Thermo Products Thermo Pride Air Conditioner Opb 24 User Manual

OUTDOOR COMBINATION OIL-FIRED  
FURNACE AND AIR CONDITIONING UNIT  
MODEL OPB (24,30,36)- 80  
INSTALLATION AND SERVICE MANUAL  
: If the information in this manual is not followed exactly, a  
fire or explosion may result causing property damage, personal  
injury, or loss of life.  
Do not store or use gasoline or other flammable vapors and liquids in the  
vicinity of this or any other appliance.  
WHAT TO DO IF YOU FIND AN OIL LEAK:  
Do not try to light any appliance.  
Immediately call your oil supplier.  
If you cannot reach your oil supplier, call the fire department.  
Installation and service must be performed by a qualified installer, service  
agency or the oil supplier. (These entities are referred to in these instructions  
as a qualified heating contractor).  
Please read these instructions prior to installation, initial firing, and before  
performing any service or maintenance.  
These instructions must be retained by the homeowner for future reference by  
qualified heating contractor.  
Thermo Products, LLC  
PO Box 217  
MO-455  
ECN 4979-MA  
North Judson, IN 46366  
Phone: (574) 896-2133  
Made In USA  
All installations and services must be performed by qualified service personnel.  
Contents  
SECTION  
PAGE  
VI. DEALER MAINTENANCE ................................................................ ……... 45  
A. General Inspection ...................................................................... ……... 45  
B. Heat Exchanger ........................................................................………. 46  
1. Disassembly to Access Heat Exchanger ...............................……… 46  
2. Heat Exchanger Reassembly................................................……… 48  
3. Operational Check ..................................................................…….. 49  
C. Electrical System ...........................................................................……. 49  
D. Supply/Return Air Blower .............................................................……...50  
E. Supply/Return Air Filter ................................................................……..50  
1. Filter Maintenance ...................................................................…….. 50  
2. Filter Replacement ...................................................................……. 50  
F. Extended Appliance Shutdown ....................................................……... 51  
VII. HOMEOWNER/USER INFORMATION AND ROUTINE MAINTENANCE ..53  
VIII. TROUBLESHOOTING .........................................................................…… 57  
A. Heating System ................................................................................….. 57  
B. Cooling System .................................................................................…. 58  
IX.  
X.  
REFERENCES .......................................................................................…. 60  
APPENDIX A: SOURCES FOR REFERENCED STANDARDS .............…. 61  
APPENDIX B: CALCULATIONS ...........................................................….. 62  
XI.  
XII. APPENDIX C: ELECTRICAL SCHEMATIC AND CONNECTION DIAGRAM  
.................................................................................................................….74  
XIII. APPENDIX D: SEQUENCE OF OPERATIONS ....................................….. 75  
XIV. APPENDIX E: TROUBLESHOOTING FLOWCHARTS .........................….. 77  
XV. APPENDIX F: SPECIFICATION SHEETS .............................................…. 86  
XVI. APPENDIX G: REPLACEMENT PARTS ...............................................….. 87  
XVII. APPENDIX H: OPB HEATING AND COOLING TEST FORM ...............…. 89  
WARRANTY …………………………………………………………………….. 90  
2
All installations and services must be performed by qualified service personnel.  
I. SAFETY INFORMATION  
This page and the following page contain reproductions of the various  
instructions and warning labels placed on the Thermo Pride oil-fired appliances.  
Please read and comply with the contents of these labels.  
3
All installations and services must be performed by qualified service personnel.  
4
All installations and services must be performed by qualified service personnel.  
The following warnings and cautions are found throughout the Thermo Pride  
Model OPB Installation and Service Manual. Please read and comply with the  
statements below.  
: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR  
EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY,  
OR LOSS OF LIFE.  
: Carefully read and thoroughly understand the following guidelines and  
warnings before continuing with the installation of this unit. Failure to follow these  
guidelines can cause improper and unsafe operation of this appliance. Unsafe operation  
can result in substantial property damage, severe personal injury, or death.  
: This unit is not to be used for temporary heating of buildings, or structures,  
under construction.  
: Maximum gross stack temperature must not exceed 550°F (288°C) under  
any circumstances.  
: Failure to comply with minimum filter installation requirements may effect the  
performance and/or void the warranty on this unit.  
: This appliance must be grounded in accordance with local codes or in the  
absence of local codes with the National Electrical Code, ANSI/NFPA 70 –1999, or the  
latest edition.  
: Turn off the electrical power to the appliance before attempting to change  
supply air blower speed wiring.  
: Personal injury or property damage could result from repair, or service, of  
this appliance by anyone other than a qualified heating contractor. The end user may  
only perform the service described under the Homeowner/User Routine Maintenance  
section of this manual.  
: To avoid injury from moving parts or electrical shock, shut off the power to  
the appliance before removing supply air blower compartment door and servicing this  
appliance.  
: When servicing controls, label all wires prior to disconnecting. Reconnect  
any wires removed correctly. Wiring errors can cause improper and dangerous  
operation. Dangerous operation can result in injury or damage.  
: Disconnect electrical power before servicing this unit.  
5
All installations and services must be performed by qualified service personnel.  
: Waterproof type connectors must be used when connecting electrical power  
and control wiring to the unit to prevent moisture from being drawn into the unit during  
operation.  
: Refrigerant is under pressure. Guard against refrigerant spraying into the  
face or on skin. Always wear protective equipment, i.e. safety glasses or goggles and  
gloves when working with refrigerant.  
: Do not under any circumstances heat the refrigerant cylinder with a torch or  
by any other means other than warm water. Excessive pressures generated in this  
manner may weaken the refrigerant container and result in an explosion!  
: To avoid injury from moving parts, or electrical shock, shut off the power to  
the appliance before removing blower compartment door and servicing this appliance.  
: When servicing controls, label all wires prior to disconnecting. Reconnect any  
removed wires correctly. Wiring errors can cause improper and dangerous operation.  
Dangerous operation can result in injury or damage.  
: Do not use this appliance if any part has been under water. Immediately call  
a qualified service technician to inspect the furnace and to replace any part of the  
control system and any gas control that has been under water.  
: The area around the appliance, including the top of the unit, must be kept  
clear and free of combustible materials, gasoline, and other flammable vapors and  
liquids.  
: The appliance vent terminal may be hot. If the terminal is hot, allow it to cool  
before touching it.  
: Shut off unit and disconnect the power source before disassembling the unit.  
: Never operate the appliance without clean air filters in place.  
: This appliance requires air for combustion, ventilation, and cooling. Do not  
block or obstruct air openings in the unit and the air space around the perimeter of the  
unit.  
: All local codes and ordinances take precedence with regard to selection and  
installation of oil storage tank and oil supply (and return) lines. In the absence of local  
codes, all tanks and lines must be selected and installed according to the instructions in  
this manual and the Standard for the Installation of Oil-Burning Equipment, NFPA 31-  
1997, or the latest edition.  
: Turn off power to furnace. Before the oil piping system is placed into  
service, it must have been leak tested by a qualified heating contractor.  
6
All installations and services must be performed by qualified service personnel.  
: For initial start-up of the appliance after installation, it may be necessary to  
purge the air out of the oil line. A qualified heating contractor should do this.  
: If you do not follow these instructions exactly, a fire or explosion may  
result causing property damage, personal injury or loss of life.  
: Do not run the oil pump dry for more than five minutes, as irreparable  
damage may result.  
: Before troubleshooting, familiarize yourself with the start up and check out  
procedures.  
: Never burn garbage or refuse in this appliance. Never try to ignite oil by  
tossing burning papers or other material into the combustion chamber.  
: Oil-fired appliances produced by Thermo Products are designed for burning  
No. 2 distillate (domestic heating) fuel oil. Never use gasoline or a mixture of oil and  
gasoline.  
I
: Do not attempt to make repairs yourself. Contact your local qualified heating  
contractor.  
: This appliance is designed to directly vent combustion products into  
the atmosphere through, and using only, the supplied vent terminal. Do not  
attempt to attach a vent connector or a vent system to, or in place of, the supplied  
vent terminal.  
: Do not attempt to operate the cooling section on a day when outdoor  
temperatures are 45°F or cooler.  
7
All installations and services must be performed by qualified service personnel.  
: Carefully read and thoroughly understand the following guidelines and  
warnings before continuing with the installation of this appliance. Failure to  
follow these guidelines can cause improper and unsafe operation of this  
appliance. Unsafe operation can result in substantial property damage, severe  
personal injury, or death.  
1. This appliance shall be used with only the type of fuel oil for which it is approved.  
Refer to the appliance-rating label for the required type of fuel.  
2. This appliance is a single, packaged, oil-fired furnace with air conditioner designed  
for outdoor installation on either combustible or non-combustible materials. This  
appliance is also approved for rooftop installation on combustible or non-combustible  
roofing materials.  
3. Ensure that adequate combustion and ventilation air is available to the unit.  
4. The airflow resistance of the duct system attached to this appliance must fall within  
the allowable external static pressure range for this unit. Refer to the Airflow  
Requirements and Sizing of Ductwork section of this manual.  
5. Make sure supply and return air ducts are completely sealed to the appliance  
casing. Refer to the Airflow Requirements and Sizing of Ductwork section of this  
manual.  
8
All installations and services must be performed by qualified service personnel.  
II. GENERAL INSTRUCTIONS  
The entire text of these instructions must be read and understood, before installing the  
appliance. It is the installer's responsibility to do the following:  
1. Inform and demonstrate to the user, the correct operation and maintenance of  
the appliance, as explained in the Homeowner/User Information and Routine  
Maintenance section of this manual.  
2. Inform the user of the hazards of flammable liquids and vapors and to remove  
such liquids and vapors from the vicinity of the appliance.  
3. Inform the user of all pertinent warnings and precautions concerning this  
appliance.  
III. GENERAL INSTALLATION  
: This unit is not to be used for temporary heating of buildings, or  
structures, under construction. Construction dust may enter the appliance or the duct  
system and cause a fire hazard. Certain chemicals used during construction when  
burned, form corrosive condensate that can substantially reduce the life of the heating  
system heat exchanger.  
With exception of the vent terminal, this appliance is shipped completely assembled and  
internally wired. All fuel oil and refrigerant piping, refrigerant charge, and electrical wiring  
have been factory installed and inspected. At the time of installation, the unit will require  
connection to electric power, fuel oil supply, condensate drain, and supply and return air  
ductwork. In addition, the vent termination kit will need assembly. In the event of a  
shortage of parts or damage, refer to the Dealer Receiving and Freight Claim  
Procedure section of the Price Guide.  
This unit uses a fan-assisted combustion system, consisting of a pressure atomizing, oil  
burner and combustion air blower, used to push the products of combustion through the  
heat exchanger system. After installation, the furnace and duct system must be  
adjusted to obtain a temperature rise of 50°F to 80°F through the unit. (Refer to the  
rating label located on side panel inside the burner compartment). The installation must  
conform with local codes or, in the absence of local codes, with the Standard for the  
Installation of Oil-Burning Equipment, NFPA 31-1997, or the latest edition, and to these  
instructions.  
9
All installations and services must be performed by qualified service personnel.  
A. Codes and Clearances:  
The following items must be considered when choosing the size and location of  
the unit.  
1. All local codes and/or regulations take precedence over the instructions  
in this manual and should be followed accordingly. In the absence of local  
codes, installation must conform to these instructions and the guidelines of the  
National Fire Protection Association (NFPA). Two applicable NFPA installation  
codes are the National Electrical Code, ANSI/NFPA 70-1999, and Standard for  
the Installation of Oil-Burning Equipment, NFPA 31-1997. The latest editions of  
these codes should be consulted.  
2. The selection of a heating unit should be based on a rate of heat loss  
calculation for the residence according to the manuals provided by the Air  
Conditioning Contractors of America (ACCA) or the American Society of  
Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE). The  
heating capacity of the unit proposed for installation should meet or slightly  
exceed the rate of heat loss for the residence. Oversizing should not exceed  
125% of the heat loss calculation.  
3. When installed, this unit should be level. If possible, it should be installed in a  
central location, with respect to outlet registers of the supply air ductwork.  
4. Definitions of "combustible" and "non-combustible" materials as presented in  
the 1996 version of the National Fuel Gas Code, ANSI Z223.1-1996/NFPA 70-  
1996, are as follows:  
a. Combustible material:  
“...materials made of or surfaced with wood,  
compressed paper, plant fibers, or other materials that  
are capable of being ignited and burned. Such materials  
shall be considered combustible even though  
flameproofed, fire-retardant treated, or plastered.”  
b. Non-combustible material:  
“...material that is not capable of being ignited and  
burned; such as material consisting entirely of, or a  
combination of, steel, iron, brick, concrete, slate,  
asbestos, glass, and plaster.”  
10  
All installations and services must be performed by qualified service personnel.  
5. Table 1 lists the required minimum clearances to combustible surfaces from  
the outer surfaces of the appliance.  
Table 1: Minimum Clearances to Combustible Materials  
Model Top  
Side Rear Front  
Bottom Vent Terminal  
(in.) (in.)  
No.  
(in.)  
(in.)  
(in.) (in.)  
OPB  
-
3
3
3
0
3
The minimum clearances listed in Table 1 are for fire protection purposes  
only. Adequate operational and service clearances must be maintained under  
all circumstances. A minimum of 36 inches clearance around the  
condenser coil should be maintained for adequate airflow to the unit. Any  
overhanging material or construction must not block from above the  
condenser fan and the vent terminal. The suggested minimum clearances  
for servicing the front of the unit and to all points requiring access are at  
least 24 inches.  
Notice: Access panels for the return air filter and the blower motor are  
located on the rear left-hand and right-hand sides of the unit,  
respectively.  
6. Install this unit outdoors only.  
7. This appliance is approved for use as a forced air furnace with cooling unit.  
8. This appliance has been designed for use with no. 2 distillate fuel (domestic  
heating) oil.  
B. Selection of Installation Location  
1. The unit should not be placed in a position where it is directly exposed to  
sunlight during the majority of the day. Inside corners on the southeast and  
southwest sides of the structure should be avoided. Heat build-up due to  
solar radiation in such corners would place an increased cooling load on the  
unit. Shaded areas on the north side of the structure are preferred.  
2. The unit must be located on a level, dry surface in an area, which is free and  
protected from excessive drafts or wind. Mount the unit on a sturdy base at  
least one inch above the ground or roof surface. A poured concrete slab, or  
equivalent, is ideal. If concrete blocks or bricks are used, be sure to use well-  
tamped gravel fill beneath the blocks or bricks to prevent settling.  
Notice: Do not install the unit on any type of combustible base.  
11  
All installations and services must be performed by qualified service personnel.  
The unit is manufactured with runner supports that raise the unit, about 1.25  
inches above the mounting base, allowing air circulation beneath the metal  
surfaces. This clearance helps to promote air circulation under the base that  
allows the unit to be mounted on combustible materials. This clearance also  
helps to reduce metal corrosion caused by a buildup of moisture under the  
appliance.  
3. The cooling system condenser must have an unrestricted supply of air for  
efficient cooling.  
4. The cooling system fan discharges air, upward through the top grill. For this  
reason, this appliance should not be located under an overhang or any other  
obstruction to airflow that would redirect the heated discharge air back into  
the condenser. The appliance should be located as illustrated in Figure 1,  
below.  
Figure 1: Selection of Appliance Installation Location  
12  
All installations and services must be performed by qualified service personnel.  
For proper and safe operation of this appliance, ensure that adequate  
clearances around air openings into the burner compartment and the  
condenser coil area are maintained. These openings are not to be blocked, or  
restricted, in any manner.  
5. Measures should be taken to prevent the entry of corrosive chemicals  
or vapors to the combustion and ventilation air supply. Such chemicals  
include, but are not limited to, chlorinated and/or fluorinated hydrocarbons.  
These substances are found in refrigerants, aerosol propellants, dry cleaning  
fluids, degreasers, and removers. Other harmful compounds may come from  
acids, salts, bleaches, air fresheners, cements, and glues. Do not store or  
use these chemicals for long periods of time in close proximity to this  
appliance.  
Vapors from such products can form corrosive compounds when burned in a  
flame. These compounds promote rapid corrosion of the burner, combustion  
chamber, heat exchanger, and the vent terminal. Rapid or excessive  
corrosion will significantly reduce the useful life of the appliance.  
6. Refer to the following section, Venting of Combustion Products, for  
additional installation location restrictions.  
C. Venting of Combustion Products  
: This appliance is designed to directly vent combustion products  
into the atmosphere through, and using only, the supplied vent terminal.  
Do not attempt to attach a vent connector or a vent system to, or in place  
of, the supplied vent terminal.  
The appliance should be installed in a location such that heavy snow  
accumulation will not excessively restrict the flow of flue (combustion) products  
from the unit. The vent terminal should not be located in a position where ice  
buildup could block the discharge of flue products. If these conditions occur, the  
performance of the heating system will be adversely affected.  
Choose an installation location where the vent terminal does not discharge over  
sidewalks, walkways, and patios. These areas may become slippery when  
wetted by water vapor in the flue products.  
Combustion products must not be allowed to accumulate within a confined space  
and recirculate back into the combustion system. Recirculation of combustion  
products promotes poor combustion. In severe cases, it may lead to sooting of  
the combustion chamber and heat exchanger, or to nuisance shutdowns of the  
heating system.  
13  
All installations and services must be performed by qualified service personnel.  
In addition, long term exposure of building materials to combustion products may  
cause discoloration of material surfaces and corrosion or degradation of  
materials. The preferred installation location will allow combustion products to  
freely escape the immediate area of the appliance and rapidly disperse into the  
atmosphere, without being drawn back into the appliance or a nearby structure.  
To prevent combustion products from entering a structure, the vent terminal must  
expel combustion products away from any point of entry. The minimum  
acceptable distances from the vent terminal to points of entry to a building are 4  
feet horizontally from, and 1 foot above, or at least 4 feet below, any window,  
door, or gravity air inlet into the building. And, 3 feet or more above any forced  
air inlet to the building located within 10 feet of the terminal.  
Once the unit is installed in a suitable location, the installer must mount the vent  
terminal to the appliance. Two sheet metal screws are installed in the unit for this  
purpose. Refer to Figure 2 for a sketch of the correctly assembled vent terminal.  
FIGURE 2: Vent Terminal Mounting Position  
D. Condensate Drain  
This appliance is equipped with a ¾ inch PVC stubbed drain extension for  
connection of a condensate line to the evaporator drain pan. A condensate  
removal line should be fabricated and attached to the PVC drain extension, refer  
to Figure 3. The condensate drain line must be pitched downward to drain  
properly. The drain line can also be trapped and the condensate pumped to a  
suitable drain. If the drain line clogs, when the air conditioner is operating, the  
condensate tray under the evaporator coil will fill with water. As a result, water  
may enter the appliance housing and the supply air ductwork to the structure.  
14  
All installations and services must be performed by qualified service personnel.  
Figure 3: Installation of a Condensate Drainage Line on the Evaporator Coil  
Condensate from the evaporator is non-corrosive and may be disposed of in any  
appropriate manner. The drain connection should be sealed at the appliance  
housing to prevent air leakage from the supply air system. Pipe sealant should  
be used sparingly on all male pipe threads. Always consult and conform to the  
requirements of local plumbing codes.  
E. Oil Tank and Piping  
: All local codes and ordinances take precedence with regard to  
selection and installation of oil storage tank and oil supply (and return)  
lines. In the absence of local codes, all tanks and lines must be selected  
and installed according to the instructions in this manual and the Standard  
for the Installation of Oil-Burning Equipment, NFPA 31-1997, or the latest  
edition.  
1. The use of black steel pipe and malleable iron fittings is recommended for  
all fuel oil service lines. Never use galvanized steel piping or fittings  
for any fuel oil lines.  
2. Where practical, provide rigid supports for the piping.  
3. If the piping size in a run must be reduced, use reducing couplings only.  
Avoid the use of reducing bushings.  
4. Remove all pipe thread burrs and inspect the pipe for dirt or other foreign  
material prior to connecting. If present, remove any deposits in the piping  
and discard any excessively corroded piping.  
15  
All installations and services must be performed by qualified service personnel.  
5. A readily accessible, design-certified, manual oil shutoff valve, with a non-  
displaceable rotor member, shall be installed in the fuel oil supply piping  
within 6 feet of the appliance.  
6. A pipe union, or flanged connection, shall be provided downstream from  
the manual oil shutoff valve to permit removal of the appliance oil pump.  
Pipe unions must be the ground joint type or flanged-jointed using a  
gasket resistant to the corrosive action of fuel oils.  
7. Pipe dope or thread sealant design-certified to be resistant to the action of  
fuel oils should be used on all threaded joints. Thread sealant should only  
be applied to the male member of a joint. The first two threads on the end  
of the male member of each pipe joint should be clean and free from  
thread sealant.  
8. Connection of the oil supply piping to the appliance should be made from  
the left-hand side of the burner, facing the burner compartment cover.  
9. When tubing is to be used for fuel oil supply lines, use of continuous runs  
of heavy wall copper tubing is recommended. Avoid running tubing  
against any type of heating unit and across ceiling or floor joists. If  
possible, install the tubing under the floor.  
10. Where tubing is used for fuel oil supply lines, insure the tubing contains no  
kinks, sharp bends, or collapsed regions where the inside cross-sectional  
area of the tube is greatly reduced. These will excessively reduce the flow  
of oil.  
11. Flared fittings should be used at all tube joints, when tubing is used for  
fuel supply lines. Do not use compression fittings. Avoid the use of  
tube fittings in inaccessible locations.  
Burners are equipped with a single-stage, fuel pump. This type of fuel pump,  
when connected with a supply line only, is satisfactory where the fuel supply is  
level with, or above the burner thus permitting gravity flow of oil to the burner. If  
the tank is above the burner, and gravity oil feed to the burner is permitted, a  
single line system may be used. The line should have a gradual slope downward  
of approximately 1/2 inch per foot, or more, from the tank to a point directly below  
where it is connected to the pump. Pitching the line upward toward the tank will  
help prevent the formation of air pockets in the line.  
NOTICE: An oil safety valve or a delayed-action, solenoid valve should be  
installed in the oil supply line of all gravity-fed systems.  
16  
All installations and services must be performed by qualified service personnel.  
When the oil tank is located below the level of the burner, it is necessary to “lift”  
the oil to the burner. A return line should be connected between the fuel pump  
and tank. This requires insertion of the "by-pass" plug into the fuel pump. If the lift  
(vertical distance between the supply line inlet and the burner) exceeds  
approximately 10 feet, a two-stage pump should be installed with a return line.  
When a return line is used with either single or two-stage pumps, in-line air is  
automatically returned to the tank, making the oil pump and lines self-purging.  
Underground tanks should be located outside the building. Installation of above  
ground tanks is permitted inside buildings, under certain conditions, as well as  
outside. Consult the Standard for Installation of Oil-Burning Equipment for  
restrictions. If permitted, connect the burner oil supply line near the base of the  
tank, opposite of the fill end. Connection at this point tends to flush older oil  
through and out of the tank. This helps to prevent the accumulation of rainwater  
and condensed water vapor in the tank, which can cause the tank to corrode.  
If the oil supplier does not already use oil additives, it is recommended that  
additives be used to emulsify any water accumulation in the oil.  
F. Oil Filter  
It is strongly recommended that an oil filter assembly be installed in the oil supply  
line to the unit. The OPB has been shipped with a pre-mounted oil filter. Should  
the filter need to be changed, replace with a similar or better filter with the  
capacity to trap a 40-50 micron particle.  
The filter cartridge should be replaced at least once a year. The filter body should  
be thoroughly cleaned before installing a new cartridge.  
G. Burner Specifications And Performance  
The model OPB has been factory equipped with the Beckett AFG oil burner. A  
.60 gal. X 80° A nozzle has been factory installed to provide low-fire operation.  
Table 2 gives the burner specifications, estimated input/output performance and  
the required nozzle size for high-fire operation.  
Note: High-fire nozzle is not included with OPB.  
17  
All installations and services must be performed by qualified service personnel.  
Table 2: Burner Specifications and High and Low Fire Heating Performance  
Oil  
Heat  
Oil Pump  
Pressure  
(PSIG)  
Heat Input  
Rate*  
(BTUH)  
Heating  
Mode  
Flowrate @  
Nozzle  
Output Burner Model  
Rate**  
(BTUH)  
Air Tube  
Combination  
Nozzle  
Type  
Number  
(GPH)  
2 0.75  
Simplex, 80  
AFG-TP1502 AF42 BNHSSS deg., hollow  
cone  
High Fire  
Low Fire  
130  
120  
105,000  
85,000  
85,000  
67,000  
1 0.6  
* Based on #2 fuel (domestic heating) oil having higher heating value of 140,000  
BTU per gallon.  
** Based on an assumed steady state, thermal efficiency of 80%.  
1 Factory installed.  
2 Provided by installer.  
For more specific burner information, consult the Model AFG Oil Burner  
Instruction Manual or contact Thermo Products, LLC. P.O. Box 217, North  
Judson, IN 46366. Phone no. 574-896-2133.  
18  
All installations and services must be performed by qualified service personnel.  
H. Airflow Requirements and Sizing of Duct Work  
The duct system must be sized and installed by a qualified installer or service  
person, following the design standards of the Air Conditioning Contractors of  
America (ACCA) or the American Society of Heating, Refrigeration, and Air  
Conditioning Engineers (ASHRAE). This furnace has been designed to  
operate against a maximum external static pressure of 0.4 in. W.G. This is  
equivalent to .2 in. W.G. supply and .2 in. W.G. return pressure drops.  
1. Supply and return air ducts have to be furnished by the installer and run  
between the appliance, which must be installed outdoors, and the interior of  
the structure the appliance serves. These ducts must be sealed to the casing  
of the appliance.  
2. To reduce the transmission of vibration and noise to the duct system and to  
reduce flexure of the duct system due to thermal expansion and contraction, it  
is recommended that flexible joints be installed at the supply and return duct  
connections to the unit.  
3. The return air duct system must equal the supply air duct system in the flow  
capacity (CFM) for a given pressure drop. Use a supplier's catalog for proper  
sizing of outlet and return air registers and grills to ensure that they meet the  
flow requirements of the run to which they are connected.  
4. The duct system shall be sized to provide the maximum air flowrate (CFM)  
required of the installation. Two common rules for determining minimum  
airflow in heating and cooling systems follow:  
a. For heating, 14 CFM of airflow are required per 1000 BTU/hr of heat  
output, based on steady state operation and a 50° to 80° temperature rise.  
b. For cooling, 400 CFM of airflow are required per ton of air conditioning.  
(For reference, a ton of A/C = 12,000 BTU/hr removed from the space.)  
Refer to Example 1, in Appendix B: Calculations of this manual, for a  
sample calculation of how to determine the required minimum air flowrate.  
5. Duct sizing is based upon both air velocity and pressure drop considerations.  
When possible, current practice favors designing ductwork for lower air  
velocities. (For residences, a maximum air velocity of 800 FPM is suggested.)  
This results in quieter duct systems, systems which require less fan power  
(reduced operating costs), and less carefully constructed ductwork (lower  
initial costs).  
However, lower air velocities also result in larger duct sizes than necessary at  
higher velocities. In some cases, space restrictions may limit the ductwork to  
smaller than optimal sizes.  
19  
All installations and services must be performed by qualified service personnel.  
6. The following method can be used to size ductwork when air velocities are  
low to moderate.  
a. Using a floor view of the residence, determine, or layout, the locations of  
the supply registers and the return air grills. (Generally, supply registers  
should be located close to sources of heat loss, i.e. windows and doors,  
around the perimeter of the building. Return grills should be located in  
central positions as far away from the supply registers as practical.)  
b. Find a location for the appliance outside the building that minimizes the  
amount of ducting required to connect the appliance to the supply and  
return air duct systems. Consider issues of access to the oil supply and  
electrical service, required service and venting clearances, exposure to  
sunlight, and operating noise when selecting this location.  
c. Plan an efficient layout for the ductwork connecting each of the supply  
air registers in the supply system to the unit. Plan and layout ductwork  
connecting each of the return air grills in the return system to the unit.  
Measure or estimate the length of duct between each register and grill.  
d. Select values for the airflow through each register and grill.  
e. Select values for the pressure drops of both the supply and return air  
systems. Each branch of the supply (or the return) air system will have  
this pressure drop. The total pressure drop of the supply and return air  
systems added together cannot exceed the maximum external static  
pressure that can be supplied by the appliance blower.  
f. Determine the required flowrate for each branch of the supply and return  
air systems. The total air flowrate, by adding the air flowrate of each  
branch of the supply system, must equal the minimum required air  
flowrate (refer to part 3, above). Likewise, the air flowrate of each of the  
branches of the return air system must sum to the required minimum  
flowrate.  
g. Using the selected air flowrates for each component of the duct system  
and manufacturer’s literature, or published literature on duct system  
pressure drops, the pressure drop for each component in the duct  
system can be estimated.  
(Chapter 32 of the ASHRAE Handbook – Fundamentals is an excellent  
source of duct system design principles and pressure drop data.)  
Conversely, for a specified type of fitting, it is also possible to determine  
the required size or diameter of the component for a specified pressure  
drop and flowrate.  
20  
All installations and services must be performed by qualified service personnel.  
h. The resistance of the take-off and the outlet register (or return grill)  
should then be summed together to determine the total pressure drop for  
each branch. This value should be close to the assumed value for the  
pressure drop of the system. If it is not close, then flowrates for each  
branch must be adjusted, or the design of the duct system must be  
altered, to give the proper pressure drops. Usually, the cross-sectional  
area of the ductwork should be changed in order to adjust the pressure  
drop to a suitable value.  
Refer to Example 2, in Appendix B: Calculations of this manual, for a  
sample calculation of how to use this method for sizing the supply side  
ductwork for a residence.  
Table 3 shows the air handling capacities of 100-ft. lengths of circular and  
rectangular ductwork based on a 0.1 in. W.G. static pressure drop. The first  
column to the right is the air flowrate and the second is the required diameter  
for a circular duct. The third column is the required cross-sectional area of the  
duct and the other columns to the left are rectangular ducts with sufficient  
cross-sectional area to handle the flow at the specified pressure drop. [For  
lengths of ductwork less than 100 ft., simply multiply 0.1 in. W.G. by the ratio  
of the actual duct length (in feet) over 100 ft. for the approximate pressure  
drop.] Use the supplier’s catalog for proper sizing of outlet air registers and  
return air grills to insure that they provide the required flowrate at the desired  
pressure drop.  
21  
All installations and services must be performed by qualified service personnel.  
Table 3: Suggested Duct Sizes for Homes, Quiet Offices, Or Similar Installations  
(Based on a 0.1 in. W.G. static pressure drop per 100 ft. of duct.)  
7. The supply and return air ducts, or flexible joints, should be carefully secured  
and sealed to the appliance housing to prevent air leakage from, or into, the  
duct system. For best performance, insulate the outside surfaces of the ducts  
to reduce heat loss from, or heat gain to, the ducts. The insulation system  
should be carefully selected and installed to minimize water and moisture  
absorption by the insulation.  
22  
All installations and services must be performed by qualified service personnel.  
8. As a final step in the installation, the appliance must be adjusted to deliver a  
temperature rise within the range of 50° to 80°F. Adjust the blower motor  
speed to obtain a temperature rise within the acceptable range. The required  
blower speed will depend on the airflow resistance of a supply and return air  
duct systems.  
I. Air Filters  
1. Filter Installation  
This OPB unit has been factory supplied with a high quality, re-usable filter  
rated for air velocities up to 600 ft/min.  
2. Use of non-Thermo Pride Filters or Retention Means  
:
Failure to comply with minimum filter installation  
requirements may affect the performance and/or void the warranty on  
this unit.  
If a method other than Thermo Pride filter racks is selected for retention of the  
filter and/or use of a different filter type is desired, refer to Table 4 for  
minimum sizing guidelines for selecting filter for the unit.  
Table 4: Minimum Required Filter Area (in square inches)  
Maximum  
Filter Type  
Air Velocity  
(ft/min)  
Model Number  
OPB24 OPB30 OPB36  
*Thermo Products  
Supplied  
600  
500  
300  
192  
230  
384  
240  
288  
480  
288  
346  
576  
Permanent  
Standard  
Permanent  
Disposable  
The Thermo Products supplied filter can be cut to size to fit other filter  
retention systems as long as the minimum size requirement is met.  
NOTICE: Any internal stiffeners used in the filter must not be removed,  
although they can be cut to size as needed.  
23  
All installations and services must be performed by qualified service personnel.  
J. Electrical Wiring  
: This appliance must be grounded in accordance with local  
codes, or in the absence of local codes, with the National Electrical Code,  
ANSI/NFPA 70-1999, or the latest edition.  
: Waterproof type connectors must be used when connecting  
electrical power and control wiring to the unit to prevent moisture from  
being drawn into the unit during operation.  
All wiring must conform to the provisions of local codes or, in the absence of local  
codes, with the provisions of the National Electrical Code, ANSI/NFPA 70-1999,  
or the latest edition, and this instruction manual.  
This appliance requires 208-240 VAC, 60 Hz, single-phase power. Refer to Table  
5 for typical electrical current draws of the individual appliance motors,  
recommended sizes for over-current and short circuit devices, and minimum  
recommended field wiring sizes. Electrical service must be brought to the unit  
from a circuit breaker, or fused disconnect switch, in accordance with local  
codes. The disconnecting switch must be located reasonably close to and within  
sight of the unit.  
Three-wire service, two “hot” leads (L1 and L2) and a neutral (N), plus a ground  
conductor, is required. Connect power to the appliance control system at the  
junction box in the burner compartment. (A knockout fitting is provided on the  
exterior of the burner compartment for this purpose.) A ground wire must be  
connected to the grounding lug, or screw, marked “Equipment Ground”, in the  
junction box.  
Field wiring of power circuits to the appliance should consist of copper  
conductors rated for at least 240 VAC with an insulation temperature rating of at  
least 75°C temperature rise. Depending upon code requirements, rigid or flexible  
conduit is recommended, and may be required. Connect the electric power  
supply as shown in the wiring diagram located on the inside of the burner  
compartment cover, or in this manual. The cooling system operates on 208-240  
VAC electric power, from supply wires L1 and L2. The heating system operates  
on 120 VAC electric power, from supply wires L1 and N.  
24  
All installations and services must be performed by qualified service personnel.  
Typically, control wiring between the outdoor appliance and the indoor  
thermostat, and if used, electronic air cleaner or humidifier, will be required. Field  
wiring of control circuits should consist of copper conductors rated for at least  
240 VAC with an insulation temperature rating conforming to Type T wire, 35°C  
temperature rise. Depending upon code requirements, rigid or flexible conduit is  
recommended, and may be required. Make connections between the thermostat,  
and electronic air cleaner or humidifier (if used), and the fan control module,  
inside the burner compartment. Consult the wiring diagram for the appropriate  
connection points on the thermostat and the fan control module.  
Table 5: Typical Electrical Requirements for Various OPB Models  
Oil  
Recommend  
ed Time  
Delay Type Recommended  
Fuse or 75 deg. C.  
Inverse Time Copper Power  
Circuit  
Breaker Size  
(Amps)  
Maximum  
Time Delay  
Type Fuse  
or Inverse  
Time Circuit  
Breaker  
Compressor Compressor Condenser Supply/Retur Burner  
Minimum  
Running  
Load  
Current  
Locked  
Rotor  
Current  
Fan Full n Air Blower Assembly  
Potential/Frequency  
/No. of Phases  
(V/Hz/Ph)  
Load  
Current  
Full Load Full Load  
Current Current  
(Amps) @ (Amps) @ (Amps) @ (Amps) @ (Amps)  
Model  
Wiring Size  
(AWG)  
200 VAC  
200 VAC  
200 VAC  
115 VAC  
@ 115  
VAC  
Size (Amps)  
OPB24  
OPB30  
15  
14.3  
58.3  
64  
40  
40  
30  
30  
10  
10  
208-240/60/1  
0.8  
9.6  
5.8  
OPB36  
18.6  
79  
50  
35  
8
OPB42  
18 4  
95  
50  
35  
8
Wire size selections in Table 5 are based upon Table 310-16 of the National  
Electrical Code for three copper conductors, with insulation rated for 75 degrees  
Celsius, contained in raceway at 30 degrees Celsius. For other wire insulation  
temperature ratings and ambient conditions, refer to the National Electrical Code  
for the minimum wire sizing requirements.  
NOTICE: Before the unit is started, the installer and/or electrician must  
check the following items.  
1. Check every electrical connection of “push-on” or “screw-on” type terminals to  
ensure that all wires and wire connectors are firmly secured. A loose terminal  
can cause poor flow of electrical power to motors and to the refrigeration  
compressor. This may result in very high current draws by these components.  
If great enough, high current draw will cause blown fuses, burned wires and  
contactor points, and pre-mature motor or compressor failure. Each electrical  
connection has been factory checked, however, connections may loosen, due  
to vibration, while the appliance is in transit. Please be certain that all  
electrical connections remain tight.  
2. Review wiring diagram for proper routing and connection of all field wiring.  
25  
All installations and services must be performed by qualified service personnel.  
3. All wiring sizes must comply with local codes or the National Electrical Code.  
To minimize voltage drop to the appliance, the next larger size wire should be  
used when long wiring runs, in excess of 100 ft., are employed. Refer to the  
wiring diagrams when wiring or servicing.  
NOTICE: Proper operation of the heating section of this unit depends upon  
correctly connecting the electrical power source. The hot leg, L1, of the  
supply circuit must be connected to the black line lead and the neutral leg,  
N, to the white line lead in the burner compartment junction box. All  
ungrounded circuit conductors must be broken by the disconnecting  
switch to prevent the hazard of electrical shock when servicing this  
appliance.  
In the event a circuit breaker trips or a fuse blows as a result of the operation of  
this appliance, investigate the appliance electrical system to determine the  
cause. Correct any electrical faults and abnormal conditions before putting the  
unit back into operation. Do not put in a larger fuse and do not exceed  
maximum fuse size listed on the rating label in order to temporarily “fix”  
the problem. The rating label is located on the inside of the burner compartment  
cover.  
The appliance control system contains a 15 amp. circuit breaker to protect  
the heating system control circuitry. The control fuse is located within the  
junction box, which is located in the burner compartment. In the event of a main  
circuit breaker trip, this may need to be reset as well.  
1. Electronic Air Cleaner (EAC) and Humidifier Installation  
The fan timer on this unit has designated terminals to control the operation of  
an electronic air cleaner and/or humidifier. These terminals provide line  
voltage for the control of these accessories, refer to Figure 4.  
Connection between EAC and N6 provides a switched 115 vac to power an  
electronic fan cleaner.  
The same switched 115 vac is available between Fan and N7 and may be  
used in conjunction with a humidistat to control a humidifier.  
These terminals are energized whenever the blower is active.  
26  
All installations and services must be performed by qualified service personnel.  
Figure 4: The Fan Control Module  
NOTICE: It is important to confirm that the operating voltage of the  
humidifier or EAC being installed matches the output of this control. If  
not, a field supplied relay or transformer may be necessary to provide  
the proper control and supply voltage for the accessory being installed.  
Refer to the manufacturer’s instructions for the humidifier or EAC for  
additional information.  
27  
All installations and services must be performed by qualified service personnel.  
2. Thermostat Anticipator Setting  
Proper control of the indoor air temperature can only be achieved if the  
thermostat is calibrated to the heating and/or cooling cycle. Calibration will  
help to produce a more constant indoor temperature by adjusting the length of  
the heating/cooling cycle to fit the application. A vital consideration of this  
calibration is related to the thermostat heat anticipator.  
The proper thermostat heat anticipator setting is 0.1 ampere. To increase the  
length of the cycle, increase the setting of the heat scale; to decrease the  
length of the cycle, decrease the setting of the heat scale.  
Anticipators for the cooling operation are generally pre-set by the thermostat  
manufacturer and require no adjustment.  
Anticipators for the heating operation are of two types, pre-set and adjustable.  
Those that are pre-set will not have an adjustment scale and are generally  
marked accordingly.  
Thermostat models having a scale as shown in Figure 5 must be adjusted to  
each application.  
Figure 5: Heat Anticipator Adjustment Scale  
In many cases, this setting can be found in the thermostat installation  
instructions. If this information is not available, or if the correct setting is  
questioned, the following procedures should be followed:  
28  
All installations and services must be performed by qualified service personnel.  
Preferred method of adjustment:  
Using an analog ammeter on the lowest scale, such as an Amp Check,  
connect the meter across terminals “R” and “W” on the sub-base (“RH” &  
“W” on an isolating thermostat sub-base). If the reading is too low to move  
the needle on to the measurement scale of the instrument, proceed as  
follows.  
i. Wrap 10 loops of single strand, insulated, thermostat wire around the  
prongs of an ammeter, refer to Figure 6. Set the scale to the 1 to 5 or 1  
to 6 amp. scale.  
Figure 6: Analog Ammeter w/ Wire Loops to Boost Reading  
ii. Connect the bare ends of this wire jumper across terminals “R” and  
“W” on the sub-base (“RH” and “W” on an isolating thermostat sub-  
base). This test must be performed without the thermostat attached to  
the sub-base.  
iii. Let the heating system operate in this position for about one minute.  
Read the amp meter scale. Regardless of the value of the meter  
reading, divide the value by 10 (for 10 loops of wire).  
This formula can be used to calculate the correct setting for the  
adjustable heat anticipator:  
Ammeter reading = Anticipator Setting.  
No. of wire loops  
29  
All installations and services must be performed by qualified service personnel.  
Or in this case,  
_2.5 A. = 0.25 A. (Anticipator Setting)  
10  
iv. Adjust the position of the anticipator indicator to match the calculated  
ammeter setting. If a slightly longer cycle is desired, the pointer should  
be moved to a higher setting. Slightly shorter cycles can be achieved  
by moving to a lower setting.  
v. Remove the meter jumper wire and reconnect the thermostat. Check  
the thermostat in the heating mode for proper operation.  
If a digital ammeter is used, read the current draw directly from meter.  
(Steps 1 through 3 are not required.) The meter reading is the correct  
anticipator setting.  
3. Blower Motor Speed Selection  
: Turn off the electrical power to the unit, before attempting  
to change supply air blower speed wiring.  
The OPB comes from the factory with the proper cooling speed selected  
and the heat rise set to approximately 65°F on low-fire.  
The heat rise is determined by the nozzle size and the switch selection on  
the control board located in the vestibule compartment.  
Switches 1, 2 & 3 of switch block SW1 (the six switch red block) are used  
to select the proper blower speed. Please refer to the table below:  
SW1 POSITION  
LOW- HIGH FIRE  
FIRE HEAT RISE  
1
2
3
OPERATION IN THIS RANGE MAY FORCE THE  
SAFETY LIMIT TO OPERATE REDUCING  
PERFORMANCE  
OFF  
ON  
OFF  
ON  
OFF  
ON  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
ON  
ON  
ON  
74  
67  
64  
73  
67  
60  
ON  
FACTORY  
SET  
OFF  
OFF  
ON  
OPERATION IN THIS RANGE MAY CAUSE  
COMBUSTION GASES TO CONDENSE AND VOID  
THE WARRANTY  
ON  
30  
All installations and services must be performed by qualified service personnel.  
IV. STARTUP PROCEDURES  
A. Heating System  
1. Initial Startup:  
: Turn off power to furnace. Before the oil piping system is placed  
into service, it must have been leak tested by a qualified heating  
contractor.  
: For initial start-up of the appliance after installation, it may be  
necessary to purge the air out of the oil line. A qualified heating contractor  
should do this.  
Review the following items before the initial startup. It may be helpful to review  
the Sequence of Operations in Appendix D of this manual, also.  
a. Check all wiring for loose connections and proper hook-up. Refer to the  
connection diagram.  
b. Leak test all field oil piping connections. Generally, this will involve  
pressurizing the oil piping with air while being careful to isolate the oil tank at  
high test pressures. A qualified heating contractor should perform this  
service.  
c. Check to see that the vent terminal is correctly installed and the terminal  
openings are clear and free from blockage.  
d. Make sure the air filter is in place and relatively clean of dirt and debris.  
e. Make sure the thermostat is set in the heating mode of operation.  
31  
All installations and services must be performed by qualified service personnel.  
For Your Safety Read Before Operating:  
: If you do not follow these instructions exactly, a  
fire or explosion may result causing property damage,  
personal injury or loss of life.  
This appliance does not have a pilot light. It is equipped with  
an ignition system that automatically lights the burner. Do not  
attempt to light the burner by hand.  
Do not use this appliance if any part has been under water.  
Immediately call a qualified service technician to inspect the  
appliance and to replace any part of the control system and  
any oil control that has been under water.  
Operating Instructions:  
i. STOP! Read the safety information above.  
ii. Set the thermostat to the lowest setting.  
iii. Turn off all electric power to the appliance.  
iv. This appliance is equipped with an ignition system that  
automatically lights the burner. Do not try to light the burner by  
hand.  
v. Rotate the manual oil shutoff valve to the “ON” position.  
vi. Turn on the electric power to the appliance.  
vii. Set the thermostat to the desired setting.  
viii. If the appliance will not operate, call your qualified service  
technician or oil supplier.  
To Turn Off Oil to Appliance:  
i. Set the thermostat to the lowest setting and set the operating  
mode switch to “OFF”.  
32  
All installations and services must be performed by qualified service personnel.  
ii. If service is to be performed, turn off the electrical power to the  
appliance.  
iii. Turn the manual oil shutoff valve to the “OFF” position.  
2. Adjustment of Burner Combustion:  
: Maximum gross stack temperature must not exceed 550°F  
(288°C) under any circumstances.  
: Do not run the oil pump dry for more than five minutes, as  
irreparable damage may result.  
NOTICE: Read the burner operation and service instructions, Model  
AFG Oil Burner Instruction Manual, before continuing.  
To initially adjust and successfully service the oil burner in the appliance  
heating section, the following test instruments are required:  
A smoke density measuring and rating device,  
A carbon-dioxide (CO2) or oxygen (O2) analyzer,  
A flue gas temperature measuring device (e.g., thermocouple or  
thermister probe with readout device),  
An analog or digital multimeter, and  
An oil pressure gauge capable of reading 0-150 PSIG.  
To initially fire the oil burner, proceed in the following manner.  
a. Turn the disconnecting switch, which provides power to the  
appliance, to the "OFF" position.  
b. Set the room thermostat above room temperature.  
c. Verify the oil tank is filled with sufficient fuel oil to operate the  
appliance.  
d. Open all valves in the oil supply line to the burner.  
e. Remove the burner compartment cover from the appliance.  
33  
All installations and services must be performed by qualified service personnel.  
f.  
Open the inspection cover on the upper mounting plate above the  
burner.  
g. Turn the disconnecting switch to “ON”.  
h. Prime the pump to remove air in the oil supply line.  
i.  
When ignition is established, make a preliminary burner air  
adjustment to attain a clean combustion flame. Generally, the burner  
bulk air band should be about 3/16 inch open and the opening of the  
burner air shutter set in the range of “2” to “7”, refer to Figure 8.  
Figure 8: Preliminary Adjustment of Burner Air Band and Air Shutter  
Replace the inspection cover above the burner.  
j.  
After the appliance is warmed up to a steady state condition (about  
15 minutes), the final burner adjustment should be made using  
combustion instrumentation for smoke, carbon dioxide (CO2) or  
excess oxygen (O2), and flue gas temperature. In order to achieve the  
most efficient combustion, the following steps must be taken:  
i. SMOKE: A smoke sample should be drawn from the heat  
exchanger flue passageway, which is covered by the vent terminal.  
(Remove a large machine screw from the front face of the vent  
terminal for direct access to the flue through the opening.) If the first  
smoke reading is zero (0), close the air band, or shutter, on the  
burner until a trace smoke reading is measured.  
34  
All installations and services must be performed by qualified service personnel.  
NOTICE: To achieve proper combustion and the efficiencies  
listed in sales brochures, instruments must be used to secure  
CO2 or O2 readings.  
ii.  
CARBON DIOXIDE (CO2) OR OXYGEN (O2): Take a CO2 sample  
from flue passageway. It is possible to achieve readings of up to  
14% CO2 (or 2% O2 ), but it is better to have a slightly lower CO2 (or  
higher O2) reading with zero smoke measured. To achieve a lower  
CO2 reading, open the air band, or shutter, on the burner until zero  
smoke is measured.  
For example, if a 13% CO2 (or 3.5% O2) is recorded at a trace of  
smoke, open the air shutter until zero smoke is measured with a  
12% CO2 (or 4.5% O2).  
Adjustment of the burner to achieve a slightly lower CO2 reading is  
recommended, although it slightly reduces combustion efficiency, to  
keep the heating system within normal operating conditions though  
external conditions may vary. Some “out-of-spec” conditions which  
may adversely affect burner performance are, low oil supply  
temperature, dirty (contaminated) oil, low heating content (BTU/gal)  
oil, cold heat exchanger surfaces, and downdraft conditions. By  
adjusting the burner in this manner, an operational tolerance is  
established allowing the burner to function well, even under less  
than ideal conditions. This results in less service and maintenance  
during a heating season.  
iii.  
FLUE GAS TEMPERATURE: The flue gas temperature will vary to  
some extent depending on the heat input rate, duct design, and the  
amount of air flow across the heat exchanger. The suggested  
minimum net flue gas temperature is 3500 F, and the maximum  
gross flue gas temperature is 5500 F. The lower the flue gas  
temperature, the higher the heating efficiency. However, stack  
temperatures under 3500 F may result in condensation of water  
vapor in the flue gases, which in turn promotes corrosion of the  
heat exchanger.  
iv.  
TEMPERATURE RISE: Temperature rise is equal to the supply air  
temperature minus return air temperature. Under steady state  
operating conditions, the temperature rise across the heating  
section should be approximately 650F. A higher temperature rise  
will slightly lower the heating efficiency. A lower temperature rise  
will slightly raise efficiency, but may cause condensation.  
35  
All installations and services must be performed by qualified service personnel.  
The supply air temperature should be measured in the supply air  
trunkline approximately 12 inches downstream of the supply air  
outlet of the appliance.  
NOTICE: Minimum temperature rise is 500 F.; maximum  
temperature rise is 800 F.  
l. After final adjustments are completed, tighten all screws to fix the  
positions of the burner air band.  
m. Check for the presence of oil leaks. Correct any oil leaks found.  
n. Reassemble the burner compartment cover.  
o. Start and stop the unit several times while checking for proper ignition of  
the burner. The flame should ignite and stabilize without any significant  
rumbles or pulsations.  
3. Adjustment Of Heat Input Rate  
This appliance was shipped from the factory with one, fixed, main burner nozzle  
sized to produce the low-fire input rate using no. 2 fuel oil at the pump pressure  
shown on the rating label. The input rate can be changed to the high-fire by  
switching to the larger burner nozzle and increasing the pump pressure.  
The main burner oil nozzles for this unit were selected based upon the following  
assumed characteristic values of the fuel oil suitable for use with this appliance  
design:  
For no. 2 distillate fuel (domestic heating) oil having a higher heating value  
of 140,000 BTU per gallon and a specific gravity of 0.88 @ 60 deg. F. (or  
“gravity” of 30 deg. API @ 60 deg. F.).  
It is possible to make minor adjustments to the heat input rate by adjusting the  
pump pressure. Sizeable changes in input rate (especially reductions) should be  
made by replacing the burner nozzle. To adjust the pump pressure to the main  
burner:  
a. With the oil shut off, remove the 1/8 in. NPT threaded pipe plug located on  
the lower rear side of the oil pump, refer to Figure 13. Attach a pressure  
gage, capable of measuring pressure in pounds per square inch gage,  
PSIG, in this opening, on the discharge side, of the oil pump.  
NOTICE: It may be necessary to remove the oil pump to attach the  
plumbing required to connect a pressure gage to the pump.  
36  
All installations and services must be performed by qualified service personnel.  
b. Turn on the fuel oil and cause the appliance to activate the heating section  
by answering a “call for heat”.  
NOTICE: It may be necessary to bleed air from the oil line before the  
burner can be fired.  
c. Allow the heating section to operate for 10 to 15 minutes.  
d. Note the oil pressure at the pump.  
e. To adjust the pressure, use a common screwdriver to turn in the pressure  
adjustment screw, located on the upper front of the oil pump body.  
f. Allow the fuel flow rate to stabilize for a moment. Recheck the oil  
pressure.  
g. If required, repeat the oil pressure adjustment again.  
h. When the input rate adjustment has been completed, shut off the fuel oil to  
the appliance. Remove the pressure gage. Reinstall the pipe plug using a  
thread compound resistant to the action of LP gases and fuel oil.  
NOTICE: It may be necessary to bleed air from the oil line before the  
burner can be fired.  
To insure the combustion air supply is adequate, it is now necessary to repeat  
the steps in the previous Initial Burner Adjustment section of this manual.  
4. Setting Supply Air Temperature Rise  
: To avoid injury from moving parts or electrical shock, shut  
off the power to the appliance before removing supply air blower  
compartment door and servicing this appliance.  
All OPB models are designed and wired at the factory for a blower speed  
during heating that should result in an approximate temperature rise of 65°F.  
The temperature rise through the heating section, for any given blower speed,  
may vary depending on a number of factors. A few of these factors are  
variations in, the actual resistance of the duct system to airflow at any time,  
the return air temperatures, and the fuel oil heating value.  
Also, fouling of the heat exchanger surfaces will reduce temperature rise. In  
general, a lower temperature rise through the heating section will result in  
higher heating efficiency.  
Temperature rise = supply air temperature - return air temperature.  
37  
All installations and services must be performed by qualified service personnel.  
After 15 to 20 minutes of continuous operation, the temperature rise through  
the furnace must fall within a range of 50° to 80° F. If the outlet or supply  
duct temperature is too high, check to make sure the return air filter is clean,  
the return air registers are free from obstruction, the outlet registers are  
properly adjusted and clear, and the supply and return air ducts are open.  
The circulating air blower is not moving enough air if the supply air  
temperature is still too high. Before proceeding further, turn off the power  
supply to the appliance and remove the vestibule cover. The speed of the  
blower must be increased by changing the switch setting on the control board,  
please refer to the table in Section 3.  
5. Checkout Procedure  
Before any system of oil piping is finally put into service, it shall be carefully  
tested to assure that it is “gas-tight”, as indicated in the Heating System  
Initial Startup section of this manual.  
NOTICE: All controls on the unit should be checked for proper  
functioning prior to the qualified service personnel leaving the job site.  
Specifically the following should be checked:  
a. With heating system in normal heating operation, check to make certain  
blower will start and stop automatically under control of the indoor  
thermostat.  
b. Check safety limit control as follows:  
i. Shut off incoming power.  
ii. Block return air opening or disconnect blower motor leads.  
iii. Restore power to appliance.  
iv. In the heating mode, set the thermostat above room temperature  
producing “a call for heat”.  
v. When high air temperatures are reached within the heating section, the  
high limit control should act to shutdown the burner.  
vi. Shut off the electrical power.  
IMPORTANT: Remove blockage or reconnect blower motor and  
restore power.  
38  
All installations and services must be performed by qualified service personnel.  
c. Make certain the thermostat will automatically start and stop the  
appliance.  
NOTICE: Heat exchanger oil will burn off on initial firing creating an  
unpleasant odor. To prevent this odor from occurring more than once, it  
is suggested the heating section be allowed to run for 30 minutes, or  
until odor has dissipated.  
39  
All installations and services must be performed by qualified service personnel.  
B. Cooling Section  
1. Initial Startup:  
: Refrigerant is under pressure.  
Guard against refrigerant  
spraying into the face or on skin. Always wear protective equipment, i.e.  
safety glasses or goggles and gloves when working with refrigerant.  
: Do not under any circumstances heat the refrigerant cylinder  
with a torch or by any other means other than warm water. Excessive  
pressures generated in this manner may weaken the refrigerant container  
and result in an explosion!  
On cool days (65°F or lower), attempts to operate the cooling section and take  
gauged pressure readings may be unsuccessful as unusually low pressure will  
be observed on the suction line. This type of operation may give the impression  
of an undercharged unit. This is not necessarily the case. A low refrigerant  
pressure reading may occur due to the combined action of the large condenser  
surface area and cold ambient air removing a large amount of heat from the  
refrigerant. As a result, subcooling of the refrigerant occurs and very low  
refrigerant pressures can be measured. Adding refrigerant in cold weather will  
result in an overcharged unit. During warm or hot weather, high ambient  
temperatures will greatly increase the refrigerant pressure which may then cause  
the high limit pressure switch to shutdown the unit. Due to the high probability of  
taking a false reading, suction line pressure should not be taken for test purposes  
when the outdoor temperature is below 70° F.  
When the outdoor air temperature is cooler than the indoor air temperature,  
refrigerant vapor will condense in the compressor. If the compressor is started  
when it contains liquid refrigerant, the lubricating oil in the crankcase will be  
diluted. Bearing damage may result under these conditions.  
The appliance is equipped with gauge ports to connect both liquid and suction  
line pressure gauges. These ports are located near the base of the unit, inside  
the burner compartment. Refrigerant hoses must be the types that incorporate a  
“finger” to depress the valve core. Connections may be made to these ports at  
any time, even while unit is in operation. Follow EPA guidelines in connecting  
service equipment to refrigerant lines. For example, using quick connects and  
short service hoses is recommended to minimize refrigerant losses.  
Line pressures on an operating air conditioning unit will vary with outdoor  
temperatures. As outdoor temperatures rise, pressures will also rise. Refer to a  
pressure-temperature chart on the unit for approximate system line pressures at  
various temperatures.  
40  
All installations and services must be performed by qualified service personnel.  
The suction pressure and condenser subcooling are the most significant  
readings. If a unit is suspected of having a low refrigerant charge, the unit should  
be recharged using the suction pressure then topped off using subcooling. Any  
additional refrigerant may cause damage or unintended problems.  
The pressure/temperature chart on the wiring diagram is to serve only as a  
guide. Pressures shown are realistic averages which will vary somewhat with  
changes in air temperatures, air flowrate across the evaporator and condenser  
coils and humidity – both inside and outside.  
If a charge must be added to the system, connect to the suction service port of  
the service valve and add a vapor charge only while the system is operating.  
Addition of liquid refrigerant at the suction port may damage the compressor.  
2. Definition of Subcooling:  
Subcooling is extra heat removed from refrigerant below the saturation  
pressure/temperature of the refrigerant. A certain amount of refrigerant  
subcooling is usually beneficial and needed to help assure the best operation of  
the cooling system. Subcooling takes place in the condenser. It is a function of  
the amount of airflow into the condenser, the outside ambient air temperature,  
the refrigerant pressure into the condenser, and pressure drop through the  
condenser.  
Refrigerant with low subcooling may partially change back into vapor, or “flash to  
gas”, while flowing to the evaporator. The resulting gas bubbles can block or  
interrupt flow through refrigerant controls causing the evaporator to “starve” for  
liquid refrigerant. The consequences are poor evaporator efficiency, high  
superheat, and generally poor cooling of the conditioned space. Unless very well-  
insulated, long liquid lines from the condenser to the evaporator, specifically  
liquid lines exposed to high ambient temperatures, are prone to reduce  
refrigerant subcooling. To insure sub-cooled liquid refrigerant reaches the  
evaporator under all conditions, it is usually advisable to take subcooling  
measurements during the warmest part of the day. Test measurements taken  
during this time would provide results typical of the most adverse conditions  
under which the cooling system would operate. Installing a liquid line sight glass  
at the inlet to the evaporator is a simple, but effective, way to prove liquid is  
feeding the evaporator. If the sight glass shows all liquid flow without bubbles this  
is a good indication that the amount of subcooling is adequate.  
NOTICE: Do not attempt a superheat measurement when the ambient  
temperature is less than 60° F. Low loading on the cooling system will  
result in low or erroneous superheat measurements.  
41  
All installations and services must be performed by qualified service personnel.  
3. Condenser Subcooling:  
Before taking subcooling measurements, allow the system to stabilize through  
continuous operation for at least 15 minutes. To determine subcooling, measure  
the refrigerant pressure at the liquid line as it leaves the condenser. It is  
preferable to measure pressure of the liquid line at the evaporator, but most  
manufacturers, including Thermo Pride, do not include test ports (or Schraeder  
valves) at the evaporator. Typically, it would be necessary to compensate for the  
pressure drop through the line connecting the condenser and the expansion  
valve. However, due to the close proximity of these components, the pressure  
drop will be small and can be neglected.  
Once the liquid line pressure is known, the refrigerant temperature must be taken  
on the liquid line as it enters the evaporator. Use a good resistive thermometer or  
thermocouple protected with a rag or insulation. Subtract the measured  
temperature from the saturation temperature of the refrigerant. The result is the  
degree of refrigerant subcooling.  
Refer to Example 4, in Appendix B: Calculations of this manual, for a sample  
calculation of how to figure the degree of subcooling for the condenser. In  
general, Thermo Pride recommends the evaporator operate with a subcooling of  
between 10°F and 15°F.  
4. Definition of Superheat:  
Superheat is extra heat added to refrigerant above the vaporization  
pressure/temperature of the refrigerant. A small amount of refrigerant superheat  
is usually beneficial and needed to help assure the best operation of the cooling  
system.  
Superheat cannot be measured with a pressure gauge alone. Both pressure and  
temperature readings of the suction line are required to evaluate the amount of  
refrigerant superheating. The degree of superheating gives an indication of two  
important system-operating parameters. Superheat at the suction line outlet of  
the evaporator indicates the efficiency of the evaporator coil. Superheated vapor  
at the suction line inlet to the compressor insures that liquid refrigerant is not  
being pumped into the compressor.  
Highly superheated vapor is also detrimental to system operation. The highly  
superheated refrigerant may overheat the compressor, resulting in premature  
failure and/or intermittent thermal cutout of the compressor. High superheat at  
the evaporator also indicates the evaporator is operating very inefficiently by  
vaporizing the refrigerant too quickly in the evaporator coil. High superheat at  
the evaporator results in some loss of the evaporator heat removal capacity.  
42  
All installations and services must be performed by qualified service personnel.  
5. Evaporator Superheat:  
Before taking a superheat measurement allow the system to stabilize for 15  
minutes under continuous operation. To measure superheat at the evaporator, a  
suction pressure reading at the outlet of the evaporator would be desirable. Since  
most residential cooling systems (including Thermo Pride evaporators) do not  
provide a test port (sometimes referred to as a Schraeder port) at the evaporator,  
the suction pressure must be read at the suction inlet to the compressor.  
Typically, it would be necessary to compensate for the pressure drop through the  
line connecting the evaporator and the compressor. However, due to the close  
proximity of these components, the pressure drop will be small and can be  
neglected. A good resistive-type thermometer or thermocouple-based sensor  
should be used to measure the suction line temperature exiting the evaporator.  
On evaporators using thermal expansion valves, read the temperature directly  
under the expansion bulb, located on the side of the suction line exiting the  
evaporator.  
Measure refrigerant temperature at the 2:00 or 10:00 positions on the outer  
surface of the evaporator suction tube. Wrap the thermometer or thermocouple  
with a rag, or insulation, to insure system airflow does not influence the  
temperature readings.  
Refer to Example 3, in Appendix B: Calculations of this manual, for a sample  
calculation of how to figure the degree of superheat for the evaporator. In  
general, Thermo Pride recommends an operating evaporator superheat of  
between 5° and 12°F.  
43  
All installations and services must be performed by qualified service personnel.  
V. INSTALLER'S INSTRUCTIONS TO USER  
After completing the installation, the installer shall inform and/or demonstrate to the  
homeowner:  
1. The location of these instructions in the appliance. These instructions must be  
kept along with instructions for any accessories in the plastic pouch on the inside  
of the appliance.  
2. The location and use of the manual oil shutoff valve and appliance electrical  
disconnecting device. The end user must be instructed to always shut off the  
electric power to the appliance, before shutting off the oil supply.  
3. The sequence of operation of the appliance.  
4. The correct operation and maintenance of the appliance, as outlined in the  
Homeowner/User Information and Routine Maintenance section of this  
manual.  
5. That failure to maintain and operate this appliance in accordance with these  
instructions could result in hazardous conditions, property damage, and bodily  
injury. It may also void the limited warranty on the appliance.  
6. Review with and encourage the user to read the label reproductions and all  
warnings and instructions outlined on the front cover and in Sections I, II, and III,  
of this manual.  
7. Recommend the user have a qualified heating contractor inspect the entire  
appliance at least once a year. Inform the user of the frequency of inspection  
required for each item in the Dealer Maintenance section of this manual.  
8. Inform the user to maintain adequate clearances around air openings into the  
appliance housing and not to block or restrict the entrance of air into the  
condenser coil or the burner compartment air openings.  
44  
All installations and services must be performed by qualified service personnel.  
VI. DEALER MAINTENANCE  
SAFETY DURING SERVICING AND INSPECTION  
: Personal injury or property damage could result from repair or  
service of this appliance by anyone other than a qualified heating contractor.  
The user may only perform the activities described in the Homeowner/User  
Routine Maintenance section of this manual.  
: To avoid injury from moving parts, or electrical shock, shut off the  
power to the appliance before removing blower compartment door and  
servicing this appliance.  
: When servicing controls, label all wires prior to disconnecting.  
Reconnect any removed wires correctly. Wiring errors can cause improper  
and dangerous operation. Dangerous operation can result in injury or damage.  
IMPORTANT: Verify the proper operation of this appliance after any servicing  
is performed.  
A qualified heating contractor should perform the following maintenance  
procedures at the beginning of each heating season. Correct any deficiencies at  
once.  
A. General Inspection  
: Shut off oil and disconnect power before continuing w/ this  
inspection.  
1. Vent terminal - Visually inspect the terminal for restrictions, loose or missing  
fasteners, external damage, and carbon build-up. Clean the vent terminal and the  
screen(s) covering any opening in the terminal. Repair any minor damage. If  
necessary, replace a severely damaged or degraded vent terminal.  
2. Burner – Visually check the burner, and below the burner, for indications of oil  
leaks. Correct any, if found. Remove the burner and measure the ignition  
electrode gap. It should be set to 5/32 inch. Adjust it, if necessary. Clean any  
accumulation of dust, dirt, or debris from the air shutter or air band openings. If  
necessary, clean housing and blower wheel with a damp cloth. Use a vacuum to  
remove any lint or dust from motor assembly. Add a few drops of non-detergent  
oil to each of the motor lubrication holes.  
3. Combustion Chamber - Inspect the liner for deterioration, oil and carbon build-up.  
If the accumulation of oil or carbon is significant, this is a strong indicator that the  
burner is out of adjustment. Inspect the burner nozzle for partial blockage and  
45  
All installations and services must be performed by qualified service personnel.  
excessive wear. Replace it, if required. Check and adjust oil pump pressure, if  
needed. Refer to Initial Heating System Adjustments section of this manual.  
4. Heat Exchanger – Visually inspect the heat exchanger for excessive carbon  
(soot) build-up. Refer to the Heat Exchanger section of the manual.  
5. Oil Filter – Replace the supply line oil filter cartridge with a new filter of the same  
type and rating. Clean the body of, or mounting plate for, the oil filter.  
6. Evaporator and Condenser Coils – Inspect both the evaporator and the  
condenser coils for dust, dirt, debris, and insects lodged between the fins.  
Remove any foreign materials found using a vacuum cleaner with a brush  
attachment or a water spray from a garden hose. Carefully straighten any bent  
fins with a thin piece of wood or a fin comb.  
7. Labels and Markings - Clean all appliance labels, markings, and instruction  
plates, as necessary, and verify that all are still legible. Any illegible or missing  
markings must be replaced. Replacements can be obtained by contacting  
Thermo Products.  
B. Heat Exchanger  
: A qualified heating contractor must clean the heat exchanger.  
At least once a year, inspect the heat exchanger for evidence of corrosion, pitting,  
warpage, deterioration, and carbon (soot) build-up. A layer of soot on the inside of  
the heat exchanger will act as an insulator and reduce heat transfer, resulting in less  
heating efficiency.  
Also, look for loose or deteriorated gaskets and insulation around the flue pipe, the  
burner, and accessible areas of the heat exchanger. If this inspection indicates heat  
exchanger cleaning is necessary, follow the heat exchanger cleaning instructions  
below.  
1. Disassembly to Access Heat Exchanger  
To clean the heat exchanger, first turn off all electrical power to the unit. Next,  
remove the cleanout access panel inside the burner compartment to gain entry to  
the cleanout covers, refer to Figure 9.  
46  
All installations and services must be performed by qualified service personnel.  
Figure 9, OPB Heat Exchanger Clean-out Ports and Related Components  
Remove the clean-out covers. Also, remove the burner compartment cover, the  
burner, and the burner mounting plate. When removing the clean-out covers, special  
care must be taken not to damage the gaskets. Should any of the gaskets separate,  
show evidence of cracks or breaks, or otherwise be unable to provide the necessary  
seal, the gasket must be replaced before reattaching the clean-out covers, refer to  
Figure 10.  
47  
All installations and services must be performed by qualified service personnel.  
With access to the inside of the heat exchanger through the burner area, cleanout  
openings, and vent terminal connection, it is now possible to use a long, flexible wire  
brush and an industrial type vacuum cleaner to remove any soot build-up.  
NOTICE: A one inch (outside diameter) vacuum cleaner hose will fit into the  
radiator.  
To vacuum and brush the horizontal drum of the heat exchanger, enter the drum  
through the clean-out openings in both directions.  
2. Heat Exchanger Reassembly  
After the heat exchanger has been cleaned, install the heat exchanger and  
reassemble the components to their factory produced state, in reverse order of  
disassembly and removal, refer to figures 9 and 10. Remount the burner being  
certain that the air tube is properly inserted into the chamber opening. If heavy  
soot deposits were found in the heat exchanger, this indicates that the burner  
may be out of adjustment. Reset the burner, as indicated under the Initial  
Burner Operation section.  
Figure 10: View of OPB Heat Exchanger  
Replace any damaged or corroded components. All gaskets and insulation must  
be inspected, and replaced, if they show any signs of damage.  
48  
All installations and services must be performed by qualified service personnel.  
3. Operational Check  
: Before troubleshooting, familiarize yourself with the start up and  
check out procedures  
NOTICE: After reassembling the appliance, check for fuel oil leakage from  
the supply piping.  
a. Check proper operation of the ignition system and for proper combustion.  
b. Observe the main burner flame. If the flame appears strange or abnormal in  
character, look for a component or components that were not reassembled  
correctly. If the components have been reassembled correctly, check for a  
blocked vent, malfunctioning combustion air blower or fuel pump, and partially  
blocked burner nozzle.  
C. Electrical System  
: When servicing controls, label all wires prior to disconnecting.  
Correctly reconnect any wires removed during servicing. Wiring errors can  
cause improper and dangerous operation. Dangerous operation can result in  
injury or damage.  
1. Check all wiring for loose connections and any signs of damage, or unusual  
wear. Replace any damaged or frayed wiring and tighten any loose connections.  
2. Use a voltmeter, or a multimeter, to check for adequate voltage at the field  
connections when the appliance operating.  
3. Use an ammeter, or a multimeter, to check the current draws of the blower  
motor, burner assembly, and air conditioning compressor to assure they are not  
exceeding rating label current specifications for each component. Also, refer to  
Table 5 for electrical specifications on these components.  
4. Check for correct operation and proper settings (if manually adjustable) of all  
controls.  
49  
All installations and services must be performed by qualified service personnel.  
D. Supply/Return Air Blower  
Check in the blower compartment for dust, dirt, debris, and for the presence of  
insects. Remove any foreign material. Clean the blower wheel, housing, and  
compartment of dust and lint with a vacuum.  
The blower motor has sealed bearings that are permanently lubricated. The blower  
motor bearings do not require oil or any type of additional lubrication.  
E. Supply/Return Air Filter  
A permanent-type air filter is provided in the return section of this unit. This filter  
should be inspected regularly. When the filter is dirty, it should be cleaned or  
replaced to assure proper heating/cooling system operation. Follow the cleaning,  
removal and replacement procedure below.  
1. Filter maintenance procedure  
The filter rack is located behind an access panel on the left-hand side of the  
unit, refer to Figure 12. Shut off the electrical power to the unit. Remove the  
screws retaining the access panel to the housing. Remove the access panel.  
Slide the dirty air filter out of the filter rack. Clean the filter by either  
vacuuming, rinsing with tap water, hosing, or dipping in an ordinary detergent  
solution. After cleaning and drying the filter, replace the completely dry filter in  
the rack. If the filter has a supporting mesh, the mesh side of the filter must be  
placed towards the furnace.  
Figure 12: Location of the OPB Supply/Return Air Filter  
2. Filter replacement  
To ensure an adequate replacement filter is selected, should the filter require  
replacing, refer to Table 4, in Air Filters section of this manual, for the  
minimum filter areas required for different types of available filters.  
50  
All installations and services must be performed by qualified service personnel.  
NOTICE: Remind the homeowner of the importance of monthly filter  
inspections during operation to ensure maximum operating efficiency.  
F. Extended Appliance Shutdown  
: Do not attempt to start burner when:  
Primary reset has been engaged more than two times.  
Excess oil has accumulated in the combustion chamber or beneath the  
burner assembly.  
The combustion chamber or the heat exchanger is full of fuel vapor.  
The combustion chamber is very hot.  
Should the appliance be shutdown or turned off for an extended period of time,  
several steps can be taken to help insure a smooth and reliable restart of the  
heating system.  
ON SHUTDOWN:  
1. Close oil supply (or manual shutoff) valve.  
2. Disconnect all electrical power to the unit.  
3. Fill the oil tank to reduce water condensation in the tank.  
4. If the shutdown period will exceed one heating season, an oil stabilizer  
should be added to the oil tank. Consult your oil supplier for  
recommendations.  
ON STARTUP:  
1. Have system inspected and started by a qualified heating contractor.  
2. Check oil level in tank. If the tank has not been filled with fresh oil, inspect  
the remaining oil for signs of contamination with water, algae, dirt or other  
impurities. If excessive, consult your oil supplier for recommendations.  
3. Change the oil filter cartridge and clean the canister.  
4. Set the room thermostat above room temperature.  
5. Open all valves in the oil supply line.  
51  
All installations and services must be performed by qualified service personnel.  
6. Open the inspection cover on the upper mounting plate.  
7. Turn on the electrical power to start the burner. If the burner does not start,  
immediately reset the manual overload switch on the motor (if so equipped)  
and the safety switch of the burner primary control. Bleed air from the fuel oil  
line as soon as the burner motor starts rotating. To bleed the fuel pump,  
attach a clear plastic hose over the vent plug, refer to Figure 13. Loosen the  
plug and catch the expelled oil in an empty container. Tighten the plug when  
all the trapped air appears to be purged. If the burner stops during bleeding,  
wait three to five minutes for the control safety switch to cool. Then manually  
reset the switch. Continue bleeding the line until the air is completely  
removed.  
Figure 13: Location of Oil Pump Vent Plug  
8. Follow the previous Initial Burner Operation procedures.  
52  
All installations and services must be performed by qualified service personnel.  
VII. HOMEOWNER/USER INFORMATION AND ROUTINE MAINTENANCE  
: Never burn garbage or refuse in this appliance. Never try to ignite oil by  
tossing burning papers or other material into the combustion chamber.  
: Oil-fired appliances produced by Thermo Products are designed for  
burning No. 2 distillate (domestic heating) fuel oil. Never use gasoline or a  
mixture of oil and gasoline.  
: Do not use this appliance if any part has been under water. Immediately  
call a qualified service technician to inspect the furnace and to replace any part of  
the control system and any oil control that has been under water.  
: Should overheating occur, or the oil supply fail to shut off, shut off the  
electrical power to the appliance, before shutting off the manual oil valve.  
: The area around the appliance, including the top of the unit, must be  
kept clear and free of combustible materials, gasoline, and other flammable  
vapors and liquids.  
I
: The appliance vent terminal may be hot. If the terminal is hot, allow it  
to cool before touching it.  
I
: Do not attempt to make repairs yourself. Contact your local qualified  
heating contractor.  
Under normal conditions, this appliance will operate in either heating or cooling mode,  
depending upon the mode of operation set at the thermostat. The unit will cycle on and  
off automatically, as required, to maintain the air temperature within the residence as  
closely as possible to the thermostat setting. However, in rare cases, the unit may  
shutdown automatically during a normal cycle or may not operate under seemingly  
normal conditions.  
If the unit will not operate in the heating mode, it may be possible to reactivate the  
unit by resetting one of the burner controls. To attempt resetting of the burner controls,  
follow this procedure.  
1. Turn the thermostat temperature setting down and set the operating mode to  
“OFF” or “COOLING”.  
2. Remove the burner compartment cover.  
3. Check to see if the LED on the burner primary (ignition) control module is  
flashing at a rapid rate. If so, the control may have “locked out”. To recycle the  
control system, depress the reset button. Refer to Figure 14.  
53  
All installations and services must be performed by qualified service personnel.  
4. Check to see if the high temperature limit switch reset button, on the burner  
motor, has “popped out”. If so, the control has activated. To reactivate the  
control, depress the reset button.  
5. Replace and secure the burner compartment cover.  
6. Set the operating mode on the thermostat to “HEATING” and turn the thermostat  
temperature setting up.  
Figure 14: Location of Reset Buttons on the Burner Primary Control and the  
Burner Motor  
If this action does not reactivate the unit, contact a qualified service agency for  
assistance.  
In general, if the thermostat is set in the heating mode, the heating system  
functions entirely automatically. However, under certain circumstances, the  
appliance may not be able to fire the burner. For instance, if the manual oil  
shutoff valve has been closed or the oil tank is out of fuel, the oil line may have  
air trapped in it. It will be necessary to purge the air by bleeding the supply line  
from the tank to the burner again for the heating system to operate. Refer to the  
instructions under the Extended Appliance Shutdown section of this manual.  
NOTICE: Thermo Products recommends that the user/homeowner, contact  
a qualified service agency for assistance in bleeding the fuel line(s) and  
lighting off the heating section.  
54  
All installations and services must be performed by qualified service personnel.  
The following maintenance points should be reviewed periodically to assure the heating  
and cooling systems continue to function properly.  
: Shut off unit and disconnect the power source before disassembling  
the unit.  
: Never operate the appliance without clean air filters in place.  
: This appliance requires air for combustion, ventilation, and cooling. Do  
not block or obstruct air openings in the unit and the air space around the  
perimeter of the unit.  
1. At least every three months, under normal usage conditions, check and clean all air  
filters in the appliance and, if present, in the duct system. If excessively dirty air  
filters are not cleaned, or changed, poor system performance will result due to  
reduced airflow. Low airflow places unnecessary strain on the compressor, possibly  
causing the system to shutdown on the refrigerant high-pressure switch. Refer to  
Figure 16 for a sketch of the filter location.  
2. Keep the outside condenser coil clean by carefully spraying the finned area with  
plain water, from the inside of the coil outward.  
3. Carefully remove any leaves, twigs, debris, trash, and insect or small animal nests/  
homes from in and around any openings in the appliance housing.  
4. Visually inspect the vent terminal for restrictions and blockages. With the heating  
system in operation, the vent terminal will be hot. Shut off the unit and allow the  
vent terminal to cool before removing any foreign materials from within the vent  
terminal.  
5. Inspect the exterior of the appliance for signs of excessive heat such as  
discoloration of materials, damage from rust or corrosion, or evidence of oil leakage.  
Pay special attention to the mounting base the appliance is resting upon. If the base  
is severely damaged, deteriorated, or unstable, shutdown the unit and call a  
qualified heating contractor for recommendations on repair or replacement of the  
base.  
6. Do not allow the fuel oil tank to run completely empty. During the summer, keep the  
tank full to reduce condensation of moisture on the inside surface of the tank.  
If the fuel tank runs completely dry, it may be necessary to bleed air from the fuel  
lines. Contact a qualified heating contractor to bleed the lines and restart the  
burner.  
7. Check the supply and return air connections to the appliance to insure the seals  
between the duct and appliance and the appliance and home are intact. Check the  
55  
All installations and services must be performed by qualified service personnel.  
ducts for any signs of collapse, holes, or excessive corrosion. Repair or replace  
components as required.  
8. It is advisable to wax the outer surface of the appliance housing yearly to provide the  
surface finish protection from excessive degradation by sunlight and inclement  
weather. A good grade of automotive wax should be used to protect the finish.  
56  
All installations and services must be performed by qualified service personnel.  
VIII. TROUBLESHOOTING  
: Power must be disconnected before servicing.  
Refer to the appendices of this manual for an electrical schematic, a connection  
diagram, flowcharts to assist in troubleshooting, product specifications, and a  
replacement parts list follow for this appliance.  
A. Heating System:  
Qualified HVAC and cooling contractors must perform all service.  
NOTICE: Before troubleshooting, familiarize yourself with the Initial Startup,  
Checkout Procedure, and Heating System Troubleshooting Flowchart.  
To assist in troubleshooting the heating section of this appliance, it is equipped with  
an integrated safety and ignition control with diagnostics. These diagnostics include  
an indicator light that relays the operational status of the control and can help in  
diagnosing the condition of the flame sensor.  
Diagnostic Features  
The Honeywell brand model R7184B (or alternate R7184U) safety and ignition  
control module used on this unit continuously monitors the operation of the heating  
system. If an abnormal condition occurs, the LED light on the control will rapidly  
flash indicating the operational status of the unit. In event this control  
malfunctions, the entire control should be replaced. It is not field-repairable.  
In the event of an operational failure of the burner system, the rate of flashes, if any,  
of the ignition control module LED should be noted, before turning off power to the  
unit. Otherwise, power to the heating section will be interrupted and the control LED  
will not furnish the diagnostic flashing. It may be necessary to restart the furnace and  
have the failure occur again. For the model R7184B, under normal operating  
conditions, the LED will be continuously lit while the burner is operating.  
If either control has sensed a flame failure, which was uncorrected by initiating  
another trial-for-ignition, the control will cease ignition trials and shutdown the  
burner, or “lockout”. The LED will continuously flash at a high rate (approximately  
1/2-second “on”; 1/2 second “off”, for the model R7184B.  
: If the appliance fails to relight after resetting the primary control twice  
contact a qualified service company. DO NOT continue to reset primary control.  
The operational condition of the flame sensor, or “cad cell”, can be checked by  
depressing the reset button on the control module, while the burner is operating.  
Count the number of flashes of the LED and compare them to the table below.  
57  
All installations and services must be performed by qualified service personnel.  
Number of flashes  
Cad Cell Resistance (in ohms)  
Model R7184B  
1 ......................................... 0 to 400  
2 ......................................... 400 to 800  
3 ......................................... 800 to 1600  
4 ......................................... 1600 <  
If it is necessary to troubleshoot the flame sensor independently of the burner  
primary, the following procedure may be used.  
CAD CELL CHECKOUT PROCEDURE:  
1. Stop burner and shutoff electrical power to the appliance.  
2. Open burner junction box (on top of the burner blower) and remove the plug-  
in portion of the cad cell by pulling it forward from and clear of the  
receptacle. Connect an ohmmeter across cad cell pins. With the cell  
exposed to direct room light, the measured resistance should be less than  
2500 ohms (in fact, it may be less than 200 ohms).  
3. Check the resistance across the cad cell pins with the cell covered  
(protected from exposure to ambient light). The resistance should be greater  
than 20,000 ohms.  
4. If cell resistances are different from above, replace the plug-in portion of cell,  
(Honeywell Part No. 130367).  
5. Carefully reinsert the plug-in portion of the cad cell into the receptacle. If the  
cad cell appears to be functioning correctly, troubleshoot the fan control  
module and the safety and ignition control (primary control) module,  
according to the Honeywell instructions covering the devices.  
B. Cooling System:  
NOTICE: Before troubleshooting, familiarize yourself with the Initial Startup  
and the Cooling System Troubleshooting Flowchart.  
If the air conditioning system will not operate, check the following points before  
calling a qualified heating contractor.  
1. Is the disconnect switch or the circuit breaker serving the appliance switched on?  
If equipped, have the disconnect switch fuses “blown” or has the circuit breaker  
tripped? If an electrical fault has occurred more than once, call your qualified  
service person to diagnose the cause and perform the required repair(s).  
58  
All installations and services must be performed by qualified service personnel.  
2. Is the sub-base of the thermostat switched to the “COOL” position?  
3. Is the temperature setting on the thermostat low enough to bring the cooling  
system on?  
4. Has the unit stopped cooling, making it necessary to wait several hours before  
the unit will restart? The fan motor, or compressor, may have shutdown on  
thermal-overload due to overheating. If this event frequently occurs, call your  
qualified heating contractor.  
5. Has it been longer than four minutes since the last cooling cycle finished or since  
power was restored form an outage.  
59  
All installations and services must be performed by qualified service personnel.  
IX. REFERENCES  
1. International Approval Services-U.S. Inc. and the National Fire Protection  
Association, 1996, National Fuel Gas Code, ANSI Z223.1-1996/NFPA 54-1996, 6th  
Ed., pp. 10 & 13.  
2. Earley, M.W., Sheehan, J.V., Caloggero, J.M., 1999, National Electrical Code  
Handbook, 8th Ed., National Fire Protection Assoc., Inc., pp. 142, 143, 256, & 502-  
510.  
3. American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc.,  
1997, ASHRAE Handbook – Fundamentals, pp. 19.9, 32.1-32.50.  
4. Lindeberg, M.R., 1984, Mechanical Engineering Review Manual, 7th Ed.,  
Professional Engineering Registration Program, San Carlos, CA, pp. 5-8 & 5-9.  
5. Avallone, E.A., Baumeister III, T., 1996, Marks’ Standard Handbook for Mechanical  
Engineers, 10th Ed., McGraw-Hill, New York, pp. 12-88 & 12-89.  
60  
All installations and services must be performed by qualified service personnel.  
X. APPENDIX A: SOURCES FOR REFERENCED STANDARDS  
1. Air Conditioning Contractors of America  
1712 New Hampshire Avenue, NW  
Washington, D.C. 20009  
(202) 483-9370  
2. American National Standards Institute, Inc.,  
Attn: Customer Service  
11 West 42nd Street  
New York, New York 10036  
(212) 642-4900  
3. American Society of Heating, Refrigeration, and Air-Conditioning Engineers, Inc.,  
1791 Tullie Circle N.E.  
Atlanta, Georgia 30329  
(404) 636-8400  
4. National Fire Protection Association,  
1 Batterymarch Park  
Quincy, Massachusetts 02269  
(800) 344-3555  
61  
All installations and services must be performed by qualified service personnel.  
XI. APPENDIX B: CALCULATIONS  
Example 1:  
Problem: It is desired to install a warm-air furnace w/ an air conditioning  
evaporator coil at a residence. The net output of the furnace is 100,000 BTU/hr  
and the evaporator will provide 4 tons of cooling to the space. Estimate the  
minimum required airflow for the system to operate satisfactorily.  
Solution: From the heat output of furnace, the heating airflow requirements can  
be estimated:  
100,000 BTU/hr x 14 CFM/1000 BTU/hr = 1400 CFM.  
From the required cooling performance, the cooling airflow requirements can be  
estimated:  
4 tons x 400 CFM/ton = 1600 CFM.  
The larger of the two airflow figures should be selected, i.e. 1600 CFM cooling  
requirement.  
If only 3 tons (36,000 BTU/hr) was installed, the required cooling airflow is:  
3 tons x 400 CFM/ton = 1200 CFM.  
Then, the duct system should be sized for the 1400 CFM heating requirement.  
Example 2:  
Problem: A plan view of a residence with 1600 sq. ft. living area is shown in  
Figure 15. The supply registers and the OPB unit have been positioned.  
Ductwork interconnecting the registers is also shown. What is the required air  
flowrate at each register? What is the required duct size for each segment of the  
duct system?  
62  
All installations and services must be performed by qualified service personnel.  
Figure 15: Plan View of a Typical Residence  
Solution: If certain flowrates are desired, for heating or cooling reasons, or are  
required, by local codes, those guidelines should be followed. In lieu of other  
requirements, room floor area can be used to select flowrates for each room.  
For instance, the floor area of the living room is 400-sq. ft. Using the result of our  
previous example, the required minimum air flowrate for the residence is 1400  
CFM. The air flowrate for the living room will be the total flowrate multiplied by  
the ratio of the living room area to the total floor area or,  
400sq. ft.  
CFMLiving Rm = 1400CFM *  
= 350CFM.  
1600 sq. ft.  
63  
All installations and services must be performed by qualified service personnel.  
This procedure can be repeated to determine the airflow for each room in the  
residence. The results of these calculations are given in Table 6, below.  
Table 6: Required Room Air Flowrates Based on Floor  
Area for Example 2  
Room  
Room Air  
Flowrate per  
Register  
(CFM)  
Number of  
Registers  
Room Floor Area Flowrate  
(Sq. Ft.)  
400  
(CFM)  
350  
1 @ 120  
2 @ 115  
Living  
3
Dining  
120  
144  
105  
126  
1
1
105  
126  
Kitchen  
Master  
Bedroom  
360  
315  
2
2 @ 157  
Bedroom  
Bedroom  
224  
224  
196  
196  
1
1
196  
196  
Master  
Bathroom  
64  
56  
1
56  
56  
Bathroom  
Total  
64  
56  
1
1600  
1400  
11  
We will assume the airflow is approximately equally split between all registers in  
a particular room. This completes steps (a) through (d) of the duct sizing method.  
For step (e), static pressure drops for each system, branch, and component must  
be selected. Since the appliance circulating blower can only tolerate a maximum  
pressure of 0.4 in. W.G., the combined resistance of the supply and return air  
systems cannot exceed this amount.  
64  
All installations and services must be performed by qualified service personnel.  
Therefore, choose a supply system static pressure drop of 0.2 in. W.G. (Then,  
the return air system will also have a static pressure drop of 0.2 in. W.G.)  
Furthermore, we will assume that the static pressure drops for all registers in the  
supply system will be 0.1 in. W.G.  
This leaves a static pressure drop of only 0.1 in. W.G. for all the ducting between  
the outlet flange of the appliance to each of the registers. (We will assume that  
the pressure drop through any short piece of ductwork connecting a branch to a  
register is included in the 0.1 in. W.G. pressure drop of the register.) Now, the  
size of the ducting for each segment of the duct system can begin.  
For the branch of the duct system, which includes segments “A”, “B”, “C”, “F”,  
and “H”, the pressure drop cannot exceed 0.1 in. W.G. This branch of the duct  
system has two 90-degree turns. The total length of this branch is the sum of the  
lengths of each segment,  
LeAH = LA + LB + LC + LF + LH  
=
(
11 ft. + 6 ft.  
)
+11 ft. + 6 ft. + 22 ft. +12 ft. + 3 ft.  
= 71 ft.  
Using the flowrate, total length of the duct, and the pressure drop, the required  
size of the duct can be determined using the following equation.  
0.2058  
*V (CFM )1.82  
0.00123174* Le  
(
ft.  
)
D
in.  
( )  
=
ΔP  
(
in.W.G.  
)
**See page 75 for a copy of the ASHRAE chart.  
This equation is applicable to standard air between 50 to 90 degrees F flowing  
through clean, round, galvanized ductwork with approximately 40 joints per 100  
feet. Using duct lengths in feet, flowrate in CFM, and pressure drop in inches  
W.G., the equation will calculate the required circular duct diameter in inches. (If  
it is desired to substitute rectangular duct for circular duct, refer to Table 7 for  
equivalent sizes.)  
Returning to the example, for a total length of 71 ft., a flowrate of 120 CFM (from  
the farthest register on segment “A”), and a pressure drop of 0.1 in. W.G., the  
required duct diameter is,  
0.2058  
1.82  
0.00123174*71*120  
0.1  
D =  
= 5.85 in. 6 in.  
65  
All installations and services must be performed by qualified service personnel.  
However, there are two, 90 degree turns in the branch that will cause a large  
pressure drop, not accounted for in our calculations. To compensate for this  
drop, we should increase the effective length of the branch. For a 90 degree,  
mitered elbow, the equivalent straight duct length is given by the following  
formula,  
D
(
in.  
)
L90 elbow  
(
ft.  
)
= 65*  
.
12  
For a 6-inch diameter 90-degree elbow, the equivalent straight duct length is,  
6
L90 elbow = 65* = 32.5 ft.  
12  
So, the total equivalent straight duct length is,  
Le = 71 ft. + 2*32.5 ft. = 136 ft. .  
Now, the required duct diameter should be recalculated,  
0.2058  
1.82  
0.00123174*136*120  
0.1  
DA =  
= 6.67 in. 7 in.  
Thus, for section ”A”, the required duct diameter is 7 inches.  
Now, it is necessary to determine the allowable pressure drops for all other  
segments in the branch. The equation for duct diameter can be rearranged to  
give the pressure drop for any flowrate, providing the duct length, the flowrate,  
and the duct diameter are known. The equation looks like this,  
1.82  
0.00123174* Le  
(
ft.  
)
*V  
(
CFM  
)
ΔP  
(
in.W.G.  
)
=
.
D
(
in. 4.86  
)
For section “B”, if the flowrate is 120 CFM, the length is 11 ft., and the duct  
diameter 7-in., the pressure drop will be,  
0.00123174*11*1201.82  
ΔP =  
= 0.00644 in.W.G. .  
B
74.86  
For section “C”, including a 7-inch, 90-degree elbow, the pressure drop is,  
*1201.82  
0.00123174*  
(
6 + 37.9  
)
ΔP =  
= 0.0257 in.W.G. .  
C
74.86  
66  
All installations and services must be performed by qualified service personnel.  
Likewise, the pressure drops for the two remaining segments in this branch can  
be calculated in the same manner. They are,  
ΔP = 0.0129 in.W.G. and  
F
ΔP = 0.00702 in.W.G. .  
H
Referring to section (f) and (g) of the method, it is now necessary to resize each  
of these duct segments for the actual required flowrate while maintaining the  
pressure drops calculated above.  
For instance, to maintain the pressure drop through segment “B” at the design  
flowrate of 120 CFM + 115 CFM = 235 CFM, the required duct diameter is,  
0.2058  
1.82  
0.00123174*11*235  
0.00644  
DB =  
= 9.04 in. 9 in.  
For segment “C”, the design flowrate is 235 CFM + 115 CFM = 350 CFM, while  
the pressure drop is 0.0257 in. W.G., then required duct diameter is,  
0.2058  
1.82  
0.00123174*6*350  
0.00257  
DC =  
= 11.1 in. 11 in.  
Including an 11 in., 90 degree elbow in segment “C”, the required diameter would  
be,  
0.2058  
0.00123174*  
(
6 + 59.6  
)
*3501.82  
DC =  
= 11.4 in. 11 in.,  
0.00257  
or approximately the same as without the elbow.  
For the segments “F” and “H” at 742 CFM and 798 CFM, respectively, the  
required duct diameters are,  
DF = 13.9 in. 14 in. and  
DH = 14.3 in. 14 in..  
Next, the branch of the system, which includes segments “D” and “E” can be  
evaluated. To balance the system, the pressure drop for segments “D” and “E”  
combined must be approximately equal to the pressure drops of segments “A”,  
“B” and “C” combined. Thus,  
ΔP + ΔP = ΔPA + ΔP + ΔP .  
E
D
B
C
67  
All installations and services must be performed by qualified service personnel.  
Using the previous pressure drop equation, the pressure drop through segment  
“A” is 0.0321 in. W.G. Then, the pressure drop for the “D” and “E” branch is,  
ΔP + ΔP = 0.0321 in.W.G. + 0.0644 in.W.G. + 0.0257 in.W.G.  
E
D
= 0.0643 in.W.G..  
The duct diameter required to pass 196 CFM @ 0.0643 in. W.G. pressure drop  
is,  
0.2058  
0.00123174*  
(
17  
)
*1961.82  
DE =  
= 5.73 in. 6 in.,  
0.0643  
Including a 6 in., 90-degree elbow in segment “E”, the required diameter would  
be,  
0.2058  
0.00123174*  
(
17 + 32.5  
)
*1961.82  
DE =  
= 7.14 in. 7 in.,  
0.0643  
or approximately 1 inch larger than without the elbow.  
The pressure drop through segment “D” should be calculated for a 5-ft. straight  
section with a 7-in., 90-degree elbow. From our previous equation, the pressure  
drop is about,  
0.00123174*  
(
5 + 37.9  
)
*1961.82  
ΔP =  
= 0.0614 in.W.G. .  
D
74.86  
The flowrate through section “D” is 392 CFM (196 CFM + 196 CFM). With the  
required pressure drop, the duct diameter is,  
0.2058  
0.00123174*  
(
5 + 37.9  
)
*3921.82  
DD =  
= 9.07 in. 9 in. .  
0.0614  
Recalculating the duct size considering the effective length of a 9 in., 90 degree  
elbow,  
0.2058  
0.00123174*  
(
5 + 48.75  
)
*3921.82  
DD =  
= 9.50 in. 10 in. ,  
0.0614  
or an increase in duct size of about 1 inch in diameter.  
68  
All installations and services must be performed by qualified service personnel.  
The pressure drops for the remaining branches of the system must be set. This  
includes segment “G”; segments “I” and “J”; and segments “K”, “L”, and “M”. To  
balance the system, the pressure drop for each branch must be approximately  
equal to the pressure drops of the other branches. For example, segment “G”  
must equal segments “D”, “E” and “F” combined. Thus,  
ΔP = ΔP + ΔP + ΔP .  
G
D
E
F
Likewise for the other branches,  
ΔP + ΔP = 0.1 in.W.G.  
I
J
ΔP + ΔP + ΔP = 0.1 in.W.G. .  
K
l
m
Using the previous technique, duct sizes can be found for all the remaining  
segments. The duct sizes adequate for the entire supply system are summarized  
in Table 7, below.  
Table 7: Required Duct Sizes for the Residence in Example 2  
Equivalent  
Air  
Circular Air Velocity in  
Duct  
Segment  
Rectangular  
Duct Dim.s  
(in.)  
Flowrate Duct Dia. Circular Duct  
(CFM)  
(in.)  
(FPM)  
A
B
C
D
E
F
G
H
I
120  
235  
350  
392  
196  
742  
56  
7
9
449  
532  
530  
719  
733  
694  
1141  
746  
924  
864  
678  
688  
587  
6 x 6  
8 x 8  
11  
10  
7
10 x 10  
9 x 9  
6 x 6  
14  
3
13 x 13  
N/A  
798  
126  
231  
370  
304  
157  
14  
5
13 x 13  
N/A  
J
7
6 x 6  
K
L
10  
9
9 x 9  
8 x 8  
M
7
6 x 6  
N/A - Not Applicable  
69  
All installations and services must be performed by qualified service personnel.  
Example 3:  
Problem: Refrigerant measurements are made on the cooling system of a typical  
OPB installation. The suction line pressure, measured at the condenser unit,  
suction line, charging port, is 135 PSIG. The temperature of the refrigerant  
(R410A) at the evaporator suction line connection is measured as 55°F. What is  
the degree of superheat for this system?  
Solution: Calculate the pressure of the refrigerant at the evaporator suction line  
connection. With the estimated refrigerant pressure and measured temperature  
at the same point, tabulated data on R410A from the refrigerant manufacturer,  
or ASHRAE, can be used to evaluate the degree of superheat.  
135 PSIG (Suction pressure measured at condenser)  
+ 0 PSIG (Added for pressure drop of suction line)  
------------------  
135 PSIG = Estimated pressure of refrigerant at evaporator exit  
From the R410A pressure/temperature chart, at 135 PSIG, the saturation  
temperature is approximately 47°F  
70  
All installations and services must be performed by qualified service personnel.  
71  
All installations and services must be performed by qualified service personnel.  
Now, the degree of superheat can be calculated.  
55°F  
- 47°F  
(Suction line temperature at outlet of evaporator)  
(Saturation temperature for R410A at 68 PSIG)  
-----------------------  
8°F  
=
Degree of evaporator superheat.  
Example 4:  
Problem: Additional refrigerant measurements are made on the cooling system  
of our typical OPB installation. The liquid line pressure, measured at the  
condenser unit, liquid line, charging port, is 340 PSIG. The temperature of the  
refrigerant (R410A) at the evaporator liquid line connection is measured as 95°F.  
What is the degree of subcooling for this system?  
Solution: Calculate the pressure of the refrigerant at the evaporator liquid line  
connection. With the estimated refrigerant pressure and measured temperature  
at the same point, tabulated data on R410A from the refrigerant manufacturer,  
or ASHRAE, can be used to evaluate the degree of subcooling.  
340 PSIG (Liquid line pressure measured at condenser)  
+ 0 PSIG (Added for pressure drop of liquid line)  
------------------  
340 PSIG = Estimated pressure of refrigerant at evaporator inlet  
From the R410A pressure/temperature chart, at 340 PSIG, the saturation  
temperature is approximately 105°F  
Now, the degree of subcooling can be calculated.  
105°F  
- 95°F  
------------------  
(Saturation temperature for R410A at 340 PSIG)  
(Suction line temperature at outlet of evaporator)  
10°F  
=
Degree of condenser subcooling  
72  
All installations and services must be performed by qualified service personnel.  
73  
All installations and services must be performed by qualified service personnel.  
XII.  
APPENDIX C: ELECTRICAL SCHEMATIC AND CONNECTION DIAGRAM  
74  
All installations and services must be performed by qualified service personnel.  
XIII. APPENDIX D: SEQUENCE OF OPERATIONS  
OPB  
1 of 2  
A. SEQUENCE OF OPERATIONS FOR THE HEATING SYSTEM  
Mode of Operation  
Control System Action  
Standby  
(At any time the oil  
valve is not energized)  
Continous safe operation check. If  
flame simulation condition present,  
system shuts off oil valve,ignitor,  
and burner motor; activates fast  
flashing LED.  
Start  
Thermostat calls for heat,  
contacts close  
Ignition electrodes spark.  
Burner motor energized.  
On power interruption, system  
shuts off, restarts when  
power is restored.  
Oil valve energized after  
15 second time delay.  
Start trial for  
ignition  
If flame is not detected, the  
oil valve is de-energized,  
the ignitor is turned off and  
the ignition control module  
goes into the "retry" sequence.  
Flame must be detected  
after 45 seconds.  
The retry sequence provides a  
60 second wait before ignition  
is attempted again.  
75  
All installations and services must be performed by qualified service personnel.  
OPB  
2 of 2  
Control System Action  
After 45 second delay, the  
ignition electrodes are de-  
energized. The circulating  
air fan is energized at heating  
speed. The (optional) electronic  
air cleaner & humidifier are  
Main Burner  
Operation  
energized.  
If ignition attempt is unsuccessful,  
the ignition control module goes into  
system lockout.  
Repeat Ignition  
Trial  
When thermostat is satisfied,  
contacts open and the oil  
valve is de-energized. After  
a 2 minute burner off delay,  
burner motor is de-energized.  
Call for Heat  
The 2 minute delay- to- fan-off  
Satisfied  
period begins.  
If system is in lockout,(check if LED  
is flashing fast) try to recycle the  
system by depressing the RESET button  
on the ignition control module.  
System Lockout  
After the delay-to-fan-off  
period ends, the circulating  
air fan and {optional)  
electronic air cleaner are  
de-energized.  
End of Cycle  
76  
All installations and services must be performed by qualified service personnel.  
XIV. APPENDIX E: TROUBLESHOOTING FLOWCHARTS  
OPB  
1 of 2  
A. SEQUENCE OF OPERATIONS FOR THE HEATING SYSTEM  
Mode of Operation  
Control System Action  
Standby  
(At any time the oil  
valve is not energized)  
Continous safe operation check. If  
flame simulation condition present,  
system shuts off oil valve,ignitor,  
and burner motor; activates fast  
flashing LED.  
Start  
Thermostat calls for heat,  
contacts close  
Ignition electrodes spark.  
Burner motor energized.  
On power interruption, system  
shuts off, restarts when  
power is restored.  
Oil valve energized after  
15 second time delay.  
Start trial for  
ignition  
If flame is not detected, the  
oil valve is de-energized,  
the ignitor is turned off and  
the ignition control module  
goes into the "retry" sequence.  
Flame must be detected  
after 45 seconds.  
The retry sequence provides a  
60 second wait before ignition  
is attempted again.  
77  
All installations and services must be performed by qualified service personnel.  
TURN THERMOSTAT TO CALL FOR HEAT  
DOES THERMOSTAT MAKE CONTACT?  
No  
No  
No  
IS ROOM TEMPERATURE  
TURN T'STAT SETTING  
ABOVE ROOM  
IS ROOM TEMPERATURE  
BELOW THERMOSTAT SETTING?  
TEMPERATURE  
Yes  
Yes  
Yes  
ALLOW THE ROOM  
AIR TO COOL  
CHECK IN PUT POWER,  
DISCONNECTING SWITCH,  
AND FUSE(S), IF EQUIPPED.  
DOES BURNER MOTOR  
START?  
No  
CHECK FOR LINE VOLTAGE  
@ FAN CONTROL MODULE.  
IF NOT 115 VAC, CHECK FOR  
BLOWN FUSE OR TURN ON  
IS THE BURNER  
PRIMARY LOCKED  
OUT ON SAFETY ?  
No  
No  
IS VOLTAGE PRESENT  
AT BURNER MOTOR?  
POWER. IF 115 VAC PRESENT,  
CHECK OUT FAN CONTROL  
MODULE & PRIMARY MODULE  
ACCORDING TO MANUFACTURER'S  
INSTRUCTIONS.  
Yes  
Yes  
Yes  
PUSH IN PRIMARY RESET BUTTON  
IS THE OIL PUMP  
MECHANICALLY  
LOCKED-UP?  
No  
No  
IS BURNER MOTOR RESET  
BUTTON POPPED OUT  
REPLACE BURNER  
MOTOR  
Yes  
Yes  
REPLACE OIL PUMP  
PUSH IN MOTOR RESET BUTTON  
78  
All installations and services must be performed by qualified service personnel.  
Yes  
IS IGNITION ESTABLISHED?  
No  
IS IGNITION TRANSFORMER  
CAPABLE OF PRODUCING A  
3/4" ARC? (10,000 VAC)  
No  
No  
ARE THE ELECTRODES  
ARCING?  
REPLACE IGNITION  
TRANSFORMER  
Yes  
DETERMINE IF THE ELECTRODES ARE  
ALIGNED, CONTACT SPRINGS TOUCHING  
ELECTRODE RODS, & PORCELAIN  
INSULATORS CLEAN AND  
Yes  
UNCRACKED. ADJUST OR REPLACE,  
AS NECESSARY.  
Yes  
IS THE COUPLING BETWEEN  
THE BURNER MOTOR AND  
THE PUMP STRIPPED?  
No  
No  
IS THE OIL PUMP  
OPERATING?  
REPLACE PUMP  
Yes  
Yes  
REPLACE COUPLER  
No  
VERIFY ALL OIL VALVE(S) ARE OPEN,  
OIL TANK IS SUFFICIENTLY FULL,  
AND OIL LINE CONTAINS OIL.  
IS OIL AVAILABLE TO THE BURNER?  
FURNACE OPERATES FOR  
COMPLETE CYCLE?  
No  
IS HEAT ANTICAPATOR SET  
TO MILLIAMP SETTING  
MEASURED ON SUBBASE?  
MEASURE MILLIAMPS BETWEEN 'W' &'R'  
ON THE T'STAT SUBBASE AND SET HEAT  
ANTICIPATOR ACCORDINGLY  
No  
No  
BURNER RUN NORMAL  
CYCLE?  
Yes  
IF PROBLEM PERSISTS CONTINUE TO NEXT SECTION.  
Yes  
Yes  
No  
No  
BLOWER RUNS  
NORMAL CYCLE?  
IS TEMPERATURE RISE  
CHECK-BLOWER SPEED  
AND RETURN AIR TEMPERATURE  
Yes  
CHECK FAN ON & OFF (DIP SWITCH)  
SETTINGS ON FAN CONTROL  
79  
All installations and services must be performed by qualified service personnel.  
PROPER COMBUSTION ACHIEVED?  
No  
IS THE AIR TUBE INSERTION  
0-1/4" BACK FROM INSIDE  
OF REFRACTORY?  
CORRECT INSERTION OR  
AIR TUBE BURNOFF  
MAY OCCUR.  
Yes  
No  
IS THE PROBLEM DELAYED  
IGNITION?  
Yes  
ALIGN ELECTRODES PER  
BURNER INSTRUCTION  
MANUAL SPECIFICATIONS  
No  
ARE THE ELECTRODES  
PROPERLY ALIGNED?  
Yes  
ADJUST TO 100-120 PSI  
UNLESS COMBUSTION  
AIR OR OIL BELOW 50  
deg. F IS PRESENT (THIS  
IS CONSIDERED BELOW)  
IS PUMP PRESSURE SET  
ACCORDING TO BURNER  
APPLICATION CHART  
Yes  
No  
No  
Yes  
ARE VENT TERMINAL AND HEAT  
EXCHANGER CLEAN?  
ADJUST AIR TO A TRACE OF  
SMOKE, THEN TAKE CO2 OR  
O2 READING, NEXT SUBTRACT  
1% FROM THE CO2 OR ADD 1%  
TO O2 . THEN, ADJUST AIR TO  
OBTAIN NEW CO2 OR O2 VALUES.  
IS BURNER SET TO  
PRODUCE A TRACE  
OF SMOKE AND  
No  
No  
IS THE NOZZLE  
PLUGGING?  
THEN "DETUNED".  
Yes  
No  
IS WATER, DIRT, OR  
SLUDGE PRESENT IN  
THE OIL SYSTEM?  
IS COMBUSTION AIR  
Yes  
Yes  
TRY TO RAISE ROOM & OIL  
IF THIS CANNOT BE DONE DO  
THE FOLLOWING:  
REPAIR OR REPLACE TANK  
TO PREVENT FUTURE  
PROBLEMS. MIX  
IN PROPER ADDITIVES  
TO REMOVE WATER  
AND SLUDGE  
DECREASE NOZZLE SIZE AND  
INCREASE PUMP PRESSURE.  
CHOOSE SMALLER NOZZLE  
SIZE AND PUMP PRESSURE  
FROM "EFFECTS OF PRESSURE  
ON NOZZLE FLOW RATES" AT  
THE END OF THE TROUBLE  
SHOOTING SECTION.  
80  
All installations and services must be performed by qualified service personnel.  
Yes  
DOES FURNACE OPERATE  
WITHOUT CONDENSING?  
No  
No  
No  
No  
IS STACK TEMPERATURE  
IS BURNER SET AS INDICATED  
IN ABOVE SECTION?  
ADJUST BURNER COMBUSTION  
TO PRODUCE ZERO SMOKE.  
Yes  
SLOW THE BLOWER SPEED  
TO RAISE TEMPERATURE  
RISE.  
IS THE TEMPERATURE  
DIFFERENCE BETWEEN SUPPLY  
Yes  
Yes  
Yes  
INCREASE LENGTH OF BURNER ON CYCLE  
BY RESETTING BURNER PRIMARY CONTROL  
DIP SWITCHES FOR A LONGER OFF DELAY.  
TROUBLE SHOOTING ENDS.  
REPEAT PROCEDURE UNTIL TROUBLE FREE OPERATION IS OBTAINED.  
EFFECTS OF PRESSURE ON NOZZLE FLOW RATE  
NOZZLE  
RATING  
AT  
NOZZLE  
RATING  
AT  
NOZZLE FLOW RATES IN  
GALLONS PER HOUR (Approx.)  
NOZZLE FLOW RATES IN  
GALLONS PER HOUR (Approx.)  
80PSI  
120PSI  
140PSI  
80 PSI  
120 PSI  
140 PSI  
100 PSI  
100 PSI  
1.35  
1.50  
1.65  
1.75  
2.00  
2.25  
2.50  
2.75  
3.00  
1.21  
1.34  
1.48  
1.57  
1.79  
2.01  
2.21  
2.44  
2.69  
1.48  
1.64  
1.81  
1.92  
2.19  
2.47  
2.74  
3.00  
3.29  
1.60  
1.78  
1.95  
2.07  
2.37  
2.66  
2.96  
3.24  
3.55  
.50  
.65  
.75  
.85  
.90  
1.00  
1.10  
1.20  
1.25  
0.45  
0.58  
0.67  
0.76  
0.81  
0.89  
0.99  
1.07  
1.12  
0.55  
0.71  
0.82  
0.93  
0.99  
1.10  
1.21  
1.31  
1.37  
0.59  
0.77  
0.89  
1.00  
1.07  
1.18  
1.30  
1.41  
1.48  
81  
All installations and services must be performed by qualified service personnel.  
82  
All installations and services must be performed by qualified service personnel.  
Notes for Air Conditioning Troubleshooting Guide  
1.101.0 Check to see if the contactor has not pulled in. If the coil has not pulled in the  
contactor, check for 24 VAC to the coil on the contactor.  
1.101.1 Check to make sure the control transformer is powering the 115 VAC circuit.  
1.101.2 Check for 115 VAC to the control transformer. Check control fuse for 115 VAC  
supply.  
1.101.3 Check to see if the thermostat is closing to complete the 24 VAC circuit.  
Remove thermostat and jump terminals R-Y and R-G. If jumping the sub-base  
works, replace thermostat.  
1.101.4 If the contactor is reading 24 VAC on the coil, but is not pulling in the contactor,  
replace the contactor.  
1.101.5 Check the entire 24 VAC circuit between the thermostat, fan control, and  
contactor for loose connections and wires pulled away from terminations or  
terminals. These conditions can cause an open circuit.  
1.101.6 Check for 24 VAC across the refrigerant high-pressure switch. If 24 VAC is  
present, check for high liquid pressure or broken wires.  
1.201.0 If the contactor is closed and line voltage is measured across lines L1 and L2  
but the unit does not run, proceed with the following checks.  
1.201.1 Check 240-volt wire leads to the capacitors and the compressor. Make sure  
the terminals on the compressor and capacitors are not touching or loose.  
1.201.2 Check for continuity across the three terminals of the compressor. (If  
continuity is not measured, the compressor windings are opened.)  
1.201.3 Check for grounded compressor windings by checking continuity to ground.  
1.201.4 The compressor may be tapped with a rubber mallet, or piece of wood, to jar  
the compressor loose.  
1.201.5 Allow the compressor to cool below 130°F. Check for continuity between  
terminals S and C on the compressor. If you do not have continuity, the thermal  
protector may require more time to cool down.  
1.201.6 Check capacitance of the run capacitor.  
83  
All installations and services must be performed by qualified service personnel.  
2.101.0 Check to see if the condenser fan motor is excessively hot as to cause the  
thermal-overload to function. Possible causes for outdoor fan motor to kick off  
on overload are:  
1) Loose wire connections.  
2) Excessive current (amp) draw, possibly due to low operating voltage.  
3) Bad motor bearings.  
4) Excessively dirty coil causing restricted airflow.  
5) Excessively hot air being pulled into unit.  
6) Stalled fan due to blockage of rotation  
2.101.1 Make sure wire leads to the motor are making good connections. A loose  
connection can cause an excessive current draw and overheat the motor.  
2.101.2 Check for defective fan run capacitor. Use an ohmmeter on highest resistance  
scale (i.e. R X 100,000 scale) or continuity. Full needle deflection or no audible  
sound indicates the capacitor is open. Replace the capacitor.  
2.101.3 Check for continuity of the motor windings, as the motor itself may be  
damaged.  
2.102.0 Make sure the discharged hot air is not recirculating back through the coil fins.  
2.103.0 A slight restriction in the outdoor coil might cause an excessive head pressure  
that over time may cause the compressor to function on thermal-overload.  
Note: Water in the system may cause restriction after a period of time.  
2.104.0 Check for refrigerant overcharge by excessive liquid and suction line pressures.  
2.105.0 If the suction pressure is low, add charge to see if the pressure comes up to the  
specified value on the appliance-rating label.  
2.106.0 Check line voltage to the compressor to see if it is excessively high or low.  
2.107.0 A defective run capacitor can also cause the compressor to overheat. Check  
out the run capacitor.  
2.108.0 The compressor may be drawing excessive current due to an internal defect  
such as severely worn or damaged bearings.  
2.109.0 Possible causes of a high superheat (15 deg. F. or higher) could be a faulty  
expansion valve or an extremely low charge.  
3.101.0 A low suction pressure that could indicate the system is low on refrigerant  
charge. However, first review the following items.  
84  
All installations and services must be performed by qualified service personnel.  
3.101.1 Dirty air filters may restrict the airflow across the evaporator coil resulting in  
frost on the coil.  
3.101.2 Are the duct system and air blower setup to move enough air to have an 18-20  
degree F. drop across the coil?  
3.101.3 Are there any registers or dampers closed restricting the airflow of the duct  
system?  
3.101.4 If the evaporator coil frosts, this indicates a low charge or insufficient air  
movement.  
3.101.5 The coil may not frost up, but still not cool properly. Is the system slightly low  
on refrigerant? Check for an 18°F temperature drop across the coil.  
3.101.6 Make sure the liquid line has not kinked or collapsed slightly causing a  
restriction.  
3.101.7 Hold bulb in hand to see if the pressure changes (this action should increase  
the suction pressure).  
3.101.8 Check out the supply/return air blower to make sure it is functioning properly.  
3.201.0 Check the following items for high suction pressure and low liquid pressure.  
Allow at least 5 minutes off time for valve to close when pressures have  
equalized if compressor has internal pressure relief valve.  
3.201.1 There may be a restriction in the condenser coil. This could be caused by  
water or other contaminants in the system. A restriction in the coil is a very  
rare problem.  
3.201.2 Check the expansion valve for restriction of the metering orifice.  
3.301.0 For high suction pressure and low superheat temperatures, review the following  
items.  
3.301.1 If the system is overcharged with refrigerant, the system will become flooded.  
Consequently, the evaporator coil will not effectively absorb heat from the  
airflow. The temperature drop across the evaporator coil will be low.  
3.301.2 Check for a properly sized expansion valve.  
85  
All installations and services must be performed by qualified service personnel.  
XV. APPENDIX F: SPECIFICATION SHEETS  
Model No.:  
OPB24-80  
OPB30-80  
OPB36-80  
Heating Performance (using # 2 fuel oil):  
Input rate (BTUH), Maximum / Minimum :  
Heating capacity (BTUH), Maximum / Minimum :  
Design temp. rise (deg. F.) on LOW fan speed:  
Burner nozzle & oil pressure for max. input rate:  
Burner nozzle & oil pressure for min. input rate:  
105,000 / 85,000  
85,000 / 68,000  
65  
0.75 GPH @ 130 PSIG, 80 deg., hollow cone type  
0.60 GPH @ 120 PSIG, 80 deg., hollow cone type  
Cooling Performance:  
Cooling capacity (tons):  
2
2.5  
3
Fan speed:  
SEER  
800  
14  
1000  
13  
1200  
13  
HCFC-410A (R-410A)  
Refrigerant:  
Factory refrigerant charge (by weight, in ounces):  
72  
72  
80  
Nominal Electrical Power Requirements:  
208-240V / 60 Hz / 1 Ph. current (Amps):  
Min. fuse or circuit breaker rating (Amps):  
18.7  
30  
24.9  
30  
27.8  
40  
Circulating Fan, Motor, & Air Filter:  
Blower wheel design and size:  
Airflow @ 0.4 in. W.G. external static pressure:  
High speed (SCFM):  
Directly-driven, DWDI FC centrifugal, 12 in. O.D.  
1250  
1090  
970  
Medium-high speed (SCFM):  
Medium-low speed (SCFM):  
Low speed (SCFM):  
800  
ECM, air-over, 48Y  
Blower motor type & frame:  
Nominal blower motor output (HP):  
Blower motor full load current (Amps):  
Number of blower speeds:  
Maximum Rotation speed (RPM):  
Direction of rotation (from shaft end):  
Motor housing diameter (in.):  
Motor housing length (in.):  
3/4  
9.6  
Variable  
1400  
Clockwise  
5.59  
6.96  
0.5  
Shaft diameter (in.):  
3.5  
Shaft length (in.):  
Permanent  
1 - 20 x 25  
Filter type:  
Number and size of air filters (in.):  
Dimensions & Weight:  
35  
47  
Height of housing (in.):  
Width of housing (in.):  
47  
Depth of housing (in.):  
20 x 12  
20 x 12  
610  
Supply air outlet, width (in.) x height (in.):  
Return air inlet, width (in.) x height (in.):  
Approx. shipping weight (including packaging, lbs):  
86  
All installations and services must be performed by qualified service personnel.  
XVI. APPENDIX G: REPLACEMENT PARTS LIST  
87  
All installations and services must be performed by qualified service personnel.  
88  
All installations and services must be performed by qualified service personnel.  
APPENDIX H: OPB HEATING AND COOLING SYSTEMS TEST FORM  
Complete this form for each Thermo Pride OPB appliance installed. Read the instruction manual carefully  
before making tests. Retain this form with appliance.  
Name:  
Customer  
Appliance  
Address:  
City, State, & Zip Code:  
Model No.:  
Serial No.:  
AFG-TP1502  
Burner Model No.:  
Mfgr & Model of Fuel Oil Filter:  
Combustion Tests *  
Combustion Chamber Condition:  
Nozzle Size & Type:  
Oil Pump Pressure (PSIG):  
CO2 (%):  
Initial Installation  
Service # 1 Service # 2 Service # 3  
O2 (%):  
Smoke No.:  
Approximate Air Shutter Opening  
(% of max.):  
Heating System  
Gross Flue Gas Temp. (deg. F):  
Ambient Air Temp. (deg. F):  
Net Flue Gas Temp. (deg. F):  
Thermal Efficiency (%):  
Is Control Operation OK?  
Any Oil Leaks?  
Initial Installation  
Refrigeration Tests *  
Service # 1 Service # 2 Service # 3  
Suction Line Pressure (PSIG):  
Suction Line Temp. (deg. F.):  
Sat. Temp. @ Evap.(deg. F.):  
Evaporator Superheat (deg. F.):  
Liquid Line Pressure (PSIG):  
Sat. Temp. @ Cond.(deg. F.):  
Liquid Line Temp. (deg. F.):  
Condenser Subcooling (deg. F.):  
Cooling System  
Is Control Operation OK?  
Any Refrigerant Leaks?  
Tests Performed By:  
Date:  
Technician  
Installer  
Notes:  
Name:  
Address:  
Phone No:  
* Operate system for at least 10 minutes before taking measurements.  
89  

Napa Essentials 85 640 User Manual
Oreck Proshield Plus Ai User Manual
Panasonic Panafax Uf 7000 User Manual
Radio Shack 23 043 User Manual
Ricoh Aficio Dsm620 User Manual
Samson Electri Actuator Type 3374 Eb 8331 1 En User Manual
Sanyo Spw Umr94exh56 User Manual
Sharp Ar M550u User Manual
Sony Infolithium Np Fp30 User Manual
Whirlpool Acu124 User Manual