GB200-IM-5
42-9184
GB200 SERIES
INSTALLATION, OPERATION
& MAINTENANCE MANUAL
WITH REPLACEMENT
PARTS LIST
GAS-FIRED STEAM
CAST IRON BOILERS
85,000 TO 165,000 BTUH INPUT
INTERMITTENT PILOT/VENT DAMPER
& STANDING PILOT/VENT DAMPER
TABLE OF CONTENTS
SECTION 1: INTRODUCTION
Step 6: Wiring Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
SECTION 3: START-UP & OPERATION
Sequence Of Operation . . . . . . . . . . . . . . . . . . . . . . . . .11
Prior To Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Start-Up & Adjustments . . . . . . . . . . . . . . . . . . . . . . . . .11
Code Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Venting Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Chimney Requirements . . . . . . . . . . . . . . . . . . . . . . . . . .3
Combustion Air Requirements . . . . . . . . . . . . . . . . . . . . .3
Water Treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Shipment of Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
SECTION 4: MAINTENANCE
Before Each Heating Season . . . . . . . . . . . . . . . . . . . . .14
Steam Boiler Cleaning Instructions . . . . . . . . . . . . . . . . .15
How To Change Orifices . . . . . . . . . . . . . . . . . . . . . . . . .15
Heating System Problems & Causes . . . . . . . . . . . . . . .15
REPLACEMENT PARTS . . . . . . . . . . . . . . . . . . . . . .16-17
SECTION 2: BOILER INSTALLATION
Step 1: Locating/Setting Boiler . . . . . . . . . . . . . . . . . . . . .4
Step 2: Installing Steam Piping . . . . . . . . . . . . . . . . . . . .5
Step 3: Installing Hydronic Components . . . . . . . . . . . . .5
Step 4: Venting Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Step 5: Installing/Testing Gas Piping . . . . . . . . . . . . . . . . .7
WARNINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
WESTCAST, INC.
260 NORTH ELM STREET WESTFIELD, MA 01085
TEL. (413) 562-9631 FAX (413) 562-3799
CHIMNEY REQUIREMENTS
NOTE: Boiler employs atmospheric combustion. Com-
bustion air must not be contaminated with halogenated
hydrocarbon vapors, aerosol propellants or freon. Other-
wise, boiler heat exchanger will be subject to corrosion,
reducing boiler life.
DANGER: A chimney which does not meet modern
safety standards will result in a fire or deadly carbon
monoxide poisoning of the building residents.
Chimney condition is of paramount importance for a safe and
efficient boiler installation. All new and replacement installa-
tions must include a chimney inspection by a qualified indi-
vidual or agency. Chimney construction materials must be
compatible with the fuel being used.
WATER TREATMENT
Water treatment is recommended in areas where water quali-
ty is a problem. A local water treatment company should be
consulted to determine the requirements for your particular
system and locality.
Particular attention should be paid on all oil-to-gas conver-
sions. Soot may have accumulated in chimney and/or
degraded chimney liner. Most utilities require complete chim-
ney cleaning. Others may require installation of new liner,
spill switches or other chimney upgrades. Check with local
utility for required safety precautions.
NOTE: Boiler is not for use in systems where water is
replenished. Minerals in the water can build up on the
heat transfer surfaces and cause overheating and subse-
quent failure of the heat exchanger.
NOTE: Boiler utilizes synthetic rubber seals. Water treat-
ment chemicals and system cleaning chemicals must be
compatible with this and all other construction materials.
COMBUSTION AIR REQUIREMENTS
Provisions for combustion air must be in accordance with the
National Fuel Gas Code ANSI Z223.1 - latest edition, as well
as all applicable local codes. If the boiler is installed in an
unconfined space, adequate air will be available via normal
infiltration. However, if building construction is unusually tight
or the boiler is installed in a confined space (a space whose
volume is less than 50 cubic feet per 1000 Btu/hr of gas input
for all fuel burning equipment), adequate air for combustion
must be provided by two openings: one located about 6”
below the ceiling, the other about 6” above the floor. When
communicating directly with the outside or through a vertical
duct, each opening must have a minimum free area of one
square inch per 4000 Btu/hr of gas input. Horizontal ducts to
the outside must have a minimum free area of one square
inch per 2000 Btu/hr of gas input. When ventilation is provid-
ed by openings in doors, etc. to adjoining spaces having ade-
quate infiltration, each opening must have a minimum free
area of one square inch per 1000 Btu/hr of gas input.
SHIPMENT OF BOILER
Each boiler is shipped in a single carton.
Optional Vent Damper
When ordered, the vent damper is shipped in an individual
carton packaged with the boiler. Mounting of the damper and
flue outlet extension are required.
WARNING: Adequate fresh air must be provided for
combustion. Improper boiler operation and inade-
quate venting of deadly flue gases may otherwise
result.
3
SECTION 2: BOILER INSTALLATION
STEP 1: LOCATING/SETTING BOILER
Remove all packing material from boiler. Check that burners,
Boiler may be installed in an alcove (see dimensions in Fig-
ure 2.1). Locate boiler so connecting flue pipe between draft
hood and chimney is as short as possible.
draft diverter and controls are in proper position.
Boiler shall be installed such that the gas ignition system
components are protected from water (dripping, spraying,
rain, etc.) during appliance operation and service (low water
cut-off repacement, condensate trap replacement, control
replacement).
Observe the following minimum clearances to combustibles:
18" on sides...alcove at front...28" at top...18" at rear...6" from
flue pipe in any direction. Maintain a minimum 1” clearance
between hot water piping and combustible materials. Local
code requirements may specify greater clearances and must
be adhered to.
NOTE: Do not loosen tie rods on boiler absorption unit.
They are intended to accommodate thermal expansion.
Loss of boiler's structural integrity and water leaks/dam-
age may result.
Remove boiler from carton and set it in position. Install on
non-combustible floor only, unless local codes permit use
and fabrication of a fireproof base (see Figure 2.2).
WARNING: Never install boiler on carpeting as heat
damage and/or fire may result.
FIGURE 2.1: MODEL GB200 BOILER DIMENSIONS
MINIMUM CLEARANCES
TO COMBUSTIBLES
DIMENSIONS
BOILER
MODEL
A
B
Top:
28"
18"
GB200-S-3
GB200-S-4L
GB200-S-4H
GB200-S-5
15 3/8"
18 7/8"
18 7/8"
22 3/8"
5"
6"
6"
7"
Rear:
Left & Right: 18"
Front: ALCOVE
PRESS.
RELIEF VALVE
B
PRESSURE CONTROL
PRESS.
GAUGE
SPILL SWITCH
9 7/8"
3"
2" STEAM
SUPPLY
3/4" PLUGGED
TAPPING
LOW
WATER
CUT-OFF
WATER
LEVEL
INDICATOR
WATER
LINE
41"
2 1/2"
2" RETURN
REAR
1/2"
PLUGGED
TAPPING
GAS
VALVE
ROLLOUT SWITCH
26 7/8"
23 1/4"
18 1/4"
23 7/8"
23 1/4"
21"
20"
14 3/4"
14 3/4"
3 3/8"
2 3/8"
16 1/2"
18 1/8"
21 7/8"
2 1/2"
2" RETURN
FRONT
18 1/8"
6 3/4"
A
-LEFT SIDE VIEW-
PROBE LOCATION FOR ELECTRIC LWCO.
-FRONT VIEW-
-RIGHT SIDE VIEW-
NOTE: OPTIONAL FLOAT LOW WATER CUT-OFF SHOWN.
4
FIGURE 2.2: RECOMMENDED FIREPROOF BASE
The supply and return lines should be equipped with drain
cocks to drain sediment and sludge from lowest points of
boiler.
STEP 3: INSTALLING HYDRONIC COMPONENTS
A low-water cutoff must be installed to protect the unit from
dry fire.
6" OVERHANG OF BLOCKS
AND SHEETMETAL ALL
AROUND
4" HOLLOW CLAY
6"
Screw extension nipple into 3/4" tapping on top of the
absorption unit and install relief valve into top of nipple with
the spindle in the vertical position (i.e., with the valve dis-
charge in the horizontal).
TILE (TWO COURSES)
OPENINGS THRU BLOCKS
IN TOP COURSE TO
BE AT 90° ANGLE
TO OPENINGS THRU
22 GAUGE
SHEETMETAL
BOTTOM COURSE
WARNING: Never install any type of valve between
the boiler and the relief valve or an explosion causing
extensive property damage, severe personal injury or
death may occur!
Most localities require the discharge piping to terminate with-
in 6" of the floor. Check local code requirements if in doubt.
Discharge piping must be of same size or larger than the
relief valve outlet and should be run as short and straight as
possible. Elbows in the discharge piping should be placed as
close to the valve as possible. If valve discharge is to be
drained away, the discharge piping must not be hard-piped to
the drain piping (i.e., an open funnel or similar arrangement
must be used).
FLOOR
STEP 2: INSTALLING STEAM PIPING
Typical piping connections are shown in Figure 2.3. All exter-
nal piping must be supported by hangers, not by the boiler or
its accessories.
Supply outlet must run full size from the boiler to a header at
least 24" above top of boiler. Condensate return piping
should be connected to boiler through a "Hartford Loop."
Install gate valves in supply and return.
CAUTION: Piping must be installed from the relief valve
discharge so there will be no danger of scalding person-
nel.
Proper steam piping practices must be followed at all times.
Maintain proper clearances between piping and combustible
material.
FIGURE 2.3: TYPICAL STEAM BOILER PIPING
STEAM
SUPPLY
GATE VALVE
SUPPLY
TAPPING
3" NPT
12" MIN.
MUST BE CLOSE
NIPPLE
HARTFORD
LOOP
WATER LINE
RETURN
TAPPING
2" NPT
GATE
VALVE
C/L OF HARTFORD
LOOP TO BE 2"
BELOW WATER
LINE
23 1/4"
DRAIN
COCKS
5
STEP 4: VENTING BOILER
A factory-mounted spill switch is provided on all GB200 boil-
ers (see Figures 2.4 & 2.4A).
FIGURE 2.4: VENT DAMPER INSTALLATION
FOR INTERMITTENT PILOT
VENT DAMPER
DANGER: Draft diverter, vent outlet and vent damper
as supplied must not be altered in any way, as proper
boiler operation would be jeopardized. Flame rollout,
fire or carbon monoxide poisoning will result.
PRESSURE
CONTROL
SPILL
SWITCH
THERMOSTAT
CONNECTION
The flue or vent connectors must be installed flush with the
inside chimney liner surface and sealed in place with furnace
cement. Horizontal positions of the single wall and type B
venting systems shall be supported by use of strap hangers
or their equivalent. Vent supports should be placed a maxi-
mum of 15 feet apart and as required to prevent sagging.
The vent connectors shall be pitched 1/4" per foot upwards
towards the chimney or vent termination.
CABLE
BRACKET
TRANSFORMER
Installing Vent Damper
PILOT
CONTROL
DANGER: Only the boiler may be served by the vent
damper. Do not attempt to use it to vent an addition-
al appliance. This will cause fire or carbon monoxide
poisoning.
THERMOSTAT
CONNECTION
The vent damper must be mounted directly on top of the draft
diverter. The vent outlet extension must be installed between
the damper and the outlet to allow the damper plate to open
and close.
Locate the motor on the front side and position the cable so
that it does not touch the metal surface of the draft diverter
(see Figure 2.4). If necessary, turn angle connector on vent
damper upward until cable clears; tighten locknut to secure.
The direction of the flow arrow imprinted on the vent damper
must point upward. The damper position indicator, which is
located on the side of the vent damper opposite the motor,
must be visible.
FIGURE 2.4A: VENT DAMPER INSTALLATION
FOR STANDING PILOT
VENT DAMPER
PRESSURE
CONTROL
SPILL
CAUTION: A minimum of 6" between vent damper and
combustible materials must be maintained. The vent
damper must be accessible for servicing and checking
position indicator.
SWITCH
THERMOSTAT
CONNECTION
If applicable, remove hairpin shipping clip which holds
damper blade in closed position and observe that damper
blade rotates slowly to open position. Do not force it closed
as it may damage the gear train and void the warranty. The
blade should move freely and without obstruction.
CABLE
BRACKET
TRANSFORMER
Secure the vent damper housing to the draft diverter outlet
with sheet metal screws or pop rivets. Refer to Figure 2.5 for
fastener locations. Install flue pipe over top of vent damper
and secure to damper housing with sheet metal screws or
pop rivets.
GAS
VALVE
Attach vent damper cable to cable clamp on boiler left panel
and join the Molex connector (see Figures 2.4 & 2.4A).
THERMOSTAT
CONNECTION
6
ADDITIONAL CHIMNEY REQUIREMENTS
FIGURE 2.5: ATTACHING VENT DAMPER TO DRAFT
DIVERTER & FLUE PIPE
Chimney condition is of paramount importance for a safe and
efficient boiler installation. All installations must include a
chimney inspection by a qualified individual or agency. Chim-
ney construction materials must be compatible with the fuel
being used (See Figure 2.5A).
MAKE SURE MOTOR IS
LOCATED ON FRONT SIDE
CLOSED OPEN
FLOW DIRECTION
Particular attention should be paid on all oil-to-gas conver-
sions. Soot may have accumulated in chimney and/or
degraded chimney liner. Most utilities require complete chim-
ney cleaning. Others may require installation of new liner,
spill switches or other chimney upgrades. Check with local
utility for required safety precautions.
FLOW DIRECTION
ARROW POINTS UP
(REAR VIEW)
DANGER: A chimney which does not meet modern
safety standards will result in a fire or deadly carbon
monoxide poisoning of the building residents.
MOUNT VENT DAMPER
OVER DRAFT DIVERTER
INSTALL SWITCH IN
OPENING
ON DRAFT DIVERTER
STEP 5: INSTALLING/TESTING GAS PIPING
Connect the gas piping from the meter to the boiler using a
pipe size which will result in a pressure drop of less than 0.3"
W.C. for natural gas or 0.5" W.C. for propane. See Figure 2.7
for the appropriate gas pipe sizing and example.
Good piping practices should be followed at all times. See
Figure 2.6 for a typical gas piping arrangement. All piping
must be supported by hangers, not by the boiler or its acces-
sories.
FIGURE 2.5A: VENTING
Install a full-sized sediment trap at the low point in gas line
upstream of gas valve. Install a non-restrictive lubricated plug
valve in the gas line close to the boiler. Install a ground joint
union at the gas valve inlet to allow for servicing. Check local
codes and utilities for any special requirements and proce-
dures.
Pipe joint compound (pipe dope) must be compatible with the
fuel (natural gas or propane) being used.
FIGURE 2.6: TYPICAL GAS PIPING
7
FIGURE 2.7: GAS PIPE SIZING TABLES & EXAMPLE
Maximum Capacity of Pipe in Cubic Feet of Natural Gas per Hour for Gas Pressures of
0.5 Psig or Less and a Pressure Drop of 0.3 Inch Water Column
(Based on a 0.60 Specific Gravity Gas)
Nominal
Iron Pipe
Size,
Length of Pipe, Feet
Internal
Diameter,
Inches
90
100
125
175
150
200
10
20
30
40
50
60
70
80
Inches
1/4"
3/8"
1/2"
3/4"
1"
1-1/4"
1-1/2"
2"
22
49
92
18
40
73
32
72
15
34
63
14
30
56
12
27
11
25
46
96
11
23
10
22
40
84
9
21
38
79
8
18
34
72
130
275
410
8
17
7
15
28
59
6
14
26
55
.326
.493
.622
.824
1.049
1.380
1.610
2.067
2.469
3.026
4.026
132
50
43
31
278
520
1,050
1,600
3,050
4,800
8,500
130 115
245 215
500 440
760 670
105
90
170
350
530
990
64
120
250
380
710
190 152
350 285
730 590
1,100 890
2,100 1,650
3,300 2,700
5,900 4,700
195 180
400 370
600 560
160 150
320 305
490 460
930 870
110 100
225 210
350 320
650 610
1,450 1,270 1,150 1,500
780
2-1/2"
3"
4"
2,300 2,000 1,850 1,700 1,600 1,500 1,400 1,250 1,130 1,050 980
4,100 3,600 3,250 3,000 2,800 2,600 2,500 2,200 2,000 1,850 1,700
8,300 7,400 6,800 6,200 5,800 5,400 5,100
17,500 12,000
4,100 3,800 3,500
4,500
9,700
Maximum Capacity of Pipe in Thousands of Btu per Hour of Undiluted Liquefied
Petroleum Gases (at 11 Inches Water Column Inlet Pressure)
(Based on a Pressure Drop of 0.5 Inch Water Column)
Nominal
Iron Pipe
Size,
Length of Pipe, Feet
90
100
125
150
10
20
30
40
50
60
70
80
Inches
275
567
1071
189 152
393 315
732 590
129 114
267 237
504 448
103
96
89
185
346
724
83
78
69
146
275
567
866
63
132
252
511
787
1/2"
3/4"
1"
1-1/4"
1-1/2"
2"
217 196
409 378
834 771
173 162
322 307
677 630
2205 1496 1212 1039 937
3307 2299 1858 1559 1417 1275 1180 1086 1023 967
6221 4331 3465 2992 2646 2394 2205 2047 1921 1811 1606 1498
Example: Boiler Model GB200-4H is to be installed. The distance from the existing gas meter to the installation site is 30
ft. What pipe size must be used? The local utility indicates the heating value of natural gas being supplied is 1000 Btu per
cu.ft. Determine cubic feet of gas per hour for above boiler model:
135,000 Btu per hour
= 135 cu.ft. per hour
1000 Btu per cu.ft.
1. Find 30 ft. in upper portion of the table for natural gas under "Length of Pipe, Feet" heading.
2. Moving down the column, match required capacity. Higher capacity is acceptable. In our case it is 152 cu.ft.
3. Move to left-hand column "Nominal Iron Pipe Size, Inches," to read required pipe size. In our case it is 3/4".
Testing Gas Piping
Minimum pressure required at the gas valve inlet is 5" W.C.
DANGER: Before placing gas piping into service,
carefully test it to assure every joint is gas tight. Bub-
ble test all joints with a soap solution. NEVER TEST
WITH AN OPEN FLAME AS FIRE OR EXPLOSION
WILL RESULT.
for natural gas and 11" W.C. for propane. Maximum pressure
allowable at the gas valve inlet is 12" W.C. If the gas pres-
sure is above these limits, a pressure regulator must be
installed. If the gas pressure is below these limits, contact the
local utility.
For any pressure testing in excess of 1/2 psi, the boiler and
its individual shutoff valve must be isolated from the piping
system by disconnecting them and capping the outlet(s). For
any pressure testing equal to or less than 1/2 psi, the boiler
must be isolated from the piping system by closing its manu-
al shutoff valve.
8
STEP 6: WIRING BOILER
For vent damper-equipped models, connect thermostat
to blue leads (see Figures 2.4 & 2.4A).
WARNING: Turn off electrical power supply before
servicing. Contact with live electric components can
cause electric shock or death.
NOTE: If any of original wire supplied with boiler must
be replaced, use similar wire of 105° C rating. Other-
wise, insulation may melt or degrade, exposing bare
wire.
All electrical and control wiring must be installed in accor-
dance with the codes listed in Section 1 of this manual. Fol-
low the wiring diagram for your particular installation as
shown in Figures 2.8, 2.9, 2.10, and 2.11.
NOTE: Boiler transformer must not be used to power
external accessories (i.e., zone valves, relays, etc.) Oth-
erwise, transformer will be overloaded and burn out.
FIGURE 2.8: Wiring Diagram & Operation Sequence for
Boilers Equipped with Intermittent Pilot, Vent Damper
and M & M #67 Low Water Cut-Off
FIGURE 2.9: Wiring Diagram & Operation Sequence for
Boilers Equipped with Standing Pilot, Vent Damper and
M & M #67 Low Water Cut-Off
9
FIGURE 2.10: Wiring Diagram & Operation Sequence for
Boilers Equipped with Intermittent Pilot, Vent Damper
and 400 Series or M & M PS804 LWCO
FIGURE 2.11: Wiring Diagram & Operation Sequence for
Boilers Equipped with Standing Pilot, Vent Damper and
400 Series or M & M PS804 LWCO
10
SECTION 3: START-UP & OPERATION
SEQUENCE OF OPERATION
FIGURE 3.1: STEAM CONTROL ARRANGEMENT
For sequence of operation of the particular boiler being
installed, refer to Figures 2.8, 2.9, 2.10 and 2.11 in Section 2
of this manual.
PRESSURE
RELIEF VALVE
PRESSURE
CONTROL
Spill and rollout switches are mounted on all GB200 boilers.
PRESSURE
GAUGE
The spill switch detects the escape of combustion products
through the draft diverter relief opening and interrupts the
power to the gas valve preventing unsafe boiler operation.
Escape of flue products could be caused by a blocked or col-
lapsed chimney or inadequate chimney draft. This is a manu-
al reset-type device and can be reactivated by depressing
the spill switch reset button mounted on the left of the boiler’s
draft diverter (see Figure 2.1 for switch location).
PRESSURE RELIEF
VALVE DISCHARGE
PIPING
OPTIONAL
FLOAT
LOW WATER
CUT OFF
The rollout switch prevents flame rollout from the boiler com-
bustion chamber, caused by blocked boiler flue passage-
ways, by interrupting power to the gas valve to prevent
unsafe boiler operation. This is a manual reset-type device
and can be reactivated by depressing the rollout switch reset
button mounted on the lower front jacket panel (see Figure
2.1 for switch location). Flue passages must be inspected by
a qualified installer if this problem occurs, prior to switch
replacement.
GAS VALVE
b. Set thermostat to no longer call for heat. Spark should
stop. Observe that damper position indicator rotates to
the closed position.
c. Set thermostat to call for heat.
WARNING: If boiler cannot be restored to normal
operation after re-setting of spill switch, or if flame
rollout switch has tripped, do not attempt to put the
boiler in operation. Immediately contact a qualified
service professional.
3. Light the boiler. For Model GB200 boilers with intermit-
tent pilot, see lighting instruction on Page 14.
4. Observe pilot and main burner flame (see Figure 3.2).
All burner ports should be ignited and burn with a steady
blue flame.
PRIOR TO START-UP
Fill system with water until the water level indicator (sight
glass) is approximately 2/3 full. This water level is 23" from
the surface on which the boiler sits.
CAUTION: Never leave the job with yellow burning
flames. This condition indicated poor combustion and
will quickly carbonize the boiler, reducing efficiency and
boiler life. It may also be an indication of improper vent-
ing or combustion air supply. If unable to adjust flame
properly, consult your local utility.
SYSTEM START-UP & ADJUSTMENTS
Safe lighting and other performance criteria were met with
the gas manifold and control assembly provided on the boiler
when the boiler underwent tests specified in ANSI Z21.13-
LATEST EDITION
5. Boilers are shipped from the factory with the primary air
shutters on the main burner wide open. It is recommend-
ed these air shutters be left in the wide open position
unless there is lifting of the flame above the burner ports.
If there is lifting, the air shutters should be gradually
closed until the lifting is eliminated. It may also be neces-
sary to adjust the primary air shutters if the input rate is
reduced by a change in the orifices.
WARNING: Keep boiler area clear and free from com-
bustible materials, gasoline and other flammable
vapors and liquids. Otherwise fire or explosion may
result.
1. Check combination gas valve on boiler and make sure it
is in the OFF position.
6. After burner has been in operation for about 10 minutes,
check gas input rate to boiler as follows:
2. For vent damper-equipped models, with the thermostat
set to call for heat, observe that vent damper position
indicator rotates to the open position (see Figure 2.5).
Damper must be in the open position when appliance
main burner is operating.
a. Make sure all appliances served by the meter are
turned off during timing of gas input rate to the boiler.
b. Measure the time in seconds that it takes for the boiler
to use 10 cubic feet of gas. Divide 36,000 by the number
of seconds (this is the number of cubic feet of gas used
per hour). Multiply this figure by the heating value of the
gas to obtain Btu input per hour.
a. After damper opens, spark should appear at the pilot
ignition electrodes.
11
FIGURE 3.2: BURNER FLAME COMPARISON/PILOT FLAME
Q3451B
Q314A/Q309A
CONSTANT PILOT
MODELS
INTERMITTENT
IGNITION PILOT
MODELS
NORMAL PILOT FLAME
NORMAL
(HARD FLAME) (TOO MUCH AIR)
LIFTING
YELLOW
TIPPING
(MARGINAL) (TOO LITTLE AIR)
YELLOW
FLAME
MAIN BURNER FLAMES
Example: A GB200-4L boiler takes 5 minutes, 27 seconds to
use 10 cubic feet of natural gas. The local utility indicated the
heating value of the natural gas being supplied is 1000
Btu/cu ft. Therefore:
9. Start and stop burners several times by raising and low-
ering the thermostat setting.
10. After boiler has been firing long enough to raise boiler
pressure above minimum setting of the primary pressure-
tol limit, check limit by turning its setting from maximum
to minimum setting. This should turn boiler off. Return
limit to desired setting.
5 minutes, 27 seconds = 327 seconds.
36,000
x 1000 = 110,000 Btu/hr
327
11. Check boiler safety shutoff controls.
Therefore, the boiler input is correct.
For boilers with intermittent pilot, with boiler firing, discon-
nect wire connected to the "PV" terminal on the Honey-
well S8600 control. The gas valve should close.
NOTE: Before calculating the input of the heating equip-
ment, obtain the heating value of the gas from the local
utility.
For boilers with constant pilot, with boiler firing, turn the
gas control knob on the gas valve to “PILOT”. The burn-
ers should go out. Extinguish the pilot and wait 3 min-
utes. Turn the gas valve control knob to “ON”. There
should be NO gas flow to the main burners with the pilot
out! If gas flow is detected, immediately turn the gas
valve control knob to “OFF” and have the problem cor-
rected.
7. If input needs to be corrected, adjust combination gas
valve pressure regulator. (Regulator is factory set at 3-
1/2" W.C. for natural gas and 10" W.C. for propane.) Turn
adjusting screw clockwise to increase gas flow (increase
input). Turn adjusting screw counterclockwise to
decrease gas flow (decrease input). In no case should
final manifold pressure setting vary more than + .3" from
factory-set pressures. If rated input cannot be obtained
with adjustment, gas supply pressure or orifice size may
be cause. Consult local utility and Smith.
12. On initial start-up and prior to each heating season, boil-
er must be cleaned with a commercially available steam
boiler cleaner (see "Steam Boiler Cleaning Instructions"
in Section 4 of this manual).
8. Gas burner orifices supplied with boiler have been care-
fully designed to provide correct gas input rate for most
gas conditions typically found in the U.S. Occasionally,
however, local gas characteristics may not allow unit to
be properly adjusted for input. If this is the case, local
utility or Smith may recommend orifices be changed.
When changing orifices follow the procedures detailed in
Section 4 of this manual.
12
WARNING:
If you do not follow these instructions exactly, a fire or explosion may result with property damage,
personal injury, or loss of life.
A. BEFORE OPERATING smell all around the appliance
area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the floor.
What to do if you smell gas:
B. Use only your hand to push in or turn the gas control
knob, never use tools. If the knob will not push in or turn
by hand don’t try to repair it, call a qualified service tech-
nician. Force or attempted repair may result in a fire or
explosion.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a neighbor's
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
C. Do not use this appliance if any part has been under
water. Immediately call a qualified service technician to
inspect the appliance and to replace any part of the con-
trol system and any gas control which has been under
water.
LIGHTING CONTINUOUS PILOT INSTRUCTIONS
Honeywell VR8200
Natural or Propane Gas
1. STOP! Read the safety information above.
2. Set the thermostat to lowest setting.
11. Replace pilot access panel.
12. Turn gas control knob counterclockwise to "ON".
13. Replace control access panel (if applicable).
3. Turn off all electric power to the appliance.
4. Remove control access panel (if applicable).
5. Rotate gas control knob clockwise to “OFF”.
6. Wait five (5) minutes to clear out any gas. Then smell for
gas, including near the floor. If you then smell gas STOP!
Follow “A” in the safety information above. If you don’t
smell gas, go to next step.
14. Turn on all electric power to the appliance.
CONTINUOUS PILOT - HONEYWELL VR8200
7. Remove the pilot access panel located below and behind
the gas control unit (if applicable).
8. Find pilot - follow metal tube from gas control. The pilot is
between the two burner tubes behind the pilot access
panel (if applicable).
9. Turn gas control knob counterclockwise to “PILOT”.
10. Push down and hold the red button next to the control
knob. Immediately light the pilot with a match. Continue
to hold the red button down for about one (1) minute after
the pilot is lit. Release button and it will pop back up. Pilot
should remain lit. If it goes out, repeat steps 5 through
10.
GAS
ON
OFF
INLET
PILOT
GAS CONTROL KNOB
RESET BUTTON
SHOWN IN "OFF" POSITION
• If button does not pop up when released, stop and
immediately call your service technician or gas suppli-
er.
• If the pilot will not stay lit after several tries, turn the
gas control knob to "OFF" and call your service tech-
nician or gas supplier.
13
OPERATING INSTRUCTIONS
Intermittent Pilot - Honeywell VR8204
Natural or Propane Gas
INTERMITTENT PILOT - HONEYWELL VR8204
1. STOP! Read the safety information on page 13..
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device which
automatically lights the pilot. Do not try to light the pilot
by hand.
5. Remove control access panel (if applicable).
6. Rotate gas control knob clockwise to “OFF”.
7. Wait five (5) minutes to clear out any gas. Then smell for
gas, including near the floor. If you then smell gas STOP!
Follow “A” on page 13. If you don’t smell gas, go to next
step.
INLET
GAS
ON
OFF
GAS CONTROL KNOB
8. Turn gas control knob counterclockwise to “ON”.
9. Replace control access panel (if applicable).
10. Turn on all electric power to the appliance.
11. Set thermostat to desired setting.
SHOWN IN "OFF" POSITION
12. If the appliance will not operate, follow the instructions
"To Turn Off Appliance and call your service technician or
gas supplier.
TO TURN OFF APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to
be performed.
3. Turn gas control knob counterclockwise to “OFF” Do not
force.
SECTION 4: MAINTENANCE
BEFORE EACH HEATING SEASON
This boiler has been designed to provide years of trouble
free performance in normal installations. Examination by the
homeowner at the beginning of each heating season, and in
mid-heating season, should assure continued good perfor-
mance. In addition, the boiler should be examined by a quali-
fied service professional at least once every year.
1. Remove and inspect draft diverter and smoke pipe (con-
necting draft diverter to chimney or vent) for obstructions,
soot accumulation, rust or corrosion. Clean and replace as
necessary. Check tightness of joints; seal all joints where
necessary.
2. Check boiler flue passageways in the boiler sections for
any blockage or soot accumulation. Remove jacket top and
draft diverter. Using a flashlight, examine all flue passage-
ways.
DANGER:To avoid fire and explosion hazards: Do not
store anything against the boiler or allow dirt or
debris to accumulate in the area immediately sur-
rounding the boiler. Keep boiler area clear and free
from combustible materials, gasoline and other
flammable vapors and liquids. Lint, paper or rags
must not be allowed to accumulate near the burners.
Do not place clothing on boiler casing to dry.
a. If passageways are free of soot and obstructions, replace
draft diverter and seal with furnace cement.
b. If passageways need cleaning, remove flueway baffles
and burners as described in paragraph 3 below. Insert
long-handle bristle flue brush down between section
tubes and upward through sections from combustion
chamber in both diagonal directions to remove carbon
from finned surfaces. Vacuum debris. Replace the draft
diverter and seal with furnace cement.
NOTE: Do not draw water from heating system for clean-
ing. Minerals in the water can build up on the heat trans-
fer surfaces and cause overheating and subsequent fail-
ure of the cast iron sections.
c. Reinstall jacket top panel.
NOTE: To reduce the risk of fouling, the low water cut-off
should be blown down at least once a week during heat-
ing season.
3. Check and clean burner assembly. Remove burner access
panel. Lift burners up and to rear until burners are disen-
gaged from orifices. Brush top of burners with soft bristle
brush and blow out with air or vacuum.
14
4. Check gas manifold for proper position and reassemble
burners to the manifold. Line up holes in burners with the ori-
fices, and slide assembly back into position. Be sure to rein-
stall burners with burner ports on the top surface
(upright).
11. Remove vent drain piping and reinstall pressure relief
valve. Open gate valves on supply and return lines. Turn on
burner. System is now ready to operate.
HOW TO CHANGE ORIFICES
1. Shut off power supply and gas supply to the boiler.
5. When a low water cut-off has been utilized, follow the
manufacturer’s maintenance instructions. As a minimum, test
the operation of electronic controls at least once a year.
Remove, clean and inspect the probe. Float type controls
should be flushed once a month during the heating season. If
LWCO fails to operate properly; it must be replaced.
2. Remove burner access panel. Lift burners up and to rear
until burners are disengaged from orifices.
3. Check orifices for proper drill size. Size is stamped onto
the body of the brass orifice (see Figure 4.1). Size can also
be checked by using a pin gauge.
6. Follow "System Start-Up & Adjustments" procedures in
Section 3 of this manual.
FIGURE 4.1: GB200 ORIFICE SIZES
Boiler
Model
GB200-3
41
GB200-4L
41
GB200-4H
37
GB200-5
38
STEAM BOILER CLEANING INSTRUCTIONS
The following procedures must be followed on initial start-up
and if the presence of sediment, sludge or impurities hamper
proper boiler operations.
(1) Nat. Gas
Drill Size
(2) Prop. Gas
Drill Size
53
53
52
52
1. With gate valves closed on supply and return lines, start
burner and allow boiler to become pressurized so that the pres-
suretol may be adjusted and set for limit cut-off desired (nor-
mally about 3 psi). Turn off burner and allow pressure to drop to
0 psi., then proceed with the following cleaning procedure.
4. All orifices are screwed into the manifold and may be
removed by using a 5/8" wrench or socket.
5. Reverse procedures above to install orifices and burners.
Be sure to reinstall burners with burner ports on the top
surface (upright).
2. Remove the pressure relief valve.
3. Add caustic soda (lewis lye) through this opening at the
rate of one pound per thousand square feet of radiation
capacity. Scout, Squirk or similar steam boiler cleaners may
be used instead of lye. Trisodium phosphate (1/4#) is also an
excellent cleaner.
HEATING SYSTEM PROBLEMS & CAUSES
No Heat
1. Blown fuse or circuit breaker.
Insufficient Heat
1. Incorrect thermostat
2. Switch turned off.
anticipator setting.
3. Pilot outage
2. Low pressuretol setting.
3. Boiler undersized or
4. Provide pipe connection (full size) from pressure relief
valve opening to a convenient drain to serve as a vent.
4. IID system malfunction.
5. Flue damper not open.
underfired.
6. Water level too low.
4. Insufficient radiation.
5. Fill the boiler with a manual fill valve until water starts to
trickle from this pipe.
Odor, Excessive
Yellow Flame,
Moisture In Building
Carbon Build-Up
6. Fire boiler at sufficient rate to generate and maintain
steam. Entrain water and impurities will then discharge (with
steam) from open vent. Add water as necessary so that the
low water cutoff does not shut off burner.
1. Leak in piping.
1. Unit overfired.
2. Carbon build-up in flueways.
2. Air shutter misadjust-
3. Blocked chimney.
ment.
3. Wrong orifices.
4. Burning in burner mix-
Noise
7. Continue this process for a minimum of one hour. The process
should continue until the steam is dry (no water coming from the
vent when the water in the gauge glass is at a normal level,
approximately 2/3 full). The time required could vary up to 3 hours.
1. Ignition or ignition noise
ing tube.
due to incorrect air shutter
adjustment.
Overheating
2. Whistle due to burr on
1. Wrong thermostat
orifices.
anticipator setting.
2. Bad thermostat
8. Turn gas valve to off position. While boiler is still hot, drain
completely through boiler drain. Make sure that all low points
in the return line are also completely drained. These areas
could trap chemicals and dirt.
3. Burner "fluteings" due to air
shutter opening too wide.
location.
3. Bad thermostat.
CAUTION: Label all wires prior to disconnection
when servicing controls. Wiring errors can cause
improper and dangerous operation.
9. Close boiler drain and refill with clean untreated warm
water. If warm water is not used, fill very slowly so as not to
crack boiler sections. Fill until water overflows through vent
pipe and runs clear.
Verify proper operation after servicing.
10. Completely drain boiler again.Refill with clean untreated
water to normal level.
15
ORDERING INFORMATION: When ordering parts, provide
model and serial number shown on unit rating plate as well
as part number and name as shown in parts list. Parts may
be obtained from your local Smith heating contractor.
GB200 Series
REPLACEMENT PARTS LIST
MODEL GB200 SERIES REPLACEMENT PARTS LIST
REF
NO.
NAME OF PART
PART NO.
GB200-3
GB200-4L
GB200-4H
GB200-5
1
Jacket - Complete
Jacket - Complete
Jacket - Complete
Burner - N.G./L.P.
Burner w/Pilot Bracket - N.G./L.P.
Base Door Ass'y
Base Door Ass'y
Base Door Ass'y
Base Pan
Base Pan
Base Pan
Manifold
Manifold
59248
59249
59250
59089
59091
59092
59093
59094
59056
59057
59058
59119
59120
59121
59145
59146
59147
59150
59151
3672
1
1
1
1
4
1
2
3
4
2
1
1
3
1
3
1
1
1
1
1
1
1
1
6
8
1
1
1
4
Manifold
1
5
5
10
Burner Orifice - #37 (N.G.)
Burner Orifice - #38 (N.G.)
Burner Orifice - # 41 (N.G.)
Burner Orifice - # 52(L.P.)
Burner Orifice - # 53 (L.P.)
Section, Rear
Section, Intermediate
Section, Front (No Coil Opening)
Heat Exchanger/Assembled Block
Heat Exchanger/Assembled Block
Heat Exchanger/Assembled Block
Port Seal - 5"
Port Seal - 2"
Pipe Plug - 2" Sq. Hd.
Flue Baffle
Low Water Cut-Off (CG400)
"Pigtail - 1/4""(CG400)"
Pressuretrol (PA404A)
Press. Gauge (0-15 P.S.I.)
Water Gauge
Pressure Relief Valve - 15 P.S.I.
Draft Diverter
Draft Diverter
Draft Diverter
Draft Diverter
Junction Box - 4" x 4"
Silicone Sealant 11 oz. (Not Shown)
3/8" Fiberglass Rope - 5ft. (Not Shown)
Block to Base Seal
Vent Damper W/Harness Ass'y.
Vent Damper W/Harness Ass'y.
Vent Damper W/Harness Ass'y.
Spill Switch (Manual Reset)
Rollout Switch (Manuall Reset)
3
4
4
3
1
1
1
1
4
1
2
1
11
12
13
14
1
2
1
1
3
1
3671
3670
72400
72401
72402
60306
59168
61547
59185
50090
61684
50493
60268
59199
61980
59212
59213
59214
59215
60178
40440
1
1
1
4
4
1
4
1
1
1
1
1
1
15
16
17
20
21
22
23
24
25
26
27
2
2
1
2
1
1
1
1
1
1
1
3
3
1
3
1
1
17
1
1
1
3
3
1
3
1
1
1
1
1
1
1
1
1
1
1
1
31
—
1
1
—
60024
32
69425
69426
69427
59271
59273
1
1
1
1
1
33
34
1
1
1
1
1
1
16
REF
NO.
NAME OF PART
PART NO.
GB200-3
GB200-4L
GB200-4H
GB200-5
Standing Pilot
5
Pilot Ass'y NG- Q314ALB, Q309A
Pilot Ass'y NG- Q314ALB, Q309A
Pilot Ass'y LP- Q314ALB, Q309A
Pilot Ass'y LP- Q314ALB, Q309D
Thermocouple K16RA-30D
Thermocouple K16RA-36D
Gas Valve - NG VR8200H-1129 NG/LP*
Transformer 115/24 V, 43VA
72364
72365
72370
72371
59109
51006
59129
50172
1
1
1
1
1
1
1
1
1
1
1
1
—
1
1
1
9
28
1
1
1
1
1
1
Honeywell Intermittent Pilot System
Pilot Ass'y NG- Q3451B
Pilot Ass'y NG- Q3451B
Pilot Ass'y LP- Q3451B
Pilot Ass'y LP- Q3451B
Ignition Cable - 24" Lg.
Ignition Cable - 30" Lg.
Gas Valve - 24V NG VR8204H-1006 NG/LP*
Transformer 120/24 V, 43VA
Ignitor Control S8600M-1013 N.G./L.P.
5
72352
72353
72358
72359
59306
59307
59127
50172
51177
1
1
1
1
1
1
1
1
1
1
1
—
1
1
1
1
9
28
30
1
1
1
1
1
1
1
1
1
*For L.P., also order Conversion Kit #50701.
17
FIGURE 1: GB200 GENERAL ASSEMBLY
32
26
27
33
20
23
1
24
22
15
31
30
25
21
28
16
11
14
17
12
13
30
34
4
3
5
6
2
10
8
9
18
19
WARNING
Any appliance that burns natural gas, propane gas, fuel oil, wood or coal is capable of producing carbon monoxide (CO).
Carbon monoxide (CO) is a gas which is odorless, colorless and tasteless but is very toxic.
If your Smith boiler is not working properly, or is not vented properly, dangerous levels of CO may accumulate. CO is lighter
than air and thus may travel throughout the building. Brief exposure to high concentrations of CO, or prolonged exposure
to lesser amounts of CO, may result in carbon monoxide poisoning.
Exposure can be fatal and exposure to high concentrations may result in the sudden onset of symptoms including uncon-
sciousness.
Symptoms of CO poisoning include:
dizziness
headaches
nausea
vision problems
loss of muscle control
weakness
shortness of breath
unclear thinking
unconsciousness
The symptoms of CO poisoning are often confused with those of influenza, and the highest incidence of poisoning occurs at
the onset of cold weather or during flu season. A victim may not experience any symptoms, only one symptom or a few symp-
toms. Suspect the presence of carbon monoxide if symptoms tend to disappear when you leave your home.
The following signs may indicate the presence of carbon monoxide:
• Hot gases from appliance, venting system, pipes, or chimney escaping into the living space.
• Flames coming out around the appliance.
• Yellow colored flames in the appliance.
• Stale or smelly air.
• The presence of soot or carbon in or around the appliance.
• Very high unexplained humidity inside the building.
If any of the symptoms CO poisoning occur, or if any of the signs of carbon monoxide are present, vacate the premises
immediately and contact a qualfied heating service company, the gas company or the fire department.
To reduce the risk of CO poisoning, have your heating system “tuned up” by a licensed heating contractor or the gas company
- preferably before each heating season. Also have the service company check your chimney or vent pipes for blockage. Your
home should also be adequately ventilated, particularly if you have insulated your home.
Only qualified, licensed service contractors should perform work on your Smith Boiler.
WARNING
Install, operate and maintain unit in accordance with manufacturer’s instructions to avoid exposure to fuel substances or sub-
stances from incomplete combustion which can cause death or serious illness. The State of California has determined that
these substances may cause cancer, birth defects, or other reproductive harm. Also, install and service this product to avoid
exposure to airborne particles of glasswool fibers and/or ceramic fibers known to the State of California to cause cancer
through inhalation.
WESTCAST, INC. • 260 NORTH ELM STREET • WESTFIELD, MA 01085 • TEL. (413) 562-9631 • FAX (413) 562-3799
20
|