Xantrex Technology Power Supply PV 225208 User Manual

OPERATION and MAINTENANCE  
MANUAL  
for  
MODEL PV-225208  
225 kW Grid-Tied Photovoltaic Inverter  
Document #151811  
Revision C November 26, 2003  
IMPORTANT SAFETY INSTRUCTIONS  
SAVE THESE INSTRUCTIONS - THIS MANUAL CONTAINS IMPORTANT INSTRUC-  
TIONS FOR XANTREX TECHNOLOGY MODEL PV-225208 GRID TIED PHOTOVOLTAIC  
INVERTER THAT SHALL BE FOLLOWED DURING INSTALLATION AND MAINTENANCE  
OF THE PV-225208.  
Xantrex Technology Inc.  
161-G SOUTH VASCO ROAD  
Livermore, CA 94550  
(925) 245-5400  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 1  
PRODUCT DESCRIPTION  
INTRODUCTION  
The Xantrex Technology Model PV-225208 is a current following grid tied photovoltaic inverter, utilizing  
state-of-the-art IPM (Intelligent Power Module), insulated gate bi-polar transistors (IGBT’s) and gate drive  
circuits to allow interface of a photovoltaic array with a utility grid. The PV-225208 consists of an inverter  
bridge, photovoltaic controller, and associated control electronics. The PV-225208 control software provides  
for complete overall system control with a variety of protection and safety features.  
MAJOR COMPONENTS  
The major components of the PV-225208 are identified in Figure 1-1. Control components are identified in  
Figure 1-2. For specific control components see Drawing No. 151808 located in Section 7 (Appendix).  
Main Enclosure  
This enclosure is NEMA-3R rated. The PV-225208 main enclosure contains the power electronic inverter  
bridge, electrical and electromechanical control components, power supplies, system sensing circuits, and the  
PV-225208 embedded control unit.Also found within the main enclosure are some of the system protection  
devices (sense and control power fuses).  
Figure 1-1  
1-1  
DOCUMENT: 151811  
PV-225208 Photovoltaic Inverter  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 1  
PRODUCT DESCRIPTION  
AC Interface Enclosure  
This enclosure is NEMA-3R rated. The AC Interface serves as the connection between the isolation  
transformer/utility and the PV-225208. This enclosure is where theAC line fuses andAC disconnect switch  
reside. For specific control components see Drawing No. 151809 in Section 7 (Appendix).  
DC Interface Enclosure  
This enclosure is NEMA-3R rated. The DC Interface serves as the connection interface between the PV  
array and the PV-225208. This enclosure is where the DC disconnect switch and DC contactor reside. For  
specific control components see Drawing No. 151810 in Section 7 (Appendix).  
CAUTION  
The fuses within the PV-225208 are intended for protecting the PV-225208 control circuitry  
only. They are not intended to provide protection for the PVarray or external cabling.  
Power Electronics Matrix  
The power electronics converters are located at the top of the PV-225208 Main Enclosure. Each matrix is  
comprised of switching transistors (IGBTs), transistor gate drive electronics, a laminated power bus, DC  
capacitor bank, and an aluminum extrusion heat sink with a cooling fan.Afan is located above each matrix  
heatsink.  
The PV array is tied logically to the matrix DC bus via the DC interface enclosure. The embedded  
control unit manages the transfer of power between the DC bus and the utility grid.  
Operator Interface  
The operator interface is located on the front door of the PV-225208 main enclosure. It consists of an On/Off  
switch and a keypad with liquid crystal display for control and monitoring purposes.All interface components  
are NEMA-3R rated. Refer to Section 4 for detailed operation instructions.  
Inductor Enclosure  
This enclosure is NEMA-3R rated. It contains the necessary filter components to insure the PV-225208 line  
currents and voltages meet IEEE-519 and UL1741 harmonic distortion requirements. Mounted on the right  
and left side of the lower enclosure are inductor fans to allow cooling of the line filter components within. This  
enclosure also serves as the mounting base for the PV-225208 main enclosure.  
CONTROL COMPONENTS  
The following assemblies are contained within the PV-225208 main enclosure as shown in Figure 1-2. For  
specific control components see Drawing No. 151808 in Section 7 (Appendix).  
Power Distribution Panel  
This panel contains many of the Electro-mechanical, protective, and control power components neces-  
sary to support the operation of the PV-225208.  
1-2  
DOCUMENT: 151811  
PV-225208 Photovoltaic Inverter  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 1  
PRODUCT DESCRIPTION  
Power Control Unit (PCU)  
The PCU is a Digital Signal Processor (DSP) based control board that performs numerous control and  
diagnostic functions associated with PV-225208 operation. Its most significant tasks are control of PV-225208  
electromechanical components and power electronics converters, signal conditioning for high voltage signal  
inputs and communication with the operator interface panel and system sensors. The PCU also contains the  
necessary DC power supplies to support its operation.  
INTERCONNECTION STANDARDS COMPLIANCE  
The PV-225208 has been tested and listed by Underwriters Laboratories to be in compliance with UL1741  
Static InvertersAnd Charge Controllers For Use In Photovoltaic Power Systems, as well as IEEE-  
929-2000 Recommended Practice For Utility Interface Of Photovoltaic (PV) Systems.  
IEEE-929-2000 provides guidance regarding equipment and functions necessary to ensure compatible  
operation of photovoltaic systems which are connected in parallel with the electric utility. UL1741 is  
the standard applied by Underwriters Laboratory to the PV-225208 to verify it meets the recommendations of  
IEEE-929-2000. Refer to both documents for details of these recommendations and test procedures.  
F-F  
E-E  
Figure 1-2  
1-3  
DOCUMENT: 151811  
PV-225208 Photovoltaic Inverter  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 1  
PRODUCT DESCRIPTION  
SPECIFICATIONS  
The PV-225208 has been designed for photovoltaic power systems, which operate within the following speci-  
fications.Application of the PV-225208 in a manner inconsistent with these specifications may cause damage  
to the PV-225208 and other system components, and is a violation of the terms of the warranty.  
Nominal AC Line Voltage  
Maximum AC Line Current  
Nominal Line Frequency  
Continuous AC Output Power  
PV Maximum Voltage  
208 VAC, +10% -12%  
695 ARMS (at low line voltage)  
60 Hz, +0.5 -0.7 Hz  
225.0 kW @ 208 VAC 3 Phase  
600 VDC  
Peak Power Tracking Window  
PV Minimum Peak Power Tracking Voltage  
PV Maximum Operating Current  
Maximum PV Array Short Circuit Current  
PV Configuration  
330*-600 VDC  
330 VDC  
710 ADC  
1100 ADC  
Monopolar negative grounded  
**-20 to 50° C  
Operating Temperature  
Storage Temperature  
-40 to 50° C  
Maximum Ambient Temperature Rating  
Relative Humidity  
50° C  
To 95%, Non-condensing  
Derated above 6,600 feet  
87 X 102 X 27  
Elevation  
Dimensions (in inches)  
Weight  
Approx. 1935 lbs.  
NEMA 3R  
Enclosure Type  
UL Listing File  
File-E199356  
*Dependent on actualAC line voltage. Refer to Section 4 for detail on the minimum power tracking voltage.  
**If ambient temperature is between -20 to 0° C, the unit must be powered up in standby for at least one  
hour prior to going on-line.  
EQUIPMENT SYMBOL  
Chassis ground – Customer supplied system ground connection point. This symbol may be found near  
a stud within the main enclosure. It is provided as a location to bond the electrical system equipment  
ground.  
1-4  
DOCUMENT: 151811  
PV-225208 Photovoltaic Inverter  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 2  
SAFETY  
SAFETY FEATURES  
WARNING  
The PV-225208 enclosure contains exposed high voltage conductors. The enclosure  
doors should remain locked, except during maintenance or testing. These servicing  
instructions are for use by qualified personnel only. To reduce the risk of electric  
shock, do not perform any servicing other than that specified in the operating  
instructions unless you are qualified to do so. Do not open the cabinet doors if  
extreme moisture is present (rain or heavy dew).  
On/Off Switch  
The PV-225208 incorporates a maintained position on/off switch located on the front door of the main enclo-  
sure. Under normal conditions, the on/off switch is in the on position. Turning the switch to the off position will  
initiate a controlled shutdown of the PV-225208 and open theA/C contactor within the unit. TheA/C contactor  
cannot be closed unless the switch is in the on position. The PV-225208 is prevented from being restarted until  
the on/off switch is turned back to the on position. Cycling the on/off switch will reset the PV-225208 and  
attempt to clear any system fault.  
Main Enclosure Door Interlock Switch  
The front door of the PV-225208 main enclosure is equipped with an interlock switch to preclude operation in  
the event of the front door being opened. It is required that the PV-225208 main enclosure door handle be  
padlocked during normal operation.  
WARNING  
The PV-225208 will immediately shutdown if the front dooris opened during opera-  
tion. It is required that the PV-225208 main enclosure doorhandle be padlocked  
during normal operations. Please make sure the unit is powered down, and isolated  
from the utility grid and PVpanels, priorto opening the front door.Allow 5 minutes for  
any stored potentials to be discharged, prior to opening the unit.  
Disconnect Switches  
Both AC & DC switches are equipped with lockout hasps for personnel safety. The switch enclosure  
door will not open while the PV-225208 is running. In addition, the switch handle and shaft provide a door  
interlock. The door cannot be opened when the switch is in the “on” position. The PV disconnect switch is  
equipped with an auxiliary contact block which enables the switch to be used as a load break PV disconnect.  
In the event a disconnect switch is opened while the PV-225208 is processing power from the PV array, the  
contact block will signal the PCU to stop processing power before the switch opens.  
Fault Reporting  
Any fault conditions are reported to the operator interface. The LCD will display a text description of  
the fault. Refer to Section 5, Troubleshooting, for detailed descriptions of system fault conditions.  
PV Ground Fault Detection  
The PV-225208 is equipped with ground fault detection circuitry (see section 3, installation and section 7,  
system schematic for further detail). Upon detection of 10 amps of ground fault current, the PV-225208  
executes an orderly shutdown, and annunciates a ground fault at the operator interface. The PV-225208 will  
remain faulted until the ground fault is remedied and cleared at the operator interface (see section 5, trouble-  
shooting).  
PV-225208 Photovoltaic Inverter  
DOCUMENT: 151811  
2-1  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 2  
SAFETY  
Over/Under Voltage and Frequency  
The over/under frequency and voltage detection setpoints have been chosen to be in compliance with  
IEEE-929 and UL1741.  
Fault Condition  
(% of Nominal)  
Voltage Range  
VAC < 104  
Trip Time  
VAC < 50%  
6 Cycles  
2 Seconds  
Normal Operation  
2 Seconds  
2 Cycles  
50% < VAC < 88%  
88% < VAC < 110%  
110% < VAC < 137%  
137% < VAC  
104 < VAC < 183  
183 < VAC < 228  
228 < VAC < 285  
285 < VAC  
f < rated -0.7  
f < 59.3  
6 Cycles  
f > rated +0.5  
f > 60.5  
6 Cycles  
Anti Island Protection  
A digital phase-shift-loop (PSL) circuit is implemented in the DSP inverter controller to prevent  
“Islanding” of the PV-225208.  
The DSP continuously makes minor adjustments to the power factor phase angle above and below  
unity. In the event of a utility outage, these adjustments destabilize the feedback between the inverter  
and the remaining load, resulting in an over/under frequency or voltage condition. The PV-225208 then  
performs an orderly shutdown. The fault condition will remain until the utility voltage and frequency have  
returned to normal for 5 minutes.  
This method has been extensively tested and proven to exceed the requirements of UL 1741.  
ISOLATION PROCEDURE  
The following procedure should be followed to de-energize the PV-225208 for maintenance:  
WARNING  
The terminals of the PV input may be energized if the arrays are energized. In  
addition, allow 5 minutes for all capacitors within the main enclosure to discharge  
afterdisconnecting the PV-225208 fromAC and DC sources.  
1. Turn the on/off switch to the off position.  
2. Open the DC interface (PV array) disconnect switch.  
3. Open the AC interface disconnect switch.  
4. Open the isolation transformer circuit breaker.  
5. Install lockout devices on the isolation transformer circuit breaker and PV disconnect switch.  
PV-225208 Photovoltaic Inverter  
DOCUMENT: 151811  
2-2  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 3  
INSTALLATION AND INITIAL TURN-ON  
ISOLATION TRANSFORMER REQUIREMENTS  
The PV-225208 UL1741 certification requires the use of a Xantrex Technology specified 225 kVA WYE/  
WYE isolation transformer between the inverter AC output and the utility interconnection (See Appendix in  
Section 7 for transformer dimensions and specifications. This custom 225 kVA isolation transformer is not part  
of the 225 kVA inverter, but can be ordered as a separate item. If maintaining the listing to UL1741 is not a  
requirement for your application, contact Xantrex Technology for a fact sheet describing the installation op-  
tions and precautions for installing this inverter in a photovoltaic system that does not require UL1741 compli-  
ance.  
WARNING  
Xantrex Technology requires installing an isolation transformer between the PV-  
225208 inverter and the point of utility interconnection. Failure to do so could result  
in catastrophic damage to the PV-225208 as well as the utility distribution system  
and will void the product warranty.  
Inverter Side Isolation Transformer Requirements  
The inverter side of the isolation transformer is configured as a WYE, and is rated for 208 VAC. The neutral  
(X0) connection on the inverter side must be left floating. If the neutral is tied to ground, the inverter will  
be damaged internally at power-up.  
Utility Side Isolation Transformer Requirements  
The utility side windings of the isolation transformer are configured WYE, and must match the voltage at the  
utility inter-tie. Verify that the transformer supplied matches the voltage requirement. Also, the transformer is  
supplied with a neutral connection on the utility side. Connection of this utility-side neutral does not affect the  
operation of the inverter. Check local jurisdiction for their requirements regarding the connection of this  
neutral.  
Contact your Xantrex Technology distributor if you have any questions regarding isolation transformer  
requirements.  
TORQUE AND WIRE GAUGE SPECIFICATIONS  
The following torque specifications are to be used on all electrical interfaces made during installation  
of the PV-225208.  
Torque Table  
Terminal Block or Bolt Size  
3/8-16 Bolt (AC)  
Torque Setting  
250 in lbs./28.2 Nm  
Terminal Block (DC+, DC-,  
& DC Neutral)  
275 in lbs/31.1 Nm  
DOCUMENT: 151811  
PV-225208 Photovoltaic Inverter  
3-1  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 3  
INSTALLATION AND INITIAL TURN-ON  
The following table shows acceptable wire gauges to be connected to the PV-225208 AC and DC inputs.  
Wire Gauge Table  
Termination  
Wire Range AWG  
Up to 4 600MCM-#2  
Conductors Per Phase  
Compression Lug (AC)  
Up to 8 600MCM-#2  
Conductors for each (+) and  
(-)  
Compression Lug (DC+ and  
DC-)  
Up to 2 350MCM-#6  
Conductors  
Terminal Block (DC Neutral)  
INSTALLATION INSTRUCTIONS  
CAUTION  
All wiring methods shall be in accordance with the National Electrical Code ANSI/  
NFPA 70. All power conductors interfacing to the PV-225208 should be sized in  
accordance with the National Electric Code ANSI/NFPA 70 and local codes. Large  
gauge wire must have a minimum bend radius dependent upon the wire gauge (refer  
to the National Electric Code, Article 373-6B). Take care to keep the wire bundles  
away from any sharp edges which may damage wire insulation over time. Xantrex  
Technology recommends using 250 MCM, 105 degrees C, minimum, copper wire  
for all connections to the PV-225208.  
Ventilation Considerations  
Maintain a minimum of 12” clearance in back , front and both sides of the PV-225208 for proper cooling fan  
operation.  
Installation  
1. Move the PV-225208 into place. Lift the PV-225208 from beneath the lower enclosure with a forklift as  
shown in Figure 3-1. (See following page.)  
2. Anchor the lower enclosure feet to the floor with a 1/2” anchor bolts.  
3. Install all conduits needed for cable entry in the shaded areas of both AC and DC interface enclo-  
sures as shown in Figure 3-2. (See following page).  
DOCUMENT: 151811  
PV-225208 Photovoltaic Inverter  
3-2  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 3  
INSTALLATION AND INITIAL TURN-ON  
Lift Here  
Figure 3-1  
Cable Entry  
Area  
Cable Entry  
Area  
Figure 3-2  
Array Grounding  
NEC 690-41/42 requires the PV array to be earth grounded. The PV-225208 chassis is also bonded to the  
PV safety ground terminal block. Refer to the system schematic in the appendix for further wiring configura-  
tion.  
DOCUMENT: 151811  
PV-225208 Photovoltaic Inverter  
3-3  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 3  
INSTALLATION AND INITIAL TURN-ON  
Ground Fault Detection  
The PV-225208 is equipped with a ground fault detection circuit  
and current transducer (CT1 in illustration). This circuit is active  
when the PV array is grounded as described in the previous  
section. In the event of a greater than 10 amp ground fault, the  
PV-225208 will execute an orderly shutdown and annunciates a  
ground fault at the operator interface. The PV-225208 will remain  
faulted until the ground fault is remedied and cleared at the opera-  
tor interface (see section 5, Troubleshooting).  
CAUTION  
The input and output circuits are isolated from the  
enclosure and the system grounding, if required by sec-  
tions 690-41, 690-42 and 690-43 of the National Electric  
Code, ANSI/NFPA 70, is the responsibility of the in-  
staller.  
CT1  
INTERCONNECTION WIRING  
CAUTION  
To reduce the risk of fire, connect only to a circuit provided with 800 amperes  
@208VAC, or 400 amperes @480VAC maximum branch circuit overcurrent protec-  
tion in accordance with the National Electrical Code, ANSI/NFPA 70.  
The following wires for connecting the PV-225208 to external devices are not provided by Xantrex Technolo-  
gy: (See installation diagram on pages 3-5.)  
·
Connect 3-Phase 208 VAC inverter output (AC Disconnect switch) to terminals of the 208 VAC  
inverter side of isolation transformer. The neutral on the inverter side of the isolation transformer  
must be left floating. Ground loops will exist when the inverter starts switching, which will  
cause the inverter to shut down due to phase over-currents and will result in damage to the  
PV-225208. Also, insure that this neutral is not bonded to the isolation transformer frame. Be  
sure to maintain proper phasing as shown in the system schematic found in Section 7.  
Connect Isolation transformer grid side terminals 1, 2, and 3 to line circuit breaker. Be sure to maintain  
proper phasing as shown in the system schematic found in Section 7.  
·
·
·
PV frame ground to ground terminal block (TB3).  
Connect PV+, PV-, and PV Safety ground to the DC interface enclosure’s designated termina-  
tions. See Section 7 for further detail .  
CAUTION  
When connecting external AC wires to the PV-225208, positive phasing sequence  
must be maintained throughout the installation process. Refer to the System Sche-  
matic in Section 7 of this manual for proper phasing convention.  
Install all wires listed above. Refer to the Appendix in Section 7 for layout of the AC and DC inter-  
face enclosures. Refer to the system schematic in Section 7 for more detailed terminal locations.  
DOCUMENT: 151811  
PV-225208 Photovoltaic Inverter  
3-4  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 3  
INSTALLATION AND INITIAL TURN-ON  
DOCUMENT: 151811  
PV-225208 Photovoltaic Inverter  
3-5  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 3  
INSTALLATION AND INITIAL TURN-ON  
INITIAL TURN ON PROCEDURE  
The following must be performed by an approved Technician:  
The following procedures are intended to verify correct installation and proper operation of the PV-225208.  
These steps are to be followed sequentially. Do not continue if any of the steps or results are unclear. Refer to  
Section 4 for a detailed description of system operation. Refer to Section 5 for fault condition descriptions and  
troubleshooting. Refer to Section 7 for detailed system schematics.  
Visual Inspection, Isolation Transformer WYE/WYE  
Verify the isolation transformer circuit breaker is open.  
If a phase rotation meter is available, verify proper phase rotation at the line side of the isolation  
transformer circuit breaker.  
Insure the neutral on the inverter side is left floating. If the inverter side neutral is tied to ground,  
the inverter will not function properly. Also, insure that the neutral is not bonded to the  
isolation transformer frame.  
Verify the inverter 208 VAC conductors are connected to the isolation transformer.  
If the wires are marked, verify they follow the sequence on the line side of the isolation transformer  
and circuit breaker.  
Verify the utility conductors are properly connected to the isolation transformer.  
Visual Inspection, PV-225208  
Insure AC and DC disconnect switches are opened.  
Remove the front cover from the inductor enclosure, open the door of the main enclosure, and  
disconnect enclosures and inspect.  
Verify all wire connections are tight.  
Inspect the fiber optic cables between the PCU and the matrix driver boards. All fibers should be  
snap-locked into their respective receivers/transmitters.  
Insure all connector jack screws on the PCU and matrix driver board are tight.  
Verify AC phase connections landed at the AC interface enclosure.  
Visual Inspection, PV Array Wiring  
Verify the PV+, PV-, and PV safety ground are isolated from each other. The safety ground must not  
be tied to PV-.  
Verify all PV fuses are installed.  
Initial Power  
Turn the On/Off switch, located on the front door to off.  
With the DC disconnect switch opened, close one of the PV array string disconnect switches.  
Carefully measure VDC across the PV +/- terminal block. The value should be the same as at the  
PV array string disconnect switch. It should also be positive.  
Close the PV disconnect switch.  
Carefully measure VDC between the DC contactor negative (-) terminal and the DC switch positive  
DOCUMENT: 151811  
PV-225208 Photovoltaic Inverter  
Operation and Maintenance Manual  
3-6  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 3  
INSTALLATION AND INITIAL TURN-ON  
(+) terminal. The value should be the same as at the PV array string disconnect switch. It should also be  
positive.  
Open all PV string disconnect switches.  
Close the isolation transformer circuit breaker.  
Verify 208 VAC voltage across the AC disconnect switch. If a phase rotation meter is available,  
verify proper phase rotation at the AC disconnect switch.  
Close the AC disconnect switch.  
Verify 208 VAC voltage across the AC line fuses F1-3.  
System Verification  
Upon applying 208 VAC power to the PV-225208, observe the operator interface panel.After approxi-  
mately 15 seconds, the panel should finish initialization and will probably report a fault condition.  
Remedy any faults reported. To clear a fault condition, press the <ENTER> key twice. If the fault message  
does not change, the fault condition is still present. Most likely, any faults seen at this point will be related  
to PV-225208 safety switches. To disable the door interlock switch with the main enclosure door opened,  
pull the switch shaft out. It will lock in its ‘maintenance’ position. Once all faults are cleared the system will  
read ‘Sleepingor ‘Keyswitch Disabledepending on the position of the On/Off switch. To re-enable  
interlock, push the shaft in and close the door.  
Scroll up the menu until ‘Enter Read Parameter:’ is displayed.  
Press <Enter>, then <19>. This is line voltage frequency being read by the PCU. It should read 60.0  
+0.5, -0.7.  
Verify the On/Off switch is in the ‘Off’ position.  
Close the PV array string disconnect switches.  
Close the PV-225208 DC disconnect switch.  
Press <F2> on the operator interface panel. If the PV voltage is above the PV Start Voltage setpoint,  
the second line should read ‘Waking Up’. Once the PV Start Time is exceeded, the PV-225208 should  
transition to ‘PowerTracking’.  
The power tracker was previously limited to 25% of PV-225208 rated power. Once the PV-225208 has  
stabilized operation (approximately 20 seconds), scroll through the main operator interface panel menu.  
Verify all phase voltages and currents are closely balanced.  
Scroll to ‘Enter Read Parameter:’ Press <ENTER> then <17> <ENTER> to view ground fault  
current value. This value should be equal to or very close to zero. Continue to monitor this value as  
the PV-225208 is commanded to higher power levels.  
Enter the write parameter menu and increase the ‘I PPT Max %’ to 50. Exit the write parameter  
menu and verify all operating values are proper.  
Continue to increment ‘I PPT Max %’to 100. Depending upon solar conditions, the PV-225208 may not  
operate at full power. If the PV array is not experiencing full sun, the PV maximum power tracker will  
regulate the PV voltage to maintain maximum PV power output. To determine if the PV-225208 has  
reached it’s maximum power output, enter <20> at the ‘Enter Read Parameter:’‘0’means the PV-225208  
has not reached maximum power, contrarily, ‘1means the PV-225208 has reached maximum power and  
executed the modified peak power tracker to limit output power.  
The PV-225208 is now fully operational.  
DOCUMENT: 151811  
PV-225208 Photovoltaic Inverter  
Operation and Maintenance Manual  
3-7  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 3  
INSTALLATION AND INITIAL TURN-ON  
Power Tracker Fine Tuning:  
All PV-225208 operating parameters have been set at the factory, based upon prior experience with PV  
arrays. Contact your XantrexTechnology distributor for further information.  
It is recommended that the PV-225208 be watched during Wake-Up and Sleep Test. If the PV-225208  
cycles between operating and sleeping at either of these times, the condition setpoints are not set properly  
(refer to section 4 for detailed description of PV-225208 state transitions). The PV225208 should not  
cycle if the setpoints are set properly.  
NOTE  
Some field adjustable parameters are password protected and may only be changed  
by trained service technicians. In particular are parameters relating to utility pro-  
tection setpoints. Any changes to these setpoints should be agreed upon by the  
local utility and the equipment owner.  
NOTE  
Visually inspect the exterior surfaces for any damage (nicks, chips, exposed base  
metal and scratches) that may have occurred during shipment orinstallation. Touch  
up or recoat using White NISSEN Feltip Paint Marker, or equivalent to prevent  
rust or corrosion.  
DOCUMENT: 151811  
PV-225208 Photovoltaic Inverter  
Operation and Maintenance Manual  
3-8  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 4  
OPERATION  
DESCRIPTION OF SYSTEM OPERATION  
Overview  
The PV-225208 is a fully automated grid-tied photovoltaic inverter. Manual interaction or control of the  
inverter is necessary only in the event of a system fault. The following conditions govern PV-225208 operation:  
Stable utility voltage and frequency must be present for all states of operation.  
Fault states are automatic from any state of operation.Afault will cause the PV-225208 to immediately  
stop processing all power. The fault condition will be reported to the operator interface.  
The on/off switch, located on the front door of the PV-225208, must be switched to the on position for all  
operating states.  
Cycling the on/off switch attempts to clear any system faults and return the PV-225208 to normal opera-  
tion.  
Operating States  
A state machine implemented within the PCU control software governs the operation of the PV225208. There  
are five steady-state operating states and numerous intermediate transition states. The intermediate transition  
states provide an orderly progression from one operating state to the next. The user has the ability to manually  
transition the PV-225208 between operating states from the operator interface keypad. Manual transitions are  
initiated by entering a ‘Goal State’, where the goal state is the desired operating state. Given all applicable  
system parameters are within acceptable limits, and the request is valid within the state machine, the PV-  
225208 will initiate the proper sequence of operations necessary to progress to the requested goal state. Refer  
to Figure 4-3 for a description of valid state transitions.  
Shutdown: The line interface controller is idle. The PCU monitors the status of the PV array and  
utility grid, waiting in standby until the PV array is available to produce power to the grid.  
Fault: The PV-225208 has encountered a fault condition. When this happens, regardless of the PV-  
225208 state-of-operation, the PV-225208 will stop processing all power and execute an orderly system  
shutdown.Adescription of the fault and fault code will appear on the operator interface LCD. The Fault  
state may be cleared from the keypad once the cause of the fault has been corrected. See Section 5 for a  
complete description of all fault codes.  
Manual Current: This operating state is provided to evaluate the existing PV array V-I character-  
istics. The PV controller regulates a constant amount of PV current as commanded by the user from  
the operator interface keypad, up to the PV current limit of the PV-225208. If the user commands more  
PV current than is available, the DC bus voltage will drop below the minimum bus voltage level and the  
PV-225208 will return to Sleeping mode.  
Matrix Test: This operating state is provided to verify proper operation of the matrix and associ-  
ated control electronics. There is no power transfer between the PV and utility in this mode.  
Power Tracking: This is the standard operating state of the PV-225208. The PV-225208 maximum  
power tracker will demand maximum power from the PV array, given sufficient PVirradiance.  
DOCUMENT: 151811  
PV-225208 Photovoltaic Inverter  
4-1  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 4  
OPERATION  
The user should be aware of the following conditions governing PV-225208 state transitions:  
• Utility power must be present for all states of operation.  
• Fault states are automatic from any state of operation.Afault will cause the PV-225208 to immediately  
stop processing all power. The fault condition will be reported to the operator interface LCD.  
• Most PV-225208 faults are latching and must be cleared at the operator interface keypad before  
transitioning to another operating state.  
• The On/Off switch, located on the front door of the PV-225208, must be in the On position for all  
operating states except Matrix Test, in which case it must be in the Off position.  
OPERATION FEATURES  
Fixed Unity Power Factor Operation  
The Xantrex PV Series grid tied inverters maintain unity power factor during operation. The control software  
constantly senses utility voltage, and constructs the output current waveform to match the utility voltage. The  
PV line of inverters are not capable of operation without the presence of normal utility voltage, nor are they  
capable of varying the output power factor off unity.  
Utility Voltage/Frequency FaultAutomatic Reset  
In the event of a utility voltage or frequency excursion outside of preset limits, the PV-225208 will stop  
operation and annunciate a fault at the operator interface. Once the utility voltage has stabilized within accept-  
able limits for a period of at least five minutes, the PV-225208 will automatically clear the fault and resume  
normal operation. Voltage and frequency fault setpoints are detailed later in this section.  
Active Island Detection  
Much concern has been given to the possibility of an inverter causing a ‘utility island’ condition during  
a utility power outage. An island condition is defined as grid tied inverter maintaining operation and  
supporting a load that has been isolated from the utility power source. This requires the load to be  
closely balanced to the output power of the inverter as well as having a resonant frequency close to  
60Hz. Needless to say, this is an extremely remote possibility. To insure this condition does not occur,  
the PV-225208 control software contains an active phase-shift-loop algorithm, which destabilizes a balanced  
load, which may otherwise be capable of maintaining inverter operation in the absence of utility voltage. This  
feature has been extensively tested and proven to exceed the safety requirements of UL-1741 and IEEE-929-  
2000.  
Ground Fault Detection  
The PV-225208 is equipped with a ground fault detection circuit and current transducer. In the event of a 10  
amp ground fault, the PV-225208 will execute an orderly shutdown and annunciates a ground fault at the  
operator interface. (See Section 5, Troubleshooting).  
DOCUMENT: 151811  
PV-225208 Photovoltaic Inverter  
4-2  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 4  
OPERATION  
Current Imbalance Detection  
In the event of phase-to-phase current imbalance of greater than 20% between phases, the inverter will ex-  
ecute an orderly shutdown, and annunciate a fault at the operator interface. See Section 5, Troubleshooting,  
for further information on this fault condition.  
DC Overvoltage Detection  
In the event of DC voltage greater than 600Vdc, the PV-225208 will execute an orderly shutdown and  
annunciate a fault to the operator interface. If DC voltage remains greater than 600Vdc, the PV-225208 may  
be irreparably damaged. See Section 5, troubleshooting for further information on this fault condition.  
Peak Power Tracking  
The PV-225208 control software employs an active PVpeak power tracker designed to maintain maximum  
power output from the PV array at all times of operation. The peak power voltage point varies primarily  
depending upon the temperature of the PV cells. The PV-225208 constantly seeks the optimum voltage and  
current operating points of the PV array to maintain maximum PV power output. Upon PV wake-up, the  
power tracker will increase power while ramping PV array voltage to the PV maximum power voltage refer-  
ence setpoint (PPT V Ref). The change rate is governed by the power point ramp time setpoint (PPT Ramp  
T). Once the PV voltage is ramped to the reference setpoint, the PCU begins to adjust the commanded PV  
voltage around the reference setpoint, seeking maximum PV power. The power tracker may only adjust the  
operating voltage +/- 20% of PPT V Ref. The PV maximum power voltage step and update rate are user  
setable (PPT V Step and PPT Rate, respectively).  
If available PVpower is above the maximum allowable power level of the PV-225208, the power tracker will  
increase voltage as needed to maintain output power below rated maximum.  
The minimum operating voltage of the PV-225208 is 330 VDC. The power tracker will not track voltage  
below this point, regardless of the reference voltage setpoint.  
Automatic Sleep Test  
Toward the end of every solar day, the PV-225208 automatically determines when to stop producing power  
dependent upon the output power of the inverter.As the net output power of the PV-225208 nears zero, a  
timer is started to allow the inverter to ride through any brief irradiance reductions.  
OPERATOR INTERFACE  
The operator interface display consists of two main menu levels: The read parameter menu and the  
write parameter menu. The read parameter menu consists of all system parameters, the date and time.  
These can be viewed any time the PV-225208 has control power.  
The write parameter menu consists of a goal state sub-menu, and all system write parameters. The write  
parameter menu is password protected and may only be changed by trained service technicians. In  
particular are parameters relating to utility protection setpoints. These have been set in the factory to  
DOCUMENT: 151811  
PV-225208 Photovoltaic Inverter  
4-3  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 4  
OPERATION  
the limits mandated by UL1741.Any changes to these setpoints should be agreed upon by the local utility and  
the equipment owner. The ability to adjust the voltage and frequency setpoints with respect to the actual utility  
voltage and frequency has been provided as a simulation tool to verify the PV-225208 accurately detects and  
responds to a utility excursion. This test should only be performed by a trained service technician. It is possible  
to adjust the setpoints in a manner that will prevent the PV-225208 from functioning.  
Upon system power up, the operator interface LCD will display the system operating state on the first  
line. The second line will display the date and time. This is the standard display.  
Refer to Section 7, Appendix for a complete description of all system read/write parameters.  
NOTE  
The operator interface display will reset itself to the standard display if there is no  
input for 30 seconds.  
Read  
Parameter  
Menu  
Standard  
Password  
Display  
Enter  
Goal State  
Password  
Write  
Parameter  
Menu  
Set Date/Time  
Change  
Parameters  
Figure 4-2  
Figure 4-1  
Operator Interface Keypad  
Operator Interface Flow Chart  
Viewing Read/Write Parameters Values  
To display any parameter, use the /\ or \/ keys on the operator interface keypad to scroll through the  
read/write parameters. The \/ key will scroll downward through the menu and the /\ key will scroll  
upward. Upon reaching the end of the menu, it will roll-over to the beginning.  
DOCUMENT: 151811  
PV-225208 Photovoltaic Inverter  
4-4  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 4  
OPERATION  
Write parameter values are password protected; however, they may be viewed in the read parameter  
menu without entering a password. From the standard display press the /\ key. The display will read  
‘Enter Parameter ID:’. Enter the desired write parameter ID, then press the ‘Enter’.  
Refer to Section 7: Appendix, for a table of all read/write parameters and their descriptions.  
Changing Write Parameter Values  
From the standard display or anywhere in the read parameter menu, you may access the write param-  
eter menu by pressing the <MENU> key. This will ask for a password. Enter the password and press  
the <ENTER> button. Use the /\ or \/ key on the operator interface keypad to scroll through the write  
parameters. To change the displayed parameter, press the <ENTER> button. Enter the desired value  
and press <ENTER>. If the value entered is outside the acceptable range for the parameter, the original  
value will remain. To leave the write parameter menu press the <MENU> button repeatedly until the  
standard display shows on the LCD.  
Refer to Section 7: Appendix, for a table of all read/write parameters and their descriptions.  
Commanding Goal State Changes  
From the standard display press the <MENU> key. This will ask for a password. Enter the password  
and press the <ENTER> button. The LCD will prompt ‘Change Goal State?’. Press <ENTER> again.  
The goal state menu will show on the LCD. Scroll through the goal state menu with the /\ or \/ keys  
until the desired goal state is reached. Press <ENTER>. The LCD will prompt: ‘Press F4 to Confirm’.  
Press <F4> and the PV-225208 will transition to this goal state. If the goal state requested violates the  
conditions of the state machine, the PV-225208 will remain in the previous state of operation.  
Setting the Date and Time  
From the standard display enter the write parameter menu (see previous). From the ‘Change Goal  
State?’ prompt, scroll up with the /\ key until date/time parameter is reached. Press the enter key. The  
date/time will be replaced with an underscore. Enter the proper date/time in a six digit format. For  
example: The date is entered month-day-year: April 28, 2002 is entered 042802 <ENTER>. The time  
is entered in military hours-minutes-seconds: 4:30 pm is entered 163000 <ENTER>. If the date/time is  
entered incorrectly the original value will remain. Press <MENU> to return to the standard display.  
MANUAL STATE TRANSITIONS  
Refer to previous sections on commanding PV-225208 goal states.  
Sleeping Matrix Test Sleeping:  
Turn the On/Off switch to the Off position. Command the PV-225208 to Matrix Test. Once the user has  
completed the test, command the PV-225208 to Sleeping. If the On/Off switch is turned to On while the  
PV-225208 is in the Matrix Test state, the PV-225208 will transition to Sleeping.  
DOCUMENT: 151811  
PV-225208 Photovoltaic Inverter  
4-5  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 4  
OPERATION  
Figure 4-3  
PV-225208 State Machine  
Power TrackingManual CurrentPower Tracking or Sleeping:  
Verify the PV manual current parameter (I Manual %) is set to the desired percent of rated. Com-  
mand the PV-225208 to Manual Current mode from the operator interface keypad. While in the manual  
current mode, the user may change the PV manual current parameter. However, the user may demand  
greater current than the capacity of the PV array. If this causes the PV voltage to drop below the minimum  
operating voltage (330 Vdc), the PV-225208 will transition to Sleeping.  
To exit the Manual Current mode the user must manually command the PV-225208 to either Power  
Tracking or Sleeping.  
AUTOMATIC STATE TRANSITIONS  
Sleeping Power Tracking Sleeping:  
The On/Off switch must be turned to the On position. Once the PV voltage exceeds the PV voltage  
start setpoint (PV V Start) the PV-225208 will start a wake-up timer (PV T Start). If the PV voltage  
remains above the PV start voltage setpoint for the duration of the wake-up timer, the PV-225208 will  
transition to PowerTracking.  
If the PV power drops below the PV power stop setpoint (PV P Stop) the PV-225208 will start a PV  
sleep timer (PV T Stop). If the PV voltage and power remain below their respective setpoints for the  
duration of the sleep timer, the PV-225208 will transition to Sleeping  
DOCUMENT: 151811  
PV-225208 Photovoltaic Inverter  
4-6  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 4  
OPERATION  
Any State Fault:  
If the PV-225208 encounters a fault, regardless of operating state, it will transition to the Fault state. The  
PV-225208 will remain in this state until the fault condition has been remedied and cleared via the front  
panel.  
A description of the fault will show on the first line of the operator interface LCD. The second line  
of the LCD will read ‘Clear Fault?’. To clear a fault press <ENTER>. The PV-225208 will transition to  
Sleeping. If the fault does not clear, the fault condition has not been corrected. If the ‘Clear Fault?mes-  
sage is not shown on the second line of the LCD, scroll through the read parameter menu with the /\ or \/  
keys until the message appears.  
AUTO-RESTART FEATURE  
In the event of a utility voltage or frequency surge or sag, which causes the inverter to shut down, the  
PV-225208 will automatically transition to a fault condition. Once the utility recovers for a period of five  
minutes, the PV-225208 will automatically clear the fault, then resume normal operation.  
ISOLATION PROCEDURE  
The following procedure should be followed to de-energize the PV-225208 for maintenance:  
1. Turn the On/Off switch to the Off position.  
2. Open the DC interface (PV array) disconnect switch.  
3. Open theAC interface disconnect switch.  
4. Open the isolation transformer circuit breaker.  
5. Install lockout devices on the isolation transformer circuit breaker and PV disconnect switch.  
WARNING  
The terminals of the PV input may be energized if the arrays are energized. In addi-  
tion, allow 5 minutes for all capacitors within the main enclosure to discharge after  
disconnecting the PV-225208 fromAC and DC sources.  
TURN-ON PROCEDURE  
Refer to Section 3 for a detailed first-time turn on procedure.  
1. Remove any lockout devices from the isolation transformer circuit breaker and PV disconnect  
switch.  
2. Close the isolation transformer circuit breaker.  
3. Close theAC interface disconnect switch.  
4. Close DC interface (PV array) disconnect switch.  
5. Turn the On/Off switch to the On position.  
After a 15 second initialization period, the PV-225208 will automatically transition to ‘Waking Up’, given the  
PV voltage is greater than the PV V Start setpoint.  
DOCUMENT: 151811  
PV-225208 Photovoltaic Inverter  
4-7  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 5  
TROUBLESHOOTING  
GENERAL  
In the event of a fault, the PV-225208 will annunciate the condition at the operator interface. The PV-225208  
will execute an orderly shutdown and remain faulted until the fault is cleared (manually or automatically).  
In general, the operator should respond to any PV-225208 fault as follows:  
1. The source of the fault should be sought by referring to the following chart.  
2. Rectify the fault condition and attempt to clear the fault by cycling the on/off switch.  
3. If the problem cannot be corrected, note and write down the fault code and description, then contact  
your Xantrex Technology distributor for assistance or service.  
ALARM AND FAULT CONDITIONS  
WARNING  
Lethal energy may be stored within each matrix assembly. Use extreme caution  
when troubleshooting. After disconnect all sources of power, wait at least 5 minutes  
for internal capacitors to discharge.  
(H) - Fault triggered by hardware.  
(S) - Fault triggered by software.  
0000 - No Faults  
No fault conditions are detected.  
002C/012C - Matrix Over-Temperature (S)  
The temperature of the matrix (002C Matrix 1; 012C Matrix 2) aluminum heat sink exceeded 85°C.  
Possible causes:  
External cooling fan inoperable  
Air flow on heat sink impeded due to accumulation of debris  
Operation above rated ambient temperature for an extended period of time  
002E - State Machine Failure (S)  
Software has encountered an undefined state.  
Attempt to clear the fault by either cycling control power or pressing the black reset button in the lower  
left corner of the PCU. If the fault is sustained, replacement or service of the PCU will be necessary.  
002F – Parameter Out Of Date (S)  
Software has determined that the system variables within the operator interface panel do not match the  
ones in the PCU. Generally this fault may be cleared and normal operation resumed.  
0031 - Ground Current Fault (S)  
The earth safety ground current has exceeded the maximum programmed value (Max Gnd Flt I).  
PV-225208 Photovoltaic Inverter  
DOCUMENT: 151811  
5-1  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 5  
TROUBLESHOOTING  
Possible causes:  
Inspect the PV array for ground faults.  
CT8 defective:Troubleshoot the ground fault CT8, located on the power distribution panel of the main  
enclosure (see system schematic drawing in Section 7), using the procedures described in faultYY27.  
0032 - PV Overvoltage (S)  
The PV voltage has exceeded the maximum programmed limit (PV Max Volt).  
Check the PV input voltage at the PV disconnect switch. If the voltage is below 600 VDC, clear the  
alarm and restart the PV-225208.  
0040 - In Programming Mode (S)  
System is in reload PROM mode.  
0042 - Bad Memory (S)  
The static memory test failed upon system initialization. This fault is generally transient in nature.  
Attempt to clear the fault by either cycling control power or pressing the black reset button in the lower  
left corner of the PCU. If the fault is sustained, replacement or service of the PCU will be necessary.  
0045 – Line Matrix Failure to Turn On (S)  
0046 – Line Matrix Failure to Turn Off (S)  
Software was not able turn on or turn off the indicated switching matrix.  
Attempt to clear the fault by either cycling control power or pressing the black reset button in the lower  
left corner of the PCU. If the fault is sustained, replacement or service of the PCU will be necessary.  
0061 – Line AC Frequency Too Low (S)  
The AC line frequency fell below the allowable limit.  
This fault is self-clearing. Once the utility frequency has recovered within the acceptable operating  
range, the PV-225208 will automatically clear this fault and resume normal operation after 5 minutes. If the  
fault will not clear, verify the adjustable setpoint is below the actual utility frequency. If the fault is sustained,  
contact your XantrexTechnology distributor for assistance or service.  
0062 - Line AC Frequency Too High (S)  
The AC frequency exceeded the allowable limit.  
This fault is self-clearing. Once the utility frequency has recovered within the acceptable operating  
range, the PV-225208 will automatically clear this fault and resume normal operation after 5 minutes. If the  
fault will not clear, verify the adjustable setpoint is above the actual utility frequency. If the fault is sustained,  
contact your Xantrex Technology distributor for assistance or service.  
PV-225208 Photovoltaic Inverter  
DOCUMENT: 151811  
5-2  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 5  
TROUBLESHOOTING  
0063 - AC Voltage Too Low (S)  
TheAC Inverter voltage fell below the minimum programmed limit (MinACVolt).  
This problem was caused by the utility. Clear the fault and restart the PV-225208.  
Possible causes:  
High momentary load which forces the inverter to current limit  
Fuses F1, F2, F3, F4, F5 or F6 blown  
SSR-1 inoperable  
Contactor K1 inoperable  
Utility voltage fell below the allowable limit.  
This fault is self-clearing. Once the utility voltage has recovered within the acceptable operating range,  
the PV-225208 will automatically clear this fault and resume normal operation after 5 minutes. If the fault will  
not clear, verify the adjustable setpoint is below the actual utility voltage. If the fault is sustained, contact your  
XantrexTechnology distributor for assistance or service.  
0064 - AC Voltage Too High (S)  
The inverter controller voltage exceeded the maximum-programmed limit (Max AC Volt).  
Possible causes:  
SSR-1 inoperable  
Contactor K1 inoperable  
Utility voltage exceeded the allowable limit.  
This fault is self-clearing. Once the utility voltage has recovered within the acceptable operating range,  
the PV-225208 will automatically clear this fault and resume normal operation after 5 minutes. If the fault will  
not clear, verify the adjustable setpoint is above the actual utility voltage. If the fault is sustained, contact your  
XantrexTechnology distributor for assistance or service.  
012A - Interrupt Time-Out (S)  
The PCU was not able to service the interrupt for approximately 1 second.  
Attempt to clear the fault and restart the PV-225208 by pressing the black reset button on the lower left corner  
of the PCU. If the fault is sustained, replacement or service of the PCU will be necessary.  
0230 – Door Interlock Switch Open (H)  
The door interlock lock switch located in the inside upper left corner of the main enclosure door is open.  
If the switch is closed and the fault still registers on the front panel, isolate the PV-225208 from external power,  
then:  
Verify continuity across the switch contact block while the switch is closed.  
Verify continuity between PCU-J2-5 and PCU-J3-3.  
0430 - PV Auxiliary Switch Open (H)  
PV-225208 Photovoltaic Inverter  
DOCUMENT: 151811  
5-3  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 5  
TROUBLESHOOTING  
The dry contact auxiliary switch mounted to the PV disconnect switch has been toggled. The auxiliary  
switch should be opened when the PV disconnect switch is open. If the fault will not clear when the PV  
disconnect switch is closed:  
Isolate PV-225208 from utility power.  
Close PV disconnect switch and check continuity between PCU J3-3 and PCU J2-7. If there is no  
continuity, inspect wiring between the PCU and the auxiliary switch (see page 2 of the system schematic  
for further detail).  
XX25/XX26 - Line Gate Drive Fault (S)  
One of the IGBT gate drive boards signaled the PCU that there was a fault. The second two digits refer to  
which matrix has the fault. XX25 refers to matrix 1 and XX26 refers to matrix 2. The particular device at  
which the fault was detected is indicated by the first two digits of the fault code, as follows:  
XX: 01 = Phase A+  
04 = Phase B+  
02 = Phase A-  
08 = Phase B-  
20 = Phase C-  
10 = Phase C+  
If more than one phase faults simultaneously, the error code will contain the summation of phase fault  
values. For example, if phaseA+ and B+ of matrix 1 fault simultaneously, the error will read 0525.  
Make sure the fiber optics for the device and matrix in question are properly connected to the driver  
board. Similarly, make sure the fiber is properly connected at the PCU.  
Clear the fault and restart the PV-225208. If the fault is sustained, contact your XantrexTechnology distributor  
for assistance or service.  
YY27/YY28 - Line Over-Current Fault (S)  
Current in one phase of the matrix has exceeded the allowable limit.YY27 refers to matrix 1 andYY28 refers  
to matrix2. The faulted phase is indicated by the first two digits of the fault code, as follows:  
YY: 01 = Phase A  
02 = Phase B  
04 = Phase C  
If more than one phase faults simultaneously, the error code will contain the summation of phase fault  
values. For example, if phaseAand C of matrix 1 fault simultaneously, the error will read 0527.  
Possible causes:  
AC system wiring short: Inspect the AC power system for short circuits.  
PCU Power Supply is defective: Verify +/-15Vdc sources, referenced to analog ground, on the  
PCU. There are labeled test points on the PCU circuit board. Note: There are two isolated +15Vdc  
power supplies labeled +15Vdc and +15Vdc Drv. The +15Vdc Drv power supply provides power  
for the matrix driver boards only.  
Faulty CT wiring: Verify the wiring between the PCU power supply and the CT is properly con-  
nected and undamaged. Refer to page 2 of the system schematic in Section 7.  
CT defective: Locate the current transducer for the matrix and phase in question (see control com-  
ponents drawing in Section 7). With a digital multi-meter measure the voltage from CT pins 1, 2, and  
3 to chassis ground. Pins 1 and 3 should read approximately +15 and -15Vdc respectively. These  
voltages are sourced directly from the PCU. Pin 2 should read less than 20mV when no current is  
passing through the CT window. If Pin 2 reads greater than 20mV, and the supply voltages are on  
PV-225208 Photovoltaic Inverter  
DOCUMENT: 151811  
5-4  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 5  
TROUBLESHOOTING  
Pins 1 and 3 are correct, the CT may be damaged.  
Clear the fault and restart the PCU. If the fault is sustained contact your Xantrex Technology distributor for  
assistance or service.  
0828 – PV Over-Current Fault (S)  
Current through the PV CT has exceeded the allowable limit.  
Possible causes:  
PV system wiring short: Inspect the PV power system for short circuits.  
PCU Power Supply is defective: Verify +/-15Vdc sources, referenced to analog ground, on the  
PCU. There are labeled test points on the PCU circuit board. Note: There are two isolated +15Vdc  
power supplies labeled +15Vdc and +15Vdc Drv. The +15Vdc Drv power supply provides power  
for the matrix driver boards only.  
Faulty CT wiring: Verify the wiring between the PCU and the CT is properly connected and undam-  
aged. Refer to the system schematic in Section 7.  
CT defective: Locate the current transducer for the PV leg in question (see control components  
drawing in Section 7). With a digital multi-meter measure the voltage from CT pins 1, 2, and 3 to  
chassis ground. Pins 1 and 3 should read approximately +15 and -15Vdc respectively. These volt-  
ages are sourced directly from the PCU. Pin 2 should read less than 20mV when no current is  
passing through the CT window. If Pin 2 reads greater than 20mV, and the supply voltages are on  
Pins 1 and 3 are correct, the CT may be damaged  
Clear the fault and restart the PCU. If the fault is sustained contact your Xantrex Technology distributor  
for assistance or service.  
8021 - DC Bus Voltage High (H)  
The DC Bus voltage has exceeded the maximum allowable limit.  
This fault is generally transient in nature. Clear the fault and attempt to restart the PV-225208.  
PV-225208 Photovoltaic Inverter  
DOCUMENT: 151811  
5-5  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 6  
PREVENTATIVE MAINTENANCE  
PERIODIC MAINTENANCE  
Xantrex Technology recommends that the following preventative maintenance be carried out on the  
PV-225208:  
Monthly intervals or as required:  
NOTE  
Visually inspect the exterior surfaces for any damage (nicks, chips, exposed base  
metal and scratches). Touch up or recoat using White NISSEN Feltip Paint Marker,  
or equivalent to prevent rust or corrosion.  
Aluminum Extrusion Heatsink  
Accumulation of dirt and debris on the aluminum extrusion heatsinks and fans will decrease the ability  
to transfer heat, which can cause the PV-225208 to shutdown on over-temperature alarms. Inspect  
the aluminum extrusion heatsinks and fans for accumulation of dirt and debris. Clean if debris is present.  
Fan Operation  
Verify proper operation of the heatsink cooling fans, located above the matrix heatsinks. The fans  
operate when the K1 contactor is closed. Remove any debris from the fans.  
Internal Circulation Fan:  
Verify the internal circulation fan is operating whenever there is utility power applied to the  
PV-225208.  
Inductor Enclosure Cooling Fans:  
Verify these fans operate whenever the PV-225208 is processing power.  
Six month intervals:  
(See Isolation Procedure located on page 6-2, and perform prior to the following)  
Enclosure Seals  
Inspect the enclosure access panel seal. If damaged, replace with equivalent closed cell foam  
gasket. Call your Xantrex Technology distributor for factory replacements or specifications.  
Electrical Connections  
Inspect the condition of all wiring within the PV-225208. Inspect all wire crimps and connections for  
damage caused from high temperature. Check for corrosion. Replace any damaged wires. Verify all  
mechanical connections are sufficiently tightened. Verify all conduction surfaces are clean and free of  
corrosion.  
DOCUMENT: 151811  
PV-225208 Photovoltaic Inverter  
6-1  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 6  
PREVENTATIVE MAINTENANCE  
Mechanical electrical connections will loosen over time. This is caused primarily by thermal cycling  
during normal operation.As connections loosen, electrical impedance will increase at the connection,  
eventually leading to fire and component damage. It is critical to check all electrical connections every  
six months.  
Inductor Enclosure  
Access the inductor enclosure and remove any accumulated dirt and debris. Vacuum enclosure  
whenever dust or dirt is present.  
ISOLATION PROCEDURE  
The following procedure should be followed to de-energize the PV-225208 for maintenance:  
WARNING  
The terminals of the PV input may be energized if the arrays are energized. In  
addition, allow 5 minutes for all capacitors within the enclosure to discharge af-  
ter shutting down the PV-225208.  
1. Turn the on/off switch to the off position.  
2. Open the DC interface (PV array) disconnect switch.  
3. Open the AC interface disconnect switch.  
4. Open the isolation transformer circuit breaker.  
5. Install lockout devices on the isolation transformer circuit breaker and PV disconnect switch.  
TURN-ON PROCEDURE  
Refer to Section 3 for a detailed first-time turn on procedure.  
1. Remove any lockout devices from the isolation transformer circuit breaker and PV disconnect  
switch.  
2. Close the isolation transformer circuit breaker.  
3. Close the AC interface disconnect switch.  
4. Close the DC interface (PV array) disconnect switch.  
5. Turn the on/off switch to the on position.  
After a 15 second initialization period and a 5 minute wake up period, the PV-225208 will automatically begin  
power tracking, given the PV voltage is greater than the PV start voltage setpoint.  
DOCUMENT: 151811  
PV-225208 Photovoltaic Inverter  
6-2  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 7  
APPENDIX  
FAULTS CODES  
Refer to section 5 for detailed fault code descriptions.  
H - Fault(s) triggered by hardware  
S - Fault(s) triggered by software  
Error  
Code  
Error  
Code  
Fault Source(s)  
H/S  
Fault Source(s)  
H/S  
0000 No Faults  
0062 Line Frequency Too High  
0063 Line Voltage Too Low  
0064 Line Voltage Too High  
012A Interrupt Time-Out  
(S)  
(S)  
(S)  
(S)  
(H)  
(H)  
(S)  
(S)  
(S)  
(H)  
002C Matrix Over-Temperature  
002E State Machine Failure  
002F Software Parameter Out of Date  
0031 Ground Current Fault  
0032 PV Over-Voltage  
(S)  
(S)  
(S)  
(S)  
(S)  
(S)  
(S)  
0230 Door Interlock  
0430 PV Auxiliary Contact Block  
XX25 Line Matrix Gate Drive  
YY27 Line Matrix Over-Current  
0828 PV Over-Current  
0040 In Programming Mode  
0042 Bad Memory  
0045 Line Matrix Control Failure to Turn On (S)  
0046 Line Matrix Control Failure to Turn Off (S)  
8021 DC Bus Voltage Too High  
0061 Line Frequency Too Low  
(S)  
READ/WRITE PARAMETER MENU  
Read-Only Parameters  
Parameters  
ID Type Units Data Limits Default Descriptions  
Current States:  
0-Initilizing  
1-Key-Disabled  
2-Sleeping  
3-Starting  
4-Power-Tracking  
5-Manual Current  
6-Matrix Test  
7-Faulted  
Current Operating  
State  
1 Read  
N/A  
N/A  
N/A  
N/A  
N/A  
Goal States:  
0-Shut Down  
1-Power-Tracking  
2-Manual Current  
3-Matrix Test  
System Goal State  
2 Read N/A  
DOCUMENT: 151811  
7-1  
PV-225208 Photovoltaic Inverter  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 7  
APPENDIX  
Parameters  
ID Type Units Data Limits Default Descriptions  
Fault Code  
3
Read N/A  
N/A  
N/A  
See Fault Codes Above  
Inverter States:  
0-Shut Down  
1-Standby  
Inverter State  
4
Read N/A  
N/A  
N/A  
2-Starting  
3-Main-Setting  
4-On-Line  
Line A-B Voltage  
5
6
7
8
9
Read Vrms  
Read Vrms  
Read Vrms  
Read Arms  
Read Arms  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
Line to Line Voltage  
Line to Line Voltage  
Line to Line Voltage  
Line B-C Voltage  
Line C-A Voltage  
Line A Current  
Line B Current  
Line C Current  
10 Read Arms  
11 Read kVA  
Inverter Real Power  
N/A  
N/A  
N/A  
N/A  
Inverter Matrix  
Temperature  
12 Read  
°C  
PV States:  
0-Shut Down  
1-Sleep  
2-Wakeup  
3-Online  
PV State  
13 Read N/A  
N/A  
N/A  
4-Sleep-Test  
PV Voltage  
PV Current  
PV Power  
14 Read VDC  
15 Read ADC  
16 Read kW  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
Ground Fault Current  
Peak Power On/Off  
17 Read Arms  
18 Read N/A  
N/A  
N/A  
N/A  
N/A  
0-On  
1-Off  
Inverter Frequency  
19 Read  
Hz  
N/A  
N/A  
N/A  
N/A  
Maximum Inverter  
Power  
Maximum Line Power  
Recorded by PCU  
20 Read kVA  
DOCUMENT: 151811  
7-2  
PV-225208 Photovoltaic Inverter  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 7  
APPENDIX  
Parameters  
ID Type Units  
Data Limits  
Default Descriptions  
Maximum Line Power  
Recorded by PCU  
Maximum PV Power  
21 Read kW  
N/A  
1:1  
1:1  
Maximum Inverter  
Current (phase A)  
Maximum Line Current  
Recorded by PCU  
22 Read Arms  
23 Read ADC  
N/A  
N/A  
Maximum PV Current  
Available to be  
Commanded by the PV  
Power Tracker  
Commanded PV  
Current  
1:1  
Maximum AC Voltage  
fault setpoint *  
Maximum AC Voltage 32 Write Volts 190 < V < 229  
Minimum AC Voltage 33 Write Volts 183 < V < 220  
229  
183  
60.5  
59.3  
10  
Minimum AC Voltage  
fault setpoint *  
Maximum AC  
Frequency  
59.3 < Hz <  
60.5  
Maximum AC Frequency  
fault setpoint *  
34 Write  
35 Write  
Hz  
Hz  
Minimum AC  
Frequency  
59.3 < Hz <  
60.5  
Minimum AC Frequency  
fault setpoint *  
Maximum Ground  
Fault Interrupt  
Ground fault current  
setpoint  
36 Write Amps  
1 < I < 20  
Peak Power Tracker  
Reference Voltage  
PPT V Ref  
PV V Start  
PV T Start  
PV T Stop  
PV P Stop  
37 Write Volts 300 < V < 600  
38 Write Volts 300 < V < 600  
400  
440  
300  
20  
PV power tracker wake-  
up voltage  
Time delay for PV  
wake-up  
39 Write Sec  
40 Write Sec  
41 Write kW  
0 < T < 1200  
0 < T < 1200  
Time delay for PV sleep  
test  
0.2 < kW <  
10.0  
PV power point to begin  
sleep test timer  
1.0  
* Inverter trips off line within two cycles on over/under voltage and frequency faults. It should be  
noted that the voltage trip limits can be up to 1% off from the actual grid voltage at full load due to  
the 1% regulation of the isolation transformer. The PV-225208 uses phase to phase voltage measurement  
to detect the under/over voltage trip limits. For an unbalanced, single phase voltage variation of +10% and  
-12% as per UL1741 the trip limits must be set to 220V for maximumAC voltage and 193Vfor minimum  
AC voltage. Consult your local utility for their specific requirement.  
DOCUMENT: 151811  
7-3  
PV-225208 Photovoltaic Inverter  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 7  
APPENDIX  
Parameters  
ID Type Units Data Limits Default Descriptions  
Percent of maximum allowable  
PV power tracker mode current  
I PPT Max %  
42 Write  
43 Write  
%
%
0 < % < 100  
0 < % < 100  
100  
25  
Percent of maximum allowable  
PV manual mode current  
I Manual %  
Turns power tracker on or off. If  
off the power tracker will  
regulate voltage at the reference  
setpoint.  
PPT Enable  
44 Write N/A  
0 or 1  
1
0 = Off  
1 = On  
PPT Rate  
45 Write Sec 0.1 < T < 10.0  
46 Write Volts 0 < V < 10.0  
0.5  
1.0  
Power tracker update rate  
Voltage perturbation step of  
power tracker  
PPT V Step  
WARRANTY AND CERTIFICATION  
Xantrex Inverter Warranty Registration  
Underwriters Laboratories Compliance Of Standard UL1741  
DRAWINGS LIST  
151828 : Schematic, System, Grid Tied PV Inverter, PV-225208  
151807 : Envelope Drawing, Grid Tied Inverter, PV-225208  
151808 : Enclosure, Main, Control Components, PV-225208  
151809 : Enclosure,AC Interface, PV-225208  
151810 : Enclosure, DC Interface, PV-225208  
151812 : Transformer, 225 kVA, 3-Pole, 60 Hz, 98% Efficient, 208Y/120 or 480Y/277  
DOCUMENT: 151811  
7-4  
PV-225208 Photovoltaic Inverter  
Operation and Maintenance Manual  
Copyright 2003, Xantrex Technology Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Xantrex Technology, Inc.  
Distributed Power Markets  
161G South Vasco Road  
Livermore, CA 94550 USA  
Phone +1 925.245.5400  
Fax +1 925.245.1022  
XANTREX PV SERIES LIMITED WARRANTY AND REGISTRATION  
Xantrex Technology warrants all equipment supplied to Customer under this purchase  
order against defects in workmanship and material for a period of (12) twelve months  
from delivery, provided that the equipment has been operated and maintained in  
accordance with the service manual provided with the equipment. Should Customer  
give Xantrex written notice of any such defects within the warranty period, and  
Xantrex’s inspection confirms the existence of such defects, Xantrex shall correct the  
defects, either by repair or replacement, at its sole option.  
For wall-mounted products (generally, below 30 kW in rating), defective products must  
be returned to Xantrex or it Authorized Service Center in the original or equivalent  
packaging. The cost of transportation and insurance on items returned for service is at  
the Customer’s expense. Return transportation and insurance expense shall be borne by  
Xantrex.  
For floor mounted inverter products (generally, 30 kW in rating and above), warranty  
repairs or replacements are performed at the installation site. Xantrex’s material, labor,  
freight and travel/living expenses associated with such repair or replacement shall be  
borne by Xantrex.  
In either case, Customer’s labor and travel/living expense shall be borne by Customer.  
Xantrex will assume no expense, liability or responsibility for repairs made by or for  
Customer without written authority from Xantrex. Xantrex shall not be responsible for  
any consequential, incidental or similar damages.  
THE FOREGOING WARRANTIES ARE IN LIEU OF ALL OTHER WARRANTIES, EXPRESS  
OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF  
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.  
Project Name  
Customer PO #  
Inverter Serial #  
Delivery Date  
______________________  
______________________  
______________________  
______________________  
Xantrex Authorized Signature:  
________________________  
Customer Authorized Signature:  
________________________  
________________________  
Date  
________________________  
Date  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Xantrex Technology Inc. PV-225208  
Photovoltaic Inverter  
Major Parts List  
Assembly Description: Main Enclosure, Control Components, PV-225208  
Xantrex Technology Assembly # 151808  
Item #  
Qty  
Reference Designator  
Xantrex Technology Part #  
Description  
Upper Enclosure  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
1
1
2
1
1
3
1
2
2
1
7
2
1
1
1
2
3
1
2
4
5
1
1
1
-
-
-
T1  
T2  
1-151751-01  
1-151775-01  
1-150209-02  
1-151614-01  
1-151615-01  
1-151774-01  
1-150204-03  
1-112129-01  
1-111196-01  
1-151782-01  
1-113712-01  
1-151187-01  
1-151023-01  
1-160006-01  
1-150343-01  
1-119154-01  
1-112590-03  
1-112590-01  
1-117452-02  
1-117452-07  
1-117452-04  
1-150329-01  
1-150329-01  
1-151787-01  
Fab, Enclosure, Upper, 2 Bay, PV225208  
Assy, PCU, W/Power Supply, PV225208  
Assy, Matrix  
Transformer, 208:24V, 250VA, 1Phase  
Transformer, 208:120V, 500VA, 1 Phase  
Transformer, 2.4V, 5V 1-Phase  
Contactor, 630A, 3-Phase  
SSR, 10A, 240V  
Capacitor, .15uF, 1000V, Ceramic Disc  
Capacitor, 10 KVAR, 3P, 600V  
CT, Hall Effect, 500A, AC  
Fan, 1/4 HP, 208VAC, 1-Phase  
Fan, 120V, 4", Internal  
Power Supply, Single Out, +15VDC  
Block, Terminal, 2-Pos  
Block, Terminal, 4-Pos, 600V  
Block, Fuse, 600V, 3-Pole  
Block, Fuse, 600V, 2-Pole  
Fuse, 15A, 500VDC  
T3,T4,T5  
K1  
SSR1,SSR2  
C4,C5  
C1  
CT1,2,3,4,5,6,8  
B1,B2  
B3  
PS1  
TB4  
TB2,TB3  
F4-12  
F13,14  
F7,8  
F9-12  
F4-6,13,14  
S6  
Fuse, 6A, 500VDC  
Fuse, 1A, 500VDC  
Switch, Interlock, Door  
Switch, Interlock, Door  
Current, Transducer, 1000A  
Lower Enclosure  
TB1  
CT7  
25  
26  
27  
28  
1
2
2
2
Qty  
1
-
1-151750-01  
1-151605-01  
1-151024-01  
Fab, Enclosure, Lower, 2 Bay, PV225208  
Reactor, 3PH, 130uH, 312 Arms  
Fan, 10", 600 CFM  
Thermostat, Disk, Snap, 157 to 169C  
Enclosure Door (Not Shown)  
Assy, LCD, W/Keypad  
L1,L2  
B4,B5  
TS1,TS2  
Reference Designator  
1-151530-02  
Xantrex Technology Part #  
1-151128-02  
29  
30  
31  
-
S3  
-
1
2
1-117906-01  
1-150326-01  
Switch, On/Off, 2 Pole  
Contact Block, NC  
151808  
Sheet 2 of 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Xantrex Technology Inc. PV-225208  
Photovoltaic Inverter  
Major Parts List  
Assembly Description: Enclosure, AC Interface, PV-225208  
Xantrex Technology Assembly # 151809  
Item #  
Qty  
Reference Designator  
Xantrex Technology Part #  
Description  
1
2
3
4
5
6
7
1
1
1
3
3
1
1
-
-
S1  
F1-3  
F1-3  
SA1  
-
1-151784-01  
1-151754-01  
1-151669-03  
1-151465-03  
1-151785-01  
1-114653-01  
1-119648-01  
Fab, Enclosure, DC Interface, PV225208  
Fab, Panel, Encl, AC, PV225208  
Switch, Dscnct, Non-Fuse, 600V, 800A  
Fusebase, Sq Body Fuse Style  
Fuse, Sq Body, 800A, 700V  
Arrestor, Surge, MOV, 650V  
Bracket, Surge Arrestor, Mntg  
151809  
Sheet 2 of 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Xantrex Technology Inc. PV-225208  
Photovoltaic Inverter  
Major Parts List  
Assembly Description: Enclosure, DC Interface, PV-225208  
Xantrex Technology Assembly # 151810  
Item #  
Qty  
Reference Designator  
Xantrex Technology Part #  
Description  
1
2
3
4
5
1
1
1
1
1
-
-
1-151783-01  
1-151755-01  
1-151669-04  
1-151786-01  
1-151792-01  
Fab, Enclosure, DC Interface, PV225208  
Fab, Panel, Encl, DC, PV225208  
Switch, Dscnct, Non-Fuse, 600V, 1200A  
Contactor, 3P, 750A, 120VAC coil  
Block, Power Distribution, 1 Pole  
S2  
K2  
TB5  
151810  
Sheet 2 of 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Xantrex Technology Inc.  
161-G South Vasco Road  
Livermore, CA, USA 94550  
SOURCE CONTROL SPECIFICATION  
DOC NO.  
REV  
A
ECO  
DATE  
DRAWN  
Q.C.  
ENGR  
MFG  
1321  
12/9/2002  
CRF  
151812  
PART DESCRIPTION  
XFMR, 225KVA, 3 PHASE, 60Hz, 208Y  
MANUFACTURER  
SQUARE D  
MFG’S PART NO.  
XANTREX PART NO.  
208Y208  
208Y480  
225TQ56373 (Custom Built)  
225TQ56374 (Custom Built)  
1-151812-01  
1-151812-02  
DATA SOURCE:  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Weider Home Gym WEBE15420 User Manual
West Bend Coffeemaker 13500 User Manual
Whirlpool Clothes Dryer ELECTRIC AND GAS DRYER User Manual
Whirlpool Clothes Dryer WGD9450W User Manual
White Rodgers Thermostat 1F57 312 User Manual
Wolf Appliance Company Microwave Oven M I C R O W AV E O V E N User Manual
X Micro Tech Network Card WL 1502 User Manual
Xoro DVD Player HSD 2200 User Manual
Yamaha Camper 5TE F8197 10 User Manual
Zenith Flat Panel Television Z42LC6DF User Manual