FILE NO.SVM-05053-1
SERVICE MANUAL
HI WALL TYPE (INDOOR UNIT)
RAV-SM562KRT-E
RAV-SM802KRT-E
R410A
Rev. Mar, 2006
1. SPECIFICATIONS
1-1. High-Wall Type(IndoorUnit)
Model name
RAV-SM562KRT-E
RAV-SM802KRT-E
Cooling
Heating
Average Cooling
Heating
Average
Standard capacity (Note 1)
(kW)
5.1
5.6
6.7
8
(1.5 – 5.6)
(1.5 – 6.3)
(2.2 – 8.0)
(2.2–9.0)
Heating low temp. capacity (Note 1) (kW)
Energy consumption effect ratio (Cooling)
Power supply
4.9
5.8
2.93 [D]
3.29 [C]
3.11
2.46 [E]
3.00 [D]
3.24
1 phase 230V (220 – 240V) 50Hz
Running current
(A)
(kW)
(kW)
(%)
8.33–7.63
1.74
8.138–7.46
1.7
13.15–12.05 12.91–11.84
Electrical
Power consumption
characteristics
2.72
2.67
(Low temp.)
Power factor
Main unit
1.95
2.21
95
95
94
94
Pure white
Appearance
Model
Panel color
Height
Width
——
——
Ceiling Panel
(Sold separately)
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
(kg)
298
Main unit
998
Depth
221
Outer
dimension
Height
Width
——
Ceiling panel
——
(Sold separately)
Depth
——
Main unit
12
Total weight
Ceiling panel
——
Heat exchanger
Finned tubu
Soundproof/Heat-insulating material
Fan
Inflammable polyethylene foam
Turbo fan
Foamed polyethylen
1110
Fan unit
Standard air flow High (Mid./Low) (m³/h)
840
Motor
(W)
30
Air filter
Attached main unit
Controller (Sold separately)
Gas side
Wired remote controller RBC-AMT21E
(mm)
(mm)
Ø12.7 (1/2”)
Ø15.9 (5/8”)
Ø9.5 (3/8”)
Connecting
Liquid side
pipe
Ø6.4 (1/4”)
41
Drain port
(Nominal dia.)
(dB• A)
25 (Polyvinyl chloride tube)
36 45
Sound level
High (Mid./Low) (Note 2)
45
41
36
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based
on the reference piping. The reference piping consists of 3 m of main piping and 2 m of branch piping connected with 0
meter height.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions
Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
– 2 –
Operation characteristic curve
<Cooling>
<Heating>
14
16
14
12
10
12
RAV-SM802KRT-E
RAV-SM802KRT-E
10
8
8
6
6
RAV-SM562KRT-E
4
2
0
RAV-SM562KRT-E
4
2
• Conditions
• Conditions
Indoor : DB27 C/WB19°C
Outdoor : DB35°C
Air flow : High
Indoor : DB20°C
Outdoor : DB7 C/WB6°C
Air flow : High
Pipe length : 7.5m
230V
Pipe length : 7.5m
230V
0
0
0
15 20
40
60 70 80
100
1520
40
60
80 90 100
Compressor speed (rps)
Compressor speed (rps)
• Capacity variation ratioaccor ding to temperature
<Cooling>
<Heating>
120
110
100
90
80
70
60
50
40
30
20
10
0
105
100
95
90
85
80
75
70
65
60
• Conditions
• Conditions
Indoor : DB27 C/WB19°C
Indoor : DB20°C
55
Indoor air flow : High
Pipe length : 7.5m
Indoor air flow : High
Pipe length : 7.5m
50
-14 -12 -10 -8 -6 -4 -2
0
2
4
6
8
10
32 33 34 35 36 37 38 39 40 41 42 43
Outsoor temp. (°C)
Outsoor temp. (°C)
– 3 –
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
High-Wall Type
RAV-SM562KRT-E/RAV-SM802KRT-E
Back body
Front panel
998
Air inlet
Grille inlet
220
50
Knock out system
51
Air outlet
Knock out system
75
56
18
57
Drain hose (0.54 m)
Connection pipe (0.49 m)
(Flare ∅6.35)
Connection pipe (0.39 m)
Wireless remote control
(For SM802 : Flare ∅15.88)
(For SM562 : Flare ∅12.7)
998
763.5
450
(For stud bolt ∅6)
(For stud bolt ∅8 -∅10)
20
20
Outline of indoor unit
65
Installation
Plate outline
∅
100
100
– 4 –
3. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM
3-1. Hi Wall type
RAV-SM562KRT-E/SM802KRT-E
Indoor unit
TCJ
sensor
Air heat exchanger
Model
Outer diameter of refrig erant pipe
TC sensor
RAV-SM
Gas side ØA
12.7 mm
Liquid side ØB
6.4 mm
562KRT-E
802KRT-E
9.5 mm
15.9 mm
Refrigerant pipe
at gas side
Outer dia. ØA
Refrigerant pipe
at liquid side
Outer dia. ØB
Pd
Packed valve
Outer dia. ØA
Packed valve
Outer dia. ØB
Ps
Outdoor unit
NOTE :
The refrigerating cycle differs according to the combined outdoor units.
For the cycle diagram, cycle pressure, etc., refer to the following Service Manual.
RAV-SMXXX0AT-E : A03-007
RAV-SPXXXXAT-E : A03-014
RAV-SMXXX1AT-E : A05-001
Cooling
Heating
– 5 –
4. WIRING DIAGRAM
4-1. Hi Wall type (Indoor unit)
RAV-SM562KRT-E/SM802KRT-E
TERMINAL
BLOCK
LOUVER
MOTOR
FAN
MOTOR
U3
U4
BLK
5 4 3 2 1
F
BUS
S
EMG
6 5 4 3 2 1
6 5 4 3 2 1
6 5 4 3
6 5 4 3
1
1
1
2
2
CN22
1
1
2
1
2
3
4
5
CN50
CN44
(BRW)
CN33
(WHI)
CN210
(WHI)
CN40
(BLU)
(WHI)
TERMINAL
BLOCK
F301 FUSE
BLK
BLK
3 3
2 2
1 1
T3.15A 250V~
B
A
CN41
DC15V(BLU)
1 1
3 3
5 5
1
2
3
DC 0VCN100
DC12V(BRW)
WHI
BLK
POWER
SUPPLY
CIRCUIT
CN67
(BLK)
DC7V
1 2
1 2
HEAT
1 1BLK
2 2BLK
CN213(WHI)
CN101
(BLU)
EXCHANGER
SENSOR
(TC)
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
9
9
10
10
CN1(WHI)
WIERD REMOTE
CONTROLLER
1
2
CN103
(GRN)
(MCC-1510)
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
9
9
10
10
HEAT
BLK
BLK
1 1
2 2
CN102
(YEL)
EXCHANGER
SENSOR
(TCJ)
Control P.C board
for indoor unit
INFRARED RAYS RECEIVE
AND INDICATION PARTS
(MCC-819)
BLK
BLK
1 1
2 2
CN104
(WHI)
CN61
CN60
(WHI)
CN80
(GRN)
CN82
(BLU)
CN81
THERMO
SENSOR
(TA)
(YEL)
(BLK)
1 2 3
1 2 3 4 5 6
1 2 3 4 5
1
1
2
2
3
3
4
4
5
5
6
6
1
2
3
4
5
6
PNL/EMG
OPTION
1
2
3
4
HA
RED WHI BLK
Color
1 2 3
1 2 3
Identification
Indoor unit
earth screw
NOTE
BLK : BLACK
BLU : BLUE
RED : RED
GRY : GRAY
PNK : PINK
GRN : GREEN
WHI : WHITE
BRW : BROWN
ORN : ORANGE
YEL : YELLOW
FM : Fan motor
TA : Indoor temp. sensor
TC :Temp. sensor
Outdoor unit
earth screw
Serial
L N
signal
TCJ :Temp. sensor
LM : Louver motor
Single phase 220V, 50Hz
– 6 –
5. SPECIFICATIONS OF ELECTRICAL PARTS
5-1. Indoor Unit
High-Wall Type
RAV-SM562KRT-E/RAV-SM802KRT-E
No.
Parts name
Fan motor (for indoor)
Type
Specifications
1
ICF340-30-X
MF-340-30-X
MP35EA12
Output (Rated) 30 W, 220–240 V
2
3
4
5
Grille motor
Thermo. sensor (TA-sensor)
Heat exchanger sensor (TC-sensor)
Heat exchanger sensor (TCJ-sensor)
268 mm
10 kW at 25°C
Ø6 mm, 400 mm
Ø6 mm, 400 mm
10 kW at 25°C
– 7 –
6. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC
(R410A) which does not damage the ozone layer.
(6) When an air conditioning system charged with a
large volume of refrigerant is installed in a small
room, it is necessary to exercise care so that,
even when refrigerant leaks, its concentration
does not exceed the marginal level.
The working pressure of the new refrigerant R410A
is 1.6 times higher than conventional refrigerant
(R22).The refrigerating oil is also changed in
accordance with change of refrigerant, so be careful
that water, dust, and existing refrigerant or refrigerat-
ing oil are not entered in the refrigerant cycle of the
air conditioner using the new refrigerant during
installation work or servicing time.
If the refrigerant gas leakage occurs and its
concentration exceeds the marginal level, an
oxygen starvation accident may result.
(7) Be sure to carry out installation or removal
according to the installation manual.
The next section describes the precautions for air
conditioner using the new refrigerant. Conforming to
contents of the next section together with the
general cautions included in this manual, perform
the correct and safe work.
Improper installation may cause refrigeration
trouble, water leakage, electric shock, fire, etc.
(8) Unauthorized modifications to the air conditioner
may be dangerous. If a breakdown occurs
please call a qualified air conditioner technician
or electrician.
6-1. Safety During Installation/Servicing
Improper repairÕs may result in water leakage,
electric shock and fire, etc.
As R410A's pressure is about 1.6 times higher than
that of R22, improper installation/servicing may
cause a serious trouble. By using tools and materi-
als exclusive for R410A, it is necessary to carry out
installation/servicing safely while taking the following
precautions into consideration.
6-2. Refrigerant Piping Installation
6-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes
and joints are mainly used. Copper pipes and joints
suitable for the refrigerant must be chosen and
installed. Furthermore, it is necessary to use clean
copper pipes and joints whose interior surfaces are
less affected by contaminants.
(1) Never use refrigerant other than R410A in an air
conditioner which is designed to operate with
R410A.
If other refrigerant than R410A is mixed, pres-
sure in the refrigeration cycle becomes abnor-
mally high, and it may cause personal injury, etc.
by a rupture.
(1) Copper Pipes
It is necessary to use seamless copper pipes
which are made of either copper or copper alloy
and it is desirable that the amount of residual oil
is less than 40 mg/10 m. Do not use copper
pipes having a collapsed, deformed or discol-
ored portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube
may become blocked with contaminants.
(2) Confirm the used refrigerant name, and use
tools and materials exclusive for the refrigerant
R410A.
The refrigerant name R410A is indicated on the
visible place of the outdoor unit of the air condi-
tioner using R410A as refrigerant.To prevent
mischarging, the diameter of the service port
differs from that of R22.
As an air conditioner using R410A incurs
pressure higher than when using R22, it is
necessary to choose adequate materials.
(3) If a refrigeration gas leakage occurs during
installation/servicing, be sure to ventilate fully.
Thicknesses of copper pipes used with R410A
are as shown in Table 6-2-1. Never use copper
pipes thinner than 0.8 mm even when it is
available on the market.
If the refrigerant gas comes into contact with fire,
a poisonous gas may occur.
(4) When installing or removing an air conditioner,
do not allow air or moisture to remain in the
refrigeration cycle. Otherwise, pressure in the
refrigeration cycle may become abnormally high
so that a rupture or personal injury may be
caused.
(5) After completion of installation work, check to
make sure that there is no refrigeration gas
leakage.
If the refrigerant gas leaks into the room, coming
into contact with fire in the fan-driven heater,
space heater, etc., a poisonous gas may occur.
– 8 –
Table 6-2-1 Thicknesses of annealed copper pipes
Thickness (mm)
Nominal diameter
Outer diameter (mm)
R410A
0.80
R22
0.80
0.80
0.80
1.00
1/4
3/8
1/2
5/8
6.35
9.52
0.80
12.70
15.88
0.80
1.00
(2) Joints
b) Socket Joints
For copper pipes, flare joints or socket joints are
used. Prior to use, be sure to remove all con-
taminants.
Socket joints are such that they are brazed
for connections, and used mainly for thick
pipings whose diameter is larger than 20 mm.
Thicknesses of socket joints are as shown in
Table 6-2-2.
a) Flare Joints
Flare joints used to connect the copper pipes
cannot be used for pipings whose outer
diameter exceeds 20 mm. In such a case,
socket joints can be used.
Sizes of flare pipe ends, flare joint ends and
flare nuts are as shown in Tables 6-2-3 to 6-
2-6 below.
Table 6-2-2 Minimum thicknesses of socket joints
Reference outer diameter of
copper pipe jointed (mm)
Minimum joint thickness
(mm)
Nominal diameter
1/4
3/8
1/2
5/8
6.35
9.52
0.50
0.60
0.70
0.80
12.70
15.88
(1) Flare Processing Procedures and Precautions
a) Cutting the Pipe
6-2-2. Processing of Piping Materials
When performing the refrigerant piping installation,
care should be taken to ensure that water or dust
does not enter the pipe interior, that no other oil
other than lubricating oils used in the installed air
conditioner is used, and that refrigerant does not
leak. When using lubricating oils in the piping
processing, use such lubricating oils whose water
content has been removed. When stored, be sure to
seal the container with an airtight cap or any other
cover.
By means of a pipe cutter, slowly cut the pipe
so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs,
refrigerant leakage may occur. Carefully
remove all burrs and clean the cut surface
before installation.
– 9 –
c) Insertion of Flare Nut
d) Flare Processing
Flare processing dimensions differ according
to the type of flare tool. When using a con-
ventional flare tool, be sure to secure "dimen-
sion A" by using a gauge for size adjustment.
Make certain that a clamp bar and copper
pipe have been cleaned.
ØD
By means of the clamp bar, perform the flare
processing correctly.
A
Use either a flare tool for R410A or conven-
tional flare tool.
Fig. 6-2-1 Flare processing dimensions
Table 6-2-3 Dimensions related to flare processing for R410A
A (mm)
Conventional flare tool
Clutch type Wing nut type
1.0 to 1.5 1.5 to 2.0
Outer
diameter
(mm)
Nominal
diameter
Thickness
(mm)
Flare tool for
R410A clutch type
1/4
3/8
1/2
5/8
6.35
9.52
0.8
0.8
0.8
1.0
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
1.0 to 1.5
1.0 to 1.5
1.0 to 1.5
1.5 to 2.0
2.0 to 2.5
2.0 to 2.5
12.70
15.88
Table 6-2-4 Dimensions related to flare processing for R22
A (mm)
Outer
diameter
(mm)
Nominal
diameter
Thickness
(mm)
Conventional flare tool
Flare tool for
R22 clutch type
Clutch type
Wing nut type
1.0 to 1.5
1/4
3/8
1/2
5/8
6.35
9.52
0.8
0.8
0.8
1.0
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
0.5 to 1.0
0.5 to 1.0
0.5 to 1.0
0.5 to 1.0
1.0 to 1.5
12.70
15.88
1.5 to 2.0
1.5 to 2.0
Table 6-2-5 Flare and flare nut dimensions for R410A
Dimension (mm)
Nominal
diameter
Outer diameter
(mm)
Thickness
(mm)
Flare nut
width (mm)
A
B
C
D
1/4
3/8
1/2
5/8
6.35
9.52
0.8
0.8
0.8
1.0
9.1
9.2
6.5
13
20
23
25
17
22
26
29
13.2
16.6
19.7
13.5
16.0
19.0
9.7
12.70
15,88
12.9
16.0
– 10 –
Table 6-2-6 Flare and flare nut dimensions for R22
Dimension (mm)
Nominal
diameter
Outer diameter
Thickness
(mm)
Flare nut width
(mm)
(mm)
A
B
C
D
1/4
3/8
1/2
5/8
3/4
6.35
9.52
0.8
0.8
0.8
1.0
1.0
9.0
9.2
6.5
13
20
20
23
34
17
22
24
27
36
13.0
16.2
19.4
23.3
13.5
16.0
19.0
24.0
9.7
12.70
15.88
19.05
12.9
16.0
19.2
D
B
A
C
Fig. 6-2-2 Relations between flare nut and flare seal surface
When it is strong, the flare nut may crack and
may be made non-removable. When choosing
the tightening torque, comply with values
designated by manufacturers.Table 6-2-7
shows reference values.
(2) Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions
do not have any scar or dust, etc.
b) Correctly align the processed flare surface
with the union axis.
NOTE:
c) Tighten the flare with designated torque by
means of a torque wrench. The tightening
torque for R410A is the same as that for
conventional R22. Incidentally, when the
torque is weak, the gas leakage may occur.
When applying oil to the flare surface, be sure to use
oil designated by the manufacturer. If any other oil is
used, the lubricating oils may deteriorate and cause
the compressor to burn out.
Table 6-2-7 Tightening torque of flare for R410A [Reference values]
Tightening torque of torque
wrenches available on the market
Nominal
diameter
Outer diameter
(mm)
Tightening torque
.
.
N m (kgf cm)
.
.
N m (kgf cm)
16 (160), 18 (180)
42 (420)
1/4
3/8
1/2
5/8
6.35
9.52
14 to 18 (140 to 180)
33 to 42 (330 to 420)
50 to 62 (500 to 620)
63 to 77 (630 to 770)
12.70
15.88
55 (550)
65 (650)
– 11 –
6-3. Tools
6-3-1. RequiredTools
The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to
prevent mixing of other refrigerant.To reinforce the pressure-resisting strength, flare processing dimensions and
opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge,
clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
(1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
(2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
(3) Tools commonly used for R410A and for conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
R410A
Conventional air
conditioner installation
air conditioner installation
No.
Used tool
Usage
Existence of
Whether conven- Whether new equipment
new equipment tional equipment
can be used with
for R410A
can be used
conventional refrigerant
Flare tool
Pipe flaring
Ye s
(Note 1)
1
2
*
Copper pipe gauge for
adjusting projection
margin
Flaring by conventional
flare tool
Ye s
Ye s
Ye s
(Note 1)
(Note 1)
*
*
Connection of flare nut
3
Torque wrench
X
X
Gauge manifold
Charge hose
4
5
6
Evacuating, refrigerant
charge, run check, etc.
X
X
X
X
Vacuum pump adapter Vacuum evacuating
Ye s
Ye s
Electronic balance for
Refrigerant charge
refrigerant charging
7
Refrigerant cylinder
Leakage detector
Charging cylinder
Refrigerant charge
Gas leakage check
Refrigerant charge
Ye s
Ye s
8
9
X
X
X
X
X
(Note 2)
10
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary
as the general tools.
(1) Vacuum pump
(4) Reamer
(9) Hole core drill (Ø65)
Use vacuum pump by
attaching vacuum pump adapter.
(5) Pipe bender
(10) Hexagon wrench
(Opposite side 4mm)
(6) Level vial
(2) Torque wrench
(3) Pipe cutter
(11) Tape measure
(12) Metal saw
(7) Screwdriver (+, -)
(8) Spanner or Monkey wrench
Also prepare the following equipments for other installation method and run check.
(1) Clamp meter
(2) Thermometer
(3) Insulation resistance tester
(4) Electroscope
– 12 –
6-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the
following steps.
Recover the refrigerant, and check no refrigerant
remains in the equipment.
When the compound gauge's pointer has indicated
- 0.1 Mpa (- 76 cmHg), place the handle Low in the
fully closed position, and turn off the vacuum pump's
power switch.
Connect the charge hose to packed valve service
port at the outdoor unit's gas side.
Keep the status as it is for 1 to 2 minutes, and ensure
that the compound gauge's pointer does not return.
Connect the charge hose of the vacuum pump
adapter.
Set the refrigerant cylinder to the electronic balance,
connect the connecting hose to the cylinder and the
connecting port of the electronic balance, and charge
liquid refrigerant.
Open fully both packed valves at liquid and gas
sides.
Place the handle of the gauge manifold Low in the
fully opened position, and turn on the vacuum pump's
power switch. Then, evacuating the refrigerant in the
cycle.
(For refrigerant charging, see the figure below.)
Never charge refrigerant exceeding the specified amount.
1.
2.
3.
If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
Do not carry out additional charging.
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the
specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high
pressure, and may cause a rupture or personal injury.
(INDOOR unit)
(Liquid side)
(Gas side)
(OUTDOOR unit)
Opened
Closed
Refrigerant cylinder
(With siphon pipe)
Check valve
Open/Close valve
for charging
Service port
Electronic balance for refrigerant charging
Fig. 6-4-1 Configuration of refrigerant charging
– 13 –
Be sure to make setting so that liquid can be charged.
When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant.
Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the
cylinder upside down if cylinder is not equipped with siphon.
[ Cylinder with siphon ]
[ Cylinder without siphon ]
Gauge manifold
Gauge manifold
OUTDOOR unit
OUTDOOR unit
c y l i n d e r
a n t g i e r R e f r
Refrigerant
cylinder
Electronic
balance
Electronic
balance
Siphon
R410A refrigerant is HFC mixed refrigerant.
Therefore, if it is charged with gas, the composi-
tion of the charged refrigerant changes and the
characteristics of the equipment varies.
Fig. 6-4-2
6-5. Brazing of Pipes
Phosphor bronze brazing filler tends to react
with sulfur and produce a fragile compound
water solution, which may cause a gas
leakage.Therefore, use any other type of
brazing filler at a hot spring resort, etc., and
coat the surface with a paint.
1.
2.
6-5-1. Materials for Brazing
(1) Silver brazing filler
Silver brazing filler is an alloy mainly composed
of silver and copper. It is used to join iron,
copper or copper alloy, and is relatively expen-
sive though it excels in solderability.
When performing brazing again at time of
servicing, use the same type of brazing filler.
(2) Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used
to join copper or copper alloy.
6-5-2. Flux
(1) Reason why flux is necessary
(3) Low temperature brazing filler
1.By removing the oxide film and any foreign
matter on the metal surface, it assists the flow
of brazing filler.
Low temperature brazing filler is generally called
solder, and is an alloy of tin and lead. Since it is
weak in adhesive strength, do not use it for
refrigerant pipes.
2.In the brazing process, it prevents the metal
surface from being oxidized.
3.By reducing the brazing filler's surface tension,
the brazing filler adheres better to the treated
metal.
– 14 –
(2) Characteristics required for flux
6-5-3. Brazing
1.Activated temperature of flux coincides with
the brazing temperature.
As brazing work requires sophisticated techniques,
experiences based upon a theoretical knowledge, it
must be performed by a person qualified.
2.Due to a wide effective temperature range, flux
is hard to carbonize.
In order to prevent the oxide film from occurring in
the pipe interior during brazing, it is effective to
proceed with brazing while letting dry Nitrogen gas
(N2) flow.
3.It is easy to remove slag after brazing.
4.The corrosive action to the treated metal and
brazing filler is minimum.
5.It excels in coating performance and is harm-
less to the human body.
Never use gas other than Nitrogen gas.
(1) Brazing method to prevent oxidation
As the flux works in a complicated manner as
described above, it is necessary to select an
adequate type of flux according to the type and
shape of treated metal, type of brazing filler and
brazing method, etc.
1.
Attach a reducing valve and a flow-meter to
the Nitrogen gas cylinder.
2.
Use a copper pipe to direct the piping mate-
rial, and attach a flow-meter to the cylinder.
(3) Types of flux
Noncorrosive flux
3. Apply a seal onto the clearance between the
piping material and inserted copper pipe for
Nitrogen in order to prevent backflow of the
Nitrogen gas.
Generally, it is a compound of borax and boric
acid.
It is effective in case where the brazing tem-
perature is higher than 800°C.
4.
When the Nitrogen gas is flowing, be sure to
keep the piping end open.
Activated flux
5.
Adjust the flow rate of Nitrogen gas so that it
is lower than 0.05 m³/Hr or 0.02 MPa (0.2kgf/
cm²) by means of the reducing valve.
Most of fluxes generally used for silver brazing
are this type.
It features an increased oxide film removing
capability due to the addition of compounds
such as potassium fluoride, potassium chloride
and sodium fluoride to the borax-boric acid
compound.
6.
7.
After performing the steps above, keep the
Nitrogen gas flowing until the pipe cools
down to a certain extent (temperature at
which pipes are touchable with hands).
Remove the flux completely after brazing.
(4) Piping materials for brazing and used braz-
ing filler/flux
Piping
material
Used brazing
filler
Used
flux
Copper - Copper Phosphor copper Do not use
M
Flow meter
Copper - Iron
Iron - Iron
Silver
Silver
Paste flux
Vapor flux
Stop valve
Nitrogen gas
cylinder
From Nitrogen cylinder
1.
Do not enter flux into the refrigeration cycle.
2.
When chlorine contained in the flux remains
within the pipe, the lubricating oil deteriorates.
Therefore, use a flux which does not contain
chlorine.
Pipe
Nitrogen
gas
Rubber plug
3.
When adding water to the flux, use water
which does not contain chlorine (e.g. distilled
water or ion-exchange water).
4.
Remove the flux after brazing.
Fig. 6-5-1 Prevention of oxidation during brazing
– 15 –
7. INDOOR UNIT CONTROL
7-1. Indoor Control Circuit
Main (Sub) master remote controller
(Wired)
Weekly timer
LCD
driver
Display
LCD
Display
LCD
Max. 8 units are connectable.*1
CPU
Display
LED
Function setup
Key switch
Function setup
Key switch
*1 When group and twin combination.
main remote controller shal be connected
follower indoor unit
CPU
CN2 CN1
*2 Weekly timer is not connectable to the
sub remote controller.
DC5V
2
*
DC5V
Remote
Power
circuit
Secondary
battery
controller
communication
circuit
Power circuit
Sold separatrly
Sold separatrly
#3
Indoor unit
#1 Header unit
Follower unit
A
B
A
B
A
B
#2
Indoor control P.C. board (MCC-1510)
U3
U4
Central control
communication
circuit
Central control
remote controller
(Sold separatrly)
EEPROM
Remote
controller
communication
circuit
DC20V
DC12V
DC5V
Reciver and Display P.C board
(MCC-819)
TA sensor
TC sensor
TCJ sensor
Buzzer
Driver
Reciver unit
Display LED
CPU
H8/3039
Same as Same as
the left the left
Driver
HA
Louver
motor
Outside
output
AC
Serial
send/
receive
circuit
Run
Wireless
remote
signal
synchronous
signal input
circuit
Warning
Ready
Setting
Thermo. ON
(A/B)
Fan motor
control
Cool
Heat
Fan
1 2 3
1 2 3
Indoor
fan
motor
Power
circuit
circuit
DC280V
DC15V
Outdoor
unit
Outdoor
unit
1 2 3
1 2 3
Outdoor unit
– 16 –
INDOOR UNIT CONTROL CIRCUIT (Continued)
7-2. Control Specifications
NO.
1
Item
Control at
power-on reset
Overview of specifications
(1) Identification of outdoor unit
Remarks
The “PREPARING” lamp
lights during initial setting
(model recognition) after
Identifies outdoor unit at power-on reset, and switches control
according to the identification result.
(2) Setting of indoor unit fan speed and adjustment of air flow direction power-on reset.
Switches indoor unit fan speed, setting of air flow direction
Fan speed, adjustment of
adjustment, etc. based on EEPROM data.
air flow direction
2
Operation mode
switching
(1) Switches operation mode according to mode select instruction
from remote controller.
R/C instructions
OFF
Outline of control
Turns OFF air conditioner
FAN
“Fan only” operation
Cooling operation
COOL
DRY
Dehumidifying operation
Heating operation
HEAT
AUTO
• Selects COOL or HEAT mode
automatically according to Ta, Ts, and To.
Ta : Room temperature
Ts : Set temperature
• The first operation is as follows according
to Ta. (COOL thermo sensor continues
OFF (FAN mode with set fan speed) within
To : Outside air temperature
the range of Ts +α-1<Ta< Ts +α+1.)
COOL
operation
+1.0
FAN mode with
set fan speed
Ta
Ts+
(
)
-1.0
HEAT
operation
• α is corrected according to outside air
temperature.
Outside air temp. Corrected value (α)
No To
>
0 K
-1 K
0 K
k=deg
To 24°C
=
>
24>To 18°C
=
To<18°C
+1 K
0 K
Abnormal To
(2) Operation instruction permission mode
HEAT and AUTO modes are not available for COOL only models.
When instruction is issued from wireless remote controller in the
HEAT or AUTO mode, it is indicated by a reception sound “pi, pi”
and by alternate blinking of “TIMER” and “PREPARING” lamps. To
cancel this alternate blinking, issue an instruction of mode other
than HEAT or AUTO.
3
Room temperature (1) Adjustment range Remote controller set temperature (°C)
control
COOL/DRY HEAT AUTO
Wired type
18 - 29
17 - 30
18 - 29 18 - 29
17 - 30 17 - 30
Wireless type
* When use of remote controller sensor is set (with DN32), even
when sensor value is within the above range in HEAT or AUTO
mode, the thermo sensor turns OFF when Ta sensor value
exceeds 35 °C.
– 17 –
NO.
3
Item
Remarks
Overview of specifications
Room temperature
control
Heat intake temperature
shift
(2) The set temperature for HEAT operation can be corrected by code
No. 06.
(When unit’s temperature
sensor is used)
Set data
0
2
4
6
Correction of set temp. +0°C +2°C +4°C +6°C
Factory setting
Set data
2
* When use of remote controller sensor is set (with DN32), no
correction is performed.
4
Capacity auto
control
(1) Issues instruction of operating frequency to outdoor unit according
to the difference between Ta and Ts.
(2) COOL operation
(GA control)
Calculates room temp. difference between Ta and Ts as well as
room temp. variation every 90 seconds to find correction value of
specified operating frequency and to correct the current operating
frequency.
Ta(n)–Ts(n) : Room temp. difference
Ta(n-1)–Ta(n) : Room temp. variation
n
: Number of detection times
n–1: Number of detection times
(90 seconds before)
(3) HEAT operation
Calculates room temp. difference between Ta and Ts as well as
room temp. variation every 60 seconds to find correction value of
specified operating frequency and to correct the current operating
frequency.
Ts(n)–Ts(n) : Room temp. difference
Ta(n)–Ta(n_1) : Room temp. variation
n
: Number of detection times
n–1: Number of detection times
(60 seconds before)
(4) DRY operation
The frequency correction control is the same as that for COOL
operation.
However, the maximum frequency is limited to S6 or so.
Note) When LOW fan speed is set, the maximum frequency is
limited to SB or so.
5
COOL/HEAT/
AUTO control
(1) Switching between COOL and HEAT is determined based on the
following control.
Ta
(˚C)
After 10 minutes pass from
thermo sensor OFF,
operation mode changes
from HEAT (thermo sensor
OFF) to COOL if Ta exceeds
Tsh +1.5.
COOL
+1.5
(COOL ON)
Tsc : COOL set temp.
Tsc
Tsh
or
Tshc : HEAT set temp. +
room temp. control/
correction
(COOL OFF)
HEAT
-1.5
( ) shows an example of
COOL ON/OFF.
After 10 minutes pass from
thermo sensor OFF,
operation mode changes
from COOL (thermo sensor
OFF) to HEAT if Ta lowers
below Tsc -1.5.
(2) The GA control after determination of operation mode follows the
description in No. 4.
(3) The room temperature control and temperature correction follow
the descriptions in No. 3 and No. 15.
– 18 –
INDOOR UNIT CONTROL CIRCUIT (Continued)
NO.
6
Item
Overview of specifications
Remarks
Fan speed control (1) A fan speed HH (quick high), H (high), L (low) or AUTO is selected HH>H+>H>
according to the instruction from remote controller for FAN mode
operation.
L+>L>UL
(2) Fan speed is switched according to the difference between Ta and Wireless type allows HH,
Ts in the AUTO mode.
H+, H, L+, L, and AUTO.
[Cooling]
HH
H+
Ta (˚C)
A
B
C
D
+3.0
+2.5
+2.0
+1.5
+1.0
HH
(HH)
H
L+
L
H+(HH)
H(HH)
E
L+(H+)
+0.5
Tsc
-0.5
L(H)
L(H)
L(L+)
F
G
• The fan speed control is the same for temperature setting by remote
controller or the unit.
• Once fan speed is changed, it remains unchanged for 3 minutes
unless different fan speed is selected by instruction.
• At the beginning of cooling, a falling gradient (higher fan speed) is
selected.
• When the temperature difference between Ta and Ts is on a
threshold line, fan speed does not change.
• ( ): Auto cooling
[Heating]
Ta (˚C)
L( L+)
(-0.5)
(0)
-1.0
Tsh
E
D
L+(H)
H(H+)
(+0.5)
+1.0
H+
(HH)
(+1.0)
(+1.5)
+2.0
+3.0
C
B
A
HH
(HH)
(+2.0)
+4.0
( ): Temperature setting by remote controller
Other than ( ): Temperature setting by unit
• Once fan speed is changed, it remains unchanged for one minute
unless different fan speed is selected by instruction.
• At the beginning of heating, a rising gradient (higher fan speed) is
selected.
• When the temperature difference between Ta and Ts is on a
threshold line, fan speed does not change.
• ( ): Auto heating
• Fan speed is switched to a higher level when Tc reaches 60 °C.
Tc : Indoor unit heat
exchange sensor
temp.
– 19 –
NO.
6
Item
Overview of specifications
Remarks
Fan speed control
COOL HEAT AP40-56
AP63
1360
1300
1240
1200
1120
1120
1020
970
AP71-80
1480
1340
1320
1300
1200
1200
1100
1040
500
HH
1220
1180
1140
1120
1060
1060
990
HH
H+
H+
H
H
L+
L
L+
L
940
UL
UL
500
500
(3) When thermo sensor turns OFF during heating, the fan speed
mode becomes UL (weak).
“HEAT PREPARING”
indication
(4) When Ta is 25 °C or above at the beginning of HEAT operation or
when canceling defrost mode, H or HH mode continues for one
minute from the time when Tc enters zone E shown in the figure in
No.7 below.
(5) The HH fan speed for auto cooling/heating is set to a speed higher
than that for normal cooling/heating. However, it varies depending
on the temperature difference of Tc during auto heating.
Tc
(˚C)
47
HH+
42
HH
7
Cool air prevention (1) Performs indoor unit fan control in the HEAT mode according to
Fan speed select setting
by remote controller takes
precedence in zones D
control
the Tc (or Tcj) sensor detect temperature. The maximum speed is
limited as shown below.
Shifts Tc control value by +6 °C and E.
during defrosting. However, zone “HEAT PREPARING” is
Tc
Tcj
(˚C)
36
HH
H
B is regarded as zone C after 6
indicated in zones A and
minutes pass from the startup of B.
compressor.
34
L
Zone E
Zone D
32
UL
30
OFF
Zone C
Zone B
24
20
Zone A
– 20 –
INDOOR UNIT CONTROL CIRCUIT (Continued)
NO.
8
Item
Freezing
prevention control
(low-temp.
Overview of specifications
Remarks
(1) Performs the following operation control in the COOL or DRY
mode according to the Tc (or Tcj) sensor detect temperature.
When zone J in the figure below is detected for 6 minutes, the
specified operating frequency is decreased from the actual
operating frequency, and the specified operating frequency is
changed every 30 seconds in zone J.
Tcj : Indoor unit heat
exchange sensor
temp.
release)
Timer count stops and is maintained in zone K.
Timer count is cleared to restore normal operation when zone I is
detected.
If the specified operating frequency becomes SO due to
continuation of zone J, return temperature A is raised from 5 to
12 °C, and operation with L fan speed continues until zone I is
detected.
Tc(˚C)
5
I
A
K
2
J
If 4-way valve cannot be switched during heating and the following
conditions become true, freezing prevention control is performed.
(However, zone J entering control temperature is changed from 2
to -5 °C.)
Tcn :
Tc after 5 minutes
from operation start
Tc (n-1):
[Conditions]
Tc at operation start
The following Aor Bbecomes true after 5 minutes pass from
operation start.
<
ATcn Tc(n–1)–5
BTcn<Tc(n–1)–1 and Tcn Ta<5°C
=
<
=
9
High-temp. release (1) Performs the following operation control in the HEAT mode
control according to the Tc (or Tcj) sensor detect temperature.
•
When zone M is detected, the specified operating frequency is
decreased from the actual operating frequency, and the specified
operating frequency is changed every 30 seconds in zone M.
This control is disabled for
twin follower indoor units.
• The specified operating frequency is maintained in zone N.
• When zone L is detected, the specified operating frequency is
returned by approx. 6 Hz every 60 seconds.
Tc
Tcj
Factory setting
(˚C)
Control temp. (°C)
M
A
A
B
N
56 (54)
52 (52)
B
L
Even when the thermo is
set to OFF, the control is
implemented in the same
way.
Note) At the beginning of operation or when Tc (or Tcj) lowers below
30 °C after operation start, values (54) and (52) in the table are
used as control temperature.
10 Residual heat
removal
Runs indoor unit fan in L (low) mode for about 30 seconds after HEAT
operation stops to remove residual heat.
– 21 –
NO.
Item
Overview of specifications
(1) During the first operation after power on, flap position is controlled Louver angle: 0 °C (full
automatically according to operation mode (COOL/HEAT). close)
Remarks
11 Flap control
Cooling
Heating
Full close
103°
0°
45°
(2) When louver position is controlled by remote controller, the unit’s
microcomputer memorizes the position for use in the next
operation.
* The memorized louver position is cleared when power is turned
off, and returns to the state of (1) above.
Alarm : A code number
(except F08 and
L31) appears on
the remote
(3) Flap position setting
• Flap position can be set within the range below.
COOL/DRY
HEAT/FAN
controller and the
indoor unit stops.
• Flap position can be set collectively or individually in the group
twin or triple operation mode. (Wireless remote controller allows
individual setting only.)
(4) Swing setting
• Flap moves within the range below.
All operation modes
• Flap swing range can be set collectively or individually in the
group twin or triple operation mode. (Setting by wireless remote
controller is disabled when the main remote controller is used.)
(5) When air conditioner operation stops, flap closes automatically. It
keeps its position in the event of an alarm.
(6) Flap tilts upward automatically during preparation for heating.
(7) In the twin or triple operation mode selected by wireless remote
controller, swing setting interlocks with the header indoor unit. If
this setting is transmitted from a follower indoor unit, operation
does not change with a reception sound “pi, pi, pi” if operation
mode differs between header unit and follower unit.
– 22 –
INDOOR UNIT CONTROL CIRCUIT (Continued)
Item
Overview of specifications
Remarks
NO.
12 HA control
(1) When connected to a remote control system (tele-control or
remote on/off interface), operation ON/OFF can be controlled by
the HA signal input.
A connector (separately
available) is required
when using the HA
(2) Outputs operation ON/OFF status to the HA output terminal.
(3) HA signal input/output specifications conform to the JEMA
standard.
terminal CH61 for remote
ON/OFF control.
When group operation is
in use, connect the
connector to either header
or follower indoor unit.
13 Filter sign
indication
(1) Transmits filter replacement signal to remote controller for
indication on the LCD when accumulated operation hours of
indoor unit fan exceeds the specified time (150 hours).
“FILTER” lamp ON
(unavailable for
wireless type)
(2) Clears accumulation timer upon receiving the filter reset signal
from remote controller. At this time, when the specified time has
already passed, the accumulated time is reset and the filter sign
disappears from the LCD.
– 23 –
NO.
Item
Overview of specifications
Remarks
14 Central control
mode switching
(1) The scope of operation by remote controller on the indoor unit
side can be switched by the setting of remote controller.
(2) Scope of operation by remote controller on the indoor unit side
[Individual] : All settings and ON/OFF operations are available.
[Central 1] : ON/OFF operations are disabled.
No indication
“CENTRAL CONTROL”
lamp ON
[Central 2] : ON/OFF operations, operation mode selection, and
temperature setting are disabled.
“CENTRAL CONTROL”
lamp ON
[Central 3] : Operation mode selection and temperature setting
are disabled.
“CENTRAL CONTROL”
lamp ON
[Central 4] : Operation mode selection is disabled.
“CENTRAL CONTROL”
lamp ON
When wired remote
controller is not used,
operation range is the
same as above though
lamp indication remains
unchanged.
If an unavailable operation
mode is transmitted from
wireless remote controller,
it is indicated with a
reception sound “pi, pi, pi,
pi, pi”.
15 Power-saving
control
(1) Power-saving operation is available in the AUTO mode.
(2) The set temperature is corrected using various sensor data within
the range where comfort is maintained.
(3) By using various sensor data including room temp. Ta, outside air
temp. To, fan speed, and indoor unit heat exchange sensor temp.
Tc, 20-minute data is averaged to calculate a set temperature
correction value.
(4) The set temperature is corrected every 20 minutes with the
following shift range.
Cooling : +1.5 to -1.0K
Heating : -1.5 to +1.0K
16 Maximum
frequency limit
control
(1) This control is performed when AUTO mode is selected.
(2) COOL mode: When To is under 28 °C, the control is as follows.
Ta(˚C)
+4
Normal control
Maximum frequency is
+3
limited to the rating of cooling.
Tsc
(3) HEAT mode: When To is over 15 °C, the control is as follows.
Ta(˚C)
Tsh
Maximum frequency is limited
to the rating of heating.
-3
-4
Normal control
– 24 –
INDOOR UNIT CONTROL CIRCUIT (Continued)
7-3. P. C. Board of Indoor Unit
MCC-1510
Microcomputer
run LED
TC sensor
TCJ sensor
Indoor unit - outdoor unit wire
EEPROM
CN101, DC5V
CN102, DC5V
D02
IC10
CN67, AC200V
HA (T10)
Optional power supply
CN61, DC12V
CN309, AC200V
Option output
CN60, DC12V
CHK
CN71, DC5V
Central control
DISP
CN40, DC 5V
CN72, DC5V
External alarm input
CN80, DC12V
Terminating resistor
provided/not provided
EXCT
CN73, DC5V
Remote controller A/B
selection
R/C power LED
SW01
D203
TA sensor
CN104, DC5V
Remote controller
CN41, DC20V
Louver
DC fan input/output
Indication output/wireless reception
FAN DRIVE
CN32, DC12V
CN33, DC12V
CN210
CN213, DC5V
– 25 –
7-4. Optional Onboard Connector Specifications
– 26 –
9
8. Troubleshooting
1. Guide to Troubleshooting
[Wired Remote Controller Type]
(1) Before starting troubleshooting
(a) Necessary tools/measuring equipment
• Phillips screwdrivers, flat-blade screwdrivers, wrenches, pliers, nipper, etc.
• Multimeter, thermometer, pressure gauge, etc.
(b) Precheck
AThe following operations are normal.
1) Compressor does not work.
• Is 3-minute delay operation functioning? (for 3 minutes after compressor OFF)
• Is thermo sensor OFF?
• Is FAN mode or TIMER mode operation going?
• Is water overflow alarm detected?
• Is high outside air temperature operation control working during heating?
2) Indoor unit fan does not work.
• Is cool air prevention control working during heating?
3) Outdoor unit fan does not work or its fan speed changes.
• Is high-temp. release operation control working during heating?
• Is low outside air temperature operation control working during cooling?
• Is defrosting operation going?
4) Operation ON/OFF by remote controller is disabled.
• Is any remote controller or external control working?
• Is auto address setting in progress?
(At t he first power on or when indoor unit address is changed, operation control is disabled for
about 5 minutes after power on.)
BAre all cables/wiring set in the initial state?
CAre indoor unit and remote controller connected correctly?
(2) Troubleshooting procedure
When an error occurs, check the unit in the following procedure.
Error → Check indication of check code
→
Check faulty location and parts
(Note) Other than the check items in the table, malfunction or wrong diagnosis of microcomputer
due to effect of power or external noise is considered. If there is any source of noise, shield
the remote controller wiring.
[Wireless Remote Controller Type]
(1) Before starting troubleshooting
(a) Necessary tools/measuring equipment
• Phillips screwdrivers, flat-blade screwdrivers, wrenches, pliers, nipper, etc.
• Multimeter, thermometer, pressure gauge, etc.
(b) Precheck
AThe following operations are normal.
1) Compressor does not work.
• Is 3-minute delay operation functioning? (for 3 minutes after compressor OFF)
• Is thermo sensor OFF?
• Is FAN mode or TIMER mode operation going?
• Is high outside air temperature operation control working during heating?
2) Indoor unit fan does not work.
• Is cool air prevention control working during heating?
– 27 –
3) Outdoor unit fan does not work or its fan speed changes.
• Is high-temp. release operation control working during heating?
• Is low outside air temperature operation control working during cooling?
• Is defrosting operation going?
4) Operation ON/OFF by remote controller is disabled.
• Is forcible operation OFF mode set?
• Is any remote controller or external control working?
• Is auto address setting in progress?
(At the first power on or when indoor unit address is changed, operation control is disabled for
about 5 minutes after power on.)
BAre all cables/wiring set in the initial state?
CAre indoor unit and receiver unit connected correctly?
(2) Troubleshooting procedure
When an error occurs, check the unit in the following procedure.
→
→
Error
Check indication of lamps
Check faulty location and parts
(Note) Other than the check items in the table, malfunction or wrong diagnosis of microcomputer
due to effect of power or external noise is considered. If there is any source of noise, shield
the signal lines.
(a) Outline of judgment
The following describes the primary judgment of locating faulty unit (indoor unit or outdoor unit). (In
the case of group control operation, the header unit also indicates errors of follower unit by lamp.)
Judging from lamp status of indoor unit
The indoor unit monitors the operating status of air conditioner. When the protection circuit is
activated, the indoor unit indicates the following self-diagnosis contents.
: OFF
: ON
: Blinking (0.5 seconds interval)
Possible causes
Lamp indication
Check code
–
OPERATION TIMER PREPARING
Power OFF
Poor connection/contact between receiver/indication unit and
indoor unit control board
All OFF
Reception error
Transmission error
Communication error
Wired remote
controller
Wrong connection or
poor contact between
wired remote controller
and indoor unit
E01
E02
E03
E08
E09
E18
OPERATION TIMER PREPARING
Duplication of indoor unit No.
Duplication of remote controller header
Invalid setting
Poor connection/contact between indoor units or indoor unit
power OFF
Blinking
(Communication error between header and follower indoor
units or between twin header and follower indoor units)
Wrong connection or poor contact between indoor unit and
outdoor unit
(Communication error between indoor and outdoor units)
E04
P12
OPERATION TIMER PREPARING
Blinking
Failure of indoor unit DC fan (Protection device of indoor unit is
activated.)
OPERATION TIMER PREPARING
Alternate blinking
– 28 –
Troubleshooting (Continued)
Outline of judgment (Contenued)
Lamp indication
Check code
Possible causes
Abnormal outdoor unit discharge
temperature
P03
P04
(*) Protection device
of outdoor unit is
activated.
Outdoor unit high-pressure system error
OPERATION TIMER PREPARING
P19
P22
P26
P29
P31
Four-way valve system error (judged by indoor unit)
Outdoor unit: Malfunction of fan
Outdoor unit: Inverter Idc activated
Outdoor unit: Position detect error
Protection device of
outdoor unit is activated.
Alternate blinking
Header and follower indoor units in the group are not running
due to the following alarm.
(Alarm code: E03, L03, L07, L08)
F01
F02
F10
Heat exchange sensor (TCJ) error
OPERATION TIMER PREPARING
Indoor unit sensor error
Heat exchange sensor (TC) error
Room temperature sensor (TA) error
Alternate blinking
F04
F06
F08
Discharge temperature sensor (TD) error
Temperature sensor (TE, TS) error
Outside air temperature sensor (TO) error
OPERATION TIMER PREPARING
(*) Outdoor unit
sensor error
Alternate blinking
F29
Failure of indoor unit EEPROM
OPERATION TIMER PREPARING
Simultaneous blinking
H01
H02
H03
H06
Compressor breakdown
Compressor locking
Current detect circuit error
Outdoor unit low-pressure system error
OPERATION TIMER PREPARING
(*) Outdoor unit
compressor
system error
Blinking
Duplication of header indoor unit
Group connection indoor unit for
individual indoor unit
Group address not set
L03
L07
L08
L09
OPERATION TIMER PREPARING
→ Auto address
*If group configuration
or address at power on
is invalid, the unit
No setting (indoor unit capacity)
Simultaneous blinking
enters address setting
mode automatically.
L20
L29
L30
L31
Duplication of indoor unit collective address
Other errors of outdoor unit (*)
External interlock error
OPERATION TIMER PREPARING
Others
Phase sequence error
Simultaneous blinking
(*) Check code detected by outdoor unit is a typical example. It varies with outdoor unit of combination.
For details, see the Service Guide of applicable outdoor unit.
– 29 –
Others (Excluding check code)
Lamp indication
Check code
–
Possible causes
Trial operation in progress
OPERATION TIMER PREPARING
Simultaneous blinking
–
Invalid setting
OPERATION TIMER PREPARING
(Auto cooling/heating setting for auto cooling/heating
unavailable unit or heating setting for cool only unit)
Alternate blinking
Error mode detected by remote controller or central controller
Diagnosis function
Judgment and action
Check code
No
indication header indoor unit
(remote
controller
disabled)
Possible causes
Air conditioner status
Conditions
–
No communication with
OFF
Failure of remote controller power
supply or indoor unit EEPROM
1.Check remote controller wires.
2.Check remote controller.
3.Check indoor unit power wiring.
4.Check indoor unit P. C. board.
5.Check indoor unit EEPROM and
insertion into socket.
Remote controller is not
connected correctly.
Indoor unit is not powered
on.
Auto address setting is not
completed.
... Auto address repetition occurs.
E01
*2
No communication with
header indoor unit
Disconnection between
OFF (auto reset)
*Operation
continues under
Indicated when an Remote controller signal reception error
error is detected
1.Check remote controller wires.
2.Check remote controller.
remote controller and header central control
indoor unit (detected by R/C)
3.Check indoor unit power wiring.
4.Check indoor unit P. C. board.
E02
E09
L20
Signal transmission error OFF (auto reset)
to indoor unit (detected by *Operation
Indicated when an Remote controller transmission error
error is detected
1.Check remote controller transmitter.
... Replace remote controller.
R/C)
continues under
central control
Multiple remote controller OFF (Follower R/C Indicated when an 1.Check for multiple remote
headers (detected by R/C) continues
operation)
error is detected
controller headers.
... One header only, others are
follower R/C.
Duplication of indoor unit OFF (auto reset)
collective address during
communication of central
control system
(detected by indoor unit/
central controller)
Indicated when an 1.Check central control network
error is detected address setting.
Central
controller
L20
–
*3
Failure of central control
communication circuit
(detected by central
controller)
Operation
continues (following error is detected
R/C)
Indicated when an 1.Check communication line,
wrong connection, and indoor
unit power supply.
Central
controller
(Transmission)
C05
(Reception)
C06
2.Check communication circuit
(U3, U4, XY terminals).
3.Check central controller
(including central control R/C).
4.Check terminating resistors
(TCC-LINK).
–
Continue/OFF
(depending on
situation)
Indicated when an Check the unit's check code with
error is detected remote controller
Failure of indoor unit group
follower unit.
Central
controller
P30/b7
*2 No check code can be indicated by wired remote controller. (Normal operation of air conditioner cannot be controlled by wired remote controller.)
Check codes are indicated by the lamps for wireless models.
*3 This is an error related to communication of remote controller (A, B) or central control system (TCC-LINK U3, U4).
Remote controller indicates E01, E02, E03, E09, E18 or no code according to situation.
– 30 –
Troubleshooting (Continued)
Check Code Table (Indoor Unit)
– 31 –
Check Code Table (Outdoor Unit)
– 32 –
Troubleshooting (Continued)
Check CodeTable
Failure mode detected by indoor unit
Diagnosis function
Judgment and action
Check code
E03
Possible causes
Air conditioner status
Conditions
No signal reception from remote
controller
OFF
Indicated when an 1.Check remote controller wiring.
(auto reset)
error is detected
• No indication on remote controller
LCD (disconnection)
•
Central controller [C06] check code
E04
Serial signal from outdoor unit does OFF
Indicated when an 1.When outdoor unit does not work at all
not reach indoor unit.
• Wrong wire connection
(auto reset)
error is detected
• Check wires, correct wrong
connection.
• Failure of outdoor unit serial
transmitter
•
Check outdoor unit boards and wiring.
2.When outdoor unit works normally
• Failure of indoor unit serial
receiver
Check boards (indoor unit receiver,
outdoor unit transmitter)
E08
L03
L07
Duplication of indoor unit address
Duplication of header indoor unit
Group line in individual indoor unit
OFF
Indicated when an 1.Check remote controller connection
error is detected
(group/individual) change after
power on.
* If group configuration or address is
not correct, the unit enters auto
address setting mode automatically
for address re-setting.
L08
L09
Indoor unit group address not set
Indoor unit capacity not set
OFF
OFF
OFF
Indicated when an 1.Set indoor unit capacity (DN=11)
error is detected
L30
P12
External interlock alarm input
Failure of indoor unit DC fan
Indicated when an 1.Check external devices.
error is detected
Indicated when an 1. Position detect error
error is detected 2.Overcurrent protection circuit
2.Check indoor unit boards.
operation of indoor unit fan driver
3. Indoor unit fan lock
4. Check indoor unit boards.
P19
Failure of 4-way valve system
• Indoor unit heat exchange
temperature lowers after HEAT
operation starts.
OFF
(auto reset)
Indicated when an 1.Check 4-way valve.
error is detected 2.Check 2-way valve/check valve.
3.Check indoor unit heat exchanger (TC/TCJ)
4.Check indoor unit boards.
.
P31
F01
F02
F10
F29
E18
Indoor unit OFF during alarming to OFF
other indoor units
Indicated when an 1.Judging follower unit when header
unit is E03, L03, L07 or L08
(follower units) error is detected
(auto reset)
2.Check indoor unit boards.
Improper mounting, disconnection OFF
Indicated when an 1.Check TCJ.
or short-circuit of indoor unit heat
exchange sensor TCJ
(auto reset)
error is detected
2.Check indoor unit boards.
Improper mounting, disconnection OFF
Indicated when an 1.Check TC.
or short-circuit of indoor unit heat
exchange sensor TC
(auto reset)
error is detected
2.Check indoor unit boards.
Improper mounting, disconnection OFF
or short-circuit of indoor unit room (auto reset)
temp. sensor TA
Indicated when an 1.Check TA.
error is detected
2.Check indoor unit boards.
Failure of indoor unit EEPROM
• EEPROM access error
OFF
(auto reset)
Indicated when an 1.Check indoor unit EEPROM and
error is detected
insertion into socket.
2.Check indoor unit boards.
Communication error between
header and follower indoor units
OFF
(auto reset)
Indicated when an 1.Check remote controller wiring.
error is detected
2.Check indoor unit power wiring.
3.Check indoor unit boards.
– 33 –
Failure mode detected by outdoor unit (Representative codes)
• The check code used varies depending on the combination with the outdoor unit.
Diagnosis function
Judgment and action
Indicated when an 1.Check power voltages (200 20 VAC).
Check code
H01
Possible causes
Air conditioner status
Conditions
Compressor breakdown
OFF
• Compressor stops due to
error is detected
2.Freezing cycle overload operation
operating frequency decrease.
3.Check current detect circuit on the AC side
.
H02
Compressor does not work.
• Overcurrent protection circuit is
activated after a certain time from
compressor startup.
OFF
Indicated when an 1.Failure of compressor (lock, etc.)
error is detected ... Replace the compressor.
2.Improper compressor wiring (phase loss)
3.Lost-phase operation of power
supply (3-phase models)
H03
H06*1
L29
Failure of current detect circuit
• Large AC current even during
compressor OFF
OFF
OFF
OFF
Indicated when an 1.Operation stops soon when restarted
error is detected ... Check IPDU.
.
2.Lost-phase operation of power supply
Check 3-phase power voltages and wiring.
• Phase loss in power supply
Low-pressure switch ON
(applicable models)
COOL : 30 seconds
HEAT : 10 minutes
Indicated when an 1.Check freezing cycle (gas
error is detected
leakage).
2.Check low-pressure switch circuit.
3.Check outdoor unit CDB board.
Other outdoor unit errors
Indicated when an 1.Check CDB/IPDU wiring.
error is detected 2.Freezing cycle overload operation
• CDB-IPDU communication error
(connector disconnection)
• Abnormal heatsink temperature
(over specified value)
L31*1
Phase detection protection circuit
activated (normal models)
Operation
continued
(compressor
OFF)
Indicated when an 1.Check phase sequence, reverse
error is detected
phase, and phase loss.
2.Check outdoor unit boards.
3.Check high-pressure switch.
4.Check high-pressure switch circuit wiring.
P03
P04
Abnormal discharge temperature
(over specified value)
OFF
Indicated when an 1.Check freezing cycle (gas leakage).
error is detected
2.Failure of electronic expansion valve
3.Check piping sensor (Td).
Failure of high-pressure protection circuit OFF
(Temperature over specified value
detected by TE sensor)
Indicated when an 1.Freezing cycle overload operation
error is detected
2.Check outdoor unit TE sensor.
3.Check outdoor unit CDB board.
4.Check high-pressure switch and circuit.
High-pressure switch (normal models)
P22
Failure of outdoor unit DC fan
OFF
Indicated when an 1.Position detect error
error is detected 2.Overcurrent protection circuit
operation of outdoor unit fan driver
3.Outdoor unit fan lock
4.Check outdoor unit CDB board.
P26
P29
F04
F06
F08
Inverter overcurrent protection
circuit activated (short time)
Main circuit short voltage operation
OFF
OFF
Indicated when an 1.Operation stops soon when restarted.
error is detected
... Compressor partial short-circuit
2.Check IPDU for improper wiring.
Failure of IPDU position detect
circuit
Indicated when an 1.The circuit is activated even after
error is detected
compressor’s 3P connector is
disconnected. ...Replace IPDU.
Improper mounting, disconnection OFF
or short-circuit of outdoor unit temp.
sensor TD
Indicated when an 1.Check TD.
error is detected
2.Check outdoor unit CDB board.
Improper mounting, disconnection OFF
or short-circuit of outdoor unit temp.
sensor TE, TS
Indicated when an 1.Check TE, TS.
error is detected
2.Check outdoor unit CDB board.
Improper mounting, disconnection Operation
Indicated when an 1.Check TO.
or short-circuit of outdoor unit
continued
error is detected
2.Check outdoor unit CDB board.
outside air temp. sensor TO
*1 ROA-P*** is not detected by 1HS models.
Fan continues rotating in a failure mode detected by outdoor unit because there is no communication between outdoor unit
and follower indoor unit in twin group.
– 34 –
Troubleshooting (Continued)
2. Troubleshooting by Remote Controller Check Indication
Main Remote Controller (RBC-AMT31E)
(1) Checking
When an error occurs in the air conditioner, a
check code and an indoor unit number appear
on the LCD of remote controller.
Check code is displayed only during
operation.
If indication disappears, check errors following
Faulty indoor unit
No.
Check code
“Checking Error Log” below.
(2) Checking Error Log
When an error occurs in the air conditioner, error log can be checked following the steps below. Up to 4
errors are memorized.
Error log can be checked in both operation ON and OFF states.
Step
Operation
Press [SET] and [TEST] at the same time for 4 seconds or more. The LCD indication changes as shown below.
Indication of “SERVICE CHECK” shows that the unit is in the error log mode.
• Code No. “01” (order of error log) is displayed.
A
• A check code is displayed.
• The address of faulty indoor unit is displayed in the UNIT No. area.
Each pressing of TEMP. ∆/∇ buttons displays stored error log sequentially.
Check code “01” shows the latest error, and “04” shows the oldest.
B
C
Note
Do not press [CL] as this button clears entire error log of indoor unit.
After checking the error log, press [TEST] to return to the normal indication.
Numbers appearing on the LCD
<Seven-segment display>
Hexadecimal number
– 35 –
TCC-LINK Central Control Remote Controller (TCB-SC642TLE)
(1) Checking
When an error occurs in the air conditioner, a
check code and an indoor unit number appear on
the LCD of remote controller.
Indication of unit number
Indication of alarm
CHECK
UNIT No.
Check code is displayed only during operation.
If indication disappears, check errors following
“Checking Error Log” below.
Alternate blinking
R.C.
No.
(2) Checking Error Log
When an error occurs in the air conditioner, error log can be checked following the steps below. Up to 4
errors are memorized.
Error log can be checked in both operation ON and OFF states.
APress [SET] and [TEST] at the same time for 4 seconds or more.
BIndication of “SERVICE CHECK” and UNIT No. “01” appear.
CWhen selecting a group number (blinking), a unit number and the latest error log, if any, are displayed
alternately.
* Temperature setting is disabled at this time.
Indication of unit number
UNIT No.
Indication of alarm
CHECK
Alternate blinking
R.C.
No.
DTo check other errors, choose a code (01 to 04) with TEMP. ∆/∇ buttons.
ETo check error log of another group, choose a group number with / buttons.
Do not press [CL] as this button clears entire error log of the selected group.
FPress [TEST] to finish the service check.
– 36 –
Troubleshooting (Continued)
3. Troubleshooting for Each Check Code
Check code
Check code name
Possible causes
AImproper R/C wire connection
BFailure of I/U power supply
CFailure of I/U board
[E01]
(New code)
I/U - R/C communication error
(detected by R/C)
DInvalid R/C address setting
EFailure of R/C board
Are R/C wires
A/B correct?
NO
Correct R/C wires.
YES
Improper harness
connection from
I/U terminal block?
YES
Correct connector connection.
Check circuit wiring.
NO
NO
NO
Group control
operation?
YES
Are all indoor
units powered ON?
Check I/U power connection
(power off and on).
YES
Check I/U boards.
→ Replace defective board.
Is R/C powered ON?A/B
terminals: Approx. 18VDC
NO
YES
Is “no header”
set by double R/C?
Correct one header/one follower.
(R/C address connector)
YES
NO
Check R/C board.
→ Replace it if necessary.
– 37 –
Check code
Check code name
Possible causes
[E02]
(New code)
R/C transmission error
Signal transmission to indoor unit is
disabled.
* Not indicated on the central controller and outdoor unit 7-segment.
Com. cable between
R/C and I/U connected
properly?
NO
Correct communication cable.
YES
Failure of R/C
transmitter → Replace R/C.
Check code
Check code name
Possible causes
No communication from R/C and communication adapter.
[E03]
I/U - R/C communication error
(New code)
(detected by I/U)
Indoor unit (I/U) detects this error when it cannot receive signals from remote controller (R/C).
Check communication wiring of R/C A and B.
This code E03 is not displayed on the R/C because of communication error.
This code is displayed on the TCC-LINK central controller.
– 38 –
Troubleshooting (Continued)
Check code
Check code name
Possible causes
[E04]
(New code)
I/U - O/U communication error
(detected by I/U)
AImproper connector connection between I/U and O/U
BImproper wire connection between I/U and O/U
CFailure of I/U or O/U board
DCase thermo sensor ON
EInvalid I/U board switch setting
NO
NO
Does O/U work?
Is group address set correctly?
YES
Check code “14”.
Correct wires.
YES
NO
NO
Are 1/2/3 wires normal?
YES
Are connectors from I/U and
O/U connected normally?
Correct connector connection.
YES
NO
NO
Is I/U switch SW02
setting correct? Bit 1, 2: OFF
Correct switch setting on
MCC-1510 board.
YES
Does voltage between
I/U terminal 2 and 3 fluctuate?
(0-140 VDC)
Check MCC-1510 board.
→ Replace it if necessary.
* Measure within
20 seconds
from power on.
Black
White
C
B
A
YES
Is 280VDC
NO
Terminal block
applied across IPDU main
circuit capacitor?
Replace IPDU.
YES
NO
NO
Is 280VDC supplied to
CDB? (CN03)
Replace IPDU.
YES
Is 7VDC supplied
to CDB? Is CN06-CN800
connection normal?
Replace IPDU.
Correct connector connection.
YES
NO
NO
Is case thermo sensor
connected? (CN500)
Correct connector connection.
YES
Check MCC-1510 board.
→ Replace it if necessary.
Check CDB. → Replace it if
necessary.
Is case thermo sensor working?
YES
Check I/U boards.
® Replace defective board.
Check and correct refrigerant volume.
– 39 –
Check code
Check code name
Possible causes
R/C header setting is duplicated.
[E09]
Duplication of R/C header
(New code)
Are 2 headers set
by double R/C?
YES
Correct one header/one follower.
(R/C address connector)
NO
Check R/C board.
→ Replace it if necessary.
Check code
Check code name
Possible causes
[E18]
Communication error between header AImproper wire connection between I/U
(New code)
and follower I/U
BImproper wire connection between I/U and O/U
CFailure of I/U board
DInvalid I/U board switch setting
NO
Are A/B wires
normal?
Correct R/C wire connection.
YES
Improper harness
connection from I/U terminal
block?
YES
NO
Correct connector connection.
Check circuit wiring.
NO
Is I/U switch SW02
setting correct?
Bit 1, 2: OFF
Correct switch setting on
MCC-1510 board.
YES
NO
NO
NO
Group control operation?
YES
Are all indoor
units powered ON?
Check I/U power connection
(power off and on).
YES
Twin or triple control?
YES
Improper signal
connection between I/U
and O/U?
YES
Correct signal wire connection
between I/U and O/U.
NO
Check MCC-1510 board.
→ Replace it if necessary.
– 40 –
Troubleshooting (Continued)
Check code
Check code name
Possible causes
[F01]
I/U sensor TCJ error
I/U sensor TCJ error
(New code)
Is TCJ connector
CN102 connected
normally?
NO
Correct connector connection.
YES
Is TCJ resistor
characteristic
normal?
NO
Replace sensor TCJ.
* See I/U temp. sensor characteristics-2.
YES
Check I/U main board.
→ Replace it if necessary.
Check code
Check code name
Possible causes
Sensor TC open or short-circuit
[F02]
I/U sensor TC error
(New code)
Is TC connector
CN101 connected
normally?
NO
Correct connector connection.
YES
Is TC resistor
characteristic
normal?
NO
Replace sensor TC.
* See I/U temp. sensor characteristics-2.
YES
Check I/U boards.
→ Replace defective board.
– 41 –
Check code
Check code name
Possible causes
Sensor TA open or short-circuit
[F10]
I/U sensor TA error
(New code)
Is TA connector
CN104 connected
normally?
NO
Correct connector connection.
YES
Is TA resistor
characteristic
normal?
NO
Replace sensor TA.
* See I/U temp. sensor characteristics-1.
YES
Check MCC-1510 board.
Replace it if necessary.
Check code
Check code name
Possible causes
[F29]
Other indoor unit errors
Failure of I/U board
(New code)
This is an error of non-volatile EEPROM IC10 on the indoor unit board, which occurs during
operation. Replace the service board.
* If EEPROM is not mounted at power on or if no data can be read/written from/in the EEPROM,
auto address mode is repeated. At this time, the AI-NET central controller indicates code “97”.
(About 3 minutes)
(Power on)
(About 1 minutes)
“SETTING” appears
on the R/C.
Reboot
(reset)
LED (D02) on the I/U
board blinks for about
10 seconds (1Hz).
“SETTING” disappears.
(Repeated)
– 42 –
Troubleshooting (Continued)
Check code
Check code name
Possible causes
[F31]
O/U EEPROM error
AFailure of O/U power supply (voltage, noise, etc.)
(New code)
BFailure of O/U CDB board.
Check power voltage.
Improve power lines.
Check external noise.
Is O/U free from
power fluctuation?
NO
YES
Check CDB board.
Check code
[E08][L03][L07][L08]
(New code/old code)
E08: I/U number duplicated
L03: Multiple header I/U under group control
L07: One or more group address “individual” under group control
L08: I/U group address not set (99)
When any of these codes is detected at power on, the unit enters auto address setting mode
automatically. (No code is indicated.)
However, if any of these codes is detected in the auto address setting mode, a check code is
displayed in some cases.
Check code
Check code name
Possible causes
Indoor unit capacity not set
[L09]
Indoor unit capacity not set
(New code)
NO
Is indoor unit
capacity set?
Set I/U capacity data. (DN=11)
YES
Check MCC-1510 board.
→ Replace it if necessary.
– 43 –
Check code
Check code name
Possible causes
[L20]
Duplication of central control address
Central control address is duplicated.
(New code)
Are U3/U4
communication
cables connected
normally?
NO
Correct cable connection.
YES
When a unit
NO
connected to U3/U4
is in a group, is it set
to header unit?
Set the connected unit to
header unit.
YES
Check and correct I/U address,
central control address.
Check code
Check code name
Possible causes
When an external alarm is input
[L30]
I/U external interlock
(New code)
NO
Is external device
connected to CN80?
Check I/U boards.
→ Replace defective board.
YES
NO
Check external device.
→ Replace it if necessary.
Is external device
working normally?
YES
Check possible error
causes.
– 44 –
Troubleshooting (Continued)
Check code
Check code name
Possible causes
AFailure of fan motor connector
[P12]
Malfunction of I/U fan motor
(New code)
BFailure of fan motor
CFailure of I/U board
DFailure of cross flow fan shaft
Turn OFF the breaker.
Turn it ON 10 seconds
after.
Is min.1VDC present
NO
NO
NO
Does fan stop with
operation OFF?
between CN210 pin
and C
Replace I/U fan
motor.
E
?
YES
YES
Start cooling with LOW
fan speed.
Is min. 280VDC present
between CN210 pin
NO
Does fan rotate?
YES
A
and C
?
YES
Stop operation and turn OFF
breaker. Disconnect CN210,
turn ON breaker again, and
then stop operation using R/C.
Is min. 15VDC present
between CN210 pin
Change fan speed to HH.
NO
D
and C with
motor connected?
YES
Is min. 280VDC present
between CN210 pin
NO
Replace I/U MCC-
1510 board.
D
and
C
?
YES
Operate I/U (except
heating) by R/C. Is min.
1VDC present between
Stop operation and unplug
AC cord. Disconnect
CN210, plug in AC cable
again, and then stop
operation using R/C.
NO
CN210 pin
E
and
C
?(Measure within
15 seconds.)
NO
NO
Does fan speed
increase?
YES
Operate I/U (except
heating) by R/C. Is min.
1VDC present between
NO
YES
Does cross flow fan
rotate normally by hand?
CN210 pin
E
and
C
? (Measure within
15 seconds.)
YES
YES
Repair cross flow
fan shaft.
Rotate the fan by hand with
operation OFF. Is 0 to
15VDC (rev return signal)
generated between CN210
NO
pin
F
and
C
?
Fan motor is normal.
YES
– 45 –
Check code
Check code name
Possible causes
AFailure of fan motor connector
[P12]
Malfunction of I/U fan motor
(New code)
BFailure of fan motor
CFailure of I/U board
DFailure of cross flow fan shaft
When AC cord is plugged
in, I/U fan starts rotating.
P. C. board
Check the fan motor output DC voltage on the I/U board.
(Blue)
(Yellow)
(White)
(Black)
Check voltage on the motor connector CN210 pin C(GND,
black) and pin E(+V line, yellow) while fan is rotating.
Yellow
1.0VDC or
higher
Below 1.0VDC
Black
Failure of I/U
MCC-1510 board
Failure of I/U fan
motor
(Red)
– 46 –
Troubleshooting (Continued)
Check code
Check code name
Possible causes
[P31]
Other I/U errors
When an error occurs with other units in the group
(New code)
(Group follower I/U error)
When header unit detects E03, L03, L07 or L08 during group operation, “P31” is indicated on follower units in the group and
their operation stops. No code or alarm log is displayed on the R/C.
– 47 –
Check code
Check code name
Possible causes
[C05], [C06]
(Central controller)
TCC-LINK central control
communication error
TCC-LINK central control communication error
Is I/U
powered ON?
NO
NO
Power ON.
YES
Is harness from I/U
terminal block
connected properly?
Correct connector connection.
YES
Can I/U be
operated by R/C
individually?
NO
NO
YES
Are U3/U4 com.
cables. normal?
*1
Correct com. cable.
* Check wrong connection, disconnection, and
shield wire’s contact with com. cable.
YES
When a unit
connected to U3/U4
is in a group, is it
set to header
unit?
NO
NO
Set the connected unit to
header unit.
YES
Free from noise?
YES
Remove noise source.
Can other units
controlled by
central R/C? Is I/U
operating status
reflected?
NO
Check central controller.
→ Replace it if necessary.
YES
Is the code [C05]?
NO
YES
NO
Confirm normal connection of
com. cable. Change connector
connection CN40 to CN44
(EMG) on I/U board.
Is I/U onboard fuse
F03 normal?
YES
Check I/U boards.
→
Replace
defective board.
– 48 –
Troubleshooting (Continued)
Relationship Between Temperature Sensor Resistance and Temperature
20
10
0
40
Characteristic-1
Characteristic-2
Sensor TC, TCJ
Sensor TA
Resistance
[k
30
]
Resistance
[k
]
20
10
0
10
20
30
40
-10
0
10
20
30
40
50
60
70
50
Temperature
Temperature
[˚C]
[˚C]
Characteristic-3
Sensor TE, TO, TS
20
10
0
200
Resistance
[k
Resistance
[k
(10°C or lower)
]
]
(10°C or higher)
100
0
-10
0
10
20
30
40
50
60
70
Temperature [˚C]
Sensor TD
Characteristic-4
20
10
0
200
Resistance
[k
(50°C or lower)
Resistance
]
[k
]
(50°C or lower)
100
0
50
100
Temperature
[˚C]
– 49 –
9. HOW TO REPLACE SERVICE BOARD OF INDOOR UNIT
Requirements When Replacing Service Board of Indoor Unit
The non-volatile EEPROM (IC10) on the board of indoor unit stores important data such as model-specific type and capacity
code (written during factory shipping) as well as system/indoor unit/group addresses set automatically/manually (written during
installation). Therefore, observe the following procedure when replacing indoor unit service boards.
After installation of indoor unit, check whether the settings are correct by checking indoor unit number and group header/
follower unit setting, and also check cycle through a trial operation.
[Replacement Procedures]
Case 1
When it is possible to power ON indoor unit before replacement and when wired R/C can read settings
Reading EEPROM Data *1 (see page 51)
Replacing Service Board and Power ON *2 (see page 51)
Writing Setting Data in EEPROM *3 (see page 52)
Power ON reset (for all indoor units connected to R/C in group control mode)
Case 2
When it is impossible to power ON indoor unit before replacement or when wired R/C is disabled
due to failure of power supply circuit (board failure)
Replacing EEPROM (For layout of components and replacement, see page 49.)
Remove the EEPROM on the board, and replace it with the EEPROM on the service board.
Replacing Service Board and Power ON *2 (see page 51)
Reading EEPROM Data *1 (see page 51)
If data cannot be read, go to Case 3.
Replacing EEPROM (For layout of components and replacement, see page 49.)
Replace EEPROM again. (Mount the original EEPROM on the service board.)
Replacing Service Board and Power ON *2 (see page 51)
Writing Setting Data in EEPROM *3 (see page 52)
Power ON reset (for all indoor units connected to R/C in group control mode)
Case 3
When the EEPROM before replacement is defective, and the settings cannot be read
Replacing Service Board and Power ON *2 (see page 51)
Writing Setting Data in EEPROM (using customer information) *3 (see page 52)
Power ON reset (for all indoor units connected to R/C in group control mode)
– 50 –
HOW TO REPLACE SERVICE BOARD OF INDOOR UNIT (Continued)
*1 Reading EEPROM Data
(Read EEPROM data that was updated at site in addition to factory setting.)
1
1) Press
* In the group control mode, the header unit number is displayed first.
At this time, code (DN) is displayed, and the fan of the selected indoor unit runs, its flap swings,
and the OPERATION, TIMER, and PREPARING lamps blink.
,
, and
on the R/C simultaneously for 4 seconds or more.
(see page 52)
2
2) Each pressing of
indicates indoor unit number in the group sequentially.
Specify indoor unit number whose board is to be replaced.
3
3) Each pressing of TEMP.
4) Change DN from to
buttons increments or decrements DN.
first. (Setting of filter sign ON time)
Write down the setting data displayed.
5) Change DN with TEMP.
buttons, and write down the setting data displayed.
6) Repeat step 5) in the same way, and write down the important setting data shown in the table
(page 49).
* DN =
to
. DN does not always shift sequentially.
to return the operation mode to normal OFF.
6
7) After writing down setting data, press
(It takes about one minute until R/C operation is enabled.)
Essential DN codes
(1) Indoor unit capacity is necessary for fan speed setting.
(2) If refrigerant line address, indoor unit address or group
address differs from that before replacement, the unit enters
auto address setting mode, which requires manual re-setting
for group operation including twin or triple operation.
DN
Description
11 Indoor unit capacity
12 Refrigerant line address
13 Indoor unit address
14 Group address
*2 Replacing Service Board and Power ON
1) Replace the board with a service board.
Reflect the jumper wire (cut) setting and switch setting on the board in the service board. For switch
setting and component layout, see page 53.
2) Power ON the indoor unit in either way of the following according to system configuration.
a) Single (individual) operation
Power ON the indoor unit with no operation.
i) Go to *3 when auto address setting mode ends (about 5 minutes).
(Refrigerant line address=1, indoor unit address=1, and group address=0 are set automatically.)
ii) Press
,
, and
on the R/C simultaneously for 4 seconds or more ( ) to cancel auto
1
address setting mode, and then go to *3. (UNIT No.
is indicated.)
b) Group operation (including twin/triple/double twin)
Power ON the indoor unit whose service board is replaced in either way of the following.
i) Power ON the indoor unit only whose service board is replaced in the same way as a) i) and ii)
above.
There must be remote controller connection. If not, operation *3 is disabled.
ii) Power ON multiple indoor units including the unit whose service board is replaced.
• Twin, triple, double twin: One system only
• Group control: All indoor units
Go to *3 when auto address setting mode ends (about 5 minutes).
* Header indoor unit may change depending on auto address setting. The refrigerant line address and
indoor unit address of the indoor unit whose service board is replaced are automatically set to an
address that is not used in other units. It is recommended that you take a memo beforehand that to
which refrigerant system the indoor unit belongs and that the indoor unit is header or follower unit in
the group.
– 51 –
*3 Writing Setting Data in EEPROM
(The data of the EEPROM on the service board is the factory setting data.)
1
1) Press
,
, and
on the R/C simultaneously for 4 seconds or more.
(see page 52)
* In the group control mode, the header unit number is displayed first.
(If auto address setting mode is canceled in 2-2) a) ii) above, UNIT No.
is indicated.)
At this time, code (DN)
is displayed, and the fan of the selected indoor unit runs, its flap swings,
and the OPERATION, TIMER, and PREPARING lamps blink.
2
2) Each pressing of
indicates indoor unit number in the group sequentially.
Specify indoor unit number whose board is replaced.
(This operation is disabled if UNIT No. is
.)
3
3) Each pressing of TEMP.
buttons increments or decrements DN.
4) Set the indoor unit capacity first.
The factory setting data is written in the EEPROM.
i) Change DN to
ii) Set the indoor unit capacity with TIME
with TEMP.
buttons.
buttons.
<Remote Controller>
4
(for
RBC-AMT21E
example, “0012” for 80 class) ... See the table (page 53).
iii) Press
iv) Press
Indication on the LCD shows normal operation.
6
to return the operation mode to normal OFF.
(It takes about one minute until R/C operation is enabled.)
SETTING
5) Write the data set after installation (such as address) in the EEPROM.
Repeat steps 1) and 2) above.
6) Specify DN
sign ON time)
with TEMP.
buttons. (Setting of filter
7) Check the displayed data comparing the content written down in *1
(page 49).
i) If the data is incorrect, change it with TIME
buttons to the
4
2
3
6
5
data of the memo, and then press
normal operation.
Indication on the LCD shows
1
ii) No operation is required for the same data.
8) Change DN with TEMP.
buttons.
RBC-AMT31E
In the same way as above, check the displayed data comparing the
content of the memo.
If the data is incorrect, change it to the data of the memo.
9) Repeat steps 7) and 8) above.
10) When the setting is completed, press
to return the operation
6
mode to normal OFF.
(It takes about one minute until R/C operation is enabled.)
* DN =
updated and
restored with
to
. DN does not always shift sequentially. Even if data is
button is pressed by mistake, the previous data can be
button unless DN is changed.
3
5
4
6
1
2
– 52 –
HOW TO REPLACE SERVICE BOARD OF INDOOR UNIT (Continued)
Example of Setting Contents to be Written Down (Code Table)
DN
Item
Memo
Factory setting
0001: 150 hours
01 Filter sign ON time
02 Filter contamination level
03 Central control address
06 HEAT intake temp. shift
0C PREPARING indication selection
0F COOL only
0000: Average
0099: Not determined
0002: +2°C
0000: Normal
0000: Heat pump type air conditioner
0008: Wall type
10 Type
Must be set to 0008
11 Indoor unit capacity
Depends on capacity type
0099: Not determined
0099: Not determined
0099: Not determined
0003: 3°C (Ts 1.5)
0000: Not provided
0002: External alarm input
0000: Thermo output ON
0000: Operation input
0000: Disabled
12 Refrigerant line address
13 Indoor unit address
14 Group address
1E Temp. range at COOL/HEAT auto switching control
28 Auto restart after power failure
2A Option/alarm input (CN80) selection
2b Thermo output (T10-C) selection
2E HA terminal (T10-A) selection
31 Ventilation fan (single operation)
32 Sensor selection
0000: Unit sensor
60 Timer setting (wired R/C)
69 Flap setting for cooling
0000: Available
0000: Normal
8b Correction of feeling of strong heating
0000: Not provided
Indoor unit capacity
Code “11”
Onboard Component Layout
<MCC-1510>
Model
Invalid
40 type
45
Setting data
0000*
0006
0007
50
0008
SW02
ON
1
2
SW01
56
0009
ON
2
1
DIP switches
(SW01, SW02)
63
0010
J01
71
0011
80
0012
* Default value of EEPROM on the
service board
IC10
EEPROM (IC10)
Mount EEPROM aligning its notch with
the notch of IC socket.
Notch
DIP switch setting
IC socket
Notch
EEPROM
Setting
AIK-AP**1H
Factory setting
Bit 1
Bit 2
Bit 1
Bit 2
Terminating resistor (for central control)
Selection of R/C A or B
*1
*1
OFF (no resistor)
OFF (A is selected)
OFF (custom models)
OFF
SW01
SW02
Selection of custom or multiple
Not used
OFF
OFF
*1: Set to the state before replacement
– 53 –
11
10. ON-SITE SETTING AND OTHERS
1. Indoor Unit
1.1 Trial Operation Setting by Remote Controller only.
The lamps on the unit blink during trial operation.
<Wired remote controller>
1
Press
on the R/C for 4 seconds. When “TRIAL OPERATION” appears on the LCD, press
.
• “TRIAL OPERATION” appears on the LCD during trial operation.
• Trial operation disables temperature control, but allows fan speed control.
• An instruction of fixed frequency is issued for cooling and heating of trial operation.
• Alarm detection is performed as usual.
The trial operation mode must be used for its original purpose only, because it stresses the air conditioner.
Choose COOL or HEAT mode only for trial operation.
• (Note) Outdoor unit does not run about 3 minutes after power on or operation stop.
2
3
Repress
after trial operation and confirm that “TRIAL OPERATION” disappears from the LCD.
Wired remote controller has 60-minute timer reset function to prevent continuous trial operation.
Checking wiring and piping of indoor/outdoor units
1. Open the front panel of the indoor unit.
2. Press [TEMPORARY] button for 10 seconds. The unit enters forcible cooling mode with a sound
“pi”. COOL operation starts forcibly about 3 minutes later. Check whether cool air is discharged. If
COOL operation does not start, recheck the wiring.
3. Repress [TEMPORARY] for about one second to stop trial operation. The vertical airflow flap
closes and the operation stops.
Checking signal transmission from R/C
1. Press [ON/OFF] on the R/C to check for normal operation using R/C.
• To enter AUTO mode, press [TEMPORARY] once
for about one second.
For forcible cooling, press [TEMPORARY] for 10
seconds or more.
• COOL operation specified by R/C may not start
depending on temperature conditions.
Use forcible cooling operation to check wiring and
piping of indoor/outdoor units.
[TEMPORARY]
button
– 54 –
ON-SITE SETTING AND OTHERS (Continued)
1.2 Forcible Defrost Setting by Remote Controller (wired R/C only)
Preliminary operation
1
Press
,
, and
at the same time for 4 seconds or more in the OFF mode.
In the group control mode, the header unit number is displayed first.
2
Each pressing of
indicates indoor unit number in the group sequentially.
Choose the main indoor unit (connected to the outdoor unit) for which forcible defrosting is to be
performed.
The fan and flap of the selected indoor unit start working.
3
4
5
6
Specify DN “8C” with
Set data 0001 with
buttons.
buttons. (Factory setting: 0000)
Press
Press
Indication on the LCD shows normal operation.
to return the operation mode to normal OFF.
Execution procedure
• Press
on the R/C.
• Choose HEAT operation mode.
• After a while, a forcible defrosting signal is transmitted to the outdoor unit. Upon receiving the signal, the
outdoor unit starts defrosting. It takes up to 12 minutes.
• On completion of defrosting, the indoor unit restart HEAT operation.
1
To reexecute defrosting, repeat steps from step
above.
Once forcible defrosting is performed, the above setting for forcible defrosting is reset.
1.3 Indication of Onboard LEDs
1. D02 (red)
Lights up by the control of main microcomputer when the indoor unit is powered on.
Blinks at intervals of one second (0.5-second on and off) when EEPROM is not mounted or write
error occurs.
Blinks at intervals of 10 seconds (5-second on and off) in the DISP mode. (CN72 short-circuited at
power on)
Blinks at intervals of 2 seconds (1-second on and off): Applicable unit in the EEPROM setting
(address, function selection, etc.) mode
2. D203 (red)
Lights up by hardware control when power is supplied to remote controller.
– 55 –
1.4 JRA Capacity Measurement Mode (wired R/C only)
Preliminary operation
1
Press
,
, and
at the same time for 4 seconds or more in the OFF mode.
In the group control mode, the header unit number is displayed first.
2
Each pressing of indicates indoor unit number in the group sequentially.
Choose the main indoor unit (connected to the outdoor unit) for which this control is to be performed.
The fan and flap of the selected indoor unit start working.
3
4
Specify DN “91” with
buttons.
buttons. (Factory setting: 0000)
Set the following data with
Data
Rating 0001
Middle 0002
5
6
Press
Press
Indication on the LCD shows normal operation.
to return the operation mode to normal OFF.
Operation Fan speed Setting temp. Flap position
Use this mode to measure JRA capacity.
Use this mode under the conditions of JIS B8615-1
Perform the settings in the table by remote
Cooling
Heating
Quick high
Quick high
Auto
18°C
29°C
23°C
24°C
Horizontal angle
Horizontal angle
Horizontal angle
Horizontal angle
Cooling rating
Heating rating
Cooling middle
Heating middle
.
Auto Cooling
Auto Cooling
controller
Execution procedure
• Press on the R/C.
.
Auto
1
To reexecute JRA capacity measurement, repeat steps from step
Once this measurement is completed, the above setting is reset.
above.
1.5 Function Select Setting (wired R/C only)
Perform the following steps in the operation OFF mode.
1
Press
,
, and
at the same time for 4 seconds or more in
the OFF mode.
In the group control mode, the header unit number is displayed
first.
2
Each pressing of
sequentially.
indicates indoor unit number in the group
Choose the main indoor unit (connected to the outdoor unit) this
function is to be performed.
The fan and flap of the selected indoor unit start working.
3
5
4
Specify DN with
buttons.
3
4
6
1
2
Operation procedure
END
1
2
3
4
5
6
Set the setting data with
buttons.
5
Press
Indication on the LCD shows normal operation.
2
• To change the selected indoor unit, go to
.
• To change the item to be set, go to
.
3
6
Press
to return the operation mode to normal OFF.
– 56 –
ON-SITE SETTING AND OTHERS (Continued)
Function Select Code (DN) Table
DN
01
Item
Description
0001: 150H
Factory setting
0001: 150H
Filter sign ON time
0000: None
0002: 2500H
0004: 10000H
0003: 5000H
0005: Clogging sensor used
02
03
06
Filter contamination level
Central control address
HEAT intake temp. shift
0000: Average
0001: Heavy
0000: Average
(half of standard time)
0001: No. 1
0099: Not determined
-
0064: No. 64
0099: Not determined
0002: +2 °C
0000: No shift
0001: +1 °C
0002: +2 °C
-
0010: +10 °C
(Up to +6 recommended)
OC
OF
PREPARING indication selection
COOL only
0000: PREPARING indicated 0001: No indication
0000: PREPARING
indicated
0000: Heat pump
0001: COOL only
(No “AUTO”, “HEAT”
0000: Heat pump
indication)
10
11
Type
0000: (Ceiling panel 1)
0000: Not determined
0001 (ceiling panel 4) -
0037
0008: Wall type
Indoor unit capacity
0001 - 0034
Depends on capacity
type
12
13
14
Refrigerant line address
Indoor unit address
Group address
0001: No. 1
-
-
0030: No. 30
0099: Not determined
0099: Not determined
0099: Not determined
0001: No. 1
0064: No. 64
0000: Individual
0001: Group header
0002: Group follower
1E
Temp. range at COOL/HEAT auto
switching control
0000: 0deg
(Switching at set temperature (data)/2)
-
0010: 10deg
0033: 3deg (Ts 1.5)
28
2A
Auto restart after power failure
0000: Not provided
0001: Provided
0000: Not provided
Option/alarm input (CN80)
selection
0000: Filter input
0002: External alarm input
0001: Alarm input
0002: External alarm
input
2b
2E
Thermo output (T10-3) selection
0000: I/U thermo sensor ON 0001: O/U compressor ON
output
0000: I/U thermo
sensor ON
HA terminal (T10-1) selection
0000: Normal (JEMA)
0002: Fire alarm input
0001: Card input
0000: Normal
(HA terminal)
31
32
60
69
8b
Ventilation fan (single operation)
Sensor selection
0000: Disabled
0001: Enabled
0000: Disabled
0000: Unit sensor
0000: Available
0000: Normal
0000: Unit sensor TA
0000: Available
0000: Normal
0001: R/C sensor
0001: Unavailable
0001: Down allowed
0001: Provided
Timer setting (wired R/C)
Flap setting for cooling
Correction of feeling of strong
heating
0000: Not provided
0000: Not provided
– 57 –
1.6 Wiring and Setting for Remote Controller
Double R/C control (when controlling by two remote controller switches)
This control is provided to control one or more indoor units by two remote controllers. Up to 2 remote
controllers can be installed.
No setting is required when using in combination with a wireless remote controller .
Controlling one indoor unit by 2
remote controllers
R/C switch R/C switch
(header)
Option
A B
(follower)
Option
A B
R/C wiring (on-site arrangement)
R/C wiring terminals
A B
Indoor unit
1 2 3
1 2 3
Outdoor unit
Setting
This control is provided to control one or more indoor units by two remote controllers.
Up to 2 remote controllers can be installed.
Remote controller (back, inside)
<Wired remote controller>
1
2
Setting to use a wired remote controller
as follower R/C:
Change the setting of DIP switch on the
back of R/C switch to “R/C follower” as
shown in the figure.
R/C follower
R/C header
1
2
DIP switch
1
2
– 58 –
ON-SITE SETTING AND OTHERS (Continued)
1.7 Monitoring Function of Remote Controller Switch
■Calling indication of sensor temperature
<Description>
Calls the service monitor mode from the remote controller to
monitor sensor temperatures of the remote controller, indoor units,
and outdoor unit.
<Procedure>
1
Press
and
on the R/C simultaneously for 4 seconds or more
to call the service monitor mode.
“Service monitor” lights up and the header indoor unit number is
displayed first, and then temperature of code “ ” is displayed.
2
Choose a sensor number (code) you want to monitor with
buttons.
1
2
4
3
The following table lists sensor numbers.
Code
Data
Code
Data
00 Room temp. under control *1
01 Room temp. (R/C)
60 Heat exchange temp. TE
61 Outside air temp. TO
62 Discharge temp. TD
63 Intake temp. TS
Returns to normal indication.
Operation procedure
02 Indoor unit intake temp.
03 Indoor unit coil temp. TCJ
04 Indoor unit coil temp. TC
05 Indoor unit coil temp. TC1
1
2
3
4
64
–
65 Heatsink temp. THS
*1 Header indoor unit only under group control
3
4
Choose an indoor unit you want to monitor with
units and outdoor unit in the same control group.
button to monitor sensor temperatures of indoor
Press
to return to the normal indication.
– 59 –
■Calling error log
<Description>
Calls past errors.
<Procedure>
1
Press
and
on the R/C simultaneously for 4 seconds or more
to call the service check mode.
“Service check” lights up and code
the latest error.
is displayed first to display
The faulty indoor unit number and error content are displayed.
2
3
To monitor other errors, change error log number (code) with
buttons.
Code
(latest) → Code
(oldest)
2
3
1
Note) Up to 4 errors are memorized in the error log.
Returns to normal indication.
Operation procedure
Press
to return to the normal indication.
1
2
3
<REQUIREMENT>
Do not press
as this button clears entire error log of indoor unit.
– 60 –
ON-SITE SETTING AND OTHERS (Continued)
<Group Control Operation>
Group control allows operation control of up to 8 indoor units using one remote controller. It includes twin,
triple, and double twin controls with one outdoor unit.
The indoor unit connected to outdoor unit controls room temperature according to the R/C setting.
<An example of system>
O/U
I/U
O/U
I/U
O/U
I/U
O/U
O/U
Header
2-1
I/U
I/U
I/U
1-1
3-1
3-2
4-1
7-1
8 units maximum
R/C
(1) Scope of R/C indication
The indoor unit setting range (operation mode/fan speed/temperature) set in the header unit is
reflected in the remote controller.
ADo not set a concealed duct high static pressure type (AID-P***1H) for header unit.
• If the type is set as header unit, settings are as follows.
Operation mode: [Auto cooling/heating], [HEAT], [COOL] or [FAN] without [DRY]
Fan speed
: [HH]
• In the DRY operation mode, FAN mode is not available for duct models.
BDo not set a “COOL only” model for header unit.
• [Auto cooling/heating] and [HEAT] operation modes are not available.
(2) HA
Both indoor and outdoor units are compatible with the remote control HA.
Operation ON/OFF control for entire group is available.
AMultiple HA inputs in one group are not allowed.
(3) Address setting
If there is no serial data communication between indoor and outdoor units at power on, the indoor unit
is regarded as twin follower unit. (Each time of power on)
... Recognition of twin header (main)/follower (sub) is carried out at each power on, and the result is
not stored in the non-volatile memory.
When performing auto address setting, power on the indoor units in a control group within 3 minutes.
... If powered on after 3 minutes when auto address judgment is completed, the unit is rebooted
and reenters auto address setting mode.
AConnect 3 wires between indoor and outdoor units properly.
BCheck refrigerant line address, indoor unit address, and group address of each unit.
Regarding twin, triple, and double twin, in particular, check for one refrigerant line address for all
units.
CAn indoor unit number (refrigerant line address/group address), once it is set, is retained in
principle unless it is not used for any other unit.
– 61 –
Indoor Unit Power ON Sequence
• Indoor units that are not supplied with power
are in waiting mode continuously.
Power ON
→System start resets the waiting mode.
• Rebooted if power is supplied halfway
<By power supply unit>
<Auto address judgment>
*
Incorrect
Checking group
configuration
Correct
N
3 minutes
passed
* Correct group configuration means
ANo duplication of indoor unit address
BNo invalid indoor unit address
CIndividual units and header/follower units
are not mixed
Y
DOnly one individual unit
EOne header and one or more follower units
in a group
System start
Auto address start
(About one minute to end)
<Initial communication>
O/U model identification (10 seconds) (I/U)
<<Notes on trial operation>>
•
Check for normal connections of power
cable, I/U-O/U serial wiring, and group wiring
Power ON all indoor units within 3 minutes
R/C operation available time (after power on)
1)When address is correct: Approx. 50 seconds
2)When auto address is used: Approx. 4-5 minutes
•
•
Twin header/follower unit identification (I/U)
Group configuration/flap information (R/C)
R/C operation enabled
(50 seconds after power on)
<Periodic communication>
Between indoor units (30-second cycle) (Header/follower)
Within same piping (30-second cycle) (Twin main/sub)
(Communication starts as soon as above status changes.)
(Repeated)
• The indoor unit powered on after auto address judgment under group control is rebooted (system reset), unless it does not
receive data from the header unit or periodic communication within same piping within 120 seconds after power on.
→The sequence restarts from auto address judgment (checking group configuration).
• If the previous address fixed and the header unit is powered on and is rebooted, the refrigerant line address of indoor units
remains unchanged, but the header unit address may change.
– 62 –
ON-SITE SETTING AND OTHERS (Continued)
3. Connections for Central Control
3.1 Connections for TCC-LINK Central Control
3.1.1 Functions
Connect an indoor unit to the TCC-LINK central controller.
3.1.2 Connection Diagram
Central controller
Indoor unit
CN40
Terminal block
CN41
(U3/U4)
TCC-LINK
Number of units
Communication length : 2km
: 64
Terminal block
(A/B)
Remote controller
3.1.3 TCC-LINK Connections
How to make connections
The terminal block for TCC-LINK central control is located at the lower right of the indoor unit.
For details, see the installation manual of applicable central control remote control system.
When using the terminal block, detach the front panel following the description on how to replace main
components in this manual.
Electric parts box
Terminal block
Cord clamp
U4
U3
Terminal block for central control wiring (lower right part without front panel)
– 63 –
3.1.4 Wiring Specifications
Number of wires
2
Size
Specification
MVVS
Up to 1000m: 1.25mm2 stranded wires
Up to 2000m: 2.0mm2 stranded wires
• A 2-wire non-polarity cable is used.
• The cable length depends on each central control system.
When used in a system including multiple air conditioners, the length includes the length of all wires
between indoor and outdoor units on the side of multiple air conditioners.
• Use 2-wire shield cable (MVVS) to protect from noise.
• Joint shield wire between indoor units by closed-end terminating, and leave its end open with insulation
processing.
Make one-point grounding at the indoor unit side. Set the terminating resistors.
(Central control for custom indoor units only)
N
o
t
AJoint shield wire between indoor units by closed-end terminating.
BLeave the end of the shield wire open with insulation processing.
CMake one-point grounding at the indoor unit side.
e
s
Central controller
U1 U2
Note B
Outdoor
unit
1 2 3
1 2 3
1 2 3
Note A
Header
1 2 3
Follower
1 2 3
Indoor
unit
U3 U4
1 2 3
A B
U3 U4
A B
A B
R/C
R/C
R/C
(Group operation)
– 64 –
ON-SITE SETTING AND OTHERS (Continued)
3.1.5 Setting Onboard Switches
Setting of terminating resistors is necessary for central control of custom indoor units only.
• Use SW01 to set terminating resistors.
• Set terminating resistors for the indoor unit only with the smallest refrigerant line address.
Central controller Central controller
Central controller: Up to 10 units
U1 U2
U3 U4
U1 U2
U3 U4
Refrigerant system 1
Refrigerant system 2
Refrigerant system 3
Outdoor
unit
1 2 3
1 2 3
1 2 3
Header
Follower
Indoor
unit
U3 U4
1 2 3
A B
U3 U4
1 2 3
1 2 3
A B
A B
TCC-LINK adapter (option)
Required for custom
indoor units other
R/C wiring
than wall type
R/C
R/C
R/C
Group operation (up to 8 indoor units)
Refrigerant line address
SW01 bit 1
1
2
3
ON
OFF
OFF
Remarks
Bit 1 ON
Factory setting
Factory setting
– 65 –
3.1.6 Onboard Switch Setting Procedure
1. Detach the front panel.
2. Remove the drain guide, ground line, sensor TCJ, sensor TC, and motor leads.
3. Remove the screws to detach the electric parts box.
Sensor TCJ insertion position
(Insert the sensor drawn from above electric parts.)
Sensor TC insertion position
(Insert the sensor drawn from under electric parts.)
Fan motor connector insertion position
Louver motor connector insertion position
Electric parts box screw
4. Detach the electric parts cover, and set SW01 bit 1 to ON.
Do not touch bit 2 as it is for other setting.
DB301
C302
L301
1 : OFF
2 : OFF
1 : ON
2 : OFF
T301
ON
ON
CN40
C301
1
2
1
2
Factory After setting
setting change
ON
1
2
CN102
CN213
IC01
BZ01
2
1
O N
SW02
MCC-1510
5. Install the removed parts by reversing steps 1 to 4.
(Insert the sensors and motor leads firmly into their correct positions.)
– 66 –
ON-SITE SETTING AND OTHERS
3.1.7 Setting Addresses
Overview
To connect custom air conditioners to the TCC-LINK central control system for central control/monitoring,
addresses of connected indoor units must be set in the following procedure.
Connections/wiring
completed
System power ON
Auto address setting
The system performs automatically after power on.
Manual setting/change of refrigerant
line addresses
Change refrigerant line address.
If auto address setting failed, set refrigerant line address manually.
11
* Refer to ADDRESS SETTING.
Is group control (including twin/triple/
double twin) going?
NO
YES
Are all indoor units with central control
function header unit (group address=1)?
YES
NO
Re-set indoor units with central control function to header
unit, and other indoor units to follower unit.
11
* Refer to ADDRESS SETTING.
Central control address number
setting
* Refer to the manual of the central control system.
END
– 67 –
(1) Manual setting/change of indoor unit refrigerant line addresses
[In the case of 29 refrigerant systems or less (when multiple air conditioners are included,
their number of refrigerant systems is also included)]
Refrigerant address “1” is assigned to all indoor units except for group control by the auto address
setting after system power on. Therefore, change refrigerant line address of each refrigerant system
using the wired remote controller.
Central
controller
Refrigerant Refrigerant
Refrigerant
system 3
Refrigerant Refrigerant
system 1
system 2
system 4
system 5
O/U
O/U
O/U
O/U
O/U
I/U
I/U
I/U
I/U
I/U
I/U
R/C
R/C
R/C
R/C
Refrigerant line
address
Indoor unit
address
1
1
0
1
1
0
1
1
0
2
1
0
1
1
1
3
1
1
1
2
2
3
2
2
1
1
1
4
1
1
2
1
2
5
1
2
An example after auto address
setting
Group address
Refrigerant line
address
Indoor unit
address
After changing refrigerant line
address manually
Group address
11
* For changing/setting refrigerant line addresses by wired remote controller, refer to ADDRESS
SETTING.
* Refrigerant line address must be unique for each refrigerant system.
To perform central control in combination of multiple and custom air conditioners, set refrigerant
line addresses different from those of multiple air conditioners.
– 68 –
ON-SITE SETTING AND OTHERS
(2) Manual setting/change of indoor unit refrigerant line addresses
[In the case of 30 refrigerant systems or more (when multiple air conditioners are included,
their number of refrigerant systems is also included)]
Regarding refrigerant systems up to No. 29, manual setting/change is the same as that on the
previous page.
• Refrigerant address “1” is assigned to all indoor units except for group control by the auto address
setting after system power on. Therefore, change refrigerant line address of each refrigerant
system using the wired remote controller.
• Also change indoor unit addresses so as to avoid duplication of indoor unit numbers.
Central
controller
Refrigerant Refrigerant
system 30 system 31
Refrigerant
system 32
Refrigerant Refrigerant
system 33 system 34
O/U
O/U
O/U
O/U
O/U
I/U
I/U
I/U
I/U
I/U
I/U
R/C
R/C
R/C
R/C
Refrigerant line
address
Indoor unit
address
1
1
0
1
1
0
1
1
0
2
1
0
1
1
1
3
1
1
1
2
2
3
2
2
1
1
1
4
1
1
2
1
2
5
1
2
An example after auto address
setting
Group address
Refrigerant line
address
Indoor unit
address
After changing refrigerant line
address manually
Group address
11
* For changing/setting refrigerant line addresses by wired remote controller, refer to ADDRESS
SETTING.
* Change refrigerant line address of all indoor units connected directly to the central controller to
“30”.
These indoor units are under twin or triple control, also change the refrigerant line address of
follower indoor units to “30”.
* Change indoor unit addresses so that they are not duplicated.
– 69 –
3.1.8 Central Control Address Number Setting
To connect an indoor unit to the central control remote controller, an address number for central control
must be set.
An address number for central control is indicated as the refrigerant line number of the remote
controller.
1. Setting by Remote Controller on Indoor Unit Side
<Procedure> Perform the following steps in the operation OFF
mode.
(Fig. 1)
1
Press
and
on the R/C simultaneously for 4 seconds
or more.
When group control is going, UNIT No.
is displayed first,
and all indoor units in the group are selected. At this time, the
fans of all the selected indoor units start running. (Fig. 1)
Maintain this state without pressing
.
For individual remote controllers without group control, a
refrigerant line address and an indoor unit address are
indicated.
4
3
2
3
Specify code
with
buttons.
2
1
5
Table 1
Choose setting data with
Table 1 shows setting data.
buttons.
Setting data Address No. for central control
0001
0002
0003
1
2
3
4
5
Press
Indication on the LCD shows normal operation.
• To change an item for setting, return to
.
2
0064
0099
64
Not set (factory setting)
Press
to return to the normal indication.
– 70 –
11. ADDRESS SETTING
1. Address Setting
Address Setting Procedure
When twin or triple operation is selected with one indoor unit and one outdoor unit or when one outdoor is
connected to each indoor unit even with multiple refrigerant systems in group operation, auto address
setting is completed during the power on process of outdoor unit.
Remote controller operation is disabled during the auto address setting process (4 to 5 minutes).
O/U refrigerant line address/I/U
address/group address setting
Connections/wiring
completed
N
Do you set I/U
address freely?
N
One refrigerant
system?
(manually)
Y
N
Is group control going?
Y
Y
(To auto address
setting mode)
N
Multiple units for
twin/triple operation?
Power ON outdoor unit
Y
N
Auto address setting
first, then corrected?
Auto address setting
ends within 4 to 5
minutes.
Connect com. cable between
R/C and I/U temporarily one
to one.
Y
Power ON outdoor unit.
Power ON outdoor unit.
(Corrected to an address/group
manually after address setting)
Set address for each
I/U individually
END
• Unless the following addresses are stored in the EEPROM (IC10) on the indoor unit board, trial
operation is disabled. (Undefined data is stored at factory shipping.)
Code
12
Factory setting data
Setting data range
Refrigerant line address
Indoor unit address
0099
0099
0001 (unit No. 1) to 0030 (unit No. 30)
13
0001 (unit No. 1) to 0064 (unit No. 64)
Maximum I/U address in the same refrigerant system (double twin=4)
Group address
14
0099
0000 : Individual (indoor units without group control)
0001 : Header (one indoor unit in the group)
0002 : Follower (indoor units in the group except header unit)
– 71 –
2. Address Setting and Group/Twin/Triple Control
<Definition of terms>
Indoor unit No.
Group address
: N-n=O/U refrigerant line address N (30 max.) -I/U address n (64 max.)
: 0=Individual (without group control)
1=Header unit under group control
2=Follower units under group control
Header indoor unit (=1) : A representative unit of multiple indoor units in group operation, which performs
communication between R/C and follower I/U. (* It does not mean an indoor unit
that communicates with O/U.)
Operation mode and setting temperature range (except flap air flow control) of
header unit are reflected on the LCD of remote controller.
Follower indoor unit (=2) : Indoor units except header unit in group operation.
It does not control communication with remote controller in principle (except
response to alarm/service data request).
Main unit
:
In a minimal configuration of refrigerant cycle such as twin, triple or double twin, an indoor
unit which communicates with O/U among those with same refrigerant line address.
Communicates with sub indoor units and with O/U (instructions to compressor)
on behalf of cycle control.
(Representative)
(Twin header)
Sub indoor unit
(Sub unit)
(Twin follower)
: Indoor units except the main indoor unit in a twin, triple or double twin system.
Communicates with the main indoor unit with the same refrigerant line address,
and provides control in synchronization with the main indoor unit. It does not
communicate with O/U (no detection of serial signal alarm).
[1] System Configuration
a)Single
b)Twin
Outdoor unit
1:1
individual
1-2
H/M
1-1
F/S
1-4
F/S
1-3
F/S
Indoor unit
(H/M)
R/C
c) Single group operation
2-1
F/M
1-1
F/M
4-1
H/M
3-1
F/M
8-1
F/M
• Each indoor unit controls outdoor unit individually.
d)Multiple single/twin/triple group operation (manual address setting)
H : Header indoor unit
F : Follower indoor unit
M: Main indoor unit
S : Sub indoor unit
2-1
F/M
1-1
F/M
1-2
F/S
1-3
F/S
3-3
H/M
3-4
F/S
3-2
F/S
3-1
F/S
• Main indoor unit : Receives data (thermo status, etc.) from sub indoor units with same refrigerant line
address, and controls O/U compressor referring to the self thermo status. Transmits
this instruction to sub units.
• Sub indoor unit : Receives data from the main indoor unit with same refrigerant line address and serial
interface with O/U, and performs thermo operation in synchronization with the main
unit. Sends self thermo ON/OFF request to the main unit.
(Example) 1-1 main unit communicates with 1-2 and 1-3 sub units without being
affected by indoor units with refrigerant line address 2 or 3.
– 72 –
[2] Examples of Auto Address Setting from No Address Setting
1) Standard (one outdoor unit)
a) Single
b) Twin
(1-1)
(1-2)
1-1
individual
1-2
H/M
1-1
F/S
(H/M)
*** Turn ON the power. Address setting is completed automatically. ***
2) Group operation (multiple O/U = multiple indoor units with serial communication interface, no twin)
2-1
1-1
3-1
8-1
F/M
F/M
H/M
F/M
8 indoor units maximum
*** Turn ON the power. Address setting is completed automatically. ***
3) Multiple group operation
A (single)
B (triple)
C (double)
2-1
F/M
1-1
F/M
2-1
F/S
3-3
H/S
3-1
F/M
2-2
F/S
1-2
F/S
3-2
F/S
*** Address change required ***
Change sub unit addresses at the same time manually
from remote controller.
2-1
1-1
1-2
1-3
3-1
3-2
3-3
3-4
H : Header indoor unit
F : Follower indoor unit
M: Main indoor unit
S : Sub indoor unit
– 73 –
3. Address Setting
When determining indoor unit addresses with wiring completed without piping
construction
(Manual setting by remote controller)
<Address setting procedure>
Connect a remote controller to the
indoor unit whose address you want to
set one to one.
Turn ON the power.
1
Press
,
, and
on the R/C
simultaneously for 4 seconds or more.
Wiring example of 2 refrigerant systems
(Solid line: wiring, broken line: refrigerant piping)
→
Refrigerant
line address
2
3
Set code
with
buttons.
O/U
O/U
Set a refrigerant line address with
buttons.
(Power cable only)
(Power cable only)
4
Press
normal operation.
Indication on the LCD shows
I/U
I/U
I/U
I/U
I/U
Refrigerant line
address → 1
Indoor unit address → 1
1
2
2
1
3
2
2
1
2
2
2
2
→
Indoor unit
address
5
6
Set code
with
buttons.
Group address → 1
For systems like this example, connect a wired remote controller
independently without connecting R/C wires, and then set these addresses.
Set indoor unit addresses with
buttons.
Group address
Individual: 0000
Header unit: 0001
in case of group control
Follower unit: 0002
7
Press
Indication on the LCD shows
normal operation.
→
Group
8
9
Set code
with
buttons.
address
Set indoor unit addresses with
buttons as follows:
Individual=
, header unit=
,
follower unit=
8
5
2
4
7
3
6
9
10
11
Press
normal operation.
Indication on the LCD shows
10
End
11
1
Press
.
Operation procedure
Indoor unit address setting is completed.
The operation mode returns to normal
OFF.
1
8
2
9
3
4
5
6
7
End
10
11
– 74 –
ADDRESS SETTING (Continued)
■Checking location of indoor unit number
(1) To find the address of indoor unit whose location is clear
In case of independent operation (1:1 connection of wired R/C
and I/U)
Perform the procedure during operation of indoor unit.
<Procedure>
1
When the indoor unit is not working, press
the R/C.
on
2
Press
.
UNIT No.
seconds.
appears on the LCD and disappears in several
The displayed number shows the refrigerant line address and
2
1
indoor unit address.
When other indoor units are connected to the same remote
controller (group control), their unit numbers are displayed in
Operation procedure
1
2
order each time
is pressed.
(2) To find the location of indoor unit from its address
When checking indoor unit number in the group.
Perform the procedure while the indoor unit is not working.
This procedure stops operation of all indoor units in the group.
<Procedure>
Indoor unit numbers appear one by one and the fan and flap of
the displayed unit run.
1
2
3
Press
or more.
• UNIT No.
and
on the R/C simultaneously for 4 seconds
appears.
• The fan and flap of all indoor units in the group run.
2
Each pressing of
the group sequentially.
• The header unit address appears first.
• The fan and flap of a selected indoor unit run.
on the R/C displays unit numbers in
3
1
End
Operation procedure
End
1
2
3
Press
to finish the procedure. Operation of all the indoor
units in the group turns OFF.
– 75 –
12. EXPLODED VIEWS AND PARTS LIST
High-Wall Type
RAV-SM562KRT-E/RAV-SM802KRT-E
219
221
220
215
213
214
232
229
228
222
218
230
216
211
208
217
227
201
209
203
231
224
226
202
212
223
210
207
234
235
236
204
233
Location
No.
Part
No.
Location
No.
Part
No.
Description
Description
201
202
203
204
207
208
209
210
211
212
213
43T00409 FRONT PANEL ASSY
43T09375 GRILLE ASSY
43T80306 AIR FILTER (L)
43T80312 AIR FILTER (R)
43T03010 BODY; RIGHT
43T03011 BODY; LEFT
43T03012 HIDE; CLAW
43T09345 LOUVER-H
43T70001 HOSE ASSY; DRAIN
43T21367 MOTOR;STEPPING
43T44373 REFRIGERATION ASSEMBLY
(FOR RAV-SM562KRT-E)
43T44374 REFRIGERATION ASSEMBLY
(FOR RAV-SM802KRT-E)
217
218
219
220
221
222
223
224
226
227
228
229
230
231
232
234
235
236
43T19322 FIX-P-SENSOR
43T49323 SPRING
43T49324 PLATE; EVA-SEAL
43T49039 HOLDER; PLATE EVA-SEAL
43T49038 PLATE; EVA-SEAL
43T49037 HOLDER; PLATE EVA-SEAL
43T79007 GUIDE DRAIN
43T39016 FIX FOR MOTOR
43T21368 MOTOR FAN
43T20315 FAN; CROSS FLOW
43T22307 M-B-BEARING
43T39015 BASE; BEARING
43T03336 BACK BODY ASSY
43T07022 HOLDER; PIPE
43T82306 PLATE; INSTALLATION
43T69495 WIRELESS REMOCON
213
216
43T49021 PIPE; SHIELD
43T83003 HOLDER; REMOTE CONTROLLER
43T62029 COVER; TERMINAL
– 76 –
RAV-SM562KRT-E/RAV-SM802KRT-E
Location
No.
Part
No.
Location
No.
Part
No.
Description
Description
401
402
403
404
405
406
43T60047 TERMINAL
43160508 TERMINAL
43T60321 TERMINAL
43T50308 SENSOR HEAT EXCHANGER
43T50306 TEMPERATURE SENSOR
43T69320 TEMPERATURE SENSOR
407
408
409
410
411
43T60361 FUSE
43T09343 E-PARTS BASE
43T69536 PC BOARD
43T69500 DISPLAY UNIT
43T09344 CORD CLAMP
– 77 –
T O S H IB A C A R R IE R ( T H A IL A N D ) C O . , LT D .
144/9 MOO 5, BANGKADI INDUSTRIAL PARK, TIVANON ROAD, TAMBOL BANGKADI,
AMPHUR MUANG, PATHUMTHANI 12000, THAILAND.
|