EMERSON LIEBERT GXT4 8000RT208 User Manual

Liebert® GXT4UPS 208 V, 5000 VA – 10,000 VA, 6000RTL630  
User Manual  
Table of Content  
i
Liebert® GXT4User Manual  
Liebert® GXT4User Manual  
ii  
iii  
Liebert® GXT4User Manual  
List of Figures  
Figure 1-7: Power distribution models for 8000 VA and 10,000 VA models (continued) . . . . . . . . . . . . . . . . . . . . 11  
Liebert® GXT4User Manual  
iv  
List of Tables  
Liebert® GXT4User Manual  
vi  
Important Safety Instructions  
Important Safety Instructions  
SAVE THESE INSTRUCTIONS  
This manual contains important safety instructions. Read all safety and operating instructions before  
operating the uninterruptible power system (UPS). Adhere to all warnings on the unit and in this manual.  
Follow all operating and user instructions. This equipment can be operated by individuals without previous  
training.  
This product is designed for commercial/industrial use only. It is not intended for use with life support and  
other designated “critical” devices. Maximum load must not exceed that shown on the UPS rating label.  
The UPS is designed for data processing equipment. The UPS is not for use in a computer room as  
defined in the standard, Protection of Electronic Computer/Data Processing Equipment ANSI/NFPA 75. If  
uncertain, consult your dealer or local Emerson Network Power® representative.  
This UPS is designed for use on a properly grounded (earthed), 100/200, 110/220, 115/230,  
120/208,120/240 or 127/220VAC, 50 or 60Hz supply. The factory default setting is 120/208VAC, 60Hz.  
Installation instructions and warning notices are in this manual.  
The Liebert GXT4 208VAC 5000 - 10000 is designed for use with a four-wire input (L1, L2, N, G).  
The Liebert GXT4-6000RTL630 is designed be used with a three-wire, two-phase utility source (L1, L2, G).  
WARNING  
precautions should be observed when replacing the battery pack:  
!
The battery can present a risk of electrical shock and high short circuit current. The following  
• Wear rubber gloves and boots  
• Remove rings, watches and other metal objects.  
• Use tools with insulated handles.  
• Do not lay tools or other metal objects on the batteries.  
• If the battery kit is damaged in any way or shows signs of leakage, contact your local Emerson  
representative immediately.  
• Do not dispose of batteries in a fire. The batteries may explode.  
• Handle, transport and recycle batteries in accordance with local regulations.  
WARNING  
improper use can result in electrical shock or fire. To ensure safety, observe the following  
precautions:  
!
Although the Liebert GXT4 has been designed and manufactured to ensure personal safety,  
• Turn Off and unplug the Liebert GXT4 before cleaning it.  
• Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.  
• Never block or insert any objects into the ventilation holes or other openings of the UPS.  
• Do not place the Liebert GXT4 power cord where it might be damaged.  
ELECTROMAGNETIC COMPATIBILITY—The Liebert GXT4 complies with the limits for a Class A digital  
device, pursuant to Part 15 of FCC rules.  
Operation is subject to the following conditions:  
• This device may not cause harmful interference.  
• This device must accept any interference received, including interference that may cause undesired  
operation. Operating this device in a residential area is likely to cause harmful interference that users  
must correct at their own expense.  
The Liebert GXT4 series complies with the requirements of EMC Directive 2004/108/EC and the published  
technical standards. Continued compliance requires installation in accordance with these instructions and  
use of accessories approved by Emerson.  
1
Liebert® GXT4User Manual  
 
Important Safety Instructions  
NOTICE  
This is a product for restricted sales distribution to informed partners. Installation restrictions or  
additional measures may be needed to prevent radio interference.  
Operate the UPS in an indoor environment only in an ambient temperature range of 0-40°C (32-104°F).  
Install it in a clean environment, free from moisture, flammable liquids, gases and corrosive substances.  
The Liebert GXT4-5000RT208, Liebert GXT4-6000RT208 and the Liebert GXT4-6000RTL630 contain no  
user-serviceable parts except the internal battery pack. The Liebert GXT4-10000RT208 and the Liebert  
GXT4-8000RT208 contain no user-serviceable parts except the internal battery pack and the Power  
Module. The UPS On/Off push buttons do not electrically isolate internal parts. Under no circumstances  
attempt to gain access internally due to the risk of electric shock or burn.  
Do not continue to use the UPS if the front panel indications are not in accordance with these operating  
instructions or the UPS performance alters in use. Refer all faults to your dealer.  
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the  
required precautions. Keep unauthorized personnel away from the batteries. Keep unauthorized personnel  
away from the batteries. Proper disposal of batteries is required. Refer to your local laws and regulations  
for disposal requirements.  
Never block or insert any object into the ventilation holes or other openings.  
DO NOT CONNECT equipment that could overload the UPS or demand DC current from the UPS, for  
example: electric drills, vacuum cleaners, laser printers, hair dryers or any appliance using half-wave  
rectification.  
Storing magnetic media on top of the UPS may result in data loss or corruption.  
Turn Off and isolate the UPS before cleaning it. Use only a soft cloth, never liquid or aerosol cleaners.  
Information for the Protection of the Environment  
UPS SERVICING—This UPS makes use of components dangerous for the environment (electronic cards,  
electronic components). The components removed must be taken to specialized collection and disposal  
centers.  
Liebert® GXT4User Manual  
2
Glossary of Symbols  
Glossary of Symbols  
Risk of electrical shock  
Indicates caution followed by important instructions  
!
AC input  
AC output  
Requests the user to consult the manual  
i
+
-
Indicates the unit contains a valve-regulated lead acid battery  
PbH2SO4  
Recycle  
R
DC voltage  
Equipment grounding conductor  
Bonded to ground  
AC voltage  
WEEE  
3
Liebert® GXT4User Manual  
 
Glossary of Symbols  
Page intentionally left blank.  
Liebert® GXT4User Manual  
4
Product Description  
1.0 Product Description  
The Liebert GXT4 is a compact, online uninterruptible power system (UPS) that continuously conditions  
and regulates its output voltage. The UPS is designed to supply microcomputers and other sensitive  
electronic equipment with clean sine wave input power.  
Upon generation, AC power is clean and stable. However, during transmission and distribution it is subject  
to voltage sags, spikes and complete failure that may interrupt computer operations, cause data loss and  
damage equipment.  
The Liebert GXT4 protects equipment from these disturbances. The Liebert GXT4 continuously charges its  
batteries from the mains, enabling it to supply power to connected loads, even when the mains fail.  
This section describes the UPS, its features, models, appearance and components, operating principles  
and operating mode.  
1.1 Features  
The UPS includes these features:  
• Intelligent battery management to extend battery life  
• LCD for user-friendly operation and local monitoring and configuration of operational parameters  
• Flexible network management with Liebert MultiLink® software  
• Fan fault self-inspection and automated diagnostic function  
• Intelligent fan operation, automatically changing rotation speed depending on system requirements, to  
decrease power consumption and noise  
• Input circuit breaker to ease recovery from overloads  
• CE mark and safety approval from CE  
• Communication options: USB port, Liebert IntelliSlot® port and terminal block communication  
• Dry contacts for remote monitoring  
• Input power factor greater than 0.99  
• Output voltage selection function  
1.2 Available Models  
Available models of the UPS are listed in Table 1-1:  
Table 1-1 UPS models, power ratings  
Model Number  
GXT4-5000RT208  
GXT4-6000RT208  
GXT4-6000RTL630  
GXT4-8000RT208  
GXT4-10000RT208  
Nominal Power Rating  
5000VA / 4000W  
6000VA / 4800W  
6000VA / 4200W  
8000VA / 7200W  
10000VA / 9000W  
5
Liebert® GXT4User Manual  
       
Product Description  
1.3 Appearance and Components  
1.3.1 Appearance  
The Liebert GXT4 rack/tower models in various power ratings have the same general appearance,  
controls and features (see Figure 1-1). The various rack/tower models differ largely in the type of  
receptacles each has.  
Figure 1-1 Liebert GXT4 5000VA and 6000VA, front view  
Upper Bezel  
Operation and Display Panel  
Operation and  
Upper Bezel  
Display Panel  
Lower Bezel and Battery Access Door  
Lower Bezel and Battery Access Door  
1.3.2 Rear Panel Features  
The rear panel of the Liebert GXT4 has these features:  
• Liebert IntelliSlot® Port  
• USB port  
• Input Circuit Breaker  
• Maintenance Bypass Circuit Breaker (not present on all optional POD’s)  
• REPO connection  
• Input Receptacle  
• General Output Receptacles (on optional PODs)  
• External Battery Connector  
• Cooling Fan  
Terminal Block Communication  
• Output Circuit Breakers (on optional PODs)  
Liebert® GXT4User Manual  
6
       
Product Description  
Figure 1-2 Rear panel—5000VA and 6000VA with input power hard-wired box  
Knockouts for  
Liebert IntelliSlot  
Unity-DP Card  
Hard-Wired  
Power Input  
and Output  
USB Port  
REPO  
Terminal Block  
Communication  
External Battery  
Connector  
Input Breaker  
NOTE  
Hard-wired and hard-wired/receptacle boxes that include a manual bypass switch permit AC  
power to continue to flow from the utility input to the load while the box is removed from the UPS.  
For details, refer to 2.6 - Connect Input/Output Power.  
Figure 1-3 Rear panel—GXT4-6000RTL630  
Output Breaker  
for L6-30R #4  
REPO Connection  
Block  
Output Breaker for  
L6-20R #2 and #3  
Terminal Block  
Communication  
USB Port  
External  
Battery  
Connector  
Liebert IntelliSlot  
Unity-DP Card  
Input Breaker  
for L6-30P #1  
IT Power  
System  
Access  
Cover  
Maintenance  
Bypass Breaker  
Output Breaker  
for L6-30R #5  
5
2
1
4
3
7
Liebert® GXT4User Manual  
   
Product Description  
Figure 1-4 Rear panel—8000VA  
Terminal Block  
Communication  
Liebert IntelliSlot  
Unity-DP Card  
REPO Connection Block  
Maintenance  
Bypass Switch  
USB Port  
Output Breaker  
Switch  
Input  
Breaker  
Switch  
Cover for Power  
Distribution Box  
Connections  
Knockouts  
for Hard-Wired  
Power Input  
External Battery  
Connectors  
Liebert® GXT4User Manual  
8
 
Product Description  
1.4 Removable Power Distribution Box  
The UPS is shipped with a power-distribution pack installed. This box contains the UPS input circuit  
breaker.  
Figure 1-5 Power distribution models for 5000 VA and 6000 VA models  
PD2-001 shown as example;  
similar features on other distribution  
boxes arranged differently  
L14-30 Input  
Output Power  
Breakers for  
Pigtails  
Power Connector  
Push Button Output  
Maintenance  
Bypass Breaker  
Power Breakers for  
L5-20 Receptacles  
PD2-001  
Receptacles: four 5-20; one  
L14-30 Output  
Power  
Connectors  
L14-30; one L6-30R  
PD2-005  
Receptacles: four L5-20R; two L6-30R  
PD2-002  
Receptacles: two 5-20R; two L6-20R  
PD2-003  
PD2-006  
receptacles: four 5-20R; two L6-30R  
Receptacles: four L6-20R; two L6-20R  
PD2-004  
PD2-007  
Receptacles: four L5-20R; two L5-30R  
Receptacles: two L6-30R; two L6-20R  
9
Liebert® GXT4User Manual  
   
Product Description  
Figure 1-6 Power distribution models for 8000 VA and 10,000 VA models  
PD2-101 shown as example;  
similar features on other  
distribution boxes arranged differently  
5-20R Output  
Receptacles  
Output Circuit Breaker  
Switch for L6-30R Pigtail #1  
L6-30ROutput  
Receptacles  
Push Button  
CircuitBreakers  
for 5-20R  
Receptacles  
5-20R Output  
Receptacles  
2
1
Output Circuit Breaker  
Switch for L6-30R Pigtail #2  
PD2-101  
Receptacles: two L6-30R; eight 5-20R  
PD2-105  
Receptacles:  
four 5-20R  
two L5-30R  
two L5-20R  
PD2-102  
Receptacles:  
four L6-20R  
four 5-20R  
PD2-103  
Receptacles:  
four L6-30R  
four 5-20R  
PD2-106  
Receptacles:  
four L6-20R  
four L5-20R  
PD2-104  
Receptacles:  
four 5-20R  
two L6-30R  
two L6-20R  
Liebert® GXT4User Manual  
10  
   
Product Description  
Figure 1-7 Power distribution models for 8000 VA and 10,000 VA models (continued)  
PD2-201  
Receptacles:  
two IEC320-C19  
eight IEC320-C13  
PD2-107  
Receptacles: four L5-20R;  
four 5-15R  
PD2-108  
Receptacles:  
two L6-30R;  
two L6-20R  
PD2-202  
Receptacles:  
(12) IEC320-C13  
PD2-109  
Receptacles:  
two L14-30R  
PD2-204  
Receptacles:  
two IEC309-32A  
four IEC320-C13  
PD2-200  
Receptacles:  
four IEC320-C19  
four IEC320-C13  
11  
Liebert® GXT4User Manual  
 
Product Description  
1.5 Internal Battery Packs  
The UPS has two internal battery packs behind a battery access door on the front of the unit. Each internal  
battery pack is fitted with a connector to link to the UPS.  
NOTE  
GXT4 10,000-VA battery pack shown in Figure 1-8. 5000-VA and 6000-VA  
battery packs have the same features.  
Figure 1-8 Internal battery pack with connector  
Battery Handle  
Battery Connector  
Front of Battery Pack  
1.6 Major Components  
The UPS is composed of mains input, TVSS and EMI/RFI filters, rectifier/PFC, inverter, battery charger,  
DC-to-DC converter, battery, dynamic bypass and UPS output.  
Maintenance Bypass  
(5/6 kVA in POD)  
(8/10 kVA in frame)  
Internal  
Bypass  
General Outlet  
(POD  
Dependent )  
L1  
Rectifier/PFC  
L1  
TVSS  
EMI/RFI  
Input  
General Outlet  
(POD  
Dependent )  
DC-DC  
Inverter  
L2  
EMI/RFI  
Output  
Filter  
Converter  
L2  
N
G
Filter  
N
G
General Outlet  
(POD  
Dependent )  
Battery  
Charger  
General Outlet  
(POD  
Dependent )  
General Outlet  
(POD  
Dependent )  
Battery  
1.6.1 Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters  
These UPS components provide surge protection and filter both electromagnetic interference (EMI) and  
radio frequency interference (RFI). They minimize any surges or interference present in the mains line and  
keep the sensitive equipment protected.  
Liebert® GXT4User Manual  
12  
       
Product Description  
1.6.2 Rectifier/Power Factor Correction (PFC) Circuit  
In normal operation, the rectifier/power factor correction (PFC) circuit converts mains AC power to  
regulated DC power for use by the inverter while ensuring that the waveshape of the input current used by  
the UPS is near ideal. Extracting this sinewave input current achieves two objectives:  
• The mains power is used as efficiently as possible by the UPS.  
• The amount of distortion reflected on the mains is reduced.  
This results in cleaner power being available to other devices in the building not being protected by the  
Liebert GXT4.  
1.6.3 Inverter  
In normal operation, the inverter utilizes the DC output of the power factor correction circuit and inverts it  
into precise, regulated sinewave AC power. Upon a mains power failure, the inverter receives its required  
energy from the battery through the DC-to-DC converter. In both modes of operation, the UPS inverter is  
on-line and continuously generating clean, precise, regulated AC output power.  
1.6.4 Battery Charger  
The battery charger utilizes energy from the mains power and precisely regulates it to continuously float  
charge the batteries. The batteries are being charged whenever the Liebert GXT4 is connected to mains  
power.  
1.6.5 DC-to-DC Converter  
The DC-to-DC converter utilizes energy from the battery system and raises the DC voltage to the optimum  
operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency  
and voltage, thus increasing reliability.  
1.6.6 Battery  
The Liebert GXT4 utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery design life,  
operate the UPS in an ambient temperature of 15°C to 25°C (59°F to 77°F). Optional external battery  
cabinets are available to extend battery run times. For run times, see Table 8-8.  
1.6.7 Internal Bypass  
The Liebert GXT4 provides an alternate path for mains power to the connected load in the unlikely event of  
a UPS malfunction. Should the UPS have an overload, overtemperature or any other UPS failure  
condition, the UPS automatically transfers the connected load to bypass. Bypass operation is indicated by  
an audible alarm and illuminated amber Bypass LED (other LEDs may be illuminated to indicate the  
diagnosed problem). To manually transfer the connected load from the inverter to bypass, press the  
Standby/Manual Bypass button once and hold it for about 2 seconds  
1.6.8 Maintenance Bypass  
The Liebert GXT4 provides a manual maintenance bypass in a removable section of the rear of the UPS.  
This allows replacement of the UPS in the event of a UPS malfunction while keeping the connected  
equipment powered with utility power.  
NOTE  
The bypass power path does NOT protect the connected equipment from disturbances in  
the mains supply.  
13  
Liebert® GXT4User Manual  
             
Product Description  
1.7 Operating Mode  
The UPS operation modes include the following: Mains (AC) Mode, Bypass Mode, Battery Mode, Battery  
Recharge Mode, Active ECO Mode and Frequency Converter Mode.  
Refer to 3.0 - Operation and Display Panel for details about the operating mode indicators and control  
buttons.  
1.7.1 Mains Mode  
During Mains Mode, the mains provides input power to the Liebert GXT4. The filters, PFC circuit and  
inverter process this power to provide high-quality sine wave power to connected loads. The UPS  
maintains the batteries in a fully charged state.  
1.7.2 Manual Bypass Mode  
Manual Bypass Mode occurs when the unit is manually placed in internal bypass by navigating the LCD  
menu to select 3 Control > 1 Turn On & Off > Turn UPS Bypass. Bypass operation is indicated by an  
audible alarm and illuminated amber bypass indicator. (If other indicators are illuminated, refer to 7.0 -  
Troubleshooting). During Bypass Mode, mains power bypasses the inverter and provides energy to the  
connected load.  
NOTICE  
Risk of loss of power to the connected load. Can cause equipment damage.  
Turning Off the UPS in Bypass Mode will result in loss of output power to the connected load.  
1.7.3 Battery Mode  
The Liebert GXT4 enters Battery Mode when mains power fails or is outside acceptable limits. The battery  
system supplies power through the DC-to-DC converter to the inverter to generate clean AC power for the  
connected loads.  
When the Liebert GXT4 enters Battery Mode, the UPS sounds a half-second beep at 10-second intervals.  
When approximately 2 minutes of run time remains, the beeps sound every 5 seconds to warn that the  
battery is getting low (this Low Battery Warning is user-configurable).  
In Battery Mode, the battery indicator will illuminate and the LCD will show the prompt utility power not  
available.  
Press either the Up or Down button once, then press the Enter button to clear the prompt and silence the  
audible alarm. Once the alarm prompt has been acknowledged, the screen showing the estimated battery  
run time and battery capacity will be visible. Refer to 7.0 - Troubleshooting.  
For approximate battery run times, refer to Table 8-4.  
NOTICE  
Risk of loss of power to the connected load. Can cause equipment damage.  
Turning Off the Liebert GXT4 when it is in Battery Mode will result in loss of output power to the  
connected load.  
If the UPS is turned Off manually, it must be manually restarted after mains power returns.  
If the UPS is turned Off by a communication signal or because the batteries are depleted, it will  
operate as set in the configuration program for Auto-Restart (Refer to 5.2.1 - Configuration  
Program).  
1.7.4 Battery Recharge Mode  
Once mains power is applied to the Liebert GXT4, the Battery Charger begins charging the batteries.  
Liebert® GXT4User Manual  
14  
         
Product Description  
1.7.5 Frequency Converter Mode  
All models of the Liebert GXT4 are capable of frequency conversion. Frequency Conversion Mode can be  
selected using the configuration program. Allowable frequency operating modes include:  
• Auto Sensing - 50Hz or 60Hz – Bypass Enabled  
• Auto Sensing - 50Hz or 60Hz – Bypass Disabled  
• Frequency Converter - 50Hz – Bypass Disabled  
• Frequency Converter - 60Hz – Bypass Disabled  
NOTE  
The default for all models of the Liebert GXT4 is “Auto Sensing - 50Hz or 60Hz – Bypass  
Enabled.”  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
Never touch the AC input receptacle while the UPS is operating. Voltage may still be present even  
when the AC input indicator is Off.  
1.7.6 Active ECO Mode  
All Liebert GXT4 models can operate in Active ECO Mode. In this mode, the connected equipment is  
powered through the bypass path to increase efficiency, reducing the electrical costs.  
Active ECO mode keeps the rectifier and inverter operating, allowing the inverter to remain synchronized  
to bypass. This synchronization allows the transfer of the connected equipment to UPS inverter power  
almost seamlessly if bypass power falls outside the user-set limits. Once bypass power returns within the  
acceptable parameters, the UPS will return to Active ECO Mode operation.  
The default setting is Active ECO Mode Off.  
15  
Liebert® GXT4User Manual  
   
Product Description  
Page intentionally left blank.  
Liebert® GXT4User Manual  
16  
Installation  
2.0 Installation  
Do NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until instructed to  
2.1 Unpacking and Inspection  
Unpack the UPS and conduct the following checks:  
• Inspect the UPS for shipping damage. Report any shipping damage to the carrier and your local dealer  
or Emerson® representative immediately.  
• Check the accessories against the delivery list. If there is any discrepancy, contact your local dealer or  
your Emerson representative immediately  
CAUTION  
moving it.  
!
The UPS is heavy (see 8.0 - Specifications). Take proper precautions when lifting or  
2.2 What’s Included  
The Liebert GXT4 is shipped with the following items:  
Terminal Block Communication terminals  
• Compact Disk with  
• Liebert MultiLink®  
• Configuration program  
• User manual (electronic version)  
• Liebert IntelliSlot® Web card (IS-WEBCARD), factory-installed  
• USB cable, one; 1.2 m (3.9 ft.)  
• Rack mounting hardware including screws, handles, and rack slide kit  
• Power Distribution Box, installed on Liebert GXT4  
• Support base set, one  
• Warnings, Safety Instructions booklet and WEEE recycling sheet (ISO 14001 compliance)  
NOTE  
The GXT4 External Battery Cabinet shipping package includes one battery cabinet, two spacers  
for tower configuration, one DC power cable and rack mounting hardware, including screws,  
handles and mounting rail kit.  
17  
Liebert® GXT4User Manual  
     
Installation  
2.3 Preparation for Installation  
2.3.1 Installation Environment  
Install the Liebert GXT4 indoors in a controlled environment, where it cannot be accidentally turned Off.  
Place it where air flows unrestricted around the unit. The installation location must be free of water,  
flammable liquids, gases, corrosives and conductive contaminants. Maintain an ambient temperature  
range of 0 to 32 - 104°F (0 – 40°C).  
NOTE  
UPS operation in sustained temperatures outside the range of 59° – 77°F (15 – 25°C)  
reduces battery life.  
Installation Clearances  
Maintain a clearance of at least 100 mm (4 inches) in the front and rear of the Liebert GXT4. Do not  
obstruct the air inlets on the front panel or rear panel of the UPS—blocking the air inlets reduces ventilation  
and heat dissipation, shortening the service life of the Liebert GXT4.  
2.4 Install the Main Cabinet  
The Liebert GXT4 may be installed in either a tower configuration or in a rack, depending on available  
space and use considerations. Determine the type of installation and follow the appropriate instructions in  
2.4.1 Tower UPS Installation  
To install the Liebert GXT4 as a tower:  
1. Take the support bases out of the accessories bag (see Figure 2-1).  
Figure 2-1 Support bases  
Spacers  
Connectors  
Support Bases  
2. If optional Liebert external battery cabinets will be connected to the Liebert GXT4, take out the spacers  
shipped with the battery cabinet.  
3. Connect the spacers and the support bases as shown in Figure 2-1. Each Liebert GXT4 needs two  
assembled support bases, one in the front and one in the rear.  
Liebert® GXT4User Manual  
18  
         
Installation  
4. Adjust the direction of the operation and display panel and logo on the Liebert GXT4.  
a. Remove the front plastic bezel cover as shown in Figure 2-2.  
Figure 2-2 Remove the front plastic bezel cover  
Front plastic  
bezel cover  
b. Pull the operation and display panel gently, rotate it 90 degrees clockwise and snap it back into  
position, as shown in Figure 2-3.  
Figure 2-3 Rotate the operation and display panel  
Operation and  
display panel  
rotated clockwise  
90 degrees  
c. Pull the logo on the front plastic bezel cover gently, rotate it 90 degrees clockwise and snap it back  
into position. The rotated front plastic bezel cover is shown in Figure 2-3.  
d. Replace the front plastic bezel cover on the Liebert GXT4. At this point, the UPS operation and  
display panel and logo have been rotated 90 degrees clockwise, which provides upright viewing  
for users.  
5. Place the Liebert GXT4 and any battery cabinets on the support bases. Each Liebert GXT4 needs two  
support assemblies.  
2.4.2 Rack Installation  
The Liebert GXT4 UPS and external battery cabinets (EBC), when installed in a rack enclosure, must be  
supported by a shelf or rack-mount rails. The Liebert GXT4 UPS and EBC units ship with all required  
hardware to allow rack-mount installation. Because different rack-mount options install differently, refer to  
the installation instructions provided with the rack mount kit being used.  
CAUTION  
!
The GXT4 is heavy; see 8.0 - Specifications. The UPS must be installed as near the bottom of a  
rack as possible. If placed too high, it can make the rack top-heavy and prone to tipping over.  
19  
Liebert® GXT4User Manual  
     
Installation  
2.5 External Battery Cabinet Installation  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
Disconnect all local and remote electric power supplies before working within.  
Ensure that the Liebert GXT4 is shut down and power has been disconnected before beginning  
any work on or in the unit.  
CAUTION  
them.  
!
The external battery cabinet(s) are heavy (see Table 8-3). Take proper precautions when lifting  
Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run  
time. External battery cabinets are designed to be placed on one side of the UPS in a tower configuration  
or stacked beneath the UPS in a rack configuration.  
Figure 2-4 External battery cabinets connected to GXT4  
GXT4  
Cable connects battery  
cabinet  
Battery Cabinet  
Second connector permits adding  
more battery cabinets to 6000VA  
Liebert GXT4  
1. Inspect the external battery cabinet for freight damage. Report damage to the carrier and your local  
dealer or Emerson representative.  
2. Optional rack-mount hardware is shipped with the external battery cabinet and may be installed at this  
time if desired.  
• Securing hardware and slide rails are sold separately. Please contact your local dealer or Emerson  
representative for these additional options and any assistance needed. Fasten the slides into  
position with the screws per the instructions included with the slide rails.  
3. Use the enclosed support bases for the tower option to prevent tip-over. One additional set of support  
base extensions ships with each external battery cabinet.  
4. Verify the External Battery Cabinet breaker is in the Off position.  
5. Connect the supplied external battery cabinet cable to the rear of the external battery cabinet, then to  
the rear of the UPS.  
6. Turn the External Battery Cabinet breaker to the On position.  
Liebert® GXT4User Manual  
20  
   
Installation  
7. Verify the circuit breaker on the External Battery Cabinet is in the On position.  
8. Use the included configuration program or the LCD to program the UPS with the number of external  
battery cabinets connected. Instructions for the configuration program are in 5.2.1 - Configuration  
The UPS is now equipped with additional backup battery run time. For approximate battery run times, refer  
to Table 8-4.  
NOTE  
When removing an external battery cabinet, the circuit breaker on the rear of the cabinet must be  
turned off before disconnecting the cable.  
NOTE  
If the UPS is to be shipped or stored for an extended time, the connector should be disconnected.  
This will minimize any standby current drain on the batteries and help attain their design life.  
2.6 Connect Input/Output Power  
The GXT4-5000RT208, Liebert GXT4-6000RT208 and Liebert GXT4-6000RTL630 are shipped with a  
power distribution box attached. The Liebert GXT4-8000RT208 and Liebert GXT4-10000RT208 are  
shipped with a cover plate over the power distribution connector.  
Follow the instructions below for removal and installation.  
NOTE  
Do not operate the UPS with the power distribution box removed. To shut off all power to this box  
and to the load, utility input power must be disconnected.  
2.6.1 Install the Power Distribution Box on 5000VA and 6000VA Models  
1. Align the connectors and press the power distribution box onto the UPS.  
2. Hold the box firmly against the UPS and tighten the captive screws except the one over the  
maintenance bypass breaker.  
3. Turn the output and input breakers On.  
4. Start the UPS according to startup instructions.  
5. Verify that the UPS lamp is illuminated.  
6. Turn the maintenance bypass breaker Off.  
7. Insert the maintenance bypass interlock bracket behind the captive screw and tighten the screw.  
NOTE  
The maintenance bypass breaker interlock bracket must be installed behind the captive screw,  
and the screw must be tightened for the UPS to operate in inverter mode.  
21  
Liebert® GXT4User Manual  
     
Installation  
2.6.2 Remove the Power Distribution Box  
from 5000VA and 6000VA Models  
1. Manually transfer the connected equipment to the internal bypass.  
a. From the main menu select CONTROL, then press Enter.  
b. Select TURN ON & OFF and press Enter.  
c. Select TURN UPS BYPASS and press Enter. The UPS will transfer the connected loads to the  
internal bypass. (For help, refer to 4.4 - Manual Bypass.)  
d. Loosen the captive screw over the maintenance bypass breaker (see Figure 2-5 for the breaker’s  
location).  
e. Turn the maintenance bypass breaker On.  
NOTICE  
The load is unprotected from disturbances in the power supply while the UPS is on bypass.  
2. Turn the output and input breakers Off.  
3. Loosen other captive screws until the power distribution box releases.  
4. Remove the power distribution box from the UPS and set it aside.  
5. Loosen the screws over the plastic cover for the connector on the rear of the panel.  
6. Slide the plastic cover over the connector and tighten the screws.  
Figure 2-5 Power distribution box removal from 5000VA and 6000VA models  
Extract these four  
captive screws  
Pigtails  
removed for  
clarity  
Maintenance Bypass Breaker  
Liebert® GXT4User Manual  
22  
   
Installation  
2.6.3 Remove the Power Distribution Cover  
from 8000VA and 10,000VA Models  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
The UPS must be shut down or the load must be transferred to an external maintenance bypass  
before a power distribution box may be added, changed or removed.  
If the UPS will be shut down, the connected load must be shut down (refer to 4.5 - Shut Down the  
GXT4).  
If the UPS will be transferred to maintenance bypass, it must be transferred to an external  
maintenance bypass. A maintenance bypass in the UPS frame must not be used.  
Verify that the Liebert GXT4 is shut down and that all local and remote electric input power has  
been disconnected before beginning any work on or in the UPS.  
1. Shut down the Liebert GXT4 (for help, refer to 4.5 - Shut Down the GXT4).  
a. From the Main Menu select CONTROL, press Enter, then select TURN ON & OFF.  
b. Press the enter key.  
c. Select TURN UPS OFF, then press Enter.  
Power to the connected loads is now Off.  
2. Turn the output and input breakers Off.  
3. Support the power distribution box and remove the two screws at the top of the box.  
4. Remove the cover or power distribution box from the UPS and set it aside.  
5. If removing a power distribution box, carefully pull apart the power distribution box connector and the  
UPS connector.  
Figure 2-6 Power distribution box removal from 8000VA and 10,000VA models  
Extract screws at these places  
Pigtails  
removed for  
clarity  
Tabs slip into slots on UPS  
23  
Liebert® GXT4User Manual  
   
Installation  
2.6.4 Install the Power Distribution Box  
on 8000VA and 10,000VA Models  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
The UPS must be shut down or the load must be transferred to an external maintenance bypass  
before a power distribution box may be added, changed or removed.  
If the UPS will be shut down, the connected load must be shut down (refer to 4.5 - Shut Down the  
GXT4).  
If the UPS will be transferred to maintenance bypass, it must be transferred to an external  
maintenance bypass. A maintenance bypass in the UPS frame must not be used.  
Verify that the Liebert GXT4 is shut down and that all local and remote electric input power has  
been disconnected before beginning any work on or in the UPS.  
1. With the cover or distribution box removed, press the UPS and distribution box connectors together.  
Ensure that the connectors are fully seated.  
2. Align the screw holes and press the power distribution box onto the UPS, making sure that the tabs at  
the bottom of the box fit into the slots on the UPS.  
3. Attach the box to the UPS by installing screws into the two holes at the top of the box.  
4. Tighten the screws.  
5. Turn the output and input breakers On.  
6. Start the UPS according to startup instructions.  
2.6.5 Distribution Box Electrical Connections  
Electrical connections are made through a removable power distribution box that attaches to the rear of the  
UPS.  
• PD2-HDWR-MBS, PD2-001, PD2-002, PD2-003, PD2-004, PD2-005, PD2-006 and PD2-007 models  
fit the 5000 and 6000VA models of the Liebert GXT4  
• PD2-L630 fits the GXT4-6000RTL630  
• PD2-101, PD2-102, PD2-103, PD2-104, PD2-105, PD2-106, PD2-107, PD2-108, PD2-109, PD2-200,  
PD2-201, PD2-202, PD2-204models fit the 8000 and 10,000VA models of the Liebert GXT4  
The installer must provide an upstream branch circuit breaker. The input circuit breaker on the distribution  
box and the output circuit breaker on the rear of the power distribution box disconnect all power between  
the main cabinet and the distribution box.  
Models equipped with a manual bypass breaker pass bypass power directly to the bypass breaker from the  
input terminal block. The input circuit breaker on the distribution box does not disconnect power from the  
manual bypass breaker.  
Table 2-1 Branch circuit breaker ratings  
Unit Rating  
5000VA  
Maximum Breaker Rating  
D Type 30A Long Delay  
6000VA  
8000VA  
D Type 60A Long Delay  
10,000VA  
Liebert® GXT4User Manual  
24  
     
Installation  
Figure 2-7 Distribution box electrical connections diagram  
UPS  
UPS  
Input  
CB  
Output  
CB  
Input  
CB  
Output  
CB  
Output  
Terminal  
Block  
Maintenance  
Bypass Breaker  
Maintenance  
Bypass Breaker  
Optional  
Output  
Distribution  
POD  
Output  
Distribution  
Plate  
Input  
Output  
Input  
Indicator Indicator  
Output  
Indicator Indicator  
Utility  
Utility  
Input  
Input  
External  
Branch CB  
External  
Branch CB  
Distribution Box Electrical Connections  
for 5000 and 6000VA Models  
Distribution Box Electrical Connections  
for 8000 and 10,000VA Models  
2.6.5.1 Terminal Block Connections  
Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not share  
the same conduit. Emerson recommends using strain relief when installing the wire.  
Table 2-2 Electrical specifications  
Recommended  
(Maximum) External  
Overcurrent Protection  
Recommended Wire  
(Including ground wire)  
(75°C copper wire)  
Maximum Wire  
Accepted by  
Terminal  
Tightening  
Torque  
UPS Model  
Terminal Block  
GXT4-5000RT208  
GXT4-6000RT208  
GXT4-6000RTL630  
GXT4-8000RT208  
GXT4-10000RT208  
2
2
30A  
60A  
10AWG (4mm )  
8AWG (6mm )  
20 in-lb  
(2.26 Nm)  
2
2
6AWG (10mm )  
4AWG (16mm )  
25  
Liebert® GXT4User Manual  
     
Installation  
Figure 2-8 Terminal block connections  
Liebert GXT4-5000 and 6000RT208  
L2  
N
L1  
L2  
N
L1  
N
OUTPUT  
INPUT  
Liebert GXT4-8000 and 10,000RT208  
L2  
N
L1  
L2  
L1  
OUTPUT  
INPUT  
NOTE  
1. Emerson recommends installing a UL489-approved breaker upstream of unit.  
2. The installer must provide circuit breaker protection according to local codes. The mains  
disconnect should be within sight of the UPS or have appropriate an appropriate lock-out.  
Maintain service space around the UPS or use flexible conduit.  
3. The installer must provide output distribution panels, circuit breaker protection or emergency  
disconnects according to local codes. Output circuits must not share a common conduit with  
any other wiring.  
4. Liebert GXT4 models with a cord-connected input plug that is to be used as the power  
disconnecting device must be installed near a wall socket or outlet that is easily accessible per  
the National Electric Code / NFPA 70 requirements. Models that qualify are:  
• Liebert GXT4-6000RTL630 with standard POD  
GXT4-5000RT208 and GXT4-6000RT208 fitted with the optional POD’s PD2-001,  
PD2-002, PD2-003, PD2-004, PD2-005, PD2-006 and PD2-007.  
Liebert® GXT4User Manual  
26  
 
Installation  
2.7 IT Power System Configuration  
1. Remove screws on the IT Power System Access Cover as shown in Figure 3.  
2. Disconnect the connectors as shown in figure.  
3. Install IT Power System Access Cover and screws.  
Figure 3  
Remove cover from IT Power System Connectors compartment  
IT Power System  
Connectors  
Remove Screws  
27  
Liebert® GXT4User Manual  
   
Installation  
Page intentionally left blank.  
Liebert® GXT4User Manual  
28  
Operation and Display Panel  
3.0 Operation and Display Panel  
This chapter describes the Liebert GXT4 controls, particularly the operation and display panel on the front  
of the Liebert GXT4. The panel has four control buttons, seven LED indicators and a liquid crystal display  
(LCD), as shown in Figure 3-1.  
Figure 3-1 Operation and display panel  
Battery Indicator  
Inverter Indicator  
Fault  
Indicator  
Bypass  
Indicator  
LCD  
Panel  
ECO Mode  
Indicator  
ESC  
Button  
Enter  
Button  
UP Button  
DOWN Button  
3.1 LED Indicators  
The seven LED indicators on the front of the operation and display panel are:  
• Inverter  
• Battery  
• Bypass  
• ECO Mode  
• Fault  
Figure 3-1 shows the indicators’ locations; their descriptions and functions are shown in Table 3-1.  
Table 3-1 LED indicators  
LED Indicators  
Inverter  
LED Color  
Description  
Green  
On when the inverter is supplying power  
On when the load is supplied by the mains through  
automatic/manual bypass  
Bypass  
Amber  
Battery  
Fault  
Amber  
Red  
On when the load is supplied by the battery  
On when an error has occurred within the UPS  
On when the UPS is in ECO Mode  
ECO Mode  
Green  
29  
Liebert® GXT4User Manual  
           
Operation and Display Panel  
3.2 Control Buttons  
The four control buttons on the front of the operation and display panel are:  
• ESC  
• Up  
• Down  
• Enter  
Figure 3-1 shows the buttons’ locations; their descriptions and functions are shown in Table 3-2.  
Table 3-2 Control buttons  
Control Buttons Description  
Pressing this button returns to the previous menu or aborts any change in the input data field  
before confirming.  
ESC Button  
Pressing this button can move the cursor up or increase the value displayed in the input data  
Up Button  
field. When a menu is displayed on several screens, pressing the button can scroll up.  
Pressing this button can move the cursor down or decrease the value displayed in the input data  
Down Button  
field. When a menu is displayed on several screens, pressing the button can scroll down.  
Enter Button  
Pressing this button can enter the next level menu or confirm the parameter setting value.  
3.3 LCD  
The LCD panel shows the UPS status and enables changes to the UPS settings by assisting in navigating  
through the Liebert GXT4’s menu (see 3.4 - Menu Structure).  
Liebert® GXT4User Manual  
30  
     
Operation and Display Panel  
3.4 Menu Structure  
The menu structure of the LCD is shown in Figure 3-2.  
Figure 3-2 Menu structure  
Audible Alarm  
Output  
Load  
Startup on Bypass  
Enable Guaranteed  
Shutdown  
Status  
Input  
Battery  
UPS  
Enable Auto Restart  
Frequency Selection  
Start  
Windows  
Time Since Startup  
Output Level Selection  
System  
Status  
Configuration  
Battery Cabinets  
Turn UPS On  
Turn UPS Off  
Turn UPS  
On/Off  
Low Battery Time Warning  
Batt Test Interval  
BATT  
Alarm  
Control  
1. Audible Alarm On  
2. Audible Alarm Off  
Main  
Menu  
Control  
Batt Replace Time  
1. Start  
2. Cancel  
Enable/Disable  
Batt Test  
3. Batt Test Result  
Voltage  
Tolerance  
ECO Mode  
View Log  
Clear Log  
Frequency  
Tolerance  
Log  
Requalification  
Time  
Factory  
Default  
About  
PN/SN/Firmware Version  
1 English  
Language  
2 French  
Address: MAC  
LCD  
Color  
Address: IPV4  
Network  
Address: IPV6STATIC  
Address: IPV6AUTO  
Address: IPV6LINK  
31  
Liebert® GXT4User Manual  
   
Operation and Display Panel  
3.4.1 Startup Screen  
When the Liebert GXT4 is starting up, it initiates a self-test and displays the screen shown in Figure 3-3 for  
about 10 seconds.  
Figure 3-3 Startup screen  
EMERSON  
Network Power  
After about 10 seconds, the LCD shows one of the On screens in Figure 3-4; the screen shown depends  
on whether input power is available.  
Figure 3-4 Startup screens  
AC NOT AVAILABLE  
START ON BATTERY?  
TURN ON UPS  
YES NO  
YES NO  
O/P: 0V 0HZ 0.0A  
I/P : 120V 60HZ 0.0A  
BATT: 100% 320MINS  
LOAD: 0%  
O/P: 0V  
HZ 0.0A  
I/P : 120V 60HZ 0.0A  
BATT: 100% 320MINS  
LOAD: 0%  
2
1
No. Description  
1
2
Input power is available.  
Input power is not available.  
To turn On the UPS, press either the Up or Down button to select YES and press the Enter button. The  
UPS will start up, the LCD will display UPS STARTING and then START SUCCESSFUL after the UPS is  
turned On, as shown in Figure 3-5.  
Figure 3-5 Starting and Start Successful screens  
UPS STARTING  
START SUCCESSFUL  
O/P: 0V 0HZ 0.0A  
I/P : 120V 60HZ 0.0A  
BATT: 100% 320MINS  
LOAD: 0%  
O/P: 120V 60HZ 4.6A  
I/P : 120V 60HZ 5.0A  
BATT: 100% 15MINS  
LOAD: 40%  
Liebert® GXT4User Manual  
32  
       
Operation and Display Panel  
3.4.2 Default Screen  
Press any button in the START SUCCESSFUL screen to enter the default interface, shown in Figure 3-6.  
NOTE  
Values shown in the default screen will vary depending on installation  
and configuration.  
In the default screen, the LCD shows the UPS model, output parameters, input parameters, battery  
capacity with run time estimate and load percentage. The UPS operation mode (online /inverter, ECO,  
Battery or Bypass) will be indicated by the LED indicators.  
If no control button (ESC, Up, Down, Enter) is pressed for 2 minutes, the LCD will enter the screen saver  
mode (backlight turns off). It will remain off until a control button is pressed.  
Figure 3-6 Default screen  
GXT4-UPS 3KVA  
O/P: 120V 60HZ 11.7A  
I /P: 120V 60HZ 13.1A  
BATT: 100% 3MINS  
LOAD: 100%  
3.4.3 Main Menu Screen  
Press the Enter button in the default screen to enter the MAIN MENU screen, as shown in Figure 3-7.  
To select a submenu, press the Up or Down button to move the cursor to the required item, then press the  
Enter button to enter its submenu or set its parameter.  
Figure 3-7 Main Menu screen  
1 STATUS  
2 CONFIGURATION  
3 CONTROL  
4 LOG  
5 ABOUT  
6 NETWORK  
33  
Liebert® GXT4User Manual  
       
Operation and Display Panel  
STATUS Screen  
In the MAIN MENU screen, select STATUS to enter the Status Screen, displaying OUTPUT, LOAD, INPUT,  
BATTERY and TIME SINCE STARTUP, as shown in Figure 3-8.  
Figure 3-8 Status screens  
OUTPUT  
LOAD  
INPUT  
VOLT  
FREQ  
CURR  
:
:
:
120V  
60 HZ  
18.6A  
CAP :  
WATT :  
90%  
1620W  
1800VA  
VOLTAGE  
FREQUENCY :  
CURRENT  
POWER  
:
120V  
60HZ  
17.6A  
VA  
:
:
POWER :  
97KWH  
: 2112KWH  
BATTERY  
TIME SINCE STARTUP  
05D 15H 30M  
CAPACITY :  
RUNTIME :  
VOLTAGE :  
90%  
100MINS  
80V  
CONFIGURATION Screen  
Select MAIN MENU > CONFIGURATION to enter the Configuration menu. This menu has seven  
submenus, as shown in Figure 3-9.  
In the CONFIGURATION screen, press the Up or Down button to move the cursor to the required item,  
then press the Enter button to enter a submenu or set its parameters.  
Figure 3-9 CONFIGURATION screen  
1. UPS  
2. BATTERY  
3. ECO MODE  
4. OUTLET 1  
5. OUTLET2  
6. LCD  
7. FACTORY DEFAULT  
Liebert® GXT4User Manual  
34  
   
Operation and Display Panel  
UPS Screen  
Select MAIN MENU > CONFIGURATION > UPS to enter the UPS screen. This menu has six screens, as  
shown in Figure 3-10.  
Press the Up or Down button to move the cursor to the required item, and press the Enter button to confirm  
the settings.  
Figure 3-10 UPS screens  
AUDIBLE ALARM  
STARTUP ON BYPASS  
NO  
GUARANTEE SHUTDOWN  
NO  
OFF  
ENABLE AUTO RESTART  
YES  
FREQUENCY SELECTION  
AUTO - BYPASS ENABLE  
VOLTAGE SELECTION  
230  
Battery Screen  
Select MAIN MENU > CONFIGURATION > BATTERY to enter the BATTERY screen. This menu has four  
screens, as shown in Figure 3-11.  
Press the Up or Down button to increase or decrease the value of the settings, and press the Enter button  
to confirm it.  
Figure 3-11 Battery screen  
EXT BATT CABINET  
CABINETS  
LOW BATTERY TIME  
MINS  
0
2
BATT TEST INTERVAL  
WEEKS  
BATT REPLACE TIME  
8
2014 Y  
1 M  
1 D  
35  
Liebert® GXT4User Manual  
   
Operation and Display Panel  
ECO Mode Screens  
Select MAIN MENU > CONFIGURATION > ECO MODE to enter the ECO MODE screens, as shown in  
Press the Up or Down button to move the cursor to the required item, and press the Enter button to confirm  
the settings.  
Figure 3-12 ECO Mode screen  
ECO MODE  
ON  
VOLTAGE TOLERANCE  
10%  
FREQUENCY TOLERANCE  
3 Hz  
REQUALIFICATION TIME  
5 MINS  
No. Description  
1
2
Outlet control is on.  
Outlet control is off.  
LCD screen  
Select Main Menu -> 2 CONFIGURATION -> 6 LCD to enter the LCD screen. This menu has two  
submenus, LANGUAGE and COLOR, as shown in Figure 3-13.  
Figure 3-13 LCD screen  
1 LANGUAGE  
2 COLOR  
Liebert® GXT4User Manual  
36  
   
Operation and Display Panel  
Select 1 LANGUAGE and press the Enter button to enter the LANGUAGE screen,  
as shown in Figure 3-14.  
The Liebert GXT4 is capable of supporting multiple languages. For the list of supported languages and  
instructions on how to upload them, refer to the Configuration Program user manual on the included CD.  
Figure 3-14 Language screen  
1 English  
2
Select ‘2 COLOR’ and press the Enter button to enter the COLOR screen, as shown in Figure 3-15.  
Figure 3-15 Color screen  
EMERSON  
EMERSON  
EMERSON  
EMERSON  
FACTORY DEFAULT screen  
Select MAIN MENU -> 2 CONFIGURATION -> 7 FACTORY DEFAULT to enter the FACTORY DEFAULT  
screen, as shown in Figure 3-16.  
Figure 3-16 Factory Default screen  
RESET ALL SETTINGS  
TO FACTORY DEFAULT  
SETTINGS?  
YES NO  
37  
Liebert® GXT4User Manual  
     
Operation and Display Panel  
Control Screen  
Select MAIN MENU -> 3 CONTROL to enter the CONTROL screen. This screen has three submenus,  
TURN ON & OFF, ALARM CONTROL and BATT TEST, as shown in Figure 3-17.  
In the CONTROL screen, press the Up or Down button to move the cursor to the required item, and press  
the Enter button to enter its submenu.  
Figure 3-17 Control screen  
1 TURN ON & OFF  
2 ALARM CONTROL  
3 BATT TEST  
TURN ON & OFF screen  
Select MAIN MENU -> 3 CONTROL -> 1 TURN ON & OFF to enter the TURN ON & OFF screen. This  
screen shows one of two displays, TURN ON UPS and TURN OFF UPS, depending on the state of the  
UPS, as shown in Figure 3-18.  
Figure 3-18 Turn UPS On or Off screen  
TURN OFF UPS  
TURN ON UPS  
TURN ON UPS BYPASS  
1
2
No. Description  
1
2
UPS is off.  
UPS is on.  
Liebert® GXT4User Manual  
38  
   
Operation and Display Panel  
ALARM CONTROL screen  
Select MAIN MENU -> 3 CONTROL -> 2 ALARM CONTROL to enter the ALARM CONTROL screen, as  
shown in Figure 3-19. This section allows active audible alarms to be silenced. To completely turn off the  
audible alarm, refer to CONFIGURATION > UPS as shown in Figure 3-10.  
Figure 3-19 Alarm Control screen  
1 AUDIBLE ALARM ON  
2 AUDIBLE ALARM OFF  
BATT TEST screen  
Select MAIN MENU -> 3 CONTROL -> 3 BATT TEST to enter the BATT TEST screen, as shown in  
Figure 3-20 Batt Test screen  
1 START  
2 CANCEL  
3 BATT TEST RESULT  
Log Screen  
Select MAIN MENU -> 4 LOG to enter the LOG screen. This screen has two submenus, VIEW LOG and  
CLEAR LOG, as shown in Figure 3-21.  
Figure 3-21 Log screens  
254/255  
1 VIEW LOG  
2 CLEAR LOG  
255 OD 1H 17m AGO  
UPS switch to Online  
mode  
39  
Liebert® GXT4User Manual  
     
Operation and Display Panel  
CLEAR LOG Screen  
Select MAIN MENU > LOG > CLEAR LOG to enter the CLEAR LOG screen, as shown in Figure 3-22.  
Press the Up or Down button to move the cursor to the required item. Press the Enter button to confirm the  
settings.  
Figure 3-22 Clear Log screen  
DO YOU WANT TO  
CLEAR EVENT LOGS?  
YES  
NO  
ABOUT Screen  
Select MAIN MENU> ABOUT to enter the ABOUT screen, as shown in Figure 3-23. The ABOUT screen  
displays UPS model, serial number, software version and hardware version.  
Figure 3-23 About screen  
PN: GXT4-2000RT230  
SN:1XXX60XXX1AFCXX  
FW VER: U100D100  
HW VER: H100  
Liebert® GXT4User Manual  
40  
   
Operation and Display Panel  
Network  
Select MAIN MENU>NETWORK to enter the NETWORK screen.  
The NETWORK screen displays the MAC address and the IPv4 IP address. If the Liebert GXT4 is fitted  
with an optional Liebert IntelliSlot® Web card (Liebert IS-WEBCARD), the screen will display IPv6 IP  
address settings (IPv6 requires configuration), as shown in Figure 3-24.  
Figure 3-24 Network screens  
ADDRESS MAC  
00-02-11-4X-AX  
ADDRESS IPV4  
ADDRESS IPV6 STATIC  
::  
10.163.226.231/24  
ADDRESS IPV6 LINK  
ADDRESS IPV6 AUTO  
::  
Fe80::202:99ff:fe0f:4ba  
2%1  
41  
Liebert® GXT4User Manual  
 
Operation and Display Panel  
3.4.4 Prompt List  
A prompt screen is displayed during the operation of the system to alert you to certain conditions and/or to  
require your confirmation of a command or other operation. See Table 3-3 for the prompts and meanings.  
Table 3-3 System prompts and meanings  
Prompt  
Mains Power Restored  
Meanings  
The mains power returns and the UPS transfers back to mains (AC)  
mode.  
UPS Return From A Low Battery Condition The UPS transfers back to mains (AC) mode from battery low mode.  
UPS Return From Battery Mode  
UPS Self Test Successful  
UPS Shutdown Command Received  
UPS Turn Off  
The UPS transfers back to mains (AC) mode from battery mode.  
The UPS self-test is successfully performed.  
The UPS shut down was initiated through communication.  
The UPS shuts down and has no output power.  
The UPS starts up successfully and supplies protected power to the  
load.  
UPS Turn On  
UPS Shutdown Process Had Been  
Cancelled  
The shutdown command sent through Liebert MultiLink or SNMP card  
to the UPS is canceled,  
ECO Mode Enabled  
The UPS is configured to ECO mode operation,  
The UPS is configured to Online mode, supplying protected power to  
the load through the inverter.  
ECO Mode Disabled  
UPS Internal Temperature Return To  
Normal  
The internal temperature of the UPS recovers to normal range.  
The loads are reduced, and the UPS recovers to normal state from  
overload.  
UPS Load Return From Overload  
Load On Inverter  
The inverter is on and supplies protected power to the load.  
The UPS is on ECO mode; the mains is supplying power to the load  
directly to reduce energy usage.  
Load On ECO Bypass  
Bypass Power Restored  
The bypass power recovered and the UPS can now transfer to bypass.  
3.4.5 Warning List  
All UPS warning messages are described in Table 3-4.  
Table 3-4 Warning list  
Warning  
Description  
The mains power is not available, or it cannot satisfy the input  
requirements for the UPS to operate from mains power  
Mains Power Not Available  
UPS Batteries Low And Exhausted Soon The battery capacity is low and will be exhausted soon  
The mains power is abnormal or the PFC side is faulty, the UPS  
UPS Has Switched To Battery Mode  
transfers back to Battery mode  
The UPS transfers to Bypass mode, at this point, the input mains power  
Load On Bypass  
supplies power to the load directly, and the load is not protected  
Input Power Wiring Error  
L-N line reverse or PE not connected.  
The bypass power is not available, or it cannot satisfy the requirements  
for the UPS transfers to bypass  
Bypass Power Not Available  
UPS Maintenance Bypass Output  
AC input not qualified, cannot start UPS  
Output disabled  
The UPS transfers to maintenance bypass.  
The utility power is not qualified, the inverter cannot be powered up  
REPO terminal connect error  
Liebert® GXT4User Manual  
42  
       
Operation and Display Panel  
3.4.6 Fault List  
All UPS fault messages are described in Table 3-5.  
Table 3-5 Fault list  
Fault  
Description  
UPS Self-Test Failed  
UPS Overload  
The battery is bad or weak or not connected.  
The UPS is overloaded.  
Inverter Out Of Order  
Battery Weak/Bad  
Output Short Circuit  
DC Bus Overvoltage  
UPS Overtemperature  
Charger Out Of Order  
Fan Out Of Order  
DC Bus Discharge Fail  
Rectifier Out Of Order  
The inverter has failed.  
The battery is bad or weak.  
The output connection is short-circuited.  
The DC bus is faulty.  
Overtemperature occurs to the UPS and the UPS will transfer to Bypass mode.  
The charger has failed.  
At least one fan is failed.  
DC-DC failure occurs.  
Rectifier failure occurs.  
If a fault occurs, the UPS automatically switches to Bypass Mode. The original operating mode will be  
maintained only in the case of a battery disconnection fault. The fault message alternates with UPS Mode  
once a second, the red fault indicator on the operation and display panel lights up and the alarm sounds  
continuously.  
If a fault occurs:  
1. Enter the ALARM CONTROL screen (see Figure 3-19), and select AUDIBLE ALARM ON or AUDIBLE  
ALARM OFF to switch the alarm On or Off.  
2. Enter the EVENT LOG screen (see Figure 3-21), and select VIEW LOG to view the entire Event log.  
NOTE  
There will be a short delay before the EVENT LOG screen displays the historical fault log to allow  
the log to load.  
43  
Liebert® GXT4User Manual  
   
Operation and Display Panel  
Page intentionally left blank.  
Liebert® GXT4User Manual  
44  
Operation  
4.0 Operation  
This section describes checks to be made before starting the UPS, how to start the UPS, manual battery  
test, manual bypass, shutting down the UPS and disconnecting mains power from the UPS.  
NOTE  
The Liebert GXT4’s battery has been fully charged before delivery, but some charge will be lost  
during storage and shipping. To ensure that the battery has adequate reserve power to protect the  
connected load, charge the battery for 5 hours before putting the UPS into service.  
4.1 Startup Checklist for the Liebert GXT4  
Before starting the UPS, perform these checks:  
___ 1. Check that the input plugs and loads are connected properly and reliably.  
___ 2. Check that the battery cable is connected properly.  
___ 3. Check that the communication cables are connected properly.  
4.2 Starting the UPS  
1. Plug the UPS into the appropriate AC outlet.  
2. Close the input breaker on the rear of the unit.  
3. The UPS will begin the startup sequence once AC power is present.  
NOTE  
The UPS will sound an audible alarm, this is normal.  
4. On the LCD, press either the Up or Down button once, then press the Enter button to turn On the UPS.  
The UPS will sound the audible alarm again as the output receptacles are now being powered by the  
internal bypass, then will sound one more time as the inverter powers the connected equipment.  
5. Check the LCD and LED indicators to ensure that the UPS is operating normally.  
6. Check the load percentage on the default screen to ensure that the connected equipment is not  
exceeding the UPS’s rated capacity.  
The UPS is now providing conditioned and protected power to the connected equipment.  
4.3 Manual Battery Test  
To initiate a manual battery test, select MAIN MENU > CONTROL>BATT TEST>START.  
• If the battery test results show FAILED, allow the UPS to recharge the batteries for 24 hours.  
• Retest the batteries after 24 hours of charging.  
• After the batteries have been retested, if the battery test still shows FAILED, contact your local  
Emerson® representative or Emerson Network Power Channel Support.  
45  
Liebert® GXT4User Manual  
         
Operation  
4.4 Manual Bypass  
To manually transfer the connected equipment to the internal bypass:  
1. From the main menu select Control then press enter.  
2. Select TURN ON & OFF and press Enter.  
3. Select TURN UPS BYPASS and press Enter. The UPS will transfer the connected loads to the internal  
bypass.  
If the internal bypass is not available because of input power problems, pressing this button once will be  
ignored. Bypass operation is indicated by an audible alarm and illuminated amber Bypass indicator. (If  
other indicators are illuminated, refer to 7.0 - Troubleshooting.)  
4.5 Shut Down the GXT4  
To shut down the UPS from the LCD:  
1. From the Main Menu select CONTROL, press Enter, then select TURN ON & OFF.  
2. Press the Enter key.  
3. Select TURN UPS OFF, then press Enter. Press either the Up or Down button to move the cursor to  
confirm the turn off command and press Enter. The UPS will sound an audible alarm; this is normal.  
4. Power to the connected equipment is now Off.  
The UPS display will still be illuminated because the batteries are still being charged. The UPS may now  
be disconnected from AC power, and the UPS will completely shut down in approximately 15 seconds.  
4.6 Disconnecting Input Power from the GXT4  
1. After the UPS has been shut down as detailed in 4.5 - Shut Down the GXT4, disconnect the input  
cable from the wall socket.  
2. Wait 30 seconds and verify that all indicators have turned Off and the fan has stopped; this indicates  
that the power-off is complete.  
3. Turn the external battery cabinet breaker switch to the Off position if the UPS has an external battery  
cabinet.  
After powering Off the UPS, the UPS ceases output and the load is powered Off.  
4.7 Maintenance Bypass  
Maintenance Bypass Mode is used when maintenance or replacement is required. To place the unit in  
Maintenance Bypass:  
1. Place the UPS on internal bypass. This may be done by either of the following methods:  
a. Refer to 4.4 - Manual Bypass.  
b. Slide the bracket away from the manual bypass breaker on the rear of the UPS. This requires  
loosening the captive screw and sliding the bracket up and away from the Manual Bypass breaker.  
2. Move the Manual Bypass breaker on the rear of the UPS to the bypass position. This requires  
loosening the captive screw and sliding the bracket up and away from the Manual Bypass breaker.  
Liebert® GXT4User Manual  
46  
           
Communication  
5.0 Communication  
This section describes the communication ports on the rear of the UPS:  
• Liebert IntelliSlot® port  
• USB port (standard B-type)  
Terminal Block Communication  
CAUTION  
!
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables should be  
segregated and run separate from all other power cables.  
5.1 Liebert IntelliSlot Communication Cards  
The Liebert IntelliSlot port accepts four optional cards:  
• Liebert IntelliSlot Web Card (IS-WEBCARD)  
• Liebert IntelliSlot Relay Card (IS-RELAY)  
• Liebert IntelliSlot MultiPort Card (IS-MULTIPORT)  
• Liebert IntelliSlot Unity Card (IS-UNITY-DP)  
The Liebert IntelliSlot Web Card provides SNMP monitoring and control of the UPS across the network.  
The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications and  
delivers support for Liebert MultiLink® shutdown software.  
The Liebert IntelliSlot MultiPort Card provides four sets of contacts for support of up to four computers that  
have Liebert MultiLink installed.  
The Liebert IntelliSlot Unity Card provides SNMP and/or RS-485 monitoring of the UPS across the network  
and/or building management system. The Liebert IntelliSlot UNITY card also enables monitoring external  
temperature, humidity and contact closure inputs using external sensors.  
Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink®, the UPS or any  
additional ancillary product for the Liebert GXT4. These instructions are available at:  
5.1.1 Liebert MultiLink  
Liebert MultiLink monitors the UPS continuously and can shut down the computer or server in the event of  
an extended power failure. Liebert MultiLink can also be configured to shut down the UPS.  
Liebert MultiLink can communicate with the UPS via the USB port, RS232 port, contact closures via  
terminal block or over the network via SNMP using the Liebert IS-WEBCARD. An optional Liebert MultiLink  
license kit permits shutting down multiple computers that are protected by the UPS.  
For more information about the Liebert IntelliSlot SNMP Card, Liebert IntelliSlot Web Card and Liebert  
MultiLink License Kits, visit the Liebert Web site (www.liebert.com) or contact your local Emerson®  
representative.  
47  
Liebert® GXT4User Manual  
     
Communication  
5.2 USB Port Communication  
The standard B-type USB port is used to connect the UPS and network server or other computer system  
using Liebert MultiLink®.  
A standard B-type USB port is provided to allow connection to a computer or network server. The USB port  
can be used to communicate with the Liebert GXT4 configuration program (see section 5.2.1 -  
Configuration Program for details) or Liebert MultiLink (refer to 5.1.1 - Liebert MultiLink for description)  
that is provided on the CD that is included with the UPS.  
5.2.1 Configuration Program  
The configuration program is on the Liebert GXT4 CD and can be used instead of making configuration  
setting changes from the LCD panel. The configuration program communicates to a computer running a  
Microsoft® Windows® operating system via the included USB cable.  
For most users, the factory default settings are adequate. This section give a brief overview of the features  
and parameters that are available for modification, as well as the factory default settings. Should any  
changes be necessary, refer to the Configuration Program User Manual that is located on the included CD  
for further details.  
The configuration program allows these features of the Liebert GXT4 to be changed:  
• Change and set the display language  
• Enable/Disable Auto-Restart (default is Enable)  
• Select frequency converter operation with a fixed output frequency of 50Hz or 60Hz, bypass disabled  
(default is Auto-Select with bypass enabled)  
• Set the Low Battery Warning alarm time from 2 to 30 minutes (default is 2 minutes)  
• Enable/Disable the Auto-Battery test (default is Enable)  
• Enable/Disable Auto-Restart after removing Remote shutdown (default is Disable)  
• Set the wiring mode of Remote shutdown (default is normally open)  
• Set the Auto-Enable output after remote shutdown (default is Disable)  
• Set the Auto-Battery test to 8, 12, 16, 20, or 26 weeks (default is 8 weeks)  
• Select the number of external battery cabinets connected to the UPS to adjust the remaining run time  
calculated by Emerson® software products (default is zero)  
• Select one of multiple output voltages to match various voltages (see Table 5-1).  
Table 5-1 Output voltage option  
UPS Model  
FactoryDefault Setting  
Output Voltage Option  
GXT4-6000RTL630  
GXT4-5000RT208  
GXT4-6000RT208  
GXT4-8000RT208  
GXT4-10000RT208  
208 VAC  
200V, 208V, 220V, 230V, 240V  
200/100V, 208/120V, 220/110V,  
230/115V, 240/120V, 220/127V  
208/120 VAC  
NOTICE  
The output voltage settings cannot be changed while the UPS is On and powering connected  
loads.  
Liebert® GXT4User Manual  
48  
       
Communication  
NOTE  
Programming the output voltage of the Liebert GXT4-5000RT208, GXT4-6000RT208, GXT4-  
8000RT208, and GXT4-10000RT208 models to 220/110VAC automatically derates both the VA  
and Watt ratings to 90% of the units ratings and programming the output voltage to 200/100VAC  
automatically derates both the VA and Watt ratings to 80% of the units ratings (refer to 9.0 -  
Specifications for the VA and Watt ratings)  
NOTE  
• This program is compatible with UPS models beginning with ‘GXT4,’ as in ‘GXT4-3000RT230.’  
It is not compatible with earlier versions of the Liebert GXT UPS.  
®
®
®
• A computer running Microsoft® Windows 2000 , Windows XP , Windows Vista , Windows 7 or  
Windows 8 is required to set up and run the configuration program.  
5.3 Terminal Block Communication  
The Terminal Block includes eight pins, as shown in Figure 5-1.  
Figure 5-1 Terminal-block communication pin layout  
No. Description  
1
2
3
4
Low battery warning  
On-battery warning  
Any mode shutdown  
Battery mode shutdown  
49  
Liebert® GXT4User Manual  
   
Communication  
5.3.1 Any Mode Shutdown  
The purpose of Any Mode Shutdown is to shut down the UPS output by turning Off the rectifier, inverter  
and static switch so that there is no power to the loads.  
Any Mode Shutdown can be operated locally or remotely:  
• Local Any Mode Shutdown can be performed by shorting the pins in terminal 3 for the UPS-models  
ending in RT208, and pins1 and 2 for the GXT4-6000RTL630 model.  
• Remote Any Mode Shutdown can be performed using a switch mounted at a remote location and  
connected to the pins in terminal 3 for the UPS-models ending in RT208, and pins1 and 2 for the  
GXT4-6000RTL630 model.  
NOTE  
Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown,  
depending on the settings in the configuration program.  
A current-limited source for this optocoupler (+12 VDC, 50 mA) will be available from the UPS.  
The connection to the UPS for remote connection will be via terminal block connector.  
Any Mode Shutdown wiring must conform to all national, regional and local wiring regulations.  
WARNING  
!
When the Auto-Enable output option is selected and the UPS output is disabled using Any Mode  
Shutdown, the Liebert GXT4’s output can turn On automatically and without warning if the  
connection is changed.  
5.3.2 Battery Mode Shutdown  
Battery Mode Shutdown permits shutting down the UPS by turning Off the rectifier, inverter and static  
switch so that there is no power to the load when the UPS is On Battery. The auxiliary power for the UPS  
will still be active.  
Battery Mode Shutdown can be performed locally or remotely:  
• Local Battery Mode shutdown can be performed by shorting the pins in terminal 4 for the UPS-models  
ending in RT208, and pins3 and 4 for the GXT4-6000RTL630 model.  
• Remote Battery Mode Shutdown can be performed using a switch mounted in a remote location and  
connected to the pins in terminal 4 for the UPS-models ending in RT208, and pins 3 and 4 for the  
GXT4-6000RTL630 model.  
NOTE  
Remote Power Off will be performed by NO contact.  
A current-limited source (+12 VDC, 50 mA) will be available from UPS.  
The connection to the Liebert GXT4 for remote connection will be via terminal block connector.  
Battery Mode Shutdown wiring must conform to all national, regional and local wiring codes and  
laws.  
This signal must last for 1.5 seconds or longer.  
A battery shutdown signal will not cause an immediate shutdown. It will start a 2-minute shutdown  
timer. This timer cannot be stopped once triggered. If the mains power returns during this  
countdown, the Liebert GXT4 will still shut down and must remain shut down for 10 seconds.  
Whether the UPS turns back On when the power is restored depends on the auto-restart setting.  
Liebert® GXT4User Manual  
50  
   
Communication  
5.3.3 On Battery  
On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the  
battery this dry contact will be closed.  
5.3.4 Low Battery  
Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the  
battery and has reached the Low Battery Warning time selected in the configuration program, this dry  
contact will be closed.  
NOTE  
The rated values for the dry contacts for the On Battery and Low Battery signals are:  
• Rated Voltage: 30 V (AC or DC)  
• Rated Current: 300 mA  
5.4 Remote Emergency Power Off—GXT4-6000RTL630  
The UPS is equipped with a Remote Emergency Power Off (REPO) connector.  
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS input  
feeder breaker to remove all sources of power to the UPS and connected equipment to comply with  
national and local wiring codes and regulations.  
Figure 5-2 REPO switch connection diagram  
UPS ships with REPO jumper  
installed allowing the UPS  
to operate  
Opening the REPO connection will disable the UPS.  
Manual restart using the front panel is required after  
the REPO connection is closed again.  
1
2
1
2
Normally closed switch system  
(fail-safe)  
CAUTION  
!
To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should be  
shielded and run separately from power cables.  
51  
Liebert® GXT4User Manual  
       
Communication  
Remote Emergency Power Off—GXT4-5000RT208,  
GXT4-6000RT208, GXT4-8000RT208, GXT4-10000RT208  
+24 V supplied  
by GXT4 UPS  
How UPS ships, with jumper removed  
and in the accessory bag.  
1
2
3
4
+24 V supplied  
by GXT4 UPS  
How UPS must be wired to operate with no repo connection.  
Jumper in accessory bag must be installed.  
1
2
3
4
+24 V supplied  
by GXT4 UPS  
How UPS must be wired to operate  
with connection to a normally-closed (NC) repo connection.  
Jumper in accessory bag must be removed as this wired  
to a remote switch.  
1
2
3
4
+24 V supplied  
by GXT4 UPS  
How UPS must be wired to operate  
with connection to a normally-open (NO) repo connection.  
Jumper in accessory bag must be installed.  
1
2
3
4
Liebert® GXT4User Manual  
52  
Maintenance  
6.0 Maintenance  
This section describes replacing the internal battery pack, precautions, checking the Liebert GXT4’s status  
and checking UPS functions.  
WARNING  
precautions should be observed before replacing the battery pack:  
!
The battery can present a risk of electrical shock and high short circuit current. The following  
• Remove rings, watches and other metal objects.  
• Use tools with insulated handles.  
• Do not lay tools or other metal objects on the batteries.  
• If the battery kit is damaged in any way or shows signs of leakage, contact your local Emerson  
representative immediately.  
• Do not dispose of batteries in a fire. The batteries may explode.  
• Handle, transport and recycle batteries in accordance with local regulations.  
6.1 Replacing the Internal Battery Pack  
The Liebert GXT4 is designed to allow the user to replace the internal battery pack safely. Refer to  
Table 6-1 for internal battery pack part numbers for Liebert GXT4 UPS:  
Table 6-1 Replacement internal battery pack model number  
Replacement Internal Battery  
Pack Model Number  
Quantity  
Required  
UPS Model Number  
GXT4-5000RT208  
GXT4-6000RT208  
GXT4-144VBATKIT  
GXT4-240VBATKIT  
GXT4-240VRTBKIT  
1
2
2
GXT4-6000RTL630  
GXT4-8000RT208  
GXT4-10000RT208  
53  
Liebert® GXT4User Manual  
     
Maintenance  
6.1.1 Battery Replacement Procedures  
Read all safety cautions before proceeding. A trained user can replace the internal battery pack when the  
UPS is always in a restricted access location (such as a rack or server closet). Contact your local dealer or  
Emerson representative to obtain the pricing of the appropriate replacement battery pack.  
CAUTION  
the instructions.  
!
Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries according to  
1. Remove the front plastic bezel cover from the UPS.  
2. Loosen and remove the 6 screws on the battery door, as shown in Figure 6-1.  
3. Lay the battery door and screws aside for reassembly.  
Figure 6-1 Removing the front bezel cover and battery door  
Battery Door  
Screws, 6  
Front Bezel  
4. Gently pull the battery wire out and disconnect the battery plug and battery receptacle, as shown in  
Figure 6-2 Disconnecting the battery plug and battery receptacle (front view)  
Battery  
Connector  
Battery  
Receptacle  
Battery  
Connector  
Battery  
Receptacle  
Liebert® GXT4User Manual  
54  
     
Maintenance  
5. Grasp the battery handle, and pull the internal battery pack out of the UPS, as shown in Figure 6-3.  
Repeat this step if both battery packs will be replaced. Each model has two battery packs.  
Figure 6-3 Pull out the battery  
5000 & 6000 VA models  
6000RTL630, 8000VA /  
10,000VA model  
Internal  
Battery  
Pack  
Internal  
Battery  
Pack  
(one of 2)  
Battery  
Handle  
Battery  
Handle  
Each model has two  
battery packs.  
Pull Out with Battery Handle  
Pull Out with Battery Handle  
6. Unpack the new internal battery pack. Take care not to destroy the packing.  
Compare the new and old internal battery pack to make sure they are the same type and model. If so,  
proceed with Step 7; if they are different, stop and contact your local Emerson representative, or  
Emerson Channel Support.  
7. Line up and slide in the new internal battery pack.  
8. Reconnect the battery plug and battery receptacle  
9. Push the battery wire and internal battery pack back into the UPS.  
10. Reattach the front battery door with the six screws.  
11. Reattach the front plastic bezel cover to the UPS.  
NOTE  
The internal battery pack is hot-swappable. However, caution should be exercised because during  
this procedure the load is unprotected from disturbances and power outages. Do not replace the  
battery while the UPS is operating in Battery Mode. This will result in a loss of output power and  
will drop the connected load.  
6.2 Battery Charging  
The batteries are valve-regulated, nonspillable, lead acid and should be kept charged to attain their design  
life. The Liebert GXT4 charges the batteries continuously when it is connected to the utility input power.  
If the Liebert GXT4 will be stored for a long time, Emerson recommends connecting the UPS to input  
power for at least 24 hours every four to six months to ensure full recharge of the batteries.  
55  
Liebert® GXT4User Manual  
   
Maintenance  
6.3 Precautions  
Although the Liebert GXT4 has been designed and manufactured to ensure personal safety, improper use  
can result in electrical shock or fire. To ensure safety, observe the following precautions:  
• Turn Off and unplug the Liebert GXT4 before cleaning it.  
• Wear rubber gloves and boots.  
• Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.  
• Never block or insert any objects into the ventilation holes or other openings of the Liebert GXT4.  
• Do not place the Liebert GXT4 power cord where it might be damaged.  
6.4 Checking UPS Status  
Emerson recommends checking the UPS operation status every six months.  
• Check if the UPS is faulty: Is the Fault Indicator On? Is the UPS sounding an alarm?  
• Check if the UPS is operating in Bypass mode: Normally, the UPS operates in Normal Mode; if it is  
operating in Bypass Mode, stop and contact your local Emerson representative or Emerson Channel  
Support.  
• Check if the battery is discharging: When the utility input is normal, the battery should not discharge. If  
the UPS is operating in Battery Mode, stop and contact your local Emerson representative or Emerson  
Channel Support.  
6.5 Checking UPS Functions  
NOTE  
UPS function check procedures may interrupt power supply to the connected load.  
Emerson recommends checking the UPS functions once every six months.  
Back up the load data before conducting the UPS functions check. Procedures are as follows:  
1. Press the Standby/Manual Bypass button to check whether the alarm and indicators are normal.  
2. Press the On/Alarm Silence/Manual Battery Test button to check again whether the indicators are On  
and the UPS is operating normally.  
3. Press the On/Alarm Silence/Manual Battery Test button for three seconds after Inverter Mode.  
The UPS should initiate battery self-test. Check to determine whether the battery is operating normally.  
If not, stop and contact your local Emerson representative or Emerson Channel Support.  
Liebert® GXT4User Manual  
56  
     
Maintenance  
6.6 Replacing the Power Module on 8000 and 10,000VA models  
CAUTION  
!
The UPS must be switched to manual bypass before personnel begin to replace the power  
module.  
NOTICE  
During the procedure, the connected load will not be protected from power disturbances, such as  
spikes, sags and failure.  
To remove the UPS power module without shutting off power to the connected load:  
1. Place the UPS on internal bypass. This may be done by any of the three following methods:  
a. Refer to 4.4 - Manual Bypass.  
b. Slide the bracket away from the manual bypass switch on the rear of the UPS; this requires  
loosening the captive screw and sliding the bracket away from the manual bypass switch.  
c. Remove the front grille covering the power module.  
2. Move the manual bypass breaker on the rear of the UPS to the bypass position; this requires loosening  
the captive screw and sliding the bracket away from the manual bypass switch (see Figure 1-6).  
3. Open the input circuit breaker on the rear of the UPS (see Figure 1-6).  
4. Open the output circuit breaker on the rear of the UPS (see Figure 1-6).  
5. Remove the top two front plastic bezels by pulling them forward.  
6. Remove the power module cover grille and the battery cover grille with the screws securing them to  
the frame.  
7. Disconnect the slotted battery connectors from the internal battery packs.  
8. If additional external batteries are used, disconnect the two external battery connectors.  
9. Slide power module restraint lever up out of the locked position.  
10. Slide the power module out the front, supporting its weight as it is withdrawn.  
Figure 6-4 Removing power module from Liebert GXT4 8000 and 10,000VA models  
Power module  
pulled part of  
the way out of  
an 8000 or  
10,000VA unit  
11. Insert the replacement UPS power module.  
12. Slide the power module restraint lever back into the locked position.  
13. Reconnect the slotted internal battery connectors.  
57  
Liebert® GXT4User Manual  
   
Maintenance  
14. Reconnect the external battery cables, if used.  
15. Reattach both front cover grilles.  
16. Reattach the front plastic bezels.  
17. Close the input circuit breaker on the rear of the UPS (see Figure 1-6).  
18. Close the output circuit breaker on the rear of the UPS (see Figure 1-6).  
19. Move the bypass breaker on the rear of the UPS back to the INVERTER position (see Figure 1-6).  
20. Slide the bracket back next to the manual bypass breaker and tighten its thumbscrew.  
21. Press the On button on the front panel one time to return the UPS to Normal Mode operation (see  
NOTE  
The power module restraint lever must be fully engaged for the UPS to operate in  
Normal Mode.  
Liebert® GXT4User Manual  
58  
Troubleshooting  
7.0 Troubleshooting  
This section indicates various UPS symptoms a user may encounter and provides a troubleshooting guide  
in the event the UPS develops a problem. Use the following information to determine whether external  
factors caused the problem and how to remedy the situation.  
7.1 UPS Symptoms  
The following symptoms indicate the Liebert GXT4 is malfunctioning:  
• The relative indicators illuminate, indicating the UPS has detected a problem.  
• An alarm buzzer sounds, alerting the user that the UPS requires attention.  
7.1.1 Indicator and LCD  
In addition to the fault indicator being illuminated, the LCD will display the fault. The displayed fault on the  
LCD is described in Table 7-1  
Table 7-1 Description of the displayed fault  
Displayed Fault  
Cause  
Corrective Steps  
Contact customer service.  
UPS self test failed  
The battery is bad or weak.  
UPS shutdown  
command received  
The UPS shuts down through communication. Contact customer service.  
Reduce the load and contact customer  
service.  
UPS overload  
The UPS is overloaded.  
Inverter Out of Order  
Battery Weak/Bad  
The inverter is faulty.  
Contact customer service.  
Replace the battery.  
The battery is bad or weak.  
Shut down the equipment and contact  
customer service.  
Output Short Circuit  
DC Bus Overvoltage  
UPS Overtemperature  
The output connection is short-circuited.  
The DC bus is faulty.  
Contact customer service.  
Over-temperature occurs to the UPS and the Reduce the load and contact customer  
UPS will transfer to Bypass mode.  
service.  
Charger Out of Order  
Fan Out of Order  
The charger is faulty.  
Contact customer service.  
Contact customer service.  
Contact customer service.  
At least one fan is faulty.  
DC Bus Discharge Fail A DC-DC failure occurs.  
NOTE  
If the UPS encounters a fault and no correction attempt is performed within 2 minutes, the LCD  
backlight will flash (on 1 second and off 1 second) as an alert.  
Press any button to exit the alert mode. If no correction attempt is performed on the UPS, the LCD  
backlight will flash again until the UPS fault is corrected.  
59  
Liebert® GXT4User Manual  
         
Troubleshooting  
7.1.2 Audible Alarm  
An audible alarm will sound in conjunction with the visual indicators to indicate a change in UPS operating  
status. The audible alarm will sound as described in Table 7-2.  
Table 7-2 Audible alarm description  
Condition  
Alarm  
Half-second beep every 10 seconds  
Two half-second beeps every 5 seconds  
1-second beep every 4 seconds  
Continuous  
Battery discharge  
Low battery  
UPS fault, load on bypass  
UPS fault, no power to load  
Overload  
Half-second beep every half second  
2-second beep every 2 minutes  
Continuous  
Battery replacement  
Battery loss  
Wiring problem (loss of proper grounding for UPS) Continuous  
Bypass reminder  
1-second beep every 60 seconds  
7.2 Troubleshooting  
In the event of an issue with the UPS, refer to Table 7-3 to determine the cause and solution. If the fault  
persists, contact Emerson® Channel Support.  
Table 7-3 Troubleshooting table  
Problem  
Cause  
Solution  
UPS is short-circuited or  
overloaded  
Ensure UPS is Off. Disconnect all loads and ensure nothing is lodged in  
output receptacles. Ensure loads are not defective or shorted internally.  
Check to ensure the internal battery is connected. If it is not, make the  
connection and try to start the unit. If the battery is connected, leave the  
UPS connected to input power for 24 hours to recharge batteries, then try  
to start the unit.  
UPS fails to start  
Batteries are not charged  
enough or not connected  
UPS is operating from battery mode. Ensure UPS is securely plugged  
into the wall receptacle.  
UPS is not plugged in  
Battery indicator UPS input protection fuse has  
UPS is operating from battery mode. Save data and close applications.  
Replace UPS input fuse, then restart UPS.  
is illuminated  
blown/opened  
UPS is operating from battery mode. Save data and close applications.  
Ensure mains supply voltage is within acceptable limits for UPS.  
Mains power is out of tolerance  
Keep UPS plugged in continuously at least 24 hours to recharge  
batteries.  
Batteries are not fully charged  
UPS has  
reduced battery UPS is overloaded  
backup time  
Check load level indicator and reduce the load on the UPS.  
Batteries may not be able to  
Replace batteries. Contact your local dealer, Emerson representative or  
Emerson Channel Support for replacement battery kit.  
hold a full charge due to age  
Check battery connections, completely power down and restart UPS.  
Battery indicator Battery source is not available;  
NOTE: If the battery circuit opens while the UPS is running, it will be  
detected when the next battery test is performed.  
is flashing.  
continuous horn.  
The AC input powers the PFC input and serves as the bypass source. If  
the AC is present but the voltage or frequency exceeds the acceptable  
range for safe operation with a load, the bypass will be disabled and this  
indicator will flash, indicating that the bypass is unavailable.  
Because the voltage or  
frequency is outside acceptable  
limits, the bypass is disabled.  
Bypass indicator  
is flashing.  
Liebert® GXT4User Manual  
60  
       
Troubleshooting  
When reporting a UPS issue to Emerson, include the UPS model and serial number. These are located in  
several places for your ease of location:  
• on the top panel (rack mount orientation)  
• the left side (tower orientation)  
• the rear panel  
• on the front of the unit behind the front plastic bezel  
• on the LCD select Main Menu > About.  
61  
Liebert® GXT4User Manual  
Troubleshooting  
Page intentionally left blank.  
Liebert® GXT4User Manual  
62  
Specifications  
8.0 Specifications  
Table 8-1 UPS specifications—5000, 6000, 8000 and 10,000 models  
GXT4-  
GXT4-  
GXT4-  
GXT4-  
Model Number  
Model Rating  
5000RT208  
6000RT208  
8000RT208  
10000RT208  
4000W/5000VA  
4800W/6000VA  
7200W/8000VA  
9000W/10000VA  
Dimensions, Rack Mount, W x D x H  
Unit, in. (mm)  
16.9 x 26.1 x 6.8 (430 x 662 x 173)  
35 x 27 x 26 (889 x 686 x 661)  
16.9 x 26.5 x 10.3 (430 x 672 x 261)  
35 x 27 x 32 (889 x 686 x 813)  
Shipping, in. (mm)  
Weight lb (kg)  
131.8 (59.8)  
202.8 (92)  
212.7 (96.7)  
297.6 (135)  
Unit, lb (kg)  
Shipping, lb (kg)  
Input AC Parameters  
Nominal Operating Frequency  
Factory Default VAC  
50 or 60Hz (Factory Default is 60Hz)  
120/208VAC at 120 degrees  
120 degrees  
120/208VAC at 120 degrees  
120 degrees  
L1-L2 Factory Default Input Phase Angle  
Allowable Input Phase Angle  
120, 180, 240 degrees, auto-sensing on application of alternating current  
(Restrictions for L-N voltages other than 120VAC)  
120 VAC nominal  
Factory Default L1-N, L2-N VAC  
User Configurable L1-N, L2-N VAC  
Input Frequency w/o Battery Operation  
Input Power Connection  
100/110/115/120VAC (can be modified with configuration program)  
40 - 70 Hz  
Hard-Wired Terminal Block 3W + G (L-L-N-G)  
150VAC  
L1-N, L2-N Maximum Allowable VAC  
Output AC Parameters  
Factory Default VAC  
120/208VAC @ 120 degrees  
120 degrees  
L1-L2 Factory Default Output Phase Angle  
Allowable Output Phase Angle  
Factory Default L1-N, L2-N VAC  
120, 180, 240 degrees, auto-sensing on initial application of input AC  
120VAC nominal  
User Configurable L1-N, L2-N VAC  
L1-N, L2-N, Operating Load Range  
105% to 130%  
100/110/115/120/127VAC, ±2%  
1 Minute  
10 seconds  
1 second  
131% to 150%  
151% to 200%  
>200% (impact load)  
At least 5 cycles  
Bypass Protection Limits  
Disable Bypass Operation  
Re-Enable Bypass Operation  
Disable Bypass Operation  
Environmental  
If input voltage exceeds ±15% of the nominal voltage  
If input voltage returns to within ±10% of nominal output voltage  
When the input frequency prevents synchronous operation  
32 to 104 (0 to 40)  
5 to 122 (-15 to 50)  
Operating Temp, °F (°C)  
Storage Temp, °F (°C)  
Relative Humidity  
0% to 95%, non-condensing  
Up to 10,000 ft. (3000m) at 77°F (25°C) without derating  
less than 55dBA at 3.2ft. (1m) rear; less than 50dBA at 3.2ft. (1m) front and sides  
Operating Elevation  
Audible Noise  
Agency  
Safety  
UL 1778, c-UL Listed  
FCC Class A  
RFI/EMI  
Surge Immunity  
Transportation  
IEEE/ANSI C62.41 Category A & B  
ISTA Procedure 1E  
63  
Liebert® GXT4User Manual  
     
Specifications  
Table 8-2 UPS specifications—Liebert GXT4-6000RTL630  
Model Number  
Model Rating  
Dimensions, Rack Mount, W X D X H, in. (mm)  
GXT4-6000RTL630  
4200W/6000VA  
Unit  
16.9 x 22.6 x 8.5 (430 x 574 x 217)  
35 x 27 x 29 (889 x 686 x 737)  
Shipping  
Weight, lb (kg)  
Unit  
132.2 (60)  
216.5 (98)  
Shipping  
Input AC Parameters  
Nominal Operating Frequency  
Factory Default VAC  
50 or 60Hz (Factory Default, 60)  
208VAC  
208/220/230/240VAC  
User Configurable VAC  
(may be modified with configuration program)  
176 – 280VAC  
Operating Voltage Range Without Battery Operation  
Maximum Allowable VAC  
280VAC  
Input Frequency Without Battery Operation  
Input Power Connection  
40 - 70Hz  
L6-30P Plug (on PD-L630 power distribution box)  
Output AC Parameters  
Factory Default VAC  
208  
(2) L6-20R and (2) L6-30R on 12" (300mm) cords  
(on PD-L630 power distribution box)  
50Hz or 60Hz, Nominal  
Output Connections  
Frequency  
Waveform  
Sinewave  
Duration Inverter Will Support Rated Load  
105% to 130%  
1 Minute  
10 seconds  
1 second  
131% to 150%  
151% to 200%  
>200% (impact load)  
Bypass Protection Limits  
Disable Bypass Operation  
Re-Enable Bypass Operation  
Disable Bypass Operation  
Environmental  
At least 5 cycles  
If input voltage exceeds ±15% of the nominal voltage  
If input voltage returns to within ±10% of nominal output voltage  
When the input frequency prevents synchronous operation  
Operating Temp, °F (°C)  
Storage Temp, °F (°C)  
Humidity  
32 to 104 (0 to 40); No Derating  
5 to 122 (-15 to 50)  
0% to 95% Relative Humidity, non-condensing  
Up to 10,000 ft. (3000m) at 77°F (25°C) without derating  
Less than 55dBA at 3.2ft. (1m) rear;  
Operating Elevation  
Audible Noise  
Less than 50dBA at 3.2ft. (1m) front and sides  
Agency  
Safety  
UL 1778, c-UL Listed  
FCC Class A  
EMI/EMC  
ESD  
EN61000-4-2  
Radiated Susceptibility  
Electrical Fast Transient  
Surge Immunity  
Transportation  
EN61000-4-3  
EN61000-4-4  
EN61000-4-5  
ISTA Procedure 1E  
Liebert® GXT4User Manual  
64  
 
Specifications  
Table 8-3 Internal battery cabinet specifications  
GXT4-144VBATKIT  
GXT4-240VBATKIT  
GXT4-288VBATKIT  
Model Number  
Used with UPS Model  
GXT4-5000RT208  
GXT4-6000RT208  
GXT4-8000RT208  
GXT4-10000RT208  
GXT4-6000RTL630  
Dimensions, Rack Mount, W x D x H, in (mm)  
Unit  
8.1 x 19.3 x 2.8  
7.2 x 15.4 x 4.4  
(184 x 390 x 113)  
10.3 x 18.4 x 7  
8.1 x 19.7 x 5.3  
(207 x 500 x 135)  
9.5 x 23.9 x 12.2  
(242 x 607 x 310)  
(206 x 490 x 70)  
10.3 x 23.7 x 12.2  
(262 x 602 x 310)  
Shipping  
(262 x 467 x 178)  
Weight lb (kg)  
Unit  
75.8 (34.4)  
81.1 (36.8)  
45.4 (20.6)  
50.7 (23)  
71.1 (32.3)  
76.4 (34.7)  
Shipping  
Type  
Valve-regulated, non-spillable, flame retardant, lead acid  
Quantity x V x Rating  
Battery Mfr / Part #  
Backup Time  
2 x 6 x 12V x 9.0 AH  
CSB UPS12460F2  
2 x 10 x 12V x 5.0AH  
CSB/HR1221W  
2 x 12 x 12V x 9.0 AH  
CSB UPS12460F2  
Recharge Time  
Environmental  
5 hours to 90% capacity after full discharge into 100% load  
32 to 104 (0 to 40)  
5 to 122 (-15 to 50)  
Operating Temp, °F (°C)  
Storage Temp, °F (°C)  
Relative Humidity  
0% to 95%, non-condensing  
Up to 10,000 ft. (3000m) at 77°F (25°C) without derating  
Operating Elevation  
Agency  
Safety  
RFI/EMI  
UL 1778, c-UL Listed  
FCC Class A  
Transportation  
ISTA Procedure 1A  
65  
Liebert® GXT4User Manual  
 
Specifications  
Table 8-4 External battery cabinet specifications  
GXT4-144VBATT  
GXT4-240VBATT  
GXT4-288VBATT  
Model Number  
GXT4-5000 &  
GXT4-8000 &  
GXT4-6000RTL630  
Used w/UPS Model  
GXT4-6000RT208  
GXT4-10000RT208  
Dimensions, W x D x H, in. (mm)  
Unit (with bezel)  
16.9 x 26.1 x 3.3  
(430 x 662 x 85)  
25.8 x 34.3 x 12.3  
(655 x 872 x 312)  
16.9 x 22.6 x 6.8  
(430 x 574 x 173)  
20.9 x 29.3 x 18.7  
(530 x 745 x 475  
16.9 x 26.5 x 6.8  
(430 x 672 x 173)  
24.5 x 33.1 x 18.7  
(622 x 842 x 475)  
Shipping  
Weight, lb (kg)  
99.9 (45.3)  
121 (55)  
143.3 (65)  
176.4 (80)  
167.6 (76.2)  
198 (90)  
Unit  
Shipping  
Battery Parameters  
Type  
Valve-regulated, non-spillable, lead acid  
2 x 10 x 12V x 9.0AH  
Qty x V  
2 x 6 x 12V x 9.0 AH  
2 x 12 x 12V x 9.0 AH  
Battery Mfr., Part #  
Backup Time  
CSB UPS12460F2; CSBHR1234WF2  
Environmental  
Operating Temp, °F (°C)  
Storage Temp, °F (°C)  
Relative Humidity  
Operating Elevation  
Agency  
32 to 104 (0 to 40)  
5 to 122 (-15 to 50)  
0% to 95%, non-condensing  
Up to 10,000 ft. (3000m) at 77°F (25°C) without derating  
Safety  
UL 1778, c-UL Listed  
FCC Class A  
RFI/EMI  
Transportation  
ISTA Procedure 1A  
Table 8-5 Power distribution specifications: GXT4-5000RT208, GXT4-6000RT208 and GXT4-6000RTL630 *  
Power Distribution Box Model #  
PD2-001  
PD2-002 PD2-003 PD2-004 PD2-005 PD2-006 PD2-007 PD2-L630 *  
PD Model #  
PD2-HDWR-MBS  
Dimensions, W x D x H, in (mm)  
Unit  
4.7x13.2x4.1  
5.2x15.5x3.5 (132x393x88)  
(119x335x105)  
Shipping  
10.2x18.4x8.7  
9.5x20.7x9.1 (242x527x230)  
(260x467  
x222)  
Weight, lb (kg)  
Unit  
6 (2.7)  
8.8 (4)  
11 (5)  
8.6 (3.9) 8.6 (3.9) 9.9 (4.5) 10.6 (4.8) 9.5 (4.3) 9.5 (4.3)  
10.8 (4.9) 10.8 (4.9) 12.1 (5.5) 12.8 (5.8) 11.7 (5.3) 11.7 (5.3)  
8.8 (4)  
11 (5)  
Shipping  
8.2 (3.7)  
Electrical Specifications  
Amp Rating  
30A 2-pole input breaker for UPS input power  
(1) L14-30P on a 10.5 ft. (3.2m) cord  
Input Power  
Connections  
Hard-Wired Terminal  
Block 3W + G (L-L-N-G)  
(1) L6-30P  
Output  
Power  
Connection  
(4) 5-20R  
(1) L14-30R  
(1) L6-30R  
(2) 5-20R (4) 5-20R (4) L5-20R (4) L5-20R  
(2) L6-20R (2) L6-30R (2) L5-30R (2) L6-30R  
(2) L5-20R (2) L6-30R  
(2) L6-20R (2) L6-20R  
Hard-Wired Terminal  
Block 3W + G (L-L-N-G)  
(4) L6-20R  
*
PD2-L630 is only compatible with the GXT4-6000RTL630 UPS model  
Liebert® GXT4User Manual  
66  
   
Specifications  
Table 8-6 Power distribution box specifications for GXT4-8000RT208 and GXT4-10000RT208  
Power Distribution Box Model #  
PD2-103 PD2-104  
POD Model #  
PD2-101  
PD2-102  
PD2-105  
PD2-106  
Dimensions, W x D x H, in. (mm)  
Unit  
7.4 x 5.7 (188 x 145)  
Shipping  
11.9 x 20.6 x 8.7 (302 x 522 x 220)  
Weight, lb (kg)  
Unit  
Shipping  
4.4 (2)  
6.6 (3)  
6.6 (3)  
8.8 (4)  
6.6 (3)  
8.8 (4)  
6.6 (3)  
8.8 (4)  
4.4 (2)  
6.6 (3)  
6.6 (3)  
8.8 (4)  
Electrical Specifications  
Amp Rating  
2-pole 60A Input Breaker  
Custom Connector 3W + G(L-L-N-G) to UPS  
(4) 5-15/20R  
Input Power  
Connection  
Output Power  
Connections  
(4) 5-15/20R  
(2) L5-30R  
(2) L5-20R  
(2) L6-30R  
(8) 5-15/20R  
(4) L6-20R  
(4) 5-15/20R  
(4) L6-30R  
(4) L6-20R  
(4) L5-20R  
(2) L6-30R  
(2) L6-20R  
(4) 5-15/20R  
Table 8-7 Power distribution box specifications for GXT4-8000RT208 and GXT4-10000RT208  
Power Distribution Box Model #  
POD Model #  
PD2-107  
PD2-108  
PD2-109  
PD2-200  
PD2-201  
PD2-202  
PD2-204  
Dimensions, W x D x H, in. (mm)  
Unit  
Shipping  
7.4 x 5.7 (188 x 145)  
11.9 x 20.6 x 8.7 (302 x 522 x 220)  
Weight, lb (kg)  
Unit  
6.6 (3)  
4.4 (2)  
6.6 (3)  
6.6 (3)  
Shipping  
8.8 (4)  
15 (6.8)  
Electrical Specifications  
Amp Rating  
2-pole 60A Input Breaker  
Input Power  
Connection  
Custom Connector 3W + G(L-L-N-G) to UPS  
Output Power  
Connections (4) L5-20R  
(2) L6-  
20R  
(4) IEC320-C19 (2) IEC320-C19  
(2) IEC309-32A  
(4) IEC320-C13  
(2) L14-30R  
(12) IEC320-C13  
(4) 5-15/20R  
(2) L6-  
30R  
(4) IEC320-C13 (8) IEC320-C13  
67  
Liebert® GXT4User Manual  
   
Specifications  
Table 8-8 Battery run time, minutes  
208/120 VAC RT Models  
208 VAC RT Model  
Number of External  
Load Percent  
of Capacity  
Battery Cabinets  
5 kVA  
134  
65  
6 kVA  
112  
52  
8 kVA  
121  
63  
10 kVA  
98  
6 kVA (L630)  
92  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
48  
39  
39  
31  
42  
32  
34  
27  
21  
29  
22  
26  
20  
15  
22  
16  
18  
Internal Battery  
16  
12  
18  
13  
16  
12  
9
14  
10  
12  
10  
8
11  
7
10  
8
6
9
7
9
7
5
8
5
8
281  
144  
92  
235  
119  
77  
256  
142  
100  
72  
206  
113  
79  
265  
124  
99  
67  
53  
55  
67  
Internal Battery  
+ 1 External  
50  
40  
55  
42  
52  
40  
32  
44  
34  
44  
Battery Cabinet  
33  
26  
36  
27  
34  
27  
21  
29  
21  
27  
23  
18  
25  
20  
24  
20  
15  
22  
16  
21  
441  
222  
146  
108  
84  
367  
186  
120  
88  
400  
217  
156  
114  
90  
322  
175  
124  
90  
462  
223  
177  
126  
98  
Internal Battery  
+ 2 External  
68  
72  
68  
53  
77  
57  
85  
Battery Cabinets  
55  
43  
59  
45  
66  
46  
38  
49  
37  
52  
40  
32  
43  
35  
48  
36  
27  
39  
29  
43  
603  
304  
198  
147  
117  
95  
505  
252  
166  
122  
95  
550  
298  
210  
156  
126  
106  
86  
444  
236  
170  
126  
100  
82  
671  
323  
254  
182  
145  
126  
100  
83  
Internal Battery  
+ 3 External  
78  
Battery Cabinets  
81  
63  
68  
68  
53  
72  
53  
57  
45  
61  
50  
74  
50  
40  
55  
42  
65  
Run times in this table are approximate. They are based on new, fully charged standard battery modules at a temperature of 77°F (25°C) with  
100% resistive UPS loading. Run times listed above can vary by ±5% due to manufacturing variances of the individual batteries.  
Liebert® GXT4User Manual  
68  
   
Specifications  
Table 8-8 Battery run time, minutes (continued)  
208/120 VAC RT Models  
208 VAC RT Model  
Number of External  
Battery Cabinets  
Load Percent  
of Capacity  
5 kVA  
766  
389  
252  
188  
149  
122  
104  
88  
6 kVA  
638  
322  
208  
156  
122  
100  
84  
8 kVA  
696  
381  
269  
198  
161  
136  
111  
92  
10 kVA  
566  
302  
214  
161  
129  
107  
87  
6 kVA (L630)  
883  
429  
336  
237  
190  
166  
135  
111  
100  
90  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
Internal Battery  
+ 4 External  
Battery Cabinets  
72  
72  
78  
60  
83  
67  
68  
53  
75  
56  
939  
476  
307  
227  
181  
149  
127  
110  
95  
783  
393  
255  
190  
149  
122  
104  
88  
854  
467  
329  
239  
195  
166  
136  
114  
102  
91  
685  
370  
262  
195  
156  
130  
109  
88  
1108  
538  
420  
296  
235  
207  
168  
139  
126  
115  
1329  
643  
506  
356  
283  
247  
201  
167  
152  
139  
Internal Battery  
+ 5 External  
Battery Cabinets  
78  
84  
84  
67  
73  
1116  
564  
364  
268  
212  
177  
149  
130  
114  
101  
931  
468  
301  
223  
177  
145  
122  
106  
91  
1015  
553  
389  
285  
228  
194  
160  
136  
119  
110  
814  
440  
310  
229  
184  
153  
129  
106  
100  
86  
Internal Battery  
+ 6 External  
Battery Cabinets  
82  
Run times in this table are approximate. They are based on new, fully charged standard battery modules at a temperature of 77°F (25°C) with  
100% resistive UPS loading. Run times listed above can vary by ±5% due to manufacturing variances of the individual batteries.  
Using the configuration program or the LCD panel, the user may specify the number of external battery  
cabinets attached to the UPS. The factory default is programmed for internal batteries only.  
Table 8-8 shows the estimated run times at different loads.  
69  
Liebert® GXT4User Manual  
Specifications  
8.1 Auto-Learning Battery Run Times  
As batteries age, the estimated run times may become less accurate. The Liebert GXT4 is programmed to  
“learn” from a full battery discharge and modify the estimated run time for the measured battery capacity.  
This can improve accuracy and compensate for aging batteries or batteries that operate at different  
ambient temperatures.  
The UPS will update the anticipated run time calculation only under certain conditions.  
• The UPS must have a steady load that is greater than 20%.  
• The UPS must be at 100% charge at the start of a battery discharge.  
• The battery discharge must continue uninterrupted until the batteries reach their end-of-discharge  
voltage.  
If all conditions are not met, the run time calculation will not be modified.  
If the configuration program is used to change the number of battery cabinets, then the values in Table 8-8  
will be restored. This will override any value that is Auto-Learned.  
8.2 Product Warranty Registration  
Registration is not required to activate the product warranty on a Liebert UPS. Registration is required to  
qualify for the Product Protection Promise. To register, visit the Emerson Network Power® Web site to fill  
out the online form at:  
To contact warranty support by e-mail: [email protected]  
8.3 Technical Support  
Technical support contacts are listed on the back cover of this document. To contact Emerson Channel  
Product Support:  
Phone  
• NORTH AMERICA: 1-800-222-5877  
• OUTSIDE NORTH AMERICA: 00-800-1155-4499  
E-mail  
• TECHNICAL SUPPORT: [email protected]  
Liebert® GXT4User Manual  
70  
     
Technical Support / Service  
Web Site  
Locations  
United States  
Monitoring  
1050 Dearborn Drive  
P.O. Box 29186  
800-222-5877  
Outside North America: +00800 1155 4499  
Columbus, OH 43229  
Europe  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD) Italy  
+39 049 9719 111  
Single-Phase UPS & Server Cabinets  
800-222-5877  
Outside North America: +00800 1155 4499  
Three-Phase UPS & Power Systems  
800-543-2378  
Outside North America: 614-841-6598  
Thermal Management Systems  
800-543-2778  
Fax: +39 049 5841 257  
Asia  
7/F, Dah Sing Financial Centre  
108 Gloucester Road, Wanchai  
Hong Kong  
852 2572220  
Fax: 852 28029250  
Outside the United States: 614-888-0246  
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims  
all liability for damages resulting from use of this information or for any errors or omissions.  
© 2016 Liebert Corporation  
All rights reserved throughout the world.  
Specifications subject to changewithout notice.  
® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.  
SL-23194_REV2_6-16  
590-1365-501A  
Emerson Network Power  

Sunpentown Intl Wa 1230e User Manual
Sunbeam 2544 User Manual
Sharp Mx M850 User Manual
Sanyo Stb1010c1 User Manual
Panasonic Dp 150fx User Manual
NEC MULTISYNC X552S User Manual
Lexmark X544w User Manual
DELTA 150LNL User Manual
CRAFTSMAN 919.165612 User Manual
CRAFTSMAN 113.299040 User Manual