Ariston Boiler 47 116 17 User Manual

Installation  
Instructions  
Type C Boilers  
G.C.N: 41-116-03  
47-116-17  
Condensing  
LEAVE THESE INSTRUCTIONS  
WITH THE END-USER  
275  
Country of destination: GB  
LEGEND:  
1.3.  
OVERALL VIEW  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
9.  
Flue connector  
Heating flow temperature probe  
Mixer  
Condensate collector  
Expansion vessel  
Condensate trap (tube)  
Condensate trap  
24 MFFI  
Diverter valve  
Main circuit flow switch  
10. Domestic hot water temperature probe  
11. Control panel  
12. Gas valve  
13. Domestic hot water flow switch  
14. Drain valve  
15. Safety valve (3 bar)  
16. Secondary heat exchanger  
17. Circulation pump with automatic air release valve  
18. Heating return temperature probe  
19. Sealed combustion chamber  
20. Combustion chamber inspection hatch  
21. Fan  
22. Ignition and detection electrode  
23. Main heat exchanger (aluminium)  
24. Automatic by-pass  
25. Silencer  
2. INSTALLATION  
The technical information and instructions provided herein below are  
intended for the installer so that the unit may be installed correctly  
and safely.  
2.1.  
REFERENCE STANDARDS  
24 RFFI SYSTEM  
The installation and initial start-up of the boiler must be by a CORGI  
Approved Installer in compliance with the installation standards  
currently in effect, as well as with any and all local health and safety  
standards i.e. CORGI.  
This appliance must be installed by a competent installer in  
accordance with the current Gas Safety (installation & use)  
Regulations.  
The installation of this appliance must be in accordance with the  
relevant requirements of the current Gas Safety (installation & use)  
Regulations, the Local Building Regulations, the current I.E.E. Wiring  
Regulations, the byelaws of the local water authority, and in Scotland,  
in accordance with the Building Standards (Scotland) Regulation and  
Health and Safety document No. 635 “Electricity at work regs. 1989”.  
Installation should also comply with the following British Standard  
Codes of Practice:  
Low pressure  
pipes  
BS 6891  
BS 6798  
BS 5449  
1988  
1987  
1990  
Boilers of rated input  
not exceeding 60 kW  
Forced circulation hot  
water system  
Installation of gas hot water  
supplies for domestic purposes  
( 2nd family gases)  
Flues  
BS 5546  
BS 5440-1  
BS 5440-2  
1990  
1990  
1989  
Air supply  
FIG. 1.1  
275  
3
2.2.  
SITING THE APPLIANCE  
2.3.  
OVERALL DIMENSIONS  
The appliance may be installed in any room or indoor area, although  
particular attention is drawn to the requirements of the current I.E.E.  
Wiring Regulations, and in Scotland, the electrical provisions of the  
Building Regulations applicable in Scotland, with respect to the  
installation of the combined appliance in a room containing a bath or  
shower.  
Where a room-sealed appliance is installed in a room containing  
a bath or shower the boiler and any electrical switch or  
appliance control, utilising mains electricity should be situated  
so that it cannot be touched by a person using the bath or  
shower.  
LEGEND:  
A = Central Heating Flow (3/4”)  
B = Domestic Hot Water Outlet (1/2”)  
C = Gas Inlet (3/4”)  
D = Domestic Cold Water Inlet (1/2”)  
E = Central Heating Return (3/4”)  
F = Cylinder Flow (3/4”)  
G = Cylinder Return (3/4”)  
H = Condensate discharge  
The location must permit adequate space for servicing and air  
circulation around the appliance as indicated in paragraph 2.4.  
The location must permit the provision of an adequate flue and  
termination.  
For unusual locations special procedures may be necessary.  
BS 6798-1987 gives detailed guidance on this aspect.  
A compartment used to enclose the appliance must be designed  
specifically for this purpose. No specific ventilation requirements are  
needed for an installation within a cupboard.  
This appliance is not suitable for outdoor installation.  
The type C appliances (in which the combustion circuit, air vent  
intake and combustion chamber are air-tight with respect to the  
room in which the appliance is installed) can be installed in any  
type of room.  
There are no limitations with respect to ventilation and the volume of  
the room itself. The boiler must be installed on a solid, permanent  
wall to prevent access to the electrical parts (when live) through the  
aperture on the back frame.  
FIG. 2.1  
24 MFFI  
181  
=
=
100  
20  
65 67 67 65  
155  
(A-B-D-E)  
208  
(C)  
24 RFFI SYSTEM  
275  
4
2.4.  
MINIMUM CLEARANCES  
FIG. 2.3  
In order to allow for access to the interior of the boiler for  
maintenance purposes, the boiler must be installed in compliance  
with the clearance requirements indicated in the diagram below.  
FIG. 2.2  
IMPORTANT!  
24 MFFI  
In the event that the power supply cable must be changed, replace it  
with one with the same specifications. Make the connections to the  
terminal board located within the control panel, as follows:  
- The yellow-green wire should be connected to the terminal marked  
with the earth symbol; make sure to re-use the ferrule mounted on  
the other supply cord;  
- The blue wire should be connected to the terminal marked “N”;  
- The brown wire should be connected to the terminal marked “L.  
Note: The diagrams for the electrical system are indicated in section  
2.11.  
Warning, this appliance must be earthed.  
External wiring to the appliance must be carried out by a qualified  
technician and be in accordance with the current I.E.E. Regulations  
and applicable local regulations. The Genus range of boilers are  
~
supplied for connection to a 230 V 50 Hz supply.  
The supply must be fused at 3 A.  
24 MFFI SYSTEM  
The method of connection to the electricity supply must facilitate  
complete electrical isolation of the appliance, by the use of a fused  
double pole isolator having a contact separation of at least 3 mm in  
all poles or alternatively, by means of a 3 A fused three pin plug and  
unswitched shuttered socket outlet both complying with BS 1363.  
The point of connection to the Electricity supply must be readily  
accessible and adjacent to the appliance unless the appliance is  
installed in a bathroom when this must be sited outside the  
bathroom.  
2.7.  
GAS CONNECTION  
The local gas region contractor connects the gas meter to the  
service pipe.  
If the gas supply for the boiler serves other appliances ensure that an  
adequate supply is available both to the boiler and the other  
appliances when they are in use at the same time.  
Pipe work must be of an adequate size. Pipes of a smaller size than  
the boiler inlet connection should not be used.  
2.5.  
MOUNTING THE APPLIANCE  
Fasten the boiler in place using the template and anchors supplied  
with the unit. It is highly recommended that a spirit level be used to  
position the boiler so that it is perfectly level.  
For additional information, please consult the instructions contained  
in the connection kit and the flue kit.  
2.6.  
ELECTRICAL CONNECTION  
For safety purposes, have a competent person carefully check the  
electrical system in the property, as the manufacturer will not be held  
liable for damage caused by the failure to earth the appliance  
properly or by anomalies in the supply of power. Make sure that the  
residential electrical system is adequate for the maximum power  
absorbed by the unit, which is indicated on the rating plate. In  
addition, check that the section of cabling is appropriate for the  
power absorbed by the boiler.  
The boiler operates with alternating current, as indicated in the  
technical data table (1.2), where the maximum absorbed power is  
also indicated. Make sure that the connections for the neutral and live  
wires correspond to the indications in the diagram. The appliance  
electrical connections are situated on the reverse of the control panel  
(see the servicing manual for further information)  
275  
5
2.8.  
WATER CONNECTIONS  
FIG. 2.5  
VIEW OF THE BOILER CONNECTIONS  
24 MFFI  
Fitting the connection kit to  
the ecoGENUS 24 RFFI  
SYSTEM only.  
It will be noted that the kit has  
two connections not required  
C
for this boiler i.e. the domestic  
cold inlet “D” and the domestic  
hot water outlet “B” (see fig.  
A
B
D
E
2.4).  
I
Although the cold water main supply must be connected to the  
isolation valve for the purpose of operating the filling-loop, the  
isolation valve is NOT connected to the boiler and should be left  
in the OFF position.  
The D.H.W. outlet is capped-off on the boiler, therefore not  
requiring the isolation valve to be used.  
H
The ecoGENUS 24 RFFI SYSTEM has 2 x 3/4" B.S.P. male  
threads for the cylinder flow and return. It is recommended that 2  
x 22mm x 3/4" female iron fittings (not supplied) be used on these  
connections (using P.T.F.E. tape), before the boiler is mounted on  
the wall.  
FIG. 2.4  
24 MFFI SYSTEM  
SYSTEM DESIGN:  
This boiler is suitable only for sealed systems.  
DRAIN COCKS:  
C
These must be located in accessible positions to permit the  
draining of the whole system. The taps must be at least 15mm  
nominal size and manufactured in accordance with BS  
2870:1980.  
A
D
E
I
SAFETY VALVE DISCHARGE:  
F
G
The discharge should terminate facing downwards on the exterior  
of the building in a position where discharging (possibly boiling  
water & steam) will not create danger or nuisance, but in an easily  
visible position, and not cause damage to electrical components  
and wiring.  
H
LEGEND:  
A = Central Heating Flow  
B = Domestic Hot Water Outlet  
C = Gas Inlet  
D = Domestic Cold Water Inlet)  
E = Central Heating Return  
F = Cylinder Flow  
The discharge must not be over an entrance or a window or any  
other type of public access.  
CONDENSATE DISCHARGE:  
The condensate discharge hose from the boiler must be inserted  
by at least 50 mm into a suitable acid resistant pipe - e.g. plastic  
waste or overflow pipe. The condensate discharge pipe must have  
a continuous fall and preferably be installed and terminated within  
the building to prevent freezing.  
The discharge pipe must be terminated in a suitable position:  
i) Connecting in to an internal soil stack (at least 450 mm above  
the invert of the stack). A trap giving a water seal of at least 75  
mm must be incorporated into the pipe run , there also must  
be an air break upstream of the trap.  
ii) Connecting into the waste system of the building such as a  
washing machine or sink. The connection must be upstream of  
the washing machine/sink (If the connection is down stream of  
the waste trap then an additional trap giving a minimum water  
seal of 75 mm and an air break must be incorporated in the  
pipe run, as above.  
G = Cylinder Return  
H = Condensate discharge  
I
= Safety valve discharge  
CENTRAL HEATING  
Detailed recommendations are given in BS 6798:1987 and BS 5449-  
1:1990, the following notes are given for general guidance.  
PIPE WORK:  
Copper tubing to BS EN 1057:1996 is recommended for water  
pipes. Jointing should be either with capillary soldered or  
compression fittings.  
Where possible pipes should have a gradient to ensure air is  
carried naturally to air release points and water flows naturally to  
drain taps.  
The appliance has a built-in automatic air release valve, however  
it should be ensured as far as possible that the appliance heat  
exchanger is not a natural collecting point for air.  
Except where providing useful heat, pipes should be insulated to  
prevent heat loss and avoid freezing.  
iii) Terminating into a gully, below the grid level but above the  
water level.  
iv) Into a soakway.  
NOTE: If any condensate pipe work is to be installed externally,  
then it should be kept to a minimum and be insulated with a  
waterproof insulation and have a continuous fall.  
AIR RELEASE POINTS:  
Particular attention should be paid to pipes passing through  
ventilated spaces in roofs and under floors.  
These must be fitted at all high points where air naturally collects  
and must be sited to facilitate complete filling of the system.  
The appliance has an integral sealed expansion vessel to  
accommodate the increase of water value when the system is  
heated.  
BY-PASS:  
The appliance includes an automatic by-pass valve, which  
protects the main heat exchanger in case of reduced or  
interrupted water circulation through the heating system, due to  
the closing of thermostatic valves or cock-type valves within the  
system.  
It can accept up to 7 l (1.5 gal) of expansion water. If the heating  
circuit has an unusually high water content, calculate the total  
275  
6
expansion and add an additional sealed expansion vessel with  
adequate capacity.  
The minimum acceptable spacing from the terminal to obstructions  
and ventilation openings are specified in Fig. 2.6  
MAINS WATER FEED - CENTRAL HEATING:  
There must be no direct connection to the mains water supply  
even through a non-return valve, without the approval of the Local  
Water Authority.  
FIG. 2.6  
FILLING:  
A temporary method for initially filling the system and replacing  
lost water during servicing and initial filling (in accordance with  
Water Supply Byelaw 14), is provided as an integral part of the  
connection kit (see FIG. 2.5). The flexible hose must be removed  
once the system has been filled. The D.H.W. inlet valve on the  
connection kit has two positions, one for winter and one for the  
summer. This enables the flow-rate through the appliance to be  
adjusted so that a sensible D.H.W. temperature may be achieved  
throughout the year.  
DOMESTIC WATER  
The domestic water must be in accordance with the relevant  
recommendation of BS 5546:1990. Copper tubing to BS EN  
1057:1996 is recommended for water carrying pipe work and  
must be used for pipe work carrying drinking water.  
RESIDUAL HEAD OF THE BOILER  
TERMINAL POSITION  
mm  
A - Directly below an open window or other opening  
B - Below gutters, solid pipes or drain pipes  
C - Below eaves  
300  
75  
200  
200  
75  
D - Below balconies or car-port roof  
E - From vertical drain pipes and soil pipes  
F - From internal or external corners  
G - Above ground or below balcony level  
H - From a surface facing a terminal  
I - From a terminal facing a terminal  
J - From an opening in the car port  
(e.g. door, window) into dwelling  
300  
300  
600  
1200  
1200  
1500  
300  
K - Vertically from a terminal in the same wall  
L - Horizontally from a terminal in the same wall  
In FIG. 2.11 below, several different types of flue systems are shown.  
For additional information regarding the flue accessories, please  
consult the Flue Pipe Accessories manual.  
2.9.  
FLUE CONNECTIONS  
FLUE SYSTEM  
Exhaust Type  
Maximum Extension Diameter  
The provision for satisfactory flue termination must be  
made as described in BS 5440-1.  
The appliance must be installed so that the flue terminal is  
exposed to outdoor air.  
Exhaust/Air  
(m)  
of Pipes  
(mm)  
The terminal must not discharge into another room or  
space such as an outhouse or lean-to.  
It is important that the position of the terminal allows a  
free passage of air across it at all times.  
The terminal should be located with due regard for the  
damage or discolouration that might occur on buildings in  
the vicinity.  
In cold or humid weather water vapour may condense on  
leaving the flue terminal.  
13  
C
4
4
Ø 60/100  
Ø 60/100  
Coaxial  
Systems  
33  
B
outlet of fumes in  
chimney or exhaust flue  
The effect of such “steaming” must be considered.  
If the terminal is less than 2 metres above a balcony,  
above ground or above a flat roof to which people have  
access, then a suitable terminal guard must be fitted.  
When ordering a terminal guard, quote the appliance  
model number.  
13  
33  
43  
C , C , C  
31 (S1=S2)  
55 (S1+S2)  
54 (S2)  
Ø 80/80  
Ø 80/80  
Ø 80  
53,  
83  
C
C
Twin Pipe  
Systems  
A suitable terminal guard is available from:  
TOWER FLUE COMPONENTS  
Morley Road  
23  
B
Tonbridge  
Kent TN9 1RA  
275  
7
FIG. 2.11  
1
2.10. ACCESSORY CONNECTION  
B
To carry out the connection for the roomstat or the outdoor sensor,  
proceed as follows:  
D
C
A
2.10.1. ROOM THERMOSTAT CONNECTION  
2
1. Unscrew the screws “A” and rotate the control panel forwards;  
2. Insert the connection cable for the thermostat or the outdoor  
sensor into the cable gland “B” and open the lid of the control  
panel after having first unscrewed fastening screws “C”.  
3. Insert the connecting cable into the cable clamp “D” shown in  
the figure and fasten it.  
E
4. Remove the grommet “E” shown in the figure, make a hole in it  
and pass the connecting cable for the roomstat or the outdoor  
sensor through it.  
5a. In order to connect up the roomstat, remove the link that is  
located in the “F” terminal (marked with the initials “TA”) and  
connect the cables.  
5b. To connect up the outdoor sensor, insert the cables into the “G”  
clamp (marked with the initials “SE”).  
3
F
6. Return the grommet “E” to its initial position, then close back  
the lid and lastly return the control panel to its place.  
7
8
9
If a remote time clock is to be fitted, disconnect the integral time  
clock plug from the P.C.B.  
Using a volt-free switching time clock, connect the switching  
wires from the time clock following points 1-6 above.  
If using a time clock and room thermostat, these must be  
connected in series as per points 1-8 above.  
G
4
Note: Only a two-wire type room thermostat can be used.  
E
For details on fitting the D.H.W. probe (ecoGENUS 27  
RFFI only), please consult the separate instruction  
sheet supplied with the probe.  
An anti-frost device is built-in to the appliance’s  
electronic regulation system.  
275  
8
2.10.2. REMOTE CONTROL CONNECTION  
2.10.3. ACCESSORY CONNECTION TERMINAL BLOCK  
Refer to the illustrations in section 2.10.1.  
1. Unscrew the screws “A” and rotate the control panel forwards.  
2. Insert the connecting cables of the remote control into the cable  
gland “B” and open the lid of the control panel after having  
unscrewed the fastening screws “C”.  
3. Remove a blind grommet, make a hole in it and pass the  
connecting cable of the remote control through it.  
4. Connect the cables of the remote control to the flying lead (see  
section 2.11.) connected to position C5 on the P.C.B. (positions  
with no closed jumper).  
5. Bring the grommet back to its initial position, then close the lid  
and lastly the control panel.  
NOTE: The wiring of the Outdoor Sensor (SE) must be done by using  
2 x 0.5 mm2 cable this guarantees a maximum length of 50 m.  
The sensor must be positioned at least 2 - 2.5 m above the  
ground and where possible facing north. The sensor must not  
be exposed to direct sunlight.  
NOTE: The wiring of the RC must be done by using 2 x 0.5 mm2 cable  
this guarantees a maximum length of 500 m.  
The “BUS” cable of the RC must be wired separately from the 230  
VAC cable.  
2.10.4. UNDER FLOOR HEATING CONNECTION  
Refer to the illustrations in section 2.10.1.  
1. Unscrew the screws “A” and rotate the control panel forwards.  
2. Insert the connecting cable of the under floor heating sensor into  
the cable gland “B” and open the lid of the instrument panel  
after having unscrewed the fastening screws “C”.  
3. Remove a blind grommet, make a hole in it and insert the  
connecting cable of the under floor heating sensor through it.  
4. Remove the jumper located in the flying clamp  
5. Connect the cables of the under floor heating sensor to the flying  
clamp connected to position C6 on the P.C.B. (in place of the  
position previously occupied by the jumper).  
6. Bring the grommet back to its initial position, close the lid and  
lastly the control panel.  
2.10.5. REMOTE CONTROL TERMINAL BLOCK,  
CYLINDER PROBE AND SECONDARY OUTLET  
CONNECTIONS TO THE P.CB.  
JUMPER:  
C6 (3-11)  
(grey)  
UNDER FLOOR  
HEATING  
SENSOR  
C5 (1-2)  
(red)  
REMOTE CONTROL  
SECONDARY OUTLET  
(LPG valve,  
secondary pump)  
C7 (1-9)  
(violet)  
275  
9
The P.C.B. is fitted with 2 fuses, on the  
live and the neutral.  
2.11. ELECTRICAL DIAGRAM  
The fuse holder contains:  
- 5 x 20mm “3.15A Slow” glass fuses  
LEGEND:  
B: Control microprocessor  
A: JUMPER  
C: Flame detection jumper (under no circumstances should this  
jumper be moved from the 1-2 position)  
D: Anti-cycling device (RA)  
E: Maximum heating output regulation (PR)  
F: Soft-light regulation (RLA)  
G: Operating mode selector knob  
H: Heating temperature adjustment  
I: Domestic hot water temperature adjustment  
J: Remote control module  
K: Main microprocessor  
When needed, the P.C.B. allows the different options to be selected  
by means of a wire link.  
The boiler has the following basic arrangement:  
1 OPEN  
2 CLOSED (jumper)  
3 OPEN  
4 OPEN  
5 OPEN  
6 OPEN  
7 CLOSED  
8 OPEN (MFFI); CLOSED (SYSTEM)  
L: Relay  
NOTE: under absolutely no circumstances must jumpers 2, 7 and 8  
be removed. The opening of such contacts will lead to boiler  
malfunction.  
M: Fuses (2 x 0.54 A SLOW)  
N: Transformer (PRI: 230V-50Hz; SEK: 10V-0,8VA; SEK:10V-3,5VA;  
SEK:10V-3,5VA;)  
O: Fuses (2 x 3.15 A SLOW)  
P: Earth  
This is the factory configuration. It is recommended that this set-up  
not be changed, unless under the following particular circumstances:  
JUMPER 3:  
if the contact is closed, the Secondary Output (flying  
clamp connected to connection C7; positions 1-9)  
controls an LPG valve (optional).  
if the contact is closed, the continuous operation of  
the pump is selected. If the contact remains open, it  
has no effect and there is no change in the  
operation of the boiler.  
Q: Spark generator  
R: Connection to the main P.C.B.  
S: Comfort light  
JUMPER 4:  
T: Programming keys  
U: Comfort key  
V: Alpha-numeric display  
JUMPER 5:  
if the contact is closed, the signal transmitted by the  
connection of the secondary output clasp  
(connected to C7; positions 1-9) relates to a  
secondary pump (optional). If the contact remains  
open, the output signal controls a zone valve  
(optional).  
X: Set and reset key  
W: Connection to PC  
C1 = FAN  
1:  
2:  
3:  
4:  
5:  
6:  
“Hall” sensor power supply 12V (red)  
“Hall” sensor ground (blue)  
Not used  
JUMPER 6:  
JUMPER 7/8:  
not used  
Start of coil (black)  
7
N.I.  
I.  
8
CONFIGURATION  
“Hall” sensor input (white)  
End of coil (brown)  
N.I. Central heating only  
N.I. MFFI  
N.I.  
I.  
I.  
I.  
Not used  
C2 = POWER SUPPLY  
RFFI System  
1:  
2:  
3:  
4:  
5:  
6:  
Earth (yellow/green)  
Earth (yellow/green)  
Not connected  
Neutral (blue)  
I = inserted (contact closed)  
N.I = not inserted (contact open)  
Not connected  
Live (brown)  
NOTE: it is essential that the operations involving setting of the  
jumpers be carried out only with the device turned off.  
275  
10  
2.12. WATER CIRCUIT DIAGRAMS  
C3 = CONNECTION TO ROOMSTAT  
1:  
2:  
Input - 1  
Input - 2  
24 MFFI  
C4 = TIMER  
1:  
2:  
3:  
4:  
3 V output  
Timer ground  
Timer output  
Not connected  
C5 = REMOTE CONTROL (Bus+/Bus-)  
1:  
2:  
Input/output-1  
Input/output-2  
C6 = SENSOR CONNECTOR  
1:  
Domestic hot water flow switch (grey)  
Main circuit flow switch (grey)  
Under floor heating thermostat (grey)  
Heating flow sensor (grey)  
Heating return sensor (grey)  
Domestic hot water sensor (grey)  
Not used: jumper  
2:  
3:  
4:  
5:  
6:  
7:  
8:  
Outdoor sensor (grey)  
9:  
Domestic hot water flow switch (grey)  
Main circuit flow switch (grey)  
Under floor heating thermostat (grey)  
Flow sensor (grey)  
10:  
11:  
12:  
13:  
14:  
15:  
16:  
Heating sensor (grey)  
Domestic hot water sensor (grey)  
Not used: under floor heating  
Outdoor sensor (grey)  
C7 = EQUIPMENT CONNECTIONS  
1:  
Secondary output (optional)  
Gas valve (white)  
2:  
LEGEND:  
3:  
3-way valve neutral (white)  
Pump (white)  
1
2
3
4
5
6
7
8
9
-
-
-
-
-
-
-
-
-
Fan  
4:  
Main Heat exchanger  
Ignition/detection electrode  
Burner  
5:  
Ionisation (black)  
6:  
Not connected  
7:  
Ground  
Gas valve  
8:  
Pump earth (yellow/green)  
Secondary output (optional)  
Gas valve (brown)  
Heating return temperature probe  
Heating flow temperature probe  
Silencer  
9:  
10:  
11:  
12:  
13:  
14:  
15:  
16:  
3-way valve (domestic hot water) (brown)  
3-way valve (heating) (brown)  
Pump (brown)  
Motorised valve  
10 - Automatic by-pass  
11 - Main circuit flow switch  
12 - Domestic hot water temperature probe  
13 - Secondary heat exchanger  
14 - Domestic hot water inlet filter  
16 - Drain valve  
Not connected  
Earth  
Gas valve earth (yellow/green)  
17 - Safety valve  
18 - Pressure gauge  
19 - Circulation pump with automatic air release valve  
20 - Expansion vessel  
21 - Condensate trap inspection cap  
22 - Condensate trap  
23 - Condensate discharge tube  
24 - Condensate trap inlet  
25 - Injector  
26 - Domestic hot water flow switch  
275  
11  
3. COMMISSIONING  
24 RFFI SYSTEM  
3.1.  
INITIAL PREPARATION  
MTS (GB) Limited support the  
information pack you will find a copy of the  
initiative. Within the  
logbook. It is  
important that this is completed in the presence of your customer,  
they are shown how to us it, and it is signed by them. Please instruct  
your customer that they must have their  
logbook with them  
whenever they contact a service engineer or us.Preliminary electrical  
system checks to ensure electrical safety must be carried out by a  
competent person i.e. polarity, earth continuity, resistance to earth  
and short circuit.  
FILLING THE HEATING SYSTEM:  
Remove the panels of the case and lower the control panel (see  
section 3.2. for further information).  
Open the central heating flow and return cocks supplied with the  
connection kit.  
Unscrew the cap on the automatic air release valve one full turn  
and leave open permanently.  
Close all air release valves on the central heating system.  
Gradually open valve(s) at the filling point (filling-loop) connection  
to the central heating system until water is heard to flow, do not  
open fully.  
Open each air release tap starting with the lower point and close it  
only when clear water, free of air, is visible.  
Purge the air from the pump by unscrewing the pump plug  
and also manually rotate the pump shaft in the direction  
indicated by the pump label to ensure the pump is free.  
Close the pump plug.  
Continue filling the system until at least 1 bar registers on the  
pressure gauge.  
Inspect the system for water soundness and remedy any leaks  
discovered.  
FILLING OF THE D.H.W. SYSTEM:  
Close all hot water draw-off taps.  
Open the cold water inlet cock supplied with the connection kit.  
Open slowly each draw-off tap and close it only when clear water,  
free of bubbles, is visible  
GAS SUPPLY:  
Inspect the entire installation including the gas meter, test for  
soundness and purge, all as described in BS 6891:1988.  
Open the gas cock (supplied with the connection kit) to the  
appliance and check the gas connector on the appliance for leaks.  
LEGEND:  
1
2
3
4
5
6
7
8
9
-
-
-
-
-
-
-
-
-
Fan  
When the installation and filling are completed turn on the central  
heating system (sect. 3.4) and run it until the temperature has  
reached the boiler operating temperature.  
The system must then be immediately flushed through.  
The flushing procedure must be in line with BS 7593:1992 Code of  
practice for treatment of water in domestic hot water central heating  
systems.  
During this operation, we highly recommend the use of a central  
heating flushing detergent (Fernox Superfloc or equivalent), whose  
function is to dissolve any foreign matter that may be in the system.  
Substances different from these could create serious problems  
to the pump or other components.  
The use of an inhibitor in the system such as Fernox MB-1 or  
equivalent is strongly recommended to prevent corrosion (sludge)  
damaging the boiler and system.  
Main Heat exchanger  
Ignition/detection electrode  
Burner  
Gas valve  
Heating return temperature probe  
Heating flow temperature probe  
Silencer  
Motorised valve  
10 - Automatic by-pass  
11 - Main circuit flow switch  
12 - Non-return valve (integral to Jig Kit)  
13 - Filling loop (integral to Jig Kit)  
14 - Indirect cylinder expansion vessel  
15 - Expansion relief valve  
16 - Drain valve  
Failure to carry out this procedure may invalidate the appliance  
warranty.  
17 - Safety valve (3 bar)  
18 - Pressure gauge  
19 - Circulation pump with automatic air release valve  
20 - Expansion vessel  
21 - Condensate trap inspection cap  
22 - Condensate trap  
23 - Condensate discharge tube  
24 - Condensate trap inlet  
25 - Injector  
275  
12  
3.2.  
REMOVING THE CASING  
3.3.  
CONTROL PANEL  
To disassemble the front casing panel, follow these steps:  
1. Unscrew the screws “A” (1/4 turn only) and rotate the control  
panel forwards;  
2. Unscrew the screws “B”;  
3. Unhook the front panel of the casing by lifting it.  
To disassemble the side panels, follow these steps:  
4. Unscrew the screws “C” (at bottom) fastening the side panels;  
5. Lift and unhook the panels.  
1
A
3
2
B
A. Selector Knob for Summer/Winter/Flue Test Modes  
B. Domestic Hot Water Temperature Adjustment Knob  
C. Central Heating Temperature Adjustment Knob  
D. On/Off L.E.D.  
E. On/Off Knob  
F. COMFORT” Function Push-button/heating only (RFFI SYSTEM)  
G. “COMFORT” Function L.E.D./heating only (RFFI SYSTEM)  
H. Reset Button  
I. Multifunction Display  
J. Heating System Pressure Gauge  
K. Time Clock  
L. Programming “+” key  
M. Programming “-” key  
3.4.  
INITIAL START-UP  
When necessary configure the main P.C.B. according to the following  
diagram (please refer to the legend on page 17)  
4
5
POSITION INSERTED  
NOT INSERTED  
C
3
Secondary outlet (connection The secondary outlet  
C7; positions 1-9) controls a  
LPG valve (optional).  
controls what is  
selected by Jumper 5.  
4
5
Continuous pump operation.  
No change in pump  
operation.  
Secondary output relates to a Secondary output  
secondary pump (optional).  
controls a zone valve  
(optional)  
7
N.I.  
I.  
8
CONFIGURATION  
N.I. Central heating only  
N.I. MFFI  
N.I.  
I.  
I.  
I.  
Not used  
RFFI System  
I = inserted (contact closed)  
N.I = not inserted (contact open)  
SECONDARY OUTLET = conntection C7 (position 1-9 page 17)  
1. Make sure that:  
-
-
the cap of the automatic air release valve is loosened;  
the system pressure is at least 1 bar on the pressure gauge;  
275  
13  
-
-
the gas cock is closed;  
3.6.  
OPERATING PARAMETERS  
the electrical connection has been carried out in the correct  
manner. To allow the air to escape from the system, proceed as  
follows:  
turn on the On/off knob “D” and position the selector knob “A” in  
the “winter” position. The boiler pump will start up and three  
consecutive attempts will be made to ignite the burner. After the  
third attempt, the electronic system will shutdown the boiler,  
because the supply of gas has been cut off. The message “A01”  
will appear on the display;  
The boiler has been designed to allow easy intervention with regard  
to the operating parameters.  
-
3.6.1. CONTROL MODES  
The generation of the set-point and the request for heat are clarified  
in the following diagram, with regard to the heating mode.  
-
let the pump operate until all the air has escaped from the  
system;  
-
-
-
repeat the procedure for bleeding the radiators of air;  
draw hot water for a short while;  
check the system pressure and, if it has gone down, fill it with  
water until it returns to 1 bar.  
2. Check the flue system for products of combustion.  
3. Check that any required local ventilation inlets are open.  
4. Fill the boiler condensate trap with water.  
N.B. In the event of prolonged period of system shutdown,  
the condensate trap should be filled before any renewed use.  
A shortage of water in the trap is dangerous because it could  
possibly lead to a leakage of fumes into the air.  
5. Turn on the gas cock and check the seals on the connections,  
including the one for the burner, making sure that the meter does  
not signal the passage of gas. Check the connections with a soap  
solution and eliminate any leaks.  
6. Press the reset button “H” for the lighting system; the spark will  
light the main burner. If the burner does not light the first time,  
repeat the procedure.  
* See section 3.6.2.  
The boiler is configured in the factory for the gas type in  
question. It is not necessary to regulate the gas type on  
installation.  
The remote control and the timer are available as an accessory Kit:  
in the preceding diagram, it is clear that in the event that a device of  
this type is not installed, the calculation of the set-point depends on  
an outdoor sensor (if installed) and is carried out by the P.C.B.  
NOTE: a configuration is also possible which allows for the  
simultaneous presence of a remote control and an outdoor sensor. In  
this case, the flow temperature is calculated as a function of the  
external temperature and the room temperature. In this manner, it is  
possible to carry out a particularly efficient modulation, which allows  
considerable comfort to be obtained, combined with savings in fuel.  
The influence of the roomstat and the timer are shown in the  
following diagram, taking into consideration the fact that:  
2
NOTE: the reference values of the CO are contained in the  
TECHNICAL INFORMATION section on page 4.  
3.5.  
DISPLAY: MESSAGES SHOWN DURING  
NORMAL OPERATION  
-
ON/OFF Room thermostat installed: contact open or closed,  
controlled by the room thermostat temperature sensor.  
ON/OFF Room thermostat not installed: contact closed (jumper).  
Timer installed: contact open or closed, controlled by the timer  
settings entered by the user.  
-
-
-
Timer not installed: contact open.  
Schematic representation of the influence exerted by the roomstat  
and by the timer on the request for heat and on the calculation of the  
set-point (flow temperature of the primary circuit) by means of the  
external temperature values:  
LEFT  
RIGHT  
During operation of the boiler, while it is carrying out its normal  
operations, the left-hand display shows a series of characters that  
refer to the operations indicated below:  
- Diagnostics phase (precedes the other operations)  
0
C
C.  
c
No request for heat  
Heating, burner off  
Heating, burner on  
Pump overrun for heating  
d
d.  
h
b
b.  
Domestic hot water, burner off  
Domestic hot water, burner on  
Pump overrun for domestic hot water  
Storage cylinder, burner off (SYSTEM version)  
Storage cylinder, burner on (SYSTEM version)  
NOTE: the flashing dot on the left-hand display always indicates  
“burner off”; if the still dot indicates “burner on”.  
The right-hand display (two-digit) shows:  
- in HEATING mode: temperature of the heating system flow;  
- in DOMESTIC HOT WATER mode: temperature of domestic hot water.  
275  
14  
3.6.2. OUTDOOR SENSOR  
In the case of the use of an outdoor sensor, the microprocessor-  
controlled P.C.B. calculates the most suitable flow temperature,  
taking into account the external temperature and the type of system.  
The microprocessor is capable of doing this because it is possible to  
establish a link between the external temperature and the flow  
temperature of the heating system water. This link translates into a  
"thermal curve".  
The type of curve should be chosen in correspondence with the  
planned temperature of the system and the nature of the heat loss  
present in the building.  
The flow temperature directly influences the room temperature,  
therefore making reference to the room temperature is equivalent to  
indicating variations in the temperature of the building.  
PROCEDURES AND PRACTICAL EXAMPLES:  
If the building is always cold, under all external temperature  
conditions (and therefore in all seasons), the steps to take are as  
follows:  
9
8
7
100  
The curve must be translated parallel to itself, i.e. raising the flow  
temperature (and thereby the room temperature) in parity with the  
external temperature.  
6
5
It is possible to carry out this operation by heating temperature knob.  
The konb in vertical position set a temperature oh 20°C. Turning the  
knob on the right it’s possible to set a higher room temperature.  
4
3
60  
2
1
20  
+20  
-20  
The type of curve is entered by means of the controls of the display  
P.C.B located under the lid of the P.C.B. itself. To access the  
programming buttons (+ / -), raise the lid with a screwdriver as shown  
in the illustration.  
In this manner, temperatures for the water coming out of the boiler  
are set successively higher, which then influence the room  
temperature increasing it to the desired settings.  
While turning the knob the display shows “d.xx” for few seconds, “xx”  
is the room temperature set. Alternatively, it is possible to lower the  
output temperature of the boiler if the room temperature is too hot.  
It is possible obtain this turning the knob on the left translating lower  
the curve.  
In the event of the chosen curve not being the most suitable for the  
type of system, it may be changed (selecting a more appropriate  
one) or moved until the desired thermal behaviour is obtained for the  
boiler and the system.  
+
-
NB: The last effect achieved by adjusting the thermal curves is to change  
the behaviour of the system in relation to the room temperature. If  
the curve used has been selected underestimating the thermal  
needs of the building, i.e. it is too “low”, it is possible that the building  
will not heat up sufficiently (the boiler will arrive to the set-point  
before the building reaches the desired temperature); the result is  
that the building will feel cold.  
275  
15  
If the room temperature is too cold during the  
winter (while in spring the temperature is  
adequate), it is necessary to enter a steeper  
curve. To do this, press the reset button for 5  
seconds and then press it repeatedly until the  
letter “F” appears (using the “+” and “-” keys).  
In this manner, the curves may be selected  
from 1 to 5.  
Alternatively, if the building is too warm in the  
winter, while the room temperature is  
adequate in warmer seasons, it is necessary  
to choose a less steep curve, adjusting it in  
the same manner as above.  
If the following situation occurs: with low external temperatures (e.g:  
winter, -20°C) the building is adequately heated, but with favourable  
climatic conditions (e.g: spring, +20°C) it is not sufficiently heated, it is  
necessary first to choose a lower curve (“F” on the display and then “-”)  
and then turning the heating temperature knob.  
In the opposite situation (in which the building is too hot in spring and  
adequately heated in winter), a higher curve (“d” and “+”) must first  
be chosen and then “moved” turning the heating temperature knob.  
The general conditions to follow upon installation are the following:  
Warning (see 3.7.2)  
* The curves 1,2,3,4,5,6 could be set in the lower temperature;  
* The curves 5,6,7,8,9 could be set in the upper temperature;  
CURVE 4-5: conventional low temperature boilers (cast iron and  
aluminum radiators, radiant plate systems). Planned  
temperature 60/45°C.  
CURVE 6-7: conventional low temperature boilers (cast iron and  
aluminum radiators, radiant plate systems). Planned  
temperature 75/60°C.  
CURVE 1:  
under floor heating (radiant panels at ultra-low  
temperature). Planned temperature 30/20°C.  
CURVE 8-9: boilers with higher temperatures (radiators, convectors,  
fan coils). Planned temperature 90/75°C.  
CURVE 2-3: under floor heating (radiant panels, low temperature  
radiant plate systems). Planned temperature 40/30°C.  
For buildings with standard insulation, materials and exposure, it is recommended initially that the straight line not be moved parallel to itself. If  
a timer is installed, it is possible to set different temperatures for daytime and night-time. It is therefore possible to lower the temperature that  
the P.C.B. calculates in relation to the values provided by the outdoor sensor by a quantity decided by the user for night-time operation. To do  
this, it is necessary to select the night function “u”, in the following manner:  
-
-
-
press the reset key for 5 seconds;  
press the same key again once to make the “n” character appear;  
using the programming keys “+” and “-”, select a value from 0 to 12 depending on the amount of night-time lowering of the temperature  
desired.  
275  
16  
entered may be viewed in the manner described in section 3.6.3.  
(the display shows the value with steps of 10).  
3.6.3. SETTINGS DISPLAY  
The boiler is designed to monitor some operating variables and  
settings by means of the display on the front control panel. Keeping  
the reset key pressed for over 10 seconds allows access to the  
“readout” function of the main system variables. By pressing the  
button repeatedly after that, it is possible to read the following  
information in sequence:  
2. PR - Maximum heating circuit power potentiometer, variable  
between the maximum allowed by the boiler and the minimum  
(see “TECHNICAL INFORMATION” table). The boiler is calibrated in  
the factory at 70%.  
3. RLA - Soft-light potentiometer, variable between the  
maximum power (shown on the display as “00”, i.e. 100%) and  
Value read on right-hand display  
Indication on the  
left-hand display  
minimum power (shown on the display as “01”, i.e. 1%). The boiler  
is calibrated in the factory at a value which is suitable for ignition  
with any type of gas (approx. 70%).  
The display shows the value between 100% (“00” on the display)  
and 1% (“01”) of this interval. The indications on the display with  
Flow temperature of the heating circuit (C°)  
Return temperature of the heating circuit (C°)  
Domestic hot water output temperature (C°)  
Ionisation current (expressed in bT)  
U/1  
U/2  
U/5  
U/F  
U/t  
P/A  
regard to the power are shown in the graph:  
DISPLAY MESSAGE REFERENCE  
Main circuit flow switch  
Heating ignition delay (see section 3.6.4. -  
expressed in min.x10)  
Maximum thermal power for heating (expressed  
in a percentage of the difference between the  
maximum power allowed by the boiler and the  
minimum)  
P/-  
Soft light power (expressed in a percentage of  
the difference between the maximum power  
allowed by the boiler and the minimum)  
Last safety shut-off (see section 3.7.)  
Last shutdown (see section 3.7.)  
P/L  
b
l
3.7.2. SETTING THE TEMPERATURE FIELD  
To return to the normal display, press the “H” reset key repeatedly  
until all the sequence of “readout” functions have scrolled through the  
display and until one of the “display of normal operations” has  
appeared (the message that appears will depend on the current  
operating mode of the boiler).  
Remove the protection of the display using a screwdriver as a lever.  
Press the reset button for over 5 seconds. The display will show  
A03. On pressing the reset button again the display will change to  
R00(R indicates the setting of the field of regulation of the flow  
temperature). Using the button “E”, the setting may be changed. It is  
possible to choose two fields of regulation of the flow temperature.  
00signifies that the flow temperature (which may be set by means  
of the knob on the front control panel) may be regulated from 30 to  
75°C. 01signifies that the flow temperature (which also may be set  
by means of the knob on the front control panel) may be regulated  
from 42 to 82 °C. The factory setting is 00.  
* NOTE 1: U/1 means that “u” and “1” blink alternately on the display  
NOTE 2: the value 100% appears as “00” on the display  
3.7.  
REGULATIONS  
3.7.1. POTENTIOMETERS  
To access the areas reserved for the regulation and control, open the  
control panel, after having first unscrewed the plastic fastening  
screws, and raise the rubber protection stopper for the  
potentiometers, as shown in the illustration.  
3.7.3. COMFORT KEY:  
24 MFFI  
The boiler allows the convenience level to be increased in the output  
of domestic hot water by means of the “COMFORT” function. This  
function keeps the secondary exchanger warm during the periods in  
which the boiler is inactive, thereby allowing the initial water drawn to  
be at a higher temperature. The function may be activated by  
pressing the “H” key on the control panel (see section 3.3.). When  
the function is active, a green light comes on, again located on the  
control panel.  
NOTE: During the overrun period of the pump, the “COMFORT”  
function, if selected, is temporarily deactivated. The L.E.D. light  
remains on to indicate that the boiler will return to the “COMFORT”  
mode once the pump overrun is terminated.  
HEATING ONLY KEY:  
24 RFFI  
This function may be activated by pressing the “H” key on the  
control panel (see section 3.3.). When the function is active, a green  
light comes on, again located on the control panel. This indicates that  
the external indirect cylinder is not maintained at the set temperature,  
only the anti-frost protection of the indirect cylinder is active. When  
the temperature goes below 5°C, the boiler turns itself on and heats  
up the indirect cylinder until the temperature goes over 10°C.  
This allows access to the three regulation potentiometers:  
1. RA - Ignition delay (anti-cycling device) potentiometer  
It is possible to set the ignition delay by adjusting the  
potentiometer with a screwdriver. The values that may be  
selected range from 0 to 15 min.  
The delay has been set at 15 minutes in the factory. The value  
275  
17  
3.7.4. PUMP OVERRUN  
3.7.5. TEST MODE  
The pump overrun may be varied (after the burner has been turned  
off). To access this function, it is necessary to press the reset button  
for over 5 seconds and then press it repeatedly until the character  
Aappears on the left-hand display.  
The P.C.B. allows the boiler to be forced to the maximum or minimum  
power.  
To make the boiler operate at maximum power (100%: 24kW), it is  
necessary to turn the selector knob “A” (section 3.3.) and, using a  
light pressure, bring it to the <  
> position. To return the boiler to its  
The following modes are available:  
normal function, turn the selector “A” to the summer or winter  
position.  
NOTE: To force the boiler to its maximum output it is necessary to  
completely rotate the potentiometer for maximum heating output  
regulation (PR).  
01  
1 minute of pump overrun  
3 minutes of pump overrun  
6 minutes of pump overrun  
9 minutes of pump overrun  
12 minutes of pump overrun  
15 minutes of pump overrun  
24 hours of pump overrun  
03  
06  
09  
12  
15  
CO  
It is also possible to set a continuous pump operation by closing the  
contact of jumper 4 (see section 2.12.).  
3.7.6. REGULATION MENU TABLE  
Summary of the functions accessed when the RESET button is pushed for 5 seconds.  
3.8.  
BOILER SAFETY SYSTEMS  
The boiler is protected from malfunctioning by means of internal  
checks by the P.C.B., which brings the boiler to a stop if necessary.  
In the event of the boiler being shut off in this manner, a code  
appears on the display which refers to the type of shut-off and the  
reason behind it.  
DISPLAY  
A01  
CAUSE  
Too many attempts to ignite on starting up  
After three attempts at ignition, no increase in DT was  
detected  
A02  
There are two types of shut-off:  
A03  
The heating flow temperature exceeds 100°C during  
operation  
-
SAFETY SHUTDOWN :these group of errors (characterised on  
the display by the letter “E”) this situation is automatically  
removed as soon as the cause behind it is resolved.  
As soon as the origin of the shutdown disappears, the boiler  
starts up again and returns to its normal operation.  
A07  
A19  
Too many failures to flame in one period during operation  
The flame was detected after the gas valve had closed  
The flame was detected before the gas valve opened  
The flow switch does not close  
A20  
A21  
-
SHUTDOWN: (characterised on the display by the letter “A”), it is  
not removed unless a manual intervention is made.  
The boiler may return to operation only if reset by means of  
pressing the button “H” (see illustration on page 18) located at  
the centre of the display.  
A22  
A33  
A99  
The flow switch does not open  
Problem with the fan  
Problem with the electronic monitoring  
There follows a list of the shutdown modes and the respective codes  
shown on the display.  
NOTE:  
When there is no ignition, check that the gas cock is open.  
Shutdown (“A” type): if such a situation occurs, it is necessary to reset  
the boiler using the appropriate key. If this shutdown occurs again, an  
Authorised Service Centre should be contacted.  
Safety shutdown: In the event that a safety shutdown occurs, it is  
necessary to contact an Authorised Service Centre.  
275  
18  
DISPLAY  
CAUSE  
temperature goes below -3°C, it turns off when the external  
temperatures raises above -1°C.  
Continuous operation of the pump: select by means of jumper 4  
(see paragraph 3.6.6.).  
E03  
Flow temperature over 100°C while boiler is not in  
operation (stand-by)  
-
NOTE: In all cases, the circulation takes place in the heating system.  
The anti-frost device activates only when (with the boiler operating  
correctly):  
E56  
E66  
E04  
E05  
E08  
E20  
E21  
Heating flow temperature probe in open circuit  
Heating flow temperature probe short-circuited  
Domestic hot water temperature probe in open circuit  
Domestic hot water temperature probe in short circuit  
Under floor heating temperature probe in open circuit  
Flame detected with gas valve closed  
-
-
-
the system pressure is correct;  
the boiler is electrically powered;  
there is a supply of gas.  
6. ANTI-SCALE DEVICE. When producing domestic hot water, the  
burner shuts off whenever the output temperature of the hot  
water exceeds 62°C or the flow temperature of the primary  
circuit exceeds 72°C. It will not turn on if the temperature of the  
primary circuit is greater than 72°C.  
Error in the electrical connection (live and neutral crossed)  
Problem with the 50Hz power supply  
E22  
E23  
E64  
E74  
E99  
Flame detection electrode short-circuited  
Heating return temperature probe in open circuit  
Heating return temperature probe in short circuit  
Problem within the electronic system  
3.9.  
COMBUSTION ANALYSIS  
The boiler is designed to  
allow for easy analysis of  
There follows a description of the safety functions that most influence  
the behaviour of the boiler.  
the  
combustion.  
products  
of  
1. FLOW SWITCH. At the beginning of every ignition sequence, the  
P.C.B. checks the operation of the main circuit flow switch.  
Initially, the pump is off and the flow switch must be open (not  
giving consent); if this does not occur within the space of a  
minute, the system carries out a shutdown. When the flow switch  
is open, the pump is turned on and within one minute the flow  
switch must close; if it does not do so, the monitoring  
mechanism shuts down the boiler (with the pump off).  
Using the special traps, it  
is possible to detect the  
temperature of the burnt  
gas, the combustion air,  
2
the concentrations of O ,  
2
CO , etc.  
The maximum heating power test conditions may be optimised by  
turning the selector knob “C” to the flue test position.  
During normal operation, the flow switch must remain closed; if it  
opens for over two seconds, the boiler shuts down, then the  
monitoring mechanism will attempt to turn it back on.  
3.5.  
DRAINING  
2. FAN. On ignition, the fan must rotate at the correct speed,  
otherwise the boiler will not attempt to turn itself on. During  
operation, the fan rotates at the speed set by the control P.C.B.;  
if the number of rotations deviates by more than 300 rpm from  
this setting, the boiler shuts off.  
The draining of the heating system must be carried out as follows:  
-
-
-
Turn off the boiler and the bipolar switch;  
Loosen the automatic air release valve (27);  
Open the system's discharge valve (18) and gather the water  
that comes out in a container;  
3. OVERHEATING. This device shuts down the boiler in the event that  
the primary circuit reaches a temperature that exceeds 100°C.  
The operation of the overheat monitoring mechanism also  
includes the following precautionary measures:  
-
Empty out from the lowest points of the system (where  
provided).  
If the system is to be left active in areas where the room temperature  
may go below 0°C during winter, it is recommended that anti-freeze  
liquid be added to the water in the heating system in order to avoid  
the need for repeated draining.  
-
After every ignition, the system flow temperature or the  
flow/return difference must increase by 3°C in 20 seconds. Until  
an increase of 3°C is reached, the boiler remains at the ignition  
power. If the increase in temperature does not come about, the  
boiler shuts down and will not attempt to re-ignite until the flow  
temperature is below 50°C. If after three attempts the  
temperature does not increase, the boiler shuts down.  
Draining the domestic hot water system  
Every time that there is a danger of freezing, the domestic hot water  
system must be drained as follows:  
-
-
-
close the water mains stop-cock;  
open all the hot and cold water outlets;  
empty out from the lowest points (where provided).  
-
-
Before the boiler attempts ignition, the system flow/return  
temperature difference must be below 20°C. In order for a  
successive attempt at ignition to be carried out, the system must  
register that once every 2 hours the flow/return temperature  
difference is below 5°C.  
If, during operation the return temperature becomes greater than  
the flow temperature by more than 5°C, the boiler shuts down  
immediately.  
4. DAILY TEST. In order to prevent the shutdown of the components,  
the boiler carries out a self-diagnosing test every 24 hours: the  
pump turns on for 3 seconds and the diverter valve moves.  
5. ANTI-FROST DEVICE. The boiler is fitted with an anti-frost device  
consisting of three separate functions:  
-
Monitoring of the system flow temperature: if this temperature  
goes below 5°C, the pump turns on (heating system circulation).  
If the temperature goes below 2°C, the boiler turns on at the  
minimum power and remains on until the return temperature is  
over 10°C.  
-
Outdoor sensor installed: the pump turns on if the external  
275  
19  
4. GAS ADJUSTMENTS  
NOTE: the values refer to the upper calorific power  
4.1.  
OVERALL VIEW  
Type of appliance  
Natural Gas  
LPG  
LPG  
LL  
E
Marking on the label of characteristics  
Further indications  
Yellow adhesive label:  
calibrated for LPG  
Wo=24.3 Kw/m3  
(from 20.2 to 24.3  
kWh/m3)  
Yellow adhesive label:  
calibrated for 'L' type  
methane  
Wo=11.5 Kw/m3  
(from 9.5 to 12.4 kWh/m)  
20mbar  
Yellow adhesive label:  
calibrated for 'H' type  
methane  
Wo=14.1 Kw/m3  
(from 11.4 to 15.2 kWh/m3)  
20mbar  
50mbar  
Factory setting for the Wobbe Wo index  
in kWh/m3  
24.3  
11.5  
14.1  
Factory setting of the thermal capacity  
for the production of hot water  
Maximum thermal power  
70% Maximum thermal power  
Factory setting of the thermal capacity  
for the heating  
4.2.  
PRELIMINARIES  
Check that the indication for type of appliance (category and type of  
gas calibration) reported on the label of characteristics corresponds  
to the gas family / group of the gas supply.  
The type of of appliance does not  
correspond to the gas family of the  
gas supply  
The appliance cannot be installed or put into operation.  
A
The type of appliance corresponds  
to the gas family of the gas supply  
Check the regulation according to section 4.3  
In the event of the heating power setting being different from the  
thermal power setting required, the gas must be adjusted as in  
section 4.3. Otherwise, it is enough to check the  
correspondence.  
Domestic hot water:  
Heating:  
B
C
The type of appliance does not  
correspond to the gas supply group  
(but corresponds to the family).  
Transform the boiler in accordance with section 4.5, after which:  
Check the regulation in accordance with 4.3  
Carry out the gas regulation in accordance with point 4.3 in  
keeping with the thermal power requested.  
Domestic hot water:  
Heating:  
4.3.2. REGULATION OF THE THERMAL POWER  
4.3.  
GAS REGULATION  
To regulate the gas, the sequence described below must be followed.  
For the regulation of the gas in the ecoGENUS, two separate  
operations are required.  
A) Domestic hot water side (test only)  
B) Heating side (regulation and test)  
-
Unscrew by 2 to 3 rotations the sealing screws marked “PE” of  
the pressure measurement inlet nipple  
-
-
Connect up a pressure gauge  
Place the appliance in operation in accordance with the usage  
manual  
A) DOMESTIC HOT WATER:  
The thermal power for the hot water is set in the factory at the  
maximum power.  
-
Measure the connection pressure (dynamic pressure)  
For this reason the boiler does not need any regulation of the gas  
from the "domestic hot water" side, just a test using the volumetric  
method at the gas meter:  
4.3.1. INLET PRESSURE TEST  
This pressure, for methane gas, must be between 18 and 25 mbar.  
In the event that the pressure is outside of the above range, the  
boiler must not be placed in operation.  
-
Make sure that there are no other gas appliances in operation  
during the test.  
-
Place the boiler in operation in accordance with the usage  
manual and draw hot water (tap totally open, temperature knob  
at 9).  
-
-
-
Turn off the boiler.  
Remove the pressure gauge.  
Screw in the sealing screws of the pressure measurement inlet  
nipple and check the seal.  
NOTE: the test of the volumetric rate of flow must be carried out for at  
least two minutes of boiler operating time.  
If it proves impossible to eliminate the defect, contact the gas supply  
board.  
-
Identify the volumetric rate of flow for the maximum thermal  
power from the table at the end of this section.  
275  
20  
-
-
Make a note of the value here. Value from table: ................l/min.  
Identify the volumetric rate of flow at the gas meter and compare  
it with that of the table.  
Differences greater than +/- 5 % are not allowed: contact the  
Authorised Service Centre and do not place the boiler in  
operation.  
fastening screws and lift up the rubber stopper protecting the  
potentiometers (see section 3.7.1.). Rotate the potentiometer PR  
to the desired point, checking the set thermal power on the  
display (as described in section 3.6.3.) and on the table below.  
-
Test:  
-
-
Turn the selector knob “A” to the flue test position.  
Do not draw hot water.  
B) HEATING:  
NOTE: The test of the volumetric rate of flow must be carried out for at  
The thermal power is set in the factory at 70% of the maximum  
power (the potentiometer corresponds to the value on the display). In  
the event that this setting has to be changed, these steps should be  
followed:  
least five minutes of boiler operation.  
Identify the volumetric rate of flow from the table and make a  
note of it here.  
Value from the table: ……….l/min.  
Identify the volumetric rate of flow at the gas meter and compare  
it with that of the table.  
-
-
-
open the control panel after having unscrewed the plastic  
4.4. CHANGING THE TYPE OF GAS  
The boiler may be transformed for use with LPG (G30-G31); the  
operation must be performed by an Authorised Service Centre.  
The operations to carry out are the following:  
1. Replacement of the nozzle (see table);  
2. Replacement of the gas label;  
3. Regulation of the slow ignition (refer to section 3.7 and the table  
in 4.3)  
CATEGORY  
NATURAL GAS  
G20  
LPG  
G30  
1.7  
G31  
1.7  
Diameter of 6 nozzle holes (mm)  
2.7  
Display of recommended soft-light  
70  
70  
70  
(about 19 kW)  
(about 19 kW)  
(about 19 kW)  
4.5.  
OPERATING TESTS  
-
Place the boiler in operation in accordance with the User’s  
Manual.  
-
-
Check the seal on the gas and water sides.  
Check that the ignition operates correctly and visually check the  
burner flame.  
-
-
Check that the domestic hot water is being correctly produced  
by drawing hot water. Check the rate of flow and/or temperature  
of the water, depending on the case.  
Check that the condensate drips without difficulty into the  
discharge.  
275  
21  
5. ZONE VALVES  
6. MAINTENANCE  
The boiler is capable of managing a heating system that uses zone  
valves. The electrical connection of these valves is carried out by  
means of the appropriate terminal board (indicated in the  
“ELECTRICAL CONNECTIONsection).  
By way of example, two possible types of systems would be:  
1. System with 2 valves with independent regulation of the zones  
(day and night).  
2. System with 1 valve (regulation of the night zone subordinated to  
that of the day).  
A possible set-up for the first type of system is as follows:  
6.1.  
GENERAL REMARKS  
It is recommended that the following inspections be carried out on  
the boiler at least once a year:  
1. Check the seals in the water group and, if necessary, replace  
the gaskets and restore the seal to perfect working order.  
2. Check the seals in the gas group and, if necessary, replace the  
gaskets and restore the seal to perfect working order.  
3. Visually check the overall state of the boiler.  
4. Visually check the combustion and, if necessary, disassemble  
and clean the burner.  
5. Following inspection 3, disassemble and clean the combustion  
chamber, if necessary.  
6. Following inspection 4, disassemble and clean the injector, if  
necessary.  
7. Clean the primary heat exchanger (see section 6.2)  
8. Regulate the correct rate of flow of the gas: rate of flow on  
ignition, partially loaded and at maximum load.  
9. Check the correct functioning of the heating safety devices:  
- temperature limit safety device.  
10. Check the correct functioning of the gas group safety devices:  
- absence of gas or flame safety device (Ionisation).  
11. Check that the electrical connections are correct (in conformity  
with the instructions manual).  
12. Check the efficiency of the production of domestic hot water  
(test the rate of flow and temperature).  
13. Carry out a general inspection of the functioning of the boiler.  
14. Check the characteristics for expulsion of the products of  
combustion.  
15. Remove the oxide from the detection electrode by means of an  
emery cloth.  
CR  
VZ1,2  
TA  
= remote control  
= zone valve 1 and 2  
= roomstat or timer-thermostat  
= radiators  
= electrical connection (live and neutral)  
= relay  
6.2.  
CLEANING THE PRIMARY EXCHANGER  
F,N  
RL  
CLEANING THE EXHAUST SIDE  
Remove the combustion chamber inspection hatch (20) (see section  
1.3). Check that the exhaust passages between the blades of the  
block are free; if there are deposits present, wash the blades with  
compressed air, water or a vinegar-based detergent.  
NOTE: it is possible to use a brush in order to mechanically remove  
the residues.  
A possible set-up for the system with a single zone valve is as  
follows:  
Use of detergents:  
-
-
-
soak the blades well  
allow the detergent to act for about 20 minutes  
rinse with a strong jet of water to remove the deposits (the  
control panel must be kept closed)  
-
make sure that there are no traces of detergents in the  
exchanger.  
CLEANING THE WATER SIDE  
Use detergents that dissolve CaCO3. Leave to act for a short time  
(in order not to damage the aluminum) and then rinse. Make sure  
that the detergent does not remain inside the exchanger.  
This set-up is simpler and more economical because it does not  
involve the use of the special relay. The night zone, however, may  
only be heated during the time periods in which the remote control  
timer gives consent to the heating of the day zone. Example:  
6.3.  
CLEANING THE CONDENSATE TRAP  
Unscrew the lower part of the condensate trap and clean it. Lastly, fill  
it with water and replace the stopper.  
day zone programming (remote control): 8-22  
night zone programming (timer-thermostat): 20-22  
NB: if the boiler is not to be used for a prolonged period, the  
condensate trap should be filled before igniting it again. A shortage  
of water in the trap is dangerous because there is the risk of exhaust  
fumes escaping into the air.  
275  
22  
6.4.  
OPERATIONAL TEST  
After having carried out the maintenance operations, fill the heating  
circuit to a pressure of approx. 1.5 bar and release the air from the  
system. Also fill the domestic hot water system.  
-
-
-
Place the boiler in operation.  
If necessary, release the air again from the heating system.  
Check the settings and the correct functioning of all the control,  
regulation and monitoring parts.  
-
-
Check the seal and the correct functioning of the system for  
expelling fumes/drawing of combustion air.  
Check that the boiler ignites properly and carry out a visual  
check on the burner flame.  
275  
23  
7. TECHNICAL INFORMATION  
24 MFFI  
24 RFFI SYSTEM  
Certification  
Category  
Thermal Capacity min/max  
63AT4528  
II2H3B/P  
8/24  
8.8/26.1  
7.9/23.3  
-/24.5  
7.9/23.3  
102.2  
96.4  
103.6  
0.42  
0.6  
2.1  
0.2  
63AT4528  
II2H3B/P  
8/24  
8.8/26.1  
7.9/23.3  
-/24.5  
7.9/23.3  
102.2  
96.4  
103.6  
0.42  
0.6  
2.1  
0.2  
kW  
kW  
kW  
kW  
kW  
%
Usable Thermal Power min/max (30/40°C)  
Usable Thermal Power min/max (60/80°C)  
Usable Thermal Power min/max (30/50°C)  
Power for Hot Water Production min/max  
Efficiency at Nominal Thermal Capacity (30/50°C)  
Efficiency at 30% of Nominal Thermal Capacity (47°C of return)  
Efficiency at 30% of Nominal Thermal Capacity (30°C of return)  
Gas Consumption after 10 Minutes*  
%
%
m3  
%
Maximum Heat Loss to the Casing (T=50°C)  
Flue Heat Loss with Burner Operating  
Flue Heat Loss with Burner Off  
%
%
35.1  
66.7  
42.9  
5
42/82  
30/75  
36/56  
5
Maximum Discharge of Fumes  
Kg/h  
°C  
°C  
°C  
°C  
°C  
°C  
35.1  
66.7  
42.9  
5
42/82  
30/75  
36/56  
5
Maximum Temperature of Discharge Fumes  
Temperature of Discharge Fumes when Heating 30/40°C (1 m of coax.)  
Minimum Room Temperature  
Heating Temperature min/max (High Temperature range)  
Heating Temperature min/max (Low Temperature range)  
Temperature of Water for Domestic Use min/max  
Class NOX  
9.3  
2
CO Content  
%
%
9.3  
4
2
O Content  
4
53.5  
20  
30  
0.65(64)  
200  
0.2  
CO Content  
ppm  
mbar  
mbar  
mbar(Pa)  
mbar  
bar  
53.5  
20  
30  
0.65(64)  
200  
0.2  
Inlet Pressure/Methane Gas G20 (boiler at maximum)  
Inlet Pressure/Liquid Gas G30 - G31 (boiler at maximum)  
Residual Discharge Head  
Maximum Head Loss on Water Side (T=20°C)  
Residual Head of System (60/80°C)  
Maximum Heating Pressure  
3
bar  
3
130  
7
Maximum Water Content in System  
Expansion Vessel Capacity  
l
l
130  
7
1
Expansion Vessel Pre-load Pressure  
Pressure of Water for Domestic Use min/max  
Nominal Capacity of Hot Water for Heating (residual head 0.25 bar)  
bar  
bar  
l/h  
l/min  
l/min  
l/min  
l/min  
l/h  
1
0.2/8-10  
820  
---  
---  
---  
---  
1.8  
0.2/8-10  
820  
13.4  
11.1  
9.6  
D.H.W. Flow Rate:  
T=25°C  
T=30°C  
T=35°C  
D.H.W. Flow Minimum Rate  
2.5  
1.8  
Quantity of Condensed Water with a (30/40°C)  
pH Condensation Value  
Electrical Supply  
Power Consumption  
Protection Grade of Electrical System  
Internal Fuse Rating  
3.5÷4  
230/50  
130  
4XD  
3.15 SLOW  
465  
890  
385  
3/4  
3.5÷4  
230/50  
130  
4XD  
3.15 SLOW  
465  
V/Hz  
W
IP  
A
Width  
Height  
Depth  
mm  
mm  
mm  
890  
385  
3/4  
1/2  
3/4  
45  
Central Heating Connections  
Domestic Hot Water Connections  
Gas Connection  
BSP  
BSP  
BSP  
Kg  
1/2  
3/4  
44.5  
Net Weight  
41-116-03  
G.C. Number  
41-116-17  
Manufacturer:  
Merloni TermoSanitari SpA - Italy  
*Calculated at 70% maximum output  
Commercial subsidiary:  
MTS (GB) LIMITED  
MTS Building  
Hughenden Avenue  
High Wycombe  
Bucks HP13 5FT  
Telephone: (01494) 755600  
Fax: (01494) 459775  
Technical Service Hot Line: (01494) 539579  
23 99 84 1439 112  
Servicing  
Instructions  
Type C Boilers  
G.C.N: 41-116-03  
47-116-17  
Condensing  
LEAVE THESE INSTRUCTIONS  
WITH THE END-USER  
Country of destination: GB  
1.  
SERVICING INSTRUCTIONS  
TABLE OF CONTENTS  
1.1  
1.2  
REPLACEMENT OF PARTS  
TO GAIN GENERAL ACCESS  
- Lowering the control panel and removing the front panel  
- Removing the side panels  
1.3  
ACCESS TO THE COMBUSTION CHAMBER  
- Removing the sealed chamber front cover  
- Removing the fan  
- Removing the burner  
- Removing the electrodes  
- Removing the heat exchanger inspection panel  
- Removing the condensate collector  
- Removing the condensate trap  
- Removing the injector  
1.4  
1.5  
ACCESS TO THE GAS VALVE  
- Removing the gas valve  
ACCESS TO THE WATER CIRCUIT  
- Removing the D.H.W. (secondary) exchanger  
- Removing the safety valve  
- Removing the automatic air vent  
- Removing the main circuit flow switch  
- Removing the diverter valve actuator  
- Removing the D.H.W. flow switch  
- Removing the pump  
- Removing the pressure gauge  
- Removing the expansion vessel  
- Removing the D.H.W. temperature sensor (N.T.C.)  
- Removing the C.H. flow temperature sensor (N.T.C.)  
- Removing the C.H. return temperature sensor (N.T.C.)  
1.6  
ACCESS TO THE CONTROL SYSTEM  
- Checking the fuses  
- Removing the time clock  
- Removing the P.C.B.s  
2.  
2.1  
3.  
4.  
FAULT FINDING  
FAULT FINDING GUIDE (FLOW-CHART)  
ELECTRICAL DIAGRAMS  
SHORT SPARE PARTS LIST  
2
To ensure efficient safe operation, it is recommended that the boiler is  
serviced annually by a competent person.  
1.  
SERVICING  
INSTRUCTIONS  
Before starting any servicing work, ensure both the gas and electrical  
supplies to the boiler are isolated and the boiler is cool.  
Before and after servicing, a combustion analysis should be made via the flue  
sampling point (please refer to the Installation Manual for further details).  
After servicing, preliminary electrical system checks must be carried out to  
ensure electrical safety (i.e. polarity, earth continuity, resistance to earth and  
short circuit).  
The life of individual components vary and they will need servicing or  
replacing as and when faults develop.  
The fault finding sequence chart in chapter 2 will help to locate which  
component is the cause of any malfunction, and instructions for removal,  
inspection and replacement of the individual parts are given in the following  
pages.  
1.1  
1.2  
REPLACEMENT  
OF PARTS  
All testing and maintenance operations on the boiler require the control panel  
to be lowered. This will also require the removal of the casing.  
TO GAIN GENERAL  
ACCESS  
To lower the control panel and dismantle the front part of the casing,  
proceed as follows:  
1. Unscrew screws “A” (1/4 turn only) (FIG. 1.1 + FIG. 1.2) and rotate the  
control panel forward;  
2. Unscrew the screws “B” (FIG. 1.3) and unhook the front panel by lifting it.  
FIG. 1.2  
B
B
FIG. 1.1  
A
A
A
FIG. 1.3  
3
Removing the side panels  
1.3  
ACCESS TO THE  
COMBUSTION CHAMBER  
1. Remove the screws “C” (FIG. 1.4);  
2. Pull each panel away from the boiler, then lift the panel  
up and away from the boiler.  
Removing the sealed chamber front cover  
1. Remove the screws “D” (FIG. 1.5);  
2. Pull the cover away from the boiler (FIG. 1.6).  
C
C
D
D
D
D
FIG. 1.5  
C
C
FIG. 1.4  
FIG. 1.6  
4
Removing the fan  
1. Loosen nut “E” (FIG. 1.7);  
FIG. 1.9  
2. Pull off the hose “F” and disconnect the electrical  
connector “G” (FIG. 1.8);  
3. Remove the nuts “H” (FIG. 1.9);  
H
4. Pull the fan away from the exchanger (FIG. 1.10).  
H
H
E
FIG. 1.7  
F
FIG. 1.10  
G
FIG. 1.8  
5
Removing the burner  
With the fan removed (see previous section);  
1. Slide the burner from its housing (FIG. 1.11).  
FIG. 1.14  
Removing the combustion chamber inspection panel  
FIG. 1.11  
1. Remove the four nuts “K” (FIG. 1.15);  
2. Remove the inspection panel (FIG. 1.16).  
Removing the electrodes  
1. Pull off the ignition cable “I” (FIG. 1.12);  
2. Remove the two allen bolts “J” (FIG. 1.13);  
3. Extract the electodes (FIG. 1.14).  
K
K
I
K
K
FIG. 1.15  
FIG. 1.16  
FIG. 1.12  
J
J
FIG. 1.13  
6
Removing the condensate collector  
1. Remove the nuts “Lfrom each side of front of the  
collector (FIG. 1.17);  
2. Remove the nuts “M” from each side of rear of the  
collector (FIG. 1.18);  
3. Release the condesate trap union “N” (FIG. 1.19);  
4. Separate the collector from the combustion  
chamber(FIG. 1.20);  
5. Remove the condensate collector (FIG. 1.21).  
N
FIG. 1.19  
L
FIG. 1.17  
FIG. 1.20  
M
FIG. 1.18  
FIG. 1.21  
7
Removing the injector  
Removing the condensate trap  
See the section on removing the fan before carring out this  
procedure  
1. Loosen the union “O” (FIG. 1.22);  
2. Remove the condensate trap (FIG. 1.23).  
1. Disconnect all connections from the fan and remove  
(FIG. 124);  
2. Remove the four screws “P” (FIG. 125);  
3. Unscrew the injector “Q” using a suitable screwdriver  
(FIG. 126);  
4. Remove the injector (FIG. 127).  
O
Fig. 1.24  
FIG. 1.22  
P
Fig. 1.23  
Fig. 1.25  
8
Q
FIG. 1.26  
FIG. 1.27  
9
1.4  
ACCESS TO THE GAS VALVE  
Removing the gas valve  
1. Disconnect the electrical connection “R” from the gas  
valve (FIG. 128);  
2. Release the top nut “S” (FIG. 1.29);  
3. Remove the screws “T” from the bottom of the gas valve  
pipe (FIG. 1.30);  
4. Remove the gas valve (FIG. 1.31).  
T
T
FIG. 1.30  
R
FIG. 1.28  
S
FIG. 1.31  
FIG. 1.29  
10  
Removing the safety valve  
1.5  
ACCESS TO THE WATER CIRCUIT  
1. Loosen union “W” (Fig. 1.35);  
2. Unscrew and remove the valve (Fig. 1.36).  
Important! Before any component is removed, the boiler  
must be drained of all water.  
Removing the D.H.W. (secondary)  
exchanger  
1. Remove the screw “U” (FIG. 1.32);  
2. Remove the screw “V” (FIG. 1.33);  
3. Push the exchanger towards the rear of the boiler, lift  
upwards and remove from the front of the boiler (FIG.  
1.34);  
4. Before replacing the exchanger ensure that the O-rings  
are in good condition and replace if necessary.  
W
U
FIG. 1.35  
FIG. 1.32  
V
FIG. 1.33  
FIG. 1.36  
FIG. 1.34  
11  
Removing the automatic air vent  
Removing the diverter valve actuator  
1. Unscrew valve “X” (FIG. 1.37);  
2. Remove (FIG. 1.38).  
1. Unplug the electrical connector “Z” (FIG. 1.41);  
2. Release the retaining clip “A1” and remove the diverter  
valve actuator (FIG. 1.42).  
Z
X
FIG. 1.41  
FIG. 1.37  
A1  
FIG. 1.42  
FIG. 1.38  
Removing the main circuit flow switch  
Removing the D.H.W. flow switch  
1. Release the retaining clip “Y” (FIG. 1.40);  
1. Release the retaining clip “B1” (FIG. 1.43);  
2. Remove the main circuit flow switch.  
2. Remove the D.H.W. flow switch.  
B1  
Y
FIG. 1.43  
FIG. 1.40  
12  
Removing the pump  
1. Unplug the electrical connection “C1” (FIG. 1.44);  
2. Release the nut “D1” (FIG. 1.45);  
3. Release the nut “E1” (FIG. 1.46);  
4. Remove the pump (FIG. 1.47).  
C1  
E1  
FIG. 1.46  
FIG. 1.44  
D1  
FIG. 1.47  
FIG. 1.45  
13  
Removing the pressure gauge  
Removing the expansion vessel  
See the section on removing the condesate trap before  
carrying out this procedure  
1. Release coupling “F1” (FIG. 1.48);  
2. Ease the pressure gauge “G1” through the control panel  
from the rear (FIG. 1.49);  
1. Loosen nut “H1” (FIG. 1.51);  
3. Remove the pressure gauge. (FIG 1.50).  
2. Loosen nut “I1” and remove backnut “J1” (FIG. 1.52);  
3. Remove the expansion vessel (FIG. 1.53).  
H1  
F1  
FIG. 1.48  
FIG. 1.51  
G1  
J1  
I1  
FIG. 1.49  
FIG. 1.52  
FIG. 1.50  
FIG. 1.53  
14  
Removing the D.H.W. temperature probe (N.T.C.) (MFFI  
only)  
1. Remove the electrical connector “K1” by pulling off  
(Fig. 1.54);  
2. Unscrew and remove the D.H.W. temperature probe “L1”  
N1  
(FIG. 1.55).  
FIG. 1.57  
K1  
Removing the C.H. return temperature probe (N.T.C.)  
1. Remove the electrical connector “O1” by pulling off  
(Fig. 1.58);  
2. Unscrew and remove the C.H. return temperature probe  
“P1” (FIG. 1.59).  
FIG. 1.54  
O1  
L1  
FIG. 1.55  
FIG. 1.58  
Removing the C.H. flow temperature probe (N.T.C.)  
1. Remove the electrical connector “M1” by pulling off  
(Fig. 1.56);  
2. Unscrew and remove the C.H.flow temperature probe  
“N1” (FIG. 1.57).  
P1  
FIG. 1.59  
M1  
FIG. 1.56  
15  
Removing the time clock  
1. Remove the inspection cover on the reverse of the  
control panel (FIG. 1.60);  
1.6  
ACCESS TO THE CONTROL SYSTEM  
2. Lower the time clock door (FIG. 1.62);  
3. Unplug the electrical connection “R1” from the time clock  
(FIG. 1.63);  
Checking the fuses  
1. Remove the inspection cover on the reverse of the  
control panel (FIG. 1.60);  
4. Gently squeeze each end of the time clock and push  
through the control panel (FIG. 1.64).  
2. Remove the fuses by pushing and rotating fuse holders  
“Q1” (FIG. 1.61).  
FIG. 1.60  
FIG. 1.62  
Q1  
R1  
FIG. 1.61  
FIG. 1.63  
FIG. 1.64  
16  
Removing the P.C.B.s  
1. Remove the inspection cover on the reverse of the  
control panel (FIG. 1.60);  
2. Remove the screws “S1” (FIG. 1.65 & FIG. 1.66);  
3. Remove the facia panel (FIG. 1.67);  
5. Disconnect the connection cable ”T1” (FIG. 1.68);  
6. Unplug the electrical connectors “U1” from the main  
P.C.B. (Fig. 1.69);  
7. Remove the main P.C.B. mounting screws “V1’ (four in  
total) (FIG. 1.70);  
8. Remove the main P.C.B. (FIG. 1.71);  
9. Remove the display P.C.B. mounting screws “W1’ (FIG.  
1.72);  
T1  
10.Remove the display P.C.B. (FIG. 1.73);  
11.Replace either P.C.B. in reverse order.  
FIG. 1.68  
U1  
S1  
U1  
U1  
S1  
FIG. 1.65  
FIG. 1.69  
S1  
V1  
S1  
FIG. 1.66  
V1  
FIG. 1.70  
FIG. 1.67  
FIG. 1.71  
17  
W1  
W1  
W1  
W1  
FIG. 1.72  
FIG. 1.73  
18  
2.  
FAULT FINDING  
It is possible to detect and correct any defect by using the standard fault  
finding diagrams described in this chapter.  
2.1  
FAULT FINDING GUIDE  
(FLOW-CHARTS)  
Model 24 MFFI  
MAKE SURE THAT:  
1. There is sufficient water in the system  
2. The gas is turned on  
3. The electrical supply is turned on  
PUSH THE ON/OFF  
BUTTON TO ON  
NO  
IS THE  
POWER L.E.D. AND  
DISPLAY ON?  
1. Check the fuses  
2. Check the power supply to  
the control panel  
3. Check/replace the  
ON/OFF button  
4. Check the connection between  
the main and display P.C.B.s  
5. Check/replace the  
YES  
DOES A STOP CODE  
APPEAR ON THE DISPLAY?  
TABLE  
I and II  
main and display P.C.B.s  
POSITION OF THE SUMMER/  
WINTER SELECTOR  
WINTER  
SUMMER  
COMFORT  
SELECTOR ON/OFF:  
green L.E.D. on  
COMFORT  
SELECTOR ON/OFF:  
green L.E.D. on  
YES: COMFORT ON  
YES: COMFORT ON  
NO:  
COMFORT OFF  
NO:  
YES YES  
Flow  
temperature  
<40°C  
Flow  
temperature  
<40°C  
COMFORT OFF  
NO  
NO  
NO NO  
Flow  
temperature  
>50°C  
Flow  
temperature  
>50°C  
YES  
YES  
D.H.W.  
IS BEING  
DRAWN?  
D.H.W.  
IS BEING  
DRAWN?  
YES  
YES  
NO  
NO  
MUST  
THE TIME CLOCK  
AND/OR ROOM THERMOSTAT  
BE ACTIVATED?  
YES  
NO  
BUILT-IN  
ELECTRONIC  
BUILT-IN  
ELECTRONIC  
ANTI-FROST DEVICE:  
ANTI-FROST DEVICE:  
Is there a condition for it to be active?  
(- flow temp. < 3°C  
Is there a condition for it to be active?  
(- flow temp. < 3°C  
YES  
YES  
- outdoor temp. < -3°C (outdoor sensor optional)  
- Jumper 4 selects the pump  
for continuous  
- outdoor temp. < -3°C (outdoor sensor optional)  
- Jumper 4 selects the pump  
for continuous  
operation)  
operation)  
NO  
NO  
THERE IS NO CALL FOR PUMP OPERATION  
THERE IS NO CALL FOR PUMP OPERATION  
A
19  
Model 24 RFFI System  
MAKE SURE THAT:  
1. There is sufficient water in the system  
2. The gas is turned on  
3. The electrical supply is turned on  
PUSH THE ON/OFF  
BUTTON TO ON  
NO  
IS THE  
POWER L.E.D. AND  
DISPLAY ON?  
1. Check the fuses  
2. Check the power supply to  
the control panel  
3. Check/replace the  
ON/OFF button  
4. Check the connection between  
the main and display P.C.B.s  
5. Check/replace the  
YES  
DOES A STOP CODE  
APPEAR ON THE DISPLAY?  
TABLE  
I and II  
main and display P.C.B.s  
POSITION OF THE SUMMER/  
WINTER SELECTOR  
SUMMER  
WINTER  
OFF (green L.E.D. off):  
cylinder active  
OFF (green L.E.D. off):  
cylinder active  
C.H. ONLY  
SELECTOR  
ON/OFF  
C.H. ONLY  
SELECTOR  
ON/OFF  
The  
C.H. flow  
temperature  
The  
C.H. flow  
temperature  
ON (green L.E.D. on):  
cylinder excluded  
ON (green L.E.D. on):  
cylinder excluded  
is lower than 80°C  
and the temperature of the  
cylinder is at least 5°C  
below the one  
is lower than 80°C  
and the temperature of the  
cylinder is at least 5°C  
below the one  
YES YES  
selected.  
selected.  
NO  
NO  
MUST  
THE TIME CLOCK  
AND/OR ROOM THERMOSTAT  
BE ACTIVATED?  
YES  
NO  
BUILT-IN  
ELECTRONIC  
BUILT-IN  
ELECTRONIC  
ANTI-FROST DEVICE:  
ANTI-FROST DEVICE:  
Is there a condition for it to be active?  
(- flow temp. < 3°C  
Is there a condition for it to be active?  
(- flow temp. < 3°C  
YES  
YES  
- outdoor temp. < -3°C (outdoor sensor optional)  
- Jumper 4 selects the pump  
for continuous  
- outdoor temp. < -3°C (outdoor sensor optional)  
- Jumper 4 selects the pump  
for continuous  
operation)  
operation)  
NO  
NO  
THERE IS NO CALL FOR PUMP OPERATION  
THERE IS NO CALL FOR PUMP OPERATION  
A
20  
Model 24 MFFI/24RFFI System  
A
IS THE  
PUMP RUNNING?  
NO  
YES  
POWER TO  
THE PUMP?  
NO  
YES  
1. Check pump cable  
2. Check/replace  
main P.C.B.  
IS  
THE MAIN  
CIRCUIT FLOW SWITCH  
WORKING CORRECTLY?  
A21: does not close  
A22: does not open  
NO  
1. Check if there is air in  
the system  
2. Check the main circuit flow  
switch operation  
YES  
3. Check the pressure on the  
water gauge and fill system  
to 1 bar  
Release/replace  
pump  
YES  
Push the  
RESET button  
B
21  
Model 24 MFFI/24RFFI System  
B
NO  
IS THE FAN  
RUNNING?  
DOES CODE  
A33 APPEAR?  
YES  
YES  
1. Check the fan cable  
2. Replace the fan  
3. Replace the main P.C.B.  
NO  
Replace  
the main P.C.B.  
1. Check/replace ignition  
electrode  
2. Check ignition cable  
3. Check/replace the main P.C.B.  
IGNITION  
SPARKS ARE GENERATED  
REGULARLY?  
NO  
YES  
1. Check the power supply  
of the gas valve.  
2. Check for an air  
pressure signal  
NO  
3. Check the gas pressure  
on the burner  
IS THE BURNER  
ALIGHT?  
4. Check the soft-light  
adjustment  
YES  
5. Replace the gas valve  
6. Check/replace the  
main P.C.B.  
NO  
BOILER HAS  
SHUTDOWN?  
YES  
1. Table II  
2. Press RESET  
IS  
YES  
THERE STILL  
A PROBLEM?  
1. Table III  
NO  
NORMAL  
OPERATION  
22  
TABLE I  
DISPLAY  
A01  
CAUSE  
Too many attempts to ignite on starting up  
After three attempts at ignition, no increase in T was detected  
The heating flow temperature exceeds 100°C during operation  
Too many failures to flame in one period during operation  
The flame was detected after the gas valve had closed  
The flame was detected before the gas valve opened  
The flow switch does not close  
A02  
A03  
A07  
A19  
A20  
A21  
A22  
A33  
A99  
The flow switch does not open  
Problem with the fan  
Problem with the electronic monitoring  
TABLE II  
DISPLAY  
CAUSE  
E03  
Flow temperature over 100°C while boiler is not in operation  
(stand-by)  
E56  
E66  
E04  
E05  
E08  
E20  
E21  
E22  
E23  
E64  
E74  
E99  
Heating flow temperature probe in open circuit  
Heating flow temperature probe  
Domestic hot water temperature probe in open circuit  
Domestic hot water temperature probe in short circuit  
Under floor heating temperature probe in open circuit  
Flame detected with gas valve closed  
Error in the electrical connection (live and neutral crossed)  
Problem with the 50Hz power supply  
Flame detection electrode short-circuited  
Heating return temperature probe in open circuit  
Heating return temperature probe in short circuit  
Problem within the electronic system  
TABLE III  
FAULTS  
POSSIBLE CAUSES  
1. Drawing D.H.W:  
Radiators heat up in summer  
mode  
- faulty 3-way valve  
2. Drawing D.H.W:  
Insufficient hot water temperature  
- check C.H./D.H.W. temperature probes  
- check gas pressures  
- check water flow rate  
- check secondary heat exchanger  
3. Drawing D.H.W:  
Noisy operation  
- primary heat exchanger faulty or lime-scale deposits  
- low heating system water pressure  
- check gas pressures  
- check C.H./D.H.W. temperature probes  
4. Decrease/increase heating circuit  
pressure  
- check for leaks on the heating circuit  
- faulty filling-loop  
- faulty secondary heat exchanger  
- expansion vessel faulty  
5. When cold water tap turned off, the - drop in pressure in the water mains, with  
boiler ignites  
consequent water hammer  
6. Insufficient radiator temperature  
- check C.H. temperature probe  
- check by-pass  
- check gas pressures  
23  
LEGEND:  
A:JUMPER  
3. ELECTRICAL  
DIAGRAMS  
When needed, the P.C.B. allows the different options to be selected by means of  
a wire link.  
The boiler has the following basic arrangement:  
1 OPEN  
2 CLOSED (jumper)  
3 OPEN  
4 OPEN  
5 OPEN  
6 OPEN  
7 CLOSED  
8 OPEN (MFFI); CLOSED (SYSTEM)  
NOTE: under absolutely no circumstances must jumpers 2, 7 and 8 be removed.  
The opening of such contacts will lead to boiler malfunction.  
This is the factory configuration. It is recommended that this set-up not be  
changed, unless under the following particular circumstances:  
JUMPER 3: if the contact is closed, the Secondary Output (flying clamp  
connected to connection C7; positions 1-9) controls a LPG valve  
(optional).  
JUMPER 4: if the contact is closed, the continuous operation of the pump is  
selected. If the contact remains open, it has no effect and there is  
no change in the operation of the boiler.  
JUMPER 5: if the contact is closed, the signal transmitted by the connection of  
the secondary output clasp (connected to C7; positions 1-9)  
relates to a secondary pump (optional). If the contact remains  
open, the output signal controls a zone valve (optional).  
JUMPER 6: not used  
JUMPER 7/8:  
7
N.I.  
I.  
N.I.  
I.  
8
N.I.  
N.I.  
I.  
CONFIGURATION  
Central heating only  
MFFI  
Not used  
RFFI System  
I = inserted (contact closed)  
N.I = not inserted (contact open)  
I.  
NOTE: it is essential that the operations involving setting of the jumpers be  
carried out only with the device turned off.  
B: Control microprocessor  
C: Flame detection jumper (under no circumstances should this jumper be  
moved from the 1-2 position)  
D: Anti-cycling device (RA)  
E: Maximum heating output regulation (PR)  
F: Soft-light regulation (RLA)  
G: Operating mode selector knob  
H: Heating temperature adjustment  
I: Domestic hot water temperature adjustment  
J: Remote control module  
K: Main microprocessor  
L: Relay  
M: Fuses (2 x 0.54 A SLOW)  
N: Transformer (PRI: 230V-50Hz; SEK: 10V-0,8VA; SEK:10V-3,5VA; SEK:10V-  
3,5VA;)  
O: Fuses (2 x 3.15 A SLOW)  
P: Earth  
Q: Spark generator  
R: Connection to the main P.C.B.  
S: Comfort light  
T: Programming keys  
U: Comfort key  
V: Alpha-numeric display  
X: Set and reset key  
W: Connection to PC  
24  
C1 = FAN  
1:  
2:  
3:  
4:  
5:  
6:  
Hallsensor power supply 12V (red)  
Hallsensor ground (blue)  
Not used  
Start of coil (black)  
Hallsensor input (white)  
End of coil (brown)  
C2 = POWER SUPPLY  
1:  
2:  
3:  
4:  
5:  
6:  
Earth (yellow/green)  
Earth (yellow/green)  
Not connected  
Neutral (blue)  
Not connected  
Live (brown)  
C3 = CONNECTION TO ROOMSTAT  
1:  
2:  
Input - 1  
Input - 2  
C4 = TIMER  
1:  
2:  
3:  
4:  
3 V output  
Timer ground  
Timer output  
Not connected  
C5 = REMOTE CONTROL (Bus+/Bus-)  
1:  
2:  
Input/output-1  
Input/output-2  
C6 = SENSOR CONNECTOR  
1:  
2:  
3:  
4:  
5:  
6:  
7:  
8:  
9:  
Domestic hot water flow switch (grey)  
Main circuit flow switch (grey)  
Under floor heating thermostat (grey)  
Heating flow sensor (grey)  
Heating return sensor (grey)  
Domestic hot water sensor (grey)  
Not used: jumper  
Outdoor sensor (grey)  
Domestic hot water flow switch (grey)  
10: Main circuit flow switch (grey)  
11: Under floor heating thermostat (grey)  
12: Flow sensor (grey)  
13: Heating sensor (grey)  
14: Domestic hot water sensor (grey)  
15: Not used: under floor heating  
16: Outdoor sensor (grey)  
C7 = EQUIPMENT CONNECTIONS  
1:  
2:  
3:  
4:  
5:  
6:  
7:  
8:  
9:  
Secondary output (optional)  
Gas valve (white)  
3-way valve neutral (white)  
Pump (white)  
Ionisation (black)  
Not connected  
Ground  
Pump earth (yellow/green)  
Secondary output (optional)  
10: Gas valve (brown)  
11: 3-way valve (domestic hot water) (brown)  
12: 3-way valve (heating) (brown)  
13: Pump (brown)  
14: Not connected  
15: Earth  
16: Gas valve earth (yellow/green)  
25  
ecoGENUS 24 MFFI - ecoGENUS 24 RFFI  
26  
4. SHORT SPARE  
PARTS LIST  
ecoGENUS - 24 MFFI  
2
56 49 51 52 55 54  
53 52 51 50 49  
48 47 46  
3
1
2
3
57  
3
57  
3
3
3
3
3
108  
57  
58  
107  
106  
57  
66  
4
5
59  
64  
65  
301  
302  
301  
60  
59  
45  
44  
105  
104  
62  
61  
58  
63  
67  
68  
75  
74  
73  
6
7
7
76  
103  
69  
8
59  
95  
43  
8
7
42  
41  
72  
77  
94  
96  
102  
101  
70  
78  
79  
93  
97  
9
71  
84  
92  
90  
40  
39  
91  
89  
10  
80  
81  
98  
99  
38  
37  
81  
88  
100  
33  
83  
36  
35  
37  
36  
82  
7
34  
33  
32  
31  
84  
7
17  
86  
85  
87  
19  
16  
11  
12  
13  
28  
8
14 15 16 17 18 19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29 30  
21  
15  
311  
313  
312  
331  
332  
13  
336  
335  
333  
334  
333  
24 MFFI  
27  
ecoGENUS - 24 MFFI  
Key  
no.  
G.C. part  
no.  
ARISTON  
Part No.  
Description  
1
7
8
E25 417  
164 225  
164 338  
E25 427  
E25 429  
573294  
573520  
569236  
997147  
997077  
998127  
571438  
998802  
998144  
573727  
573172  
573528  
997207  
571649  
998765  
569390  
998672  
998668  
998459  
998889  
998888  
998651  
998077  
998894  
997206  
997151  
569387  
573521  
564264  
998791  
998792  
573768  
998801  
998670  
571444  
571441  
574248  
998490  
571987  
571441  
574248  
571447  
998013  
Expansion vessel  
Gasket 3/4"  
Temperature probe (C.H.W.)  
Motor (3-way valve)  
Fixing clip (motor)  
Flow group  
Gas valve  
Micro switch set (main flow & D.H.W.)  
Return group  
Manual vent cock  
Safety valve 1/2" 3 bar)  
Gasket 1/2"  
Time clock  
Pressure gauge  
P.C.B. (display)  
Gasket 1/4"  
Electrode (ignition/detection)  
Burner  
Electrode cable (resistive)  
Fan cable & sensor  
Fan  
Injector (G20)  
O-ring gasket  
Secondary exchanger (p-type 27kW)  
O-ring (secondary exchanger)  
Pump  
Gasket 1"  
Gasket 3/8"  
Auto air vent  
Condensate Trap  
Cap (trap filling)  
Gasket (airtight - condensate trap)  
P.C.B. (main)  
Main exchanger (aluminium)  
D.H.W. actuator Kit  
Heating pressure switch kit  
Pressure cover  
Central heating by-pass kit  
D.H.W. pressure switch kit  
Heating pressure switch kit  
Pressure cover  
1
1
1
1
1
11  
12  
13  
15  
20  
21  
22  
23  
24  
30  
38  
41  
42  
62  
64  
70  
72  
73  
75  
78  
80  
81  
83  
84  
87  
89  
90  
91  
92  
97  
1
1
1
1
1
1
1
1
1
1
1
1
1
378 814  
E26 378  
164 229  
E26 819  
E25 437  
164 261  
1
1
E26 657  
E26 658  
E25 518  
164 230  
164 282  
379 079  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
106  
311  
312  
313  
331  
332  
333  
334  
335  
336  
E25 581  
E24 077  
3-way spring kit  
Heating actuator bush  
28  
ecoGENUS - 24 RFFI SYSTEM  
2
57 50 52 53 56 55  
54 53 52 51 50  
49 48 47  
3
1
2
3
58  
3
58  
3
3
3
3
3
106  
58  
59  
105  
104  
58  
67  
4
5
60  
65  
66  
301  
302  
301  
61  
60  
46  
45  
103  
102  
63  
62  
59  
64  
68  
69  
75  
74  
73  
6
7
7
76  
101  
70  
8
8
60  
93  
44  
7
43  
42  
71  
92  
91  
88  
94  
100  
99  
9
89  
95  
72  
90  
87  
86  
41  
40  
80  
80  
77  
79  
96  
97  
39  
38  
78  
7
7
98  
34  
37  
36  
38  
37  
19  
10  
85  
18  
35  
34  
33  
32  
11  
84  
83  
82  
81  
11  
12  
13  
7
29  
14  
15 16  
8
17 18 19 20  
21 22 21  
17  
23  
24 25  
21  
26  
27  
28  
29  
30 31  
23  
14  
331  
336  
335  
332  
333  
334  
333  
24 RFFI SYSTEM  
29  
ecoGENUS - 24 RFFI SYSTEM  
Key  
no.  
G.C. part  
no.  
ARISTON  
Part No.  
Description  
1
7
8
E25 417  
164 225  
164 338  
E25 427  
E25 429  
573294  
573520  
569236  
997147  
997077  
998456  
571438  
573528  
997828  
573727  
573172  
997207  
571649  
998765  
569390  
998672  
998668  
998889  
998888  
998651  
998783  
997151  
569387  
573521  
998791  
573768  
998792  
564254  
998459  
998801  
998670  
571987  
571443  
571441  
574248  
571447  
998013  
Expansion vessel  
Gasket 3/4"  
Temperature probe (C.H.W.)  
Motor (3- Way valve)  
Fixing clip (motor)  
Flow group  
Gas valve  
Gasket 1/2"  
Return group  
Manual vent cock  
Safety valve 1/2" 3 bar)  
Time clock  
Pressure gauge  
P.C.B. (display)  
Gasket 1/4"  
Electrode (ignition/detection)  
Burner  
Fan cable & sensor  
Fan  
1
1
1
1
1
12  
13  
14  
17  
21  
23  
24  
25  
31  
39  
42  
43  
63  
65  
71  
73  
75A  
75B  
79  
80  
84  
86  
87  
88  
90  
164 229  
1
1
1
1
1
1
1
1
1
1
1
1
1
378 814  
E26 378  
E26 819  
E25 437  
164 261  
Injector (G20)  
Injector (G30)  
Pump  
Gasket 1"  
E25 518  
164 230  
164 282  
1
1
Gasket 3/8"  
Condensate Trap  
Gasket (airtight - condensate trap)  
Cap (trap filling)  
Auto air vent  
Electrode cable (resistive)  
P.C.B. (main)  
Main exchanger (aluminium)  
D.H.W. pressure switch kit  
Central heating by-pass kit  
Heating pressure switch kit  
Pressure cover  
1
379 079  
91  
95  
1
1
1
1
104  
331  
332  
333  
334  
335  
336  
1
1
1
1
1
1
1
1
1
1
1
1
E24 077  
3-way spring kit  
Heating actuator bush  
30  
Manufacturer:  
Merloni TermoSanitari SpA - Italy  
Commercial subsidiary: MTS (GB) LIMITED  
MTS Building  
Hughenden Avenue  
High Wycombe  
Bucks HP13 5FT  
Telephone: (01494) 755600  
Fax: (01494) 459775  
Technical Service Hot Line: (01494) 539579  
SPARE PARTS EXPLODED VIEW  
GAS WALL BOILERS  
Models  
ECOGENUS 24 MFFI  
Edition 1 of 1 December 1999  
2
56 49 51 52 55 54  
53 52 51 50 49  
48 47 46  
3
1
2
3
57  
3
57  
3
3
3
3
3
108  
57  
58  
107  
106  
57  
66  
4
5
59  
64  
65  
301  
302  
301  
60  
59  
45  
44  
105  
104  
62  
61  
58  
63  
67  
68  
75  
74  
73  
6
7
7
76  
103  
69  
8
59  
95  
43  
8
7
42  
41  
72  
77  
94  
96  
102  
101  
70  
78  
79  
93  
97  
9
71  
92  
90  
40  
39  
91  
89  
10  
80  
81  
98  
99  
38  
37  
84  
84  
81  
88  
100  
33  
83  
36  
35  
37  
36  
82  
7
17  
34  
33  
32  
31  
7
86  
85  
87  
19  
16  
11  
12  
13  
28  
8
14 15 16 17 18 19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29 30  
code 998144  
code 571438  
311  
313  
312  
code 998127  
331  
332  
336  
335  
333  
MODELS  
ECOGENUS 24 MFFI  
CHARACTERISTICS  
SERIAL NO:  
VALIDITY  
REF.  
334  
333  
METHANE  
9933500098  
A
PART. CODE DESCRIPTION  
REF.  
NOTE  
1
2
3
573294 Expansion vessel  
573310 Expansion vessel insert  
574302 Casing support bracket (Plastic)  
573244 3/8" lock nut  
4
5
6
------  
------  
Frame  
Hydraulic group support  
11  
11  
7
573520 Gasket 3/4"  
8
9
569236 Temperature probe (C.H.W.)  
998655 Pipe (C.H. flow)  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
64  
65  
998656 Pipe (gas valve/burner jet)  
997147 Motor (3-Way valve)  
997077 Fixing clip (motor)  
998127 Flow group  
570615 1/8" Brass plug  
571438 Gas valve  
565048 O-ring gasket (gas valve)  
998665 Union (gas valve)  
573793 Intake (pressure - control valve)  
573824 Bracket (M/Flow Micro Switch)  
998802 Micro switch set (main flow & D.H.W.)  
998144 Return group  
573727 Manual vent cock  
573172 Safety valve (1/2" 3 bar)  
573528 Gasket 1/2"  
573311 Pipe (expansion vessel)  
998674 Wiring (power supply)  
573302 Summer/Winter selector kit  
998747 Control knob kit  
998661 Door (instruction/time clock)  
997207 Time clock  
998772 On/off push button kit  
998778 Control panel (front)  
998751 Button (reset)  
999073 Cover (display)  
998766 Film (display)  
998381 Pin (front cover)  
998739 Fixing spring (front cover)  
571649 Pressure gauge  
------  
Control panel  
11  
11  
571562 Cable clamp  
998765 P.C.B. (display)  
569390 Gasket 1/4"  
------  
Cover (connectors)  
999060 Low voltage wiring  
998676 High voltage wiring  
998076 View window glass gasket  
998075 View window glass  
574104 Panel (sealed chamber - front)  
573247 Panel (sealed chamber - side)  
------  
Sealed chamber  
11  
573865 Flue gasket  
573330 Air return cover  
573326 Flue intake plug  
998474 Flue exhaust manifold / header  
573337 Gasket (flue manifold)  
572984 Casing support bracket  
570717 Spring (fastening)  
998666 Nipple (gas - 3/4" M/M)  
998785 Dowel (M6x35)  
998782 View window glass  
998775 Retaining ring (D=16mm)  
998672 Electrode (Ignition/Detection)  
998767 Cap (electrodes)  
998668 Burner  
998680 Gasket (elbow)  
PART. CODE DESCRIPTION  
REF.  
NOTE  
66  
67  
998788 Elbow (fan)  
------ Flame mirror  
11  
68  
69  
70  
71  
72  
73  
998786 Diaphragm (condensing boiler)  
998654 Pipe (C.H. return)  
998459 Electrode cable (resistive)  
999071 Pipe (fan suction silencer)  
998889 Fan cable & sensor  
998888 Fan  
74  
998681 Gasket (fan inlet)  
75  
998651 Injector (G20)  
76  
570772 Cable holder  
77  
998065 By-pass pipe  
78  
998077 O-ring gasket  
79  
80  
81  
82  
998064 Spring (by-pass pipe)  
573295 Secondary exchanger (p-type 27kW)  
573825 O-Ring (secondary exchanger)  
573576 Compensation tube  
997151 Pump  
83  
84  
569387 Gasket 1"  
85  
86  
87  
998019 Pipe (safety valve outlet)  
998567 Safety valve outlet pipe ring nut  
573521 Gasket 3/8"  
88  
89  
998413 Pipe (condensate - plastic)  
564254 Auto air vent  
90  
998791 Condensate Trap  
91  
998792 Cap (trap filling)  
92  
93  
94  
95  
96  
97  
573768 Gasket (airtight - condensate trap)  
998412 Pipe (drain - plastic)  
998787 Condensate tray (aluminium)  
998808 Gasket (adhesive - 10x5 mm)  
998784 Fixing nut (tray rear)  
998801 P.C.B. (main)  
98  
99  
998382 Grommet (regulation access)  
569720 Blind grommet  
100  
101  
102  
103  
104  
105  
106  
107  
108  
998653 L.E.D. lens  
569424 On/off neon switch  
998460 Gasket (igniter insulation)  
998777 Aluminium inspection lid  
573766 Front cover gasket  
------  
998670 Main exchanger (aluminium)  
------ Top fixing bracket  
Bottom fixing bracket  
11  
11  
998423 Lip gasket (D=66 mm)  
301  
302  
998414 Case panel (side)  
998478 Case panel (front)  
311  
312  
313  
571444 D.H.W. actuator Kit  
571441 Heating pressure switch kit  
574248 Pressure cover  
331  
332  
333  
334  
335  
336  
998490 Central heating by-pass kit  
571987 D.H.W. pressure switch kit  
571441 Heating pressure switch kit  
574248 Pressure cover  
571447 3-Way spring kit  
998013 Heating actuator bush  
NOTE DESCRIPTION  
11  
Not supplied as a spare part  

AGFA 500 D User Manual
Blaupunkt PCA 2100 User Manual
Boss Audio Systems Car Stereo System CCR612 User Manual
DeLonghi DBL740 Series User Manual
Gateway 8450R User Manual
Haier JC 110GD User Manual
Hitachi VM 3700A User Manual
Hypertec 6102HY User Manual
JBL VT4880 User Manual
JVC Everio Digital Camcorder LYT1994 001B M User Manual