AO Smith Water Heater ARGSS02708 User Manual

Instruction Manual  
RESIDENTIAL GAS WATER HEATERS  
POWER VENTED GAS MODELS W/HOT SURFACE IGNITION  
NOT FOR USE IN MANUFACTURED (MOBILE) HOMES  
Ashland City, TN 37015  
www.hotwater.com  
For Your Safety •  
AN ODORANT IS ADDED TO THE GAS USED  
BY THIS WATER HEATER.  
ALL TECHNICAL AND WARRANTY QUESTIONS: SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS  
PURCHASED. IF YOU ARE UNSUCCESSFUL, PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER.  
KEEP THIS MANUAL IN THE POCKET ON HEATER FOR FUTURE REFERENCE  
WHENEVER MAINTENANCE ADJUSTMENT OR SERVICE IS REQUIRED.  
PRINTED 1207  
197423-002  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GENERAL SAFETY  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
GENERAL SAFETY  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
SAFE INSTALLATION, USE AND SERVICE ........................... 2  
Vent Attenuation Assembly Installation Instructions .......21-22  
Vent Pipe Preparation .............................................. 23-24  
LIGHTING & OPERATING LABEL ........................................25  
TEMPERATURE REGULATION ............................................26  
FOR YOUR INFORMATION ..................................................27  
Start Up Conditions  
GENERAL SAFETY ............................................................. 3-4  
TABLE OF CONTENTS ...........................................................5  
INTRODUCTION .....................................................................5  
Preparing for the Installation ............................................5  
TYPICAL INSTALLATION .................................................... 6-8  
LOCATING THE NEW WATER HEATER ........................... 9-11  
Facts to Consider About Location .............................. 9-10  
Insulation Blankets .........................................................10  
Combustion Air and Ventilation for Appliances  
Smoke/Odor ...........................................................27  
Thermal Expansion .................................................27  
Strange Sounds ......................................................27  
Operational Conditions ...................................................27  
Smelly Water ..........................................................27  
“Air” in Hot Water Faucets ......................................27  
High Temperature Shut Off System ........................27  
PERIODIC MAINTENANCE ............................................ 28-30  
Venting System Inspection .............................................28  
Burner Operation and Inspection ...................................28  
Burner Cleaning .............................................................28  
Housekeeping .......................................................... 28-29  
Anode Rod Inspection ....................................................29  
Temperature-Pressure Relief Valve Operation ..............29  
Draining ..........................................................................29  
Service ...........................................................................30  
LEAKAGE CHECKPOINTS ...................................................30  
REPAIR PARTS .....................................................................31  
TROUBLESHOOTING ..................................................... 32-34  
WARRANTY ..........................................................................35  
Located in Unconfined Spaces.......................................10  
Combustion Air and Ventilation for Appliances  
Located in Confined Spaces ..................................... 10-11  
INSTALLING THE WATER HEATER ............................... 12-24  
Chemical Vapor Corrosion .............................................12  
Water Piping ............................................................. 12-13  
Temperature-Pressure Relief Valve ...............................13  
Gas Piping ......................................................................14  
Sediment Traps ..............................................................15  
Filling the Water Heater .................................................15  
Vent Pipe Assembly .......................................................15  
Venting ...........................................................................15  
Vent Pipe Termination ....................................................16  
Planning the Vent System ..............................................17  
Condensate .............................................................. 17-18  
Blower Assembly Installation..........................................18  
Installation of Vent System ....................................... 18-20  
INTRODUCTION  
2. The installation must conform with these instructions and the  
local code authority having jurisdiction. In the absence of local  
codes, installations shall comply with the National Fuel Gas Code  
(ANSI Z223.1/NFPA 54) or the Natural Gas and Propane  
Installation Code (CAN/CSA B149.1) and the National Electrical  
Code (NFPA70), or the Canadian Electrical Code (C22.1). These  
publications are available from The National Fire Protection  
Association, 1 Batterymarch Park, Quincy, MA 02269.  
Thank You for purchasing this water heater. Properly installed and  
maintained, it should give you years of trouble free service.  
Abbreviations Found In This Instruction Manual:  
• CSA - Canadian Standards Association  
• ANSI - American National Standards Institute  
• NFPA - National Fire Protection Association  
• ASME - American Society of Mechanical Engineers  
• GAMA - Gas Appliance Manufacturer’s Association  
• UL - Underwriters Laboratories Inc.  
3. The water heater when installed must be grounded in accordance  
with the local codes, or in the absence of local codes: the National  
Electrical Code (NFPA70) or the Canadian Electrical Code (C22.1).  
4. If after reading this manual you have any questions or do not  
understand any portion of the instructions, call the local gas utility  
or the manufacturer whose name appears on the rating plate.  
This gas-fired water heater is design certified by Underwriters  
Laboratories Inc. under American National Standard/CSA Standard  
for Gas Water Heaters ANSI Z21.10.3 • CSA 4.3 (current edition).  
5. Carefully plan the place where you are going to put the water  
heater. Correct combustion, vent action, and vent pipe installation  
are very important in preventing death from possible carbon  
monoxide poisoning and fires, see Figures 1 and 2.  
PREPARING FOR THE INSTALLATION  
Examine the location to ensure the water heater complies with  
the “Locating the New Water Heater” section in this manual.  
1. Read the “General Safety” section, page 3 and 4 of this manual  
first and then the entire manual carefully. If you don’t follow the safety  
rules, the water heater will not operate properly. It could cause  
DEATH, SERIOUS BODILY INJURYAND/OR PROPERTY DAMAGE.  
6. For California installation this water heater must be braced,  
anchored, or strapped to avoid falling or moving during an  
earthquake. See instructions for correct installation procedures.  
Instructions may be obtained from California Office of the State  
Architect, 400 P Street, Sacramento, CA 95814.  
This manual contains instructions for the installation, operation, and  
maintenance of the gas-fired water heater. It also contains warnings  
throughout the manual that you must read and be aware of. All  
warnings and all instructions are essential to the proper operation of  
the water heater and your safety. Since we cannot put everything  
on the first few pages, READ THE ENTIRE MANUAL BEFORE  
ATTEMPTING TO INSTALLOR OPERATE THE WATER HEATER.  
7. Massachusetts Code requires this water heater to be installed in  
accordance with Massachusetts 248-CMR 2.00: State Plumbing  
Code and 248-CMR 5.00.  
8. Complies with SCAQMD rule #1146 and districts having equivalent  
NOx requirements.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL INSTALLATION  
GET TO KNOW YOUR WATER HEATER - GAS MODELS  
H H Bushing  
II Nipple  
JJ Condensate Tee  
KK Hose Barb  
LL Plug  
MM Vent Pipe Assembly #1  
NN Vent Pipe Assembly #2  
OO Vent Pipe Assembly #3  
PP Side Recirculation Loop  
Inlet***  
Q Q Side Recirculation Loop  
Outlet*** (not shown)  
R R Vent Attenuation  
Assembly (VAA) (Optional)  
SS Access Door  
A
B
C
D
F
G
H
J
K
L
M
N
O
P
Vent Pipe  
Anode  
Hot Water Outlet  
Outlet (120 VAC)  
Gas Supply  
Main Manual Gas Shut Off Valve  
Ground Joint Union  
Dirt Leg  
Outer Door  
Union  
Inlet Water Shut Off Valve  
Cold Water Inlet  
Inlet Dip Tube  
Temperature & Pressure  
Relief Valve  
Q
R
S
Rating Plate  
Insulation  
Vent Terminal  
Drain Valve  
Igniter And Main Burner  
Drain Pan  
T
U
W
X
Control  
Control Harness*  
Y
AA Motor & Blower  
CC Condensate Fitting  
(4 Places Shown)**  
D D Plastic Top  
E E On/Off Switch  
F F Exhaust Tee  
G G Elbow  
REPLACEMENT PARTS AND DELIMING  
PRODUCTS  
Replacement parts and recommended delimer may be ordered through  
authorized servicers or distributors. When ordering parts, provide complete  
model and serial numbers (see rating plate), quantity and name of part  
desired. Standard hardware items may be purchased locally.  
CONDENSATE ASSEMBLY  
(U) NATURAL GAS MAIN BURNER  
WITH IGNITER ASSEMBLY  
SIDE VIEW  
TEMPERATURE INDICATORS  
(X)  
VACUUM RELIEF  
VALVE  
*INSTALL PER  
LOCAL CODES  
* CAUTION HARNESS HAS 120 VAC. IN OPERATION.  
** See "PLANNING THE VENT SYSTEM", "CONDENSATE" and "BLOWER ASSEMBLY INSTALLATION" for  
more information.  
***The side recirculation loop connections may not be used as the primary water inlet and outlet connections.  
For your convenience, plugs are installed in these fittings at the factory. Remove these plugs if needed for  
your specific installation. Otherwise (as with all connections) check for leaks while filling the tank with  
water and after completing the installation.  
TEMPERATURE ADJUSTMENT BUTTONS  
FIGURE 1  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL INSTALLATION  
CONDENSATE HOSE AND DRAIN PAN  
* Note: Condensate Trap Loops must be oriented in a vertical plane as shown. The traps  
also must be primed by filling half of the loop with water prior to operating the water heater.  
Carefully plan the location of the loops and straight sections of hose prior to cutting hoses.  
If necessary, secure the hoses to the side of the water heater or some other rigid structure  
to prevent crimping. While securing the hoses, do not pierce or crimp the hoses.  
FIGURE 1 (continued).  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL INSTALLATION  
MIXING VALVE USAGE  
FIGURE 2.  
This appliance has been design certified as complying withAmerican  
National Standard/CSAStandard for water heaters and is considered  
HOTTER WATER CAN SCALD:  
suitable for:  
Water heaters are intended to produce hot water. Water heated to a  
temperature which will satisfy space heating, clothes washing, dish  
washing, and other sanitizing needs can scald and permanently injure  
you upon contact. Some people are more likely to be permanently  
injured by hot water than others. These include the elderly, children,  
the infirm, or physically/mentally handicapped. If anyone using hot  
water in your home fits into one of these groups or if there is a local  
code or state law requiring a certain temperature water at the hot  
water tap, then you must take special precautions. In addition to  
using the lowest possible temperature setting that satisfies your hot  
water needs, a means such as a Mixing Valve, shall be used at the hot  
water taps used by these people or at the water heater. Mixing valves  
are available at plumbing supply or hardware stores. Consult a Qualified  
Installer or Service Agency. Follow mixing valve manufacturer’s  
instructions for installation of the valves. Before changing the factory  
setting on the thermostat, read the “Temperature Regulation” section in  
this manual, see Figure 26.  
Water (Potable) Heating and Space Heating: All models are  
considered suitable for water (potable) heating and space heating.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
LOCATING THE NEW WATER HEATER  
FACTS TO CONSIDERABOUT THE LOCATION  
Carefully choose an indoor location for the new water heater, because  
the placement is a very important consideration for the safety of the  
occupants in the building and for the most economical use of the  
appliance. This water heater is not for use in manufactured  
(mobile) homes or outdoor installation.  
Whether replacing an old water heater or putting the water heater in a  
new location, the following critical points must be observed:  
1. Select a location indoors as close as practical to the vent terminal or  
location to which the water heater vent piping is going to be connected,  
and as centralized with the water piping system as possible.  
2. Selected location must provide adequate clearances for servicing  
and proper operation of the water heater.  
Installation of the water heater must be accomplished in such a manner  
that if the tank or any connections should leak, the flow will not cause  
damage to the structure. For this reason, it is not advisable to install  
the water heater in an attic or upper floor. When such locations cannot  
be avoided, a suitable drain pan should be installed under the water  
heater. Drain pans are available at your local hardware store. Such  
a drain pan must have a clearance of at least 1.0" (2.5cm) greater  
than any point on the water heater’s outer jacket and must be piped  
to an adequate drain. The pan must not restrict combustion air flow.  
For example, if a circular pan is used, it must be a minimum of 27"  
(69cm) in diameter. See Figure 1.  
Water heater life depends upon water quality, water pressure  
and the environment in which the water heater is installed. Water  
heaters are sometimes installed in locations where leakage may  
result in property damage, even with the use of a drain pan piped  
to a drain. However, unanticipated damage can be reduced or  
prevented by a leak detector or water shut-off device used in  
conjunction with a piped drain pan. These devices are available  
from some plumbing supply wholesalers and retailers, and detect  
and react to leakage in various ways:  
• Sensors mounted in the drain pan that trigger an alarm or turn off  
the incoming water to the water heater when leakage is detected.  
• Sensors mounted in the drain pan that turn off the water supply  
to the entire home when water is detected in the drain pan.  
• Water supply shut-off devices that activate based on the water  
pressure differential between the cold water and hot water pipes  
connected to the water heater.  
• Devices that will turn off the gas supply to a gas water heater  
while at the same time shutting off its water supply.  
INSTALLATIONS IN AREAS WHERE FLAMMABLE LIQUIDS  
(VAPORS) ARE LIKELY TO BE PRESENT OR STORED  
(GARAGES, STORAGEAND UTILITYAREAS, ETC.): Flammable  
liquids (such as gasoline, solvents, propane (LP or butane, etc.)  
and other substances (such as adhesives, etc.) emit flammable  
vapors which can be ignited by a gas water heater’s hot surface  
igniter or main burner. The resulting flashback and fire can cause  
death or serious burns to anyone in the area.  
This water heater must not be installed directly on carpeting.  
Carpeting must be protected by metal or wood panel beneath the  
appliance extending beyond the full width and depth of the appliance  
by at least 3" (7.6 cm) in any direction, or if the appliance is installed  
Also, the water heater must be located and/or protected so it is not  
subject to physical damage by a moving vehicle.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
If this water heater will be used in beauty shops, barber shops, cleaning  
establishments, or self-service laundries with dry cleaning equipment,  
it is imperative that the water heater or water heaters be installed so  
that combustion and ventilation air be taken from outside these areas.  
in an alcove or closet, the entire floor must be covered by the panel.  
Failure to heed this warning may result in a fire hazard.  
Propellants of aerosol sprays and volatile compounds, (cleaners,  
chlorine based chemicals, refrigerants, etc.) in addition to being highly  
flammable in many cases, will also react to form corrosive hydrochloric  
acid when exposed to the combustion products of the water heater.  
The results can be hazardous, and also cause product failure.  
INSULATION BLANKETS  
Insulation blankets are available to the general public for external use  
on gas water heaters but are not necessary with these products. The  
purpose of an insulation blanket is to reduce the standby heat loss  
encountered with storage tank heaters. Your water heater meets or  
exceeds the Energy Policy Act standards with respect to insulation and  
standby loss requirements, making an insulation blanket unnecessary.  
Minimum clearances between the water heater and combustible  
construction are0 inch at the sides and rear, 5.5"(14.0 cm)from the front  
and 12" (30.5 cm) from the top. (Standard clearance.) If clearances stated  
on the heater differ from standard clearances, install water heater  
according to clearances stated on the heater.  
Should you choose to apply an insulation blanket to this heater, you  
should follow these instructions (For identification of components  
mentioned below, see Figure 1). Failure to follow these instructions  
can restrict the air flow required for proper combustion, potentially  
resulting in fire, asphyxiation, serious personal injury or death.  
Adequate clearance 24" (61.0 cm) for servicing this appliance should  
be considered before installation, such as changing the anodes, etc.  
A minimum clearance of 5.5" (14.0 cm) must be allowed for access to  
replaceable parts such as the thermostats, drain valve and relief valve.  
When installing the heater, consideration must be given to proper location.  
Location selected should be as close to the wall as practicable and as  
centralized with the water piping system as possible.  
• Do not apply insulation to the top of the water heater, as this will  
interfere with safe operation of the blower assembly.  
• Do not cover the outer door, thermostat or temperature & pressure  
relief valve.  
• Do not allow insulation to come within 2" (5.1 cm) of the floor to  
prevent blockage of combustion air flow to the burner.  
• Do not cover the instruction manual. Keep it on the side of the  
water heater or nearby for future reference.  
• Do obtain new warning and instruction labels from the manufacturer  
for placement on the blanket directly over the existing labels.  
• Do inspect the insulation blanket frequently to make certain it  
does not sag, thereby obstructing combustion air flow.  
FIGURE 4.  
A gas water heater cannot operate properly without the correct  
amount of air for combustion. Do not install in a confined area  
such as a closet, unless you provide air as shown in the “Locating  
The New Water Heater” section. Never obstruct the flow of  
ventilation air. If you have any doubts or questions at all, call your  
gas supplier. Failure to provide the proper amount of combustion  
air can result in a fire or explosion and cause death, serious bodily  
injury, or property damage.  
COMBUSTION AIR AND VENTILATION FOR  
APPLIANCES LOCATED IN UNCONFINED SPACES  
UNCONFINED SPACE is space whose volume is not less than  
50 cubic feet per 1,000 Btu per hour (4.8 cubic meters per kW) of the  
aggregate input rating of all appliances installed in that space. Rooms  
communicating directly with the space in which the appliances are  
installed, through openings not furnished with doors, are considered  
a part of the unconfined space.  
In unconfined spaces in buildings, infiltration may be adequate to  
provide air for combustion, ventilation and dilution of flue gases.  
However, in buildings of tight construction (for example, weather  
stripping, heavily insulated, caulked, vapor barrier, etc.), additional air  
may need to be provided using the methods described in “Combustion  
Air and Ventilation for Appliances Located in Confined Spaces.”  
COMBUSTION AIR AND VENTILATION FOR  
APPLIANCES LOCATED IN CONFINED SPACES  
CONFINED SPACE is a space whose volume is less than 50 cubic  
feet per 1,000 Btu per hour (4.8 cm per kW) of the aggregate input  
rating of all appliances installed in that space.  
When drawing combustion air from inside a conventionally  
constructed building to a confined space, such a space shall be  
provided with two permanent openings. ONE WITHIN 12 INCHES  
(30 cm) OF THE ENCLOSURE TOPAND ONE WITHIN 12 INCHES  
(30 cm) OFTHEENCLOSUREBOTTOM. Eachopeningshallhaveafree  
FIGURE 5.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
area of one square inch per 1000 Btu/hr (22 cm2/kW) of the total input of  
all appliances in the enclosure, but not less than 100 square inches (645  
cm2).  
If the confined space is within a building of tight construction, air for  
combustion and ventilation must be obtained from outdoors. When  
directly communicating with the outdoors or communicating through  
vertical ducts, two permanent openings, located in the above manner,  
shall be provided. Each opening shall have a free area of not less  
than one square inch per 4000 Btu/hr (5.5 cm2/kW) of total input of all  
appliances in the enclosure. If horizontal ducts are used, each opening  
shall have a free area of not less than one square inch per 2000 Btu/  
hr (11cm2/kW) of the total input of all appliances in the enclosure.  
A. ALL AIR FROM INSIDE BUILDINGS: (See Figure 5 and 6)  
FIGURE8.  
The confined space shall be provided with two permanent openings  
communicating directly with an additional room(s) of sufficient volume  
so that the combined volume of all spaces meets the criteria for an  
unconfined space. The total input of all gas utilization equipment installed  
in the combined space shall be considered in making this determination.  
Each opening shall have a minimum free area of one square inch per  
1,000 Btu per hour (22 cm2/kW) of the total input rating of all gas utilization  
equipment in the confined space, but not less than 100 square inches  
(645 cm2). One opening shall commence within 12 inches  
(30 cm) of the top and one commencing within 12 inches (30 cm) of the  
bottom of the enclosures.  
4. When ducts are used, they shall be of the same cross-sectional  
area as the free area of the openings to which they connect. The  
minimum short side dimension of rectangular air ducts shall not be  
less than 3 inches (7.6 cm), see Figure 9.  
FIGURE9.  
5. Alternatively a single permanent opening may be used when  
communicating directly with the outdoors, or with spaces that freely  
communicate with the outdoors. The opening shall have a minimum  
free area of 1 square inch per 3,000 BTU per hour (8.3 cm2/kW) of  
total input rating of all equipment in enclosure. See Figure 9A.  
FIGURE6.  
B. ALL AIR FROM OUTDOORS: (See Figures 7, 8 and 9)  
The confined space shall be provided with two permanent openings,  
one commencing within 12 inches (30 cm) of the top and one  
commencing within 12 inches (30 cm) from the bottom of the  
enclosure. The openings shall communicate directly, or by ducts,  
with the outdoors or spaces (crawl or attic) that freely communicate  
with the outdoors.  
1. When directly communicating with the outdoors, each opening shall  
have a minimum free area of 1 square inch per 4,000 Btu per hour  
(5.5 cm2/kW) of total input rating of all equipment in the enclosure,  
see Figure 7.  
FIGURE9A.  
6. Louvers and Grilles: In calculating free area, consideration shall be  
given to the blocking effect of louvers, grilles or screens protecting  
openings. Screens used shall not be smaller than 1/4 inch (6.4 mm)  
mesh. If the free area through a design of louver or grille is known,  
it should be used in calculating the size opening required to provide  
the free area specified. If the design and free area is not known, it  
may be assumed that wood louvers will be 20-25 percent free area  
and metal louvers and grilles will have 60-75 percent free area.  
Louvers and grilles shall be fixed in the open position or interlocked  
with the equipment so that they are opened automatically during  
equipment operation.  
FIGURE7.  
2. When communicating with the outdoors through vertical ducts, each  
opening shall have a minimum free area of 1 square inch per 4,000  
Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the  
enclosure, see Figure 8.  
7. Special Conditions Created by Mechanical Exhausting or  
Fireplaces: operation of exhaust fans, ventilation systems, clothes  
dryers or fireplaces may create conditions requiring special  
attention to avoid unsatisfactory operation of installed gas  
utilization equipment.  
3. When communicating with the outdoors through horizontal ducts,  
each opening shall have a minimum free area of 1 square inch per  
2,000 Btu per hour (11 cm2/kW)) of total input rating of all equipment  
in the enclosure, see Figure 9.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLING THE NEW WATER HEATER  
Water supply systems may, because of such events as high line pressure,  
CHEMICALVAPORCORROSION  
frequent cut-offs, the effects of water hammer among others, have  
installed devices such as pressure reducing valves, check valves, back  
flow preventers, etc. to control these types of problems. When these  
devices are not equipped with an internal by-pass, and no other measures  
are taken, the devices cause the water system to be closed. As water is  
heated, it expands (thermal expansion) and closed systems do not allow  
for the expansion of heated water.  
CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY OCCUR IF  
AIRFORCOMBUSTIONCONTAINSCERTAINCHEMICALVAPORS.SUCH  
CORROSION MAY RESULT IN FAILUREAND RISK OF ASPHYXIATION.  
Spray can propellants, cleaning solvents, refrigerator and air  
conditioning refrigerants, swimming pool chemicals, calcium and  
sodium chloride (water softener salt), waxes, and process chemicals  
are typical compounds which are potentially corrosive.  
The water within the water heater tank expands as it is heated and increases  
the pressure of the water system. If the relieving point of the water heater’s  
temperature-pressure relief valve is reached, the valve will relieve the  
excess pressure. The temperature-pressure relief valve is not intended  
for the constant relief of thermal expansion. This is an unacceptable  
condition and must be corrected.  
Do not store products of this sort near the heater. Also, air which is  
brought in contact with the heater should not contain any of these  
chemicals. If necessary, uncontaminated air should be obtained from  
remote or outside sources. The limited warranty is voided when failure  
of water heater is due to a corrosive atmosphere. (See limited warranty  
for complete terms and conditions).  
It is recommended that any devices installed which could create a closed  
system have a by-pass and/or the system have an expansion tank to  
relieve the pressure built by thermal expansion in the water system.  
Expansion tanks are available for ordering through a local plumbing  
contractor. Contact the local water supplier and/or a service agency for  
assistance in controlling these situations.  
WATER PIPING  
NOTE: To protect against untimely corrosion of hot and cold  
water fittings, it is strongly recommended that di-electric unions  
or couplings be installed on this water heater when connected  
to copper pipe.  
All gas piping must comply with local codes and ordinances or with the National  
Fuel Gas Code (ANSI Z223.1/ NFPA-54) or the Natural Gas and Propane  
Installation Code (CAN/CSAB149.1) whichever applies. Copper and brass  
tubing and fittings (except tin lined copper tubing) shall not be used.  
HOTTER WATER CAN SCALD:  
Water heaters are intended to produce hot water. Water heated to a  
temperature which will satisfy space heating, clothes washing, dish  
washing, cleaning and other sanitizing needs can scald and permanently  
injure you upon contact. Some people are more likely to be permanently  
injured by hot water than others. These include the elderly, children, the  
infirm, or physically/mentally handicapped. If anyone using hot water in  
your home fits into one of these groups or if there is a local code or  
state law requiring a certain temperature water at the hot water tap,  
then you must take special precautions. In addition to using the lowest  
possible temperature setting that satisfies your hot water needs, a means  
such as a *mixing valve, shall be used at the hot water taps used by  
these people or at the water heater, see Figure 2. Valves for reducing  
point of use temperature by mixing cold and hot water are also available:  
Consult a Qualified Installer or ServiceAgency. Follow manufacturer’s  
instructions for installation of the valves. Before changing the factory  
setting on the thermostat, read the “Temperature Regulation” section  
in this manual.  
This water heater shall not be connected to any heating systems or  
component(s) used with a non-potable water heating appliance.  
All piping components connected to this unit for space heating applications  
shall be suitable for use with potable water.  
Toxic chemicals, such as those used for boiler treatment shall not be  
introduced into this system.  
When the system requires water for space heating at temperatures higher  
than required for domestic water purposes, a tempering valve must be  
installed. Please refer to Figure 2 for suggested piping arrangement.  
FIGURE10.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 10 shows the typical attachment of the water piping to the  
water heater. The water heater is equipped with 3/4 inch NPT water  
connections.  
The valve must be marked with a maximum set pressure not to exceed  
the marked hydrostatic working pressure of the water heater  
(150 psi = 1,035 kPa) and a discharge capacity not less than the  
water heater input rate as shown on the model rating plate.  
NOTE: If using copper tubing, solder tubing to an adapter before  
attaching the adapter to the water heater connections. Do not  
solder the water lines directly to the water heater connections.  
It will harm the dip tube and damage the tank.  
For safe operation of the water heater, the relief valve must not be  
removed from its designated opening nor plugged.  
The temperature-pressure relief valve must be installed directly into  
the fitting of the water heater designed for the relief valve. Position  
the valve downward and provide tubing so that any discharge will exit  
only within 6 inches (15.2 cm) above, or at any distance below the  
structural floor. Be certain that no contact is made with any live  
electrical part. The discharge opening must not be blocked or reduced  
in size under any circumstances. Excessive length, over 30 feet (9.14  
m), or use of more than four elbows can cause restriction and reduce  
the discharge capacity of the valve, see Figures 10 or 14.  
T & P Valve and Pipe Insulation (if supplied)  
Remove insulation for T & P valve and pipe connections from carton.  
No valve or other obstruction is to be placed between the relief valve  
and the tank. Do not connect tubing directly to discharge drain unless  
a 6" (15.2 cm) air gap is provided. To prevent bodily injury, hazard to  
life, or property damage, the relief valve must be allowed to discharge  
water in quantities should circumstances demand. If the discharge  
pipe is not connected to a drain or other suitable means, the water  
flow may cause property damage.  
FIGURE 11.  
Fit pipe insulation over the incoming cold water line and the hot water  
line. Make sure that the insulation is against the top cover of the  
heater.Fit T & P valve insulation over valve. Make sure that the  
insulation does not interfere with the lever of the T & P valve.  
Secure all insulation using tape.  
TEMPERATURE-PRESSURE RELIEF VALVE  
The Discharge Pipe:  
Shall not be smaller in size than the outlet pipe size of the valve, or  
have any reducing couplings or other restrictions.  
Shall not be plugged or blocked.  
Shall be of material listed for hot water distribution.  
Shall be installed so as to allow complete drainage of both the  
temperature-pressure relief valve, and the discharge pipe.  
Shall terminate at an adequate drain.  
Shall not have any valve between the relief valve and tank.  
This heater is provided with a properly certified combination  
temperature - pressure relief valve by the manufacturer.  
The valve is certified by a nationally recognized testing laboratory  
that maintains periodic inspection of production of listed equipment of  
materials as meeting the requirements for Relief Valves for Hot Water  
Supply Systems, ANSI Z21.22 • CSA4.4, and the code requirements  
ofASME.  
The temperature-pressure relief valve must be manually operated at least  
once a year. Caution should be taken to ensure that (1) no one is in front  
of or around the outlet of the temperature-pressure relief valve discharge  
line, and (2) the water manually discharged will not cause any bodily  
injury or property damage because the water may be extremely hot.  
If after manually operating the valve, it fails to completely reset and  
continues to release water, immediately close the cold water inlet to  
the water heater, follow the draining instructions, and replace the  
temperature-pressure relief valve with a new one.  
If replaced, the valve must meet the requirements of local codes, but  
not less than a combination temperature and pressure relief valve  
certified as indicated in the above paragraph.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
This heater is approved for operation up to 5,300 feet (1,615 m) without  
alteration. High altitude models are available from the factory for elevations  
between 5,300 feet (1,615 m) and 10,100 feet (3,079 m). For elevations  
above10,100feet(3,079m)theinputratingshouldbereducedattherateof  
4 percent for each 1,000 feet (305 meters) above sea level which requires  
replacementoftheburnerorificeinaccordancewithNationalFuelGasCode  
(ANSIZ223.1/NFPA 54)ortheNatural Gas andPropane InstallationCode  
(CAN/CSAB149.1). Contactyourlocalgassupplierforfurtherinformation.  
GAS PIPING  
Failure to replace the standard orifice with a high altitude orifice when  
installedabove10,100feet(3,079m)couldresultinimproperandinefficient  
operation of the appliance, producing carbon monoxide gas in excess of  
safe limits, which could result in serious injury or death. Contact your gas  
supplier for any specific changes which may be required in your area.  
Make sure the gas supplied is the same type listed on the model rating  
plate. The inlet gas pressure must not exceed 14 inch water column (3.5  
kPa) for natural and propane gas (L.P.). The minimum inlet gas pressure  
shown on the rating plate is that which will permit firing at rated input.  
All gas piping must comply with local codes and ordinances or with the  
National Fuel Gas Code (ANSI Z223.1/ NFPA-54) or the Natural Gas and  
Propane Installation Code (CAN/CSAB149.1) whicheverapplies.Copper  
or brass tubing and fittings (except tin lined copper tubing) shall not be used.  
Use pipe joint compound or teflon tape marked as being resistant to  
the action of petroleum [Propane (L.P.)] gases.  
If the gas control valve is subjected to pressures exceeding 1/2 psi  
(3.5 kPa), the damage to the gas control valve could result in a fire  
or explosion from leaking gas.  
The appliance and its gas connection must be leak tested before  
placing the appliance in operation.  
If the main gas line Shut-off serving all gas appliances is used, also  
turn “off” the gas at each appliance. Leave all gas appliances shut  
“off” until the water heater installation is complete.  
The appliance and its individual Shut-off valve shall be disconnected from  
the gas supply piping system during any pressure testing of that system at  
test pressures in excess of 1/2 pound per square inch (3.5 kPa). It shall be  
isolated from the gas supply piping system by closing its individual manual  
Shut-off valve during any pressure testing of the gas supply piping system  
at test pressures equal to or less than 1/2 pound per square inch (3.5 kPa).  
A gas line of sufficient size must be run to the water heater. Consult  
the current edition of National Fuel Gas Code (ANSI Z223.1/NFPA  
54) or the Natural Gas and Propane Installation Code (CAN/CSA  
B149.1) and your gas supplier concerning pipe size.  
Connecting the gas piping to the gas control valve of the water heater can  
be accomplished by either of the two methods shown in Figures 12 and 13.  
There must be:  
• A readily accessible manual shut off valve in the gas supply line  
serving the water heater, and  
• A drip leg (sediment trap) ahead of the gas control valve to help  
prevent dirt and foreign materials from entering the gas control valve.  
• A flexible gas connector or a ground joint union between the shut  
off valve and control valve to permit servicing of the unit.  
Be sure to check all the gas piping for leaks before lighting the water  
heater. Use a soapy water solution, not a match or open flame.  
Rinse off soapy solution and wipe dry.  
FIGURE 12. GAS PIPING WITH  
FLEXIBLE CONNECTOR.  
FIGURE 13. GAS PIPING WITH ALL  
BLACK IRON PIPE TO GAS CONTROL.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Never use this water heater unless it is completely full of water. To prevent  
damagetothetank, thetankmustbefilledwithwater.Watermustflowfrom  
the hot water faucet before turning “ON” gas to the water heater.  
SEDIMENT TRAPS  
To fill the water heater with water:  
1. Close the water heater drain valve by turning the handle to the right  
(clockwise). The drain valve is on the lower front of the water heater.  
2. Open the cold water supply valve to the water heater.  
NOTE: The cold water supply valve must be left open when  
the water heater is in use.  
3. To insure complete filling of the tank, allow air to exit by opening the  
nearest hot water faucet. Allow water to run until a constant flow is  
obtained. This will let air out of the water heater and the piping.  
4. Check all water piping and connections for leaks. Repair as needed.  
VENT PIPE ASSEMBLY  
There are three parts of the vent pipe assembly that connect the water  
heater exhaust (located on the lower back side of the water heater) to  
the inlet of the blower assembly (mounted on top of the water heater) as  
shown in Figure 1. These parts will need to be assembled according to  
the instructions in the VENT PIPE PREPARATION section of this manual.  
These PVC parts should be assembled withASTM D-2564 grade cement.  
A sediment trap shall be installed as close to the inlet of the water  
heater as practical at the time of water heater installation. The  
sediment trap shall be either a tee fitting with a capped nipple in the  
bottom outlet or other device recognized as an effective sediment  
trap. If a tee fitting is used, it shall be installed in conformance with  
one of the methods of installation shown in Figures 12 and 13.  
Assemble Vent Pipe Assemblies #1, #2 and #3 (See Figure 1) prior  
to cementing. The preferred orientation of Vent Pipe Assembly #1  
(Condensate U-Assembly) is shown in Figure 16. However this  
assembly may be rotated to a different orientation as needed for the  
specific installation requirements. Note the rotational orientation of  
each part by marking a line several inches long across the joints.The  
long tube of Vent Pipe Assembly #2 should be approximately vertical.  
If it is found that either of the two pieces of pipe in Vent PipeAssembly  
#2 are too long for proper fit-up, then remove as little material as  
possible to improve the fit-up. Keep in mind that the pipes will insert  
slightly further into the elbows when cement is applied as it acts as  
a lubricating agent. The vertical distance from the bottom of the  
Condensate U-Assembly to the floor that supports the water heater  
should be approximately 0.25" (0.64 cm), see Figure 16. Disassemble  
the parts and cement back together using the alignment marks. After  
the cement dries, attach the assembly to the blower and the water  
heater exhaust using the supplied rubber boots and hose clamps.  
Contaminants in the gas lines may cause improper operation of the  
gas control valve that may result in fire or explosion. Before attaching  
the gas line be sure that all gas pipe is clean on the inside. To trap  
any dirt or foreign material in the gas supply line, a drip leg  
(sometimes called a sediment trap) must be incorporated in the  
piping. The drip leg must be readily accessible. Install in accordance  
with the “Gas Piping” section. Refer to the current edition of the  
National Fuel Gas Code (ANSI Z223.1/NFPA 54) or the Natural  
Gas and Propane Installation Code (CAN/CSA B149.1).  
Acondensate trap is incorporated in the bottom of this vent pipe assembly.  
See the CONDENSATE section of this manual for further details.  
VENTING  
FIGURE14.  
FILLING THE WATER HEATER  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
U.S. HORIZONTAL VENT CLEARANCES  
CANADIAN HORIZONTAL VENT CLEARANCES  
FIGURE 15  
WARNING  
VENT HOOD(S) MAY BE  
EXTREMELY HOT  
DURING OPERATION.  
Instructions on proper installation through a sidewall are provided  
in Figure 15.  
VENT PIPE TERMINATION  
Plan the vent system layout so that proper clearances are  
maintained from plumbing and wiring.  
The first step is to determine where the vent pipe will terminate. See  
Figures 15, 20 and 21. The vent may terminate through a sidewall  
as shown in Figure 20 or through the roof as shown in Figure 21.  
Vent pipes serving power vented appliances are classified by  
building codes as "vent connectors". Required clearances from  
combustible materials must be provided in accordance with  
information in this manual under LOCATING THE NEW WATER  
HEATER and INSTALLING THE WATER HEATER, and with the  
National Fuel Gas Code and local codes.  
The vent system must terminate so that proper clearances are  
maintained as cited in local codes or the current edition of the National  
Fuel Gas Code, (ANSI Z223.1, 12.9.1 through 12.9.4) or the Natural  
Gas and Propane Installation Code (CAN/CSA-B149.1).  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
a special fitting that must be used with this appliance. Any outlet  
piping, fittings and glue used to vent this appliance that is not supplied  
by the manufacturer must comply with the ULC S636 requirements.  
PLANNING THE VENT SYSTEM  
Plan the route of the vent system from the discharge of the blower to  
the planned location of the vent terminal.  
If the water heater is being installed as a replacement for an existing power  
vented heater in pre-existing venting, a thorough inspection of the existing  
venting system must be performed prior to any installation work. Verify that  
thecorrectmaterialasdetailedabovehasbeenused, andthattheminimum  
or maximum vent lengths and terminal location as detailed in this manual  
have been met. Carefully inspect the entire venting system for any signs of  
cracks or fractures, particularly at the joints between elbows and other  
fittings and the straight runs of vent pipe. Check the system for signs of  
sagging or other stresses in the joints as a result of misalignment of any  
components in the system. If any of these conditions are found, they must  
be corrected in accordance with the venting instructions in this manual  
before completing the installation and putting the water heater into service.  
1. Layout total vent system to use a minimum of vent pipe and elbows.  
2. This water heater is capable of venting flue gases equivalent to 25'  
(7.6 m) of 2" pipe, 65' (19.8 m) of 3" pipe, or 128' (39.0 m) of 4" pipe  
as listed in Table 1.  
TABLE 1  
Number of  
90° Elbows  
2" Maximum  
Pipe - ft. (m)  
3" Maximum  
Pipe - ft. (m)  
4" Maximum  
Pipe - ft. (m)  
1
2
3
4
5
6
20 (6.1)  
15 (4.6)  
10 (3.0)  
60 (18.3)  
55 (16.8)  
50 (15.2)  
45 (13.7)  
40 (12.2)  
35 (10.7)  
120 (36.6)  
112 (34.1)  
104 (31.7)  
96 (29.3)  
88 (26.8)  
80 (24.3)  
NOTE: A. For water heaters in locations with high ambient temperatures  
(above100°F)itisrecommendedthatCPVCorABSpipeandfittingsbeused.  
B.A22.5 degree elbow (2" vent pipe) or a 45 degree elbow (3" and 4" vent  
pipe)withaninstalledscreenVENTTERMINALmustbeusedinallcases.  
--  
--  
--  
4. There will be some installations where condensate will be formed  
in the horizontal runs of the vent system. This condensate will run  
into the condensate boot attached to the blower and out the fitting.  
The water heater is shipped with condensate hose that attaches to  
the fitting on the condensate boot. No other Tee or fitting is required.  
See Figures 17, 20 and 21.  
The minimum vent lengths for each of the pipe sizes is one 90° on top  
of the unit plus 2' (61 cm) of straight pipe and the appropriate termination.  
NOTE: The equivalent feet (m) of pipe listed above are exclusive of  
the termination. That is, the termination, with an installed screen, is  
assumed to be in the system and the remainder of the system must  
not exceed the lengths discussed above.  
CONDENSATE  
This water heater is a condensing unit and requires a drain to be located  
in close proximity to allow the condensate to drain safely.The condensate  
drains from the unit at the exhaust tee located at the bottom of the unit  
(see figure 16) and from two places on the blower assembly (see figure  
17). Condensate from this water heater is mildly acidic. Please note that  
some local codes require that condensate is treated by using a pH  
neutralizing filter prior to disposal.  
3. The blower discharge adapter is made to accept only straight  
sections of 2" pipe. To start, a minimum of 2 inches (5.1 cm) of 2"  
pipe must be attached to the blower discharge, see Figure 17.  
If using 2" inch vent pipe:  
A minimum of 2 inches (5.1 cm) must be attached to the blower  
before the first elbow. After the first elbow add the additional  
venting required for the installation. The total system cannot  
exceed the lengths discussed above, where each elbow is  
equal to 5 feet (1.5 m) of straight pipe.  
NOTE: It is important that the condensate hose on the bottom of the unit is  
not installed elevated above the clamp that is secured to the side of the  
jacket, see figure 16. This must be true for the entire length of the hose  
from the clamp to the exit into an appropriate drain. If these instructions are  
not followed or if the condensate hose is blocked, water will spill from the  
condensate trap. As with every water heater installation, a drain pan  
should be used to prevent water damage to the surrounding area. If  
necessary, a condensate pump with an incorporated reservoir may be  
used to pump the water to an appropriate drain. To avoid condensate  
spillage, select a pump with an overflow switch.  
If using 3" or 4" inch vent pipe:  
Two inches(5.1 cm) of pipe must be attached to the blower discharge  
before adding a reducer to acquire the desired pipe diameter. An  
appropriately sized 45 degree elbow (supplied locally-a schedule 40  
DWV)ventterminalmustbeobtainedwithanequivalentscreen(supplied  
in vent kit). The total system cannot exceed the equivalent pipe lengths  
discussed above where each elbow is equal to 5 feet (1.5 m) of  
straightpipe(3"ventpipe)or8feet(2.4 m) ofstraightpipe(4"ventpipe).  
Caution must be used to ensure that the drain is free and clear of  
debrisandwillnotallowbackflowthroughthecondensatehose.Consideration  
mustbegiventoavoidfreezingofthecondensatelineswhichcouldresultin  
excessive build up of condensate inside the water heater. Waterproof heat  
tape may be required to prevent freezing of the condensate lines. Please  
ensure that the outlet of the condensate draindoes not create a slippery  
condition which could lead to personal injury.  
U.S. Installations  
NOTE: This unit can be vented with PVC pipe materials (Cellular Core  
ASTM-F891; DWVASTM-D2665 or CSAB181.2; Schedule 40, 80, 120  
ASTM-D1785orCSAB137.3;orSDRSeriesASTM-D2241orCSAB137.3),  
CPVC pipe materials (CPVC41ASTM-D2846 or CSAB137.6; Schedule  
40, 80ASTM-F441orCSAB137.6;orSDRSeriesASTM-F442),ABSpipe  
materials (Schedule 40 DWVASTM-D2661 or CSAB181.1 or Schedule  
40DWVCellularCoreASTM-F628).Thefittings,otherthantheTERMINATION  
should be equivalent to PVC-DWV fittings meetingASTM D-2665 (Use  
CPVCfittings,ASTMF-438forCPVCpipeandABSfittings,ASTMD-2661/  
3311 forABS pipe). If CPVC or ABS pipe and fittings are used, then the  
proper cement must be used for all joints, including joining the pipe to the  
Termination (PVC Material). If local codes do not allow the use of the PVC  
termination when a material other than PVC is used for venting, then an  
equivalentfittingofthatmaterialmaybesubstitutedifthescreeninthePVC  
terminal is removed and inserted into the new fitting.  
PVC Materials should useASTM D-2564 Grade Cement; CPVC Materials  
should useASTM F-493 Grade Cement andABS Materials should use  
ASTM D-2235 Grade Cement.  
Canadian Installation of this water heater must comply with CAN/CSA  
B149.1 - Natural Gas and Propane Installation Code which requires  
the vent system components be certified to ULC S636.  
This water heater has been design certified to be vented with PVC  
pipe certified and marked as complying with ULC S636. This water  
heater is supplied with a 2 inch 22.5 degree termination elbow that is  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The condensate trap may be primed by filling the CONDENSATE U-  
ASSEMBLY with tap water using the supplied hose while the water  
heater is not operating. The system is fully primed when the hose is  
lowered below the hose clamp on the side of the water heater and  
water begins to flow out of the hose. In most installations the water  
heater will self-prime the condensate trap during the first full heat-up  
cycle. If a sound of air bubbling through water (gurgling) is heard while  
the blower is operating after the first heat-up cycle, then turn the unit  
off and contact your plumber or service representative.  
6. Make sure the ON/OFF switch is in the OFF position and that the  
outer harness is connected from the blower control box to the  
connector on the bottom side of the gas valve.  
7. If the outer harness is not factory installed, make sure the ON/  
OFF switch is in the OFF position and then connect the outer  
harness from the blower control box to the connector on the  
bottom side of the gas valve.  
If these instructions are not followed, the condensate build-up will  
block the exhaust outlet, which will cause improper operation.  
8. Do not plug in power cord until vent system is completely installed.  
The Power Vent operates on 110-120 Vac. therefore a grounded  
outlet must be within reach of the 6 foot (1.8 m) flexible power  
cord supplied with the vent (See Figure 1). The power cord  
supplied may be used on a unit only where local codes permit.  
If local codes do not permit use of flexible power supply cord:  
A. Make sure the unit is unplugged from the wall outlet. Remove  
the plastic top cap. Remove screws and open panel on the  
front of the control box on the blower.  
CONDENSATESYSTEM-FIGURE16  
Condensate is likely to form in the venting system attached to this water  
heater. The vent pipe should be sloped downward away from the blower  
assembly (not less than 1/8" (3.2 mm) nor greater than 1/2" (12.7 mm)  
per foot (30 cm) maximum). If the vent piping is vented level or sloped  
upwards away from the blower assembly, then adequate means for  
draining and disposing of the condensate needs to be made by the  
installer. In either case, a 3/8" drain hose should be connected to the  
built-in drain port. Prior to operating the water heater, make sure the  
removable cap is installed on the second drain port, see Figure 17.  
B. Cut the flexible power cord, leaving enough to be able to make  
connections. Remove the strain relief fitting from the box.  
C. Install a suitable conduit fitting inside the enclosure.  
D. Splice field wiring into existing wiring using code authorized  
method (wire nuts, etc).  
E. Be certain that neutral and line connections are not reversed  
when making these connections.  
BLOWER ASSEMBLY INSTALLATION  
1. Thispowerventedwaterheatercomeswiththeblowerassemblyinstalled.  
2. After the unit is set in place, make sure the blower assembly is  
still mounted securely. Also make sure that one of the drain  
ports of the rubber boot vent adapter is capped off. Lastly, make  
sure there is no damage to the blower.  
F. Ground heater properly. This water heater must be grounded  
in accordance with the National Electrical Code NFPA 70 or  
the Canadian Electrical Code C22.1 and/or local codes.These  
must be followed in all cases.  
3. Condensate drains from two locations on the blower assembly as  
shown in figure 17. A condensate hose must be secured to form a  
"trap" as shown in figure 17 for these condensate drain connections.  
These two hoses may be connected together. The hose(s) should  
be routed to a suitable drain. A fitting that may be used to join the  
two hoses from the blower assembly is included in a supplied kit.  
The water heater must be connected to a grounded metal,  
permanent wiring system; or an equipment grounding  
conductor must be run with the circuit conductors and  
connected to the equipment grounding terminal or lead on  
the water heater, see Figure 19.  
G. Close the panel on the control box. Make sure that the access  
panel is secured shut.  
9. The blower discharge boot is made to accept only straight sections  
of 2" pipe. To start off with an elbow, a short section of the furnished  
pipe, a minimum of 2 inches (5.1 cm), must be cut and glued into  
the end of the elbow that will mount on the discharge boot.  
INSTALLATION OF VENT SYSTEM  
Before beginning installation of piping system thoroughly read the  
section of this manual VENT PIPE PREPARATION.  
FIGURE 17.  
If you are installing your system so that it vents through roof, please  
refer to section titled INSTALLATION OF VERTICALVENTSYSTEM.  
4. Make sure there is no packing material in the inlet or discharge  
of the blower.  
VENT TERMINAL INSTALLATION, SIDEWALL  
5. Make sure that the plastic tubing is still attached from the air  
pressure switch to the port on the blower housing. Make sure  
the plastic tubing is not folded anywhere between the pressure  
switch and the blower housing.  
1. Install the vent terminal by using the cover plate as a template to  
mark the hole for the vent pipe to pass through the wall. BEWARE  
OF CONCEALED WIRING AND PIPING INSIDE THE WALL.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
the wall plate over the pipe to stop against the vent terminal. Place a bead  
of caulking (not supplied) around the gap between the pipe and cover  
plate. Apply enough to fill some of the gap between the pipe and wall.  
Place some of the caulking on the back of the plate to hold it against the  
wall after installation. If the vent pipe is installed up to the wall, with a  
coupling on the end against the wall opening, the pipe with the vent  
terminal can be prepared for gluing before inserting through the wall. Slide  
the pipe through the wall and insert into the coupling on the other side of  
the wall, making sure that the vent terminal ends up pointed in the correct  
position, see Figure 18.  
2. IftheVentTerminalisbeinginstalledontheoutsideofafinishedwall,itmay  
beeasiertomarkboththeinsideandoutsidewall.Aligntheholesbydrilling  
a hole through the center of the template from the inside through to the  
outside. Thetemplatecannowbepositionedontheoutsidewallusingthe  
drilledholeasacenteringpointforthetemplate.  
3. A) MASONRY SIDE WALLS  
Chisel an opening approximately one half inch (1.3 cm) larger than  
the marked circle.  
B) WOODEN SIDE WALLS  
Drill a pilot hole approximately one quarter inch (0.64 cm) outside of  
the marked circle. This pilot hole is used as a starting point for a  
saws-all or sabre saw blade. Cut around the marked circle staying  
approximately one quarter inch (0.64 cm) outside of the line. (This  
will allow the vent to easily slide through the opening. The resulting  
gap will be covered up by the Vent Terminal cover plate.) Repeat this  
step on inside wall if necessary.  
SEQUENCE OF INSTALLATIONS, FIGURE 18  
Cut a length of PVC pipe about 3.5 inches (8.9 cm) longer than the wall  
thicknessattheopening. Gluetheventterminaltothissectionofpipe. Slide  
VENT TERMINATION - FIGURE 18.  
CAUTION  
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND  
DANGEROUS OPERATION. VERIFY PROPER OPERATION AFTER SERVICING.  
POWER VENT WIRING SCHEMATIC - FIGURE 19.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Provide support for all pipe protruding through the roof. All piping  
should be properly secured. The vent system piping should be  
INSTALLATION OF VENT SYSTEM, SIDEWALL  
With the route of the venting system and selection of materials completed, supported every 5 feet (1.5 m) of vertical run and every 3 feet (91  
as discussed in the section of this manual titled PLANNING THE VENT cm) of horizontal run. All piping and fittings must be joined by the  
SYSTEM, the through the wall vent terminal in place and the first section proper procedures as described under: VENT PIPE  
of piping, up to first elbow, installed at the blower it is time to complete PREPARATION.  
the installation of the venting system for the sidewall installation.  
FIGURE 20  
FIGURE 21  
Before completing the installation of the venting system be sure to read  
the sections of this manual discussing the proper method of cutting  
and cementing PVC pipe and fittings: VENT PIPE PREPARATION.  
IMPORTANT  
The vent system must terminate so that proper clearances are  
maintained as cited in local codes or the current edition of the  
National Fuel Gas Code (ANSI Z223.1) or the Natural Gas and  
Propane Installation Code (CAN/CSA-B149.1) and as listed below:  
It is recommended that the completion of the venting system start at  
the blower assembly and run to the coupling on the inside wall of  
the vent terminal, Figure18.  
The vent system piping should be supported every 5 feet (1.5 m)  
of vertical run and every 3 feet (91 cm) of horizontal run. All piping  
and fittings must be joined by the proper procedures as described  
under: VENT PIPE PREPARATION.  
1. Vent Termination must extend a minimum of 18 inches (46 cm) above  
roof or 18 inches (46 cm) above the anticipated snow level to prevent  
blockage of the vent termination, as shown in Figures 20 and 21.  
2. The venting system shall terminate at least four (4) feet (1.2 m)  
from or one (1) foot (30 cm) above any gable, dormer or other  
roof structure with building interior access; i.e., vent, window, etc.  
INSTALLATION OF VERTICAL VENT SYSTEM  
A proper flashing or "BOOT" should be used to seal the pipe where  
it exits the roof. The total vent system should not exceed the  
equivalent feet of pipe as listed in Table 1.  
3. The venting system shall terminate three (3) feet (91 cm)  
above any forced air inlet located within ten feet (3.0 m).  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
support the VAA and the surrounding vent pipe could create a  
hazardous situation. DO NOT puncture any surface of the VAA.  
VENT ATTENUATION ASSEMBLY  
INSTALLATION INSTRUCTIONS  
5. Confirm that the hex plug is securely installed in the 1/2" fitting  
found on the center of the VAA pipe. It is imperative that the plug  
is secure and air tight to prevent any combustion gases escaping  
into the room. If the plug is not securely tightened, remove and  
reinstall using Teflon tape on the threads. Once installed along  
with the rest of the vent configuration, make sure to operate the  
unit through at least one heat up cycle to ensure there is no leakage  
around the plug or any joints of the VAA or vent pipe system.  
The Vent Attenuation Assembly (VAA) is designed to provide a  
reduction in fan noise created in the blower wheel. This installation of  
this VAA is optional. Review directions thoroughly prior to installing  
the new VAA. Please contact the manufacturer of the water heater as  
shown in the instruction manual with any questions or for additional  
product support.  
VENT ATTENUATION ASSEMBLY KIT PARTS LIST  
The kit consists of the following items. If a part is missing, use the  
contact information in the instruction manual to acquire missing  
component(s).  
• vent attenuation assembly  
• flexible tubing  
• hose barb  
• hex plug (installed on VAA)  
• instruction sheet  
VENT ATTENUATION ASSEMBLY INSTALLATION  
The VAA is designed for both vertical and horizontal installations. The  
vertical installation does not require the additional hose barb and flexible  
tubing. However, the horizontal installation will require the hose barb  
and flexible tubing to release condensate buildup from the VAA. See  
instructions and diagrams that follow for a more detailed description.  
FIGURE 22: Typical Vertical Installation  
Horizontal VAA Installations  
1. The VAA is designed to accept two inch PVC pipe into the adapters on  
both ends. The VAA can be installed to the piping from either side  
(there is no specific inlet or outlet). For optimum performance, install  
VAA as close as possible to the blower assembly.  
2. Use standard PVC cement (not included with kit) and glue the two  
inch PVC pipe coming from the blower into the VAA. Make sure  
the 1/2" fitting is on the bottom side of the VAA. This will be used  
to run the condensate hose to a suitable drain. See typical vent  
installation in Figure 23.  
3. Perform the same sequence on the PVC pipe coming from the  
exhaust side (vent terminal side) of the VAA.  
4. Make sure the VAAand vent pipe is supported securely to a permanent  
fixture (stud or wall). Use standard support straps (not supplied with  
kit) that may be found at a local hardware store. Failure to properly  
support the VAA and the surrounding vent pipe could create a  
hazardous situation. DO NOT puncture any surface of theVAA.  
5. Remove hex plug from the center pipe of the VAA. Locate the  
hose barb and install into the 1/2" fitting on the center of the VAA.  
Using Teflon tape on the threads, install hose barb into 1/2" fitting  
securely. It is imperative that the hose barb is secure and tight to  
prevent any combustion gases escaping into the room.  
Vertical VAA Installations (Recommended)  
1. The VAA is designed to accept two inch PVC pipe into the adapters  
on both ends. The VAA can be installed to the piping from either side  
(there is no specific inlet or outlet). For optimum performance, install  
VAA as close as possible to the blower assembly.  
6. Locate flexible tubing. Slide one end of tube over the hose barb  
located on the center pipe of the VAA. The ridges on the hose  
barb should prevent the tube from sliding off, however, to ensure  
there are no leaks and possible dislocation from hose barb, use a  
wire tie or hose clamp (not supplied with kit) and secure.  
2. Use standard PVC cement (not included with kit) and glue the two  
inch PVC pipe coming from the blower into the VAA.  
3. Perform the same sequence on the PVC pipe coming from the  
exhaust side (vent terminal side) of the VAA.  
7. Take the other end of the flexible tubing and form an 8 inch (20  
cm) diameter circle approximately 3 feet (91 cm) down from the  
hose barb located in the VAA. To ensure that the circle (loop)  
maintains its shape, use two wire ties (not supplied with kit) to  
secure it.  
4. Make sure the VAAand vent pipe is supported securely to a permanent  
fixture (stud or wall). Use standard support straps (not supplied with  
kit) that may be found at a local hardware store. Failure to properly  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. Take the end of the tube at the bottom of the floor and route it to  
a suitable drain. This will provide an area where the condensate  
can drain without affecting the area around the appliance.  
9. Once installed along with the rest of the vent configuration,  
make sure to operate the unit through at least one heat up  
cycle to ensure there is no leakage around the hose barb or  
any joints of the VAA or vent pipe system.  
FIGURE 24: Typical Installation for Vertical Vent with 3 or 4 inch Pipe  
Installation of VAA with 3 & 4 inch Pipe for Horizontal Vent  
Some applications may require the use of 3 or 4 inch vent pipe for longer  
vent lengths. Please refer to the Figure25 as you review these instructions.  
Refer back to the horizontal VAA installation steps but with the following  
changes to the vent construction.  
3 inch vent (Horizontal VAA Installations)  
The VAA is designed to accommodate only 2 inch vent pipe. The  
installer must use 2 inch vent pipe between the blower assembly and  
the inlet into the VAA. On the outlet side of the VAA, a short run of 2  
inch vent pipe is required. From this point on, a 2 inch to 3 inch adapter  
may be used. From the 2 inch to 3 inch adapter, the installer may use  
up to 52 equivalent feet (15.8 m) of pipe. This is 8 equivalent feet (2.4  
m) less than the original 60 equivalent feet (18.3 m) specified with  
one elbow due to the 2 inch elbow instead of a 3 inch elbow required  
for the vent from the blower to the inlet of the VAA, see Figure 25 for  
typical installation.  
FIGURE 23: Typical Horizontal Installation  
Installation for VAA with 3 & 4 inch Pipe for Vertical Vent  
Some applications may require the use of 3 or 4 inch vent pipe for  
longer vent lengths. Please refer to the Figure 24 as you review  
these instructions. Refer back to the vertical VAA installation steps  
but with the following changes to the vent construction.  
4 inch vent (Horizontal VAA Installations)  
The VAAis designed to accommodate only 2 inch vent pipe. The installer  
must use 2 inch vent pipe betweenthe blower assembly and the inlet into  
the VAA. On the outlet side of the VAA a short run of 2 inch vent pipe is  
required. From this point on, a 2 inch to 4 inch adapter may be used. From  
the 2 inch to 4 inch adapter, the installer may use up to 102 equivalent feet  
(31.1 m) of pipe. This is 18 equivalent feet (5.5 m) less than the original  
120 equivalent feet (36.6 m) specified with one elbow due to the 2 inch  
elbow instead of a 4 inch elbow required for the vent from the blower to  
the inlet of the VAA, see Figure 25 for typical installation.  
3 inch vent (Vertical VAA Installations)  
The VAA is designed to accommodate only 2 inch vent pipe. The  
installer must use 2 inch vent pipe between the blower assembly  
and the inlet into the VAA. On the outlet side of the VAA, a short run  
of 2 inch vent pipe is required. Each of the short pieces of 2 inch  
pipe entering and exiting the VAA must not exceed 6 inches (15 cm)  
in length. From this point on, a 2 inch to 3 inch adapter may be  
used. From the 2 inch to 3 inch adapter, the installer may use up to  
65 equivalent feet (19.8 m) of pipe, see Figure 24 for typical  
installation.  
Remember to operate the unit for at least one heat cycle to ensure  
there are no air leaks in the vent joints of the VAA and the vent pipe  
system. Air leaks will allow flue gas by-products to disseminate into  
the room creating an unsafe environment and could cause illness,  
asphyxiation and/or even death.  
4 inch vent (Vertical VAA Installations)  
The VAA is designed to accommodate only 2 inch vent pipe. The  
installer must use 2 inch vent pipe between the blower assembly  
and the inlet into the VAA. On the outlet side of the VAA, a short run  
of 2 inch vent pipe is required. Each of the short pieces of 2 inch  
pipe entering and exiting the VAA must not exceed 6 inches (15 cm)  
in length. From this point on, a 2 inch to 4 inch adapter may be  
used. From the 2 inch to 4 inch adapter, the installer may use up to  
128 equivalent feet (39.0 m) of pipe, see Figure 24 for typical  
installation.  
Remember to operate the unit for at least one heat cycle to  
ensure there are no air leaks in the vent joints of the VAA and  
the vent pipe system. Air leaks will allow flue gas by-products  
to disseminate into the room creating an unsafe environment  
and could cause illness, asphyxiation and/or even death.  
FIGURE 25: Typical Installation for Horizontal Vent with 3 or 4 inch  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRIMER  
VENT PIPE PREPARATION  
It is recommended that Tetrahydrofuran (THF) be used to prepare  
the surfaces of pipe and fittings for solvent welding. Do not use  
water, rags, gasoline or any other substitutes for cleaning PVC or  
CPVC surfaces. A chemical cleaner such as MEK may be used.  
1. INITIAL PREPARATION  
A. Make sure the solvent cement you are planning to use is  
designed for the specific application you are attempting.  
CEMENT  
B. Know the physical and chemical characteristics and limitations of  
the PVC and CPVC piping materials that you are about to use.  
The cement should be a bodied cement of approximately 500 to  
1600 centipoise viscosity containing 10-20% (by weight) virgin PVC  
material solvated with tetrahydrofuran (THF). Small quantities of  
dimethyl formamide (DMF) may be included to act as a retarding  
agent to extend curing time. Select the proper cement; Schedule  
40 cement should be used for Schedule 40 pipe. Never use all-  
purpose cements, commercial glues and adhesives or ABS cement  
to join PVC or CPVC pipe and fittings.  
C. Know the reputation of your manufacturer and their products.  
D. Know your own qualifications or those of your contractor. The  
solvent welding technique of joining PVC and CPVC pipe is a  
specialized skill just as any other pipe fitting technique.  
E. Closely supervise the installation and inspect the finished  
job before start-up.  
F. Contact the manufacturer, supplier, or competent consulting  
agency if you have any questions about the application or  
installation of PVC and CPVC pipe.  
G. Take the time and effort to do a professional job. Shortcuts  
will only cause you problems and delays in start-up. By far,  
the majority of failures in PVC and CPVC systems are the  
result of shortcuts and/or improper joining techniques.  
APPLICATORS  
Select a suitable pure bristle type paint brush. Use a proper width  
brush or roller to apply the primer and cement (see chart below).  
Speedy application of cement is important due to its fast drying  
characteristics. IMPORTANT NOTE:Adauber type applicator should  
only be used on pipe sizes 2" and below. For larger diameter pipe, a  
brush or roller must be used.  
2. SELECTION OF MATERIALS  
Cutting Device - Saw or Pipe Cutter  
Deburring Tool, Knife, File, or Beveling Machine (2" and above)  
Brush - Pure Bristle  
RECOMMENDED BRUSH* SIZE FOR PRIMER  
AND CEMENT APPLICATIONS  
Rag - Cotton (Not Synthetic)  
Nominal Pipe  
Size Brush Width  
Primer and Cleaner  
(IPS)  
Solvent Cement - PVC for PVC Components and CPVC for  
CPVC Components  
2
3
1.5" (3.8 cm)  
1.5" - 2.5" (3.8 cm - 6.4 cm)  
Containers - Metal or Glass to hold Primer and Cement. Select  
the type of PVC or CPVC materials to be used on the basis of  
their application with respect to chemical resistance, pressure  
rating, temperature characteristics, etc.  
*USE ONLY NATURAL BRISTLE  
3. MAKING THE JOINT  
Insertion Tool - Helpful for larger diameter pipe and fittings 6  
inches (15.2 cm) and above.  
A. Cutting  
Pipe must be squarely cut to allow for the proper interfacing of  
the pipe end and the fitting socket bottom. This can be  
accomplished with a miter box saw or wheel type cutter. Wheel  
type cutters are not generally recommended for larger diameters  
since they tend to flare the corner of the pipe end. If this type of  
cutter is used, the flare on the end must be completely removed.  
NOTE: Power saws should be specifically designed to cut plastic pipe.  
STEP A  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. Deburring  
Use a knife, plastic pipe deburring tool, or file to remove burrs from the  
end of small diameter pipe. Be sure to remove all burrs from around the  
inside as well as the outside of the pipe. Aslight chamfer (bevel) of about  
10°-15° should be added to the end to permit easier insertion of the pipe  
into the end of the fitting. Failure to chamfer the edge of the pipe may  
remove cement from the fitting socket, causing the joint to leak.  
STEP E  
F. Joint assembly  
Working quickly, insert the pipe into the fitting socket bottom and  
give the pipe or fitting a 1/4 turn to evenly distribute the cement.  
Do not continue to rotate the pipe after it has hit the bottom of the  
fitting socket. A good joint will have sufficient cement to make a  
bead all the way around the outside of the fitting hub. The fitting  
will have a tendency to slide back while the cement is still wet so  
hold the joint together for about 15 seconds.  
STEP B  
C. Test dry fit of the joint  
Tapered fitting sockets are designed so that an interfaced fit should  
occur when the pipe is inserted about 1/3 to 2/3 of the way into the  
socket. Occasionally, when pipe fitting dimensions are at the tolerance  
extremes, it will be possible to fully insert dry pipe to the bottom of the  
fitting socket. When this happens, a sufficient quantity of cement  
must be applied to the joint to fill the gap between the pipe and fitting.  
The gap must be filled to obtain a strong, leak-free joint.  
D. Inspection, cleaning, priming  
Visually inspect the inside of the pipe and fitting sockets and remove  
all dirt, grease or moisture with a clean dry rag. If wiping fails to  
clean the surfaces, a chemical cleaner must be used. Check for  
possible damage such as splits or cracks and replace if necessary.  
Depth-of-entry  
STEP F  
Marking the depth of entry is a way to check if the pipe has reached  
the bottom of the fitting socket in Step F. Measure the fitting depth  
and mark this distance on the pipe O.D. You may want to add  
several inches to the distance and make a second mark as the  
primer and cement will most likely destroy your first one.  
G. Cleanup and joint movement  
Remove all excess cement from around the pipe and fitting with  
a dry cotton rag. This must be done while the cement is still soft.  
The joint should not be disturbed immediately after the cementing  
procedure, and sufficient time should be allowed for proper curing  
of the joint. Exact drying time is difficult to predict because it  
depends on variables such as temperature, humidity and cement  
integrity. For more specific information, you should contact your  
solvent cement manufacturer.  
Apply primer to the surface of the pipe and fitting socket with a natural  
bristle brush. This process softens and prepares the PVC or CPVC for  
the solvent cementing step. Move quickly and without hesitation to  
the cementing procedure while the surfaces are still wet with primer.  
E. Application of solvent cement  
• Apply the solvent cement evenly and quickly around the outside of  
the pipe at a width a little greater than the depth of the fitting socket.  
• Apply a light coat of cement evenly around the inside of the  
fitting socket. Avoid puddling.  
• Apply a second coat of cement to the pipe end.  
STEPG  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR YOUR SAFETY READ BEFORE OPERATING  
WARNING: If you do not follow these instructions exactly, a fire or  
explosion may result causing property damage, personal injury or loss of  
life.  
BEFORE OPERATING: ENTIRE SYSTEM MUST BE FILLED WITH WATER AND AIR PURGED FROM ALL LINES.  
A. This appliance does not have a pilot. It is equipped  
with an ignition device which automatically lights the  
burner. Do NOT try to light the burner by hand.  
B. BEFORE OPERATING smell all around the appliance  
area for gas. Be sure to smell next to the floor because  
some gas is heavier than air and will settle on the floor.  
WHAT TO DO IF YOU SMELL GAS:  
If you cannot reach your gas supplier, call the fire  
department.  
C. Use only your hand to push in the gas control buttons.  
Never use tools. If the control buttons will not push in,  
don’t try to repair them, call a qualified service technician.  
Force or attempted repair may result in a fire or explosion.  
D. Do not use this appliance if any part has been under  
water. Immediately contact a qualified installer or service  
agency to replace a flooded water heater. Do not attempt  
to repair the unit! It must be replaced!  
Do not try to light any appliance.  
Do not touch any electric switch;  
Do not use any phone in your building.  
Immediately call your gas supplier from a neighbor’s  
phone. Follow the gas supplier’s instructions.  
OPERATING INSTRUCTIONS  
4. This appliance is equipped with a device which  
automatically lights the burner.  
DO NOT TRY TO LIGHT THE BURNER BY HAND.  
5. Wait five (5) minutes to  
If you then smell gas,  
clear out any gas.  
STOP! Follow “B” in  
the safety information above on this label. If you don’t  
smell gas, go to the next step.  
6. Turn on all electrical power to the appliance.  
7. Set thermostat to desired setting by first pressing the  
COOLER  
and HOTTER  
buttons together  
and holding for 1 second. Then press the HOTTER  
button.  
8. If the appliance will not operate, follow the instructions  
“TO TURN OFF GAS TO APPLIANCE” and call your  
technician or gas supplier.  
1.  
STOP! Read the safety information above,  
on this label.  
9. WATER TEMPERATURE ADJUSTMENT  
is approximately 120°F.  
2. Set the thermostat to the lowest setting by first pressing  
the COOLER and HOTTER buttons together  
CAUTION: Hotter water increases the risk  
of scald injury. Consult the instruction  
manual before changing temperature.  
and holding for 1 second. Then press the COOLER  
button until the WARM indicator light appears.  
3. Set the “ON/OFF” switch on the blower control box to  
the “OFF” position.  
WARNING: TURN OFF ALL ELECTRIC  
POWER BEFORE SERVICING  
TO TURN OFF GAS TO APPLIANCE  
1. Set the thermostat to the lowest setting by first pressing the COOLER  
and HOTTER  
buttons together and  
holding for 1 second. Then press the COOLER button until the WARM indicator light appears.  
2. Set the ON/OFF switch on the blower control box to the “OFF” position.  
3. Turn off all electric power to the appliance if service is to be performed.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TEMPERATURE REGULATION  
It is recommended that lower water temperatures be used to avoid the  
To avoid any unintentional changes in water temperature settings, the  
control has a tamper resistant feature for changing the temperature  
setting. To change the temperature setting follow these instructions:  
risk of scalding. It is further recommended, in all cases, that the water  
temperature be set for the lowest temperature which satisfies your  
hot water needs. This will also provide the most energy efficient  
operation of the water heater.  
1. “Wake Up” the temperature indicators by holding down both  
“COOLER” and “HOTTER” temperature adjustment buttons at the  
same time for one second, see Figure 26. One or two of the  
temperature indicators will light up. These indicators will only remain  
on for 30 seconds if no further buttons are pressed.After 30 seconds  
the control will go back to “Sleep” mode.  
Short repeated heating cycles caused by small hot water uses can  
cause temperatures at the point of use to exceed the thermostat setting  
by up to 20°F (11°C). If you experience this type of use you should  
consider using lower temperature settings to reduce scald hazards.  
2. Release both of the temperature adjustment buttons.  
a. To decrease the temperature press and release the “COOLER”  
button until the desired setting is reached.  
b. To increase the temperature press and release the “HOTTER”  
button until the desired setting is reached.  
NOTE: Holding down the button will not continue to lower or raise the  
temperature setting. The button must be pressed and released for  
each temperature change desired.  
Should overheating occur or the gas supply fail to shut off, turn off the  
manual gas control valve to the appliance.  
HOT WATER CAN SCALD: Water heaters are intended to produce hot  
water. Water heated to a temperature which will satisfy space heating,  
clothes washing, dish washing, and other sanitizing needs can scald and  
permanently injure you upon contact. Some people are more likely to be  
permanently injured by hot water than others. These include the elderly,  
children, theinfirm, orphysically/mentallyhandicapped. Ifanyoneusinghot  
waterfrom this heater fitsintooneofthesegroupsorifthereisalocalcode  
or state law requiring a certain temperature water at the hot water tap, then  
you must take special precautions. In addition to using the lowest possible  
temperature setting that satisfies your hot water needs, a means such as a  
mixing valve, shall be used at the hot water taps used by these people or at  
thewaterheater. Mixingvalvesareavailableatplumbingsupplyorhardware  
stores, see Figure 2. Follow manufacturer’s instructions for installation of  
the valves. Before changing the factory setting on the thermostat, in this  
manual, seeFigure26.  
TEMPERATURE INDICATORS  
Never allow small children to use a hot water tap, or to draw their own  
bath water. Never leave a child or handicapped person unattended in  
a bathtub or shower.  
TEMPERATUREADJUSTMENT BUTTONS  
Time to Produce  
2nd & 3rd Degree  
Display  
B C D E F  
The water heater should be located in an area where the general  
public does not have access. If a suitable area is not available, a cover  
should be installed over the thermostat to prevent tampering.  
Temperature Setting  
Burns on Adult Skin  
F = approx. 180°F (82°C)  
E = approx. 170°F (77°C)  
D = approx. 160°F (71°C)  
C = approx. 150°F (65°C)  
B = approx. 140°F (60°C)  
Nearly Instantaneous  
Nearly Instantaneous  
About 1/2 Second  
The water temperature setting was factory set at the lowest temperature;  
Pressing the “COOLER”  
button decreases temperature and pressing  
About 1 1/2 Seconds  
Less than 5 Seconds  
the “HOTTER” button increases the temperature.  
B = approx. 130°F (54°C)  
= approx. 120°F (49°C)  
More than 30 Seconds  
More than 5 Minutes  
Setting the water heater temperature at 120°F (49°C) (Approx. “  
mark on temperature setting of gas valve) will reduce the risks of  
scalds. Some states or local codes require settings at specific lower  
temperatures.  
FIGURE26.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR YOUR INFORMATION  
conditions will cause a reaction between this rod and the water. The  
START UP CONDITIONS  
most common complaint associated with the anode rod is one of a  
“rotten egg smell” in the hot water. The smell is a result of four factors  
which must all be present for the odor to develop:  
SMOKE/ODOR  
It is not uncommon to experience a small amount of smoke and  
odor during the initial start-up. This is due to burning off of oil from  
metal parts, and will disappear in a short while.  
a. A concentration of sulfate in the supply water.  
b. Little or no dissolved oxygen in the water.  
c. A sulfate reducing bacteria which has accumulated within the  
water heater (this harmless bacteria is nontoxic to humans).  
d. An excess of active hydrogen in the tank. This is caused by the  
corrosion protective action of the anode.  
THERMAL EXPANSION  
Smelly water may be eliminated or reduced in some water heater  
models by replacing the anode(s) with one of less active material,  
and then chlorinating the water heater tank and all water lines. Contact  
the local water heater supplier or service agency for further information  
concerning anAnode Replacement Kit and this chlorination treatment.  
If the smelly water persists after the anode replacement and  
chlorination treatment, we can only suggest that chlorination or aeration  
of the water supply be considered to eliminate the water problem.  
Water supply systems may, because of such events as high line  
pressure, frequent cut-offs, the effects of water hammer among  
others, have installed devices such as pressure reducing valves,  
check valves, back flow preventers, etc. to control these types of  
problems. When these devices are not equipped with an internal  
by-pass, and no other measures are taken, the devices cause the  
water system to be closed. As water is heated, it expands (thermal  
expansion) and closed systems do not allow for the expansion of  
heated water.  
Do not remove the anode leaving the tank unprotected. By doing  
so, all warranty on the water heater tank is voided.  
“AIR” IN HOT WATER FAUCETS  
The water within the water tank expands as it is heated and  
increases the pressure of the water system. If the relieving point  
of the water heater’s temperature-pressure relief valve is  
reached, the valve will release the excess pressure. The  
temperature-pressure relief valve is not intended for the  
constant relief of thermal expansion. This is an unacceptable  
condition and must be corrected. It is recommended that any  
devices installed which could create a closed system have a  
by-pass and/or the system have an expansion tank or device to  
relieve the pressure built by thermal expansion in the water  
system. Expansion tanks are available for ordering through a  
local plumbing contractor. Contact the local water heater supplier  
or service agency for assistance in controlling these situations.  
HYDROGEN GAS: Hydrogen gas can be produced in a hot water  
system that has not been used for a long period of time (generally  
two weeks or more). Hydrogen gas is extremely flammable and  
explosive. To prevent the possibility of injury under these conditions,  
we recommend the hot water faucet, located farthest away, be  
opened for several minutes before any electrical appliances which  
are connected to the hot water system are used (such as a  
dishwasher or washing machine). If hydrogen gas is present, there  
will probably be an unusual sound similar to air escaping through  
the pipe as the hot water faucet is opened. There must be no  
smoking or open flame near the faucet at the time it is open.  
STRANGE SOUNDS  
Possible noises due to expansion and contraction of some metal  
parts during periods of heat-up and cool-down do not necessarily  
represent harmful or dangerous conditions.  
Condensation causes sizzling and popping within the burner area  
during heating and cooling periods and should be considered normal.  
See “Condensate” in this section.  
HIGH WATER TEMPERATURE SHUT OFF SYSTEM  
This water heater is equipped with an automatic gas shut-off system.  
This system works when high water temperatures are present. Turn  
“OFF” the entire gas supply to the water heater. The high temperature  
shut-off is built into the gas control valve. It is non-resettable. If the  
high temperature shut-off activates, the gas control valve must be  
replaced. Contact your gas supplier or service agency.  
OPERATIONAL CONDITIONS  
SMELLY WATER  
In each water heater there is installed at least one anode rod (see  
parts section) for corrosion protection of the tank. Certain water  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PERIODIC MAINTENANCE  
VENTING SYSTEM INSPECTION  
characteristics and ignition sequences. This can be done by  
removing the Outer Door and viewing the main burner operation  
through the Viewport on the Inner Door, see Figure 1. The main  
burner should provide complete combustion of gas, ignite rapidly,  
give reasonably quiet operation, and cause no excessive flame  
lifting from the burner ports. If the proper flame characteristics are  
not evident (see Figure 27), make sure that the flow of combustion  
and ventilation air is not blocked.  
You should also check for sooting. Soot is not normal and will impair  
proper combustion.Avisual inspection of the main burner and HSI igniter  
assembly should also be done at least once a year, see Figure 27.  
Soot build-up indicates a problem that requires correction before  
further use. Turn “OFF” gas to water heater and leave off until repairs  
are made, because failure to correct the cause of the sooting can  
result in a fire causing death, serious injury, or property damage.  
At least once a year a visual inspection should be made of the venting  
system. You should look for:  
FIGURE 27.  
1. Obstructions which could cause improper venting. The  
combustion and ventilation air flow must not be obstructed.  
2. Damage or deterioration which could cause improper venting or  
leakage of combustion products.  
BURNER CLEANING  
In the event your burner or burner air openings require cleaning,  
turn the blower switch to the “OFF” position and allow the burner  
to cool. Call a service agency to remove and clean the burner and  
correct the problem that required the burner to be cleaned.  
Be sure the vent piping is properly connected to prevent escape of  
dangerous flue gasses which could cause deadly asphyxiation.  
Obstructions and deteriorated vent systems may present serious  
health risk or asphyxiation.  
HOUSEKEEPING  
Chemical vapor corrosion of the flue and vent system may occur if  
air for combustion contains certain chemical vapors. Spray can  
propellants, cleaning solvents, refrigerator and air conditioner  
refrigerants, swimming pool chemicals, calcium and sodium  
chloride, waxes, bleach and process chemicals are typical  
compounds which are potentially corrosive.  
Vacuum around base of water heater for dust, dirt, and lint on a  
regular basis.  
If after inspection of the vent system you found sooting or deterioration,  
something is wrong. Call the local gas utility to correct the problem  
and clean or replace the flue and venting before resuming operation  
of the water heater.  
BURNER OPERATION AND INSPECTION  
Flood damage to a water heater may not be readily visible or  
immediately detectable. However, over a period of time a flooded  
water heater will create dangerous conditions which can cause  
DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.  
Contact a qualified installer or service agency to replace a flooded  
water heater. Do not attempt to repair the unit! It must be replaced!  
At least once a year a visual inspection should be made of the  
main burner and the hot surface igniter assembly for proper flame  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLED IN SUITABLEAREA: To insure sufficient ventilation and  
combustion air supply, proper clearances from the water heater must  
be maintained. See “Locating the New Water Heater” section.  
Combustible materials such as clothing, cleaning materials, or  
flammable liquids, etc. must not be placed against or adjacent to  
the water heater which can cause a fire.  
When checking the temperature-pressure relief valve operation,  
make sure that (1) no one is in front of or around the outlet of the  
temperature-pressure relief valve discharge line, and (2) that the  
water discharge will not cause any property damage, as the water  
may be extremely hot, see Figure 28.  
If after manually operating the valve, it fails to completely reset and  
continues to release water, immediately close the cold water inlet  
to the water heater, follow the draining instructions, and replace the  
temperature-pressure relief valve with a new one.  
ANODE ROD INSPECTION  
If the temperature-pressure relief valve on the appliance weeps or  
discharges periodically, this may be due to thermal expansion. You  
may have a check valve installed in the water line or a water meter  
with a check valve. Consult your local water supplier or service  
agency for further information. Do not plug the temperature-  
pressure relief valve.  
The anode rod is used to protect the tank from corrosion. Most hot  
water tanks are equipped with an anode rod. The submerged rod  
sacrifices itself to protect the tank. Instead of corroding the tank,  
water ions attack and eat away the anode rod. This does not affect  
the water’s taste or color. The rod must be maintained to keep the  
tank in operating condition.  
DRAINING  
Anode deterioration depends on water conductivity, not necessarily  
water condition. A corroded or pitted anode rod indicates high water  
conductivity and should be checked and/or replaced more often than  
an anode rod that appears to be intact. Replacement of a depleted  
anode rod can extend the life of your water heater. Inspection should  
be conducted by a qualified technician, and at a minimum should be  
checked annually after the warranty period.  
TEMPERATURE-PRESSURE  
RELIEF VALVE OPERATION  
The water heater should be drained if being shut down during  
freezing temperatures. Also periodic draining and cleaning of  
sediment from the tank may be necessary.  
1. Set the blower switch to the “OFF” position.  
2. CLOSE the cold water inlet valve to the water heater.  
3. OPEN a nearby hot water faucet and leave open to allow for  
draining.  
4. Connect a hose to the drain valve and terminate to an adequate  
drain.  
The temperature-pressure relief valve must be manually operated  
at least once a year.  
5. OPEN the water heater drain valve to allow for tank draining.  
NOTE: If the water heater is going to be shut down and  
drained for an extended period, the drain valve should be  
left open with hose connected allowing water to terminate  
to an adequate drain.  
6. CLOSE the drain valve.  
7. Follow instructions in the “Filling The Water Heater” section.  
8. Follow the lighting instructions on the label or see “Lighting  
Instructions” in this manual to restart the water heater.  
FIGURE 28.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE  
If you are not thoroughly familiar with gas codes, your water heater,  
and safety practices, contact your gas supplier or qualified installer  
to check the water heater.  
If a condition persists or you are uncertain about the operation of  
the water heater contact a service agency.  
Read this manual first. Then before checking the water heater make  
sure the gas supply has been turned “OFF”, and never turn the gas  
“ON” before the tank is completely full of water.  
Use this guide to check a “Leaking” water heater. Many  
suspected “Leakers” are not leaking tanks. Often the source of  
the water can be found and corrected.  
LEAKAGE CHECKPOINTS  
Never use this water heater unless it is completely filled with water.  
To prevent damage to the tank, the tank must be filled with water.  
Water must flow from the hot water faucet before turning “ON” gas  
to the water heater.  
B
A *Condensation may be seen on pipes in humid weather or pipe  
connections may be leaking.  
D
C
B. *The anode rod fitting may be leaking.  
C. Small amounts of water from temperature-pressure relief valve  
may be due to thermal expansion or high water pressure in your  
area.  
D. *The temperature-pressure relief valve may be leaking at the  
tank fitting.  
E. Water from a drain valve may be due to the valve being slightly  
opened.  
F. *The drain valve may be leaking at the tank fitting.  
F
G. Combustion products contain water vapor which can condense  
on the cooler surfaces of the tank. Droplets form and drip onto  
the burner or run on the floor. This is common at the time of  
start-up after installation and when incoming water is cold.  
G
E
H. Water in the water heater bottom or on the floor may be  
from condensation, loose connections, or the relief valve.  
DO NOT replace the water heater until a full inspection of  
all possible water sources is made and necessary  
corrective steps taken.  
Leakage from other appliances, water lines, or ground seepage  
should also be checked.  
*
To check where threaded portion enters tank, insert cotton swab  
between jacket opening and fitting. If cotton is wet, follow  
“Draining” instructions in the “Periodic Maintenance” section and  
then remove fitting. Put pipe dope or teflon tape on the threads  
and replace. Then follow “Filling the Water Heater” instructions  
in the “Installing the New Water Heater” section.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REPAIR PARTS LIST  
5
4
Key No.  
1
Part Description  
Outer Door  
2
Aluminum Anode  
Intellivent Control  
Plastic Top  
14  
15  
3
6
4
2
13  
5
Blower Assembly  
Switch and Harness Assembly  
T&P Valve  
6
7
7
8
Drain Valve  
9
Wiring Harness  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
Aluminum Anode Outlet  
Vent Pipe Assembly #1  
Vent Pipe Assembly #2  
Vent Pipe Assembly #3  
Inlet Tube  
10  
Pipe Nipple  
Burner Tube Assembly  
Hot Surface Igniter  
Burner Head Assembly  
Embossed Inner Door  
Insulation - Inner Door  
Insulation - Viewport  
Window - Observation  
Viewport  
12  
9
3
8
Nut - Serrated Hex Flange  
Screw - Sheet Metal, # 8-15  
Orifice - Burner  
Vent Kit Assembly  
Wall Plate 2”  
11  
1
Wall Plate 3”  
18  
Screen and Vent Terminal Assembly  
Instruction Tag-Wire Screen F/E 3”  
Instruction Tag-Wire Screen F/E 4”  
Instruction Sheet  
16  
17  
26  
Wire Screen 3”  
16  
Wire Screen 4”  
Wall Plate 4”  
Flexible Tubing  
25  
Reducing Hose Barb Tee  
Hose Barb Tee  
24  
20  
* Not Shown.  
** Optional  
21  
25  
23  
Now that you have purchased this water heater, should a need ever exist  
for repairpartsorservice, simplycontactthecompanyitwaspurchasedfrom  
ordirectfromthemanufacturerlistedontheratingplateonthewaterheater.  
19  
22  
24  
34 35  
27  
28  
39  
38  
Be sure to provide all pertinent facts when you call or visit.  
Selling prices will be furnished on request or parts will be  
shipped at prevailing prices and you will be billed accordingly.  
The model number of your Gas Water Heater will be found on the  
rating place located above the gas control valve.  
32  
30  
29  
31  
33  
WHEN ORDERING REPAIR PARTS, ALWAYS GIVE THE  
FOLLOWING INFORMATION:  
MODEL NUMBER  
TYPE GAS (NATURAL OR PROPANE (L.P.)  
SERIAL NUMBER  
37  
PART DESCRIPTION  
THIS IS A REPAIR PARTS LIST, NOT A PACKING LIST. PARTS  
ARE NOT DRAWN TO SCALE.  
36  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING GUIDELINES  
TROUBLE SHOOTING  
Please check guidelines below. For your safety, water heater service should be performed only by a qualified service technician.  
Read the GENERAL SAFETY INFORMATION section first.  
INTELLI-VENT TROUBLESHOOTING CHART - RESIDENTIAL CONTROL  
#
LED STATUS  
PROBLEM  
SOLUTION  
A B C  
Inadequate or no earth ground  
sensed by the Intelli-Vent™  
control.  
1. Ensure the wall outlet is properly grounded.  
1
2. Ensure all ground connections/wires on the  
water heater are secure.  
A B C  
Power supply to Intelli-Vent™  
control has reversed polarity or a  
high resistance to earth ground.  
1. Ensure the wall outlet is properly wired.  
2
2. Ensure all internal 120 VAC wiring connections and  
wiring harness have no reversed wires. 120 VAC  
“hot” wire must connect to the on/off switch.  
3. Ensure the wall outlet is properly grounded.  
4. Ensure all ground connections/wires on the water  
heater are secure.  
A B C  
Pressure switch circuit remaining  
closed for more than 5 seconds  
after heating cycle begins.  
Blower does not start.  
1. Ensure air pressure switch circuit wiring is correct  
and the air pressure switch is not jumpered.  
3
2. Secure power to water heater, check continuity of air  
pressure switch contacts with wires disconnected.  
Service Note:  
Disconnect power - disconnect one  
wire from the air pressure switch  
or the vent temperature limit  
switch. Turn power back on -  
blower should start.  
A If pressure switch contacts show continuity (closed  
circuit) replace the pressure switch.  
B If pressure switch contacts are open and all wiring  
is correct - turn the power off for 10-20 seconds  
then on again to clear the error code - if the error  
code persists replace the Intelli-Vent™ control.  
A B C  
Pressure switch circuit remains open  
longer than 5 seconds after the blower  
is energized.  
1. Ensure the blower is running - check for 120 VAC to  
the blower when the heating cycle begins, check the  
wiring. If the control does not energize the blower -  
replace the Intelli-Vent™ control. If the blower fails to  
start when energized -replace the blower assembly.  
4
Blower may run continuously in  
this condition.  
2. Ensure the air pressure switch sensing tube is properly  
connected - not kinked or damaged.  
3. Check continuity of vent temperature limit switch - replace  
switch if contacts remain open under 160ºF (71°C).  
4. Ensure the correct size of vent pipe (2”, 3”, 4”) was used  
per installation manual for vent length. Ensure maximum  
number of elbows or equivalent feet of vent pipe has not  
exceeded maximum limits.  
Service Note:  
To learn more about performing Air  
Pressure Switch tests visit our web  
technical bulletin A-023-06 Air Pressure  
Switches.  
5. Ensure there are no obstructions in the vent pipe.  
6. Check air pressure switch performance - check pressure  
with a digital manometer - check continuity of contacts.  
(see service note in left column) If the switch proves  
defective - replace the air pressure switch and or the  
blower assembly as required.  
7. If air pressure switch performance test results prove  
the air pressure switch is working properly and error  
code 4 persists - replace the Intelli-Vent™ control.  
A B C  
The Intelli-Vent™ control has detected  
an open ignitor circuit.  
1. Check wiring to the hot surface ignitor - replace ignitor  
assembly if wiring is damaged or worn.  
5
Service Note:  
2. Check ignitor assembly plug and the socket on the  
Intelli-Vent™ body for good connection. Replace  
ignitor assembly and/or control if necessary.  
The resistance (ohms) of a hot surface  
ignitor will increase over time. If the  
resistance at room temperature is near  
18.8 ohms - consider replacing the ignitor  
as a preventative measure.  
3. Check resistance of ignitor at room temperature 77ºF  
(25°C) at the plug end. Replace ignitor if resistance  
is not within 11.5 and 18.8 ohms at room temperature.  
4. If results from the above tests were good and error  
code 5 persists - replace the Intelli-Vent™ control.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING GUIDELINES  
TROUBLE SHOOTING  
Please check guidelines below. For your safety, water heater service should be performed only by a qualified service technician.  
Read the GENERAL SAFETY INFORMATION section first.  
INTELLI-VENT TROUBLESHOOTING CHART - RESIDENTIAL CONTROL  
#
LED STATUS  
PROBLEM  
SOLUTION  
Ignition/flame failure.  
1. Gas supply is turned off - pressure too low. Ensure  
supply and manifold gas pressures are within  
A B C  
6
The water heater has reached the  
maximum number of retries and is  
requirements in the installation manual. Manifold gas  
pressure is non-adjustable if pressure is off by more  
currently locked out for one hour.  
than 0.3” W.C. (75 Pa) replace the Intelli-Vent™ control.  
2. Low supply voltage - should be 115 -125 VAC.  
Cycle the power to the water heater  
off and on to reset.  
3. Ensure flame sensor is making good contact with the  
burner flame, ensure flame is steady see #8 below.  
Service Note:  
The resistance (ohms) of a hot surface  
ignitor will increase over time. If the  
resistance at room temperature is near  
18.8 ohms - consider replacing the ignitor  
as a preventative measure.  
4. Ensure the flame sensor is clean - use ultra fine steel  
wool or Scotch-Brite™ pad to clean flame sensor.  
5. Ensure the hot surface ignitor is positioned to provide  
consistent ignition.  
6. Check for any cracks in ignitor assembly ceramic  
insulators - replace ignitor assembly if damaged.  
7. Check resistance of ignitor at room temperature (77ºF)  
(25°C) at the plug end. Replace ignitor if resistance is  
not within 11.5 and 18.8 ohms at room temperature.  
8. Ensure the correct size of vent pipe (2”, 3”, 4”) was  
used per installation manual for vent length. Using larger  
pipe than required may cause excessive air turbulance  
in the combustion chamber.  
A B C  
Self diagnostic tests have found a problem  
with the gas valve driver circuit, internal  
microprocessor, or other internal circuits.  
1. Turn the power off for 10-20 seconds then on again to  
clear these error codes.  
7
8
2. If any of these error codes persist or cannot be cleared-  
replace the Intelli-Vent™ control.  
A B C  
A B C  
A B C  
9
Flame signal has been sensed out of  
proper sequence.  
1. Turn the power off for 10-20 seconds and then on again  
again to clear this error code.  
10  
2. Replace the Intelli-Vent™ control if this error code persists.  
A B C  
A B C  
A B C  
Water temperature in the tank has  
exceeded 195°F (91°C) and has  
activated the ECO.  
1. Turn the power off for 10-20 seconds then on again  
to clear this error code.  
11  
12  
2. Replace the Intelli-Vent™ if the error code persists.  
The self diagnostic check detected one  
or both of the temperature adjust buttons  
are stuck.  
1. Press and release temperature adjust buttons. If the  
above action does not clear the error, the control will  
continue to regulate water temperature at the last setting.  
However, settings will no longer be adjustable - the  
control should be replaced.  
The self diagnostic test has detected the  
water temperature sensor (thermistor) is  
either open or shorted.  
1. Turn the power off for 10-20 seconds then on again  
to clear this error code.  
13  
2. Replace the Intelli-Vent™ control if this error code persist.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING GUIDELINES  
These guidelines should be utilized by a qualified service agent.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIMITED RESIDENTIAL GAS WARRANTY  
b. Shipping and delivery charges for forwarding the new water heater or  
THIS WARRANTY IS APPLICABLE TO THE ORIGINAL OWNER ONLY.  
If the glass lined tank in this water heater shall prove upon examination by  
(thewarrantor)tohaveleakedduringthewarrantyperiodinnormalresidential  
use, due to natural corrosion from potable water therein, the warrantor will  
furnish the ORIGINAL OWNER a replacement water heater of equivalent  
size and current model, or a replacement part for any component part which  
fails in normal use, in accordance with the warranty terms and conditions  
specifiedbelow. THEWATERHEATERREPLACEMENTMODELORPART  
WILLBEWARRANTEDFORONLYTHEUNEXPIREDPORTIONOFTHE  
ORIGINAL WARRANTY. The warranty period will be determined by the  
original installation date of the water heater. PROOF-OF-PURCHASEAND  
PROOF-OF-INSTALLATION ARE NECESSARY TO VALIDATE THIS  
WARRANTY. This warranty is not transferable.  
replacement part from the nearest distributor and returning the claimed  
defective heater or part to such distributor except in the state of  
California where such charges are the manufacturer’s responsibility.  
c. All cost necessary or incidental for handling and administrative  
charges, and for any materials and/or permits required for  
installation of the replacement heater or part.  
LIMITATION ON IMPLIED WARRANTIES  
Implied warranties, including any warranty of merchantability imposed on  
the sale of this heater under state law are limited to one year duration for the  
heater or any of its parts. Some states do not allow limitations on how long  
an implied warranty lasts, so the above limitations may not apply to you.  
CLAIM PROCEDURE  
Any claim under this warranty should be initiated with the dealer who  
sold the heater, or with any other dealer handling the warrantor’s products.  
WARRANTY PERIOD  
Product Line  
TANK1  
PARTS2  
GPHE-50  
6 YEARS  
6 YEARS  
The warrantor will only honor replacement with identical or similar  
water heater or parts thereof which are manufactured or distributed  
by the warrantor.  
When the water heater has been used for other than single family  
residential application: 1. The Tank warranty shall be reduced to 3 years  
on 10 year models and 1 year on 6 and 8 year models. 2. The parts  
warranty shall be reduced to 1 year for all models. Returned parts which  
meet any of the following conditions are not covered by this warranty: 1)  
improper installation or removal; 2) damaged by other than normal wear;  
3) replaced for cosmetic purposes; or 4) returned with defaced date codes.  
Dealer replacements are made subject to in-warranty validation by  
warrantor.  
PROOF-OF-PURCHASE AND PROOF-OF-INSTALLATION DATES  
ARE REQUIRED TO SUPPORT WARRANTY FOR CLAIM FROM  
ORIGINALOWNER. THIS FORM DOES NOT CONSTITUTE PROOF-  
OF-PURCHASE OR PROOF-OF-INSTALLATION.  
CONDITIONS AND EXCEPTIONS  
This warranty shall apply only when the water heater is installed and  
operated in accordance with: 1) all local fire codes and plumbing codes,  
ordinances and regulations; 2) the printed instructions provided with it;  
3) good industry practices; and 4) proper safety practices such as but  
not limited to a properly sized drain pan if installed in an area where  
leakage from connections of the tank would result in damage to the  
area adjacent to the heater. In addition, a new temperature and pressure  
relief valve, certified by the Canadian StandardsAssociation must have  
been properly installed and piped to the nearest drain.  
DISCLAIMERS  
NO EXPRESS WARRANTY HAS BEEN OR WILL BE MADE IN BEHALF  
OF THE WARRANTOR WITH RESPECT TO THE MERCHANTABILITY  
OF THE HEATER OR THE INSTALLATION, OPERATION, REPAIR OR  
REPLACEMENTOFTHEHEATERORPARTS. THEWARRANTORSHALL  
NOT BE RESPONSIBLE FOR WATER DAMAGE, LOSS OF USE OF THE  
UNIT,INCONVENIENCE,LOSSORDAMAGETOPERSONALPROPERTY,  
OR OTHER CONSEQUENTIAL DAMAGE. THE WARRANTOR SHALL  
NOTBELIABLEBYVIRTUEOFTHISWARRANTYOROTHERWISEFOR  
DAMAGE TO ANY PERSONS OR PROPERTY, WHETHER DIRECT OR  
INDIRECT, AND WHETHERARISING IN CONTRACT OR IN TORT.  
This warranty shall apply only when the heater is:  
owned by the original purchaser;  
used at temperatures not exceeding the maximum calibrated  
setting of its thermostat;  
not subjected to excessive water pressure fluctuations and not  
subject to an operating pressure greater than 150 P.S.I.;  
filled with potable water, free to circulate at all times and with the  
tank free of damaging water sediment or scale deposits;  
used in a non-corrosive and non-contaminated atmosphere;  
used with factory approved anode(s) installed;  
in its original installation location;  
in the United States and its territories or possessions or Canada;  
sized in accordance with proper sizing techniques for residential  
water heaters;  
bearing a rating plate which has not been altered, defaced or  
removed except as required by the warrantor;  
used in an open system or in a closed system with a properly  
sized and installed thermal expansion tank;  
fired at the factory rated input using the fuel stated in the face of  
the rating plate;  
Some states do not allow the limitation or exclusion of incidental or  
consequential damages, so the above limitation or exclusion may not  
apply to you.  
This warranty gives you specific legal rights, and you may also have  
other rights which vary from state to state. Should governmental  
regulations or industry standards prohibit the Manufacturer from furnishing  
a comparable model replacement under this warranty, the Owner will be  
furnished with the closest comparable water heater meeting the current  
governmental regulations and industry standards. A supplementary fee  
may be assessed to cover the additional cost associated with the changes  
made to meet applicable regulations and standards.  
Fill out and keep with water heater.  
operated with the inner and outer combustion chamber doors  
in place;  
maintained in accordance with the instructions printed in the  
manual included with the heater.  
IMPORTANT INFORMATION  
Model Number____________________________________________  
Serial Number_____________________________________________  
Installation Information:  
Any accident to the water heater or any part thereof (including freezing,  
fire, floods, or lightning), any misuse, abuse or alteration of it, any  
operation of it in a modified form, or any attempt to repair tank leaks  
or parts, will void this warranty.  
Date Installed _____________________________________________  
Company’s Name _________________________________________  
Street or P.O. Box _________________________________________  
City, State, and Zip Code ___________________________________  
Phone Number _______________Plumber’s Name_______________  
SERVICE AND LABOR RESPONSIBILITY  
UNDER THIS LIMITED WARRANTY, THE WARRANTOR WILL  
PROVIDE ONLY A REPLACEMENT WATER HEATER OR PART  
THEREOF. THE OWNER IS RESPONSIBLE FORALLOTHER COSTS.  
Such costs may include but are not limited to:  
a. Labor charges for service, removal, or reinstallation of the water  
heater or part thereof.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

3D Connexion Elliptical Trainer RMR203HG User Manual
3M Automobile Accessories MR3 User Manual
3M Water System STM150 User Manual
Airlink101 Switch ASW108 User Manual
American Standard Plumbing Product 41751 User Manual
Asus Computer Drive W H D A 1 User Manual
Atlona TV Cables AT80COMP5 User Manual
AVerMedia Technologies DVR EB1304 NET User Manual
Axis Communications Security Camera Axis 210A User Manual
BC Speakers Speaker 10PLB76 User Manual