York Predator Dm 078 User Manual

246645-YTG-C-0708  
®
TECHNICAL  
GUIDE  
DESCRIPTION  
®
YORK Predator® units are convertible single packages  
with a common footprint cabinet and common roof curb for  
all 6-1/2 through 12-1/2 ton models. All units have two  
compressors with independent refrigeration circuits to pro-  
vide two stages of cooling. The units were designed for  
commercial applications and can be easily installed on a  
roof curb, slab, or frame.  
All Predator® units are self-contained and assembled on  
rigid full perimeter base rails allowing for 3-way forklift  
access and overhead rigging. Every unit is completely  
charged, wired, piped, and tested at the factory to provide  
a quick and easy field installation.  
STANDARD EFFICIENCY  
SINGLE PACKAGE AIR CONDITIONERS AND  
SINGLE PACKAGE GAS/ELECTRIC UNITS  
DM 078, 090, 102, 120 and 150  
All units are convertible between side and down airflow. A  
independent economizer design is used on side and down  
discharge applications, as well as all tonnage sizes.  
6-1/2, 7-1/2, 8-1/2, 10 and 12-1/2 NOMINAL TONS  
9.0 EER  
Predator® units are available in the following configura-  
tions: cooling only, cooling with electric heat, and cooling  
with gas heat. Electric heaters are available as factory-  
installed options or field-installed accessories.  
Tested in accordance with:  
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE  
 
246645-YTG-C-0708  
Filter drier  
(solid core)  
Simplicity™ control board  
w/screw connector for T-stat  
wiring and network connections  
Filter access  
(2” throw-away)  
Disconnect location  
(optional disconnect switch)  
Terminal block for  
hi-voltage connection  
Condenser section  
Second model  
nameplate  
Slide-out motor and  
blower assembly for  
easy adjustment  
and service  
inside hinged  
access panel  
Dual stage  
cooling for  
maximum  
comfort  
Belt-drive  
blower motor  
Power ventor motor  
Compressor #2  
access (high-  
efficiency  
compressor  
w/crankcase  
heater)  
20-gauge alumi-  
nized steel tubular  
heat exchanger for  
long life (stainless  
steel option)  
Two-stage gas  
heating to maintain  
warm, comfortable  
temperature  
Base rails w/forklift  
slots (three sides)  
and lifting holes  
Slide-out drain pan  
with steel 3/4” NPT,  
female connection  
Intelligent control  
board for safe and  
efficient operation  
Roof curbs in eight- and  
fourteen-inch heights. Roof  
curbs for transitioning from  
York Sunline™ footprint to  
the ZH Series footprints are  
also available (field-installed  
accessory)  
Compressor #1 access  
(high-efficiency compressor  
w/crankcase heater)  
Side entry power  
and control wiring  
knockouts  
Toolless  
door latch  
FIGURE 1 - PREDATOR® COMPONENT LOCATION (DM 120 SHOWN)  
Service windows have been placed in both condenser  
section walls. Rotation of the cover allows easy access  
to the condenser coils for cleaning or inspection.  
FEATURES  
Standard Efficiency– All standard efficiency units have  
a minimum EER of 9.0. Gas/electric units have elec-  
tronic spark ignition and power vented combustion with  
steady state efficiencies of 80%.  
Both the unit control board and ignition control board utilize  
flash codes to aid in diagnosis of unit malfunctions. Unique  
alarm codes quickly identify the source of the unit alarm.  
Service Friendly – The Predator® incorporates a num-  
All units use the same standard filter size. This stan-  
dardization removes any confusion on which filter sizes  
are needed for replacement.  
ber of enhancements which improve serviceability.  
The motor and blower slide out of the unit as a common  
assembly. This facilitates greater access to all the indoor  
airflow components, thus simplifying maintenance and  
adjustment.  
The non-corrosive drain pan slides out of the unit to per-  
mit easy cleaning. The drain pan is accessed by remov-  
ing the drain pan cover plate on the rear of the unit.  
Once the plate is removed, the drain pan slides out  
through the rear of the unit.  
Service time is reduced through the use of hinged, tool-  
less panels. Such panels provide access to frequently  
inspected components and areas, including the control  
box, compressors, filters, indoor motor & blower, and the  
heating section. The panels are screwed in place at the  
factory to prevent access by children or other unauthor-  
ized persons. It is recommended that the panels be  
secured with screws once service is complete.  
All Predator® units have a second model nameplate  
located inside the control access door. This is to prevent  
deterioration of the nameplate through weathering.  
Environmentally Aware – For improved Indoor Air  
Quality, foil faced insulation is used exclusively through-  
out the units.  
Johnson Controls Unitary Products  
3
   
246645-YTG-C-0708  
Balanced Heating – The Predator® offers “Ultimate Heat-  
On Board Diagnostics - Each alarm will energize a  
trouble light on the thermostat, if so equipped, and  
flash an alarm code on the control board LED. Each  
high and low-pressure switch alarm as well as each  
freezestat alarm has its own flash code. The control  
board saves the five most recent alarms in memory,  
and these alarms can be reviewed at any time.  
Alarms and programmed values are retained  
through the loss of power.  
st  
nd  
ing Comfort” with a balance between 1 and 2 stage  
st  
gas heating. The 1 stage of a gas heat Predator® unit  
provides 60% of the heating capacity. Balanced heating  
allows the unit to better maintain desired temperatures.  
Convertible Airflow Design – The side duct openings  
are covered when they leave the factory. If a side sup-  
ply/return is desired, the installer simply removes the two  
side duct covers from the outside of the unit and installs  
them over the down shot openings. No panel cutting is  
required. Convertible airflow design allows maximum  
field flexibility and minimum inventory.  
Reliable – From the beginning – All units undergo com-  
puter automated testing before they leave the factory.  
Units are tested for refrigerant charge and pressure, unit  
amperage, and 100% functionality. For the long term –  
All Predator® units are painted with a long lasting, pow-  
der paint that stands up over the life of the unit. The paint  
used has been proven by a 1000 hour salt spray test.  
System Protection - Suction line freezestats are supplied  
on all units to protect against loss of charge and coil frost-  
ing when the economizer operates at low outdoor air tem-  
peratures while the compressors are running. Every unit  
has solid-core liquid line filter-driers and high and low-  
pressure switches. Internal compressor protection is stan-  
dard on all compressors. Crankcase heaters are standard  
on reciprocating compressors. Scroll compressors do not  
require crankcase heaters. Phase Monitors are standard  
on units with scroll compressors. This accessory monitors  
the incoming power to the unit and protects the unit from  
phase loss and reversed phase rotation.  
Flexible Placement – All models and configurations  
share the same cabinet/footprint and thus the same roof  
curb. You have the flexibility to set one curb and choose  
the correct tonnage size and heating option after the  
internal loads have been determined.  
To further simplify planning and installation, Predator®  
cabinets are designed to fit your roof. With the optional  
roof curb, the unit ductwork is designed to fit around 24”  
on-center joists or between 48” on-center joists.  
Advanced Controls - S implicity™ control boards have  
standardized a number of features previously available  
only as options or by utilizing additional controls.  
The drain pan can be rotated to drain to either the front  
or the rear of the unit. Additionally, the drain pan can be  
piped to drain through the roof curb. As it is sometimes  
difficult to have a level installation, the drain pan features  
a generous slope to ensure proper drainage.  
Low Ambient - An integrated low-ambient control  
allows all units to operate in the cooling mode down  
to 0°F outdoor ambient without additional assis-  
tance. Optionally, the control board can be pro-  
grammed to lockout the compressors when the  
outdoor air temperature is low or when free cooling  
is available.  
Full Perimeter Base Rails – The permanently attached  
base rails provide a solid foundation for the entire unit  
and protect the unit during shipment. The rails offer fork-  
lift access from 3 sides, and rigging holes are available  
so that an overhead crane can be used to place the units  
on a roof.  
Anti-Short Cycle Protection - To aid compressor  
life, an anti-short cycle delay is incorporated into the  
standard controls. Compressor reliability is further  
ensured by programmable minimum run times. For  
testing, the anti-short cycle delay can be temporarily  
overridden with the push of a button.  
Easy Installation – Gas and electric utility knockouts are  
supplied in the unit underside as well as the side of the  
unit. A clearly identified location is provided to mount a  
field supplied electrical disconnect switch. Utility con-  
nections can be made quickly and with a minimum  
amount of field labor.  
Fan Delays - Fan on and fan off delays are fully pro-  
grammable. Furthermore, the heating and cooling  
fan delay times are independent of one another. All  
units are programmed with default values based  
upon their configuration of cooling and heat.  
All units are shipped with 2” filters installed.  
Wide Range of Indoor Airflows – All indoor fan motors  
are belt-drive type providing maximum flexibility to han-  
dle most airflow requirements. For high static applica-  
tions, factory installed alternate indoor fan motors are  
available. With the optional indoor fan motor, all units  
can supply nominal airflow at a minimum of 1.5” ESP.  
Safety Monitoring - The control board monitors the  
high and low-pressure switches, the freezestats, the  
gas valve, if applicable, and the temperature limit  
switch on gas and electric heat units. The unit con-  
trol board will alarm on ignition failures, compressor  
lockouts and repeated limit switch trips.  
Warranty - All models include a 1-year limited warranty  
on the complete unit. Compressors and electric heater  
elements each carry a 5-year warranty. Aluminized steel  
and stainless steel tubular heat exchangers carry an  
additional 10-year warranty.  
Nuisance Trip Protection and Strikes - To prevent  
nuisance trouble calls, the control board uses a  
“three times, you’re out” philosophy. The high and  
low-pressure switches and the freezestats must trip  
three times within two hours before the unit control  
board will lock out the associated compressor.  
4
Johnson Controls Unitary Products  
246645-YTG-C-0708  
ers close. The changeover from mechanical refrigera-  
tion to economizer operation is regulated by the  
standard single enthalpy input. There is an optional  
input dual dry bulb available. To meet regulated air  
standards, the economizer control accepts an optional  
FACTORY INSTALLED OPTIONS  
®
YORK offers several equipment options factory installed, for  
the Predator® line.  
Optional Factory Installed Economizers - Predator  
units offer a variety of optional factory installed econo-  
mizers with low leak dampers. The outdoor air enthalpy  
sensor enables economizer operation if the outdoor  
enthalpy is less than the setpoint of the economizer logic  
module. See Table 41 to determine the correct econo-  
mizer for your application.  
CO input for demand ventilation. With single enthalpy  
2
input, the economizer control monitors outdoor air. The  
dual enthalpy kit provides a second input used to mon-  
itor the return air. With a dual input kit installed, the  
economizer control compares the values of the two  
enthalpy or temperature inputs and positions the  
dampers to provide the maximum efficiency possible.  
Downflow Economizer - (With barometric relief) -  
The economizer is provided with a single enthalpy  
input. The economizer is 2% low leakage type, and is  
shipped installed and wired. The installer needs only  
to assemble and mount the outdoor air hood (Pro-  
vided). The economizer has spring return, fully modu-  
lating damper actuators and is capable of introducing  
up to 100% outdoor air. As the outdoor air intake  
dampers open, the return air dampers close. The  
changeover from mechanical refrigeration to econo-  
mizer operation is regulated by the standard single  
enthalpy input. There is an optional input dual dry  
bulb available. To meet regulated air standards, the  
Power Exhaust (Downflow only) - This accessory  
installs in the unit with a down flow economizer.  
Motorized Outdoor Air Damper - The motorized out-  
door air damper includes a slide-in/plug-in damper  
assembly with an outdoor air hood and filters. The out-  
door air dampers open to the preset position when the  
indoor fan motor is energized. The damper has a range  
of 0% to 100% outdoor air entry. Factory installed option  
or field installed accessory.  
Alternate Indoor Blower Motor - For applications with  
high static restrictions, units are offered with optional  
indoor motors that provide higher static output and/or  
higher airflow, depending upon the installer’s needs.  
economizer control accepts an optional CO input for  
2
demand ventilation. With single enthalpy input, the  
economizer control monitors outdoor air. The dual  
enthalpy kit provides a second input used to monitor  
the return air. With a dual input kit installed, the econ-  
omizer control compares the values of the two  
enthalpy or temperature inputs and positions the  
dampers to provide the maximum efficiency possible.  
Aluminized Steel Gas Heat Exchanger - For applica-  
tions in non-corrosive environments.  
Stainless Steel Gas Heat Exchanger - For applications  
in corrosive environments, this option provides a full  
stainless steel heat exchanger assembly.  
Stainless Steel Drain Pan - An optional rust-proof stain-  
less steel drain pan is available to provide years of trou-  
ble-free operation in corrosive environments.  
Horizontal Economizer - (Without barometric  
relief) - All features of the downflow economizer  
exist except you must order the duct mount baro-  
metric relief separately. You must order a 1EH0408  
if you are installing a power exhaust. You can  
order a 1RD0411 Barometric Relief for horizontal  
flow economizers only.  
Electric Heaters - The electric heaters range from 9kW  
to 54kW and are available in all the voltage options of the  
base units. All heaters are dual staged. All heaters are  
intended for single point power supply.  
BAS Ready Economizer -(With barometric relief)  
- The economizer is provided with a Belimo actuator  
that requires a 0-10V DC input from an external  
source (i.e., field installed building automation sys-  
tem controller). Power exhaust options are avail-  
able. The economizer is 2% low leakage type with  
spring return and fully modulating dampers capable  
of introducing up to 100% outside air. Also include 2”  
pleated filters.  
Disconnect Switch - For gas heat units and cooling  
units with electric heat, an HACR breaker sized to the  
unit is provided. For cooling only units, a switch sized to  
the largest electric heat available for the particular unit is  
provided. Factory installed option only.  
Convenience Outlet - (Non-Powered /Powered) - This  
option locates a 120V single-phase GFCI outlet with  
cover, on the corner of the unit housing adjacent to the  
compressors. The “Non-powered” option requires the  
installer to provide the 120V single-phase power source  
and wiring. The “Powered” option is powered by a step-  
down transformer in the unit. Factory installed option only.  
Slab Economizer for Energy Recovery Ventilators-  
(With barometric relief and Fresh Air Hood) - The  
economizer is provided with a single enthalpy input.  
The economizer is 2% low leakage type, and is  
shipped installed and wired. The economizer has  
spring return, fully modulating damper actuators and is  
capable of introducing up to 100% outdoor air. As the  
outdoor air intake dampers open, the return air damp-  
Smoke Detectors - The smoke detectors stop operation  
of the unit by interrupting power to the control board if  
smoke is detected within the air compartment. Available  
for both the supply and/or return air.  
Johnson Controls Unitary Products  
5
 
246645-YTG-C-0708  
S implicity™ INTELLI-Comfort™ with ModLINC  
Control - The York® S implicity™ INTELLI-Comfort™  
with ModLINC control is factory installed. It includes all  
the features of the INTELLI-Comfort™ control with an  
additional control to translate communications from  
MODBUS to the BACnet MSTP protocol.  
Factory installed smoke detectors in the return air,  
may be subjected to freezing temperatures during  
"off" times due to out side air infiltration. These  
smoke detectors have an operational limit of 32 °F  
to 131°F. Smoke detectors installed in areas that  
could be out side those limitations will have to be  
moved to prevent having false alarms.  
Novar® BAS Control - The Novar® ETC-3 building  
automation system controller is factory installed. Incudes  
supply air sensor, return air sensor, dirty filter indicator  
switch, and air proving switch.  
Johnson Controls BAS Control - The Johnson Control  
YK-UNT-1126 building automation system controller is  
factory installed. Includes supply air sensor, return air  
sensor, dirty filter indicator switch, and air proving switch.  
Phase Monitors - Designed to prevent unit damage. The  
phase monitor will shut the unit down in an out-of phase  
condition. (Standard on units with Scroll Compressors.)  
Coil Guard - Customers can purchase a coil guard kit to  
protect the condenser coil from damage. Additionally,  
this kit stops animals and foreign objects from entering  
the space between the inner condenser coil and the  
main cabinet. This is not a hail guard kit.  
CPC BAS Control - The Computer Process Controls  
Model 810-3060 ARTC Advanced Rooftop building auto-  
mation system controller is factory installed. Includes  
supply air sensor, return air sensor, dirty filter indicator  
switch and air proving switch.  
Dirty Filter Switch - This kit includes a differential pres-  
sure switch that energizes the fault light on the unit ther-  
mostat, indicating that there is an abnormally high  
pressure drop across the filters. Factory installed option  
or field installed accessory.  
Honeywell BAS Control - The Honeywell W7750C  
building automation system controller is factory installed.  
Includes air supply sensor, return air sensor, dirty filter  
indicator switch, and air proving switch.  
York Commercial Comfort System (YCCS) - Provides  
rooftop system integration for YCCS single zone and  
change-over bypass systems.  
Technicoat Condenser Coils - The condenser coils are  
coated with a phenolic coating for protection against cor-  
rosion due to harsh environments.  
FIELD INSTALLED ACCESSORIES  
Technicoat Evaporator Coil - The evaporator coils are  
coated with a phenolic coating for protection against cor-  
rosion due to harsh environments.  
®
YORK offers several equipment accessories for field instal-  
lation, for the Predator® line.  
BAS - Building Automation System Controls S implic-  
ity™ INTELLI-Comfort™ Control - The York® S implic-  
ity™ INTELLI-Comfort™ control is factory installed. It  
includes a supply air sensor, a return air sensor, and an  
outside air sensor. There are provisions for a field installed  
dirty filter indicator switch, an air-proving switch, an Out-  
side Air Humidity sensor, a Return Air Humidity sensor, an  
Inside IAQ sensor, and an Outside Air IAQ sensor. Con-  
struction mode operation, 365-day real time clock with 7  
day programming plus holiday scheduling is built-in. Two  
different modes of demand ventilation are achieved  
Downflow Economizer - (With barometric relief) - The  
economizer is provided with a single enthalpy input. The  
economizer is 2% low leakage type. The economizer has  
spring return, fully modulating damper actuators and is  
capable of introducing up to 100% outdoor air. As the out-  
door air intake dampers open, the return air dampers  
close. The changeover from mechanical refrigeration to  
economizer operation is regulated by the standard single  
enthalpy input. There is an optional input dual dry bulb  
available. To meet regulated air standards, the economizer  
control accepts an optional CO input for demand ventila-  
2
through the INTELLI-Comfort™ using CO sensors. It  
2
tion. With single enthalpy input, the economizer control  
monitors outdoor air. The dual enthalpy kit provides a sec-  
ond input used to monitor the return air. With a dual input  
kit installed, the economizer control compares the values  
of the two enthalpy or temperature inputs and positions the  
dampers to provide the maximum efficiency possible  
uses an inside CO sensor to perform Demand Ventilation.  
2
It can also use an Outside CO sensor to perform Differen-  
2
tial Demand Ventilation. It uses a Patented Comfort Venti-  
lation algorithm to provide comfortable ventilation air  
temperature. The patented economizer-loading algorithm  
will protect the equipment when harsh operating conditions  
exist. Humidity in the occupied space or return duct can be  
monitored and controlled via humidity sensors and the on-  
board connection for hot gas re-heat system. It uses the  
INTELLI-Start™ algorithm to maximize energy savings by  
recovering the building from the Unoccupied Setpoints to  
the Occupied Setpoints just in time for the Occupied Time  
Period to begin. The S implicity™ INTELLI-Comfort™ bal-  
Horizontal Economizer - (Without barometric relief) -  
All features of the downflow economizer exist except you  
must order the duct mount barometric relief separately.  
You must order a 1EH0408 if you are installing a  
power exhaust. You can order a 1RD0411 Barometric  
Relief for horizontal flow economizer.  
Slab Economizer for Energy Recovery Ventilator-  
(Without barometric relief or Fresh Air Hood) - The  
economizer is provided with a single enthalpy input. The  
ances space temperature, ventilation air temperature, CO  
and humidity for ultimate comfort.  
2
6
Johnson Controls Unitary Products  
 
246645-YTG-C-0708  
economizer is 2% low leakage type. The economizer has  
spring return, fully modulating damper actuators and is  
capable of introducing up to 100% outdoor air. As the out-  
door air intake dampers open, the return air dampers  
close. The changeover from mechanical refrigeration to  
economizer operation is regulated by the standard single  
enthalpy input. There is an optional input dual dry bulb  
available. To meet regulated air standards, the economizer  
Flue Exhaust Extension Kit - In locations with wind or  
weather conditions which may interfere with proper  
exhausting of furnace combustion products, this kit can  
be installed to prevent the flue exhaust from entering  
nearby fresh air intakes.  
-60°F Gas Heat Kit - For installations which require gas  
heat units to perform in low ambient temperatures, a gas  
section heating kit is available. This kit provides electric  
heat in the gas heat controls section to ensure the gas  
valve and controls will continue to function properly at  
extremely low temperatures.  
control accepts an optional CO input for demand ventila-  
2
tion. With single enthalpy input, the economizer control  
monitors outdoor air. The dual enthalpy kit provides a sec-  
ond input used to monitor the return air. With a dual input  
kit installed, the economizer control compares the values  
of the two enthalpy or temperature inputs and positions the  
dampers to provide the maximum efficiency possible.  
Gas Heat High Altitude Kit - This kit converts a gas heat  
unit to operate at high altitudes, 2,000 to 6,000 feet. Con-  
version kits are available for natural gas and propane.  
Gas Heat Propane Conversion Kit - This kit converts a  
gas-fired heater from natural gas to propane. It contains the  
main burner orifices and gas valve replacement springs.  
You can order 1EH0409 Barometric Relief/FA Hood  
for field installations without an ERV.  
Dual Enthalpy Control, Accessory - This kit contains  
the required components to convert a single enthalpy  
economizer to dual enthalpy.  
Gas Piping Kit - Contains pipe nipples, fittings and gas  
cock required for gas supply connection with external  
shut off.  
Barometric Relief Damper - Zero to 100% capacity  
barometric relief dampers for use with horizontal flow, or  
field installed slab economizers.  
Electric Heaters - The electric heaters range from 9 kW  
to 54kW and are available in all the voltage options of the  
base units. All heaters are dual staged. Cooling units  
include an adapter panel for easy installation of the elec-  
tric heaters. Necessary hardware and connectors are  
included with the heaters. All heaters are intended for  
single point power supply.  
Power Exhaust - This accessory installs in the unit with  
a down flow economizer. Power exhaust plugs into the  
connector in the unit bulkhead. You must purchase  
1EH0408 barometric relief when applying to a hori-  
zontal flow application.  
Low Limit / Compressor Lockout Kit  
Manual Outdoor Air Damper - Like the motorized out-  
door air damper, each manual outdoor air damper  
includes a slide-in damper assembly with an outdoor air  
hood and filters. Customers have a choice of dampers  
with ranges of 0% to 100% or 0% to 35% outdoor air entry.  
1. Compressor Lockout (CLO): To prevent mechani-  
cal (compressorized) operation of the unit during  
cold outdoor conditions where there is a risk of  
returning liquid refrigerant back to the compressors.  
2. Low Limit Control (LLC): To prevent the supply air  
from dropping below a specified setpoint by utilizing  
the units first stage heating means when there is a  
demand for cooling during cold outside conditions.  
Motorized Outdoor Air Damper - The motorized out-  
door air damper includes a slide-in/plug-in damper  
assembly with an outdoor air hood and filters. The out-  
door air dampers open to the preset position when the  
indoor fan motor is energized. The damper has a range  
of 0% to 100% outdoor air entry. Factory installed option  
or field installed accessory.  
Metal Frame Filter Kit - Metal frame with polyester filter  
medium.  
Permanent Filters - Permanent filters are available.  
Smoke Detectors - The smoke detectors stop operation  
of the unit by interrupting power to the control board if  
smoke is detected within the air compartment.  
Roof Curbs - The roof curbs have insulated decks and  
are shipped disassembled The roof curbs are available  
in 8” and 14” heights. For applications with security con-  
cerns, burglar bars are available for the duct openings of  
the roof curbs.  
CO Sensor - Senses CO levels and automatically  
2
2
overrides the economizer when levels rise above the  
preset limits.  
Roof Curb Transition - Single Piece Adapter (10” High) -  
Roof curbs for transitioning from Sunline™ units to Preda-  
tor® units. Fits 7.5 to 12.5 Sunline™ roof curbs only.  
Dirty Filter Switch - This kit includes a differential pres-  
sure switch that energizes the fault light on the unit ther-  
mostat, indicating that there is an abnormally high  
pressure drop across the filters.  
Burglar Bars - Mount in the supply and return openings  
to prevent entry into the duct work.  
Coil Guard - Field installed decorative wire coil guard.  
Thermostat - The units are designed to operate with 24-  
volt electronic and electro-mechanical thermostats. All  
units (with or without an economizer) operate with two-  
stage heat/two-stage cool or two-stage cooling only ther-  
mostats, depending upon unit configuration.  
Hail Guard - This kit includes a sloped hood which  
installs over the outside condenser coil and prevents  
damage to the coil fins from hail strikes. Field installed  
accessory only.  
Johnson Controls Unitary Products  
7
246645-YTG-C-0708  
TABLE 1: ACCESSORIES  
Part Number  
Description  
Weight  
1RC0470  
Roof Curb, 8" Height  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1RC0471  
Roof Curb, 14" Height  
1RC0472  
Roof Curb, Transition (7.5 T through 12.5 T)  
Burglar Bars, Downflow  
1BD0408  
2TP04520925  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
2TP04520946  
2TP04521846  
2TP04522446  
2TP04523646  
2TP04525446  
2TP04520958  
2TP04521858  
2TP04522458  
2TP04523658  
2TP04525458  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
2TP04540946  
2TP04541846  
2TP04542446  
2TP04543646  
2TP04540958  
2TP04541858  
2TP04542458  
2TP04543658  
1FA0411  
Electric Heat 9kW 230V  
Electric Heat 18kW 230V  
Electric Heat 24kW 230V  
Electric Heat 36kW 230V  
Electric Heat 54kW 230V  
Electric Heat 9kW 460V  
Electric Heat 18kW 460V  
Electric Heat 24kW 460V  
Electric Heat 36kW 460V  
Electric Heat 54kW 460V  
Electric Heat 9kW 575V  
Electric Heat 18kW 575V  
Electric Heat 24kW 575V  
Electric Heat 36kW 575V  
Electric Heat 54kW 575V  
Electric Heat 9kW 230V, 42" Tall Cabinet  
Electric Heat 18kW 230V, 42" Tall Cabinet  
Electric Heat 24kW 230V, 42" Tall Cabinet  
Electric Heat 36kW 230V, 42" Tall Cabinet  
Electric Heat 9kW 460V, 42" Tall Cabinet  
Electric Heat 18kW 460V, 42" Tall Cabinet  
Electric Heat 24kW 460V, 42" Tall Cabinet  
Electric Heat 36kW 460V, 42" Tall Cabinet  
Electric Heat 9kW 575V, 42" Tall Cabinet  
Electric Heat 18kW 575V, 42" Tall Cabinet  
Electric Heat 24kW 575V, 42" Tall Cabinet  
Electric Heat 36kW 575V, 42" Tall Cabinet  
Manual Outside Air Damper 0-35%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)  
Manual Outside Air Damper 0-100%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)  
Motorized Damper, Downflow (Incl. Hood, Damper & Filter, no Barometric Relief)  
Motorized Damper, Horizontal (Incl. Hood, Damper & Filter, no Barometric Relief)  
Economizer, Downflow (Incl. Barometric Relief & All Hoods)  
1FA0412  
2MD04702724  
2MD04703324  
2EE04705424  
2EE04705524  
2EE04705224  
2EE04705624  
2PE04703225  
2PE04703246  
2PE04703258  
2EC04700924  
1EH0407  
124 lbs.  
97 lbs.  
Economizer, Horizontal (Incl. Dampers & Hoods, no Barometric Relief)  
Economizer, Slab, Downflow (Incl. Dampers only no Hoods or Barometric Relief)  
"Downflow Economizer, Slab type for ERV (no Barometric Relief or FA hood)", 42" Tall Cabinet  
Power Exhaust, Downflow, 230V (For Units with Economizer only)  
Power Exhaust, Downflow, 460V(For Units with Economizer only)  
Power Exhaust, Downflow, 580V (For Units with Economizer only)  
Dual Enthalpy Control (Use with Single Enthalpy Economizer)  
-
-
-
-
-
Hood Kit, Downflow Economizer (Included with all Downflow Economizers)  
Barometric Relief Kit, Ductmount for Horizontal Application (Incl. Damper & Hood)  
Barometric Relief Kit, Ductmount for Horizontal Application w/Power Exhaust (Incl. Damper & Hood)  
Barometric Relief / Hood Kit, for Field Installed Slab Econ. w/o ERV (Incl. Barometric Relief & FA Hood)  
CO2 Detector Unit Mount  
1RD0411  
1EH0408  
25 lbs.  
1EH0409  
-
-
-
-
2AQ04700424  
2AQ04700324  
2SD04700424  
2MK04700624  
1CG0419  
CO2 Detector Space Mount  
Smoke Detector, Supply or Return (Return Not Available with Horizontal Economizer)  
Low Limit / Compressor Lockout Kit  
Coil Guard (Electric / Electric & HP models)  
-
8
Johnson Controls Unitary Products  
 
246645-YTG-C-0708  
TABLE 1: ACCESSORIES (CONTINUED)  
Part Number  
Description  
Weight  
1CG0420  
1CG0427  
1CG0428  
1HG0411  
1HG0415  
1GP0405  
1NP0442  
1HA0442  
1HA0443  
1FE0412  
Coil Guard (Gas / Electric models)  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Coil Guard (Electric / Electric & HP Models), 42" Tall Cabinet  
Coil Guard (Gas / Electric Models), 42" Tall Cabinet  
Hail Guard Kit  
Hail Guard Kit, 42" Tall Cabinet  
Gas Piping Kit  
Propane Conversion Kit  
High Altitude Kit for Natural Gas  
High Altitude Kit for Propane  
Flue Exhaust Extension Kit  
2BC04700106  
2BC04700151  
2BC04700154  
1FL0402  
Gas Heat Kit, -60 deg F, 230V  
Gas Heat Kit, -60 deg F, 460V  
Gas Heat Kit, -60 deg F, 575V  
Permanent Filter Kit (Includes (4) Four Filters)  
Permanent Filter Kit, (Includes (4) Four Filters) 42" Tall Cabinet  
Dirty Filter Switch  
1FL0423  
2DF0401  
1FF0410  
Filter Frame Kit, Metal  
1FF0411  
Metal Filter Frame Kit, 42" Tall Cabinet  
Johnson Controls Unitary Products  
9
246645-YTG-C-0708  
NOMENCLATURE  
®
6.5-12.5 Ton York Model Number Nomenclature  
D M 090 N10 A 2 A AA 3 0 1 2 4 A  
Product Category  
Product Style  
D = A/C, Single Pkg., R-22  
A = Style A  
B = Style B  
C = Style C  
Product Identifier  
M = 9.0 EER A/C  
Configuration Options (not required for all units)  
These four digits will not be assigned until a quote is requested, or an order placed.  
SS Drain Pan  
CPC Controller, DFS, APS  
Nominal Cooling Capacity  
Johnson Controller UNT 1126 (N2 protocol), DFS, APS  
Honeywell Controller, DFS, APS  
078 = 6.5 Ton  
090 = 7.5 Ton  
102 = 8.5 Ton  
120 = 10.0 Ton  
150 = 12.5 Ton  
Novar Controller, DFS, APS  
Simplicity IntelliComfort Controller  
Simplicity IntelliComfort Controller w/ModLinc  
York Commercial Comfort System (YCCS) Rtu Controller  
2" Pleated filters  
Heat Type and Nominal Heat Capacity  
C00 = Cooling Only. No heat installed  
BAS Ready Unit with Belimo Economizer  
Shipping Bag  
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned  
Gas Heat Options  
Product Generation  
N10 = 100 MBH Output Aluminized Steel  
N15 = 150 MBH Output Aluminized Steel  
N20 = 200 MBH Output Aluminized Steel  
S10 = 100 MBH Output Stainless Steel  
S15 = 150 MBH Output Stainless Steel  
S20 = 200 MBH Output Stainless Steel  
3 = Third Generation  
4 = Fourth Generation  
Additional Options  
Electric Heat Options  
AA = None  
RC = Coil Guard, Shipping Bag & American Flag  
AB = Phase Monitor  
TA = Technicoat Condenser Coil  
E09 = 9 KW  
E18 = 18 KW  
E24 = 24 KW  
E36 = 36 KW  
E54 = 54 KW  
AC = Coil Guard  
AD = Dirty Filter Switch  
AE = Phase Monitor & Coil Guard  
AF = Phase Monitor & Dirty Filter Switch  
AG = Coil Guard & Dirty Filter Switch  
AH = Phase Monitor, Coil Guard & Dirty Filter Switch  
TJ = Technicoat Evaporator Coil  
TS = Technicoat Evaporator & Condenser Coils  
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be  
located in digits 15-18.  
Airflow  
A = Std. Motor  
B = Std. Motor/Econo./Barometric Relief (Downflow  
Only)  
Installation Options  
C = Std. Motor/Econo./Power Exhaust (Downflow Only)  
D = Std. Motor/Motorized Damper (Downflow Only)  
E = Std. Motor/Horizontal Economizer (No Baro.)  
F = Std. Motor/Slab Econo./Power Exhaust  
(Downflow Only)  
A = No Options Installed  
B = Option 1  
C = Option 2  
G = Std. Motor/Slab Econo./Barometric Relief  
(Downflow Only)  
D = Options 1 & 2  
E = Option 3  
N = Hi Static Mtr.  
F = Option 4  
P = Hi Static Mtr./Econo./Barometric Relief  
(Downflow Only)  
G = Options 1 & 3  
H = Options 1 & 4  
J = Options 1, 2 & 3  
K = Options 1, 2, & 4  
L = Options 1,3 & 4  
M = Options 1, 2, 3, & 4  
N = Options 2 & 3  
P = Options 2 & 4  
Q = Options 2, 3, & 4  
R = Options 3 & 4  
S = Option 5  
Q = Hi Static Mtr./Econo./Power Exhaust  
(Downflow Only)  
R = Hi Static Mtr./Motorized Damper (Downflow Only)  
S = Hi Static Mtr./Horizontal Economizer (No Baro.)  
T = Hi Static Mtr./Slab Econo./Power Exhaust  
(Downflow Only)  
U = Hi Static Mtr./Slab Econo./Barometric Relief  
(Downflow only)  
T = Options 1 & 5  
U = Options 1, 3, & 5  
V = Options 1, 4, & 5  
W = Options 1, 3, 4, & 5  
X = Options 3 & 5  
Y = Options 4 & 5  
Z = Options 3, 4 & 5  
Voltage  
2 = 208/230-3-60  
3 = 380-3-60  
4 = 460-3-60  
5 = 575-3-60  
Options  
1 = Disconnect  
2 = Non-Pwr'd Conv. Outlet  
3 = Smoke Detector S.A.  
4 = Smoke Detector R.A.  
5 = Pwr'd Conv. Outlet  
10  
Johnson Controls Unitary Products  
 
246645-YTG-C-0708  
TABLE 2: DM PHYSICAL DATA  
Component  
Models  
102  
078  
090  
120  
150  
Blower, Centrifugal (Dia. X Wd. in.)  
15 x 15  
1-1/2  
2
12 x 12  
2
12 X 12  
15 x 15  
2
15 x 15  
3
Evaporator  
Blower  
Motor, Standard (HP)  
Motor, Optional (HP)  
Rows  
3
3
3
3
5
2
2
3
2
3
Fins per Inch  
Height (in.)  
15  
15  
15  
15  
15  
Evaporator  
Coil  
30  
32  
32  
40  
40  
Face Area (ft.2 each)  
Propeller Dia. (in., each)  
Motor (HP, each)  
CFM, Nominal (each)  
Rows (each)  
9.9  
24  
10.67  
24  
10.67  
24  
13.2  
24  
13.2  
24  
Condenser  
Fan  
(2 per Unit)  
1/3  
1700  
1
3/4  
3/4  
2200  
1
3/4  
2200  
1
3/4  
2200  
1
2200  
2
Condenser  
Coil  
(2 per unit)  
Fins per Inch  
20  
20  
20  
20  
20  
Height (in. each)  
24  
28  
36  
44  
44  
Face Area (ft.2 each)  
System 1 (lb./oz.)  
System 2 (lb./oz.)  
Quantity  
7.9  
4/6  
4/0  
2
9.33  
4/10  
3/14  
2
12  
14.5  
6/12  
6/12  
2
14.5  
10/12  
11/0  
2
5/8  
5/2  
2
Refrigerant  
Charge  
Compressors  
Air Filters  
Type  
Recip  
25x20x2  
4
Recip  
25x16x2  
4
Recip.  
25x16x2  
4
Recip  
25x20x2  
4
Scroll  
25x20x2  
4
Size (Wd. x Ht. x Thickness in.)  
Number Per Unit  
Johnson Controls Unitary Products  
11  
 
246645-YTG-C-0708  
TABLE 3: DM CAPACITY RATINGS  
Cooling Capacities  
Gas Heat Capacity  
Nominal  
Electric Heat  
*
ARI Ratings  
Sound  
Rating  
Gas Line  
Size  
(in. OD)  
Size  
CFM  
Model  
(Tons)  
Seasonal Temp.  
Efficiency Rise  
Capacity  
Input Output  
(MBH) (MBH)  
(dB)  
MBH EER IPLV  
(kW)  
(%)  
(°F)  
Cooling  
Only  
-
-
-
-
-
-
-
-
-
Electric  
Heat  
078  
(6-1/2)  
9, 18, 24, 34  
-
-
77  
9.0  
9.0  
9.0  
9.0  
9.3  
9.45  
2600  
84  
89  
90  
90  
90  
Gas Heat  
Gas Heat  
-
-
120  
180  
96  
80  
80  
20-50  
35-65  
3/4  
3/4  
144  
Cooling  
Only  
-
-
-
-
-
-
-
-
-
-
-
Electric  
Heat  
090  
(7-1/2)  
18, 34  
86  
9.2  
2886  
Gas Heat  
Gas Heat  
-
-
120  
180  
96  
80  
80  
15-45  
30-60  
3/4  
3/4  
144  
Cooling  
Only  
-
-
-
-
-
-
-
-
-
-
-
Electric  
Heat  
102  
(8-1/2)  
9, 18, 24, 34  
99  
10.04 3400  
Gas Heat  
Gas Heat  
-
-
120  
180  
96  
80  
80  
15-45  
30-60  
3/4  
3/4  
144  
Cooling  
Only  
-
-
-
-
-
-
-
-
-
-
-
Electric  
Heat  
120  
(10)  
9, 24, 34 54  
120  
9.10  
4000  
Gas Heat  
Gas Heat  
-
-
180  
240  
144  
192  
80  
80  
20-50  
35-65  
3/4  
3/4  
Cooling  
Only  
-
-
-
-
-
-
-
-
-
-
-
Electric  
Heat  
150  
(12-1/2)  
9, 24, 34, 54  
144  
9.25  
4500  
Gas Heat  
Gas Heat  
-
-
180  
240  
144  
192  
80  
80  
10-40  
25-55  
3/4  
3/4  
*
Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb.  
Rated in accordance with ARI 270 standard.  
See Table 20.  
TABLE 4: UNIT VOLTAGE LIMITATIONS  
POWER RATING  
208/230-3-60  
460-3-60  
MIN.  
187  
432  
540  
MAX.  
252  
504  
575-3-60  
630  
12  
Johnson Controls Unitary Products  
   
246645-YTG-C-0708  
TABLE 5: COOLING CAPACITY DM078 (6-1/2 TON) UNIT  
Air On  
Temperature of Air on Condenser Coil 85°F  
Evap. Coil  
Temperature of Air on Condenser Coil 95°F  
Sensible Capacity (MBH)*  
Return Dry Bulb (°F)  
Sensible Capacity (MBH)*  
Return Dry Bulb (°F)  
Tot.  
Cap.*  
(MBH)  
Tot.  
Input†  
(kW)  
Tot.  
Cap.* Input†  
(MBH)  
Tot.  
WB  
(°F)  
CFM  
1950  
2275  
2600  
2925  
3250  
(kW)  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
87  
80  
71  
66  
91  
83  
74  
69  
94  
87  
77  
72  
95  
88  
77  
73  
96  
89  
78  
74  
6.8  
6.7  
6.4  
6.4  
6.9  
6.7  
6.5  
6.5  
7.0  
6.8  
6.6  
6.6  
7.0  
6.8  
6.6  
6.6  
7.0  
6.8  
6.6  
6.6  
49  
61  
71  
66  
54  
67  
74  
69  
59  
74  
77  
72  
63  
78  
77  
73  
67  
83  
78  
74  
43  
55  
66  
66  
47  
61  
72  
69  
52  
66  
77  
72  
55  
70  
77  
73  
58  
73  
78  
74  
37  
50  
61  
61  
41  
54  
66  
67  
44  
58  
72  
72  
46  
61  
75  
73  
48  
64  
78  
74  
32  
44  
55  
56  
34  
47  
60  
60  
37  
51  
64  
65  
37  
52  
66  
64  
38  
54  
68  
64  
26  
38  
50  
50  
28  
41  
53  
54  
29  
43  
57  
57  
29  
44  
58  
56  
29  
44  
59  
54  
-
-
78  
73  
63  
59  
82  
76  
66  
62  
86  
80  
69  
65  
85  
79  
69  
64  
85  
78  
68  
64  
7.3  
7.1  
6.9  
6.8  
7.4  
7.2  
6.9  
6.9  
7.5  
7.3  
7.0  
7.0  
7.5  
7.3  
7.1  
7.0  
7.5  
7.3  
7.1  
7.1  
45  
57  
63  
59  
50  
64  
66  
62  
56  
70  
69  
65  
60  
74  
69  
64  
64  
78  
68  
64  
40  
52  
61  
59  
44  
57  
65  
62  
48  
63  
69  
65  
51  
66  
69  
64  
54  
70  
68  
64  
34  
46  
56  
54  
37  
51  
61  
60  
41  
55  
67  
65  
43  
58  
67  
64  
44  
60  
68  
64  
28  
41  
50  
49  
31  
44  
55  
53  
33  
48  
59  
57  
34  
49  
59  
56  
35  
50  
58  
54  
23  
35  
45  
43  
24  
38  
48  
46  
26  
40  
52  
50  
25  
40  
50  
47  
25  
41  
49  
45  
-
-
33  
44  
44  
-
34  
47  
47  
-
36  
49  
49  
-
35  
49  
47  
-
27  
39  
39  
-
28  
40  
40  
-
28  
42  
42  
-
26  
40  
38  
-
29  
39  
37  
-
31  
42  
40  
-
33  
44  
42  
-
32  
42  
39  
-
24  
33  
32  
-
24  
35  
33  
-
25  
37  
35  
-
23  
33  
30  
-
35  
49  
45  
25  
39  
35  
31  
39  
35  
21  
29  
25  
Temperature of Air on Condenser Coil 105°F  
Temperature of Air on Condenser Coil 115°F  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
73  
66  
64  
54  
76  
68  
67  
56  
78  
71  
69  
58  
78  
70  
69  
58  
78  
70  
69  
57  
7.8  
7.5  
7.4  
7.3  
7.9  
7.6  
7.5  
7.4  
8.0  
7.7  
7.5  
7.5  
8.0  
7.7  
7.6  
7.5  
8.1  
7.8  
7.6  
7.6  
43  
54  
61  
54  
48  
60  
65  
56  
53  
66  
69  
58  
57  
68  
69  
58  
61  
70  
69  
57  
37  
48  
57  
54  
41  
54  
62  
56  
45  
59  
67  
58  
48  
62  
68  
58  
52  
66  
69  
57  
31  
43  
52  
48  
34  
47  
57  
53  
38  
51  
62  
58  
40  
54  
64  
58  
42  
57  
67  
57  
26  
37  
46  
43  
28  
40  
50  
46  
30  
44  
54  
50  
31  
46  
56  
49  
32  
48  
57  
48  
20  
32  
41  
37  
21  
34  
44  
40  
22  
36  
47  
42  
23  
37  
47  
40  
23  
38  
48  
38  
-
-
67  
58  
66  
48  
69  
60  
67  
49  
71  
61  
69  
50  
71  
62  
69  
51  
71  
62  
70  
51  
8.3  
7.9  
7.9  
7.8  
8.4  
8.0  
8.0  
7.9  
8.4  
8.1  
8.0  
7.9  
8.5  
8.2  
8.1  
8.0  
8.6  
8.3  
8.2  
8.1  
40  
51  
59  
48  
45  
56  
64  
49  
49  
61  
69  
50  
54  
62  
69  
51  
59  
62  
70  
51  
35  
45  
54  
48  
38  
50  
59  
49  
42  
55  
64  
50  
46  
58  
67  
51  
49  
62  
70  
51  
29  
40  
48  
43  
32  
43  
52  
46  
34  
47  
57  
50  
37  
51  
61  
51  
40  
55  
66  
51  
23  
34  
42  
37  
25  
37  
46  
40  
27  
39  
49  
43  
28  
42  
53  
42  
30  
45  
56  
41  
18  
29  
37  
31  
18  
30  
39  
33  
19  
32  
42  
35  
20  
33  
44  
33  
20  
35  
46  
31  
-
-
26  
35  
32  
-
27  
37  
33  
-
28  
39  
35  
-
28  
38  
32  
-
21  
30  
26  
-
21  
31  
27  
-
21  
31  
27  
-
20  
30  
23  
-
23  
31  
26  
-
24  
33  
27  
-
24  
34  
28  
-
25  
35  
25  
-
17  
26  
20  
-
17  
26  
20  
-
17  
26  
20  
-
16  
27  
16  
-
1950  
2275  
2600  
2925  
3250  
28  
38  
28  
19  
28  
19  
25  
37  
22  
16  
27  
12  
Temperature of Air on Condenser Coil 125°F  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
62  
51  
67  
42  
63  
52  
68  
43  
63  
52  
69  
43  
64  
53  
70  
44  
65  
54  
71  
44  
8.8  
8.4  
8.4  
8.3  
8.8  
8.4  
8.5  
8.3  
8.9  
8.5  
8.5  
8.4  
9.0  
8.6  
8.6  
8.5  
9.1  
8.7  
8.8  
8.6  
38  
48  
57  
42  
42  
52  
63  
43  
46  
52  
69  
43  
52  
53  
70  
44  
57  
54  
71  
44  
32  
42  
50  
42  
35  
46  
56  
43  
39  
50  
62  
43  
43  
53  
66  
44  
47  
54  
71  
44  
27  
37  
44  
37  
29  
40  
48  
40  
31  
43  
52  
43  
34  
47  
58  
44  
38  
52  
65  
44  
21  
31  
39  
31  
22  
33  
41  
33  
23  
35  
44  
35  
26  
39  
50  
35  
28  
42  
55  
34  
15  
25  
33  
26  
16  
27  
35  
27  
16  
28  
37  
28  
17  
30  
41  
26  
18  
32  
45  
25  
-
-
*
These capacities are gross ratings. For net  
capacity, deduct air blower motor, MBH = 3.415  
x kW. Refer to the appropriate Blower Perfor-  
mance Table for the kW of the supply air  
blower motor.  
These ratings include condenser fan motors  
and the compressor motors but not the supply  
air blower motor.  
20  
27  
20  
-
20  
28  
20  
-
20  
29  
20  
-
21  
32  
18  
-
14  
22  
15  
-
13  
22  
14  
-
12  
21  
13  
-
13  
24  
9
1950  
2275  
2600  
2925  
3250  
-
23  
36  
15  
13  
26  
5
Johnson Controls Unitary Products  
13  
 
246645-YTG-C-0708  
TABLE 6: COOLING CAPACITY DM090 (7-1/2 TON) UNIT  
Temperature of Air on Condenser Coil  
Air on Evap-  
orator Coil  
75°F  
85°F  
*
*
Sensible Capacity (MBH)  
Return Dry Bulb (°F)  
Sensible Capacity (MBH)  
Return Dry Bulb (°F)  
Total Total  
Cap.  
Total Total  
Cap.  
WB  
CFM  
*
*
Input  
Input  
(°F)  
(MBH) (kW)  
(MBH) (kW)  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
101.7  
96.3  
89.4  
88.6  
105.2  
99.6  
92.5  
91.6  
108.7  
102.9  
95.6  
7.2  
7.1  
7.0  
6.9  
7.3  
7.2  
7.0  
7.0  
7.3  
7.2  
7.1  
7.0  
7.3  
7.2  
7.1  
7.1  
7.4  
7.2  
7.1  
7.1  
57.5 51.1 44.7 38.3 31.8  
-
-
96.7  
7.8  
7.6  
7.5  
7.5  
7.8  
7.7  
7.5  
7.5  
7.9  
7.8  
7.6  
7.6  
7.9  
7.8  
7.6  
7.6  
7.9  
7.8  
7.6  
7.6  
55.8 49.4 43.0 36.6 30.1  
-
-
73.3 66.8 60.4 54.0 47.6 41.2 34.8 90.8  
89.4 80.1 73.7 67.3 60.9 54.4 48.0 83.5  
88.6 85.9 79.5 73.1 66.7 60.3 53.8 83.7  
70.8 64.4 58.0 51.6 45.2 38.8 32.4  
83.5 77.4 71.0 64.5 58.1 51.7 45.3  
83.7 81.9 75.5 69.0 62.6 56.2 49.8  
2250  
63.7 56.2 48.6 41.0 33.4  
-
-
99.9  
61.8 54.2 46.6 39.1 31.5  
-
-
67  
80.9 73.3 65.7 58.1 50.5 43.0 35.4 93.8  
92.5 87.8 80.1 72.5 65.0 57.4 49.8 86.2  
91.6 90.3 86.5 78.9 71.3 63.7 56.1 86.5  
78.1 70.6 63.0 55.4 47.8 40.2 32.6  
86.2 83.2 77.0 69.4 61.9 54.3 46.7  
86.5 85.6 81.9 74.3 66.7 59.2 51.6  
2625  
62  
57  
72  
70.0 61.2 52.5 43.7 35.0  
-
-
103.1  
67.8 59.1 50.3 41.6 32.8  
-
-
67  
88.5 79.7 71.0 62.2 53.5 44.7 36.0 96.8  
95.6 95.6 86.6 77.8 69.1 60.3 51.6 89.0  
94.7 94.7 93.4 84.6 75.9 67.2 58.4 89.2  
85.4 76.7 67.9 59.2 50.4 41.7 32.9  
89.0 89.0 83.1 74.3 65.6 56.8 48.1  
89.2 89.2 88.4 79.6 70.9 62.1 53.4  
3000  
62  
57  
72  
94.7  
110.1  
104.2  
96.8  
74.1 64.1 54.2 44.2 34.3  
-
-
104.4  
72.3 62.4 52.4 42.5 32.5  
-
-
67  
93.8 83.3 73.3 63.3 53.4 43.4 33.5 98.0  
96.8 96.8 91.1 81.2 71.2 61.2 51.3 90.1  
95.9 95.9 95.2 85.3 75.3 65.4 55.4 90.4  
90.7 80.7 70.8 60.8 50.8 40.9 30.9  
90.1 90.1 86.6 76.6 66.6 56.7 46.7  
90.4 90.4 89.9 80.0 70.0 60.0 50.1  
3375  
62  
57  
72  
67  
62  
57  
95.9  
111.5  
105.5  
98.0  
78.3 67.1 55.9 44.7 33.5  
-
-
105.7  
76.9 65.7 54.5 43.3 32.2  
-
-
99.1 86.8 75.6 64.4 53.3 42.1 30.9 99.2  
98.0 98.0 95.7 84.5 73.3 62.1 51.0 91.2  
97.1 97.1 97.1 85.9 74.7 63.6 52.4 91.5  
95°F  
96.0 84.8 73.6 62.4 51.2 40.1 28.9  
91.2 91.2 90.0 78.8 67.7 56.5 45.3  
91.5 91.5 91.5 80.3 69.1 57.9 46.8  
105°F  
3750  
97.1  
72  
67  
62  
57  
72  
91.8  
85.3  
77.5  
78.9  
94.6  
87.9  
79.9  
81.3  
97.5  
90.6  
82.3  
83.8  
98.7  
91.7  
83.3  
84.8  
99.9  
92.8  
84.4  
85.9  
8.4  
8.2  
8.0  
8.0  
8.4  
8.3  
8.1  
8.1  
8.5  
8.3  
8.1  
8.2  
8.5  
8.4  
8.2  
8.2  
8.5  
8.4  
8.2  
8.2  
54.1 47.7 41.3 34.9 28.4  
-
-
85.6  
9.0  
8.7  
8.6  
8.6  
9.0  
8.8  
8.6  
8.7  
9.1  
8.9  
8.7  
8.7  
9.1  
8.9  
8.8  
8.8  
9.2  
8.9  
8.8  
8.8  
51.6 45.2 38.8 32.3 25.9  
-
-
68.4 62.0 55.6 49.2 42.8 36.3 29.9 78.0  
77.5 74.6 68.2 61.8 55.4 49.0 42.6 72.4  
78.9 77.8 71.4 65.0 58.6 52.1 45.7 73.2  
65.4 59.0 52.6 46.2 39.8 33.4 26.9  
72.4 70.5 64.0 57.6 51.2 44.8 38.4  
73.2 71.7 65.3 58.9 52.5 46.1 39.6  
2250  
59.9 52.3 44.7 37.1 29.6  
-
-
87.9  
57.1 49.6 42.0 34.4 26.8  
-
-
67  
75.4 67.8 60.2 52.7 45.1 37.5 29.9 80.1  
79.9 78.5 73.9 66.3 58.8 51.2 43.6 74.3  
81.3 80.8 77.4 69.8 62.2 54.6 47.0 75.2  
71.7 64.6 57.0 49.4 41.8 34.3 26.7  
74.3 73.3 69.4 61.8 54.2 46.6 39.1  
75.2 74.4 70.7 63.2 55.6 48.0 40.4  
2625  
62  
57  
72  
65.7 56.9 48.2 39.4 30.7  
-
-
90.2  
62.7 54.0 45.2 36.5 27.7  
-
-
67  
82.4 73.6 64.9 56.1 47.4 38.6 29.9 82.1  
82.3 82.3 79.6 70.9 62.1 53.4 44.6 76.2  
83.8 83.8 83.3 74.6 65.8 57.1 48.3 77.1  
78.0 70.1 61.4 52.6 43.9 35.1 26.4  
76.2 76.2 74.7 66.0 57.2 48.5 39.7  
77.1 77.1 76.2 67.4 58.7 49.9 41.2  
3000  
62  
57  
72  
70.6 60.6 50.7 40.7 30.7  
-
-
91.5  
67.7 57.7 47.8 37.8 27.8  
-
-
67  
87.6 78.2 68.2 58.3 48.3 38.3 28.4 83.3  
83.3 83.3 82.0 72.0 62.1 52.1 42.1 77.3  
84.8 84.8 84.6 74.6 64.7 54.7 44.7 78.2  
81.2 74.8 64.9 54.9 44.9 35.0 25.0  
77.3 77.3 76.6 66.6 56.6 46.7 36.7  
78.2 78.2 77.8 67.8 57.8 47.9 37.9  
3375  
62  
57  
72  
67  
62  
57  
75.5 64.3 53.1 42.0 30.8  
-
-
92.8  
72.7 61.5 50.3 39.2 28.0  
-
-
92.8 82.7 71.6 60.4 49.2 38.0 26.9 84.5  
84.4 84.4 84.4 73.2 62.0 50.8 39.6 78.4  
85.9 85.9 85.9 74.7 63.5 52.3 41.1 79.3  
115°F  
84.5 79.4 68.3 57.2 46.0 34.8 23.6  
78.4 78.4 78.4 67.2 56.1 44.9 33.7  
79.3 79.3 79.3 68.1 57.0 45.8 34.6  
125°F  
3750  
72  
67  
62  
57  
72  
79.5  
70.7  
67.3  
67.6  
81.2  
72.2  
68.7  
69.0  
82.9  
73.7  
70.1  
70.4  
84.3  
74.9  
71.3  
71.6  
85.7  
76.1  
72.5  
72.8  
9.6  
9.3  
9.1  
9.1  
9.6  
9.4  
9.2  
9.2  
9.7  
9.5  
9.3  
9.3  
9.8  
9.5  
9.3  
9.3  
9.8  
9.5  
9.4  
9.4  
49.1 42.6 36.2 29.8 23.4  
-
-
73.4  
10.1  
9.8  
9.7  
9.7  
10.2  
9.9  
9.8  
9.8  
10.3  
10.0  
9.9  
46.5 40.1 33.7 27.3 20.9  
-
-
62.5 56.0 49.6 43.2 36.8 30.4 24.0 63.4  
67.3 66.3 59.9 53.4 47.0 40.6 34.2 62.2  
67.6 65.6 59.2 52.8 46.4 40.0 33.5 61.9  
59.5 53.1 46.6 40.2 33.8 27.4 21.0  
62.2 62.1 55.7 49.2 42.8 36.4 30.0  
61.9 59.5 53.1 46.7 40.3 33.9 27.4  
2250  
54.4 46.8 39.2 31.7 24.1  
-
-
74.5  
51.7 44.1 36.5 28.9 21.3  
-
-
67  
68.1 61.3 53.8 46.2 38.6 31.0 23.4 64.3  
68.7 68.2 64.8 57.3 49.7 42.1 34.5 63.1  
69.0 68.0 64.1 56.6 49.0 41.4 33.8 62.8  
64.3 58.1 50.5 42.9 35.4 27.8 20.2  
63.1 63.0 60.3 52.7 45.1 37.6 30.0  
62.8 61.6 57.5 49.9 42.4 34.8 27.2  
2625  
62  
57  
72  
59.8 51.0 42.3 33.5 24.8  
-
-
75.5  
56.8 48.1 39.3 30.6 21.8  
-
-
67  
73.7 66.6 57.9 49.1 40.4 31.6 22.9 65.2  
70.1 70.1 69.8 61.1 52.3 43.6 34.8 64.0  
70.4 70.4 69.1 60.3 51.6 42.8 34.1 63.7  
65.2 63.2 54.4 45.7 36.9 28.2 19.4  
64.0 64.0 64.0 56.2 47.4 38.7 29.9  
63.7 63.7 62.0 53.2 44.5 35.7 27.0  
3000  
62  
57  
72  
9.9  
64.8 54.9 44.9 34.9 25.0  
-
-
77.0  
10.4  
10.0  
9.9  
61.9 52.0 42.0 32.1 22.1  
-
-
67  
74.9 71.4 61.5 51.5 41.6 31.6 21.6 66.5  
71.3 71.3 71.2 61.2 51.2 41.3 31.3 65.3  
71.6 71.6 70.9 61.0 51.0 41.0 31.1 65.0  
66.5 66.5 58.1 48.2 38.2 28.2 18.3  
65.3 65.3 65.3 55.8 45.8 35.8 25.9  
65.0 65.0 64.1 54.1 44.2 34.2 24.2  
3375  
62  
57  
72  
67  
62  
57  
9.9  
69.9 58.7 47.5 36.3 25.2  
-
-
78.6  
10.4  
10.1  
10.0  
9.9  
67.1 55.9 44.7 33.5 22.4  
-
-
76.1 76.1 65.1 53.9 42.7 31.6 20.4 67.8  
72.5 72.5 72.5 61.3 50.1 38.9 27.8 66.5  
72.8 72.8 72.8 61.6 50.4 39.3 28.1 66.2  
67.8 67.8 61.9 50.7 39.5 28.3 17.2  
66.5 66.5 66.5 55.4 44.2 33.0 21.8  
66.2 66.2 66.2 55.1 43.9 32.7 21.5  
3750  
*
The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-  
mance table for the kW of the supply air blower motor.  
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.  
14  
Johnson Controls Unitary Products  
 
246645-YTG-C-0708  
TABLE 7: COOLING CAPACITY DM102 (8-1/2 TON) UNIT  
Temperature of Air on Condenser Coil  
Air on Evap-  
orator Coil  
75°F  
85°F  
*
*
Sensible Capacity (MBH)  
Return Dry Bulb (°F)  
Sensible Capacity (MBH)  
Return Dry Bulb (°F)  
Total Total  
Cap.  
Total Total  
Cap.  
WB  
CFM  
*
*
Input  
Input  
(°F)  
(MBH) (kW)  
(MBH) (kW)  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
123.8  
112.4  
106.9  
99.3  
7.4  
7.3  
7.1  
7.1  
7.4  
7.3  
7.2  
7.1  
7.5  
7.4  
7.2  
7.2  
7.5  
7.4  
7.3  
7.3  
7.6  
7.5  
7.3  
7.3  
68.9 61.6 54.3 47.1 39.8  
-
-
114.8  
8.0  
7.9  
7.7  
7.7  
8.1  
7.9  
7.7  
7.8  
8.2  
8.0  
7.8  
7.8  
8.2  
8.0  
7.8  
7.9  
8.3  
8.1  
7.9  
7.9  
65.3 58.0 50.8 43.5 36.2  
-
-
85.2 78.0 70.7 63.4 56.2 48.9 41.6 104.3  
106.9 95.5 88.1 80.8 73.5 66.3 59.0 96.4  
99.3 98.9 91.5 84.2 76.9 69.7 62.4 93.2  
81.9 74.6 67.3 60.1 52.8 45.5 38.3  
96.4 90.7 83.5 76.2 68.9 61.6 54.4  
93.2 92.9 85.7 78.4 71.1 63.9 56.6  
2550  
127.6  
115.9  
110.3  
102.4  
131.5  
119.4  
113.7  
105.5  
134.7  
122.3  
116.4  
108.1  
137.9  
125.3  
119.2  
110.7  
75.6 67.0 58.5 49.9 41.3  
-
-
118.7  
72.0 63.4 54.8 46.2 37.6  
-
-
67  
93.2 84.6 76.0 67.4 58.8 50.2 41.7 107.8  
110.3 104.6 94.7 86.1 77.5 69.0 60.4 99.7  
102.4 102.2 98.4 89.8 81.2 72.6 64.0 96.3  
89.9 81.3 72.7 64.1 55.5 46.9 38.3  
99.7 96.9 90.1 81.5 72.9 64.3 55.7  
96.3 96.2 92.5 83.9 75.3 66.7 58.1  
2975  
62  
57  
72  
82.4 72.5 62.6 52.6 42.7  
-
-
122.6  
78.7 68.7 58.8 48.9 39.0  
-
-
67  
101.2 91.3 81.3 71.4 61.5 51.6 41.7 111.3  
113.7 113.7 101.4 91.5 81.5 71.6 61.7 103.0  
105.5 105.5 105.3 95.4 85.5 75.5 65.6 99.5  
97.9 88.0 78.0 68.1 58.2 48.3 38.4  
103.0 103.0 96.7 86.8 76.9 67.0 57.1  
99.5 99.5 99.3 89.4 79.5 69.5 59.6  
3400  
62  
57  
72  
88.7 77.5 66.2 54.9 43.6  
-
-
125.2  
85.0 73.7 62.4 51.1 39.8  
-
-
67  
110.0 97.3 86.0 74.7 63.4 52.1 40.9 113.7  
116.4 116.4 110.3 99.0 87.7 76.4 65.1 105.2  
108.1 108.1 108.0 96.7 85.4 74.1 62.8 101.6  
105.4 94.1 82.8 71.5 60.2 48.9 37.6  
105.2 105.2 102.1 90.8 79.5 68.2 56.9  
101.6 101.6 101.5 90.2 78.9 67.6 56.4  
3825  
62  
57  
72  
67  
62  
57  
95.1 82.4 69.8 57.1 44.4  
-
-
127.8  
91.3 78.7 66.0 53.3 40.7  
-
-
118.8 103.4 90.7 78.0 65.4 52.7 40.0 116.1  
119.2 119.2 119.2 106.5 93.8 81.2 68.5 107.4  
110.7 110.7 110.7 98.0 85.3 72.6 60.0 103.8  
95°F  
112.9 100.2 87.6 74.9 62.2 49.6 36.9  
107.4 107.4 107.4 94.8 82.1 69.4 56.8  
103.8 103.8 103.8 91.1 78.4 65.8 53.1  
105°F  
4250  
72  
67  
62  
57  
72  
105.8  
96.1  
86.0  
87.0  
109.7  
99.7  
89.1  
90.2  
113.6  
103.2  
92.3  
8.7  
8.5  
8.3  
8.3  
8.8  
8.5  
8.3  
8.4  
8.8  
8.6  
8.4  
8.4  
8.9  
8.6  
8.4  
8.5  
8.9  
8.7  
8.5  
8.5  
61.7 54.5 47.2 39.9 32.6  
-
-
96.9  
9.4  
9.1  
8.9  
8.9  
9.4  
9.1  
9.0  
9.0  
9.5  
9.2  
9.0  
9.1  
9.5  
9.2  
9.1  
9.1  
9.6  
9.3  
9.1  
9.1  
58.0 50.8 43.5 36.2 29.0  
-
-
78.5 71.3 64.0 56.7 49.5 42.2 34.9 86.6  
86.0 86.0 78.8 71.6 64.3 57.0 49.7 79.4  
87.0 87.0 79.9 72.6 65.3 58.1 50.8 79.5  
74.3 67.0 59.7 52.5 45.2 37.9 30.7  
79.4 78.9 71.7 64.4 57.1 49.9 42.6  
79.5 79.4 72.2 65.0 57.7 50.4 43.2  
2550  
68.3 59.7 51.1 42.5 34.0  
-
-
100.5  
64.6 56.0 47.4 38.8 30.2  
-
-
67  
86.6 78.0 69.4 60.8 52.2 43.6 35.0 89.8  
89.1 89.1 85.4 76.8 68.3 59.7 51.1 82.3  
90.2 90.2 86.6 78.0 69.4 60.8 52.2 82.5  
81.5 73.7 65.1 56.5 47.9 39.3 30.7  
82.3 82.1 78.1 69.5 60.9 52.3 43.7  
82.5 82.4 78.7 70.1 61.5 52.9 44.3  
2975  
62  
57  
72  
74.9 65.0 55.1 45.2 35.3  
-
-
104.0  
71.1 61.2 51.3 41.3 31.4  
-
-
67  
94.6 84.7 74.7 64.8 54.9 45.0 35.1 93.0  
92.3 92.3 92.1 82.1 72.2 62.3 52.4 85.3  
93.5 93.5 93.3 83.4 73.5 63.5 53.6 85.4  
88.7 80.3 70.4 60.5 50.6 40.7 30.8  
85.3 85.3 84.5 74.6 64.6 54.7 44.8  
85.4 85.4 85.1 75.2 65.3 55.4 45.5  
3400  
62  
57  
72  
93.5  
115.7  
105.1  
94.0  
81.2 70.0 58.7 47.4 36.1  
-
-
105.6  
77.4 66.1 54.8 43.5 32.2  
-
-
67  
100.8 90.9 79.6 68.3 57.0 45.7 34.4 94.5  
94.0 94.0 93.9 82.6 71.3 60.0 48.7 86.6  
95.2 95.2 95.1 83.8 72.5 61.2 49.9 86.7  
92.3 85.7 75.3 64.0 52.7 41.4 30.1  
86.6 86.6 86.2 74.9 63.6 52.3 41.0  
86.7 86.7 86.6 75.3 64.0 52.7 41.4  
3825  
62  
57  
72  
67  
62  
57  
95.2  
117.7  
107.0  
95.7  
87.6 74.9 62.2 49.6 36.9  
-
-
107.3  
83.7 71.0 58.3 45.7 33.0  
-
-
107.0 97.1 84.4 71.8 59.1 46.4 33.7 95.9  
95.7 95.7 95.7 83.0 70.4 57.7 45.0 87.9  
96.9 96.9 96.9 84.2 71.5 58.9 46.2 88.1  
115°F  
95.9 91.0 80.2 67.5 54.8 42.1 29.5  
87.9 87.9 87.9 75.3 62.6 49.9 37.3  
88.1 88.1 88.1 75.4 62.7 50.1 37.4  
125°F  
4250  
96.9  
72  
67  
62  
57  
72  
88.0  
77.2  
72.9  
72.1  
91.2  
80.0  
75.5  
74.7  
94.5  
82.8  
78.2  
77.4  
95.6  
83.9  
79.2  
78.3  
96.8  
84.9  
80.2  
79.3  
10.0  
9.7  
9.6  
9.6  
10.1  
9.7  
9.6  
9.6  
10.1  
9.8  
9.7  
9.7  
10.2  
9.8  
9.7  
9.7  
10.2  
9.9  
9.8  
9.8  
54.3 47.1 39.8 32.5 25.3  
-
-
79.1  
10.7  
10.2  
10.2  
10.2  
10.7  
10.3  
10.2  
10.2  
10.8  
10.4  
10.3  
10.3  
10.9  
10.4  
10.4  
10.4  
10.9  
10.5  
10.4  
10.4  
50.7 43.4 36.1 28.8 21.6  
-
-
70.0 62.8 55.5 48.2 40.9 33.7 26.4 67.7  
72.9 71.8 64.5 57.3 50.0 42.7 35.5 66.3  
72.1 71.9 64.6 57.3 50.1 42.8 35.5 64.6  
65.8 58.5 51.2 44.0 36.7 29.4 22.1  
66.3 64.7 57.4 50.1 42.9 35.6 28.3  
64.6 64.3 57.0 49.7 42.4 35.2 27.9  
2550  
60.8 52.2 43.6 35.0 26.4  
-
-
82.0  
57.0 48.4 39.8 31.3 22.7  
-
-
67  
76.4 69.4 60.8 52.2 43.6 35.0 26.4 70.2  
75.5 75.0 70.7 62.1 53.5 44.9 36.3 68.7  
74.7 74.6 70.8 62.2 53.6 45.0 36.4 67.0  
70.2 65.1 56.5 47.9 39.3 30.7 22.1  
68.7 68.0 63.4 54.8 46.2 37.6 29.0  
67.0 66.8 62.9 54.3 45.7 37.1 28.5  
2975  
62  
57  
72  
67.2 57.3 47.4 37.5 27.6  
-
-
84.9  
63.4 53.5 43.6 33.7 23.7  
-
-
67  
82.8 76.0 66.1 56.2 46.3 36.4 26.4 72.6  
78.2 78.2 76.9 67.0 57.1 47.1 37.2 71.2  
77.4 77.4 77.0 67.1 57.1 47.2 37.3 69.3  
72.6 71.7 61.8 51.9 41.9 32.0 22.1  
71.2 71.2 69.3 59.4 49.5 39.6 29.6  
69.3 69.3 68.8 58.9 49.0 39.1 29.2  
3400  
62  
57  
72  
73.5 62.2 50.9 39.6 28.3  
-
-
85.6  
69.6 58.3 47.1 35.8 24.5  
-
-
67  
83.9 80.4 71.0 59.7 48.4 37.1 25.8 73.2  
79.2 79.2 78.5 67.2 55.9 44.6 33.4 71.8  
78.3 78.3 78.1 66.8 55.5 44.3 33.0 69.9  
73.2 73.2 66.7 55.4 44.1 32.8 21.5  
71.8 71.8 70.8 59.6 48.3 37.0 25.7  
69.9 69.9 69.7 58.4 47.1 35.8 24.5  
3825  
62  
57  
72  
67  
62  
57  
79.8 67.1 54.4 41.8 29.1  
-
-
86.3  
75.9 63.2 50.5 37.9 25.2  
-
-
84.9 84.9 75.9 63.2 50.5 37.9 25.2 73.8  
80.2 80.2 80.2 67.5 54.8 42.1 29.5 72.4  
79.3 79.3 79.3 66.6 53.9 41.3 28.6 70.5  
73.8 73.8 71.6 58.9 46.3 33.6 20.9  
72.4 72.4 72.4 59.7 47.0 34.4 21.7  
70.5 70.5 70.5 57.8 45.1 32.5 19.8  
4250  
*
The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-  
mance table for the kW of the supply air blower motor.  
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.  
Johnson Controls Unitary Products  
15  
 
246645-YTG-C-0708  
TABLE 8: COOLING CAPACITY DM120 (10 TON) UNIT  
Air On  
Temperature of Air on Condenser Coil 85°F  
Evap. Coil  
Temperature of Air on Condenser Coil 95°F  
Sensible Capacity (MBH)*  
Return Dry Bulb (°F)  
Sensible Capacity (MBH)*  
Tot.  
Tot.  
Cap.* Input†  
(MBH)  
Tot.  
Tot.  
Cap.* Input†  
(MBH)  
WB  
(°F)  
Return Dry Bulb (°F)  
CFM  
3000  
3500  
4000  
4500  
5000  
(kW)  
(kW)  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
132  
124  
116  
110  
135  
127  
119  
112  
138  
130  
121  
115  
141  
132  
124  
117  
144  
135  
126  
119  
11.0  
10.7  
10.5  
10.3  
11.1  
10.8  
10.6  
10.4  
11.2  
10.9  
10.7  
10.5  
11.3  
11.0  
10.7  
10.5  
11.3  
11.0  
10.8  
10.6  
76  
96  
68  
87  
59  
79  
98  
50  
70  
89  
92  
53  
74  
95  
98  
56  
78  
42  
62  
81  
83  
43  
64  
84  
87  
44  
66  
88  
91  
45  
69  
92  
90  
45  
71  
95  
90  
-
-
125  
116  
106  
106  
129  
120  
110  
109  
133  
124  
113  
113  
135  
126  
115  
115  
138  
128  
117  
117  
11.7  
11.4  
11.1  
11.1  
11.8  
11.5  
11.2  
11.2  
12.0  
11.7  
11.3  
11.3  
12.0  
11.7  
11.4  
11.4  
12.1  
11.8  
11.5  
11.5  
74  
93  
65  
84  
57  
75  
91  
95  
62  
82  
99  
48  
67  
82  
86  
52  
72  
89  
93  
55  
77  
95  
40  
58  
74  
78  
41  
62  
79  
83  
43  
65  
84  
88  
43  
66  
85  
88  
43  
67  
86  
87  
-
-
53  
72  
75  
-
54  
74  
77  
-
55  
76  
80  
-
55  
78  
77  
-
45  
64  
66  
-
44  
64  
67  
-
43  
65  
68  
-
42  
65  
64  
-
50  
65  
69  
-
52  
69  
73  
-
54  
72  
76  
-
53  
72  
74  
-
41  
57  
61  
-
42  
58  
63  
-
42  
60  
65  
-
39  
58  
61  
-
115 106  
110 109 101  
83  
104  
118 114 105  
112 112 108  
91  
113 101  
121 121 111 100  
115 115 115 103  
106 100  
106 103  
82  
102  
110 106  
109 108 103  
90  
112 100  
113 113 107  
113 113 111 100  
96  
119 106  
115 115 112  
115 115 114 101  
102  
126 111  
117 117 116 101  
117 117 117 102  
73  
94  
63  
84  
72  
92  
79  
67  
90  
78  
67  
89  
98  
85  
71  
95  
58  
82  
83  
70  
92  
56  
79  
98  
122 108  
124 124 118 105  
117 117 117 104  
105  
90  
75  
60  
86  
87  
72  
96  
58  
81  
130 116 101  
126 126 125 110  
119 119 119 105  
56  
80  
75  
41  
65  
60  
52  
71  
72  
37  
57  
57  
Temperature of Air on Condenser Coil 105°F  
Temperature of Air on Condenser Coil 115°F  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
117  
107  
97  
12.4  
12.0  
11.6  
11.7  
12.5  
12.1  
11.7  
11.8  
12.7  
12.2  
11.9  
11.9  
12.8  
12.3  
12.0  
12.0  
12.9  
12.4  
12.1  
12.1  
70  
89  
97  
98  
78  
62  
80  
94  
96  
68  
88  
99  
53  
71  
85  
88  
58  
78  
93  
95  
63  
84  
45  
63  
77  
79  
48  
68  
83  
85  
51  
72  
89  
91  
53  
75  
91  
93  
54  
78  
93  
95  
36  
54  
68  
71  
38  
57  
73  
75  
39  
61  
77  
80  
39  
62  
77  
80  
40  
63  
78  
80  
-
-
109  
97  
88  
13.1  
12.5  
12.2  
12.3  
13.2  
12.6  
12.3  
12.4  
13.4  
12.8  
12.4  
12.5  
13.5  
12.9  
12.5  
12.6  
13.6  
13.0  
12.7  
12.7  
67  
85  
88  
91  
75  
94  
91  
94  
82  
103  
94  
97  
89  
106  
96  
99  
96  
58  
76  
88  
89  
64  
83  
91  
93  
70  
91  
94  
97  
76  
98  
96  
99  
81  
50  
67  
80  
81  
54  
73  
87  
88  
59  
79  
94  
95  
63  
84  
96  
98  
66  
90  
99  
41  
59  
71  
72  
44  
63  
76  
78  
47  
68  
82  
83  
49  
71  
83  
85  
51  
75  
84  
87  
33  
50  
62  
64  
34  
53  
66  
67  
35  
56  
70  
71  
36  
58  
70  
72  
37  
60  
69  
72  
-
-
46  
60  
62  
-
47  
62  
65  
-
49  
65  
68  
-
49  
64  
66  
-
37  
51  
54  
-
37  
52  
55  
-
37  
54  
56  
-
35  
51  
53  
-
42  
54  
55  
-
43  
56  
57  
-
44  
59  
60  
-
45  
56  
59  
-
33  
45  
46  
-
33  
46  
47  
-
33  
47  
48  
-
31  
43  
45  
-
3000  
3500  
4000  
4500  
5000  
98  
91  
121  
110  
100  
102  
124  
113  
103  
105  
127  
116  
106  
107  
130  
119  
108  
110  
113  
100  
91  
98  
100  
102 100  
86  
94  
74  
96  
116  
103  
94  
107  
103 103 100  
105 105 103  
93  
112 102  
106 106 104  
107 107 106  
97  
79  
66  
88  
119  
106  
96  
99  
99  
84  
69  
93  
123  
109  
99  
117 108  
108 108 107  
110 110 110  
48  
63  
65  
33  
48  
50  
109 104  
99 99  
102 102 102  
45  
54  
57  
30  
39  
42  
102  
Temperature of Air on Condenser Coil 125°F  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
101  
87  
79  
83  
105  
90  
81  
86  
108  
92  
84  
88  
112  
96  
87  
91  
115  
99  
89  
13.8  
13.0  
12.7  
12.9  
14.0  
13.2  
12.9  
13.0  
14.1  
13.3  
13.0  
13.1  
14.2  
13.4  
13.1  
13.2  
14.4  
13.6  
13.3  
13.4  
64  
80  
79  
83  
71  
89  
81  
86  
78  
92  
84  
88  
86  
96  
87  
91  
93  
99  
89  
94  
55  
72  
79  
82  
61  
79  
81  
85  
66  
86  
84  
88  
72  
94  
87  
91  
78  
99  
89  
94  
46  
63  
74  
74  
51  
69  
80  
80  
55  
75  
84  
87  
59  
80  
87  
90  
63  
86  
89  
94  
38  
55  
65  
65  
40  
59  
70  
70  
43  
63  
75  
75  
46  
67  
75  
77  
48  
71  
75  
79  
29  
46  
57  
56  
30  
49  
60  
60  
31  
51  
64  
63  
32  
54  
62  
64  
33  
56  
60  
65  
-
-
*
These capacities are gross ratings. For net  
capacity, deduct air blower motor, MBH = 3.415  
x kW. Refer to the appropriate Blower Perfor-  
mance Table for the kW of the supply air  
blower motor.  
These ratings include condenser fan motors  
and the compressor motors but not the supply  
air blower motor.  
38  
48  
48  
-
39  
50  
50  
-
40  
52  
52  
-
41  
49  
51  
-
29  
40  
39  
-
29  
40  
40  
-
28  
40  
40  
-
27  
35  
37  
-
3000  
3500  
4000  
4500  
5000  
41  
45  
50  
27  
30  
35  
94  
16  
Johnson Controls Unitary Products  
 
246645-YTG-C-0708  
TABLE 9: COOLING CAPACITY DM150 (12-1/2 TON) UNIT  
Air On  
Temperature of Air on Condenser Coil 85°F  
Evap. Coil  
Temperature of Air on Condenser Coil 95°F  
Sensible Capacity (MBH)*  
Return Dry Bulb (°F)  
Sensible Capacity (MBH)*  
Return Dry Bulb (°F)  
Tot.  
Cap.*  
(MBH)  
Tot.  
Input†  
(kW)  
Tot.  
Cap.* Input†  
(MBH)  
Tot.  
WB  
(°F)  
CFM  
3750  
4375  
5000  
5625  
6250  
(kW)  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
154  
152  
145  
144  
158  
156  
148  
147  
161  
159  
151  
150  
161  
158  
151  
150  
160  
158  
150  
149  
12.0  
11.8  
11.6  
11.6  
12.0  
11.8  
11.7  
11.7  
12.1  
11.8  
11.7  
11.7  
12.1  
11.9  
11.7  
11.7  
12.1  
11.9  
11.7  
11.7  
93  
82  
71  
61  
90  
50  
79  
39  
69  
96  
29  
58  
85  
90  
26  
57  
85  
91  
22  
56  
86  
92  
16  
50  
81  
83  
10  
45  
76  
74  
151  
147  
138  
138  
155  
150  
142  
142  
158  
154  
145  
145  
157  
153  
144  
144  
157  
152  
143  
143  
13.4  
13.1  
13.0  
13.0  
13.5  
13.2  
13.0  
13.0  
13.5  
13.2  
13.1  
13.1  
13.5  
13.2  
13.1  
13.1  
13.5  
13.2  
13.1  
13.0  
91  
80  
70  
98  
59  
88  
48  
77  
38  
66  
91  
94  
37  
68  
94  
98  
36  
69  
97  
27  
56  
80  
84  
24  
55  
81  
85  
22  
55  
83  
87  
16  
50  
76  
78  
10  
45  
69  
69  
122 112 101  
145 138 128 117 106  
144 143 133 122 111 101  
101  
133 120 107  
148 145 136 123 111  
147 147 141 129 116 104  
110  
120 109  
138 134 123 112 101  
138 137 126 116 105  
89  
76  
63  
95  
51  
82  
38  
70  
98  
100  
87  
75  
62  
93  
50  
80  
131 118 106  
142 139 132 119 107  
142 141 136 123 111  
95  
81  
66  
99  
52  
85  
37  
70  
109  
95  
80  
65  
98  
51  
84  
143 129 114  
151 151 144 130 115 101  
150 150 150 136 121 106  
142 128 113  
145 145 141 126 112  
145 145 145 131 116 101  
115  
147 133 116 100  
144 144 142 126 109  
144 144 144 128 111  
122 103  
152 138 119 101  
116  
99  
83  
66  
49  
83  
33  
67  
97  
99  
82  
66  
49  
83  
32  
66  
92  
94  
28  
63  
88  
88  
150 133 117 100  
151 151 147 131 114  
150 150 150 133 116 100  
122 103  
156 138 119 100  
150 150 150 132 113  
149 149 149 130 112  
84  
66  
47  
82  
28  
63  
94  
93  
84  
66  
47  
82  
143 143 143 125 106  
143 143 143 125 106  
Temperature of Air on Condenser Coil 105°F  
Temperature of Air on Condenser Coil 115°F  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
144  
139  
130  
130  
148  
143  
134  
134  
152  
147  
137  
137  
151  
145  
136  
136  
149  
144  
134  
135  
15.1  
14.7  
14.5  
14.5  
15.1  
14.8  
14.6  
14.6  
15.2  
14.9  
14.6  
14.7  
15.3  
14.9  
14.7  
14.7  
15.3  
14.9  
14.7  
14.7  
88  
77  
66  
96  
56  
85  
45  
74  
94  
96  
47  
79  
34  
63  
83  
85  
34  
66  
87  
89  
34  
68  
91  
93  
30  
65  
85  
86  
26  
61  
79  
79  
24  
53  
72  
74  
22  
53  
75  
77  
20  
54  
77  
79  
13  
48  
68  
69  
7
138  
131  
122  
122  
142  
135  
126  
126  
146  
139  
129  
129  
144  
137  
127  
127  
142  
135  
125  
126  
16.7  
16.2  
16.0  
16.1  
16.8  
16.4  
16.1  
16.2  
16.9  
16.5  
16.2  
16.3  
17.0  
16.6  
16.3  
16.4  
17.0  
16.6  
16.3  
16.4  
85  
74  
63  
93  
53  
82  
97  
97  
57  
89  
42  
71  
86  
86  
44  
77  
93  
93  
47  
82  
31  
61  
75  
75  
32  
64  
80  
81  
32  
68  
85  
86  
28  
64  
78  
78  
23  
59  
70  
70  
21  
50  
65  
65  
19  
51  
68  
68  
18  
53  
71  
71  
11  
47  
61  
61  
4
117 106  
130 126 115 104  
130 128 117 106  
114 103  
122 118 107  
122 118 108  
3750  
4375  
5000  
5625  
6250  
98  
85  
72  
60  
91  
95  
82  
70  
129 117 104  
134 131 125 113 100  
134 132 127 114 102  
127 115 102  
126 124 118 106  
126 124 118 106  
107  
93  
78  
63  
98  
49  
83  
105  
91  
76  
61  
97  
141 127 112  
137 137 135 121 106  
137 137 137 123 108  
139 126 111  
129 129 129 115 100  
129 129 129 115 100  
113  
96  
80  
63  
98  
47  
82  
111  
94  
77  
61  
97  
44  
80  
94  
94  
42  
78  
88  
88  
142 131 115  
136 136 135 118 102  
136 136 136 119 103  
119 100  
144 136 117  
137 130 113  
127 127 127 111  
127 127 127 111  
82  
63  
99  
44  
80  
97  
97  
116  
97  
79  
60  
97  
43  
60  
60  
135 134 115  
125 125 125 107  
126 126 126 107  
41  
51  
51  
134 134 134 116  
135 135 135 116  
Temperature of Air on Condenser Coil 125°F  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
131  
124  
114  
114  
136  
128  
117  
118  
140  
132  
121  
121  
137  
129  
119  
119  
134  
127  
117  
117  
18.3  
17.8  
17.5  
17.6  
18.4  
18.0  
17.6  
17.8  
18.6  
18.2  
17.8  
18.0  
18.7  
18.2  
17.9  
18.0  
18.8  
18.3  
18.0  
18.1  
81  
71  
60  
90  
49  
79  
89  
87  
54  
88  
99  
97  
60  
96  
39  
68  
78  
77  
42  
75  
86  
85  
45  
81  
94  
92  
42  
79  
87  
86  
39  
76  
79  
79  
28  
58  
68  
66  
29  
62  
74  
72  
30  
67  
80  
78  
25  
62  
70  
69  
20  
58  
61  
61  
17  
47  
57  
55  
17  
50  
61  
59  
16  
52  
65  
63  
9
46  
53  
53  
2
39  
42  
42  
*
These capacities are gross ratings. For net  
capacity, deduct air blower motor, MBH = 3.415  
x kW. Refer to the appropriate Blower Perfor-  
mance Table for the kW of the supply air  
blower motor.  
These ratings include condenser fan motors  
and the compressor motors but not the supply  
air blower motor.  
111 100  
114 110 100  
3750  
4375  
5000  
5625  
6250  
114 109  
92 80  
124 113 100  
117 116 112  
118 115 110  
98  
67  
103  
89  
74  
132 125 111  
121 121 121 109  
121 121 121 107  
108  
92  
75  
58  
95  
129 129 112  
119 119 119 103  
119 119 119 102  
113  
95  
76  
57  
95  
98  
98  
127 127 113  
117 117 117  
117 117 117  
Johnson Controls Unitary Products  
17  
 
246645-YTG-C-0708  
TABLE 10: ELECTRICAL DATA DM078 (6-1/2 TON) STD EFFICIENCY W/O PWRD CONVENIENCE OUTLET  
MCA  
Max  
Fuse*  
Size  
Max Fuse* Size  
w/Power  
Supply  
Blower  
Pwr  
Pwr  
Min. Circuit  
Ampacity  
(Amps)  
OD Fan  
Motors  
w/Power  
Exhaust  
(Amps)  
Compressors  
Exh Conv  
Electric Heater Actual Heater  
Exhaust  
Voltage  
Motor FLA Motor Outlet  
Model No.  
KW Amps  
(Amps)  
(Amps)  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
1.5  
HP  
2
HP  
1.5  
HP  
2
HP  
1.5  
HP  
2
1.5  
2
1.5  
HP  
50  
50  
70  
80  
2
HP  
50  
50  
70  
80  
110  
50  
50  
80  
90  
125  
30  
30  
35  
45  
60  
20  
20  
30  
40  
50  
FLA FLA  
HP HP HP  
None  
--  
6.8  
13.5  
18  
25.5  
--  
--  
38.0  
38.0  
54.6  
70.2  
96.2  
38.0  
38.0  
61.9  
79.9  
40.0 43.5 45.5 50 50  
40.0 43.5 45.5 50 50  
57.1 61.5 64.0 60 60  
72.7 77.1 79.6 80 80  
2TP04520925  
2TP04521825  
2TP04522425  
2TP04523625  
None  
18.9  
37.5  
50.0  
70.8  
--  
208  
230  
460  
12.8 110.0  
1.5  
1.5  
0.8  
0.6  
6.2  
6.2  
3.1  
2.4  
8.2  
8.2  
4.1  
3.6  
5.5  
5.5  
2.2  
1.8  
0.0  
0.0  
0.0  
0.0  
98.7 103.1 105.6 100 100 110  
40.0 43.5 45.5 50 50  
40.0 43.5 45.5 50 50  
64.4 68.8 71.3 70 70  
82.4 86.8 89.3 80 90  
50  
50  
70  
90  
2TP04520925  
2TP04521825  
2TP04522425  
2TP04523625  
None  
2TP04520946  
2TP04521846  
2TP04522446  
2TP04523646  
None  
2TP04520958  
2TP04521858  
2TP04522458  
2TP04523658  
9
21.7  
43.3  
57.7  
12.8 110.0  
18  
24  
34  
--  
81.8 110.0 112.5 116.9 119.4 110 125 125  
--  
20.7  
20.7  
30.9  
40  
21.7 22.9 23.9 25 25  
21.7 22.9 23.9 25 25  
32.2 33.7 34.9 35 35  
41.2 42.7  
56.2 57.7  
16.3 16.9 18.1 20 20  
16.3 16.9 18.1 20 20  
26.2 26.9 28.4 25 30  
33.4 34.1 35.6 35 35  
45.4 46.1 47.6 45 50  
25  
25  
35  
45  
60  
20  
20  
30  
35  
50  
9
11.3  
22.6  
30.1  
42.7  
--  
7.1  
5.1  
54.0  
44.0  
18  
24  
34  
--  
44  
59  
40 45  
60 60  
55  
15.1  
15.1  
24.7  
31.9  
43.9  
9
9.0  
575  
18  
24  
34  
18.1  
24.1  
34.1  
*
Maximum HACR breaker of the same AMP size is applicable.  
TABLE 11: ELECTRICAL DATA DM078 (6-1/2 TON) STD EFFICIENCY WITH PWRD CONVENIENCE OUTLET  
MCA  
Max  
Fuse*  
Size  
Max Fuse* Size  
w/Power  
Supply  
Blower  
Pwr  
Pwr  
Min. Circuit  
Ampacity  
(Amps)  
OD Fan  
Motors  
w/Power  
Exhaust  
(Amps)  
Compressors  
Exh Conv  
Electric Heater Actual Heater  
Exhaust  
Voltage  
Motor FLA Motor Outlet  
Model No.  
KW Amps  
(Amps)  
(Amps)  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
1.5  
HP  
2
HP  
1.5  
HP  
2
HP  
1.5  
HP  
2
1.5  
2
1.5  
HP  
60  
60  
80  
90  
2
HP  
60  
60  
80  
100  
125  
60  
FLA FLA  
HP HP HP  
None  
--  
6.8  
13.5  
18  
25.5  
--  
--  
48.0  
48.0  
67.1  
82.7  
50.0 53.5 55.5 60 60  
50.0 53.5 55.5 60 60  
69.6 74.0 76.5 70 70  
85.2 89.6 92.1 90 90  
2TP04520925  
2TP04521825  
2TP04522425  
2TP04523625  
None  
18.9  
37.5  
50.0  
208  
230  
460  
12.8 110.0  
1.5  
1.5  
0.8  
0.6  
6.2  
6.2  
3.1  
2.4  
8.2  
8.2  
4.1  
3.6  
5.5  
5.5  
2.2  
1.8  
10.0  
10.0  
5.0  
70.8 108.7 111.2 115.6 118.1 110 125 125  
--  
48.0  
48.0  
74.4  
92.4  
50.0 53.5 55.5 60 60  
50.0 54.2 56.7 60 60  
76.9 81.3 83.8 80 80  
60  
60  
90  
2TP04520925  
2TP04521825  
2TP04522425  
2TP04523625  
None  
2TP04520946  
2TP04521846  
2TP04522446  
2TP04523646  
None  
2TP04520958  
2TP04521858  
2TP04522458  
2TP04523658  
9
21.7  
43.3  
57.7  
60  
90  
12.8 110.0  
18  
24  
34  
--  
94.9 99.3 101.8 100 100 100  
110  
150  
35  
81.8 122.5 125.0 129.4 131.9 125 125 150  
--  
25.7  
25.7  
37.2  
46.2  
61.2  
19.1  
19.1  
29.7  
36.9  
48.9  
26.7 27.9 28.9 30 30  
26.7 27.9 28.9 30 30  
38.4 39.9 41.2 40 40  
30  
30  
40  
50  
70  
25  
25  
35  
40  
60  
9
11.3  
22.6  
30.1  
42.7  
--  
35  
7.1  
5.1  
54.0  
44.0  
18  
24  
34  
--  
45  
47.5  
62.5  
49  
64  
50.2 50 50  
65.2 70 70  
60  
70  
20.3 20.9 22.1 20 25  
20.3 21.1 22.6 20 25  
31.2 31.9 33.4 30 35  
38.4 39.1 40.6 40 40  
50.4 51.1 52.6 50 60  
25  
9
9.0  
25  
575  
4.0  
18  
24  
34  
18.1  
24.1  
34.1  
35  
45  
60  
*
Maximum HACR breaker of the same AMP size is applicable.  
18  
Johnson Controls Unitary Products  
   
246645-YTG-C-0708  
TABLE 12: ELECTRICAL DATA - DM090 (7-1/2 TON) STANDARD EFFICIENCY W/O PWRD CONV. OUTLET  
Supply  
Blower Motor  
FLA  
Pwr  
Conv  
Outlet  
Max Fuse Size  
w/Power Exhaust  
(Amps)  
OD Fan  
Motors  
Pwr Exh  
Motor  
Min. Circuit  
MCA w/Power  
Max Fuse*  
Compressors  
Ampacity (Amps) Exhaust (Amps) Size (Amps)  
Electric Heater  
Model No.  
Actual  
KW  
Heater  
Amps  
Voltage  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
2 HP 3 HP  
FLA  
FLA  
2 HP  
3 HP  
2 HP  
3 HP  
2 HP 3 HP 2 HP  
3 HP  
None  
--  
--  
41.1  
41.1  
57.1  
72.7  
98.7  
43.8  
43.8  
60.5  
76.1  
102.1  
46.6  
46.6  
64.0  
79.6  
105.6  
49.3  
49.3  
67.3  
83.0  
109.0  
50  
50  
60  
80  
50  
50  
70  
80  
50  
50  
60  
60  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
6.8  
18.9  
37.5  
50.0  
70.8  
208  
230  
460  
575  
11.5  
11.5  
6.4  
84.0  
84.0  
42.0  
34.0  
3.5  
3.5  
1.6  
1.3  
8.2  
8.2  
4.1  
3.6  
10.9  
10.9  
5.3  
5.5  
0.0  
13.5  
18.0  
25.5  
70  
70  
80  
110  
90  
110  
100 110  
None  
--  
--  
41.1  
41.1  
64.4  
82.4  
112.5  
43.8  
43.8  
67.8  
85.8  
115.9  
46.6  
46.6  
71.3  
89.3  
119.4  
49.3  
49.3  
74.6  
92.7  
122.7  
50  
50  
70  
90  
50  
50  
70  
90  
50  
50  
60  
60  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
9.0  
21.7  
43.3  
57.7  
81.8  
5.5  
2.2  
1.8  
0.0  
0.0  
0.0  
18.0  
24.0  
34.0  
80  
80  
90  
125  
100  
125  
125 125  
None  
--  
--  
21.7  
21.7  
32.2  
41.2  
56.2  
22.9  
22.9  
33.7  
42.7  
57.7  
23.9  
23.9  
34.9  
44  
25.1  
25.1  
36.4  
45.5  
60.5  
25  
25  
35  
45  
60  
25  
25  
35  
45  
60  
30  
30  
35  
45  
60  
30  
30  
40  
50  
70  
2TP04540946  
2TP04541846  
2TP04542446  
2TP04543646  
9
11.3  
22.6  
30.1  
42.7  
18  
24  
34  
59  
None  
--  
--  
17.7  
17.7  
26.2  
33.4  
45.4  
18.2  
18.2  
26.8  
34  
19.5  
19.5  
28.4  
35.6  
47.6  
20  
20  
20  
20  
30  
35  
50  
20  
20  
30  
35  
50  
20  
20  
30  
40  
50  
25  
25  
30  
40  
50  
2TP04540958  
2TP04541858  
2TP04542458  
2TP04543658  
9
9.0  
5.1  
4.1  
18  
24  
34  
18.1  
24.1  
34.1  
29  
36.2  
48.3  
46  
TABLE 13: ELECTRICAL DATA - DM090 (7-1/2 TON) STANDARD EFFICIENCY W/PWRD CONV. OUTLET  
Supply  
Blower Motor  
FLA  
Pwr  
Conv  
Outlet  
Max Fuse Size  
w/Power Exhaust  
(Amps)  
OD Fan  
Motors  
Pwr Exh  
Motor  
Min. Circuit  
MCA w/Power  
Max Fuse*  
Compressors  
Ampacity (Amps) Exhaust (Amps) Size (Amps)  
Electric Heater  
Model No.  
Actual  
KW  
Heater  
Amps  
Voltage  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
2 HP 3 HP  
FLA  
FLA  
2 HP  
3 HP  
2 HP  
3 HP  
2 HP 3 HP 2 HP  
3 HP  
None  
--  
--  
51.1  
51.1  
69.6  
85.2  
111.2  
53.8  
53.8  
73.0  
88.6  
114.6  
56.6  
56.6  
76.5  
92.1  
118.1  
59.3  
59.3  
79.8  
95.5  
121.5  
60  
60  
70  
90  
60  
60  
80  
90  
60  
60  
70  
70  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
6.8  
18.9  
37.5  
50.0  
70.8  
208  
230  
460  
575  
11.5  
11.5  
6.4  
84.0  
84.0  
42.0  
34.0  
3.5  
3.5  
1.6  
1.3  
8.2  
8.2  
4.1  
3.6  
10.9  
10.9  
5.3  
5.5  
10.0  
13.5  
18.0  
25.5  
80  
80  
100  
125  
100  
125  
125 125  
None  
--  
--  
51.1  
51.1  
76.9  
94.9  
125.0  
53.8  
53.8  
80.3  
98.3  
128.4  
56.6  
56.7  
59.3  
60.1  
60  
60  
80  
60  
60  
90  
60  
60  
70  
70  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
9.0  
21.7  
43.3  
57.7  
81.8  
5.5  
2.2  
1.8  
10.0  
5.0  
18.0  
24.0  
34.0  
83.8  
87.1  
90  
90  
101.8  
131.9  
105.2  
135.2  
100 100  
125 150  
110  
150  
110  
150  
None  
--  
--  
26.7  
26.7  
38.4  
47.5  
62.5  
27.9  
27.9  
39.9  
49  
28.9  
28.9  
41.2  
50.2  
65.2  
30.1  
30.1  
42.7  
51.7  
66.7  
30  
30  
40  
50  
70  
30  
30  
40  
50  
70  
35  
35  
45  
60  
70  
35  
35  
45  
60  
70  
2TP04540946  
2TP04541846  
2TP04542446  
2TP04543646  
9
11.3  
22.6  
30.1  
42.7  
18  
24  
34  
64  
None  
--  
--  
21.7  
21.7  
31.2  
38.4  
50.4  
22.2  
22.2  
31.8  
39  
23.5  
23.5  
33.4  
40.6  
52.6  
24  
24  
25  
25  
35  
40  
60  
25  
25  
35  
40  
60  
25  
25  
35  
45  
60  
25  
25  
35  
45  
60  
2TP04540958  
2TP04541858  
2TP04542458  
2TP04543658  
9
9.0  
5.1  
4.1  
4.0  
18  
24  
34  
18.1  
24.1  
34.1  
34  
41.2  
53.3  
51  
Johnson Controls Unitary Products  
19  
   
246645-YTG-C-0708  
TABLE 14: ELECTRICAL DATA DM102 (8-1/2 TON) STD EFFICIENCY W/O PWRD CONVENIENCE OUTLET  
Max Fuse Size  
Pwr  
Conv  
Outlet  
Min. Circuit MCA w/Power  
OD Fan Supply Blower Pwr Exh  
Max Fuse*  
Size (Amps)  
w/Power  
Exhaust  
(Amps)  
Compressors  
Ampacity  
(Amps)  
Exhaust  
(Amps)  
Motors  
Motor FLA  
Motor  
Electric Heater Actual Heater  
Voltage  
Model No.  
KW  
Amps  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
3 HP  
3 HP  
FLA  
FLA  
3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP  
None  
--  
6.8  
13.5  
18  
25.5  
--  
--  
44.2  
44.2  
60.5  
76.1  
44.2  
44.2  
60.5  
76.1  
49.7  
49.7  
67.3  
83.0  
49.7  
49.7  
67.3  
83.0  
50  
50  
70  
80  
110  
50  
50  
70  
90  
125  
25  
25  
35  
45  
60  
20  
20  
30  
35  
50  
50  
50  
70  
80  
110  
50  
50  
70  
90  
125  
25  
25  
35  
45  
60  
20  
20  
30  
35  
50  
60  
60  
70  
90  
110  
60  
60  
80  
100  
125  
30  
30  
40  
50  
70  
25  
25  
30  
40  
50  
60  
60  
70  
90  
110  
60  
60  
80  
100  
125  
30  
30  
40  
50  
70  
25  
25  
30  
40  
50  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
None  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
None  
2TP04540946  
2TP04541846  
2TP04542446  
2TP04543646  
None  
2TP04540958  
2TP04541858  
2TP04542458  
2TP04543658  
18.9  
37.5  
50.0  
70.8  
--  
21.7  
43.3  
57.7  
81.8  
--  
11.3  
22.6  
30.1  
42.7  
--  
208  
230  
460  
575  
11.7  
11.7  
6.4  
88.0  
88.0  
42.0  
36.0  
3.5  
3.5  
1.6  
1.3  
10.9  
10.9  
5.3  
10.9  
5.5  
5.5  
2.2  
1.8  
0.0  
102.1 102.1 109.0 109.0  
44.2  
44.2  
67.8  
85.8  
44.2  
44.2  
67.8  
85.8  
50.4  
50.4  
74.6  
92.7  
50.4  
50.4  
74.6  
92.7  
9
10.9  
5.3  
0.0  
0.0  
0.0  
18  
24  
34  
--  
115.9 115.9 122.7 122.7  
22.9  
22.9  
33.7  
42.7  
57.7  
18.2  
18.2  
26.8  
34  
22.9  
22.9  
33.7  
42.7  
57.7  
18.2  
18.2  
26.8  
34  
25.1  
25.1  
36.4  
45.5  
60.5  
20  
20  
29  
36.2  
48.3  
25.1  
25.1  
36.4  
45.5  
60.5  
20  
20  
29  
36.2  
48.3  
9
18  
24  
34  
--  
9
9.0  
5.1  
4.1  
4.1  
18  
24  
34  
18.1  
24.1  
34.1  
46  
46  
TABLE 15: ELECTRICAL DATA DM102 (8-1/2 TON) STD EFFICIENCY WITH PWRD CONVENIENCE OUTLET  
Max Fuse Size  
Pwr  
Conv  
Outlet  
Min. Circuit MCA w/Power  
OD Fan Supply Blower Pwr Exh  
Max Fuse*  
Size (Amps)  
w/Power  
Exhaust  
(Amps)  
Compressors  
Ampacity  
(Amps)  
Exhaust  
(Amps)  
Motors  
Motor FLA  
Motor  
Electric Heater Actual Heater  
Voltage  
Model No.  
KW  
Amps  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
3 HP  
3 HP  
FLA  
FLA  
3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP  
None  
--  
--  
54.2  
54.2  
73.0  
88.6  
54.2  
54.2  
73.0  
88.6  
59.7  
59.7  
79.8  
95.5  
59.7  
59.7  
79.8  
95.5  
60  
60  
60  
60  
70  
70  
70  
70  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
6.8  
18.9  
37.5  
50.0  
70.8  
208  
230  
460  
575  
11.7  
11.7  
6.4  
88.0  
88.0  
42.0  
36.0  
3.5  
3.5  
1.6  
1.3  
10.9  
10.9  
5.3  
10.9  
5.5  
5.5  
2.2  
1.8  
10.0  
13.5  
18  
25.5  
80  
80  
80  
80  
90  
125  
90  
125  
100  
125  
100  
125  
114.6 114.6 121.5 121.5  
None  
--  
9
--  
54.2  
54.2  
80.3  
98.3  
54.2  
54.2  
80.3  
59.7  
59.7  
87.1  
59.7  
59.7  
87.1  
60  
60  
60  
60  
70  
70  
70  
70  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
21.7  
43.3  
57.7  
81.8  
10.9  
5.3  
10.0  
10.0  
10.0  
18  
24  
34  
90  
90  
90  
90  
98.3 105.2 105.2  
100  
150  
100  
150  
110  
150  
110  
150  
128.4 128.4 135.2 135.2  
None  
--  
--  
27.9  
27.9  
39.9  
49  
27.9  
27.9  
39.9  
49  
30.1  
30.1  
42.7  
51.7  
66.7  
30.1  
30.1  
42.7  
51.7  
66.7  
30  
30  
40  
50  
70  
30  
30  
40  
50  
70  
35  
35  
45  
60  
70  
35  
35  
45  
60  
70  
2TP04540946  
2TP04541846  
2TP04542446  
2TP04543646  
9
11.3  
22.6  
30.1  
42.7  
18  
24  
34  
64  
64  
None  
--  
--  
22.2  
22.2  
31.8  
39  
22.2  
22.2  
31.8  
39  
24  
24  
24  
24  
25  
25  
35  
40  
60  
25  
25  
35  
40  
60  
25  
25  
35  
45  
60  
25  
25  
35  
45  
60  
2TP04540958  
2TP04541858  
2TP04542458  
2TP04543658  
9
9.0  
5.1  
4.1  
4.1  
18  
24  
34  
18.1  
24.1  
34.1  
34  
34  
41.2  
53.3  
41.2  
53.3  
51  
51  
20  
Johnson Controls Unitary Products  
   
246645-YTG-C-0708  
TABLE 16: ELECTRICAL DATA DM120 (10 TON) STD EFFICIENCY W/O PWRD CONVENIENCE OUTLET  
MCA  
Max  
Fuse*  
Size  
Max Fuse* Size  
w/Power  
Supply  
Blower  
Pwr  
Pwr  
Min. Circuit  
Ampacity  
(Amps)  
OD Fan  
Motors  
w/Power  
Exhaust  
(Amps)  
Compressors  
Exh Conv  
Electric Heater Actual Heater  
Exhaust  
Voltage  
Motor FLA Motor Outlet  
Model No.  
KW  
Amps  
(Amps)  
(Amps)  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
2
HP  
3
HP  
2
HP  
3
HP  
2
3
2
3
2
HP  
70  
3
HP  
70  
70  
90  
FLA  
FLA  
HP  
HP  
HP HP  
None  
--  
13.5  
18  
25.5  
40.6  
--  
--  
51.9  
57.1  
72.7  
54.6 57.4 60.1 60 70  
60.5 64.0 67.3 60 70  
76.1 79.6 83.0 80 80  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
37.5  
50.0  
70.8  
70  
208  
230  
460  
16.3 150.0  
3.5  
3.5  
1.6  
1.3  
8.2 10.9  
8.2 10.9  
5.5  
0.0  
80  
98.7 102.1 105.6 109.0 100 110  
112.7 151.1 154.5 158.0 161.4 175 175  
110  
175  
70  
110  
175  
70  
--  
51.9  
64.4  
82.4  
54.6 57.4 60.1 60 70  
67.8 71.3 74.6 70 70  
85.8 89.3 92.7 90 90  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
2TP04521846  
2TP04522446  
2TP04523646  
2TP04525446  
None  
18  
24  
34  
54  
--  
18  
24  
34  
54  
--  
43.3  
57.7  
80  
80  
16.3 150.0  
5.5  
2.2  
1.8  
0.0  
0.0  
0.0  
90  
100  
125  
175  
45  
81.8 112.5 115.9 119.4 122.7 125 125  
129.9 140.2 143.5 147.0 150.4 150 175  
125  
175  
45  
--  
33.2  
33.2  
41.2  
56.2  
70.1  
22.2  
26.2  
33.4  
45.4  
56.5  
34.4 35.4 36.6 40 45  
34.4 35.4 36.6 40 45  
22.6  
30.1  
42.7  
67.8  
--  
45  
45  
11.5  
7.1  
75.0  
62.0  
4.1  
3.6  
5.3  
4.1  
42.7  
57.7  
44  
59  
45.5 45 45  
60.5 60 60  
45  
50  
60  
70  
71.6 72.8 74.3 80 80  
22.7 24 24.5 25 25  
26.8 28.4 29 30 30  
35.6 36.2 35 35  
47.6 48.3 50 50  
57.1 58.7 59.3 70 70  
80  
80  
30  
30  
2TP04521858  
2TP04522458  
2TP04523658  
2TP04525458  
18  
24  
34  
54  
18.1  
24.1  
34.1  
54.2  
30  
30  
575  
34  
46  
40  
40  
50  
50  
70  
70  
*
Maximum HACR breaker of the same AMP size is applicable.  
TABLE 17: ELECTRICAL DATA DM120 (10 TON) STD EFFICIENCY WITH PWRD CONVENIENCE OUTLET  
MCA  
Max  
Fuse*  
Size  
Max Fuse* Size  
w/Power  
Supply  
Blower  
Pwr  
Pwr  
Min. Circuit  
Ampacity  
(Amps)  
OD Fan  
Motors  
w/Power  
Exhaust  
(Amps)  
Compressors  
Exh Conv  
Electric Heater Actual Heater  
Exhaust  
Voltage  
Motor FLA Motor Outlet  
Model No.  
KW  
Amps  
(Amps)  
(Amps)  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
2
HP  
3
HP  
2
HP  
3
HP  
2
3
2
3
2
3
FLA  
FLA  
HP  
HP  
HP HP  
HP  
80  
HP  
80  
None  
--  
13.5  
18  
25.5  
40.6  
--  
--  
37.5  
50.0  
61.9  
69.6  
85.2  
64.6 67.4 70.1 70 80  
73.0 76.5 79.8 70 80  
88.6 92.1 95.5 90 90  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
80  
80  
208  
230  
460  
16.3 150.0  
3.5  
3.5  
1.6  
1.3  
8.2 10.9  
8.2 10.9  
5.5  
10.0  
100  
125  
175  
80  
100  
125  
175  
80  
70.8 111.2 114.6 118.1 121.5 125 125  
112.7 163.6 167.0 170.5 173.9 175 175  
--  
61.9  
76.9  
94.9  
64.6 67.4 70.1 70 80  
80.3 83.8 87.1 80 90  
98.3 101.8 105.2 100 100  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
2TP04521846  
2TP04522446  
2TP04523646  
2TP04525446  
None  
18  
24  
34  
54  
--  
18  
24  
34  
54  
--  
43.3  
57.7  
90  
90  
16.3 150.0  
5.5  
2.2  
1.8  
10.0  
5.0  
110  
150  
175  
50  
110  
150  
175  
50  
81.8 125.0 128.4 131.9 135.2 125 150  
129.9 152.7 156.0 159.5 162.9 175 175  
--  
38.2  
38.4  
47.5  
62.5  
76.3  
26.2  
31.2  
38.4  
50.4  
61.5  
39.4 40.4 41.6 45 50  
39.9 41.2 42.7 45 50  
50.2 51.7 50 50  
65.2 66.7 70 70  
77.8 79.1 80.6 90 90  
26.7 28 28.5 30 30  
31.8 33.4 34 35 35  
40.6 41.2 40 40  
52.6 53.3 60 60  
62.1 63.7 64.3 70 70  
22.6  
30.1  
42.7  
67.8  
--  
50  
50  
11.5  
7.1  
75.0  
62.0  
4.1  
3.6  
5.3  
4.1  
49  
64  
60  
60  
70  
70  
90  
90  
35  
35  
2TP04521858  
2TP04522458  
2TP04523658  
2TP04525458  
18  
24  
34  
54  
18.1  
24.1  
34.1  
54.2  
35  
35  
575  
4.0  
39  
51  
45  
45  
60  
60  
70  
70  
*
Maximum HACR breaker of the same AMP size is applicable.  
Johnson Controls Unitary Products  
21  
   
246645-YTG-C-0708  
TABLE 18: ELECTRICAL DATA DM150 (12-1/2 TON) STD EFFICIENCY W/O PWRD CONVENIENCE OUTLET  
MCA  
Max  
Fuse*  
Size  
Max  
Fuse  
Size  
Supply  
Blower  
Pwr  
Pwr  
Min. Circuit  
Ampacity  
(Amps)  
OD Fan  
Motors  
w/Power  
Exhaust  
(Amps)  
Compressors  
Exh Conv  
Electric Heater Actual Heater  
Voltage  
Motor FLA Motor Outlet  
Model No.  
KW  
Amps  
(Amps) w/Power  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
3
5
HP  
3
5
HP  
3
5
3
5
3
5
FLA  
FLA  
HP  
HP  
HP  
HP HP HP HP HP  
None  
--  
13.5  
18  
25.5  
40.6  
--  
18  
24  
34  
54  
--  
18  
24  
34  
54  
--  
18  
24  
34  
54  
--  
37.5  
50.0  
62.9 68.1 68.4 73.6 80 80 80 90  
62.9 68.1 68.4 73.8 80 80 80 90  
76.1 82.6 83.0 89.5 80 90 90 90  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
208  
230  
460  
20.0 146.0  
3.5  
3.5  
1.6  
1.3  
10.9 16.1  
10.9 16.1  
5.5  
0.0  
70.8 102.1 108.6 109.0 115.5 110 110 110 125  
112.7 154.5 161.0 161.4 167.9 175 175 175 175  
--  
43.3  
57.7  
81.8 115.9 122.4 122.7 129.2 125 125 125 150  
129.9 143.5 150.0 150.4 156.9 175 175 175 175  
--  
22.6  
30.1  
42.7  
67.8  
--  
18.1  
24.1  
34.1  
54.2  
62.9 68.1 68.4 73.6 80 80 80 90  
67.8 74.3 74.6 81.1 80 80 80 90  
85.8 92.3 92.7 99.2 90 100 100 100  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
2TP04521846  
2TP04522446  
2TP04523646  
2TP04525446  
None  
20.0 146.0  
5.5  
2.2  
1.8  
0.0  
0.0  
0.0  
27.4 30.2 29.6 32.4 35 35 35 40  
33.7 37.2 36.4 39.9 35 40 40 40  
8.4  
6.7  
73.0  
60.0  
5.3  
4.1  
8.1  
6.0  
42.7 46.2 45.5  
57.7 61.2 60.5  
49  
64  
45 50 50 50  
60 70 70 70  
71.6 75.1 74.3 77.8 80 90 80 90  
21.8 23.7 23.6 25.5 25 30 30 30  
2TP04521858  
2TP04522458  
2TP04523658  
2TP04525458  
26.8 29.2  
29  
31.4 30 30 30 35  
575  
34  
46  
36.4 36.2 38.6 35 40 40 40  
48.4 48.3 50.6 50 50 50 60  
57.1 59.5 59.3 61.7 70 70 70 70  
*
Maximum HACR breaker of the same AMP size is applicable.  
TABLE 19: ELECTRICAL DATA DM150 (12-1/2 TON) STD EFFICIENCY W/PWRD CONVENIENCE OUTLET  
MCA  
Max  
Fuse*  
Size  
Max  
Fuse  
Size  
Supply  
Blower  
Pwr  
Pwr  
Min. Circuit  
Ampacity  
(Amps)  
OD Fan  
Motors  
w/Power  
Exhaust  
(Amps)  
Compressors  
Exh Conv  
Electric Heater Actual Heater  
Voltage  
Motor FLA Motor Outlet  
Model No.  
KW  
Amps  
(Amps) w/Power  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
3
5
HP  
3
5
HP  
3
5
3
5
3
5
FLA  
FLA  
HP  
HP  
HP  
HP HP HP HP HP  
None  
--  
13.5  
18  
25.5  
40.6  
--  
18  
24  
34  
54  
--  
18  
24  
34  
54  
--  
18  
24  
34  
54  
--  
37.5  
50.0  
72.9 78.1 78.4 83.6 90 90 90 100  
73.0 79.5 79.8 86.3 90 90 90 100  
88.6 95.1 95.5 102.0 90 100 100 110  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
208  
230  
460  
20.0 146.0  
3.5  
3.5  
1.6  
1.3  
10.9 16.1  
10.9 16.1  
5.5  
10.0  
70.8 114.6 121.1 121.5 128.0 125 125 125 150  
112.7 167.0 173.5 173.9 180.4 175 175 175 200  
--  
43.3  
57.7  
81.8 128.4 134.9 135.2 141.7 150 150 150 150  
129.9 156.0 162.5 162.9 169.4 175 175 175 175  
--  
22.6  
30.1  
42.7  
67.8  
--  
18.1  
24.1  
34.1  
54.2  
72.9 78.1 78.4 83.6 90 90 90 100  
80.3 86.8 87.1 93.6 90 90 90 100  
98.3 104.8 105.2 111.7 100 110 110 125  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
2TP04521846  
2TP04522446  
2TP04523646  
2TP04525446  
None  
20.0 146.0  
5.5  
2.2  
1.8  
10.0  
5.0  
32.4 35.2 34.6 37.4 40 40 40 45  
39.9 43.4 42.7 46.2 40 45 45 50  
8.4  
6.7  
73.0  
60.0  
5.3  
4.1  
8.1  
6.0  
49  
64  
52.5 51.7 55.2 50 60 60 60  
67.5 66.7 70.2 70 70 70 80  
77.8 81.3 80.6 84.1 90 90 90 90  
25.8 27.7 27.6 29.5 30 30 30 35  
2TP04521858  
2TP04522458  
2TP04523658  
2TP04525458  
31.8 34.2  
34  
36.4 35 35 35 40  
575  
4.0  
39  
51  
41.4 41.2 43.6 40 45 45 45  
53.4 53.3 55.6 60 60 60 60  
62.1 64.5 64.3 66.7 70 70 70 70  
*
Maximum HACR breaker of the same AMP size is applicable.  
NOTES FOR TABLE 21 THROUGH TABLE 30:  
TABLE 20: ELECTRIC HEAT MULTIPLIERS  
Blower performance includes dry coil and 2” throwaway  
filters.  
VOLTAGE  
kW Cap. Multiplier  
NOMINAL  
RATING  
208  
0.75  
0.92  
0.92  
0.92  
Blower performance for gas heat includes the maximum  
number of heat tubes available for each tonnage.  
240  
230  
480  
600  
460  
ESP (External Static Pressure) given is that available for  
the supply and return air duct system. All internal resis-  
tances have been deducted from the total static pressure  
of the blower.  
575  
NOTE: Electric heaters are rated at nominal voltage. Use  
this table to determine the electric heat capacity for  
heaters supplied at lower voltages.  
22  
Johnson Controls Unitary Products  
     
246645-YTG-C-0708  
Johnson Controls Unitary Products  
23  
 
246645-YTG-C-0708  
24  
Johnson Controls Unitary Products  
 
246645-YTG-C-0708  
Johnson Controls Unitary Products  
25  
 
246645-YTG-C-0708  
26  
Johnson Controls Unitary Products  
 
246645-YTG-C-0708  
Johnson Controls Unitary Products  
27  
 
246645-YTG-C-0708  
28  
Johnson Controls Unitary Products  
 
246645-YTG-C-0708  
Johnson Controls Unitary Products  
29  
 
246645-YTG-C-0708  
30  
Johnson Controls Unitary Products  
 
246645-YTG-C-0708  
Johnson Controls Unitary Products  
31  
 
246645-YTG-C-0708  
32  
Johnson Controls Unitary Products  
 
246645-YTG-C-0708  
TABLE 31: ADDITIONAL STATIC RESISTANCE DM078, 120 AND 150  
Electric Heat KW  
*
† ‡  
CFM  
Cooling Only  
Economizer  
9
18  
24  
36  
54  
1900  
2100  
2300  
2500  
2700  
2900  
3100  
3300  
3500  
3700  
3900  
4100  
4300  
4500  
4700  
4900  
5100  
5300  
5500  
5700  
5900  
6100  
6300  
0.06  
0.07  
0.08  
0.09  
0.11  
0.12  
0.14  
0.16  
0.18  
0.20  
0.23  
0.25  
0.28  
0.30  
0.33  
0.36  
0.39  
0.42  
0.45  
0.48  
0.52  
0.56  
0.60  
0.02  
0.02  
0.02  
0.02  
0.03  
0.03  
0.03  
0.03  
0.04  
0.04  
0.04  
0.04  
0.05  
0.05  
0.05  
0.05  
0.06  
0.06  
0.06  
0.06  
0.07  
0.07  
0.07  
0.05  
0.06  
0.07  
0.08  
0.09  
0.10  
0.12  
0.13  
0.15  
0.17  
0.19  
0.21  
0.23  
0.25  
0.28  
0.30  
0.33  
0.35  
0.38  
0.41  
0.44  
0.47  
0.50  
0.06  
0.07  
0.08  
0.09  
0.10  
0.11  
0.13  
0.14  
0.16  
0.18  
0.20  
0.22  
0.24  
0.26  
0.29  
0.31  
0.34  
0.37  
0.40  
0.43  
0.46  
0.49  
0.53  
0.07  
0.08  
0.09  
0.10  
0.12  
0.13  
0.15  
0.17  
0.19  
0.21  
0.23  
0.25  
0.28  
0.30  
0.33  
0.35  
0.38  
0.41  
0.44  
0.47  
0.50  
0.53  
0.56  
0.08  
0.09  
0.10  
0.11  
0.13  
0.14  
0.16  
0.18  
0.20  
0.22  
0.24  
0.26  
0.29  
0.31  
0.34  
0.37  
0.40  
0.43  
0.46  
0.49  
0.53  
0.56  
0.59  
0.10  
0.11  
0.13  
0.14  
0.16  
0.18  
0.20  
0.22  
0.24  
0.26  
0.28  
0.31  
0.34  
0.37  
0.40  
0.43  
0.46  
0.49  
0.53  
0.56  
0.59  
0.62  
0.65  
*
Add these resistance values to the available static resistance in the respective Blower Performance Tables.  
Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.  
The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return  
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.  
TABLE 32: ADDITIONAL STATIC RESISTANCE DM090, 102  
Electric Heat KW†  
24  
*
† ‡  
CFM  
Cooling Only  
Economizer  
9
18  
36  
54  
1900  
2100  
2300  
2500  
2700  
2900  
3100  
3300  
3500  
3700  
3900  
4100  
4300  
-0.004  
0.01  
0.01  
0.02  
0.03  
0.04  
0.05  
0.06  
0.07  
0.08  
0.09  
0.09  
0.10  
0.07  
0.09  
0.11  
0.13  
0.16  
0.18  
0.20  
0.22  
0.24  
0.27  
0.29  
0.31  
0.33  
0.05  
0.06  
0.07  
0.08  
0.09  
0.1  
0.06  
0.07  
0.08  
0.09  
0.1  
0.07  
0.08  
0.09  
0.1  
0.08  
0.09  
0.1  
0.1  
0.11  
0.13  
0.14  
0.16  
0.18  
0.2  
0.11  
0.13  
0.14  
0.16  
0.18  
0.2  
0.12  
0.13  
0.15  
0.17  
0.19  
0.21  
0.23  
0.25  
0.28  
0.11  
0.13  
0.14  
0.16  
0.18  
0.2  
0.12  
0.13  
0.15  
0.17  
0.19  
0.21  
0.23  
0.22  
0.24  
0.26  
0.28  
0.31  
0.34  
0.22  
0.24  
0.26  
0.29  
0.22  
0.24  
*
Deduct these resistance values to the available static resistance in the respective Blower Performance Tables.  
Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.  
The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return  
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.  
Johnson Controls Unitary Products  
33  
       
246645-YTG-C-0708  
TABLE 33: ELECTRIC HEAT MINIMUM SUPPLY AIR CFM  
UNIT MODEL SIZE (NOMINAL TONS)  
HEATER  
078 (6.5)  
090 (7.5)  
102 (8.5)  
120 (10)  
150 (12.5)  
VOLTAGE  
kW  
MINIMUM SUPPLY AIR CFM  
1950  
1950  
1950  
1950  
N/A  
2250  
2250  
2250  
2250  
N/A  
2550  
2550  
2550  
2550  
N/A  
N/A  
3000  
3000  
3000  
3500  
N/A  
N/A  
3750  
3750  
3750  
4000  
N/A  
9
18  
24  
36  
54  
9
208/230  
1950  
1950  
1950  
1950  
N/A  
2250  
2250  
2250  
2250  
N/A  
2550  
2550  
2550  
2550  
N/A  
3000  
3000  
3000  
3000  
N/A  
3750  
3750  
3750  
3750  
N/A  
18  
24  
36  
54  
9
480  
600  
1950  
1950  
1950  
1950  
N/A  
2250  
2250  
2250  
2250  
N/A  
2550  
2550  
2550  
2550  
N/A  
3000  
3000  
3000  
3500  
3750  
3750  
3750  
3750  
18  
24  
36  
54  
TABLE 34: INDOOR BLOWER SPECIFICATIONS  
MOTOR  
RPM Eff.  
1-1/2 1725 80% 1.15  
MOTOR SHEAVE  
BLOWER SHEAVE  
MODEL  
DM078  
DM090  
DM102  
DM120  
DM150  
BELT  
HP  
SF Frame Datum Dia. (in.) Bore (in.) Model Datum Dia. (in.) Bore (in.) Model  
56  
56  
3.4 - 4.4  
3.4 - 4.4  
3.4 - 4.4  
3.4 - 4.4  
3.4 - 4.4  
3.4 - 4.4  
3.4 - 4.4  
3.4 - 4.4  
3.4 - 4.4  
4.3 - 5.3  
7/8  
7/8  
7/8  
7/8  
7/8  
7/8  
7/8  
7/8  
7/8  
1 1/8  
1VM50  
1VM50  
1VM50  
1VM50  
1VM50  
1VM50  
1VM50  
1VM50  
1VM50  
1VP56  
9.5  
7.5  
6.5  
6.0  
6.0  
5.7  
8.5  
7.0  
7.0  
6.7  
1
1
1
1
1
1
1
1
1
1
AK99  
AK79  
AK69  
AK64  
AK64  
AK61  
AK89  
AK74  
AK74  
BK77  
A58  
A55  
A49  
A49  
A49  
A49  
A56  
A54  
A54  
BX55  
2
2
3
3
3
2
3
3
5
1725 80% 1.15  
1725 80% 1.15  
1725 80% 1.15  
1725 80% 1.15  
1725 80% 1.15  
1725 80% 1.15  
1725 80% 1.15  
1725 80% 1.15  
1725 87% 1.15  
56  
56  
56  
56  
56  
56  
56  
184T  
TABLE 35: POWER EXHAUST SPECIFICATIONS  
MOTOR  
RPM*  
ELECTRICAL  
POWER EXHAUST  
FUSE  
SIZE  
CFM@  
0.1 ESP  
VOLT  
PHASE  
MODEL  
HP  
QTY  
LRA  
24.9  
FLA  
5.0  
MCA  
2PE0473225  
2PE0473246  
2PE0473258  
208/230  
460  
1
1
1
6.3  
2.8  
1.9  
10  
5
1075  
1050  
0.75  
1
2.2  
3,800  
N/A  
575  
1.5  
4
*
Motors are multi-tapped and factory wired for high speed.  
34  
Johnson Controls Unitary Products  
     
246645-YTG-C-0708  
Y
X
FRONT  
LEFT  
X
Y
Unit Model Number  
DM078  
47 1/2  
38  
25 1/2  
23  
DM090  
38  
23  
DM102  
F
R
O
N
T
47 1/2  
47 1/2  
25 1/2  
25 1/2  
DM120  
L
E
F
T
B
C
DM150  
A
FIGURE 3 - UNIT CENTER OF GRAVITY  
D
FIGURE 2 - UNIT 4 POINT LOAD  
TABLE 36: 4 POINT LOAD WEIGHT  
Location (lbs.)  
Model  
A
B
C
D
DM078  
DM090  
DM102  
DM120  
DM150  
228  
192  
195  
245  
262  
195  
143  
146  
209  
224  
285  
224  
228  
305  
327  
333  
301  
306  
357  
382  
F
R
O
N
T
L
E
F
T
D
C
B
A
E
F
FIGURE 4 - UNIT 6 POINT LOAD  
Johnson Controls Unitary Products  
35  
       
246645-YTG-C-0708  
TABLE 37: 6 POINT LOAD WEIGHT  
TABLE 38: UNIT WEIGHT  
Model  
DM078  
DM090  
DM102  
DM120  
DM150  
Shipping Weight (lbs.)  
Operating Weight (lbs.)  
Locations (lbs.)  
Model  
1046  
865  
1041  
860  
A
B
C
D
E
F
DM078  
DM090  
DM102  
DM120  
DM150  
156  
135  
137  
168  
180  
140  
110  
112  
151  
161  
127  
91  
185  
142  
145  
198  
212  
205  
172  
145  
219  
235  
228  
211  
214  
244  
262  
880  
875  
1121  
1200  
1116  
1195  
93  
136  
145  
30-11/32  
See Detail  
A
X
Control  
Entry  
Ø 7/8  
Power  
Entry  
Ø 2-1/2  
Power  
Entry  
4-1/4  
Ø 2-1/2  
11-1/2  
Convenience  
Power  
Outlet  
Entry  
For Baserail  
Dimensions  
See Detail B  
Ø 7/8  
FRONT  
17-3/16  
For Drain  
Dimensions  
See Detail C  
30-3/16  
24-3/16  
6-3/16  
59  
LEFT  
89  
27  
FIGURE 5 - UNIT DIMENSIONS  
TABLE 40: UNIT CLEARANCES  
TABLE 39: UNIT HEIGHT  
72”  
36”  
36”  
Right  
12”  
36”  
0”  
X
Top*  
Unit Model Number  
DM078  
50 3/4  
42  
Front  
Left  
DM090  
Rear†  
Bottom‡  
42  
DM102  
*
Units must be installed outdoors. Overhanging struc-  
ture or shrubs should not obstruct condenser air dis-  
charge outlet.  
50 3/4  
50 3/4  
DM120  
DM150  
To remove the slide-out drain pan, a rear clearance of  
60” is required. If space is unavailable, the drain pan  
can be removed through the front by separating the  
corner wall.  
DETAIL A  
G
a
s
P
i
p
e
I
n
l
e
t
Units may be installed on combustible floors made from  
wood or class A, B or C roof covering materials.  
5
-
1
/
4
B
P
a
a
s
n
e
1
7
-
1
3
/
1
6
V
i
e
w
o
f
W
a
l
l
A
c
r
o
s
s
f
r
o
m
C
o
i
l
36  
Johnson Controls Unitary Products  
         
246645-YTG-C-0708  
DETAIL C  
DETAIL B  
2-3/8  
5
-
3
/
8
3-3/4  
3-9/16  
R
I
G
H
T
8
0
-
5
/
8
I
N
S
U
L
A
T
E
D
D
E
C
K
U
N
D
E
R
C
O
N
D
E
N
S
E
R
S
E
C
T
I
O
N
2
0
S
U
P
P
L
Y
2
0
6
R
E
T
U
R
N
2
T
Y
P
.
3
0
I
N
S
O
U
L
A
T
E
D
D
E
C
K
U
N
D
E
R
5
0
-
1
/
2
C
M
P
R
E
S
S
O
R
S
E
C
T
I
O
N
F
R
O
N
T
8
o
r
1
4
FIGURE 6 - PREDATOR® ROOF CURB DIMENSIONS  
Johnson Controls Unitary Products  
37  
 
246645-YTG-C-0708  
2
T
Y
P
2
3
4
3
0
-
1
/
2
5
0
-
1
/
2
8
0
-
5
/
8
2
6
R
E
T
U
R
N
S
U
P
P
L
Y
1
0
7
6
-
5
/
8
5
9
-
1
/
4
9
4
F
R
O
N
T
R
I
G
H
T
6
4
-
1
/
4
FIGURE 7 - SUNLINE™ TO PREDATOR® TRANSITION ROOF CURBS  
32-11/16  
6-13/16  
Supply  
Air  
6-13/16  
6-13/16  
Return  
Air  
24  
LEFT  
27-1/2  
21  
18  
21-3/16  
19-3/16  
17-3/16  
12-5/16  
7-1/8  
FRONT  
14-23/32  
16-3/8  
Bottom  
Bottom  
Bottom  
Gas Supply Entry  
18-1/16  
19-5/8  
Condensate  
Drain  
Power, Control and  
Convenience Outlet  
Wiring Entries  
63-1/2  
FIGURE 8 - BOTTOM DUCT OPENINGS (FROM ABOVE)  
38  
Johnson Controls Unitary Products  
   
246645-YTG-C-0708  
REAR DUCT DIMENSIONS  
DIMENSION  
CABINET SIZE  
“A”  
“B”  
“C”  
50 3/4”  
42”  
28 1/4  
27 3/4  
18 1/16  
12 1/16  
28 1/4  
27 1/2  
FIGURE 9 - REAR DUCT DIMENSIONS  
58 1/4  
88 1/4  
39 1/2  
or  
47 1/2  
Outside Air  
Intake Hood  
35 3/4  
Relief Hood for  
Power Exhaust or  
Barometric Relief  
26  
25 3/4  
26  
30 1/4  
FIGURE 10 - DOWNFLOW ECONOMIZER HOOD DETAIL  
Johnson Controls Unitary Products  
39  
   
246645-YTG-C-0708  
TABLE 41: ECONOMIZER USAGE  
Application  
Cabinet Height  
Description  
Model  
Bottom Return  
Side Return  
All  
All  
Downflow economizer with barometric relief  
Horizontal economizer without barometric relief  
Slab Economizer, 42” tall cabinet  
2EE04705424  
2EE04705524*  
2EE04705624†  
2EE04705224†  
42"  
50"  
ERV or End Return  
Slab Economizer, 50” tall cabinet  
*
Barometric relief must be ordered separately and installed in duct work.  
Barometric relief or fresh air hood not included. Must be ordered separately.  
2EE04705424  
Fresh Air Hood Fresh Air Damper Return Air Damper  
Barometric Relief Damper  
2EE04705424  
2EE04705424  
2EE04705424  
2EE04705424  
Barometric Relief Hood  
FIGURE 11 - FACTORY INSTALLED DOWNFLOW ECONOMIZER  
2EE04705424  
Fresh Air Hood  
2EE04705424  
2EE04705424  
2PE047032XX  
Power Exhaust  
Fresh Air Damper Return Air Damper  
2EE04705424  
Barometric Relief Damper  
2EE04705424  
Barometric Relief Hood  
FIGURE 12 - FIELD INSTALLED DOWNFLOW ECONOMIZER W/POWER EXHAUST  
40  
Johnson Controls Unitary Products  
       
246645-YTG-C-0708  
2EE04705524  
Return Air Damper  
Field Installed  
Duct Work  
2EE04705524  
Fresh Air Damper  
2PE047032XX  
Power Exhaust  
1EH0408  
Barometric  
Relief Damper  
1EH0408  
Barometric  
Relief Hood  
2EE04705524  
Fresh Air Hood  
FIGURE 13 - FIELD INSTALLED HORIZONTAL ECONOMIZER W/POWER EXHAUST  
1EH0409  
Fresh Air Hood  
2EE04705X24  
Slab Economizer  
2PE047032XX  
Power Exhaust  
1EH0409 Barometric  
Relief Damper  
1EH0409 Barometric  
Relief Hood  
FIGURE 14 - SLAB ECONOMIZER DOWNFLOW W/POWER EXHAUST  
Johnson Controls Unitary Products  
41  
   
246645-YTG-C-0708  
1EH0409  
Fresh Air Hood  
Field Installed  
Duct Work  
2EE04705X24  
Slab Economizer  
1EH0409  
Barometric Relief Hood  
2PE047032XX  
Power Exhaust  
1EH0409  
Barometric Relief Damper  
FIGURE 15 - SLAB ECONOMIZER END RETURN W/POWER EXHAUST  
42  
Johnson Controls Unitary Products  
 
246645-YTG-C-0708  
FIGURE 16 - COOLING UNIT WITH GAS HEAT WIRING 230 VOLT DIAGRAM  
Johnson Controls Unitary Products  
43  
 
246645-YTG-C-0708  
FIGURE 17 - COOLING UNIT WITH/WITHOUT ELECTRIC HEAT WIRING DIAGRAM  
44  
Johnson Controls Unitary Products  
 
246645-YTG-C-0708  
FIGURE 18 - COOLING UNIT WITH GAS HEAT WIRING 460, 575 VOLT AND 50 HZ DIAGRAM  
Johnson Controls Unitary Products  
45  
 
246645-YTG-C-0708  
GUIDE SPECIFICATIONS  
PREDATOR®  
DM 078, 090, 102, 120 & 150  
9.0 EER  
GENERAL  
Units shall be manufactured by York International Unitary  
Products Group in an ISO 9001 certified facility. YORK® Pred-  
ator® units are convertible single packages with a common  
footprint cabinet and common roof curb for all 6-1/2 through  
12-1/2 ton models. All units have two compressors with inde-  
pendent refrigeration circuits to provide 2 stages of cooling.  
The units were designed for light commercial applications  
and can be easily installed on a roof curb, slab, or frame. All  
Predator® units are self-contained and assembled on rigid full  
perimeter base rails allowing for 3-way forklift access and  
overhead rigging. Every unit is completely charged, wired,  
piped, and tested at the factory to provide a quick and easy  
field installation. All units are convertible between side and  
down airflow. Independent economizer designs are used on  
side and down discharge applications, as well as all tonnage  
sizes. Predator® units are available in the following configura-  
tions: cooling only, cooling with electric heat, and cooling with  
gas heat. Electric heaters are available as factory-installed  
options and field-installed accessories.  
fan performance without removing panels or creating bypass  
of the coils. Condensate pan shall be slide out design, con-  
structed of a non corrosive material, internally sloped and  
conforming to ASHRAE 62-B9 standards. Condensate con-  
nection shall be a minimum of ¾” I.D. female and be rigid  
mount connection.  
INDOOR (EVAPORATOR) FAN ASSEMBLY  
Fan shall be a belt drive assembly and include an adjustable  
pitch motor pulley. Job site selected brake horsepower shall  
not exceed the motors nameplate horsepower rating plus the  
service factor. Units shall be designed to operate within the  
service factor. Fan wheel shall be double inlet type with for-  
ward curve blades, dynamically balanced to operate  
smoothly throughout the entire range of operation. Airflow  
design shall be constant volume. Bearings shall be sealed  
and permanently lubricated for longer life and no mainte-  
nance. Entire blower assembly and motor shall be slide out  
design.  
DESCRIPTION  
OUTDOOR (CONDENSER) FAN ASSEMBLY  
The outdoor fans shall be of the direct drive type, discharge  
air vertically, have aluminum blades riveted to corrosion  
resistant steel spider brackets and shall be dynamically bal-  
anced for smooth operation. The outdoor fan motors shall  
have permanently lubricated bearings internally protected  
against overload conditions and staged independently. A  
cleaning window shall be provided on two sides of the units  
for coil cleaning.  
Units shall be factory assembled, single package, (Elec/Elec,  
Gas/Elec), designed for outdoor installation. Units shall have  
a minimum EER of 9.0. They shall have built in field convert-  
ible duct connections for down discharge supply/return or  
horizontal discharge supply/return and be available with fac-  
tory installed options or field installed accessories. The units  
shall be factory wired, piped and charged with R-22 refriger-  
ant and factory tested prior to shipment. All unit wiring shall  
be both numbered and color coded. The cooling performance  
shall be rated in accordance with DOE and ARI test proce-  
dures. Units shall be CSA certified to ANSI Z21.47 and UL  
1995/CAN/CSA No. 236-M90 standards.  
REFRIGERANT COMPONENTS  
Compressors:  
A. Shall be fully hermetic type, direct drive, internally pro-  
tected with internal high-pressure relief and over temper-  
ature protection. The hermetic motor shall be suction gas  
cooled and have a voltage range of + or – 10% of the  
unit nameplate voltage.  
UNIT CABINET  
Unit cabinet shall be constructed of G90 galvanized steel with  
exterior surfaces coated with a non-chalking, powder paint  
finish, certified at 1000 hours salt spray test per ASTM-B117  
standards. Indoor blower sections shall be insulated with up  
to 1” thick insulation coated on the airside. Aluminum foil  
faced insulation shall be used in the unit’s compartments and  
be fastened to prevent insulation from entering the air  
stream. Cabinet doors shall be hinged with tool-less access  
for easy servicing and maintenance. Full perimeter base rails  
shall be provided to assure reliable transit of equipment,  
overhead rigging, fork truck access and proper sealing on  
roof curb applications. Disposable 2” filters shall be furnished  
and be accessible through hinged access door. Fan perfor-  
mance measuring ports shall be provided on the outside of  
the cabinet to allow accurate air measurements of evaporator  
B. Shall have internal spring isolation and sound muffling to  
minimize vibration and noise, and be externally isolated  
on a dedicated, independent mounting.  
Coils:  
A. Evaporator and condenser coils shall have aluminum  
plate fins mechanically bonded to seamless internally  
enhanced copper tubes with all joints brazed. Special  
Phenolic coating shall be available as a factory option.  
B. Evaporator and condenser coils shall be of the direct  
expansion, draw-thru design.  
46  
Johnson Controls Unitary Products  
 
246645-YTG-C-0708  
Refrigerant Circuit and Refrigerant Safety Components shall  
include:  
shot type, constructed of aluminum-coated steel. All gas pip-  
ing shall enter the unit cabinet at a single location, through  
either the side or bottom, without any field modifications. An  
integrated control board shall provide timed control of evapo-  
rator fan functioning and burner ignition. Heating section shall  
be provided with the following minimum protection:  
A. Independent fixed-orifice or thermally operated expan-  
sion devices.  
B. Solid core filter drier/strainer to eliminate any moisture or  
foreign matter.  
A. Primary and auxiliary high-temperature limit switches.  
B. Induced draft pressure sensor.  
C. Accessible service gage connections on both suction  
and discharge lines to charge, evacuate, and measure  
refrigerant pressure during any necessary servicing or  
troubleshooting, without losing charge.  
C. Flame roll out switch (manual reset).  
D. Flame proving controls. Unit shall have two independent  
st  
nd  
D. The unit shall have two independent refrigerant circuits,  
equally split in 50% capacity increments.  
stages of capacity (60% 1 stage, 100% 2 stage).  
ELECTRIC HEATING SECTION (IF EQUIPPED)  
Unit Controls:  
An electric heating section, with nickel chromium elements,  
shall be provided in a range of 9 thru 54 KW, offering two  
states of capacity all sizes. The heating section shall have a  
primary limit control(s) (automatic reset) to prevent the heat-  
ing element system from operating at an excessive tempera-  
ture. The Heating Section assembly shall slide out of the unit  
for easy maintenance and service. Units with Electric Heating  
Sections shall be wired for a single point power supply with  
branch circuit fusing (where required).  
A. Unit shall be complete with self-contained low-voltage  
control circuit protected by a resettable circuit breaker on  
the 24-volt transformer side.  
B. Unit shall incorporate a lockout circuit which provides  
reset capability at the space thermostat or base unit  
should any of the following standard safety devices trip  
and shut off compressor:  
C. Loss-of-charge/Low-pressure switch.  
(1) High-pressure switch.  
UNIT OPERATING CHARACTERISTICS  
Unit shall be capable of starting and running at 125 ºF out-  
door temperature, exceeding maximum load criteria of ARI  
Standard 340/360. The compressor, with standard controls,  
shall be capable of operation down to 0 ºF outdoor tempera-  
ture. Unit shall be provided with fan time delay to prevent cold  
air delivery before heat exchanger warms up. (Gas heat only)  
(2) Freeze-protection thermostat, evaporator coil. If any  
of the above safety devices trip, an LED (light-emitting  
diode) indicator shall flash a diagnostic code that indi-  
cates which safety switch has tripped.  
D. Unit shall incorporate “AUTO RESET” compressor over  
temperature, over current protection.  
ELECTRICAL REQUIREMENTS - All unit power wiring shall  
enter unit cabinet at a single factory provided location and be  
capable of side or bottom entry to minimize roof penetrations  
and avoid unit field modifications. Separate side and bottom  
openings shall be provided for the control wiring.  
E. Unit shall operate with conventional thermostat designs  
and have a low voltage terminal strip for easy hook-up.  
F. Unit control board shall have on-board diagnostics and  
fault code display.  
STANDARD LIMITED WARRANTIES - Compressor – 5  
Years, Heat Exchanger – 10 Years, Elect. Heat Elem. – 5  
Years, Parts – 1 Year  
G. Standard controls shall include anti-short cycle and low  
voltage protection, and permit cooling operation down to  
0 ºF.  
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall  
be made available by either/or):  
H. Control board shall monitor each refrigerant safety  
switch independently.  
1. ELECTRONIC ENTHALPY AUTOMATIC ECONO-  
MIZER – Outdoor and return air dampers that are inter-  
locked and positioned by a fully-modulating, spring-  
return damper actuator. The maximum leakage rate for  
the outdoor air intake dampers shall not exceed 2%  
when dampers are fully closed and operating against a  
pressure differential of 0.5 IWG. A unit-mounted potenti-  
ometer shall be provided to adjust the outdoor and return  
air damper assembly to take in outdoor air to meet the  
minimum ventilation requirement of the conditioned  
space during normal operation. During economizer oper-  
ation, a mixed-air temperature control shall modulate the  
I. Control board shall retain last 5 fault codes in non-vola-  
tile memory, which will not be lost in the event of a power  
loss.  
GAS HEATING SECTION (IF EQUIPPED)  
Heat exchanger and exhaust system shall be constructed of  
aluminized steel and shall be designed with induced draft  
combustion with post purge logic, energy saving direct spark  
ignition, and redundant main gas valve. The heat exchanger  
shall be of the tubular type, constructed of T1-40 aluminized  
steel for corrosion resistance and allowing minimum mixed  
air entering temperature of 40 ºF. Burners shall be of the in-  
Johnson Controls Unitary Products  
47  
outdoor and return air damper assembly to prevent the  
supply air temperature from dropping below 55 ºF.  
Changeover from compressor to economizer operation  
shall be provided by an integral electronic enthalpy con-  
trol that feeds input into the basic module. The outdoor  
intake opening shall be covered with a rain hood that  
matches the exterior of the unit. Water eliminator/filters  
shall be provided. Simultaneous economizer/compressor  
operation is also possible. Dampers shall fully close on  
power loss. Available with barometric relief or power  
exhaust.  
COIL GUARD - Designed to prevent condenser coil  
damage.  
BAS CONTROLS - Include supply air sensor, return air  
sensor, dirty filter indicator and air proving switch.  
DIRTY FILTER SWITCH – This kit includes a differential  
pressure switch that energizes the fault light on the unit  
thermostat, indicating that there is an abnormally high-  
pressure drop across the filters.  
BREAKER – An HACR breaker can be factory installed  
on gas heat units or cooling units with electric heat.  
2. MOTORIZED OUTDOOR AIR DAMPERS – Outdoor  
and return air dampers that are interlocked and posi-  
tioned by a 2-position, spring-return damper actuator.  
The maximum leakage rate for the outdoor air intake  
dampers shall not exceed 2% when dampers are fully  
closed and operating against a pressure differential of  
0.5 IWG. A unit-mounted potentiometer shall be provided  
to adjust the outdoor and return air damper assembly to  
take in the design CFM of outdoor air to meet the ventila-  
tion requirements of the conditioned space during normal  
operation. Whenever the indoor fan motor is energized,  
the dampers open up to one of two pre-selected posi-  
tions – regardless of the outdoor air enthalpy. Dampers  
return to the fully closed position when the indoor fan  
motor is de-energized. Dampers shall fully close on  
power loss.  
DISCONNECT SWITCH - A disconnect can be factory  
installed on a cooling only units sized for the largest elec-  
tric heat available.  
STAINLESS STEEL HEAT EXCHANGER – For applica-  
tions in a corrosive environment, this option provides a  
full stainless steel heat exchanger assembly.  
STAINLESS STEEL DRAIN PAN – Provides years of  
trouble-free operation in corrosive environments.  
SMOKE DETECTOR – A smoke detector can be factory  
mounted and wired in the supply and/or return air com-  
partments.  
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE  
ROOF CURB - 14” and 8” high, full perimeter knockdown  
curb, with hinged design for quick assembly.  
ADDITIONAL FACTORY INSTALLED OPTIONS  
BAROMETRIC RELIEF DAMPER – (Unit mounted –  
Downflow, Duct Mounted – Horizontal) – Contains a rain  
hood, air inlet screen, exhaust damper and mounting  
hardware. Used to relieve internal air pressure through  
the unit during economizer operation.  
ALTERNATE INDOOR BLOWER MOTOR – For appli-  
cations with high restrictions, units are available with  
optional indoor blower motors that provide higher static  
output and/or higher airflow.  
CONVENIENCE OUTLET (POWERED/NON-POW-  
ERED) – Unit can be provided with an optional 120VAC  
GFCI outlet with cover on the corner of the unit housing  
the compressors.  
PROPANE CONVERSION KIT – Contains new orifices  
and gas valve springs to convert from natural to L.P. gas.  
–60 ºF GAS HEAT KIT – Provides an electric heat kit for  
the gas compartment for use in extreme low ambient  
conditions.  
ELECTRIC HEAT - Electric heaters range from 9 kW to  
54 kW and are available in all the voltage options of the  
base unit.  
ECONOMIZER (Downflow and Horizontal flow)  
POWER EXHAUST – (Unit mount – Downflow, Duct  
mount – Horizontal flow)  
PHASE MONITOR - Designed to prevent damage in out-  
of-phase condition.  
DUAL ENTHALPY KIT - Provides a second input to  
economizer to monitor return air.  
Subject to change without notice. Printed in U.S.A.  
246645-YTG-C-0708  
Copyright © 2008 by Johnson Controls, Inc. All rights reserved.  
Supersedes: 246645-YTG-B-0606  
Johnson Controls Unitary Products  
5005 York Drive  
Norman, OK 73069  

Lexmark 13b0503 User Manual
Multiquip Trash Pump Qp4tz User Manual
Newair Acp 1000e User Manual
Samsung Inkjet Facsimile Sf 331p User Manual
Sanyo Rs1211 User Manual
Schumacher Se 1252ma User Manual
Sony Found Not Kdl 32xbr6 User Manual
Toshiba Eo1 33057 User Manual
Trane Air Conditioner Tcont800as11aa User Manual
Xerox All In One Printer M15i User Manual