State Industries Electric Heater GP650HTPDT User Manual

COMMERCIAL / RESIDENTIAL GAS WATER HEATERS  
SERVICE HANDBOOK  
ULTRA HIGH EFFICIENCY  
POWER VENT / POWER DIRECT VENT  
FOR MODELS:  
• SHE50-100 NE  
• SHE50-100 PE  
• GP650 YTPDT  
• GP650 HTPDT  
PRINTED 0308  
198148-000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
INTRODUCTION  
This Service Manual is designed to be an aid in servicing and troubleshooting the 96%  
thermally efficient, 50 gallon, 100,000 Btu/hr residential and light duty commercial power  
vent - power direct vent model water heaters listed on the cover of this manual.The  
instructions, illustrations and procedures contained in this manual are used to verify proper  
operation and to diagnose and repair common service problems.  
This manual does not replace or supersede the Instruction Manual that came with the water  
heater. Always refer to the Instruction Manual that came with the water heater for complete  
installation instructions. If the Instruction Manual is not available copies can be obtained  
from the manufacturers web site or by calling the technical support phone number shown on  
the water heater labeling.  
QUALIFICATIONS - QUALIFIED SERVICE AGENT  
Servicing the products referenced in this manual requires the ability (in the field involved)  
equivalent to that of a Qualified Service Agent as defined by the American National  
Standards Institute (ANSI) below. Installation skills such as plumbing, air supply, venting,  
gas supply, electrical supply are required in addition to diagnostic and electrical testing  
skills.  
ANSI Z223.1 2006 Sec. 3.3.83: “Qualified Agency” - “Any individual, firm, corporation or  
company that either in person or through a representative is engaged in and is responsible  
for (a) the installation, testing or replacement of gas piping or (b) the connection, installation,  
testing, repair or servicing of appliances and equipment; that is experienced in such work;  
that is familiar with all precautions required; and that has complied with all the requirements  
of the authority having jurisdiction.”  
SERVICE WARNING  
If you are not qualified (as defined by ANSI above) and licensed or certified as required by  
the authority having jurisdiction to perform a given task do not attempt to perform any of the  
service or installation procedures described in this manual. If you do not understand the  
instructions given in this manual or do not feel confident in your abilities to perform a given  
task do not attempt to perform any procedures outlined in this manual.  
IMPORTANT SERVICE REMINDER  
When performing any troubleshooting step outlined in this Service Manual always consider  
the wiring and connectors between components. Perform a close visual inspection of all  
wiring and connectors to and from a given component before replacement. Ensure wires  
were stripped before being crimped in a wire connector, ensure wires are crimped tightly in  
their connectors, ensure connection pins in sockets and plugs are not damaged or worn,  
ensure plugs and sockets are mating properly and providing good contact.  
Failure to perform this critical step or failing to perform this step thoroughly often results in  
needless down time, unnecessary parts replacement, and customer dissatisfaction.  
Technical Literature Department  
2 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
INSTRUCTION MANUAL  
Have a copy of the Instruction Manual that came with the water heater on hand for the  
correct model water heater you are working with before servicing.  
Installation information given in this Service Manual is not a complete installation  
instruction. Installation information covered in this Service Manual has a limited focus as it  
applies to servicing. This Service Manual does not replace or supersede the Instruction  
Manual that came with the water heater. Always refer to the Instruction Manual that came  
with the water heater for complete installation instructions.  
If the Instruction Manual is not on hand copies can be obtained from the manufacturers web  
site or by calling the technical support phone number shown on the water heater labeling.  
TOOLS REQUIRED  
• Instruction Manual that came with the water heater.  
• All tools common to installation and service of commercial water heaters such as hand  
tools, torch, pipe wrenches etc.  
• Long (8-10”) T handle SAE hex (allen key) wrenches including 5/32”, 1/8” and 1/4” - for  
blower, burner, and gas valve removal and installation.  
• Two digital manometers range -20.00 to +20.00" W.C., resolution - 0.01" W.C.  
Recommend UEI model EM200 or equivalent. Required to test performance of air  
pressure switches. Also used to measure low pressure supply gas and manifold gas  
pressure.  
• Digital Multi Meter DMM; recommend Fieldpiece HS36, Fluke 187, UEI DL289 or  
equivalent capable of measuring:  
• AC/DC Voltage  
• AC Frequency (Hz)  
• Ohms  
• DC micro amps µA (flame sensing current)  
• AC amp meter- recommend UEI model DL289 or equivalent.  
• 120 VAC household outlet tester (see Service Notes Electrical page 8)  
Technical Literature Department  
3 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
INSTALLATION CONSIDERATIONS  
INSTRUCTION MANUAL  
Installation information given in this Service Manual is not a complete installation  
instruction. Installation information covered in this Service Manual has a limited focus as it  
applies to servicing. This Service Manual does not replace or supersede the Instruction  
Manual that came with the water heater. Always refer to the Instruction Manual that came  
with the water heater for complete installation instructions.  
If the instruction Manual that came with the water heater is not on hand copies can be  
obtained from the manufacturers web site or by calling the technical support phone number  
shown on the water heater labeling.  
CLOSED WATER SYSTEMS  
Water supply systems may, because of code requirements or such conditions as high line  
pressure, among others, have installed devices such as pressure reducing valves, check  
valves, and back flow preventers. Devices such as these cause the water system to be a  
closed system.  
Virtually all commercial and most residential water supply systems are closed systems  
today. Closed water systems will experience thermal expansion which, if not controlled with  
a properly installed and sized thermal expansion tank, can cause premature failure  
(leakage) of the water heater. Water heater failure (leakage) on closed systems where there  
is not a thermal expansion tank installed is not covered under the limited warranty.  
THERMAL EXPANSION  
As water is heated, it expands (thermal expansion). In a closed system the volume of water  
will grow when it is heated. As the volume of water grows there will be a corresponding  
increase in water pressure due to thermal expansion. Thermal expansion can cause  
premature tank failure (leakage). This type of failure is not covered under the limited  
warranty. Thermal expansion can also cause intermittent temperature-pressure relief valve  
operation: water discharged from the valve due to excessive pressure build up. This  
condition is not covered under the limited warranty. The temperature-pressure relief  
valve is not intended for the constant relief of thermal expansion.  
A properly sized thermal expansion tank should be installed on all closed systems to control  
the harmful effects of thermal expansion.  
Technical Literature Department  
4 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
AIR REQUIREMENTS  
Carefully review the requirements for combustion and ventilation air in the Instruction  
Manual that came with the water heater. Failure to meet these requirements when the water  
heater is installed or overlooking their importance when servicing the water heater often  
results in needless down time, unnecessary parts replacement, and customer  
dissatisfaction. If the Instruction Manual is not on hand copies can be obtained from the  
manufacturers web site or by calling the technical support phone number shown on the  
water heater labeling.  
An inadequate supply of air for combustion and ventilation often causes operational  
problems. A lack of combustion and ventilation air can create a negative ambient air  
pressure in the installed space which can lead to improper combustion and operational  
problems with air pressure switches.  
CONTAMINATED AIR  
Combustion air that is contaminated can greatly diminish the life span of the water heater  
and water heater components such as hot surface igniters and burners. Propellants of  
aerosol sprays, beauty shop supplies, water softener chemicals and chemicals used in dry  
cleaning processes that are present in the combustion, ventilation or ambient air can cause  
such damage.  
Vapors from volatile compounds such as solvents, cleaners, chlorine based chemicals and  
refrigerants in addition to being highly flammable in many cases, can also react to form  
highly corrosive substances such as hydrochloric acid inside the water heater’s combustion  
chamber. The results can be hazardous and cause product failure.  
If this water heater will be installed in beauty shops, barber shops or laundries with dry  
cleaning equipment, it is imperative the water heater be installed as a Direct Vent appliance  
so that air for combustion is derived directly from the outside atmosphere through a sealed  
intake air pipe. See the Installation of Vent System section in the Instruction Manual that  
came with the water heater for more information on Direct Vent installations.  
Technical Literature Department  
5 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
VENTING  
The venting information presented in this Service Manual is not a complete venting  
installation instruction. Refer to the Instruction Manual that came with the water heater for  
complete installation instructions.  
The water heater covered in this Service Manual may be installed as a conventionally  
vented water heater or as a direct vent water heater. Conventional vent installations use  
room air for combustion. There will be one “vent” pipe installed on a conventional vent  
installation. Direct vent installations derive all air for combustion from the outdoor  
atmosphere through a second “intake air” pipe. There will be two pipes (vent and intake air)  
installed on a direct vent installation.  
The vent and intake air piping (direct vent installations) may not be combined with any other  
appliances under any conditions.  
Maximum Equivalent Length Requirements  
The vent and intake air pipe (direct vent installations) for the water heater covered in this  
Service Manual can be installed using 2, 3, or 4 inch pipe depending on the overall  
“equivalent” length of each pipe; see Table 1 on page 7.  
The vent and intake air terminations do not factor into the overall equivalent feet  
calculations.  
The vent and intake air connection fittings on the water heater do not factor into the overall  
equivalent feet calculations.  
Additional 2 or 3 inch 90° elbows installed are equivalent to 5 linear feet of pipe. Additional 4  
inch 90° elbows are equivalent to 8 linear feet of pipe. 45° elbows will count for half the  
equivalent length a 90° elbow does.  
= 5 linear feet of pipe  
2”  
= 5 linear feet of pipe  
3”  
= 8 linear feet of pipe  
4”  
Overall equivalent lengths are determined by adding the total length of pipe installed to the  
accumulated total equivalent length of all the additional elbows factored in.  
The maximum equivalent lengths given in the Instruction Manual that came with the water  
heater and shown in Table 1 (page 7) are for the vent pipe AND for the intake air pipe. IE: A  
2 inch vent pipe can be up to 20 equivalent feet with one 90° elbow. On a direct vent  
installation the 2 inch intake air pipe can also be up to 20 equivalent feet with one 90° elbow.  
Carefully review the venting installation instructions and maximum equivalent length  
requirements for the vent and intake air piping. Ensure the vent system has been installed  
per Instruction Manual requirements.  
Technical Literature Department  
6 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
VENTING (CONT)  
Pipe Size Requirements  
Ensure the correct size pipe has been used for the overall equivalent length of the vent and  
intake air piping installed. Longer equivalent lengths require larger pipe sizes, see Table 1.  
Maximum Elbow Requirements  
Three and four inch vent and intake air pipe installations allow a maximum of 6 - 90° elbows  
in the vent pipe AND a maximum 6 - 90°elbows in the intake air pipe. Two inch installations  
allow a maximum of 3 - 90° elbows in the vent pipe AND a maximum 3 - 90° elbows the  
intake air pipe.  
Table 1  
NUMBER  
2” MAXIMUM PIPE  
3” MAXIMUM PIPE  
4” MAXIMUM PIPE  
90° ELBOWS  
LENGTH FEET (METERS) LENGTH FEET (METERS) LENGTH FEET (METERS)  
1
2
3
20 (6.1)  
15 (4.6)  
10 (3.0)  
60 (18.3)  
55 (16.8)  
50 (15.2)  
120 (36.6)  
112 (34.1)  
104 (31.7)  
4 elbows not allowed in 2” pipe  
(use larger pipe size)  
4
5
6
45 (13.7)  
40 (12.2)  
35 (10.7)  
96 (29.3)  
88 (26.8)  
80 (24.3)  
5 elbows not allowed in 2” pipe  
(use larger pipe size)  
6 elbows not allowed in 2” pipe  
(use larger pipe size)  
Service Notes - Venting  
Remove all plastic debris from the edges of intake air pipe sections after cutting on direct  
vent installations. Plastic debris left on intake air pipe sections can collect inside and clog the  
burner and lead to rough operation and/or ignition failure. See Service Notes page 11.  
Using a smaller pipe size than required for a given length or installing more elbows on the  
vent pipe can cause the water heater’s control system to declare a fault condition, lock out  
and display the “Blocked Exhaust” fault message on the UIM display (see page 27).  
Overlooking the same requirements for the intake air pipe on direct vent installations or  
failing to remove the screen from the intake air connection when direct venting can cause  
the water heater’s control system to declare a fault condition, lock out and display the  
Blocked Inlet” fault message on the UIM display (see page 27).  
The screen inside the intake air connection is meant to keep  
larger debris from entering the blower when the water heater is  
installed conventionally; using room air for combustion.  
Remove This Screen  
For Direct Vent  
Installations  
When the water heater is installed in a direct vent configuration  
the screen inside the intake air connection on the water heater  
must be removed. If left in place it will become clogged over time  
and lead to “Blocked Inlet” lock out conditions.  
The screen on the intake air termination will keep larger debris  
from entering the blower on direct vent installations.  
Technical Literature Department  
7 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
ELECTRICAL REQUIREMENTS  
The water heater covered by this Service Manual must be grounded in accordance with  
the local codes, or in the absence of local codes: the National Electrical Code (NFPA 70) or  
the Canadian Electrical Code (C22.1).  
The water heater covered by this Service Manual requires a 120 VAC 1Ø (single phase)  
power supply. It is factory equipped with a standard 3 prong appliance cord that plugs into a  
standard 120 VAC wall outlet. 5.2 FLA (full load amps) approximate.  
As shown in the illustration below there should be 120 VAC present between the power  
supply hot and ground wires. 120 VAC should also present between the hot and neutral  
wires. There should be 0 VAC present between the neutral and ground wires.  
Correct wiring for a standard 120 VAC wall outlet is also shown in the Illustration below. Note  
the orientation of the ground connect is at the bottom. Reversed polarity is when the hot and  
neutral wires are connected opposite from what is shown here.  
Service Notes - Electrical  
This water heater is a polarity sensitive appliance and will not operate if the power supply  
polarity is reversed. If the polarity of the power supply is reversed the water heater’s control  
system will declare a fault condition and display “AC Reversed” on the UIM display.  
The water heater’s burner must be grounded for flame sensing current to be established and  
verify ignition. If the burner is not grounded the water heater’s control system will declare a  
fault condition and display “Ignition Failure” on the UIM display after 3 failed ignition trials.  
Also shown is an outlet tester that will quickly determine if the plug is wired correctly. These  
testers will also diagnose reversed polarity, open ground and open neutral wire problems.  
Outlet testers are inexpensive and simple to use. They are available at most hardware  
stores and home centers.  
120 VAC 1Ø Power Supply  
Correctly Wired Outlet  
120 VAC 1Ø  
Wall Outlet  
HOT  
NEUTRAL  
GROUND  
Neutral  
Hot  
Ground  
Outlet Tester  
120 volts  
0 volts  
120 volts  
Technical Literature Department  
8 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
OPERATION & SERVICE  
HOW IT WORKS  
This section of the Service Manual will cover operation, common service procedures and  
water heater construction. The water heater covered in this Service Manual has a helical coil  
shaped heat exchanger that is submerged in the storage tank. The water heater uses a top  
mounted down fired radial burner. This is a forced draft burner; hot burning gases are forced  
through the heat exchanger under pressure and exit through the exhaust/vent connection  
located at the bottom of the water heater.  
INTERNAL VIEW  
COMBUSTION  
BLOWER/BURNER  
AIR INTAKE  
GAS VALVE  
ASSEMBLY  
CONNECTION  
Starting at the top combustion air and  
fuel gas are drawn in by the blower  
The hot burning gases exit the radial  
through the coil shaped heat  
exchanger.  
Flue gases spiral through the heat  
exchanger and exit the water heater  
through the exhaust/vent connection  
at the bottom.  
EXTERNAL VIEW  
COMBUSTION  
AIR INTAKE  
HELICAL  
SHAPED  
HEAT EXHNGER  
CONNECTION  
EXHAUST/VENT  
CONNECTION  
EXHAUST/VENT  
CONNECTION  
Technical Literature Department  
9 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
BLOWER  
The blower is an assembly consisting of the blower housing, motor and an integrated VFD  
(variable frequency drive). Blower operation is controlled by the CCB (central control  
board - page 35). The CCB sends 120 VAC to the Blower/VFD assembly high voltage 3 pin  
socket. The CCB also sends a PWM (pulse width modulation) signal to the Blower/VFD  
assembly low voltage 5 pin socket.  
The PWM signal is a digital instruction sent to the VFD instructing it to start, stop, and control  
blower speed. The VFD powers the blower motor directly. The VFD also varies the  
frequency (Hz) of the power it sends to the blower motor which in turn controls blower  
speed. Higher frequency = faster blower speed, lower frequency = slower blower speed.  
Service Notes - Blower  
The PWM signal plug MUST remain plugged in to the 5 pin socket on the blower assembly  
at all times. Removing this plug will cause the blower to accelerate and the Btu/hr input of  
the water heater to increase to a much higher rate. This may cause damage to the water  
heater.  
Blower Housing  
Low Voltage PWM 5 Pin Socket  
Blower Motor / VFD Assembly  
High Voltage 120 VAC 3 Pin Socket  
Technical Literature Department  
10 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
BURNER  
The images below show a complete blower/burner assembly removed along with a top view  
of the water heater with the blower removed.  
Service Notes - Burner (Flame Sensor)  
The burner installed in the water heater is a radial fire burner. Radial fire burners can trap  
debris that enter the blower. Be sure to thoroughly clean the edges of intake air pipe  
sections after cutting during the installation. If this is not done plastic shavings can collect  
inside the burner and lead to rough operation and/or ignition failure.  
The burner should be removed and inspected whenever servicing for rough operation or  
ignition failure problems. Burner removal requires removal of the blower. Blower removal  
requires 8-10” long T handle 1/8” hex (allen) wrench.  
The flame sensor will accumulate corrosion (rust etc) over time. This will reduce flame  
sensing current. This is the most common cause of “Ignition Failure” lock outs. The flame  
sensor should cleaned when servicing due to ignition failure and as a routine maintenance  
procedure. Fine grade steel wool is recommended for cleaning the flame sensor; do not use  
coarse abrasives such as sand paper.  
Blower Adapter  
Igniter  
Radial Fire Burner  
Blower VFD  
Assembly  
Flame Sensor  
Top View Water Heater - Blower Removed  
Burner Ground Wire  
Blower Adapter  
Burner View Port  
Blower removal  
requires 8 -10” long T  
handle 1/8” hex (allen)  
wrench.  
Burner must be grounded  
for flame sensing current to  
be established. See Service  
Technical Literature Department  
11 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
BURNER (CONT)  
Burner & Blower Removal  
The burner should be removed and inspected whenever service is being performed for  
rough operation or ignition failure. Radial fire burners like the one used on this water heater  
can trap debris, see Service Notes - Venting on page 7.  
The following images illustrate the burner removal procedure. Long T handle hex wrenches  
(8-10”) will save considerable time when removing/installing the burner & blower.  
BLOWER/BURNER REMOVAL PROCEDURE  
Blower Prover Sensing Tube  
1 Ensure power to the water heater is turned off.  
2 The blower assembly must be removed first.  
3 Disconnect the two wiring plugs from the blower  
assembly sockets (see Service Notes - Blower  
page 10).  
4 Disconnect the Blower Prover air pressure switch  
sensing tube.  
5 Remove 4 blower flange mounting screws -  
1/8” hex. Using long T handle hex wrench will  
save considerable time.Do not over tighten when  
Blower Flange  
1/8” Hex Machine Screws  
reinstalling - torque should not exceed 40 inch  
lbs.  
6 Remove the blower assembly from the blower  
adapter.  
7 Remove the blower flange gasket. Gasket may be  
reused if not damaged or showing signs of  
excessive wear.  
8 Remove the flame sensor - 1 Phillips head screw.  
CONTINUED ON NEXT PAGE  
Blower Flange  
Flame Sensor  
Blower Flange Gasket  
Blower Adapter  
Technical Literature Department  
12 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
BURNER (CONT)  
Burner/Blower Removal (cont)  
BLOWER/BURNER REMOVAL PROCEDURE  
(CONT)  
9 Remove 4 blower adapter 1/4” hex machine  
screws. Do not over tighten when reinstalling -  
torque should not exceed 40 inch lbs.  
1/4” Hex Machine Screws  
10 Remove the blower adapter.  
11 Be extremely careful when handling the Sight  
Glass inside the Burner View Port (page 11) this  
can easily be dropped and lost - and the water  
heater must have the sight glass in place to  
operate safely.  
12 Remove the hot surface igniter - 2 Phillips head  
screws.  
13 Remove the blower adapter gasket. Gasket may  
be reused if not damaged or showing signs of  
excessive wear.  
Blower Adapter  
14 Lift the burner up and out.  
Blower Adapter Gasket  
Sight Glass inside  
Burner View Port  
Burner  
Hot Surface Igniter  
Service Notes - Blower Flange & Blower Adapter Gaskets.  
Whenever the blower or burner is removed for service DO NOT overtighten the machine  
screws that hold the blower flange to the blower adapter (page 12) or the blower adapter to  
the water heater tank (above). Torque on these screws should not exceed 40 inch lbs.  
If these mounting screws are overtightened the gaskets will be squeezed and deformed  
from their natural shape. This can partially block the flow of the fuel air mixture and cause  
rough starting, rough operation and ignition failure.  
If these gaskets are deformed from overtightening the mounting screws it can also lead to  
gasket leakage. Hot flue gases leaking from these points can burn up wiring, igniters, and  
other components.  
Technical Literature Department  
13 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
VENTURI  
A Venturi is connected to the inlet of the blower. All combustion air flows through the Venturi.  
The outlet of the 24 VAC gas valve connects directly to the side of the Venturi. Fuel gas  
flows from the outlet of the gas valve into the side of the Venturi directly.  
Inside the Venturi there is a cone shaped restrictor that constricts the air passage to the  
blower inlet. As air enters the constriction point it’s velocity increases. A pressure drop  
occurs at this point and creates a negative pressure in the cavity between the cone shaped  
restrictor and the Venturi housing. This negative pressure “pulls” gas from the outlet of the  
gas valve into the blower where it is mixed with combustion air and then supplied to the  
burner. See the images below.  
24 VAC Gas Valve  
Blower  
Gas Inlet  
Venturi Inlet  
Venturi  
Negative Pressure  
Blower  
Velocity Increases  
At Constriction Point  
Pressure Drops  
Combustion Air  
Negative Pressure  
Burner  
Supply Gas  
Technical Literature Department  
14 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
GAS VALVE  
The outlet of the gas valve is connected by flange directly to the side of the Venturi (page  
14). There is no manifold gas line on the water heater. A gas orifice with gasket is fitted into  
the gas valve’s outlet flange. See the images below.  
Gas Valve Removal  
The gas valve must be removed to inspect the gas orifice. There are 3 - 5/32” hex head  
screws that secure the gas valve to the Venturi. Long T handle hex wrenches (8-10”) will  
save considerable time when removing/installing the gas valve, blower and burner.  
GAS VALVE REMOVAL PROCEDURE  
5/32” hex wrench  
24 VAC Gas Valve  
1 Ensure power to the water heater is turned off.  
2 Turn off the supply gas shut off valve.  
3 Disconnect supply gas line to water heater.  
4 Remove 3 gas valve mounting screws - 5/32” hex  
head machine screws. Support gas valve body  
when removing last screw. Long T handle hex  
wrenches (8-10”) will save considerable time  
when removing/installing the gas valve.  
5 Carefully lift gas valve body off of flange  
connection on Venturi.  
Venturi  
6 Gas orifice and gasket are now accessible.  
Gas Orifice  
& Gasket  
24 VAC Gas Valve  
Venturi  
Natural Gas Orifice  
Propane Gas Orifice 0.162”  
0.191”  
Gas Orifice  
& Gasket  
Gasket  
Orifice  
Technical Literature Department  
15 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
GAS PRESSURE TESTING  
The water heater covered in this Service Manual is rated at 100,000 Btu/hr input. It is  
certified for elevations up to 10,100 feet (3079 meters) without adjustment. Call the technical  
support phone number shown on the water heater labeling before operating the water  
heater at higher elevations.  
Service Notes - Checking Gas Pressures  
Manifold and supply gas pressure can be measured at two test ports on the water heater’s  
gas valve. The manifold test port is closest to the blower housing and the supply test port is  
furthest. The valve in each test port is opened/closed with a small slotted screwdriver.  
Manifold gas pressure will run at 0.00” W.C. or lower, in a negative pressure, depending on  
the operating state or mode the control system is currently in (see Venturi on page 14).  
Manifold gas pressure will be considerably lower, -6.50” to -7.50” W.C. during the pre/post  
purge modes when the blower is running and the gas valve is closed. When the gas valve  
opens (energized) gas entering the Venturi will cause a rise in manifold gas pressure.  
Manifold gas pressure will vary depending on vent/intake air pipe lengths. Manifold gas  
pressure will typically be 0.00” W.C. to +0.05” W.C. during the heating mode.  
There may also be a drop in supply gas pressure noticed when the water heater’s gas valve  
opens. Seeing a rise in manifold pressure and a corresponding drop in supply gas pressure  
confirms the gas valve is opening and gas is flowing to the burner. The procedure for  
checking manifold and supply gas pressures is shown in the illustrations that follow.  
CHECKING GAS PRESSURES  
1 Ensure power to the water heater is turned off.  
2 Turn off the supply gas shut off valve.  
3 Open the manifold and supply gas pressure test  
ports on the gas valve. Turn the needle valve  
slotted heads 1/2 to 1 full turn counterclockwise  
with a small slotted screwdriver.  
4 Attach sensing tube from 2 digital manometers  
(see tool requirements page 3) to each gas  
Manifold Gas  
Test Port  
Supply Gas  
Test Port  
pressure test port on the gas valve as shown.  
CONTINUED ON NEXT PAGE  
Sensing Tubes  
From Manometers  
Turn test port needle valves counter-clockwise  
to open and clockwise to close. Always close  
test ports when finished and check for leaks  
Supply Gas  
Test Port  
Manifold Gas  
Test Port  
Technical Literature Department  
16 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
GAS PRESSURES (CONT)  
CHECKING GAS PRESSURES (CONT)  
5 Open the supply gas shut off valve - restore  
power - start a heating cycle.  
Typical manifold and supply gas pressures during:  
1 Standby Mode  
2 Pre-Purge Mode  
3 Heating Mode  
6 The rise in manifold pressure and corresponding  
drop in supply gas pressure confirms the water  
heater’s gas valve is opening and gas is flowing  
to the burner.  
7 Record the supply and manifold gas pressures  
with the water heater firing.  
1 BLOWER OFF / GAS VALVE OFF  
Manifold 0.00” W.C. Supply +9.70” W.C.  
8 Supply gas pressure should not drop below  
minimum given in Table 2 below.  
9 Manifold gas pressure should be within the range  
shown in Table 2 below.  
10 Look through the burner view port (page 11)  
burner flame should be blue.  
11 Shut off power and gas supply - disconnect  
manometers - close test port needle valves.  
Manifold  
Gas  
Supply  
Gas  
12 Restore power and gas supply. Check for gas  
2 BLOWER ON / GAS VALVE OFF  
3 BLOWER ON / GAS VALVE ON  
Manifold -6.86” W.C. Supply +9.70” W.C.  
Manifold +0.05” W.C. Supply +7.04” W.C.  
Manifold  
Gas  
Supply  
Gas  
Manifold  
Gas  
Supply  
Gas  
Service Notes - Gas Pressure Adjustment  
Manifold gas pressure is factory set and should not be adjusted in the field. If manifold gas  
pressure differs greatly from the pressures in Table 2 consider the calibration of the  
manometer being used - try a different manometer. Call the technical support phone number  
on the water heater label for further assistance if pressures are considerably different.  
Table 2 - Gas Pressures  
MINIMUM SUPPLY  
FUEL TYPE  
MAXIMUM SUPPLY  
MANIFOLD  
0.00” to +0.05” W.C.  
(0.00 to +0.012 kPa)  
Natural Gas  
3.5” W.C. (0.87 kPa)  
14.0” W.C. (3.48 kPa)  
0.00” to +0.05” W.C.  
(0.00 to +0.012 kPa)  
Propane Gas  
8.0” W.C. (1.99 kPa)  
14.0” W.C. (3.48 kPa)  
†. Minimum supply gas pressures must be maintained under both load and no load conditions.  
Technical Literature Department  
17 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
AIR PRESSURE SWITCHES  
Air pressure switch technical bulletins TB-A023-06 and TB-S023-06 explain air pressure  
switch construction and test procedures in detail. These technical bulletins are available on  
the manufacturers web site or by calling the technical support phone number shown on the  
water heater labeling. Construction and types of air pressure switches used on the water  
heater covered in this Service Manual are shown below.  
Construction  
Normal State  
Activated State  
(open switch contacts)  
(closed switch contacts)  
Switch Contacts  
Wiring Terminals  
Internal Linkage  
Vent Port  
Flexible Diaphragm  
Sensing Port  
Application & Type  
Normal State  
Activated State  
Blower Prover  
Air Pressure Switch  
Normally open contacts,  
close on a rise in pressure.  
Blocked Intake  
Air Pressure Switch  
Normally closed contacts,  
open on a fall in pressure.  
Blocked Exhaust  
Air Pressure Switch  
Normally closed contacts,  
open on a rise in pressure.  
Technical Literature Department  
18 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
AIR PRESSURE SWITCHES (CONT)  
The water heater covered in this Service Manual is factory equipped with three air pressure  
switches. These switches are used to provide verification or prove electrically that the  
blower is running and that the vent and intake air pipes are not blocked or restricted. The  
switches are located on the top of the water heater as shown in the illustration below.  
TOP VIEW  
FRONT  
BLOWER PROVER SWITCH  
normally open contacts - close on a rise in pressure  
BLOCKED INTAKE SWITCH  
normally closed contacts - open on a fall in pressure  
BLOCKED EXHAUST SWITCH  
normally closed contacts - open on a rise in pressure  
All switches have SPST(single pole single throw) contacts.  
These switches monitor air pressure through plastic sensing tubes from three different  
sensing ports on the water heater. The Blower Prover switch monitors pressure from the  
blower’s outlet flange. The Blocked Intake switch monitors pressure from the blower’s intake  
air connection fitting. The Blocked Exhaust switch monitors pressure from the exhaust/vent  
connection elbow on the bottom of the water heater. See the images below.  
Blower Prover Switch  
Blocked Intake Switch  
Blocked Exhaust Switch  
Blocked Exhaust Switch Sensing Port  
Technical Literature Department  
19 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
AIR PRESSURE SWITCH OPERATION  
The control system monitors the “state” of the air pressure switches individually through  
three separate circuits (see wiring on diagram page 39). The “state” of the switch refers to  
whether the switch contacts are open or closed. See the construction drawings on page 18.  
Before each call for heat begins, before the blower starts, the control system performs a  
diagnostic test. During this test the control system checks the air pressure switches. The  
switches must be in their correct normal state at this point.  
The Blower Prover is a normally open switch and the Blocked Intake/Exhaust switches are  
normally closed. If the Blower Prover is not verified open or the Blocked Intake/Exhaust  
switches are not verified closed during this test; the control system would lock out and  
display a fault message indicating which pressure switch had caused the fault condition. IE:  
“Blower Prover Failure.”  
After the blower starts the Blower Prover switch contacts must activate (close) for the  
water heater to continue in the Sequence of Operation (see page 40). If the Blower Prover  
switch contacts do not close after the blower starts, the control system would lock out and  
display a fault message; IE: “Blower Prover Open.”  
Normal State  
Activated State  
(contacts closed - after blower starts)  
Blower Prover  
Air Pressure Switch  
(contacts open - before blower starts)  
Normally open contacts,  
close on a rise in pressure.  
The Blocked Intake and Blocked Exhaust switches must remain closed at all times. If the  
control system senses the contacts of either of these switches are open it will lock out and  
display a fault message; IE “Blocked Inlet” or “Blocked Exhaust Vent”  
Technical Literature Department  
20 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
AIR PRESSURE SWITCH TESTING  
Air pressure switch testing involves three procedures:  
• Normal State Test  
• Operational State Test  
• Pressure Test  
Normal State Test  
Turn off power and disconnect the wires to the pressure switches. Wrap electrical tape  
around the wire ends to prevent shorts. A continuity test is performed, using an ohm meter,  
between the wiring terminals of the switch. The Blower Prover switch has normally open  
contacts. The Blocked Intake and Blocked Exhaust switches have normally closed contacts.  
If this test confirms the Blower Prover switch contacts are open and the Blocked Intake/  
Exhaust switch contacts are closed - the switches have passed the test. If test results  
indicate the Blower Prover switch contacts are closed - the switch must be replaced. If either  
the Blocked Intake or Exhaust switch contacts are open - the switch must be replaced.  
Operational State Test  
The operational test is also a continuity test performed with an ohm meter between the  
pressure switch wiring terminals. However, this test is performed while the blower is running  
during the pre-purge mode. Ensure the wires to the air pressure switches are disconnected  
and that electrical tape is wrapped around the wire ends to prevent shorts. Perform a  
continuity test between the wiring terminals on the air pressure switches with the blower  
running (water heater in pre-purge mode).  
During this test the normally open contacts of the Blower Prover switch should close. The  
Blower Prover switch “activates” (closes its contacts) during normal operation to verify or  
“prove” that the blower is running. If the contacts remain open during this test the third test,  
the pressure test, must be performed to determine if the pressure switch is defective. During  
this test the Blocked Intake and the Blocked Exhaust switch contacts should remain closed,  
if the contacts open during this test the third test, the pressure test, must be performed to  
determine if the pressure switch is defective.  
Technical Literature Department  
21 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
AIR PRESSURE SWITCH TESTING (CONT)  
Pressure Test  
The Pressure Test is necessary when the air pressure switch in question has passed the  
Normal State Test but failed the Operational State Test (see page 21). This test requires a  
digital manometer (see Tool Requirements page 3 and the images on page 23).  
Before performing this test examine the sensing tube connections on the water heater’s  
sensing ports and on the pressure switch (see page 19). Check for wear, leaks, kinks, or any  
kind of debris or condensate in the sensing tubes, repair/replace as necessary.  
To determine if an air pressure switch is operating properly you must know the “pressure  
activation” point for the switch and whether it activates on a rise or a fall in pressure. This  
information is provided in Table 3 below.  
Procedure: Disconnect the pressure sensing tube from the sensing port on the switch being  
tested, leave the other end connected. Connect a digital manometer to the sensing tube.  
Turn the power on and start a call for heat. When the blower comes up to full speed, record  
the pressure reading. Repeat this at all three air pressure switches as necessary. Compare  
the pressure readings taken to the activation pressures in Table 3 below. See page 23.  
Blower Prover Switch: If the pressure reading taken at the Blower Prover switch sensing  
tube is at or above the activation pressure shown in Table 3 and the switch contacts did not  
close in the Operational Test - the switch is defective and must be replaced. If the pressure  
reading taken does not reach or rise above the activation pressure in Table 3 the pressure  
switch IS NOT defective and should not be replaced - call the technical support phone  
number shown on the water heater labeling for assistance.  
Blocked Intake Switch: Note these are negative pressures. If the pressure reading taken at  
the Blocked Intake switch sensing tube does not reach or drop lower than the pressure  
shown in Table 3 and the switch contacts were opening during the Operational Test - the  
switch is defective and must be replaced. If the pressure reading taken reaches or drops  
lower than the pressure shown in Table 3 and the switch contacts were opening during the  
Operational Test - the switch IS NOT defective and should not be replaced. Check for  
restrictions, too many equivalent feet, or too many elbows in the intake air piping.  
Blocked Exhaust Switch: If the pressure reading taken at the Blocked Exhaust switch  
sensing tube does not reach or rise above the activation pressure given in Table 3 and the  
switch contacts were opening during the Operational Test - the switch is defective and must  
be replaced. If the pressure reading taken reaches or exceeds the pressure shown in Table  
3 and the switch contacts were opening during the Operational Test - the switch IS NOT  
defective and should not be replaced. Ensure the condensate tube connected to the exhaust  
elbow on the water heater is not clogged and is draining freely. Check for restrictions, too  
many equivalent feet, or too many elbows in the vent pipe.  
Table 3 - Air Pressure Switch Parameters  
BLOWER PROVER  
Normally Open Contacts  
Close on a rise in pressure  
BLOCKED INTAKE  
Normally Closed Contacts  
Open on a fall in pressure  
BLOCKED EXHAUST  
Normally Closed Contacts  
Open on a rise in pressure  
+1.00” W.C.(± 0.05” W.C)  
-2.00” W.C. (± 0.05” W.C)  
+2.00” W.C. (+0.05” W.C)  
Technical Literature Department  
22 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
AIR PRESSURE SWITCH TESTING (CONT)  
BLOWER PROVER SWITCH  
PRESSURE TEST  
BLOCKED INTAKE SWITCH  
PRESSURE TEST  
BLOCKED EXHAUST SWITCH  
PRESSURE TEST  
Technical Literature Department  
23 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
FLAME SENSING TEST  
To prove burner flame during ignition the control system monitors flame sensing current  
through the flame sensor. It is a DC micro amp (µA) current that flows through the flame  
sensor. The control system must sense a minimum level of current to “prove” flame. The  
minimum flame sensing current is approximately 1.0 µA. If flame sensing current remains  
lower than 1.0 µA the control system would lock out after 3 failed trials for ignition and  
display “Ignition Failure.” Flame sensing current typically runs much higher than minimum  
when the flame sensor is clean; between 8.0 µA to 12.0 µA.  
The most common cause of “Ignition Failure” lock out is a contaminated or corroded flame  
sensor. Rust/corrosion will accumulate on the flame sensor over time. Cleaning the flame  
sensor is a common maintenance procedure that should be performed anytime the water  
heater is being serviced. Clean the flame sensor with ultra fine steel wool or an ultra fine  
Scotch-Brite pad. DO NOT use a coarse abrasive material such as sand paper.  
The burner not being grounded can also cause ignition failure - see page 8.  
Measuring Flame Sensing Current  
Measuring flame sensing current requires a multi meter with DC micro amp functionality.  
See tool requirements on page 3. The meter’s selector is set to DC micro amps. The flame  
sensor wire is disconnected and one of the meter probes is inserted in the wire connector.  
The other meter probe touches the flame sensor terminal. There must be constant contact at  
both points to measure current. Start the water heater - when ignition occurs the meter will  
read flame sensing current in real time. See the image below.  
Flame Sensor  
If flame sensing current is lower than 8.0 µA, remove the flame sensor and clean it with ultra  
fine steel wool. Perform a close visual inspection of the flame sensor. If the sensor appears  
to be damaged or shows signs of excessive wear, replace the flame sensor. If the ceramic  
insulator on the flame sensor has any visible cracks, replace the flame sensor. When  
finished inspecting and cleaning the flame sensor, reinstall it and measure flame sensing  
current again.  
Technical Literature Department  
24 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
IGNITER CURRENT TEST  
The water heater covered by this Service Manual uses a hot surface igniter (HSI). The  
control system CCB (page 35) powers the igniter (120 VAC) and monitors igniter current (AC  
amps). The more current flowing through the igniter; the hotter the igniter will be. The hotter  
the igniter is; the more likely it will be to ignite the burner.  
The normal resistance of the hot surface igniter (when new) will be between 40-70 ohms at  
77°F (25°C). Hot surface igniters are wearing parts; with age and wear the resistance  
(ohms) of the igniter will increase. As the resistance (ohms) increases the current (AC amps)  
will decrease. More importantly the heat generated by the igniter will decrease at lower amp  
draws. Over time hot surface Igniters will wear out and must be replaced as they will no  
longer generate enough heat to cause ignition.  
The control system is programmed to verify a minimum of 2.0 AC amps before it will initiate  
a trial for ignition by energizing the gas valve (see Sequence of Operation page 40). If the  
control system senses less than 2.0 igniter amps during the warm up period the control  
system will lock out and display the “Low Igniter Current” fault message.  
Igniter current can be measured at CCB J5 socket or at the igniter. Clip the amp meter  
around one of the two igniter wires to measure igniter current. See the images below.  
Service Notes - Hot Surface Igniters  
It is a good practice to check igniter current when any service or maintenance is being  
performed. Igniter current will be 4.0 to 5.0 AC amps when the igniter is new. Because hot  
surface igniters are wearing parts they can cause intermittent ignition failure with age and  
wear. Replacing the igniter when current is lower than 3.0 AC amps is a good preventive  
maintenance procedure that can prevent loss of hot water and customer dissatisfaction.  
Technical Literature Department  
25 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
CONTROL SYSTEM  
INTRODUCTION  
This portion of the service manual will cover the control system. The control system includes  
several components: a UIM (User Interface Module), a CCB (Central Control Board), and an  
Overlay/Button Pad. More information on these components will be given in the pages that  
follow.  
Control System Features  
Advanced Diagnostics: Plain english text based diagnostic information (fault messages)  
on board to help equipment owners accurately describe the reason for a given lock out  
condition and service technicians quickly and accurately service the water heater.  
Fault History Screen: Will retain a 9 event history of fault messages with a time stamp.  
This will help diagnose load and/or environmental conditions that may be contributing to a  
problem with operation or a lock-out.  
Fault Occurrence Screen: Will keep a running total of how many times each lock out/fault  
condition has occurred since the water heater was first installed. This is valuable information  
for a service technician when trying to determine root causes for service problems.  
Help Screens: Text based operational information to help the user understand how to  
change settings, navigate the menu screens and what the various icons and displayed items  
mean.  
EMI / RFI Filtering: Built into all control system circuit boards. (EMI = Electro Magnetic  
Interference, RFI = Radio Frequency Interference) Helps prevent or eliminate erratic  
operation caused by EMI/RFI.  
Technical Literature Department  
26 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
UIM  
The UIM (User Interface Module) is the display on the front of the water heater. The UIM’s  
major components include a Circuit Board with LCD display and a Button Pad Overlay which  
contains the five user input buttons.  
Service Notes - Button Pad Ribbon Cable  
The Ribbon Cable that connects the Button Pad Overlay to the UIM Circuit Board must be  
plugged in exactly as shown in the images below; with the metal crimp connections visible  
on the plug end and the UIM Circuit Board back facing out. There are six pins on this Ribbon  
cable socket, Ensure all six pins are inserted into the Ribbon Cable plug whenever removing  
or installing the UIM or Button Pad Overlay.  
Failure to connect this Ribbon cable exactly as shown when servicing will render the User  
Input Buttons inoperable. This should be checked whenever the nature of the service  
complaint is an inoperable or unresponsive controller or UIM.  
UIM Circuit Board Back  
Button Pad Overlay  
J3 Socket - Button Pad  
Communication  
J2 Socket - CCB  
Communication  
Ribbon Cable To  
Button Pad  
Ensure Ribbon Cable Plug  
is inserted exactly as shown.  
LCD  
Screen  
UIM Circuit Board Front  
Technical Literature Department  
27 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
UIM (CONT)  
User input buttons on the UIM include an Up, a Down, and three Operational buttons.  
The Up and Down buttons are used to navigate through the various menus and screens  
displayed and to adjust or change user settings such as the Operating Set Point.  
The three Operational buttons are multifunctional. Their function is defined by the text that  
appears above each button on the UIM display. The Operational button’s function will  
change depending on what menu or screen is currently displayed.  
Commercial & Residential Product Differences  
The illustration below shows the control system’s “Desktop” screen. This is the control  
system’s default screen. If there are no active fault messages and no user input for  
approximately 10 minutes the control system will return to this screen automatically.  
The water heater covered by this Service Manual is available in commercial and residential  
models. The “Tank Temperature” data shown on the desktop screen below will not be visible  
on residential models. Tank Temperature will be displayed on the commercial models only.  
The maximum Operating Set Point for a residential model will be 160°F (71°C). Maximum  
Operating Set Point on commercial models will be 180°F (82°C).  
UIM - User Interface Module Display  
Up & Down  
Buttons  
Operational  
Buttons  
Discreet Menu - Contact Information  
While viewing the Desktop screen (above). Press and hold down the middle Operational  
button for 30 seconds and then release it. This will launch a discreet menu with a provision  
for entering personalized contact information. Installing contractors and/or service  
technicians can enter their company name and telephone number. This contact information  
would be displayed with all fault messages whenever the control system was in a lock out  
condition.  
Technical Literature Department  
28 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
UIM (CONT)  
Desktop Screen  
The Desktop screen is the default screen. If there are no active fault messages the display  
will return to this screen with no user input after approximately 10 minutes. The Desktop  
screen displays text and icons that provide operational and diagnostic information.  
The first line of text on the Desktop screen is the temperature of the water inside the tank.  
Tank Temperature data will only be visible on commercial models.  
The second line of text on the Desktop screen is the Operating Set Point. The Operating  
Set Point is a user setting that can be adjusted in the Temperatures Menu. The Operating  
Set Point is the temperature at which the water heater will maintain the water inside the tank.  
The third line of text on the Desktop screen shows the current Status of the control system.  
The current Operational State of the water heater’s control system is displayed in real time.  
Operational States are explained on page 31.  
CONTROL SYSTEM DESKTOP SCREEN  
Discreet Menu - Contact Information  
While viewing the Desktop screen  
(left). Press and hold down the middle  
Operational button for 30 seconds  
then release it. This will launch a  
discreet menu that contains a  
provision for adding personalized  
contact information that will be  
displayed on all fault message  
screens. The installing contractor or  
service agent can enter their  
company name and phone number to  
help the home or business owner  
contact them for service.  
Note: Tank Temperature will only be visible on commercial models.  
Service Note - Sequence of Operation Display  
The Desktop screen displays the Sequence of Operation in real time using animated “Status  
Icons.” This is valuable information when servicing the water heater that can help correctly  
diagnose service problems more quickly.  
Review the Sequence of Operation on page 40 and the Status Icons explanation in Table 4  
on page 30. Learn to use this visual display of the Sequence of Operation when  
troubleshooting the water heater. IE: if the Igniter Status Icon comes on but the Check Mark  
Status Icon does not appear next to it within 5 seconds the control system has not sensed  
minimum igniter current of 2.0 AC amps.  
Technical Literature Department  
29 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
UIM (CONT)  
Table 4 - Status Icons  
STATUS ICON  
DESCRIPTION  
The temperature of the water in the tank has fallen and the water heater will now initialize  
a new heating cycle.  
The temperature of the water in the tank has reached the Operating Set Point.  
The control is unable to initiate any further heating cycles. This is usually caused by a  
fault condition detected by the control.  
The blower is being energized.  
The Blower Prover Air Pressure Switch contacts have closed. Check Mark Icon is visual  
confirmation of contact closure.  
The igniter has been energized.  
The igniter has been energized and the control system has sensed minimum (2.0 AC  
amps).Check Mark Icon is visual confirmation of minimum igniter current.  
The gas valve has been energized.  
The control system has sensed minimum (1.0 µA) DC micro amps.Flame Icon is visual  
confirmation of minimum flame sensing current.  
The control has detected a fault condition.  
The control has detected a warning condition. These conditions will not cause the control  
system to lock out (discontinue water heater operation), but does merit attention.  
Technical Literature Department  
30 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
UIM (CONT)  
Table 5 - Operational States (Modes)  
STATE  
DESCRIPTION  
The water heater is not in an active heating cycle. This usually means the temperature  
in the tank has reached Operating Set Point and has not dropped low enough to initiate  
a call for heat.  
Standby  
Input Verification  
Pre-Purge  
The control system is waiting for specific conditions to occur (primarily pressure switch  
normal state verification - see page 20) before the unit can continue in the Sequence of  
Operation.  
The blower has been energized - the control system is purging out any excess gas or  
left over products of combustion from the heat exchanger at the beginning of each  
heating cycle.  
The igniter has been energized and is currently warming up to ensure proper ignition -  
typically last 17-20 seconds.  
Igniter Warmup  
The control system is allowing for a steady burner flame to be established. Duration of  
this and the Ignition Verification state is typically 4-6 seconds.  
Ignition Activation  
Ignition Verification Assurance of proper flame sense is being determined.  
After a failed trial for ignition the control system is purging out any excess gas or left  
over products of combustion from the heat exchanger before another trail for ignition.  
Inter-Purge  
Heating  
Burner flame has been properly established - minimum flame sensing current has  
been verified by the control system - water in the tank is being heated.  
The control system is purging out any excess gas or left over products of combustion  
from the heat exchanger after a successful heating cycle.  
Post-Purge  
The control system has detected a fault and declared a fault condition. The control  
system is locked out. A fault message is displayed on the UIM (page 27). The problem  
that caused the lock out must be corrected before the water heater can resume a  
heating cycle.  
Fault  
Technical Literature Department  
31 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
OPERATING SET POINT ADJUSTMENT  
When the temperature sensed by the control system at the Temperature Probe (top of the  
water heater) reaches the Operating Set Point the control system will end the heating cycle.  
A call for heat will be activated again when the tank temperature drops below the Operating  
Set Point minus the Differential setting plus one degree.  
Example: Operating Set Point is 120°, Differential setting is 2° (factory default). A call for  
heat will be activated when tank temperature drops to 117°. 120 - (2+1) = 117.  
The Operating Set Point and the Differential setting is adjusted or changed in the  
Temperatures menu. The following illustrations and instructions will explain how to adjust  
these user settings and navigate the control system menus.  
ACTION  
DISPLAY  
From the desktop screen, press MENU.  
NOTE: Notice how the text on the UIM display above the  
Operational Buttons changes as you navigate through  
the various menus and screens.  
With Temperatures selected (highlighted in black) in the  
Main Menu, press the Operational Button underneath  
“SELECT” to enter the Temperatures Menu.  
If Temperatures is not selected use the Up and Down  
buttons to select this menu item.  
With the Operating Set Point selected in the  
Temperatures Menu, press the Operational Button  
underneath “CHANGE” to activate the adjustment mode  
for this menu item.  
NOTE: The Upper Probe Offset can be used to override  
the control system’s calculated tank temperature by 5°  
above or below current reading. Adjustable range is -5°F  
to +5°F.  
Press the UP and DOWN buttons to adjust the Operating  
Set Point to the desired setting.  
Press the Operational Button underneath “UPDATE” to  
confirm the new setting or “CANCEL” to discard the new  
setting and retain the previous setting.  
NOTE: This same procedure can also be used to adjust  
the Differential and the Upper Probe Offset user settings.  
Technical Literature Department  
32 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
CONTROL SYSTEM MENUS  
Desktop: This is the default screen for the control system. If there are no active faults or  
warnings the display will return to this screen with no user input after approximately 10  
minutes. Information/settings available:  
Tank Temperature (commercial models only)  
• Operating Set Point  
• Operating States  
• Status (Graphical) Icons  
Temperatures: This menu contains the user settings and temperature information.  
Information/settings available:  
• Operating Set Point - adjustable (90-180°F commercial models, 90-160°F residential models)  
• Differential - adjustable (2-20° factory setting is 2°)  
• Upper Temperature (commercial models only)  
• (Heater Regulated to Upper) configuration information  
• Upper Probe Offset - adjustable -5°F to +5°F. overrides the perceived tank temp by this setting.  
Heater Status: This menu shows the current operating state of the water heater, Blower,  
Igniter, Gas Valve and the state of the contacts (open/closed) for the air pressure switches  
and the ECO along with the state of the CCB S1 dip switches. Information shown in this  
menu is in real time. Information/settings available:  
• Status - operating state (see page 31)  
• ECO Contact - open or closed  
• Blocked Inlet PS - air pressure switch contacts open or closed  
• Blocked Outlet PS - air pressure switch contacts open or closed  
• Blower Prover PS - air pressure switch contacts open or closed  
• Blower Low On - blower is running at low speed yes/no (N/A models equipped w/ 2 speed blowers)  
• Blower High On - blower is running at high speed yes/no  
• Igniter On - is currently energized yes/no (yes = energized; no = not energized)  
• Igniter Current - igniter current is above minimum 2.0 AC amps yes/no  
• Gas Valve On - is currently energized yes/no (yes = energized; no = not energized)  
• Flame Detected - flame sensing current is above minimum 1.0 µA yes/no  
• External Input Enabled - external control enable/disable circuit activated yes/no  
• Ignition Trials - maximum number of retries for ignition 1 or 3 S1 dip switch setting (see page 38)  
Display Settings: This menu contains user settings for the UIM display contrast, back light  
and temperature units. Information/settings available:  
Temperature Units - adjustable Celsius or or Fahrenheit  
• Backlight Delay - adjustable - seconds to continuous  
• Contrast - adjustable  
Technical Literature Department  
33 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
CONTROL SYSTEM MENUS (CONT)  
Heater Information: This menu contains historic operational and configuration information.  
Information/settings available:  
• Elapsed Time - hrs & mins - how long the water heater has been powered on  
• Burner On Time - hrs & mins - burner run time cumulative  
• Cycle Count - total number of heating cycles  
• Ignition Failure Count - total number of ignition failures  
• Flame Loss Count - total number of lost flame events  
• CCB Version - software revision of the control systems CCB circuit board  
• UIM Version -software revision of the control systems UIM circuit board  
• Configuration - manufacturer and model number configuration  
Current Fault: This menu will only contain information when the water heater is in a lock out  
condition. It will contain the current fault message/condition.  
Fault History: This menu contains a history of fault occurrences with a time stamp. The  
time stamp associated with the fault condition can be subtracted from the “Elapsed Time” in  
the “Heater Information” menu to determine when or how long ago the given event occurred.  
The control system will keep the last 9 events in history. When a new event occurs the oldest  
event will be lost.  
Fault Occurrence: This menu contains a running total (cumulative) for all fault conditions  
declared by the control system. This information can be useful in determining root causes for  
service problems. Information/settings available:  
• Ignition Failure  
• ECO  
• Blocked Inlet  
• Blocked Outlet  
• Thermostat Input 4  
• Blower Prover  
• Flame Detect Error  
• Flame Probe  
• External Output Relay  
• Gas Valve  
• Igniter Fail  
• Power Supply Fail  
• CCB Hardware  
• Model Faults  
• CCB Communications  
Restore Factory Defaults: This menu allows the end user to restore all settings to their  
factory defaults.  
Help Menu: This menu contains information to help users use the control system, menu  
items include; Operating Instructions, Status Icon Legend, Operating States, Adjust  
Operating Set Point, Change Display Units, Restore Factory Defaults, Contact Information.  
Technical Literature Department  
34 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
CCB  
The CCB circuit board is the main control. All instructions for ignition and temperature  
control originate from this circuit board. Diagnostic and operational messages are generated  
by the CCB and sent to the UIM (page 27). Most of the water heater’s components, such as  
the igniter, blower, gas valve, and temperature probe are directly connected to one of the  
CCB’s socket connectors.  
Service Notes - CCB Replacement  
If the CCB fails and needs to be replaced the replacement board will be shipped with the  
gray plastic enclosure and a new 24 VAC transformer. There is no need to remove the circuit  
board from the enclosure when the CCB is being replaced.  
Enclosure With Front Removed  
CCB Circuit Board  
Transformer  
120V x 24V  
50 VA  
Technical Literature Department  
35 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
CCB (CONT)  
Socket Identification  
All wiring connections and sockets will be identified in the following pages. The  
Troubleshooting section of this Service Manual will refer back to this illustration and  
information.  
1
2
3
4
5
1
2
3
4
1
2
4
1
2
J4  
J5  
J3  
J2  
J1  
15  
14  
13  
12  
11  
10  
9
8
7
6
5
4
3
2
1
S1  
J6  
4
3
2
1
J7  
J9  
J13  
J11  
1
2
3
4
5
6
7
8
J10  
J16  
1
3
J15  
1
2
4
2
Technical Literature Department  
36 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
CCB (CONT)  
J1 Socket - Transformer  
PIN #  
DESCRIPTION  
1
2
3
4
5
120 VAC hot to transformer  
Not used  
120 VAC neutral to transformer  
24 VAC out from transformer  
24 VAC out from transformer  
J2 Socket - 120 VAC To Blower  
PIN #  
DESCRIPTION  
DESCRIPTION  
1
2
3
4
120 VAC hot to blower  
120 VAC neutral to blower  
Not used  
Not used  
J3 Socket - 120 VAC Power Supply  
PIN #  
1
2
3
120 VAC hot  
Earth Ground  
120 VAC neutral  
J4 Flame Sensor - Male Spade Connector  
J5 Socket - Igniter 120 VAC HSI (hot surface igniter - Silicon Carbide)  
PIN #  
DESCRIPTION  
1
2
120 VAC hot  
120 VAC neutral  
J6 Socket - Gas Valve, Pressure Switches, Enable/Disable Circuit  
PIN #  
DESCRIPTION  
1
2
Not used  
Gas valve - 24 VAC  
Not used  
3
4
Blocked Intake air pressure switch  
5
Blocked Exhaust air pressure switch  
Blower Prover air pressure switch  
Blower Prover air pressure switch  
Enable/disable external control circuit - jumper installed from factory  
Not used  
6
7
8
9
10  
11  
12  
13  
14  
15  
Blocked Exhaust air pressure switch  
Enable/disable external control circuit - jumper installed from factory  
Not used  
Not used  
Blocked Intake air pressure switch  
Gas valve - 24 VAC  
Technical Literature Department  
37 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
CCB (CONT)  
J7 Socket - Temperature Probe/ECO (immersion probe - top of the water heater)  
PIN #  
DESCRIPTION  
ECO (energy cut out) 24 VAC out (red wire)  
1
2
3
4
Upper temperature probe (thermistor) +5.0 VDC (black wire)  
Upper temperature probe (thermistor) -5.0 VDC (black wire)  
ECO (energy cut out) 24 VAC return (red wire)  
J9 Port - Communication Port - Not Used  
J10 Socket - Not Used  
J11 Port - Communication Port - Not Used  
J13 Socket - Blower Speed Control (VFD)  
PIN #  
DESCRIPTION  
1
2
3
4
5
6
7
8
Not used  
Not used  
To Blower low voltage PWM plug (see page 10) - pin #5 (white w/grn stripe)  
Not used  
Not used  
Not used  
To Blower low voltage PWM plug (see page 10) - pin #4 (white w/blue stripe)  
To Blower low voltage PWM plug (see page 10) - pin #1 (white w/brn stripe)  
J15 Socket - Not Used  
J16 Port - Communication Port - UIM Display (user interface module)  
S1 Dip Switch  
The S1 dip switches are configured from the factory and should not be changed. The  
illustration below shows the 4 dip switches with labeling. Dip switches are toggle type micro  
switches. Flipping a dip switch towards “Open” would be the same as “Off.” Flipping a dip  
switch the other way (towards the switch numbers) is the same as “On.”  
Dip switch #1 is used to configure the water heater to declare a fault condition and lock out  
after one or three failed trials for ignition. The factory setting is “on” for three trials.  
Dip switches #2 and #3 are used when this control system is installed on other products.  
The factory setting for these two dip switches is “on.”  
Dip switch #4 is a spare, configuration does not matter.  
3
1 Retry  
Retries  
Use Yes  
Type Tstat  
Spare  
No  
OFF  
OPEN  
ON  
CLOSED  
Ext  
Input  
Vent  
Spare  
Technical Literature Department  
38 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
WIRING DIAGRAM  
120 VAC 1Ø  
Power Supply  
Ground  
Neutral  
Hot  
Service Notes - Polarity & Ground  
This water heater is polarity and ground sensitive. The control system will lock out and  
display a fault message (“AC Reversed”) if the power supply polarity is reversed. Flame  
sensing current cannot be established if the burner is not grounded which will lead to ignition  
failure. See electrical requirements on page 8.  
Technical Literature Department  
39 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
SEQUENCE OF OPERATION  
Call for heat initiated  
Control System Declares  
Fault Condition - Locks Out  
One of the following  
Fault Messages Displayed:  
Air Pressure Switch Test Is Performed  
Blower Prover Switch is verified open  
NO  
Blocked Intake and Blocked Exhaust Switches are verified closed  
“Blower Prover Failure”  
“Blocked Inlet”  
“Blocked Exhaust Vent”  
YES  
Blower Motor is energized  
Pre-purge State  
Control System Declares  
Fault Condition - Locks Out  
“Blower Prover Open”  
Fault Message Displayed  
Blower Prover Switch is verified closed  
NO  
YES  
Igniter is energized for warm up period  
(approx 17 seconds)  
Control System Declares  
Fault Condition - Locks Out  
“Low Igniter Current”  
Control System (CCB) Verifies Igniter  
Current at 2.0 AC Amps Minimum  
NO  
Fault Message Displayed  
YES  
Gas Valve Is Energized  
Gas Flows To Burner  
Control System (CCB) Verifies Flame  
Sensing Current at 1.0µA DC Micro Amps Minimum  
YES  
NO  
Water Is Heated To  
Operating Set Point  
Gas Valve Is  
De-energized  
Gas Valve Is  
De-energized  
Inter-Purge State  
30 Sec Approx  
Post-Purge State  
30 Sec Approx  
Retries Up To  
3 Times  
Control System Declares  
Control System Goes Into  
Standby State/Mode  
Fault Condition - Locks Out  
“Ignition Failure”  
Fault Message Displayed  
Technical Literature Department  
40 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
TROUBLESHOOTING  
The control system performs exhaustive self diagnostics and displays detected fault  
conditions in plain english fault messages on the UIM (page 27) when there is a problem.  
When the control system declares a fault condition it will “lock out” and disable heating.  
Troubleshooting procedures for the most common error messages are covered in this  
manual. In the tables that follow the first column shows the fault message as displayed by  
the UIM along with an explanation. The second column details things to check or repair.  
Rough Starting - Rough Operation Note:  
If the water heater is experiencing rough operation or rough starting review the Service  
Notes - Blower Flange & Blower Adapter Gaskets on page 13. Remove and inspect the  
burner for debris or damage - see pages 11 - 13.  
Heater Status Menu  
This menu (page 33) shows the current operating state (energized/de-energized) of the  
Blower, Igniter and Gas Valve. The state (open/closed) of the contacts for the Blower Prover,  
Blocked Intake and Blocked Exhaust Switches. This information and more is shown in real  
time. Use this menu when troubleshooting the water heater to quickly and accurately  
diagnose operational problems.  
Things to check before servicing  
• Using the Instruction Manual that came with the water heater as reference, verify the  
water piping, gas line, venting and electrical have all been properly installed.  
• Ensure 120 VAC is supplied to the water heater and that the polarity is correct per the  
electrical requirements on page 8.  
• Ensure the water heater is properly grounded (page 8). Flame sensing current cannot be  
established unless the burner is grounded. This can cause ignition failure, after three  
failed trials for ignition the UIM would display the “Ignition Failure” fault message.  
• Ensure supply gas pressure is within the minimum and maximum requirements (page 17).  
Resetting the control system  
To reset the control system from a lock out condition; turn the power supply off for  
approximately 20 seconds and then back on. Keep in mind if the condition that caused the  
fault has not been corrected the control system will continue to lock out.  
Important Service Reminder  
When performing any troubleshooting step outlined in this Service Manual always consider  
the wiring and connectors between components. Perform a close visual inspection of all  
wiring and connectors to and from a given component before replacement. Ensure wires  
were stripped before being crimped in a wire connector, ensure wires are crimped tightly in  
their connectors, ensure connection pins in sockets and plugs are not damaged or worn,  
ensure plugs and sockets are mating properly and providing good contact.  
Failure to perform this critical step or failing to perform this step thoroughly often results in  
needless down time, unnecessary parts replacement, and customer dissatisfaction.  
Technical Literature Department  
41 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
CONTROL SYSTEM UNRESPONSIVE  
DISPLAYED MESSAGE  
CHECK/REPAIR  
CONDITION/INDICATES  
Ensure the on/off switch is on and working -  
replace switch if defective.  
UIM Display Is Blank  
On/Off is turned off  
Check communication cable connections at  
UIM’s J2 Socket (page 27) and the CCB’s J16  
Socket (page 36). Secure power and install a  
new comm cable. (standard Cat 5 network  
cable).  
Water heater is not plugged in  
Tripped Breaker - Blown Fuses  
120 VAC power supply problems  
24 VAC power supply problems  
Defective transformer  
Closely inspect communication ports on CCB  
and UIM for damage or wear.  
Wiring or plug/socket connection problems  
UIM communication cable problems  
Ensure 120 VAC power is properly connected in  
the junction box on the back of the water heater.  
Important Service Reminder:  
Ensure 120 VAC is supplied to CCB’s J3 Socket  
pins 1 & 3. Hot wire to pin 1, neutral wire to pin 3  
(page 36).  
When performing any troubleshooting steps outlined  
in this service manual always consider the wiring  
and connectors between components. Perform a  
close visual inspection of all wiring and connectors  
to a given component before replacement.  
Check 120 VAC to transformer primary winding  
at CCB’s J1 socket pins 1 & 3 (page 36) with J1  
plug removed, power on.  
Ensure wires were stripped before being crimped in  
a wire connector, ensure wires are crimped tightly in  
their connectors, ensure connection pins in sockets  
and plugs are not damaged or worn, ensure plugs  
and sockets are mating properly and providing good  
contact.  
Check J1 plug and J1 socket on the CCB for  
wear or damage. Ensure plugs and sockets are  
mating properly and providing good contact.  
Check for 24 VAC from transformer secondary  
winding at CCB’s J1 socket pins 4 & 5 with J1  
plug inserted, power on. If 24 VAC is not present  
AND the two checks above were performed and  
the results were successful - replace the trans-  
former. Check all wiring for shorts before power-  
ing up the new transformer.  
Failure to perform this critical step or failing to  
perform this step thoroughly often results in  
needless down time, unnecessary parts  
replacement, and customer dissatisfaction.  
Call the technical support phone number shown  
on the water heater labeling for further assis-  
tance if the problem has not been corrected  
after performing the procedures outlined here.  
Ensure Ribbon Cable from the Button overlay is  
inserted correctly in UIM J3 Socket (page 27).  
UIM is Inoperable  
UIM does not respond to any user input using the  
operational and/or Up and Down buttons.  
Call the technical support phone number shown  
on the water heater labeling for further assis-  
tance if the problem has not been corrected  
after performing the procedures outlined here.  
Water heater may be maintaining water temperature  
at the last saved setting or may not be operating at  
all.  
Technical Literature Department  
42 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
FAULT MESSAGES  
DISPLAYED MESSAGE  
CONDITION/INDICATES  
CHECK/REPAIR  
Check incoming power supply wiring to the  
water heater in the junction box - ensure that  
the hot wire is connected to the water heater’s  
black wire and the neutral wire is connected to  
the water heater’s white wire inside the junction  
box. See electrical requirements on page 8.  
“AC Reversed”  
The control system has detected the power supply  
polarity is reversed.  
Check for 120 VAC at CCB’s J3 Socket (page  
36) pins 1 & 3 with J3 plug inserted, power on.  
Check for AC voltage between pin 1 and ground  
- should indicate 120 VAC.  
Check for AC voltage between pin 3 and ground  
- should indicate 0 VAC.  
Call the technical support phone number shown  
on the water heater labeling for further assis-  
tance if the problem has not been corrected  
after performing the procedures outlined here.  
Check Temperature Probe plug and socket con-  
nection at CCB’s J7 Socket (page 36). Perform  
close visual inspection of the pins inside the  
plug and socket - ensure plugs and sockets are  
mating properly and providing good contact.  
“Upper Probe Open”  
The control system has detected over 56,000 ohms  
from the Temperature Probe on top of the water  
heater.  
Check all wiring between the Temperature  
Probe and the J7 Socket on the CCB. Repair/  
replace anything worn or damaged.  
Unplug J7 plug from CCB, check resistance  
between the two black wires in the plug end with  
an ohm meter. If resistance is above 56,000  
ohms - replace the Temperature Probe.  
Call the technical support phone number shown  
on the water heater labeling for further assis-  
tance if the problem has not been corrected  
after performing the procedures outlined here.  
Technical Literature Department  
43 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
FAULT MESSAGES (CONT)  
DISPLAYED MESSAGE  
CHECK/REPAIR  
CONDITION/INDICATES  
Check all wiring between the Temperature  
Probe and the J7 Socket on the CCB (page 36).  
Repair/replace anything worn or damaged.  
“Upper Probe Short”  
The control system has detected less than 390  
ohms from the Temperature Probe on top of the  
water heater.  
Unplug J7 plug from CCB, check resistance  
between the two black wires in the plug end with  
an ohm meter. If resistance is at or below 390  
ohms - replace the Temperature Probe.  
Call the technical support phone number shown  
on the water heater labeling for further assis-  
tance if the problem has not been corrected  
after performing the procedures outlined here.  
Disconnect the wire from the flame sensor (see  
pages 12 and 24). Check for continuity between  
flame sensor and ground with an ohm meter.  
There should be no continuity - infinite resis-  
tance.  
“Flame Probe Short”  
The control system has detected that the flame  
sensor is grounded.  
If above test indicates there is continuity  
between the flame sensor and ground - remove  
the flame sensor (see pages 12 and 24). Ensure  
the flame sensor is not bent and touching the  
burner.  
Check all flame sensor wiring between the  
flame sensor and the J4 male spade connector  
on the CCB (page 36). Ensure there are not any  
pinched wires or shorts - repair/replace anything  
worn or damaged.  
Replace the flame sensor.  
Call the technical support phone number shown  
on the water heater labeling for further assis-  
tance if the problem has not been corrected  
after performing the procedures outlined here.  
Technical Literature Department  
44 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
FAULT MESSAGES (CONT)  
DISPLAYED MESSAGE  
CHECK/REPAIR  
CONDITION/INDICATES  
The burner has not shut down properly. Check  
gas valve for 100% closure. Check for flame  
candling after the heating cycle has ended  
through the Burner View Port, see page 11.  
“Flame Detect Error”  
The control system has detected flame sensing  
current out of sequence.  
If burner flame is candling after the heating  
cycle has ended - replace gas valve assembly,  
see gas valve removal procedure page 15.  
Call the technical support phone number shown  
on the water heater labeling for further assis-  
tance if the problem has not been corrected  
after performing the procedures outlined here.  
Be extremely careful - record temperature from  
a nearby hot water fixture.  
“Energy Cut Out (ECO)”  
The control system has detected water temperature  
in the tank above 190°F. Tank temperature must cool  
to 140°F before the fault message (lock out) can be  
reset. Cycle power off (20 seconds) and on again to  
reset.  
If recorded temperature is above 180°F - shut  
off power and gas to the water heater and call  
the technical support phone number shown on  
the water heater labeling for further assistance.  
DO NOT LEAVE THE WATER HEATER IN  
OPERATION.  
If recorded temperature from above is well  
below 180°- cycle power to reset the control  
system. Watch the water heater through several  
heating cycles. If tank temperature climbs to  
excessively high temperatures - shut off power  
and gas to the water heater and call the techni-  
cal support phone number shown on the water  
heater labeling for further assistance. DO NOT  
LEAVE THE WATER HEATER IN OPERATION.  
Check Temperature Probe plug and socket con-  
nection at CCB’s J7 Socket (page 36). Perform  
close visual inspection of the pins inside the  
plug and socket - ensure plugs and sockets are  
mating properly and providing good contact.  
Check all wiring between the Temperature  
Probe and the J7 Socket on the CCB. Repair/  
replace anything worn or damaged.  
With the J7 plug disconnected from the CCB  
(page 36) check for continuity between the two  
red wires in the plug end (pins 1 & 4) with an  
ohm meter. If there is no continuity between  
these two wires and the tank temperature is not  
excessive - replace the Temperature Probe.  
Technical Literature Department  
45 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
FAULT MESSAGES (CONT)  
DISPLAYED MESSAGE  
CHECK/REPAIR  
CONDITION/INDICATES  
If the water heater has been installed as a con-  
ventional vent appliance - Ensure the intake air  
connection screen is not clogged with debris.  
See Service Notes - Venting on page 7.  
“Blocked Inlet”  
The control system has detected open contacts at  
the Blocked Intake air pressure switch - inadequate  
supply of intake (combustion) air.  
If water heater has been installed as a direct  
vent appliance - check for restrictions, too many  
equivalent feet, or too many elbows in the intake  
air piping. Review venting installation section of  
the Instruction Manual that came with the water  
heater - see Table 1 on page 7 in this manual.  
Ensure the vent/intake air piping has been  
installed within manufacturers requirements.  
If water heater has been installed as a direct  
vent appliance - temporarily disconnect the  
intake air pipe at the blower connection on the  
water heater - ensure the screen inside the  
intake air connection was removed during  
installation. See the Service Notes for venting  
on page 7.  
Check all wiring between the Blocked Intake air  
pressure switch and the CCB’s J6 Socket (page  
36) pins 4 & 14. Perform close visual inspection  
of the pins inside the plug and socket - ensure  
plugs and sockets are mating properly and pro-  
viding good contact. Repair/replace anything  
worn or damaged.  
Review the air pressure switch information  
beginning on page 18. Perform the pressure  
switch test procedure for the Blocked Intake air  
pressure switch - see pages 21 through 23.  
Replace the Blocked Intake switch if defective.  
Call the technical support phone number shown  
on the water heater labeling for further assis-  
tance if the problem has not been corrected  
after performing the procedures outlined here.  
Technical Literature Department  
46 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
FAULT MESSAGES (CONT)  
DISPLAYED MESSAGE  
CHECK/REPAIR  
CONDITION/INDICATES  
Check for restrictions, too many equivalent feet,  
or too many elbows in the vent pipe. Ensure  
“Blocked Exhaust Vent”  
The control system has detected open contacts at  
the Blocked Exhaust air pressure switch - the water  
heater is not venting properly.  
Review venting installation section of the  
Instruction Manual that came with the water  
heater - see Table 1 on page 7 in this manual.  
Ensure the vent/intake air piping has been  
installed within manufacturers requirements.  
Check all wiring between the Blocked Exhaust  
air pressure switch and the CCB’s J6 Socket  
(page 36) pins 5 & 10. Perform close visual  
inspection of the pins inside the plug and socket  
- ensure plugs and sockets are mating properly  
and providing good contact. Repair/replace any-  
thing worn or damaged.  
Review the air pressure switch information  
beginning on page 18. Perform the pressure  
switch test procedure for the Blocked Exhaust  
air pressure switch - see pages 21 through 23.  
Replace the Blocked Exhaust switch if defec-  
tive.  
Call the technical support phone number shown  
on the water heater labeling for further assis-  
tance if the problem has not been corrected  
after performing the procedures outlined here.  
Check all wiring between the Blower Prover air  
pressure switch and the CCB’s J6 Socket (page  
36) pins 6 & 7. Ensure there are no shorted or  
pinched wires.  
“Blower Prover Failure”  
The control system has detected closed contacts at  
the Blower Prover air pressure switch out of  
sequence. Blower Prover air pressure switch  
contacts should be open at the beginning of each  
heating cycle - see the Sequence of Operation on  
page 40.  
Ensure there are no jumper wires installed on  
the Blower Prover switch.  
Ensure there are no jumper wires installed  
between the CCB’s J6 Socket pins 6 & 7.  
Review the air pressure switch information  
beginning on page 18. Perform the pressure  
switch test procedure for the Blower Prover air  
pressure switch - see pages 21 through 23.  
Replace the Blower Prover switch if defective.  
Call the technical support phone number shown  
on the water heater labeling for further assis-  
tance if the problem has not been corrected  
after performing the procedures outlined here.  
Technical Literature Department  
47 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
FAULT MESSAGES (CONT)  
DISPLAYED MESSAGE  
CHECK/REPAIR  
CONDITION/INDICATES  
PERFORM ALL THESE TESTS WITH POWER  
TURNED ON AND A CALL FOR HEAT ACTIVE.  
“Blower Prover Open”  
(Blower Not Running)  
Check for 120 VAC at the CCB’s J2 Socket  
(page 36) pins 1 & 2. Perform close visual  
inspection of the pins inside the plug and socket  
- ensure plugs and sockets are mating properly  
and providing good contact.  
The control system has detected open contacts at  
the Blower Prover air pressure switch after Blower  
has been energized.  
Check all wiring between CCB’s J2 Socket pins  
1 & 2 and the blower motor assembly’s high  
voltage 3 Pin Socket (see page 10).  
Disconnect the plug at the blower motor assem-  
bly’s high voltage 3 Pin Socket - check for 120  
VAC at the plug end.  
Perform close visual inspection of the pins  
inside the plug and socket at the blower motor  
assembly’s high voltage 3 Pin Socket - ensure  
plugs and sockets are mating properly and pro-  
viding good contact.  
Disconnect the plug at the blower assembly’s  
Low Voltage PWM 5 pin plug (see page 10). If  
the Blower has not been running prior and starts  
running when this plug is disconnected - call the  
technical support phone number shown on the  
water heater labeling for further assistance.  
Ensure the Blower Prover air pressure switch  
sensing tube is connected properly at both ends  
and that it is not kinked or damaged. Repair/  
replace anything worn or damaged as neces-  
sary.  
“Blower Prover Open”  
(Blower Is Running)  
The control system has detected open contacts at  
the Blower Prover air pressure switch after Blower  
has been energized.  
Check all wiring between CCB’s J6 Socket  
(page 35) pins 6 & 7 and the Blower Prover air  
pressure switch. Repair/replace anything worn  
or damaged as necessary.  
Perform close visual inspection of the pins  
inside the CCB J6 plug and socket - ensure  
plugs and sockets are mating properly and pro-  
viding good contact.  
Review the air pressure switch information  
beginning on page 18. Perform the pressure  
switch test procedure for the Blower Prover air  
pressure switch - see pages 21 through 23.  
Replace the Blower Prover switch if defective.  
Technical Literature Department  
48 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
FAULT MESSAGES (CONT)  
DISPLAYED MESSAGE  
CHECK/REPAIR  
CONDITION/INDICATES  
Check all wiring between CCB’s J5 Socket  
(page 35) pins 1 & 2 and the hot surface igniter.  
Repair/replace anything worn or damaged as  
necessary.  
“Low Igniter Current”  
The control system has detected less than 2.0 AC  
amps through the igniter during the igniter warm up  
period.  
Perform close visual inspection of the pins  
inside the CCB J5 plug and socket - ensure  
plugs and sockets are mating properly and pro-  
viding good contact. Repair/replace anything  
worn or damaged as necessary.  
With power turned on and a call for heat active -  
ensure there is 120 VAC between pins 1 & 2 of  
the CCB’s J5 Socket during the igniter warm up  
period. - the igniter lighting bolt icon will appear  
on the UIM display during the igniter warm up  
period. See Table 4 on page 30.  
Turn off power to the water heater - disconnect  
wires to igniter at the igniter. Check for continu-  
ity between the two igniter wires. If the igniter  
shows to be an open circuit - replace the igniter.  
With power turned on and a call for heat active -  
check amp draw through the igniter with an AC  
amp meter during the igniter warm up period.  
This procedure is illustrated and explained on  
page 25. Replace igniter if amp draw is less  
than 3.0 AC amps.  
Call the technical support phone number shown  
on the water heater labeling for further assis-  
tance if the problem has not been corrected  
after performing the procedures outlined here.  
Technical Literature Department  
49 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
FAULT MESSAGES (CONT)  
DISPLAYED MESSAGE  
CHECK/REPAIR  
CONDITION/INDICATES  
Visually check for burner flame through the view  
port on the top of the water heater (see illustra-  
tions on page 11) during the Ignition Verification  
operating state (Table 5 - page 31) - the Gas  
Valve icon will appear on UIM display during this  
operating state.  
“Ignition Failure”  
The control system has detected less than 1.0 µA  
(DC micro amps) through the flame sensor during  
the Ignition Verification operating state on three  
consecutive trials for ignition.  
Ensure the gas supply shut off valve is open.  
Ensure there is adequate air for combustion &  
ventilation. See air requirements in the Instruc-  
tion Manual that came with the water heater.  
Ensure the burner is grounded - see electrical  
requirements and service notes on page 8.  
Ensure flame sensor wiring is plugged in  
securely at the CCB’s J4 male spade connector  
(page 35) and at the flame sensor wiring termi-  
nal (page 24).  
Check all wiring between the flame sensor and  
the CCB J4 connection. Repair/replace anything  
worn or damaged as necessary.  
Rough Starting - Rough Operation Note:  
If the water heater is experiencing rough operation  
or rough starting review the Service Notes - Blower  
Flange & Blower Adapter Gaskets on page 13.  
Remove and clean the flame sensor (page 24)  
with fine steel wool - check for signs of exces-  
sive wear, bent, damage, cracks in the insulator  
- replace flame sensor if worn or damaged.  
Call the technical support phone number shown on  
the water heater labeling for further assistance if the  
problem has not been corrected after performing the  
procedures outlined here.  
Check for flame sensing current during the Igni-  
tion Verification operating state - Gas Valve icon  
will appear on UIM display (Table 5 - page 31).  
Flame sensing current test procedure is illus-  
trated and explained on page 24.  
If flame sensing current measured is well above  
the 1.0 µA (DC micro amps) minimum during  
this test and the control system continues to  
declare the Ignition Failure fault condition after  
three trials - call the technical support phone  
number shown on the water heater labeling for  
further assistance.  
If the flame sensing current measured is not  
established or is below 1.0 µA - continue to the  
next check/repair procedure.  
Technical Literature Department  
50 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
FAULT MESSAGES (CONT)  
DISPLAYED MESSAGE  
CHECK/REPAIR  
CONDITION/INDICATES  
Check for 24 VAC to the Gas Valve solenoid coil  
at the in-line male/female spade connectors  
during the Ignition Activation operating state  
(Gas Valve icon will be visible on the UIM dis-  
play during this period).  
“Ignition Failure”  
The control system has detected less than 1.0 µA  
(DC micro amps) through the flame sensor during  
the Ignition Verification operating state on three  
consecutive trials for ignition.  
Check all wiring, plugs, and sockets between  
the Gas valve solenoid coil and CCB’s J6  
Socket pins 2 & 15 (page 35). Repair/replace  
anything worn or damaged.  
If 24 VAC is not being sent to the Gas Valve  
solenoid coil during the Ignition Activation oper-  
ating state and all wiring, plugs, and sockets are  
in good condition and making good contact - call  
the technical support phone number shown on  
the water heater labeling for further assistance.  
Check supply and manifold gas pressures. This  
procedure is illustrated and explained on pages  
16 and 17.  
Rough Starting - Rough Operation Note:  
If the water heater is experiencing rough operation  
or rough starting review the Service Notes - Blower  
Flange & Blower Adapter Gaskets on page 13.  
If supply gas pressure is below the minimum  
requirement shown in Table 2 on page 17 -  
raise/restore supply gas pressure to minimum  
requirement. If supply gas pressure is above  
maximum requirement - reduce supply gas  
pressure below maximum requirement.  
Call the technical support phone number shown on  
the water heater labeling for further assistance if the  
problem has not been corrected after performing the  
procedures outlined here.  
If there is not a rise in manifold pressure and a  
corresponding drop in supply gas pressure  
when the Gas Valve is energized as outlined on  
on pages 16 and 17 the gas valve is not open-  
ing or is clogged and is not allowing gas to flow  
to the burner - continue to the next procedure.  
Remove the Gas Valve and ensure the gas ori-  
fice and gasket are installed properly and that  
the correct size orifice for the fuel type is  
installed. The procedure for removing the gas  
valve to check the gas orifice is illustrated and  
explained on page 15. Inspect the Gas Valve for  
any signs of damage - replace if necessary.  
Remove the burner and inspect it for damage or  
debris that may have collected inside the burner  
and be causing the ignition failure. The burner  
removal procedure is illustrated and explained  
on pages 11 through 13. If the burner is dam-  
aged or severely clogged with debris - replace  
the burner.  
Technical Literature Department  
51 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ULTRA HIGH EFFICIENCY POWER VENT/POWER DIRECT VENT - SERVICE MANUAL  
FAULT MESSAGES (CONT)  
DISPLAYED MESSAGE  
CHECK/REPAIR  
CONDITION/INDICATES  
Turn off power - check all wiring and connectors  
between the CCB’s J6 Socket (page 35) pins 2  
& 15 and the Gas Valve’s solenoid coil. Repair/  
replace anything worn or damaged as neces-  
sary.  
“Gas Valve Failure”  
The control system has not detected any current  
through the gas valve after it has been energized.  
Perform close visual inspection of the pins  
inside the CCB J6 plug and socket - ensure  
plugs and sockets are mating properly and pro-  
viding good contact. Repair/replace anything  
worn or damaged as necessary.  
Turn off power - disconnect the Gas Valve wir-  
ing plug on top of the Gas Valve solenoid coil.  
Check Gas Valve solenoid coil resistance with  
an ohm meter at the solenoid coil terminals.  
Normal resistance is approximately 7 million  
ohms. If the Gas Valve solenoid coil is an open  
circuit - replace the Gas Valve.  
Check for 24 VAC at CCB’s J6 Socket pins 2 &  
15 during the Ignition Activation operating state  
(the Gas Valve status icon will be visible on the  
UIM display during this period.  
Call the technical support phone number shown  
on the water heater labeling for further assis-  
tance if the problem has not been corrected  
after performing the procedures outlined here.  
Turn off power - check the communication cable  
connections between the J2 Socket on the UIM  
circuit board (page 27) and the CCB J16 Port  
(page 35).  
“Communication Failure”  
Loss of communication between the CCB and the  
UIM.  
Try a new communication cable (standard cate-  
gory V network cable) between the CCB and the  
UIM.  
Call the technical support phone number shown  
on the water heater labeling for further assis-  
tance if the problem has not been corrected  
after performing the procedures outlined here.  
Technical Literature Department  
52 of 52  
Ashland City, TN © 2008  
Servicing should only be performed by a Qualified Service Agent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
500 Tennessee Waltz Parkway  
Ashland City, TN 37015  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Snapper Lawn Mower ZF2200K User Manual
Sony DVD Player BDP S280 User Manual
Sony MiniDisc Player MDS PC1 User Manual
Sony MiniDisc Player MDS W1 User Manual
Speco Technologies Power Supply PSR 12S User Manual
StarTechcom Network Cables USBDUP15 User Manual
StarTechcom Server ECS0016 User Manual
Sub Zero Refrigerator ICBBI 30U User Manual
Sunbeam Wok WW4500D User Manual
Sylvania Flat Panel Television LD195SL8 User Manual