Smith Cast Iron Boilers GB200 SERIES User Manual

GB200-IM-5  
42-9184  
GB200 SERIES  
INSTALLATION, OPERATION  
& MAINTENANCE MANUAL  
WITH REPLACEMENT  
PARTS LIST  
GAS-FIRED STEAM  
CAST IRON BOILERS  
85,000 TO 165,000 BTUH INPUT  
INTERMITTENT PILOT/VENT DAMPER  
& STANDING PILOT/VENT DAMPER  
TABLE OF CONTENTS  
SECTION 1: INTRODUCTION  
Step 6: Wiring Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
SECTION 3: START-UP & OPERATION  
Sequence Of Operation . . . . . . . . . . . . . . . . . . . . . . . . .11  
Prior To Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11  
Start-Up & Adjustments . . . . . . . . . . . . . . . . . . . . . . . . .11  
Code Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2  
Venting Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . .2  
Chimney Requirements . . . . . . . . . . . . . . . . . . . . . . . . . .3  
Combustion Air Requirements . . . . . . . . . . . . . . . . . . . . .3  
Water Treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
Shipment of Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
SECTION 4: MAINTENANCE  
Before Each Heating Season . . . . . . . . . . . . . . . . . . . . .14  
Steam Boiler Cleaning Instructions . . . . . . . . . . . . . . . . .15  
How To Change Orifices . . . . . . . . . . . . . . . . . . . . . . . . .15  
Heating System Problems & Causes . . . . . . . . . . . . . . .15  
REPLACEMENT PARTS . . . . . . . . . . . . . . . . . . . . . .16-17  
SECTION 2: BOILER INSTALLATION  
Step 1: Locating/Setting Boiler . . . . . . . . . . . . . . . . . . . . .4  
Step 2: Installing Steam Piping . . . . . . . . . . . . . . . . . . . .5  
Step 3: Installing Hydronic Components . . . . . . . . . . . . .5  
Step 4: Venting Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . .6  
Step 5: Installing/Testing Gas Piping . . . . . . . . . . . . . . . . .7  
WARNINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20  
WESTCAST, INC.  
260 NORTH ELM STREET WESTFIELD, MA 01085  
TEL. (413) 562-9631 FAX (413) 562-3799  
CHIMNEY REQUIREMENTS  
NOTE: Boiler employs atmospheric combustion. Com-  
bustion air must not be contaminated with halogenated  
hydrocarbon vapors, aerosol propellants or freon. Other-  
wise, boiler heat exchanger will be subject to corrosion,  
reducing boiler life.  
DANGER: A chimney which does not meet modern  
safety standards will result in a fire or deadly carbon  
monoxide poisoning of the building residents.  
Chimney condition is of paramount importance for a safe and  
efficient boiler installation. All new and replacement installa-  
tions must include a chimney inspection by a qualified indi-  
vidual or agency. Chimney construction materials must be  
compatible with the fuel being used.  
WATER TREATMENT  
Water treatment is recommended in areas where water quali-  
ty is a problem. A local water treatment company should be  
consulted to determine the requirements for your particular  
system and locality.  
Particular attention should be paid on all oil-to-gas conver-  
sions. Soot may have accumulated in chimney and/or  
degraded chimney liner. Most utilities require complete chim-  
ney cleaning. Others may require installation of new liner,  
spill switches or other chimney upgrades. Check with local  
utility for required safety precautions.  
NOTE: Boiler is not for use in systems where water is  
replenished. Minerals in the water can build up on the  
heat transfer surfaces and cause overheating and subse-  
quent failure of the heat exchanger.  
NOTE: Boiler utilizes synthetic rubber seals. Water treat-  
ment chemicals and system cleaning chemicals must be  
compatible with this and all other construction materials.  
COMBUSTION AIR REQUIREMENTS  
Provisions for combustion air must be in accordance with the  
National Fuel Gas Code ANSI Z223.1 - latest edition, as well  
as all applicable local codes. If the boiler is installed in an  
unconfined space, adequate air will be available via normal  
infiltration. However, if building construction is unusually tight  
or the boiler is installed in a confined space (a space whose  
volume is less than 50 cubic feet per 1000 Btu/hr of gas input  
for all fuel burning equipment), adequate air for combustion  
must be provided by two openings: one located about 6”  
below the ceiling, the other about 6” above the floor. When  
communicating directly with the outside or through a vertical  
duct, each opening must have a minimum free area of one  
square inch per 4000 Btu/hr of gas input. Horizontal ducts to  
the outside must have a minimum free area of one square  
inch per 2000 Btu/hr of gas input. When ventilation is provid-  
ed by openings in doors, etc. to adjoining spaces having ade-  
quate infiltration, each opening must have a minimum free  
area of one square inch per 1000 Btu/hr of gas input.  
SHIPMENT OF BOILER  
Each boiler is shipped in a single carton.  
Optional Vent Damper  
When ordered, the vent damper is shipped in an individual  
carton packaged with the boiler. Mounting of the damper and  
flue outlet extension are required.  
WARNING: Adequate fresh air must be provided for  
combustion. Improper boiler operation and inade-  
quate venting of deadly flue gases may otherwise  
result.  
3
SECTION 2: BOILER INSTALLATION  
STEP 1: LOCATING/SETTING BOILER  
Remove all packing material from boiler. Check that burners,  
Boiler may be installed in an alcove (see dimensions in Fig-  
ure 2.1). Locate boiler so connecting flue pipe between draft  
hood and chimney is as short as possible.  
draft diverter and controls are in proper position.  
Boiler shall be installed such that the gas ignition system  
components are protected from water (dripping, spraying,  
rain, etc.) during appliance operation and service (low water  
cut-off repacement, condensate trap replacement, control  
replacement).  
Observe the following minimum clearances to combustibles:  
18" on sides...alcove at front...28" at top...18" at rear...6" from  
flue pipe in any direction. Maintain a minimum 1” clearance  
between hot water piping and combustible materials. Local  
code requirements may specify greater clearances and must  
be adhered to.  
NOTE: Do not loosen tie rods on boiler absorption unit.  
They are intended to accommodate thermal expansion.  
Loss of boiler's structural integrity and water leaks/dam-  
age may result.  
Remove boiler from carton and set it in position. Install on  
non-combustible floor only, unless local codes permit use  
and fabrication of a fireproof base (see Figure 2.2).  
WARNING: Never install boiler on carpeting as heat  
damage and/or fire may result.  
FIGURE 2.1: MODEL GB200 BOILER DIMENSIONS  
MINIMUM CLEARANCES  
TO COMBUSTIBLES  
DIMENSIONS  
BOILER  
MODEL  
A
B
Top:  
28"  
18"  
GB200-S-3  
GB200-S-4L  
GB200-S-4H  
GB200-S-5  
15 3/8"  
18 7/8"  
18 7/8"  
22 3/8"  
5"  
6"  
6"  
7"  
Rear:  
Left & Right: 18"  
Front: ALCOVE  
PRESS.  
RELIEF VALVE  
B
PRESSURE CONTROL  
PRESS.  
GAUGE  
SPILL SWITCH  
9 7/8"  
3"  
2" STEAM  
SUPPLY  
3/4" PLUGGED  
TAPPING  
LOW  
WATER  
CUT-OFF  
WATER  
LEVEL  
INDICATOR  
WATER  
LINE  
41"  
2 1/2"  
2" RETURN  
REAR  
1/2"  
PLUGGED  
TAPPING  
GAS  
VALVE  
ROLLOUT SWITCH  
26 7/8"  
23 1/4"  
18 1/4"  
23 7/8"  
23 1/4"  
21"  
20"  
14 3/4"  
14 3/4"  
3 3/8"  
2 3/8"  
16 1/2"  
18 1/8"  
21 7/8"  
2 1/2"  
2" RETURN  
FRONT  
18 1/8"  
6 3/4"  
A
-LEFT SIDE VIEW-  
PROBE LOCATION FOR ELECTRIC LWCO.  
-FRONT VIEW-  
-RIGHT SIDE VIEW-  
NOTE: OPTIONAL FLOAT LOW WATER CUT-OFF SHOWN.  
4
FIGURE 2.2: RECOMMENDED FIREPROOF BASE  
The supply and return lines should be equipped with drain  
cocks to drain sediment and sludge from lowest points of  
boiler.  
STEP 3: INSTALLING HYDRONIC COMPONENTS  
A low-water cutoff must be installed to protect the unit from  
dry fire.  
6" OVERHANG OF BLOCKS  
AND SHEETMETAL ALL  
AROUND  
4" HOLLOW CLAY  
6"  
Screw extension nipple into 3/4" tapping on top of the  
absorption unit and install relief valve into top of nipple with  
the spindle in the vertical position (i.e., with the valve dis-  
charge in the horizontal).  
TILE (TWO COURSES)  
OPENINGS THRU BLOCKS  
IN TOP COURSE TO  
BE AT 90° ANGLE  
TO OPENINGS THRU  
22 GAUGE  
SHEETMETAL  
BOTTOM COURSE  
WARNING: Never install any type of valve between  
the boiler and the relief valve or an explosion causing  
extensive property damage, severe personal injury or  
death may occur!  
Most localities require the discharge piping to terminate with-  
in 6" of the floor. Check local code requirements if in doubt.  
Discharge piping must be of same size or larger than the  
relief valve outlet and should be run as short and straight as  
possible. Elbows in the discharge piping should be placed as  
close to the valve as possible. If valve discharge is to be  
drained away, the discharge piping must not be hard-piped to  
the drain piping (i.e., an open funnel or similar arrangement  
must be used).  
FLOOR  
STEP 2: INSTALLING STEAM PIPING  
Typical piping connections are shown in Figure 2.3. All exter-  
nal piping must be supported by hangers, not by the boiler or  
its accessories.  
Supply outlet must run full size from the boiler to a header at  
least 24" above top of boiler. Condensate return piping  
should be connected to boiler through a "Hartford Loop."  
Install gate valves in supply and return.  
CAUTION: Piping must be installed from the relief valve  
discharge so there will be no danger of scalding person-  
nel.  
Proper steam piping practices must be followed at all times.  
Maintain proper clearances between piping and combustible  
material.  
FIGURE 2.3: TYPICAL STEAM BOILER PIPING  
STEAM  
SUPPLY  
GATE VALVE  
SUPPLY  
TAPPING  
3" NPT  
12" MIN.  
MUST BE CLOSE  
NIPPLE  
HARTFORD  
LOOP  
WATER LINE  
RETURN  
TAPPING  
2" NPT  
GATE  
VALVE  
C/L OF HARTFORD  
LOOP TO BE 2"  
BELOW WATER  
LINE  
23 1/4"  
DRAIN  
COCKS  
5
STEP 4: VENTING BOILER  
A factory-mounted spill switch is provided on all GB200 boil-  
ers (see Figures 2.4 & 2.4A).  
FIGURE 2.4: VENT DAMPER INSTALLATION  
FOR INTERMITTENT PILOT  
VENT DAMPER  
DANGER: Draft diverter, vent outlet and vent damper  
as supplied must not be altered in any way, as proper  
boiler operation would be jeopardized. Flame rollout,  
fire or carbon monoxide poisoning will result.  
PRESSURE  
CONTROL  
SPILL  
SWITCH  
THERMOSTAT  
CONNECTION  
The flue or vent connectors must be installed flush with the  
inside chimney liner surface and sealed in place with furnace  
cement. Horizontal positions of the single wall and type B  
venting systems shall be supported by use of strap hangers  
or their equivalent. Vent supports should be placed a maxi-  
mum of 15 feet apart and as required to prevent sagging.  
The vent connectors shall be pitched 1/4" per foot upwards  
towards the chimney or vent termination.  
CABLE  
BRACKET  
TRANSFORMER  
Installing Vent Damper  
PILOT  
CONTROL  
DANGER: Only the boiler may be served by the vent  
damper. Do not attempt to use it to vent an addition-  
al appliance. This will cause fire or carbon monoxide  
poisoning.  
THERMOSTAT  
CONNECTION  
The vent damper must be mounted directly on top of the draft  
diverter. The vent outlet extension must be installed between  
the damper and the outlet to allow the damper plate to open  
and close.  
Locate the motor on the front side and position the cable so  
that it does not touch the metal surface of the draft diverter  
(see Figure 2.4). If necessary, turn angle connector on vent  
damper upward until cable clears; tighten locknut to secure.  
The direction of the flow arrow imprinted on the vent damper  
must point upward. The damper position indicator, which is  
located on the side of the vent damper opposite the motor,  
must be visible.  
FIGURE 2.4A: VENT DAMPER INSTALLATION  
FOR STANDING PILOT  
VENT DAMPER  
PRESSURE  
CONTROL  
SPILL  
CAUTION: A minimum of 6" between vent damper and  
combustible materials must be maintained. The vent  
damper must be accessible for servicing and checking  
position indicator.  
SWITCH  
THERMOSTAT  
CONNECTION  
If applicable, remove hairpin shipping clip which holds  
damper blade in closed position and observe that damper  
blade rotates slowly to open position. Do not force it closed  
as it may damage the gear train and void the warranty. The  
blade should move freely and without obstruction.  
CABLE  
BRACKET  
TRANSFORMER  
Secure the vent damper housing to the draft diverter outlet  
with sheet metal screws or pop rivets. Refer to Figure 2.5 for  
fastener locations. Install flue pipe over top of vent damper  
and secure to damper housing with sheet metal screws or  
pop rivets.  
GAS  
VALVE  
Attach vent damper cable to cable clamp on boiler left panel  
and join the Molex connector (see Figures 2.4 & 2.4A).  
THERMOSTAT  
CONNECTION  
6
ADDITIONAL CHIMNEY REQUIREMENTS  
FIGURE 2.5: ATTACHING VENT DAMPER TO DRAFT  
DIVERTER & FLUE PIPE  
Chimney condition is of paramount importance for a safe and  
efficient boiler installation. All installations must include a  
chimney inspection by a qualified individual or agency. Chim-  
ney construction materials must be compatible with the fuel  
being used (See Figure 2.5A).  
MAKE SURE MOTOR IS  
LOCATED ON FRONT SIDE  
CLOSED OPEN  
FLOW DIRECTION  
Particular attention should be paid on all oil-to-gas conver-  
sions. Soot may have accumulated in chimney and/or  
degraded chimney liner. Most utilities require complete chim-  
ney cleaning. Others may require installation of new liner,  
spill switches or other chimney upgrades. Check with local  
utility for required safety precautions.  
FLOW DIRECTION  
ARROW POINTS UP  
(REAR VIEW)  
DANGER: A chimney which does not meet modern  
safety standards will result in a fire or deadly carbon  
monoxide poisoning of the building residents.  
MOUNT VENT DAMPER  
OVER DRAFT DIVERTER  
INSTALL SWITCH IN  
OPENING  
ON DRAFT DIVERTER  
STEP 5: INSTALLING/TESTING GAS PIPING  
Connect the gas piping from the meter to the boiler using a  
pipe size which will result in a pressure drop of less than 0.3"  
W.C. for natural gas or 0.5" W.C. for propane. See Figure 2.7  
for the appropriate gas pipe sizing and example.  
Good piping practices should be followed at all times. See  
Figure 2.6 for a typical gas piping arrangement. All piping  
must be supported by hangers, not by the boiler or its acces-  
sories.  
FIGURE 2.5A: VENTING  
Install a full-sized sediment trap at the low point in gas line  
upstream of gas valve. Install a non-restrictive lubricated plug  
valve in the gas line close to the boiler. Install a ground joint  
union at the gas valve inlet to allow for servicing. Check local  
codes and utilities for any special requirements and proce-  
dures.  
Pipe joint compound (pipe dope) must be compatible with the  
fuel (natural gas or propane) being used.  
FIGURE 2.6: TYPICAL GAS PIPING  
7
FIGURE 2.7: GAS PIPE SIZING TABLES & EXAMPLE  
Maximum Capacity of Pipe in Cubic Feet of Natural Gas per Hour for Gas Pressures of  
0.5 Psig or Less and a Pressure Drop of 0.3 Inch Water Column  
(Based on a 0.60 Specific Gravity Gas)  
Nominal  
Iron Pipe  
Size,  
Length of Pipe, Feet  
Internal  
Diameter,  
Inches  
90  
100  
125  
175  
150  
200  
10  
20  
30  
40  
50  
60  
70  
80  
Inches  
1/4"  
3/8"  
1/2"  
3/4"  
1"  
1-1/4"  
1-1/2"  
2"  
22  
49  
92  
18  
40  
73  
32  
72  
15  
34  
63  
14  
30  
56  
12  
27  
11  
25  
46  
96  
11  
23  
10  
22  
40  
84  
9
21  
38  
79  
8
18  
34  
72  
130  
275  
410  
8
17  
7
15  
28  
59  
6
14  
26  
55  
.326  
.493  
.622  
.824  
1.049  
1.380  
1.610  
2.067  
2.469  
3.026  
4.026  
132  
50  
43  
31  
278  
520  
1,050  
1,600  
3,050  
4,800  
8,500  
130 115  
245 215  
500 440  
760 670  
105  
90  
170  
350  
530  
990  
64  
120  
250  
380  
710  
190 152  
350 285  
730 590  
1,100 890  
2,100 1,650  
3,300 2,700  
5,900 4,700  
195 180  
400 370  
600 560  
160 150  
320 305  
490 460  
930 870  
110 100  
225 210  
350 320  
650 610  
1,450 1,270 1,150 1,500  
780  
2-1/2"  
3"  
4"  
2,300 2,000 1,850 1,700 1,600 1,500 1,400 1,250 1,130 1,050 980  
4,100 3,600 3,250 3,000 2,800 2,600 2,500 2,200 2,000 1,850 1,700  
8,300 7,400 6,800 6,200 5,800 5,400 5,100  
17,500 12,000  
4,100 3,800 3,500  
4,500  
9,700  
Maximum Capacity of Pipe in Thousands of Btu per Hour of Undiluted Liquefied  
Petroleum Gases (at 11 Inches Water Column Inlet Pressure)  
(Based on a Pressure Drop of 0.5 Inch Water Column)  
Nominal  
Iron Pipe  
Size,  
Length of Pipe, Feet  
90  
100  
125  
150  
10  
20  
30  
40  
50  
60  
70  
80  
Inches  
275  
567  
1071  
189 152  
393 315  
732 590  
129 114  
267 237  
504 448  
103  
96  
89  
185  
346  
724  
83  
78  
69  
146  
275  
567  
866  
63  
132  
252  
511  
787  
1/2"  
3/4"  
1"  
1-1/4"  
1-1/2"  
2"  
217 196  
409 378  
834 771  
173 162  
322 307  
677 630  
2205 1496 1212 1039 937  
3307 2299 1858 1559 1417 1275 1180 1086 1023 967  
6221 4331 3465 2992 2646 2394 2205 2047 1921 1811 1606 1498  
Example: Boiler Model GB200-4H is to be installed. The distance from the existing gas meter to the installation site is 30  
ft. What pipe size must be used? The local utility indicates the heating value of natural gas being supplied is 1000 Btu per  
cu.ft. Determine cubic feet of gas per hour for above boiler model:  
135,000 Btu per hour  
= 135 cu.ft. per hour  
1000 Btu per cu.ft.  
1. Find 30 ft. in upper portion of the table for natural gas under "Length of Pipe, Feet" heading.  
2. Moving down the column, match required capacity. Higher capacity is acceptable. In our case it is 152 cu.ft.  
3. Move to left-hand column "Nominal Iron Pipe Size, Inches," to read required pipe size. In our case it is 3/4".  
Testing Gas Piping  
Minimum pressure required at the gas valve inlet is 5" W.C.  
DANGER: Before placing gas piping into service,  
carefully test it to assure every joint is gas tight. Bub-  
ble test all joints with a soap solution. NEVER TEST  
WITH AN OPEN FLAME AS FIRE OR EXPLOSION  
WILL RESULT.  
for natural gas and 11" W.C. for propane. Maximum pressure  
allowable at the gas valve inlet is 12" W.C. If the gas pres-  
sure is above these limits, a pressure regulator must be  
installed. If the gas pressure is below these limits, contact the  
local utility.  
For any pressure testing in excess of 1/2 psi, the boiler and  
its individual shutoff valve must be isolated from the piping  
system by disconnecting them and capping the outlet(s). For  
any pressure testing equal to or less than 1/2 psi, the boiler  
must be isolated from the piping system by closing its manu-  
al shutoff valve.  
8
STEP 6: WIRING BOILER  
For vent damper-equipped models, connect thermostat  
to blue leads (see Figures 2.4 & 2.4A).  
WARNING: Turn off electrical power supply before  
servicing. Contact with live electric components can  
cause electric shock or death.  
NOTE: If any of original wire supplied with boiler must  
be replaced, use similar wire of 105° C rating. Other-  
wise, insulation may melt or degrade, exposing bare  
wire.  
All electrical and control wiring must be installed in accor-  
dance with the codes listed in Section 1 of this manual. Fol-  
low the wiring diagram for your particular installation as  
shown in Figures 2.8, 2.9, 2.10, and 2.11.  
NOTE: Boiler transformer must not be used to power  
external accessories (i.e., zone valves, relays, etc.) Oth-  
erwise, transformer will be overloaded and burn out.  
FIGURE 2.8: Wiring Diagram & Operation Sequence for  
Boilers Equipped with Intermittent Pilot, Vent Damper  
and M & M #67 Low Water Cut-Off  
FIGURE 2.9: Wiring Diagram & Operation Sequence for  
Boilers Equipped with Standing Pilot, Vent Damper and  
M & M #67 Low Water Cut-Off  
9
FIGURE 2.10: Wiring Diagram & Operation Sequence for  
Boilers Equipped with Intermittent Pilot, Vent Damper  
and 400 Series or M & M PS804 LWCO  
FIGURE 2.11: Wiring Diagram & Operation Sequence for  
Boilers Equipped with Standing Pilot, Vent Damper and  
400 Series or M & M PS804 LWCO  
10  
SECTION 3: START-UP & OPERATION  
SEQUENCE OF OPERATION  
FIGURE 3.1: STEAM CONTROL ARRANGEMENT  
For sequence of operation of the particular boiler being  
installed, refer to Figures 2.8, 2.9, 2.10 and 2.11 in Section 2  
of this manual.  
PRESSURE  
RELIEF VALVE  
PRESSURE  
CONTROL  
Spill and rollout switches are mounted on all GB200 boilers.  
PRESSURE  
GAUGE  
The spill switch detects the escape of combustion products  
through the draft diverter relief opening and interrupts the  
power to the gas valve preventing unsafe boiler operation.  
Escape of flue products could be caused by a blocked or col-  
lapsed chimney or inadequate chimney draft. This is a manu-  
al reset-type device and can be reactivated by depressing  
the spill switch reset button mounted on the left of the boilers  
draft diverter (see Figure 2.1 for switch location).  
PRESSURE RELIEF  
VALVE DISCHARGE  
PIPING  
OPTIONAL  
FLOAT  
LOW WATER  
CUT OFF  
The rollout switch prevents flame rollout from the boiler com-  
bustion chamber, caused by blocked boiler flue passage-  
ways, by interrupting power to the gas valve to prevent  
unsafe boiler operation. This is a manual reset-type device  
and can be reactivated by depressing the rollout switch reset  
button mounted on the lower front jacket panel (see Figure  
2.1 for switch location). Flue passages must be inspected by  
a qualified installer if this problem occurs, prior to switch  
replacement.  
GAS VALVE  
b. Set thermostat to no longer call for heat. Spark should  
stop. Observe that damper position indicator rotates to  
the closed position.  
c. Set thermostat to call for heat.  
WARNING: If boiler cannot be restored to normal  
operation after re-setting of spill switch, or if flame  
rollout switch has tripped, do not attempt to put the  
boiler in operation. Immediately contact a qualified  
service professional.  
3. Light the boiler. For Model GB200 boilers with intermit-  
tent pilot, see lighting instruction on Page 14.  
4. Observe pilot and main burner flame (see Figure 3.2).  
All burner ports should be ignited and burn with a steady  
blue flame.  
PRIOR TO START-UP  
Fill system with water until the water level indicator (sight  
glass) is approximately 2/3 full. This water level is 23" from  
the surface on which the boiler sits.  
CAUTION: Never leave the job with yellow burning  
flames. This condition indicated poor combustion and  
will quickly carbonize the boiler, reducing efficiency and  
boiler life. It may also be an indication of improper vent-  
ing or combustion air supply. If unable to adjust flame  
properly, consult your local utility.  
SYSTEM START-UP & ADJUSTMENTS  
Safe lighting and other performance criteria were met with  
the gas manifold and control assembly provided on the boiler  
when the boiler underwent tests specified in ANSI Z21.13-  
LATEST EDITION  
5. Boilers are shipped from the factory with the primary air  
shutters on the main burner wide open. It is recommend-  
ed these air shutters be left in the wide open position  
unless there is lifting of the flame above the burner ports.  
If there is lifting, the air shutters should be gradually  
closed until the lifting is eliminated. It may also be neces-  
sary to adjust the primary air shutters if the input rate is  
reduced by a change in the orifices.  
WARNING: Keep boiler area clear and free from com-  
bustible materials, gasoline and other flammable  
vapors and liquids. Otherwise fire or explosion may  
result.  
1. Check combination gas valve on boiler and make sure it  
is in the OFF position.  
6. After burner has been in operation for about 10 minutes,  
check gas input rate to boiler as follows:  
2. For vent damper-equipped models, with the thermostat  
set to call for heat, observe that vent damper position  
indicator rotates to the open position (see Figure 2.5).  
Damper must be in the open position when appliance  
main burner is operating.  
a. Make sure all appliances served by the meter are  
turned off during timing of gas input rate to the boiler.  
b. Measure the time in seconds that it takes for the boiler  
to use 10 cubic feet of gas. Divide 36,000 by the number  
of seconds (this is the number of cubic feet of gas used  
per hour). Multiply this figure by the heating value of the  
gas to obtain Btu input per hour.  
a. After damper opens, spark should appear at the pilot  
ignition electrodes.  
11  
FIGURE 3.2: BURNER FLAME COMPARISON/PILOT FLAME  
Q3451B  
Q314A/Q309A  
CONSTANT PILOT  
MODELS  
INTERMITTENT  
IGNITION PILOT  
MODELS  
NORMAL PILOT FLAME  
NORMAL  
(HARD FLAME) (TOO MUCH AIR)  
LIFTING  
YELLOW  
TIPPING  
(MARGINAL) (TOO LITTLE AIR)  
YELLOW  
FLAME  
MAIN BURNER FLAMES  
Example: A GB200-4L boiler takes 5 minutes, 27 seconds to  
use 10 cubic feet of natural gas. The local utility indicated the  
heating value of the natural gas being supplied is 1000  
Btu/cu ft. Therefore:  
9. Start and stop burners several times by raising and low-  
ering the thermostat setting.  
10. After boiler has been firing long enough to raise boiler  
pressure above minimum setting of the primary pressure-  
tol limit, check limit by turning its setting from maximum  
to minimum setting. This should turn boiler off. Return  
limit to desired setting.  
5 minutes, 27 seconds = 327 seconds.  
36,000  
x 1000 = 110,000 Btu/hr  
327  
11. Check boiler safety shutoff controls.  
Therefore, the boiler input is correct.  
For boilers with intermittent pilot, with boiler firing, discon-  
nect wire connected to the "PV" terminal on the Honey-  
well S8600 control. The gas valve should close.  
NOTE: Before calculating the input of the heating equip-  
ment, obtain the heating value of the gas from the local  
utility.  
For boilers with constant pilot, with boiler firing, turn the  
gas control knob on the gas valve to PILOT. The burn-  
ers should go out. Extinguish the pilot and wait 3 min-  
utes. Turn the gas valve control knob to ON. There  
should be NO gas flow to the main burners with the pilot  
out! If gas flow is detected, immediately turn the gas  
valve control knob to OFFand have the problem cor-  
rected.  
7. If input needs to be corrected, adjust combination gas  
valve pressure regulator. (Regulator is factory set at 3-  
1/2" W.C. for natural gas and 10" W.C. for propane.) Turn  
adjusting screw clockwise to increase gas flow (increase  
input). Turn adjusting screw counterclockwise to  
decrease gas flow (decrease input). In no case should  
final manifold pressure setting vary more than + .3" from  
factory-set pressures. If rated input cannot be obtained  
with adjustment, gas supply pressure or orifice size may  
be cause. Consult local utility and Smith.  
12. On initial start-up and prior to each heating season, boil-  
er must be cleaned with a commercially available steam  
boiler cleaner (see "Steam Boiler Cleaning Instructions"  
in Section 4 of this manual).  
8. Gas burner orifices supplied with boiler have been care-  
fully designed to provide correct gas input rate for most  
gas conditions typically found in the U.S. Occasionally,  
however, local gas characteristics may not allow unit to  
be properly adjusted for input. If this is the case, local  
utility or Smith may recommend orifices be changed.  
When changing orifices follow the procedures detailed in  
Section 4 of this manual.  
12  
WARNING:  
If you do not follow these instructions exactly, a fire or explosion may result with property damage,  
personal injury, or loss of life.  
A. BEFORE OPERATING smell all around the appliance  
area for gas. Be sure to smell next to the floor because  
some gas is heavier than air and will settle on the floor.  
What to do if you smell gas:  
B. Use only your hand to push in or turn the gas control  
knob, never use tools. If the knob will not push in or turn  
by hand dont try to repair it, call a qualified service tech-  
nician. Force or attempted repair may result in a fire or  
explosion.  
Do not try to light any appliance.  
Do not touch any electrical switch; do not use any  
phone in your building.  
Immediately call your gas supplier from a neighbor's  
phone. Follow the gas suppliers instructions.  
If you cannot reach your gas supplier, call the fire  
department.  
C. Do not use this appliance if any part has been under  
water. Immediately call a qualified service technician to  
inspect the appliance and to replace any part of the con-  
trol system and any gas control which has been under  
water.  
LIGHTING CONTINUOUS PILOT INSTRUCTIONS  
Honeywell VR8200  
Natural or Propane Gas  
1. STOP! Read the safety information above.  
2. Set the thermostat to lowest setting.  
11. Replace pilot access panel.  
12. Turn gas control knob counterclockwise to "ON".  
13. Replace control access panel (if applicable).  
3. Turn off all electric power to the appliance.  
4. Remove control access panel (if applicable).  
5. Rotate gas control knob clockwise to OFF.  
6. Wait five (5) minutes to clear out any gas. Then smell for  
gas, including near the floor. If you then smell gas STOP!  
Follow Ain the safety information above. If you dont  
smell gas, go to next step.  
14. Turn on all electric power to the appliance.  
CONTINUOUS PILOT - HONEYWELL VR8200  
7. Remove the pilot access panel located below and behind  
the gas control unit (if applicable).  
8. Find pilot - follow metal tube from gas control. The pilot is  
between the two burner tubes behind the pilot access  
panel (if applicable).  
9. Turn gas control knob counterclockwise to PILOT.  
10. Push down and hold the red button next to the control  
knob. Immediately light the pilot with a match. Continue  
to hold the red button down for about one (1) minute after  
the pilot is lit. Release button and it will pop back up. Pilot  
should remain lit. If it goes out, repeat steps 5 through  
10.  
GAS  
ON  
OFF  
INLET  
PILOT  
GAS CONTROL KNOB  
RESET BUTTON  
SHOWN IN "OFF" POSITION  
If button does not pop up when released, stop and  
immediately call your service technician or gas suppli-  
er.  
If the pilot will not stay lit after several tries, turn the  
gas control knob to "OFF" and call your service tech-  
nician or gas supplier.  
13  
OPERATING INSTRUCTIONS  
Intermittent Pilot - Honeywell VR8204  
Natural or Propane Gas  
INTERMITTENT PILOT - HONEYWELL VR8204  
1. STOP! Read the safety information on page 13..  
2. Set the thermostat to lowest setting.  
3. Turn off all electric power to the appliance.  
4. This appliance is equipped with an ignition device which  
automatically lights the pilot. Do not try to light the pilot  
by hand.  
5. Remove control access panel (if applicable).  
6. Rotate gas control knob clockwise to OFF.  
7. Wait five (5) minutes to clear out any gas. Then smell for  
gas, including near the floor. If you then smell gas STOP!  
Follow Aon page 13. If you dont smell gas, go to next  
step.  
INLET  
GAS  
ON  
OFF  
GAS CONTROL KNOB  
8. Turn gas control knob counterclockwise to ON.  
9. Replace control access panel (if applicable).  
10. Turn on all electric power to the appliance.  
11. Set thermostat to desired setting.  
SHOWN IN "OFF" POSITION  
12. If the appliance will not operate, follow the instructions  
"To Turn Off Appliance and call your service technician or  
gas supplier.  
TO TURN OFF APPLIANCE  
1. Set the thermostat to lowest setting.  
2. Turn off all electric power to the appliance if service is to  
be performed.  
3. Turn gas control knob counterclockwise to OFFDo not  
force.  
SECTION 4: MAINTENANCE  
BEFORE EACH HEATING SEASON  
This boiler has been designed to provide years of trouble  
free performance in normal installations. Examination by the  
homeowner at the beginning of each heating season, and in  
mid-heating season, should assure continued good perfor-  
mance. In addition, the boiler should be examined by a quali-  
fied service professional at least once every year.  
1. Remove and inspect draft diverter and smoke pipe (con-  
necting draft diverter to chimney or vent) for obstructions,  
soot accumulation, rust or corrosion. Clean and replace as  
necessary. Check tightness of joints; seal all joints where  
necessary.  
2. Check boiler flue passageways in the boiler sections for  
any blockage or soot accumulation. Remove jacket top and  
draft diverter. Using a flashlight, examine all flue passage-  
ways.  
DANGER:To avoid fire and explosion hazards: Do not  
store anything against the boiler or allow dirt or  
debris to accumulate in the area immediately sur-  
rounding the boiler. Keep boiler area clear and free  
from combustible materials, gasoline and other  
flammable vapors and liquids. Lint, paper or rags  
must not be allowed to accumulate near the burners.  
Do not place clothing on boiler casing to dry.  
a. If passageways are free of soot and obstructions, replace  
draft diverter and seal with furnace cement.  
b. If passageways need cleaning, remove flueway baffles  
and burners as described in paragraph 3 below. Insert  
long-handle bristle flue brush down between section  
tubes and upward through sections from combustion  
chamber in both diagonal directions to remove carbon  
from finned surfaces. Vacuum debris. Replace the draft  
diverter and seal with furnace cement.  
NOTE: Do not draw water from heating system for clean-  
ing. Minerals in the water can build up on the heat trans-  
fer surfaces and cause overheating and subsequent fail-  
ure of the cast iron sections.  
c. Reinstall jacket top panel.  
NOTE: To reduce the risk of fouling, the low water cut-off  
should be blown down at least once a week during heat-  
ing season.  
3. Check and clean burner assembly. Remove burner access  
panel. Lift burners up and to rear until burners are disen-  
gaged from orifices. Brush top of burners with soft bristle  
brush and blow out with air or vacuum.  
14  
4. Check gas manifold for proper position and reassemble  
burners to the manifold. Line up holes in burners with the ori-  
fices, and slide assembly back into position. Be sure to rein-  
stall burners with burner ports on the top surface  
(upright).  
11. Remove vent drain piping and reinstall pressure relief  
valve. Open gate valves on supply and return lines. Turn on  
burner. System is now ready to operate.  
HOW TO CHANGE ORIFICES  
1. Shut off power supply and gas supply to the boiler.  
5. When a low water cut-off has been utilized, follow the  
manufacturers maintenance instructions. As a minimum, test  
the operation of electronic controls at least once a year.  
Remove, clean and inspect the probe. Float type controls  
should be flushed once a month during the heating season. If  
LWCO fails to operate properly; it must be replaced.  
2. Remove burner access panel. Lift burners up and to rear  
until burners are disengaged from orifices.  
3. Check orifices for proper drill size. Size is stamped onto  
the body of the brass orifice (see Figure 4.1). Size can also  
be checked by using a pin gauge.  
6. Follow "System Start-Up & Adjustments" procedures in  
Section 3 of this manual.  
FIGURE 4.1: GB200 ORIFICE SIZES  
Boiler  
Model  
GB200-3  
41  
GB200-4L  
41  
GB200-4H  
37  
GB200-5  
38  
STEAM BOILER CLEANING INSTRUCTIONS  
The following procedures must be followed on initial start-up  
and if the presence of sediment, sludge or impurities hamper  
proper boiler operations.  
(1) Nat. Gas  
Drill Size  
(2) Prop. Gas  
Drill Size  
53  
53  
52  
52  
1. With gate valves closed on supply and return lines, start  
burner and allow boiler to become pressurized so that the pres-  
suretol may be adjusted and set for limit cut-off desired (nor-  
mally about 3 psi). Turn off burner and allow pressure to drop to  
0 psi., then proceed with the following cleaning procedure.  
4. All orifices are screwed into the manifold and may be  
removed by using a 5/8" wrench or socket.  
5. Reverse procedures above to install orifices and burners.  
Be sure to reinstall burners with burner ports on the top  
surface (upright).  
2. Remove the pressure relief valve.  
3. Add caustic soda (lewis lye) through this opening at the  
rate of one pound per thousand square feet of radiation  
capacity. Scout, Squirk or similar steam boiler cleaners may  
be used instead of lye. Trisodium phosphate (1/4#) is also an  
excellent cleaner.  
HEATING SYSTEM PROBLEMS & CAUSES  
No Heat  
1. Blown fuse or circuit breaker.  
Insufficient Heat  
1. Incorrect thermostat  
2. Switch turned off.  
anticipator setting.  
3. Pilot outage  
2. Low pressuretol setting.  
3. Boiler undersized or  
4. Provide pipe connection (full size) from pressure relief  
valve opening to a convenient drain to serve as a vent.  
4. IID system malfunction.  
5. Flue damper not open.  
underfired.  
6. Water level too low.  
4. Insufficient radiation.  
5. Fill the boiler with a manual fill valve until water starts to  
trickle from this pipe.  
Odor, Excessive  
Yellow Flame,  
Moisture In Building  
Carbon Build-Up  
6. Fire boiler at sufficient rate to generate and maintain  
steam. Entrain water and impurities will then discharge (with  
steam) from open vent. Add water as necessary so that the  
low water cutoff does not shut off burner.  
1. Leak in piping.  
1. Unit overfired.  
2. Carbon build-up in flueways.  
2. Air shutter misadjust-  
3. Blocked chimney.  
ment.  
3. Wrong orifices.  
4. Burning in burner mix-  
Noise  
7. Continue this process for a minimum of one hour. The process  
should continue until the steam is dry (no water coming from the  
vent when the water in the gauge glass is at a normal level,  
approximately 2/3 full). The time required could vary up to 3 hours.  
1. Ignition or ignition noise  
ing tube.  
due to incorrect air shutter  
adjustment.  
Overheating  
2. Whistle due to burr on  
1. Wrong thermostat  
orifices.  
anticipator setting.  
2. Bad thermostat  
8. Turn gas valve to off position. While boiler is still hot, drain  
completely through boiler drain. Make sure that all low points  
in the return line are also completely drained. These areas  
could trap chemicals and dirt.  
3. Burner "fluteings" due to air  
shutter opening too wide.  
location.  
3. Bad thermostat.  
CAUTION: Label all wires prior to disconnection  
when servicing controls. Wiring errors can cause  
improper and dangerous operation.  
9. Close boiler drain and refill with clean untreated warm  
water. If warm water is not used, fill very slowly so as not to  
crack boiler sections. Fill until water overflows through vent  
pipe and runs clear.  
Verify proper operation after servicing.  
10. Completely drain boiler again.Refill with clean untreated  
water to normal level.  
15  
ORDERING INFORMATION: When ordering parts, provide  
model and serial number shown on unit rating plate as well  
as part number and name as shown in parts list. Parts may  
be obtained from your local Smith heating contractor.  
GB200 Series  
REPLACEMENT PARTS LIST  
MODEL GB200 SERIES REPLACEMENT PARTS LIST  
REF  
NO.  
NAME OF PART  
PART NO.  
GB200-3  
GB200-4L  
GB200-4H  
GB200-5  
1
Jacket - Complete  
Jacket - Complete  
Jacket - Complete  
Burner - N.G./L.P.  
Burner w/Pilot Bracket - N.G./L.P.  
Base Door Ass'y  
Base Door Ass'y  
Base Door Ass'y  
Base Pan  
Base Pan  
Base Pan  
Manifold  
Manifold  
59248  
59249  
59250  
59089  
59091  
59092  
59093  
59094  
59056  
59057  
59058  
59119  
59120  
59121  
59145  
59146  
59147  
59150  
59151  
3672  
1
1
1
1
4
1
2
3
4
2
1
1
3
1
3
1
1
1
1
1
1
1
1
6
8
1
1
1
4
Manifold  
1
5
5
10  
Burner Orifice - #37 (N.G.)  
Burner Orifice - #38 (N.G.)  
Burner Orifice - # 41 (N.G.)  
Burner Orifice - # 52(L.P.)  
Burner Orifice - # 53 (L.P.)  
Section, Rear  
Section, Intermediate  
Section, Front (No Coil Opening)  
Heat Exchanger/Assembled Block  
Heat Exchanger/Assembled Block  
Heat Exchanger/Assembled Block  
Port Seal - 5"  
Port Seal - 2"  
Pipe Plug - 2" Sq. Hd.  
Flue Baffle  
Low Water Cut-Off (CG400)  
"Pigtail - 1/4""(CG400)"  
Pressuretrol (PA404A)  
Press. Gauge (0-15 P.S.I.)  
Water Gauge  
Pressure Relief Valve - 15 P.S.I.  
Draft Diverter  
Draft Diverter  
Draft Diverter  
Draft Diverter  
Junction Box - 4" x 4"  
Silicone Sealant 11 oz. (Not Shown)  
3/8" Fiberglass Rope - 5ft. (Not Shown)  
Block to Base Seal  
Vent Damper W/Harness Ass'y.  
Vent Damper W/Harness Ass'y.  
Vent Damper W/Harness Ass'y.  
Spill Switch (Manual Reset)  
Rollout Switch (Manuall Reset)  
3
4
4
3
1
1
1
1
4
1
2
1
11  
12  
13  
14  
1
2
1
1
3
1
3671  
3670  
72400  
72401  
72402  
60306  
59168  
61547  
59185  
50090  
61684  
50493  
60268  
59199  
61980  
59212  
59213  
59214  
59215  
60178  
40440  
1
1
1
4
4
1
4
1
1
1
1
1
1
15  
16  
17  
20  
21  
22  
23  
24  
25  
26  
27  
2
2
1
2
1
1
1
1
1
1
1
3
3
1
3
1
1
17  
1
1
1
3
3
1
3
1
1
1
1
1
1
1
1
1
1
1
1
31  
1
1
60024  
32  
69425  
69426  
69427  
59271  
59273  
1
1
1
1
1
33  
34  
1
1
1
1
1
1
16  
REF  
NO.  
NAME OF PART  
PART NO.  
GB200-3  
GB200-4L  
GB200-4H  
GB200-5  
Standing Pilot  
5
Pilot Ass'y NG- Q314ALB, Q309A  
Pilot Ass'y NG- Q314ALB, Q309A  
Pilot Ass'y LP- Q314ALB, Q309A  
Pilot Ass'y LP- Q314ALB, Q309D  
Thermocouple K16RA-30D  
Thermocouple K16RA-36D  
Gas Valve - NG VR8200H-1129 NG/LP*  
Transformer 115/24 V, 43VA  
72364  
72365  
72370  
72371  
59109  
51006  
59129  
50172  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
9
28  
1
1
1
1
1
1
Honeywell Intermittent Pilot System  
Pilot Ass'y NG- Q3451B  
Pilot Ass'y NG- Q3451B  
Pilot Ass'y LP- Q3451B  
Pilot Ass'y LP- Q3451B  
Ignition Cable - 24" Lg.  
Ignition Cable - 30" Lg.  
Gas Valve - 24V NG VR8204H-1006 NG/LP*  
Transformer 120/24 V, 43VA  
Ignitor Control S8600M-1013 N.G./L.P.  
5
72352  
72353  
72358  
72359  
59306  
59307  
59127  
50172  
51177  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
9
28  
30  
1
1
1
1
1
1
1
1
1
*For L.P., also order Conversion Kit #50701.  
17  
FIGURE 1: GB200 GENERAL ASSEMBLY  
32  
26  
27  
33  
20  
23  
1
24  
22  
15  
31  
30  
25  
21  
28  
16  
11  
14  
17  
12  
13  
30  
34  
4
3
5
6
2
10  
8
9
18  
19  
WARNING  
Any appliance that burns natural gas, propane gas, fuel oil, wood or coal is capable of producing carbon monoxide (CO).  
Carbon monoxide (CO) is a gas which is odorless, colorless and tasteless but is very toxic.  
If your Smith boiler is not working properly, or is not vented properly, dangerous levels of CO may accumulate. CO is lighter  
than air and thus may travel throughout the building. Brief exposure to high concentrations of CO, or prolonged exposure  
to lesser amounts of CO, may result in carbon monoxide poisoning.  
Exposure can be fatal and exposure to high concentrations may result in the sudden onset of symptoms including uncon-  
sciousness.  
Symptoms of CO poisoning include:  
dizziness  
headaches  
nausea  
vision problems  
loss of muscle control  
weakness  
shortness of breath  
unclear thinking  
unconsciousness  
The symptoms of CO poisoning are often confused with those of influenza, and the highest incidence of poisoning occurs at  
the onset of cold weather or during flu season. A victim may not experience any symptoms, only one symptom or a few symp-  
toms. Suspect the presence of carbon monoxide if symptoms tend to disappear when you leave your home.  
The following signs may indicate the presence of carbon monoxide:  
Hot gases from appliance, venting system, pipes, or chimney escaping into the living space.  
Flames coming out around the appliance.  
Yellow colored flames in the appliance.  
Stale or smelly air.  
The presence of soot or carbon in or around the appliance.  
Very high unexplained humidity inside the building.  
If any of the symptoms CO poisoning occur, or if any of the signs of carbon monoxide are present, vacate the premises  
immediately and contact a qualfied heating service company, the gas company or the fire department.  
To reduce the risk of CO poisoning, have your heating system tuned upby a licensed heating contractor or the gas company  
- preferably before each heating season. Also have the service company check your chimney or vent pipes for blockage. Your  
home should also be adequately ventilated, particularly if you have insulated your home.  
Only qualified, licensed service contractors should perform work on your Smith Boiler.  
WARNING  
Install, operate and maintain unit in accordance with manufacturers instructions to avoid exposure to fuel substances or sub-  
stances from incomplete combustion which can cause death or serious illness. The State of California has determined that  
these substances may cause cancer, birth defects, or other reproductive harm. Also, install and service this product to avoid  
exposure to airborne particles of glasswool fibers and/or ceramic fibers known to the State of California to cause cancer  
through inhalation.  
WESTCAST, INC. 260 NORTH ELM STREET WESTFIELD, MA 01085 TEL. (413) 562-9631 FAX (413) 562-3799  
20  

Westcott 1867 User Manual
Venturer LCD Kitchen TV User Manual
Transition Networks MEDIA CONVERTER A CF 01 User Manual
Tokina BUILT IN VARIFOCAL LENS TVB3516DCIR User Manual
Sub Zero ICB427R User Manual
Sony MSX M256S User Manual
Sony CCD TR 620 E User Manual
Sony Camcorder DSC W570 User Manual
Sony 2 685 154 1100000000#User Manual
Saris Bicycle Accessories 6200 User Manual