					LVUN-600   
					Non-invasive Ultrasonic Point Level Switches   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				UNPACKING INSTRUCTIONS   
					UNPACKING INSTRUCTIONS   
					Remove the Packing List and verify that you have received all equipment, includ-   
					ing the following (quantities in parentheses):   
					Ultrasonic Level Switch (1)   
					Operator’s Manual (1)   
					If you have any questions about the shipment, please call the OMEGA Customer   
					Service Department. When you receive the shipment, inspect the container and   
					equipment for signs of damage. Note any evidence of rough handling in transit.   
					Immediately report any damage to the shipping agent.   
					Note:   
					The carrier will not honor damage claims unless all shipping   
					material is saved for inspection. After examining and removing   
					contents, save packing material and carton in the event reship-   
					ping is necessary.   
					For Ultrasonic Point Level Switches LVUN-600 Series   
					2 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				TABLE OF CONTENTS   
					Page   
					Chapter 1   
					Chapter 2   
					Chapter 3   
					Chapter 4   
					Chapter 5   
					Point Level Model Description . . . . . . . . . . . . . . . . . . . . . . . . . .4   
					Principles of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4   
					Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-7   
					System Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-9   
					Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-11   
					3 
					For Ultrasonic Point Level Switches LVUN-600Series   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SYSTEM DESCRIPTIONS   
					1 
					GENERAL DESCRIPTION   
					The LVUN-600 Series Liquid Level Detection system is an ideal, low cost ultrasonic   
					liquid level detection system for many applications. It operates in a broad spec-   
					trum of viscous to light liquids.   
					PRINCIPLES OF OPERATION   
					2 
					PRINCIPLES OF OPERATION   
					The LVUN-600 Series operates using ultrasonic sound wave propagation. Ultrasonic   
					sound waves are greatly attenuated when transmitted through air. Conversely,   
					when liquid is present, transmission of the sound waves is greatly enhanced. The   
					electronic control unit, either integral or remote to the sensor, generates electrical   
					signals that are converted to bursts of ultrasonic energy at the sensor. The ultra-   
					sonic bursts are transmitted across the liquid sensing gap of the sensor. Upon   
					receipt of a valid signal at the receiver, the solid state electronics generate a “data   
					enable” condition indicating liquid is present. This signal energizes a relay and   
					provides an output condition.   
					4 
					For Ultrasonic Point Level Switches LVUN-600 Series   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				INSTALLATION   
					3 
					GENERAL INSTALLATION   
					All units are easy to install. The sensor with its remote electronic control unit can   
					be mounted in any position or orientation desired.   
					Make sure that all wiring, conduit and electrical fittings conform to local electrical   
					codes for the location selected.   
					VISUAL INSPECTION   
					Unpack the control unit and sensor assemblies. Visually inspect them for any   
					damage. Advise Cosense immediately if either assembly is damaged.   
					PRELIMINARY OPERATIONAL CHECK   
					Before installing the unit, a simple operational checkout should be performed as   
					follows:   
					WARNING: In a hazardous environment never open the housing cover or con-   
					nect the power leads without first disconnecting the electrical power at its   
					source.   
					1. Fill a container with liquid.   
					2. Open the control unit housing cover and connect the power to the control unit   
					(see wiring diagram).   
					3. Apply power from the source.   
					4. Place the sensor in the liquid. The relay should energize.   
					5. Remove the sensor from the liquid. The relay will de-energize indicating that   
					the system is functioning properly.   
					6. Disconnect the power to the control unit.   
					7. Proceed to final installation.   
					NON-INVASIVE / CLAMP-ON TIME   
					Refer to the typical installation diagram and follow the instructions below.   
					1. Clean the mounting surface of the pipe or vessel.   
					2. Coat the sensor faces and the area on the pipe or vessel where sensors are to   
					be mounted liberally with coupling compound (silicone grease or heat sink   
					compound).   
					3. Clamp the sensor assembly on the pipe or vessel. Tighten the clamp assembly   
					on the vessel until the sensor assembly is firmly mounted against the sensor   
					wall. Do not over tighten.   
					4. Run the cable to the control unit assembly.   
					For Ultrasonic Point Level Switches LVUN-600Series   
					5 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				INSTALLATION   
					3 
					CONTROL UNIT   
					Refer to the typical installation diagram and control unit dimensions when   
					installing the control unit.   
					CALIBRATION PROCEDURE   
					After the installation is complete, the system must be calibrated for proper opera-   
					tion.   
					1. Connect the sensor cable to electronics as shown in wiring diagram.   
					2. Connect power as per wiring diagram.   
					3. Turn the power on.   
					4. Allow the liquid to rise above the sensing point until the relay is energized.   
					5. Allow the liquid to fall below the sensing point, relay should de-energized.   
					6. Repeat steps 4 and 5.   
					7. Unit is now calibrated. When the liquid level is above the sensing point, the   
					relay will be energized. When the liquid level is below the sensing point,   
					the relay will be de-energized.   
					MAINTENANCE   
					PREVENTIVE MAINTENANCE   
					Electronics are constructed with solid state components.   
					Periodically, check and clean the sensor(s) when used with   
					liquids which cause a coating to build up on the sensor. No   
					other maintenance is required.   
					CLEANING   
					If the pipe or vessel to which the sensor is mounted is to be steam cleaned or   
					cleaned with abrasive detergents, remove the entire unit before cleaning by:   
					1. Disconnecting the power at source.   
					2. Opening the housing cover.   
					For Ultrasonic Point Level Switches LVUN-600 Series   
					6 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				INSTALLATION   
					3 
					3. Removing power and control wiring cables.   
					4. Unthreading the sensor.   
					To reinstall, follow Installation Procedure   
					SYSTEM MALFUNCTION   
					Should the system malfunction, notify OMEGA immediately   
					7 
					For Ultrasonic Point Level Switches LVUN-600 Series   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SYSTEM WIRING DIAGRAM   
					4 
					WIRING DIAGRAM   
					Two Channel   
					For Ultrasonic Point Level Switches LVUN-600 Series   
					8 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SYSTEM WIRING DIAGRAM   
					4 
					WIRING DIAGRAM   
					Multi Channel:   
					Four Channel:   
					Three Channel:   
					9 
					For Ultrasonic Point Level Switches LVUN-600 Series   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				DIMENSIONAL DRAWINGS   
					5 
					ENCLOSURE DIMENSIONS   
					For Ultrasonic Point Level Switches LVUN-600 Series   
					10   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				DIMENSIONAL DRAWINGS   
					5 
					TYPICAL APPLICATION   
					For Ultrasonic Point Level Switches LVUN-600 Series   
					11   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Download from Www.Somanuals.com. All Manuals Search And Download.   
				Download from Www.Somanuals.com. All Manuals Search And Download.   
				WARRANTY/DISCLAIMER   
					OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a   
					period of 13 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month   
					grace period to the normal one (1) year product warranty to cover handling and shipping time. This   
					ensures that OMEGA’s customers receive maximum coverage on each product.   
					If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service   
					Department will issue an Authorized Return (AR) number immediately upon phone or written request.   
					Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no   
					charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser,   
					including but not limited to mishandling, improper interfacing, operation outside of design limits,   
					improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of   
					having been tampered with or shows evidence of having been damaged as a result of excessive corrosion;   
					or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating   
					conditions outside of OMEGA’s control. Components in which wear is not warranted, include but are not   
					limited to contact points, fuses, and triacs.   
					OMEGA is pleased to offer suggestions on the use of its various products. However,   
					OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any   
					damages that result from the use of its products in accordance with information provided by   
					OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the   
					company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR   
					REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF   
					TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY   
					AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF   
					LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of   
					OMEGA with respect to this order, whether based on contract, warranty, negligence,   
					indemnification, strict liability or otherwise, shall not exceed the purchase price of the   
					component upon which liability is based. In no event shall OMEGA be liable for   
					consequential, incidental or special damages.   
					CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic   
					Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical   
					applications or used on humans. Should any Product(s) be used in or with any nuclear installation or   
					activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility   
					as set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify   
					OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the   
					Product(s) in such a manner.   
					RETURN REQUESTS/INQUIRIES   
					Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE   
					RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN   
					(AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID   
					PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return   
					package and on any correspondence.   
					The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent   
					breakage in transit.   
					FOR WARRANTY RETURNS, please have the   
					following information available BEFORE   
					contacting OMEGA:   
					FOR NON-WARRANTY REPAIRS, consult OMEGA   
					for current repair charges. Have the following   
					information available BEFORE contacting OMEGA:   
					1. Purchase Order number under which the product   
					was PURCHASED,   
					1. Purchase Order number to cover the COST   
					of the repair,   
					2. Model and serial number of the product under   
					warranty, and   
					3. Repair instructions and/or specific problems   
					relative to the product.   
					2. Model and serial number of the product, and   
					3. Repair instructions and/or specific problems   
					relative to the product.   
					OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords   
					our customers the latest in technology and engineering.   
					OMEGA is a registered trademark of OMEGA ENGINEERING, INC.   
					© Copyright 2005 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied,   
					reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the   
					prior written consent of OMEGA ENGINEERING, INC.   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Where Do I Find Everything I Need for   
					Process Measurement and Control?   
					OMEGA…Of Course!   
					Shop online at omega.com   
					TEMPERATURE   
					Ⅺ 
					ߜ   Ⅺ 
					ߜ   Ⅺ 
					ߜ   Ⅺ 
					ߜ   Ⅺ 
					ߜ   Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies   
					Wire: Thermocouple, RTD & Thermistor   
					Calibrators & Ice Point References   
					Recorders, Controllers & Process Monitors   
					Infrared Pyrometers   
					PRESSURE, STRAIN AND FORCE   
					Ⅺ 
					ߜ   Ⅺ 
					ߜ   Ⅺ 
					ߜ   Ⅺ 
					ߜ   Transducers & Strain Gages   
					Load Cells & Pressure Gages   
					Displacement Transducers   
					Instrumentation & Accessories   
					FLOW/LEVEL   
					Ⅺ 
					ߜ   Ⅺ 
					ߜ   Ⅺ 
					ߜ   Ⅺ 
					ߜ   Rotameters, Gas Mass Flowmeters & Flow Computers   
					Air Velocity Indicators   
					Turbine/Paddlewheel Systems   
					Totalizers & Batch Controllers   
					pH/CONDUCTIVITY   
					Ⅺ 
					ߜ   Ⅺ 
					ߜ   Ⅺ 
					ߜ   Ⅺ 
					ߜ   pH Electrodes, Testers & Accessories   
					Benchtop/Laboratory Meters   
					Controllers, Calibrators, Simulators & Pumps   
					Industrial pH & Conductivity Equipment   
					DATA ACQUISITION   
					Ⅺ 
					ߜ   Ⅺ 
					ߜ   Ⅺ 
					ߜ   Ⅺ 
					ߜ   Ⅺ 
					ߜ   Data Acquisition & Engineering Software   
					Communications-Based Acquisition Systems   
					Plug-in Cards for Apple, IBM & Compatibles   
					Datalogging Systems   
					Recorders, Printers & Plotters   
					HEATERS   
					Ⅺ 
					ߜ   Ⅺ 
					ߜ   Ⅺ 
					ߜ   Ⅺ 
					ߜ   Ⅺ 
					ߜ   Heating Cable   
					Cartridge & Strip Heaters   
					Immersion & Band Heaters   
					Flexible Heaters   
					Laboratory Heaters   
					ENVIRONMENTAL   
					MONITORING AND CONTROL   
					Ⅺ 
					ߜ   Ⅺ 
					ߜ   Ⅺ 
					ߜ   Ⅺ 
					ߜ   Ⅺ 
					ߜ   Ⅺ 
					ߜ   Metering & Control Instrumentation   
					Refractometers   
					Pumps & Tubing   
					Air, Soil & Water Monitors   
					Industrial Water & Wastewater Treatment   
					pH, Conductivity & Dissolved Oxygen Instruments   
					M-4201/1005   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				 |