Toshiba Air Conditioner RAS 10YAV E User Manual

FILE NO. A00-T004  
SERVICE MANUAL  
AIR-CONDITIONER  
SPLIT TYPE  
RAS-10YKV-E/RAS-10YAV-E  
RAS-13YKV-E/RAS-13YAV-E  
R410A  
PRINTED IN JAPAN, Aug.,2000 ToMo  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. SPECIFICATIONS  
1-1. Specifications  
RAS-10YKV-E/RAS-10YAV-E  
Unit model  
Indoor  
RAS-10YKV-E  
Outdoor  
RAS-10YAV-E  
Current limited  
Cooling capacity  
Cooling capacity range  
Heating capacity  
Heating capacity range  
Power supply  
(kW)  
(kW)  
(kW)  
(kW)  
2,7  
0,8 3,4  
3,6  
0,8 6,2  
220 230 240V 1Ph 50/60Hz  
Electric  
characteristics  
Indoor  
Operation mode  
Cooling  
0,15  
Heating  
0,15  
Running current  
Power consumption  
Power factor  
Operation mode  
Running current  
Power consumption  
Power factor  
(A)  
(W)  
(%)  
30  
30  
87  
Cooling  
3,39 / 3,23 / 3,09  
670  
87  
Heating  
4,40 / 4,20 / 4,02  
870  
Outdoor  
(A)  
(W)  
(%)  
(A)  
90  
90  
Starting current  
4,55 / 4,35 / 4,17  
COP (Cooling/Heating)  
3,86 / 4,00  
Operating noise  
Indoor  
High  
Medium (Cooling / Heating) (dBA)  
Low (Cooling / Heating) (dBA)  
(Cooling / Heating) (dBA)  
38 / 39  
34 / 35  
30 / 30  
Outdoor  
(Cooling / Heating)  
(dBA)  
45 / 46  
Indoor unit  
Unit model  
Dimension  
RAS-10YKV-E  
Height  
Width  
Depth  
(mm)  
(mm)  
(mm)  
(kg)  
265  
790  
189  
8
Net weight  
Fan motor output  
(W)  
19  
Air flow rate (Cooling / Heating)  
Unit model  
(m³/h)  
480 / 520  
RAS-10YAV-E  
Outdoor unit  
Dimension  
Height  
Width  
Depth  
(mm)  
(mm)  
(mm)  
(kg)  
550  
780  
270  
38  
Net weight  
Compressor Motor output  
Type  
(W)  
750  
Twin rotary type with DC-inverter variable speed control  
Model  
DA91A1F-44F  
Fan motor output  
Air flow rate (Cooling / Heating)  
(W)  
(m³/h)  
40  
2120 / 2120  
Piping connection Type  
Indoor unit  
Flare connection  
Liquid side  
Gas side  
Ø6,35  
Ø9,52  
Outdoor unit Liquid side  
Gas side  
Ø6,35  
Ø9,52  
Maximum length (Per unit)  
Maximum chargeless length  
Maximum height difference  
Name of refrigerant  
Weight  
(m)  
(m)  
(m)  
15  
15  
10  
R410A  
Refrigerant  
(kg)  
0,8  
Wiring connection  
Power supply  
3 Wires : includes earth  
Interconnection  
4 Wires : includes earth  
Usable temperature range  
Accessory Indoor unit  
Indoor (Cooling / Heating)  
Outdoor (Cooling / Heating)  
Installation plate  
(°C)  
(°C)  
21 32 / 0 28  
10 43 / 10 21  
1
Wireless remote control  
Label  
1
2
Remote controller holder  
Pan head wood screw  
Purifying filter  
1
2 (Ø3,1 x 16L)  
1
Deodorizing filter  
Batteries  
1
2
Mounting screw  
6 (Ø4 x 25L)  
Installation manual  
Owner's manual  
Outdoor unit Drain nipple  
1
1
1
• The specifications may be subject to change without notice for purpose of improvement.  
– 3 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RAS-13YKV-E/RAS-13YAV-E  
Unit model  
Indoor  
RAS-13YKV-E  
Outdoor  
RAS-13YAV-E  
Current limited  
Cooling capacity  
Cooling capacity range  
Heating capacity  
Heating capacity range  
Power supply  
(kW)  
(kW)  
(kW)  
(kW)  
3,7  
0,8 4,0  
4,8  
0,8 6,6  
220 230 240V 1Ph 50/60Hz  
Electric  
characteristics  
Indoor  
Operation mode  
Running current  
Power consumption  
Power factor  
Operation mode  
Running current  
Power consumption  
Power factor  
Cooling  
0,15  
Heating  
0,15  
(A)  
(W)  
(%)  
30  
30  
87  
Cooling  
5,59 / 5,34 / 5,11  
1170  
87  
Heating  
7,03 / 6,71 / 6,43  
1470  
Outdoor  
(A)  
(W)  
(%)  
(A)  
95  
95  
Starting current  
7,18 / 6,86 / 6,58  
COP (Cooling/Heating)  
3,08 / 3,20  
Operating noise  
Indoor  
High  
Medium (Cooling / Heating) (dBA)  
Low (Cooling / Heating) (dBA)  
(Cooling / Heating) (dBA)  
41 / 41  
36 / 36  
30 / 30  
Outdoor  
(Cooling / Heating)  
(dBA)  
48 / 50  
Indoor unit  
Unit model  
Dimension  
RAS-13YKV-E  
Height  
Width  
Depth  
(mm)  
(mm)  
(mm)  
(kg)  
265  
790  
189  
8
Net weight  
Fan motor output  
(W)  
19  
Air flow rate (Cooling / Heating)  
Unit model  
(m³/h)  
530 / 560  
RAS-13YAV-E  
Outdoor unit  
Dimension  
Height  
Width  
Depth  
(mm)  
(mm)  
(mm)  
(kg)  
550  
780  
270  
38  
Net weight  
Compressor Motor output  
Type  
(W)  
750  
Twin rotary type with DC-inverter variable speed control  
Model  
DA91A1F-44F  
Fan motor output  
Air flow rate (Cooling / Heating)  
(W)  
(m³/h)  
40  
2520 / 2520  
Piping connection Type  
Indoor unit  
Flare connection  
Liquid side  
Gas side  
Ø6,35  
Ø9,52  
Outdoor unit Liquid side  
Gas side  
Ø6,35  
Ø9,52  
Maximum length (Per unit)  
Maximum chargeless length  
Maximum height difference  
Name of refrigerant  
Weight  
(m)  
(m)  
(m)  
15  
15  
10  
R410A  
Refrigerant  
(kg)  
0,8  
Wiring connection  
Power supply  
3 Wires : includes earth  
Interconnection  
4 Wires : includes earth  
Usable temperature range  
Accessory Indoor unit  
Indoor (Cooling / Heating)  
Outdoor (Cooling / Heating)  
Installation plate  
(°C)  
(°C)  
21 32 / 0 28  
10 43 / 10 21  
1
Wireless remote control  
Label  
1
2
Remote controller holder  
Pan head wood screw  
Purifying filter  
1
2 (Ø3,1 x 16L)  
1
Deodorizing filter  
Batteries  
1
2
Mounting screw  
6 (Ø4 x 25L)  
Installation manual  
Owner's manual  
Outdoor unit Drain nipple  
1
1
1
The specifications may be subject to change without notice for purpose of improvement.  
4 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1-2. Operation Characteristic Curve  
<Cooling>  
<Heating>  
7
7
6
6
5
4
3
2
1
RAS-10YKV-E  
RAS-13YKV-E  
RAS-10YKV-E  
RAS-13YKV-E  
5
4
3
2
Conditions  
Indoor : DB 27˚C/WB 19˚C  
Outdoor : DB 35˚C  
Air flow : High  
Pipe length : 5m  
230V  
• Conditions  
Indoor : DB 20˚C  
Outdoor : DB 7˚C/WB 6˚C  
Air flow : High  
1
0
Pipe length : 5m  
230V  
0
0
0
20  
40  
60  
80  
100  
20  
40  
60  
80  
100  
Compressor speed (rps)  
Compressor speed (rps)  
1-3. Capacity Variation Ratio According toTemperature  
<Cooling>  
105  
100  
95  
90  
85  
80  
75  
70  
65  
60  
55  
50  
120  
110  
100  
90  
80  
70  
60  
50  
40  
30  
20  
10  
0
Current Limited Start  
RAS-10YKV-E  
RAS-13YKV-E  
RAS-10YKV-E  
RAS-13YKV-E  
Conditions  
Conditions  
Indoor : DB27˚C/WB19˚C  
Indoor air flow : High  
Pipe length 5m  
Indoor : DB 20˚C  
Indoor air flow : High  
Pipe length : 5m  
10  
9  
8  
7  
6  
5  
4  
3  
2  
1  
0 1 2 3 4 5 6 7 8 9 10  
32 33 34 35 36 37 38 39 40 41 42 43  
Outdoor temp. (˚C)  
Outdoor temp. (˚C)  
Capacity ratio : 100% = 2,7 kW (RAS-10YKV-E)  
100% = 3,7 kW (RAS-13YKV-E)  
*
– 5 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. REFRIGERANT R410A  
This air conditioner adopts the new refrigerant HFC  
(R410A) which does not damage the ozone layer.  
(5) After completion of installation work, check to  
make sure that there is no refrigeration gas  
leakage.  
The working pressure of the new refrigerant R410A  
is 1,6 times higher than conventional refrigerant  
(R22).The refrigerating oil is also changed in  
accordance with change of refrigerant, so be careful  
that water, dust, and existing refrigerant or refrigerat-  
ing oil are not entered in the refrigerant cycle of the  
air conditioner using the new refrigerant during  
installation work or servicing time.  
If the refrigerant gas leaks into the room, coming  
into contact with fire in the fan-driven heater,  
space heater, etc., a poisonous gas may occur.  
(6) When an air conditioning system charged with a  
large volume of refrigerant is installed in a small  
room, it is necessary to exercise care so that,  
even when refrigerant leaks, its concentration  
does not exceed the marginal level.  
The next section describes the precautions for air  
conditioner using the new refrigerant. Conforming to  
contents of the next section together with the  
general cautions included in this manual, perform  
the correct and safe work.  
If the refrigerant gas leakage occurs and its  
concentration exceeds the marginal level, an  
oxygen starvation accident may result.  
(7) Be sure to carry out installation or removal  
according to the installation manual.  
2-1. Safety During Installation/Servicing  
Improper installation may cause refrigeration  
trouble, water leakage, electric shock, fire, etc.  
As R410A’s pressure is about 1,6 times higher than  
that of R22, improper installation/servicing may  
cause a serious trouble. By using tools and materi-  
als exclusive for R410A, it is necessary to carry out  
installation/servicing safely while taking the following  
precautions into consideration.  
(8) Unauthorized modifications to the air conditioner  
may be dangerous. If a breakdown occurs  
please call a qualified air conditioner technician  
or electrician.  
Improper repair’s may result in water leakage,  
electric shock and fire, etc.  
(1) Never use refrigerant other than R410A in an air  
conditioner which is designed to operate with  
R410A.  
2-2. Refrigerant Piping Installation  
2-2-1. Piping Materials and Joints Used  
If other refrigerant than R410A is mixed, pres-  
sure in the refrigeration cycle becomes abnor-  
mally high, and it may cause personal injury, etc.  
by a rupture.  
For the refrigerant piping installation, copper pipes  
and joints are mainly used. Copper pipes and joints  
suitable for the refrigerant must be chosen and  
installed. Furthermore, it is necessary to use clean  
copper pipes and joints whose interior surfaces are  
less affected by contaminants.  
(2) Confirm the used refrigerant name, and use  
tools and materials exclusive for the refrigerant  
R410A.  
The refrigerant name R410A is indicated on the  
visible place of the outdoor unit of the air condi-  
tioner using R410A as refrigerant.To prevent  
mischarging, the diameter of the service port  
differs from that of R22.  
(1) Copper Pipes  
It is necessary to use seamless copper pipes  
which are made of either copper or copper alloy  
and it is desirable that the amount of residual oil  
is less than 40 mg/10 m. Do not use copper  
pipes having a collapsed, deformed or discol-  
ored portion (especially on the interior surface).  
Otherwise, the expansion valve or capillary tube  
may become blocked with contaminants.  
(3) If a refrigeration gas leakage occurs during  
installation/servicing, be sure to ventilate fully.  
If the refrigerant gas comes into contact with fire,  
a poisonous gas may occur.  
(4) When installing or removing an air conditioner,  
do not allow air or moisture to remain in the  
refrigeration cycle. Otherwise, pressure in the  
refrigeration cycle may become abnormally high  
so that a rupture or personal injury may be  
caused.  
As an air conditioner using R410A incurs  
pressure higher than when using R22, it is  
necessary to choose adequate materials.  
Thicknesses of copper pipes used with R410A  
are as shown in Table 2-2-1. Never use copper  
pipes thinner than 0,8 mm even when it is  
available on the market.  
– 6 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 2-2-1 Thicknesses of annealed copper pipes  
Thickness (mm)  
Nominal diameter  
Outer diameter (mm)  
R410A  
0,80  
R22  
0,80  
0,80  
0,80  
1,00  
1/4  
3/8  
1/2  
5/8  
6,35  
9,52  
0,80  
12,70  
15,88  
0,80  
1,00  
(2) Joints  
b) Socket Joints  
For copper pipes, flare joints or socket joints are  
used. Prior to use, be sure to remove all con-  
taminants.  
Socket joints are such that they are brazed  
for connections, and used mainly for thick  
pipings whose diameter is larger than 20 mm.  
Thicknesses of socket joints are as shown in  
Table 2-2-2.  
a) Flare Joints  
Flare joints used to connect the copper pipes  
cannot be used for pipings whose outer  
diameter exceeds 20 mm. In such a case,  
socket joints can be used.  
Sizes of flare pipe ends, flare joint ends and  
flare nuts are as shown in Tables 2-2-3 to 2-  
2-6 below.  
Table 2-2-2 Minimum thicknesses of socket joints  
Reference outer diameter of  
copper pipe jointed (mm)  
Minimum joint thickness  
(mm)  
Nominal diameter  
1/4  
3/8  
1/2  
5/8  
6,35  
9,52  
0,50  
0,60  
0,70  
0,80  
12,70  
15,88  
(1) Flare Processing Procedures and Precautions  
a) Cutting the Pipe  
2-2-2. Processing of Piping Materials  
When performing the refrigerant piping installation,  
care should be taken to ensure that water or dust  
does not enter the pipe interior, that no other oil  
other than lubricating oils used in the installed air  
conditioner is used, and that refrigerant does not  
leak. When using lubricating oils in the piping  
processing, use such lubricating oils whose water  
content has been removed. When stored, be sure to  
seal the container with an airtight cap or any other  
cover.  
By means of a pipe cutter, slowly cut the pipe  
so that it is not deformed.  
b) Removing Burrs and Chips  
If the flared section has chips or burrs,  
refrigerant leakage may occur. Carefully  
remove all burrs and clean the cut surface  
before installation.  
– 7 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
c) Insertion of Flare Nut  
d) Flare Processing  
Flare processing dimensions differ according  
to the type of flare tool. When using a con-  
ventional flare tool, be sure to secure dimen-  
sion Aby using a gauge for size adjustment.  
Make certain that a clamp bar and copper  
pipe have been cleaned.  
ØD  
By means of the clamp bar, perform the flare  
processing correctly.  
A
Use either a flare tool for R410A or conven-  
tional flare tool.  
Fig. 2-2-1 Flare processing dimensions  
Table 2-2-3 Dimensions related to flare processing for R410A  
A (mm)  
Conventional flare tool  
Outer  
diameter  
(mm)  
Nominal  
diameter  
Thickness  
(mm)  
Flare tool for R410A  
clutch type  
Clutch type  
1,0 to 1,5  
1,0 to 1,5  
1,0 to 1,5  
1,0 to 1,5  
Wing nut type  
1,5 to 2,0  
1/4  
3/8  
1/2  
5/8  
6,35  
9,52  
0,8  
0,8  
0,8  
1,0  
0 to 0,5  
0 to 0,5  
0 to 0,5  
0 to 0,5  
1,5 to 2,0  
12,70  
15,88  
2,0 to 2,5  
2,0 to 2,5  
Table 2-2-4 Dimensions related to flare processing for R22  
A (mm)  
Outer  
diameter  
(mm)  
Nominal  
diameter  
Thickness  
(mm)  
Conventional flare tool  
Flare tool for R410A  
clutch type  
Clutch type  
0,5 to 1,0  
0,5 to 1,0  
0,5 to 1,0  
0,5 to 1,0  
Wing nut type  
1,0 to 1,5  
1/4  
3/8  
1/2  
5/8  
6,35  
9,52  
0,8  
0,8  
0,8  
1,0  
0 to 0,5  
0 to 0,5  
0 to 0,5  
0 to 0,5  
1,0 to 1,5  
12,70  
15,88  
1,0 to 2,0  
1,0 to 2,0  
Table 2-2-5 Flare and flare nut dimensions for R410A  
Outer  
diameter  
(mm)  
Dimension (mm)  
Flare nut  
width  
(mm)  
Nominal  
diameter  
Thickness  
(mm)  
A
B
C
D
1/4  
3/8  
1/2  
5/8  
6,35  
9,52  
0,8  
0,8  
0,8  
1,0  
9,1  
9,2  
6,5  
9,7  
13  
20  
23  
25  
17  
22  
26  
29  
13,2  
16,6  
19,7  
13,5  
16,0  
19,0  
12,70  
15,88  
12,9  
16,0  
8 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 2-2-6 Flare and flare nut dimensions for R22  
Outer  
diameter  
(mm)  
Dimension (mm)  
Thickness  
Flare nut  
width  
(mm)  
Nominal  
diameter  
(mm)  
A
B
C
D
1/4  
3/8  
1/2  
5/8  
3/4  
6,35  
9,52  
0,8  
0,8  
0,8  
1,0  
1,0  
9,0  
9,2  
6,5  
9,7  
13  
20  
20  
23  
34  
17  
22  
24  
27  
36  
13,0  
16,2  
19,7  
23,3  
13,5  
16,0  
19,0  
24,0  
12,70  
15,88  
19,05  
12,9  
16,0  
19,2  
D
B
A
C
Fig. 2-2-2 Relations between flare nut and flare seal surface  
(2) Flare Connecting Procedures and Precautions  
When it is strong, the flare nut may crack and  
may be made non-removable. When choosing  
the tightening torque, comply with values  
designated by manufacturers. Table 2-2-7  
shows reference values.  
a) Make sure that the flare and union portions  
do not have any scar or dust, etc.  
b) Correctly align the processed flare surface  
with the union axis.  
Note:  
c) Tighten the flare with designated torque by  
means of a torque wrench.The tightening  
torque for R410A is the same as that for  
conventional R22. Incidentally, when the  
torque is weak, the gas leakage may occur.  
When applying oil to the flare surface, be sure to use  
oil designated by the manufacturer. If any other oil is  
used, the lubricating oils may deteriorate and cause  
the compressor to burn out.  
Table 2-2-7 Tightening torque of flare for R410A [Reference values]  
Tightening torque of torque  
wrenches available on the market  
N•m (kgf•cm)  
Nominal  
diameter  
Outer diameter  
(mm)  
Tightening torque  
N•m (kgf•cm)  
1/4  
3/8  
1/2  
5/8  
6,35  
9,52  
14 to 18 (140 to 180)  
33 to 42 (330 to 420)  
50 to 62 (500 to 620)  
63 to 77 (630 to 770)  
16 (160), 18 (180)  
42 (420)  
12,70  
15,88  
55 (550)  
65 (650)  
9 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2-3. Tools  
2-3-1. Required Tools  
The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to prevent  
mixing of other refrigerant.To reinforce the pressure-resisting strength, flare processing dimensions and opposite side  
dimension of flare nut (For Ø12,7 copper pipe) of the refrigerant piping are lengthened.  
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge,  
clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.  
(1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))  
(2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)  
(3) Tools commonly used for R410A and for conventional refrigerant (R22)  
The table below shows the tools exclusive for R410A and their interchangeability.  
Tools exclusive for R410A (The following tools for R410A are required.)  
Tools whose specifications are changed for R410A and their interchangeability  
R410A air conditioner  
installation  
Conventional air  
conditioner installation  
Existence of  
Whether  
Whether new equip-  
ment can be used with  
No.  
Used tool  
Usage  
new equipment conventional  
for R410A  
equipment can conventional refriger-  
be used ant  

Flare tool  
Pipe flaring  
Yes  
(Note 1)  
¡
*
*
Copper pipe gauge for Flaring by  
adjusting projection  
margin  
conventional flare  
tool  
Yes  
(Note 1)  
(Note 1)  
*
Torque wrench  
(For Ø12,7)  
Connection of flare  
nut  
ƒ
Yes  
Yes  
X
X
X
X
Evacuating, refriger-  
ant charge, run  
check, etc.  
Gauge manifold  
Charge hose  
Vacuum pump adapter Vacuum evacuating  
Electronic balance for  
Yes  
Yes  
X
X
¡
¡
Refrigerant charge  
refrigerant charging  
ˆ
Š
Refrigerant cylinder  
Leakage detector  
Charging cylinder  
Refrigerant charge  
Gas leakage check  
Refrigerant charge  
Yes  
Yes  
X
X
X
X
¡
X
(Note 2)  
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection  
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.  
(Note 2) Charging cylinder for R410A is being currently developed.  
General tools (Conventional tools can be used.)  
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary  
as the general tools.  
(4) Reamer  
(9) Hole core drill (Ø65)  
(1) Vacuum pump  
(5) Pipe bender  
(10) Hexagon wrench  
(Opposite side 5mm)  
Use vacuum pump by  
attaching vacuum pump adapter.  
(6) Level vial  
(11) Tape measure  
(12) Metal saw  
(2) Torque wrench (For Ø6,35)  
(7) Screwdriver (+, )  
(8) Spanner or Monkey wrench  
(3) Pipe cutter  
Also prepare the following equipments for other installation method and run check.  
(1) Clamp meter  
(2) Thermometer  
(3) Insulation resistance tester  
(4) Electroscope  
10 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2-4. Recharging of Refrigerant  
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the  
following steps.  
Recover the refrigerant, and check no refrigerant  
remains in the equipment.  
When the compound gauges pointer has indicated  
0,1 Mpa (76 cmHg), place the handle Low in the  
fully closed position, and turn off the vacuum pumps  
power switch.  
Connect the charge hose to packed valve service  
port at the outdoor units gas side.  
Keep the status as it is for 1 to 2 minutes, and ensure  
that the compound gauges pointer does not return.  
Connect the charge hose of the vacuum pump  
adapter.  
Set the refrigerant cylinder to the electronic balance,  
connect the connecting hose to the cylinder and the  
connecting port of the electronic balance, and charge  
liquid refrigerant.  
Open fully both packed valves at liquid and gas  
sides.  
Place the handle of the gauge manifold Low in the  
fully opened position, and turn on the vacuum pumps  
power switch. Then, evacuating the refrigerant in the  
cycle.  
(For refrigerant charging, see the figure below.)  
Never charge refrigerant exceeding the specified amount.  

ƒ
If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.  
Do not carry out additional charging.  
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the  
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the  
specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally  
high pressure, and may cause a rupture or personal injury.  
(INDOOR unit)  
(Liquid side)  
(OUTDOOR unit)  
Opened  
Closed  
(Gas side)  
Refrigerant cylinder  
(With siphon pipe)  
Check valve  
Open/Close valve  
for charging  
Service port  
Electronic balance for refrigerant charging  
Fig. 2-4-1 Configuration of refrigerant charging  
11 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Be sure to make setting so that liquid can be charged.  

When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.  
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant.  
Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the  
cylinder upside down if cylinder is not equipped with siphon.  
[ Cylinder with siphon ]  
[ Cylinder without siphon ]  
Gauge manifold  
Gauge manifold  
OUTDOOR unit  
OUTDOOR unit  
c y l i n d e r  
a n t i g e r R e f r  
Refrigerant  
cylinder  
Electronic  
balance  
Electronic  
balance  
Siphon  
R410A refrigerant is HFC mixed refrigerant.  
Therefore, if it is charged with gas, the compo-  
sition of the charged refrigerant changes and  
the characteristics of the equipment varies.  
Fig. 2-4-2  
Phosphor bronze brazing filler tends to react  
with sulfur and produce a fragile compound  
water solution, which may cause a gas leak-  
age.Therefore, use any other type of brazing  
filler at a hot spring resort, etc., and coat the  
surface with a paint.  
2-5. Brazing of Pipes  

2-5-1. Materials for Brazing  
(1) Silver brazing filler  
Silver brazing filler is an alloy mainly composed  
of silver and copper. It is used to join iron,  
copper or copper alloy, and is relatively expen-  
sive though it excels in solderability.  
When performing brazing again at time of  
servicing, use the same type of brazing filler.  
(2) Phosphor bronze brazing filler  
2-5-2. Flux  
Phosphor bronze brazing filler is generally used  
to join copper or copper alloy.  
(1) Reason why flux is necessary  
By removing the oxide film and any foreign  
matter on the metal surface, it assists the flow  
of brazing filler.  
In the brazing process, it prevents the metal  
surface from being oxidized.  
By reducing the brazing fillers surface tension,  
the brazing filler adheres better to the treated  
metal.  
(3) Low temperature brazing filler  
Low temperature brazing filler is generally called  
solder, and is an alloy of tin and lead. Since it is  
weak in adhesive strength, do not use it for  
refrigerant pipes.  
12 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(2) Characteristics required for flux  
2-5-3. Brazing  
Activated temperature of flux coincides with  
the brazing temperature.  
Due to a wide effective temperature range, flux  
is hard to carbonize.  
It is easy to remove slag after brazing.  
The corrosive action to the treated metal and  
brazing filler is minimum.  
As brazing work requires sophisticated techniques,  
experiences based upon a theoretical knowledge, it  
must be performed by a person qualified.  
In order to prevent the oxide film from occurring in  
the pipe interior during brazing, it is effective to  
proceed with brazing while letting dry Nitrogen gas  
(N2) flow.  
It excels in coating performance and is  
harmless to the human body.  
Never use gas other than Nitrogen gas.  
(1) Brazing method to prevent oxidation  
As the flux works in a complicated manner as  
described above, it is necessary to select an  
adequate type of flux according to the type and  
shape of treated metal, type of brazing filler and  
brazing method, etc.  
Attach a reducing valve and a flow-meter to  
the Nitrogen gas cylinder.  

Use a copper pipe to direct the piping  
material, and attach a flow-meter to the  
cylinder.  
(3) Types of flux  
Noncorrosive flux  
Apply a seal onto the clearance between the  
piping material and inserted copper pipe for  
Nitrogen in order to prevent backflow of the  
Nitrogen gas.  
Generally, it is a compound of borax and boric  
acid.  
It is effective in case where the brazing  
temperature is higher than 800°C.  
ƒ
When the Nitrogen gas is flowing, be sure to  
keep the piping end open.  
Activated flux  
Most of fluxes generally used for silver brazing  
are this type.  
It features an increased oxide film removing  
capability due to the addition of compounds  
such as potassium fluoride, potassium chlo-  
ride and sodium fluoride to the borax-boric  
acid compound.  
Adjust the flow rate of Nitrogen gas so that it  
is lower than 0,05 m3/Hr or 0,02 MPa (0,2kgf/  
cm2) by means of the reducing valve.  
After performing the steps above, keep the  
Nitrogen gas flowing until the pipe cools  
down to a certain extent (temperature at  
which pipes are touchable with hands).  
(4) Piping materials for brazing and used braz-  
ing filler/flux  
Remove the flux completely after brazing.  
Piping  
material  
Used brazing  
filler  
Used  
flux  
Copper - Copper Phosphor copper Do not use  
M
Flow meter  
Copper - Iron  
Iron - Iron  
Silver  
Silver  
Paste flux  
Vapor flux  
Stop valve  
Nitrogen gas  
cylinder  
Do not enter flux into the refrigeration cycle.  

From Nitrogen cylinder  
When chlorine contained in the flux remains  
within the pipe, the lubricating oil deterio-  
rates. Therefore, use a flux which does not  
contain chlorine.  
Pipe  
Nitrogen  
gas  
When adding water to the flux, use water  
which does not contain chlorine (e.g. distilled  
water or ion-exchange water).  
ƒ
Rubber plug  
Remove the flux after brazing.  
Fig. 2-5-1 Prevention of oxidation during brazing  
13 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. CONSTRUCTION VIEWS  
3-1. Indoor Unit  
RAS-10YKV-E, RAS-13YKV-E  
Heat exchanger  
Air inlet  
Air filter  
189  
790  
Air outlet  
47  
Knock out system  
50 94  
790  
326  
Front panel  
Back body  
Hanger  
232  
232  
47  
Drain hose (0,54m)  
321  
Knock out system  
External  
Connecting pipe (0,39m)  
(Flare ø9,52)  
Connecting pipe (0,49m)  
Hanger  
length reference  
(Flare ø6,35)  
65,5  
65,5  
659  
450  
344  
326  
Hanger  
For stud bolt  
(ø8~ø10)  
Hanger  
For stud bolt  
(ø6)  
Minimum  
distance  
to ceiling  
Minimum  
distance to wall  
Minimum  
distance  
to wall  
120 or more  
120 or more  
Wireless  
remote controller  
Hanger  
Hanger  
Installation  
60,5  
126  
plate outline  
55  
16  
10,5  
76  
Center line  
269  
319  
790  
– 14 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-2. Outdoor Unit  
RAS-10YAV-E  
RAS-13YAV-E  
600  
Ø25 drain hole  
90  
A leg part  
Ø11 x 17U-shape hole  
50  
(For Ø8-Ø10 anchor bolt)  
115  
8-Ø6 hole  
(For fixing outdoor unit)  
B leg part  
Ø11 x 17 long hole  
(For Ø8-Ø10 anchor bolt)  
Ø4,5 embossing (Ø4STS used)  
(For sunshade roof attaching)  
Valve cover  
157  
Fan guard  
59  
49,5  
147  
115,5  
Hanger  
Z
Charging  
port  
780  
61  
322  
Earth terminal  
Connecting pipe port  
(Pipe dia.Ø6,35)  
Detailed A leg part  
600  
50  
R15  
36  
11  
Connecting pipe port  
(Pipe dia.Ø9,52)  
Z
view  
Outside line  
of product  
2-Ø6 hole  
Mounting dimensions of anchor bolt  
600  
4 x Ø11 x 17U-shape hole  
(For Ø8-Ø10 anchor bolt)  
D
Intake  
2-Ø6 hole  
A
11  
250 or more  
Intake  
Outside line  
of product  
100 or  
more  
C
(Minimum distance  
from wall)  
Outside line  
of product  
36  
50  
R15  
200 or more  
600  
Outlet  
4 x Ø11 × 17 long hole  
(For Ø8-Ø10 anchor bolt)  
Detailed B leg part  
B
– 15 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. WIRING DIAGRAM  
FAN MOTOR  
DC MOTOR  
4-1. Indoor Unit  
RAS-10YKV-E, RAS-13YKV-E  
LOUVER  
MOTOR  
6 5 4 3 2 1  
6 5 4 3 2 1  
5 4 3 2 1  
5 4 3 2 1  
CN10  
CN07  
R109  
VARISTOR  
5
6
R116  
BLK  
P04  
IC04  
J04  
SG01 DSA  
L01  
R01  
T6,3A 250V  
DB01  
TO1  
F01 FUSE  
DC35V  
DC12V  
DC7V  
R21  
3
INDOOR  
TERMINAL  
BLOCK  
C02  
C01  
C15  
2
BLK  
1
DC0V  
CN30  
WHI  
2
MAIN P.C. BOARD  
(MCC-772)  
C06  
RED  
3
IC02  
GRN & YEL  
IC  
IC01  
CN23  
4
CN13  
CN03  
1 2  
1 2  
CN01  
1 2  
1 2  
OUTDOOR INDOOR  
UNIT UNIT  
1 2 3 4 5 6 7 8 9  
1 2 3 4 5 6 7 8 9  
1 2 3 4 5 6 7 8 9  
INFRARED RAYS RECEIVE  
AND INDICATION PARTS  
HEAT  
EXCHANGER  
SENSOR  
(TC)  
1
CN25  
THERMO  
SENSOR  
(TA)  
Table 4-1-1 Simple check points for diagnosing faults  
COLOR  
IDENTIFICATION  
Check items  
Diagnosis result  
BRW : BROWN  
RED : RED  
WHI : WHITE  
YEL : YELLOW  
BLU : BLUE  
Check to see if the OPERATION indicator goes on and off when the main  
switch or breaker is turned on, or the power cord is plugged in the wall  
outlet. (Check the primary and secondary voltage of transformer.)  
OPERATION  
indicator  
Check for power supply voltage between  
. (Refer to the name  
 ‚  
Terminal  
block  
BLK : BLACK  
GRY : GRAY  
PNK : PINK  
plate.) (Check the primary and secondary voltage of transformer.)  
Check for fluctuate voltage between . (DC 15 to 60V)  
‚ ƒ  
Fuse  
6,3A  
Check to determine if the fuse is open.  
(Check Varistor : R109, R21)  
ORN : ORANGE  
GRN : GREEN &  
&YEL YELLOW  
Check for voltage at the pink lead of the infrared rays receive parts.  
(Check the transformer and the rated voltage power supply circuit.)  
DC 5V  
Check for voltage at the  
lead of louver motor.  
ƒ  
DC 12V  
DC 35V  
(Check the transformer and the rated voltage power supply circuit.)  
Check for voltage at the CN10 connector side point.  
(Check the transformer and the rated voltage power supply circuit.)  
For detailed diagnostic procedure, refer to the service data.  
DSA : Surge Absorber  
– 16 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4-2. Outdoor Unit  
RAS-10YAV-E, RAS-13YAV-E  
P.M.V. : Pulse Modulating Valve  
COIL  
THERMOSTAT  
FOR  
POWER  
SUPPLY  
FOR  
To  
4WAY VALVE  
COMPRESSOR 220/240V~  
50/60Hz  
INDOOR  
UNIT  
TE  
TD  
TO  
TS  
FAN MOTOR  
FM  
~ ~ ~  
~ ~ ~ ~  
REACTOR  
P. M . V.  
L
N
1
2
3
1
1
2
2
1
1
2
2
1
1
2
2
3
3
1
1
2
2
1
1
2
2
3
3
5
5
4
4
3
3
2
2
1
1
1
1
2
2
3
3
1
1
2
2
3
3
6
6
5
5
4
4
3
3
2
2
1
1
1
1
2
2
BLK  
P06  
CN600  
CN601  
CN602  
CN603  
P08 P07  
CN301  
CN300  
CN701  
CN703  
CN500 P01 P02  
P03  
P.C. BOARD  
MCC-808  
F01  
FUSE  
25A  
SURGE  
ABSORBER  
RELAY  
VARISTOR  
CT  
P09  
P10  
ORN  
P11  
1
2
1
2
POWER RELAY  
P12  
P13  
REACTOR  
C13  
G
E
A
~
PUR  
P14  
ELECTRONIC  
STARTER  
F03  
FUSE  
15A  
C12 C14  
F04  
FUSE  
3,15A  
~
+
DB01  
RELAY  
P19  
YEL  
P20  
+
BU  
EU  
BV  
EV  
BW  
EW  
BX  
BY  
BZ  
Q200  
BLU  
P21 RED  
P22 WHI  
P23 BLK  
1
2
3
1
2
3
COLOR IDENTIFICATION  
CM  
P18  
P17  
COMPRESSOR  
BLK : BLACK  
BLU : BLUE  
RED : RED  
GRY : GRAY  
PNK : PINK  
WHI : WHITE  
BRW : BROWN  
ORN : ORANGE  
YEL :YELLOW  
PUR : PURPLE  
– 17 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. SPECIFICATIONS OF ELECTRICAL PARTS  
5-1. Indoor Unit  
RAS-10YKV-E, RAS-13YKV-E  
No.  
1
Parts name  
Fan motor (for indoor)  
Thermo. sensor (TA-sensor)  
DC-DC transformer (T01)  
Microcomputer  
Type  
TICF-35-19-4  
Specifications  
DC35V, 19W  
2
( – )  
10kat 25°C  
3
SWT-34 or SWT-46  
TMP87PM40AF or TMP87CM40AF  
DC390V, Secondary DC35V, 12V, 7V  
4
Heat exchanger temp. sensor  
(TC-sensor)  
5
( – )  
10kat 25°C  
6
7
8
9
Line filter (L01)  
Diode (DB01)  
Capacitor (C02)  
Fuse (F01)  
UF-253Y0R7  
RBV-406 or D3SBA60  
KMH450VNSN100M25B  
TSCR6,3A  
25mH, AC0,7A  
4A, 600V  
100µF, 450V  
T6,3A, 250V  
10 Power supply IC (IC01)  
11 Varistor (R21, R109)  
12 Resistor (R01)  
MA2830-FJ  
4A, 600V  
15G561K  
560V  
ERF-5TK5R6  
5,6, 5W  
13 Louver motor  
MP35EA7  
Output (Rated) 2W, 10poles, 1phase DC12V  
5-2. Outdoor Unit  
RAS-10YAV-E, RAS-13YAV-E  
No.  
Parts name  
Model name  
SC-15-S06J  
SC-20-01J  
Rating  
15A, 0,6mH  
L03  
L01  
SC coil  
(Noise filter)  
1
20A, 150µH  
Primary side DC280V, Secondary side  
7,5V x 1, 13V x 1, 26,5V x 3, 16V x 1, 15V x 1  
2
DC-DC transformer  
SWT-43  
3
4
Reactor  
CH38Z-K  
L=10mH, 16A x 2  
DC140V, 40W  
Outside fan motor  
ICF-140-40-7  
Coil DC12V  
Contact AC125V, 3A  
5
6
7
8
9
Fan control relay  
AJQ1341  
Suction temp. sensor  
(TS sensor)  
(Inverter attached)  
(Inverter attached)  
(Inverter attached)  
(Inverter attached)  
10k(25°C)  
62k(20°C)  
10k(25°C)  
10k(25°C)  
Discharge temp. sensor  
(TD sensor)  
Outside air temp. sensor  
(TO sensor)  
Heat exchanger temp.  
sensor (TE sensor)  
10 Terminal block (9P)  
——  
20A, AC250V  
For protection of switching power source  
3,15A, AC250V  
11 Fuse  
For protection of transistor module breakage 15A, AC250V  
For protection of inverter input overcurrent  
LLQ2G501KHUATF, 400LISN500K35F  
25A, AC250V  
12 Electrolytic capacitor  
13 Transistor module  
14 Compressor  
500µF, DC400V X 3 pieces  
6MBI25GS-060-01 or 6MBI25GS-060-01A 25A, 600V  
DA91A1F-44F  
US-622KXTMQO-SS  
MP7003  
3-phases 4-poles 750W  
15 Compressor thermo.  
16 Converter module  
OFF: 125 4°C, ON: 90 5° C  
Diode: 25A, 600V, IGBT: 40A, 600V  
– 18 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. REFRIGERANT CYCLE DIAGRAM  
6-1. Refrigerant Cycle Diagram  
RAS-10YKV-E/RAS-10YAV-E  
RAS-13YKV-E/RAS-13YAV-E  
T1 Temp. measurement  
INDOOR UNIT  
Indoor heat  
exchanger  
Cross flow fan  
P
Pressure measurement  
Deoxidized copper pipe  
Outer dia. : 6,35mm  
Thickness : 0,8mm  
Max. : 15m  
Gauge attaching port  
Vacuum pump connecting port  
Sectional shape  
of heat insulator  
Deoxidized copper pipe  
Outer dia. : 9,52mm  
Thickness : 0,8mm  
Strainer  
Muffler  
4-way valve  
(CHV-0213)  
Pulse modulating  
valve at liquid side  
(SEV15RC2)  
Muffler  
TD  
Compressor  
DA91A1F-44F  
TS  
Outdoor heat  
exchanger  
Split capillary  
Ø1,5 x 200  
Ø1,5 x 200  
TE  
Temp. measurement  
T2  
Refrigerant amount : 0,8kg  
Propeller fan  
Gas leak check position  
Refrigerant flow (Cooling)  
Refrigerant flow (Heating)  
OUTDOOR UNIT  
NOTE :  
NOTE :  
• The maximum pipe length of this air conditioner is 15 m. The additional charging of refrigerant is unneces-  
sary because this air conditioner is designed with charge-less specification.  
– 19 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6-2. Operation Data  
<Cooling>  
Temperature  
condition (°C)  
Heat exchanger  
pipe temp.  
Standard  
pressure  
P (MPa)  
Compressor  
revolution  
(rps)  
Indoor fan Outdoor fan  
Model name  
mode  
mode  
Indoor Outdoor  
T1 (°C)  
9 to 11  
8 to 10  
T2 (°C)  
42 to 44  
46 to 48  
10YKV-E  
13YKV-E  
0,8 to 1,0  
0,8 to 1,0  
High  
High  
High  
High  
56  
85  
27/19  
35/–  
<Heating>  
Temperature  
condition (°C)  
Heat exchanger  
pipe temp.  
Standard  
pressure  
P (MPa)  
Compressor  
revolution  
(rps)  
Indoor fan Outdoor fan  
Model name  
mode  
mode  
Indoor Outdoor  
T1 (°C)  
42 to 44  
50 to 52  
T2 (°C)  
2 to 4  
0 to 3  
10YKV-E  
13YKV-E  
3,5 to 3,7  
2,5 to 2,7  
High  
High  
High  
High  
70  
97  
20/–  
7/6  
NOTES :  
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.  
(Thermistor themometer)  
(2) Connecting piping condition : 5 m  
– 20 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. CONTROL BLOCK DIAGRAM  
7-1. Indoor Unit  
RAS-10YKV-E, RAS-13YKV-E  
Indoor Unit Control Panel  
M.C.U  
Heat Exchanger Sensor  
Temperature Sensor  
Functions  
Operation  
Display  
• Louver Control  
Timer  
Display  
Infrared Rays Signal Receiver  
• 3-minute Delay at Restart for Compressor  
ECONO.  
Initializing Circuit  
• Motor Revolution Control  
Infrared  
Rays  
Sign Display  
Clock Frequency  
Oscillator Circuit  
• Processing  
(Temperature Processing)  
PRE DEF.  
Sign Display  
• Timer  
Indoor  
Fan Motor  
• Serial Signal Communication  
Power Supply  
Circuit  
Louver ON/OFF Signal  
Remote  
Controller  
Louver  
Motor  
Noise Filter  
Louver Driver  
Serial Signal Transmitter/Receiver  
From Outdoor Unit  
Serial Signal Communication  
REMOTE CONTROLLER  
Infrared  
Rays  
Remote Controller  
Operation (START/STOP)  
Operation Mode Selection  
AUTO, COOL, DRY, HEAT  
Thermo. Setting  
Fan Speed Selection  
ON TIMER Setting  
OFF TIMER Setting  
Louver AUTO Swing  
Louver Direction Setting  
ECONO.  
– 21 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MICRO-COMPUTER BLOCK DIAGRAM  
For INDOOR UNIT  
220–230–240 V  
~ 50/60 Hz  
MCC808 (P.C.B)  
OUTDOOR UNIT  
Inddor unit  
send/receive  
circuit  
Rotor position  
detect circuit  
M.C.U  
• PWM synthesis function  
Rotor position  
detect circuit  
• Input current release control  
• IGBT over-current detect control  
• Outdoor fan control  
Discharge  
temp. sensor  
Gate drive  
circuit  
• High power factor correction control  
• Inverter output frequency control  
• A/D converter function  
Outdoor air  
temp. sensor  
Gate drive  
circuit  
• P.M.V. control  
• Discharge temp. control  
• 4-way valve control  
Suction temp.  
sensor  
Over current  
detect circuit  
• Signal communication to indoor unit  
Heat exchanger  
temp.sensor  
Over current  
sensor  
High Power  
factor Correction  
circuit  
Clock  
frequency  
16MHz  
Noise  
Filter  
Input current  
sensor  
Converter  
Outdoor  
Over current  
sensor  
Inverter  
(DC AC)  
(AC  
DC)  
Fan motor  
Driver circuit  
of P.M.V.  
Relay  
circuit  
Over current  
sensor  
Inverter  
(DC AC)  
Compressor  
4-way  
valve  
P.M.V.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. OPERATION DESCRIPTION  
(1) Role of indoor unit controller  
8-1. Outline of Air Conditioner Control  
The indoor unit controller judges the operation  
commands from the remote controller and  
assumes the following functions.  
This air conditioner is a capacity-variable type air  
conditioner, which uses DC motor for the indoor fan  
motor and the outdoor fan motor. And the capacity-  
proportional control compressor which can change  
the motor speed in the range from 13 to 120 rps is  
mounted. The DC motor drive circuit is mounted to  
the indoor unit. The compressor and the inverter to  
control fan motor are mounted to the outdoor unit.  
The entire air conditioner is mainly controlled by the  
indoor unit controller.  
• Judgment of suction air temperature of the  
indoor heat exchanger by using the indoor  
temp. sensor.  
Temperature setting of the indoor heat ex-  
changer by using heat exchanger sensor  
(Prevent-freezing control)  
• Louver motor control  
The indoor unit controller drives the indoor fan motor  
based upon command sent from the remote control-  
ler, and transfers the operation command to the  
outdoor unit controller.  
• Indoor fan motor operation control  
• LED display control  
Transferring of operation command signal  
(Serial signal) to the outdoor unit  
The outdoor unit controller receives operation  
command from the indoor unit side, and controls the  
outdoor fan and the pulse modulating valve.  
• Reception of information of operation status  
(Serial signal including outside temp. data) to  
the outdoor unit and judgment/display of error  
Besides, detecting revolution position of the com-  
pressor motor, the outdoor unit controller controls  
speed of the compressor motor by controlling output  
voltage of the inverter and switching timing of the  
supply power (current transfer timing) so that motors  
drive according to the operation command. And  
then, the outdoor unit controller transfers reversely  
the operating status information of the outdoor unit  
to control the indoor unit controller.  
(2) Role of outdoor unit controller  
Receiving the operation command signal (Serial  
signal) from the indoor controller, the outdoor  
unit performs its role.  
• Compressor operation  
control  
Operations followed  
to judgment of serial  
signal from indoor  
side.  
• Operation control of  
outdoor fan motor  
As the compressor adopts four-pole  
brushless DC motor, the frequency of the  
supply power from inverter to compressor is  
two-times cycles of the actual number of  
revolution.  
P.M.V. control  
• Detection of inverter input current and current  
release operation  
• Over-current detection and prevention opera-  
tion to transistor module (Compressor stop  
function)  
• Compressor and outdoor fan stop function  
when serial signal is off (when the serial signal  
does not reach the board assembly of outdoor  
control by trouble of the signal system)  
Transferring of operation information (Serial  
signal) from outdoor unit to indoor unit  
• Detection of outdoor temperature and opera-  
tion revolution control  
• Defrost control in heating operation (Temp.  
measurement by outdoor heat exchanger and  
control for four-way valve and outdoor fan)  
– 23 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(3) Contents of operation command signal (Serial  
signal) from indoor unit controller to outdoor unit  
controller  
8-1-1. Capacity Control  
The cooling and heating capacity is varied by  
changing compressor motor speed.The inverter  
changes compressor motor speed by changing AC  
220–230–240V power to DC once, and controls  
capacity by changing supply power status to the  
compressor with transistor module (includes 6  
transistors).The outline of the control is as follows:  
The revolution position and revolution speed of the  
motor are detected by detecting winding electromo-  
tive force of the compressor motor under operation,  
and the revolution speed is changed so that the  
motor drives based upon revolution speed of the  
operation command by changing timing (current  
transfer timing) to exchange inverter output voltage  
and supply power winding.  
The following three types of signals are sent  
from the indoor unit controller.  
• Operation mode set on the remote control  
• Compressor revolution command signal defined  
by indoor temperature and set temperature  
(Correction along with variation of room  
temperature and correction of indoor heat  
exchanger temperature are added.)  
• For these two types of signals ( [Operation  
mode] and [Compressor revolution] ), the  
outdoor unit controller monitors the input  
current to the inverter, and performs the  
followed operation within the range that  
current does not exceed the allowable value.  
Detection of the revolution position for controlling is  
performed 12 times per 1 revolution of compressor.  
The range of supply power frequency to the com-  
pressor differs according to the operation status  
(COOL, HEAT, DRY).  
Temperature of indoor heat exchanger by indoor  
heat exchanger sensor  
(Minimum revolution control)  
(4) Contents of operation command signal (Serial  
signal) from outdoor unit controller to indoor unit  
controller  
Table 8-1-1 Compressor revolution range  
Operation  
mode  
Compressor  
revolution (rps)  
Model name  
The following signals are sent from the outdoor  
unit controller.  
10YKV-E  
13YKV-E  
10YKV-E  
13YKV-E  
13 to 74  
13 to 94  
16 to 110  
16 to 114  
COOL  
HEAT  
• The current operation mode  
• The current compressor revolution  
• Outdoor temperature  
• Existence of protective circuit operation  
8-1-2. Current Release Control  
For transferring of these signals, the indoor  
unit controller monitors the contents of signals,  
and judges existence of trouble occurrence.  
The outdoor main circuit control section (Inverter  
assembly) detects the input current to the outdoor  
unit. If the current value with compressor motor  
speed instructed from indoor side exceeds the  
specified value, the outdoor main circuit control  
section controls compressor motor speed by reduc-  
ing motor speed so that value becomes closest to  
the command within the limited value.  
Contents of judgment are described below.  
• Whether distinction of the current operation  
status meets to the operation command  
signal  
• Whether protective circuit operates  
When no signal is received from the  
outdoor unit controller, it is assumed as a  
trouble.  
8-1-3. Power Factor Improvement Control  
Power factor improvement control is performed  
mainly aiming to reduce the current on much power  
consumption of cooling/heating operation. Control-  
ling starts from the time when input power has  
reached at a certain point.To be concrete, IGBT of  
the power factor improvement circuit is used, and  
the power factor is improved by keeping IGBT on for  
an arbitrary period to widen electro-angle of the  
input current.  
– 24 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8-1-4. Prevent-Freezing Control  
8-1-6. Louver Control  
The indoor heat exchanger sensor detects refriger-  
ant vapor temperature in COOL/DRY operation.  
If the temperature is below the specified value,  
compressor motor speed is reduced so that opera-  
tion is performed in temperature below the specified  
value to prevent-freezing of indoor heat exchanger.  
(1) Vertical air flow louvers  
Positions of vertical air flow louvers are auto-  
matically controlled according to the operation  
status (AUTO, COOL, DRY, HEAT). Besides,  
positions of vertical air flow louvers can be  
arbitrarily set by pressing the [SET] button.  
The louver position which has been set by the  
[SET] button is stored in microcomputer, and the  
louver is automatically set at the stored position  
in the next operation.  
8-1-5. P. M. V. (Pulse Modulating Valve)  
Using P.M.V., refrigerant flow of refrigeration cycle is  
varied for the optimum temperature. Controlling  
each unit separately by two P.M.V. corresponds to  
difference of pipe length, fan speed, and unit tem-  
perature.  
(2) Swing  
If the [AUTO] button is pressed during running  
operation, vertical air flow louvers start swinging.  
When the [AUTO] button is pressed again,  
swinging stops.  
After the power has been turned on, when a serial  
operation signal is received from indoor at the first  
time, or when PMV alarm is detected and the  
equipment is reactivated, move the valve once until  
it hits on the stopper for positioning of the valve.  
In this case, ticktack sound may be heard.  
8-1-7. Indoor Fan Control (DC Fan Motor)  
The indoor fan is operated by motor speed non-step  
variable DC drive system motor. For flow rate, motor  
speed is controlled manually in three steps (LOW,  
MED, HIGH), and with the unit of 10 rpm from upper  
limit to lower limit in AUTO mode as described in  
Table 8-1-2. It is not selected by relay, so selecting  
sound does not generate.  
Table 8-1-2  
RAS-10YKV-E  
RAS-13YKV-E  
Operation  
mode  
Fan mode  
Motor speed  
(rpm)  
Air flow rate  
(m³/h)  
Motor speed  
Air flow rate  
(m³/h)  
(rpm)  
1210  
1020  
850  
H
M
L
1120  
980  
480  
400  
330  
320  
520  
450  
380  
530  
420  
330  
320  
560  
470  
380  
COOL  
DRY  
850  
H
M
L
820  
820  
1200  
1070  
930  
1270  
1100  
930  
HEAT  
25 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8-1-8. Outdoor Fan Control (DC Fan Motor)  
Although the outdoor fan motor drives the outdoor fan by non-step variable system of the revolution speed, the  
revolution speed is restricted to three steps on the convenience of controlling. If a strong wind is lashing outside  
of the room, the operation may be continued as the outdoor fan stops in order to protect the outdoor fan motor.  
If a fan lock occurred due to entering of foreign matter, the air conditioner stops and an alarm is displayed.  
<COOL, DRY>  
Table 8-1-3  
Model name  
Compressor revolution (rps)  
TO 38°C  
RAS-10YAV-E  
To 34,1  
800  
RAS-13YAV-E  
To 34,1  
940  
To 13,2  
450  
From 34,7  
800  
To 13,2  
450  
From 34,7  
940  
Outdoor temp. sensor  
TO < 38°C  
450  
630  
800  
450  
700  
940  
TO  
TO < 15°C  
390  
390  
TO 38°C  
450  
450  
630  
800  
630  
450  
450  
700  
940  
700  
ECONO. operation  
TO is abnormal  
<HEAT>  
TO < 38°C  
450  
450  
TO < 15°C  
390  
390  
630  
630  
800  
700  
700  
940  
Table 8-1-4  
Model name  
Compressor revolution (rps)  
RAS-10YAV-E  
To 44,3  
580  
RAS-13YAV-E  
To 44,3  
650  
To 16,2  
390  
From 44,9  
800  
To 16,2  
390  
From 44,9  
900  
TO 5°C  
TO < 5°C  
TO 5°C  
TO < 5°C  
Outdoor temp. sensor  
TO  
580  
580  
800  
650  
650  
940  
390  
390  
580  
390  
390  
650  
ECONO. operation  
TO is abnormal  
390  
580  
580  
390  
650  
650  
390  
580  
800  
390  
650  
900  
8-2. Description of Operation Circuit  
Turning [ON] the breaker flashes the operation lamp.  
This is the display of power-ON (or notification of power failure).  
When pushing [START/STOP] button of the remote control, receive sound is issued from the main unit, and  
the next operations are performed together with opening the vertical air flow louvers.  
26 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(1) Cooling capacity control  
8-2-1. Cooling Operation  
(The Remote Controller MODE Button  
• The cooling capacity and room temperature  
are controlled by changing the compressor  
motor speed according to both the difference  
between the temperature detected by the  
room temperature sensor and the temperature  
set by TEMP button and also any change in  
room temperature.  
is Set to the COOL Position)  
• Once the setting is made, the operation mode is  
memorized in the microcomputer so that the  
same operation can be effected thereafter simply  
by pushing [START/STOP] button.  
• A cooling operation signal is transmitted to  
outdoor unit.  
• When compressor has been activated or  
reactivated, it operates with Max. 41 rps for 2  
minutes, with Max. 91 rps from 2 minute to 3  
minutes, and with Max. 94 rps after 3 minutes  
passed.  
• The indoor fan motor operates as shown in Fig.  
8-2-1 when FAN button is set to AUTO.  
• The motor operates with a constant air flow when  
the FAN button is set to LOW, MED, or HIGH.  
• When room temperature is lower than set  
temperature, indoor fan motor is operated at  
fan speed L– as shown in Fig. 8-2-1 while the  
outdoor unit stops.  
• The outdoor unit controls the outdoor fan relay  
R01, R02 and R03, and the compressor motor  
speed according to the operation command  
signal sent from the indoor unit.  
(2) Prevent-freezing control  
If temperature of indoor heat exchanger de-  
tected by the indoor heat exchanger sensor is  
5°C or lower, compressor motor speed is  
gradually lowered to prevent freezing of the  
indoor heat exchanger. If temperature is 7°C or  
higher, return the operation to the above item  
(1).  
˚C  
+3  
M+  
+2,5  
*1  
+2  
*1  
+1,5  
(3) Current release control  
*1  
+1  
The input current of compressor and outdoor fan  
motor (Precisely inverter main circuit control  
section) which occupy most of air conditioner  
input is detected by the outdoor current sensor,  
and compressor motor speed is gradually  
lowered so that current value does not exceed  
9,0A if current value exceeds 9,0A. When the  
current value lowers to 8,5A, return the opera-  
tion to the above item (1).  
L–  
+0,5  
Set  
0
In normal  
operation  
temp.  
0,5  
NOTE :  
1: Calculated from difference in motor speed of  
M+ and L–, and controlled.  
*
Comp. motor  
speed down  
9,0  
Fig. 8-2-1 Setting of air flow [Fan AUTO]  
Comp. motor  
speed keep  
8,5  
Normal control  
Fig. 8-2-2  
(4) Outdoor temperature release control  
The outdoor temperature release is controlled by  
changing the current release points 9,0 and 8,5  
in the above item according to temperature  
detected by the outdoor temperature sensor.  
For example, if the outdoor temperature is 43°C,  
the value of current release point becomes 8,0A.  
– 27 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(5) Limit for maximum compressor motor speed  
by indoor fan speed  
(7) Discharge temperature control  
(Common control to cooling and heating)  
When outdoor temperature sensor detected  
32°C or lower, and indoor heat exchanger  
sensor detected 17°C or lower, the maximum  
compressor motor speed is limited by the indoor  
fan speed.  
The discharge temperature of refrigerant gas  
from the compressor is detected by the dis-  
charge temperature sensor, and controls operat-  
ing compressor motor speed.  
1) Control 1 (A zone) : Normal operation zone  
For example, the compressor motor speed is  
limited as described in the table below.  
When TD detect value is 98°C or lower, the  
operation is performed with operating motor  
speed instructed by the serial signal.  
Table 8-2-1  
2) Control 2 (B zone) : Slow-up zone of motor  
speed  
RAS-10YKV-E RAS-13YKV-E  
Air flow rate  
(rps)  
56  
(rps)  
85  
When TD detect value is 98°C or higher,  
operating motor speed is slowly up.  
HIGH  
M+  
49  
71  
3) Control 3 (C zone) : Keep zone  
MED.  
L–, L  
43  
57  
When TD detect value is 105°C or higher,  
operating motor speed is not changed if  
raising operation speed.  
36  
44  
UL, SUL  
30  
30  
4) Control 4 (D zone) : Slow down zone of motor  
speed  
When TD detect value is 108°C or higher,  
operating motor speed is slowly down.  
(6) Louver control  
The vertical air flow louvers are automatically set  
to horizontal or cool memory position.  
5) Control 5 (E zone) : Normal down of motor  
speed  
When temperature of indoor heat exchanger  
becomes 5°C or lower by the prevent-freezing  
control and the compressor is turned off, the  
vertical air flow louvers close once and then  
return to the position of previous time.  
When TD detect value is 112°C or higher,  
operating motor speed is down.  
6) Control 6 (F zone) : Operation stop zone  
If TD detect value exceeds 117°C during  
operation, stop the operation immediately.  
Then, restart the operation when TD detect  
value becomes 105°C or lower.  
TD  
(˚C)  
Zone  
F
Operation stop zone  
117  
112  
108  
E
D
Normal down zone of motor speed  
Slow down of motor speed  
Release of motor speed  
C
B
Keep zone : Motor speed is not changed.  
Slow-up zone of motor speed  
105  
98  
A
Normal operation zone  
Fig. 8-2-3 Compressor motor speed control  
– 28 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(8) ECONO. operation control  
2) Setting 10 at 16 rps and 13 at 20 rps as the  
maximum operating compressor motor  
When the ECONO. button of the remote control-  
ler is pushed, quiet and mild operation is per-  
formed by restraining air flow and operating  
motor speed.  
speed, the minimum capacity operation range  
is widened every 1 hour and 2 hours have  
passed after ECONO. operation had started.  
1) Indoor air flow is controlled between SUL  
and L– (Low air (–)).  
Compressor motor speed  
10  
13  
Air volume  
L–  
16 rps  
15 rps  
20 rps  
17 rps  
3,5  
3
{(L–) + (SUL)}/2  
2,5  
2
SUL  
13 rps  
13 rps  
1,5  
1
0,5  
1H  
2H  
Time  
Fig. 8-2-4  
8-2-2. DRY Operation  
(The Remote Controller MODE Button  
is Set to the DRY Position)  
+2,5  
+2,0  
+1,5  
+1,0  
+0,5  
0
• Once the setting is made, the operation mode is  
memorized in the microcomputer so that the  
same operation can be effected thereafter simply  
by pushing [START/STOP] button.  
L–  
*1  
• Dry operation signal is transmitted to outdoor  
unit.  
SUL  
• The Cooling operation giving priority to dehumidi-  
fying, which restrains the indoor fan speed and  
compressor motor speed, is performed.  
Set  
temp.  
• The indoor fan motor operates as shown in Fig.  
8-2-5. (Fan speed is AUTO only.)  
–0,5  
• The outdoor unit controls the outdoor fan relay  
R01, R02 and R03, and the compressor motor  
speed according to the operation command  
signal sent from the indoor unit.  
NOTE :  
*1 : Middle motor speed between L– and SUL  
Fig. 8-2-5 Setting of air flow  
– 29 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
[In starting and in stability]  
8-2-3. Heating Operation  
Transferring of heating operation signal from indoor  
unit to outdoor unit starts.  
In starting  
In stability  
• Until 12 minutes  
passed after  
operation start  
• When 12 to 25  
minutes passed  
after operation start  
and room temp. is  
higher than (set  
temp. –3°C)  
The indoor fan motor operates by the room tempera-  
ture when selecting “AUTO” of “FAN” as shown in  
Fig. 8-2-6, and operates with a set air flow when  
selecting “Low” to “High”.  
• When 12 to 25  
FAN  
minutes passed  
AUTO  
However, to prevent cold draft, revolution speed of  
the fan is restricted by indoor heat exchanger when  
air flow is AUTO (Fig. 8-2-7) and starting of FAN  
Manual.  
after operation start  
and room temp. is  
3°C or lower than  
set temp.  
• When 25 minutes or  
more passed after  
operation start  
FAN  
Manual  
• Room temp. < Set  
temp. –4°C  
• Room temp. Set  
temp. –3,5°C  
[Basic control]  
LOW  
Set  
temp.  
0
–0,5  
–1  
–1,5  
–2  
The outdoor unit controls the outdoor fan based  
upon the operation signal sent from the indoor unit,  
and also controls revolution speed of the compres-  
sor motor.  
1
*
2
*
M+  
The power coupler (IC20) for four-way valve is  
turned on, and turned off in defrost operation.  
–5,0  
–5,5  
(1) Heating capacity control  
HIGH  
[FAN AUTO]  
Calculate the difference between temperature  
detected by room temp. sensor every minute and  
the set temp. set on “Temp. indicator” and  
variation amount of room temp.  
*1, *2 : Approximate revolution speed of M+ and L to  
linear according to temperature.  
Fig. 8-2-6 Setting of air flow  
Then, obtain the correction amount of the  
command signal, and correct the current fre-  
quency command signal.  
[Cold draft preventing control]  
The upper limit of fan revolution speed is shown  
below.  
(2) High-temp. release control  
If temperature of the indoor heat exchanger  
detected by the indoor heat exchanger sensor is  
55°C or higher, compressor motor speed is  
gradually lowered to prevent over-temp. rising of  
compressed pressure.  
HIGH  
44  
43  
33  
32  
Approximate  
revolution speed  
of HIGH and SUL  
linear by Tc.  
If temperature becomes below 48°C, return to  
above item (1).  
31  
30  
20  
19  
3
*
SUL  
(3) Current release control  
2
*
A
A + 4  
The input current of compressor and outdoor fan  
motor (Precisely inverter main circuit control  
section) which occupy most of air conditioner  
input is detected by the outdoor current sensor.  
The compressor motor speed is lowered gradu-  
ally according to the range of TO (outside air  
temp.) if the input current exceeds the current  
value determined in each zone as shown in Fig.  
8-2-8 so that the input current does not exceed  
the set value.  
( NOTE : 1)  
SUL  
Stop  
*
A – 8 A – 8  
Starting  
FAN  
of FAN  
AUTO  
Manual  
Fig. 8-2-7 Cold draft preventing control  
NOTES :  
(1) Stops for 2 minutes after thermostat-OFF.  
(2) 24°C when the set temp. is 24°C or more  
Set temp. when the set temp. is below 24°C  
In case that the current lowered by approx. 0,5A  
than each set value, return to above item (1).  
(3) SUL : Super ultra low  
– 30 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2) Defrost operation  
Operation of the compressor is stopped  
once, turn off power coupler for four-way  
valve after 10 seconds, and then exchange  
the four-way valve.  
TO  
10,8A  
10,3A  
9,8A  
16,0  
15,5  
11,0  
10,5  
After 20 seconds, restart operation of the  
compressor. Turn off the outdoor fan just  
when the compressor stopped.  
If temperature of the indoor heat exchanger  
lowered than 38°C, stop the indoor fan.  
3) Defrost reset  
Fig. 8-2-8  
Resetting operation from defrost to heating is  
performed when any one of the following  
conditions is satisfied.  
(4) Defrost control  
1) Detection of frost  
a. Temperature of the outdoor heat ex-  
changer rose to +8°C or higher.  
In heating operation, time duration while the  
compressor operates is counted, and defrost  
operation starts by any condition described  
below.  
b. A status that temperature of the outdoor  
heat exchanger is +5°C or higher contin-  
ued for 80 seconds.  
a. The counted time is 28 minutes or more,  
and status that temperature of the outdoor  
heat exchanger detected by the outdoor  
heat exchanger is –20°C or lower contin-  
ued for 2 minutes or more.  
c. Defrost operation continued for 10 min-  
utes.  
In resetting defrost operation, the compressor  
stops for 50 seconds if defrost has started  
under condition a. to c. in item 1), but the  
compressor is reset to heating operation  
keeping operated if defrost has started under  
condition d. in item 1).  
b. The counted time is 28 minutes or more,  
and status that temperature of the outdoor  
heat exchanger detected by the outdoor  
heat exchanger is –7°C or lower and  
temperature lowered by 2,5 °C than the  
minimum value of the outdoor heat ex-  
changer during 10 to 15-minutes count  
time continued for 2 minutes or more.  
(5) Louver control  
The vertical air flow louvers are automatically set  
to heating position or heat memory position.  
When the compressor is turned off by high-temp.  
release control, the vertical air flow louvers close  
once and then return to the position of previous  
time.  
c. The counted time is 34 minutes or more,  
and status that temperature of the outdoor  
heat exchanger detected by the outdoor  
heat exchanger is –5°C or lower and  
temperature lowered by 3,0 °C than the  
minimum value of the outdoor heat ex-  
changer during 10 to 15-minutes count  
time continued for 2 minutes or more.  
d. If the following three conditions are satis-  
fied, defrost operation (Timer defrost)  
starts after heating operation for 37  
minutes.  
 Setting on remote control, HEAT  
(mode), HIGH (Fan), 30°C (temp.).  
Room temp. is 19°C to 24°C, and  
outside air temp. is 5°C or lower.  
ƒ Defrost operation has been already  
performed once.  
– 31 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(2) After selecting the operation mode (COOL, DRY,  
HEAT), select an operation mode again when a  
status that the compressor was turned off by the  
room temperature or outside air temperature  
continues for 15 minutes.  
8-2-4. Automatic Operation  
(1) As shown in Fig. 8-2-9, the operation mode  
(COOL, DRY, HEAT) is selected according to the  
outside temperature and room temperature  
when the operation has started.  
(3) Powerful Cool mode control  
The operation in Fan mode continues until an  
operation mode is selected.  
When the outside temperature is above 32°C  
and indoor temperature is above 28°C, select  
Cool mode control. In Cool mode, the air flow  
louver directs downward. When the room tem-  
perature gains access to the set temperature, it  
becomes cool memory position.  
If the room temperature is 20°C or higher when  
AUTOoperation started within 2 hours after  
HEAToperation had stopped, select an opera-  
tion mode after Fan operation of ultra low fan.  
In AUTO operation, the set temperature of each  
operation can be corrected by the remote  
controller in the range of 17 to 30°C.  
Powerful Cooling/Drying with  
setting on remote controller  
Ts = 25˚C  
TA  
28  
Cooling/Drying with setting on remote controller  
Ts = 25˚C  
26  
24  
23  
Monitoring  
(Follow to the Fan control in previous  
mode when being selected again.)  
Heating with setting  
on remote controller  
Ts = 25˚C  
20  
Ts correction by outside  
temperature ( To)  
5
15 18  
1  
24  
32  
To  
2  
0
+1  
Fig. 8-2-9  
8-3-1. Temporary Auto Operation  
8-3. Temporary Operation  
When the TEMPORARY button is pushed, the  
Auto operation with set temperature fixed at 25°C  
starts. Controlling is same as that of Auto opera-  
tion by the remote controller.  
Temporary Auto operation, existence of Auto  
Restart, and Temporary Cooling operation can be  
set by the TEMPORARY button of the indoor  
controller.  
When the TEMPORARY button is pushed again,  
the operation stops.  
During Temporary Auto operation, operation by  
the remote controller is accepted.  
Using the Auto Restart function, the Temporary  
Auto operation starts when power failure is reset.  
8-3-2. Temporary Cooling Operation  
TEMPORARY  
button  
TEMPORARY  
When the TEMPORARY operation button keeps  
pushed for 10 seconds, Cooling operation of  
which compressor motor speed and the indoor  
fan speed are fixed starts.  
Table 8-3-1  
Compressor motor speed :  
10 : 30 rps  
TEMPORARY button  
Control  
13 : 30 rps  
OFF ON  
Temporary Auto operation start  
Indoor fan speed : Low  
After pushing button  
for 3 seconds  
Auto Restart control select  
When the TEMPORARY operation button is  
pushed again, the operation stops.  
After pushing button  
for 10 seconds  
Temporary Cooling  
operation start  
Auto Restart function is unavailable.  
– 32 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8-4-1. How to Set the Auto Restart  
8-4. Auto Restart Function  
To set the Auto Restart function, proceed as follows:  
This unit is equipped with an Automatic restarting  
facility which allows the unit to restart and resume  
the set operating conditions in the event of a power  
supply shutdown without the use of the hand control.  
Access the TEMPORARY button located in the lower  
right hand corner beneath the hinged front panel of  
the indoor unit (please refer to Fig. 8-2-9). The  
power supply to the unit must be on - the function  
will not be set if the power is off.  
The operation will resume without warning three  
minutes after the power is restored.  
To enable the Auto Restart function, push the  
TEMPORARY button continuously for three  
seconds.  
The Auto Restart function is set not to work on  
shipment from the factory, and so it is necessary to  
set it to function as required.  
The unit will acknowledge the setting and beep three  
times. The system will now restart automatically.  
The above Auto Restart settings can be carried out:  
• When the system is stand-by (not operating)  
Operation  
Motion  
Push the TEMPORARY button  
continuously more than three  
seconds.  
Stand-by  
The system starts to operate.  
about three seconds after  
The unit beeps three times.  
The green light goes on.  
The orange light goes on.  
0
3S  
The system is operating.  
TEMPORARY  
If the system is not required to run at this time, push the TEMPORARY  
button once more or use the remote controller and the unit will stop.  
• When the system is operating  
Operation  
Motion  
Push the TEMPORARY button  
continuously more than three  
seconds.  
Operating  
The green light goes on.  
The green light goes off.  
The system stops to operate.  
about three seconds after  
The unit beeps three times.  
0
3S  
The system stops.  
TEMPORARY  
If the system is not required to stop at this time, use the remote  
controller and to restart.  
During subsequent operation, the orange light goes on.  
During louver swing (AUTO) operation, after  
restart by the Auto Restart function the louver  
swing stops.  
The Auto Restart function will not accept an  
instruction if timer operation with the remote  
controller is selected.  
– 33 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The system will now be required to manually restart  
with the remote controller after the main supply is  
turned off.  
8-4-2. How to Cancel the Auto Restart  
To cancel the Auto Restart function, proceed as  
follows:  
Cancellation is carried out:  
Repeat the setting procedure: the unit will  
acknowledge the instruction and beep three times.  
When the system is stand-by (not operating)  
Operation  
Motion  
Push the TEMPORARY button  
continuously more than three  
seconds.  
Stand-by  
The system starts to operate.  
about three seconds after  
The unit beeps three times.  
The orange light goes on.  
The green light goes on.  
0
3S  
The system is operating.  
TEMPORARY  
If the system is not required to run at this time, push the TEMPORARY  
button once more or use the remote controller and the unit will stop.  
When the system is operating  
Operation  
Motion  
Push the TEMPORARY button  
continuously more than three  
seconds.  
Operating  
The orange light goes on.  
The orange light goes off.  
The system stops to operate.  
about three seconds after  
The unit beeps three times.  
0
3S  
The system stops.  
TEMPORARY  
If the system is not required to stop at this time, use the remote control  
ler and to restart.  
During subsequent operation, the green light goes on.  
(2) If OFF-TIMER operation is reserved without  
setting of Auto Restart operation, the reservation  
is cancelled with power failure.  
8-4-3. In Case of Power Failure during the  
Timer Operation  
(1) If ON-TIMER operation is reserved with setting  
of Auto Restart operation, it is cancelled with  
power failure. (The OPERATION lamp on the  
main unit goes on and off to inform of power  
failure.) In that case, try to reserve ON-TIMER  
operation once again.  
(The OPERATION lamp on the main unit goes  
on and off to inform of power failure.) In that  
case, try to reserve OFF-TIMER operation.  
When Auto Restart operation is set, OFF-TIMER  
reservation is also cancelled with power failure.  
34 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8-5. Remote Controller  
8-5-1. Parts Name of Remote Controller  
Transmitter  
TEMP.  
MODE  
FAN  
AUTO  
LOW  
MED.  
HIGH  
AUTO  
COOL  
DRY  
˚C  
HEAT  
Hr.ON OFF TIMER  
TEMP. (Temperature) buttons  
Push this button to set a desired  
temperature.  
START/STOP button  
Push this button to start/stop the air  
conditioner.  
TEMP.  
FAN (Fan speed) button  
START/STOP  
Push this button to change air flow.  
AUTO (Auto louver) button  
Push this button to swing the vertical air  
flow louvers automatically.  
SET button  
AUTO  
MODE  
SET  
CHK  
FAN  
Push this button to change wind direction.  
MODE (Mode select) button  
Push this button to select an operation  
mode.  
ECONO.  
ECONO. (Economy) button  
Push this button to operate economically.  
TIMER  
ON (On timer) button  
CHK (Check) button  
ON  
OFF  
RSV  
CNL  
Push this button to start the unit at the  
time set by the timer.  
Service man pushes this button to check  
the location of a problem.  
OFF (Off timer) button  
CNL (Cancel) button  
Push this button to stop the unit at the  
time set by the timer.  
Push this button to cancel reservation of  
timer operation.  
RSV (Reserve) button  
Push this button to reserve timer  
operation.  
8-5-2. Name of Indications on Remote Controller  
All indication that appear on the remote controller are shown for explanation.  
Transmission indicator  
This mark is indicated when a button is pushed.  
Set temperature is indicated  
(17˚C to 30˚C).  
Selected operation mode with  
the MODE button is indicated.  
Selected degree of air flow  
(HIGH, MED., LOW or AUTO) is indicated.  
MODE  
AUTO  
COOL  
DRY  
TEMP.  
FAN  
AUTO  
LOW  
MED.  
HIGH  
˚C  
Hr.ON OFF TIMER  
HEAT  
This mark is indicated when  
the ECONO. button is pushed.  
Set time for timer  
operation is indicated.  
– 35 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power supply cord of parts of appliance for outdoor use shall be more  
than polychloroprene sheathed flexible cord (design H07 RN-F), or  
cord designation 245 IEC 66. (2,0mm² or more)  
9. INSTALLATION PROCEDURE  
For general public use  
9-1. Safety Cautions  
Remark per EMC Directive 89/336/EEC  
CAUTION  
New Refrigerant Air Conditioner Installation  
For to prevent flicker impressions during the start of the compressor (technical process) following installation  
conditions do apply.  
This air conditioner adopts the new HFC refrigerant (R410A) which does not destroy ozone layer.  
1. The power connection for the air conditioner has to be done at the main power distribution.  
This distribution has to be of an impedance.  
Normally the required impedance is reached at a 32A fusing point. Air conditioner fuse has to be 16A max.!  
2. No other equipment has to be connected to this power line.  
R410A refrigerant is apt to be affected by impurity such as water, oxidizing membrane, and oils because pressure of  
R410A refrigerant is approx. 1,6 times of refrigerant R22. Accompanied with adoption of the new refrigerant,  
refrigerating machine oil has been also changed. Therefore, during installation work, be sure that water, dust, former  
refrigerant, or refrigerating machine oil does not enter into the refrigerating cycle of new-refrigerant air conditioner.  
To prevent mixing of refrigerant or refrigerating machine oil, the sizes of connecting sections of charging port of the main  
unit or installation tools are different from those for the conventional refrigerant. Accordingly, the exclusive tools are  
required for the new refrigerant (R410A) as shown below.  
For connecting pipes, use new and clean piping materials with high pressure-tight force, which were made for R410A  
only, so that water or dust does not enter. Moreover, do not use the existing piping because there are problems about  
pressure-tight force and inner impurity in the existing piping.  
3. For detailed installation acceptance please refer to your contact with the power supplier, it restriction do apply  
for products like washing machines, air conditioners or electrical ovens.  
4. For power details of the air conditioner refer to the rating plate of the product.  
9-1-1. Installation Diagram of Indoor and Outdoor Units  
CAUTION  
To Disconnect the Appliance from the Mains Supply.  
For the rear left and left piping  
This appliance must be connected to the mains by means of a circuit breaker or a switch with a contact separation of at  
least 3 mm.  
Clip anchor  
Wall  
Hook  
If this is not possible, a power supply plug with earth must be used. This plug must be easily accessible after  
installation. The plug must be disconnected from the power supply socket in order to disconnect the appliance  
completely from the mains.  
Hook  
Front cabinet  
1
Installation  
plate  
Insert the cushion between  
the indoor unit and wall,  
and lift indoor unit to make  
work easier.  
Front panel  
DANGER  
Hook  
FOR USE BY QUALIFIED PERSONS ONLY.  
TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE ALL POWER  
SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.  
Do not allow the drain hose to  
get slack.  
5
Mounting screw  
CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED BY WRONG  
WAY, ELECTRIC PARTS MAY BE DAMAGED.  
Cut the piping hole  
sloped slightly  
CHECK THE EARTH WIRE IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.  
DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.  
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.  
Shield pipe  
TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT WELL AWAY  
(MORE THAN 2M.) FROM HEAT SOURCES SUCH AS RADIATORS, HEAT REGISTORS, FURNACE, STOVES, ETC.  
WHEN MOVING THE AIR-CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY CAREFUL  
NOT TO GET THE SPECIFIED REFRIGERANT (R-22) WITH ANY OTHER GASEOUS BODY INTO THE REFRIG-  
ERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT, THE GAS PRESSURE IN THE  
REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE  
AND INJURIES ON PERSONS.  
IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE INSTALLATION WORK,  
IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS IS HEATED BY FIRE OR  
SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.  
Pan head  
Make sure to run the drain  
hose sloped downward.  
wood screw  
8
7
Deodorizing  
filter  
The auxiliary piping can be  
connected the left, rear left,  
rear, right or bottom.  
6
Purifying  
filter  
4
Remote  
controller  
holder  
2
Wireless  
remote controller  
Right  
WARNING  
Rear  
Never modify this unit by removing any of the safety guards or by by-passing any of the safety interlock switches.  
Rear left  
Do not install in a place which cannot bear the weight of the unit. Personal injury and property damage can result if  
the unit falls.  
Before doing the electrical work, attach an approved plug to the power supply cord. And make sure the equipment to  
be earthed.  
Appliance shall be installed in accordance with national wiring regulations.  
If you detect any damage, do not install the unit. Contact your Toshiba dealer immediately.  
Left  
Bottom  
Before install the wireless  
remote controller  
Insulation of refrigerant pipes  
insulates the pipes separately,  
not together.  
With the remote controller  
cover open, load the batteries  
supplied correctly, observing  
their polarity.  
ore  
or m  
m
200m  
2
Wireless remote controller  
CAUTION  
Exposure of unit to water or other moisture before installation will result in an electrical short.  
Do not store in a wet basement or expose to rain or water.  
3
Batteries  
After unpacking the unit, examine it carefully for possible damage.  
Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify the noise  
level of the unit or where noise and discharged air might disturb user’s neighbors.  
6 mm thick heat resisting  
polyethylene foam  
Cover  
To avoid personal injury, be careful when handling parts with sharp edges.  
Please read the installation manual carefully before installing the unit. It contains further important instructions for  
proper installation.  
As shown in the figure, hang power cord  
and connecting cable downward, and  
take out it along piping connection port.  
Fig. 9-1-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9-1-2. Optional Installation Parts  
9-2. Indoor Unit  
9-2-1. Installation Place  
A place which provides the spaces around the  
indoor unit as shown in the above diagram.  
A place where there is no obstacle near the air  
inlet and outlet.  
A place which allows an easy installation of the  
piping to the outdoor unit.  
Mounting the Installation Plate  
Fixing bolt arrangement of outdoor unit  
For installation of the indoor unit, use the  
paper pattern on the back.  
Part  
code  
Secure the outdoor unit with the fixing bolts and nuts if the  
Parts name  
Q’ty  
unit is likely to be exposed  
to a strong wind.  
Use ø8 mm or ø10 mm  
anchor bolts and nuts.  
Anchor bolt hole  
600  
40mm  
66mm  
Suction side  
Refrigerant piping  
Liquid side : Ø6,35  
Gas side : Ø9,52  
Each  
one  
115  
A
120mm  
65,5mm  
If it is necessary to drain  
the defrost water attach  
65,5mm  
Pipe insulating material  
(Polyethylene foam, 6mm thick)  
B
C
1
Pipe  
hole  
drain nipple to the bottom  
A place which allows the front panel to be  
opened.  
Drain hole  
Diffuser  
plate of the outdoor unit  
before installing it.  
Pipe hole  
1
Each  
one  
Putty, PVC tapes  
Fig. 9-1-2  
Installation  
plate  
Thread  
Weight  
5
Mounting  
screw  
Indoor unit  
CAUTION  
Direct sunlight to the indoor unit wireless  
receiver should be avoided.  
Fig. 9-2-3  
9-1-3. Accessory and Installation Parts  
When the installation plate is directly  
mounted on the wall  
The microprocessor in the indoor unit should not  
be too close to r-f noise sources.  
Part  
No.  
Part  
No.  
Part name (Q'ty)  
Part name (Q'ty)  
Name  
(For details, see the owner's manual.)  
1. Securely fit the installation plate onto the  
wall by screwing it in the upper and lower  
parts to hook up the indoor unit.  
2. To mount the installation plate on a  
concrete wall with anchor bolts, utilize the  
anchor bolt holes as illustrated in the  
above figure.  
1
2
3
4
Owners manual  
5
6
7
8
Others  
Mounting screw Ø4 x 25 x 6  
Installation plate x 1  
Remote controller  
Installation manual  
A place where there are no obstacles such as a  
curtain that may block the signal from the indoor  
unit.  
Do not install the remote controller in a place  
exposed to direct sunlight or close to a heating  
source, such as a stove.  
Keep the remote controller at least 1 m apart from  
the nearest TV set or stereo equipment.  
(This is necessary to prevent image disturbances  
or noise interference.)  
Purifying filter x 1  
Wireless remote controller x 1  
This model is not equipped with  
an extention drain hose.  
Deodorizing filter x 1  
Battery x 2  
Option :  
3. Install the installation plate horizontally in  
the wall.  
For the extention drain hose, use  
an optionally available RB-821SW  
or commercially available one.  
Pan head wood screw Ø3,1x 16 x 2  
Remote controller holder x 1  
CAUTION  
9-1-4. Installation/Servicing Tools Changes in the product and components  
In the case of an air conditioner using R410A, in order to prevent any other refrigerant from being charged  
accidentally, to service port diameter of the outdoor unit control valve (3 way valve) has been changed.  
(1/2 UNF 20 threads per inch)  
In order to increase the pressure resisting strength of the refrigerant piping flare processing diameter and  
size of opposite side of flare nuts has been changed.  
(for copper pipes with nominal dimensions 1/2 and 5/8)  
When installing the installation plate with  
mounting screw, do not use the anchor  
bolt hole. Otherwise the unit may fall down  
and result in personal injury and property  
damage.  
The location of the remote controller should be  
determined as shown below.  
(Side view)  
(Top view)  
Indoor unit  
˚
5
4
Anchor bolt  
New tools for R410A  
Reception  
range  
Remote  
controller  
Remote  
controller  
Reception  
range  
Projection  
New tools for R410A  
Applicable to R22 model  
Changes  
: Axial distance  
*
15mm or less  
As pressure is high, it is impossible to measure by means of  
conventional gauge. In order to prevent any other refrigerant from  
being charged, each port diameter has been changed.  
Fig. 9-2-1  
Gauge manifold  
×
Fig. 9-2-4  
5 mm dia. hole  
9-2-2. Cutting a Hole and Mounting  
Installation Plate  
In order to increase pressure resisting strength, hose materials and  
port size have been changed (to 1/2 UNF 20 threads per inch).  
When purchasing a charge hose, be sure to confirm the port size.  
Charge hose  
×
5
Mounting screw  
Ø4 x 25  
Cutting a Hole  
As pressure is high and gasification speed is fast, it is difficult to read  
the indicated value by means of charging cylinder, as air bubbles  
occur.  
Electronic balance  
for refrigerant charging  
¡
When install the  
refrigerant pipes  
from the rear.  
Clip anchor  
(local parts)  
Fig. 9-2-5  
Torque wrench  
The size of opposite sides of flare nuts have been increased. Incidentally,  
a common wrench is used for nominal diameters 1/4 and 3/8.  
The center of the piping slot  
is above the arrow.  
The center of the pipe  
hole is above the arrow.  
(nominal diam. 1/2, 5/8)  
×
CAUTION  
By increasing the clamp bars receiving hole, strength of spring in the  
tool has been improved.  
Flare tool (clutch type)  
Pipe hole  
¡
Failure to firmly install the unit may result  
in personal injury and property damage if  
the unit falls.  
80mm  
Gauge for projection adjustment ——  
Used when flare is made by using conventional flare tool.  
Connected to conventional vacuum pump. It is necessary to use an  
adapter to prevent vacuum pump oil from flowing back to the charge  
hose. The charge hose connecting part has two ports-one for  
conventional refrigerant (7/16 UNF 20 threads per inch) and one for  
R410A. If the vacuum pump oil (mineral) mixes with R410A a sludge  
may occur and damage the equipment.  
Fig. 9-2-2  
In case of block, brick, concrete or similar  
type walls, make 5 mm dia. holes in the  
wall.  
Vacuum pump adapter  
¡
1. After determining the pipe hole position on the  
mounting plate (80 mm ), drill the pipe hole  
(ø65 mm) at a slight downward slant to the  
outdoor side.  
Insert clip anchors for appropriate  
Gas leakage detector  
Exclusive for HFC refrigerant.  
Exclusive for HFC refrigerant.  
mounting screws.  
×
NOTE  
NOTE  
Incidentally, the refrigerant cylindercomes with the refrigerant designation (R410A) and protector coating  
in the U. Ss ARI specified rose color (ARI color code: PMS 507).  
Also, the charge port and packing for refrigerant cylinderrequire 1/2 UNF 20 threads per inch correspond-  
ing to the charge hoses port size.  
When drilling the wall that contains a metal lath,  
wire lath or metal plate, be sure to use a pipe  
hole brim ring sold separately.  
Install the installation plate using 4 to 6  
pieces of mounting screw securing four  
corners with screws.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9-2-3. Electrical Work  
1. The supply voltage must be the same as the  
rated voltage of the air conditioner.  
2. Prepare the power source for exclusive use with  
the air conditioner.  
9-2-5. Piping and Drain Hose Installation  
In case of rightward piping  
9-2-6. Indoor Unit Fixing  
1. Pass the pipe through the hole in the wall, and  
hook the indoor unit on the installation plate at  
the upper hooks.  
2. Swing the indoor unit to right and left to confirm  
that it is firmly hooked up on the installation plate.  
3. While pressing the indoor unit onto the wall,  
hook it at the lower part on the installation plate.  
Pull the indoor unit toward you to confirm that it  
is firmly hooked up on the installation plate.  
How to connect the connecting cable  
Wiring of the connecting cable can be carried out  
without removing of the front cabinet.  
Slit  
• After scribing slits of the  
(front cabinet)  
1. Remove the front cabinet.  
front cabinet and the rear  
panel by a knife or a  
Fully open the front cabinet. Disengage the  
support arm located in the upper center while  
pushing its handle leftwards, and then remove  
the panel toward you.  
marking-off pin, cut them by  
NOTE  
a pair of nippers or the like.  
Slit (rear panel)  
• Wire type : More than H07RN-F or 245IEC66  
(2,0mm² or more)  
Fig. 9-2-12  
2. Remove the terminal cover and cord clamp.  
3. Insert the connecting cable (according to local  
cords) into pipe hole on the wall.  
4. Take out the connecting cable through the cable  
slot on the rear panel so that it is exploded by  
about 15 cm long in the front side.  
5. Insert the connecting cable fully into the  
terminal block and secure it by screw tightly.  
6. Tightening torque : 1,2 Nm (0,12 kgfcm)  
7. Secure the connecting cable with the cord clamp.  
8. Fix the wiring cover, rear plate bushing and  
front cabinet on the indoor unit.  
In case of downward piping  
CAUTION  
• Use power specified above table.  
• This appliance can be connected to the mains  
in either of the following two ways.  
(1) Connection to fixed wiring :  
Hook here  
1
• After scribing the slit of the front  
1
cabinet and slit in the lower part  
Installation  
plate  
Slit  
(front cabinet)  
of the rear panel by a knife or a  
marking-off pin, cut them by a  
2
Fig. 9-2-16  
pair of nippers or the like.  
Press (unhook)  
Hook  
Slit  
(rear panel)  
Fig. 9-2-13  
A switch or circuit breaker which  
disconnects all poles and has a contact  
separation of at least 3 mm must be  
incorporate in the fixed wiring.  
An approved circuit breaker or switches  
must be used.  
• For detaching the  
indoor unit from the  
installation plate pull  
the indoor unit toward  
you while pushing its  
bottom up at the  
Left-hand connection with piping  
Bend the connecting pipe so that it is laid within  
43 mm above the wall surface. If the connecting  
pipe is laid exceeding 43 mm above the wall  
surface, the indoor unit may unstably be set on the  
wall. When bending the connecting pipe, make sure  
to use spring bender so as not to crush the pipe.  
Push  
Push  
CAUTION  
specified parts.  
(2) Connection with power supply plug :  
Be sure to refer to the wiring system diagram  
labeled inside the front panel.  
Check local electrical cords and also any  
specific wiring instructions or limitation.  
Fig. 9-2-17  
Attach power supply plug with power cord  
and plug it into wall outlet. An approved  
power supply cord and plug must be used.  
9-2-7. Drainage  
1. Run the drain hose sloping downwards.  
Bend the connection pipe within a radius of 30 mm.  
To connect pipe after installation of unit (figure)  
(To the forefront of flare)  
NOTE  
196mm  
Terminal block  
Cord  
NOTE  
Liquid side  
96mm  
Hole should be made at a slight downward slant  
on the outdoor side.  
Gas side  
• Perform wiring works so as to allow a generous  
wiring capacity.  
Terminal  
clamp  
Connecting  
cable  
Earth line  
cover  
Screw  
Outward form  
of indoor unit  
Do not rise the drain hose.  
Do not form the drain hose  
into the waved shape.  
Screw  
R 30mm (Use polisin (polyethylene core)  
or the like for bending pipe.)  
Fig. 9-2-8  
Connecting  
cable  
9-2-4. Wiring Connection  
How to remove the front cabinet  
50 mm  
Screw  
or more  
80˚  
Use the handle of screwdriver,etc.  
Stripping length of connecting cable  
Fig. 9-2-14  
NOTE  
If the pipe is bent incorrectly, the indoor unit may  
unstably be set on the wall.  
1
2
3
Do not put the  
Do not put the drain  
hose end in the  
drainage ditch.  
10mm  
1
2
3
drain hose end  
(4)  
10mm  
into water.  
(4)  
50mm  
Fig. 9-2-18  
40mm  
After passing the connecting pipe through the pipe  
hole, connect the connecting pipe to the auxiliary  
pipes and wrap the facing tape around them.  
2. Put water in the drain pan and make sure that  
the water is drained out of doors.  
3. When connecting extension drain hose, insulate  
the connecting part of extension drain hose with  
(1) (2)  
(3)  
(1) (2)  
Earth  
line  
Vertical air flow louver  
NOTE  
NOTE  
Connect the earth line to the  
metallic part ( mark) located  
at the side of 3P terminal.  
Use stranded wire only.  
WIRE TYPE : more than  
H05 RN-F  
CAUTION  
shield pipe.  
Fig. 9-2-6  
Shield pipe  
• Bind the auxiliary pipes (two) and connecting  
Fig. 9-2-9  
cable with facing tape  
How to open the screw cap  
Indoor unit  
tightly. In case of  
Connecting  
How to install the front cabinet on the indoor unit  
• Install the front cabinet through the opposite  
order of “How to remove the front cabinet”.  
When the panel is removed and mounted again,  
take the following actions:  
After fastening the two screws, one each at the left  
and right of the air outlet be sure to push the upper  
center , right end , left end ƒ and the lower  
center of the air outlet, and confirm that no gap  
is left between the front cabinet and the rear plate.  
Auxiliary  
• Place your finger on the lower part and push  
to open the screw cap.  
cable  
leftward piping and  
Drain hose Inside the room  
Extension drain hose  
pipes  
rear-leftward piping,  
Fig. 9-2-19  
bind the auxiliary  
Installation  
plate  
pipes (two) only with  
facing tape.  
CAUTION  
Fig. 9-2-15  
• Carefully arrange pipes so that any pipe does  
not stick out of the rear plate of the indoor unit.  
Arrange the drain pipe for proper drainage from  
the unit.  
Improper drainage can result in dew-dropping.  
• Carefully connect the auxiliary pipes and  
connecting pipes to each other and cut off the  
insulating tape wound on the connecting pipe  
to avoid double-taping at the joint, moreover,  
seal the joint with the vinyl tape, etc.  
• Since dewing results in a machine trouble,  
make sure to insulate both the connecting pipes.  
(Use polyethylene foam as insulating material.)  
Fig. 9-2-7  
This air conditioner has the structure designed to  
drain water collected from dew,  
1 Open the screw caps and remove the two  
screws securing the front cabinet.  
2 Close the screw caps as behind.  
3 Open the vertical air flow louver horizontally by  
hand.  
4 Slightly open the lower part of the front cabinet  
then pull the upper part of the front cabinet  
toward you to remove it from the rear plate.  
• If cooling (dry) operation is made without pushing  
the air outlet, dew can be  
Wall  
which forms on the back of the  
Push  
3
Push  
1
Push  
2
deposited on the front  
cabinet surface. In addition  
a gap between the front  
cabinet and the rear plate  
will become wilder,  
indoor unit, to the drain pan.  
Drain  
guide  
Therefore, do not store the  
power cord and other parts  
at a height above the drain  
guide.  
4
Space for  
pipes  
• When bending a pipe, carefully do it not to  
crush it.  
Push  
spoiling the apperance.  
Fig. 9-2-20  
Fig. 9-2-10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9-3-5. Gas Leak Test  
9-3. Outdoor Unit  
9-3-1. Installation Place  
A place which provides the spaces around the  
outdoor unit as shown in the left diagram.  
Tightening Connection  
CAUTION  
Align the centers of the connecting pipes and tighten the  
flare nut as far as possible with your fingers Then  
tighten the nut with a spanner and torque wrench as  
shown in the figure.  
KEEP IMPORTANT 4 POINTS FOR PIPING WORK  
1. Take away dust and moisture  
(Inside of the connecting pipes.)  
A place which can bear the weight of the  
outdoor unit and does not allow an increase in  
noise level and vibration.  
A place where the operation noise and  
discharged air do not disturb your neighbors.  
A place which is not exposed to a strong wind.  
A place free of a leakage of combustible gases.  
A place which does not block a passage.  
When the outdoor unit is to be installed in an  
elevated position, be sure to secure its feet.  
2. Tight connection (between pipes and unit)  
3. Evacuate the air in the connecting pipes using  
VACUUM PUMP.  
CAUTION  
Flare nut connections  
(Indoor unit)  
Do not apply excess torque. Otherwise, the nut  
may crack depending on the conditions.  
Flare nut connections  
(Outdoor unit)  
Valve stem cap connection  
4. Check gas leak (connected points)  
(Unit : N·m)  
PackedValve Handling Precautions  
Open the valve stem all the way out; but do not try  
to open it beyond the stopper.  
Service port cap connection  
Outer dia. of copper pipe  
ø6,35 mm  
Tightening torque  
14 to 18 (1,4 to 1,8 kgfm)  
33 to 42 (3,3 to 4,2 kgfm)  
50 to 62 (5,0 to 6,2 kgfm)  
Fig. 9-3-9  
ø9,52 mm  
ø12,7 mm  
Securely tighten the valve stem cap with torque in  
Check the flare nut connections, valve  
stem cap connections and service port cap  
connections for gas leak with a leak  
detector or soap water.  
the following table :  
• Tightening torque of flare pipe connections  
Hexagonal  
wrench is  
required.  
An allowable length of the connecting pipe is up 15m.  
Gas side  
50 to 62 Nm  
Pressure of R410A becomes higher than that of R22.  
(Approx. 1,6 times) Therefore, using a torque wrench,  
tighten firmly the flare pipe connecting sections which  
connect the indoor and outdoor units  
up to the specified tightening torque.  
Incorrect connections may cause not  
only a gas leakage, but also a trouble  
of the refrigeration cycle.  
(ø12,7 mm) (5,0 to 6,2 kgfm)  
Gas side 33 to 42 Nm  
An allowable height level is up to 10 m.  
A place where the drain water does not raise  
any problem.  
(ø9,52 mm) (3,3 to 4,2 kgfm)  
Flare at  
indoor  
Liquid side  
14 to 18 Nm  
9-3-6. Test Operation  
unit side  
(ø6,35 mm) (1,4 to 1,8 kgfm)  
CAUTION  
1. Install the outdoor unit without anything  
blocking the air discharging.  
2. When the outdoor unit is installed in a place  
exposed always to a strong wind like a coast or  
on a high story of a building, secure the normal  
fan operation using a duct or a wind shield.  
3. Specially in windy area, install the unit to  
prevent the admission of wind.  
4. Installation in the following places may result  
trouble. Do not install the unit such places.  
A place full of machine oil.  
A saline-place such as coast.  
A place full of sulfide gas.  
A place where high-frequency waves are  
likely to be generated  
as from audio  
To switch the TEST RUN (COOL) mode,  
press TEMPORARY button for 10 sec.  
(The beeper will make a short beep.)  
14 to 18 Nm  
Service port  
(1,4 to 1,8 kgfm)  
Fig. 9-3-7  
Half union  
Flare nut  
9-3-4. Wiring Connection  
1. Remove the electric parts cover from the outdoor  
unit.  
2. Connect the connecting cable to the terminal as  
identified with their respective matched numbers  
on the terminal block of indoor and outdoor unit.  
3. When connecting the connecting cable to the  
outdoor unit terminal, make a loop as shown  
installation diagram of indoor and outdoor unit, to  
prevent water coming in the outdoor unit.  
Flare at  
outdoor  
unit side  
Externally  
threaded side  
Use a wrench  
to secure.  
Internally  
threaded side  
Use a torque wrench  
to secure.  
Fig. 9-3-4  
Fig. 9-3-5  
9-3-3. Evacuating  
After the piping has been connected to all indoor unit(s),  
you can perform the air purge together at once.  
TEMPORARY  
button  
AIR PURGE  
Evacuate the air in the connecting pipes and in the  
indoor unit using vacuum pump. Do not use the  
refrigerant in the outdoor unit. For details, see the  
manual of vacuum pump.  
TEMPORARY  
4. Insulate the unused cords (conductors) with water  
coming in the outdoor unit. Process them so that  
they do not touch any electrical or metal parts.  
Use a vacuum pump  
Fig. 9-3-10  
equipment,  
Stripping length of connecting cable  
Strong  
welders, and  
Be sure to use a vacuum pump with counter-flow  
prevention function so that inside oil of the pump does not  
flow backward into pipes of the air conditioner when the  
pump stops. (If inside oil of the vacuum pump enters into  
the air conditioner which adopts R410A, a trouble of the  
refrigeration cycle may be caused.)  
1. Connect the charge hose from the manifold valve to the  
service port of the gas side packed valve.  
2. Connect the charge hose to the port of vacuum pump.  
wind  
Terminal block (Connecting cable)  
medical  
equipment.  
10  
10  
L
N
1
2
3
9-3-7. Auto Restart Setting  
Fig. 9-3-1  
10  
10  
This product is designed so that, after a  
power failure, it can restart automatically in  
the same operating mode as before the  
power failure,  
40  
40  
9-3-2. Refrigerant Piping Connection  
30  
30  
Flaring 1. Cut the pipe with a pipe cutter.  
Earth line  
Connecting cable  
Connecting  
cable  
Power Power  
cord cord  
Fig. 9-3-8  
90˚  
Obliquity Roughness  
Warp  
3. Open fully the low pressure side handle of the gauge  
manifold valve.  
Information  
Model  
RAS-10YKV-E/RAS-13YKV-E  
The product was shipped with Auto  
Restart function in the off position.  
Turn it on as required.  
4. Operate the vacuum pump to start for evacuating.  
Perform evacuating for about 15 minutes if the piping  
length is 20 meters. (15 minutes for 20 meters)  
(assuming a pump capacity of 27 liters per minute.)  
Then confirm that the compound pressure gauge  
reading is 101 kPa ( 76 cmHg).  
Power source  
50/60 Hz, 220 240 V Single phase  
Fig. 9-3-2  
Maximum running current  
Plug socket & fuse rating  
Power cord  
8,5A  
2. Insert a flare nut into the pipe, and flare the pipe.  
• Projection margin in flaring : A (Unit : mm)  
Rigid (Clutch type)  
10A  
H07RN-F or 245IEC66 (2,0mm² or more)  
How to Set the Auto Restart  
Compound  
Pressure gauge  
Outer dia. of  
R410A  
Conventional  
pressure  
CAUTION  
Wrong wiring connection may cause some  
electrical parts burn out.  
Be sure to comply with local codes on running  
the wire from outdoor unit to indoor unit (size of  
wire and wiring method etc.)  
5. Close the low pressure side  
valve handle of gauge manifold.  
Press and hold down the TEMPORARY  
button for about 3 seconds. After 3  
seconds, the electronic beeper makes  
three short beeps to tell you the Auto  
Restart has been selected.  
To cancel the Auto Restart, follow the  
steps described in the section Auto Restart  
Function of the Owners Manual.  
copper pipe  
tool used  
tool used  
gauge  
-101kPa  
Manifold valve  
(-76cmHg)  
6,35  
9,52  
12,7  
0 to 0,5  
0 to 0,5  
0 to 0,5  
1,0 to 1,5  
1,0 to 1,5  
1,0 to 1,5  
6. Open fully the valve stem of  
Handle Hi  
(Keep full closed)  
Charge hose  
(For R410A only)  
Handle Lo  
the packed valves (both side  
Charge hose  
(For R410A only)  
of Gas and Liquid).  
Vacuum pump  
adapter for  
7. Remove the charging hose  
from the service port.  
8. Securely tighten the caps  
on the packed valves.  
counter-flow  
prevention  
Imperial (Wing nut type)  
Connecting  
pipe  
A
(For R410A only)  
Outer dia. of  
Every wire must be connected firmly.  
R410A  
copper pipe  
6,35  
Vacuum  
pump  
1,5 to 2,0  
1,5 to 2,0  
2,0 to 2,5  
NOTE : Connecting cable  
Wire type : More than H07RN-F or 245IEC66  
(2,0mm² or more)  
Die  
Pipe  
Packed valve at liquid side  
Packed valve at gas side  
Service port  
(Valve core (Setting pin))  
9,52  
12,7  
Fig. 9-3-3  
Fig. 9-3-6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10. HOW TO DIAGNOSETHE TROUBLE  
The pulse modulating circuits are mounted to both  
NOTE :  
indoor and outdoor units. Therefore, diagnose  
troubles according to the trouble diagnosis proce-  
dure as described below. (Refer to the check points  
in servicing written on the wiring diagrams attached  
to the indoor/outdoor units.)  
A large-capacity electrolytic capacitor is used in the  
outdoor unit controller (inverter).Therefore, if the  
power supply is turned off, charge (charging voltage  
DC280V) remains and discharging takes a lot of  
time. After turning off the power source, if touching  
the charging section before discharging, an electri-  
cal shock may be caused. Discharge the electrolytic  
capacitor completely by using soldering iron, etc.  
Table 10-1  
No.  
1
Troubleshooting Procedure  
First Confirmation  
Page  
40  
< Discharging method >  
2
Primary Judgment  
41  
(1) Remove the inverter cover (plating) by opening  
four mounting claws.  
3
Judgment by Flashing LED of Indoor Unit  
42  
(2) As shown below, connect the discharge resis-  
tance (approx. 10040W) or plug of the solder-  
ing iron to voltage between + – terminals of the  
C14 (“CAUTION HIGH VOLTAGE 320V” is  
indicated.) electrolytic capacitor (500µF/400V)  
on P.C. board, and then perform discharging.  
Self-Diagnosis by Service Check Remote  
Controller  
4
43  
5
6
Judgment of Trouble by Every Symptom  
How to Check Simply the Main Parts  
46  
53  
Inverter cover  
P. C. board  
(Soldered surface)  
Discharging position  
(Discharging period  
10 seconds or more)  
Plug of  
soldering iron  
MCC-808  
Fig. 10-1  
10-1-2. Confirmation of Power Voltage  
10-1. First Confirmation  
Confirm that power voltage is AC 220–230–240  
10%. If power voltage is not in this range, the unit  
may not operate normally.  
10-1-1. Confirmation of Power Supply  
Confirm that the power breaker operates (ON)  
normally.  
– 40 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10-1-3. Operation Which is not a Trouble (Program Operation)  
For controlling the air conditioner, the program operations are built in the microcomputer as described in the  
following table. If a claim is made for running operation, check whether or not it meets to the contents in the  
following table. When it does, we inform you that it is not trouble of equipment, but it is indispensable for control-  
ling and maintaining of air conditioner.  
Table 10-1-1  
No.  
Operation of air conditioner  
Description  
1
When power breaker is turned “ON”, the  
operation lamp (Green) of the indoor unit  
flashes.  
The OPERATION lamp of the indoor unit flashes when  
power source is turned on. If [START/STOP] button is  
operated once, flashing stops. (Flashes also in power  
failure)  
2
Compressor may not operate even if the  
room temperature is within range of  
compressor-ON.  
The compressor does not operate while compressor  
restart delay timer (3-minutes timer) operates.  
The same phenomenon is found after power source has  
been turned on because 3-minutes timer operates.  
3
4
In Dry and ECONO. mode, FAN (air flow)  
display does not change even though FAN  
(air flow select) button is operated.  
The air flow indication is fixed to [AUTO].  
Increasing of compressor motor speed  
stops approx. 30 seconds after operation  
For smooth operation of the compressor, the compressor  
motor speed is restricted to Max. 41 rps for 2 minutes, and  
started, and then compressor motor speed Max.91 rps for 2 minutes to 3 minutes, respectively after  
increases again approx. 30 seconds after. the operation has started.  
5
6
7
The set value of the remote controller  
should be below the room temperature.  
If the set value is above the room temperature, Cooling  
operation is not performed. And check whether battery of  
the remote controller is consumed or not.  
In AUTO mode, the operation mode is  
changed.  
After selecting Cool or Heat mode, select an operation  
mode again if the compressor keeps stop status for 15  
minutes.  
In HEAT mode, the compressor motor  
speed does not increase up to the maxi-  
mum speed or decreases before the  
temperature arrives at the set tempera-  
ture.  
The compressor motor speed may decrease by high-temp.  
release control (Release protective operation by temp.-up  
of the indoor heat exchanger) or current release control.  
10-2. Primary Judgment  
To diagnose the troubles, use the following methods.  
(1) Judgment by flashing LED of indoor unit  
(2) Self-diagnosis by service check remote controller  
(3) Judgment of trouble by every symptom  
Firstly use the method (1) for diagnosis. Then, use the method (2) or (3) to diagnose the details of troubles.  
– 41 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10-3. Judgment by Flashing LED of Indoor Unit  
While the indoor unit monitors the operation status of the air conditioner, if the protective circuit operates, the  
contents of self-diagnosis are displayed with block on the indoor unit indication section.  
Table 10-3-1  
Check  
code  
Item  
A
Block display  
Description for self-diagnosis  
OPERATION  
ECONO.  
TIMER  
OPERATION (Green)  
Power failure (when power is ON)  
Flashing display (1 Hz)  
Indoor  
PRE DEF.  
indication  
lamp flashes.  
OPERATION  
ECONO.  
TIMER  
OPERATION (Green)  
Flashing display (5 Hz)  
Protective circuit operation for  
indoor P.C. board  
B
Which lamp  
does flash?  
PRE DEF.  
OPERATION  
ECONO.  
TIMER  
OPERATION (Green)  
TIMER (Yellow)  
Protective circuit operation for  
connecting cable and serial signal  
system  
C
D
Flashing display (5 Hz)  
PRE DEF.  
OPERATION (Green)  
PRE DEF. (Orange)  
Flashing display (5 Hz)  
OPERATION  
ECONO.  
TIMER  
Protective circuit operation for  
outdoor P.C. board  
PRE DEF.  
OPERATION  
ECONO.  
TIMER  
Protective circuit operation for others  
(including compressor)  
OPERATION (Green)  
TIMER (Yellow)  
PRE DEF. (Orange)  
Flashing display (5 Hz)  
E
PRE DEF.  
NOTES :  
(1) The contents of items B and C and a part of item E are displayed when air conditioner operates.  
(2) When item B and C, and item B and a part of item E occur concurrently, priority is given to the block of item B.  
(3) The check codes can be confirmed on the remote controller for servicing.  
– 42 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10-4. Self-Diagnosis by Remote Controller (Check Code)  
(1) The self-diagnosis by the check code is performed while items B to E blocks are displayed.  
(2) When turning the operation mode on the remote controller to the service mode, and operating the remote  
controller, the controller of the indoor unit can self-diagnose operation of the protection circuit by displayed  
contents (check code) on the remote controller, by whether all the lamps flash (5Hz) and the receiving  
sound (Pi, Pi, Pi ... for 10 seconds) is heard. The timer lamp usually flashes (5Hz) during self-diagnosis.  
10-4-1. Self-Diagnosis  
Push the CHK button by something with thin edge.  
1
Check  
is displayed in the indication  
part of the remote controller.  
CHK  
E
TIMER  
Push  
toward the remote controller one by one.  
2
If it is normal, the receiving sound Piis heard  
every pushing it and check code in the indication  
part of the remote controller changes.  
MODE  
TEMP.  
FAN  
AUTO  
LOW  
MED.  
HIGH  
AUTO  
COOL  
DRY  
˚C  
HEAT  
Hr.ON OFF TIMER  
The timer lamp of the air conditioner flashes.  
(5 times for 1 second)  
TEMP.  
Check all of 35 check codes (  
to  
).  
START/STOP  
Push to return to the objective code if passed.  
AUTO  
MODE  
SET  
CHK  
FAN  
If a trouble occurs, the receiving sound Pi”  
changes to Pi, Pi, Pi (continues for approx.  
10 seconds).  
ECONO.  
TIMER  
Check the check code in the indication part  
of the remote controller.  
ON  
OFF  
RSV  
CNL  
2-digits alphanumeric characters are displayed in the  
indication part of the remote controller.  
All the lamps of the air conditioner flash  
(5 times for 1 second).  
Alphanumeric characters are  
used for the check codes.  
START/STOP  
To release the self-diagnosis function, push  
button.  
Display returns to one before check.  
is 5.  
is A.  
is C.  
is 6.  
is B.  
is D.  
3
Fig. 10-4-1  
10-4-2. Operation Control by Rated Frequency in Service Mode  
In the service mode, pushing “ON” or “OFF” operates the air conditioner by rated frequency of COOL or HEAT  
mode for 30 minutes. (Cooling function operates under condition of room temperature by 24°C or more while  
heating function by 23°C or less, respectively.)  
– 43 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10-4-3. Caution at Servicing  
(1) After servicing, push the START/STOP button to return to the normal mode.  
(2) After servicing by the check code, turn off breaker of the power supply, and turn on breaker of the power  
supply again so that memory in the microcomputer returns the initial status. However, the check codes are  
not deleted even if the power supply is turned off because they are stored in the fixed memory.  
Table 10-4-1  
Block distinction  
Operation of diagnosis function  
Air  
Judgment and action  
Check  
Block  
code  
Check  
code  
Cause of operation  
conditioner  
status  
Remarks  
Indoor P.C.  
board etc.  
Short-circuit or  
disconnection of the room continues.  
temperature sensor  
Operation  
Displayed when  
error is detected.  
1. Check the room temp. sensor.  
2. When the room temp. sensor is  
normal, check P.C. board.  
(TA sensor).  
Being out of place,  
disconnection, short-  
circuit, or migration of  
heat exchanger sensor  
(TC sensor)  
Operation  
continues.  
Displayed when  
error is detected.  
1. Check heat exchanger sensor.  
2. When heat exchanger sensor is  
normal, check P.C. board.  
Lock of indoor fan or  
trouble on the indoor fan  
circuit  
All off  
Displayed when  
error is detected.  
1. Check P.C. board.  
2. When P.C. board is normal, check  
the motor.  
Not  
displayed  
Trouble on other indoor  
P.C. boards  
Operation  
continues.  
Displayed when  
error is detected.  
Replace P.C. board.  
Connecting  
cable and  
serial signal  
Return serial signal is not Operation  
Flashes when  
1. When the outdoor unit never  
operate:  
sent to indoor side from  
operation started.  
continues.  
trouble is detected  
on Return serial  
signal, and normal  
status when signal  
is reset.  
(1) Check connecting cable, and  
correct if defective wiring.  
(1) Defective wiring of  
connecting cable  
(2) Check 25A fuse of inverter P.C.  
board.  
(2) Operation of  
compressor thermo.  
Gas shortage  
Gas leak  
(3) Check 3,15A of inverter P.C.  
board.  
2. To display [Other] block during  
operation, check compressor  
thermo. operation and supply gas  
(check gas leak also).  
3. Unit operates normally during check.  
If Return serial signal does not stop  
between indoor terminal board 2 and  
3, replace inverter P.C. board.  
If signal stops between indoor  
terminal board 2 and 3, replace  
indoor P.C. board.  
Operation command  
signal is not sent to  
outdoor side.  
Operation  
continues  
Flashes when  
If Return serial signal does not stop  
trouble is detected between indoor terminal board 2 and 3,  
on Operation replace inverter P.C. board.  
command signal, If signal stops between indoor terminal  
and normal status board 2 and 3, replace indoor P.C.  
when signal is  
reset.  
board.  
– 44 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Block distinction  
Operation of diagnosis function  
Air  
Judgment and action  
Check  
Block  
code  
Check  
code  
Cause of operation  
conditioner  
status  
Remarks  
Outdoor  
P.C. board  
Inverter over-current  
protective circuit  
operates. (Short time)  
All off  
All off  
Displayed when  
error is detected. operations stop immediately. : Replace  
P.C. board.  
Even if trying operation again, all  
Position-detect circuit  
error or short-circuit  
between windings of  
compressor  
Displayed when  
error is detected.  
1. Even if connecting lead wire of  
compressor is removed, position-  
detect circuit error occurred. :  
Replace P.C. board.  
2. Measure resistance between wires  
of compressor, and perform short-  
circuit. : Replace compressor.  
Current-detect circuit  
error  
All off  
All off  
Displayed when  
error is detected. operations stop immediately. :  
Replace P.C. board.  
Even if trying operation again, all  
Being out of place,  
disconnection or short-  
circuit of outdoor temp.  
sensor  
Displayed when  
error is detected.  
1. Check outdoor temp. sensors  
(TE, TS).  
2. Check P.C. board.  
Disconnection or short-  
circuit of discharge temp.  
sensor  
All off  
Displayed when  
error is detected.  
1. Check discharge temp. sensor (TD).  
2. Check P.C. board  
Outdoor fan drive system All off  
error  
Displayed when  
error is detected. protective operation of outdoor fan  
drive system, fan lock, etc. :  
Position-detect error, over-current  
Replace P.C. board or fan motor.  
Not  
displayed  
Outdoor heat exchanger Operation  
1. Check outdoor heat exchanger temp.  
sensor (TE).  
temp. sensor error  
continues  
——  
2. Check P.C. board.  
Outdoor  
P.C. board  
Compressor drive output All off  
error, Compressor error  
(lock, missing, etc.),  
Break down  
Displayed when  
error is detected. up, position-detect circuit error  
occurred. : Replace compressor.  
When 20 seconds passed after start-  
Others  
(including  
compressor)  
Return serial signal has Operation  
Flashes when  
1. Repeat Start and Stop with interval  
of approx. 10 to 40 minutes. (Code is  
not displayed during operation.)  
been sent when  
continues  
trouble is detected  
on Return serial  
signal, and normal  
status when signal  
is reset.  
operation started, but it  
is not sent from halfway.  
(1) Compressor thermo.  
operation  
Gas shortage  
Gas leak  
(2) Instantaneous power  
failure  
Supply gas. (Check also gas leak).  
2. Unit operates normally during check.  
If Return serial signal does not stop  
between indoor terminal block 2 and  
3, replace inverter P.C. board.  
If signal stops between indoor  
terminal block 2 and 3, replace  
indoor P.C. board.  
Compressor does not  
rotate.  
(Current protective  
circuit does not operate  
when a specified time  
passed after compressor  
had been activated.)  
All off  
Displayed when  
error is detected.  
1. Trouble on compressor  
2. Trouble on wiring of compressor  
(Missed phase)  
Discharge temp.  
exceeded 117°C  
All off  
All off  
Displayed when  
error is detected.  
1. Check dischage temp. sensor (TD).  
2. Degassing  
3. Trouble on P.M.V.  
Break down of  
compressor  
Displayed when  
error is detected.  
1. Check power voltage.  
(220–30–40 V+10%)  
2. Overload operation of refrigeration  
cycle  
Check installation condition  
(Short-circuit of outdoor diffuser).  
Four-way valve inverse  
error  
(TC sensor value  
lowered during heating  
operation.)  
Operation  
continues  
1. Check four-valve operation.  
——  
– 45 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10-5. Judgment ofTrouble by Every Symptom  
10-5-1. Indoor Unit (Including Remote Controller)  
(1) Power is not turned on (Does not operate entirely)  
Operation  
Check Item  
Turn off the power supply  
once, and turn on it again  
after 5 seconds passed.  
Considerable main cause  
Measures  
NO  
Does the operation  
lamp flash?  
Item by symptom  
YES  
Is the power supply  
turned on by pressing  
[START/STOP] button  
on remote controller?  
Does send display  
of remote controller flash  
normally, and is the signal  
sent securely?  
NO  
NO  
Remote controller  
error  
YES  
YES  
(No trouble)  
Refer to the item of  
Remote controller  
check. (p.49)  
Parts (R21, R109, SG01,  
C15, C01, DB01, C02,  
IC01, T01) are defective.  
YES  
YES  
Is fuse of indoor control  
board blown? (F01)  
NO  
Replace temp.  
fuse set.  
Check connecting  
wire.  
Connection of connecting  
wire is defective.  
Is temp. fuse blown?  
NO  
Is voltage indicated  
on rear of indoor control  
board (DC12V or 5V)  
normal?  
YES  
NO  
Microcomputer  
is defective.  
Replace main  
board.  
Is DC310 to 340V  
applied to primary  
side of SW trans.  
(T01) applied?  
NO  
NO  
To item of Pre-check or  
trouble before power board  
Is DC35V,  
DC12V, DC7V  
applied to secondary  
side of SW trans.  
(T01) applied?  
Is DC35V,  
Turn “OFF” breaker  
once, and “ON”  
again after removing  
motor.  
SW trans.,  
IC (IC01) for  
power supply, ]  
or fan motor  
DC12V, DC7V  
applied to secondary  
side of SW trans.  
(T01) applied?  
YES  
YES  
Motor is defective.  
• Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of  
damage of the motor.  
(2) Power is not turned on though Indoor P.C. board is replaced  
<Confirmation procedure>  
Turn on power supply.  
NO  
NO  
Is wired correctly to white and black  
lead wires of terminal block?  
Does operation lamp flash?  
YES  
Correct wiring.  
YES  
To item of “Power supply  
is not turned on”.  
– 46 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(3) Only the indoor fan does not operate  
Operation  
Check Item  
Turn off the  
power supply.  
Considerable main cause  
Measures  
Turn on the  
power supply.  
Item by symptom  
Does the fan  
NO  
Replace the board.  
stop in no operating  
status?  
Control board is defective.  
YES  
Start the operation  
with low fan setting  
in cool operation.  
Is the DC 35V  
measured between  
(red lead wire) and  
(black lead wire)  
of the motor connector  
(CN10) ?  
Turn off the power supply,  
and turn it on after  
removing the motor from  
the board.  
NO  
NO  
1
Does the fan rotate?  
YES  
2
YES  
Turn off the power supply.  
Change the setting of  
cooling to high fan.  
Repair the  
bearing of the  
cross flow fan.  
Does the cross  
flow fan rotate  
normally?  
NO  
YES  
Turn on the power supply.  
Is the voltage of  
DC35V measured  
between 1 and 2 GND of  
the motor connector  
(CN10) ?  
NO  
NO  
Replace  
the board.  
Operation  
stops  
Does the fan speed  
become higher?  
YES  
YES  
Is the rotation signal  
(DC+5V 0V) output between  
4 (blue lead wire) and (black  
lead wire) of the motor connector  
(CN10) when rotating the cross  
flow fan by hand in no operating  
status ? (2 pulses/one turn)  
2
NO  
YES  
Replace the  
control board.  
Replace the  
fan motor.  
Normal  
– 47 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(4) Indoor fan motor starts rotating by turning on power supply alone  
(Operation may be normally performed (selected) by operation on the remote controller.)  
<Cause>  
IC is built in the indoor fan motor, therefore P.C. board is also mounted to inside of the motor.  
If soldering of P.C. board in the motor is defective or IC is defective, the fan motor may rotate by only inputting  
the power (turning on power supply).  
<Confirmation procedure>  
(1) Remove the front panel.(Remove 2 screws and clicks.)  
(2) Remove cover of the fan motor lead wire. (1 click)  
(3) Check the voltage (DC) using CN10 connector while the fan rotates.  
NOTE :  
• Do not disconnect the connector while the fan rotates.  
• Use a thin tester rod.  
Indoor fan starts rotating when power supply breaker is turned "ON".  
P.C. board  
CN10  
(Check output voltage (DC) of the fan motor on P.C. board.)  
5
4 Blue  
Yellow  
Black  
3 Yellow  
2 Black  
1 Red  
Measure the voltage of the motor connector  
CN10 pin 2 (GND : Black) and pin 3 (V line : Yellow)  
under condition that the indoor fan rotates.  
Above DC 0.4V  
Below DC 0.4V  
DC  
P.C. board is defective.  
Motor is defective.  
– 48 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(5) How to examine whether remote controller is good or bad  
Operation  
Check Items  
There is no beep from  
the indoor unit.  
The operation lamp of  
the air conditioner main  
unit does not light.  
Push the START/STOP button.  
Considerable main cause  
Measures  
NO  
Does the transmission  
indicator of remote  
controller light?  
Item by symptom  
YES  
Is there direct  
Take out the batteries and  
insert them again.  
(rear side of remote controller)  
NO  
sunlight on the  
receptor of the  
air conditioner?  
YES  
Is operation  
possible when the  
transmitter is moved  
nearer to the infrared  
signal receiver of the  
air conditioner?  
Is there any  
thyristor  
fluorescent light  
near by?  
NO  
NO  
YES  
YES  
Battery life  
Is Temporary Cool  
Push the START/  
STOP button  
operation possible when  
keeping the temporary  
switch of the air conditioner  
main unit pressed for  
NO  
NO  
Does the transmission  
indicator light?  
10 seconds or more?  
YES  
YES  
NO  
Is there any receiving  
sound and operation?  
YES  
Can any signal tone  
be heard in a transistor  
radio when transmitting  
within 5cm distance  
from the radio?  
NO  
YES  
Keep the air  
conditioner away  
from thyristor  
Remote  
controller  
is failure.  
Replace  
P.C. board.  
Avoid direct  
sunlight.  
Replace the  
battery.  
Normal  
fluorescent light.  
– 49 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10-5-2. Wiring Failure (Interconnecting and Serial Signal Wire)  
(1) Outdoor unit does not operate  
1) Is the voltage between  
and  
of the indoor terminal block varied?  
ƒ
Confirm that transmission from indoor to outdoor is correctly performed based upon the following dia-  
gram.  
NOTE:  
• Measurement should be performed 2 minutes and 30 seconds after starting of the operation.  
• Be sure to prepare a diode for judgment.  
Terminal block at indoor side  
Red  
3
2
1
S5277G or equivalent (G or J type)  
(Diode with rated voltage of 400V  
or more is acceptable.)  
S5277G  
White  
Tester  
Terminal block  
Normal time  
:Voltage swings between DC15 and 60V.  
Abnormal time :Voltage does not vary.  
(2) Outdoor unit stops in a little while after operation started  
<Check procedure> Select phenomena described below.  
(1) The outdoor unit stops 10 to 20 minutes after operation started, and 10 minutes or more are required to  
restart the unit.  
Gas circulation amount is down.  
Measure gas pressure.  
Gas shortage  
Gas leak  
Pipe clogging  
Thermo. operation of compressor  
(2) If the unit stops once, it does not operate until the power will be turned on again.  
To item of Compressor does not operate.  
(3) The outdoor unit stops 10 minutes to 1 hour after operation started, and an alarm is displayed.  
(Discharge temp. error check code 03, 1E Sensor temp. error check code 02, 1C)  
Gas leak  
P.M.V. is defective.  
Refer to the chart in 10-6.  
Miswiring of connecting wires of indoor/outdoor units  
Clogging of pipe and coming-off of TC sensor  
– 50 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10-6. Check Code 1C (Miswiring in indoor/outdoor units) and 1E  
<Check procedure>  
1C  
1E  
Operation  
Check Item  
Gas leakage,  
Discharge temp. error,  
gas leakage  
(Check code 03, 1E)  
disconnection of TS/TC  
sensors (Check code 02, 1C)  
Considerable main cause  
Measures  
Item by symptom  
Valve drive check  
NO  
NO  
Is coil of the pulse modulation valve  
(P.M.V.) correctly set?  
Set it correctly.  
Set it correctly.  
YES  
Is connector of coil connected to inverter?  
YES  
Is positioning sound of valve (sound hitting to stopper) heard from valve  
when the air conditioner starts the operation after turning off power of the  
air conditioner once?  
NOTE :  
After all the operations stopped by the remote controller, the power keeps  
being supplied to outdoor unit for approx. 3 minutes. If operating the air  
conditioner by remote controller again just after all the operations stopped by the  
remote controller, positioning of the valve is not performed when outdoor unit  
is activated because supplying power to the outdoor unit is not interrupted.  
After positioning of the valve, activate the compressor and the outdoor fan.  
It takes approx. 7 seconds for positioning of the valve, and sound ticktack  
(hitting sound to stopper) is heard for approx. 0.5 seconds at least of that  
period. As the sound is low, check sound by using screwdriver, etc.  
NO  
Replace coil valve.  
YES  
Are temp. sensors of indoor/outdoor units correctly set to the holder?  
NOTE :  
The temperature sensors which are used to control electronic control valve  
include indoor heat exchanger sensor (TC), outdoor heat exchanger temp.  
sensor (TE), and outdoor suction temp. sensor (TS).  
NO  
Set it correctly.  
YES  
Gas amount check and valve clogging check  
Remove TC sensor connector from the P.C. board in indoor unit.(Remove connector from the P.C. board.)  
Operate the air conditioner in COOL mode by TEMP button (“Pi” sound is heard if keeping pushed for 10 seconds.).  
The operation enters temporary operation mode which fixes opening degree of P.M.V. and No. of revolution of  
compressor. Check condensation at outlet of P.M.V., and then check operating pressure from the service port.  
Existence of condensation at outlet of P.M.V.  
YES  
Replace valve.  
Add gas.  
If there is condensation at outlet (1/4 inch=Ø6,35mm valve side),  
the valve is clogged.  
Check the operating pressure from service port, and add gas if pressure is low.  
– 51 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10-7. How to DiagnoseTrouble in Outdoor Unit  
10-7-1. Summarized Inner Diagnosis of Inverter Assembly  
Diagnosis/Process flowchart  
Item  
Contents  
Summary  
Preparation Turn “OFF” the power breaker,  
and remove 3P connector  
which connects inverter and  
compressor.  
Remove  
connector of  
compressor.  
If fuse was blown, be sure to  
Check  
• Check whether 25A fuse on check the electrolytic  
the control board assembly capacitor and diode block.  
NG  
Check 25A fuse  
(Part No.F01).  
is blown or not. (F01)  
(DB01)  
OK  
Replace fuse.  
• Connect discharge  
resistance (approx.  
10040W) or soldering  
iron (plug) between +, –  
terminals of the electro-  
lytic capacitor (500µF) of  
C14 (with printed CAU-  
TION HIGH VOLTAGE) on  
P.C. board.  
Check  
electrolytic  
capacitor, diode  
block (DB01),  
etc.  
Check  
Check whether 15A fuse on  
the control board assembly  
is blown or not. (F03)  
• 15A fuse (F03) on the  
control board is provided for  
power factor improvement  
control circuit. The operation  
continues even if fuse is  
blown.  
Check  
15A fuse  
NG  
NG  
Plug of  
Discharging position  
soldering  
(Part No.F03).  
(Discharging period  
iron  
10 seconds or more)  
OK  
Replace control  
board assembly.  
Check  
terminal voltage  
of electrolytic  
capacitor.  
OK  
Check  
electrolytic  
capacitor, diode  
(DB01),  
If 15A fuse is blown,  
discharge both edges of  
the electrolytic capacitor  
with soldering iron.  
etc.  
Operation  
Turn on power breaker, and  
operate the air conditioner in  
COOL mode by short-circuit of OK if 500µF →  
NO  
Does outdoor  
fan rotate?  
the timer.  
DC280 to 320V  
Measurement Measure terminal voltage of  
the electrolytic capacity.  
YES  
YES  
Remove CN300 while  
Does LED on control  
board flash or go on?  
500µF:400WV x 3  
pushing the part indicated  
by an arrow because CN01  
is a connector with lock.  
NO  
After operation, turn off the  
Remove connector  
CN300 of outdoor fan  
motor, and using a  
tester, check resistance  
value between every  
phases at motor side.  
Check  
Stop  
power breaker after 2 minutes  
20 seconds passed, and  
discharge the electrolytic  
capacity by soldering iron.  
Check voltage between motor  
phases.  
NG  
OK  
Check  
Measurement • Is not winding between  
-

Replace  
outdoor  
fan motor.  
,
-
, or  
-
opened  
Resistance between  
phases should be approx. 55  
to 77Ω  
‚ ‚ ƒ  ƒ  
or short-circuited?  
• Is not frame grounded with  
, or  
,
 ‚  
?
ƒ
A
B
C
Should be 10Mor more.  
– 52 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Diagnosis/Process flowchart  
Item  
Contents  
Summary  
Check  
Check winding resistance  
between phases of compres-  
sor, and resistance between  
outdoor frames by using a  
tester.  
A
B
C
• Is not grounded.  
• Is not short-circuited  
between windings.  
OK if 10Mor more  
Check  
NG  
winding of  
compressor.  
OK if 0,51Ω → 0,57Ω  
(Check by a digital tester.)  
OK  
• Winding is not opened.  
Check  
fan motor  
position  
detect  
Replace  
com-  
Operation  
Remove connector CN300 of  
the outdoor fan motor, turn  
on the power breaker, and  
perform the operation.  
(Stops though activation is  
prompted.)  
NG  
pressor.  
signal.  
OK  
Replace  
outdoor  
fan  
Check operation within 2  
minutes 20 seconds after  
activation stopped.  
motor.  
Check  
<Output check of fan motor a) One or two of three  
position detect signal>  
While connecting connector  
5P (CN301) for position  
detection, using a tester,  
voltages should be 5V,  
and others should be 0V.  
(When all are 0V or 5V, it  
is not accepted.)  
Replace control  
board assembly.  
measure voltage between  
b) When rotating the fan  
slowly with hands, the  
voltage between pins  
should move from 0V to  
5V.  

Check  
NG  
-
. Between  
-
ꢀ „  
: 5V  
compressor  
winding  
resistance.  
OK  
(Check it with an analog  
tester.)  
Replace  
Replace  
compressor.  
control board.  
(2) Inspection procedures  
10-8. How to Check Simply the Main  
Parts  
1) When a P.C. board is judged to be defective,  
check for disconnection, burning, or discol-  
oration of the copper foil pattern or this P.C.  
board.  
10-8-1. How to Check the P.C. Board  
(Indoor Unit)  
2) The P.C. board consists of the following 2  
parts  
(1) Operating precautions  
1) When removing the front panel or the P.C.  
board, be sure to shut off the power supply  
breaker.  
a. Main P.C. board part:  
DC power supply circuit (5V, 12V, 35V),  
Indoor fan motor control circuit, CPU and  
peripheral circuits, buzzer, and Driving  
circuit of top/bottom louvers  
2) When removing the P.C. board, hold the edge  
of the P.C. board and do not apply force to the  
parts.  
b. Indication unit of infrared ray receiving  
Infrared ray receiving circuit, LED:  
3) When connecting or disconnecting the  
connectors on the P.C. board, hold the whole  
housing. Do not pull at the lead wire.  
To check defect of the P.C. board, follow  
the procedure described below.  
– 53 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(3) Check procedures  
Table 10-8-1  
No.  
Procedure  
Check point (Symptom)  
Causes  
1
Shut off the power supply and  
remove the P.C. board assembly  
from the electronic parts base.  
1. Is the fuse blown?  
1. * Application of shock voltage.  
* Overload by short-circuit of the  
parts.  
Remove the connecting cable from  
the terminal block.  
2
Remove the connector for the  
motor, and turn the power on.  
Voltage check  
1. * AC power cord is defective.  
* Poor contact of the terminal plate.  
* Miss wiring of the power relay.  
2. Fuse is defective.  
1. Between TP1 and TP2  
(220–230–240V AC)  
If the OPERATION lamp flashes  
(0,5 sec. :ON, 0,5 sec. :OFF) when  
the power turning on, the checking  
points described as 1-5 of right  
column are not necessary to  
perform.  
2. Between TP2 and pin 1 of CN04  
(220–230–240V AC)  
3. Operation of the thermal fuse.  
4. * Capacitor (C01, C15) is defective.  
* Line filter (L01) is defective.  
* Resistor (R01) is defective.  
* Diode (DB01) is defective.  
3. Between TP2 and pin 3 of CN04  
(220–230–240V AC)  
4. Between + and – of C02  
(310 ~ 340V DC)  
5. Between 35V and GND  
6. Between 12V and GND  
7. Between 5 V and GND  
5. IC01, IC02, T01 are defective.  
6. IC01, IC02, T01, F03 are defective.  
7. IC01, IC02, T01, F02, Q29, IC03  
are defective.  
3
Make the operation status by  
pushing once the START/STOP  
button, except the status of [ON  
TIMER].  
Voltage check  
1. Breaking wire of the relay coil,  
defective relay driver. (IC31)  
1. Voltage of relay coil. (DC 12V)  
Between pin 10 of IC31 and GND  
Between pin 11 of IC31 and GND  
2. Poor contact of relay.  
2. Between No. 1 and 2 of connecting  
cable terminal block.  
(220–230–240V AC)  
4
5
Start the operation with the system  
which the time of the restart delay  
timer is shortened.  
1. All indicators light for 3 sec.  
Defective indicator, or poor  
housing assembly. (CN13)  
2. Indicators do not indicate normally  
after approximate 3 sec.  
Make the operation status by pressing  
once the START/STOP button.  
1. Compressor does not operate.  
2. OPERATION lamp flashes.  
1. The temperature of the indoor heat  
exchanger is abnormally low.  
1. The time of the restart delay timer  
is shortened.  
2. Poor contact of the heat exchanger  
sensor. (The connector is  
disconnected.) (CN01)  
2. Cool operation  
3. Heat exchanger sensor, main P.C.  
board are defective.  
3. Air volume [AUTO]  
4. Make the setting temperature lower  
enough than room temperature.  
4. Main P.C. board is defective.  
5. Continuous operation.  
Turn the power on after connecting  
the motor connector.  
6
1. The voltage of DC 35V is not  
measured between the red and  
black of the motor terminals.  
1. Indoor fan motor is defective.  
(Protecting operation on the P.C.  
board.)  
Start the operation with the following  
condition.  
2. Motor does not rotate.  
(The key operation is accepted.)  
2. Poor contact of the motor  
connector.  
1. Operation [Cooling]  
2. Airflow [High fan]  
3. The motor rotates, but it vibrates too 3. P.C. board is defective.  
much.  
3. Continuous operation  
– 54 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10-8-2. P.C. Board Layout  
GND  
5V  
35V  
12V  
TP1  
TP2  
BottomView  
(For the Top View, refer to page 61.)  
[1] Sensor characteristic table  
100  
90  
80  
70  
60  
50  
40  
30  
20  
TD  
TD : Discharge temp. sensor  
TA : Room temp. sensor  
TC : Heat exchanger temp. sensor  
TO : Outdoor temp. sensor  
TE : Outdoor heat exchanger temp. sensor  
TS : Suction temp. sensor  
TA, TC, TO, TE, TS  
40 50  
10  
0
0
10  
20  
30  
Temperature (˚C)  
– 55 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10-8-3. Indoor Unit (Other Parts)  
No.  
Part name  
Checking procedure  
1
Room temp. (TA) sensor  
Heat exchanger (TC) sensor  
Disconnect the connector and measure the resistance value with tester.  
(Normal temp.)  
Temperature  
10°C  
20°C  
25°C  
30°C  
40°C  
Sensor  
TA, TC (k)  
20,7  
12,6  
10,0  
7,9  
4,5  
2
3
Remote controller  
To item of How to judge whether remote controller is good or bad of the  
Judgment of trouble by symptom.  
Louver motor  
MP35EA7  
Measure the resistance value of each winding coil by using the tester.  
(Under normal temp. 25°C)  
Position Resistance value  
1
2
3
4
5
6
Brown  
Red  
Orange  
Yellow  
Pink  
1 to 4  
1 to 6  
2 to 3  
2 to 5  
130 10   
Blue  
4
Indoor fan motor  
Since judgment of DC motor is difficult on the single motor, refer to 10-  
5-1. (3).  
10-8-4. Outdoor Unit  
No.  
Part name  
Checking procedure  
1
Compressor  
(Model : DA91A1F-44F)  
Measure the resistance value of each winding by using the tester.  
Red  
Position  
Resistance value  
0,51 to 0,57 Ω  
0,51 to 0,57 Ω  
0,51 to 0,57 Ω  
Under 20°C  
Red - White  
White - Black  
Black - Red  
White  
Black  
2
Outdoor fan motor  
(Model : ICF-140-40-7)  
Measure the resistance value of winding by using the tester.  
Red  
Position  
Resistance value  
5 to 20 k Ω  
1 Yellow  
Yellow- Pink  
4 Pink  
5 Gray  
White  
Black  
For details, refer to Section 10-9.  
3
4
Compressor thermo. Bimetal Check conduction by using the tester.  
type (Model : PW - 2AL)  
Outdoor temperature sensor  
(TO), discharge temperature  
sensor (TD), suction  
temperature sensor (TS),  
outdoor heat exchanger  
temperature sensor (TE)  
Disconnect the connector, and measure resistance value with the tester.  
(Normal temperature)  
Temperature  
Sensor  
10°C  
20°C  
30°C  
40°C  
50°C  
TD (k)  
105  
64  
41  
27  
18  
TGa : Heat pump model only.  
TO, TS, TE : Refer to the TA, TC characteristic table in Indoor (Refer to  
Table 10-8-3, No. 1).  
– 56 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10-8-5. Checking Method for Each Part  
No.  
Part name  
Checking procedure  
1. Turn OFF the power supply breaker.  
1
Electrolytic capacitor  
(For raising pressure,  
smoothing)  
2. Discharge all four capacitors completely.  
3. Check that safety valve at the bottom of capacitor is not broken.  
4. Check that vessel is not swollen or exploded.  
5. Check that electrolytic liquid does not blow off.  
6. Check that the normal charging characteristics are shown in  
continuity test by the tester.  
C12 C13 C14 C15  
Case that product is good  
Pointer swings once, and  
returns slowly. When  
performing test once again  
under another polarity, the  
pointer should return.  
MCC-808  
Soldered  
surface  
C12, C13, C14 500µF/400V  
1. Turn OFF the power supply breaker.  
2
Converter module  
2. Discharge all four capacitors completely.  
3. Check that the normal rectification characteristics are shown in  
continuity test by the tester.  
Mark  
+ ~ – ~  
A
E
G
1
2
+ ~ – ~  
A
E
G
1
2
Diode check  
IGBT check  
Tester rod  
Tester rod  
Resistance value  
in good product  
Resistance value  
in good product  
+
~
~
+
~
G
~
~
1
2
2
E
50k or more  
(0 in trouble)  
50k or more  
(0 in trouble)  
~
~
~
~
1
2
1
2
1
2
+
A
E
– 57 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10-9. How to Simply Judge Whether Outdoor Fan Motor is Good or Bad  
1. Symptom  
• Outdoor fan motor does not rotate.  
• Outdoor fan motor stops within several tens seconds though it started rotating.  
• Outdoor fan motor rotates or does not rotate according to the position where the fan stopped., etc.  
Remote controller check code “02 : Outdoor block, 1A : Outdoor fan drive system error”  
2. Cause  
The following causes are considered when the outdoor fan motor does not normally rotate.  
1) Mechanical lock of the outdoor fan motor  
2) Winding error of the outdoor fan motor  
3) Position-detect circuit error inside of the outdoor fan motor  
or  
4) Motor drive circuit error of the outdoor P.C. board  
3. How to simply judge whether outdoor fan motor is good or bad  
Turn OFF the breaker.  
Disconnect two connectors (CN300 and CN301)  
of the outdoor fan motor from the inverter.  
NO  
Does the fan rotate without trouble  
when rotating it with hands?  
YES  
If the resistance value between  
1 (Red lead)  
2 (White lead)  
3 (Black lead)  
– 2 (White lead)  
– 3 (Black lead)  
– 1 (Red lead)  
CN300  
NO  
NO  
of the connector  
(CN300 : Motor winding)  
is 50 to 80 , it is normal.  
YES  
If the resistance value between  
1 (Yellow lead)  
– 4 (Pink lead)  
of the connector  
(CN301 : Motor position detection)  
is 5k to 20k , it is normal.  
YES  
Fan motor is normal.  
Fan motor error  
(Outdoor P.C. board error)  
NOTE :  
However, GND circuit error inside of the motor may be accepted in some cases when the above check is  
performed.  
When the fan motor does not become normal even if P.C. board is replaced, replace the outdoor fan motor.  
– 58 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11. HOWTO REPLACETHE MAIN PARTS  
11-1. Indoor Unit  
No.  
Part name  
Procedure  
Remarks  

Front panel  
1) After stopping the operation of the air conditioner,  
be sure to turn off the circuit breaker or disconnect  
the power plug from the AC wall socket.  
2) Open the screw caps and remove the two screws  
fixing the front panel.  
5
5
3) Close the screw caps as they were.  
4) Open the horizontal louver right below by your  
finger.  
3 2  
4
2 3  
5) Open the lower side of front panel until it touches  
the horizontal louver, and remove it from the indoor  
unit by turning it.  
<To assemble the front panel>  
1) Fix the two screws to secure the front panel.  
2) Close the screw caps as they were.  
3
3
3
3
3) Press four places where are the center, right end,  
left end and lower portions of the air outlet.  
4) Check the gap between the front panel and the  
main unit.  
If cooling or drying operation is performed without  
pressing the center of the air outlet, the surface of  
the front panel may be covered with frost and have  
a waterdrop.  
Electrical part  
assembly  
1) Perform the process  
above.  

Upper nail  
Screw  
2) Remove the screw securing the shield metal plate.  
Drain  
guide  
3) Remove the electrical part cover by pressing the  
nail located on upper portion of the electrical part  
cover.  
Screw  
4) Remove the drain guide.  
Electrical  
part cover  
5) Remove the screw securing to the end plate of the  
heat exchanger.  
6) Remove the connector (5p) for the fan motor and  
the connector (6p) for the louver motor from the  
microcomputer assembly.  
Lower fixing nail  
Screw  
7) After unhooking the electrical part base by press-  
ing the fixing nail located on its lower portion, draw  
the electrical part base out toward you to remove it  
from the main unit.  
8) Pull the TC sensor out from the holder of the heat  
exchanger.  
TC  
9) Dress the connecting cable securely as shown in  
the right illustration.  
sensor  
When assembling dress the connecting  
cable in loop and put it into the drain-pan.  
(Improper dressing will cause water leakage.)  
ƒ
Drain-pan  
assembly  
1) Perform the process  
above.  
2) Remove the drain-pan by pressing the four hooks  
downwards. (Keep it with the drain hose.)  
Hooks  
– 59 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
No.  
Part name  
Horizontal grille  
Note:  
Procedure  
1) Perform the process  
Remarks  
.
2) Remove the screw fixing the louver motor, and  
remove the louver motor.  
The horizontal  
grille can not be  
removed without  
removing the  
3) Remove the shaft of the horizontal grille from the  
drain-pan.  
Louver  
motor  
louver motor.  
Horizontal grille  
Screw  
Hooks  
Heat exchanger  
1) Perform the process  
.
ƒ
2) Remove the pipe holder from the rear side of main  
unit by removing the screw.  
Pipe  
holder  
3) Unhook the hooks fixing the left side of the heat  
exchanger and remove the screw fixing it, then  
remove the right side of the end plate from the rib  
fixing the main unit by sliding the heat exchanger  
slightly to the right side.  
Hooks fixing the  
heat exchanger  
Shaft bearing  
base  
Screw fixing the  
heat exchanger  
Cross flow fan  
1) Perform the process  
.
ƒ
2) Loosen the set screw of the cross flow fan.  
Hook  
3) Remove the screw fixing the shaft bearing base.  
Screw  
4) Lift slightly up the left side of the heat exchanger,  
and pull the shaft bearing base out left downwards.  
When assembling it, fix it with the set screw on the  
position where the gap between the rear plate surface  
and the left end surface of the cross flow fan is 6 to 7  
Shaft  
bearing  
base  
mm.  
Cross  
flow fan  
6 to 7mm  
Rear plate  
Shaft bearing  
1) Perform the process  
above.  
2) Remove the shaft bearing from the shaft bearing  
base.  
<Caution for assembling>  
• If a part of the shaft bearing is protruded from the  
housing, assemble it after pushing its portion into  
the correct position in the housing.  
ˆ
Fan motor  
1) Perform the process  
above.  
Mount the fan motor  
asshown in figure  
belowwhen  
Ribs  
2) Perform the process -2) above.  
assembling.  
3) Remove the left and right motor bands.  
Put the end of lead  
wire at the portion  
between two ribs.  
4) Remove the fan motor after pulling the cross flow  
fan out sliding it left and right.  
– 60 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11-2. Microcomputer  
No.  
Part name  
Procedure  
Remarks  

Common  
procedure  
1) Turn the power supply off to stop the operation of  
air-conditioner.  
Replace the thermal fuse, terminal  
block, microcomputer ass’y and the  
P.C. board ass’y.  
2) Remove the front panel.  
• Remove the two fixing screws. (Ø4 x 14l)  
3) Remove the electrical part base.  
<P.C. board layout>  
– 61 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11-3. Outdoor Unit  
No.  
Part name  
Procedure  
Remarks  
Common  
procedure  
1. Detachment  

Upper cabinet  
1) Stop operation of the air conditioner, and remove  
the power plug of the indoor unit from plug  
socket.  
Wiring  
cover  
2) Remove the valve cover. (ST1TØ4 x 10l 1 pc.)  
• After removing screw, remove the valve cover  
pulling it downward.  
Valve  
cover  
3) Remove wiring cover (ST1TØ4 x 10l 2 pcs.),  
and then remove connecting cable.  
4) Remove the upper cabinet.  
(ST1TØ4 x 10l 2 pcs.)  
• After removing screws, remove the upper  
cabinet pulling it upward.  
2. Attachment  
1) Attach the upper cabinet.  
(ST1TØ4 x 10l 2 pcs.)  
• Hook the rear side of the upper cabinet to claw  
of the rear cabinet, and then put it on the front  
cabinet.  
2) Perform cabling of connecting cable, and attach  
the wiring cover.  
• Insert the upper part into the upper cabinet,  
insert claw which has been hooked to the  
lower part into the square hole, and then fix it  
with screw. (ST1TØ4 x 10l 1 pc.)  
3) Attach the valve cover. (ST1TØ4 x 10l 1 pc.)  
• Insert the upper part to the upper cabinet, set  
hook claw of the valve cover to square holes  
(at three positions) of the main unit, and attach  
it pushing upward.  
Front cabinet  
1. Detachment  
1) Perform work of item 1 of  
.

2) Remove screws (ST1TØ4 x 10l 1 pc.) of the  
front cabinet and inverter cover and screws  
(ST1TØ4 x 10l 3 pcs.) of the front cabinet and  
lower part.  
• The left side of the front is made to insert to  
the rear cabinet, so remove it pulling upward.  
2. Attachment  
1) Insert claw at the left side of the front into the  
Claw  
Square hole  
rear cabinet.  
2) Hook the lower part at the right side of the front  
to concave part of the bottom plate. Insert claw  
of the rear cabinet into square hole of the front  
cabinet.  
3) Attach the removed screws to the original  
positions.  
Concave section  
– 62 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
No.  
Part name  
Procedure  
Remarks  
Inverter  
assembly  
1. Detachment  
1) Perform work of item 1 of  
Inverter cover  
ƒ
P. C. board  
(Soldered surface)  
.

2) Remove screw (ST1TØ4 x 10l 1 pc.) of the  
upper part of the front cabinet.  
• If removing the inverter cover in this condition,  
P.C. board can be checked.  
• If there is no space in the upper part of the  
upper cabinet, perform work of  
.
Plug of  
soldering  
iron  
Be careful to check the inverter because  
high-voltage circuit is incorporated in it.  
Discharging position  
(Discharging period  
10 seconds or more)  
3) Perform discharging by connecting + , – polarity  
by discharging resistance (approx. 10040W) or  
plug of soldering iron to + , – terminals of the  
C14 (printed “CAUTION HIGH VOLTAGE” is  
attached.) electrolytic capacitor (500µF) on P.C.  
board.  
Be careful to discharge the capacitor  
because the electrolytic capacitor cannot  
naturally discharge and voltage remains  
according to trouble type in some cases.  
Bundled  
part  
NOTE :  
Holder  
This capacitor is one with mass capacity.  
Therefore, it is dangerous that a large  
spark generates if short-circuiting be-  
tween + , – polarity with screwdriver, etc.  
for discharging.  
Terminal block  
The connector is one with lock,  
so remove it while pushing the  
part indicated by an arrow.  
4) Remove screw (ST1TØ4 x 10l 1 pc.) fixing the  
main body and the inverter box.  
5) Remove various lead wires from the holder at  
upper part of the inverter box and wiring holder  
at right side of the terminal block.  
6) Remove the lead wire from the bundled part at  
left side of the terminal block.  
7) Pull the inverter box upward.  
8) Disconnect connectors of various lead wires.  
Requirement :  
As each connector has a lock mecha-  
nism, avoid to remove the connector by  
holding the lead wire, but by holding the  
connector.  
Be sure to remove the connector  
by holding the connector, not by  
pulling the lead wire.  
– 63 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
No.  
Part name  
Procedure  
Remarks  
Control board 1) Disconnect lead wires and connectors connected  
assembly  
from the control board assembly to other parts.  
1. Lead wires  
CN301  
CN300  
CN703  
CN500  
CN701  
• Connection with terminal block :  
3 wires (Black, White, Orange)  
• Connection with compressor :  
Remove the connector (3P).  
CN602 CN601  
CN600 CN603  
• Connection with reactor :  
Remove the relay connectors from P07, 08  
(2P, White) and P12, 13 (2P, Yellow).  
2. Connectors  
CN300, CN301 and CN701, etc.  
at the control board assembly  
side are connectors with locks.  
Therefore, remove the connector  
while pushing the part indicated  
by an arrow.  
CN300 : Outdoor fan (3P, White)  
CN301 : Outdoor fan position detection  
(5P, White)  
CN701 : 4 valve (3P,Yellow)  
CN600 : TE sensor (2P, White)  
CN601 : TD sensor (3P, White)  
CN603 : TS sensor (3P, White)  
CN602 : TO sensor (2P, White)  
CN500 : Case thermo. (2P, White)  
CN703 : Pulse modulating valve (6P, White)  
2) Remove the control board assembly from P.C.  
board base.  
1. Main control board assembly side  
• Remove two claws of P.C. board base, and  
remove upward the heat sink with hands.  
• Remove three screws fixing the heat sink  
and main control board assembly side, and  
replace the board with a new one.  
P.C. board base  
P.C. board  
When mounting a new board,  
check that the board is correctly  
set in the groove of base holder  
of P.C. board base.  
Rear cabinet  
1) Perform work of item 1 of , and  

.
‚ ƒ  
Reactor  
2) Remove fixed screws fixing to the bottom plate.  
(ST1TØ4 x 10l 3 pcs.)  
3) Remove fixed screws fixing to the heat  
exchanger. (ST1TØ4 x 10l 2 pcs.)  
4) Remove fixed screw fixing to the valve mounting  
plate. (ST1TØ4 x 10l 1 pc.)  
– 64 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
No.  
Part name  
Procedure  
1) Perform work of item 1 of  
Remarks  
Fan motor  
and  
.

2) Remove the flange nut fixing the fan motor and  
the propeller.  
Fan motor  
• Flange nut is loosened by turning clockwise.  
(To tighten the flange nut, turn counterclock-  
wise.)  
Propeller fan  
3) Remove the propeller fan.  
4) Disconnect the connector for fan motor from the  
inverter.  
5) Remove the fixing screws (3 pcs.) holding by  
hands so that the fan motor does not fall.  
Flange nut  
Compressor  
1) Perform work of item 1 of  
2) Extract refrigerant gas.  
and  
,
,
,
‚ ƒ „ ꢀ  
.

3) Remove the partition board.  
(ST1TØ4 x 10l 2 pcs.)  
4) Remove the sound-insulation material.  
5) Remove terminal cover of the compressor, and  
disconnect lead wire of the compressor thermo.  
and the compressor from the terminal.  
6) Remove pipe connected to the compressor with  
a burner.  
7) Remove the fixing screw of the bottom plate and  
heat exchanger. (ST1TØ4 x 10l 1 pc.)  
8) Remove the fixing screw of the bottom plate and  
valve clamping plate. (ST1TØ4 x 10l 2 pcs.)  
9) Pull upward the refrigeration cycle.  
10) Remove nut fixing the compressor to the  
bottom plate.  
Partition  
board  
Valve  
clamping  
plate  
Compressor  
thermo.  
Compressor  
Reactor  
1) Perform work of item 1 of , and  
2) Remove lead wires clung in holder on the  
partition board.  
.
ƒ

ˆ
Reactor  
3) Remove screws fixing the reactor.  
(ST1TØ4 x 10l 2 pcs.)  
– 65 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
No.  
Part name  
Pulse  
modulating  
valve coil  
Procedure  
Remarks  
1. Detachment  
1) Perform work of item 1 of , and  
,
,
.

‚ ƒ ꢀ  
2) Turn the coil clockwise (counterclockwise) by 90  
degrees, and remove coil from the pulse modu-  
lating valve.  
2. Attachment  
Take-out part  
1) Set take-out part of the lead wire of coil to the  
coil inserting position of the pulse modulating  
valve, and attach the coil.  
2) Turn the coil by 90 degrees, set surely the  
concave part at lower part of the coil to the  
positioning hole of the pulse modulating valve,  
and then fix the coil.  
of lead wire  
Notch  
Coil inserting  
position  
Coil fix  
position  
The pulse modulating valve has A room  
side and B room side. After mounting it,  
check that coil at B room side (Red  
marking is marked on the pulse modulat-  
ing valve.) is connected to CN13 of the  
control board assembly.  
Coil inserting  
position  
Positioning  
hole  
Fan guard  
1. Detachment  
Š
1) Perform work of item 1 of , and  
.

2) Remove the front cabinet, and put it down so  
that fan guard side directs downward.  
Minus screwdriver  
Hooking claw  
Perform work on a corrugated cardboard,  
cloth, etc. to prevent flaw to the product.  
3) Remove the hooking claws by pushing minus  
screwdriver according to the arrow mark in the  
right figure, and remove the fan guard.  
2. Attachment  
1) Insert claw of the fan guard in the hole of the  
front cabinet. Push the hooking claws (10  
positions) by hands and fix the claws.  
All the attaching works have completed.  
Check that all the hooking claws are fixed  
to the specified positions.  
– 66 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
No.  
Part name  
Procedure  
Remarks  
11  
Replacement  
of temperature  
sensor for  
1) Cut the sensor 100 mm longer than old one.  
2) Cut the protective tube after pulling out it  
(200 mm).  
Cutting here  
100  
Thermal  
servicing only  
3) Move the protective tube toward the thermal  
sensor side and tear the tip of lead wire in  
two then strip the covering part.  
4) Pass the stripped part through the thermal  
constringent tube.  
Connector  
sensor part  
Common service  
parts of sensor  
TO, TS, TE, TD  
Cutting here  
200  
5) Cut the old sensor 100 mm length on the  
connector side, and recycle that connector.  
6) Tear the lead wire in two on the connector  
side and strip the covering part.  
Thermal  
constringent tube  
7) Twist the leads on the connector and sensor  
sides, and solder them.  
8) Move the thermal constringent tubes toward  
the soldered parts and heat them with the  
dryer and constring them.  
Cutting here  
100  
9) Wind the attached color tape round the both  
terminals of the protective tube when colored  
protective tube is used.  
Soldered part  
10)Fix the sensor again.  
NOTES :  
1) Store the joint part of the sensor and the  
connector in the electric parts box.  
2) Never joint them near the thermal sensor  
part. Otherwise it would cause insulation  
inferiority because of dew drops.  
3) When replacing the sensor using the colored  
protective tube, wind the color tape matching  
the color of that tube.  
Dryer  
Winding the color tape  
These are parts  
for servicing  
sensors.  
Parts name  
Q'ty  
Remarks  
Length : 3m  
For spare  
1
2
3
4
5
6
Sensor  
1
1
1
3
1
3
Sensor Spring (A)  
Sensor Spring (B)  
Thermal constringent tube  
Color tape  
Please check  
that the accesso-  
ries shown in the  
right table are  
packed.  
For spare  
Including one spare  
9 colors  
Terminal  
– 67 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MCC-808  
– 68 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12. EXPLODED VIEWS AND PARTS LIST  
12-1. Indoor Unit (1)  
RAS-10YKV-E, RAS-13YKV-E  
407 : RAS-10YKV-E  
408 : RAS-13YKV-E  
404  
402  
412  
413  
403  
405  
Location  
No.  
Part  
No.  
Location  
No.  
Part  
No.  
Description  
Description  
402  
403  
404  
405  
43T60002 Terminal Block, 3P,  
AC 300V, 20A  
407  
408  
412  
413  
43T69062 P.C. Board Assembly,  
MCC-772 (10YKV-E)  
43T69004 Sensor, Heat Exchanger  
10k, 25°C  
43T69005 Sensor, Thermostat  
10k, 25°C  
43T69031 P.C. Board, Assembly,  
WRS-LED, MCC-766  
43T69063 P.C. Board Assembly,  
MCC-772 (13YKV-E)  
43T61001 Base, E-Parts,  
ABS, Black UL94-5V  
43T62006 Base, Shield  
SGCC-Z08-LUB  
– 69 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor Unit (2)  
233  
230  
231  
RAS-10YKV-E, RAS-13YKV-E  
228  
222  
221  
215  
216  
217  
229  
244  
211  
214  
210  
232  
201  
202  
226  
227  
236  
225  
220  
218  
219  
243  
213  
206  
224  
245  
204  
207  
212  
209  
241  
239  
208  
246  
237  
203  
242  
238  
Location  
No.  
Part  
No.  
Location  
No.  
Part  
No.  
Description  
Description  
201  
202  
203  
204  
206  
207  
208  
208  
209  
210  
43T00043 Front Panel Assembly  
43T00044 Grille, Suction  
43T80001 Air Filter (L)  
43T80002 Air Filter (R)  
43T07021 Screw Cap (L)  
222  
224  
225  
226  
227  
228  
229  
230  
231  
232  
233  
236  
237  
238  
239  
241  
242  
243  
244  
245  
246  
43T49023 Holder of Plate of EVA-SEAL  
43T79002 Drain Guide  
43T39002 Motor Band (Left)  
43T39001 Motor Band (Right)  
43T21010 Fan Motor  
43T20007 Fan, Cross Flow  
43T22002 Bearing  
43T39003 Base, Bearing  
43T03001 Rear Plate  
43T07020 Screw Cap (R)  
43T08106 LED Panel (10YKV-E)  
43T08107 LED Panel (13YKV-E)  
43T19004 Accepted Signal Filter  
43T09035 Horizontal Louver Assembly  
for Service  
43T09004 Louver Assembly  
43T70001 Drain Hose Assembly  
43T21003 Motor, Stepping  
43T07001 Bushing  
43T44024 Refrigerant Cycle Assembly  
43T47006 Pipe, Delivery  
43T47005 Pipe, Suction  
43T49007 Pipe, Shield  
43T07002 Pipe Holder  
43T82001 Installation Plate  
43T69044 Remote Controller  
43T63002 Holder, Remote Controller  
43T62020 Cover, E-Parts  
43T62002 Cover, Up, Terminal  
43T62003 Cord Clamp  
43T62004 Shield Cover  
43T39010 Drain Guide (UP)  
43T49024 U Pipe Holder  
43T01002 Mark  
211  
212  
213  
214  
215  
216  
217  
218  
219  
220  
221  
43T19003 Holder, Sensor  
43T49003 Spring  
43T49028 Plate, EVA-SEAL  
43T85061 Manual  
– 70 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12-2. Outdoor Unit  
RAS-10YAV-E, RAS-13YAV-E  
31  
2
32  
17, 18  
1
8
11, 13  
12, 14  
19  
7
10  
28  
20  
23  
21  
9
22  
24, 25  
6
2
5
4
33  
1
26, 27, 29  
22  
23  
3
4
5
29  
15  
Location  
No.  
Part  
No.  
Location  
No.  
Part  
No.  
Description  
Description  
01  
02  
03  
04  
05  
06  
07  
08  
09  
10  
11  
12  
13  
14  
15  
17  
43005368 Cabinet, Back, Assembly  
43005369 Cabinet, Upper, Assembly  
43005401 Cabinet, Front, Assembly  
4301V030 Guard, Fan  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
31  
32  
33  
43046378 Coil, P.M.V.  
43058264 Reactor  
43050298 Thermo. Bimetal, CS-7  
4302C019 Motor, Fan, DC  
43047549 Nut, Flange  
43020310 Fan, Propeller  
43097204 Nut  
43049643 Cushion, Rubber  
43063274 Holder, Sensor  
43063198 Holder, Sensor  
43063195 Holder, Thermo. Bimetal  
43019904 Holder, Sensor  
43046344 Valve, 4-way  
43046348 Solenoid Coil  
43032441 Drain Nipple  
43042461 Base, Assembly  
4301V012 Cover, Valve, Packed  
43062230 Cover, Wiring, Assembly  
43019903 Hanger  
43041607 Compressor  
43043644 Condenser, Assembly  
43046382 Valve, Packed, 6,35  
43046383 Valve, Packed, 9,52  
43147196 Bonnet, 1/4 IN  
43047401 Bonnet, 3/8 IN  
43047491 Tube, Capillary, I.D.1,5  
43046351 Valve, Pulse Modulating  
– 71 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12-3. P.C. Board Layout  
RAS-10YAV-E, RAS-13YAV-E  
704  
708  
707  
703  
701  
TO Sensor (Ø6)  
TE Sensor (Ø6)  
TS Sensor (Ø6)  
706  
TD Sensor (Ø4)  
702  
4
4
3
2
1
4
3
2
1
705  
Location  
No.  
Part  
No.  
Location  
No.  
Part  
No.  
Description  
Description  
701  
702  
703  
704  
43050382 Sensor, TC (F6)  
43050334 Sensor, TD (F4)  
705  
706  
707  
708  
4306A044 Terminal block, 9P  
43062215 Base, P.C. Board  
43063306 Heatsink  
43060052 Fuse, 25A, 250V, Lead Type  
43060726 Fuse, 15A, 250V, Lead Type  
4306S230 P.C. Board Assembly,  
MCC-808  
– 72 –  
Download from Www.Somanuals.com. All Manuals Search And Download.  
T O S H IB A C A R R IE R C O R P O R A T IO N  
3 3 6 T A D E H A R A F U J I-S H I, S H IZ U O K A -K E N , 4 1 6 -8 5 2 1 , J A P A N  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TURN  
407 (10YKV-E)  
43T69062  
404 43T69005  
Sensor,Thermostat  
10kW, 25°C  
P.C. Board Assembly,  
M40C7C-(71732YKV-E)  
43T69063  
P.C. Board Assembly,  
MCC-772  
402 43T60002  
Terminal Block, 3P,  
AC 300V, 20A  
412 43T61001  
Base, E-Parts,  
ABS, Black UL94-5V  
413 43T61001  
Base, E-Parts,  
ABS, Black UL94-5V  
403 43T69004 Sensor,  
Heat Exchanger  
10kW, 25°C  
405 43T69031  
P.C. Board,Assembly,  
WRS-LED, MCC-766  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TURN  
211 43T09004  
Louver Assembly  
214 43T07001  
Bushing  
201 43T00043  
210 43T09035  
212 43T70001  
Front Panel Assembly  
Horizontal Louver  
Drain Hose Assembly  
Assembly for Service  
202 43T00044  
Grille, Suction  
213 43T21003  
Motor, Stepping  
206 43T07021  
Screw Cap (L)  
239 43T62002  
245  
Cover, Up, Terminal  
43T01002  
Mark  
207 43T07020  
Screw Cap (R)  
209 43T19004  
Accepted Signal Filter  
208 (10YKV-E)  
43T08106  
LED Panel  
238 43T62020  
208 (10YKV-E)  
203 43T80001  
Cover, E-Parts  
43T08106  
Air Filter (L)  
LED Panel  
204 43T80002  
Air Filter (R)  
242 43T62004  
Shield Cover  
246 85061  
Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TURN  
231 43T03001  
Rear Plate  
233 43T82001  
228 43T20007  
Installation Plate  
Fan, Cross Flow  
230 43T39003  
Base, Bearing  
222  
43T49023  
Holder of Plate  
of EVA-SEAL  
221  
232 43T07002  
229  
43T49028  
Pipe Holder  
43T22002  
Bearing  
Plate, EVA-SEAL  
215  
236 43T69044  
43T44024  
Refrigerant  
Cycle Assembly  
244 43T49024  
Remote Controller  
U Pipe Holder  
226  
43T39001  
Motor Band (Right)  
220  
216  
227 43T21010  
43T49003  
Spring  
43T47006  
Pipe, Delivery  
Fan Motor  
225 43T39002  
Motor Band (Left)  
241 43T62003  
243  
Cord Clamp  
43T39010  
237  
Drain Guide (UP)  
43T63002  
Holder, Remote  
Controller  
224 43T79002  
217 43T47005  
Drain Guide  
218 43T49007  
Pipe, Suction  
219 43T19003  
Pipe, Shield  
Holder, Sensor  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TURN  
1
43005368  
2
43005369  
Cabinet, Back, Assembly  
Cabinet, Upper,  
Assembly  
8
43019903  
Hanger  
7
19  
43062230  
43058264  
Reactor  
Cover, Wiring,  
Assembly  
21 4302C019  
Motor, Fan, DC  
23 43020310  
Fan, Propeller  
22 43047549  
Nut, Flange  
24  
43097204  
6
4301V012  
N25ut  
Cover, Valve, Packed  
43049643  
Cushion, Rubber  
5
43042461  
Base, Assembly  
33 43032441  
Drain Nipple  
3
43005401  
Cabinet, Front, Assembly  
4
4301V030  
Guard, Fan  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TURN  
31 43046344  
17 43046351  
Valve, 4-way  
Valve, Pulse Modulating  
18 43046378  
32 43046348  
Solenoid Coil  
Coil, P.M.V.  
11 43046382  
Valve, Packed, 6,35  
13 43147196  
Bonnet, 1/4 IN  
12 43046383  
10  
Valve, Packed, 9,52  
14 43047401  
43043644  
Condenser,  
Assembly  
28 43063195  
Holder, Thermo. Bimetal  
Bonnet, 3/8 IN  
20 43050298  
Thermo. Bimetal, CS-7  
2
43005369  
9
43041607  
Cabinet, Upper,  
Assembly  
Compressor  
1
43005368  
Cabinet, Back,  
Assembly  
4
4301V030  
Guard, Fan  
26 43063274  
22 43047549  
H27old4e3r0, 6S3e1n9s8or  
Nut, Flange  
23 43020310  
H29old4e3r0, 1S9e9n0s4or  
Fan, Propeller  
Holder, Sensor  
5
43042461  
15 43047491  
Tube, Capillary, I.D.1,5  
29 43019904  
Base, Assembly  
Holder, Sensor  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TURN  
704 43060726  
Fuse, 15A, 250V, Lead Type  
708 4306S230  
P.C. Board Assembly,  
MCC-808  
707 43063306  
703 43060052  
Heatsink  
Fuse, 25A, 250V, Lead Type  
701 43050382  
Sensor, TC (F6)  
TO Sensor (Ø6)  
TE Sensor (Ø6)  
706 43062215  
TS Sensor (Ø6)  
Base, P.C. Board  
TD Sensor (Ø4)  
702 43050334  
Sensor, TD (F4)  
4
4
3
2
1
4
3
2
1
705 4306A044  
Terminal block, 9P  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Tektronix Sander TDS 600C TDS 700D User Manual
Thermador Refrigerator T24IR User Manual
Toro Lawn Mower 13AX60RG744 User Manual
Toshiba Flat Panel Television SRTTM1 User Manual
TP Link Dishwasher TL SG1008 User Manual
Tricity Bendix Dishwasher TBDW 41 User Manual
Tyco Network Card S610s User Manual
ViewSonic Computer Monitor P75F+ User Manual
Vornado Iron SF 510 User Manual
Vulcan Hart Griddle RRE24D User Manual