Toshiba Air Conditioner Rav Sm802krt E User Manual

FILE NO.SVM-05053-1  
SERVICE MANUAL  
HI WALL TYPE (INDOOR UNIT)  
RAV-SM562KRT-E  
RAV-SM802KRT-E  
R410A  
Rev. Mar, 2006  
1. SPECIFICATIONS  
1-1. High-Wall Type(IndoorUnit)  
Model name  
RAV-SM562KRT-E  
RAV-SM802KRT-E  
Cooling  
Heating  
Average Cooling  
Heating  
Average  
Standard capacity (Note 1)  
(kW)  
5.1  
5.6  
6.7  
8
(1.5 – 5.6)  
(1.5 – 6.3)  
(2.2 – 8.0)  
(2.2–9.0)  
Heating low temp. capacity (Note 1) (kW)  
Energy consumption effect ratio (Cooling)  
Power supply  
4.9  
5.8  
2.93 [D]  
3.29 [C]  
3.11  
2.46 [E]  
3.00 [D]  
3.24  
1 phase 230V (220 – 240V) 50Hz  
Running current  
(A)  
(kW)  
(kW)  
(%)  
8.33–7.63  
1.74  
8.138–7.46  
1.7  
13.15–12.05 12.91–11.84  
Electrical  
Power consumption  
characteristics  
2.72  
2.67  
(Low temp.)  
Power factor  
Main unit  
1.95  
2.21  
95  
95  
94  
94  
Pure white  
Appearance  
Model  
Panel color  
Height  
Width  
——  
——  
Ceiling Panel  
(Sold separately)  
(mm)  
(mm)  
(mm)  
(mm)  
(mm)  
(mm)  
(kg)  
298  
Main unit  
998  
Depth  
221  
Outer  
dimension  
Height  
Width  
——  
Ceiling panel  
——  
(Sold separately)  
Depth  
——  
Main unit  
12  
Total weight  
Ceiling panel  
——  
Heat exchanger  
Finned tubu  
Soundproof/Heat-insulating material  
Fan  
Inflammable polyethylene foam  
Turbo fan  
Foamed polyethylen  
1110  
Fan unit  
Standard air flow High (Mid./Low) (m³/h)  
840  
Motor  
(W)  
30  
Air filter  
Attached main unit  
Controller (Sold separately)  
Gas side  
Wired remote controller RBC-AMT21E  
(mm)  
(mm)  
Ø12.7 (1/2”)  
Ø15.9 (5/8”)  
Ø9.5 (3/8”)  
Connecting  
Liquid side  
pipe  
Ø6.4 (1/4”)  
41  
Drain port  
(Nominal dia.)  
(dB• A)  
25 (Polyvinyl chloride tube)  
36 45  
Sound level  
High (Mid./Low) (Note 2)  
45  
41  
36  
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based  
on the reference piping. The reference piping consists of 3 m of main piping and 2 m of branch piping connected with 0  
meter height.  
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in  
the actual operating environment become larger than the indicated values due to the effects of external sound.  
Note : Rated conditions  
Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB  
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB  
2 –  
Operation characteristic curve  
<Cooling>  
<Heating>  
14  
16  
14  
12  
10  
12  
RAV-SM802KRT-E  
RAV-SM802KRT-E  
10  
8
8
6
6
RAV-SM562KRT-E  
4
2
0
RAV-SM562KRT-E  
4
2
• Conditions  
• Conditions  
Indoor : DB27 C/WB19°C  
Outdoor : DB35°C  
Air flow : High  
Indoor : DB20°C  
Outdoor : DB7 C/WB6°C  
Air flow : High  
Pipe length : 7.5m  
230V  
Pipe length : 7.5m  
230V  
0
0
0
15 20  
40  
60 70 80  
100  
1520  
40  
60  
80 90 100  
Compressor speed (rps)  
Compressor speed (rps)  
• Capacity variation ratioaccor ding to temperature  
<Cooling>  
<Heating>  
120  
110  
100  
90  
80  
70  
60  
50  
40  
30  
20  
10  
0
105  
100  
95  
90  
85  
80  
75  
70  
65  
60  
• Conditions  
• Conditions  
Indoor : DB27 C/WB19°C  
Indoor : DB20°C  
55  
Indoor air flow : High  
Pipe length : 7.5m  
Indoor air flow : High  
Pipe length : 7.5m  
50  
-14 -12 -10 -8 -6 -4 -2  
0
2
4
6
8
10  
32 33 34 35 36 37 38 39 40 41 42 43  
Outsoor temp. (°C)  
Outsoor temp. (°C)  
3 –  
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)  
High-Wall Type  
RAV-SM562KRT-E/RAV-SM802KRT-E  
Back body  
Front panel  
998  
Air inlet  
Grille inlet  
220  
50  
Knock out system  
51  
Air outlet  
Knock out system  
75  
56  
18  
57  
Drain hose (0.54 m)  
Connection pipe (0.49 m)  
(Flare 6.35)  
Connection pipe (0.39 m)  
Wireless remote control  
(For SM802 : Flare 15.88)  
(For SM562 : Flare 12.7)  
998  
763.5  
450  
(For stud bolt 6)  
(For stud bolt 8 -10)  
20  
20  
Outline of indoor unit  
65  
Installation  
Plate outline  
100  
100  
4 –  
3. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM  
3-1. Hi Wall type  
RAV-SM562KRT-E/SM802KRT-E  
Indoor unit  
TCJ  
sensor  
Air heat exchanger  
Model  
Outer diameter of refrig erant pipe  
TC sensor  
RAV-SM  
Gas side ØA  
12.7 mm  
Liquid side ØB  
6.4 mm  
562KRT-E  
802KRT-E  
9.5 mm  
15.9 mm  
Refrigerant pipe  
at gas side  
Outer dia. ØA  
Refrigerant pipe  
at liquid side  
Outer dia. ØB  
Pd  
Packed valve  
Outer dia. ØA  
Packed valve  
Outer dia. ØB  
Ps  
Outdoor unit  
NOTE :  
The refrigerating cycle differs according to the combined outdoor units.  
For the cycle diagram, cycle pressure, etc., refer to the following Service Manual.  
RAV-SMXXX0AT-E : A03-007  
RAV-SPXXXXAT-E : A03-014  
RAV-SMXXX1AT-E : A05-001  
Cooling  
Heating  
5 –  
4. WIRING DIAGRAM  
4-1. Hi Wall type (Indoor unit)  
RAV-SM562KRT-E/SM802KRT-E  
TERMINAL  
BLOCK  
LOUVER  
MOTOR  
FAN  
MOTOR  
U3  
U4  
BLK  
5 4 3 2 1  
F
BUS  
S
EMG  
6 5 4 3 2 1  
6 5 4 3 2 1  
6 5 4 3  
6 5 4 3  
CN22  
CN50  
CN44  
(BRW)  
CN33  
(WHI)  
CN210  
(WHI)  
CN40  
(BLU)  
(WHI)  
TERMINAL  
BLOCK  
F301 FUSE  
BLK  
BLK  
3 3  
2 2  
1 1  
T3.15A 250V~  
CN41  
DC15(BLU)  
1 1  
3 3  
5 5  
DC 0VCN100  
DC12V(BRW)  
WHI  
BLK  
POWER  
SUPPLY  
CIRCUIT  
CN67  
(BLK)  
DC7V  
1 2  
1 2  
HEAT  
BLK  
BLK  
CN213(WHI)  
CN101  
(BLU)  
EXCHANGER  
SENSOR  
(TC)  
1 2 3 4 5 6 7 8  
1 2 3 4 5 6 7 8  
9
9
10  
10  
CN1(WHI)  
WIERD REMOTE  
CONTROLLER  
CN103  
(GRN)  
(MCC-1510)  
1 2 3 4 5 6 7 8  
1 2 3 4 5 6 7 8  
9
9
10  
10  
HEAT  
BLK  
BLK  
1 1  
2 2  
CN102  
(YEL)  
EXCHANGER  
SENSOR  
(TCJ)  
Control P.C board  
for indoor unit  
INFRARED RAYS RECEIVE  
AND INDICATION PARTS  
(MCC-819)  
BLK  
BLK  
1 1  
2 2  
CN104  
(WHI)  
CN61  
CN60  
(WHI)  
CN80  
(GRN)  
CN82  
(BLU)  
CN81  
THERMO  
SENSOR  
(TA)  
(YEL)  
(BLK)  
1 2 3  
1 2 3 4 5 6  
1 2 3 4 5  
PNL/EMG  
OPTION  
HA  
RED WHI BLK  
Color  
1 2 3  
1 2 3  
Identification  
Indoor unit  
earth screw  
NOTE  
BLK : BLACK  
BLU : BLUE  
RED : RED  
GRY : GRAY  
PNK : PINK  
GRN : GREEN  
WHI : WHITE  
BRW : BROWN  
ORN : ORANGE  
YEL : YELLOW  
FM : Fan motor  
TA : Indoor temp. sensor  
TC :Temp. sensor  
Outdoor unit  
earth screw  
Serial  
L N  
signal  
TCJ :Temp. sensor  
LM : Louver motor  
Single phase 220V, 50Hz  
6 –  
5. SPECIFICATIONS OF ELECTRICAL PARTS  
5-1. Indoor Unit  
High-Wall Type  
RAV-SM562KRT-E/RAV-SM802KRT-E  
No.  
Parts name  
Fan motor (for indoor)  
Type  
Specifications  
1
ICF340-30-X  
MF-340-30-X  
MP35EA12  
Output (Rated) 30 W, 220–240 V  
2
3
4
5
Grille motor  
Thermo. sensor (TA-sensor)  
Heat exchanger sensor (TC-sensor)  
Heat exchanger sensor (TCJ-sensor)  
268 mm  
10 kW at 25°C  
Ø6 mm, 400 mm  
Ø6 mm, 400 mm  
10 kW at 25°C  
7 –  
6. REFRIGERANT R410A  
This air conditioner adopts the new refrigerant HFC  
(R410A) which does not damage the ozone layer.  
(6) When an air conditioning system charged with a  
large volume of refrigerant is installed in a small  
room, it is necessary to exercise care so that,  
even when refrigerant leaks, its concentration  
does not exceed the marginal level.  
The working pressure of the new refrigerant R410A  
is 1.6 times higher than conventional refrigerant  
(R22).The refrigerating oil is also changed in  
accordance with change of refrigerant, so be careful  
that water, dust, and existing refrigerant or refrigerat-  
ing oil are not entered in the refrigerant cycle of the  
air conditioner using the new refrigerant during  
installation work or servicing time.  
If the refrigerant gas leakage occurs and its  
concentration exceeds the marginal level, an  
oxygen starvation accident may result.  
(7) Be sure to carry out installation or removal  
according to the installation manual.  
The next section describes the precautions for air  
conditioner using the new refrigerant. Conforming to  
contents of the next section together with the  
general cautions included in this manual, perform  
the correct and safe work.  
Improper installation may cause refrigeration  
trouble, water leakage, electric shock, fire, etc.  
(8) Unauthorized modifications to the air conditioner  
may be dangerous. If a breakdown occurs  
please call a qualified air conditioner technician  
or electrician.  
6-1. Safety During Installation/Servicing  
Improper repairÕs may result in water leakage,  
electric shock and fire, etc.  
As R410A's pressure is about 1.6 times higher than  
that of R22, improper installation/servicing may  
cause a serious trouble. By using tools and materi-  
als exclusive for R410A, it is necessary to carry out  
installation/servicing safely while taking the following  
precautions into consideration.  
6-2. Refrigerant Piping Installation  
6-2-1. Piping Materials and Joints Used  
For the refrigerant piping installation, copper pipes  
and joints are mainly used. Copper pipes and joints  
suitable for the refrigerant must be chosen and  
installed. Furthermore, it is necessary to use clean  
copper pipes and joints whose interior surfaces are  
less affected by contaminants.  
(1) Never use refrigerant other than R410A in an air  
conditioner which is designed to operate with  
R410A.  
If other refrigerant than R410A is mixed, pres-  
sure in the refrigeration cycle becomes abnor-  
mally high, and it may cause personal injury, etc.  
by a rupture.  
(1) Copper Pipes  
It is necessary to use seamless copper pipes  
which are made of either copper or copper alloy  
and it is desirable that the amount of residual oil  
is less than 40 mg/10 m. Do not use copper  
pipes having a collapsed, deformed or discol-  
ored portion (especially on the interior surface).  
Otherwise, the expansion valve or capillary tube  
may become blocked with contaminants.  
(2) Confirm the used refrigerant name, and use  
tools and materials exclusive for the refrigerant  
R410A.  
The refrigerant name R410A is indicated on the  
visible place of the outdoor unit of the air condi-  
tioner using R410A as refrigerant.To prevent  
mischarging, the diameter of the service port  
differs from that of R22.  
As an air conditioner using R410A incurs  
pressure higher than when using R22, it is  
necessary to choose adequate materials.  
(3) If a refrigeration gas leakage occurs during  
installation/servicing, be sure to ventilate fully.  
Thicknesses of copper pipes used with R410A  
are as shown in Table 6-2-1. Never use copper  
pipes thinner than 0.8 mm even when it is  
available on the market.  
If the refrigerant gas comes into contact with fire,  
a poisonous gas may occur.  
(4) When installing or removing an air conditioner,  
do not allow air or moisture to remain in the  
refrigeration cycle. Otherwise, pressure in the  
refrigeration cycle may become abnormally high  
so that a rupture or personal injury may be  
caused.  
(5) After completion of installation work, check to  
make sure that there is no refrigeration gas  
leakage.  
If the refrigerant gas leaks into the room, coming  
into contact with fire in the fan-driven heater,  
space heater, etc., a poisonous gas may occur.  
8 –  
Table 6-2-1 Thicknesses of annealed copper pipes  
Thickness (mm)  
Nominal diameter  
Outer diameter (mm)  
R410A  
0.80  
R22  
0.80  
0.80  
0.80  
1.00  
1/4  
3/8  
1/2  
5/8  
6.35  
9.52  
0.80  
12.70  
15.88  
0.80  
1.00  
(2) Joints  
b) Socket Joints  
For copper pipes, flare joints or socket joints are  
used. Prior to use, be sure to remove all con-  
taminants.  
Socket joints are such that they are brazed  
for connections, and used mainly for thick  
pipings whose diameter is larger than 20 mm.  
Thicknesses of socket joints are as shown in  
Table 6-2-2.  
a) Flare Joints  
Flare joints used to connect the copper pipes  
cannot be used for pipings whose outer  
diameter exceeds 20 mm. In such a case,  
socket joints can be used.  
Sizes of flare pipe ends, flare joint ends and  
flare nuts are as shown in Tables 6-2-3 to 6-  
2-6 below.  
Table 6-2-2 Minimum thicknesses of socket joints  
Reference outer diameter of  
copper pipe jointed (mm)  
Minimum joint thickness  
(mm)  
Nominal diameter  
1/4  
3/8  
1/2  
5/8  
6.35  
9.52  
0.50  
0.60  
0.70  
0.80  
12.70  
15.88  
(1) Flare Processing Procedures and Precautions  
a) Cutting the Pipe  
6-2-2. Processing of Piping Materials  
When performing the refrigerant piping installation,  
care should be taken to ensure that water or dust  
does not enter the pipe interior, that no other oil  
other than lubricating oils used in the installed air  
conditioner is used, and that refrigerant does not  
leak. When using lubricating oils in the piping  
processing, use such lubricating oils whose water  
content has been removed. When stored, be sure to  
seal the container with an airtight cap or any other  
cover.  
By means of a pipe cutter, slowly cut the pipe  
so that it is not deformed.  
b) Removing Burrs and Chips  
If the flared section has chips or burrs,  
refrigerant leakage may occur. Carefully  
remove all burrs and clean the cut surface  
before installation.  
9 –  
c) Insertion of Flare Nut  
d) Flare Processing  
Flare processing dimensions differ according  
to the type of flare tool. When using a con-  
ventional flare tool, be sure to secure "dimen-  
sion A" by using a gauge for size adjustment.  
Make certain that a clamp bar and copper  
pipe have been cleaned.  
ØD  
By means of the clamp bar, perform the flare  
processing correctly.  
A
Use either a flare tool for R410A or conven-  
tional flare tool.  
Fig. 6-2-1 Flare processing dimensions  
Table 6-2-3 Dimensions related to flare processing for R410A  
A (mm)  
Conventional flare tool  
Clutch type Wing nut type  
1.0 to 1.5 1.5 to 2.0  
Outer  
diameter  
(mm)  
Nominal  
diameter  
Thickness  
(mm)  
Flare tool for  
R410A clutch type  
1/4  
3/8  
1/2  
5/8  
6.35  
9.52  
0.8  
0.8  
0.8  
1.0  
0 to 0.5  
0 to 0.5  
0 to 0.5  
0 to 0.5  
1.0 to 1.5  
1.0 to 1.5  
1.0 to 1.5  
1.5 to 2.0  
2.0 to 2.5  
2.0 to 2.5  
12.70  
15.88  
Table 6-2-4 Dimensions related to flare processing for R22  
A (mm)  
Outer  
diameter  
(mm)  
Nominal  
diameter  
Thickness  
(mm)  
Conventional flare tool  
Flare tool for  
R22 clutch type  
Clutch type  
Wing nut type  
1.0 to 1.5  
1/4  
3/8  
1/2  
5/8  
6.35  
9.52  
0.8  
0.8  
0.8  
1.0  
0 to 0.5  
0 to 0.5  
0 to 0.5  
0 to 0.5  
0.5 to 1.0  
0.5 to 1.0  
0.5 to 1.0  
0.5 to 1.0  
1.0 to 1.5  
12.70  
15.88  
1.5 to 2.0  
1.5 to 2.0  
Table 6-2-5 Flare and flare nut dimensions for R410A  
Dimension (mm)  
Nominal  
diameter  
Outer diameter  
(mm)  
Thickness  
(mm)  
Flare nut  
width (mm)  
A
B
C
D
1/4  
3/8  
1/2  
5/8  
6.35  
9.52  
0.8  
0.8  
0.8  
1.0  
9.1  
9.2  
6.5  
13  
20  
23  
25  
17  
22  
26  
29  
13.2  
16.6  
19.7  
13.5  
16.0  
19.0  
9.7  
12.70  
15,88  
12.9  
16.0  
10 –  
Table 6-2-6 Flare and flare nut dimensions for R22  
Dimension (mm)  
Nominal  
diameter  
Outer diameter  
Thickness  
(mm)  
Flare nut width  
(mm)  
(mm)  
A
B
C
D
1/4  
3/8  
1/2  
5/8  
3/4  
6.35  
9.52  
0.8  
0.8  
0.8  
1.0  
1.0  
9.0  
9.2  
6.5  
13  
20  
20  
23  
34  
17  
22  
24  
27  
36  
13.0  
16.2  
19.4  
23.3  
13.5  
16.0  
19.0  
24.0  
9.7  
12.70  
15.88  
19.05  
12.9  
16.0  
19.2  
D
B
A
C
Fig. 6-2-2 Relations between flare nut and flare seal surface  
When it is strong, the flare nut may crack and  
may be made non-removable. When choosing  
the tightening torque, comply with values  
designated by manufacturers.Table 6-2-7  
shows reference values.  
(2) Flare Connecting Procedures and Precautions  
a) Make sure that the flare and union portions  
do not have any scar or dust, etc.  
b) Correctly align the processed flare surface  
with the union axis.  
NOTE:  
c) Tighten the flare with designated torque by  
means of a torque wrench. The tightening  
torque for R410A is the same as that for  
conventional R22. Incidentally, when the  
torque is weak, the gas leakage may occur.  
When applying oil to the flare surface, be sure to use  
oil designated by the manufacturer. If any other oil is  
used, the lubricating oils may deteriorate and cause  
the compressor to burn out.  
Table 6-2-7 Tightening torque of flare for R410A [Reference values]  
Tightening torque of torque  
wrenches available on the market  
Nominal  
diameter  
Outer diameter  
(mm)  
Tightening torque  
.
.
N m (kgf cm)  
.
.
N m (kgf cm)  
16 (160), 18 (180)  
42 (420)  
1/4  
3/8  
1/2  
5/8  
6.35  
9.52  
14 to 18 (140 to 180)  
33 to 42 (330 to 420)  
50 to 62 (500 to 620)  
63 to 77 (630 to 770)  
12.70  
15.88  
55 (550)  
65 (650)  
11 –  
6-3. Tools  
6-3-1. RequiredTools  
The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to  
prevent mixing of other refrigerant.To reinforce the pressure-resisting strength, flare processing dimensions and  
opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.  
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge,  
clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.  
(1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))  
(2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)  
(3) Tools commonly used for R410A and for conventional refrigerant (R22)  
The table below shows the tools exclusive for R410A and their interchangeability.  
Tools exclusive for R410A (The following tools for R410A are required.)  
Tools whose specifications are changed for R410A and their interchangeability  
R410A  
Conventional air  
conditioner installation  
air conditioner installation  
No.  
Used tool  
Usage  
Existence of  
Whether conven- Whether new equipment  
new equipment tional equipment  
can be used with  
for R410A  
can be used  
conventional refrigerant  
Flare tool  
Pipe flaring  
Ye s  
(Note 1)  
1
2
*
Copper pipe gauge for  
adjusting projection  
margin  
Flaring by conventional  
flare tool  
Ye s  
Ye s  
Ye s  
(Note 1)  
(Note 1)  
*
*
Connection of flare nut  
3
Torque wrench  
X
X
Gauge manifold  
Charge hose  
4
5
6
Evacuating, refrigerant  
charge, run check, etc.  
X
X
X
X
Vacuum pump adapter Vacuum evacuating  
Ye s  
Ye s  
Electronic balance for  
Refrigerant charge  
refrigerant charging  
7
Refrigerant cylinder  
Leakage detector  
Charging cylinder  
Refrigerant charge  
Gas leakage check  
Refrigerant charge  
Ye s  
Ye s  
8
9
X
X
X
X
X
(Note 2)  
10  
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection  
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.  
(Note 2) Charging cylinder for R410A is being currently developed.  
General tools (Conventional tools can be used.)  
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary  
as the general tools.  
(1) Vacuum pump  
(4) Reamer  
(9) Hole core drill (Ø65)  
Use vacuum pump by  
attaching vacuum pump adapter.  
(5) Pipe bender  
(10) Hexagon wrench  
(Opposite side 4mm)  
(6) Level vial  
(2) Torque wrench  
(3) Pipe cutter  
(11) Tape measure  
(12) Metal saw  
(7) Screwdriver (+, -)  
(8) Spanner or Monkey wrench  
Also prepare the following equipments for other installation method and run check.  
(1) Clamp meter  
(2) Thermometer  
(3) Insulation resistance tester  
(4) Electroscope  
12 –  
6-4. Recharging of Refrigerant  
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the  
following steps.  
Recover the refrigerant, and check no refrigerant  
remains in the equipment.  
When the compound gauge's pointer has indicated  
- 0.1 Mpa (- 76 cmHg), place the handle Low in the  
fully closed position, and turn off the vacuum pump's  
power switch.  
Connect the charge hose to packed valve service  
port at the outdoor unit's gas side.  
Keep the status as it is for 1 to 2 minutes, and ensure  
that the compound gauge's pointer does not return.  
Connect the charge hose of the vacuum pump  
adapter.  
Set the refrigerant cylinder to the electronic balance,  
connect the connecting hose to the cylinder and the  
connecting port of the electronic balance, and charge  
liquid refrigerant.  
Open fully both packed valves at liquid and gas  
sides.  
Place the handle of the gauge manifold Low in the  
fully opened position, and turn on the vacuum pump's  
power switch. Then, evacuating the refrigerant in the  
cycle.  
(For refrigerant charging, see the figure below.)  
Never charge refrigerant exceeding the specified amount.  
1.  
2.  
3.  
If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.  
Do not carry out additional charging.  
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the  
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the  
specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high  
pressure, and may cause a rupture or personal injury.  
(INDOOR unit)  
(Liquid side)  
(Gas side)  
(OUTDOOR unit)  
Opened  
Closed  
Refrigerant cylinder  
(With siphon pipe)  
Check valve  
Open/Close valve  
for charging  
Service port  
Electronic balance for refrigerant charging  
Fig. 6-4-1 Configuration of refrigerant charging  
– 13 –  
Be sure to make setting so that liquid can be charged.  
When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.  
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant.  
Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the  
cylinder upside down if cylinder is not equipped with siphon.  
[ Cylinder with siphon ]  
[ Cylinder without siphon ]  
Gauge manifold  
Gauge manifold  
OUTDOOR unit  
OUTDOOR unit  
c y l i n d e r  
a n t g i e r R e f r  
Refrigerant  
cylinder  
Electronic  
balance  
Electronic  
balance  
Siphon  
R410A refrigerant is HFC mixed refrigerant.  
Therefore, if it is charged with gas, the composi-  
tion of the charged refrigerant changes and the  
characteristics of the equipment varies.  
Fig. 6-4-2  
6-5. Brazing of Pipes  
Phosphor bronze brazing filler tends to react  
with sulfur and produce a fragile compound  
water solution, which may cause a gas  
leakage.Therefore, use any other type of  
brazing filler at a hot spring resort, etc., and  
coat the surface with a paint.  
1.  
2.  
6-5-1. Materials for Brazing  
(1) Silver brazing filler  
Silver brazing filler is an alloy mainly composed  
of silver and copper. It is used to join iron,  
copper or copper alloy, and is relatively expen-  
sive though it excels in solderability.  
When performing brazing again at time of  
servicing, use the same type of brazing filler.  
(2) Phosphor bronze brazing filler  
Phosphor bronze brazing filler is generally used  
to join copper or copper alloy.  
6-5-2. Flux  
(1) Reason why flux is necessary  
(3) Low temperature brazing filler  
1.By removing the oxide film and any foreign  
matter on the metal surface, it assists the flow  
of brazing filler.  
Low temperature brazing filler is generally called  
solder, and is an alloy of tin and lead. Since it is  
weak in adhesive strength, do not use it for  
refrigerant pipes.  
2.In the brazing process, it prevents the metal  
surface from being oxidized.  
3.By reducing the brazing filler's surface tension,  
the brazing filler adheres better to the treated  
metal.  
14 –  
(2) Characteristics required for flux  
6-5-3. Brazing  
1.Activated temperature of flux coincides with  
the brazing temperature.  
As brazing work requires sophisticated techniques,  
experiences based upon a theoretical knowledge, it  
must be performed by a person qualified.  
2.Due to a wide effective temperature range, flux  
is hard to carbonize.  
In order to prevent the oxide film from occurring in  
the pipe interior during brazing, it is effective to  
proceed with brazing while letting dry Nitrogen gas  
(N2) flow.  
3.It is easy to remove slag after brazing.  
4.The corrosive action to the treated metal and  
brazing filler is minimum.  
5.It excels in coating performance and is harm-  
less to the human body.  
Never use gas other than Nitrogen gas.  
(1) Brazing method to prevent oxidation  
As the flux works in a complicated manner as  
described above, it is necessary to select an  
adequate type of flux according to the type and  
shape of treated metal, type of brazing filler and  
brazing method, etc.  
1.  
Attach a reducing valve and a flow-meter to  
the Nitrogen gas cylinder.  
2.  
Use a copper pipe to direct the piping mate-  
rial, and attach a flow-meter to the cylinder.  
(3) Types of flux  
Noncorrosive flux  
3. Apply a seal onto the clearance between the  
piping material and inserted copper pipe for  
Nitrogen in order to prevent backflow of the  
Nitrogen gas.  
Generally, it is a compound of borax and boric  
acid.  
It is effective in case where the brazing tem-  
perature is higher than 800°C.  
4.  
When the Nitrogen gas is flowing, be sure to  
keep the piping end open.  
Activated flux  
5.  
Adjust the flow rate of Nitrogen gas so that it  
is lower than 0.05 m³/Hr or 0.02 MPa (0.2kgf/  
cm²) by means of the reducing valve.  
Most of fluxes generally used for silver brazing  
are this type.  
It features an increased oxide film removing  
capability due to the addition of compounds  
such as potassium fluoride, potassium chloride  
and sodium fluoride to the borax-boric acid  
compound.  
6.  
7.  
After performing the steps above, keep the  
Nitrogen gas flowing until the pipe cools  
down to a certain extent (temperature at  
which pipes are touchable with hands).  
Remove the flux completely after brazing.  
(4) Piping materials for brazing and used braz-  
ing filler/flux  
Piping  
material  
Used brazing  
filler  
Used  
flux  
Copper - Copper Phosphor copper Do not use  
M
Flow meter  
Copper - Iron  
Iron - Iron  
Silver  
Silver  
Paste flux  
Vapor flux  
Stop valve  
Nitrogen gas  
cylinder  
From Nitrogen cylinder  
1.  
Do not enter flux into the refrigeration cycle.  
2.  
When chlorine contained in the flux remains  
within the pipe, the lubricating oil deteriorates.  
Therefore, use a flux which does not contain  
chlorine.  
Pipe  
Nitrogen  
gas  
Rubber plug  
3.  
When adding water to the flux, use water  
which does not contain chlorine (e.g. distilled  
water or ion-exchange water).  
4.  
Remove the flux after brazing.  
Fig. 6-5-1 Prevention of oxidation during brazing  
15 –  
7. INDOOR UNIT CONTROL  
7-1. Indoor Control Circuit  
Main (Sub) master remote controller  
(Wired)  
Weekly timer  
LCD  
driver  
Display  
LCD  
Display  
LCD  
Max. 8 units are connectable.*1  
CPU  
Display  
LED  
Function setup  
Key switch  
Function setup  
Key switch  
*1 When group and twin combination.  
main remote controller shal be connected  
follower indoor unit  
CPU  
CN2 CN1  
*2 Weekly timer is not connectable to the  
sub remote controller.  
DC5V  
2
*
DC5V  
Remote  
Power  
circuit  
Secondary  
battery  
controller  
communication  
circuit  
Power circuit  
Sold separatrly  
Sold separatrly  
#3  
Indoor unit  
#1 Header unit  
Follower unit  
A
B
A
B
A
B
#2  
Indoor control P.C. board (MCC-1510)  
U3  
U4  
Central control  
communication  
circuit  
Central control  
remote controller  
(Sold separatrly)  
EEPROM  
Remote  
controller  
communication  
circuit  
DC20V  
DC12V  
DC5V  
Reciver and Display P.C board  
(MCC-819)  
TA sensor  
TC sensor  
TCJ sensor  
Buzzer  
Driver  
Reciver unit  
Display LED  
CPU  
H8/3039  
Same as Same as  
the left the left  
Driver  
HA  
Louver  
motor  
Outside  
output  
AC  
Serial  
send/  
receive  
circuit  
Run  
Wireless  
remote  
signal  
synchronous  
signal input  
circuit  
Warning  
Ready  
Setting  
Thermo. ON  
(A/B)  
Fan motor  
control  
Cool  
Heat  
Fan  
1 2 3  
1 2 3  
Indoor  
fan  
motor  
Power  
circuit  
circuit  
DC280V  
DC15V  
Outdoor  
unit  
Outdoor  
unit  
1 2 3  
1 2 3  
Outdoor unit  
16 –  
INDOOR UNIT CONTROL CIRCUIT (Continued)  
7-2. Control Specifications  
NO.  
1
Item  
Control at  
power-on reset  
Overview of specifications  
(1) Identification of outdoor unit  
Remarks  
The “PREPARING” lamp  
lights during initial setting  
(model recognition) after  
Identifies outdoor unit at power-on reset, and switches control  
according to the identification result.  
(2) Setting of indoor unit fan speed and adjustment of air flow direction power-on reset.  
Switches indoor unit fan speed, setting of air flow direction  
Fan speed, adjustment of  
adjustment, etc. based on EEPROM data.  
air flow direction  
2
Operation mode  
switching  
(1) Switches operation mode according to mode select instruction  
from remote controller.  
R/C instructions  
OFF  
Outline of control  
Turns OFF air conditioner  
FAN  
“Fan only” operation  
Cooling operation  
COOL  
DRY  
Dehumidifying operation  
Heating operation  
HEAT  
AUTO  
• Selects COOL or HEAT mode  
automatically according to Ta, Ts, and To.  
Ta : Room temperature  
Ts : Set temperature  
• The first operation is as follows according  
to Ta. (COOL thermo sensor continues  
OFF (FAN mode with set fan speed) within  
To : Outside air temperature  
the range of Ts +α-1<Ta< Ts +α+1.)  
COOL  
operation  
+1.0  
FAN mode with  
set fan speed  
Ta  
Ts+  
(
)
-1.0  
HEAT  
operation  
α is corrected according to outside air  
temperature.  
Outside air temp. Corrected value (α)  
No To  
>
0 K  
-1 K  
0 K  
k=deg  
To 24°C  
=
>
24>To 18°C  
=
To<18°C  
+1 K  
0 K  
Abnormal To  
(2) Operation instruction permission mode  
HEAT and AUTO modes are not available for COOL only models.  
When instruction is issued from wireless remote controller in the  
HEAT or AUTO mode, it is indicated by a reception sound “pi, pi”  
and by alternate blinking of “TIMER” and “PREPARING” lamps. To  
cancel this alternate blinking, issue an instruction of mode other  
than HEAT or AUTO.  
3
Room temperature (1) Adjustment range Remote controller set temperature (°C)  
control  
COOL/DRY HEAT AUTO  
Wired type  
18 - 29  
17 - 30  
18 - 29 18 - 29  
17 - 30 17 - 30  
Wireless type  
* When use of remote controller sensor is set (with DN32), even  
when sensor value is within the above range in HEAT or AUTO  
mode, the thermo sensor turns OFF when Ta sensor value  
exceeds 35 °C.  
17 –  
NO.  
3
Item  
Remarks  
Overview of specifications  
Room temperature  
control  
Heat intake temperature  
shift  
(2) The set temperature for HEAT operation can be corrected by code  
No. 06.  
(When unit’s temperature  
sensor is used)  
Set data  
0
2
4
6
Correction of set temp. +0°C +2°C +4°C +6°C  
Factory setting  
Set data  
2
* When use of remote controller sensor is set (with DN32), no  
correction is performed.  
4
Capacity auto  
control  
(1) Issues instruction of operating frequency to outdoor unit according  
to the difference between Ta and Ts.  
(2) COOL operation  
(GA control)  
Calculates room temp. difference between Ta and Ts as well as  
room temp. variation every 90 seconds to find correction value of  
specified operating frequency and to correct the current operating  
frequency.  
Ta(n)–Ts(n) : Room temp. difference  
Ta(n-1)–Ta(n) : Room temp. variation  
n
: Number of detection times  
n–1: Number of detection times  
(90 seconds before)  
(3) HEAT operation  
Calculates room temp. difference between Ta and Ts as well as  
room temp. variation every 60 seconds to find correction value of  
specified operating frequency and to correct the current operating  
frequency.  
Ts(n)–Ts(n) : Room temp. difference  
Ta(n)–Ta(n_1) : Room temp. variation  
n
: Number of detection times  
n–1: Number of detection times  
(60 seconds before)  
(4) DRY operation  
The frequency correction control is the same as that for COOL  
operation.  
However, the maximum frequency is limited to S6 or so.  
Note) When LOW fan speed is set, the maximum frequency is  
limited to SB or so.  
5
COOL/HEAT/  
AUTO control  
(1) Switching between COOL and HEAT is determined based on the  
following control.  
Ta  
(˚C)  
After 10 minutes pass from  
thermo sensor OFF,  
operation mode changes  
from HEAT (thermo sensor  
OFF) to COOL if Ta exceeds  
Tsh +1.5.  
COOL  
+1.5  
(COOL ON)  
Tsc : COOL set temp.  
Tsc  
Tsh  
or  
Tshc : HEAT set temp. +  
room temp. control/  
correction  
(COOL OFF)  
HEAT  
-1.5  
( ) shows an example of  
COOL ON/OFF.  
After 10 minutes pass from  
thermo sensor OFF,  
operation mode changes  
from COOL (thermo sensor  
OFF) to HEAT if Ta lowers  
below Tsc -1.5.  
(2) The GA control after determination of operation mode follows the  
description in No. 4.  
(3) The room temperature control and temperature correction follow  
the descriptions in No. 3 and No. 15.  
18 –  
INDOOR UNIT CONTROL CIRCUIT (Continued)  
NO.  
6
Item  
Overview of specifications  
Remarks  
Fan speed control (1) A fan speed HH (quick high), H (high), L (low) or AUTO is selected HH>H+>H>  
according to the instruction from remote controller for FAN mode  
operation.  
L+>L>UL  
(2) Fan speed is switched according to the difference between Ta and Wireless type allows HH,  
Ts in the AUTO mode.  
H+, H, L+, L, and AUTO.  
[Cooling]  
HH  
H+  
Ta (˚C)  
A
B
C
D
+3.0  
+2.5  
+2.0  
+1.5  
+1.0  
HH  
(HH)  
H
L+  
L
H+(HH)  
H(HH)  
E
L+(H+)  
+0.5  
Tsc  
-0.5  
L(H)  
L(H)  
L(L+)  
F
G
• The fan speed control is the same for temperature setting by remote  
controller or the unit.  
• Once fan speed is changed, it remains unchanged for 3 minutes  
unless different fan speed is selected by instruction.  
• At the beginning of cooling, a falling gradient (higher fan speed) is  
selected.  
• When the temperature difference between Ta and Ts is on a  
threshold line, fan speed does not change.  
• ( ): Auto cooling  
[Heating]  
Ta (˚C)  
L( L+)  
(-0.5)  
(0)  
-1.0  
Tsh  
E
D
L+(H)  
H(H+)  
(+0.5)  
+1.0  
H+  
(HH)  
(+1.0)  
(+1.5)  
+2.0  
+3.0  
C
B
A
HH  
(HH)  
(+2.0)  
+4.0  
( ): Temperature setting by remote controller  
Other than ( ): Temperature setting by unit  
• Once fan speed is changed, it remains unchanged for one minute  
unless different fan speed is selected by instruction.  
• At the beginning of heating, a rising gradient (higher fan speed) is  
selected.  
• When the temperature difference between Ta and Ts is on a  
threshold line, fan speed does not change.  
• ( ): Auto heating  
• Fan speed is switched to a higher level when Tc reaches 60 °C.  
Tc : Indoor unit heat  
exchange sensor  
temp.  
19 –  
NO.  
6
Item  
Overview of specifications  
Remarks  
Fan speed control  
COOL HEAT AP40-56  
AP63  
1360  
1300  
1240  
1200  
1120  
1120  
1020  
970  
AP71-80  
1480  
1340  
1320  
1300  
1200  
1200  
1100  
1040  
500  
HH  
1220  
1180  
1140  
1120  
1060  
1060  
990  
HH  
H+  
H+  
H
H
L+  
L
L+  
L
940  
UL  
UL  
500  
500  
(3) When thermo sensor turns OFF during heating, the fan speed  
mode becomes UL (weak).  
“HEAT PREPARING”  
indication  
(4) When Ta is 25 °C or above at the beginning of HEAT operation or  
when canceling defrost mode, H or HH mode continues for one  
minute from the time when Tc enters zone E shown in the figure in  
No.7 below.  
(5) The HH fan speed for auto cooling/heating is set to a speed higher  
than that for normal cooling/heating. However, it varies depending  
on the temperature difference of Tc during auto heating.  
Tc  
(˚C)  
47  
HH+  
42  
HH  
7
Cool air prevention (1) Performs indoor unit fan control in the HEAT mode according to  
Fan speed select setting  
by remote controller takes  
precedence in zones D  
control  
the Tc (or Tcj) sensor detect temperature. The maximum speed is  
limited as shown below.  
Shifts Tc control value by +6 °C and E.  
during defrosting. However, zone “HEAT PREPARING” is  
Tc  
Tcj  
(˚C)  
36  
HH  
H
B is regarded as zone C after 6  
indicated in zones A and  
minutes pass from the startup of B.  
compressor.  
34  
L
Zone E  
Zone D  
32  
UL  
30  
OFF  
Zone C  
Zone B  
24  
20  
Zone A  
20 –  
INDOOR UNIT CONTROL CIRCUIT (Continued)  
NO.  
8
Item  
Freezing  
prevention control  
(low-temp.  
Overview of specifications  
Remarks  
(1) Performs the following operation control in the COOL or DRY  
mode according to the Tc (or Tcj) sensor detect temperature.  
When zone J in the figure below is detected for 6 minutes, the  
specified operating frequency is decreased from the actual  
operating frequency, and the specified operating frequency is  
changed every 30 seconds in zone J.  
Tcj : Indoor unit heat  
exchange sensor  
temp.  
release)  
Timer count stops and is maintained in zone K.  
Timer count is cleared to restore normal operation when zone I is  
detected.  
If the specified operating frequency becomes SO due to  
continuation of zone J, return temperature A is raised from 5 to  
12 °C, and operation with L fan speed continues until zone I is  
detected.  
Tc(˚C)  
5
I
A
K
2
J
If 4-way valve cannot be switched during heating and the following  
conditions become true, freezing prevention control is performed.  
(However, zone J entering control temperature is changed from 2  
to -5 °C.)  
Tcn :  
Tc after 5 minutes  
from operation start  
Tc (n-1):  
[Conditions]  
Tc at operation start  
The following Aor Bbecomes true after 5 minutes pass from  
operation start.  
<
ATcn Tc(n–1)–5  
BTcn<Tc(n–1)–1 and Tcn Ta<5°C  
=
<
=
9
High-temp. release (1) Performs the following operation control in the HEAT mode  
control according to the Tc (or Tcj) sensor detect temperature.  
When zone M is detected, the specified operating frequency is  
decreased from the actual operating frequency, and the specified  
operating frequency is changed every 30 seconds in zone M.  
This control is disabled for  
twin follower indoor units.  
• The specified operating frequency is maintained in zone N.  
• When zone L is detected, the specified operating frequency is  
returned by approx. 6 Hz every 60 seconds.  
Tc  
Tcj  
Factory setting  
(˚C)  
Control temp. (°C)  
M
A
A
B
N
56 (54)  
52 (52)  
B
L
Even when the thermo is  
set to OFF, the control is  
implemented in the same  
way.  
Note) At the beginning of operation or when Tc (or Tcj) lowers below  
30 °C after operation start, values (54) and (52) in the table are  
used as control temperature.  
10 Residual heat  
removal  
Runs indoor unit fan in L (low) mode for about 30 seconds after HEAT  
operation stops to remove residual heat.  
21 –  
NO.  
Item  
Overview of specifications  
(1) During the first operation after power on, flap position is controlled Louver angle: 0 °C (full  
automatically according to operation mode (COOL/HEAT). close)  
Remarks  
11 Flap control  
Cooling  
Heating  
Full close  
103°  
0°  
45°  
(2) When louver position is controlled by remote controller, the unit’s  
microcomputer memorizes the position for use in the next  
operation.  
* The memorized louver position is cleared when power is turned  
off, and returns to the state of (1) above.  
Alarm : A code number  
(except F08 and  
L31) appears on  
the remote  
(3) Flap position setting  
• Flap position can be set within the range below.  
COOL/DRY  
HEAT/FAN  
controller and the  
indoor unit stops.  
• Flap position can be set collectively or individually in the group  
twin or triple operation mode. (Wireless remote controller allows  
individual setting only.)  
(4) Swing setting  
• Flap moves within the range below.  
All operation modes  
• Flap swing range can be set collectively or individually in the  
group twin or triple operation mode. (Setting by wireless remote  
controller is disabled when the main remote controller is used.)  
(5) When air conditioner operation stops, flap closes automatically. It  
keeps its position in the event of an alarm.  
(6) Flap tilts upward automatically during preparation for heating.  
(7) In the twin or triple operation mode selected by wireless remote  
controller, swing setting interlocks with the header indoor unit. If  
this setting is transmitted from a follower indoor unit, operation  
does not change with a reception sound “pi, pi, pi” if operation  
mode differs between header unit and follower unit.  
22 –  
INDOOR UNIT CONTROL CIRCUIT (Continued)  
Item  
Overview of specifications  
Remarks  
NO.  
12 HA control  
(1) When connected to a remote control system (tele-control or  
remote on/off interface), operation ON/OFF can be controlled by  
the HA signal input.  
A connector (separately  
available) is required  
when using the HA  
(2) Outputs operation ON/OFF status to the HA output terminal.  
(3) HA signal input/output specifications conform to the JEMA  
standard.  
terminal CH61 for remote  
ON/OFF control.  
When group operation is  
in use, connect the  
connector to either header  
or follower indoor unit.  
13 Filter sign  
indication  
(1) Transmits filter replacement signal to remote controller for  
indication on the LCD when accumulated operation hours of  
indoor unit fan exceeds the specified time (150 hours).  
“FILTER” lamp ON  
(unavailable for  
wireless type)  
(2) Clears accumulation timer upon receiving the filter reset signal  
from remote controller. At this time, when the specified time has  
already passed, the accumulated time is reset and the filter sign  
disappears from the LCD.  
– 23 –  
NO.  
Item  
Overview of specifications  
Remarks  
14 Central control  
mode switching  
(1) The scope of operation by remote controller on the indoor unit  
side can be switched by the setting of remote controller.  
(2) Scope of operation by remote controller on the indoor unit side  
[Individual] : All settings and ON/OFF operations are available.  
[Central 1] : ON/OFF operations are disabled.  
No indication  
“CENTRAL CONTROL”  
lamp ON  
[Central 2] : ON/OFF operations, operation mode selection, and  
temperature setting are disabled.  
“CENTRAL CONTROL”  
lamp ON  
[Central 3] : Operation mode selection and temperature setting  
are disabled.  
“CENTRAL CONTROL”  
lamp ON  
[Central 4] : Operation mode selection is disabled.  
“CENTRAL CONTROL”  
lamp ON  
When wired remote  
controller is not used,  
operation range is the  
same as above though  
lamp indication remains  
unchanged.  
If an unavailable operation  
mode is transmitted from  
wireless remote controller,  
it is indicated with a  
reception sound “pi, pi, pi,  
pi, pi”.  
15 Power-saving  
control  
(1) Power-saving operation is available in the AUTO mode.  
(2) The set temperature is corrected using various sensor data within  
the range where comfort is maintained.  
(3) By using various sensor data including room temp. Ta, outside air  
temp. To, fan speed, and indoor unit heat exchange sensor temp.  
Tc, 20-minute data is averaged to calculate a set temperature  
correction value.  
(4) The set temperature is corrected every 20 minutes with the  
following shift range.  
Cooling : +1.5 to -1.0K  
Heating : -1.5 to +1.0K  
16 Maximum  
frequency limit  
control  
(1) This control is performed when AUTO mode is selected.  
(2) COOL mode: When To is under 28 °C, the control is as follows.  
Ta(˚C)  
+4  
Normal control  
Maximum frequency is  
+3  
limited to the rating of cooling.  
Tsc  
(3) HEAT mode: When To is over 15 °C, the control is as follows.  
Ta(˚C)  
Tsh  
Maximum frequency is limited  
to the rating of heating.  
-3  
-4  
Normal control  
24 –  
INDOOR UNIT CONTROL CIRCUIT (Continued)  
7-3. P. C. Board of Indoor Unit  
MCC-1510  
Microcomputer  
run LED  
TC sensor  
TCJ sensor  
Indoor unit - outdoor unit wire  
EEPROM  
CN101, DC5V  
CN102, DC5V  
D02  
IC10  
CN67, AC200V  
HA (T10)  
Optional power supply  
CN61, DC12V  
CN309, AC200V  
Option output  
CN60, DC12V  
CHK  
CN71, DC5V  
Central control  
DISP  
CN40, DC 5V  
CN72, DC5V  
External alarm input  
CN80, DC12V  
Terminating resistor  
provided/not provided  
EXCT  
CN73, DC5V  
Remote controller A/B  
selection  
R/C power LED  
SW01  
D203  
TA sensor  
CN104, DC5V  
Remote controller  
CN41, DC20V  
Louver  
DC fan input/output  
Indication output/wireless reception  
FAN DRIVE  
CN32, DC12V  
CN33, DC12V  
CN210  
CN213, DC5V  
25 –  
7-4. Optional Onboard Connector Specifications  
26 –  
9
8. Troubleshooting  
1. Guide to Troubleshooting  
[Wired Remote Controller Type]  
(1) Before starting troubleshooting  
(a) Necessary tools/measuring equipment  
• Phillips screwdrivers, flat-blade screwdrivers, wrenches, pliers, nipper, etc.  
• Multimeter, thermometer, pressure gauge, etc.  
(b) Precheck  
AThe following operations are normal.  
1) Compressor does not work.  
• Is 3-minute delay operation functioning? (for 3 minutes after compressor OFF)  
• Is thermo sensor OFF?  
• Is FAN mode or TIMER mode operation going?  
• Is water overflow alarm detected?  
• Is high outside air temperature operation control working during heating?  
2) Indoor unit fan does not work.  
• Is cool air prevention control working during heating?  
3) Outdoor unit fan does not work or its fan speed changes.  
• Is high-temp. release operation control working during heating?  
• Is low outside air temperature operation control working during cooling?  
• Is defrosting operation going?  
4) Operation ON/OFF by remote controller is disabled.  
• Is any remote controller or external control working?  
• Is auto address setting in progress?  
(At t he first power on or when indoor unit address is changed, operation control is disabled for  
about 5 minutes after power on.)  
BAre all cables/wiring set in the initial state?  
CAre indoor unit and remote controller connected correctly?  
(2) Troubleshooting procedure  
When an error occurs, check the unit in the following procedure.  
Error Check indication of check code  
Check faulty location and parts  
(Note) Other than the check items in the table, malfunction or wrong diagnosis of microcomputer  
due to effect of power or external noise is considered. If there is any source of noise, shield  
the remote controller wiring.  
[Wireless Remote Controller Type]  
(1) Before starting troubleshooting  
(a) Necessary tools/measuring equipment  
• Phillips screwdrivers, flat-blade screwdrivers, wrenches, pliers, nipper, etc.  
• Multimeter, thermometer, pressure gauge, etc.  
(b) Precheck  
AThe following operations are normal.  
1) Compressor does not work.  
• Is 3-minute delay operation functioning? (for 3 minutes after compressor OFF)  
• Is thermo sensor OFF?  
• Is FAN mode or TIMER mode operation going?  
• Is high outside air temperature operation control working during heating?  
2) Indoor unit fan does not work.  
• Is cool air prevention control working during heating?  
27 –  
3) Outdoor unit fan does not work or its fan speed changes.  
• Is high-temp. release operation control working during heating?  
• Is low outside air temperature operation control working during cooling?  
• Is defrosting operation going?  
4) Operation ON/OFF by remote controller is disabled.  
• Is forcible operation OFF mode set?  
• Is any remote controller or external control working?  
• Is auto address setting in progress?  
(At the first power on or when indoor unit address is changed, operation control is disabled for  
about 5 minutes after power on.)  
BAre all cables/wiring set in the initial state?  
CAre indoor unit and receiver unit connected correctly?  
(2) Troubleshooting procedure  
When an error occurs, check the unit in the following procedure.  
Error  
Check indication of lamps  
Check faulty location and parts  
(Note) Other than the check items in the table, malfunction or wrong diagnosis of microcomputer  
due to effect of power or external noise is considered. If there is any source of noise, shield  
the signal lines.  
(a) Outline of judgment  
The following describes the primary judgment of locating faulty unit (indoor unit or outdoor unit). (In  
the case of group control operation, the header unit also indicates errors of follower unit by lamp.)  
Judging from lamp status of indoor unit  
The indoor unit monitors the operating status of air conditioner. When the protection circuit is  
activated, the indoor unit indicates the following self-diagnosis contents.  
: OFF  
: ON  
: Blinking (0.5 seconds interval)  
Possible causes  
Lamp indication  
Check code  
OPERATION TIMER PREPARING  
Power OFF  
Poor connection/contact between receiver/indication unit and  
indoor unit control board  
All OFF  
Reception error  
Transmission error  
Communication error  
Wired remote  
controller  
Wrong connection or  
poor contact between  
wired remote controller  
and indoor unit  
E01  
E02  
E03  
E08  
E09  
E18  
OPERATION TIMER PREPARING  
Duplication of indoor unit No.  
Duplication of remote controller header  
Invalid setting  
Poor connection/contact between indoor units or indoor unit  
power OFF  
Blinking  
(Communication error between header and follower indoor  
units or between twin header and follower indoor units)  
Wrong connection or poor contact between indoor unit and  
outdoor unit  
(Communication error between indoor and outdoor units)  
E04  
P12  
OPERATION TIMER PREPARING  
Blinking  
Failure of indoor unit DC fan (Protection device of indoor unit is  
activated.)  
OPERATION TIMER PREPARING  
Alternate blinking  
28 –  
Troubleshooting (Continued)  
Outline of judgment (Contenued)  
Lamp indication  
Check code  
Possible causes  
Abnormal outdoor unit discharge  
temperature  
P03  
P04  
(*) Protection device  
of outdoor unit is  
activated.  
Outdoor unit high-pressure system error  
OPERATION TIMER PREPARING  
P19  
P22  
P26  
P29  
P31  
Four-way valve system error (judged by indoor unit)  
Outdoor unit: Malfunction of fan  
Outdoor unit: Inverter Idc activated  
Outdoor unit: Position detect error  
Protection device of  
outdoor unit is activated.  
Alternate blinking  
Header and follower indoor units in the group are not running  
due to the following alarm.  
(Alarm code: E03, L03, L07, L08)  
F01  
F02  
F10  
Heat exchange sensor (TCJ) error  
OPERATION TIMER PREPARING  
Indoor unit sensor error  
Heat exchange sensor (TC) error  
Room temperature sensor (TA) error  
Alternate blinking  
F04  
F06  
F08  
Discharge temperature sensor (TD) error  
Temperature sensor (TE, TS) error  
Outside air temperature sensor (TO) error  
OPERATION TIMER PREPARING  
(*) Outdoor unit  
sensor error  
Alternate blinking  
F29  
Failure of indoor unit EEPROM  
OPERATION TIMER PREPARING  
Simultaneous blinking  
H01  
H02  
H03  
H06  
Compressor breakdown  
Compressor locking  
Current detect circuit error  
Outdoor unit low-pressure system error  
OPERATION TIMER PREPARING  
(*) Outdoor unit  
compressor  
system error  
Blinking  
Duplication of header indoor unit  
Group connection indoor unit for  
individual indoor unit  
Group address not set  
L03  
L07  
L08  
L09  
OPERATION TIMER PREPARING  
Auto address  
*If group configuration  
or address at power on  
is invalid, the unit  
No setting (indoor unit capacity)  
Simultaneous blinking  
enters address setting  
mode automatically.  
L20  
L29  
L30  
L31  
Duplication of indoor unit collective address  
Other errors of outdoor unit (*)  
External interlock error  
OPERATION TIMER PREPARING  
Others  
Phase sequence error  
Simultaneous blinking  
(*) Check code detected by outdoor unit is a typical example. It varies with outdoor unit of combination.  
For details, see the Service Guide of applicable outdoor unit.  
29 –  
Others (Excluding check code)  
Lamp indication  
Check code  
Possible causes  
Trial operation in progress  
OPERATION TIMER PREPARING  
Simultaneous blinking  
Invalid setting  
OPERATION TIMER PREPARING  
(Auto cooling/heating setting for auto cooling/heating  
unavailable unit or heating setting for cool only unit)  
Alternate blinking  
Error mode detected by remote controller or central controller  
Diagnosis function  
Judgment and action  
Check code  
No  
indication header indoor unit  
(remote  
controller  
disabled)  
Possible causes  
Air conditioner status  
Conditions  
No communication with  
OFF  
Failure of remote controller power  
supply or indoor unit EEPROM  
1.Check remote controller wires.  
2.Check remote controller.  
3.Check indoor unit power wiring.  
4.Check indoor unit P. C. board.  
5.Check indoor unit EEPROM and  
insertion into socket.  
Remote controller is not  
connected correctly.  
Indoor unit is not powered  
on.  
Auto address setting is not  
completed.  
... Auto address repetition occurs.  
E01  
*2  
No communication with  
header indoor unit  
Disconnection between  
OFF (auto reset)  
*Operation  
continues under  
Indicated when an Remote controller signal reception error  
error is detected  
1.Check remote controller wires.  
2.Check remote controller.  
remote controller and header central control  
indoor unit (detected by R/C)  
3.Check indoor unit power wiring.  
4.Check indoor unit P. C. board.  
E02  
E09  
L20  
Signal transmission error OFF (auto reset)  
to indoor unit (detected by *Operation  
Indicated when an Remote controller transmission error  
error is detected  
1.Check remote controller transmitter.  
... Replace remote controller.  
R/C)  
continues under  
central control  
Multiple remote controller OFF (Follower R/C Indicated when an 1.Check for multiple remote  
headers (detected by R/C) continues  
operation)  
error is detected  
controller headers.  
... One header only, others are  
follower R/C.  
Duplication of indoor unit OFF (auto reset)  
collective address during  
communication of central  
control system  
(detected by indoor unit/  
central controller)  
Indicated when an 1.Check central control network  
error is detected address setting.  
Central  
controller  
L20  
*3  
Failure of central control  
communication circuit  
(detected by central  
controller)  
Operation  
continues (following error is detected  
R/C)  
Indicated when an 1.Check communication line,  
wrong connection, and indoor  
unit power supply.  
Central  
controller  
(Transmission)  
C05  
(Reception)  
C06  
2.Check communication circuit  
(U3, U4, XY terminals).  
3.Check central controller  
(including central control R/C).  
4.Check terminating resistors  
(TCC-LINK).  
Continue/OFF  
(depending on  
situation)  
Indicated when an Check the unit's check code with  
error is detected remote controller  
Failure of indoor unit group  
follower unit.  
Central  
controller  
P30/b7  
*2 No check code can be indicated by wired remote controller. (Normal operation of air conditioner cannot be controlled by wired remote controller.)  
Check codes are indicated by the lamps for wireless models.  
*3 This is an error related to communication of remote controller (A, B) or central control system (TCC-LINK U3, U4).  
Remote controller indicates E01, E02, E03, E09, E18 or no code according to situation.  
30 –  
Troubleshooting (Continued)  
Check Code Table (Indoor Unit)  
31 –  
Check Code Table (Outdoor Unit)  
32 –  
Troubleshooting (Continued)  
Check CodeTable  
Failure mode detected by indoor unit  
Diagnosis function  
Judgment and action  
Check code  
E03  
Possible causes  
Air conditioner status  
Conditions  
No signal reception from remote  
controller  
OFF  
Indicated when an 1.Check remote controller wiring.  
(auto reset)  
error is detected  
• No indication on remote controller  
LCD (disconnection)  
Central controller [C06] check code  
E04  
Serial signal from outdoor unit does OFF  
Indicated when an 1.When outdoor unit does not work at all  
not reach indoor unit.  
• Wrong wire connection  
(auto reset)  
error is detected  
• Check wires, correct wrong  
connection.  
• Failure of outdoor unit serial  
transmitter  
Check outdoor unit boards and wiring.  
2.When outdoor unit works normally  
• Failure of indoor unit serial  
receiver  
Check boards (indoor unit receiver,  
outdoor unit transmitter)  
E08  
L03  
L07  
Duplication of indoor unit address  
Duplication of header indoor unit  
Group line in individual indoor unit  
OFF  
Indicated when an 1.Check remote controller connection  
error is detected  
(group/individual) change after  
power on.  
* If group configuration or address is  
not correct, the unit enters auto  
address setting mode automatically  
for address re-setting.  
L08  
L09  
Indoor unit group address not set  
Indoor unit capacity not set  
OFF  
OFF  
OFF  
Indicated when an 1.Set indoor unit capacity (DN=11)  
error is detected  
L30  
P12  
External interlock alarm input  
Failure of indoor unit DC fan  
Indicated when an 1.Check external devices.  
error is detected  
Indicated when an 1. Position detect error  
error is detected 2.Overcurrent protection circuit  
2.Check indoor unit boards.  
operation of indoor unit fan driver  
3. Indoor unit fan lock  
4. Check indoor unit boards.  
P19  
Failure of 4-way valve system  
• Indoor unit heat exchange  
temperature lowers after HEAT  
operation starts.  
OFF  
(auto reset)  
Indicated when an 1.Check 4-way valve.  
error is detected 2.Check 2-way valve/check valve.  
3.Check indoor unit heat exchanger (TC/TCJ)  
4.Check indoor unit boards.  
.
P31  
F01  
F02  
F10  
F29  
E18  
Indoor unit OFF during alarming to OFF  
other indoor units  
Indicated when an 1.Judging follower unit when header  
unit is E03, L03, L07 or L08  
(follower units) error is detected  
(auto reset)  
2.Check indoor unit boards.  
Improper mounting, disconnection OFF  
Indicated when an 1.Check TCJ.  
or short-circuit of indoor unit heat  
exchange sensor TCJ  
(auto reset)  
error is detected  
2.Check indoor unit boards.  
Improper mounting, disconnection OFF  
Indicated when an 1.Check TC.  
or short-circuit of indoor unit heat  
exchange sensor TC  
(auto reset)  
error is detected  
2.Check indoor unit boards.  
Improper mounting, disconnection OFF  
or short-circuit of indoor unit room (auto reset)  
temp. sensor TA  
Indicated when an 1.Check TA.  
error is detected  
2.Check indoor unit boards.  
Failure of indoor unit EEPROM  
• EEPROM access error  
OFF  
(auto reset)  
Indicated when an 1.Check indoor unit EEPROM and  
error is detected  
insertion into socket.  
2.Check indoor unit boards.  
Communication error between  
header and follower indoor units  
OFF  
(auto reset)  
Indicated when an 1.Check remote controller wiring.  
error is detected  
2.Check indoor unit power wiring.  
3.Check indoor unit boards.  
33 –  
Failure mode detected by outdoor unit (Representative codes)  
• The check code used varies depending on the combination with the outdoor unit.  
Diagnosis function  
Judgment and action  
Indicated when an 1.Check power voltages (200 20 VAC).  
Check code  
H01  
Possible causes  
Air conditioner status  
Conditions  
Compressor breakdown  
OFF  
• Compressor stops due to  
error is detected  
2.Freezing cycle overload operation  
operating frequency decrease.  
3.Check current detect circuit on the AC side  
.
H02  
Compressor does not work.  
• Overcurrent protection circuit is  
activated after a certain time from  
compressor startup.  
OFF  
Indicated when an 1.Failure of compressor (lock, etc.)  
error is detected ... Replace the compressor.  
2.Improper compressor wiring (phase loss)  
3.Lost-phase operation of power  
supply (3-phase models)  
H03  
H06*1  
L29  
Failure of current detect circuit  
• Large AC current even during  
compressor OFF  
OFF  
OFF  
OFF  
Indicated when an 1.Operation stops soon when restarted  
error is detected ... Check IPDU.  
.
2.Lost-phase operation of power supply  
Check 3-phase power voltages and wiring.  
• Phase loss in power supply  
Low-pressure switch ON  
(applicable models)  
COOL : 30 seconds  
HEAT : 10 minutes  
Indicated when an 1.Check freezing cycle (gas  
error is detected  
leakage).  
2.Check low-pressure switch circuit.  
3.Check outdoor unit CDB board.  
Other outdoor unit errors  
Indicated when an 1.Check CDB/IPDU wiring.  
error is detected 2.Freezing cycle overload operation  
• CDB-IPDU communication error  
(connector disconnection)  
• Abnormal heatsink temperature  
(over specified value)  
L31*1  
Phase detection protection circuit  
activated (normal models)  
Operation  
continued  
(compressor  
OFF)  
Indicated when an 1.Check phase sequence, reverse  
error is detected  
phase, and phase loss.  
2.Check outdoor unit boards.  
3.Check high-pressure switch.  
4.Check high-pressure switch circuit wiring.  
P03  
P04  
Abnormal discharge temperature  
(over specified value)  
OFF  
Indicated when an 1.Check freezing cycle (gas leakage).  
error is detected  
2.Failure of electronic expansion valve  
3.Check piping sensor (Td).  
Failure of high-pressure protection circuit OFF  
(Temperature over specified value  
detected by TE sensor)  
Indicated when an 1.Freezing cycle overload operation  
error is detected  
2.Check outdoor unit TE sensor.  
3.Check outdoor unit CDB board.  
4.Check high-pressure switch and circuit.  
High-pressure switch (normal models)  
P22  
Failure of outdoor unit DC fan  
OFF  
Indicated when an 1.Position detect error  
error is detected 2.Overcurrent protection circuit  
operation of outdoor unit fan driver  
3.Outdoor unit fan lock  
4.Check outdoor unit CDB board.  
P26  
P29  
F04  
F06  
F08  
Inverter overcurrent protection  
circuit activated (short time)  
Main circuit short voltage operation  
OFF  
OFF  
Indicated when an 1.Operation stops soon when restarted.  
error is detected  
... Compressor partial short-circuit  
2.Check IPDU for improper wiring.  
Failure of IPDU position detect  
circuit  
Indicated when an 1.The circuit is activated even after  
error is detected  
compressor’s 3P connector is  
disconnected. ...Replace IPDU.  
Improper mounting, disconnection OFF  
or short-circuit of outdoor unit temp.  
sensor TD  
Indicated when an 1.Check TD.  
error is detected  
2.Check outdoor unit CDB board.  
Improper mounting, disconnection OFF  
or short-circuit of outdoor unit temp.  
sensor TE, TS  
Indicated when an 1.Check TE, TS.  
error is detected  
2.Check outdoor unit CDB board.  
Improper mounting, disconnection Operation  
Indicated when an 1.Check TO.  
or short-circuit of outdoor unit  
continued  
error is detected  
2.Check outdoor unit CDB board.  
outside air temp. sensor TO  
*1 ROA-P*** is not detected by 1HS models.  
Fan continues rotating in a failure mode detected by outdoor unit because there is no communication between outdoor unit  
and follower indoor unit in twin group.  
34 –  
Troubleshooting (Continued)  
2. Troubleshooting by Remote Controller Check Indication  
Main Remote Controller (RBC-AMT31E)  
(1) Checking  
When an error occurs in the air conditioner, a  
check code and an indoor unit number appear  
on the LCD of remote controller.  
Check code is displayed only during  
operation.  
If indication disappears, check errors following  
Faulty indoor unit  
No.  
Check code  
“Checking Error Log” below.  
(2) Checking Error Log  
When an error occurs in the air conditioner, error log can be checked following the steps below. Up to 4  
errors are memorized.  
Error log can be checked in both operation ON and OFF states.  
Step  
Operation  
Press [SET] and [TEST] at the same time for 4 seconds or more. The LCD indication changes as shown below.  
Indication of “SERVICE CHECK” shows that the unit is in the error log mode.  
• Code No. “01” (order of error log) is displayed.  
A
• A check code is displayed.  
• The address of faulty indoor unit is displayed in the UNIT No. area.  
Each pressing of TEMP. /buttons displays stored error log sequentially.  
Check code “01” shows the latest error, and “04” shows the oldest.  
B
C
Note  
Do not press [CL] as this button clears entire error log of indoor unit.  
After checking the error log, press [TEST] to return to the normal indication.  
Numbers appearing on the LCD  
<Seven-segment display>  
Hexadecimal number  
35 –  
TCC-LINK Central Control Remote Controller (TCB-SC642TLE)  
(1) Checking  
When an error occurs in the air conditioner, a  
check code and an indoor unit number appear on  
the LCD of remote controller.  
Indication of unit number  
Indication of alarm  
CHECK  
UNIT No.  
Check code is displayed only during operation.  
If indication disappears, check errors following  
“Checking Error Log” below.  
Alternate blinking  
R.C.  
No.  
(2) Checking Error Log  
When an error occurs in the air conditioner, error log can be checked following the steps below. Up to 4  
errors are memorized.  
Error log can be checked in both operation ON and OFF states.  
APress [SET] and [TEST] at the same time for 4 seconds or more.  
BIndication of “SERVICE CHECK” and UNIT No. “01” appear.  
CWhen selecting a group number (blinking), a unit number and the latest error log, if any, are displayed  
alternately.  
* Temperature setting is disabled at this time.  
Indication of unit number  
UNIT No.  
Indication of alarm  
CHECK  
Alternate blinking  
R.C.  
No.  
DTo check other errors, choose a code (01 to 04) with TEMP. /buttons.  
ETo check error log of another group, choose a group number with / buttons.  
Do not press [CL] as this button clears entire error log of the selected group.  
FPress [TEST] to finish the service check.  
36 –  
Troubleshooting (Continued)  
3. Troubleshooting for Each Check Code  
Check code  
Check code name  
Possible causes  
AImproper R/C wire connection  
BFailure of I/U power supply  
CFailure of I/U board  
[E01]  
(New code)  
I/U - R/C communication error  
(detected by R/C)  
DInvalid R/C address setting  
EFailure of R/C board  
Are R/C wires  
A/B correct?  
NO  
Correct R/C wires.  
YES  
Improper harness  
connection from  
I/U terminal block?  
YES  
Correct connector connection.  
Check circuit wiring.  
NO  
NO  
NO  
Group control  
operation?  
YES  
Are all indoor  
units powered ON?  
Check I/U power connection  
(power off and on).  
YES  
Check I/U boards.  
Replace defective board.  
Is R/C powered ON?A/B  
terminals: Approx. 18VDC  
NO  
YES  
Is “no header”  
set by double R/C?  
Correct one header/one follower.  
(R/C address connector)  
YES  
NO  
Check R/C board.  
Replace it if necessary.  
37 –  
Check code  
Check code name  
Possible causes  
[E02]  
(New code)  
R/C transmission error  
Signal transmission to indoor unit is  
disabled.  
* Not indicated on the central controller and outdoor unit 7-segment.  
Com. cable between  
R/C and I/U connected  
properly?  
NO  
Correct communication cable.  
YES  
Failure of R/C  
transmitter Replace R/C.  
Check code  
Check code name  
Possible causes  
No communication from R/C and communication adapter.  
[E03]  
I/U - R/C communication error  
(New code)  
(detected by I/U)  
Indoor unit (I/U) detects this error when it cannot receive signals from remote controller (R/C).  
Check communication wiring of R/C A and B.  
This code E03 is not displayed on the R/C because of communication error.  
This code is displayed on the TCC-LINK central controller.  
38 –  
Troubleshooting (Continued)  
Check code  
Check code name  
Possible causes  
[E04]  
(New code)  
I/U - O/U communication error  
(detected by I/U)  
AImproper connector connection between I/U and O/U  
BImproper wire connection between I/U and O/U  
CFailure of I/U or O/U board  
DCase thermo sensor ON  
EInvalid I/U board switch setting  
NO  
NO  
Does O/U work?  
Is group address set correctly?  
YES  
Check code “14”.  
Correct wires.  
YES  
NO  
NO  
Are 1/2/3 wires normal?  
YES  
Are connectors from I/U and  
O/U connected normally?  
Correct connector connection.  
YES  
NO  
NO  
Is I/U switch SW02  
setting correct? Bit 1, 2: OFF  
Correct switch setting on  
MCC-1510 board.  
YES  
Does voltage between  
I/U terminal 2 and 3 fluctuate?  
(0-140 VDC)  
Check MCC-1510 board.  
Replace it if necessary.  
* Measure within  
20 seconds  
from power on.  
Black  
White  
C
B
A
YES  
Is 280VDC  
NO  
Terminal block  
applied across IPDU main  
circuit capacitor?  
Replace IPDU.  
YES  
NO  
NO  
Is 280VDC supplied to  
CDB? (CN03)  
Replace IPDU.  
YES  
Is 7VDC supplied  
to CDB? Is CN06-CN800  
connection normal?  
Replace IPDU.  
Correct connector connection.  
YES  
NO  
NO  
Is case thermo sensor  
connected? (CN500)  
Correct connector connection.  
YES  
Check MCC-1510 board.  
Replace it if necessary.  
Check CDB. Replace it if  
necessary.  
Is case thermo sensor working?  
YES  
Check I/U boards.  
® Replace defective board.  
Check and correct refrigerant volume.  
39 –  
Check code  
Check code name  
Possible causes  
R/C header setting is duplicated.  
[E09]  
Duplication of R/C header  
(New code)  
Are 2 headers set  
by double R/C?  
YES  
Correct one header/one follower.  
(R/C address connector)  
NO  
Check R/C board.  
Replace it if necessary.  
Check code  
Check code name  
Possible causes  
[E18]  
Communication error between header AImproper wire connection between I/U  
(New code)  
and follower I/U  
BImproper wire connection between I/U and O/U  
CFailure of I/U board  
DInvalid I/U board switch setting  
NO  
Are A/B wires  
normal?  
Correct R/C wire connection.  
YES  
Improper harness  
connection from I/U terminal  
block?  
YES  
NO  
Correct connector connection.  
Check circuit wiring.  
NO  
Is I/U switch SW02  
setting correct?  
Bit 1, 2: OFF  
Correct switch setting on  
MCC-1510 board.  
YES  
NO  
NO  
NO  
Group control operation?  
YES  
Are all indoor  
units powered ON?  
Check I/U power connection  
(power off and on).  
YES  
Twin or triple control?  
YES  
Improper signal  
connection between I/U  
and O/U?  
YES  
Correct signal wire connection  
between I/U and O/U.  
NO  
Check MCC-1510 board.  
Replace it if necessary.  
40 –  
Troubleshooting (Continued)  
Check code  
Check code name  
Possible causes  
[F01]  
I/U sensor TCJ error  
I/U sensor TCJ error  
(New code)  
Is TCJ connector  
CN102 connected  
normally?  
NO  
Correct connector connection.  
YES  
Is TCJ resistor  
characteristic  
normal?  
NO  
Replace sensor TCJ.  
* See I/U temp. sensor characteristics-2.  
YES  
Check I/U main board.  
Replace it if necessary.  
Check code  
Check code name  
Possible causes  
Sensor TC open or short-circuit  
[F02]  
I/U sensor TC error  
(New code)  
Is TC connector  
CN101 connected  
normally?  
NO  
Correct connector connection.  
YES  
Is TC resistor  
characteristic  
normal?  
NO  
Replace sensor TC.  
* See I/U temp. sensor characteristics-2.  
YES  
Check I/U boards.  
Replace defective board.  
41 –  
Check code  
Check code name  
Possible causes  
Sensor TA open or short-circuit  
[F10]  
I/U sensor TA error  
(New code)  
Is TA connector  
CN104 connected  
normally?  
NO  
Correct connector connection.  
YES  
Is TA resistor  
characteristic  
normal?  
NO  
Replace sensor TA.  
* See I/U temp. sensor characteristics-1.  
YES  
Check MCC-1510 board.  
Replace it if necessary.  
Check code  
Check code name  
Possible causes  
[F29]  
Other indoor unit errors  
Failure of I/U board  
(New code)  
This is an error of non-volatile EEPROM IC10 on the indoor unit board, which occurs during  
operation. Replace the service board.  
* If EEPROM is not mounted at power on or if no data can be read/written from/in the EEPROM,  
auto address mode is repeated. At this time, the AI-NET central controller indicates code “97”.  
(About 3 minutes)  
(Power on)  
(About 1 minutes)  
“SETTING” appears  
on the R/C.  
Reboot  
(reset)  
LED (D02) on the I/U  
board blinks for about  
10 seconds (1Hz).  
“SETTING” disappears.  
(Repeated)  
42 –  
Troubleshooting (Continued)  
Check code  
Check code name  
Possible causes  
[F31]  
O/U EEPROM error  
AFailure of O/U power supply (voltage, noise, etc.)  
(New code)  
BFailure of O/U CDB board.  
Check power voltage.  
Improve power lines.  
Check external noise.  
Is O/U free from  
power fluctuation?  
NO  
YES  
Check CDB board.  
Check code  
[E08][L03][L07][L08]  
(New code/old code)  
E08: I/U number duplicated  
L03: Multiple header I/U under group control  
L07: One or more group address “individual” under group control  
L08: I/U group address not set (99)  
When any of these codes is detected at power on, the unit enters auto address setting mode  
automatically. (No code is indicated.)  
However, if any of these codes is detected in the auto address setting mode, a check code is  
displayed in some cases.  
Check code  
Check code name  
Possible causes  
Indoor unit capacity not set  
[L09]  
Indoor unit capacity not set  
(New code)  
NO  
Is indoor unit  
capacity set?  
Set I/U capacity data. (DN=11)  
YES  
Check MCC-1510 board.  
Replace it if necessary.  
43 –  
Check code  
Check code name  
Possible causes  
[L20]  
Duplication of central control address  
Central control address is duplicated.  
(New code)  
Are U3/U4  
communication  
cables connected  
normally?  
NO  
Correct cable connection.  
YES  
When a unit  
NO  
connected to U3/U4  
is in a group, is it set  
to header unit?  
Set the connected unit to  
header unit.  
YES  
Check and correct I/U address,  
central control address.  
Check code  
Check code name  
Possible causes  
When an external alarm is input  
[L30]  
I/U external interlock  
(New code)  
NO  
Is external device  
connected to CN80?  
Check I/U boards.  
Replace defective board.  
YES  
NO  
Check external device.  
Replace it if necessary.  
Is external device  
working normally?  
YES  
Check possible error  
causes.  
44 –  
Troubleshooting (Continued)  
Check code  
Check code name  
Possible causes  
AFailure of fan motor connector  
[P12]  
Malfunction of I/U fan motor  
(New code)  
BFailure of fan motor  
CFailure of I/U board  
DFailure of cross flow fan shaft  
Turn OFF the breaker.  
Turn it ON 10 seconds  
after.  
Is min.1VDC present  
NO  
NO  
NO  
Does fan stop with  
operation OFF?  
between CN210 pin  
and C  
Replace I/U fan  
motor.  
E
?
YES  
YES  
Start cooling with LOW  
fan speed.  
Is min. 280VDC present  
between CN210 pin  
NO  
Does fan rotate?  
YES  
A
and C  
?
YES  
Stop operation and turn OFF  
breaker. Disconnect CN210,  
turn ON breaker again, and  
then stop operation using R/C.  
Is min. 15VDC present  
between CN210 pin  
Change fan speed to HH.  
NO  
D
and C with  
motor connected?  
YES  
Is min. 280VDC present  
between CN210 pin  
NO  
Replace I/U MCC-  
1510 board.  
D
and  
C
?
YES  
Operate I/U (except  
heating) by R/C. Is min.  
1VDC present between  
Stop operation and unplug  
AC cord. Disconnect  
CN210, plug in AC cable  
again, and then stop  
operation using R/C.  
NO  
CN210 pin  
E
and  
C
?(Measure within  
15 seconds.)  
NO  
NO  
Does fan speed  
increase?  
YES  
Operate I/U (except  
heating) by R/C. Is min.  
1VDC present between  
NO  
YES  
Does cross flow fan  
rotate normally by hand?  
CN210 pin  
E
and  
C
? (Measure within  
15 seconds.)  
YES  
YES  
Repair cross flow  
fan shaft.  
Rotate the fan by hand with  
operation OFF. Is 0 to  
15VDC (rev return signal)  
generated between CN210  
NO  
pin  
F
and  
C
?
Fan motor is normal.  
YES  
45 –  
Check code  
Check code name  
Possible causes  
AFailure of fan motor connector  
[P12]  
Malfunction of I/U fan motor  
(New code)  
BFailure of fan motor  
CFailure of I/U board  
DFailure of cross flow fan shaft  
When AC cord is plugged  
in, I/U fan starts rotating.  
P. C. board  
Check the fan motor output DC voltage on the I/U board.  
(Blue)  
(Yellow)  
(White)  
(Black)  
Check voltage on the motor connector CN210 pin C(GND,  
black) and pin E(+V line, yellow) while fan is rotating.  
Yellow  
1.0VDC or  
higher  
Below 1.0VDC  
Black  
Failure of I/U  
MCC-1510 board  
Failure of I/U fan  
motor  
(Red)  
46 –  
Troubleshooting (Continued)  
Check code  
Check code name  
Possible causes  
[P31]  
Other I/U errors  
When an error occurs with other units in the group  
(New code)  
(Group follower I/U error)  
When header unit detects E03, L03, L07 or L08 during group operation, “P31” is indicated on follower units in the group and  
their operation stops. No code or alarm log is displayed on the R/C.  
47 –  
Check code  
Check code name  
Possible causes  
[C05], [C06]  
(Central controller)  
TCC-LINK central control  
communication error  
TCC-LINK central control communication error  
Is I/U  
powered ON?  
NO  
NO  
Power ON.  
YES  
Is harness from I/U  
terminal block  
connected properly?  
Correct connector connection.  
YES  
Can I/U be  
operated by R/C  
individually?  
NO  
NO  
YES  
Are U3/U4 com.  
cables. normal?  
*1  
Correct com. cable.  
* Check wrong connection, disconnection, and  
shield wire’s contact with com. cable.  
YES  
When a unit  
connected to U3/U4  
is in a group, is it  
set to header  
unit?  
NO  
NO  
Set the connected unit to  
header unit.  
YES  
Free from noise?  
YES  
Remove noise source.  
Can other units  
controlled by  
central R/C? Is I/U  
operating status  
reflected?  
NO  
Check central controller.  
Replace it if necessary.  
YES  
Is the code [C05]?  
NO  
YES  
NO  
Confirm normal connection of  
com. cable. Change connector  
connection CN40 to CN44  
(EMG) on I/U board.  
Is I/U onboard fuse  
F03 normal?  
YES  
Check I/U boards.  
Replace  
defective board.  
48 –  
Troubleshooting (Continued)  
Relationship Between Temperature Sensor Resistance and Temperature  
20  
10  
0
40  
Characteristic-1  
Characteristic-2  
Sensor TC, TCJ  
Sensor TA  
Resistance  
[k  
30  
]
Resistance  
[k  
]
20  
10  
0
10  
20  
30  
40  
-10  
0
10  
20  
30  
40  
50  
60  
70  
50  
Temperature  
Temperature  
[˚C]  
[˚C]  
Characteristic-3  
Sensor TE, TO, TS  
20  
10  
0
200  
Resistance  
[k  
Resistance  
[k  
(10°C or lower)  
]
]
(10°C or higher)  
100  
0
-10  
0
10  
20  
30  
40  
50  
60  
70  
Temperature [˚C]  
Sensor TD  
Characteristic-4  
20  
10  
0
200  
Resistance  
[k  
(50°C or lower)  
Resistance  
]
[k  
]
(50°C or lower)  
100  
0
50  
100  
Temperature  
[˚C]  
49 –  
9. HOW TO REPLACE SERVICE BOARD OF INDOOR UNIT  
Requirements When Replacing Service Board of Indoor Unit  
The non-volatile EEPROM (IC10) on the board of indoor unit stores important data such as model-specific type and capacity  
code (written during factory shipping) as well as system/indoor unit/group addresses set automatically/manually (written during  
installation). Therefore, observe the following procedure when replacing indoor unit service boards.  
After installation of indoor unit, check whether the settings are correct by checking indoor unit number and group header/  
follower unit setting, and also check cycle through a trial operation.  
[Replacement Procedures]  
Case 1  
When it is possible to power ON indoor unit before replacement and when wired R/C can read settings  
Reading EEPROM Data *1 (see page 51)  
Replacing Service Board and Power ON *2 (see page 51)  
Writing Setting Data in EEPROM *3 (see page 52)  
Power ON reset (for all indoor units connected to R/C in group control mode)  
Case 2  
When it is impossible to power ON indoor unit before replacement or when wired R/C is disabled  
due to failure of power supply circuit (board failure)  
Replacing EEPROM (For layout of components and replacement, see page 49.)  
Remove the EEPROM on the board, and replace it with the EEPROM on the service board.  
Replacing Service Board and Power ON *2 (see page 51)  
Reading EEPROM Data *1 (see page 51)  
If data cannot be read, go to Case 3.  
Replacing EEPROM (For layout of components and replacement, see page 49.)  
Replace EEPROM again. (Mount the original EEPROM on the service board.)  
Replacing Service Board and Power ON *2 (see page 51)  
Writing Setting Data in EEPROM *3 (see page 52)  
Power ON reset (for all indoor units connected to R/C in group control mode)  
Case 3  
When the EEPROM before replacement is defective, and the settings cannot be read  
Replacing Service Board and Power ON *2 (see page 51)  
Writing Setting Data in EEPROM (using customer information) *3 (see page 52)  
Power ON reset (for all indoor units connected to R/C in group control mode)  
50 –  
HOW TO REPLACE SERVICE BOARD OF INDOOR UNIT (Continued)  
*1 Reading EEPROM Data  
(Read EEPROM data that was updated at site in addition to factory setting.)  
1
1) Press  
* In the group control mode, the header unit number is displayed first.  
At this time, code (DN) is displayed, and the fan of the selected indoor unit runs, its flap swings,  
and the OPERATION, TIMER, and PREPARING lamps blink.  
,
, and  
on the R/C simultaneously for 4 seconds or more.  
(see page 52)  
2
2) Each pressing of  
indicates indoor unit number in the group sequentially.  
Specify indoor unit number whose board is to be replaced.  
3
3) Each pressing of TEMP.  
4) Change DN from to  
buttons increments or decrements DN.  
first. (Setting of filter sign ON time)  
Write down the setting data displayed.  
5) Change DN with TEMP.  
buttons, and write down the setting data displayed.  
6) Repeat step 5) in the same way, and write down the important setting data shown in the table  
(page 49).  
* DN =  
to  
. DN does not always shift sequentially.  
to return the operation mode to normal OFF.  
6
7) After writing down setting data, press  
(It takes about one minute until R/C operation is enabled.)  
Essential DN codes  
(1) Indoor unit capacity is necessary for fan speed setting.  
(2) If refrigerant line address, indoor unit address or group  
address differs from that before replacement, the unit enters  
auto address setting mode, which requires manual re-setting  
for group operation including twin or triple operation.  
DN  
Description  
11 Indoor unit capacity  
12 Refrigerant line address  
13 Indoor unit address  
14 Group address  
*2 Replacing Service Board and Power ON  
1) Replace the board with a service board.  
Reflect the jumper wire (cut) setting and switch setting on the board in the service board. For switch  
setting and component layout, see page 53.  
2) Power ON the indoor unit in either way of the following according to system configuration.  
a) Single (individual) operation  
Power ON the indoor unit with no operation.  
i) Go to *3 when auto address setting mode ends (about 5 minutes).  
(Refrigerant line address=1, indoor unit address=1, and group address=0 are set automatically.)  
ii) Press  
,
, and  
on the R/C simultaneously for 4 seconds or more ( ) to cancel auto  
1
address setting mode, and then go to *3. (UNIT No.  
is indicated.)  
b) Group operation (including twin/triple/double twin)  
Power ON the indoor unit whose service board is replaced in either way of the following.  
i) Power ON the indoor unit only whose service board is replaced in the same way as a) i) and ii)  
above.  
There must be remote controller connection. If not, operation *3 is disabled.  
ii) Power ON multiple indoor units including the unit whose service board is replaced.  
Twin, triple, double twin: One system only  
• Group control: All indoor units  
Go to *3 when auto address setting mode ends (about 5 minutes).  
* Header indoor unit may change depending on auto address setting. The refrigerant line address and  
indoor unit address of the indoor unit whose service board is replaced are automatically set to an  
address that is not used in other units. It is recommended that you take a memo beforehand that to  
which refrigerant system the indoor unit belongs and that the indoor unit is header or follower unit in  
the group.  
51 –  
*3 Writing Setting Data in EEPROM  
(The data of the EEPROM on the service board is the factory setting data.)  
1
1) Press  
,
, and  
on the R/C simultaneously for 4 seconds or more.  
(see page 52)  
* In the group control mode, the header unit number is displayed first.  
(If auto address setting mode is canceled in 2-2) a) ii) above, UNIT No.  
is indicated.)  
At this time, code (DN)  
is displayed, and the fan of the selected indoor unit runs, its flap swings,  
and the OPERATION, TIMER, and PREPARING lamps blink.  
2
2) Each pressing of  
indicates indoor unit number in the group sequentially.  
Specify indoor unit number whose board is replaced.  
(This operation is disabled if UNIT No. is  
.)  
3
3) Each pressing of TEMP.  
buttons increments or decrements DN.  
4) Set the indoor unit capacity first.  
The factory setting data is written in the EEPROM.  
i) Change DN to  
ii) Set the indoor unit capacity with TIME  
with TEMP.  
buttons.  
buttons.  
<Remote Controller>  
4
(for  
RBC-AMT21E  
example, “0012” for 80 class) ... See the table (page 53).  
iii) Press  
iv) Press  
Indication on the LCD shows normal operation.  
6
to return the operation mode to normal OFF.  
(It takes about one minute until R/C operation is enabled.)  
SETTING  
5) Write the data set after installation (such as address) in the EEPROM.  
Repeat steps 1) and 2) above.  
6) Specify DN  
sign ON time)  
with TEMP.  
buttons. (Setting of filter  
7) Check the displayed data comparing the content written down in *1  
(page 49).  
i) If the data is incorrect, change it with TIME  
buttons to the  
4
2
3
6
5
data of the memo, and then press  
normal operation.  
Indication on the LCD shows  
1
ii) No operation is required for the same data.  
8) Change DN with TEMP.  
buttons.  
RBC-AMT31E  
In the same way as above, check the displayed data comparing the  
content of the memo.  
If the data is incorrect, change it to the data of the memo.  
9) Repeat steps 7) and 8) above.  
10) When the setting is completed, press  
to return the operation  
6
mode to normal OFF.  
(It takes about one minute until R/C operation is enabled.)  
* DN =  
updated and  
restored with  
to  
. DN does not always shift sequentially. Even if data is  
button is pressed by mistake, the previous data can be  
button unless DN is changed.  
3
5
4
6
1
2
52 –  
HOW TO REPLACE SERVICE BOARD OF INDOOR UNIT (Continued)  
Example of Setting Contents to be Written Down (Code Table)  
DN  
Item  
Memo  
Factory setting  
0001: 150 hours  
01 Filter sign ON time  
02 Filter contamination level  
03 Central control address  
06 HEAT intake temp. shift  
0C PREPARING indication selection  
0F COOL only  
0000: Average  
0099: Not determined  
0002: +2°C  
0000: Normal  
0000: Heat pump type air conditioner  
0008: Wall type  
10 Type  
Must be set to 0008  
11 Indoor unit capacity  
Depends on capacity type  
0099: Not determined  
0099: Not determined  
0099: Not determined  
0003: 3°C (Ts 1.5)  
0000: Not provided  
0002: External alarm input  
0000: Thermo output ON  
0000: Operation input  
0000: Disabled  
12 Refrigerant line address  
13 Indoor unit address  
14 Group address  
1E Temp. range at COOL/HEAT auto switching control  
28 Auto restart after power failure  
2A Option/alarm input (CN80) selection  
2b Thermo output (T10-C) selection  
2E HA terminal (T10-A) selection  
31 Ventilation fan (single operation)  
32 Sensor selection  
0000: Unit sensor  
60 Timer setting (wired R/C)  
69 Flap setting for cooling  
0000: Available  
0000: Normal  
8b Correction of feeling of strong heating  
0000: Not provided  
Indoor unit capacity  
Code “11”  
Onboard Component Layout  
<MCC-1510>  
Model  
Invalid  
40 type  
45  
Setting data  
0000*  
0006  
0007  
50  
0008  
SW02  
ON  
1
2
SW01  
56  
0009  
ON  
2
1
DIP switches  
(SW01, SW02)  
63  
0010  
J01  
71  
0011  
80  
0012  
* Default value of EEPROM on the  
service board  
IC10  
EEPROM (IC10)  
Mount EEPROM aligning its notch with  
the notch of IC socket.  
Notch  
DIP switch setting  
IC socket  
Notch  
EEPROM  
Setting  
AIK-AP**1H  
Factory setting  
Bit 1  
Bit 2  
Bit 1  
Bit 2  
Terminating resistor (for central control)  
Selection of R/C A or B  
*1  
*1  
OFF (no resistor)  
OFF (A is selected)  
OFF (custom models)  
OFF  
SW01  
SW02  
Selection of custom or multiple  
Not used  
OFF  
OFF  
*1: Set to the state before replacement  
53 –  
11  
10. ON-SITE SETTING AND OTHERS  
1. Indoor Unit  
1.1 Trial Operation Setting by Remote Controller only.  
The lamps on the unit blink during trial operation.  
<Wired remote controller>  
1
Press  
on the R/C for 4 seconds. When “TRIAL OPERATION” appears on the LCD, press  
.
• “TRIAL OPERATION” appears on the LCD during trial operation.  
Trial operation disables temperature control, but allows fan speed control.  
• An instruction of fixed frequency is issued for cooling and heating of trial operation.  
• Alarm detection is performed as usual.  
The trial operation mode must be used for its original purpose only, because it stresses the air conditioner.  
Choose COOL or HEAT mode only for trial operation.  
• (Note) Outdoor unit does not run about 3 minutes after power on or operation stop.  
2
3
Repress  
after trial operation and confirm that “TRIAL OPERATION” disappears from the LCD.  
Wired remote controller has 60-minute timer reset function to prevent continuous trial operation.  
Checking wiring and piping of indoor/outdoor units  
1. Open the front panel of the indoor unit.  
2. Press [TEMPORARY] button for 10 seconds. The unit enters forcible cooling mode with a sound  
“pi”. COOL operation starts forcibly about 3 minutes later. Check whether cool air is discharged. If  
COOL operation does not start, recheck the wiring.  
3. Repress [TEMPORARY] for about one second to stop trial operation. The vertical airflow flap  
closes and the operation stops.  
Checking signal transmission from R/C  
1. Press [ON/OFF] on the R/C to check for normal operation using R/C.  
To enter AUTO mode, press [TEMPORARY] once  
for about one second.  
For forcible cooling, press [TEMPORARY] for 10  
seconds or more.  
• COOL operation specified by R/C may not start  
depending on temperature conditions.  
Use forcible cooling operation to check wiring and  
piping of indoor/outdoor units.  
[TEMPORARY]  
button  
54 –  
ON-SITE SETTING AND OTHERS (Continued)  
1.2 Forcible Defrost Setting by Remote Controller (wired R/C only)  
Preliminary operation  
1
Press  
,
, and  
at the same time for 4 seconds or more in the OFF mode.  
In the group control mode, the header unit number is displayed first.  
2
Each pressing of  
indicates indoor unit number in the group sequentially.  
Choose the main indoor unit (connected to the outdoor unit) for which forcible defrosting is to be  
performed.  
The fan and flap of the selected indoor unit start working.  
3
4
5
6
Specify DN “8C” with  
Set data 0001 with  
buttons.  
buttons. (Factory setting: 0000)  
Press  
Press  
Indication on the LCD shows normal operation.  
to return the operation mode to normal OFF.  
Execution procedure  
• Press  
on the R/C.  
• Choose HEAT operation mode.  
• After a while, a forcible defrosting signal is transmitted to the outdoor unit. Upon receiving the signal, the  
outdoor unit starts defrosting. It takes up to 12 minutes.  
• On completion of defrosting, the indoor unit restart HEAT operation.  
1
To reexecute defrosting, repeat steps from step  
above.  
Once forcible defrosting is performed, the above setting for forcible defrosting is reset.  
1.3 Indication of Onboard LEDs  
1. D02 (red)  
Lights up by the control of main microcomputer when the indoor unit is powered on.  
Blinks at intervals of one second (0.5-second on and off) when EEPROM is not mounted or write  
error occurs.  
Blinks at intervals of 10 seconds (5-second on and off) in the DISP mode. (CN72 short-circuited at  
power on)  
Blinks at intervals of 2 seconds (1-second on and off): Applicable unit in the EEPROM setting  
(address, function selection, etc.) mode  
2. D203 (red)  
Lights up by hardware control when power is supplied to remote controller.  
55 –  
1.4 JRA Capacity Measurement Mode (wired R/C only)  
Preliminary operation  
1
Press  
,
, and  
at the same time for 4 seconds or more in the OFF mode.  
In the group control mode, the header unit number is displayed first.  
2
Each pressing of indicates indoor unit number in the group sequentially.  
Choose the main indoor unit (connected to the outdoor unit) for which this control is to be performed.  
The fan and flap of the selected indoor unit start working.  
3
4
Specify DN “91” with  
buttons.  
buttons. (Factory setting: 0000)  
Set the following data with  
Data  
Rating 0001  
Middle 0002  
5
6
Press  
Press  
Indication on the LCD shows normal operation.  
to return the operation mode to normal OFF.  
Operation Fan speed Setting temp. Flap position  
Use this mode to measure JRA capacity.  
Use this mode under the conditions of JIS B8615-1  
Perform the settings in the table by remote  
Cooling  
Heating  
Quick high  
Quick high  
Auto  
18°C  
29°C  
23°C  
24°C  
Horizontal angle  
Horizontal angle  
Horizontal angle  
Horizontal angle  
Cooling rating  
Heating rating  
Cooling middle  
Heating middle  
.
Auto Cooling  
Auto Cooling  
controller  
Execution procedure  
• Press on the R/C.  
.
Auto  
1
To reexecute JRA capacity measurement, repeat steps from step  
Once this measurement is completed, the above setting is reset.  
above.  
1.5 Function Select Setting (wired R/C only)  
Perform the following steps in the operation OFF mode.  
1
Press  
,
, and  
at the same time for 4 seconds or more in  
the OFF mode.  
In the group control mode, the header unit number is displayed  
first.  
2
Each pressing of  
sequentially.  
indicates indoor unit number in the group  
Choose the main indoor unit (connected to the outdoor unit) this  
function is to be performed.  
The fan and flap of the selected indoor unit start working.  
3
5
4
Specify DN with  
buttons.  
3
4
6
1
2
Operation procedure  
END  
1
2
3
4
5
6
Set the setting data with  
buttons.  
5
Press  
Indication on the LCD shows normal operation.  
2
To change the selected indoor unit, go to  
.
To change the item to be set, go to  
.
3
6
Press  
to return the operation mode to normal OFF.  
56 –  
ON-SITE SETTING AND OTHERS (Continued)  
Function Select Code (DN) Table  
DN  
01  
Item  
Description  
0001: 150H  
Factory setting  
0001: 150H  
Filter sign ON time  
0000: None  
0002: 2500H  
0004: 10000H  
0003: 5000H  
0005: Clogging sensor used  
02  
03  
06  
Filter contamination level  
Central control address  
HEAT intake temp. shift  
0000: Average  
0001: Heavy  
0000: Average  
(half of standard time)  
0001: No. 1  
0099: Not determined  
-
0064: No. 64  
0099: Not determined  
0002: +2 °C  
0000: No shift  
0001: +1 °C  
0002: +2 °C  
-
0010: +10 °C  
(Up to +6 recommended)  
OC  
OF  
PREPARING indication selection  
COOL only  
0000: PREPARING indicated 0001: No indication  
0000: PREPARING  
indicated  
0000: Heat pump  
0001: COOL only  
(No “AUTO”, “HEAT”  
0000: Heat pump  
indication)  
10  
11  
Type  
0000: (Ceiling panel 1)  
0000: Not determined  
0001 (ceiling panel 4) -  
0037  
0008: Wall type  
Indoor unit capacity  
0001 - 0034  
Depends on capacity  
type  
12  
13  
14  
Refrigerant line address  
Indoor unit address  
Group address  
0001: No. 1  
-
-
0030: No. 30  
0099: Not determined  
0099: Not determined  
0099: Not determined  
0001: No. 1  
0064: No. 64  
0000: Individual  
0001: Group header  
0002: Group follower  
1E  
Temp. range at COOL/HEAT auto  
switching control  
0000: 0deg  
(Switching at set temperature (data)/2)  
-
0010: 10deg  
0033: 3deg (Ts 1.5)  
28  
2A  
Auto restart after power failure  
0000: Not provided  
0001: Provided  
0000: Not provided  
Option/alarm input (CN80)  
selection  
0000: Filter input  
0002: External alarm input  
0001: Alarm input  
0002: External alarm  
input  
2b  
2E  
Thermo output (T10-3) selection  
0000: I/U thermo sensor ON 0001: O/U compressor ON  
output  
0000: I/U thermo  
sensor ON  
HA terminal (T10-1) selection  
0000: Normal (JEMA)  
0002: Fire alarm input  
0001: Card input  
0000: Normal  
(HA terminal)  
31  
32  
60  
69  
8b  
Ventilation fan (single operation)  
Sensor selection  
0000: Disabled  
0001: Enabled  
0000: Disabled  
0000: Unit sensor  
0000: Available  
0000: Normal  
0000: Unit sensor TA  
0000: Available  
0000: Normal  
0001: R/C sensor  
0001: Unavailable  
0001: Down allowed  
0001: Provided  
Timer setting (wired R/C)  
Flap setting for cooling  
Correction of feeling of strong  
heating  
0000: Not provided  
0000: Not provided  
57 –  
1.6 Wiring and Setting for Remote Controller  
Double R/C control (when controlling by two remote controller switches)  
This control is provided to control one or more indoor units by two remote controllers. Up to 2 remote  
controllers can be installed.  
No setting is required when using in combination with a wireless remote controller .  
Controlling one indoor unit by 2  
remote controllers  
R/C switch R/C switch  
(header)  
Option  
A B  
(follower)  
Option  
A B  
R/C wiring (on-site arrangement)  
R/C wiring terminals  
A B  
Indoor unit  
1 2 3  
1 2 3  
Outdoor unit  
Setting  
This control is provided to control one or more indoor units by two remote controllers.  
Up to 2 remote controllers can be installed.  
Remote controller (back, inside)  
<Wired remote controller>  
1
2
Setting to use a wired remote controller  
as follower R/C:  
Change the setting of DIP switch on the  
back of R/C switch to “R/C follower” as  
shown in the figure.  
R/C follower  
R/C header  
1
2
DIP switch  
1
2
58 –  
ON-SITE SETTING AND OTHERS (Continued)  
1.7 Monitoring Function of Remote Controller Switch  
Calling indication of sensor temperature  
<Description>  
Calls the service monitor mode from the remote controller to  
monitor sensor temperatures of the remote controller, indoor units,  
and outdoor unit.  
<Procedure>  
1
Press  
and  
on the R/C simultaneously for 4 seconds or more  
to call the service monitor mode.  
“Service monitor” lights up and the header indoor unit number is  
displayed first, and then temperature of code “ ” is displayed.  
2
Choose a sensor number (code) you want to monitor with  
buttons.  
1
2
4
3
The following table lists sensor numbers.  
Code  
Data  
Code  
Data  
00 Room temp. under control *1  
01 Room temp. (R/C)  
60 Heat exchange temp. TE  
61 Outside air temp. TO  
62 Discharge temp. TD  
63 Intake temp. TS  
Returns to normal indication.  
Operation procedure  
02 Indoor unit intake temp.  
03 Indoor unit coil temp. TCJ  
04 Indoor unit coil temp. TC  
05 Indoor unit coil temp. TC1  
1
2
3
4
64  
65 Heatsink temp. THS  
*1 Header indoor unit only under group control  
3
4
Choose an indoor unit you want to monitor with  
units and outdoor unit in the same control group.  
button to monitor sensor temperatures of indoor  
Press  
to return to the normal indication.  
59 –  
Calling error log  
<Description>  
Calls past errors.  
<Procedure>  
1
Press  
and  
on the R/C simultaneously for 4 seconds or more  
to call the service check mode.  
“Service check” lights up and code  
the latest error.  
is displayed first to display  
The faulty indoor unit number and error content are displayed.  
2
3
To monitor other errors, change error log number (code) with  
buttons.  
Code  
(latest) Code  
(oldest)  
2
3
1
Note) Up to 4 errors are memorized in the error log.  
Returns to normal indication.  
Operation procedure  
Press  
to return to the normal indication.  
1
2
3
<REQUIREMENT>  
Do not press  
as this button clears entire error log of indoor unit.  
60 –  
ON-SITE SETTING AND OTHERS (Continued)  
<Group Control Operation>  
Group control allows operation control of up to 8 indoor units using one remote controller. It includes twin,  
triple, and double twin controls with one outdoor unit.  
The indoor unit connected to outdoor unit controls room temperature according to the R/C setting.  
<An example of system>  
O/U  
I/U  
O/U  
I/U  
O/U  
I/U  
O/U  
O/U  
Header  
2-1  
I/U  
I/U  
I/U  
1-1  
3-1  
3-2  
4-1  
7-1  
8 units maximum  
R/C  
(1) Scope of R/C indication  
The indoor unit setting range (operation mode/fan speed/temperature) set in the header unit is  
reflected in the remote controller.  
ADo not set a concealed duct high static pressure type (AID-P***1H) for header unit.  
• If the type is set as header unit, settings are as follows.  
Operation mode: [Auto cooling/heating], [HEAT], [COOL] or [FAN] without [DRY]  
Fan speed  
: [HH]  
• In the DRY operation mode, FAN mode is not available for duct models.  
BDo not set a “COOL only” model for header unit.  
• [Auto cooling/heating] and [HEAT] operation modes are not available.  
(2) HA  
Both indoor and outdoor units are compatible with the remote control HA.  
Operation ON/OFF control for entire group is available.  
AMultiple HA inputs in one group are not allowed.  
(3) Address setting  
If there is no serial data communication between indoor and outdoor units at power on, the indoor unit  
is regarded as twin follower unit. (Each time of power on)  
... Recognition of twin header (main)/follower (sub) is carried out at each power on, and the result is  
not stored in the non-volatile memory.  
When performing auto address setting, power on the indoor units in a control group within 3 minutes.  
... If powered on after 3 minutes when auto address judgment is completed, the unit is rebooted  
and reenters auto address setting mode.  
AConnect 3 wires between indoor and outdoor units properly.  
BCheck refrigerant line address, indoor unit address, and group address of each unit.  
Regarding twin, triple, and double twin, in particular, check for one refrigerant line address for all  
units.  
CAn indoor unit number (refrigerant line address/group address), once it is set, is retained in  
principle unless it is not used for any other unit.  
61 –  
Indoor Unit Power ON Sequence  
• Indoor units that are not supplied with power  
are in waiting mode continuously.  
Power ON  
System start resets the waiting mode.  
• Rebooted if power is supplied halfway  
<By power supply unit>  
<Auto address judgment>  
*
Incorrect  
Checking group  
configuration  
Correct  
N
3 minutes  
passed  
* Correct group configuration means  
ANo duplication of indoor unit address  
BNo invalid indoor unit address  
CIndividual units and header/follower units  
are not mixed  
Y
DOnly one individual unit  
EOne header and one or more follower units  
in a group  
System start  
Auto address start  
(About one minute to end)  
<Initial communication>  
O/U model identification (10 seconds) (I/U)  
<<Notes on trial operation>>  
Check for normal connections of power  
cable, I/U-O/U serial wiring, and group wiring  
Power ON all indoor units within 3 minutes  
R/C operation available time (after power on)  
1)When address is correct: Approx. 50 seconds  
2)When auto address is used: Approx. 4-5 minutes  
Twin header/follower unit identification (I/U)  
Group configuration/flap information (R/C)  
R/C operation enabled  
(50 seconds after power on)  
<Periodic communication>  
Between indoor units (30-second cycle) (Header/follower)  
Within same piping (30-second cycle) (Twin main/sub)  
(Communication starts as soon as above status changes.)  
(Repeated)  
• The indoor unit powered on after auto address judgment under group control is rebooted (system reset), unless it does not  
receive data from the header unit or periodic communication within same piping within 120 seconds after power on.  
The sequence restarts from auto address judgment (checking group configuration).  
• If the previous address fixed and the header unit is powered on and is rebooted, the refrigerant line address of indoor units  
remains unchanged, but the header unit address may change.  
62 –  
ON-SITE SETTING AND OTHERS (Continued)  
3. Connections for Central Control  
3.1 Connections for TCC-LINK Central Control  
3.1.1 Functions  
Connect an indoor unit to the TCC-LINK central controller.  
3.1.2 Connection Diagram  
Central controller  
Indoor unit  
CN40  
Terminal block  
CN41  
(U3/U4)  
TCC-LINK  
Number of units  
Communication length : 2km  
: 64  
Terminal block  
(A/B)  
Remote controller  
3.1.3 TCC-LINK Connections  
How to make connections  
The terminal block for TCC-LINK central control is located at the lower right of the indoor unit.  
For details, see the installation manual of applicable central control remote control system.  
When using the terminal block, detach the front panel following the description on how to replace main  
components in this manual.  
Electric parts box  
Terminal block  
Cord clamp  
U4  
U3  
Terminal block for central control wiring (lower right part without front panel)  
63 –  
3.1.4 Wiring Specifications  
Number of wires  
2
Size  
Specification  
MVVS  
Up to 1000m: 1.25mm2 stranded wires  
Up to 2000m: 2.0mm2 stranded wires  
• A 2-wire non-polarity cable is used.  
• The cable length depends on each central control system.  
When used in a system including multiple air conditioners, the length includes the length of all wires  
between indoor and outdoor units on the side of multiple air conditioners.  
• Use 2-wire shield cable (MVVS) to protect from noise.  
• Joint shield wire between indoor units by closed-end terminating, and leave its end open with insulation  
processing.  
Make one-point grounding at the indoor unit side. Set the terminating resistors.  
(Central control for custom indoor units only)  
N
o
t
AJoint shield wire between indoor units by closed-end terminating.  
BLeave the end of the shield wire open with insulation processing.  
CMake one-point grounding at the indoor unit side.  
e
s
Central controller  
U1 U2  
Note B  
Outdoor  
unit  
1 2 3  
1 2 3  
1 2 3  
Note A  
Header  
1 2 3  
Follower  
1 2 3  
Indoor  
unit  
U3 U4  
1 2 3  
A B  
U3 U4  
A B  
A B  
R/C  
R/C  
R/C  
(Group operation)  
64 –  
ON-SITE SETTING AND OTHERS (Continued)  
3.1.5 Setting Onboard Switches  
Setting of terminating resistors is necessary for central control of custom indoor units only.  
• Use SW01 to set terminating resistors.  
Set terminating resistors for the indoor unit only with the smallest refrigerant line address.  
Central controller Central controller  
Central controller: Up to 10 units  
U1 U2  
U3 U4  
U1 U2  
U3 U4  
Refrigerant system 1  
Refrigerant system 2  
Refrigerant system 3  
Outdoor  
unit  
1 2 3  
1 2 3  
1 2 3  
Header  
Follower  
Indoor  
unit  
U3 U4  
1 2 3  
A B  
U3 U4  
1 2 3  
1 2 3  
A B  
A B  
TCC-LINK adapter (option)  
Required for custom  
indoor units other  
R/C wiring  
than wall type  
R/C  
R/C  
R/C  
Group operation (up to 8 indoor units)  
Refrigerant line address  
SW01 bit 1  
1
2
3
ON  
OFF  
OFF  
Remarks  
Bit 1 ON  
Factory setting  
Factory setting  
65 –  
3.1.6 Onboard Switch Setting Procedure  
1. Detach the front panel.  
2. Remove the drain guide, ground line, sensor TCJ, sensor TC, and motor leads.  
3. Remove the screws to detach the electric parts box.  
Sensor TCJ insertion position  
(Insert the sensor drawn from above electric parts.)  
Sensor TC insertion position  
(Insert the sensor drawn from under electric parts.)  
Fan motor connector insertion position  
Louver motor connector insertion position  
Electric parts box screw  
4. Detach the electric parts cover, and set SW01 bit 1 to ON.  
Do not touch bit 2 as it is for other setting.  
DB301  
C302  
L301  
1 : OFF  
2 : OFF  
1 : ON  
2 : OFF  
T301  
ON  
ON  
CN40  
C301  
1
2
1
2
Factory After setting  
setting change  
ON  
1
2
CN102  
CN213  
IC01  
BZ01  
2
1
O N  
SW02  
MCC-1510  
5. Install the removed parts by reversing steps 1 to 4.  
(Insert the sensors and motor leads firmly into their correct positions.)  
66 –  
ON-SITE SETTING AND OTHERS  
3.1.7 Setting Addresses  
Overview  
To connect custom air conditioners to the TCC-LINK central control system for central control/monitoring,  
addresses of connected indoor units must be set in the following procedure.  
Connections/wiring  
completed  
System power ON  
Auto address setting  
The system performs automatically after power on.  
Manual setting/change of refrigerant  
line addresses  
Change refrigerant line address.  
If auto address setting failed, set refrigerant line address manually.  
11  
* Refer to ADDRESS SETTING.  
Is group control (including twin/triple/  
double twin) going?  
NO  
YES  
Are all indoor units with central control  
function header unit (group address=1)?  
YES  
NO  
Re-set indoor units with central control function to header  
unit, and other indoor units to follower unit.  
11  
* Refer to ADDRESS SETTING.  
Central control address number  
setting  
* Refer to the manual of the central control system.  
END  
67 –  
(1) Manual setting/change of indoor unit refrigerant line addresses  
[In the case of 29 refrigerant systems or less (when multiple air conditioners are included,  
their number of refrigerant systems is also included)]  
Refrigerant address “1” is assigned to all indoor units except for group control by the auto address  
setting after system power on. Therefore, change refrigerant line address of each refrigerant system  
using the wired remote controller.  
Central  
controller  
Refrigerant Refrigerant  
Refrigerant  
system 3  
Refrigerant Refrigerant  
system 1  
system 2  
system 4  
system 5  
O/U  
O/U  
O/U  
O/U  
O/U  
I/U  
I/U  
I/U  
I/U  
I/U  
I/U  
R/C  
R/C  
R/C  
R/C  
Refrigerant line  
address  
Indoor unit  
address  
1
1
0
1
1
0
1
1
0
2
1
0
1
1
1
3
1
1
1
2
2
3
2
2
1
1
1
4
1
1
2
1
2
5
1
2
An example after auto address  
setting  
Group address  
Refrigerant line  
address  
Indoor unit  
address  
After changing refrigerant line  
address manually  
Group address  
11  
* For changing/setting refrigerant line addresses by wired remote controller, refer to ADDRESS  
SETTING.  
* Refrigerant line address must be unique for each refrigerant system.  
To perform central control in combination of multiple and custom air conditioners, set refrigerant  
line addresses different from those of multiple air conditioners.  
68 –  
ON-SITE SETTING AND OTHERS  
(2) Manual setting/change of indoor unit refrigerant line addresses  
[In the case of 30 refrigerant systems or more (when multiple air conditioners are included,  
their number of refrigerant systems is also included)]  
Regarding refrigerant systems up to No. 29, manual setting/change is the same as that on the  
previous page.  
• Refrigerant address “1” is assigned to all indoor units except for group control by the auto address  
setting after system power on. Therefore, change refrigerant line address of each refrigerant  
system using the wired remote controller.  
• Also change indoor unit addresses so as to avoid duplication of indoor unit numbers.  
Central  
controller  
Refrigerant Refrigerant  
system 30 system 31  
Refrigerant  
system 32  
Refrigerant Refrigerant  
system 33 system 34  
O/U  
O/U  
O/U  
O/U  
O/U  
I/U  
I/U  
I/U  
I/U  
I/U  
I/U  
R/C  
R/C  
R/C  
R/C  
Refrigerant line  
address  
Indoor unit  
address  
1
1
0
1
1
0
1
1
0
2
1
0
1
1
1
3
1
1
1
2
2
3
2
2
1
1
1
4
1
1
2
1
2
5
1
2
An example after auto address  
setting  
Group address  
Refrigerant line  
address  
Indoor unit  
address  
After changing refrigerant line  
address manually  
Group address  
11  
* For changing/setting refrigerant line addresses by wired remote controller, refer to ADDRESS  
SETTING.  
* Change refrigerant line address of all indoor units connected directly to the central controller to  
“30”.  
These indoor units are under twin or triple control, also change the refrigerant line address of  
follower indoor units to “30”.  
* Change indoor unit addresses so that they are not duplicated.  
69 –  
3.1.8 Central Control Address Number Setting  
To connect an indoor unit to the central control remote controller, an address number for central control  
must be set.  
An address number for central control is indicated as the refrigerant line number of the remote  
controller.  
1. Setting by Remote Controller on Indoor Unit Side  
<Procedure> Perform the following steps in the operation OFF  
mode.  
(Fig. 1)  
1
Press  
and  
on the R/C simultaneously for 4 seconds  
or more.  
When group control is going, UNIT No.  
is displayed first,  
and all indoor units in the group are selected. At this time, the  
fans of all the selected indoor units start running. (Fig. 1)  
Maintain this state without pressing  
.
For individual remote controllers without group control, a  
refrigerant line address and an indoor unit address are  
indicated.  
4
3
2
3
Specify code  
with  
buttons.  
2
1
5
Table 1  
Choose setting data with  
Table 1 shows setting data.  
buttons.  
Setting data Address No. for central control  
0001  
0002  
0003  
1
2
3
4
5
Press  
Indication on the LCD shows normal operation.  
To change an item for setting, return to  
.
2
0064  
0099  
64  
Not set (factory setting)  
Press  
to return to the normal indication.  
70 –  
11. ADDRESS SETTING  
1. Address Setting  
Address Setting Procedure  
When twin or triple operation is selected with one indoor unit and one outdoor unit or when one outdoor is  
connected to each indoor unit even with multiple refrigerant systems in group operation, auto address  
setting is completed during the power on process of outdoor unit.  
Remote controller operation is disabled during the auto address setting process (4 to 5 minutes).  
O/U refrigerant line address/I/U  
address/group address setting  
Connections/wiring  
completed  
N
Do you set I/U  
address freely?  
N
One refrigerant  
system?  
(manually)  
Y
N
Is group control going?  
Y
Y
(To auto address  
setting mode)  
N
Multiple units for  
twin/triple operation?  
Power ON outdoor unit  
Y
N
Auto address setting  
first, then corrected?  
Auto address setting  
ends within 4 to 5  
minutes.  
Connect com. cable between  
R/C and I/U temporarily one  
to one.  
Y
Power ON outdoor unit.  
Power ON outdoor unit.  
(Corrected to an address/group  
manually after address setting)  
Set address for each  
I/U individually  
END  
• Unless the following addresses are stored in the EEPROM (IC10) on the indoor unit board, trial  
operation is disabled. (Undefined data is stored at factory shipping.)  
Code  
12  
Factory setting data  
Setting data range  
Refrigerant line address  
Indoor unit address  
0099  
0099  
0001 (unit No. 1) to 0030 (unit No. 30)  
13  
0001 (unit No. 1) to 0064 (unit No. 64)  
Maximum I/U address in the same refrigerant system (double twin=4)  
Group address  
14  
0099  
0000 : Individual (indoor units without group control)  
0001 : Header (one indoor unit in the group)  
0002 : Follower (indoor units in the group except header unit)  
71 –  
2. Address Setting and Group/Twin/Triple Control  
<Definition of terms>  
Indoor unit No.  
Group address  
: N-n=O/U refrigerant line address N (30 max.) -I/U address n (64 max.)  
: 0=Individual (without group control)  
1=Header unit under group control  
2=Follower units under group control  
Header indoor unit (=1) : A representative unit of multiple indoor units in group operation, which performs  
communication between R/C and follower I/U. (* It does not mean an indoor unit  
that communicates with O/U.)  
Operation mode and setting temperature range (except flap air flow control) of  
header unit are reflected on the LCD of remote controller.  
Follower indoor unit (=2) : Indoor units except header unit in group operation.  
It does not control communication with remote controller in principle (except  
response to alarm/service data request).  
Main unit  
:
In a minimal configuration of refrigerant cycle such as twin, triple or double twin, an indoor  
unit which communicates with O/U among those with same refrigerant line address.  
Communicates with sub indoor units and with O/U (instructions to compressor)  
on behalf of cycle control.  
(Representative)  
(Twin header)  
Sub indoor unit  
(Sub unit)  
(Twin follower)  
: Indoor units except the main indoor unit in a twin, triple or double twin system.  
Communicates with the main indoor unit with the same refrigerant line address,  
and provides control in synchronization with the main indoor unit. It does not  
communicate with O/U (no detection of serial signal alarm).  
[1] System Configuration  
a)Single  
b)Twin  
Outdoor unit  
1:1  
individual  
1-2  
H/M  
1-1  
F/S  
1-4  
F/S  
1-3  
F/S  
Indoor unit  
(H/M)  
R/C  
c) Single group operation  
2-1  
F/M  
1-1  
F/M  
4-1  
H/M  
3-1  
F/M  
8-1  
F/M  
• Each indoor unit controls outdoor unit individually.  
d)Multiple single/twin/triple group operation (manual address setting)  
H : Header indoor unit  
F : Follower indoor unit  
M: Main indoor unit  
S : Sub indoor unit  
2-1  
F/M  
1-1  
F/M  
1-2  
F/S  
1-3  
F/S  
3-3  
H/M  
3-4  
F/S  
3-2  
F/S  
3-1  
F/S  
• Main indoor unit : Receives data (thermo status, etc.) from sub indoor units with same refrigerant line  
address, and controls O/U compressor referring to the self thermo status. Transmits  
this instruction to sub units.  
• Sub indoor unit : Receives data from the main indoor unit with same refrigerant line address and serial  
interface with O/U, and performs thermo operation in synchronization with the main  
unit. Sends self thermo ON/OFF request to the main unit.  
(Example) 1-1 main unit communicates with 1-2 and 1-3 sub units without being  
affected by indoor units with refrigerant line address 2 or 3.  
72 –  
[2] Examples of Auto Address Setting from No Address Setting  
1) Standard (one outdoor unit)  
a) Single  
b) Twin  
(1-1)  
(1-2)  
1-1  
individual  
1-2  
H/M  
1-1  
F/S  
(H/M)  
*** Turn ON the power. Address setting is completed automatically. ***  
2) Group operation (multiple O/U = multiple indoor units with serial communication interface, no twin)  
2-1  
1-1  
3-1  
8-1  
F/M  
F/M  
H/M  
F/M  
8 indoor units maximum  
*** Turn ON the power. Address setting is completed automatically. ***  
3) Multiple group operation  
A (single)  
B (triple)  
C (double)  
2-1  
F/M  
1-1  
F/M  
2-1  
F/S  
3-3  
H/S  
3-1  
F/M  
2-2  
F/S  
1-2  
F/S  
3-2  
F/S  
*** Address change required ***  
Change sub unit addresses at the same time manually  
from remote controller.  
2-1  
1-1  
1-2  
1-3  
3-1  
3-2  
3-3  
3-4  
H : Header indoor unit  
F : Follower indoor unit  
M: Main indoor unit  
S : Sub indoor unit  
73 –  
3. Address Setting  
When determining indoor unit addresses with wiring completed without piping  
construction  
(Manual setting by remote controller)  
<Address setting procedure>  
Connect a remote controller to the  
indoor unit whose address you want to  
set one to one.  
Turn ON the power.  
1
Press  
,
, and  
on the R/C  
simultaneously for 4 seconds or more.  
Wiring example of 2 refrigerant systems  
(Solid line: wiring, broken line: refrigerant piping)  
Refrigerant  
line address  
2
3
Set code  
with  
buttons.  
O/U  
O/U  
Set a refrigerant line address with  
buttons.  
(Power cable only)  
(Power cable only)  
4
Press  
normal operation.  
Indication on the LCD shows  
I/U  
I/U  
I/U  
I/U  
I/U  
Refrigerant line  
address 1  
Indoor unit address 1  
1
2
2
1
3
2
2
1
2
2
2
2
Indoor unit  
address  
5
6
Set code  
with  
buttons.  
Group address 1  
For systems like this example, connect a wired remote controller  
independently without connecting R/C wires, and then set these addresses.  
Set indoor unit addresses with  
buttons.  
Group address  
Individual: 0000  
Header unit: 0001  
in case of group control  
Follower unit: 0002  
7
Press  
Indication on the LCD shows  
normal operation.  
Group  
8
9
Set code  
with  
buttons.  
address  
Set indoor unit addresses with  
buttons as follows:  
Individual=  
, header unit=  
,
follower unit=  
8
5
2
4
7
3
6
9
10  
11  
Press  
normal operation.  
Indication on the LCD shows  
10  
End  
11  
1
Press  
.
Operation procedure  
Indoor unit address setting is completed.  
The operation mode returns to normal  
OFF.  
1
8
2
9
3
4
5
6
7
End  
10  
11  
74 –  
ADDRESS SETTING (Continued)  
Checking location of indoor unit number  
(1) To find the address of indoor unit whose location is clear  
In case of independent operation (1:1 connection of wired R/C  
and I/U)  
Perform the procedure during operation of indoor unit.  
<Procedure>  
1
When the indoor unit is not working, press  
the R/C.  
on  
2
Press  
.
UNIT No.  
seconds.  
appears on the LCD and disappears in several  
The displayed number shows the refrigerant line address and  
2
1
indoor unit address.  
When other indoor units are connected to the same remote  
controller (group control), their unit numbers are displayed in  
Operation procedure  
1
2
order each time  
is pressed.  
(2) To find the location of indoor unit from its address  
When checking indoor unit number in the group.  
Perform the procedure while the indoor unit is not working.  
This procedure stops operation of all indoor units in the group.  
<Procedure>  
Indoor unit numbers appear one by one and the fan and flap of  
the displayed unit run.  
1
2
3
Press  
or more.  
• UNIT No.  
and  
on the R/C simultaneously for 4 seconds  
appears.  
• The fan and flap of all indoor units in the group run.  
2
Each pressing of  
the group sequentially.  
• The header unit address appears first.  
• The fan and flap of a selected indoor unit run.  
on the R/C displays unit numbers in  
3
1
End  
Operation procedure  
End  
1
2
3
Press  
to finish the procedure. Operation of all the indoor  
units in the group turns OFF.  
75 –  
12. EXPLODED VIEWS AND PARTS LIST  
High-Wall Type  
RAV-SM562KRT-E/RAV-SM802KRT-E  
219  
221  
220  
215  
213  
214  
232  
229  
228  
222  
218  
230  
216  
211  
208  
217  
227  
201  
209  
203  
231  
224  
226  
202  
212  
223  
210  
207  
234  
235  
236  
204  
233  
Location  
No.  
Part  
No.  
Location  
No.  
Part  
No.  
Description  
Description  
201  
202  
203  
204  
207  
208  
209  
210  
211  
212  
213  
43T00409 FRONT PANEL ASSY  
43T09375 GRILLE ASSY  
43T80306 AIR FILTER (L)  
43T80312 AIR FILTER (R)  
43T03010 BODY; RIGHT  
43T03011 BODY; LEFT  
43T03012 HIDE; CLAW  
43T09345 LOUVER-H  
43T70001 HOSE ASSY; DRAIN  
43T21367 MOTOR;STEPPING  
43T44373 REFRIGERATION ASSEMBLY  
(FOR RAV-SM562KRT-E)  
43T44374 REFRIGERATION ASSEMBLY  
(FOR RAV-SM802KRT-E)  
217  
218  
219  
220  
221  
222  
223  
224  
226  
227  
228  
229  
230  
231  
232  
234  
235  
236  
43T19322 FIX-P-SENSOR  
43T49323 SPRING  
43T49324 PLATE; EVA-SEAL  
43T49039 HOLDER; PLATE EVA-SEAL  
43T49038 PLATE; EVA-SEAL  
43T49037 HOLDER; PLATE EVA-SEAL  
43T79007 GUIDE DRAIN  
43T39016 FIX FOR MOTOR  
43T21368 MOTOR FAN  
43T20315 FAN; CROSS FLOW  
43T22307 M-B-BEARING  
43T39015 BASE; BEARING  
43T03336 BACK BODY ASSY  
43T07022 HOLDER; PIPE  
43T82306 PLATE; INSTALLATION  
43T69495 WIRELESS REMOCON  
213  
216  
43T49021 PIPE; SHIELD  
43T83003 HOLDER; REMOTE CONTROLLER  
43T62029 COVER; TERMINAL  
76 –  
RAV-SM562KRT-E/RAV-SM802KRT-E  
Location  
No.  
Part  
No.  
Location  
No.  
Part  
No.  
Description  
Description  
401  
402  
403  
404  
405  
406  
43T60047 TERMINAL  
43160508 TERMINAL  
43T60321 TERMINAL  
43T50308 SENSOR HEAT EXCHANGER  
43T50306 TEMPERATURE SENSOR  
43T69320 TEMPERATURE SENSOR  
407  
408  
409  
410  
411  
43T60361 FUSE  
43T09343 E-PARTS BASE  
43T69536 PC BOARD  
43T69500 DISPLAY UNIT  
43T09344 CORD CLAMP  
77 –  
T O S H IB A C A R R IE R ( T H A IL A N D ) C O . , LT D .  
144/9 MOO 5, BANGKADI INDUSTRIAL PARK, TIVANON ROAD, TAMBOL BANGKADI,  
AMPHUR MUANG, PATHUMTHANI 12000, THAILAND.  

Murphy Diesel Fuel Shutoff Valve Sv Series User Manual
Panasonic Kx Pw708dwe5 User Manual
Panasonic Kx Tg5240al User Manual
Philips Scb1430nb User Manual
Smc Networks Robo Cylinder Rgs4d User Manual
Soleus Air Air Conditioner Gm Ttw 12hc User Manual
Toshiba B Sa4 User Manual
Toshiba Rav Sm2802dt E User Manual
Xerox M35 User Manual
Xerox Workcentre M118i User Manual