88
Water & steam boilers – Series 2
for use with Gas, Light Oil, & Gas/Light Oil – Fired Burners
• Maintenance
• Parts
• Installation
• Startup
Boiler Manual
For additional
information, refer to . .
Burner
specification and
data sheets
for burners pre-tested
with model 88 boilers
This manual must only be used by a qualified INSTALLER Consider piping and installation when determining
heating installer/service technician. Read all
instructions before installing. Follow all in-
structions in proper order. Failure to comply
could result in severe personal injury, death
or substantial property damage.
boiler location.
Any claims for damage or shortage in shipment must be
filed immediately against the transportation company
by the consignee.
USER . . . . This manual is for use only by your qualified heating
installer/service technician. Boiler and burner must be
installed by a qualified service technician. We recom-
mend regular service by a qualified service technician,
at least annually.
When calling or writing about the boiler—
Please have the boiler model number from the
boiler rating label and the CP number from
the boiler jacket.
Part No. 550-100-068/0308
Boiler manual:
• Installation • Start-Up • Maintenance • Parts
Contents
Before installing boiler 4
Set boiler in place 7
Assembling the block 8
Perform hydrostatic pressure test 11
Complete block assembly 12
Connect water boiler piping 14
Connect steam boiler piping 16
Install jacket 20
Pipe tankless heaters 25
Install water boiler controls 26
Install steam boiler controls 27
Connect breeching and venting systems 29
Install burner & wiring and fill system 31
Install fuel piping 32
Make final adjustments 33
Handling ceramic fiber and fiberglass materials 34
Ratings 35
Dimensions 36
Parts 38
Warranty 40
Part No. 550-100-068/0308
3
Weil-McLain 88 Water and steam boilers — Series 2 — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
Before installing boiler
Installation must comply with —
Figure 1 Boiler foundation, when required
1. State, provincial and local plumbing, heating and electrical
codes.
2. Regulations of servicing utilities.
3. ASME Section IV, Low Pressure Boiler and Pressure Vessel Code.
4. National Fuel Gas Code, ANSI/NFPA 54, when applicable.
5. National codes where applicable.
Before selecting boiler location
1. Check for nearby connections to:
a. Fuel supply.
b. Electrical power.
c. System water or steam piping.
d. Venting systems - see page 29.
e. Combustion and ventilation air supply — see page 5.
2. Check area around boiler. Remove any combustible materials,
gasoline and other ammable vapors and liquids.
Failure to keep boiler area clear and free of combustible
materials, gasoline and other ammable liquids and
vapors can result in severe personal injury, death and
substantial property damage.
Figure 2 Boiler foundation (see Figure 1)
Boiler model
Length, L, minimum
Provide clearance around boiler
number
(inches)
1. Provide minimum clearances to combustible materials:
•
•
•
•
•
•
•
Boiler top — 24 inches.
Boiler front — 48 inches.
Boiler flue — 9 inches.
Boiler rear — 9 inches.
488
588
33
41
688
49
Boiler sides — 6 inches.
788
57
Single-wall vent pipe – 18 inches.
Double-wall vent pipe – refer to vent pipe manufacturer's
recommendations for vent pipe clearances.
888
65
2. Boiler may be installed on combustible ooring.
3. See page 36 for boiler dimensions.
988
73
1088
1188
1288
1388
1488
1588
1688
1788
1888
81
Flue pipe/breeching clearances take precedence over
jacket clearances.
89
97
4. Provide minimum clearances for servicing:
•
Left side — for cleaning and tankless heater removal –
39 inches.
105
113
121
129
137
145
•
•
Rear — for breeching — 36 inches.
Allow sufficient space on remaining sides for cleaning,servicing
and burner installation. See burner literature for length and
recommended service clearances.
Lay a foundation, if needed
1. Floor construction and condition must be suitable for weight of
boiler when filled with water. See page 36 for approximate boiler
operating weight.
2. A level concrete or brick foundation, constructed per Figure 1 and
Figure 2 is required when:
a. A oor could possibly become ooded.
b. Non-level conditions exist.
4
Part No. 550-100-068/0308
Boiler manual:
• Installation • Start-Up • Maintenance • Parts
(continued)
Before installing boiler
Combustion and ventilation air openings
Figure 3 Combustion and ventilation air openings
— Boiler room below grade
Adequate combustion and ventilation air must be
provided to assure proper combustion and prevent
possibility of ue gas leakage and carbon monoxide
emissions, causing severe personal injury or death.
Do not install an exhaust fan in boiler room. Incor-
rect burner operation can result.
When combustion and ventilation air enters
through side wall openings, ensure that the open-
ings comply with the requirements of Figure 3 and
Figure 4.
Opening sizes must comply with state, provincial or
local codes. In the absence of local requirements, use
the National Fuel Gas Code, ANSI/NFPA 54). The
following information is taken from ANSI/NFPA 54.
For details and information not addressed below,
refer to the standard.
Figure 4 Combustion and ventilation air openings
— Boiler room partially or completely
above grade
Combustion air openings to inside
Required volume of interior spaces
ANSI/NFPA 54 allows combustion air to be supplied through openings
to interior spaces if the volume of the connected interior spaces
meets the minimum volume required by the standard.
The minimum volume of interior spaces can be taken as 50 cubic feet
per 1,000 Btuh of all appliances in the spaces, or the minimum volume
can be calculated using the formulas given in ANSI/NFPA 54. Excep-
tion: If the air infiltration rate for the spaces is known to be less than
0.40 air changes per hour, the minimum volume must be calculated
as specified in the standard.
Inside air opening sizes and locations
For spaces that provide the minimum volume required by ANSI/
NFPA 54, the air openings must be sized per the following:
Combustion air openings to
outside
Outdoor combustion air can be taken through per-
manent openings (TWO or ONE), as described in the
following. The minimum dimension of air openings
shall not be less than 3 inches (80 mm).
Combining spaces on the same story — Each opening shall have
a minimum free area of 1 in2/1000 Btuh (2200 mm2/kW) of the total
input rating of all appliances in the space but not less than 100 in2
(0.06 m2). One opening shall commence within 12 inches (300 mm)
of the top, and one opening shall commence within 12 inches (300
mm) of the bottom, of the enclosure. The minimum dimension of air
openings shall be not less than 3 inches (80 mm).
Outside openings: TWO permanent openings
method
Combining spaces in different stories — The volumes of spaces
in different stories shall be considered as communicating spaces where
such spaces are connected by one or more openings in doors or oors
having a total minimum free area of 2 in2/1000 Btuh (4400 mm2/kW)
of total input rating of all appliances.
Two permanent openings, one commencing within
12 inches (300 mm) of the top and one commencing
within 12 inches (300 mm) of the bottom of the enclo-
sure shall be provided.The openings shall communicate
directly, or by ducts, with the outdoors or spaces that
Part No. 550-100-068/0308
5
Weil-McLain 88 Water and steam boilers — Series 2 — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
(continued)
Before installing boiler
freely communicate with the outdoors, as follows:
system, the combustion air shall be supplied from
outdoors at the minimum rate of 0.35 ft3/minute per
1000 Btuh (0.034 m3/min per kW) for all appliances
located within the space.
•
Where directly communicating with the outdoors or where
communicating to the outdoors through vertical ducts, each
opening shall have a minimum free area of 1 in2/4000 Btuh
(550 mm2/kW) of total input rating of all appliances in the
enclosure.
•
Where exhaust fans are installed in the building,
additional air shall be provided to replace the
exhausted air.
•
Where communicating with the outdoors through horizon-
tal ducts, each opening shall have a minimum free area of
1 in2/2000 Btuh (1100 mm2/kW) of total input rating of all
appliances in the enclosure.
•
Each of the appliances served shall be inter-
locked to the mechanical air supply system to
prevent main burner operation where the me-
chanical air supply system is not in operation.
Outside openings: ONE permanent opening method
•
Where combustion air is provided by the build-
ing’s mechanical ventilation system, the system
shall provide the specified combustion air rate
in addition to the required ventilation air.
One permanent opening, commencing within 12 inches (300 mm)
of the top of the enclosure, shall be provided. The appliance shall
have clearances of at least 1 in. (25 mm) from the sides and back
and 6 inches (150 mm) from the front of the appliance. The opening
shall directly communicate with the outdoors or shall communicate
through a vertical or horizontal duct to the outdoors or spaces that
freely communicate with the outdoors and shall have a minimum free
area of the following:
Louvers, Grilles, and Screens.
The required size of openings for combustion, venti-
lation, and dilution air shall be based on the net free
area of each opening.
(1) 1 in2/3000 Btu/hr (700 mm2 per kW) of the total input rating of
all appliances located in the enclosure, and . . .
Where the free area through a design of louver or grille
or screen is known,it shall be used in calculating the size
opening required to provide the free area specified.
(2) Not less than the sum of the areas of all vent connectors in the
space.
Where the louver and grille design and free area are not
known, it shall be assumed that wood louvers will have
25 percent free area, and metal louvers and grilles will
have 75 percent free area.
Combustion air — combination indoor and
outdoor openings
ANSI/NFPA 54 allows combustion air to be taken from a combination
of openings to outside and to interior spaces. Follow all requirements
of the standard to determine the minimum volume of interior spaces
and to calculate minimum sizes of openings.
Non-motorized louvers and grilles shall be fixed in the
open position.
Minimum screen mesh size
Screens shall not be smaller than ¼ inch mesh.
Engineered Installations
Motorized louvers
Engineered combustion air installations shall provide an adequate sup-
ply of combustion, ventilation, and dilution air and shall he approved
by the authority having jurisdiction.
Motorized louvers shall be interlocked with the appli-
ance so they are proven in the full open position prior
to main burner ignition and during main burner opera-
tion. Means shall be proved to prevent the main burner
from igniting should the louver fail to open during
burner startup, and to shut down the main burner if
the louvers close during burner operation.
Mechanical Combustion Air Supply
Where all combustion air is provided by a mechanical air supply
6
Part No. 550-100-068/0308
Boiler manual:
• Installation • Start-Up • Maintenance • Parts
Set boiler in place
Ensure the equipment and cables used for lifting are
Figure 5 Section assembly lifting weights
designed to handle the load. See Figure 5 for approximate
weights of model 88 section assemblies.Failure to comply
can result in severe personal injury, death or substantial
property damage.
Boiler
model
Approximate
lifting
Minimum
sling length —
number
weight
(from crane hook to
boiler lifting lugs)
(pounds)
For packaged boiler:
1. Remove top jacket panels. Set aside until after boiler is piped.
488
588
2928
3490
4152
4714
5276
5838
6400
7062
7624
8186
8748
9310
9872
10,584
11,146
2' 6"
3' 0"
4' 0"
4' 6"
5' 0"
6' 0"
6' 6"
7' 0"
8' 0"
8' 6"
9' 0"
10' 0"
10' 6"
11' 0"
12' 0"
The boiler contains ceramic fiber and fiberglass materials.
Use care when handling these materials per instructions
on "Handling ceramic fiber and fiberglass materials,"
page 34 of this manual. Failure to comply could result
in severe personal injury.
688
788
888
2. Remove lag screws (2 in front, 2 in rear) from shipping rails.
988
3. Remove boiler from skid. Cables are already attached to block as-
sembly. See Figure 5 for lifting weight.
1088
1188
1288
1388
1488
1588
1688
1788
1888
•
•
Using crane — hook middle of each cable to eye of crane.
Using hoist — hook middle of each cable to hoist. Raise boiler
off skid. Use pipe rollers under skid angles to roll boiler.
4. Place boiler in final position. Center boiler on foundation, if
used.
5. Level boiler. Shim under skid angles, if necessary.
6. Cut off cables.
Cables are not intended for long-term usage. Cables may
corrode inside boiler, weakening their lifting strength.
Failure to remove cables can result in severe personal
injury, death or substantial property damage.
7. Proceed to "Perform hydrostatic pressure test," page 11.
For block assembly:
1. Remove lag screws (2 in front, 2 in rear) from shipping rails.
Gas tight seal must be maintained to pre-
vent possible ue gas leakage and carbon
monoxide emissions, resulting in severe
personal injury or death.
2. Remove boiler from skid. Cables are already attached to block as-
sembly. See Figure 5 for lifting weight.
a. Check inside section assembly for any light
passing through unsealed areas.
b. Mark all unsealed areas.
•
•
Using crane – attach free end of cables to eye of crane.
Using hoist – attach free end of cables to hoist. Raise boiler off skid.
Use pipe rollers under steel skid angles to roll boiler.
c. At unsealed areas, check for:
3. Place boiler in final position. Center boiler on foundation, if
used.
•
•
•
Damaged gaskets.
4. Level boiler. Shim under skid angles, if necessary.
5. Cut off cables.
Sealing rope not in place.
Loose bolts or nuts.
Cables are not intended for long-term usage. Cables may
corrode inside boiler, weakening their lifting strength.
Failure to remove cables can result in severe personal
injury, death or substantial property damage.
d. Correct all conditions and repeat step b. If un-
sealed areas still exist,contact yourWeil-McLain
distributor or sales office before continuing
installation.
6. Inspect block assembly for disjointed sections. Check gas-tight seal
of ue collector hood and cleanout plates.
7. Proceed to "Perform hydrostatic pressure test,"
page 11.
Part No. 550-100-068/0308
7
Weil-McLain 88 Water and steam boilers — Series 2 — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
Assembling the block
Figure 6 Sealing rope installation
Sections are top heavy. Unbolted sections may fall
if not supported, resulting in severe personal injury
or death.
Prepare and position back section
1. Apply 1/8" continuous bead of sealing rope adhesive in sealing rope
grooves. See Figure 6. Do not get any adhesive on machined
port surfaces.
2. Place ½" sealing rope in groove.Around curves,grasp at 1" intervals
and push together. Do not stretch.
Do not pre-cut rope. Gas tight seal must be maintained
to prevent possibility of ue gas leakage and carbon
monoxide emissions, causing severe personal injury or
death. Cut rope as each section is completed.
3. Remove any grit from port machined surfaces with clean rag.
Do not use petroleum-based cleaning or sealing com-
pounds in boiler system. Severe damage to system
components can result, causing substantial property
damage.
4. Place 9" and 6" sealing rings in appropriate port openings. See
Figure 6. If sealing ring slips out of groove, stretch ring gently for
several seconds, then reposition in groove.
1
5. Apply continuous bead of silicone sealant no larger than /16"
Figure 7 Silicone sealant
around entire outside edge of outer machined surface of port.
Refer to Figure 7. Do not apply silicone sealant on, next to or
under sealing ring.
Silicone sealant applied as specified above prevents un-
burned oil vapors from coming in contact with sealing
ring.Vapor contact can damage rings, resulting in severe
damage to boiler and substantial property damage.
6. Hoist back section upright. Then temporarily screw a 6-inch
threaded pipe at least 36 inches long into the lower (return) tap-
ping.
7. Hoist the section and put into position.
8. Place a block under the 6-inch pipe to hold the back section up-
right and plumb.
The back section must be plumb before installing other
sections to ensure the block will assemble correctly.
9. The 6-inch support pipe and block can be removed after several
sections have been installed, and the assembly is stable.
10. Install intermediate sections as described on the following page.
8
Part No. 550-100-068/0308
Boiler manual:
• Installation • Start-Up • Maintenance • Parts
Assembling the block
Figure 8 Sealing ring installation and port
Sections are top heavy. Unbolted sections may fall
if not supported, resulting in severe personal injury
or death.
alignment
Install intermediate sections
1. Remove and discard 3/8" diameter shipping tie rods.
2. Remove grit from port machined surfaces with clean rag.
Do not use petroleum-based cleaning or sealing com-
pounds in boiler system. Severe damage to system
components can result, causing substantial property
damage.
3. Position intermediate section so aligning lugs fit into sockets of
next section. See Figure 8.
After erecting first intermediate section,
check both sections for plumb. Failure
to plumb sections can cause misaligned
piping and breeching, possibly resulting
in property damage.
4. Install TI (tankless intermediate) and SI (supply intermediate)
sections (when used) in order shown in Figure 9, page 10.
5. Draw sections together until metal-to-metal contact is made
around machined port openings (see Figure 8):
6. Repeat steps 1-5.
a. Oil threads on 4 draw rods. Install washer and nut on end to
be tightened. Use nut only on other end.
7. Check each section for proper sealing rope position
before proceeding to next section.
b. Uniformly draw sections together, starting at washer/nut
end.
Failure to position sealing rope properly
can cause boiler to not seal gas-tight.
Gas tight seal prevents possible ue gas
leakage and carbon monoxide emissions,
resulting in severe personal injury or
death.
Important — Leave an equal amount of thread on each
end of the draw rod. This is needed to allow securing the
jacket support brackets in place. The draw rods must not
extend past the face of the front or back section, or they
will interfere with the jacket.
c. Draw rods should be torqued to a range of 90 to 100 ft-lbs. Do
not back off draw rods.
8. Install remaining intermediate sections and front
section using the same procedure.
d. Metal-to-metal contact will be achieved around port openings.
See Figure 8. If gap occurs, it should be no greater than .032".
Check with feeler gauge.
If using tankless heater (TI)
sections
e. If, for any reason, gap around machined port opening exceeds
.032", check for rope extending from rope grooves, dirt on port
openings or sockets, or misaligned lugs. If corrections are made
and gap still exists, contact your Weil-McLain distributor or
sales office before continuing installation.
•
Install tankless heaters and gaskets or heater cover
plates and gaskets. Use /8" x /4" studs, washers
3
3
and nuts.
Part No. 550-100-068/0308
9
Weil-McLain 88 Water and steam boilers — Series 2 — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
(continued)
Assembling the block
Figure 9 Section arrangement
Max
number
of
tankless
heaters
Boiler model
number
Section arrangement
(all heaters must be on left side of boiler)
W = water
S = steam
F = front / B = back / I = Intermediate
TI = tankless intermediate SI = supply intermediate (steam only)
"I" can be substituted for "TI" sections
1
2
2
3
3
4
4
5
5
4
6
6
6
5
7
7
7
7
8
8
8
6
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀB
488 W&S
588 W&S
688 W&S
788 W&S
888 W&S
988 W&S
1088 W&S
1188 W&S
1288 W
1288 S
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀB
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀB
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀB
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀB
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀB
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀB
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀB
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀB
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀSIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀB
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀB
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀSIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀB
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀB
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀSIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀB
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀB
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀSIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀB
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀB
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀSIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀB
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀB
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀSIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀSIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀB
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀB
Fꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀSIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀSIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀTIꢀ•ꢀIꢀ•ꢀB
1388 W
1388 S
1488 W
1488 S
1588 W
1588 S
1688 W
1688 S
1788 W
1788 S
1888 W
1888 S
10
Part No. 550-100-068/0308
Boiler manual:
• Installation • Start-Up • Maintenance • Parts
Perform hydrostatic pressure test
Prepare boiler and test:
Figure 11 Boiler tappings
1. See Figure 10 and Figure 11 for tapping locations. Install:
a. Boiler drain (not furnished).
b. Water pressure gauge — for test only. Be sure gauge can handle
test pressure — see step 3.
c. Air vent in upper tapping (K).
2. Plug remaining tappings.
Do not pressure test with any control installed. Damage
to control can occur due to overpressure.
3. Fill boiler.Vent all air. Pressure test at least 10 minutes at a pressure
not less than the following:
a. Steam boiler: Between 45 and 55 psig.
b. Water boiler: 1½ times maximum allowable working
pressure (MAWP) stamped on the boiler nameplate, located
on boiler jacket front panel.
Do not exceed above test pressures by more than 10
psig.
Do not leave boiler unattended. Cold water fill could
expand and cause excessive pressure, resulting in severe
personal injury, death or substantial property damage.
4. Check for maintained gauge pressure and leaks. Repair if found.
Leaks must be repaired at once. Failure to do so can dam-
age boiler, resulting in substantial property damage.
Do not use petroleum-based cleaning or sealing com-
pounds in boiler system. Severe damage to system
components can result, causing substantial property
damage.
5. Drain boiler and remove air vent, boiler drain and gauge. Remove
plugs from tappings that will be used for controls and accesso-
ries.
Figure 10 Boiler tapping locations and sizes (see Figure 11)
Location
Size
Steam
Water
A
2"
Steam relief valve and/or
Skim tapping
High limit
Manual reset limit
B
L
2"
1"
1"
Steam relief valve
Secondary probe LWCO
Low water cut-offs
—
Water relief valve
Not used — Plug
C1 & C2
C1
Alternate low water cut-offs
Combination high and low
limit control
D1 & D2
1"
Alternate low water cut-offs
Firing rate temperature
control (when used)
Low water cut-offs
E1 & E2
F1 & F2
G
½"
C\,"
¾"
Gauge glass
—
—
Try cock tappings
Pressure limit control,
Pressure operating control and
pressure gauge,
Combination pressure–
temperature gauge
Firing rate pressure control
(when used)
H
K
¾"
1"
Boiler drain (see Figure 17,
page page 15, for system blow-
off (drain) valve locations and
sizes
Boiler drain
—
Piping to compression tank or
automatic air vent
Part No. 550-100-068/0308
11
Weil-McLain 88 Water and steam boilers — Series 2 — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
Complete block assembly
b. Position 3/8" sealing rope in groove.
Install burner mounting plate on front
section
c. Secure assembly to section. Use 10-32 x ¾"
truss-head screws.
1. Install four ½" x 3½" studs to secure burner mounting plate to
section:
2. Repeat above steps for back observation port as-
sembly.
a. Thread and lock together two nuts on rounded end of stud.
Thread at end of stud into one of four holes located around
opening.
b. Remove nuts.
c. Repeat steps a and b for remaining studs.
Insert HXT-bars
1. See Figure 12, page 12.
2. Flue HXT-bars are identified by painted ends. They
must be inserted as shown, with the HXT-bars in
the sequence:
2. Install burner mounting plate:
a. Apply 1/8" continuous bead of sealing rope adhesive in groove
around opening in section.
•
Top position
red-tipped, HXT-bar 24 inches long —
place on the top row of pins.
Middle position
b. Position ½" sealing rope in groove. Overlap ends at least one
inch.
c. Install burner mounting plate with part number and the word,
"UP," positioned at top. Use ½" washers and nuts.
•
•
•
white-tipped HXT-bar, 26 inches long —
place on the first row of pins below the top
clean-out plate boss.
Install observation port assemblies on front
and back sections
•
Bottom position
1. Install front observation port assembly:
•
blue-tipped HXT-bar, 34 inches long —
place on the first row of pins below the
bottom cleanout plate boss.
a. Apply 1/8" continuous bead of sealing rope adhesive in groove
on observation port.
Figure 12 Insert HXT-bars through cleanout openings as shown below (omit the bottom, blue-tipped, HXT-bar in the opening
between the front section and the first intermediate section)
12
Part No. 550-100-068/0308
Boiler manual:
• Installation • Start-Up • Maintenance • Parts
(continued)
Complete block assembly
DO NOT insert a bottom HXT-bar into the opening
between the FRONT section and the first intermediate
section.
Figure 13 Cleanout plate assembly
3. To remove ue HXT-bars when required to clean the boiler
ueways, grab the end of each HXT-bar with pliers and pull
straight out. Clean HXT-bars and replace as shown in Fig-
ure 12, page 12.
Install cleanout plates
Cleanout plates must be installed gas-tight to prevent
possibility of ue gas leakage and carbon monoxide
emissions, resulting in severe personal injury or death.
1. See Figure 13.
2. Position two ¼" x 1¾" carriage bolts in cleanout opening, be-
tween the cleanout plate bosses, as shown. Secure with washers
and nuts.
3. Place woven fiberglass gasket over carriage bolts.
4. Mount cleanout plate over opening. Secure with nuts and wash-
ers.
5. Repeat steps 1 through 3 for remaining cleanout plates.
Install draft hood collar
1. Install 1/8" continuous bead of sealing rope adhesive in groove on
draft hood collar.
The boiler contains ceramic fiber and
2. Position ½" sealing rope in groove. Overlap ends of rope at least
1 inch.
fiberglass materials. Use care when han-
dling these materials per instructions on
page 34 of this manual. Failure to comply
could result in severe personal injury.
3. Mount collar over ueway outlet on back section. Secure with ½
x 1½" hex head cap screws and washers.
Part No. 550-100-068/0308
13
Weil-McLain 88 Water and steam boilers — Series 2 — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
Connect water boiler piping
General water piping information
Figure 14 Water boiler piping, typical
1. System water supply and return piping should be installed and
piping connections attached to boiler before erecting jacket or
installing controls.
2. Do not pipe in through supply and out through return. This creates
reverse water ow through boiler that must not be used.
3. When installing in a system in which return water temperature can
drop below 140°F, apply the by-pass piping with by-pass pump as
shown in .
Install piping
Install piping as shown in Figure 14, page 14 and Figure 18, page 15
(if applicable) for single boilers. For multiple boilers, see Fig-
ure 19, page 15.
Improperly piped systems or undersized piping can
contribute to erratic boiler operation and possible boiler
or system damage.
1. Connect supply and return piping:
a. Size according to tables below.
•
For known flow rates or higher flow rate (less than 20°F
temperature rise) through boiler, see Figure 15.
•
For unknown flow rates, size piping per Figure 17,
page page 15, using 20°F temperature rise through boiler.
Flow at higher rates than shown in the tables in this
manual for given pipe sizes can damage the boiler, caus-
ing substantial property damage.
b. Locate circulator in supply piping.
c. For return piping, use full diameter pipe for 10 times that
diameter before making any reduction. For example, a 4-inch
return should not be reduced any closer to boiler return tap-
ping than 40 inches.
Figure 15 Recommended minimum pipe sizes for
known flow rates (note 1)
d. Install system blow-off (drain) valve in lowest part of return
piping close to boiler. ASME minimum size requirements are
given in Figure 17, page 15.
Water flow rate Supply pipe size
Return pipe size
GPM
Up to 35
36–50
A
B
2"
2"
2½"
3"
2. Install expansion tank:
2½"
3"
a. Closed type – connect to 1" tapping "K" (see page 11). Use
1" NPT piping. Any horizontal piping must pitch up toward
tank at least 1 inch per each 5 feet of piping.
51–77
78–142
143–237
238–404
4"
4"
5"
5"
b. Diaphragm type – Refer to tank manufacturer's literature for
6" (note 2)
6"
location. Install automatic air vent in "K" tapping.
Note 1
High temperature rise through boiler is permissible when boiler
piping connections are sized per this table. Intermittent
flow at high velocities may damage any boiler.
6-inch piping requires nipples and 5" x 6" reducing couplings
(provided with 1288 through 1888 boilers only).The total
pressure drop through the 1888 boiler using the nipple and
reducing coupling will not exceed ¼ PSI. For smaller boilers, the
pressure drop will be less.
c. Connect cold water fill to expansion tank piping. Figure 14
shows typical piping when using a closed type tank. Connect
to the same location as the expansion tank connects to the
system when using a diaphragm type tank.
Note 2
d. Also shown are recommended valves and water meter, when
used.Water meter will detect added make-up water, indicating
leaks in system.
14
Part No. 550-100-068/0308
Boiler manual:
• Installation • Start-Up • Maintenance • Parts
(continued)
Connect water boiler piping
Figure 16 Recommended minimum pipe sizes when flow rate is
Figure 18 By-pass piping for return water less than
not known (see Figure 14, page page 14) (note 1)
140°F
Boiler
model
Supply pipe size
Return pipe size
A
B
488
3"
4"
3"
4"
588 – 788
888 – 1188
1288 – 1888
5"
5"
6" (note 2)
6" (note 2)
By-pass circulator sizing:
Note 1
Pipe sizes are based on a 20°F temperature rise through the boiler. For applications
with higher flow rates (lower temperature rise), determine the flow rate and use
Figure 15, page page 14 to size the piping.
1. Size system circulator as required. Determine GPM
and head requirements.
Note 2
6-inch piping requires nipples and 5" x 6" reducing couplings (provided with 1288
through 1888 boilers only).The total pressure drop through the 1888 boiler using the
nipple and reducing coupling will not exceed ¼ PSI. For smaller boilers, the pressure
drop will be less.
2. Provide a by-pass circulator for EACH boiler. The ow
rate for each by-pass circulator will be:
Flow = ¼ x (System circulator GPM) ÷ (# of boilers)
3. All circulators must run at the same time.
Figure 17 ASME drain valve size
4. Example: For a 1,000,000 Btuh single boiler, with
system temperature drop of 20°F:
Boiler
model
Minimum blow-off
valve size
• System GPM = 1,000,000 ÷ 20 ÷ 500 = 100 GPM
• By-pass GPM = ¼ x 100 GPM = 25 GPM
488 – 588
688 – 1088
1188 – 1888
1"
• Determine by-pass circuit head loss for pipe size
and fittings used.
1¼"
1½"
5. In most applications, a standard booster pump should
be adequate.
Piping multiple boilers
1. See Figure 18. (Expansion tanks, relief valves and other accessories
are required, but omitted from the illustration for simplicity.)
Figure 19 Multiple water boiler piping
2. The boiler piping circuits are referred to as the secondary circuits
in the following.
3. The legend for Figure 18 and boiler pump sizing recommenda-
tions follow:
A
Size boiler pump GPM based on the following:
a Temp rise = High limit temp – Return water temp
Boiler Gross Output, Btuh
b GPM =
Temperature rise x 500
c. Calculate only secondary (boiler) piping circuit resistance. Al-
low for head loss through the boiler equal to three 90 degree
elbows of secondary pipe size.
d. Operate each boiler and its pump with a Weil-McLain boiler
control panel.
e. Size secondary (boiler) circuit piping using the ow rate ranges
given in Figure 17, page 15.
B Primary pump GPM and head calculation should not include
secondary boiler circuits. Primary pump can operate continuously
during heating season.
C Connection to primary circuit — Space 12" maximum or as close
as practical.
D Check valve.
E
Hand valve.
Part No. 550-100-068/0308
15
Weil-McLain 88 Water and steam boilers — Series 2 — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
Connect steam boiler piping
General steam piping information:
Figure 20 Cold water fill piping
1. Hartford loop piping arrangement and wet return are required for
steam boilers. Use the Hartford loop for both pumped-return and
gravity-return systems.
2. Maintain 24-inch minimum from waterline to bottom of header (63"
from bottom of section).
3. When using condensate receiver, feed pump must be energized by
boiler-mounted pump controller.
4. Install piping:
a. Install piping as shown on page 17 through page 18 for single boil-
ers. See page 19 for additional requirements when piping multiple
boilers.
b. Return pipe sizing.
•
•
Pumped return — Size return piping by pump.
Gravity return — Size gravity return same as Hartford loop
equalizer pipe size.
Figure 21 Condensate piping to boiler
c. Drain valve — Install system drain valve in lowest part of return
piping close to boiler. See Figure 17, page 15, for sizing.
d. Cold water fill piping — Connect cold water fill piping as shown in
Figure 20. Also shown are recommended valves and water meter,
if used. Water meter will detect added makeup water, indicating
leaks in system.
e. Condensate return piping:
•
Satisfactory operation of any steam heating system depends on
adequate return of condensate to maintain steady water level.
•
•
Avoid adding excessive amounts of raw make-up water.
Where condensate return is not adequate, a low water cutoff
with pump control, condensate receiver, and condensate boiler
feed pump should be installed.
•
See Figure 21 for piping and Figure 22 for sizing.
Figure 22 Condensate receiver capacity required
Boiler
I=B=R gross output Gallons condensate
Minimum condensate receiver capacity (gallons) (Note 1)
Recommended condensate
model number
(lbs steam per hour)
per hour
feed pump capacity
GPM at 15 PSI
15-minute boiler
operation
30-minute boiler 45-minute boiler 60-minute boiler
operation
operation
operation
488
488R
588
810
97
29
28
58
87
116
114
156
196
234
273
313
289
353
332
392
432
470
511
550
588
574
629
668
3.2
3.1
794
95
57
85
1084
1358
1632
1904
2170
1991
2452
2304
2724
3000
3270
3550
3820
4090
3980
4370
4640
130
163
195
228
261
239
294
277
327
360
392
426
458
490
478
524
557
39
78
117
147
176
205
235
217
265
249
294
324
353
383
412
441
430
471
501
4.3
688
49
98
5.4
788
59
117
137
157
145
176
166
196
216
235
255
274
294
287
314
334
6.5
888
68
7.6
988
78
8.7
988R
1088
1088R
1188
1288
1388
1488
1588
1688
1688R
1788
1888
72
8.0
88
9.8
83
9.2
98
10.9
12.0
13.1
14.2
15.3
16.4
15.9
14.5
18.6
108
117
127
137
147
143
157
167
Note 1 — Maximum time to when condensate returns to boiler — the longer the time for condensate to return, the larger the receiver must be.
16
Part No. 550-100-068/0308
Boiler manual:
• Installation • Start-Up • Maintenance • Parts
(continued)
Connect steam boiler piping
Improperly piped systems or undersized piping can
contribute to erratic boiler operation and possible boiler
or system damage. Piping system must be installed as
shown, using pipe sizes shown. Pipe sizes shown are for
two-pipe, pumped-return systems. Adjust pipe sizing
as needed when connecting to gravity-return systems.
Consult local Weil-McLain distributor or sales office
before installing alternate piping.
Figure 23 Model 488 through 688 steam (1 riser)
Steam boiler piping guidelines
Minimum height of header above water line must
be 24 inches
The boiler header must always be at least 24 inches
above the water line, as shown in all steam boiler piping
diagrams.Installing the pipe lower will result in increased
water carryover to the system, resulting in potential seri-
ous damage to system components and oxygen corrosion
due to excess make-up water.
Hartford loop piping for all steam boilers
1. You must install the system supply pipe between the equalizer
elbow and the last boiler riser pipe connection to the header. This
assists in separating water from the steam as it turns upward into
the steam supply pipe.
2. Locate the top of the Hartford loop return nipple at least 4 inches
below the water line, as shown.
Figure 24 Model 788 through 1188 steam (2 risers required)
Drawing legend & notes
(Figure 23 through Figure 26)
1
2
Riser pipes (one for each supply intermediate
section)
Horizontal pipes needed to offset the header
to allow for expansion and contraction of the
header
3
Steam supply must be located between last riser
connection and equalizer elbow
4
5
6
Equalizer elbow — full size or reducing
Equalizer pipe
Close nipple at Hartford loop tee to reduce water
hammer potential
7
8
Condensate return line (gravity or pumped)
Minimum 4 inches between water line and top
of Hartford loop return nipple
9
Boiler water line — all automatic water level
controls must be set to maintain this level
10 Minimum 24 inches between water line and
bottom of header
Part No. 550-100-068/0308
17
Weil-McLain 88 Water and steam boilers — Series 2 — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
(continued)
Connect steam boiler piping
Figure 25 Model 1288 through 1888 steam (3 or 4 risers required)
Drawing legend & notes
(Figure 23 through Figure 26)
1
2
3
4
5
6
7
8
9
Riser pipes (one for each supply intermediate section)
Horizontal pipes needed to offset the header to allow for expansion and contraction of the header
Steam supply must be located between last riser connection and equalizer elbow
Equalizer elbow — full size or reducing
Equalizer pipe
Close nipple at Hartford loop tee to reduce water hammer potential
Condensate return line (gravity or pumped)
Minimum 4 inches between water line and top of Hartford loop return nipple
Boiler water line — all automatic water level controls must be set to maintain this level
10 Minimum 24 inches between water line and bottom of header
18
Part No. 550-100-068/0308
Boiler manual:
• Installation • Start-Up • Maintenance • Parts
(continued)
Connect steam boiler piping
Figure 26 Multiple Steam Boiler Piping Gravity Condensate Return
See page 18 for numbered
circle references.
A
Pipe as shown for gravity return systems, connect-
D Install stop valves per ASME code requirements.
ing point A to the wet gravity return.
•
For pump-return systems, if using automatic
steam valves, use only slow-opening automatic
valves. Use a Weil-McLain Boiler Control Sys-
tem (such as a BCP panel) to open each steam
valve automatically before firing burner.
•
For pumped-return systems, install boiler water
level control on each boiler with body mark at
level indicated in Figure 42, page 28. Provide at
point A either:
•
•
Separate feed pumps and check valves for each
E
F
Construct common supply drop header with pipe
size at least same size as largest boiler header size.
boiler, or . . .
Single feed pump, with separate solenoid valve
for each boiler.
Use:
•
•
A Weil-McLain Boiler Control System (such as
a BCP panel) with header-mounted pressure
control(s) to sequence boilers, or . . .
B For pumped-return systems, install a combination
oat and thermostatic trap on each boiler to prevent
ooding of one boiler while other boiler is firing.
Install trap in skim tapping (see Figure 39, page 27).
Connect traps to condensate receiver.
A steam pressure controller.
G Install drip line in common supply drop header.
Gravity-return systems are self-levelling if the wet
returns are piped to the common system wet return.
•
•
Gravity-return: Pipe drip line to wet return.
Pumped-return: Use combination oat and
thermostatic trap and drain to condensate
receiver.
C Install boiler piping as shown in the preceding pages
of this manual.
Part No. 550-100-068/0308
19
Weil-McLain 88 Water and steam boilers — Series 2 — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
Install jacket
Before installing jacket
Figure 27 Place support brackets as listed below
The boiler contains ceramic fiber and fiberglass materials.
Boiler
Upper brackets on
Lower brackets
on sections:
None
Use care when handling these materials per instructions
on page 34 of this manual. Failure to comply could result
in severe personal injury.
sections:
2, 3
2, 4
2, 5
2, 6
488
588
688
788
888
988
None
None
None
None
1. These parts must be on boiler:
3, 6
2, 5, 8
a. Plugs for unused tappings
b. Supply and return piping and steam supply header
c. Cleanout plates
d. Tankless heaters (when used), tankless heater cover plates
(when used), tankless heater piping (when used)
e. Flue damper assembly
None
1088
1188
1288
1388
1488
1588
1688
1788
1888
3, 6, 9
3, 6, 9
3, 7, 10
6
6
7
7
7
8
9
9
10
3, 7, 11
3, 7, 10, 13
2, 5, 8, 11, 14
2, 5, 9, 12, 15
2, 5, 9, 13, 16
2, 6, 10, 14, 17
f. Observation port assemblies
2. These parts may be on boiler:
a. Burner mounting plate and burner
3. These parts must be off boiler:
a. Water or steam gauge
3. Attach the upper channels to the upper supports as
shown in callouts and , Figure 29, page 21.
,
b. Limit control and low water cutoff
c. Gauge glass and gauge glass cocks, tri-cocks
d. Drain cock
Use two #10 x ½" screws at each bracket. Models
988 and larger have two-piece channels.
•
The side channels are labelled A and B in Fig-
ure 29. Figure 28 gives the lengths of the side
channel parts for each model.
Remove jacket parts from cartons
•
The channels at the boiler front and rear are
part numbers 426400030 & 426400031, re-
spectively.
1. Locate jacket cartons.
2. Remove jacket parts from cartons as needed. Leave in cartons as
long as possible to avoid damage.
Figure 28 Upper and lower side channel lengths
3. Jacket parts are in the boxes listed below:
Boiler
Upper channel lengths
Lower channel lengths
Part
Box label descriptions
included in CRNR boxes
BKT
(inches)
(inches)
Jacket screws (in jacket corner boxes)
Jacket support brackets & hex nuts
Jacket side support channels, upper & lower
Jacket front/rear support channels, upper & lower
Jacket front panel
A
B
A
B
488
588
688
788
888
30
38
46
54
62
NA
NA
NA
NA
NA
26
34
42
50
58
NA
NA
NA
NA
NA
included in TRM/CHNL boxes
COM
988
35
35
66
NA
PNL-F
1088
1188
1288
1388
1488
1588
1688
1788
1888
43
43
51
51
51
59
67
67
71
35
43
43
51
59
59
59
67
71
40
40
48
48
48
56
64
64
72
34
42
42
50
58
58
58
66
66
Jacket back panel
PNL-B
Jacket side and top panels
Jacket corners
L / R / T
CRNR
Jacket trim
TRM/CHNL
Install support brackets/channels
4. Attach the four jacket corners to the upper channels
as shown in callout , Figure 29, page 21. Corner
part numbers are: 426400054 (front left),055 (front
right), 056 (back left), and 057 (back right).
1. Place upper and lower support brackets over draw rods as shown
in Figure 29, page 21. Place the brackets on the sections as given in
Figure 27. Sections are numbered from front to back.
2. Fasten each bracket loosely using two 5/8" nuts screwed onto the
ends of the tie rods as shown.
5. Attach the lower side, front and rear channels to
the jacket corners as shown in callouts
and
of Figure 29, page 21. Models 1088 and larger
have two-piece side channels. The channels are
labelled A and B in Figure 29. Figure 28 gives the
lengths of these parts for each model. Front and
rear lower channels are part numbers 426400032
and 426400033.
Models 488 through 988 do not require lower support
brackets. Only upper brackets are required.
Fasten all nuts and screws loosely during assembly to
allow adjustment after all jacket frame parts are in-
stalled.
20
Part No. 550-100-068/0308
Boiler manual:
• Installation • Start-Up • Maintenance • Parts
(continued)
Install jacket
Figure 29 Installing jacket support brackets, support channels and corners (piping and other components omitted for clarity)
Part No. 550-100-068/0308
21
Weil-McLain 88 Water and steam boilers — Series 2 — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
(continued)
Install jacket
Install jacket front and back panels
1. Slide the jacket front and back panels down over the top channels
and into the bottom channels as shown in Figure 30.
Figure 30 Installing (removing) jacket front, rear
and side panels
2. Slide the upper and lower channels as needed to square up the
fit.
Install jacket side panels
1. Remove jacket side panels from cartons.
2. Before installing side panels, square up the jacket support rails.
•
Place any of the jacket side panels on the rails as shown in
Figure 30.
•
•
Butt the side panel against the jacket corner panel.
Push/pull on the upper and lower channels until the fit-up of
the side panel, corner panel and channels is square.
Place a jacket top panel in position against the jacket front panel
to ensure the top alignment is square.Adjust the jacket support
rails forward or backward if needed for square alignment.
Tighten the 5/8-inch nuts on the upper (and lower) support
brackets.
Tighten the screws securing the upper and lower rails to the
support brackets.
Tighten the screws securing the front and back panels to the
rails.
•
•
•
•
3. Apply all jacket side panels in the order shown in Figure 32.
•
Remove jacket knockouts as required for tankless heaters and
tankless heater openings.
•
Note that panel sequence is not important for boilers not
equipped with tankless heater intermediate sections.
Install jacket top panels
1. Place jacket top panels as shown in Figure 33, page 24.
•
Remove knockouts for riser pipes and air bleed piping (front
section) using tin snips.
Figure 31 Press jacket trim down over jacket front,
rear and side panels
Install jacket trim
2. Press jacket trim down over the front and side jacket panels as
shown in Figure 31.
22
Part No. 550-100-068/0308
Boiler manual:
• Installation • Start-Up • Maintenance • Parts
(continued)
Install jacket
Figure 32 Jacket side panel placement
Part No. 550-100-068/0308
23
Weil-McLain 88 Water and steam boilers — Series 2 — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
(continued)
Install jacket
Figure 33 Jacket top panel placement
24
Part No. 550-100-068/0308
Boiler manual:
• Installation • Start-Up • Maintenance • Parts
Pipe tankless heaters
To pipe tankless heaters:
1. See Figure 35.
2. Size piping no smaller than heater inlet and out-
let.
Hot water can scald!
3. Automatic mixing valve must be installed. See
Figure 35. Follow manufacturer's instructions to
install.
4. Flow regulating valve must be installed. Size accord-
ing to continuous draw of heater. See Figure 34.
Follow manufacturer's instructions to install.
5. Operating control with small adjustable differen-
tial scale is recommended. Install in temperature
control tapping in heater plate.
6. Multiple tankless heaters (see Figure 35):
a. Use cold water supply header with individual
risers to each heater. Size header by increasing
one pipe size for each additional heater.
b. Use hot water outlet header with individual
risers to each heater. Size header by increasing
one pipe size for each additional heater.
c. Do not pipe multiple heaters in series.
7. In hard water areas, soften cold domestic water
supply to heaters to prevent lime build-up.
Consumer Product Safety Commission and some
states recommend domestic hot water tempera-
ture of 130°F or less.
Figure 34 Tankless heater ratings (Weil-McLain
ratings)
When installing an automatic mixing valve, se-
lection and installation must comply with valve
manufacturer's recommendations and instruc-
tions.
Heater
number
Intermittent
draw – GPM
(note 2)
Continuous
draw GPM
(notes 1, 2)
Inlet and
outlet tappings
820
8.5
6.5
¾"
GPM based on 40–140°F DHW with boiler water
at 200°F
Note 1
Note 2
Water heated to a temperature suitable for clothes
washing, dish washing and other sanitizing needs
will scald and cause injury.
Based on continuous draw with no recovery period
Children, elderly, infirm or physically handi-
capped persons are more likely to be injured
by hot water. Never leave them unattended in
or near a bathtub, shower or sink. Never allow
small children to use a hot water faucet or draw
their own bath. If anyone using hot water in the
building fits this description, or if state laws or
local codes require certain water temperatures at
hot water faucets, take special precautions:
Figure 35 Tankless Heater Piping
— Install automatic mixing valve set according
to those standards.
— Use lowest practical temperature setting.
— Check water temperature immediately after
first heating cycle and after any adjustment.
Part No. 550-100-068/0308
25
Weil-McLain 88 Water and steam boilers — Series 2 — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
Install water boiler controls
Install controls:
Figure 37 Water control locations
1. Install furnished controls per Figure 36 and Figure 37.
Failure to properly install, pipe and wire boiler controls
can result in severe damage to boiler, building and per-
sonnel; and is not covered by boiler warranty.
2. Relief valve must be installed with spindle in vertical position. Use
fittings provided with boiler. Do not make any other connection
in that piping.
Relief valve discharge line must be piped using rigid
material suitable for 375°F, threaded one end, near oor
close to drain to eliminate potential of severe burns. Do
not pipe to any area where freezing could occur. Do not
plug, valve or place any obstruction in discharge line.
3. When installing low water cut-off
a. Must be installed if boiler is located above radiation level.
b. May be required on water boilers by certain state, local or ter-
ritorial codes or insurance companies.
c. Install low water cutoff designed for water installations where
shown in Figure 36 and Figure 37.
4. If installation is to comply withASME installation requirements,an
additional high temperature limit is needed. Purchase and install in
supply line between boiler and isolation valve or in tapping "A."
5. Dual limit control settings:
a Low – set according to design requirements.
b High – at least 20° higher than low limit, 240°F maximum.
6. Install optional controls per control manufacturer's instructions.
Figure 36 Water control tappings (see Figure 37)
Location
Size
Function
A
2"
High limit
Manual reset limit
B
L
2"
1"
1"
Water relief valve
Not used — plug
C1 & C2
C1
Alternate low water cut-offs
Combination high and low
limit control
D1 & D2
1"
Firing rate temperature
control (when used)
Low water cut-offs
E1 & E2
½"
C\,"
¾"
¾"
1"
—
F1 & F2
—
G
H
K
Combination pressure–temperature gauge
Boiler drain
Piping to compression tank or automatic air vent
26
Part No. 550-100-068/0308
Boiler manual:
• Installation • Start-Up • Maintenance • Parts
Install steam boiler controls
Install controls:
Figure 39 Steam control locations
1. Install controls where shown in Figure 38 and Figure 39.
Failure to properly install, pipe and wire boiler controls
can result in severe damage to boiler, building and per-
sonnel; and is not covered by boiler warranty.
a. Install steam pressure operating and high limit controls and
pressure gauge. See Figure 38, Figure 39 and Figure 40, page 28.
Pressure limit control settings:
•
•
Low – set according to design requirements.
High – set at least 2 psi higher than low limit, 15 psi maxi-
mum.
b. Relief valve must be installed with spindle in vertical position.
Use fittings provided with boiler. Do not make any other con-
nection in that piping.
Pipe relief valve discharge through vertical piping to at-
mosphere. Use rigid material suitable for 375°F, threaded
one end only. Install drain pan elbow to drain condensate.
Pipe near oor close to oor drain to eliminate potential
of severe burns. Do not pipe to any area where freezing
could occur. Do not plug, valve or place any obstruction
in discharge line.
c. Install water level controls and gauge glass per Figure 38,
Figure 39 and Figure 42, page 28.
•
•
Fittings for controls to be furnished by others.
If water level control is not shown in Figure 41, page 28,
locate casting mark on control and install per manufac-
turer's instructions.
Do not use water level controls with quick hook-up fit-
tings. Nuisance shutdowns will occur.
Figure 38 Steam control tappings (see Figure 39)
Location
Size
Function
A
2"
Steam relief valve and/or
Skim tapping
B
2"
1"
1"
Steam relief valve
L
Secondary probe low water cut-off
C1 & C2
C1
Low water cut-offs (see Figure 42, page 28)
—
D1 & D2
E1 & E2
F1 & F2
G
1"
½"
C\,"
¾"
Alternate low water cut-offs (see Figure 42, page 28)
Gauge glass
Try cock tappings
Pressure limit control,
Pressure operating control and pressure gauge,
Firing rate pressure control (when used)
H
K
¾"
1"
Boiler drain (see Figure 17, page page 15, for system
blow-off (drain) valve locations and sizes
—
Part No. 550-100-068/0308
27
Weil-McLain 88 Water and steam boilers — Series 2 — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
(continued)
Install steam boiler controls
Figure 40 Steam control siphon and fittings
Figure 41 Float-type water level control locations
Primary water level
control
Casting line
height above
bottom of gauge
glass
Back-up water level
control
Casting line
height above
bottom of gauge
glass
Note 1
"A"
¼"
Notes 1, 2
None
"B"
—
61, 63
1½"
2C\,"
2"
61, 63
½"
—
None
150
¼"
¼"
¼"
—
150MD, 157MD
(see Note 3)
2C\,"
2C\,"
2"
61, 63
51-2 & 51-S-2
None
2"
93, 193, 94
61, 63
¼"
¼"
¼"
93, 193, 94
(see Note 3)
2"
2"
51-2 & 51-S-2
51-2 & 51-S-2
(see Note 3)
1"to 1¼"
None
—
Notes:
1. Other manufacturer's controls providing similar function may be used, if properly
located and selected.
2. Use low water cut-off function only. Pump controller function must only be handled
by the primary control.
3. When pump control is used with feedwater tank, install pump control on boiler and
make-up water feeder on tank. Use separate low water cutoff on boiler when back-
up is needed. Do not install combination low water cutoff and feeder as back-up
control on boiler. Feeder will operate before pump control operates.
Figure 42 Water level control locations (see Figure 41)
28
Part No. 550-100-068/0308
Boiler manual:
• Installation • Start-Up • Maintenance • Parts
Connect breeching and venting systems
General venting information
Figure 43 Minimum breeching diameter
1. Model 88 boilers operate with positive overfire pressure. Adjust
damper assembly (see Figure 49, page 33) during burner start-up
to achieve 0.1" W.C. positive pressure at damper sample hole.
Boiler
model
I=B=R
vent or liner diameter
(inches)
Boiler flue
collar
dimensions
(inches)
Select type of venting system
Forced
draft
Balanced
draft
Forced draft
•
Boiler, breeching and stub vent operate at positive pressure. Entire
system must be gas-tight to prevent leaks. Stub vent height must be
limited to prevent negative draft with 3-foot minimum stub vent
height above roof. See Figure 44 and Figure 46.
10
10
12
12
14
14
14
16
16
16
18
18
18
18
20
12
15
15
18
18
18
21
21
21
24
24
24
24
24
27
10 round
10 round
488
588
Balanced draft
10 round
688
•
Boiler operates with positive pressure overfire. Chimney may
provide excess draft which may require a barometric draft control
installed and set to provide minimum draft to maintain 0.1" posi-
tive pressure at ue collar. Minimum chimney height above roof
is 3 feet. See Figure 45 and Figure 47.
12 round
788
12 round
888
14 round
988
Construct metal breeching:
14 round
1088
1188
1288
1388
1488
1588
1688
1788
1888
1. See Figure 43 for minimum breeching diameter.
14 round
2. Select material type and thickness in compliance with local
codes.
14 round
Conventional ue pipe should not be used as it could
leak ue gases and carbon monoxide emissions through
seams and joints, resulting in severe personal injury or
death.
14 round
16 round
3. Refer to ASHRAE Guide for chimney and breeching calculations
and construction and lining.
16 round
16 round
Long horizontal breechings,excessive number of tees and
elbows or other obstructions restricting combustion gas
ow can result in possibility of condensation, ue gas
leakage and carbon monoxide emissions, causing severe
personal injury or death.
16Z\, x 19M\, oval
16Z\, x 19M\, oval
Part No. 550-100-068/0308
29
Weil-McLain 88 Water and steam boilers — Series 2 — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
Connect breeching and venting systems
Figure 44 Stub vent – forced draft — single boiler
Figure 46 Stub vent – forced draft — multiple
boilers
Figure 45 Conventional chimney – balanced draft
with barometric draft control when
required — single boiler
Figure 47 Conventional chimney – balanced draft
with barometric draft control when
required — multiple boilers
30
Part No. 550-100-068/0308
Boiler manual:
• Installation • Start-Up • Maintenance • Parts
Install burner & wiring and fill system
For unusually hard water areas or low pH conditions
To install burner
(less than 7.0) consult local water treatment company.
Provide a water softener for make-up water if hardness
exceeds 7 grains.
1. Unpack burner.
2. Place gasket around air tube and against burner mounting ange.
If sealing rope is used, apply 1/8" continuous bead of rope adhesive
around burner mounting ange and apply sealing rope to make
gas-tight seal.
Freeze protection (when used)
(water boilers only)
3. Mount burner into opening in burner mounting plate.
1. Use antifreeze especially made for hydronic systems.
Inhibited propylene glycol is recommended.
Maintain gas-tight seal between burner mounting ange
and plate to prevent damage to air tube.
4. Level burner using burner support brackets where required.
5. Secure with furnished bolts.
Do not use automotive, ethylene glycol
or undiluted antifreeze. Severe personal
injury or death can result.
6. Retain burner information packet. Keep with boiler.
2. 50% solution provides protection to about -30°F.
3. Local codes may require back- ow preventer or
actual disconnect from city water supply.
To wire burner and boiler controls
Electric shock hazard. Can cause severe personal injury
or death if power source is not disconnected before
installing or servicing boiler and burner.
4. Determine quantity according to system water
content. Boiler water content is listed in "Ratings,"
page 35. Percent of solution will affect sizing of heat
distribution units, circulator and expansion tank.
1. Install all wiring in compliance with:
5. Follow antifreeze manufacturer's instructions.
•
•
National Electrical Code ANSI/NFPA 70.
Any additional national, state, or local codes.
2. Follow burner manual and wiring diagram found in burner in-
formation packet.
To fill water boilers
1. Close manual air vents and drain cocks.
3. Use #14 AWG wire for operating and safety circuit wiring.
2. Fill to correct system pressure. Correct pressure will
vary with each installation.
4. Where burner motor voltage differs from control voltage, supply
proper voltage to each. Size fused disconnects and conductors per
National Electrical Code ANSI/NFPA 70.
3. Starting on lowest oor, open air vents one at a
time until water squirts out. Close vent. Repeat
with remaining vents.
Determine if water treatment is needed
(water boilers only)
4. Refill boiler to correct pressure.
Do not use petroleum-based cleaning or sealing com-
pounds in boiler system. Severe damage to system
components can result, causing substantial property
damage.
To fill steam boilers
1. Do not fill (except for leakage test) until boiler is
ready to be fired.
Continual make-up water will reduce boiler life. Minerals can build up
in sections, reducing heat transfer, overheating cast iron and causing
section failure.
2. Fill to normal waterline, halfway up gauge glass.
3. Recommend boiler water pH 7.0 to 8.5.
Part No. 550-100-068/0308
31
Weil-McLain 88 Water and steam boilers — Series 2 — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
Install fuel piping
Gas piping
Figure 48 Gas supply piping
1. In sizing the gas piping, the following factors should be consid-
ered:
a. Diameter and length of the gas supply piping.
b. Number of fittings.
c. Maximum gas consumption (including any possible future
expansion).
d. Allowable loss in gas pressure from the gas meter outlet to
the boiler.
2. Minimum inlet natural gas pressure required at manual main shut-
off valve — see the burner manual and material list.
3. Follow good piping practices.
4. Pipe joint compound (pipe dope) must be resistant to the corrosive
action of liquefied petroleum gases and applied sparingly only to
the male threads of pipe joints.
5. A ground joint union must be installed in the piping to provide
for servicing. The supply piping must include a manual shut-off
valve and sediment trap. See Figure 48.
6. Piping must be supported by hangers, not by the burner or its
accessories.
7. Purge all air from the supply piping.
8. All gas piping must be tested for leaks after installation. Use soap
suds mixture only.
Fuel oil piping
To prevent oil ow in case of oil line breakage:
7. Follow good piping practices.
8. Pipe joint compound (pipe dope) must be resistant
to corrosive action of fuel oil. Apply sparingly only
to male threads of pipe joints.
•
Use anti-syphon device when any part of the oil tank
is above burner level.
•
Use check valve in suction line on burner side of
manual shut-off valve nearest tank when top of fuel
oil tank is below burner level.
9. Supply and return piping should be sized to design
conditions, but not less than ½" O.D. continuous
copper tubing.
Failure to comply could result in fuel leakage or fire, caus-
ing potential severe personal injury, death or substantial
property damage.
10. Auxiliary fuel oil pump is recommended when
suction line lift exceeds 12 feet.
11. Install swing joints so they will tighten as buried
tank settles to prevent fuel line breakage.
1. A two-pipe fuel oil piping system is required for all installations.
2. Supply and return lines must enter tank from top, extending to
within 4 to 6 inches from bottom of tank.
12. Where iron pipe is required by local codes, make
swing joints with nipples and elbows several inches
long on both suction and return line. Locate close
to tank.
3. Use oil filter sized for fuel pump suction gear capacity.
4. Install oil filter.
Do not install filter outside or close to an outside wall.
13. Install manual shut-off valve in suction line piping
near burner and where piping enters building from
outside tank.
5. Use continuous copper tubing to reduce possible piping leaks and
to ensure reliable seal when oil piping is buried.
14. Pitch suction line piping toward fuel tank.
6. Use are fittings, not compression fittings.
15. Provide tee and plug at highest point in suction
line to release air from suction line and aid in
priming.
Fire hazard — DO NOT USE soldered fittings. No safe
repair can be made.
32
Part No. 550-100-068/0308
Boiler manual:
• Installation • Start-Up • Maintenance • Parts
Make final adjustments
Adjust burner and damper assembly:
Figure 49 Flue collar/damper assembly
1. Lock ue damper OPEN (Figure 49).
Make final burner adjustments using combustion test
equipment to assure proper operation. Do not fire boiler
without water. Sections will overheat, damaging boiler
and resulting in severe property damage.
2. Refer to burner manual for start-up and service.
3. Let burner advance to high fire. Heat boiler to design conditions.
4. Using combustion test equipment, adjust burner for:
a. 12% ( ¼%) CO2 for No. 2 fuel oil, 0 smoke.
b. 9 – 10% CO2 natural gas; CO in ue gas not to exceed 50 ppm
(0.01%).
c. Flue gas temperature no lower than 330°F
On some applications, if draft conditions or burner char-
acteristics cause the burner ame pattern to impinge on
the combustion chamber wall, you may notice pinging
sounds from the boiler. Adjust the burner if possible to
redirect the ame. If this does not work, contact your
boiler supplier or Weil-McLain to obtain an optional
combustion chamber kit (see page 38 for contents).
8. Drain boiler.
9. While boiler is warm, but not hot, ush all inte-
rior surfaces under full pressure until drain water
runs clear.
5. Adjust ue collar damper (Figure 49) to ensure 0.1" W.C. positive
pressure at test opening.
6. Tighten screws to secure in position.
10. Remove skim piping.
7. Plug test opening with 1/8" plug provided with ue collar/damper
assembly.
11. Re-insert plug at boiler skim tapping.
12. Close drain cock.
8. Adjust barometric draft control, when used, to design condi-
tions.
13. Fill with fresh water to normal water line.
9. Repeat steps 4 through 6. Adjust as required.
14. Start burner and steam for 15 minutes to remove
dissolved gases.
Skim steam boilers:
15. Stop burner.
16. Check traps and air vents for proper operation.
Clean all newly installed steam boilers to remove oil.
Failure to properly clean can result in violent water level
uctuations, water passing into steam mains, or high
maintenance costs on strainers, traps and vents. Skim
boiler only. Do not clean old piping or leaks can occur.
Check boiler for gas-tight seal:
Boiler must be sealed gas-tight to prevent
possible flue gas leakage and carbon
monoxide emissions, resulting in severe
personal injury or death.
Do not use petroleum-based cleaning or sealing com-
pounds in boiler system. Severe damage to system
components can result, causing substantial property
damage.
1. Remove boiler jacket side and top panels.
1. Remove 2" plug from skim tapping tapping "A" (see Fig-
The boiler contains ceramic fiber and
fiberglass materials. Use care when han-
dling these materials per instructions on
page 38 of this manual. Failure to comply
could result in severe personal injury.
ure 38, page 27).
2. Provide 2" skim piping from tapping to oor drain.
3. Raise waterline to midpoint of skim piping.
4. Fire burner to maintain temperature below steaming rate during
skimming process.
2. Start burner. Observe all sealing points and chalk
mark any not gas-tight.
5. Feed in water to maintain water level.
3. To seal all chalk-marked areas:
6. Cycle burner ON/OFF as needed to prevent rise in steam pres-
sure.
a. Use silicone sealant on section ueways.
b. Check gaskets and sealing rope placement.
4. Reinstall all jacket panels.
7. Continue skimming until discharge is clear. This may take several
hours.
Part No. 550-100-068/0308
33
Weil-McLain 88 Water and steam boilers — Series 2 — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
Handling ceramic fiber and fiberglass materials
REMOVAL OF FRONT PLATE OR CLEANOUT PLATE MATERIALS
The burner front plate and cleanout plate gaskets contain ceramic fiber materials. Ceramic fibers can be
converted to cristobalite in very high temperature applications. The International Agency for Research
on Cancer (IARC) has concluded, "Crystalline silica inhaled in the form of quartz or cristobalite from
occupational sources is carcinogenic to humans (Group 1).":
■
Avoid breathing dust and contact with skin and eyes.
•
Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA re-
quirements for cristobalite at the time this document was written. Other types of respirators
may be needed depending on the job site conditions. Current NIOSH recommendations can be
respirators, manufacturers, and phone numbers are also listed on this web site.
•
Wear long-sleeved, loose fitting clothing, gloves, and eye protection.
■
■
■
Apply enough water to the combustion chamber lining or base insulation to prevent airborne
dust.
Remove combustion chamber lining or base insulation from the boiler and place it in a plastic bag
for disposal.
Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer thor-
oughly.
NIOSH stated First Aid.
■
Eye: Irrigate immediately.
Breathing: Fresh air.
■
REMOVAL OR INSTALLATION OF FIBERGLASS WOOL:
This product contains fiberglass jacket insulation and ceramic fiber materials in jacket insulation, burner
front plate insulation and cleanout plate gaskets. Airborne fibers from these materials have been listed
by the State of California as a possible cause of cancer through inhalation.
■
Avoid breathing dust and contact with skin and eyes.
•
Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA
requirements for fiberglass wool at the time this document was written. Other types of respira-
tors may be needed depending on the job site conditions. Current NIOSH recommendations
approved respirators, manufacturers, and phone numbers are also listed on this web site.
•
Wear long-sleeved, loose fitting clothing, gloves, and eye protection.
■
■
Operations such as sawing, blowing, tear out, and spraying may generate airborne fiber concentra-
tion requiring additional protection.
Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer thor-
oughly.
NIOSH stated First Aid.
■
■
Eye: Irrigate immediately.
Breathing: Fresh air.
34
Part No. 550-100-068/0308
Boiler manual:
• Installation • Start-Up • Maintenance • Parts
Ratings
Boiler
model
number
I=B=R
burner
capacity
Gross
I=B=R
output
Net I=B=R ratings
Boiler Combustion
H.P.
Thermal
efficiency
Net
firebox
Flue
gas
Positive Flue
pressure outlet
Boiler Packaged
water boiler
efficiency
volume volume in firebox diameter content weight
Light oil Gas
GPH
MBH Steam Steam Water
Sq. Ft MBH
Oil
Gas
Oil
Gas
Cubic
feet
CFM
Inches
W.C.
Inches Gallons Pounds
MBH
MBH
Notes:
1, 10
2, 3
2, 4
5, 6
8
8
8
—
—
—
—
—
—
7
9
—
—
—
488R
488
6.9
7.0
996
827
839
2,583
2,621
620
629
845
719
730
979
24.7
25.1
33.6
87.5
87.5
87.0
86.7
86.5
86.3
86.2
86.2
86.2
86.2
86.1
86.0
84.8
84.8
84.4
84.1
83.9
83.7
83.7
83.7
83.6
83.6
83.5
83.5
84.4
83.4
83.3
83.3
83.3
83.3
83.3
85.6
85.6
85.6
85.6
85.6
85.6
85.6
85.6
85.6
85.6
85.7
85.7
85.7
85.7
85.7
85.7
85.7
85.7
85.7
83.1
83.1
83.1
83.1
83.1
83.1
83.1
83.1
83.1
83.1
83.1
83.1
83.1
83.1
83.1
83.1
83.1
83.1
83.1
11.02
11.02
14.45
18.08
21.61
25.14
28.67
28.67
32.20
32.20
35.76
39.26
42.79
46.32
49.85
53.38
53.38
56.91
60.44
376
370
0.60
0.60
0.63
0.65
0.67
0.69
0.70
0.70
0.71
0.71
0.72
0.73
0.74
0.75
0.76
0.77
0.78
0.79
0.80
10
10
10
10
12
12
14
14
14
14
14
14
14
16
16
16
16
18 *
18 *
109
109
132
155
178
201
224
224
247
247
270
293
316
339
362
385
385
408
431
2860
2860
3340
3820
4345
4925
5600
5600
6130
6130
6695
7260
7890
8410
9005
9525
9525
9780
10775
1,010
1,356
1,701
2,046
2,382
2,482
2,737
2,887
3,082
3,428
3,773
4,119
4,464
4,809
4,979
5,155
5,494
5,845
588
9.4
1,126 3,521
507
688
11.8
14.2
16.6
17.2
18.8
1,413 4,469 1,072 1,229 42.2
1,700 5,463 1,311 1,478 50.8
1,987 6,427 1,543 1,728 59.4
2,062 6,671 1,601 1,793 61.6
2,274 7,358 1,766 1,977 67.9
2,399 7,763 1,863 2,086 71.7
2,561 8,283 1,988 2,227 76.5
2,848 9,213 2,211 2,477 85.1
3,135 10,147 2,434 2,726 93.7
639
788
772
888
906
988R
988
1,031
954
1088R 20.0
1,184
1,101
1,299
1,443
1,588
1,735
1,854
2,003
1,945
2,152
2,303
1088
1188
1288
1388
1488
1588
21.5
23.5
26.0
28.5
31.0
33.0
3,422 11,071 2,657 2,976 102.2 86.0
3,709 12,000 2,880 3,225 110.8 86.0
3,996 12,925 3,102 3,475 119.4 85.9
4,137 13,383 3,212 3,597 123.6 85.9
4,283 13,854 3,325 3,724 127.9 85.9
4,570 14,783 3,548 3,974 136.5 85.9
4,857 15,713 3,771 4,123 145.1 85.9
1688R 34.5
1688
1788
1888
35.5
38.0
40.5
5. Gross I=B=R ratings have been determined under the I=B=R provision
governing forced draft boiler-burner units.
1. See below to specify complete model number.
6. Based on average water temperature of 170°F in heat distributing
units.
7. Flue gas volume at outlet temperature.
8. Net I=B=R ratings are based on net installed radiation of sufficient
quantity for the requirements of the building.
Nothing need be added for normal piping and pick-up.
Water ratings are based on a piping and pick-up allowance of 1.15.
Steam ratings are based on the following allowances: 488 – 588 =
1.333; 688 = 1.323; 788 = 1.301; 888 = 1.289; 988 – 1888 = 1.288.
An additional allowance should be made for gravity hot water systems
or for unusual piping and pick-up loads.
2. Burner input based on maximum of 2,000 feet altitude. For other
altitudes, consult Weil-McLain distributor/agent or sales office.
Consult local Weil-McLain distributor/agent or sales office.
3. No. 2 fuel oil — Commercial Standard Spec CS75-56. Heating
value of oil = 140,000 Btu per gallon.
9. With 0.10" W.C. positive pressure at flue collar.
10. Water boilers tested for 80 PSIG, ASME water working pressure.
Steam boilers tested for 15 PSIG, ASME steam working pressure.
4. Gas pressure required at burner gas train inlet for rated burner
input; based on 1,000 Btu per cubic foot natural gas, specific
gravity of 0.60. Refer to burner manual for required pressure.
*
Flue collar connection is oval, 16Z\," x 19M\,"
Part No. 550-100-068/0308
35
Weil-McLain 88 Water and steam boilers — Series 2 — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
Dimensions
Dimensions (inches)
Model
A
B
C
D
E
L
W
H
488
588
23
31
—
—
—
—
10
10
10
12
12
14
14
14
14
14
16
16
16
54¾
54¾
54¾
53¾
53¾
52¾
52¾
52¾
52¾
52¾
51¾
51¾
51¾
51¾
51¾
34¾
42¾
30
38
23C\,
31C\,
39C\,
47C\,
55C\,
63C\,
71C\,
79C\,
87C\,
95C\,
103C\,
111C\,
119C\,
127C\,
135C\,
688
39
—
—
50¾
46
788
47
—
—
58¾
54
888
55
—
—
66¾
62
988
63
—
—
74¾
70
1088
1188
1288
1388
1488
1588
1688
1788
1888
71
—
—
82¾
78
79
—
—
90¾
86
87
39½
47½
55½
63½
47½
31½
39½
—
98¾
94
95
—
106¾
114¾
122¾
130¾
138¾
146¾
102
110
118
126
134
142
103
111
119
127
135
—
—
—
79½
87½
16Z\," x 19M\,"
oval
Model
Supply & return tappings
Burner lengths (Dimension F)
Supply tappings (No. & size) Return tappings (No. & size)
Carlin
Riello
Power-
Flame
Beckett
Oil
Beckett
Gas
Steam
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
3 – 5"
3 – 5"
3 – 5"
3 – 5"
3 – 5"
3 – 5"
4 – 5"
4 – 5"
Water
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
2 – 5"
Steam
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
Water
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
1 – 6"
488R
488
21
21
21
21
21
21
21
26
26
26
26
26
26
26
—
—
—
—
—
33
33
33
33
33
49
49
49
49
49
49
49
49
49
49
49
49
49
56
31
31
31
34
34
34
34
34
34
34
39
39
39
39
39
39
39
44
44
21
21
21
22
22
22
22
22
22
22
23
23
23
—
—
—
—
—
—
29
30
30
30
30
30
30
30
30
30
30
30
30
30
—
—
—
—
—
588
688
788
888
988R
988
1088R
1088
1188
1288
1388
1488
1588
1688R
1688
1788
1888
36
Part No. 550-100-068/0308
Boiler manual:
• Installation • Start-Up • Maintenance • Parts
(continued)
Dimensions
Figure 50 Dimensions (see lettered dimensions on opposite page)
Part No. 550-100-068/0308
37
Weil-McLain 88 Water and steam boilers — Series 2 — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
Parts
Item
Description
Part number
1
2
Front sections (8823)
316-301-210
316-301-212
Regular intermediate section (8825)
3
Tankless intermediate section (8826)
316-301-214
4
Back section (8828)
316-301-211
—
—
5
Supply intermediate section (8824) (not shown)
Section replacement kit (includes rope seals, rope adhesive and sealant for one joint)
Burner mounting plate
316-301-213
386-300-213
Order for specific burner
590-735-140
6 & 13
7
Sealing rope — ½" (13 feet per joint, 7 feet for burner plate, 6 feet for flue collar)
Tankless heater, when used, number 820
Heater gasket
590-291-909
8
590-317-579
9
Heater cover plate
450-030-934
10
11
12
Draw rod 5/8"-11UNC-2A x 13" (apply to front and rear sections)
Draw rod 5/8"-11UNC-2A x 11" (apply between intermediate sections)
560-134-505
560-134-495
Draft hood collar assembly
(includes damper collar, damper, damper quadrant, locking plate, swivel, brackets and rope)
a. 10-inch — 488 through 688. . . . . . . . . . . . . . . . . . . . .
340-004-606
340-004-607
340-004-608
340-004-609
340-004-612
330-056-634
460-003-646
563-530-784
b. 12-inch — 788 and 888 . . . . . . . . . . . . . . . . . . . . . . .
c. 14-inch — 988 through 1388 . . . . . . . . . . . . . . . . . . . .
d. 16-inch — 1488 through 1688 . . . . . . . . . . . . . . . . . . .
e. 18-inch — 1788 and 1888 . . . . . . . . . . . . . . . . . . . . .
f. Quadrant for flue collar . . . . . . . . . . . . . . . . . . . . . . .
g. Damper blade . . . . . . . . . . . . . . . . . . . . . . . . . . . .
h. Damper locking plate . . . . . . . . . . . . . . . . . . . . . . . .
14
15
Cleanout plate
450-030-965
590-317-305
Woven fiberglass gasket for cleanout plate
16 & 18
Observation port assembly (includes frame, rope, gasket, plugs and sight glass)
383-600-099
591-419-199
590-317-580
a. Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
b. Sight glass only . . . . . . . . . . . . . . . . . . . . . . . . . . .
c. Washer gasket for sight glass (2Z\, x 1Z\v x Z\, inches) . . . . . . . .
17
19
20
21
22
23
24
25
26
27
28
29
30
Sealing rope, C\," (1 foot per observation port)
590-317-150
Obtain locally
Obtain locally
Obtain locally
Obtain locally
Obtain locally
Obtain locally
Obtain locally
Obtain locally
Obtain locally
Obtain locally
Obtain locally
Burner mounting plate studs (½ x 3½ inches)
Cleanout plate nut, ¼"
Cap screw, ½–13 x ¾"
Observation port screw, 10–32 x 1½"
Flue collar cap screw, ½" x 1½"
Flue collar washer, ZZ\zn"
Burner mounting plate washer, ½"
Burner mounting plate nut, ½"
Draw rod nut, B\,"
Cleanout plate washer, ¼"
Cleanout plate carriage bolt, ¼" x 1¾"
HXT-bars (see Figure 12, page 12, for installation and placement details for HXT-bars)
d. 3-flueway kit (includes 3 sets of bars)
416-400-130
416-400-131
e. 2-flueway kit (includes 2 sets of bars)
Not shown
Combustion chamber liner kit (optional) — includes ceramic fiber blanket for left side wall plus water glass adhesive — see
page 33. Consult your local Weil-McLain sales office for details.
Contact local Weil-McLain
sales office
38
Part No. 550-100-068/0308
Boiler manual:
• Installation • Start-Up • Maintenance • Parts
(continued)
Parts
Figure 51 Parts
Part No. 550-100-068/0308
39
Weil-McLain 88 Water and steam boilers — Series 2 — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
Warranty
April 1, 2003
Weil-McLain Limited Warranties
Residential & Commercial Cast Iron Boilers
Residential Water Warranty — Limited Lifetime
Residential Steam Warranty — Limited 10 Year
Commercial Warranty — Limited 10 Year
Indirect-Fired Water Heaters
Residential Water Heater Warranty — Limited Lifetime
Commercial Water Heater Warranty — Limited 15 Year
First Year — (Residential and Commercial Water Heaters) Weil-McLain warrants
that its indirect-fired water heaters are free from defects in material and workmanship
for one year from the date of installation. If any parts are found to be defective from
such defects, Weil-McLain will provide replacement of such defective parts.
Second Year and Beyond — (Residential Only)
First Year — (All Residential & Commercial Cast Iron Boilers) Weil-McLain
warrants that its cast iron boilers are free from defects in material and workman-
ship for one year from date of installation. If any parts are found to be defective
from such defects, Weil-McLain will provide replacement of such defective parts.
Second Through Tenth Year — (Residential & Commercial Water/Steam)
Weil-McLain warrants that the cast iron sections of its water and steam boilers are
free from defects in material and workmanship from the date of installation for the
second through the tenth year. If, during such time, any section is found to be
defective, Weil-McLain will provide replacement of such defective section(s).
Eleventh Year and Beyond — (Residential Water Only) Weil-McLain warrants
that the cast iron sections of its residential water boilers are free from defects in
material and workmanship for the eleventh year and beyond from the date of
installation. If, during such time period, any section(s) is found to be defective,
Weil-McLain will provide replacement of such defective section(s) upon the
payment of a proportionate charge based on the time the boiler has been in
service. The proportionate charge will be equal to the appropriate percentage of
the list price of such section(s) at the time the warranty claim is made, and will be
determined as follows: 11th year-5%; 12th year-10%; 13th year-15%; 14th year-
20%; 15th year-25%; 16th year-30%; 17th year-35%; 18th year-40%; 19th year-
45%; 20th year-50%; 21st year-55%; 22nd year-60%; 23rd year-65%; 24th year-
70%; 25th year & beyond -75%.
Second Through Fifth Years — (Commercial Only)
Weil-McLain warrants that the tank assembly components of its indirect-fired water
heaters are free from defects in material and workmanship for the second through
the fifth year from the date of installation (commercial only), or for the second year
from the date of installation and beyond (for residential only). If, during such time
periods, a leak in the tank assembly should occur, Weil-McLain will provide replace-
ment for the original tank assembly.
Sixth Year through Fifteenth Year — (Commercial Only) Weil-McLain warrants
that the tank assembly components of its commercial indirect-fired water heaters are
free from defects in material and workmanship for the sixth year through the fifteenth
year following the date of installation. If, during such time period, a leak in the tank
assembly should occur, Weil-McLain will provide replacement for such defective tank
assembly. Such replacement will be furnished with the nearest comparable model
available from Weil-McLain at the time of such replacement and upon payment of a
proportionate charge. Proportionate charges will be equal to the appropriate percent-
age of the current list price of such commercial indirect-fired water heater at the time
warranty claim is made and will be determined as follows: 6th & 7th year-55%; 8th &
9th year-60%; 10th & 11th year-65%; 12th & 13th year-70%; 14th & 15th year-75%.
These warranties do not cover boilers operated with combustion air contam-
inated externally by chemical vapors or with improper fuel additives, or with water
conditions which may have caused unusual deposits in the cast iron sections.
See section “For all Weil-McLain Products” for additional warranty information.
These warranties do not cover:
1. Any water heater not initially installed with a new temperature-pressure relief valve
bearing the listing of the American Society of Mechanical Engineers (A.S.M.E.) at the
time of the water heater installation.
Weil-McLain Ultra Cast Aluminum Boilers
2. Any water heater that has a failure or malfunction resulting from a.) failure to keep the
tank full of potable water; b.) failure to assure that water in the tank is free to circulate
at all times; or c.) failure to keep the tank free of water sediment or scale deposits.
3. Any water heater that has potable water in the unit with a chloride or chlorine content
higher than 80 mg/liter.
4. Any water heater installed in a residence containing any type of water softener system
that is not installed and maintained in accordance with manufacturer’s specifications.
5. Any water heater installation where non-metallic piping products without an oxygen
barrier are used.
Residential Warranty — Limited 15 Year (includes 5-Year Ultra Protection Plan)
Commercial Warranty — Limited 15 Year (does NOT include Ultra HPP)
First Through Fifth Year — Weil-McLain warrants that its cast aluminum boilers
are free from defects in material and workmanship for one year from the date of
installation and the heat exchanger is free from defects in material and
workmanship for five years from the date of installation. If any parts in the first
year, or the heat exchanger in the first five years are found to be defective from
such defects, Weil-McLain will provide replacement of such defective parts or heat
6. Any water heater used for non-potable application such as pool or process heating.
See section “For all Weil-McLain Products” for additional warranty information.
exchanger. In addition to the product warranty, Weil-McLain will provide a 5-Year “Ultra”
Homeowner Protection Plan (“UHPP”) for residential applications only to cover parts and labor
for five years from the date of installation provided only if the Ultra boiler is properly registered
with the UHPP Administrator within one month of the date of installation. UHPP claims must be
processed directly through thePlan Administrator and not through Weil-McLain.
Sixth Through Tenth Year — Weil-McLain warrants that the heat exchangers of
its cast aluminum boilers are free from defects in material and workmanship for
the sixth through the tenth year from the date of installation. If, during such time,
the heat exchanger is found to be defective, Weil-McLain will provide replacement
of such defective heat exchanger.
Radiant Heating Products
Radiant Heating Products Warranty — Limited 30 Year
IPP & IPC Products Warranty — Limited 3 Year
Weil-McLain warrants that its AlumiPex and Qual-Pex radiant heating products are
free from defects in material and workmanship for thirty years (three years for IPP
and IPC products) from the date of installation. If any parts are found to be defective
from such defects during such time period, Weil-McLain will provide replacement of
such defective parts. It is expressly understood that failure as a result of freezing of
Eleventh Through Fifteenth Year
—
Weil-McLain warrants that the heat
water within the pipes (tubing) does not constitute
workmanship and shall not be covered by this warranty.
See section “For all Weil-McLain Products” for additional warranty information.
a
defect in material or
exchangers of its cast aluminum boilers are free from defects in material and
workmanship for the eleventh through fifteenth year from the date of installation.
If, during such time period, the heat exchanger is found to be defective, Weil-
McLain will provide replacement for such defective heat exchanger upon the
payment of a proportionate charge based on the time the boiler has been in
service. The proportionate charge will be equal to the appropriate percentage of
the list price of such heat exchanger at the time the warranty claim is made, and
will be determined as follows: 11th year - 10%; 12th year - 20%; 13th year -
40%; 14th year - 60%; 15th year - 80%; 16th year & beyond - 100%.
Parts and Accessories
Parts and Accessories Warranty — Limited 1 Year
Weil-McLain warrants that parts and accessories that were purchased through Weil-
McLain are free from defects in material and workmanship for one year from the date
of installation. If any parts and/or accessories are found to be defective from such
defects during such time period, Weil-McLain will provide replacement of such
defective parts. Parts and accessories covered under this warranty include only
those items that are not covered under other Weil-McLain product warranties.
See section “For all Weil-McLain Products” for additional warranty information.
This warranty does not cover boilers operated with combustion air contaminated
externally by chemical vapors or with improper fuel additives, or with water/
system conditions which may have caused heat exchanger failure.
See section “For all Weil-McLain Products” for additional warranty information.
For All Weil-McLain Products: These warranties are subject to the condition
that the Weil-McLain Product(s) must have been installed in accordance with
manufacturers’ instructions by a heating contractor whose principal occupation is
the sale and installation of plumbing, heating and/or air conditioning equipment.
These warranties extend only to the first retail purchaser of the products and only
to a product that has not been moved from its original installation site.
In addition to each product warranty listed, Weil-McLain warranties do not cover:
1. Components that are part of the heating system (products) but were not fur-
nished by Weil-McLain as a part of the heating system (products).
2. The workmanship of any installer of Weil-McLain’s product(s). In addition, this
warranty does not assume any liability of any nature for unsatisfactory perform-
ance caused by improper installation.
3. Any costs for labor for removal and reinstallation of the alleged defective part,
transportation to Weil-McLain, if necessary, and any other materials necessary
to perform the exchange.
4. Any products that have a failure or malfunction resulting from improper or
negligent operation, accident, abuse, freezing, misuse, unauthorized alteration
or improper repair or maintenance.
NOTE: Residential warranties do not cover any residential products installed in build-
ings other than one or two family dwelling units, unless they are buildings with indi-
vidual residential products for each dwelling unit.
THE WARRANTIES DESCRIBED HEREIN ARE IN LIEU OF ALL OTHER WAR-
RANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IM-
PLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE AND MER-
CHANTABILITY. WEIL-McLAIN EXPRESSLY DISCLAIMS AND EXCLUDES ANY
LIABILITY FOR CONSEQUENTIAL, INCIDENTAL, INDIRECT OR PUNITIVE DAM-
AGES FOR BREACH OF ANY EXPRESS WARRANTY. For prompt product war-
ranty claims, notify the installer who, in turn, will notify the Weil-McLain distributor
from whom he purchased the boiler. If this action does not result in warranty resolu-
tion, contact Weil-McLain Consumer Relations Department, 500 Blaine Street, Michi-
gan City, Indiana 46360, with details in support of the warranty claim. Alleged defec-
tive part or parts must be returned through the same trade channel in accordance
with the Weil-McLain procedure currently in force for handling returned goods for the
purpose of inspection to determine cause of failure. Weil-McLain will furnish new
part(s) to an authorized Weil-McLain distributor who, in turn will furnish the new part
(s) to the heating contractor who installed the boiler. If you have any questions about
the coverage of this warranty, contact Weil-McLain at the address above.
5. Improper adjustments (including boiler/burner), control settings, care or mainte-
nance. Information is in the installation, start-up, operations, owner/user’s
manuals, service/maintenance instructions, and other printed/technical informa-
tion provided with the product or direct from Weil-McLain or weil-mclain.com.
Part No. 550-141-950/0403
40
Part No. 550-100-068/0308
|