Bunn HC 2 HC 3 User Manual

®
BUNN  
HC-2  
HC-3  
(SERIAL # HC00025000 - UP)  
OPERATING & SERVICE MANUAL  
BUNN-O-MATICCORPORATION  
POST OFFICE BOX 3227  
SPRINGFIELD, ILLINOIS 62708-3227  
PHONE: (217) 529-6601 FAX: (217) 529-6644  
27591.0000 6/00 ©1996 Bunn-O-Matic Corporation  
USER NOTICES  
Carefully read and follow all notices on the equipment and in this manual. They were written for your protection.  
All notices are to be kept in good condition. Replace any unreadable or damaged labels.  
26525.0000  
00656.0000  
00831.0000  
12368.0002  
11646.0000  
27620.0000  
27591 061500  
3
INITIAL SET-UP  
1. Locate the drip tray assembly beneath the dispenser nested in the packing material.  
2. Remove the drip tray and the drip tray cover and set them aside.  
3. Remove the water strainer assembly from the drip tray and set it aside.  
4. Remove the four legs from the drip tray, apply non-skid pads to the bottom of the legs and securely install  
the legs in the dispenser base.  
ELECTRICAL REQUIREMENTS  
CAUTION - The dispenser must be disconnected from the power source until specified in Initial Set-Up.  
The 120 volt version of this dispenser has an attached cordset. The mating connector must be a NEMA 5-15R.  
L2 RED  
WHITE  
L2 WHITE  
120V A.C.  
WHITE  
208 or  
NEUTRAL  
L1BLACK  
120V. A.C.  
240V a.c.  
240V A.C.  
L1 BLACK  
120V A.C.  
L1BLACK  
P2185  
P2185  
P1841  
Amodels require 2-wire,  
grounded service rated 240  
volts ac, 20 amp, single  
phase, 50 Hz  
Requires 2-wire grounded ser-  
vice rated 120 volts ac, 15 amp,  
single phase, 60 Hz  
Requires 3-wire, grounded service  
rated 120/208 volts or 120/240 volts  
ac, 20 amp, single phase, 60 HZ  
ELECTRICAL HOOK-UP  
CAUTION - Improper electrical installation will damage electronic components.  
1. An electrician must provide electrical service as specified.  
2. Using a voltmeter, check the voltage and color coding of each conductor at the electrical source.  
3. Open the front door of the dispenser and place the heater switch in the OFF(upper position).  
4. Remove the right side panel of the dispenser.  
120 volt versions proceed to step 6.  
120/240 volt and 240 volt versions proceed to next step.  
5. Install the electrical wiring to the terminal block as illustrated above.  
6. Connect the dispenser to the power source and verify the voltage at the terminal block. Reinstall the side  
panel.  
7. If plumbing is to be hooked-up later be sure the dispenser is disconnected from the power source. If  
plumbing has been hooked-up, the dispenser is ready for Initial Fill & Heat.  
PLUMBING REQUIREMENTS  
This dispenser must be connected to a COLD WATER system with operating pressure between 20 and 90 psi (138  
and 620 kPa) from a 12" or larger supply line. A shut-off valve should be installed in the line before the dispenser.  
Install a regulator in the line when pressure is greater than 90 psi (620 kPa) to reduce it to 50 psi (345 kPa). The  
water inlet fitting is 14" flare.  
NOTE - Bunn-O-Matic recommends 14" copper tubing for installations of less than 25 feet and 38" for more than  
25 feet from the 12" water supply line. At least 18 inches of an FDA approved flexible beverage tubing, such as  
reinforced braided polyethylene or silicone, before the dispenser will facilitate movement to clean the countertop.  
It can be purchased direct from Bunn-O-Matic (part number 00326-0000). Bunn-O-Matic does not recommend  
the use of a saddle valve to install the dispenser. The size and shape of the hole made in the supply line by this type  
of device may restrict water flow.  
This equipment must be installed to comply with the Basic Plumbing Code of the Building  
Officials and Code Administrators International, Inc. (BOCA) and the Food Service Sanita-  
tion Manual of the Food and Drug Administration (FDA).  
27591 061500  
4
PLUMBING HOOK-UP  
1. Securely attach the short piece of tubing on the water strainer assembly to the inlet fitting on the bottom of  
the dispenser.  
2. Flush the water line and securely attach it to the flare fitting on the water strainer assembly.  
3. Turn-on the water supply.  
INITIAL fill & heat  
CAUTION - The dispenser must be disconnected from the power source throughout the initial set-up, except  
when specified in the instructions.  
1. Turn-on the water supply and connect the dispenser to the power source.  
2. Water will automatically flow into the tank to the proper level and then shut-off. This will take less than five  
minutes.  
3. When the tank is full of water, open the front door and place the heater switch in the ON(lower) position.  
A tank full of cold water will take approximately forty minutes for the water to heat on 120 volt versions, and  
twenty minutes on 120/240 and 240 volt versions.  
During this waiting period, complete these dispenser set-up steps:  
a. Place the drip tray in front of the dispenser. Set the drip tray cover in place.  
b. Place a set of keyholes in the cup locator plate over the screws beneath the hopper access door and push  
down gently.  
c. Fill the hopper(s) with the dry product to be dispensed.  
DISPENSER USE  
1. Simply place a cup on the drip tray beneath the desired dispensing tip.  
2. Press the button to froth and dispense the beverage.  
3. Release the button when the cup is approximately 2/3 full and allow the mixing chamber to drain.  
NOTE - The mixing chamber must drain at the end of each dispense.  
COLD BEVERAGE SET-UP (OPTIONAL)  
Cold beverages may be dispensed from the left dispense position on the HC-2 & HC-3 models. Simply place  
the HOT/COLD switch near the left whipper chamber in the COLD(upper) position.  
CLEANING  
Refer to the decal inside the hopper access door for cleaning recommendations and procedures.  
The use of a damp cloth rinsed in any mild, non-abrasive, liquid detergent is recommended for cleaning all  
surfaces on Bunn-O-Matic equipment.  
ADJUSTMENTS  
The hot or cold beverage solenoid(s) is (are) preset to dispense approximately one ounce per second. This  
amount can be adjusted:  
1. Disconnect the dispenser from the power source.  
2. Remove the small right side access panel.  
3. Rotate the control at the base of the desired solenoid(s) clockwise to decrease or counterclockwise to  
increase the amount of water.  
4. For cold beverage adjustment remove the 1-1/2plug on the lower left side of the dispenser and rotate the  
needle valve clockwise to decrease or counterclockwise to increase the amount of cold water.  
27591 031597  
5
DRAINING THE HOT WATER TANK  
CAUTION - The dispenser must be disconnected from the power source throughout these steps.  
1. Disconnect the dispenser from the power source.  
2. Open front door and place tank heater switch in the OFF(upper) position.  
3. Shut-off and disconnect the incoming water supply.  
4. Remove the top panel.  
5. Gently remove one of the grommets from the tank lid.  
6. Insert a tube to the bottom of the tank and syphon ALL of the water out.  
(Bunn-O-Matic has a syphon assembly #12440.0000 available for this purpose.)  
NOTE - The dispenser must be refilled using the INITIAL FILL & HEAT steps before reconnecting to the power  
source.  
HOPPER DISPENSE RATE OF PRODUCT  
1. Hopper dispense rate with 22 tooth gear and auger wire is approximately 4 to 6 grams per second.  
2. Hopper dispense rate with 22 tooth gear and auger wire with optional restrictor is approximately 3 to 5  
grams per second.  
3. Hopper dispense rate with optional 32 tooth gear and auger wire is 6 to 9 grams per second.  
TROUBLESHOOTING  
A troubleshooting guide is provided to suggest probable causes and remedies for the most likely problems  
encountered. If the problem remains after exhausting the troubleshooting steps, contact the Bunn-O-Matic  
Technical Service Department.  
Inspection, testing, andrepairofelectricalequipmentshouldbeperformedonlybyqualifiedservicepersonnel.  
All electronic components have 120 volt ac or 240 volt ac and low voltage dc potential on their terminals.  
Shorting of terminals or the application of external voltages may result in board failure.  
Intermittent operation of electronic circuit boards is unlikely. Board failure will normally be permanent. If an  
intermittent condition is encountered, the cause will likely be a switch contact or a loose connection at a  
terminal or crimp.  
Solenoid removal requires interrupting the water supply to the valve. Damage may result if solenoids are  
energized for more than ten minutes without a supply of water.  
Theuseoftwowrenchesisrecommendedwheneverplumbingfittingsaretightenedorloosened. Thiswillhelp  
to avoid twists and kinks in the tubing.  
Make certain that all plumbing connections are sealed and electrical connections tight and isolated.  
This unit is heated at all times. Keep away from combustibles.  
WARNING – • Exercise extreme caution when servicing electrical equipment.  
Unplug the dispenser when servicing, except when electrical tests are specified.  
Follow recommended service procedures  
Replace all protective shields or safety notices  
27591 031597  
6
TROUBLESHOOTING (cont.)  
PROBLEM  
PROBABLE CAUSE  
REMEDY  
1. No water  
Water lines and valves to the  
dispenser must be open.  
Product will not dispense  
2. No power or incorrect voltage to (A1) Check the terminal block for  
the dispenser  
120 volts across the black and  
white terminals on two wire 120  
volt dispenser.  
(A2) Check the terminal block for  
120 volts across the red and  
white terminal and the black and  
white terminal on three wire  
120/240 volt dispenser.  
(A3) Check the terminal block for  
240 volts across the white and  
black terminal on two wire 240  
volt dispenser.  
(B) Check circuit breakers or  
fuses.  
3. Dispense switch  
Refer to Service - Dispense  
Switch for testing procedure.  
See page 18  
4. Dispense solenoid valve  
(Hot or Cold)  
Refer to Service - Dispense  
solenoid valve for testing proce-  
dures. See page 30 or 31  
5. Solenoid valve (Inlet)  
6. Level control board and probe  
7. Overflow protection switch  
8. Auger drive  
Refer to Service - Solenoid Valve  
(Inlet) for testing procedures.  
See page 32  
Refer to Service - Level Control  
Board and Probe for testing  
procedures. See page 26  
Refer to Service - Overflow  
protection switch for testing  
procedures. See page 28  
Refer to Service - Auger Drive.  
See page 12  
27591 031597  
7
TROUBLESHOOTING (cont.)  
PROBLEM  
PROBABLE CAUSE  
REMEDY  
9. Water strainer  
(A) Direction of flow arrow must  
be pointing towards dispenser.  
Product will not dispense (cont.)  
(B) Remove the flow control and  
check for obstructions. Clear or  
replace.  
10. Lime build-up  
Inspect the tank assembly for  
CAUTION - Tank and tank compo- excessive lime deposits. Delime as  
nents should be delimed regularly  
depending on local water condi-  
tions. Excessive mineral build-up  
on stainless steel surfaces can  
initiate corrosive reactions result-  
ing in serious leaks.  
required.  
1. Limit thermostat  
Refer to Service - Limit Thermo-  
stat for testing procedures. See  
page 27  
Water is not hot  
CAUTION - Do not eliminate or  
bypass limit thermostat. Use only  
BOM replacement part  
#29329.1000  
2. Control thermostat (mechanical Refer to Service - Control Thermo-  
or electronic)  
stat for testing procedures. See  
page 16  
3. Tank Heater  
Refer to Service - Tank Heater for  
testing procedures. See page 33  
4. Tank heater switch  
Refer to Service - Tank Heater  
Switch for testing procedures. See  
page 34  
1. Lime build-up  
Inspect tank assembly for exces-  
Spitting or excessive steaming  
CAUTION - Tank and tank compo- sive lime deposits. Delime as  
nents should be delimed regularly  
depending on local water condi-  
tions. Excessive mineral build-up  
on stainless steel surfaces can  
initiate corrosive reactions result-  
ing in serious leaks.  
required.  
2. Control thermostat (mechanical Refer to Service - Control Thermo-  
or electronic)  
stat for testing procedures. See  
page 16  
27591 061500  
8
TROUBLESHOOTING (cont.)  
PROBLEM  
REMEDY  
PROBABLE CAUSE  
Inspect the tank assembly for  
excessive lime deposits. Delime as  
required.  
Dripping from dispense tip  
1. Lime build-up  
CAUTION - Tank and tank compo-  
nents should be delimed regularly  
depending on local water condi-  
tions. Excessive mineral build-up  
on stainless steel surfaces can  
initiate corrosive reactions result-  
ing in serious leaks.  
Remove the dispense solenoid  
valve and clear any obstructions.  
Rebuild or replace the valve if  
necessary. See page 30 or 31  
2. Dispense solenoid valve  
(Hot or Cold)  
Refer to Service - Level Control  
Board and Probe for testing  
procedures. See page 26  
Water flows into tank continuously 1. Level control board and probe  
2. Solenoid valve (Inlet)  
Refer to Service - Solenoid Valve  
(Inlet) for testing procedures. See  
page 32  
Refer to Service - Overflow  
Protection Switch for testing  
procedures. See page 28  
3. Overflow Protection Switch  
27591 031597  
9
TROUBLESHOOTING (cont.)  
PROBLEM  
REMEDY  
PROBABLE CAUSE  
Product overflows container  
Refer to Service - Dispense  
Switch for testing procedures. See  
page 18  
1. Dispense switch  
Remove the solenoid valve and  
clear any obstructions. Rebuild or  
replace the valve if necessary. See  
page 30 or 31  
2. Dispense solenoid valve  
(Hot or Cold)  
Weak product  
Place an empty container beneath  
the dispense tip. Initiate a dispense  
cycle and check the water tempera-  
tureimmediatelybelowthedispense  
tip with a thermometer.  
1. Water temperature  
(A) Reading for mechanical thermo-  
statmodelsshouldbe180°Fto200°F  
(seethermostattemperaturesettings  
decal in USER NOTICES on page 3.  
(B) Reading for electronic thermo-  
stat should be185°F to 190°F.  
Adjust the control thermostat to in-  
crease or decrease the water tem-  
perature. Replace if necessary.  
Referto Service-WhipperMotorfor  
testing procedure. See page 20  
2. Whipper motor  
3. Frother  
Refer to Service - Frother Compo-  
nents. See page 20  
RefertoService-DispenseSolenoid  
Valve for test procedures. See page  
30 or 31  
4. Dispense solenoid valve  
(Hot or Cold)  
Refer to Service - Auger Drive Com-  
ponents. See page 12  
5. Auger drive  
6. Auger spring  
7. Auger motor  
Refer to Service - Auger Drive Com-  
ponents. See page 12  
Refer to Service - Auger Drive Com-  
ponents. See page 14  
27591 031597  
10  
TROUBLESHOOTING (CONT.)  
PROBLEM  
PROBABLE CAUSE  
REMEDY  
Dispenser is making unusual  
noises  
1. Plumbing Lines  
Plumbing lines should not be rest-  
ing on the counter top.  
2. Water Supply  
(A)Thedispensermustbeconnected  
to a cold water line  
(B) Water pressure to the dispenser  
must not exceed 90 psi (620 kPa).  
Install a regulator if necessary to  
lower the working pressure to ap-  
proximately 50 psi (345 kPa).  
3. Tank Heater  
1. Fan  
Remove and clean lime off the tank  
heater. See page 33  
Excess dust  
Refer to Service - Fan for testing  
procedures. See page 19  
2. Hopper Delay Board  
Refer to Service - Hopper Delay  
Board for testing procedures. See  
page 22  
3. Transformer (240V 2 Wire  
Models Only)  
Refer to Service - Transformer for  
testing procedures. See page 35  
Display not lit  
1. Lamp  
Refer to Service - Lamp, see page  
24 for lamp replacement.  
2. Lamp Holder  
3. Starter - Lamp  
4. Ballast  
Refer to Service - Lamp Holder for  
testing procedures. See page 24  
Refer to Service - Starter for  
testing procedures. See page 25  
Refer to Service - Ballast for  
testing procedures. See page 15  
27591 061500  
11  
AUGER DRIVE COMPONENTS  
SERVICE  
Thissectionprovidesproceduresfortestingand  
replacing various major components used in this  
dispenser should service become necessary. Refer to  
Troubleshooting for assistance in determining the  
cause of any problem.  
WARNING - Inspection, testing, and repair of electri-  
cal equipment should be performed only by qualified  
service personnel. The dispenser should be un-  
plugged when servicing, except when electrical tests  
are required and the test procedure specifically states  
to plug-in the dispenser.  
COMPONENT ACCESS  
WARNING-Disconnectthedispenser fromthepower  
source before the removal of any panel or the replace-  
ment of any component.  
All components are accessible by opening the  
door, removal of the door covers, reflector, dispenser  
top covers, left and right side covers.  
Refer to the contents listing for component loca-  
tion.  
Contents  
P1199.45  
FIG. 1 AUGER DRIVE COMPONENTS  
Location  
The auger components are located inside  
Auger Drive Components......................................12  
Auger Motor .........................................................14  
Ballast...................................................................15  
Control Thermostat...............................................16  
Dispense Switch ...................................................18  
Fan........................................................................19  
Frother ................................................................. 20  
Hopper Delay Board..............................................22  
Hot/Cold Switch....................................................23  
Lamp Holder .........................................................24  
Lamp ....................................................................24  
Lamp Starter and Socket ......................................25  
Level Control Board and Level Probe....................26  
Limit Thermostat ..................................................27  
Overflow Protection Switch ..................................28  
Rinse/Run Switch .................................................29  
Solenoid (Cold Drink - Optional)...........................30  
Solenoid (Dispense) .............................................31  
Solenoid (Inlet) .....................................................32  
Tank Heater ..........................................................33  
Tank Heater Switch...............................................34  
Transformer (240V Models Only) .........................35  
Whipper Motor .....................................................20  
Wiring Diagrams.......................................... 37 & 38  
the bottom part of the hopper except for the auger  
drive bracket, washer and locknut, which are located  
on the outside bottom rear of the hopper. The auger  
motors are located on the rear of the front panel.  
Refer to Fig. 2 for disassembly and assembly.  
Test Procedures - Auger motors  
1. Disconnect the dispenser from the power source.  
2. Disconnect the wires from the motor to be tested.  
3. Check the voltage across the white/violet wire for  
the right motor, white/blue wire for the center  
motor or the white/red wire for the left motor and  
the white/black wire with a voltmeter. Press and  
holdtheappropriateDispenseswitch. Connectthe  
dispenser to the power supply. The indication  
must be :  
a) 120 volts ac for two wire 120 volt models.  
b) 120 volts ac for three wire 120/208 volt or 120/  
240 volt models.  
c) 240 volts ac for two wire 240 volt models.  
4. Disconnect the dispenser from the power supply.  
27591 031597  
12  
SERVICE  
AUGER DRIVE COMPONENTS (cont.)  
4
1
2
3
5
If voltage is present as described, proceed to #5.  
If voltage is not present as described, refer to the wir-  
ing diagrams and check the dispenser wiring harness.  
6
11  
13  
5. With the wires removed from the motor to be  
tested. Check for continuity across the two ter-  
minals on the bottom of the auger motor.  
If continuity is present as described, reconnect the  
wires to the terminals on the bottom of the auger  
motor, the auger motor is operating properly.  
7
8
9
10  
12  
If continuity is not present as described, replace the  
auger motor.  
14  
Removal, Cleaning and Replacement  
21  
Hopper & Auger  
1. Open the dispenser door and raise the top front  
cover.  
2. Lift the front edge of hopper assy (21) over the  
tab on hopper support plate (20) and slide hop-  
per assembly out the front of the dispenser.  
3. Remove hopper lid (1) and empty product.  
4. Pull off the ejector elbow (14).  
5. Remove auger disc assy (2) by pulling agitator  
support rod (4) towards agitator disc assy and  
lifting agitator disc assy from hopper (10).  
6. Remove auger (12) by pulling it out the front of  
the hopper (10).  
15 16 17 18 19 20  
7. Remove auger drive shaft (5) by removing the  
retaining clip (6) from auger drive shaft.  
8. Slide washer (8) and auger drive shaft bracket  
(7) off of the auger drive shaft (5).  
9. Slide auger drive shaft (5) from auger drive shaft  
bushing (3) and remove from hopper (10).  
10. Remove locknut (9) from auger drive shaft bush-  
ing (3) and remove auger drive shaft bushing  
from hopper (10).  
11. Wash components in a mild solution of dish de-  
tergent using a bristle brush when needed.  
12. Rinse and dry each item thoroughly.  
13. Check for damaged or broken components, re-  
place any if necessary and reassemble hopper  
assy.  
P1200.35  
FIG. 2 AUGER DRIVE & HOPPER DISASSEMBLY  
10. Hopper  
11. Spring  
12. Auger Wire  
1. Hopper Lid  
2. Agitator Disc Assy  
3. Auger Drive Bracket  
4. Agitator Support Rod  
5. Auger Drive Shaft  
Bushing  
6. Retainer Clip  
7. Auger Drive Bracket  
8. Washer  
13. Auger Wire/Restrictor  
(Optional)  
14. Ejector Elbow  
15. Wiring Harness Clamp  
16. Auger Motor Bracket  
17. Auger Motor  
18. Dust Seal  
19. Shoulder Screw  
20. Hopper Support plate  
21. Hopper Assy  
27591 111596  
9. Locknut  
13  
5. Remove auger motor mounting bracket (16),  
auger motor (17) and dust seal (18) as an as-  
sembly.  
SERVICE (cont.)  
AUGER DRIVE COMPONENTS (cont.)  
6. Remove dust seal (18) from auger motor (17).  
7. Remove the three #8-32 screws securing the left  
auger motor to the auger motor mounting bracket  
or the four #8-32 screws securing the center and  
right auger motors to the auger motor mounting  
bracket.  
14. Install hopper assy (21) in the dispenser by slid-  
ing hopper assy in the guides on the hopper sup-  
port plate (20) until the slot in the bottom rear  
the hopper seats against the shoulder screw (19)  
in the hopper support plate.  
8. Remove auger motor and discard.  
9. Using three #8-32 screws on the left auger mo-  
tor or four #8-32 screw on the center or right  
auger motor install new auger motor (17) on  
mounting bracket (16).  
10. Install dust seal (18) on auger motor shaft.  
11. Using four #8-32 locking screws install auger  
motor, dust seal and mounting bracket to the rear  
of the front panel.  
12. Left auger motor only - Using one #8-32 screw  
attach hose routing clamp (15) to the mounting  
bracket.  
13. Reconnect the wires to the terminals on the bot-  
tom of the auger motor.  
Auger Drive Motor (Refer to Fig. 2)  
1. Disconnect the wires from the auger motor (17)  
to be removed.  
2. Remove hopper assy (21) and set aside for reas-  
sembly.  
3. Left side auger motor only - Remove the #8-32  
screw securing hose routing clamp (15) and au-  
ger motor (17) to the auger motor mounting  
bracket (16).  
4. Remove the four #8-32 locking screws, located  
inside on the rear of the front housing, securing  
auger motor mounting bracket (16) and auger  
motor (17) to the rear of the front panel.  
14. Install hopper assy (21).  
15. Refer to the illustration below when reconnect-  
ing wires.  
CENTER HC-3 ONLY  
RIGHT HC-2 & 3  
LEFT HC-2 & 3  
WHI/BLK to Run/Rinse  
Switch  
WHI/BLK to Run/Rinse  
Switch  
WHI/BLU from Hopper  
Delay Circuit Board  
WHI/BLK to  
Run/Rinse  
Switch  
WHI/RED from Hopper  
Delay Circuit Board  
WHI/VIO from Hopper  
Delay Circuit Board  
T1201  
FIG. 3 AUGER MOTOR TERMINALS  
27591 031597  
14  
If voltage is not present as described, replace the  
ballast.  
SERVICE (cont.)  
BALLAST  
Removal and Replacement  
1. Disconnect the wires from the ballast.  
2. Remove the two #8-32 keps nuts securing the  
ballast to the dispenser base.  
3. Remove and discard ballast.  
4. Install new ballast over the two weld studs on  
the dispenser base and secure with two #8-32  
keps nuts.  
5. Refer to the illustration below when reconnect-  
ing the wires.  
BLK to Terminal Block  
WHI to Main  
Wiring Harness  
WHI & BLU to  
Door  
Interconnect  
Harness  
120V, 120/208V, & 120/240V Models  
P1199.40  
WHI to Main  
FIG. 4 BALLAST  
Wiring Harness  
Location  
RED & BLU to  
Door  
Interconnect  
Harness  
The front door lamp ballast is located on the  
front center of the base behind the front panel.  
Test Procedure  
1. Disconnect the dispenser from the power source.  
2. Disconnect the two terminal plug of the door in-  
terconnect harness from the connector of the  
ballast.  
BLK to Terminal Block  
240V Models  
3. Check the voltage across the white wire and the  
blue wire terminal of the ballast with a voltmeter.  
Connect the dispenser to power source. The in-  
dication must be:  
P1202.45  
FIG. 5 BALLAST TERMINALS  
a) 120 volts ac for two wire 120 volt models.  
b) 120 volts ac for three wire 120/208 volt  
models or 120/240 volts models.  
c) 240 volts ac for two wire 240 volt models.  
If voltage is present as described the ballast is oper-  
ating properly.  
27591 031597  
15  
SERVICE (cont.)  
Test Procedure  
Mechanical Thermostat  
CONTROL THERMOSTAT  
1. Disconnect the dispenser from the power source.  
2. Disconnect the black wire of the control thermo-  
stat from the black lead from the limit thermo-  
stat.  
3. Remove bulb from the tank.  
4. Check the voltage across black wire on the con-  
trol thermostat and the white pole on the termi-  
nal block with the tank heater switch in the ON”  
lower position with a voltmeter. Connect the dis-  
penser to the power source. The indication must  
be:  
a) 120 volts ac for two wire 120 volt models.  
b) 120 volts ac for three wire 120/208 volt or  
120/240 volt models.  
MECHANICAL  
c) 240 volts ac for two wire 240 volt models.  
5. Disconnect the dispenser from the power source.  
P1199.45  
If voltage is present as described the control thermo-  
stat is operating properly. Reinstall bulb into the tank.  
If voltage is not present as described, replace the ther-  
mostat.  
Electronic Thermostat (Optional)  
1. Disconnect the dispenser from the power source.  
2. Disconnect the black wire of the control thermo-  
stat from the black lead from the limit thermostat.  
3. Remove temperature probe from the tank  
4. Check the voltage across black wire on the control  
thermostat and the white pole on the terminal  
block with the tank heater switch in the ONlower  
position with a voltmeter. Connect the dispenser  
to the power source. The indication must be:  
a) 120 volts ac for two wire 120 volt models.  
b) 120 volts ac for three wire 120/208 volt or 120/  
240 volt models.  
ELECTRONIC (OPTIONAL)  
P1203.45  
FIG. 6 CONTROL THERMOSTAT  
c) 240 volts ac for two wire 240 volt models.  
5. Disconnect the dispenser from the power source.  
Location  
Mechanical Thermostat  
If voltage is present as described the control thermo-  
stat is operating properly.Reinstall teperature probe  
into the tank.  
The mechanical thermostat is located on the  
upper right side of the rear panel inside the dispenser.  
If voltage is not present as described, replace the ther-  
mostat.  
Electronic Thermostat (Optional)  
The electronic thermostat is located on the  
right front side of the base just behind the front panel.  
27591 031597  
16  
9. Carefully bend the capillary tube so that the tube  
and bulb inside the tank are in the vertical posi-  
tion and away from any electrical connections.  
10. Refer to the illustration below and reconnect the  
wires.  
NOTE - The capillary tube must be clear of any electri-  
cal termination and not kinked.  
SERVICE (cont.)  
CONTROL THERMOSTAT (cont.)  
Removal and Replacement.  
Mechanical Thermostat  
1. Disconnect the wires from the thermostat.  
2. Remove the thermostat capillary bulb by firmly  
pulling-up on the capillary at the tank lid. This  
will disengage the grommet from the tank lid.  
3. Remove the #8-32 screw securing the thermo-  
stat to the rear panel.  
Electronic Thermostat (Optional)  
1. Disconnect the wires from the thermostat.  
2. Remove the two #8-32 keps nuts securing the  
thermostat to the dispenser base.  
3. Remove the temperature probe from the grom-  
met in the tank lid.  
4. Remove thermostat and discard.  
5. Install new thermostat over the studs on the dis-  
penser base and secure with two #8-32 keps nuts.  
6. Push the temperature probe into the grommet in  
the tank lid until the top of the tube is flush with  
grommet.  
4. Slide the thermostat off of the guide stud on the  
rear panel and discard.  
5
Slide new thermostat over the guide stud on rear  
panel.  
6. Secure the thermostat to the rear panel using a  
#8-32 screw.  
7. Slide the grommet to the line 4.5above the bulb  
on the new capillary tube.  
8. Insert the capillary bulb through the hole in the  
tank lid and press the grommet firmly and evenly  
so that the groove in the grommet fits into the  
tank lid.  
7. Refer to the illustration below and reconnect the  
wires.  
BLK to Limit Thermostat  
BLK to Limit  
Thermostat  
BLU to Tank  
Heater Switch  
TAN to Tank  
Heater  
Switch  
BLK to Terminal  
Block  
WHI to Terminal  
Block  
MECHANICAL  
ELECTRONIC  
P1204  
FIG. 7 THERMOSTAT TERMINALS  
27591 031597  
17  
5. Disconnect the dispenser from the power source.  
SERVICE (cont.)  
DISPENSE SWITCH  
If voltage is present as described, proceed to #6.  
If voltage is not present as described, refer to the wir-  
ing diagram and check the dispenser wiring harness.  
6. Check for continuity across the wires removed  
from the dispense switch with the switch in the  
ONpressed position. Continuity must not be  
present when the switch is in the OFFreleased  
position.  
If continuity is present as described, reconnect the  
connector to the door interconnect wiring harness, the  
switch is operating properly.  
If continuity is not present as described, replace the  
switch.  
Removal and Replacement  
1. Open the dispenser door.  
2. Remove the six #8-32 screws securing the bot-  
tom door cover and remove cover.  
3. Disconnect the connector on the dispense switch  
to be removed from the door interconnect wiring  
harness connector.  
P1196.70  
FIG.8 DISPENSE SWITCH  
4. Remove the mounting nut from the dispense  
switch and remove switch from the front side of  
the door.  
5. Install new switch through the front of the door  
and secure with mounting nut.  
6. Reconnect the connector on the dispense switch  
to the connector on door interconnect wiring har-  
ness.  
Location:  
The dispense switches are located on the lower  
outside of the dispenser door.  
NOTE: The center dispense switch is for HC-3 Models  
only.  
Test Procedure:  
1. Disconnectthedispenserfromthepowersource.  
2. Open the dispenser door and remove the bottom  
door cover.  
3. Disconnect the connector of the dispense switch  
to be tested from the connector on the door  
interconnect wiring harness.  
7. Reinstall the door bottom cover using six #8-32  
screws.  
8. Refer to the illustration below when reinstalling  
wires.  
4. Check for voltage across the black and red/black  
wires for the right dispense switch, black and  
red/white wires for the center dispense switch or  
the black and red wires for the left dispense  
switch in the connector of the door interconnect  
wiring harness. Connect the dispenser to the  
power supply. The indication must be:  
a) 120 volts ac for two wire 120 volt models.  
b)120voltsacforthreewire120/208voltor120/  
240 volt models.  
P1205.58  
c) 240 volts ac for two wire 240 volt models.  
FIG. 9 DISPENSE SWITCH CONNECTORS  
27591 031597  
18  
SERVICE (cont.)  
Removal and Replacement:  
1. Remove hoppers from the dispenser. Refer to Fig.  
2 for hopper removal.  
FAN  
2. Remove the four #8-32 screws securing the hop-  
per mounting plate to the front panel and remove  
panel.  
3. Remove the four screws securing the fan mount-  
ing plate to the dispenser front panel.  
4. Lift fan mounting plate out of the front panel far  
enough so the fan leads can be disconnected from  
the main wiring harness.  
5. Remove fan mounting plate, fan and exhaust tube  
as an assembly.  
6. Remove the four #8-32 screws and four #8-32  
nuts securing exhaust tube and fan to the bottom  
of the fan mounting plate and discard fan.  
7. Install new fan and the exhaust tube to the bottom  
of the fan mounting plate using four #8-32 screws  
and four #8-32 nuts.  
NOTE: Be sure arrow on the new fan is pointing down.  
8. Set fan mounting plate with fan and exhaust tube  
inside the front panel far enough to connect the  
black leads from the fan to the black and white  
leads on the main wiring harness.  
9. Install fan mounting plate into position and secure  
with four #8-32 screws.  
10. Install hopper mounting plate using four #8-32  
screws.  
P1199.45  
FIG. 10 FAN  
Location:  
The fan is located inside the front panel, mounted  
on a plate beneath the hopper mounting plate.  
11. Install hoppers, refer to Fig. 2.  
Test Procedures:  
1. Disconnect the dispenser from the power source.  
2. Disconnect the black and white wires from the  
black leads on the fan.  
3. Check the voltage across the black and white  
wires on the main harness or transformer with a  
voltmeter. Connect the dispenser to the power  
source. The indication must be:  
a) 120 volts ac for two wire 120 volts models.  
b) 120 volts ac for three wire 120/208 volt or 120/  
240 volt models.  
c) 120 volts ac for two wire 240 volt models.  
If voltage is present as described, replace the fan  
If voltage is not present as described, refer to wiring  
diagram and check the dispenser wiring harness.  
27591 031597  
19  
a) 120 volts ac for two wire 120 volt models.  
b) 120 volts ac for three wire 120/208 volt or 120/  
240 volt models.  
SERVICE (cont.)  
FROTHER AND WHIPPER MOTOR  
c) 240 volts ac for two wire 240 volt models.  
4. Disconnect the dispenser from the power source.  
If voltage is present as described, replace the motor.  
If voltage is not present as described, refer to the wir-  
ing diagrams and check the dispenser wiring harness.  
1 2  
12  
11  
P1203.45  
FIG. 11 FROTHER AND WHIPPER MOTOR  
Location:  
The frothers are located behind the dispenser  
door, mounted on the front of the front panel inside  
the whipper chamber.  
10 9  
8
7 6 5 4 3  
P1206  
FIG. 12 MIXING/WHIPPER CHAMBER  
COMPONENTS  
The whipper motors are located on the back  
side of the front section of the front panel.  
NOTE: The center position is for HC-3 Models only.  
1. Steam Collector  
7. #6-32 Screw  
2. Mixing Chamber  
3. Dispense Tip  
4. Whipper Chamber  
5. O-Ring  
8. Receptical w/Seal  
9. Teflon Washer  
10. O-Ring  
11. #8-32 Acorn Nut  
12. Motor Assy.  
Test Procedure:  
1. Disconnect the dispenser from the power source.  
2. Disconnect the white/violet and white wires on  
the right motor, white/blue and white wires on  
the center motor or the white/red and white wires  
on the left motor from the black leads on the  
motors.  
3. Press and hold the appropriate dispense switch  
and check the voltage across the disconnected  
harness wires with a voltmeter. Connect the dis-  
penser to the power source. The reading must  
be:  
6. Frother  
Removal, Cleaning and Replacement (Refer to Fig. 12):  
1. Open the dispenser door.  
2. Remove the steam collector (1) by pulling it for-  
ward and at the same time twisting it clockwise.  
3. Pull the mixing chamber (2) out of the whipper  
chamber (4).  
27591 031597  
20  
whipper chamber (4). Be sure the cutout part of  
the dispense tip is facing the outside of the dis-  
penser.  
SERVICE (cont.)  
FROTHER AND WHIPPER MOTOR (cont.)  
4. Remove dispense tip (3) and twist the whipper  
chamber (4) clockwise and pull it off the whipper  
chamber receptacle (8).  
5. Pull the frother (6) off the motor shaft. Notice the  
flat side on the shaft and the matching flat inside  
the frother. It is important that these two flats are  
lined up when reassembling.  
23. Slip the mixing chamber (2) onto the mixing  
chamber water inlet tube far enough so the mixing  
chamber (2) will seat inside the whipper chamber  
(4).  
24. Install the steam collector (1) onto the mixing  
chamber (2) by pushing down and toward the  
dispenser while twisting until the flange on the  
steam collector lines-up with the slot in the front  
panel.  
6. Slip the o-ring (5) off the whipper chamber  
receptical (8).  
7. Remove the two #6-32 screws (7) securing whip-  
per chamber receptical (8) to the front panel.  
8. Slide the receptical w/seal off of the motor shaft.  
9. Slide teflon washer (9) and o-ring (10) off of the  
motor shaft.  
10. Disconnect the black leads on the motor (12) from  
the main wiring harness.  
25. Refer to illustration below when reconnecting the  
wires.  
NOTE: To remove the center motor you also have to  
remove the hopper assy., fan and exhaust tube. Refer  
to AUGER DRIVE COMPONENTS and FAN.  
11. Remove the two #8-32 acorn nuts (11) securing  
the motor (12) to the rear of front panel.  
12. Remove motor and discard. See NOTE.  
13. Install new motor (12) on rear of front panel and  
secure with two #8-32 acorn nuts (11) and con-  
nect black leads on the motor to the main wiring  
harness.  
14. Slide o-ring (10) onto the motor shaft to approxi-  
mately 1/8of the front panel.  
15. Wash remaining components in a mild solution of  
dish detergent using a bristle brush.  
16. Rinse thoroughly and allow to dry before reinstall-  
ing in the dispenser.  
17. Place teflon washer into back opening of whipper  
chamberrecepticalandalignonenotchwithbump  
in the opening.  
18. Slide whipper chamber receptacle w/seal on to the  
motorshaftandsecuretothefrontpanelusingtwo  
#6-32 screws (7).  
FIG.13 WHIPPER MOTOR TERMINALS P1207.50  
19. Slipo-ring(5)ontothewhipperchamberreceptical  
(8).  
20. Pushfrother(6)ontothemotorshaft, makingsure  
theflatinthefrother(6)linesupwiththeflatonthe  
motor shaft.  
21. Install whipper chamber (4) on the whipper cham-  
ber receptical (8) by twisting counterclockwise  
untilthetabsonthewhipperchamber(4)lockwith  
the tabs on the whipper chamber receptical (8). Be  
sure dispense port is pointing down.  
22. Install dispense tip (3) into the bottom of the  
27591 031597  
21  
SERVICE (cont.)  
HOPPER DELAY BOARD  
If voltage is not present as described, refer to the wir-  
ing diagram and check the dispenser wiring harness.  
5. Reconnect the white and black wires of the hop-  
per delay board harness to the main harness.  
6. Check the voltage across the terminals on the  
auger motor with a voltmeter. Press and hold the  
appropriate dispense switch. Connect the dis-  
penser to the power source. After a delay of .7  
seconds the indication must be:  
a) 120 volts ac for two wire 120 volt models.  
b) 120 volts ac for three wire 120/208 volt or 120/  
240 volt models.  
c) 240 volts ac for two wire 240 volt models.  
7. Disconnect the dispenser from the power source.  
If voltage is present as described the hopper delay  
board is operating properly.  
If voltage is not present as described, replace the hop-  
per delay board.  
Removal and Replacement:  
1. Disconnect the eight pin plug from the hopper  
delay board.  
2. Remove the two #8-32 keps nuts securing the  
hopper delay board mounting bracket to the dis-  
penser base.  
P1199.45  
3. Remove hopper delay board mounting bracket  
with hopper delay board and shield attached.  
4. Remove the two #8-32 screws securing the hop-  
per delay board to the mounting bracket and dis-  
card the delay board.  
5. Install new delay board on the mounting bracket  
with shield between the bracket and the delay  
board using two #8-32 screws.  
6. Install mounting bracket with hopper delay board  
and shield over the studs on the dispenser base,  
secure with two #8-32 keps nuts.  
7. Reconnect the eight pin connector to the hopper  
delay board.  
FIG. 13 HOPPER DELAY BOARD  
Location  
The hopper delay board is located on the left  
front side of the dispenser base just behind the front  
panel.  
Test Procedures:  
1. Disconnect the dispenser from the power source.  
2. Disconnectthewhiteandblackwiresofthehopper  
delay board harness from the main wiring har-  
ness.  
3. Checkthevoltageacrossthewhiteandblackwires  
of the main wiring harness with a voltmeter. Con-  
nect the dispenser to the power source. The indi-  
cation must be:  
a) 120 volts ac for two wire 120 volt models.  
b) 120 volts ac for three wire 120/208 volt or 120/  
240 volt models.  
c) 240 volts ac for two wire 240 volt models.  
4. Disconnect the dispenser from the power source.  
If voltage is present as described, proceed to #5.  
27591 031597  
22  
4. Disconnect the dispenser from the power source.  
SERVICE (cont.)  
HOT/COLD SWITCH (Optional)  
If voltage is present as described, reconnect the four  
pin plugs and proceed to #5.  
If voltage is not present as described, refer to the  
wiring diagram and check the main wiring harness.  
5. Disconnect the wires from the switch termi-  
nals.  
6. With the switch in the upper Coldposition check  
for continuity between the center terminal and  
the bottom terminal. With the switch in the down  
Hotposition check for continuity between the  
center terminal and the upper terminal.  
If continuity is present as described, the hot/cold  
switch is operating properly.  
If continuity is not present as described, replace the  
switch.  
Removal and Replacement:  
1. Remove all wires from the switch terminals.  
2. Remove the mounting nut on the front of the front  
panel.  
3. Remove the hot/cold switch from the rear of the  
front panel.  
4. Push new hot/cold switch through the hole on  
the left side of the front panel and secure with  
mounting nut.  
5. Reconnect the wires to the terminals on rear of  
the switch.  
6. Refer to the illustration below when reconnect-  
ing the wires.  
P1199.45  
FIG. 14 HOT/COLD SWITCH  
Location:  
The hot/cold switch is located on the left side  
of the front panel.  
Test Procedure:  
WHI/BRN to Main  
Harness  
WHI/RED to Main  
Harness  
WHI/YEL to Cold  
Solenoid  
1. Disconnect the dispenser from the power source.  
2. Disconnect the four pin plug from the hot/cold  
switch and the four pin connector on the main  
wiring harness.  
3. Press the left dispense switch on the door and  
check the voltage across the white wire (P4) and  
white/redwire(P2)inthefourpinconnectoronthe  
main wiring harness with a voltmeter. Connect the  
dispenser to the power source. The indication  
must be:  
P1208  
FIG. 15 HOT/COLD SWITCH TERMINALS  
a) 120 volts ac for two wire 120 volt models.  
b) 120 volts ac for three wire 120/208 volt or 120/  
240 volt models.  
c) 240 volts ac for two wire 240 volt models.  
27591 031597  
23  
If continuity is present as described, lamp holders are  
operating properly.  
If continuity is not present as described replace the  
lamp holder.  
SERVICE (cont.)  
LAMP HOLDER  
1
2
3
Removal and Replacement:  
1. Open dispenser door (1).  
2. Remove the six #8-32 screws securing bottom  
door cover (5) to the door (1) and remove cover.  
3. Disconnect the door wiring harness from the door  
interconnect wiring harness.  
4. Remove eight #8-32 screws securing the upper  
door cover w/reflector (4) to the door.  
5. Remove the upper door cover w/reflector (4),  
lamp (3), lamp holders (2) and door wiring har-  
ness as a assembly.  
4
5
2
6. Rotate lamp (3) 90° and remove from lamp hold-  
ers (2).  
7. Remove the #6-32 securing the lamp holder (2) to  
be removed, remove lamp holder (2) and discard.  
8. Install new lamp holder (2) and secure with a #6-  
32 screw.  
6
9. Install lamp (3) into lamp holders (2) and turn 90°  
until the pins snap in place.  
10. Install upper door cover w/reflector (4), lamp (3),  
lamp holders (2) and door wiring harness as a  
assembly using eight #8-32 screws.  
11. Reconnect the plug on the door wiring harness to  
the connector on the door interconnect wiring  
harness.  
P1209.75  
FIG. 16 LAMP HOLDERS  
1. Door Assy  
2. Lamp Holders  
3. Lamp  
4. Upper Cover W/Reflec-  
tor  
5. Lower Cover  
6. Starter W/Socket  
12. Install the door bottom cover (5) using six #8-32  
screws.  
LAMP REPLACEMENT (Refer to Fig. 16)  
Location:  
1. Open the dispenser door (1).  
The lamp holders are located on the front of  
the reflector behind the display panel.  
2. Remove the upper door cover w/reflector (4),  
lamp (3), lamp holders (2) as an assembly.  
3. Rotate lamp (3) 90° and remove from the lamp  
holders (2).  
4. Insert new lamp (3) into lamp holders (2) and turn  
90° until the pins snap in place.  
5. Reinstall upper door cover w/reflector (4), new  
lamp(3)andlampholders(2)onthedoorassy(1).  
Test Procedure:  
1. Disconnect the dispenser from the power source.  
2. Disconnect the plugs on the door wiring harness  
from the connectors on the lamp holders.  
3. Remove lamp from lamp holders.  
4. Disconnect the two pin plugs of each lamp holder  
from the door wiring harness.  
5. Check for continuity on each lead of the lamp  
holders.  
27591 031597  
24  
hole in the bottom cover (5) and releasing spring  
tabs.  
SERVICE (cont.)  
LAMP STARTER and SOCKET (120V, 120/208V &  
120/240V Models Only)  
8. Insertnewstarter(6)intosocketandturn90° until  
the pins snap in place.  
9. Connect the plug on the sockets leads to the  
connector on the door wiring harness.  
10. Install door bottom cover (5) with starter and  
starter socket on door assy (1) using six #8-32  
screws.  
Location:  
The lamp starter (6) is located inside the door  
assy (1) on the top of the door bottom cover (5).  
Test Procedures:  
1. Disconnect the dispenser from the power source.  
2. Disconnect the plug on the starter leads from the  
connector on the door wiring harness.  
3. Remove lamp starter from starter socket.  
4. Disconnect the two pin plugs of each of the starter  
sockets from the door wiring harness.  
5. Check for continuity on each lead of the starter  
socket.  
If continuity is present as described the starter socket  
is operating properly.  
Ifcontinuityisnotpresentasdescribedreplacethethe  
starter socket.  
6. Remove starter (6) from starter socket.  
7. Checkforcontinuityacrossthepinsonthebottom  
of the starter (6).  
If continuity is present as described , replace the  
starter.  
If continuity is not present as described, starter is  
operating properly.  
Note:Ifcontinuitytestareboth asdescribedandlamp  
does not light, replace the starter socket.  
Removal and Replacement (Refer to Fig.16):  
1. Open dispenser door assy (1)  
2. Remove the six #8-32 screws securing the door  
bottom cover (5) to the door assy (1).  
3. Disconnect the plug on the starter socket and the  
connector on the door wiring harness.  
4. Remove cover (5) with starter w/socket (6) as  
assembly.  
5. Rotate starter 90° and remove from the starter  
socket.  
6. Compress the spring tabs on the socket and re-  
move socket from the door bottom cover (5).  
7. Install new socket by compressing spring tabs on  
the socket and pushing the socket up through the  
27591 031597  
25  
wiringdiagramandcheckthedispenserwiringhaness.  
SERVICE (cont.)  
LEVEL CONTROL BOARD AND LEVEL PROBE  
5. Reconnect the violet wire to terminal 1.  
6. Carefully connect a piece of insulated jumper wire  
to terminal 4. Keep the other end of this wire away  
from any metal surface of the dispenser.  
7. Check the voltage across terminals 1 & 3 with a  
voltmeter. Connect the dispenser to the power  
source.Theindicationmustbe120voltsacfortwo  
wire 120 volt models, three wire 120/208 volt  
models, three wire 120/240 volt models and 240  
volts ac for two wire 240 volt models after a delay  
of approximately 5 seconds.  
8. Touch the free end of jumper wire to the dispenser  
housing. The indication must be 0.  
9. Move the jumper wire away from the dispenser  
housing. Theindicationmustagainbe120voltsac  
for two wire 120 volt models, three wire 120/208  
volt models , three wire 120/240 volt models and  
240 volts ac for two wire 240 volt models after a  
delay of approximately 5 seconds.  
10. Disconnect the dispenser from the power source  
and remove the jumper wire from terminal 4.  
If voltage is present as described, the level control  
board is operating properly, proceed to #11.  
If voltage is not present as described, replace the level  
control board.  
P1203.45  
FIG. 17 LEVEL CONTROL BOARD AND PROBE  
11. Reconnect the pink wire to terminal 4.  
12. Gently pull the probe out of the tank lid and inspect  
for corrosion. Replace it if necessary.  
13. Place the probe so that neither end is in contact  
with any metal surface of the dispenser.  
14. Check the voltage across terminals 1 & 3 with a  
voltmeter. Connect the dispenser to the power  
source.Theindicationmustbe120voltsacfortwo  
wire 120 volt models, three wire 120/208 volt  
models, three wire 120/240 volt models and 240  
volts ac for two wire 240 volt models after a delay  
of approximately 5 seconds.  
15. Move the probe's flat end to the dispenser hous-  
ing. The indication must be 0.  
16. Movetheprobe'sflat endawayfromthedispenser  
housing. The indication should again be 120 volts  
ac for two wire 120 volt models, three wire 120/  
208 volt models, three wire 120/240 volt models  
and 240 volt ac for two wire 240 volt models.  
Location:  
The level control board is located on the upper  
right rear of the front panel just in front of the tank.  
TheLevelprobeislocatedontherightcenterofthe  
tank lid.  
Test Procedure:  
1. Disconnect the dispenser from the power source.  
2. Removethevioletwirefromterminal1&pinkwire  
from terminal 4 of the circuit board.  
3. Check the voltage across terminals 2 & 3 with a  
voltmeter. Connect the dispenser to the power  
source. The indication must be 120 volts ac for  
two wire 120 volt models, three wire 120/208 volt  
models, three wire 120/240 volt models and 240  
volts ac for two wire 240 volt models.  
4. Disconnect the dispenser from the power source.  
If voltage is present as described, proceed to #5.  
If voltage is not present as described, refer to the  
27591 031597  
26  
Location:  
The limit thermostat is located in the center of  
the tank lid.  
SERVICE (cont.)  
LEVEL CONTROL BOARD AND LEVEL PROBE (cont.)  
If voltage is present as described, reinstall the probe,  
the level control board and level probe are operating  
properly.  
If voltage is not present as described, check the pink  
probe wire for continuity.  
Test Procedures:  
1. Disconnect the dispenser from the power source.  
2. Disconnect both black wires from the limit ther-  
mostat.  
3. Check for continuity across the limit thermostat  
terminals.  
Removal and Replacement:  
1. Remove all wires from the level control board.  
2. Removetwo#8-32 kepsnutsholdinglevelcontrol  
board to upper left rear of the front panel.  
3. Remove level control board and spacers.  
3. Install the new level control board and spacers to  
the upper left rear of the front panel using two #8-  
32 keps nuts.  
If continuity is present as described, the limit thermo-  
stat is operating properly.  
If continuity is not present as described, replace the  
limit thermostat.  
Removal and Replacement:  
1. Remove all wires from the limit thermostat ter-  
minals.  
4. Refer to the illustration below when reconnecting  
the wires.  
2. Carefully slide the limit thermostat out from un-  
der the retaining clip and remove the limit ther-  
mostat.  
3. Carefully slide the new limit thermostat into the  
retaining clip.  
4. Refer to the illustration below when reconnect-  
ing the wires.  
BLK to Tank  
Heater  
BLK to Control  
Thermostat  
P1210  
FIG. 18 LEVEL BOARD TERMINALS  
LIMIT THERMOSTAT  
FIG. 20 LIMIT THERMOSTAT TERMINALS P1800  
P1199.45  
FIG. 19 LIMIT THERMOSTAT  
27591 061500  
27  
Removal and Replacement:  
SERVICE (cont.)  
1. Disconnect the red leads from the overflow pro-  
tection switch from the black wire from the termi-  
nal block and the blue wire from the liquid level  
board.  
OVERFLOW PROTECTION SWITCH  
2. Remove the nut beneath the copper overflow cup.  
3. Remove the entire switch assembly from the cup.  
4. Place the new switch assembly into the cup, wires  
first. Make sure that a gasket is in place around the  
threaded switch stem.  
NOTE - The magnets must be at the top of float and  
there must be NO adjusting washers installed for  
the overflow protection switch to operate prop-  
erly.  
5. Installthenutbeneaththecopperoverflowcup. Be  
sure not to overtighten.  
6. Refer to the illustration below when reconnecting  
wires.  
P1199.45  
RED to BLK Wire  
RED to BLU Lead  
from Terminal  
from Liquid Level  
Block  
FIG. 21 OVERFLOW PROTECTION SWITCH  
Location:  
Board  
P1212  
The overflow protection switch is located in-  
side the copper overflow cup on the upper front of  
the tank.  
FIG. 22 OVERFLOW PROTECTION  
SWITCH LEADS  
Test Procedures:  
1. Disconnect the dispenser from the power source.  
2. Remove the wire nuts connecting the red wires  
from the overflow protection switch to the black  
wirefromtheterminalblockandbluewirefromthe  
liquid level board.  
3. Check for continuity across the safety overflow  
switchredwiresonlyuntiltheplasticfloatisraised  
and check that continuity returns when the plastic  
float is again lowered.  
If continuity is present as described, reconnect the  
red wires to the black wire from the terminal block  
and the blue wire from the liquid level board.  
If continuity is not present as described, replace the  
overflow protection switch.  
27591 111596  
28  
3. Remove switch with wires attached from the back  
side of the front panel.  
4. Disconnect the wires from the switch and dis-  
card the switch.  
SERVICE (cont.)  
RUN/RINSE SWITCH  
5. Referring to the illustration below (Fig. 24) re-  
connect the wires to the new switch.  
6. Install new switch with wires attached through  
the hole in the front panel and secure with facenut.  
P1213  
FIG. 24 RUN/RINSE SWITCH TERMINALS  
P1199.45  
FIG. 23 RUN/RINSE SWITCH  
Location:  
The run/rinse switch is located on the right  
side of the front panel.  
Test Procedures:  
1. Disconnect the dispenser from the power source.  
2. Check for continuity between center terminals and  
the upper terminals with the switch in the RUN”  
lower position. Continuity must not be present  
with the switch in the RINSEupper position.  
If continuity is present as described, the switch is  
operating properly.  
If continuity is not present as described, replace the  
switch.  
Removal and Replacement:  
1. Open the dispenser door.  
2. Remove the facenut securing the run/rinse switch  
to the dispenser front panel.  
27591 111596  
29  
If voltage is not present as described, refer to wiring  
diagram and check dispenser wiring harness.  
SERVICE (cont.)  
SOLENOID VALVE (COLD WATER - OPTIONAL)  
5. Check for continuity across the solenoid valve  
coil terminals.  
If continuity is present as described, reconnect the  
white and white/yellow wires to the solenoid.  
If continuity is not present as described, replace the  
solenoid valve.  
6. Check the solenoid valve for coil action. Connect  
the brewer to the power source. With "HOT/COLD"  
switch in the "COLD" upper position press the left  
dispense switch and listen carefully in the vicin-  
ity of the solenoid valve for a "clicking" sound as  
the coil magnet attracts.  
7. Disconnect the dispenser from the power source.  
If the sound is heard as described and water will not  
pass through the solenoid valve, there may be a block-  
age in the water line before the solenoid valve or, the  
solenoid valve may require inspection for wear, and  
removal of waterborne particles.  
If the sound is not heard as described, replace the  
solenoid valve.  
FIG. 25 COLD WATER SOLENOID VALVEP1214.45  
Location:  
Removal and Replacement:  
1. Remove the white and white/yellow wires from  
the solenoid valve.  
2. Turn-off the water supply to the dispenser.  
3. Disconnect the water lines to and from the sole-  
noid valve.  
The cold water solenoid valve is located on  
the left side of the dispenser base just behind the hop-  
per delay board.  
4. Remove the two #8-32 keps nuts and washers  
securing the solenoid mounting bracket to the  
base. Remove solenoid bracket and solenoid  
valve as an assembly.  
5. Remove the two #10-32 screws and lockwashers  
securing the solenoid valve to the solenoid  
bracket.  
6. Using two #10-32 screws and lockwashers in-  
stall new solenoid valve on solenoid mounting  
bracket.  
7. Using two #8-32 keps nuts and washers install  
solenoid valve and bracket to the base of the dis-  
penser.  
Test Procedures:  
1. Disconnectthedispenserfromthepowersource.  
2. Disconnect the white and white/yellow wires  
from the solenoid valve. With the HOT/COLD”  
switchinthe"COLD"upperpositionpressthe left  
dispense switch on front of the door.  
3. Check the voltage across the white and white/  
yellow wires with a voltmeter. Connect the dis-  
penser to the power source. The indication must  
be 120 volts ac for two wire 120 volt models,  
threewire120/208,120/240voltmodelsand240  
volts ac for two wire 240 volt models.  
4. Disconnect the brewer from the power source,  
8. Securely fasten the water lines to and from the  
solenoid valve.  
If voltage is present as described, proceed to #5  
9. Refer to Fig. 26 when reconnecting the wires.  
27591 031597  
30  
Test Procedures:  
SERVICE (cont.)  
1. Disconnectthedispenserfromthepowersource.  
2. Disconnectthewhiteandwhite/violet, white/blue  
or white/ brown wires from the solenoid valve.  
With the RUN/RINSEswitch in the "RINSE"  
upper position press the appropriate dispense  
switch on front of the door.  
SOLENOID VALVE (COLD WATER - OPTIONAL) (cont.)  
WHI/YEL to Hot/Cold  
Switch  
WHI to Terminal Block  
3. Check the voltage across the white and white/  
violet, white/blue or white/brown wires with a  
voltmeter. Connect the dispenser to the power  
source. The indication must be 120 volts ac for  
two wire 120 volt models, three wire 120/208,  
120/240 volt models and 240 volts ac for two  
wire 240 volt models.  
P1215  
FIG. 26 COLD WATER SOLENOID TERMINALS  
4. Disconnectthedispenserfromthepowersource,  
SOLENOID VALVES (DISPENSE)  
If voltage is present as described, proceed to #5  
If voltage is not present as described, refer to wiring  
diagram and check dispenser wiring harness.  
5. Check for continuity across the solenoid valve  
coil terminals.  
If continuity is present as described, reconnect the  
white and white/violet, white/blue or white/brown  
wires to the solenoid.  
If continuity is not present as described, replace the  
solenoid valve.  
6. Check the solenoid valve for coil action. Connect  
the dispenser to the power source. With "RUN/  
RINSE" switch in the "RINSE" upper position press  
the appropriate dispense switch and listen care-  
fully in the vicinity of the solenoid valve for a "click-  
ing" sound as the coil magnet attracts.  
7. Disconnect the dispenser from the power source.  
If the sound is heard as described and water will not  
pass through the solenoid valve, there may be a block-  
age in the water outlet before the solenoid valve or,  
the solenoid valve may require inspection for wear,  
and removal of waterborne particles.  
P1203.45  
FIG. 27 DISPENSE SOLENOID VALVES  
If the sound is not heard as described, replace the  
solenoid valve.  
Location:  
The dispense solenoids are located on the  
upper right side of the tank.  
Removal and Replacement:  
1. Remove the white and white/violet, white/blue or  
white/ brown wires from the solenoid valve.  
2. Turn-off the water supply to the dispenser.  
27591 031597  
31  
SOLENOID VALVE (INLET)  
SERVICE (cont.)  
SOLENOID VALVES (DISPENSE) (cont.)  
3. Drain enough water from the tank so the water  
level is below the dispense valve mounting hole.  
NOTE: Bunn-O-Matic has a syphon assembly,  
#12440.0000. available for this purpose.  
4. Disconnect the water line from the solenoid valve.  
5. Remove the #10-32 screw securing the solenoid  
valve to side of the tank. Remove solenoid valve.  
6. Usingthe #10-32screwinstallnewsolenoidvalve  
on side of the tank  
7. Push the water line onto the tube on bottom of  
solenoid valve.  
8. Refer to Fig. 26 when reconnecting the wires.  
P1203.45  
FIG. 27 INLET SOLENOID VALVE  
Location:  
The inlet solenoid is located on the lower right  
side of the rear panel.  
Test Procedures:  
1. Disconnectthedispenser fromthepowersource.  
2. Disconnect the white and violet wires from the  
solenoid valve.  
3. Check the voltage across the white and violet  
wires with a voltmeter. Connect the dispenser to  
the power source. The indication must be 120  
volts ac for two wire 120 volt models, three wire  
120/208, 120/240 volt models and 240 volts ac  
for two wire 240 volt models.  
P1216  
FIG. 26 DISPENSE SOLENOID VALVE  
TERMINALS  
4. Disconnectthedispenserfromthepowersource,  
If voltage is present as described, proceed to #5  
If voltage is not present as described, refer to the  
wiring diagram and check dispenser wiring harness.  
5. Check for continuity across the solenoid valve  
coil terminals.  
If continuity is present as described, reconnect the  
white and violet wires to the solenoid.  
27591 031597  
32  
TANK HEATER  
SERVICE (cont.)  
SOLENOID VALVE (INLET) (cont.)  
If continuity is not present as described, replace the  
solenoid valve.  
6. Check the solenoid valve for coil action. Connect  
the dispenser to the power source. Listen care-  
fully in the vicinity of the solenoid valve for a  
"clicking" sound as the coil magnet attracts.  
7. Disconnect the dispenser from the power source.  
If the sound is heard as described and water will not  
pass through the solenoid valve, there may be a block-  
age in the water line before the solenoid valve or, the  
solenoid valve may require inspection for wear, and  
removal of waterborne particles.  
If the sound is not heard as described, replace the  
solenoid valve.  
Removal and Replacement:  
1. Remove the white and violet wires from the so-  
lenoid valve.  
2. Turn-off the water supply to the dispenser.  
3. Disconnect the water lines to and from the sole-  
noid valve.  
P1199.40  
FIG. 29 TANK HEATER  
Location:  
4. Remove the two #10-32 screws and nuts secur-  
ing the solenoid to the rear panel. Remove sole-  
noid.  
The tank heater is located inside the tank and  
secured to the tank lid.  
5. Using two #10-32 screws and nuts install new  
solenoid valve on rear panel.  
6. Securely fasten the water lines to and from the  
solenoid valve.  
Test Procedure:  
1. Disconnect the dispenser from the power source.  
2. Checkthevoltageacrosstheblackandwhitewires  
120voltmodelsorblackandredwiresfor120/208  
volt modelsor120/240voltmodelswithavoltme-  
ter. Connect the dispenser to the power source.  
The indication must be:  
7. Refer to Fig. 28 when reconnecting the wires.  
a) 120 volts ac for two wire 120 volt models;  
b) 208 volts ac for three wire 120/208 volt models.  
c) 240 volts ac for three wire 120/240 volt models  
and two wire 240 volt models.  
3. Disconnect the dispenser from the power source.  
WHI from Terminal  
Block  
If voltage is present as described, proceed to #4.  
If voltage is not present as described, refer to the  
dispenser wiring diagram and check the wiring har-  
ness.  
VIO from Liquid  
Level Board  
P1217  
FIG. 28 INLET SOLENOID VALVE TERMINALS  
4. Disconnect the black wire and the white or red  
wire from the tank heater terminals.  
27591 031597  
33  
SERVICE (cont.)  
TANK HEATER (cont.)  
WHI or RED to  
Terminal Block  
BLK to Limit  
Thermostat  
5. Check for continuity across the tank heater termi-  
nals.  
If continuity is present as described, reconnect the  
wires, the tank heater is operating properly.  
If continuity is not present as described, replace the  
tank heater.  
NOTE - If the tank heater remains unable to heat,  
remove and inspect heater for cracks in the sheath.  
Removal and Replacement:  
1. Shut-off water supply to the dispenser.  
2. Disconnect the water supply tube on the tank lid.  
3. Disconnect the black wires on the limit thermo-  
stat.  
4. Disconnecttheblackwireandthewhiteorredwire  
from the tank heater terminals.  
5. Disconnect the pink wire from the liquid level  
probe.  
6. Remove the thermostat capillary bulb by firmly  
pulling-up on the capillary at the tank lid. This will  
disengage the grommet from the tank lid.  
7. Remove the ten #8-32 nuts securing the tank lid to  
the tank.  
P1218  
FIG. 30 TANK HEATER TERMINALS  
TANK HEATER SWITCH  
8. Remove tank lid with limit thermostat, liquid level  
probe and tank heater as a assembly.  
9. Remove the two hex nuts securing the tank heater  
to the tank lid. Remove tank heater with gaskets  
and discard.  
10. Install new tank heater with gaskets on the tank lid  
and secure with two hex nuts.  
11. Install tank lid with limit thermostat, liquid level  
probe and tank heater on the tank and secure with  
ten #8-32 hex nuts.  
12. Connect water inlet line to the tank lid.  
13. Reconnect the black wires to limit thermostat, the  
pinkwiretotheliquidlevelprobe. Refertothelimit  
thermostat and the liquid level board and probe  
sections in this manual when reconnecting wires.  
14. RefertoFig. 30whenreconnectingthewirestothe  
tank heater.  
P1199.35  
FIG. 31 TANK HEATER SWITCH  
Location:  
The tank heater switch located inside the dis-  
penser on the upper right of the front panel.  
27591 031597  
34  
TRANSFORMER (240V TWO WIRE MODELS ONLY)  
SERVICE (cont.)  
TANK HEATER SWITCH (cont.)  
Test Procedure:  
1. Disconnect the dispenser from the power source.  
2. Disconnect the black wire and the blue/black wire  
onelectro/mechanicalthermostatsorthetanwires  
on electronic thermostats.  
3. With the switch in the ONlower position check  
for continuity between the center and the upper  
terminal. With the switch in the OFFupper posi-  
tion no continuity should be present between  
center and upper terminals.  
1
2
3
If continuity is present as described, the heater ON/  
OFFswitch is operating properly.  
If continuity is not present as described, replace the  
switch.  
P1289  
FIG. 33 TRANSFORMER  
Location:  
The transformer is located behind the front  
cover just to the right of the ballest on the dispenser  
base.  
Removal and Replacement:  
1. Remove the switch mounting nut on the front of  
the front panel.  
2. Remove switch with wires attached from the rear  
of the front panel.  
3. Remove the wires from the switch terminals and  
discard switch.  
4. Connect the wires to the new switch, refer to fig.  
32.  
5. Push new switch through hole in the front panel  
and secure with face nut.  
Test Procedure:  
1. Disconnect the dispenser from the power source.  
2. Disconnect the two pin connector of the trans-  
former from the fan.  
3. Connect voltmeter, set to read at least 120 volts ac  
across the black and white leads of the trans-  
former connector.  
4. Connect the dispenser to the power source. The  
voltage indication should be approximately 120  
volts ac.  
BLUBLK from Electro/  
mechanical Thermostat  
or TAN from Electronic  
Thermostat  
5. Disconnect the dispenser from the power source.  
If voltage is present as described the transformer is  
operating properly.  
If voltage is not present as described, replace the  
transformer.  
BLK from Terminal  
Block (Electro/mechani-  
cal)  
TAN from Electronic  
Thermostat  
FIG. 32 TANK HEATER SWITCH TERMINALSP1219  
27591 031597  
35  
SERVICE (cont.)  
TRANSFORMER (240V TWO WIRE  
MODELSONLY)(cont.)  
Removal and Replacement:  
1. Disconnect the wires from the transformer.  
2. Remove the two #8-32 keps nuts securing the  
transformer to the dispenser base.  
3. Remove and discard the transformer.  
4. Installnewtransformeroverthetwoweldstudson  
the dispenser base and secure with two #8-32  
keps nuts.  
5. Refer to Fig. 34 when renonnecting the wires.  
RED & BLK to  
Main Harness  
1
2
3
BLK & WHI to  
Fan  
P1288  
FIG.34 TRANSFORMER TERMINALS  
27591 031597  
36  
SCHEMATIC WIRING DIAGRAM HC-2, & HC-3  
GRN  
L2 N  
L1  
ELECTROMECHANICAL THERMOSTAT CONFIGURATION  
HEATER SW.  
BLU/BLK-16  
BLK-16  
LIMIT  
RED-16 (3-WIRE MODELS)  
WHI-16 (2-WIRE MODELS)  
THERMOSTAT  
THERMOSTAT  
TANK HEATER  
TANK HEATER  
BLU-16  
BLK-16  
BLK-16  
BLK-16  
BLK-16  
BLK-16  
ELECTRONIC THERMOSTAT CONFIGURATION  
HEATER SW.  
TAN  
TAN  
LIMIT  
THERMOSTAT  
RED-16 (3-WIRE MODELS)  
WHI-16 (2-WIRE MODELS)  
BLK-16  
BLK-16  
ELECTRONIC  
THERMOSTAT  
ASSEMBLY  
WHI  
OVERFLOW SWITCH  
TANK INLET  
SOL  
BLK  
BLK  
BLK  
RED  
RED  
VIO  
WHI  
WHI  
WHI/VIO  
WHI/BLU  
1
1
2
3
4
HOPPER  
DELAY  
LIQUID  
LEVEL  
BOARD  
BLU  
2
3
4
5
6
7
8
PNK-20  
BLK  
BLK  
WHI  
BLK  
WHI/RED  
WHI/GRN  
WHI/GRN  
WHI  
PROBE  
FLOURESCENT  
LAMP  
BALLAST  
1
BLK  
BLK BLK  
WHI  
WHI  
WHI  
BLU  
WHI  
WHI  
WHI  
WHI  
DISPENSE  
WHIPPER  
M
HOPPER  
WHI/RED  
WHI  
WHI/RED  
WHI  
WHI/RED  
WHI/BLK  
M
SOL  
RUN/RINSE SWITCH  
WHI/GRN  
WHI  
WHI  
WHI  
RIGHT DISPENSE  
RIGHT WHIPPER  
RIGHT HOPPER  
WHI/VIO  
WHI/VIO  
CENTER DISPENSE  
WHI/BLU WHI  
WHI/BLU  
LEFT DISPENSE  
WHI  
WHI/VIO  
WHI  
WHI/VIO  
WHI/BLK  
M
SOL  
M
WHI/VIO  
WHI/BLU  
CENTER WHIPPER  
CENTER HOPPER  
WHI/BLU  
WHI  
WHI/BLU  
WHI/BLK  
SOL  
M
M
LEFT WHIPPER  
LEFT HOPPER  
WHI/BRN  
WHI  
WHI/RED  
WHI  
WHI/RED  
WHI/BLK  
SOL  
M
M
RUN/RINSE SWITCH  
WHI/GRN  
WHI/BLK  
COLD DRINK OPTION (LEFT ONLY)  
WHI  
WHI/GRN  
WHI  
4
1
SOL  
WHI/BRN  
WHI/RED  
WHI/RED  
WHI/BRN  
WHI/RED  
WHI/RED  
JUMPER PLUG MUST BE  
USED WHEN COLD  
DRINK FEATURE NOT  
INSTALLED  
RED  
RED  
RED  
WHI/YEL  
HOT/COLD SWITCH  
1
1
4
GRN/WHI  
GRN/BLK  
1
WHI  
BLK  
BLU  
BLU  
1
BLK  
BLK  
RED  
BLK  
STARTER  
RED/WHI  
RED/BLK  
1
RED  
BLK  
WHI  
1
DISPENSE  
SWITCH  
ASSY.  
DISPENSE SWITCH  
(RIGHT, MODELS HC-2 & HC-3)  
BLK  
1
RED/BLK  
4
1
BLK  
RED  
4
DISPENSE SWITCH  
(CENTER, MODEL HC-3 ONLY)  
BLK  
RED/WHI  
4
1
120 VOLTS AC - 2 WIRE OR  
120/208-240 VOLTS AC - 3 WIRE  
SINGLE PHASE, 60 HZ  
DISPENSE SWITCH  
(LEFT, MODELS HC-2 & HC-3)  
(ALSO HC-1 SWITCH)  
BLK  
RED  
4
27591 031597  
37  
SCHEMATIC WIRING DIAGRAM HCA-2, & HCA-3  
GRN  
L1  
L2  
ELECTROMECHANICAL THERMOSTAT CONFIGURATION  
HEATER SW.  
BLU/BLK-16  
BLK-16  
LIMIT  
THERMOSTAT  
THERMOSTAT  
TANK HEATER  
BLU-16  
BLK-16  
BLK-16  
BLK-16  
BLK-16  
WHI -16  
ELECTRONIC THERMOSTAT CONFIGURATION  
HEATER SW.  
TAN  
TAN  
LIMIT  
THERMOSTAT  
TANK HEATER  
RED  
BLK-16  
BLK-16  
BLK-16  
BLK  
WHI -16  
WHI  
ELECTRONIC  
THERMOSTAT  
ASSEMBLY  
OVERFLOW SWITCH  
BLK  
RED  
TANK INLET  
WHI/VIO  
WHI/BLU  
1
HOPPER  
VIO  
WHI  
WHI  
2
3
4
5
6
7
8
SOL  
DELAY  
1
2
3
4
LIQUID  
LEVEL  
BOARD  
BLU  
BLK  
BLK  
WHI  
BLK  
WHI/RED  
WHI/GRN  
WHI/GRN  
WHI  
PNK-20  
PROBE  
BLK  
1
RED  
RED  
BLU  
BLU  
BLK  
WHI  
BLK  
WHI  
BLK  
RED  
XFRMR BLK  
WHI  
FLOURESCENT  
LAMP  
BALLAST  
1
WHI  
WHI  
WHI  
WHI  
WHI  
WHI/RED  
DISPENSE  
SOL  
WHIPPER  
HOPPER  
WHI/BLK  
M
WHI/RED  
WHI  
WHI  
WHI/RED  
M
RUN/RINSE SWITCH  
WHI/GRN  
WHI  
WHI  
WHI/VIO  
WHI  
RIGHT DISPENSE  
RIGHT WHIPPER  
RIGHT HOPPER  
WHI/VIO  
WHI/VIO  
WHI  
WHI  
WHI/VIO  
WHI/BLK  
M
SOL  
M
WHI/VIO  
WHI/BLU  
CENTER DISPENSE  
WHI/BLU WHI  
WHI/BLU  
LEFT DISPENSE  
WHI/BRN WHI  
CENTER WHIPPER  
CENTER HOPPER  
WHI/BLU  
WHI  
WHI/BLU  
WHI/BLK  
SOL  
M
M
LEFT WHIPPER  
LEFT HOPPER  
WHI/RED  
WHI  
WHI/RED  
WHI/BLK  
SOL  
M
M
RUN/RINSE SWITCH  
WHI/GRN  
WHI/BLK  
COLD DRINK OPTION (LEFT ONLY)  
WHI  
WHI/GRN  
WHI  
4
1
SOL  
WHI/BRN  
WHI/RED  
WHI/RED  
WHI/BRN  
WHI/RED  
WHI/RED  
JUMPER PLUG MUST BE  
USED WHEN COLD  
DRINK FEATURE NOT  
INSTALLED  
RED  
RED  
RED  
WHI/YEL  
HOT/COLD SWITCH  
1
4
1
4
4
1
BLU  
BLU  
RED  
RED  
WHI  
BLK  
BLU/BLK  
BLU  
1
1
ORA/BLK  
ORA  
RED  
BLK  
RED/WHI  
RED/BLK  
DISPENSE  
SWITCH  
ASSY.  
BLK  
WHI  
1
DISPENSE SWITCH  
(RIGHT, MODELS HC-2 & HC-3)  
1
4
BLK  
RED/BLK  
BLK  
RED  
4
1
DISPENSE SWITCH  
(CENTER, MODEL HC-3 ONLY)  
BLK  
RED/WHI  
4
240 VOLTS A C  
2 WIRE  
SINGLE PHASE,  
50 HZ  
1
DISPENSE SWITCH  
(LEFT, MODELS HC-2 & HC-3)  
(ALSO HC-1 SWITCH)  
BLK  
RED  
4
27593.0004B 2/97  
©
1996 BUNN-O-MATC CORPORATION  
27591 031597  
38  

National Instruments 9211 User Manual
MTD 247 465A000 User Manual
Motorola TIMEPORT VTM 280 User Manual
Memorex MPD8507 User Manual
LG Electronics LG Lifes Good Cell Phone 501C User Manual
LG Electronics Fone SD7130 User Manual
Kyocera 5135 User Manual
HHB comm PERSONAL COMPACT DISC RECORDER CDR 830 User Manual
Harbor Freight Tools 92281 User Manual
Curtis CR4975 User Manual