Western Telematic Network Card RPC 4840N User Manual

RPC-4840N  
Network Ready Remote Power Controller  
User's Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warnings and Cautions:  
No Serviceable Parts Inside;  
Authorized Service Personnel Only  
Do not attempt to repair or service this device yourself. Internal  
components must be serviced by authorized personnel only.  
Shock Hazard - Do Not Enter  
Nameplate Power Warning  
This device should only be operated with the type of power  
source indicated on the instrument nameplate. If you are not  
sure of the type of power service available, consult your local  
power company.  
Connect unit only to a properly measured supply. Use  
only three wire cord which is provided with the unit.  
Reliable earthing of this equipment must be maintained.  
Particular attention should be given to supply  
connections when connecting to power strips, rather than  
direct connections to the branch circuit.  
Rack Mount Installation  
When installing this device in an instrument rack, the following  
factors must be accounted for:  
1. Enclosed Racks: Enclosed racks must provide adequate  
ventilation. Make certain that the rack is not overly  
crowded and note that each unit in the rack generates its  
own heat. An enclosed rack should have louvered sides  
and a fan to circulate cooling air.  
When mounting the unit in an enclosed rack with a  
ventilation fan at the top of the rack, note that excessive  
heat generated by devices at the bottom of the rack can be  
drawn upward and into the ventilation slots of units  
located at the top. Make certain to provide adequate  
ventilation for equipment installed at the bottom of  
the rack.  
(Continued)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Rack Mount Installation (Continued)  
1. Enclosed Racks (Continued):  
The ambient within the rack may be greater than room  
ambient. Installation should be such that the amount of air  
flow required for safe operation is not compromised. The  
maximum temperature for the equipment in this  
environment is 45°C. Consideration should be given to the  
maximum rated ambient.  
Installation should be such that a hazardous stability  
condition is not achieved due to uneven loading.  
2. Open Racks: Make certain that the rack frame does not  
block the ventilation slots on the instrument cover. If the  
device is installed on sliders, check the unit when seated  
all the way into the rack to make certain that ventilation  
slots are not blocked.  
Ventilation  
Slots in the instrument cover are provided to allow ventilation  
for heat dissipation. To ensure safe, reliable operation, these  
openings must not be covered or blocked.  
Disconnect Power  
If any of the following events are noted, immediately disconnect  
the unit from the power source and contact qualified service  
personnel:  
1. If the power cord becomes frayed or damaged.  
2. If liquid has been spilled into the device or if the device  
has been exposed to rain or water.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Download from Www.Somanuals.com. All Manuals Search And Download.  
List of Figures  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Introduction  
Network equipment sometimes "locks-up", requiring a service  
call just to flip the power switch to perform a simple reboot. The  
RPC-4840N Heavy Duty Remote Power Controller gives you the  
ability to reboot DC powered equipment from anywhere on the  
LAN/WAN, or if the network is down, to simply dial-in from a  
modem for out-of-band power control.  
Intelligent Power Control  
The RPC-4840N can communicate over any TCP/IP network  
using standard Telnet, or out-of-band using an external modem  
and terminal emulation. Each DC circuit can be assigned an  
individual password, device name, reboot delay time and unique  
power-up default status.  
Security  
Address specific IP security masks prevent unauthorized users  
from accessing the RPC command menu via network. The RPC  
provides two separate password security levels; System level and  
User level. The System password allows access to all  
configuration and command functions. The User password  
allows limited access to command functions.  
Easy to Use, Easy to Configure  
The RPC-4840N can be configured over the network, via modem,  
or locally via the RPC Console Port. Easy-to-use commands let  
you assign a location name, set system parameters and view  
circuit status. Circuits can be switched On, Off, or Booted using  
circuit numbers or user-defined names.  
Heavy Duty DC Power Control  
The RPC-4840N can control up to 40 amps of DC power per  
circuit. Since larger routers require as much as 30 amps, the  
RPC has power control to spare. The optional second Circuit  
Module allows the RPC to control power for two 40 amp, DC  
powered instruments.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features:  
· Dual 40 Amp Circuits  
· On/Off/Reboot Switching  
· Integral 10Base-T Interface  
· RS232 Modem and Console Ports  
· Circuit-Specific Password Security  
· Network Security Features  
· Manual On/Off Buttons  
Typographic Conventions  
Throughout this manual, typefaces and characters have been used  
to denote the following:  
COURIER FONT Indicates characters typed on the keyboard.  
For example, /ON 1 or /OFF 2.  
[Bold Font]  
Text set in bold face and enclosed in  
square brackets indicates a specific key.  
For example, [Enter] or [Esc].  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Unit Description  
2.1. Front Panel  
As shown in Figure 2.1, the RPC-4840N front panel includes a  
series of LED indicators which function as follows:  
ON: Lights when Power is applied to the Control Section.  
À
Á
RDY: Flashes when the RPC-4840N is ready to receive  
commands. Indicates that the Console Port has received  
the "Ready" signal from the control device.  
RXD: Lights when the RPC-4840N receives commands.  
Â
Ã
Circuit 1 Indicator: Lights when the Circuit 1 Switch is  
closed (Power ON to connected device.)  
Circuit 2 Indicator: Lights when the optional Circuit 2  
Switch is closed (Power ON to connected device.)  
Ä
2.2. Back Panel  
Network Port and Activity Indicator: A 10BaseT, RJ45  
À
Ethernet port for connection to your TCP/IP network. To  
communicate via network, you must first specify network  
parameters as described in Section 5.6.  
Note: The RPC-4840N features a 10BaseT interface.  
When connecting the RPC to a 100BaseT interface, note  
that most 100BaseT router switches will autosense to  
determine if the device is 100BaseT or 10BaseT and then  
configure the network interface accordingly. If your router  
switch does not autosense, then the network interface port  
must be manually set to 10BaseT.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Options Switch: Four DIP Switches which set the default  
baud rate, boot delay, echo mode, and timeout.  
Á
Â
Ã
Ä
Å
Æ
Default Button: Used in conjunction with the Reset  
Button to reset the unit to defaults (see Section 4.3.)  
Console Port: A Male RS-232, DB9 Connector, DTE  
configuration. For connection to a local PC.  
Modem Port: A Male RS-232, DB9 Connector, DTE  
configuration. For connection to an external modem.  
Reset Button: Used in conjunction with the Default  
Button to reset the unit to defaults (see Section 4.3.)  
Circuit Module 1: For connection to your DC power  
supply and DC powered device. Each circuit is capable of  
switching up to 40 Amps. Note that power for control  
functions is also derived from the Circuit 1 input terminal.  
A. ON Indicator: Lights when the corresponding Circuit  
Module is switched On (switch closed).  
B. Emergency Override Breaker: If the circuit is  
overloaded, the breaker pops out and opens the circuit.  
If necessary the Override Breaker can also be manually  
pulled out to open the circuit. To reset the circuit,  
press the Override Breaker in.  
Circuit Module 2 (Optional): For connection to a second  
DC power supply and DC powered device. Same as  
Circuit Module 1.  
Ç
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Quick Start Guide  
This section provides a brief overview of basic RPC-4840N  
capabilities, and describes a simple test that can be performed to  
determine if the unit is operating properly and demonstrate basic  
communication capabilities.  
Note that this Quick Start procedure is included only to provide a  
quick demonstration of basic RPC-4840N capabilities. In order  
to take full advantage of the complete range of features provided  
by this unit, it is strongly recommended that you should complete  
the entire Installation and Configuration sections after  
completing the Quick Start procedure.  
1. Apply Power to the RPC-4840N: Connect an appropriate  
power source to the input terminals on the Circuit 1  
terminal block, located on the RPC back panel. Prior to  
connecting the unit to your power supply, make certain to  
review the safety precautions listed at the beginning of this  
User's Guide.  
2. Connect a PC to the RPC-4840N: Attach a standard null  
modem cable from your PC COM port to the Console Port  
connector on the RPC back panel. For a description of the  
port interface, please refer to Appendix A.  
Note: When the RPC is shipped from the factory,  
Console Port communication parameters are set as  
follows: 9600 bps, 8 Data Bits, One Stop Bit, No  
Parity. Although the RPC allows these parameters  
to be easily redefined, for this Quick Start  
procedure, it is recommended that you configure  
your communications program to accept the default  
parameters.  
3. Access the Command Mode: Start your communications  
program and then press [Enter]; the System Help Screen  
should be displayed (Figure 3.1) and the "RPC>" command  
prompt should appear. For more information on command  
mode access, please refer to Section 5.2.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Configure Network Port: In order to communicate with  
the RPC-4840N via the Network Port, you must first  
define the IP Address, Subnet Mask, and Gateway  
Address. At the RPC> command prompt, type /N and  
press [Enter] to display the Network Parameters menu.  
a) Settings for network parameters will depend on the  
configuration of your individual network. Please  
contact your network administrator to determine  
appropriate settings for the IP Address, Subnet Mask,  
and Gateway Address.  
b) To assign network parameters, key in the number for  
the desired parameter, press [Enter], and then follow  
the instructions in the resulting submenu. For  
example, to define the IP Address, type 1 and  
press [Enter].  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Exit Command Mode: When you have finished setting  
Network Parameters, type /X and press [Enter] to exit the  
command mode at the Console Port.  
Note: Only one port may access the command  
mode at a given time. In order to allow access to the  
RPC unit via other ports, always exit from the  
command mode when finished communicating with  
the unit.  
6. Connect Network Cable: Connect your network interface  
to the RPC-4840N Network Port. The Network Port is an  
RJ45, 10BaseT Ethernet jack, for connection to a TCP/IP  
network.  
Note: The RPC features a 10BaseT Interface.  
When connecting to a 100BaseT interface, note that  
most router switches will autosense to determine if  
the device is 100BaseT or 10BaseT, and then  
configure the network interface accordingly. If your  
router switch does not autosense, then the network  
interface port must be manually set to 10BaseT.  
7. Network Access: Telnet to the RPC's IP address. For  
example, if the IP address is "119.1.1.1", on a UNIX  
system the Telnet command would be invoked as follows:  
$ telnet 119.1.1.1 [Enter]  
After the Telnet connection is established, the RPC should  
display the System Help Screen and the RPC> command  
prompt should appear, indicating that you have  
successfully accessed the RPC Command Mode via the  
Network Port.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. Test Boot Commands: When the RPC-4840N is powered  
up, both switched circuits will be set in the ON (closed)  
position. In order to test for proper operation, you may  
wish to perform the following test. Note that it is not  
necessary to connect a device to either switched circuit in  
order to perform this test.  
a) Reboot Circuits: To initiate a boot cycle at both  
circuits, go to the RPC> command prompt, type  
/BOOT * and press [Enter]. Power to both circuits  
will be switched OFF. After the Boot Delay Period  
(Default = 5 Seconds), the power to both circuits will  
then be automatically switched back ON. Note that the  
Circuit Status Indicators on the RPC front panel will  
also switch Off and On.  
b) Switch Circuits OFF: To switch both circuits OFF, go  
to the RPC> command prompt, type /OFF * and then  
press [Enter]. Power to both circuits will be switched  
OFF. Note that the Circuit Status Indicators will also  
be switched Off.  
c) Switch Circuits ON: To switch both circuits ON, go  
to the RPC> command prompt, type /ON * and then  
press [Enter]. Power to both circuits will be switched  
ON. Note that the Circuit Status Indicators will also be  
switched On.  
9. Exit Command Mode: Type /X and press [Enter] to exit  
from the RPC Command Mode, or disconnect using your  
Telnet program.  
This completes the introductory overview of the RPC-4840N.  
Prior to installing and operating the unit, please review the  
remainder of this User's Guide for important information  
regarding safety considerations, as well as more detailed  
installation, configuration, and operation instructions.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Installation  
4.1. Power Connection  
Connect your DC power supply to the Circuit 1 Input Terminals  
as shown in Figure 4.1. Connect the power supply lines from  
your DC Powered device to the Output Terminals. Note that the  
RPC-4840N is available with two separate 40 amp circuits. In  
order for both circuits to function, power must be connected to  
both input connectors on the unit's back panel.  
CAUTIONS:  
This device should only be operated with the  
type of power source indicated on the  
instrument nameplate. If you are not sure of the  
type of power service available, please contact  
your local power company.  
Reliable earthing (grounding) of this unit must  
be maintained. Particular attention should be  
given to supply connections when connecting to  
power strips, rather than directly to the branch  
circuit.  
"Always On" Architecture: The RPC features "Always On"  
architecture. This means that once the RPC is connected to your  
power supply, both circuits will always be set in the ON state,  
unless program commands are used to set the circuit(s) to  
the OFF state.  
Note: In addition to supplying power to the device  
connected to Circuit 1, the Circuit 1 power input  
also provides power for the RPC control section.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.2. Option Switches  
The Option Switches select default settings for the Baud Rate,  
Command Echo, Boot Delay and Disconnect Timeout. Default  
settings selected via the Option Switches will be used when the  
unit is reset to default parameters as described in Section 4.3.  
Notes:  
Although the Option Switches select default  
settings for these features, the RPC-4840N  
configuration menus can also be used to select  
operating parameters as described in Section 5.  
If Option Switch settings are changed, the new  
settings will not be applied until the unit is reset  
as described in Section 4.3.  
Option Switch settings are described below:  
Baud Rate: The default baud rate for both the Console Port and  
Modem Port.  
Boot Delay: The default Boot Delay setting. When a boot cycle  
is initiated, the Boot Delay determines the length of time each  
switched circuit will remain off until power is restored.  
Command Echo: The default setting for the Command Echo for  
the Console Port, Modem Port and Network Port. When  
enabled, commands entered at your keyboard will be sent to  
the RPC and echoed back to your display monitor.  
Disconnect Timeout: The default Disconnect Timeout value.  
This determines how long the RPC will wait for additional  
commands before automatically disconnecting. Note that  
when the RPC times out, DTR will drop, and the modem  
disconnect and initialize strings will be sent.  
Switch Function  
Up  
Down  
* = Factory Setting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3. Reset Unit to Defaults  
If Option Switch settings are changed, the new settings will not  
be applied until the unit is reset to default settings. There are  
two ways to reset the unit to defaults:  
Note: When these reset procedures are performed,  
all user selected parameters, including passwords  
and circuit names will be lost. Prior to performing  
these reset procedures, it is strongly recommended  
to save configuration parameters to an ASCII text  
file as described in Section 7.  
4.3.1.  
Default Button / Reset Button (Local)  
Typically, this method is used when you have immediate access  
to the installation site.  
1. Simultaneously press the DEFAULT and RESET buttons,  
located on the RPC Back Panel.  
2. Release the RESET button, wait for approximately five  
seconds, and then release the DEFAULT button.  
4.3.2.  
Default Parameters Option  
To reset the unit to default parameters using the General  
Parameters Menu's "Default Parameters" option, proceed  
as follows. Note that this method requires that you have already  
connected a local or remote PC to the unit and have accessed the  
command mode.  
1. Access the RPC Command Mode (see Section 6.1).  
2. At the RPC> command prompt, type /G and press [Enter].  
The General Parameters menu will appear.  
3. From the General Parameters menu, type A and press  
[Enter]. If command confirmation is enabled, the unit  
will display a "Sure?" prompt. Type Y and press [Enter]  
to proceed with the reset procedure. After a brief pause,  
parameters will be reset to default values.  
Note: If the Default Parameters function is invoked  
via the Network Port, the IP Address will not be  
reset. If this function is invoked via the Console  
Port or Modem Port, the IP Address will be reset.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.4. Console Port Connection  
The Console Port is a male, DB9 connector, wired in a DTE  
configuration (similar to an AT style computer), which is used  
for connection to a local PC or control device. Appendix A  
describes the Console Port interface.  
4.5. Connecting an External Modem  
When connecting directly to an external modem, use a standard  
DB9 AT to Modem cable. Section 5.4 describes the procedure  
for defining the modem command strings. Appendix A describes  
the modem port interface.  
4.6. Connecting the Network Cable  
The Network Port is an RJ45 Ethernet jack, for connection to a  
TCP/IP network. Connect your 10Base-T cable to the Network  
Port. Before attempting to access the unit via network, please  
assign the IP Address, Gateway Address and Subnet Mask as  
described in Section 5.6.  
Note: The RPC features a 10BaseT interface.  
When connecting the RPC to a 100BaseT interface,  
note that most router switches will autosense to  
determine if the device is 100BaseT or 10BaseT and  
then configure the network interface accordingly. If  
your router switch does not auto-configure for  
10BaseT vs. 100BaseT, then the network interface  
port must be manually set to 10BaseT.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Configuration  
5.1. System Mode and User Mode  
In order to restrict access to sensitive command functions, the  
RPC-4840N features two separate operating modes; System  
Mode and User Mode.  
The System Mode allows access to all configuration menus,  
command functions and status screens. When the System Mode  
is active, Boot/On/Off commands can always be directed to  
either of the two switched circuits, even if each circuit has been  
assigned a separate password. The System Mode Status Screen  
shows On/Off conditions for both switched circuits, and lists  
currently defined system parameters.  
The User Mode allows limited access to command functions and  
status screens; users are not allowed to access configuration  
menus. When the User Mode is active, Boot/On/Off commands  
can only be directed to the specific circuit(s) allowed by the User  
Password entered at login. If a different User Password is  
assigned to each RPC circuit, then a user who accesses the RPC  
using the password for Circuit 1 is not allowed to boot or switch  
Circuit 2. On the other hand, if the same User Password is  
assigned to both circuits, then that user will be able to direct  
commands to both circuits. The User Mode Status Screen only  
shows conditions at the circuit(s) owned by the User Password;  
system parameters are not displayed.  
When properly configured, the RPC will display a password  
prompt when the unit is contacted via the Console Port, Modem  
Port or Network Port. The password entered at this prompt  
determines whether the unit will start-up in System Mode or User  
Mode. If the System Password (defined via the General  
Parameters menu) is entered, the System Mode will be active. If  
the User Password (defined via the circuit Configuration Menus)  
is entered, the User Mode will be active.  
If the System Password is not defined, the RPC will not display  
the password prompt, and will always start-up in System Mode.  
Once the System Password has been defined, individual users can  
be granted access by assigning passwords to the two switched  
circuits as described in Section 5.5.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.2. Communicating with the RPC-4840N  
In order to configure the unit or invoke command functions, the  
user must first connect to the RPC-4840N and access the  
command mode.  
1. The RPC is transparent to parity and will accept 7 or 8 bit  
characters, but will always answer back at 8 bits, no parity.  
Make certain your communication program (e.g.  
HyperTerminal or ProComm) is set for the appropriate  
baud rate, bits and parity.  
a) Via Modem: Start your communications program.  
Dial the external modem connected to the RPC. Wait  
for the Connect message and proceed to Step 2.  
b) Via Local PC: Start your communications program  
and then press [Enter].  
c) Via Network: During initial configuration, the RPC  
cannot be accessed via the Network Port. After  
network parameters have been defined (see  
Section 5.6), the unit may then be accessed via network  
as described in Section 6.1.  
Note: Only one port can access the command mode  
at a given time. When communicating via the  
Console Port or Modem Port, always make certain to  
disconnect (using the /X command) when you have  
finished. If the Console Port or Modem Port are  
busy, you will not be able to access the command  
mode via the Network Port. For more information,  
please refer to Section 6.7.  
2. Password: If the System Password has been defined, the  
unit will display the Password Prompt. Key in either the  
System Password or User Password, and press [Enter]. If  
the system password has not been defined, the prompt will  
not be displayed. Note that the Password feature is case  
sensitive.  
3. If the System Password is entered, the RPC will display  
the System Help Screen (Figure 5.1). If the User Password  
is entered, the User Help Screen (Figure 5.2) will be  
displayed.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.3. Command/Menu Conventions  
When invoking RPC-4840N commands and selecting items from  
configuration menus, note the following:  
· To display the Help Screen, type /H [Enter].  
· All RPC commands can be invoked at the RPC> command  
prompt, or from the General Parameters Menu, Port  
Parameters Menus or Network Parameters Menu.  
· RPC commands are not case sensitive.  
· All commands are invoked by pressing [Enter].  
· To select an item from a menu, key in the number for the  
item and press [Enter]. To exit from a menu, press [Esc] at  
any time. Parameters defined up to that point will be saved.  
· The ",Y" option can temporarily suppress the "Sure?"  
confirmation prompt. The ",Y" option is entered at the end  
of the command line, immediately following the command  
or argument. For example, to reset the network port without  
displaying the "Sure?" prompt, type /T,Y [Enter].  
5.4. Defining General Parameters  
When the "RPC>" prompt appears, type /G [Enter] to display  
the General Parameters menu (Figure 5.3). Note that this menu  
is not available in User Mode. The General Parameters menu  
offers the following options:  
1. System Password: (Up to 16 characters, case-sensitive)  
When the System Password is defined, the RPC will  
display a prompt before allowing access to command  
mode. If the System Password is entered, the RPC will  
start-up in System Mode. To define the System Password,  
type 1 and press [Enter]. (Default = undefined).  
Note: If the System Password is not defined, the  
password prompt will not be displayed, and the RPC  
will always start-up in System Mode.  
2. Site ID: Defines a text string (up to 32 characters) that is  
often used to indicate the installation site. To define the  
Site ID, type 2 and press [Enter]. (Default = undefined).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Modem Initialization String: To define the Modem  
Initialization String (up to 32 characters), type 3 and  
press [Enter]. For more information on the initialization  
string, please refer to the user's guide for your external  
modem. Make certain that the modem is set to auto-  
answer in one ring. (Default = ATE0M0Q1&C1&D2S0=1).  
4. Modem Disconnect String: To define the Disconnect  
String (up to 32 characters), type 4 press [Enter], and  
follow the instructions in the submenu. For more  
information, please refer to the user's guide for your  
external modem. (Default = undefined).  
5. Baud Rate: To select the baud rate for the Modem Port  
and Console Port, type 5 press [Enter], and follow the  
instructions in the submenu. Make certain to select a rate  
that is compatible with the external modem, and/or the  
device connected to the Console Port. (Default value  
determined by Option Switch 1; Factory Setting = 9600).  
Note: When this setting is changed, the new baud  
rate will not be applied until the user exits and then  
re-enters the RPC Command Mode.  
6. Command Echo: Enables/Disables the command echo.  
When enabled, commands sent to the RPC will be echoed  
back to your PC, allowing keystrokes to be displayed . To  
enable/disable the echo, type 6, press [Enter] and follow  
the instructions in the submenu. (Default determined by  
Option Switch 3; Factory Setting = Disabled).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. Disconnect Timeout: Determines how long the RPC will  
wait for additional commands. Type 7, press [Enter], and  
follow the instructions in the submenu. (Default  
determined by Option Switch 4; Factory Setting = 2 Min.).  
Note: It is recommended that the Disconnect  
Timeout should be set at the lowest acceptable  
value. Since only one port is allowed to access the  
command mode at a given time, shorter timeout  
values will decrease the chance of other users being  
shut out of command mode if a user fails to  
disconnect when finished communicating with  
the unit.  
8. Command Confirmation: When enabled, the RPC will  
display a "Sure?" prompt before completing the /T, /X, /R,  
/BOOT, /ON, /OFF, /D and "A" commands, and will also  
display the System Status screen after commands are  
successfully completed. When disabled, the "Sure?"  
prompt is suppressed, and the Status Screen is not sent  
when commands are completed. (Default = Enabled).  
9. Automated Mode: When enabled, the RPC-4840N will  
execute the /ON, /OFF, /BOOT, /D, and /X commands  
without displaying the confirmation prompt, status screen,  
or confirmation messages. This allows the RPC to be  
controlled by a device that generates commands to control  
power switching without human interaction. For more  
information, please refer to Section 6.5.  
(Default = Off).  
Note: When this option is enabled, password  
security functions are disabled, and users are able to  
access System Level menus and control both circuits  
without entering a password.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A. Default Parameters: Resets the RPC to the default values  
specified by the Option Switches. In addition, all menu  
selected parameters, including circuit names and  
passwords, will be lost. If Command Confirmation is  
disabled, the "Sure?" prompt will not be sent.  
Note: If the Default Parameters function is invoked  
via the Network Port, the IP Address is not reset. If  
this function is invoked via the Console Port or  
Modem Port, the IP Address will be reset.  
After defining the General Parameters, press [Esc] to exit from  
the General Parameters menu.  
5.5. Circuit Parameters  
The Circuit Parameters menus are used to assign names and  
select parameters for each of the two switched circuits. There is  
a separate Parameters menu for each circuit. Note that the  
Circuit Parameters menus are not available in User Mode.  
In addition to selecting parameters for each circuit, the Circuit  
Parameters menus also allow you to assign an individual User  
Password to each circuit. If the same User Password is assigned  
to both circuits, then that password will allow the user to direct  
Boot/On/Off commands to both circuits. If a different password  
is assigned to each circuit, then each password will only allow  
access to it's corresponding circuit module.  
To access the Circuit Parameters menus from the RPC> prompt,  
type /P n and press [Enter] where n is the number or name of  
one of the two switched circuits. The Circuit Parameters menu  
(Figure 5.4) offers the following options:  
1. Circuit Name: (Up to 16 Characters) Assigns a name to  
the circuit. Typically, this name describes the piece of  
equipment that is connected to the switched circuit. When  
circuit names are assigned, Boot/On/Off commands can be  
invoked using the name or number of the desired circuit.  
(Default = undefined).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Password: (Up to 16 Characters) Assigns a User  
Password to this circuit. When a User Password is  
assigned, the circuit is then "owned" by that password.  
When a User Password is entered at login, the user will  
have access to only the circuit(s) which are owned by this  
password. (Default = undefined).  
Notes:  
· If you wish to allow a single user to access both  
switched circuits, assign the same User Password  
to both circuits.  
· If the System Password is defined, and the circuit's  
User Password is not defined, then the System  
Password will "own" this circuit, and only the  
System Mode will be able to control the circuit.  
3. Boot Delay: During a Boot cycle, the circuit is first  
switched off and then switched back on. The Boot Delay  
is the length of time which elapses between the time when  
power is switched off and the time that power is restored.  
The Boot Delay can be 1, 5, 10, 15, 30 or 60 seconds.  
(Default determined by Option Switch 2; Factory Setting =  
5 Seconds).  
4. Power-Up Default: Determines how this circuit will react  
when the /D (default) command is invoked, or after a  
power interruption. Each circuit can be automatically  
switched On or Off as specified by the Power-Up Default.  
(Default = On).  
After Circuit Parameters have been defined, press [Esc] to exit  
from the Circuit Parameters menu.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.6. Network Parameters  
In order to communicate with the RPC-4840N via network, the  
IP Address, Subnet Mask and Gateway Address must first be  
defined using the Network Parameters menu. If desired, this  
menu also allows you to implement IP Security features, which  
restrict command mode access based on the user's IP Address.  
Settings for network parameters depend upon the configuration  
of your individual network. Please contact your network  
administrator for appropriate settings, and then assign parameters  
as described in this section.  
To access the Network Parameters menu (Figure 5.5), type /N  
and press [Enter]. Note that this menu is not available in User  
Mode. The following options are available:  
1. IP Address: Defines the IP Address for the RPC-4840N  
unit. Type 1 press [Enter], and follow the instructions in  
the submenu. (Default = undefined)  
2. Subnet Mask: Defines the Subnet Mask for the RPC unit.  
Type 2 press [Enter], and follow the instructions in the  
submenu. (Default = undefined)  
3. Gateway Address: Defines the Gateway Address for the  
RPC. Type 3 press [Enter], and follow the instructions in  
the submenu. (Default = undefined)  
4. IP Security: Sets up the IP Security feature as described  
in Section 5.6.1.  
5. Mac Address: Displays the unit's MAC Address. Note  
that this item is not used to redefine the MAC Address.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.6.1.  
Implementing IP Security  
The RPC-4840N can be configured to restrict unauthorized IP  
addresses from Telneting to the unit. This allows the user to  
grant Telnet access to only a specific group of IP addresses, or  
block a particular IP address from gaining access. In the default  
state, the RPC accepts incoming IP connections from all hosts.  
To configure the IP Security feature, proceed as follows:  
1. Access the Network Parameters menu as described in  
Section 5.6. Note that the Network Parameters menu is  
not available in User Mode.  
2. When the Network Parameters menu appears, type 4 and  
press [Enter] to access the IP Security menu (Figure 5.6).  
3. The IP Security menu lists five IP Security "masks" along  
with the selected permit/deny action for each mask.  
a) Each Security Mask prompt is used to define a specific  
IP address or range of IP addresses. Each Mask Action  
prompt is used to define the permit/deny action for the  
corresponding Mask.  
b) Masks are listed in order of ascending priority; Mask 1  
has the lowest priority, Mask 5 has the highest priority.  
c) Masks have a cumulative effect; high priority masks  
supersede the effect of lower priority masks.  
d) Each IP Address consists of a series of four eight bit  
numbers. The number 255 is used as a wild card.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example 1: Deny access to all hosts except 192.1.1.5:  
Since 255 is a wild card, Mask #1 blocks all IP Addresses. Mask  
#2 then specifically grants access to 192.1.1.5 only.  
Example 2: Allow access only by addresses that begin with 192.  
Since 255 is a wild card, Mask 1 blocks all IP addresses. Mask 2  
then grants access to all addresses that begin with 192.  
Example 3: Allow access only by addresses that begin with 192,  
deny access to 192.1.1.5.  
Since 255 is a wild card, Mask 1 blocks all IP addresses. Mask 2  
then grants access to all addresses that begin with 192. Finally,  
Mask 3 specifically blocks access by 192.1.1.5.  
Note:  
· Mask #5 has priority over the other four masks. If  
Mask #5 is set to deny access by  
"255.255.255.255" (all wild cards), all IP  
Addresses will be blocked, and you will not be able  
to access the RPC-4840N Command Mode via  
network. Access will only be allowed via the  
Console Port or Modem Port.  
· When using the wild card address  
"255.255.255.255" to block access by all IP  
Addresses, make certain that at least one higher  
priority mask permits access by your IP address.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.7. Save Configuration Parameters  
After the unit has been completely configured, it is recommended  
to save parameters to an ASCII file as described in Section 7.  
This allows quick recovery in the event that the unit is reset to  
default parameters, or the configuration is accidentally deleted or  
altered.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Operation  
6.1. Access the Command Mode  
Commands can be sent to the RPC-4840N via Network or  
modem, or from a local PC connected to the Console Port. To  
access the Command Mode, proceed as follows:  
Note: Only one port can access command mode at a  
given time. When you have finished communicating  
with the unit, always make certain to disconnect  
using the /X command. When the Console Port or  
Modem Port are busy, you will not be able to access  
the command mode via the Network Port. For more  
information, please refer to Section 6.7.  
1. Contact the RPC-4840N:  
a) Via Network: Telnet to the RPC unit's IP Address.  
For example, if the IP Address is 192.1.1.1, on a UNIX  
system the Telnet command would be as follows:  
$ telnet 192.1.1.1 [Enter]  
Notes:  
· In order to contact the RPC via telnet, you must  
first define the unit's Network Parameters as  
described in Section 5.6.  
· If the Telnet connection to the RPC is refused, this  
may mean that the unit is busy, or that the IP  
Security feature has denied the connection.  
b) Via Modem: Start your communications program (e.g.  
HyperTerminal). Dial the external modem connected  
to the RPC, then wait for the Connect Message.  
c) Via Console Port: Start your communications  
program and press [Enter].  
2. Password: If the System password has been defined, a  
prompt will be displayed. Key in your System or User  
Password, and press [Enter].  
3. Disconnect: To end the session, type /X and press  
[Enter] (or disconnect using Telnet software).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.2. Displaying circuit Status  
The Status Screen displays the On/Off state and selected  
parameters for the switched circuits. To display the Status  
Screen, type /S and press [Enter]. Note that although the /S  
command is available in both User and System Mode, the System  
Status Screen includes more information than the User Status  
Screen.  
When the System Mode is active, the /S command will produce  
the screen shown in Figure 6.1, which lists status and parameters  
for both circuits, along with Console Port parameters, and  
modem command strings. Note that in System Mode, the /S  
command will also accept an argument which will display the  
User Password for each circuit. To display circuit passwords,  
access the System Mode, type /SP and press [Enter].  
When the User Mode is active, the /S command produces a  
different version of the status screen, which lists the status and  
parameters only for the circuit(s) owned by the User password  
entered at login. If a separate User Password is assigned to the  
other circuit, the User Mode Status Screen will not list the status  
for that circuit. In User mode, passwords cannot be displayed.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.3. Boot/On/Off Commands  
These commands are used to Boot or toggle the On/Off status of  
the RPC-4840N's two switched circuits. If the same password  
has been applied to both circuits, commands can be directed to  
Circuit 1, Circuit 2, or both circuits. If a separate User Password  
has been assigned to each circuit, then commands can only be  
applied to the circuit that is owned by the User Password entered  
at log in. Circuits may be specified by name or number.  
Notes:  
· When User Mode is active, commands will only be  
applied to circuits owned by the User's password.  
· To apply a command to both circuits, enter an  
asterisk (*) in place of the circuit number or name.  
Commands can only be applied to both circuits  
when the unit is operating in System Mode, or  
when both circuits are owned by the same  
User Password.  
· When commands are applied to both circuits, the  
RPC will delay for approximately 1 second  
between actions. For example, when switching  
both circuits On, the RPC will switch Circuit 1 On,  
delay one second, then switch Circuit 2 On.  
· Wait for the "RPC>" prompt to appear before  
entering commands. The prompt will not reappear  
until the previous command is complete.  
· Commands are not case sensitive. All commands  
are invoked by pressing [Enter].  
· If command confirmation is enabled, the RPC will  
display the Status Screen after the Boot/On/Off  
commands are successfully completed.  
1. Boot Circuit(s): To initiate a Boot cycle, type /BOOT n  
and press [Enter]. Where "n" is a the number or name of  
the desired circuit. Note that the "/BOOT" command can  
also be entered as "/BO".  
Examples:  
· To boot both circuits, type /BOOT * or /BO * and then  
press [Enter].  
· To boot Circuit 1, type /BOOT 1 or /BO 1 and then  
press [Enter].  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Switch Circuit(s) On: To power-on a circuit, type /ON n  
and press [Enter]. Where "n" is the number or name of  
the desired circuit.  
Examples:  
· To power-on both circuits, type /ON * and  
press [Enter].  
· To power-on Circuit 1, type /ON 1 and press [Enter].  
3. Switch Circuit(s) Off: To power-off a circuit, type /OFF  
n and press [Enter]. Where "n" is the number or name of  
the desired circuit. Note that the "/OFF" command can  
also be entered as "/OF".  
Examples:  
· To power-off both circuits, type /OFF * or /OF * and  
press [Enter].  
· To power-off a circuit named POWER2, type  
/OFF POWER2 or /OF POWER2 and press [Enter].  
4. Suppress Command Confirmation Prompt: To execute a  
Boot/On/Off command without displaying the "Sure?"  
prompt, include the ",Y" option in the command line. The  
",Y" option is entered immediately following the  
command argument.  
Examples:  
· To boot both circuits without displaying the "Sure?"  
prompts, type /BOOT *,Y or /BO *,Y and then  
press [Enter].  
· To power-off a circuit named POWER1 without  
displaying the "Sure?" prompt, type /OFF POWER1,Y  
or /OF POWER1,Y and then press [Enter].  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.4. The Default Command  
The Default Command (/D) sets circuits to their default On/Off  
status. The default status is set using the Circuit Parameters  
menus described in Section 5.5. To set the circuits to their  
default settings, type /D and press [Enter].  
Note:  
· When User Mode is active, this command will only  
be applied to the circuit owned by the User's  
password. The command will not be applied to a  
circuit owned by another User Password.  
· When the System Mode is active, this command  
will be applied to both circuits.  
· This command will always be applied to all owned  
circuits. It cannot be directed only to a specific  
circuit module.  
6.5. The Automated Mode  
The Automated Mode allows the RPC-4840N to perform  
On/Off/Boot/Default/Exit commands, without displaying menus  
or generating response messages. Automated Mode is designed  
to allow the RPC to be controlled by a computer (or another  
automatic system) which can generate commands to control  
power switching functions without human intervention.  
When the Automated Mode is enabled, the /ON, /OFF, /BOOT,  
/D and /X commands are executed without a "Sure?"  
confirmation prompt and without command response messages;  
the only reply to these commands is the "RPC>" prompt, which  
is displayed when the command is complete.  
Note: When Automated Mode is enabled, all RPC  
password security functions are disabled, and users  
are able to access System Level command functions  
(including the configuration menus), and control  
both circuits without entering a password. If you  
need to enable the Automated Mode, but want to  
restrict network access to RPC configuration menus,  
it is recommended to enable and configure the IP  
Security Function as described in Section 5.6.1.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To enable/disable the Automated Mode, access the RPC-4840N  
General Parameters menu, and proceed as described in  
Section 5.4. When the Automated Mode is enabled, RPC  
functions will change as follows:  
1. All Password Security Suppressed: When a user  
attempts to access the command mode, the password  
prompt will not be displayed at either the Network Port,  
Modem Port, or Console Port. Unless restricted by the IP  
Security Function, all users will be allowed to access  
System Level command functions and control both  
circuits. At the Console Port, all commands are  
immediately accepted, whether the circuit is awake  
or asleep.  
2. Status Screen Suppressed: The status screen will not be  
automatically displayed after commands are successfully  
executed. Note however, that the /S command can still be  
invoked to display the status screen if desired.  
3. "Sure?" Prompt Suppressed: All commands are  
executed without prompting for user confirmation.  
4. Error Messages Suppressed: If the [Enter] key is  
pressed without entering a command, the RPC will not  
respond with the "Invalid Command" message. Note  
however, that an error message will still be generated if  
commands are invoked using invalid formats or arguments.  
All other status display and configuration commands will still  
function as normal.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.6. Other Commands  
6.6.1.  
Login as Different User  
The /R command is used to re-login using a different password.  
When invoked, the RPC will display the password prompt,  
allowing the user to enter a different password in order to access  
the other circuit or System Level command functions. The /R  
command is typically used to switch from User Mode to  
System Mode.  
The /R command is available in both System Mode and User  
Mode. To login as a different user, type /R, press [Enter], and  
then key in a different valid password at the prompt. To  
suppress the "Sure?" prompt, type /R,Y [Enter].  
6.6.2.  
Reset Network Port  
The /T command is used to reinitialize the RPC Network card.  
The /T command is not available in User Mode. To reset the  
Network Port, type /T and press [Enter]. To suppress the  
"Sure?" prompt, type /T,Y [Enter].  
Note: The /T command can only be issued via the  
Console Port or Modem Port. The /T command  
cannot be invoked via the Network Port.  
6.6.3.  
Exit / Disconnect  
To exit from the RPC Command Mode and discontinue  
connection to the unit, type /X and press [Enter]. The RPC will  
display the "DISCONNECT" message. To suppress the "Sure?"  
prompt, type /X,Y [Enter].  
Note: Only one port may access the command  
mode at any given time. In order to allow access to  
the RPC unit via other ports, always exit from the  
command mode when you are finished  
communicating with the unit. For more information,  
please refer to Section 6.7.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.7. Operating Tips  
When connecting to the RPC via network, modem or console  
port, the following factors should be kept in mind:  
1. One Connection at a Time: Only one port can access the  
command mode at a time. Therefore, it is recommended  
that users should always disconnect using the /X command  
when finished communicating with the unit. When a  
command port is busy, the RPC will react as follows:  
a) Network Port Busy: If a second user attempts to  
connect via the Modem Port, the RPC will send a busy  
message. If a second user attempts to connect via the  
Console Port, the port will not wake.  
b) Modem Port Busy: If a second user attempts to  
connect via the Network Port, the connection will be  
refused. If a second user attempts to connect via the  
Console Port, the port will not wake.  
c) Console Port Busy: If a second user attempts to  
connect via the Network Port, the connection will be  
refused. If a second user attempts to connect via the  
Modem Port, the Console Port will disconnect and the  
Modem Port will be granted access; the Modem Port  
has priority over the Console Port.  
2. Ping Packet Size: The RPC will not accept Ping Packets  
larger than approximately 1000 bytes.  
If you have any questions regarding configuration or operation of  
the RPC-4840N, please contact WTI Technical Support as  
described in Appendix C.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. Saving and Restoring  
Configuration Parameters  
After the RPC-4840N has been properly configured, parameters  
can be downloaded and saved as an ASCII text file. Later, if the  
configuration is accidentally altered, the file with the saved  
parameters can be uploaded to automatically reconfigure the unit  
without the need to manually assign each parameter.  
Saved parameters can also be uploaded to other RPC-4840N  
units. This allows rapid set-up when several units will be  
configured with the same parameters.  
The "Save Parameters" procedure can be performed from any  
terminal emulation program (e.g. ProComm, Crosstalk,  
Hyperterminal, etc.), which allows downloading of ASCII files.  
7.1. Sending Parameters to a File  
1. Start your communications program and access the  
RPC command mode using the System Level Password.  
2. When the RPC> command prompt appears, type /DL and  
press [Enter]. The RPC will prompt you to prepare your  
communications program. Set up your communications  
program to receive an ASCII download, and specify a  
name for the file that will receive the saved parameters  
(e.g. RPC.PAR).  
3. When the communications program is ready to receive the  
file, return to the RPC command mode, and press [Enter]  
to proceed.  
4. The RPC-4840N will send a series of ASCII command  
lines which specify the currently selected parameters.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.2. Restoring Saved Parameters  
This section describes the procedure for using ProComm to send  
saved parameters to the RPC-4840N.  
1. Start your communications program and access the  
RPC-4840N command mode using the System Level  
Password.  
2. Configure your communications program to upload an  
ASCII text file.  
3. Upload the file with the saved parameters. If necessary,  
key in the file name and directory path.  
4. When the upload is complete, make certain to terminate  
the communications program's upload mode.  
Note:  
· The current On/Off status of each RPC-4840N  
circuit will not be saved or restored. However, the  
selected default On/Off setting for each circuit will  
be saved and restored.  
· When the configuration file is sent to the  
RPC-4840N via telnet, the unit's IP Address,  
Subnet Mask, and Gateway Address cannot be  
altered.  
5. Type /SP and press [Enter], the RPC-4840N will display  
the Status Screen with passwords revealed. Check the  
Status Screen to make certain that saved parameters have  
been restored.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A. Interface Descriptions  
A.1. Console Port Interface  
A.2. Modem Port Interface  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. Specifications  
Switched DC Circuits: 1 or 2 code-selectable 40 amp Circuit  
Modules (Second Circuit Module is Optional).  
Each Circuit Module is rated at -48 VDC @ 40 amps max.  
Circuit Module: 40 amp On/Off, Push/Pull Circuit Breaker  
Terminations: Terminal Block with #10 screws.  
Network Interface: 10Base-T, RJ45  
Modem and Console Port Interface:  
Connector: DB9M, RS232C, DTE  
Coding: Serial ASCII, 8 Bits, No Parity  
LEDs: ON, RDY, RXD, CKT 1 ON, CKT 2 ON  
Physical / Environmental:  
Operating Temperature: 0°C to 45°C  
Humidity: 10 - 90% RH, Non-Condensing  
Temperature: 0°C to 30°C operating  
Power: -48 VDC (±10%) @ 40 amps max.  
Size: 3.5" x 19.00" x 7.5" (H x W x D).  
Requires two rack spaces.  
Weight: 10 pounds shipping weight  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Customer Service  
Customer Service hours are from 8:00 AM to 5:00 PM,  
PST/PDT, Monday through Friday. When calling, please be  
prepared to give the name and model of the unit, its serial  
number and a description of its symptoms. If the unit should  
need to be returned for factory repair it must be accompanied by  
a Return Authorization number from Customer Service.  
WTI Customer Service  
5 Sterling  
Irvine, California 92618  
Toll Free Service Line: 1-888-280-7227  
Local Phone: (949) 586-9950  
Service Fax: (949) 457-8138  
Trademark and Copyright Information  
WTI and Western Telematic are trademarks of Western Telematic  
Incorporated. All other product names mentioned in this  
publication are trademarks of their respective companies.  
Information and descriptions contained herein are the property of  
Western Telematic, Inc.. Such information and descriptions may  
not be copied, disseminated or distributed without the express  
written consent of Western Telematic, Incorporated.  
©Copyright Western Telematic, Inc., 2002. All right reserved.  
Printed in the United States of America.  
January 2002  
WTI Part Number: 13224 Rev. A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
#
D
A
B
C
E
F
G
H
I
Download from Www.Somanuals.com. All Manuals Search And Download.  
L
R
M
S
N
O
P
T
U
W
Q
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
·
·
·
·
Download from Www.Somanuals.com. All Manuals Search And Download.  

Weil McLain Boiler 550 141 830 1202 User Manual
Western Telematic Switch PLS 345 User Manual
Williams Furnace 4505621 User Manual
Winegard Satellite TV System MV3500A User Manual
Wolf Convection Oven WKEHD1 User Manual
Wolfgang Puck Waffle Iron WPWB0010 User Manual
Yamaha CD Player CD S1000 User Manual
Yamaha Stereo Amplifier AX 590 User Manual
Zanussi Washer FR 1250 S User Manual
Zanussi Washer IZ 141 S User Manual