Bosch Appliances Smoke Alarm D9124 User Manual

Fire Alarm Systems | D9124 Addressable Fire Alarm Control Panel (FACP)  
D9124 Addressable Fire Alarm Control  
Panel (FACP)  
24 VDC, 4 A power for initiation circuits and NACs;  
12 VDC, 1.4 A power for system accessories  
Up to eight supervised or 32 unsupervised remote  
annunciators  
One-man Fire Test Mode  
Schedules (Skeds function) service reminder for local  
systems  
Low battery, AC power supply, and battery lead  
supervision  
Dual phone line monitor  
The D9124 FACP controls complex alarm systems used in  
schools, universities, manufacturing plants, and health care  
facilities. Program it for fire, fire supervisory, intrusion, or  
access control applications. Program it locally using the  
D5200CE hand-held programmer or remotely using RPS  
over telephone lines or local-area or wide-area networks  
(LAN or WAN).  
Five system power trouble conditions are selected by DIP  
switches. They can be individually linked to a central  
station, or grouped to activate a trouble relay, allowing a  
single supervised address to monitor the power supply.  
A pair of 12 V batteries provides standby power. Two  
additional batteries provide standby power for initiating  
devices and notification appliances. All four batteries are  
housed within the panel enclosure.  
The D9124 FACP is a modular assembly, installed in a red  
steel enclosure, which can be surface- or flush-mounted.  
The enclosure has keyed controller access making it  
suitable for installation in public access areas.  
Note  
Batteries are not included in the D9124 and  
must be purchased separately.  
Central Station Communication  
Events can be communicated to a central station by the  
digital communicator or by adding an optional Ethernet  
interface module. The optional Bosch D6500 or D6600  
Functions  
Alarm Verification  
2
NetCom Receiver and Modem IIIa reporting format provide  
The alarm verification feature reduces potential false alarms  
by requiring a reset and a second alarm signal from the  
device before the control panel raises an alarm condition.  
individual point reporting to monitoring facilities.  
The D5500 Remote Programming Software (RPS) allows  
the following to be controlled from a central station:  
Auxiliary and Standby Power  
Resetting notification appliances  
Activating or deactivating remote annunciation  
Activating or deactivating relays  
Supervising battery condition  
Setting point status and armed status  
Enabling or disabling reporting functions  
Shunting reporting points during servicing  
The 4 A, 24 VDC power supply charges the standby batteries  
and powers auxiliary devices. The power supply responds  
to low battery or battery disconnect conditions with a  
Trouble LED and a Trouble Relay for sounders or lights.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
D9124 Addressable Fire Alarm Control Panel (FACP) | 3  
Technical Specifications  
Category  
Product ID  
D192G  
Product Description  
Bell supervision module  
POPEX module  
Environmental Considerations  
D8125  
Relative Humidity:  
Up to 85%; non-condensing  
D8125MUX Zonex to dual multiplex interface  
Temperature (operating):  
+32°F to +122°F (0°C to +50°C)  
D8128D  
D8129  
OctoPOPIT module  
Inputs  
Octo-relay module  
D8130  
Release module  
Sensor Circuits:  
Up to two 8125 POPEX modules,  
119 addresses per module  
D9127U  
D9127T  
D9131A  
DX4020  
POPIT module (no tamper)  
POPIT module (tamper)  
Parallel printer interface module  
Ethernet interface module  
Handheld programmer  
Sensor Circuit Protection:  
Power limited to 4 A; short circuit, reverse  
polarity, thermal overload and current over-  
load protection on-board  
Sensor Loop Technology:  
Four-wire addressable circuits  
Programming D5200CE  
Products  
Mechanical Properties  
RPS  
Remote Programming Software  
Remote Programming Software  
Remote Programming Software  
Color:  
Red  
RPS-LITE  
RPS-INTL  
Material:  
16-gauge (1.5 mm) steel  
Dimensions (H x W x D)  
Enclosure Box:  
36.1 in. x 22.1 in. x 3.2 in.  
(92 cm x 56 cm x 8.1 cm)  
Parts Included  
Removable Door:  
37.1 in. x 23.3 in. x 1.1 in.  
(94 cm x 59 cm x 2.8 cm)  
The D9124 Addressable Control Panel is shipped in three  
boxes. One box contains:  
Outputs  
Quant.  
Component  
Off-board relays:  
Up to 16 optional D8129 Relay Modules (eight re-  
lay outputs per module)  
1
D9412GLTB Control Panel (less terminal blocks)  
On-board NACs:  
Two; 1.8 A maximum per circuit  
Another box contains:  
Power Requirements  
Quant.  
Component  
Current (operating)  
Alarm + sensor load:  
Idle:  
1
D9101 Enclosure Assembly with Door  
874 mA  
The third box contains a D9100 Accessory Module Carrier  
that includes the following:  
412 mA  
Power (auxiliary):  
Power (primary):  
24 VDC nominal at 1.8 A  
120 VAC, 60 Hz, 360 VA  
Quant.  
Component  
2
1
1
1
D192C Indicating Circuit Supervision Modules  
D928 Dual Phone Line Switcher  
D8125 POPEX Module (additional optional)  
D9142LC 24 VDC Power Supply  
Ordering Information  
D9124 Addressable Fire Alarm Control  
Panel (FACP)  
Up to eight supervised or 32 unsupervised re-  
mote annunciators  
D9124  
D113  
The third box also contains:  
Quant.  
Component  
Accessories  
1
1
1
1
2
2
1
1
D1256 Fire Alarm Keypad  
D1601 Transformer  
D113 Battery Lead Supervision Module  
Supervises wiring connections for two 12 V  
batteriesconnectedtothesamesetofcharging  
terminals.  
Wiring Harness  
Wiring Harness for the D8125 POPEX Module  
560 Ω Resistors (for D192C Modules)  
D161 Dual Modular Telephone Cords  
D162 Dual Modular Telephone Cord  
Literature pack  
D122 Dual Battery Harness  
Harness with circuit breaker. Connects two  
batteries to a compatible control panel.  
D122  
D135A Low‑battery Disconnect Module  
Disconnects the control panel from the battery  
when the battery level drops to 9.5 VDC.  
D135A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4 | D9124 Addressable Fire Alarm Control Panel (FACP)  
Ordering Information  
D127 Reversing Relay Module  
Reports two separate alarm conditions to the  
central station.  
D127  
D136  
D136 Plug‑In Relay  
Maximum rating is 1 A at 24 VDC or 2 A at  
12 VDC. Available individually (D136) or in a  
package of 25 (D136‑25).  
D138 Mounting Bracket, Right Angle  
Used to mount accessory modules in D8103,  
D8108A, and D8109 enclosures.  
D138  
Americas:  
Bosch Security Systems, Inc.  
130 Perinton Parkway  
Europe, Middle East, Africa:  
Bosch Security Systems B.V.  
P.O. Box 80002  
Asia-Pacific:  
Robert Bosch (SEA) Pte Ltd, Security Systems  
11 Bishan Street 21  
Represented by  
Fairport, New York, 14450, USA  
Phone: +1 800 289 0096  
Fax: +1 585 223 9180  
5600 JB Eindhoven, The Netherlands  
Phone: + 31 40 2577 284  
Fax: +31 40 2577 330  
Singapore 573943  
Phone: +65 6258 5511  
Fax: +65 6571 2698  
© Bosch Security Systems Inc. 2010 | Data subject to change without notice  
T1113332363 | Cur: en-US, V5, 4 Jul 2010  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Beko Washer WM5101W User Manual
Black Decker Grinder KG2001 User Manual
Blaupunkt Stereo Receiver PCA460 User Manual
Bowflex Home Gym Revolution User Manual
Broil King Griddle GRD550 User Manual
Cecilware Boiler ME10 GN User Manual
Century Car Seat 45100 User Manual
Channel Vision Home Security System P 0921 User Manual
ChefScape Blender SE650 User Manual
Cisco Systems Conference Phone CP7921GAK9RF User Manual