York Y33 User Manual

246653-YTG-E-0108  
TOMORROW’S UNIT TODAY  
GENERAL  
®
Introducing the YORK Millennium 25, 30, & 40 ton rooftop  
line - units designed to provide peak performance and value  
both today and for years to come. Millennium units are manu-  
factured at an ISO 9001 registered facility, and each rooftop  
is completely computer-run tested prior to shipment.  
TECHNICAL GUIDE  
The Millennium is designed to be flexible enough to meet  
your needs today and in the future. The true value of YORK’s  
Millennium is that it can be designed to fit any need, from  
cooling only, constant volume applications to variable air vol-  
ume systems with variable frequency drive.  
®
MILLENNIUM  
SINGLE PACKAGE ROOFTOP UNITS  
Y32, Y33 & Y34  
FEATURING:  
25, 30, & 40 TON  
Cooling Only Units  
Cooling/Gas Heating Units (Natural) Standard or  
Modulating Gas Heat available  
Cooling/Electric Heating Units  
Cooling/Hot Water Heating Units  
Cooling/Steam Heating Units  
Industry Leading Efficiency  
25 TON (10 EER)  
30 & 40 TON (9.5 EER)  
Double Wall Construction  
Stainless Steel or Powder Coated Drain Pan  
Multiple Scroll Compressors  
Multiple Refrigeration Circuits  
Upgradable Motor Efficiency  
Enhanced Filtration  
Vibration Isolated Supply Fan and Motor  
Technicoated Evaporator and Condenser Coils  
High Capacity Evaporator Coils  
Single Power Point Connection  
Easy Access Hinged Doors  
Variable Air Volume  
Constant Air Volume  
30 TON UNIT SHOWN  
Factory Installed Economizers/Disconnect/Convenience  
Outlet/Control Options  
Low Profile  
®
MILLENNIUM SIMPLICITY ELITE™ FEATURES:  
Single Button Programming and LED Display  
Designed to operate on both constant and variable air  
volume units  
365-Day real time clock with automatic Daylight Savings  
time adjustment  
Occupancy Schedule allowing two schedules per day  
20 Holiday schedules with programmable schedules that  
can start at any time, day or night  
Patented Comfort Ventilation operation for economical  
and comfortable economizer operation  
Demand Ventilation option to assure proper IAQ condi-  
ISO 9001  
Certified Quality  
Management System  
tions based on available space or return air CO levels  
2
Temperature/Humidity programming algorithm allows  
programmable limits to help control humidity in the space  
Smoke Purge automatically ventilates the space when  
smoke is detected  
Monitors dirty filters and proves airflow before starting  
heating or cooling  
Intelligent recovery to bring the space temperature up to  
occupied setting quicker and more economically  
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE  
     
246653-YTG-E-0108  
LIST OF FIGURES  
Fig.#  
Pg.#  
Fig.#  
Pg.#  
2
18 STEAM PIPING CROSS SECTION . . . . . . . . . . . . . . 25  
HOT WATER COIL - 25 & 30 TON, 1 ROW,  
3
4
5
6
7
8
9
HOT WATER COIL - 25 & 30 TON, 1 ROW,  
21 ALTITUDE/TEMPERATURE CONVERSION  
HOT WATER COIL - 25 & 30 TON, 1 ROW,  
HOT WATER COIL - 25 & 30 TON, 1 ROW,  
25 POWER EXHAUST - ONE FORWARD CURVE  
HOT WATER COIL - 40 TON, 1 ROW,  
26 POWER EXHAUST - TWO FORWARD CURVED  
HOT WATER COIL - 40 TON, 1 ROW,  
HOT WATER COIL - 40 TON, 1 ROW,  
HOT WATER COIL - 40 TON, 1 ROW,  
10 HOT WATER COIL - 25 & 30 TON, 2 ROW,  
11 HOT WATER COIL - 25 & 30 TON, 2 ROW,  
12 HOT WATER COIL - 25 & 30 TON, 2 ROW,  
13 HOT WATER COIL - 25 & 30 TON, 2 ROW,  
36 CLEARANCES - HOOD/ECONOMIZER & MOTOR  
37 CLEARANCES - HOOD/ECONOMIZER & MOTOR  
Johnson Controls Unitary Products  
3
246653-YTG-E-0108  
LIST OF TABLES  
Tbl.#  
Pg.#  
Tbl.#  
Pg.#  
6
9
34 COOLING PERFORMANCE 40 TON STANDARD  
CAPACITY COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38  
MODULATING GAS HEATING CAPACITIES . . . . . . 12  
35 COOLING PERFORMANCE 40 TON HIGH  
CAPACITY COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41  
WATER PRESSURE DROP (1 ROW,  
10 STATIC RESISTANCE HOT WATER COIL  
43 POWER EXHAUST - ONE FORWARD CURVED  
44 POWER EXHAUST - TWO FORWARD CURVED  
12 STATIC RESISTANCE HOT WATER COIL  
14 WATER PRESSURE DROP (2 ROW,  
15 STATIC RESISTANCE HOT WATER COIL  
48 ELECTRICAL DATA 25 TON WITH ELECTRIC  
HEAT R22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63  
49 ELECTRICAL DATA 30 TON WITH ELECTRIC  
HEAT R22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64  
50 ELECTRICAL DATA 40 TON WITH ELECTRIC  
HEAT R22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65  
18 STATIC RESISTANCE HOT WATER COIL  
51 ELECTRICAL DATA 25 TON WITH POWER  
52 ELECTRICAL DATA 30 TON WITH POWER  
21 STATIC RESISTANCE STEAM COIL  
53 ELECTRICAL DATA 40 TON WITH POWER  
23 STATIC RESISTANCE STEAM COIL  
54 ELECTRICAL DATA 25 TON WITH ELECTRIC HEAT  
AND POWER EXHAUST R22 . . . . . . . . . . . . . . . . . . 69  
25 SUPPLY FAN MOTOR AND DRIVE DATA . . . . . . . . 27  
55 ELECTRICAL DATA 30 TON WITH ELECTRIC HEAT  
AND POWER EXHAUST R22 . . . . . . . . . . . . . . . . . . 72  
56 ELECTRICAL DATA 40 TON WITH ELECTRIC HEAT  
AND POWER EXHAUST R22 . . . . . . . . . . . . . . . . . . 75  
29 DRIVE ADJUSTMENT FOR POWER EXHAUST  
30 DRIVE ADJUSTMENT FOR POWER EXHAUST  
31 COOLING PERFORMANCE 25 TON . . . . . . . . . . . . . 31  
32 COOLING PERFORMANCE 30 TON STANDARD  
CAPACITY COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32  
33 COOLING PERFORMANCE 30 TON HIGH  
CAPACITY COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
4
Johnson Controls Unitary Products  
246653-YTG-E-0108  
®
YORK Millennium  
Efficient, Durable Scroll Compressors - The Millennium  
design uses industrial grade hermetic scroll compressors for  
peak efficiency and low noise operation. The compressor  
design is so durable that it can actually hold more liquid  
charge without slugging than is present in each refrigerant  
circuit at shipment, dramatically reducing the chances of ever  
slugging a compressor with liquid charge.  
OVERVIEW  
Introducing the YORK Millennium 25, 30, & 40 ton rooftop  
line - units designed to provide peak performance and value  
both today and for years to come. When we asked our cus-  
tomers what they wanted in a new rooftop line, we were care-  
ful to listen to both the needs of today and tomorrow. So,  
you'll find that Millennium units not only help you solve  
today's problems, but can handle tomorrow's difficulties as  
well:  
Multiple Refrigeration Circuits for Greater Turndown - The  
YORK Millennium unit has intertwined 10 ton circuits (12.5  
ton circuits on the 25 ton) - giving the best unloading capabil-  
ity in the industry. With more and more designs requiring  
higher outside air quantities, the lower capacity capability is  
an outstanding way to neutralize outside air without over-con-  
ditioning the space on off-peak days. And, Millennium's high  
quality balance-port thermal expansion valves are more  
effective at metering refrigerant flow in part-load conditions,  
making Millennium a peak-performer across a wide capacity  
range.  
Industry Leading Efficiency - The Millennium's 9.5 EER (10  
EER 25 ton) rating makes it the most frugal energy consumer  
in its class. When it comes to lower operating costs, Millen-  
nium simply outperforms the competition.  
Double Wall Construction - Millennium units come double  
walled as standard. The galvanized sheet metal liner pro-  
vides the best protection against microbial growth, helping  
both the unit and the indoor air stay fresh and clean. And, the  
rigid sheet metal inner liner keeps the insulation completely  
out of the air stream, eliminating concerns about fiberglass  
particles.  
FEATURES AND BENEFITS  
When it comes to flexibility, Millennium really shines. Our cus-  
tomers were clear about one thing - not all installations are  
the same. Some have very simple needs, others are more  
involved. The YORK Millennium serves both markets - and all  
of those in between - extremely well. YORK engineers crafted  
a design which is both uniquely flexible and competitive, giv-  
ing you the best of both worlds. In addition to a competitive  
base product, Millennium offers unparalleled flexibility.  
Optional features include:  
Drain Pan Whisks Away Condensate - Condensate is fre-  
quently the source of microbial contamination. Competitive  
drain pans often are insufficiently sloped to properly drain all  
of the condensate, causing drain pan corrosion and bacterial  
growth to begin almost immediately. The YORK design is  
sloped at the 1/4” per foot recommended by the ASHRAE  
62.1-2004 ventilation draft standard, with an extra large drain  
connection capable of removing up to three gallons of con-  
densate per minute. It is available in either powder coat  
painted steel or stainless steel for long life.  
Variable Air Volume - YORK gives you the ability to vary air  
volume by inlet guide vanes or variable frequency drive - the  
choice is yours. All Millennium VAV units come standard with  
hot gas bypass to give extended operation range.  
Johnson Controls Unitary Products  
5
   
246653-YTG-E-0108  
Optional Head Pressure Control - For those applications  
where mechanical cooling is required below 40°F, optional  
low ambient operation allows compressor operation down to  
F.  
ers. Comparative enthalpy, single enthalpy and dry bulb con-  
trol are available.  
Optional Factory Installed Disconnect - A conveniently  
located actuator handle in the front of the unit can disconnect  
line power to the entire unit, eliminating the need for a field  
provided disconnect. The handle may also be locked in either  
position through the use of a standard padlock. Millennium's  
single point power connection makes this option particularly  
appealing. If desired, the disconnect may be ordered with a  
115 volt, GFCI protected convenience outlet, including a fac-  
tory wired transformer to power the outlet from the single  
point power connection; the convenience outlet remains  
operational when the disconnect is open.  
Easily Upgrade Motor Efficiency to Meet Tighter Codes -  
Optional high efficiency motors help you make simple  
upgrades to meet more demanding building and energy  
codes.  
Enhanced Filtration Options - Millennium gives designers the  
flexibility to meet various IAQ requirements with a full range  
of rigid and throwaway filters at different efficiency levels.  
Vibration Isolation - The Millennium's neoprene mounts are  
typically sufficient for most applications but when sound and  
vibration transmission are a major concern, YORK offers 1"  
and 2" isolation springs for even greater protection from sup-  
ply air fan noise and vibration.  
Heating Done Your Way - Millennium offers the choice of nat-  
ural gas standard or modulating gas heat, electric resistance  
heat, hot water heat, steam, or no heat at all. Very simply, the  
choice is yours.  
Corrosion Resistant Coils- Many industrial and seacoast  
applications require enhanced protection from corrosive envi-  
ronments.  
INSTALLATION FEATURES  
With YORK Millennium, high performance doesn't mean high  
complexity. YORK listened carefully to make sure that Millen-  
nium was as simple as possible, and service convenience  
comes standard with each unit. From a single curb size to the  
easy service access, you'll find that Millennium was designed  
to be easy from start to finish.  
Optional TechniCoated Coated Condenser and Evapo-  
rator Coils - Many industrial and seacoast applications  
require enhanced protection from corrosive environ-  
ments. The special dipped phenolic coating process  
provides a high level of protection for the exposed con-  
denser coil.  
Full Range of Air Flows and Static Pressures - The Millen-  
nium design gives a complete offering of supply air flows and  
static pressure combinations to meet most every application  
requirement.  
Optional Copper-Copper Condenser and Evaporator  
Coils - For corrosion resistance.  
High Capacity Evaporator Coils - For those applications  
which require slightly more capacity than offered by the stan-  
dard Millennium product, YORK offers the option of higher  
capacity evaporator coils, boosting cooling output without  
increasing unit size. (30 & 40 Ton R-22 only)  
Single Power Point Connection - Millennium units have a sin-  
gle gas and electric connection, minimizing time at the job  
site. For further installation flexibility, power and gas connec-  
tions may be brought up from the curb or through the side of  
the unit.  
Variety of Exhaust Air Options - YORK Millennium offers a  
wide variety of exhaust air options, including barometric  
relief, non-modulating power exhaust, and modulating power  
exhaust. And, because Millennium units use forward-curved  
blowers for power exhaust fans, they can exhaust up to 100%  
of the nominal supply air at much greater static pressure  
loads than competitive units. Not available on end return.  
Simple Controls - Millennium's controls system is easy to  
understand and apply, and it doesn't lock you into proprietary  
devices. A choice for YORK Millennium today does not limit  
your choices tomorrow.  
Rain Hoods Rotate Into Place - No bulky, field--installed rain  
hoods here. Millennium rain hoods ship rotated inside the  
unit. Once on the job, installer merely rotates the hood  
upward and puts in a few screws - an easy one-person job.  
NOTE: In most applications, the supply fan will keep the  
return at negative pressure. A barometric relief will  
function better when ducted to building space, not  
the return.  
Excellent Access for Service - Service access on Millennium  
is a snap. Hinged and latched door options give access on  
both sides of the unit to all major components. Some doors  
have positive action slide latches for even greater ease of  
access. All service fittings are conveniently located to mini-  
mize time and effort.  
Optional Factory Installed Economizers - Millennium units  
offer economizers with Standard or Optional low leak damp-  
6
Johnson Controls Unitary Products  
 
246653-YTG-E-0108  
PITCHED ROOF  
ANGLED CONDENSER  
COILS  
SOLID, CLASS II FAN CONSTRUCTION  
INTERTWINED COIL  
DOUBLE WALL CONSTRUCTION  
HINGED, LATCHED  
ACCESS DOORS  
LOW LEAK DAMPERS  
Low Profile - Millennium units stand only 64” above their  
curb, minimizing potential aesthetic conflicts.  
CONSTRUCTION FEATURES  
YORK's Millennium rooftop line is built for the long haul, with  
high end features and construction offered at a competitive  
price. Millennium units are manufactured at an ISO 9001 reg-  
istered facility, and each rooftop is completely computer-run  
tested prior to shipment. Some of the valuable construction  
features of the Millennium which are not found on competitive  
units include:  
Extended flue connection - Each gas unit ships with a field  
mounted external flue. The flue lifts all products of furnace  
combustion far above the unit - eliminating the possibility of  
corrosion in the furnace heat exchanger from recirculating  
flue gases.  
Protective Covering - Special polyurethane sleeves which  
cover the distributor tubing keep distributor tubes from con-  
tacting each other and wearing out.  
Double Wall Construction - Each unit has both an exterior  
and an interior wall, which make for a more rigid design with  
panels and doors that are solid, not flimsy. The unit features a  
fully framed construction for even greater stability.  
Built-in Hail Guard - Condenser coils angled at 30 degrees  
from the vertical are inherently protected from damage due to  
shipment, hail, etc.  
Powder Paint - Industry leading 1000 salt spray hour paint  
keeps the unit in great condition for years to come.  
Induced Draft Furnace - This design provides a positive  
exhaust of all combustion products.  
Johnson Controls Unitary Products  
7
 
246653-YTG-E-0108  
LIST OF FEATURES AND BENEFITS  
Field Installed Accessories  
Standard Features  
9.5 EER (10 EER on 25 ton)  
Double wall construction  
Major components have hinged and latched access  
doors  
Industrial duty scroll compressors  
Sturdy framed construction  
Sloped stainless steel or powder coated drain pan  
Separate 10 ton circuits (30 and 40 ton units) or 12.5 ton  
(25 ton unit)  
Intertwined evaporator coil  
Angled condenser coils for superior protection  
Single power point connection  
Through-the-curb or through-the-base utility connections  
Retractable outside air hoods  
Powder paint tested to 1000 salt spray hours  
Mechanical cooling from 40° F to 125° F  
1-1/2” insulation  
7-Day Programmable Wall Thermostat-Can be used with  
or without remote sensors. Can be used on CV and VAV  
units when wall thermostat is required for scheduling and  
temperature control.  
Energy Recovery Ventilators- 8,000 and 13,000 CFM  
models available. Great for applications involving 30% or  
more of required outdoor air where energy use and com-  
fort must be optimized.  
Wall Sensors- Remote space sensors used with CV or  
VAV unit for unit control via the Simplicity® Elite™ con-  
trol. Standard sensor, sensor with override and sensor  
with override and + 5 degree adjustment.  
Simplicity® Transporter- Device allows internet control  
and monitoring of HVAC units equipped with Simplicity®  
Elite™ controls.  
Phase Monitor Kit- Includes control and wiring to monitor  
and protect the unit from phase reversal, phase loss and  
low voltage.  
Burglar Bars- Prevent any type of building entry through  
the RTU unit with bars that block the return and supply  
openings on downflow applications.  
Partial perimeter roofcurb- Designed for application on  
all 25-40 ton Millennium rooftop units. 14" height.  
Barometric Relief Kit- Provides barometric relief hood  
and dampers for duct mounting on units requiring end  
return.  
Sloped unit roof with drip lip  
High and low refrigerant pressure protection  
Polyurethane sleeves to protect small diameter tubing  
Steel framing around blowers with deflection springs or  
rubber isolators for low vibration  
Fully factory packaged and run-tested  
10 year gas heat exchanger warranty  
One year compressor warranty  
One year warranty on all parts  
Natural Gas to Propane Conversion Kits- Contains ori-  
fices and gas valves parts to convert from Natural Gas to  
Propane. (Not available on modulating heat.)  
High Altitude Kit- Natural gas kit designed for natural gas  
heating applications between 2,000 and 6,000 feet  
above sea level.  
Factory Installed Options  
Economizer with standard or low leak dampers  
Natural gas standard or modulating gas heat with reli-  
able induced draft design  
Electric heat in three sizes  
Variable air volume using either inlet guide vanes, wired  
for VFD (variable frequency drive), or factory installed  
VFD.  
1, 2” blower isolator springs or rubber isolators  
A variety of blower horsepower offerings  
High efficiency motors  
High efficiency filtration  
Barometric relief  
Power exhaust of 100% of nominal air flow  
Technicoat corrosive resistant coating on condenser and  
evaporator coils  
Copper-Copper corrosive resistant condenser and evap-  
orator coils  
0°F low ambient operation of mechanical cooling  
Hot gas bypass (standard on all VAV units)  
High capacity evaporator coils  
Single unit disconnect  
Convenience outlet and transformer factory wired  
Hot water heating coil with one or two rows  
One row steam heating coil  
®
Simplicity Elite™ controls  
ModLINC translator  
York Commercial Comfort System (YCCS)  
8
Johnson Controls Unitary Products  
       
246653-YTG-E-0108  
NOMENCLATURE  
Johnson Controls Unitary Products  
9
 
246653-YTG-E-0108  
TABLE 1: GENERAL PHYSICAL DATA  
UNIT SIZE  
25 TON  
30 TON  
40 TON  
UNIT EER / IPLV  
(STANDARD CAPACITY EVAPORATOR)  
10.0 / 10.92  
9.5 / 10.97  
9.5 / 9.73  
COMPRESSOR DATA  
NUMBER/SIZE  
TYPE  
2 x 12.5 Ton  
3 x 10 Ton  
Scroll  
4 x 10 Ton  
Scroll  
Scroll  
UNIT CAPACITY STEPS  
50%, 100%  
33%, 67%, 100%  
25%, 50%, 75%, 100%  
INDOOR FAN AND DRIVE  
NUMBER / TYPE  
DIAMETER X WIDTH (INCHES)  
HP RANGE  
1 / FC  
1 / FC  
22 x 20  
1 / FC  
25 x 22  
22 x20  
7.5 - 20  
10 - 25  
10 - 25  
CFM RANGE (FULL LOAD)  
ESP RANGE  
6,000 - 12,500  
6,000 - 15,000  
0.2" - 4.0”  
8,000 - 18,000  
0.2" - 4.0"  
0.2” - 4.0”  
EXHAUST FAN  
NUMBER/SIZE/TYPE  
HP RANGE (SINGLE MOTOR)  
CFM  
1/FC  
2/FC  
7.5 - 15  
2/FC  
7.5 - 15  
5 - 10  
3,000 - 9,000  
4,000 - 18,000  
4,000 - 18,000  
STANDARD EVAPORATOR COIL  
SIZE (SQ. FT.)  
ROWS/FPI  
26.0  
26.0  
30.4  
3 / 13  
3 / 16  
4 / 13  
HIGH CAPACITY EVAPORATOR COIL  
SIZE (SQ. FT.)  
ROWS/FPI  
26.0  
26.0  
30.4  
2/16  
4 / 16  
4 / 16  
CONDENSER COIL  
SIZE (SQ. FT.)  
ROWS/FPI  
52.0  
48.8  
65.0  
2/16  
2 /16  
2 /16  
CONDENSER FANS  
QUANTITY / DIAMETER (INCHES)  
NOMINAL CFM  
4 / 24  
3 / 24  
6,800  
1.0  
4 / 24  
6,800  
1.0  
4,600  
MOTOR HP  
3 / 4  
ELECTRIC HEAT  
KW RANGE  
40 KW  
40 - 108  
40 - 108  
1
40 - 108  
1
1
80 AND 108 KW / CAPACITY STEPS (CV/VAV)  
2 / 1  
2 / 1  
2 / 1  
NATURAL GAS HEAT  
UNIT SIZE  
25 TON  
30 TON  
1 / 1  
2 / 1  
-
40 TON  
1 / 1  
267 MBH CAPACITY STEPS (CV/VAV)  
1 / 1  
533 MBH CAPACITY STEPS (CV/VAV)  
2 / 1  
2 / 1  
800 MBH CAPACITY STEPS (CV/VAV)  
-
6 / 1  
3 / 1*  
6 / 1  
267 MBH “MODULATING” CAPACITY STEPS (CV ONLY)  
533 MBH “MODULATING” CAPACITY STEPS (CV ONLY)  
800 MBH “MODULATING” CAPACITY STEPS (CV ONLY)  
6 / 1  
12 / 2  
-
12 / 2  
12 / 2  
17 / 3  
-
HOT WATER COIL  
22.5” x 65”  
25 Ton  
SIZE (INCHES)  
CAPACITY  
22.5" X 65”  
30 Ton  
22.5" X 65”  
40 Ton  
STEAM COIL  
SIZE (INCHES)  
TYPE  
21" X 65"  
Steam Coil  
FILTERS 2" TA  
4 / 16 x 25 & 6 / 20 x 25  
30.4  
NUMBER / SIZE  
4 / 16 x 25 & 6 / 20 x 25  
30.4  
4 / 16 x 25 & 6 / 20 x 25  
30.4  
FACE AREA (SQ. FT.)  
FILTERS 2" PLEATED, 30%  
4 / 16 x 25 & 6 / 20 x 25  
30.4  
NUMBER / SIZE  
4 / 16 x 25 & 6 / 20 x 25  
30.4  
4 / 16 x 25 & 6 / 20 x 25  
30.4  
FACE AREA (SQ. FT.)  
FILTERS 65% RIGID W/ 2” TA PREFILTERS  
4 / 16 x 25 & 6 / 20 x 25  
30.4  
NUMBER / SIZE  
4 /16 x 25 & 6 / 20 x 25  
30.4  
4 / 16 x 25 & 6 / 20 x 25  
30.4  
FACE AREA (SQ. FT.)  
FILTERS 95% RIGID W/ 2” TA PREFILTERS  
4 ea. 16 x 25 / 6 ea. 20 x 25  
30.4  
NUMBER / SIZE  
4 ea. 16 x 25 / 6 ea. 20 x 25  
30.4  
4 ea. 16 x 25 / 6 ea. 20 x 25  
30.4  
FACE AREA (SQ. FT.)  
* Unit Control Board with 3 heating outputs only, all other Unit Control Boards 2/1.  
10  
Johnson Controls Unitary Products  
 
246653-YTG-E-0108  
TABLE 2: REFRIGERANT CHARGE  
CHARGE  
FACTORY/ FIELD  
CHARGED  
UNIT (TONS)  
MODEL  
TYPE  
SYS #1  
SYS #2  
26lb / 0oz  
SYS #3  
SYS #4  
25  
25  
30  
30  
30  
30  
40  
40  
wo/HGBP  
w/HGBP  
wo/HGBP  
R22  
R22  
R22  
R22  
R22  
R22  
R22  
R22  
Factory  
Factory  
Factory  
Factory  
Factory  
Factory  
Factory  
Factory  
25 lb. / 8 oz.  
26 lb. / 0 oz.  
13 lb. / 4 oz.  
14 lb. / 6 oz.  
14 lb. / 0 oz.  
15 lb. / 2 oz.  
15 lb. / 5 oz.  
15 lb. / 13 oz.  
-
-
-
-
26 lb. / 0oz  
13 lb. / 8 oz.  
13 lb. / 8 oz.  
14 lb. / 10 oz.  
13 lb. / 8 oz.  
14 lb. / 10 oz.  
15 lb. / 5 oz.  
15 lb. / 5 oz.  
-
1
14 lb. / 10 oz.  
13 lb. / 8 oz.  
14 lb. / 10 oz.  
15 lb. / 4 oz.  
15 lb. / 4 oz.  
-
wo/HGBP  
w/HGBP  
-
w/HGBP  
-
wo/HGBP  
w/HGBP  
15 lb. / 15 oz.  
15 lb. / 15 oz.  
1.  
With high capacity evaporator coil.  
c. Ensure that it is offered in the Y34 unit. Read option  
model as N5.  
SELECTION PROCEDURE  
GIVEN:  
From the basic nomenclature, the model now becomes  
Y34AN5. Add voltage code of “4” for 460-3-60. Nomen-  
clature becomes Y34AN54.  
Required Cooling Capacity  
Required Sensible Cooling  
Required Heating (Gas)  
460,000 Btuh  
390,000 Btuh  
320,000 Btuh  
SELECT FAN SPEED AND HORSEPOWER  
REQUIREMENTS OF SUPPLY AIR FAN  
Entering Air on Evaporator  
Outside Design Temperature  
Supply Fan CFM  
83° F DB/ 67° F WB  
95° F  
1. Find Supply Air Performance Tables for the 40 ton unit.  
13,000 CFM  
1.25 IWG  
a. Check footnotes and make necessary additions or  
deductions to static resistance of ductwork:  
External Static Pressure  
Electrical Supply Voltage  
Economizer Required  
2” Throw Away Filters  
Constant Volume  
460-3-60  
Ductwork static resistance  
1.25 IWG  
Economizer static resistance addition  
(interpolate) =.25 IWG + Gas Heat (High) =  
0.5 IWG  
2.0 IWG  
Total Static Resistance  
b. Enter Fan Performance Table at 13,000 CFM and  
2.0 IWG static pressure:  
SELECT UNIT:  
1. Determine nominal tons:  
460,000 / 12,000 = 38.33 Tons  
RPM = 690  
BHP = 10.7  
Thus, a nominal 40 ton unit is selected.  
NOTE: Either a Class I or Class II blower could be used.  
2. Reference Cooling Capacity Table for a 40 ton unit with  
standard evaporator coil.  
c. Enter the Fan Motor Drive Tables. Selecting a 15 hp  
motor allows (service factor of 1.5) for a maximum  
operating BHP greater than the 10.7 BHP require-  
ment.  
a. Locate the table for a standard evaporator coil with  
95° F air on the condenser.  
b. Enter table at 13,000 CFM and 67°F WB air on  
evaporator  
SIZE OVERCURRENT PROTECTION DEVICE AND  
DETERMINE CIRCUIT AMPACITY  
c. Trace to 83° F Entering Dry Bulb column.  
1. Find electrical tables for the basic 40 ton unit.  
a. Enter table for 460-3-60 voltage.  
d. Read 493 MBH total capacity and 403 MBH sensi-  
ble capacity.  
The 40 ton unit will meet the cooling requirements. From  
the nomenclature, the unit will be a Y34. Choose the  
appropriate configuration for the next digit. Assuming  
bottom return and supply, the fourth digit would be an  
“A,” making the model Y34A.  
b. Find 15 hp in the Supply Air Fan column.  
c. Trace to Minimum Circuit Ampacity column - read  
104.  
d. Trace to Max. Fuse/Breaker Size column - read 110.  
e. Size wire and overprotection device accordingly.  
f. Check all footnotes.  
3. Find Gas Heating Capacity Table.  
a. Trace down Output column.  
b. Find output which exceeds 320,000 Btuh require-  
ment. The N5 option gives 426 MBH output.  
Johnson Controls Unitary Products  
11  
           
246653-YTG-E-0108  
TABLE 3: STANDARD GAS HEATING CAPACITIES  
1
3
INPUT CAPACITY (MBH)  
OUTPUT  
GAS RATE, CU. FT./HR.  
GAS HEAT  
OPTION  
AVAILABLE ON  
MODELS  
CAPACITY  
(MBH)  
1ST STAGE  
TOTAL  
1ST STAGE  
TOTAL  
2
N3  
N5  
N8  
Y32/Y33/Y34  
Y32/Y33/Y34  
Y34 ONLY  
267  
267  
267  
533  
800  
213  
426  
638  
247  
247  
247  
247  
495  
742  
4
267  
1.  
Heating capacity is only staged on CV models. VAV models use only one stage at full capacity.  
Blower motor heat not included.  
2.  
3.  
3
Based on a heat content of 1075 Btu/Ft.  
4.  
Unit Control Board with 3 heating outputs only. For all other Unit Control Boards the 1st Stage is 533 MBH.  
TABLE 4: TEMPERATURE RISE  
TABLE 5: MINIMUM HEATING CFM  
MODULES  
MODULES  
TON  
TON  
1
2
3
1
2
3
25  
30  
40  
5-35  
5-35  
5-30  
25-55  
20-50  
10-45  
-
-
25  
30  
40  
5,644  
5,644  
6,584  
7,183  
7,901  
8,779  
-
-
25-55  
13,169  
TABLE 6: MODULATING GAS HEATING CAPACITIES  
INPUT CAPACITY (MBH)  
MINIMUM MAXIMUM  
OUTPUT CAPACITY  
GAS RATE, CU. FT./HR.  
AVAILABLE ON  
MODELS  
GAS HEAT OPTION  
STEPS  
1
(MBH)  
MINIMUM  
MAXIMUM  
2
D3  
Y32/Y33/Y34  
Y32/Y33/Y34  
Y34 ONLY  
69  
267  
6
213  
426  
638  
64  
247  
2
D5  
69  
69  
533  
800  
12  
17  
64  
64  
495  
744  
2
D8  
1.  
Output Capacity at Full Fire.  
Modulating Gas Heat available on CV models only.  
2.  
12  
Johnson Controls Unitary Products  
     
246653-YTG-E-0108  
TABLE 7: MODULATING HEAT  
STAGES OF GAS CONTROL (% OF FULL HEAT OUTPUT)  
GAS HEAT OPTION  
AVAILABLE ON MODELS  
STEP  
1
INPUT  
OUTPUT  
55,466  
% OF TOTAL OUTPUT  
26%  
69,333  
2
106,666  
165,332  
202,665  
229,332  
266,666  
69,333  
85,333  
40%  
D3  
3
132,266  
162,132  
183,466  
213,333  
55,466  
62%  
(Turn down ration  
3.8 to 1)  
Y32, Y33, Y34  
4
76%  
5
86%  
6
100%  
13%  
1
2
106,666  
165,332  
202,665  
229,332  
266,666  
325,331  
362,664  
389,331  
426,664  
495,997  
533,330  
69,333  
85,333  
20%  
3
132,266  
162,132  
183,466  
213,333  
260,265  
290,132  
311,465  
341,331  
396,798  
426,664  
55,466  
31%  
4
38%  
5
43%  
D5  
6
50%  
(Turn down ration  
7.7 to 1)  
Y32, Y33, Y34  
7
61%  
8
68%  
9
73%  
10  
11  
12  
1
80%  
93%  
100%  
9%  
2
106,666  
165,332  
202,665  
229,332  
266,666  
325,331  
362,664  
389,331  
426,664  
495,997  
533,330  
586,663  
655,996  
693,329  
762,662  
799,995  
85,333  
13%  
3
132,266  
162,132  
183,466  
213,333  
260,265  
290,132  
311,465  
341,331  
396,798  
426,664  
469,330  
524,797  
554,663  
610,130  
639,996  
21%  
4
25%  
5
29%  
6
33%  
7
41%  
8
45%  
D8  
(Turn down ration  
11.5 to 1)  
Y34 Only  
9
49%  
10  
11  
12  
13  
14  
15  
16  
17  
53%  
62%  
67%  
73%  
82%  
87%  
95%  
100%  
TABLE 8: ELECTRIC HEATING CAPACITIES  
2
MBH AND KW PER STAGE  
ELECTRIC  
NOMINAL  
KW  
NOMINAL  
MBH  
AVAILABLE ON MODELS  
HEAT OPTION  
RATED VOLTAGE  
STAGE 1  
STAGE 2  
1
KW  
MBH  
137  
137  
246  
KW  
MBH  
0
3
4
E4  
E8  
E1  
Y32, Y33, Y34  
Y32, Y33, Y34  
240 /480 /575  
40  
80  
137  
273  
369  
40  
40  
72  
0
2
3
240 /480 /575  
40  
36  
136  
123  
3
Y32, Y33, Y34 (460 & 575 volt only)  
480 /575  
108  
1.  
2.  
3.  
4.  
Supply air fan motor heat not included.  
Heating capacity is only staged on CV models. VAV models use only one stage at full capacity.  
For 208 volts, multiply kW and MBH values by .751. For 230 volts, multiply kW and MBH values by .918  
For 460 volts, multiply kW and MBH values by .918.  
Johnson Controls Unitary Products  
13  
   
246653-YTG-E-0108  
1
HOT WATER HEATING  
The YORK Millennium Rooftop units (30 - 40 Ton sizes) can  
be furnished with a YORK hot water coil as the source of heat  
(Bottom Supply Only). A one or two row coil will be factory  
installed in the heating section downstream of the supply air  
fan and just above the supply air opening in the bottom of the  
unit.  
DO NOT use tin based solder. Brazing with tin  
based solder could cause equipment damage or  
possible injury to OCCUPANTS of the structure  
that is being conditioned.  
TABLE 11: HOT WATER COIL (1 ROW, 25 & 30  
The hot water control valve will not be provided. The installer  
will need to field supply a water valve. The installer must also  
connect the hot water piping, and valve wiring at the job site  
for the hot water heat section to be operational.  
1
TON)  
CAPACITY (MBH) AT ENTERING WATER  
TEMPERATURE  
GPM  
10  
CFM  
140 °F  
91.4  
160 °F  
180 °F  
139.3  
155.8  
168.8  
179.6  
192.9  
156  
200 °F  
163.6  
182.9  
198.4  
211.2  
226.9  
182.7  
207.7  
228.2  
245.6  
267.8  
190.1  
217.5  
240.2  
259.7  
284.8  
194.1  
222.8  
246.8  
267.5  
294.1  
For all hot water coils the entering water temperature should  
not exceed 200°F.  
6000  
8000  
115.3  
128.8  
139.5  
148.4  
159.2  
129.4  
147  
102  
10000  
12000  
15000  
6000  
110.4  
117.3  
125.9  
103  
PHYSICAL DATA HOT WATER COIL - 1 ROW  
Coil Casing . . . . . . . . . . . . . . . . . . . . Galvanized Steel  
Coil Construction. . . . . . . . . . . . . . . . Al Fin / Cu. Tube  
Rows Deep . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
Fin Thickness . . . . . . . . . . . . . . . . . . . . . . . . . . . .006”  
Tube Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .016”  
Tubes / Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Fins Per Inch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
Tubes High . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.50”  
Tube Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65”  
8000  
116.8  
128.2  
137.8  
150  
177.2  
194.7  
209.5  
228.2  
162.5  
185.8  
205.1  
221.8  
243  
20  
30  
10000  
12000  
15000  
6000  
161.3  
173.6  
189  
107.6  
122.8  
135.5  
146.4  
160.3  
110.1  
126.1  
139.6  
151.2  
166.1  
135  
8000  
154.3  
170.3  
184  
10000  
12000  
15000  
6000  
201.6  
138  
166  
8000  
158.2  
175.2  
189.8  
208.6  
190.5  
210.9  
228.5  
251.3  
40  
10000  
12000  
15000  
Face Area . . . . . . . . . . . . . . . . . . . . . . . . . . . .10.16ft.2  
Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71lbs.  
Operating Weight . . . . . . . . . . . . . . . . . . . . . . . .83lbs.  
1.  
Based on 60°F entering air temperature, 2.00” maximum pres-  
sure drop across the hot water coil.  
TABLE 9: WATER PRESSURE DROP (1 ROW, 25 &  
30 TON)  
PIPING CONNECTIONS  
GPM  
10  
20  
30  
40  
WATER PRESSURE DROP  
0.9  
3.0  
6.0  
10.0  
The hot water piping must enter the unit through the floor of  
the heat section compartment. The access doors to the com-  
partment are gasketed so the compartment can be sealed.  
However, as added protection for water leakage into the  
space, the piping access holes should be sealed with a heat  
resistant mastic (see the following illustration for approximate  
location of the compartment and piping connections.  
TABLE 10: STATIC RESISTANCE HOT WATER COIL  
(25 & 30 TON)  
CFM  
6000  
0.07  
0.14  
8000  
0.11  
0.23  
10000  
0.16  
15000  
0.32  
AIR PRESSURE DROP 1 ROW  
AIR PRESSURE DROP 2 ROW  
0.33  
0.65  
NOTE: Water pressure drop numbers are based on 60°F  
entering air temperature, 2.00” maximum air pres-  
sure drop across the hot water coil(s). ARI certified  
ratings at covering other conditions are available  
upon request. Hot water coils are approved for use  
with glycol (rates available upon request).  
1. Hot water, steam or electric heat is not available for  
front or rear supply.  
14  
Johnson Controls Unitary Products  
           
246653-YTG-E-0108  
1
TABLE 13: HOT WATER COIL (1 ROW 40 TON)  
(1 OR 2 ROW)  
CAPACITY (MBH) AT ENTERING WATER  
TEMPERATURE  
GPM  
CFM  
CONDENSING  
SECTION  
HOT WATER  
COIL  
140 °F  
102  
160 °F  
128.8  
144.1  
155.9  
165.4  
173.3  
147  
180 °F  
155.8  
174.4  
188.8  
200.4  
210.1  
177.2  
202.3  
222.4  
239  
200 °F  
182.9  
205.1  
222.1  
235.8  
247.3  
207.7  
237.2  
260.8  
280.5  
297.3  
217.5  
250.3  
276.9  
299.3  
318.6  
222.8  
257.5  
285.8  
309.7  
330.6  
8000  
11000  
14000  
17000  
20000  
8000  
26"  
114  
INLET (2")  
OUTLET (2")  
8.38"  
10  
123.2  
130.6  
136.8  
116.8  
133.2  
146.2  
157  
OUTSIDE OF  
BASE RAIL  
15.8"  
11.88"  
2.25"  
2.55"  
88.75"  
11000  
14000  
17000  
20000  
8000  
167.7  
184.2  
197.9  
209.6  
154.3  
177.4  
196.1  
211.8  
225.3  
158.2  
182.7  
202.6  
219.5  
234.2  
HEAT SECTION  
COMPARTMENT  
C
L
20  
30  
166.2  
122.8  
141.2  
155.9  
168.3  
179.1  
126.1  
145.6  
161.4  
174.7  
186.3  
253.2  
185.8  
213.8  
236.4  
255.4  
271.8  
190.5  
220  
FIGURE 1 - HOT WATER PIPING CROSS-SEC-  
TION  
11000  
14000  
17000  
20000  
8000  
TABLE 12: STATIC RESISTANCE HOT WATER COIL  
(1 ROW, 40 TON)  
11000  
14000  
17000  
20000  
CFM  
8000  
0.11  
0.23  
11000  
0.19  
14000  
0.29  
20000  
0.52  
40  
244.1  
264.5  
282.3  
AIR PRESSURE DROP 1 ROW  
AIR PRESSURE DROP 2 ROW  
0.39  
0.58  
1.06  
1.  
Based on 60°F entering air temperature, 2.00” maximum pres-  
sure drop across the hot water coil.  
Johnson Controls Unitary Products  
15  
     
246653-YTG-E-0108  
2 3 0 .0  
2 2 0 .0  
2 1 0 .0  
2 0 0 .0  
1 9 0 .0  
1 8 0 .0  
1 7 0 .0  
1 6 0 .0  
1 5 0 .0  
1 4 0 .0  
1 3 0 .0  
1 2 0 .0  
1 1 0 .0  
1 0 0 .0  
9 0 .0  
1 4 0 °F  
1 6 0 °F  
1 8 0 °F  
2 0 0 °F  
8 0 .0  
6 0 0 0  
7 0 0 0  
8 0 0 0  
9 0 0 0  
1 0 0 0 0  
1 1 0 0 0  
1 2 0 0 0  
1 3 0 0 0  
1 4 0 0 0  
1 5 0 0 0  
F L O W R A T E (C F M )  
FIGURE 2 - HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 10 GPM  
270.0  
260.0  
250.0  
240.0  
230.0  
220.0  
210.0  
200.0  
190.0  
180.0  
170.0  
160.0  
150.0  
140.0  
130.0  
120.0  
110.0  
100.0  
90.0  
140 °F  
160 °F  
180 °F  
200 °F  
6000  
7000  
8000  
9000  
10000  
11000  
12000  
13000  
14000  
15000  
FLO W RATE (CFM )  
FIGURE 3 - HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 20 GPM  
16  
Johnson Controls Unitary Products  
   
246653-YTG-E-0108  
2 9 0 .0  
2 8 0 .0  
2 7 0 .0  
2 6 0 .0  
2 5 0 .0  
2 4 0 .0  
2 3 0 .0  
2 2 0 .0  
2 1 0 .0  
2 0 0 .0  
1 9 0 .0  
1 8 0 .0  
1 7 0 .0  
1 6 0 .0  
1 5 0 .0  
1 4 0 .0  
1 3 0 .0  
1 2 0 .0  
1 1 0 .0  
1 0 0 .0  
1 4 0 °F  
1 6 0 °F  
1 8 0 °F  
2 0 0 °F  
6 0 0 0  
7 0 0 0  
8 0 0 0  
9 0 0 0  
1 0 0 0 0  
1 1 0 0 0  
1 2 0 0 0  
1 3 0 0 0  
1 4 0 0 0  
1 5 0 0 0  
F L O W R A T E (C F M )  
FIGURE 4 - HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 30 GPM  
300.0  
290.0  
280.0  
270.0  
260.0  
250.0  
240.0  
230.0  
220.0  
210.0  
200.0  
190.0  
180.0  
170.0  
160.0  
150.0  
140.0  
130.0  
120.0  
110.0  
100.0  
140 °F  
160 °F  
180 °F  
200 °F  
6000  
7000  
8000  
9000  
10000  
11000  
12000  
13000  
14000  
15000  
F L O W R AT E (C F M )  
FIGURE 5 - HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 40 GPM  
Johnson Controls Unitary Products  
17  
   
246653-YTG-E-0108  
250.0  
240.0  
230.0  
220.0  
210.0  
200.0  
190.0  
180.0  
170.0  
160.0  
150.0  
140.0  
130.0  
120.0  
110.0  
100.0  
90.0  
140 °F  
160 °F  
180 °F  
200 °F  
8000  
9000  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
19000  
20000  
FLO W R AT E (C FM )  
FIGURE 6 - HOT WATER COIL - 40 TON, 1 ROW, AT 10 GPM  
300.0  
290.0  
280.0  
270.0  
260.0  
250.0  
240.0  
230.0  
220.0  
210.0  
200.0  
190.0  
180.0  
170.0  
160.0  
150.0  
140.0  
130.0  
120.0  
110.0  
100.0  
140 °F  
160 °F  
180 °F  
200 °F  
8000  
9000  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
19000  
20000  
FLO W RATE (CFM )  
FIGURE 7 - HOT WATER COIL - 40 TON, 1 ROW, AT 20 GPM  
18  
Johnson Controls Unitary Products  
   
246653-YTG-E-0108  
320.0  
310.0  
300.0  
290.0  
280.0  
270.0  
260.0  
250.0  
240.0  
230.0  
220.0  
210.0  
200.0  
190.0  
180.0  
170.0  
160.0  
150.0  
140.0  
130.0  
120.0  
110.0  
140 °F  
160 °F  
180 °F  
200 °F  
8000  
9000  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
19000  
20000  
FLOW RATE (CFM )  
FIGURE 8 - HOT WATER COIL - 40 TON, 1 ROW, AT 30 GPM  
3 4 0 .0  
3 3 0 .0  
3 2 0 .0  
3 1 0 .0  
3 0 0 .0  
2 9 0 .0  
2 8 0 .0  
2 7 0 .0  
2 6 0 .0  
2 5 0 .0  
2 4 0 .0  
2 3 0 .0  
2 2 0 .0  
2 1 0 .0  
2 0 0 .0  
1 9 0 .0  
1 8 0 .0  
1 7 0 .0  
1 6 0 .0  
1 5 0 .0  
1 4 0 .0  
1 3 0 .0  
1 2 0 .0  
1 4 0 °F  
1 6 0 °F  
1 8 0 °F  
2 0 0 °F  
8 0 0 0  
9 0 0 0  
1 0 0 0 0  
1 1 0 0 0  
1 2 0 0 0  
1 3 0 0 0  
1 4 0 0 0  
1 5 0 0 0  
1 6 0 0 0  
1 7 0 0 0  
1 8 0 0 0  
1 9 0 0 0  
2 0 0 0 0  
F L O W R A T E (C F M )  
FIGURE 9 - HOT WATER COIL - 40 TON, 1 ROW, AT 40 GPM  
Johnson Controls Unitary Products  
19  
   
246653-YTG-E-0108  
PHYSICAL DATA HOT WATER COIL - 2 ROW  
TABLE 16: HOT WATER COIL (2 ROW, 25 & 30  
1
TON) (CONTINUED)  
Coil Casing . . . . . . . . . . . . . . . . . . . . Galvanized Steel  
Coil Construction. . . . . . . . . . . . . . . . Al Fin / Cu. Tube  
Rows Deep . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Fin Thickness . . . . . . . . . . . . . . . . . . . . . . . . . . . .006”  
Tube Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .016”  
Tubes / Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Fins Per Inch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
Tubes High . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.50”  
Tube Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65”  
CAPACITY (MBH) AT ENTERING WATER TEMPERATURE  
GPM  
60  
CFM  
140 °F  
206.1  
243.6  
275.3  
302.9  
338.4  
210.5  
249.8  
283.3  
312.7  
351.0  
160 °F  
258.7  
305.9  
345.9  
380.7  
425.7  
263.9  
313.3  
355.6  
392.7  
440.9  
180 °F  
311.4  
368.4  
416.8  
458.9  
513.4  
317.4  
377.1  
428.2  
473.0  
531.3  
200 °F  
364.2  
431.1  
488.0  
537.6  
601.7  
371.1  
441.1  
501.0  
553.6  
622.1  
6000  
8000  
10000  
12000  
15000  
6000  
8000  
80  
10000  
12000  
15000  
1.  
Based on 60°F entering air temperature, 2.00” maximum pres-  
sure drop across the hot water coil.  
Face Area . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.16 ft.2  
Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90 lbs  
1
TABLE 17: HOT WATER COIL (2 ROWS, 40 TON)  
Operating Weight . . . . . . . . . . . . . . . . . . . . . . .110 lbs  
CAPACITY (MBH) AT ENTERING WATER  
TEMPERATURE  
GPM  
CFM  
140 °F  
203.8  
233.9  
257.0  
275.5  
290.9  
232.2  
273.3  
306.3  
333.9  
357.5  
243.6  
289.5  
327.2  
359.2  
386.9  
249.8  
298.5  
338.9  
373.4  
403.6  
160 °F  
180 °F  
311.1  
358.1  
394.2  
423.3  
447.4  
352.2  
415.3  
466.3  
508.9  
545.4  
368.4  
438.5  
496.3  
545.3  
587.9  
377.1  
451.2  
512.8  
565.6  
611.8  
200 °F  
365.5  
421.0  
463.8  
498.3  
526.9  
412.7  
487.0  
547.1  
597.3  
640.5  
431.1  
513.6  
581.5  
639.2  
689.4  
441.1  
528.1  
600.5  
662.5  
716.8  
TABLE 14: WATER PRESSURE DROP (2 ROW, 25 &  
30 TON)  
8000  
11000  
14000  
17000  
20000  
8000  
257.2  
295.7  
325.3  
349.0  
368.7  
292.0  
344.1  
386.0  
421.1  
451.1  
305.9  
363.9  
411.5  
452.0  
487.1  
313.3  
374.7  
425.7  
469.3  
507.5  
20  
GPM  
20  
40  
60  
80  
WATER  
PRESSURE  
DROP  
0.9  
3.0  
6.0  
10.0  
11000  
14000  
17000  
20000  
8000  
TABLE 15: STATIC RESISTANCE HOT WATER COIL  
(25 & 30 TON)  
40  
60  
CFM  
6000  
8000  
10000  
15000  
AIR PRESSURE DROP  
1 ROW  
11000  
14000  
17000  
20000  
8000  
0.07  
0.11  
0.16  
0.32  
AIR PRESSURE DROP  
2 ROW  
0.14  
0.23  
0.33  
0.65  
NOTE: Water pressure drop numbers are based on 60°F  
entering air temperature, 2.00” maximum air pres-  
sure drop across the hot water coil(s). ARI certified  
ratings at covering other conditions are available  
upon request. Hot water coils are approved for use  
with glycol (rates available upon request.)  
11000  
14000  
17000  
20000  
80  
1.  
Based on 60°F entering air temperature, 2.00” maximum air  
pressure drop across the hot water coil.  
ARI certified ratings at other conditions available upon request.  
Hot water coils are approved for use with glycol (ratings avail-  
able upon request).  
TABLE 16: HOT WATER COIL (2 ROW, 25 & 30  
1
TON)  
TABLE 18: STATIC RESISTANCE HOT WATER  
COIL (40 TON)  
CAPACITY (MBH) AT ENTERING WATER TEMPERATURE  
GPM  
20  
CFM  
140 °F  
177.5  
203.8  
224.8  
242.2  
263.6  
198.1  
232.2  
260.7  
285.0  
316.0  
160 °F  
223.8  
257.2  
284.1  
306.4  
333.8  
248.9  
292.0  
328.1  
359.0  
398.4  
180 °F  
270.4  
311.1  
343.9  
371.1  
404.6  
300.0  
352.2  
395.9  
433.4  
481.3  
200 °F  
317.3  
365.5  
404.2  
436.4  
476.1  
351.3  
412.7  
464.1  
508.3  
564.8  
6000  
8000  
CFM  
8000  
0.11  
0.23  
11000  
0.19  
14000  
0.29  
20000  
0.52  
AIR PRESSURE DROP 1 ROW  
AIR PRESSURE DROP 2 ROW  
10000  
12000  
15000  
6000  
0.39  
0.58  
1.06  
TABLE 19: WATER PRESSURE DROP (2 ROW, 40  
TON)  
8000  
40  
10000  
12000  
15000  
GPM  
20  
40  
60  
80  
WATER PRESSURE DROP  
0.9  
3.0  
6.0  
10.0  
20  
Johnson Controls Unitary Products  
             
246653-YTG-E-0108  
480.0  
460.0  
440.0  
420.0  
400.0  
380.0  
360.0  
340.0  
320.0  
300.0  
280.0  
260.0  
240.0  
220.0  
200.0  
180.0  
160.0  
140 °F  
160 °F  
180 °F  
200 °F  
6000  
7000  
8000  
9000  
10000  
11000  
12000  
13000  
14000  
15000  
F LO W R AT E (C F M )  
FIGURE 10 - HOT WATER COIL - 25 & 30 TON, 2 ROW, AT 20 GPM  
580.0  
560.0  
540.0  
520.0  
500.0  
480.0  
460.0  
440.0  
420.0  
400.0  
380.0  
360.0  
340.0  
320.0  
300.0  
280.0  
260.0  
240.0  
220.0  
200.0  
180.0  
140 °F  
160 °F  
180 °F  
200 °F  
6000  
7000  
8000  
9000  
10000  
11000  
12000  
13000  
14000  
15000  
F L O W R AT E (C F M )  
FIGURE 11 - HOT WATER COIL - 25 & 30 TON, 2 ROW, AT 40 GPM  
Johnson Controls Unitary Products  
21  
   
246653-YTG-E-0108  
610.0  
590.0  
570.0  
550.0  
530.0  
510.0  
490.0  
470.0  
450.0  
430.0  
410.0  
390.0  
370.0  
350.0  
330.0  
310.0  
290.0  
270.0  
250.0  
230.0  
210.0  
140 °F  
160 °F  
180 °F  
200 °F  
190.0  
6000  
7000  
8000  
9000  
10000  
11000  
12000  
13000  
14000  
15000  
FLO W RATE (CFM )  
FIGURE 12 - HOT WATER COIL - 25 & 30 TON, 2 ROW, AT 60 GPM  
640.0  
620.0  
600.0  
580.0  
560.0  
540.0  
520.0  
500.0  
480.0  
460.0  
440.0  
420.0  
400.0  
380.0  
360.0  
340.0  
320.0  
300.0  
280.0  
260.0  
240.0  
220.0  
200.0  
140 °F  
160 °F  
180 °F  
200 °F  
6000  
7000  
8000  
9000  
10000  
11000  
12000  
13000  
14000  
15000  
FLO W R AT E (C FM )  
FIGURE 13 - HOT WATER COIL - 25 & 30 TON, 2 ROW, AT 80 GPM  
22  
Johnson Controls Unitary Products  
   
246653-YTG-E-0108  
530.0  
510.0  
490.0  
470.0  
450.0  
430.0  
410.0  
390.0  
370.0  
350.0  
330.0  
310.0  
290.0  
270.0  
250.0  
230.0  
210.0  
190.0  
140 °F  
160 °F  
180 °F  
200 °F  
8000  
9000  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
19000  
20000  
FLO W R ATE (C FM )  
FIGURE 14 - HOT WATER COIL - 40 TON, 2 ROW, AT 20 GPM  
650.0  
630.0  
610.0  
590.0  
570.0  
550.0  
530.0  
510.0  
490.0  
470.0  
450.0  
430.0  
410.0  
390.0  
370.0  
350.0  
330.0  
310.0  
290.0  
270.0  
250.0  
230.0  
210.0  
140 °F  
160 °F  
180 °F  
200 °F  
8000  
9000  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
19000  
20000  
FLO W R AT E (C F M )  
FIGURE 15 - HOT WATER COIL - 40 TON, 2 ROW, AT 40 GPM  
Johnson Controls Unitary Products  
23  
   
246653-YTG-E-0108  
700.0  
680.0  
660.0  
640.0  
620.0  
600.0  
580.0  
560.0  
540.0  
520.0  
500.0  
480.0  
460.0  
440.0  
420.0  
400.0  
380.0  
360.0  
340.0  
320.0  
300.0  
280.0  
260.0  
240.0  
220.0  
140 °F  
160 °F  
180 °F  
200 °F  
8000  
9000  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
19000  
20000  
FLO W R AT E (C FM )  
FIGURE 16 - HOT WATER COIL - 40 TON, 2 ROW, AT 60 GPM  
730.0  
710.0  
690.0  
670.0  
650.0  
630.0  
610.0  
590.0  
570.0  
550.0  
530.0  
510.0  
490.0  
470.0  
450.0  
430.0  
410.0  
390.0  
370.0  
350.0  
330.0  
310.0  
290.0  
270.0  
250.0  
230.0  
140 °F  
160 °F  
180 °F  
200 °F  
8000  
9000  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
19000  
20000  
F L O W R AT E (C F M )  
FIGURE 17 - HOT WATER COIL - 40 TON, 2 ROW, AT 80 GPM  
24  
Johnson Controls Unitary Products  
   
246653-YTG-E-0108  
STEAM HEATING  
TABLE 22: STEAM COIL (1 ROW, 40 TON)  
CAPACITY (MBH) AT STEAM PRESSURE (PSI)  
The YORK Millennium units (25, 30, and 40 ton sizes) can be  
manufactured with a steam heat coil (Bottom Supply only).  
YORK's one row steam coil is installed in the heating section  
just downstream of the supply air fan and just above the sup-  
ply air opening in the bottom of the unit.  
CFM  
2
6
10  
15  
8000  
11000  
14000  
17000  
20000  
221.1  
252.9  
278.2  
299.4  
317.6  
236.9  
271.0  
298.0  
320.7  
340.2  
250.4  
286.4  
315.0  
339.0  
359.6  
265.0  
303.1  
333.4  
358.8  
380.6  
The steam control valve will not be provided. The installer  
will need to field supply a steam control valve. Connect the  
steam piping and valve power wiring at the job site for the  
steam heat section to be operational.  
TABLE 23: STATIC RESISTANCE STEAM COIL  
(1 ROW, 40 TON)  
There are no provisions in the coil or control sequence to pre-  
vent freezing of condensate. The control valve, piping and  
field installed wiring connections are particularly vulnerable  
because they are installed in the vestibule outside of the con-  
ditioned air stream.  
CFM  
8000  
11000  
14000  
17000  
20000  
AIR PRESSURE DROP  
0.18  
0.31  
0.48  
0.67  
0.88  
PIPING CONNECTIONS  
The steam piping must enter the unit through the floor of the  
heat section compartment. The access doors to the compart-  
ment are gasketed to the compartment can be sealed. How-  
ever, as added protection for condensate leakage into the  
space, the piping access holes should be sealed with a heat  
resistant mastic. The following figure illustrates the approxi-  
mate location of the compartment and piping connections.  
All piping, control valves, and wiring that is field installed must  
conform to all local and national codes  
Condensate can freeze on the control valve and piping if they  
are not properly insulated.  
PHYSICAL DATA STEAM COIL - 1 ROW  
Coil Casing . . . . . . . . . . . . . . . . . . . . Galvanized Steel  
Coil Construction . . . . . . . . . . . . . . . Al Fin / Cu. Tube  
Rows Deep. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
Fin Thickness . . . . . . . . . . . . . . . . . . . . . . . . . . . ..010”  
Tube Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..035”  
Tubes / Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2  
Fins Per Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6  
Tubes High . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21”  
Tube Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65”  
T
O
P
V
I
E
W
C
O
N
D
E
N
S
I
N
G
S
T
E
O
A
M
S
E
C
T
I
O
N
C
I
L
2
6
"
O
U
T
L
E
T
(
1
1
/
2
"
)
O
U
T
S
I
D
E
O
F
1
5
.
8
"
I
N
L
E
T
(
2
"
)
B
A
S
E
R
A
I
L
8
"
8
.
3
8
"
Face Area. . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.48 ft.2  
Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 lbs.  
2
.
5
5
"
9
"
8
8
.
7
5
"
H
E
A
T
S
E
C
T
I
E
O
N
*Hot water, steam coil or electric heat not available for front or  
rear supply.  
C
O
M
P
A
R
T
M
N
T
C
L
1
FIGURE 18 - STEAM PIPING CROSS SECTION  
TABLE 20: STEAM COIL (1 ROW, 25 & 30 TON)  
CAPACITY (MBH) AT STEAM PRESSURE (PSI)  
CFM  
2
6
10  
15  
6000  
8000  
194.1  
221.1  
243.2  
261.9  
285.6  
207.9  
236.9  
260.5  
280.6  
306.0  
219.8  
250.4  
275.4  
296.6  
323.5  
232.6  
265.0  
291.4  
313.9  
342.4  
10000  
12000  
15000  
DO NOT use tin based solder. Brazing with tin  
based solder could cause equipment damage or  
possible injury to OCCUPANTS of the structure that  
is being conditioned.  
1.  
Based on 60°F entering air temperature, 2.00” maximum air  
pressure drop across the coil.  
TABLE 21: STATIC RESISTANCE STEAM COIL  
(1 ROW, 25 & 30 TON)  
CFM  
6000  
8000  
10000  
12000  
15000  
AIR PRESSURE DROP  
0.11  
0.18  
0.26  
0.36  
0.54  
Johnson Controls Unitary Products  
25  
               
246653-YTG-E-0108  
350  
340  
330  
320  
310  
300  
290  
280  
270  
260  
250  
240  
230  
220  
210  
200  
190  
180  
2 psi  
6 psi  
10 psi  
15 psi  
6000  
7000  
8000  
9000  
10000  
11000  
12000  
13000  
14000  
15000  
FLO W R ATE (C FM )  
FIGURE 19 - STEAM COIL - 25 & 30 TON, 1 ROW  
390  
380  
370  
360  
350  
340  
330  
320  
310  
300  
290  
280  
270  
260  
250  
240  
230  
220  
210  
2 psi  
6 psi  
10 psi  
15 psi  
8000  
9000  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
19000  
20000  
FLOW RATE (CFM )  
FIGURE 20 - STEAM COIL - 40 TON, 1 ROW  
26  
Johnson Controls Unitary Products  
   
246653-YTG-E-0108  
TABLE 24: EXHAUST FAN DRIVE DATA  
MOTOR  
MOTOR PULLEY  
BLOWER PULLEY  
BELTS  
BLOWER  
RPM  
RANGE  
MOTOR EFF  
(STD.  
MOTOR)  
MOTOR  
EFF (HI  
EFF OPT)  
MODEL  
FRAME  
SIZE  
PITCH DIA  
BORE  
PITCH DIA  
BORE  
HP  
DESIGNATION  
QTY  
(INCHES)  
(INCHES)  
(INCHES)  
(INCHES)  
758  
852  
976  
852  
976  
1069  
852  
976  
1069  
5
213T  
215T  
215T  
213T  
215T  
254T  
184T  
215T  
254T  
87.5  
88.5  
89.5  
84  
89.5  
91.7  
91  
4.9  
5.5  
6.3  
5.5  
6.3  
6.9  
5.5  
6.3  
6.9  
1-3/8  
1-3/8  
1-5/8  
1-3/8  
1-3/8  
1-3/8  
1-3/8  
1-3/8  
1-3/8  
11.3  
11.3  
11.3  
11.3  
11.3  
11.3  
11.3  
11.3  
11.3  
2-3/16  
2-3/16  
BX63  
BX63  
BX63  
B65  
2
2
2
2
2
2
2
2
2
25 Ton  
30 Ton  
40 Ton  
7.5  
10  
7.5  
10  
15  
7.5  
10  
15  
2-3/16  
86.5  
89.5  
89.5  
86.5  
89.5  
89.5  
1-11/16  
1-11/16  
1-11/16  
1-11/16  
1-11/16  
1-11/16  
86.5  
85.7  
84  
B65  
B65  
B65  
86.5  
85.7  
B65  
B65  
1
TABLE 25: SUPPLY FAN MOTOR AND DRIVE DATA  
MOTOR  
MOTOR PULLEY  
BLOWER PULLEY  
BELTS  
BLOWER  
RPM  
RANGE  
MOTOR  
MOTOR  
EFFICIENCY  
(STD. MOTOR)  
MODEL  
25 Ton  
30 Ton  
FRAME  
SIZE  
EFFICIENCY  
(ULTRA HI  
EFF OPT)  
PITCH DIA  
(INCHES)  
BORE  
(INCHES)  
PITCH DIA  
(INCHES)  
BORE  
(INCHES)  
DESIGNA  
TION  
HP  
QTY  
567  
692  
793  
894  
617  
743  
856  
907  
617  
652  
728  
780  
7.5  
10  
15  
20  
10  
15  
20  
25  
10  
15  
20  
25  
213T  
215T  
254T  
256T  
215T  
254T  
256T  
284T  
215T  
254T  
256T  
284T  
88.5  
89.5  
91  
91.7  
91  
4.5  
5.5  
6.3  
7.1  
4.9  
5.9  
6.7  
7.1  
4.9  
5.1  
5.7  
6.1  
1-3/8  
1-3/8  
1-5/8  
1-5/8  
1-3/8  
1-5/8  
1-5/8  
1-7/8  
1-3/8  
1-5/8  
1-5/8  
1-7/8  
13.9  
13.9  
13.9  
13.9  
13.9  
13.9  
13.7  
13.7  
13.9  
13.7  
13.7  
13.7  
2-3/16  
2-3/16  
2-3/16  
2-3/16  
2-3/16  
2-3/16  
2-3/16  
2-3/16  
2-7/16  
2-7/16  
2-7/16  
2-7/16  
BX56  
BX56  
2
2
2
2
2
2
2
2
2
2
2
2
91.7  
93  
BX56  
91  
BX56  
89.5  
91  
91  
BX56  
91.7  
93  
BX56  
91  
5VX610  
5VX610  
BX67  
91.7  
89.5  
91  
93.6  
91  
91.7  
93  
5VX710  
5VX710  
5VX710  
40 Ton  
91  
91.7  
93.6  
1.  
kW = (BHP X 0.746) / Motor Eff.  
MBH = kW X 3.414  
MBH = (BHP X 2.546) / Motor Eff.  
NOTES: 1) Class I Blowers are limited to 15 HP motors on 25 and 30 Ton units.  
2) Class I Blowers are limited to 20 HP motors on the 40 Ton units.  
3) Class II Blowers are not HP limited, can use 25 HP.  
Johnson Controls Unitary Products  
27  
 
246653-YTG-E-0108  
SUPPLY AIR DRIVE ADJUSTMENT  
At unit start-up, the measured CFM may be higher or lower  
than the specified CFM shown in Figures 22, 23, and 24. To  
achieve the specified CFM, the speed of the drive may have  
to be decreased or increased by changing the pitch diameter  
(PD) of the motor sheave as outlined below:  
Even small changes in blower speed can result in  
substantial changes in static pressure and bhp.  
Bhp or amp draw of the blower motor will increase  
(see table) by the cube ratio of the blower speed.  
Static pressure will increase by the square ratio of  
the blower speed. Tables 26, 27 and 28 are for  
reference only. All blower speed changes must be  
made by qualified personnel with strict adherence  
to the fan laws.  
Example:  
Failure to properly adjust the total system air quan-  
tity can result in extensive blower damage.  
A 30-ton unit was selected to deliver 12,000 CFM with a 20  
HP motor and a 856 RPM drive, but the unit is only delivering  
11,000 CFM per Figure 23.  
Use the equation to determine the required PD for the new  
motor sheave (12,000 CFM / 11,000 CFM) x 6.7” = 7.31”.  
Before making any blower speed changes review  
the installation for any installation errors, leaks or  
undesirable systems effects that can result in loss  
of air flow.  
Use the 30-ton table to select a Browning 2B5V74 which will  
increase the speed of the unit's drive and its supply air CFM  
109%.  
New drive speed = 1.091 x 856 = 933 RPM  
New supply air = 1.091 x 11,000 = 12,000 CFM  
Re-use the existing belts and blower sheave.  
New motor BHP = (speed increase)3 x estimated motor  
BHP at original start-up with 11,000 CFM and 856 RPM =  
(1.091)3 x 11.0 BHP = 1.2986 x 11.0 BHP = 14.3 BHP  
New motor amps = (speed increase)3 x measured motor  
amps at original start-up with 11,000 CFM and 856 RPM.  
28  
Johnson Controls Unitary Products  
 
246653-YTG-E-0108  
TABLE 26: 25 TON DRIVE ADJUSTMENT  
7.5 HP MOTOR & 567 RPM DRIVE  
10 HP MOTOR & 692 RPM DRIVE  
15 HP MOTOR & 793 RPM DRIVE  
20 HP MOTOR & 894 RPM DRIVE  
%RPM  
& CFM  
REQD  
PD  
BROWNING  
2B5V_ _  
%RPM  
& CFM  
REQD  
PD  
BROWNING  
2B5V_ _  
%RPM  
& CFM  
REQD  
PD  
BROWNING  
2B5V_ _  
%RPM  
& CFM  
REQD  
PD  
BROWNING  
2B5V_ _  
-
-
-
-
82  
86  
89  
93  
96  
4.5  
4.7  
4.9  
5.1  
5.3  
42  
44  
46  
48  
50  
84  
87  
90  
94  
97  
5.3  
5.5  
5.7  
5.9  
6.1  
50  
52  
54  
56  
58  
86  
89  
91  
94  
97  
6.1  
6.3  
6.5  
6.7  
6.9  
58  
60  
62  
64  
66  
-
-
100  
104  
109  
(Std.)4.5  
4.7  
42  
44  
46  
4.9  
(Std.)  
5.5  
(Std)  
6.3  
(Std.)  
7.1  
113  
5.1  
48  
100  
52  
100  
60  
100  
68  
118  
5.3  
5.5  
5.7  
-
50  
52  
54  
-
104  
107  
111  
115  
118  
122  
5.7  
5.9  
6.1  
6.3  
6.5  
6.7  
54  
56  
58  
60  
62  
64  
103  
106  
110  
113  
116  
122  
6.5  
6.7  
6.9  
7.1  
7.3  
7.7  
62  
64  
66  
68  
70  
74  
103  
108  
117  
125  
-
7.3  
7.7  
8.3  
8.9  
-
70  
74  
80  
86  
-
122  
126  
-
-
-
-
-
-
-
-
-
-
TABLE 27: 30 TON DRIVE ADJUSTMENT  
10 HP MOTOR & 617 RPM DRIVE  
15 HP MOTOR & 743 RPM DRIVE  
20 HP MOTOR & 856 RPM DRIVE  
25 HP MOTOR & 907 RPM DRIVE  
%RPM  
& CFM  
REQD  
PD  
BROWNING  
2B5V_ _  
%RPM  
& CFM  
REQD  
PD  
BROWNING  
2B5V_ _  
%RPM  
& CFM  
REQD  
PD  
BROWNING  
2B5V_ _  
%RPM  
& CFM  
REQD  
PD  
BROWNING  
2B5V_ _  
91.8  
95.9  
4.5  
4.7  
42  
44  
86.4  
89.8  
5.1  
5.3  
48  
50  
82.1  
85.1  
5.5  
5.7  
54  
56  
86.3  
89.0  
6.1  
6.3  
60  
62  
(Std.)  
4.9  
100.0  
104.1  
108.2  
46  
48  
50  
93.2  
96.6  
5.5  
5.7  
52  
54  
56  
88.1  
91.0  
94.0  
5.9  
6.1  
6.3  
58  
60  
62  
91.8  
94.5  
97.3  
6.5  
6.7  
6.9  
64  
66  
68  
5.1  
(Std.)  
5.9  
5.3  
100.0  
(Std.)  
7.1  
112.2  
116.3  
5.5  
5.7  
52  
54  
103.4  
106.8  
6.1  
6.3  
58  
60  
97.0  
6.5  
64  
66  
100.0  
105.5  
70  
74  
(Std.)  
6.7  
100.0  
7.5  
120.4  
5.9  
56  
58  
-
110.2  
113.6  
116.9  
120.3  
123.7  
6.5  
6.7  
6.9  
7.1  
7.3  
62  
64  
66  
68  
70  
103.0  
106.0  
112.0  
120.9  
129.9  
6.9  
7.1  
7.5  
8.1  
8.7  
68  
70  
74  
80  
86  
113.7  
8.1  
80  
86  
-
124.5  
6.1  
121.9  
8.7  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
TABLE 28: 40 TON DRIVE ADJUSTMENT  
10 HP MOTOR & 617 RPM DRIVE  
15 HP MOTOR & 652 RPM DRIVE  
20 HP MOTOR & 728 RPM DRIVE  
25 HP MOTOR & 780 RPM DRIVE  
%RPM  
& CFM  
REQD  
PD  
BROWNING  
2B5V_ _  
% RPM  
& CFM  
REQD  
PD  
BROWNING  
2B5V_ _  
%RPM  
& CFM  
REQD  
PD  
BROWNING  
2B5V_ _  
%RPM  
& CFM  
REQD  
PD  
BROWNING  
2B5V_ _  
91.8  
95.9  
4.5  
4.7  
42  
44  
88.2  
92.1  
4.5  
4.7  
44  
46  
82.5  
86.0  
4.7  
4.9  
46  
48  
83.7  
86.9  
5.1  
5.3  
50  
52  
(Std.)  
4.9  
100.0  
46  
96.0  
4.9  
48  
89.5  
5.1  
50  
90.2  
5.5  
54  
(Std.)  
5.1  
104.1  
108.2  
112.2  
5.1  
5.3  
5.5  
48  
50  
52  
100.0  
103.9  
107.8  
50  
52  
54  
93.0  
96.5  
5.3  
5.5  
52  
54  
56  
93.4  
96.7  
5.7  
5.9  
56  
58  
60  
5.3  
(Std.)  
5.7  
(Std.)  
6.1  
5.5  
100.0  
100.0  
116.3  
5.7  
54  
-
111.7  
115.6  
119.5  
123.4  
127.4  
-
5.7  
5.9  
6.1  
6.3  
6.5  
-
56  
58  
60  
62  
64  
66  
103.5  
107.0  
110.5  
114.0  
117.5  
121.1  
5.9  
6.1  
6.3  
6.5  
6.7  
6.9  
58  
60  
62  
64  
66  
68  
103.3  
106.6  
109.8  
113.1  
116.4  
119.7  
6.3  
6.5  
6.7  
6.9  
7.1  
7.5  
62  
64  
66  
68  
70  
74  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTES: 1) Class I Blowers are limited to 15 HP motors on 25 and 30 Ton units.  
2) Class I Blowers are limited to 20 HP motors on the 40 Ton units.  
3) Class II Blowers are not HP limited, can use 25 HP.  
Johnson Controls Unitary Products  
29  
     
246653-YTG-E-0108  
TABLE 29: DRIVE ADJUSTMENT FOR POWER EXHAUST - 25 TON  
5 HP MOTOR & 759 RPM DRIVE  
7.5 HP MOTOR & 852 RPM DRIVE  
10 HP MOTOR & 975 RPM DRIVE  
%RPM  
& CFM  
REQD  
PD  
BROWNING  
2B5V_ _  
%RPM  
& CFM  
REQD  
PD  
BROWNING  
2B5V_ _  
%RPM  
& CFM  
BROWNING  
2B5V_ _  
REQD PD  
100  
(Std.) 4.9  
5.1  
46  
92  
5.1  
5.3  
48  
93  
5.9  
6.1  
56  
104  
48  
96  
50  
97  
58  
109  
5.3  
50  
100  
104  
108  
112  
(Std.) 5.5  
5.7  
52  
100  
103  
107  
110  
(Std.) 6.3  
6.5  
60  
113  
5.5  
52  
54  
62  
117  
5.7  
54  
5.9  
56  
6.7  
64  
122  
5.9  
56  
6.1  
58  
6.9  
66  
TABLE 30: DRIVE ADJUSTMENT FOR POWER EXHAUST - 30 & 40 TON  
7.5 HP MOTOR & 852 RPM DRIVE  
10 HP MOTOR & 976 RPM DRIVE  
15 HP MOTOR & 1069 RPM DRIVE  
% RPM  
& CFM  
REQ’D  
PD (IN)  
BROWNING  
2B5V_ _  
% RPM  
& CFM  
REQ’D  
PD (IN)  
BROWNING  
2B5V_ _  
% RPM  
& CFM  
REQ’D  
PD (IN)  
BROWNING  
2B5V_ _  
96.4  
5.3  
(Std.) 5.5  
5.7  
52  
93.7  
5.9  
6.1  
58  
94.2  
6.5  
6.7  
64  
100.0  
103.6  
107.3  
110.9  
114.5  
54  
96.8  
60  
97.1  
66  
56  
100.0  
103.2  
106.3  
109.5  
(Std.) 6.3  
6.5  
62  
100.0  
102.9  
108.7  
117.4  
(Std.) 6.9  
7.1  
68  
5.9  
58  
64  
70  
6.1  
60  
6.7  
66  
7.5  
74  
6.3  
62  
6.9  
68  
8.1  
80  
30  
Johnson Controls Unitary Products  
   
246653-YTG-E-0108  
TABLE 31: COOLING PERFORMANCE 25 TON  
TEMPERATURE OF AIR ON CONDENSER COIL  
2
AIR ON EVAPORATOR COIL  
75°F  
85°F  
2
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
TOTAL  
CAP.  
(MBH)  
TOTAL  
INPUT  
(KW)  
TOTAL  
TOTAL  
INPUT  
(KW)  
WB  
(°F)  
1
1
CFM  
7500  
CAP.  
(MBH)  
86 83 80 77 74 71 68  
86 83 80 77 74 71 68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
337.7  
310.2  
271.9  
243.9  
344.1  
316.1  
277.1  
248.7  
350.5  
321.9  
282.3  
253.4  
355.5  
326.5  
286.3  
257.1  
360.5  
331.1  
290.4  
260.8  
23.0  
21.6  
21.5  
20.8  
23.7  
22.2  
22.1  
21.4  
24.3  
22.8  
22.7  
21.9  
26.5  
24.9  
24.7  
23.9  
28.7  
26.9  
26.8  
25.9  
179 165 152 138 124  
-
-
326.9  
296.8  
269.6  
253.3  
331.9  
301.4  
273.7  
257.2  
336.8  
305.9  
277.9  
261.0  
341.2  
309.8  
281.4  
264.4  
345.5  
313.8  
285.0  
267.7  
24.5  
23.9  
23.5  
23.1  
25.2  
24.5  
24.1  
23.7  
25.8  
25.1  
24.7  
24.3  
27.7  
27.0  
26.6  
26.1  
29.7  
28.9  
28.4  
28.0  
175 161 147 133 119  
-
-
223 209 195 181 168 154 140  
254 240 226 212 198 184 170  
243 247 246 233 219 205 191  
217 203 189 175 161 147 134  
257 243 229 215 201 187 174  
253 253 246 232 218 204 190  
194 177 159 141 124  
-
-
186 170 154 138 122  
-
-
240 222 205 187 170 152 134  
268 255 237 220 202 184 167  
248 250 259 241 223 206 188  
230 214 198 182 165 149 133  
267 256 240 223 207 191 175  
257 257 257 241 224 208 192  
8750  
10000  
11250  
12500  
209 188 166 145 124  
-
-
198 179 161 142 124  
-
-
257 236 214 193 172 150 129  
282 270 248 227 206 184 163  
253 253 271 249 228 207 185  
244 225 206 188 169 151 132  
277 269 250 232 213 194 176  
261 261 268 249 231 212 194  
218 197 177 156 136  
-
-
209 190 171 152 133  
-
-
269 249 228 208 187 167 146  
286 280 267 247 226 206 185  
257 257 265 245 224 204 183  
258 239 220 201 182 163 144  
281 277 266 247 228 210 191  
264 264 268 249 230 211 192  
227 207 187 168 148  
-
-
221 201 182 162 143  
-
-
281 261 242 222 202 183 163  
290 290 286 267 247 227 208  
260 260 260 241 221 201 182  
95°F  
272 253 233 214 195 175 156  
285 285 283 263 244 225 205  
267 267 267 248 228 209 190  
105°F  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
316.1  
283.5  
267.4  
262.7  
319.6  
286.7  
270.4  
265.7  
323.2  
289.8  
273.4  
268.6  
326.8  
293.1  
276.5  
271.7  
330.5  
296.4  
279.6  
274.7  
26.1  
26.2  
25.5  
25.4  
26.6  
26.8  
26.1  
26.0  
27.2  
27.4  
26.7  
26.6  
29.0  
29.1  
28.4  
28.3  
30.7  
30.9  
30.1  
30.0  
171 157 143 129 115  
-
-
297.4  
268.6  
251.6  
242.6  
301.6  
272.4  
255.1  
246.0  
305.7  
276.1  
258.6  
249.4  
309.0  
279.0  
261.4  
252.0  
312.2  
282.0  
264.1  
254.7  
29.4  
29.0  
28.5  
28.3  
29.9  
29.5  
28.9  
28.8  
30.3  
30.0  
29.4  
29.2  
32.2  
31.8  
31.2  
31.0  
34.0  
33.6  
32.9  
32.8  
162 149 135 121 107  
-
-
211 197 183 169 155 141 127  
260 246 232 219 205 191 177  
262 259 245 231 217 203 189  
204 190 176 163 149 135 121  
248 239 226 212 198 184 170  
242 240 232 218 204 190 176  
7500  
8750  
179 164 149 134 119  
-
-
170 155 141 126 111  
-
-
221 206 191 176 161 146 131  
267 257 242 227 212 198 183  
265 263 255 240 225 210 196  
214 199 184 170 155 140 125  
253 248 236 221 206 191 177  
246 245 242 227 212 198 183  
187 171 155 139 124  
-
-
178 162 147 131 115  
-
-
230 214 199 183 167 151 136  
273 268 252 236 220 205 189  
268 268 265 250 234 218 202  
223 208 192 177 161 145 130  
258 256 246 230 214 199 183  
249 249 252 237 221 205 190  
10000  
11250  
12500  
200 183 166 148 131  
-
-
191 174 157 139 122  
-
-
247 229 212 194 177 160 142  
276 273 266 248 231 213 196  
271 271 270 252 235 217 200  
240 223 205 188 171 153 136  
261 260 255 237 220 203 185  
252 252 253 236 219 201 184  
214 195 176 157 138  
-
-
205 186 167 148 129  
-
-
264 244 225 206 187 168 149  
279 279 279 260 241 222 203  
274 274 274 255 236 217 198  
115°F  
256 237 218 199 180 161 142  
264 264 264 245 226 207 188  
254 254 254 235 216 197 178  
125°F  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
278.8  
253.7  
235.8  
222.5  
283.5  
258.0  
239.8  
226.3  
288.3  
262.4  
243.9  
230.1  
291.1  
265.0  
246.2  
232.3  
293.9  
267.5  
248.6  
234.6  
32.7  
31.9  
31.4  
31.2  
33.1  
32.2  
31.7  
31.5  
33.4  
32.6  
32.1  
31.8  
35.4  
34.4  
34.0  
33.7  
37.3  
36.3  
35.8  
35.6  
154 140 126 113 99.  
-
-
260.1  
238.8  
220.0  
202.4  
265.5  
243.7  
224.5  
206.6  
270.8  
248.6  
229.1  
210.8  
273.3  
250.9  
231.1  
212.7  
275.7  
253.1  
233.1  
214.5  
36.1  
34.7  
34.4  
34.0  
36.3  
34.9  
34.6  
34.3  
36.5  
35.1  
34.8  
34.5  
38.6  
37.1  
36.7  
36.4  
40.6  
39.1  
38.7  
38.3  
145 132 118 104 91.  
-
-
197 183 170 156 142 129 115  
235 232 219 205 191 178 164  
222 222 219 205 191 177 164  
190 177 163 149 136 122 109  
220 220 212 198 185 171 157  
202 202 202 192 178 165 151  
7500  
8750  
162 147 132 118 103  
-
-
153 138 124 109 95.  
-
-
207 192 178 163 149 134 119  
239 238 229 214 200 185 171  
226 226 229 214 200 185 170  
200 186 171 157 142 128 113  
224 224 223 208 194 179 165  
206 206 206 201 187 172 158  
169 154 138 123 107  
-
-
161 145 130 115 99.  
-
-
217 201 186 170 155 139 124  
243 243 239 224 208 193 178  
230 230 239 224 208 193 177  
210 195 179 164 149 133 118  
229 229 229 218 202 187 172  
210 210 210 210 196 180 165  
10000  
11250  
12500  
182 165 148 131 113  
-
-
173 156 139 122 105  
-
-
233 216 199 181 164 147 130  
246 246 244 227 209 192 175  
232 232 237 220 202 185 168  
226 209 192 175 158 141 124  
231 231 231 216 199 182 165  
212 212 212 203 186 169 152  
195 176 157 138 119  
-
-
185 167 148 129 110  
-
-
249 230 211 192 173 155 136  
248 248 248 229 210 191 173  
234 234 234 215 196 177 159  
242 223 204 185 167 148 129  
233 233 233 214 195 176 158  
214 214 214 195 177 158 139  
1.  
2.  
The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat *MBh = 3.415 x kW). Refer to the  
appropriate Blower Performance table for the kW of the supply air blower motor.  
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.  
Johnson Controls Unitary Products  
31  
246653-YTG-E-0108  
TABLE 32: COOLING PERFORMANCE 30 TON STANDARD CAPACITY COIL  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON EVAPORATOR COIL  
75°F  
85°F  
2
2
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
TOTAL  
CAP.  
(MBH)  
TOTAL  
INPUT  
(KW)  
TOTAL  
CAP.  
(MBH)  
TOTAL  
WB  
(°F)  
1
1
CFM  
6000  
INPUT  
(KW)  
86 83 80 77 74 71 68  
86 83 80 77 74 71 68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
385  
353  
330  
316  
398  
366  
342  
339  
405  
375  
354  
353  
415  
385  
369  
368  
420  
393  
379  
379  
424  
399  
391  
391  
430  
406  
399  
402  
436  
401  
410  
409  
436  
419  
416  
418  
439  
425  
421  
424  
27.8  
27.3  
26.6  
26.1  
28.0  
27.2  
26.9  
26.8  
28.3  
27.5  
27.1  
27.3  
28.5  
27.6  
27.3  
27.5  
28.7  
27.7  
27.5  
27.1  
28.8  
27.9  
27.5  
27.4  
28.6  
28.0  
27.6  
27.6  
29.0  
28.1  
27.5  
27.5  
29.0  
28.2  
27.9  
27.9  
28.8  
28.2  
27.8  
27.8  
223 203 183 163 142  
-
-
370  
341  
316  
306  
382  
353  
329  
326  
391  
362  
342  
342  
398  
371  
356  
356  
404  
378  
368  
367  
408  
383  
378  
378  
412  
388  
387  
387  
416  
393  
395  
395  
419  
403  
402  
402  
422  
409  
408  
408  
30.6  
30.0  
29.4  
28.9  
30.9  
30.2  
29.7  
29.4  
31.1  
30.4  
29.9  
29.7  
31.2  
30.6  
30.1  
30.0  
31.4  
30.7  
30.2  
30.2  
31.5  
30.8  
30.3  
30.4  
31.5  
30.9  
30.6  
30.6  
31.6  
31.0  
30.7  
30.7  
31.7  
31.1  
30.9  
30.9  
31.7  
31.2  
31.0  
31.0  
217 197 177 157 136  
-
-
259 240 220 200 179 159 141  
295 275 254 235 215 195 175  
316 307 287 269 249 229 209  
254 234 214 194 174 153 133  
289 269 249 229 209 189 169  
306 298 283 263 243 223 203  
240 216 193 169 145  
-
-
234 210 187 163 139  
-
-
281 258 238 212 191 164 143  
321 300 279 256 230 206 183  
339 327 318 293 270 246 226  
276 253 230 206 183 159 135  
318 294 271 248 224 201 177  
326 316 307 288 264 241 218  
7000  
8000  
256 229 202 175 147  
-
-
250 223 196 169 141  
-
-
304 277 250 223 196 169 141  
354 327 297 270 247 217 190  
353 344 334 322 290 263 239  
298 271 245 218 191 164 136  
342 319 292 265 239 212 185  
342 332 322 312 285 258 232  
272 241 211 183 149  
-
-
266 236 205 175 143  
-
-
325 298 265 238 205 177 146  
369 344 317 291 258 231 200  
368 355 348 336 311 280 253  
320 290 260 230 199 169 138  
356 341 312 283 253 223 193  
356 345 335 324 304 275 245  
9000  
284 254 220 186 152  
-
-
281 248 214 180 146  
-
-
341 313 283 246 213 179 147  
379 369 334 307 275 241 208  
379 371 358 348 326 297 265  
339 308 275 241 207 173 139  
368 357 331 300 267 234 200  
367 357 346 335 321 290 258  
10000  
11000  
12000  
13000  
14000  
15000  
303 266 229 192 154  
-
-
297 260 223 186 148  
-
-
363 329 294 261 224 183 145  
391 381 346 321 286 251 215  
391 377 366 356 348 312 276  
358 324 289 253 216 178 140  
378 367 348 315 280 244 207  
378 366 355 344 333 304 269  
317 277 238 197 156  
-
-
311 273 232 192 150  
-
-
388 344 308 267 229 191 146  
399 388 377 338 298 260 221  
402 388 376 365 351 329 286  
377 339 302 263 223 183 141  
387 375 364 329 291 253 214  
387 375 363 352 340 317 280  
329 287 245 203 161  
-
-
324 283 241 197 153  
-
-
398 361 324 277 236 192 147  
410 398 383 350 306 268 227  
409 397 386 374 360 328 299  
392 354 314 272 231 187 142  
395 383 371 342 302 261 220  
395 383 371 359 347 329 291  
338 297 252 209 160  
-
-
337 293 249 203 155  
-
-
419 372 333 289 242 200 148  
416 404 389 366 323 276 235  
418 403 391 380 368 354 308  
403 368 326 281 237 192 143  
402 390 377 355 314 269 226  
402 389 377 365 353 341 300  
356 306 259 213 163  
-
-
350 302 256 209 157  
-
-
425 398 344 295 248 201 153  
421 412 397 370 333 283 240  
424 409 399 385 373 361 317  
409 383 337 290 243 196 145  
408 396 383 366 324 277 231  
408 395 383 370 358 346 310  
32  
Johnson Controls Unitary Products  
246653-YTG-E-0108  
TABLE 32: COOLING PERFORMANCE 30 TON STANDARD CAPACITY COIL (CONTINUED)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON EVAPORATOR COIL  
95°F  
105°F  
2
2
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
TOTAL  
CAP.  
(MBH)  
TOTAL  
TOTAL  
TOTAL  
INPUT  
(KW)  
WB  
1
1
CFM  
(°F)  
INPUT  
(KW)  
CAP.  
(MBH)  
86 83 80 77 74 71 68  
86 83 80 77 74 71 68  
72  
67  
62  
57  
72  
355  
328  
303  
296  
366  
339  
316  
314  
375  
348  
330  
330  
381  
356  
343  
343  
387  
362  
355  
354  
391  
367  
364  
364  
394  
372  
373  
372  
397  
381  
380  
380  
401  
387  
387  
386  
404  
393  
393  
392  
34.0  
33.3  
32.7  
32.2  
34.3  
33.6  
33.0  
32.6  
34.5  
33.8  
33.2  
32.9  
34.6  
34.0  
33.4  
33.2  
34.8  
34.1  
33.5  
33.6  
34.9  
34.2  
33.7  
33.8  
35.0  
34.3  
34.0  
34.0  
35.0  
34.4  
34.2  
34.2  
35.1  
34.5  
34.3  
34.3  
35.2  
34.6  
34.5  
34.5  
211 191 171 151 130  
-
-
340  
314  
291  
286  
350  
324  
303  
303  
357  
333  
318  
317  
364  
340  
330  
329  
369  
345  
340  
340  
373  
351  
349  
349  
376  
358  
357  
357  
379  
365  
365  
364  
382  
371  
371  
370  
385  
377  
376  
376  
38.0  
37.2  
36.5  
36.0  
38.2  
37.4  
36.8  
36.4  
38.5  
37.7  
37.0  
36.9  
38.7  
37.8  
37.2  
37.1  
38.9  
37.9  
37.4  
37.3  
39.0  
38.1  
37.7  
37.6  
39.1  
38.2  
37.8  
37.8  
39.2  
38.3  
38.0  
38.0  
39.2  
38.4  
38.1  
38.1  
39.3  
38.4  
38.3  
38.3  
205 185 165 145 124  
-
-
248 228 208 188 168 147 126  
283 263 243 223 203 183 163  
296 288 277 257 237 217 197  
241 222 202 182 161 141 120  
277 257 236 217 197 177 157  
286 277 269 251 231 211 191  
6000  
228 204 181 157 133  
-
-
222 198 175 151 127  
-
-
67  
270 247 223 200 176 153 128  
312 288 264 241 218 195 171  
314 305 296 282 258 235 211  
263 240 217 194 170 146 122  
303 282 258 235 212 188 165  
303 294 285 275 252 228 205  
7000  
62  
57  
72  
244 217 190 163 135  
-
-
238 211 184 157 129  
-
-
67  
292 265 239 212 185 158 130  
330 312 286 259 232 206 179  
330 320 310 301 279 252 225  
286 259 232 205 178 151 123  
318 306 279 252 226 199 172  
317 308 298 289 272 245 218  
8000  
62  
57  
72  
260 230 199 168 137  
-
-
254 223 193 162 131  
-
-
67  
314 283 254 223 193 162 131  
343 333 306 276 247 216 186  
343 333 322 312 297 269 238  
307 277 247 217 187 156 125  
330 320 299 270 240 210 179  
329 319 309 300 290 262 232  
9000  
62  
57  
72  
276 242 208 174 140  
-
-
269 236 202 168 134  
-
-
67  
334 302 268 235 201 167 132  
355 344 325 293 260 227 193  
354 343 333 322 312 283 251  
326 295 262 228 195 161 126  
340 330 316 286 254 220 187  
340 329 319 309 299 276 244  
10000  
62  
57  
72  
291 254 217 180 142  
-
-
285 248 211 174 136  
-
-
67  
352 318 283 246 209 172 134  
364 353 342 308 273 237 200  
364 353 342 331 319 296 262  
345 311 276 240 203 165 127  
349 339 328 300 265 230 194  
349 338 327 317 306 288 255  
11000  
62  
57  
72  
305 267 226 186 144  
-
-
299 259 220 179 138  
-
-
67  
367 333 295 257 217 176 135  
373 361 350 321 284 246 207  
372 361 349 338 327 308 273  
358 326 287 249 211 170 128  
357 346 335 314 277 239 200  
357 346 334 323 312 302 265  
12000  
62  
57  
72  
318 277 235 191 146  
-
-
311 269 227 185 140  
-
-
67  
381 347 306 266 225 181 136  
380 368 357 334 296 254 213  
380 368 356 344 333 322 283  
365 340 300 259 218 174 129  
365 353 341 326 288 247 206  
364 352 341 329 318 307 275  
13000  
62  
57  
72  
332 287 243 197 149  
-
-
323 279 234 191 142  
-
-
67  
387 361 319 274 231 185 137  
387 375 363 345 306 262 218  
386 374 362 350 338 327 292  
371 351 312 268 224 179 130  
371 359 347 336 299 255 211  
370 358 346 335 323 312 284  
14000  
62  
57  
72  
67  
62  
57  
343 296 250 203 151  
-
-
335 288 241 195 145  
-
-
393 372 330 284 237 190 138  
393 380 368 356 316 270 223  
392 380 367 355 343 331 302  
377 365 323 277 230 183 132  
376 364 352 340 309 262 216  
376 364 351 340 328 316 293  
15000  
Johnson Controls Unitary Products  
33  
246653-YTG-E-0108  
TABLE 32: COOLING PERFORMANCE 30 TON STANDARD CAPACITY COIL (CONTINUED)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON EVAPORATOR COIL  
115°F  
125°F  
2
2
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
TOTAL  
CAP.  
(MBH)  
TOTAL  
TOTAL  
CAP.  
(MBH)  
TOTAL  
WB  
(°F)  
1
1
CFM  
6000  
INPUT  
(KW)  
INPUT  
(KW)  
86 83 80 77 74 71 68  
86 83 80 77 74 71 68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
324  
299  
277  
275  
333  
309  
291  
291  
340  
317  
305  
305  
345  
323  
317  
316  
350  
329  
326  
326  
353  
335  
334  
334  
357  
343  
342  
341  
361  
349  
348  
348  
364  
354  
354  
353  
366  
359  
359  
359  
42.5  
41.7  
40.7  
40.3  
42.8  
41.8  
41.0  
40.8  
42.8  
42.0  
41.3  
41.2  
43.0  
42.2  
41.5  
41.6  
43.2  
42.3  
41.9  
41.9  
43.5  
42.5  
42.2  
42.0  
43.6  
42.6  
42.2  
42.2  
43.7  
42.9  
42.4  
42.4  
43.8  
43.0  
42.6  
42.6  
43.8  
43.1  
42.7  
42.7  
199 179 159 138 118  
-
-
307  
283  
261  
263  
315  
294  
280  
278  
324  
300  
291  
294  
324  
305  
304  
304  
330  
314  
313  
312  
331  
319  
319  
319  
337  
327  
328  
324  
343  
333  
329  
332  
347  
336  
336  
335  
347  
339  
342  
341  
47.5  
46.8  
45.3  
45.1  
48.1  
46.8  
45.6  
45.8  
47.4  
46.7  
46.1  
45.8  
47.5  
47.2  
46.3  
46.7  
47.7  
47.3  
47.0  
47.4  
48.4  
47.4  
47.2  
47.0  
48.5  
47.5  
47.2  
47.2  
48.5  
48.2  
47.4  
47.4  
48.9  
48.3  
47.8  
47.8  
48.7  
48.7  
47.7  
47.7  
193 173 153 130 112  
-
-
235 215 195 175 155 135 114  
270 250 230 210 190 170 150  
275 266 258 244 224 204 184  
230 207 187 167 150 129 108  
262 242 225 202 182 162 142  
263 255 244 236 216 196 176  
215 192 168 144 120  
-
-
207 186 160 136 112  
-
-
257 234 211 187 164 140 115  
291 275 252 228 205 182 158  
291 282 273 265 245 221 198  
252 229 205 179 158 135 107  
276 267 246 220 197 177 150  
278 269 260 252 237 214 190  
7000  
8000  
231 205 178 150 123  
-
-
223 199 172 142 117  
-
-
279 252 226 199 172 145 117  
305 296 273 246 219 192 165  
305 295 286 276 264 239 212  
271 244 221 194 167 140 112  
291 282 268 241 211 185 158  
294 281 274 262 255 234 207  
247 217 187 156 125  
-
-
239 212 181 150 119  
-
-
300 271 240 210 180 149 118  
317 307 292 262 233 203 173  
316 306 296 287 277 254 225  
293 265 233 202 172 141 110  
304 294 285 252 226 195 168  
304 294 283 273 258 245 217  
9000  
263 230 196 162 127  
-
-
258 224 190 156 119  
-
-
320 289 255 222 188 154 119  
326 316 306 277 245 213 180  
326 315 305 295 285 267 235  
316 284 247 217 180 146 111  
313 302 295 266 233 206 172  
312 301 291 280 270 256 224  
10000  
11000  
12000  
13000  
14000  
15000  
278 242 205 168 130  
-
-
270 236 199 162 124  
-
-
335 304 269 233 196 159 120  
334 324 314 291 257 223 186  
334 323 313 303 292 282 247  
322 297 262 225 188 154 113  
319 308 300 281 249 216 176  
319 308 300 289 277 278 238  
292 252 214 173 132  
-
-
284 246 208 168 126  
-
-
343 318 281 241 204 163 122  
342 331 320 304 268 231 191  
341 330 319 309 298 288 256  
322 309 277 233 196 155 117  
328 316 305 291 257 222 180  
324 313 304 296 285 266 246  
305 264 221 179 134  
-
-
300 262 217 173 128  
-
-
349 332 291 250 210 168 122  
348 337 326 315 278 239 197  
348 336 325 314 304 293 267  
333 323 279 239 201 163 115  
329 320 312 301 266 230 186  
332 320 308 299 291 280 259  
317 274 228 184 136  
-
-
314 272 225 176 131  
-
-
354 343 302 261 215 172 123  
354 342 331 320 288 247 203  
353 342 330 319 308 297 276  
336 337 289 253 204 164 116  
336 324 315 297 273 238 194  
335 326 314 302 293 282 268  
329 283 234 188 139  
-
-
325 281 229 182 133  
-
-
359 348 313 268 221 176 124  
359 347 335 324 300 255 208  
359 347 335 323 312 301 283  
339 321 300 257 210 169 114  
342 329 317 308 289 249 199  
341 329 319 304 295 286 272  
1.  
2.  
The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat *MBh = 3.415 x kW). Refer to the  
appropriate Blower Performance table for the kW of the supply air blower motor.  
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.  
34  
Johnson Controls Unitary Products  
246653-YTG-E-0108  
TABLE 33: COOLING PERFORMANCE 30 TON HIGH CAPACITY COIL  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON EVAPORATOR COIL  
75°F  
85°F  
2
2
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
TOTAL  
CAP.  
(MBH)  
TOTAL  
TOTAL  
CAP.  
TOTAL  
WB  
1
1
CFM  
(°F)  
INPUT  
(KW)  
INPUT  
(KW)  
(MBH)  
86 83 80 77 74 71 68  
86 83 80 77 74 71 68  
72  
67  
62  
57  
72  
401  
367  
338  
321  
412  
382  
352  
345  
423  
394  
364  
361  
432  
404  
380  
377  
440  
410  
389  
391  
445  
416  
405  
402  
449  
420  
414  
413  
453  
431  
424  
424  
459  
431  
431  
430  
461  
440  
437  
439  
27.9  
27.3  
27.1  
26.5  
28.2  
27.4  
26.9  
26.8  
28.5  
28.0  
27.4  
27.2  
28.7  
27.7  
27.3  
27.1  
28.8  
28.0  
27.7  
27.4  
28.9  
28.2  
27.7  
27.4  
29.0  
28.3  
28.0  
27.6  
29.4  
28.4  
27.9  
27.9  
29.5  
28.8  
28.1  
28.4  
29.6  
28.9  
28.3  
28.3  
232 212 192 168 151  
-
-
385  
354  
327  
312  
397  
367  
340  
333  
407  
378  
351  
350  
415  
387  
366  
365  
421  
393  
378  
378  
426  
399  
390  
389  
431  
405  
399  
399  
434  
411  
408  
408  
438  
416  
416  
415  
441  
423  
422  
422  
31.0  
30.4  
29.8  
29.2  
31.3  
30.6  
30.0  
29.5  
31.5  
30.9  
30.3  
29.8  
31.7  
31.0  
30.4  
30.1  
31.8  
31.1  
30.6  
30.4  
32.0  
31.2  
30.7  
30.6  
32.0  
31.3  
30.9  
30.8  
32.1  
31.4  
31.0  
31.0  
32.2  
31.5  
31.2  
31.2  
32.3  
31.6  
31.3  
31.3  
224 204 184 163 143  
-
-
268 248 225 205 185 165 147  
302 283 263 240 223 203 183  
321 312 292 277 254 234 217  
260 240 220 200 180 160 140  
295 275 255 235 216 196 176  
312 303 288 269 249 229 210  
6000  
245 225 198 177 153  
-
-
240 217 193 170 146  
-
-
67  
287 267 244 220 194 173 149  
327 304 285 261 238 215 189  
345 333 324 298 278 252 229  
282 259 236 213 189 166 142  
323 300 277 254 231 208 184  
333 323 314 293 271 247 224  
7000  
62  
57  
72  
261 234 210 180 156  
-
-
256 229 203 175 148  
-
-
67  
309 285 256 232 205 178 147  
364 330 306 279 253 226 199  
361 351 342 326 298 272 245  
304 278 251 225 198 171 143  
351 325 299 272 246 219 192  
350 340 330 318 292 265 238  
8000  
62  
57  
72  
280 250 220 186 155  
-
-
272 242 212 181 150  
-
-
67  
334 301 271 241 213 183 152  
380 355 327 297 267 237 206  
377 367 356 347 319 289 258  
327 296 266 236 206 176 145  
366 350 320 290 260 230 200  
365 354 344 333 312 282 252  
9000  
62  
57  
72  
296 259 229 195 157  
-
-
288 254 221 187 152  
-
-
67  
356 322 288 255 221 187 153  
389 378 348 314 281 247 214  
391 381 370 359 340 308 272  
348 315 281 248 214 180 146  
378 367 341 307 274 240 207  
378 367 356 345 332 299 265  
10000  
62  
57  
72  
312 275 238 197 162  
-
-
304 267 230 192 155  
-
-
67  
378 340 303 266 229 192 153  
405 390 364 331 295 258 221  
402 390 379 365 357 323 285  
370 333 296 259 222 185 147  
390 378 362 325 288 251 214  
389 377 366 354 343 315 278  
11000  
62  
57  
72  
325 284 247 206 164  
-
-
319 279 239 198 157  
-
-
67  
393 358 318 275 237 193 155  
414 402 391 350 311 268 227  
413 401 390 375 364 332 297  
392 351 311 270 230 189 148  
399 387 376 342 302 261 221  
399 387 375 363 351 329 291  
12000  
62  
57  
72  
340 296 256 211 166  
-
-
335 291 248 204 159  
-
-
67  
425 372 333 289 245 201 158  
424 412 397 368 322 281 234  
424 409 397 385 370 350 314  
409 369 326 282 238 194 149  
408 396 383 357 315 272 228  
408 395 383 371 358 343 304  
13000  
62  
57  
72  
356 312 265 214 168  
-
-
351 304 257 209 161  
-
-
67  
431 393 347 300 253 205 159  
431 419 404 377 340 291 244  
430 415 406 391 379 367 326  
416 386 340 293 246 198 150  
416 403 390 372 329 282 235  
415 402 390 377 365 353 315  
14000  
62  
57  
72  
67  
62  
57  
372 321 273 223 171  
-
-
367 316 266 215 163  
-
-
440 404 360 312 260 209 155  
437 424 415 403 348 302 248  
439 424 412 396 387 372 339  
423 400 354 304 254 203 150  
422 409 397 385 340 292 241  
422 409 396 383 371 358 326  
15000  
Johnson Controls Unitary Products  
35  
246653-YTG-E-0108  
TABLE 33: COOLING PERFORMANCE 30 TON HIGH CAPACITY COIL (CONTINUED)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON EVAPORATOR COIL  
95°F  
105°F  
2
2
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
TOTAL  
CAP.  
(MBH)  
TOTAL  
INPUT  
(KW)  
TOTAL  
CAP.  
(MBH)  
TOTAL  
WB  
(°F)  
1
1
CFM  
6000  
INPUT  
(KW)  
86 83 80 77 74 71 68  
86 83 80 77 74 71 68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
369  
340  
314  
302  
381  
352  
326  
321  
390  
362  
338  
338  
397  
370  
352  
352  
402  
376  
365  
364  
407  
382  
375  
375  
412  
388  
384  
384  
415  
393  
392  
392  
418  
400  
400  
399  
421  
406  
406  
405  
34.5  
33.8  
33.0  
32.4  
34.8  
34.1  
33.4  
32.8  
35.0  
34.3  
33.6  
33.1  
35.2  
34.5  
33.8  
33.5  
35.3  
34.6  
34.0  
33.8  
35.5  
34.7  
34.1  
34.1  
35.5  
34.8  
34.3  
34.3  
35.6  
34.9  
34.5  
34.5  
35.7  
34.9  
34.7  
34.6  
35.8  
35.0  
34.8  
34.8  
217 197 177 157 136  
-
-
353  
325  
299  
291  
364  
337  
310  
309  
372  
346  
325  
325  
378  
353  
338  
338  
383  
359  
350  
349  
388  
365  
360  
360  
392  
369  
369  
368  
396  
377  
376  
376  
399  
383  
383  
382  
401  
389  
389  
388  
38.4  
37.5  
36.7  
36.1  
38.7  
37.9  
37.1  
36.7  
39.0  
38.2  
37.3  
37.1  
39.2  
38.2  
37.5  
37.3  
39.3  
38.5  
37.9  
37.6  
39.4  
38.7  
37.9  
37.9  
39.5  
38.8  
38.2  
38.1  
39.9  
38.9  
38.4  
38.4  
40.0  
39.0  
38.6  
38.6  
40.1  
39.1  
38.8  
38.8  
211 191 171 150 130  
-
-
253 233 214 194 174 154 133  
288 268 248 229 209 189 169  
302 293 282 262 243 223 203  
247 227 207 187 167 147 126  
281 262 242 222 202 182 162  
291 282 274 256 236 216 196  
234 210 187 163 139  
-
-
227 204 180 156 132  
-
-
276 252 229 206 183 159 135  
317 294 270 247 224 201 178  
321 312 303 287 264 241 218  
269 246 223 199 176 152 128  
309 286 264 240 217 194 171  
309 300 291 280 257 234 211  
7000  
8000  
250 223 196 169 141  
-
-
243 216 189 162 135  
-
-
298 271 245 218 191 164 137  
338 319 292 265 239 212 185  
338 328 318 308 285 258 231  
291 264 238 211 184 157 129  
325 312 285 258 232 205 178  
325 315 306 296 277 251 224  
265 235 205 175 144  
-
-
259 229 199 168 137  
-
-
320 290 260 230 199 169 138  
352 341 313 283 253 223 193  
352 341 331 320 305 275 245  
313 283 253 223 192 162 131  
338 328 306 276 246 216 185  
338 328 317 308 298 268 237  
9000  
281 248 214 180 146  
-
-
275 241 208 174 139  
-
-
341 308 274 241 207 173 139  
365 354 334 300 267 233 200  
364 353 342 331 321 291 258  
335 301 267 234 200 166 132  
350 339 327 293 260 226 193  
349 339 328 317 307 284 251  
10000  
11000  
12000  
13000  
14000  
15000  
297 260 223 186 148  
-
-
291 254 217 179 141  
-
-
363 326 289 252 215 178 140  
375 364 353 318 281 244 207  
375 363 352 341 329 307 271  
357 319 282 245 208 171 132  
360 348 337 310 274 237 200  
360 348 337 326 315 299 264  
313 273 232 191 150  
-
-
307 266 226 185 143  
-
-
384 344 304 264 223 183 141  
384 372 361 334 294 254 214  
384 372 360 349 337 322 284  
369 337 297 257 216 175 134  
369 357 346 326 287 247 206  
368 356 345 333 322 311 276  
329 285 241 197 152  
-
-
322 278 235 190 145  
-
-
393 363 319 275 231 187 141  
392 380 368 348 308 264 221  
392 380 368 356 344 332 295  
377 354 312 268 224 180 134  
376 364 352 341 301 257 213  
376 364 352 340 328 317 287  
345 297 250 203 154  
-
-
338 291 244 196 147  
-
-
400 378 333 286 239 191 142  
400 387 375 362 320 274 227  
399 387 374 362 350 338 306  
383 369 326 279 232 184 135  
383 371 359 347 313 267 220  
382 370 358 346 334 322 299  
361 310 259 208 156  
-
-
354 303 252 202 150  
-
-
406 391 347 297 247 196 144  
406 393 380 368 332 284 234  
405 393 380 368 355 343 316  
389 377 339 291 239 188 137  
389 376 364 352 324 278 227  
388 376 364 351 339 327 309  
36  
Johnson Controls Unitary Products  
246653-YTG-E-0108  
TABLE 33: COOLING PERFORMANCE 30 TON HIGH CAPACITY COIL (CONTINUED)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON EVAPORATOR COIL  
115°F  
125°F  
2
2
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
TOTAL  
CAP.  
(MBH)  
TOTAL  
INPUT  
(KW)  
TOTAL  
CAP.  
(MBH)  
TOTAL  
WB  
(°F)  
1
1
CFM  
6000  
INPUT  
(KW)  
86 83 80 77 74 71 68  
86 83 80 77 74 71 68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
336  
310  
286  
280  
346  
321  
297  
297  
354  
329  
312  
312  
359  
335  
324  
324  
364  
341  
335  
334  
369  
345  
344  
344  
372  
353  
352  
352  
375  
360  
359  
359  
378  
366  
366  
365  
381  
371  
371  
371  
42.9  
41.9  
41.2  
40.3  
43.3  
42.4  
41.5  
41.0  
43.5  
42.6  
41.8  
41.4  
43.7  
42.8  
42.0  
41.8  
43.9  
43.0  
42.4  
42.2  
44.0  
43.1  
42.5  
42.3  
44.1  
43.3  
42.5  
42.5  
44.2  
43.4  
42.8  
42.7  
44.3  
43.5  
43.1  
43.1  
44.3  
43.4  
43.3  
43.3  
204 184 164 144 123  
-
-
318  
295  
275  
269  
327  
304  
287  
285  
336  
311  
299  
299  
340  
316  
310  
310  
345  
322  
320  
319  
350  
322  
327  
327  
352  
340  
333  
336  
352  
342  
341  
341  
355  
349  
349  
348  
361  
352  
352  
354  
48.0  
47.0  
46.5  
45.0  
48.6  
47.6  
46.6  
45.7  
48.5  
47.5  
47.1  
46.0  
48.7  
48.3  
47.3  
47.0  
49.1  
48.1  
47.5  
47.6  
49.3  
47.9  
47.9  
47.3  
49.3  
48.3  
47.2  
47.5  
48.5  
48.4  
47.7  
47.4  
48.6  
48.4  
48.2  
48.1  
48.4  
47.9  
48.3  
48.3  
196 176 156 139 115  
-
-
240 220 200 180 160 140 119  
274 255 235 215 195 175 155  
280 271 263 248 229 209 189  
232 212 193 173 153 133 112  
267 247 227 208 188 168 148  
269 260 249 238 222 202 182  
220 197 173 150 126  
-
-
213 189 166 145 121  
-
-
262 239 216 192 169 145 121  
297 280 257 233 210 187 163  
297 288 279 270 250 227 203  
255 231 208 185 162 138 114  
281 276 249 226 203 180 154  
285 276 267 257 243 220 194  
7000  
8000  
236 210 183 155 128  
-
-
229 205 178 148 120  
-
-
284 258 231 204 177 150 122  
312 303 277 251 224 198 171  
312 302 293 283 270 244 217  
277 253 224 197 170 143 116  
299 292 268 244 215 191 164  
299 289 279 269 264 237 210  
252 222 192 161 130  
-
-
244 214 184 154 123  
-
-
306 276 246 216 185 155 123  
324 314 299 269 238 208 178  
324 314 304 294 284 260 230  
299 269 239 209 178 148 114  
310 299 292 262 229 199 172  
310 299 292 278 263 251 224  
9000  
268 235 201 167 132  
-
-
260 230 193 159 125  
-
-
328 294 260 227 193 159 124  
335 324 314 286 252 219 185  
334 324 314 303 293 277 243  
320 287 253 220 186 152 115  
320 309 295 279 243 212 176  
319 308 300 289 279 270 234  
10000  
11000  
12000  
13000  
14000  
15000  
284 247 210 172 134  
-
-
276 239 202 165 127  
-
-
345 312 275 238 201 164 125  
344 333 322 303 266 229 192  
344 333 322 311 301 291 256  
327 305 268 231 194 157 119  
327 319 308 297 257 220 183  
327 318 307 296 287 283 247  
300 259 219 178 136  
-
-
292 252 211 170 129  
-
-
353 331 290 250 209 168 126  
352 341 329 318 280 239 199  
352 340 329 318 307 296 267  
336 326 283 243 202 162 117  
333 324 310 310 273 230 193  
336 324 312 304 292 277 257  
316 272 228 184 139  
-
-
311 267 220 179 134  
-
-
360 347 305 261 217 173 128  
359 347 336 325 293 250 206  
359 347 335 324 313 302 280  
342 342 298 254 210 166 123  
341 329 320 300 284 243 200  
341 329 317 308 299 287 274  
332 284 237 189 141  
-
-
327 276 229 182 136  
-
-
366 354 319 272 225 177 120  
366 354 342 330 305 260 213  
365 353 341 330 318 307 290  
349 333 312 265 218 170 97  
349 336 324 311 296 253 206  
348 336 323 314 302 293 279  
347 297 246 195 139  
-
-
340 292 241 187 123  
-
-
371 359 332 283 233 182 128  
371 359 347 335 315 270 219  
371 358 346 334 323 311 298  
352 337 326 273 229 178 117  
352 342 329 317 305 260 210  
354 339 326 317 307 295 283  
1.  
2.  
The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat *MBh = 3.415 x kW). Refer to the  
appropriate Blower Performance table for the kW of the supply air blower motor.  
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.  
Johnson Controls Unitary Products  
37  
246653-YTG-E-0108  
TABLE 34: COOLING PERFORMANCE 40 TON STANDARD CAPACITY COIL  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON EVAPORATOR COIL  
75°F  
85°F  
2
2
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
TOTAL  
CAP.  
(MBH)  
TOTAL  
INPUT  
(KW)  
TOTAL  
CAP.  
(MBH)  
TOTAL  
WB  
(°F)  
1
1
CFM  
8000  
INPUT  
(KW)  
86 83 80 77 74 71 68  
86 83 80 77 74 71 68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
530  
488  
454  
430  
544  
505  
466  
452  
556  
515  
471  
468  
566  
526  
488  
490  
572  
535  
506  
503  
580  
544  
518  
517  
585  
544  
528  
530  
589  
552  
540  
539  
593  
555  
551  
550  
599  
559  
559  
558  
602  
569  
568  
565  
608  
575  
575  
574  
608  
581  
583  
580  
39.3  
37.7  
37.5  
36.6  
39.0  
37.7  
37.8  
37.1  
39.3  
38.3  
38.1  
37.1  
39.5  
39.1  
38.3  
38.1  
39.7  
39.5  
38.6  
38.3  
39.6  
39.4  
39.0  
38.3  
40.0  
39.5  
38.1  
38.3  
40.1  
39.6  
38.5  
38.5  
40.2  
39.8  
38.7  
38.5  
40.0  
39.9  
38.7  
38.7  
40.1  
39.7  
38.9  
39.2  
40.2  
39.8  
39.1  
39.1  
40.6  
40.1  
39.5  
39.4  
303 280 253 226 195  
-
-
509  
469  
435  
416  
522  
484  
447  
437  
533  
494  
455  
453  
542  
504  
471  
472  
548  
512  
487  
485  
555  
520  
499  
498  
560  
522  
509  
510  
564  
529  
520  
519  
568  
533  
530  
529  
573  
538  
538  
537  
576  
547  
546  
544  
581  
553  
553  
552  
582  
559  
560  
558  
43.3  
42.2  
41.4  
40.6  
43.5  
42.5  
41.7  
41.1  
43.7  
42.8  
42.0  
41.4  
43.9  
43.0  
42.2  
41.8  
44.1  
43.2  
42.4  
42.1  
44.2  
43.3  
42.6  
42.4  
44.4  
43.4  
42.6  
42.6  
44.5  
43.5  
42.8  
42.8  
44.6  
43.7  
43.0  
43.0  
44.6  
43.7  
43.2  
43.2  
44.7  
43.8  
43.4  
43.4  
44.8  
43.9  
43.5  
43.5  
44.9  
44.0  
43.7  
43.7  
296 270 243 216 188  
-
-
352 325 302 272 245 218 194  
397 375 345 319 295 266 239  
430 416 389 364 337 311 287  
344 318 292 265 238 211 184  
391 365 338 312 286 259 232  
416 404 383 357 330 304 278  
323 293 259 232 198  
-
-
313 283 252 222 191  
-
-
377 344 317 287 254 226 195  
427 397 367 340 310 280 250  
452 437 424 394 361 331 302  
367 337 308 278 247 217 186  
419 390 360 331 301 271 241  
437 424 412 382 352 322 293  
9000  
339 302 272 238 200  
-
-
329 295 262 228 193  
-
-
396 366 332 299 265 231 197  
450 421 391 358 325 288 258  
474 455 443 412 382 349 315  
389 356 323 290 256 222 188  
448 415 382 349 316 282 249  
455 441 428 406 373 340 307  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
19000  
20000  
355 318 281 244 206  
-
-
345 308 271 234 196  
-
-
418 384 347 308 271 236 195  
488 446 412 376 339 302 265  
484 475 459 446 408 366 329  
411 375 338 301 264 227 189  
471 439 403 367 330 293 257  
470 457 443 430 394 357 320  
371 330 287 246 205  
-
-
361 321 280 239 198  
-
-
440 402 362 322 282 241 200  
500 469 432 393 353 313 273  
500 486 473 460 423 382 345  
433 393 353 313 273 232 191  
485 462 424 384 344 304 264  
484 470 456 442 413 374 334  
383 340 296 252 207  
-
-
376 333 289 245 200  
-
-
464 418 377 334 290 246 201  
515 498 448 410 367 323 280  
514 497 483 469 438 398 355  
455 411 368 325 281 237 192  
498 482 443 402 358 315 271  
497 482 468 453 429 390 347  
399 352 305 261 209  
-
-
392 345 298 251 202  
-
-
485 437 392 345 298 250 202  
528 510 476 426 381 334 287  
524 510 495 481 452 414 371  
473 430 383 336 289 241 193  
509 494 461 418 372 325 278  
508 493 478 463 444 405 360  
415 368 314 263 215  
-
-
408 358 307 256 205  
-
-
505 452 402 356 306 255 203  
537 522 487 443 391 343 294  
539 521 506 489 474 433 381  
492 446 397 347 297 246 194  
519 504 477 433 385 336 285  
519 503 488 472 457 419 372  
433 377 323 269 214  
-
-
424 370 316 262 207  
-
-
522 471 419 368 314 256 204  
548 533 500 462 402 353 301  
547 529 514 499 481 441 395  
510 462 411 359 305 250 195  
529 513 492 447 397 346 292  
528 512 496 481 465 431 383  
442 391 332 278 216  
-
-
437 383 325 268 209  
-
-
526 482 430 375 321 264 205  
556 540 524 476 418 365 306  
555 539 524 505 490 455 402  
527 476 424 369 313 255 196  
537 521 505 461 409 355 299  
536 520 504 488 472 443 393  
464 398 341 280 218  
-
-
451 393 334 273 211  
-
-
548 504 444 385 334 268 206  
565 546 530 486 429 373 311  
565 546 530 514 499 454 412  
540 491 436 378 321 260 197  
545 528 512 473 420 363 306  
544 527 511 495 479 454 403  
471 408 354 289 223  
-
-
464 403 343 279 214  
-
-
572 517 459 394 337 273 210  
572 556 536 491 437 378 319  
571 555 539 520 504 486 420  
552 505 448 388 328 264 199  
552 535 518 484 430 371 312  
551 534 518 501 485 468 413  
486 421 364 292 226  
-
-
476 413 351 284 216  
-
-
581 527 464 402 349 274 208  
577 561 545 505 449 386 324  
580 560 541 528 509 490 434  
559 518 458 396 334 268 200  
558 541 524 500 441 379 317  
558 540 523 507 490 473 423  
38  
Johnson Controls Unitary Products  
246653-YTG-E-0108  
TABLE 34: COOLING PERFORMANCE 40 TON STANDARD CAPACITY COIL (CONTINUED)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON EVAPORATOR COIL  
95°F  
105°F  
2
2
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
TOTAL  
CAP.  
(MBH)  
TOTAL  
TOTAL  
TOTAL  
INPUT  
(KW)  
WB  
1
1
CFM  
(°F)  
INPUT  
(KW)  
CAP.  
(MBH)  
86 83 80 77 74 71 68  
86 83 80 77 74 71 68  
72  
67  
62  
57  
72  
488  
450  
416  
402  
500  
463  
428  
422  
510  
473  
439  
438  
518  
482  
454  
454  
524  
489  
468  
467  
530  
496  
480  
479  
535  
500  
490  
490  
539  
506  
500  
499  
543  
511  
509  
508  
547  
517  
517  
516  
550  
525  
524  
523  
554  
531  
531  
530  
556  
537  
537  
536  
48.1  
47.1  
46.0  
45.2  
48.5  
47.5  
46.3  
45.7  
48.7  
47.7  
46.6  
46.2  
48.9  
47.7  
46.8  
46.4  
49.1  
47.9  
47.0  
46.7  
49.3  
48.1  
47.2  
47.1  
49.4  
48.2  
47.5  
47.4  
49.5  
48.3  
47.7  
47.6  
49.6  
48.4  
47.9  
47.9  
49.7  
48.5  
48.1  
48.1  
49.8  
48.7  
48.3  
48.2  
49.9  
48.8  
48.4  
48.4  
49.9  
48.8  
48.6  
48.6  
288 261 234 207 180  
-
-
467  
431  
397  
388  
478  
442  
409  
407  
487  
452  
423  
423  
494  
460  
437  
436  
500  
466  
449  
449  
505  
472  
461  
460  
510  
478  
471  
470  
514  
483  
480  
479  
518  
489  
488  
487  
521  
496  
496  
495  
524  
503  
502  
502  
527  
509  
509  
508  
530  
515  
514  
514  
53.7  
52.4  
51.3  
50.4  
54.0  
52.7  
51.6  
50.9  
54.3  
53.0  
51.9  
51.5  
54.5  
53.2  
52.1  
51.9  
54.7  
53.6  
52.4  
52.1  
54.9  
53.8  
52.8  
52.4  
55.0  
53.9  
52.8  
52.7  
55.1  
54.0  
53.2  
52.9  
55.2  
53.9  
53.4  
53.2  
55.3  
54.3  
53.4  
53.4  
55.4  
54.4  
53.6  
53.6  
55.5  
54.5  
53.8  
53.8  
55.6  
54.5  
54.2  
54.1  
279 253 226 199 171  
-
-
336 310 283 257 230 203 175  
383 356 330 304 277 251 224  
402 391 375 349 322 296 269  
328 301 275 248 221 194 167  
373 348 321 295 268 242 215  
388 377 365 340 313 287 260  
8000  
304 274 244 213 183  
-
-
296 266 235 205 174  
-
-
67  
358 329 299 269 239 208 177  
411 382 352 322 292 262 232  
422 410 398 372 343 313 284  
350 320 290 260 230 199 168  
403 373 343 313 283 253 223  
407 395 382 364 334 304 275  
9000  
62  
57  
72  
320 287 253 219 185  
-
-
312 278 245 211 176  
-
-
67  
381 347 314 281 247 213 179  
439 407 373 340 307 274 240  
438 426 413 397 364 331 298  
372 339 305 272 238 204 170  
423 397 364 331 298 264 231  
423 410 398 385 355 322 288  
10000  
62  
57  
72  
336 299 262 225 187  
-
-
328 291 254 217 179  
-
-
67  
403 366 329 293 256 218 181  
454 431 394 358 321 284 248  
454 440 427 414 383 348 311  
394 357 320 284 247 209 171  
437 422 385 349 312 275 238  
436 424 411 398 375 339 302  
11000  
62  
57  
72  
352 312 272 231 190  
-
-
344 303 263 222 181  
-
-
67  
425 384 344 304 264 223 182  
468 451 415 375 335 295 255  
467 453 439 425 403 365 324  
416 375 335 295 255 214 173  
449 436 405 366 326 286 246  
449 435 422 409 393 355 315  
12000  
62  
57  
72  
368 325 281 237 192  
-
-
359 316 272 228 183  
-
-
67  
446 403 359 316 272 228 183  
480 465 434 393 349 306 262  
479 465 451 436 418 381 338  
437 394 350 307 263 219 174  
461 447 421 383 340 296 253  
460 446 432 418 405 371 328  
13000  
62  
57  
72  
384 337 290 242 194  
-
-
375 328 281 234 185  
-
-
67  
463 421 374 327 280 232 184  
490 476 449 409 363 316 269  
490 475 460 445 431 395 350  
455 410 365 318 271 223 175  
471 456 440 399 354 307 260  
470 456 441 427 413 384 341  
14000  
62  
57  
72  
400 349 299 248 196  
-
-
391 341 290 239 188  
-
-
67  
481 437 389 338 288 237 185  
500 485 465 423 376 327 276  
499 484 469 454 439 407 362  
472 425 378 329 279 228 176  
480 465 451 413 364 316 267  
479 464 449 435 420 397 351  
15000  
62  
57  
72  
415 362 308 254 199  
-
-
406 353 299 245 190  
-
-
67  
499 452 402 350 296 242 186  
509 493 478 435 388 337 283  
508 493 477 462 447 420 372  
489 441 392 341 287 232 177  
488 473 458 426 375 326 274  
487 472 457 442 427 408 362  
16000  
62  
57  
72  
429 374 317 259 201  
-
-
418 364 308 251 192  
-
-
67  
517 467 415 360 304 246 187  
517 501 485 448 399 345 290  
516 500 484 469 453 431 383  
496 455 403 348 294 237 178  
496 480 464 437 388 335 279  
495 479 464 448 433 419 372  
17000  
62  
57  
72  
440 385 326 265 203  
-
-
431 374 317 256 194  
-
-
67  
525 479 426 369 310 251 188  
524 508 492 461 410 353 297  
523 507 491 475 459 444 393  
503 468 414 358 301 241 179  
502 486 470 450 399 343 284  
502 486 470 454 439 424 382  
18000  
62  
57  
72  
455 395 333 270 205  
-
-
444 384 324 262 196  
-
-
67  
531 494 437 379 318 255 189  
531 514 498 474 421 362 302  
530 513 497 481 465 449 403  
509 484 426 367 307 246 180  
509 493 476 461 410 351 289  
508 492 476 460 444 429 390  
19000  
62  
57  
72  
67  
62  
57  
466 404 340 276 207  
-
-
456 394 331 268 199  
-
-
537 507 449 387 322 260 191  
537 520 503 487 431 370 307  
536 519 503 486 470 454 411  
515 494 437 375 313 250 181  
514 498 482 466 419 359 294  
514 497 481 465 449 433 398  
20000  
Johnson Controls Unitary Products  
39  
246653-YTG-E-0108  
TABLE 34: COOLING PERFORMANCE 40 TON STANDARD CAPACITY COIL (CONTINUED)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON EVAPORATOR COIL  
115°F  
125°F  
2
2
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
TOTAL  
CAP.  
(MBH)  
TOTAL  
TOTAL  
CAP.  
(MBH)  
TOTAL  
WB  
(°F)  
1
1
CFM  
8000  
INPUT  
(KW)  
INPUT  
(KW)  
86 83 80 77 74 71 68  
86 83 80 77 74 71 68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
446  
411  
379  
373  
456  
421  
391  
391  
464  
430  
406  
406  
470  
437  
419  
419  
475  
443  
431  
431  
481  
449  
441  
441  
485  
455  
450  
450  
489  
460  
459  
458  
492  
467  
466  
466  
495  
475  
473  
473  
498  
481  
480  
479  
501  
486  
485  
485  
503  
491  
491  
490  
60.0  
58.5  
57.5  
56.5  
60.3  
59.1  
57.7  
57.1  
60.3  
59.4  
57.9  
57.6  
60.6  
59.3  
58.4  
58.1  
61.1  
59.5  
58.4  
58.5  
61.2  
60.0  
58.6  
58.8  
61.4  
59.9  
59.2  
59.1  
61.5  
60.3  
59.4  
59.1  
61.6  
60.4  
59.7  
59.4  
61.7  
60.3  
59.6  
59.6  
61.8  
60.7  
59.9  
59.8  
61.9  
60.8  
60.1  
60.0  
62.0  
60.6  
60.2  
60.2  
271 244 217 190 163  
-
-
425  
392  
360  
359  
434  
400  
372  
376  
441  
409  
390  
391  
446  
415  
402  
401  
451  
420  
412  
413  
456  
425  
422  
422  
460  
433  
431  
430  
464  
437  
439  
438  
467  
445  
445  
445  
469  
454  
452  
452  
472  
459  
458  
458  
474  
464  
463  
463  
477  
469  
468  
468  
65.6  
63.8  
62.8  
61.7  
65.8  
64.3  
63.0  
62.3  
65.9  
64.7  
63.2  
62.9  
66.2  
64.8  
63.7  
63.6  
66.7  
65.2  
63.8  
63.9  
66.8  
65.7  
64.2  
64.1  
67.0  
65.6  
64.5  
64.4  
67.1  
66.0  
64.9  
64.4  
67.2  
65.9  
65.2  
64.7  
67.3  
66.1  
64.9  
64.9  
67.4  
66.4  
65.2  
65.2  
67.5  
66.5  
65.5  
65.4  
67.7  
66.3  
65.8  
65.7  
262 236 209 182 154  
-
-
319 292 266 239 212 185 158  
365 339 312 286 259 233 206  
373 362 351 330 304 278 251  
311 283 258 230 203 176 150  
355 331 303 277 250 224 197  
359 348 341 321 295 269 242  
287 257 227 196 165  
-
-
279 249 218 188 156  
-
-
341 311 281 251 221 190 159  
391 363 334 304 274 244 214  
391 379 367 355 325 295 265  
333 302 272 242 212 181 150  
383 354 325 295 265 235 205  
376 364 351 347 316 286 256  
9000  
303 270 236 202 168  
-
-
295 261 228 194 159  
-
-
363 330 296 263 229 195 161  
406 388 355 321 288 255 222  
406 393 381 369 345 312 279  
354 322 287 254 220 186 152  
390 378 346 312 279 245 213  
391 377 366 357 336 303 269  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
19000  
20000  
319 282 245 208 170  
-
-
311 274 237 200 162  
-
-
385 348 311 275 238 200 162  
419 407 376 339 303 266 229  
419 406 393 381 365 329 292  
376 339 302 266 229 191 152  
402 398 367 330 294 257 219  
401 390 377 365 357 320 283  
335 295 254 214 172  
-
-
327 286 245 205 163  
-
-
406 366 326 286 246 205 163  
431 418 395 357 316 276 236  
431 417 404 391 378 344 305  
397 357 317 277 237 196 154  
412 403 385 348 307 267 227  
413 399 387 375 368 334 296  
351 307 263 219 174  
-
-
342 298 254 210 165  
-
-
427 385 341 297 254 209 165  
441 427 414 372 330 287 243  
441 427 414 400 387 358 318  
418 376 332 288 245 200 156  
422 409 401 362 321 277 234  
422 408 395 382 374 348 308  
367 320 272 225 177  
-
-
358 311 263 217 168  
-
-
445 402 356 309 262 214 166  
450 436 423 386 344 297 250  
450 436 422 408 395 372 330  
437 391 347 300 253 205 157  
431 416 414 376 335 288 241  
430 417 403 390 377 361 321  
383 332 282 231 179  
-
-
374 324 273 222 171  
-
-
460 416 369 320 270 219 167  
459 444 431 400 356 308 257  
458 444 429 416 402 384 341  
451 404 358 311 261 210 158  
439 424 417 390 344 297 248  
438 424 409 397 383 374 330  
397 345 291 236 181  
-
-
388 336 282 227 172  
-
-
467 432 381 330 278 223 167  
466 452 437 414 367 316 264  
466 451 436 422 408 394 351  
457 421 371 321 269 213 158  
445 432 417 405 354 305 255  
445 430 416 402 388 382 341  
410 355 300 242 183  
-
-
399 345 291 234 174  
-
-
475 444 394 339 285 228 168  
473 458 443 429 378 323 271  
473 458 443 428 414 399 361  
454 432 382 327 275 219 159  
452 437 422 418 367 313 260  
452 437 423 407 394 387 350  
422 367 307 248 186  
-
-
413 356 298 239 177  
-
-
481 460 404 348 291 232 169  
480 464 449 434 389 331 276  
479 464 448 433 419 404 371  
459 449 392 337 282 222 160  
458 442 427 423 378 321 263  
458 443 427 412 399 384 360  
434 375 314 253 188  
-
-
423 364 305 245 179  
-
-
486 471 416 357 297 237 169  
485 470 454 439 398 339 281  
485 469 454 438 423 408 378  
464 461 405 345 286 228 160  
463 449 432 426 387 328 268  
463 448 433 417 402 388 365  
447 385 321 259 190  
-
-
437 375 312 251 182  
-
-
491 475 429 366 303 241 171  
491 475 459 444 407 347 286  
490 474 458 443 427 412 386  
469 462 417 354 294 231 161  
468 453 438 423 395 336 273  
468 452 436 422 406 391 373  
1.  
2.  
The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat *MBh = 3.415 x kW). Refer to the  
appropriate Blower Performance table for the kW of the supply air blower motor.  
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.  
40  
Johnson Controls Unitary Products  
246653-YTG-E-0108  
TABLE 35: COOLING PERFORMANCE 40 TON HIGH CAPACITY COIL  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON EVAPORATOR COIL  
75°F  
85°F  
2
2
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
TOTAL  
CAP.  
(MBH)  
TOTAL  
TOTAL  
CAP.  
TOTAL  
WB  
1
1
CFM  
(°F)  
INPUT  
(KW)  
INPUT  
(KW)  
(MBH)  
86 83 80 77 74 71 68  
86 83 80 77 74 71 68  
72  
67  
62  
57  
72  
535  
492  
459  
432  
553  
510  
475  
457  
564  
520  
483  
480  
572  
528  
493  
492  
578  
539  
511  
508  
590  
543  
523  
526  
592  
559  
537  
536  
599  
561  
549  
546  
600  
571  
558  
557  
607  
570  
569  
569  
611  
577  
576  
576  
614  
587  
583  
585  
617  
593  
592  
594  
39.0  
38.2  
37.7  
36.7  
39.1  
38.9  
38.1  
37.2  
40.2  
38.8  
38.4  
37.3  
40.2  
39.4  
38.3  
38.4  
40.7  
39.3  
38.6  
38.6  
40.8  
39.5  
38.9  
38.3  
41.0  
39.6  
39.0  
38.6  
40.8  
39.8  
39.1  
38.9  
40.9  
39.6  
38.7  
38.8  
41.0  
40.0  
39.1  
39.0  
41.1  
40.3  
39.3  
39.2  
41.2  
40.4  
39.4  
39.1  
41.3  
40.8  
39.9  
39.8  
310 280 253 226 199  
-
-
517  
476  
440  
421  
531  
490  
454  
443  
542  
501  
465  
462  
551  
511  
478  
478  
558  
520  
494  
493  
565  
527  
507  
507  
570  
534  
519  
519  
575  
539  
530  
529  
579  
545  
540  
539  
584  
550  
549  
548  
588  
557  
557  
556  
591  
565  
564  
564  
594  
572  
571  
571  
43.4  
42.4  
41.6  
40.8  
43.7  
42.8  
41.9  
41.2  
44.0  
43.0  
42.2  
41.6  
44.2  
43.3  
42.4  
42.0  
44.4  
43.4  
42.6  
42.3  
44.6  
43.6  
42.7  
42.6  
44.7  
43.7  
42.9  
42.9  
44.8  
43.8  
43.0  
43.1  
44.9  
43.9  
43.2  
43.3  
45.0  
44.1  
43.5  
43.5  
45.1  
44.2  
43.7  
43.7  
45.1  
44.3  
43.9  
43.8  
45.2  
44.4  
44.0  
44.0  
300 273 246 219 192  
-
-
357 331 302 278 251 224 197  
404 378 351 325 298 272 245  
432 421 393 370 343 317 290  
348 322 295 269 242 215 188  
395 368 342 316 289 263 236  
421 409 386 360 334 308 281  
8000  
323 293 263 235 204  
-
-
316 286 256 226 195  
-
-
67  
380 350 317 288 260 230 199  
435 403 373 343 313 284 253  
457 442 427 400 362 335 305  
371 341 311 281 251 221 190  
424 394 364 334 305 275 245  
443 430 416 386 355 326 296  
9000  
62  
57  
72  
342 306 275 241 204  
-
-
333 299 266 232 197  
-
-
67  
402 369 336 302 269 235 201  
453 427 395 361 331 295 261  
480 464 449 415 385 352 319  
393 360 327 294 260 226 192  
452 419 386 353 320 286 253  
462 448 435 409 377 343 310  
10000  
62  
57  
72  
358 321 284 247 209  
-
-
349 312 275 238 200  
-
-
67  
421 384 351 314 280 240 202  
493 452 416 382 342 309 272  
492 481 469 444 408 369 332  
415 378 342 305 269 231 193  
478 443 407 371 334 298 261  
478 464 451 434 398 361 324  
11000  
62  
57  
72  
374 334 294 250 211  
-
-
365 325 284 243 202  
-
-
67  
446 406 366 326 285 245 206  
511 468 436 397 356 317 276  
508 494 483 464 426 389 349  
437 397 357 317 277 236 195  
494 468 428 388 348 308 268  
493 479 465 450 417 378 338  
12000  
62  
57  
72  
387 346 300 258 211  
-
-
380 337 293 249 204  
-
-
67  
467 421 381 337 294 249 204  
523 509 456 414 370 327 283  
526 508 494 480 440 405 362  
459 415 372 329 285 241 196  
507 492 449 406 362 319 275  
507 492 477 462 437 395 351  
13000  
62  
57  
72  
406 356 309 264 216  
-
-
396 349 302 255 207  
-
-
67  
493 443 395 349 301 257 206  
537 522 479 432 384 341 293  
536 521 507 489 466 418 375  
481 434 387 340 293 246 197  
519 504 470 423 376 330 283  
519 503 488 473 455 411 364  
14000  
62  
57  
72  
422 371 318 267 218  
-
-
412 362 311 260 209  
-
-
67  
516 461 413 360 309 259 207  
549 531 490 451 398 348 300  
546 534 516 498 486 438 385  
502 452 402 351 301 250 198  
530 514 488 441 390 340 290  
529 514 498 482 467 427 377  
15000  
62  
57  
72  
437 381 327 275 220  
-
-
428 374 320 266 211  
-
-
67  
529 477 425 371 317 266 208  
558 542 519 464 412 358 307  
557 542 526 508 493 450 400  
521 470 416 363 309 255 199  
540 524 505 457 404 350 297  
539 523 507 491 475 441 390  
16000  
62  
57  
72  
453 396 336 281 219  
-
-
444 387 329 272 213  
-
-
67  
543 492 440 382 325 268 209  
569 550 534 492 428 371 314  
569 552 534 518 500 464 414  
541 487 431 374 317 259 200  
549 532 516 472 418 361 304  
548 532 515 499 482 454 403  
17000  
62  
57  
72  
467 408 345 284 224  
-
-
459 399 338 277 215  
-
-
67  
577 513 454 394 333 275 210  
576 560 541 504 436 382 321  
576 559 543 524 508 472 420  
557 503 446 385 325 264 201  
557 540 523 485 430 371 311  
556 539 523 506 489 466 413  
18000  
62  
57  
72  
482 418 354 292 224  
-
-
475 411 347 283 217  
-
-
67  
587 532 467 406 341 276 211  
583 566 550 510 447 391 325  
585 566 549 530 517 498 441  
565 517 458 397 333 268 203  
564 547 530 499 441 381 317  
564 546 529 512 496 479 423  
19000  
62  
57  
72  
67  
62  
57  
492 432 363 295 229  
-
-
488 424 356 288 220  
-
-
593 534 475 413 351 284 215  
592 575 556 521 468 396 332  
594 575 558 539 519 503 438  
572 532 470 408 341 273 204  
571 554 536 513 452 389 324  
571 553 536 518 501 484 433  
20000  
Johnson Controls Unitary Products  
41  
246653-YTG-E-0108  
TABLE 35: COOLING PERFORMANCE 40 TON HIGH CAPACITY COIL (CONTINUED)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON EVAPORATOR COIL  
95°F  
105°F  
2
2
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
TOTAL  
CAP.  
(MBH)  
TOTAL  
INPUT  
(KW)  
TOTAL  
CAP.  
(MBH)  
TOTAL  
WB  
(°F)  
1
1
CFM  
8000  
INPUT  
(KW)  
86 83 80 77 74 71 68  
86 83 80 77 74 71 68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
497  
458  
422  
408  
509  
470  
434  
428  
519  
481  
447  
445  
528  
491  
462  
462  
535  
499  
476  
476  
540  
506  
489  
488  
546  
510  
500  
500  
550  
516  
510  
510  
555  
521  
520  
519  
559  
529  
528  
527  
563  
536  
536  
535  
566  
543  
543  
542  
569  
550  
549  
548  
48.4  
47.2  
46.2  
45.4  
48.7  
47.5  
46.5  
45.9  
48.8  
47.8  
46.8  
46.4  
49.1  
48.0  
47.1  
46.6  
49.2  
48.2  
47.3  
46.9  
49.4  
48.4  
47.4  
47.4  
49.5  
48.5  
47.6  
47.7  
49.7  
48.6  
47.8  
47.9  
49.8  
48.8  
48.2  
48.2  
49.9  
48.9  
48.4  
48.4  
50.0  
49.0  
48.6  
48.6  
50.0  
49.1  
48.8  
48.8  
50.1  
49.2  
48.9  
48.9  
291 265 238 211 184  
-
-
475  
438  
405  
393  
487  
450  
415  
412  
495  
460  
429  
429  
503  
468  
445  
444  
509  
476  
457  
457  
515  
480  
469  
469  
520  
487  
480  
479  
524  
492  
489  
489  
528  
499  
498  
497  
532  
507  
506  
506  
536  
514  
513  
513  
539  
521  
520  
519  
542  
527  
526  
525  
54.0  
52.6  
51.5  
50.5  
54.1  
53.0  
51.9  
51.3  
54.6  
53.2  
52.2  
51.7  
54.9  
53.5  
52.4  
52.2  
55.1  
53.7  
52.7  
52.4  
55.2  
53.9  
53.0  
52.7  
55.4  
54.0  
53.1  
53.0  
55.5  
54.2  
53.5  
53.3  
55.6  
54.3  
53.7  
53.5  
55.7  
54.4  
53.8  
53.7  
55.8  
54.7  
54.0  
53.9  
55.9  
54.8  
54.1  
54.1  
56.0  
55.2  
54.6  
54.5  
283 256 229 202 175  
-
-
339 313 287 260 233 206 179  
386 359 333 307 280 254 227  
408 396 378 351 325 299 272  
330 304 278 251 224 197 170  
377 351 324 298 271 245 218  
393 382 369 343 316 290 263  
308 278 248 217 186  
-
-
299 269 239 208 177  
-
-
362 332 303 273 242 212 181  
414 385 355 325 296 266 236  
428 416 403 375 347 317 287  
353 323 293 264 233 203 172  
405 376 346 316 286 257 226  
412 400 388 367 338 308 278  
9000  
324 291 257 223 189  
-
-
315 282 248 214 180  
-
-
384 351 318 285 251 217 183  
444 410 377 344 310 277 244  
445 432 420 401 368 334 301  
375 342 309 275 242 208 174  
429 400 368 334 301 268 234  
429 416 404 391 358 325 292  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
19000  
20000  
340 303 266 229 191  
-
-
331 294 257 220 182  
-
-
407 370 333 296 259 222 184  
462 434 398 361 325 288 251  
462 447 434 421 388 352 315  
397 360 324 287 250 213 175  
445 425 389 352 315 279 242  
444 430 418 405 378 342 305  
356 316 275 235 193  
-
-
347 307 267 226 184  
-
-
428 388 348 308 268 227 185  
476 460 419 379 339 299 259  
476 462 447 434 408 368 328  
419 379 339 299 258 218 176  
457 444 409 370 329 290 249  
457 443 429 416 399 359 319  
372 328 285 240 196  
-
-
363 319 276 231 187  
-
-
450 407 363 320 276 232 187  
489 474 440 397 353 310 266  
488 474 459 444 428 385 341  
440 397 354 310 267 222 177  
469 455 429 387 343 300 256  
469 454 440 426 413 375 332  
387 341 294 246 198  
-
-
379 332 285 237 189  
-
-
471 425 378 331 284 236 188  
500 485 460 414 367 320 273  
500 484 469 455 440 402 354  
463 416 368 322 274 227 179  
480 465 449 405 357 311 263  
479 464 450 435 421 391 345  
403 353 303 252 200  
-
-
395 344 294 243 191  
-
-
491 443 392 342 292 241 189  
510 495 478 431 381 331 280  
510 494 479 464 448 416 368  
483 434 383 333 282 232 180  
489 474 460 421 371 321 270  
489 474 459 444 429 405 358  
419 366 312 257 202  
-
-
410 357 303 248 193  
-
-
511 461 407 354 300 245 190  
520 504 488 447 395 341 287  
519 503 487 472 456 430 380  
499 450 398 344 290 236 181  
498 482 468 434 385 331 277  
497 482 466 451 436 417 370  
435 378 321 263 205  
-
-
426 369 312 254 195  
-
-
529 478 422 365 308 250 191  
528 512 496 458 408 351 294  
527 511 495 479 463 442 392  
507 465 413 355 298 241 182  
506 490 474 450 398 341 284  
506 489 474 458 443 428 381  
451 390 330 269 206  
-
-
443 381 321 260 197  
-
-
536 492 436 376 316 254 192  
536 519 503 472 421 361 301  
535 518 502 486 469 453 403  
514 480 424 367 306 245 183  
513 497 481 465 409 352 291  
513 496 480 464 448 433 390  
467 403 339 274 209  
-
-
458 394 330 265 200  
-
-
543 505 448 387 324 259 194  
543 526 509 486 432 371 308  
542 525 508 492 475 459 409  
521 496 437 376 314 249 184  
520 503 487 471 420 361 298  
519 503 486 470 454 438 399  
481 415 348 280 211  
-
-
471 405 339 271 202  
-
-
550 524 461 399 331 263 194  
549 532 515 498 439 380 315  
548 531 514 497 481 464 423  
527 510 448 386 321 254 185  
526 509 493 476 429 369 305  
525 509 492 476 459 443 408  
42  
Johnson Controls Unitary Products  
246653-YTG-E-0108  
TABLE 35: COOLING PERFORMANCE 40 TON HIGH CAPACITY COIL (CONTINUED)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON EVAPORATOR COIL  
115°F  
125°F  
2
2
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
SENSIBLE CAPACITY (MBH)  
RETURN DRY BULB (°F)  
TOTAL  
CAP.  
(MBH)  
TOTAL  
INPUT  
(KW)  
TOTAL  
CAP.  
(MBH)  
TOTAL  
WB  
(°F)  
1
1
CFM  
8000  
INPUT  
(KW)  
86 83 80 77 74 71 68  
86 83 80 77 74 71 68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
453  
417  
384  
378  
464  
428  
396  
396  
472  
438  
412  
412  
478  
446  
427  
426  
484  
451  
438  
438  
490  
457  
449  
449  
494  
464  
459  
459  
499  
469  
468  
468  
502  
477  
476  
476  
505  
485  
483  
483  
508  
491  
490  
489  
511  
497  
496  
496  
513  
502  
502  
501  
60.3  
59.0  
57.7  
56.7  
60.7  
59.4  
57.9  
57.3  
60.7  
59.4  
58.2  
57.9  
61.0  
59.7  
58.9  
58.3  
61.5  
59.9  
59.0  
58.8  
61.6  
60.1  
59.2  
59.1  
61.8  
60.5  
59.5  
59.5  
61.9  
60.4  
59.8  
59.5  
62.1  
60.8  
60.1  
59.8  
62.2  
60.7  
60.0  
60.0  
62.3  
61.1  
60.2  
60.2  
62.3  
61.1  
60.5  
60.4  
62.4  
61.0  
60.6  
60.6  
274 247 220 193 166  
-
-
431  
397  
367  
363  
442  
408  
377  
380  
448  
417  
394  
396  
453  
423  
410  
408  
458  
428  
419  
419  
465  
431  
429  
430  
468  
441  
439  
438  
473  
445  
447  
447  
475  
455  
454  
454  
478  
463  
461  
462  
481  
469  
467  
467  
484  
475  
473  
473  
486  
479  
479  
478  
65.9  
64.4  
63.0  
61.8  
66.1  
64.9  
63.3  
62.7  
66.5  
64.8  
63.6  
63.2  
66.8  
65.2  
64.2  
63.9  
67.4  
65.4  
64.4  
64.3  
67.4  
65.6  
64.8  
64.4  
67.7  
66.0  
65.0  
64.8  
67.7  
66.0  
65.5  
64.9  
67.9  
66.3  
65.6  
65.1  
68.0  
66.2  
65.4  
65.3  
68.1  
66.8  
65.6  
65.5  
68.2  
66.8  
65.8  
65.7  
68.3  
67.0  
66.3  
66.2  
266 238 211 184 157  
-
-
321 295 269 242 215 188 161  
367 342 315 288 262 236 209  
378 367 356 333 307 281 254  
312 286 260 233 206 179 152  
358 334 306 279 253 227 200  
363 353 347 325 298 272 245  
290 260 230 199 168  
-
-
281 251 221 190 159  
-
-
344 314 284 254 224 194 163  
396 367 337 307 277 247 217  
396 384 373 358 328 298 268  
335 305 274 245 215 185 154  
387 358 328 298 267 238 207  
380 368 358 350 319 289 259  
9000  
306 273 239 205 171  
-
-
297 264 230 196 162  
-
-
366 333 300 266 233 199 164  
412 391 358 325 292 258 225  
412 400 387 375 348 316 282  
357 324 291 256 224 190 155  
397 381 349 315 283 249 215  
396 384 371 365 338 307 273  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
19000  
20000  
322 285 248 211 173  
-
-
313 276 239 202 164  
-
-
388 351 315 278 241 203 166  
427 413 379 342 306 269 232  
426 413 400 387 369 332 296  
378 341 306 269 232 194 157  
410 404 370 333 296 260 223  
408 396 384 371 359 322 286  
338 298 258 217 175  
-
-
329 289 250 208 166  
-
-
409 370 329 289 249 208 167  
438 425 400 360 320 280 239  
438 425 411 398 385 349 309  
400 361 320 280 239 199 158  
419 409 390 351 310 271 229  
419 406 393 380 376 340 300  
354 310 267 222 178  
-
-
345 301 258 213 169  
-
-
431 388 344 301 257 213 168  
449 436 420 377 334 290 247  
449 435 421 408 394 365 322  
421 378 335 291 248 203 158  
429 417 409 367 324 280 237  
430 415 402 390 379 355 313  
370 323 276 228 180  
-
-
362 314 267 219 171  
-
-
453 406 359 312 265 217 169  
459 445 431 394 348 301 254  
459 444 431 416 402 380 335  
445 397 349 303 255 208 160  
439 425 420 385 338 292 244  
438 424 412 396 383 369 326  
386 335 285 234 182  
-
-
378 326 276 225 173  
-
-
469 424 374 324 273 222 169  
468 453 439 408 361 311 260  
468 453 438 424 410 395 348  
461 415 365 315 263 213 160  
447 432 421 398 351 301 250  
447 433 418 404 391 384 338  
402 348 294 239 184  
-
-
393 339 285 230 175  
-
-
477 442 389 335 281 227 170  
476 461 446 425 373 321 267  
476 460 445 430 416 402 359  
465 431 380 325 271 218 161  
454 439 426 412 363 311 257  
454 439 424 409 396 389 349  
418 360 303 245 186  
-
-
409 351 294 236 176  
-
-
485 455 404 346 289 231 171  
483 468 453 438 385 330 274  
483 467 452 437 422 407 368  
463 442 395 336 279 222 162  
461 446 431 430 375 320 264  
462 445 431 416 402 393 357  
432 372 312 251 189  
-
-
424 363 303 242 180  
-
-
491 472 414 357 297 235 172  
490 474 458 444 398 339 281  
489 474 458 442 427 412 380  
469 460 402 348 287 226 163  
467 452 436 437 386 330 271  
467 452 436 420 406 392 367  
446 385 321 256 190  
-
-
437 376 312 247 181  
-
-
497 481 428 367 305 240 174  
496 480 464 449 408 348 288  
496 479 464 448 432 417 389  
475 472 417 356 295 230 164  
473 457 442 434 396 338 278  
473 457 442 426 411 396 379  
460 396 330 262 193  
-
-
450 386 321 253 184  
-
-
502 486 441 376 311 244 175  
502 485 469 453 420 356 294  
501 485 469 453 437 421 399  
479 472 428 363 301 235 166  
479 462 447 431 410 345 284  
478 463 447 432 415 400 384  
1.  
2.  
The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat *MBh = 3.415 x kW). Refer to the  
appropriate Blower Performance table for the kW of the supply air blower motor.  
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.  
Johnson Controls Unitary Products  
43  
246653-YTG-E-0108  
order to use the indoor blower tables for high altitude applica-  
tions, certain corrections are necessary.  
CFM, STATIC PRESSURE, AND POWER - ALTI-  
TUDE AND TEMPERATURE CORRECTIONS  
A centrifugal fan is a "constant volume" device. This means  
that, if the rpm remains constant, the CFM delivered is the  
same regardless of the density of the air. However, since the  
air at high altitude is less dense, less static pressure will be  
generated and less power will be required than a similar  
application at sea level. Air density correction factors are  
shown in Table 36 and Figure 21.  
The information below should be used to assist in application  
of product when being applied at altitudes at or exceeding  
1000 feet above sea level.  
The air flow rates listed in the standard blower performance  
tables are based on standard air at sea level. As the altitude  
or temperature increases, the density of air decreases. In  
TABLE 36: ALTITUDE CORRECTION FACTORS  
ALTITUDE (FEET)  
AIR TEMP  
0
1000  
1.022  
1.002  
0.982  
0.964  
0.947  
0.929  
0.912  
2000  
0.986  
0.966  
0.948  
0.930  
0.913  
0.897  
0.880  
3000  
0.950  
0.931  
0.913  
0.896  
0.880  
0.864  
0.848  
4000  
0.916  
0.898  
0.880  
0.864  
0.848  
0.833  
0.817  
5000  
0.882  
0.864  
0.848  
0.832  
0.817  
0.802  
0.787  
6000  
0.849  
0.832  
0.816  
0.801  
0.787  
0.772  
0.758  
7000  
0.818  
0.802  
0.787  
0.772  
0.758  
0.744  
0.730  
8000  
0.788  
0.772  
0.757  
0.743  
0.730  
0.716  
0.703  
9000  
0.758  
0.743  
0.729  
0.715  
0.702  
0.689  
0.676  
10000  
0.729  
0.715  
0.701  
0.688  
0.676  
0.663  
0.651  
40  
50  
1.060  
1.039  
1.019  
1.000  
0.982  
0.964  
0.946  
60  
70  
80  
90  
100  
The examples below will assist in determining the airflow per-  
formance of the product at altitude.  
blower tables to select the blower speed and the BHP  
requirement.  
Example 1: What are the corrected CFM, static pressure,  
and BHP at an elevation of 5,000 ft. if the blower performance  
data is 6,000 CFM, 1.5 IWC and 4.0 BHP?  
Solution: As in the example above, no temperature informa-  
tion is given so 70°F is assumed.  
The 1.5" static pressure given is at an elevation of 5,000 ft.  
The first step is to convert this static pressure to equivalent  
sea level conditions.  
Solution: At an elevation of 5,000 ft the indoor blower will still  
deliver 6,000 CFM if the rpm is unchanged. However, Table  
36 must be used to determine the static pressure and BHP.  
Since no temperature data is given, we will assume an air  
temperature of 70°F. Table 36 shows the correction factor to  
be 0.832.  
Sea level static pressure = 1.5 / .832 = 1.80"  
Enter the blower table at 6000 sCFM and static pressure of  
1.8". The rpm listed will be the same rpm needed at 5,000 ft.  
Corrected static pressure = 1.5 x 0.832 = 1.248 IWC  
Corrected BHP = 4.0 x 0.832 = 3.328  
Suppose that the corresponding BHP listed in the table is 3.2.  
This value must be corrected for elevation.  
Example 2: A system, located at 5,000 feet of elevation, is to  
BHP at 5,000 ft = 3.2 x .832 = 2.66  
deliver 6,000 CFM at a static pressure of 1.5". Use the unit  
44  
Johnson Controls Unitary Products  
   
246653-YTG-E-0108  
FIGURE 21 - ALTITUDE/TEMPERATURE CONVERSION FACTOR  
Johnson Controls Unitary Products  
45  
 
246653-YTG-E-0108  
1, 2  
TABLE 37: FAN PERFORMANCE - 25 TON  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
0.6 0.8  
0.2  
1.2  
2.2  
3.2  
0.4  
1.4  
2.4  
3.4  
1.0  
2.0  
3.0  
4.0  
AIRFLOW CFM  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
-
BHP  
BHP  
0.9  
1.1  
1.5  
2.0  
2.6  
3.4  
4.3  
5.4  
6.7  
8.1  
BHP  
1.1  
1.4  
1.8  
2.3  
2.9  
3.8  
4.7  
5.8  
7.1  
8.6  
BHP  
1.4  
1.7  
2.1  
2.7  
3.3  
4.2  
5.1  
6.3  
7.5  
9.1  
4000  
5000  
-
342  
362  
387  
415  
446  
480  
514  
550  
585  
622  
0.6  
0.9  
1.2  
1.7  
2.3  
3.0  
3.9  
5.0  
6.3  
7.7  
404  
415  
433  
456  
484  
514  
545  
579  
612  
647  
456  
465  
478  
497  
520  
547  
576  
608  
638  
671  
506  
512  
521  
535  
555  
579  
606  
635  
664  
696  
306  
337  
370  
408  
444  
481  
520  
557  
596  
0.7  
1.0  
1.4  
2.0  
2.7  
3.6  
4.6  
5.8  
7.2  
6000  
7000  
8000  
9000  
10000  
11000  
12000  
13000  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
1.6 1.8  
AIRFLOW CFM  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
1.7  
2.1  
2.5  
3.0  
3.7  
4.6  
5.5  
6.7  
8.0  
9.6  
BHP  
2.0  
2.4  
2.9  
3.4  
4.1  
5.0  
6.0  
7.2  
8.5  
BHP  
2.3  
2.8  
3.3  
3.9  
4.6  
5.4  
6.4  
7.6  
9.0  
BHP  
2.7  
3.2  
3.7  
4.3  
5.0  
5.9  
6.9  
8.1  
9.5  
BHP  
3.0  
3.5  
4.1  
4.7  
5.4  
6.4  
7.4  
8.6  
4000  
5000  
549  
555  
562  
573  
591  
611  
634  
662  
690  
720  
591  
597  
602  
610  
624  
642  
663  
689  
714  
743  
628  
634  
638  
645  
657  
673  
692  
715  
739  
766  
663  
670  
674  
679  
689  
703  
719  
741  
763  
789  
698  
705  
709  
713  
720  
732  
747  
766  
787  
811  
6000  
7000  
8000  
9000  
10000  
11000  
12000  
13000  
10.0  
11.8  
10.1  
10.6  
11.2  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
2.6 2.8  
AIRFLOW CFM  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
3.3  
3.9  
4.5  
5.2  
6.0  
6.9  
7.9  
9.2  
BHP  
3.7  
BHP  
4.1  
4.7  
5.4  
6.1  
7.0  
7.9  
9.0  
BHP  
4.4  
BHP  
4.8  
4000  
5000  
728  
736  
740  
744  
751  
760  
774  
792  
811  
833  
757  
767  
772  
775  
781  
789  
801  
817  
834  
855  
787  
798  
803  
805  
810  
817  
826  
841  
857  
877  
814  
825  
830  
833  
837  
843  
852  
865  
880  
899  
839  
851  
858  
861  
865  
870  
878  
890  
903  
921  
4.3  
5.1  
5.5  
6000  
5.0  
5.9  
6.3  
7000  
5.6  
6.6  
7.1  
8000  
6.5  
7.5  
8.0  
9000  
7.4  
8.4  
9.0  
10000  
11000  
12000  
13000  
8.4  
9.5  
10.1  
11.4  
13.0  
14.7  
9.7  
10.2  
11.8  
13.5  
10.8  
12.4  
14.1  
10.6  
12.3  
11.2  
12.9  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
3.6 3.8  
AIRFLOW CFM  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
5.1  
BHP  
5.5  
BHP  
5.9  
6.8  
7.7  
8.7  
9.6  
BHP  
6.3  
BHP  
6.7  
4000  
5000  
864  
878  
885  
889  
892  
897  
903  
913  
926  
942  
890  
904  
911  
914  
918  
921  
927  
936  
948  
963  
913  
927  
935  
939  
942  
946  
951  
959  
970  
984  
935  
950  
959  
964  
967  
970  
975  
983  
992  
1005  
957  
973  
6.0  
6.4  
7.3  
7.7  
6000  
6.8  
7.3  
8.2  
983  
8.7  
7000  
7.6  
8.1  
9.2  
988  
9.7  
8000  
8.5  
9.1  
10.2  
11.3  
12.6  
14.0  
15.4  
17.3  
992  
10.8  
11.9  
13.2  
14.6  
16.1  
18.0  
9000  
9.5  
10.1  
11.3  
12.7  
14.2  
15.9  
10.7  
11.9  
13.3  
14.8  
16.6  
995  
10000  
11000  
12000  
13000  
10.7  
12.1  
13.6  
15.3  
999  
1005  
1013  
1025  
1.  
Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.  
Refer to Tables 10, 15, 21 and 42 for component additions and deductions to fan performance tables.  
BHP includes drive losses.  
2.  
3.  
4. Shaded RPMs require Class II blower.  
46  
Johnson Controls Unitary Products  
 
246653-YTG-E-0108  
25 Ton Forward Curve  
8.0  
7.5  
7.0  
6.5  
6.0  
5.5  
5.0  
4.5  
4.0  
3.5  
3.0  
2.5  
2.0  
1.5  
1.0  
0.5  
0.0  
5
00  
A
0
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
CFM (x1000)  
A - Standard Unit  
Note: Standard Unit includes wet evaporator coil, clean 2" throwaway filters, system  
and cabinet effects at standard air density and 0' elevation.  
FIGURE 22 - FAN PERFORMANCE - 25 TON  
Johnson Controls Unitary Products  
47  
 
246653-YTG-E-0108  
1, 2  
0.4  
TABLE 38: FAN PERFORMANCE - 30 TON  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
0.6  
0.2  
1.2  
2.2  
3.2  
0.8  
1.8  
2.8  
3.8  
1.0  
2.0  
3.0  
4.0  
AIRFLOW (CFM)  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
0.9  
1.4  
1.9  
2.6  
3.4  
4.4  
5.7  
7.1  
8.8  
BHP  
1.2  
1.7  
2.2  
2.9  
3.9  
4.9  
6.2  
7.7  
9.3  
BHP  
1.6  
2.0  
2.6  
3.4  
4.3  
5.4  
6.7  
8.2  
BHP  
1.9  
2.3  
3.0  
3.8  
4.7  
5.9  
7.2  
8.8  
BHP  
2.2  
2.7  
3.5  
4.2  
5.3  
6.4  
7.8  
9.3  
6000  
7000  
321  
357  
398  
436  
477  
519  
560  
603  
645  
688  
373  
404  
437  
473  
511  
549  
589  
629  
669  
711  
422  
447  
477  
509  
543  
579  
617  
654  
694  
733  
469  
490  
515  
543  
575  
609  
643  
680  
718  
755.6  
513  
529  
551  
577  
606  
637  
670  
705  
741  
778  
8000  
9000  
10000  
11000  
12000  
13000  
14000  
15000  
10.0  
12.1  
10.5  
12.7  
11.2  
13.3  
10.7  
11.3  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
1.6  
1.4  
2.4  
3.4  
AIRFLOW (CFM)  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
2.5  
BHP  
2.9  
3.6  
4.3  
5.1  
6.3  
7.5  
8.9  
BHP  
3.4  
4.0  
4.7  
5.7  
6.8  
8.0  
9.6  
BHP  
3.7  
BHP  
4.1  
6000  
7000  
554  
568  
587  
610  
636  
665  
697  
729  
764  
800  
596  
607  
622  
642  
666  
693  
722  
753  
787  
821  
632  
642  
655  
673  
695  
720  
747  
777  
809  
842  
668  
676  
689  
704  
723  
746  
772  
801  
831  
863  
703  
710  
720  
734  
751  
773  
797  
824  
853  
884  
3.2  
4.4  
4.8  
8000  
3.9  
5.3  
5.7  
9000  
4.7  
6.2  
6.7  
10000  
11000  
12000  
13000  
14000  
15000  
5.8  
7.4  
7.9  
6.9  
8.6  
9.2  
8.3  
10.1  
11.9  
13.9  
16.0  
10.7  
12.5  
14.5  
16.7  
10.0  
11.9  
14.0  
10.5  
12.5  
14.6  
11.2  
13.2  
15.3  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
2.6  
AIRFLOW (CFM)  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
4.5  
BHP  
4.9  
5.8  
6.7  
7.8  
9.0  
BHP  
5.4  
6.3  
7.2  
8.3  
9.6  
BHP  
5.8  
BHP  
6.3  
6000  
7000  
734  
741  
750  
763  
779  
799  
821  
847  
874  
904  
765  
772  
781  
792  
807  
824  
845  
869  
896  
924  
796  
803  
810  
820  
833  
849  
869  
892  
917  
944  
824  
830  
837  
847  
859  
874  
893  
914  
938  
964  
850  
858  
865  
873  
885  
899  
916  
936  
959  
984  
5.3  
6.7  
7.2  
8000  
6.2  
7.8  
8.3  
9000  
7.2  
8.9  
9.5  
10000  
11000  
12000  
13000  
14000  
15000  
8.4  
10.2  
11.7  
13.3  
15.2  
17.3  
19.7  
10.8  
12.3  
14.1  
15.9  
18.1  
20.5  
9.8  
10.4  
12.1  
13.9  
15.9  
18.3  
11.0  
12.7  
14.6  
16.6  
19.0  
11.3  
13.2  
15.2  
17.4  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
3.6  
AIRFLOW (CFM)  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
6.7  
BHP  
7.1  
BHP  
7.7  
BHP  
8.1  
BHP  
8.6  
6000  
7000  
877  
885  
892  
900  
910  
923  
939  
958  
980  
1004  
904  
911  
928  
935  
951  
959  
975  
984  
7.7  
8.2  
8.7  
9.2  
9.7  
8000  
8.8  
917  
925  
934  
946  
961  
980  
1001  
1023  
9.3  
942  
9.9  
966  
10.4  
11.8  
13.3  
14.9  
16.8  
18.8  
21.1  
23.6  
991  
10.9  
12.4  
14.0  
15.5  
17.5  
19.5  
21.8  
24.5  
9000  
10.0  
11.4  
13.0  
14.7  
16.6  
18.8  
21.2  
10.6  
12.1  
13.7  
15.3  
17.3  
19.6  
22.1  
949  
11.1  
12.7  
14.3  
16.1  
18.1  
20.4  
22.9  
974  
998  
10000  
11000  
12000  
13000  
14000  
15000  
958  
982  
1006  
1015  
1028  
1043  
1060  
1081  
970  
993  
984  
1006  
1022  
1040  
1062  
1001  
1021  
1043  
1.  
Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.  
Refer to Tables 10, 15, 21 and 42 for component additions and deductions to fan performance tables.  
BHP includes drive losses.  
2.  
3.  
4. Shaded RPMs require Class II blower.  
48  
Johnson Controls Unitary Products  
 
246653-YTG-E-0108  
30 Ton Forward Curve  
8.0  
7.5  
7.0  
6.5  
6.0  
5.5  
5.0  
4.5  
4.0  
3.5  
3.0  
2.5  
2.0  
1.5  
1.0  
0.5  
0.0  
A
0
2
4
6
8
10  
12  
14  
16  
18  
20  
CFM (x1000)  
A - Standard Unit  
Note: Standard Unit includes wet evaporator coil, clean 2" throwaway filters, system  
and cabinet effects at standard air density and 0' elevation.  
FIGURE 23 - FAN PERFORMANCE - 30 TON  
Johnson Controls Unitary Products  
49  
 
246653-YTG-E-0108  
1,2  
TABLE 39: FAN PERFORMANCE - 40 TON  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
0.6  
0.2  
1.2  
2.2  
3.2  
0.4  
0.8  
1.8  
2.8  
3.8  
1.0  
2.0  
3.0  
4.0  
AIRFLOW (CFM)  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
1.4  
1.9  
2.4  
3.0  
3.9  
4.8  
6.0  
7.2  
8.7  
BHP  
1.8  
2.3  
2.8  
3.6  
4.5  
5.5  
6.6  
8.0  
9.5  
BHP  
2.2  
2.7  
3.4  
4.1  
5.0  
6.1  
7.2  
8.6  
BHP  
2.6  
3.2  
3.9  
4.7  
5.7  
6.7  
8.0  
9.3  
BHP  
3.0  
3.7  
4.4  
5.3  
6.2  
7.4  
8.6  
8000  
9000  
304  
329  
356  
385  
414  
442  
472  
503  
532  
562  
593  
348  
371  
396  
421  
446  
473  
502  
529  
557  
587  
616  
393  
411  
432  
454  
479  
504  
529  
555  
583  
611  
638  
431  
448  
467  
488  
510  
532  
556  
581  
607  
633  
660  
469  
484  
502  
519  
539  
560  
583  
607  
631  
656  
682  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
10.1  
11.8  
13.5  
15.4  
10.2  
12.0  
13.9  
10.9  
12.7  
14.7  
10.4  
12.3  
11.1  
13.1  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
1.6  
1.4  
2.4  
3.4  
AIRFLOW (CFM)  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
3.5  
4.2  
4.9  
5.8  
6.8  
8.0  
9.3  
BHP  
4.0  
4.6  
5.5  
6.4  
7.5  
8.6  
BHP  
4.4  
5.1  
6.1  
7.0  
8.1  
9.3  
BHP  
4.9  
5.8  
6.6  
7.6  
BHP  
5.5  
8000  
9000  
506  
518  
532  
549  
568  
588  
609  
631  
654  
678  
703  
537  
549  
563  
579  
596  
614  
634  
655  
677  
701  
724  
569  
581  
594  
608  
623  
640  
658  
679  
700  
722  
744  
601  
610  
621  
634  
649  
665  
683  
702  
722  
742  
764  
627  
637  
648  
661  
675  
690  
707  
724  
743  
763  
785  
6.3  
7.1  
8.2  
9.5  
10.7  
12.2  
13.9  
15.6  
17.6  
19.8  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
8.7  
10.0  
11.4  
13.1  
14.8  
16.8  
19.0  
10.0  
11.6  
13.2  
15.1  
17.2  
10.7  
12.3  
14.1  
16.0  
18.1  
10.8  
12.5  
14.3  
16.4  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
2.6  
AIRFLOW (CFM)  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
6.0  
6.8  
7.8  
8.8  
BHP  
6.5  
7.4  
8.4  
9.5  
BHP  
7.0  
8.0  
BHP  
7.6  
8.5  
BHP  
8.1  
8000  
9000  
654  
664  
675  
687  
700  
714  
729  
746  
764  
784  
805  
681  
691  
701  
712  
723  
737  
752  
768  
786  
805  
824  
706  
715  
725  
735  
747  
760  
774  
790  
807  
824  
843  
729  
738  
748  
758  
770  
782  
796  
811  
826  
843  
862  
752  
761  
771  
781  
793  
805  
817  
831  
846  
863  
881  
9.1  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
9.0  
9.6  
10.2  
11.4  
12.9  
14.4  
16.0  
17.9  
19.8  
22.1  
24.5  
10.2  
11.4  
12.9  
14.5  
16.2  
18.2  
20.3  
22.6  
10.8  
12.2  
13.7  
15.2  
17.0  
19.0  
21.1  
23.5  
10.1  
11.4  
13.0  
14.6  
16.5  
18.5  
20.7  
10.7  
12.2  
13.8  
15.4  
17.3  
19.4  
21.6  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
3.6  
AIRFLOW (CFM)  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
8.7  
9.8  
BHP  
BHP  
BHP  
10.4  
11.6  
12.9  
14.3  
15.8  
17.4  
19.2  
21.2  
23.3  
25.7  
-
BHP  
11.0  
12.2  
13.5  
14.9  
16.5  
18.2  
20.1  
22.1  
24.3  
-
8000  
9000  
774  
784  
794  
804  
814  
825  
837  
851  
866  
882  
900  
797  
806  
815  
824  
835  
846  
858  
871  
886  
901  
-
9.2  
817  
826  
836  
845  
855  
866  
878  
891  
905  
919  
-
9.9  
837  
846  
856  
865  
876  
886  
898  
910  
923  
937  
-
857  
866  
876  
886  
896  
906  
917  
928  
941  
-
10.3  
11.6  
12.8  
14.3  
15.9  
17.6  
19.5  
21.5  
23.8  
-
10.9  
12.2  
13.5  
15.0  
16.6  
18.4  
20.4  
22.5  
24.8  
-
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
10.8  
12.2  
13.5  
15.1  
16.8  
18.7  
20.7  
23.0  
25.4  
-
-
1.  
Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.  
Refer to Tables 12, 18, 23 and 42 for component additions and deductions to fan performance tables.  
BHP includes drive losses.  
2.  
3.  
4. Shaded RPMs require Class II blower.  
50  
Johnson Controls Unitary Products  
 
246653-YTG-E-0108  
40 Ton Forward Curve  
7.0  
6.5  
6.0  
5.5  
5.0  
4.5  
4.0  
3.5  
3.0  
2.5  
2.0  
1.5  
1.0  
0.5  
0.0  
A
300  
0
2
4
6
8
10  
12  
14  
16  
18  
20  
CFM (x1000)  
A - Standard Unit  
Note: Standard Unit includes wet evaporator coil, clean 2" throwaway filters, system  
and cabinet effects at standard air density and 0' elevation.  
FIGURE 24 - FAN PERFORMANCE - 40 TON  
Johnson Controls Unitary Products  
51  
 
246653-YTG-E-0108  
1,2  
TABLE 40: FAN PERFORMANCE - 25 & 30 TON AIRFOIL  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
0.6  
0.2  
1.2  
2.2  
3.2  
0.4  
1.4  
2.4  
3.4  
0.8  
1.8  
2.8  
3.8  
1.0  
2.0  
3.0  
4.0  
AIRFLOW (CFM)  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
0.3  
0.6  
0.9  
1.3  
1.9  
2.7  
3.6  
4.7  
6.0  
7.6  
9.4  
BHP  
0.5  
0.7  
1.1  
1.6  
2.2  
2.9  
3.9  
5.0  
6.4  
7.9  
9.8  
BHP  
0.6  
0.9  
1.3  
1.8  
2.4  
3.2  
4.2  
5.3  
6.7  
8.3  
BHP  
0.8  
1.1  
1.5  
2.0  
2.7  
3.5  
4.5  
5.7  
7.1  
8.7  
BHP  
1.0  
1.3  
1.7  
2.3  
2.9  
3.8  
4.8  
6.1  
7.5  
9.1  
4000  
5000  
595  
709  
667  
769  
735  
827  
800  
882  
862  
935  
6000  
827  
879  
929  
977  
1024  
1122  
1227  
1336  
1449  
1565  
1682  
1802  
1922  
2043  
7000  
948  
995  
1038  
1151  
1268  
1387  
1508  
1629  
1752  
1875  
2000  
1081  
1190  
1303  
1418  
1536  
1656  
1777  
1899  
2022  
8000  
1072  
1197  
1322  
1447  
1574  
1701  
1828  
1955  
1113  
1233  
1354  
1478  
1602  
1726  
1852  
1978  
9000  
10000  
11000  
12000  
13000  
14000  
15000  
10.2  
12.4  
10.6  
12.8  
11.1  
13.2  
11.5  
11.9  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
1.6  
AIRFLOW (CFM)  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
1.1  
1.5  
1.9  
2.5  
3.2  
4.1  
5.1  
6.4  
7.8  
9.6  
11.5  
13.7  
BHP  
1.3  
1.7  
2.2  
2.8  
3.5  
4.4  
5.5  
6.8  
8.2  
BHP  
1.5  
1.9  
2.4  
3.0  
3.8  
4.7  
5.8  
7.1  
8.6  
BHP  
1.7  
BHP  
1.9  
4000  
5000  
921  
978  
1032  
1087  
1158  
1241  
1335  
1434  
1539  
1648  
1760  
1874  
1990  
2107  
1085  
1134  
1201  
1280  
1369  
1466  
1569  
1675  
1785  
1898  
2012  
2128  
1135  
1180  
1242  
1318  
1404  
1498  
1598  
1702  
1810  
1921  
2034  
2149  
988  
1037  
1114  
1203  
1300  
1403  
1510  
1621  
1734  
1850  
1967  
2086  
2.1  
2.4  
6000  
1070  
1163  
1263  
1370  
1480  
1593  
1709  
1826  
1944  
2065  
2.7  
2.9  
7000  
3.3  
3.6  
8000  
4.1  
4.4  
9000  
5.0  
5.4  
10000  
11000  
12000  
13000  
14000  
15000  
6.2  
6.5  
7.5  
7.8  
9.0  
9.4  
10.0  
11.9  
14.2  
10.4  
12.4  
14.7  
10.8  
12.8  
15.1  
11.2  
13.3  
15.6  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
2.6  
AIRFLOW (CFM)  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
2.2  
BHP  
2.4  
2.9  
3.4  
4.1  
5.0  
6.0  
7.2  
8.6  
BHP  
2.6  
3.1  
3.7  
4.4  
5.3  
6.4  
7.6  
9.0  
BHP  
2.8  
BHP  
3.1  
4000  
5000  
1184  
1225  
1283  
1355  
1438  
1529  
1626  
1728  
1835  
1944  
2055  
2169  
1231  
1269  
1323  
1392  
1471  
1559  
1654  
1755  
1859  
1967  
2077  
2190  
1277  
1312  
1362  
1427  
1504  
1590  
1683  
1781  
1884  
1990  
2099  
2210  
1321  
1353  
1402  
1463  
1537  
1620  
1710  
1807  
1908  
2012  
2120  
2230  
1364  
1395  
1439  
1498  
1569  
1649  
1738  
1832  
1932  
2035  
2141  
2250  
2.6  
3.4  
3.6  
6000  
3.2  
4.0  
4.3  
7000  
3.9  
4.7  
5.0  
8000  
4.7  
5.7  
6.0  
9000  
5.7  
6.7  
7.1  
10000  
11000  
12000  
13000  
14000  
15000  
6.9  
7.9  
8.3  
8.2  
9.4  
9.8  
9.8  
10.2  
12.1  
14.2  
16.6  
10.6  
12.5  
14.7  
17.1  
11.1  
13.0  
15.1  
17.6  
11.5  
13.4  
15.6  
18.1  
11.7  
13.7  
16.1  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
3.6  
AIRFLOW (CFM)  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
3.3  
BHP  
3.6  
4.2  
4.9  
5.7  
6.7  
7.8  
9.1  
BHP  
3.8  
4.4  
5.1  
6.0  
7.0  
8.1  
9.5  
BHP  
4.1  
BHP  
4.4  
4000  
5000  
1407  
1434  
1476  
1532  
1601  
1679  
1765  
1858  
1955  
2057  
2162  
2270  
1447  
1473  
1513  
1566  
1632  
1708  
1792  
1883  
1979  
2079  
2183  
2290  
1487  
1512  
1549  
1600  
1663  
1737  
1819  
1908  
2003  
2102  
2204  
2310  
1525  
1549  
1584  
1633  
1694  
1765  
1846  
1933  
2026  
2123  
2225  
2329  
1563  
1586  
1619  
1666  
1724  
1794  
1872  
1957  
2049  
2145  
2245  
2348  
3.9  
4.7  
5.0  
6000  
4.6  
5.5  
5.8  
7000  
5.4  
6.3  
6.7  
8000  
6.3  
7.3  
7.7  
9000  
7.4  
8.5  
8.9  
10000  
11000  
12000  
13000  
14000  
15000  
8.7  
9.9  
10.3  
11.9  
13.7  
15.7  
18.1  
20.6  
10.2  
11.9  
13.9  
16.1  
18.6  
10.6  
12.4  
14.3  
16.6  
19.1  
11.0  
12.8  
14.8  
17.1  
19.6  
11.4  
13.2  
15.2  
17.6  
20.1  
52  
Johnson Controls Unitary Products  
 
246653-YTG-E-0108  
1,2  
TABLE 40: FAN PERFORMANCE - 25 & 30 TON AIRFOIL (CONTINUED)  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
4.2  
4.4  
4.6  
4.8  
5.0  
AIRFLOW (CFM)  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
4.6  
5.3  
6.1  
7.0  
8.0  
9.3  
BHP  
4.9  
5.6  
6.4  
7.3  
8.4  
9.7  
BHP  
5.2  
5.9  
6.7  
7.7  
8.8  
BHP  
5.5  
6.2  
7.0  
8.0  
9.1  
BHP  
5.8  
4000  
5000  
1601  
1621  
1653  
1698  
1754  
1822  
1898  
1982  
2072  
2167  
2265  
2368  
1636  
1656  
1687  
1730  
1784  
1850  
1924  
2006  
2095  
2188  
2286  
2387  
1672  
1691  
1720  
1761  
1814  
1877  
1950  
2030  
2117  
2210  
2306  
2406  
1707  
1725  
1753  
1792  
1843  
1905  
1976  
2054  
2140  
2231  
2326  
2425  
1740  
1758  
1785  
1822  
1872  
1932  
2001  
2078  
2162  
2252  
2346  
2444  
6.5  
6000  
7.4  
7000  
8.4  
8000  
9.5  
9000  
10.0  
11.5  
13.1  
15.0  
17.2  
19.6  
22.2  
10.4  
11.9  
13.6  
15.5  
17.7  
20.1  
22.8  
10.8  
12.3  
14.0  
15.9  
18.2  
20.6  
23.3  
10000  
11000  
12000  
13000  
14000  
15000  
10.7  
12.3  
14.1  
16.2  
18.6  
21.1  
11.1  
12.7  
14.6  
16.7  
19.1  
21.7  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
5.6  
5.2  
5.4  
5.8  
6.0  
AIRFLOW (CFM)  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
6.1  
BHP  
6.4  
BHP  
6.7  
BHP  
7.0  
BHP  
7.3  
4000  
5000  
1774  
1791  
1817  
1853  
1901  
1958  
2026  
2102  
2185  
2273  
2366  
2463  
1807  
1823  
1847  
1883  
1928  
1985  
2051  
2126  
2207  
2294  
2386  
2482  
1838  
1855  
1878  
1912  
1956  
2012  
2076  
2149  
2229  
2315  
2406  
2501  
1870  
1886  
1909  
1941  
1984  
2038  
2101  
2172  
2251  
2336  
2425  
1902  
1917  
1938  
1970  
2012  
2064  
2125  
2196  
2273  
2356  
2445  
6.8  
7.1  
7.5  
7.8  
8.1  
6000  
7.7  
8.0  
8.4  
8.7  
9.1  
7000  
8.7  
9.1  
9.4  
9.8  
10.2  
11.4  
12.8  
14.4  
16.3  
18.3  
20.6  
23.2  
8000  
9.9  
10.2  
11.6  
13.1  
14.9  
16.9  
19.1  
21.6  
24.4  
10.6  
12.0  
13.6  
15.3  
17.4  
19.6  
22.1  
24.9  
11.0  
12.4  
14.0  
15.8  
17.9  
20.1  
22.6  
9000  
11.2  
12.7  
14.5  
16.4  
18.6  
21.1  
23.8  
10000  
11000  
12000  
13000  
14000  
15000  
1.  
Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.  
Refer to Tables 10, 12, 15, 18, 21, 23 and 42 for component additions and deductions to fan performance tables.  
BHP includes drive losses.  
2.  
3.  
4. Shaded RPMs require Class II blower.  
Johnson Controls Unitary Products  
53  
246653-YTG-E-0108  
1,2  
TABLE 41: FAN PERFORMANCE - 40 TON AIRFOIL  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
0.6  
0.2  
1.2  
2.2  
0.4  
1.4  
2.4  
0.8  
1.8  
2.8  
1.0  
2.0  
3.0  
AIRFLOW (CFM)  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
1.4  
1.8  
2.5  
3.2  
4.1  
5.1  
6.3  
7.7  
9.2  
BHP  
1.6  
2.1  
2.8  
3.5  
4.5  
5.5  
6.8  
8.2  
9.8  
BHP  
1.9  
2.4  
3.1  
3.9  
4.8  
5.9  
7.2  
8.6  
BHP  
2.2  
2.7  
3.4  
4.3  
5.2  
6.4  
7.7  
9.1  
BHP  
2.4  
3.1  
3.8  
4.6  
5.6  
6.8  
8.1  
9.6  
8000  
9000  
769  
855  
814  
896  
856  
898  
937  
933  
971  
1008  
1081  
1157  
1236  
1316  
1397  
1479  
1563  
1647  
1732  
1817  
1903  
1989  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
19000  
20000  
21000  
22000  
941  
978  
1013  
1095  
1177  
1261  
1346  
1431  
1518  
1604  
1691  
1778  
1866  
1953  
2042  
1047  
1126  
1207  
1289  
1372  
1455  
1540  
1625  
1712  
1798  
1884  
1971  
1029  
1117  
1205  
1294  
1382  
1471  
1560  
1649  
1739  
1828  
1918  
2008  
1062  
1147  
1233  
1320  
1407  
1495  
1582  
1670  
1758  
1847  
1936  
2025  
10.3  
12.1  
14.2  
16.4  
19.0  
21.7  
24.8  
10.8  
12.6  
14.7  
17.1  
19.6  
22.4  
11.3  
13.2  
15.3  
17.7  
20.3  
23.1  
11.0  
13.0  
15.2  
17.7  
20.4  
23.4  
11.6  
13.6  
15.8  
18.3  
21.1  
24.1  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
1.6  
AIRFLOW (CFM)  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
2.7  
BHP  
3.0  
3.7  
4.5  
5.4  
6.5  
7.7  
9.1  
BHP  
3.3  
4.0  
4.8  
5.8  
6.9  
8.1  
9.5  
BHP  
3.6  
BHP  
4.0  
8000  
9000  
975  
1013  
1077  
1146  
1218  
1292  
1368  
1446  
1526  
1607  
1689  
1771  
1855  
1939  
2024  
1049  
1111  
1177  
1247  
1320  
1395  
1471  
1549  
1629  
1710  
1791  
1874  
1957  
1085  
1144  
1208  
1276  
1346  
1420  
1495  
1572  
1650  
1730  
1811  
1893  
1975  
1120  
1177  
1238  
1305  
1373  
1445  
1519  
1595  
1672  
1750  
1830  
1911  
1993  
1043  
1114  
1188  
1264  
1342  
1422  
1503  
1585  
1668  
1751  
1836  
1921  
2007  
3.4  
4.4  
4.7  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
19000  
20000  
21000  
22000  
4.1  
5.2  
5.6  
5.0  
6.2  
6.6  
6.1  
7.3  
7.7  
7.2  
8.6  
9.0  
8.6  
10.0  
11.6  
13.4  
15.4  
17.7  
20.1  
22.9  
10.5  
12.1  
14.0  
16.0  
18.3  
20.8  
23.5  
10.1  
11.8  
13.8  
15.9  
18.3  
20.9  
23.8  
10.6  
12.4  
14.3  
16.5  
18.9  
21.5  
24.5  
11.1  
12.9  
14.9  
17.1  
19.5  
22.2  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
2.6  
AIRFLOW (CFM)  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
4.3  
BHP  
4.6  
5.4  
6.3  
7.4  
8.6  
9.9  
BHP  
4.9  
5.8  
6.7  
7.8  
9.0  
BHP  
5.3  
BHP  
5.6  
8000  
9000  
1154  
1209  
1268  
1332  
1400  
1470  
1542  
1617  
1693  
1770  
1849  
1929  
2010  
1188  
1240  
1298  
1359  
1425  
1494  
1565  
1638  
1714  
1791  
1868  
1947  
2027  
1220  
1270  
1326  
1387  
1451  
1518  
1588  
1660  
1734  
1810  
1887  
1965  
1252  
1301  
1355  
1414  
1476  
1542  
1611  
1682  
1755  
1830  
1906  
1984  
1284  
1330  
1383  
1440  
1502  
1566  
1633  
1704  
1775  
1849  
1925  
2002  
5.0  
6.1  
6.5  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
19000  
20000  
6.0  
7.1  
7.5  
7.0  
8.2  
8.6  
8.1  
9.4  
9.9  
9.5  
10.4  
11.9  
13.7  
15.6  
17.7  
20.1  
22.7  
10.8  
12.4  
14.2  
16.1  
18.3  
20.7  
23.3  
11.3  
12.9  
14.7  
16.7  
18.9  
21.3  
24.0  
10.9  
12.6  
14.5  
16.6  
18.9  
21.4  
24.2  
11.4  
13.1  
15.0  
17.2  
19.5  
22.0  
24.8  
54  
Johnson Controls Unitary Products  
 
246653-YTG-E-0108  
1,2  
TABLE 41: FAN PERFORMANCE - 40 TON AIRFOIL (CONTINUED)  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
3.2  
3.4  
3.6  
3.8  
4.0  
AIRFLOW (CFM)  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
6.0  
BHP  
6.4  
BHP  
6.7  
BHP  
7.1  
BHP  
7.4  
8000  
9000  
1315  
1360  
1411  
1466  
1526  
1590  
1656  
1725  
1796  
1868  
1943  
2019  
1345  
1389  
1438  
1492  
1550  
1613  
1678  
1745  
1816  
1888  
1961  
1375  
1417  
1464  
1517  
1575  
1635  
1700  
1766  
1835  
1907  
1980  
1405  
1445  
1491  
1542  
1599  
1658  
1721  
1787  
1855  
1926  
1998  
1433  
1472  
1517  
1567  
1622  
1681  
1743  
1808  
1875  
1944  
2016  
6.9  
7.3  
7.6  
8.0  
8.4  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
19000  
20000  
7.9  
8.3  
8.7  
9.1  
9.5  
9.0  
9.5  
9.9  
10.3  
11.7  
13.2  
14.9  
16.9  
19.0  
21.2  
23.8  
10.8  
12.2  
13.7  
15.5  
17.4  
19.5  
21.8  
24.4  
10.3  
11.8  
13.4  
15.2  
17.3  
19.5  
21.9  
24.6  
10.8  
12.3  
13.9  
15.8  
17.8  
20.1  
22.5  
11.2  
12.7  
14.4  
16.3  
18.4  
20.6  
23.2  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
4.6  
4.2  
4.4  
4.8  
5.0  
AIRFLOW (CFM)  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
7.8  
BHP  
8.2  
BHP  
8.6  
BHP  
9.0  
BHP  
9.4  
8000  
9000  
1462  
1500  
1543  
1592  
1645  
1703  
1764  
1828  
1895  
1963  
2033  
1490  
1526  
1569  
1617  
1669  
1725  
1785  
1848  
1914  
1981  
1518  
1553  
1594  
1640  
1692  
1747  
1806  
1868  
1933  
2000  
1545  
1579  
1619  
1664  
1715  
1769  
1827  
1888  
1952  
2018  
1572  
1605  
1644  
1688  
1737  
1791  
1847  
1908  
1971  
2036  
8.8  
9.2  
9.6  
10.0  
11.2  
12.6  
14.1  
15.7  
17.6  
19.6  
21.8  
24.3  
10.4  
11.7  
13.0  
14.6  
16.2  
18.1  
20.2  
22.4  
24.9  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
9.9  
10.4  
11.7  
13.1  
14.7  
16.5  
18.5  
20.7  
23.1  
10.8  
12.1  
13.6  
15.2  
17.1  
19.1  
21.2  
23.7  
11.2  
12.6  
14.2  
16.0  
18.0  
20.1  
22.5  
25.0  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
5.6  
5.2  
5.4  
5.8  
6.0  
AIRFLOW (CFM)  
3
3
3
3
3
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
9.8  
BHP  
BHP  
BHP  
11.0  
12.2  
13.5  
14.9  
16.6  
18.4  
20.3  
22.5  
24.8  
BHP  
11.4  
12.6  
13.9  
15.4  
17.1  
18.9  
20.8  
23.0  
8000  
9000  
1599  
1630  
1668  
1712  
1759  
1812  
1868  
1927  
1990  
1624  
1655  
1692  
1734  
1782  
1833  
1888  
1947  
2008  
10.2  
11.3  
12.6  
14.0  
15.5  
17.3  
19.2  
21.3  
23.6  
1650  
1680  
1716  
1757  
1804  
1854  
1908  
1966  
2027  
10.6  
11.7  
13.0  
14.5  
16.0  
17.8  
19.8  
21.9  
24.2  
1675  
1705  
1740  
1780  
1825  
1875  
1928  
1985  
2045  
1701  
1729  
1763  
1803  
1847  
1896  
1948  
2004  
10.9  
12.1  
13.5  
15.0  
16.8  
18.7  
20.7  
23.0  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
17000  
18000  
1.  
Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.  
Refer to Tables 10, 12, 15, 18, 21, 23 and 42 for component additions and deductions to fan performance tables.  
BHP includes drive losses.  
2.  
3.  
4. Shaded RPMs require Class II blower.  
Johnson Controls Unitary Products  
55  
246653-YTG-E-0108  
1, 2  
TABLE 42: COMPONENT STATIC RESISTANCE  
CFM  
12,000  
-0.13  
COMPONENT COIL  
LOSSES  
6,000  
-0.06  
8,000  
-0.08  
10,000  
14,000  
-
16,000  
-
18,000  
-
STD. 25 TON, DRY  
STD. 25 TON, WET  
STD. 30 TON, DRY  
STD. 30 TON, WET  
HI CAP 30 TON, DRY  
HI CAP 30 TON, WET  
STD. 40 TON, DRY  
STD. 40 TON, WET  
HI CAP 40 TON, DRY  
HI CAP 40 TON, WET  
FILTER LOSSES  
2” TA OR HI EFF.  
RIGID 6”, 65%  
-0.10  
Baseline  
-0.112  
Baseline  
-0.045  
Baseline  
-0.019  
0.042  
Baseline  
-0.075  
Baseline  
-0.035  
0.069  
Baseline  
-0.157  
Baseline  
-0.073  
0.142  
Baseline  
-0.207  
Baseline  
-0.098  
0.186  
Baseline  
-0.264  
Baseline  
-0.124  
0.236  
Baseline  
-0.326  
Baseline  
-0.155  
0.290  
Baseline  
-0.052  
0.103  
-0.030  
Baseline  
-0.020  
0.023  
-0.051  
Baseline  
-0.033  
0.038  
-0.076  
Baseline  
-0.050  
0.057  
-0.106  
Baseline  
-0.069  
0.079  
-0.140  
Baseline  
-0.092  
0.105  
-0.177  
Baseline  
-0.116  
0.133  
-0.219  
Baseline  
-0.144  
0.164  
Baseline  
0.048  
Baseline  
0.080  
Baseline  
0.119  
Baseline  
0.165  
Baseline  
0.217  
Baseline  
0.274  
Baseline  
0.338  
RIGID 6”, 95%  
0.189  
0.308  
0.448  
0.609  
0.790  
0.988  
1.205  
IGV LOSSES  
25 & 30 TON  
0.048  
0.027  
0.085  
0.049  
0.132  
0.076  
0.190  
0.110  
0.259  
0.149  
0.338  
0.195  
0.428  
0.246  
40 TON  
GAS HEAT  
267 MBH HEAT  
533 MBH HEAT  
800 MBH HEAT  
ELECTRIC HEAT  
ECONOMIZER  
0.106  
0.212  
0.318  
0.050  
0.063  
0.046  
0.141  
0.283  
0.423  
0.100  
0.104  
0.081  
0.177  
0.353  
0.531  
0.150  
0.153  
0.127  
0.212  
0.424  
0.636  
0.310  
0.210  
0.182  
0.247  
0.495  
0.741  
0.430  
0.276  
0.248  
0.283  
0.566  
0.849  
0.530  
0.349  
0.324  
0.318  
0.636  
0.954  
0.680  
0.429  
0.410  
POWER EXHAUST  
1.  
Baseline losses based on system/cabinet effects, wet standard coil and 2” throwaway filters at 70°F, 0 feet elevation with standard air.  
See Tables 10, 12, 15, 18, 21 and 23 for hot water and steam water coil static resistance.  
2.  
56  
Johnson Controls Unitary Products  
 
246653-YTG-E-0108  
1
TABLE 43: POWER EXHAUST - ONE FORWARD CURVED FAN 25 TON  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
0.2  
0.4 0.6 0.8  
1.0  
AIRFLOW CFM  
2
2
2
2
2
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
BHP  
BHP  
BHP  
BHP  
4000  
5000  
6000  
7000  
8000  
9000  
10000  
442  
524  
612  
703  
791  
877  
967  
0.66  
1.21  
1.93  
3.00  
3.81  
5.81  
8.42  
496  
566  
646  
731  
821  
911  
0.78  
1.35  
2.18  
3.32  
4.29  
6.17  
8.76  
562  
609  
679  
759  
844  
932  
1022  
0.91  
1.50  
2.36  
3.54  
4.77  
6.53  
9.09  
626  
663  
717  
787  
868  
953  
1041  
1.05  
1.66  
2.55  
3.75  
5.24  
6.90  
9.43  
687  
717  
762  
820  
892  
974  
1059  
1.22  
1.83  
2.73  
3.97  
5.49  
7.27  
9.77  
1004  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
1.4 1.6 1.8  
1.2  
2.0  
AIRFLOW CFM  
2
2
2
2
2
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
1.39  
2.00  
2.92  
4.18  
5.74  
7.63  
10.10  
BHP  
BHP  
BHP  
1.93  
2.60  
3.57  
4.83  
6.50  
8.54  
-
BHP  
2.14  
2.81  
3.80  
5.04  
6.75  
8.81  
-
4000  
5000  
6000  
7000  
8000  
9000  
10000  
743  
768  
806  
857  
921  
995  
1077  
799  
818  
1.54  
2.18  
3.10  
4.40  
6.00  
7.97  
10.44  
850  
865  
895  
933  
985  
1048  
-
1.74  
2.39  
3.33  
4.61  
6.25  
8.25  
-
900  
911  
937  
972  
1018  
1075  
-
948  
955  
978  
1010  
1052  
1103  
-
850  
895  
953  
1020  
1096  
1.  
Fan performance is based on system/cabinet effects and back draft damper effects at standard air density and 0 feet elevation.  
BHP includes 5% drive losses.  
2.  
Johnson Controls Unitary Products  
57  
 
246653-YTG-E-0108  
Power Exhaust 25 Ton  
8.0  
7.5  
7.0  
6.5  
6.0  
5.5  
5.0  
4.5  
4.0  
3.5  
3.0  
2.5  
2.0  
1.5  
1.0  
0.5  
1600  
1500  
10 BHP  
7.5 BHP  
1400  
1300  
5 BHP  
1200  
1100  
1000  
900  
800  
700  
600  
500  
400  
300  
0.0  
0.0  
2.0  
4.0  
6.0  
8.0  
10.0  
12.0  
14.0  
16.0  
18.0  
CFM (x1000)  
FIGURE 25 - POWER EXHAUST - ONE FORWARD CURVE FAN - 25 TONS  
58  
Johnson Controls Unitary Products  
 
246653-YTG-E-0108  
1
TABLE 44: POWER EXHAUST - TWO FORWARD CURVED FANS - 30 & 40 TON  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
0.2  
0.4  
.06  
0.8  
1.0  
AIRFLOW CFM  
2 3  
2 3  
BHP  
2 3  
2 3  
BHP  
2 3  
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
BHP  
0.32  
BHP  
0.74  
4000  
5000  
363  
402  
445  
494  
544  
597  
651  
705  
761  
817  
874  
932  
989  
468  
494  
527  
565  
609  
654  
703  
753  
805  
858  
912  
967  
1022  
0.53  
560  
576  
602  
633  
670  
711  
641  
652  
670  
697  
729  
765  
805  
847  
893  
939  
988  
1037  
1088  
0.95  
716  
722  
735  
757  
784  
817  
853  
893  
934  
979  
1025  
1072  
-
1.16  
1.47  
2.00  
2.52  
3.15  
3.89  
4.83  
5.99  
7.25  
8.82  
10.50  
12.60  
-
0.53  
0.84  
1.26  
1.79  
2.42  
3.26  
4.31  
5.46  
6.93  
8.51  
10.40  
12.60  
0.74  
1.05  
1.58  
2.10  
2.84  
3.68  
4.73  
5.88  
7.35  
9.03  
10.92  
13.23  
1.05  
1.37  
1.79  
2.42  
3.15  
3.99  
5.15  
6.30  
7.77  
9.56  
11.55  
13.76  
1.26  
1.68  
2.10  
2.73  
3.47  
4.41  
5.57  
6.83  
8.30  
9.98  
12.08  
14.28  
6000  
7000  
8000  
9000  
10000  
11000  
12000  
13000  
14000  
15000  
16000  
754  
801  
849  
899  
950  
1002  
1055  
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)  
1.6  
1.2  
1.4  
1.8  
2
AIRFLOW CFM  
2 3  
2 3  
BHP  
2 3  
2 3  
BHP  
2 3  
RPM  
RPM  
RPM  
RPM  
RPM  
BHP  
1.47  
BHP  
1.89  
BHP  
2.42  
4000  
5000  
783  
788  
798  
814  
837  
866  
900  
936  
976  
1018  
1061  
1107  
844  
848  
1.68  
903  
906  
956  
959  
2.21  
1008  
1011  
1014  
1021  
1033  
1050  
1073  
1101  
1131  
1165  
1202  
1240  
1.79  
2.21  
2.84  
3.47  
4.31  
5.25  
6.41  
7.77  
9.35  
11.13  
13.23  
2.10  
2.63  
3.15  
3.89  
4.73  
5.67  
6.93  
8.30  
9.87  
11.66  
13.76  
2.42  
2.94  
3.47  
4.20  
5.15  
6.20  
7.35  
8.72  
10.40  
12.29  
14.39  
2.63  
3.26  
3.89  
4.62  
5.57  
6.62  
7.88  
9.24  
10.92  
12.92  
14.91  
2.94  
3.57  
4.20  
5.04  
5.99  
7.14  
8.30  
9.77  
11.55  
13.44  
15.54  
6000  
855  
911  
963  
7000  
869  
922  
972  
8000  
889  
938  
987  
9000  
915  
961  
1007  
1032  
1061  
1094  
1129  
1167  
1208  
10000  
11000  
12000  
13000  
14000  
15000  
945  
989  
979  
1020  
1055  
1093  
1133  
1175  
1016  
1055  
1098  
1141  
1.  
2.  
3.  
Fan performance is based on system/cabinet effects and back draft damper effects at standard air density and 0 feet elevation.  
BHP includes the sum of both exhaust fan motors.  
BHP does includes 5% drive losses.  
Johnson Controls Unitary Products  
59  
 
246653-YTG-E-0108  
FIGURE 26 - POWER EXHAUST - TWO FORWARD CURVED FANS - 30 & 40 TONS  
60  
Johnson Controls Unitary Products  
 
246653-YTG-E-0108  
TABLE 45: ELECTRICAL DATA 25 TON BASIC UNIT R22  
COMPRESSORS  
(EACH)  
OD FAN MOTORS  
(EACH)  
MAX  
FUSE  
BREAKER  
SIZE  
SUPPLY BLOWER  
1
2
MCA  
/
VOLTAGE  
3
(AMPS)  
QTY.  
RLA  
LRA  
MCC  
QTY  
FLA  
HP  
FLA  
7.5  
10  
15  
20  
7.5  
10  
15  
20  
7.5  
10  
15  
20  
7.5  
10  
15  
20  
24.2  
30.8  
46.2  
59.4  
22.0  
28.0  
42.0  
54.0  
11.0  
14.0  
21.0  
27.0  
9.0  
137  
144  
160  
177  
134  
140  
154  
169  
59  
175  
175  
200  
225  
150  
175  
175  
200  
70  
208-3-60  
2
42.3  
245  
66.0  
4
4
4
4
3.8  
230-3-60  
460-3-60  
2
2
2
42.3  
17.6  
14.2  
245  
125  
100  
66.0  
27.5  
22.2  
3.8  
1.9  
1.5  
62  
70  
70  
90  
78  
100  
60  
48  
11.0  
17.0  
22.0  
50  
60  
575-3-60  
56  
70  
63  
80  
1.  
Minimum Circuit Ampacity.  
Dual Element, Time Delay Type.  
HACR type per NEC  
2.  
3.  
TABLE 46: ELECTRICAL DATA 30 TON BASIC UNIT R22  
COMPRESSORS  
(EACH)  
OD FAN MOTORS  
(EACH)  
MAX  
2
SUPPLY BLOWER  
1
MCA  
FUSE  
/
VOLTAGE  
3
(AMPS)  
BREAKER  
SIZE  
QTY.  
RLA  
LRA  
MCC  
QTY  
FLA  
HP  
FLA  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
30.8  
46.2  
59.4  
74.8  
28.0  
42.0  
54.0  
68.0  
14.0  
21.0  
27.0  
34.0  
11.0  
17.0  
22.0  
27.0  
165  
183  
199  
219  
162  
177  
192  
210  
76  
200  
225  
250  
250  
175  
200  
225  
250  
90  
208-3-60  
3
37.2  
239  
58.0  
3
3
3
3
4.5  
230-3-60  
460-3-60  
3
3
3
37.2  
17.2  
12.4  
239  
125  
80  
58.0  
27.0  
19.3  
4.5  
2.2  
1.7  
84  
100  
110  
125  
60  
92  
101  
56  
64  
80  
575-3-60  
70  
90  
76  
100  
1.  
Minimum Circuit Ampacity.  
Dual Element, Time Delay Type.  
HACR type per NEC  
2.  
3.  
Johnson Controls Unitary Products  
61  
   
246653-YTG-E-0108  
TABLE 47: ELECTRICAL DATA 40 TON BASIC UNIT R22  
COMPRESSORS  
(EACH)  
OD FAN MOTORS  
(EACH)  
MAX  
FUSE  
BREAKER  
SIZE  
SUPPLY BLOWER  
1
2
MCA  
/
VOLTAGE  
3
(AMPS)  
QTY.  
RLA  
LRA  
MCC  
QTY  
FLA  
HP  
FLA  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
30.8  
46.2  
59.4  
74.8  
28.0  
42.0  
54.0  
68.0  
14.0  
21.0  
27.0  
34.0  
11.0  
17.0  
22.0  
27.0  
207  
225  
241  
260  
203  
219  
234  
251  
96  
225  
250  
250  
300  
225  
250  
250  
300  
110  
110  
125  
150  
80  
208-3-60  
4
37.2  
239  
58.0  
4
4
4
4
4.5  
230-3-60  
460-3-60  
4
4
4
37.2  
17.2  
12.4  
239  
125  
80  
58.0  
27.0  
19.3  
4.5  
2.2  
1.7  
104  
111  
120  
71  
78  
90  
575-3-60  
84  
100  
110  
90  
1.  
Minimum Circuit Ampacity.  
Dual Element, Time Delay Type.  
HACR type per NEC  
2.  
3.  
62  
Johnson Controls Unitary Products  
 
246653-YTG-E-0108  
TABLE 48: ELECTRICAL DATA 25 TON WITH ELECTRIC HEAT R22  
COMPRESSORS  
(EACH)  
OD FAN MOTORS  
(EACH)  
MAX  
FUSE  
BREAKER  
SIZE  
SUPPLY BLOWER  
ELECTRIC HEAT  
1
2
MCA  
/
VOLTAGE  
3
(AMPS)  
APPLIED  
QTY. RLA LRA MCC  
QTY  
FLA  
HP  
FLA  
OPTION  
KW  
KW  
STAGES  
7.5  
10  
15  
20  
7.5  
10  
15  
20  
7.5  
10  
15  
20  
7.5  
10  
15  
20  
7.5  
10  
15  
20  
7.5  
10  
15  
20  
7.5  
10  
15  
20  
7.5  
10  
15  
20  
7.5  
10  
15  
20  
7.5  
10  
15  
20  
24.2  
30.8  
46.2  
59.4  
24.2  
30.8  
46.2  
59.4  
22.0  
28.0  
42.0  
54.0  
22.0  
28.0  
42.0  
54.0  
11.0  
14.0  
21.0  
27.0  
11.0  
14.0  
21.0  
27.0  
11.0  
14.0  
21.0  
27.0  
9.0  
E4  
E4  
E4  
E4  
E8  
E8  
E8  
E8  
E4  
E4  
E4  
E4  
E8  
E8  
E8  
E8  
E4  
E4  
E4  
E4  
E8  
E8  
E8  
E8  
E1  
E1  
E1  
E1  
E4  
E4  
E4  
E4  
E8  
E8  
E8  
E8  
E1  
E1  
E1  
E1  
40  
40  
30  
1
1
1
1
2
2
2
2
1
1
1
1
2
2
2
2
1
1
1
1
2
2
2
2
2
2
2
2
1
1
1
1
2
2
2
2
2
2
2
2
137  
144  
162  
178  
197  
205  
225  
241  
148  
155  
173  
188  
220  
227  
245  
260  
74  
175  
175  
200  
225  
225  
225  
250  
300  
175  
175  
175  
200  
250  
250  
250  
300  
80  
30  
40  
30  
40  
30  
208-3-60  
2
42.3  
245  
66.0  
4
3.8  
80  
60  
80  
60  
80  
60  
80  
60  
40  
36.8  
36.8  
36.8  
36.8  
73.6  
73.6  
73.6  
73.6  
36.8  
36.8  
36.8  
36.8  
73.6  
73.6  
73.6  
73.6  
99.4  
99.4  
99.4  
99.4  
36.8  
36.8  
36.8  
36.8  
73.6  
73.6  
73.6  
73.6  
99.4  
99.4  
99.4  
99.4  
40  
40  
40  
230-3-60  
2
42.3  
245  
66.0  
4
3.8  
80  
80  
80  
80  
40  
40  
78  
80  
40  
86  
90  
40  
94  
110  
125  
125  
125  
150  
175  
175  
175  
175  
60  
80  
110  
114  
122  
130  
144  
147  
156  
164  
59  
80  
460-3-60  
2
17.6  
125  
27.5  
4
1.9  
80  
80  
108  
108  
108  
108  
40  
11.0  
17.0  
22.0  
9.0  
40  
62  
70  
40  
69  
70  
40  
76  
80  
80  
88  
100  
100  
110  
125  
125  
150  
150  
150  
11.0  
17.0  
22.0  
9.0  
80  
91  
575-3-60  
2
14.2  
100  
22.2  
4
1.5  
80  
98  
80  
104  
115  
118  
125  
131  
108  
108  
108  
108  
11.0  
17.0  
22.0  
1.  
Minimum Circuit Ampacity.  
2.  
3.  
Dual Element, Time Delay Type.  
HACR type per NEC  
Johnson Controls Unitary Products  
63  
246653-YTG-E-0108  
TABLE 49: ELECTRICAL DATA 30 TON WITH ELECTRIC HEAT R22  
COMPRESSORS  
(EACH)  
OD FAN MOTORS  
(EACH)  
MAX  
FUSE  
BREAKER  
SIZE  
SUPPLY BLOWER  
ELECTRIC HEAT  
1
2
MCA  
/
VOLTAGE  
208-3-60  
3
(AMPS)  
APPLIED  
QTY. RLA LRA MCC  
QTY  
FLA  
HP  
FLA  
OPTION  
KW  
KW  
STAGES  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
30.8  
46.2  
59.4  
74.8  
30.8  
46.2  
59.4  
74.8  
28.0  
42.0  
54.0  
68.0  
28.0  
42.0  
54.0  
68.0  
14.0  
21.0  
27.0  
34.0  
14.0  
21.0  
27.0  
34.0  
14.0  
21.0  
27.0  
34.0  
11.0  
17.0  
22.0  
27.0  
11.0  
17.0  
22.0  
27.0  
11.0  
17.0  
22.0  
27.0  
E4  
E4  
E4  
E4  
E8  
E8  
E8  
E8  
E4  
E4  
E4  
E4  
E8  
E8  
E8  
E8  
E4  
E4  
E4  
E4  
E8  
E8  
E8  
E8  
E1  
E1  
E1  
E1  
E4  
E4  
E4  
E4  
E8  
E8  
E8  
E8  
E1  
E1  
E1  
E1  
40  
40  
30  
1
1
1
1
2
2
2
2
1
1
1
1
2
2
2
2
1
1
1
1
2
2
2
2
2
2
2
2
1
1
1
1
2
2
2
2
2
2
2
2
165  
183  
199  
219  
205  
225  
241  
260  
162  
177  
192  
210  
227  
245  
260  
277  
78  
200  
225  
250  
250  
225  
250  
300  
300  
175  
200  
225  
250  
250  
250  
300  
300  
90  
30  
40  
30  
40  
30  
3
37.2  
239  
58.0  
3
4.5  
80  
60  
80  
60  
80  
60  
80  
60  
40  
36.8  
36.8  
36.8  
36.8  
73.6  
73.6  
73.6  
73.6  
36.8  
36.8  
36.8  
36.8  
73.6  
73.6  
73.6  
73.6  
99.4  
99.4  
99.4  
99.4  
36.8  
36.8  
36.8  
36.8  
73.6  
73.6  
73.6  
73.6  
99.4  
99.4  
99.4  
99.4  
40  
40  
40  
230-3-60  
3
37.2  
239  
58.0  
3
4.5  
80  
80  
80  
80  
40  
40  
86  
100  
110  
125  
125  
125  
150  
150  
175  
175  
175  
200  
70  
40  
94  
40  
103  
114  
122  
130  
139  
147  
156  
164  
172  
62  
80  
80  
460-3-60  
3
17.2  
125  
27.0  
3
2.2  
80  
80  
108  
108  
108  
108  
40  
40  
69  
80  
40  
76  
90  
40  
82  
100  
100  
110  
125  
125  
150  
150  
150  
150  
80  
91  
80  
98  
575-3-60  
3
12.4  
80  
19.3  
3
1.7  
80  
104  
111  
118  
125  
131  
138  
80  
108  
108  
108  
108  
1.  
Minimum Circuit Ampacity.  
2.  
3.  
Dual Element, Time Delay Type.  
HACR type per NEC  
64  
Johnson Controls Unitary Products  
246653-YTG-E-0108  
TABLE 50: ELECTRICAL DATA 40 TON WITH ELECTRIC HEAT R22  
COMPRESSORS  
(EACH)  
OD FAN MOTORS  
(EACH)  
MAX  
FUSE  
BREAKER  
SIZE  
SUPPLY BLOWER  
ELECTRIC HEAT  
1
2
MCA  
/
VOLTAGE  
3
(AMPS)  
APPLIED  
QTY. RLA LRA MCC  
QTY  
FLA  
HP  
FLA  
OPTION  
KW  
KW  
STAGES  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
30.8  
46.2  
59.4  
74.8  
30.8  
46.2  
59.4  
74.8  
28.0  
42.0  
54.0  
68.0  
28.0  
42.0  
54.0  
68.0  
14.0  
21.0  
27.0  
34.0  
14.0  
21.0  
27.0  
34.0  
14.0  
21.0  
27.0  
34.0  
11.0  
17.0  
22.0  
27.0  
11.0  
17.0  
22.0  
27.0  
11.0  
17.0  
22.0  
27.0  
E4  
E4  
E4  
E4  
E8  
E8  
E8  
E8  
E4  
E4  
E4  
E4  
E8  
E8  
E8  
E8  
E4  
E4  
E4  
E4  
E8  
E8  
E8  
E8  
E1  
E1  
E1  
E1  
E4  
E4  
E4  
E4  
E8  
E8  
E8  
E8  
E1  
E1  
E1  
E1  
40  
40  
30.0  
30.0  
30.0  
30.0  
60.1  
60.1  
60.1  
60.1  
36.8  
36.8  
36.8  
36.8  
73.6  
73.6  
73.6  
73.6  
36.8  
36.8  
36.8  
36.8  
73.6  
73.6  
73.6  
73.6  
99.4  
99.4  
99.4  
99.4  
36.8  
36.8  
36.8  
36.8  
73.6  
73.6  
73.6  
73.6  
99.4  
99.4  
99.4  
99.4  
1
1
1
1
2
2
2
2
1
1
1
1
2
2
2
2
1
1
1
1
2
2
2
2
2
2
2
2
1
1
1
1
2
2
2
2
2
2
2
2
207  
225  
241  
260  
207  
225  
241  
260  
203  
219  
234  
251  
227  
245  
260  
277  
96  
225  
250  
300  
300  
225  
250  
300  
300  
225  
250  
250  
300  
250  
250  
300  
300  
110  
110  
125  
150  
125  
125  
150  
150  
175  
175  
175  
200  
80  
40  
40  
208-3-60  
4
37.2  
239  
58.0  
4
4.5  
80  
80  
80  
80  
40  
40  
40  
40  
230-3-60  
4
37.2  
239  
58.0  
4
4.5  
80  
80  
80  
80  
40  
40  
104  
111  
120  
114  
122  
130  
139  
147  
156  
164  
172  
71  
40  
40  
80  
80  
460-3-60  
4
17.2  
125  
27.0  
4
2.2  
80  
80  
108  
108  
108  
108  
40  
40  
78  
90  
40  
84  
100  
110  
100  
110  
125  
125  
150  
150  
150  
150  
40  
90  
80  
91  
80  
98  
575-3-60  
4
12.4  
80  
19.3  
4
1.7  
80  
104  
111  
118  
125  
131  
138  
80  
108  
108  
108  
108  
1.  
Minimum Circuit Ampacity.  
2.  
3.  
Dual Element, Time Delay Type.  
HACR type per NEC  
Johnson Controls Unitary Products  
65  
246653-YTG-E-0108  
TABLE 51: ELECTRICAL DATA 25 TON WITH POWER EXHAUST R22  
COMPRESSORS  
(EACH)  
OD FAN MOTORS  
(EACH)  
MAX  
FUSE  
BREAKER  
SIZE  
SUPPLY BLOWER  
PWR EXH MOTOR  
1
2
MCA  
/
VOLTAGE  
3
(AMPS)  
QTY.  
RLA  
LRA  
MCC  
QTY  
FLA  
HP  
FLA  
HP  
FLA  
5
7.5  
10  
5
16.7  
24.2  
30.8  
16.7  
24.2  
30.8  
16.7  
24.2  
30.8  
16.7  
24.2  
30.8  
15.2  
22.0  
28.0  
15.2  
22.0  
28.0  
15.2  
22.0  
28.0  
15.2  
22.0  
28.0  
7.6  
154  
161  
168  
160  
168  
175  
177  
184  
191  
193  
201  
207  
149  
156  
162  
155  
162  
168  
169  
176  
182  
184  
191  
197  
67  
175  
200  
200  
200  
200  
200  
200  
225  
225  
250  
250  
250  
175  
175  
200  
175  
200  
200  
200  
200  
200  
225  
225  
250  
80  
7.5  
10  
15  
20  
7.5  
10  
15  
20  
7.5  
10  
15  
20  
7.5  
10  
15  
20  
24.2  
30.8  
46.2  
59.4  
22.0  
28.0  
42.0  
54.0  
11.0  
14.0  
21.0  
27.0  
9.0  
7.5  
10  
5
208-3-60  
2
42.3  
245  
66.0  
4
3.8  
7.5  
10  
5
7.5  
10  
5
7.5  
10  
5
7.5  
10  
5
230-3-60  
2
2
2
42.3  
17.6  
14.2  
245  
125  
100  
66.0  
27.5  
22.2  
4
4
4
3.8  
1.9  
1.5  
7.5  
10  
5
7.5  
10  
5
7.5  
10  
5
11.0  
14.0  
7.6  
70  
80  
73  
90  
70  
80  
7.5  
10  
5
11.0  
14.0  
7.6  
73  
90  
76  
90  
460-3-60  
78  
90  
7.5  
10  
5
11.0  
14.0  
7.6  
81  
100  
100  
110  
110  
110  
60  
84  
85  
7.5  
10  
5
11.0  
14.0  
6.1  
89  
92  
54  
7.5  
10  
5
9.0  
57  
70  
11.0  
6.1  
59  
70  
56  
70  
11.0  
17.0  
22.0  
7.5  
10  
5
9.0  
59  
70  
11.0  
6.1  
61  
70  
575-3-60  
63  
70  
7.5  
10  
5
9.0  
65  
80  
11.0  
6.1  
67  
80  
69  
90  
7.5  
10  
9.0  
72  
90  
11.0  
74  
90  
1.  
Minimum Circuit Ampacity.  
Dual Element, Time Delay Type.  
HACR type per NEC  
2.  
3.  
66  
Johnson Controls Unitary Products  
 
246653-YTG-E-0108  
TABLE 52: ELECTRICAL DATA 30 TON WITH POWER EXHAUST R22  
COMPRESSORS  
(EACH)  
OD FAN MOTORS  
(EACH)  
MAX  
FUSE  
BREAKER  
SIZE  
SUPPLY BLOWER  
PWR EXH MOTOR  
1
2
MCA  
/
VOLTAGE  
3
(AMPS)  
QTY.  
RLA  
LRA  
MCC  
QTY  
FLA  
HP  
FLA  
HP  
FLA  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
24.2  
30.8  
46.2  
24.2  
30.8  
46.2  
24.2  
30.8  
46.2  
24.2  
30.8  
46.2  
22.0  
28.0  
42.0  
22.0  
28.0  
42.0  
22.0  
28.0  
42.0  
22.0  
28.0  
42.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
9.0  
189  
196  
214  
207  
214  
229  
224  
230  
246  
243  
249  
265  
184  
190  
205  
199  
205  
219  
214  
220  
234  
232  
238  
252  
87  
225  
225  
250  
250  
250  
250  
250  
250  
300  
300  
300  
300  
200  
225  
225  
225  
225  
250  
250  
250  
250  
250  
300  
300  
100  
100  
110  
110  
110  
125  
125  
125  
125  
125  
125  
150  
70  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
30.8  
46.2  
59.4  
74.8  
28.0  
42.0  
54.0  
68.0  
14.0  
21.0  
27.0  
34.0  
11.0  
17.0  
22.0  
27.0  
208-3-60  
3
37.2  
239  
58.0  
3
4.5  
230-3-60  
3
3
3
37.2  
17.2  
12.4  
239  
125  
80  
58.0  
27.0  
19.3  
3
3
3
4.5  
2.2  
1.7  
90  
98  
95  
98  
105  
103  
106  
113  
112  
115  
122  
65  
460-3-60  
11.0  
17.0  
9.0  
67  
70  
75  
90  
73  
80  
11.0  
17.0  
9.0  
75  
90  
81  
90  
575-3-60  
79  
100  
100  
100  
110  
110  
110  
11.0  
17.0  
9.0  
81  
87  
85  
11.0  
17.0  
87  
93  
1.  
Minimum Circuit Ampacity.  
Dual Element, Time Delay Type.  
HACR type per NEC  
2.  
3.  
Johnson Controls Unitary Products  
67  
 
246653-YTG-E-0108  
TABLE 53: ELECTRICAL DATA 40 TON WITH POWER EXHAUST R22  
COMPRESSORS  
(EACH)  
OD FAN MOTORS  
(EACH)  
MAX  
FUSE  
BREAKER  
SIZE  
SUPPLY BLOWER  
PWR EXH MOTOR  
1
2
MCA  
/
VOLTAGE  
3
(AMPS)  
QTY.  
RLA  
LRA  
MCC  
QTY  
FLA  
HP  
FLA  
HP  
FLA  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
24.2  
30.8  
46.2  
24.2  
30.8  
46.2  
24.2  
30.8  
46.2  
24.2  
30.8  
46.2  
22.0  
28.0  
42.0  
22.0  
28.0  
42.0  
22.0  
28.0  
42.0  
22.0  
28.0  
42.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
9.0  
231  
238  
255  
249  
255  
271  
265  
272  
287  
285  
291  
307  
225  
231  
247  
241  
247  
261  
256  
262  
276  
273  
279  
293  
107  
110  
118  
115  
118  
125  
122  
125  
132  
131  
134  
141  
80  
250  
250  
300  
250  
300  
300  
300  
300  
300  
350  
350  
350  
250  
250  
250  
250  
250  
300  
300  
300  
300  
300  
300  
350  
110  
125  
125  
125  
125  
125  
125  
150  
150  
150  
150  
150  
90  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
30.8  
46.2  
59.4  
74.8  
28.0  
42.0  
54.0  
68.0  
14.0  
21.0  
27.0  
34.0  
11.0  
17.0  
22.0  
27.0  
208-3-60  
4
37.2  
239  
58.0  
4
4.5  
230-3-60  
4
4
4
37.2  
17.2  
12.4  
239  
125  
80  
58.0  
27.0  
19.3  
4
4
4
4.5  
2.2  
1.7  
460-3-60  
11.0  
17.0  
9.0  
82  
90  
89  
100  
100  
100  
110  
110  
110  
110  
125  
125  
125  
87  
11.0  
17.0  
9.0  
89  
95  
575-3-60  
93  
11.0  
17.0  
9.0  
95  
101  
99  
11.0  
17.0  
101  
107  
1.  
Minimum Circuit Ampacity.  
Dual Element, Time Delay Type.  
HACR type per NEC  
2.  
3.  
68  
Johnson Controls Unitary Products  
 
246653-YTG-E-0108  
TABLE 54: ELECTRICAL DATA 25 TON WITH ELECTRIC HEAT AND POWER EXHAUST R22  
COMPRESSORS  
(EACH)  
OD FAN MOTORS  
(EACH)  
MAX  
FUSE  
BREAKER  
SIZE  
ELECTRIC HEAT  
SUPPLY BLOWER  
PWR EXH MOTOR  
1
2
MCA  
/
VOLTAGE  
3
(AMPS)  
OPTION KW STAGES QTY. RLA LRA MCC  
QTY  
FLA  
HP  
FLA  
HP  
FLA  
5
7.5  
10  
5
16.7  
24.2  
30.8  
16.7  
24.2  
30.8  
16.7  
24.2  
30.8  
16.7  
24.2  
30.8  
16.7  
24.2  
30.8  
16.7  
24.2  
30.8  
16.7  
24.2  
30.8  
16.7  
24.2  
30.8  
15.2  
22.0  
28.0  
15.2  
22.0  
28.0  
15.2  
22.0  
28.0  
15.2  
22.0  
28.0  
15.2  
22.0  
28.0  
15.2  
22.0  
28.0  
15.2  
22.0  
28.0  
15.2  
22.0  
28.0  
154  
161  
168  
160  
168  
175  
179  
186  
193  
195  
203  
209  
214  
221  
229  
222  
229  
236  
241  
249  
255  
258  
265  
272  
163  
170  
177  
170  
177  
183  
188  
195  
201  
203  
210  
216  
235  
242  
249  
243  
249  
255  
260  
267  
273  
275  
282  
288  
175  
200  
200  
200  
200  
200  
200  
225  
225  
250  
250  
250  
225  
225  
250  
250  
250  
250  
250  
250  
300  
300  
300  
300  
175  
175  
200  
175  
200  
200  
200  
200  
225  
225  
225  
250  
250  
250  
250  
250  
250  
300  
300  
300  
300  
300  
300  
300  
7.5  
24.2  
10  
15  
20  
7.5  
10  
15  
20  
7.5  
10  
15  
20  
7.5  
10  
15  
20  
30.8  
46.2  
59.4  
24.2  
30.8  
46.2  
59.4  
22.0  
28.0  
42.0  
54.0  
22.0  
28.0  
42.0  
54.0  
7.5  
10  
5
E4  
E8  
E4  
E8  
40  
80  
40  
80  
1
2
1
2
2
2
2
2
42.3 245 66.0  
42.3 245 66.0  
42.3 245 66.0  
42.3 245 66.0  
4
3.8  
7.5  
10  
5
7.5  
10  
5
208-3-60  
7.5  
10  
5
7.5  
10  
5
4
4
4
3.8  
3.8  
3.8  
7.5  
10  
5
7.5  
10  
5
7.5  
10  
5
7.5  
10  
5
7.5  
10  
5
7.5  
10  
5
230-3-60  
7.5  
10  
5
7.5  
10  
5
7.5  
10  
5
7.5  
10  
Johnson Controls Unitary Products  
69  
246653-YTG-E-0108  
TABLE 54: ELECTRICAL DATA 25 TON WITH ELECTRIC HEAT AND POWER EXHAUST R22 (CONTINUED)  
COMPRESSORS  
(EACH)  
OD FAN MOTORS  
(EACH)  
MAX  
FUSE  
BREAKER  
SIZE  
ELECTRIC HEAT  
SUPPLY BLOWER  
PWR EXH MOTOR  
1
2
MCA  
/
VOLTAGE  
3
(AMPS)  
OPTION KW STAGES QTY. RLA LRA MCC  
QTY  
FLA  
HP  
FLA  
HP  
FLA  
5
7.5  
10  
5
7.6  
11.0  
14.0  
7.6  
81  
90  
7.5  
11.0  
85  
90  
89  
90  
85  
90  
10  
15  
20  
7.5  
10  
15  
20  
7.5  
10  
15  
20  
14.0  
21.0  
27.0  
11.0  
14.0  
21.0  
27.0  
11.0  
14.0  
21.0  
27.0  
7.5  
10  
5
11.0  
14.0  
7.6  
89  
90  
92  
100  
100  
100  
110  
110  
110  
110  
125  
125  
125  
125  
125  
150  
150  
150  
150  
150  
150  
150  
175  
175  
175  
175  
175  
175  
175  
175  
175  
175  
200  
200  
E4  
E8  
E1  
40  
1
2
2
2
2
2
17.6 125 27.5  
17.6 125 27.5  
17.6 125 27.5  
4
1.9  
94  
7.5  
10  
5
11.0  
14.0  
7.6  
97  
100  
101  
105  
108  
118  
121  
125  
121  
125  
128  
130  
133  
136  
138  
141  
144  
151  
155  
158  
155  
158  
161  
164  
167  
170  
171  
175  
178  
7.5  
10  
5
11.0  
14.0  
7.6  
7.5  
10  
5
11.0  
14.0  
7.6  
7.5  
10  
5
11.0  
14.0  
7.6  
460-3-60  
80  
4
1.9  
7.5  
10  
5
11.0  
14.0  
7.6  
7.5  
10  
5
11.0  
14.0  
7.6  
7.5  
10  
5
11.0  
14.0  
7.6  
7.5  
10  
5
11.0  
14.0  
7.6  
108  
4
1.9  
7.5  
10  
5
11.0  
14.0  
7.6  
7.5  
10  
11.0  
14.0  
70  
Johnson Controls Unitary Products  
246653-YTG-E-0108  
TABLE 54: ELECTRICAL DATA 25 TON WITH ELECTRIC HEAT AND POWER EXHAUST R22 (CONTINUED)  
COMPRESSORS  
(EACH)  
OD FAN MOTORS  
(EACH)  
MAX  
FUSE  
BREAKER  
SIZE  
ELECTRIC HEAT  
SUPPLY BLOWER  
PWR EXH MOTOR  
1
2
MCA  
/
VOLTAGE  
3
(AMPS)  
OPTION KW STAGES QTY. RLA LRA MCC  
QTY  
FLA  
HP  
FLA  
HP  
FLA  
5
7.5  
10  
5
6.1  
9.0  
65  
68  
70  
70  
7.5  
9.0  
11.0  
6.1  
71  
80  
68  
70  
10  
15  
20  
7.5  
10  
15  
20  
7.5  
10  
15  
20  
11.0  
17.0  
22.0  
9.0  
7.5  
10  
5
9.0  
71  
80  
11.0  
6.1  
73  
80  
E4  
E8  
E1  
40  
1
2
2
2
2
2
14.2 100 22.2  
14.2 100 22.2  
14.2 100 22.2  
4
1.5  
75  
80  
7.5  
10  
5
9.0  
78  
80  
11.0  
6.1  
80  
90  
82  
90  
7.5  
10  
5
9.0  
85  
90  
11.0  
6.1  
87  
90  
94  
100  
100  
110  
100  
110  
110  
110  
110  
125  
125  
125  
125  
150  
150  
150  
150  
150  
150  
150  
150  
150  
150  
150  
150  
7.5  
10  
5
9.0  
97  
11.0  
6.1  
100  
97  
11.0  
17.0  
22.0  
9.0  
7.5  
10  
5
9.0  
100  
102  
104  
107  
109  
111  
113  
115  
121  
124  
127  
124  
127  
129  
131  
134  
136  
138  
140  
142  
11.0  
6.1  
575-3-60  
80  
4
1.5  
7.5  
10  
5
9.0  
11.0  
6.1  
7.5  
10  
5
9.0  
11.0  
6.1  
7.5  
10  
5
9.0  
11.0  
6.1  
11.0  
17.0  
22.0  
7.5  
10  
5
9.0  
11.0  
6.1  
108  
4
1.5  
7.5  
10  
5
9.0  
11.0  
6.1  
7.5  
10  
9.0  
11.0  
1.  
Minimum Circuit Ampacity.  
2.  
3.  
Dual Element, Time Delay Type.  
HACR type per NEC  
Johnson Controls Unitary Products  
71  
246653-YTG-E-0108  
TABLE 55: ELECTRICAL DATA 30 TON WITH ELECTRIC HEAT AND POWER EXHAUST R22  
COMPRESSORS  
(EACH)  
OD FAN MOTORS  
(EACH)  
MAX  
FUSE  
BREAKER  
SIZE  
ELECTRIC HEAT  
SUPPLY BLOWER  
PWR EXH MOTOR  
1
2
MCA  
/
VOLTAGE  
3
(AMPS)  
OPTION KW STAGES QTY. RLA LRA MCC  
QTY  
FLA  
HP  
FLA  
HP  
FLA  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
24.2  
30.8  
46.2  
24.2  
30.8  
46.2  
24.2  
30.8  
46.2  
24.2  
30.8  
46.2  
24.2  
30.8  
46.2  
24.2  
30.8  
46.2  
24.2  
30.8  
46.2  
24.2  
30.8  
46.2  
22.0  
28.0  
42.0  
22.0  
28.0  
42.0  
22.0  
28.0  
42.0  
22.0  
28.0  
42.0  
22.0  
28.0  
42.0  
22.0  
28.0  
42.0  
22.0  
28.0  
42.0  
22.0  
28.0  
42.0  
189  
196  
214  
207  
214  
229  
224  
230  
246  
243  
249  
265  
229  
236  
255  
249  
255  
271  
265  
272  
287  
284  
291  
306  
184  
190  
205  
199  
205  
219  
214  
220  
234  
232  
238  
252  
249  
255  
273  
267  
273  
287  
282  
288  
302  
299  
305  
319  
225  
225  
250  
250  
250  
250  
250  
250  
300  
300  
300  
300  
250  
250  
300  
250  
300  
300  
300  
300  
300  
350  
350  
350  
200  
225  
225  
225  
225  
250  
250  
250  
250  
250  
300  
300  
250  
300  
300  
300  
300  
300  
300  
300  
350  
350  
350  
350  
10  
30.8  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
46.2  
59.4  
74.8  
30.8  
46.2  
59.4  
74.8  
28.0  
42.0  
54.0  
68.0  
28.0  
42.0  
54.0  
68.0  
E4  
E8  
E4  
E8  
40  
80  
40  
80  
1
2
1
2
3
3
3
3
37.2 239 58.0  
37.2 239 58.0  
37.2 239 58.0  
37.2 239 58.0  
3
5.8  
208-3-60  
3
3
3
5.8  
5.8  
5.8  
230-3-60  
72  
Johnson Controls Unitary Products  
246653-YTG-E-0108  
TABLE 55: ELECTRICAL DATA 30 TON WITH ELECTRIC HEAT AND POWER EXHAUST R22 (CONTINUED)  
COMPRESSORS  
(EACH)  
OD FAN MOTORS  
(EACH)  
MAX  
FUSE  
BREAKER  
SIZE  
ELECTRIC HEAT  
SUPPLY BLOWER  
PWR EXH MOTOR  
1
2
MCA  
/
VOLTAGE  
3
(AMPS)  
OPTION KW STAGES QTY. RLA LRA MCC  
QTY  
FLA  
HP  
FLA  
HP  
FLA  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
89  
100  
100  
110  
110  
110  
125  
125  
125  
125  
125  
125  
150  
125  
150  
150  
150  
150  
150  
150  
150  
175  
175  
175  
175  
175  
175  
175  
175  
175  
200  
200  
200  
200  
200  
200  
225  
10  
14.0  
92  
100  
97  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
21.0  
27.0  
34.0  
14.0  
21.0  
27.0  
34.0  
14.0  
21.0  
27.0  
34.0  
100  
107  
105  
108  
115  
114  
117  
124  
125  
128  
136  
133  
136  
143  
141  
144  
151  
150  
153  
160  
158  
161  
170  
167  
170  
177  
175  
178  
185  
183  
186  
193  
E4  
E8  
E1  
40  
1
2
2
3
3
3
17.2 125 27.0  
17.2 125 27.0  
17.2 125 27.0  
3
2.2  
460-3-60  
80  
3
2.2  
108  
3
2.2  
Johnson Controls Unitary Products  
73  
246653-YTG-E-0108  
TABLE 55: ELECTRICAL DATA 30 TON WITH ELECTRIC HEAT AND POWER EXHAUST R22 (CONTINUED)  
COMPRESSORS  
(EACH)  
OD FAN MOTORS  
(EACH)  
MAX  
FUSE  
BREAKER  
SIZE  
ELECTRIC HEAT  
SUPPLY BLOWER  
PWR EXH MOTOR  
1
2
MCA  
/
VOLTAGE  
3
(AMPS)  
OPTION KW STAGES QTY. RLA LRA MCC  
QTY  
FLA  
HP  
FLA  
HP  
FLA  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
9.0  
11.0  
17.0  
9.0  
71  
73  
80  
10  
11.0  
80  
80  
90  
78  
80  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
17.0  
22.0  
27.0  
11.0  
17.0  
22.0  
27.0  
11.0  
17.0  
22.0  
27.0  
11.0  
17.0  
9.0  
80  
90  
86  
90  
E4  
E8  
E1  
40  
1
2
2
3
3
3
12.4  
12.4  
12.4  
80  
80  
80  
19.3  
19.3  
19.3  
3
1.7  
85  
100  
100  
100  
110  
110  
110  
110  
110  
125  
110  
125  
125  
125  
125  
125  
125  
125  
150  
150  
150  
150  
150  
150  
150  
150  
150  
150  
150  
175  
175  
11.0  
17.0  
9.0  
87  
93  
91  
11.0  
17.0  
9.0  
93  
99  
100  
102  
109  
107  
109  
115  
113  
115  
121  
120  
122  
128  
127  
129  
136  
134  
136  
142  
140  
142  
148  
147  
149  
155  
11.0  
17.0  
9.0  
11.0  
17.0  
9.0  
575-3-60  
80  
3
1.7  
11.0  
17.0  
9.0  
11.0  
17.0  
9.0  
11.0  
17.0  
9.0  
11.0  
17.0  
9.0  
108  
3
1.7  
11.0  
17.0  
9.0  
11.0  
17.0  
1.  
Minimum Circuit Ampacity.  
2.  
3.  
Dual Element, Time Delay Type.  
HACR type per NEC  
74  
Johnson Controls Unitary Products  
246653-YTG-E-0108  
TABLE 56: ELECTRICAL DATA 40 TON WITH ELECTRIC HEAT AND POWER EXHAUST R22  
COMPRESSORS  
(EACH)  
OD FAN MOTORS  
(EACH)  
MAX  
FUSE  
BREAKER  
SIZE  
ELECTRIC HEAT  
SUPPLY BLOWER  
PWR EXH MOTOR  
1
2
MCA  
/
VOLTAGE  
3
(AMPS)  
OPTION KW STAGES QTY. RLA LRA MCC  
QTY  
FLA  
HP  
FLA  
HP  
FLA  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
24.2  
30.8  
46.2  
24.2  
30.8  
46.2  
24.2  
30.8  
46.2  
24.2  
30.8  
46.2  
24.2  
30.8  
46.2  
24.2  
30.8  
46.2  
24.2  
30.8  
46.2  
24.2  
30.8  
46.2  
22.0  
28.0  
42.0  
22.0  
28.0  
42.0  
22.0  
28.0  
42.0  
22.0  
28.0  
42.0  
22.0  
28.0  
42.0  
22.0  
28.0  
42.0  
22.0  
28.0  
42.0  
22.0  
28.0  
42.0  
231  
238  
255  
249  
255  
271  
265  
272  
287  
285  
291  
307  
231  
238  
255  
249  
255  
271  
265  
272  
287  
285  
291  
307  
225  
231  
247  
241  
247  
261  
256  
262  
276  
273  
279  
293  
249  
255  
273  
267  
273  
287  
282  
288  
302  
299  
305  
319  
250  
250  
300  
250  
300  
300  
300  
300  
300  
350  
350  
350  
250  
250  
300  
250  
300  
300  
300  
300  
300  
350  
350  
350  
250  
250  
250  
250  
250  
300  
300  
300  
300  
300  
300  
350  
250  
300  
300  
300  
300  
300  
300  
300  
350  
350  
350  
350  
10  
30.8  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
46.2  
59.4  
74.8  
30.8  
46.2  
59.4  
74.8  
28.0  
42.0  
54.0  
68.0  
28.0  
42.0  
54.0  
68.0  
E4  
E8  
E4  
E8  
40  
80  
40  
80  
1
2
1
2
4
4
4
4
37.2 239 58.0  
37.2 239 58.0  
37.2 239 58.0  
37.2 239 58.0  
4
4.5  
208-3-60  
4
4
4
4.5  
4.5  
4.5  
230-3-60  
Johnson Controls Unitary Products  
75  
246653-YTG-E-0108  
TABLE 56: ELECTRICAL DATA 40 TON WITH ELECTRIC HEAT AND POWER EXHAUST R22 (CONTINUED)  
COMPRESSORS  
(EACH)  
OD FAN MOTORS  
(EACH)  
MAX  
FUSE  
BREAKER  
SIZE  
ELECTRIC HEAT  
SUPPLY BLOWER  
PWR EXH MOTOR  
1
2
MCA  
/
VOLTAGE  
3
(AMPS)  
OPTION KW STAGES QTY. RLA LRA MCC  
QTY  
FLA  
HP  
FLA  
HP  
FLA  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
11.0  
14.0  
21.0  
107  
110  
118  
115  
118  
125  
122  
125  
132  
131  
134  
141  
125  
128  
136  
133  
136  
143  
141  
144  
151  
150  
153  
160  
158  
161  
170  
167  
170  
177  
175  
178  
185  
183  
186  
193  
110  
125  
125  
125  
125  
125  
125  
150  
150  
150  
150  
150  
125  
150  
150  
150  
150  
150  
150  
150  
175  
175  
175  
175  
175  
175  
175  
175  
175  
200  
200  
200  
200  
200  
200  
225  
10  
14.0  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
21.0  
27.0  
34.0  
14.0  
21.0  
27.0  
34.0  
14.0  
21.0  
27.0  
34.0  
E4  
E8  
E1  
40  
1
2
2
4
4
4
17.2 125 27.0  
17.2 125 27.0  
17.2 125 27.0  
4
2.2  
460-3-60  
80  
4
2.2  
108  
4
2.2  
76  
Johnson Controls Unitary Products  
246653-YTG-E-0108  
TABLE 56: ELECTRICAL DATA 40 TON WITH ELECTRIC HEAT AND POWER EXHAUST R22 (CONTINUED)  
COMPRESSORS  
(EACH)  
OD FAN MOTORS  
(EACH)  
MAX  
FUSE  
BREAKER  
SIZE  
ELECTRIC HEAT  
SUPPLY BLOWER  
PWR EXH MOTOR  
1
2
MCA  
/
VOLTAGE  
3
(AMPS)  
OPTION KW STAGES QTY. RLA LRA MCC  
QTY  
FLA  
HP  
FLA  
HP  
FLA  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
9.0  
11.0  
17.0  
9.0  
80  
90  
10  
11.0  
82  
90  
89  
100  
100  
100  
110  
110  
110  
110  
125  
125  
125  
110  
110  
125  
110  
125  
125  
125  
125  
125  
125  
125  
150  
150  
150  
150  
150  
150  
150  
150  
150  
150  
150  
175  
175  
87  
15  
20  
25  
10  
15  
20  
25  
10  
15  
20  
25  
17.0  
22.0  
27.0  
11.0  
17.0  
22.0  
27.0  
11.0  
17.0  
22.0  
27.0  
11.0  
17.0  
9.0  
89  
95  
E4  
E8  
E1  
40  
1
2
2
4
4
4
12.4  
12.4  
12.4  
80  
80  
80  
19.3  
19.3  
19.3  
4
1.7  
93  
11.0  
17.0  
9.0  
95  
101  
99  
11.0  
17.0  
9.0  
101  
107  
100  
102  
109  
107  
109  
115  
113  
115  
121  
120  
122  
128  
127  
129  
136  
134  
136  
142  
140  
142  
148  
147  
149  
155  
11.0  
17.0  
9.0  
11.0  
17.0  
9.0  
575-3-60  
80  
4
1.7  
11.0  
17.0  
9.0  
11.0  
17.0  
9.0  
11.0  
17.0  
9.0  
11.0  
17.0  
9.0  
108  
4
1.7  
11.0  
17.0  
9.0  
11.0  
17.0  
1.  
Minimum Circuit Ampacity.  
2.  
3.  
Dual Element, Time Delay Type.  
HACR type per NEC  
Johnson Controls Unitary Products  
77  
246653-YTG-E-0108  
TABLE 57: UNIT WEIGHTS  
TABLE 58: SUPPLY FAN MOTOR VFD WEIGHTS  
Supply Fan Motor VFD  
230V  
460V  
575V  
COMPONENT  
Basic Unit  
25 TON  
30 TON  
40 TON  
4410  
Gas Heat  
4565  
4845  
W/O Bypass  
7.5hp  
60  
60  
25  
25  
50  
50  
50  
30  
30  
60  
60  
60  
267 MBH  
533 MBH  
800 MBH  
180  
320  
-
180  
320  
-
180  
320  
450  
10hp  
15hp  
75  
Electric Heat  
20hp  
75  
40KW  
80KW  
108KW  
40  
105  
110  
40  
105  
110  
40  
105  
110  
25hp  
115  
W/Bypass  
7.5hp  
Hot Water Heat  
155  
155  
185  
185  
255  
90  
90  
120  
120  
155  
155  
155  
1 Row Coil  
2 Row Coil  
70  
85  
70  
85  
70  
85  
10hp  
Steam Heat  
85  
Blower  
15hp  
140  
140  
140  
1 Row Coil  
85  
85  
20hp  
Forward Curve Fan (Std Fan)  
FC IGV  
0
0
0
25hp  
155  
135  
155  
155  
135  
155  
175  
155  
180  
Air Foil Fan  
AF IGV  
TABLE 59: EXHAUST FAN MOTOR VFD WEIGHTS  
Exhaust Fan Motor  
W/O Bypass  
230V  
460V  
575V  
Motor - Supply Fan  
7.5hp  
10hp  
15hp  
20hp  
25hp  
110  
145  
200  
240  
-
-
-
145  
200  
240  
300  
145  
200  
240  
300  
5hp  
7.5hp  
10hp  
15hp  
15  
50  
50  
65  
10  
15  
15  
40  
20  
20  
20  
50  
Supply Fan Motor VFD  
See Table 58  
Refrigeration  
Hi Cap. Evap. Coil  
T-Coat Evap.  
T-Coat cond.  
-
50  
30  
30  
10  
15  
40  
40  
10  
NOTE: If the Millennium is VAV with ERV, add the weight of an  
exhaust VFD - it will be in the unit.  
32  
32  
10  
Hot Gas Bypass  
CENTER OF  
Low Ambient Head Pressure Control  
C
GRAVITY  
208-230/380/460  
575  
5
25  
5
25  
5
25  
BACK  
CONDENSER  
COIL END  
B
Filters  
D
6" Rigid  
70  
70  
70  
Exhaust1  
X
Exhaust Type  
92  
"
Barometric  
Modulated  
Exhaust Motor  
45  
140  
65  
275  
65  
275  
Y
A
FRONT  
240"  
5hp  
7.5hp  
10hp  
80  
80  
110  
145  
80  
110  
145  
200  
110  
145  
200  
FIGURE 27 - CENTER OF GRAVITY  
TABLE 60: UNIT CENTER OF GRAVITY  
15hp  
200  
Exhaust Motor VFD  
See Table 59  
Economizer  
25 TON  
30 TON  
40 TON  
X
Std. Econ.  
Econ. w/ERV  
235  
235  
50  
235  
50  
MODEL  
X
Y
X
Y
Y
50  
Control  
15  
BASIC UNIT  
99”  
48”  
100”  
47”  
96”  
46"  
BASIC UNIT /W  
ECON.  
Disconnect  
110V outlet  
Optilogic  
15  
55  
20  
15  
55  
20  
110”  
48”  
48”  
110”  
47”  
46”  
100”  
46"  
55  
20  
BASIC UNIT /W  
ECON. & GAS OR  
ELECT. HEAT,  
STEAM OR HOT  
WATER HEAT  
104”  
118”  
104”  
114”  
99”  
45"  
45"  
Roof Curb  
415  
Partial Curb  
415  
415  
1.  
BASIC UNIT /W  
ECON. & GAS OR  
ELECT. HEAT, &  
POWER EXHAUST  
If ERV and Supply Fan VAV are selected, add the weight of an  
Exhaust VFD, Table 58.  
47”  
46”  
111”  
78  
Johnson Controls Unitary Products  
         
246653-YTG-E-0108  
TABLE 61: UNIT CORNERWEIGHT  
25 TON  
30 TON  
40 TON  
UNIT  
DESCRIPTION  
A
B
C
D
A
B
C
D
A
B
C
D
BASIC UNIT  
870  
949  
1352  
1239  
930  
972  
1360  
1328  
1303  
969  
969  
1454  
1454  
BASIC UNIT WITH  
ECONOMIZER  
1018  
1111  
1313  
1203  
1076  
1124  
1272  
1058  
1058  
1482  
1482  
BASIC UNIT WITH  
ECONOMIZER AND  
GAS OR ELECTRIC  
HEAT  
994  
1084  
1418  
1300  
1073  
1073  
1403  
1410  
1403  
1102  
1055  
1503  
1570  
BASIC UNIT WITH  
ECONOMIZER AND  
GAS OR ELECTRIC  
HEAT AND POWER  
EXHAUST  
1220  
1275  
1318  
1262  
1275  
1275  
1410  
1335  
1278  
1485  
1551  
NOTES:Basic Unit = cooling only, 10hp FC fan.  
+ Econ = +235lb  
+ Heat = single stage gas, 180 lb  
+ Power Exhaust = modulating 7.5hp  
TABLE 62: INDOOR SOUND POWER RATING  
SOUND POWER (DB 10-12 WATTS)  
OCTAVE BAND CENTERLINE FREQUENCY (HZ)  
ESP  
BLOWER  
MODEL NUMBER  
CFM  
DBA  
IWG  
1.5  
RPM  
BHP  
63  
125  
88  
250  
85  
500  
85  
1000  
80  
2000  
78  
4000  
74  
8000  
Y32  
Y33  
Y34  
10,000  
12750  
17500  
750  
840  
800  
7.5  
12.8  
20  
90  
93  
95  
68  
71  
72  
87  
90  
91  
1.5  
91  
88  
88  
83  
81  
77  
1.3  
92  
89  
89  
84  
83  
78  
Sound Power Ratings for Supply Air Blowers in our Millen-  
nium Units with High Gas Heat, Economizer, 2: T/A Filters  
and Wet DX Sound power calculations complements of Lau’s  
revised “Whirlwind” application selection software for air mov-  
ing components.  
The sound ratings above occur at the blower wheel. To deter-  
mine the sound rating at a unit’s supply and return air duct  
connection, subtract the attenuation factors listed below.  
TABLE 63: ATTENUATION FACTORS  
OCTAVE BAND CENTERLINE FREQUENCY (HZ)  
63  
125  
250  
500  
1000  
12  
2000  
4000  
8000  
LOCATION  
SOUND ATTENUATION (DB WATTS)  
SUPPLY AIR  
RETURN AIR  
11  
13  
13  
15  
18  
22  
10  
23  
21  
25  
21  
25  
23  
29  
23  
29  
TABLE 64: OUTDOOR SOUND POWER RATING  
OCTAVE BAND CENTERLINE FREQUENCY (HERTZ)  
MODEL  
65  
125  
250  
500  
1000  
2000  
4000  
8000  
db(A)  
SOUND POWER LEVEL, DB (10)-12 WATTS  
Y32  
Y33  
Y34  
88  
87  
88  
91  
90  
91  
89  
88  
89  
86  
86  
86  
82  
82  
82  
79  
80  
80  
76  
77  
77  
72  
73  
73  
88  
88  
88  
NOTE: These values have been accessed using a model of  
sound propagation from a point source into the  
hemispheric free field (AMCA 303-79). The dBA val-  
ues provided are to be used for reference only. Cal-  
culation of dBA values cover matters of system  
design, and the fan manufacturer has no way of  
knowing the details of each system. This constitutes  
an exception to any specification or guarantee  
requiring a dBA value or sound data in any other  
form than sound power level ratings.  
Johnson Controls Unitary Products  
79  
       
246653-YTG-E-0108  
EVAPORATOR COIL  
AND DRAINPAN ACCESS  
POWER & CONTROL WIRING  
FILTER ACCESS  
COMPRESSOR ACCESS  
REAR  
RIGHT  
SIDE  
HEAT SECTION  
FRONT  
LEFT SIDE  
POWER EXHAUST ACCESS  
HEAT SECTION  
EVAPORATOR COIL  
AND DRAINPAN ACCESS  
FILTER DRIERS  
FILTER ACCESS  
REAR  
SUPPLY BLOWER & MOTOR  
FIGURE 28 - COMPONENT LOCATION  
80  
Johnson Controls Unitary Products  
 
246653-YTG-E-0108  
NOTE:  
RETURN AIR  
SUPPLY AIR  
FACTORY INSTALLED POWER  
EXHAUST CANNOT BE ORDERED  
WITH END RETURN.  
REAR  
RIGHT SIDE  
SEE  
DETAIL  
C
SEE  
DETAIL  
B
7-7/8"  
64"  
75.6"  
24.9"  
6.25"  
100.10"  
128.50"  
8.15"  
76-3/8  
92"  
LEFT SIDE  
FRONT  
RIGHT  
SIDE  
4.5"  
REAR  
OPEN  
3.625"  
80.93"  
26"  
SEE  
DETAIL  
A
71.61"  
12"  
MIN  
6.46"  
15.89"  
C
L
88.7"  
FRONT  
LEFT SIDE  
240"  
TO GAS VALVE  
MANIFOLD  
2-1/2”  
DIA. HOLES  
3-5/8"  
4-5/8”  
7”  
28”  
BASE RAIL  
6.46"  
3-1/16"  
11”  
BASE RAIL  
2-1/2"  
1-1/2" FPT  
1-1/4” NPT  
DETAIL B  
(ELECTRICAL CONNECTION)  
DETAIL A  
DETAIL C  
(GAS CONNECTION  
THROUGH CURB)  
(DRAIN CONNECTION)  
FOR COOLING ONLY AND ALL HEATING APPLICATIONS  
FIGURE 29 - END RETURN, BOTTOM SUPPLY  
Johnson Controls Unitary Products  
81  
 
246653-YTG-E-0108  
RETURN AIR  
SUPPLY AIR  
REAR  
RIGHT  
SIDE  
SEE  
DETAIL  
C
SEE  
DETAIL  
B
64"  
100.10"  
128.50"  
FRONT  
92"  
LEFT  
SIDE  
RIGHT  
SIDE  
REAR  
4.5"  
OPEN  
3.625"  
80.93"  
4.5"  
SEE  
DETAIL  
A
26"  
71.61"  
6.46"  
12"  
MIN  
15.89"  
88.7"  
38.59"  
127.5"  
83"  
FRONT  
LEFT  
SIDE  
C
240"  
L
C
L
4.5"  
TO GAS VALVE  
MANIFOLD  
2-1/2”  
DIA. HOLES  
3-5/8"  
4-5/8”  
7”  
BASE RAIL  
28”  
6.46"  
3-1/16"  
BASE RAIL  
11”  
1-1/4" FPT  
1-1/2" FPT  
1-1/4” NPT  
DETAIL B  
(ELECTRICAL CONNECTION)  
DETAIL A  
(DRAIN CONNECTION)  
DETAIL C  
(GAS CONNECTION  
THROUGH CURB)  
FOR COOLING ONLY AND ALL HEATING APPLICATIONS  
FIGURE 30 - BOTTOM SUPPLY AND RETURN  
82  
Johnson Controls Unitary Products  
 
246653-YTG-E-0108  
FRONT SUPPLY: FOR COOLING ONLY APPLICATIONS  
REAR SUPPLY: FOR COOLING ONLY OR GAS HEAT APPLICATIONS  
FRONT  
REAR  
RETURN AIR  
SUPPLY AIR  
REAR  
RIGHT SIDE  
26"  
55"  
64"  
75.6"  
100.10"  
8.15"  
SEE  
128.50"  
DETAIL  
92"  
B
SEE  
DETAIL  
C
FRONT  
LEFT SIDE  
RIGHT  
SIDE  
REAR  
OPEN  
3.625"  
80.93"  
4.5"  
SEE  
DETAIL  
A
12"  
MIN  
6.46"  
TO GAS VALVE  
MANIFOLD  
38.59"  
83"  
FRONT  
2-1/2”  
DIA. HOLES  
240"  
LEFT SIDE  
4.5"  
3-5/8"  
4-5/8”  
7”  
28”  
BASE RAIL  
6.46"  
3-1/16"  
11”  
BASE RAIL  
2-1/2"  
1-1/2" FPT  
1-1/4” NPT  
DETAIL C  
(GAS CONNECTION  
THROUGH CURB)  
DETAIL B  
(ELECTRICAL CONNECTION)  
DETAIL A  
(DRAIN CONNECTION)  
FIGURE 31 - BOTTOM RETURN, FRONT & REAR SUPPLY  
Johnson Controls Unitary Products  
83  
 
246653-YTG-E-0108  
FRONT SUPPLY: FOR COOLING ONLY APPLICATIONS  
REAR SUPPLY: FOR COOLING ONLY OR GAS HEAT APPLICATIONS  
26"  
55"  
REAR  
RETURN AIR  
SUPPLY AIR  
REAR  
RIGHT  
SIDE  
26"  
55"  
7-7/8"  
64"  
75.6"  
100.10"  
24.9"  
6.25"  
8.15"  
76-3/8  
92"  
128.50"  
SEE  
DETAIL  
B
SEE  
LEFT  
SIDE  
FRONT  
DETAIL  
C
RIGHT  
SIDE  
REAR  
OPEN  
3.625"  
80.93"  
SEE  
DETAIL  
A
12"  
MIN  
6.46"  
FRONT  
TO GAS VALVE  
MANIFOLD  
LEFT  
SIDE  
240"  
2-1/2”  
DIA. HOLES  
3-5/8"  
7”  
4-5/8”  
28”  
BASE RAIL  
11”  
6.46"  
3-1/16"  
1-1/4” NPT  
1-1/2" FPT  
2-1/2"  
BASE RAIL  
DETAIL C  
(GAS CONNECTION  
THROUGH CURB)  
DETAIL A  
(DRAIN CONNECTION)  
DETAIL B  
(ELECTRICAL CONNECTION)  
FIGURE 32 - END RETURN, FRONT & REAR SUPPLY  
84  
Johnson Controls Unitary Products  
 
246653-YTG-E-0108  
259.68  
35.42  
39.31  
93.43  
241.22  
FIGURE 33 - MILLENNIUM OVERHEAD VIEW  
GAS HEAT  
BLOWER  
SECTION  
EVAPORATOR  
SECTION  
FILTER  
SECTION  
ECONOMIZER POWER  
EXHAUST SECTION  
CONDENSER SECTION  
SECTION  
FIGURE 34 - MILLENNIUM MAJOR COMPONENT LAYOUT  
Johnson Controls Unitary Products  
85  
   
246653-YTG-E-0108  
Hinged,  
Tool-Free  
Door  
Optional  
Hinged,  
Tool-Free  
Door  
Hinged,  
Tool-Free  
Door  
Hinged, Tool-Free  
w/PE Option  
1
2
3
4
BACK VIEW  
Hinged,  
Tool-Free  
Door  
Optional  
Hinged,  
Tool-Free  
Door  
Hinged,  
Tool-Free  
Door  
Hinged,  
Tool-Free  
w/Gas  
or Other  
Heat Source  
Hinged, Tool-Free  
w/PE Option  
5
6
7
8
9
FRONT VIEW  
1. STD Cabinet Option includes Hinged, Tool-Free  
Doors # 1, 3, 6, 8.  
4. Doors 1, 2, 3, 6, 7, 8 & 9 are 56.31 inches high by  
27.33 inches wide.  
2. Premium Cabinet Option includes Hinged, Tool-Free  
Doors # 1, 2, 3, 6, 7, 8.  
5. Doors 4 & 5 are 26.5 inches high by 33.63 inches  
wide.  
3. Doors # 4, 5, 9 are dependent upon unit Heating  
and Power Exhaust Options.  
FIGURE 35 - MILLENNIUM CABINET DOOR CONFIGURATION  
86  
Johnson Controls Unitary Products  
 
246653-YTG-E-0108  
FIGURE 36 - CLEARANCES - HOOD/ECONOMIZER & MOTOR DRIVE - SIDE  
FIGURE 37 - CLEARANCES - HOOD/ECONOMIZER & MOTOR DRIVE - FRONT & END  
Johnson Controls Unitary Products  
87  
   
246653-YTG-E-0108  
2
3
5
.
0
0
9
5
.
0
9
3
8
.
5
9
2
6
.
0
0
7
1
.
6
1
R
E
T
U
R
N
S
U
P
P
L
Y
8
3
.
0
0
A
I
R
A
I
R
O
P
E
N
I
N
G
O
P
E
N
I
N
G
8
7
.
0
0
1
1
.
3
9
4
.
0
0
2
.
0
0
1
4
.
0
0
I
n
s
u
l
a
t
i
o
n
E
d
g
e
P
r
o
t
e
c
t
o
r
(
S
h
e
e
t
M
e
t
a
l
N
o
s
e
P
i
e
c
e
)
A
A
F
I
E
L
D
S
U
P
P
L
I
E
D
T
y
p
i
c
a
l
I
n
s
u
l
a
t
i
o
n
D
U
C
T
A
B
A
B
-
-
I
I
F
F
U
U
N
N
I
I
T
T
I
I
S
S
N
A
O
T
I
N
S
T
A
L
L
E
D
S
E
E
S
E
C
T
I
O
N
"
A
-
A
"
L
R
E
A
D
Y
I
N
S
T
A
L
L
E
D
N
O
T
E
:
P
r
o
t
e
c
t
i
n
s
u
l
a
t
i
o
l
n
w
i
t
h
a
s
h
e
e
t
m
e
t
a
l
n
d
o
u
s
c
e
t
p
i
e
c
k
e
.
w
h
e
n
i
n
s
t
a
l
i
n
g
a
i
n
t
e
r
n
a
l
l
y
i
n
s
u
l
a
t
e
d
w
o
r
T
Y
P
I
C
A
L
D
U
C
T
I
N
S
T
A
L
L
A
T
I
O
N
S
B
A
S
E
R
A
I
L
B
A
S
E
R
A
I
L
C
R
O
S
S
-
S
E
C
T
I
O
N
(
Y
O
R
K
U
N
I
T
)
1
.
2
5
"
C
U
R
B
G
A
S
K
E
T
1
.
7
5
"
4
.
6
3
"
2
.
5
0
"
1
.
5
0
"
2
"
X
4
"
N
A
I
L
E
R
(
1
4
.
0
0
)
2
.
0
0
"
1
4
G
A
.
G
A
L
V
S
T
E
E
L
R
O
O
F
C
U
R
B
S
E
C
T
I
O
N
"
A
-
A
"
FIGURE 38 - PARTIAL ROOF CURB MODEL 1RC0455P  
88  
Johnson Controls Unitary Products  
 
246653-YTG-E-0108  
meet NFPA-90A regulations for smoke and flame spread rat-  
ings. The cabinet corner post and the intermediate side sup-  
ports shall be 16 gauge steel. All access doors shall be 18  
gauge on the exterior surfaces, and 20 gauge on the interior.  
Floor shall be 18 gauge, and 24 gauge. All serviceable sec-  
tions shall have hinged access doors with latches on both  
sides of the unit. All access doors shall be constructed of 20  
gauge steel on the outside, with 24 gauge on the inside. Each  
door shall seal against a rubber gasket to prevent air and  
water leakage. The roof shall be double wall, with 18 gauge  
on the external surface and 24 gauge on the interior. The roof  
shall be formed with a 45 degree drip lip overhanging the  
sidewalls to prevent precipitation drainage from streaming  
down the side of the unit. Roof sections shall be connected  
together via integral channels fastened with screws and  
sealed with rubber gasketing. Each fastened seam shall be  
further protected by a sheet metal channel covering the full  
length of the gasket surface, making a completely water tight  
seal.  
GUIDE SPECIFICATIONS - YORK  
MILLENNIUM 25, 30, & 40 TON UNITS  
GENERAL  
Units shall be manufactured by Johnson Controls Unitary  
Products in an ISO 9001 certified facility. Introducing the  
YORK Millennium 25, 30, & 40 ton rooftop line - units  
designed to provide peak performance and value both today  
and for years to come. Millennium units are manufactured at  
an ISO 9001 registered facility, and each rooftop is com-  
pletely computer-run tested prior to shipment. The Millennium  
is designed to be flexible enough to meet your needs today  
and in the future. The true value of York's Millennium is that it  
can be designed to fit any need, from cooling only, constant  
volume applications to variable air volume systems with vari-  
able frequency drive.  
DESCRIPTION  
SUPPLY AIR SYSTEM  
SUPPLY AIR FAN  
Supply York Millennium packaged rooftop system in accor-  
dance with the capacities in the plans. Units shall be rated by  
the manufacturer at a minimum (30/40 Ton units: 9.5 EER /  
25 Ton units: 10 EER) according to ARI 360. Units shall be  
shipped in a single package, fully charged with R-22 refriger-  
ant. The manufacturing facility shall be registered under ISO  
9001 Quality Standards for Manufacturing. Units shall carry  
both ETL and CSA safety approval ratings. Tags and decals  
to aid in the service or indicate caution areas shall be pro-  
vided. Installation and maintenance manuals shall be sup-  
plied with each unit. Units shall be capable of providing  
mechanical cooling down to 40°F (0°F with low ambient kit).  
Unit shall be capable of starting and running at 125°F. Unit  
electric and gas connections shall be either through the curb  
or the side of the unit.  
Fans shall be centrifugal type - Class I or Class II, statically  
and dynamically balanced in the factory. Fan wheels shall be  
designed for continuous operation at the maximum rate of fan  
speed and motor HP. The fan and motor assembly shall be  
mounted on a common base to allow consistent belt tension  
with no relative motion between the fan and motor shafts.  
The entire assembly shall be isolated from the unit base with  
(optional 1”, 2" deflection springs or rubber isolators). The fan  
discharge shall be connected to the cabinet through a rein-  
forced neoprene flexible connection to eliminate vibration  
transmission from the fan to the unit casing. Fans shall be  
double-width, double-inlet with forward curved blades.  
OPTIONAL  
CONSTRUCTION  
Base  
On variable air volume units without variable frequency  
drives, fans shall be provided with heavy gauge, corrosion  
resistant blades, with zinc-plated steel inter-locking operating  
mechanism. Both inlet vanes must operate from a single  
shaft and be synchronized for precise control.  
The base rail shall be constructed of 12 gauge galvanized  
steel, extending the full perimeter of the unit. All components  
shall be supported from the base, and the base shall include  
integral lifting lugs. The unit base rail shall overhang the roof  
curb for water runoff and shall have a fabricated recess with a  
continuous flat surface to seat on the roof curb gasket, pro-  
viding a positive, weather tight seal between the unit and the  
curb.  
Units equipped with variable frequency drive on supply fan  
must be controlled by a duct static transducer providing a 2-  
10 VDC signal to the drive. Supply fan variable frequency  
drives shall have factory option of being equipped with a  
manual drive bypass.  
Casing  
BEARINGS AND DRIVES  
The unit cabinet shall be double wall construction to provide  
both maximum resistance to bacterial growth in the air stream  
and superior structural integrity. All sheet metal shall be G90  
mill galvanized sheet metal, formed and reinforced to provide  
a rigid assembly. Sheet metal shall be cleaned in an alkaline  
and zinc phosphate bath, and the exterior surfaces shall be  
coated with a 1.5 mil powder paint, capable of withstanding  
1000 salt spray hours in accordance with ASTM B-117. The  
unit shall be insulated with 1-1/2", 1 pound density fiberglass  
insulation between the two sheet metal skins. Insulation shall  
Bearings shall be self-aligning pillow-block re-greasable ball  
bearings with an average life expectancy of 200,000 hours.  
Grease fittings shall be accessible through access doors. Fan  
motors shall be NEMA designed, Standard efficiency (option,  
Hi-efficiency) ball bearing type with electrical characteristics  
and horsepower as specified. Motors shall be 1750 RPM,  
open drip proof type. The motor shall be located within the  
unit on an adjustable, heavy steel base. All fan motor drives  
Johnson Controls Unitary Products  
89  
                   
246653-YTG-E-0108  
shall be selected for a minimum service factor of 1.2 and  
have fixed pitched sheaves.  
Barometric Relief (Optional)  
Building air exhaust shall be accomplished through baromet-  
ric relief dampers installed in the return air plenum. The  
dampers will open relative to the building pressure. The  
opening pressure shall be adjustable.  
AIR FILTERING SYSTEM  
All filter holding frames shall be of heavy duty construction  
designed for industrial applications. All filters shall be either  
side accessible or front loading with access doors provided  
on both sides of the filter section. All filter media shall be  
Class II listed under UL Standard 900. Filter efficiencies shall  
be rated in accordance with ASHRAE Standard 52-76 2"  
Throwaway Filters with fiberglass media multiple shall be  
standard  
Exhaust Air Fans (Optional)  
General - forward curved centrifugal fan(s) shall be installed  
in the return air plenum for positive power exhaust. Fans shall  
be on a common shaft, driven by a single motor. The fans,  
motors and drives shall be of the same quality and design as  
specified for the Supply Air Fan, except the fans shall be  
Class I. Fans shall be capable of exhausting up to 100% of  
the nominal CFM of the unit. Non-modulating Exhaust - Units  
with non-modulating power exhaust shall have a barometric  
relief damper to prevent outside air from entering in the off  
cycle. The fans shall cycle on and off with building pressure.  
Modulating Operation - The fans shall be capable of modulat-  
ing the amount of air from 0% to 100% of nominal CFM. Mod-  
ulation shall be through discharge dampers or variable  
frequency motor speed modulation. Dampers or VFD shall be  
controlled by static pressure in the conditioned space or  
return air duct.  
OPTIONAL  
Two inch pleated, throwaway filters with 30% efficiency. Rigid  
filters shall be high performance, expanded area, disposable  
type filters. Rigid filter sections shall be preceded by a 2  
throwaway prefilter assembly. Filter efficiency shall be 95%  
(Option: 65%) based on ASHRAE Standard 52-76.  
AIR INLET SYSTEM  
General  
ENERGY RECOVERY VENTILATION (FIELD  
INSTALLED OPTION)  
Outside Air inlet openings shall be covered by a factory  
installed rain hood permanently attached to the cabinet to  
prevent windblown precipitation from entering the unit. The  
rain hoods on the front and back of the unit shall be rotated  
into the cabinet and secured for shipment so that upon instal-  
lation they need only be rotated upwards and screwed into  
place. The outside air hood shall contain a removable and  
cleanable filter with an efficiency rating of 50% based on  
ASHRAE 52- 76. All damper assemblies shall be of low leak  
design. Damper blades shall be fabricated from a minimum of  
16 gauge galvanized steel. Blade ends and edges shall be  
covered with vinyl seals. Damper shafts shall be fabricated  
from solid steel and mounted in the frame with bronze bear-  
ings. On all units not equipped with an economizer, an option  
shall be available for a manually adjustable outside air  
damper shall be capable of admitting 0-25% outside air.  
General  
The packaged rooftop unit shall have attached at the jobsite a  
powered exhaust combined with an air intake through a rotat-  
ing energy recovery wheel, which captures sensible and  
latent heat from the exhaust air stream and returns it to the  
incoming air stream. The energy recovery module will be con-  
tained in a separate enclosure designed to attach to the end  
of the Millennium packaged rooftop unit equipped with Sim-  
plicity® Elite™ control.  
The Energy Recovery Ventilation module will be capable of  
exhausting up to 8,000 (13,000) CFM.  
Control parameters for the ERV will be preset in the unit con-  
trol.  
Economizer (Optional)  
An economizer shall have outdoor air and return air dampers  
(optional standard or low leak type) that are interlocked and  
positioned by fully modulating, solid state damper actuators.  
The actuators shall be spring loaded so that the outside air  
damper will close when power to the unit is interrupted. The  
operation of the economizer shall be fully integrated into the  
cooling control system. The economizer shall be available for  
control via a dry bulb sensor (Optional: single or dual  
enthalpy sensors).  
HEATING SYSTEM (OPTIONAL)  
Gas-fired Heating Section  
One or more gas-fired heating modules shall be installed to  
provide the heating requirements per the schedule shown on  
the plans. The heat exchanger shall be of tubular design.  
Tubes shall be 2-1/4" OD and constructed of minimum 20  
gauge, G160 aluminized steel (1.6 mil aluminum silicone  
alloy) for corrosion resistance (Optional: 409 Stainless Steel).  
Flue baffles shall be made of 430 stainless steel. Each gas-  
fired heat module shall have an induced draft combustion fan  
with energy efficient intermittent pilot spark ignition and  
redundant main gas valves with pressure regulator. Units with  
standing pilot ignition shall not be acceptable. An induced  
draft fan shall be provided to maintain a positive flow of air  
RELIEF SYSTEM (Optional)  
All units with relief must have an economizer.  
90  
Johnson Controls Unitary Products  
                       
246653-YTG-E-0108  
through each tube, to expel the flue gas and to maintain a  
negative pressure within the heat exchanger relative to the  
conditioned space. Induced draft fans shall be direct-drive.  
One (1) high limit controller per heating module, with auto-  
matic reset to prevent the heat exchanger from operating at  
an excessive temperature will be installed. A pressure switch  
on the combustion section must be provided to prevent igni-  
tion until sufficient air flow is established through the heat  
exchanger. Secondary airflow safety shall be provided by roll-  
out switch protection. The rollout switch shall discontinue fur-  
nace operation if the flue becomes restricted. Units shall ship  
with an external flue to be shipped in the unit and mounted on  
the job site. The flue shall discharge products of combustion  
above the unit, preventing recycling of corrosive combustion  
gases back through the heat exchanger. Gas heating sec-  
tions shall be both ETL and CSA approved to both US and  
Canadian safety standards.  
fully drawn collars to accurately space fins, and to form a pro-  
tective sheath for the primary surface. A structural galvanized  
steel casing shall protect the coil. Tube sheets on each end  
shall have drawn collars to support tubes. An intermediate  
coil support shall be provided. The coil shall be circuited to  
provide free draining and venting, through one vent and  
drain. Completed coil, including headers, connections and  
return bends shall be tested with 325 pounds compressed air  
under water. Coils shall be designed for operation at 250 psig  
design working pressure.  
Steam Heating Coil  
The manufacturer shall furnish and factory install a steam  
heating coil in the rooftop units, as described in the following  
specifications. Steam coil capacities and pressure drops shall  
be certified in accordance with ARI standard 410. The steam  
coil shall be constructed in the non-freeze style. The steam  
coil shall have six fins per inch, and 2" inlet, and 1 1/2" outlet  
connection. Tubes shall be 1" OD seamless copper tubing  
with a minimum wall thickness of 0.035" and expanded into  
the fin collars for maximum fin-tube bond. Inner distributing  
tubes shall be 5/8" OD seamless copper tubing with a mini-  
mum wall thickness of 1/4". The copper to copper joints shall  
be joined with high temperature, silver solder. Corrugated fins  
with integral spacing collars shall cover the entire tube sur-  
face. Headers shall be constructed of seamless copper. The  
header tube holes shall be extruded providing better tube to  
header contact for a stronger braze connection. All header  
connections shall be of red brass or steel, with male pipe  
threads and silver braze to headers. Casing shall be 16  
gauge galvanized steel. Chafing shall be prevented by  
extruding and flaring the holes in the tube sheet and interme-  
diate tube sheet. The core shall be pitched in the direction of  
the condensate connection for proper drainage. The com-  
pleted coil (including headers and connections) shall be  
tested underwater with 325 lbs. compressed air to ensure a  
leak free coil.  
Optional Modulating Furnace control or Single Stage control  
available.  
Electric Heating Section  
An electric slip-in heater shall be installed within the rooftop  
unit to provide the heating requirements per the schedule  
shown on the plans. The electric heater shall be wired in such  
a manner as to provide two equal steps of capacity (80 and  
108 kW) or a single step of capacity (40 kW). The furnace  
shall be an industrial grade design using an open coil(s)  
made of the highest grade resistance wire containing 80%  
nickel and 20% chromium. The resistance coil(s) shall be  
adequately supported in the air stream using ceramic bush-  
ings in the supporting framework. Terminals of the coil(s)  
shall be stainless steel with high temperature ceramic bush-  
ings. The primary high temperature protection shall be an  
automatic reset type thermal cut out. Secondary protection  
shall be an automatic reset type thermal cut out. Secondary  
protection shall be a replaceable thermal link. The operation  
of the electric heater shall be an integral part of the roof top  
control system. Power connection to the strip heater shall be  
through the single power point connection for the entire unit.  
Electric heat shall be ETL certified to both US and Canadian  
safety standards.  
REFRIGERATION SYSTEM  
Units shall have two (25 ton), three (30 ton) or four (40 ton)  
independent refrigerant circuits for maximum load-matching  
capability. Each refrigerant circuit shall be controlled with a  
balance-port thermal expansion valve for maximum control at  
low load conditions.  
Hot Water Heating Coil  
The manufacturer shall furnish and factory install a hot water  
coil in the rooftop units, as described in the following specifi-  
cations. Water coil capacities and pressure drops shall be  
certified in accordance with ARI Standard 410. The hot water  
coil shall have eight fins per inch, 2 tubes per circuit, and 2"  
inlet and outlet connection. Primary surface shall be 1/2" OD  
copper tube, staggered in direction of airflow. Tubes shall be  
mandrel expanded to form fin bond and provide burnished,  
work-hardened interior surface. Return bends shall be die  
formed and silver-brazed to tubes. Headers shall be of heavy  
seamless copper tubing, silver-brazed to tubes. Connections  
shall be of red brass, with male pipe threads, silver brazed to  
headers. Connections also have 1/4" FPT drain plug on each  
connection. Extended surface shall consist of die-formed,  
continuous, aluminum fins with formed channels, and surface  
treatment to minimize moisture carry-over. Fins shall have  
Evaporator Coils  
Evaporator coils shall be direct expansion type with inter-  
twined circuiting to assure complete coil face activity during  
part load operation. Coil fins shall be enhanced aluminum  
type. Coil types shall be 3/8” OD copper, internally enhanced  
and mechanically expanded to bond with the fins. Coil casing  
shall be fabricated from heavy gauge galvanized steel. All  
coils shall be pressure tested at a minimum of 450 PSIG. A  
galvanized powder painted steel drain pan shall be provided  
under the entire length and width of the evaporator coil,  
including all return bends. The main drain pan shall be sloped  
a total of 1/4” per foot towards the drainage point. Main drain  
pan shall be easily cleanable in the field. The condensate  
drain opening shall be flush with the bottom of the drain pan  
Johnson Controls Unitary Products  
91  
         
246653-YTG-E-0108  
to allow complete drainage. Coils in excess of 48 inches high  
shall have an intermediate drain pan, also fabricated of galva-  
nized powder painted steel extending the entire finned length  
of the coil to provide better water drainage. Drainage from the  
intermediate drain pan shall be to the primary drain pan.  
OPTIONAL: Drain pans shall be constructed of stainless  
steel. OPTIONAL: Evaporator coils shall be protected by the  
Technicoat 10-1 four coat process. Coils shall be dipped in a  
phenolic coating, which provides substantial resistance to  
corrosion of aluminum and copper. OPTIONAL: Copper-tube/  
Copper-finned evaporator coil assemblies.  
CONTROLS  
GENERAL DESCRIPTION  
Equipment with Simplicity® as standard shall be factory run-  
tested through the control, after the test is complete; there will  
be no wires to re-connect. All control wiring points shall be  
tested and verified through communication.  
The control shall be UL or CSA recognized. The control shall  
be manufactured in a manufacturing facility that is certified to  
ISO 9001.  
Compressors  
COMPRESSOR CONTROL  
Units shall have two (25 ton), three (30 ton) or four (40 ton)  
industrial duty hermetic scroll compressors, independently  
piped and charged. Compressor frame shall be cast iron, with  
cast iron fixed and orbiting scrolls. Compressors shall be  
internally protected with thermal pressure relief. Each com-  
pressor shall include a discharge line check valve.Compres-  
sors shall be vibration isolated from the unit, and installed in  
an easily accessible area of the unit.  
The control shall have a five-minute Anti-Short Cycle Delay to  
prevent excessive compressor cycling. The control shall  
have a three-minute minimum run time to insure that oil gets  
returned to the compressor each time it starts. The minimum  
runtime shall be programmable up to 10 minutes.  
The control shall monitor the High and Low Pressure  
switches separately for each refrigeration circuit. The control  
shall have a 30 second Low Pressure Switch bypass when it  
starts any compressor.  
Condenser Coils  
Condenser coils shall have 3/8” seamless copper tubes,  
arranged in staggered rows, mechanically expanded into alu-  
minum fins. Coils shall be protected from hail damage with a  
V configuration, with individual flat coils rotated 30 from the  
vertical plane for each condensing circuit. Condensing coils  
shall have an integral subcooler for more efficient, stable  
operation. OPTIONAL: Condenser coils shall be protected by  
the TechniCoat 10-1 four coat process. Coils shall be dipped  
in a phenolic coating, which provides substantial resistance  
to corrosion of aluminum and copper. OPTIONAL: Copper-  
tube/Copper-finned condenser coil assemblies.  
A hard compressor lockout shall occur if the control detects  
the same switch trip three times in a two-hour window, which  
starts when the first trip occurs. On the first and second trips,  
the control will turn the compressor off and wait five-minutes  
after the switch re-closes, before restarting the compressor.  
The control shall be capable of operating both compressors  
and the economizer when there is a call for both stages of  
cooling.  
The control shall have a means of locking out mechanical  
compression below a programmable low ambient trip point.  
This must be done without adding extra components to the  
unit.  
Condenser Fans and Motors  
Condenser fans shall be direct drive, propeller type, discharg-  
ing vertically. Condenser fan motors shall be 3 phase, totally  
enclosed air over (TEAO) type, with built in thermal overload  
protection.  
The control shall have a means of locking out the mechanical  
compression when the economizer is operating in free cool-  
ing mode without additional components  
Refrigerant Piping  
All interconnecting piping between refrigeration components  
shall be copper tubing with brazed joints. Each refrigerant cir-  
cuit shall be equipped with liquid line filter drier, and moisture  
indicating sight glass. Each circuit shall also have both high  
and low pressure switches installed on either side of the com-  
pressor and include shrader depressors for replacement of  
the pressure switches without removing charge. All small  
diameter distributor tubing to the evaporator coil shall be pro-  
tected by polyurethane sleeves over the length of the tubing  
to prevent the tubes from copper-to-copper contact during  
shipment or operation.  
The control shall have a means of starting the compressor  
before the indoor Fan comes on w1hen operating with a  
Thermostat in the AUTO FAN mode.  
FAN CONTROL  
The control shall have fully adjustable Fan ON and Fan OFF  
delays for both Heating and Cooling settable at the control or  
via communication.  
The control's default Fan OFF delay for Cooling shall be 30  
seconds to take advantage of the remaining capacity in the  
coil after the compressor has been turned off.  
Hot Gas Bypass (Optional on CV; standard on VAV)  
Unit shall have hot gas bypass factory installed on the lead  
compressor.  
92  
Johnson Controls Unitary Products  
                 
246653-YTG-E-0108  
The control shall lock on the Fan if the high temperature limit  
trips three times in one hour of operation.  
The control will have low voltage protection for the contactors  
and will not energize a contactor if the voltage is below 19.2  
VAC, to insure contactor pull-in. If the control has a compres-  
sor contactor energized when the voltage drops, it shall not  
de-energize the contactor until the voltage drops below 16  
VAC, which is the drop out voltage for most contactors.  
The control will have a software programmable Fan Mode  
Switch for Auto operation or Continuous operation.  
When the Fan is in the Continuous mode, it will run continu-  
ously during the occupied schedule and in the Auto mode  
when in an unoccupied schedule.  
The control shall have a means of low ambient control with-  
out adding any additional components. The control shall  
have a means of cycling the compressor on for 10 minutes  
and off for 5 minutes to defrost the indoor coil when the out  
side ambient is below a low ambient switch point without add-  
ing additional components.  
The control shall be capable of operating the fan without a G  
or fan signal from the thermostat.  
EQUIPMENT CONTROL FEATURES  
The control shall have a means of storing compressor run  
time. This data shall be available through communication.  
The control shall have the ability to clear this data when a  
compressor is replaced.  
The control shall be capable of communicating on the Stan-  
dard Open protocol, Modbus RTU.  
®
®
The register data for the Modbus must be publicly available  
and open.  
The control shall have the ability to store a name of at least  
26 characters in length. The control will leave the factory with  
the serial number of the equipment it is in, stored in non-vola-  
tile memory in the Name location.  
Monitoring Software shall be provided at no cost. The moni-  
toring software shall have a flashing icon when any unit wired  
to the computer has an alarm. Clicking the flashing icon shall  
display the fault code and the details of the fault.  
The control shall have the ability to store the model number  
of the equipment of at least 26 characters in length. The con-  
trol will leave the factory with the model number of the equip-  
ment it is in, stored in non-volatile memory.  
The networking setup shall be completed by connecting a  
three-wire daisy chain cable to each unit, then powering all  
the units up and pushing a button on each control. There  
shall not be any dipswitches to configure the network  
address.  
The control shall have the ability to store the serial number of  
the equipment of at least 26 characters in length. The control  
will leave the factory with the serial number of the equipment  
it is in, stored in non-volatile memory.  
The control shall use a communication driver that is capable  
of having 64 nodes on the bus before a repeater is needed.  
The control shall not power the contactors through the ther-  
mostat wiring. Dropping voltage over the thermostat wiring  
causes chattering contactors when the contactors are pow-  
ered in this manner.  
The control shall use non-volatile memory to store the last  
five alarms. There shall be a single button to push to recall  
these last five alarms. The alarms shall be stored first in last  
out. The first flash code shall be the last alarm that occurred.  
There shall be a button press sequence to clear the alarms in  
non-volatile memory.  
The control will operate and monitor up to 3 stages of heat  
independently.  
The control shall have a button to reset compressor lockouts  
without powering the unit down.  
The control shall monitor the Gas Heat operation in the heat-  
ing mode. It shall monitor the gas valve when there is a call  
for heating. The control shall alarm when there is a call for  
heat and no gas valve voltage after 5 minutes.  
The control shall have a button to clear compressor Anti-  
Short Cycle Delays. When this button is pressed it will only  
clear the Anti-Short Cycle Delays for one cycle only and not  
permanently.  
There will only be one control board for this series of units, for  
both CV and VAV operation.  
The control will be compatible with any BAS (Building Auto-  
mation System). Any BAS shall be able to control the equip-  
ment when wired to the control's Thermostat Terminal Strip.  
COMFORT CONTROL FEATURES  
The control will be installed and tested at the factory where  
the equipment is assembled.  
The control shall have loading of at least 25 milliamps on all  
thermostat inputs for controllers and thermostats that use out-  
put TRIACs.  
The control will use a Wall Senor that has a means of overrid-  
ing the unoccupied mode for a programmable amount of  
time.  
The control shall have a Smoke Detector Shutdown input on  
the board. The control shall be powered through this input,  
so when the Smoke Detector trips, the control will shut down  
the unit immediately.  
The Unoccupied Override time will be programmed in min-  
utes up to 4 hours.  
Johnson Controls Unitary Products  
93  
   
246653-YTG-E-0108  
The control will use a Wall Sensor that has a warmer/cooler  
dial so the occupants can offset the programmed setpoint by  
a programmed amount between 1 and 5 degrees.  
The control will have a Space Temperature Alarm.  
The control will have a Supply Air Temperature Alarm for  
Heating and Cooling. The Alarm temperature will be pro-  
grammable  
The control will have a Supply Air Sensor as standard.  
The control will have a Return Air Sensor as standard.  
The control will have an Outside Air Sensor as standard.  
The Control will be able to do a Pre-Occupancy Purge at a  
Programmable Time.  
The control will have a hardware Smoke-Purge input.  
The control will have the ability to read a dirty filter switch  
The control will use the Return Air Sensor in place of the  
Space Sensor if the Space Sensor fails for any reason, the  
control will have a 365 day Real Time Clock.  
The control will have the capability of reading a Fan proving  
switch.  
The Real Time Clock will be able to do automatic Daylight  
Savings Time adjustment.  
The control will have an intelligent recovery function that will  
bring the space to the Occupied Setpoint just before or at the  
beginning of the first Occupied schedule each day. The con-  
trol will learn and apply the minimum run time required to heat  
or cool the space to setpoint for the first Occupied period of a  
day.  
The control will have an Occupancy Schedule that allows two  
different Occupied schedules per day for each of the seven  
days of the week individually.  
The control will have 20 Holiday Schedules, each capable of  
99 days.  
The control will have Software controllable Mode Switches  
(Heat, Cool, and Fan).  
The control's Holiday Schedules will have a start time associ-  
ated with each schedule.  
The control will meter and track Unoccupied Override Time  
for billing purposes.  
The control will control the Economizer directly.  
The control will be capable of operating the Economizer using  
Dry Bulb, Outside Enthalpy, or Differential Enthalpy.  
OPTIONAL COMMUNICATION TRANSLATOR  
Overview  
When the control is using Enthalpy to control the Economizer,  
it will also have an Outside Air Temperature enable Setpoint.  
®
The ModLINC translator operates as a Modbus Client pro-  
®
viding an interface between a BACnet control system and  
®
devices that communicate using the Modbus RTU protocol.  
The control will use two setpoints for Supply Air Temperature  
for the Economizer operation. One will be for a small space  
cooling demand and one for a large space cooling demand.  
The ModLINC is preconfigured to provide an interface to  
YORK UP products equipped with an Intelli-Comfort or Sim-  
plicity-Elite controller and allows monitoring and control by a  
®
third-party BACnet Building Automation System (BAS).  
The control will have the ability to do Demand Ventilation  
using one CO sensor.  
2
The ModLINC mounts inside the control panel of the UP unit  
and utilizes 24 VAC power from the unit's control transformer.  
One port is connected to the UP controller. The other port  
The control will have a programmable maximum Outside Air  
Damper Position for IAQ operation.  
®
must be connected to the BACnet network.  
The control will have the ability to temper the ventilation air  
during times when heating or cooling is not required.  
The ModLINC translator is preconfigured to obtain opera-  
tional data points from the controller and expose them on a  
BACnet network.  
®
The control will have the ability to offset the operating set-  
point based on high Humidity in the Space.  
"The ModLINC device is primary a control offered and config-  
ured by York's ESG (Engineering Systems Group). The  
The control will have programmable limits when offsetting the  
Operating Setpoint to control Humidity.  
®
device can be used with other BACnet MS/TP systems, but  
a qualified controls contractor must be involved. UP cannot  
support the ModLINC device beyond its hardware functional-  
ity and cannot guarantee functionality with the ISN or other  
third party BAS devices."  
The control must be able to lockout Cooling below a program-  
mable Outside Air Temperature Setpoint.  
The control will be able to lockout Heating above a program-  
mable Outside Air Temperature Setpoint.  
Please refer to the ModLINC Installation/Application manual  
Part Number 126367.  
94  
Johnson Controls Unitary Products  
   
246653-YTG-E-0108  
Remote Wall Mounted Temperature Sensors  
OPTIONAL CONTROL  
Attractive wall mounted temperature sensors are available to  
precisely control multiple or individual zone temperature.  
Sensors are available without adjustment, with override and  
override with programmable setpoint adjustment.  
York Commercial Comfort System (YCCS)  
Provides rooftop system integration for YCCS single zone,  
change-over bypass and VAV systems.  
Dirty Filter Switch  
AVAILABLE ACCESSORIES  
The following accessories shall be available:  
Partial perimeter roof curbs  
A Dirty Filter pressure switch kit is available for field installa-  
tion. Switches will monitor pressure drop across the units air  
filters and provide an alarm when filters become dirty.  
Propane Conversion Kits  
14" high roof curb with wood nailer. The partial perimeter roof  
curb surrounds the portion of the unit which has airflow, and  
includes a support at the compressor end of the unit.  
Contains the necessary orifices and gas valve parts to con-  
vert from natural gas to propane. Propane cannot be used on  
modulating gas heat units.  
Burglar Bars  
High Altitude Conversion Kits  
This accessory mounts in the supply and return opening of  
the partial perimeter curb to prevent entry into the building  
through the ductwork.  
These kits are required for natural gas applications between  
2,000 and 6,000 feet.  
Field Installed Barometric Relief  
Energy Recovery Ventilators  
This accessory is a set of barometric relief dampers and hood  
used for the millennium barometric relief option that is fully  
assembled for mounting to return ductwork. This accessory is  
intended for use on horizontal return applications.  
8,000 and 13,000 CFM models available. Great applications  
involving 30% or more of required outdoor air where energy  
use and comfort must be optimized.  
Programmable thermostat, with or without remote sen-  
sor (required for constant volume units)  
Provides 2 Heat/4 Cool control and 7 day programming.  
Johnson Controls Unitary Products  
95  
                   
Subject to change without notice. Printed in U.S.A.  
246653-YTG-E-0108  
Copyright © 2008 by Johnson Controls, Inc. All rights reserved.  
Supersedes: 246653/036-21091-004-D-0206  
Johnson Controls Unitary Products  
5005 York Drive  
Norman, OK 73069  

Lexmark S600 User Manual
Lexmark X364dn User Manual
Panasonic Cs E24gkr User Manual
Philips 5475nb User Manual
Quantum Lc 15000 User Manual
Samsung Avmkc026ea B 0 User Manual
Tecumseh Automobile Parts Lh358ea Hm100 User Manual
Toshiba Air Conditioner Rav Sm803ut E User Manual
Trane Air Conditioner 61e User Manual
T Tech 12 Volt Power Supply Jump Starter Jncxfe User Manual