Mitsubishi Electronics 15 User Manual

AIR-COOLED ROOFTOP PACKAGED AIR CONDITIONERS  
Series  
:
COOLING ONLY PR-5,8,10,15,20  
:
HEAT PUMP  
PRH-5,8,10,15,20  
PRH-5,8,10,15,20-L  
DATA BOOK  
SAFETY FOR USE  
Before conducting installation work, please read this ''SAFETY FOR USE'' carefully  
for correct installation.  
Since the caution items shown here contain important description relative to safety, please  
observe them without fail.  
Erroneous handling gives a high possibility to induce serious results such as  
death or heavy injury.  
Warning  
Erroneous handling may induce serious injury depending on the situation.  
Caution  
After reading, please keep it with you together the Instruction Manual, and read it again at the  
movement of the unit.  
Warning  
Never repair the unit, remodel or transfer it to  
another site by yourself.  
If they are performed improperly, water leakage, electric  
shock or fire may result. If you need to have the unit  
repaired or moved, consult your dealer.  
The unit should not be installed by the user.  
If the unit is installed improperly, explosion, water  
leakage, electric shock or fire may be result.  
Consult your dealer or specialist subcontractor for  
repair and movement.  
For installation, conduct the work correctly by  
following the Installation Manual.  
Improper installation may cause a fire, electrical shock  
or water leakage.  
Use only the specified refrigerant (R-22) to charge  
the refrigerant circuit.  
Do not mix it with any other refrigerant and do not allow  
air to remain in the circuit.  
Air enclosed in the circuit can cause high pressure resulting  
in a rupture and other hazards.  
Install the unit on a spot sufficiently durable against  
the unit weight.  
Insufficient durability can cause an injury by the falling  
down of unit.  
After completing installation work, make sure that  
refrigerant gas has not leaked.  
If refrigerant gas has leaked and exposed to fan heater,  
stove, oven and so on, it may generate noxious gases.  
All electric work must be performed by licensed  
technician, according to local regulations and the  
instructions given in this manual.  
The units should be powered by dedicated power lines.  
Power lines with insufficient capacity or improper  
electrical work may result in electric shock or fire.  
Take a proper measure to suppress the critical  
concentration of refrigerant if leaked when  
installing the unit in a small room.  
The limit density is made not to be exceeded even if the  
refrigerant leaks by any chance.  
You are necessary to ventilation measures to prevent  
the accident. If the refrigerant leaks, hypoxia accident  
may caused.  
Use only the specified cables for wiring.  
The connections must be made secured without  
tension the terminals.  
Improper connection or fastening can cause a fire or  
electrical shock.  
For the countermeasure to be taken, consult your  
dealer.  
The unit should be installed according to the  
instructions in order to minimize the risk of damage  
from earthquakes, typhoons or strong winds.  
Improper installation work can cause an injury by the  
falling down of the unit.  
The terminal block cover of unit must be firmly  
attached to prevent entry of dust and moisture.  
Improper mounting of the cover cause electric shock or  
fire.  
Use only optional parts authorised by Mitsubishi  
Electric.  
If the accessories are installed improperly, water  
leakage, electric shock or fire may result.  
Ask your dealer or an authorised company to install  
them.  
The unit must be installed on stable, flat surface,  
in a place where there is no accumulation of snow,  
leaves or rubbish.  
The unit should be installed in a location where air  
and noise emitted by the unit will not disturb the  
neighbors.  
If the unit is loosely mounted, it may fall, and cause injury.  
- 2 -  
Caution  
Arrange the configuration of wiring not to bring up  
Refrain from installing the unit in an area where  
flammable gas can accumulate around the unit.  
If the flammable gas can accumulate around the unit, an  
explosion can occur.  
When the unit is installed at telecommunication  
centers or hospitals, take a proper provision  
against noise.  
The erroneous operation of air conditioner may be  
induced by inverter equipment, independent power  
device, medical equipment or communication  
equipment.  
While the erroneous operation of medical equipment or  
communication equipment may caused by the air  
conditioner.  
the panel and terminal cover, and fasten the panel  
and terminal cover securely.  
The poor mounting of the panel or terminal cover may  
cause the heat generation of the terminal connection,  
a fire or electrical shock.  
Do not wash the unit with water.  
If washed with water, electrical shock may be caused.  
Do not handle the switch with wet hands.  
Otherwise electrical shock can be resulted.  
Be very careful on handling the unit.  
When carrying in outdoor unit, be sure to support it at  
four points.  
Carrying in and lifting with 3-point support may make  
outdoor unit unstable, resulting in a fall of it.  
The unit should not be carried by only one person if it is  
more than 20kg.  
For special use as for foods, animals/plants,  
precision equipment or art objects, the applicability  
should be confirmed beforehand.  
As the use for the applications other than that  
designed originally may result in the deterioration of the  
quality. Consult your dealer in this regard.  
Do not use the unit under a special atmosphere.  
Installing the unit at the following places may cause a  
trouble, a place where much machine oil, salt sonnet,  
humidity or dust, spa district, a place full of sulfur gas,  
volatile gas, or corrosive gas, a place near high  
frequency processing machine.  
Thermal insulation of the drain pipes is necessary  
prevent dew condensation.  
If the drain pipes are not properly insulated,  
condensation will result and drip on ceiling, floor or other  
possessions.  
The drain piping must process by surely,and insulate  
the drain piping not to be dewy.  
Some units use PP bands for packing.  
Do not use any PP band for delivery purpose.  
Do not touch the heat exchanger fins with your bear  
hands.  
Doing so may cut your hands.  
Be sure to safely dispose the packaging materials.  
Packaging materials, such as catches and other metal  
or wooden parts, may cause stabs or other injuries.  
Tear off and discard plastic packing bags so that  
children will not play any of them.  
If children play with a plastic bag which was not torn off,  
it may cause a risk of suffocation.  
The base and attachments of the unit should be  
periodically checked for looseness, cracks or other  
damage.  
If such defects are left uncorrected, the unit may fall and  
cause personal injury or property damage.  
When the room humidity exceeds 80% or when the  
drain pipe is clogged, water may drip from the indoor  
unit. The outdoor unit produces condensation during the  
heating operation.  
Make sure to provide drainage around the outdoor unit if  
such condensation is likely to cause damage.  
Turn on the main power switch more than 6 hours  
before starting operation.  
Do not turn the main power switch OFF during seasons  
of heavy use, doing so can result In failure.  
Do not touch the compressor or refrigerant piping  
without wearing glove on your hands.  
Touching directly such part can cause a burn or  
frostbite as it becomes high or low temperature  
according to the refrigerant state.  
Do not touch the metal edges inside the unit  
without wearing glove on your hands.  
Touching directly it may injure your hands.  
Do not remove the front panel or the fan guard from  
the unit when it is running.  
You could be injured if you touch rotating, hot or high-  
voltage parts.  
Install drain piping according to this Installation  
Manual to ensure proper drainage.  
Place thermal insulation on the pipes to prevent  
condensation.  
Improper drain piping may cause water leakage and  
damage to furniture or other possessions.  
The unit must be properly earth connected.  
Do not connect the earth wire to gas pipe, city water  
pipe, lightning rod or telephone earth wire.  
Improper earth connection may cause electrical shock.  
When installing at a watery place, provide an  
electric leak breaker.  
Failure to mount the electric leak breaker may cause  
electrical shock.  
Use breaker or fuse with proper capacity.  
Make sure that there is a main power switch.  
Using a wire or a copper wire instead of proper capacity  
of fuse can cause fire or trouble.  
Other appliances connected to the same line could cause  
an overload.  
Do not operate the air conditioner without the air  
filter set place.  
Dust may accumulate, and cause a failure.  
At emergency (if you smell something burning), stop  
operation and turn the power source switch off.  
Continuing the operation without eliminating the  
emergency state may cause a machine trouble, fire, or  
electrical shock.  
For the power lines, use standard cables of  
sufficient current capacity.  
Otherwise, current leakage, overheating or fire may  
occur.  
After stopping operation, be sure to wait for five  
minutes before turning off the main power switch.  
Otherwise, water leakage or unit failure may occur.  
When installing the power lines, do not apply  
tension to the cables.  
The tighten or loosen the connections may cause generate  
heat and cause fire.  
- 3 -  
A COMPLETE LINE UP  
PR-5YC  
PRH-5YA  
PRH-5YA-L  
(PRH ONLY)  
Cooling capacity Heatling capacity  
14,000 kcal/h  
55,600 BTU/h  
16.3 kW  
13,000 kcal/h  
51,600 BTU/h  
15.1 kW  
PR-8YC  
PRH-8YA  
PRH-8YA-L  
(PRH ONLY)  
Heatling capacity  
19,800 kcal/h  
78,600 BTU/h  
23 kW  
Cooling capacity  
20,500 kcal/h  
81,300 BTU/h  
23.8 kW  
PR-10YC  
PRH-10YA  
PRH-10YA-L  
(PRH ONLY)  
Cooling capacity Heatling capacity  
25,500 kcal/h  
101,200 BTU/h  
29.7 kW  
27,500 kcal/h  
109,100 BTU/h  
32 kW  
PR-15YC  
PRH-15YA  
PRH-15YA-L  
(PRH ONLY)  
Heatling capacity  
39,100 kcal/h  
155,100 BTU/h  
45.5 kW  
Cooling capacity  
39,800 kcal/h  
157,900 BTU/h  
46.3 kW  
PR-20YC  
PRH-20YA  
PRH-20YA-L  
(PRH ONLY)  
Heatling capacity  
52,600 kcal/h  
208,700 BTU/h  
61.2 kW  
Cooling capacity  
52,300 kcal/h  
207,500 BTU/h  
60.8 kW  
- 4 -  
FEATURES  
High Sensible Cooling Capacity  
Labor Saving Installation  
The sensible cooling capacity has been significantly  
improved through optimized heat exchanger design.  
Because of the single unit configuration, all  
refrigeration work can be omitted. The unit operation  
can commence immediately after connection to the  
power supply, drain piping, ducting and control  
system.  
Comfort Heating  
The PRH series are designed to provide effective heating  
even when the outside temperature is down to 0˚C. The  
PRH-L series are designed to provide effective heating  
even when the outside temperature is down to -10˚C.In  
addition, the twin circuit models, PRH-15,20YA,  
PRH-15,20YA-L are provided with control features that  
prevents both refrigeration circuits defrosting at the same  
time. This ensures constant comfort conditions during  
defrost and varying loads.  
Low Ambient Cooling  
In applications with relatively high internal loads,  
there may be a requirement for all series to operate  
on cooling at low ambient conditions. An optional  
accessory is available to maintain the refrigeration  
circuit in balance at outdoor temperatures as low as  
0˚C (PRH only).In case of PR,PRH-L is -5˚C.  
Please consult your local Mitsubishi Electric Sales  
office for application advice on this accessory.  
Highly Efficient Operation  
The EER (Energy Efficiency Ratio) on these models is  
greatly improved by revised design specifications and by  
being manufactured stringently to Mitsubishi Electric  
high quality standards.  
Wide Electrical Control Capability  
All series may be ordered in either of two control  
configurations.  
The factory standard is for provision of a 24 volt  
terminal block to enable a field wired control of the  
contractors choice to be connected.  
Flexibility of Supply Air Delivery  
Alternatively, for models PR-5-10YC,PRH-5-10YA,  
PRH-5-10YA-L the intelligent "K" series remote  
control system may be ordered. The K control  
utilizes a microprocessor and includes liquid crystal  
display with touch pad for adjustment of control  
parameters.  
These options give the flexibility to enable  
connection to Building Management Systems,  
smoke spill cycles, economy cycles, remote  
monitoring etc.  
All series feature belt driven Supply Air fans enabling  
accurate matching of actual airflow rates to the specified  
quantities. Accurate commissioning is assisted by the  
capability to exchange pulleys and belts if necessary to  
achieve the desired air balance.  
Please consult your local Mitsubishi Electric Sales  
office for application advice on these controls.  
- 5 -  
DESCRIPTIONS  
compressors, air-cooled condensers, evaporator  
MITSUBISHI ELECTRIC Rooftop Air Conditioners  
Series PR,PRH,RPH-L are available in a wide  
range of sizes and models to enable the designer  
to select the best model for each application.  
The complete range has been designed for  
outdoor installation, and the units are provided with  
the latest technological features to ensure  
economical, reliable and comfortable ducted type  
air conditioning.  
fans, condenser fans and auxiliary and control  
equipment, completely packaged in a water-proof  
enclosure.  
With the development of all series demands for  
such features as light weight, compactness,  
increased capacity, appropriate static pressure , air  
flow control, and having flexibility of inter-facing  
energy saving electronic controls Mitsubishi  
Electric have met market expectations.  
All series units are completely assembled, wired  
and strictly tested at the factory. They consist of a  
MECHANICAL SPECIFICATIONS  
General  
Condenser Coils  
All units are factory assembled, piped, internally  
wired and fully charged with R-22. They are also  
tested and checked under a strict quality control  
system in the factory. All units are designed for  
outdoor rooftop or ground level installation. Exterior  
surfaces of all units are phosphatized, zinc-coated  
steel with acrylic resin primer and ivory white baked  
enamel finish.  
Unnecessary power input due to higher  
discharge pressure is avoided by high  
performance designs of cross-finned coils.  
Condenser coils are made of 9.52mm OD,  
0.35mm thick seamless copper tubes  
mechanically bonded to 0.12mm thick aluminium  
plate fins. Each coil is factory pressure and leak  
tested at 3.3MPa.  
Refrigeration Controls  
Evaporator Fans  
Refrigeration controls include condenser fan,  
evaporator fan and compressor contactor. Each  
circuit of the unit has a separate set of refrigeration  
controls. PR, PRH,PRH-L-15,20 units have two  
independent circuits.  
Belt-drive, forward curved, centrifugal type fans  
made of galvanized steel are used to deliver an  
accurate airflow at low noise level.  
Condenser Fan  
This direct-drive propeller fan is dynamically  
balanced, to ensure smooth airflow. A weather-  
proof three-phase squirrel cage induction motor  
is used to drive the condenser fan.  
Compressors  
All units have high efficiency type hermetic line  
starting compressors. Compressors are equipped  
with thermal overload protector, overcurrent relay  
and high pressure protection controls. Crankcase  
heaters are standard .  
Evaporator Coils  
Highly efficient cross-finned coils are applied to  
provide a larger cooling capacity with low air speed  
on the coil. Coils are made of 9.52mm OD and  
0.35mm thick seamless copper tubing  
mechanically bonded to 0.12mm thick aluminium  
fins and are factory leak tested at a pressure of  
3.3MPa. They are provided with strainers attached  
to the capillary tubes to further ensure a clean  
system.  
- 6-  
TYPICAL INSTALLATION EXAMPLE  
PR  
PRH  
PRH-L  
- 7-  
SPECIFICATIONS  
PR-5YC  
PR-8YC  
PR-10YC  
PR-15YC  
PR-20YC  
PRH-5YA  
PRH-8YA  
PRH-10YA  
PRH-15YA PRH-20YA  
ITEM  
PRH-5YA-L PRH-8YA-L PRH-10YA-L PRH-15YA-L PRH-20YA-L  
kW  
BTU/h  
kcal/h  
kW  
16.3  
55,600  
14,000  
13  
23.8  
81,300  
20,500  
19.7  
29.7  
101,200  
25,500  
25.3  
46.3  
157,900  
39,800  
38.4  
60.8  
207,500  
52,300  
50.2  
TOTAL COOLING CAPACITY  
(GROSS)  
SENSIBLE COOLING CAPACITY  
(GROSS)  
BTU/h  
kcal/h  
kW  
44,400  
11,200  
15.1  
67,100  
16,900  
23  
86,500  
21,800  
32  
130,900  
33,000  
45.5  
171,400  
43,200  
61.2  
TOTALHEATING CAPACITY  
(GROSS)  
(PRH-YA,PRH-YA-L ONLY)  
BTU/h  
kcal/h  
%
51,600  
13,000  
78,600  
19,800  
0-100  
109,100  
27,500  
155,100  
39,100  
208,700  
52,600  
CAPACITY STEPS  
REFRIGERANT  
0-50-100  
R22(FACTORY CHARGED)  
CAPILLARY TUBE  
REFRIGERANT CONTROL  
EXTERNAR FINISH  
COLOR(MUNSELL NO.)  
HEIGHT  
ACRYLIC RESIN COATING  
MUNSELL 5Y8/1  
mm  
mm  
mm  
kg  
1,000  
1,200  
1,990  
1,840  
DIMENSION  
WIDTH  
DEPTH  
1,000  
299  
1,300  
1,600  
393  
NET WEIGHT  
COMPRESSOR  
MOTOR OUTPUT  
INDOOR COIL  
FAN  
413  
698  
729  
HERMETIC LINE START(RECIPROCATING)  
kW  
3.73  
5.6  
7.5  
2
X
5.6  
2
X
7.5  
CROSS FINCOIL  
CENTRIFUGAL (GALVANIZED STEEL) - BELT DRIVE  
THREE PHASE CAGE INDUCTION MOTOR  
FAN MOTOR  
FAN MOTOR OUTPUT  
kW  
CMM  
CFM  
L/S  
0.75  
54  
1.1  
84  
1.5  
2.2  
168  
3
100  
190  
NOMINAL AIR FLOW  
1,907  
900  
10  
2,967  
1,400  
10  
3,532  
5,934  
2,800  
20  
6,711  
3,160  
20  
1,660  
EXTERNAL STATIC  
PRESSURE  
mmAq  
Pa  
10  
100  
100  
100  
200  
200  
OUTDOOR COIL  
FAN  
CROSS FIN COIL  
PROPELLER -DIRECT DRIVE  
FAN MOTOR  
THREE PHASE CAGE INDUCTION MOTOR  
X
X
FANMOTOR OUTPUT  
kW  
CMM  
CFM  
L/S  
0.15  
95  
0.35  
185  
0.35  
185  
2
0.35  
185  
2
0.35  
185  
2
X
2
X
NOMINAL AIR FLOW  
X
X
3,355  
1,583  
6,534  
3,083  
6,534  
3,083  
25.4  
2
6,534  
3,083  
2
6,534  
3,083  
2
2
X
X
DRAIN CONNECTION  
mm  
HIGHPRESSURE SWITCH,FUSE  
PROTECTION DEVICES  
OVER CURRENT RELAY (COMP.& INDOOR FAN,OUTDOOR FAN)  
INTERNAL THERMOSTAT (COMP. & OUTDOOR FAN)  
ANTISHORT-CYCLE TIMER,FREEZE & FROST PROTECTOR  
NOTE 1. NOMINAL COOLING & HEATING CAPACITIES ARE BASED FOLLOWING CONDITIONS.  
COOLING : INDOOR:27˚CDB, 19˚C WB ; OUTDOOR:35˚CDB.  
HEATING : INDOOR:21˚CDB ; OUTDOOR:7DB, 6˚C WB.  
2. CAPACITIES ARE GROSS CAPACITIES WHICH DO NOT INCLUDE A DEDUCTION FOR EVAPORATOR  
FAN MOTOR HEAT.  
- 8 -  
ELECTRICAL DATA  
Cooling  
PR-5YC  
PR-8YC  
PR-10YC  
PR-15YC  
PR-20YC  
PRH-5YA  
PRH-8YA  
PRH-10YA  
PRH-15YA  
PRH-20YA  
VOLT  
ITEM  
PRH-5YA-L PRH-8YA-L  
PRH-10YA-L PRH-15YA-L PRH-20YA-L  
TOTAL INPUT  
kW  
A
5.4  
10.3  
73  
8.3  
15.9  
73  
11.4  
20.2  
79  
16.8  
30.8  
76  
22.7  
39.1  
81  
TOTAL RUNCURRENT  
POWER FACTOR  
START CURRENT  
%
A
62  
87  
100  
115  
135  
415V COMPRESSOR INPUT  
RUNCURRENT  
kW  
A
3.92  
7.44  
1.24  
2.26  
0.24  
0.6  
6.46  
11.70  
1.30  
2.90  
0.54  
1.3  
9.22  
15.62  
1.64  
3.28  
0.54  
1.3  
2 X 6.55  
2 X 11.74  
2.62  
2 X9.30  
2 X15.22  
3.02  
I/D FAN INPUT  
RUNCURRENT  
kW  
A
4.72  
6.06  
O/D FAN INPUT  
RUNCURRENT  
kW  
A
2 X 0.54  
2 X 1.3  
2 X0.54  
2 X 1.3  
TOTAL INPUT  
kW  
A
5.4  
11.2  
73  
8.3  
17.3  
73  
11.4  
21.9  
79  
16.8  
33.6  
76  
22.7  
42.6  
81  
TOTAL RUNCURRENT  
POWER FACTOR  
START CURRENT  
%
A
68  
95  
109  
126  
147  
380V COMPRESSOR INPUT  
RUNCURRENT  
kW  
A
3.92  
8.06  
1.24  
2.48  
0.24  
0.66  
6.46  
12.71  
1.30  
3.17  
0.54  
1.42  
9.22  
16.90  
1.64  
3.58  
0.54  
1.42  
2 X 6.55  
2 X 12.80  
2.62  
2 X9.30  
2 X16.57  
3.02  
I/D FAN INPUT  
RUNCURRENT  
kW  
A
5.16  
6.62  
O/D FAN INPUT  
RUNCURRENT  
kW  
A
2 X 0.54  
2 X 1.42  
2 X0.54  
2 X1.42  
(PRH,PRH-L Only)  
Heating  
PRH-5YA  
PRH-8YA  
PRH-10YA  
PRH-15YA  
PRH-20YA  
VOLT  
ITEM  
PRH-5YA-L PRH-8YA-L PRH-10YA-L PRH-15YA-L PRH-20YA-L  
kW  
A
4.8  
9.8  
68  
7.0  
14.1  
69  
9.6  
18.2  
73  
14.4  
27.2  
74  
19.3  
34.8  
77  
TOTAL INPUT  
TOTAL RUNCURRENT  
POWER FACTOR  
%
A
62  
87  
100  
111  
131  
START CURRENT  
415V COMPRESSOR INPUT  
RUNCURRENT  
kW  
A
3.32  
6.94  
1.24  
2.26  
0.24  
0.6  
5.16  
9.90  
1.30  
2.90  
0.54  
1.3  
7.42  
13.62  
1.64  
3.28  
0.54  
1.3  
2 X5.35  
2 X9.94  
2.62  
2 X7.60  
2 X13.07  
3.02  
I/D FAN INPUT  
RUNCURRENT  
kW  
A
4.72  
6.06  
O/D FAN INPUT  
RUNCURRENT  
kW  
A
2 X0.54  
2 X 1.3  
2 X0.54  
2 X 1.3  
kW  
A
4.8  
10.7  
68  
7.0  
15.4  
69  
9.6  
20.0  
73  
14.4  
29.6  
74  
19.3  
38.1  
77  
TOTAL INPUT  
TOTAL RUNCURRENT  
POWER FACTOR  
START CURRENT  
%
A
68  
95  
109  
121  
143  
380V COMPRESSOR INPUT  
RUNCURRENT  
kW  
A
3.32  
7.56  
1.24  
2.48  
0.24  
0.66  
5.16  
10.81  
1.30  
3.17  
0.54  
1.42  
7.42  
15.00  
1.64  
3.58  
0.54  
1.42  
2 X5.35  
2 X10.8  
2.62  
2 X7.60  
2 X14.32  
3.02  
I/D FAN INPUT  
RUNCURRENT  
kW  
A
5.16  
6.62  
O/D FAN INPUT  
RUNCURRENT  
kW  
A
2 X0.54  
2 X1.42  
2 X0.54  
2 X1.42  
- 9 -  
CAPACITY TABLES  
- 10 -  
- 11 -  
- 12 -  
- 13 -  
- 14 -  
- 15 -  
- 16 -  
- 17 -  
- 18 -  
- 19 -  
Operation range  
PR-YC  
Cooling  
50  
46  
40  
30  
20  
10  
0
-10  
10  
15  
20 2425  
30  
Indoor temp.(˚CWB)  
PRH-YA  
Heating  
Cooling  
50  
46  
15  
40  
10  
5
30  
20  
10  
0
- 5  
0
-10  
10  
-10  
10  
15  
20 2425  
30  
15  
20  
25 27 30  
Indoor temp.(˚CWB)  
Indoor temp.(˚CDB)  
Heating  
Cooling  
PRH-YA-L  
50  
46  
15  
40  
10  
5
30  
20  
10  
0
- 5  
0
-10  
10  
-10  
10  
15  
20 2425  
30  
15  
20  
25 27 30  
Indoor temp.(˚CWB)  
Indoor temp.(˚CDB)  
- 20-  
FAN PERFORMANCE  
Airflow  
PR-5YC  
CMM  
45  
750  
1230  
139.7  
5.5  
165.1  
6.5  
B39  
0.75  
1330  
139.7  
5.5  
50  
55  
60  
PRH-5YA  
PRH-5YA-L  
L/S  
830  
1320  
920  
1450  
1000  
1450  
FAN SPEED  
rpm  
PULLEYSIZE  
mm  
inch  
127  
5
139.7  
5.5  
139.7  
5.5  
(MOTOR SIDE)  
Operation range  
100  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
mm  
inch  
inch  
kw  
139.7  
5.5  
B36  
0.75  
1450  
139.7  
5.5  
139.7  
5.5  
B37  
0.75  
1580  
152.4  
6
139.7  
5.5  
B37  
0.75  
1580  
152.4  
6
139.7  
5.5  
B40  
1.1  
1610  
127  
5
139.7  
5.5  
B39  
1.1  
1600  
139.7  
5.5  
127  
5
B39  
1.1  
-
-
-
Fan speed  
MOTOR  
(rpm)  
700  
600  
500  
400  
300  
200  
100  
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
200  
152.4  
6
External  
static  
pressure  
(Pa)  
1800  
1700  
B38  
0.75  
1450  
139.7  
5.5  
139.7  
5.5  
B37  
0.75  
1610  
127  
5.0  
114.3  
4.5  
B35  
0.75  
MOTOR  
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
1600  
1500  
139.7  
5.5  
B40  
1.1  
-
114.3  
4.5  
B37  
1.1  
-
-
-
-
-
300  
1400  
MOTOR  
1300  
1200  
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
-
-
-
-
-
-
-
1100  
400  
-
-
-
45  
750  
50  
830  
60  
1000  
(CMM)  
( / s)  
-
-
-
-
-
-
MOTOR  
-
-
-
Airflow  
Std.  
Airflow  
CMM  
L/S  
60  
1000  
1000  
70  
1170  
1090  
80  
1330  
1310  
90  
1500  
1310  
95  
1580  
1450  
PR-8YC  
FAN SPEED  
rpm  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
mm  
inch  
mm  
114.3  
4.5  
114.3  
4.5  
114.3  
4.5  
114.3  
4.5  
127  
5.0  
PRH-8YA  
165.1  
152.4  
127  
127  
127  
100  
200  
PRH-8YA-L  
(FAN SIDE)  
BELT SIZE  
inch  
inch  
kw  
6.5  
B39  
1.1  
1230  
139.7  
5.5  
165.1  
6.5  
B41  
1.1  
1450  
127  
5.0  
127  
5.0  
B38  
1.1  
1580  
152.4  
6.0  
139.7  
5.5  
B40  
1.1  
1740  
152.4  
6.0  
127  
5.0  
B39  
1.1  
6.0  
B39  
1.1  
1320  
127  
5.0  
139.7  
5.5  
B39  
1.1  
1450  
127  
5.0  
127  
5.0  
B38  
1.1  
1600  
139.7  
5.5  
127  
5.0  
B39  
1.1  
1740  
152.4  
6.0  
127  
5.0  
B36  
1.5  
5.0  
B37  
1.1  
1450  
127  
5.0  
127  
5.0  
B38  
1.1  
1580  
152.4  
6
139.7  
5.5  
B37  
1.5  
1690  
177.8  
7.0  
152.4  
6.0  
B39  
1.5  
-
-
-
-
-
-
-
5.0  
B37  
1.5  
1450  
127  
5.0  
127  
5.0  
B35  
1.5  
1600  
139.7  
5.5  
127  
5.0  
B35  
1.5  
-
-
-
-
-
5.0  
B35  
1.5  
1580  
152.4  
6.0  
139.7  
5.5  
Operation range  
MOTOR  
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
Fan speed (rpm)  
600  
500  
400  
300  
200  
100  
1800  
1700  
B37  
1.5  
External  
static  
pressure  
(Pa)  
MOTOR  
1600  
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1.5kW  
1500  
1400  
1.1kW  
300  
400  
500  
1300  
1200  
1100  
MOTOR  
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
1000  
60  
1000  
70  
1170  
80  
1330  
90  
1500  
(CMM)  
-
-
-
-
-
-
-
-
(
/ s)  
MOTOR  
Airflow  
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
MOTOR  
-
Std.  
- 21 -  
PR-10YC  
Airflow  
90  
1500  
1320  
127  
CMM  
L/S  
100  
1660  
110  
1830  
120  
2000  
1550  
190.5  
7.5  
177.8  
7.0  
B39  
2.2  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
PRH-10YA  
PRH-10YA-L  
FAN SPEED  
rpm  
mm  
1450  
139.7  
5.5  
1450  
139.7  
5.5  
PULLEYSIZE  
(MOTOR SIDE)  
Operation range  
inch  
mm  
5.0  
139.7  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
139.7  
139.7  
100  
200  
inch  
inch  
kw  
5.5  
B35  
1.5  
1450  
139.7  
5.5  
139.7  
5.5  
B36  
1.5  
1580  
152.4  
6
139.7  
5.5  
B37  
1.5  
1710  
165.1  
6.5  
5.5  
B36  
1.5  
1450  
139.7  
5.5  
139.7  
5.5  
B36  
1.5  
1600  
139.7  
5.5  
127  
5.0  
B33  
2.2  
1740  
152.4  
6.0  
5.5  
B33  
2.2  
1600  
139.7  
5.5  
127  
5.0  
B33  
2.2  
1740  
152.4  
6.0  
127  
5.0  
B34  
2.2  
-
Fan speed  
MOTOR  
(rpm)  
600  
External  
static  
pressure  
(Pa)  
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
500  
1800  
1700  
400  
MOTOR  
1600  
300  
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
1500  
2.2kW  
300  
200  
1400  
1.5kW  
1300  
100  
MOTOR  
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
1200  
-
-
-
-
-
-
90  
100  
1670  
110  
1830  
120  
2000  
(CMM)  
( / s)  
400  
139.7  
5.5  
B35  
2.2  
127  
5.0  
B34  
2.2  
1500  
Airflow  
MOTOR  
Std.  
Airflow  
120  
CMM  
130  
140  
2330  
690  
114.3  
4.5  
241.3  
9.5  
150  
2500  
730  
127  
5.0  
160  
170  
2830  
760  
127  
5.0  
241.3  
9.5  
180  
PR-15YC  
L/S  
2000  
2170  
2670  
3000  
FAN SPEED  
rpm  
640  
101.6  
4.0  
640  
101.6  
4.0  
730  
127  
5.0  
810  
127  
5.0  
PRH-15YA  
PRH-15YA-L  
PULLEYSIZE  
(MOTOR SIDE)  
mm  
inch  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
mm  
inch  
inch  
kw  
228.6  
228.6  
254  
254  
228.6  
100  
200  
9.0  
9.0  
10.0  
10.0  
9.0  
Operation range  
B37  
2.2  
2
B37  
2
B39  
2.2  
2
B41  
2
B41  
2
B40  
2
B39  
2
MOTOR  
2.2  
810  
127  
5.0  
2.2  
850  
127  
5.0  
2.2  
890  
2.2  
890  
2.2  
910  
127  
5.0  
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
760  
127  
5.0  
810  
127  
5.0  
External  
static  
pressure  
(Pa)  
Fan speed  
139.7  
5.5  
139.7  
5.5  
(rpm)  
800  
241.3  
9.5  
228.6  
9.0  
228.6  
9.0  
215.9  
8.5  
228.6  
9.0  
228.6  
9.0  
203.2  
8.0  
B40  
2
B39  
2
B39  
2
B38  
2
B39  
2
B39  
2
B37  
2
700  
MOTOR  
2.2  
910  
127  
5.0  
2.2  
910  
127  
5.0  
2.2  
910  
127  
5.0  
2.2  
970  
127  
5.0  
2.2  
1000  
139.7  
5.5  
2.2  
970  
127  
5.0  
3.0  
1040  
127  
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
1200  
600  
5.0  
300  
400  
500  
600  
203.2  
8.0  
203.2  
8.0  
203.2  
8.0  
190.5  
7.5  
203.2  
8.0  
190.5  
7.5  
177.8  
7.0  
3.0kW  
2.2kW  
2
2
2
2
2
2
2
B37  
B37  
B37  
B36  
B37  
B36  
B35  
500  
MOTOR  
2.2  
1040  
127  
2.2  
1040  
127  
2.2  
1040  
127  
2.2  
1040  
127  
3.0  
1040  
127  
3.0  
1040  
127  
3.0  
-
1100  
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
-
400  
5.0  
5.0  
5.0  
5.0  
5.0  
5.0  
-
1000  
177.8  
7.0  
177.8  
7.0  
177.8  
7.0  
177.8  
7.0  
177.8  
7.0  
177.8  
7.0  
-
-
900  
300  
B35  
B35  
B35  
B35  
B35  
B35  
-
2
2
2
2
2
2
MOTOR  
2.2  
1120  
127  
2.2  
1140  
139.7  
5.5  
3.0  
1120  
127  
3.0  
1120  
127  
3.0  
-
3.0  
-
-
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
-
800  
200  
-
-
-
5.0  
5.0  
5.0  
-
-
-
700  
165.1  
6.5  
177.8  
7.0  
165.1  
6.5  
165.1  
6.5  
-
-
-
-
-
-
100  
600  
B34  
2
B36  
2
B34  
2
B34  
2
-
-
-
MOTOR  
2.2  
1210  
127  
3.0  
1230  
139.7  
5.5  
3.0  
1230  
139.7  
5.5  
3.0  
-
-
-
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
-
-
-
-
-
-
-
-
-
-
-
-
-
120  
2000  
140  
2330  
160  
2670  
180  
3000  
(CMM)  
/ s)  
5.0  
-
-
-
(
152.4  
6.0  
165.1  
6.5  
165.1  
6.5  
-
-
-
-
-
-
Airflow  
B33  
2
B35  
2
B35  
2
-
-
-
MOTOR  
3
3
3
-
-
-
Std.  
- 22 -  
Airflow  
170  
2830  
730  
CMM  
L/S  
180  
3000  
810  
190  
3170  
810  
200  
3330  
840  
210  
3500  
910  
220  
3670  
940  
FAN SPEED  
rpm  
PR-20YC  
mm  
inch  
PULLEY SIZE  
127  
5.0  
254  
10.0  
B43  
3.0  
127  
5.0  
228.6  
9.0  
B41  
3.0  
910  
127  
5.0  
203.2  
8.0  
127  
5.0  
228.6  
9.0  
B41  
3.0  
910  
127  
5.0  
203.2  
8.0  
139.7  
5.5  
241.3  
127  
5.0  
203.2  
8.0  
B39  
3.0  
1000  
139.7  
5.5  
203.2  
8.0  
139.7  
5.5  
215.9  
(MOTOR SIDE)  
PRH-20YA  
PRH-20YA-L  
PULLEY SIZE  
(FAN SIDE)  
BELT SIZE  
mm  
inch  
inch  
kw  
100  
200  
9.5  
8.5  
2
2
2
2
2
2
B42  
B41  
MOTOR  
3.0  
910  
127  
5.0  
203.2  
8.0  
4.0  
970  
127  
5.0  
190.5  
7.5  
FAN SPEED  
PULLEY SIZE  
(MOTOR SIDE)  
PULLEY SIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
850  
127  
5.0  
215.9  
8.5  
B40  
3.0  
940  
139.7  
5.5  
215.9  
8.5  
External  
static  
pressure  
(Pa)  
Operation range  
Fan speed  
2
2
B39  
2
B39  
2
B39  
2
B40  
2
B38  
(rpm)  
MOTOR  
3.0  
1000  
139.7  
5.5  
203.2  
8.0  
3.0  
1040  
127  
5.0  
177.8  
7.0  
3.0  
1040  
127  
5.0  
177.8  
7.0  
4.0  
1040  
127  
5.0  
177.8  
7.0  
B37  
4.0  
-
-
4.0  
700  
FAN SPEED  
PULLEY SIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
rpm  
mm  
inch  
mm  
inch  
-
-
-
-
-
300  
400  
600  
1200  
2
2
2
2
2
BELT SIZE  
MOTOR  
inch  
kw  
B41  
B40  
B37  
B37  
-
-
3.0  
1040  
127  
5.0  
177.8  
7.0  
3.0  
1040  
127  
5.0  
177.8  
7
4.0  
1060  
139.7  
5.5  
190.5  
7.5  
B39  
4.0  
-
-
-
-
-
-
-
-
-
-
-
-
-
4.0  
1120  
127  
5.0  
165.1  
6.5  
500  
FAN SPEED  
PULLEY SIZE  
(MOTOR SIDE)  
PULLEY SIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1100  
-
-
-
-
400  
4.0kW  
3.0kW  
B37  
2
B37  
2
2
B36  
2
1000  
300  
MOTOR  
3.0  
1140  
139.7  
5.5  
177.8  
7.0  
4.0  
1120  
127  
5.0  
165.1  
6.5  
4.0  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
FAN SPEED  
PULLEY SIZE  
(MOTOR SIDE)  
PULLEY SIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
900  
200  
500  
800  
B38  
4
2
B36  
2
MOTOR  
4
-
-
-
-
-
-
-
100  
700  
FAN SPEED  
PULLEY SIZE  
(MOTOR SIDE)  
PULLEY SIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
1230  
139.7  
5.5  
165.1  
6.5  
600  
170  
2830 3000  
180  
200  
3330  
220  
3670  
(CMM)  
B37  
4.0  
2
(
/ s)  
MOTOR  
-
Airflow  
Std.  
- 23 -  
Pulley outside dimensions are shown below: (Unit : mm)  
(1) Shape of belt groove  
e
f
Sectional plan of V-belt  
w
L0  
V-belt  
thickness  
(Reference)  
Shape of Nominal  
V-belt Dia. øP.C ( ˚  
a
W
L0  
K
K0  
e
f
r1  
r2  
r3  
16.5mm  
)
r1  
r3  
Over 125  
Under 160  
34 15.86  
a
r2 r2  
Over 160  
36  
38  
12.5 5.5 9.5 19.0 12.5 0.2~0.5 0.5~1.0  
1~2  
11  
16.07  
16.29  
B
Under 200  
40˚  
Over 200  
B type  
(2) Shape of motor pulley boss (Unit : mm)  
C
PR-5 10  
MOTOR  
CAPACITY  
A
B
C
PRH-5 10 Pulley for blower & motor  
(kW)  
+0.009  
0
+0.073  
+0.040  
0.75  
19  
24  
24  
28  
28  
38  
15.5  
20.0  
20.0  
23.9  
23.9  
33.0  
6
8
- 0.004  
- 0.2  
+0.009  
- 0.004  
0
+0.073  
+0.040  
1.1  
1.5  
- 0.2  
+0.009  
- 0.004  
0
+0.073  
+0.040  
8
- 0.2  
+0.009  
- 0.004  
0
+0.073  
+0.040  
2.2, 3.0  
4.0  
8
- 0.2  
+0.009  
- 0.004  
0
+0.073  
+0.040  
8
- 0.2  
+0.018  
- 0.002  
0
+0.089  
+0.050  
5.5  
10  
- 0.2  
PR-8 20  
PR-5  
PRH-5  
PR-15,20  
PRH-8 20  
c
PRH-15, 20 Pulley for blower & motor  
MODEL  
a
b
c
PR-5  
-0.020  
0
19  
20  
20  
25  
PRH-5  
-0.007  
- 0.1  
PR-8,10  
-0.020  
-0.007  
0
0
- 0.1  
16.5  
21.0  
6
8
PRH-8, 10  
- 0.036  
-0.020  
-0.007  
PR-15,20  
0
0
- 0.1  
- 0.036  
PRH-15, 20  
(3) Shape of motor (Unit : mm)  
L
AC  
SHAFT  
Diameter  
Limits  
TBW  
AD  
AE  
+0.009  
-0.004  
+0.018  
-0.002  
19 to 28  
32 to 48  
ED  
F
E
øD  
Shaft  
tapped  
DH x EH  
deep  
Holes  
K Dia.  
EB  
E
AA  
AA  
LL  
A CRS  
AB  
C
B CRS  
BB  
BC  
Frame Fixing  
OUT PUT Size  
Shaft  
General  
ED DH EH AA AB BB BC  
A
B
C
H
K
D
E
F
G
L
HA AC AD AE EB LL TBW TBH  
0.75  
1.1  
80  
125 100 50  
80 10 19  
90 10 24  
90 10 24  
40  
50  
50  
60  
60  
6
8
8
8
8
15.5 25 M6 16 27 157 127 13.5 295  
20 32 M8 19 28 174 152 38.5 320  
20 32 M8 19 28 174 152 13.5 320  
23.9 40 M10 22 28 184 170 15 371  
23.9 40 M10 22 35 218 170 15 377  
4
4
4
4
4
5
158 132 102 1.5 75 103 103  
178 140 110 1.5 100 103 103  
178 140 110 1.5 100 103 103  
208 138 120 1.6 23 103 103  
215 164 130 1.6 23 131 131  
257 189 154 1.6 26 131 131  
90SN 140 100 56  
90N 140 125 56  
1.5  
2.2,3.0  
4.0  
100L 160 140 63 100 12 28  
112M 190 140 70 112 12 28  
132S 216 140 89 132 12 38  
5.5  
80 10 33 56 M12 28 38 243 208 53 458  
- 24 -  
NC CURVES  
PR-5YC  
PRH-5YA  
PRH-5YA-L  
50Hz  
CONDITION  
A scale  
62db  
63 Hz  
67  
125 Hz  
63  
250 Hz  
62  
500 Hz  
61  
1000 Hz  
57  
2000 Hz  
50  
4000 Hz  
45  
8000 Hz  
43  
COOLING &  
HEATING  
90  
80  
70  
60  
50  
40  
30  
20  
NC-70  
NC-60  
NC-50  
NC-40  
NC-30  
NC-20  
10  
over  
45  
63  
90  
125  
180  
250  
355  
500  
710  
1000  
1400  
2000  
2800  
4000  
5600  
8000  
all  
octave-band frequency [Hz]  
Note. The measuring point is 1m from the comp. service panel.  
PR-8YC  
PRH-8YA  
PRH-8YA-L  
50Hz  
CONDITION  
A scale  
64db  
63 Hz  
70  
125 Hz  
67  
250 Hz  
62  
500 Hz  
60  
1000 Hz  
58  
2000 Hz  
56  
4000 Hz  
52  
8000 Hz  
50  
COOLING &  
HEATING  
90  
80  
70  
60  
50  
40  
30  
20  
10  
NC-70  
NC-60  
NC-50  
NC-40  
NC-30  
NC-20  
over  
all  
45  
63  
90  
125  
180  
250  
355  
500  
710  
1000  
1400  
2000  
2800  
4000  
5600  
8000  
octave-band frequency [Hz]  
Note. The measuring point is 1m from the comp. service panel.  
- 25 -  
PR-10YC  
PRH-10YA  
PRH-10YA-L  
50Hz  
CONDITION  
A scale  
64db  
63 Hz  
71  
125 Hz  
69  
250 Hz  
63  
500 Hz  
61  
1000 Hz  
59  
2000 Hz  
57  
4000 Hz  
49  
8000 Hz  
44  
COOLING &  
HEATING  
90  
80  
70  
60  
50  
40  
30  
NC-70  
NC-60  
NC-50  
NC-40  
NC-30  
NC-20  
20  
10  
over  
all  
45  
63  
90  
125  
180  
250  
355  
500  
710  
1000  
1400  
2000  
2800  
4000  
5600  
8000  
octave-band frequency [Hz]  
Note. The measuring point is 1m from the comp. service panel.  
PR-15YC  
PRH-15YA  
PRH-15YA-L  
50Hz  
CONDITION  
A scale 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz  
COOLING &  
HEATING  
68db  
76  
76  
68  
65  
62  
59  
51  
48  
90  
80  
70  
60  
50  
40  
30  
20  
NC-70  
NC-60  
NC-50  
NC-40  
NC-30  
NC-20  
10  
over  
45  
63  
90  
125  
180  
250  
355  
500  
710  
1000  
1400  
2000  
2800  
4000  
5600  
8000  
all  
octave-band frequency [Hz]  
Note. The measuring point is 1m from the comp. service panel.  
- 26 -  
50Hz  
PR-20YC  
PRH-20YA  
PRH-20YA-L  
CONDITION  
A scale  
68db  
63 Hz  
73.5  
125 Hz  
77  
250 Hz  
70  
500 Hz  
65  
1000 Hz 2000 Hz 4000 Hz 8000 Hz  
COOLING &  
HEATING  
60  
58  
51  
48  
90  
80  
70  
60  
50  
40  
30  
NC-70  
NC-60  
NC-50  
NC-40  
NC-30  
NC-20  
20  
10  
over  
all  
45  
63  
90  
125  
180  
250  
355  
500  
710  
1000  
1400  
2000  
2800  
4000  
5600  
8000  
octave-band frequency [Hz]  
Note. The measuring point is 1m from the comp. service panel.  
OUTLINE DIMENSIONS  
PR-5YC  
PRH-5YA  
PRH-5YA-L  
25  
1030  
25  
16-ø3.5 HOLES  
(1030)  
25  
CONDENSER AIR OUTLET  
65  
10  
25  
200  
200  
850  
200  
200  
25  
A
SUPPLY AIR DUCT FLANGE  
25  
A(DETAIL)  
RETURN AIR DUCT FLANGE  
6-15X25 MTG HOLES  
10  
65  
900  
30  
210  
210  
210  
210  
30  
850  
900  
75  
75  
50  
40  
50  
40  
1600  
16-ø3.5 HOLES  
1000  
49  
607  
944  
470  
SUPPLY AIR  
CONDENSER AIR INLET  
(2 SIDES)  
CONTROL BOX  
RETURN AIR  
22  
22  
54.5  
80  
54.5  
971  
DRAIN 1B PT  
1534  
WIRING HOLE  
80  
4- ø25  
SASPENSION HOLES  
424  
1080  
- 27 -  
PR-8,10YC  
PRH-8, 10YA  
PRH-8, 10YA-L  
20-ø3.5 HOLES  
25  
1330  
25  
(1330)  
25  
65  
10  
35  
180  
180  
180  
180  
180  
180  
35  
CONDENSER AIR  
OUTLET  
1150  
A
SUPPLY AIR DUCT FLANGE  
25  
A(DETAIL)  
RETURN AIR DUCT FLANGE  
6-15X25 MTG HOLES  
1200  
190 190  
10  
65  
30  
190  
190  
190  
190  
30  
75  
1150  
1200  
1300  
75  
1600  
20-ø3.5 HOLES  
50  
40  
50  
40  
49  
607  
944  
470  
SUPPLY AIR  
CONTROL BOX  
CONDENSER AIR INLET  
(2 SIDES)  
RETURN AIR  
22  
54.5  
22  
54.5  
80  
80  
1271  
1380  
4-ø25  
SASPENSION HOLES  
DRAIN 1B PT  
1534  
WIRING HOLE  
424  
PR-15,20YC  
PRH-15, 20YA  
PRH-15, 20YA-L  
26-ø3.5 HOLES  
25  
2010  
25  
25  
2010  
62  
60 150 200 200 200 200 200 200 200 150  
1820  
60  
10  
CONDENSER AIR OUTLET  
A
25  
SUPPLY AIR DUCT FLANGE  
A (DETAIL)  
RETURN AIR DUCT FLANGE  
1879  
6-15X25 MTG HOLES  
10  
62  
39.5  
200 200 200 200 200 200 200 200 200 39.5  
85  
85  
1820  
1879  
1990  
26-ø3.5 HOLES  
55.5  
35  
55.5  
35  
1840  
43  
717  
1080  
990  
540  
SUPPLY AIR  
CONTROL BOX  
CONDENSER  
AIR INLET  
(3 SIDES)  
RETURN AIR  
RETURN AIR  
101  
131  
22  
54.5  
22  
WIRING HOLE  
DRAIN 1B PT  
1742.7  
1951  
2060  
4-ø25  
54.5  
556.5  
SUSPENSION HOLES  
37  
- 28 -  
WIRING DIAGRAMS  
PR-5, 8, 10YC (STANDARD)  
Power Supply  
3Phase  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
380~415Volt  
50Herts  
PR- 5YC ···40A  
PR- 8YC ···50A  
PR-10YC ···60A  
TB1  
51C  
52C  
INTERNAL  
MC  
L1  
L2  
L3  
RED  
RED  
PROTECTOR  
RED  
WHITE  
WHITE  
BLACK  
WHITE  
BLACK  
BLACK  
TB2  
RED  
51F2  
TB2  
1
RED  
R1  
RED  
R2  
S2  
T2  
MF2  
N
BLUE  
WHITE  
BLACK  
WHITE  
BLACK  
WHITE  
BLACK  
S1  
T1  
2
3
PE  
52F  
51F1  
RED  
RED  
WHITE  
BLACK  
MF1  
F
INTERNAL  
F
(3.15A)  
PROTECTOR  
TB3  
11  
11  
TB4  
1
SWITCH BOX  
(FIELD SUPPLY)  
15  
51F1  
F
SW1  
(3.15A)  
GL  
RL  
51F2  
63H  
FZ1  
52C  
Tr  
23  
WA  
SW2  
51  
1
C
AC  
AC  
24V  
220~  
240V  
3
2
4
5
6
TB4  
26L  
3
CZ  
CZ  
CH  
52F  
CZ  
FZ0  
FZ1  
TM  
(3MIN)  
52C  
8,20YC ONLY  
30  
CZ  
30  
CZ  
TM  
FZ0  
FZ1  
30  
CZ  
7
52C  
12 TB3  
TB3  
12  
Caution,  
Symbol  
Name  
1.To protect each Fan motors and Compressors from abnormal current,  
these Over current relays<51C>,<51F1,2>are installed.  
Therefore,do not change factory set value of these Over current relays.  
2.To protect the compressor from frequently "ON-OFF" ,timer<TM>is  
installed. Therefore,do not change factory set value of this timer.  
MC  
MF1  
MF2  
52C  
52F  
TB1~4  
CH  
F
Tr  
51C  
51F1, 2  
63H  
26L  
Compressor motor  
Fan motor (in door)  
Fan motor (out door)  
Contactor (compressor)  
Contactor (fan I/D)  
Terminal block  
Crankcase heater  
Fuse  
Transformer  
Over current relay(compressor)  
Over current relay (fan I/D,O/D)  
High-pressure switch  
Thermostat(freeze protection)  
Timer (anti short cycle)  
Auxiliary relay (fan)  
Auxiliary relay (compressor)  
Auxiliary relay (check)  
Switch (off)  
Note:  
1.The dotted lines show field wiring.  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
5.Specification subject to change without notice.  
TM  
FZ0·1  
CZ  
30CZ  
<SW1>  
<SW2>  
<GL>  
Switch (on)  
Lamp (operation)  
<RL>  
Lamp (check)  
Thermostat (room temp.)  
<23WA>  
- 29 -  
PR-15, 20YC (STANDARD)  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
Power supply  
3Phase  
380~415Volt  
50Hertz  
PR -15YC···100A  
PR -20YC···125A  
MC1  
INTERNAL  
PROTECTOR  
52C1  
51C1  
TB1  
L1  
L2  
L3  
Red  
White  
Red  
Red  
White  
Black  
Black  
Black  
TB2  
R11  
51F2  
R12  
S12  
T12  
1
2
3
Red  
Red  
Red  
Blue  
S11  
T11  
White  
Black  
N
White  
Black  
White  
Black  
MF2  
PE  
MC2  
51C2  
INTERNAL  
PROTECTOR  
52C2  
Red  
Red  
Red  
White  
White  
Black  
Black  
INTERNAL  
PROTECTOR  
Black  
TB3  
51F3  
Red  
Red  
21  
21  
21  
22  
22  
22  
1
2
3
R
S
T
R
S
T
White  
Black  
White  
Black  
MF3  
52F  
51F1  
Red  
INTERNAL  
PROTECTOR  
Red  
White  
Black  
MF1  
F
F(3.15A)  
TB4 11  
TB4 14  
51F1  
TB5  
1
SWITCH BOX  
(FIELD SUPPLY)  
FZ0  
F
30  
30  
(3.15A)  
CZ2-2  
CZ1-2  
RL1  
RL2  
SW1  
23WA  
GL  
High  
Low  
51F2  
51F3  
SW2  
Tr  
63  
63  
AC  
H1  
H2  
CZ1  
CZ2  
220~  
240V  
AC  
CZ1  
CZ2  
24V  
51C1  
1
2
3
4
5
6
7
8
51C2  
1
TB5  
52 52  
C1 C2  
52  
C2  
52  
C1  
52  
TM  
TM  
CZ1  
C2  
(3MIN)  
(3MIN)  
26  
L1  
26  
L2  
52  
C1  
FZ0  
CH2  
CZ2  
52  
3
3
F
FZ1  
FZ1  
TM  
CH1  
2
52  
C1  
FZ0  
(2SEC)  
30  
30  
30  
CZ1-1  
30  
CZ2-1  
CZ1  
CZ2  
2
FZ1  
52  
C2  
C3Z20-1  
C3Z10-1  
C3Z10-2  
C3Z20-2  
9
TB4 12  
TB412  
Caution,  
Symbol  
MC1·2  
Name  
1.To protect each Fan motors and Compressors from abnormal current,  
these Over current relays <51C1,2> , <51F1,2,3> are installed.  
Therefore,do not change factory set value of these Over current relays.  
2.To protect the compressors from frequently "ON-OFF" ,timer <TM> is  
installed. Therefore,do not change factory set value of this timer.  
3.This timer <2> installed so that two compressors may never start at  
the same time. The unit stop if the set value of the timer is changed.  
Compressor motor  
Fan motor (in door)  
Fan motor (out door)  
Contactor (compressor)  
Contactor (fan I/D)  
Terminal block  
MF1  
MF2·3  
52C1·2  
52F  
TB1~5  
CH1·2  
F
Crankcase heater  
Fuse  
Note:  
Tr  
51C1·2  
Transformer  
1.The dotted lines show field wiring.  
Over current relay(compressor)  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
51F1~3 Over current relay (fan I/D,O/D)  
63H1·2  
26L1·2  
TM  
2
High-pressure switch  
Thermostat(freeze protection)  
Timer (anti short cycle)  
Timer  
5.Specification subject to change without notice.  
FZ0·1  
Auxiliary relay (fan)  
CZ1·2  
30CZ1-1,2  
30CZ2-1,2  
<SW1>  
<SW2>  
<GL>  
Auxiliary relay (compressor)  
Auxiliary relay (check)  
Auxiliary relay (check)  
Switch (off)  
Switch (on)  
Lamp (power on)  
<RL1·2> Lamp (check)  
<23WA> Thermostat (room temp.)  
- 30 -  
PR-5, 8, 10YC  
(SPECIAL ORDER : K CONTROL)  
Power supply  
3Phase  
380~415Volt  
50Hertz  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
MC  
INTERNAL  
PR- 5YC ···40A  
PR- 8YC ···50A  
PR-10YC ···60A  
PROTECTOR  
TB1  
L1  
52C  
51C  
Red  
Red  
White  
Black  
Red  
L2  
L3  
White  
Black  
Black  
51F2  
TB2  
1
2
3
1
2
Red  
R
R
N
Blue  
White  
Black  
S1  
S 2  
MF2  
1
2
T
T
PE  
52F  
51F1  
Red  
Red  
DSA  
CN  
1
White  
Black  
MF1  
Blue  
Green/Yellow  
Black  
3
INTERNAL  
PROTECTOR  
F(3.15A)  
TB3 11  
11  
15  
TH2  
30  
IB  
CZ  
51F1  
51F2  
63H  
FZ  
TB4  
A
B
C
D
52F  
51C  
CZ  
FZ  
Tr  
TH5  
CZ  
52C  
CH  
FZ  
52C  
30  
CZ  
R/C  
30  
CZ  
8,10YC ONLY  
TB3 12  
TB3 12  
Caution,  
Name  
Symbol  
MC  
To protect each Fan motors and Compressor from abnormal current,  
these Over current relays<51C>,<51F1,2>are installed.  
Therefore,do not change factory set value of these Over current relays.  
Compressor motor  
Fan motor(indoor)  
Fan motor(outdoor)  
Contactor(compressor)  
Contactor(fan I/D)  
Terminal block  
Crankcase heater  
Fuse  
MF1  
MF2  
52C  
52F  
TB1~4  
CH  
F
Tr  
51C  
51F1,2  
63H  
FZ  
Note:  
1.The dotted lines show field wiring.  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
Transformer  
Over current relay(compressor)  
Over current relay(fanI/D,O/D)  
High-pressure switch  
Auxiliary relay(fan)  
5.Specification subject to change without notice.  
CZ  
30CZ  
IB  
Auxiliary relay(compressor)  
Auxiliary relay(check)  
Indoor board  
TH2  
TH5  
R/C  
DSA  
Thermistor(pipe)  
Thermistor(room temp.)  
Remote controller  
Surge absorber circuit board  
- 31 -  
PR-5, 8, 10YC  
(SPECIAL ORDER : LOW TEMPERATURE)  
CIRCUIT BREAKER  
Power supply  
3Phase  
380~415Volt  
50Hertz  
MC  
(FIELD SUPPLY)  
INTERNAL  
PR - 5YC ···40A  
PR - 8YC ···50A  
PR -10YC ···60A  
PROTECTOR  
TB1  
L1  
51C  
52C  
Red  
White  
Black  
Red  
Red  
L2  
L3  
White  
Black  
Black  
51F2  
TB2  
52F2  
TB2  
1
2
3
Red  
2
2
2
2
2
2
R
1
R
1
R
S
T
R
S
T
Red  
Red  
White  
Black  
N
Blue  
White  
S1  
S 1  
White  
Black  
MF2  
PE  
Black  
T
1
T
1
52F1  
51F1  
51F3  
Red  
Red  
52F3  
52F4  
White  
Black  
MF1  
Black  
Tr1  
INTERNAL  
PROTECTOR  
F(3.15A)  
TB3 11  
11  
51F3  
TB4  
1
SWITCH BOX  
(FIELD SUPPLY)  
15  
14  
F
51F1  
51F2  
63H  
(3.15A)  
RL  
SW1  
FZ1  
GL  
23WA  
TB4  
26D3  
SW2  
FZ  
2
FZ  
3
FZ  
4
Tr2  
FZ  
2
AC  
220~  
AC  
51  
1
C
240V  
24V  
2
3
4
5
52  
F1  
6
26D4  
52  
F2  
52  
F4  
CZ  
FZ2  
CZ  
26L  
3
52  
F3  
FZ0  
TM  
52C  
CH  
52  
C
CZ  
(3MIN)  
FZ3  
FZ1  
30  
CZ  
30  
FZ  
3
CZ  
FZ1  
52C  
FZ0  
TM  
FZ4  
30  
CZ  
7
8,10YC ONLY  
12  
TB3 12  
Caution,  
Symbol  
MC  
Name  
1.To protect each Fan motors and Compressor from abnormal current,  
these Over current relays<51C>,<51F1,2,3>are installed.  
Therefore,do not change factory set value of these Over current relays.  
2.To protect the compressor from frequently "ON-OFF" ,timer<TM>is  
installed. Therefore,do not change factory set value of this timer.  
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
Contactor (compressor)  
Contactor (fan I/D)  
Terminal block  
Crankcase heater  
Fuse  
MF1  
MF2  
52C  
52F1  
TB1~4  
CH  
Note:  
1.The dotted lines show field wiring.  
F
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
Tr1·2  
51C  
51F1,2,3  
63H  
26L  
Transformer  
Over current relay(compressor)  
Over current relay(fanI/D,O/D)  
High-pressure switch  
Thermostat(freeze protection)  
Timer (anti short cycle)  
5.Specification subject to change without notice.  
TM  
FZ0,1 Auxiliary relay (fan)  
CZ  
Auxiliary relay (compressor)  
30CZ  
<SW1>  
Auxiliary relay (check)  
Switch (off)  
<SW2>  
<GL>  
<RL>  
Switch (on)  
Lamp (operation)  
Lamp (check)  
<23WA> Thermostat (room temp.)  
52F2~4  
FZ2~4  
Contactor (fan O/D)  
Auxiliary relay (fan O/D)  
- 32 -  
PR-15, 20YC  
(SPECIAL ORDER : LOW TEMPERATURE)  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
Power supply  
3Phase  
380~415Volt  
50Hertz  
PR -15YC···100A  
PR -20YC···125A  
MC1  
INTERNAL  
PROTECTOR  
52C1  
51C1  
TB1  
L1  
L2  
L3  
Red  
White  
Black  
Red  
Red  
White  
Black  
Black  
TB2  
R11 R11  
51F2  
TB2  
52F2  
Red  
1
2
3
Red  
Red  
R12  
R12  
Red  
White  
Black  
Blue  
N
White  
Black  
White  
Black  
S11 S11  
T11 T11  
S12 S12  
White  
Black  
MF2  
T12  
T12  
PE  
51F4  
MC2  
51C2  
INTERNAL  
PROTECTOR  
52C2  
52F3  
Red  
Red  
Red  
White  
White  
Black  
Black  
INTERNAL  
PROTECTOR  
Black  
52F4  
Tr1  
51F3  
TB3  
TB3  
52F5  
1
2
3
Red  
22  
22  
22  
R
S
T
22  
22  
22  
R
S
T
21  
21  
R
S
T
21  
Red  
R
S
T
Red  
White  
Black  
21  
White  
Black  
White  
Black  
MF3  
21  
21  
51F5  
52F6  
52F  
51F1  
Red  
INTERNAL  
PROTECTOR  
52F7  
Red  
Tr2  
White  
Black  
MF1  
F
F(3.15A)  
TB4 11  
TB5  
1
SWITCH BOX  
(FIELD SUPPLY)  
FZ0  
51F1  
TB4  
11  
F
30  
30  
(3.15A)  
CZ1-2  
CZ2-2  
RL1  
RL2  
SW1  
23WA  
51F4  
51F2  
51F5  
High  
Low  
GL  
26D3  
26D1  
51F3  
63  
SW  
2
FZ  
2
FZ  
2
FZ  
FZ  
5
FZ  
3
FZ  
4
FZ  
6
FZ  
7
Tr  
5
63  
AC  
H1  
H2  
51C2  
1
CZ1  
CZ2  
220 ~  
240V  
AC  
CZ1  
CZ2  
24V  
51C1  
1
2
3
5
6
8
4
7
TB5  
52 52  
C1 C2  
52  
26D4  
26D2  
C2  
52  
52  
C2  
52  
F2  
52  
F4  
52  
F5  
52  
F7  
TM  
TM  
FZ2  
FZ5  
CZ1  
C1  
(3MIN)  
(3MIN)  
26  
L1  
26  
L2  
52  
C1  
FZ0  
52  
F3  
52  
F6  
CZ2  
CH2  
52  
3
3
F
FZ6  
FZ3  
FZ1  
FZ1  
TM  
CH1  
2
FZ  
3
FZ  
6
52  
C1  
FZ0  
(2SEC)  
30  
30  
30  
CZ1-1  
30  
CZ2-1  
CZ1  
2
CZ2  
FZ1  
52  
C2  
FZ4  
FZ7  
30  
30  
C3Z10-1  
C3Z10-2  
10  
CZ2-1  
CZ2-2  
TB4 12  
TB4 12  
Symbol  
Name  
Caution,  
1.To protect each Fan motors and Compressors  
from abnormal current,these Over current relays<51C1,2>,  
<51F1~5>are installed.  
Therefore,do not change factory set value of these Over current relays.  
2.To protect the compressors from frequently "ON-OFF",timer<TM>is  
installed. Therefore,do not change factory set value of this timer.  
3.This timer<2>installed so that two compressors may never start at  
the same time. The unit stop if the set value of the timer is changed.  
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
Contactor (compressor)  
Contactor (fan I/D)  
Terminal block  
Crankcase heater  
Fuse  
MC1·2  
MF1  
MF2·3  
52C1·2  
52F1  
TB1~5  
CH1·2  
F
Tr1~3  
51C1·2  
51F1~5  
63H1·2  
26L1·2  
TM  
Transformer  
Note:  
Over current relay(compressor)  
Over current relay (fan I/D,O/D)  
High-pressure switch  
Thermostat(freeze protection)  
Timer (anti short cycle)  
Timer  
1.The dotted lines show field wiring.  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
2
5.Specification subject to change without notice.  
FZ0·1  
Auxiliary relay (fan)  
Auxiliary relay (compressor)  
Auxiliary relay (check)  
Auxiliary relay (check)  
Switch (off)  
CZ1·2  
30CZ1-1, 2  
30CZ2-1, 2  
<SW1>  
<SW2>  
<GL>  
Switch (on)  
Lamp (operation)  
<RL1·2>  
Lamp (check)  
<23WA>  
26D1~4  
52F2~7  
Thermostat (room temp.)  
Thermostat (ambiemt temp.)  
Contactor (fan O/D)  
Auxiliary relay (fan O/D)  
FZ2~7  
- 33 -  
PR-5, 8, 10YC  
(SPECIAL ORDER : K CONTROL & LOW TEMPERATURE)  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
PR - 5YC ···40A  
PR - 8YC ···50A  
PR -10YC ···60A  
Power supply  
3Phase  
380~415Volt  
50Hertz  
MC  
INTERNAL  
PROTECTOR  
TB1  
52C  
51C  
L1  
Red  
Red  
White  
Red  
L2  
L3  
White  
Black  
Black  
Black  
51F2  
TB2  
TB2  
1
2
3
52F2  
R
S
T
R
S
T
R
R2  
S 2  
T2  
1
1
1
1
1
1
2
Red  
Red  
Red  
Blue  
N
S 2  
T2  
White  
Black  
White  
Black  
MF2  
White  
Black  
PE  
52F1  
51F1  
51F3  
Red  
Red  
52F3  
DSA  
CN  
1
White  
Black  
MF1  
Blue  
Green/Yellow  
Black  
3
52F4  
Tr1  
INTERNAL  
PROTECTOR  
F(3.15A)  
TB3 11  
11  
TH2  
51F3  
30  
15  
14  
IB  
CZ  
51F1  
FZ1  
51F2  
63H  
51C  
26D3  
FZ  
2
FZ  
2
FZ  
3
FZ  
4
A
B
C
D
TB4  
52  
F1  
FZ1  
CZ  
Tr2  
26D4  
52  
F2  
52  
F4  
FZ2  
TH5  
52  
F3  
CZ  
52C  
CH  
FZ1  
FZ3  
52C  
30  
FZ  
3
CZ  
R/C  
30  
CZ  
FZ4  
8,10YC ONLY  
12  
TB3 12  
Caution,  
Symbol  
MC  
MF1  
MF2  
52C  
52F1  
TB1~4  
CH  
Name  
To protect each Fan motors and Compressor from abnormal current,  
these Over current relays<51C>,<51F1,2,3>are installed.  
Therefore,do not change factory set value of these Over current relays.  
Compressor motor  
Fan motor(indoor)  
Fan motor(outdoor)  
Contactor(compressor)  
Contactor(fan I/D)  
Terminal block  
Crankcase heater  
Fuse  
Note:  
1.The dotted lines show field wiring.  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
F
Tr1·2  
51C  
51F1,2,3  
63H  
FZ1  
CZ  
Transformer  
(compressor)  
Over current relay  
5.Specification subject to change without notice.  
Over current relay(fanI/D,O/D)  
High-pressure switch  
Auxiliary relay(fan)  
Auxiliary relay(compressor)  
Auxiliary relay(check)  
Indoor board  
30CZ  
IB  
TH2  
52F2~4  
FZ2~4  
Thermistor(pipe)  
Contactor(fan O/D)  
Auxiliary relay(fan O/D)  
Thermistor(room temp)  
Remote controller  
Surge absorber circuit board  
TH5  
R/C  
DSA  
- 34 -  
PRH-5, 8, 10YA  
PRH-5, 8, 10YA-L (STANDARD)  
CIRCUIT BREAKER  
Power Supply  
3Phase  
(FIELD SUPPLY)  
PRH- 5YA,  
PRH- 5YA-L  
PRH- 8YA,  
···40A  
380~415Volt  
50Hertz  
···50A  
···60A  
PRH- 8YA-L  
PRH-10YA,  
TB1  
51C  
PRH-10YA-L  
52C  
INTERNAL  
MC  
L1  
L2  
L3  
RED  
RED  
PROTECTOR  
RED  
WHITE  
WHITE  
BLACK  
WHITE  
BLACK  
BLACK  
TB2  
RED  
51F2  
TB2  
X1  
1
2
3
RED  
R1  
RED  
R2  
S2  
T2  
MF2  
N
BLUE  
WHITE  
BLACK  
WHITE  
BLACK  
WHITE  
BLACK  
S1  
T1  
PE  
52F  
51F1  
RED  
RED  
WHITE  
BLACK  
MF1  
F
INTERNAL  
F
(3.15A)  
PROTECTOR  
TB3  
11  
11  
TB4  
1
SWITCH BOX  
(FIELD SUPPLY)  
15  
HZ  
HZ  
13  
51F1  
F
SW2  
14  
SW1  
(3.15A)  
COOL  
C
HEAT  
GL  
RL  
51F2  
63H  
FZ1  
52C  
Tr  
X1  
H
SW3  
26  
D2  
23  
WA  
C
51  
1
AC  
AC  
24V  
21  
S4  
220~  
240V  
3
2
4
5
6
7
TB4  
26L  
3
CZ  
TM  
CZ  
CH  
52F  
CZ  
HZ  
FZ0  
26  
D1  
X2  
FZ1  
52C  
8,10YA,  
YA-L  
ONLY  
X1  
X2  
(3MIN)  
30  
CZ  
30  
CZ  
TM  
FZ0  
FZ1  
30  
CZ  
8
52C  
12 TB3  
TB3  
12  
Caution,  
Symbol  
Name  
1.To protect each Fan motors and Compressors from abnormal current,  
these Over current relays<51C>,<51F1,2>are installed.  
Therefore,do not change factory set value of these Over current relays.  
2.To protect the compressor from frequently "ON-OFF" ,timer<TM>is  
installed. Therefore,do not change factory set value of this timer.  
MC  
MF1  
MF2  
52C  
52F  
TB1~4  
CH  
F
Tr  
51C  
51F1, 2  
63H  
Compressor motor  
Fan motor (in door)  
Fan motor (out door)  
Contactor (compressor)  
Contactor (fan I/D)  
Terminal block  
Crankcase heater  
Fuse  
Note:  
1.The dotted lines show field wiring.  
Transformer  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
Over current relay(compressor)  
Over current relay (fan I/D,O/D)  
High-pressure switch  
Thermostat(freeze protection)  
Thermostat (defrost)  
5.Specification subject to change without notice.  
26L  
26D1·2  
TM  
Timer (anti short cycle)  
4-Way valve  
Auxiliary relay (fan)  
21S4  
FZ0·1  
CZ  
HZ  
30CZ  
X1·2  
<SW1>  
<SW2>  
<SW3>  
<GL>  
<RL>  
Auxiliary relay (compressor)  
Auxiliary relay (heater)  
Auxiliary relay (check)  
Auxiliary relay (defrost)  
Switch (operation mode)  
Switch (off)  
Switch (on)  
Lamp (operation)  
Lamp (check)  
Thermostat (room temp.)  
<23WA>  
- 35 -  
PRH-15, 20YA  
PRH-15, 20YA-L (STANDARD)  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
PRH-15YA  
PRH-15YA-L  
PRH-20YA  
Power supply  
3Phase  
380~415Volt  
50Herts  
···100A  
MC1  
···125A  
INTERNAL  
PRH-20YA-L  
PROTECTOR  
52C1  
51C1  
TB1  
L1  
L2  
L3  
Red  
White  
Red  
Red  
White  
Black  
Black  
Black  
TB2  
R12  
51F2  
X1  
1
2
3
Red  
Red  
R11  
S11  
T11  
Red  
Blue  
N
White  
Black  
White  
Black  
S12  
T12  
White  
Black  
MF2  
MC2  
51C2  
INTERNAL  
PROTECTOR  
52C2  
Red  
Red  
Red  
White  
White  
Black  
Black  
INTERNAL  
PROTECTOR  
Black  
TB3  
51F3  
X2  
1
2
3
21  
21  
21  
22  
22  
22  
R
S
T
R
S
T
Red  
Red  
White  
Black  
White  
Black  
MF3  
52F  
51F1  
Red  
INTERNAL  
PROTECTOR  
Red  
White  
Black  
MF1  
F
F(3.15A)  
TB4 11  
TB5  
1
SWITCH BOX  
(FIELD SUPPLY)  
FZ0  
51F1  
51F2  
HZ  
HZ  
14  
F
30  
30  
SW1  
C
(3.15A)  
CZ2-2  
CZ1-2  
HEAT  
COOL  
RL1  
RL2  
SW2  
TB4 13  
GL  
C
H
H
51F3  
SW3  
High  
Low  
3
Tr  
X1 X2  
X2  
63  
63  
23WA  
AC  
H1  
H2  
CZ1  
CZ2  
220~  
240V  
AC  
CZ1  
CZ2  
24V  
51  
C1  
51  
C2  
2
4
5
6
7
8
9
26  
TB5  
52 52  
C1 C2  
21  
52  
C2  
D4  
26  
S41  
1
1
D3  
52  
C1  
52  
TM  
TM  
21  
CZ1  
HZ  
C2  
(3MIN)  
(3MIN)  
26  
L1  
26  
L2  
S42  
26  
52  
C1  
FZ0  
CH2  
CZ2  
X4  
52  
F
26  
D2  
X3  
3
3
D1  
FZ1  
FZ1  
TM  
CH1  
2
X2  
52  
C1  
FZ0  
(2SEC)  
30  
30  
X1  
30  
CZ1-1  
30  
CZ2-1  
CZ1  
CZ2  
2
X4  
FZ1  
X3  
52  
C2  
C3Z20-1  
C3Z10-1  
C3Z10-2  
C3Z20-2  
10  
TB4 12  
TB4 12  
Caution,  
Symbol  
MC1·2  
Name  
1.To protect each Fan motors and Compressors from abnormal current,  
these Over current relays<51C1,2>,<51F1,2,3>are installed.  
Compressor motor  
Fan motor (in door)  
Fan motor (out door)  
Contactor (compressor)  
Contactor (fan I/D)  
Terminal block  
Crankcase heater  
Fuse  
MF1  
MF2·3  
52C1·2  
52F  
TB1~5  
CH1·2  
F
Therefore,do not change factory set value of these Over current relays.  
2.To protect the compressors from frequently "ON-OFF" ,timer<TM>is  
installed. Therefore,do not change factory set value of this timer.  
3.This timer<2>installed so that two compressors may never start at  
the same time. The unit stop if the set value of the timer is changed.  
Note:  
Tr  
Transformer  
1.The dotted lines show field wiring.  
51C1·2  
51F1~3  
63H1·2  
26L1·2  
26D1~4  
TM  
Over current relay(compressor)  
Over current relay (fan I/D,O/D)  
High-pressure switch  
Thermostat(freeze protection)  
Thermostat (defrost)  
Timer (anti short cycle)  
Timer  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
5.Specification subject to change without notice.  
2
21S41·42  
4-Way valve  
FZ0·1  
CZ1·2  
HZ  
30CZ1-1,2  
30CZ2-1,2  
X1~4  
<SW1>  
<SW2>  
<SW3>  
<GL>  
Auxiliary relay (fan)  
Auxiliary relay (compressor)  
Auxiliary relay (heater)  
Auxiliary relay (check)  
Auxiliary relay (check)  
Auxiliary relay (defrost)  
Switch (operation mode)  
Switch (off)  
Switch (on)  
Lamp (operation)  
<RL1·2>  
<23WA>  
Lamp (check)  
Thermostat (room temp.)  
- 36 -  
PRH-5, 8, 10YA  
PRH-5, 8, 10YA-L  
(SPECIAL ORDER : K CONTROL)  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
PRH- 5YA,  
···40A  
Power supply  
3Phase  
380~415Volt  
50Herts  
PRH- 5YA-L  
PRH- 8YA,  
PRH- 8YA-L···50A  
PRH-10YA,  
PRH-10YA-L···60A  
MC  
INTERNAL  
PROTECTOR  
TB1  
L1  
52C  
51C  
Red  
Red  
White  
Black  
Red  
L2  
L3  
White  
Black  
Black  
51F2  
TB2  
X1  
1
2
3
1
2
Red  
R
R
N
Blue  
White  
Black  
S1  
S 2  
MF2  
1
2
T
T
PE  
52F  
51F1  
Red  
Red  
DSA  
White  
Black  
CN  
MF1  
Blue  
Green/Yellow  
Black  
1
3
INTERNAL  
PROTECTOR  
F(3.15A)  
TB3 11  
11  
15  
TH2  
HZ  
HZ  
14  
30  
IB  
CZ  
51F1  
51F2  
13  
FZ  
X1  
63H  
51  
TB4  
A
B
C
D
21  
S4  
52F  
HZ  
CZ  
FZ  
CM  
26  
D2  
Tr  
TH5  
26  
D1  
X2  
CZ  
52C  
CH  
FZ  
X1  
52C  
30  
X2  
CZ  
R/C  
30  
CZ  
8,10YA,YA-L ONLY  
TB3 12  
TB3 12  
Caution,  
Name  
Symbol  
MC  
To protect each Fan motors and Compressor from abnormal current,  
these Over current relays<51C>,<51F1,2>are installed.  
Therefore,do not change factory set value of these Over current  
relays.  
Compressor motor  
Fan motor(indoor)  
Fan motor(outdoor)  
Contactor(compressor)  
Contactor(fan I/D)  
Terminal block  
Crankcase heater  
Fuse  
MF1  
MF2  
52C  
52F  
TB1~4  
CH  
Note:  
1.The dotted lines show field wiring.  
F
Tr  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
Transformer  
51C  
51F1,2  
63H  
26D1·2  
21S4  
FZ  
Over current relay(compressor)  
Over current relay(fanI/D,O/D)  
High-pressure switch  
Thermostat(defrost)  
5.Specification subject to change without notice.  
4-Way valve  
Auxiliary relay(fan)  
CZ  
HZ  
30CZ  
X1·2  
IB  
Auxiliary relay(compressor)  
Auxiliary relay(heater)  
Auxiliary relay(check)  
Auxiliary relay(defrost)  
Indoor board  
TH2  
TH5  
R/C  
DSA  
Thermistor(pipe)  
Thermistor(room temp.)  
Remote controller  
Surge absorber circuit board  
- 37 -  
PRH-5, 8, 10YA  
PRH-5, 8, 10YA-L  
(SPECIAL ORDER : LOW TEMPERATURE)  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
PRH- 5YA,  
···40A  
Power supply  
3Phase  
PRH- 5YA-L  
MC  
INTERNAL  
PRH- 8YA,  
PRH- 8YA-L  
PRH-10YA,  
···50A  
380~415Volt  
50Herts  
PROTECTOR  
···60A  
TB1  
L1  
51C  
52C  
PRH-10YA-L  
Red  
White  
Black  
Red  
Red  
L2  
L3  
White  
Black  
Black  
51F2  
TB2  
X1  
52F2  
TB2  
1
2
3
2
2
2
2
2
2
R
1
R
1
R
S
T
R
S
T
Red  
Red  
Red  
White  
Black  
N
Blue  
S1  
S 1  
White  
Black  
White  
Black  
MF2  
PE  
T
1
T
1
52F1  
51F1  
51F3  
Red  
Red  
52F3  
52F4  
White  
Black  
MF1  
Black  
Tr1  
INTERNAL  
PROTECTOR  
F(3.15A)  
TB3 11  
11  
51F3  
TB4  
1
SWITCH BOX  
(FIELD SUPPLY)  
HZ  
16  
15  
HZ  
14  
F
51F1  
51F2  
63H  
SW1  
COOL  
TB313  
(3.15A)  
HEAT  
RL  
SW2  
FZ1  
GL  
C
H
26D3  
X1  
SW3  
23WA  
FZ  
2
FZ  
3
FZ  
4
Tr2  
FZ  
2
AC  
21  
S4  
220~  
AC  
240V  
24V  
51  
C
26  
D2  
2
3
4
5
6
7
52  
F1  
26D4  
52  
F2  
52  
F4  
CZ  
FZ2  
TB4  
1
CZ  
HZ  
26  
X2  
26L  
3
52  
F3  
FZ0  
D1  
TM  
52C  
CH  
52  
C
CZ  
(3MIN)  
FZ3  
X1  
FZ1  
30  
CZ  
30  
X2  
FZ  
3
CZ  
FZ1  
52C  
FZ0  
TM  
FZ4  
30  
CZ  
8
8,10YA,  
12  
YA-L ONLY  
TB3 12  
Caution,  
Symbol  
MC  
Name  
1.To protect each Fan motors and Compressor from abnormal current,  
these Over current relays<51C>,<51F1,2,3>are installed.  
Therefore,do not change factory set value of these Over current relays.  
2.To protect the compressor from frequently "ON-OFF",timer<TM>is  
installed. Therefore,do not change factory set value of this timer.  
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
Contactor (compressor)  
Contactor (fan I/D)  
Terminal block  
Crankcase heater  
Fuse  
MF1  
MF2  
52C  
52F1  
TB1~4  
CH  
Note:  
1.The dotted lines show field wiring.  
F
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
Tr1·2  
51C  
51F1,2,3  
63H  
26L  
26D1~4  
TM  
21S4  
Transformer  
Over current relay(compressor)  
Over current relay(fanI/D,O/D)  
High-pressure switch  
Thermostat(freeze protection)  
Thermostat (defrost)  
5.Specification subject to change without notice.  
Timer (anti short cycle)  
4-Way valve  
FZ0,1 Auxiliary relay (fan)  
CZ  
Auxiliary relay (compressor)  
HZ  
Auxiliary relay (heater)  
Auxiliary relay (check)  
Auxiliary relay (defrost)  
Switch (operatin mode)  
Switch (off)  
30CZ  
X1·2  
<SW1>  
<SW2>  
<SW3>  
<GL>  
Switch (on)  
Lamp (operation)  
<RL>  
Lamp (check)  
<23WA>  
52F2~4  
FZ2~4  
Thermostat (room temp.)  
Contactor (fan O/D)  
Auxiliary relay (fan O/D)  
- 38 -  
PRH-15, 20YA  
PRH-15, 20YA-L  
(SPECIAL ORDER : LOW TEMPERATURE)  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
PRH-15YA  
Power supply  
3Phase  
380~415Volt  
50Herts  
···100A  
PRH-15YA-L  
PRH-20YA  
MC1  
INTERNAL  
···125A  
PROTECTOR  
PRH-20YA -L  
52C1  
51C1  
TB1  
L1  
L2  
L3  
Red  
White  
Black  
Red  
Red  
White  
Black  
Black  
TB2  
R11 R11  
51F2  
TB2  
X1  
52F2  
1
2
3
Red  
R12  
S12 S12  
T12 T12  
R12  
Red  
Red  
Red  
Blue  
N
White  
Black  
S11 S11  
T11 T11  
White  
Black  
White  
Black  
White  
Black  
MF2  
PE  
51F4  
MC2  
51C2  
INTERNAL  
PROTECTOR  
52C2  
52F3  
Red  
Red  
Red  
White  
White  
Black  
Black  
INTERNAL  
PROTECTOR  
Black  
52F4  
Tr1  
51F3  
TB3  
TB3  
52F5  
X2  
1
2
3
22  
22  
22  
R
S
T
22  
22  
22  
R
S
T
21  
21  
R
S
T
21  
Red  
R
S
T
Red  
Red  
21  
White  
Black  
White  
Black  
White  
Black  
MF3  
21  
21  
51F5  
52F6  
52F  
51F1  
Red  
INTERNAL  
PROTECTOR  
52F7  
Red  
Tr2  
White  
Black  
MF1  
F
F(3.15A)  
TB4 11  
TB5  
1
SWITCH BOX  
(FIELD SUPPLY)  
HZ  
18  
FZ0  
51F1  
HZ  
TB4 14  
F
30  
30  
SW1  
C
(3.15A)  
CZ1-2  
CZ2-2  
HEAT  
COOL  
RL1  
RL2  
SW2  
TB4 13  
51F4  
51F2  
51F5  
GL  
26D3  
FZ  
26D1  
C
H
H
51F3  
63  
SW3  
FZ  
FZ  
FZ  
5
FZ  
3
FZ  
4
FZ  
6
FZ  
7
High  
Low  
Tr  
X1 X2  
X2  
2
2
5
63  
23WA  
AC  
H1  
H2  
CZ1  
CZ2  
220~  
240V  
AC  
CZ1  
CZ2  
24V  
51  
51  
2
3
4
5
6
7
8
9
C1  
C2  
26  
TB5  
52 52  
C1 C2  
21  
52  
C2  
D4  
26  
26D4  
S41  
26D2  
1
1
D3  
52  
52  
C2  
52  
F2  
52  
F4  
52  
F5  
52  
F7  
TM  
TM  
FZ2  
FZ5  
21  
S42  
CZ1  
HZ  
C1  
(3MIN)  
(3MIN)  
26  
L1  
26  
L2  
52  
C1  
FZ0  
26  
D2  
52  
F3  
52  
F6  
CH2  
CZ2  
X4  
52  
F
26  
X3  
3
3
D1  
FZ6  
FZ3  
FZ1  
FZ1  
TM  
CH1  
2
FZ  
FZ  
6
X2  
52  
C1  
FZ0  
(2SEC)  
3
30  
30  
X1  
30  
CZ1-1  
30  
CZ2-1  
CZ1  
2
CZ2  
X4  
FZ1  
X3  
52  
C2  
FZ4  
FZ7  
30  
30  
C3Z10-1  
C3Z10-2  
10  
CZ2-1  
CZ2-2  
TB4 12  
TB4 12  
Symbol  
Name  
Caution,  
1.To protect each Fan motors and Compressors  
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
Contactor (compressor)  
Contactor (fan I/D)  
Terminal block  
Crankcase heater  
Fuse  
MC1·2  
MF1  
MF2·3  
52C1·2  
52F1  
TB1~5  
CH1·2  
F
from abnormal current,these Over current relays<51C1,2>,  
<51F1~5>are installed.  
Therefore,do not change factory set value of these Over current relays.  
2.To protect the compressors from frequently "ON-OFF",timer<TM>is  
installed. Therefore,do not change factory set value of this timer.  
3.This timer<2>installed so that two compressors may never start at  
the same time. The unit stop if the set value of the timer is changed.  
Tr1~3  
Transformer  
Note:  
51C1·2  
51F1~5  
63H1·2  
26L1·2  
26D1~4  
TM  
Over current relay(compressor)  
Over current relay (fan I/D,O/D)  
High-pressure switch  
Thermostat(freeze protection)  
Thermostat (defrost)  
Timer (anti short cycle)  
Timer  
1.The dotted lines show field wiring.  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
5.Specification subject to change without notice.  
2
4-Way valve  
21S41·42  
FZ0·1  
CZ1·2  
HZ  
30CZ1-1, 2  
30CZ2-1, 2  
X1~4  
<SW1>  
<SW2>  
<SW3>  
<GL>  
Auxiliary relay (fan)  
Auxiliary relay (compressor)  
Auxiliary relay (heater)  
Auxiliary relay (check)  
Auxiliary relay (check)  
Auxiliary relay (defrost)  
Switch (operation mode)  
Switch (off)  
Switch (on)  
Lamp (operation)  
<RL1·2>  
Lamp (check)  
<23WA>  
26D1~4  
52F2~7  
Thermostat (room temp.)  
Thermostat (ambiemt temp.)  
Contactor (fan O/D)  
Auxiliary relay (fan O/D)  
FZ2~7  
- 39 -  
PRH-5, 8, 10YA  
PRH-5, 8, 10YA-L  
(SPECIAL ORDER : K CONTROL & LOW TEMPERATURE)  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
PRH- 5YA,  
···40A  
Power supply  
PRH- 5YA-L  
3Phase  
PRH- 8YA,  
···50A  
380~415Volt  
50Hertz  
PRH- 8YA-L  
PRH- 10YA  
MC  
INTERNAL  
···60A  
PROTECTOR  
PRH-10YA-L  
TB1  
52C  
51C  
L1  
Red  
Red  
White  
Red  
L2  
L3  
White  
Black  
Black  
Black  
51F2  
TB2  
TB2  
X1  
1
2
3
52F2  
R
S
T
R
S
T
R
R2  
S 2  
T2  
1
1
1
1
1
1
2
Red  
Red  
Red  
Blue  
N
S 2  
T2  
White  
Black  
White  
Black  
MF2  
White  
Black  
PE  
52F1  
51F1  
51F3  
Red  
Red  
52F3  
DSA  
White  
Black  
CN  
1
3
MF1  
Blue  
Green/Yellow  
Black  
52F4  
Tr1  
INTERNAL  
PROTECTOR  
F(3.15A)  
TB3 11  
11  
TH2  
51F3  
HZ  
16  
HZ  
30  
15  
14  
IB  
CZ  
TB3 13  
51F1  
FZ1  
51F2  
63H  
26D3  
X1  
FZ  
2
FZ  
FZ  
3
FZ  
4
A
B
C
D
TB4  
2
52  
F1  
21  
S4  
FZ1  
HZ  
CZ  
26  
D2  
Tr2  
51  
C
26D4  
52  
F2  
52  
F4  
FZ2  
TH5  
26  
D1  
X2  
52  
F3  
CZ  
52C  
CH  
FZ1  
FZ3  
X1  
52C  
30  
X2  
FZ  
3
CZ  
R/C  
30  
FZ4  
CZ  
12  
8,10YA,YA-L ONLY  
TB3 12  
Caution,  
Symbol  
MC  
Name  
To protect each Fan motors and Compressor from abnormal current,  
these Over current relays<51C>,<51F1,2,3>are installed.  
Therefore,do not change factory set value of these Over current relays.  
Compressor motor  
Fan motor(indoor)  
Fan motor(outdoor)  
Contactor(compressor)  
Contactor(fan I/D)  
Terminal block  
MF1  
MF2  
52C  
52F1  
TB1~4  
CH  
Note:  
1.The dotted lines show field wiring.  
Crankcase heater  
Fuse  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
F
Tr1·2  
51C  
51F1,2,3  
63H  
26D1~4  
21S4  
FZ1  
CZ  
HZ  
30CZ  
X1·2  
IB  
Transformer  
(compressor)  
Over current relay  
5.Specification subject to change without notice.  
Over current relay(fanI/D,O/D)  
High-pressure switch  
Thermostat(defrost)  
4-Way valve  
Auxiliary relay(fan)  
Auxiliary relay(compressor)  
Auxiliary relay(heater)  
Auxiliary relay(check)  
Auxiliary relay(defrost)  
Indoor board  
TH2  
52F2~4  
FZ2~4  
Thermistor(pipe)  
Contactor(fan O/D)  
Auxiliary relay(fan O/D)  
Thermistor(room temp)  
Remote controller  
Surge absorber circuit board  
TH5  
R/C  
DSA  
- 40 -  
ELECTRICAL OPERATION FLOW CHARTS  
PR-5, 8, 10YC  
START  
POWER ON  
CH ON  
GL ON  
30CZ ON (SELF HOLD)  
NO  
SW2 ON?  
YES  
FZ0,1 ON (SELF HOLD)  
52F ON  
MF1 OPERATE  
YES  
NO  
23WA ON?  
YES  
CZ ON  
TM ON  
NO  
PASS THE 3 MIN.?  
YES  
52C ON  
MC OPERATE  
MF2 OPERATE  
CH OFF  
SAFETY  
NO  
DEVICE OFF?  
YES  
30CZ OFF  
52C OFF  
MC STOP  
MF2 STOP  
RL ON  
CH ON  
SERVICE CALL  
- 41 -  
PRH-5, 8, 10YA  
PRH-5, 8, 10YA-L  
START  
POWER ON  
CH ON  
GL ON  
30CZ ON (SELF HOLD)  
NO  
SW3 ON?  
YES  
FZ0,1 ON (SELF HOLD)  
52F ON  
MF1 OPERATE  
NO  
NO  
SW1 COOL?  
HZ ON  
YES  
21S4 ON  
23WA ON?  
NO  
23WA ON?  
YES  
CZ ON  
YES  
CZ ON  
TM ON  
TM ON  
NO  
PASS THE 3 MIN.?  
YES  
NO  
PASS THE 3 MIN.?  
YES  
52C ON  
MC OPERATE  
MF2 OPERATE  
52C ON  
MC OPERATE  
MF2 OPERATE  
CH OFF  
CH OFF  
SAFETY  
NO  
DEVICE OFF?  
NO  
CONDENSING  
<
TEMP. -12˚C?  
=
YES  
30CZ OFF  
YES  
26D1, 2 ON  
52C OFF  
MC STOP  
MF2 STOP  
X1 ON  
X2 ON (SELF HOLD)  
RL ON  
CH ON  
21S4 OFF  
MF2 STOP  
SERVICE CALL  
NO  
CONDENSING  
<
TEMP. 6˚C?  
=
YES  
26D1, 2 OFF  
X1, 2 OFF  
21S4 ON  
MF2 OPERATE  
- 42 -  
PR-15, 20YC  
START  
POWER ON  
CH1, 2 ON  
GL ON  
30CZ1, 30CZ2 ON (SELF HOLD)  
NO  
SW2 ON?  
YES  
FZ0, FZ1 ON (SELF HOLD)  
52F ON  
MF1 OPERATE  
YES  
NO  
23WA No.1 ON?  
YES  
CZ1 ON  
TM1 ON  
NO  
PASS THE 3 MIN.?  
YES  
52C1 ON  
MC1 OPERATE  
MF2 OPERATE  
CH1 OFF  
NO  
23WA No.2 ON?  
YES  
CZ2 ON  
TM2 ON  
NO  
PASS THE 2 SEC.?  
YES  
52C2 ON  
MC2 OPERATE  
MF3 OPERATE  
CH2 OFF  
NO  
No.2 SAFETY  
DEVICE OFF?  
NO  
No.1 SAFETY  
DEVICE OFF?  
YES  
30CZ2 OFF  
YES  
30CZ1 OFF  
52C2 OFF  
MC2 STOP  
MF3 STOP  
52C1 OFF  
MC1 STOP  
MF2 STOP  
RL2 ON  
RL1 ON  
CH1 ON  
CH2 ON  
SERVICE CALL  
- 43 -  
PRH-15, 20YA  
PRH-15, 20YA-L  
HZ ON  
START  
POWER ON  
21S41, 2 ON  
CH1, 2 ON  
NO  
23WA No.2 ON?  
GL ON  
YES  
CZ1 ON  
30CZ1, 30CZ2 ON (SELF HOLD)  
TM1 ON  
NO  
SW3 ON?  
NO  
NO  
YES  
PASS THE 3 MIN.?  
FZ0, FZ1 ON (SELF HOLD)  
YES  
52F ON  
MF1 OPERATE  
TM2 ON  
NO  
NO  
PASS THE 2 SEC.?  
YES  
SW1 COOL?  
YES  
52C2 ON  
MC2 OPERATE  
MF3 OPERATE  
23WA No.1 ON?  
YES  
CH2 OFF  
CZ1 ON  
TM1 ON  
NO  
23WA No.1 ON?  
YES  
NO  
PASS THE 3 MIN.?  
YES  
52C1 ON  
MC1 OPERATE  
MF2 OPERATE  
52C1 ON  
MC1 OPERATE  
MF2 OPERATE  
CH1 OFF  
CH1 OFF  
NO  
No.1 CONDENSING  
<
TEMP. -12˚C?  
=
NO  
23WA No.2 ON?  
YES  
26D1, 3 ON  
YES  
CZ2 ON  
X1 ON  
NO  
X3 ON (SELF HOLD)  
No.2 CONDENSING  
TEMP. -12˚C?  
=
TM2 ON  
<
21S41 OFF  
MF2 STOP  
YES  
NO  
PASS THE 2 SEC.?  
YES  
26D2, 4 ON  
X2 ON  
NO  
No.1 CONDENSING  
<
X4 ON (SELF HOLD)  
52C2 ON  
MC2 OPERATE  
MF3 OPERATE  
TEMP. 6˚C?  
=
21S42 OFF  
MF3 STOP  
YES  
26D1, 3 OFF  
CH2 OFF  
No.2 SAFETY  
DEVICE OFF?  
NO  
X1, 3 OFF  
NO  
No.2 CONDENSING  
NO  
No.1 SAFETY  
DEVICE OFF?  
<
TEMP. 6˚C?  
=
YES  
21S41 ON  
MF2 OPERATE  
30CZ2 OFF  
YES  
YES  
30CZ1 OFF  
52C2 OFF  
MC2 STOP  
MF3 STOP  
YES  
No.1 DEFROST  
OPERATION?  
52C1 OFF  
MC1 STOP  
MF2 STOP  
NO  
RL2 ON  
21S42 ON  
MF2 OPERATE  
RL1 ON  
CH1 ON  
CH2 ON  
SERVICE CALL  
- 44 -  
REFRIGERANT SCHEMATICS  
PR-5YC  
Condenser  
Evaporator  
ø19.05  
High  
Check  
pressure  
joint  
switch  
ø19.05  
Check  
joint  
Pressure  
gauge  
ø12.7  
Check  
joint  
ø22.2  
Check  
joint  
Compressor  
Capillary  
Tube  
ø12.7  
ø12.7  
Strainer  
Dryer  
: OPTION  
Notes: This schematics shows one refrigerant cycle.  
PR-15,20YC or PRH-15,20YA or PRH-15,20YA-L is  
composed of two refrigerant cycles.  
PR-8, 10, 15, 20YC  
Condenser  
Evaporator  
ø19.05  
High  
pressure  
switch  
Check  
joint  
ø19.05  
Check  
joint  
Pressure  
gauge  
ø12.7  
Check  
joint  
ø22.2  
Check  
joint  
Compressor  
Capillary  
Tube  
ø12.7  
ø12.7  
Strainer  
Dryer  
: OPTION  
- 45 -  
PRH-5YA  
Condenser  
Evaporator  
ø19.05  
High  
pressure  
switch  
4-Way  
valve  
Check  
joint  
Check  
joint  
ø19.05  
Pressure  
gauge  
ø12.7  
Check  
joint  
ø22.2  
Check  
joint  
Compressor  
Capillary  
Tube  
Capillary  
Tube  
ø12.7  
ø12.7  
Strainer  
Check Strainer  
valve  
Dryer  
: OPTION  
Notes: This schematics shows one refrigerant cycle.  
PR-15,20YC or PRH-15,20YA or PRH-15,20YA-L is  
composed of two refrigerant cycles.  
PRH-8, 10, 15, 20YA  
Condenser  
Evaporator  
8, 15YA: ø22.0  
10, 20YA: ø25.4  
High  
pressure  
switch  
4-Way  
valve  
Check  
joint  
8, 15YA: ø22.0  
10, 20YA: ø25.4  
Pressure  
gauge  
Muffler  
ø15.88  
ø15.88  
Check  
joint  
Check  
joint  
ø25.4  
Check  
joint  
Compressor  
Capillary  
Tube  
Capillary  
Tube  
ø12.7  
ø12.7  
Strainer  
Check Strainer  
valve  
Dryer  
: OPTION  
- 46 -  
PRH-5YA-L  
Condenser  
Evaporator  
ø19.05  
High  
pressure  
switch  
4-Way  
valve  
Check  
joint  
Check  
joint  
ø19.05  
Pressure  
gauge  
ø12.7  
Check  
joint  
ø22.2  
Check  
joint  
Accumulator  
Compressor  
Capillary  
Tube  
Capillary  
Tube  
ø12.7  
ø12.7  
Strainer  
Check Strainer  
valve  
Dryer  
: OPTION  
Notes: This schematics shows one refrigerant cycle.  
PR-15,20YC or PRH-15,20YA or PRH-15,20YA-L is  
composed of two refrigerant cycles.  
PRH-8, 10,15,20YA-L  
Condenser  
Evaporator  
8,15YA-L: ø22.0  
10,20YA-L: ø25.4  
High  
pressure  
switch  
4-Way  
valve  
Check  
joint  
8,15YA-L: ø22.0  
10,20YA-L: ø25.4  
Pressure  
gauge  
Muffler  
ø15.88  
ø15.88  
Check  
joint  
Check  
joinøt25.4  
Check  
joint  
Accumulator  
Compressor  
Capillary  
Tube  
Capillary  
Tube  
ø12.7  
ø12.7  
Strainer  
Check Strainer  
valve  
Dryer  
: OPTION  
- 47 -  
SAFETY & CONTROL DEVICES  
PR-5YC  
PRH-5YA  
PRH-5YA-L  
PR-8YC  
PRH-8YA  
PRH-8YA-L  
PR-10YC  
PRH-10YA  
PRH-10YA-L  
ITEM  
NO.  
COMPRESSOR OVER CURRENT RELAY  
COMPRESSOR INTERNAL THERMOSTAT  
HIGH PRESSURE SWITCH  
51C  
-
26.0A  
27.5A  
120˚C OFF  
2.94MPa OFF  
-2˚C IN  
31.0A  
110˚C OFF  
130˚C OFF  
63H  
26L  
26D1,2  
51F1  
51F2  
-
FREEZE PROTECTOR  
FROST PROTECTOR (ONLY PRH-YA,PRH-YA-L)  
INDOOR FAN MOTOR OVER CURRENT RELAY  
OUTDOOR FAN MOTOR OVER CURRENT RELAY  
OUTDOOR FAN MOTOR INTERNAL THERMOSTAT  
FUSE (CONTROL CIRCUIT)  
-12˚C IN, 6˚C OUT  
3.2A  
2.3A  
3.6A  
2.0A  
150˚C OFF  
3.15A  
F
FUSE (OPERATION CIRCUIT)  
F
3.15A  
OUTDOOR FAN MOTOR OVER CURRENT RELAY  
(USE THE OPTIONAL PARTS : LOW AMBIENT PARTS)  
51F3  
NO.  
2.0A  
PR-15YC  
PRH-15YA  
PRH-15YA-L  
PR-20YC  
PRH-20YA  
PRH-20YA-L  
ITEM  
COMPRESSOR OVER CURRENT RELAY  
COMPRESSOR INTERNAL THERMOSTAT  
HIGH PRESSURE SWITCH  
51C1,2  
27.5A  
31.0A  
-
63H1,2  
26L1,2  
26D1,2,3,4  
51F1  
51F2,3  
-
120˚C OFF  
130˚C OFF  
2.94MPa OFF  
FREEZE PROTECTOR  
-2˚C IN  
FROST PROTECTOR (ONLY PRH-YA,PRH-YA-L)  
INDOOR FAN MOTOR OVER CURRENT RELAY  
OUTDOOR FAN MOTOR OVER CURRENT RELAY  
OUTDOOR FAN MOTOR INTERNAL THERMOSTAT  
FUSE (CONTROL CIRCUIT)  
-12˚C IN, 6˚COUT  
5.0A  
6.6A  
2.0A  
150˚C OFF  
3.15A  
F
FUSE (OPERATION CIRCUIT)  
F
3.15A  
OUTDOOR FAN MOTOR OVER CURRENT RELAY  
(USE THE OPTIONAL PARTS : LOW AMBIENT PARTS)  
51F4,5  
2.0A  
ACCESSORY AVAILABILITY  
PARTS CODE  
PRH-8YA  
-
MODEL NAME  
DESCRIPTION  
PR-5YC  
PRH-5YA  
-
PRH-5YA-L  
PR-8YC  
PRH-8YA-L  
PR-10YC  
PRH-10YA  
-
PRH-10YA-L  
PR- YC-K  
PRH- YA-K  
PRH- YA-LK  
PR- YC  
-
-
-
-
-
-
-
-
-
-
-
K-Remote controller  
-
-
-
-
-
-
PAC-201LC  
-
PAC-202LC  
-
PAC-203LC  
-
-
PRH- YA  
PRH- YA-L  
PR- YC  
PRH- YA  
PRH- YA-L  
PR- YC  
-
-
PAC-201LC  
-
-
-
PAC-202LC  
-
-
-
PAC-203LC  
-
Lowtemperaturecooling  
Pressuregauge  
Finguard  
-
-
PAC-201LC  
-
-
PAC-202LC  
-
-
PAC-203LC  
PAC001PG  
-
-
PAC002PG  
-
-
PAC003PG  
-
-
-
-
PAC001PG  
-
-
PAC002PG  
-
-
PAC003PG  
-
-
PAC001PG  
-
-
PAC002PG  
-
-
PAC003PG  
PAC101FG  
-
-
PAC102FG  
-
-
PAC103FG  
-
-
PRH- YA  
PRH- YA-L  
-
-
PAC101FG  
-
-
-
PAC102FG  
-
-
-
PAC103FG  
-
PAC101FG  
PAC102FG  
PAC103FG  
PARTS CODE  
DESCRIPTION  
MODEL NAME  
PR-15YC  
PRH-15YA  
PRH-15YA-L  
PR-20YC  
PRH-20YA  
PRH-20YA-L  
PR- YC  
PAC-201LCX2(PCS)  
-
-
PAC-201LCX2(PCS)  
-
-
Lowtemperaturecooling  
PRH- YA  
PRH- YA-L  
PR- YC  
-
-
PAC-201LCX2(PCS)  
-
-
-
PAC-201LCX2(PCS)  
-
-
-
PAC-201LCX2(PCS)  
-
-
PAC-201LCX2(PCS)  
PAC001PGX2(PCS)  
-
PAC001PGX2(PCS)  
-
Pressuregauge  
Finguard  
PRH- YA  
PRH- YA-L  
PR- YC  
PRH- YA  
PRH- YA-L  
-
-
PAC001PGX2(PCS)  
-
-
-
PAC001PGX2(PCS)  
-
-
-
PAC001PGX2(PCS)  
-
-
PAC001PGX2(PCS)  
PAC104FG  
-
-
-
-
PAC105FG  
-
-
PAC104FG  
-
-
-
PAC105FG  
-
PAC104FG  
PAC105FG  
:Factory install  
:Field install  
- 48 -  
PHYSICAL DATA  
[PRODUCT]  
ROOFTOP AIR-COOLED HEATPUMP PACKAGED AIR CONDITIONERS  
Product type  
PR,PRH,PRH-L SERIES  
PR-10YC  
Product number: Cooling type  
PR-5YC  
PR-8YC  
PR-15YC  
PR-20YC  
Product number: Heat pump  
Product number: Heat pump  
PRH-5YA  
PRH-5YA-L  
PRH-8YA  
PRH-10YA  
PRH-10YA-L  
PRH-15YA  
PRH-15YA-L  
PRH-20YA  
PRH-20YA-L  
PRH-8YA-L  
28.1  
23.8  
19.7  
8.3  
Capacity  
kw  
kW  
kW  
kW  
17.6  
16.3  
13  
35.2  
52.8  
46.3  
38.4  
16.8  
0.18  
45.5  
14.4  
70.3  
60.8  
50.2  
22.7  
0.11  
61.2  
19.3  
Coolingcapacity(AS1861)  
29.7  
SensibleCooling capacity(AS1861)  
Cooling power consumption(Input)  
ByPass Factor  
25.3  
5.4  
11.4  
0.19  
15.1  
4.6  
0.24  
23  
0.18  
Heating capacity (AS1861) (Only PRH-YA,PRH-YA-L)  
Heating power consumption (Only PRH-YA,PRH-YA-L)  
kW  
kW  
32  
7
9.6  
[ELECTRICAL]  
Design voltage  
Cycles  
Volts  
Hz  
415  
50  
Phases  
3
Power supply  
Control voltage  
Maximum voltage  
Minimum voltage  
Approx. starting current  
Volts  
Volts  
Volts  
Volts  
Amps  
415  
240/24  
415  
380  
100  
62  
87  
115  
135  
Unit current (Nominal voltage and AS1861  
maximum conditions)  
Amps  
12.8  
20.6  
25.7  
37.9  
50.9  
Fan motorhp  
HP  
Amps  
rpm  
1.0  
1.5  
2
3
4
Fan motorcurrent  
Fan motor speed  
[COMPRESSOR]  
Make  
2.26  
1,400  
2.90  
1,410  
3.28  
4.72  
1,420  
6.06  
COPELAND  
Model  
CRNQ-0500-TFD QR90K1-TFD  
QR12M1-TFD  
QR90K1-TFD  
QR12M1-TFD  
2
Type  
HERMETIC LINE START (RECIPROCATING)  
Quantity  
1
1
1
2
Nominalmotorhp  
Locked rotor current  
Normalrun current(AS1861)  
Swept volume  
HP  
Amps  
Amps  
cc/rev  
mm  
5
7.5  
10  
2
7.5  
2
10  
59.5  
7.65  
101.92  
49.78  
26.19  
83.4  
11.7  
177.45  
95.2  
15.62  
221.8  
83.4  
95.2  
2  
11.74  
2
15.22  
2
177.45  
2
221.8  
Bore  
55.58  
4
Stroke  
mm  
18.29  
22.86  
2,900  
18.29  
22.86  
Speed  
rpm  
Numberof cylinders  
Oil charge  
2
ml  
2,070  
3,250  
23,250  
Type of oil  
Calumet R015 or Witco 3GS  
70  
watts  
40  
270  
Crankcase heater  
[REFRIGERATION SYSTEM]  
Refrigerant  
R22  
5.8  
Refrigerant charge per circuit  
Numberof refrigerant controls  
Refrigerant control  
Reverse cycle valve (Only PRH-YA,PRH-YA-L)  
kg  
3.6  
1
4.6  
1
24.6  
25.8  
1
2
2
Capillary tube  
4-Way valve  
Reverse cycle defrost  
Defrost system (Only PRH-YA,PRH-YA-L)  
[EVAPORATOR]  
Quantity  
1
1
1
2
2
Facearea  
sq.m  
0.53  
3
0.69  
4
20.65  
Rows deep  
3
3
4
Rows high  
26  
26  
26  
30  
30  
Finned length  
Face velocity  
Fins per meter  
Fin materialthickness  
Finmaterial  
mm  
m/s  
800  
1.7  
512  
1,046  
2.4  
2850  
2.0  
2.2  
2.4  
512  
512  
0.12  
473  
2.11  
11  
512  
1.95  
15  
mm  
Aluminium  
1.95  
Fins pitch  
mm  
mm  
mm  
1.95  
10  
1.95  
13  
Tube diameter  
Gauge of copper tube  
Numberof circuits  
9.52  
0.35  
17  
- 49 -  
[PRODUCT]  
ROOFTOP PACKAGE AIR COOLED HEATPUMP AND COOLING ONLY UNITS  
PRH SERIES  
Product type  
Product number : Heat pump  
[INDOOR AIR CIRCUIT]  
Number of blowers  
PRH-5YA  
PRH-8YA  
PRH-10YA  
PRH-15YA  
PRH-20YA  
1
2
2
2
2
Diameterof blowers  
mm  
mm  
253  
393  
282  
Width of blowers  
Blower drive  
182  
Beltdrive  
1.5  
Fan motor output  
Normal fan motor run current  
Air quantity  
kW  
A
0.75  
2.26  
900  
1.1  
2.2  
3.0  
2.90  
1,400  
3.28  
4.72  
2,800  
6.06  
3,160  
L/s  
1,660  
Externalstatic pressure  
Pa  
100  
200  
Supply air dimensions(h  
Return air dimensions(h  
[CONDENSER]  
Quantity  
w)  
mm mm  
300 850  
410 900  
300 1,150  
410 1,200  
428 1,820  
464 1,879  
w)  
mm mm  
1
1.3  
3
1
1.12  
3
1
1.46  
3
2
2
21.32  
3
Facearea  
sq.m  
21.07  
Rows deep  
3
Rows high  
30  
23  
30  
30  
37  
Finned length  
Face velocity  
mm  
m/s  
1,700  
1.2  
473  
1,920  
21,400  
2.8  
2.1  
473  
0.12  
2.9  
2.3  
Fins per meter  
Fin material thickness  
Fin material  
473  
473  
473  
mm  
Aluminium  
Fins pitch  
mm  
mm  
mm  
2.11  
11  
2.11  
2.11  
9.52  
0.35  
15  
2.11  
2.11  
Tube diameter  
Gauge of copper tube  
Numberof circuits  
11  
1
11  
2
14  
2
[OUTDOOR AIR CIRCUIT]  
Number of fans  
1
600  
-
1
Diameter of fans  
mm  
mm  
800  
645  
Pitch of fans  
Fan drive  
-
-
990  
Direct drive  
Fan motor output  
Quantity  
kw  
0.15  
1
0.35  
1
0.35  
1
20.35  
2
20.35  
2
Normal fan motor run current  
Fan motor speed  
Amps  
rpm  
0.6  
650  
1.3  
1.3  
21.3  
21.3  
Air quantity  
L/s  
1,583  
3,083  
1,300  
23,083  
[ENCLOSURE AND FRAME]  
height  
mm  
mm  
mm  
1,000  
1,600  
1,200  
1,990  
1,840  
Dimension  
Color  
width  
depth  
1,000  
Munsell 5Y8/1  
Panel thickness  
mm  
mm  
1.2  
Condensate drain size  
25.4  
Weight  
kg  
299  
73  
393  
75  
413  
75  
698  
79  
729  
79  
Sound power level  
Sound pressure level  
dbA  
dbA  
62  
64  
64  
68  
68  
- 50 -  
INSTALLATION  
All series of air conditioners are designed for outdoor installations and are to be placed on a slab or  
rooftop, however if the air conditioner is to be installed in a plant room application, please contact your  
equipment supplier prior to installation.  
Access for both service and installation must be provided to the compressors, control wiring and fans as  
shown below.  
1.Clearances  
(1) Care must be taken to prevent recirculation of  
the condenser air. To stabilize compressor  
condensing pressures it is recommended that  
wherever possible the condenser air inlet side  
be faced away from prevailing winds.  
(2) For rooftop installation, the type of mounting  
base depends on the roof construction. A built-  
up roof may not support the weight of the unit  
and so it may be necessary to support the unit  
by adding structural members below it.  
(3) The units are equipped with hoisting  
plates for rigging and hoisting of the unit.  
The hoisting plates are located in the base  
of the unit.  
When hoisting the unit with a crane,  
spreader bars must be used to prevent  
damage to side panels by the supporting  
cables.  
PR-15,20YC  
PRH-15,20YA  
PRH-15,20YA-L  
PR-5 10YC  
PRH-5~10YA  
PRH-5~10YA-L  
300mm(min. clearance)  
300mm(min. clearance)  
Condenser inlet  
1,000mm(min. clearance)  
Evaporator coil service  
Condenser inlet  
700mm(min. clearance)  
Electrical  
control circuit  
1,000mm(min. clearance)  
and compressor  
Evaporator coil service  
service  
Condenser inlet  
300mm(min. clearance)  
1,000mm(min. clearance)  
Evaporator coil service  
1,500mm(min. clearance)  
Condenser outlet  
1,500mm(min. clearance)  
Condenser outlet  
2.Roof Mounting  
(1) The figure shows the use of the roof curb available  
for mounting these units.  
(2) The curb should be sealed and fixed to the roof by  
weather stripping. A suggested means of sealing  
the unit and roof curb is shown below.  
4-ø15roof mounting holes  
6-ø15  
Roof curb  
Unit mounting holes  
Unit  
Seal with tar  
Roof deck  
Roof curb  
- 51 -  
3.Duct Work  
PRH unit  
Vertical air  
plenum  
(1) All series units are equipped with horizontal  
supply and return air openings. Duct connection to  
the unit should be made with duct flanges and  
secured directly to the air openings with flexible  
duct connectors to avoid normal noise transmission.  
Plenum  
divider  
Insulation  
Roof curb  
(2) For vertical air supply, a field supply plenum should  
be used.  
The figure below shows the recommended method  
for duct connection.  
Roof curb  
Duct  
(3) To prevent air leakage, all duct seams should be  
taped.  
Roof line  
Duct  
Singleduct  
divider  
Ducts run in air spaces that are not air-conditioned  
must be insulated and provided with a vapor barrier.  
Ducts exposed to the outside must be  
weatherproofed. For quiet operation, we  
recommend that the insulation on the supply duct  
be placed inside, lining the duct.  
Duct connection with a vertical air plenum  
(4) Where ducts from the outside enter a building, the  
duct openings in the building should be sealed with  
weather stripping to prevent rain, duct, sand,etc.  
from entering the building.  
(5) Correctly sized filters must be fitted and there is no  
provision within the unit, however the filters may be  
installed in the return air.  
4.Drain piping  
(1) A 1 FPT condensate drain fitting is provided. The  
drain pipe can be led out at the right or left side.  
Under standard specifications, it is led out at the left  
side and the right side is covered.  
>
A 70mm  
=
>
B 2C  
Drain piping  
=
>
C 2XE.S.P  
=
(2) The drain pipe must be provided with a trap on the  
outside of the unit and also installed at an incline for  
proper drainage, as shown below.  
The drain pipe  
should extend  
below this level.  
Drain trap  
Note:ESP=External Static Pressure  
(3) To prevent condensate formation and leakage,  
provide the drain pipe with insulation to safeguard  
against sweating.  
Drain trap for condensate  
(4) Upon completion of the piping work, check that there  
is no leakage and that the water drains off properly.  
- 52 -  
5.Electrical Wiring  
Remove the panel on the right side (PR,PRH-5 10) or the rear side (PR,PRH-15,20) of the unit and  
connect the units power supply wiring to the proper terminals in the control box, as shown below.  
PR-5YC  
PRH-5YA  
PRH-5YA-L  
PR-8YC  
PRH-8YA  
PRH-8YA-L  
PR-10YC  
PRH-10YA  
PRH-10YA-L  
PR-15YC  
PRH-15YA  
PRH-15YA-L  
PR-20YC  
PRH-20YA  
PRH-20YA-L  
MODEL  
INDOOR FAN MOTOR OUTPUT <kW>  
2
0.75  
1.1  
1.1  
1.5  
1.5  
2.2  
2.2  
3.0  
3.0  
4.0  
<mm  
mm  
>
>
5.5  
5.5  
40  
5.5  
5.5  
50  
8
8
22  
22  
22  
22  
POWER SUPPLY  
EARTH  
WIRING  
2
<
< A >  
60  
100  
100  
MAIN SWITCH  
Std.  
Control box  
Terminal block  
Terminal block  
Control box  
power supply  
power supply  
Wiring for PR,PRH-15,20(rear view)  
Wiring for PR,PRH-5 10(right side view)  
TN-NET SYSTEM (For European models only)  
L1  
L2  
L3  
N
PE  
Note:  
All electrical wiring must be comply with local electrical authority regulations.  
6.Final Checks  
After having installed the unit, check that:  
(1) The unit is fixed securely.  
(2) The unit is installed properly.  
(3) The drain pipe is provided with a drain trap.  
(4) The electrical wiring has been connected correctly and the terminal screws have been properly  
tightened.  
(5) The duct work has been performed correctly.  
7.Trial Operation  
(1) Before turning the unit on, measure the resistance between the terminals of the electrical parts and  
ground with a 500V megger and check that the value is at least 1M. If the measured value is below 1M,  
do not operate the unit.  
(2) Check the operation of the high pressure switch by activating it. Operation should stop when the two leads  
of the outdoor unit fan motor are removed from the contactor and cooling continues for 5~10min.  
(3) Check that the indoor and outdoor fans are rotating in the proper direction.  
(4) After having checked the above points, proceed with a trial operation of the unit.  
- 53 -  
INSTRUCTIONS FOR USE  
1.CHECK POINTS FOR OPERATION  
Check the following points before you operate your air conditioner.  
(1) Check that there is nothing blocking the flow of air from the air outlet into the air inlet.  
Indoor Unit  
Outlet grille  
Inlet grille  
Ceiling  
Ceiling  
Obstacle blocking air inlet  
Obstacle blocking air inlet  
Outdoor Unit  
Obstacle blocking air inlet  
(2) Make sure the air conditioner is properly grounded by checking the ground terminal .  
Ground  
- 54 -  
2.CAUTION FOR USE  
Keep the following points in mind to safeguard against failures and breakdowns.  
(1) This air conditioner does not restart within 3min.  
after shut down.  
3 Minutes  
(These models have a crankcase heater in the  
Shutdown  
Operation  
compressor. If the air conditioner is shut down  
for a short time, please do not turn the power  
switch to OFF, but turn the operation switch to OFF.)  
(2) If the air conditioner is shut down by a power failure,  
set the operation switch to OFF. When the power is  
restored, normal air conditioner operation can be  
resumed.  
(3) Do not stick rods or other objects through the air  
outlet during operation since this may result in  
equipment damage or personal injury.  
3.MAINTENANCE  
For superior performance and lasting durability, please do not forget to conduct  
proper and regular maintenance.  
3.1 Cleaning the Air Filter  
Clean the air filter about once a week with a neutral cleanser and leave it to dry in a shady location. Clean  
more regularly if the air filter gets very dirty.  
If the filter gets blocked, air will not be sucked in properly, and the cooling effect will deteriorate. Failure to  
clean the air filter may result in equipment breakdown or malfunctions.  
3.2 Cleaning panels  
Clean dirt off front panel as follows.  
Fingermarks  
Use a household neutral cleanser such as for  
dishes or vegetables. Moisten a soft cloth with  
Neutral  
Cleanser  
the cleanser, then wipe lightly. Next,wipe three  
or four times with another soft cloth moisten  
Grease  
with water. Finally, wipe off all the remaining  
cleanser with a soft cloth.  
Moisten a soft cloth with the alcohol, then wipe  
off lightly. Isopropyl alcohol is sold at stores as  
reagents in small quantities.  
Adhesive  
Isopropyl  
alcohol  
Note:  
Alcohol is highly combustible. Take extreme  
Paste  
care when handling. Also, do not use paint or  
adhesive thinner.  
3.3 Cleaning the Outdoor Unit Heat Exchanger  
If you use your air conditioner for prolonged periods,  
the outdoor heat exchanger will become dirty, impairing  
its function and reducing air conditioners performance.  
Consult your equipment supplier or air conditioning  
contractor on how to clean the heat exchanger.  
Heat exchanger  
Heat exchanger  
- 55 -  
4. PREPARING FOR OPERATION AFTER PROLONGED SHUTDOWN  
When the usage season starts, proceed with the following before starting operation:  
(1)Clean the air filter.  
(2)Do not use the unit immediately. Turn the main power switch on for a period of 3 hours before restarting  
cooling / heating operation. This allows the compressors to come up to the correct operation temperatures.  
Failure to do this, could cause compressor failure.  
5.PREPARING FOR PROLONGED SHUTDOWN  
After the usage season is over, prepare the air conditioner for later use by:  
(1)Setting the power switch to OFF.  
(2)Consulting your Air conditioning specialist for detailed information.  
6.TROUBLESHOOTING  
If any trouble occurs, turn the operation (start or run) switch off immediately.  
Symptom  
Possible cause  
Power failure.  
Remedy  
Wait for power supply  
recovery.  
Both fan and compressor  
do not run.  
Blown fuse of power  
source switch.  
Contact your  
Air conditioning specialist  
.
Excessively low power  
source voltage.  
Ask your electric power  
company.  
For temperature control,  
• decrease the set  
temperature at cooling.  
• increase the set  
temperature at heating.  
The set temperature of  
thermostat is  
• excessively high for  
cooling.  
• excessively low for  
heating.  
Fan runs but compressor  
does not run.  
Can not be operated as  
it is out of temperature  
control range.  
The room temperature is  
• excessively low for  
cooling.  
• excessively high for  
heating.  
Air outlet and inlet  
are blocked.  
Remove blocking matter.  
Clean it.  
Fan runs but stops  
immediately.  
The filter installed in  
the field is clogged  
with dust.  
Windows and doors are  
being opened.  
Close them.  
Air outlet and inlet  
are blocked.  
Remove blocking matter.  
Runs but without  
cooling/heating.  
For temperature control,  
• decrease the set  
temperature at cooling.  
• increase the set  
temperature at heating.  
The set temperature of  
thermostat is  
• excessively high for  
cooling.  
• excessively low for  
heating.  
Insufficient  
refrigerant charge.  
Contact your  
Air conditioning specialist  
.
Note:  
If the unit does not operate normally after troubleshooting, please contact your local equipment supplier or  
air conditioning contractor.  
- 56 -  
SPECIFICATION GUIDELINES  
Please supply and install a one piece, air to air reverse cycle air conditioning system.  
The system shall be completely assembled, tested and have a complete refrigeration charge ready for  
installation and operation from the factory.  
The system shall operate at outdoor ambient temperatures as high as 46˚C.  
The system shall have a total cooling capacity of  
L/s at ˚C db and ˚C wb entering indoor coil temperature with a  
entering  
the outdoor coil.  
kW or greater with an indoor air quantity of  
˚C temperature  
The system shall have a sensible heat capacity of  
˚C.  
kW or greater with a room db temperature of  
The total heating capacity (without electric element heaters) shall be  
kW or greater at  
˚Cdb,  
˚C wb outdoor air conditions, with  
˚C of indoor air entering indoor coil at ˚C db. One  
kW electric heater element (accessory) shall be furnished.  
The compressors shall be a welded high efficiency hermetic type with internal vibration isolation and be  
equipped with a crankcase heater.  
Compressors shall be protected by a factory installed anti-cycle device and provide a 3 minute delay before  
compressor can restart.  
Coils shall be of non-ferrous construction with mechanically bonded aluminium plate fins. Outdoor coils  
shall be made, of 9.52mm OD, 0.35mm thick seamless copper tubes mechanically bonded to 0.12mm thick  
aluminium plate fins.  
Coils with multiple stage refrigeration systems shall consist of independent circuits. Face area of the coil  
2
shall not be less than  
M . The coil shall be factory pressure and leak tested at 3,233 kPa pressure.  
2
The indoor coil face area shall be not less than  
M .  
Multi-wing propeller type fans shall be fitted at the condenser and shall be dynamically balanced, to ensure  
smooth airflow and shall discharge vertically and be direct driven by a weatherproof three phase squirrel  
cage  
kW induction motor.  
The system shall be factory wired and all electrical wiring must comply with the Local wiring code. (Controls  
and control wiring shall be supplied by the contractor). Compressors and fan motors shall have both internal  
and current sensitive overload devices.  
An automatic defrost control shall be included to accomplish defrosting (only if required) every  
minutes for a period of  
minutes.  
A low voltage transformer (24V) shall be factory installed in the unit for an external control circuit.  
High pressure switch (pre-set) shall be factory installed.  
The enclosure shall be a single, enclosed, weatherproof casing constructed of phosphatised, zinc coated  
steel with acrylic resin primer and ivory white baked enamel finish.  
The unit shall be provided with hoisting plates for rigging and hoisting the unit. The hoisting plates shall be  
located in the base of the unit.  
The unit shall have a 25mm OD male drain connection provided. The drain pipe shall be accessible from  
either the left or right side of the unit. A blanking cap shall be provided to cap the drain outlet not being  
used.  
The duct (field supply) shall be fully insulated with fiber glass insulation to prevent sweating and to minimize  
sound.  
Each unit shall have a drain pan of 1mm thick steel coated with epoxy resin enamel.  
The enclosure shall have openings provided for power connections. Access for both service and installation  
shall be provided to compressors, control wiring, filters, electric heaters (when fitted) and fans.  
Side panels and top panels shall be removable for easy service access.  
The unit maximum dimensions shall be : height:  
mm, width:  
mm and depth:  
mm.  
Due to continuous product development, these guidelines are subject to change.  
- 57 -  
MEMO  
- 58 -  
DATA BOOK PR,PRH  
MITSUBISHI ELECTRIC CORPORATION  
HEAD OFFICE DENKI BLDG., MARUNOUCHI,TOKYO 100,TELEX J24532 CABLE MELCO TOKYO  
New publication effective Jan. 1999.  
Specifications subject to change without notice.  
Issuued in January. 1999 MEE98K036  
Printed in Japan.  

Nokia Extra Power Dc 11 User Manual
Panasonic Hq 2051th User Manual
Samsung Aqv18j User Manual
Sanyo Rcs Sh80ug User Manual
Sharp Af 08erl User Manual
Sharp Afs80fx User Manual
Soleus Air Air Conditioner Gm Ttw 12ese User Manual
Sony Bcg 34hue User Manual
Universal Power Group Consumer Battery Solutions User Manual
Xerox All In One Printer Workcenter M20 User Manual