Vulcan Hart Range EG160 User Manual

SERVICE MANUAL  
GAS RESTAURANT RANGE  
EG24, 36, 48, 60, 160 AND 260  
MODEL  
EG24  
EG36  
EG48  
EG60  
EG160  
EG260  
ML-52486  
ML-52487  
ML-114956  
ML-52488  
ML-52489  
ML-52490  
EG36  
VULCAN-HART COMPANY, P.O. BOX 696, LOUISVILLE, KY 40201-0696, TEL. (502) 778-2791  
FORM 31054 Rev. A (5-98)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS RESTAURANT RANGE MODELS  
EG60  
EG160  
EG260  
EG48  
EG24  
EG36  
PL-53006  
– 4 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE MANUAL  
GAS RESTAURANT RANGES  
INDEX  
PLEASE KEEP THIS MANUAL FOR FUTURE REFERENCE  
DESCRIPTION  
PAGE  
SERVICE NOTATIONS  
6
7
UNITS MOUNTED ON CASTERS  
SERVICING SIMPLE CHECKS AND ADJUSTMENTS  
GAS CONNECTIONS  
7-10  
11, 12  
12  
TESTING THE GAS SUPPLY SYSTEM  
ORIFICE SIZE REQUIREMENTS FOR DIFFERENT ELEVATIONS  
PILOT LIGHTING AND ADJUSTMENTS  
12  
13-17  
18-21  
22-24  
24-27  
28  
THERMOSTAT ADJUSTMENTS  
REGULATOR CHECK, ADJUSTMENT, INSTALLATION  
STANDARD OVEN & GRIDDLE THERMOSTAT REPLACEMENT  
OVEN PILOT CHECK, REPLACEMENT  
STANDARD OVEN PILOT SAFETY VALVE CHECK, REPLACEMENT  
THERMOCOUPLE CHECK, REPLACEMENT  
OVEN BURNER NOZZLE AND ORIFICE CHECK, REPLACEMENT  
OVEN BURNER CHECK, REPLACEMENT  
29-31  
32  
33  
34  
TOP SECTION PILOT CHECK, REPLACEMENT  
PILOT ADJUSTMENT VALVE REPLACEMENT  
TOP SECTION BURNER VALVE AND NOZZLE CHECK, REPLACEMENT  
35  
35  
36  
5 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DEDICATED TECHNICAL SERVICE HOT LINE-  
(1-502-778-2791)  
SERVICE NOTATIONS:  
1. The procedures outlined in this manual are to be performed only by Vulcan-Hart authorized service  
representatives.  
2. An authorized Vulcan-Hart service representative is one who is familiar with Vulcan equipment and who has been  
endorsed by Vulcan-Hart Company to service the equipment. All authorized service personnel are required to stock  
aminimumamountofpartsandshouldbeequippedwithacompletesetofwiringdiagrams, serviceandpartsmanuals  
covering all Vulcan-Hart equipment.  
3. For all field conversion service installation procedures, refer to the codes and compliances outlined in the installation  
and operation manual.  
4. The unit rating plate stating model no., serial no. and unit gas type is located on the inside of the lower kick panel.  
5. Caution should be taken when servicing this equipment. Some service testing is required while the unit is in operation.  
During these test procedures, it is advisable not to leave the unit unattended and to exercise caution during all testing  
operations.  
WARNING: THE RANGE AND ITS PARTS ARE HOT. BE VERY CAREFUL WHEN OPERATING OR SERVICING THE  
RANGE.  
6 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNITS MOUNTED ON CASTERS  
Units mounted on casters utilizing a flex hose and quick-disconnect must be installed with a restraining device. The  
restraining device must be connected at all times. If disconnection of the device is necessary, turn off the gas supply before  
disconnection. Reconnect the restraint before turning the gas supply on and returning the unit to its original installation  
position and before beginning unit operation.  
SERVICING SIMPLE CHECKS AND ADJUSTMENTS  
The following is a list of simple checks and adjustments which are commonly associated with the malfunctioning of  
this equipment. Perform these checks and adjustments for relevant unit symptoms before the removal of any major  
parts or controls. Any service related questions for these units can be answered by calling the number on the front of this  
manual.  
CHECKS  
1. Check the unit rating plate and verify that the gas type, pressure rating and voltage ratings (if applicable) are correct  
for the unit and the installation site affected. If not correct, make required adjustments.  
2. Ensure that all unit and main gas and electrical supply lines are connected properly. (For electrical problems, check  
for tripped circuit breakers.)  
ADJUSTMENTS  
1. Legs/Casters  
TOOLS REQUIRED: Carpenters level, channel locks.  
If the cooked product seems to be lopsided, check the leveling of the unit. Place a carpenters level inside the oven cavity  
across the oven rack(s). Level the unit from front to back and from side to side.  
To adjust the leveling of the unit, tilt the unit to one side and, using channel locks, unscrew the adjustable leg insert as  
required. Repeat this procedure as necessary for each leg.  
NOTE: Casters for this range are of the non-leveling type. Therefore, the surface which the unit is resting on must be level.  
If floor surface is not level, the unit will experience cooking problems until the range is level.  
Check the unit leveling again before leaving the store to ensure that the problem has been corrected.  
7 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICING SIMPLE CHECKS AND ADJUSTMENTS (Cont.)  
2. Oven Door Turnbuckle  
NOTE: For the 24L units, refer to procedure outlined under 2A.  
If the oven door is not closing properly, the door turnbuckle may require adjustment. To adjust the turnbuckle, flip down  
the lower front kick panel. The turnbuckle is connected between the right- and left-hand door springs (Fig. 1). With your  
hand, rotate the cast center piece of the turnbuckle two rotations at a time, then check the door tension. Repeat this  
procedure until the door works as desired. After adjustment has been made, tighten the locknuts.  
Fig. 1  
2A. 24L Oven Door J-Bolt Assembly  
If the oven door is not closing properly, the door J-bolt assembly may require adjustment. To adjust the J-bolt assembly,  
flip down the lower front kick panel. The J-bolt assembly is connected to the right-hand bell crank arm (Fig. 2). The  
adjustment is made by the two 14-20 locknuts. Turn each nut in a clockwise direction to increase tension on the door; turn  
each nut in a counterclockwise direction to decrease the tension. Repeat this procedure until door works as desired. After  
adjustment has been made, tighten the locknuts.  
Fig. 2  
8 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICING SIMPLE CHECKS AND ADJUSTMENTS (Cont.)  
3. Pilot Flame Height  
TOOLS REQUIRED: Standard flat blade screwdriver.  
Top Burners: To adjust pilot flame height of the unit top burners, locate the pilot adjustment screws found on the front  
manifold pipe. It is not necessary to remove the manifold cover, as adjustment access holes have been provided in the  
panel. With screwdriver, turn the adjustment screw of the pilot valve experiencing the pilot flame height problems  
(Fig. 3). Rotate the screw clockwise to decrease and counterclockwise to increase the flame height.  
Fig. 3  
Oven: On rare occasions, the oven pilot may need adjustment. To do this:  
1. Remove the pilot adjustment cap (Fig. 4)  
Oven Pilot  
Control Button  
Pilot Adjustment Cap  
Y
Fig. 4  
9 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICING SIMPLE CHECKS AND ADJUSTMENTS (Cont.)  
2. With screwdriver, adjust pilot key (located under pilot adjustment cap) to provide the proper size flame.  
3. Replace pilot adjustment cap.  
NOTE: If unit still is not heating correctly, refer to THERMOSTAT ADJUSTMENTS on Page 18.  
4. Air Shutter Adjustment  
TOOLS REQUIRED: Standard flat blade screwdriver.  
The efficiency of the oven depends on a delicate balance between the air supply and the volume of gas. Whenever this  
balance is disturbed, poor operating characteristics and excessive gas consumption will occur.  
Thegasmixerbalanceiscontrolledbyanairshutteronthefrontoftheovenburner. Ayellowstreamingflameontheburner  
is an indication of insufficient air. To correct this condition, loosen the screw locking the shutter into position. Rotate the  
air shutter open until the burner flame begins to lift from the burner, then close the shutter slightly down again and lock it  
into place (Figs. 5 & 6).  
Fig. 6  
Fig. 5  
10 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS CONNECTIONS  
CAUTION: All gas supply connections and any pipe joint compound used must be resistant to the action of  
propane gases.  
Each unit is factory-equipped with the type gas specified on the rating plate. The installation gas connection is a  
3
4" (19mm) 14 FPT thread ANSI schedule #40 standard pipe.  
Codes require that a gas shutoff valve be installed in the gas line ahead of the range.  
Standard units are equipped with fixed burner orifices which coincide with the proper unit operation elevation. See Orifice  
Size Requirements for Different Elevations on Page 12. NOTE: Do not attempt to drill out orifice sizes. Obtain proper  
conversion kit from Vulcan-Hart depot.  
Install the gas pressure regulator.  
NOTE: Before installing, check regulator supplied against unit rating plate gas supply.  
As of 7/11/90, the gas pressure regulator is NOT factory installed to this equipment. The regulator for this unit gas type  
is sealed within a plastic bag attached to the oven rack inside the oven cavity. This regulator must be field installed by a  
qualified installation/service representative. The installer must adhere to all installation and pressure testing codes  
outlined in the Installation and Operation manual (supplied with the equipment), and local installation ordinances.  
Natural gas regulators are preset for 3.7" W.C. (Water Column) (.92 kPa); propane gas regulators for 10.0" W.C.(2.5 kPa).  
1. Locate 34" (19mm) gas connection pipe extending from rear of range.  
2. Cover pipe threads with leak sealant.  
3. Screw regulator hand-tight onto pipe with regulator arrow pointing towards range body back (see Fig. 7).  
4. Using pipe wrench, tighten regulator securely in an upright position (see Fig. 7).  
The arrow on the regulator shows the direction of the gas flow (Fig. 7). While connecting the range to the gas supply, the  
pressure regulator must be mounted horizontally to ensure proper preset outlet pressure. If the regulator is reinstalled in  
any other position, the outlet pressure must be reset (Fig. 8).  
Fig. 8  
Fig. 7  
11 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS CONNECTIONS (Cont.)  
NOTE: A leak limiter is supplied with every regulator to allow excess gas pressure to escape. Do not obstruct leak  
limiter on gas pressure regulator as obstruction may cause regulator to malfunction.  
WARNING: PRIOR TO LIGHTING, CHECK ALL JOINTS IN THE GAS SUPPLY LINE FOR LEAKS. USE SOAP AND  
WATER SOLUTION. DO NOT USE AN OPEN FLAME.  
After piping has been checked for leaks, all piping receiving gas should be fully purged to remove air.  
TESTING THE GAS SUPPLY SYSTEM  
1
IMPORTANT: When test pressures exceed 2 psig (3.45 kPa), the range and its individual shutoff valve must be  
disconnected from the gas supply piping system.  
When test pressures are 12 psig (3.45 kPa) or less, the range must be isolated from the gas supply system by closing its  
individual manual shutoff valve.  
ORIFICE SIZE REQUIREMENTS  
FOR DIFFERENT ELEVATIONS  
FOR RESTAURANT RANGE  
OPEN TOP  
HOT TOP  
GRIDDLE  
BRO/GRID  
(STD)  
OVEN  
INPUT AT SEA LEVEL  
17,500  
20,000  
15,000  
10,000  
30,000  
PER BURNER (BTUS)  
5.124 kW  
5.856 kW  
4.392 kW  
2.928 kW  
8.784 kW  
ORIFICE SIZE  
NAT/PROP NAT/PROP  
NAT/PROP  
NAT/PROP  
NAT/PROP  
Drill  
47/56  
mm  
Drill  
44/55  
mm  
Drill  
48/57  
mm  
Drill  
52/62  
mm  
Drill  
36/52  
mm  
SEA LEVEL  
TO  
2000 FT  
2.00/1.5  
2.20/1.35  
1.95/1.10  
1.60/1.00  
2.7/1.60  
Drill  
48/56  
mm  
Drill  
45/55  
mm  
Drill  
49/58  
mm  
Drill  
53/65  
mm  
Drill  
39/53  
mm  
2000 FT  
TO  
4000 FT  
1.95/1.15  
2.10/1.35  
1.85/1.05  
1.50/0.9  
2.50/1.50  
Drill  
49/57  
mm  
Drill  
46/56  
mm  
Drill  
50/60  
mm  
Drill  
53/66  
mm  
Drill  
40/54  
mm  
4000 FT  
TO  
6000 FT  
1.48/1.10  
2.05/1.15  
1.80/1.00  
1.50/0.8  
2.50/1.40  
Drill  
50/58  
mm  
Drill  
47/57  
mm  
Drill  
51/63  
mm  
Drill  
54/67  
mm  
Drill  
41/55  
mm  
6000 FT  
TO  
8000 FT  
1.80/1.05  
2.00/1.10  
1.70/0.9  
1.40/0.8  
2.45/1.35  
12 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PILOT LIGHTING AND ADJUSTMENTS  
NOTE: Although pilot lighting procedures are to be performed by both installation and operation personnel, only the  
installation/service personnel should attempt to make any pilot, burner, or temperature adjustments to this unit. The  
operation personnel are authorized only to perform the procedures for pilot lighting. All adjustment procedures associated  
with pilot lighting must be performed by an authorized Vulcan-Hart installation or service person. While performing  
these procedures, do not turn the burner valves ONwith the burner heads removed.  
HOT TOP AND GRIDDLE TOP BURNERS  
1. Turn main gas supply ON.  
2. Wait 30 seconds and, using a taper, light the hot top or griddle top pilot (Fig. 9).  
Fig. 9  
3. If pilot fails to light, turn main gas supply OFF. Wait 5 minutes and repeat the above procedures.  
4. Turn one hot top or griddle top burner valve ONto remove air from the gas line. Turn burner valve OFFwhen gas  
begins to flow.  
HOT TOP AND GRIDDLE TOP PILOT BURNER ADJUSTMENTS  
TOOLS REQUIRED: Standard flat blade screwdriver.  
After pilot is lit, adjust pilot burner flame, if necessary, by rotating the adjustment screw of the pilot valve located on the  
manifold pipe (see Fig. 3).  
1. Turn burner ON. Burner flame should appear on burner head within a second.  
2. Rotate the screw clockwise to decrease and counterclockwise to increase the flame.  
Nightly Shutdown: Turn burner valve OFF; pilot will remain lit.  
Complete Shutdown  
1. Turn burner valve OFF; pilot will remain lit.  
2. Turn main gas supply OFF.  
13 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PILOT LIGHTING AND ADJUSTMENTS (Cont.)  
OPEN TOP BURNERS  
1. Turn main gas supply ON.  
2. Wait 30 seconds and, using a taper, light the open top pilot (Fig. 10).  
Fig. 10  
3. If pilot fails to light, turn main gas supply OFF. Wait 5 minutes and repeat the above procedures.  
4. Turn one open top burner valve ONto remove air from the gas line. Turn burner OFFwhen gas begins to flow.  
OPEN TOP BURNER ADJUSTMENTS  
TOOLS REQUIRED: Standard flat blade screwdriver.  
1. After pilot is lit, turn open top burners ON.  
2. Adjust the burner flame, if necessary, by rotating the adjustment screw of the pilot valve located on the manifold pipe  
(see Fig. 3). Rotate the screw clockwise to decrease and counterclockwise to increase the flame.  
Nightly Shutdown: Turn burner valve OFF; pilot will remain lit.  
Complete Shutdown  
1. Turn burner valve OFF; pilot will remain lit.  
2. Turn main gas supply OFF.  
14 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PILOT LIGHTING AND ADJUSTMENTS (Cont.)  
BROILER/GRIDDLE  
1. Turn main gas supply ON.  
2. Wait 30 seconds and, using a taper, light broiler/griddle pilot (see Fig. 9).  
3. If pilot fails to light, turn main gas supply OFF. Wait 5 minutes and repeat Steps 1 and 2.  
4. Turn burner valve ONto purge air from the lines. Turn burner valve OFFwhen gas begins to flow.  
BROILER/GRIDDLE ADJUSTMENTS  
TOOLS REQUIRED: Standard flat blade screwdriver, lighter taper.  
Adjust pilot burner flame, if necessary, by rotating the pilot adjustment screw clockwise to decrease and counterclockwise  
to increase the burner flame. The pilot adjustment valve is located on the broiler/griddle manifold pipe.  
Nightly Shutdown: Turn burner valve OFF; pilot will remain lit.  
Complete Shutdown  
1. Turn burner valve OFF; pilot will remain lit.  
2. Turn main gas supply OFF.  
STANDARD OVEN  
NOTE: Perform open top/griddle lighting instructions before lighting oven pilot.  
1. Open unit kick panel and lift up the pilot lighting hole cover (Fig. 11).  
Fig. 11  
15 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PILOT LIGHTING AND ADJUSTMENTS (Cont.)  
2. Light pilot by depressing the reset button located behind the kick panel (Fig. 12). Light pilot and continue to hold reset  
button in for 1 minute. If pilot fails to light, turn main gas supply OFFand wait 5 minutes before repeating Step 2.  
3. After pilot is lit, turn the temperature dial to the desired setting.  
Nightly Shutdown: Turn oven burner valve OFF.  
Complete Shutdown  
1. Turn oven burner valve OFF.  
2. Turn main gas supply OFF.  
Fig. 12  
PL-21434  
PL-21433  
16 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PILOT LIGHTING AND ADJUSTMENTS (Cont.)  
OVEN BURNER ADJUSTMENTS  
NOTE: These procedures should be performed only by a qualified Vulcan-Hart service representative.  
TOOLS REQUIRED: Standard flat blade screwdriver.  
All Restaurant Range series units equipped with pressure regulator and fixed orifices have been adjusted at the factory  
and should require no further adjustments. However, the efficiency of the range depends on a delicate balance between  
the air supply and the volume of gas. Whenever this balance is disturbed, poor operating characteristics and excessive  
gas consumption will occur. The gas mixer balance is controlled by an air shutter on the front of the oven burner  
(Fig. 15).  
Fig. 15  
A yellow streaming flame on the burner is an indication of insufficient air. To correct this condition, open the air shutter  
until the burner flame begins to lift from the burner, then close the shutter slightly down and lock into place.  
PL-21446  
17 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THERMOSTAT ADJUSTMENTS  
NOTE: These procedures should be performed only by a qualified Vulcan-Hart service representative.  
STANDARD OVEN  
Althoughtheunitthermostatsarefactorypositionedtotheirpropersetting, itisnotunusualforthethermostattobeknocked  
out of adjustment during shipment. If the oven or griddle heat response seems to be lacking after burner air shutter  
adjustments have been checked, perform the following adjustments.  
NOTE: There are two possible conditions of the thermostat that must be checked: bypass adjustment and temperature  
calibration.  
Bypass Adjustment  
TOOLS REQUIRED: Thermometer test instrument (not of bi-metal or mercury type), standard flat blade screwdriver.  
WARNING: DO NOT USE BI-METAL OR MERCURY THERMOMETERS WHEN TESTING FOOD EQUIPMENT OR  
PRODUCTS. CHEMICALS WITHIN THESE INSTRUMENTS MAY BE TOXIC IF EXPOSED TO FOOD.  
1. Using a test instrument or thermometer, check the oven or griddle temperature (whichever is in question of heat  
response) against the thermostat dial setting.  
Place the thermocouple of the test instrument on the center of the oven rack. Light the main burner by turning the  
thermostat to 500°F (260°C).  
Allow at least 10 minutes for temperatures to stabilize. Check reading against dial setting.  
2. If temperature is out of calibration, allow unit to cool until the oven bottom or griddle plate (whichever is being tested)  
is cool to the touch. Remove oven bottom or griddle plate to expose burner area (Fig. 16). (Removal of oven bottom  
is an optional procedure. Burner flame may also be observed through the oven view port.)  
Fig. 16  
18 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THERMOSTAT ADJUSTMENTS (Cont.)  
3. Light the burner. Turn the dial to the highest set temperature.  
4. After 10 minutes, turn the dial clockwise to the point slightly beyond the first mark on the dial (shown by an X).  
5. Remove the dial and sleeve (Fig. 17).  
Fig. 17  
Fig. 18  
6. With a screwdriver, turn the left-hand bypass adjustor screw counterclockwise to increase the flame, clockwise to  
decrease it, until the flame appears to be 18" (3.175mm) over the entire burner area (Fig. 18).  
7. Reinstall the sleeve and dial. Turn the dial clockwise until it locks into the OFFposition.  
8. Reinstall oven bottom or griddle plate.  
Temperature Calibration  
TOOLS REQUIRED: Thermometer test instrument (not of bi-metal or mercury type), standard flat blade screwdriver.  
WARNING: DO NOT USE BI-METAL OR MERCURY THERMOMETERS WHEN TESTING FOOD EQUIPMENT OR  
PRODUCTS. CHEMICALS WITHIN THESE INSTRUMENTS MAY BE TOXIC IF EXPOSED TO FOOD.  
1. Using a test instrument or thermometer, check the oven or griddle temperature (whichever is in question concerning  
heat response) against the thermostat dial setting.  
For Ovens: Place the thermocouple of the test instrument in the center of the oven rack.  
For Griddles: Place the thermocouple in the center of each individual griddle section. Each griddle section must be  
tested.  
2. Light the main burner by turning the thermostat to 500°F (260°C).  
19 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THERMOSTAT ADJUSTMENTS (Cont.)  
3. Allow unit to heat until the burner flame is heard cutting OFF. Wait about 10 minutes until the burner flame has cycled  
ONand OFFseveral times. Then compare the test instrument reading with the dial setting. If the reading is within  
15°F (-9.4°C) of the dial setting, its calibration is correct. If reading is not within this temperature window, then  
recalibrate by performing Steps 4 through 13.  
4. Pull the dial straight off the dial shaft (see Fig. 17).  
5. Using a screwdriver placed through the dial shaft, push the metal dial insert out of the dial (Fig. 19).  
Fig. 19  
6. Replace the dial back onto the unit. Turn the dial to the 400°F (204.4°C) mark and light the oven burner.  
7. After the oven has been on for at least 15 minutes, check the oven temperature.  
NOTE: Keep door open only as long as necessary to obtain the reading.  
8. Continue to monitor the oven temperature readings every 5 minutes until two successive readings within  
5°F (-15°C) of one another are obtained.  
9. Check the successive reading against the thermostat dial. If the reading is within 15°F (-9.4°C) of the dial setting,  
the thermostat calibration is correct. If the reading is incorrect, the thermostat must be recalibrated.  
20 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THERMOSTAT ADJUSTMENTS (Cont.)  
10. To recalibrate, hold the thermostat dial in place. Insert screwdriver into dial shaft to engage the calibration stem  
adjustment screw (Fig. 20). Push inward (do not turn stem).  
Fig. 20  
11. While holding stem calibration screw in place, turn thermostat dial until it is set on the actual temperature shown by  
the testing device (Fig. 21).  
Fig. 21  
12. Release the calibration screw and reinstall the dial insert.  
13. Set the dial to 450°F (232.2°C) and recheck temperature reading as described in Steps 7 through 9. If calibration is  
not within 15°F (-9.4°C) of the dial setting, the thermostat must be replaced.  
21 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REGULATOR CHECK, ADJUSTMENT, INSTALLATION  
REGULATOR CHECK  
A regulator is installed on each range. When servicing this equipment for possible gas pressure problems, the following  
visual checks should be made first.  
Make sure the regulator has been installed at the rear of the unit with arrow pointing in the horizontal position in the  
direction of gas flow. The only exception to this rule is if the outlet pressure of the unit has been reset prior to this service  
call.  
Then turn on the range top burners. Observe the burner flames. If you notice the flames fluctuating, perform the  
following procedures.  
NOTE: Gas supply pressure must not be greater than 12 psig (14" Water Column) (3.448 kPa). All ranges should be  
installed utilizing an individual gas line shutoff valve. The range and its individual shutoff valve must be disconnected  
1
from the gas supply piping system during any pressure testing of that system at test pressures in excess of 2 psig  
(3.45 kPa). In addition, the appliance must be isolated from the gas supply piping system by closing its individual  
manual shutoff valves during any pressure testing of the gas supply piping system at test pressures equal to or less than  
1
2
psig (3.45 kPa), as stated by the American National Standards Z83.11 (latest edition). Copies of this standard are  
available from The American Gas Association, 1515 Wilson Blvd., Arlington, Virginia 22209.  
A leak limiter is supplied with every regulator to limit gas leakage if regulator rupture occurs. Do not obstruct leak limiter  
on gas pressure regulator as obstruction may cause regulator to malfunction.  
TOOLS REQUIRED: Manometer, flat blade screwdriver, 6" adjustable wrench, slip joint plier or pipe wrench.  
1. Connect the manometer to the pressure tap provided on the manifold pipe near the regulator (Fig. 23).  
Fig. 23  
22 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REGULATOR CHECK, ADJUSTMENT, INSTALLATION (Cont.)  
2. With only two open top burners ON, note the manometer reading. The reading should be 3.7" Water Column  
(.92 kPa) for natural gas units and 10.0" Water Column (2.5 kPa) for propane gas units. If readings taken are lower,  
check the incoming line pressure. NOTE: The line pressure should never drop below 5.0" Water Column (1.25 kPa)  
for natural gas or 11.0" Water Column (2.7 kPa) for propane gas.  
If line pressure is incorrect, it must be adjusted in order to properly operate the unit . If the line pressure is good, then  
the regulator requires adjustment (refer to procedures for regulator adjustment).  
If, after the regulator adjustment has been made, the 3.7" Water Column (.92 kPa) (natural gas) or 10.0" Water  
Column (2.5 kPa) (propane gas) still is not being maintained, replace the regulator.  
3. With the regulator now reading 3.7" Water Column (.92 kPa) (natural gas) or 10.0" Water Column (2.5 kPa) (propane  
gas), turn two open top burners ON.  
4. Recheck the pressure reading. The reading should not fluctuate more than .10" (0.7 kPa). If reading is not within  
tolerance, replace the regulator.  
NOTE: When the burners are OFF, if the pressure reading climbs to an outlet regulator pressure stated in Step 2, check  
the regulator vent for obstruction (Figs. 24 & 25).  
Fig. 24  
Fig. 25  
Check also for gas leak at vent. If vent is leaking gas, replace the regulator.  
REGULATOR ADJUSTMENT  
TOOLS REQUIRED: Flat blade screwdriver, manometer, and 6" adjustable wrench.  
NOTE: Before making a regulator adjustment, always verify that the incoming line pressure is correct. The required  
incoming minimum line pressure for the Restaurant Range series is 5.0" (1.25 kPa) for natural gas and 11.0" (2.7 kPa)  
for propane gas. If the line pressure is not correct, it must be rectified or the unit will not properly operate or achieve  
proper regulator adjustment. Also, the regulator must be attached to the unit in the horizontal position with the arrow  
pointing in the direction of the gas flow (see Fig. 7).  
23 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REGULATOR CHECK, ADJUSTMENT, INSTALLATION (Cont.)  
1. Connect the manometer to the pressure tap provided on the rear manifold pipe (see Fig. 23).  
2. Check the reading. The reading should be 3.7" Water Column (.92 kPa) for natural gas and 10.0" Water Column  
(2.5 kPa) for propane gas.  
3. If reading is incorrect and the proper line pressure has been verified, then the regulator must be adjusted. Using a  
standard flat blade screwdriver, remove the regulator adjustment cap (Figs. 26 & 27).  
Fig. 27  
Fig. 26  
Insert the screwdriver into the adjustment shaft and turn the adjustment stop while watching the manometer until the  
correct pressure reading is achieved. Clockwise rotation of the stop increases pressure; counterclockwise rotation  
decreases pressure.  
After resetting the pressure to the correct setting, reinstall the adjustment cap and remove the testing equipment.  
REGULATOR INSTALLATION  
TOOLS REQUIRED: Slip joint plier or pipe wrench.  
NOTE: The pressure regulator must be attached to the unit in the horizontal position with the arrow pointing in the  
direction of the gas flow, unless at some point in time the regulator has been recalibrated (see Fig. 7).  
1. Turn main gas supply OFF.  
2. Remove old regulator.  
3. Wrap the manifold pipe threads of the insulating end with pipe thread sealant.  
4. Install new regulator as indicated by the above NOTE.  
5. Turn main gas supply ONand check the regulator connections for gas leakage using a soap and water solution. If  
no leaks are found, return unit to full operation. If leak is detected, turn main gas valve OFFand eliminate leakage.  
24 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STANDARD OVEN & GRIDDLE THERMOSTAT REPLACEMENT  
STANDARD OVEN AND GRIDDLE THERMOSTAT CHECKS AND CALIBRATION  
Refer to THERMOSTAT ADJUSTMENTS on Page 18 of this manual for the procedures for checking and calibrating the  
thermostat for the standard oven and griddle.  
STANDARD OVEN AND GRIDDLE THERMOSTAT REPLACEMENT  
TOOLS REQUIRED: Pipe wrench, 6" adjustable wrench, 18" flat blade screwdriver, 516" socket, and socket wrench.  
1. Disconnect unit gas supply and allow unit to cool.  
2. From inside the oven cavity, remove the capillary bulb from the clips mounted to the cavity back wall (Fig. 28).  
Fig. 28  
Fig. 29  
3. Remove the top grates or griddle sections required to access the thermostat and capillary wiring (Fig. 29).  
25 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STANDARD OVEN & GRIDDLE  
THERMOSTAT REPLACEMENT (Cont.)  
4. From inside the oven, straighten the capillary lead. From the opening in the oven top section, pull the capillary out of  
the oven cavity (Fig. 29).  
Fig. 30  
5. Remove the top section burner valve knobs, top grates and aeration plate. (Figs. 30)  
6. Remove screws holding the control panel in place.  
7. Disconnect the thermostat burner tubing (Fig. 31).  
Fig. 31  
8. Remove top burners, if required, to access the thermostat.  
26 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STANDARD OVEN & GRIDDLE  
THERMOSTAT REPLACEMENT (Cont.)  
9.Unscrew the thermostat from the manifold pipe (Figs. 33, 34, & 35).  
Fig. 34  
Fig. 33  
Fig. 35  
10. Replace thermostat mounting block. Place pipe dope on the threaded end of the new thermostat mounting block to  
be installed onto the unit.  
11. Install the new thermostat by reversing Steps 1 through 9 above.  
NOTE: Do not kink the new capillary line when feeding it through the oven cavity. The capillary wire may be wrapped  
loosely around the gas tube to keep the wire from laying detached in the top section burner area. Also, using a soap and  
water solution, the thermostat must be tested for gas leak after being installed.  
27 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OVEN PILOT CHECK, REPLACEMENT  
OVEN PILOT CHECK  
If all other systems have been checked and pilot will not stay lit, replacement of the pilot may be necessary.  
OVEN PILOT REPLACEMENT  
1
TOOLS REQUIRED: 4" socket, socket driver, 12" and 716" open end wrenches.  
1. Disconnect unit from main gas supply and allow unit to cool.  
2. Remove oven bottom assembly (see Fig. 16).  
3. Disconnect pilot from gas tubing (Fig. 41).  
Fig. 41  
4. Remove (2) #8 sheet metal screws holding pilot bracket in place.  
5. Lift bracket away from oven burner.  
6. Remove pilot from bracket.  
7. Remove pilot by following Steps 1 through 5 in reverse order.  
28 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STANDARD OVEN PILOT SAFETY VALVE CHECK,  
REPLACEMENT  
STANDARD OVEN PILOT SAFETY VALVE CHECK  
NOTE: A quick check of the following conditions and symptoms will assist in verifying that the pilot safety valve is properly  
functioning.  
TOOLS REQUIRED: Flow meter, millivolt tester.  
If the unit pilot is ONbut the unit is not heating, check the gas flow from the thermostat to the safety valve, using a flow  
meter (Fig. 36). (Flow meter kits are available from Vulcan-Hart Service Parts Depots under Part No. 495.)  
FOR PROPER USAGE OF FLOW METER, REFER TO THE MANUFACTURERS INSTRUCTIONS PROVIDED IN  
THE FLOW METER KIT.  
Fig. 36  
The meter should show signs of massive flow. If flow is not found, replace the thermostat and recheck gas flow.  
If meter does show signs of gas flow, then perform the following checks on the safety valve. If there is an obvious problem  
with the pilot safety valve, the unit will not heat and pilot outage will occur.  
1. Fold down lower kick panel.  
2. Perform the pilot lighting procedures (see Page 13).  
3. If pilot will not stay lit, check pilot for clogging.  
4. If the unit still will not stay lit, using a volt meter, check the millivolt reading from the valve thermocouple connection  
while holding the pilot button in the ONposition (Fig. 37).  
29 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STANDARD OVEN PILOT SAFETY VALVE CHECK,  
REPLACEMENT (Cont.)  
Fig. 37  
5. If the millivolt reading is below 5 MV, replace the thermocouple.  
6. If the MV reading is within tolerance, the safety valve should be replaced.  
SAFETY VALVE REPLACEMENT PROCEDURES  
TOOLS REQUIRED: 716" open end wrench, 1116" open wrench, and 38" open end wrench.  
1. Disconnect unit from main gas supply.  
2. Disconnect thermocouple from safety valve (Fig. 38).  
Fig. 38  
30 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STANDARD OVEN PILOT SAFETY VALVE CHECK,  
REPLACEMENT (Cont.)  
3. Disconnect right- and left-hand pilot gas tubing from the safety valve (Fig. 39).  
Fig. 39  
4. Disconnect right- and left-hand burner gas tubing from the safety valve (Fig. 40).  
Fig. 40  
5. Remove safety valve from unit.  
6. Install new valve by reversing Steps 1 through 4.  
31 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THERMOCOUPLE CHECK, REPLACEMENT  
THERMOCOUPLE CHECK  
1. Fold lower kick panel down.  
2. Perform pilot lighting procedures (see Page 13).  
3. If unit will not stay lit, using a volt meter, check the millivolt reading from the valve thermocouple connection while  
holding pilot button in the ONposition (see Fig. 37).  
4. If millivolt reading is below 5 MV, replace thermocouple.  
THERMOCOUPLE REPLACEMENT  
TOOLS REQUIRED: 716" open end wrench, 38" open end wrench, 14" socket and socket driver.  
1. Disconnect unit from main gas supply.  
2. Remove 716" nut holding thermocouple to pilot bracket.  
3. Remove thermocouple from bracket (Fig. 42).  
Fig. 43  
Fig. 42  
4. Feed thermocouple assembly through front burner box (Fig. 43).  
5. Remove thermocouple lead from safety valve (see Fig. 38).  
6. Install new thermocouple by reversing Steps 1 through 5.  
NOTE: Be careful not to kink new thermocouple wire during the installation process.  
32 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OVEN BURNER NOZZLE AND ORIFICE CHECK, REPLACEMENT  
OVEN BURNER NOZZLE AND ORIFICE CHECK  
If burner operation seems poor and all other systems have been verified, remove burner nozzle and orifice to check for  
blockage or damage. Blockages can often be cleaned using water pressure and a mild soap solution or by running a  
correct size drill tap through the nozzle opening.  
OVEN BURNER NOZZLE AND ORIFICE REPLACEMENT  
TOOLS REQUIRED: 12" open end wrench.  
1. Disconnect unit from gas and allow unit to cool.  
2. Follow steps listed under the replacement of the safety valve in order to access the oven burner nozzle.  
3. Remove burner nozzle.  
4. Remove orifice spud.  
5. Check for blockage or damages (Fig. 44).  
NOTE: If blockage is apparent, the obstruction can either be cleaned or the entire nozzle assembly replaced. Verify also  
that the proper nozzle orifice size is being used, and verify BTU rating with flow meter. (Flow meter kits are available from  
Vulcan-Hart Service Parts Depots under Part No. 420000.)  
FOR PROPER USAGE OF FLOW METER, REFER TO THE MANUFACTURERS INSTRUCTIONS PROVIDED IN  
THE FLOW METER KIT.  
Fig. 44  
33 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OVEN BURNER CHECK, REPLACEMENT  
OVEN BURNER CHECK  
If the oven burner is not properly firing and all other systems have been checked, the oven burner may need to be cleaned  
or replaced.  
OVEN BURNER REPLACEMENT  
1
TOOLS REQUIRED: 4" socket and socket driver.  
1. Disconnect unit from main gas supply and allow unit to cool.  
2. Remove burner strap-down tie if applicable.  
3. Remove (2) #8 sheet metal screws securing burner to pilot bracket (Fig. 45).  
Fig. 45  
4. Tilt burner upward and slide burner away from burner nozzle (see Fig. 43).  
5. Reinstall new burner by reversing Steps 1 through 4.  
34 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TOP SECTION PILOT CHECK, REPLACEMENT  
TOP SECTION PILOT CHECK  
If all other systems have been checked and pilot will not stay lit, cleaning or replacement of pilot may be necessary.  
TOP SECTION PILOT REPLACEMENT  
TOOLS REQUIRED: 716" open end wrench.  
1. Disconnect unit from main gas supply and allow unit to cool.  
2. Remove defective pilot from pilot tube.  
3. Check pilot for blockage.  
4. If blockage is found, clean pilot tip and replace or install new pilot tip.  
5. If blockage is not found but pilot appears to be malfunctioning, check pilot tube and pilot adjustment valve for  
obstructions.  
PILOT ADJUSTMENT VALVE REPLACEMENT  
TOOLS REQUIRED: 716" open end wrench, pipe wrench or a 6" adjustable wrench.  
1. Disconnect unit from main gas supply.  
2. Disconnect pilot tubing (Fig. 46).  
Fig. 46  
3. Remove valve from unit manifold.  
4. With pipe dope covering the threads, install new pilot valve by reversing procedures 1 through 3.  
35 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TOP SECTION BURNER VALVE AND NOZZLE CHECK,  
REPLACEMENT  
TOP SECTION BURNER VALVE CHECK  
After a long period of use on the range, the top section burner valve can show signs of wear. Check valve for gas leakage  
and sloppy valve control. Check also for valve nozzle blockage or damage.  
TOP SECTION BURNER VALVE AND NOZZLE REPLACEMENT  
TOOLS REQUIRED: 12" open end wrench, 6" adjustable wrench or standard pipe wrench, 14" socket and socket driver.  
1. Disconnect main unit gas supply.  
2. Remove control panel cover and top grates or griddle section.  
3. Remove and check valve and valve nozzle for obstructions and damage.  
4. Remove obstruction, or if necessary, replace nozzle or entire valve. When reinstalling, or if the installation of a new  
valve is required, be sure to use pipe thread sealant on the threaded end which engages the manifold pipe.  
FORM 31054 Rev. A (5-98)  
PRINTED IN U.S.A.  
36 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Texas Instruments Calculator TI 83 User Manual
Tokina Camera Accessories TVR0614 User Manual
Toshiba Cordless Telephone SG 1701 User Manual
Tricity Bendix Dishwasher DH 101 User Manual
Tripp Lite Surge Protector TLM915NC User Manual
True Fitness Treadmill Z55 HRC User Manual
Univex Mixer SRM20 User Manual
Vanguard Heating Electric Heater VMH3000TNSA User Manual
Vector TV Mount PWA 14 User Manual
Wayne Dalton Door 260597 User Manual