Baxi Potterton Gold FSB 30 HE User Manual

You can rely on  
Installation & Service Instructions  
Gold  
FSB 30 HE  
Floor Standing  
Condensing Boiler  
These instructions include the Benchmark Commissioning Checklist  
and should be left with the user for safe keeping.  
© Baxi Heating UK Ltd 2011  
Installer Notification Guidelines  
Choose Building  
Regulations Notification  
Route  
Competent Person's  
Building Control  
Self Certification Scheme  
Install and Commission this  
appliance to manufacturer's  
instructions  
Contact your relevant Local  
Authority Building Control  
(LABC) who will arrange  
an inspection or contact  
a government approved  
inspector  
Complete the  
Benchmark Checklist  
If you notify via the ‘Gas Safe  
Register’, the register will issue  
the Building Regulations  
Install and Commission this  
appliance to manufacturer's  
instructions  
certificate on members’ behalf  
Scheme Members only  
Call ‘Gas Safe Register’ on:  
0800 408 5577  
Complete the  
Benchmark Checklist  
or log onto:  
within 10 days  
You must ensure that the  
certificate number issued by  
the ‘Gas Safe Register’ is written  
onto the Benchmark Checklist  
‘Gas Safe Register’ will issue a  
Building Regulations Compliance  
Certificate to the property owner  
and inform the relevant LABC  
LABC will record the data  
and will issue a  
certificate of compliance  
3
© Baxi Heating UK Ltd 2011  
Legislation  
This company declare that no substances harmful to  
health are contained in the appliance or used during  
appliance manufacture.  
IMPORTANT - Installation, Commissioning, Service & Repair  
This appliance must be installed in accordance with the manufacturers instructions and  
the regulations in force. Read the instructions fully before installing or using the  
appliance.  
The appliance is suitable only for installation in GB and IE  
and should be installed in accordance with the rules in  
force, and only used in a suitably ventilated location.  
In GB, this must be carried out by a competent person as stated in the Gas Safety  
(Installation & Use) Regulations.  
In GB, the installation must be carried out by a Gas Safe  
Registered Installer. It must be carried out in accordance  
with the relevant requirements of the:  
Gas Safety (Installation & Use) Regulations.  
The appropriate Building Regulations either The Building  
Regulations, The Building Regulations (Scotland), Building  
Regulations (Northern Ireland).  
The Water Fittings Regulations or Water Byelaws in  
Scotland.  
The Current I.E.E. Wiring Regulations.  
Definition of competence: A person who works for a Gas Safe registered company  
and holding current certificates in the relevant ACS modules, is deemed competent.  
In IE, this must be carried out by a competent person as stated in I.S. 813 “Domestic  
Gas Installations”.  
The addition of anything that may interfere with the normal operation of the appliance  
without express written permission from the manufacturer or his agent could invalidate  
the appliance warranty. In GB this could also infringe the Gas Safety (Installation and  
Use) Regulations.  
Where no specific instructions are given, reference should  
be made to the relevant British Standard Code of Practice.  
In IE, the installation must be carried out by a competent  
Person and installed in accordance with the current edition  
of I.S. 813 Domestic Gas Installations, the current Building  
Regulations and reference should be made to the current  
ETCI rules for electrical installation.  
Warning - Check the information on the data plate is compatible with local supply  
conditions.  
All systems must be thoroughly flushed and treated  
with inhibitor (see section 6.2).  
All Gas Safe registered engineers carry an ID card with their licence number and a  
photograph. You can check your engineer is registered by telephoning  
The boiler meets the requirements of Statutory Instrument “ The Boiler (Efficiency)  
Regulations 1993 No 3083” and is deemed to meet the requirements of Directive  
92/42/EEC on the energy efficiency requirements for new hot water boilers fired with  
liquid or gaseous fuels:-  
Codes of Practice, most recent version should be used  
In GB the following Codes of Practice apply:  
Standard  
Scope  
BS 6891  
Gas Installation.  
BS 5482 Part 1  
BS 5546  
Butane & Propane Gas Installation  
Installation of hot water supplies for domestic  
purposes.  
Type test for purpose of Regulation 5 certified by:  
Notified Body 0087.  
BS EN 12828  
BS EN 12831  
BS EN 14336  
Heating systems in buildings.  
Heating systems in buildings - Calculation of load.  
Installation & commissioning of water based  
heating systems.  
Product/Production certified by:  
Notified Body 0086.  
BS 6798  
Installation of gas fired hot water boilers.  
Flues.  
Ventilation.  
Expansion vessels and ancillary equipment for  
sealed water systems.  
BS 5440 Part 1  
BS 5440 Part 2  
BS 7074  
For GB/IE only.  
BS 7593  
Treatment of water in domestic hot water  
central heating systems.  
In IE the following Codes of Practice apply:  
Standard  
Scope  
I.S. 813  
Domestic Gas Installations.  
The following standards give valuable additional information;  
BS 5546  
Installation of hot water supplies for domestic  
purposes.  
BS EN 12828  
BS EN 12831  
BS EN 14336  
Heating systems in buildings.  
Heating systems in buildings - Calculation of load.  
Installation & commissioning of water based  
heating systems.  
BS 7074  
BS 7593  
Expansion vessels and ancillary equipment for  
sealed water systems.  
Treatment of water in domestic hot water  
central heating systems.  
4
© Baxi Heating UK Ltd 2011  
Contents  
Section  
1.0  
Page  
Introduction  
6
2.0  
3.0  
4.0  
5.0  
6.0  
7.0  
8.0  
9.0  
General Layout  
7
8
Boiler Operation  
Technical Data  
9
Dimensions and Fixings  
System Details  
10  
11  
15  
20  
25  
29  
34  
36  
38  
39  
42  
49  
50  
58  
Site Requirements  
Flue Options  
Plume Displacement  
10.0 Installation  
11.0 Electrical  
12.0 Commissioning the Boiler  
13.0 Completion  
14.0 Servicing the Boiler  
15.0 Changing Components  
16.0 Short Parts List  
17.0 Fault Finding  
Benchmark Checklist  
5
© Baxi Heating UK Ltd 2011  
Facia Securing Screws  
1.0 Introduction  
1.1  
Description  
Optional Integral Timer  
Position of Label  
1. The Potterton Gold FSB 30 HE is a gas fired room  
sealed fan assisted condensing central heating boiler.  
2. The maximum output of the boiler is 30.18 kW (Non -  
Condensing) 32.61 kW (Condensing).  
3. The boiler is designed for use on Natural Gas (G20)  
only.  
4. The boiler is suitable for fully pumped open vented and  
sealed systems, providing heating and hot water.  
5. A label giving details of the model, serial number and  
Gas Council number is situated on the rear of the drop  
down facia panel (Fig. 1).  
6. The boiler data badge is positioned on the air box door  
(Fig. 2).  
Fig. 1  
7. The boiler is intended to be installed in residential /  
commercial / light industrial E.M.C. environments on a  
governed meter supply only.  
8. The boiler must be installed with one of the purpose  
designed flues such as the standard horizontal flue kit, part  
no 236921.  
Case Securing Screws  
1.2  
Important Information  
Man-made mineral fibre  
• Some component parts of this boiler (insulation pads,  
gaskets and rope seals) are manufactured from man-made  
mineral fibre.  
• Prolonged or excessive exposure to this material may  
result in some irritation to the eyes, skin or respiratory  
tract.  
It is advisable to wear gloves when handling these items.  
Irritant dust will only be released from the items if they  
are broken up or subjected to severe abrasion. In these  
instances a suitable dust mask and goggles should be  
worn.  
• Always thoroughly wash hands after installation,  
servicing or changing components.  
Air Box Door  
• When disposing of any items manufactured from man-  
made mineral fibre care must be exercised.  
If any irritation of the eyes or severe irritation of the skin  
is experienced seek medical attention.  
Fig. 2  
Data Badge  
6
© Baxi Heating UK Ltd 2011  
2.0 General Layout  
2.1  
Layout (Figs. 3, 4, 5 & 6)  
16  
1.  
Condensate Pump  
2.  
Flue Elbow (supplied in std. flue kit)  
Heat Exchanger  
3.  
4.  
Burner  
5.  
Air Box  
6.  
Fan Protection Thermostat - Black  
Fan Assembly  
7.  
Fig. 5  
2
8.  
Condensate Trap  
15  
14  
9.  
PCB Housing Assembly  
Gas Tap  
17  
10.  
11.  
12.  
13.  
14.  
15.  
16.  
17.  
18.  
19.  
18  
Gas / Air Ratio Valve  
Flow Pipe Connection  
Return Pipe Connection  
Flow Temperature Safety Thermostat - Black  
Flow Temperature Thermistor - Red  
Flow Switch (dry fire protection)  
Position of Optional Integral Timer Wiring  
Pipe Access Panel  
13  
12  
3
9
19  
Manual Air Vent  
4
6
2.2  
KIT  
110Ø Concentric Flues & Optional Extras  
PART No  
5
Standard Flue Kit 850mm (inc. elbow)  
Extended Flue Kit - 1.75M ( inc. elbow)  
Flue Plume Deflector Kit  
236921  
5111457  
248167  
248484  
Terminal Guard (suitable for use with above)  
FLUE EXTENSION KITS (110/70)  
Flue Extension 250mm  
241692  
241694  
241695  
Flue Extension 500mm  
Flue Extension 1000mm (Use two kits for 2M etc.)  
Flue Bend x 2 - 45° (Reduce overall length of flue  
by 0.5m when fitting this bend)  
241689  
241687  
Fig. 3  
Flue Bend - 93° (Reduce overall length of flue  
by 1m when fitting each bend)  
7
VERTICAL FLUE  
Vertical Flue Terminal  
242802  
1
Vertical Flue Adaptor  
5106888  
See Section 7.12 for more flue option details  
Integral Twin Channel Timer  
5117696  
8
11  
Fig. 6  
Fig. 4  
10  
7
© Baxi Heating UK Ltd 2011  
3.0 Boiler Operation  
3.1  
Boiler Operation  
Mains On.  
Condensate Pump will  
operate as necessary (3.1.9)  
1. Switched Live On: When switched live is supplied to  
the boiler and the flow temperature is less than the set  
point the sequence below commences.  
Flow  
temperature less  
than set point ?  
2. Flow Switch: After 10 seconds if the flow switch has  
made then fan pre-purge occurs. After 10 seconds if  
the flow switch has not made then anti-cycle occurs.  
3. Fan Pre-Purge: The flow switch is made and the fan  
is on while the spark generator and gas valve are off.  
After 5 seconds ignition occurs.  
YES  
System Pump  
Running and Flow  
switch made ?  
NO  
4. Ignition: The flow switch is made, fan, spark  
generator and gas valve are on. If a flame is detected  
then burner on occurs. If a flame is not detected within  
5 seconds and less than 5 ignition attempts have been  
made then fan purge occurs. If a flame is not detected  
within 5 seconds and 5 ignition attempts have been  
made then ignition lockout occurs.  
YES  
Ignition done  
and less than 5  
attempts made ?  
YES  
5 second  
Fan Pre-Purge.  
5. Burner On: The flow switch is made, fan and gas  
valve are on while the spark generator is off. Flow  
temperature is controlled by varying the fan speed (and  
thereby the gas rate) to achieve optimum operation. If  
the flow temperature is greater than the set point or  
the TRVs all shut down then fan post purge occurs.  
5 second  
Ignition Period.  
6. Fan Post Purge: The fan is on while the spark  
generator and gas valve are off. After 5 seconds if the  
TRVs are shut down then anti-cycle occurs.  
Flame Detected ?  
Ignition done and  
5 attempts made ?  
7. Anti-cycle: The fan, spark generator and gas valve  
YES  
are off.  
Burner On.  
YES  
8. Ignition Lockout: The fan, spark generator and gas  
valve are off. The boiler can only be reset by manually  
using the reset button.  
All TRVs  
shut or Flow temperature  
greater than set point ?  
Ignition  
Lockout.  
9. Condensate Pump: Condensate accumulates in a  
reservoir within the pump assembly. The pump may  
run at any time, independent of boiler operation, to  
discharge the condensate to drain.  
YES  
5 second  
Fan Post Purge.  
YES  
All TRVs  
shut down ?  
3 minute  
Anti-cycle.  
8
© Baxi Heating UK Ltd 2011  
4.0 Technical Data  
Appliance Type  
C13  
C33  
Horizontal  
Electrical Supply  
230V~ 50Hz  
Flue Terminal  
Dimensions  
Diameter - 110mm  
Projection - 150mm  
The boiler must be connected to an earthed  
supply. A permanent and switched live are  
required. The boiler has a 4 wire connection.  
Appliance Category  
CAT I  
2H  
Heat Input (Q)(Gross)  
Max  
33.76  
Min  
Connections  
Gas Supply  
Central Heating Flow  
Central Heating Return  
Condensate Drain (Pump)  
Power Consumption  
80W  
-
-
-
-
15mm  
28mm  
28mm  
10mm o.d.  
kW  
10.3  
External Fuse Rating  
3A  
Heat Output (P)  
(Non Condensing 70° C Mean Water Temp)  
Internal Fuse Rating (BS 4265)  
Max  
Min  
Outercase Dimensions  
Casing Height  
Casing Width  
Fuse  
3.15 AT (PCB)  
IPXX  
kW  
30.18  
9.2  
-
-
-
850mm  
390mm  
520mm  
Electrical Protection  
Heat Output (P)  
Casing Depth  
(Condensing 40° C Mean Water Temp)  
Max  
Water Content  
Min  
Minimum Clearances  
litres  
2.6  
(For unventilated compartments see Section 7.2)  
kW  
32.61  
10.0  
Both Sides  
Above Casing  
Above Casing  
Under fixed worktop -  
(It is recommended that any  
worktop is removable)  
Front (For Servicing)  
Front (In Operation)  
-
-
5mm  
15mm  
Static Head  
max  
Max Gas Rate (2H - G20 - 20mbar)  
(After 10 Mins)  
30 metres  
1 metre  
min  
kW Input  
m3/hr  
33.76  
3.4  
Low Head  
0.2m min  
-
-
-
25mm  
500mm  
5mm  
Inlet Pressure at Gas Valve (Natural Gas)  
System Detail  
Fully pumped open vented & sealed systems.  
No bypass required.  
Min  
18.1 mbar  
Max  
22.5 mbar  
Weights  
kg  
(see Section 10.1)  
Packaged Boiler Carton  
Packaged Flue Kit  
Installation Lift Weight  
Installed Weight (dry)  
-
-
-
-
49.5  
3.6  
37.5  
44.5  
Controls  
Injector (Natural Gas)  
boiler thermostat, safety thermostat,  
flow switch, electronic flame sensing,  
temperature protection thermostat &  
condensate blockage and level sensors  
Diameter  
6.5mm  
0.004  
CO/CO2 Ratio  
Recommended System  
Temperature Drop  
Condensing  
NO Class  
x
5
Boiler Flow Temperature (adjustable)  
20°C  
55° C to 78° C (± 5° C)  
Condensate Pump  
Head  
3 metres  
Flow Rate  
Connection  
1.8 l/min  
10mm o.d. (pipe supplied)  
Boiler Hydraulic Resistance Chart  
SEDBUK Declaration  
91  
83  
75  
66  
58  
50  
42  
33  
25  
17  
8
220  
200  
180  
160  
140  
120  
100  
80  
SAP 2005 Seasonal Efficiency  
model is 90.9%  
This value is used in the UK Governments Standard  
Assessment Procedure (SAP) for energy rating of  
dwellings. The test data from which it has been  
calculated has been certified by 0087.  
60  
40  
20  
0
10  
20  
30  
40  
Water Flow Rate (litres/min)  
9
© Baxi Heating UK Ltd 2011  
5.0 Dimensions and Fixings  
DIMENSIONS  
A 850mm  
At least  
1.5°  
B 520mm  
C 390mm  
A
D 125mm Ø Min.  
E 175mm  
F 150mm  
B
C
D
The 1.5° fall provided by the elbow  
is to allow condensate to run back to  
the boiler, for discharge through the  
condensate disposal system.  
Flue Ø 110mm  
Fig. 7  
F
E
SIDE FLUE (left and right)  
For every 1m of horizontal flue  
length, the clearance above the top  
of the flue elbow should be 27.5mm  
to incorporate the 1.5° fall in the flue  
from the terminal to the elbow. It is  
especially important to consider  
this when fitting the boiler under a  
work top !  
Y
X
At least  
1.5°  
Flue length (Y)  
up to 1m  
1m - 2m  
Clearance (X)  
27.5mm  
55mm  
2m - 3m  
82.5mm  
3m - 4m  
110mm  
Fig. 8  
10  
© Baxi Heating UK Ltd 2011  
6.0 System Details  
6.1  
Water Circulating Systems  
1. The boiler is suitable for use with open vent fully  
pumped systems and sealed systems .  
The following conditions should be observed on all  
systems:  
• The static head must not exceed 30m of water.  
• The boiler must not be used with a direct cylinder.  
• Drain cocks should be fitted to all system low points.  
• All gas and water pipes and electrical wiring must be  
installed in a way which would not restrict the servicing  
of the boiler.  
• Position isolating valves as close to circulating pump as  
possible.  
6.2  
Treatment of Water Circulating  
Systems  
1. All recirculatory water systems will be subject to  
corrosion unless they are flushed and an appropriate  
water treatment is applied. To prevent this, follow the  
guidelines given in BS 7593 “Treatment of Water in  
Domestic Hot Water Central Heating Systems” and the  
treatment manufacturers instructions.  
2. Treatment must involve the use of a proprietary  
cleanser, such as Sentinel X300 or X400, or Fernox F3  
and an inhibitor such as Sentinel X100 or Fernox MB-1.  
3. Full instructions are supplied with the products, for  
further information contact Sentinel (0800 389 4670) or  
Fernox (0870 870 0362).  
Failure to flush and add inhibitor to the system will  
invalidate the appliance warranty.  
4. It is important to check the inhibitor concentration after  
installation, system modification and at every service in  
accordance with the inhibitor manufacturers instructions.  
(Test kits are available from inhibitor stockists.)  
5. For information or advice regarding any of the above  
contact Technical Enquiries 0844 871 1555.  
11  
© Baxi Heating UK Ltd 2011  
Boiler Air  
Vent  
Copper  
0.5m  
6.0 System Details  
Copper  
0.5m  
Flow  
6.3  
Pipework  
Boiler  
Return  
Copper  
1m  
1. The sizes of flow and return pipes from the boiler  
should be determined by normal methods, according to  
the requirements of the system.  
Fig. 9  
2. The connection tails for the boiler are 28mm diameter.  
The 28mm section of the tails can be cut back to 22mm if  
required.  
22mm  
Open Vent  
45°  
3. The flow & return tails are push - fit Oring  
and clip connections within the boiler case.  
1000mm  
Min  
15mm  
Cold  
Feed  
400mm  
Min Head  
Boiler Air  
Vent  
4. A 20 °C drop in temperature across the system is  
recommended for condensing boilers. Existing radiators  
may be oversized and so allow this, but where radiator  
sizing is marginal it may be advisable to retain a system  
temperature drop of 11°C.  
150mm  
Max  
Boiler  
Pump  
5. In systems using non-metallic pipework it is necessary  
to use copper pipe for the boiler Flow and Return. The  
copper must extend at least 1 metre from the boiler and  
include any branches (Fig. 9).  
Flow  
Return  
Typical Low Head Installation  
Fig. 10  
6. This boiler does not require a bypass.  
6.4  
Low Head Installation  
22mm  
Open Vent  
45°  
1. Using a close couple arrangement the minimum head is  
as shown in the diagrams (Figs. 10 & 11) subject to the  
following conditions:  
Boiler Air  
Vent  
15mm  
Cold  
Feed  
400mm  
Min Head  
1000mm  
Min  
a) The pump being adjusted to give a 20°C drop across  
the boiler.  
b) The pump must be fitted on the flow.  
c) The pump must be fitted in accordance with the  
pump manufacturer's instructions.  
Boiler  
150mm  
Max  
d) The open vent pipe must be taken up from a tee in a  
horizontal section of the flow pipe.  
Pump  
Flow  
Return  
2. For heads below 400mm then an alternative utilising a  
combined vent and feed pipe may be connected (Fig. 12).  
This must be a minimum of 22mm diameter. It is  
recommended that an air separator is fitted when using a  
combined feed and vent pipe.  
If Conditions Require,  
This System Possible  
Fig. 11  
6.5  
Air Vents  
22mm  
Feed & Vent  
Pipe  
For correct operation of the flow switch the boiler  
and system MUST be completely vented.  
200mm  
Min  
Boiler Air  
Vent  
1. A manual air vent is fitted on the flow pipe, to enable  
complete venting of the boiler. The pipe access panel  
must be removed to do this.  
Air  
Separator  
2. Additional vents should be fitted at suitable points on  
the system as required.  
Boiler  
Pump  
Flow  
Return  
Fig. 12  
Alternative Low Head Installation  
12  
© Baxi Heating UK Ltd 2011  
Key to colours  
b
-
-
-
-
-
-
Blue  
6.0 System Details  
br  
w
o
Brown  
White  
Orange  
Grey  
6.6  
System Controls & Wiring  
gr  
g/y  
Green/Yellow  
This boiler requires a permanent live for  
operation of the condensate pump and frost  
protection.  
230V  
50Hz  
1. To comply with Part L1 of the Building Regulations the  
heating system into which the boiler is installed should  
include the following:  
L
N
E
b
Y Plan  
Diverter  
Valve  
g/y  
w
Cylinder  
Stat  
gr  
a) zone controls  
1
o
Room  
Stat  
b) timing controls  
C
2
c) boiler control interlocks  
2. Such a system needs to be fully pumped and must  
provide independent temperature and time control to  
both the heating and hot water circuits and have a boiler  
and system pump interlock.  
S/L  
E
N
P/L  
System Control  
Wiring Centre  
Boiler Connection  
(4 Core Wire)  
Timer  
3. The boiler should be controlled so that it operates on  
demand only. Where it is proposed to effect control by  
thermostatic radiator valves a room thermostat should  
also be provided to switch off the boiler when there is  
no demand for heating.  
L
N
CH on  
HW on  
HW off  
N E  
L
Pump  
Y Plan, Room Thermostat System, CH Interlocked By Room Thermostat,  
DHW Interlocked By Cylinder Thermostat  
At least the Radiator(s) near the Room Thermostat not TRV’d  
Pump run from Switched Live  
gr  
230V  
b
gr  
50Hz  
L
N
E
Motor  
Motor  
b
br  
o
S Plan  
Valve  
S Plan  
Valve  
br  
g/y  
g/y  
Cylinder  
Stat  
o
Room  
Stat  
S/L  
E
N
P/L  
System Control  
Wiring Centre  
Boiler Connection  
(4 Core Wire)  
Timer  
L
N
CH on  
HW on  
N E  
L
Pump  
S Plan, Room Thermostat System, CH Interlocked By Room Thermostat,  
DHW Interlocked By Cylinder Thermostat  
At least the Radiator(s) near the Room Thermostat not TRV’d  
Pump run from Switched Live  
13  
© Baxi Heating UK Ltd 2011  
6.0 System Details  
3 Litre  
Top Up Bottle  
(if required)  
Air  
Vent  
6.7  
Sealed Systems (Fig. 13)  
1. SAFETY VALVE - A safety valve complying with the  
requirements of BS 6750 Part 1 must be fitted close to  
the boiler on the flow pipe by means of a horizontal or  
vertically upward connection with no intervening valve  
or restrictions and should be positioned to facilitate  
testing. The valve should be pre-set and non-adjustable  
to operate at a pressure of 3 bar (45 Ibf/in2). It must be  
arranged to discharge any water or steam through a pipe  
to a safe outlet position.  
Filling  
Point  
Pressure  
Gauge  
Safety  
Valve  
Pump  
Radiator  
Circuit  
Expansion  
Vessel  
2. PRESSURE GAUGE - A pressure gauge of minimum  
range 0-4 bar (0-60 Ibf/in2) with a fill pressure indicator  
must be fitted to the system, preferably at the same  
point as the expansion vessel in an easily visible position.  
Boiler  
System Drains at  
Low Point  
Max Boiler Flow  
Temp = 82° C  
3. EXPANSION VESSEL - An expansion vessel  
complying with the requirements of BS 4814 must be  
fitted to the system by means of a connection close to  
the inlet side of the circulating pump in accordance with  
the manufacturers instructions, the connecting pipe being  
unrestricted and not less than 15mm (1/2 in) nominal size.  
The volume of the vessel should be suitable for the  
system water content and the nitrogen or air charge  
pressure should not be less than the system static head  
(See Table. 1).  
Fig. 13  
Method of determining minimum expansion  
vessel volume for sealed systems.  
Multiply Total  
Vessel Charge  
Pressure (Bar)  
Initial System  
Pressure (Bar)  
Water Content Of  
System By (Litres)  
Further details of sealed system design can be obtained  
from BS 5449 and the British Gas publication entitled  
'Specifications for Domestic Wet Central Heating  
Systems'.  
0.5  
1.0  
1.5  
2.0  
0.067  
0.112  
0.207  
0.441  
0.5  
1.0  
1.5  
4. FILLING POINT - A filling point connection on the  
central heating return pipework must be provided to  
facilitate initial filling and pressurising and also any  
subsequent water loss replacement / refilling. The sealed  
primary circuits may be filled or replenished by means of  
a temporary connection between the primary circuit and  
a supply pipe provided a Listed’ double check valve or  
some other no less effective backflow prevention device  
is permanently connected at the inlet to the circuit and  
the temporary connection is removed after use. The  
filling method adopted must be in accordance with all  
relevant water supply regulations and use approved  
equipment.  
1.0  
1.5  
2.0  
0.087  
0.152  
0.330  
1.5  
2.0  
0.125  
0.265  
Example :- System Volume = 75 litres  
Vessel Charge Pressure = 1.0 bar  
Initial System Pressure = 1.5 bar  
Then :- 75 x 0.152 = 11.4 litres  
Expansion Vessel Volume  
Table. 1  
Your attention is drawn to, for GB: Guidance G24.2 and  
recommendation R24.2 of the Water Regulations Guide.  
for IE: the current edition of I.S. 813 “Domestic Gas  
Installations”.  
NOTE  
Where a vessel of the calculated size is not obtainable then  
the next available larger size should be used.  
5. MAKE UP SYSTEM - A method of replacing water  
lost from the system should be provided either by  
means of a make up vessel of not more than 3 litres (5  
pints) capacity, mounted above the highest point of the  
system, or by re-pressurisation of the system.  
6. VENTING - A method of venting the system during  
filling and commissioning must be provided by fitting  
automatic air vents or by venting manually.  
Double  
Check  
Valve  
7. HOT WATER STORAGE - The hot water storage  
vessel must be of the indirect coil type.  
Stop  
Valve  
Stop  
Valve  
8. COMPONENTS - All components used in the system  
must be suitable for operation at 110°C (230°F) and at  
the pressure allowed by the safety valve.  
Mains  
Inlet  
Temporary  
Hose  
CH  
Return  
Fig. 14  
14  
© Baxi Heating UK Ltd 2011  
7.0 Site Requirements  
7.1  
Location  
NOTE: Due to the high efficiency of the boiler a  
plume of water vapour will be discharged from the  
flue. This should be taken into account when siting  
the flue terminal.  
1. The boiler must be fitted on a suitable flat and level  
surface capable of supporting the weight. Any wall behind  
the boiler must be at 90° to the floor to allow case top  
cover to fit correctly.  
Zone 2  
Window  
2. The flue must pass through an outside wall or roof and  
discharge to atmosphere in a position permitting  
satisfactory removal of combustion products and  
providing an adequate air supply.  
Recess  
Zone 1  
Zone 0  
Zone 2  
3. The boiler should be fitted within the building unless  
otherwise protected by a suitable enclosure i.e. garage or  
outhouse.  
0.6 m  
Window  
Recess  
4. The boiler incorporates a frost protection device. This  
will only protect the boiler. To ensure protection of the  
system pipework and components it is recommended to  
incorporate an appropriate device within the system  
controls.  
Zone 2  
5. If the boiler is fitted in a room containing a bath or  
shower, it can only be fitted in Zone 3, (Figs. A & B  
shows zone dimensions for a bathtub. For other  
examples refer to the Current I.E.E. Wiring Regulations).  
Reference must be made to the relevant requirements:-  
In GB this is the current I.E.E. Wiring Regulations and  
Building Regulations.  
Fig. A  
In GB Only  
Ceiling  
Window Recess  
Zone 2  
Outside Zones  
In IE reference should be made to the current edition of  
I.S. 813 “Domestic Gas Installations” and the current  
ETCI rules.  
6. If the boiler is to be fitted into a building of timber  
frame construction then reference must be made to the  
current edition of Institute of Gas Engineers Publication  
IGE/UP/7 (Gas Installations in Timber Framed Housing).  
2.25 m  
Zone 1  
Zone 0  
Zone 2  
0.6 m  
7.2  
Compartment  
1. Where the boiler is installed in a cupboard or  
compartment, no air vents are required for cooling  
purposes providing that the minimum dimensions below  
are maintained.  
Fig. B  
In GB Only  
Width  
Height  
Depth  
400mm  
875mm  
525mm  
2. Any compartment should be large enough to house  
the boiler only.  
15  
© Baxi Heating UK Ltd 2011  
7.0 Site Requirements  
5mm Min  
5mm Min  
390mm  
7.3  
Clearances (Figs. 15 &16)  
15mm Min  
1. These dimensions include the necessary clearances  
around the boiler for case removal, spanner access and air  
movement. Additional clearances may be required for the  
passage of pipes around local obstructions such as joists  
running parallel to the front face of the boiler. For side flue  
installations also See Section 8.1, Figs. 20 & 21.  
(25mm if under  
non removable  
worktop)  
2. It is recommended that any worktop is removable for  
servicing access.  
7.4  
Gas Supply  
850mm  
1. Check that the information concerning the state of  
adjustment given on the data plate is compatible with local  
supply conditions.  
2. The gas installation should be in accordance with the  
relevant standards. In GB this is BS 6891. In IE this is the  
current edition of I.S. 813 “Domestic Gas Installations”.  
3. The connection to the boiler is a 15mm tail on the gas  
service cock. The tail protrudes through the boiler rear  
panel and is protected by a transit bracket which may be  
removed to aid connection.  
Fig. 15  
4. Ensure that the pipework from the meter to the boiler  
is of adequate size. (If the boiler is further than 3 metres  
from the Gas Meter 22mm pipe should be used). Do not  
use pipes of a smaller diameter than the boiler gas  
connection.  
7.5  
Electrical Supply  
1. External wiring must be correctly earthed, polarised and  
in accordance with relevant regulations/rules. In GB this is  
the current I.E.E. Wiring Regulations. In IE reference  
should be made to the current edition of ETCI rules.  
2. The mains supply is 230V ~ 50Hz fused at 3A.  
500mm Min  
NOTE: The method of connection to the electricity  
supply must facilitate complete electrical isolation of the  
appliance and system”.  
For Servicing  
Purposes  
Connection may be via a fused double-pole isolator with a  
contact separation of at least 3mm in all poles, which must  
be in an accessible position to the user and serve the  
boiler and system controls only.  
There is no method of isolating the boiler at the user  
interface.  
3. Four core cable is required to supply the boiler as a  
permanent live is necessary for the operation of the  
condensate pump and frost protection.  
520mm  
5mm Min  
Fig. 16  
In Operation  
16  
© Baxi Heating UK Ltd 2011  
7.0 Site Requirements  
Condensate Pump Flow Graph  
7.6  
Condensate Drain - General  
Failure to install the condensate discharge pipework  
correctly will affect the reliable operation of the boiler.  
4
3
2
1
1. Ensure the discharge of condensate complies with any  
national or local regulations in force.  
BS 6798 & Part H1 of the Building Regulations give further  
guidance.  
2. If any further drain pipe is required (additional to that supplied  
with the boiler), it should be run in a proprietary material  
e.g. PVC, PVC-U, ABS, PVC-C or PP.  
0
3.5  
2.5  
Flow (l/min)  
4
1.5  
3
2
3. Metal pipework is NOT suitable for use in condensate  
discharge systems.  
4. Any pipe fitted externally must be kept as short as possible to  
minimise the potential of freezing and must be insulated using  
waterproof material.  
Min. radius 100mm  
Point A’  
5. When discharging condensate into a soil stack or waste pipe  
the effects of existing plumbing must be considered.  
Gravity Drain min. fall 3°  
7.7  
Condensate Disposal  
Note: The point of discharge from  
1. This boiler incorporates an automatic pumped condensate  
system. See the graph opposite for available pump flow rates.  
the pumped length of condensate  
pipe (point A) must not be below  
the level of the pump, whether  
discharging direct into a drain or  
into an additional gravity drain.  
Max. Head  
3 metres  
2. 3.5 metres of flexible 10mm PVC pipe are supplied with the  
boiler. 0.5 metres of this length remains coiled within the boiler  
to allow removal of the pump assembly. This must not be  
uncoiled to provide extra length.  
Boiler  
3. A fitting and securing clip (Fig. B) to accept the 10mm PVC  
pipe and connect to 21.5mm overflow pipe is also supplied.  
Alternative Horizontal  
Discharge  
4. The 10mm pipe can be routed to a maximum of 3 metres  
vertically and then discharge via gravity or be routed horizontally  
(Fig. A). A combination of vertical and horizontal runs is  
permissible.  
Fig. A  
5. The pipe must be supported, either using suitably spaced clips  
or run within larger diameter pipe. When using clips take care  
not to deform the pipe.  
10mm PVC Pipe  
(8.5mm I.D.)  
6. When routing the pipe through a wall it must be suitably  
sleeved. Also the pipe must not be exposed to sources of heat,  
and should be protected in locations where it may be damaged.  
Securing Clip  
8.5mm Ø O.D.  
7. The pipe should be routed so that any sharp bends, dips and  
loops are avoided. A minimum radius of 100mm is  
recommended for any bends. No slope is necessary and air  
breaks are not required on the pumped part of the condensate  
run.  
8. If the boiler is fitted in an unheated location the entire length  
of condensate pipe should be treated as external, and run within  
insulated larger diameter pipe.  
21.5mm Ø O.D. to fit  
Overflow Pipe  
Condensate Pipe  
Direct Connect  
Fitting  
Fig. B  
17  
© Baxi Heating UK Ltd 2011  
7.0 Site Requirement  
Termination via internal discharge branch e.g  
sink waste - downstream  
7.7  
Condensate Disposal (cont.)  
Pipe must terminate  
Direct Connect Fitting  
above water level but  
below surrounding surface  
9. Ensure that the condensate can discharge freely (without  
blockage or restriction of the pipe) into the drain.  
Sink  
10. Examples are shown of condensate pipe methods of  
termination:-  
Branch of Tee to be  
± 10° from vertical  
i) via an internal discharge branch  
(e.g. sink waste) - Fig. C.  
10°  
10°  
ii) to an internal or external soil and vent pipe -  
Fig. D.  
From Boiler  
Fig. C  
iii) to a drain or gully - Fig. E. Ensure that the  
condensate can discharge freely (without  
blockage or restriction of the pipe) into the  
drain.  
iv) to a soakaway - Fig. F.  
Termination to an internal soil and vent pipe  
Direct Connect Fitting  
From Boiler  
Min. 450mm  
Fig. D  
Termination to a drain or gully  
Pipe must terminate above  
water level but below  
surrounding surface  
From Boiler  
Fig. E  
Termination to a purpose made  
soak-away  
500mm Min  
Holes in the soak-away must  
face away from the building  
From Boiler  
Fig. F  
18  
© Baxi Heating UK Ltd 2011  
7.0 Site Requirements  
Terminal Position with Minimum Distance (Fig. 17)  
(mm)  
a
A
Directly below an opening, air brick, opening  
windows, etc.  
Above an opening, air brick, opening window etc.  
Horizontally to an opening, air brick, opening window etc.  
Below gutters, soil pipes or drain pipes.  
Below eaves.  
300  
300  
300  
25  
7.8  
Flue  
a
a
B
C
NOTE: Due to the high efficiency of the boiler a plume of  
water vapour will be discharged from the flue. This should  
be taken into account when siting the flue terminal.  
D
E
F
G
H
I
25  
Below balconies or car port roof.  
From a vertical drain pipe or soil pipe.  
25  
1. The following guidelines indicate the general requirements  
for siting balanced flue terminals.  
For GB recommendations are given in BS 5440 Pt.1.  
For IE recommendations are given in the current edition of I.S.  
813 “Domestic Gas Installations”.  
25  
115  
300  
600  
1200  
600  
(i)  
(ii)  
(i)  
(ii)  
25  
From an internal or external  
corner.  
Above ground, roof or balcony level.  
J
K
From a surface or boundary line facing a terminal.  
From a terminal facing a terminal (Horizontal flue).  
From a terminal facing a terminal (Vertical flue).  
From an opening in carport (e.g. door, window)  
into the dwelling.  
L
2. If the terminal discharges onto a pathway or passageway,  
check that combustion products will not cause a nuisance and  
that the terminal will not obstruct the passageway.  
1200  
1500  
300  
M
N
Vertically from a terminal on the same wall.  
Horizontally from a terminal on the same wall.  
3. When siting the flue take into consideration the effect the  
plume of water vapour may have on neighbours .  
R
S
T
U
From adjacent wall to flue (vertical only).  
From an adjacent opening window (vertical only).  
Adjacent to windows or openings on pitched and flat roofs  
Below windows or openings on pitched roofs  
300  
1000  
600  
4. Adjacent surfaces close to the flue terminal may need  
protection from the effects of condensation. Alternatively a flue  
deflector kit (part no. 248167) is available.  
2000  
Table. 2  
a
5. For installation of the flue into an internal corner at the  
25mm dimension the flue plume deflector kit (part no. 248167)  
must be fitted.  
In addition, the terminal should be no nearer than 150 mm to an  
opening in the building fabric formed for the purpose of accommodating  
a built-in element such as a window frame. See BS 5440 Pt. 1.  
6. * Reduction to the boundary is possible down to 25mm but  
the flue plume deflector kit (part no. 248167) must be fitted.  
NOTE: The distance from a fanned draught boiler terminal  
installed parallel to a boundary may not be less than 300mm  
in accordance with the diagram below, unless the flue deflector  
kit is used (see 7.8.6 opposite)  
*
7. If a terminal is less than 2 metres above a balcony, above  
ground or above a flat roof to which people have access, then  
a suitable terminal guard must be provided.  
300 min  
Terminal  
Assembly  
*
8. If required a suitable terminal guard (part no. 248484) is  
available from Potterton for use with the flue deflector. See  
also Section 8.8.  
9. For fitting under low soffits and eaves the Plume  
Displacement Kit or Flue Deflector Kit is recommended.  
TopView Rear Flue  
IMPORTANT:  
Only ONE 25mm clearance is allowed per installation.  
• Under car ports we recommend the use of the plume  
displacement kit.  
Fig. 16a  
Property Boundary Line  
• The terminal position must ensure the safe and  
nuisance - free dispersal of combustion products.  
IMPORTANT: If fitting a Plume  
Displacement Flue Kit, the air inlet  
must be a minimum of 150mm from  
any opening windows or doors.  
T
J,K  
U
Plume  
Displacement Kit  
N
R
D
E
A
M
I
C
I
I
I
S
F
F
B
J,K  
L
A
A
I
Air Inlet  
G
H
H
Likely flue positions requiring  
a flue terminal guard  
Fig. 17  
Opening Window  
or Door  
150mm  
MIN.  
Fig. 17a  
19  
© Baxi Heating UK Ltd 2011  
8.0 Flue Options  
8.1  
Horizontal Flue Systems  
Only a flue approved with the Potterton Gold FSB HE 30  
can be used.  
(ii)  
(i)  
Concentric  
The maximum equivalent lengths are 4m (horizontal) or  
(vertical). Their lengths exclude the standard elbow and  
flue/terminal assembly (horizontal) and terminal assembly  
(vertical).  
Horizontal  
Flue System Examples  
Any additional “in line” bends in the flue system must be  
taken into consideration. Their equivalent lengths are:  
Concentric Pipes:  
45° bend  
93° bend  
0.5 m  
1.0 m  
(ii)  
(i)  
NOTE: Flue length is measured from point (i) to (ii) as  
shown.  
Plume Displacement 70/110 dia Kit  
1M Extensions, 45° & 93° bends  
are also available - see Section 9.0  
IMPORTANT: All flue systems must be securely  
supported at least once every metre. Suitable pipe  
supports are available as accessories.  
NOTE: Horizontal flue pipes should always be installed with a 1.5° fall from the  
terminal to allow condensate to run back to the boiler.  
This bend is equivalent to  
0.5 metre  
B
A
(ii)  
This bend is equivalent to  
0.5 metre  
(i)  
Total equivalent length =  
A+B+2x45°Bends  
20  
© Baxi Heating UK Ltd 2011  
Vertical Flue System  
Examples (Twin Pipe)  
8.0 Flue Options  
8.2  
Twin & Vertical Flue Systems  
Concentric  
The maximum equivalent lengths are 4m (vertical). Their  
lengths exclude the standard elbow and terminal assembly  
(vertical).  
(ii)  
(i)  
Twin Flue  
The total maximum equivalent flue length is 150m.  
NOTE: Each 1m of flue duct should be calculated as 2m.  
Any additional “in line” bends in the flue system must be  
taken into consideration. Their equivalent lengths are:  
Concentric Pipes:  
135° bend  
93° bend  
0.5 m  
1.0 m  
Twin Flue Pipe:  
135° bend (air duct)  
135° bend (flue duct)  
90° bend (air duct)  
90° bend (flue duct)  
1.3 m  
2.6 m  
4.8 m  
9.6 m  
(ii)  
(i)  
IMPORTANT: All flue systems must be securely  
supported at least once every metre. Suitable pipe  
supports are available as accessories.  
Vertical Flue  
System Examples  
Total Equivalent Length =  
A+B+C+1x90°Bend  
Roof  
Terminal  
All vertical and angled runs must be included,  
measured from the boiler adaptor (point X) to the  
joint with the flue terminal (point Y). One 91.5°  
bend or two 135° bends can be included without  
reduction of the flue length.  
The total equivalent length  
for this example is  
17.2 + 34.4 = 51.6 metres.  
If further elbows are required the flue length must  
be reduced by the following amounts:-  
(ii)  
1 metre for each 91.5° bend  
0.5 metre for each 135° bend  
AIR DUCT  
No of  
C
Equivalent  
Sub total  
Length Value  
fittings/pipes  
B
1m extension  
135°bend  
5
2
2
5.0m  
2.6m  
9.6m  
1m  
1.3m  
4.8m  
91.5°bend  
This bend is equivalent to  
1 metre  
Equivalent Length Air Duct = 17.2m  
FLUE DUCT  
A
No of  
Sub total  
Equivalent  
Length Value  
fittings/pipes  
(i)  
1m extension  
135°bend  
5
2
2
10.0m  
5.2m  
2m  
2.6m  
91.5°bend  
19.2m  
9.6m  
Equivalent Length Flue Duct = 34.4m  
21  
© Baxi Heating UK Ltd 2011  
8.0 Flue Options  
8.3  
Flue Accessories  
Key Accessory  
FLUE GROUP B  
Concentric Flue System 110mm diameter  
Size  
Code No  
B
A1  
A
Horizontal Flue Terminal  
Horizontal Flue Terminal (incl elbow)  
850mm  
243013BAX  
236921  
A1  
A
B
Flue Extension  
1000mm 241695  
500mm  
250mm  
93°  
135°  
110mm  
241694  
241692  
241687  
241689  
243014BAX  
5106888  
248167  
C
D
U
T
S
Flue Bend  
Flue Bend (pair)  
Pipe Support  
Vertical Flue Boiler Adaptor  
Flue Terminal Deflector  
E
T
K
FLUE GROUP P  
Twin Flue System 80mm diameter  
E
Flue Extension (pair)  
1000mm 246137  
500mm  
250mm  
90°  
246136  
246135  
5121560  
5121561  
242757  
5111081  
F
G
J
Flue Bend (pair)  
Flue Bend (2 pair)  
Vertical Flue Boiler Adaptor Kit  
Pipe Support (pair)  
135°  
S
W
80mm  
D
C
FLUE GROUP B,P  
Vertical Flue Kits  
K
L
M
N
Vertical Flue Terminal  
242802  
243015  
243131  
243016BAX  
Pitched Roof Flashing  
Roof Cover Plate  
Flat Roof Flashing  
25°/50°  
G
F
U,W  
M
L
N
J
22  
© Baxi Heating UK Ltd 2011  
8.0 Flue Options  
For Vertical Flues  
8.4  
For Vertical Flue Systems  
Vertical Flue  
Adaptor  
1. Undo the screws securing the blanking plate to the  
boiler top panel. Discard the plate.  
Gasket  
2. Fix the vertical adaptor and gasket to the top panel with  
the previously removed screws.  
Blank Plate  
8.5  
For Twin Flue Systems  
1. Undo the screws securing the blanking plate to the  
boiler top panel. Discard the plate.  
2. Fix both the air and flue adaptors with their gaskets  
onto the boiler top panel. Secure with screws.  
For Twin Flues  
Air Duct  
Adaptor  
Flue Duct  
Adaptor  
Gasket  
Gasket  
23  
© Baxi Heating UK Ltd 2011  
8.0 Flue Options  
8.6  
For Roof Terminals  
1. In the case of a pitched roof 25 - 50 degrees, position  
the lead tile to replace/flash over existing roof tiling. Make  
an aperture in the roof suitable for the lower tube of the  
roof terminal and ensure the integrity of the roof cover is  
maintained. The adjustable plastic collar can either be  
positioned on the lead tile or the lower tube of the roof  
terminal prior to the final positioning of the vertical flue  
through the tile. Check the collar is correctly located to suit  
required roof pitch (either 25° to 38° or 37° to 50°). From  
inside the roof adjust the flue to a vertical position and  
secure to the roof structure with the clamp supplied.  
Approx  
1425mm  
2. For flat roof installations the aluminium flashing must be  
incorporated into the roof covering and the appropriate  
aperture made in the roof decking. The vertical flue is  
lowered onto the flashing making sure the collar of the flue  
locates securely with the flashing. (A mastic seal may be  
necessary). From inside the roof, adjust the flue to a vertical  
position and secure to the roof structure with the clamp  
supplied.  
Cut the same  
amount off the  
Air Duct &  
Flue Duct  
Air Duct  
Flue Duct  
Push Fit Adaptor  
IMPORTANT: If the boiler is not fitted immediately  
after the flue system, temporary precautions must be  
taken to prevent rain entry into the room of installation.  
Any precautionary measures must be removed prior to  
commissioning the boiler.  
8.7  
Flue Dimensions  
The standard horizontal flue kit allows for flue lengths  
between 270mm (105/8”) and 800mm (32”) from elbow to  
terminal (Fig. 18).  
The maximum permissible equivalent flue length is: 4  
Flue Deflector  
metres.  
NOTE: Each additional 45° of flue bend will account  
for an equivalent flue length of 0.5m.  
Fig. 18  
eg. 45° = 0.5m,  
90° = 2 x 45° = 1m etc.  
8.8  
Terminal Guard (Fig. 19)  
Fig. 18a  
1. When codes of practice dictate the use of terminal  
guards, they can be obtained from most Plumbers’ and  
Builders’ Merchants.  
2. When ordering a terminal guard, quote the appliance  
model number.  
3. The flue terminal guard should be positioned centrally  
over the terminal and fixed as illustrated.  
8.9  
Flue Deflector (Fig. 18a)  
1. If required, push the flue deflector over the terminal end  
and rotate to the optimum angle for deflecting plume.  
Secure the deflector to the terminal with screws provided.  
Fig. 19  
24  
© Baxi Heating UK Ltd 2011  
9.0 Plume Displacement  
Plume Outlet (Peak’  
MUST be Uppermost)  
9.1  
Plume Displacement Kit (P.D.K.)  
Kit No 5121371  
Content of kit  
1
1
2
1
1
2
1
70/110 Concentric Flue  
1m 70 Dia Exhaust Flue Pipe  
Support Brackets  
0.94 metre  
93° Elbow/Plume Outlet Assembly  
Flue Trim  
ORings  
Elbow with Gasket  
1. This kit is recommended for installations where the  
condensate plume emitted from the flue may cause a nuisance  
or affect the surroundings.  
2. The terminal must be positioned outside the building with  
the outlet connection upwards.  
3. The 70Ø pipe connects to the outlet of the concentric  
terminal assembly. The elbow/plume outlet must be fitted to  
the end of the 70Ø pipe.  
NOTE: The plume outlet must always be at least 45° to  
the wall, with the peak’ uppermost to prevent rain entry  
(Figs. A & B), and be at least 2 metres above ground level.  
It must be secured as shown in Fig. C.  
The outlet must be positioned so that any condensate  
plume is directed away from adjacent surfaces.  
Fig. C  
4. It is possible to reduce or increase (with the addition of  
extensions) the length of either or both the 70/110 concentric  
and 70Ø exhaust.  
5. Standard concentric flue extension kits may be added  
between the boiler elbow and the terminal assembly.  
Outlet must be  
at least 45° from  
wall face  
‘Peak’ MUST be  
Uppermost  
45°  
45°  
6. The minimum length of the concentric flue is 100mm when  
measured from the edge of the boiler flue elbow. There is a  
further 45mm engagement into the elbow.  
IMPORTANT: The maximum equivalent length of  
concentric flue is:- 4 metres  
Additional elbows may be fitted in the concentric flue, but  
the equivalent length must be reduced by 1 metre (93°  
elbow) or 0.5 metres (45° elbow).  
7. 70Ø 1 metre extensions (including support bracket), and  
additional 93° & 45° elbows are available. Any additional 93°  
& 45° elbows must be accounted for when calculating flue  
lengths. 70Ø 93° elbows are equivalent to 3.5 metres of  
straight length and 45° elbows to 1 metre.  
500mm Min.  
NOTE: Permitted positions of the plume outlet relative to  
doors, windows etc. are the same as for conventional  
concentric flues as detailed in the main Installation &  
Servicing Instructions and BS5440 Pt. 1. It is NOT  
necessary to fit a terminal guard over the air inlet or the  
plume outlet.  
Fig. A  
Outlet Connection  
upwards  
Fig. B  
25  
© Baxi Heating UK Ltd 2011  
30  
28  
26  
24  
22  
20  
30  
28  
26  
24  
22  
20  
9.0 Plume Displacement  
9.2  
Determining Permissible Lengths - P.D.K.  
18  
16  
14  
12  
10  
18  
16  
14  
12  
10  
In the graph the solid line diagonal represents the  
relationship between the concentric flue assembly (and any  
extensions) and the 70Ø exhaust (and any extensions or  
additional bends).  
8
6
4
2
0
8
6
4
2
0
Example 1 - Not Permissible  
If, for instance, a concentric length of 3.25 metres was  
required and the 70Ø exhaust needed to be 10 metres the  
graph shows that this combination would NOT be  
permissible as the intersection point would be above the  
solid diagonal line.  
0
1
2
3
4
0
1
2
3
4
Concentric 70/110 Flue (metres)  
Concentric 70/110 Flue (metres)  
Example 1  
Example 2  
Flue Lengths - Not Permissible  
Flue Lengths - OK  
30  
28  
26  
24  
22  
20  
Example 2 - Flue Lengths OK  
Where both lengths have been determined they can be  
applied to the graph to check that the installation is  
permissible. For example, if it was known that 2 metres of  
concentric flue and 4 metres of 70Ø exhaust were required,  
the values could be applied to the graph as shown in  
Example 2.. As the point of intersection of the dotted lines is  
below the solid diagonal line, the combination of lengths is  
shown to be acceptable.  
18  
16  
14  
12  
10  
Example 3 - Flue Lengths OK  
8
6
4
2
In the example shown, assume that the concentric part of  
the flue needs to be 2 metres long. Find the position of 2 on  
the horizontal axis of the graph and then project upwards to  
the solid diagonal line. This is represented by the vertical  
thick dotted line. Where this dotted line intersects with the  
solid diagonal line on the graph, project across to the vertical  
axis. As can be seen this corresponds with 14 metres.  
Therefore, the total equivalent length of the 70Ø exhaust  
can be up to 14 metres. Any elbow equivalencies must be  
accounted for i.e. 93° elbows are equal to 1 metre, each 45°  
elbow to 0.5 metres.  
0
0
1
2
3
4
Concentric 70/110 Flue (metres)  
Example 3  
Flue Lengths - OK  
Support  
Bracket  
70Ø Exhaust  
45° Elbow  
Flue Length - Worked Example  
X
In Fig. D opposite an additional 93° elbow and pair of 45°  
elbows have been included in the 70Ø exhaust.  
Also 3 straight extension pieces have been used.  
93° Elbow  
Y
1 metre Extension  
To calculate total length:-  
1 metre supplied in kit  
Length of 70Ø supplied in kit =  
3 x 1 metre Extensions =  
1 x 93° Elbow =  
1 metre  
3 metres  
1 metre  
Concentric 70/110 Flue  
(MUST be installed  
horizontally)  
2 x 45° Elbow =  
1 metre (0.5 metres each)  
Concentric Flue  
Total 70Ø =  
6 metres  
After consulting the table in Example 3 it can be determined  
that the concentric flue could be up to approximately 3.25  
metres long.  
Additional Accessories  
A - 93° Elbow  
B - 45° Elbow (Pair)  
5117381  
5117382  
C - 1 metre 60Ø Extension 5117380  
Fig. D  
26  
© Baxi Heating UK Ltd 2011  
9.0 Plume Displacement  
9.3  
General Fitting Notes - P.D.K.  
1. Cut a hole in the external wall which the horizontal  
concentric flue assembly will pass through.  
This section of the  
flue MUST be  
horizontal  
2. When completed the terminal must be at least 2 metres  
above ground level (Fig. E).  
Min. 2 metres  
3. Measure and cut to size the concentric assembly and any  
extensions that are being used.  
4. Insert the concentric assembly through the hole from  
outside the building and mark the position of the flue trim  
securing holes.  
Min. 0.3 metres  
5. Drill and plug the wall to accept the flue trim securing  
screws, and re-insert the concentric assembly through the  
wall.  
6. Connect any extensions that are being used to the  
concentric assembly. Engage the extension or concentric  
assembly in the boiler flue elbow.  
7. Fit the boiler flue elbow to the boiler top panel, ensuring  
the gasket is in place (Fig. F).  
Fig. E  
Ensure that the concentric assembly is horizontal and that  
the external air inlet is to the bottom. Any extensions  
should fall back to the boiler.  
8. Use suitable brackets to support the concentric assembly  
and any extensions, and make good inside and outside.  
Secure the flue trim to the wall.  
9. The 70Ø exhaust can now be fitted to the spigot at the  
terminal end.  
10. If it is necessary to shorten the 70Ø exhaust or any of  
the extensions, the excess material must be cut from the  
plain end of the pipe.  
Fig. F  
11. Determine the position of the 70Ø exhaust and mark  
on the wall a suitable position for the support bracket. Drill  
and plug the wall. If extensions are being used, a support  
bracket is supplied in each kit.  
12. Engage the M6 threaded part of the mounting bolt in  
the boss on the support bracket. Using the bracket for  
leverage, screw the mounting bolt into the plugged hole  
until the bracket is secure and level (Fig. G).  
13. Slacken the two screws securing the retaining strap to  
the bracket, and pivot the strap aside to allow fitting the  
70Ø exhaust.  
14. Complete the installation of the 70Ø exhaust, securing  
in the brackets. Fit the 93° elbow and plume outlet. Ensure  
the plume outlet is at least 45° to the wall and that the  
peak’ is uppermost.  
Fig. G  
15. Continue with installation and commissioning of the  
boiler.  
27  
© Baxi Heating UK Ltd 2011  
9.0 Plume Displacement  
Plume Outlet  
9.3  
General Fitting Notes - P.D.K. (cont.)  
Elbow  
16. For aesthetic purposes it is permissible to route the  
70Ø exhaust in an enclosed box, but the air inlet and  
plume outlet MUST remain in free air.  
17. It is also possible to separate the plume outlet from  
the 93° elbow to allow the flue to be installed as shown  
in Fig. H.  
18. When the plume outlet is positioned under a balcony  
or other projection (Figs. I & J) it must protrude at least  
200mm (it is not necessary to extend it further than this).  
Fig. H  
200mm Min.  
Fig. I  
200mm Min.  
Fig. J  
28  
© Baxi Heating UK Ltd 2011  
10.0 Installation  
Example  
2m  
Edge of Boiler  
125mm  
Check Site Requirements before commencing.  
EXAMPLE: If the boiler is 2 metres  
away from corner of wall the flue  
duct hole will be 55mm higher than  
the horizontal side flue centre line.  
This will maintain an approx. 1.5°  
backfall to the boiler. It is especially  
important to consider this when  
fitting the boiler under a work top !  
10.1  
Initial Preparation & Installation  
Example  
V = 55mm  
1. Remove the outer carton.  
2. For the boiler to operate correctly it must be level  
in both planes. Place the fixing template in the  
proposed boiler position ensuring that it is level.  
Horizontal  
Side Flue  
Centre Line  
3. Mark the centre of the flue hole (rear exit).  
For side exit: project the horizontal side flue centre  
line into the corner of the room and along the wall to  
where the flue hole will be drilled. (Fig. 20).  
Centre  
Hole  
Wall Thickness  
up to 227mm  
Flue Hole ø  
125mm core drill  
150mm core drill  
175mm core drill  
The diagram (Fig. 21) shows the dimensions required  
to ensure any horizontal flue is installed with the  
correct fall to the boiler. Mark the offset (V) dimension  
and if required, mark the position of the gas, water and  
condensate pipes. Remove the template.  
up to 750mm  
up to 1200mm  
Template  
Fig. 20  
4. Cut the hole for the flue (minimum diameter  
125mm, see table (Fig. 20) for wall thicknesses and flue  
hole diameters).  
Backfall to the boiler, ie. 2m flue offset (V) position 55mm  
Flue Duct Hole  
OffsetV (mm)  
13.5  
27.5  
55  
82.5  
110 (mm)  
5. Complete any pipework and wiring that will be  
inaccessible once the boiler is in position.  
1.5°  
V
6. Undo the securing screws and remove the facia,  
front door panel and top panel (see Figs. 1 & 2 on  
page 6). Remove the securing screw and disengage the  
pipe access panel.  
0.5  
1.0  
2.0  
3.0  
10.2  
Making the Water Connections  
4.0  
(metres)  
1. If desired the flow and return tails supplied with the  
boiler can be fitted at this stage and secured with the  
spring clips. The flow and return connections are  
identified on the boiler rear panel. The flow pipe  
incorporates a manual air vent.  
Fig. 21  
2. Note that the seal is made by use of an Oring,  
therefore some pipe movement will be evident even  
though a water tight seal has been achieved. Excessive  
force could result in damage to the connection.  
3. Make all soldered joints before connecting the tails  
to the boiler to avoid damaging the O rings.  
4. Refit the pipe access panel.  
10.3  
Making the Gas Connection  
1. The connection to the boiler is a 15mm tail on the  
gas service cock. The tail protrudes through the boiler  
rear panel and is protected by a transit bracket which  
may be removed to aid connection (see Fig. 22).  
Flow  
Tail  
Hole for  
Electrical  
Cable  
Return  
Tail  
2. If solder joints are being used for the gas connection,  
remove the gas tap from the valve as excessive heat  
may damage the O ring seal.  
Hole for  
Transit  
Bracket  
Condensate  
Drain Outlet  
10.4  
Priming the Condensate Trap  
1. Using a funnel and tube, carefully pour  
Gas  
approximately 1 cupful (250ml) of tap water into the  
flue products exhaust at the terminal or flue elbow  
sampling point to ensure a seal is made in the trap.  
Connection  
Fig. 22  
29  
© Baxi Heating UK Ltd 2011  
10.0 Installation  
Wall Thickness  
10.5  
Fitting the Standard Flue  
IMPORTANT: The flue should always be installed  
with at least 1.5° fall from terminal to elbow, to  
allow condensate to run back to the boiler.  
At least  
1.5°  
1. The standard flue is suitable for lengths 270mm  
minimum to 800mm maximum (measured from the  
edge of the flue elbow outlet).  
Rear Flue: maximum wall thickness - 575mm  
Side Flue: maximum wall thickness - 535mm  
2. For rear exit - measure the wall thickness  
(Fig. 26) and to this dimension add 270mm. This  
dimension to be known as (X).  
i.e. (X) = wall thickness + 270  
3. Take the flue and mark off (X) from the terminal end  
as indicated in the diagram (Fig. 27).  
4. For side exit - measure the distance from the edge  
of the boiler case to the inner face of the wall (Fig. 26)  
and to this dimension add the wall thickness + 280mm.  
This dimension to be known as (Z).  
i.e. (Z) = case to wall + wall thickness + 280  
5. Take the flue and mark off (Z) from the terminal end  
as indicated (Fig. 27).  
Edge of Boiler Case to Wall  
Wall Thickness  
Before cutting check your dimensions !  
6. The flue tubes are fixed together. Cut through both  
tubes whilst resting the flue on the semi-circular packing  
pieces. Deburr both tube ends.  
Fig. 26  
NOTE: When cutting ensure the cut does not  
interfere with the inner flue support bracket  
(Fig. 27a).  
(Z) = Side Exit  
(X) = Rear Exit  
Waste  
Flue  
Fig. 27  
Inner Flue Support Bracket  
Fig. 27a  
30  
© Baxi Heating UK Ltd 2011  
10.0 Installation  
10.5  
Fitting the Standard Flue (Cont)  
Inner Flue Support Bracket  
7. Ensure the inner flue support bracket is positioned  
in the flue (Fig. 28).  
8. Engage the flue into the flue elbow using soap  
solution to ease the engagement, ensuring the flue  
terminal is positioned as shown (Fig. 29).  
Fig. 28  
9. Place the gasket over the flue exit on the boiler.  
10. Slide the flue assembly through the hole in the wall.  
Flue  
11. Engage the elbow on to the flue connection on top  
of the boiler. Secure with the four screws supplied in  
the kit.  
12. Make good between the wall and air duct outside  
the building ensuring the 3° drop between the terminal  
and elbow.  
Flue Elbow  
13. The flue trim should be fitted once the installation  
is complete and the flue secure (Fig. 30). Apply a  
suitable mastic to the inside of the trim and press  
against the wall finish, making sure the brickwork is  
dust free and dry.  
Fig. 29  
14. If necessary fit a flue plume deflector kit and/or  
terminal guard (see Sections 7.6 & 8.8).  
Gasket  
Fig. 30  
Flue Trim  
Shaded Areas indicate  
Recommended Handling  
Points  
31  
© Baxi Heating UK Ltd 2011  
Min. radius 100mm  
Point A’  
10.0 Installation  
Gravity Drain min. fall 3°  
Note: The point of discharge from  
10.6  
Making the Condensate Drain  
Connection  
the pumped length of condensate  
pipe (point A) must not be below  
the level of the pump, whether  
discharging direct into a drain or  
into an additional gravity drain.  
Max. Head  
3 metres  
Boiler  
1. 3.5 metres of flexible 10mm PVC pipe are supplied  
with the boiler, ready connected to the pump. 0.5  
metres of this length remains coiled within the boiler  
to allow removal of the pump assembly. This must not  
be uncoiled to provide extra length.  
Alternative Horizontal  
Discharge  
2. A fitting and securing clip (Fig. B) to accept the  
10mm PVC pipe and connect to 21.5mm overflow  
pipe is also supplied. When using this fitting to connect  
to a 21.5mm overflow tee piece the branch must be  
vertical ± 10° (Fig. C).  
Fig. A  
10mm PVC Pipe  
(8.5mm I.D.)  
Condensate Pipe  
Direct Connect  
Fitting  
3. Feed the pipe through the grommet in the rear  
panel and connect to the drain system.  
Securing Clip  
4. The 10mm pipe can be routed to a maximum of 3  
metres vertically and then discharge via gravity or be  
routed horizontally (Fig. A). A combination of vertical  
and horizontal runs is permissible.  
8.5mm Ø O.D.  
21.5mm Ø O.D. to fit  
Overflow Pipe  
Fig. B  
5. The pipe must be supported, either using suitably  
spaced clips or run within larger diameter pipe. When  
using clips take care not to deform the pipe.  
Termination via internal discharge branch e.g  
sink waste - downstream  
Pipe must terminate  
Direct Connect Fitting  
Branch of Tee to be  
± 10° from vertical  
above water level but  
below surrounding surface  
10°  
10°  
6. When routing the pipe through a wall it must be  
suitably sleeved. Also the pipe must not be exposed to  
sources of heat, and should be protected in locations  
where it may be damaged.  
Sink  
7. The pipe should be routed so that any sharp bends,  
dips and loops are avoided. A minimum radius of  
100mm is recommended for any bends. No slope is  
necessary and air breaks are not required on the  
pumped part of the condensate run.  
From Boiler  
Fig. C  
Termination to an internal soil and vent pipe  
8. If the boiler is fitted in an unheated location the  
entire length of condensate pipe should be treated as  
external, and run within insulated larger diameter pipe.  
Direct Connect Fitting  
9. Ensure that the condensate can discharge freely  
(without blockage or restriction of the pipe) into the  
drain.  
From Boiler  
Min. 450mm  
Fig. D  
10. Examples are shown of condensate pipe methods  
of termination:-  
Termination to a drain or gully  
i) via an internal discharge branch  
(e.g. sink waste) - Fig. B.  
Pipe must terminate above  
water level but below  
surrounding surface  
ii) to an internal or external soil and vent  
pipe - Fig. C.  
Termination to a purpose made  
soak-away  
iii) to a drain or gully - Fig. D. Ensure that  
the condensate can discharge freely  
(without blockage or restriction of the  
pipe) into the drain.  
From Boiler  
500mm Min  
Fig. E  
iv) to a soakaway - Fig. E.  
From Boiler  
Holes in the soak-  
away must face away  
from the building  
Fig. F  
32  
© Baxi Heating UK Ltd 2011  
10.0 Installation  
10.7  
Making The Electrical Connections  
W ARN IN G: T his boile r m ust be e ar t he d  
IMPORTANT: Four core cable is required to supply the  
boiler as a permanent live is necessary for the operation  
of the condensate pump and frost protection.  
1. The electrical connections are on the right hand side of the  
boiler. Depending upon the nature of the installation it may  
be preferable to wire up to the boiler first before  
manoeuvering into position.  
2. Undo the two screws securing the cable clamp and place  
to one side (Fig. 31).  
3. Route the incoming electrical cable(s) from the system  
control wiring centre through the grommet in rear of the  
boiler and the grommet in the support bracket. This will  
prevent damage to the cable(s).  
4. Lay the cable through the cable clamp to gauge the length  
of wire required when it is connected to the 4-way terminal  
block.  
5. Connect the (S/L), ( ), (N) and (P/L) wires to the  
4-way terminal block (Fig. 33) and refit the cable clamp  
(Fig. 31).  
Fig. 31  
Cable Clamp  
INTEGRAL PROGRAMMER  
If the optional integral programmer is being fitted it can be  
done at this stage. Consult the instructions supplied in the  
programmer kit.  
Check the electrical installation for;  
earth continuity, short circuits, resistance to earth, correct  
polarity and fuse rating.  
Fig. 32  
4-way Terminal Block  
Fig. 33  
S/L  
N
P/L  
Wiring from System  
Controls  
S/L Switched Live  
Earth  
Neutral  
N
Permanent Live  
P/L  
33  
© Baxi Heating UK Ltd 2011  
11.0 Electrical  
11.1  
Schematic Wiring Diagram  
Condensate Removal System  
Condensate Pump  
Condensate  
Level Switch  
Condensate  
Over-Level Switch  
Fan  
Overheat  
Thermostat  
Condensate  
Trap  
N
L
g/y  
CH  
Flow  
Switch  
bk  
325Vdc  
DC Fan  
bk  
Spark  
Electrode Detection  
Electrode  
Flame  
Flow  
gy  
Gas  
Valve  
Thermistor  
w
Flow  
Overheat  
Thermostat  
w
gy  
gy  
gy  
bk  
r
g/y  
r
b
r
bk  
br  
r
w
b
g
br  
w
g/y  
op  
PCB  
b
br  
Optional InternalTimer  
g/y  
o
Electrical  
Filter  
Earths not shown to aid  
clarity of diagram  
o
y
v
b
br  
Boiler Connection  
(4 Core Cable)  
P/L  
S/L  
N
Key To Wiring Colours  
b - Blue  
r
- Red  
bk - Black  
w - White  
br - Brown  
gy - Grey  
o - Orange  
g - Green  
g/y- Green/Yellow  
op - Opaque  
y - Yellow  
v - Violet  
34  
© Baxi Heating UK Ltd 2011  
11.0 Electrical  
11.2  
Illustrated Wiring Diagram  
P/L  
br  
N
S/L  
Flow  
Thermistor  
b
g/y  
r
g/y  
r
CH  
Flow Switch  
Electrical  
Filter  
g/y  
br  
Spark  
Electrode  
b
gy  
Flame  
Detection  
Electrode  
gy  
o
Main  
PCB  
g/y  
w
Layout of PCB Pins  
op  
CondensateTrap  
w
br  
g
r
bk  
GasValve  
w
r
bk  
gy  
g/y  
b
gy  
br  
bk  
Fan Overheat  
Thermostat  
b
w
bk  
Fan  
Flow Overheat  
Thermostat  
g/y  
Wiring Key  
b
- Blue  
bk - Black  
br - Brown  
r
- Red  
w
- White  
g/y - Green/Yellow  
- Green  
g
gy - Grey  
op - Opaque  
y
- Yellow  
35  
© Baxi Heating UK Ltd 2011  
12.0 Commissioning the Boiler  
12.1  
Commissioning the Boiler  
W ARN IN G: T he PCB Cont r ol and Fan Asse m bly  
ar e 325 Vdc. Isolat e at supply be for e acce ss.  
1. Reference should be made to BS:EN 12828 & 14336 when  
commissioning the boiler.  
Flue Sampling Point  
2. At the time of commissioning, complete all relevant sections  
of the Benchmark Checklist at the rear of this publications.  
Manual Air Vent  
3. Flush the whole system using a suitable flushing agent (see  
Section 6.2) and vent the radiators. Check for water leaks.  
Gas Service  
Cock  
4. Refill the system with inhibitor following the inhibitor  
manufacturers instructions and BS 7593 Code of Practice for  
Treatment of Water in Domestic Hot Water Central Heating  
Systems (see Section 6.2).  
5. Complete the label supplied with the inhibitor and attach to  
the inside of the boiler case. Detail of system treatment should  
be added for future reference.  
Fig. 35  
Open  
Fig. 34  
6. Turn the gas supply on and purge according to in GB BS 6891  
and in IE I.S. 813 “Domestic Gas Installations”.  
7. Turn the gas service cock anticlockwise to the ON position  
and check for gas tightness up to the gas valve (Fig. 34). Turn the  
power to the boiler ON.  
DO NOT check gas pressure here  
IMPORTANT: The combustion for this appliance has been  
checked, adjusted and preset at the factory for operation on  
the gas type specified on the appliance data plate. No  
measurement of the combustion is necessary. Do not adjust  
the air/gas ratio valve.  
Fig. 36  
8. Having checked:  
• That the boiler has been installed in accordance with  
these instructions.  
Inlet Gas Pressure Test Point  
The integrity of the flue system and the flue seals.  
The integrity of the boiler combustion circuit and the  
relevant seals.  
Turn the Central Heating Control Knob clockwise  
to increase or anticlockwise to decrease the  
boiler flow temperature.  
Central Heating  
Control Knob  
(No OFF Position)  
Low  
Proceed to put the boiler into operation as follows:  
High  
The Reset Button should extinguish the  
Flame Failure Light and restore normal  
operation.  
Reset Button  
12.2  
Priming the Condensate Pump  
Reset  
1. Using a funnel and tube, carefully pour approximately 1litre of  
tap water into the flue products exhaust at the terminal or flue  
elbow sampling point to fill the trap and allow the condensate  
pump reservoir to fill.  
This indicates that there is electricity to the Boiler.  
Mains On  
(Green Light)  
This indicates that the Burner has fired up  
and is heating your system.  
Burner On  
(Green Light)  
If Flame Failure Light is ON. Press the Reset  
Button. If Flame Failure occurs persistently  
consult your Installer or Service Engineer.  
Flame Failure  
(Red Light)  
2. Continue filling with water until the condensate pump  
operates.  
This indicates that the Condensate Pump is running.  
The pump ONLY runs when the condensate reservoir is full.  
Condensate Pump  
(Green Light)  
3. Check that the condensate drain pipework is not leaking and  
that it is discharging correctly to drain.  
4. See Fig. 36a for operation of LEDs on boiler facia.  
Fig. 36a  
36  
© Baxi Heating UK Ltd 2011  
12.0 Commissioning the Boiler  
12.3  
Check the Operational (Working) Gas  
Inlet Pressure  
1. Ensure that all controls are calling for heat and  
maximum load is applied to the system.  
2. With the boiler operating in the maximum rate  
condition check that the operational (working) gas  
pressure at the inlet gas pressure test point is in  
accordance with B.S. 6798 & B.S. 6891.  
3. Ensure that this inlet pressure can be obtained with  
all other gas appliances in the property working.  
Measure the Gas Rate  
4. With any other appliances & pilot lights turned OFF  
the gas rate can be measured. It should be as shown in  
Section 4.0 Technical Data.  
DO NOT check gas pressure here  
5. Carefully read and complete all sections of the  
Benchmark Commissioning Checklist at the rear of this  
publication that are relevant to the boiler and  
installation. These details will be required in the event of  
any warranty work. The publication must be handed to  
the user for safe keeping and each subsequent regular  
service visit recorded.  
Fig. 36b  
6. For IE, it is necessary to complete a “Declaration of  
Conformityto indicate compliance with I.S. 813. An  
example of this is given in I.S. 813 “Domestic Gas  
Installations”. This is in addition to the Benchmark  
Commissioning Checklist.  
Inlet Gas Pressure Test Point  
37  
© Baxi Heating UK Ltd 2011  
13.0 Completion  
13.1  
Fitting The Case Panels & Facia  
1. Refit the case top panel and front door, securing with  
the screws previously removed (Fig.37).  
2. Locate the facia panel and secure with the screws  
previously removed (Fig. 38).  
3. The “Important Ventilation Information” label can be  
removed unless the boiler is installed in an unventilated  
compartment.  
13.2  
‘Benchmark’ Checklist  
1. Carefully read and complete all sections of the  
Benchmark Commissioning Checklist at the rear of this  
publication that are relevant to the boiler and  
installation. These details will be required in the event  
of any warranty work. The publication must be handed  
to the user for safe keeping and each subsequent  
regular service visit recorded.  
Outercase Securing  
Screws  
2. For IE, it is necessary to complete a “Declaration of  
Conformityto indicate compliance to I.S. 813. An  
example of this is given in I.S. 813 “Domestic Gas  
Installations”. This is in addition to the Benchmark  
Commissioning Checklist.  
Fig. 37  
13.3  
Handover  
1. Instruct the user in the operation of the boiler and  
system controls. Hand over the Users Operating,  
Installation and Servicing Instructions, giving advice on  
the necessity of regular servicing.  
2. Demonstrate to the user the action required if a gas  
leak occurs or is suspected. Show them how to turn off  
the gas supply at the meter control, and advise them  
not to operate electric light or power switches, and to  
ventilate the property.  
3. Show the user the location of the system control  
isolation switch, and demonstrate its operation.  
4. Advise the user that they may observe a plume of  
vapour from the flue terminal, and that it is part of the  
normal efficient operation of the boiler.  
Facia Securing Screws  
Fig. 38  
38  
© Baxi Heating UK Ltd 2011  
14.0 Servicing the Boiler  
14.1  
Annual Servicing  
W ARN IN G: T he PCB Cont r ol and Fan  
Asse m bly ar e 325 Vdc. Isolat e syst e m cont r ols  
be for e acce ss.  
IMPORTANT: When servicing ensure that both the gas and  
electrical supplies, including Switched and Permanent Live to the  
boiler are isolated before any work is started.  
The four LEDs on the facia will all be OFF.  
It is important to isolate the electrical supply at the system  
isolation switch as it is not possible to do this on the boiler itself.  
Hazardous materials are not used in the construction of this  
product, however reasonable care during service is  
recommended - see Section 1.2.  
When replacing the combustion box door after servicing it is  
essential that the retaining screws are tightened fully.  
1. For reasons of safety and economy, it is recommended that  
the boiler is serviced annually. Servicing must be performed by a  
competent person in accordance with B.S. 7967-4.  
2. After servicing, complete the relevant Service Interval Record  
section of the Benchmark Commissioning Checklist at the rear of  
this publication.  
IMPORTANT: During routine servicing, and after any  
maintenance or change of part of the combustion circuit, the  
following must be checked:-  
• The integrity of the complete flue system and the flue seals.  
• The integrity of the boiler combustion circuit and relevant  
seals as described in Section 14.2.  
• The operational gas inlet pressure as described in Section  
12.2.1 to 12.2.3 and the gas rate as described in 12.2.4.  
• The combustion performance as described in Check the  
Combustion Performance’ (14.1.4 to 14.1.6 below).  
3. Competence to carry out Checking Combustion  
Performance  
B.S. 6798 Specification for Installation & Maintenance of Gas  
Fired Boilers not exceeding 70kWadvises that:-  
• The person carrying out a combustion measurement should  
have been assessed as competent in the use of a flue gas  
analyser and the interpretation of the results.  
• The flue gas analyser used should be one meeting the  
requirements of BS7927 or BS-EN50379-3 and be calibrated  
in accordance with the analyser manufacturers’ requirements.  
• Competence can be demonstrated by satisfactory  
completion of the CPA1 ACS assessment, which covers the  
use of electronic portable combustion gas analysers in  
accordance with BS 7967, Parts 1 to 4.  
Check the Combustion Performance (CO/CO ratio)  
2
4. Set the boiler to operate at maximum rate as described in  
Section 12.2.  
5. Remove the cap from the flue sampling point, insert the  
analyser probe and obtain the CO/CO ratio. This must be  
2
less than 0.004.  
6. If the combustion reading (CO/CO ratio) is greater than  
2
this, and the integrity of the complete flue system and  
combustion circuit seals has been verified, and the inlet gas  
pressure and gas rate are satisfactory either:  
• Perform the Annual Servicing - Inspection’ (Section 14.2) &  
re-check.  
Replace the gas valve (Section 15.8) & re-check.  
39  
© Baxi Heating UK Ltd 2011  
14.0 Servicing the Boiler  
14.2  
Annual Servicing - Inspection  
W ARN IN G: T he PCB Cont r ol and Fan  
Asse m bly ar e 325 Vdc. Isolat e syst e m  
cont r ols be for e acce ss  
1. Ensure that the boiler is cool.  
2. Remove the facia and front door panel.  
3. Release the four 1/4 turn screws securing the air box door  
panel and remove the panel (Fig. 39).  
4. Disconnect the three leads from the terminals (Fig. 40).  
5. Undo the four screws securing the combustion box door  
and remove the door (Fig. 41).  
6. Visually check for debris/damage and clean or replace if  
necessary the following:  
a) Burner.  
Air Box Door Panel  
b) Heat exchanger fins.  
Fig. 39  
c) Fan compartment (Check also for condensate leaks).  
d) Insulation.  
e) Door seals-Important: Pay particular attention to  
the condition of the combustion box door seals.  
f) Electrodes.  
g) The condensate trap.  
h) The condensate pump  
i) Top of heat exchanger.  
Spark  
Sleeve  
Sensing  
Lead Terminals  
Fig. 40  
Earth  
Combustion Box  
Door Panel  
Fig. 41  
40  
© Baxi Heating UK Ltd 2011  
14.0 Servicing the Boiler  
14.2  
Annual Servicing - Inspection (Cont)  
Flue Sampling Point  
7. To clean the heat exchanger and burner proceed as  
follows:  
a) Disconnect the electrical leads to the fan component  
protection sensor (Fig. 42).  
Fig. 41a  
b) Loosen the screw retaining the gas injector pipe at  
the venturi (Fig. 42).  
c) Undo the two wing nuts to disconnect the fan  
(Fig. 42).  
d) Remove the fan and disconnect the electrical supply  
to it (Fig. 42).  
e) Remove the gas injector pipe from the gas valve  
(push-fit) (Fig. 42).  
Injector Pipe  
f) Remove the condensate trap drain plug and place a  
vessel underneath to catch the condensate (care should  
be taken as this could be hot). The condensate drain  
pipe may be removed to increase access.  
Injector Pipe Retaining  
Screw  
g) Undo the condensate trap securing nut, lock nut and  
the condensate drain pipe. Remove the condensate trap  
and disconnect the sensor leads (Fig. 43). Clean the trap  
and refit the drain plug.  
Securing Nut  
Fan  
h) Remove the two screws securing the burner and  
remove the burner. Visually inspect the internal burner  
baffle for obstruction, check seal around baffle for  
cracks/damage. Clean with a soft brush.  
Sensor  
Leads  
Protection  
Sensor Leads  
Electrical Supply  
i) Loosen the two screws retaining the heat exchanger  
support bracket and slide to the left to remove  
(Fig. 44).  
Condensate  
Trap  
Fig. 42  
Wing Nuts  
Lock Nut  
Service Drain  
Plug  
j) Remove the four screws securing the heat  
exchanger/combustion box base and withdraw the  
base.  
Trap to Condensate  
Pump Inlet Pipe  
Central Insulation Panel  
k) Lower the central insulation panel and check  
condition (Fig. 44). Replace the lower insulation pad if  
necessary.  
Fig. 43  
l) Ensure the heat exchanger fins are clear of any  
obstruction.  
Burner  
m) Check condition of all seals. Important: Pay  
particular attention to the condition of the  
combustion box door seals.  
Combustion  
Box Base  
Heat Exchanger  
Support Bracket  
n) Reassemble in reverse order and check for leaks.  
8. Check the operation of the condensate pump and  
drain pipework (see Section 10.1)  
9. Check CO/CO  
See section 4.0.  
2
ratio at flue sampling point (Fig.41a).  
Combustion Box Base  
Securing Screws  
Burner Securing  
Screws  
10. Complete the relevant Service Interval Record  
section of the Benchmark Commissioning Checklist at  
the rear of this publication and then hand it back to the  
user.  
Fig. 44  
41  
© Baxi Heating UK Ltd 2011  
15.0 Changing Components  
15.1  
Changing Components & Preparation  
W ARN IN G: T he PCB Cont r ol and Fan  
Asse m bly ar e 325 Vdc. Isolat e syst e m  
cont r ols be for e acce ss.  
IMPORTANT: Ensure that both the gas and electrical  
supplies, including Switched and Permanent Live to the  
boiler are isolated before any work is started.  
The four facia LEDs will be all OFF.  
It is important to isolate the electrical supply at the  
system isolation switch as it is not possible to do this  
on the boiler itself.  
Hazardous materials are not used in the construction of  
this product, however reasonable care is recommended  
- see Section 1.2.  
When replacing the combustion box door it is essential  
that the retaining screws are tightened fully.  
Remove the facia and front door panel.  
For the replacement of some components it will be  
necessary to drain the boiler. Proceed as follows:-  
Fig. 45  
Heat Exchanger  
Manifold  
1. Isolate the water circuit and drain the system as  
necessary. A drain point is located on the heat  
exchanger manifold at the right hand side of the boiler  
(Fig. 45) to enable the heat exchanger to be drained.  
2. Place a tube on the drain point to drain water away  
from the electrics. Turn anticlockwise to open (Fig. 45).  
Drain Point  
Tube  
3. After changing a component recommission the boiler  
where appropriate and check the inhibitor  
concentration (see Section 6.2 and 10.1).  
Electrical Connections  
Pipe Access  
Panel  
The thermistor, safety thermostat, interface PCB and  
the flow switch can be accessed after removal of the  
pipe access panel (Fig. 46).  
Flow Temperature Thermistor (Red)  
15.2  
Flow Temperature Thermistor and  
Safety Thermostat (Fig. 46)  
1. The procedure is the same for both the thermistor  
and the safety thermostat.  
Safety  
Thermostat  
(Black)  
2. Remove the pipe access panel and disconnect the  
electrical connections from the sensor.  
Fig. 46  
3. Remove the sensor from the pipe.  
4. Fit the new thermistor or safety thermostat and  
reassemble in reverse order.  
42  
© Baxi Heating UK Ltd 2011  
15.0 Changing Components  
Pipe Access  
Panel  
15.3  
Flowswitch (Fig. 47)  
1. Drain the boiler (see Section 13.1 paragraph 2 & 3).  
2. Remove the pipe access panel and remove the securing  
clip from the O ring joint between the flow pipe and the  
system. Undo screws on support bracket.  
Support Bracket  
3. Remove the securing clip from the O ring joint  
between the flow pipe and the flowswitch.  
4. Remove the two screws securing the flow switch to the  
boiler.  
5. Disconnect the inline electrical connection and remove  
the flowswitch.  
Flow Switch  
6. Fit the new flowswitch and reassemble in reverse order.  
7. Recommission the boiler and check the inhibitor  
concentration (see Section 6.2 and 10.1).  
Flow Pipe  
15.4  
Condensate Pump - Complete (Fig. 47a)  
Fig. 47  
1. Remove the pipe from the trap to the pump inlet and  
disconnect the electrical plug.  
2. Lift the pump off the support studs and ease it  
forwards. Release the snap fit clip and disconnect the  
condensate outlet pipe.  
Clip  
Over Level Switch  
3. Connect the condensate outlet pipe to the new pump  
using the new clip provided.  
4. With the new pump in place on the studs, refit the trap  
discharge pipe, ensuring the Oring is in place. Reconnect  
the electrical plug.  
5. Neatly coil the excess condensate outlet pipe adjacent  
to the pump, ensuring that it is not kinked or restricted.  
6. Check operation of the pump - See Section 10.2.  
15.5  
Condensate Pump - Level Switches  
(Fig. 47a)  
1. Remove the complete Condensate Pump as described  
in Section 13.4, and remove the cover.  
Condensate Pump  
(Cover Removed)  
Fig. 47a  
2. Disconnect the wires from the switch(es) and remove  
the retaining screws. On the Level Switch remove the  
circlip and washers connecting the plunger to the  
actuating arm.  
3. Fit the new switch(es). Align the actuating arm of the  
Level Switch with the plunger, ensuring that there is a  
washer at each side of the arm.  
Level Switch  
4. Reconnect the wires. On the Over Level Switch there  
is no connection to the lower spade terminal.  
5. Check operation of the pump - See Section 10.2.  
43  
© Baxi Heating UK Ltd 2011  
15.0 Changing Components  
15.6  
PCB (Figs. 48 & 49)  
Control  
Knob  
W ARN IN G: T he PCB Cont r ol and Fan  
Asse m bly ar e 325 Vdc. Isolat e syst e m  
cont r ols be for e acce ss.  
1. Pull the control knob off the spindle and remove the  
plastic button cover. Refit them onto the new PCB  
(Fig. 48).  
2. Remove the top right hand securing screw and swing  
out the PCB housing. Remove the PCB cover and  
disconnect the electrical plugs noting their positions  
3. Remove the screw securing the PCB to the housing.  
The PCB can be removed from the housing.  
4. Ensure that the two jumpers are fitted to the new  
PCB as shown (Fig. 49).  
Fig. 48  
PCB Housing Securing  
Screw  
5. Reconnect the plugs, fit the new PCB to the housing  
and reassemble in reverse order.  
Plastic Button  
Cover  
Hinge open  
PCB Housing  
Blue (CN11) Jumper  
Red (CN12) Jumper  
Fig. 49  
44  
© Baxi Heating UK Ltd 2011  
15.0 Changing Components  
The fan and venturi, gas valve, injector pipe,  
condensate trap, fan protection sensor, spark and  
sensing electrodes can be accessed and changed on  
the removal of the airbox door panel.  
1. Remove the airbox door panel by loosening the four  
1
/
4
turn screws (Fig. 50).  
15.7  
Spark and Sensing Electrodes  
(Fig. 51)  
1. Disconnect all three leads from tabs.  
Spark  
Earth  
-
-
-
Opaque cable  
Green/Yellow cable  
White cable  
Sensing  
2. Remove the two screws securing each of the  
electrodes to the combustion box door and remove the  
electrodes.  
3. Fit the new electrodes (and new gasket, as required)  
and reassemble in reverse order.  
Air Box Door Panel  
Fig. 50  
15.8  
Fan (Fig. 52)  
W ARN IN G: T he PCB Cont r ol and Fan  
Asse m bly ar e 325 Vdc. Isolat e syst e m  
cont r ols be for e acce ss.  
1. Loosen the screw holding the injector pipe into the  
venturi.  
2. Remove the electrical connections to the fan and  
protection sensor on the fan.  
Sensing  
Combustion  
Box Door  
Earth  
Spark  
3. Remove the wing nuts securing the fan to the base of  
the combustion box.  
Fig. 51  
4. Lower the fan and remove.  
5. If changing the fan, remove the screws securing the  
venturi and fan protection sensor bracket, noting the  
positions of the injector opening and sensor bracket, fix  
them to the new fan.  
Injector Pipe  
Injector  
Opening  
Screw  
6. Fit the new fan and reassemble in reverse order.  
Gasket  
Fan  
The injector pipe, condensate trap and gas valve can  
be changed after the removal of  
the fan.  
Protection  
Sensor  
Venturi  
Electrical Connections  
Fig. 52  
Electrical Connection  
Wing Nuts  
45  
© Baxi Heating UK Ltd 2011  
15.0 Changing Components  
The removal of the fan is necessary to enable the changing of  
the injector pipe, condensate trap and gas valve (see section  
13.6).  
15.9  
Injector Pipe (Fig. 53)  
1. Remove the injector pipe by pulling out from the Oring  
joint in the gas valve.  
2. Fit the new injector pipe and reassemble in reverse order.  
Injector Pipe  
15.10 Gas Valve (Fig. 53)  
IMPORTANT: After replacing the valve the CO must be  
2
checked as detailed in Section 14.1.4 to 14.1.6. Only  
change the valve if a suitable calibrated combustion  
analyser is available, operated by a competent person -  
see Section 14.1.3.  
Gas Valve  
Securing Screws  
Case Pressure Pipe  
Gasket  
1. Isolate gas supply and disconnect the gas tap by removing  
the four screws.  
2. If required remove the condensate pump to increase access  
(see Section 13.4) and undo the case pressure pipe from the  
valve.  
Boiler Side  
3. Disconnect the electrical plug from the gas valve.  
4. Remove the fan (see Section 13.6) and injector pipe.  
Aluminium  
Spacer  
‘O ring’  
Gas Valve  
Gas Tap  
5. Remove the two gas valve securing screws from inside the  
air box holding the gas valve, and remove the valve.  
6. Remove the aluminium spacer and its gasket from the gas  
valve.  
Fig. 53  
Electrical Plug  
7. Fit the aluminium spacer and its gasket to the new valve.  
8. Fit the new gas valve and reassemble in reverse order.  
NOTE: Check for gas tightness after replacing gas valve.  
9. Check the CO2 level. If the level is greater than that quoted,  
telephone the Technical Enquiries for further advice.  
Securing  
Nut  
15.11 Condensate Trap (Fig. 54)  
Sensor  
Leads  
1. Disconnect the condensate trap from the base of the heat  
exchanger.  
2. Disconnect the condensate drain ‘O ring connection from  
the condensate trap and condensate pump. For ease of access  
also remove the pump.  
Condensate  
Trap  
3. Undo the condensate trap lock nut.  
4. Remove the condensate trap from the boiler.  
5. Disconnect the sensor leads.  
Lock Nut  
Service Drain  
Plug  
6. Fit the new condensate trap and reassemble in reverse  
order. When refitting the pipe from the trap to the pump  
ensure that all seals and connections are made.  
Trap to Condensate  
Pump Inlet Pipe  
Fig. 54  
7. Prime the condensate trap (fill first chamber), check for leaks  
(see Section 8.5).  
46  
© Baxi Heating UK Ltd 2011  
15.0 Changing Components  
Combustion Box  
Door Panel  
The burner and heat exchanger can be changed after  
removal of the combustion box door. To change the  
heat exchanger, the fan and burner must be removed  
first (see section 13.6 and 13.10).  
1. Remove the combustion box door by removing the  
four securing screws (Fig. 55).  
IMPORTANT: On refitting the combustion box  
door check the condition of the combustion box  
door seals.  
15.12 Burner (Fig. 56)  
Fig. 55  
1. Remove the two screws securing the burner to the  
base of the combustion box.  
Burner  
Support  
Bracket  
2. Remove the burner carefully from the combustion  
box base.  
Return  
Connection  
3. Check the burner seal on the heat exchanger base,  
replace if necessary. Fit the new burner and reassemble  
in reverse order.  
Fig. 57  
15.13 Heat Exchanger  
Fig. 56  
1. Drain the boiler (see section 13.1 paragraph 2 & 3).  
2. Remove all components in the base of the airbox.  
Flow  
Switch  
Securing Screws  
3. Undo the screws on the support bracket. Remove  
the screws securing the flow switch and return  
connections and remove the connections (Fig. 57).  
4. Remove the screws securing the heat exchanger  
manifold and remove the manifold (Fig. 58).  
5. Ease the combustion box left hand side panel to clear  
the stud, lift the heat exchanger assembly (Fig. 59) and  
rotate the bottom upwards whilst pulling it forwards  
out of the airbox.  
6. Ensure that the heat exchanger is disengaged from  
the flue elbow and clear of the stud in the left hand side  
of the combustion box.  
Fig. 58  
7. Fit the new heat exchanger and reassemble in reverse  
order.  
Heat Exchanger  
Manifold  
8. Recommission the boiler and check the inhibitor  
concentration (see Section 6.2 and 10.1).  
Heat Exchanger  
Assembly  
Fig. 59  
47  
© Baxi Heating UK Ltd 2011  
15.0 Changing Components  
15.14 Heat Exchanger Lower Insulation Pad  
(Fig. 60)  
1. Remove all components in the base of the airbox.  
2. Remove the burner (see section 13.10).  
3. Remove the four bolts securing the combustion box  
base.  
4. Remove the combustion box base.  
5. Pull the central insulation panel down from the  
centre of the heat exchanger and remove the lower  
insulation pad.  
Central Insulation Panel  
Upper Insulation  
6. Fit the new insulation pad and reassemble in reverse  
order.  
Pad  
Lower Insulation  
Pad  
15.15 Heat Exchanger Upper Insulation Pad  
(Fig. 60)  
Fig. 60  
Burner  
1. Remove all components in the base of the airbox.  
2. Remove the burner (see section 13.10).  
Combustion  
Box Base  
3. Remove the heat exchanger (see section 13.11).  
4. Remove the four bolts securing the combustion box  
base.  
Support Bracket  
5. Remove the combustion box base.  
Combustion Box Base  
Securing Screws  
6. Pull the central insulation panel down from the  
centre of the heat exchanger.  
Burner Securing  
Screws  
7. Fit the new insulation pad and reassemble in reverse  
order.  
48  
© Baxi Heating UK Ltd 2011  
16.0 Short Parts List  
Short Parts List  
A
B
C
Key  
No.  
G.C.  
No.  
Description  
Manufacturers  
Part No.  
A
E06 058  
Flow Temperature  
Thermistor (Red)  
240670  
242459  
B
C
E06 059  
E06 060  
Flow Switch  
Safety Thermostat  
(Black)  
242235  
D
E
F
PCB  
5129147  
5109925  
241900  
Fan  
E
Gas Valve  
G
H
I
E06 085  
Viewing Window  
Condensate Trap  
Electrodes Kit  
Burner Assy  
242484  
D
5111714  
5132366  
5107430  
242497  
J
G
K
L
M
N
O
E06 097  
Heat Exchanger Assy  
Control Knob  
Condensate Pump  
Level Switch  
Over Level Switch  
5109996  
5117661  
5117591  
5117592  
F
I
H
M
K
J
N
O
L
49  
© Baxi Heating UK Ltd 2011  
17.0 Fault Finding  
NOTE: The fan is supplied with 325 Vdc.  
Fan Fault Finding should only be carried out after the  
boiler has been electrically isolated.  
Mains On  
LED Light LED Light LED Light  
(Green)  
(Green) (Red)  
Boiler On  
Lockout  
General Fault Finding should only be carried out by  
someone who is appropriately qualified.  
denotes LED flashing  
*
Lights  
Off Off Off  
Lights  
Go to Electrical Supply  
section of the fault finding  
instructions.  
Go to Thermistor section  
YES  
YES  
YES  
YES  
YES  
YES  
On  
On  
YES  
YES  
*
of the fault finding  
instructions.  
Low Electrical Supply  
Incoming Voltage less than  
180V. Check System  
Lights  
Lights  
Off On  
Off onn  
Live & Neutral Reversed  
Incoming Live and Neutral  
reversed.  
*
*
*
Controls & System Wiring.  
Otherwise contact Electricity  
Provider.  
LV Wiring Harness  
Ensure the small 8 way  
connector is securely plugged  
into the PCB. If the fault  
Lights  
On On On  
YES  
YES  
YES  
Lights  
Go to Dry-Fire  
section of the fault finding  
instructions.  
On  
* *  
persists replace wiring harness.  
Lights  
On
PCB Fault  
Replace PCB.  
*
*
*
Lights  
On Off On  
Go to Ignition Lockout section  
of the fault finding instructions.  
Lights  
On On  
PCB Fault  
Replace PCB.  
Lights  
On Off 
Go to Overheat Lockout  
section of the fault finding  
instructions.  
*
Lights  
On On
YES  
YES  
PCB Fault  
Replace PCB.  
*
Lights  
Go to Fan Lockout  
section of the fault finding  
instructions.  
On
*
*
Lights  
Go to Condensate Pump  
section of the fault finding  
instructions.  
On  
* *  
50  
© Baxi Heating UK Ltd 2011  
Lights  
Off Off Off  
17.0 Fault Finding  
ELECTRICAL SUPPLY  
No Permanent Live to  
boiler. Check Mains Fuse  
and  
NO  
240V at A ?  
A
System Wiring.  
B
YES  
No Switched Live to  
boiler. Check System  
Controls and System  
Wiring.  
NO  
NO  
240V at B ?  
N
P/L  
S/L  
YES  
Check P/L wiring from  
terminal block to PCB.  
240V at C ?  
YES  
NO  
NO  
Check S/L wiring from  
terminal block to PCB.  
240V at D ?  
YES  
Check for short circuit on  
condensate pump, fan &  
gas valve. Replace if  
PCB fuse OK ?  
shorted & replace fuse.  
YES  
Replace PCB.  
C
D
Fuse  
51  
© Baxi Heating UK Ltd 2011  
Lights  
* * On  
17.0 Fault Finding  
DRY-FIRE  
NO  
Is the  
Fill system with water and  
system full of water ?  
bleed out all air.  
YES  
NO  
Is the  
Pump or Pump Wiring  
fault.  
pump running ?  
YES  
Unplug  
5-way PCB  
connector. Is  
there continuity  
between H  
YES  
Replace PCB.  
H
Viewed from  
Wire Entry end  
NO  
Disconnect  
Flow Switch Inline  
connector. With pump running is  
there continuity across flow  
switch ?  
YES  
NO  
Wires from inline  
connector to PCB faulty.  
NO  
Remove  
Is there a  
NO  
flow switch from boiler.  
Is there a physical blockage to  
the paddle within the  
flow switch ?  
Replace Flow Switch.  
blockage in the system ?  
YES  
YES  
Remove Blockage.  
Remove Blockage.  
52  
© Baxi Heating UK Ltd 2011  
Lights  
On Off On  
17.0 Fault Finding  
IGNITION LOCKOUT  
I
Gas Valve 5-way  
Connector Plug  
Is there  
NO  
Check isolation valve and  
gas supply.  
gas at gas valve inlet ?  
J
YES  
Remove  
5-way connector  
YES  
Reset Lockout.  
Is there gas flow  
(check at meter) ?  
NO  
from gas valve. Is there 240  
Vdc between I & J  
Replace Gas Valve.  
during ignition ?  
NO  
YES  
Is  
Remove  
the larger of the  
two 6-way PCB connectors.  
Is there continuity from I to L  
& from J to K ?  
Remove Gas Valve & check  
inlet filter for blockage.  
Otherwise incorrect gas supply  
to boiler.  
NO  
there at least  
NO  
Lead from PCB to Gas  
Valve faulty.  
18mbar dynamic at gas valve  
inlet ?  
YES  
YES  
Replace PCB.  
Is  
YES  
Condensate Trap  
blocked or water on  
terminals ?  
Clear blockage and dry  
sensors.  
K
L
NO  
Is  
YES  
YES  
Check and if necessary  
change over level switch  
(see Section 13.5)  
Condensate Pump  
reservoir full ?  
6-way Connector  
NO  
Is  
Replace spark or flame  
detection probe and  
gaskets.  
spark or flame detection  
probe damaged ?  
NO  
NO  
Is  
Set spark gap to 3.5mm.  
spark gap between 3 and  
4mm ?  
YES  
Is  
Is the  
YES  
wiring from PCB  
NO  
to spark probe & flame  
detection probe OK ?  
burner blocked or  
damaged ?  
Replace PCB.  
YES  
NO  
Clean burner or replace as  
necessary.  
Rectify wiring.  
53  
© Baxi Heating UK Ltd 2011  
Lights  
On Off onn  
17.0 Fault Finding  
*
OVERHEAT LOCKOUT  
Disconnect  
NO  
black stat on flow pipe.  
When flow < 60° C is there  
continuity across stat ?  
Replace Stat.  
YES  
Reconnect stat.  
Disconnect fan stat.  
When fan temp < 60° C  
is there continuity  
across stat ?  
NO  
NO  
NO  
Replace Stat.  
YES  
Reconnect stat.  
Disconnect the larger of  
the 6-way PCB connectors.  
Is there continuity  
M
Wiring from PCB to  
thermostats faulty.  
across M ?  
YES  
6-way Connector  
Disconnect  
thermistor  
(red sensor on flow pipe).  
Is resistance between  
0.5kë & 20kë ?  
Replace thermistor.  
YES  
Is  
YES  
Replace combustion  
chamber door seal & trim  
seal.  
combustion chamber  
door seal damaged or not in  
place ?  
NO  
Replace PCB.  
54  
© Baxi Heating UK Ltd 2011  
Lights  
17.0 Fault Finding  
On
*
*
FAN LOCKOUT  
NOTE: The fan is supplied with 325 Vdc.  
Fan Fault Finding should only be carried out after the  
boiler has been electrically isolated.  
Fan  
PCB  
Connection  
Connection  
Unplug  
NO  
3-way PCB connector  
& unplug fan. Is there  
continuity from N to O &  
from P to Q ?  
O
Q
N
P
Rectify wiring.  
YES  
Fan  
PCB  
Connection  
Connection  
Unplug  
the smaller of the  
6-way PCB connector. Is there  
continuity from R to S & from T  
to U & from  
NO  
Rectify wiring.  
R
T
V
S
U
W
V to W ?  
YES  
Viewed from  
Wire Entry end  
Replace fan.  
55  
© Baxi Heating UK Ltd 2011  
17.0 Fault Finding  
Lights  
On  
On  
THERMISTOR  
*
Unplug  
thermistor,  
Is thermistor resistance between  
NO  
Replace thermistor.  
0.5kë & 20kë ?  
D
YES  
Plug in  
thermistor, leave  
NO  
Wiring from PCB to  
thermistor faulty.  
8-way connector unplugged.  
Is resistance at D between  
0.5kë & 20kë ?  
Viewed from  
Wire Entry end  
YES  
Replace PCB.  
56  
© Baxi Heating UK Ltd 2011  
17.0 Fault Finding  
CONDENSATE PUMP  
Lights  
Lights  
On Off On  
* * On  
Reset boiler  
and add approx. 1 litre  
tap water to the condensate  
system via the flue or  
sample point  
Condensate pump level switch  
activated for longer than 3  
minutes - boiler locks out.  
Boiler will try to relight 4 times  
in 5 minutes.  
Condensate pump over level  
switch activated - pump  
reservoir level too high  
resulting in ignition lockout.  
5Vdc at A ?  
No - replace PCB  
Does the  
pump motor run as  
the condensate level  
rises ?  
Mechanical fault  
NO  
NO  
on float, linkage or switch.  
Mechanical fault on pump  
or impellor.  
5Vdc at B ? No - check wiring.  
240V across C & D ?  
No - replace level  
switch  
YES  
YES  
Go to diagram for  
connections to check  
Is motor  
resistance across C & D  
approx. 40 ohms ?  
No - replace pump  
assembly  
If fault cannot be rectified  
replace level switch or  
pump assembly.  
NO  
NO  
Condensate pipe  
blocked or kinked, or outlet  
blocked or frozen  
at drain.  
Condensate pump  
outlet back check valve  
blocked or seized shut.  
As the pump motor runs  
does the condensate flow to  
drain ?  
YES  
YES  
Rectify fault, replacing pipe  
if necessary.  
If fault cannot be rectified  
replace pump assembly.  
YES  
Is  
Condensate pipe  
has high resistance - too long  
or restricted, head greater than  
3 metres.  
NO  
NO  
condensate flow  
rate at least 1.8 l/min and run  
time less than 3  
Pump motor or  
impellor worn - replace  
pump assembly  
minutes ?  
YES  
YES  
Rectify fault, replacing or  
re - routing pipe  
if necessary.  
Condensate Pump Assembly  
Condensate  
Level Switch  
Condensate Pump  
Condensate  
Motor  
Over-Level Switch  
N
L
Does  
NO  
Mechanical fault on  
float, linkage or level switch.  
After 3 mins boiler  
pump motor stop  
as level in reservoir  
falls ?  
gy  
‘C’ ‘D’  
‘B’  
will lock out.  
gy  
YES  
YES  
If fault cannot be rectified  
replace level switch or  
pump assembly.  
PCB  
Operation correct  
‘A’  
57  
© Baxi Heating UK Ltd 2011  
Failure to install and commission according to the manufacturer’s instructions and complete this Benchmark Commissioning Checklist will invalidate the warranty. This  
does not affect the customer’s statutory rights.  
If yes, and if required by the manufacturer, has a water scale reducer been fitted?  
CONDENSING BOILERS ONLY  
The condensate drain has been installed in accordance with the manufacturer’s instructions and/or BS5546/BS6798  
If the condensate pipe terminates externally has the pipe diameter been increased and weatherproof insulation fitted?  
Yes  
Yes  
58  
Service Record  
It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed.  
Service Provider  
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the  
manufacturer’s instructions.  
Always use the manufacturer’s specified spare part when replacing controls.  
Service 1  
Service 2  
Date:  
Date:  
Engineer Name:  
Engineer Name:  
Company Name:  
Telephone No.  
Company Name:  
Telephone No.  
Gas Safe Register No.  
Comments:  
Gas Safe Register No.  
Comments:  
Signature:  
Signature:  
Service 3  
Service 4  
Date:  
Date:  
Engineer Name:  
Engineer Name:  
Company Name:  
Telephone No.  
Company Name:  
Telephone No.  
Gas Safe Register No.  
Comments:  
Gas Safe Register No.  
Comments:  
Signature:  
Signature:  
Service 5  
Service 6  
Date:  
Date:  
Engineer Name:  
Engineer Name:  
Company Name:  
Telephone No.  
Company Name:  
Telephone No.  
Operative ID No.  
Comments:  
Gas Safe Register No.  
Comments:  
Signature:  
Signature:  
Service 7  
Service 8  
Date:  
Date:  
Engineer Name:  
Engineer Name:  
Company Name:  
Telephone No.  
Company Name:  
Telephone No.  
Gas Safe Register No.  
Comments:  
Gas Safe Register No.  
Comments:  
Signature:  
Signature:  
Service 9  
Service 10  
Date:  
Date:  
Engineer Name:  
Engineer Name:  
Company Name:  
Telephone No.  
Company Name:  
Telephone No.  
Gas Safe Register No.  
Comments:  
Gas Safe Register No.  
Comments:  
Signature:  
Signature:  
59  
All descriptions and illustrations provided in this leaflet have been carefully  
prepared but we reserve the right to make changes and improvements in  
our products which may affect the accuracy of the information contained in  
this leaflet. All goods are sold subject to our standard Conditions of Sale  
which are available on request.  
PO TTERTO N  
A Tr ading Divisio n o f Baxi Heat ing UK Lt d (3879156)  
Brooks House, Coventry Road, Warwick. CV34 4LL  
After Sales Service 0844 871 1560 Technical Enquiries 0844 871 1555  
e&oe  
© Baxi Heating UK Ltd 2011  
Comp No. 720896601 (6/11)  

Aiwa CDC X135 User Manual
A O Smith GWT 2500 User Manual
ARRI ULTRA 16 User Manual
Black Box Cable Box Zone 4 Seismic Cabinets, 45U User Manual
Bushnell Binoculars 20 1925 User Manual
Bushnell Binoculars 202310 User Manual
Chromalox PQ404 6 User Manual
Infiniti Car Speaker 6 1 User Manual
JVC Camcorder GR SXM530 User Manual
JVC Car Stereo System KD R205 User Manual