| Catalog No:   Effective:   Replaces:   5000.65   8/26/05   NEW   Y-200 Modem Module   For use with   Y-200 Series Electronic Boiler Sequencer   & Outdoor Reset Control System   Installation and Operating Manual   P/N 241263   Download from Www.Somanuals.com. All Manuals Search And Download.   Installation and Operating Manual   Y-200 Modem Module   Contents   Introduction   Introduction.............................................................1   The Raypak Y-200 series modem module provides   the ultimate method to communicate with the Y-200   controller and auxiliary equipment.   Important Safety Instructions...................................1   Installation and Set-Up ............................................2   Limited Warranty....................................................4   IMPORTANT SAFETY   INSTRUCTIONS   IMPORTANT NOTICE: These instructions are   intended for use by qualified personnel who are spe-   cifically trained and experienced in the installation of   this type of equipment and related system compo-   nents. Installation and service personnel may be re-   quired by some states to be licensed. If your state   requires certification, be sure your contractor bears   the appropriate license. Only qualified persons shall   attempt to repair this equipment. Repair must be ac-   cording to these instructions.   WARNING: Improper installation, adjustment, al-   teration, service or maintenance may damage the   equipment, create a hazard resulting in asphyxiation,   explosion, fire, electric shock, personal injury or   property damage, and will void the warranty.   CAUTION: THIS APPLIANCE HAS PROVI-   SIONS TO BE CONNECTED TO MORE THAN   ONE (1) SUPPLY SOURCE. TO REDUCE THE   RISK OF ELECTRIC SHOCK, DISCONNECT ALL   SUCH CONNECTIONS BEFORE SERVICING.   CAUTION: RISK OF ELECTRIC SHOCK. MORE   THAN ONE (1) DISCONNECT SWITCH MAY BE   REQUIRED TO DE-ENERGIZE THE EQUIP-   MENT BEFORE SERVICING.   1 Download from Www.Somanuals.com. All Manuals Search And Download.   Y-200 Modem Module   Installation and Operating Manual   Installation and Set-up   Note: A PCMCIA card might be necessary on some   laptop computers for proper operation.   Modem Board Installation   1. Remove power from the Y-200 control.   2. Install the plug-in modem module (P/N 601741)   on to connectors “J22” and “J23” as shown on   the PCB. (See Fig. #.)   3. Plug an active phone line into “PJ1” on the mo-   dem board. (See Fig. #.)   4. Record the phone line number: _____________.   5. Restore power to the Y-200 control.   Fig. 2   Computer Preparations and Dialing   If you have call waiting on your phone line, enter   *70 before the number. This will temporarily   turn off call waiting for the time your modem is   connected.   1. From the   menu, choose Programs,   Accessories, Communications, HyperTerminal.   (Make sure the Caps Lock is turned off when   using HyperTerminal.)   4. In the Connect window, modify the number and   the dialing propriety if necessary.   2. In the Connection Description window, select a   name and icon for the connection and select OK.   (See example in Fig. 1.)   5. In the Connect window, click on the dial button   to dial the number.   6. As soon as the computer makes a connection,   “Enter Password:” appears on the screen. (If it   does not prompt you for a password try typing   the “U” key or disconnect and try again till it   does.)   7. Type “Y200” and <Enter>. (This password can   be changed on the Y-200 display window #29.)   8. The first Y-200 display window (#1) of the   Y-200 will be placed on the screen.   9. You can now operate or setup the Y-200 re-   motely, with the exception of screen # 30 which   is programmed at the Y-200 control only). If   you attempt to reprogram screen #30 remotely   the Y-200 will kick you off line.   Fig. 1   3. In the Connect To window, enter the area code   and phone number (no spaces, hyphens, etc.)   then select OK. (See Fig. 2.)   2 Download from Www.Somanuals.com. All Manuals Search And Download.   Installation and Operating Manual   Y-200 Modem Module   b. Go into the program mode and enter the   phone number by using the keypad up or   down and left or right arrows.   Dialing into the Y-200 Programming   Keys and Operation   1. The “U” key takes you up through the screen   displays and in the program mode changes the   character above the cursor scrolling up.   c. If you program in too many numbers and   you want to erase the extra numbers, insert a   “#” sign after the last number you want to   keep. To verify, exit the program mode and   screen #30 and then go back to screen #30.   The # sign indicates the end of phone num-   ber.   2. The “D” key takes you down through the screen   displays and in the program mode changes the   character above the cursor scrolling down.   3. The “P” key puts you into the program mode.   4. The “M” key takes you out of the program mode.   5. The “<”key moves the cursor to the left.   6. The “>” key moves the cursor to the right.   d. Up to 16 numbers can be stored.   2. To program in the Alarm Call ID:   a. Go to screen #31.   b. Enter the ID code of the Y-200 location.   7. Now you can program or set up the Y-200 re-   motely.   c. If you program in too many characters and   you want to erase the extra characters, put   the “#” sign after the last number you want   to keep. To verify, exit the program mode   and screen #31 and then go back to screen   #31. The # sign indicates the end of the ID   code.   8. To get into the password-protected windows   above #19 you must go to window #19 then type   “P” then “M” then use the “U” and “D” keys to   scroll through screens #20 through #33.   Dialing out from the Y-200 Computer   Preparation   d. Up to 16 numbers or letters can be stored.   3. To program the Alarm Call Retry:   a. Go to screen #32.   1. Activate the HyperTerminal on your computer   2. Type “AT” then <Enter>.   b. Program in the number of times you want   the Y-200 to try and call out when there is a   fault condition (00 to 20).   3. You should see the “OK” on your computer   screen.   4. Type “ATS0=1” <Enter>.   c. Modem activity is also displayed   4. To program the Alarm Call Event:   a. Go to screen #33.   5. You should see another “OK” on your computer   screen. (Computer answers on one ring).   6. The computer is now set up to receive calls from   the Y-200 when there is an alarm condition.   b. Program in the alarm conditions you wish to   be enabled. The cursor appears under the   first “A” when in the program mode.   7. The same thing can be accomplished by clicking   on the “Call” and then on the “Wait for a call”   button in the Hyper Terminal window.   c. Screen will change to an alarm condition   and at the end it will show weather it is in   the Enable or Disable condition.   Dialing out from the Y-200 (Alarm No-   tification) Programming and Opera-   tion   1. To program in the phone number the Y-200   should notify in case of an alarm condition:   a. Go to screen #30 (ON THE Y-200 CON-   TROL ONLY).   3 Download from Www.Somanuals.com. All Manuals Search And Download.   LIMITED WARRANTY   Y-200 Modem Module   for Y-200 Series Electronic Boiler Sequencer   & Outdoor Reset Control System   SCOPE OF WARRANTY   Raypak, Inc. ("Raypak") warrants to the original owner the Control System to be free from defects in materials and workmanship under   normal use and service for the applicable warranty period. In accordance with the terms of this Limited Warranty, RAYPAK will furnish a   replacement or repair, at our option, any defective part which fails in normal use and service during the applicable warranty period. The re-   placement or repair will be warranted for only the unexpired portion of the original Warranty Period.   APPLICABLE WARRANTY PERIOD   The effective date of warranty coverage is the date of original installation, of the Control System, by a qualified electrician or by a RAYPAK   authorized service technician. The Applicable Warranty Period is one (1) year from the effective date.   WARRANTY EXCLUSIONS   This Limited Warranty does not apply:   1. If the control system is not properly installed by a qualified technician in accordance with manufacture's installation instructions,   applicable codes, ordinances and good trade practices;   2. To damage or malfunctions resulting from failure to properly install, operate or maintain the system in accordance with the manufac-   ture's instructions;   3. If the rating plate(s) or serial number(s) are altered, defaced or removed;   4. If the System is modified in any way or used with any non-factory authorized accessories or components;   5. To damage or failure from abuse, accident, act of nature, fire, flood, freezing or the like;   6. To accessories, rubber or plastic parts, light bulbs or glass parts;   7. If the System is moved from its original installation site; or if the original owner no longer owns the site or the System.   LABOR AND SHIPPING COSTS   This Limited Warranty does not cover labor costs for service, removal or reinstallation of any part nor shipping charges to or from RAYPAK'S   designated repair center or to or from the installation site. All such costs are your responsibility.   HOW TO MAKE A WARRANTY CLAIM   To make a warranty claim, promptly ship (postage prepaid) or carry the defective part to a designated RAYPAK Service Dealer or Service   Station in the United States, supplying proof of purchase and date of installation and the model and serial numbers. If you cannot locate a   dealer, contact RAYPAK'S Service Department at the address/telephone listed below. Raypak reserves the right at all times to inspect   the claimed defect and verify warranty coverage at its factory.   EXCLUSIVE WARRANTY - LIMITATION OF LIABILITY   This is the only warranty given by RAYPAK. No one is authorized to make any other warranties on Raypak's behalf. ANY IMPLIED WAR-   RANTIES, INCLUDING MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, SHALL NOT EXTEND BEYOND THE   APPLICABLE WARRANTY PERIOD SPECIFIED ABOVE. RAYPAK'S SOLE LIABILITY WITH RESPECT TO ANY DEFECT SHALL   BE AS SET FORTH IN THIS LIMITED WARRANTY. ANY CLAIMS FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES (INCLUDING   DAMAGE FROM WATER LEAKAGE) ARE EXCLUDED. Some states do not allow limitations on how long an implied warranty lasts, or for   the exclusion of incidental or consequential damages, so the above limitation or exclusion may not apply to you.   THIS LIMITED WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY   FROM STATE TO STATE.   We suggest you immediately complete the information below and retain this Limited Warranty Certificate in case warranty service is needed.   Raypak, Inc., Service Department   2151 Eastman Avenue, Oxnard, California 93030   Telephone: (805) 278-5300 Fax (805) 278-5468   The following information must be provided when you write or call:   Original Owner   Mailing Address   Model Number   Serial Number   Date of Installation   Installation Site   Contractor/Installer   City   State   Zip Code   Daytime Telephone Number   Download from Www.Somanuals.com. All Manuals Search And Download.   Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (805) 278-5468   Raypak Canada Limited, 2805 Slough St., Mississauga, Ontario, Canada L4T 1G2 (905) 677-7999 Fax (905) 677-8036   Litho in U.S.A.   Download from Www.Somanuals.com. All Manuals Search And Download.   |