CFM Ventilation Hood UVCVR36 User Manual

Vent-Free Fireboxes  
Models: UVSTR36, UVCVR36  
INSTALLER/CONSUMER  
SAFETY INFORMATION  
DO NOT INSTALL THE APPLIANCE IN  
THIS FIREBOX, UNLESS THIS  
FIREBOX MEETS THE MINIMUM  
DIMENSIONS REQUIRED FOR THE  
INSTALLATION.  
UVSTR36  
WARNING: If the information in this  
manual is not followed exactly, a fire or  
explosion may result causing property  
damage, personal injury or loss of life.  
FOR USE ONLY WITH A LISTED  
GAS-FIRED, UNVENTED,  
DECORATIVE ROOM HEATER NOT TO  
EXCEED 40,000 BTU/H  
DO NOT BUILD A WOOD FIRE.  
DUE TO HIGH TEMPERATURES, THE  
APPLIANCE SHOULD BE LOCATED  
OUT OF TRAFFIC AND AWAY FROM  
FURNITURE AND DRAPERIES.  
UVCVR36  
Do not attempt to modify or alter the  
construction of the appliance or its  
components. Any modification or  
alteration of construction may void the  
warranty of these units.  
Homeowner's Installation and  
Operating Manual  
Do not store or use gasoline or other  
flammable vapors and liquids in the  
vicinity of this or any other appliance.  
Improper maintenance or service can  
cause injury or property damage. Refer  
to this manual. For additional infor-  
mation, consult a qualified installer,  
service agency, or the gas supplier.  
These Ventless Fireboxes are design  
certified to ANSI 21.91.2001 and are for  
use with any ANSI Z21.11.2 Unvented  
Room Heaters.  
I
Carefully review the instructions supplied  
with the decorative type unvented room  
heater for the minimum fireplace size  
requirement.  
INSTALLER: Leave this manual with the appliance.  
CONSUMER: Retain this manual for future reference.  
7412960 10/06 Rev. 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UVSTR / UVCVR Series Vent-Free Fireboxes  
General Information  
Installation Precautions  
DO NOT BURN WOOD OR OTHER MATERI-  
ALS IN THESE FIREBOXES.  
This Majestic Fireplaces firebox and its components  
have been tested and will operate safely when installed  
in accordance with this installation manual. Read all in-  
structions before starting installation, then follow these  
instructions carefully during installation to maximize  
firebox benefit and safety. Report to your dealer any  
parts damaged in shipment.  
General Information  
The installation must conform with local building codes  
or, in the absence of local codes, with the National Fuel  
Gas Code, ANSI Z223.1/NFPA 54 (latest edition) and  
with the National Electrical Code, ANSI/NFPA70 (latest  
edition).  
This firebox is a highly engineered system. Unless you  
use CFM Corporation components which have been  
designed for the system, you may create a possible fire  
hazard.  
In the Commonwealth of Massachusetts, all gas fitting  
and installation of this heater shall only be done by a  
licensed gas fitter or licensed plumber.  
NOTE: Installation and repair should be done by a qual-  
ified service person. The firebox should be inspected  
before use and at least annually by a qualified service  
person. More frequent cleaning may be required due  
to excessive lint form carpeting, bedding material, etc.  
It is imperative that control compartment, burners, and  
circulating air passageways of the firebox be kept clean.  
CFM Corporation warranty will be voided by, and  
CFM Corporation disclaims any responsibility for,  
the following actions:  
Installation of any damaged firebox.  
Modification of the firebox or any of the compo-  
nent parts thereof.  
Installation other than as instructed by CFM Cor-  
poration.  
Any safety screen or guard removed for servicing the  
firebox must be replaced prior to operating the firebox.  
Installation and/or use of any component part  
or accessory not manufactured or approved by  
CFM Corporation in combination or assembly  
with a Majestic Fireplaces firebox, notwithstand-  
ing any independent testing laboratory or other  
third party approval of such component part or  
accessory.  
Provide adequate combustion and ventilation air.  
The flow of combustion and ventilation air MUST NOT  
be obstructed.  
Provide adequate clearance around air openings into  
the combustion chamber and adequate accessibility  
clearance for servicing and proper operation. NEVER  
obstruct the opening of the firebox.  
Any such action may create a possible fire hazard.  
Consult your local building codes.  
These models may NOT be installed in a bedroom  
or bathroom.  
Proposition 65 Warning: Fuels used in gas, wood-  
burning or oil fired appliances, and the products of  
combustion of such fuels, contain chemicals known  
to the State of California to cause cancer, birth de-  
fects and other reproductive harm.  
Glass doors are NOT available for these fireboxes.  
WARNING: Check with your electronics manufactur-  
er before installing a television or other electronic  
device above this fireplace.  
California Health & Safety Code Sec. 25249.6  
Fireplace Screen  
The fireplace screen must be in place when the firebox  
is operating, and unless other provisions for combustion  
air are made, the screen must have openings for the  
introduction for combustion air.  
WARNING: Be sure to read complete Vent  
Free Gas Log Heater and Vent-Free Fire-  
place Installation and Operating Instruc-  
tions before installing this product.  
3
7412960  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UVSTR / UVCVR Series Vent-Free Fireboxes  
UVSTR36 Specifications  
Rough  
Opening  
Depth  
24"  
��"  
Recessed  
Nailing  
"  
Flange  
Rough Opening Width 41"  
Rough  
Opening  
Height  
"  
Gas Line  
Access  
40"  
36"  
"  
36"  
40"  
12"  
14"  
"  
"  
"  
Outside Air  
FP676  
Fig. 1 UVSTR36 Series specification and framing dimensions.  
UVCVR36 Specifications  
Framing Recess  
"  
24"  
��"  
Rough  
Opening  
Depth  
"  
Recessed  
Rough  
Opening  
Height  
Nailing  
Flange  
"  
40"  
"  
36"  
"  
36"  
Outside  
Air  
14"  
"  
Gas Line  
Access  
"  
40"  
12"  
FP677  
Fig. 2 UVCVR36 Series specification and framing dimensions.  
7412960  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
UVSTR / UVCVR Series Vent-Free Fireboxes  
3A  
3B  
(Top View)  
(Front View)  
CEILING  
COMBUSTIBLE  
FINISHED WALL  
MANTEL TRIM  
MANTEL  
TRIM  
LEG  
42" Min.  
36"  
FIREBOX  
2"  
2"  
11" Min.  
4¹⁄₂"  
4¹⁄₂"  
NONCOMBUSTIBLE  
FACING MATERIAL  
(Side View)  
HEADER  
DRYWALL  
(Side View)  
8"  
MANTEL  
SHELF  
1¹⁄₂"  
4"  
12"  
8"  
STAND-OFF  
Seal with  
noncombustible  
material  
Front leg  
of grate  
3"  
FP679  
Fig. 3 Clearances to combustibles.  
Minimum Clearances  
Sidewall Clearances:  
The clearance from the side of the firebox to any com-  
bustible wall should not be less than 11" . (Fig. 3A)  
B
A
Ceiling Clearances:  
The ceiling height should not be less than 42" from the  
top of the fireplace opening. (Fig. 3A)  
Mantel Clearances:  
FP1545  
If a combustible mantel is installed, it must meet the  
clearance requirements detailed in Figure 3A. A mantel  
breastplate can be installed at a minimum height of 8"  
with a maximum projection of 1¹⁄₂".  
Front/Back Width Side Width  
A
B
UVSTR/UVCVR36  
29"  
17¹⁄₈"  
Fig. 4 Hearth dimensions.  
Grate Clearance:  
The minimum clearance between the front legs of the  
grate and front edge of the fireplace is 3" . (Fig. 3B)  
5
7412960  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UVSTR / UVCVR Series Vent-Free Fireboxes  
Installation  
Planning  
Installing Outside Air Kit  
In planning the installation for the firebox it is neces-  
sary to determine where the unit is to be installed and  
whether optional accessories are desired. Gas supply  
piping should also be planned.  
An outside air kit may be installed in all UVSTR/CVR  
Series fireboxes. If desired, or if local codes man-  
date the use of an air kit, then an AKU2 is required to  
complete the installation (from air kit to out-of-doors).  
If the outside air kit is to be used, the AKU2 MUST be  
installed BEFORE the fireplace is enclosed. Refer to  
the AKU2 instructions for field installation.  
These models may NOT be installed in a bedroom  
or bathroom.  
Glass doors are NOT available for these fireboxes.  
The firebox can be mounted on any of the following  
surfaces:  
A flat hard combustible surface.  
A raised platform of combustible or noncombustible  
material.  
Nail Top  
Standoffs  
A concrete block or other solid object placed be-  
neath each of the four corners of the appliance.  
Nail Eight  
Side-Nailing  
Flanges  
If the firebox is installed directly on carpeting, tile or  
other combustible material other than wood flooring, it  
should be installed on a metal or wood panel extending  
the full width and depth of the unit.  
At this point, you should have decided what compo-  
nents to include in your installation, and where the  
firebox is to be located. If this has not been done, stop  
and consult your dealer for planning assistance.  
UVSTR36  
Framing  
Firebox framing can be built before or after the firebox  
is set in place. Framing should be positioned to ac-  
commodate wall covering and firebox facing material.  
The firebox framing should be constructed of 2 x 4 or  
heavier lumber. The framing headers may rest on the  
top of the firebox standoffs Refer to Figs. 1 and 2 for  
firebox framing dimensions.  
Nail Top  
Standoffs  
Nail Four  
Side-Nailing  
Flanges  
Anchor Firebox in Position  
To prevent shifting of the firebox and to maintain sealing  
(described later), anchor the firebox. Two methods are  
possible for these fireboxes.  
UVCVR36  
One method is to use the eight fastening tabs (four  
with cove model) provided with the firebox. (Fig. 5) The  
firebox may be secured to the vertical framing members  
with these tabs and nails or other suitable fasteners.  
FP680  
Fig. 5 Adjustable drywall strip (nailing flange).  
The second method uses the standoffs at the front of  
the firebox. A nail may be installed through the standoffs  
and into the header to stabilize the top of the firebox.  
(Fig. 5)  
7412960  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
UVSTR / UVCVR Series Vent-Free Fireboxes  
NOTE: The gas line connection to the log set can be  
made with properly tinned 3/8" copper tubing, 1/2" rigid  
pipe, or an approved flex connector. Because some mu-  
nicipalities have additional local codes, it is always best  
to consult your local authority.  
Connect the Gas Line  
Gas access holes are provided on both sides of the  
firebox.  
Check gas valve type. Use only the gas type indicated  
on the gas log rating plate. If the gas listed on the plate  
is not your type of gas supply, DO NOT INSTALL. Con-  
tact your Dealer for the proper model.  
U.S. INSTALLATIONS – Follow local codes and the  
National Fuel Gas Code ANSI Z223.1/NFPA 54.  
Always check for gas leaks with a mild  
soap and water solution. Do not use an  
open flame for leak testing.  
Always use an external regulator for all LP fireboxes to  
reduce the supply tank pressure to a maximum 14" w.c.  
This is in addition to the regulator fitted to the vent-free  
heater.  
When using copper or flex connector use only approved  
fittings. Always provide a union so that gas line can  
be easily disconnected for burner or fan servicing. See  
gas specification for pressure details and ratings.  
WARNING: Connection directly to an un-  
regulated LP tank can cause an explosion.  
For final connection of the gas log heater to the gas  
line, see Section 5 and Figure 6.  
Cold Climate Insulation  
In cold climates, insulation of the enclosure around the  
firebox is suggested to avoid problems with cold air.  
1/2" Gas Supply  
1/2" x 3/8" Shut-Off Valve  
Insulating the enclosure around the firebox is recom-  
mended, but not a requirement  
3/8" Nipple  
3/8" Union  
The following steps are suggested to minimize cold air  
problems.  
3/8"  
Insulate the base of the firebox with a noncombustible  
insulation. This step is particularly important for outside  
wall installations over concrete slab floor construction.  
If a platform is used to raise the firebox, the insulation  
should be placed onto the platform before the firebox is  
set. (Fig. 7)  
Nipple  
Gas Supply Line  
FP598  
Fig. 6 Typical gas supply installation.  
Refer to Page 5, Figure 3 for minimum clearances to  
combustibles.  
Install Gas Log Heater  
Inspect joints of the firebox as well as the points of seal-  
ing between the firebox and the finishing materials.  
1. Connect the shutoff valve, union and any required  
approved fittings (See NOTE below) between the valve  
and the gas line.  
When a firebox is installed in a chase or on an outside  
wall, the enclosure should be insulated like any other  
outside wall of the home. Plywood or hardboard may  
be placed on the standoffs and insulation placed on this  
surface. (Fig. 8)  
Access to the gas line on the UV Series firebox is made  
through the left or right side of the firebox. Locate the  
appropriate gas line in the outer casing of the firebox  
and remove the insulation from the gas line tube.  
From the inside of the firebox, locate the knockout on  
the firebrick - be sure you are on the appropriate or gas  
line side of the firebox. Using a flat- bladed screwdriver  
or small chisel and hammer, carefully tap around the  
knockout until it loosens and falls out.  
2. Install the Vent-Free Gas Log Heater exactly as  
described in the instructions for the heater. If for any  
reason, you do not have these instructions, contact  
your dealer or manufacturer for another copy.  
7
7412960  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UVSTR / UVCVR Series Vent-Free Fireboxes  
Finishing  
See Page 5, Figure 3 for allowable finishing materials  
and clearances to combustibles.  
Hard Flat  
Surface  
All joints (top, bottom and sides), where the wall or  
decorative facing material meets the firebox surround  
must be completely sealed with a noncombustible ma-  
terial. Refer to Figures 9-12.  
Hearth Extension  
A hearth extension may be used but is not required for  
these fireboxes.  
Top View  
Insulation  
Noncombustible  
Caulking/Insulation  
2 x 4 Stud  
Standoff  
Platform  
FP681  
Finishing Material  
Fireplace Front  
FP684  
Fig. 7 Insulation between firebox and platform.  
Fig. 9 Seal spaces between firebox and finishing materials.  
Finished Wall  
See mantel drawing for  
shelf-to-surround dimen-  
Insulation  
sion  
Stud  
Mantel Shelf  
Plywood  
Support  
2 x 4 Finished  
Header  
Seal with noncombus-  
tible material ONLY  
Standoff  
Surround  
Fireplace  
Front  
Top View  
Side  
View  
1/2"  
Finished Wall  
May be sealed with noncombustible  
material  
FP682  
Fireplace Front  
FP683  
Fig. 8 Additional insulating methods. UVSTR36 shown.  
Fig. 10 Surround flush with finished wall.  
7412960  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
UVSTR / UVCVR Series Vent-Free Fireboxes  
4¹⁄₄" Max.  
Finished Wall  
2 x 4 Finished  
Header  
Must be sealed with  
noncombustible mate-  
rial  
Brick Sur-  
face  
Standoff  
Noncombustible  
Decorative Fac-  
ing  
Extended  
Hood  
Surround  
FP610  
Fig. 11 Appliance surround flush with finish wall.  
FP685  
2 x 4 Finished Header  
Finished Wall  
Covered Wall  
Fig. 13 Side view of firebox with extended hood.  
Must be sealed with non-  
combustible material  
Noncombustible  
Decorative Fac-  
ing  
Standoff  
Surround  
FP611  
Fig. 12 Facing on firebox flush with finished wall.  
Slot  
Screw  
(Fastens to  
side rail from  
inside hood)  
Install Hood  
A 2" or 4" Hood can be purchased for the UVSTR36  
and the UVCVR36. A Hood must be installed if the  
mantel falls within the dimensions and location shown  
in Figure 3. Failure to do so may create a fire hazard.  
Use Top Slot  
WARNING: When the black surround is covered  
by a brick surface, (Fig. 13), use an extended hood.  
The hood should extend out to the brick surface  
(Refer to Figs. 13 and 14) and be attached to the  
firebox. The maximum brick to noncombustible sur-  
face that may extend out past the black surround  
surface is 4¹⁄₄".  
Screw  
FP613  
Fig. 14 Hood location.  
The size of the Hood required depends on BTU ratings  
and clearances. See the Accessories section on Page  
13 for details.  
9
7412960  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UVSTR / UVCVR Series Vent-Free Fireboxes  
Maintenance  
Keep the control compartment, logs and burner area  
surrounding the logs clean by carefully vacuuming or  
brushing at least twice a year or as necessary.  
THE LOGS CAN GET VERY HOT – HANDLE ONLY  
WHEN COOL.  
Firebox  
Model and serial numbers are listed on the rat-  
ing plate (located on right side of combustion  
chamber).  
Always turn off the gas to the pilot before cleaning. For  
relighting, refer to the lighting instructions located on  
the Rating Plate of the gas log set.  
Record your model and serial numbers here for  
future reference:  
Never obstruct the flow of combustion and ventilation  
air, Keep the front of the appliance clear of all obstacles  
and materials.  
Model #  
Serial #  
____________________________  
____________________________  
Leave at least a 36" clearance from the front of the  
firebox to any room furnishings.  
Contact CFM Corporation for questions concerning  
prices and policies covering replacement parts. Parts  
may be ordered through your Majestic Fireplaces dis-  
tributor or dealer.  
Vent-free Log Heater  
Record your model and serial numbers here for  
future reference:  
You will need the following information when ordering  
replacement parts:  
Model #  
Serial #  
____________________________  
____________________________  
1. The appliance model number.  
2. The serial number.  
3. A description of the part.  
Should you need additional information beyond what  
your dealer can furnish, contact:  
CFM Corporation  
410 Admiral Meadowvale Blvd.  
Mississauga, Ontario  
Canada L5N 8A3  
7412960  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UVSTR / UVCVR Series Vent-Free Fireboxes  
1
2
3
6
4
5
7
CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time,  
without notice.  
UVCVR Vent Free Firebox  
Ref. Description  
UVCVR  
3079148  
3079147  
3087102  
3036118  
3090102  
3080137  
20003212  
1. Brick - Filler  
2. Brick - Side  
3. Brick - Hearth  
4. Screen Assembly (Screens and Rod)  
5. Brick - Hearth End  
6. Screen Assembly - End  
7. O.S.A. Assy.  
11  
7412960  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UVSTR / UVCVR Series Vent-Free Fireboxes  
1
2
3
5
4
CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time,  
without notice.  
UVSTR Vent Free Firebox  
Ref. Description  
UVSTR  
1. Brick - Filler  
2. Brick - Side  
3. Brick - Hearth  
4. Screen Assembly (Screens and Rod)  
5. O.S.A. Assy  
3079148  
3079147  
3087102  
3049121  
20003212  
7412960  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UVSTR / UVCVR Series Vent-Free Fireboxes  
Accessories  
The following accessories for these appliances are available from your local Majestic Fireplaces distributor. Each ac-  
cessory comes with a separate installation instruction for mounting to the particular firebox. Be sure to read  
each instruction thoroughly before installing.  
See your Majestic Fireplaces distributor or dealer for other finishing options such as marble and mantels — available  
in a wide selection of styles.  
Accessory  
Description  
Model Number  
Outside Air  
Completes connection from air kit to out-of-doors  
Termination  
AKU2  
Polished Brass  
Finish  
Black Finish  
2" Hood  
4" Hood  
4" Hood  
4" Hood  
For heater up to 40,000 BTU's with a  
mantel 8" wide by 28" high  
For heater up to 40,000 BTU's with a  
mantel 8" wide by 12" high  
Extended Hood for brick facings and heater up to  
40,000 BTUs and mantel 8" wide by 12" high  
Glass Hood for heater up to 40,000 BTUs  
and mantel 8" wide by 12" high  
UV36BH2  
UV36BH4  
UV36BH4E  
UV36GH4  
UV36PH2  
UV36PH4  
UV36PH4E  
--  
CAUTION: This firebox is a highly engineered system, and, as such, must be operated only with CFM  
Corporation approved components. If you use an unapproved component to make any modifications, you  
may create a possible fire hazard and will void CFM Corporation warranty. In addition, such action may void  
the coverage provided by the owner’s insurance.  
13  
7412960  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UVSTR / UVCVR Series Vent-Free Fireboxes  
7412960  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIMITED LIFETIME WARRANTY  
PRODUCT COVERED BY THIS WARRANTY  
All Vermont Castings gas stoves, gas inserts, and gas fireplaces, and all Majestic brand gas fireplaces equipped with  
an Insta-Flame Ceramic Burner, or standard steel tube burner.  
BASIC WARRANTY  
CFM Corporation (hereinafter referred to collectively as the Company)  
warrants that your new Vermont Castings or Majestic Gas Fireplace/  
Stove is free from manufacturing and material defects for a period of  
one year from the date of purchase, subject to the following conditions  
and limitations.  
Any part and/or component replaced under the provisions of this  
warranty is covered for six months or the remainder of the original  
warranty, whichever is longest.  
This warranty is limited to the repair of or replacement of part(s) found  
to be defective in material or workmanship, provided that such part(s)  
have been subjected to normal conditions of use and service, after  
said defect is confirmed by the Company’s inspection.  
EXTENDED LIFETIME WARRANTY  
The heat exchanger, where applicable, and combustion chamber  
of every Vermont Castings or Majestic gas product is warranted for  
life against through wall perforation. All appliances equipped with an  
Insta-Flame Ceramic Burner have limited lifetime coverage on the  
ceramic burner plaque. Warrantees are made to the original owner  
subject to proof of purchase and the conditions and limitations listed  
on this Warranty Document  
The company may, at its discretion, fully discharge all obligations  
with respect to this warranty by refunding the wholesale price of the  
defective part(s)  
Any installation, labor, construction, transportation, or other related  
costs/expenses arising from defective part(s), repair, replacement,  
or otherwise of same, will not be covered by this warranty, nor shall  
the Company assume responsibility for same. Further, the Company  
will not be responsible for any incidental, indirect, or consequential  
damages except as provided by law.  
COMPONENT WARRANTY  
CAST IRON: All external and internal cast iron parts are warranted for a  
period of three years.  
SOME STATES DO NOT ALLOW FOR THE EXCLUSION OR  
LIMITATIONS OF INCIDENTALAND CONSEQUENTIAL DAMAGES  
OR LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY  
LASTS, SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOUR  
CIRCUMSTANCES. THIS WARRANTY GIVES YOU SPECIFIC  
RIGHTSAND YOU MAY HAVE OTHER RIGHTS WHICH VARY FROM  
STATE TO STATE.  
Note: On porcelain enamel finished external parts and accessories  
The Company offers no Warranty on chipping of enamel surfaces.  
Inspect all product prior to accepting it for any damage to the  
enamel.  
The salt air environment of coastal areas or a high humidity  
environment can be corrosive to the porcelain enamel finish. These  
conditions can cause rusting of the cast iron beneath the porcelain  
enamel finish, which will cause the finish to flake off.  
All other warranties-expressed or implied- with respect to the product,  
its components and accessories, or any obligations/liabilities on the  
part of the Company are hereby expressly excluded.  
Dye lot variations with replacement parts and/or accessories can  
occur and are not covered by warranty.  
The Company neither assumes, nor authorizes any third party to  
assume on its behalf, any other liabilities with respect to the sale of  
this Vermont Castings or Majestic product  
GLASS DOORS: Glass doors are covered for a period of one year.  
Glass doors are not warranted for breakage due to misuse or accident.  
Glass doors are not covered for discoloration or burned in stains due to  
environmental issues, or improper cleaning and maintenance.  
The warranties as outlined within this document do not apply to  
chimney components or other non CFM Corporation accessories used  
in conjunction with the installation of this product..  
BRASS PLATED PARTS AND ACCESSORIES: Brass parts should be  
cleaned with Lemon oil only. Brass cleaners cannot be used. Mortar  
mix and masonry cleaners may corrode the brass finish. The Company  
will not be responsible for, nor will it warrant any brass parts which are  
damaged by external chemicals or down draft conditions.  
Damage to the unit while in transit is not covered by this warranty but  
is subject to claim against the common carrier. Contact the dealer  
from whom you purchased your fireplace/stove (do not operate the  
appliance as this might negate the ability to process the claim with the  
carrier).  
GAS VALVES: Gas valves are covered for a period of one year  
The Company will not be responsible for:  
ELECTRONIC AND MECHANICAL COMPONENTS: Electronic and  
mechanical components of the burner assembly are covered for one  
year. All steel tube burners are warranted for one year.  
a) Down drafts or spillage caused by environmental conditions such  
as near-by trees, buildings, roof tops, hills, or mountains.  
b) Inadequate ventilation or negative air pressure caused by  
mechanical systems such as furnaces, fans, clothes dryers, etc.  
ACCESSORIES: Unless otherwise noted all components and CFM  
Corporation company supplied accessories are covered for a period of  
one year.  
This warranty is void if:  
a) The fireplace has been operated in atmospheres contaminated by  
chlorine, fluorine, or other damaging chemicals.  
CONDITIONS AND LIMITATIONS  
b) The fireplace has been subjected to prolonged periods of  
dampness or condensation  
c) Any damages to the fireplace, combustion chamber, heat  
exchanger or other components due to water, or weather damage,  
which is the result of but not limited to, improper chimney/venting  
installation.  
This new Vermont Castings or Majestic product must be installed by  
a competent, authorized, service contractor. A licensed technician, as  
prescribed by the local jurisdiction must perform any installation/service  
work. It must be installed and operated at all times in accordance with  
the Installation and Operating instructions furnished with the product.  
Any alteration, willful abuse, accident, or misuse of the product shall  
nullify this warranty.  
d) Any alteration, willful abuse, accident, or misuse of the product  
This warranty is non-transferable, and is made to the original owner,  
provided that the purchase was made through an authorized supplier  
of the Company.  
has occurred.  
IF WARRANTY SERVICE IS NEEDED…  
1) Contact your supplier. Make sure you have your warranty,  
your sales receipt, and the model/serial number of your  
CFM Corporation product.  
2) DO NOT ATTEMPT TO DO ANY SERVICE WORK  
YOURSELF.  
The customer must pay for anyAuthorized Dealer in-home travel fees  
or service charges for in-home repair work. It is the dealers option  
whether the repair work will be done in the customer’s home or in the  
dealer’s shop.  
If upon inspection, the damage is found to be the fault of the  
manufacturer, repairs will be authorized at no charge to the customer  
parts and/or labor.  
15  
7412960  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CFM Corporation  
2695 Meadowvale Blvd. • Mississauga, Ontario, Canada L5N 8A3  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Black Decker Cordless Sander BDERO100 User Manual
Black Decker Saw 7662 User Manual
Bose Speaker System 16 Series II, 15 Series III User Manual
Brainboxes Network Card UC 101 User Manual
Brother Sewing Machine 2500D User Manual
Candy Washer CB 63 TR User Manual
Canon All in One Printer 2230 User Manual
Canon Camcorder DC 100 User Manual
Canon Camera Lens 2537A003 User Manual
Carrier Thermostat 33CS250 01 User Manual