Burnham MEGASTEAM MST629 User Manual

INSTALLATION, OPERATING AND  
SERVICE INSTRUCTIONS FOR  
MegaSteam™  
3-PASS OIL BOILER  
As an  
ENERGY STAR® Partner,  
Burnham Hydronics  
has determined that the  
MST288, MST396, MST513 and  
MST629 meet the  
ENERGY STAR®  
guidelines for Energy  
efficiency established by the  
United States Environmental  
Protection Agency (EPA).  
For service or repairs to boiler, call your heating contractor or oil supplier. When seeking  
information on boiler, provide Boiler Model Number and Serial Number as shown on Rating  
Label located on top of the boiler.  
Boiler Model Number  
Boiler Serial Number  
Installation Date  
MST  
Heating Contractor  
Phone Number  
Address  
Price - $3.00  
100618-01R4-5/08  
DANGER  
DO NOT store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other  
appliance.  
WARNING  
Improperinstallation,adjustment,alteration,serviceormaintenancecancausepropertydamage,personal  
injury or loss of life. Failure to follow all instructions in the proper order can cause personal injury or  
death. Read and understand all instructions, including all those contained in component manufacturers  
manuals which are provided with the appliance before installing, starting-up, operating, maintaining or  
servicing this appliance. Keep this manual and literature in legible condition and posted near appliance  
for reference by owner and service technician.  
This boiler requires regular maintenance and service to operate safely. Follow the instructions contained  
in this manual.  
Installation,maintenance,andservicemustbeperformedonlybyanexperienced,skilledandknowledgeable  
installer or service agency.  
All heating systems should be designed by competent contractors and only persons knowledgeable in  
the layout and installation of hydronic heating systems should attempt installation of any boiler.  
Installation is not complete unless a safety valve is installed into 1½"" x ¾"" NPT reducing bushing,  
mounted into rear section boss, at the back of rear section. See Unit-Pak Boiler Assembly and Steam  
Boiler Trim & Piping Sections of this manual for details.  
It is the responsibility of the installing contractor to see that all controls are correctly installed and are  
operating properly when the installation is completed.  
This boiler is suitable for installation on combustible flooring. Do not install boiler on carpeting.  
Do not tamper with or alter the boiler or controls.  
Inspect flueways at least once a year - preferably at the start of the heating season. The inside of  
the combustion chamber, the vent system and boiler flueways should be cleaned if soot or scale has  
accumulated.  
When cleaning this boiler, take precaution to avoid damage to burner swing door insulation. If damaged,  
or if there is evidence of previous damage, burner swing door insulation must be replaced immediately.  
Oil Burner and Controls must be checked at least once a year or as may be necessitated.  
Do not operate unit with jumpered or absent controls or safety devices.  
Do not operate unit if any control, switch, component, or device has been subject to water.  
Appliance materials of construction, products of combustion and the fuel contain alumina, silica, heavy  
metals, carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances which  
can cause death or serious injury and which are known to the state of California to cause cancer, birth  
defects and other reproductive harm. Always use proper safety clothing, respirators and equipment when  
servicing or working nearby the appliance.  
3
WARNING  
This boiler contains very hot water under high pressure. Do not unscrew any pipe fittings nor attempt  
to disconnect any components of this boiler without positively assuring the water is cool and has no  
pressure. Always wear protective clothing and equipment when installing, starting up or servicing this  
boiler to prevent scald injuries. Do not rely on the pressure and temperature gauges to determine the  
temperature and pressure of the boiler. This boiler contains components which become very hot when  
the boiler is operating. Do not touch any components unless they are cool.  
This boiler must be properly vented. The chimney must be inspected for any obstructions and cleaned  
priortoeachheatingseason.Acleanandunobstructedchimneyueisnecessarytoproducetheminimum  
draft required to safely evacuate noxious fumes that could cause personal injury or loss of life. Evidence  
of loose debris and or condensate induced stains at the base of the chimney flue, connector or smokepipe  
joints may be signs of condensing flue gases. Flue gas condensate is corrosive, which requires special  
consideration and must be addressed immediately. Refer to Section V, "Venting and Air Intake Piping".  
This boiler needs fresh air for safe operation and must be installed so there are provisions for adequate  
combustion and ventilation air.  
This boiler is supplied with controls which may cause the boiler to shut down and not re-start without  
service. If damage due to frozen pipes is a possibility, the heating system should not be left unattended in  
cold weather; or appropriate safeguards and alarms should be installed on the heating system to prevent  
damage if the boiler is inoperative.  
This boiler is designed to burn No. ꢀ fuel oil only. Do not use gasoline, crankcase drainings, or any oil  
containing gasoline. Never burn garbage or paper in this boiler. Do not convert to any solid fuel (i.e.  
wood, coal). Do not convert to any gaseous fuel (i.e. natural gas, LP). All flammable debris, rags, paper,  
wood scraps, etc., should be kept clear of the boiler at all times. Keep the boiler area clean and free of  
fire hazards.  
All boilers equipped with burner swing door have a potential hazard which, if ignored, can cause severe  
property damage, personal injury or loss of life. Before opening swing door, unplug burner power cord  
from receptacle located in lower right corner of jacket front panel and turn off service switch to boiler  
to prevent accidental firing of burner outside the combustion chamber. Be sure to tighten swing door  
fasteners completely when service is completed.  
TABLE OF CONTENTS  
I. Pre-Installation . . . . . . . . . . . . . . . . . . . .  
II. Unit-Pak Boiler Assy . . . . . . . . . . . . . . .  
7
9
VII. Oil Piping . . . . . . . . . . . . . . . . . . . . . . . 37  
VIII. System Start-Up . . . . . . . . . . . . . . . . . . 39  
IX. Maintenance & Service Instructions . . . 45  
X. Boiler Cleaning . . . . . . . . . . . . . . . . . . . 48  
XI. Trouble Shooting . . . . . . . . . . . . . . . . . 50  
XII. Repair Parts . . . . . . . . . . . . . . . . . . . . . 51  
III. Steam Boiler Trim & Piping . . . . . . . . . . . 22  
IV. Tankless & Indirect Water Heater Piping . 24  
V. Venting & Air Intake Piping . . . . . . . . . . 27  
VI. Electrical . . . . . . . . . . . . . . . . . . . . . . . . 32  
4
5
TABLE 1A: DIMENSIONAL DATA (SEE FIGURE 1)  
Dimensions (See  
Figure 1)  
Water Content (To Normal  
Water Line) - Gallons  
With Tankless  
Heat Transfer  
Surface Area  
- sq. Ft.  
Boiler  
Model No.  
Actual Shipping  
Weight (LB.)  
"A"  
"B"  
"C"  
Non-Heater  
Heater  
MST288  
MST396  
MST513  
MST629  
22-5/8"  
22-5/8"  
28-5/8"  
34-5/8"  
24"  
24"  
30"  
36"  
6"  
6"  
6"  
7"  
15.3  
14.9  
14.9  
19.3  
23.8  
20.29  
20.29  
27.29  
34.29  
607  
607  
744  
881  
15.3  
19.7  
24.1  
NOTE: 1: Maximum Working Pressure: Steam - 15 PSI  
TABLE 1B: RATING DATA  
I=B=R NET  
Ratings  
Steam Steam  
Minimum Chimney  
Requirements  
Burner Capacity  
DOE Heating  
Boiler  
Model  
No.  
AFUE  
%
Round Rectangle Height  
GPH MBH  
Capacity MBH  
MBH  
Sq. Ft.  
In. Dia.  
In. x In.  
Ft.  
15  
15  
15  
15  
MST288  
MST396  
MST513  
MST629  
0.75  
1.05  
1.35  
1.65  
105  
147  
189  
231  
92  
69  
288  
6
6
7
7
8 X 8  
86.0  
86.0  
86.0  
86.0  
127  
164  
201  
95  
396  
8 X 8  
123  
151  
513  
8 X 8  
629  
8 X 8  
6
SECTION I: PRE-INSTALLATION  
A. INSPECT SHIPMENT carefully for any signs of  
30" for flueway cleaning (MST513)  
36" for flueway cleaning (MST629)  
damage.  
b. Clearance from Jacket Left Side Panel -  
1. All equipment is carefully manufactured, inspected  
and packed. Our responsibility ceases upon delivery  
of crated boiler to the carrier in good condition.  
19" for burner swing door, if opened fully  
with burner mounted, otherwise 1" with  
burner removed  
2. Any claims for damage or shortage in shipment  
must be filed immediately against the carrier by the  
consignee. No claims for variances from, or shortage  
in orders, will be allowed by the manufacturer  
unless presented within sixty (60) days after receipt  
of goods.  
12" access clearance to service rear of  
boiler if right side clearance is less  
than 12"  
1" minimum if right side clearance is 12" or  
larger to access and service rear of boiler.  
B. LOCATE BOILER in front of final position before  
c. Clearance from Jacket Right Side Panel -  
removing crate. See Figure 1.  
6" minimum from external Electrical  
Enclosure if left side clearance is 12" or  
larger to access and service rear of the boiler  
1. LOCATE so that vent pipe connection to chimney  
will be short and direct.  
24" minimum from rear tanklesss heater (if  
equipped) for servicing and removal of the  
heater  
2. BOILER IS SUITABLE FOR INSTALLATION  
ON COMBUSTIBLE FLOOR. Boiler cannot be  
installed on carpeting.  
d. Clearance from Jacket Rear Panel -  
3. FOR BASEMENT INSTALLATION, provide  
a solid elevated base, such as concrete, if floor is  
not level, or if water may be encountered on floor  
around boiler.  
12" minimum for rear smokebox cleaning  
(Note: This dimension will also be  
controlled by horizontal to vertical to  
horizontal smokepipe arrangement - See  
Figures 2 and 14.)  
4. PROVIDE RECOMMENDED SERVICE  
CLEARANCE, if applicable, as follows:  
a. Clearance from Jacket Front Panel -  
5. For minimum clearances to combustible materials.  
24" for servicing burner  
See Figure 2.  
24" for flueway cleaning (MST288 &  
MST396)  
Figure ꢀ: Minimum Installation Clearances To Combustible Materials (Inches)  
NOTES:  
Listed clearances cannot be reduced for alcove or closet  
installations.  
1. Listed clearances comply with American National Standard  
ANSI/NFPA 31, Installation of Oil Burning Equipment.  
3. For reduced clearances to combustible material, protection  
must be provided as described in the above ANSI/NFPA 31  
standard.  
2. MegaSteam™ boilers can be installed in rooms with  
clearances from combustible material as listed above.  
a. Outdoor air for combustion may be provided  
with an optional Burnham Inlet Air Accessory  
Kit, Part Number 611280031 (only available  
and suitable for use on Beckett AFG with  
burner enclosure cover burner). See Section V  
for installation details.  
NOTICE  
Clearance to venting is for single wall vent  
pipe. If Type L vent is used, clearance may be  
reduced to the minimum required by the vent pipe  
manufacturer.  
or  
b. Outdoor air may be provided with the use of two  
permanent openings which communicate directly  
or by duct with the outdoors or spaces (crawl or  
attic) freely communicating with the outdoors.  
Locate one opening within 12 inches of top  
of space. Locate remaining opening within 12  
inches of bottom of space. Minimum dimension  
of air opening is 3 inches. Size each opening per  
following:  
C. PROVIDE COMBUSTION AND VENTILATION  
AIR. Local and National Codes may apply and should  
be referenced.  
WARNING  
Adequate combustion and ventilation air must  
be provided to assure proper combustion and  
to maintain safe ambient air temperatures.  
i. Direct communication with outdoors.  
Minimum free area of 1 square inch per  
4,000 BTU per hour input of all equipment  
in space.  
Do not install boiler where gasoline or other  
flammable vapors or liquids, or sources of  
hydrocarbons (i.e. bleaches, fabric softeners,  
etc.) are used or stored.  
Do not install boiler in laundry room, or, in  
vicinity of clothes dryer to prevent inadequate  
air supply to burner and lint contamination of  
burner air intake openings.  
ii. Vertical ducts. Minimum free area of 1  
square inch per 4,000 BTU per hour input of  
all equipment in space. Duct cross-sectional  
area shall be same as opening free area.  
iii. Horizontal ducts. Minimum free area of 1  
square inch per 2,000 BTU per hour input of  
all equipment in space. Duct cross-sectional  
area shall be same as opening free area.  
1. Determine volume of space (boiler room). Rooms  
communicating directly with the space in which  
the appliances are installed, through openings not  
furnished with doors, are considered a part of the  
space.  
Alternate method for boiler located within  
confined space. Use indoor air if two  
permanent openings communicate directly  
with additional space(s) of sufficient volume  
such that combined volume of all spaces  
meet criteria for unconfined space. Size each  
opening for minimum free area of 1 square  
inch per 1,000 BTU per hour input of all  
equipment in spaces, but not less than 100  
square inches.  
Volume(ft3) = Length(ft) x Width(ft) x Height(ft)  
2. Determine total input of all appliances in the space.  
Add inputs of all appliances in the space and round  
the result to the nearest 1000 BTU per hour.  
3. Determine type of space. Divide Volume by total  
input of all appliances in space. If the result is  
greater than or equal to 50 ft3/1000 BTU per hour,  
then it is considered an unconfined space. If the  
result is less than 50 ft3/1000 BTU per hour then the  
space is considered a confined space.  
6. Louvers and Grilles of Ventilation Ducts  
a. All outside openings should be screened and  
louvered. Screens used should not be smaller  
than 1/4 inch mesh. Louvers will prevent the  
entrance of rain and snow.  
4. For boiler located in an unconfined space of a  
conventionally constructed building, the fresh  
air infiltration through cracks around windows  
and doors normally provides adequate air for  
combustion and ventilation.  
b. Free area requirements need to consider the  
blocking effect of louvers, grilles, or screens  
protecting the openings. If the free area of the  
louver or grille is not known, assume wood  
louvers have 20-25 percent free area and metal  
louvers and grilles have 60-75 percent free area.  
5. For boiler located in a confined space or an  
unconfined space in a building of unusually tight  
construction, provide outdoor air.  
c. Louvers and grilles must be fixed in the open  
position, or interlocked with the equipment to  
open automatically during equipment operation.  
8
SECTION II: UNIT-PAK BOILER ASSEMBLY  
MegaSteam™ Unit-Pak Boiler Assembly Shipment  
Content Check List (see Figure 3)  
1. ___ Cast Iron Section/Burner Swing Door/Smoke Box Assembly Mounted on Shipping Skid:  
____ MST3 (Rear Section, Heater) – Part # 100566-03 / 100045-01 / 100021-01  
____ MST4 (Rear Section, Heater) – Part # 100566-04 / 100045-01 / 100021-01  
____ MST5 (Rear Section, Heater) – Part # 100566-05 / 100045-02 / 100021-01  
____ MST3 (Rear Section, Non-Heater) – Part # 100567-03 / 100045-01 / 100021-01  
____ MST4 (Rear Section, Non-Heater) – Part # 100567-04 / 100045-01 / 100021-01  
____ MST5 (Rear Section, Non-Heater) – Part # 100567-05 / 100045-02 / 100021-01  
2. ___ Control Carton  
____ CG450 LWCO; W/Tankless Heater - Part # 100608-01  
____ PS801 LWCO; W/Tankless Heater - Part # 100622-01  
____ #67 LWCO; W/Tankless Heater - Part # 100678-01  
5. ____ Insulation Wrapper  
____ CG450 LWCO; L/Tankless Heater - Part # 100680-01  
____ MST3 - Part #100614-03  
____ PS801 LWCO; L/Tankless Heater - Part # 100681-01  
____ #67 LWCO; L/Tankless Heater - Part # 100679-01  
____ MST4 - Part #100614-04  
____ MST5 - Part #100614-05  
3. ___ Jacket Carton  
6. ___ Instruction/Label Bag  
____ MST3 – Part # 100609-03  
____ MST4 – Part # 100609-04  
____ MST5 – Part # 100609-05  
____ MST (All Models) – Part # 100617-01  
7. ___ Oil Burner Carton  
____ Beckett MST288 – Part # 100625-01  
____ Beckett MST396 – Part # 100053-01  
____ Beckett MST513 – Part # 100054-01  
____ Beckett MST629 – Part # 100055-01  
4. ___ Part Carton  
____ MST3 & 4 - Part # 100615-01  
____ MST5 - Part # 100629-01  
Figure 3: MegaSteam™ Unit-Pak Boiler Shipment Contents (outside container removed)  
9
6. For manual Cast Iron Section/Burner Swing Door/  
Smoke Box Assembly removal prepare one piece of  
4” x 4” x 16” lg. (or two pieces of 2” x 4” x 16” lg.)  
and two pieces of 1” Sch. 40 black pipe to be used  
as handles. Suggested pipe length for each handle is  
72” (3-section); 78” (4-section) and 84” (5-section).  
A. CAST IRON SECTION ASSEMBLY TAPPINGS  
Refer to Table 3 "Purpose of Tappings and Bosses" and  
Figure 7.  
1. All tappings have factory installed thread protectors.  
The thread protectors must be removed prior to  
jacket and piping installation.  
7. Place wooden block(s) 12” from rear of skid as  
2. Depending of installation specifics and boiler build  
ordered, some tappings (front section Optional Front  
Return, rear section Indirect Heater Supply and  
Indirect Heater Limit) may not be used and must be  
plugged before jacket and piping installation. The  
appropriate size plugs for above mentioned tappings,  
as well as rear section Surface Blowoff and front  
section probe type LWCO tappings, are enclosed  
into Part Cartons (100615-01 or 100629-01) and  
Control Cartons (100678-01 and 100679-01),  
supplied as part of MegaSteam™ Unit-Pak Boiler  
shipment.  
shown. See Figure 4 “ Boiler Removal from Skid”.  
8. Insert 1” Sch. 40 black pipe handles thru leg holes in  
front and rear section legs. Center rear pipe ends on  
wooden block(s). See Figure 4.  
9. For best leverage, the pipe handles should extend  
48” minimum beyond front section face.  
10. Using the pipe handles, lift the Cast Iron Section/  
Burner Swing Door/Smoke Box Assembly until  
adjustable legs are elevated above the skid deck  
boards.  
11. Remove the skid from underneath the Cast Iron  
B. REMOVAL OF CAST IRON SECTION/  
BURNER SWING DOOR / SMOKE BOx  
ASSEMBLY FROM SKID.  
Section/Burner Swing Door/Smoke Box Assembly.  
12. Lower pipe handles until front adjustable legs touch  
the floor. Place wood blocks under front legs, if  
required, before lowering, to provide hand clearance.  
WARNING  
13. To lower rear of the Cast Iron Section/Burner Swing  
Door/Smoke Box Assembly tilt unit slightly forward  
by pushing on smokebox, or, lift pipes protruding  
thru rear legs, until wooden block(s) can be removed  
(see Figure 4). Slowly allow the weight of boiler to  
tilt backward until rear legs rest on floor.  
The Cast Iron Section/Burner Swing Door/Smoke  
Box Assembly has a substantial weight. Insure  
the travel path to permanent location, as well as  
mounting surface at boiler permanent location,  
are structurally sound and rated to handle the  
boiler weight and water content (refer to Table 1A).  
Otherwise, a potentially hazardous situation could  
result in death, serious injury and substantial  
property damage.  
14. If wood blocks were placed under front legs, lift pipe  
handles; remove the blocks and lower front legs to  
floor. Remove pipe handles.  
15. Move Cast Iron Section/Burner Swing Door/Smoke  
Box Assembly to permanent position by sliding or  
walking.  
1. Move crated Cast Iron Section/Burner Swing  
Door/Smoke Box Assembly and part cartons on the  
shipping skid as close to final permanent location as  
possible.  
CAUTION  
Do not drop boiler when removing from skid and  
moving to permanent position.  
2. Remove all fasteners at crate skid. Lift outside  
container. Examine the skid contents for damage due  
to shipping and handling.  
C. PROCEDURE TO OPEN, CLOSE AND  
SECURE BURNER SWING DOOR.  
3. Remove Insulation Wrapper, Control Carton, Jacket  
Carton, Part Carton and Oil Burner Carton from skid  
and set aside.  
Throughout this manual you will be instructed to open  
and close Burner Swing Door for various reasons.  
There is a proper and improper method of closing  
and securing the door opened for front jacket panel  
installation, inspection, cleaning or field service. Refer  
to Figures 5A, 5B, 5C and paragraphs D “Jacket Front  
Panel Installation”, and, F “Closing/Securing Burner  
Swing Door” for details.  
4. Instruction/Label Bag is affixed to Section Assembly  
tie rod. Remove the bag and locate MegaSteam™  
Boiler Installation, Operating and Service Instruc-  
tion manual. READ AND UNDERSTAND ALL  
INSTRUCTIONS BEFORE ATTEMPTING UNIT  
HANDLING AND INSTALLATION.  
5. The Cast Iron Section/Burner Swing Door/Smoke  
Box Assembly is secured to shipping skid with four  
lag screws. Remove the screws and discard.  
D. JACKET FRONT PANEL INSTALLATION.  
In order to install front jacket panel Burner Swing Door  
and door mounting bracket need to be removed. As  
shipped, the door would open to the left side.  
10  
11  
1. To open/remove Burner Swing Door (mounted on  
Cast Iron Section/Burner Swing Door/Smoke Box  
Assembly) and door mounting bracket for front  
jacket panel installation:  
4. Place front jacket panel over front section  
attachment bosses and align jacket holes with front  
section boss holes.  
5. Firstly, install two 5/16”-18 x ½” Phillips pan head  
machine screws hand tight to secure front jacket  
panel right side to casting  
a. Loosen but not remove door left side latching  
hardware (3/8”-16 x 1-3/4” tap bolt).  
b. Loosen and remove door right side latching  
hardware (3/8”-16 x 1-3/4” tap bolt and 5/16”  
washer) and set aside.  
6. Secondly, insert 5/16”-18 – ¾” hex head cap  
screw thru door mounting bracket upper hole  
and upper hole on left side of front jacket panel  
simultaneously, and, fasten the bracket and panel to  
casting hand tight.  
c. Remove door left side latching hardware (3/8”-  
16 x 1-3/4” tap bolt and 5/16” washer) and set  
aside.  
7. Thirdly, insert 5/16”-18 – ¾” hex head cap  
screw thru door mounting bracket lower hole  
and lower hole on left side of front jacket panel  
simultaneously, and, fasten the bracket and panel to  
casting hand tight.  
d. Lift the door off mounting bracket and set aside.  
e. Remove two 5/16”-18 – ¾” hex head cap screws  
securing door mounting bracket to front section  
and set aside.  
8. Finally, tighten both sets of hardware to secure the  
bracket and front jacket panel.  
f. Remove door mounting bracket and set aside.  
g. Note/mark cap screw bosses on front section  
left side; locate/mark similar two bosses directly  
opposite on front section right side. These four  
front section bosses are front jacket panel and  
door mounting bracket attachment points.  
9. Inspect fiberglass rope located on the swing door.  
The rope must be evenly distributed around the  
perimeter of the door groove and cannot bunch or  
overhang. Repair or replace, if the rope is damaged,  
or, there is a gap between the rope ends.  
See also Figure 7 “Purpose of Tappings & Bosses”.  
10. Inspect burner swing door insulation for damage and  
proper type.  
2. Open Jacket Carton and locate jacket front panel  
(has factory attached 1” fiberglass insulation). See  
also “Repair Parts” Section, “Jacket Assembly”  
illustration for part identification.  
By design, for all models, cast bars on front section  
between the combustion chamber, and, between the  
left and right side 2nd and 3rd pass flueways should  
make an impression in door insulation to seal the  
chambers.  
3. Open Part Carton, locate Hardware Bag, remove  
two 5/16”-18 x ½” Phillips pan head machine  
screws.  
Figure 5A: Partial Front View - Burner Swing Door Mounted to Boiler - Fully Closed and Secured  
1ꢀ  
11. Upon inspection completion, lift door and place  
integral cast hinge pins into door mounting bracket  
slotted holes. Do not close and secure door at this  
time, proceed to installing stainless steel flueway  
baffles.  
By design, door insulation on model MST629 will  
have two by-pass pockets cast into the insulation  
centered on the bar between the combustion  
chamber and 3rd pass flueways. By design, door  
insulation on models MST288, MST396 & MST513  
will not have any by-pass pockets. If insulation is  
damaged, or, improper type regarding the pockets, it  
must be replaced.  
12. Locate/remove four #8 x ½” shoulder sheet metal  
screws from Hardware Bag, then, install them into  
front panel flange holes.  
Figure 5B: Top View - Burner Swing Door Mounted to Cast Iron Block Assembly (Jacket Removed for Clarity)  
13  
Figure 5C: Top View - Burner Swing Door Fully Closed but Not Properly Secured or Sealed  
Models MST396, MST513 and MST629 - To  
install flueway baffle in 2nd pass flueway on  
left side of boiler, hold baffle with word "Left"  
readable at the top. Slide baffle in flueway until  
position tab touches fins on right side of 2nd pass  
flueway. To install flueway baffle in 2nd pass  
flueway on right side of boiler, hold baffle with  
word "Right" readable at the top. Slide baffle  
in flueway until position tab touches fins on left  
side of 2nd pass flueway.  
E. FLUEWAY BAFFLE INSTALLATION.  
Flueway baffles are enclosed into Part Carton. Baffle  
requirements differ by boiler model, see Table 2.  
TABLE ꢀ: BAFFLE USAGE  
Boiler  
Model  
Baffle Usage  
2nd Pass 3rd Pass  
MST288  
MST396  
MST513  
MST629  
None  
F. CLOSING / SECURING BURNER SWING  
DOOR.  
(2)  
P/N 100042-01  
None  
1. To close and secure Burner Swing Door:  
a. From fully open position, rotate the door to the  
closed position.  
NOTE: Read caution statement before proceeding.  
b. Lift door upward into the build-in cast ramp/door  
rest (protruding from the bottom of the front  
section casting – see Figure 5A).  
CAUTION  
These baffles will generate higher efficiencies  
and lower stack temperatures. Under certain  
conditions, a lower gross stack temperature  
entering the chimney has the potential to  
be cooled below the dew point and create  
condensate on interior surfaces. Flue gas  
condensate is corrosive, which requires  
special consideration and must be addressed  
immediately.  
c. Use one hand to apply pressure directly to the  
door to hold it in closed position while re-  
installing earlier removed door-latching hardware  
(3/8”-16 x 1-3/4” tap bolt and 5/16” washer).  
Prior to re-installation, apply a drop of supplied  
Anti-seize (pouch provided in Part Carton) to  
both tap bolts for rust protection and to facilitate  
easy removal, if burner door is to be open for  
inspection and service. ALWAYS INSTALL  
RIGHT SIDE LATCHING HARDWARE FIRST,  
THEN INSTALL EARLIER REMOVED LEFT  
SIDE HINGE HARDWARE (3/8”-16 X 1-3/4”  
TAP BOLT AND 5/16” WASHER) SECOND.  
Apply additional pressure while hand tightening  
the hardware as far as possible and then release  
the pressure.  
DO NOT install baffles until you have read  
Section V, "Venting" completely.  
1. To install flueway baffles, provided in miscellaneous  
part cartons, as follows, refer to Figure 6 and  
Table 2:  
14  
G. JACKET REAR PANEL INSTALLATION.  
1. Locate jacket rear panel (has factory attached 3”  
fiberglass insulation) inside Jacket Carton. See  
also “Repair Parts” Section, “Jacket Assembly”  
illustration for part identification.  
2. Locate and remove from Hardware Bag rear panel  
mounting hardware – (2 pcs) 5/16”-18 x 3” lg. tap  
studs, (2 pcs) 5/16”-18 plated acorn nuts, (2 pcs)  
5/8” x 2-9/32” round spacers and (2 pcs) 5/16”-18 x  
½” Phillips pan head machine screws.  
3. Locate rear panel two lower attachment bosses on  
rear section. See Figure 7 “Purpose of Tappings &  
Bosses”.  
4. Thread both 5/16”-18 x 3” lg. tap studs, with short  
threaded end, into lower attachment bosses on rear  
section.  
5. Install both 5/8” x 2-9/32” round spacers over tap  
studs.  
6. Place rear jacket panel over rear section, so both  
tap studs clear thru lower panel holes, rear section  
cleanout openings clear thru matching panel cutouts  
and brass sample port plug clears panel matching  
hole.  
7. Secure panel bottom to studs with acorn nuts hand  
tight.  
8. Align upper panel attachment holes with smokebox  
upper attachment bosses and install 5/16”-18 x ½”  
Phillips pan head machine screws hand tight.  
Figure 6: Flueway Baffle Positioning/Orientation in  
Flueways  
9. Securely tighten rear jacket panel mounting  
hardware.  
10. Locate/remove four #8 x ½” shoulder sheet metal  
screws from Hardware Bag, then, install them into  
rear panel flange holes.  
NOTICE  
When securing burner swing door make sure door  
is drawn-in equally on both sides.  
H. FLUE CLEANOUT COVERS AND SMOKEBOx  
COLLAR INSTALLATION.  
d. Use a hand or socket wrench to tighten door  
hardware. ALWAYS START WITH RIGHT  
SIDE TAP BOLT FIRST. Use an alternating  
tightening method from right side tap bolt to  
left side tap bolt to tighten door equally, until  
sealed, without applying excessive torque.  
NEVER TIGHTEN LEFT SIDE TAP BOLT  
FIRST, OR, EITHER PIECE OF HARDWARE  
100% WITHOUT USING THE ALTERNATING  
METHOD DESCRIBED ABOVE. See Figure  
5B.  
1. Remove two cast iron Cleanout Covers, cast iron  
Smokebox Collar and the tube of hi-temperature  
silicon adhesive sealant from Part Carton. See also  
“Repair Parts” Section, “Bare Boiler Assembly”  
illustration for part identification.  
2. Check the rope gasket factory attached to the covers.  
Repair or replace, if the rope is damaged, or, there is  
a gap between the rope ends.  
3. Locate/remove four 5/16”-18 – 7/8” hex head cap  
screws from Hardware Bag.  
e. Failure to follow the prescribed procedure could  
cause thread damage to casting and /or leak at  
the door seal. IF LEFT SIDE TAP BOLT IS  
TIGHTENED BEFORE RIGHT SIDE TAP  
BOLT, RIGHT SIDE OF THE DOOR CAN  
NOT BE DRAWN-IN TO PROVIDE AN AIR-  
TIGHT SEAL, as shown in Figure 5C. Applying  
excessive torque will only cause thread damage.  
4. Apply a drop of supplied Anti-seize (pouch provided  
in Part Carton) to each of four (4) 5/16”-18 x 7/8”  
hex head cap screws for rust protection and to  
facilitate easy removal for future service.  
5. Position left Cleanout Cover over rear section  
cleanout opening, align section boss holes with  
Cleanout Cover holes, install both 5/16”-18 – 7/8”  
hex head cap screws hand tight, then, alternately  
tighten them with open end or socket wrench.  
15  
Figure ꢁ: Purpose of Tappings and Bosses  
TABLE 3: PURPOSE OF TAPPINGS & BOSSES  
Steam Boiler  
With Heater  
Tapping  
Location  
Thread Size  
UNC  
Size, NPT  
Boss Location  
Less Heater  
A
B
¼" - 18  
¼" - 18  
Pressure Gauge  
Pressure Limit  
Probe LWCO - Std.  
Plugged (Float LWO)  
C
¾" - 14  
Water Gauge Glass (Probe LWCO)  
Water Gauge Glass, Pressuretrol &  
LWCO (Float LWCO)  
D
½" - 14  
E
F
ꢀ" - 11½"  
¾" - 14  
Supply (Front & Rear Tappings)  
Safety Valve  
G
H
J
1½" - 11½  
1¼" - 11½  
1½" - 11½  
1" - 11½  
½" - 14  
Condensate Return  
Optional Front Return  
Surface Blowoff (Plugged)  
Indirect Water Heater Supply  
Indirect Water Heater Limit  
K
L
Jacket Front Panel, Burner Swing  
Door Mounting Bracket  
M (4 pcs)  
N (ꢀ pcs)  
P (10 pcs)  
5/16" - 18  
3/8" - 16  
5/16" - 18  
Burner Swing Door  
Jacket Rear Panel, Smoke Box Collar,  
Cleanout Covers  
Q
R
¼" - 18  
½"-14  
Smokebox Pressure Tapping  
L4006  
Operating  
Control  
Plugged  
16  
6. Repeat above steps with right Cleanout Cover.  
5. Pick up Molex end of Burner Harness stuffed  
between front panel insulation and insulation  
wrapper and feed it thru Right Side Jacket Panel  
front cutout, letting the harness connector to hang  
over the cutout edge temporarily.  
7. Apply the adhesive sealant to the underside of the  
collar, all around, at the inside corner of the collar  
outer ring. Insure adhesive bead is complete all  
around and without gaps.  
6. Place Right Side Jacket Panel, clearing rear section  
tankless heater collar/ mounting flange, over four  
#8 x ½” shoulder sheet metal screws, previously  
installed at Front and Rear Jacket Panel side flanges,  
so teardrop cutouts in the side panel inside flanges  
engage all four screws simultaneously.  
8. Place the collar over smokebox tongue and align  
collar integral mounting ear slots with smokebox  
bosses.  
9. Thread-in both 5/16”-18 – 7/8” hex head cap screws  
hand tight, then, alternately tighten them with open  
end or socket wrench.  
7. Slide the panel downwards to lock all screws  
securely.  
I. INSULATION WRAPPER AND BURNER  
POWER OUTLET RECEPTACLE WITH  
HARNESS INSTALLATION.  
8. Pick up Top Jacket Panel from Jacket Carton.  
9. Place the panel between side panels upper inside  
flanges and slide it forward, until top panel front  
flange U-bend locks over front panel top flange, and,  
top panel rear flange is positioned over rear jacket  
panel.  
1. Insulation Wrapper is vacuum packed/sealed in  
plastic bag at the factory.  
2. Carefully cut the plastic bag and remove Insulation  
Wrapper. The wrapper will expand upon removal.  
3. Unfold Insulation Wrapper, position it over section  
assembly centered left to right and align two  
wrapper upper holes with 2" NPT pipe tappings in  
front and rear section top.  
10. Locate/remove two #8 x ½” sheet metal screws from  
Hardware Bag.  
11. Install both screws into top panel rear flange to  
secure the top panel to rear jacket panel.  
4. Insure wrapper fits snugly around rear section  
tankless heater collar/ mounting flange (if boiler  
is equipped with tankless heater) and trim the  
insulation at tankless heater cutout. Do not trim off  
insulation on boilers having non-heater rear section.  
K. ExTERNAL ELECTRICAL ENCLOSURE  
MOUNTING.  
1. Remove two #8 x ½” shoulder sheet metal screws  
and one #8 x ½” sheet metal screw from Hardware  
Bag.  
5. Tack Insulation Wrapper bottom ends under section  
assembly, between front and rear section legs.  
2. Install both #8 x ½” shoulder sheet metal screws  
into Right Side Jacket Panel, at two upper corners of  
the panel front cutout.  
6. Locate and remove Burner Power Outlet Receptacle  
with factory attached Burner Harness from Control  
Carton.  
3. Locate and remove External Electrical Enclosure  
assembly from Control Carton.  
7. Feed Molex end of Burner Harness thru front jacket  
panel right side outlet receptacle cutout. Insure  
that the receptacle middle prong opening is facing  
down. Snap the receptacle into front jacket panel.  
Temporarily, stuff Molex end of Burner Harness  
between front panel insulation and insulation  
wrapper near boiler top.  
4. Remove the enclosure cover and set aside.  
5. Pick Molex connector end of Burner Harness and  
feed it inside the enclosure, thru bushed hole at  
enclosure lower left corner, next to transformer/  
relay.  
6. Place the enclosure over installed shoulder sheet  
metal screws, so teardrop cutouts in the enclosure  
base engage both screws simultaneously, then, slide  
the enclosure downwards to lock it in place.  
J. SIDE AND TOP JACKET PANEL  
INSTALLATION.  
1. Pick up Left Side Jacket Panel from Jacket Carton.  
See also “Repair Parts” Section, “Jacket Assembly”  
illustration for part identification.  
7. Install #8 x ½” sheet metal screw thru enclosure  
base lower hole, located to the right of transformer/  
relay, into right side panel to secure the enclosure.  
2. Place Left Side Jacket Panel over four #8 x ½”  
shoulder sheet metal screws, earlier installed at  
Front and Rear Jacket Panel side flanges, so teardrop  
cutouts in the side panel inside flanges engage all  
four screws simultaneously.  
8. Plug-in burner harness Molex connector into  
dedicated burner harness receptacle inside the  
enclosure (lower left off transformer/relay). See “  
Control Plug-In Diagram” label attached to inside of  
the enclosure cover for details.  
3. Slide the panel downwards to lock all screws  
securely.  
9. Do not install the enclosure cover yet; proceed to  
control installation.  
4. Pick up Right Side Jacket Panel from Jacket Carton.  
See also “Repair Parts” Section, “Jacket Assembly”  
illustration for part identification.  
1ꢁ  
2. Install the probe into the appropriate front section  
tapping. See Figure 7 “Purpose of Tappings &  
Bosses”.  
L. TRIM AND CONTROLS INSTALLATION.  
Pressure Limit Installation.  
1. Locate and remove L404F Pressure Limit with  
factory attached harness from Control Carton.  
3. Slip LWCO with factory attached harness over the  
probe and clamp in place. Note that CG450 LWCO  
will be positioned right side up, with diagnostic  
LED(s) on the top flange, while PS801 LWCO  
will be positioned upside down, with diagnostic  
LED(s) on the bottom flange. Connect the wire(s)  
between the probe and control per manufacturer’s  
instructions.  
2. Locate and remove 1/4" NPT x 1-7/8" x 4 x 90°  
syphon enclosed in Part Carton.  
3. Review and locate pressure limit tapping on front  
section. See Table 3 “ Purpose of Tappings &  
Bosses” and Figure 7.  
4. Thread 1-7/8" lg. syphon-threaded short end into  
the bottom of Pressure Limit with factory attached  
harness. Do not tighten the syphon by holding the  
limit case; apply a wrench to the brass hex below  
the case.  
4. Pick-up the LWCO harness Molex end and feed it  
into the enclosure, thru external electrical enclosure  
top flange front left 7/8” hole; then, snap-in harness  
BX connector into the hole, and, plug-in Molex  
connector into dedicated LWCO receptacle inside  
the enclosure (middle left off transformer/relay). See  
“ Control Plug-In Diagram” label attached to inside  
of the enclosure cover for details.  
5. Thread ¼" NPT x 4" lg. syphon-threaded long end  
into pressure limit tapping on front section. See  
Figure 8 "Pressure Limit Installation.  
6. L404F pressure limit does not require leveling. The  
pressure limit final orientation must be parallel to  
boiler front, having the harness on the right side.  
N. PRESSURE GAUGE AND GAUGE GLASS  
INSTALLATION.  
1. Remove the 6” water gauge glass set from Part  
Carton.  
7. Pick-up the pressure limit harness Molex end and  
feed it into the enclosure, thru top flange rear left  
7/8” hole; then, snap-in harness BX connector into  
the hole, and, plug Molex connector into dedicated  
pressure limit receptacle inside the enclosure (upper  
left off transformer/relay). See “ Control Plug-In  
Diagram” label attached to inside of the enclosure  
cover for details.  
2. Install the gauge glass using the two ½” NPT  
tappings to the right of the probe LWCO. See Figure  
7 “Purpose of Tappings & Bosses”.  
3. Thread the pressure gauge into 1/4” NPT tapping of  
the front section. See Figure 7 “Purpose of Tappings  
& Bosses”. Tighten with wrench applied to the  
square shank of the gauge.  
CAUTION  
Do not apply pressure to gauge case, as this may  
result in inaccurate readings.  
O. FLOAT LWCO (MCDONNELL-MILLER #67),  
AND GAUGE GLASS INSTALLATION.  
1. Pre-assemble float-type LWCO per Figure 9 "Float-  
Type LWCO and Gauge Glass Installation".  
2. Install two ½” NPT x 2½" long Sch 40 brass nipples,  
supplied loose inside Control Carton (disregard two  
½" NPT x 1½" long brass nipples provided with  
#67 LWCO package) and ½" NPT brass unions into  
upper and lower front section tappings. See Table 3  
"Purpose of Tappings & Bosses" and Figure 7.  
3. Install water gauge glass on low water cut-off  
Figure 8: Pressure Limit Installation  
assembly tee fittings.  
M. PROBE LWCO (HYDROLEVEL CG450,  
OR, MCDONNELL-MILLER PS801-120)  
INSTALLATION.  
4. Do not remove ¼” NPT plug factory installed on top  
of #67 LWCO.  
5. Insure that 3/8" NPT plug (provided within #67  
LWCO package) is installed at bottom of #67  
LWCO.  
1. Remove either Hydrolevel CG450 LWCO with  
factory attached harness and Hydrolevel probe  
#EL1214, or, McDonnell-Miller PS801-120 with  
factory attached harness and #153875 probe from  
Control Carton.  
6. Remove #67 LWCO J-box cover.  
18  
19  
7. Screw LWCO to External Wiring Enclosure wiring  
harness (end with fork and female disconnect  
terminals) connector into low water cut-off J-box  
top fitting, and attach wires to the terminals per  
LWCO wiring detail shown in Figure 9 "Float-Type  
LWCO and Gauge Glass Installation".  
nipple, ¾” NPT 90° black elbow and ¾” NPT black  
coupling) from Part Carton.  
2. Thread 3/4" NPT x 3” lg. black nipple into rear  
section safety valve tapping, install ¾” NPT 90°  
black elbow facing upward, then, thread 3/4" NPT  
x 8” lg. black nipple into the elbow, and, install ¾”  
NPT black coupling onto nipple end.  
8. Re-install #67 LWCO J-box cover.  
9. Pick-up the LWCO harness Molex end and feed it  
into the enclosure, thru external electrical enclosure  
top flange front left 7/8” hole; then, snap-in harness  
BX connector into the hole, and, plug-in Molex  
connector into dedicated LWCO receptacle inside  
the enclosure (middle left off transformer/relay). See  
“ Control Plug-In Diagram” label attached to inside  
of the enclosure cover for details.  
3. Thread safety valve into the ¾” NPT black coupling.  
Pipe the safety valve discharge as shown in Figure  
11 “ Recommended Boiler Piping For Gravity  
Return Steam Boiler” shown in Section III of this  
manual. Installation of the safety valve must be  
consistent with ANSI/ASME Boiler and Pressure  
Vessel Code, Section IV.  
WARNING  
10. Pick-up the pressure limit harness Molex end  
and feed it into the enclosure, thru External  
Electrical Enclosure top flange rear left 7/8” hole;  
then, snap-in harness BX connector into the hole,  
and, plug-in Molex connector into dedicated pressure  
limit receptacle inside the enclosure (upper left off  
transformer/relay). See “ Control Plug-In Diagram”  
label attached to inside of the enclosure cover for  
details.  
Safety valve discharge piping must be piped near  
floor to eliminate potential of severe burns. Do  
not pipe in any area where freezing could occur.  
Do not install any shut-off valves, plugs or caps.  
4. Remove 1-1/2" NPT x 5” lg. black nipple, 1-1/2”  
x 1-1/2” x ¾” NPT black tee and drain valve from  
Part Carton.  
P. AqUASTAT CONTROLLER INSTALLATION  
NOTICE  
(BOILERS WITH TANKLESS HEATER ONLY).  
1. On boilers with tankless heater, install the L4006A  
aquastat controller well (found in Part Carton) into  
½” NPT tapping in tankless heater plate.  
Lower rear section Tapping "H" is used for  
standard condensate return on steam boilers.  
5. Thread 1-1/2" NPT x 5” lg. black nipple into lower  
rear section tapping, then, install 1-1/2” x 1-1/2” x  
¾” NPT black tee onto nipple end. Black tee side  
outlet may be oriented to either left, or, right side.  
2. Remove the L4006A aquastat controller with factory  
attached harness from Control Carton.  
3. Slip the bulb of the aquastat controller into the well  
and secure the controller in place with the set screw.  
6. Install the drain valve into black tee ¾” NPT side  
outlet.  
WARNING  
R. OIL BURNER INSTALLATION.  
1. Install oil burner, refer to Figure 10.  
a. Open burner carton and remove contents.  
Aquastat bulb must be fully inserted into the  
well.  
4. Feed the L4006A aquastat controller harness end  
thru external electrical enclosure top flange middle  
right bushed hole. See “ Control Plug-In Diagram”  
label attached to inside of the enclosure cover for  
details.  
b. Check oil nozzle in burner for size, angle and  
type, inspect electrode settings, check head  
setting, check air band and air shutter settings,  
refer to Table 8 at rear of this manual.  
c. Place oil burner gasket on burner and align holes.  
5. See Figures 18, 19 and 20 (whichever applicable)  
for tankless heater aquastat connection details.  
CAUTION  
6. Using needle nose pliers form hook on harness each  
stripped end and wrap hooks around screws under  
terminals "R" and "G" of the R8285C Transformer-  
Relay; then, tighten screws securely.  
Do not install burner without gasket.  
d. Remove three (3) 5/16-18 x 3/4 lg. cap screw  
from burner swing door used for mounting  
burner.  
q. SAFETY VALVE AND DRAIN VALVE  
INSTALLATION.  
e. Thread (1) 5/16-18 x 3/4 lg. cap screw,  
approximately three (3) full turns, into tapping  
located at 12:00 o'clock on burner swing door.  
1. Remove safety valve and related piping (3/4”  
NPT x 3” lg. black nipple, 3/4” NPT x 8” lg. black  
ꢀ0  
f. Insert oil burner into the opening of burner  
swing door. Align and engage keyhole slot in  
burner flange over head of protruding cap screw  
installed in previous Step. Rotate burner to the  
right to lock flange behind head of cap screw.  
h. Plug burner power cord into power outlet  
receptacle located in lower right corner of front  
panel.  
g. Align holes and install two (2) remaining cap  
screws. Level burner and fully tighten all three  
(3) screws.  
Figure 10: Oil Burner Installation  
ꢀ1  
SECTION III: STEAM BOILER PIPING & TRIM  
WARNING  
Failure to properly pipe boiler may result in improper operation and damage to boiler or structure.  
Do not increase steam boiler input above the ratings.  
A. EVALUATE THE ExISTING STEAM SYSTEM.  
2. Repair any leaks in the system.  
The single most important factor in determining the  
expected life cycle of a steam boiler, is the amount of  
fresh water added to the boiler during operation. Fresh  
water brings minerals and oxygen into the boiler. These  
contaminants greatly accelerate corrosion of the cast  
iron boiler sections.  
3. Install accurate water meter on the fresh water  
supply to the boiler.  
B. CONNECT SYSTEM SUPPLY AND RETURN  
PIPING TO BOILER. See Figure 11 for piping  
details. Also consult I=B=R Installation and Piping  
Guides.  
1. Assure that all system radiators, piping and vents are  
absolutely leak tight.  
CAUTION  
a. When a steam boiler is installed in an existing  
system, ALL air vents should be replaced at the  
same time. This assures that the new boiler will  
not be compromised by existing system leaks.  
Maintain minimum ½ inch clearance from hot  
water piping to combustible materials.  
b. If the system contains hidden supply or return  
piping (hidden behind walls, buried in concrete,  
etc.) pressure test this piping to assure there are  
no leaks.  
NOTICE  
Do not use softened water in steam boilers. Accelerated boiler corrosion will result. Tie in fresh water  
supply to the boiler upstream of a water softener.  
Oxygen contamination of boiler water will cause corrosion of iron and steel boiler components, and  
can lead to boiler failure. Burnham's Standard Warranty does not cover problems caused by oxygen  
contamination of boiler water or scale (lime) build-up caused by frequent addition of water.  
Before using copper for steam piping, consider the following characteristics of copper piping:  
1) high coefficient of thermal expansion can induce mechanical stresses and cause expansion/  
contraction noises if not accounted for in the piping system design and installation,  
ꢀ) high heat transfer rate (heat loss) of uninsulated copper piping must be included in the normal  
piping and pickup factors used to size the boiler,  
3) soldering or brazing pastes and fluxes that end up in the system can cause poor heat transfer,  
surging, an unsteady water line and wet steam if not thoroughly removed during the boil out  
procedure and,  
4) galvanic corrosion of the adjoining metal may occur due to dissimilar metals in certain water  
chemistries if dielectric unions are not used.  
ꢀꢀ  
ꢀ3  
SECTION IV: TANKLESS & INDIRECT WATER HEATER PIPING  
A. CONNECT TANKLESS HEATER PIPING as  
shown in Figure 12. See Table 4 for Tankless Heater  
Rating.  
possible by piping the hot water from the heater  
prior to entering the mixing valve. The mixing valve  
should be “trapped” by installing it below the cold  
water inlet to heater to prevent lime formation in the  
valve. Refer to Figure 12.  
WARNING  
3. FLUSHING OF HEATER — All water contains  
some sediment which settles on the inside of the  
coil. Consequently, the heater should be periodically  
back washed. This is accomplished by installing  
hose bibs as illustrated and allowing water at city  
pressure to run into hose bib A, through the heater,  
and out hose bib B until the discharge is clear. The  
tees in which the hose bibs are located should be  
the same size as heater connections to minimize  
pressure drop.  
Install automatic mixing valve at tankless heater  
outlet to avoid risk of burns or scalding due to  
excessively hot water at fixtures. Adjust and  
maintain the mixing valve in accordance with  
the manufacturer's instructions. Do not operate  
tankless heater without mixing valve.  
THE FOLLOWING GUIDELINES SHOULD BE  
FOLLOWED WHEN PIPING THE TANKLESS  
HEATER:  
4. HARD WATER — A water analysis is necessary  
to determine the hardness of your potable  
water. This is applicable to some city water and  
particularly to well water. An appropriate water  
softener should be installed based on the analysis  
and dealer’s recommendation. This is not only  
beneficial to the tankless heater but to piping and  
fixtures plus the many other benefits derived from  
soft water.  
1. FLOW REGULATION — If flow through the  
heater is greater than its rating, the supply of  
adequate hot water may not be able to keep up  
with the demand. For this reason a flow regulator  
matching the heater rating should be installed in  
the cold water line to the heater. The flow regulator  
should preferably be located below the inlet to the  
heater and a minimum of 3’ away from the inlet  
so that the regulator is not subjected to excess  
temperatures that may occur during “off” periods  
when it is possible for heat to be conducted back  
through the supply line. The flow regulator also  
limits the flow of supply water regardless of inlet  
pressure variations in the range of 20 to 125 psi.  
NOTICE  
During summertime operation, the normal  
water line on a steam boiler can be raised  
1", from ꢀ8-ꢁ/8" to ꢀ9-ꢁ/8" (see Figure 1) for  
improved tankless heater performance on  
steam boilers.  
2. TEMPERING OF HOT WATER — Installation  
of an automatic mixing valve will lengthen the  
delivery of the available hot water by mixing some  
cold water with the hot. This prevents the possibility  
of scalding hot water at the fixtures. In addition,  
savings of hot water will be achieved since the user  
will not waste as much hot water while seeking a  
water temperature. Higher temperature hot water  
required by dishwashers and automatic washers is  
Use street elbow fittings in tankless in and out  
connections to assure adequate clearance of  
piping.  
CAUTION  
Use of hard water with a tankless coil will, over a short period of time, reduce the output of the coil and reduce  
the useful life of the coil.  
ꢀ4  
Figure 1ꢀ: Schematic Tankless Water Heater Piping  
TABLE 4: TANKLESS HEATER DATA:  
Heater Rating  
(GPM)  
Pressure Drop thru  
Heater (PSI)  
Boiler Model  
Heater No.  
MST288  
MST396  
MST513  
MST629  
3.00  
3.25  
3.50  
4.00  
22.0  
24.3  
26.5  
31.0  
222A  
ꢀ5  
Figure 13: Alliance™ Water Heater Piping with MegaSteam™ Boiler  
B. CONNECT ALLIANCE™ INDIRECT WATER  
HEATER PIPING as shown in Figure 13.  
1. Refer to Alliance™ manual for additional  
information.  
ꢀ6  
SeCtiOn V: Venting & Air intAke piping  
a. Loose Mortar – Loose mortar could be an  
A. Chimney Venting  
indication of a prior history of condensing flue  
gases upon the inside walls of the chimney.  
Colder climates are more susceptible to this  
condition. Under no circumstances shall a  
chimney of this condition be used until it meets  
the requirements of NFPA 211.  
1. Chimney venting is an important part of a safe  
and efficient oil fired appliance system. Contact  
your local fire and building officials on specific  
requirements for restrictions and the installation  
of fuel oil burning equipment. In addition,  
consult with a professional knowledgeable on  
the requirements of NFPA 31 – Standard for the  
Installation of Oil-Burning Equipment and NFPA  
211 - Standard for Chimneys, Fireplaces, Vents, and  
Solid Fuel-Burning Appliances for installations in  
the United States  
b. Unlined Chimney – Under no circumstances  
shall a chimney constructed of brick only  
be used. Only approved clay liners or listed  
chimney lining systems shall be used as specified  
in NFPA 31.  
c. Abandoned Openings – Openings through the  
chimney wall that are no longer used shall  
be sealed in accordance to NFPA 211. Often  
abandoned openings are improperly sealed and  
usually covered by a gypsum wall covering.  
2. The safe venting of oil fired boilers is dependent on  
many factors. Some of these factors include:  
a. sufficient draft during the entire heating season  
to allow for the safe discharge of combustion by-  
products and;  
b. suitable corrosion protection in the event of  
condensing flue gases. Only a trained and  
qualified contractor may install this product.  
d. Clean Chimney – Chimney shall be free of all  
loose debris.  
5. Draft Regulator – the draft regulator supplied with  
the boiler must be used with this appliance. No  
other draft regulator shall be used. Refer to Figures  
14 and 15.  
3. The MegaSteam™ can be vented into a fireclay  
tile-lined masonry chimney that meets requirements  
outlined in Paragraph 4 below. It can also be vented  
into a chimney constructed from type L vent or a  
factory built chimney that complies with the type  
HT requirements of UL 103. The chimney and  
vent pipe shall have a sufficient draft at all times,  
to assure safe proper operation of the boiler. See  
Figure 14 for recommended installation.  
B. Chimney COnneCtOr  
1. A chimney connector (vent pipe) is used to connect  
the boiler to the base of the chimney. The chimney  
connector should be kept as short as possible. The  
horizontal length of the chimney connector shall not  
be greater than 10 feet.  
NOTE: Secure chimney connector to cast iron  
smokebox collar with three (3) #10 x ½" self drilling  
hex head TEK screws provided in appropriate  
Parts Carton. Locate screws around perimeter of  
connector as shown in Figure 14 and approximately  
½" in from edge. Use drill with 5/16" hex bit to  
drive screws through connector and smokebox  
collar.  
WARNING  
Do not de-rate the appliance. Failure to fire the  
unit at it's designed input may cause excessive  
condensation upon the interior walls of the  
chimney. In addition, the lower input may not  
create enough draft to adequately evacuate the  
by-products of combustion.  
4. Chimney Inspection – Prior to the installation of  
any new or replacement fuel burning equipment the  
chimney shall be inspected by a qualified installer.  
The chimney shall be inspected for integrity as  
well as for proper draft and condensate control.  
Some jurisdictions require the use of a liner when  
changing fuel types. Some jurisdictions require  
the use of a liner even when the same fuel is used.  
At a minimum, the chimney shall be examined  
by a qualified person in accordance with the  
requirements of Chapter 11 of NFPA 211, Standard  
for Chimneys, Fireplaces, Vents, and Solid Fuel-  
Burning Appliances.  
DANGER  
The chimney and connector shall be inspected  
annually for signs of debris and corrosion.  
Loose mortar at the base of the chimney may be  
a sign of condensate damage to the chimney.  
A chimney professional shall be contacted  
immediately to examine the damage and  
recommend a solution. Long term operation  
while in this condition may cause a venting  
failure and force flue gases into the living  
space. If the chimney is to be relined use the  
recommendations in NFPA 31, Appendix E.  
27  
Figure 14: Recommended Vent Pipe Arrangement and Chimney Requirements  
Figure 15: Proper and Improper Locations of Draft Regulator  
ꢀ8  
2. Type B Chimney Connector - a type B chimney  
connector can be used to transmit the flue gases  
provided flue gas temperature entering the chimney  
connector is greater than 310°F.  
2. NFPA 31 has information to help the installer  
make an appropriate choice of venting materials.  
In some cases a chimney may have to be lined to  
create sufficient draft. In other cases, the chimney  
may have to be lined to prevent the corrosion  
of a masonry chimney. Consult with a chimney  
specialist knowledgeable on the requirements for  
chimney requirements in your area.  
3. Type L Chimney Connector - a type L vent or  
other suitable material shall be used for a chimney  
connector if the temperature or exiting temperature  
is less than 310°F.  
CAUTION  
DANGER  
Any doubt on the condition of a chimney  
or it's ability to prevent the generation and  
accumulation of flue gas condensate, must be  
relined according to NFPA31.  
Any signs of condensate seepage at the base of  
the chimney shall be inspected immediately. The  
discoloration may be a sign of chimney damage  
and must be remedied immediately.  
C. DRAFT  
CAUTION  
1. The natural draft generated through a chimney is  
dependent on several factors including, chimney  
height, temperature of flue gases, cross section area  
of chimney, chimney wall insulation value, dilution  
air and total volume of flue gases, to name a few.  
Make sure that the boiler has been running for at  
least 5 minutes before measuring the draft.  
Use the chimney venting tables as a guide. It  
is highly recommended that any borderline  
application should result in the relining of the  
chimney with a suitable liner that creates sufficient  
draft and to protect against corrosion caused by  
flue gas condensate.  
2. Minimum Draft at Breech (Canopy) – The draft  
induced by a chimney must create at least a  
pressure of 0 (zero) inches water column (“ w.c.)  
at the pressure tapping on the canopy mounted  
on rear of boiler (see Figure 16). The pressure  
at the canopy cannot be positive since this could  
create a condition that allows flue gas by-products  
to escape from the draft regulator. A negative  
pressure reading up to -.03 inches water column  
is acceptable for proper operation. (See Table 8,  
Burner Specifications at the rear of this manual for  
more details)  
3. Baffles – The efficiency of the boiler is based on the  
insertion of flue baffles supplied with your product.  
Under no circumstances are other baffles to be used  
on this product. The baffles are installed in the 2nd  
pass (two inner flueways) on the MST396, MST513  
and MST629 Refer to Section II, Item E, Paragraph  
1 for baffle installation. If there is any doubt  
on the application of this boiler on the intended  
chimney, consult with your local code officials.  
At a minimum, remove the baffles to increase the  
stack temperature. See Table 8 for temperature  
differential (T) with baffles IN and OUT. In  
addition, the lower the CO2 level the higher the  
stack temperature.  
3. Minimum Overfire Pressure – The overfire  
pressure is another piece of information that is  
often measured, however this should be done for  
observation purposes only! The breech pressure  
must be used to qualify the draft condition. See  
Table 8 for more details as a guide. Actual draft and  
temperature measurements may be different then  
those values in the table.  
D. STACK TEMPERATURE  
1. The temperature of the flue gases has a significant  
effect on the amount of draft created in a vertical  
chimney as well as the propensity to create  
condensate. The higher the stack temperature, the  
greater the amount of draft that can be generated. A  
lower stack temperature not only reduces the amount  
of draft that can be created but it also increases the  
possibility that the flue gases could condense in the  
chimney connector or stack.  
Figure 16: Smokebox Pressure Tapping for  
Checking Draft at Breech  
ꢀ9  
1. General  
a. Use 4" dia., single wall galvanized metal pipe  
WARNING  
and fittings available at most heating distributors  
for air intake piping. Maximum allowable air  
intake length is 50 equivalent feet. Each elbow  
is equal to 6 equivalent feet.  
Remove the baffles if there are any signs  
of condensation in the chimney or chimney  
connector. Consult with your local chimney  
professional for recommendations.  
E. MINIMUM CLEARANCES  
WARNING  
See Figure 2 for details regarding clearances to  
combustibles for the boiler.  
Do not exceed maximum allowable air intake  
length.  
F. OPTIONAL AIR INTAKE PIPING  
INSTALLATION - All air for combustion can be  
supplied directly to the burner from outdoors providing  
that the criteria for chimney, vent connector and  
minimum stack temperature outlined in this section  
can be maintained. (ONLY AVAILABLE WITH  
BECKETT BURNER). See Figure 17.  
b. Start at burner. Work toward air intake terminal.  
c. Maintain minimum of 1/4 inch per foot slope in  
horizontal run to air intake terminal. Slope down  
toward air intake terminal.  
d. Seal all joints gas-tight, using silicone caulk or  
self-adhesive aluminum tape.  
2. After determining location, cut a hole in the wall to  
accept 4 inch air intake pipe. See Figure 15.  
WARNING  
Using outdoor air in the middle of winter  
may result in lower stack temperatures  
and chimney degradation. Any signs of  
condensate seepage or discoloration at  
the base of chimney must be remedied  
immediately per the details outlined in this  
section.  
3. Remove the metal knockout in right side of burner  
cover. Install Burnham Inlet Air Accessory Kit, Part  
Number 611280031.  
4. Mount the Vacuum Relief Valve Tee Assembly (P/N  
8116268 included with Kit) or 90° elbow into the  
burner inlet ring. See Figure 16.  
a. Secure with at least three (3) sheet metal screws  
Do not reduce size of air intake pipe.  
evenly spaced around the burner inlet ring.  
Read, understand and follow combustion air  
instruction restrictions contained in the Pre-  
Installation Section of this manual.  
b. Assemble the vacuum relief valve balance  
weight onto the gate. Refer to the vacuum relief  
valve manufacturer's instructions.  
Figure 1ꢁ: Optional Air Intake Piping Installation - Only Available with Beckett Burner  
30  
c. Mount the vacuum relief valve into the tee and  
fasten with a screw and nut in collar tabs. To  
ensure proper operation, the gate must be level  
across the pivot point and plumb. Refer to  
vacuum relief valve manufacturer's instructions.  
7. Seal all external joints with weatherproof caulk.  
WARNING  
Donotlocateairintakewherepetroleumdistillates,  
CFC's, detergents, volatile vapors or any other  
chemicals are present. Severe boiler corrosion  
and failure will result.  
5. Install remainder of air intake, securing each joint  
with at least three (3) sheet metal screws evenly  
spaced.  
6. Install air intake terminal. See Figure 17.  
NOTICE  
Intake terminal must be at least 1ꢀ inches above  
grade plus snow accumulation.  
31  
SECTION VI: ELECTRICAL  
DANGER  
Positively assure all electrical connections are unpowered before attempting installation or service of  
electrical components or connections of the boiler or building. Lock out all electrical boxes with padlock  
once power is turned off.  
WARNING  
Failure to properly wire electrical connections to the boiler may result in serious physical harm.  
Electrical power may be from more than one source. Make sure all power is off before attempting any  
electrical work.  
Each boiler must be protected with a properly sized fused disconnect.  
Never jump out or make inoperative any safety or operating controls.  
A. GENERAL  
1. Install wiring and electrically ground boiler in  
6. If an Alliance™ indirect water heater is used, use  
priority zoning. Do not use priority zoning for  
Hydro-Air Systems.  
accordance with requirements of the authority  
having jurisdiction, or in absence of such  
requirements the National Electrical Code, ANSI/  
NFPA 70.  
7. Wiring should conform to Figure 18.  
B. INSTALL A ROOM THERMOSTAT on an  
inside wall about four feet above floor. Never install  
thermostat on an outside wall or where it will be  
influenced by drafts, hot or cold water pipes, lighting  
fixtures, television, rays of the sun or near a fireplace.  
Keep large furniture away from thermostat so there will  
be free movement of room air around this control.  
2. Refer to National Electric Code or Local Electric  
Codes for proper size and type of wire required.  
Follow Code.  
3. A separate electrical circuit must be run from  
the main electrical service with an over-current  
device/disconnect in the circuit. A service switch is  
recommended and may be required by some local  
jurisdictions.  
Heat Anticipator in Thermostat should be set to match  
the requirements of the control to which it is connected.  
See Figure 20 for desired system and heat anticipator  
setting. If system tends to overheat above the  
thermostat's temperature setting, reduce heat anticipator  
setting by .1 or .2 amps. If system tends to short cycle  
without reaching desired room temperature, increase  
heat anticipator setting by .1 or .2 amps.  
4. Use anti-short bushings on all wiring passing  
through boiler jacket, junction boxes and/or control  
boxes.  
5. Use armored cable (BX) over all exposed line  
voltage wiring.  
3ꢀ  
33  
34  
35  
BOILER SEQUENCE OF OPERATION WITH PROBE LWCO (See Figure 18)  
When the thermostat calls for heat, it energizes the R8285C Control Center relay which in turn energizes the cad cell  
primary control, bringing on the burner. The burner will operate in the following sequence: Prepurge for the first 10  
seconds; fire until the thermostat is satisfied or the limit setting on the high limit is reached; post-purge for the last 10  
seconds. When the pressure limit control restores the circuit on a drop in pressure, the burner will start if the thermo-  
stat is still calling for heat.  
The probe low water cut-off will shut down the burner after a 10-15 second delay, if the water level in the boiler drops  
below the probe level.  
The Hydrolevel CG450 low water cut-off will shut down the burner for 90 seconds every 10 minutes of firing time to  
allow water level to stabilize. If the water level is too low the burnerwill not be allowed to restart.  
The probe low water cut-off will reset and restart the burner with a call for heat a few seconds after the water is re-  
turned to its normal level.  
On burner start, if the cad cell does not see flame within approximately 15 seconds, primary control will shut burner  
down and enter into a recycle mode, after 60 seconds burner will restart and repeat trial for ignition. If after three  
(3) trials for ignition, flame is not detected, control will enter into restricted mode and must be reset manually before  
burner can be restarted.  
When there is no demand for heat, the operating control will maintain the boiler water temperature at the selected  
setting for proper operation of the domestic water heater, if equipped with optional tankless heater.  
BOILER SEQUENCE OF OPERATION WITH PROBE LWCO (See Figure 19)  
When the thermostat calls for heat, it energizes the R8285C Control center relay, which in  
turn energizes the cad cell primary control, bringing on the burner. The burner will  
operate in the following sequence: Prepurge for the first 10 seconds; fire until the  
thermostat is satisfied or the limit setting on the high limit is reached; post-purge  
for the last 10 seconds. When the pressure limit control restores the circuit on a  
McDonnell & Miller PS-801  
Terminals May be Lettered or  
Numbered as Follows:  
Wire  
Color  
Numbered Lettered  
Terminals Terminals  
drop in pressure, the burner will start if the thermostat is still calling for heat.  
The probe low water cut-off will shut down the burner after a 10-15 second delay, if  
the water level in the boiler drops below the probe level.  
The probe low water cut-off will reset and restart the burner with a call for heat a  
few seconds after the water is returned to its normal level.  
On burner start, if the cad cell does not see flame within approximately 15 sec-  
onds, primary control will shut burner down and enter into a recycle mode, after 60  
seconds burner will restart and repeat trial ignition. If after three (3) trials for igni-  
tion, flame is not detected, control will enter into restricted mode and must be reset  
manually before burner can be restarted.  
RD  
BK  
5
1
B
H
WH  
2
N
Jumper  
1-3  
H-C  
When there is no demand for heat, the operating control will maintain the boiler  
water temperature at the selected setting for proper operation of the domestic  
water heater, if equipped with optional tankless heater.  
BOILER SEQUENCE OF OPERATION WITH FLOAT LWCO (See Figure ꢀ0)  
When the thermostat calls for heat, it energizes the R8285C Control center relay, which in turn energizes the cad cell  
primary control, bringing on the burner. The burner will operate in the following sequence: Prepurge for the first 10  
seconds; fire until the thermostat is satisfied or the limit setting on the high limit is reached; post-purge for the last 10  
seconds. When the pressure limit control restores the circuit on a drop in pressure, the burner will start if the thermo-  
stat is still calling for heat. The low water cut-off will shut down the burner if the water level in the boiler drops too low.  
The control resets and restarts the burner with a call for heat a few seconds after the water is returned to its normal  
level.  
On burner start, if the cad cell does not see flame within approximately 15 seconds, primary control will shut burner  
down and enter into a recycle mode, after 60 seconds burner will restart and repeat trial for ignition. If after three  
(3) trials for ignition, flame is not detected, control will enter into restricted mode and must be reset manually before  
burner can be restarted.  
When there is no demand for heat, the operating control will maintain the boiler water temperature at the selected set-  
ting for proper operation of the domestic water heater, if equipped with optional tankless heater.  
36  
SECTION VII: OIL PIPING  
A. GENERAL  
1. Use flexible oil line(s) so the burner swing door  
WARNING  
Under no circumstances can copper with sweat  
style connectors be used.  
can be opened without disconnecting the oil supply  
piping.  
2. A supply line fuel oil filter is recommended as a  
minimum for all firing rates but a pleated paper fuel  
oil filter is recommended for the firing rates below  
1.0 gph to prevent nozzle fouling.  
NOTICE  
Some jurisdictions require the use of a fusible  
shutoff valve at the tank and/or the burner. In  
addition, some jurisdictions require the use of a  
fusible electrical interlock with the burner circuit.  
Check your local Codes for special requirements.  
3. Use Flared fittings only. Cast iron fittings cannot be  
used.  
NOTICE  
B. SINGLE PIPE OIL LINES  
Do not use compression fittings.  
1. Standard burners are provided with single-stage  
3450 rpm fuel units with the bypass plug removed  
for single-pipe installations.  
Oil piping must be absolutely airtight or leaks  
or loss of prime may result. Bleed line and  
fuel unit completely.  
2. The single-stage fuel unit may be installed single-  
pipe with gravity feed or lift. Maximum allowable  
lift is 8 feet. See Figure 21.  
Refer to your local jurisdictions regarding  
any special considerations for fuel supply  
requirements. In addition, refer to NFPA 31,  
Standard for the installation of Oil-Burning  
Equipment.  
3. Fuel Oil Line Deaerator – On many occasions a  
leaky oil delivery line can introduce air into the  
fuel oil supply system. This often creates a rough  
starting condition and can create a burner lockout  
state. In addition to fixing the leak, a fuel line  
deaerator can be installed to eliminate air. The  
single line from the fuel tank is connected to the  
deaerator. The burner pump must be connected  
to the deaerator as a two pipe system. Follow the  
oil pump manufacturer’s recommendations for  
conversion to a two pipe system.  
4. Use of a high efficiency micron filter (Garber or  
equivalent) in addition to a conventional filter is  
highly recommended.  
5. Piping used to connect the oil burner to the oil  
supply tank shall not be smaller than 3/8" iron pipe  
or 3/8" OD copper tubing. Copper tubing shall have  
a .032" minimum wall thickness.  
Figure ꢀ1: Single Pipe Oil Line  
3ꢁ  
C. TWO PIPE OIL LINES  
3. Under no circumstances is a manual shutoff valve to  
be located on the return line of a two pipe system.  
Accidental closure of the return line will rupture the  
oil pump seals.  
1. For two piped systems, where more lift is required,  
the two-stage fuel unit is recommended. Table  
5 (two-stage) and Table 6 (single-stage) show  
allowable lift and lengths of 3/8 inch and 1/2 inch  
OD tubing for both suction and return lines. Refer  
to Figure 22.  
TABLE 6: SINGLE-STAGE UNITS (3450 RPM) -  
TWO PIPE SySTEMS  
2. Follow the oil pump manufacturer’s recommenda-  
tions on the proper connections for a two pipe  
system. Some manufacturers require the insertion  
of a bypass plug.  
Maximum Length of Tubing  
"H" + "R" (See Figure 22)  
3/8" OD Tubing 1/2" OD Tubing  
(3 GPH) (3 GPH)  
Lift "H"  
(See Fig. 21)  
TABLE 5: TWO-STAGE UNITS (3450 RPM) -  
0'  
1'  
84'  
78'  
73'  
68'  
63'  
57'  
52'  
47'  
42'  
36'  
31'  
26'  
21'  
---  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
83'  
TWO PIPE SySTEMS  
Maximum Length of Tubing  
2'  
"H" + "R" (See Figure 22)  
3/8" OD Tubing 1/2" OD Tubing  
(3 GPH) (3 GPH)  
Lift "H"  
(See Fig. 22)  
3'  
4'  
5'  
0'  
2'  
93'  
85'  
77'  
69'  
60'  
52'  
44'  
36'  
27'  
---  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
76'  
6'  
7'  
4'  
8'  
6'  
9'  
8'  
10'  
11'  
12'  
13'  
14'  
10'  
12'  
14'  
16'  
18'  
62'  
---  
41'  
Figure ꢀꢀ: Two Pipe Oil Lines  
38  
SECTION VIII: SYSTEM START-UP  
WARNING  
All boilers equipped with burner swing door have a potential hazard which can cause severe property damage,  
personal injury or loss of life if ignored. Before opening swing door, turn off service switch to boiler to  
prevent accidental firing of burner outside the combustion chamber. Be sure to tighten swing door fastener  
completely when service is completed.  
1. SET ROOM THERMOSTAT about 10° above  
A. ALWAYS INSPECT INSTALLATION  
BEFORE STARTING BURNER.  
room temperature.  
2. PRESS RED RESET BUTTON on front of  
burner cover, hold for one (1) second and release to  
reset primary control.  
1. Verify that the venting, water piping, oil piping, and  
electrical system are installed properly. Refer to  
Installation Instructions contained in this manual.  
3. On STEAM BOILERS:  
2. Confirm all electrical, water and oil supplies are  
turned off at the source and that the vent is clear  
from obstructions.  
a. With an L404F1367 - set cut-out pressure  
(MAIN scale) on the pressure limit for (1) PSI  
and differential pressure (DIFF.) for .5 PSI.  
These pressures may be varied to suit individual  
requirements of the system.  
WARNING  
Completely read, understand and follow all  
instructions in this manual before attempting  
start up.  
4. On STEAM BOILERS WITH TANKLESS  
DOMESTIC WATER HEATERS, set boiler  
water temperature dial on L4006 operating control  
at 190°F (max.). Set differential at 10°.  
B. FILL HEATING SYSTEM WITH WATER.  
E. ADJUST OIL BURNER BEFORE  
STARTING.  
NOTICE  
1. CHECK BURNER AIR BAND, AIR SHUTTER  
AND HEAD SETTING (if applicable), readjust if  
necessary, see Table 8 at rear of manual.  
It is important, especially in a steam system, to  
properly remove the oil and dirt from the system.  
Failure to clean the system can result in erratic  
water lines and surging.  
2. OPEN ALL OIL LINE VALVES.  
3. Attach a plastic hose to fuel pump vent fitting and  
CLEAN HEATING SYSTEM if boiler water or  
condensate return water is dirty or if erratic water lines  
or surging exist after a few days of boiler operation.  
provide a pan to catch the oil.  
4. OPEN FLAME OBSERVATION PORT COVER  
on burner swing door.  
Refer to Maintenance and Service Instructions Section  
of this manual for proper cleaning instructions for  
steam and water boilers.  
F. START OIL BURNER.  
1. Open vent fitting on fuel pump.  
1. STEAM BOILERS — Fill boiler to normal water  
2. PRESS RED RESET BUTTON on front of burner  
cover, hold for one (1) second and release to reset  
primary control.  
line. Refer to Figure No. 1.  
WARNING  
3. TURN ‘ON’ BURNER service switch and  
allow burner to run until oil flows from vent  
fitting in a SOLID stream without air bubbles for  
approximately 10 seconds.  
The maximum operating pressure of this boiler is  
posted on the ASME Data Label located on the top  
of the boiler. Never exceed this pressure. Do not  
plug relief valve.  
NOTE: For Primary Control "Pump Priming  
Cycle" details, see Paragraph I, No. 2., Step a.,  
Item ii .  
C. CHECK CONTROLS, WIRING AND  
BURNER to be sure that all connections are tight and  
burner is rigid, that all electrical connections have been  
completed and fuses installed, and that oil tank is filled  
and oil lines have been tested.  
4. Close vent fitting and burner flame should start  
immediately after prepurge is completed. Prepurge  
prevents burner flame until 15 seconds has elapsed  
after initial power is applied to burner. During  
prepurge the motor and igniter will operate but the  
oil valve will remain closed. Refer to Oil Primary  
Control Instructions for more details.  
D. SET CONTROLS with burner service switch turned  
“OFF”.  
39  
See Table 8 (at rear of this manual) for details  
regarding the overfire pressure when baffles are both  
installed and removed.  
5. Adjust oil pressure.  
a. When checking a fuel unit's operating pressure, a  
reliable pressure gauge may be installed in either  
the bleeder port or the nozzle port. See Figure  
23.  
3. READJUST THE HEAD SETTING only if  
necessary.  
b. Locate oil pressure adjusting screw and turn  
screw to obtain proper pump pressure, refer to  
Table 8 at rear of manual.  
a. MST288 & MST396:  
Beckett MB(L1) Head burner has a fixed head  
which is non-adjustable.  
c. To check the cut-off pressure, deadhead a reliable  
pressure gauge onto the copper connector tube  
attached to the nozzle port. Run the burner for  
a short period of time. Shut the burner off. The  
pressure should drop and hold.  
b. MST513 & MST629:  
Beckett MD(V1) (variable) Head burners have  
the ability to control air by moving the head. It  
might be necessary to move the head forward  
or back one position at a time to optimize the  
smoke and CO2 readings. See Figure 24.  
d. Remove the gauge and install bleeder port and/or  
reconnect the nozzle port line.  
4. TURN “OFF” BURNER and remove pressure  
gauge. Install gauge port/bleeder plug and tighten.  
Start burner again.  
WARNING  
Do not loosen or remove any oil line fittings while  
burner is operating.  
5. FLAME FAILURE  
The MegaSteam™ boiler controls operate the burner  
automatically. If for unknown reasons the burner  
ceases to fire and the reset button on the primary  
control has tripped, the burner has experienced  
ignition failure.  
WARNING  
Do not attempt to start the burner when excess oil  
has accumulated, when the unit is full of vapor, or  
when the combustion chamber is very hot.  
Figure ꢀ3: Adjusting Fuel Pump Pressure  
G. ADJUST OIL BURNER WHILE  
H. CHECK FOR CLEAN CUT OFF OF  
BURNER.  
OPERATING. (flame present)  
1. ADJUST DRAFT REGULATOR for a draft of  
zero inches (water gauge) in the canopy (see Figure  
18) after chimney has reached operating temperature  
and while burner is running. (At least five minutes)  
See Table 8 at rear of manual for details.  
1. AIR IN THE OIL LINE between fuel unit and  
nozzle will compress when burner is on and will  
expand when burner stops, causing oil to squirt from  
nozzle at low pressure as the burner slows down and  
causing nozzle to drip after burner stops. Usually,  
cycling the burner operation about 5 to 10 times will  
eliminate air from the oil line.  
2. READJUST THE AIR BAND on burner for a  
light orange colored flame while the draft in the  
canopy is zero inches water column ("w.c.). Use a  
smoke tester and adjust air for minimum smoke (not  
to exceed #1) with a minimum of excess air. Make  
final check using suitable instrumentation to obtain  
a CO2 of 11.5 to 12.5% with draft of zero inches  
water column ("w.c.) (water gauge) in canopy.  
These settings will assure a safe and efficient  
operating condition. If the flame appears stringy  
instead of a solid fire, try another nozzle of the same  
type. Flame should be solid and compact. After  
all adjustments are made recheck for a draft of zero  
inches water column ("w.c.) in the canopy. Replace  
plug at completion.  
2. IF NOZZLE CONTINUES TO DRIP, repeat  
Paragraph H, No. 1. If this does not stop the  
dripping, remove cut-off valve and seat, and wipe  
both with a clean cloth until clean, then replace  
and readjust oil pressure. If dripping or after burn  
persist replace fuel pump.  
I. TEST CONTROLS.  
1. Check thermostat operation. Raise and lower  
thermostat setting as required to start and stop  
burner.  
40  
41  
vi. Diagnostic LED: The indicator light on oil  
primary control provides lockout, recycle  
and cad cell indications as follows:  
WARNING  
Before installation of the boiler is considered  
complete, the operation of all boiler controls must  
be checked, particularly the primary control and  
pressure limit control.  
Flashing at 1 Hz (½ second on, ½ second  
off): system is locked out or in Restricted  
Mode.  
Flashing at ¼ Hz (2 seconds on, 2 seconds  
2. VERIFY PRIMARY CONTROL FEATURES  
using procedures outlined in Instructions furnished  
with control or instructions as follows:  
off): control is in Recycle Mode.  
On: cad cell is sensing flame.  
Off: cad cell is not sensing flame.  
a. FEATURES AND CONTROLS  
i. The R7184 is a microprocessor-based  
control. The indicator light provides  
diagnostic information for lockout, recycling  
and patented cad cell status. There is a  
manual reset button to exit the Lockout  
Mode and enter the Idle Mode (see Figure  
25).  
vii. Cad Cell Resistance Check: For proper  
operation it is important that the cad cell  
resistance is below 1600 ohms. During a  
normal call for heat, once the control has  
entered the Run Mode, press and release the  
reset button. Indicator light will flash 1 to 4  
flashes. See Table 7 for equivalent cad cell  
resistance.  
TABLE ꢁ: CAD CELL RESISTANCE WHEN  
SENSING FLAME  
Flashes  
Cad Cell Resistance in ohms  
Less than 400  
1
2
3
4
More than 400 and less than 800  
More than 800 and less than 1600  
More than 1600 and less than 5000  
b. CHECK OIL PRIMARY CONTROL  
Figure ꢀ5: Rꢁ184 Terminals, LED and Reset Button  
ii. Pump Priming Cycle: To facilitate purging  
air from the oil lines and filters, the R7184  
can be placed in a purge routine by pressing  
and releasing the reset button during the  
safety check, delayed valve-on, ignition or  
carry-over periods.  
CAUTION  
Due to the potential hazard of line voltage,  
only a trained, experienced service technician  
should perform the following safety checks.  
This control contains no field-serviceable  
parts. Do not attempt to take it apart.  
Replace entire control if operation is not as  
described.  
iii. Limited Recycle: This feature limits the  
number of recycle trials (for each call  
for heat) to a maximum of three trials. If  
the flame is lost three times and does not  
successfully satisfy a call for heat, the  
R7184 locks out.  
i. Preliminary Steps  
Check wiring connections and power  
supply.  
iv. Limited Reset (Restricted Mode): In order  
to limit the accumulation of unburned oil in  
the combustion area, the control can only be  
reset three times. The reset count returns to  
zero each time a call for heat is successfully  
completed.  
Make sure power is on to the controls.  
Make sure limit control is closed.  
Check contacts between ignitor and the  
electrodes.  
To reset from Restricted Mode: Press and  
hold the reset button for 30 seconds.  
When the LED flashes twice, the device  
has reset.  
Check the oil pump pressure.  
Check the piping to the oil tank.  
Check the oil nozzle, oil supply and oil  
filter.  
ii. Check Safety Features  
Safe Start:  
v. T-T Jumper: Select models have pre-  
installed T-T jumper. Do not remove  
jumper. See Figure 25.  
4ꢀ  
Place a jumper across cad cell terminals.  
If safety switch shuts down burner and  
resistance is above 1600 OHMS, open line  
switch to boiler. Access cad cell under  
ignitor, clean face of cad cell and see that  
cell is securely in socket. Check gasket  
around perimeter of ignitor lid for proper  
seal. If gasket is missing or damaged,  
replace gasket. Room light can effect cad  
cell resistance. Reset safety switch.  
Follow procedure to turn on burner.  
Burner must not start, indicator light turns  
on and control remains in Idle Mode.  
Remove jumper.  
iii. Simulate Ignition or Flame Failure:  
Follow procedure to turn on burner.  
Close hand valve in oil supply line.  
Close line switch to boiler. If burner starts  
and runs beyond safety switch cut-off  
time, cell is good. If not, install new cell.  
Failure occurs, device enters Recycle  
Mode. Indicator light flashes at ¼ Hz rate  
2 seconds on, 2 seconds off).  
Device tries to restart system after  
approximately 60 seconds.  
v. Power Failure Check: After Flame is  
established, turn the power off to the control/  
burner. The burner should shut down safely.  
When power is restored a normal ignition  
sequence should be started.  
After third Recycle Mode trial, safety  
switch locks out within safety switch  
timing indicated on label and control  
enters Restricted Mode. Indicator light  
flashes at 1 Hz rate (½ second on, ½  
second off). Ignition and motor stop and  
oil valves closes.  
3. WARNING — Check Pressure Limit Control  
— Jumper Thermostat Terminals. Allow burner to  
operate until shut-down by limit. Installation is not  
considered complete until this check has been made.  
iv.  
Cad Cell Check: See Figure 26.  
WARNING  
Jumper must be removed after this check.  
4. Check low water cut off control with water level at  
normal water line (see Figure 1). Raise thermostat  
setting to allow burner to operate. Open boiler drain  
to allow water level to drop to bottom of sight glass  
until burner operation is shut-down by low water  
cut-off.  
Close boiler drain and refill to normal water line.  
Burner should automatically restart during fill.  
Lower thermostat setting.  
Figure ꢀ6: Cad Cell Location  
5. Check operating control on boiler equipped with  
tankless heaters. With burner off, draw hot water  
until burner starts, then turn off hot water and check  
burner shut-down.  
Perform cad cell resistance check as  
outlined in control feature. If resistance is  
below 1600 OHMS and burner runs  
beyond safety cut-out time, cad cell is  
good.  
J. IF CONTROLS DO NOT MEET  
REqUIREMENTS outlined in Paragraph I.,  
replace control and repeat checkout procedures.  
43  
Important Product Safety Information  
Refractory Ceramic Fiber Product  
Warning:  
The Repair Parts list designates parts that contain refractory ceramic fibers  
(RCF). RCF has been classified as a possible human carcinogen. When  
exposed to temperatures about 1805°F, such as during direct flame contact,  
RCF changes into crystalline silica, a known carcinogen. When disturbed as a  
result of servicing or repair, these substances become airborne and, if inhaled,  
may be hazardous to your health.  
AVOID Breathing Fiber Particulates and Dust  
Precautionary Measures:  
Do not remove or replace RCF parts or attempt any service or repair work  
involving RCF without wearing the following protective gear:  
1. A National Institute for Occupational Safety and Health (NIOSH)  
approved respirator  
2. Long sleeved, loose fitting clothing  
3. Gloves  
4. Eye Protection  
• Take steps to assure adequate ventilation.  
• Wash all exposed body areas gently with soap and water after contact.  
• Wash work clothes separately from other laundry and rinse washing  
machine after use to avoid contaminating other clothes.  
• Discard used RCF components by sealing in an airtight plastic bag. RCF  
and crystalline silica are not classified as hazardous wastes in the United  
States and Canada.  
First Aid Procedures:  
• If contact with eyes: Flush with water for at least 15 minutes. Seek  
immediate medical attention if irritation persists.  
• If contact with skin: Wash affected area gently with soap and water.  
Seek immediate medical attention if irritation persists.  
• If breathing difficulty develops: Leave the area and move to a location  
with clean fresh air. Seek immediate medical attention if breathing  
difficulties persist.  
• Ingestion: Do not induce vomiting. Drink plenty of water. Seek  
immediate medical attention.  
44  
SECTION Ix: MAINTENANCE AND SERVICE INSTRUCTIONS  
h. Clean the pipe threads of the probe to remove  
old, hardened pipe dope and other foreign matter.  
i. Apply a moderate amount of good quality pipe  
dope to the pipe threads on the probe, leaving the  
two end threads bare. Do not use PTFE (Teflon)  
tape.  
j. Screw the probe into the boiler tapping.  
k. Mount the low water cut-off control on the  
probe.  
A. MAINTENANCE OF LOW WATER CUT-  
OFF DEVICES  
WARNING  
Probe and float type low water cut-off devices  
require annual inspection and maintenance.  
1. PROBE TYPE LOW WATER CUT-OFF  
Although these devices are solid state in their  
operation, the probe is exposed to possible  
contamination in the boiler water and subject to  
fouling.  
l. Reconnect the control to probe wiring.  
m. Fill the boiler to its normal waterline.  
n. Add boiler water treatment compound as needed  
(refer to Paragraph B.).  
It is important to physically remove the probe from  
the boiler tapping annually and inspect that probe  
for accumulation of scale or sediment.  
Follow these steps to inspect, clean and/or replace  
the probe:  
a. Turn off electric service to the boiler.  
b. Drain boiler water to a level below the tapping  
for the probe.  
o. Restore electric service to the boiler.  
p. Fire burner to bring the water in the boiler to a  
boil to drive off free oxygen.  
q. WARNING — BEFORE RETURNING  
BOILER TO SERVICE: Follow the low water  
cut-off check out procedure in Section VIII,  
Paragraph I, No. 4.  
c. Disconnect wiring connections between the low  
water cut-off control and the probe.  
d. Remove the low water cut-off control from the  
probe.  
2. FLOAT TYPE LOW WATER CUT-OFF  
During the heating season, if an external low water  
cut-off is on the boiler, the blow off valve should  
be opened once a month (use greater frequency  
where conditions warrant), to flush out the sediment  
chamber so the device will be free to function  
properly.  
DANGER  
Assure that the boiler is at zero pressure before  
removing the LWCO probe. Do not rely on the  
pressure gauge to indicate that the boiler is at  
zero pressure. Open the safety valve to relieve  
all internal pressure prior to proceeding. Safety  
valve discharge piping must be piped such that  
the potential for burns is eliminated.  
Low water cut-offs and water feeders should  
be dismantled annually by qualified personnel,  
to the extent necessary to insure freedom from  
obstructions and proper functioning of the  
working parts. Inspect connecting lines to boiler  
for accumulation of mud, scale, etc., and clean as  
required. Examine all visible wiring for brittle or  
worn insulation and make sure electrical contacts  
are clean and that they function properly. Give  
special attention to solder joints on bellows and float  
when this type of control is used. Check float for  
evidence of collapse and check mercury bulb (where  
applicable) for mercury separation or discoloration.  
Do not attempt to repair mechanisms in the field.  
Complete replacement mechanisms, including  
necessary gaskets and installation instructions are  
available from the manufacturer.  
e. Unscrew the probe from the boiler tapping.  
f. Inspect that portion of the probe that is exposed  
to the boiler water for a scale or sediment  
buildup.  
g. Light deposits may be removed by wiping the  
probe with a damp cloth. Wiping the probe with  
a cloth soaked in vinegar will remove more  
tenacious lime deposits. The most stubborn  
deposits may be removed from the probe by  
using a diluted amount, 3 parts of water to 1 part  
of phosphoric acid (H2PO4).  
B. BOILER AND SYSTEM CLEANING  
INSTRUCTIONS FOR TROUBLE FREE  
OPERATION  
CAUTION  
1. STEAM BOILERS  
Exercise caution when handling phosphoric acid  
and follow the instruction label on its container.  
a. Oil, greases & sediments which accumulate in a  
new boiler and piping must be removed in order  
to prevent an unsteady water line and carry over  
of the water into the supply main above boiler.  
45  
drain. Close gate valve in Hartford Loop and  
open drain valve in return main. Fill boiler  
to normal water level, turn on oil burner and  
operate boiler at this water level for at least  
30 minutes after the condensate begins to  
run hot, then turn off burner.  
Close all radiator valves. Remove all supply  
main air valves and plug the openings in  
supply main.  
Operate the boiler with steam in the entire  
system for a few days allowing the condensate  
to return to the boiler. If the condensate can  
temporarily be wasted, operate boiler only for  
the length of time it takes for condensate to run  
clear. If the latter cannot be achieved or if the  
condensate is returned to the boiler, boil out  
the boiler using the SURFACE BLOW-OFF  
connection, see Figure 7.  
i. Drain boiler until 1” of water is visible in  
gauge glass. Run temporary 1½” NPT pipe  
line from the surface blow-off connection to  
an open drain or some other location where  
hot water may be discharged safely. Do not  
install valve in this line.  
ii. Draw about 5 gallons of hot water from  
boiler into a container and dissolve into it  
the appropriate amount of a recommended  
boilout compound. Remove safety valve  
from boiler and pour this solution into  
boiler, then reinstall safety valve.  
iii. Turn on oil burner and keep operating while  
feeding water to boiler slowly. This will  
raise water level in boiler slowly so that  
water will be boiling hot and will rise slowly  
into supply main and back through return  
main, flowing from drain hose at about  
180°F. Continue until water runs clear from  
drain hose for at least 30 minutes.  
ii. Drain about 5 gallons of hot water from  
boiler into a container and dissolve into it  
an appropriate amount of recommended boil  
out compound. Remove safety valve & add  
solution to boiler water thru exposed tapping  
using a funnel.  
NOTICE  
iv. Stop feeding water to boiler but continue  
operating oil burner until excess water in  
boiler flows out through supply main and  
water lowers (by steaming) until it reaches  
normal level in boiler. Turn off oil burner.  
Drain boiler. Open all radiator valves.  
Reinstall all supply main air valves. Open  
gate valve in Hartford Loop.  
Check with local authorities or consult local  
water treatment services for acceptable chemical  
cleaning compounds.  
iii. Start burner and operate sufficiently to boil  
the water without producing steam pressure.  
Boil for about 5 hours. Open boiler feed  
pipe sufficiently to permit a steady trickle  
of water from the surface blow-off pipe.  
Continue this slow boiling and trickle of  
overflow for several hours until the water  
coming from the overflow is clear.  
iv. Stop burner and drain boiler in a manner  
and to a location that hot water can be  
discharged with safety.  
v. Refill boiler to normal water line. If water  
in gauge glass does not appear to be clear,  
repeat steps (i. thru iii.) and boil out the  
boiler for a longer time.  
v. When boiler has cooled down sufficiently  
(crown sheet of sections are not too hot to  
touch), close the drain valves at boiler and  
in return main and feed water slowly up to  
normal level in boiler. Turn on oil burner  
and allow boiler to steam for 10 minutes,  
then turn off burner. Draw off one quart of  
water from bottom gauge glass fitting and  
discard. Draw off another quart sample and  
if this sample is not clear, repeat the cycle  
of draining the boiler and return main and  
refilling the boiler until sample is clear.  
vi. If the boiler water becomes dirty again  
at a later date due to additional sediment  
loosened up in the piping, close gate valve  
in Hartford Loop, open drain valve in  
return main, turn on oil burner and allow  
Condensate to flow to drain until it has run  
clear for at least 30 minutes while feeding  
water to boiler so as to maintain normal  
water level. Turn off oil burner, drain boiler,  
open gate valve in Hartford Loop, then  
repeat Step 1 above.  
b. Low pressure steam boilers such as the  
MegaSteam™, should be maintained with  
appropriate water treatment compounds.  
Add suitable water treatment compounds as  
recommended by your qualified water treatment  
company.  
c. Remove temporary surface blow-off piping, plug  
tapping and reinstall safety valve. Boil or bring  
water temperature to 180°F promptly in order to  
drive off the dissolved gases in the fresh water.  
d. If unsteady water line, foaming or priming  
persist, install gate valve in Hartford Loop and  
drain valves in return main and at boiler as  
shown in Figure 11 and proceed as follows:  
e. Make pH or Alkalinity Test.  
After boiler and system have been cleaned and  
refilled as previously described, test the pH of  
the water in the system. This can easily be done  
i
Connect hoses from drain valves to floor  
46  
More make-up water and higher concentrations of  
contaminants damage the boiler sooner. Our warranty  
does not cover oxygen corrosion and sediment-  
related damage. Clearly it is in everyone’s best  
interest to prevent this type of failure. You can do your  
part by ensuring that your system is leak-free.  
by drawing a small sample of boiler water and  
testing with hydrion paper which is used in the  
same manner as litmus paper, except it gives  
specific readings. A color chart on the side of  
the small hydrion dispenser gives the reading in  
pH. Hydrion paper is inexpensive and obtainable  
from any chemical supply house or through your  
local druggist. The pH should be higher than  
7, but lower than 11. Add some of the washout  
chemical (caustic soda), if necessary, to bring the  
pH within the specified range.  
D. ATTENTION TO BOILER WHILE NOT IN  
OPERATION.  
NOTICE  
f. Boiler is now ready to be put into service.  
If boiler is not used during winter time, it must be  
fully drained to prevent freeze damage.  
C. ExCESSIVE MAKE-UP WATER  
1. Spray inside surfaces with light lubricating or  
crankcase oil using gun with extended stem so as to  
reach all corners.  
IMPORTANT  
IF, DURING NORMAL OPERATION, IT IS  
NECESSARy TO ADD MORE WATER THAN  
INDICATED BELOW, CONSULT A QUALIFIED  
SERVICE TECHNICIAN TO CHECK yOUR  
SySTEM FOR LEAKS.  
2. With steam boilers, at end of season add sufficient  
water to fill boiler to top of water column and leave  
it that way until fall when water should be drained  
again to proper level. If at this time boiler water is  
dirty, drain water, flush out boiler, and refill with  
clean water to prescribed water level.  
EXCESSIVE WATER ADDITION:  
(Gallons / Month)  
3. Always keep the manual fuel supply valve shut off  
if the burner is shut down for an extended period of  
time.  
MSTꢀ88: 6  
MST396: 8  
MST6ꢀ9: 11  
MST513: 9½  
4. To recondition the heating system in the fall season  
after a prolonged shut down, follow the instructions  
outlined in Section VIII, Paragraphs A through J.  
A leaky system will increase the volume of make-up  
water supplied to the boiler, which can significantly  
shorten the life of the boiler. Entrained in make-up  
water are dissolved minerals, salts and oxygen. When  
the fresh, cool make-up water is heated in the boiler, the  
minerals fall out as sediment, the salts coat the inside  
of the boiler, and the oxygen escapes as a gas. The  
accumulation of sediment eventually isolates the water  
from contacting the cast iron. When this happens the  
cast iron in that area gets extremely hot and eventually  
cracks. The presence of free oxygen or chloride salts  
in the boiler corrodes the cast iron from the inside.  
WARNING  
This boiler contains controls which may cause the  
boiler to shut down and not restart without service.  
If damage due to frozen pipes is a possibility, the  
heating system should not be left unattended  
in cold weather; or appropriate safeguards and  
alarms should be installed on the heating system  
to prevent damage if the boiler is inoperative.  
4ꢁ  
SECTION x: BOILER CLEANING  
WARNING  
All boiler cleaning must be completed with burner service switch turned off. Boilers equipped with burner  
swing door have a potential hazard which can cause severe property damage, personal injury or loss of life  
if ignored. Before opening swing door, turn off service switch to boiler to prevent accidental firing of burner  
outside the combustion chamber. Disconnect the burner plug from the receptacle in the front jacket. Be sure  
to tighten swing door fastener completely when service is completed.  
A. CLEAN THE FLUEWAYS (See Figure 27).  
C. AFTER CLEANING, vacuum all remaining debris  
as necessary. Inspect burner swing door insulation, and  
rope gasket for signs of damage. If damaged, replace as  
needed.  
1. For access to the combustion chamber remove the  
two (2) 3/8" - 16 cap screws. If boiler is equipped  
with flexible fuel line(s), swing door open.  
D. REASSEMBLE BOILER.  
2. Remove the two smoke box clean-out covers from  
the rear smoke box by removing the four 5/16"-18  
hex head bolts. It is NOT necessary to remove the  
vent connector from the smoke box to clean boiler.  
If necessary, remove the vent connector if there is  
evidence of heavy soot accumulation in the boiler  
or to inspect base of chimney for condensate or  
accumulation of debris.  
CAUTION  
Do not start the burner unless the burner swing  
door and canopy cover plates are secured in  
place.  
1 Insert the baffles (if originally installed) into the  
correct flue way. The baffles are installed in the 2nd  
pass (two inner flue ways) on the MST396, MST513  
and MST629.  
3. Remove the baffles (if installed) from the flue  
passages. There is a pair of baffles in each boiler.  
The baffles are installed in the 2nd pass (two inner  
flue ways) on the MST396, MST513 and MST629.  
4. Clean the 3rd Pass – Insert a 2" dia. x 42" long  
wire or fiber bristle brush into each of the two 3rd  
passes. Using long strokes push the brush all the  
way through the boiler until the brush has exited  
the smoke box opening. Pull the brush all the way  
forward until it has exited the front of the boiler.  
Continue this operation for the entire height of the  
flue way until clean. Repeat the operation for the  
other 3rd pass flue way.  
5. Clean the 2nd Pass - Insert a 2" dia. x 42" long wire  
or fiber bristle brush into each of the two 2nd passes.  
Using long strokes push the brush all the way  
through the boiler until the brush hits the back wall  
of the reversing chamber. Pull the brush all the way  
forward until it has exited the front of the boiler.  
Continue this operation for the entire height of the  
flue way until clean. Repeat the operation for the  
other 2nd pass flue way.  
2. Attach the smoke box clean-out covers onto the  
rear of the boiler. Verify that the rope gasket is  
in good working order before assembly. Replace  
rope gasket if necessary. Use the 3/8" hardware  
originally removed. Do not over tighten. They  
should be snug but not bottomed out.  
NOTICE  
When securing burner swing door make sure door  
is drawn-in equally on both sides.  
Tighten swing door hardware to provide adequate  
seal to rope gasket around perimeter of door.  
Use an alternating tightening method from right side  
to left side cap screw to pull door tight equally.  
NOTICE  
Do not overtighten. The rope gasket will provide  
sufficient seal when the door is snugged into  
place.  
6. Vacuum the loose debris in the bottom of the  
combustion chamber and smoke box.  
B. CLEAN THE COMBUSTION CHAMBER  
– Use a wire or fiber bristle brush to clean the surfaces  
of the combustion chamber. Vacuum all of the loose  
debris in the bottom of the combustion chamber.  
48  
Figure ꢀꢁ: Cleaning Boiler Flueways and Combustion Chamber Surfaces  
WARNING  
The boiler must be connected to an approved chimney in good condition. Serious property damage could  
result if the boiler is connected to a dirty or inadequate chimney. The interior of the chimney flue must be  
inspected and cleaned before the start of the heating season and should be inspected periodically throughout  
the heating season for any obstructions. Aclean and unobstructed chimney flue is necessary to allow noxious  
fumes that could cause injury or loss of life to vent safely and will contribute toward maintaining the boiler's  
efficiency.  
49  
SECTION xI: TROUBLE SHOOTING  
A. COMBUSTION  
8. COLD OIL — If the oil temperature approaching  
the fuel pump is 40°F or lower, poor combustion or  
delayed ignition may result. Cold oil is harder to  
atomize at the nozzle. Thus, the spray droplets get  
larger and the flame shape gets longer. An outside  
fuel tank that is above grade or has fuel lines in a  
shallow bury is a good candidate for cold oil. The  
best solution is to bury the tank and lines deep  
enough to keep the oil above 40°F.  
1. NOZZLES — Although the nozzle is a relatively  
inexpensive device, its function is critical to the  
successful operation of the oil burner. The selection  
of the nozzle supplied with the MegaSteam™ boiler  
is the result of extensive testing to obtain the best  
flame shape and efficient combustion. Other brands  
of the same spray angle and spray pattern may be  
used but may not perform at the expected level of  
CO2 and smoke. Nozzles are delicate and should be  
protected from dirt and abuse. Nozzles are mass-  
produced and can vary from sample to sample. For  
all of those reasons a spare nozzle is a desirable item  
for a serviceman to have.  
9. HIGH ALTITUDE INSTALLATIONS — Air  
openings must be increased at higher altitudes. Use  
instruments and set for 11.5 to 12.5% CO2.  
10.START-UP NOISE — Late ignition is the cause  
of start-up noises. If it occurs recheck for electrode  
settings, flame shape, air or water in the fuel lines.  
2. FLAME SHAPE — Looking into the combustion  
chamber through the observation port, the flame  
should appear straight with no sparklers rolling up  
toward the crown of the chamber. If the flame drags  
to the right or left, sends sparklers upward or makes  
wet spots on the chamber walls, the nozzle should  
be replaced. If the condition persists look for fuel  
leaks, air leaks, water or dirt in the fuel as described  
above.  
11. SHUT DOWN NOISE — If the flame runs out of  
air before it runs out of fuel, an after burn with noise  
may occur. That may be the result of a faulty cut-off  
valve in the fuel pump, or it may be air trapped in the  
nozzle line. It may take several firing cycles for that  
air to be fully vented through the nozzle. Water in the  
fuel or poor flame shape can also cause shut down  
noises.  
3. FUEL LEAKS — Any fuel leak between the  
pump and the nozzle will be detrimental to good  
combustion results. Look for wet surfaces in the air  
tube, under the ignitor, and around the air inlet. Any  
such leaks should be repaired as they may cause  
erratic burning of the fuel and in the extreme case  
may become a fire hazard.  
NOTICE  
CHECK TEST PROCEDURE. A very good test for  
isolating fuel side problems is to disconnect the  
fuel system and with a 24" length of tubing, fire  
out of an auxiliary five gallon pail of clean, fresh,  
warm #ꢀ oil from another source. If the burner runs  
successfully when drawing out of the auxiliary  
pail then the problem is isolated to the fuel or fuel  
lines being used on the jobsite.  
4. AIR LEAKS — Any such leaks should be repaired,  
as they may cause erratic burning of the fuel and in  
extreme cases may become a fire hazard.  
5. GASKET LEAKS — If 11.5 to 12.5% CO2 with a  
#1 smoke cannot be obtained in the breeching, look  
for air leaks around the burner mounting gasket,  
observation door, and canopy gasket. Such air leaks  
will cause a lower CO2 reading in the breeching. The  
smaller the firing rate the greater effect an air leak  
can have on CO2 readings.  
B. OIL PRIMARY CONTROL  
1. Burner (control) will not come on.  
a. No power to control.  
b. Control is in lockout or restricted mode. Press  
reset button for one (1) second to exit lockout. If  
control has recycled three times within the same  
call for heat, it will enter into restricted mode.  
To reset from restricted mode, refer to Section  
VIII, Paragraph I, No. 2 for details.  
6. DIRT — A fuel filter is a good investment.  
Accidental accumulation of dirt in the fuel system  
can clog the nozzle or nozzle strainer and produce a  
poor spray pattern from the nozzle. The smaller the  
firing rate, the smaller the slots become in the nozzle  
and the more prone to plugging it becomes with the  
same amount of dirt.  
c. CAD cell seeing light.  
d. CAD assembly defective.  
e. Control motor relay is stuck closed (see note  
below).  
7. WATER Water in the fuel in large amounts will  
stall the fuel pump. Water in the fuel in smaller  
amounts will cause excessive wear on the pump,  
but more importantly water doesn’t burn. It chills  
the flame and causes smoke and unburned fuel to  
pass out of the combustion chamber and clog the  
2. Burner (control) will light, then shut down after a  
short time, then restart after one (1) minute.  
a. CAD cell is defective.  
b. Air leaking into oil line causing flame out.  
c. Defective nozzle causing flame to be erratic.  
flueways of the boiler.  
50  
Note: The Safety Monitoring Circuit (SMC) is  
designed to provide lockout in the event of a  
stuck or welded motor relay.  
d. Excessive airflow or draft causing flame to leave  
burner head.  
e. Excessive back pressure causing flame to be  
erratic.  
NOTICE  
3. Control locks out after Trial For Ignition (TFI).  
a. No oil to burner.  
If flame is not established within 15 seconds  
of oil valve actuation (known as Trial For  
Ignition [TFI]) lockout will occur. Lockout is  
indicated by a red LED solid-on located on the  
oil primary control.  
b. Shorted electrodes.  
c. Nozzle clogged.  
d. Airflow too high.  
e. Ignitor module defective.  
f. CAD cell defective.  
Latch-up will occur if the control locks-out  
three (3) times during a call for heat. This  
is indicated by steady-on red and amber  
LED's.  
g. Oil valve stuck open or closed.  
SECTION xII: REPAIR PARTS  
All MegaSteam™ Boiler Repair Parts may be obtained through your local U.S. Boiler Co., Inc. Wholesale Distributor. Should  
you require assistance in locating a Wholesale Distributor in your area, or have questions regarding the availability of U.S. Boiler  
Co., Inc. products or repair parts, please contact Burnham Customer Service at (717) 481-8400 or Fax (717) 481-8408.  
51  
5ꢀ  
Item  
No.  
Description  
Part No. MST288 MST396 MST513 MST629  
1. BARE BOILER ASSEMBLy  
1A  
1B  
Front Section, Machined  
100569-01  
100571-01  
100573-01  
100676-01  
806600375  
7066003  
1
1
1
1
1
2
1
3
Center Section, Machined  
1C1  
1C2  
1D1  
1D2  
Rear Section (Htr.), Steam, Machined  
Rear Section (Non-Htr.), Steam, Machined  
Slip Nipple, 22-B Steel  
1
1
1
1
1
1
1
1
2
2
3
4
5" Cast Iron Slip Nipple  
2
2
3
4
Upper Tie Rod, 3/8" -16 x 16" Lg.  
Upper Tie Rod, 3/8" -16 x 21-1/2" Lg.  
Upper Tie Rod, 3/8" -16 x 27-1/2" Lg.  
Lower Tie Rod, 3/8" -16 x 15" Lg.  
Lower Tie Rod, 3/8" -16 x 20-3/4" Lg.  
Lower Tie Rod, 3/8" -16 x 27" Lg.  
3/8" Flat Washer, USS, Plain  
80861075  
80861033  
80861014  
80861016  
80861012  
80861018  
80860600  
80860400  
1
1
---  
1
---  
---  
1
1E  
1F  
---  
---  
1
---  
---  
1
---  
---  
1
---  
---  
1
---  
---  
4
---  
---  
4
---  
4
1G  
1H  
4
3/8" -16 Heavy Hex Nut, Plain  
4
4
4
4
Spanner Bar w/Threaded Inserts,  
1-1/4" x 1-1/2" x 20-3/8" Lg.  
100012-02  
100012-03  
100012-04  
2
2
---  
2
---  
---  
2
Spanner Bar w/Threaded Inserts,  
1-1/4" x 1-1/2" x 26-3/8" Lg.  
1J  
---  
---  
---  
---  
Spanner Bar w/Threaded Inserts,  
1-1/4" x 1-1/2" x 32-3/8" Lg.  
---  
1K  
1L  
Carriage Bolt, 3/8" -16 x 1-1/4" Lg., Plated  
Cap Screw, 5/16" -18 x 7/8" Lg., Plated  
Flat Washer, 5/16", USS, Plated  
Hex Nut, 5/16 -18, Serrated Flange, Plated  
Hinge Bracket  
100215-01  
80861371  
80860611  
80860443  
100014-01  
4
4
4
4
1
4
4
4
4
1
4
4
4
4
1
4
4
4
4
1
1M  
1N  
1P  
Hinge Bracket  
Mount Burner  
2
3
2
3
2
3
2
3
1Q  
1R  
5/16" -18 x 3/4" Lg. Cap Screw, Plated  
Cast Iron Burner Swing Door (Only)  
80861340  
100071-01  
1
1
1
1
53  
54  
Item  
No.  
Description  
Part No. MST288 MST396 MST513 MST629  
1. BARE BOILER ASSEMBLy (Continued)  
Burner Swing Door Insulation (Less Pockets)  
100039-01  
100039-02  
100097-01  
100096-01  
100074-01  
80860647  
100050-01  
100102-01  
80860611  
100021-01  
80860611  
80861340  
806603542  
1
---  
1
1
1
2
2
2
2
1
4
4
1
1
---  
1
1
1
2
2
2
2
1
4
4
1
1
---  
1
1
1
2
2
2
2
1
4
4
1
---  
1
1
1
1
2
2
2
2
1
4
4
1
1S  
Burner Swing Door Insulation (With Pockets)  
1T  
1U  
1V  
1W  
1X  
1Y  
1Z  
5/8" Dia. Rope Gasket - Burner Swing Door  
1/8" Dia. Rope Gasket - Observation Port  
Observation Port Cover  
5/16" Flat Washer, SAE, Plated  
Socket Head Cap Screw, 5/16" x 5/8" Lg., Plated  
Tap Bolt, 3/8" -16 x 1-3/4" Lg., Plated  
5/16" Flat Washer, USS, Plated  
1AA Smokebox  
1BB  
5/16" Flat Washer, USS, Plated  
1CC Cap Screw, 5/16" -18 x 3/4" Lg., Plated  
1DD 1/4" NPT Pipe Plug, Square Head, Brass  
6" Dia.  
7" Dia.  
100093-01  
100094-01  
1
1
1
---  
1
1EE  
1FF  
Smokebox Collar  
---  
---  
---  
5/16" Flat Washer, USS, Plated  
80860611  
80861371  
100104-01  
100095-01  
6036036  
2
2
2
2
1
1
1
2
2
2
2
1
1
1
2
2
2
2
1
1
1
2
2
2
2
1
1
1
1GG Cap Screw, 5/16" -18 x 7/8" Lg., Plated  
1HH Cast Iron Clean-Cut Cover (only)  
1JJ  
1KK  
1LL  
1/2" Dia. Rope Gasket - Clean-Cut Cover  
222A Heater Carton Assembly  
Tapped Heater Cover Plate - Rear Heater  
7036031  
1MM Heater Cover Plate Gasket  
8036068  
Cap Screw, 3/8" -16" x 7/8" Lg., Plated,  
ASME Grade SA307B  
1NN  
80861337  
80860647  
6
6
6
6
6
6
6
6
1PP  
5/16" Flat Washer, SAE, Plated  
55  
56  
Item  
No.  
Description  
Part No. MST288 MST396 MST513 MST629  
ꢀ. JACKET ASSEMBLy  
2A  
2B  
Jacket Front Panel Assembly w/Insulation  
Power Outlet Receptacle, w/Harness  
100575-01  
100605-01  
1
1
1
1
1
1
1
1
#8 x 1/2" Type AB Truss Head w/Shoulder, Sheet Metal  
Screw, Plated  
2C  
100038-01  
10  
10  
10  
10  
2D  
2E  
2F  
2G  
2H  
Jacket Rear Panel Assembly w/Insulation  
External Wiring Enclosure  
100578-01  
100602-01  
100046-01  
100035-01  
100047-01  
100614-03  
100614-04  
100614-05  
100581-03  
100581-04  
100581-05  
100583-03  
100583-04  
100583-05  
100585-03  
100585-04  
100585-05  
60228001  
60228002  
80860955  
1
1
1
1
1
1
1
1
Tap End Stud, 5/16" -18 x 3" Lg., Plain  
5/8" O.D. x 2-5/32" Lg. Jacket Spacer  
Acorn Nut, 5/16" -18, Plated  
2
2
2
2
2
2
2
2
2
2
2
2
1
1
---  
1
---  
---  
1
2J  
2K  
2L  
3" Thick Fiberglass Insulation Wrapper  
---  
---  
1
---  
---  
1
---  
---  
1
Jacket Left Side Panel - 3 Section  
Jacket Left Side Panel - 4 Section  
Jacket Left Side Panel - 5 Section  
Jacket Right Side Panel - 3 Section  
Jacket Right Side Panel - 4 Section  
Jacket Right Side Panel - 5 Section  
Jacket Top Panel - 3 Section  
---  
---  
1
---  
---  
1
---  
---  
1
---  
---  
1
---  
---  
1
---  
---  
1
---  
---  
1
---  
---  
1
---  
---  
1
2M  
Jacket Top Panel - 4 Section  
---  
---  
1
---  
---  
1
Jacket Top Panel - 5 Section  
---  
1
2N  
2P  
2Q  
Beckett Burner Enclosure Backer Plate  
Beckett Burner Enclosure Cover  
Knob, Dimco #2-116-335  
1
1
1
1
1
4
4
4
4
Sheet Metal Screw, Plated, Phillips Truss Head,  
Type AB, #8 x 1/2" Lg.  
2R  
2S  
80860000  
80860019  
2
1
2
1
2
1
2
1
Sheet Metal Screw, Plated, Phillips Pan Head,  
Type B, #8 x 1/2" Lg.  
5ꢁ  
58  
Item  
No.  
Description  
Part No.  
MST288 MST396 MST513 MST629  
3. MST - TRIM AND CONTROLS  
6" RC-STD Draft Regulator  
3A  
8116288  
8116289  
1
---  
1
1
---  
1
1
---  
1
---  
1
7" RC-STD Draft Regulator  
3B  
3C  
Pressure Gauge  
8056010  
1
Probe, Hydrolevel EL-1214 (for Hydrolevel CG450)  
Low Water Cut-off, Hydrolevel CG450 (less Probe)  
Low Water Cut-off, McDonnell & Miller PS-801  
Nipple, 3/4" NPT x 3" Lg.  
80160629  
80160623  
80160723  
806600002  
806601502  
806603010  
80160369  
81660530  
8056091  
1
1
1
1
3D  
1
1
1
1
3E  
3F  
3J  
1
1
1
1
1
1
1
1
1
1
1
1
1
---  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Elbow, 3/4" NPT x 90  
Syphon, 1/4" NPT x 1-7/8" x 4" x 90  
Pressure Limit, Honeywell L404F1367  
Safety Valve, 3/4" NPT, 15 PSI, Conbraco 13-511-08  
Gauge Glass Set, 6", Conbraco 20-104-10  
Low Water Cut-off, McDonnell & Miller 67  
Nipple, 1-1/2" NPT x 5" Lg.  
3K  
3L  
3M  
3N  
3P  
3Q  
3R  
3S  
3T  
3U  
3W  
80160597  
808600060  
806601105  
806603061  
80160400  
80160497  
80160848  
100042-01  
Tee, 1-1/2' x 1-1/2" x 3/4"  
Drain Valve, 3/4" NPT, Conbraco 35-302-03  
Limit, Honeywell L4006A2015  
Well, 1/2" NPT x 3", Honeywell 123872A  
Oil Primary Control, Honeywell R7184P1064  
Stainless Steel 2nd Pass Blueway Baffle  
Beckett AFG Oil Burner w/Gasket for:  
MST288 Spec. No. BCB7706  
100625-01  
100053-01  
1
---  
1
---  
---  
---  
---  
MST396 Spec. No. BCB7703  
---  
3X  
3Y  
MST513 Spec. No. BCB7704  
MST629 Spec. No. BCB7705  
100054-01  
100055-01  
---  
---  
---  
---  
1
---  
1
---  
(NOTE: See Pages 60 and 61 for burner Parts Breakdown)  
Fan Center, Honeywell R8285C w/Connectors  
100640-01  
1
1
1
1
59  
60  
BECKETT OIL BURNER PART NOS. FOR MEGASTEAM™ SERIES BOILERS  
NOTE: When ordering parts always give the serial and model numbers shown on the boiler and burner. Also  
provide the name of the part(s) and part number as listed below.  
Boiler Model  
MST288  
AFG70MMAQN  
BCB7706  
3492  
MST396  
AFG70MMAQN  
BCB7703  
3492  
MST513  
AFG70MLASN  
BCB7704  
3492  
MST629  
AFG70MKASN  
BCB7705  
3492  
Air Tube Combination  
Beckett's Spec. No.  
Air Band  
Air Band Nut  
4150  
4150  
4150  
4150  
Air Band Screw  
4198  
4198  
4198  
4198  
Air Shutter  
3709  
3709  
3709  
3709  
Air Shutter Screw  
Blower Wheel  
4198  
4198  
4198  
4198  
2999  
2999  
2999  
2999  
Coupling  
2454  
2454  
2454  
2454  
Low Firing Rate Baffle  
Bulkhead Knurled Locknut  
Connector Tube Assembly  
Electrode Clamp  
Electrode Clamp Screw  
Electrode Insulator Assembly  
Support / Spacer Assembly  
Escutcheon Plate  
Adjusting Plate Assembly  
Head  
Less  
Less  
Less  
Less  
3666  
3666  
3666  
3666  
5636  
5636  
5636  
5636  
149  
149  
149  
149  
4219  
4219  
4219  
4219  
5780  
5780  
5780  
5780  
5992  
5992  
5992  
5992  
---  
---  
---  
---  
5941  
5941  
5941  
5941  
5913  
5913  
5913  
5913  
Head Screws  
4221  
4221  
4221  
4221  
Flange Gasket  
3811  
3811  
3811  
3811  
AFG Housing  
5874GY  
21805E/218  
213  
5874GY  
21805E/218  
213  
5874GY  
21805E/218  
213  
5874GY  
21805E/218  
213  
Motor  
Nozzle Adapter  
Nozzle Line  
Electrode Assembly  
NL70MD  
21844  
NL70MD  
21844  
NL70MD  
21844  
NL70MD  
21844  
Oil Pump, Clean Cut,  
Single Stage  
Oil Pump, Clean Cut,  
Two-Stage  
21941  
21941  
21941  
21941  
Static Plate  
3383  
51771U  
42176  
4292  
3383  
51771U  
4217  
3383  
51771U  
4217  
3383  
51771U  
4217  
Ignitor  
Ignitor Hinge Screw  
Ignitor Holding Screw  
Ignitor Gasket Kit  
Wire Guard  
4292  
4292  
4292  
51304  
10251  
3741  
51304  
10251  
3741  
51304  
10251  
3741  
51304  
10251  
3741  
Junction Box  
Flame Detector  
Oil Solenoid Valve Coil  
Oil Solenoid Valve Cord  
7006Q  
21775U  
21807  
7006Q  
21775U  
21807  
7006Q  
21775U  
21807  
7006Q  
21775U  
21807  
61  
6ꢀ  
SERVICE RECORD  
DATE  
SERVICE PERFORMED  
63  
Limited Warranty  
FOR RESIDENTIAL CAST IRON STEAM BOILERS  
By this Warranty Statement the U.S. BoilerCompany, Inc. of Lancaster,  
5. This warranty applies only to boilers installed within the United States, and  
Canada.  
Pennsylvania issues limited warranties subject to the terms and conditions  
stated below. These limited warranties apply to residential cast iron boilers  
labeled Independence®, Independence® PV, V8Hand MegaSteamSeries,  
these warranties are issued only to the original homeowner at the original  
place of installation.  
6. In order for this warranty to be effective:  
a.) The boiler must have been properly installed in a single or two-family  
residential dwelling. This warranty does not apply to boilers installed in  
apartments or to commercial or industrial installation.  
FIRSTYEAR - LIMITED WARRANTY FOR  
RESIDENTIAL CAST IRON STEAM BOILERS  
b.) The boiler must have been assembled in strict compliance with  
installation instructions furnished with the boiler by U.S. Boiler Company, Inc.  
c.) Boiler components must not have been damaged in handling during  
shipment or installation.  
U.S. Boiler Company, Inc. warrants its residential cast iron steam boilers  
labeled Independence, Independence PV, V8H and MegaSteam Series to be  
free of defects in material and workmanship when shipped and to remain free  
of such defects under normal usage for a period of one year from the date of  
original installation. In the event that any part of such a steam boiler is found  
to be defective in material or workmanship during the one-year period, then  
U.S. Boiler Company, Inc. will repair or replace, at its option, the defective  
part.  
7. The foregoing provisions of this warranty shall be effective to the maximum  
extent permitted by applicable law, and, to the extent that any such  
provision would otherwise be inconsistent with applicable law, such  
provision shall be limited in effect to the minimum extent necessary to avoid  
such unconscionable result or inconsistency with applicable law.  
8. The remedy for breach of this warranty is expressly limited to the repair or  
replacement of any part found to be defective under conditions of normal  
use; and the remedy for breach of this warranty or for negligence does not  
extend to liability for incidental, special or consequential damages or losses  
such as loss of the use of the materials, inconvenience or loss of  
time. Some states do not allow the exclusion or limitation of incidental or  
consequential damages so the above limitation or exclusion may not apply  
to you.  
SECOND THROUGH 10YEAR - LIMITED  
WARRANTY FOR THE CAST IRON SECTION  
ASSEMBLY OF RESIDENTIAL CAST IRON STEAM BOILERS  
U.S. Boiler Company, Inc. warrants the cast iron section assembly of its  
residential cast iron steam boilers labeled Independence, Independence PV,  
V8H and MegaSteam Series, to be free of defects in material and  
workmanship when shipped and to remain free of such defects under normal  
usage for a period of 10 years from the date of original boiler installation.  
In the event that such cast iron section assembly is found to be defective in  
material or workmanship during this period, U.S. Boiler Company, Inc. will  
repair or replace, at its option, the defective cast iron section assembly.  
9. This warranty is in lieu of all others, and any and all express or implied  
warranties (including, without limitation, any implied warranties of  
merchantability or tness for a particular purpose) are expressly limited in  
duration to the period of the warranty as previously stated herein. Some  
states do not allow limitation on how long an implied warranty lasts, so  
the above limitation may not apply to you.  
FIRST THROUGH 5YEAR - LIMITED WARRANTY AGAINST  
WATERSIDE CORROSION IN THE MEGASTEAM SERIES  
10.Not withstanding any of the above provisions, U.S. Boiler Company, Inc.  
liability under this warranty shall not exceed the selling price of the  
product found to be defective.  
U.S. Boiler Company, Inc. warrants the cast iron sections of the MegaSteam  
boiler to resist TEMPERATURE INDUCED CHLORIDE ACTIVATED  
GRAPHITIC CORROSION for a period of ve years from the date of original  
installation. In the event that any cast iron section of a MegaSteam boiler fails  
due to this corrosion mechanism during this period, U.S. Boiler Company, Inc.  
will repair or replace, at its option, the failed cast iron section assembly.  
PROCEDURE FOR OBTAINING WARRANTY SERVICE  
In order to assure prompt warranty service the homeowner is requested  
to complete and mail the attached Warranty Card within ten days after the  
installation of the boiler, although failure to comply with this request will not  
void the homeowner’s rights under this warranty.  
LIFETIME NIPPLE LEAKAGE WARRANTY  
U.S. Boiler Company, Inc. warrants the cast iron and steel nipples that join the  
sections to be free from defects in material and workmanship for the lifetime  
of the original owner at the time of installation. In the event that such nipples  
are found to be defective in material or workmanship during this period, U.S.  
Boiler Company, Inc. will repair or replace at its option, the cast iron section  
assembly.  
Upon discovery of a condition believed to be related to a defect in material  
or workmanship covered by this warranty statement, the homeowner should  
notify the installer who will in turn notify the distributor. If this action is not  
possible or does not produce a prompt response, the homeowner should write  
to U.S. Boiler Company, Inc., at P.O. Box 3079, Lancaster, PA 17604 giving full  
particulars in support of the claim.  
ADDITIONAL TERMS AND CONDITIONS  
The homeowner is required to make available for inspection by U.S. Boiler  
Company, Inc. or its representative the parts claimed to be defective and, if  
requested by U.S. Boiler Company, Inc., to ship said parts prepaid to Burnham  
Hydronics at the above address for inspection or repair. In addition, the  
homeowner agrees to make all reasonable efforts to settle any disagreement  
arising in connection with his claim before resorting to legal remedies in the  
courts.  
1. This warranty does not cover expenses for removal or reinstallation. The  
homeowner will be responsible for the cost of removing and reinstalling  
the defective part or its replacement and all labor and material connected  
therewith. Replacement material will be invoiced to the distributor in the  
usual manner and will be subject to adjustment upon proof of defect.  
2. This warranty, in no way, can be considered as a guarantee of  
workmanship of an installer connected with the installation of the U.S.  
Boiler Company, Inc. boiler or as imposing on U.S. Boiler Company, Inc.  
liability of any nature for unsatisfactory performance as a result of faulty  
workmanship in the installation, which liability is expressly disclaimed.  
THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND YOU MAY  
ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE.  
3. This warranty will not be applicable if the boiler is used or operated  
over its rated capacity; or installed for uses other than home heating;  
or is not maintained in accordance with U.S. Boiler Company, Inc.  
recommendation or accepted good practice as determined by hydronics  
industry standards.  
4. This warranty will not be applicable if the boiler has been damaged as a  
result of being improperly serviced or operated, including but not limited  
to the following: operated with insufcient water, allowed to freeze; subject  
to ood conditions; or operated with water conditions and/or fuels or  
additives which cause unusual deposits or corrosion in or on the heat  
exchanger.  

Alphasonik PM6002E User Manual
Black Decker BLBD10GWUC User Manual
Canon 2567A004 User Manual
Citizen Systems Calculator SDC 3910 User Manual
Dell XLH1 User Manual
Hisense SPORT HB420S User Manual
HP (Hewlett Packard) 40gs User Manual
Hyundai H CMD7075 User Manual
JVC Car Stereo System KD R610 User Manual
JVC GR DF570 User Manual