Heatiator Heatilator BH60 User Manual

Installation & Operating manual  
The bio-Flow 60  
(bh60) Pellet boiler  
dANgEr: rISk OF FIrE Or ExPlOSION  
- dO NOT burN gArbAgE, gASOlINE,  
drAIN OIl Or OThEr FlAmmAblE  
lIQuIdS IN ThIS APPlIANCE.  
wArNINg: rISk OF FIrE  
- dO NOT OPErATE wITh FuEl  
lOAdINg Or ASh rEmOvAl dOOrS  
OPEN.  
- dO NOT STOrE FuEl Or OThEr  
COmbuSTIblE  
mATErIAl wIThIN  
mArkEdINSTAllATIONClEArANCES.  
-
INSPECT ANd ClEAN ENTIrE  
vENTINg SYSTEm INCludINg All  
FluES ANd ChImNEY rEgulArlY.  
r10  
SAFETY NOTICE  
PlEASE rEAd ThIS ENTIrE mANuAl bEFOrE YOu INSTAll ANd uSE YOur NEw bOIlEr. FAIlurE TO FOllOw  
INSTruCTIONS mAY rESulT IN PrOPErTY dAmAgE, bOdIlY INjurY, Or EvEN dEATh.  
FOr rESIdENTIAl uSE IN ThE u.S. ANd CANAdA.  
IF ThIS PEllET bOIlEr IS NOT PrOPErlYINSTAllEd,AhOuSE FIrE mAYrESulT. FOrYOur SAFETY, FOllOw INSTAllATION  
dIrECTIONS.  
CONTACT lOCAl buIldINg Or FIrE OFFICIAlS AbOuT rESTrICTIONS ANd INSTAllATION INSPECTION  
rEQuIrEmENTS IN YOur ArEA.  
CONTACT YOur lOCAlAuThOrITY (SuChAS muNICIPAl buIldINg dEPArTmENT, FIrE dEPArTmENT, FIrE PrEvENTION  
burEAu, ETC.) TO dETErmINE ThE NEEd FOr A PErmIT.  
CETTE guIdE d’uTIlISATION EST dISPONIblE EN FrANCAIS. ChEZ vOTrE CONCESSIONNAIrE.  
SAvE ThESE INSTruCTIONS  
manual #3-90-233h  
bh60 Parts  
Flue Pipe - 3”  
Pellet Vent  
Combustion Blower  
Cover  
Hopper Lid  
Heat Exchange  
Cleanout Cover  
Pressure Relief  
Valve  
Temperature/  
Pressure Gauge  
Heating System  
Supply & Return  
(either side)  
Combustion Blower  
Remote Zone  
Control / OAT  
Sensor Terminal  
Control Board  
Power Cord  
Outside Air  
Knockout  
(either side)  
Circuit Breaker  
Side Access  
Panel  
Boiler Drain  
(Either Side)  
1- Controlled &  
1-Un-controlled  
120VAC Outlets  
Firebox Door  
Firebox Draft  
Test Port  
Levelling Feet  
3
Table of Contents  
Options  
5
Installation  
venting  
6
9
Plumbing  
Electrical  
14  
20  
Operation  
26  
33  
38  
39  
40  
41  
42  
43  
maintenance  
Troubleshooting  
Specifications  
wiring diagram  
warranty  
Testing label  
Service Parts  
Start-up Quick reference back Cover  
Please read this entire manual before you install and use  
your new boiler. Failure to follow instructions may result in  
property damage, bodily injury, or even death.  
SAvE ThESE INSTruCTIONS  
hearth & home Technologies  
352 Mountain House Road  
Halifax, PA 17032  
4
Options  
Outside Air Components  
Flex pipe part#  
1-00-08543  
(25')  
Inlet Cover part#  
1-10-08542  
Direct Vent Wall Passthrough  
Standard method of attaching outside air. Be sure to  
use the inlet cover to prevent birds and/or rodents  
from entering the intake pipe. This method requires a  
hole to the outside, separate from the vent passage.  
Item # 1-10-677077 provides for safe passing of  
the 3” pellet vent pipe through an outside wall,  
while providing the attachment for outside air. No  
extra holes needed.  
water Piping Supports-  
Bulk Storage Hopper-  
Item # 2-00-232044B, secures to the boiler  
and gives the support needed for the  
expansion tank and circulator, while keeping  
them at a workable distance from the boiler.  
Item # 1-00-73450, with 1500 lb  
pellet capacity, it will automatically  
re-fill the unit hopper when it falls  
below a certain level.  
Atmospheric Conversion-  
Item # 1-00-232200, provides  
automatic fill, and converts the  
heating system plumbing from  
pressurized to a zero pressure  
system. Allows for installation into  
more places where codes and  
standards restrict pressurized  
systems. Circuit Board Dipswitch  
#6 must be “ON” when installed.  
5
Installation  
Preparation For Installation:  
Boiler Kit Materials: (Refer to page 3)  
List of items shipped with the unit.  
1 - 3/4” Boiler Drain  
1. Install 3/4” MPT boiler drain in the fitting as shown. Either  
side can be utilized. Note: If using the supply and return on  
each side, either one of the returns is going to need the drain  
valve incorporated.  
Note: Use teflon pipe thread sealant or teflon tape onALL  
threads before connections are made.  
1 - 3/4” Safety Relief Valve  
1 - 1/2” Dual Temperature/Pressure Gauge  
1 - Outdoor Air Sensor  
2 - Piping Support Brackets  
1 - Scraper Tool  
2. Install the 1/2” MPT temperature/pressure gauge in fitting  
where shown.  
4 - 1½” Levelling Feet. (page 7)  
3. Locate and install the outside air temperature sensor.  
Location of this sensor should be on the North side of the  
home or building and out of direct sunlight. Use a cat3 cable  
or 18-2 thermostat wire to attach the sensor to the terminals  
located beside the control board. The wires can be connected  
to the sensor with wire nuts or butt splice connectors.  
Attach Outside Air  
Sensor Here  
Note:  
It is recommended that the  
levelling feet be installed  
in all installations. The air  
space provided will help to  
prevent condensation or  
trapped moisture which may  
lead to rust on the bottom of  
the unit.  
Bolt-Down Brackets:  
Use the brackets from  
the original packaging  
and at least 4 bolts (not  
supplied) to secure the  
unit in its permanent  
location.  
The feet can be adjusted  
using a 7/16” open end  
wrench.  
Recommended for all  
installations.  
6
Installation  
Minimum non-combustible floor protection area  
Placement and System design:  
The first thing that needs to be done is deciding where  
and how the boiler will be installed.  
NON-COMBUSTIBLE  
FLOOR PROTECTION  
Things that need to be taken into consideration are the  
intended use of the boiler. For example, is the boiler  
going to be used as a secondary or backup heating  
system? If it is to be used in conjunction with an existing  
oil or gas boiler system will it be piped in parallel or  
in series? The answers to these and other questions  
can be determined by talking to your certified dealer  
or a qualified HVAC or plumbing contractor. This will  
ensure that the boiler is installed and piped to best  
accommodate your needs and expectations.  
46 7/8[1190.63mm]US  
48 7/8[1241.43mm]CAN  
16[406.4mm]US  
18”[457.2mm]CAN  
Much consideration must be given to the venting. Due  
to low exhaust gas temperatures, the boiler should  
be placed where the venting system can be as short  
as possible. Pay particular attention to electrical  
connection needs and combustible/service clearance  
requirements.  
After the boiler is set into place the venting can be  
installed.  
46 7/8[1190.63mm]US  
48 7/8[1241.43mm]CAN  
Make sure any exhausting devices or appliances used  
in the area are installed so as not to create negative  
pressure in the room where the boiler is located.  
Floor Protection:  
The striped area indicates the minimum required floor  
protection area if the boiler is going to be placed on  
a combustible floor. Special Note: When installing  
on a protected floor, the levelling feet need to be  
adjusted so that the bottom of the unit is 1¼ inches  
off the floor protector (see illustration below). This  
boiler requires 46⅞” X 29⅛” (48⅞ X 29⅛ in Canada)  
of non combustible floor protection as shown above.  
16” (US) or 18” (Canada) of the floor protection must  
be in front of the boiler as shown, with 6” extending on  
either side. CSA/CAN B366.1 requires floor protection  
extending 2” (50mm) under horizontal section of  
chimney connector. Floor protection must be a minimum  
of 26 gauge sheet metal.  
This boiler must not be installed in an area or room  
where chemicals or solvents are used or stored in  
quantities above that of normal use.  
NOTICE: For installations above 3000 ft. elevation,  
or any installation using the atmospheric conversion,  
circuit board dipswitch #6 must be in the “ON” position.  
Note: It is recommended that the levelling feet be  
installed in all installations. The air space provided will  
help to prevent condensation or trapped moisture which  
may lead to rust on the bottom of the unit.  
The feet can be adjusted using a 7/16” open end  
wrench.  
Levelling feet must be adjusted  
to give 1¼ in of clearance when  
installing boiler on a protected  
combustible floor.  
This appliance is also approved for installation  
into a shop.  
7
Installation  
C
b
A
d
minimum Clearances To Combustible materials  
Sidewall To Appliance A  
6” (152 mm)  
6” (152 mm)  
mur latéral à l’Appareil  
mur Arrre à l’Appareil  
haut du Poêle au Plafond  
backwall To Appliance b  
Stove Top To Ceiling  
C
16” (406 mm)  
48” (1219 mm)  
3” (76 mm)  
Stove Front To Combustibles d  
Combustibles To Pellet vent  
minimum Alcove height  
minimum Alcove width  
des Combustibles au devant du Poêle  
matériaux Combustibles au Conduit de Fumée  
hauteur de l’Alve  
72” (1829 mm)  
48” (1219 mm)  
60” (1524 mm)  
largeur de l’Alve  
minimum Alcove depth  
Profondeur de l’Alve  
wArNINg! rISk OF FIrE! Hearth & Home Technologies disclaims any responsibility for, and the warranty  
and agency listing will be voided by the following actions:  
dO NOT:  
Install or operate a damaged appliance  
Modify the appliance  
Install other than as instructed by Hearth & Home Technologies  
Operate the appliance without fully assembling all components  
Overfire the appliance  
Install any component or part not approved by Hearth & Home Technologies  
Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage.  
For assistance or additional information, consult a qualified installer, service agency or your dealer.  
8
venting  
H. A vent must not be installed within 3 feet (90 cm)  
Requirements for Terminating the Venting  
WARNING: Venting terminals must not be recessed  
into a wall or siding.  
NOTE: Only PL vent pipe wall pass-throughs and  
fire stops should be used when venting through com-  
bustible materials.  
NOTE: Always take into consideration the effect  
the prevailing wind direction or other wind currents  
will cause with flyash and /or smoke when placing the  
termination.  
In addition, the following must be observed:  
A. The clearance above grade must be a minimum of  
18”.1  
B. The clearance to a window or door that may be  
opened must be a minimum of 48” to the side, 48”  
below the window/door, and 12” above the window/  
door.1  
C. A 12” clearance to a permanently closed window is  
recommended to prevent condensation on the window.  
D. The vertical clearance to a ventilated soffit located  
above the terminal within a horizontal distance of 2 feet  
(60 cm) from the center-line of the terminal must be a  
minimum of 18”.  
above a gas meter/regulator assembly when measured  
from the horizontal center-line of the regulator.1  
I. The clearance to service regulator vent outlet must be  
a minimum of 6 feet.1  
J. The clearance to a non-mechanical air supply inlet  
to the building or the combustion air inlet to any other  
appliance must be a minimum of 48”.1  
K. The clearance to a mechanical air supply inlet must  
be a minimum of 10 feet.1  
L. The clearance above a paved sidewalk or a paved  
driveway located on public property must be a minimum  
of 7 feet.1,2  
M. The clearance under a veranda, porch, deck or  
balcony must be a minimum of 12 inches.1,3 (See B. also)  
NOTE: The clearance to vegetation and other exte-  
rior combustibles such as mulch is 36” as measured from  
the center of the outlet or cap. This 36” radius continues  
to grade or a minimum of 7 feet below the outlet.  
1Certain Canadian and or Local codes or regulations  
may require different clearances.  
2A vent shall not terminate directly above a sidewalk  
or paved driveway which is located between two  
single family dwellings and serves both dwellings.  
3Only permitted if veranda, porch, deck, or balcony is  
fully open on a minimum of 2 sides beneath the floor.  
E. The clearance to an unventilated soffit must be a  
minimum of 12”.  
F. The clearance to an outside corner is 11” from center  
of pipe.  
G. The clearance to an inside corner is 12”. If you see  
deposits developing on the wall, you may need to extend  
this distance to accomodate your installation conditions.  
NOTE:Where passage through a wall, orpartition of  
combustible construction is desired, the installation  
shall conform to CAN/CSA-B365. (if in Canada)  
Fig. 2  
= Air supply inlet  
= Vent terminal  
= Area where terminal is not permitted  
9
venting  
Venting  
18  
Use only 3” pellet vent pipe to vent your pellet boiler.  
4
Fig. 3  
5
15  
10  
5
A combustion blower is used to extract the combustion  
gases from the firebox. This creates a negative pressure in  
the firebox and a positive pressure in the venting system as  
shown in Fig. 4. The longer the vent pipe and more elbows  
used in the system, the greater the flow resistance, and the  
greater the chance for creosote accumulation. Because of  
these facts we recommend using as few elbows as possible  
and 18 feet or less of vent pipe. The maximum horizontal  
run should never exceed 8 feet.  
6
7
8
9
10  
10  
8
The Total Lineal Feet  
Decreases as the  
Altitude Increases  
6
4
2
0
Be sure to use wall and ceiling pass through fittings  
(which are approved for pellet vent pipe ) when going  
through combustible materials. Be sure to use a starting  
collar to attach the venting system to the stove. The starting  
collar must be sealed to the stove flue collar with high  
temp silicone caulking or aluminum tape, and screwed  
into the unitsue collar in a minimum of three (3) places.  
8
6
4
2
Total Lineal Feet Combined  
Should Not Exceed 18' as  
measured from the outlet.  
Maximum Horizontal Run 8'  
Due to low exhaust temperatures, increasing the diameter  
of the venting or exceeding the recommendations of the  
venting graph, is strongly discouraged.  
NOTE:Use only 3” diameter Pellet venting system.  
Be sure to inspect and clean exhaust venting system  
frequently.  
Vent Pipe  
3” pellet vent pipe (also known as “PL” vent) is constructed  
of two layers with air space between the layers. This air space  
actsasaninsulatorandreducestheoutsidesurfacetemperature  
to allow a minimum clearance to combustibles as low as 1  
inch. In Canada the minimum clearance to combustibles is  
3 inches. Check with the venting manufacturer to be certain  
of specified clearances.  
Fig. 4  
The sections of pipe lock together to form an air tight seal  
in most cases; however, in some cases a perfect seal is not  
achieved. For this reason and the fact that the unit operates  
with a positive vent pressure, we specify that all joints  
within the structure should be secured with at least 3  
screws, and sealed with silicone caulking.  
+
-
Creosote - Formation and Need for Removal - When wood is burned slowly, it produces tar and other organic vapors,  
which combine with expelled moisture to form creosote. The creosote vapors condense in the relatively cool chimney flue  
of a slow-burning fire. As a result, creosote residue accumulates on the flue lining. When ignited, this creosote makes an  
extremely hot fire. The pellet vent pipe should be inspected at least twice monthly during the heating season to determine  
if a creosote buildup has occurred. If creosote has accumulated it should be removed to reduce the risk of a chimney fire.  
Guidance on minimizing creosote formation and the need for periodic creosote removal: The chimney should be inspected  
during the heating season to determine if a creosote build-up has occurred. If a significant layer of creosote has accumulated,  
1/8” (3mm) or more, it should be removed to reduce the risk of a chimney fire.  
10  
Venting  
venting  
The minimum vent configuration is a 90o or Tee on a starter  
collar and a 24” length horizontal through an exterior wall.  
Acap on the end should direct the flue gases down and away  
from the structure. See Fig. 5.  
This is the minimum venting configuration. NOTE: A starting  
collar is needed in order to remove the units’ cleanout cover.  
The maximum horizontal length is 8 feet. The minimum  
termination height above the exterior grade is 18”. The  
maximum total length of any configuration is 18 feet*.  
* (see venting graph on page 10 for exceptions)  
NOTE: Cleanout Tee’s should always be used on the  
transitions to horizontal pipe to allow easy access for  
cleaning.  
3” Type “L” or  
“PL” Vent pipe  
The venting graph allows for one(1) 90 deg. or Tee fitting  
in any configuration.  
If more 90’s, T’s, or 45’s are needed the total length must  
be adjusted to allow for the added restriction.  
Up to four (4) additional 90’s, Tee’s, or equivalent 45’s  
can be added as long as the overall length is adjusted in  
accordance with the values listed below. (See the venting  
graph on page 10.)  
Fig. 5  
Each Vertical ---- 90 deg. or T subtract 2.5 feet  
Each Vertical ---- 45 deg.  
Each Horizontal - 90 deg. or T subtract 5.0 feet  
Each Horizontal - 45 deg. subtract 2.5 feet  
subtract 1.5 feet  
Venting Into An Existing Chimney  
The boiler may be vented into an existing masonry or Class  
A metal chimney, providing that the chimney is less than 20  
feet above the connector. A flue liner, no more than 4-inch  
diameter, must be installed, along with a termination cap and  
the proper flashing to seal the existing flue.  
The venting Can Not be installed in a chimney serving  
another appliance.  
Other examples of possible installations of the venting.  
The chimney should be cleaned and/or inspected before  
installation of the vent liner.  
Any exterior venting (vent pipe exposed to outside  
ambiant temperatures) should be kept to a  
minimum, due to potential condensation problems.  
This is especially important in high humidity-cold  
weather climates, such as maritime areas, lake shores,  
and low river valleys.  
Due to low exhaust temperatures, and the increased  
possibility of condensation and creosote formation, additional  
measures may need taken to increase the flue temperature.  
One such measure would be to remove the two rear-most  
spiral baffles, above the burn pot, from their heat exchange  
tubes. Although some efficiency will be lost, an increased  
flue temperature will result.  
The flue liner should be inspected frequently, during  
operation, to monitor its performance and cleanliness.  
NOTE: Use only 3” diameterPellet venting system.  
Be sure to inspect and clean exhaust venting system  
frequently.  
11  
venting Installation  
To reduce probability of reverse drafting during  
a power failure, Hearth & Home Technologies  
strongly recommends:  
INSTALLATION IS TO BE PERFORMED BY  
A QUALIFIED INSTALLER.  
•Installing the pellet vent with a minimum vertical rise  
of five feet. Preferably terminating above the roof line.  
NOTE: All installation clearances and restrictions  
must be adhered to.  
•Installing an outside air connection to the appliance.  
To prevent soot damage to exterior walls, and to  
prevent re-entry of soot or ash into the home:  
INSTALLATION IS TO BE PERFORMED BY A  
QUALIFIED INSTALLER.  
•Maintain specified clearances to windows, doors and  
air inlets, including air conditioners.  
DO NOT INSTALL A FLUE DAMPER IN THE  
EXHAUST VENTING SYSTEM OF THIS UNIT.  
Vents should not be placed below ventillated soffits.  
•Avoid venting into alcove locations.  
DO NOT CONNECT THIS UNIT TOACHIMNEY  
FLUE SERVING ANOTHER APPLIANCE.  
Vents should not terminate under overhangs, decks or  
onto covered porches.  
•Maintain minimum clearance of 12” from the vent  
termination to the exterior wall.  
INSTALL VENT WALL PASS-THROUGHS AT  
CLEARANCES SPECIFIED BY THE VENT  
MANUFACTURER.  
Hearth  
&
Home Technologies assumes no  
responsibility for, nor does the warranty extend to,  
smoke damage caused by reverse drafting of pellet  
appliances under power failure conditions.  
NOTE: Read and follow all of the vent pipe  
manufacturersinstructions on the proper installation  
and support of the vent pipe. Adhere to all clearances  
to combustibles.  
WARNING  
KEEP COMBUSTIBLE MATERIALS SUCH  
AS GRASS, LEAVES, ETC. AT LEAST 3 FEET  
AWAY FROM THE POINT DIRECTLY UNDER  
THE VENT TERMINATION. (BETWEEN THE  
VENTAND THE GROUND)  
CAUTION  
KEEP COMBUSTIBLES AWAY  
FROM FLUE OUTLET.  
12  
Installation  
NOTE: If outside air is installed, the inlet cover should not  
be placed in an area where drifting of snow or ice will build  
up, blocking the intake air supply.  
Inlet Cover part#  
1-10-08542  
Hearth & Home Technologies strongly recommends the use  
of outside air for all pellet boiler applications.  
Per national building codes, consideration must be given  
to combustion air supply for all appliances in the vicinity  
of the pellet boiler. Failure to supply adequate combustion  
air for all appliance demands may lead to backdrafting of  
those appliances. Consult with your HVAC Professional to  
determine that all combustion air requirements are met.  
Fig. 6  
Outside Air Pipe  
Knockout  
When the appliance is side-wall vented: The air intake is  
best located on the same exterior wall as, and lower than the  
exhaust vent outlet.  
When the appliance is roof vented: The air intake is best  
located on the exterior wall oriented towards the prevailing  
wind direction, during the heating season.  
Rear Cover  
Side Cover  
The Outside Air Intake Pipe is inside the Rear Cover and to  
the right of the feeder motor. The flex pipe is made to slide  
inside the Air Intake Pipe. See Fig. 8. It should be held into  
place with silicone, foil tape, or a hose clamp. (not supplied)  
Feeder Cover  
Fig. 7  
Negative Pressure and Electrical Power Failure  
To reduce the probability of back-drafting or burn-back in the  
pellet appliance during a power failure, the appliance must  
be able to draft naturally without exhaust blower operation.  
Negative pressure in the house will resist this natural draft if  
not accounted for in the pellet appliance installation.  
Heat rises in the house and leaks out at upper levels. This air  
must be replaced with cold air from outdoors which flows into  
lower levels of the house. Vents and chimneys into basements  
and lower levels can become the conduit for air supply and  
reverse under these conditions.  
Outside Air Inlet Pipe  
Fig. 8  
The outside air supply will supply most of the demands of  
the pellet appliance to resist back-drafting, but consideration  
must be given to the total house demand. It may be necessary  
to add additional ventilation to the space in which the pellet  
appliance is located. Consult with your HVAC professional  
to determine the ventilation demands for your house.  
Outside Air  
Although strongly recommended, the use of outside  
air is optional, except where required by local building  
codes. To install outside air, use metal flex pipe, part  
# 1-00-08543 (25’ roll) See Fig. 6. There is a break-  
away hole on either rear panel which must be removed  
before connecting the flex pipe. See Fig. 7. The pipe  
should be run outside and terminate 3 feet or more  
below or 1 foot or more to the side of the vent pipe  
outlet. Never terminate the outside air above the vent  
pipe outlet. The maximum length of this pipe is 15  
feet. Inlet cover part number 1-10-08542 should be  
used to keep birds, rodents etc.out of the inlet pipe.  
See Fig.6.  
during a loss of electrical power the hopper lid  
must be kept in a closed and latched position.  
Opening the lid while the combustion blower  
is non-operational will allow smoke into the  
home and potential overheating of the hopper  
and fuel. This can lead to a fire in the hopper.  
13  
Installation-Plumbing  
NOTE: ALWAYS REFER TO THE INDIVIDUAL COMPONENTS  
RECOMMENDED INSTALLATION INSTRUCTIONS FOR THE PROPER  
MOUNTING POSITION AND LOCATION WITHIN THE PIPING SYSTEM.  
TYPICAL BOILER HOT WATER PIPING SHOWING AIR REMOVAL SYSTEM, PROVISIONS FOR THE  
EXPANSION OF WATER AND THE AUTOMATIC COLD WATER SUPPLY. ALSO SHOWN BUT NOT  
NECESSARILY NEEDED IS THE BOILER BYPASS LINE.THE NECESSITY OF THIS LINE WILL BE  
DETERMINED BY THE INSTALLING CERTIFIED PLUMBER OR HVAC CONTRACTOR.  
NOTICE: When installing with the Atmospheric Conversion, all of the pressurized system  
** THERMOMETER  
components shown are not necessary. Air vents or bleeders should be removed from the  
AIR VENT  
plumbing system to prevent air from entering the lines. Control dipswitch #6 must beON.  
AIR SCOOP  
SYSTEM SUPPLY 3/4"  
SYSTEM SUPPLY 3/4"  
SHUT-OFF  
VALVE  
* AUTOMATIC AIR VENT  
* TEMP/PRESSURE  
GAUGE  
COLD  
WATER  
PRESSURE REDUCING  
SHUT-OFF  
VALVE  
CHECK VALVE (OR  
BACKFLOW  
PREVENTER IF  
REQUIRED)  
SUPPLY 1/2"  
* PRESSURE RELIEF VALVE  
VALVE (PRV) OR  
COMBINATION PRV AND  
RELIEF VALVE  
BYPASS  
VALVE  
UNION  
EXPANSION TANK  
(DIAPHRAGM TYPE)  
* 3/4" NPT MALE  
PLUG  
3/4" BOILER  
BYPASS LINE (IF  
REQUIRED)  
PIPE TO WITHIN  
6" OF THE FLOOR  
OR A FLOOR  
DRAIN  
** THERMOMETER  
UNION  
SYSTEM RETURN 3/4"  
SHUT-OFF VALVE  
* BOILER DRAIN,  
3/4" NPT MALE  
3/4" HOSE  
X
NOTE: Cold return water temperature (Sustained temperatures below 140 degrees  
Fahrenheit) will lead to condensation or moisture in the firebox.This moisture can  
lead to creosote formation.To help minimize moisture and creosote, it is strongly  
recommended that some method of temperature balance is incorporated into the  
return system.  
* ITEMS SUPPLIED  
** OPTIONAL  
NOTE: ALWAYS REFER TO THE INDIVIDUAL COMPONENTS  
RECOMMENDED INSTALLATION INSTRUCTIONS FOR THE PROPER  
MOUNTING POSITION AND LOCATION WITHIN THE PIPING SYSTEM.  
EXAMPLE OF A TYPICAL MULTI-ZONE HEATING SYSTEM WITH BOILER BYPASS AND INDIRECT  
DOMESTIC HOT WATER ZONE  
NOTICE: When installing with the Atmospheric Conversion, all of the pressurized  
EXPANSION TANK, AIR REMOVAL AND COLD WATER SUPPLY  
system components shown are not necessary. Air vents or bleeders should be  
removed from the plumbing system to prevent air from entering the lines.  
Control dipswitch #6 must beON.  
** THERMOMETER  
BALANCING VALVE  
CHECK VALVE  
SYSTEM SUPPLY 3/4"  
SYSTEM SUPPLY 3/4"  
COLD  
HOT  
* AUTOMATIC AIR VENT  
BOILER BYPASS CAN ALSO BE DONE WITH A 3-WAY  
MIXING VALVE AND CAN BE CONTROLLED MANUALLY  
OR WITH AN AUTOMATIC ACTUATING MOTOR. IF SO,  
THE TWO BALANCING VALVES ARE NOT NEEDED  
* TEMP/PRESSURE  
GAUGE  
SHUT-OFF VALVE  
DOMESTIC HOT  
WATER STORAGE  
HEATER WITH  
INTERNAL HEAT  
EXCHANGER  
CIRCULATOR  
* PRESSURE RELIEF VALVE  
BOILER WATER  
SUPPLY WATER  
BYPASS (BALANCING) VALVE  
UNION  
RETURN WATER  
* 3/4" NPT MALE PLUG  
IN  
PIPE TO WITHIN 6" OF THE FLOOR OR A  
FLOOR DRAIN  
OUT  
** THERMOMETER  
UNION  
SYSTEM RETURN 3/4"  
SHUT-OFF VALVE  
CHECK VALVE  
* BOILER DRAIN, 3/4" NPT MALE X  
3/4" HOSE  
NOTE: Cold return water temperature (Sustained temperatures below 140 degrees  
Fahrenheit) will lead to condensation or moisture in the firebox.This moisture can  
lead to creosote formation.To help minimize moisture and creosote, it is strongly  
recommended that some method of temperature balance is incorporated into the  
return system.  
* ITEMS SUPPLIED  
** OPTIONAL  
14  
Installation-Plumbing  
Boilers intended to be connected to an existing boiler or boiler system shall:  
1. Be capable of being installed without interfering with the normal delivery of heated water from the original boiler to the  
radiation system.  
2. Be capable of being installed to operate as intended without affecting the operation of the electrical and mechanical safety  
controls of the original boiler.  
3. Provide, upon completion of the installation, for a change over from one fuel to the other without requiring the manual  
adjustment of any controls or components other than the thermostats.  
4. Be compatible with the operation of a service water-heating coil within the original boiler without bypassing the operation  
of the solid-fuel boiler.  
5. Have provision for preventing, or adequate water capacity within the boiler to prevent, damage to the boiler from loss of  
circulation due to electrical power failure.  
6. Be capable of being installed without changing the function of the control or rewiring of the original boiler. A wiring  
interconnection is permitted. The electrical system of both boilers shall be powered from a single branch circuit without  
exception.  
(CAN/CSA-B366.1-M91)  
7. Pertaining to CAN/CSA- B365-01, Have a clearly labelled device, located at each entrance to the boiler area, which can  
be thrown to discontinue operation to the feed system.  
Anti-freeze and/or boiler water treatment:  
There is no restriction on the type of commercial antifreeze used. When filling the boiler water system, it is recommended  
that some form of boiler water treatment be used.  
EXAMPLE OF PIPING WITH AN INDEPENDENT CIRCULATOR SYSTEM  
CONNECTED TO AN EXISTING OPERATIONAL BOILER  
NOTICE: When installing with the Atmospheric Conversion, all of the  
pressurized system components shown are not necessary. Air vents or  
bleeders should be removed from the plumbing system to prevent air  
from entering the lines. Control dipswitch #6 must beON.  
NOTE: NOT SHOWN IN THIS DRAWING ARE ALL OF THE  
ASSOCIATED PIPING AND CONTROLS THAT SHOULD  
ALREADY BE IN PLACE WITH THE EXISTING BOILER  
SYSTEM. FOR EXAMPLE,THE EXPANSION TANK,THE  
COLD WATER SUPPLY , AIR REMOVAL SYSTEM ETC... IT IS  
EXTREMELY IMPORTANT THAT THIS BOILER BE  
INSTALLED BY A QUALIFIED INSTALLER AND THAT ALL  
EXISTING CONTROLS AND SAFETY DEVICES ARE  
VERIFIED AS OPERATIONAL.  
SYSTEM SUPPLY  
BALANCING VALVE  
SUPPLY 3/4"  
UNION  
UNION  
IN  
SHUT-OFF  
VALVE  
* AUTOMATIC AIR VENT  
* TEMP/PRESSURE  
GAUGE  
* PRESSURE RELIEF VALVE  
EXISTING  
BOILER  
UNION  
CIRCULATOR  
PIPE TO WITHIN  
6" OF THE  
FLOOR OR A  
FLOOR DRAIN  
OUT  
SHUT-OFF VALVE  
UNION  
UNION  
NOTE: ALWAYS REFER TO THE INDIVIDUAL COMPONENTS  
RECOMMENDED INSTALLATION INSTRUCTIONS FOR THE PROPER  
MOUNTING POSITION AND LOCATION WITHIN THE PIPING SYSTEM.  
SHUT-OFF  
VALVE  
CIRCULATOR  
SYSTEM RETURN  
SHUT-OFF VALVE  
UNION  
RETURN 3/4"  
NOTE: Cold return water temperature (Sustained temperatures below 140 degrees  
Fahrenheit) will lead to condensation or moisture in the firebox.This moisture can  
lead to creosote formation.To help minimize moisture and creosote, it is strongly  
recommended that some method of temperature balance is incorporated into the  
return system.  
* ITEMS SUPPLIED  
15  
Installing Duct  
Installation-Plumbing  
NOTE: ALWAYS REFER TO THE INDIVIDUAL COMPONENTS RECOMMENDED  
INSTALLATION INSTRUCTIONS FOR THE PROPER MOUNTING POSITION AND  
LOCATION WITHIN THE PIPING SYSTEM.  
EXAMPLE OF PIPING IN SERIES WITH  
AN EXISTING OPERATIONAL BOILER  
NOTICE: When installing with the Atmospheric Conversion, all of the pressurized  
system components shown are not necessary. Air vents or bleeders should be  
removed from the plumbing system to prevent air from entering the lines.  
Control dipswitch #6 must beON.  
SYSTEM SUPPLY 3/4"  
NOTE: NOT SHOWN IN THIS DRAWING ARE ALL OF THE  
ASSOCIATED PIPING AND CONTROLS THAT SHOULD  
ALREADY BE IN PLACE WITH THE EXISTING BOILER SYSTEM.  
FOR EXAMPLE,THE EXPANSION TANK,THE COLD WATER  
SUPPLY , AIR REMOVAL SYSTEM ETC... IT IS EXTREMELY  
IMPORTANT THAT THIS BOILER BE INSTALLED BY A  
QUALIFIED INSTALLER AND THAT ALL EXISTING CONTROLS  
AND SAFETY DEVICES ARE VERIFIED AS OPERATIONAL.  
OUT  
IN  
* AUTOMATIC AIR VENT  
* TEMP/PRESSURE  
GAUGE  
SHUT-OFF VALVE  
* PRESSURE RELIEF VALVE  
UNION  
EXISTING BOILER  
* 3/4" NPT MALE PLUG  
PIPE TO WITHIN 6" OF THE FLOOR OR A  
FLOOR DRAIN  
UNION  
SYSTEM RETURN 3/4"  
SHUT-OFF VALVE  
* BOILER DRAIN, 3/4" NPT MALE X 3/4" HOSE  
NOTE: Cold return water temperature (Sustained temperatures below 140 degrees  
Fahrenheit) will lead to condensation or moisture in the firebox.This moisture can  
lead to creosote formation.To help minimize moisture and creosote, it is strongly  
recommended that some method of temperature balance is incorporated into the  
return system.  
* ITEMS SUPPLIED  
NOTE: ALWAYS REFER TO THE INDIVIDUAL COMPONENTS  
RECOMMENDED INSTALLATION INSTRUCTIONS FOR THE PROPER  
MOUNTING POSITION AND LOCATION WITHIN THE PIPING SYSTEM.  
EXAMPLE OF PIPING IN PARALLEL WITH  
AN EXISTING OPERATIONAL BOILER  
NOTICE: When installing with the Atmospheric Conversion, all of  
the pressurized system components shown are not necessary.  
Air vents or bleeders should be removed from the plumbing  
system to prevent air from entering the lines. Control dipswitch  
#6 must beON.  
SYSTEM SUPPLY 3/4"  
BALANCING  
VALVE  
BALANCING  
VALVE  
NOTE: NOT SHOWN IN THIS DRAWING ARE ALL OF THE  
ASSOCIATED PIPING AND CONTROLS THAT SHOULD  
ALREADY BE IN PLACE WITH THE EXISTING BOILER  
SYSTEM. FOR EXAMPLE,THE EXPANSION TANK,THE  
COLD WATER SUPPLY , AIR REMOVAL SYSTEM ETC... IT IS  
EXTREMELY IMPORTANT THAT THIS BOILER BE  
INSTALLED BY A QUALIFIED INSTALLER AND THAT ALL  
EXISTING CONTROLS AND SAFETY DEVICES ARE  
VERIFIED AS OPERATIONAL.  
UNION  
UNION  
OUT  
* AUTOMATIC AIR VENT  
* TEMP/PRESSURE  
GAUGE  
IN  
* PRESSURE RELIEF VALVE  
UNION  
EXISTING  
BOILER  
* 3/4" NPT MALE PLUG  
PIPE TO WITHIN  
6" OF THE  
FLOOR OR A  
FLOOR DRAIN  
SHUT-OFF  
VALVE  
SYSTEM RETURN 3/4"  
SHUT-OFF VALVE  
UNION  
* BOILER DRAIN, 3/4" NPT MALE  
X 3/4" HOSE  
NOTE: Cold return water temperature (Sustained temperatures below 140 degrees  
Fahrenheit) will lead to condensation or moisture in the firebox.This moisture can  
lead to creosote formation.To help minimize moisture and creosote, it is strongly  
recommended that some method of temperature balance is incorporated into the  
return system.  
* ITEMS SUPPLIED  
16  
Installing Duct/Air Conditioning  
Installation-Plumbing  
TYPICAL BOILER HOT WATER PIPING SHOWING AIR REMOVAL SYSTEM, PROVISIONS FOR THE  
EXPANSION OF WATER AND THE AUTOMATIC COLD WATER SUPPLY. ALSO SHOWN IS THE AUTOMATIC  
MIXING VALVE.THIS COULD ALSO BE DONE BY (2) CLOSELY SPACED TEE'S.THE PROPER PIPING FOR THE  
INTENDED USE WILL BE DETERMINED BY THE INSTALLING CERTIFIED PLUMBER OR HVAC CONTRACTOR.  
NOTE: ALWAYS REFER TO THE INDIVIDUAL COMPONENTS  
RECOMMENDED INSTALLATION INSTRUCTIONS FOR THE PROPER  
MOUNTING POSITION AND LOCATION WITHIN THE PIPING SYSTEM.  
NOTICE: When installing with the Atmospheric Conversion, all of the  
** THERMOMETER  
pressurized system components shown are not necessary. Air vents or  
AIR VENT  
bleeders should be removed from the plumbing system to prevent air  
from entering the lines. Control dipswitch #6 must beON.  
AIR SCOOP  
SYSTEM SUPPLY 3/4"  
AUTOMATIC  
MIXING VALVE  
SHUT-OFF  
VALVE  
SHUT-OFF VALVE  
* AUTOMATIC AIR VENT  
COLD WATER  
SUPPLY 1/2"  
* TEMP/PRESSURE  
GAUGE  
EXPANSION TANK  
(DIAPHRAGM TYPE)  
* PRESSURE  
RELIEF VALVE  
UNION  
CHECK VALVE (OR BACKFLOW  
PREVENTER IF REQUIRED)  
PRESSURE REDUCING VALVE  
(PRV) OR COMBINATION PRV  
AND RELIEF VALVE  
* 3/4" NPT MALE PLUG  
PIPE TO WITHIN 6" OF THE  
FLOOR OR A FLOOR DRAIN  
** THERMOMETER  
SENSING BULB  
UNION  
SHUT-OFF VALVE  
SYSTEM RETURN 3/4"  
* BOILER DRAIN, 3/4" NPT  
MALE X 3/4" HOSE  
NOTE: Cold return water temperature (Sustained temperatures below 140 degrees  
Fahrenheit) will lead to condensation or moisture in the firebox.This moisture can  
lead to creosote formation.To help minimize moisture and creosote, it is strongly  
recommended that some method of temperature balance is incorporated into the  
return system.  
* ITEMS SUPPLIED  
** OPTIONAL  
EXAMPLE OF TYPICAL TANKLESS DOMESTIC HOT WATER PIPING  
TEMPERED HOT WATER TO  
HIGH TEMPERATURE WATER  
SHOWERS AND FAUCETS  
( IF NEEDED )  
NOTE: ALWAYS REFER TO THE INDIVIDUAL COMPONENTS  
RECOMMENDED INSTALLATION INSTRUCTIONS FOR THE PROPER  
MOUNTING POSITION AND LOCATION WITHIN THE PIPING  
SYSTEM.  
CUSTOMER SUPPLIED SS  
PLATE HEAT EXCHANGER  
MIXING VALVE  
SHUT-OFF VALVE  
MIXING VALVE SET TO DESIRED WATER TEMPERATURE.  
NORMALLY NOT MORE THAN 120 DEGREES.  
INLET  
DOMESTIC WATER  
OUTLET  
HOSE BIB TO BACKFLUSH COIL IF NEEDED  
OUTLET  
DOMESTIC WATER  
INLET  
SAFETY RELIEF VALVE  
SHUT-OFF VALVE  
ISOLATION VALVE  
FLOW REGULATOR  
HOSE BIB  
COLD WATER SUPPLY  
FLOW REGULATOR WILL NEED TO MATCH THE GPM RATING OF THE DOMESTIC COIL.  
17  
Installation-Plumbing  
EXAMPLES OF TYPICAL DOMESTIC HOT WATER STORAGE PIPING  
EXAMPLE #2  
EXAMPLE #1  
CAUTION: No domestic water  
temperature  
CAUTION: No domestic water  
temperature  
HIGHER  
regulation shown  
TEMPERATURE  
WATER (IF NEEDED)  
regulation shown  
FROM BOILER  
FROM BOILER  
TEMPERED HOT WATER FOR  
SHOWERS AND FAUCETS  
COLD  
HOT  
COLD  
HOT  
MIXING VALVE  
MIXING VALVE SET TO DESIRED WATER TEMPERATURE.  
NORMALLY NOT MORE THAN 120 DEGREES.  
DOMESTIC HOT  
WATER STORAGE  
HEATER WITH  
INTERNAL HEAT  
EXCHANGER  
CIRCULATOR  
DOMESTIC HOT  
WATER  
STORAGE  
CIRCULATOR  
HEATER WITH  
INTERNAL HEAT  
EXCHANGER  
NOTE: ALWAYS REFER TO THE INDIVIDUAL COMPONENTS RECOMMENDED  
INSTALLATION INSTRUCTIONS FOR THE PROPER MOUNTING POSITION AND  
LOCATION WITHIN THE PIPING SYSTEM.  
IN  
IN  
TO BOILER  
OUT  
TO BOILER  
OUT  
NOTE: ALWAYS REFER TO THE INDIVIDUAL COMPONENTS RECOMMENDED  
INSTALLATION INSTRUCTIONS FOR THE PROPER MOUNTING POSITION AND  
LOCATION WITHIN THE PIPING SYSTEM.  
EXAMPLE OF A TYPICAL MULTI-ZONE HEATING SYSTEM WITH A SINGLE  
CIRCULATOR AND INDIVIDUAL ZONE VALVES  
NOTICE: When installing with the Atmospheric Conversion, all  
of the pressurized system components shown are not  
necessary. Air vents or bleeders should be removed from the  
plumbing system to prevent air from entering the lines. Control  
dipswitch #6 must beON.  
AIR VENT (TYPICALLY  
INSTALLED IN THE HIGHEST  
ACCESSABLE LOCATION IN  
THE PIPING)  
AIR VENT  
BALANCING  
VALVE  
FROM ADDITIONAL ZONES  
ZONE 1  
ZONE 2  
ZONE 3  
ZONE VALVE  
UNION  
CIRCULATOR  
TO ADDITIONAL ZONES  
FROM BOILER  
SHUT-OFF VALVE  
UNION  
SYSTEM SUPPLY 3/4"  
TO BOILER  
NOTE: Cold return water temperature (Sustained temperatures below  
140 degrees Fahrenheit) will lead to condensation or moisture in the  
firebox.This moisture can lead to creosote formation.To help minimize  
moisture and creosote, it is strongly recommended that some method  
of temperature balance is incorporated into the return system.  
SYSTEM RETURN 3/4"  
18  
Installation-Plumbing  
NOTE: ALWAYS REFER TO THE INDIVIDUAL COMPONENTS RECOMMENDED  
INSTALLATION INSTRUCTIONS FOR THE PROPER MOUNTING POSITION AND  
LOCATION WITHIN THE PIPING SYSTEM.  
EXAMPLE OF A COMBINATION HIGH/LOW MULTI-ZONE HEATING SYSTEM  
WITH INDIVIDUAL ZONE CIRCULATORS  
NOTICE: When installing with the  
Atmospheric Conversion, all of the  
(HIGH TEMPERATURE) BASEBOARD HEAT  
pressurized system components  
shown are not necessary. Air vents or  
(LOW TEMPERATURE) RADIANT FLOOR HEAT  
bleeders should be removed from the  
plumbing system to prevent air from  
entering the lines. Control dipswitch  
#6 must beON.  
(LOW TEMPERATURE) RADIANT FLOOR HEAT  
AIR VENT  
AIR VENT (TYPICALLY  
INSTALLED IN THE HIGHEST  
ACCESSABLE LOCATION IN  
THE PIPING)  
NOTE: IF CIRCULATOR DOES NOT HAVE  
CHECK VALVE THEN A FLOW CONTOL  
VALVE WILL ALSO BE NEEDED AND  
INSTALLED IN THIS LOCATION  
SHUT-OFF VALVE  
CIRCULATORS WITH INTEGRAL  
CHECK VALVE (SEE NOTE)  
ZONE 3  
ZONE 2  
ZONE 1  
MIX  
UNION  
SHUT-OFF VALVE  
HOT  
COLD  
FROM BOILER  
SYSTEM SUPPLY 3/4"  
THERMOSTATIC  
MIXING VALVE  
NOTE: Cold return water temperature (Sustained temperatures below 140 degrees  
Fahrenheit) will lead to condensation or moisture in the firebox.This moisture can lead to  
creosote formation.To help minimize moisture and creosote, it is strongly recommended  
that some method of temperature balance is incorporated into the return system.  
TO BOILER  
SYSTEM RETURN 3/4"  
HOT WATER  
HEATING COIL  
TO BE SIZED  
EXAMPLE OF A TYPICAL FORCED HOT AIR HEATING SYSTEM  
WITH THE BOILER DIRECT TO AN IN DUCT HOT WATER COIL  
NOTE: ALWAYS REFER TO THE INDIVIDUAL COMPONENTS  
RECOMMENDED INSTALLATION INSTRUCTIONS FOR THE  
BY INSTALLER  
NOTICE: When installing with the Atmospheric Conversion, all of the  
pressurized system components shown are not necessary. Air vents  
or bleeders should be removed from the plumbing system to prevent  
air from entering the lines. Control dipswitch #6 must beON.  
PROPER MOUNTING POSITION AND LOCATION WITHIN THE  
PIPING SYSTEM.  
AIR VENT  
AIR FLOW  
AIR FLOW  
FLOW CHECK  
SYSTEM SUPPLY 3/4"  
* AUTOMATIC AIR VENT  
* TEMP/PRESSURE  
GAUGE  
* PRESSURE RELIEF VALVE  
EXISTING  
GAS / OIL  
FURNACE  
OR  
PURGE & BALANCE  
VALVE  
SHUT-OFF  
UNION  
VALVE  
ELECTRIC  
HEAT  
PUMP  
RETURN  
AIR FLOW  
* 3/4" NPT MALE PLUG  
PIPE TO  
WITHIN 6" OF  
THE FLOOR  
OR A FLOOR  
DRAIN  
NOTE: NEVER INSTALL HOT WATER  
COIL ON THE RETURN SIDE  
OF THE HEATING SYSTEM  
SHUT-OFF VALVE  
CIRCULATOR  
UNION  
SYSTEM RETURN 3/4"  
SHUT-OFF VALVE  
* BOILER DRAIN,  
3/4" NPT MALE  
3/4" HOSE  
X
COLD  
WATER  
SUPPLY 1/2"  
* ITEMS SUPPLIED  
CHECK VALVE (OR BACKFLOW  
PREVENTER IF REQUIRED)  
PRESSURE REDUCING VALVE  
(PRV) OR COMBINATION  
PRV AND RELIEF VALVE  
EXPANSION TANK  
(DIAPHRAGM TYPE)  
(SIZED FOR TOTAL  
SYSTEM VOLUME)  
NOTE: Cold return water temperature (Sustained temperatures below 140 degrees Fahrenheit)  
will lead to condensation or moisture in the firebox.This moisture can lead to creosote  
formation.To help minimize moisture and creosote, it is strongly recommended that some  
method of temperature balance is incorporated into the return system.  
19  
Installation with A hot Air System  
Electrical interconnection of the BH60 to an existing heat pump, or fuel-fired hot air furnace:  
Interconnection with a heat pump will generally require a second thermostat to be installed. It is recommended  
that a new electronic thermostat be installed as close to the existing thermostat as possible. Installing within one  
foot of the existing thermostat is recommended for ease of interconnection and similar temperature sensing ability.  
If programmability is desired, both thermostats should have this capability. If only the new thermostat is  
programmable, you’ll need to keep the existing thermostat set several degrees below the lowest programmed  
temperature setting of the new thermostat. NOTE: In this configuration, if the BH60 cannot maintain the desired  
thermostat setting, the room will be allowed to cool to the lower set point of the existing thermostat before allowing  
the heat pump to operate.  
Special note: Even if the heat pump has a multi-stage thermostat, it cannot be re-wired to make the first stage control  
the BH60, and the second stage control the heat pump. All multi-stage heat pump thermostats are interconnected  
so that the compressor unit and/or the changeover solenoid activate with the first stage only.  
Controlling the existing furnace fan during overheat situation.  
Following the wiring diagram on the next page, you will need to supply and install a piece of 18/3 Thermostat  
wire between the low-voltage control terminal strip on the upper left-hand side of the BH60’s control cover, to the  
low-voltage control of the existing furnace.  
Note: Some systems may have external terminals and some may have them enclosed within the unit. If the  
connections to the exisitng system need to be made internally, be sure to use the proper protective grommet  
or connector where passing through the cabinet of the existing unit.  
If the wiring used does not match the colorings listed, follow the corresponding numbers on the terminal strips  
to ensure proper connection.  
Step 1. Disconnect electrical power to the existing heating system.  
Step 2. Install the above mentioned thermostat wire between the two systems  
Step 3. Connect the three (3) wires to the BH60 control terminal strip as indicated.  
Step 4. Remove the green wire which comes from the exisiting thermostat and connects to the terminal marked  
“G” on the existing system and splice it to the green (or #1) wire from the BH60.  
Step 5. Connect the white wire (or #5) from the BH60 to the “G” terminal of the existing system. This white wire  
should be the only wire connected to “G”.  
Step 6. Now, the red (#3) wire from the BH60 should be added to the “R” terminal of the existing system. Do not  
remove or replace any existing wires from “R”, just add this one to them.  
Restore power to the existing system only. Using the existing thermostat, increase the setting to verify that the  
system works as it did prior to the interconnection. Increase and decrease the thermostat a few times to verify  
proper reaction. In the case of a heat pump system, be sure the outdoor compressor unit is also cycling. Notice:  
Most compressors have a built in lockout timer (usually 5 minutes) so you may need to wait between thermostat  
adjustments to verify proper operation.  
Once you are certain that nothing changed with the operation of the existing system, turn the existing system’s  
thermostat down far enough that it won’t come on during the test. Connect power to the BH60, and turn on the  
circuit breaker on the front of the unit. With the control in the “OFF” position, turn the feed adjuster knob to “Test”.  
When the OVERHEAT SAFETY ZONE light illuminates, the fan on the existing system should come on. Be sure  
that the fan is the only thing on. There should be no power to the compressor or the oil or gas burner.  
20  
Installation with A hot Air System  
Existing T'stat  
New T'stat  
set 3° below new t'stat  
set 3° above existing t'stat  
W1 O/B  
W1 O/B  
L
Y
G
R
C
L
Y
G
R
C
SPLICE  
( by installer )  
Existing T'stat  
Wiring  
New T'stat Wire  
( by installer )  
LOW VOLTAGE  
SPLICE  
( by installer )  
W1 O/B  
L
Y
G
R C  
Through grommet  
in control cover  
LOW VOLTAGE  
LOW VOLTAGE 24 VAC COIL  
( by installer )  
New T'stat Wire  
( by installer )  
8
7
HIGH VOLTAGE ( L1 )  
L
6
5
( by installer )  
N
4
3
1
R2 RELAY  
Grainger# 2XC01- Omron LY2F 24V  
( by installer )  
HIGH VOLTAGE ( N )  
HIGH VOLTAGE ( ORANGE) from control board  
8
7
SPLICE  
( by installer )  
6
5
4
3
1
R1 RELAY  
Grainger#2XC02-Omron LY2F 120V  
3
5
1
RED  
WHITE  
GREEN  
O/A sensor terminals  
The top three screws only  
on the 5 pole terminal strip  
21  
Installation with A hot Air System - fan only capable  
Existing T'stat  
New T'stat  
set 3° below new t'stat  
set 3° above existing t'stat  
W1 G  
R
C
W1 G  
R
C
SPLICE  
( by installer )  
New T'stat Wire  
( by installer )  
Existing T'stat  
Wiring  
LOW VOLTAGE  
Through grommet  
in control cover  
LOW VOLTAGE  
LOW VOLTAGE 24 VAC COIL  
( by installer )  
New T'stat Wire  
( by installer )  
8
7
HIGH VOLTAGE ( L1 )  
L
6
5
( by installer )  
N
4
3
1
R2 RELAY  
Grainger#2XC01-  
Omron LY2F 24V  
( by installer )  
HIGH VOLTAGE ( N )  
HIGH VOLTAGE ( ORANGE) from control board  
8
7
SPLICE  
( by installer )  
6
5
4
3
1
R1 RELAY  
Grainger#2XC02-  
Omron LY2F 120V  
O/A sensor terminals  
The top two screws only  
on the 5 pole terminal strip  
22  
Connection with a 2-wire hot air system  
EXISTING BURNER / FAN SYSTEM  
( GAS, OIL, ELECTRIC)  
n
e t R u r  
e u N t  
o t H  
e t R u r  
n
o t H  
factory wiring  
to circulator outlet  
23  
Connection with a wireless thermostat  
WIRELESS THERMOSTAT WIRING  
BROWN to control board  
LT.BLUE to control board  
BROWN  
LT.BLUE  
L
N
GREEN/YELLOW  
Installer Supplied  
Wireless T’stat  
Receiver  
ORANGE from control  
VIOLET from control  
GREEN/YELLOW  
8
7
WHITE  
RED  
6
5
4
3
1
GREEN  
R1 RELAY  
Grainger#2XC02  
Omron LY2F 120V  
LOW VOLTAGE  
LT.BLUE  
BROWN  
BROWN  
1.5 AMP  
AUX. OUTLET  
NON SWITCHED,  
CIRCUIT BREAKER  
PROTECTED  
2 AMP-CONTROLLED  
CIRCULATOR OUTLET  
/AUX. DUMP ZONE  
EXTERNAL WIRING FOR UNITS WITH 4 POLE TERMINAL STRIP  
WHEN USING AN RC T'STAT or OTHER DUAL T'STATS  
INSIDE EXISTING HVAC CONTROL SECTION  
EXISTING THERMOSTAT WIRE  
WIRENUT SPLICE  
8
7
R2 RELAY  
Grainger #2XC01  
Omron LY2F 24V  
GREEN  
6
5
RED  
4
3
1
GREEN  
GREEN  
( by INSTALLER )  
R
G
Y
O/B  
C
L
W1  
18/2 THERMOSTAT WIRE  
( by INSTALLER )  
4 POLE TERMINAL STRIP  
LEFT SIDE OF CONTROL COVER  
R1  
RED  
BLUE  
3
5
FAN/ZONE CONTRL  
FAN/ZONE CONTRL  
3
5
N.O. contacts  
WHITE  
BLUE  
OUTSIDE AIR SENSOR  
OUTSIDE AIR SENSOR  
EXISTING INTERNAL WIRING of HF60  
24  
Installation  
Draft Test Procedure  
After the venting is completed, the firebox draft will need  
to be checked and possibly adjusted.After removing the  
plug bolt from the draft hole (3/16” hex key wrench)  
shown in Fig. 9, insert the draft meter tube. The hopper  
lid must be latched during this test. (It is recommended  
that the draft meter have a scale of 0 to 1” WC.)  
Turn the feed adjuster to “Test”. this will start the  
combustion blower and allow you to check and record  
the High Draft ______ - IWC date _______ The  
maximum draft allowed is -.9” Water Column (-224 Pa).  
There is no adjustment for the High Draft, other than  
re-positioning the combustion blower fan blade on its  
shaft, or a change in the venting configuration.  
After the first 60 seconds the “Test” mode lowers the  
combustion blower voltage to the Low Burn voltage.  
During this lowered voltage cycle, the Low Draft must  
be checked and adjusted if necessary. The recommended  
low draft setting should be between -.45 and -.55 IWC.  
Depending on the amount of vertical rise, it may not be  
possible to get a low draft reading in this range. In this  
case, re-positioning the fan blade further on the motor  
shaft may be helpful.  
Draft  
Testing Port  
Fig. 9  
Test”  
There is a low draft voltage adjustment screw located  
through the small hole to the right of the Igniter Light.  
See Fig. 10. Adjusted Low Draft is __________ -IWC.  
To increase the draft in higher altitudes, kit #  
1-00-232059 High Altitude Intake Reduction, may be  
needed.  
Don’t forget to turn the feed adjuster off of “Test”, and  
Low Draft  
Adjustment Pot  
reinstall the draft test plug bolt into the boiler.  
CAUTION: Hot While In Operation. Do  
Not Touch. Keep Children, Clothing And  
Furniture Away. Contact May Cause Skin  
Burns. See Nameplate And Instructions.  
Fig. 10  
High altitude kit #1-00-232059.  
Install this ring to increase draft in higher altitude  
installation locations.  
WARNING: Keep Doors Closed During  
Operation.  
WARNING: Do Not Store Fuel or Other  
Combustible Material Within Installation  
Clearance Area.  
WARNING: Risk of Fire - Do Not Operate  
With the Flue Draft Exceeding -.9” Water  
Column (-224 Pa).  
25  
Operation  
Power Light  
Feed adjuster  
Indicates power to the  
control board. (Ready)  
Sets the maximum feed rate  
Test  
Combustion blower, feed motor  
and safety dump zone are fully  
energized for the first minute.  
Then, the combustion blower  
will stay on low.  
Status Light  
Will be lit anytime the unit is  
in operation.  
Overheat Saftey Zone Light  
Indicates that the boiler water  
temperature has reached 210  
Degrees F.  
Lighting Mode Selector  
Switched between Auto and  
Manual lighting.  
Mode Selector/Min Temp  
Dial  
Used to turn the boiler on  
or off and set the desired  
minimum operating  
temperautre of the boiler.  
Combustion Blower Light  
Indicates Power to  
combustion blower  
Feed Motor Light Indicates  
Power to the feed motor.  
Diagnostic Port  
For maintenance only.  
Requires special DDM monitor  
supplied to trained technicians  
exclusively.  
Igniter Light  
Indicates power to the igniter  
Max Temp dial  
The “Max Temp Dial” is used to set the desired maximum operating temperature  
of the boiler.  
Status light error messages:  
7 Blinks: Boiler water overheat saftey shut down. This  
requires a manual reset by cycling the main power off for a  
few seconds and re-connect.  
3 Blinks: Indicates that the ESP (Exhaust Sensing Probe)  
has gone out of range too many times. If the unit is operating  
correctly, perform a manual reset by cycling the main power  
off at the circuit breaker for a few seconds. If the 3 blinks  
persist, contact your service technician.  
Explanation and Importance of the OverHeat Safety Zone  
When the unit is operating at High burn, and all demand from  
the heating system stops, the control will reduce the feed  
rate and shut down completely as necessary. This may take  
several minutes, and the remaining heat may cause the water  
temperature to continue to rise. When the water temperature  
gets too high, the OVERHEAT SAFETY ZONE light on the  
control will illuminate and the relay R1 is energized. This will  
close contacts #5 and #3 (Fan Contacts on the interconnection  
Page 20), and will also energize the controlled circulator  
outlet, for the hot water dump zone.  
4 Blinks: Indicates mis-communication with the aquastat, or  
the aquastat is not attached properly. May require a manual  
reset (turn off power at circuit breaker). Note that in some  
optional control methods, this status will occur during normal  
operation and reset automatically.  
5 Blinks: (InAuto Light Mode Only) Indicates that the igniter  
has failed to light the fire after 40 Minutes. To reset - Turn  
the Mode Selector/Min. Temp. to OFF and then back to the  
desired temperature.  
When using a hot water coil in an air duct system, if you  
do not want the living space heated beyond the thermostat  
setting during an over heat dump, an alternate dump zone  
will need to be installed and some internal control re-wiring  
will be necessary.  
6 Blinks: Indicates that the control has calculated poor or  
incomplete combustion occurring for 25 or more minutes.  
A six blink status may occur if the stove is allowed to run  
out of pellets. To reset, turn Mode Selector/Min Temp dial  
to “OFF” then back on to the desired temperature. If the unit  
was not out of pellets, see Troubleshooting section, Page 38,  
for more details.  
label from unit control panel showing outlets  
26  
Operation  
Setting The Boiler Temperature  
Without the Outdoor Air Temp - Sensor Installed  
To set the maximum boiler water temperature, simply  
turn the Max. Temp. water temperature dial to the  
desired setting. The control and the boiler will then  
perform to achieve and maintain the set temperature.  
The Min. Temp. Knob is the boiler water temperature  
minimum, or the lowest temperature the water will  
go before the unit re-starts. Turning the knob fully  
counterclockwise is the “OFF” position, while turning  
the knob clockwise, past the 140 degree marking, is the  
“ON” position.  
With The Outdoor Air Temp - Sensor Installed  
Maximum boiler temp setting is as described above,  
with the added feature of automatic maximum water  
temp controlled by the OAT sensor.  
The MIN. TEMP. knob, in addition to being the mode  
setting (on or off), also has the function of setting the  
minimum boiler water temperature. This would be the  
lowest boiler water temperature that you want to have  
based on the following factors;  
WATER TEMPERATURE  
1.) Outdoor Air Temperature (OAT)  
2.) Domestic Hot Water Use  
a.) Hot Water Coil Option  
b.) Indirect Hot Water Storage  
3.) Overall Volume of the Heating System  
MAX. TEMP.  
Control Board Operation  
MIN. TEMP.  
Aquastat Sensor - This sensor is located behind the  
control panel. This sensor, along with the outdoor air  
sensor, is what the control board uses to regulate the burn  
rate based on the observed conditions. (Boiler Temp. &  
Outdoor Air Temperature)  
The boiler is designed to withstand lower return water  
temperatures. However, extended return temperatures below  
140 degrees F can cause condensation.  
Outdoor Air Temp - Sensor (OAT): This sensor is  
located outside the building (on the north side of the  
house and out of direct sunlight). The Outdoor Air  
Sensor is used to perform hot water reset based on  
outdoor air temperatures.  
When the OAT sensor is installed, at 20° F. or below  
(outside temperature), the boiler will operate at the  
temperature set on the MAX. TEMP. knob. The boiler  
water temperature will decrease by 1 degree F. for  
every 1 degree F. in temperature rise (above 20°) of the  
outdoor air.  
NOTE:  
If the system is run at the lower temperature settings,  
conditions of the firebox, boiler tubes, secondary ash chamber  
and venting should be monitored closely. If any indications  
show excess condensation, the boiler water temperature will  
need to be increased until condensation does not occur.  
NOTE: Pellet Boiler Outdoor Air Reset Operation  
Graph located on page 28.  
27  
Operation  
28  
Operation  
Starting A Fire Automatically  
1. Turn Mode Selector to “OFF”.  
This resets the control in addition to turning it off.  
2. Clean Burnpot with scraper.  
This is typically a weekly maintenance procedure, but,  
depending on the fuel being burned, may need done  
more frequently. Cleaning the burn pot with the scraper  
with a small amount of new fuel in the bottom is not a  
problem. First, scrape the ashes from the front of the  
burn pot into the ash pan. Then scrape the hole grid  
surface downward into the burn pot. When the stove is  
ignited these scrapings will be pushed out by the feeder.  
CAUTION: Wear Heat-Resistant GlovesTo Perform  
The Scraping Procedure.  
Access the burnpot through the firebox door. Scraping  
can be done while the unit is in operation. *see caution  
3. Fill Hopper with pellets.  
Before refilling the hopper, check for excessive fines  
in the bottom of the hopper. Fines are small pieces of  
broken pellets (sawdust). Fines do not flow easily and  
often build up on the hopper funnel bottom angles.  
These fines can be pushed into the feeder opening and  
then fill the hopper with pellets. As the system works,  
they will be burned.  
29  
Operation  
4. If Starting After an Empty Hopper, Turn Feed  
Adjuster to “TEST” (for one 60 second cycle). This  
will charge pellets into the auger tube and also allow  
you to check the motors for operation. NOTE: The  
auger motor will not operate with any of the doors  
or hopper lid open.  
5. Turn Feed Adjuster to #5.  
If this is your first fire or you are trying a new fuel, set  
the feed adjuster to #5. This setting works well with the  
average wood pellets, but may need adjusted for your  
particular fuel. After you know a feed rate setting that  
works well for your application, stick with that setting.  
NOTE: You know your feed rate is too high when:  
The overheat safety feature is energized each time the  
heating zone demand turns off during a high burn. OR,  
If unburned or partially burned pellets are found in the  
ash pan. (this may also indicate a need for scraping the  
burn pot)  
If you need to keep the feed adjuster on its maximum  
setting, your unit is under-sized for the heating system.  
Continuous operation at maximum burn rate may cause  
pre-mature failure of the firebox baffles.  
Note: The firebox baffles (#1-10-232052) are  
considered to be a consumable item, and are  
therefore not covered by the product warranty.  
6. Flip the IgniterSwitch up into the “AUTO” position.  
due to low water temperature, the initial start will be  
a longer process than when the water temperature  
is closer to the minimum setting.  
WATER TEMPERATURE  
7. Turn the MAX. TEMP. Dial on the control board to  
the desired temperature. This setting must always be at  
least 5° F. higher than the MIN. TEMP. setting.  
WARNING: HOT WHILE IN OPERATION.  
KEEP CHILDREN, CLOTHING, AND  
FURNITURE AWAY. CONTACT MAY CAUSE  
SKIN BURNS.  
MAX. TEMP.  
MIN. TEMP.  
30  
Operation  
7. Open the firebox door to access the burnpot.  
8. Turn the MIN. TEMP. Dial on the control board  
to the desired Minimum temperature. This will start the  
lighting process if the temperature at the aquastat sensor  
is approximately 5° F. less than the set temperature on the  
MAX TEMP. dial.  
Fig. 13  
9. Fill hopper with pellets and remove ashes as required.  
8. Fill the burnpot with pellets as shown.  
See Fig. 14. Only fill level with the front edge.  
( ------- DO NOT OVERFILL ------- )  
Type of Fuel  
Use pelletized wood only. The lower the ash content of  
the pellets the less cleaning that will be needed of the heat  
exchanger tubes. The cleaner these tubes are kept, the more  
efficient the boiler will be.  
NOTE: Do not burn garbage, gasoline, naphtha, engine oil,  
or other inappropriate materials in this appliance.  
Store pellets in the manufacturer’s wrapping until needed  
to prevent pellets from absorbing moisture. Do not store  
fuel within the appliance installation clearances, or within  
the space required for fueling, ash removal, and other  
routine maintenance operations.  
Fig. 14  
9. Have matches or other ignition source ready.  
Never attempt to start a fire if there is no power  
or if the combustion blower is not operating.  
10. Turn Mode Selector to desired MIN TEMP setting.This  
will start the combustion blower and allow the ESPto control  
the fire in relation to the MAX TEMPDial setting. (The MAX  
TEMP dial setting must always be set above the MIN TEMP  
setting) Once the fire is well established the MAX TEMPdial  
can remain on any temperature setting desired.  
Never open the hopper lid during a fire if there  
is no power or if the combustion blower is not  
operating.  
Lighting A Fire Manually  
DURING MANUAL OPERATION:  
Lighting the fire manually will not be necessary unless  
the ignition system fails.  
SPECIAL NOTE: When the Switch is set to Manual  
ignite position, the boiler will function as in auto mode,  
except the fire will not be allowed to go out. It will only  
be allowed to go to a minimum burn rate between the  
times the aquastat is calling for heat. This rate is about  
1.1 pound of fuel per hour. If used in manual mode, be  
sure there is an overheat dump in place. Note that if the  
overheat dump zone does not provide sufficient cooling,  
and the water temperature continues to rise, the feed  
motor will be forced to shut off. Because the unit is set  
on Manual Ignition, it will not re-ignite when the water  
temperature cools below the settings.  
Follow steps 1 through 5 of the instructions for automatic  
lighting.  
6. Flip the Igniter Switch Down into the “MANUAL-  
LIGHT” position. See Fig. 12.  
Fig. 12  
31  
Operation  
11. Apply starting gel as shown in Fig.15  
12. Light The Starting Gel With A Match.  
13. Close The Doors  
Fig. 15  
The fire will light and the control will adjust the rate of  
burn to the proper level, according to the MAX TEMP  
dial setting.  
NOTE: Stirring the starting gel into the pellets usually  
allows the fire to become established quicker.  
CAUTION: Avapor flash could occur if too much time  
is allowed to pass before lighting the starting gel.  
NOTICE: when burning the boiler in the  
manual ignition mode, there must be an  
overheat dump zone incorporated into the  
plumbing system.  
CAUTION: Care must be taken not to get starting gel  
on your hands or clothing. Serious burns could occur  
during the lighting process.  
CAUTION: Never try to apply more starting gel to an  
already burning fire, or a fire with smoldering pellets.  
If heating demand stops during manual operation, the  
control will take the unit to low burn. If no heat is used  
during this time, the water temperature may continue  
to rise to the point at which the feeder will be turned  
off and the fire will go out. This will require a manual  
re-start of the system. (see page 26 “7 Blinks”)  
“NEVER USE GASOLINE, GASOLINE-TYPE  
LANTERN FUEL, KEROSENE, CHARCOAL  
LIGHTER FLUID, OR SIMILAR LIQUIDS TO  
START OR “FRESHEN UP “ A FIRE IN THIS  
BOILER. KEEP ALL SUCH LIQUIDS WELL  
AWAY FROM THE UNIT WHILE IN USE”.  
Solid-fuel burning appliances need to be cleaned  
frequently because soot, creosote, and ash may  
accumulate. If you suspect a chimney/vent pipe fire do  
the following:  
1. Call the fire department.  
2. Remove fuel from the burn pot using the burnpot  
scraping tool to scrape the pellets into the ash pan.  
3. Remove the ash pan from the unit and take outside.  
Do not place the ash pan on a combustible material.  
4. Turn off circuit breaker at unit.  
Fig. 16  
5. Do not use the unit until a qualified person has  
inspected your appliance and venting.  
32  
maintenance  
Burnpot Cleaning:  
Scrape the burnpot to  
remove any carbon  
deposits which may  
have formed.  
The burnpot should be cleaned no less than once a week.  
For best operation the burnpot should be cleaned every  
time the hopper is filled with pellets. The fire does not have  
to be out to scrape the burnpot although it is recommended  
the boiler be on minimum burn at the time of cleaning.  
Scraping can be done  
while the boiler is in  
operation, accessed  
through the firebox  
door opening. Wear  
gloves to protect  
from burns.  
CAUTION: Wear Gloves To Prevent Burns.  
Use the flat end of the scraper provided to scrape down over  
the holed surface of the burnpot grate. See Fig. 17. It is  
not necessary to clean out the scrapings from this cleaning  
because they will be pushed out as the auger operates.  
Note: Make a special effort to scrape the bottom inside  
corners of the burnpot where the auger tube enters the  
burnpot. Carbon deposits can build up over time in this  
area that may cause a restriction to the flow of pellets into  
the burnpot.  
Note: The end of the scraper may need sharpened  
occasionally, for best results.  
Fig. 17  
While scraping the burnpot, you can also use the scraper tool  
to tap on each of the visible heat exchange spirals. This will  
help to maintain maximum efficiency between cleanings.  
Cleaning the Burnpot Air Chamber:  
This area only needs to be cleaned twice a heating season,  
unless excessive buildup is noticed during scheduled  
cleanings.  
There is a cover on the front of the burnpot to gain access to  
the air chamber. The cover is held into place by two thumb  
screws. Loosen the thumb screws and remove the cover. See  
Fig. 19. The air chamber can be cleaned of any ash that has  
fallen through the holes during operation and cleaning.  
Burnpot  
cleanout cover  
NOTE: ALWAYS REMEMBER TO CLOSE THE CLEANOUT  
COVER AFTER CLEANING.  
Feeder Chamber (Fig. 20):  
Fig. 19  
This chamber may get a buildup of fines from the feeder  
mechanism movement. This area should be checked and  
cleaned at least once a year.  
To remove the feeder cover:  
• Loosen the 5/16” wing nut.  
Fines area  
• Slide the cover off of the threaded stud and lift upward.  
• Inspect and clean the inner chamber as necessary. See Fig. 20.  
There is a removable plate in this area that deflects fines  
into the auger. To remove this plate, roll it out under the  
pusher arm.  
• Reinstall the cover making certain it is centered on the feeder  
body and hand-tighten the wing nut.  
Feeder cover Fig. 20  
33  
maintenance  
Inner Refractory Lining  
The firebox and heat exchanger tube access areas are  
lined with high-temperature, fibrous ceramic insulation  
panels (much like spacecraft tiles). The surface of these  
panels is hardened to resist normal wear from brushing  
with a non-metal brush. The panels are not designed  
to be cleaned with the scraper or other sharp objects.  
Caution must be taken when cleaning these panels  
because damage to them is not covered by the warranty.  
The ash pan slides into the unit on a rail system.This keeps  
the ash pan from contacting the sides and floor refractory  
panels. Caution must be taken to ensure there is nothing on  
the floor surface prior to inserting the ash pan.  
Ash Removal  
It is recommended to remove the ashes when the boiler  
is not in operation. This lessens the chances of coming in  
contact with hot surfaces. Ashes can be removed while  
in operation but, extra care must be taken including  
wearing protective gloves.  
Firebox Refractory  
Linings  
Open The Firebox Door  
Swing the latch downward and open the door as shown in  
fig. 21.  
Fig. 21  
NOTE: Keep hopper lid, and firebox door closed during  
operation and maintain all seals in good condition. Air  
leaks will cause low draft conditions, which will result  
in feeder shutdown.  
Soot and Flyash: Formation and Need for  
Removal  
Disposal of Ashes:  
Ashes should be placed in a steel container with a  
tight fitting lid. The closed container of ashes should  
be moved outdoors immediately and placed on a non-  
combustible floor or on the ground, well away from all  
combustible materials, pending final disposal. If ashes  
are disposed of by burial in soil or otherwise locally  
dispersed, they should be retained in the closed container  
until all cinders have thoroughly cooled. Other waste  
shall not be placed in this container.  
The products of combustion will contain small  
particles of flyash. The flyash will collect in the exhaust  
venting system and restrict the flow of the flue gases.  
Incomplete combustion, such as occurs during startup,  
shutdown, or incorrect operation of the boiler will lead  
to some soot formation which will collect in the exhaust  
venting system. The exhaust venting system should  
be inspected at least twice monthly until an apropriate  
cleaning schedule is determined.  
34  
maintenance  
Firebox Baffle Removal  
Spirals can be used to scrape the heat  
exchange tubes.  
Silicone sealing  
gasket  
The tabs go into the slots on the baffle and the latch flips  
downward to seal at the angle. Lift the latch and lift the baffle  
off of the tabs for removal. Ashes from the heat exchange  
tubes can be cleaned from this area. Sliding the firebrick  
from one side to the other will allow more space for baffle  
removal.  
Inspect all sealing gaskets to ensure a proper seal and  
re-install all components removed for cleaning.  
Note:Thereboxbaffles(#1-10-232052)areconsidered  
to be a consumable item. Check for signs of warping  
or damage, and replace if necessary.  
Cleaning  
To maintain maximum heating efficiency, this  
cleaning should be performed weekly during the  
burn season. The frequency of this cleaning will be  
directly related to the quality and quantity of fuel  
being consumed. Keep in mind that the cleaner the heat  
exchanger tubes are kept, the higher the heat transfer  
efficiency will be.  
Due to the ease of restarting, it is recommended that  
the boiler be turned OFF for an hour before cleaning.  
Start by removing the two firebox baffles as shown  
above, then reinstall the ash pan. Next, remove the top  
heat exchanger cover to expose the heat exchanger  
tubes. Vacuum this upper exhaust chamber. Some of  
the tubes contain a spiral baffle which you can use as a  
cleaning device. Simply work the spiral up and down,  
approximately 6 inches, to scrape the inside surface of  
the heat exchange tube(s). The removed debris will fall  
to the ash pan and on the angled chamber of the firebox.  
Once all tubes are cleaned, remove the ash pan and clean  
the remainder from the angles.  
CAUTION: For your safety, do not vacuum hot ashes  
or embers. Some portions will remain hot, long after  
shut-down. Wear gloves to protect skin from burns.  
CAUTION: Cleaning of the heat exchangers, flue  
pipe, chimney, and combustion blower fan, is  
especially important at the end of the heating season  
to minimize corrosion during the summer months,  
caused by accumulated ash.  
With a wisp brush, paint brush or a soot vac, clean  
the firebox walls and any fly ash that has accumulated  
in the burnpot, or burnpot opening.At this time you can  
scrape and clean the burnpot and fines cleanout area.  
35  
maintenance  
The boiler MUST be OFF at the circuit breaker, and  
COOL before you attempt to clean the combustion  
Blower Cover  
blower.  
The wire to the combustion blower doesn’t need to be  
disconnected during the cleaning process.  
Loosen the three (3) thumb screws about 4 turns each.  
See Fig. 23. Hold the motor head with one hand and the  
blower plate handle with the other hand. Pull outward  
on the plate handle until the complete unit comes loose.  
Now rotate the plate counter-clockwise about 1/8 turn.  
This will allow the complete assembly to be removed  
from the blower chamber.  
Latch  
Fig. 22  
Theexhaust sensing  
probe (ESP) is  
located here.  
Clean the blower fan blade and the blower plate sealing  
overlap. See Fig. 24.  
NOTE: Be careful not to bend the fan blade, this will  
throw the fan blade out of balance or it may rub the  
inner chamber, which may affect the performance of  
the boiler. Any horizontal and vertical flue pipe directly  
above the unit should be cleaned at this time  
Three Thumb Screws  
Fig. 23  
NOTE: The horizontal flue pipe directly above the  
boiler is the first place fly ash will settle, due to the  
slowing of flue gas velocity through horizontal pipe.  
Cleaning of horizontal venting pipes is very important  
to the efficiency of this boiler.NOTE: The exhaust  
probe sensing tip extends into this same area. CARE  
MUST BE TAKEN NOT TO DAMAGE THE ESP  
DURING CLEANING. Bending of the ESPwill make  
it difficult to remove if it should become necessary.  
See Fig. 23.  
Sealing Overlap  
Clean the boiler blower plate sealing overlap. See Fig  
24. Make sure there is no fly ash buildup that may block  
the easy flow of flue gases into the combustion blower  
inlet hole. (A flashlight may be necessary.)  
5” Double Bladed Fan  
(standard) #3-21-502221  
Fig. 24  
CAUTION: Inspect flue pipes, flue pipe joints and  
flue pipe seals regularly to ensure that smoke and  
flue gases are not entering the home.  
Combustion Blower Cleaning  
Remove the combustion blower cover.There are two  
latches that hold the shield in place (Fig. 22). Flip the  
latches up and pull the shield away from the boiler.  
36  
Special Insructions/ Power Failure  
Requirements as specified by CAN/CSA- B366.1  
Operation of the HF60 During a Power Failure - A supply of 120 VAC is required for operation. In  
the event of a power failure, the unit will not operate. The boiler can be powered alternatively using the  
Surefire 512 Battery Back-up system, or a generator. The generator must be properly filtered to maintain  
a constant sine wave of 60 cycle, with a steady 120 Volt output.  
EXAMPLE OF PIPING IN ACCORDANCE  
WITH (CAN/CSA-B366.1)  
A POWER FAILURE HEAT DISSIPATION LOOP  
TO NORMAL HEATING DEMAND  
(HIGH TEMPERATURE) BASEBOARD HEAT  
BASEBOARD MUST BE AT LEAST  
24" HIGHER THAN BOILER FOR  
PROPER GRAVITY FLOW  
MINIMUM OF 36" OF 3/4" FINNED BASEBOARD  
120VAC,NORMALLY OPEN,FULL FLOW,  
UNION  
SHUT-OFF VALVE  
SOLENOID VALVE or EQUIVALENT  
SYSTEM SUPPLY 3/4"  
NOTE: ALWAYS REFER TO THE INDIVIDUAL COMPONENTS  
RECOMMENDED INSTALLATION INSTRUCTIONS FOR THE PROPER  
MOUNTING POSITION AND LOCATION WITHIN THE PIPING  
SYSTEM.  
UNION  
SYSTEM RETURN 3/4"  
SHUT-OFF VALVE  
THE SOLENOID CAN BE POWERED  
FROM THE CONTROL PANEL  
OUTLET MARKED-  
PRV PIPE TO WITHIN 6" OF THE  
FLOOR OR A FLOOR DRAIN  
1/8Fiberglass Gasket #3-44-232043  
Door Glass #3-40-73363  
1/4”White Ceramic Gasket #3-44-232073  
Door Glass Cover Plate #2-00-232066  
(4) #10-32 Nuts #3-30-8010321  
Screen Plate #2-00-232016  
Screwdriver Slot  
Using a flat screwdriver, pry up and out to remove the screen plate. Remove the (4) 10-32 nuts  
with a 3/8wrench or socket. Remove the cover plate, the broken glass, and the gaskets. Install  
a new 1/8gasket, a new glass, and a new 1/4white gasket. Re-install the cover plate.While  
making sure that everything is centered, tighten the (4) nuts to secure the glass.To install the  
screen plate, insert it into the slots at the top of the opening, then push in the bottom.  
37  
Troubleshooting  
FEEdEr dOES NOT FEEd  
SmOkE IS vISIblE COmINg OuT OF vENT  
1. No pellets in hopper.  
1. Air-fuel ratio is too rich.  
A. Feed rate too high.  
B. Draft too low caused by a gasket leak.  
lOw hEAT OuTPuT  
2. Firebox draft may be too low for low draft pressure  
switch in feeder circuit to operate. Check for  
improperly closed doors, loose or missing  
gasket on doors or hopper lid, or a faulty pressure  
switch.  
3. Feed motor will not run until the ESP senses 170  
deg. F. Maybe you did not put enough pellets in  
the burn pot before lighting the fire manually.  
4. Something is restricting flow in the hopper or  
causing the slide plate to stick.  
1. Feed rate too low  
2. Draft too low because of gasket leak.  
3. Poor quality or damp pellets  
4. Combination of 1 and 2.  
helpful hints  
5. Feed motor has failed.  
PArTIAllY burNEd PEllETS  
1. Feed rate too high.  
Cleaning burn Pot  
Whenever your boiler is not burning, take the  
opportunity to scrape the burn pot to remove carbon  
buildup. A vacuum cleaner is handy to remove the  
residue. be sure of no hot embers if you use a  
vacuum.  
2. Draft too low. (Check burn pot clean-out slide and  
door gasket).  
3. Burn pot or heat exchanger tubes may need to  
be cleaned.  
4. Combination of all the above.  
Carbon buildup can be scraped loose with the fire  
burning using the special tool provided with your boiler.  
Scrape the floor and sides of the burn pot. The carbon  
will be pushed out by the incoming fuel. Always wear  
gloves to do this.  
5. #6 status blink: A 6 blink control board status  
indication is caused by poor or incomplete  
combustion. The Automatic Ignition circuit board  
has the ability to track the combustion through  
feed settings and ESP temperatures. When the  
control board has calculated poor or incomplete  
combustion, it will shut down the unit as a safety  
feature. (Poor or incomplete combustion is  
a contributor of creosote which may cause a  
chimney fire)  
removing Ashes  
Ashes can be removed while in operation, but extra  
care must be taken and always wear gloves.  
Maximum Feed Adjuster settings are not needed  
in most cases. Operating in the normal range (#4)  
is recommended when maximum heat output is not  
required. The ESP prevents the stove from being over-  
fired.  
A 6 blink status may be caused by several things:  
1. Blocked or partially blocked flue.  
2. Blocked or partially blocked inlet air.  
a. Backdraft damper on the inlet pipe may be stuck  
closed.  
Keep the boiler free of dust and dirt.  
b. If outside air is installed, the inlet cover may be  
blocked.  
3. The air chamber under the burnpot may be filled  
with fines and small bits of ash.  
4. The holes in the burnpot may be getting filled with  
ash or carbon buildup.  
5. Combustion blower fan may need cleaned.  
6. There is no fuel in the hopper.  
Fuel  
Pellet fuels are put into 3 categories in terms of ash  
content. Premium at 1% or less, Standard at 3% or  
less and all others at 3% or more.  
The BH60 is capable of burning all 3 categories  
of pellets, due to a patented feeder and burn pot  
system.  
SmOkE SmEll  
Seal the vent pipe joints and connection to unit with  
silicone.  
It should be noted, however, that higher ash content  
will require more frequent ash removal, scraping of  
the burn pot, and may provide less BTU’s per pound.  
Normally, standard and high ash pellets cost less  
than premium pellets and can be cost effective when  
burned in the BH60.  
FIrE hAS gONE OuT  
1. No pellets in hopper.  
2. Draft setting is too low.  
3. Something is restricting fuel flow.  
4. Feed motor or combustion blower has failed.  
5. Power failure or blown fuse.  
The moisture content must not exceed 8%. Higher  
moisture will rob BTU’s and may not burn properly.  
6. Firebox door or hopper left open.  
38  
Specifications  
39  
Wiring Diagram  
wiring diagram  
U G  
W H I T E 1 3 P I N P L  
R E D  
U E . B T L L  
C K A B L  
W H I T E  
G R E E N  
G R E E N  
W O  
G R E E N / Y E L L  
U E . B T L L  
W O N B R  
W O Y E L L  
U E . B T L  
C K A B L  
C K A B L  
U E . B T L L  
G R E E N / Y E L L  
W O  
N.O.CONTACTS  
LOW PRESSURE SWITCH  
40  
warranty  
ECO-CHOICE™ LIMITED WARRANTY  
Hearth & Home Technologies Inc., on behalf of its Heatilator® brand (”HHT”), extends the following warranty for all ECO-  
CHOICE™ furnace and boiler products (“Products”) that are purchased from an HHT authorized dealer.  
Warranty Coverage: Subject to the conditions, exclusions and limitations set forth below, HHT warrants to the original  
owner of the Products, and to any transferee taking ownership of the Products at the site of original installation within two  
years following the date of original purchase, that the Products will operate free from defects in material and workmanship  
under normal conditions and use, as described in the operating instructions furnished with the Product, during the warranty  
period described below. HHT will, at its option, repair or replace any Product covered by this warranty that is determined  
to be defective in material or workmanship.  
Warranty Period: The warranty period runs for six years, except for mechanical and electrical components, which are  
warranted for three years. The warranty period begins on the earlier of: (i) the date of invoice for the Product; (ii) in the case  
of new home construction, the date of first occupancy of the residence or six months after the date of sale of the Product by  
an HHT authorized dealer, whichever occurs first; or (iii) the date 24 months following the date of Product shipment from  
HHT, regardless of the invoice or occupancy date.  
Warranty Conditions: This warranty applies only to Products: (i) installed, operated, and maintained as recommended in  
the Product user’s manual; (ii) purchased through an HHT authorized dealer; (iii) while remaining at the site of original  
installation; and (iv) that have not been altered after leaving the factory.  
How to File a Claim: Claims must be made within the warranty period to the dealer who sold the Product. If that dealer  
cannot provide the warranty service, contact the nearest HHT authorized dealer. Additional service fees may apply if you  
are seeking warranty service from a dealer other than the dealer from whom you originally purchased the Product. Travel  
and shipping charges for parts are not covered by this warranty.  
Warranty Exclusions: This warranty does not cover the following: (1) consumable and normal wear items, including,  
without limitation, flame guides, grates, coal bars, afterburner hoods, fire brick, gaskets, paint, glass discoloration, burnpot  
housing weldments, burnpot grate weldments (pellet or corn), burnpot front plates (pellet or corn), burnpot front plate  
locks, corn auger extensions, ceramic inserts, and ceramic insert plates; (2) noise caused by minor expansion, contraction  
or movement of parts; (3) damage resulting from: (i) failure to install, operate or maintain the Product according to the  
installation and operating instructions and listing agent identification label furnished with the Product; (ii) failure to install  
the Product according to local building codes; (iii) shipping or improper handling; (iv) abuse, misuse, continued operation  
with damaged, corroded or failed components, accident, or incorrectly performed repairs; (v) environmental conditions,  
inadequate ventilation, negative pressure or drafting caused by tightly sealed construction, insufficient make-up air supply,  
or handling devices such as exhaust fans or forced air furnaces or other such causes; (vi) use of fuels other than those  
specified in the operating instructions; (vii) installation or use of components or accessories not supplied with the Product  
or authorized and approved in writing by HHT; (viii) modification of the product not expressly authorized and approved by  
HHT in writing; or (ix) interruptions or fluctuations of electrical power supply to the Product; (4) non-HHT components  
or accessories used in conjunction with the Product; (5) the Products’ capability to heat a desired space; information is  
provided to assist the consumer and the dealer in selecting the proper Product for the application; consideration must be  
given to Product location and configuration, environmental conditions, insulation and air tightness of the structure; or (6)  
additional or unusual utility bills incurred due to any malfunction or defect in Products.  
Limitations of Liability: Repair or replacement in accordance with the provisions of this warranty will be the owner’s  
exclusive remedy for and will constitute HHT’s sole obligation under this warranty, under any other warranty (express or  
implied), or in contract, tort or otherwise. No employee, agent, dealer, or other person is authorized to give any warranty  
on behalf of HHT. TO THE EXTENT ALLOWED BY LAW, HHT MAKES NO OTHER WARRANTY, EXPRESS  
OR IMPLIED, INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR  
PURPOSE. HHT WILL NOT BE LIABLE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES ARISING  
OUT OF DEFECTS IN OR USE OF THE PRODUCTS. Some states do not allow exclusions or limitation of incidental or  
consequential damages, so these limitations may not apply to you. This warranty gives you specific rights; you also may  
have other rights, which vary from state to state. The duration of any implied warranty is limited to the duration of the  
warranty period specified herein.  
41  
Testing label  
BH60  
8
Wood Pellets  
BH60  
Flooring must be non-combustible material extending
16” (US) or 18”(CAN) in front of the ash removal d
e revêtement de sol doit être de l'étendre de matériel incombustible 6” aux  
côtés, et 16” (USA) ou 18”(Canada) devant la porte d'enlèvement de cendre.  
WAfire - Do not operate with the flue draft exceeding  
-.9 in Water Column / -224Pa.  
ATTENTION: Risque de feu -Ne fonctionnez pas avec l'ébauche  
deconduite de cheminée excédant -.9 " colonne de l'eau / -224Pa.  
Hearth & Home Technologies  
352 Mountain House Road, Halifax, PA 17032  
3-90-232H  
42  
Service Parts  
bh105  
beginning manufacturing date: july 2009  
bioflow hydronic 105k Pellet boiler  
Ending manufacturing date: Active  
1
2
28  
3
27  
26  
4
5
25  
6
24  
23  
22  
21  
7
20  
8
9
10  
19  
18  
11  
12  
14  
13  
17  
15  
16  
IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement  
parts for your appliance please provide model number and serial number. All parts listed  
in this manual may be ordered from an authorized dealer.  
Stocked  
at depot  
ITEm  
dESCrIPTION  
COmmENTS  
PArT NumbEr  
1-10-72140A  
3-44-677185  
3-31-00927  
1-10-07330  
1-00-06143  
1-00-015605  
3-20-49447-5  
2-00-72158B  
3-20-6866  
1
Hopper Assembly  
Gasket, Hopper Throat  
Hopper Lid Spring Latch  
Control Board Plate, Studded w/label  
Control Board  
Y
Y
2
3
Y
Y
Y
Control Knob/Shaft  
25 Sets  
Pkg of 5  
Fuse, 6 AMP  
4
5
6
7
Feeder Cover Assembly  
Differential Switch  
Y
Red Nylon Knob  
3-31-72196  
1-10-72153A  
Swing Plate Assembly  
Additional service part numbers appear on following page.  
04/12  
Service Parts  
bh60  
beginning manufacturing date: may 2009  
Ending manufacturing date: Active  
IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement  
parts for your appliance please provide model number and serial number. All parts listed  
in this manual may be ordered from an authorized dealer.  
Stocked  
at depot  
ITEm  
description  
Plumbing Support Kit - Qty. 2 req.  
Firetube Cleanout Door Assembly  
Draft Section Refractory Side  
1/4-20 x 1-1/2" Wingscrew with Collar  
Draft Section Weldment  
COmmENTS  
PArT NumbEr  
1-10-232044-18  
1-10-232060-18A  
3-40-232054  
1
2
3
4
5
6
7
8
Qty. 2 req.  
Pkg of 10  
3-31-782124-10  
1-10-232011W  
3-44-232089  
Y
1/2" Foam Insulation Wrap Around  
1/2" Foam Insulation  
3-44-232088  
Hopper Assembly  
1-10-232034-18A  
1-00-375501  
Gasket, Hopper Top  
20 Ft  
Y
Y
Gasket. Hopper Throat  
3-44-677185  
9
Feeder Shield Rear  
1-00-232039-18  
3-44-232085  
10  
11  
12  
13  
14  
15  
1" Foil Faced Fiberglass Insulation  
UL Feeder Assembly  
refer to feeder page  
3-20-6866  
Differential Switch  
Y
Y
Tempco 450W Igniter  
3-20-00450  
1" Foil Faced Fiberglass Insulation  
Tube Cleanout Plate  
3-44-232086  
Qty. 2 req.  
Qty. 2 req.  
2-00-232008B  
2-00-232031-1B  
2-00-232031-2B  
3-40-232010  
Hopper Stiffener Bracket Left  
Hopper Stiffener Bracket Right  
Firebox Refractory Side  
16  
17  
18  
Burn Pot Scraper  
3-99-7498  
3-44-232094-1  
3-44-232094-2  
3-44-232094-3  
3-20-02679  
19  
Water Jacket Gasket  
Long Bottom  
Short bottom  
20  
21  
Air Pump  
Y
Y
Filter & Fitting  
1-00-02679  
1/4" Ceramic Paper Feeder Insulation  
3/4" NPT Square Plug  
3-44-232078  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
Qty. 4 req.  
3-10-00600  
Feeder Cover Left  
1-00-232096-18  
3-10-07560  
3/4" NPT Boiler Drain  
Outer Skin Left  
1-00-232026-18  
1-10-232005W  
3-50-05229  
Combustion Section Weldment  
Steel Sleeve Bushing 3/8 OD x 1/2 OAL  
Elevator Bolt 3/8-16 x 1-1/2"  
Firebox Cleanout Cover Retainer  
Tube Cleanout Cover Plate  
Tube Cleanout Latch  
Qty. 4 req.  
Qty. 2 req.  
Qty. 2 req.  
Qty. 2 req.  
3-30-937161501  
2-00-232056B  
2-00-232052B  
2-00-232009L  
Y
Additional service part numbers on the following page.  
02/12  
Service Parts  
bh60  
beginning manufacturing date: may 2009  
Ending manufacturing date: Active  
IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement parts for  
your appliance please provide model number and serial number. All parts listed in this manual may  
be ordered from an authorized dealer.  
Stocked  
at depot  
ITEm  
32  
description  
COmmENTS  
Qty. 2 req.  
PArT NumbEr  
3-20-1000  
3/8" Flex Connector  
Ceramic Insert  
33  
Pkg of 10  
3-20-05238-10  
3-00-03000  
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
34  
Flame Guide  
35  
Burnpot Assembly  
Clean Out Cover  
Thumb Screw  
1-10-232079A  
1-00-06623  
2 Sets  
Pkg of 10  
3-31-782108-10  
3-44-724114  
2-00-724104  
3-44-724115  
3-40-232015  
3-40-232093  
3-40-232006  
1-10-232049A  
1-00-232019-18  
1-00-232074  
3-40-5555  
36  
37  
38  
39  
40  
41  
42  
43  
Ceramic Insert Gasket  
Ceramic Insert Plate  
Burn Pot Gasket  
Firebox Refractory Rear  
Firebrick  
Firebox Refractory Bottom  
Ash Pan Assembly  
Ash Door Assembly  
Ash Door Spacer Set w/Gasket  
Glass 5.25 x 5.25  
Refractory  
3-40-232023  
1-00-232055-18  
1-00-06143  
44  
Control Board Plate Assembly  
Control Board  
Y
Y
Y
Fuse, 6 AMP  
Pkg of 5  
3-20-49447-5  
3-10-78427  
45  
46  
Pressure / Temperature Gauge  
Plumbing Assembly  
1-10-232080A  
1-00-232028A-18  
1-00-232028B-18  
1-00-232027-18  
3-21-08639  
Pre 004510191  
Post 004510191  
47  
Combustion Motor Cover  
48  
49  
50  
Outer Skin Front  
Combustion Blower  
Blade 5" Single  
Y
Y
3-20-502221  
3-31-004357  
1-10-73416  
External Retaining Ring  
Combustion Blower Mount  
Flex Conduit Support Bracket  
3/8" Flex Conduit  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
2-00-232071B  
1-00-25043  
7 Ft  
Y
Ash Door Hinge  
2-00-232020L  
1-10-232001W  
2-00-232053-8  
3-20-00844  
Water Jacket Weldment  
Spiral Fire Tube Baffle  
ESP Probe  
Pkg of 8  
Qty. 2 req.  
Y
Y
1/2" Foam Insulation  
2" Fiberglass Insulation  
Feeder Cover Right  
Outer Skin Right  
3-44-232087  
3-44-232090  
1-00-232097-18  
1-00-232025-18  
Additional service part numbers on the following page.  
02/12  
Service Parts  
bh60  
beginning manufacturing date: may 2009  
Ending manufacturing date: Active  
IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement  
parts for your appliance please provide model number and serial number. All parts listed  
in this manual may be ordered from an authorized dealer.  
Stocked  
at depot  
ITEm  
61  
description  
COmmENTS  
Qty. 4 req.  
PArT NumbEr  
3-31-00927  
Spring Latch  
Y
Y
Y
Y
62  
3/8"-16 x 1/4" Alloy Steel Black Oxide Cup Point SSS  
Touch up Paint (RED)  
Pkg of 25  
3-30-2014-25  
3-42-00018  
Circuit breaker 10 Amp (orange - on/off switch)  
High Altitude Intake Reduction  
3-20-334110  
1-00-232059  
3-20-232076  
Wiring Harness  
Y
#11 Feeder Assembly  
11.1  
11.15  
11.14  
11.12  
11.16  
11.2  
11.13  
11.11  
11.3  
11.10  
11.9  
11.4  
11.5  
11.8  
11.7  
11.6  
11  
UL Feeder Assembly  
1-10-232108A  
3-20-09302  
Pellet Feeder Gear Motor, 4RPM  
Feed Motor Fan Blade  
UL Feeder Cam  
11.1  
Y
Y
Y
Y
Y
Pkg of 3  
3-20-09302-3  
3-31-3014  
11.2  
11.3  
Feeder Air Crossover Kit  
9MM Silicone Tube  
1-00-67900  
5 Ft  
1-00-511427  
1-10-06810A  
3-44-72224-6  
1-10-72222  
Pellet Air Intake Assembly  
Gasket Feeder Air Intake  
UL Feeder Air Intake  
11.4  
11.5  
Pkg of 6  
Pkg of 10  
Y
11.6  
Gasket Ultra Air Intake  
Ultra Feeder Weldment  
UL Feeder Pusher Arm  
Fines Deflector  
3-44-677160-10  
1-10-72226S  
1-10-677187W  
11.7  
Y
Y
Y
11.8  
11.9  
No longer available 2-00-677138-10  
1-00-677122  
11.10  
11.11  
11.12  
11.13  
11.14  
11.15  
11.16  
Gasket, UL Feeder Cover  
Slide Plate Assembly  
Y
Y
Y
Y
Y
Y
1-10-677121A  
UL Feeder Auger Assembly  
Bearing Flange w/Hardware  
UL Feeder Gear Motor Bracket w/Grommet  
UL Feeder Cam Block  
3-50-00565  
1-00-04035  
1-00-247406  
3-00-677154  
02/12  
Notes  
At Harman, we build each product to a standard, not a price.  
This powerful heating appliance boasts uncompromising  
attention to detail and helps preserve our planet by using  
environmentally responsible fuels.  
(Signature of Boxer)  
Your premium quality hearth product designed and assembled  
by the experienced and skilled members at Harman in Halifax,  
PA, USA.  

Audiovox Mobile Video 128 8810 User Manual
Blaupunkt FRANKFURT RCM 82 User Manual
Canon EF 16 User Manual
Cateye CYCLOCOMPUTER CC RD400DW User Manual
Clarion DB625MP User Manual
Crown Boiler XBF EID User Manual
Focal Access 1 165 A3 User Manual
Huey Chiao HCB02 User Manual
JVC Digital Camcorder GZE300BUS User Manual
JVC GR AXM270 User Manual