MEDIUM VOLTAGE CONTROLLERS  
JK400 Series  
Toshiba's JK400 series complies with EEMAC,  
NEMA, UL and CSA standards and is available in  
non-reversing and reversing full voltage, autotrans-  
former, reactor, multi-speed, synchronous and  
wound rotor configurations. Latched contactors  
are also available.  
The JK400 series is available in the following  
enclosed ratings:  
360 amps  
2300-6600 Volts  
Up to 5,000 HP  
Current Rating  
Maximum  
Maximum Continuous Amperes*  
90" One-High Controller or Lower  
Controller in a Two-High Stacking Upper Controller in a Two-High  
Maximum Continuous  
Amperes*  
Continuous  
Amperes*  
46" and 61"  
One-High Controller  
360  
Enclosure Type  
Arrangement  
Stacking Arrangement  
Type 1 Ventilated  
Type 1 Non-Ventilated  
Type 12, 3, 3R  
360  
320  
310  
320  
280  
280  
320  
310  
* Actual limits based on your specific application parameters. All specifications subject to change without notice.  
Short Circuit & Withstand Capability  
Interrupting  
Capacity  
(Symmetrical  
Amperes)  
Interrupting  
Capacity  
(Symmetrical 30 Seconds  
Short Time  
Capability  
Short Time  
Capability  
1 Second  
(Amperes)  
Dielectric  
Withstand  
1 Minute  
(kVAC)  
Impulse  
Voltage  
Withstand  
(kV)  
MVA)  
(Amperes)  
200 @ 2.3 kV  
350 @ 4.0 kV  
400 @ 4.6 kV  
570 @ 6.6 kV  
50,000  
@ 2.3 - 6.6 kV  
2400  
6000  
18.2  
60  
Application Table  
Maximum Horsepower at Utilization Voltage  
Enclosed  
2300 Volts, 3 Phase  
4200 Volts, 3 Phase  
6600 Volts, 3 Phase  
Maximum  
Continuous  
Current  
Synchronous  
Motors  
Synchronous  
Synchronous  
Induction  
Motors  
Induction  
Motors  
Induction  
Motors  
Motors  
Motors  
(Amperes)  
0.8 PF 1.0 PF  
0.8 PF 1.0 PF  
0.8 PF 1.0 PF  
360  
320  
310  
280  
1500  
1250  
1250  
1000  
1750  
1500  
1500  
1250  
1500  
1250  
1250  
1000  
2500  
2250  
2000  
1750  
3000  
2500  
2500  
2250  
2500  
2250  
2000  
1750  
4000  
3500  
3500  
3000  
5000  
4500  
4000  
3500  
4000  
3500  
3500  
3000  
For transformer and capacitor load switching applications, consult factory.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MEDIUM VOLTAGE CONTROLLERS  
JK720 Series  
The new JK720 Series of motor controller is the  
result of extensive research and development.  
This state-of-the-art controller was designed in  
Houston, Texas, and is currently being manufac-  
tured under ISO 9001 standards in the same  
manufacturing facility as Toshiba motors and  
drives. The components in this new series have  
been arranged in the most logical manner to  
produce a tightly designed unit. This stream-  
lined, space saving design provides the ultimate  
in maintenance ease and safety features.  
Isolated Low Voltage Compartment  
The low voltage section is oversized and is at a  
convenient height. This section is isolated from  
the medium voltage section and includes:  
Thermal Overload Protection Relay  
Pilot Lights (door mounted)  
Push Buttons (door mounted)  
Single Phase Ammeter (door mounted)  
CPT Secondary Fuses  
Control Terminal Points for Customer Connections  
Timers (for Reduced Voltage Controllers)  
Standard Options:  
Metering & Metering Switches  
Ground Fault Protection Relay  
These medium voltage controllers are available in  
across-the-line or reduced voltage models for the  
control of induction, wound rotor or synchronous  
motors, transformers, or capacitors up to 4.8kV.  
All controllers are designed to meet NEMA Class  
E2 requirements. These fixed type controllers  
are available in one high enclosures with the  
following standard features:  
Phase Sequence Protection Relay  
RTD Monitor/Relay  
Solid State (2E) Protection Relay  
(Overload/Single Phase)  
S2E21 Multi-funtion Protection Relay  
Standard Features:  
Bolted Pressure Isolation Switch  
Less Resistance  
Less Wear  
Standard Features Full & Reduced  
Voltage Controllers  
Zero Insertion Pressure  
Mechanical Interlocking System  
Toshiba Medium Voltage Vacuum Contactor 720A  
Bolted Pressure Switch Connections  
36" Wide Footprint  
Rigid 11 Gauge Steel Frame  
Front Accessible Main Bus  
Current Transformers  
Current Limiting, High Interrupting Capacity,  
"R" Rated Motor Starting Fuses  
Start and Stop Push Buttons  
Run and Off Pilot Lights  
Single Phase Ammeter  
Control Power Transformer with Primary  
and Secondary Fuses  
Thermal Bimetallic Overload Relay  
Separate Medium and Low Voltage  
Compartments  
Reduced Voltage Autotransformer  
Controller  
Additional Standard Features:  
Shorting (400A) and Run (720A), Vacuum  
Contactors  
NEMA Medium Duty, Three Winding, Copper  
Wound Autotransformer with 50%, 65%, and  
80% Taps  
Adjustable Solid State Transition Timer  
Adjustable Solid State Incomplete Sequence  
Timer  
Built-in Run/Test Circuit  
Mechanical and Electrical Interlocks  
If UL or CUL is required, specify when ordering.  
Consult Factory for applicable models and options.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MEDIUM VOLTAGE CONTROLLERS  
JK720 Series  
Toshiba's JK720 series complies with EEMAC,  
NEMA, UL and CSA standards and is available in  
non-reversing and reversing full voltage, autotrans-  
former, reactor, multi-speed, synchronous and  
wound rotor configurations. Latched contactors  
are also available.  
The JK720 series is available in the following  
enclosed ratings:  
720 amps  
2300-4800 Volts  
Up to 6,000 HP  
Note: An Incoming Section is required for the JK720  
FVNR, FVR and RVAT type starters, transformer  
feeders and capacitor switching controllers.  
Current Rating  
Maximum Continuous  
Enclosure Type  
Amperes*  
One-High Controller  
Type 1 Ventilated  
Type 1 Non-Ventilated  
Type 12 & 3R  
720  
650  
600  
* Actual limits based on your specific application parameters.  
All specifications subject to change without notice.  
Short Circuit & Withstand Capability  
Interrupting  
Capacity  
(Symmetrical  
Amperes)  
Interrupting  
Capacity  
(Symmetrical 30 Seconds 1 Second  
Short Time Short Time Dielectric  
Impulse  
Voltage  
Withstand  
(kV)  
Capability  
Capability  
Withstand  
1 Minute  
(kV)  
MVA)  
(Amperes)  
(Amperes)  
200 @ 2.3 kV  
350 @ 4.0 kV  
400 @ 4.6 kV  
50,000  
@ 2.3 - 4.6 kV  
AC 13.25  
DC 19  
4320  
10,800  
60  
Application Table  
Maximum Horsepower at Utilization Voltage  
Enclosed  
2300 Volts, 3 Phase  
4200 Volts, 3 Phase  
Maximum  
Continuous  
Current  
Synchronous  
Motors  
Synchronous  
Induction  
Motors  
Induction  
Motors  
Motors  
(Amperes)  
0.8 PF 1.0 PF  
0.8 PF 1.0 PF  
720  
650  
600  
3000  
2750  
2500  
3500  
3000  
2750  
3000  
2750  
2500  
5500  
5000  
4500  
6000  
5500  
5000  
5500  
5000  
4500  
For transformer and capacitor load switching applications, consult factory.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
JK Series Product Specification  
400A MEDIUM VOLTAGE FIXED CONTROLLER  
1.  
Standards  
1.1 Basic controller shall comply with NEMA ICS3-1993, Part 2 (ICS2-324) and UL 347  
Standards. Basic controller can be UL Listed and CSA Certified.  
2.  
Structure  
2.1  
Dimensions  
FVNR One-high - 30"W x 36"D x 46"H (no bus, small LV compartment)  
FVNR One-high - 30"W x 36"D x 61"H (bus provision, large LV compartment)  
FVNR One-high - 30"W x 36"D x 90"H (bus provision, empty upper MV compartment)  
FVNR Two-high - 30"W x 36"D x 90"H  
RVAT (up to 1250HP) - 36"W x 36"D x 90"H  
RVAT (1250HP-4000HP) - 42"W x 36"D x 90"H  
2.2  
Fabrication  
2.2.1 11 gauge frame with 16 gauge side, back and top sheets.  
2.2.2 Front of cubicle to be an all-welded assembly. Remainder of frame to be bolted  
construction.  
2.2.3 Back and top sheets to be removable for easy access for assembly and wiring.  
2.2.4 Basic dimensions and squareness of cubicle to be controlled by accurately located NC-  
punches holes. With exception of welded front frame, cubicle should be capable of being  
assembled without a fixture.  
2.2.5 All doors shall be minimum 12 gauge steel.  
2.2.6 All structural components shall be given a corrosion resistant finish by either galvanizing or  
painting. Galvanized steel shall be used only for internal structural members or panels.  
2.2.7 All panels used to mount low voltage devices shall be painted white for superior visibility.  
Panels shall be easily removable or swing-out to provide access to horizontal bus mounted in the  
middle rear of the cubicle.  
2.3  
General Arrangement of Components  
2.3.1 Medium voltage compartments, low voltage compartments and power bus compartments  
shall be isolated by grounded steel barriers.  
2.3.2 Complete front accessibility to all components shall be provided for installation against  
walls or for back-to-back arrangements.  
2.3.3 Low voltage components shall be located so that components are accessible with medium  
voltage doors closed. Low voltage compartment shall be sized with consideration to mounting  
commonly used devices.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.4  
Handling and Installation  
2.4.1 Removable angles or eye bolts shall be provided at the top of the structure for lifting.  
3.  
Power Bus  
3.1  
Horizontal power bus shall be located at the center rear of the cubicle, in the same location as  
other JK Series controllers.  
3.2  
Horizontal power bus ratings of 1200 and 2000 amperes are available. Bus sizes shall match  
those provided in other JK Series controllers.  
3.3  
3.4  
3.5  
Horizontal power bus shall be braced for 50kA RMS symmetrical.  
Horizontal power bus shall be tin plated as standard with insulated bus and silver plating optional.  
Bare copper 1/4 x 2 inch horizontal ground bus shall be available and the location shall match  
other JK Series controllers.  
3.6  
Vertical power bus feeding 400 ampere controllers shall be 1/4 x 1-1/4 inch tin plated copper.  
Insulated bus and silver plating are optional.  
3.7  
4.  
Horizontal power bus shall be front accessible by removing or swinging open a panel.  
Medium Voltage Controllers - 400 Amperes  
4.1  
Medium Voltage Controller Compartment  
4.1.1 The medium voltage controller compartment for controllers rated 400 amperes shall consist  
of an isolation switch (4.2), a fixed mounted vacuum contactor (4.3), three fixed mounted power  
fuses (4.4), three current transformers and a control power transformer with primary fuses.  
Optionally a second control or potential transformer with primary fuses may be provided.  
4.1.2 Internal power connections between power components shall be made using either high  
voltage cable or bus bars.  
4.1.3 Connection of customer's outgoing load cables shall be made to terminals mounted on the  
rear of the medium voltage contactor. It shall be possible to terminate outgoing load cables with  
the removal of the horizontally mounted power fuses. Sufficient wire bending space shall be  
provided for terminating shielded cables as large as 1-2/0 per phase, or unshielded cables as  
large as 1-350MCM per phase, top or bottom entry.  
4.1.4 A zero sequence current transformer for ground fault sensing when required shall be  
provided. It shall be located within the MV compartment where customer’s load cable can be  
conveniently passed through the current transformer window prior to termination.  
4.1.5 Three current transformers for metering and relaying shall be provided. These shall be of  
the window type (or bar type as option) with burden capacity as required for operating the various  
meters and relays.  
4.1.6 Control power and optional potential transformers shall be of the encapsulated type with  
primary fuses. Primary side of transformers shall be wired to the load side of the main controller  
power fuses. Transformers shall be arranged to provide easy access for replacement of primary  
fuses.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.2  
Bolted Pressure Isolation Switch  
4.2.1 A Toshiba type JK fixed mounted, gang-operated isolation switch shall be provided with  
each controller to isolate the medium voltage compartment from the power source.  
4.2.2 The switch shall be directly driven by an externally operable handle mounted on the right  
hand flange of the cubicle. The handle shall provide positive indication of the position of the  
switch.  
4.2.3 The switch mechanism shall be designed such that in the closed position it provides the  
equivalent of a bolted pressure joint at both ends of the movable blades, rather than relying on  
spring pressure.  
4.2.4 The line side of the switch shall be bus connected to the main horizontal power bus or to  
the incoming terminals of the controller. The load side of the switch shall be bus connected to  
the main controller power fuses.  
4.2.5 The switch blades shall automatically ground the line side of the power fuses when the  
switch is opened. This allows any stored energy in the controller load circuit to be discharged by  
closing the contactor using test power.  
4.2.6 It shall be possible to visually confirm that the switch blades are open and grounded by  
viewing the blades through the viewing window with the medium voltage door closed. Also, there  
shall be a mechanical operated flag (visible through the window in the medium voltage door)  
displaying the switch in the “OPEN” position with the door closed.  
4.2.7 A shutter mechanism shall automatically isolate the medium voltage compartment from all  
live parts when the switch is opened.  
4.2.8 The external operating handle for the isolation switch shall be designed to accept up to  
three external padlocks in the OFF position.  
4.2.9 The switch shall be capable of interrupting the no-load current of the largest control power  
transformer which can be connected to it. The interrupting capability of the switch shall be a  
minimum of 0.4 amperes at 110% of rated line voltage.  
4.2.10 The switch shall be rated as follows:  
400 amperes @ 7.2kV  
4.2.11 The mechanical life of the switch and its operating mechanism shall be 10,000 operations  
minimum.  
4.2.12 All switch current-carrying parts shall be silver plated. An optional tin-over-silver plated  
switch shall be available for use in paper mill applications.  
4.3  
Vacuum Contactor  
4.3.1 The Toshiba HCV-5HA vacuum contactor shall be used in these controllers.  
4.3.2 The contactor shall be bolted into the medium voltage compartment. It shall be arranged  
such that the power connections are front-accessible so it can be unbolted and removed if  
necessary for maintenance.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3.3 Power connections from the isolation switch to the main power fuses shall be made using  
bus bar. Connections from the contactor through the current transformers to the outgoing load  
terminals shall be made using power cable furnished by others.  
4.3.4 The contactor shall be available with an optional mechanical latch with provisions for  
manual or electrical trip.  
4.3.5 The contactor shall be mechanically and electrically interlocked with the isolation switch as  
described in the section on interlocking (4.5).  
4.4  
Power Fuses  
4.4.1 The power fuses shall be arranged horizontally at the top of the contactor unit. In this  
position, the blown fuse indicators on the fuses shall be visible, through the viewing window, when  
the medium voltage door is closed.  
4.4.2 The fuse unit shall include either single or double barrel power fuses, R-rated or E-rated, 3"  
diameter.  
4.5  
Interlocking  
4.5.1 A mechanical interlock shall be provided between the vacuum contactor and the isolation  
switch. The interlock shall prevent the isolation switch from being opened or closed unless the  
main contacts of the contactor are opened.  
4.5.2 The interlock described in 4.5.1 shall also operate in a manner such that it will prevent the  
closing of the main contacts of the vacuum contactor unless the isolation switch is either fully  
opened or fully closed.  
4.5.3 An electrical interlock shall be provided as a backup to the mechanical interlock in 4.5.1.  
This interlock shall switch off control power to the vacuum contactor at any isolating switch  
position other than fully opened or fully closed.  
4.5.4 A mechanical interlock shall be provided between the isolation switch and the medium  
voltage compartment door. This interlock shall prevent the door from being opened unless the  
isolating switch is in the fully open position.  
4.5.5 The interlock described in 4.5.4 shall be capable of being circumvented in the event  
emergency entrance to the controller is required. Circumventing the interlock shall require two  
separate and distinct operations and shall require the use of a tool.  
4.5.6 A mechanical interlock between the isolation switch and the medium voltage door shall be  
provided to prevent the isolating switch from being closed when the door is open. This interlock  
shall be capable of being circumvented only by the use of a tool.  
4.5.7 An electrical interlock shall be provided to ensure the isolation switch does not open with  
the control power transformer under load. This interlock shall be designed such that during  
switch opening, the transformer secondary is disconnected prior to the opening of the switch  
blades. Also, the isolating switch blades must close before the secondary load is reconnected.  
4.5.8 An electrical interlock shall be provided to prevent the vacuum contactor from being closed  
using external test power unless the isolation switch is fully opened and the secondary of the  
normal control power transformer is disconnected from the control circuit to prevent backfeeding  
the transformer.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.  
Ratings  
5.1  
Controller shall be rated as follows:  
5.1.1 Interrupting Ratings:  
400 Ampere Controller:  
- contactor  
7.0kA @ 6.9kV  
- fused controller  
50kA RMS Sym. @ 7.2kV  
200MVA @ 2.3kV  
350MVA @ 4.0kV  
400MVA @ 4.6kV  
570MVA @ 6.6kV  
5.1.2 Continuous Thermal Ratings:  
400 Ampere Controller:  
Enclosure type  
Max. Continuous  
Amperes  
Max. Continuous  
Amperes  
Max. Continuous  
Amperes  
90” One-high controller or  
Lower controller in a Two-  
high stacking  
Upper controller in a  
Two-high stacking  
arrangement  
46” and 61” One-high  
controller  
arrangement  
NEMA-1 Ventilated  
360  
320  
310  
360  
320  
310  
320  
280  
280  
NEMA-1 Non-ventilated  
NEMA-12/3R  
5.1.3 Short Time Thermal Rating:  
400 Ampere Contactor: 2400A for 30 seconds  
6000A for 1 second  
5.1.4 Impulse Withstand:  
400 Ampere Controller: 60kV  
1.2 x 50 microsecond wave  
Rev. 2, 2/16/1999  
Download from Www.Somanuals.com. All Manuals Search And Download.  
JK Series Product Specification  
720A MEDIUM VOLTAGE FIXED CONTROLLER  
1.  
Standards  
1.1 Basic controller shall comply with NEMA ICS3-1993, Part 2 (ICS2-324) and UL 347  
Standards. Basic controller can be UL/CUL Listed.  
2.  
Structure  
2.1  
Dimensions  
Across-the-Line (one-high) - 36"W x 36"D x 90"H  
Reduced Voltage Autotransformer - (2) 36"W x 36"D x 90"H  
2.2  
Fabrication  
2.2.1 11 gauge frame with 16 gauge side, back and top sheets.  
2.2.2 Front of cubicle to be an all-welded assembly. Remainder of frame to be bolted  
construction.  
2.2.3 Side, back and top sheets to be removable for easy access for assembly and wiring.  
2.2.4 Basic dimensions and squareness of cubicle to be controlled by accurately located NC-  
punches holes. With exception of welded front frame, cubicle should be capable of being  
assembled without a fixture.  
2.2.5 All doors shall be minimum 12 gauge steel.  
2.2.6 All structural components shall be given a corrosion resistant finish by either galvanizing or  
painting. Galvanized steel shall be used only for internal structural members or panels.  
2.2.7 All panels used to mount low voltage devices shall be painted white for superior visibility.  
Panels shall be easily removable or swing-out to provide access to horizontal bus mounted in the  
rear of the cubicle.  
2.3 General Arrangement of Components  
2.3.1 Medium voltage compartments, low voltage compartments, power bus compartments and  
field conductor wireways shall be isolated by grounded steel barriers.  
2.3.2 Complete front accessibility to all components shall be provided for installation against  
walls or for back-to-back arrangements.  
2.3.3 Low voltage components shall be located so that components are accessible with medium  
voltage door closed. Low voltage compartment shall be sized with consideration to mounting  
commonly used devices.  
2.4  
Handling and Installation  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.4.1 Removable angles or eye bolts shall be provided at the top of the structure for lifting.  
2.4.2 Optional removable sill channels shall be available.  
Power Bus  
3.  
3.1  
Horizontal power bus shall be located at the center rear of the cubicle, in the same location as  
other JK Series controllers.  
3.2  
Horizontal power bus ratings of 1200 and 2000 amperes shall be available. Bus sizes shall  
match those provided in other JK Series controllers.  
3.3  
3.4  
3.5  
Horizontal power bus shall be braced for 50kA RMS symmetrical.  
Horizontal power bus shall be tin plated as standard with silver plating optional.  
Bare copper 1/4 x 2 inch horizontal ground bus shall be available and the location shall match  
other JK Series controllers.  
3.6  
Vertical power bus feeding 720 ampere controllers shall be 3/8 x 2 inch tin plated copper. Silver  
plating shall be optional.  
3.7  
4.  
Horizontal power bus shall be front accessible by removing or swinging open a panel.  
Medium Voltage Controllers - 720 Amperes  
4.1  
Medium Voltage Controller Compartment  
4.1.1 The medium voltage controller compartment for controllers rated 720 amperes shall consist  
of an isolation switch (4.2), a fixed mounted vacuum contactor (4.3), three fixed mounted power  
fuses (4.4), three current transformers and a control power transformer with primary fuses.  
Optionally a second control or potential transformer with primary fuses may be provided.  
4.1.2 Internal power connections between power components shall be made using either high  
voltage cable or bus bars.  
4.1.3 Connection of customer's outgoing load cables shall be made to terminals mounted on the  
left side of the medium voltage compartment. It shall be possible to terminate outgoing load  
cables without the removal of major components such as the vacuum contactor and power fuses.  
Sufficient wire bending space shall be provided for terminating shielded cables as large as 2-  
500MCM per phase, top or bottom entry.  
4.1.4 A zero sequence current transformer for ground fault sensing when required shall be  
provided. It shall be located such that factory installed internal power cables from all three  
phases shall pass through its window. Ground current sensors for Toshiba 2E ground fault  
module and Multilin ground fault relay shall be available as a minimum.  
4.1.5 Three current transformers for metering and relaying shall be provided. These shall be of  
the window type with burden capacity as required for operating the various meters and relays.  
4.1.6 Control power and optional potential transformers shall be of the encapsulated type with  
integral primary fuses. All transformers shall be rated 60kV BIL. Primary side of transformers  
shall be wired to the load side of the main controller power fuses. Transformers shall be  
arranged to provide easy access for replacement of primary fuses.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.2  
Bolted Pressure Isolation Switch  
4.2.1 A fixed mounted, gang-operated isolation switch shall be provided with each controller to  
isolate the medium voltage compartment from the power source.  
4.2.2 The switch shall be directly driven by an externally operable handle mounted on the right  
hand flange of the cubicle. The handle shall provide positive indication of the position of the  
switch.  
4.2.3 The switch mechanism shall be designed such that in the closed position it provides the  
equivalent of a bolted pressure joint at both ends of the movable blades, rather than relying on  
spring pressure.  
4.2.4 The line side of the switch shall be bus connected to the main horizontal power bus or to  
the incoming terminals of the controller. The load side of the switch shall be bus connected to  
the main controller power fuses.  
4.2.5 The switch blades shall automatically ground the line side of the power fuses when the  
switch is opened. This allows any stored energy in the controller load circuit to be discharged by  
closing the contactor using test power.  
4.2.6 It shall be possible to visually confirm that the switch blades are open and grounded by  
viewing the blades through the viewing window with the medium voltage door closed. Also, there  
shall be a mechanical operated flag (visible through the window in the medium voltage door)  
displaying the switch in the “OPEN” position with the door closed.  
4.2.7 A shutter mechanism shall automatically isolate the medium voltage compartment from all  
live parts when the switch is opened.  
4.2.8 The external operating handle for the isolation switch shall be designed to accept up to  
three external padlocks in the OFF position.  
4.2.9 The switch shall be capable of interrupting the no-load current of the largest control power  
transformer which can be connected to it. The interrupting capability of the switch shall be a  
minimum of 0.4 amperes at 110% of rated line voltage.  
4.2.10 The switch shall be rated as follows:  
720 amperes @ 5.0kV  
4.2.11 The mechanical life of the switch and its operating mechanism shall be 10,000 operations  
minimum.  
4.2.12 All switch current-carrying parts shall be silver plated. An optional tin-over-silver plated  
switch shall be available for use in paper mill applications.  
4.3  
Vacuum Contactor  
4.3.1 The Toshiba CV-6KAU vacuum contactor shall be used in these controllers.  
4.3.2 The contactor shall be bolted into the medium voltage compartment. It shall be arranged  
such that the power connections are front-accessible so it can be unbolted and removed if  
necessary for maintenance.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3.3 Power connections from the isolation switch to the contactor shall be made using bus bar.  
Connections from the contactor through the current transformers to the outgoing load terminals  
shall be made using power cable.  
4.3.4 The contactor shall be supplied with an optional mechanical latch with provisions for  
manual or electrical trip.  
4.3.5 The contactor shall be fully mechanically and electrically interlocked with the isolation  
switch as described in the section on interlocking (4.5).  
4.4  
Power Fuses  
4.4.1 Main current-limiting power fuses shall be provided for both motor starting (R rated) and  
transformer feeder (E rated) applications.  
4.4.2 Available fuse ratings for motor starting applications shall be Gould Type A051B2DAR0  
rated 38R (630A), 5kV or A051B3DAR0 rated 57X (900A), 5kV.  
4.4.3 Available fuse ratings for transformer feeder applications shall be Gould Type  
A055C2D0R0-500E and 600E, and A055B3D0R0-750E and 900E, rated 5.5kV.  
4.4.4 All power fuses shall employ bolt-in mounting.  
4.4.5 The blown fuse indicators on the fuses shall be visible, through the viewing window, when  
the medium voltage door is closed.  
4.5  
Interlocking  
4.5.1 A mechanical interlock shall be provided between the vacuum contactor and the isolation  
switch. The interlock shall prevent the isolation switch from being opened or closed unless the  
main contacts of the contactor are opened.  
4.5.2 The interlock described in 4.5.1 shall also operate in a manner such that it will prevent the  
closing of the main contacts of the vacuum contactor unless the isolation switch is either fully  
opened or fully closed.  
4.5.3 An electrical interlock shall be provided as a backup to the mechanical interlock in 4.5.1.  
This interlock shall switch off control power to the vacuum contactor at any switch position other  
than fully opened or fully closed.  
4.5.4 A mechanical interlock shall be provided between the isolation switch and the medium  
voltage compartment door. This interlock shall prevent the door from being opened unless the  
switch is in the fully open position.  
4.5.5 The interlock described in 4.5.4 shall be capable of being circumvented in the event  
emergency entrance to the controller is required. Circumventing the interlock shall require two  
separate and distinct operations and shall require the use of a tool.  
4.5.6 A mechanical interlock between the isolation switch and the medium voltage door shall be  
provided to prevent the switch from being closed when the door is open. This interlock shall be  
capable of being circumvented only by the use of a tool.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.5.7 An electrical interlock shall be provided to ensure the isolation switch does not open with  
the control power transformer under load. This interlock shall be designed such that during  
switch opening, the transformer secondary is disconnected prior to the opening of the switch  
blades. Also, during switch closing, the switch blades must close before the secondary load is  
reconnected.  
4.5.8 An electrical interlock shall be provided to prevent the vacuum contactor from being closed  
using external test power unless the isolation switch is fully opened and the secondary of the  
normal control power transformer is disconnected from the control circuit to prevent backfeeding  
the transformer.  
5.  
Ratings  
5.1  
Controllers shall be rated as follows:  
5.1.1 Interrupting Ratings  
- Contactor  
- Controller  
7.2kA @ 6.6kV Max.  
50kA RMS Sym. @ 5.0kV Max.  
200MVA @ 2.3kV  
350MVA @ 4.0kV  
400MVA @ 4.6kV  
5.1.2 Continuous Current Ratings  
N-1 Enclosure (Ventilated)  
N-1 Enclosure (Non-ventilated)  
N-12, 3, 3R Enclosure  
720A  
650A  
600A  
5.1.3 Horsepower Ratings - Induction Motors (Approximate)  
3000  
2750  
2500  
N-1 Enclosure (Ventilated)  
N-1 Encl. (Non-ventilated)  
N-12, 3, 3R Enclosure  
5500  
5000  
4500  
5.1.4 Short Time Current Ratings  
4320A - 30 seconds  
10,800A - 1 second  
5.1.5 Impulse Voltage Withstand  
60kV  
1.2 x 50 microsecond wave  
Rev. 5, 2/16/1999  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
North America Headquarters & Manufacturing Facilities (Houston, TX)  
TOSHIBA - Quality by Design  
Our company culture and history is strongly rooted in quality. Our designs are  
technologically innovative and our products are manufactured from start to end  
using only the highest quality foreign and domestic parts.  
Product Warranty  
Toshiba offers a comprehensive warranty program on its full line of industrial  
products. Consult your salesperson or the factory for specific information.  
Need to Know More?  
information on Toshiba products.  
Customer Support Services  
Toshiba offers 24 hour service nationwide. For assistance of any type,  
call: 1-800-231-1412  
ADJUSTABLE SPEED DRIVES  
MOTORS  
CONTROLS  
UPS  
INSTRUMENTATION  
PLC  
Available Through:  
INDUSTRIAL DIVISION  
13131 West Little York Road, Houston, Texas 77041  
Tel 713/466-0277 Fax 713/466-8773  
US 800/231-1412 Canada 800/872-2192 Mexico 01/800/527-1204  
Copyright 2/2005  
*pacjKSBROCH050218*  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Tascam Musical Instrument FW 1082 User Manual
TDK Power Supply 750W HALF RACK User Manual
Technics Speaker SB AFC150A User Manual
Tiger Games 7 585 User Manual
Topcom Telephone 122+ User Manual
Toshiba Portable Multimedia Player S60 MES G60 User Manual
Troy Bilt Blower TB197BV User Manual
True Fitness Exercise Bike P100 User Manual
VTech Cordless Telephone VT9127 User Manual
Walker Indoor Furnishings W44CMPBL User Manual