Wolf Appliance Company Ventilation Hood 801640 User Manual

MODEL 801640  
Page 1  
EXTERIOR VENTILATOR KITS  
!
WARNING  
CAUTION  
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR  
INJURY TO PERSONS, OBSERVE THE FOLLOWING:  
1. For general ventilating use only.Do not use to exhaust hazard-  
ous or explosive materials and vapors.  
1. Use this unit only in the manner intended by the manufacturer.  
2. To avoid motor bearing damage and noisy and/or unbalanced  
impellers, keep drywall spray, construction dust, etc. off power  
unit.  
If you have questions, contact the manufacturer or your distribu-  
tor.  
2. Before servicing or cleaning unit, switch power off at service  
panel and lock the service disconnecting means to prevent  
power from being switched on accidentally. When the service  
disconnecting means cannot be locked, securely fasten a  
prominent warning device, such as a tag, to the service panel.  
3. Your ventilator motor has a thermal overload which will auto-  
matically shut off the motor if it becomes overheated.The motor  
will restart when it cools down. If the motor continues to shut  
off and restart, have the hood serviced.  
3. Installation work and electrical wiring must be done by a  
qualified person(s) in accordance with all applicable codes  
and standards, including fire-rated construction codes and  
standards.  
4. Please read specification label on product for further informa-  
tion and requirements.  
4. Sufficient air is needed for proper combustion and exhausting  
of gases through the flue (chimney) of fuel burning equip-  
ment to prevent backdrafting. Follow the heating equipment  
manufacturer’s guidelines and safety standards such as those  
published by the National Fire Protection Association (NFPA),  
and the American Society for Heating, Refrigeration and Air  
Conditioning Engineers (ASHRAE), and the local code authori-  
ties.  
SPECIFICATIONS  
5. When cutting or drilling into wall or ceiling, do not damage  
electrical wiring and other hidden utilities.  
MODEL VOLTS AMPS  
801640 120 2.4  
CFM  
DUCT SIZE  
6. Ducted fans must always be vented to the outdoors.  
7. Do not use this unit with an additional speed control device.  
8. To reduce the risk of fire, use only steel ductwork.  
9. This unit must be grounded.  
600  
10 "DIA.  
TO REDUCE THE RISK OF A COOKTOP GREASE FIRE:  
1. Never leave surface units unattended at high settings.Boilovers  
cause smoking and greasy spillovers that may ignite.Heat oils  
slowly on low or medium settings.  
2. Always turn hood ON when cooking at high heat or when  
cooking flaming foods.  
3. Clean ventilating fans frequently.Grease should not be allowed  
to accumulate on fan or filter.  
PLAN THE INSTALLATION  
4. Use proper pan size.Always use cookware appropriate for the  
size of the surface element.  
1. Locate the ventilator so the length of the duct run and number  
of elbows and transitions needed are kept to a minimum.  
TO REDUCE THE RISK OF INJURY TO PERSONS IN THE  
EVENT OF A COOKTOP GREASE FIRE, OBSERVE THE  
FOLLOWING:*  
2. Where possible, ventilator should be located between wall  
studs or roof rafters.  
3. Avoid pipes, wires, or other ductwork that may be running  
through the wall.  
1. SMOTHER FLAMES with a close-fitting lid, cookie sheet, or  
metal tray, then turn off the burner.BE CAREFULTO PREVENT  
BURNS. If the flames do not go out immediately, EVACUATE  
AND CALL THE FIRE DEPARTMENT.  
4. Be sure that there is enough space for any transitions that  
may be needed between the ventilator and the connecting  
ductwork.  
2. NEVER PICK UP A FLAMING PAN - You may be burned.  
5. For best performance, locate transitions nearest to ventilator.  
3. DO NOT USE WATER, including wet dishcloths or towels -  
violent steam explosion will result.  
4. Use an extinguisher ONLY if:  
A. You know you have a Class ABC extinguisher and you  
already know how to operate it.  
B. The fire is small and contained in the area where it started.  
C. The fire department is being called.  
D. You can fight the fire with your back to an exit.  
* Based on “Kitchen Fire Safety Tips” published by NFPA.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL 801640  
Page 3  
WALL MOUNT  
INSTALLATION  
For use with Models CTWH30,CTWH36,IH4227,W302418-W422418,W302718-W422418,W362210-W482210.  
PREPARE THE WALL  
WIRE THE VENTILATOR  
BLACK  
TO  
BLACK  
24¾"  
10¾"  
REMOVE  
SIDING  
8½"  
127  
/8  
"
11" dia.  
hole  
Pilot  
Hole  
WHITE  
TO  
WHITE  
120 VAC  
LINE IN  
GREEN  
TO  
GREEN  
28¼"  
4 Remove 7 COVER SCREWS and lift off ventilator cover.  
Remove BIRD SCREEN and WIRING COVER.  
91  
/8  
"
1¼"  
dia. hole  
5 Feed the electric power cable through the 1¼" DIAMETER  
HOLE and connect cable to ventilator with a proper  
connector for the type of cable being used.  
6 Connect BLACK TO BLACK, WHITE TO WHITE, and the  
GREEN TO GREEN or bare wire. Replace wiring cover.  
7¼"  
INSTALL THE VENTILATOR  
OUTSIDE - WALL VIEW  
From inside the wall:  
6
Mounting  
7 Cover  
Screws  
Holes  
1 Drill a PILOT HOLE through the wall, 8½" from the inside  
edge of a WALL STUD.  
From outside - on the wall:  
2 Measure and mark the 25" x 29½" rectangle.Cut and remove  
Shipping  
Cardboard  
only the siding inside this rectangle.  
3 Measure and mark the 11" DIAMETER HOLE and the 1¼"  
DIAMETER HOLE. Cut these holes all the way through the  
wall.  
Wiring  
Cover  
Bird Screen  
Flashing Sheet  
OUTSIDE - WALL VIEW  
7 Remove SHIPPING CARDBOARD from blower wheel.  
8 Place ventilator on wall so that ventilator's discharge collar  
fits into 11" diameter hole.  
9 Use the 6 screws (provided) to attach the ventilator to the  
wall. 6 MOUNTING HOLES are provided.  
10 Seal the screw heads and edges of the flashing sheet with  
a good grade of roofing cement.  
11 Check for free movement of the spring-loaded damper,  
re-install BIRD SCREEN and ventilator cover. Turn on  
power and check operation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL 801640  
Page 4  
ATTACH POWER CORD TO HOOD  
Some wall and island hoods (excluding CTWH30, CTWH36, IH4227) require the use of a separate  
power cord and strain relief bushing (included), for proper wiring of exterior blowers. Please refer to  
the installation instructions supplied with your Wolf hood.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL 801641  
Page 1  
EXTERIOR VENTILATOR KITS  
!
WARNING  
CAUTION  
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR  
INJURY TO PERSONS, OBSERVE THE FOLLOWING:  
1. For general ventilating use only.Do not use to exhaust hazard-  
ous or explosive materials and vapors.  
1. Use this unit only in the manner intended by the manufacturer.  
2. To avoid motor bearing damage and noisy and/or unbalanced  
impellers, keep drywall spray, construction dust, etc. off power  
unit.  
If you have questions, contact the manufacturer or your distribu-  
tor.  
2. Before servicing or cleaning unit, switch power off at service  
panel and lock the service disconnecting means to prevent  
power from being switched on accidentally. When the service  
disconnecting means cannot be locked, securely fasten a  
prominent warning device, such as a tag, to the service panel.  
3. Your ventilator motor has a thermal overload which will auto-  
matically shut off the motor if it becomes overheated.The motor  
will restart when it cools down. If the motor continues to shut  
off and restart, have the hood serviced.  
3. Installation work and electrical wiring must be done by a  
qualified person(s) in accordance with all applicable codes  
and standards, including fire-rated construction codes and  
standards.  
4. Please read specification label on product for further informa-  
tion and requirements.  
4. Sufficient air is needed for proper combustion and exhausting  
of gases through the flue (chimney) of fuel burning equip-  
ment to prevent backdrafting. Follow the heating equipment  
manufacturer’s guidelines and safety standards such as those  
published by the National Fire Protection Association (NFPA),  
and the American Society for Heating, Refrigeration and Air  
Conditioning Engineers (ASHRAE), and the local code authori-  
ties.  
SPECIFICATIONS  
5. When cutting or drilling into wall or ceiling, do not damage  
electrical wiring and other hidden utilities.  
MODEL VOLTS AMPS  
801641 120 5.7  
CFM  
DUCT SIZE  
6. Ducted fans must always be vented to the outdoors.  
7. Do not use this unit with an additional speed control device.  
8. To reduce the risk of fire, use only steel ductwork.  
9. This unit must be grounded.  
900  
10 "DIA.  
TO REDUCE THE RISK OF A COOKTOP GREASE FIRE:  
1. Never leave surface units unattended at high settings.Boilovers  
cause smoking and greasy spillovers that may ignite.Heat oils  
slowly on low or medium settings.  
2. Always turn hood ON when cooking at high heat or when  
cooking flaming foods.  
3. Clean ventilating fans frequently.Grease should not be allowed  
to accumulate on fan or filter.  
PLAN THE INSTALLATION  
4. Use proper pan size.Always use cookware appropriate for the  
size of the surface element.  
1. Locate the ventilator so the length of the duct run and number  
of elbows and transitions needed are kept to a minimum.  
TO REDUCE THE RISK OF INJURY TO PERSONS IN THE  
EVENT OF A COOKTOP GREASE FIRE, OBSERVE THE  
FOLLOWING:*  
2. Where possible, ventilator should be located between wall  
studs or roof rafters.  
3. Avoid pipes, wires, or other ductwork that may be running  
through the wall.  
1. SMOTHER FLAMES with a close-fitting lid, cookie sheet, or  
metal tray, then turn off the burner.BE CAREFULTO PREVENT  
BURNS. If the flames do not go out immediately, EVACUATE  
AND CALL THE FIRE DEPARTMENT.  
4. Be sure that there is enough space for any transitions that  
may be needed between the ventilator and the connecting  
ductwork.  
2. NEVER PICK UP A FLAMING PAN - You may be burned.  
5. For best performance, locate transitions nearest to ventilator.  
3. DO NOT USE WATER, including wet dishcloths or towels -  
violent steam explosion will result.  
4. Use an extinguisher ONLY if:  
A. You know you have a Class ABC extinguisher and you  
already know how to operate it.  
B. The fire is small and contained in the area where it started.  
C. The fire department is being called.  
D. You can fight the fire with your back to an exit.  
* Based on “Kitchen Fire Safety Tips” published by NFPA.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL 801641  
Page 2  
ROOF MOUNT  
INSTALLATION  
For use with Models CTWH30, CTWH36, IH4227, DD30R, DD36R, DD45R,W30-662418,  
W30-662718,W36-482210, I36-663418, L34-582212.  
PREPARE THE ROOF  
WIRE THE VENTILATOR  
BLACK  
TO  
BLACK  
20¾"  
8½"  
REMOVE  
SHINGLES  
11"  
dia.  
hole  
103  
/
8
"
Pilot  
Hole  
WHITE  
TO  
WHITE  
120 VAC  
LINE IN  
GREEN  
TO  
GREEN  
20½"  
5 Remove 7 COVER SCREWS and lift off ventilator cover.  
Remove BIRD SCREEN and WIRING COVER.  
6 Feed the electric power cable through the 1¼" DIAMETER  
HOLE and connect cable to ventilator with a proper  
connector for the type of cable being used.  
91  
/
8
"
1¼"  
dia. hole  
7 Connect BLACK TO BLACK, WHITE TO WHITE, and the  
GREEN TO GREEN or bare wire. Replace wiring cover.  
7¼"  
INSTALL THE VENTILATOR  
OUTSIDE - ROOF VIEW  
6
From inside the attic space:  
Mounting  
7 Cover  
Screws  
1 Drill a PILOT HOLE up through the roof, 8½" from the inside  
edge of a ROOF RAFTER.  
Holes  
From outside - on the roof:  
Remove  
roofing  
2 Measure and mark the 20¾" x 20½" rectangle. Cut and  
remove only the shingles inside this rectangle.  
nails from  
Shipping  
top 2/3 of  
3 Measure and mark the 11" DIAMETER HOLE and the 1¼"  
DIAMETER HOLE. Cut these holes all the way through the  
roof.  
Cardboard  
shingles.  
Wiring  
Cover  
2
Bird Screen  
Flashing Sheet  
"
¾
6
2
"
OUTSIDE - ROOF VIEW  
"
¼
8
2
4
2
¾
"
8 Remove SHIPPING CARDBOARD from blower wheel.  
9 Remove roofing nails from top 2/3 of shingles around cut-out  
area.  
10 Slide the ventilator's FLASHING SHEET up and under  
the loosened shingles until ventilator's discharge collar  
fits into 11" diameter hole.  
For flat roof installations:  
4 Build a curb that will mount the blower at a minimum pitch of  
2/12. Discharge end of the blower should be pointed away  
from prevailing winds.  
11 Use the 6 screws (provided) to attach the ventilator to the  
roof. 6 MOUNTING HOLES are provided.  
12 Seal the screw heads, loosened shingles, and edges of  
the flashing sheet, with a good grade of roofing cement.  
13 Check for free movement of the spring-loaded damper,  
re-install BIRD SCREEN and ventilator cover. Turn on  
power and check operation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL 801641  
Page 3  
WALL MOUNT  
INSTALLATION  
For use with Models CTWH30, CTWH36, IH4227, DD30R, DD36R, DD45R,W30-662418,  
W30-662718,W36-482210, I36-663418, L34-582212.  
PREPARE THE WALL  
WIRE THE VENTILATOR  
BLACK  
TO  
BLACK  
24¾"  
10¾"  
REMOVE  
SIDING  
8½"  
127  
/8  
"
11" dia.  
hole  
Pilot  
Hole  
WHITE  
TO  
WHITE  
120 VAC  
LINE IN  
GREEN  
TO  
GREEN  
28¼"  
4 Remove 7 COVER SCREWS and lift off ventilator cover.  
Remove BIRD SCREEN and WIRING COVER.  
91  
/8  
"
1¼"  
dia. hole  
5 Feed the electric power cable through the 1¼" DIAMETER  
HOLE and connect cable to ventilator with a proper  
connector for the type of cable being used.  
6 Connect BLACK TO BLACK, WHITE TO WHITE, and the  
GREEN TO GREEN or bare wire. Replace wiring cover.  
7¼"  
INSTALL THE VENTILATOR  
OUTSIDE - WALL VIEW  
From inside the wall:  
6
Mounting  
7 Cover  
Screws  
Holes  
1 Drill a PILOT HOLE through the wall, 8½" from the inside  
edge of a WALL STUD.  
From outside - on the wall:  
2 Measure and mark the 25" x 29½" rectangle.Cut and remove  
Shipping  
Cardboard  
only the siding inside this rectangle.  
3 Measure and mark the 11" DIAMETER HOLE and the 1¼"  
DIAMETER HOLE. Cut these holes all the way through the  
wall.  
Wiring  
Cover  
Bird Screen  
Flashing Sheet  
OUTSIDE - WALL VIEW  
7 Remove SHIPPING CARDBOARD from blower wheel.  
8 Place ventilator on wall so that ventilator's discharge collar  
fits into 11" diameter hole.  
9 Use the 6 screws (provided) to attach the ventilator to the  
wall. 6 MOUNTING HOLES are provided.  
10 Seal the screw heads and edges of the flashing sheet with  
a good grade of roofing cement.  
11 Check for free movement of the spring-loaded damper,  
re-install BIRD SCREEN and ventilator cover. Turn on  
power and check operation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL 801641  
Page 4  
ATTACH POWER CORD TO HOOD  
Some wall and island hoods (excluding CTWH30, CTWH36, IH4227) require the use of a separate  
power cord and strain relief bushing (included), for proper wiring of exterior blowers. Please refer to  
the installation instructions supplied with your Wolf hood.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL 801642  
Page 1  
EXTERIOR VENTILATOR KITS  
!
WARNING  
CAUTION  
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR  
INJURY TO PERSONS, OBSERVE THE FOLLOWING:  
1. For general ventilating use only.Do not use to exhaust hazard-  
ous or explosive materials and vapors.  
1. Use this unit only in the manner intended by the manufacturer.  
2. To avoid motor bearing damage and noisy and/or unbalanced  
impellers, keep drywall spray, construction dust, etc. off power  
unit.  
If you have questions, contact the manufacturer or your distribu-  
tor.  
2. Before servicing or cleaning unit, switch power off at service  
panel and lock the service disconnecting means to prevent  
power from being switched on accidentally. When the service  
disconnecting means cannot be locked, securely fasten a  
prominent warning device, such as a tag, to the service panel.  
3. Your ventilator motor has a thermal overload which will auto-  
matically shut off the motor if it becomes overheated.The motor  
will restart when it cools down. If the motor continues to shut  
off and restart, have the hood serviced.  
3. Installation work and electrical wiring must be done by a  
qualified person(s) in accordance with all applicable codes  
and standards, including fire-rated construction codes and  
standards.  
4. Please read specification label on product for further informa-  
tion and requirements.  
4. Sufficient air is needed for proper combustion and exhausting  
of gases through the flue (chimney) of fuel burning equip-  
ment to prevent backdrafting. Follow the heating equipment  
manufacturer’s guidelines and safety standards such as those  
published by the National Fire Protection Association (NFPA),  
and the American Society for Heating, Refrigeration and Air  
Conditioning Engineers (ASHRAE), and the local code authori-  
ties.  
SPECIFICATIONS  
5. When cutting or drilling into wall or ceiling, do not damage  
electrical wiring and other hidden utilities.  
MODEL VOLTS AMPS  
801642 120 3.0  
CFM  
DUCT SIZE  
6. Ducted fans must always be vented to the outdoors.  
7. Do not use this unit with an additional speed control device.  
8. To reduce the risk of fire, use only steel ductwork.  
9. This unit must be grounded.  
1200  
10" DIA.  
TO REDUCE THE RISK OF A COOKTOP GREASE FIRE:  
1. Never leave surface units unattended at high settings.Boilovers  
cause smoking and greasy spillovers that may ignite.Heat oils  
slowly on low or medium settings.  
2. Always turn hood ON when cooking at high heat or when  
cooking flaming foods.  
3. Clean ventilating fans frequently.Grease should not be allowed  
to accumulate on fan or filter.  
PLAN THE INSTALLATION  
4. Use proper pan size.Always use cookware appropriate for the  
size of the surface element.  
1. Locate the ventilator so the length of the duct run and number  
of elbows and transitions needed are kept to a minimum.  
TO REDUCE THE RISK OF INJURY TO PERSONS IN THE  
EVENT OF A COOKTOP GREASE FIRE, OBSERVE THE  
FOLLOWING:*  
2. Where possible, ventilator should be located between wall  
studs or roof rafters.  
3. Avoid pipes, wires, or other ductwork that may be running  
through the wall.  
1. SMOTHER FLAMES with a close-fitting lid, cookie sheet, or  
metal tray, then turn off the burner.BE CAREFULTO PREVENT  
BURNS. If the flames do not go out immediately, EVACUATE  
AND CALL THE FIRE DEPARTMENT.  
4. Be sure that there is enough space for any transitions that  
may be needed between the ventilator and the connecting  
ductwork.  
2. NEVER PICK UP A FLAMING PAN - You may be burned.  
5. For best performance, locate transitions nearest to ventilator.  
3. DO NOT USE WATER, including wet dishcloths or towels -  
violent steam explosion will result.  
4. Use an extinguisher ONLY if:  
A. You know you have a Class ABC extinguisher and you  
already know how to operate it.  
B. The fire is small and contained in the area where it started.  
C. The fire department is being called.  
D. You can fight the fire with your back to an exit.  
* Based on “Kitchen Fire Safety Tips” published by NFPA.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL 801642  
Page 2  
ROOF MOUNT  
INSTALLATION  
For use with Models CTWH30, CTWH36, IH4227, DD30R, DD36R, DD45R, W30-662418, W30-662718,  
I36-663418, L34-582212.  
PREPARE THE ROOF  
WIRE THE VENTILATOR  
5 Remove 10  
COVER SCREWS  
and lift off  
15"  
ventilator cover.  
6 Feed the electric  
GROUND  
1¼" dia. hole  
power cable  
TO  
through the 1¼"  
DIAMETER HOLE  
and connect cable  
to ventilator with a  
proper connector  
for the type of  
GROUNDING  
SCREW  
REMOVE SHINGLES  
1211  
/
16"  
1"  
WHITE  
TO  
BLUE  
cable being used.  
20½"  
7 Connect BLACK  
TO BLACK,  
120  
VAC  
LINE  
IN  
WHITE TO BLUE,  
and GROUND  
TO GROUNDING  
SCREW.  
Pilot Hole  
(centered  
between rafters)  
11" dia.  
hole  
BLACK TO BLACK  
913/16"  
INSTALL THE VENTILATOR  
18"  
Drill 6  
Mounting  
Holes  
10 Cover  
Screws  
From inside the attic space:  
1 Drill a PILOT HOLE up through the roof, centered between  
ROOF RAFTERS.  
Remove  
roofing  
nails from  
top 2/3 of  
shingles.  
From outside - on the roof:  
2 Measure and mark the 18" x 20½" rectangle.Cut and remove  
only the shingles inside this rectangle.  
3 Measure and mark the 11" DIAMETER HOLE and the 1¼"  
DIAMETER HOLE. Cut these holes all the way through the  
roof.  
Flashing  
Sheet  
Damper  
"
2
"
Bird Screen  
½
9
2
"
7
OUTSIDE - ROOF VIEW  
8 Remove roofing nails from top 2/3 of shingles around  
2
2
"
cut-out area.  
9 Slide the ventilator's FLASHING SHEET up and under  
the loosened shingles until ventilator's discharge collar  
fits into 11" diameter hole.  
2
"
10 Use the 6 screws (provided) to attach the ventilator  
to the roof. DRILL 6 MOUNTING HOLES inside the  
ventilator, as necessary.  
For flat roof installations:  
4 Build a curb that will mount the blower at a minimum pitch of  
2/12. Discharge end of the blower should be pointed away  
from prevailing winds.  
11 Seal the screw heads, loosened shingles, and edges of  
the flashing sheet, with a good grade of roofing cement.  
12 Check for free movement of the spring-loaded  
DAMPER, and re-install the ventilator cover. Turn on  
power and check operation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL 801642  
Page 3  
WALL MOUNT  
INSTALLATION  
For use with Models CTWH30, CTWH36, IH4227, DD30R, DD36R, DD45R, W30-662418, W30-662718,  
I36-663418, L34-582212.  
PREPARE THE WALL  
WIRE THE VENTILATOR  
4 Remove 10  
COVER SCREWS  
and lift off  
17"  
ventilator cover.  
5 Feed the electric  
1¼" dia. hole  
Pilot Hole  
GROUND  
power cable  
TO  
through the 1¼"  
DIAMETER HOLE  
and connect cable  
to ventilator with a  
proper connector  
for the type of  
GROUNDING  
SCREW  
3
"
1411  
/16"  
(centered between studs)  
WHITE  
TO  
BLUE  
cable being used.  
29½"  
6 Connect BLACK  
TO BLACK,  
120  
VAC  
LINE  
IN  
WHITE TO BLUE,  
and GROUND  
TO GROUNDING  
SCREW.  
11" dia.  
REMOVE  
BLACK TO BLACK  
hole  
SIDING  
INSTALL THE VENTILATOR  
1113/16"  
Drill 6  
Mounting  
Holes  
10 Cover  
Screws  
22"  
From inside the wall:  
1 Drill a PILOT HOLE through the wall, centered between  
WALL STUDS.  
From outside - on the wall:  
2 Measure and mark the 22" x 29½" rectangle.Cut and remove  
only the siding inside this rectangle.  
Flashing  
Sheet  
3 Measure and mark the 11" DIAMETER HOLE and the 1¼"  
DIAMETER HOLE. Cut these holes all the way through the  
wall.  
Damper  
Bird Screen  
OUTSIDE - WROAOLLFVIEW  
7 Place ventilator on wall so that ventilator's discharge collar  
fits into 11" diameter hole.  
8 Use the 6 screws (provided) to attach the ventilator to the  
wall. DRILL 6 MOUNTING HOLES inside the ventilator, as  
necessary.  
9 Seal the screw heads and edges of the flashing sheet with  
a good grade of roofing cement.  
10 Check for free movement of the spring-loaded DAMPER  
and re-install ventilator cover. Turn on power and check  
operation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL 801642  
Page 4  
ATTACH POWER CORD TO HOOD  
Some wall and island hoods (excluding CTWH30, CTWH36, IH4227) require the use of a separate  
power cord and strain relief bushing (included), for proper wiring of exterior blowers. Please refer to  
the installation instructions supplied with your Wolf hood.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL 804701  
Page 1  
EXTERIOR VENTILATOR KITS  
!
WARNING  
CAUTION  
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR  
INJURY TO PERSONS, OBSERVE THE FOLLOWING:  
1. For general ventilating use only.Do not use to exhaust hazard-  
ous or explosive materials and vapors.  
1. Use this unit only in the manner intended by the manufacturer.  
2. To avoid motor bearing damage and noisy and/or unbalanced  
impellers, keep drywall spray, construction dust, etc. off power  
unit.  
If you have questions, contact the manufacturer or your distribu-  
tor.  
2. Before servicing or cleaning unit, switch power off at service  
panel and lock the service disconnecting means to prevent  
power from being switched on accidentally. When the service  
disconnecting means cannot be locked, securely fasten a  
prominent warning device, such as a tag, to the service panel.  
3. Your ventilator motor has a thermal overload which will auto-  
matically shut off the motor if it becomes overheated.The motor  
will restart when it cools down. If the motor continues to shut  
off and restart, have the hood serviced.  
3. Installation work and electrical wiring must be done by a  
qualified person(s) in accordance with all applicable codes  
and standards, including fire-rated construction codes and  
standards.  
4. Please read specification label on product for further informa-  
tion and requirements.  
4. Sufficient air is needed for proper combustion and exhausting  
of gases through the flue (chimney) of fuel burning equip-  
ment to prevent backdrafting. Follow the heating equipment  
manufacturer’s guidelines and safety standards such as those  
published by the National Fire Protection Association (NFPA),  
and the American Society for Heating, Refrigeration and Air  
Conditioning Engineers (ASHRAE), and the local code authori-  
ties.  
SPECIFICATIONS  
5. When cutting or drilling into wall or ceiling, do not damage  
electrical wiring and other hidden utilities.  
MODEL VOLTS AMPS  
804701 120 4.3  
CFM  
DUCT SIZE  
6. Ducted fans must always be vented to the outdoors.  
7. Do not use this unit with an additional speed control device.  
8. To reduce the risk of fire, use only steel ductwork.  
9. This unit must be grounded.  
1500  
10" DIA.  
TO REDUCE THE RISK OF A COOKTOP GREASE FIRE:  
1. Never leave surface units unattended at high settings.Boilovers  
cause smoking and greasy spillovers that may ignite.Heat oils  
slowly on low or medium settings.  
2. Always turn hood ON when cooking at high heat or when  
cooking flaming foods.  
3. Clean ventilating fans frequently.Grease should not be allowed  
to accumulate on fan or filter.  
PLAN THE INSTALLATION  
4. Use proper pan size.Always use cookware appropriate for the  
size of the surface element.  
1. Locate the ventilator so the length of the duct run and number  
of elbows and transitions needed are kept to a minimum.  
TO REDUCE THE RISK OF INJURY TO PERSONS IN THE  
EVENT OF A COOKTOP GREASE FIRE, OBSERVE THE  
FOLLOWING:*  
2. Where possible, ventilator should be located between wall  
studs or roof rafters.  
3. Avoid pipes, wires, or other ductwork that may be running  
through the wall.  
1. SMOTHER FLAMES with a close-fitting lid, cookie sheet, or  
metal tray, then turn off the burner.BE CAREFULTO PREVENT  
BURNS. If the flames do not go out immediately, EVACUATE  
AND CALL THE FIRE DEPARTMENT.  
4. Be sure that there is enough space for any transitions that  
may be needed between the ventilator and the connecting  
ductwork.  
2. NEVER PICK UP A FLAMING PAN - You may be burned.  
5. For best performance, locate transitions nearest to ventilator.  
3. DO NOT USE WATER, including wet dishcloths or towels -  
violent steam explosion will result.  
4. Use an extinguisher ONLY if:  
A. You know you have a Class ABC extinguisher and you  
already know how to operate it.  
B. The fire is small and contained in the area where it started.  
C. The fire department is being called.  
D. You can fight the fire with your back to an exit.  
* Based on “Kitchen Fire Safety Tips” published by NFPA.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL 804701  
Page 2  
ROOF MOUNT  
INSTALLATION  
For use with Models CTWH30, CTWH36, IH4227,W30-662418,W30-662718, I36-663418,  
L34-582212, DD30R, DD36R, DD45R.  
WIRE THE VENTILATOR  
PREPARE THE ROOF  
5 Remove 10  
COVER SCREWS  
and lift off  
ventilator cover.  
18"  
6 Feed the electric  
GROUND  
power cable  
TO  
through the 1¼"  
DIAMETER HOLE  
and connect cable  
to ventilator with a  
proper connector  
for the type of  
GROUNDING  
SCREW  
1¼" dia. hole  
REMOVE SHINGLES  
1211  
/
16"  
1"  
WHITE  
TO  
BLUE  
cable being used.  
7 Connect BLACK  
20½"  
TO BLACK,  
120  
VAC  
LINE  
IN  
WHITE TO BLUE,  
and GROUND  
TO GROUNDING  
SCREW.  
Pilot Hole  
(centered  
between rafters)  
11" dia.  
hole  
BLACK TO BLACK  
INSTALL THE VENTILATOR  
125  
/
8
"
Drill 6  
Mounting  
Holes  
21"  
10 Cover  
Screws  
From inside the attic space:  
1 Drill a PILOT HOLE up through the roof, centered between  
ROOF RAFTERS.  
Remove  
roofing  
nails from  
top 2/3 of  
shingles.  
From outside - on the roof:  
2 Measure and mark the 21" x 20½" rectangle.Cut and remove  
only the shingles inside this rectangle.  
Flashing  
Sheet  
3 Measure and mark the 11" DIAMETER HOLE and the 1¼"  
DIAMETER HOLE. Cut these holes all the way through the  
roof.  
Damper  
"
2
Bird Screen  
"
½
9
2
"
OUTSIDE - ROOF VIEW  
7
8 Remove roofing nails from top 2/3 of shingles around cut-out  
area.  
2
5
"
9 Slide the ventilator's FLASHING SHEET up and under the  
loosened shingles until ventilator's discharge collar fits into  
11" diameter hole.  
2
"
10 Use the 6 screws (provided) to attach the ventilator to the  
roof. DRILL 6 MOUNTING HOLES inside the ventilator,  
as necessary.  
For flat roof installations:  
4 Build a curb that will mount the blower at a minimum pitch of  
2/12. Discharge end of the blower should be pointed away  
from prevailing winds.  
11 Seal the screw heads, loosened shingles, and edges of  
the flashing sheet, with a good grade of roofing cement.  
12 Check for free movement of the spring-loaded DAMPER,  
and re-install the ventilator cover.Turn on power and check  
operation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL 804701  
Page 3  
WALL MOUNT  
INSTALLATION  
For use with Models CTWH30, CTWH36, IH4227,W30-662418,W30-662718, I36-663418,  
L34-582212, DD30R, DD36R, DD45R.  
WIRE THE VENTILATOR  
PREPARE THE WALL  
4 Remove 10  
COVER SCREWS  
and lift off  
ventilator cover.  
20"  
5 Feed the electric  
GROUND  
power cable  
TO  
through the 1¼"  
DIAMETER HOLE  
and connect cable  
to ventilator with a  
proper connector  
for the type of  
1¼" dia. hole  
GROUNDING  
SCREW  
Pilot Hole  
(centered between studs)  
WHITE  
TO  
3
"
1411  
/16"  
BLUE  
cable being used.  
6 Connect BLACK  
TO BLACK,  
29½"  
120  
VAC  
LINE  
IN  
WHITE TO BLUE,  
and GROUND  
TO GROUNDING  
SCREW.  
BLACK TO BLACK  
11" dia.  
REMOVE  
hole  
SIDING  
INSTALL THE VENTILATOR  
Drill 6  
Mounting  
Holes  
14 5/  
8
"
10 Cover  
Screws  
25"  
From inside the wall:  
1 Drill a PILOT HOLE through the wall, centered between  
WALL STUDS.  
From outside - on the wall:  
Flashing  
Sheet  
2 Measure and mark the 25" x 29½" rectangle.Cut and remove  
only the siding inside this rectangle.  
3 Measure and mark the 11" DIAMETER HOLE and the 1¼"  
DIAMETER HOLE. Cut these holes all the way through the  
wall.  
Damper  
Bird Screen  
OUTSIDE - WROAOLLFVIEW  
7 Place ventilator on wall so that ventilator's discharge collar  
fits into 11" diameter hole.  
8 Use the 6 screws (provided) to attach the ventilator to the  
wall. DRILL 6 MOUNTING HOLES inside the ventilator, as  
necessary.  
9 Seal the screw heads and edges of the flashing sheet with  
a good grade of roofing cement.  
10 Check for free movement of the spring-loaded DAMPER  
and re-install ventilator cover. Turn on power and check  
operation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL 804701  
Page 4  
ATTACH POWER CORD TO HOOD  
Some wall and island hoods (excluding CTWH30, CTWH36, IH4227) require the use of a separate  
power cord and strain relief bushing (included), for proper wiring of exterior blowers. Please refer to  
the installation instructions supplied with your Wolf hood.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Weed Eater Trimmer 530086725 User Manual
Whirlpool Convection Oven GBD279 User Manual
Whirlpool Range 9753051 User Manual
Whistler Marine Battery PRO 800W User Manual
White Outdoor Trimmer WH80BC User Manual
Windsor Vacuum Cleaner 86037580 User Manual
Windsor Vacuum Cleaner Priza User Manual
X Micro Tech Network Router WLAN 11b Access Point User Manual
Yamaha DVR CBX D5 User Manual
Zanussi Freezer 726323 User Manual