set Point  
Fluid Set Point  
1
2
H S P A  
H S P B  
X
X
Head  
Pressure Set Point Circuit  
A
Head Pressure Set Point Circuit B  
Limit  
CRAMP X  
R E S E T  
CRST2 X*  
CREF2 X*  
X*  
Reset Set Points  
2 RESET SET POINTS  
Cooling Max Reset  
Max Reset Occurs at X  
Cooling Minimum Reset  
Min Reset Occurs at X  
or Degree  
X*  
or Degree  
DEMAND  
X*  
Demand Set Points  
3 DEMAND SET POINTS  
Demand Switch  
1
Set Point  
DLS2 X*  
DMAX X*  
RMAX X*  
X*  
Demand Switch 2 Set Point  
4-20  
Maximum Demand Limit  
Max Demand Limit Occurs at X  
4-20  
Minimum Demand Limit  
Minimum Demand Limit Occurs at X  
X*  
SHED  
CCN  
Amount  
Date, Time and Day of Week  
4 DATE AND TIME  
DAY  
Day 1 = Mon, 2 = Tues  
Hours are displayed in  
7
=
Sun  
time. Decimal point serves as colon.  
MM.DD YR  
When entering date, enter a decimal  
point between entries. Each entry must be two numbers.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STATUS FUNCTION This function shows the rotating  
display, current status of alarm (diagnostic) codes, capacity  
stages, operating modes, chilled water set point, all meas-  
ured system temperatures and pressures, superheat values,  
pressure switch positions, analog inputs, and switch inputs.  
These subfunctions are defined on pages 37 and 38.  
Table 10  
Operationat and Mode Display Codes  
The operating modes are displayed by name or code num-  
ber, to indicate the operating status of the unit at a given  
time. The modes are:  
CODE  
Unit is off. LOCAL/ENABLE-STOP-CCN switch is  
( R o t a t i n g D i s p l a y )  
in OFF position, or LOCAL/ENABLE-STOP-CCN  
LOCAL OFF  
switch may be in LOCAL position with external ON/  
OFF switch in OFF position  
(Alarms)  
Alarms are messages that one or more  
Unit is off due to CCN network command. LOCAL/  
CCN OFF  
faults have been detected. Each fault is assigned  
a
code num-  
ENABLE-STOP-CCN switch is in CCN position.  
ber which is reported with the alarm. See Table 10 for code  
definitions. The codes indicate failures that cause the unit  
to shut down, terminate an option (such as reset) or result  
in the use of a default value as set point.  
Unit is off due to internal clock schedule. LOCAL/  
CLOCK OFF  
ENABLE-STOP-CCN switch is in LOCAL position.  
Unit is on. LOCAL/ENABLE-STOP-CCN switch is  
in LOCAL position If external ON/OFF switch is used,  
it will be in ON bosition.  
LOCAL ON  
CCN ON  
Up to 5 alarm codes can be stored at once. To view them  
to enter the alarm displays  
Unit is on due CCN command  
STOP-CCN switch is in CCN position.  
in sequence, pqress  
to move to the individual alarm dis-  
Unit is on due to internal clock schedule or  
CLOCK ON pied override function.  
CCN switch is in LOCAL position.  
plays. Press  
and then prqess  
after  
a
code has been displayed. The mean-  
Dual set point is in effect In this mode, unit contin-  
ues to run in unoccupied condition, but leaving wa-  
ter set point is automatically increased to a higher  
ing of the code scrolls across the screen. See Example  
M O D E  
7
level  
set  
is in SET function)  
Example 1  
Reading Alarm Codes  
Temperature reset is in effect. In this mode, unit is  
using temperature reset to adjust leaving water set  
point upward, and unit is currently controlling to the  
modified set point. The set point can be modified  
based on return water, outdoor-air temperature or  
space temperature  
K E Y P A D  
ENTRY  
DISPLAY  
RESPONSE  
MODE 8  
COMMENTS  
Keypad has not been used for  
at least 10 minutes. Alternating  
summary display appears on  
screen  
Demand limit is in effect. This indicates that ca-  
pacity of unit is being limited by demand limit con-  
trol option Because of this limitation, unit may  
not be able to produce the desired leaving water  
temperature  
0
S T A G E S  
2 ALARMS  
MODE 9  
2
alarms detected  
2
A L A R M S  
Load limit is in effect. This indicates that capacity of  
a system of units is being limited by a CCN  
shed command Due to this limitation, unit may  
not be able to produce the desired leaving water  
temperature.  
A L A R M  
9
First alarm code  
MODE 10  
MODE II  
COOLER LEAVING  
FLUID THERMISTOR Explanation of alarm code  
F A I L U R E  
Not  
Second alarm code Cooler  
A L A R M 4 2  
freeze  
protection  
Ramp load (pulldown) limiting is in effect. In this mode,  
the  
at  
leaving water temperature is dropped  
COOLER FREEZE  
P R O T E C T I O N  
Explanation of alarm code  
is limited to  
a
predetermined value to prevent com-  
MODE 12  
MODE 13  
pressor overloading, See CRAMP set point in the  
SET function in Table  
modified, if desired, to any rate from 2 F to 2 F  
to  
9
The  
limit can be  
When a diagnostic (alarm) code is stored in the display  
and the machine automatically resets, the code is deleted.  
Codes for safeties which do not automatically reset are not  
deleted until the problem is corrected and the machine is  
switched to STOP, then back to LOCAL/ENABLE or CCN.  
Timed override is in effect This is a 1 to 4 hour  
temporary override of the programmed schedule,  
forcing unit to occupied mode Override can be im-  
plemented with unit under LOCAL or CCN control  
Override expires after each use  
Low cooler suction protection is in effect In this mode,  
circuit capacity is not allowed to increase if cooler  
(Modes)  
The operating mode codes are dis-  
saturated suction temperature is  
F
C) for  
played to indicate the operating status of the unit at a given  
time. See Table 10.  
water or 30”  
F
(16” C) for brine or more below leav-  
MODE 14  
ing fluid temperature, and saturated suction tem-  
perature is less than 32 F C). If these conditions  
persist beyond 10 minutes, circuit is shut down and  
fault code 44 or 45 is displayed.  
CCN  
CarrierComfort Network  
To enter the MODES subfunction, depress  
and  
use the  
q
key to determine if more than one mode ap-  
plies. See Example 2 to read current mode with expansion.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Reading Current Operating Modes  
Example 2  
(Analog Inputs)  
analog inputs, if any. Enter  
transducer supply voltage, 4-20  
This subfunction displays  
KEYPAD  
ENTRY  
DISPLAY  
RESPONSE  
, then use the  
reset signal can be dis-  
q
. The  
COMMENTS  
I
I
Keypad has not been used for at  
least 10 minutes Rotating summary  
display appears on screen  
TUE  
played. This is useful for problem diagnosis prior to using  
LOCAL ON  
the test function.  
C O O L  
1
0
A L A R M S  
( I n p u t s )  
This subfunction displays status  
There are 2 modes currently in effect  
Unit is on by chiller on/off switch  
Temperature reset is in effect  
2 MODES  
(ON/OFF) of input switch where applicable. Status of dual  
set point switch, and demand limit switches 1 and 2 can be  
displayed. This is useful for problem diagnosis prior to us-  
ing the test function.  
LOCAL ON  
c
c
l
l
M O D E  
8
(Outputs)  
This function displays ON/OFF sta-  
tus of alarm relay, all fan relays, and chilled water pump  
relay. It also displays ON/OFF status of compressor unload-  
ers (if used). The position of each EXV (in percent open)  
can be displayed.  
This subfunction displays the capac-  
ity stage number. See Tables for compressor load-  
(Stage)  
and use the  
ing sequence. To enqter the STAGE subfunction, press  
to display the stage number.  
TEST FUNCTION The test function operates the diag-  
nostic program. To initiate test function, the LOCAL/  
ENABLE-STOP-CCN switch must be in STOP position.  
Additional provides the following information:  
Percent of total unit capacity being utilized.  
Percent of each circuit capacity being utilized.  
Demand limit set point in effect (can be any value be-  
tween 0% and 100%).  
To reach a particular test, enter its subfunction number,  
then scroll to desired test by pressing the  
key. Press  
to terminate or  
to start a test. Press  
test. Pressing the  
q
or  
q
or  
a
Load limit set point in effect. This is a CCN function for  
controlling operation of multiple units between 0% and  
100% of total capacity of all units combined.  
exit  
a
q
key after  
test has started ad-  
vances system to next test, whether current test is operating  
or has timed out, Once in the next step, you may start  
Status of each compressor relay. When a compressor is  
on, the number of that compressor is displayed. If a com-  
pressor is off, a 0 is displayed. For example: In a given  
circuit, if compressors 1 and 3 are running, and 2 and 4  
are not running, 0301 is displayed for that circuit.  
test by pressing  
or advance past it by pressing  
.
While the unit is in test, you may leave test function and  
access another display or function by pressing appropriate  
keys. However, a component that is operating when an-  
other function is accessed remains operating. You must  
Load/Unload factor for compressors. This factor is an in-  
dication of when a step of capacity is added or sub-  
tracted. Its value can range from slightly less than -1 .O  
to slightly more than 1 .O. When load/unload factor  
reaches + 1.0, a compressor is added. When the load/  
unload factor reaches -1 .O, a compressor is subtracted.  
re-enter test function and press the  
the component. Components with a timed operating limit  
time out normally even if another function is accessed.  
key to shut down  
Keypad entry  
allows the operator to make the  
If compressor unloaders are used, at  
a compressor is  
following checks by using  
LID display check.  
:
unloaded and at  
a compressor is loaded up.  
is 8.8.8.8.8.8.8.8 .  
Operation of remote alarm.  
(Set Point)  
This subfunction displays leaving  
Operation of condenser fans.  
water temperature and leaving chilled water set point. If  
unit is programmed for dual set point, the chilled water set  
point currently in effect (either occupied or unoccupied) is  
displayed. If reset is in effect, the unit operates to the mod-  
ified chilled water set point. This means the leaving water  
temperature may not equal the chilled water set point The  
modified chilled water set point can also be displayed in the  
Status function. To enter the set point subfunction, de-  
Operation of chilled water pump.  
Operation of  
To drive EXV fully open, enter  
(100% open). To drive EXV fully closed,  
(0% open).  
ter  
Keypad entry.  
compressor unloader  
accesses the compressor and  
tests.  
press  
and use the  
q
to display modified leaving  
chilled water set point followed by leaving water set point  
and actual cooler leaving fluid temperature.  
During compressor operational tests, compressor starts  
and runs for 10 seconds. Compressor service valves must  
be open. Energize crankcase heaters 24 hours prior to  
performing compressor tests.  
(Temperature)  
The temperature subfunction dis-  
plays the readings at temperature sensing thermistors.  
Since test function checks only certain outputs, it is good  
practice to also check all inputs and outputs accessible  
To read a temperature, enter  
, then scroll to de-  
key. See Table 9 for the  
sired temperature using the  
order of readouts.  
through the status function. These are located at  
,
and (see Table 9). If keypad is not used  
(Pressure)  
This subfunction displays suction,  
for 10 minutes, unit automatically leaves test function and  
resumes rotating display. See Example 3.  
discharge and net oil pressure at lead compressor of each  
circuit of unit.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
b. The next value displayed depends on how the sched-  
ule function has been programmed. (See pages  
47.) If dual set point has been selected, the next set  
Example 3  
Using Test Function  
KEYPAD  
ENTRY  
DISPLAY  
RESPONSE  
COMMENTS  
I
point after  
has been pressed is the unoccupied  
C O M P  
Factory/field test of compressors  
subfunction of test function  
chilled water set point. If single set point or inactive  
schedule  
been selected in the schedule function,  
haqs  
is pressed, the display shows the  
Circuit A, Compressor  
test  
CPA OFF  
CPA ON  
then when  
modified chilled water set point.  
Pressing starts the test:  
when the compressor should be running  
the display shows CPA1 on  
c. The final value displayed when the  
q
is pressed  
CPA 1 OFF If the test is allowed to time out (10 sec-  
onds) the display will show off  
is the cooling ramp loading rate. This is the maxi-  
mum rate at which the leaving chilled water is al-  
lowed to drop, and can be field set from 0.2 to 2.0 F  
CPA 2 OFF Pressing the down arrow key advances  
the system to Circuit A, compressor 2 test  
11” to 1.1”  
This value is not displayed  
unless the function is enabled (see Adjustable Field  
Configurations on page 45).  
NOTE: Once a compressor has been run using the  
is not allowed to run again for 30 seconds.  
function, it  
E
l
Reading and  
Set Points Example 4 shows how  
to read and change the chilled water set point. Other set  
points can be changed by following the same procedure.  
Refer to Table 9 for the sequence of display of set points in  
each subfunction.  
HISTORY FUNCTION  
sequent  
run time for each circuit.  
Keystrokes  
and sub-  
keystrokes display total unit run time and total  
Keystrokes  
and subsequent  
keystrokes dis-  
Example 4  
Reading and Changing  
.
Chilled Water Set Point  
play total unit starts and the total starts for each circuit.  
and subsequent  
alarms along with  
q
keystrokes dis-  
Keystrokes  
play the last  
DISPLAY  
RESPONSE  
KEYPAD  
E N T R Y  
C O M M E N T S  
5
a
description of each alarm.  
S E T P O I N T  
System set points  
SET POINT FUNCTION Set points are entered through  
the keypad. Set points can be changed within the upper and  
lower limits, which are fixed. The ranges are listed  
below.  
44.0  
Present occupied chilled water  
set point is 44 0 F  
420  
Chilled Water Set Point  
chilled water set point is 42 0 F  
Water:  
Present unoccupied chilled water  
set point is 44.0 F  
44.0  
50.0  
38 to 70 F (3.3 to 21 C)  
Brine:  
Press the D  
i
s
p
l
a
y
15 to 70 F (-9.4 to 21 C)  
shows new unoccupied chilled  
water set point is 50.0 F  
Set Point  
0.2 to 2.0 F (0.11 to 1.1  
R E S E T  
Displays the maximum reset and  
minimum reset set points The  
minimum and maximum reference  
reset set points can also be  
displayed.  
Reset Set Points  
Maximum Reset Range:  
to 20” F (0” to 11” C)  
These set points are not  
accessible when reset type has  
been configured for NONE in  
the service function  
Maximum Reset Reference Range:  
Return Fluid Reset  
to 20” F  
(0” to 11”  
External Temperature Reset 20 to 125 F  
Temperature Reset Based on Return Water  
(-6.6 to 51.6  
The control system is capable of providing leaving water  
temperature reset based on return water temperature. Be-  
cause the temperature difference between leaving water tem-  
perature and return water temperature is a measure of the  
building load, return water temperature reset is essentially  
an average building load reset method.  
External Signal Reset 4 to 20  
Minimum Reset Reference Range:  
Return Fluid Reset to 20” F  
(0” to 11”  
External Temperature Reset 20 to 125 F  
(-6.6 to 51.6 C)  
External Signal Reset 4 to 20  
Under normal operation, the chiller  
a constant  
leaving water temperature approximately equal to chilled  
water set point. As building load drops from 100% down to  
entering cooler water temperature drops in proportion  
to load. Thus, temperature drop across the cooler drops from  
a typical 10 F (5.5 C) at full load to a theoretical F (0” C)  
at no load. See Fig. 4.  
Demand Limit Set Points  
Switch Input:  
Step 1  
Step 2  
0 to 100% Capacity Reduction  
0 to 100% Capacity Reduction  
External Signal:  
Maximum Demand Limit 4 to 20  
At partial load, leaving chilled water temperature may be  
lower than required. If this is allowed to increase (reset),  
the efficiency of the chiller increases. Amount of reset can  
Minimum Demand Limit 4 to 20  
Set points are grouped in subfunctions as follows:  
be defined as  
a
function of cooler temperature drop, as shown  
Displays chiller water and cooling ramp set points.  
in Fig. 4. This is a simple linear function that requires 4  
pieces of input data for the set function:  
a. The first value shown is the occupied chilled water  
set point.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example  
5
Using Return Water  
Maximum Reset Amount (CRST2)  
0” to 20” F (0” to 11” C). This is maximum amount leav-  
ing chilled water set point is to be increased.  
allowable range  
Temperature Reset  
KEYPAD  
ENTRY  
DISPLAY  
RESPONSE  
2. Maximum Reset Reference (CREF2) allowable range  
0” to 20” F (0” to 11” C). This is the cooler temperature  
drop at which reset reaches its maximum value.  
COMMENTS  
Field configuration  
subfunction of  
service function  
FLD CFG  
3. Minimum Reset Amount  
allowable range  
C). This is minimum amount leav-  
to F (0” to  
C S P T Y P  
X
Scroll past single/dual  
ing chilled water set point is to be increased when reset  
is initiated.  
Display shows no reset  
type has been selected  
CRTYP 0  
4. Minimum Reset Reference (CREFl)  
allowable range  
Return water temperature  
is selected and activated  
0” to 20” F (0” to 11” C). This is the cooler temperature  
drop at which reset is at its minimum value. (Reset be-  
gins here  
C R T Y P  
1
S E T P O I N T  
44.0  
System set points  
NOTE: Reset set points are not accessible unless the reset  
function is enabled first. This is done as a field configura-  
tion. Select one of the 3 choices for type of reset: Return  
Fluid Reset, External Temperature Reset, or 4-20  
ternal Signal (with a loop isolator) Reset.  
Present occupied chilled  
water set point  
Enter new chilled water  
set point  
45 6  
Ex-  
Reset set points  
maximum reset  
R E S E T  
If dual set point control is enabled (see Field Wiring sec-  
tion on page 7 1), the amount of reset is applied to which-  
ever set point is in effect at the time.  
Example 5 demonstrates how to activate reset. Example  
6 demonstrates how to change the type of reset. Assume  
that reset is to be based on return water temperature, the  
desired reset range is to be 2” to 10” F (1” to 5.5” C) and  
full load is a 10” F (5.5” C) drop across the cooler. See  
Fig. 4.  
C R S T 2  
0
0
Cooling maximum reset  
is 10 F  
C R S T 2 1 0  
0
Cooling maximum reset  
CREF2 0.0  
CREF2 1.0  
0 0  
reference is 0” F  
Cooling maximum reset  
reference is 1 F  
Cooling minimum reset  
is  
F
Activating reset based on external temperature or  
Cooling minimum reset  
2.0  
4-20  
signal is done the same way, except the reference  
is 2 F  
set point range is 20” to 125” F (-6.6” to 5 1.6” C), or 4 to  
Cooling minimum reset  
reference is 0” F  
CREFl 0.0  
8 0  
20  
depending on which method was selected at the field  
configuration step.  
Cooling minimum reset  
reference is  
F
9
8
7
I
q
13  
8 0  
6 0  
0
2
3
4
5
6
7
8
9
RESET REFERENCE TEMPERATURE (COOLER EWT-LWT)  
Fig.  
4
Cooling Return Water Reset  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example 6  
Changing Reset Type  
Temperature Reset Based on External Temperature If de-  
sired, temperature reset can be based on an external tem-  
perature, such as space or outdoor-air temperature. This re-  
To change type of reset, first log on as shown in  
Table 11. Also refer to Set Point Function section, page 39,  
for information on entering reset set points using reset  
feature.  
quires a thermistor  
Part No.  
located in  
the space or outdoor air and wired to terminals as follows  
(also see Field Wiring section on page 71):  
KEYPAD  
ENTRY  
DISPLAY  
RESPONSE  
COMMENTS  
4 in/4 out Module  
and  
Field configuration  
subfunction of  
service function  
At the field configuration step, select external tempera-  
FLD CFG  
ture reset by entering  
q
when CRTYP  
0
appears. Then  
Scroll past single cooling  
set point  
C S P T Y P  
0
enter set points as described previously in Example 5. See  
Fig. 5.  
No reset has been  
selected  
CRTYP 0  
Temperature Reset Based on 4-20  
Signal- If desired,  
signal. For  
Return water temperature  
reset is selected and  
activated  
CRTYP  
1
temperature reset can be based on a 4-20  
refer to Field Wiring section on page  
proper connections,  
71 and Fig. 6.  
Reset type is changed to  
space or outdoor-air  
temperature reset and  
activated  
CRTYP 2  
reset by  
entering  
At thqe field configuration step, select 4-20  
when CRTYP  
0
appears. Then enter set points  
Reset type is changed to  
as described previously in Example 5. See Fig.  
CRTYP 3  
CRTYP 0  
4-20  
signal reset  
and activated  
Demand Limit, 2-Stage Switch Control This control has  
Reset is deactivated  
been designed to accept demand limit signals from a build-  
ing load shedding control. The demand limit function pro-  
vides for 2 capacity steps. The keypad is used to set the 2  
demand limit set points, which range from 100 to 0% of  
capacity. Capacity steps are controlled by 2 field-supplied  
relay contacts connected to the designated chiller terminals.  
(See Field Wiring section on page 7 1 and Fig. 6.)  
RESET REFERENCE TEMPERATURE  
AIR OR  
Cooling External Temperature Reset  
Fig. 5  
4 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
P O I N T NUMBER OF  
FIRST CHANNEL  
P
W
R
4
I
RET  
DO+  
c
D
LIMIT  
C O D E 3 1 2  
LEGEND  
COMM  
PWR  
SW  
Communications Bus  
Power  
Switch  
NOTE: For specific connection points,  
see Fig. 24 29.  
(ALARM  
(MODE  
4 IN/4 OUT Options Module Wiring for Reset, Demand Limit,  
Dual Set Point  
Fig 6  
To use Demand Limit, first enable loadshed, then enter  
demand limit set points. See Example 7A. Closing the first  
stage demand limit contact puts unit on the first demand  
limit level, that is, the unit does not exceed the percentage  
of capacity entered as demand limit stage 1. Closing con-  
tacts on second-stage demand limit relay prevents unit from  
exceeding capacity entered as demand limit stage 2. The  
demand limit stage that is set to the lowest demand takes  
priority if both demand limit inputs are closed.  
The demand limit function must be enabled in order to  
function and may be turned off when its operation is not  
desired. The demand limit relays can, in off condition, re-  
main connected without affecting machine operation.  
Table 11  
Service Functions  
To view and modify configurations, the password must  
be entered under the log on subfunction.  
KEY FAD  
E N T R Y  
COMMENT  
DISPLAY  
F U N C T I O N  
I
Enter Password/  
P A S S W O R D  
Disable  
Password  
LOGGED ON Logged On  
NOTE: Configurations may be modified at this time. When  
finished viewing and/or modifying configurations, log out  
as follows:  
-Demand Limit, 4-20  
Signal  
The controls can also  
accept a 4-20  
signal for load shedding. Input for the  
L O G G E D O N  
signal are terminals shown below:  
Disable  
Protection  
Password  
Externally powered (loop isolator required)  
L O G O F F  
Positive lead to  
Negative lead to  
4 In/4 Out Module  
4 In/4 Out Module  
Logged Off/  
LOG  
Enable  
Password  
Protection  
Int erna lly pow ered  
Positive lead to  
Negative lead to  
4 In/4 Out Module  
4 In/4 Out Module  
Software  
Information  
V E R S I O N  
xxxxxxxx  
X
Version  
of Software  
No  
See Field Wiring section on page 71 and Fig. 6.  
entering  
At fielqd configuration step, select 4-20  
when the LSTYP 0 display appears. See  
by  
Language  
Options  
Example 7B. Then enter set points as follows. In this ex-  
ample, set points are coordinates of the demand limit curve  
shown in Fig. 8.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
16  
8
6
0
0
2
4
6
8
18  
2 0  
RESET REFERENCE SIGNAL  
-20 MA INPUT)  
Fig. 7  
4-20  
Cooling Temperature Reset  
Using Demand Limit (4-20  
Example  
(First Log On As Shown in Table 11)  
Example 7A  
(First Log On as Shown in Table 11)  
Using Demand Limit  
KEYPAD  
ENTRY  
DISPLAY  
RESPONSE  
KEYPAD  
ENTRY  
DISPLAY  
RESPONSE  
COMMENTS  
COMMENTS  
Field configuration subfunction  
of service function  
Field configuration sub-  
function of service function  
FLD CFG  
FLD CFG  
ERTYP  
LSTYP  
Scroll past other elements in  
the subfunction  
Scroll past other elements  
in the subfunction  
E R T Y P  
LSTYP  
LSTYP  
0
is not enabled  
is now enabled  
is not enabled  
is now enabled  
for 2-stage switch control  
2
L S T Y P  
1
q ‘n  
for 4-20  
signal control  
Demand Limit set points  
subfunction of set point  
function  
DEMAND  
Demand Limit set points  
DEMAND  
Maximum demand limit is 100%  
Maximum demand limit is 90%  
D M A X 1 0 0  
1 currently set  
100  
60  
a t 1 0 0 %  
D M A X 9 0  
reset to 60%  
Maximum demand limit  
reference is 20  
RMAX 20  
2 currently set  
D L S 2 1 0 0  
DLS2 40  
a t 1 0 0 %  
Maximum demand limit  
reference is 15  
R M A X 1 5  
2 reset to 40%  
0
Minimum demand limit is 0%  
Minimum demand limit is 20%  
20  
4
To Disable Demand Limit:  
Minimum demand limit  
reference is 4  
KEYPAD  
ENTRY  
DISPLAY  
COMMENTS  
RESPONSE  
Minimum demand limit  
reference is 6  
6
Field configuration sub-  
function of servicefunction  
FLD CFG  
Scroll past other elements  
E R T Y P  
L S T Y P  
LSTYP  
0
1
in the subfunction  
is enabled for  
2-stage switch control  
is now disabled  
0
NOTE: Select 3 for Carrier comfort Network (CCN) load limiting  
Select  
4
for CCN demand limiting.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
= 90  
M A X D E M A N D  
DEMAND  
SIGNAL (4-20 MA INPUT)  
Fig. 8  
4-20  
Demand Limiting  
Off  
The service function is  
Reading and Changing Time Displav  
and displayed in 24-hour time. The day of the week is  
tered as a number.  
Time is entered  
word protected. Therefore, to gain entry to this function,  
this password must be entered. Pressing  
allows the technician to view, change or enter  
tion codes. To log off, perform the following keystrokes:  
1 = Mon, 2 = Tue, 7 = Sun, etc.  
is used as the colon when entering time. See  
8.  
The service function is once again  
word protected.  
Setting Time of Day and  
Day of Week  
Example 8  
Software Information  
number of the software that resides in the processor mod-  
ule. Press a second time to display the language op-  
tions that are available in the field configuration group.  
T h e a n d su b f ions are summarized in  
Table  
displays the version  
KEYPAD  
ENTRY  
DISPLAY  
COMMENTS  
RESPONSE  
Time display sub-  
function of set point  
function  
T I M E  
Current setting is  
Monday, 4:00  
MON 1600  
New setting of  
Tuesday,  
p m  
Configuration Codes  
allows entry into  
TUE 13 05  
is entered  
and displayed  
the factory configuration subfunction. Under this subfunc-  
Current date is  
Jan. 1, 1990  
tion, there are  
6
groups of configuration codes that are down-  
JAN 01 90  
loaded at the factory. Each group is made up of 8 digits. If  
processor module is replaced in the field, these 6 groups of  
configuration codes must be entered through the keypad and  
New setting  
April 15, 1990  
is entered  
APR  
90  
display module. Factory configuration codes (groups  
1
through  
and displayed  
6) that apply to the particular Flotronic’” II chiller being  
serviced are found on a label diagram located inside the  
control box cover. See Table 12 for a summary of factory  
configuration subfunction keystrokes.  
SERVICE FUNCTION  
This function allows the  
to view and input configuration data. Factory  
uration data, field configuration data and service configu-  
ration data may be viewed or entered through the keypad  
and display module. See Table 9 for a complete listing of  
configurable items. Whenever a processor module is re-  
placed in the field, the complete list of configuration codes  
must be entered.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Adjustable Field Configurations  
Table 13  
Factory Configuration Keystrokes  
To change a configuration enter the new configuration  
Table 12  
SERVICE  
C O D E  
FACTORY  
ITEM AND CODES  
address  
and press  
q
while on the correct configuration.  
CCN  
001  
001  
(Entered by CCN Technician)  
S UB-  
F U N C T I O N  
DISPLAY  
COMMENTS  
CCN Bus Number  
0 0 0  
9 6 0 0  
0 0 0  
9 6 0 0  
(Entered by CCN Technician)  
F A C T O R Y  
C O D E S  
CCN Baud Rate  
3 FACTORY  
FACT CFG  
(Entered by CCN Technician)  
C F G  
Cooler Fluid Select  
=
Standard Models  
1
=
Water (38 to 70  
F
xxxxxxxx  
xxxxxxxx  
xxxxxxxx  
xxxxxxxx  
xxxxxxxx  
xxxxxxxx  
1
to 21 C] Set Point)  
Medium Brine (15 to 70  
f-9 to 21 C] Set Point)  
= Brine Models  
2
=
F
Unit Select  
English  
1 = Metric  
0
0
Configuration  
C o d e  
0
=
3
Display Language Select  
Configuration  
C o d e  
1
1
English  
4
No. Circuit  
A
Unloaders  
=
=
0
=
=
No Unloaders  
One Unloader  
Two Unloaders  
0
1
2
No.  
B
Unloaders  
190-210';  
0
No Unloaders  
One Unloader  
Two Unloaders  
0
0
S E R V I C E  
1
S R V C F G  
2
=
=
Hot Gas Bypass Select  
No Valve  
0
0
=
xxxxxxxx  
xxxxxxxx  
Loading Sequence Select  
1
1
=
Equal Circuit Loading  
Staged Circuit Loading  
2
=
Sequence Select  
L1e=adA/Luatgomatic  
Pressure Switch Select  
Not Used  
Air Cooled  
0
0
0
0
=
=
Adiustable Field Configurations After logging on, press  
to enter subfunction. The subfunction allows oper-  
ation of the chiller to be customized to meet the particular  
needs of the application. The chiller comes from the fac-  
1
Head Pressure Control Type  
0
1
=
=
Not Used  
Air Cooled  
Head Pressure Control Method  
1
=
EXV Controlled  
2
Set Point Control for  
Both Circuits  
tory  
to meet the needs of most applications.  
Each item should be checked to determine which configu-  
ration alternative best meets the needs of a particular appli-  
cation. See Table 13 for factory loaded configuration codes  
and alternative configurations.  
3
=
Set Point Control for  
Circuit A; EXV Control  
1
for Circuit  
B
4
=
Set Point Control for  
Circuit B; EXV Control  
for Circuit  
A
If processor module is replaced, the replacement module  
is preloaded with factory default configuration codes. Each  
configuration code must be checked and, if necessary, re-  
configured to meet needs of the application. See  
Table 13 for pre-loaded service replacement configuration  
codes.  
Cooling Set Point  
Control Select  
0
1
=
=
Single Set Point Control  
External Switch  
0
0
0
0
Controlled Set Point  
Clock Controlled  
Set Point  
2
Cooling Reset  
Select  
Control  
0
2
3
=
No Reset  
to enter the  
Service Configuration Codes Press  
=
Return Fluid Reset  
=
External Temperature  
service configuration subfunction. The first 2 items under  
this subfunction are 2 groups (8 digits each) of configura-  
tion codes that are downloaded at the factory. If processor  
module is replaced in the field, the 2 groups of configura-  
tion codes must be entered through the keypad and display  
module. The 2 groups of configuration codes (groups 7 and  
8) that apply to the unit being serviced can be found on a  
label diagram inside the control box cover. See Table 12  
for keystroke information to enter configuration codes 7  
and 8.  
Reset  
=
4-20  
Controlled  
Reset  
External Reset Sensor Select  
0
=
Thermistor Connected to  
Options Module  
Obtained Through CCN  
0
0
0
0
1
=
Demand Limit Control Select  
0
=
=
No Demand Limiting  
1
Two External Switch Input  
0
2
= External 4-20  
CCN Load Limiting  
(Multi-Unit)  
3
4
CCN  
Interface  
Ramo Load Select  
SCHEDULE FUNCTION This function provides a means  
to automatically switch chiller from an occupied mode to  
an unoccupied mode, When using schedule function, chilled  
water pump relay must be used to switch chilled water pump  
on and off. Connections for chilled water pump relay are:  
1
Enabled  
Cooler Pump Interlock Select  
0
0
0
1
=
=
No Interlock  
With Interlock  
and  
and  
(040-210 and associated modular units)  
(225, 250, and 280 units). The chilled  
Cooler Pump Control Select  
0
1
=
=
Not Controlled  
or  
ON/OFF Controlled  
water pump relay starts chilled water pump but compres-  
sors do not run until remote chilled water pump interlock  
L E G E N D  
Carrier Comfort Network  
Electronic Expansion Valve  
contacts are between  
and associated modular units, or between  
on 250, and 280 units are closed and  
and  
on  
and  
*And associated modular units  
leaving chilled water temperature is above set point. If a  
remote chilled water pump interlock is not used, the first  
compressor starts (upon a call for cooling) approximately  
one minute after chilled water pump is turned on.  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example  
9
The schedule function can be programmed for inactive,  
single set point, or dual set point operation.  
When schedule is configured for inactive, chilled water  
pump relay remains energized continuously but is not used  
since chiller is usually controlled by remote chilled water  
pump interlock contacts.  
Using the Schedule Function  
DISPLAY  
No  
schedule  
override  
O V R D  
O V R D  
O V R O  
C L O C K  
C L O C K  
0
3
0
in effect  
3
hours override in effect  
When unit is configured for single set point operation,  
chilled water pump relay is energized whenever chiller is in  
occupied mode regardless of whether chiller is running. When  
chiller is in unoccupied mode, chilled water pump relay is  
not energized.  
Override cancelled  
0
Schedule function is inactive  
Schedule function is enabled  
through local unit clock  
1
When unit is configured for dual set point, chilled water  
pump relay is energized continuously, in both occupied and  
unoccupied modes. Occupied mode places occupied chilled  
water set point into effect; unoccupied mode places unoc-  
cupied chilled water set point into effect.  
Schedule function is enabled  
throuah CCN clock 65  
C L O C K 6 5  
Define schedule period  
Start of occupied time  
1
PERIOD  
1
For this example, first  
period should stat-t here  
so no entry  
The schedule consists of from one to  
8
occupied time pe-  
riods, set by the operator. These time periods can be flagged  
to be in effect or not in effect on each day of the week. The  
Start of unoccupied time  
(end of period) For this  
period 1 should  
day begins at 00  
and ends at 24.00. The machine is in  
00.00  
unoccupied mode unless a scheduled time period is in ef-  
fect, If an occupied period is to extend past midnight, it  
must be programmed in the following manner: occupied pe-  
end at 3:00  
Period ends at 3:00  
Monday is now flagged no  
a
m.  
1
a
m
riod must end at  
hours (midnight); a new occupied  
period must be programmed to begin at  
hours.  
for  
1 To out  
M O N N O  
into’ effect on  
NOTE: This is true only if the occupied period starts at  
(midnight). If the occupied period starts at a time  
other than midnight, then the occupied period must end at  
hours (midnight) and new occupied period must be  
Monday must be flagged  
Monday is now fla ged for  
period to be in e ect  
M O N Y E S  
TUE YES  
T U E N O  
For this example, period  
is to be in effect on Monday  
only All other days must  
checked to be sure that thev  
are flagged no. If any day  
flagged yes, change to no  
programmed to start at  
in order for the chiller to stay  
in the occupied mode past midnight.  
The time schedule can be overridden to keep unit in oc-  
cupied mode for one, 2, 3 or 4 hours on a one-time basis.  
See Example 9.  
Tuesday is now flagged  
no for period  
All subfunctions of schedule function are password pro-  
tected except the override subfunction,  
.
P E R I O D  
2
Define schedule period  
2
word entry into subfunctions through  
is done through service function. See page 44, logging on/  
logging off.  
occ 00 00 Start of occupied  
will start  
occ 7 00  
00.00  
Figure 9 shows a schedule for an office building with the  
chiller operating on a single set point schedule. The sched-  
ule is based on building occupancy with a 3-hour off-peak  
cool-down period from midnight to 3 a.m. following the  
weekend shutdown. To learn how this sample schedule would  
be programmed, see Example 9.  
NOTE: This schedule was designed to illustrate the pro-  
gramming of the schedule function and is not intended as a  
recommended schedule for chiller operation.  
Start of unoccupied time  
(end of period) For this  
example, period 2 should  
end at 18:00 (6:00  
p
m
)
Period  
(6:00  
2
m
ends at 18:OO  
)
18 00  
p
Monday is now flagged no  
for period 2 To put period 2  
into effect on Monday,  
M O N N O  
MON YES  
Monday must be flagged yes  
Monday is now flagged for  
period  
2
to be in effect  
Tuesay is now flagged no  
for period 2 To put period 2  
into effect on Tuesday,  
T U E N O  
Tuesday must be flagged  
Tuesday is now flagged for  
TUE YES  
period  
2
to be in effect  
For this example, period  
is to be in effect only on  
2
Monday  
and  
Tuesday  
All other days must be  
checked to be sure that  
they are flagged no. If  
W E D Y E S  
a
day is flagged yes,  
change to no  
Wednesday is now flagged  
no for period  
W E D N O  
2
Carrier Comfort Network  
Example  
CCN  
9
continued next page.  
4 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Holiday Schedule Function  
Example 10  
Example 9  
Using the Schedule Function  
D I S P L A Y  
H O L I D A Y  
E N T E R  
COMMENT  
D I S P L A Y  
PROGRAMMING PERIOD 3:  
JAN01 02 (Includes Jan  
and 2nd)  
Define  
period  
schedule  
3
P E R I O D  
occ  
3
Start of occupied  
lime  
01 (Includes April 17th)  
MAY21 01 (Includes May 21 st)  
JUL03 01 (Includes July 3rd)  
JULO4 01 (Includes July 4th)  
SEP07 01 (Includes Sep 7th)  
will start  
occ 7 00  
Start of unoccupied time  
(end of period 3). For this  
example, period  
end at  
00 00  
21 30  
3
should  
p m )  
Period 3 ends at  
p
m
)
Check to be sure that  
Monday and Tuesday are  
flagged for period  
M O N N O  
3
02 (Inclu2d7eths) Nov 26th  
and  
TUE NO  
W E D N O  
W E D Y E S  
T H U R N O  
FRI NO  
DEC24 02 (Includes  
24th  
Wednesday  
no, change to yes  
is  
flagged  
and 25th)  
02 (includes  
and  
30th  
W e d n e s d a y i s n o w  
flagged yes for period  
3
Check to be sure that all  
other days are flagged no  
N
E
W
MAY25 01 (Includes May 25th)  
SAT NO  
SUN NO  
N E W  
N E W  
N E W  
Period 4 and 5 can be programmed in the same manner,  
flagging Thursday and Friday yes for period 4 and Saturday  
yes for period 5 For this example, periods 6, 7, and 8 are  
not used: they should be programmed OCC 00.00,  
00.00.  
NOTE: When a day is flagged yes for 2 overlapping peri-  
ods, occupied time will take precedence over unoccupied  
time. Occupied times can overlap in the schedule with no  
consequence.  
N E W  
NEW (30TH  
NEW indicates a holiday that has not been assigned yet.  
To extend an occupied mode beyond its normal termina-  
tion for a one-time schedule override, program as shown  
below:  
I
2 -  
3 -  
4 -  
5 -  
8 -  
9 -  
II  
Holidav Schedule  
Press  
to schedule up to  
30 holiday periods. All holidays are entered with numerical  
values. First, the month (01 to  
then the day (01 to 3  
‘ERIO  
3
then the duration of the holiday period in days.  
Examples: July 24 is  
25 26 is 12.25.02  
If any of the 30 holiday periods are not used, the display  
shows NEW.  
1 9  
20  
See Example 10.  
OCCUPIED  
UNOCCUPIED  
Sample Time Schedule  
Fig. 9  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13. Cooler entering or leaving fluid thermistor failure  
14. Low transducer supply voltage  
TROUBLESHOOTING  
The  
II control has many features to aid the  
technicians in troubleshooting a Flotronic II Chiller. By us-  
ing keypad and display module and status function, actual  
operating conditions of the chiller are displayed while unit  
is running. Test function allows proper operation of com-  
15. Loss of communications between processor module and  
other control modules  
16. Low refrigerant pressure  
pressors, compressor unloaders, fans,  
and other com-  
Single Circuit Stoppage  
can be caused by the following:  
Single circuit stoppage  
ponents to be checked while chiller is stopped. Service function  
displays how configurable items are configured. If an op-  
erating fault is detected, an alarm is generated and an  
1
Low oil pressure in lead compressor  
2. Open contacts in lead compressor high-pressure switch  
3. Low refrigerant pressure  
4. Thermistor failure  
alarm code(s) is displayed under the subfunction  
,
along with an explanation of the fault. Up to 5 current alarm  
codes are stored. For checking specific items, see Table 9.  
5. Transducer failure  
6. Ground fault in lead compressor indicator (indicator is  
Checking Display Codes  
To determine how ma-  
chine has been programmed to operate, check diagnostic  
field-supplied on 040-060, 070  
associated modular units)  
Hz],  
110, and  
information  
and operating mode displays  
If no  
ules  
follows:  
follow procedures in Control Mod-  
64. If display is working, continue as  
7. High suction superheat  
8. Low suction superheat  
9. Lead compressor circuit breaker  
Stoppage of one  
Note all alarm codes displayed,  
2. Note all operating mode codes displayed,  
3. Note leaving chilled water temperature set point in ef-  
fect and current leaving water temperature,  
.
circuit by a safety device action does not affect other  
circuit. When a safety device trips on a lead compres-  
sor, circuit is shut down immediately and EXV closes.  
.
10. Ground fault for any circuit compressor  
250, 280, and associated modular units).  
.
If machine is running, compare the “in effect” leaving  
water temperature set point with current water tempera-  
ture. Remember, if reset is in effect, the values may be  
different because machine is operating to the modified  
chilled water set point, If current temperature is equal to  
set point, but set point is not the one desired, remember  
that if dual set point has been selected in the schedule  
Lag Compressor Stoppage  
Lag compressor stop-  
page can be caused by the following:  
Open contacts in high-pressure switch  
2. Compressor ground fault (indicator is field-supplied on  
040-060, 070  
units)  
Hz],  
110, and associated modular  
function, there are  
2
set points to which the machine can  
3. Compressor circuit breaker trip  
be operating. Check the programming of schedule func-  
tion to see if occupied or unoccupied set point should be  
in effect.  
Not required to run to meet cooling load requirement  
Unit Shutoff  
To shut unit off, move LOCAL/  
If stoppage occurs more than once as a result of any of  
the above safety devices, determine and correct the cause  
before attempting another restart.  
ENABLE-STOP-CCN Switch to STOP position. Any re-  
frigeration circuit operating at this time continues to com-  
plete the  
cycle. Lag compressors stop immediately,  
and lead compressors run to complete  
After cause for stoppage has been  
corrected, restart is either automatic or manual, depending  
Restart Procedure  
Complete Unit Stoppage  
page can be caused by any of the following conditions:  
Complete unit stop-  
on fault. Manual reset requires that  
STOP-CCN switch be moved to STOP position, then back  
to original operating position. Some typical fault conditions  
are described below. For a complete list of fault conditions,  
codes, and reset type, see Table 14.  
1. Cooling load satisfied  
2. Remote ON/OFF contacts open  
3. Programmed schedule  
4. Emergency stop command from CCN  
5. General power failure  
POWER FAILURE EXTERNAL TO THE UNIT  
restarts automatically when power is restored.  
Unit  
6. Blown fuse in control power feed disconnect  
7. Open control circuit fuse  
Typical Stoppage Faults and Reset Types  
Chilled Water, Low Flow  
Manual reset  
8. LOCAL/ENABLE-STOP-CCN switch moved to STOP  
Chilled Water, Low Temperature Auto reset first time, manual  
position  
if repeat  
9. Freeze protection trip  
10. Low flow protection trip  
Chilled Water Pump Interlock  
Control Circuit Fuse Blown  
High-Pressure Switch Open  
Low Refrigerant Pressure  
Low Oil Pressure  
Manual reset  
Unit restarts automatically when  
power is restored  
11. Open contacts in chilled water flow switch (optional)  
12. Open contacts in any auxiliary interlock. Terminals that  
Manual reset  
Auto reset first time, then manual  
if within same day  
are  
from factory are in series with control  
switch. Opening the circuit between these terminals places  
unit in stop mode, similar to moving the control switch  
to STOP position. Unit cannot start if these contacts  
are open. If they open while unit is running, unit pumps  
down and stops.  
Manual reset  
Gas Thermostat Open Manual reset  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
pressor, energizes alarm light, and displays a code of  
3, 4, 5, 6, 7, or 8 depending on the compressor. Compres-  
sor locks off; to reset, use manual reset method.  
Alarm Codes  
Following is a detailed description of  
each alarm code error and possible cause. Manual reset of  
an alarm is accomplished by moving  
STOP-CCN Switch to STOP position, then back to LO-  
CAL or CCN position. See Table 14 for listing of each alarm  
code.  
If lead compressor in  
pressors in the circuit stop and lock off. Only the alarm  
mode for lead compressor is displayed.  
The microprocessor is also programmed to indicate com-  
pressor failure if feedback terminal on DSIO-LV or -EXV  
terminal strip receives voltage when compressor is not  
supposed to be on.  
a
circuit shuts down, the other com-  
Code 0  
No alarms exist  
Codes 1 8 Compressor failure  
If DSIO-LV or -EXV relay module control relay feed-  
back switch or signal is sensed as open during operation of  
a compressor, microprocessor detects this and stops com-  
Table 14  
Alarm Codes  
ACTION TAKEN  
B Y C O N T R O L  
C K T  
D E S C R I P T I O N  
No Alarms Exist  
PROBABLE CAUSE  
DISPLAY  
0
1
Compressor Al failure  
Circuit  
A
shut down  
No  
Manual  
High-pressure switch trip, discharge gas  
thermostat trip, or wiring error  
Manual  
Manual  
Manual  
CPCS Ground Fault Protection  
Compressor A2, A3, A4 failure  
Compressor  
Circuit  
Compressor  
shut  
down  
Yes  
2, 3,  
5
4
Compressor  
Compressor  
failure  
B
shut down  
No  
failure  
shut  
down  
7,  
9
A u t o  
A u t o  
A u t o  
A u t o  
A u t o  
Leaving water thermistor failure  
Entering water thermistor failure  
Compressor Al sensor failure  
Unit shut down  
Unit shut down  
Yes  
Yes  
Yes  
Yes  
N o  
1 0  
1 9  
2 0  
2 1  
Thermistor or transducer failure  
or wiring error.  
Circuit  
Circuit  
A
B
shut down  
shut down  
Compressor  
sensor failure  
Reset thermistor failure  
Normal set point used  
Circuit  
Circuit  
Circuit  
Circuit  
Circuit  
Circuit  
A
B
A
B
A
B
shut down  
shut down  
shut down  
shut down  
shut down  
shut down  
Auto.  
A u t o  
A u t o  
Auto.  
Auto.  
A u t o  
2 2  
2 3  
2 4  
2 5  
2 6  
2 7  
Discharge pressure transducer failure, circuit  
Discharge pressure transducer failure, circuit  
A
B
Yes  
N o  
N o  
N o  
N O  
Suction pressure transducer failure, circuit  
Suction pressure transducer failure, circuit  
A
Transducer failure or wiring error  
B
Oil pressure transducer failure, circuit  
Oil pressure transducer failure, circuit  
A
Unit shut down  
Unit shut down  
N o  
N o  
A u t o  
Unit voltage low or PSI faulty  
Chilled water pump inoperative  
2 8  
2 9  
Transducer supply voltage low  
Interlock switch oaen  
M a n u a l  
4-20  
reset input failure  
Normal set point used  
Demand limit ignored  
Unit shut down  
N o  
N o  
N o  
A u t o  
A u t o  
Auto.  
3 0  
demand limit failure  
Wiring error or faulty module  
3 2  
Loss of communication with DSIO-LV  
or improper address  
code  
Unit shut down  
Unit shut down  
N o  
A u t o  
A u t o  
3 3  
3 4  
Loss of communication with DSIO-EXV  
Loss of communication with  
Not used  
4
Out module  
Yes  
3 5  
3 6  
I
Low refrigerant pressure circuit  
A
B
No  
No  
Low refrigerant charge, plugged filter  
drier, faulty EXV  
*
3 7  
Low refrigerant pressure circuit  
Low refri erant charge, plugged filter  
drier. fau tv EXV  
No  
No  
Manual  
Faulty EXV, transducer, or thermistor  
Faultv EXV, transducer, or thermistor.  
3 8  
3 9  
4 0  
M a n u a l  
oil pressure circuit  
oil pressure circuit  
A
Circuit  
Circuit  
A
B
shut down  
shut down  
N o  
Manual  
Manual  
Low oil level, circuit breaker trip,  
faulty EXV, crankcase heater,  
or Pressure Transducer  
4 1  
B
No  
Low oil level, circuit breaker trip,  
fautty EXV, crankcase heater,  
or  
transducer  
4 2  
4 3  
Cooler  
freeze  
protection  
Unit shut down  
Unit shut down  
No  
No  
Low water flow or faulty thermistor  
Low cooler water flow  
Manual  
Manual  
M a n u a l  
Chilled water pump failure  
or faulty thermistor  
No  
Faulty EXV or thermistor  
4 4  
4 5  
Low suction temperature circuit  
Low suction temperature circuit  
A
B
Circuit  
A
shut down  
after 10 minutes  
Circuit  
afler  
B
shut down  
N o  
Faulty EXV or thermistor  
minutes  
4 6  
4 7  
High suction superheat circuit  
High suction superheat circuit  
A
B
Circuit  
A
shut down  
Yes  
Yes  
Manual  
Manual  
Low charge, faulty EXV or  
thermistor, or plugged filter drier  
Low charge, faulty EXV or  
thermistor, or plugged filter drier.  
Circuit  
B
shut down  
M a n u a l  
Faulty EXV or thermistor  
Faultv EXV or thermistor  
4 8  
4 9  
Low suction superheat circuit  
Low suction superheat circuit  
A
Circuit  
A
shut down  
Yes  
Yes  
B
Circuit shut down  
Manual  
Manual  
M a n u a l  
C C N  
Configuration  
Configuration  
error  
Illegal  
configuration  
Unit cannot start  
Unit cannot start  
Unit shut down  
omitted  
5 1  
Initial configuration required  
Network  
command.  
Emergency stop by CCN command  
Yes  
5 2  
L E G E N D  
*Reset automatic first time, manual if repeated same day  
Compressor Protection Control Module  
Power Supply  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
and circuit start-up follows normal sequence. Cause of  
fault is usually a bad thermistor, wiring error or loose  
connection.  
Possible causes of failure:  
High-Pressure Switch Open High-pressure switch for  
each compressor is wired in series with 24-v power that  
energizes compressor control relay. If high-pressure switch  
opens during operation, compressor stops. This is  
detected by microprocessor through the feedback  
terminals.  
On units with transducers, if the saturated suction tem-  
perature is greater than the leaving water temperature plus  
10” F (5.5 C) for more than 5 minutes, the affected circuit  
shuts down (after going through normal pumpout). The re-  
set is automatic if the saturated suction temperature returns  
to the acceptable range and start-up follows the normal se-  
quence. Cause of this fault is usually a bad transducer, a  
wiring error, or a loose connection.  
DSIO-LV or DSIO-EXV Module Failure If a DSIO-LV  
relay module relay fails open or closed, microprocessor  
detects this, locks compressor off and indicates an error.  
3 . Wiring Errors If a wiring error exists causing CPCS,  
CR, or feedback switch not to function properly, micro-  
processor indicates an error.  
Code 21 Reset thermistor failure (applies only to installa-  
tions having external temperature reset)  
If temperature measured by this thermistor is outside range  
4. Processor (PSIO) Failure  
If hardware that monitors  
of  
to 240 F (-40 to 116 C), reset function is disabled  
feedback switch fails, or processor fails to energize re-  
lay module relay to on, an error may be indicated.  
and unit controls to normal set point. If temperature returns  
to the acceptable range, reset function is automatically en-  
abled. Cause of this fault is usually a bad thermistor, wir-  
ing error or loose connection.  
NOTE: The control does not detect circuit breaker fail-  
ures. If a circuit breaker trips on lead compressor in a  
circuit, a low oil pressure failure is indicated. On the  
other compressors, no failure is indicated.  
Code 22 Compressor  
A
1
discharge pressure  
transducer failure  
5 . Ground Fault Module on 130-2 10, 225, 250, 280, and  
Code 23 Compressor  
B
1
discharge pressure  
associated modular units (CGFA or CGFB) Open  
ule contacts are in lead compressor circuits, but ground  
fault could be in any compressor in affected circuit.  
Ground fault of any 040-l 10 and associated modular unit  
compressor (field-supplied accessory on 040-060 and 070,  
60 Hz units; standard on 070, 50 Hz and 80-l 10 and as-  
sociated modular units) will cause a trip.  
Mod-  
transducer failure  
Code 24 Compressor  
failure  
A
1
suction pressure transducer  
suction pressure transducer  
Code 25 Compressor  
B
1
failure  
Code 26 Compressor Al oil pressure transducer failure  
Code 27 Compressor Bl oil pressure transducer failure  
6. Checkout Procedure  
Shut off main power to unit. Turn  
then step through subfunc-  
on control power,  
If output voltage of any of these transducers is greater  
than 5 v, affected circuit shuts down without going through  
process. Other circuit continues to run. Reset is  
automatic if output voltage returns to the acceptable range,  
and circuit start-up follows normal sequence. Cause of fault  
is usually a bad transducer or a wiring error.  
tion  
code 5 is compressor  
step works correctly, then failure code is caused by:  
to proper compressor number (i.e., failure  
Next, energize the step. If  
l
HPS (high-pressure switch) open  
Misplaced feedback wire from and J5 terminals  
Ground wire and 24-v feeds reversed on one or more  
points on  
l
Code 28  
Low transducer supply voltage  
If transducer supply voltage is less than 4.5 v or greater  
than 5.5 v, unit shuts down without going through  
process. Reset is automatic if supply voltage returns to the  
acceptable range, and circuit start-up follows normal se-  
quence. Cause of fault is usually a faulty transformer, or  
primary voltage is out of range.  
The voltage supplied to the processor is polarized. When  
checking for proper voltage supply, be sure to consider this  
polarity. If voltage appears to be within acceptable toler-  
Compressor Alarm Circuit  
alarm circuit, processor closes contacts between  
nals 2 and 3 to start compressor. See Fig.  
ties shown to left of must be closed in order for power to  
reach compressor control relay, and the feedback input ter-  
minals on J3.  
Failure of power to terminal 1 on  
tween 2 and 3 on J4 should be closed, causes a code 1  
alarm.  
For compressor Al  
termi-  
Safe-  
when contacts be-  
ance, check to be sure the transformer supplying  
is not  
grounded. Grounding the supply transformer can result in  
serious damage to the control system.  
Terminal 2 on  
is the other leg of the compressor Al  
Code 29 Chilled water pump interlock switch open  
(applies only if unit is configured for use with  
a chilled water pump interlock).  
feedback channel. It is connected to the 24-v common.  
NOTE: Similar connections for each compressor can be  
lowed on the unit wiring diagrams located on the unit.  
Code can occur under any of these conditions:  
Code 9  
Leaving water thermistor failure  
1. Interlock switch fails to close within o n e minute after  
chilled water pump starts  
Code 10 Entering water thermistor failure  
If temperature measured by these thermistors is outside  
range of -40 to 240 F (-40 to 116 C), unit shuts down after  
2. Interlock switch opens during unit operation  
3. Interlock voltage is detected, but unit is not configured  
for interlock  
going through a normal  
Reset is automatic if tem-  
perature returns to the acceptable range, and unit start-up  
follows normal sequence. Cause of fault is usually a bad  
thermistor, wiring error, or loose connection.  
4. Interlock voltage is outside its valid range  
If any of these conditions occur, all compressors are dis-  
abled and, if running, shutdown occurs without  
Chilled water pump also shuts down. Reset is manual, with  
LOCAL/ENABLE-STOP-CCN switch. Most probable cause  
of this fault is shutdown or failure of chilled water pump to  
start. Other possibilities are improper configuration or wir-  
ing errors.  
Code 19  
Code 20  
Compressor Al suction sensor failure  
Compressor suction sensor failure  
On units with thermistors, if temperature measured by  
these thermistors is outside the range of -40 to 240 F (-40  
to 116 C), affected circuit shuts down after going through a  
normal  
Other circuit continues to run. Reset is  
automatic if temperature returns to the acceptable range,  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ginning of  
or  
F (5.5” C) below leaving water  
Code 30 Reset input failure (4 to 20  
temperature or reaches a saturated suction temperature of  
-15 F (-26 C). If appropriate saturated suction temperature  
is not met within 3 minutes (on 2 consecutive tries}, circuit  
Code 31 Demand limit input failure (4 to 20  
These codes apply only if unit is configured for these  
functions. If  
signal is less than 4 or more than  
shuts down without  
Reset is manual with LOCAL/  
20 reset or demand limit function is disabled and unit  
ENABLE-STOP-CCN Switch, and start-up follows normal  
functions normally. If  
range, function is automatically enabled.  
signal returns to the acceptable  
sequence.  
Possible causes for this alarm are  
ducer or a faulty EXV.  
a
bad thermistor or trans-  
Code 32 Loss of communication with compressor  
relay module (DISO-LV)  
Code 33 Loss of communication with EXV relay  
Code 40 Low oil pressure, Circuit A  
Code 41 Low oil pressure, Circuit  
module (DSIO-EXV)  
If communication is lost with either of these modules,  
If oil pressure differential is less than set point for more  
than 2 minutes at start-up, or more than one minute during  
normal operation, affected circuit shuts down without go-  
unit shuts down without  
This alarm resets auto-  
matically when communication is restored. The unit starts  
up normally after alarm condition is reset. Probable cause  
of condition is a faulty or improperly connected plug, wir-  
ing error, or faulty module.  
ing through  
process, Reset is manual with LOCAL/  
ENABLE-STOP-CCN switch, and start-up follows normal  
sequence. Factory configured differential oil pressure is  
6 psig.  
Loss of communication can be attributed to a grounded  
transformer with a secondary voltage of 21  
supplying  
Possible causes of fault are faulty compressor, EXV, crank-  
case heater or transducer, refrigerant overcharge, insuffi-  
cient oil charge, or tripped circuit breaker.  
the PSIO, DSIO-LV, or 4 IN/4 OUT modules; the  
transformer supplying the DSIO-EXV module; or the  
transformer supplying PS  
1
for the transformers. These  
Code 42 Cooler freeze protection  
transformers should not be grounded, or serious damage to  
If cooler entering or leaving water temperature is below  
34 F (1.1 C) for water or more than 8” F (4.4” C) below set  
controls can result. Check to be sure the  
are  
not grounded.  
point for brine, unit shuts down without  
Chilled  
NOTE: If a blank  
module is downloaded without be-  
water pump continues to run if controlled by chiller con-  
ing connected to the modules DSIO, this alarm is  
energized.  
trols. Reset is automatic when leaving water temperature  
reaches  
F (3” C) above set point, providing there has  
Code 34 Loss of communication with 4 In/4 Out module  
This applies only if one or more of the following options  
are used:  
been no prior occurrence of this fault the same day. If fault  
has occurred previously the same day, reset is manual with  
LOCAL/ENABLE-STOP-CCN switch.  
Possible causes of fault are low water flow or faulty  
thermistor.  
Code 43 Low water flow  
If any compressors are operating and entering water tem-  
perature is 3” F (1.7” C) or more below leaving water tem-  
perature for more than one minute, unit shuts down without  
Chilled water pump also shuts down. Reset is  
manual with LOCAL/ENABLE-STOP-CCN switch, and  
start-up follows normal sequence.  
external temperature reset  
l
l
l
l
l
4-20  
temperature reset  
external switch controlled dual set point  
switch controlled demand limit  
4-20  
demand limit  
hot gas bypass  
If communication is lost with 4 IN/4 OUT module, the  
unit shuts off automatically, after finishing  
of alarm is automatic when communication is restored. Start-up  
after alarm is remedied follows a normal sequence. Proba-  
ble cause of condition is a faulty or improperly connected  
plug, wiring error, or faulty module.  
Reset  
This is a suitable method for sensing low water flow be-  
cause entering water thermistor is in the cooler shell and  
responds more quickly to compressor operation than the leav-  
ing water thermistor in the leaving water nozzle, Possible  
causes of fault are faulty chilled water pump, control or  
thermistor.  
Loss of communication can be attributed to a grounded  
transformer with a secondary voltage of 21  
the PSIO, DSIO-LV, or 4 IN/4 OUT; the  
former supplying the DSIO-EXV module, or the  
supplying  
trans-  
trans-  
Code 44 Low cooler suction temperature, Circuit A  
Code 45 Low cooler suction temperature, Circuit B  
former supplying PS  
should  
1
for the transformers. These transformers  
be grounded, or serious damage to controls can  
If saturated suction temperature is less than 32 F (0°C)  
result. Check to be sure the transformers are not grounded.  
and is 20” F (11” C) for water or 30” F  
C) for brine or  
Code 36 Low refrigerant pressure, Circuit A  
Code 37 Low refrigerant pressure, Circuit B  
more below leaving fluid temperature, mode 14 is dis-  
played. Unit continues to run, but additional compressors  
are not allowed to start, If condition persists for more than  
10 minutes, fault code is displayed, and unit shuts down  
If suction pressure transducer senses a pressure below set  
point for more than 5 minutes at start-up or more than  
2 minutes during normal operation, affected circuit shuts  
without  
Reset is manual with  
down without going through the  
process. Reset is  
STOP-CCN switch, and start-up follows normal sequence.  
automatic when pressure reaches 10 psig above set point if  
there have been no previous occurrences of this fault on the  
same day. If this is a repeat occurrence on same day, then  
reset is manual, with LOCAL/ENABLE-STOP-CCN switch,  
Factory configured set point is 27 psig for standard chillers  
and 12 psig for brine chillers.  
Possible causes of fault are low refrigerant charge, faulty  
EXV, plugged filter drier, or faulty transducer.  
Code 38 Failure to pump out, Circuit A  
Code 39 Failure to pump out, Circuit B  
Possible causes of fault are low refrigerant charge, plugged  
filter drier, or a faulty EXV or thermistor.  
Code 46 High suction superheat, Circuit A  
Code 47  
High suction superheat, Circuit B  
If EXV is fully open, suction superheat is greater than  
75 F (42 C) and saturated evaporator temperature is less  
than MOP (maximum operating pressure) for more than 5  
minutes, unit shuts down after normal  
process.  
Reset is manual with LOCAL/ENABLE-STOP-CCN switch,  
and start-up follows normal sequence.  
The  
process is terminated when saturated suc-  
tion temperature is 10” F (5.5” C) below temperature at  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
This fault indicates factory configuration has not been  
done, and unit is not allowed to start. Refer to unit wiring  
label diagrams for factory configuration codes, There are 8  
groups of S-digit numbers that must be entered. The first  
Possible causes of fault are low refrigerant charge, plugged  
filter drier, or a faulty EXV or thermistor.  
Code 48 Low suction superheat, Circuit A  
Low suction superheat, Circuit B  
Code 49  
groups must be entered under s u b f u n c t i o n . G r o u p s  
If EXV is at minimum position, suction superheat is less  
than  
F (5.5” C) or saturated evaporator temperature is  
7 and 8 must be entered under s u b f u n c t i o n .  
greater than MOP (maximum operating pressure) for more  
than  
5
minutes, affected circuit shuts down after going through  
Enter each group, then press the  
key. Use the  
process, Reset is manual with  
down arrow after each group to bring up the next  
empty screen. Unit should start after factory and field con-  
figurations are correctly entered.  
STOP-CCN switch, and start-up follows normal sequence.  
Possible causes of fault are faulty EXV or thermistor.  
Code 50 Illegal configuration  
The usual cause of this fault is replacement of the pro-  
cessor module. Refer to instructions accompanying the re-  
placement module.  
This fault indicates a configuration error. Unit is not al-  
lowed to start. Check all configuration data and set points  
and correct any errors.  
Code 52 Emergency stop by CCN command.  
Code 51 Initial configuration required  
Unit goes through normal shutdown when this command  
is received, and goes through normal start-up when  
mand is cancelled.  
LEGEND  
STANDARD:  
040-060 50 Hz  
040-070 60 Hz  
-
-
-
-
I
-
-
-
-
-
-
STANDARD:  
ACCESSORY:  
070 50  
Contactor  
Circuit Breaker  
Communications Bus  
Compressor Protection  
,
040-060 50 Hz  
040-070 60 Hz  
CR’S  
C O M M  
Control  
Module  
CR  
D G T  
Compressor Contactor Relay  
Discharge Gas Thermostat (Optional)  
Relay Module (Low Voltage)  
HPS  
High-Pressure Switch  
Low  
Plug  
P o w e r  
S n u b b e r  
PWR  
SNB  
Terminal  
Block  
TRAN  
Transformer  
U
Unloader  
Fig.  
24-V Safety Circuit Wiring (040-070)  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONTROL  
24VAC  
I
S
E
C
O N D A R  
Y
1
LEGEND  
Contactor  
Communications Bus  
Compressor Protection Control Module  
Discharge Gas Thermostat (Optional)  
Relay Module (Low Voltage)  
l-tigh-Pressure Switch  
Low Voltage  
DGT  
HPS  
Plug  
PWR  
Power  
Terminal Block  
Transformer  
Unloader  
U
Fig.  
24-V Safety Circuit Wiring (080-110 and Associated Modular Units)  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEGEND  
Ground Fault Module  
Communications Bus  
Compressor Contactor Relay  
Relay Module (Low Voltage)  
High-Pressure Switch  
Low Voltage  
CGF  
SNB  
Plug  
Snubber  
Terminal Block  
Transformer  
TRAN  
U
Unloader  
24-V Safety Circuit Wiring (130-210 and Associated Modular Units)  
Fig.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEGEND  
Contactor  
Ground Fault Module  
C o m m o n  
C G F  
Control  
Relay  
Discharge Gas Thermostat (Optional)  
Relay Module (Low Voltage)  
Electronic Expansion Valve  
High-Pressure Switch  
D G T  
E X V  
H P S  
Low Volta  
Normally  
Plug  
e
Reset Button  
Terminal  
Board  
TB  
24-V Safety Circuit Wiring (225, 250, and 280 Units)  
Fig.  
5 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHECKOUT PROCEDURE  
agnose and correct EXV problems.  
Follow steps below to di-  
Electronic Expansion Valve  
EXV OPERATION These valves control the flow of liq-  
uid refrigerant into the cooler. They are operated by pro-  
cessor to maintain a specified superheat at lead compressor  
entering gas thermistor (located between compressor motor  
and cylinders). There is one EXV per circuit. See Fig. 11.  
Check EXV driver outputs. Check EXV output signals  
at appropriate terminals on EXV driver module (see  
Fig. 12) as follows:  
Connect positive test lead to terminal 1 on EXV driver.  
Set meter for approximately 20 vdc. Enter outputs  
High-pressure liquid refrigerant enters valve through bot-  
tom. A series of calibrated slots are located in side of ori-  
fice assembly. As refrigerant passes through orifice, pres-  
sure drops and refrigerant changes to a 2-phase condition  
(liquid and vapor). To control refrigerant flow for different  
operating conditions, sleeve moves up and down over ori-  
fice, thereby changing orifice size. Sleeve is moved by a  
linear stepper motor. Stepper motor moves in increments  
and is controlled directly by processor module. As stepper  
motor rotates, motion is transferred into linear movement  
by lead screw. Through stepper motor and lead screws,  
760 discrete steps of motion are obtained. The large num-  
ber of steps and long stroke result in very accurate control  
of refrigerant flow.  
subfunction of test function by pressing  
, then  
advance to EXVA test by pressing  
q
8
times. Press  
The driver should drive the circuit  
A
EXV  
fully open. During next several seconds connect nega-  
tive test lead to pins 2, 3, 4 and 5 in succession. Voltage  
should rise and fall at each pin. If it remains constant at  
a voltage or at zero v, remove connector to valve and  
recheck.  
Press  
to close circuit A EXV. If a problem still  
exists, replace EXV driver module. If voltage reading is  
correct, expansion valve should be checked. Next, test  
EXVB. Connect positive test lead to pin 7 and the neg-  
ative test lead to pin 8, 9, 10, 11 in succession during  
EXVB test.  
The  
subfunction shows EXV valve position as  
a percent of full open. Position should change constantly  
while unit operates. If a valve stops moving for any reason  
(mechanical or electrical) other than a processor or ther-  
mistor failure, the processor continues to attempt to open or  
close the valve to correct the superheat. Once the calcu-  
lated valve position reaches 60 (fully closed) for 040-210  
and associated modular units, 145 (fully closed) for 225,  
250, and 280 units, or 760 (fully open) it remains there. If  
EXV position reading remains at 60, 145 or 760, and the  
thermistors and pressure transducers are reading correctly,  
the EXV is not moving. Follow EXV checkout procedure  
below to determine cause.  
2. Check EXV wiring, Check wiring to electronic expan-  
sion valves from terminal strip on EXV driver. See  
Fig. 12.  
a. Check color coding and wire connections. Make sure  
they are connected to correct terminals at driver and  
EXV plug connections.  
b. Check for continuity and tight connection at all pin  
terminals.  
c. Check plug connections at driver and at  
sure EXV cables are not crossed.  
to be  
The EXV is also used to limit cooler suction temperature  
to 50 F (10 C). This makes it possible for chiller to start at  
higher cooler water temperatures without overloading com-  
pressor. This is commonly referred to as MOP (maximum  
operating pressure), and serves as a load limiting device to  
prevent compressor motor overloading, This MOP or load  
E X V D R I V E R  
BOARD  
J4  
I
limiting feature enables the 30G  
II chillers to  
operate with up to 95 F (35 C) entering water temperatures  
during start-up and subsequent pull-down.  
STEPPER  
‘ D C )  
O R I F I C E  
ASSEMBLY  
(INSIDE  
EXV  
Electronic Expansion Valve  
PISTON  
Fig. 12  
EXV Cable Connections to  
SLEEVE)  
EXV Driver Module,  
3. Check resistance of EXV motor windings. Remove plug  
at terminal strip and check resistance between com-  
mon lead (red wire, terminal D) and remaining leads,  
A, B , C, and E (see Fig.  
25 ohms 2 ohms.  
Resistance should be  
Control of valve is by microprocessor. A thermistor and  
a
pressure transducer located in lead compressor are used  
to determine superheat. The thermistor measures tem-  
perature of the superheated gas entering the compressor  
cylinders. The pressure transducer measures refrigerant  
pressure in the suction manifold. The microprocessor con-  
verts pressure reading to a saturation temperature. The  
difference between temperature of superheated gas and  
saturation temperature is the superheat.  
Fig. 11  
c Expansion Valve (EXV)  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
c. Remove screws holding top cover of EXV. Carefully  
remove top cover. If EXV plug was disconnected dur-  
ing this process, reconnect it after cover is removed.  
Because the  
are controlled by the processor mod-  
ule, it is possible to track valve position. During initial  
start-up, EXV is fully closed. After start-up, valve po-  
sition is tracked by processor by constantly observing  
amount of valve movement.  
The processor keeps track of EXV position by counting  
the number of open and closed steps it has sent to each  
valve. It has no direct physical feedback of valve posi-  
tion. Whenever unit is switched from STOP to RUN po-  
sition, both valves are initialized, allowing the proces-  
sor to send enough closing pulses to the valve to move it  
from fully open to fully closed, then reset the position  
counter to zero.  
When removing top cover, be careful to avoid dam-  
aging motor leads.  
d. Enter appropriate EXV test step for EXVA or  
EXVB in the outputs subfunction of the test function  
to initiate test. With  
cover lifted off EXV valve body, observe operation  
of valve motor and lead screw. The motor should  
turn counterclockwise, and the lead screw should move  
up out of motor hub until valve is fully open. Lead  
screw movement should be smooth and uniform from  
4. The EXV test can be used to drive EXV to any desired  
position. When EXV opens, the metering slots begin to  
provide enough refrigerant for operation at these steps:  
step 60 for sizes 040-210 and associated modular units,  
fully closed to fully open position. Press  
check open to closed operation.  
If valve is properly connected to processor and re-  
ceiving correct signals, yet does not operate as de-  
scribed above, valve should be replaced.  
or  
for sizes 225, 250, and 280. This is fully closed  
position when circuit is operating. The fully open posi-  
tion is 760 steps.  
5. Check thermistors and pressure transducers that control  
EXV. Check thermistors and pressure transducers that  
control processor output voltage pulses to  
See  
Operation of EXV valve can also be checked without  
removing top cover. This method depends on oper-  
ator’s skill in determining whether or not valve is  
moving. To use this method, initiate EXV test and  
open valve. Immediately grasp EXV valve body. As  
valve drives open, a soft, smooth pulse is felt for ap-  
proximately 26 seconds as valve travels from fully  
closed to fully open. When valve reaches end of its  
Fig, 13 for locations.  
Circuit A  
ducer SPTA  
Circuit B  
Thermistor T7, Suction Pressure Trans-  
Thermistor T8, Suction Pressure Trans-  
ducer SPTB  
a. Use temperature subfunction of the status function  
to determine if thermistors are reading  
correctly.  
b. Check thermistor calibration at known temperature  
by measuring actual resistance and comparing value  
measured with values listed in Tables 15 and 16.  
c. Make sure thermistor leads are connected to proper  
pin terminals at terminal strip on processor mod-  
ule and that thermistor probes are located in proper  
position in refrigerant circuit. See Fig. 14 and 15.  
opening stroke,  
a
hard pulse is felt momentarily. Drive  
valve closed and a soft, smooth pulse is felt for the  
26 seconds necessary for valve to travel from fully  
open to fully closed. When valve reaches end of its  
stroke, a hard pulse is again felt as valve overdrives  
by 50 steps. Valve should be driven through at least  
2 complete cycles to be sure it is operating properly.  
If  
a
hard pulse is felt for the 26 second duration, valve  
is not moving and should be replaced.  
The EXV test can be repeated as required by enter-  
d. Use the pressure subfunction of the Status function  
ing any percentage from 0 (  
movement.  
to 100 to initiate  
(
to determine if pressure transducers are  
reading correctly. Connect a calibrated gage to lead  
compressor suction or discharge pressure connection  
to check transducer reading.  
If operating problems persist after reassembly, they  
may be due to out-of-calibration thermistor(s) or inter-  
mittent connections between processor board terminals  
and EXV plug. Recheck all wiring connections and volt-  
e. Make sure transducer leads are properly connected in  
junction box and at processor board. Check trans-  
former 5 output. Check voltage transducer 5 vdc  
v.  
age  
signals,  
Other possible causes of improper refrigerant flow con-  
trol could be restrictions in liquid line, Check for plugged  
filter drier(s) or restricted metering slots in the EXV.  
Formation of ice or frost on lower body of electronic ex-  
pansion valve is one symptom of restricted metering slots.  
However, frost or ice formation is normally expected  
when leaving fluid temperature from the cooler is below  
40 F. Clean or replace valve if necessary.  
NOTE: Frosting of valve is normal during compressor  
Test steps and at initial start-up. Frost should dissipate  
after 5 to 10 minutes operation in a system that is oper-  
ating properly. If valve is to be replaced, wrap valve  
with a wet cloth to prevent excessive heat from damag-  
ing internal components.  
When above checks have been completed, check ac-  
tual operation of EXV by using procedures outlined  
in Step 5.  
6. Check operation of  
a. Close liauid line service valve of circuit to be checked,  
and run  
in that circuit to pump down low side of  
Repeat test step 3 ensure all refrigerant  
has been pumped from low side.  
NOTE: Be sure to allow compressors to run for the  
full period.  
the test step (  
for lead  
b. Turn off compressor circuit breaker(s). Close com-  
pressor discharge service valves and remove any re-  
maining refrigerant from low side of system.  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MUFFLERS  
C O M P R E S S O R S  
FILTER  
D R I E R  
I
CIRCUIT  
CIRCUIT A  
J
LEGEND  
Discharge Pressure Transducer  
Oil Pressure Transducer  
Suction Pressure Transducer  
Thermistor Number  
DPT  
T
Thermistor and Pressure Transducer Locations  
Fig. 13  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEAVING  
W A T E R / B R I N E  
THERMISTOR  
C O O L E R  
F L U I D  
B A F F L E  
ENTERING  
W A T E R / B R I N E  
C O N N E C T I O N  
A I R  
VENT  
SUCTION  
C O N N E C T I O N  
D R A I N  
C O N N E C T I O N  
C O O L E R  
TUBE  
(TYPICAL)  
L E A V I N G  
W A T E R / B R I N E  
C O N N E C T I O N  
ENTERING  
W A T E R / B R I N E  
THERMISTOR  
Fig. 14  
Thermistor Locations  
(Circuits A and B, Lead Compressor Only)  
THERMISTOR  
W E L L  
JACKETED  
C A B L E  
S E N S O R  
TUBE  
JACKETED  
COUPLING  
A C C E S S O R Y  
I
NOTE: BEND  
FOR INSERTION  
INTO WELL  
(76)  
6)  
F E R R U L E S  
INSIDE  
(4 8) DIA  
(6.4)  
COUPLING  
OD  
REFRIGERANT TEMPERATURE SENSOR (T7, T8 040-210 AND  
ASSOCIATED MODULAR UNITS)  
WATER-SIDE TEMPERATURE SENSOR (Tl, T2,  
(T7, T8 225, 250, 280)  
ALL UNITS),  
Thermistors  
Fig. 15  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pressure Transducers  
TWO  
of pressure trans-  
a low pres-  
All thermistors are identical in their tem-  
perature vs. resistance performance. Resistance at various  
temperatures are listed in Tables 15 and 16.  
Thermistors  
ducers are used on 30G  
sure transducer and a high pressure transducer. The low  
pressure transducer is identified by  
a
white dot on the body  
LOCATION  
shown in Fig. 13.  
General location of thermistor sensors are  
of the transducer, and the high pressure transducer by a red  
dot. See Fig. 16.  
Cooler Leaving Water Thermistor  
is located in  
Three pressure transducers are mounted on each lead com-  
pressor: 2 low-pressure transducers to monitor compressor  
suction pressure and oil pressure, and a high-pressure trans-  
ducer to monitor compressor discharge pressure (see  
Fig. 17 for exact locations on compressor). Each transducer  
is supplied with 5 vdc power from a rectifier which changes  
leaving water nozzle. The probe is immersed directly in the  
All thermistor connections are made through a  
coupling. See Fig. 15. Actual location is shown in Fig. 13  
and 14.  
Cooler Entering Water Thermistor  
cooler shell in first baffle space near tube bundle. Ther-  
mistor connection is made through a coupling. See  
T2 is located in  
24  
to 5 vdc.  
TROUBLESHOOTING If transducer is suspected of be-  
ing faulty, first check supply voltage to transducer. Supply  
Fig. 15. Actual location is shown in Fig. 13 and 14.  
Compressor Suction Gas Temperature Thermistors  
and  
voltage should be 5 vdc  
v. If supply voltage is cor-  
T7 and  
are located in lead compressor in each  
rect, compare pressure reading displayed on keypad and dis-  
circuit in suction passage between motor and cylinders, above  
oil pump. They are well-type thermistors on 040-210 and  
associated modular units, or ferrule-type on 225, 250, 280  
units. See Fig. 13 and 14.  
play module against pressure shown on a calibrated pres-  
sure gage. If the  
2
pressure readings are not reasonably close,  
replace pressure transducer.  
TRANSDUCER REPLACEMENT  
THERMISTOR REPLACEMENT (Tl , T2, T7,  
pressor and Cooler)  
(Com-  
Transducers are installed directly in the refrigerant cir-  
cuit. Relieve all refrigerant pressure using standard re-  
frigeration practices before removing.  
Thermistors are installed directly in fluid or refrigerant  
circuit. Relieve all refrigerant pressure using standard  
refrigerant practices or drain fluid before removing.  
r
1. Relieve refrigerant pressure using standard refrigeration  
practices.  
Proceed as follows (see Fig. 15):  
2. Disconnect transducer wiring at transducer by pulling  
up on locking tab while pulling weather-tight connection  
pfug from end of transducer. Do not pull on trans-  
ducer wires.  
To replace sensors  
T2, T7  
and  
1. Remove and discard original thermistor and coupling.  
3. Unscrew transducer from  
male flare fitting. When  
IMPORTANT: Do not disassemble new coupling.  
Install as received.  
installing new pressure transducer, do not use thread  
sealer. Thread sealer can plug transducer and render it  
inoperative.  
I
2. Apply pipe sealant to  
NPT threads on replace-  
4. Insert weathertight wiring plug into end of transducer  
until locking tab snaps in place.  
ment coupling and install in place of original. Do not  
use packing nut to tighten coupling. This damages fer-  
rules (see Fig. 15).  
5. Check for refrigerant leaks.  
3. Insert new thermistor in coupling body to its full depth.  
If thermistor bottoms out before full depth is reached,  
pull thermistor back out in, before tightening packing  
nut. Hand tighten packing nut to position ferrules, then  
SAE FEMALE FLARE  
finish tightening  
turns with a suitable tool. Ferrules  
are now attached to thermistor which can be withdrawn  
from coupling for unit servicing.  
To replace thermistors T7 and  
(040-210 and associated  
modula r unit s):  
Add a small amount of thermal conductive grease to ther-  
mistor well. Thermistors are friction-fit thermistors, which  
must be slipped into receiver located in the compressor pump  
end.  
WHITE DOT-LOW PRESSURE TRANSDUCER  
RED DOT -HIGH PRESSURE TRANSDUCER  
Society of Automotive Engineers  
SAE  
Fig. 16  
Pressure Transducer  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1 5  
Thermistor Temperature  
vs Resistance/Voltage Drop;  
II  
VOLTAGE  
D R O P ( V )  
RESISTANCE  
(OHMS)  
TEMPERATURE  
VOLTAGE  
D R O P ( V )  
RESISTANCE  
(OHMS)  
TEMPERATURE  
VOLTAGE  
D R O P ( V )  
( O H M S )  
4
8
2
1
98010  
94707  
91522  
88449  
85486  
82627  
79871  
77212  
74648  
72175  
69790  
67490  
65272  
63133  
61070  
59081  
57162  
55311  
53526  
51804  
5 0 1 4 3  
48541  
46996  
45505  
44066  
42679  
4 1 3 3 9  
40047  
38800  
37596  
3 6 4 3 5  
3 5 3 1 3  
34231  
3
.
0
9
3
5781  
1 6 7  
1 6 8  
1 6 9  
1 7 0  
1 7 1  
1 7 2  
1 7 3  
1 7 4  
1 7 5  
1 7 6  
1 7 7  
1 7 8  
1 7 9  
1 8 0  
1 8 1  
1 8 2  
1 8 3  
1 8 4  
1 8 5  
1 8 6  
1 8 7  
1 8 8  
1 8 9  
1 9 0  
1 9 1  
1 9 2  
1 9 3  
1 9 4  
1 9 5  
1 9 6  
1 9 7  
1 9 8  
1 9 9  
200  
201  
0
.
8
3
8
7 1 9  
- 24. 0  
- 23. 0  
- 22. 0  
- 21. 0  
- 20. 0  
4818  
4814  
4806  
4. 800  
4793  
4786  
4779  
4772  
4764  
4. 757  
4749  
4740  
4734  
4724  
4715  
4705  
4696  
4. 688  
4676  
4666  
4657  
4648  
3. 064  
3034  
3005  
2977  
2. 947  
2. 917  
2884  
2857  
2. 827  
2797  
2766  
2738  
2708  
2679  
0824  
0. 810  
0. 797  
0. 783  
0770  
0758  
0745  
0734  
0722  
0. 710  
0. 700  
0. 689  
0678  
0668  
0659  
7 0 5  
5637  
5497  
5361  
5 2 2 9  
5101  
4976  
4855  
4 7 3 7  
4622  
4511  
4403  
4 2 9 8  
4196  
4096  
4000  
3906  
3814  
3 7 2 6  
3640  
3556  
3474  
3395  
3 3 1 8  
3243  
3170  
3099  
3031  
6 7 7  
6 6 3  
6 5 0  
6 3 8  
6 2 6  
6 1 4  
-18.0  
-17.0  
-16.0  
15.0  
14.0  
-13.0  
-12.0  
79  
82  
6 0 2  
5 9 1  
5 8 1  
5 7 0  
5 6 1  
5 5 1  
5 4 2  
5 3 3  
5 2 4  
5 1 6  
5 0 8  
5 0 1  
4 9 4  
487  
10.0  
-9.0  
- 8. 0  
- 7. 0  
- 6. 0  
- 5. 0  
- 4. 0  
2
650  
2622  
2593  
2563  
2533  
2505  
2. 476  
2447  
2417  
2388  
2360  
2332  
2. 305  
2277  
0
649  
0640  
0632  
0. 623  
0. 615  
0607  
0600  
0592  
0. 585  
0579  
0572  
0566  
0560  
0554  
0548  
0542  
89  
-l:o  
0 . 0  
4' 613  
4602  
4592  
4579  
4. 567  
4554  
4540  
4527  
4. 514  
4. 501  
4487  
4472  
4457  
4442  
4427  
4413  
4397  
4. 381  
4366  
4348  
4. 330  
4313  
4. 295  
4278  
4258  
4241  
4223  
4202  
4184  
4. 165  
4145  
4125  
4103  
4082  
4. 059  
4037  
4017  
3994  
3. 968  
3. 948  
3927  
3902  
3. 878  
3854  
3828  
3805  
3781  
3757  
3729  
3705  
3. 679  
3653  
3627  
3600  
3. 575  
3547  
3520  
3493  
3464  
3437  
3409  
3382  
3. 353  
3. 323  
3295  
3. 267  
3238  
3210  
9 6  
4 6 7  
4 6 1  
4 5 6  
4 5 0  
4 4 5  
4 3 9  
4 3 4  
4 2 9  
424  
4 1 9  
4 1 5  
4 1 0  
4 0 5  
4 0 1  
3 9 8  
3 9 1  
3 8 6  
3 8 2  
3 7 7  
3 7 2  
3 6 7  
361  
2964  
2898  
2835  
2773  
2713  
2655  
2597  
2542  
2488  
2436  
2
251  
5: o  
2217  
2189  
2. 162  
2136  
2107  
2080  
2053  
2028  
1 0 2  
8: 0  
9. 0  
10. 0  
1 1 . 0  
1 2 . 0  
1 3 . 0  
14. 0  
33185  
3 2 1 7 6  
31202  
1 0 5  
1 0 6  
0526  
0. 520  
0515  
0. 510  
202  
2 0 3  
204  
205  
2 0 6  
2 0 7  
2 0 8  
3 0 2 6 0  
29351  
2 8 4 7 3  
2 7 6 2 4  
26804  
26011  
1 0 9  
1 1 0  
1 1 1  
1 1 2  
2
001  
973  
1. 946  
919  
1
2286  
2239  
2192  
2147  
2103  
2060  
2018  
1 9 7 7  
1 9 3 7  
1 8 9 8  
1 8 6 0  
1 8 2 2  
1 7 8 6  
1 7 5 0  
1 7 1 5  
1 6 8 0  
1 6 4 7  
0
494  
1 6 . 0  
1 7 . 0  
1 8 . 0  
1 9 . 0  
20. 0  
21. 0  
22. 0  
23. 0  
24. 0  
25. 0  
26. 0  
27. 0  
28. 0  
29. 0  
30. 0  
31 .o  
32. 0  
33. 0  
34. 0  
35. 0  
36. 0  
37. 0  
38. 0  
39. 0  
40. 0  
41. 0  
42. 0  
43. 0  
44. 0  
45. 0  
46. 0  
47. 0  
48. 0  
49. 0  
50. 0  
51. 0  
52. 0  
53. 0  
54. 0  
55. 0  
56. 0  
57. 0  
58. 0  
59. 0  
60. 0  
1
0488  
2 5 2 4 5  
2 4 5 0 5  
2 3 7 8 9  
2 3 0 9 6  
2 2 4 2 7  
2 1 7 7 9  
2 1 1 5 3  
2 0 5 4 7  
1 9 9 6 0  
1 9 3 9 3  
1 8 8 4 3  
18311  
1 7 7 9 6  
1 7 2 9 7  
1 6 8 1 4  
1 6 3 4 6  
1 5 8 9 2  
1 5 4 5 3  
1 5 0 2 7  
1 4 6 1 4  
1 4 2 1 4  
1 3 8 2 6  
1 3 4 4 9  
1 3 0 8 4  
1 2 7 3 0  
1 2 3 8 7  
1 2 0 5 3  
1897  
1870  
1.846  
1.822  
1792  
1 1 4  
1 1 5  
1 1 6  
1 1 7  
1 1 8  
1 1 9  
1 2 0  
1 2 1  
2 1 0  
211  
0471  
0465  
2 1 2  
213  
2 1 4  
2 1 5  
2 1 6  
217  
2 1 8  
2 1 9  
2 2 0  
221  
0
459  
1
771  
0. 453  
3 5 6  
3 5 0  
1. 748  
1724  
1. 702  
1676'  
1653  
0. 446  
0439  
0432  
3 4 4  
3 3 8  
0. 425  
3 3 2  
3 2 5  
3 1 8  
311  
3 0 4  
2 9 7  
2 8 9  
2 8 2  
1 2 3  
1 2 4  
1 2 5  
1 2 6  
127  
1 2 8  
1 2 9  
1 3 0  
1 3 1  
132  
1 3 3  
1 3 4  
1 3 5  
136  
1 3 7  
1 3 8  
139  
0417  
1
1
630  
607  
585  
0
409  
0401  
0393  
0384  
0375  
0366  
222  
2 2 3  
224  
2 2 5  
1562  
1538  
1
1496  
1474  
1453  
1. 431  
408  
517  
1 5 8 2  
1 5 5 0  
1 5 1 9  
1 4 8 9  
459  
1 4 3 0  
1401  
1 3 7 3  
1 3 4 5  
1 3 1 8  
1291  
1389  
1369  
1348  
1
327  
1308  
1291  
289  
1 1 7 3 0  
1 4 0  
1 2 6 5  
1 1 4 1 6  
1 4 1  
1 2 4 0  
1 1 1 1 2  
1 0 8 1 6  
1 0 5 2 9  
1 0 2 5 0  
9 9 7 9  
9717  
9461  
9 2 1 3  
8973  
8739  
8511  
1 4 2  
1 4 3  
1 4 4  
1 4 5  
1 4 6  
147  
1 4 6  
1 4 9  
1 5 0  
1 5 1  
1 5 2  
1 5 3  
1 5 4  
269  
250  
1 2 1 4  
1 1 9 0  
1 1 6 5  
1141  
1 1 1 8  
1 0 9 5  
1 0 7 2  
1 0 5 0  
1 0 2 9  
1 0 0 7  
986  
1230  
1
1192  
211  
1
1
1
155  
136  
118  
100  
1. 082  
064  
965  
8291  
8076  
7 8 6 8  
7 6 6 5  
7 4 6 8  
7277  
7091  
1
1
047  
0 2 9  
945  
925  
156  
1 5 7  
1 5 8  
159  
1 6 0  
1 6 1  
1 6 2  
163  
1 6 4  
1 6 5  
166  
1. 012  
906  
0
995  
887  
62. 0  
63. 0  
64. 0  
65. 0  
66. 0  
67. 0  
68. 0  
69. 0  
0978  
868  
0
962  
850  
6911  
0945  
832  
0
929  
6735  
6564  
6399  
6238  
6 0 8 1  
5929  
815  
798  
782  
765  
750  
734  
0914  
0
898  
3
181  
0883  
0868  
0853  
3152  
3123  
6 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 16  
Thermistor Temperature  
vs Resistance/Voltage Drop; Flotronic’” II  
TEMPERATURE  
VOLTAGE  
DROP (V)  
RESISTANCE  
(Ohms)  
TEMPERATURE  
VOLTAGE  
DROP (V)  
RESISTANCE  
(Ohms)  
168230  
157440  
147410  
138090  
129 410  
121 330  
113810  
106 880  
100 260  
94165  
- 4 0  
- 3 9  
- 3 8  
- 3 7  
- 3 6  
- 3 5  
- 3 4  
- 3 3  
- 3 2  
-31  
- 3 0  
- 2 9  
- 2 8  
- 2 7  
- 2 6  
- 2 5  
- 2 4  
- 2 3  
- 2 2  
-21  
4.896  
1 . 9 4 4  
1898  
1 . 8 5 2  
1 . 8 0 7  
1 . 7 6 3  
1 . 7 1 9  
1 . 6 7 7  
1635  
1594  
1553  
1513  
1474  
1436  
1 . 3 9 9  
1 . 3 6 3  
1 . 3 2 7  
1. 291  
2
272  
2184  
4 6  
4 7  
4 8  
4 . 8 7 4  
4 . 8 6 6  
4
4
4
8 5 7  
8 4 8  
8 3 8  
1
1
1
871  
801  
734  
4.828  
4.817  
4.806  
1670  
1609  
88 480  
1
1
1
1
1
1
1
550  
493  
439  
387  
337  
290  
244  
200  
158  
118  
079  
041  
4
794  
83 170  
78125  
73 580  
69 250  
4 . 7 8 2  
4.769  
4.755  
4.740  
4
725  
4710  
4.693  
4.676  
57 875  
54 555  
5 1 4 5 0  
48 536  
45 807  
43 247  
40 845  
38 592  
38 476  
34 489  
1 . 2 5 8  
6 2  
1
4
4
4
4
6 5 7  
639  
619  
5 9 8  
- 2 0  
- 1 9  
- 1 8  
- 1 7  
- 1 6  
- 1 5  
- 1 4  
- 1 3  
- 1 2  
-11  
1
1
1 . 1 2 9  
1006  
9 7 1  
4 . 5 7 7  
1040  
1012  
0. 984  
9 3 8  
9 0 6  
8 7 6  
8 3 6  
8 0 5  
7 7 5  
7 4 7  
719  
693  
6 6 9  
645  
6 2 3  
602  
583  
5 6 4  
547  
5 3 1  
516  
502  
4 8 9  
477  
466  
456  
446  
436  
427  
4 1 9  
4 1 0  
402  
393  
385  
376  
367  
3 5 7  
3 4 6  
3 3 5  
3 2 4  
312  
4
554  
4 . 5 3 1  
4 . 5 0 7  
4482  
4 . 4 5 6  
4 . 4 2 8  
4400  
4371  
4341  
4310  
4. 278  
4. 245  
4 . 2 1 1  
4 . 1 7 6  
4 . 1 4 0  
4 . 1 0 3  
4 . 0 6 5  
4026  
3. 986  
3. 945  
3. 903  
3860  
3816  
3 . 7 7 1  
3726  
32  
621  
0
949  
0. 920  
892  
30 866  
29 216  
27 633  
26 202  
24 827  
23 532  
22313  
21 163  
20 079  
19 058  
18 094  
17184  
16 325  
15515  
14749  
14026  
13 342  
12 696  
12085  
506  
0
- 1 0  
0. 865  
0 . 8 3 8  
0813  
- 7  
0
789  
7 8  
7 9  
8 0  
0765  
0743  
0722  
0702  
0. 683  
0665  
0648  
0 . 6 3 2  
0. 617  
0. 603  
0. 590  
0. 577  
0. 566  
0555  
0545  
0. 535  
0. 525  
0. 515  
0 . 5 0 6  
0 . 4 9 6  
0 . 4 8 6  
0 . 4 7 6  
0466  
0454  
0 . 4 4 2  
- 2  
- 1  
0
959  
3
1 0 4 4 1  
9
949  
3
680  
3. 633  
3. 585  
3. 537  
3. 487  
3438  
3387  
3 . 3 3 7  
3285  
3234  
3 . 1 8 1  
3 . 1 2 9  
3. 076  
3 . 0 2 3  
2. 970  
2 . 9 1 7  
2 . 8 6 4  
2 . 8 1 0  
2. 757  
2. 704  
2 . 6 5 1  
2. 598  
2. 545  
2. 493  
2 . 4 4 1  
2 . 3 8 9  
2337  
2 . 2 8 6  
2236  
2 . 1 8 6  
2 . 1 3 7  
2087  
2 . 0 3 9  
1. 991  
9485  
9
8
8
7
7
7
044  
627  
231  
855  
499  
161  
101  
102  
6
840  
6
6
5
536  
246  
971  
0
429  
104  
105  
106  
107  
0. 416  
0401  
0386  
0370  
5
5
710  
461  
285  
5
5
4
4
225  
000  
786  
583  
4389  
4
4
3
204  
028  
861  
3
701  
3
3
3
549  
404  
266  
3134  
3
2
2
2
2
2
2
008  
888  
773  
663  
559  
459  
363  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DISCHARGE  
PRESSURE  
TRANSDUCER*  
THERMISTOR*  
ENTERING  
CYLINDERS  
REFRIGERANT  
TEMPERATURE  
*Lead compressor only  
SUCTION  
PRESSURE  
EQUALIZER  
LINE  
OIL  
PRESSURE  
SIGHT GLASS  
(EACH COMPRESSOR)  
TRANSDUCER*  
TRANSDUCER*  
Fig. 17  
Lead Compressor Transducer and Thermistor Locations  
6 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Modules  
Turn controller power off before servicing controls. This  
ensures safety and prevents damage to controller.  
PROCESSOR MODULE  
(SIO), LOW-VOLTAGE  
4 IN/4 OUT MODULE  
(DSIO), AND  
EXV DRIVER MODULE (DSIO)  
The PSIO, DSIO and  
SIO modules all perform continuous diagnostic evaluations  
of the condition of the hardware. Proper operation of these  
modules is indicated by  
front surface of the  
(light emitting diodes) on the  
and on the top horizontal sur-  
face of the  
and SIO.  
RED LED Blinking continuously at a to  
rate  
indicates proper operation. Lighted continuously indicates  
a problem requiring replacement of module. Off continu-  
ously indicates power should be checked. If there is no in-  
put power, check fuses. If fuse is bad, check for shorted  
secondary of transformer or for bad module. On the  
module, if the light is blinking at a rate of twice per sec-  
ond, the module should be replaced.  
GREEN LED On a  
and an SIO, this is the green  
LED closest to COMM connectors. The other green LED  
on module indicates external communications, when used.  
Green LED should always be blinking when power is on. It  
indicates modules are communicating properly. If green LED  
is not blinking, check red LED. If red LED is normal, check  
module address switches. See Fig.  
(Processor Module)  
Proper addresses are:  
01 (different when CCN  
connected)  
DSIO (Relay Module)  
19  
DSIO (EXV Driver Module)  
(4 In/4 Out Module)  
31  
59  
If  
modules indicate communication failure, check COMM  
plug on  
module for proper seating. If a good connec-  
tion is assured and condition persists, replace  
module.  
ADDRESS  
SELECTOR  
If only DSIO or  
module indicates communication  
failure, check COMM plug on that mode for proper seat-  
ing. If a good connection is assured and condition persists,  
replace DSIO or SIO module.  
All system operating intelligence rests in  
module ,  
the module that controls unit. This module monitors con-  
ditions through input and output ports and through DSIO  
modules (low-voltage relay module and EXV driver  
module).  
The machine operator communicates with microproces-  
sor through keypad and display module. Communication  
between  
and other modules is accomplished by  
a
3-wire  
sensor bus. These 3 wires run in parallel from module to  
module.  
On sensor bus terminal strips, terminal 1 of  
ule is connected to terminal 1 of each of the other modules.  
Terminals 2 and 3 are connected in the same manner. See  
Fig, 19, If a terminal 2 wire is connected to terminal sys-  
tem does not work.  
Fig. 18  
Selector Switch Locations  
Module Address  
In  
relay module, and keypad and display module are all pow-  
ered from a common power source which connects  
to terminals 1 and 2 of power input strip on each module. A  
separate source of power is used to power options  
module through terminals 1 and 2 on power input strip. A  
II Chillers, processor module, low-voltage  
separate source of 12.5  
power is used to power EXV  
driver module through terminals 1 and 2 on power input  
strip.  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LOW VOLTAGE RELAY MODULE (DSIO) (Fig.  
Inputs on strip are discrete inputs (ON/OFF).  
power is applied across the 2 terminals in a  
Inputs  
When  
channel it reads as on signal. Zero v reads as an off signal.  
Outputs  
Terminal strips J4 and  
are internal relays whose  
signal from micro-  
coils are powered-up and powered-off by  
a
processor. The relays switch the circuit to which they are  
connected. No power is supplied to these connections by  
DSIO module.  
(LID) (4  
DRIVER)  
S E N S O R B U S C O N N E C T O R  
Sensor Bus Wiring  
(Communications)  
Fig.  
PROCESSOR MODULE (PSIO) (Fig. 20)  
Each input channel has 3 terminals; only 2 of the  
RED STATUS LIGHT  
Inputs  
AND  
ARE  
(C)  
terminals are used. Application of machine determines which  
terminals are used. Always refer to individual unit wiring  
for terminal numbers.  
NEL I2  
Outputs  
Output is 24 vdc. There are 3 terminals, only 2  
I
I
of which are used, depending on application. Refer to unit  
wiring diagram.  
I
I
RELAYS  
NOTE: Address switches (see Fig. 20) must be set at 01  
(different when CCN connected).  
9
C H A S S I S  
G R O U N D  
8
7
0
-( REAR)  
N E T W O R K  
COMMON  
NO  
6
5
(FORWARD)  
S E N S O R B U S  
A D D R E S S A D J U S T M E N T  
(NOT SHOWN) ON UNDERSIDE  
0
0
C O N N E C T O R  
J8  
A D D R E S S  
S W I T C H E S  
LEGEND  
Communications Bus  
Normally Closed  
Open  
Fig. 21  
Low-Voltage Relay Module  
I-  
Power  
Fig. 20  
Processor Module  
6 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4
OUT MODULE (SIO) (Fig. 22)  
4 In/4 Out mod-  
ule allows the following features to be utilized:  
Temperature Reset by outdoor air or space temperature.  
A remote thermistor (Part No,  
quired.  
is also re-  
NOTE: This accessory is not required for return water  
L
P W R  
temperature reset.  
I
2. Temperature Reset by remote 4-20  
signal.  
N
3. Demand Limit by remote 2-stage switch.  
P
U
4. Demand Limit by remote 4-20  
5. Dual Set Point by remote switch.  
The options module is standard on  
signal  
ADDRESS  
S W I T C H E S  
J7  
T
and  
S
associated modular chillers and is available as a  
field-installed accessory on  
Flotronic II chillers.  
250, and 280  
Remember to reconfigure the chiller for each feature se-  
lected (see Table 13). For temperature reset, demand limit,  
and dual set point, desired set points must be entered through  
keypad and display module (see Set Point Function section  
on page 39).  
0
See Table 17 for overall troubleshooting information.  
l
l
l
T
P
J6  
l
U
T
S
LEGEND  
Communications Bus  
Power  
Fig. 22  
4
Out Module  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Table  
SYMPTOMS  
CAUSE  
REMEDY  
COMPRESSOR DOES  
NOT RUN  
Power line open  
Reset circuit breaker  
Control fuse open  
Check control circuit for ground or short.  
Replace fuse  
High Pressure Switch (HPS)  
tripped  
Move LOCAL/ENABLE-STOP-CCN switch to STOP  
position then back to RUN or CCN position.  
Tripped power breaker  
Check the controls. Find cause of trip  
and reset breaker  
Loose terminal connection  
Improperly wired controls  
Low line voltage  
Check connections  
Check wiring and rewire.  
Check line voltage. Determine location  
of voltage drop and remedy deficiency  
Compressor motor defective  
Check motor winding for open or shot-t.  
Replace compressor if necessary.  
Seized compressor  
Loss of charge  
Replace compressor.  
Repair leak and recharge  
Replace transducer.  
COMPRESSOR CYCLES OFF  
ON LOW PRESSURE  
Bad transducer  
Add  
refrigerant.  
Low refrigerant charge  
COMPRESSOR SHUTS DOWN  
High-pressure control erratic in action  
Compressor discharge valve partially closed  
Condenser fan(s) not operating  
Replace control  
Open  
or replace if defective.  
Check wiring. Repair or replace motor(s)  
if defective.  
Condenser coil  
or  
Clean coil.  
UNIT OPERATES LONG OR  
CONTINUOUSLY  
Low refrigerant charge  
Control contacts fused  
Add  
refrigerant,  
Replace control  
Clean or replace  
plugged or plugged expansion  
valve or filter driver  
Defective insulation  
Service load  
Replace or repair.  
Keep doors and windows closed.  
Check valves. Replace if necessary.  
Support piping as required  
Piping vibration  
SYSTEM NOISES  
Expansion valve hissing  
Add  
refrigerant.  
Check for plugged liquid line filter drier.  
Check valve plates for valve noise.  
Replace compressor (worn bearings).  
Check for loose compressor  
Compressor noisy  
bolts.  
Repair leak.  
COMPRESSOR LOSES OIL  
FROSTED SUCTION LINE  
Leak in system  
Mechanical damage (blown piston or  
broken discharge valve)  
Repair damage or replace compressor.  
Crankcase heaters not energized  
Replace heaters, check wiring and  
crankcase heater relay contacts.  
durina  
shutdown  
Check cooler and compressor thermistors.  
Test EXV.  
Expansion valve admitting excess  
refrigerant  
Shortaae of refriaerant due to leak  
Shutoff valve partially closed or restricted  
Burned out coil  
Repair leak and recharge  
Open valve or remove restriction.  
Replace coil  
HOT LIQUID LINE  
FROSTED LIQUID LINE  
COMPRESSOR DOES NOT  
UNLOAD  
Replace  
valve  
Defective capacity control valve  
Miswired  
solenoid  
Rewire correctly.  
Replace spring  
Rewire correctly  
Weak, broken, or wrong valve body spring  
Miswired  
solenoid  
DOES NOT  
Defective capacity control valve  
Replace  
valve.  
Plugged strainer (high side)  
Clean or replace strainer.  
Clean or replace the necessary parts.  
Stuck or damaged unloader piston or  
piston ring(s)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wire the primary side of the transformer in parallel with  
TRAN3. See Fig. 23. This supplies transformer with proper  
line voltage. Be sure to connect proper tap of the trans-  
former to ensure supply of proper secondary voltage.  
ACCESSORY UNLOADER INSTALLATION  
Some of the 30G II units come standard with  
unloader(s), and many permit additional unloader(s) to be  
added if desired. See Table 18.  
Wire the secondary side of transformer to DSIO-LV  
IMPORTANT: Accessory hot gas bypass cannot be  
installed with accessory unloaders on units with more  
than 4 compressors.  
and a jumper from DSIO-LV  
Wire the secondary common to  
to DSIO-LV  
Connect  
the transformer ground to ground hole supplied near the  
transformer. These connections provide DSIO with nec-  
essary power to energize the solenoid coils.  
If accessory unloaders are desired, an accessory unloader  
package is used. Package includes  
a
suction cutoff unloader  
3. When all connections are made, check for proper wiring  
and tight connections. Replace and secure inner panel.  
Restore power to unit.  
head package. The 24-v coil in the package can be used for  
040-l 10, 130 (60 Hz) and associated modular units. A  
115 v or 230 v coil must be used for 130 (50 Hz), 150-210,  
225, 250, 280, and associated modular units. Coil voltage  
depends on control circuit voltage, Consult current Carrier  
price pages for appropriate part numbers.  
4. Configure the processor. With the addition of extra un-  
loaders, the unit configuration has changed. To change  
the configuration of the processor, enter the service func-  
tion using the keypad and display module. Before any  
changes can be made, the  
NOTE: The accessory package will include all necessary  
components and wiring with the following exceptions: The  
field must provide screws, and on the 130-2 10, 225, 250,  
280, and associated modular units, the field must also sup-  
CCN switch must be in the STOP position, and the ser-  
vicer must log on to the processor.  
a. Press  
Keypad LCD displays the word  
a d LaCD  
Keypad LCD  
ply a  
vdc (part number  
unloader relay  
PASSWORD.  
Enter d  
LOGGEDON.  
and wire (90” C or equivalent).  
i
s
. p K e y p  
l
y
s
Table 18 Standard and Accessory Unloaders  
I
NO. OF ACCESSORY  
To change configuration, press  
C.  
displays FLD CFG.  
d. If an additional unloader was added to compressor  
Circuit  
A
Circuit  
B
or2  
Al, press until NULA 1 appears in keypad dis-  
1
0
1
1
play. Press for the number of unloaders on  
circuit A. Keypad display now reads NULA 2.  
0
If an additional unloader was added to compressor  
*And associated modular units  
B
1, press  
q
until NULB  
appears in keypad dis-  
Installation  
1. Be sure all electrical disconnects are open and tagged  
before any work begins. Inspect the package contents  
for any damage during shipping. File a claim with the  
shipper if damage has occurred.  
play. Press  
for the number of unloaders on  
circuit B. Keypad display now reads NULB 2.  
Key-  
When configuration is complete, press  
pad display reads LOGGEDON. Press  
until  
. Keypad dis-  
2. For ease of installation, factory-supplied wiring for the  
additional unloader is provided in the compressor  
harness.  
pad display reads LOG OFF. Press  
play reads EXIT LOG.  
5. Using test function, check unloaders. Press  
Install the additional unloader cylinder head on the lead  
3.  
Key-  
compressor, Al or  
according to instructions pro-  
vided by the compressor manufacturer in the accessory  
pad display reads OUTPUTS. Press  
until display  
package.  
reads ULA  
2
OFF. Press  
q
.
Relay energizes. Press  
until reads  
4. Continue installation per either 040-l 10, 130 (60 Hz)  
units or 130 (50 Hz), 150-210, 225, 250, and 280 units  
section as appropriate.  
and relay deenergizes. Press  
ULB2 OFF. Press  
. Relay energizes. Press  
display q  
0 4  
10, 130 (60 Hz) UNITS (and associated modular units)  
and relay deenergizes.  
1. Wire the solenoid before any field wiring begins. Wir-  
ing between components and control box must be en-  
closed in conduit. All local electrical codes and National  
Electrical Code (NEC) must be followed. Factory wires  
are provided in the compressor harness to connect the  
solenoid. These wires are in the compressor control box.  
6. When unloader check has been performed, return LOCAL/  
ENABLE-STOP-CCN to proper position. Close and se-  
cure control box door.  
2. Wire the control side. Open the left side control box  
door and remove inner panel. Using the holes provided  
and field-supplied screws, install field-supplied trans-  
former above the DSIO-LV on the control panel.  
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SC H E M A T I C  
i
FROM  
OR  
CONTROL SCHEMATIC  
TRAN  
080-110  
Hz) and 130 (60  
L E G E N D  
Contactor  
Compressor Protection Control System  
Control Relay  
Module  
Terminal Block  
Transformer  
Unloader  
Low oltage  
U
Fig. 23  
Accessory Unloader Control Wiring  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
130 (50 Hz), 150-210, 225, 250, AND 280 UNITS (and  
To change the configuration, type  
keypad LCD will display “FLD CFG.” Press  
until either 0” or “NULA is displayed  
(depending on the number of unloaders provided as  
standard), Then press (for 1 unloader on Al)  
or (for 2 unloaders on compressor Al). The  
display will now read either “NULA 1” or  
‘NULA 2, as appropriate, Press  
and the  
associated modular units)  
Install control wiring. The minimum wire size for  
stallation is 16  
(American Wire Gage). Refer to  
Fig. 24 and 25 for proper wiring. Open the control box  
door. Locate unloader relays A and B (URA, URB) in  
place of the hot gas bypass relays as shown on the com-  
ponent arrangement diagram on the unit. Mount the re-  
lays with the field-supplied screws. Be careful not to  
damage the components and wiring in the area when mount-  
ing the relays.  
to get to the  
NULB display, and change this setting in the same  
manner as with circuit A.  
2
Wire the control side. Wire the URA coil in series be-  
tween  
and  
19 of the 4 IN/4 OUT module with  
the wires provided. Wire the URB coil in series be-  
d. Once the configuration is complete, press  
tween  
and  
of the same module with the wires  
and the keypad LCD will display “LOGGEDON,”  
provided.  
Press  
until the keypad LCD display reads “LOG  
Locate the black wire in the control harness originating  
from labeled HGBPR-A-COM. Connect this wire  
to the URA terminal COM. Connect the wire labeled  
HGBPR-A-NO to URA-NO. Connect the wire from  
OFF.” Press  
and the keypad LCD will display  
“EXIT LOG.”  
5
Once the unloader heads are installed, the unit is checked  
for leaks, and the system is prepared for operation per  
B,  
URA-NO to  
For an extra unloader on circuit  
connect the wire labeled HGBPR-B-COM to  
COM, and the wire labeled HGBPR-B-NO to  
NO. Connect the wire from URB-NO to  
instructions for the compressor unloader head instal-  
lation, check the output of the relays using the test func-  
tion as follows:  
the  
3. Wire in the solenoid valves.  
a. Press  
and the display will read  
NOTE: Wires external to the control box must be run in  
conduit  
b. Press the  
q
to scroll down until the display reads  
Terminal blocks are provided for easy field wiring. Use  
“CPA1 OFF.”  
one of the isolated  
(22-mm) holes in the side of  
c. Press  
, and the compressor should start.  
the compressor electrical box with a strain relief to run  
the wires to the solenoid coil. Connect URA between  
d. Press  
,
and the compressor should stop.  
a
and  
Connect URB between  
and  
e. Press  
f. Press  
until the display reads  
OFF.”  
Check all of the electrical connections for proper  
location and tightness, and replace and secure the elec-  
trical box of the compressor,  
c l  
, and the solenoid should energize.  
and the solenoid should deenergize.  
and keys to check the remainder of  
g. Press  
q
4. Configure the microprocessor, Once the relays are mounted  
in the control box, the microprocessor must be config-  
h. Use the  
ured for the unloader option. ‘To do so:  
the unloader coils.  
a. Be sure the LOCAL/ENABLE-STOP-CCN switch is  
in the STOP position.  
6. Once the check has been performed, return the LOCAL/  
ENABLE-STOP-CCN switch to the proper position.  
b. Log into the processor and enter the service func-  
tion using the keypad and display module.  
7. Close and secure the control box door.  
8. Start the unit and confirm that the chiller operates  
Type  
. The keypad LCD will display  
properly.  
“PASSWORD.” Enter  
and the  
keypad LCD will display “LOGGEDON.  
LEGEND  
Terminal Block  
Transformer  
COM  
Communications Bus  
Hot Gas Bypass Relay  
Unloader  
Normally  
Open  
Unloader Relay  
S n u b b e r  
II  
Unloader Wiring, 130 (50 Hz), 150-210, 225, 250, 280  
Fig. 24 - Flotronic’”  
70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
-
-
-
-
-
-
-
-
-
-
-
-
w
-
-
-
m
-
-
I
I
-
-
-
-
-
-
-
-
-
-
-
-
-
-
l
- - - ‘ I  
S W I T C H  
I
I
I
I
I
-
-
-
-
-
-
-
-
I
-
-
-
-
I
-
!
I
I
I
I
l
I
L
-
-
B
-
-
-
-
-
I
211  
I
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
A
-
-
I
I
- - - - - - - - m - w - - - - - - -  
- - -OUT-PUT- I - - - - - - - - - - - - - - - - Y - -  
4-20  
LEGEND  
Switch  
Transformer  
Unloader Relay  
Contactor  
Circuit Breaker  
COMM  
Communications Bus UR  
Accessory Unloader Control Wiring, 130 (50 Hz),  
280  
Fig. 25  
FIELD WIRING  
Refer to Fig, 26 36 for field wiring.  
4
O U T  
T B 7  
T B 7  
T B 7  
T B 7  
M O D U L E  
STAGE  
1
!
-
-
-
-
-
-
i
t
-
-
-
-
L
- - - - - - - - - - -  
STAGE  
1
L
e m - - -  
- - -  
I
H -  
r
STAGE2  
2
STAGE2  
Terminal Block  
-
-
-
-
-
-
-
-
-
-
-
u
N O T E S :  
NOTE: Contacts must be rated for dry circuit application, capable of  
1
Requires accessory options module package.  
2 Contacts must be rated for dry circuit application, capable of re-  
reliably switching a 5 vdc,  
to 20  
load  
liably switching a 5 vdc, 1  
to 20  
load  
Demand Limit  
Two External Switch  
Fig. 26A  
Inputs,  
Two External Switch  
250, 280 Units  
Demand Limit  
Inputs,  
Fig. 26B  
and Associated Modular Units  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIELD SUPPLIED  
LOOP ISOLATOR  
EXTERNAL  
EXTERNAL  
POWER  
AND ASSOCIATED MODULAR UNITS  
+
3
AND ASSOCIATED MODULAR  
-
-
-
u
+
3
-
u
FIELD SUPPLIED  
LOOP ISOLATOR  
T B - 7  
FLOTRONIC II UNITS  
4
l-E-11  
-
I
I
I
TB  
Terminal Block  
FLOTRONIC II UNITS  
NOTE: The  
sory options module package for this feature  
Flotronic’” II units require the acces-  
TB  
Terminal Block  
NOTE: The  
Flotronic II units require the acces-  
sory options module package for this feature.  
Fig. 27  
Demand Limit  
4-20  
Signal  
(Externally Powered)  
Fig. 30  
Remote Reset from 4-20  
Signal  
(Externally Powered)  
4
OUT  
MODULE  
-
-
SIGNAL  
GENERATOR  
-
-
-
AND ASSOCIATED MODULAR UNITS  
AND ASSOCIATED MODULAR UNITS  
4
3
TB-11  
TB-7  
FLOTRONIC II UNITS  
FLOTRONIC II UNITS  
TB  
Terminal Block  
TB  
Terminal Block  
NOTE: The Flotronic II units require the acces-  
sory options module package for this feature  
NOTE: The  
sory options module package for this feature.  
Flotronic II units require the acces-  
Demand Limit  
(Internally Powered)  
4-20  
Signal  
Fig. 31  
Remote Reset from 4-20  
Signal  
Fig. 28  
(Internally Powered)  
4
IN/4 OUT  
REMOVE JUMPER  
CONTACTS  
M O D U L E  
-
-
6
3
-
-
-
-
-
-
-
-
c
l
-
-
-
-
-
- -  
-
4
REMOTE THERMISTOR  
-
-
-
-
-
-
-
-
-
-
-
-
AND ASSOCIATED MODULAR UNITS  
AND ASSOCIATED MODULAR UNITS  
JUMPER  
- - - -  
g
TB-7  
- - - -  
10 TE7  
6
TB-11  
FLOTRONIC I UNITS  
FLOTRONIC II UNITS  
TB  
Terminal Block  
TB  
Terminal Block  
N O T E S :  
1 The  
Flotronic II units require the accessory op-  
tions module for this feature.  
2. Contacts must be rated for dry circuit application, capable of  
NOTE: The  
Flotronic II units require the acces-  
sory options module package for this feature.  
switching a 5 vdc, 1  
to 20  
load  
Remote Reset from Space or  
Outdoor-Air Temperature  
Fig. 29  
Remote On/Off  
Fig. 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(CWFS)  
4
OUT  
M O D U L E  
TB-6  
S W I T C H  
-
-
-
-
-
-
I - -  
-
-
-
-
-
_
_
_
AND ASSOCIATED MODULAR UNITS  
AND ASSOCIATED MODULAR UNITS  
-
-
-
-
-
7
-
-
-
-
-
-
-
-
8
2
FLOTRONIC  
Chilled Water Pump Interlock  
Chilled Water Flow Switch (not required  
protection is provided by Flotronic II controls)  
Terminal Block  
I
I
UN ITS  
FLOTRONIC’” II UNITS  
CWFS  
low flow  
T B  
Terminal Block  
T B  
NOTE: The  
sory options module for this feature  
Flotronic II units require the acces-  
NOTE: Contacts must be rated for dry circuit application, capable of  
reliably switching a 5 vdc,  
to 20  
load.  
Fig. 33  
Remote Dual Set Point Control  
Fig. 36  
Interlocks  
REPLACING DEFECTIVE  
PROCESSOR MODULE  
-
-
-
-
-
3
The replacement part number is printed on a small label  
-
c
l
on front of the  
module. The model and serial num-  
bers are printed on the unit nameplate located on an exte-  
rior corner post. The proper software and unit configuration  
data is factory installed by Carrier in the replacement mod-  
T5-3  
AND  
MODULAR UNITS  
ule. Therefore, when ordering  
a
replacement processor mod-  
ule (PSIO), specify complete replacement part number,  
unit model number, and serial number. If these numbers  
are not provided, the replacement module order is config-  
ured instead as a generic Flotronic’” 11 replacement mod-  
ule. This requires reconfiguration of the module by the  
installer.  
4
FLOTRONIC II UNITS  
Chilled Water Pump  
Terminal Block  
T B  
Electrical shock can cause personal injury, Disconnect  
all electrical power before servicing.  
NOTE: The maximum load allowed for the chilled water pump circuit  
is 125 va sealed, 1250 va inrush at 115 or 230 v  
Fig. 34  
Chilled Water Pump  
Installation  
1. Verify the existing  
module is defective by using  
the procedure described in the Control Modules sec-  
tion on page 64.  
ALARM  
SHUTOFF  
2. Refer to Start-Up Checklist for Flotronic II Chiller Sys-  
tems (completed at time of original start-up) found in  
job folder. This information is needed later in this  
S W I T C H  
-
-
-
-
-
-
-
a
-
-
-
1
TB-3  
I -  
I
i
procedure. If checklist does not exist, fill out the  
T 8 - 3  
c
l
and  
configuration code sections on  
a
new check-  
list. Tailor the various options and configurations as  
needed for this particular installation.  
AND ASSOCIATED MODULAR UNITS  
3 . Check that all power to unit is off. Carefully discon-  
nect all wires from defective module by unplugging the  
6 connectors. It is not necessary to remove any of the  
individual wires from the connectors. Remove the green  
ground wire.  
2
TB-5  
FLOTRONIC II UNITS  
TB  
Terminal  
Block  
4 . Remove defective  
by removing its mounting screws  
with a Phillips screwdriver, and removing the module  
from the control box, Save the screws for later use.  
NOTE: The maximum load allowed for the alarm circuit is 125 va  
sealed, 1250 va inrush at 115 or 230 v  
5 . Use a small screwdriver to set address switches and  
Fig. 35  
Remote Alarm  
S2 on the new  
module to exactly match the set-  
tings on the defective module.  
6 . Package the defective module in the carton of the new  
module for return to Carrier.  
7 . Mount the new module in the unit control box using a  
Phillips screwdriver and the screws saved in Step  
4
above.  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
while displaying CODE 6. The display returns in ap-  
proximately 15 seconds.  
8. Reinstall all 6 wire connectors and the green ground  
wire.  
NOTE: Codes with leading zeros in the configuration  
will be displayed starting with the first number greater  
than zero.  
9. Carefully check all wiring connections before restoring  
power.  
10. Verify the LOCAL/ENABLE-STOP-CCN switch is in  
STOP position  
14. Press  
to verify each item is configured as needed  
11. Restore control power. Verify the red and green lights  
for this particular installation. Table 9 shows the fac-  
tory configuration code default settings. Table 9 also  
shows the service replacement code default settings which  
are used if no model number was specified when or-  
on top of  
and front of each DSIO module re-  
spond as described in Control Modules section on  
page 64. The keypad and display module  
or LID)  
should also begin its rotating display.  
dering the replacement  
module. It is strongly sug-  
gested that the Start-Up Checklist for  
II Chiller  
12. Using the keypad and display module, press  
Systems (completed at time of original start-up) be used  
at this time to verify and/or reprogram the various op-  
tions and configurations required for this job.  
to verify that the software version number matches the  
ER (engineering requirement) number shown on the  
label.  
After completing the configuration steps outlined above,  
13. Press  
to verify that the 6 factory configuration  
restore main power and perform a unit test as  
codes (CODE 1 through CODE 6) exactly match the  
codes listed for this unit model on the component ar-  
rangement label diagram on the control box door. If  
they are different or are all zeros, reenter the codes.  
scribed in  
and  
sections on page 38.  
Complete this procedure and restore chiller to normal  
operation by returning the  
CCN switch to desired position.  
If any changes are required, the  
display becomes  
blank and reconfigures itself after pressing the  
key  
74  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Copyright  
1994  
Carrier  
Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
B
T a b  
P C 9 0 3  
Catalog No 563-015  
Printed in  
U
S
A
Form  
Pg 76  
l-94  
Replaces:  
T ,  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Black Box Computer Hardware MediaCento HX Transmitter and Receivers User Manual
Bolens Lawn Mower 112 340A User Manual
Breville Slow Cooker BSC560XL User Manual
Bushnell Weather Radio 950070C User Manual
Cabletron Systems Network Card 9E106 06 User Manual
Carrier Water Dispenser 30HXA User Manual
Casio Watch 1914 User Manual
Casio Watch QW 761 User Manual
Celestron Heat Pump VMC30SB 1 User Manual
Chicago Pneumatic Impact Driver CP8750 User Manual