Baxi Potterton Performa 24 Eco HE User Manual

You can rely on  
Installation & Service Instructions  
Performa  
24 Eco HE  
Condensing  
Combination Boiler  
2
Burner On  
Reset  
1
3
Flame Failure  
0
4
Power On  
bar  
These instructions include the Benchmark Commissioning  
Checklist and should be left with the user for safe keeping.  
© Baxi Heating UK Ltd 2009  
Installer Notification Guidelines  
Choose Building  
Regulations Notification  
Route  
Competent Person's  
Building Control  
Self Certification Scheme  
Install and Commission this  
appliance to manufacturer's  
instructions  
Contact your relevant Local  
Authority Building Control  
(LABC) who will arrange  
an inspection or contact  
a government approved  
inspector  
Complete the  
Benchmark Checklist  
If you notify via the ‘Gas Safe  
Register’, the register will issue  
the Building Regulations  
Install and Commission this  
appliance to manufacturer's  
instructions  
certificate on members’ behalf  
Scheme Members only  
Call ‘Gas Safe Register’ on:  
0800 408 5577  
Complete the  
Benchmark Checklist  
or log onto:  
within 10 days  
You must ensure that the  
certificate number issued by  
the ‘Gas Safe Register’ is written  
onto the Benchmark Checklist  
‘Gas Safe Register’ will issue a  
Building Regulations Compliance  
Certificate to the property owner  
and inform the relevant LABC  
LABC will record the data  
and will issue a  
certificate of compliance  
3
© Baxi Heating UK Ltd 2009  
Legislation  
IMPORTANT - Installation, Commissioning, Service & Repair  
This company declare that no substances harmful to health  
are contained in the appliance or used during appliance  
manufacture.  
This appliance must be installed in accordance with the manufacturer’s instructions and  
the regulations in force. Read the instructions fully before installing or using the  
appliance.  
The appliance is suitable only for installation in GB and IE and  
should be installed in accordance with the rules in force, and  
only used in a suitably ventilated location.  
In GB, this must be carried out by a competent person as stated in the Gas Safety  
(Installation & Use) Regulations.  
In GB, the installation must be carried out by a Gas Safe  
Registered Installer. It must be carried out in accordance with  
the relevant requirements of the:  
Definition of competence: A person who works for a Gas Safe registered company  
and holding current certificates in the relevant ACS modules, is deemed competent.  
• Gas Safety (Installation & Use) Regulations.  
• The appropriate Building Regulations either The  
Building Regulations, The Building Regulations  
(Scotland), Building Regulations (Northern Ireland).  
• The Water Fittings Regulations or Water Byelaws in  
Scotland.  
All Gas Safe registered engineers carry an ID card with their licence number and a  
photograph. You can check your engineer is registered by telephoning  
• The Current I.E.E. Wiring Regulations.  
In IE, this must be carried out by a competent person as stated in I.S. 813 “Domestic  
Gas Installations”.  
Where no specific instructions are given, reference should be  
made to the relevant British Standard Code of Practice.  
The addition of anything that may interfere with the normal operation of the appliance  
without express written permission from the manufacturer or his agent could invalidate  
the appliance warranty. In GB this could also infringe the Gas Safety (Installation and  
Use) Regulations.  
In IE, the installation must be carried out by a competent  
Person and installed in accordance with the current edition of  
I.S. 813 ‘Domestic Gas Installations’, the current Building  
Regulations and reference should be made to the current ETCI  
rules for electrical installation.  
Warning - Check the information on the data plate is compatible with local supply  
All systems must be thoroughly flushed and treated with  
inhibitor (see section 6.2).  
conditions.  
Codes of Practice, most recent version should be used  
In GB the following Codes of Practice apply:  
Standard  
BS 6891  
BS 5546  
Scope  
Gas Installation.  
Installation of hot water supplies for  
domestic purposes.  
BS 5449  
BS 6798  
BS 5440 Part 1  
BS 5440 Part 2  
BS 7074  
Forced circulation hot water systems.  
Installation of gas fired hot water boilers.  
Flues.  
The boiler meets the requirements of Statutory Instrument “ The Boiler (Efficiency)  
Ventilation.  
o
Regulations 1993 N 3083” and is deemed to meet the requirements of Directive  
Expansion vessels and ancillary equipment  
for sealed water systems.  
Treatment of water in domestic hot water  
central heating systems.  
92/42/EEC on the energy efficiency requirements for new hot water boilers fired with  
liquid or gaseous fuels:-  
BS 7593  
In IE the following Codes of Practice apply:  
Type test for purpose of Regulation 5 certified by:  
Notified Body 0051.  
Standard  
I.S. 813  
Scope  
Domestic Gas Installations.  
The following BS standards give valuable additional information;  
BS 5546  
Installation of hot water supplies for  
domestic purposes.  
Product/Production certified by:  
Notified Body 0086.  
BS 5449  
BS 7074  
Forced circulation hot water systems.  
Expansion vessels and ancillary equipment  
for sealed water systems.  
BS 7593  
Treatment of water in domestic hot water  
central heating systems.  
For GB/IE only.  
4
© Baxi Heating UK Ltd 2009  
Safe Manual Handling  
General  
The following advice should be adhered to, from when first handling the boiler to the final stages of installation, and also during maintenance.  
Most injuries as a result of inappropriate handling and lifting are to the back, but all other parts of the body are vulnerable, particularly shoulders, arms and hands.  
Health & Safety is the responsibility of EVERYONE.  
There is no ‘safe’ limit for one man - each person has different capabilities. The boiler should be handled and lifted by TWO PEOPLE.  
Do not handle or lift unless you feel physically able.  
Wear appropriate Personal Protection Equipment e.g. protective gloves, safety footwear etc.  
Preparation  
Co-ordinate movements - know where, and when, you are both going.  
Minimise the number of times needed to move the boiler - plan ahead.  
Always ensure when handling or lifting the route is clear and unobstructed. If possible avoid steps, wet or slippery surfaces, unlit areas etc. and take special care  
on ladders/into lofts.  
Technique  
When handling or lifting always use safe techniques - keep your back straight, bend your knees. Don’t twist - move your feet, avoid bending forwards and  
sideways and keep the load as close to your body as possible.  
Where possible transport the boiler using a sack truck or other suitable trolley.  
Always grip the boiler firmly, and before lifting feel where the weight is concentrated to establish the centre of gravity, repositioning yourself as necessary. See the  
‘Installation’ section of these instructions for recommended lift points.  
Remember  
The circumstances of each installation are different. Always asses the risks associated with handling and lifting according to the individual conditions.  
If at any time when installing the boiler you feel that you may have injured yourself STOP !!  
DO NOT ‘work through’ the pain - you may cause further injury.  
IF IN ANY DOUBT DO NOT HANDLE OR LIFT THE BOILER - OBTAIN ADVICE OR ASSISTANCE BEFORE PROCEEDING !!  
5
© Baxi Heating UK Ltd 2009  
1.0 Introduction  
1.1  
Description  
Case Front Panel  
1. The Potterton Performa 24 Eco HE is a fully automatic  
gas fired wall mounted condensing combination boiler. It  
is room sealed and fan assisted, and will serve central  
heating and mains fed domestic hot water.  
2. The boiler is set to give a maximum output of  
25.2 kW (condensing).  
3. It is designed for use on Natural Gas (G20) and can be  
converted to use Propane.  
4. The boiler is suitable for use only on fully pumped  
sealed heating systems. Priority is given to domestic hot  
water.  
5. The boiler data badge gives details of the model, serial  
number and Gas Council number and is situated on the  
control box. It is visible when the case front panel is  
removed (Fig. 1).  
6. The boiler is intended to be installed in residential /  
commercial / light industrial E.M.C. environments on a  
governed meter supply only.  
Control Box  
7. The boiler must be installed with one of the purpose  
designed flues such as the standard horizontal flue kit,  
part no. 5118489.  
Fig. 1  
Data Badge  
8. All systems must be thoroughly flushed and treated  
with inhibitor (see section 6.2).  
1.2  
Contents of Pack  
The pack contains:-  
Boiler  
Wall Plate (inc. taps)  
Set of Connections  
Template  
Literature Pack  
6
© Baxi Heating UK Ltd 2009  
2.0 General Layout  
1
2.1  
Layout  
20  
1.  
Air Pressure Switch  
19  
2.  
Expansion Vessel  
3.  
Burner Manifold  
4.  
Automatic Air Vent  
5.  
DHW Plate Heat Exchanger  
Circulation Pump  
18  
17  
6.  
7.  
Drain Off Point  
8.  
Safety Pressure Relief Valve  
Optional Integral Timer Position  
Central Heating System Pressure Gauge  
Control PCB  
9.  
2
3
10.  
11.  
12.  
13.  
14.  
15.  
16.  
17.  
18.  
19.  
20.  
21.  
22.  
23.  
24.  
25.  
26.  
16  
15  
Control Box  
3-Way Valve Assembly  
Condensate Trap  
Flame Sensing Electrode  
Spark Electrode  
4
5
13  
6
Burner  
Primary Heat Exchanger  
Fan Assembly  
Secondary Heat Exchanger  
On/Off/Reset Selector Switch  
Burner & Fault Indicator Neon  
Power Neon  
7
8
14  
Flame Failure & Fault Indicator Neon  
Central Heating Temperature Control  
Hot Water Temperature Control  
12  
11  
10  
9
2
Burner On  
Flame Failure  
Power On  
Reset  
1
3
0
4
bar  
22  
25  
26  
9
21  
23  
24  
10  
7
© Baxi Heating UK Ltd 2009  
3.0 Appliance Operation  
1
NOTE: All delay timers mentioned in 3.1 and 3.2 are  
overridden by domestic hot water demand.  
Central Heating Circuit  
27  
7
3.1  
Central Heating Mode (Fig. 2)  
2
1. With a demand for heating, the pump circulates water  
through the primary circuit. At a pre-determined flow  
rate the central heating flow switch operates, initiating  
the ignition sequence.  
3
5
4
26  
6
2. The main burner ignites at low rate, then the gas valve  
controls the gas rate to maintain the heating  
temperature measured by the temperature sensor.  
25  
24  
8
23  
3. When the flow temperature exceeds the setting  
temperature, a 3 minute delay occurs before the burner  
relights automatically (anti-cycling). The pump continues  
to run during this period.  
9
22  
21  
11  
17  
15  
10  
20  
16  
3.2  
Domestic Hot Water Mode (Fig. 3)  
18  
14  
13  
12  
19  
1. Priority is given to the domestic hot water supply. A  
demand at a tap or shower will override any central  
heating requirement.  
Fig. 2  
Key  
2. The flow of water will operate the DHW flow switch  
which requests the 3 way valve to change position. This  
will allow the pump to circulate the primary water  
through the DHW plate heat exchanger.  
1
2
3
4
5
6
7
8
9
Primary Heat Exchanger  
Burner  
Ignition Electrode  
Flame Sensing Electrode  
Gas Valve  
15 Domestic Hot Water Outlet  
16 Heating Flow  
17 Pressure Gauge  
18 Hydraulic Differential Pressure Sensor Microswitch  
19 Automatic By-Pass  
20 Hydraulic Differential Pressure Sensor  
21 Diverter Valve Assembly  
22 Domestic Hot Water Flow Priority Assembly  
23 Domestic Hot Water Flow Priority Microswitch  
24 Safety Thermostat  
25 Central Heating Temperature Sensor  
26 Expansion Vessel  
Pump  
Automatic Air Vent  
Plate Heat Exchanger  
Flow Sensor with Filter  
3. The burner will light automatically and the  
temperature of the domestic hot water is controlled by  
the temperature sensor.  
10 Pressure Relief Valve  
11 Boiler Drain Point  
12 Heating Return  
13 Cold Water Inlet On/Off Valve and Filter  
14 Gas Inlet  
4. When the domestic hot water demand ceases the  
burner will extinguish and the diverter valve will remain  
in the domestic hot water mode, unless there is a  
demand for central heating.  
27 Secondary Heat Exchanger  
1
IMPORTANT: When the selector switch is in the  
‘0’ (Off) position the electrical supply to the boiler  
is isolated. The boiler will not operate and the  
integral timer (if fitted) will require resetting once  
the selector switch is turned to either the DHW  
or CH position.  
Domestic Hot Water Circuit  
27  
2
3
5
4
7
26  
6
25  
24  
8
23  
22  
9
11  
21  
17  
15  
10  
20  
18  
16  
14  
13  
12  
19  
Fig. 3  
8
© Baxi Heating UK Ltd 2009  
4.0 Technical Data  
Appliance Type  
C12  
C32  
C52  
Electrical Protection  
IPX4D  
Central Heating Primary Circuit  
Pressures  
Appliance Category  
Heat Input CH  
CAT II  
2H 3P  
NO Class  
x
3
bar  
3
2.5  
0.5  
1-2  
Safety Discharge  
Max Operating  
Min Operating  
Condensate Drain  
1” BSP  
Max  
24.8  
Min  
Flue Terminal  
Dimensions  
Diameter  
Projection  
100mm  
125mm  
kW  
10.6  
Recommend Operating  
Heat Output CH (Non-Condensing)  
DHW Circuit  
Pressures  
Max Operating  
Min Operating  
bar  
Max  
Min  
Connections  
Gas Supply  
Central Heating Flow  
Central Heating Return  
Cold Water Mains Inlet  
DHW Flow  
copper tails  
22mm  
22mm  
22mm  
15mm  
8
0.2  
kW  
24  
9.8  
-
-
-
-
-
-
Heat Output CH (Condensing)  
Min Operating Pressure  
at 11.1 l/min  
Max  
Min  
0.9  
kW  
25.2  
10.1  
15mm  
15mm  
Pressure Relief Discharge  
Flow Rates  
DHW Flow Rate  
@ 30°CRise  
l/min  
Heat Input DHW  
Max  
Outercase Dimensions  
Casing Height  
Overall Height Inc Flue  
Elbow  
Casing Width  
Casing Depth  
11.5  
9.8  
kW  
24.8  
-
780mm  
DHW Flow Rate  
@ 35°CRise  
Heat Output DHW  
Max  
-
-
-
965mm  
450mm  
345mm  
Min Working  
DHW Flow Rate  
2.5  
kW  
24  
Pump  
Available Head  
Max Gas Rate  
(Natural Gas - G20)  
(After 10 mins)  
2.62  
Clearances  
See graph below  
- (For Central Heating  
Above Casing  
Below Casing  
Front  
Front  
L.H. Side  
R.H. Side  
200 mm Min  
200 mm Min  
3
m /h  
Expansion Vessel  
only. Integral with appliance)  
450 mm Min (For Servicing)  
5 mm Min (In Operation)  
5 mm Min  
5 mm Min (In Operation)  
20mm Min (See Note*)  
Burner Pressure  
(Natural Gas - G20)  
Max Rate  
10.2 0.5  
Min Rate  
0.2  
bar  
0.5  
mbar  
2
Min Pre-charge Pressure  
Inlet Pressure (Natural Gas - G20)  
mbar 20  
litre  
125  
1.0  
*NOTE: The boiler can be operated with a  
clearance of 5mm at the right. This is also  
sufficient for routine maintenance. However a  
clearance of 20mm is required if it is necessary to  
remove the secondary heat exchanger. This  
should be considered when siting the appliance  
and in the event of any subsequent alterations in  
the area of installation  
Max Capacity of  
CH System  
Burner Injector (Natural Gas - G20)  
15 x 1.18mm Diameter  
Primary Water Content  
of Boiler (unpressurised)  
Electrical Supply  
(Appliance must be connected to an  
earthed supply)  
230V~ 50H  
z
Temperatures  
C.H. Flow Temp (adjustable)  
Power Consumption  
External Fuse Rating  
170W  
3A  
35°C to 85°C max ( 5°C)  
Weights  
Packaged Boiler Carton  
Installation Lift Weight  
kg  
50  
43.5  
D.H.W. Flow Temp (adjustable)  
35°C to 65°C max ( 5°C)  
dependent upon flow rate  
Internal Fuse Rating  
Fuse 2A Fast Blow to BS 4265  
Pump - Available Head  
5
4.5  
4
LPG Propane - G31  
Burner Injector 15 x 0.77mm diameter  
3.5  
3
Burner Pressure  
Propane  
Max Rate Min Rate  
mbar  
21.8 0.5 4.4 0.2  
Inlet Pressures  
2.5  
2
37  
mbar  
1.5  
1
0.5  
0
0
200  
400  
600  
800  
1000  
1200  
Flow Rate (l/h)  
9
© Baxi Heating UK Ltd 2009  
5.0 Dimensions and Fixings  
Dimensions  
A 780mm  
E
At Least 1.5°  
G
A
B 345mm  
C 450mm  
D 116mm Ø Min.  
E 185mm  
F 190mm  
G 131mm  
B
360° Orientation  
C
D
Tube Ø 100mm  
F
Tap Rail  
28mm  
Condensate  
Drain  
65 mm  
65 mm  
65 mm  
65 mm  
65 mm  
Heating  
Return  
(22mm)  
Pressure Relief  
Heating  
Flow  
(22mm)  
Domestic Hot  
Water Outlet  
(15mm)  
Gas  
Inlet  
(22mm)  
ColdWater  
Inlet  
(15mm)  
Valve  
(15mm)  
10  
© Baxi Heating UK Ltd 2009  
6.0 System Details  
6.1  
Information  
1. The Potterton Performa 24 Eco HE Condensing Combination  
Boiler is ‘Water Byelaws Scheme - Approved Products’.  
To comply with the Water Byelaws your attention is drawn to the  
following installation requirements and notes (IRN).  
a) IRN 001 -  
See text of entry for installation  
requirements and notes.  
Byelaw 14.  
b) IRN 302 -  
2. Reference to the WRc publications, ‘Water fittings and materials  
directory’ and ‘Water supply byelaws guide’ give full details of  
byelaws and the IRNs.  
6.2  
Central Heating Circuit  
1. The appliance is suitable for fully pumped SEALED SYSTEMS  
ONLY.  
Treatment of Water Circulating Systems  
• All recirculatory water systems will be subject to  
corrosion unless an appropriate water treatment is  
applied. This means that the efficiency of the system will  
deteriorate as corrosion sludge accumulates within the system,  
risking damage to pump and valves, boiler noise and circulation  
problems.  
• When fitting new systems flux will be evident within the system,  
which can lead to damage of system components.  
• All systems must be thoroughly drained and flushed out. Using,  
for example Betz-Dearborn Sentinel X300 or X400 or Fernox  
Superfloc Universal Cleanser. They should be used following the  
flushing agent manufacturer’s instructions.  
• System additives - corrosion inhibitors and flushing  
agents/descalers should comply to BS7593 requirements, e.g. Betz-  
Dearborn Sentinel X100 and Fernox-Copal which should be used  
following the inhibitor manufacturer’s instructions.  
Failure to flush and add inhibitor to the system will invalidate  
the appliance warranty.  
• It is important to check the inhibitor concentration after  
installation, system modification and at every service in accordance  
with the manufacturer’s instructions. (Test kits are available from  
inhibitor stockists.)  
• For information or advice regarding any of the above contact  
Technical Enquiries.  
6.3  
Bypass  
1. The boiler is fitted with an automatic integral bypass.  
6.4  
System Control  
1. The boiler is designed for use in a heating system that  
incorporates external controls, i.e. a minimum of a timer  
device.  
2. Suitable timer kits are available as optional extras.  
3. For optimum operating conditions and maximum economy  
the fitting of a programmable room thermostat is  
recommended.  
11  
© Baxi Heating UK Ltd 2009  
6.0 System Details  
6.5  
System Filling and Pressurising  
1. A filling point connection on the central heating  
return pipework must be provided to facilitate initial  
filling and pressurising and also any subsequent water  
loss replacement/refilling.  
Double  
Check  
Valve  
2. There are connection points on the mains cold water  
inlet and central heating return isolating taps (Fig. 5) to  
which the optional filling loop kit (Part No. 248221) can  
be assembled.  
Stop  
Valve  
Stop  
Valve  
3. The filling method adopted must be in accordance  
with all relevant water supply regulations and use  
approved equipment.  
Temporary  
Hose  
DHW  
Mains  
Inlet  
CH  
Return  
4. Your attention is drawn to,  
for GB: guidance G24.2 and recommendation R24.2 of  
the Water Regulations Guide.  
Fig. 4  
for IE: the current edition of I.S. 813. “Domestic Gas  
Installations”.  
5. The sealed primary circuits may be filled or  
replenished by means of a temporary connection  
between the circuit and a supply pipe provided a  
‘Listed’ double check valve or some other no less  
effective backflow prevention device is permanently  
connected at the inlet to the circuit and the temporary  
connection is removed after use.  
Fig. 5  
6.6  
Expansion Vessel  
(Central Heating only)  
1. The appliance expansion vessel is pre-charged to 0.5  
bar. Therefore, the minimum cold fill pressure is 0.5 bar.  
The vessel is suitable for correct operation for system  
capacities up to 125 litres. For greater system capacities  
an additional expansion vessel must be fitted. For GB  
refer to BS 7074 Pt 1. For IE, the current edition of  
I.S. 813 “Domestic Gas Installations”.  
Filling Loop  
6.7  
Safety Pressure Relief Valve (Fig. 6)  
1. The pressure relief valve is set at 3 bar, therefore all  
pipework, fittings, etc. should be suitable for pressures in  
excess of 3 bar.  
2. The pressure relief discharge pipe should be not less  
than 15mm dia, run continuously downward, and  
discharge outside the building, preferably over a drain. It  
should be routed in such a manner that no hazard  
occurs to occupants or causes damage to wiring or  
electrical components. The end of the pipe should  
terminate facing down and towards the wall.  
Fig. 6  
Pressure Relief Valve  
Discharge Pipe  
3. The discharge must not be above a window,  
entrance or other public access. Consideration must be  
given to the possibility that boiling water/steam could  
discharge from the pipe.  
4. A remote relief valve kit is available to enable the  
boiler to be installed in cellars or similar locations below  
outside ground level (kit no. 5121379).  
12  
© Baxi Heating UK Ltd 2009  
6.0 System Details  
Other Tap  
Outlets  
6.8  
Domestic Hot Water Circuit (Fig. 7)  
1. All DHW circuits, connections, fittings, etc. should be  
fully in accordance with relevant standards and water  
supply regulations.  
Boiler  
Expansion  
Vessel*  
2. Your attention is drawn to:  
for GB: Guidance G17 to G24 and recommendation R17  
to R24 of the Water Regulations Guide.  
for IE: the current edition of I.S. 813. “domestic Gas  
Installations”.  
Check  
Valve*  
Pressure Reducer  
Valve*  
3. The Water Regulations recommendations for England  
and Wales prohibits backflow from appliances into the  
wholesome water supply due to thermal expansion.  
However this type of instantaneous combination boiler,  
with less than 15 litres of stored capacity, does not  
require any backflow prevention device as any thermal  
expansion is accommodated within the appliance.  
It is possible in certain circumstances that other cold  
water demands (e.g. washing machines, flushing of W.C.s)  
may affect the DHW function of the boiler. In these  
instances the fitting of a backflow prevention device and  
expansion vessel is recommended.  
To Hot  
Taps  
Stop Tap  
*See 6.8 for instances when  
these items may be required  
Fig. 7  
4. Also if there is an existing check valve, loose jumpered  
stop cock, water meter or water treatment device  
already fitted to the wholesome water supply connected  
to the boiler domestic hot water (DHW) inlet supply  
then a suitable expansion device may be required.  
5. The boiler’s maximum working mains pressure is 8 bar,  
therefore all pipework, connections, fittings, etc. should  
be suitable for pressures in excess of 8 bar. A pressure  
reducing valve must be fitted for pressures in excess of 8  
bar. The manufacturer of any outlet fittings, such as a  
shower valve, may require a lower maximum pressure.  
The pressure reduction must take account of all fittings  
connected to the DHW system.  
6.9  
Showers  
1. If a shower control is supplied from the appliance it  
should be of the thermostatic or pressure balanced type.  
Thermostatic type shower valves provide the best  
comfort and guard against water at too high a  
temperature. Existing controls may not be suitable - refer  
to the shower valve manufacturer.  
6.10  
Hard Water Areas  
1. If the area of the installation is recognised as a HARD  
WATER AREA then a suitable device should be fitted to  
treat the mains water supply to the boiler. Contact your  
Water Distribution Company for advice on suitable  
devices.  
13  
© Baxi Heating UK Ltd 2009  
7.0 Site Requirements  
20mm/5mm Min  
See * NOTE:  
450mm  
5mm Min  
7.1  
Location  
1. The boiler may be fitted to any suitable wall with the  
flue passing through an outside wall or roof and discharging  
to atmosphere in a position permitting satisfactory removal  
of combustion products and providing an adequate air  
supply. The boiler should be fitted within the building  
unless otherwise protected by a suitable enclosure i.e.  
garage or outhouse. (The boiler may be fitted inside a  
cupboard-see Section 7.3).  
200mm Min  
2. If the boiler is sited in an unheated enclosure then it is  
recommended to leave the ON/OFF Selector Switch in  
the domestic hot water and central heating position to  
give frost protection.  
780mm  
3. If the boiler is fitted in a room containing a bath or  
shower reference must be made to the relevant  
requirements.  
In GB this is the current I.E.E. Wiring Regulations and  
Building Regulations.  
In IE reference should be made to the current edition of  
I.S. 813 “Domestic Gas Installations” and the current ETCI  
rules.  
2
Burner On  
Flame Failure  
Power On  
Reset  
1
3
0
4
bar  
4. If the boiler is to be fitted into a building of timber frame  
construction then reference must be made to the current  
edition of Institute of Gas Engineers Publication IGE/UP/7  
(Gas Installations in Timber Framed Housing).  
200mm Min  
Fig. 8  
7.2  
Clearances (Figs. 8 & 9)  
1. A flat vertical area is required for the installation of the  
boiler.  
2. These dimensions include the necessary clearances  
around the boiler for case removal, access during routine  
maintenance and air movement. Additional clearances may  
be required for the passage of pipes around local  
obstructions such as joists running parallel to the front face  
of the boiler.  
* NOTE: The boiler can be operated with a clearance  
of 5mm at the right. This is also sufficient for routine  
maintenance. However a clearance of 20mm is  
required if it is necessary to remove the secondary  
heat exchanger. This should be considered when  
siting the appliance and in the event of any  
450mm Min  
For Servicing  
Purposes  
subsequent alteration in the area of installation.  
5mm Min  
In Operation  
Fig. 9  
14  
© Baxi Heating UK Ltd 2009  
7.0 Site Requirements  
7.3  
Ventilation of Compartments  
1. Where the appliance is installed in a cupboard or  
compartment, no air vents are required.  
2. BS 5440: Part 2 Clause 4.2 refers to room sealed  
appliances installed in compartments. The appliance will  
run sufficiently cool without ventilation.  
7.4  
Gas Supply  
1. The gas installation should be in accordance with the  
relevant standards. In GB this is BS 6891. In IE this is the  
current edition of I.S. 813 “Domestic Gas Installations”.  
2. The connection to the appliance is a 22mm copper  
tail located at the rear of the gas service cock (Fig. 10).  
3. Ensure that the pipework from the meter to the  
appliance is of adequate size. Do not use pipes of a  
smaller diameter than the boiler gas connection  
(22mm).  
7.5  
Electrical Supply  
1. External wiring must be correctly earthed, polarised  
and in accordance with relevant regulations/rules. In GB  
this is the current I.E.e. Wiring Regulations. In IE  
reference should be made to the current edition of  
ETCI rules.  
2. The mains supply is 230V ~ 50H fused at 3A.  
z
NOTE: The method of connection to the  
electricity supply must facilitate complete electrical  
isolation of the appliance.  
Connection may be via a fused double-pole  
isolator with a contact separation of at least 3mm  
in all poles and servicing the boiler and system  
controls only.  
Fig. 10  
Gas Service Cock  
15  
© Baxi Heating UK Ltd 2009  
7.0 Site Requirements  
Termination to an internal soil and vent pipe  
Boiler  
7.6  
Condensate Drain  
FAILURE TO INSTALL THE CONDENSATE  
DISCHARGE PIPEWORK CORRECTLY WILL AFFECT  
THE RELIABLE OPERATION OF THE BOILER  
The condensate discharge pipe MUST NOT RISE at any  
point along its length. There MUST be a fall of AT LEAST  
2.5° (50mm per metre) along the entire run.  
1. The condensate outlet terminates in a 1” BSP nut and seal  
3
for the connection of 21.5mm ( /4in) plastic overflow pipe  
450mm min  
which should generally discharge internally into the household  
drainage system. If this is not possible, discharge into an  
outside drain is acceptable.  
2. Ensure the discharge of condensate complies with any  
national or local regulations in force.  
External termination via internal  
discharge branch  
e.g sink waste - downstream  
Boiler  
BS 6798:2000 & Part H1 of the Building Regulations give  
further guidance.  
3. The discharge pipe should be run in a proprietary drain pipe  
material e.g. PVC, PVC-U, ABS, PVC-C or PP.  
Pipe must terminate  
above water level but  
below surrounding  
surface  
Sink  
4. Metal pipework is NOT suitable for use in condensate  
discharge systems.  
5. The pipe should be a minimum of 21.5mm diameter and  
must be supported using suitably spaced clips to prevent  
sagging.  
6. It is advisable to keep the condensate pipe internal.  
7. External runs greater than 3 metres or runs in cold areas  
External termination to a drain or gully  
should use 32mm waste pipe.  
Boiler  
8. If the boiler is fitted in an unheated location the entire  
condensate discharge pipe should be treated as an external  
run.  
Pipe must terminate above  
water level but below  
surrounding surface  
9. In all cases discharge pipe must be installed to aid disposal  
of the condensate. To reduce the risk of condensate being  
trapped, as few bends and fittings as possible should be used.  
10. When discharging condensate into a soil stack or waste  
pipe the effects of existing plumbing must be considered. If soil  
pipes or waste pipes are subjected to internal pressure  
fluctuations when WC's are flushed or sinks emptied then  
back-pressure may force water out of the boiler trap and  
cause appliance lockout.  
External termination to a purpose made soak-away  
Examples are shown of the following methods of termination:-  
i) to an internal soil & vent pipe  
Boiler  
ii) via an internal discharge branch (e.g. sink waste)  
iii) to a drain or gully  
500mm min  
iv) to a purpose made soakaway  
Holes in the soak-away must  
face away from the building  
16  
© Baxi Heating UK Ltd 2009  
Terminal Position with Minimum Distance (Fig. 11)  
(mm)  
7.0 Site Requirements  
a
a
A
Directly below an opening, air brick, opening  
windows, etc.  
Above an opening, air brick, opening window etc.  
Horizontally to an opening, air brick, opening window etc.  
Below gutters, soil pipes or drain pipes.  
Below eaves.  
Below balconies or car port roof.  
From a vertical drain pipe or soil pipe.  
From an internal or external corner.  
300  
300  
300  
25  
25  
25  
a
B
7.7  
Flue  
C
D
E
F
NOTE: Due to the nature of the boiler a plume of water  
vapour will be discharged from the flue. This should be  
taken into account when siting the flue terminal.  
G
H
I
J
K
25  
25  
Above ground, roof or balcony level.  
300  
600  
1200  
600  
1. The following guidelines indicate the general requirements  
for siting balanced flue terminals. For GB recommendations  
are given in BS 5440 Pt 1. For IE recommendations are given  
in the current edition of I.S. 813 “Domestic Gas  
Installations”.  
From a surface or boundary line facing a terminal.  
From a terminal facing a terminal (Horizontal flue).  
From a terminal facing a terminal (Vertical flue).  
From an opening in carport (e.g. door, window)  
into the dwelling.  
Vertically from a terminal on the same wall.  
Horizontally from a terminal on the same wall.  
From adjacent wall to flue (vertical only).  
From an adjacent opening window (vertical only).  
Adjacent to windows or openings on pitched and flat roofs  
Below windows or openings on pitched roofs  
L
1200  
1500  
300  
300  
1000  
600  
M
N
R
S
T
2. If the terminal discharges onto a pathway or passageway,  
check that combustion products will not cause a nuisance  
and that the terminal will not obstruct the passageway.  
U
2000  
3. If a terminal is less than 2 metres above a balcony, above  
ground or above a flat roof to which people have access,  
then a suitable terminal guard must be provided.  
a
In addition, the terminal should be no nearer than 150 mm to an  
opening in the building fabric formed for the purpose of accommodating  
a built-in element such as a window frame. See BS 5440 Pt. 1.  
IMPORTANT:  
• Only ONE 25mm clearance is allowed per installation.  
• Under car ports we recommend the use of the plume  
displacement kit.  
• The terminal position must ensure the safe and  
nuisance - free dispersal of combustion products.  
NOTE: The distance from a fanned draught appliance terminal  
installed parallel to a boundary may not be less than 300mm in  
accordance with the diagram below  
300 min  
Terminal  
Assembly  
Plume  
Displacement Kit  
IMPORTANT: If fitting a Plume  
Displacement Flue Kit, the air inlet  
must be a minimum of 100mm from  
any opening windows or doors (see  
Section 9.0).  
TopView Rear Flue  
Fig. 12  
Property Boundary Line  
T
J,K  
Air Inlet  
U
Opening Window  
or Door  
100mm  
MIN.  
Fig. 12a  
N
R
I
D
E
A
M
I
C
I
I
S
F
B
J,K  
F
L
A
A
G
H
H
I
Likely flue positions requiring  
a flue terminal guard  
Fig. 11  
17  
© Baxi Heating UK Ltd 2009  
8.0 Flue Options  
8.1  
Horizontal Flue Systems  
1. The standard flue is suitable only for horizontal  
termination applications.  
2. All fittings should be fully engaged. The approximate  
engagement is 40mm. Apply soap solution to the seal on  
each fitting to aid assembly.  
Y
X
3. Maximum permissible equivalent flue lengths are:-  
Horizontal Concentric 4 metres  
4. Any additional “in line” bends in the flue system must be  
taken into consideration.  
Their equivalent lengths are:-  
Concentric Pipes:  
Horizontal  
Flues  
135° bend  
93° bend  
0.5 metres  
1.0 metres  
Twin Flue Pipe  
135° bend  
91.5° bend  
0.25 metres  
0.50 metres  
The elbow supplied with the standard horizontal telescopic  
flue kit is not included in any equivalent length calculations  
Plume Displacement Kit 60 /100 Ø  
1M Extensions, 45° & 93° bends are  
also available - see Section 9.0  
NOTE: Flue length is measured from point X to Y as  
shown.  
IMPORTANT: All flue systems must be securely  
supported at least once every metre. Suitable pipe  
supports are available as accessories.  
NOTE: Horizontal flue pipes should always be installed with a 1.5° fall from the  
terminal to allow condensate to run back to the boiler.  
This bend is equivalent to  
1 metre  
C
A
Y
B
This bend is equivalent to  
1 metre  
X
Total equivalent length (up to 3m) =  
A+B+C+2x90°Bends  
18  
© Baxi Heating UK Ltd 2009  
8.0 Flue Options  
Vertical  
Flues  
8.2  
Twin & Vertical Flue Systems  
(Twin Pipe)  
1. Maximum permissible equivalent flue lengths are:-  
Vertical Concentric  
Vertical Twin Pipe  
4m  
12m*  
Y
* Both the air and flue duct can be up to 12 metres  
long each.  
X
2. Any additional “in line” bends in the flue system must  
be taken into consideration. Their equivalent lengths  
are:-  
Concentric Pipes:  
45° bend  
93° bend  
0.5 metres  
1.0 metres  
Twin Flue Pipe  
Vertical  
Flues  
45° bend  
0.25 metres  
0.50 metres  
91.5° bend  
The elbow supplied with the standard horizontal flue is  
not included in any equivalent length calculations  
Y
NOTE: Flue length is measured from point X to Y  
as shown.  
IMPORTANT: All flue systems must be securely  
supported at least once every metre. Suitable pipe  
supports are available as accessories.  
X
Total Equivalent Length =  
A+B+C+1x90°Bend  
Roof  
Terminal  
All vertical and angled runs must be included,  
measured from the boiler adaptor (point X) to the  
joint with the flue terminal (point Y). One 91.5°  
bend or two 135° bends can be included without  
reduction of the flue length.  
660mm  
The total equivalent  
length for this example  
is = 6.5 metres.  
If further elbows are required the flue length must  
be reduced by the following amounts:-  
Y
1 metre for each 91.5° bend  
0.5 metre for each 135° bend  
C
AIR DUCT  
N of  
fittings/pipes  
o
Equivalent  
Length Value  
Sub total  
B
1m extension  
45°bend  
5
2
2
5.0m  
0.5m  
1.0m  
1m  
0.25m  
0.5m  
91.5°bend  
This bend is equivalent to  
1 metre  
Equivalent Length Air Duct = 6.5m  
A
X
FLUE DUCT  
N of  
fittings/pipes  
o
Equivalent  
Sub total  
Length Value  
1m  
1m extension  
45°bend  
5
2
2
5.0m  
0.5m  
1.0m  
0.25m  
0.5m  
91.5°bend  
Equivalent Length Flue Duct = 6.5m  
19  
© Baxi Heating UK Ltd 2009  
8.0 Flue Options  
8.3  
Flue Accessories  
Key Accessory  
FLUE GROUP A  
Concentric Flue System 100mm diameter  
Size  
Code No  
A1  
A
B
Horizontal Flue Terminal  
Horizontal Flue Terminal (incl elbow)  
Flue Extension  
5111073  
5118489  
1000mm 5111074  
A1  
A
C
D
U
R
Flue Bend  
93°  
135°  
5111075  
5111085  
Flue Bend (pair)  
Pipe Support (painted)  
Vertical Flue Adaptor  
Wall Liner  
100mmØ 5111080  
5111070  
P
5111067  
S
Flue Terminal Deflector  
5111068  
FLUE GROUP N  
Twin Flue System 80mm diameter  
E
P
B
E
F
Flue Extension (pair)  
Flue Bend (pair)  
1000mm 5111087  
90°  
135°  
5111072  
5111086  
5111079  
5111084  
5111081  
K, K1  
G
J
H
W
Flue Bend (2 pair)  
Vertical Flue Boiler Adaptor Kit  
Vertical Flue Adaptor  
Pipe Support (pair)  
80mm  
FLUE GROUP A, N, G  
Vertical Flue Kits  
K
K1  
L
M
N
Vertical Flue Terminal (use with 5111070)  
Vertical Flue Terminal  
5111078  
5118576  
5122151  
246143  
246144  
R
D
C
Pitched Roof Flashing  
Roof Cover Plate  
Flat Roof Flashing  
25°/50°  
G
F
M
H
U,W  
L
N
S
J
20  
© Baxi Heating UK Ltd 2009  
8.0 Flue Options  
For Twin Flue Systems fit the adaptors as follows:-  
8.4  
Flue Duct Adaptor  
Flue Duct Adaptor  
Boiler Adaptor  
1. Engage the flue duct adaptor on the boiler adaptor,  
making sure that it is pushed down as far as possible.  
Blanking Plate  
8.5  
Air duct adaptor  
1. Undo the screws securing the blanking plate to the boiler  
top panel. Discard the plate.  
2. There are three restrictor plates supplied in the kit. One  
marked ‘23’ and one marked ‘27’, these can be discarded  
The third restrictor MUST be positioned as shown in the  
diagram below.  
3. Take one of the gaskets supplied in the kit and place on  
the boiler top panel.  
4. Align the restrictor as shown. Position the second gasket  
over the restrictor.  
5. Using the screws previously removed secure the inlet  
adaptor to the top panel.  
6. Continue to fit the twin flue system.  
Position of Restrictor  
Air Duct Adaptor  
Gasket  
Restrictor  
Gasket  
21  
© Baxi Heating UK Ltd 2009  
8.0 Flue Options  
8.6  
For Roof Terminals  
1. In the case of a pitched roof 25 - 50 degrees, position the lead  
tile to replace/flash over existing roof tiling. Make an aperture in  
the roof suitable for the lower tube of the roof terminal and  
ensure the integrity of the roof cover is maintained. The  
Approx  
1425mm  
adjustable plastic collar can either be positioned on the lead tile  
or the lower tube of the roof terminal prior to the final  
positioning of the vertical flue through the tile. Check the collar is  
correctly located to suit required roof pitch (either 25° to 38° or  
37° to 50°). From inside the roof adjust the flue to a vertical  
position and secure to the roof structure with the clamp supplied.  
2. For flat roof installations the aluminium flashing must be  
incorporated into the roof covering and the appropriate aperture  
made in the roof decking. The vertical flue is lowered onto the  
flashing making sure the collar of the flue locates securely with the  
flashing. (A mastic seal may be necessary). From inside the roof,  
adjust the flue to a vertical position and secure to the roof  
structure with the clamp supplied.  
Cut the same  
amount off the  
Air Duct &  
Air Duct  
Flue Duct  
Flue Duct  
Push Fit Adaptor  
8.7  
Flue Dimensions  
1. The standard horizontal flue kit allows for flue lengths between  
100mm and 685mm from elbow to terminal (Fig. 13).  
The maximum permissible equivalent flue length is: 4 metres  
NOTE: Each additional 45° of flue bend will account for an  
equivalent flue length of 0.5m.  
eg. 45° = 0.5m,  
90° = 2 x 45° = 1m etc.  
Flue Deflector  
8.8  
Flue Trim  
1. The rubber flue trim supplied may be fitted to either the  
outside wall or on the inner wall of installation.  
Fig. 13  
8.9  
Terminal Guard (Fig. 14)  
1. When codes of practice dictate the use of terminal guards, they  
can be obtained from most Plumbers’ and Builders’ Merchants.  
Fig. 13a  
2. There must be a clearance of at least 50mm between any part  
of the terminal and the guard.  
3. When ordering a terminal guard, quote the appliance name and  
model number.  
4. The flue terminal guard should be positioned centrally over the  
terminal and fixed as illustrated.  
8.10  
Flue Deflector (Fig. 13a)  
1. If required a flue deflector is available from your Potterton  
stockist.  
Fig. 14  
2. Push the flue deflector over the terminal end and rotate to the  
optimum angle for deflecting plume. Secure the deflector to the  
terminal with screws provided.  
22  
© Baxi Heating UK Ltd 2009  
93° Elbow/Plume  
Outlet Assembly  
9.0 Plume Displacement  
60Ø Support  
Bracket  
9.1  
Plume Displacement Kit (Fig. 14b)  
O Ring  
Kit No 5118638  
Content of kit  
0.9 metres  
1
1
1
2
1
1
3
1
1
0.9m 60/100 Concentric Flue  
1m 60 Dia Exhaust Flue Pipe  
Adaptor  
60Ø Exhaust  
Flue Pipe  
60 Dia Support Brackets  
93° Elbow/Plume Outlet Assembly  
Flexible Flue Trim  
60Ø Support  
Bracket  
“O” Rings  
‘Jubilee Clip  
O Ring  
Adaptor  
O Ring  
Fig. 14a  
Boiler Elbow  
Flexible Flue  
Trim  
1. This kit is recommended for installations where the  
condensate plume emitted from the flue may cause a nuisance  
or affect the surroundings.  
‘Jubilee’ Clip  
2. The terminal must be positioned outside the building with  
the air inlet facing downward and outlet connection upwards.  
Elbow  
3. The plume outlet must always be at least 45° to the wall,  
with the ‘peak’ uppermost to prevent rain entry (Figs. 15 &  
16), and be at least 2 metres above ground level. It must be  
secured as shown in Fig. 12a. The plume outlet must also be  
at least 500mm from the air inlet in any direction (Fig. 16).  
60/100Ø  
Concentric Flue  
Fig. 14b  
Outlet must be at  
least 45° from  
wall face  
NOTE: The outlet must be positioned so that any  
condensate plume is directed away from adjacent surfaces.  
There must be a constant fall along the entire length of the  
flue system from the outlet back to the boiler.  
45°  
‘Peak’ Uppermost  
45°  
4. It is possible to reduce or increase (with the addition of  
extensions) the length of either or both the 60/100 concentric  
and 60Ø exhaust.  
5. Standard concentric flue extension kits may be added  
between the boiler elbow and the terminal assembly.  
6. The minimum length of the concentric flue is 100mm when  
measured from the edge of the flue elbow.  
500mm Min.  
IMPORTANT: The maximum equivalent length of  
concentric flue is:- 2.5 metres  
Additional bends may be fitted in the concentric flue, but  
the equivalent length must be reduced by 1 metre (93°  
bend) or 0.5 metres (45° bend).  
Fig. 15  
Air Inlet at Bottom  
7. 60Ø 1 metre extensions (including support bracket), and  
additional 93° & 45° elbows are available. Any additional 93°  
& 45° elbows must be accounted for when calculating flue  
lengths.  
Fig. 16  
NOTE: Permitted positions of the plume outlet relative to  
doors, windows etc. are the same as for conventional  
concentric flues as detailed in the main Installation &  
Servicing Instructions and BS5440 Pt. 1. It is NOT  
necessary to fit a terminal guard over the air inlet or the  
plume outlet.  
23  
© Baxi Heating UK Ltd 2009  
9.0 Plume Displacement  
3
3
9.2  
Determining Permissible Lengths  
2
2
In the graph the solid line diagonal represents the  
relationship between the concentric flue assembly (and any  
extensions) and the 60Ø exhaust (and any extensions or  
additional bends).  
1
0
1
0
Example 1 - Not Permissible  
If, for instance, a concentric length of 2 metres was required  
and the 60Ø exhaust needed to be 1.5 metres the graph  
shows that this combination would NOT be permissible as  
the intersection point would be above the solid diagonal line.  
3
3
1
2
1
2
0
0
Concentric 60/100 Flue (metres)Y  
Concentric 60/100 Flue (metres)Y  
Example 1  
Example 2  
Flue Lengths - Not Permissible  
Flue Lengths - OK  
3
Example 2 - Flue Lengths OK  
Where both lengths have been determined they can be  
applied to the graph to check that the installation is  
permissible. For example, if it was known that 1 metre of  
concentric flue and 1.5 metres of 60Ø exhaust were  
required, the values could be applied to the graph as shown  
in Example 2.. As the point of intersection of the dotted lines  
is below the solid diagonal line, the combination of lengths is  
shown to be acceptable.  
2
1
Example 3 - Flue Lengths OK  
In the example shown, assume that the concentric part of  
the flue needs to be 1 metres long. Find the position of ‘1’ on  
the horizontal axis of the graph and then project upwards to  
the solid diagonal line. This is represented by the vertical  
thick dotted line. Where this dotted line intersects with the  
solid diagonal line on the graph, project across to the vertical  
axis. As can be seen this corresponds with 2 metres.  
Therefore, the total equivalent length of the 60Ø exhaust  
can be up to 2 metres. Any bend equivalencies must be  
accounted for i.e. 93° bends are equal to 1 metre, each 45°  
bend to 0.5 metres.  
0
3
1
2
0
Concentric 60/100 Flue (metres)Y  
Example 3  
Flue Lengths - OK  
60Ø Exhaust  
X
Support  
Bracket  
Y
Flue Length - Worked Example  
Potterton Performa 24 Eco HE  
93° Elbow  
In Fig. 18 opposite an additional 93° bend has been included  
in the 60Ø exhaust. with 2 x 1metre extensions which have  
been cut to 0.25metres and fitted. The waste is discarded.  
Extension  
Concentric 60/100 Flue  
Concentric Flue  
To calculate total length:-  
Fig. 17  
2 x 0.25 metre Lengths =  
1 x 93° Elbow =  
0.5 metres  
1 metre  
Total 60Ø Exhaust =  
1.5 metres  
After consulting the table in Example 3 it can be determined  
that the concentric flue could be up to approximately 0.5  
metres long.  
Additional Accessories  
A - 93° Elbow  
B - 45° Elbow (Pair)  
5117381  
5117382  
Fig. 18  
C - 1 metre 60Ø Extension 5117380  
24  
© Baxi Heating UK Ltd 2009  
9.0 Plume Displacement  
9.3  
General Fitting Notes  
1. Cut a hole in the external wall which the concentric flue  
assembly will pass through. The hole should allow the flue  
to fall back to the boiler at an angle of 1.5° to 3°.  
2. When completed the terminal must be at least 2 metres  
above ground level (Fig. 19).  
Min. 2 metres  
3. Measure and cut to size the concentric assembly and any  
extensions that are being used.  
4. Insert the concentric assembly through the hole from  
outside the building.  
5. If required, the flexible flue trim should be fitted prior to  
this as it cannot be fitted after. Use the large ‘Jubilee’ clip to  
secure the trim to the flue (See Fig. 20, trim shown  
dotted), with the screw part of the clip at the bottom.  
Fig. 19  
6. Connect any extensions or elbows that are being used  
to the concentric assembly. Engage the extension, elbow  
or concentric assembly in the boiler flue elbow. Fit the  
boiler flue elbow to the boiler adaptor.  
Flue Trim  
7. Ensure that the concentric assembly and any extensions  
fall back to the boiler at an angle of 3° and that the  
external air inlet is to the bottom.  
8. Use suitable brackets to support the concentric  
assembly and any extensions, and make good inside and  
outside.  
Spigot  
9. The 60Ø exhaust can now be fitted. Slide the adaptor  
over the plain end of the 60Ø exhaust (Fig. 22) and engage  
the exhaust in the terminal. Slide the adaptor down over  
the spigot. Mark and drill the adaptor, using a 2mm bit, as  
shown in Fig. 21. Secure the adaptor to the spigot using  
one of the screws supplied.  
Position of ‘Jubilee’ Clip  
screw  
Fig. 20  
50mm  
Adaptor  
10. If it is necessary to shorten the 60Ø exhaust or any of  
the extensions, the excess material must be cut from the  
plain end of the pipe.  
Fig. 22  
11. Determine the position of the 60Ø exhaust and mark  
on the wall a suitable position for the support bracket. If  
extensions are being used, a support bracket is supplied in  
each kit.  
30mm  
Fig. 21  
12. Drill the wall, and fit the bracket(s) using the plug and  
screw provided.  
30mm  
13. Mark and drill the 60Ø exhaust, using a 2mm bit, as  
shown in Fig. 23. Complete the installation of the 60Ø  
exhaust, securing in the brackets.  
Fig. 23  
14. Fit the 93° elbow/plume outlet and secure with the  
two remaining screws supplied. Ensure the plume outlet is  
at least 45° to the wall and that the ‘peak’ is uppermost  
(Fig. 24).  
Fig. 24  
25  
© Baxi Heating UK Ltd 2009  
9.0 Plume Displacement  
Plume Outlet  
Elbow  
9.3  
General Fitting Notes (cont.)  
15. For aesthetic purposes it is permissible to route the  
60Ø exhaust in an enclosed box, but the air inlet and  
plume outlet MUST remain in free air.  
16. It is also possible to separate the plume outlet from the  
93° elbow to allow the flue to be installed as shown in  
Fig. 25.  
17. To do this, first slacken the two screws retaining the  
plume outlet to the elbow, and remove the outlet (Fig. 26).  
The elbow can now be used to connect the vertical to  
horizontal 60Ø exhaust (Fig. 25). Retighten the screws in  
the elbow.  
Fig. 25  
18. The outlet can now be fitted into the female end of an  
60Ø extension piece. It must be secured using two of the  
screws supplied in the bag with the ‘Jubilee’ clip.  
19. Mark the female end of the extension at 30mm as  
shown in two positions, directly opposite each other  
(Fig. 27).  
Fig. 26  
30mm  
20. Using a suitable bit (e.g. 2mm), drill through the  
extension and outlet. Secure using two of the screws  
supplied.  
21. The remaining screw must be used to secure the  
adaptor to the concentric terminal.  
Fig. 27  
22. When the plume outlet is positioned under a balcony  
or other projection (Fig. 28) it must protrude at least  
200mm (it is not necessary to extend it further than this).  
200mm Min.  
23. When under balconies or projections it is permissible to  
rotate the concentric flue length up to 70°, clockwise or  
anti-clockwise (Fig. 29), if there is insufficient space to  
connect vertically.  
24.This will allow the connection of the exhaust to the  
outlet spigot.  
25. All other minimum & maximum dimensions must be  
adhered to, and the air inlet positioned such that it will not  
be subject to rain entry.  
Fig. 28  
70°  
Concentric Flue Length  
(shown end-on)  
Outlet Spigot  
Fig. 29  
26  
© Baxi Heating UK Ltd 2009  
10.0 Installation  
10.1  
Initial Preparation  
The gas supply, gas type and pressure must be  
checked for suitability before connection (see Section  
7.4).  
1. After considering the site requirements  
(see Section 7.0) position the fixing template on the  
wall ensuring it is level both horizontally and vertically.  
2. Mark the position of the two most suitable fixing slots  
for the wall plate and boiler lower fixing holes. It is  
preferable to use the horizontal fixing slots.  
190mm  
3. Mark the position of the centre of the flue hole (rear  
exit). For side flue exit, mark as shown (Fig. 30).  
4. Note the shaded area on the template. Pipework  
may be routed upwards behind the boiler, providing it  
does not conflict with the shaded area.  
5. If required, mark the position of the gas and water  
pipes. Remove the template.  
For Side Flue Exit  
6. Cut the hole for the flue (minimum diameter  
116mm).  
Fig. 30  
7. Drill the wall as previously marked to accept the wall  
plugs supplied. Secure the wall plate using the fixing  
screws.  
8. Using a spirit level ensure that the plate is level  
before finally tightening the screws.  
9. Connect the gas and water pipes to the valves on the  
wall plate using the copper tails supplied. Ensure that  
the sealing washers are fitted between the connections.  
10.2  
Flushing  
1. Connect a tube to the central heating flow or return  
pipe (Fig. 31).  
2. Flush thoroughly (see System Details, Section 6.2).  
10.3  
Preparing The Boiler  
Flushing Tube  
1. Remove all packaging.  
2. Stand the boiler on its base by using the rear lower  
edge as a pivot.  
NOTE: A small amount of water may drain from  
the boiler in the upright position.  
Fig. 31  
Central Heating Return  
27  
© Baxi Heating UK Ltd 2009  
10.0 Installation  
Wall Plate  
10.4  
Fitting The Boiler  
1. Remove the sealing caps from the boiler connections.  
NOTE: A small amount of water may drain from the  
boiler once the caps are removed.  
2. Lift the boiler as indicated by the shaded areas. The  
boiler should be lifted by TWO PEOPLE. Engage the slots  
at the top rear of the boiler on the wall plate (Fig. 35)  
(see Safe Manual Handling page 5).  
3. Insert the sealing washers between the valves and  
pipes on the wall plate and the boiler connections. The  
rubber washers must be used on the gas connection.  
Fig. 32  
4. Tighten all the connections.  
10.5  
Fitting the Safety Pressure Relief  
Discharge Pipe (Fig. 33)  
Suggested Lifting Points  
shown as shaded area  
1. Remove the discharge pipe from the kit.  
2. Determine the routing of the discharge pipe in the  
vicinity of the boiler. Make up as much of the pipework as  
is practical, including the discharge pipe supplied.  
3. The pipework must be at least 15mm diameter and  
run continuously downwards to a discharge point outside  
the building. See section 6.7 for further details.  
4. Utilising one of the sealing washers, connect the  
discharge pipe to the adaptor and tighten the nut.  
5. Complete the discharge pipework and route it to the  
outside discharge point.  
IMPORTANT: Make all soldered joints before  
connecting to the safety pressure relief valve.  
Pressure Relief Valve  
Fig. 33  
Discharge Pipe  
28  
© Baxi Heating UK Ltd 2009  
10.0 Installation  
10.6  
Condensate Drain (see section 7.6)  
1. Connect the condensate drain using the 1” BSP nut  
and seal supplied.  
Ensure the discharge of condensate complies with  
any national or local regulations in force (see British  
Gas “Guidance Notes for the Installation of  
Domestic Gas Condensing Boilers”.  
Fig. 34  
2. The condensate outlet terminates in a 1” BSP nut and  
seal for the connection of 21.5mm ( /4in) plastic  
3
overflow pipe which should generally discharge internally  
into the household drainage system. If this is not  
possible, discharge into an outside drain is acceptable.  
10.7  
Fitting The Flue  
HORIZONTAL FLUE  
Wall Thickness  
1. The standard flue is suitable for lengths between  
100mm minimum and 685mm maximum, as measured  
from the edge of the flue elbow outlet to the joint  
between the terminal and air duct (Fig. 34).  
Flue Elbow  
(X)  
2. Locate the flue elbow on the adaptor at the top of  
the boiler. Set the elbow to the required orientation  
(Fig. 35).  
Adaptor  
NOTE: The flue elbow is angled at 91.5 degrees to  
ensure a fall back to the boiler.  
3. Measure the distance from the outside wall face to  
the elbow. This dimension will be known as ‘X’ (Fig. 36).  
4. To dimension ‘X’ add 50mm. This dimension to be  
known as ‘Y’.  
IMPORTANT: Check all dimensions before cutting.  
Fig. 35  
(X)  
Wall Thickness  
Fig. 36  
29  
© Baxi Heating UK Ltd 2009  
10.0 Installation  
10.7  
Fitting the Flue (Cont)  
Waste  
Y
5. Mark dimension ‘Y’ on the flue as shown (Fig. 37).  
Carefully cut the waste material from the flue, ensuring  
that the ducts are square and free from burrs.  
6. The inner flue duct support bracket may be in the  
waste portion of the flue. In this case retrieve the  
bracket before discarding the waste.  
Flue  
Fig. 37  
7. Take the inner flue support bracket (if not already  
fitted) and engage it over the flue duct. This will  
centralise the flue and air ducts, and ease assembly  
(Fig. 38).  
8. Insert the flue through the hole in the wall. Fit the  
elbow to the boiler adaptor, ensuring that it is pushed  
fully in.  
Inner Flue Support Bracket  
9. Draw the flue back through the wall and engage it in  
the elbow. It may be necessary to use soap solution or  
similar to ease assembly of the elbow adaptor and flue  
(Fig. 39).  
10. Make good between the wall and air duct outside  
the building.  
Fig. 38  
11. Fit the flue trim if required, and if necessary fit a  
terminal guard (see Section 8.8 & 8.9).  
VERTICAL FLUE  
1. Only a flue approved with the Potterton Performa 24  
Eco HE can be used.  
Flue Elbow  
Fig. 39  
30  
© Baxi Heating UK Ltd 2009  
10.0 Installation  
10.8  
Making The Electrical Connections  
To connect the mains input cable proceed as follows:-  
1. Slacken the facia securing screws and lift the  
outercase panel so that its locating tabs are clear of the  
facia. Remove the panel.  
2. Completely undo the screws securing the facia panel  
and hinge it down (Fig. 40).  
Control Box Cover  
Fig. 41  
3. Remove the control box cover securing screws.  
Disengage the barbs on the control box from the  
cover. Remove the cover (Fig. 41).  
4. Slacken the cable clamp on the LH side of the boiler  
chassis (Fig. 42). Insert the cable through the clamp and  
route it to the terminal block.  
5. Slacken the screws in the terminal block, connect  
the input cable, and tighten the screws.  
Fig. 40  
Fig. 42  
Facia Panel  
Cable Clamp  
6. If an external control is to be connected it can be  
done at this point. Run the input cable from the  
external control through the second cable clamp on  
the boiler chassis. Refer to the instructions supplied  
with the control.  
Frost Thermostat  
br  
b
L
Fuse  
N
L
N
External Clock  
g/y  
bk  
bk  
7. To connect external control(s) remove the link  
between terminals 1 & 2. The 230V supply at terminal  
1 must be connected to the external control. The  
switched output from the external control must be  
connected to terminal 2 (Fig. 43).  
Fused supply 3A  
230V ~ 50Hz  
Always fit fast  
blow 2A fuse  
1
230 V  
SL  
N
2
br  
b
Live (brown)  
Neutral (blue)  
g/y  
bk  
bk  
Earth (green/yellow)  
Room Thermostat  
NOTE: If the room thermostat being used  
incorporates an anticipator it MUST be wired as  
shown in Fig. 43  
1
2
230V  
IMPORTANT: If an integral timer is fitted to the boiler  
an external frost thermostat wired as shown will not  
operate correctly. Only external timers may be used in  
such installations, as in the diagram.  
IMPORTANT: The external control MUST be  
suitable for 230V switching.  
Terminal Block  
Fig. 43  
8. Ensure that both mains input and, where fitted,  
external control input cables have sufficient slack to  
allow the control box to drop down. Tighten the cable  
clamp(s) on the boiler chassis.  
Functional Flow Diagram  
Pump  
Fan  
L
External  
Controls  
230 V  
br  
br  
b
b
N
bk  
b
br  
br  
Pressure Switch  
9. If the optional integral timer is to be used it should  
be fitted at this point. Refer to the instructions supplied  
with the timer. NOTE: An external frost thermostat  
cannot be used with the integral timer.  
br  
b
Selector /  
Reset Switch  
N
bk  
b
b
Flue Thermostat  
Safety Overheat Thermostat  
r
Central Heating  
NTC Sensor  
b
r
r
g
DHW  
NTC Sensor  
bk  
g
10.9  
Preliminary Electrical Checks  
PCB  
bk  
bk  
Gas Valve Modulator  
Spark Electrode  
Gas Valve  
1. Prior to commissioning the boiler preliminary  
electrical system checks should be carried out.  
b
br  
bk  
Key to Wiring  
b - blue  
br - brown  
bk - black  
r - red  
Condensate Trap  
2. These should be performed using a suitable meter,  
and include checks for Ground Continuity,  
Flame Sensing Electrode  
r
Hydraulic Differential Pressure Switch  
DHW Flow Priority Microswitch  
g - green  
Resistance to Ground, Short Circuit and Polarity.  
r
g
g
Fig. 44  
31  
© Baxi Heating UK Ltd 2009  
11.0 Commissioning the Boiler  
11.1  
Commissioning the Boiler  
Screw  
1. Reference should be made to BS 5449 Section 5  
when commissioning the boiler.  
2. At the time of commissioning complete all relevant  
sections of the Benchmark Commissioning Checklist at  
the rear of this publication.  
Automatic Air  
Vent  
3. Open the mains water supply to the boiler.  
4. Open all hot water taps to purge the DHW system.  
5. Ensure that the filling loop is connected and open,  
then open the heating flow and return valves on the  
boiler.  
6. Open the screw on the automatic air vent  
(Fig. 45).  
7. The system must be flushed in accordance with BS  
7593 (see Section 6.2) and the flushing agent  
manufacturers instructions.  
Pump  
Fig. 45  
8. Pressurise the system to 1.0 bar then close and  
disconnect the filling loop.  
9. Turn the gas supply on and purge according to in GB  
BS 6891 and in IE I.S. 813 “Domestic Gas Installations”.  
2
1
3
0
4
10. Test for gas soundness.  
bar  
11. If at any time during commissioning it is required to  
terminate a particular cycle, e.g. the pump overrun  
period, turn the selector to the OFF position and then  
Selector Switch  
Fig. 46  
Pressure Gauge  
back to either ( ) or (  
) (Fig. 47).  
2
Burner On  
Reset  
1
3
Flame Failure  
Power On  
0
4
bar  
Power On  
Neon  
Hot Water  
Temperature Control  
Central Heating  
Temperature Control  
Fig. 47  
32  
© Baxi Heating UK Ltd 2009  
11.0 Commissioning the Boiler  
Pressure Test Point  
Sealing Screw  
11.2  
Checking the Burner Pressure  
1. Turn on the gas and electrical supplies to the boiler  
and ensure that all external controls are calling for  
heat.  
Gas Valve  
2. Set the temperature controls to maximum and the  
selector switch to the Off position (Fig. 51).  
3. Slacken the pressure test point sealing screw on the  
gas valve and connect a pressure gauge (Fig. 48).  
Fig. 48  
4. Undo the screws securing the inner door panel. Lift  
the panel slightly to disengage it from the studs on top  
of the case.  
Plastic  
Protection  
Cap  
5. Turn the selector switch fully anticlockwise against  
the spring pressure to the reset position and hold for  
2 seconds to reset the boiler (Fig. 51).  
6. Turn the selector switch to the Cental Heating and  
Domestic Hot Water position (  
neon ( ) will illuminate (Fig. 51).  
). The power On  
Modulator  
Wire  
Maximum Rate  
Adjustment Nut  
7. Turn a hot water tap on to give a flow rate of at  
least 10l/min.  
Minimum Rate  
Adjustment Nut  
Fig. 49  
NOTE: Gas Valve Electrical  
Plug/Igniter not shown for clarity.  
8. The pressure should be :-  
NG  
Propane  
10.2mbar  
21.8mbar  
If not, check that the gas supply pressure is correct  
(Natural Gas 20mbar, and Propane 37mbar).  
2
9. The pressure can be adjusted if required.  
1
3
0
4
10. To check and set minimum pressure first remove  
one of the modulator wires.  
bar  
Selector Switch  
Pressure Gauge  
Fig. 50  
Adjusting the Pressure (Fig 49)  
11. Remove the plastic protection cap from the  
pressure adjustment nuts on the valve.  
2
Burner On  
Reset  
1
3
Flame Failure  
Power On  
0
4
bar  
12. The smaller nut (5mm) adjusts minimum pressure  
and the larger nut (8mm) maximum pressure.  
Power On  
Neon  
13. Using a suitable spanner adjust the relevant nut  
until the correct pressure is achieved.  
Central Heating  
Temperature Control  
Hot Water  
Temperature Control  
Fig. 51  
14. Once the pressure has been set turn the boiler off  
and disconnect the pressure gauge.  
15. Tighten the pressure test screw and refit the  
modulator to the valve. Reassemble in reverse order.  
33  
© Baxi Heating UK Ltd 2009  
12.0 Completion  
12.1  
Completion  
Case Front Panel  
1. Refit the case front panel and tighten the securing  
screws (Fig. 52).  
2. Instruct the user in the operation of the boiler and  
system, explaining the operational sequence.  
3. Carefully read and complete all sections of the  
Benchmark Commissioning Checklist at the rear of this  
publication that are relevant to the appliance and  
installation. These details will be required in the event of  
any warranty work. The publication must be handed to  
the user for safe keeping and each subsequent regular  
service visit recorded.  
4. For IE, it is necessary to complete a “Declaration of  
Conformity” to indicate compliance with I.S. 813. An  
example of this is given in I.S. 813 “Domestic Gas  
Installations”. This is in addition to the Benchmark  
Commissioning Checklist.  
5. Hand over the Users Operating, Installation and  
Servicing Instructions, giving advice on the necessity of  
regular servicing.  
Facia Panel  
Fig. 52  
34  
© Baxi Heating UK Ltd 2009  
13.0 Servicing the Boiler  
Case Front Panel  
13 .1 Annual Servicing  
1. For reasons of safety and economy, it is  
recommended that the boiler is serviced annually.  
Servicing must be performed by a competent person.  
2. After servicing, complete the relevant Service Interval  
Record section of the Benchmark Commissioning  
Checklist at the rear of this publication.  
3. Ensure that the boiler is cool.  
4. Ensure that both the gas and electrical supplies to  
the boiler are isolated.  
5. Slacken the screws securing the facia panel. Lift the  
outercase panel so that its securing tabs are clear of the  
facia. Remove the panel (Fig. 53).  
Fig. 53  
6. Remove the screws securing the inner door panel. Lift  
the panel slightly to disengage it from the studs on top  
of the case (Fig. 54).  
Facia Panel Securing  
Screws  
7. Note the positions of the three wires on the fan  
motor and remove them. Remove the sensing tube  
from the fan spigot (Fig. 55).  
Fan Wires  
Fan  
8. Slacken the screws on the fan spigot outlet pipe  
clamp. Ease the clamp to the left over the pipe.  
9. Remove the four screws securing the combustion  
box door and remove the door (Fig. 54).  
Sensing  
Tube  
Ease Outlet Pipe Clamp  
To The Left  
Fig. 55  
Combustion  
Box Door  
Fig. 54  
Inner Door  
Panel  
35  
© Baxi Heating UK Ltd 2009  
Baffle  
Tab  
Spring Clip  
13.0  
Servicing the Boiler  
13.1  
Annual Servicing (Cont)  
10. Ease the front edge of the left hand baffle upwards,  
disengaging the spring clip. Disengage the tab on the  
baffle from the slot in the fan hood (Fig. 56).  
11. Undo the screws securing the fan and hood to the  
appliance back panel. Draw the assembly forwards  
(Fig. 57).  
Fig. 56  
12. Undo the screws securing the burner to the injector  
manifold. Draw the burner out of the combustion box,  
pulling the electrode grommets from the slots in the  
combustion box lower panel (Fig. 58).  
Fan and Hood  
Assembly  
Fig. 57  
13. Disconnect the electrode leads and grommets from  
the electrodes. Completely remove the burner (Fig. 58).  
14. Brush any deposits from the injectors. Do not use a  
pin or wire to clean them.  
15. Brush the burner blades and venturis and clean the  
combustion box.  
16. Ensure that the heat exchanger fins are clear of any  
obstruction.  
Electrode  
Grommets  
NOTE: If necessary the secondary heat exchanger  
may be dismantled - see section 14.24.  
DHW Filters (Fig. 60)  
17. If the flow of domestic hot water is diminished, it  
may be necessary to clean the filters.  
18. Initially check the cold water inlet tap filter.  
Fig. 58  
Threaded  
Bush  
19. Turn the tap off. Undo the blanking cap and remove  
the thread bush (Fig. 59).  
Fig. 59  
Burner  
20. Extract the filter and rinse thoroughly in clean water.  
Reassemble and check the flow. If required clean the  
manifold filter as described below.  
Cartridge  
Body  
21. Undo the filter cartridge from the inlet/return  
manifold.  
Filter Gauze  
22. Dismantle the cartridge and carefully remove the  
flow regulator and filter gauze. Rinse them thoroughly in  
clean water and reassemble in reverse order.  
Blanking Cap  
Cold Water  
Inlet Tap  
23. Check that the pressure vessel charge is 0.5bar and  
reassemble in reverse order of dismantling and  
recommission.  
Flow  
Regulator  
Venturi  
24. Turn the selector switch fully anticlockwise against  
the spring pressure to the reset position and hold for 2  
seconds to reset the boiler.  
Fig. 60  
25. Complete the relevant Service Interval Record  
section of the Benchmark Commissioning Checklist at  
the rear of this publication and then hand it back to the  
user.  
Inlet/Return Manifold  
36  
© Baxi Heating UK Ltd 2009  
14.0 Changing Components  
IMPORTANT: When changing components ensure  
that both the gas and electrical supplies to the  
boiler are isolated before any work is started.  
When the new component has been fitted turn the  
selector switch fully anticlockwise against the spring  
pressure to the ‘Reset’ position and hold for 2  
seconds to reset the boiler before recommissioning.  
Pressure  
Switch  
Sensing  
Tubes  
See Section 13.1 “Annual Servicing” for removal of case  
panel, door etc.  
14.1  
Fan (Figs. 62 & 63)  
Fig. 61  
1. Note the positions of the sensing tube on the outlet  
elbow and three wires on the fan motor and remove  
them.  
Pressure  
Switch Wires  
2. Slacken the screw on the fan spigot outlet pipe clamp.  
Ease the clamp to the left over the pipe.  
3. Remove the four screws securing the combustion box  
door and remove the door.  
Fan Wires  
Fan  
4. Ease the front edge of the left hand baffle upwards,  
disengaging the spring clip. Disengage the tab on the  
baffle from the slot in the fan hood.  
5. Undo the screws securing the fan hood to the  
appliance back panel, and draw the fan and hood  
assembly forwards.  
Sensing  
Tube  
6. Remove the screws and spring washers securing the  
fan to the hood, and the screw securing the outlet pipe.  
Ease Outlet Pipe Clamp  
To The Left  
7. Transfer the outlet pipe and clamp to the new fan.  
8. Fit the new fan to the hood using the screws and  
spring washers previously removed.  
Fig. 62  
9. Reassemble in reverse order of dismantling.  
14.2  
Pressure Switch (Fig. 61)  
Fan Spigot  
Outlet Pipe  
1. Remove the fan and hood assembly as described in  
section 14.1.  
2. Note the positions of the two sensing tubes and  
wires and remove them.  
Baffle  
Tab  
Spring Clip  
3. Remove the two screws holding the pressure switch  
to the bracket on the combustion box top panel.  
Fan  
4. Fit the new pressure switch and reassemble all  
components in reverse order of dismantling.  
Fan Hood  
Fig. 63  
Spring Washer  
Securing Screw  
37  
© Baxi Heating UK Ltd 2009  
14.0 Changing Components  
14.3  
Heat Exchanger (Fig. 64)  
1. Remove the fan as described in section 14.1.  
2. Drain the primary circuit. Prise the three pipe  
connecting clips off the joints in the flow and return  
pipes. Remove the heat exchanger return pipe.  
3. Lift the heat exchanger to disconnect the flow pipe  
joint. Withdraw it from the appliance, taking care not to  
damage the rear insulation piece.  
Pipe Connecting  
Clips  
Heat Exchanger  
Return Pipe  
4. Fit the new heat exchanger.  
5. Reassemble in reverse order of dismantling, and  
repressurise the system.  
14.4  
Burner (Fig. 65)  
1. Remove the four screws securing the combustion box  
door and remove the door.  
Flow Pipe  
2. Undo the screws securing the burner to the injector  
manifold. Draw the burner out of the combustion box,  
pulling the electrode grommets from the slots in the  
combustion box lower panel.  
Fig. 64  
Heat Exchanger  
3. Disconnect the electrode leads and grommets from  
the electrodes. Completely remove the burner.  
4. Undo the screws securing the electrodes to the  
burner. Examine the condition of the electrodes,  
replacing if necessary. Fit the electrodes to the new  
burner.  
5. Engage the burner location brackets over the studs on  
the injector manifold and reassemble in reverse order.  
Burner  
Electrodes  
Electrode  
Grommets  
Fig. 65  
Electrode  
Leads  
38  
© Baxi Heating UK Ltd 2009  
14.0 Changing Components  
Injector  
Manifold  
Inlet Elbow  
14.5  
Injectors (Fig. 66)  
1. Remove the burner as described in Section 14.4.  
2. Undo the screws securing the injector manifold to  
the inlet elbow and remove the manifold.  
Gasket  
3. Unscrew and replace injectors as required and  
examine the sealing gasket, replacing as necessary.  
Reassemble in reverse order.  
Injector  
14.6  
Electrodes (Fig. 66)  
Burner  
Electrodes  
1. Remove the four screws securing the combustion  
box door and remove the door.  
Fig. 66  
Electrode  
Grommets  
2. Undo the screws securing the burner to the  
injector manifold. Draw the burner out of the  
combustion box, pulling the electrode grommets from  
the slots in the combustion box lower panel.  
Electrode  
Leads  
3. Disconnect the lead and grommet from the  
electrode being replaced. Undo the securing screw  
and withdraw the electrode to the burner.  
4. Reassemble in reverse order.  
14.7  
Insulation (Fig. 67)  
1. Remove the four screws securing the combustion  
box door and remove the door.  
2. Slide the side insulation pieces carefully out of their  
carriers.  
3. To replace the rear insulation piece it is necessary  
to remove the heat exchanger as described in Section  
14.3 and slide out the side pieces.  
Side Insulation  
4. The combustion box door insulation piece can be  
replaced by carefully bending up the two retaining  
tabs.  
Rear Insulation  
5. Replace all insulation pieces and reassemble in  
reverse order.  
13.8  
Side Insulation  
Combustion Box  
Door  
Front Insulation  
Fig. 67  
39  
© Baxi Heating UK Ltd 2009  
14.0 Changing Components  
14.8  
Gas Valve (Fig. 68)  
1. Undo the nut on the gas feed pipe under the boiler.  
Modulator  
Wires  
2. Completely undo the securing screws and hinge the  
facia panel down.  
Ignition  
Lead  
Gas Valve  
3. Disconnect the wires from the valve modulator and  
the ignition lead from the spark generator. Disconnect  
the pressure sensing pipe from the valve. Undo the  
screw securing the spark generator electrical plug to the  
valve and disconnect the plug.  
4. Pull the earth wire off the spade terminal on the valve.  
5. Remove the screws securing the inlet pipe flange to  
the boiler bottom panel and those securing the outlet  
manifold to the burner manifold.  
Electrical Plug  
6. Remove the valve from the boiler.  
Earth Wire  
Inlet Pipe  
7. Note the orientation of the inlet pipe and outlet  
manifold. Undo the securing screws and remove the  
pipe and manifold.  
Gas Feed  
Pipe  
8. Examine the ‘O’ ring seals for damage, replacing as  
necessary.  
Fig. 68  
9. Fit the inlet pipe and outlet manifold to the new valve,  
ensuring that the ‘O’ ring seals are in place.  
10. Reassemble in reverse order and check the burner  
pressure (Section 11.2).  
Flow Pipe  
14.9  
Temperature Sensor (Fig. 69)  
1. Ease the retaining tab on the sensor away and  
disconnect the electrical plug.  
Safety Thermostat  
2. Unscrew the sensor from it’s pocket and reassemble  
in reverse order. The plug will only fit one way.  
14.10 Safety Thermostat (Fig. 69)  
1. Pull the electrical connections off the thermostat.  
2. Remove the screws securing the thermostat to the  
mounting plate on the flow pipe.  
Temperature  
Sensor  
3. Reassemble in reverse order. The thermostat is not  
polarised - either wire can fit either terminal on the  
thermostat.  
Fig. 69  
40  
© Baxi Heating UK Ltd 2009  
14.0 Changing Components  
14.11 Pump - Head Only (Fig. 71)  
1. Drain the primary circuit and remove the socket  
head screws securing the pump head to the body and  
draw the head away.  
2. Undo the screw on the pump wiring cover and  
remove the cover. Using a suitable flat bladed screw  
driver press the cable securing levers downwards to  
release each wire after noting their position.  
3. A standard Grundfos 15-60 replacement head can  
now be fitted. Connect the wiring to the new head.  
The pump speed must be set to 3 (Fig. 72).  
4. Reassemble in reverse order.  
14.12 Pump - Complete (Fig. 73)  
1. Drain the primary circuit and unscrew the automatic  
air vent from the pump body. Undo the two screws  
securing the body to the pipe and manifold and draw  
the pump forwards.  
Pump Wiring  
Cover  
Pump Body  
2. Undo the screw on the pump wiring cover and  
remove the cover. Using a suitable flat bladed screw  
driver press the cable securing levers downwards to  
release each wire after noting their position.  
Socket Headed  
Screw  
3. Connect the wiring to the new pump. Examine the  
‘O’ ring seals on the return pipe and manifold, replacing  
if necessary.  
Pump Head  
4. Fit the air vent to the pump body and reassemble in  
reverse order.  
Fig. 71  
14.13 Automatic Air Vent (Fig. 73)  
1. Drain the primary circuit and unscrew the automatic  
air vent from the pump body.  
Pump Setting  
Automatic Air  
Vent  
2. Examine the ‘O’ ring seal, replacing if necessary, and  
fit it to the new automatic air vent.  
Fig. 72  
3. Reassemble in reverse order.  
Pump Wiring  
Cover  
Fig. 73  
41  
© Baxi Heating UK Ltd 2009  
14.0 Changing Components  
14.14 Pressure Gauge (Figs. 74 & 75)  
1. Drain the primary circuit and undo the nut on the  
pressure gauge capillary.  
2. Remove the timer cover and ease the timer wiring  
aside. Undo the screws securing the gauge retaining  
bracket.  
Fig. 74  
Pressure Gauge  
Capillary  
3. Remove the bracket and gauge assembly. Depress  
the barbs on the side of the gauge and remove the  
retaining bracket.  
Gauge Retaining  
Bracket  
4. Reassemble in reverse order.  
14.15 Expansion Vessel (Fig. 76)  
Timer Cover  
1. To replace the expansion vessel it is necessary to  
remove the boiler from the wall.  
Pressure Gauge  
Fig. 75  
Note: Alternatively a vessel of equivalent  
capacity can be fitted on the system return  
pipe as close as possible to the boiler.  
Expansion Vessel  
2. Drain the system and undo all gas, water and  
condensate drain connections. Remove the flue elbow.  
3. Lift the boiler off the wall plate and lay it on it’s side  
on a clean flat surface.  
4. Undo the nut on the vessel outlet spigot, and  
remove the locknut and spring washer securing the  
spigot to the boiler chassis.  
Retaining Clip  
5. Undo the screws and remove the appliance upper  
cross member. Slide the expansion vessel out of the  
retaining clips.  
Vessel Outlet Spigot  
Boiler Chassis  
Lock Nut  
6. Reassemble in reverse order. Fully recommission  
the appliance and system.  
Spring  
Washer  
14.16 Condensate Trap (Fig. 77)  
Fig. 76  
1. Disconnect the two sensing wires from the trap  
connections.  
Inlet Pipe  
Sensing Wires  
2. Squeeze together the wire spring clip to release and  
ease the inlet pipe from the trap spigot.  
Wire Spring  
Clip  
3. Undo the nut securing the condensate drain pipe to  
the trap. Disconnect the pipe and sealing washer.  
Condensate  
Trap  
4. From underneath the boiler remove the screws  
securing the trap bracket.  
Bracket  
5. Remove the trap and bracket from the boiler. Undo  
the locknut securing the trap to the bracket.  
Fig. 77  
Condensate  
Drain Pipe  
6. Reassemble in reverse order.  
42  
© Baxi Heating UK Ltd 2009  
14.0 Changing Components  
14.17 Pressure Relief Valve (Fig. 78)  
1. Drain the primary circuit.  
2. Disconnect the discharge pipe from the valve. Using a  
suitable hexagon key undo the grub screw sufficiently to  
release the valve.  
3. Note the orientation of the valve, rotate it and  
withdraw it from the manifold.  
4. Fit the new valve and ‘O’ ring seal and set to the  
previously noted orientation. Reassemble in reverse  
order.  
‘O’ ring seal  
14.18 P.C.B. (Fig. 80)  
1. Note the settings of the temperature control knobs.  
Rotate the knobs fully anticlockwise and carefully pull  
them off the drive pins.  
Grub Screw  
Pressure Relief Valve  
2. Completely undo the screws securing the control box  
cover and release the cover retaining barbs from their  
slots. Disengage the rear of the cover from the control  
box hinge pin (Fig. 79).  
Fig. 78  
Discharge Pipe  
3. Note the position of all plugs and wires on the P.C.B.  
and disconnect them.  
4. Undo the securing screws and remove the P.C.B.  
Transfer the control knob drive pins to the new P.C.B.  
and turn them fully anticlockwise.  
5. Reassemble in reverse order, ensuring that the  
temperature controllers are reset to their previous  
positions.  
Control Box Cover  
P.C.B.  
Fig. 79  
14.19 Selector Switch (Fig. 80)  
1. Note the setting of the selector switch knob and  
carefully pull it off the facia.  
2. Completely undo the screws securing the control box  
cover and release the cover retaining barbs from their  
slots. Disengage the rear of the cover from the control  
box hinge pin (Fig. 79).  
Selector  
Switch  
Drive Pins  
3. Note the position of the electrical connections and  
the orientation of the switch. Remove the electrical  
connections.  
4. Remove the screws securing the switch to the facia  
panel.  
5. Fit the new switch, ensuring that it is correctly  
positioned and reassemble in reverse order.  
Facia  
Fig. 80  
Selector Switch Knob  
Temperature Control Knobs  
43  
© Baxi Heating UK Ltd 2009  
14.0 Changing Components  
Plate Heat Exchanger  
14.20 Plate Heat Exchanger (Fig. 67)  
1. Drain the primary circuit.  
2. While supporting the heat exchanger undo the  
screws securing it to the brass manifolds.  
3. Withdraw the heat exchanger upwards and to the  
left of the gas valve, taking care not to damage any  
wires or controls.  
Rubber Seal  
Seals  
4. There are four rubber seals between the manifolds  
and heat exchanger which may need replacement.  
Fig. 81  
5. Ease the seals out of the manifold. Replace carefully,  
ensuring that the seal is inserted into the manifold  
parallel and pushed fully in.  
6. When fitting the new heat exchanger note that the  
left hand location stud is offset towards the centre  
more than the right hand one.  
7. Reassemble in reverse order.  
14.21 Diverter Valve Assembly  
(Figs. 82 & 83)  
The diverter valve assembly comprises of a central  
heating pressure differential valve and a domestic hot  
water pressure differential valve. These are connected  
to a manifold which is joined to the plate heat  
exchanger.  
Sensing Pipes  
Diverter Manifold  
DHW Pressure Differential Valve (Fig. 83)  
1. Drain the primary circuit.  
Microswitch  
Bracket  
2. Undo the screw securing the microswitch bracket to  
the valve (Fig. 82).  
Grub Screws  
3. Disconnect the two sensing pipes and slacken the  
grub screws securing the valve to the diverter manifold.  
DHW Pressure  
Differential Valve  
Fig. 82  
4. Draw the valve away from the diverter manifold. The  
valve may now be replaced or split to examine the  
diaphragm.  
Diaphragm  
5. To examine the diaphragm hold the valve body  
securely and carefully remove the six screws. The  
diaphragm spring will force apart the two halves of the  
valve.  
Diaphragm  
Spring  
6. Remove the plastic disc and pushrod assembly.  
Carefully examine the diaphragm and replace it if there  
is any damage.  
Plastic Disc  
Pushrod  
7. Reassemble in reverse order.  
Fig. 83  
44  
© Baxi Heating UK Ltd 2009  
14.0 Changing Components  
Central Heating Pressure  
Differential Valve  
Microswitch / Bracket  
14.21 Diverter Valve Assembly (Cont)  
Sensing Pipe  
Pressure Differential Valve (Fig. 84)  
1. Remove the pressure differential valve as described  
above.  
By-pass Pipe  
Diaphragm  
2. From the brass diverter manifold undo the nut on  
the heating flow pipe. Remove the screw securing the  
diverter manifold to the appliance lower bracket.  
Spring Clip  
3. Disconnect the pressure gauge capillary from the  
diverter manifold and remove the two wires from the  
microswitch.  
Heating Flow  
Pipe  
4. Prise off the spring clip securing the by-pass pipe to  
the diverter manifold and disconnect the sensing pipe.  
Diverter Manifold  
5. Ease the diverter manifold out of the plate heat  
exchanger manifold. Remove the assembly from the  
appliance.  
Fig. 84  
Pressure Gauge  
Capillary  
6. Undo the screw securing the microswitch bracket  
to the valve body. The sensor may now be dismantled  
to examine the diaphragm.  
7. To examine the diaphragm hold the assembly  
securely and carefully remove the four screws. The  
diaphragm spring will force the two halves of the valve  
apart.  
8. Carefully examine the diaphragm and replace it if  
there is any damage.  
9. Reassemble in reverse order.  
CH Pressure Microswitch (Fig. 84)  
1. Remove the two wires from the Pressure  
microswitch.  
2. Undo the screw securing the microswitch bracket  
to the valve body.  
3. Reassemble in reverse order.  
Cartridge  
Body  
14.22 Flow Regulator (Figs. 85 & 86)  
Filter Gauze  
1. Undo the filter cartridge from the inlet/return  
manifold.  
Fig. 85  
2. Unscrew the venturi and remove the flow regulator.  
Flow  
Regulator  
Fig. 86  
3. Check the cleanliness of the filter gauze, rinsing  
thoroughly in clean water as necessary. Fit the new  
flow regulator and reassemble in reverse order.  
Venturi  
Inlet/Return Manifold  
45  
© Baxi Heating UK Ltd 2009  
14.0  
Changing Components  
Secondary  
Heat Exchanger  
14.23 Secondary Heat Exchanger (Fig. 87)  
1. Drain the primary circuit  
Pipe Connecting Clip  
2. Undo the four screws securing the right hand case  
panel. Remove the panel.  
3. Prise the connecting clips from the heat exchanger  
return pipe and the boiler return pipe. Remove the  
pipes.  
Outer Drum  
4. Remove the fan and hood assembly as described in  
Section 14.1  
Boiler Return Pipe  
5. Remove the nut securing the elbow to the secondary  
heat exchanger. Draw the elbow and outlet pipe  
forwards.  
Heat Exchanger  
Return Pipe  
Elbow  
Fig. 87  
6. Remove the secondary heat exchanger from the  
outer drum by easing it forward.  
7. Reassemble in reverse order of dismantling.  
14.24 Flue Overheat Thermostat (Fig. 88)  
NOTE: The flue overheat thermostat includes a  
reset button. Check that the thermostat will not  
reset before replacing.  
1. Remove the fan and hood assembly as described in  
Section 14.1  
2. Pull the two wires off the terminals on the flue  
overheat thermostat. Unscrew the thermostat from the  
adaptor in the outlet elbow.  
3. Reassemble in reverse order of dismantling.  
Fig. 88  
Overheat Thermostat  
46  
© Baxi Heating UK Ltd 2009  
15.0 Illustrated Wiring Diagram  
Pump  
Mains Input  
Link  
g/y  
On/Off/Reset  
Selector Switch  
b
br  
Fuse  
Temperature Sensor  
bk  
g/y  
bk  
br  
b
8
b
b
b
9
Hydraulic Differential  
Pressure Switch  
10  
br  
1
bk  
2
bk  
11  
r
3
1
4
br  
12  
13  
14  
15  
16  
17  
br  
r
2
3
4
5
6
7
br  
bk  
18  
19  
20  
b
r
Flue Thermostat  
r
M3  
b
r
Optional Timers  
Gas Valve  
M1  
35  
b
bk  
Control PCB  
36  
37  
38  
39  
M2  
M7  
bk  
br  
b
44  
43  
42  
M4  
bk  
bk  
Safety Thermostat  
32  
31  
30  
29  
28  
b
b
Air Pressure  
Switch  
3-Way Valve  
Microswitch  
br  
br  
27  
g/y  
M5  
FA2  
Fan  
g/y  
Flame  
Sensing  
Electrode  
Condensate  
Trap  
br - brown  
bk - black  
b
r
- blue  
- red  
y
- yellow  
g/y - green / yellow  
w - white  
gr - grey  
47  
© Baxi Heating UK Ltd 2009  
16.0 Fault Finding  
Carry out initial fault finding checks  
1. Check that gas, water and electrical supplies are available at the boiler. Electrical supply = 230V ~ 50 Hz.  
CH water system pressurised to 0.5 bar when the boiler is cold. The preferred minimum gas pressure is 19.5mbar (natural gas),  
or 36mbar (propane).  
2. Carry out electrical system checks, i.e. Ground Continuity, Resistance to Ground, Short Circuit and Polarity with a suitable meter.  
NOTE: These checks must be repeated after any servicing or fault finding.  
3. Ensure all external controls are calling for heat and check all external and internal fuses. Before any servicing or replacement of parts  
ensure the gas and electrical supplies are isolated.  
Refer to Section 13.1 “Illustrated Wiring Diagram” for position of numbered terminals  
Central Heating - Follow operational sequence  
NOTE: When instructed to turn the Selector to  
Turn selector to  
neon illuminated  
the reset position turn the Selector Switch fully  
anticlockwise against the spring pressure and hold  
for 2 seconds to reset the boiler.  
NO  
Go to section ‘A’  
YES  
Go to section ‘B’  
YES  
Turn  
thermostat  
to max.  
Pump runs  
External controls and, where  
fitted, integral timer calling for  
heat  
Ensure controls are set to  
demand and verify the  
contacts are closed  
NO  
NO  
YES  
NO  
NO  
Primary flow switch operated  
YES  
Go to section ‘C’  
Turn the selector switch to  
the ‘Reset’ position and hold  
for at least 2 seconds. If  
regular resetting is required,  
or appliance still does not  
operate, investigation is  
necessary  
Go to sections ‘J’, ‘L’ & ‘D’  
Fan runs at max speed  
YES  
NO  
NO  
Air pressure  
switch proved  
Go to section ‘E’  
YES  
YES  
Spark at ignition electrodes  
for up to 10 seconds  
Turn selector to the reset  
position. If the light does not  
extinguish go to sections  
H & K  
illuminated  
NO  
YES  
Replace PCB  
NO  
YES  
Burner on  
neon  
Go to section ‘F’  
Go to section ‘I’  
illuminated  
YES  
Burner extinguishes  
after 10 seconds  
NO  
Burner output  
modulates until set  
temperature is reached  
NO  
YES  
Go to section ‘G’  
Fan stops  
YES  
YES  
YES  
Operation sequence correct  
Burner goes out  
Pump stops  
48  
© Baxi Heating UK Ltd 2009  
16.0 Fault Finding  
Domestic Hot Water - Follow operational sequence  
Turn selector to  
neon illuminated  
NO  
Replace diaphragm  
Go to section ‘A’  
YES  
YES  
Is mains water  
filter and differential  
assembly clean?  
YES  
DHW flow valve diaphragm  
damaged  
NO  
YES  
Turn  
thermostat to max.  
NO  
DHW flow rate more than  
2.5l/min.  
DHW flow valve rod  
obstructed  
Open DHW tap fully. DHW  
flow switch operated  
YES  
NO  
YES  
Replace DHW flow  
microswitch  
Continuity across DHW flow  
microswitch terminals and  
PCB - M1 connector  
terminals 13 & 14 (terminals  
12-14 open)  
Primary water is diverted  
from CH system to DHW  
heat exchanger and flow  
microswitch operated  
NO  
Replace PCB  
YES  
NO  
NO  
NO  
Pump runs  
YES  
Go to section ‘B’  
Go to section ‘C’  
Primary flow switch operated  
YES  
Turn the selector switch to  
the ‘Reset’ position and hold  
for at least 2 seconds. If  
regular resetting is required,  
or appliance still does not  
operate investigation is  
necessary  
Go to section ‘J’, ‘L’ & ‘D’  
Fan runs at max speed  
YES  
NO  
NO  
Go to section ‘E’  
Air pressure switch proved  
YES  
Turn the selector to the reset  
position. If the light does not  
extinguish go to section  
H & K  
YES  
neon illuminated  
NO  
Spark at ignition electrodes  
for up to 10 seconds  
YES  
Replace PCB  
NO  
YES  
Burner on  
neon  
Go to section ‘F’  
Go to section ‘I’  
illuminated  
YES  
Burner extinguishes  
after 10 seconds  
NO  
Reduce the DHW flow rate.  
If burner does not modulate  
clean temperature sensor and  
DHW heat exchanger. If  
modulation does not occur  
go to section ‘G’  
NO  
Burner output modulates to  
maintain temperature set at  
thermostat  
YES  
Close DHW tap  
YES  
DHW flow valve  
senses no flow.  
Primary water diverted to  
CH system. DHW flow  
switch released off  
NO  
NO  
Diverter valve spindle  
assembly faulty  
YES  
YES  
YES  
Operation sequence correct  
Burner goes out  
Fan stops  
Pump stops  
49  
© Baxi Heating UK Ltd 2009  
Fault Finding Solutions Sections A to F  
16.0 Fault Finding  
Is there 230V at:  
A
NO  
1.  
2.  
3.  
Main terminals L and N  
Main terminal fuse  
Check electrical supply  
Replace fuse  
YES  
NO  
neon  
illuminated  
Replace PCB  
NO  
Selector terminals a & b and a  
& 3. PCB - M1 connector  
terminals 9 & 10  
Check wiring  
Replace selector  
Is there 230V at:  
B
NO  
NO  
1.  
2.  
Pump  
If pump jammed, release  
Replace pump  
Replace PCB  
PCB - M1 connector terminals 8 & 15  
YES  
Change pump supply cable  
NO  
1.  
2.  
CH system pressure 0.5 to 1.5 bar  
Re-pressurise system  
C
D
NO  
Check the tap of the automatic air  
vent is opened  
Open the automatic air vent  
YES  
3.  
Primary flow valve diaphragm damaged  
NO  
Replace diaphragm  
Flow valve rod obstructed  
1.  
2.  
3.  
Continuity across flow  
NO  
Replace microswitch  
Replace sensor  
microswitch and PCB M2  
connector terminals 3 & 4  
Primary temperature sensor faulty.  
Cold resistance approx. 11K ohms  
(resistance reduces with increase in temp.)  
YES  
Fan connections correct at fan.  
YES  
YES  
PCB - M5 connector, is 230V  
Fan jammed or faulty winding  
Replace PCB  
Replace fan  
across terminals 28 & 29  
NO  
Check and correct if necessary  
1. Electrical and pressure tube connections  
2. Blockage of pressure tubes  
3. Restriction in flue  
E
F
NO  
Replace air pressure  
switch  
4. Venturi  
NO  
Gas at burner  
Ensure gas is on and purged  
YES  
PCB - M4 connector is approx 230V AC, terminals  
36 & 38  
Replace gas valve  
NO  
YES  
Turn selector switch to  
‘Reset’ position  
neon illuminated  
NO  
Replace PCB  
50  
© Baxi Heating UK Ltd 2009  
Fault Finding Solutions Sections G to L  
16.0 Fault Finding  
G
1.  
2.  
Check the burner setting pressure of the  
gas valve  
(see Section 11.2 of Commissioning)  
Voltage at modulating coil of gas valve is:  
Max. burner press.approx 9V DC (13V DC LPG)  
Min. burner press.approx 1V DC  
YES  
NO  
Replace gas valve  
Replace PCB  
Current at modulating coil of gas valve is:  
(Use an instrument with average function for this  
measure)  
30 ÷ 230 mA DC (45 ÷ 310 mA DC LPG)  
NO  
Check and correct if necessary  
1. Ignition electrode and lead  
2. Electrode connection  
H
I
Replace PCB  
230V at Main PCB - M4  
connector across terminals  
37 & 38. Check wiring  
YES  
YES  
Replace gas valve  
electrical plug/igniter  
assy  
3. Spark gap and position  
Ensure that mains input terminal L  
is Live (230V) and N is Neutral  
(0V)  
YES  
Check and correct if necessary  
1. Flame sensing electrode and lead connections  
2. Electrode position  
YES  
NO  
Replace PCB  
Flame current should be 1 μA approx.  
Replace flame sensing electrode  
Boiler overheat thermostat operated  
NO  
Allow to cool. Continuity across  
thermostat terminals more than  
1.5 ohm  
J
YES  
Replace boiler overheat  
thermostat  
or faulty, i.e. continuity across  
thermostat terminals  
YES  
Replace PCB  
NO  
Check terminal 1 of ON/OFF/RESET selector is in connection  
with PCB - M1 connector terminal 16  
Check electrical continuity across terminals 1 & a of  
ON/OFF/RESET selector when turned to ‘Reset’ position  
Replace ON/OFF/RESET selector  
K
L
YES  
Replace PCB  
Press the reset button on the flue overheat thermostat. If the  
boiler does not relight or repeatedly cuts out check the operation  
of the flue system or replace the flue overheat thermostat. If the  
flue overheat thermostat has not been activated see section ‘D’  
51  
© Baxi Heating UK Ltd 2009  
17.0 Fault Indication Display  
17.0  
Fault Indication Display  
1. The boiler has three neon indicators. The upper two  
function as boiler on and fault indicators.  
A
2. Depending on the nature of the fault the upper two neons  
will illuminate, go off or flash.  
Burner On  
Flame Failure  
Power On  
Off  
Fast Flashing (2 every second)  
3. There are five possible combinations, each indicating one  
or more fault conditions. These are described below.  
On  
A
The flue or flue terminal is blocked or obstructed in some  
way, or there is an internal fault.  
B
B
Burner On  
Flame Failure  
Power On  
Off  
Slow Flashing (1 every 2 seconds)  
On  
The circulating pump is faulty or the system pressure has  
dropped. Check the system pressure. If the pressure is in the  
normal range a pump fault is indicated.  
C
A fault on the boiler temperature sensor is indicated.  
D
C
The primary system or the boiler has overheated. Allow the  
boiler to cool. Turn the selector switch fully anti-clockwise  
against the spring pressure to the ‘Reset’ position and hold for  
at least 2 seconds.  
Burner On  
Flame Failure  
Power On  
Slow Flashing (1 every 2 seconds)  
Slow Flashing (1 every 2 seconds)  
On  
If the boiler does not relight after resetting it is possible that  
the flue has overheated.  
E
The burner has failed to light, or incomplete lighting of the  
burner has occurred. Turn the selector switch fully anti-  
clockwise against the spring pressure to the ‘Reset’ position  
and hold for at least 2 seconds.  
D
Burner On  
Flame Failure  
Power On  
Slow Flashing (1 every 2 seconds)  
If the boiler does not relight after resetting blockage of the  
condensate drain or trap has occurred.  
On  
On  
E
Burner On  
Flame Failure  
Power On  
Off  
On  
On  
52  
© Baxi Heating UK Ltd 2009  
18.0 Short Parts List  
Short Parts List  
Key  
No.  
G.C.  
No.  
Description  
Manufacturers  
Part No.  
44  
140  
22  
23  
32  
41  
44  
59  
63  
Fan  
5112627  
5112999  
5112431  
5112770  
248210  
22  
Pressure Switch  
Heat Exchanger  
Burner  
131  
135  
A
E66 402  
E66 408  
E66 411  
Injector - 1.18 NG  
Electrode Lead  
63  
248037  
Spark or Sensing  
Electrode  
247384  
248042  
72  
Pump  
101  
102  
103  
131  
135  
140  
154  
169  
371  
A
E66 432  
E66 434  
343 619  
Hydraulic Outlet Assy. 248061  
154  
Valve - 3 Way Assy.  
248062  
23  
Pressure Differential Assy.248063  
Temperature Sensor  
5108265  
E66 697  
Safety Limit Thermostat 248078  
Gas Valve  
PCB  
5107339  
5112657  
248090  
41  
E66 453  
Pressure Gauge  
72  
Igniter/Gas Valve Cable 5112385  
101  
Flue Overheat  
Thermostat  
5112395  
59  
102  
103  
371  
32  
169  
53  
© Baxi Heating UK Ltd 2009  
GAS BOILER SYSTEM COMMISSIONING CHECKLIST  
This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating  
compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.  
Failure to install and commission this equipment to the manufacturer’s instructions may invalidate the warranty but does not affect statutory rights.  
Customer Name  
Address  
Telephone Number  
Boiler Make and Model  
Boiler Serial Number  
Commissioned by (print name)  
Company Name  
CORGI ID Number  
Telephone Number  
Company Address  
Commissioning Date  
To be completed by the customer on receipt of a Building Regulations Compliance Certificate :  
*
Building Regulations Notification Number (if applicable)  
CONTROLS Tick the appropriate boxes  
Time and Temperature Control to Heating  
Room Thermostat and  
Programmer/Timer  
Programmable  
Room Thermostat  
Load/Weather  
Compensation  
Optimum Start  
Control  
Time and Temperature Control to Hot Water  
Heating Zone Valves  
Cylinder Thermostat and Programmer/Timer  
Combination Boiler  
Not Required  
Not Required  
Not Required  
Not Required  
Provided  
Fitted  
Fitted  
Fitted  
Fitted  
Hot Water Zone Valves  
Thermostatic Radiator Valves  
Automatic Bypass to System  
Boiler Interlock  
ALL SYSTEMS  
The system has been flushed and cleaned in accordance with BS7593 and boiler manufacturer’s instructions  
Yes  
What system cleaner was used?  
What inhibitor was used?  
Quantity  
litres  
ft3/hr  
CENTRAL HEATING MODE Measure and Record:  
m3/hr  
mbar  
OR  
OR  
Gas Rate  
Burner Operating Pressure (if applicable)  
Central Heating Flow Temperature  
Central Heating Return Temperature  
Gas Inlet Pressure  
mbar  
°C  
°C  
COMBINATION BOILERS ONLY  
Is the installation in a hard water area (above 200ppm)?  
If yes, has a water scale reducer been fitted?  
What type of scale reducer has been fitted?  
DOMESTIC HOT WATER MODE Measure and Record:  
Gas Rate  
Yes  
Yes  
No  
No  
ft3/hr  
m3/hr OR  
mbar OR  
Burner Operating Pressure (at maximum rate)  
Cold Water Inlet Temperature  
Gas Inlet Pressure (at maximum rate)  
mbar  
°C  
Hot water has been checked at all outlets  
Water Flow Rate  
Yes  
Temperature  
°C  
l/min  
CONDENSING BOILERS ONLY  
The condensate drain has been installed in accordance with the manufacturer’s instructions and/or BS5546/BS6798  
Yes  
ALL INSTALLATIONS  
If required by the manufacturer, record the following  
CO2  
%
OR CO  
ppm OR CO/CO2 Ratio  
The heating and hot water system complies with the appropriate Building Regulations  
Yes  
Yes  
Yes  
Yes  
The boiler and associated products have been installed and commissioned in accordance with the manufacturer’s instructions  
The operation of the boiler and system controls have been demonstrated to and understood by the customer  
The manufacturer’s literature, including Benchmark Checklist and Service Record, has been explained and left with the customer  
Commissioning Engineer’s Signature  
Customer’s Signature  
(To confirm satisfactory demonstration and receipt of manufacturer’s literature)  
All installations in England and Wales must be notified to Local Authority Building Control (LABC) either directly or through a Competent Persons Scheme.  
A Building Regulations Compliance Certificate will then be issued to the customer.  
*
54  
©Heating and Hotwater Industry Council (HHIC)  
SERVICE RECORD  
It is recommended that your heating system is serviced regularly and that the appropriate Service Record is completed.  
Service Provider  
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s  
instructions.  
Always use the manufacturer’s specified spare part when replacing controls.  
SERVICE 1 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
SERVICE 2 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
No  
No  
No  
No  
Company Name  
Company Name  
Telephone Number  
CORGI ID Number  
Comments  
Telephone Number  
CORGI ID Number  
Comments  
Signature  
Signature  
SERVICE 3 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
SERVICE 4 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
Company Name  
Company Name  
Telephone Number  
CORGI ID Number  
Comments  
Telephone Number  
CORGI ID Number  
Comments  
Signature  
Signature  
SERVICE 5 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
SERVICE 6 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
Company Name  
Company Name  
Telephone Number  
CORGI ID Number  
Comments  
Telephone Number  
CORGI ID Number  
Comments  
Signature  
Signature  
SERVICE 7 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
SERVICE 8 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
Company Name  
Company Name  
Telephone Number  
CORGI ID Number  
Comments  
Telephone Number  
CORGI ID Number  
Comments  
Signature  
Signature  
SERVICE 9 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
SERVICE 10 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
Company Name  
Company Name  
Telephone Number  
CORGI ID Number  
Comments  
Telephone Number  
CORGI ID Number  
Comments  
Signature  
Signature  
55  
All descriptions and illustrations provided in this leaflet have been  
carefully prepared but we reserve the right to make changes and  
improvements in our products which may affect the accuracy of the  
information contained in this leaflet. All goods are sold subject to our  
standard Conditions of Sale which are available on request.  
POTTERTON  
A Trading Division of Baxi Heating UK Ltd (3879156)  
A Division of Baxi Group  
Brooks House, Coventry Road, Warwick. CV34 4LL  
After Sales Service 08706 017 017 Technical Enquiries 08706 049 049  
e&oe  
o
© Baxi Heating UK Ltd 2009  
Comp N 5111811 - Iss 6 - 3/09  

Alpine Electronics Car Video System IVE W535HD User Manual
Audiovox Jensen Phase Linear UMP400 User Manual
Audiovox VBP500 User Manual
Cuisinart BFM 1000 User Manual
Custom Brackets Two Way System Horizontal Configuration CSC2264H User Manual
Eizo CG223W User Manual
Focal Polyglass 100 CVX User Manual
Hitachi LL 401 User Manual
HP (Hewlett Packard) HP 19 INch LCD Monitor LP1965 User Manual
JVC GR DVL355 User Manual