Trane Air Conditioner YSC060 120 User Manual

Packaged Gas/Electric  
Rooftop Units  
Precedent™  
YSC060-120  
50 Hz  
February 2004  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Introduction  
2
4
Features and Benefits  
Application Considerations  
Selection Procedure  
Model Number Description  
General Data  
9
10  
12  
13  
14  
42  
43  
44  
45  
53  
54  
Performance Data  
Zone Controls  
Electrical Data  
Jobsite Connection  
Dimensional Data  
Weights  
Mechanical Specifications  
RT-PRC017-EN  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
Easy Access Panels  
Remove two screws for access to the  
standardized internal components and  
wiring.  
Easy-Adjust Idler Arm  
With the Easy-Adjust Idler Arm, the belt  
and sheaves can be quickly adjusted  
without moving the mounted fan motor.  
The result is a major savings in time and  
money.  
Patented Condenser Coil  
Precedent boasts a patented 1+1+1  
Hybrid coil, permanently gapped for  
easy cleaning.  
Unit Cabinet  
The compact cabinet with rounded  
corners takes up less room and is less  
costly to ship. The beveled and ribbed  
top is not only aesthetically pleasing, it is  
designed to prevent water from pooling.  
Single Point Power  
A single electrical connection powers the  
unit.  
Colored And Numbered Wiring  
You save time and money tracing wires  
and diagnosing the unit.  
Convertible Units  
Sloped Drain Pans  
• The units ship in a downflow  
configuration. They can be easily  
converted to horizontal by simply  
moving two panels.  
Every Precedent unit has a non-  
corrosive, removable, double-sloped  
drain pan that’s easy to clean and  
reversible to allow installation of drain  
trap on either side of the unit.  
• Units come complete with horizontal  
duct flanges so the contractor doesn’t  
have to field fabricate them. These  
duct flanges are a time and cost saver.  
Compressors  
Through the Base Condensate  
Every unit includes provisions for  
through the base condensate drain  
connections. This allows the drain to be  
connected through the roof curb instead  
of a roof penetration.  
Precedentcontains the best  
compressor technology available to  
achieve the highest possible  
performance. Our compressor line  
includes Trane built Climatuff™  
reciprocating and scrolls.  
Foil-Faced Insulation  
Easy Access Panels  
All panels in the Evaporator section of  
the unit have cleanable foil-faced  
insulation. All edges are either captured  
or sealed to ensure no fibers get into the  
airstream.  
Easy access panels reduce the number of  
possible water entry points.  
Low Ambient Cooling  
All Precedent units have cooling  
capabilities down to -18°C (0°F) as  
standard.  
Unit Base  
For added water integrity, Precedent has  
a raised 29 mm (11/8") lip around the  
units downflow supply and return to  
prevent water from blowing into the  
ductwork.  
4
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
Standardized Components  
Progressive Tubular Heat Exchanger  
The compact cabinet features a tubular  
heat exchanger in low, medium and high  
heat capacities.  
Components are placed in the same  
location on all Precedentunits.  
Familiarize yourself with one Precedent  
and you are familiar with every  
Precedent.  
The heat exchanger is fabricated using  
stainless steel burners and corrosion-  
resistant aluminized steel tubes as  
standard on all models. It has an induced  
draft blower to pull the gas mixture  
through the burner tubes. The heater  
has a direct spark ignition system which  
doubles as a safety device to prove the  
flame.  
Flexible Applications  
• Only two roof curbs for the 5-10 ton  
Precedent line. . .simplifies curb  
selection.  
ReliaTel microprocessor controls to  
meet either the simple or the more  
cLoomwpolrexhiagphpgliacsathioena.t capacities.  
• Airflow is outstanding. The Precedent  
can replace an older machine with old  
ductwork and, in many cases, improve  
comfort through better air distribution.  
• Belt drive —standard or oversized  
supply fan motors meet a wide airflow  
range.  
• Precedent offers ultimate flexibility.  
Options and components are not pre-  
packaged at the factory. Units are built  
to order in our standard “shortest in  
the industry”ship cycle time.  
Easy Access Low Voltage Terminal  
Board  
Precedents Low Voltage Terminal Board  
is external to the electrical control  
cabinet. It is extremely easy to test  
operation of all unit functions. This is  
another cost and time saving installation  
feature.  
Low Voltage Connections  
The wiring of the low voltage  
connections to the unit and the zone  
sensors is as simple as 1-1, 2-2, and 3-3.  
This simplified system makes it easy for  
the installer to wire.  
Single-Side Service  
Single-side service is standard on all  
Precedent units.  
RT-PRC017-EN  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
• Eliminates the need for field-installed  
components with its built-in anti-short-  
cycle timer, time delay relay and  
minimum ‘’on’’ time controls. These  
controls are factory tested to assure  
proper operation.  
• Requires no special tools to run the  
Precedent unit through its paces  
during testing. Simply place a jumper  
betweenTest 1 andTest 2 terminals on  
the Low VoltageTerminal Board and  
the unit will walk through its  
Micro Controls  
Several years ago,Trane was the first to  
introduce microprocessor controls into  
the Light Commercial Market. That  
design, along with immeasurable  
experience, has provided the technology  
for Tranes second-generation ReliaTel™  
microprocessor controls.  
operational steps. The unit  
automatically returns control to the  
zone sensor after stepping through the  
test mode a single time, even if the  
jumper is left on the unit.  
• As long as the unit has power and the  
LED is lit, the Micro is operational. The  
light indicates that the Micro is  
functioning properly.  
ReliaTel Micro:  
• Provides unit control for heating,  
cooling, and ventilating by utilizing  
input from sensors that measure  
outdoor and indoor temperature.  
• Features expanded diagnostic  
capabilities when used withTranes  
Integrated ComfortSystems.  
• Improves quality and reliability  
through the use of time-tested  
microprocessor controls and logic.  
• As an energy benefit, softens electrical  
‘’spikes’’ by staging on fans,  
compressors and heaters.  
• Prevents the unit from short cycling,  
considerably improving compressor  
life.  
• The Intelligent Fallback or Adaptive  
Control is a benefit to the building  
occupant. If a component goes astray,  
the unit will continue to operate at  
predetermined temperature set points.  
• Ensures that the compressor will run  
for a specific amount of time, which  
allows oil to return for better  
lubrication, enhancing the reliability of  
the compressor.  
• Intelligent Anticipation is a standard  
feature of the Micro. Functioning  
constantly, the Micro and zone sensors  
work together in harmony, to provide  
tight comfort control.  
• Reduces the number of components  
required to operate the unit, thereby  
reducing possibilities for component  
failure.  
6
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
Factory-installed Options  
Hinged Access Doors  
The following options round-out the  
complete line of Precedent™ options:  
These doors permit easy access to the  
filter, fan/heat, and compressor/control  
sections. They reduce the potential roof  
damage from screws or sharp access  
door corners.  
— 0 - 50% Manual or Motorized  
Outside Air  
— Discharge Air Sensor  
— Hail Protection Quality Coil Guards  
Economizer  
Equipped with either dry bulb, reference  
or comparative enthalpy sensing, this  
feature provides free cooling as the  
outdoor temperature and/or humidity  
decreases. Economizers, correctly  
installed, offer valuable energy savings.  
Factory-installed economizers save time  
and ensure proper installation.  
— Wide array of Zone Sensors and  
Thermostats  
— Liquid Propane Conversion Kits  
— Factory built Roof Curb  
One of Our Finest Assets:  
Trane Sales Representatives are a  
Support group that can assist you with:  
— Product  
Phase Monitor  
Phase monitor shall provide 100%  
protection for motors and compressors  
against problems caused by phase loss,  
phase imbalance, and phase reversal.  
Phase monitor is equipped with an LED  
that provides an ON or FAULT indicator.  
— Application  
— Service  
Training  
— Special Applications  
— Specifications  
— Computer Programs and much more  
Clogged Filter/Fan Fail Switches  
Precedent has the features and benefits  
that make it first class in the light  
commercial rooftop market. Designed  
with input from field contractors and  
engineers, its airflow performance is  
outstanding.  
These sensors allow a zone sensor  
service light or Integrated Comfort  
System to indicate a dirty filter or a fan  
thats not working.The field installation  
charges for these valuable feedback  
devices often eliminate them from  
consideration. Factory installation can  
make such features a good investment.  
Precedent…The same Trane  
quality…with added flexibility.  
COMM3/4 Communication Interface  
Available factory or field-installed. This  
module, when applied with ReliaTel,  
easily interfaces withTranes Integrated  
ComfortSystem.  
RT-PRC017-EN  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
Quality And Reliability Testing  
We perform a 100% coil leak test at the  
factory. The evaporator and condenser  
coils are leak tested at 1375 kPa (200  
psig) and pressure tested to 3100 kPa  
(450 psig).  
• All Precedentdesigns were rigorously  
rain tested at the factory to ensure  
water integrity.  
• Actual shipping tests were performed  
to determine packaging requirements.  
Units were test shipped around the  
country to determine the best  
packaging.  
• All parts are inspected at the point of  
final assembly. Sub-standard parts are  
identified and rejected immediately.  
• The requirement for cycle testing of  
heat exchangers is 10,000 cycles by  
ANSI Z21.47. This is the standard  
required by both UL and AGA for cycle  
test requirments. Trane requires the  
design to be tested to 2½ times this  
current standard.  
• Factory shake and drop tests were  
used as part of the package design  
process to help assure that the unit  
arrives at the job site in top condition.  
• Rigging tests include lifting a unit into  
the air and letting it drop one foot,  
assuring that the lifting lugs and rails  
hold up under stress.  
• Every unit receives a 100% unit run test  
before leaving the production line to  
make sure it lives up to rigorousTrane  
requirements.  
We test designs at our factory not on  
our customers!  
VariTrac™  
VariTrac  
WhenTrane’s changeover VAV System  
for light commercial applications is  
coupled with Precedent, it provides the  
latest in technological advances for  
comfort management systems and can  
allow thermostat control in every zone  
served by VariTrac.  
8
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Application  
Considerations  
Heating Operation  
Application of this product should be  
within the cataloged airflow and cooling  
considerations.  
The heat exchanger is manufactured  
with aluminized steel. To prevent  
condensation within the heat exchanger,  
do not exceed 50% outside air.  
Low Ambient Cooling  
The Precedentline features, as  
standard, low ambient cooling down to  
-18°C (0°F). Contact your localTrane  
Representative for more assistance with  
low ambient cooling applications.  
Condensate Trap  
The evaporator is a draw-thru  
configuration. A trap must be field  
provided prior to start-up on the cooling  
cycle.  
Barometric Relief  
This product offers an optional  
Clearance Requirements  
The recommended clearances identified  
with unit dimensions should be  
maintained to assure adequate service,  
maximum capacity and peak operating  
efficiency. Actual clearances which  
appear inadequate should be reviewed  
with the localTrane sales personnel.  
barometric relief damper for use in  
conjunction with economizer option.  
This option consists of gravity dampers  
which open with increased pressure. As  
the building air pressure increases, the  
pressure in the unit return air section  
also increases, opening the dampers and  
relieving the conditioned space.  
Unit Pitch  
These units have reversible sloped  
condensate drain pans. Units must be  
installed level; any unit slope must be  
toward side of unit where condensate  
drain is connected.  
NOTE: THE EFFECTIVENESS OF  
BAROMETRIC RELIEF DAMPER DURING  
ECONOMIZING OPERATION IS SYSTEM  
RELATED. PRESSURE DROP OFTHE  
RETURN AIR SYSTEM SHOULD BE  
CONSIDERED TO CONTROL BUILDING  
PRESSURIZATION.  
RT-PRC017-EN  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Selection  
Procedures - SI Units  
Cooling Capacity  
Heating Capacity  
Step 1 — Calculate the buildings total  
and sensible cooling loads at design  
conditions. Use theTrane calculation  
form or any other standard accepted  
method.  
Step 1 — Calculate the building heating  
load using theTrane calculation form or  
other standard accepted method.  
Step 2 — Size the system heating  
capacity to match the calculated  
building heating load. The following  
are building heating requirements:  
a. Total heating load of 17.6 kW  
b. 3400 m3/h  
Example: The following are the building  
cooling requirements:  
a. Electrical Characteristics: 380-415/50/3  
b. Summer Design Conditions: Entering  
Evaporator Coil: 27° DB/ 19° WB  
Outdoor Ambient: 35°  
c. Fuel - Natural gas  
For the YSC060AD there are two  
heating capacities available, 19.6 kW  
and 29.3 kW input models shown in  
Table PD-32.The output capacities of  
these furnaces are 15.7 kW and 23.4 kW  
respectively.The high heat model with  
23.4 kW best matches the building  
requirements, indicating a YHC060AD*  
should be selected.  
c. Total Cooling Load: 16.5 kW  
d. Sensible Cooling Load: 11.8 kW  
e. Airflow: 3400 m3/h External Static  
Pressure: 125 Pa  
f. Downflow Configuration  
Step 2 — Size the equipment usingTable  
PD-1 to match the cooling loads at  
design conditions.  
Table PD-1 shows that aYSC060AD has  
a gross cooling capacity of 17.8 kW and  
14.4 kW sensible capacity at 35 DB  
ambient and 3400 m3/h with 27 DB/ 19  
WB air entering the evaporator.  
Air Delivery Selection  
External static pressure drop through  
the air distribution system has been  
calculated to be 150 Pa. EnterTable PD-  
8 for a YSC060AD*H at 3400 m3/h and  
150 Pa static pressure. The standard  
motor will give the desired airflow.  
Use the following formula to calculate  
fan motor heat, which can be found in  
the notes inTable PD-8:  
Accessory Selection  
Select accessories needed to  
accommodate the application.  
Fan motor heat (kW)  
= 1.144 x (Fan kW) + 0.132  
For example: With 3400 m3/h and 125 Pa,  
specified by the engineer,Table PD-8  
shows 0.73 kW for a high heat model.  
Fan motor heat =  
1.144 x 0.73 + 0.132 = 0.97kW  
NetTotal Cooling =  
17.8 kW - 0.97 = 16.8 kW  
Net Sensible Cooling Capacity  
14.4 kW - 0.97 = 13.4 kW.  
10  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Selection  
Procedures - IP Units  
Cooling Capacity  
Heating Capacity  
Step 1 — Calculate the buildings total  
and sensible cooling loads at design  
conditions. Use theTrane calculation  
form or any other standard accepted  
method.  
Step 1 — Calculate the building heating  
load using theTrane calculation form or  
other standard accepted method.  
Step 2 — Size the system heating  
capacity to match the calculated building  
heating load. The following are building  
heating requirements:  
Example: The following are the building  
cooling requirements:  
a. Electrical Characteristics: 380-415/50/3  
b. Summer Design Conditions: Entering  
Evaporator Coil: 80° DB/ 67° WB  
Outdoor Ambient: 95°  
a. Total heating load of 70.0 MBh  
b. 2000 cfm  
c. Fuel - Natural gas  
For the YSC060AD there are two heating  
capacities available, 67 MBh and 100  
MBh input models shown inTable PD-  
32. The output capacities of these  
furnaces are 54 MBh and 80 MBh  
respectively.The high heat model with  
80 MBh best matches the building  
requirements, indicating a YSC060AD*H  
should be selected.  
c. Total Cooling Load: 58 MBh  
d. Sensible Cooling Load: 42 MBh  
e. Airflow: 2000 cfm External Static  
Pressure: .6 in wg  
f. Downflow Configuration  
Step 2 — Size the equipment usingTable  
PD-1a to match the cooling loads at  
design conditions.  
Table PD-1a shows that aYSC060AD has  
a gross cooling capacity of 62.0 MBh and  
46.4 MBh sensible capacity at 95 DB  
ambient and 2000 cfm with 80 DB/ 67  
WB air entering the evaporator.  
Air Delivery Selection  
External static pressure drop through the  
air distribution system has been  
calculated to be 0.6 inches of water. Enter  
Table PD-8a for aYSC060AD*H at 2000  
cfm and 0.60 static pressure. The  
standard motor will give the desired  
airflow.  
Use the following formula to calculate  
fan motor heat, which can be found in  
the notes inTable PD-8a:  
Accessory Selection  
Select accessories needed to  
accommodate the application.  
Fan motor heat (MBh) =  
2.915 x (Fan bhp) + 0.451  
For example: With 2000 cfm and 0.60  
inches, specified by the engineer,Table  
PD-8a shows 1.06 bhp for a high heat  
model.  
Fan motor heat =  
2.915 x 1.06 + 0.451 = 3.5 MBh  
NetTotal Cooling =  
62.0 MBh - 3.5 = 58.5 MBh  
Net Sensible Cooling Capacity  
46.4 MBh - 3.5 = 42.9 MBh.  
RT-PRC017-EN  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model  
Number  
Description  
Y
1
S
2
C 060 A  
3 4,5,6 7  
D
8
R
9
L
A
**  
C
0
0
0
0
0
0
0
0
0
0
1
10 11 12,13 14 15 16 17 18 19 20 21 22 23 24 25  
Digit 18 - Through the Base Provisions  
Digit 1 - Unit Function  
Digits 12, 13 - Service Sequence  
** Factory Assigned  
0 = No Through the Base Provisions  
Y = DX Cooling, Gas Heat  
=
Digit 19 - Disconnect/Circuit Breaker/Phase  
Monitor (3 phase only)  
Digit 2 - Efficiency  
Digit 14 - Fresh Air Selection  
S = Standard Efficiency  
0 = No Fresh Air  
A = Manual Outside Air Damper 0-50%  
B = Motorized Outside Air Damper 0-50%  
C = Economizer, Dry Bulb 0-100%  
without Barometric Relief  
0 = No Disconnect or Circuit Breaker  
3 = Phase Monitor Only (No Disconnect,  
No Circuit Breaker)  
Digit 3 - Airflow  
C = Convertible  
D = Economizer, Dry Bulb 0-100%  
with Barometric Relief  
E = Economizer, Reference Enthalpy  
0-100% without Barometric Relief  
F = Economizer, Reference Enthalpy  
0-100% with Barometric Relief  
G = Economizer, Comparative Enthalpy  
0-100% without Barometric Relief  
H = Economizer, Comparative Enthalpy  
0-100% with Barometric Relief  
Digit 20 - Convenience Outlet  
Digits 4,5,6 - Nominal Gross Cooling  
Capacity (MBh)  
0 = No Convenience Outlet  
kW  
060 = 17.6  
072 = 21.1  
090 = 26.4  
102 = 29.9  
120 = 35.1  
Tons  
5
Digit 21 - Communications Options  
0 = No Communications Interface  
1 = Comm-3/4 Communications Interface  
2 = Comm-5 Communications Interface  
6
7.5  
8.5  
10  
Digit 22 - Refrigeration System Option  
Digit 7 - Major Design Sequence  
0 = Standard Refrigeration System  
Digit 15 - Supply Fan/Drive Type/Motor  
A = First  
0 = Standard Drive  
1 = Oversized Motor  
Digit 23 - Refrigeration Controls  
Digit 8 - Unit Voltage  
0 = No Refrigeration Control  
D = 380-415/50/3  
Digit 16 - Hinged Service AccessFilters  
Digit 24 - Smoke Detector  
0 = Standard Panels/Standard Filters  
A = Hinged Access Panels/Standard Filters  
B = Standard Panels/50 mm (2”)  
Pleated Filters  
C = Hinged Access Panels/50 mm 2”  
Pleated Filters  
Digit 9 - Unit Controls  
R = ReliaTelMicroprocessor  
0 = No Smoke Detector  
Digit 25 - Monitoring Controls  
Digit 10 - Heating Capacity  
0 = No Monitoring Control  
1 = Clogged Filter Switch  
2 = Fan Failure Switch  
3 = DischargeAir Sensing Tube  
4 = Clogged Filter Switch and Fan Fail  
Switch  
5 = Clogged Filter Switch and Discharge  
Air Sensing Tube  
6 = Fan Fail Switch and Discharge Air  
Sensing Tube  
L = Low  
H = High  
Digit 17 - Condenser Coil Protection  
0 = Standard Coil  
Digit 11 - Minor Design Sequence  
1 = Standard Coil with Hail Guard  
2 = Epoxy Coated Condenser Coil  
3 = Epoxy Coated Condenser Coil with  
Hail Guard  
A = First Sequence  
7 = Clogged Filter and Fan Fail Switches  
and Discharge Air Sensing Tube  
12  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Data  
Table GD-1 — General Data  
Convertible Units  
YSC060AD  
Convertible Units  
YSC072AD  
Convertible Units  
YSC090AD  
Convertible Units  
YSC102AD  
Convertible Units  
YSC120AD  
1
Cooling Performance  
Gross Capacity - kW (MBh)  
18.2 (62.0)  
2.99 (10.2)  
3400 (2000)  
3400 (2000)  
17.3 (59.0)  
5.78  
23.2 (79.0)  
3.08 (10.5)  
4080 (2400)  
3570 (2100)  
22.0 (75.0)  
7.14  
26.7 (91.0)  
3.02 (10.3)  
5100 (3000)  
4460 (2625)  
25.2 (86.0)  
8.35  
31.1 (106.0)  
3.02 (10.3)  
5780 (3400)  
5100 (3000)  
29.9 (102.0)  
9.9  
34.9 (119.0)  
2.99 (10.2)  
6800 (4000)  
5950 (3500)  
33.1 (113.0)  
11.08  
COP (EER) 2  
Nominal Airflow - m3/h (cfm)  
Rated Airflow - m3/h (cfm)  
Net Capacity - kW (MBh)  
System Power - kW  
3
Heating Performance  
Heating Models  
Low - G80 High - G120  
Low - G120 High G-200  
29.3 (100) 48.9 (167)  
Low - G120 High G-200  
Low - G150 High G-250 Low - G150 High G-250  
Heating Input - kW (MBH)  
Heating Output - kW (MBH)  
Steady State Efficiency %  
No. Burners  
19.6 (67)  
29.3 (100)  
29.3 (100)  
48.9 (167)  
36.7 (125) 60.9 (208) 36.7 (125)  
60.9 (208)  
15.7 (54)  
23.4 (80)  
23.4 (80)  
39.1 (134)  
23.4 (80)  
39.1 (134)  
29.3 (100)  
48.7 (166)  
29.3 (100)  
48.7 (166)  
90  
90  
90  
90  
90  
90  
90  
90  
90  
90  
2
1
3
1
3
1
4
2
3
1
4
2
3
2
5
2
3
2
5
2
No. Stages  
Gas Connection Pipe Size - in.  
3/4 NPT  
3/4 NPT  
3/4 NPT  
3/4 NPT  
3/4 NPT  
3/4 NPT  
3/4 NPT  
3/4 NPT  
3/4 NPT  
3/4 NPT  
Compressor  
Number -Type  
1-Climatuff Scroll  
80  
1-Trane 3-D Scroll  
85  
1-Trane 3-D Scroll  
85  
2-Climatuff Scroll  
83  
2-Climatuff Scroll  
79  
Outdoor Sound Rating dB 4  
Outdoor Coil - Type  
Lanced  
Lanced  
Lanced  
Lanced  
Lanced  
Tube Size in. OD  
0.3125  
1.02 (10.96)  
3 / 17  
0.3125  
1.29 (13.88)  
2 / 17  
0.3125  
1.29 (13.88)  
2 / 17  
0.3125  
1.75 (18.89)  
2 / 17  
0.3125  
2.41 (25.92)  
2 / 17  
Face Area - m2 (sq ft)  
Rows / FPI  
Indoor Coil - Type  
Lanced  
Lanced  
Lanced  
Lanced  
Lanced  
Tube Size OD - in.  
0.3125  
0.62 (6.68)  
3 / 16  
0.3125  
0.92 (9.89)  
2 / 16  
0.3125  
0.92 (9.89)  
3 / 16  
0.3125  
1.15 (12.36)  
3 / 16  
0.3125  
1.15 (12.36)  
4 / 16  
Face Area - m2 (sq ft)  
Rows / FPI  
Refrigerant Control  
Drain Connection No. / Size - in.  
Outdoor Fan - Type  
No. Used / Diameter - in.  
DriveType / No. Speeds  
CFM  
Short Orifice  
1 / 0.75 NPT  
Propeller  
1 / 22  
Direct / 1  
2900  
Short Orifice  
1 / 0.75 NPT  
Propeller  
1 / 26  
Direct / 1  
5100  
Short Orifice  
1 / 0.75 NPT  
Propeller  
1 / 26  
Direct / 1  
5200  
Short Orifice  
1 / 0.75 NPT  
Propeller  
1 / 26  
Direct / 1  
5500  
Short Orifice  
1 / 0.75 NPT  
Propeller  
1 / 26  
Direct / 1  
5800  
No. Motors / kW (HP)  
Motor RPM  
1 / 0.30 (0.40)  
950  
1 / .56 (0.75)  
950  
1 / .56 (0.75)  
950  
1 / .56 (0.75)  
950  
1 / .56 (0.75)  
950  
Belt Drive Indoor Fan -Type  
No. Used  
FC Centrifugal  
1
FC Centrifugal  
1
FC Centrifugal  
1
FC Centrifugal  
1
FC Centrifugal  
1
Fan Diameter x Width - mm (in.)  
DrvieType / No. Speeds  
No. Motors  
280 X 280 (11 x 11)  
Belt / Variable Speed  
1
305 X 305 (12 x 12)  
Belt / Variable Speed  
1
305 X 305 (12 x 12)  
Belt / Variable Speed  
1
381 X 381 (15 x 15)  
Belt / Variable Speed  
1
381 X 381 (15 x 15)  
Belt / Variable Speed  
1
Standard Motor Power - kW (HP)  
Oversized Motor Power - kW (HP)  
Motor RPM - Standard / Oversized  
Motor Frame Size  
1.1 (1.5)  
-
1450 / -  
56  
1.1 (1.5)  
1.5 (2.0)  
1450 / 1450  
56  
1.5 (2.0)  
2.2 (3.0)  
1450 / 2850  
56  
1.5 (2.0)  
2.2 (3.0)  
1450 / 2850  
56  
2.2 (3.0)  
-
2850 / -  
56  
Filters - Type Furnished  
(No.) Size Reccommended - mm  
(No.) Size Reccommended - in.  
Refrigerant Charge - kg (lbs) of R-22 5  
Throwaway  
(2) 508 X 762 X 25  
(2) 20 X 30 X 1  
3.7 (8.2)  
Throwaway  
(4) 406 X 635 X 50  
(4) 16 X 25 X 2  
3.7 (8.2)  
Throwaway  
(4) 406 X 635 X 50  
(4) 16 X 25 X 2  
4.5 (10.0)  
Throwaway  
(4) 508 X 635 X 50  
(4) 20 X 25 X 2  
Circuit 1 - 3.8 (8.3)  
Circuit 2 - 2.0 (4.4)  
Throwaway  
(4) 508 X 635 X 50  
(4) 20 X 25 X 2  
Circuit 1 - 3.4 (7.5)  
Circuit 2 - 3.3 (7.3)  
Notes:  
1. Cooling Performance is rated at 35.0 C (95 F) ambient, 26.7 C (80 F) entering dry bulb, 19.4 C (67 F) entering wet bulb. Gross capacity does not include the effect of fan motor  
heat. Net capacity includes the effect of fan motor heat. Units are suitable for operation to 20 % of nominal airflow.  
2. EER are rated at ARI conditions.  
3. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards.  
Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.  
4. Outdoor Sound rating shown is tested in accordance with ARI Standard 270. For more information refer to Performance Data Table "Sound Power Level".  
5. Refrigerant charge is an approcimate value. For a more precise value, see unit nameplate and service literature.  
RT-PRC017-EN  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-1 — Gross Cooling Capacities (kW) -YSC060AD - (SI)  
Ambient Temperature (C)  
Enter.  
Dry  
Bulb  
30  
35  
40  
19  
45  
19  
Entering Wet Bulb Temperature (C)  
19 22 16  
m3/h  
Temp  
16  
19  
22  
16  
22  
16  
22  
Airflow (C)  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
16.2 13.9 18.5 11.3 19.9 8.3 15.0 13.3 17.4 11.3 19.3 8.0 13.9 12.7 16.1 10.7 18.4 7.5 12.7 12.1 14.7 9.5 17.3 7.0  
16.7 16.7 18.6 14.1 20.0 11.1 15.8 15.8 17.4 13.6 19.4 10.8 14.8 14.8 16.1 13.0 18.5 10.3 13.8 13.8 14.7 12.3 17.3 9.8  
18.1 18.1 18.7 16.9 20.2 13.6 17.2 17.2 17.7 16.5 19.5 13.5 16.2 16.2 16.5 15.9 18.5 13.1 15.1 15.1 15.1 15.1 17.3 12.6  
19.3 19.3 19.2 19.2 20.3 16.2 18.5 18.5 18.5 18.5 19.6 16.1 17.6 17.6 17.6 17.6 18.7 15.9 16.6 16.6 16.6 16.6 17.5 15.4  
16.7 14.8 18.8 11.8 20.1 8.6 15.5 14.2 17.8 11.3 19.5 8.3 14.2 13.5 16.5 11.4 18.7 7.7 13.1 12.9 15.0 10.8 17.6 7.2  
17.5 17.5 18.9 14.9 20.2 11.4 16.5 16.5 17.8 14.4 19.6 11.2 15.4 15.4 16.5 13.8 18.8 10.8 14.4 14.4 15.1 13.1 17.6 10.3  
18.8 18.8 19.1 17.9 20.4 14.1 17.9 17.9 18.2 17.6 19.7 14.1 16.9 16.9 17.0 17.0 18.8 13.8 15.8 15.8 15.8 15.8 17.7 13.4  
19.8 19.8 19.8 19.8 20.6 16.8 19.2 19.2 19.2 19.2 19.9 16.9 18.3 18.3 18.3 18.3 19.0 16.8 17.4 17.4 17.4 17.4 17.9 16.4  
17.1 15.6 19.1 12.3 20.2 8.8 15.9 15.0 18.1 11.8 19.7 8.5 14.6 14.3 16.8 11.2 18.9 7.9 13.4 13.4 15.3 11.4 17.8 7.5  
18.1 18.1 19.2 15.5 20.4 11.6 17.1 17.1 18.2 15.1 19.8 11.5 16.0 16.0 16.9 14.6 19.0 11.3 14.9 14.9 15.4 13.9 17.9 10.8  
19.3 19.3 19.5 18.7 20.6 14.5 18.5 18.5 18.6 18.6 20.0 14.6 17.6 17.6 17.6 17.6 19.1 14.4 16.5 16.5 16.5 16.5 17.9 14.1  
20.2 20.2 20.2 20.2 20.8 17.4 19.6 19.6 19.6 19.6 20.2 17.6 18.9 18.9 18.9 18.9 19.3 17.6 18.0 18.0 18.0 18.0 18.3 17.4  
17.4 16.4 19.3 12.6 20.3 9.1 16.2 15.8 18.4 12.2 19.8 8.8 14.9 14.9 17.1 11.7 19.0 8.1 13.9 13.9 15.5 12.1 18.0 7.7  
18.6 18.6 19.4 16.1 20.5 12.3 17.7 17.7 18.4 15.8 19.9 11.8 16.6 16.6 17.2 15.3 19.1 11.6 15.4 15.4 15.8 14.6 18.1 11.2  
19.7 19.7 19.7 19.4 20.7 14.9 19.0 19.0 19.0 19.0 20.1 15.0 18.1 18.1 18.1 18.1 19.3 15.0 17.1 17.1 17.1 17.1 18.2 14.7  
20.5 20.5 20.5 20.5 20.9 17.9 20.0 20.0 20.0 20.0 20.4 18.2 19.3 19.3 19.3 19.3 19.5 18.3 18.4 18.4 18.4 18.4 18.6 18.2  
24  
27  
30  
3060  
33  
24  
27  
3400  
30  
33  
24  
27  
3740  
30  
33  
24  
27  
4080  
30  
33  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.  
2. TGC = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
Table PD-1a _ Gross Cooling Capacities (MBH) _ YSC060AD _ (IP)  
Ambient Temperature (F)  
Enter.  
Dry  
Bulb  
85  
95  
105  
67  
115  
67  
Entering Wet Bulb Temperature (F)  
67  
CFM  
Temp  
61  
67  
73  
61  
73  
61  
73  
61  
73  
Airflow (F)  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
56.1 47.1 64.4 37.0 68.8 25.1 51.6 44.7 60.6 36.7 66.9 23.9 47.0 42.4 55.6 34.5 64.0 22.6 42.4 40.1 50.2 30.3 60.0 20.8  
57.3 56.5 64.6 45.8 69.3 34.2 53.3 53.3 60.7 43.9 67.3 32.9 49.5 49.5 55.7 41.6 64.2 31.4 45.7 45.7 50.4 39.2 60.1 29.6  
61.3 61.3 64.9 54.5 69.7 42.0 57.7 57.7 61.0 52.9 67.6 41.4 53.9 53.9 56.3 50.7 64.4 40.3 50.0 50.0 51.2 48.3 60.2 38.4  
65.0 65.0 65.8 63.3 70.4 49.7 62.1 62.1 62.4 62.2 68.0 49.7 58.5 58.5 58.5 58.5 64.6 48.8 54.4 54.4 54.4 54.4 60.3 47.2  
57.5 49.8 65.4 38.5 69.3 25.5 53.0 47.5 61.8 38.7 67.5 24.4 48.3 45.1 56.9 36.6 64.7 23.0 43.7 42.8 51.3 34.2 60.9 21.4  
59.3 59.3 65.6 47.9 69.8 35.4 55.7 55.7 62.0 46.4 68.0 34.2 51.6 51.6 57.1 44.1 65.0 32.7 47.7 47.7 51.5 41.6 61.0 30.9  
63.6 63.6 66.0 57.3 70.5 43.1 60.3 60.3 62.5 56.2 68.3 43.0 56.4 56.4 58.0 54.1 65.2 42.1 52.2 52.2 52.8 51.7 61.2 40.6  
66.9 66.9 67.2 66.5 71.1 51.4 64.4 64.4 64.4 64.4 68.9 51.8 61.0 61.0 61.0 61.0 65.6 51.3 57.1 57.1 57.1 57.1 61.5 50.1  
58.8 52.5 66.1 39.8 69.6 25.9 54.3 50.2 62.8 38.1 67.9 24.9 49.4 47.8 58.0 38.6 65.3 23.4 44.8 44.8 52.2 36.2 61.6 21.7  
61.5 61.5 66.4 49.8 70.3 36.8 57.8 57.8 63.0 48.6 68.3 35.0 53.6 53.6 58.2 46.5 65.6 33.9 49.4 49.4 52.6 44.0 61.8 32.2  
65.4 65.4 67.0 59.8 71.0 44.6 62.4 62.4 63.7 59.2 69.0 44.3 58.7 58.7 59.4 57.4 66.0 43.8 54.3 54.3 54.3 54.3 62.0 42.5  
68.4 68.4 68.4 68.4 71.7 52.8 66.1 66.1 66.1 66.1 69.6 53.6 63.1 63.1 63.0 63.0 66.4 53.6 59.3 59.3 59.3 59.3 62.4 52.7  
60.0 55.1 66.6 40.8 70.0 26.4 55.5 52.8 63.6 39.6 68.3 25.3 50.6 50.4 59.0 37.4 65.7 24.0 46.2 46.2 53.1 38.2 62.2 22.1  
63.2 63.2 67.1 51.4 70.7 37.7 59.6 59.6 63.8 50.7 68.8 35.8 55.4 55.4 59.2 48.8 66.2 35.0 51.1 51.1 53.5 46.3 62.4 33.4  
66.7 66.7 67.8 62.0 71.5 45.3 64.1 64.1 64.8 61.9 69.5 45.5 60.5 60.5 60.8 60.6 66.6 45.2 56.3 56.3 56.2 56.2 62.7 44.3  
69.5 69.5 69.5 69.5 72.1 54.1 67.4 67.4 67.4 67.4 70.2 55.3 64.6 64.6 64.5 64.5 67.1 55.7 61.1 61.1 61.0 61.0 63.2 55.1  
75  
80  
85  
1800  
90  
75  
80  
2000  
85  
90  
75  
80  
2200  
85  
90  
75  
80  
2400  
85  
90  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.  
2. TGC = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
14  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-2 - Gross Cooling Capacities (kW) -YSC072AD - (SI)  
Ambient Temperature (C)  
Enter.  
Dry  
Bulb  
30  
35  
40  
19  
45  
19  
Entering Wet Bulb Temperature (C)  
19 22 16  
m3/h  
Temp  
16  
19  
22  
16  
22  
16  
22  
Airflow (C)  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
20.9 17.5 23.3 14.6 24.6 10.3 19.7 16.8 22.4 13.6 24.0 9.9 18.4 16.1 21.2 12.9 23.2 9.4 17.1 15.4 19.7 12.9 22.0 9.0  
21.6 21.2 23.4 17.4 24.8 13.5 20.4 20.4 22.5 17.0 24.1 13.3 19.4 19.4 21.2 16.4 23.3 12.8 18.2 18.2 19.8 15.7 22.1 12.3  
22.9 22.9 23.6 20.6 25.0 16.5 22.1 22.1 22.7 20.4 24.3 16.3 21.0 21.0 21.5 19.9 23.5 16.1 19.9 19.9 20.2 19.2 22.2 15.6  
24.0 24.0 24.1 23.8 25.2 19.4 23.4 23.4 23.3 23.3 24.5 19.3 22.5 22.5 22.4 22.4 23.6 19.3 21.4 21.4 21.4 21.4 22.3 18.8  
21.5 18.5 23.6 15.2 24.8 10.6 20.3 17.9 22.8 14.2 24.2 10.1 19.0 17.2 21.6 13.6 23.4 9.8 17.6 16.4 20.1 12.9 22.3 9.3  
22.3 22.3 23.8 18.1 25.1 14.5 21.3 21.3 22.9 17.9 24.3 13.6 20.2 20.2 21.6 17.3 23.6 13.4 19.0 19.0 20.2 16.6 22.4 12.8  
23.6 23.6 24.0 21.6 25.3 17.6 22.9 22.9 23.2 21.5 24.6 16.8 21.8 21.8 22.0 21.1 23.7 16.7 20.7 20.7 20.8 20.5 22.5 16.3  
24.6 24.6 24.6 24.6 25.5 20.0 23.9 23.9 23.9 23.9 24.8 20.1 23.1 23.1 23.1 23.1 23.9 20.1 22.1 22.1 22.1 22.1 22.7 19.8  
22.0 19.5 23.9 15.8 25.0 10.7 20.8 18.9 23.1 14.7 24.4 10.4 19.5 18.2 21.9 14.2 23.5 10.1 18.1 17.4 20.5 13.5 22.5 9.6  
22.9 22.9 24.0 18.7 25.3 13.9 22.1 22.1 23.2 18.6 24.5 13.9 20.9 20.9 22.0 18.2 23.7 13.6 19.7 19.7 20.6 17.6 22.6 13.3  
24.1 24.1 24.3 22.4 25.5 17.4 23.4 23.4 23.5 22.4 24.8 17.3 22.5 22.5 22.5 22.2 23.9 17.2 21.3 21.3 21.3 21.3 22.8 17.0  
25.0 25.0 25.0 25.0 25.7 20.7 24.4 24.4 24.4 24.4 25.1 20.8 23.7 23.7 23.7 23.7 24.2 20.8 22.6 22.6 22.6 22.6 23.1 20.7  
22.4 20.3 24.1 16.3 25.2 10.9 21.2 19.8 23.2 15.1 24.5 10.7 19.9 19.1 22.2 14.7 23.6 10.3 18.5 18.4 20.8 14.0 22.7 9.9  
23.4 23.4 24.3 19.3 25.5 14.5 22.6 22.6 23.4 19.2 24.7 14.7 21.5 21.5 22.3 19.0 23.8 14.0 20.3 20.3 20.9 18.4 22.8 13.7  
24.5 24.5 24.6 23.2 25.6 17.8 23.8 23.8 23.9 23.2 25.0 17.8 23.0 23.0 23.0 23.0 24.1 17.7 21.8 21.8 21.8 21.8 23.0 17.7  
25.4 25.4 25.4 25.4 25.9 21.2 24.8 24.8 24.8 24.8 25.3 21.4 24.1 24.1 24.1 24.1 24.4 21.4 23.1 23.1 23.1 23.1 23.4 21.6  
24  
27  
30  
3670  
33  
24  
27  
4080  
30  
33  
24  
27  
4490  
30  
33  
24  
27  
4900  
30  
33  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.  
2. TGC = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
Table PD-2a _ Gross Cooling Capacities (MBH) -YSC072AD - (IP)  
Ambient Temperature (F)  
Enter.  
Dry  
Bulb  
85  
95  
105  
67  
115  
67  
Entering Wet Bulb Temperature (F)  
67  
CFM  
Temp  
61  
67  
73  
61  
73  
61  
73  
61  
73  
Airflow (F)  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
72.2 59.1 80.6 47.1 85.1 31.0 67.5 56.5 77.7 44.1 82.7 29.6 62.6 53.9 73.0 41.8 79.9 28.0 57.4 51.2 67.5 39.2 75.5 26.0  
73.8 70.7 81.0 56.1 85.8 42.2 69.4 68.2 77.9 55.0 83.4 40.7 65.0 65.0 73.1 52.6 80.4 39.0 60.6 60.6 67.6 50.0 75.8 36.8  
77.7 77.7 81.4 66.3 86.3 51.7 74.3 74.3 78.2 65.6 83.8 50.1 70.3 70.3 73.6 63.5 80.7 49.2 66.0 66.0 68.3 61.0 76.1 47.4  
81.3 81.3 82.4 76.3 87.1 59.8 78.8 78.8 79.4 76.0 84.6 59.4 75.1 75.1 75.3 74.6 81.3 59.0 70.8 70.8 70.7 70.7 76.6 57.4  
74.2 62.5 81.6 49.2 85.7 31.5 69.3 59.9 78.7 46.0 83.4 30.1 64.4 57.3 74.2 43.7 80.2 28.5 59.1 54.6 68.9 41.1 76.3 26.6  
76.1 75.0 82.1 58.2 86.5 43.7 72.1 72.1 79.0 57.4 84.2 42.1 67.9 67.9 74.4 55.4 80.9 40.4 63.3 63.3 69.0 53.0 76.8 38.4  
80.0 80.0 82.6 69.1 86.8 52.8 77.1 77.1 79.5 68.7 84.7 51.6 73.1 73.1 75.3 67.3 81.4 50.7 68.7 68.7 70.1 65.0 77.2 49.4  
83.3 83.3 83.8 79.7 87.1 61.5 80.7 80.7 80.9 79.4 85.5 61.5 77.5 77.5 77.5 77.5 82.1 61.1 73.3 73.3 73.3 73.3 77.8 60.2  
75.8 65.6 82.3 50.7 86.2 32.0 71.0 63.2 79.4 49.8 84.0 30.7 66.0 60.6 75.4 45.6 80.7 29.0 60.6 57.8 70.0 42.9 77.0 27.2  
78.1 78.1 82.9 60.1 87.2 44.1 74.6 74.6 79.8 59.4 84.7 44.3 70.3 70.3 75.6 58.1 81.2 41.3 65.7 65.7 70.1 55.7 77.6 39.8  
81.7 81.7 83.6 71.6 88.2 54.0 79.1 79.1 80.5 71.3 85.4 53.6 75.4 75.4 76.6 70.7 82.0 52.1 70.9 70.9 71.6 68.7 78.1 51.3  
84.8 84.8 85.0 82.5 89.1 62.3 82.3 82.3 82.3 82.3 86.1 61.2 79.4 79.4 79.4 79.4 82.8 63.0 75.2 75.2 75.2 75.2 78.7 62.8  
77.0 68.3 82.9 52.2 86.6 32.5 72.5 66.4 80.0 51.4 84.5 31.2 67.5 63.7 76.2 47.1 81.2 29.5 62.1 61.0 70.8 44.7 77.6 27.8  
79.6 79.6 83.7 61.8 87.6 44.7 76.6 76.6 80.6 61.3 85.4 44.0 72.4 72.4 76.5 60.5 81.8 42.1 67.7 67.7 71.1 58.2 78.1 40.9  
83.0 83.0 84.4 73.9 88.7 54.9 80.4 80.4 81.5 73.9 86.2 54.1 77.1 77.1 77.8 73.8 82.7 53.5 72.7 72.7 72.9 71.9 78.8 53.0  
85.9 85.9 86.0 85.0 89.6 65.2 83.6 83.6 83.6 83.6 87.0 63.2 81.0 81.0 81.0 81.0 83.5 65.0 76.8 76.8 76.8 76.8 79.5 65.3  
75  
80  
85  
2160  
90  
75  
80  
2400  
85  
90  
75  
80  
2640  
85  
90  
75  
80  
2880  
85  
90  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.  
2. TGC = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
RT-PRC017-EN  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-3 - Gross Cooling Capacities (kW) -YSC090AD - (SI)  
Ambient Temperature (C)  
Enter.  
Dry  
Bulb  
30  
35  
40  
19  
45  
19  
Entering Wet Bulb Temperature (C)  
19 22 16  
m3/h  
Temp  
16  
19  
22  
16  
22  
16  
22  
Airflow (C)  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
24.5 21.6 26.9 17.1 28.1 12.0 22.7 20.6 25.8 16.3 27.7 11.5 20.8 19.6 24.1 15.4 26.8 11.0 19.0 18.7 22.0 14.8 25.6 10.3  
25.4 25.4 27.1 21.1 28.5 15.9 24.1 24.1 25.9 20.8 27.8 15.9 22.5 22.5 24.3 20.0 27.0 15.5 20.9 20.9 22.2 19.0 25.7 14.8  
27.0 27.0 27.4 25.3 28.7 19.5 26.0 26.0 26.4 25.3 28.1 19.7 24.8 24.8 25.0 24.8 27.1 19.6 23.2 23.2 23.1 23.1 25.8 19.2  
28.1 28.1 28.1 28.1 29.0 23.3 27.5 27.5 27.5 27.5 28.4 23.6 26.5 26.5 26.5 26.5 27.4 23.9 25.3 25.3 25.3 25.3 26.1 23.6  
25.1 23.0 27.2 18.1 28.4 12.4 23.4 22.1 26.2 17.1 27.8 11.9 21.4 21.1 24.6 16.8 27.1 11.3 19.7 19.7 22.5 15.3 25.9 10.7  
26.3 26.3 27.4 22.0 28.6 16.3 25.1 25.1 26.4 22.0 28.0 16.2 23.6 23.6 24.9 21.4 27.2 16.0 21.9 21.9 22.8 20.4 26.0 15.6  
27.6 27.6 27.8 26.4 29.0 20.2 26.8 26.8 27.0 26.8 28.3 20.4 25.7 25.7 25.7 25.7 27.4 20.6 24.3 24.3 24.3 24.3 26.2 20.4  
28.6 28.6 28.6 28.6 29.3 24.1 28.1 28.1 28.1 28.1 28.7 24.6 27.3 27.3 27.3 27.3 27.8 25.0 26.2 26.2 26.2 26.2 26.6 25.1  
25.6 24.2 27.4 18.4 28.4 12.5 24.0 23.5 26.5 18.3 28.0 12.2 22.0 22.0 25.1 17.1 27.3 11.7 20.4 20.4 22.9 16.2 26.2 11.1  
26.9 26.9 27.7 22.8 28.8 16.5 25.9 25.9 26.8 23.0 28.3 16.7 24.5 24.5 25.4 22.7 27.4 16.5 22.8 22.8 23.5 21.8 26.3 16.3  
28.0 28.0 28.1 27.3 29.1 20.6 27.4 27.4 27.4 27.4 28.7 21.2 26.5 26.5 26.4 26.4 27.7 21.4 25.2 25.2 25.2 25.2 26.5 21.4  
28.9 28.9 28.9 28.9 29.5 24.7 28.5 28.5 28.5 28.5 29.1 25.6 27.8 27.8 27.8 27.8 28.1 26.0 26.8 26.8 26.8 26.8 27.0 26.3  
26.1 25.4 27.6 18.5 28.5 12.7 24.5 24.5 26.7 19.1 28.1 12.5 22.8 22.8 25.4 18.0 27.4 12.0 21.1 21.1 23.4 17.0 26.3 11.4  
27.3 27.3 27.9 23.4 28.9 16.8 26.5 26.5 27.1 23.9 28.5 17.1 25.3 25.3 25.8 23.8 27.7 17.0 23.6 23.6 24.1 23.1 26.5 16.9  
28.3 28.3 28.4 28.1 29.2 21.0 27.8 27.8 27.8 27.8 28.8 21.8 27.0 27.0 27.0 27.0 27.9 22.1 25.8 25.8 25.8 25.8 26.8 22.3  
29.1 29.1 29.1 29.1 29.6 25.2 28.8 28.8 28.8 28.8 29.3 26.4 28.2 28.2 28.2 28.2 28.4 26.9 27.3 27.3 27.3 27.3 27.4 27.4  
24  
27  
30  
4590  
33  
24  
27  
5100  
30  
33  
24  
27  
5610  
30  
33  
24  
27  
6120  
30  
33  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.  
2. TGC = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
Table PD-3a - Gross Cooling Capacities (MBH) -YSC090AD - (IP)  
Ambient Temperature (F)  
Enter.  
Dry  
Bulb  
85  
95  
105  
67  
115  
67  
Entering Wet Bulb Temperature (F)  
67  
CFM  
Temp  
61  
67  
73  
61  
73  
61  
73  
61  
73  
Airflow (F)  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
84.4 72.7 92.7 55.2 96.6 35.6 77.7 69.1 89.4 52.6 95.2 34.0 70.4 65.4 83.4 50.6 92.5 32.0 63.7 61.9 75.3 46.9 88.2 29.8  
86.5 86.5 93.3 67.5 97.8 48.9 81.2 81.2 89.6 66.8 96.2 48.4 75.1 75.1 83.8 64.0 93.1 46.6 69.4 69.4 75.8 60.3 88.5 44.1  
91.5 91.5 94.2 80.6 98.9 59.9 87.7 87.7 90.6 80.8 97.2 60.5 82.5 82.5 85.1 78.8 93.5 59.5 76.4 76.4 77.7 75.2 88.8 58.1  
95.1 95.1 95.7 93.2 100.0 71.0 92.6 92.6 92.5 92.5 97.5 71.8 88.7 88.7 88.7 88.7 94.3 72.6 83.7 83.7 83.6 83.6 89.5 71.8  
86.5 77.3 93.5 56.9 97.1 36.1 80.0 73.9 90.6 56.4 95.8 34.6 72.6 70.1 85.2 52.3 93.2 32.7 65.6 65.6 76.9 49.9 89.1 30.5  
89.4 89.4 94.3 70.0 98.3 52.8 84.9 84.9 91.0 70.2 96.9 49.4 78.8 78.8 85.6 68.2 93.9 48.9 72.7 72.7 77.8 64.5 89.6 46.3  
93.6 93.6 95.4 83.8 99.4 61.1 90.6 90.6 92.2 85.2 98.0 62.3 86.1 86.1 87.3 84.2 94.5 61.9 80.1 80.1 80.1 80.1 90.0 61.2  
96.8 96.8 97.0 96.7 100.5 72.8 94.8 94.8 94.8 94.8 99.0 75.4 91.5 91.5 91.4 91.4 95.4 75.8 87.0 87.0 87.0 87.0 90.9 75.9  
88.1 81.3 94.3 59.1 97.5 36.7 82.1 78.5 91.4 58.6 96.2 35.2 74.1 74.1 86.4 54.8 93.7 33.4 68.1 68.1 78.5 51.2 89.8 31.2  
91.4 91.4 95.1 72.1 98.7 50.2 87.6 87.6 92.1 73.3 97.4 50.3 82.2 82.2 87.1 72.0 94.5 49.7 75.6 75.6 79.7 68.7 90.4 48.3  
95.1 95.1 96.2 86.6 99.8 62.1 92.7 92.7 93.6 89.0 98.5 63.8 88.8 88.8 89.2 89.1 95.2 64.0 83.5 83.5 83.5 83.5 90.9 63.9  
97.9 97.9 97.9 97.9 101.0 74.3 96.4 96.4 96.3 96.3 99.7 77.5 93.5 93.5 93.5 93.5 96.3 78.6 89.4 89.4 89.4 89.4 92.1 79.5  
89.5 85.0 95.1 60.6 97.8 37.2 84.0 83.1 92.2 60.7 96.6 35.7 76.7 76.7 87.5 57.3 94.1 34.0 70.4 70.4 80.0 53.8 90.4 31.9  
92.9 92.9 95.6 74.0 99.0 50.8 89.7 89.7 93.0 76.0 97.8 51.0 84.8 84.8 88.3 75.6 95.2 50.9 78.1 78.1 81.6 72.8 90.9 49.5  
96.2 96.2 96.9 88.9 100.2 63.1 94.2 94.2 94.7 92.3 99.0 65.1 90.7 90.7 90.7 90.7 95.8 65.8 86.0 86.0 86.0 86.0 91.7 66.3  
98.7 98.7 98.7 98.7 101.3 75.7 97.5 97.5 97.5 97.5 100.1 79.4 94.9 94.9 94.9 94.9 97.0 81.1 91.2 91.2 91.2 91.2 93.0 82.7  
75  
80  
85  
2700  
90  
75  
80  
3000  
85  
90  
75  
80  
3300  
85  
90  
75  
80  
3600  
85  
90  
NOTES:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.  
2. TGC = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
16  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-4 - Gross Cooling Capacities (kW) -YSC102AD - (SI)  
Ambient Temperature (C)  
Enter.  
Dry  
Bulb  
30  
35  
40  
19  
45  
19  
Entering Wet Bulb Temperature (C)  
19 22 16  
m3/h  
Temp  
16  
19  
22  
16  
22  
16  
22  
Airflow (C)  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
28.0 24.3 31.5 19.5 33.4 14.1 26.0 23.3 30.0 18.7 32.5 13.5 23.9 22.2 27.8 17.7 31.3 12.9 21.6 21.6 25.4 17.3 29.7 12.2  
29.0 28.4 31.6 24.3 33.6 18.7 27.4 27.1 30.1 23.6 32.7 18.5 25.6 25.6 28.0 22.7 31.4 17.8 23.9 23.9 25.6 21.6 29.8 17.1  
31.0 31.0 31.9 29.0 33.9 23.0 29.7 29.7 30.5 28.6 32.9 22.8 28.1 28.1 28.1 28.1 31.5 22.5 26.3 26.3 26.5 25.7 29.9 22.0  
32.6 32.6 32.7 32.1 34.1 27.3 31.6 31.6 31.6 31.4 33.2 27.3 30.4 30.4 30.3 30.3 31.8 27.2 28.9 28.9 28.8 28.8 30.2 26.8  
28.8 25.8 31.9 20.4 33.6 14.4 26.8 24.8 30.5 19.6 32.8 13.9 24.2 24.2 28.5 18.7 31.6 13.4 22.5 22.5 26.0 17.6 30.1 12.6  
30.1 29.8 32.1 25.4 34.0 19.2 28.6 28.6 30.7 25.0 32.9 19.1 26.8 26.8 28.8 24.2 31.7 18.6 25.0 25.0 26.3 23.1 30.2 17.9  
32.0 32.0 32.5 30.5 34.2 23.7 30.9 30.9 30.9 30.9 33.2 23.7 29.4 29.4 29.4 29.4 31.9 23.6 27.6 27.6 27.7 27.2 30.3 23.2  
33.4 33.4 33.4 33.2 34.5 28.1 32.6 32.6 32.5 32.5 33.6 28.5 31.4 31.4 31.4 31.4 32.3 28.5 30.0 30.0 30.0 30.0 30.8 28.3  
29.5 27.3 32.2 21.1 33.8 14.7 27.6 26.3 31.0 20.5 33.0 14.4 25.1 25.1 29.1 19.6 31.8 13.8 23.5 22.9 26.5 18.5 30.4 12.9  
31.0 31.0 32.5 26.5 34.2 19.7 29.7 29.7 31.2 26.3 33.3 19.5 27.9 27.9 29.4 25.6 32.0 19.2 26.0 26.0 27.0 24.5 30.5 18.7  
32.7 32.7 33.0 31.7 34.6 24.5 31.7 31.7 31.7 31.7 33.6 24.6 30.4 30.4 30.5 29.9 32.3 24.5 28.8 28.8 28.8 28.6 30.7 24.3  
34.0 34.0 34.0 34.0 34.8 28.9 33.2 33.2 33.2 33.2 33.9 29.5 32.1 32.1 32.1 32.1 32.7 29.7 30.9 30.9 30.9 30.9 31.3 29.7  
30.1 28.7 32.5 21.7 33.9 15.1 27.9 27.9 31.3 21.4 33.1 14.7 26.0 26.0 29.3 20.4 32.2 14.2 24.2 23.9 27.0 19.4 30.6 13.3  
31.7 31.7 32.8 27.4 34.4 20.0 30.5 30.5 31.6 27.4 33.4 20.0 28.8 28.8 29.8 26.9 32.3 19.7 26.9 26.9 27.6 25.9 30.7 19.4  
33.2 33.2 33.2 33.2 34.8 25.0 32.3 32.3 32.4 31.7 33.7 25.2 31.2 31.2 31.2 30.9 32.6 25.4 29.7 29.7 29.7 29.7 31.0 25.3  
34.4 34.4 34.4 34.4 35.2 30.0 33.7 33.7 33.7 33.7 34.2 30.4 32.9 32.9 32.9 32.9 33.1 30.8 31.5 31.5 31.5 31.5 31.4 31.4  
24  
27  
30  
5200  
33  
24  
27  
5780  
30  
33  
24  
27  
6360  
30  
33  
24  
27  
6940  
30  
33  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.  
2. TGC = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
Table PD-4a - Gross Cooling Capacities (MBH) -YSC102AD - (IP)  
Ambient Temperature (F)  
Enter.  
Dry  
Bulb  
85  
95  
105  
67  
115  
67  
Entering Wet Bulb Temperature (F)  
67  
CFM  
Temp  
61  
67  
73  
61  
73  
61  
73  
61  
73  
Airflow (F)  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
96.7 81.9 109.1 63.4 115.0 42.2 89.1 78.1 104.0 60.7 112.1 40.4 81.2 74.1 96.3 59.2 107.9 38.3 73.7 70.3 87.0 55.2 102.4 35.8  
98.2 98.2 109.4 78.3 116.1 58.1 92.7 90.8 104.2 76.3 113.0 56.2 85.7 85.2 96.6 72.9 108.5 53.9 79.3 79.3 87.4 68.8 102.7 51.3  
105.0 105.0 110.2 93.1 117.3 70.8 100.0 100.0 105.0 91.8 113.6 70.4 93.6 93.6 98.0 88.8 108.9 68.7 86.8 86.8 89.2 84.7 103.1 66.7  
110.4 110.4 111.6 107.4 118.0 84.0 106.5 106.5 106.4 106.4 114.4 83.5 101.4 101.4 101.7 99.6 109.6 83.1 94.8 94.8 94.9 94.6 103.5 81.6  
99.3 87.0 110.2 65.9 115.6 42.9 91.8 83.2 105.8 63.7 112.9 41.1 83.6 79.1 98.7 60.6 108.8 39.0 75.2 75.2 89.0 58.6 103.4 36.5  
102.5 100.4 110.9 81.6 116.9 59.2 96.7 95.9 106.0 80.4 113.8 58.8 89.7 89.7 99.0 77.4 109.6 56.1 82.9 82.9 89.7 73.3 103.9 53.5  
108.4 108.4 111.9 97.4 118.2 72.7 104.1 104.1 107.2 97.0 114.6 72.7 98.2 98.2 100.8 94.9 110.1 71.5 91.0 91.0 91.0 91.0 104.2 70.0  
113.2 113.2 113.1 113.1 119.5 86.5 109.7 109.7 109.9 107.6 115.6 86.6 105.1 105.1 105.1 104.4 111.0 86.9 99.4 99.4 99.2 99.2 105.1 86.0  
101.6 91.8 111.3 67.8 116.2 43.6 94.3 88.2 107.1 66.5 113.5 41.8 84.7 84.7 100.4 63.0 109.5 39.6 78.4 76.4 90.9 59.0 104.2 37.1  
105.4 104.4 112.1 84.5 117.6 60.0 100.3 100.3 107.4 84.0 114.7 59.4 93.4 93.4 100.9 81.6 110.0 57.9 86.1 86.1 91.7 77.7 104.8 55.6  
111.0 111.0 113.3 101.2 118.9 74.2 107.0 107.0 108.9 101.7 116.0 74.8 101.8 101.8 101.8 101.8 111.2 73.8 94.9 94.9 94.9 94.9 105.3 72.9  
115.2 115.2 115.2 115.2 120.3 88.6 112.1 112.1 112.1 111.1 116.5 89.3 107.8 107.8 107.7 107.7 112.1 90.2 102.6 102.6 102.6 102.6 106.4 90.0  
103.5 96.3 112.1 69.5 116.6 43.8 94.9 94.9 107.9 68.7 114.0 42.5 87.5 87.5 101.8 65.6 110.0 40.3 80.7 79.5 92.4 61.7 104.8 37.8  
107.9 107.9 113.0 87.1 118.1 60.8 103.1 103.1 108.6 87.3 115.3 60.3 96.8 96.8 102.5 85.6 110.7 59.5 89.1 89.1 93.7 82.0 105.4 57.5  
112.9 112.9 114.4 104.5 119.5 75.5 109.3 109.3 110.4 105.7 116.7 76.5 104.5 104.5 104.5 104.5 111.9 76.7 98.2 98.2 98.6 96.7 106.2 75.5  
116.7 116.7 116.7 116.7 120.9 90.6 113.9 113.9 113.8 113.8 117.9 92.9 109.9 109.9 109.8 109.8 113.0 93.2 104.9 104.9 104.9 104.9 107.5 93.5  
75  
80  
85  
3060  
90  
75  
80  
3400  
85  
90  
75  
80  
3740  
85  
90  
75  
80  
4080  
85  
90  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.  
2. TGC = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
RT-PRC017-EN  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-5 - Gross Cooling Capacities (kW) -YSC120AD - (SI)  
Ambient Temperature (C)  
Enter.  
Dry  
Bulb  
30  
35  
40  
19  
45  
19  
Entering Wet Bulb Temperature (C)  
19 22 16  
m3/h  
Temp  
16  
19  
22  
16  
22  
16  
22  
Airflow (C)  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
31.9 28.6 35.3 22.8 37.2 15.9 29.6 27.4 33.6 21.7 36.5 15.4 27.1 26.2 31.0 20.5 35.2 14.8 24.6 24.6 28.4 19.9 33.2 14.0  
33.4 33.4 35.5 28.2 37.7 21.4 31.6 31.6 33.9 27.8 36.7 21.4 29.5 29.5 31.3 26.6 35.3 20.7 27.5 27.5 28.9 25.5 33.3 19.9  
35.5 35.5 36.0 33.8 38.1 26.5 34.2 34.2 34.5 33.8 37.0 26.7 32.3 32.3 32.2 32.2 35.5 26.6 30.4 30.4 30.4 30.4 33.4 25.9  
37.1 37.1 37.1 37.1 38.5 31.6 36.2 36.2 36.2 36.2 37.3 31.9 34.8 34.8 34.8 34.8 35.9 32.3 33.2 33.2 33.2 33.2 34.0 31.8  
32.7 30.4 35.7 23.8 37.5 16.3 30.5 29.3 34.2 22.8 36.8 15.9 27.8 27.8 31.9 21.8 35.5 15.3 25.7 25.7 29.0 21.2 33.7 14.5  
34.5 34.5 36.0 29.5 38.0 21.9 32.9 32.9 34.5 29.4 37.0 22.0 30.9 30.9 32.3 28.5 35.7 21.7 28.7 28.7 29.7 27.4 33.8 21.0  
36.3 36.3 36.6 35.4 38.4 27.4 35.3 35.3 35.3 35.3 37.3 27.6 33.7 33.7 33.7 33.7 35.9 27.8 31.8 31.8 31.7 31.7 34.0 27.5  
37.9 37.9 37.8 37.8 38.9 32.8 37.0 37.0 37.0 37.0 37.8 33.3 35.9 35.9 35.9 35.9 36.5 33.9 34.4 34.4 34.4 34.4 34.7 33.8  
33.5 32.2 36.0 24.7 37.8 16.9 31.1 31.1 34.7 23.9 37.0 16.3 28.9 28.9 32.4 22.9 35.8 15.7 26.6 26.6 29.6 22.5 34.1 14.9  
35.3 35.3 36.4 30.6 38.2 22.4 34.0 34.0 35.0 30.8 37.4 22.7 32.0 32.0 33.0 30.2 36.0 22.5 29.9 29.9 30.5 29.1 34.2 22.0  
37.0 37.0 37.0 37.0 38.7 28.1 36.1 36.1 36.1 36.1 37.9 28.9 34.7 34.7 34.7 34.7 36.4 29.1 32.9 32.9 32.9 32.9 34.5 29.0  
38.4 38.4 38.3 38.3 39.2 33.7 37.7 37.7 37.7 37.7 38.4 34.9 36.7 36.7 36.7 36.7 37.0 35.4 35.3 35.3 35.3 35.3 35.3 35.3  
33.9 33.9 36.3 24.9 37.9 17.3 32.0 32.0 35.0 25.6 37.5 16.1 29.8 29.8 32.8 23.9 36.1 16.2 27.5 27.5 29.8 23.6 34.4 15.3  
35.9 35.9 36.7 31.7 38.5 22.8 34.8 34.8 35.5 32.2 37.7 23.2 32.9 32.9 33.6 31.9 36.3 23.2 30.6 30.6 30.6 30.6 34.5 23.0  
37.5 37.5 37.5 37.5 38.9 28.8 36.7 36.7 36.7 36.7 38.1 29.8 35.5 35.5 35.5 35.5 36.7 30.2 33.7 33.7 33.7 33.7 34.9 30.5  
38.8 38.8 38.7 38.7 39.5 34.6 38.4 38.4 38.2 38.2 38.7 36.1 37.3 37.3 37.3 37.3 37.4 36.7 36.0 36.0 36.0 36.0 36.0 36.0  
24  
27  
30  
6120  
33  
24  
27  
6800  
30  
33  
24  
27  
7480  
30  
33  
24  
27  
8160  
30  
33  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.  
2. TGC = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
Table PD-5a - Gross Cooling Capacities (MBH) -YSC120AD - (IP)  
Ambient Temperature (F)  
Enter.  
Dry  
Bulb  
85  
95  
105  
67  
115  
67  
Entering Wet Bulb Temperature (F)  
67  
CFM  
Temp  
61  
67  
73  
61  
73  
61  
73  
61  
73  
Airflow (F)  
TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC  
109.9 96.4 122.1 73.8 128.5 47.6 101.2 92.1 116.7 70.3 125.9 45.7 91.8 87.5 107.7 67.7 121.6 43.4 82.1 82.1 97.2 63.2 115.0 40.9  
113.5 113.5 122.6 90.4 129.9 65.7 106.6 106.6 117.1 89.2 127.2 65.0 99.0 99.0 108.4 85.4 122.2 62.4 91.0 91.0 98.2 81.0 115.2 59.7  
120.2 120.2 123.8 108.0 131.3 80.9 115.2 115.2 118.5 107.9 127.8 81.5 108.1 108.1 110.5 104.9 122.6 80.6 100.3 100.3 100.3 100.3 115.4 78.4  
125.4 125.4 125.4 125.4 132.7 96.3 121.8 121.8 121.8 121.8 128.7 97.3 116.4 116.4 116.4 116.4 123.6 98.2 109.2 109.2 109.2 109.2 116.4 97.0  
112.7 102.4 123.1 75.6 129.3 48.4 104.2 98.3 118.5 73.6 126.9 46.6 93.7 93.7 109.9 70.9 122.7 44.3 85.6 85.6 99.3 67.2 116.5 41.9  
117.3 117.3 124.1 94.1 130.8 66.9 111.1 111.1 119.0 94.0 128.2 66.8 103.5 103.5 110.8 90.8 123.5 65.3 95.2 95.2 100.8 86.6 116.8 62.5  
123.2 123.2 125.6 112.8 132.3 82.9 119.0 119.0 120.8 114.1 129.5 84.5 112.5 112.5 112.5 112.5 124.1 84.2 104.9 104.9 104.8 104.8 117.1 83.0  
127.9 127.9 127.9 127.9 133.8 99.2 124.9 124.9 124.9 124.9 130.8 102.4 120.2 120.2 120.2 120.2 125.3 103.1 113.9 113.9 113.8 113.8 118.4 102.9  
115.1 108.2 124.5 77.5 130.0 49.2 107.0 104.4 119.8 77.6 127.6 47.4 97.3 97.3 111.7 73.2 123.6 45.2 88.7 88.7 101.1 71.1 117.6 42.7  
120.1 120.1 125.3 97.3 131.6 67.9 114.9 114.9 120.6 98.4 129.0 68.2 107.3 107.3 112.9 96.1 124.5 68.1 98.9 98.9 103.1 92.0 118.0 65.1  
125.5 125.5 127.0 116.9 133.1 84.7 121.9 121.9 122.8 119.6 130.5 87.0 116.4 116.4 116.3 116.3 125.3 88.0 108.7 108.7 108.7 108.7 118.4 87.0  
130.0 130.0 129.7 129.7 134.7 101.8 127.3 127.3 127.2 127.2 131.9 105.9 123.0 123.0 123.0 123.0 126.7 107.5 117.2 117.2 117.2 117.2 120.2 108.4  
117.1 113.2 125.5 81.7 130.6 50.0 108.8 108.8 120.8 80.6 128.3 48.2 100.5 100.5 113.2 76.3 124.3 46.1 91.6 91.6 102.7 72.1 118.5 43.6  
122.3 122.3 126.5 100.7 132.2 68.9 117.8 117.8 122.0 102.4 129.8 69.5 110.5 110.5 114.9 101.3 125.7 69.3 102.2 102.2 105.2 97.3 119.0 67.7  
127.2 127.2 128.4 121.1 133.8 86.3 124.1 124.1 124.1 124.1 131.2 89.2 119.0 119.0 119.0 119.0 126.5 90.9 112.0 112.0 112.0 112.0 119.7 90.9  
131.3 131.3 131.5 131.5 135.4 104.2 129.3 129.3 129.0 129.0 132.8 108.9 125.2 125.2 125.2 125.2 127.8 111.4 119.8 119.8 119.8 119.8 121.7 113.3  
75  
80  
85  
3600  
90  
75  
80  
4000  
85  
90  
75  
80  
4400  
85  
90  
75  
80  
4800  
85  
90  
Notes:  
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.  
2. TGC = Total Gross Capacity  
3. SHC = Sensible Heat Capacity  
18  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-6 - Belt Drive Evaporator Fan Performance -YSC060AD*L - Low Heat - Downflow Configuration - (SI)  
External Static Pressure (Pascals)  
25  
50  
75  
100  
RPM  
1.12 Nom kW Standard Motor & Low Static Drive  
125  
RPM  
150  
RPM  
175  
RPM  
200  
RPM  
225  
RPM kW  
250  
RPM kW  
m3/h  
RPM  
kW  
RPM  
kW  
RPM  
kW  
kW  
kW  
kW  
kW  
kW  
1.12 Nom kW Std Mtr & Drive  
0.55 1031 0.60 1067 0.65 1101 0.70  
2720  
3060  
3400  
3740  
4080  
716  
791  
867  
944  
0.28  
0.38  
0.51  
0.66  
768  
840  
914  
989  
0.32  
0.43  
0.56  
0.73  
816  
884  
955  
0.36  
0.47  
0.61  
863  
927  
994  
1063 0.84  
1135 1.04  
0.39  
0.51  
0.66  
909  
969  
1033 0.71  
1099 0.89  
1168 1.10  
0.44  
0.56  
953  
0.50  
993  
1010 0.61  
1070 0.76  
1134 0.94  
1200 1.16  
1049 0.67 1087 0.73 1122 0.79 1156 0.85  
1107 0.82 1143 0.88 1178 0.95 1212 1.02  
1168 0.99 1202 1.05 1235 1.12 1267 1.19  
1027 0.78  
1101 0.98  
1022 0.85  
1064 0.92  
1233 1.22  
-
-
-
-
-
-
External Static Pressure (Pascals)  
300 325  
RPM RPM  
1.12 Nom kW Standard Motor & Drive  
275  
RPM  
350  
RPM  
375  
RPM  
m3/h  
kW  
kW  
kW  
kW  
kW  
2720  
3060  
3400  
3740  
4080  
1135 0.75  
1188 0.90  
1244 1.08  
1300 1.27  
1166 0.80  
1218 0.96  
1273 1.14  
1198 0.85  
1249 1.01  
1303 1.20  
1228 0.91  
1279 1.07  
1332 1.27  
1258 0.96  
1307 1.13  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
TestedTo Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
Notes:  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132  
Table PD-6a - Belt Drive Evaporator Fan Performance -YSC060AD*L - Low Heat - Downflow Configuration - (IP)  
External Static Pressure (Inches of Water)  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
1.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
1-1/2 HP Standard Motor & Low Static Drive  
1-1/2 HP Std Motor & Drive  
1600  
1800  
2000  
2200  
2400  
716  
791  
867  
944  
0.37  
0.51  
0.68  
0.89  
768  
840  
914  
989  
0.43  
0.57  
0.76  
0.97  
816  
884  
955  
1027 1.05  
1101 1.32  
0.48  
0.63  
0.82  
863  
927  
994  
1063 1.12  
1135 1.40  
0.53  
0.69  
0.89  
909  
969  
1033 0.95  
1099 1.19  
1168 1.48  
0.60  
0.75  
953  
0.67  
993  
0.74 1031 0.81 1067 0.87 1101 0.94  
1010 0.82  
1070 1.02  
1134 1.26  
1200 1.55  
1049 0.90 1087 0.99 1122 1.06 1156 1.14  
1107 1.10 1143 1.18 1178 1.27 1212 1.36  
1168 1.33 1202 1.41 1235 1.51 1267 1.60  
1022 1.14  
1064 1.23  
1233 1.63  
-
-
-
-
-
-
External Static Pressure (Inches of Water)  
1.10  
1.20  
1.30  
1.40  
1.50  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
1-1/2 HP Standard Motor & Drive  
1600  
1800  
2000  
2200  
2400  
1135 1.01  
1188 1.21  
1244 1.45  
1300 1.70  
1166 1.07  
1218 1.28  
1273 1.53  
1198 1.14  
1249 1.36  
1303 1.61  
1228 1.22  
1279 1.44  
1332 1.70  
1258 1.29  
1307 1.51  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
Tested To Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451  
RT-PRC017-EN  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-7 - Belt Drive Evaporator Fan Performance - YSC060AD*L - Horizontal Configuration (SI)  
External Static Pressure (Pascals)  
25  
50  
75  
100  
RPM  
1.12 Nom kW Std Motor & Low Static Drive  
125  
RPM  
150  
RPM  
175  
RPM  
200  
RPM  
225  
RPM kW  
250  
RPM kW  
m3/h  
RPM  
kW  
RPM  
kW  
RPM  
kW  
kW  
kW  
kW  
kW  
kW  
1.12 Nom kW Standard Motor & Drive  
2720  
3060  
3400  
3740  
4080  
788  
871  
956  
1042 0.78  
1129 1.00  
0.33  
0.45  
0.60  
850  
927  
1006 0.67  
1088 0.85  
1171 1.08  
0.38  
0.51  
911  
983  
1057 0.74  
1133 0.93  
1213 1.16  
0.44  
0.57  
964  
0.49  
1011 0.55  
1082 0.70  
1153 0.88  
1224 1.09  
1296 1.33  
1055 0.61  
1124 0.76  
1195 0.95  
1266 1.16  
1097 0.66 1137 0.72 1176 0.78 1213 0.84  
1164 0.83 1201 0.89 1239 0.95 1275 1.02  
1233 1.02 1270 1.09 1305 1.16 1339 1.23  
1035 0.64  
1106 0.81  
1179 1.01  
1255 1.25  
1305 1.24 1340 1.32  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
External Static Pressure (Pascals)  
300 325 350  
kW RPM RPM  
1.12 Nom kW Standard Motor & Drive  
275  
375  
RPM  
m3/h  
RPM  
kW  
RPM  
kW  
kW  
kW  
2720  
3060  
3400  
3740  
4080  
1248 0.91  
1310 1.09  
1373 1.30  
1282 0.97  
1344 1.16  
1314 1.04  
1344 1.11  
1374 1.18  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
TestedTo Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132  
Table PD-7a - Belt Drive Evaporator Fan Performance -YSC060AD*L - Horizontal Configuration - (IP)  
External Static Pressure (Inches of Water)  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
1.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
1-1/2 HP Standard Motor & Low Static Drive  
1-1/2 HP Standard Motor & Drive  
1600  
1800  
2000  
2200  
2400  
788  
871  
956  
1042 1.05  
1129 1.34  
0.44  
0.60  
0.80  
850  
927  
1006 0.89  
1088 1.15  
1171 1.45  
0.51  
0.68  
911  
983  
1057 0.99  
1133 1.25  
1213 1.56  
0.59  
0.77  
964  
0.66  
1011 0.74  
1082 0.94  
1153 1.18  
1224 1.46  
1296 1.78  
1055 0.81  
1097 0.89 1137 0.97 1176 1.05 1213 1.13  
1164 1.11 1201 1.19 1239 1.28 1275 1.37  
1233 1.36 1270 1.46 1305 1.55 1339 1.65  
1035 0.85  
1106 1.08  
1179 1.35  
1255 1.67  
1124 1.02  
1195 1.27  
1266 1.56  
1305 1.66 1340 1.77 1375  
-
-
-
-
-
-
-
-
-
-
-
-
-
External Static Pressure (Inches of Water)  
1.10  
1.20  
1.30  
1.40  
1.50  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
1-1/2 HP Standard Motor & Drive  
1600  
1800  
2000  
2200  
2400  
1248 1.21  
1310 1.46  
1373 1.75  
1282 1.30  
1344 1.55  
1314 1.39  
1344 1.48  
1374 1.58  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
TestedTo Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451  
20  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-8 - Belt Drive Evaporator Fan Performance -YSC060AD*H - High Heat - Downflow Configuration - (SI)  
External Static Pressure (Pascals)  
25  
50  
75  
100  
RPM  
1.12 Nom kW Standard Motor & Low Static Drive  
125  
RPM  
150  
RPM  
175  
RPM  
200  
RPM  
1.12 Nom kW Std Mtr & Drive  
225  
RPM kW  
250  
RPM kW  
m3/h  
RPM  
kW  
RPM  
kW  
RPM  
kW  
kW  
kW  
kW  
kW  
kW  
2720  
3060  
3400  
3740  
4080  
734  
813  
894  
974  
0.29  
0.40  
0.54  
0.70  
784  
859  
936  
1014 0.76  
1093 0.97  
0.33  
0.45  
0.59  
833  
903  
976  
1051 0.82  
1127 1.03  
0.37  
0.49  
0.64  
879  
945  
1014 0.69  
1087 0.87  
1160 1.09  
0.41  
0.53  
924  
987  
1052 0.73  
1122 0.92  
1193 1.15  
0.46  
0.58  
967  
0.52  
1007 0.57 1043 0.62 1078 0.67 1113 0.72  
1066 0.70 1103 0.76 1137 0.82 1169 0.87  
1126 0.85 1162 0.92 1196 0.98 1229 1.05  
1190 1.03 1224 1.10 1257 1.17 1288 1.24  
1027 0.64  
1089 0.79  
1156 0.98  
1225 1.20  
1055 0.90  
1256 1.26 1288 1.32  
-
-
-
-
External Static Pressure (Pascals)  
300 325 350  
kW RPM RPM  
1.12 Nom kW Standard Motor & Drive  
275  
kW  
375  
RPM  
m3/h  
RPM  
RPM  
kW  
kW  
kW  
2720  
3060  
3400  
3740  
4080  
1145 0.77  
1202 0.93  
1260 1.11  
1320 1.32  
1177 0.82  
1232 0.98  
1289 1.17  
1208 0.87  
1262 1.04  
1319 1.24  
1238 0.93  
1290 1.09  
1347 1.30  
1268 0.98  
1319 1.15  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
Tested To Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132  
Table PD-8a - Belt Drive Evaporator Fan Performance -YSC060AD*H - High Heat - Downflow Configuration - (IP)  
External Static Pressure (Inches of Water)  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
1.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
1-1/2 HP Standard Motor & Low Static Drive  
1-1/2 HP Std Motor & Drive  
1600  
1800  
2000  
2200  
2400  
734  
813  
894  
974  
0.39  
0.54  
0.72  
0.94  
784  
859  
936  
1014 1.02  
1093 1.30  
0.44  
0.60  
0.79  
833  
903  
976  
1051 1.10  
1127 1.38  
0.49  
0.66  
0.86  
879  
945  
1014 0.92  
1087 1.17  
1160 1.46  
0.55  
0.72  
924  
987  
1052 0.98  
1122 1.24  
1193 1.54  
0.62  
0.78  
967  
0.69  
1007 0.76 1043 0.83 1078 0.89 1113 0.96  
1066 0.94 1103 1.02 1137 1.09 1169 1.17  
1126 1.14 1162 1.23 1196 1.32 1229 1.41  
1190 1.38 1224 1.47 1257 1.57 1288 1.67  
1027 0.86  
1089 1.06  
1156 1.31  
1225 1.61  
1055 1.21  
1256 1.69 1288 1.77  
-
-
-
-
External Static Pressure (Inches of Water)  
1.10  
1.20  
1.30  
1.40  
1.50  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
1-1/2 HP Standard Motor & Drive  
1600  
1800  
2000  
2200  
2400  
1145 1.03  
1202 1.24  
1260 1.49  
1320 1.77  
1177 1.10  
1232 1.32  
1289 1.57  
1208 1.17  
1262 1.39  
1319 1.66  
1238 1.24  
1290 1.47  
1347 1.74  
1268 1.31  
1319 1.55  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
Tested To Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451  
RT-PRC017-EN  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-9 - Belt Drive Evaporator Fan Performance -YSC060AD*H - High Heat - Horizontal Configuration (SI)  
External Static Pressure (Pascals)  
25  
50  
75  
100  
RPM  
1.12 Nom kW Std Motor & Low Static Drive  
125  
RPM  
150  
RPM  
175  
RPM  
200  
RPM  
225  
RPM kW  
250  
RPM kW  
m3/h  
RPM  
kW  
RPM  
kW  
RPM  
kW  
kW  
kW  
kW  
kW  
kW  
1.12 Nom kW Standard Motor & Drive  
2720  
3060  
3400  
3740  
4080  
809  
895  
983  
1072 0.83  
1161 1.06  
0.34  
0.47  
0.63  
871  
951  
1033 0.70  
1117 0.90  
1203 1.14  
0.40  
0.54  
930  
0.46  
980  
0.51  
1026 0.57  
1100 0.73  
1176 0.91  
1251 1.14  
1069 0.63  
1141 0.79  
1216 0.98  
1292 1.21  
1111 0.68 1151 0.74 1189 0.80 1225 0.87  
1180 0.85 1218 0.92 1255 0.98 1290 1.05  
1253 1.05 1289 1.13 1323 1.20 1357 1.27  
1006 0.60  
1083 0.77  
1163 0.98  
1245 1.23  
1056 0.66  
1131 0.84  
1209 1.06  
1287 1.31  
1329 1.29  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
External Static Pressure (Pascals)  
300 325 350  
kW RPM RPM  
1.12 Nom kW Standard Motor & Drive  
275  
kW  
375  
RPM  
m3/h  
RPM  
RPM  
kW  
kW  
kW  
2720  
3060  
3400  
3740  
4080  
1260 0.93  
1324 1.12  
1293 0.99  
1357 1.19  
1324 1.06  
1390 1.26  
1355 1.13  
1383 1.20  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
TestedTo Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132  
Table PD-9a - Belt Drive Evaporator Fan Performance -YSC060AD*H - High Heat - Horizontal Configuration - (IP)  
External Static Pressure (Inches of Water)  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
1.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
1-1/2 HP Standard Motor & Low Static Drive  
1-1/2 HP Standard Motor & Drive  
1600  
1800  
2000  
2200  
2400  
809  
895  
983  
1072 1.11  
1161 1.42  
0.46  
0.64  
0.85  
871  
951  
1033 0.94  
1117 1.21  
1203 1.53  
0.54  
0.72  
930  
0.61  
980  
0.69  
1026 0.76  
1100 0.97  
1176 1.23  
1251 1.52  
1069 0.84  
1141 1.06  
1216 1.32  
1292 1.63  
1111 0.92 1151 1.00 1189 1.08 1225 1.16  
1180 1.14 1218 1.23 1255 1.32 1290 1.41  
1253 1.41 1289 1.51 1323 1.60 1357 1.70  
1006 0.81  
1083 1.04  
1163 1.32  
1245 1.64  
1056 0.89  
1131 1.13  
1209 1.42  
1287 1.76  
1329 1.73  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
External Static Pressure (Inches of Water)  
1.20 1.30 1.40  
BHP RPM  
1.10  
1.50  
CFM RPM BHP RPM BHP RPM BHP RPM  
BHP  
1-1/2 HP Standard Motor & Drive  
1600  
1800  
2000  
2200  
2400  
1260 1.24  
1324 1.50  
1293 1.33  
1357 1.59  
1324 1.42  
1390 1.69  
1355 1.52  
1383 1.60  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Notes:  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
TestedTo Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
22  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-10 - Belt Drive Evaporator Fan Performance -YSC072AD*L - Low Heat - Downflow Configuration - (SI)  
External Static Pressure (Pascals)  
25  
50  
75  
100  
RPM  
1.12 Nom kW Standard Motor & Low Static Drive  
125  
RPM  
150  
RPM  
175  
RPM  
200  
RPM  
225  
RPM kW  
250  
RPM kW  
m3/h  
RPM  
kW  
RPM  
kW  
RPM  
kW  
kW  
kW  
kW  
kW  
kW  
1.12 Nom kW Standard Motor & Drive  
3260  
3670  
4080  
4490  
4890  
-
-
-
-
532  
570  
610  
652  
694  
0.22  
0.28  
0.36  
0.45  
0.57  
592  
624  
659  
698  
737  
0.27  
0.33  
0.41  
0.51  
0.62  
646  
677  
707  
741  
778  
0.32  
0.39  
0.48  
0.58  
0.69  
695  
725  
755  
786  
818  
0.37  
0.45  
0.55  
0.65  
0.77  
740  
768  
798  
828  
859  
0.43  
0.51  
0.61  
0.72  
0.85  
783  
809  
838  
868  
898  
0.48  
0.57  
0.67  
0.79  
0.93  
824  
848  
876  
905  
936  
0.54  
0.63  
0.74  
0.86  
1.00  
864 0.61  
886 0.70  
912 0.81  
939 0.93  
901 0.67  
923 0.77  
947 0.88  
973 1.01  
556  
601  
646  
0.30  
0.39  
0.49  
970 1.08 1003 1.16  
1.12 Nom kW Standard Motor  
& Hi Static Drive  
External Static Pressure (Pascals)  
300 325 350  
RPM RPM  
275  
RPM  
375  
RPM  
CFM  
kW  
RPM  
kW  
kW  
kW  
kW  
1.12 Nom kW Std Motor  
& Drive  
1.12 Nom kW Standard Motor  
& Hi Static Drive  
3260  
3670  
4080  
4490  
4890  
937  
957  
981  
1007 1.08  
1034 1.24  
0.73  
0.83  
0.95  
970  
992  
1014 1.02  
1038 1.16  
1066 1.32  
0.79  
0.90  
1004 0.85  
1024 0.97  
1046 1.10  
1070 1.24  
1095 1.40  
1036 0.91  
1057 1.04  
1077 1.18  
1100 1.32  
1124 1.48  
1067 0.97  
1086 1.11  
1108 1.25  
1130 1.40  
1154 1.57  
1.50 Nom kW Over-Sized Motor  
& High Static Drive  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
Tested To Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
Notes:  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132  
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464  
Table PD-10a - Belt Drive Evaporator Fan Performance -YSC072AD*L - Low Heat - Downflow Configuration - (IP)  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
1-1/2 HP Standard Motor & Low Static Drive  
1-1/2 HP Standard Motor & Drive  
1920  
2160  
2400  
2640  
2880  
-
-
-
-
532  
570  
610  
652  
694  
0.29  
0.37  
0.48  
0.61  
0.76  
592  
624  
659  
698  
737  
0.36  
0.45  
0.56  
0.69  
0.84  
646  
677  
707  
741  
778  
0.43  
0.53  
0.64  
0.77  
0.93  
695  
725  
755  
786  
818  
0.50  
0.61  
0.73  
0.87  
1.03  
740  
768  
798  
828  
859  
0.57  
0.68  
0.82  
0.97  
1.13  
783  
809  
838  
868  
898  
0.65  
0.76  
0.90  
1.06  
1.24  
824  
848  
876  
905  
936  
0.73  
0.85  
0.99  
1.16  
1.35  
864 0.81  
886 0.94  
912 1.08  
939 1.25  
901 0.89  
923 1.03  
947 1.18  
973 1.35  
556  
601  
646  
0.41  
0.52  
0.66  
970 1.45 1003 1.55  
1-1/2 HP Standard Motor  
& Hi Static Drive  
External Static Pressure (Inches of Water)  
1.10  
RPM BHP  
1.20  
1.30  
RPM BHP  
1.40  
RPM BHP  
1.50  
RPM BHP  
CFM  
RPM BHP  
1-1/2 HP Std Mtr  
& Drive  
1-1/2 HP Standard Motor &  
Hi Static Drive  
1920  
2160  
2400  
2640  
2880  
937  
957  
981  
1007 1.45  
1034 1.66  
0.98  
1.12  
1.27  
970  
992  
1014 1.37  
1038 1.56  
1066 1.77  
1.05  
1.21  
1004 1.13  
1024 1.30  
1046 1.48  
1070 1.66  
1095 1.87  
1036 1.22  
1057 1.40  
1077 1.58  
1100 1.77  
1124 1.99  
1067 1.30  
1086 1.48  
1108 1.68  
1130 1.88  
1154 2.11  
2 HP Over-Sized Motor & Hi Static Drive  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
Tested To Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
Notes:  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451  
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500  
RT-PRC017-EN  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-11 - Belt Drive Evaporator Fan Performance - YSC072AD*L - Horizontal Configuration (SI)  
External Static Pressure (Pascals)  
25  
50  
75  
100  
RPM  
125  
RPM  
150  
RPM  
1.12 Nom kW Standard Motor & Drive  
175  
RPM  
200  
RPM  
225  
RPM kW  
250  
RPM kW  
m3/h  
RPM  
kW  
RPM  
kW  
RPM  
kW  
kW  
kW  
kW  
kW  
kW  
1.12 Nom kW Std Mtr &  
Low Static Drive  
3260  
3670  
4080  
4490  
4890  
-
-
586  
629  
679  
732  
786  
0.25  
0.33  
0.43  
0.54  
0.68  
645  
685  
726  
770  
818  
0.31  
0.38  
0.48  
0.60  
0.74  
695  
735  
775  
816  
858  
0.35  
0.45  
0.55  
0.66  
0.81  
741  
779  
819  
860  
900  
0.41  
0.50  
0.62  
0.74  
0.88  
785  
820  
858  
899  
940  
0.47  
0.56  
0.68  
0.82  
0.97  
828  
860  
896  
935  
977  
0.53  
0.63  
0.74  
0.88  
870  
898  
932  
970  
0.59  
0.70  
0.81  
913 0.66  
937 0.77  
967 0.89 1002 0.97  
952 0.72  
976 0.84  
584  
640  
696  
752  
0.28  
0.38  
0.49  
0.62  
0.95 1004 1.03 1036 1.11  
1.05 1010 1.13 1042 1.20 1072 1.27  
1.12 Nom kW Standard Motor & Drive  
1.12 Nom kW Standard Motor & Hi Static Drive  
External Static Pressure (Pascals)  
275  
RPM  
300  
RPM  
1.12 Nom kW Standard Motor & Hi Static Drive  
325  
RPM  
350  
RPM  
375  
RPM  
CFM  
kW  
kW  
kW  
kW  
kW  
3260  
3670  
4080  
4490  
4890  
990  
0.78  
1027 0.85  
1048 0.98  
1072 1.12  
1100 1.28  
1134 1.45  
1063 0.92  
1082 1.05  
1106 1.20  
1132 1.36  
1163 1.54  
1096 0.99  
1117 1.12  
1139 1.27  
1164 1.45  
1191 1.63  
1129 1.06  
1149 1.20  
1169 1.35  
1194 1.53  
1221 1.72  
1012 0.90  
1038 1.04  
1067 1.19  
1103 1.36  
1.50 Nom kW Over-Sized Motor & Hi Static Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
Tested To Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132  
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464  
Table PD-11a - Belt Drive Evaporator Fan Performance - YSC072AD*L - Horizontal Configuration - (IP)  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
1-1/2 HP Standard Motor & Low Static Drive  
1-1/2 HP Standard Motor & Drive  
1920  
2160  
2400  
2640  
2880  
-
-
586  
629  
679  
732  
786  
0.33  
0.44  
0.57  
0.73  
0.92  
645  
685  
726  
770  
818  
0.41  
0.52  
0.64  
0.80  
0.99  
695  
735  
775  
816  
858  
0.48  
0.60  
0.74  
0.89  
1.08  
741  
779  
819  
860  
900  
0.55  
0.67  
0.83  
1.00  
1.18  
785  
820  
858  
899  
940  
0.63  
0.75  
0.91  
1.10  
1.30  
828  
860  
896  
935  
977  
0.71  
0.84  
0.99  
1.19  
870  
898  
932  
970  
0.79  
0.94  
1.09  
913 0.88  
937 1.03  
967 1.19 1002 1.29  
952 0.96  
976 1.12  
584  
640  
696  
752  
0.38  
0.50  
0.65  
0.83  
1.28 1004 1.38 1036 1.49  
1.41 1010 1.51 1042 1.60 1072 1.70  
1-1/2 HP Standard Motor & Drive  
1-1/2 HP Std Motor & Hi Static Drive  
External Static Pressure (Inches of Water)  
1.10  
RPM BHP  
1.20  
1.30  
RPM BHP  
1.40  
RPM BHP  
1.50  
RPM BHP  
CFM  
RPM BHP  
1-1/2 HP Standard Motor & Hi Static Drive  
1920  
2160  
2400  
2640  
2880  
990  
1.05  
1027 1.14  
1048 1.31  
1072 1.50  
1100 1.71  
1134 1.94  
1063 1.24  
1082 1.40  
1106 1.60  
1132 1.83  
1163 2.07  
1096 1.33  
1117 1.50  
1139 1.71  
1164 1.94  
1191 2.19  
1129 1.42  
1149 1.61  
1169 1.81  
1194 2.05  
1221 2.31  
1012 1.21  
1038 1.40  
1067 1.60  
1103 1.82  
2 HP Over-Sized Motor & Hi Static Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
Tested To Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451  
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500  
24  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-12 - Belt Drive Evaporator Fan Performance -YSC072AD*H - High Heat - Downflow Configuration - (SI)  
External Static Pressure (Pascals)  
25  
50  
75  
100  
RPM  
1.12 Nom kW Standard Motor & Low Static Drive  
125  
RPM  
150  
RPM  
175  
RPM  
200  
RPM  
225  
RPM kW  
250  
RPM kW  
m3/h  
RPM  
kW  
RPM  
kW  
RPM  
kW  
kW  
kW  
kW  
kW  
kW  
1.12Nom kW Standard Motor & Drive  
3260  
3670  
4080  
4490  
4890  
-
-
586  
631  
678  
728  
779  
0.26  
0.34  
0.44  
0.56  
0.69  
641  
684  
727  
772  
818  
0.31  
0.40  
0.50  
0.63  
0.77  
690  
731  
773  
815  
860  
0.37  
0.46  
0.57  
0.70  
0.85  
735  
773  
814  
857  
899  
0.42  
0.52  
0.64  
0.77  
0.93  
779  
814  
853  
894  
936  
0.48  
0.58  
0.70  
0.84  
1.01  
820  
854  
890  
929  
970  
0.54  
0.64  
0.77  
0.91  
859  
891  
926  
963  
0.60  
0.71  
0.84  
0.98  
896 0.66  
928 0.78  
961 0.91  
932 0.72  
963 0.84  
994 0.98  
577  
630  
684  
738  
0.29  
0.38  
0.49  
0.63  
996 1.06 1028 1.14  
1.08 1003 1.16 1035 1.24 1066 1.32  
1.50 Nom kW Over-Sized Motor  
& High Static Drive  
External Static Pressure (Pascals)  
300 325 350  
RPM RPM  
275  
RPM  
375  
RPM  
CFM  
kW  
RPM  
kW  
kW  
kW  
kW  
1.12 Nom kW Std Motor  
& Drive  
1.12 Nom kW Std Mtr  
& Hi Static Drive  
3260  
3670  
4080  
4490  
4890  
968  
996  
1027 1.05  
1060 1.22  
1096 1.40  
0.78  
0.91  
1000 0.84  
1028 0.98  
1058 1.13  
1090 1.29  
1125 1.48  
1033 0.90  
1061 1.05  
1090 1.21  
1120 1.38  
1155 1.57  
1063 0.96  
1091 1.12  
1118 1.28  
1150 1.46  
1181 1.66  
1094 1.03  
1121 1.18  
1149 1.36  
1178 1.54  
1210 1.75  
1.50 Nom kW Over-Sized Motor & High Static Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
Tested To Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132  
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464  
Table PD-12a - Belt Drive Evaporator Fan Performance -YSC072AD*H - High Heat - Downflow Configuration - (IP)  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
1-1/2 HP Standard Motor & Low Static Drive  
1-1/2 HP Standard Motor & Drive  
1920  
2160  
2400  
2640  
2880  
-
-
586  
631  
678  
728  
779  
0.35  
0.46  
0.59  
0.75  
0.93  
641  
684  
727  
772  
818  
0.42  
0.54  
0.68  
0.84  
1.03  
690  
731  
773  
815  
860  
0.49  
0.62  
0.77  
0.94  
1.14  
735  
773  
814  
857  
899  
0.56  
0.69  
0.85  
1.04  
1.24  
779  
814  
853  
894  
936  
0.64  
0.78  
0.94  
1.13  
1.35  
820  
854  
890  
929  
970  
0.72  
0.86  
1.03  
1.22  
859  
891  
926  
963  
0.80  
0.95  
1.12  
1.32  
896 0.88  
928 1.04  
961 1.22  
932 0.96  
963 1.13  
994 1.31  
577  
630  
684  
738  
0.38  
0.51  
0.66  
0.84  
996 1.42 1028 1.52  
1.45 1003 1.56 1035 1.66 1066 1.77  
2 HP Over-Sized Motor  
& Hi Static Drive  
External Static Pressure (Inches of Water)  
1.10  
RPM BHP  
1.20  
1.30  
RPM BHP  
1.40  
RPM BHP  
1.50  
RPM BHP  
CFM  
RPM BHP  
1-1/2 HP Std Mtr  
1-1/2 HP Std Motor &  
Hi Static Drive  
& Drive  
1920  
2160  
2400  
2640  
2880  
968  
996  
1027 1.41  
1060 1.63  
1096 1.88  
1.05  
1.22  
1000 1.13  
1028 1.31  
1058 1.51  
1090 1.74  
1125 1.99  
1033 1.21  
1061 1.41  
1090 1.62  
1120 1.85  
1155 2.11  
1063 1.29  
1091 1.50  
1118 1.72  
1150 1.96  
1181 2.22  
1094 1.38  
1121 1.59  
1149 1.82  
1178 2.07  
1210 2.34  
2 HP Over-Sized Motor & Hi Static Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
Tested To Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451  
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500  
RT-PRC017-EN  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-13 - Belt Drive Evaporator Fan Performance - YSC072AD*H - High Heat - Horizontal Configuration (SI)  
External Static Pressure (Pascals)  
25  
50  
75  
100  
RPM  
1.12 Nom kW Standard Motor & Low Static Drive  
125  
RPM  
150  
RPM  
175  
RPM  
200  
RPM  
225  
RPM kW  
250  
RPM kW  
m3/h  
RPM  
kW  
RPM  
kW  
RPM  
kW  
kW  
kW  
kW  
kW  
kW  
1.12 Nom kW Standard Motor & Drive  
3260  
3670  
4080  
4490  
4890  
579  
636  
696  
757  
818  
0.24  
0.33  
0.45  
0.58  
0.74  
639  
692  
746  
802  
858  
0.30  
0.39  
0.51  
0.64  
0.81  
690  
741  
794  
847  
900  
0.35  
0.46  
0.58  
0.72  
0.88  
736  
784  
836  
888  
940  
0.40  
0.51  
0.64  
0.80  
0.97  
780  
826  
874  
924  
977  
0.46  
0.57  
0.70  
0.86  
1.05  
824  
865  
911  
959  
0.52  
0.64  
0.77  
0.93  
866  
903  
947  
993  
0.59  
0.71  
0.84  
907  
943  
982  
0.65  
0.78  
947 0.71  
979 0.84 1017 0.91  
986 0.78  
0.92 1017 1.00 1051 1.07  
1.00 1026 1.08 1058 1.17 1089 1.25  
1010 1.13  
1042 1.20 1073 1.27 1104 1.36 1133 1.45  
1.50 Nom kW Over-Sized Motor  
1.12 Nom kW Standard Motor & Drive  
& High Static Drive  
External Static Pressure (Pascals)  
1.12 Nom kW Std Mtr  
& Hi Static Drive  
275  
RPM  
300  
RPM  
325  
RPM  
350  
RPM  
375  
RPM  
CFM  
kW  
kW  
kW  
kW  
kW  
1.12 Nom kW Standard Motor  
& Hi Static Drive  
3260  
3670  
4080  
4490  
4890  
1023 0.84  
1053 0.98  
1085 1.15  
1122 1.34  
1163 1.54  
1059 0.92  
1087 1.06  
1119 1.23  
1153 1.42  
1192 1.64  
1093 0.98  
1121 1.13  
1151 1.30  
1184 1.50  
1221 1.72  
1126 1.06  
1153 1.21  
1182 1.38  
1215 1.59  
1156 1.12  
1185 1.29  
1214 1.47  
-
-
-
-
-
-
1.50 Nom kW Over-Sized Motor & Hi Static Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
Tested To Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132  
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464  
Table PD-13a - Belt Drive Evaporator Fan Performance -YSC072AD*H - High Heat - Horizontal Configuration - (IP)  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
1-1/2 HP Standard Motor & Low Static Drive  
1-1/2 HP Standard Motor & Drive  
1920  
2160  
2400  
2640  
2880  
579  
636  
696  
757  
818  
0.33  
0.45  
0.60  
0.78  
1.00  
639  
692  
746  
802  
858  
0.40  
0.53  
0.68  
0.86  
1.08  
690  
741  
794  
847  
900  
0.47  
0.61  
0.78  
0.96  
1.18  
736  
784  
836  
888  
940  
0.54  
0.68  
0.86  
1.07  
1.30  
780  
826  
874  
924  
977  
0.62  
0.76  
0.94  
1.16  
1.41  
824  
865  
911  
959  
0.70  
0.85  
1.03  
1.25  
866  
903  
947  
993  
0.79  
0.95  
1.13  
907  
943  
982  
0.87  
1.04  
947 0.95  
979 1.13 1017 1.23  
986 1.04  
1.23 1017 1.34 1051 1.44  
1.35 1026 1.45 1058 1.56 1089 1.68  
1010 1.51  
1042 1.61 1073 1.71 1104 1.82 1133 1.94  
1-1/2 HP Standard Motor & Drive  
2 HP Over-Sized Motor  
& Hi Static Drive  
External Static Pressure (Inches of Water)  
1.10  
RPM BHP  
1.20  
1.30  
RPM BHP  
1.40  
RPM BHP  
1.50  
RPM BHP  
1-1/2 HP Std Motor  
& Hi Static Drive  
CFM  
RPM BHP  
1-1/2 HP Standard Motor & Hi Static Drive  
1920  
2160  
2400  
2640  
2880  
1023 1.13  
1053 1.32  
1085 1.54  
1122 1.79  
1163 2.07  
1059 1.23  
1087 1.42  
1119 1.65  
1153 1.90  
1192 2.19  
1093  
1.32  
1126 1.42  
1153 1.62  
1182 1.85  
1215 2.13  
1156 1.51  
1185 1.72  
1214 1.96  
1121 1.52  
1151 1.75  
1184 2.01  
1221 2.31  
-
-
-
-
-
-
2 HP Over-Sized Motor & Hi Static Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
Tested To Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451  
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500  
26  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-14 - Belt Drive Evaporator Fan Performance -YSC090AD*L - Low Heat - Downflow Configuration - (SI)  
External Static Pressure (Pascals)  
25  
50  
75  
100  
RPM  
1.50 Nom kW Standard Motor & Low Static Drive  
125  
RPM  
150  
RPM  
175  
RPM  
200  
RPM  
225  
RPM kW  
250  
RPM kW  
m3/h  
RPM  
kW  
RPM  
kW  
RPM  
kW  
kW  
kW  
kW  
kW  
kW  
1.50 Nom kW Standard Motor & Drive  
4080  
4590  
5100  
5610  
6120  
-
-
-
-
-
-
676  
727  
780  
834  
890  
0.44  
0.57  
0.73  
0.92  
1.15  
726  
770  
819  
871  
925  
0.50  
0.64  
0.80  
1.00  
1.23  
773  
814  
858  
906  
958  
0.57  
0.71  
0.88  
1.08  
1.31  
815  
856  
898  
942  
991  
0.64  
0.79  
0.96  
1.17  
1.40  
854  
895  
936  
978  
0.70  
0.86  
1.05  
891  
931  
972  
0.77  
0.94  
928 0.84  
965 1.01  
963 0.91  
998 1.08  
682  
738  
795  
853  
0.50  
0.66  
0.85  
1.07  
693  
753  
814  
0.59  
0.77  
0.97  
1.13 1006 1.21 1038 1.29  
1.26 1014 1.35 1048 1.44 1080 1.53  
1023 1.50 1057 1.60 1088 1.70 1121 1.80  
2.24 Nom kW Over-Sized  
Motor & Hi Static Drive  
External Static Pressure (Pascals)  
300 325 350  
RPM RPM  
275  
RPM  
375  
RPM  
CFM  
kW  
RPM  
kW  
kW  
kW  
kW  
1.50 Nom kW Standard Motor & Drive  
4080  
4590  
5100  
5610  
6120  
996  
0.98  
1028 1.06  
1062 1.24  
1099 1.46  
1139 1.71  
1181 2.00  
1061 1.14  
1093 1.32  
1128 1.54  
1167 1.80  
1208 2.10  
1092 1.21  
1123 1.41  
1158 1.63  
1195 1.89  
1236 2.20  
1122 1.29  
1153 1.49  
1185 1.72  
1222 1.98  
1261 2.29  
1.50 Nom kW Standard Motor  
& Hi Static Drive  
1031 1.16  
1070 1.38  
1110 1.62  
1151 1.90  
2.24 Nom kW Over-Sized Motor & Hi Static Drive  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
Tested To Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
1.50 Nom kW Standard Motor & Hi Static Drive  
Notes:  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464  
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139  
Table PD-14a - Belt Drive Evaporator Fan Performance -YSC090AD*L - Low Heat - Downflow Configuration - (IP)  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
2 HP Standard Motor & Low Static Drive  
2 HP Standard Motor & Drive  
2400  
2700  
3000  
3300  
3600  
-
-
-
-
-
-
676  
727  
780  
834  
890  
0.59  
0.76  
0.97  
1.23  
1.55  
726  
770  
819  
871  
925  
0.67  
0.85  
1.07  
1.33  
1.65  
773  
814  
858  
906  
958  
0.77  
0.95  
1.18  
1.45  
1.76  
815  
856  
898  
942  
991  
0.85  
1.06  
1.29  
1.56  
1.88  
854  
895  
936  
978  
0.94  
1.16  
1.40  
891  
931  
972  
1.03  
1.25  
928 1.12  
965 1.35  
963 1.22  
998 1.45  
682  
738  
795  
853  
0.68  
0.89  
1.14  
1.44  
693  
753  
814  
0.79  
1.03  
1.31  
1.52 1006 1.63 1038 1.73  
1.69 1014 1.81 1048 1.94 1080 2.06  
1023 2.01 1057 2.14 1088 2.28 1121 2.41  
3 HP Over-Sized  
Motor & Drive  
External Static Pressure (Inches of Water)  
1.10  
RPM BHP  
1.20  
1.30  
RPM BHP  
1.40  
RPM BHP  
1.50  
RPM BHP  
CFM  
RPM BHP  
2 HP Standard Motor & Drive  
2400  
2700  
3000  
3300  
3600  
996  
1.32  
1028 1.42  
1062 1.66  
1099 1.95  
1139 2.29  
1181 2.68  
1061 1.52  
1093 1.78  
1128 2.07  
1167 2.42  
1208 2.81  
1092 1.63  
1123 1.89  
1158 2.19  
1195 2.54  
1236 2.95  
1122 1.73  
1153 2.00  
1185 2.31  
1222 2.66  
1261 3.07  
1031 1.56  
1070 1.85  
1110 2.18  
1151 2.55  
2 HP Standard Motor &  
Hi Static Drive  
3 HP Over-Sized Mtr & Hi Static Drive  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
Tested To Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
2 HP Standard Motor & Hi Static Drive  
Notes:  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500  
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475  
RT-PRC017-EN  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-15 - Belt Drive Evaporator Fan Performance - YSC090AD*L - Horizontal Configuration (SI)  
External Static Pressure (Pascals)  
25  
50  
75  
100  
RPM  
1.50 Nom kW Standard Motor & Low Static Drive  
125  
RPM  
150  
RPM  
175  
RPM  
200  
RPM  
225  
RPM kW  
250  
RPM kW  
m3/h  
RPM  
kW  
RPM  
kW  
RPM  
kW  
kW  
kW  
kW  
kW  
kW  
1.50 Nom kW Standard Motor & Drive  
4080  
4590  
5100  
5610  
6120  
-
-
694  
760  
830  
901  
973  
0.44  
0.60  
0.79  
1.03  
1.31  
745  
801  
862  
929  
0.50  
0.66  
0.86  
1.10  
793  
847  
902  
961  
0.58  
0.73  
0.93  
1.17  
835  
889  
943  
998  
0.64  
0.82  
1.01  
1.25  
874  
927  
981  
1036 1.34  
1091 1.62  
0.70  
0.89  
1.10  
911  
963  
0.77  
0.96  
948  
997  
0.85  
982 0.92 1017 1.00  
725  
798  
872  
946  
0.54  
0.73  
0.96  
1.23  
1.03 1030 1.11 1061 1.19  
1017 1.19 1050 1.27 1081 1.34 1111 1.42  
1071 1.44 1104 1.54 1135 1.63 1164 1.71  
1125 1.72 1158 1.83 1189 1.95 1219 2.05  
2.24 Nom kW Over-Sized  
1000 1.38  
1025 1.45  
1057 1.54  
Motor & Hi Static Drive  
1.50 Nom kW Std Mtr  
& Hi Static Drive  
External Static Pressure (Pascals)  
300 325 350  
RPM RPM  
275  
RPM  
375  
RPM kW  
CFM  
kW  
RPM  
kW  
kW  
kW  
1.50 Nom kW Std Mtr & Drive  
1.50 Nom kW Std Mtr  
& Hi Static Drive  
4080  
4590  
5100  
5610  
6120  
1053 1.08  
1093 1.28  
1141 1.51  
1192 1.79  
1246 2.14  
1087 1.15  
1124 1.37  
1170 1.60  
1220 1.88  
1272 2.23  
1121 1.23  
1156 1.45  
1198 1.70  
1247 1.98  
1298 2.32  
1153 1.31  
1187 1.54  
1227 1.80  
1272 2.07  
1323 2.41  
1185 1.39  
1218 1.63  
1255 1.89  
1299 2.18  
1348 2.52  
2.24 Nom kW Over-Sized Motor & Hi Static Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
TestedTo Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464  
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139  
Table PD-15a - Belt Drive Evaporator Fan Performance -YSC090AD*L - Horizontal Configuration - (IP)  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
2 HP Std Motor & Low Static Drive  
2 HP Standard Motor & Drive  
2400  
2700  
3000  
3300  
3600  
-
-
694  
760  
830  
901  
973  
0.59  
0.80  
1.06  
1.38  
1.75  
745  
801  
862  
929  
0.67  
0.88  
1.15  
1.47  
793  
847  
902  
961  
0.77  
0.98  
1.24  
1.56  
835  
889  
943  
998  
0.86  
1.09  
1.35  
1.67  
874  
927  
981  
1036 1.80  
1091 2.17  
0.94  
1.19  
1.48  
911  
963  
1.03  
1.28  
948  
997  
1.13  
982 1.23 1017 1.34  
725  
798  
872  
946  
0.73  
0.98  
1.28  
1.65  
1.38 1030 1.48 1061 1.60  
1017 1.60 1050 1.70 1081 1.80 1111 1.90  
1071 1.93 1104 2.07 1135 2.19 1164 2.30  
1125 2.31 1158 2.46 1189 2.61 1219 2.75  
3 HP Over-Sized Motor  
1000 1.85  
1025 1.95  
1057 2.06  
& Hi Static Drive  
External Static Pressure (Inches of Water)  
2 HP Std Mtr & Hi Static Drive  
1.10  
RPM BHP  
1.20  
1.30  
RPM BHP  
1.40  
RPM BHP  
1.50  
RPM BHP  
CFM  
RPM BHP  
2 HP Standard Motor & Drive  
2 HP Standard Motor  
& Hi Static Drive  
2400  
2700  
3000  
3300  
3600  
1053 1.44  
1093 1.71  
1141 2.02  
1192 2.41  
1246 2.87  
1087 1.55  
1124 1.83  
1170 2.15  
1220 2.52  
1272 2.99  
1121 1.65  
1156 1.95  
1198 2.28  
1247 2.65  
1298 3.11  
1153 1.76  
1187 2.06  
1227 2.41  
1272 2.78  
1323 3.24  
1185 1.86  
1218 2.18  
1255 2.54  
1299 2.92  
1348 3.37  
3 HP Over-Sized Motor & High Static Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
Tested To Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500  
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475  
28  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-16 - Belt Drive Evaporator Fan Performance -YSC090AD*H - High Heat - Downflow Configuration - (SI)  
External Static Pressure (Pascals)  
25  
50  
75  
100  
RPM  
1.50 Nom kW Standard Motor & Low Static Drive  
125  
RPM  
150  
RPM  
175  
RPM  
200  
RPM  
225  
RPM kW  
250  
RPM kW  
m3/h  
RPM  
kW  
RPM  
kW  
RPM  
kW  
kW  
kW  
kW  
kW  
kW  
1.50 Nom kW Standard Motor & Drive  
4080  
4590  
5100  
5610  
6120  
-
-
697  
760  
826  
894  
963  
0.46  
0.62  
0.81  
1.05  
1.33  
745  
804  
865  
929  
995  
0.53  
0.69  
0.89  
1.13  
1.42  
790  
847  
905  
965  
0.60  
0.77  
0.98  
1.22  
830  
887  
943  
1001 1.32  
1061 1.61  
0.66  
0.85  
1.06  
869  
922  
979  
1036 1.41  
1093 1.71  
0.73  
0.92  
1.15  
906  
958  
0.80  
0.99  
941  
991  
0.87  
976 0.94 1009 1.01  
717  
787  
858  
930  
0.55  
0.74  
0.97  
1.24  
1.07 1024 1.14 1055 1.22  
1012 1.23 1044 1.31 1075 1.39 1105 1.47  
1068 1.50 1099 1.59 1129 1.68 1157 1.77  
1126 1.82 1157 1.92 1185 2.02 1212 2.11  
1028 1.51  
2.24 Nom kW Over-Sized  
Motor & Hi Static Drive  
External Static Pressure (Pascals)  
300 325 350  
RPM RPM  
275  
RPM  
375  
RPM  
CFM  
kW  
RPM  
kW  
kW  
kW  
kW  
1.50 Nom kW Std Mtr & Drive  
1.50 Nom kW Std Motor  
& Hi Static Drive  
4080  
4590  
5100  
5610  
6120  
1042 1.09  
1086 1.30  
1134 1.56  
1185 1.86  
1239 2.21  
1073 1.17  
1117 1.39  
1163 1.65  
1212 1.95  
1265 2.31  
1104 1.24  
1146 1.47  
1191 1.74  
1238 2.04  
1290 2.40  
1134 1.32  
1174 1.56  
1218 1.83  
1265 2.14  
1316 2.51  
1163 1.40  
1203 1.65  
1245 1.92  
1292 2.24  
1340 2.61  
2.24 Nom kW Over-Sized Motor & Hi Static Drive  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
Tested To Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
Notes:  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464  
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139  
Table PD-16a - Belt Drive Evaporator Fan Performance -YSC090AD*H - High Heat - Downflow Configuration - (IP)  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
2 HP Standard Motor & Low Static Drive  
2 HP Standard Motor & Drive  
2400  
2700  
3000  
3300  
3600  
-
-
697  
760  
826  
894  
963  
0.62  
0.83  
1.09  
1.41  
1.78  
745  
804  
865  
929  
995  
0.71  
0.93  
1.20  
1.52  
1.90  
790  
847  
905  
965  
0.80  
1.03  
1.31  
1.64  
830  
887  
943  
1001 1.77  
1061 2.16  
0.89  
1.13  
1.42  
869  
922  
979  
1036 1.89  
1093 2.30  
0.98  
1.23  
1.54  
906  
958  
1.07  
1.33  
941  
991  
1.16  
976 1.26 1009 1.36  
717  
787  
858  
930  
0.74  
0.99  
1.30  
1.66  
1.43 1024 1.53 1055 1.64  
1012 1.64 1044 1.76 1075 1.87 1105 1.98  
1068 2.01 1099 2.13 1129 2.25 1157 2.37  
1126 2.43 1157 2.57 1185 2.70 1212 2.83  
3 HP Over-Sized Motor & Drive  
1028 2.03  
External Static Pressure (Inches of Water)  
1.10  
RPM BHP  
1.20  
1.30  
RPM BHP  
1.40  
RPM BHP  
1.50  
RPM BHP  
CFM  
RPM BHP  
2 HP Standard Motor &  
Hi Static Drive  
2 HP Standard Motor & Drive  
2400  
2700  
3000  
3300  
3600  
1042 1.46  
1086 1.75  
1134 2.09  
1185 2.49  
1239 2.96  
1073 1.56  
1117 1.86  
1163 2.21  
1212 2.61  
1265 3.09  
1104 1.67  
1146 1.97  
1191 2.33  
1238 2.74  
1290 3.22  
1134 1.77  
1174 2.09  
1218 2.45  
1265 2.87  
1316 3.36  
1163 1.87  
1203 2.21  
1245 2.58  
1292 3.01  
1340 3.49  
3 HP Over-Sized Mtr & Hi Static Drive  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
Tested To Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
Notes:  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500  
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475  
RT-PRC017-EN  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-17 - Belt Drive Evaporator Fan Performance - YSC090AD*H - High Heat - Horizontal Configuration (SI)  
External Static Pressure (Pascals)  
25  
50  
75  
100  
RPM  
1.50 Nom kW Standard Motor & Drive  
125  
RPM  
150  
RPM  
175  
RPM  
200  
RPM  
225  
RPM kW  
250  
RPM kW  
m3/h  
RPM  
kW  
RPM  
kW  
RPM  
kW  
kW  
kW  
kW  
kW  
kW  
1.50 Nom kW Standard Motor  
& Low Static Drive  
4080  
4590  
5100  
5610  
6120  
713  
790  
869  
949  
0.46  
0.64  
0.87  
1.14  
764  
837  
910  
985  
0.53  
0.71  
0.94  
1.22  
811  
880  
950  
1023 1.30  
1096 1.64  
0.61  
0.80  
1.03  
851  
919  
989  
1058 1.40  
1130 1.74  
0.67  
0.88  
1.12  
889  
955  
1023 1.21  
1092 1.51  
1162 1.85  
0.73  
0.94  
926  
989  
1056 1.28  
1124 1.60  
1193 1.96  
0.80  
1.01  
962  
0.88  
997  
0.95 1031 1.03 1067 1.11  
1022 1.09 1054 1.17 1086 1.26 1117 1.35  
1086 1.36 1116 1.43 1146 1.52 1175 1.62  
1154 1.68 1182 1.77 1210 1.85 1237 1.94  
1222 2.06 1250 2.16 1276 2.25 1302 2.34  
1029 1.47  
1061 1.55  
2.24 Nom kW Over-Sized  
Motor & Hi Static Drive  
1.50 Nom kW Std Mtr  
& Hi Static Drive  
External Static Pressure (Pascals)  
300 325 350  
RPM RPM RPM  
275  
RPM  
375  
RPM kW  
CFM  
kW  
kW  
kW  
kW  
1.50 Nom kW Std Mtr  
& Drive  
1.50 Nom kW Standard Motor  
& Hi Static Drive  
4080  
4590  
5100  
5610  
6120  
1101 1.19  
1148 1.43  
1204 1.72  
1264 2.04  
1327 2.43  
1134 1.26  
1180 1.52  
1232 1.81  
1290 2.14  
1352 2.53  
1166 1.34  
1210 1.60  
1260 1.91  
1316 2.25  
1376 2.64  
1197 1.42  
1241 1.69  
1287 2.00  
1342 2.36  
1401 2.75  
1229 1.50  
1269 1.78  
1316 2.10  
1367 2.46  
1425 2.87  
2.24 Nom kW Over-Sized Motor & Hi Static Drive  
Factory Supplied Motors, In Commercial Equipment, Are  
Definite Purpose Motors, Specifically Designed And  
Tested To Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
Notes:  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464  
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139  
Table PD-17a - Belt Drive Evaporator Fan Performance -YSC090AD*H - High Heat - Horizontal Configuration - (IP)  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
2 HP Std Motor & Low Static Drive  
2 HP Standard Motor & Drive  
2400  
2700  
3000  
3300  
3600  
713  
790  
869  
949  
0.62  
0.86  
1.16  
1.53  
764  
837  
910  
985  
0.71  
0.96  
1.26  
1.63  
811  
880  
950  
1023 1.75  
1096 2.19  
0.81  
1.07  
1.38  
851  
919  
989  
1058 1.88  
1130 2.33  
0.89  
1.17  
1.50  
889  
955  
1023 1.62  
1092 2.02  
1162 2.48  
0.97  
1.26  
926  
989  
1056 1.72  
1124 2.15  
1193 2.63  
1.07  
1.36  
962  
1.17  
997  
1.28 1031 1.38 1067 1.48  
1022 1.46 1054 1.57 1086 1.69 1117 1.80  
1086 1.82 1116 1.92 1146 2.04 1175 2.17  
1154 2.26 1182 2.37 1210 2.48 1237 2.60  
1222 2.77 1250 2.89 1276 3.01 1302 3.13  
1029 1.97  
1061 2.07  
3 HP Over-Sized Motor & Hi Static Drive  
2 HP Std Mtr & Hi Static Drive  
External Static Pressure (Inches of Water)  
1.10  
1.20  
1.30  
1.40  
1.50  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
2 HP Std Mtr & Drive  
2 HP Standard Motor  
& Hi Static Drive  
2400  
2700  
3000  
3300  
3600  
1101 1.59  
1148 1.92  
1204 2.30  
1264 2.74  
1327 3.26  
1134 1.69  
1166 1.80  
1210 2.15  
1260 2.56  
1316 3.02  
1376 3.54  
1197 1.90  
1241 2.27  
1287 2.69  
1342 3.16  
1401 3.69  
1229 2.02  
1180 2.04  
1232 2.43  
1290 2.87  
1352 3.39  
1269 2.39  
1316 2.82  
1367 3.30  
1425 3.85  
3 HP Over-Sized Motor & High Static Drive  
Factory Supplied Motors, In Commercial Equipment, Are  
Notes:  
Definite Purpose Motors, Specifically Designed And  
TestedTo Operate Reliably And Continuously At All  
Cataloged Conditions. Using The Full Horsepower Range  
Of Our Fan Motors As Shown In OurTabular Data Will  
Not Result In NuisanceTripping Or Premature Motor  
Failure. Our Products Warranty Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500  
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475  
30  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-18 - Belt Drive Evaporator Fan Performance -YSC102AD*L - Low Heat - Downflow Configuration - (SI)  
External Static Pressure (Pascals)  
25  
50  
75  
100  
RPM  
1.50 Nom kW Standard Motor & Low Static Drive  
125  
RPM  
150  
RPM  
175  
RPM  
200  
RPM  
1.50 Nom kW Std Mtr & Drive  
225  
RPM kW  
250  
RPM kW  
m3/h  
RPM  
kW  
RPM  
kW  
RPM  
kW  
kW  
kW  
kW  
kW  
kW  
4620  
5200  
5780  
6350  
6930  
-
-
-
-
-
-
610  
656  
704  
754  
805  
0.44  
0.56  
0.71  
0.89  
1.09  
651  
693  
739  
787  
836  
0.53  
0.65  
0.80  
0.98  
1.20  
691  
731  
772  
817  
865  
0.62  
0.75  
0.90  
1.08  
1.30  
729  
766  
806  
848  
893  
0.70  
0.84  
1.00  
1.19  
1.41  
766  
800  
838  
879  
921  
0.80  
0.94  
1.11  
1.31  
1.53  
799  
834  
870  
908  
949  
0.89  
1.04  
1.22  
1.43  
1.65  
831 0.99  
865 1.15  
900 1.33  
937 1.54  
861 1.10  
895 1.25  
931 1.45  
966 1.66  
617  
667  
719  
772  
0.49  
0.63  
0.79  
0.99  
628  
684  
740  
0.54  
0.70  
0.89  
977 1.78 1004 1.92  
2.24 Nom kW Over-Sized  
Motor & High Static Drive  
External Static Pressure (Pascals)  
375 400  
RPM RPM  
275  
RPM  
300  
RPM  
325  
RPM  
350  
RPM  
425  
RPM  
450  
RPM  
475  
RPM kW  
500  
RPM kW  
m3/h  
kW  
kW  
kW  
kW  
kW  
kW  
kW  
kW  
1.50 Nom kW Standard Motor & Drive  
4620  
5200  
5780  
6350  
6930  
890  
924  
959  
993  
1.21  
1.37  
1.56  
1.79  
917  
951  
986  
1020 1.91  
1056 2.18  
1.31  
1.48  
1.68  
944  
978  
1012 1.80  
1046 2.04  
1082 2.31  
1.43  
1.61  
970  
1.54  
996  
1.66  
1022 1.77  
1051 1.98  
1084 2.19  
1119 2.44  
1154 2.72  
1048 1.89 1071 2.01 1096 2.13 1118 2.25  
1075 2.11 1098 2.23 1122 2.36 1144 2.49  
1108 2.33 1130 2.46 1153 2.61 1174 2.75  
1141 2.58 1163 2.72 1185 2.87 1207 3.02  
1176 2.86 1199 3.01 1220 3.16 1241 3.31  
1003 1.73  
1037 1.93  
1071 2.17  
1106 2.44  
1027 1.85  
1061 2.06  
1096 2.30  
1131 2.58  
1030 2.04  
2.24 Nom kW Over-Sized Motor & High Static Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo  
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors  
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Products Warranty  
Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464  
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139  
Table PD-18a - Belt Drive Evaporator Fan Performance -YSC102AD*L - Low Heat - Downflow Configuration - (IP)  
External Static Pressure (Inches of Water)  
.10  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
2 HP Standard Motor & Low Static Drive  
2 HP Standard Motor & Drive  
2720  
3060  
3400  
3740  
4080  
-
-
-
-
-
-
610  
656  
704  
754  
805  
0.59  
0.76  
0.96  
1.19  
1.47  
651  
693  
739  
787  
836  
0.71  
0.87  
1.07  
1.32  
1.61  
691  
731  
772  
817  
865  
0.83  
1.00  
1.20  
1.45  
1.74  
729  
766  
806  
848  
893  
0.94  
1.13  
1.35  
1.59  
1.89  
766  
800  
838  
879  
921  
1.07  
1.26  
1.49  
1.75  
2.05  
799  
834  
870  
908  
949  
1.19  
1.40  
1.64  
1.91  
2.21  
831 1.33  
865 1.54  
900 1.79  
937 2.07  
861 1.47  
895 1.68  
931 1.94  
966 2.23  
617  
667  
719  
772  
0.65  
0.84  
1.06  
1.32  
628  
684  
740  
0.72  
0.94  
1.20  
977 2.39 1004 2.57  
3 HP Over-Sized Motor & Drive  
External Static Pressure (Inches of Water)  
1.10  
RPM BHP  
1.20  
RPM BHP  
2 HP Standard Motor & Drive  
1.30  
RPM BHP  
1.40  
1.50  
RPM BHP  
1.60  
RPM BHP  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
2720  
3060  
3400  
3740  
4080  
890  
924  
959  
993  
1.62  
1.84  
2.09  
2.39  
917  
951  
986  
1020 2.56  
1056 2.92  
1.76  
1.99  
2.25  
944  
978  
1012 2.42  
1046 2.73  
1082 3.10  
1.91  
2.15  
970  
2.07  
996  
2.22  
1022 2.38  
1051 2.65  
1084 2.94  
1119 3.27  
1154 3.65  
1048 2.54 1071 2.69 1096 2.86 1118 3.02  
1075 2.82 1098 2.99 1122 3.17 1144 3.34  
1108 3.13 1130 3.31 1153 3.50 1174 3.68  
1141 3.45 1163 3.64 1185 3.84 1207 4.04  
1176 3.83 1199 4.03 1220 4.23 1241 4.44  
1003 2.32  
1037 2.59  
1071 2.90  
1106 3.28  
1027 2.48  
1061 2.77  
1096 3.08  
1131 3.46  
1030 2.74  
3 HP Over-Sized Motor & Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo  
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors  
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Products Warranty  
Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500  
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475  
RT-PRC017-EN  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-19 - Belt Drive Evaporator Fan Performance - YSC102AD*L - Horizontal Configuration (SI)  
External Static Pressure (Pascals)  
25  
50  
75  
100  
RPM  
1.50 Nom kW Standard Motor & Low Static Drive  
125  
RPM  
150  
RPM  
1.50 Nom kW Standard Motor & Drive  
175  
RPM  
200  
RPM  
225  
RPM kW  
250  
RPM kW  
m3/h  
RPM  
kW  
RPM  
kW  
RPM  
kW  
kW  
kW  
kW  
kW  
kW  
4620  
5200  
5780  
6350  
6930  
610  
675  
742  
810  
878  
0.44  
0.61  
0.82  
1.07  
1.37  
657  
718  
779  
842  
907  
0.52  
0.70  
0.91  
1.16  
1.47  
700  
757  
817  
878  
939  
0.60  
0.78  
1.01  
1.27  
1.58  
747  
794  
851  
911  
971  
0.70  
0.87  
1.10  
1.38  
1.70  
793  
837  
885  
941  
0.80  
0.98  
1.21  
1.49  
837  
879  
923  
972  
0.91  
1.10  
1.33  
1.60  
873  
919  
962  
1.00  
1.22  
1.46  
905  
955  
999  
1.09  
1.34  
935 1.18  
987 1.44 1014 1.54  
963 1.27  
1.59 1033 1.72 1066 1.85  
1006 1.73 1041 1.87 1076 2.02 1109 2.17  
1056 2.06 1087 2.20 1120 2.35 1151 2.50  
1000 1.82  
1029 1.94  
2.24 Nom kW Over-Sized Motor & High Static Drive  
External Static Pressure (Pascals)  
375 400  
RPM RPM  
275  
RPM  
300  
RPM  
325  
RPM  
350  
RPM  
425  
RPM  
450  
RPM  
475  
RPM kW  
500  
RPM kW  
m3/h  
kW  
kW  
kW  
kW  
kW  
kW  
kW  
kW  
1.50 Nom kW Std Mtr & Drive  
4620  
5200  
5780  
6350  
6930  
989  
1.36  
1015 1.45  
1067 1.74  
1118 2.08  
1169 2.45  
1213 2.83  
1038 1.53  
1092 1.84  
1144 2.19  
1195 2.58  
1241 2.98  
1062 1.62  
1115 1.94  
1167 2.30  
1219 2.70  
1268 3.14  
1085 1.71  
1138 2.04  
1190 2.41  
1242 2.83  
1292 3.28  
1108 1.80  
1159 2.14  
1212 2.52  
1264 2.95  
1129 1.88 1152 1.98 1172 2.06 1194 2.16  
1180 2.23 1200 2.33 1221 2.43 1241 2.53  
1233 2.63 1253 2.74 1273 2.85 1292 2.96  
1042 1.64  
1093 1.97  
1140 2.31  
1182 2.66  
1286 3.07 1307 3.19 1326 3.31  
-
-
-
-
-
-
-
-
-
-
-
-
2.24 Nom kW Over-Sized Motor & High Static Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo  
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors  
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Products Warranty  
Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464  
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139  
Table PD-19a - Belt Drive Evaporator Fan Performance - YSC102AD*L - Horizontal Configuration - (IP)  
External Static Pressure (Inches of Water)  
1.10  
1.20  
1.30  
1.40  
1.50  
1.60  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
2 HP Standard Motor & Low Static Drive  
2 HP Standard Motor & Drive  
2720  
3060  
3400  
3740  
4080  
610  
675  
742  
810  
878  
0.59  
0.82  
1.09  
1.44  
1.84  
657  
718  
779  
842  
907  
0.70  
0.93  
1.21  
1.56  
1.97  
700  
757  
817  
878  
939  
0.81  
1.05  
1.35  
1.70  
2.12  
747  
794  
851  
911  
971  
0.93  
1.17  
1.48  
1.85  
2.28  
793  
837  
885  
941  
1.08  
1.32  
1.62  
1.99  
837  
879  
923  
972  
1.22  
1.48  
1.78  
2.14  
873  
919  
962  
1.35  
1.64  
1.96  
905  
955  
999  
1.47  
1.79  
935 1.58  
987 1.94 1014 2.07  
963 1.70  
2.13 1033 2.31 1066 2.48  
1006 2.32 1041 2.51 1076 2.71 1109 2.90  
1056 2.76 1087 2.95 1120 3.16 1151 3.36  
3 HP Over-Sized Motor & Drive  
1000 2.44  
1029 2.60  
External Static Pressure (Inches of Water)  
1.10  
RPM BHP  
2 HP Standard Motor & Drive  
1.20  
RPM BHP  
1.30  
RPM BHP  
1.40  
RPM BHP  
1.50  
RPM BHP  
1.60  
RPM BHP  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP  
3 HP Over-Sized Motor & Drive  
2720  
3060  
3400  
3740  
4080  
989  
1.82  
1015 1.94  
1067 2.34  
1118 2.78  
1169 3.28  
1213 3.79  
1038 2.05  
1092 2.47  
1144 2.94  
1195 3.46  
1241 4.00  
1062 2.17  
1115 2.60  
1167 3.08  
1219 3.63  
1268 4.21  
1085 2.29  
1138 2.74  
1190 3.23  
1242 3.79  
1292 4.40  
1108 2.41  
1159 2.87  
1212 3.38  
1264 3.96  
1129 2.53 1152 2.65 1172 2.77 1194 2.89  
1180 3.00 1200 3.13 1221 3.26 1241 3.40  
1233 3.53 1253 3.67 1273 3.82 1292 3.97  
1042 2.20  
1093 2.64  
1140 3.10  
1182 3.57  
1286 4.12 1307 4.28 1326 4.44  
-
-
-
-
-
-
-
-
-
-
-
-
3 HP Over-Sized Motor & Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo  
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors  
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Products Warranty  
Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500  
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475  
32  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-20 - Belt Drive Evaporator Fan Performance -YSC102AD*H - High Heat - Downflow Configuration - (SI)  
External Static Pressure (Pascals)  
25  
50  
75  
100  
RPM  
1.50 Nom kW Standard Motor & Low Static Drive  
125  
RPM  
150  
RPM  
175  
RPM  
200  
RPM  
225  
RPM kW  
250  
RPM kW  
m3/h  
RPM  
kW  
RPM  
kW  
RPM  
kW  
kW  
kW  
kW  
kW  
kW  
1.50 Nom kW Standard Motor & Drive  
4620  
5200  
5780  
6350  
6930  
-
-
-
-
-
-
636  
686  
738  
792  
848  
0.50  
0.63  
0.80  
1.00  
1.24  
676  
723  
772  
823  
877  
0.58  
0.73  
0.90  
1.10  
1.34  
716  
759  
805  
854  
905  
0.67  
0.82  
1.00  
1.21  
1.46  
752  
794  
837  
884  
933  
0.76  
0.92  
1.11  
1.33  
1.58  
787  
827  
869  
914  
961  
0.85  
1.02  
1.22  
1.45  
1.71  
819  
859  
900  
943  
988  
0.96  
1.13  
1.33  
1.57  
850 1.06  
890 1.23  
929 1.44  
971 1.69  
879 1.17  
918 1.34  
959 1.56  
999 1.81  
648  
704  
761  
818  
0.55  
0.71  
0.91  
1.14  
667  
726  
786  
0.62  
0.81  
1.03  
1.84 1015 1.97 1041 2.10  
2.24 Nom kW Over-Sized  
Motor & High Static Drive  
External Static Pressure (Pascals)  
375 400  
RPM RPM  
275  
RPM  
300  
RPM  
325  
RPM  
350  
RPM  
425  
RPM  
450  
RPM  
475  
RPM kW  
500  
RPM kW  
m3/h  
kW  
kW  
kW  
kW  
kW  
kW  
kW  
kW  
1.50 Nom kW Standard Motor & Drive  
4620  
5200  
5780  
6350  
6930  
907  
946  
986  
1025 1.94  
1067 2.23  
1.27  
1.46  
1.68  
934  
971  
1011 1.80  
1051 2.06  
1092 2.36  
1.39  
1.58  
960  
997  
1037 1.93  
1077 2.19  
1117 2.50  
1.50  
1.70  
987  
1.62  
1013 1.73  
1047 1.95  
1085 2.19  
1123 2.46  
1164 2.78  
1038 1.85  
1070 2.08  
1107 2.33  
1147 2.61  
1187 2.92  
1064 1.97 1087 2.09 1111 2.21 1134 2.34  
1094 2.21 1117 2.34 1140 2.47 1163 2.60  
1130 2.46 1151 2.60 1174 2.75 1194 2.88  
1168 2.75 1189 2.89 1211 3.04 1231 3.19  
1023 1.83  
1061 2.06  
1100 2.32  
1140 2.64  
1208 3.07 1229 3.22  
-
-
-
-
2.24 Nom kW Over-Sized Motor & High Static Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo  
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors  
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Products Warranty  
Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464  
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139  
Table PD-20a - Belt Drive Evaporator Fan Performance -YSC102AD*H - High Heat - Downflow Configuration - (IP)  
External Static Pressure (Inches of Water)  
1.10  
1.20  
1.30  
1.40  
1.50  
1.60  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
2 HP Standard Motor & Low Static Drive  
2 HP Standard Motor & Drive  
2720  
3060  
3400  
3740  
4080  
-
-
-
-
-
-
636  
686  
738  
792  
848  
0.66  
0.85  
1.07  
1.34  
1.66  
676  
723  
772  
823  
877  
0.78  
0.97  
1.20  
1.47  
1.80  
716  
759  
805  
854  
905  
0.90  
1.10  
1.34  
1.62  
1.95  
752  
794  
837  
884  
933  
1.02  
1.24  
1.49  
1.78  
2.12  
787  
827  
869  
914  
961  
1.15  
1.37  
1.64  
1.94  
2.29  
819  
859  
900  
943  
988  
1.28  
1.51  
1.79  
2.11  
850 1.42  
890 1.65  
929 1.94  
971 2.26  
879 1.56  
918 1.80  
959 2.09  
999 2.43  
648  
704  
761  
818  
0.73  
0.95  
1.22  
1.53  
667  
726  
786  
0.84  
1.09  
1.38  
2.46 1015 2.64 1041 2.82  
3 HP Over-Sized Motor & Drive  
External Static Pressure (Inches of Water)  
1.10  
RPM BHP  
1.20  
RPM BHP  
2 HP Standard Motor & Drive  
1.30  
RPM BHP  
1.40  
RPM BHP  
1.50  
RPM BHP  
1.60  
RPM BHP  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP  
2720  
3060  
3400  
3740  
4080  
907  
946  
986  
1025 2.60  
1067 2.99  
1.71  
1.96  
2.25  
934  
971  
1011 2.41  
1051 2.77  
1092 3.17  
1.86  
2.11  
960  
997  
1037 2.59  
1077 2.94  
1117 3.36  
2.01  
2.28  
987  
2.17  
1013 2.32  
1047 2.62  
1085 2.94  
1123 3.30  
1164 3.73  
1038 2.48  
1070 2.79  
1107 3.12  
1147 3.50  
1187 3.92  
1064 2.64 1087 2.80 1111 2.97 1134 3.14  
1094 2.96 1117 3.13 1140 3.31 1163 3.49  
1130 3.30 1151 3.48 1174 3.69 1194 3.87  
1168 3.68 1189 3.88 1211 4.08 1231 4.28  
1023 2.45  
1061 2.76  
1100 3.12  
1140 3.54  
1208 4.12 1229 4.32  
-
-
-
-
3 HP Over-Sized Motor & Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo  
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors  
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Products Warranty  
Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500  
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475  
RT-PRC017-EN  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-21 - Belt Drive Evaporator Fan Performance - YSC102AD*H - High Heat - Horizontal Configuration (SI)  
External Static Pressure (Pascals)  
25  
50  
75  
100  
RPM  
125  
RPM  
150  
RPM  
1.50 Nom kW Standard Motor & Drive  
175  
RPM  
200  
RPM  
225  
RPM kW  
250  
RPM kW  
m3/h  
RPM  
kW  
RPM  
kW  
RPM  
kW  
kW  
kW  
kW  
kW  
kW  
1.50 Nom kW Std Mtr & Low Static Drive  
4620  
5200  
5780  
6350  
6930  
651  
722  
793  
865  
937  
0.51  
0.70  
0.94  
1.23  
1.57  
694  
761  
830  
899  
970  
0.59  
0.79  
1.04  
1.34  
1.70  
740  
798  
863  
930  
999  
0.68  
0.88  
1.14  
1.45  
1.81  
787  
841  
898  
961  
0.79  
1.00  
1.25  
1.56  
831  
883  
937  
994  
0.89  
1.11  
1.37  
1.68  
869  
923  
975  
1028 1.82  
1085 2.19  
0.99  
1.23  
1.51  
901  
958  
1.08  
1.35  
931  
989  
1.17  
959 1.26  
986 1.35  
1.45 1017 1.55 1045 1.65  
1011 1.64 1045 1.77 1075 1.89 1103 2.01  
1063 1.96 1097 2.11 1129 2.26 1159 2.40  
1118 2.34 1150 2.50 1181 2.66 1211 2.82  
1027 1.93  
1055 2.05  
2.24 Nom kW Over-Sized Motor & High Static Drive  
External Static Pressure (Pascals)  
275  
RPM  
300  
RPM  
325  
RPM  
350  
RPM  
375  
RPM  
400  
RPM  
425  
RPM  
450  
RPM  
475  
RPM kW  
500  
RPM kW  
m3/h  
kW  
kW  
kW  
kW  
kW  
kW  
kW  
kW  
1.50 Nom kW Std Mtr & Drive  
4620  
5200  
5780  
6350  
6930  
1011 1.43  
1070 1.75  
1128 2.12  
1186 2.53  
1239 2.97  
1036 1.52  
1094 1.85  
1152 2.23  
1210 2.65  
1267 3.13  
1059 1.61  
1117 1.95  
1176 2.34  
1233 2.78  
1291 3.27  
1082 1.69  
1139 2.05  
1198 2.45  
1256 2.90  
1104 1.78  
1161 2.15  
1219 2.56  
1278 3.03  
1127 1.87  
1182 2.24  
1241 2.67  
1298 3.15  
1149 1.96 1170 2.05 1191 2.14 1212 2.24  
1203 2.35 1222 2.44 1243 2.54 1262 2.64  
1261 2.78 1280 2.88 1299 2.99 1319 3.11  
1319 3.27  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2.24 Nom kW Over-Sized Motor & High Static Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo  
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors  
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Products Warranty  
Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464  
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139  
Table PD-21a - Belt Drive Evaporator Fan Performance -YSC102AD*H - High Heat - Horizontal Configuration - (IP)  
External Static Pressure (Inches of Water)  
1.10  
1.20  
1.30  
1.40  
1.50  
1.60  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
2 HP Std Motor & Low Static Drive  
2 HP Standard Motor & Drive  
2720  
3060  
3400  
3740  
4080  
651  
722  
793  
865  
937  
0.69  
0.94  
1.26  
1.65  
2.11  
694  
761  
830  
899  
970  
0.79  
1.06  
1.40  
1.80  
2.27  
740  
798  
863  
930  
999  
0.92  
1.18  
1.53  
1.94  
2.43  
787  
841  
898  
961  
1.06  
1.34  
1.67  
2.09  
831  
883  
937  
994  
1.20  
1.49  
1.84  
2.26  
869  
923  
975  
1028 2.44  
1085 2.94  
1.33  
1.65  
2.02  
901  
958  
1.45  
1.81  
931  
989  
1.57  
959 1.69  
986 1.81  
1.95 1017 2.08 1045 2.22  
1011 2.20 1045 2.37 1075 2.54 1103 2.69  
1063 2.63 1097 2.83 1129 3.03 1159 3.22  
1118 3.14 1150 3.35 1181 3.57 1211 3.78  
1027 2.59  
1055 2.75  
3 HP Over-Sized Motor & Drive  
External Static Pressure (Inches of Water)  
1.10  
RPM BHP  
2 HP Std Motor & Drive  
1.20  
RPM BHP  
1.30  
RPM BHP  
1.40  
RPM BHP  
1.50  
RPM BHP  
1.60  
RPM BHP  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP  
3 HP Over-Sized Motor & Drive  
2720  
3060  
3400  
3740  
4080  
1011 1.92  
1070 2.35  
1128 2.84  
1186 3.40  
1239 3.99  
1036 2.04  
1094 2.48  
1152 2.99  
1210 3.56  
1267 4.20  
1059 2.15  
1117 2.61  
1176 3.14  
1233 3.73  
1291 4.39  
1082 2.27  
1139 2.75  
1198 3.29  
1256 3.90  
1104 2.39  
1161 2.88  
1219 3.43  
1278 4.06  
1127 2.51  
1182 3.01  
1241 3.58  
1298 4.22  
1149 2.64 1170 2.75 1191 2.88 1212 3.00  
1203 3.15 1222 3.27 1243 3.41 1262 3.54  
1261 3.73 1280 3.87 1299 4.02 1319 4.17  
1319 4.39  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3 HP Over-Sized Motor & Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo  
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors  
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Products Warranty  
Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500  
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475  
34  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-22 - Belt Drive Evaporator Fan Performance -YSC120AD*L - Low Heat - Downflow Configuration - (SI)  
External Static Pressure (Pascals)  
25  
50  
75  
100  
RPM  
2.24 Nom kW Standard Motor & Low Static Drive  
125  
RPM  
150  
RPM  
175  
RPM  
200  
RPM  
225  
RPM kW  
2.24 Nom kW Standard  
Motor & Drive  
250  
RPM kW  
m3/h  
RPM  
kW  
RPM  
kW  
RPM  
kW  
kW  
kW  
kW  
kW  
kW  
5440  
6120  
6800  
7480  
8160  
-
-
-
-
-
-
691  
751  
813  
876  
940  
0.66  
0.86  
1.11  
1.41  
1.75  
727  
784  
843  
905  
967  
0.75  
0.95  
1.21  
1.52  
1.88  
763  
816  
873  
932  
993  
0.85  
1.06  
1.31  
1.63  
2.00  
798  
848  
902  
959  
0.95  
1.17  
1.43  
1.74  
832  
879  
931  
985  
1.06  
1.29  
1.56  
863  
910  
959  
1.16  
1.41  
1.69  
895 1.27  
940 1.53  
986 1.82 1014 1.94  
924 1.39  
968 1.64  
717  
780  
845  
911  
0.77  
1.00  
1.29  
1.62  
746  
814  
883  
0.90  
1.17  
1.50  
1.87 1012 2.01 1037 2.14 1063 2.29  
1018 2.12  
1042 2.24 1067 2.38 1091 2.53 1115 2.68  
External Static Pressure (Pascals)  
375 400  
RPM RPM  
275  
RPM  
300  
RPM  
325  
RPM  
350  
RPM  
425  
RPM  
450  
RPM  
475  
RPM kW  
500  
RPM kW  
m3/h  
kW  
kW  
kW  
kW  
kW  
kW  
kW  
kW  
2.24 Nom kW Standard Motor & Drive  
5440  
6120  
6800  
7480  
8160  
952  
996  
1041 2.08  
1088 2.43  
1139 2.83  
1.50  
1.77  
979  
1.63  
1004 1.75  
1049 2.02  
1092 2.34  
1137 2.72  
1185 3.15  
1029 1.87  
1073 2.15  
1117 2.48  
1162 2.87  
1208 3.30  
1053 2.00  
1097 2.29  
1141 2.62  
1185 3.01  
1078 2.13  
1120 2.43  
1164 2.76  
1207 3.16  
1101 2.27 1124 2.41 1146 2.54 1169 3.59  
1142 2.56 1164 2.71 1186 2.85 1207 4.02  
1023 1.89  
1067 2.21  
1113 2.57  
1161 2.99  
1186 2.91 1208 3.06 1228 3.20  
-
-
-
-
-
-
1229 3.30  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2.24 Nom kW Standard Motor & High Static Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo  
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors  
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Products Warranty  
Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139  
Table PD-22a - Belt Drive Evaporator Fan Performance -YSC120AD*L - Low Heat - Downflow Configuration - (IP)  
External Static Pressure (Inches of Water)  
1.10  
1.20  
1.30  
1.40  
1.50  
1.60  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
3 HP Standard Motor & Low Static Drive  
3 HP Std Motor & Drive  
3200  
3600  
4000  
4400  
4800  
-
-
-
-
-
-
691  
751  
813  
876  
940  
0.88  
1.15  
1.49  
1.88  
2.35  
727  
784  
843  
905  
967  
1.00  
1.28  
1.62  
2.03  
2.52  
763  
816  
873  
932  
993  
1.14  
1.42  
1.76  
2.18  
2.68  
798  
848  
902  
959  
1.28  
1.57  
1.92  
2.34  
832  
879  
931  
985  
1.42  
1.73  
2.09  
863  
910  
959  
1.56  
1.89  
2.26  
895 1.71  
940 2.05  
986 2.43 1014 2.61  
924 1.86  
968 2.20  
717  
780  
845  
911  
1.03  
1.35  
1.73  
2.18  
746  
814  
883  
1.21  
1.57  
2.02  
2.51 1012 2.69 1037 2.88 1063 3.07  
1018 2.84  
1042 3.01 1067 3.20 1091 3.39 1115 3.59  
External Static Pressure (Inches of Water)  
1.10  
RPM BHP  
1.20  
RPM BHP  
1.30  
RPM BHP  
1.40  
RPM BHP  
1.50  
RPM BHP  
1.60  
RPM BHP  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP  
3 HP Standard Motor & Drive  
3200  
3600  
4000  
4400  
4800  
952  
996  
1041 2.79  
1088 3.26  
1139 3.80  
2.01  
2.37  
979  
2.18  
1004 2.34  
1049 2.71  
1092 3.14  
1137 3.64  
1185 4.22  
1029 2.51  
1053 2.68  
1097 3.07  
1141 3.51  
1185 4.04  
1078 2.86  
1120 3.25  
1164 3.7  
1207 4.23  
1101 3.04 1124 3.23 1146 3.41 1169 3.59  
1142 3.43 1164 3.63 1186 3.83 1207 4.02  
1023 2.53  
1067 2.96  
1113 3.45  
1161 4.00  
1073 2.88  
1117 3.33  
1162 3.84  
1208 4.43  
1186 3.90 1208 4.10 1228 4.30  
-
-
-
-
-
-
1229 4.43  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3 HP Standard Motor & High Static Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo  
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors  
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Products Warranty  
Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475  
RT-PRC017-EN  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-23 - Belt Drive Evaporator Fan Performance - YSC120AD*L - Horizontal Configuration (SI)  
External Static Pressure (Pascals)  
25  
50  
75  
100  
RPM  
2.24 Nom kW Standard Motor & Low Static Drive  
125  
RPM  
150  
RPM  
175  
RPM  
200  
RPM  
225  
RPM kW  
250  
RPM kW  
m3/h  
RPM  
kW  
RPM  
kW  
RPM  
kW  
kW  
kW  
kW  
kW  
kW  
2.24 Nom kW Standard Motor & Drive  
5440  
6120  
6800  
7480  
8160  
719  
799  
881  
963  
0.72  
1.00  
1.35  
1.78  
761  
836  
913  
992  
0.82  
1.11  
1.46  
1.89  
798  
872  
947  
1023 2.02  
1099 2.54  
0.91  
1.21  
1.58  
834  
904  
977  
1052 2.16  
1127 2.69  
1.01  
1.32  
1.70  
875  
936  
1006 1.82  
1079 2.28  
1154 2.83  
1.13  
1.43  
916  
972  
1035 1.94  
1106 2.41  
1179 2.97  
1.25  
1.56  
955  
1.38  
991  
1.50 1022 1.61 1050 1.72  
1009 1.70 1045 1.84 1079 1.98 1111 2.12  
1066 2.08 1100 2.23 1133 2.38 1165 2.54  
1132 2.54 1160 2.69 1189 2.85 1219 3.02  
1203 3.11 1227 3.25  
1045 2.29  
1072 2.41  
2.24 Nom kW Standard Motor & High Static Drive  
External Static Pressure (Pascals)  
375 400  
RPM RPM  
275  
RPM  
300  
RPM  
2.24 Nom kW Standard Motor & Drive  
325  
RPM  
350  
RPM  
425  
RPM  
450  
RPM  
475  
RPM kW  
500  
RPM kW  
m3/h  
kW  
kW  
kW  
kW  
kW  
kW  
kW  
kW  
5440  
6120  
6800  
7480  
8160  
1077 1.83  
1140 2.25  
1196 2.70  
1250 3.19  
1103 1.94  
1165 2.37  
1225 2.86  
1126 2.04  
1190 2.49  
1252 3.00  
1150 2.14  
1214 2.61  
1276 3.15  
1171 2.24  
1235 2.73  
1299 3.28  
1193 2.35  
1257 2.85  
1214 2.45 1233 2.55 1253 2.65 1274 3.46  
1279 2.97 1298 3.08 1317 3.19 1338 4.10  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2.24 Nom kW Standard Motor & High Static Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo  
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors  
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Products Warranty  
Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139  
Table PD-23a - Belt Drive Evaporator Fan Performance -YSC120AD*L - Horizontal Configuration - (IP)  
External Static Pressure (Inches of Water)  
1.10  
1.20  
1.30  
1.40  
1.50  
1.60  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
3 HP Standard Motor & Low Static Drive  
3 HP Standard Motor & Drive  
3200  
3600  
4000  
4400  
4800  
719  
799  
881  
963  
0.97  
1.35  
1.81  
2.39  
761  
836  
913  
992  
1.10  
1.48  
1.96  
2.54  
798  
872  
947  
1023 2.71  
1099 3.41  
1.22  
1.63  
2.12  
834  
904  
977  
1052 2.89  
1127 3.61  
1.35  
1.77  
2.28  
875  
936  
1006 2.44  
1079 3.06  
1154 3.80  
1.51  
1.91  
916  
972  
1035 2.60  
1106 3.23  
1179 3.98  
1.68  
2.09  
955  
1.85  
991  
2.01 1022 2.16 1050 2.31  
1009 2.28 1045 2.47 1079 2.66 1111 2.84  
1066 2.78 1100 2.99 1133 3.20 1165 3.41  
1132 3.41 1160 3.61 1189 3.82 1219 4.05  
1203 4.17 1227 4.36  
1045 3.07  
1072 3.23  
3 HP Standard Motor & High Static Drive  
External Static Pressure (Inches of Water)  
1.10  
1.20  
1.30  
1.40  
1.50  
1.60  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
3 HP Standard Motor & Drive  
3200  
3600  
4000  
4400  
4800  
1077 2.45  
1140 3.02  
1196 3.62  
1250 4.28  
1103 2.60  
1165 3.18  
1225 3.83  
1126 2.73  
1190 3.34  
1252 4.03  
1150 2.87  
1214 3.51  
1276 4.22  
1171 3.01  
1235 3.66  
1299 4.40  
1193 3.15  
1257 3.82  
1214 3.29 1233 3.42 1253 3.56 1274 3.71  
1279 3.98 1298 4.13 1317 4.28 1338 4.45  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3 HP Standard Motor & High Static Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo  
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors  
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Products Warranty  
Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475  
36  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-24 - Belt Drive Evaporator Fan Performance -YSC120AD*H - High Heat - Downflow Configuration - (SI)  
External Static Pressure (Pascals)  
25  
50  
75  
100  
RPM  
2.24 Nom kW Standard Motor & Low Static Drive  
125  
RPM  
150  
RPM  
175  
RPM  
200  
RPM  
225  
RPM kW  
2.24 Nom kW Standard  
Motor & Drive  
250  
RPM kW  
m3/h  
RPM  
kW  
RPM  
kW  
RPM  
kW  
kW  
kW  
kW  
kW  
kW  
5440  
6120  
6800  
7480  
8160  
-
-
-
-
723  
787  
854  
923  
992  
0.74  
0.96  
1.25  
1.59  
1.99  
759  
820  
883  
949  
0.84  
1.07  
1.36  
1.70  
793  
851  
913  
976  
0.94  
1.18  
1.48  
1.83  
827  
882  
941  
1003 1.96  
1066 2.38  
1.05  
1.30  
1.60  
860  
913  
969  
1.15  
1.42  
1.73  
891  
942  
997  
1.26  
1.54  
921 1.37  
971 1.66  
949 1.49  
999 1.78  
721  
793  
866  
939  
0.78  
1.04  
1.36  
1.75  
755  
824  
895  
967  
0.87  
1.15  
1.48  
1.87  
1.86 1024 1.99 1050 2.12  
1029 2.10 1054 2.24 1079 2.38 1104 2.53  
1090 2.52 1114 2.67 1138 2.83 1161 2.98  
1017 2.12  
1042 2.24  
External Static Pressure (Pascals)  
375 400  
RPM RPM  
275  
RPM  
300  
RPM  
325  
RPM  
350  
RPM  
425  
RPM  
450  
RPM  
475  
RPM kW  
500  
RPM kW  
m3/h  
kW  
kW  
kW  
kW  
kW  
kW  
kW  
kW  
2.24 Nom kW Standard Motor & Drive  
5440  
6120  
6800  
7480  
8160  
976  
1.61  
1001 1.73  
1052 2.03  
1101 2.39  
1153 2.81  
1207 3.30  
1027 1.86  
1076 2.17  
1126 2.53  
1176 2.96  
1051 1.99  
1100 2.30  
1149 2.67  
1200 3.11  
1075 2.12  
1122 2.44  
1172 2.81  
1222 3.26  
1098 2.25  
1145 2.58  
1194 2.96  
1120 2.38 1143 2.52 1166 2.66 1189 3.59  
1167 2.73 1188 2.87 1210 3.02 1230 4.02  
1025 1.90  
1076 2.26  
1129 2.67  
1184 3.14  
1216 3.12 1236 3.26  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2.24 Nom kW Standard Motor & High Static Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo  
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors  
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Products Warranty  
Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139  
Table PD-24a - Belt Drive Evaporator Fan Performance -YSC120AD*H - High Heat - Downflow Configuration - (IP)  
External Static Pressure (Inches of Water)  
1.10  
1.20  
1.30  
1.40  
1.50  
1.60  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
3 HP Standard Motor & Low Static Drive  
3 HP Standard Motor & Drive  
3200  
3600  
4000  
4400  
4800  
-
-
-
-
723  
787  
854  
923  
992  
0.99  
1.29  
1.67  
2.13  
2.67  
759  
820  
883  
949  
1.12  
1.44  
1.82  
2.28  
793  
851  
913  
976  
1.26  
1.59  
1.98  
2.45  
827  
882  
941  
1003 2.63  
1066 3.19  
1.40  
1.75  
2.15  
860  
913  
969  
1.55  
1.90  
2.32  
891  
942  
997  
1.69  
2.06  
921 1.84  
971 2.22  
949 2.00  
999 2.39  
721  
793  
866  
939  
1.04  
1.40  
1.83  
2.34  
755  
824  
895  
967  
1.17  
1.54  
1.98  
2.51  
2.50 1024 2.67 1050 2.85  
1029 2.81 1054 3.00 1079 3.20 1104 3.39  
1090 3.38 1114 3.58 1138 3.79 1161 4.00  
1017 2.84  
1042 3.01  
External Static Pressure (Inches of Water)  
1.10  
RPM BHP  
1.20  
RPM BHP  
1.30  
RPM BHP  
1.40  
1.50  
RPM BHP  
1.60  
RPM BHP  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
3 HP Standard Motor & Drive  
3200  
3600  
4000  
4400  
4800  
976  
2.16  
1001 2.32  
1052 2.73  
1101 3.20  
1153 3.77  
1207 4.42  
1027 2.49  
1076 2.90  
1126 3.40  
1176 3.97  
1051 2.66  
1075 2.84  
1122 3.27  
1172 3.77  
1222 4.37  
1098 3.02  
1145 3.46  
1194 3.97  
1120 3.19 1143 3.38 1166 3.57 1189 3.75  
1167 3.66 1188 3.85 1210 4.05 1230 4.25  
1025 2.55  
1076 3.03  
1129 3.58  
1184 4.21  
1100 3.09  
1149 3.58  
1200 4.17  
1216 4.18 1236 4.38  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3 HP Standard Motor & High Static Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo  
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors  
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Products Warranty  
Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475  
RT-PRC017-EN  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-25 - Belt Drive Evaporator Fan Performance - YSC120AD*H - High Heat - Horizontal Configuration (SI)  
External Static Pressure (Pascals)  
25  
50  
75  
100  
RPM  
125  
RPM  
150  
RPM  
175  
RPM  
200  
RPM  
225  
RPM kW  
250  
RPM kW  
m3/h  
2.24 Nom kW Standard Motor & Low Static Drive  
RPM  
kW  
RPM  
kW  
RPM  
kW  
kW  
kW  
kW  
kW  
kW  
2.24 Nom kW Standard Motor & Drive  
1.52 1028 1.64 1055 1.74 1082 1.85  
5440  
6120  
6800  
7480  
8160  
768  
856  
943  
0.84  
1.16  
1.57  
805  
888  
973  
0.93  
1.27  
1.68  
842  
921  
1.03  
1.37  
884  
955  
1.15  
1.49  
924  
992  
1.28  
1.63  
962  
1.40  
998  
1028 1.77  
1096 2.21  
1167 2.73  
1243 3.36  
1063 1.91 1096 2.05 1126 2.19 1153 2.31  
1129 2.36 1161 2.52 1192 2.68 1222 2.84  
1198 2.90 1228 3.07 1257 3.24  
1002 1.80  
1086 2.32  
1171 2.93  
1031 1.92  
1113 2.45  
1195 3.07  
1062 2.06  
1139 2.57  
1219 3.21  
1031 2.06  
1119 2.58  
1060 2.19  
1146 2.79  
-
-
-
-
-
-
-
-
-
-
2.24 Nom kW Standard Motor & High Static Drive  
External Static Pressure (Pascals)  
375 400  
RPM RPM  
275  
RPM  
300  
RPM  
325  
RPM  
350  
RPM  
425  
RPM  
450  
RPM kW  
475  
RPM kW  
500  
RPM kW  
m3/h  
kW  
kW  
kW  
kW  
kW  
kW  
kW  
2.24 Nom kW Standard Motor & Drive  
5440  
6120  
6800  
7480  
8160  
1107 1.95  
1178 2.43  
1249 2.99  
1131 2.06  
1202 2.55  
1273 3.13  
1154 2.16  
1224 2.67  
1296 3.26  
1176 2.27  
1247 2.79  
1197 2.37  
1268 2.91  
1218 2.47  
1288 3.02  
1238 2.58 1257 2.68 1276 2.78 1296 3.59  
1308 3.14 1328 3.26  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2.24 Nom kW Standard Motor & High Static Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo  
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors  
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Products  
Warranty Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139  
Table PD-25a - Belt Drive Evaporator Fan Performance -YSC120AD*H - High Heat - Horizontal Configuration - (IP)  
External Static Pressure (Inches of Water)  
1.10  
1.20  
1.30  
1.40  
1.50  
1.60  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
3 HP Standard Motor & Low Static Drive  
3 HP Standard Motor & Drive  
3200  
3600  
4000  
4400  
4800  
768  
856  
943  
1031 2.76  
1119 3.45  
1.12  
1.56  
2.10  
805  
888  
973  
1060 2.94  
1146 3.74  
1.25  
1.70  
2.26  
842  
921  
1002 2.41  
1086 3.11  
1171 3.93  
1.38  
1.84  
884  
955  
1031 2.58  
1113 3.28  
1195 4.11  
1.54  
2.00  
924  
992  
1062 2.76  
1139 3.45  
1219 4.30  
1.71  
2.19  
962  
1.88  
998  
2.04 1028 2.19 1055 2.34 1082 2.48  
1028 2.37  
1096 2.96  
1167 3.66  
1243 4.50  
1063 2.57 1096 2.75 1126 2.93 1153 3.10  
1129 3.17 1161 3.38 1192 3.59 1222 3.81  
1198 3.89 1228 4.11 1257 4.34  
-
-
-
-
-
-
-
-
-
-
3 HP Standard Motor & High Static Drive  
External Static Pressure (Inches of Water)  
1.10  
1.20  
1.30  
1.40  
1.50  
1.60  
1.70  
1.80  
1.90  
2.00  
CFM  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP  
RPM BHP RPM BHP RPM BHP RPM BHP  
3 HP Standard Motor & Drive  
3200  
3600  
4000  
4400  
4800  
1107 2.62  
1178 3.27  
1249 4.01  
1131 2.76  
1202 3.42  
1273 4.19  
1154 2.90  
1224 3.58  
1296 4.38  
1176 3.04  
1247 3.74  
1197 3.17  
1268 3.90  
1218 3.32  
1288 4.05  
1238 3.46 1257 3.59 1276 3.73 1296 3.87  
1308 4.21 1328 4.37  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3 HP Standard Motor & High Static Drive  
Notes:  
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed AndTestedTo  
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors  
As Shown In OurTabular Data Will Not Result In NuisanceTripping Or Premature Motor Failure. Our Products Warranty  
Will Not Be Affected.  
Data Includes Pressure Drop DueTo Wet Coils And Filters.  
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475  
38  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-26 - Standard Motor & Sheave/Fan Speed (RPM)  
Unit  
6 Turns  
Open  
N/A  
N/A  
N/A  
859  
786  
894  
5 Turns  
Open  
1036  
698  
806  
913  
4 Turns  
Open  
1105  
751  
860  
967  
3 Turns  
Open  
1174  
806  
913  
1021  
934  
2 Turns  
Open  
1243  
859  
968  
1075  
982  
1 Turns  
Open  
1312  
913  
1022  
1129  
1032  
1174  
Model No.  
YSC060AD  
YSC072ADRL  
YSC072ADRH  
YSC090AD  
YSC102AD  
YSC120AD  
Closed  
1381  
967  
1074  
N/A  
836  
950  
885  
1006  
N/A  
N/A  
1062  
1118  
Factory set at 3 turns open  
Table PD-27 - Standard Motor & Low Static Drive Accessory Sheave/Fan Speed (RPM)  
Unit  
6 Turns  
Open  
N/A  
N/A  
N/A  
5 Turns  
Open  
691  
537  
671  
4 Turns  
Open  
760  
590  
714  
3 Turns  
Open  
829  
644  
757  
2 Turns  
Open  
898  
698  
800  
1 Turns  
Open  
967  
752  
843  
Model No.  
YSC060AD  
YSC072ADRL  
YSC090AD  
YSC102AD  
YSC120AD  
Closed  
1036  
806  
886  
811  
N/A  
N/A  
629  
717  
664  
754  
701  
799  
737  
844  
773  
885  
922  
Factory set at 3 turns open  
Table PD-28 - Standard Motor & High Static Drive Accessory Sheave/Fan Speed (RPM)  
Unit  
6 Turns  
Open  
N/A  
N/A  
1020  
936  
5 Turns  
Open  
1243  
967  
1073  
981  
4 Turns  
Open  
1311  
1021  
1127  
1032  
1174  
3 Turns  
Open  
1379  
1075  
1181  
1083  
1229  
2 Turns  
Open  
1450  
1128  
1235  
1134  
1285  
1 Turns  
Open  
1515  
1183  
1289  
1182  
1341  
Model No.  
YSC060AD  
YSC072AD  
YSC090AD  
YSC102AD  
YSC120AD  
Closed  
1588  
1235  
N/A  
N/A  
N/A  
1062  
1118  
Factory set at 3 turns open  
Table PD-29 - Oversized Motor & Drive Sheave/Fan Speed (RPM)  
Unit  
6 Turns  
Open  
N/A  
1112  
N/A  
5 Turns  
Open  
967  
1182  
971  
4 Turns  
Open  
1021  
1252  
1041  
N/A  
3 Turns  
Open  
1075  
1322  
1111  
N/A  
2 Turns  
Open  
1128  
1392  
1181  
N/A  
1 Turns  
Open  
1183  
1460  
1251  
N/A  
Model No.  
YSC072AD  
YSC090AD  
YSC102AD  
YSC120AD  
Closed  
1235  
N/A  
1321  
N/A  
N/A  
N/A  
Factory set at 3 turns open  
Table PD-30 - Sound Power Level - dB (ref. 10 -12 Watts)  
Unit  
Octave  
63  
Overall  
dBA  
80  
85  
85  
Model No.  
YSC060AD  
YSC072AD  
YSC090AD  
YSC102AD  
YSC120AD  
Note:  
125  
91  
90  
90  
89  
86  
250  
79  
86  
86  
84  
80  
500  
77  
82  
83  
81  
77  
1000  
74  
79  
80  
77  
2000  
71  
75  
75  
72  
4000  
8000  
63  
63  
64  
62  
84  
83  
83  
83  
68  
70  
71  
69  
66  
83  
79  
83  
73  
69  
60  
Tests follow ARI 270-95  
RT-PRC017-EN  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-31 - Static Pressure Drops Through Accessories - (Pascals)  
Economizer with  
OA/RA Dampers2  
100% RA 100% OA  
Downflow Horizontal  
30  
Unit  
Model No.  
YSC060AD  
Airflow  
(m3/h)  
2720  
3400  
4080  
3260  
4080  
4890  
4080  
5100  
6120  
4620  
5780  
6930  
5440  
6800  
8160  
Standard Pleated Filters 100% OA  
100% RA  
Filters1  
25  
(50 mm)  
37  
55  
72  
17  
22  
30  
22  
32  
45  
20  
27  
40  
25  
37  
50  
30  
46  
64  
25  
27  
33  
27  
35  
52  
31  
47  
75  
42  
65  
85  
11  
4
6
9
5
5
10  
5
12  
20  
10  
15  
22  
12  
20  
25  
37  
55  
10  
15  
22  
15  
25  
35  
12  
20  
30  
17  
27  
40  
17  
26  
2
46  
64  
15  
20  
25  
20  
30  
62  
22  
45  
77  
35  
75  
87  
YSC072AD  
YSC090AD  
YSC102AD  
YSC120AD  
Notes:  
5
10  
5
12  
17  
7
15  
17  
12  
17  
22  
1. Tested with standard filters. TheYSC060AD has 25 mm (1 inch) standard fiters.  
The YSC072AD - 120AD has 50 mm (2 inch) standard filters.  
The difference in pressure drop should be considered when utilizing optional 50 mm (2 inch) pleated filters.  
2. OA = Outside Air and RA = Return Air  
3. Nominal kW ratings at 380 V  
Table PD-31a - Static Pressure Drops Through Accessories - (Inches of Water Column)  
Economizer with  
OA/RA Dampers2  
Unit  
Model No.  
YSC060AD  
Airflow  
(CFM)  
1600  
2000  
2400  
1920  
2400  
2880  
2400  
3000  
3600  
2720  
3400  
4080  
3200  
4000  
4800  
Standard Pleated Filters 100% OA  
100% RA  
100% OA  
100% RA  
Filters1  
0.10  
0.15  
0.22  
0.04  
0.06  
0.09  
0.06  
0.10  
0.14  
0.05  
0.08  
0.12  
0.07  
0.11  
0.16  
(2 inch)  
0.15  
0.22  
0.29  
0.07  
0.09  
0.12  
0.09  
0.13  
0.18  
0.08  
0.11  
0.16  
0.10  
0.15  
0.20  
Downflow  
Horizontal  
0.12  
0.18  
0.26  
0.10  
0.11  
0.13  
0.11  
0.14  
0.21  
0.12  
0.19  
0.30  
0.17  
0.26  
0.34  
0.04  
0.07  
0.10  
0.01  
0.02  
0.04  
0.02  
0.05  
0.07  
0.03  
0.06  
0.07  
0.05  
0.07  
0.09  
0.12  
0.18  
0.26  
0.06  
0.08  
0.10  
0.08  
0.12  
0.25  
0.09  
0.18  
0.31  
0.14  
0.30  
0.35  
0.01  
0.02  
0.04  
0.02  
0.02  
0.04  
0.02  
0.05  
0.08  
0.04  
0.06  
0.09  
0.05  
0.08  
0.10  
YSC072AD  
YSC090AD  
YSC102AD  
YSC120AD  
Notes:  
1. Tested with standard filters. TheYSC060AD has 25 mm (1 inch) standard fiters.  
The YSC072AD - 120AD has 50 mm (2 inch) standard filters.  
The difference in pressure drop should be considered when utilizing optional 50 mm (2 inch) pleated filters.  
2. OA = Outside Air and RA = Return Air  
3. Nominal kW ratings at 380 V  
40  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-32 — Gas-Fired Heating Capacities for G20,G25, and G31  
Unit  
Model No.  
Furnace  
Model  
G80  
Heating Input  
Input kW Input MBH Output kW  
Heating Output  
Output MBH  
YSC060*DRL  
YSC060*DRH  
YSC072*DRL  
YSC072*DRH  
YSC090*DRL  
YSC090*DRH  
YSC102*DRL  
YSC102*DRH  
YSC120*DRL  
YSC120*DRH  
19.6  
29.3  
29.3  
48.9  
29.3  
48.9  
36.7  
60.9  
36.7  
60.9  
67  
15.7  
23.4  
23.4  
39.1  
23.4  
39.1  
29.3  
48.7  
29.3  
48.7  
54  
80  
80  
134  
80  
134  
100  
166  
100  
166  
G120  
G120  
G200  
G120  
G200  
G150  
G250  
G150  
G250  
100  
100  
167  
100  
167  
125  
208  
125  
208  
Ratings shown are for elevations up to 2,000 ft. For higher elevations, reduce ratings at a rate of 4% per 1,000  
ft. elevation.  
RT-PRC017-EN  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Zone Controls  
Non-Programmable Manual Auto  
Changeover with Digital LCD Display —  
Auto, heat, cool or off mode selection  
button. Auto or off fan button. Status  
indication LCD indicators - System  
on,heat, cool, or service.  
Zone Sensors  
Conventional Thermostats  
Zone Sensors are the building  
Conventional Thermostats are the  
building occupants comfort control  
devices when a generic thermostat is  
desired.  
occupants comfort control devices for  
Precedentunits with ReliaTelcontrol:  
Manual Changeover — Heat, Cool or Off  
System Switch. Fan Auto or Off Switch.  
One temperature  
Manual Changeover — One Heat, One  
Cool Thermostat. Heat, Cool or Off  
System Switch.  
setpoint lever.  
Fan Auto or On  
Switch. Set Point  
Dial. Adjustable  
Heat Anticipator.  
Automatic Changeover — One Heat,  
Two CoolThermostat. Off, Auto System  
Switch. Auto/On Fan Switch.  
Programmable Night Setback — Auto or  
manual changeover with seven-day  
programming. Keyboard selection of  
Heat, Cool, Fan, Auto, or On. All  
Manual/Automatic Changeover — Auto,  
Heat, Cool or Off System Switch. Fan  
Auto or Off Switch. Two temperature  
setpoint levers.  
Optional Status  
Indication LED  
lights, System On,  
Heat, Cool, or  
Service.  
Programmable Electronic Night Setback  
Thermostat — Heating setback and  
cooling setup with 7-day, programming  
capability. Available in two-stage  
heating/cooling or one-stage heating/  
cooling versions with automatic  
changeover.  
programmable sensors have System  
On, Heat, Cool, Service LED/indicators as  
standard. Night Setback Sensors have  
one (1) Occupied, one (1) Un-occupied,  
and two (2) Override programs per day.  
Integrated ComfortSystem —  
Sensor(s) available with optional  
temperature  
Remote Sensor —  
Sensor(s) available for all zone sensors  
to provide remote  
sensing  
capabilities.  
adjustment and  
override  
buttons to  
provide central  
control through  
a Trane  
Integrated  
Comfort™  
system.  
42  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
Table ED-1 — Unit Wiring  
Standard Indoor Fan Motor  
Oversized Indoor Fan Motor  
Unit  
Minimum  
Maximum Fuse  
Minimum  
Maximum Fuse  
Unit  
Operating  
Voltage Range  
342-456  
Circuit  
Ampacitiy  
17.7  
23.2  
24.8  
Size Or Maximum  
Circuit  
Ampacitiy  
17.7  
24.2  
26.5  
Size Or Maximum  
Model No.  
YSC060ADR  
YSC072ADR  
YSC090ADR  
YSC102ADR  
YSC120ADR  
Circuit Breaker1  
Circuit Breaker1  
25  
35  
35  
35  
40  
25  
35  
35  
35  
40  
342-456  
342-456  
342-456  
342-456  
26.8  
31.2  
28.5  
31.2  
Notes:  
1. All units to be installed under local codes  
Table ED-2 — Electrical Characteristics - Evaporator Fan Motor - 50 Hz  
Standard Evaporator Fan Motor  
Oversized Evaporator Fan Motor  
Unit  
Amps  
Amps  
Model No.  
YSC060AD  
YSC072AD  
YSC090AD  
YSC102AD  
YSC120AD  
No.  
1
1
1
1
Volts  
Phase  
HP  
1.5  
1.5  
2.0  
2.0  
3.0  
FLA  
4.3  
4.3  
5.3  
5.3  
7.0  
LRA  
25.3  
25.3  
36.4  
36.4  
57.0  
No.  
Volts  
-
380-415  
380-415  
380-415  
-
Phase  
-
3
3
3
-
HP  
-
2.0  
3.0  
3.0  
-
FLA  
-
5.3  
7.0  
7.0  
-
LRA  
-
36.4  
57.0  
57.0  
-
380-415  
380-415  
380-415  
380-415  
380-415  
3
3
3
3
3
-
1
1
1
-
1
Table ED-3 — Electrical Characteristics - Compressor Motor and Condenser Motor - 50 Hz  
Compressor Motor  
Condenser Fan Motor  
Unit  
Amps  
Amps  
1
Model No.  
YSC060AD  
YSC072AD  
YSC090AD  
YSC102AD  
YSC120AD  
No.  
1
1
1
2
Volts  
Phase  
HP  
RPM  
2875  
2875  
2875  
2875  
2875  
RLA1  
9.5  
12.7  
13.2  
9.3 / 6.9  
9.9 / 8.5  
LRA1  
74.00  
95.00  
100.00  
No.  
Phase  
HP  
FLA  
1.9  
2.8  
2.8  
2.8  
2.8  
LRA  
2.8  
7.1  
7.1  
7.1  
380-415  
380-415  
380-415  
380-415  
380-415  
3
3
3
3
3
5.7  
7.5  
8.3  
6.0 / 3.8  
6.0 / 4.8  
1
1
1
1
1
1
1
1
1
1
0.40  
0.75  
0.75  
0.75  
0.75  
74.0 / 48.0  
74.0 / 61.8  
2
7.1  
Note:  
1. Comp1/Comp2  
Table ED-4 Electrical Characteristics - Inducer Motor  
Model No.  
YSC060-090*DRL  
YSC060*DRH  
YSC102-120*DRL  
YSC072-120*DRH  
Heat  
Low  
High  
Low  
High  
Heating Stages  
Watts  
21  
HP  
RPM  
2525  
Volts  
Phase  
LRA  
1
1/35  
1/15  
208-230  
1
1
0.6  
2
50  
2800/2550  
208-230  
0.45  
RT-PRC017-EN  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Jobsite  
Connections  
Typical Number Of Wires  
Zone Sensors  
DISCONNECT  
SWITCH  
(BY OTHERS)  
A — Manual Changeover  
Manual/Auto Changeover  
Manual/Auto Changeover with  
Status Indication LEDs  
4
5
ZONE SENSOR  
OR THERMOSTAT  
10  
7
Programmable Night Setback with  
Status Indication LEDs  
ROOFTOP  
UNIT  
Thermostats  
A — 4 wires, 24-volts  
B — 3 Power Wires + 1 Ground Wire (three phase)  
2 Power Wires + 1 Ground Wire (single phase)  
For specific wiring information, see the installation instructions.  
All wiring except power wires is low voltage.  
All customer supplied wiring to be copper and must conform to NEC or CEC and local electrical codes. Wiring shown dotted is to be furnished and installed by the customer.  
44  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
YSC060  
All dimensions are in inches/millimeters.  
YSC060  
RT-PRC017-EN  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
YSC060  
All dimensions are in inches/millimeters  
YSC060 — Downflow Airflow Supply and  
Return  
YSC060 — Horizontal Airflow Supply and  
Return  
YSC060 — Unit Clearance and Roof Opening  
46  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
YSC060  
All dimensions are in inches/millimeters.  
YSC060 — Roof Curb  
YSC060 — Downflow Duct Connections —  
Field Fabricated  
RT-PRC017-EN  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
YSC072-120  
All dimensions are in inches/millimeters.  
YSC072 and YSC090  
YSC102 and YSC120  
48  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
YSC072-120  
All dimensions are in inches/millimeters.  
YSC072-120 — Downflow Airflow Supply and Return  
YSC072-120 — Horizontal Airflow Supply and  
Return  
YSC072-120 — Unit Clearance and Roof  
Opening  
RT-PRC017-EN  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
YSC072-120  
All dimensions are in inches/millimeters.  
YSC072-120 — Roof Curb  
YSC072-120 — Downflow Duct Connections —  
Field Fabricated  
ALL FLANGES 1 1/4” (31 MM)  
50  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional YSC060 Options/  
Data Accessories  
YSC060 — Economizer, Manual, or Motorized  
Damper Hood  
YSC060 — Barometric Relief Damper Hood  
YSC060 — Swing Diameter for Hinged  
Door(s) Option  
See Page 42 for Through the Base Utilities Information  
RT-PRC017-EN  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional YSC072-120  
Data  
Options/Accessories  
YSC072-120 — Economizer and Barometric  
Relief Damper Hoods  
YSC072-120 — Swing Diameter for Hinged  
Door(s) Option  
52  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Weights  
Table W-1 - Maximum Unit and Corner Weights and Center of Gravity Dimensions (SI)  
MaximumWeights(2) (kg)  
Corner Weights(1) (kg)  
Center of Gravity (mm)  
Unit  
Model No.  
YSC060AD  
YSC072AD  
YSC090AD  
YSC102AD  
YSC120AD  
Shipping(2)  
295  
Net(2)  
260  
350  
419  
434  
481  
A
81  
113  
139  
141  
155  
B
64  
90  
110  
114  
126  
C
D
62  
83  
95  
100  
111  
Length  
810  
990  
970  
1020  
1020  
Width  
510  
560  
530  
560  
54  
64  
75  
79  
89  
398  
466  
482  
528  
560  
Notes:  
(1) Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support.  
(2) Weights are approximate.  
Table W-1a - Maximum Unit and Corner Weights and Center of Gravity Dimensions (IP)  
MaximumWeights (lbs)  
Corner Weights(1) (lbs)  
Center of Gravity (in)  
Unit  
Model No.  
YSC060AD  
YSC072AD  
YSC090AD  
YSC102AD  
YSC120AD  
Shipping(2)  
651  
877  
1028  
1062  
1165  
Net  
574  
772  
923  
957  
1060  
A
B
C
D
Length  
32  
39  
38  
40  
Width  
179  
249  
306  
310  
342  
140  
198  
243  
252  
277  
119  
141  
165  
175  
197  
136  
184  
210  
220  
245  
20  
22  
21  
22  
22  
40  
Notes:  
(1) Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support.  
(2) Weights are approximate.  
Table W-2 - Accessory Net Weights(1) (2) (kg)  
Table W-2a - Accessory Net Weights(1) (2) (lbs)  
Net Weights(2)  
YSC072-120  
Net Weights(2)  
Accessory(3)  
YSC060  
Accessory(3)  
YSC060  
YSC072-120  
Economizer  
12  
3
9
7
32  
2
5
5
7
16  
5
14  
12  
52  
4
9
5
14  
Economizer  
26  
7
20  
16  
70  
5
12  
10  
15  
36  
10  
30  
26  
115  
8
20  
12  
30  
Barometric Relief  
Motorized Outside Air Damper  
Manual Outside Air Damper  
Roof Curb  
Oversized Motor  
Coil Guards  
Barometric Relief  
Motorized Outside Air Damper  
Manual Outside Air Damper  
Roof Curb  
Oversized Motor  
Coil Guards  
Hinged Doors  
Electric Heaters  
Hinged Doors  
Electric Heaters  
Notes:  
Notes:  
(1) Weights for options not listed are < 3 kg.  
(1) Weights for options not listed are < 5 lbs.  
(2) Net weight should be added to unit weight when ordering factory-installed  
accessories.  
(3) Some accessories not available on all units.  
2) Net weight should be added to unit weight when ordering factory-installed  
accessories.  
(3) Some accessories not available on all units.  
RT-PRC017-EN  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical  
Specifications  
General  
UnitTop  
Evaporator And Condenser Coils  
Internally finned, 8 mm (5/16”) copper  
tubes mechanically bonded to a  
Units shall be convertible airflow.  
Operating range in cooling shall be  
between 46°C and -18°C (115°F and 0°F)  
cooling as standard from the factory for  
all units. All units shall be factory  
assembled, internally wired, fully  
charged with R-22, and 100 percent run-  
tested before leaving the factory. Wiring  
internal to the unit shall be colored and  
numbered for simplified identification.  
The top cover shall be one piece  
construction or, where seams exist, it  
shall be double-hemmed and gasket-  
sealed. The ribbed top adds extra  
strength and prevents water from  
pooling on unit top.  
configured aluminum plate fin shall be  
standard. Coils shall be leak tested at the  
factory to ensure pressure integrity.The  
evaporator coil and condenser coil shall  
be leak tested to 1375 kPa (200 psig) and  
pressure tested to 3100 kPa (450 psig).  
The condensate coil shall have a patent  
pending 1 +1+1hybrid design with slight  
gaps for ease of cleaning. A removeable,  
reversible, double-sloped condensate  
drain pan is standard. Provision for  
through the base condensate drain is  
standard.  
Filters  
25 mm (1 inch), throwaway filters shall  
be standard on all 5 ton units.. The filter  
rack can be converted to two inch  
capability. 50 mm (2 inch) filters shall be  
factory supplied on all 6-10 ton units.  
Optional two inch pleated filters shall be  
available.  
Casing  
Unit casing shall be constructed of zinc  
coated, heavy gauge, galvanized steel.  
Exterior surfaces shall be cleaned,  
phosphatized, and finished with a  
weather-resistant baked enamel finish.  
Cabinet construction shall allow for all  
maintenance on one side of the unit.  
Service panels shall have lifting handles  
and be removed and reinstalled by  
removing only a single fastener while  
providing a water and air tight seal. All  
exposed vertical panels and top covers  
in the indoor air section shall be  
Gas Heating Section  
The heating section shall have a  
Compressors  
All units shall have direct-drive,  
progressive tubular heat exchanger  
design using stainless steel burners and  
corrosion resistant steel throughout. An  
induced draft combustion blower shall be  
used to pull the combustion products  
through the firing tubes.The heater shall  
use a direct spark ignition (DSI) system.  
On initial call for heat, the combusiton  
blower shall purge the heat exchanger  
for 20 seconds before ignition After three  
unsuccessful ignition attempts, the entire  
heating system shall be locked out until  
manually reset at the thermostat/zone  
sensor. Units shall be suitable for use with  
natural gas or propane (field-installed kit).  
hermetic, scroll type compressors with  
centrifugal type oil pumps. Motor shall  
be suction gas-cooled and shall have a  
voltage utilization range of plus or minus  
10 percent of unit nameplate voltage.  
Internal overloads shall be provided with  
the scroll compressors. Low and high  
pressure switches shall be standard.  
insulated with a cleanable foil faced, fire-  
retardent permanent, odorless glass  
fiber material. The base of the unit shall  
be insulated with 13 mm, 16 kg (1/2 inch,  
1 pound) density foil-faced, closed-cell  
material. All insulation edges shall be  
either captured or sealed.The units base  
pan shall have no penetrations within  
the perimeter of the curb other than the  
raised 29 mm (11/8 inch) high downflow  
supply/return openings to provide an  
added water integrity precaution, if the  
condensate drain backs up. The base of  
the unit shall have provisions for forklift  
and crane lifting, with forklift capabilities  
on three sides of the unit.  
Refrigerant Circuits  
Service pressure ports, and refrigerant  
line filter driers shall be factory-installed  
as standard. An area shall be provided  
for replacement suction line driers.  
Outdoor Fans  
The outdoor fans shall be direct-drive,  
statically and dynamically balanced,  
draw-through in the vertical discharge  
position.The fan motor shall be  
permanently lubricated and shall have  
built-in thermal overload protection.  
54  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical  
Specifications  
Indoor Fan  
Manual Outside Air Damper  
Factory or field-installed rain hood and  
screen shall provide up to 50 percent  
outside air.  
Accessories/Options  
Roof Curb  
All units shall have belt drive motors.  
Units with belt drive motors shall have  
an adjustable idler-arm assembly for  
quick-adjustment to fan belts and motor  
sheaves. All motors shall be thermally  
protected. Oversized motors shall be  
available for high static operations.  
The roof curb shall be designed to mate  
with the units downflow supply and  
return openings and provide support and  
a watertight installation when installed  
properly.The roof curb design shall allow  
field-fabricated rectangular supply/return  
ductwork to be connected directly to the  
curb. Curb shall be shipped knocked down  
for field assembly and shall include wood  
nailer strips.  
Oversized Motors  
Factory or field-installed oversized  
motors shall be available for high static  
applications.  
Controls  
Discharge Air Sensing  
Unit shall be completely factory wired  
with necessary controls and contactor  
pressure lugs or terminal block for  
power wiring. Unit shall have single  
point power entry as standard. Units  
shall provide an external location for  
mounting a fused disconnect device.  
This factory or field option provides true  
discharge air sensing in heating models.  
This sensor is a status indicator readable  
throughTracerorTracker.  
Economizer  
This accessory shall be either field or  
factory-installed and is available with or  
without barometric relief.The assembly  
includes fully modulating 0-100 percent  
motor and dampers, minimum position  
setting, preset linkage, wiring harness  
with plug, spring return actuators and  
fixed dry bulb control. Optional solid state  
enthalpy and differential enthalpy control  
shall be either factory or field-installed.  
The factory-installed economizer arrives  
in the shipping position and shall be  
moved to the operating position by the  
installing contractor.  
Coil Guards  
Hail protection quality coil guards shall be  
either factory or field-installed for  
condenser coil protection.  
Microprocessor controls provide for all  
24 volt control functions. With the  
microprocessor controls, the resident  
control algorithms shall make all  
heating, cooling, and/or ventilating  
decisions in response to electronic  
signals from sensors measuring indoor  
and outdoor temperatures. The control  
algorithm maintains accurate  
temperature control, minimizes drift  
from set point, and provides better  
building comfort. A centralized Micro-  
processor shall provide anti-short cycle  
timing and time delay between  
Fan Failure/Clogged Filter Switches  
These factory or field-installed options  
allow for individual fan failure and dirty  
filter indication.The fan failure switch will  
disable all unit functions and “flash” the  
Service LED on the zone sensor.The dirty  
filter switch will light the Service LED on  
the zone sensor and will allow continued  
unit operation.  
High Pressure Cutout  
All units have High Pressure cutout as  
standard.  
Phase Monitor  
Phase monitor shall provide 100%  
protection for motors and compressors  
against problems caused by phase loss,  
phase imbalance, and phase reversal.  
Phase monitor is equipped with an LED  
that provides an ON or FAULT indicator.  
compressors to provide a higher level of  
machine protection.  
Hinged Access Doors  
Sheet metal hinges are available factory-  
installed on the Filter/Evaporator Access  
Door, Indoor Fan/Heat Exchanger Door,  
and the Compressor/Control Access  
Door.  
Remote Potentiometer  
Field-installed, the minimum position  
setting of economizer shall be adjusted  
with this accessory.  
Black Epoxy Coated Condenser Coil  
The coil provides corrosion protection to  
condenser coils for seacoast application.  
The protection is a factory applied  
thermoset vinyl coating, bonded to  
normal aluminum fin stock.The uniform  
thickness of the bonded vinyl layer  
exhibits excellent corrosion protection in  
salt spray tests.  
Motorized Outside Air Dampers  
Factory or field-installed manually set  
outdoor air dampers shall provide up to  
50 percent outside air. Once set, outdoor  
air dampers shall open to set position  
when indoor fan starts.The damper shall  
close to the full closed position when  
indoor fan shuts down.  
RT-PRC017-EN  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical  
Specifications  
Reference Enthalpy Control  
Control Options  
Replaces the dry bulb control with a wet  
bulb changeover controller which has a  
fully adjustable setpoint. Enthalpy control  
offers a higher level of comfort control,  
along with energy savings potential, than  
the standard dry bulb control. This is due  
to the additional wet bulb sensing  
capability.This option shall be available  
for all units. It can be field-installed or  
factory-installed with the factory-installed  
economizer.  
Comm-3/4Trane Communication  
Interface  
This factory or field-installed option shall  
be provided to interface microprocessor  
controlled units with theTrane Integrated  
Comfortsystems.  
Comm-5 LonTalk Communication  
Interface  
This factory or field-installed option shall  
be provided to allow the unit to  
communicate as aTrane Comm-5 device  
or directly with generic LonTalk Network  
Building Automation System Controls.  
Differential Enthalpy Control  
Replaces the standard dry bulb control  
with two enthalpy sensors that compare  
total heat content of the indoor air and  
outdoor air to determine the most  
Zone Sensor  
Field-installed, this accessory shall be  
provided to interface with the Micro  
equipped units and shall be available in  
either manual, automatic programmable  
with night setback, with system  
malfunction lights or remote sensor  
options.  
efficient air source.This control option  
offers the highest level of comfort control,  
plus energy efficiency, available.This  
option shall be available for all units. It can  
be field-installed or factory-installed with  
the factory-installed economizer.  
Thermostats  
LowAmbient Cooling  
Two stage heating and cooling operation  
or one stage heating and cooling shall be  
available, for field installation, in either  
manual or automatic changeover.  
Automatic programmable electronic with  
night set back shall also be available.  
All microprocessor units shall have  
cooling capabilities down to -18°C (0°F) as  
standard.  
56  
RT-PRC017-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Literature Order Number  
File Number  
RT-PRC017-EN  
PL-UN-000-RT-PRC017-EN-02-04  
PL-UN-000-RT-PRC017-EN-12-03  
03-03Webb/Mason 02-04 Electronic Only  
Supersedes  
Trane  
A business of American Standard Companies  
Stocking Location  
For more information, contact your local district  
office or e-mail us at [email protected]  
Trane has a policy of continuous product and product data improvement and reserves the right to change design  
and specifications without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Tektronix Door 140 User Manual
Telex Intercom System US2002 User Manual
TOA Electronics Car Amplifier VM 2120 User Manual
Toshiba Computer Drive MG03ACA300 User Manual
Traulsen Appliance Trim Kit RET132EUT User Manual
Troy Bilt Tiller 12174 User Manual
Ultra electronic Printer Latin Series User Manual
Uniden Answering Machine 7500AI User Manual
Uniden Cordless Telephone XC630 User Manual
VTech Cordless Telephone VT 2420 User Manual