		 Mitsubishi Electronics Mitsubishi Digital Electronics Air Conditioner Ms Awa User Manual  | 
	
| 	
		 Revision B:   
					• MXZ-2A20NA- 1 , MXZ-4A36NA, MSZ-FD,   
					MSZ-D and MSY-D have been added.   
					Please void OBT16 REVISED EDITION-A.   
					No. OBT16   
					REVISED EDITION-B   
					SERVICE TECHNICAL GUIDE   
					Wireless type Models   
					MS-A•WA   
					MSZ-A•NA   
					· MU-A•WA   
					· MUZ-A•NA   
					· MUZ-A•NA -   
					· MUY-A•NA   
					U 
					MSY-A•NA   
					MSZ-FD•NA · MUZ-FD•NA   
					U 
					· MUZ-FD•NA -   
					· MUZ-D•NA   
					MSZ-D•NA   
					MSY-D•NA   
					U 
					· MUZ-D•NA -   
					· MUY-D•NA   
					Inverter-controlled multi system type Models   
					· MXZ-A•NA   
					CONTENTS   
					1. MS MICROPROCESSOR CONTROL··················4   
					2. MSZ, MSY MICROPROCESSOR CONTROL······7   
					3. MXZ MICROPROCESSOR CONTROL··············21   
				1. MS MICROPROCESSOR CONTROL···························································4   
					Indoor unit models   
					Outdoor unit models   
					MS-A09WA   
					MS-A12WA   
					MU-A09WA   
					MU-A12WA   
					1-1. COOL OPERATION ···············································································4   
					1-2. DRY OPERATION ··················································································4   
					1-3. AUTO VANE OPERATION·····································································6   
					2. MSZ, MSY MICROPROCESSOR CONTROL···············································7   
					Indoor unit models   
					Outdoor unit models   
					MSZ-A09NA   
					MSZ-A12NA   
					MSZ-A15NA   
					MSZ-A17NA   
					MSZ-A24NA   
					MSY-A15NA   
					MSY-A17NA   
					MSY-A24NA   
					MSZ-FD09NA MUZ-A09NA   
					MSZ-FD12NA MUZ-A12NA   
					MUZ-FD09NA   
					MUZ-FD12NA   
					MUZ-D30NA   
					MUZ-D36NA   
					MUY-D30NA   
					MUY-D36NA   
					MSZ-D30NA   
					MSZ-D36NA   
					MSY-D30NA   
					MSY-D36NA   
					MUZ-A15NA   
					MUZ-A17NA   
					MUZ-A24NA   
					MUY-A15NA   
					MUY-A17NA   
					MUY-A24NA   
					2-1. COOL OPERATION ··············································································7   
					2-2. DRY OPERATION ·················································································8   
					2-3. HEAT OPERATION···············································································8   
					2-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION ·····················10   
					2-5. OUTDOOR FAN MOTOR CONTROL·················································11   
					2-6. AUTO VANE OPERATION··································································11   
					2-7   
					2-8   
					2-9   
					. 
					. 
					. 
					INVERTER SYSTEM CONTROL························································12   
					OPERATIONAL FREQUENCY CONTROL OF OUTDOOR UNIT ·····17   
					EXPANSION VALVE CONTROL (LEV CONTROL)···························18   
					3. MXZ MICROPROCESSOR CONTROL·······················································21   
					Outdoor unit models   
					MXZ-2A20NA   
					MXZ-3A30NA   
					MXZ-4A36NA   
					3-1. INVERTER SYSTEM CONTROL·························································21   
					3-2. EXPANSION VALVE CONTROL (LEV CONTROL)····························23   
					3-3. OPERATIONAL FREQUENCY RANGE ··············································29   
					3-4. HEAT DEFROSTING CONTROL·························································30   
					3-5. DISCHARGE TEMPERATURE PROTECTION CONTROL·······················30   
					3-6. OUTDOOR FAN CONTROL ································································30   
					3-7. PRE-HEAT CONTROL·········································································31   
					3-8. COOL OPERATION····················································································31   
					3-9. DRY OPERATION·································································· BACK COVER   
					3-10   
					. HEAT OPERATION···························································BACK COVER   
					3 
				1 
					MS MICROPROCESSOR CONTROL   
					MS-A•WA   
					MU-A•WA   
					1-1. COOL ( ) OPERATION   
					1. Thermostat control   
					Thermostat is ON or OFF by difference between room temperature and set temperature   
					Room temperature minus   
					Room temperature minus   
					set temperature (Initial)   
					set temperature (During operation)   
					Thermostat   
					ON   
					OFF   
					-1.8 °F or more   
					less than-1.8 °F   
					-1.8 °F   
					-1.3 °F   
					2. Indoor fan speed control   
					Indoor fan operates continuously at the set speed by FAN SPEED CONTROL button regardless of the thermostat’s OFF-   
					ON.   
					In AUTO the fan speed is as follows.   
					Room temperature minus   
					set temperature (Initial)   
					3.1 °F or more   
					Room temperature minus   
					set temperature (During operation)   
					Fan speed   
					High   
					Med.   
					Low   
					between 1.8 and 3.1 °F   
					less than 1.8 °F   
					5.4 °F   
					3.1 °F   
					1.8 °F   
					3. Coil frost prevention   
					Temperature control   
					When the indoor coil thermistor RT12 reads 37 °F or below the coil frost prevention mode starts immediately.   
					However, the coil frost prevention doesn’t work for 5 minutes since the compressor has started.   
					The indoor fan operates at the set speed and the compressor stops for 5 minutes.   
					After that, if the indoor coil thermistor still reads below 37 °F, this mode is prolonged until the indoor coil thermistor reads   
					over 37 °F.   
					Time control   
					When the three conditions as follows have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes.   
					a. Compressor has been continuously operating.   
					b. Indoor fan speed is Low or Med.   
					c. Room temperature is below 79 °F.   
					When compressor stops, the accumulated time is cancelled and when compressor restarts, time counting starts from the   
					beginning.   
					Time counting also stops temporarily when the indoor fan speed becomes High or the room temperature exceeds 79 °F.   
					However, when two of the above conditions (b. and c.) are satisfied again. Time accumulation is resumed.   
					Operation chart   
					Example   
					ON   
					Compressor   
					Outdoor fan   
					OFF   
					( Continuously at set speed)   
					Indoor fan   
					ON   
					Set temperature and   
					initial room temperature in dry mode   
					1-2. DRY ( ) OPERATION   
					°F   
					95   
					Set temperature is as shown on the right chart.   
					The system for dry operation uses the same refrigerant circuit as the   
					cooling circuit.   
					The compressor and the indoor fan are controlled by the room tem-   
					perature.   
					By such controls, indoor flow amounts will be reduced in order to   
					lower humidity without much room temperature decrease.   
					86   
					77   
					68   
					59   
					50   
					50   
					59   
					68   
					77   
					86   
					95 °F   
					Initial room temperature   
					4 
				1. Thermostat control   
					Thermostat is ON or OFF by difference between room temperature and set temperature.   
					Room temperature minus   
					Room temperature minus   
					set temperature (Initial)   
					set temperature (During operation)   
					Thermostat   
					ON   
					OFF   
					-1.8 °F or more   
					less than-1.8 °F   
					-1.8 °F   
					-1.3 °F   
					2. Indoor fan speed control   
					Indoor fan operates at the set speed by FAN SPEED CONTROL button.   
					When thermostat OFF (compressor OFF), fan speed becomes Very Low.   
					In AUTO the fan speed is as follows.   
					Room temperature minus   
					set temperature (Initial)   
					3.1 F or more   
					Room temperature minus   
					set temperature (During operation)   
					Fan speed   
					High   
					Med.   
					Low   
					between 1.8 and 3.1 F   
					less than 1.8 F   
					4.5   
					F 
					3.1   
					F 
					1.8   
					F 
					3. The operation of the compressor and indoor/ outdoor fan   
					Compressor operates by room temperature control and time control.   
					Set temperature is controlled to fall 4 °F from initial room temperature.   
					Indoor fan and outdoor fan operate in the same cycle as the compressor.   
					•When the room temperature is 73 °F or over:   
					When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.   
					When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.   
					•When the room temperature is under 73 °F.   
					When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF.   
					When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.   
					Operation time chart   
					Example   
					ON   
					Thermostat   
					OFF   
					ON   
					Indoor fan   
					OFF   
					ON   
					Outdoor fan   
					Compressor   
					OFF   
					8 minutes   
					4 minutes   
					3 minutes   
					1 minute   
					4. Coil frost prevention   
					Coil frost prevention is as same as COOL mode. (2-1.3.)   
					The indoor fan maintains the actual speed of the moment. However ,when coil frost prevention works while the compressor   
					is not operating, its speed becomes the set speed.   
					5 
				1-3. AUTO VANE OPERATION   
					1. Horizontal vane   
					ECONO COOL (   
					) operation (ECONOmical operation)   
					When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 3.6 °F higher than that in   
					COOL mode.   
					Also the horizontal vane swings in various cycle according to the temperature of indoor heat exchanger (indoor coil   
					thermistor).   
					SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher than that   
					in COOL mode, the air conditioner can keep comfort. As a result, energy can be saved.   
					ECONO COOL operation is cancelled when ECONO COOL button is pressed once again or VANE CONTROL button is   
					pressed or change to other operation mode.   
					<SWING operation>   
					In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”.   
					According to the temperature of indoor coil thermistor at starting of this operation, next downward blow time is decided.   
					Then when the downward blow has been finished, next horizontal blow time is decided.   
					For initial 10 minutes the swing operation is performed in table G~H for quick cooling.   
					Also, after 10 minutes when the difference of set temperature and room temperature is more than 3.6 °F, the swing   
					operation is performed in table D~H for more cooling.   
					The air conditioner repeats the swing operation in various cycle as follows.   
					Temperature of indoor   
					coil thermistor (°F)   
					Downward blow time Horizontal blow time   
					(second)   
					(second)   
					A 
					B 
					C 
					D 
					E 
					F 
					59 or less   
					59 to 63   
					63 to 64   
					64 to 68   
					68 to 70   
					70 to 72   
					72 to 75   
					more than 75   
					2 
					5 
					8 
					11   
					14   
					17   
					20   
					23   
					23   
					20   
					17   
					14   
					11   
					8 
					G 
					H 
					5 
					2 
					6 
				2 
					MSZ,MSY MICROPROCESSOR CONTROL   
					MSZ-A•NA   
					MSY-A•NA   
					MUZ-A•NA   
					MUY-A•NA   
					MSZ-FD•NA MSY-D•NA   
					MSZ-D•NA   
					MUZ-FD•NA MUY-D•NA   
					MUZ-D•NA   
					2-1. COOL ( ) OPERATION   
					1. Thermostat control   
					Thermostat is ON or OFF by difference between room temperature and set temperature   
					Room temperature minus   
					set temperature (Initial)   
					Room temperature minus   
					set temperature (During operation)   
					Thermostat   
					ON   
					OFF   
					-1.8 °F or more   
					less than-1.8 °F   
					-1.8 °F   
					-1.3 °F   
					2. Indoor fan speed control   
					Indoor fan operates continuously at the set speed by FAN SPEED CONTROL button regardless of the thermostat’s OFF-   
					ON.   
					In AUTO the fan speed is as follows.   
					Room temperature minus   
					set temperature (Initial)   
					3.1 °F or more   
					Room temperature minus   
					set temperature (During operation)   
					MSZ-A   
					MSY-A   
					Fan speed   
					High   
					Med.   
					Low   
					between 1.8 and 3.1 °F   
					less than 1.8 °F   
					5.4 °F   
					3.1 °F   
					1.8 °F   
					Room temperature minus   
					set temperature (Initial)   
					2.7 °F or more   
					between 1.8 and 2.7 °F   
					less than 1.8 °F   
					Room temperature minus   
					set temperature (During operation)   
					MSZ-FD   
					MSZ-D   
					MSY-D   
					Fan speed   
					High   
					Med.   
					Low   
					5.4 °F   
					2.7 °F   
					1.8 °F   
					3. Coil frost prevention   
					The compressor operational frequency is controlled to prevent the temperature of indoor heat exchanger from falling exces-   
					sively.   
					The compressor is turned OFF for 5 minutes when the temperature of indoor coil thermistor continues 37 °F or less for 5   
					minutes or more.   
					The indoor fan maintains the actual speed of the moment.   
					4. Low outside temperature operation   
					If the outside temperature falls to 64 °F or less during operation in COOL mode, the unit will switch to the low outside tem-   
					perature operation mode.   
					<Operation>   
					(1) Outdoor fan control   
					The outdoor fan rotation speed slows down to maintain sufficient cooling capacity.   
					NOTE: Even when the unit is in the "thermostat-off" status under the low outside temperature operation mode, the out-   
					door fan rotation does not stop.   
					(2) Dew drop prevention   
					When the ambient temperature thermistor reads 10 °F (MUZ-A MUY-A MUZ-D MUY-D), -4 °F (MUZ-FD) or less, as   
					coil frost or dew drop from indoor unit may occur, the compressor turns OFF with the outdoor fan ON for prevention of   
					them.   
					(3) Outdoor temperature detecting control   
					To detect the exact outdoor temperature in this mode, the compressor turns OFF but the outdoor fan stays ON for 3   
					minutes once 1 hour. If the outdoor temperature rises over 64 °F, the unit goes back to the normal COOL mode. If the   
					outside temperature stays below 64 °F, the unit continues to run in the low outside temperature operation mode.   
					Other protections work as well as in the normal COOL mode.   
					7 
				Set temperature and   
					initial room temperature in dry mode   
					2-2. DRY ( ) OPERATION   
					°F   
					95   
					Set temperature is as shown on the right chart.   
					The system for dry operation uses the same refrigerant circuit as the   
					cooling circuit.   
					The compressor and the indoor fan are controlled by the room tem-   
					perature.   
					By such controls, indoor flow amounts will be reduced in order to   
					lower humidity without much room temperature decrease.   
					86   
					77   
					68   
					59   
					50   
					50   
					59   
					68   
					77   
					86   
					95 °F   
					Initial room temperature   
					1. Thermostat control   
					Thermostat is ON or OFF by difference between room temperature and set temperature.   
					Room temperature minus   
					set temperature (Initial)   
					Room temperature minus   
					set temperature (During operation)   
					Thermostat   
					ON   
					OFF   
					-1.8 °F or more   
					less than-1.8 °F   
					-1.8 °F   
					-1.3 °F   
					2. Indoor fan speed control   
					Indoor fan operates at the set speed by FAN SPEED CONTROL button.   
					When thermostat OFF (compressor OFF), fan speed becomes Very Low.   
					In AUTO the fan speed is as follows.   
					Room temperature minus   
					set temperature (Initial)   
					3.1 F or more   
					Room temperature minus   
					set temperature (During operation)   
					Fan speed   
					High   
					Med.   
					Low   
					between 1.8 and 3.1 F   
					less than 1.8 F   
					4.5   
					F 
					3.1   
					F 
					1.8   
					F 
					3. Coil frost prevention   
					Coil frost prevention is as same as COOL mode. (2-1.3.)   
					The indoor fan maintains the actual speed of the moment. However ,when coil frost prevention works while the compressor   
					is not operating, its speed becomes the set speed.   
					4. Low outside temperature operation   
					Low outside temperature operation is as same as COOL mode. (2-1.4.)   
					2-3. HEAT ( ) OPERATION (MSZ)   
					1. Thermostat control   
					Thermostat is ON or OFF by difference between room temperature and set temperature.   
					Room temperature minus   
					set temperature (Initial)   
					less than 3.6 °F   
					Room temperature minus   
					set temperature (During operation)   
					Thermostat   
					ON   
					OFF   
					3.6 °F or more   
					3.6 °F   
					3 °F   
					2. Indoor fan speed control   
					(1) Indoor fan operates at the set speed by FAN SPEED CONTROL button.   
					In Auto the fan speed is as follows.   
					Room temperature minus   
					set temperature (Initial)   
					Room temperature minus   
					set temperature (During operation)   
					Fan speed   
					High   
					Med.   
					Low   
					3.6 °F or more   
					between 0.4 and 3.6 °F   
					less than 0.4 °F   
					3.6 °F 7.2 °F   
					0.4 °F   
					3 °F   
					8 
				(2) Cold air prevention control   
					MSZ-A09/12/15/17 MSZ-FD MSZ-D   
					When the compressor is not operating,   
					( ) if the temperature of room temperature thermistor is less than 66 °F, the fan stops.   
					( 
					) if the temperature of room temperature thermistor is 66 °F or more and   
					( ) if the temperature of indoor coil themistor is less than 32 °F, the fan stops.   
					( 
					) if the temperature of indoor coil themistor is 32 °F or more, the fan operates at Very Low.   
					When the compressor is operating,   
					( ) if the temperature of indoor coil themistor is 104 °F or more, the fan operates at set speed.   
					( 
					) if the temperature of indoor coil themistor is less than 104 °F and   
					( ) if heating operation starts after defrosting, the fan stops.   
					( 
					( 
					) if the temperature of room temperature thermistor is 66 °F or less, the fan stops.   
					) if the temperature of room temperature thermistor is more than 66 °F, the fan operates at Very Low.   
					NOTE : When 3 minutes have passed since the compressor started operation, this control is released regardless of the   
					temperature of room temperature thermistor and indoor coil thermistor.   
					MSZ-A24   
					When the compressor is not operating,   
					( ) if the temperature of room temperature thermistor is 59 °F or less, or temperature of indoor coil thermistor is   
					less than 64 °F, the fan stops.   
					( 
					) if the temperature of room temperature thermistor is more than 59 °F, or temperature of indoor coil themistor is   
					more than 64 °F, the fan operates at Very Low.   
					When the compressor is operating,   
					( ) if the temperature of indoor coil themistor is 64 °F or more, the fan operates at set speed.   
					( 
					) if the temperature of indoor coil themistor is less than 64 °F and   
					( ) if heating operation starts after defrosting, the fan stops.   
					( 
					( 
					) if the temperature of room temperature thermistor is 59 °F or less, the fan stops.   
					) if the temperature of room temperature thermistor is more than 59 °F, the fan operates at Very Low.   
					NOTE : When 3 minutes have passed since the compressor started operation, this control is released regardless of the   
					temperature of room temperature thermistor and indoor coil thermistor.   
					(3) Warm air control (MSZ-FD)   
					When the following any condition of (a. ~ c.) and the condition of are satisfied at the same time, warm air control   
					works.   
					a.) Fan speed is used in MANUAL.   
					b.) When cold air prevention has been released.   
					c.) When defrosting has been finished.   
					When the temperature of indoor coil thermistor is less than 104 °F.   
					When warm air control works, the fan speed changes as follows to blow out warm air gradually.   
					Gradation of fan speed in initial   
					<Time condition>   
					<Indoor fan speed>   
					Less than 2 minutes------------ Low   
					2 minutes to 4 minutes -------- Med.   
					More than 4 minutes ----------- High or Super high   
					The upper limit of the fan speed in MANUAL is the set speed.   
					When the temperature of indoor coil thermistor has been 104 °F or more, or when the set speed has been changed, this   
					control is released and the fan speed is the set speed.   
					3. Overload starting   
					When the room temperature thermistor reads 64 °F or more, the compressor runs with its maximum frequency regulated for   
					10 minutes after the start-up.   
					4. Defrosting   
					(1) Starting conditions of defrosting   
					When the following conditions a) ~ c) are satisfied, the defrosting starts.   
					a) The defrost thermistor reads 27 °F or less.   
					b) The cumulative operation time of the compressor has reached any of the set values (40, 45, 55, 65, 75, 85, 95, 105,   
					115, 125, 150 minutes.   
					c) More than 5 minutes have passed since the start-up of the compressor.   
					Set value of compressor operation time (here in after referred to as defrost interval)   
					This is decided by the temperature of defrost thermistor, ambient temperature thermistor, and the previous defrosting   
					time. For example, the first defrost interval is 40 minutes long, and the second is 45 minutes long. The third and sub-   
					sequent intervals are set to be longer, and less frequent, depending on defrosting time.   
					… 
					The third and subsequent defrost intervals follow any of the three patterns 5 or 10 to 20 minutes longer, the same,   
					… 
					or 5 or 10 to 20 minutes shorter compared with the previous defrost interval   
					shortest 40 minutes.   
					with the longest 125 minutes and the   
					9 
				(2) Releasing conditions of defrosting   
					Defrosting is released when any of the following conditions is satisfied:   
					a) The defrost thermistor continues to read 50 °F or more (MUZ-A09/12 MUZ-D) / 41 °F or more (MUZ-A15/17 MUZ-FD) /   
					59 °F or more (MUZ-A24) for 30 seconds.   
					b) Defrosting time has exceeded 10 minutes.   
					c) Any other mode than HEAT mode is set during defrosting.   
					Time chart of defrosting in HEAT mode (reverse type)   
					<Indoor unit>   
					horizontal   
					set position   
					set speed   
					set position   
					set speed   
					Horizontal vane   
					Indoor fan   
					< 
					horizontal (temperature of indoor coil thermistor 102 °F)   
					Very Low (temperature of indoor coil thermistor > 64 °F)   
					OFF   
					30   
					seconds   
					<Outdoor unit>   
					Maximum frequency   
					Compressor normal   
					OFF   
					30   
					OFF   
					30   
					40   
					40   
					seconds seconds   
					seconds seconds   
					5 seconds   
					5 seconds   
					ON   
					ON   
					Outdoor fan   
					OFF   
					ON (HEAT)   
					ON (HEAT)   
					R.V. coil   
					(21S4)   
					OFF (COOL)   
					2-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION (MSZ)   
					Once desired temperature is set, unit operation is switched automatically between COOL and HEAT operation.   
					1. Mode selection   
					(1) Initial mode   
					At first indoor unit operates only indoor fan with outdoor unit OFF for 3 minutes to detect present room temperature.   
					Following the conditions below, operation mode is selected.   
					If the room temperature thermistor reads more than set temperature, COOL mode is selected.   
					If the room temperature thermistor reads set temperature or less, HEAT mode is selected.   
					10   
				(2) Mode change   
					In case of the following conditions, the operation mode is changed.   
					COOL mode changes to HEAT mode when 15 minutes have passed with the room temperature 4 °F below the set   
					temperature.   
					HEAT mode changes to COOL mode when 15 minutes have passed with the room temperature 4 °F above the set   
					temperature.   
					In the other cases than the above conditions, the present operation mode is continued.   
					NOTE1: Mode selection is performed when multi standby (refer to NOTE2) is released and the unit starts operation with   
					ON-timer.   
					NOTE2: If two or more indoor units are operating in multi system, there might be a case that the indoor unit, which is   
					operating in AUTO (   
					of standby.   
					), cannot change over the other operating mode (COOL   
					HEAT) and becomes a state   
					(3) Indoor fan control/ Vane control   
					As the indoor fan speed and the horizontal vane position depend on the selected operation mode, when the operation   
					mode changes over, they change to the exclusive ones.   
					2-5. OUTDOOR FAN MOTOR CONTROL   
					Fan speed is switched according to the compressor frequency.   
					<Relation between compressor frequency and fan speed>   
					Compressor frequency (Hz)   
					Fan speed   
					High   
					Down   
					Up   
					Down   
					Up   
					MUZ-A   
					MUY-A   
					33   
					44   
					Low   
					Min. Compressor frequency Max.   
					MUZ-FD   
					33   
					39   
					44   
					54   
					MUZ-D   
					MUY-D   
					2-6. AUTO VANE OPERATION   
					1. Horizontal vane   
					(1) Cold air prevention in HEAT operation (MUZ)   
					When any of the following conditions occurs in HEAT operation, the vane angle changes to Horizontal position automati-   
					cally to prevent cold air blowing on users.   
					Compressor is not operating.   
					Defrosting is performed.   
					Indoor coil thermistor temperature does not exceed 102 °F within about 3 minutes after compressor starts.   
					NOTE: When 2 or more indoor units are operated with multi outdoor unit, even if any indoor unit turns thermostat off,   
					this control doesn’t work in the indoor unit.   
					(2) ECONO COOL (   
					) operation (ECONOmical operation)   
					When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 3.6 °F higher than that in   
					COOL mode.   
					Also the horizontal vane swings in various cycle according to the temperature of indoor heat exchanger (indoor coil   
					thermistor).   
					SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher than that   
					in COOL mode, the air conditioner can keep comfort. As a result, energy can be saved.   
					ECONO COOL operation is cancelled when ECONO COOL button is pressed once again or VANE CONTROL button is   
					pressed or change to other operation mode.   
					11   
				<SWING operation>   
					In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”.   
					According to the temperature of indoor coil thermistor RT12 at starting of this operation, next downward blow time is   
					decided. Then when the downward blow has been finished, next horizontal blow time is decided.   
					For initial 10 minutes the swing operation is performed in table G~H for quick cooling.   
					Also, after 10 minutes when the difference of set temperature and room temperature is more than 3.6 °F, the swing   
					operation is performed in table D~H for more cooling.   
					The air conditioner repeats the swing operation in various cycle as follows.   
					Temperature of indoor   
					coil thermistor (°F)   
					Downward blow time Horizontal blow time   
					(second)   
					(second)   
					A 
					B 
					C 
					D 
					E 
					F 
					59 or less   
					59 to 63   
					63 to 64   
					64 to 68   
					68 to 70   
					70 to 72   
					72 to 75   
					more than 75   
					2 
					5 
					8 
					11   
					14   
					17   
					20   
					23   
					23   
					20   
					17   
					14   
					11   
					8 
					G 
					H 
					5 
					2 
					2-7. INVERTER SYSTEM CONTROL   
					2-7-1. Inverter main power supply circuit   
					MUZ-A09/12/15/17   
					MUY-A15/17   
					MUZ-FD   
					CURRENT   
					DIODE   
					TRANSFORMER   
					REACTOR   
					MODULE1   
					U 
					U 
					V 
					P 
					NOISE   
					FILTER   
					CIRCUIT   
					RESISTOR   
					RELAY   
					+ 
					+ 
					POWER   
					SUPPLY   
					~ 
					~ 
					SMOOTHING   
					CAPACITOR   
					MS   
					3~   
					V 
					- 
					N 
					W 
					W 
					IPM   
					COMPRESSOR   
					+ 
					~ 
					~ 
					SWITCHING   
					POWER   
					TRANSISTOR   
					DIODE   
					MODULE2   
					- 
					BOOSTER CHOPPER CIRCUIT   
					Function of main parts   
					NAME   
					FUNCTION   
					INTELLIGENT POWER MODULE (IPM)   
					SMOOTHING CAPACITOR   
					CURRENT TRANSFORMER   
					DIODE MODULE 1   
					It supplies three-phase AC power to compressor.   
					It stabilizes the DC voltage and supply it to IPM.   
					It measures the current of the compressor motor.   
					It converts the AC voltage to DC voltage.   
					It absorbs the rush current not to run into the main power supply circuit when   
					the electricity turns ON.   
					RESISTOR   
					RELAY   
					It short-circuits the resistance which restricts rush current during the normal   
					operation after the compressor startup.   
					DIODE MODULE 2   
					BOOSTER   
					It improves power factor.   
					It controls the bus-bar voltage.   
					SWITCHING POWER TRANSISTOR   
					CHOPPER   
					CIRCUIT   
					REACTOR   
					12   
				MUZ-A24   
					MUY-A24   
					MUZ-D   
					MUY-D   
					CURRENT   
					TRANSFORMER   
					REACTOR   
					U 
					U 
					V 
					P 
					N 
					NOISE   
					FILTER   
					CIRCUIT   
					RESISTOR   
					RELAY   
					+ 
					POWER   
					SUPPLY   
					SMOOTHING   
					CAPACITOR   
					MS   
					3~   
					PFC   
					V 
					W 
					W 
					IPM   
					COMPRESSOR   
					Function of main parts   
					NAME   
					FUNCTION   
					INTELLIGENT POWER MODULE (IPM)   
					SMOOTHING CAPACITOR   
					It supplies three-phase AC power to compressor.   
					It stabilizes the DC voltage and supplies it to IPM.   
					It measures the current of the compressor motor.   
					It measures the current of the main power supply circuit.   
					CURRENT TRANSFORMER   
					REACTOR   
					It rectifies AC, controls its voltage and improves the power factor of power   
					supply.   
					POWER FACTOR CORRECTION MODULE (PFC)   
					RESISTOR   
					RELAY   
					It restricts rush current with the resistance.   
					It short-circuits the resistance which restricts rush current during the compres-   
					sor operates.   
					13   
				2-7-2. Outline of main power supply circuit   
					MUZ-A09/12/15/17 MUY-A15/17 MUZ-FD   
					1. At the start of operation   
					Main power supply circuit is formed when RELAY is turned ON at COMPRESSOR startup.   
					To prevent rush current from running into the circuit when power supply is turned ON,   
					RESISTOR is placed in sub circuit.   
					2. At normal operation   
					When AC runs into POWER P.C. board, its external noise is eliminated in NOISE FILTER CIRCUIT.   
					After noise is eliminated from AC, it is rectified to DC by DIODE MODULE 1.   
					DC voltage, to which AC has been rectified by process , is stabilized by SMOOTHING CAPACITOR and supplied to IPM.   
					DC voltage, which has been stabilized in process , is converted to three-phase AC by IPM and supplied to COMPRES-   
					SOR.   
					CURRENT TRANSFORMER, which is placed in the power supply circuit to COMPRESSOR, are used to measure the val-   
					ue of phase current and locate the polar direction of rotor with algorithm. PWM (Pulse width modulation) controls impressed   
					voltage and frequency with those information.   
					3. Purpose of PAM adoption   
					PAM : Pulse Amplitude Modulation   
					PAM has been adopted for the efficiency improvement and the adaptation to IEC harmonic current emission standard   
					Outline of simple partial switching method   
					In conventional inverter models, DIODE MODULE rectifies AC voltage to DC voltage, SMOOTHING CAPACITOR makes its   
					DC waveform smooth, and IPM converts its DC voltage to imitated AC voltage again in order to drive the compressor motor.   
					However, it has been difficult to meet IEC harmonic current emission standard by above circuit because harmonic gets   
					generated in the input current waveform and power factor gets down. The simple partial switching method with PAM, which   
					has been adopted this time, places and utilizes BOOSTER CHOPPER CIRCUIT before rectifying AC voltage in the general   
					passive-method converter circuit. As harmonic gets suppressed and the peak of waveform gets lower by adding BOOSTER   
					CHOPPER CIRCUIT as mentioned above and by synchronizing the timing of switching with the zero-cross point of waveform,   
					the input current waveform can be improved and the requirement of IEC harmonic current emission standard can be satisfied.   
					Since the switching synchronized with the zero cross point, this simple partial switching method has the feature of lower en-   
					ergy loss compared to active filter method. In addition, output and efficiency is enhanced by combining with vector-controlled   
					inverter in order to boost the voltage of power supplied to IPM.   
					Input current waveform without PAM   
					Input current waveform with PAM   
					Due to the time of no electricity;   
					· Power factor gets worse.   
					· Harmonic gets increased.   
					Owing to the increase of energized time;   
					· Power factor gets better.   
					· Harmonic gets suppressed.   
					Input current   
					Input voltage   
					Energized time is short in   
					case L inductance is small.   
					No electricity runs into   
					diode module because the   
					voltage at both sides of smoothing   
					capacitor is higher than input voltage.   
					14   
				4. Intelligent power module   
					IPM consists of the following components   
					· IGBT (x6)   
					: Converts DC waveform to three-phase AC waveform and outputs it.   
					· Drive Circuit   
					· Protection circuit   
					: Drives transistors.   
					: Protects transistors from overcurrent.   
					Since the above components are all integrated in IPM, IPM has a merit to make the control circuit simplify and miniaturize.   
					5. Elimination of electrical noise   
					NOISE FILTER CIRCUIT, which is formed by *CMC COILS capacitors placed on the POWER P.C. board, eliminates electri-   
					cal noise of AC power that is supplied to main power supply circuit. And this circuit prevents the electrical noise generated in   
					the inverter circuit from leaking out.   
					*CMC COILS; Common mode choke coils   
					MUZ-A24 MUY-A24 MUZ-D MUY-D   
					1. At the start of operation   
					Main power supply circuit is formed when RELAY is turned ON at COMPRESSOR startup.   
					To prevent rush current from running into the circuit when power supply is turned ON, RESISTOR are placed in sub circuit.   
					2. At normal operation   
					When AC runs into noise filter P.C. board, its external noise is eliminated in NOISE FILTER CIRCUIT.   
					After noise being eliminated from AC, it is rectified to DC by REACTOR and PFC. If the operating frequency becomes 25   
					Hz or more, DC voltage rises to 370 V.   
					DC voltage, to which has AC been rectified by process , is stabilized by SMOOTHING CAPACITOR and supplied to IPM.   
					The DC (Bus voltage), which has been stabilized in process , is converted to three-phase AC by IPM and supplied to   
					COMPRESSOR.   
					CURRENT TRANSFORMER, which is placed in the power supply circuit to COMPRESSOR, are used to measure the   
					value of phase current and locate the polar direction of rotor with algorithm. PWM (Pulse width modulation) controls im-   
					pressed voltage and frequency with those information.   
					3. Power factor improvement   
					Booster coil reactor and power factor controller rectify AC to DC and control its voltage.   
					In the motor drive system of sine wave control, power factor can be improved by reducing harmonics. PFC and reactor stabi-   
					lize the voltage of DC supplied to inverter circuit and make its waveform smooth.   
					4. Power transistor module   
					IPM consists of the following components.   
					· Power Transistors (x6) : Converts DC waveform to three-phase AC waveform and outputs it.   
					· Drive Circuit   
					: Drives transistors.   
					· Protection circuit   
					: Protects transistors from over current.   
					Since the above components are all integrated in IPM, IPM has a merit that can get the control circuit simplified and miniatur-   
					ized.   
					5. Elimination of electrical noise   
					NOISE FILTER CIRCUIT, which is formed by *CMC COILS and capacitors placed on the noise filter P.C. board, eliminates   
					electrical noise of AC power that is supplied to main power supply circuit. In short, common mode noise is absorbed in this   
					circuit.   
					Moreover, normal mode noise is absorbed in another NOISE FILTER CIRCUIT which is formed by *NMC COILS and capaci-   
					tors.   
					Both NOISE FILTER CIRCUIT exists for preventing the electrical noise generated in the inverter circuit from leaking out.   
					*CMC COILS; Common mode choke coils   
					*NMC COILS; Normal mode choke coils   
					15   
				2-7-3. Sine wave control   
					In these air conditioners, compressor equips brushless DC motor which doesn't have Hall element.   
					In short, the motor is sensorless. However, it's necessary to locate the polar direction of rotor in order to drive brushless DC mo-   
					tor efficiently. The general detection method of the polar direction for such a DC motor is to locate it from the voltage induced by   
					unenergized stator.   
					Therefore, it is necessary to have a certain period of time in which the stator is being unenergized for the rotor position detection   
					when the voltage of supplied power is impressed.   
					So the motor has been driven by square wave control (the conventional motor drive system) which energizes the motor only   
					when the range of electrical angle is within 120° because it is forced to be unenergized within 30° at start & end of one heap in   
					one waveform cycle (180°) when the voltage is impressed.   
					However, torque pulsation occurs at rotation in this method when the current-carrying phases are switched over to other phases   
					in sequence. Therefore, sine wave control system is adopted for these air conditioners because it can make the phase-to-phase   
					current waveform smoother (sine wave) in order to drive the motor more efficiently and smoothly.   
					2-7-4. Characteristics of sine wave control in case of brushless DC motor   
					Although ordinary three-phase induction motor requires energy to excite the magnetic field of rotor, brushless DC motor   
					doesn't need it. So, higher efficiency and torque are provided.   
					● 
					This control provides the most efficient waveform corresponding to the rotation times of compressor motor.   
					The rotation can be set to higher compared to the conventional motor drive system. So, the time in which air conditioner   
					can be operated with energy saved is longer than conventional models. This can save annual electric consumption.   
					● 
					● 
					Compared to square wave control, the torque pulsation is reduced at rotation so that the motor operates more quietly.   
					Since response and efficiency of motor are enhanced in sine wave control, finer adjustment can be provided.   
					● 
					● 
					DC Motor   
					Permanent magnet is embedded   
					Necessary   
					AC Motor   
					Excited by magnetic field of stator   
					Unnecessary   
					Rotor   
					Rotor Position Signal   
					In brushless DC motor, permanent magnet is embedded in the rotor. Therefore, it doesn't require energy to excite the rotor   
					like AC motor does. However, it's necessary to control the frequency of three-phase AC current supplied to the stator accord-   
					ing to the polar direction of magnet embedded in the rotor so as to drive the motor efficiently. Controlling 3 phase AC current   
					frequency also means controlling the timing to switch the polarity of stator. Therefore, the polar direction of rotor needs to be   
					detected.   
					2-7-5. Control Method of Rotation Times   
					Sine wave control makes the current transformers conduct real time detection of the value of the current running into the mo-   
					tor, locates the rotor position from the detected value, and decides if voltage should be impressed and if frequency should be   
					changed.   
					Compared to the conventional control and rotor position detection method, sine wave control can provide finer adjustment of the   
					voltage of supplied power. The value of the current running into the motor is determined by each motor characteristic.   
					16   
				2-8. OPERATIONAL FREQUENCY CONTROL OF OUTDOOR UNIT   
					1. Outline   
					The operational frequency is as following:   
					First, the target operational frequency is set based on the difference between the room temperature and the set tem-   
					perature.   
					Second, the target operational frequency is regulated by discharge temperature protection, high pressure protection,   
					electric current protection and overload protection and also by the maximum/minimum frequency.   
					2. Maximum/minimum frequency in each operation mode.   
					Unit: Hz   
					COOL   
					HEAT (MUZ)   
					DRY   
					Applied model   
					Minimum Maximum Minimum Maximum Minimum Maximum   
					frequency frequency frequency frequency frequency frequency   
					MUZ-A09   
					MUZ-A12   
					32   
					32   
					70   
					73   
					32   
					32   
					76   
					71   
					32   
					32   
					57   
					57   
					MUZ-A15   
					MUY-A15   
					MUZ-A17   
					MUY-A17   
					MUZ-A24   
					MUY-A24   
					10   
					10   
					15   
					82   
					87   
					15   
					15   
					15   
					93   
					93   
					10   
					10   
					15   
					68   
					68   
					110   
					108   
					102   
					MUZ-FD09   
					MUZ-FD12   
					MUZ-D30   
					MUY-D36   
					MUZ-D36   
					MUY-D36   
					10   
					10   
					20   
					20   
					20   
					20   
					52   
					62   
					84   
					79   
					91   
					92   
					10   
					10   
					20   
					— 
					20   
					— 
					100   
					100   
					87   
					10   
					10   
					20   
					20   
					20   
					20   
					41   
					41   
					83   
					79   
					83   
					79   
					— 
					94   
					— 
					The operation frequency in COOL mode is restricted by the upper limit frequency after 1 hour or 0.5 ~ 1 hour as   
					shown below for dew prevention.   
					It is rated frequency or less.   
					Maximum   
					frequency   
					Upper limit   
					1 hour   
					frequency   
					or   
					Rated frequency or less   
					Time   
					0.5~1 hour   
					17   
				2-9. EXPANSION VALVE CONTROL (LEV CONTROL)   
					(1) Outline of LEV control   
					The LEV basic control is comprised of setting LEV opening degree to the standard opening °F set for each operational   
					frequency of the compressor. However, when any change in indoor/outdoor temperatures or other factors cause air con-   
					ditioning load fluctuation, the LEV control also works to correct LEV opening degree based on discharge temperature   
					(Shell temperature) of the compressor, developing the unit’s performance.   
					Minimum   
					: 33 pulse (MUZ-A09/12/15/17 MUY-A15/17)   
					59 pulse (MUZ-A24 MUY-A24)   
					54 pulse (MUZ-FD)   
					Control range   
					58 pulse (MUZ-D MUY-D)   
					: 500 pulse   
					Maximum   
					Open : 40 pulse/second   
					Close : 90 pulse/second.   
					Actuating speed   
					Opening degree adjustment   
					LEV opening degree is always adjusted in opening direction.   
					(When reducing the opening degree, LEV is once over-closed,   
					and then adjusted to the proper degree by opening.   
					Unit OFF   
					LEV remains at maximum opening degree (reaches maximum   
					opening degree approximate in 15 minutes after compressor   
					stops)   
					Remote controller ON   
					LEV is positioned. (first full-closed at zero pulse and then posi-   
					tioned.)   
					COOL · DRY MODE   
					During 1 to 5 minutes after compressor starts   
					LEV is fixed to standard opening degree according to opera-   
					tional frequency of compressor.   
					HEAT MODE   
					During 1 to 15 minutes after compressor starts   
					More than 5 (COOL, DRY), 15 (HEAT (MUZ)) minutes LEV opening degree is corrected to get target discharge tem-   
					have passed since compressor start-up   
					perature of compressor.   
					(For lower discharge temperature than target temperature,   
					LEV is corrected in closing direction.)   
					(For higher discharge temperature than target temperature,   
					LEV is corrected in opening direction.)   
					It may take more than 30 minutes to reach target tempera-   
					ture, depending on operating conditions.   
					Thermostat OFF   
					Thermostat ON   
					LEV is adjusted to exclusive opening degree for thermostat   
					OFF.   
					LEV is controlled in the same way as that after the compres-   
					sor has started up.   
					Defrosting in HEAT mode   
					LEV is adjusted to open 500 pulse.   
					18   
				(2) Time chart   
					Air conditioner OFF   
					(thermostat off)   
					Air conditioner ON   
					Positioning   
					Opening degree is   
					corrected according   
					to discharge   
					Standard   
					opening   
					degree   
					Commanded   
					to open   
					temperature.   
					about 5 minutes <COOL, DRY>   
					about 15 minutes <HEAT>   
					Time   
					ON   
					OFF Time   
					(3) Control data   
					06   
					05   
					F 
					E 
					D 
					04   
					03   
					02   
					01   
					C 
					B 
					A(target discharge temperature)   
					(Hz)   
					30   
					50   
					70   
					90   
					110   
					130   
					Operational frequency of the compressor   
					(a) Reference value of target discharge temperature   
					(COOL / HEAT (MUZ) F)   
					Applied model   
					A 
					B 
					C 
					D 
					E 
					F 
					COOL   
					HEAT   
					COOL   
					HEAT   
					COOL   
					HEAT   
					COOL   
					HEAT   
					COOL   
					HEAT   
					122   
					113   
					129   
					120   
					140   
					140   
					120   
					109   
					126   
					131   
					127   
					126   
					136   
					136   
					140   
					145   
					131   
					124   
					135   
					140   
					140   
					138   
					147   
					151   
					140   
					149   
					142   
					138   
					149   
					149   
					151   
					154   
					158   
					165   
					145   
					153   
					153   
					156   
					167   
					154   
					158   
					169   
					158   
					180   
					147   
					158   
					162   
					167   
					183   
					162   
					158   
					169   
					158   
					185   
					153   
					158   
					169   
					176   
					187   
					167   
					MUZ-A09/12   
					MUZ-A15/17   
					MUY-A15/17   
					MUZ-A24   
					MUY-A24   
					MUZ-FD   
					MUZ-D   
					MUY-D   
					In COOL operation, the two indoor coil thermistors (one main and one sub) sense temperature ununiformity (super   
					heat) at the heat exchanger, and when temperature difference have developed, the indoor coil thermistors adjust   
					LEV opening degree to get approximate 10 degrees lower temperature than the target temperature in the table   
					above, thus diminishing super heat.   
					19   
				(b) Reference value of LEV standard opening degree (pulse)   
					Applied model   
					A 
					B 
					C 
					D 
					E 
					F 
					COOL   
					HEAT   
					COOL   
					HEAT   
					COOL   
					HEAT   
					COOL   
					HEAT   
					COOL   
					HEAT   
					130   
					100   
					290   
					130   
					150   
					130   
					180   
					130   
					150   
					100   
					190   
					130   
					300   
					150   
					166   
					150   
					240   
					180   
					170   
					120   
					240   
					170   
					350   
					220   
					186   
					170   
					300   
					240   
					210   
					140   
					260   
					210   
					350   
					250   
					206   
					196   
					320   
					270   
					250   
					190   
					260   
					230   
					370   
					280   
					230   
					210   
					320   
					300   
					280   
					240   
					260   
					230   
					370   
					300   
					260   
					226   
					320   
					300   
					300   
					280   
					MUZ-A09/12   
					MUZ-A15/17   
					MUY-A15/17   
					MUZ-A24   
					MUY-A24   
					MUZ-FD   
					MUZ-D   
					MUY-D   
					20   
				3 
					MXZ MICROPROCESSOR CONTROL   
					MXZ-A•NA   
					3-1. INVERTER SYSTEM CONTROL   
					3-1-1. Inverter main power supply circuit   
					CURRENT   
					TRANSFORMER   
					REACTOR   
					U 
					U 
					V 
					P 
					N 
					NOISE   
					FILTER   
					CIRCUIT   
					RESISTOR   
					RELAY   
					+ 
					POWER   
					SUPPLY   
					SMOOTHING   
					CAPACITOR   
					MS   
					3~   
					PFC   
					V 
					W 
					W 
					IPM   
					COMPRESSOR   
					Function of main parts   
					NAME   
					FUNCTION   
					INTELLIGENT POWER MODULE (IPM)   
					SMOOTHING CAPACITOR   
					It supplies three-phase AC power to compressor.   
					It stabilizes the DC voltage and supplies it to IPM.   
					It measures the current of the compressor motor.   
					CURRENT TRANSFORMER   
					It measures the current of the main power supply circuit.   
					REACTOR   
					It rectifies AC, controls its voltage and improves the power factor of power   
					supply.   
					POWER FACTOR CORRECTION MODULE (PFC)   
					RESISTOR   
					RELAY   
					It restricts rush current with the resistance.   
					It short-circuits the resistance which restricts rush current during the compres-   
					sor operates.   
					3-1-2. Outline of main power supply circuit   
					1. At the start of operation   
					Main power supply circuit is formed when RELAY is turned ON at COMPRESSOR startup.   
					To prevent rush current from running into the circuit when power supply is turned ON, RESISTOR are placed in sub circuit.   
					2. At normal operation   
					When AC runs into noise filter P.C. board, its external noise is eliminated in NOISE FILTER CIRCUIT.   
					After noise being eliminated from AC, it is rectified to DC by REACTOR and PFC. If the operating frequency becomes 25   
					Hz or more, DC voltage rises to 370 V.   
					DC voltage, to which has AC been rectified by process , is stabilized by SMOOTHING CAPACITOR and supplied to IPM.   
					The DC (Bus voltage), which has been stabilized in process , is converted to three-phase AC by IPM and supplied to   
					COMPRESSOR.   
					CURRENT TRANSFORMER, which is placed in the power supply circuit to COMPRESSOR, are used to measure the val-   
					ue of phase current and locate the polar direction of rotor with algorithm. PWM (Pulse width modulation) controls impressed   
					voltage and frequency with those information.   
					21   
				3. Power factor improvement   
					Booster coil reactor and PFC rectify AC to DC and control its voltage.   
					In the motor drive system of sine wave control, power factor can be improved by reducing harmonics. PFC and reactor stabi-   
					lize the voltage of DC supplied to inverter circuit and make its waveform smooth.   
					4. Power transistor module   
					IPM consists of the following components.   
					· Power Transistors (x6) : Converts DC waveform to three-phase AC waveform and outputs it.   
					· Drive Circuit   
					: Drives transistors.   
					· Protection circuit   
					: Protects transistors from over current.   
					Since the above components are all integrated in IPM, IPM has a merit that can get the control circuit simplified and miniatur-   
					ized.   
					5. Elimination of electrical noise   
					NOISE FILTER CIRCUIT, which is formed by *CMC COILS and capacitors placed on the noise filter P.C. board, eliminates   
					electrical noise of AC power that is supplied to main power supply circuit. In short, common mode noise is absorbed in this   
					circuit.   
					Moreover, normal mode noise is absorbed in another NOISE FILTER CIRCUIT which is formed by *NMC COILS and capaci-   
					tors.   
					Both NOISE FILTER CIRCUIT exists for preventing the electrical noise generated in the inverter circuit from leaking out.   
					*CMC COILS; Common mode choke coils   
					*NMC COILS; Normal mode choke coils   
					3-1-3. Sine wave control   
					In these air conditioners, compressor equips brushless DC motor which doesn't have Hall element.   
					In short, the motor is sensorless. However, it's necessary to locate the polar direction of rotor in order to drive brushless DC mo-   
					tor efficiently. The general detection method of the polar direction for such a DC motor is to locate it from the voltage induced by   
					unenergized stator.   
					Therefore, it is necessary to have a certain period of time in which the stator is being unenergized for the rotor position detection   
					when the voltage of supplied power is impressed.   
					So the motor has been driven by square wave control (the conventional motor drive system) which energizes the motor only   
					when the range of electrical angle is within 120° because it is forced to be unenergized within 30° at start & end of one heap in   
					one waveform cycle (180°) when the voltage is impressed.   
					However, torque pulsation occurs at rotation in this method when the current-carrying phases are switched over to other phases   
					in sequence. Therefore, sine wave control system is adopted for these air conditioners because it can make the phase-to-phase   
					current waveform smoother (sine wave) in order to drive the motor more efficiently and smoothly.   
					3-1-4. Characteristics of sine wave control in case of brushless DC motor   
					Although ordinary three-phase induction motor requires energy to excite the magnetic field of rotor, brushless DC motor   
					doesn't need it. So, higher efficiency and torque are provided.   
					● 
					This control provides the most efficient waveform corresponding to the rotation times of compressor motor.   
					The rotation can be set to higher compared to the conventional motor drive system. So, the time in which air conditioner can   
					be operated with energy saved is longer than conventional models. This can save annual electric consumption.   
					● 
					● 
					Compared to square wave control, the torque pulsation is reduced at rotation so that the motor operates more quietly.   
					Since response and efficiency are enhanced in sine wave control, finer adjustment can be provided.   
					● 
					● 
					DC Motor   
					Permanent magnet is embedded   
					Necessary   
					AC Motor   
					Excited by magnetic field of stator   
					Unnecessary   
					Rotor   
					Rotor Position Signal   
					In brushless DC motor, permanent magnet is embedded in the rotor. Therefore, it doesn't require energy to excite the rotor   
					like AC motor does. However, it's necessary to control the frequency of three-phase AC current supplied to the stator accord-   
					ing to the polar direction of magnet embedded in the rotor so as to drive the motor efficiently. Controlling 3 phase AC current   
					frequency also means controlling the timing to switch the polarity of stator. Therefore, the polar direction of rotor needs to be   
					detected.   
					3-1-5. Control Method of Rotation Times   
					Sine wave control makes the current transformers conduct real time detection of the value of the current running into the mo-   
					tor, locates the rotor position from the detected value and decides if voltage should be impressed and if frequency should be   
					changed.   
					Compared to the conventional control and rotor position detection method, sine wave control can provide finer adjustment of the   
					voltage of supplied power. The value of the current running into the motor is determined by each motor characteristic.   
					22   
				3-2. EXPANSION VALVE CONTROL (LEV CONTROL)   
					Linear expansion valve (LEV) is controlled by “Thermostat ON” commands given from each unit.   
					Indoor unit status   
					LEV opening   
					Stop of all indoor unit   
					Opening before stop → 500 pulse in 15 minutes   
					When outdoor unit is operating, COOL : 5 pulse (full closed)   
					some indoor units stop and some HEAT :(MXZ-2A / 3A30NA) : 140 pulse (slightly opened)   
					1 
					:(MXZ-3A30NA-   
					/ 4A ) : 100 → 59 pulse   
					operate.   
					When the outdoor unit operates (When the other indoor unit operates) : 5 pulse.   
					When outdoor unit stops. (When the other indoor unit stops or thermo off) :   
					Maintain LEV opening before stop → 500 pulse in 15 minutes   
					Thermostat OFF in COOL or DRY   
					mode   
					• LEV opening for each indoor unit is determined by adding adjustment in accordance   
					with the number of operating unit and the capacity class to standard opening, based   
					on the operation frequency:   
					Ex.) Opening 130 pulse in standard opening 1 → Minimum 80 pulse, Maximum 205   
					pulse. (Capacity code 4 at 1 unit operation) (Capacity code 1 at 3 units operation)   
					Thermostat ON in COOL or DRY • After starting operation, adjustment in accordance with intake super heat, discharge   
					mode   
					temperature is included in standard opening. 1   
					NOTE: LEV opening in each frequency at DRY operation and COOL operation is the   
					same. However, velocity and compressor operation frequency controls are differ-   
					ent. See 3-3. OPERATIONAL FREQUENCY RANGE   
					(As far as the indoor unit velocity control goes, refer to DRY operation in MICRO-   
					PROCESSOR CONTROL in indoor unit.)   
					• When the outdoor unit operates. (When the other indoor unit operates) : 140 pulse.   
					Thermostat OFF in HEAT mode • When the outdoor unit stops. (When the other indoor unit stops or thermo off) : Main-   
					tain LEV opening before stop → 500 pulse in 15 minutes. “   
					• LEV opening for each indoor unit is determined by adding adjustment in accordance   
					with the number of operating unit and the capacity class to standard opening, based   
					on the operation frequency:   
					Ex.) Opening 120 pulse in standard opening 1 → Minimum 70 pulse, Maximum 165   
					pulse. (Capacity code 4 at 1 unit operation) (Capacity code 1 at 3 units operation)   
					• After starting operation, opening becomes the one that adjustment in accordance with   
					discharge temperature was added to basic opening. 1 “   
					Thermostat ON in HEAT mode   
					1 LEV opening when the outdoor unit is operating: Upper limit 500 pulse, Lower limit 53pulse (MXZ-2A / 3A30NA), 59 pulse   
					1 
					(MXZ-3A30NA-   
					/ 4A).   
					23   
				MXZ-2A20NA/3A30NA   
					The table below shows the role of Exclusive LEV and Receiver LEV in each operation mode.   
					Discharge   
					Capacity Distribution Temperature   
					Protection   
					Evaporation   
					Temperature   
					Protection   
					Circulation Amount   
					Control   
					High Pressure   
					Protection   
					Exclusive LEV   
					Receiver LEV   
					Exclusive LEV   
					Receiver LEV   
					○ 
					× 
					× 
					○ 
					○ 
					× 
					○ 
					× 
					○ 
					○ 
					○ 
					○ 
					○ 
					○ 
					○ 
					○ 
					○ 
					○ 
					— 
					— 
					COOL   
					HEAT   
					Outdoor   
					heat   
					Indoor heat Exclusive   
					exchanger LEV   
					exchanger   
					Receiver   
					Receiver   
					LEV   
					(MXZ-3A30NA)   
					In COOL mode, the two indoor coil thermistors (one main and one sub) sense temperature ununiformity (super heat) at the   
					heat exchanger, and when temperature difference have developed, the indoor coil thermistors adjust LEV opening to dimin-   
					ish the super heat. This action is called Evaporation Temperature Protection.   
					The opening pulse of the Receiver LEV is fixed to the standard No.3 in cooling operation, and so is that of each Exclusive   
					LEV in heating operation.   
					However the opening pulse will be changed to the standard No.4 or No.5 when the discharge temperature protection or high-   
					pressure protection is working.   
					In addition to that, it will also be changed to standard No.2 or No.1 when the opening pulse of the each Exclusive LEV   
					becomes 100 pulse or less in cooling operation or so does that of Receiver LEV in heating operation.   
					<MXZ-2A20NA>   
					Number of   
					operating   
					indoor units   
					LEV opening (pulse)   
					COOL   
					HEAT   
					Standard No.   
					1 unit   
					200   
					300   
					400   
					450   
					500   
					2 units   
					1 unit   
					120   
					140   
					160   
					220   
					280   
					2 units   
					120   
					140   
					160   
					220   
					1 
					2 
					3 
					4 
					5 
					150   
					320   
					360   
					410   
					500   
					280   
					<MXZ-3A30NA>   
					Number of   
					operating   
					indoor units   
					LEV opening (pulse)   
					COOL   
					HEAT   
					1 unit   
					2 units   
					250   
					320   
					360   
					410   
					3 units   
					1 unit   
					2 units   
					250   
					300   
					380   
					400   
					3 units   
					Standard No.   
					1 
					2 
					3 
					4 
					5 
					150   
					250   
					350   
					400   
					450   
					250   
					320   
					370   
					420   
					470   
					250   
					300   
					450   
					460   
					470   
					250   
					300   
					380   
					390   
					440   
					460   
					450   
					24   
				Determination of LEV standard opening in each indoor unit   
					• The standard opening is on the straight line, which connects an each standard point in the section where divided into   
					seven according to the operation frequency of compressor as shown in the figure below.   
					(LEV opening is controlled in proportion to the operation frequency.)   
					NOTE: Opening is adjusted at the standard opening according to the indoor unit conditions.   
					However, inclination of standard opening in each point of opening does not change with the original curve.   
					• Add opening provided in Difference in capacity in the table below to the standard opening from 1 to 8, when capacity   
					of the indoor unit is excluding code 1.   
					• Add opening provided in Difference in operation number in the table below to determined LEV opening for each   
					indoor unit, when 2 or 3 indoor units are operated at the same time.   
					NOTE: Even when the adjusted standard opening exceeds the driving range from 59 to 500 pulse, actual driving out-   
					put opening is in a range from 59 to 500 pulse.   
					4Hz   
					10   
					09   
					08   
					07   
					06   
					05   
					04   
					03   
					02   
					01   
					23 38 54 69 84 100 115 131 146 MXZ-2A   
					14 23 32 41 50 59 68 77 86 MXZ-3A/4A   
					Compressor operating frequency (Hz)   
					MXZ-2A20NA   
					Standard opening (pulse)   
					LEV Opening (code)   
					COOL   
					1 
					2 
					3 
					4 
					5 
					6 
					7 
					8 
					9 
					10   
					120 130 136 146 156 160 170 180 190 200   
					100 110 120 130 146 160 170 180 190 200   
					HEAT   
					Difference in capacity   
					Difference in operation number   
					Code3,4 Code5,6 Code7,8 Code9,10 Code11,12 Code13,14 Code15or above   
					2 
					-20   
					0 
					COOL   
					HEAT   
					3 
					3 
					6 
					6 
					9 
					9 
					12   
					52   
					15   
					55   
					25   
					65   
					35   
					75   
					MXZ-3A30NA   
					Standard opening (pulse)   
					LEV Opening (code)   
					COOL   
					1 
					2 
					3 
					4 
					5 
					6 
					7 
					8 
					9 
					10   
					126 130 134 138 140 142 182 228 296 310   
					140 146 150 170 180 200 224 244 272 280   
					HEAT   
					Difference in capacity   
					Difference in operation number   
					Code3,4 Code5,6 Code7,8 Code9,10 Code11,12 Code13,14 Code15or above   
					2 
					-20   
					0 
					3 
					-30   
					0 
					COOL   
					HEAT   
					3 
					3 
					6 
					6 
					9 
					9 
					12   
					52   
					15   
					55   
					25   
					65   
					35   
					75   
					25   
				1 
					MXZ-2A20NA-   
					Exclusive LEV   
					Standard opening (pulse)   
					LEV Opening (code)   
					COOL   
					1 
					2 
					3 
					4 
					5 
					6 
					7 
					8 
					9 
					10   
					120 130 136 146 156 160 170 180 190 200   
					248 248 258 266 274 280 286 292 300 306   
					HEAT   
					Difference in capacity   
					Difference in operation number   
					Code3,4 Code5,6 Code7,8 Code9,10 Code11,12 Code13,14 Code15or above   
					2 
					COOL   
					HEAT   
					3 
					3 
					6 
					6 
					9 
					9 
					12   
					52   
					15   
					55   
					25   
					65   
					35   
					75   
					-20   
					30   
					Receiver LEV   
					Standard opening (pulse)   
					LEV Opening (code)   
					COOL   
					1 
					2 
					3 
					4 
					5 
					6 
					7 
					8 
					9 
					10   
					140 150 160 170 180 190 200 200 200 200   
					80 84 90 110 120 130 140 150 160 170   
					HEAT   
					Difference in operation number   
					Operation number   
					2 
					COOL   
					HEAT   
					-20   
					30   
					1 
					MXZ-3A30NA-   
					MXZ-4A36NA   
					Exclusive LEV   
					Standard opening (pulse)   
					LEV Opening (code)   
					COOL   
					1 
					2 
					3 
					4 
					5 
					6 
					7 
					8 
					9 
					10   
					126 130 134 138 150 160 170 180 190 200   
					248 248 258 266 274 280 286 292 300 306   
					HEAT   
					Difference in capacity   
					Difference in operation number   
					Code3,4 Code5,6 Code7,8 Code9,10 Code11,12 Code13,14 Code15or above   
					2 
					-20   
					-4   
					3 
					-30   
					-8   
					4(MXZ-4A)   
					-30   
					-12   
					COOL   
					HEAT   
					3 
					3 
					6 
					6 
					9 
					9 
					12   
					52   
					15   
					55   
					25   
					65   
					35   
					75   
					Receiver LEV   
					Standard opening (pulse)   
					LEV Opening (code)   
					COOL   
					1 
					2 
					3 
					4 
					5 
					6 
					7 
					8 
					9 
					10   
					270 280 290 300 310 320 330 340 350 360   
					140 152 160 170 180 200 224 244 274 280   
					HEAT   
					Difference in operation number   
					Operation number   
					2 
					28   
					-45   
					3 
					56   
					-60   
					4(MXZ-4A)   
					84   
					COOL   
					HEAT   
					-60   
					Capacity code   
					Indoor unit   
					4 
					7 
					9 
					10 12   
					09 12 15 17 24   
					26   
				<Correction>   
					COOL   
					DRY   
					HEAT   
					Discharge temperature   
					2 
					2 
					● 
					● 
					● 
					Each correction   
					• (Each gas pipe temperature thermistor - Minimum gas pipe temperature thermistor)   
					1 
					— 
					● 
					● 
					• (Main indoor coil thermistor - Sub indoor coil thermistor)   
					1 Perform this, when number of operation units is 2 units or more.   
					1 
					1 
					MXZ-2A20NA-   
					MXZ-3A30NA-   
					and MXZ-4A36NA are excluded.   
					, 
					2 Correct the LEV opening by discharge temperature.   
					(1) LEV opening correction by discharge temperature   
					The target discharge temperature is determined according to frequency zone and number of operation unit of the com-   
					pressor.   
					MXZ-2A20NA   
					Target discharge temperature (°F)   
					Number of operating unit   
					Operation frequency   
					of compressor (Hz)   
					COOL   
					COOL   
					COOL   
					HEAT   
					HEAT   
					HEAT   
					1 unit   
					95   
					104   
					120.2   
					136.4   
					149   
					2 units   
					136.4   
					140   
					1 unit   
					122   
					132.8   
					140   
					2 units   
					122   
					122   
					132.8   
					140   
					140   
					Minimum ~ 23   
					24 ~ 38   
					39 ~ 54   
					55 ~ 69   
					70 ~ 85   
					149   
					154.4   
					158   
					140   
					140   
					86 ~ Maximum   
					158   
					158   
					140   
					140   
					MXZ-2A20NA-   
					1 
					Target discharge temperature (°F)   
					Number of operating unit   
					Operation frequency   
					of compressor (Hz)   
					1 unit   
					95   
					104   
					120.2   
					136.4   
					149   
					2 units   
					136.4   
					140   
					1 unit   
					122   
					132.8   
					140   
					2 units   
					122   
					122   
					132.8   
					140   
					140   
					Minimum ~ 23   
					24 ~ 38   
					39 ~ 54   
					55 ~ 69   
					70 ~ 85   
					149   
					154.4   
					158   
					158   
					145.4   
					150.8   
					152.6   
					86 ~ Maximum   
					158   
					140   
					MXZ-3A30NA   
					Target discharge temperature (°F)   
					Number of operating unit   
					Operation frequency   
					of compressor (Hz)   
					1 unit   
					95   
					104   
					120.2   
					136.4   
					149   
					154.4   
					158   
					2 units   
					131   
					131   
					136.4   
					140   
					149   
					154.4   
					158   
					163.4   
					167   
					3 units   
					134.6   
					134.6   
					145.4   
					149   
					158   
					163.4   
					167   
					1 unit   
					125.6   
					136.4   
					149   
					154.4   
					154.4   
					154.4   
					154.4   
					154.4   
					154.4   
					172.4   
					2 unit   
					143.6   
					150.8   
					165.2   
					172.4   
					172.4   
					172.4   
					172.4   
					172.4   
					172.4   
					172.4   
					3 units   
					122   
					131   
					Minimum ~ 14   
					15 ~ 23   
					24 ~ 32   
					33 ~ 41   
					42 ~ 50   
					51 ~ 59   
					60 ~ 68   
					69 ~ 77   
					78 ~ 86   
					140   
					152.6   
					161.6   
					168.8   
					168.8   
					168.8   
					168.8   
					168.8   
					167   
					167   
					167   
					176   
					179.6   
					179.6   
					87 ~ Maximum   
					176   
					27   
				MXZ-3A30NA-   
					MXZ-4A36NA   
					1 
					Target discharge temperature (°F)   
					COOL   
					HEAT   
					Operation frequency   
					of compressor (Hz)   
					Number of operating unit   
					4 units   
					4 units   
					(MXZ-4A36)   
					1 unit   
					2 units   
					3 units   
					1 unit   
					2 unit   
					3 units   
					(MXZ-4A36)   
					140   
					Minimum ~ 14   
					15 ~ 23   
					95   
					131   
					131   
					136.4   
					140   
					149   
					154.4   
					158   
					163.4   
					167   
					176   
					134.6   
					134.6   
					145.4   
					149   
					158   
					163.4   
					167   
					176   
					179.6   
					179.6   
					125.6   
					136.4   
					149   
					143.6   
					150.8   
					165.2   
					172.4   
					172.4   
					172.4   
					172.4   
					172.4   
					172.4   
					172.4   
					122   
					131   
					140   
					152.6   
					161.6   
					168.8   
					168.8   
					168.8   
					168.8   
					168.8   
					122   
					122   
					122   
					122   
					131   
					140   
					140   
					140   
					140   
					140   
					107.6   
					120.2   
					136.4   
					149   
					154.4   
					158   
					167   
					167   
					167   
					140   
					140   
					24 ~ 32   
					33 ~ 41   
					42 ~ 50   
					51 ~ 59   
					60 ~ 68   
					69 ~ 77   
					78 ~ 86   
					143.6   
					149   
					158   
					154.4   
					154.4   
					154.4   
					154.4   
					154.4   
					154.4   
					172.4   
					158   
					161.6   
					161.6   
					161.6   
					87 ~ Maximum   
					Correct the LEV opening according to the difference between target discharge temperature and discharge temperature.   
					MXZ-2A   
					LEV opening correction (pulse)   
					Discharge temperature (°F)   
					More than Target discharge temperature+18   
					Target discharge temperature + 18 to Target discharge temperature + 9   
					Target discharge temperature + 9 to Target discharge temperature + 3.6   
					Target discharge temperature + 3.6 to Target discharge temperature - 3.6   
					Target discharge temperature - 3.6 to Target discharge temperature - 9   
					Target discharge temperature - 9 to Target discharge temperature - 18   
					Target discharge temperature - 18 or less   
					COOL   
					HEAT   
					5 
					4 
					8 
					3 
					2 
					1 
					0 
					0 
					-1   
					-3   
					-4   
					-1   
					-2   
					-3   
					MXZ-3A MXZ-4A   
					LEV opening correction (pulse)   
					Discharge temperature (°F)   
					COOL   
					HEAT   
					More than Target discharge temperature + 21.6   
					4 
					2 
					1 
					6 
					2 
					1 
					Target discharge temperature + 21.6 to Target discharge temperature + 9   
					Target discharge temperature + 9 to Target discharge temperature + 5.4   
					Target discharge temperature + 5.4 to Target discharge temperature - 5.4   
					Target discharge temperature - 5.4 to Target discharge temperature - 9   
					Target discharge temperature - 9 to Target discharge temperature - 21.6   
					Target discharge temperature - 21.6 or less   
					0 
					0 
					-1   
					-3   
					-8   
					-1   
					-2   
					-8   
					(2) Separate correction (COOL,DRY)   
					(Correction by the separate super heat)   
					a) Correct the LEV separately by temperature difference between each gas pipe temperature and the minimum gas pipe   
					temperature of all.   
					Calculate each super heat of the unit from the expression below;   
					(Super heat) = (Each gas pipe temperature) - (Minimum gas pipe temperature)   
					Separate correction is performed according to each super heat in the table below.   
					MXZ-2A20NA   
					MXZ-3A30NA   
					LEV opening   
					correction (pulse)   
					LEV opening   
					correction (pulse)   
					Superheat   
					Superheat   
					more than 16.2   
					10.8 to 16.2   
					5.4 to 10.8   
					3 
					2 
					1 
					0 
					more than 16.2   
					10.8 to 16.2   
					5.4 to 10.8   
					12   
					8 
					4 
					5.4 or less   
					5.4 or less   
					0 
					28   
				b) Correct the LEV separately by temperature difference “ ∆RT” between main/sub indoor coil thermistor.   
					LEV opening   
					∆RT   
					correction (pulse)   
					10.8 ∆RT   
					7.2 ∆RT < 10.8   
					∆RT < 7.2   
					2 
					1 
					1 
					In addition, decrease the target discharge temperature corresponding ∆RT.   
					Temperature to be   
					decreased (°F)   
					∆ RT   
					10.8 ∆RT   
					7.2 ∆RT< 10.8   
					∆RT < 7.2   
					18   
					9 
					9 
					3-3. OPERATIONAL FREQUENCY RANGE   
					MXZ-2A20NA   
					COOL (Hz)   
					HEAT (Hz)   
					Max.   
					92   
					Number of operating   
					unit   
					Capacity code   
					DRY (Hz)   
					Min.   
					20   
					20   
					20   
					20   
					30   
					30   
					30   
					20   
					Max.   
					65   
					85   
					100   
					100   
					105   
					105   
					105   
					105   
					Min.   
					48   
					48   
					48   
					48   
					58   
					58   
					58   
					58   
					Defrost   
					92   
					92   
					100   
					100   
					100   
					100   
					100   
					100   
					4 
					7 
					9,10   
					12   
					8 ~ 10   
					11 ~ 13   
					14 ~ 16   
					17 ~   
					25   
					30   
					75   
					75   
					52   
					52   
					52   
					100   
					92   
					100   
					100   
					112   
					112   
					112   
					112   
					1 
					2 
					1 
					MXZ-2A20NA-   
					COOL (Hz)   
					HEAT (Hz)   
					Max.   
					92   
					Number of operating   
					unit   
					Capacity code   
					DRY (Hz)   
					Min.   
					20   
					20   
					20   
					20   
					30   
					30   
					30   
					30   
					Max.   
					65   
					85   
					93   
					93   
					93   
					93   
					93   
					93   
					Min.   
					48   
					48   
					48   
					48   
					58   
					58   
					58   
					58   
					Defrost   
					92   
					92   
					92   
					92   
					101   
					101   
					101   
					101   
					4 
					7 
					9,10   
					12   
					8 ~ 10   
					11 ~ 13   
					14 ~ 16   
					17 ~   
					35   
					34   
					75   
					75   
					52   
					52   
					52   
					93   
					92   
					92   
					92   
					110   
					110   
					110   
					110   
					1 
					2 
					MXZ-3A30NA   
					COOL (Hz)   
					HEAT (Hz)   
					Number of operating   
					unit   
					Capacity code   
					DRY (Hz)   
					Min.   
					15   
					15   
					15   
					15   
					24   
					24   
					24   
					24   
					52   
					Max.   
					58   
					58   
					62   
					68   
					80   
					80   
					80   
					80   
					90   
					Min.   
					22   
					22   
					22   
					22   
					35   
					35   
					35   
					35   
					39   
					Max.   
					48   
					48   
					62   
					90   
					70   
					90   
					94   
					94   
					94   
					Defrost   
					48   
					48   
					58   
					58   
					58   
					58   
					58   
					58   
					4 
					7 
					9,10   
					12   
					8 ~ 10   
					11 ~ 13   
					14 ~ 16   
					17 ~   
					12 ~   
					20   
					25   
					44   
					44   
					31   
					31   
					31   
					59   
					65   
					1 
					2 
					3 
					58   
					29   
				1 
					MXZ-3A30NA-   
					MXZ-4A   
					COOL (Hz)   
					Min.   
					HEAT (Hz)   
					Max.   
					70   
					Number of operating   
					unit   
					Capacity code   
					DRY (Hz)   
					Max.   
					58   
					58   
					71   
					80   
					80   
					80   
					80   
					80   
					80   
					90   
					90   
					Min.   
					20   
					20   
					20   
					20   
					20   
					20   
					20   
					20   
					20   
					20   
					20   
					Defrost   
					58   
					58   
					58   
					58   
					58   
					58   
					58   
					58   
					4 
					7 
					9,10   
					12   
					8 ~ 10   
					11 ~ 13   
					14 ~ 16   
					17 ~   
					12 ~   
					12 ~   
					16 ~   
					25   
					25   
					25   
					25   
					25   
					25   
					25   
					25   
					25   
					25   
					25   
					25   
					25   
					25   
					35   
					31   
					31   
					42   
					42   
					52   
					52   
					52   
					70   
					80   
					80   
					80   
					80   
					80   
					80   
					80   
					1 
					2 
					3 (MXZ-3A)   
					3 (MXZ-4A)   
					4 (MXZ-4A)   
					58   
					58   
					58   
					103   
					113   
					3-4. HEAT DEFROSTING CONTROL   
					(1) Starting conditions of defrosting   
					When the following conditions a) ~ c) are satisfied, the defrosting starts.   
					a) The defrost thermistor reads 26.6 °F or less.   
					b) The cumulative operation time of the compressor has reached any of the set values (31, 35, 45, 55, 65, 75, 85, 95,   
					105, 115, 150 minutes).   
					c) More than 5 minutes have passed since the start-up of the compressor.   
					Set value of compressor operation time (hereinafter referred to as defrost interval)   
					This is decided by the temperature of defrost thermistor and ambient temperature thermistor, the previous defrosting   
					time. For example, the first defrost interval is 40 minutes long, and the second is 45 minutes long. The third and sub-   
					sequent intervals are set to be longer, and less frequent, depending on defrosting time.   
					… 
					The third and subsequent defrost intervals follow any of the three patterns 5 or 10 to 20 minutes longer, the same,   
					… 
					or 5 or 10 to 20 minutes shorter compared with the previous defrost interval   
					shortest 40 minutes.   
					with the longest 125 minutes and the   
					(2) Releasing conditions of defrosting   
					Defrosting is released when any of the following conditions is satisfied:   
					a) The defrost thermistor continues to read 50.7 °F.   
					b) Defrosting time exceeds 10 minutes.   
					c) Any other mode than HEAT mode is set during defrosting.   
					3-5. DISCHARGE TEMPERATURE PROTECTION CONTROL   
					This protection controls the compressor ON/OFF and operation frequency according to temperature of the discharge tempera-   
					ture thermistor.   
					(1) Compressor ON/OFF   
					When temperature of the discharge temperature thermistor exceeds 240.8 °F, the control stops the compressor.   
					When temperature of the discharge temperature thermistor is 176 °F (2A/3A30NA)/ 212 °F (3A30NA- 1 /4A) or less, the   
					controls starts the compressor.   
					(2) Compressor operation frequency   
					When temperature of the discharge temperature thermistor is expected to be higher than 240.8 °F, the control decreases   
					12 Hz from the current frequency.   
					When temperature of the discharge temperature thermistor is expected to be higher than 231.8 °F and less than 240.8 °F,   
					the control decreases 6 Hz from the current frequency.   
					When temperature of the discharge temperature thermistor is expected to be higher than 219.2 °F and less than 231.8 °F,   
					the control is set at the current frequency.   
					3-6. OUTDOOR FAN CONTROL   
					Fan speed is switched according to the number of operating indoor unit and the compressor frequency.   
					<Relation between compressor frequency and fan speed>   
					Fan speed   
					Compressor frequency (Hz)   
					Down   
					Up   
					High   
					Down   
					Up   
					MXZ-2A   
					MXZ-3A30NA   
					30   
					40   
					Low   
					1 
					MXZ-3A30NA-   
					MXZ-4A   
					Min. Compressor frequency Max.   
					40   
					50   
					NOTE : When the indoor coil thermistor is 134.6 ˚F or more on HEAT operation, fan speed is fixed to Low speed.   
					Or, the indoor coil thermistor is 113 ˚F or less on HEAT operation, fan speed is back to normal.   
					30   
				3-7. PRE-HEAT CONTROL   
					MXZ-2A20NA- MXZ-3A30NA-   
					1 
					1 
					MXZ-4A36NA   
					The compressor is energized even while it is not operating.   
					This is to generate heat at the winding to improve the compressor's start-up condition.   
					Power   
					ON   
					OFF   
					Compressor ON   
					OFF   
					Outside temperature   
					68 °F   
					30min.   
					30 min.   
					30 min.   
					30 min.   
					30 min.   
					30 min. 15 min. 30 min.15 min. 30 min.   
					Pre-heat   
					ON   
					OFF   
					Start   
					Stop   
					When outside   
					temperature is   
					above 68 °F   
					Breaker ON   
					operation operation   
					1. Pre-heat control is turned ON for 15 or 30 min, after the breaker is turned ON.   
					2. 30 min. after the unit is stopped, pre-heat control is turned ON for 15 or 30 min. and turned OFF for 30 min."   
					This is repeated as shown in the graph until the breaker is turned OFF.   
					When outside temperature is 68 °F or below, pre-heat control is ON for 30 min."   
					When outside temperature is 69.8 °F or above, pre-heat control is ON for 15 min."   
					NOTE: When the unit is started with the remote controller, pre-heat control is turned OFF."   
					Compressor uses 50 W when pre-heat control is turned ON.   
					3-8. COOL OPERATION   
					1. Thermostat control   
					Thermostat is ON or OFF by difference between room temperature and set temperature.   
					Room temperature minus   
					set temperature (Initial)   
					Room temperature minus   
					set temperature (During operation)   
					Thermostat   
					ON   
					OFF   
					-1.8 °F or more   
					less than-1.8 °F   
					-1.8 °F   
					-1.3 °F   
					2. Coil frost prevention   
					The compressor operational frequency is controlled to prevent the indoor heat exchanger temperature from falling exces-   
					sively.   
					Compressor is turned OFF for 5 minutes when temperature of indoor coil thermistor continues 37.4 °F or less for 5 min-   
					utes or more.   
					31   
				3-9. DRY OPERATION   
					1. Thermostat control   
					Thermostat is ON or OFF by difference between room temperature and set temperature.   
					Room temperature minus   
					set temperature (Initial)   
					Room temperature minus   
					set temperature (During operation)   
					Thermostat   
					ON   
					OFF   
					-1.8 °F or more   
					less than-1.8 °F   
					-1.8 °F   
					-1.3 °F   
					2. Coil frost prevention   
					Coil frost prevention is as same as COOL mode. (3-8.2.)   
					3-10. HEAT OPERATION   
					1. Thermostat control   
					Thermostat is ON or OFF by difference between room temperature and set temperature.   
					Room temperature minus   
					set temperature (Initial)   
					Room temperature minus   
					set temperature (During operation)   
					Thermostat   
					ON   
					OFF   
					less than 3.6 °F   
					3.6 °F or more   
					3.6 °F   
					3 °F   
					2. High pressure protection   
					In HEAT operation the indoor coil thermistor detects the temperature of the indoor heat exchanger. The compressor opera-   
					tional frequency is controlled to prevent the condensing pressure from increasing excessively.   
					HEAD OFFICE: TOKYO BLDG.,2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN   
					Copyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD   
					Distributed in Feb. 2008. No. OBT16 REVISED EDITION-B 6   
					Distributed in May 2007. No. OBT16 REVISED EDITION-A 7   
					Distributed in Apr. 2006. No. OBT16 7   
					Made in Japan   
					New publication, effective Feb. 2008   
					Specifications subject to change without notice.   
				 |