SPLIT-TYPE AIR CONDITIONERS
Natural Comfort
For
Everybody
POWER CEILING CASSETTE
WALL MOUNTED
CEILING SUSPENDED
CEILING CONCEALED
R22
Remote controller
Contents
4hp
5hp
6hp
PLH-4AAK
PLH-5AAK
PLH-6AAK
P.7
PKH-4FAK
PCH-4GAK
PEH-4EAK
P.8
P.9
PCH-5GAK
PCH-6GAK
Optional
PEH-5EAK
PEH-6EAK
P.10
PUH-4YKSA
PUH-5YKSA
PUH-6YKSA
2
The MEQ Difference
High performance, low power consumption,
and excellent reliability.
In today’s competitive environment, simply meeting industry standards, however
stringent, is not enough. Our aim is to exceed them. That’s why when it comes to
comfort, efficiency and durability: Mitsubishi Electric offers you a distinctive advantage.
We call it MEQ — Mitsubishi Electric Quality. And it's a new benchmark that results
in leading edge products, such as air conditioners that consume minimal power and
protect your investment with a long operational lifespan. You can also enjoy superb
reliability, as they’re built to endure the punishment of extreme weather conditions
year in and year out.
Mitsubishi Electric Offers
Three Important Advantages
Comfort
Efficiency
Durability
True Comfort is Yours to
Enjoy with Our Line-up
Optimum Cost Performance
and Energy Savings
Rugged Construction, Rigorous
Testing, Long-lasting Operation
We create products designed to
ensure that you and your surrounding
will always be in a perfect harmony.
Whichever model from our Mr. SLIM
line-up you may choose for commer-
cial use in restaurants, stores, or
offices will be your guarantee of
exceptional comfort in every and all
operating condition.
MEQ results in air conditioners that
are rated among the best in the
industry in terms of quality and energy
efficiency. We strive for a perfect bal-
ance of performance, reliability, low
power consumption and long opera-
tional life span. This is complement-
ed by continuous introduction of new
technologies and components that
further reduce energy requirements
and improve eco-friendliness.
MEQ is behind a mindset that goes to
extremes to ensure higher quality
products that protect the initial
investment over years of reliable ser-
vice. We subject our indoor and
outdoor units to rigorous durability
testing, including harsher tempera-
ture extremes than likely found
anywhere in the world.
3
The First Choice
for Any and All Applications
Whatever your requirements may be, Mitsubishi Electric offers advanced
split-type heat pumps perfect for any interior, any need. Significantly
decreased noise levels enhance comfort while a long list of convenient
features allow for easy installation and far less maintenance. A variety of
system control configurations plus twin multi operation — where multiple
indoor units can be connected to a single outdoor unit — make
our units the first choice for the diverse applications of today.
New Remote Controller
Renovating air conditioning communication
by advanced MA Remote Controller newly developed
Dot Liquid Crystal Display
Multi-language Display
Acknowledging the operation and control status at a glance.
The large size display upgrades visual acknowledgement
capability. The operation and control status can be understood
promptly.
8 languages
can be displayed.
Display can be switched over for 8 kinds of
language.
Multi-
Ianguage
[English]
[French]
[Spanish]
[Italian]
[German]
Display example [Operation mode]
Dot liquid crystal display section
[Russian]
[Chinese]
[Japanese]
Operation Control Function
Weekly Timer
The function of the weekly timer equipped can change the set
temperature in addition to the ON/OFF control. Up to 8 pat-
terns can be set for each calendar day.
Air conditioning operation
always within a limited
temperature range
Limiting the set
temperature range
Automatic turning off of
Auto Off timer
air conditioning operation
Preventing the random
Operation locking
modification of setting
4
Mr. SLIM New A/K Control System Configuration
Control function
System configuration
Features
Necessary parts & equipment
■ Sequential start adaptable
■ Same mode operation
■ Maximum no. of units connectable per
group: 16-refrigerant (Outdoor 16 sets)
Interface
Interface
Indoor Unit
Group control
with 1 remote
controller
Remote
■ MAC-397IF-E
(one for each outdoor unit)
Controller
1.
Outdoor Unit
Relay
■ Simultaneous ON/OFF remote
■ Timer adapter PAC-SE55RA-E
Combined
Remote/local
control
Box
Adapter
■ Operation can be switched between
the distant controller panel and
handheld controller
Distant
Controller
Panel
(connect to CN32 on indoor circuit board)
■ Relay box (on-site)
2.
3.
4.
Remote
Controller
Indoor Unit
■ 2 remote controllers can be connected
to one group
Operation with
2 remote
controllers
Remote
Controller
■ Additional remote controller (option)
Indoor Unit
■ Control with the latest command
Individual
control from
distant room
■ Extension of remote controller cord
(MAX. 500m)
■ Remote controller cord (on-site)
Remote
Controller
Indoor Unit
■ Weekly timer operation possible as
standard (7 days-8 patterns)
—
5. Timer
operation
■ Optional adapter allows operation with ■ Timer adapter PAC-SE55RA-E
timer sold on the market
(connect to CN32 on indoor circuit board)
■ Timer adapter PAC-SE55RA-E
(connect to CN32 on indoor circuit board)
■ Static signal receivable
Operation by
external signal
6.
■ Multiple remote controller adpter
PAC-725AD
■ Pulse signal receivable
(connect to CN51 on indoor circuit board)
Power
Supply
Power failure
7. automatic
recovery
■ Returns to the state before power
failure as standard
Indoor Unit
■ Function setting by remote controller
Remote
Controller
■ Multiple remote controller adpter
PAC-725AD
(connect to CN51 on indoor circuit board)
Adapter
Indoor Unit
Relay
Box
Connection of
remote display
■ Connectable to display panel in the
field adapter
8.
Distant
Display
Remote
Controller
■ Relay OMRON made LY-1 (DC12V)
PAC-SE55RA-E
Timer Adapter
MAC-397IF-E
MA & Control Terminal Interface
PAC-725AD
Multiple Remote Controller Adapter
(10 units of PAC-SA88HA-E)
5
Twin Multi Operation
Two indoor units can be connected to a single outdoor unit
and all units can be operated simultaneously from a single
remote controller using the optional multi-distribution pipe
(only indoor units of the same capacity and type can be
connected).
INDOOR UNIT
INDOOR UNIT
Outdoor Unit and Twin-Multi Combinations
2.5HP
3HP
PKH-3FAK
PCH-3GAK
PLH-3AAK
PEH-3EAK
Applicable indoor units
PEH-2.5EAK
Multi-Distribution Pipe
Twin-multi
50:50
Outdoor unit
PUH-5YKSA
PUH-6YKSA
2.5 + 2.5
3 + 3
Multi-distribution pipe
SDD-50S-E
Note
● The capacity of both indoor units must be identical.
● Different types of indoor units with identical capacities can be
connected.
● The height difference between both indoor units must be 1meter or
less.
OUTDOOR UNIT
● When two units are connected, the main unit can be used to control
the operation of all units.
Mr. SLIM Convenient Remote Controller
Advanced MA remote controller
Stylish wireless remote controller with all the latest programming features
Wired remote controller*
Wireless remote controller for PLH-AAK
● FAN SPEED SELECT button
Used to change fan speed.
● Fan speed indicator
Displays the fan speed setting
(HIGH or LOW).
● VANE CONTROL button
Used to change airflow direction.
● HOUR and MINUTE
buttons
Used to set the time and timer settings.
● MODE SELECTION button
Used to select operating modes —
Cool, Dry, and Heat, and Auto.
● TIMER button/
RESET button
● TIMER CONTROL buttons
STOP (OFF timer): When this function is
activated, the air conditioner will auto-
matically stop at the preset time.
● DOT LIQUID CRYSTAL display
● MULTI-LANGUAGE display
● OPERATION CONTROL function
● WEEKLY TIMER
START (ON timer): When this function is
activated, the air conditioner will auto-
matically start at the preset time.
*Please refer to page 4.
6
P O W E R C E I L I N G C A S S E T T E
Design uniformity improves installation flexibility
From the smallest 3HP unit to the largest 6HP model, the new high-
power ceiling cassettes offer a uniformly square 950 x 950mm width
and depth design. Thanks to the uniformity of the panel size, planning
for unit positioning in any room is enhanced and the installation of dif-
ferent capacity models within the same floor space is made possible.
PLH-AAK
S E R I E S
PLH-3AAK
PLH-4AAK
PLH-5AAK
PLH-6AAK
Unit height of only 258mm [PLH-3]
The new high-power ceiling cassette models
boast slim body height for smooth
and aesthetic installation
PLH-3AAK
even in limited
ceiling plenum
applications.
258mm
(40mm less than
conventional models)
PLH-4/5/6AAK
298mm
Automatic vane shutter
When the air conditioner is not operat-
ing, the vane shutter* closes automati-
cally to conceal the air outlet and
create an aesthetically appealing flat
surface.
Vane shutter closes automatically
During operation
When turned off
* This feature will not activate when the vane is set at
fixed position.
Wide-flow air outlet
The new high-power ceiling
■ 4-way high ceiling 2
cassettes offer a wide-flow air
outlet that enables effective air con-
ditioning of atrium-type ceilings up
4.2m
to 4.2 meters in height.
■ 3-way standard
INDEX
Ideal for high-
The demands of high-
ceiling applications such
as halls, showrooms or
shopping malls can now
ceiling applications
as high as
3.6m
Specifications .........................................p.11
Option ......................................................p.13
4.2m
(PLH-4/5/6)
■ 4-way standard
be fully answered thanks to this powerful yet highly
efficient airflow.
3.2m
Specifications according to ceiling height and number of vents
PLH-3
PLH-4/5/6
High ceiling 1 High ceiling 2
Standard
2.7
High ceiling 1 High ceiling 2
Standard
3.2
4-way
3-way
2-way
3.0
3.3
3.5
3.5
3.5
—
3.6
4.0
4.2
4.2
4.2
—
3.0
3.6
3.3
4.0
* Optional air outlet shutter plate (PAC-SG06SP-E) is necessary for two- or three-way airflow settings.
Features at-a-glance
Installation & Maintenance
Chargeless system
Compact design
Comfort
Others
•
•
•
•
•
•
•
•
•
Auto-angle airflow
Versatile airflow
72 airflow patterns
Smudge/draft free
High ceiling application
Computerized dehumidifier
Quiet operation
•
•
•
•
•
•
System control
•
Twin-multi operation
Auto vane shutter
Auto restart
Fresh air intake
Outdoor unit operating
range up to 46ºC
•
•
•
•
•
Drain water lift-up (850mm)
Handy corner-pocket
Long-life filter (2500 hrs.)
Self-diagnostic function
Filter indicator
(For wired remote controller)
Bacteria- and mold-resistant fiter
•
Flockless vanes
7
W A L L M O U N T E D
Auto-flap shutter
When the unit is turned off, the
shutter closes automatically over
the air outlet to enhance the stylish
design. The shutter also functions
as a flap to adjust airflow angle to
ensure that comforting air reaches every corner of the room.
PKH-FAK
S E R I E S
PKH-3FAK PKH-4FAK
Enhanced noise suppression
Low-noise operation has been
Model
PKH-3
PKH-4
Sound pressure level (Lo/Hi)
achieved through the introduction
of a “near-silent” fan and a
design which minimises airflow
resistance.
39/45
41/46
(dB)
Multi-directional piping
To reduce installation time, drain piping can be connected from left
and right. Refrigerant piping can also be connected from the rear, left,
right and base of the unit.
Easy removable filter
Convenient thumbscrews on the filters
enable the filters to be quickly removed for
easier cleaning.
Back plate installation guide
To save time and effort, the back plate installation guide provides clear
instructions on installation positions. The enlarged back plate secures
the unit firmly to the wall, while the support piece which lifts the unit
makes the left-side piping work much easier.
INDEX
Drain lift-up mechanism (optional)
For greater installation flexibility, the drain water pipe lift-up mecha-
nism has been raised 800mm from the base of the unit.
Specifications .........................................p.11
Option ......................................................p.13
Features at-a-glance
Installation & Maintenance
Comfort
Others
•
•
•
•
•
Chargeless system
Easy removable filter
Drain water lift-up (800mm)*
4-way multi directional piping
Self-diagnostic function
•
•
•
Auto-angle airflow
Computerized dehumidifier
Quiet operation
•
•
•
•
System control
Twin-multi operation
Auto-flap shutter
Outdoor unit operating
range up to 46ºC
*Optional
8
C E I L I N G S U S P E N D E D
Extra slim, extra stylish
Sleek and slim with stylishly curved lines, the PCH-GAK Series blends
right into any interior. It also features a single air outlet with an auto
vane that closes like a shutter when the unit is turned off to enhance
overall appearance.
PCH-GAK
S E R I E S
Innovative auto vane system
PCH-3GAK PCH-4GAK
PCH-5GAK PCH-6GAK
The auto vane system swings up and down
automatically to distribute air more evenly
throughout the room.
Auto vane
Swing
Quiet and comfortable
Smoother airflow, an improved air vent design, and a slimmer fan
combine to provide exceptionally quiet operation — a mere 43dB on
high and 37dB on low (PCH-3GAK).
New direct suspension system
For easier installation, the PCH-GAK Series features a new direct sus-
pension system that makes it unnecessary to remove nuts and bolts
from the main body. A one-touch suspension system is also available.
Direct suspension with attachment fixture attached
1. Leave attachment fixture attached to main unit.
2. Suspend the attachment fixture from the suspension bolts.
3. Simply tighten the nuts to secure the unit.
Suspension bolts
Ceiling surface
Attachment fixture
Air outlet
INDEX
Specifications .........................................p.12
Option ......................................................p.13
Piping flexibility simplifies installation
All piping, including those related to drainage, can be connected from
the right, rear and top of the unit. This provides greater flexibility in
selecting piping layout and installation locations.
Flockless vanes
With the adoption of new flockless vanes, dirt and other impurities can
be cleaned off easily with mild household detergent.
Fan phase control plus microprocessor control allow
airflow settings to match ceiling height.
Drain water lift-up mechanism can be pre-installed
(optional).
Features at-a-glance
Installation & Maintenance
Comfort
Others
•
•
Chargeless system
New direct suspension
system
Drain water lift-up (500mm)*
Flexible piping
Long-life filter (2500 hrs.)
Washable filter*
•
•
•
•
Auto swing
•
•
•
•
•
System control
Twin-multi operation
Auto restart
Auto vane shutter
Outdoor unit operating
range up to 46ºC
High ceiling application
Computerized dehumidifier
Quiet operation
•
•
•
•
•
Self-diagnostic function
*Optional
9
C E I L I N G C O N C E A L E D
Limitless installation possibilities
Offering all the benefits of split-type models plus other important
advantages, the PEH-EAK Series is not only easy to install but also very
versatile. For example, the distance between the air-intake and air-out-
let vents can be varied to allow airflow to be positioned in the opti-
mum location.
PEH-EAK
S E R I E S
PEH-2.5EAK PEH-3EAK
PEH-4EAK
PEH-5EAK
PEH-6EAK
Long-rectangular room
L-shaped room
PEH-2.5EAK
PEH-3EAK
PEH-4EAK
Room with
fixed ceiling
fixtures
PEH-5EAK
PEH-6EAK
Computerized dehumidification
The computerized dehumidifier mode — where fan speed is controlled
precisely — increases dehumidification volume while improving dehu-
midifying efficiency.
INDEX
Specifications .........................................p.12
Option ......................................................p.13
Features at-a-glance
Installation & Maintenance
Comfort
Others
•
•
•
Chargeless system
Smooth instllation
Self-diagnostic function
•
•
Computerized dehumidifier
Quiet operation
•
•
•
•
System control
Twin-multi operation
Auto restart
Outdoor unit operating
range up to 46ºC
10
S P E C I F I C A T I O N S
PLH-AAK
POWER CEILING CASSETTE
Models
Function
Capacity
Total input
COP
PLH-3AAK
PLH-4AAK
PLH-5AAK
PLH-5AAK
PLH-6AAK
PLH-6AAK
Cooling
7,700
3.32
Heating
8,400
3.11
Cooling
9,700
3.46
Heating
10,400
3.45
Cooling
12,400
4.51
Heating
14,000
4.46
Cooling
14,000
5.07
Heating
16,100
4.92
W
kW
W/W
2.32
2.70
2.80
3.01
2.75
3.14
2.76
3.27
Model name
PLH-3AAK
PLH-4AAK
External finish
Power supply
Galvanized sheets with gray heat insulation
Single phase, 50Hz, 240V
Airflow (Lo-Hi)
l/s
Pa ( mmAq)
dB
250 – 333
28 – 34
333 – 467
367 – 500
External static pressure
Indoor unit
0 (direct blow)
Sound pressure level (Lo-Hi)
Dimensions
33 – 41
35 – 43
37 – 45
W mm
D mm
H mm
840
840
258
24
298
30
Weight
kg
30
32
External finish
Munsell 0.70Y 8.59/0.97
W mm
D mm
H mm
kg
950
950
30
Indoor grille
Dimensions
Weight
5
Model name
PUH-3YKA
PUH-4YKSA
PUH-5YKSA
PUH-6YKSA
External finish
Munsell 5Y 7/1
Power supply
3-phase 50Hz, 415V (4 wires)
Capillary tube
Refrigerant (R-22) control
Compressor output
kW
2.4
2.7
3.5
4.0
Internal thermostat, HP switch /
thermal relay, thermal switch,
anti- phase protector
Thermal relay, thermal switch, HP switch, anti-phase protector
Protection devices
Outdoor unit
Airflow
l/s
W
833
1,584
38
1,667
Crankcase heater
Sound pressure level
Sound power level
dB
52
66
54
69
55
56
71
dB
70
W mm
D mm
H mm
kg
870
970
Dimensions
Weight
295 + 24
345 + 24
1,258
114
850
75
94
117
PKH-FAK
WALL MOUNTED
Models
Function
Capacity
Total input
COP
PKH-3FAK
PKH-4FAK
Cooling
Heating
9,100
3.04
Cooling
9,500
3.31
Heating
10,700
3.30
W
kW
7,900
3.25
2.43
W/W
3.00
2.87
3.24
Model name
PKH-3FAK
PKH-4FAK
External finish
Power supply
Munsell 3.4Y 7.7/0.8
Single phase, 50Hz, 240V
Airflow (Lo-Hi)
l/s
Pa (mmAq)
dB
250 – 333
367 – 467
External static pressure
Indoor unit
0 (direct blow)
41 – 46
1,680
235
Sound pressure level (Lo-Hi)
Dimensions
39 – 45
1,400
W mm
D mm
H mm
kg
340
Weight
24
28
Model name
PUH-3YKA
PUH-4YKSA
External finish
Power supply
Munsell 5Y 7/1
3-ph., 50Hz, 415V (4 wires)
Refrigerant (R-22) control
Compressor output
Capillary tube
kW
2.4
2.7
Internal thermostat, HP switch/thermal relay, thermal switch, HP switch,
anti-phase protector
Thermal relay, thermal switch, HP switch, anti-phase protector
1,584
Protection devices
Outdoor unit
Airflow
l/s
W
833
Crankcase heater
Sound pressure level
Sound power level
38
dB
52
66
54
69
dB
W mm
D mm
H mm
kg
870
Dimensions
Weight
295 + 24
850
75
1,258
94
11
S P E C I F I C A T I O N S
PCH-GAK
CEILING SUSPENDED
PCH-3GAK
PCH-4GAK
PCH-4GAK
PCH-5GAK
PCH-6GAK
Models
Function
Capacity
Total input
Cooling
7,600
3.28
Heating
8,500
3.07
Cooling
10,000
3.36
Heating
10,450
3.35
Cooling
12,400
4.45
Heating
13,900
4.40
Cooling
14,500
4.97
Heating
15,000
4.82
W
kW
COP
W/W
2.32
2.77
2.98
3.12
2.79
3.16
2.92
3.11
Model name
External finish
Power supply
Airflow (Lo-Hi)
PCH-3GAK
PCH-5GAK
PCH-6GAK
Munsell 0.70Y 8.59/0.97
Single phase, 50Hz, 240V
l/s
Pa (mmAq)
dB
233 – 300
37 – 43
333 – 417
40 – 45
450 – 567
1,620
External static pressure
Indoor unit
0 (direct blow)
680
Sound pressure level (Lo-Hi)
41 – 46
42 – 48
W mm
D mm
H mm
kg
1,310
Dimensions
210
34
270
43
Weight
37
45
PUH-3YKA
PUH-4YKSA
PUH-5YKSA
PUH-6YKSA
Model name
External finish
Power supply
Munsell 5Y 7/1
3-ph., 50Hz, 415V (4 wires)
Refrigerant (R-22) control
Compressor output
Capillary tube
kW
2.4
2.7
3.5
4.0
Internal thermostat, HP switch/thermal
relay, thermal switch, HP switch,
anti-phase protector
thermal relay, thermal switch,
HP switch, anti-phase protector
Internal thermostat, thermal switch, HP switch, anti- phase protector
1,667
Protection devices
Outdoor unit
Airflow
l/s
W
833
1,584
38
Crankcase heater
Sound pressure level
Sound power level
dB
52
66
54
69
55
70
56
71
dB
W mm
D mm
H mm
kg
870
295 + 24
970
Dimensions
Weight
345 +24
850
75
1,258
114
94
117
PEH-EAK
CEILING CONCEALED
Models
PEH-2.5EAK
PEH-3EAK
PEH-4EAK
Cooling Heating
9,700
PEH-5EAK
PEH-6EAK
Function
Cooling
6,700
2.90
Heating
6,800
2.71
Cooling
Heating
8,300
3.33
Cooling
12,400
4.86
Heating
13,000
4.81
Cooling
Heating
17,400
5.66
Capacity
W
kW
8,000
3.47
2.31
10,400
3.63
15,200
5.81
Total input
COP
3.64
2.66
W/W
2.31
2.51
2.49
2.87
2.55
2.70
2.62
3.07
Model name
External finish
Power supply
PEH-2.5EAK
PEH-3EAK
PEH-4EAK
PEH-5EAK
PEH-6EAK
Galvanized sheets
Single phase, 50Hz, 240V
450 – 567
Airflow (Lo-Hi)
l/s
Pa (mmAq)
dB
367 – 450
567 – 700
1,255
800 – 1,000
External static pressure
127 (12.7) at Hi-notch
Indoor unit
Sound pressure level (Lo-Hi)
Dimensions
52 – 55
785
54 – 58
51 – 55
1,415
W mm
D mm
H mm
kg
1,055
690
428
Weight
45
46
58
72
73
Model name
External finish
PUH-2.5AKA
PUH-3VKA / PUH-3YKA
PUH-4YKSA
Munsell 5Y 7/1
PUH-5YKSA
PUH-6YKSA
Single ph., 50Hz, 240V/
3-ph., 50Hz, 415V (4 wires)
Power supply
Single ph., 50Hz, 240V
2.0
3-ph., 50Hz, 415V (4 wires)
Refrigerant (R-22) control
Compressor output
Capillary tube
2.7
kW
2.2 / 2.4
3.5
4.0
Intermal thermostat, HP
switch/thermal relay, thermal
switch, HP switch, anti-
phase protector
Thermal relay, thermal
switch, HP switch, anti-
phase protector
Internal thermostat,
thermal switch,
HP switch, anti-phase protector
Internal thermostat,
HP switch
Protection devices
Outdoor unit
Airflow
l/s
W
833
1,584
1,667
Crankcase heater
Sound pressure level
Sound power level
38
54
69
dB
52
66
55
70
56
71
dB
W mm
D mm
H mm
kg
870
970
Dimensions
Weight
295 + 24
345 +24
850
1,258
114
68
75
94
117
12
GENERAL SPECIFICACIONS FOR ALL MODELS
■ Notes for All Specifications
● Rating conditions: Cooling - Indoor 27ºCDB, 19ºCWB; Outdoor 35ºCDB
Heating - Indoor 20ºCDB
● Data based on indicated voltage Indoor unit : 1-ph, 240V, 50Hz
Outdoor unit: 1-ph, 240V, 50Hz/3-ph, 415V, 50Hz
; Outdoor 7ºCDB,6ºCWB
● Refrigerant piping length (one-way): 5m (16ft)
● Refrigerant charge is suitable for 5m piping length.
■ Guaranteed Operating Range
Limits
Indoors
Outdoors
-5ºC DB
46ºC DB
Lower
Upper
Lower
Upper
21ºC DB, 15.5ºC WB
35ºC DB, 22.5ºC WB
20ºC DB
Cooling
Heating
-8.5ºC DB, -9.5ºC WB
21ºC DB, 15.5ºC WB
27ºC DB
■ Refrigerant Piping
Models
Between indoor & outdoor units
Max. piping length, m
Pipe size O.D., mm
Liquid
Gas
Max. height difference, m
Max. number of bends
PLH-3AAK, PKH-3FAK,
50
50
50
15
Ø 9.52
Ø 9.52
Ø 15.88
PCH-3GAK, PEH-2.5EAK, PEH-3EAK
PKH-4FAK PLH-4/5/6AAK,
50
15
Ø 19.05
PCH-4/5/6GAK, PEH-4/5/6EAK
■ Optional Refrigerant Pipes
Part number
Pipe length
5m (16ft)
7m (23ft)
10m (33ft)
15m (49ft)
Connection method
Pipe size OD, mm (ft)
Applicable models
PAC-05FFS-E
PAC-SC51PI-E
PAC-SC52PI-E
PAC-SC53PI-E
PAC-SC54PI-E
Flared-flared
PAC-07FFS-E
PAC-10FFS-E
PAC-15FFS-E
Flared-flared
Liquid: Ø 9.52 (3/8) Gas: Ø 15.88 (5/8)
PKH-3FAK, PLH-3AAK, PCH-3GAK, PEH-2.5EAK, PEH-3EAK
Liquid: Ø 9.52 (3/8) Gas: Ø 19.05 (3/4)
PKH-4FAK, PLH-4/5/6AAK, PCH-4/5/6GAK, PEH-4/5/6EAK
■ Additional Refrigerant Charge [R-22: kg]
Piping length (one-way)
Models
5m
0
10m
15m
20m
25m
30m
35m
0.2
0.2
0.3
0.3
0.3
40m
0.2
0.2
0.3
0.3
0.3
45m
0.5
0.5
0.6
0.6
0.6
50m
PUH-2.5AKA
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.5
0.5
0.6
0.6
0.6
PUH-3VKA/PUH-3YKA
PUH-4YKSA
0
0
PUH-5YKSA
0
PUH-6YKSA
0
■ Cooling Capacity Correction Factors
Models
Correction factors (Cooling / Heating)
One-way piping length, m
5
10
15
20
25
30
35
40
45
50
PEH-2.5EAK
1.00/1.00
0.989/1.00
0.980/1.00
0.960/1.00
0.950/1.00
0.970/1.00
0 .9 4 0 / 0 .9 9 8
0 .9 3 0 / 0 .9 9 5
0 .9 2 0 / 0 .9 9 3
0 .9 1 0 / 0 .9 9 0
PKH-3FAK, PCH-3GAK,
PLH-3AAK, PEH-3EAK
PKH-4FAK PCH-4GAK,
PLH-4AAK, PEH-4EAK
PCH-5GAK PLH-5AAK,
PEH-5EAK
PCH-6GAK, PLH-6AAK
PEH-6EAK
1.00/1.00
1.00/1.00
1.00/1.00
1.00/1.00
0.981/1.00
0.989/1.00
0.981/1.00
0.975/1.00
0.968/1.00
0.980/1.00
0.968/1.00
0.955/1.00
0.952/1.00
0.970/1.00
0.952/1.00
0.935/1.00
0.940/1.00
0.960/1.00
0.940/1.00
0.918/1.00
0.925/1.00
0.950/1.00
0.925/1.00
0.900/1.00
0 .9 1 3 / 0 .9 9 8
0 .9 4 0 / 0 .9 9 8
0 .9 1 3 / 0 .9 9 8
0 .8 8 4 / 0 .9 9 8
0 .9 0 0 / 0 .9 9 5
0 .8 8 6 / 0 .9 9 3
0 .9 2 0 / 0 .9 9 3
0 .8 8 6 / 0 .9 9 3
0 .8 5 5 / 0 .9 9 3
0 .8 7 4 / 0 .9 9 0
0 .9 3 0 / 0 .9 9 5
0 .9 0 0 / 0 .9 9 5
0 .8 6 9 / 0 .9 9 5
0 .9 1 0 / 0 .9 9 0
0 .8 7 4 / 0 .9 9 0
0 .8 4 0 / 0 .9 9 0
■ Main Optional Parts
Model
Description
Applicable models
New A/K control
MAC-397IF-E
PAC-SE55RA-E
PAC-725AD
MA & Control Terminal Interface
Timer Adapter
New A/K control
New A/K control
New A/K control
PUH-2.5~4
PUH-5/6
Multiple Remote Controller Adapter (10 sets)
Remote Sensor
PAC-SE41TS-E
PAC-SA46DS-E
PAC-SA47DS-E
PAC-292SG-D
SDD-50S-E
Drain Socket
Drain Socket
Air Outlet Guide
PUH-2.5~6
PUH-5/6
Distribution Pipe for Twin Use
Multi-Function Casement
High Efficiency Filter Element
Air Outlet Shutter Plate
Drain Lift-Up Mechanism
Drain Lift-Up Mechanism
High Efficiency Filter
PAC-SG03TM-E
PAC-SG01KF
PAC-SG06SP-E
PAC-SE85DMA-E
PAC-SE86DMA-E
PAC-SE81KF-E
PAC-SE82KF-E
PAR-SL99B-E
PAR-SL97A-E
PLH series
PLH series
PLH series
PCH-3
PCH-4~6
PCH-3/4
High Efficiency Filter
PCH-5/6
Wireless Remote Controller
Wireless Remote Controller
PCH series
PLH series
13
■ Outdoor Unit Installation Location
• When installing a single outdoor unit:
Obstacle at rear only
Service space
Top obstacles
Obstacles at the right, left
and rear
Obstacles at the front and
rear only
Obstacle at the front and
rear only
PUH-2.5, 3
10mm or more
Obstruction width: 1.5 times the width of
outdoor unit or smaller
Obstruction height: Unit height or lower
Air outlet guide
500mm or more
100mm or more
3000mm or more
100mm or more
PUH-4,5,6
10mm or more
PUH-2.5, 3
PUH-4,5,6
A
B
C
D
E
F
G
H
I
J
100mm or more
10mm or more
500mm or more
500mm or more
Service space
100mm or more
500mm or more
10mm or more
200mm or more
150mm or more
10mm or more
500mm or more
500mm or more
K
L
M
N
O
P
500mm or more
150mm or more
3800mm or more
150mm or more
150mm or more
500mm or more
10mm or more
300mm or more
Q
• When installing many outdoor units:
Face-to-face arrangement
(with air outlet guides)
Face-to-face arrangement
(without air outlet guides)
Parallel arrangement
(with air outlet guides)
Parallel arrangement
(without air outlet guides)
PUH-2.5, 3
PUH-4,5,6
A
B
C
D
E
F
G
H
I
200mm or more
500mm or more
200mm or more
1200mm or more
1000mm or more
2000mm or more
100mm or more
10mm or more
300mm or more
500mm or more
300mm or more
1500mm or more
1500mm or more
2500mm or more
150mm or more
10mm or more
Side-by-side arrangement
200mm or more
300mm or more
Up to 10 units (When the optional air outlet
guides are used, no more than five units should
be arranged side by side.)
J
K
1000mm or more
1000mm or more
Precautions/recommendations concerning the installation and operation of Mitsubishi Electric Mr. Slim air conditioners.
■ When used in rooms with high ceilings, it is recommended that a ceiling fan or
circulator be installed to improve air circulation and temperature variations within
the room.
■ Avoid exposure to high-frequency waves as this may cause the microprocessor
to malfunction.
■ Rated noise levels were derived from tests in an anechoic test room. Noise
levels may therefore be greater depending on the surroundings, application,
and/or manner of installation.
■ The remote-control circuits under microprocessor control remain on at all
times whether the air conditioner is or is not in operation. For more economical
operation, it is recommended that the main power switch be turned off when the
air conditioner(s) is not used for long periods.
■ Avoid using air conditioners in rooms with high humidity because excessive
condensation will occur as the air cools.
■ Avoid using air conditioning units in areas where they are exposed to oil or oily
smoke (cooking areas or machine shops). Oil which adheres to the heat
exchangers will cause reduced efficiency, generate mist and may damage plastic
components.
■ To avoid fire hazards, do not use air conditioners in areas where inflammable
gases are present.
■ Odours for buildings, cosmetics, perspiration, cigarette smoke, etc., may
accumulate in the heat exchanger and emanate from the air conditioner. This is
not indicative of mechanical trouble.
14
Mitsubishi Electric Shizuoka Works acquired ISO
9001 certification under Series 9000 of the
International Standard Organization (ISO) based on
a review of Quality warranties for the production of
refrigeration and air conditioning equipment.
Mitsubishi Electric Shizuoka Works acquired envi-
ronmental management system standard ISO
14001 certification.
NATIONAL
ACCREDITATION
OF CERTIFICATION
BOOIS
ISO 9001
Certificate Number 49385
Certificate Number EC97J1132
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
MITSUBISHI ELECTRIC AUSTRALIA PTY LTD.
BLACK DIAMOND TECHNOLOGIES
www.mitsubishielectric.com.au (Incorporated in New South Wales)ABN 58 001 215 792
New South Wales: Victoria/Tasmania:
Queensland
Unit 12,
Far North
South Australia/
Northern Territory: Unit 5,
77 Port Road,
Hindmarsh 5007
Ph: (08) 8340 2000
Western Australia:
Wellington:
Auckland:
Unit 1,
4 Walls Road
Po Box 12-726,
Penrose
Christchurch:
Suite 2, Level 1,
37 Mandeville Street
Po Box 1604
348 Victoria Road,
Rydalmere 2116
Ph: (02) 9684 7555
Unit 4,
Queensland:
Capricorn Air,
13 Mackley st,
Garbutt 4814
Ph: (07) 4775 5222
1 Parliament Street
Po Box 30-772
Lower Hutt
Wellington
Ph: (04) 560 9147
Fax: (04) 560 9133
303 Burwood Highway, 469 Nudgee Rd.,
East Burwood 3151
329 Collier Road,
Bassendean 6054
Ph: (08) 9377 3400
Hendra 4011
Ph: (07) 3623 2000
Fax: (02) 9898 1043 Ph: (03) 9262 9855
Ph: (03) 341 2837
Fax: (08) 8340 0555 Fax: (08) 9377 3499
Ph: (09) 526 9347 Fax: (03) 341 2838
Fax: (09) 526 9369
Fax: (03) 9262 9844
Fax: (07) 3630 1888
Fax: (07) 4775 5305
Revised publication, effective August 2006
Superseding publication of L-179-0-C3085-E November 2005
Specifications subject to change without notice.
L-179-0-C3085-F SI-0608 Printed in Japan(NLP)
|
Mitsubishi Motors Automobile Parts Km148 User Manual
Olivetti 450 User Manual
Panasonic 135fp User Manual
Philips Sbc Sc762 User Manual
Royal Sovereign Arp 1400bls User Manual
Sanyo Ks3032 User Manual
Sharp Al 2030 User Manual
Trion M1100 User Manual
Whirlpool Acq154 User Manual
York Ymbe User Manual