10-00 PRINCIPLE OF OPERATION  
1.  
PRINCIPLE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
COMBUSTION SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
A.  
10-10 OPERATION  
1.  
WATER MANAGEMENT - BETTER EFFICIENCY THAN EVER . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
A.  
B.  
C.  
D.  
E.  
F.  
G.  
INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
SAFETY WATER LEVEL CONTROL CHECK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
SELF DIAGNOSTIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
ENERGY EFFICIENT BLOWDOWN SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
INTERNAL DRAIN WATER TEMPERING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
CAPACITY TURN DOWN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
GSTC UNIT NEWTWORKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
REMOTE FAULT INDICATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
MODULATING CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
ON/OFF CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
ELECTRICAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
VENTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
STEAM INSTALLATION GUIDELINES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15  
CALCULATION OF ANNUAL OPERATING COSTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15  
NATURAL GAS HUMIDIFIER. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15  
ELECTRIC GAS HUMIDIFIER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15  
OPERATING COST SAVINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15  
2.  
A.  
B.  
C.  
D.  
3.  
4.  
5.  
6.  
7.  
A.  
B.  
C.  
10-20 MAINTENANCE  
1.  
2.  
3.  
WATER CONDITIONS VS. HUMIDIFIER CLEANING REQUIREMENTS . . . . . . . . . . . . . . . . . . 18  
PREVENTIVE MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19  
PRE-CLEANING SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19  
10-30 OPTIONS & ACCESSORIES  
1.  
OPTIONS AND ACCESSORIES AVAILABLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22  
NORTEC MODULATING HUMIDISTAT WITH DIGITAL DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22  
HUMIDISTAT WITH INTEGRAL SENSOR AND CONTROLLER WITH DIGITAL DISPLAY . . . . . . . . . 22  
HUMIDISTAT WITH INTEGRAL SENSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22  
NORTEC ON/OFF CONTROLS WITH DIGITAL DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
CONFIGURATION OPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
DIRECT VENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
STAND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
KEEP WARM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
INDOOR FREEZE PROTECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24  
OUTDOOR FREEZE PROTECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24  
A.  
B.  
C.  
D.  
E.  
F.  
G.  
H.  
I.  
J.  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
K.  
L.  
ON-LINE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24  
LINKS 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24  
OUTDOOR 120 VAC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26  
DRAIN WATER SUMP PUMP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26  
STEAM DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26  
REMOTE MOUNTED BLOWER PACK. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26  
SHORT ABSORPTION MANIFOLD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26  
M.  
N.  
O.  
P.  
Q.  
10-40 SPECIFICATION  
1.  
GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
A.  
B.  
C.  
D.  
E.  
QUALITY ASSURANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30  
SUBMITALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30  
EXTRA MATERIALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31  
REFERENCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31  
COORDINATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31  
2.  
3.  
PRODUCTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
A.  
GAS FIRED STEAM HUMIDIFIER - GSTC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31  
EXAMINATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
EXAMINATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35  
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35  
TESTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35  
TRAINING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36  
A.  
B.  
C.  
D.  
WARRANTY  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIST OF FIGURES  
Figure  
Page  
10-00 PRINCIPLE OF OPERATION  
Figure 1.  
Figure 2.  
Figure 3.  
Figure 4.  
GS Indoor Series. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3  
GS Outdoor Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3  
GSTC Key Pad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4  
GSP Key Pad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4  
10-10 OPERATION  
Figure 1.  
Figure 2.  
Figure 3.  
Figure 4.  
Figure 5.  
Humidifier Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
Physical Dimensions - GS Indoor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
Physical Dimensions - GS Outdoor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
GSTC / GSP Indoor Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
GSTC Outdoor Clearance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
10-30 OPTIONS & ACCESSORIES  
Figure 1.  
Figure 2.  
Figure 3.  
Figure 4.  
Figure 5.  
NORTEC LINKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
NORTEC OnLine. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
Steam Distributor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
Blower Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
Short Absorption Manifold. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIST OF TABLES  
Table  
Page  
10-00 PRINCIPLE OF OPERATION  
Table 1.  
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Table 2.  
Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THIS PAGE INTENTIONALLY LEFT BLANK  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10-00  
PRINCIPLE OF  
OPERATION  
10-00  
Page 1  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. PRINCIPLE OF OPERATION  
A. Combustion System  
(1) The combustion system is based on a fully modulating forced draft combustion air  
blower, a negative pressure regulated gas valve, and a 100% premix burner. On a  
call for humidity, the combustion air blower starts and creates a negative pressure  
across an orifice located at the air inlet.  
(2) The blower is energized to purge the system, then the hot surface igniter is activated.  
During this time the electronic ignition module does a diagnostic check of safety  
systems including the air-proving switch, which senses the negative pressure at the  
air inlet orifice. After the function of the safety systems has been verified, the gas  
valve will open and the gas/air mixture is ignited by the hot surface igniter.  
(3) If a flame is sensed by the flame sensor, the gas valve remains open and  
combustion continues. If a flame is not sensed, the above sequence is repeated to a  
maximum of three times after which the ignition module will lock out. The gas valve  
maintains a constant ratio air to gas independent of blower speed or external  
conditions. This air and fuel is thoroughly mixed in the blower and then forced  
through the burner ports where ignition occurs.  
(4) Hot products of combustion are forced through a baffle inside the heat exchanger  
and then vented outside. The heat exchanger has a large flat surface to minimize  
scale build-up and promote scale shedding to the bottom of the tank. This self-  
cleaning action helps to maintain the efficiency of the heat exchanger while the  
smooth surfaces allow for easy cleaning when necessary.  
(5) The GS 100 has a single removable combustion chamber/heat exchanger. The  
combustion system is duplicated on larger units with multiple chambers inside a  
common tank.  
Table 1. Technical Data  
UNIT TYPE  
GS 600  
GS 500  
25-525  
11-238  
700,000  
206  
SPECIFICATION  
GS 100  
25-105  
11-48  
GS 200 GS 300 GS 400  
25-630  
11-286  
840,000  
247  
Rated Capacity: lbs/hr*  
Rated Capacity: kg/hr*  
Input BTU/hr max  
25-210  
11-95  
25-315  
11-143  
25-420  
11-191  
140,000 280,000 420,000 560,000  
Input kJ/hr max  
41  
1.1  
3.2  
2.1  
6.3  
82  
124  
165  
Flue Emissions  
Low CO (< 10 ppm) and Low (NOx <40 ppm)  
5.2  
11.5  
10  
4.3  
10.6  
8.4  
GSTC/GSP Rated Amps  
Voltage/Phase  
1.9  
4.0  
3.7  
7.4  
2.7  
208-240/1 Standard  
6.9 7.7  
208-240/1 Standard  
5.3 6.8  
120/1 Standard  
13.7 15.2  
120/1 Standard  
3.5  
GSTC Outdoor Rated Amps  
Voltage/Phase  
GSTC/GSP Rated Amps  
Voltage/Phase  
22.6  
21.0  
GSTC Outdoor Rated Amps  
Voltage/Phase  
10-00  
Page 2  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 1. GS Indoor Series  
Figure 2. GS Outdoor Series  
10-00  
Page 3  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 3. GSTC Key Pad  
Figure 4. GSP Key Pad  
10-00  
Page 4  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 2. Standard Features  
Standard Features  
GSTC  
GSP*  
Steam Capacity adjustment  
x
Full size alphanumeric display and keypad  
Total Controller with Modbus host protocol  
Transducer signal acceptance  
Individual component diagnostic capability  
Keypad set-point adjustment (humidity)  
Display of relative humidity  
x
x
x
x
x
x
Low and high relative humidity alarms  
Adjustable drain with no call for humidity  
Keep warm feature  
x
x
x
Networking capability up to 10 units  
Pre-cleaning sequence  
x
x
Troubleshooting Guide  
x
Self diagnostic capabilities  
x
Fault history  
x
Smart drain water cooling  
x
On/off cycling prevention  
x
Full tank blowdown capability via timer or external trigger  
Board mounted display for fault and demand indication  
Parameter change through jumper settings  
Remote fault indication  
Single or Dual modulation signal acceptance  
Industry standard modulation signal acceptance  
Time to next maintenance alarm  
Internal Drain water cooler  
System demand indication  
Output display  
Precise five level water level indication  
Status indicator lamps  
Backlit display  
B or BH venting options  
BH stack vent (outdoor only)  
Large Side tank cleaning port  
Top access cleaning (300, 400, 500 & 600 lb models)  
Single water connections  
Turn-down ratio from maximum output to 25lbs/hr(11kg/hr)  
Time proportioning below 25lbs/hr(11kg/hr)  
120V or 208-240V power supply  
Freeze Protection (Outdoor only) See Section 10-30, Page 24.  
Integral enclosure (outdoor only)  
Nortec Links Building Management System capable using BACnet  
or LonWorks N2 protocols  
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
not req.  
keypad  
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
o
o
Nortec OnLine for web based monitoring and control  
Sealed combustion / Direct vent  
Floor stand  
o
o
o
o
o
Distribution Systems  
Short Absorption Manifold SAM-e  
Steam Distributor  
Blower Pack  
o
o
o
o
o
o
x = standard o = optional  
10-00  
Page 5  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THIS PAGE INTENTIONALLY LEFT BLANK  
10-00  
Page 6  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10-10  
OPERATION  
10-10  
Page 7  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. WATER MANAGEMENT – BETTER EFFICIENCY THAN EVER  
A. Introduction  
(1) The GS Series of humidifiers is equipped with a unique float chamber water level  
monitoring device. Two magnetic floats (one is a backup) measure 5 different water  
levels in the humidifier for proper operation. The float chamber and board are located  
away from the boiling action to increase reading accuracy and reduce mineral build-  
up since it is not in the boiling water.  
(2) The float chamber is connected to the tank under the water level and above the  
water level to ensure equalization of pressure between the tank and float chamber.  
In addition cooling water is introduced in the float chamber to reduce scale build-up.  
(3) The unit also includes an internal 1” air gap and a vacuum breaker to prevent  
siphoning effect.  
(4) On initial start-up, the solenoid operated fill valve fills the tank. The water level will  
reach the backup float first and then the main float. As a safety precaution, if the  
back-up and main float read a different water level at any time during the operation of  
the unit, the unit will shut down on a fault.  
(5) On initial start-up, the unit will fill to the top yellow position, and activate an internal  
test to confirm operation of the drain pump to ensure the drain is not blocked.  
(6) The drain pump is then activated until the water level goes down to the green middle  
level, and the combustion sequence will start upon a demand for humidity. During  
the steam production, the unit will also self-check if the floats and drain pump are  
operational by activating a drain sequence every 24 hours (adjustable to time of  
day).  
Figure 1. Humidifier Tank  
10-10  
Page 8  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model  
A
B
C
D
Vent Dia  
B Type  
Vent Dia  
BH Type  
Shipped  
Weight  
Operating  
Weight  
Steam Outlet  
Gas Supply  
in  
cm  
in  
cm  
52.8  
69  
in  
cm  
16  
in  
cm  
in  
cm  
in  
cm  
in  
cm  
lbs  
kg  
lbs  
kg  
in  
1 x  
1.75  
1 x  
3
1 x  
3
1 x  
4
1 x  
4
1 x  
4
cm  
1 x  
4.4  
1 x  
7.6  
1 x  
7.6  
1 x  
10.2  
1 x  
10.2  
(NPT)  
(NPT)  
GSTC  
100  
GSTC  
200  
GSTC  
300  
GSTC  
400  
GSTC  
500  
GSTC  
600  
20.8  
27.2  
42.7  
42.7  
58.3  
58.3  
6.3  
9.3  
23.6  
37.1  
37.1  
37.1  
36.6  
36.6  
16.1  
22.4  
38  
40.8  
56.8  
96.4  
96.4  
136  
136  
4
5
7
7
8
8
10.2  
12.7  
17.8  
17.8  
20.3  
20.3  
3
4
5
5
6
6
7.6  
267  
355  
485  
529  
659  
703  
121  
161  
220  
240  
299  
319  
423  
599  
192  
272  
440  
450  
619  
628  
0.5  
1.27  
1.91  
2.54  
2.54  
3.18  
3.18  
11.6  
10.9  
10.9  
7.4  
29.5  
27.8  
27.8  
18.7  
18.7  
14.6  
14.6  
14.6  
14.4  
14.4  
10.2  
12.7  
12.7  
15.2  
15.2  
0.75  
1
109  
109  
148  
148  
970  
38  
992  
1
53.6  
53.6  
1364  
1384  
1.25  
1.25  
1 x  
10.2  
7.4  
Figure 2. Physical Dimensions – GS Indoor Humidifier  
10-10  
Page 9  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 3. Physical Dimensions – GS Outdoor Humidifier  
10-10  
Page 10  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. Safety Water Level Control Check  
(1) To ensure safe operation, the humidifier constantly monitors the back up float of  
the humidifier and also performs float checks at regular intervals.  
C. Self Diagnostic  
(1) This feature allows the user to activate various hardware elements within the  
system to prove operational compliance.  
D. Energy Efficient Blowdown Sequence – Unique to Nortec  
(1) Fill valve and blow down sequences are based on steam production and not time  
of operation to increase efficiency of the unit. If the demand signal controls the unit  
at the minimum output, of 25 lbs/hr, only 25% of 25 lbs/hr will be drained.  
E. Internal Drain Water Tempering  
(1) The unique design for the internal Drain Water Cooler from NORTEC will ensure  
water tempering at all times of the water going to drain. The fresh fill water will  
completely mix with incoming hot water from the tank during blow down or drain  
cycles and ensure water does not exit the system at more then 140ºF (60ºC).  
(2) When the “SMART” feature is enabled on the TC version, the temperature of the  
tank is monitored and fresh cold water will be used only when drain water is above  
140ºF (60ºC).  
F. Capacity Turn Down  
(1) The GS humidifier is capable of full modulation of the output of each burner down  
to 25 lbs/hr. For example on a four-burner system, such as the GS 400, the  
turndown ratio is 6% of total output.  
(2) When the control signal requires less than 25 lbs/hr output, the internal controller of  
the unit takes over with a unique time proportioning algorithm and to control the  
output and modulate down to 0 lbs/hr.  
G. GSTC Unit Networking  
(1) The new TC controller of the GS Series allows staged modulation through  
networking of up to 10 units when higher capacities of steam require multiple units.  
The modulating signal will be wired to the master unit and this one will control the  
output of the other units for seamless modulation from 25 lbs/hr up to 6300 lbs/hr.  
All units will be configured as master or staged. The operational range of each unit  
will be set in the internal controller at the factory. A control modulation signal to the  
master unit and a three-wire connection between each unit being staged is all that  
is required.  
2. CONTROLS  
A. Introduction  
(1) The GSTC model features a backlit alphanumeric keypad for user interface, which  
allows for adjustment of operating parameters and displays system operating status.  
(2) The GSP model uses status indication lights.  
10-10  
Page 11  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(3) All control electronics are integral to humidifier cabinet and do not require separate  
cabinet on the humidifier.  
B. Remote Fault Indication  
(1) The GS Series provides output signals of the following type:  
(a) Humidifier “ON”  
(b) Humidifier “Active”  
(c) Humidifier “Service”  
(d) Humidifier “Fault”  
C. Modulating Controls  
(1) All models accept a single or dual channel input control signal(s) of the following  
type(s):  
(a) 0-20 mA  
(b) 4-20 mA  
(c) 0-5 VDC  
(d) 1-5 VDC  
(e) 0-10 VDC  
(f) 2-10 VDC  
(2) The GS Series can accept the following inputs:  
(a) Two different modulating inputs demand or transducer signal.  
(b) Full tank blowdown activation (24 VAC).  
D. On / Off Controls  
(1) Safety on/off controls are available from NORTEC as safety accessories. These  
controls are highly recommended by NORTEC for high limit or air proving. If controls  
were not ordered with the humidifier, they must be supplied by others.  
3. ELECTRICAL  
(1) Humidifiers require field wiring to primary voltage terminal blocks. The power  
requirement is a 120 or 208-240 V single-phase supply. Wiring is fed through a 7/8"  
hole on lower right hand side of control compartment.  
(2) External wiring sizes must be in accordance with NEC and/or CEC and existing local  
electrical codes and by-laws.  
4. VENTING  
(1) The GS Series of Gas Steam humidifiers offer tremendous venting capability.  
Whether you use galvanized B venting or special BH venting, the GS Series comes  
ready for field connection. Please make sure that the correct size of vent is used  
and follows local codes for proper operation of the unit.  
(2) Humidifiers can be vented up to 100 ft (30 m) equivalent without requiring power  
assistance . The GS Series can be vented horizontally through the wall or vertically  
10-10  
Page 12  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
through the roof without any special requirements when using BH venting. Required  
vent flue size depends on unit model. All connections to the flue pipes are made  
without having to open the humidifier cabinetry.  
(3) The GS Outdoor Series comes complete with BH vent, ready for easy assembly.  
5. CLEARANCES  
(1) The clearance dimensions shown in Figure 4 and 5 are for reference only and are  
the minimum requirements for maintenance of the humidifier.  
(2) All units have frontal cleaning port access.  
(3) For GS 100/200, frontal cleaning port access is required only. For GS 300/400, top  
access is accessible from the front without clearance on the left side. For GS  
500/600, left side clearance is required to allow cleaning of the back of the heat  
exchanger.  
10-10  
Page 13  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 4. GSTC/GSP Indoor Clearance  
Figure 5. GSTC Outdoor Clearance  
10-10  
Page 14  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. STEAM INSTALLATION GUIDELINES  
(1) The GS Series humidifier comes with a single steam outlet on all capacities. The GS  
100, 200/300, 400/500/600 have respectively (1.75” (4.4 cm) O.D., 3” (7.6 cm) O.D.  
and 4” (10.16) O.D.). Consult option and accessories section for more details. Refer  
to the Steam Absorption and Distribution Manual, Form #XX-231 for design of the  
steam distribution system.  
7. CALCULATION OF ANNUAL OPERATING COSTS  
A. Natural Gas Humidifier  
(1) Annual operating cost equals: annual hours of operation, times energy cost, times  
humidifier capacity.  
(a) Example: GS 100  
(b) Natural gas cost $4.50 (U.S.) per million BTU  
(c) $0.45 (U.S.) per Therm (100,000 BTU)Annual hours of operation = 2000 at full  
output (Equivalent to comfort humidification in upper mid-west.)  
(d) Input of humidifier = 140,000 BTU/hr  
(e) Total energy used = 2000 x 140,000 = 280,000,000 BTU  
(f) Annual Cost = 238 x 4.50 = $1260.00  
B. Electric Gas Humidifier  
(1) Annual operating cost equals: annual hours of operation, times energy cost, times  
humidifier capacity.  
(a) Example: NHMC 100  
(b) Electricity cost (usage charge) $0.08 per kw/hr.  
(c) Annual hours of operation = 2000 at full output (Equivalent to comfort  
humidification in mid-west.)  
(d) Input of humidifier = 34 kw  
(e) Total energy used = 2000 x 34 = 68,000 kw/hr  
(f) Annual Cost = 68,000 x 0.08 = $5,440.00  
C. Operating Cost Savings  
(1) Gas vs Electric = more than 4 times the operating cost.  
10-10  
Page 15  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THIS PAGE INTENTIONALLY LEFT BLANK  
10-10  
Page 16  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10-20  
MAINTENANCE  
10-20  
Page 17  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. WATER CONDITIONS VS. HUMIDIFIER CLEANING REQUIREMENTS  
(1) The GS Series humidifiers are to operate on cold potable, De-Ionized (DI) or  
Reverse-Osmosis (RO) water supply and since the output of all GS Series  
humidifiers is pure clean steam, minerals from the incoming water are left behind.  
These minerals will eventually coat the tank walls or settle to the bottom of the  
tank. The mineral content of the incoming water, the unit running time, output  
capacity setting and blowdown rate ultimately determine time between each  
cleaning.  
(2) The Gas Steam humidifier will periodically “blowdown” or skim water from the tank  
to reduce the concentration of total dissolved solids that accumulate during long-  
term operation. The Gas Steam humidifiers are shipped from the factory set at  
25% of output. This setting ensures that scale build-up will be minimized for most  
water conditions. The amount of blowdown is field adjustable.  
(3) The unit also monitors operation time and will indicate to the user when  
maintenance is required. This time is adjustable to adapt to your water conditions  
but is set from the factory at 500 hours of 100% operation.  
(4) Three parameters will help determine the proper blowdown setting of the Gas  
Steam humidifier.  
(a) Water hardness  
(b) Silica content  
(c) Chlorides  
(5) Due to the wide range of water conditions found throughout North America it is  
important that the blowdown is set according to the local water conditions. By  
water conditions we are referring to the hardness of the water supplied to the  
humidifier. The hardness is measured in grains per gallon. It is also important to  
test for silica content. Silicates may cause foaming and contribute to scale buildup  
in the humidifier tank and float chamber. When excessive foaming occurs. Consult  
factory for possible solutions.  
(6) If you are unaware of the hardness or silica content of your water supply, there  
are many “do it yourself” kits, which can be purchased, or there are several  
companies that will perform the tests for a reasonable price. You can even contact  
your municipality for your water condition.  
(7) It is possible to reduce this setting according to observation and guidelines in the  
blowdown setting table found in the GS Installation Manual (Form # XX-287). Also,  
when high silica content has been identified, the humidifier tank and float chamber  
will require increased maintenance and the blowdown setting should be increased  
to maximum setting. In this case silica content may determine the appropriate  
blowdown setting.  
(8) Softened water is recommended if the incoming water has a hardness in excess of  
8 grains/gal (136 ppm).  
(9) Reverse osmosis (RO) water can provide very long times between cleaning since  
it is cleaner than softened water. Deionized (DI) water can reduce the  
10-20  
Page 18  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
maintenance a step further than RO and all the GS Series components are ready  
for RO or DI water use as a standard.  
(10) Contact your local Nortec representative for a quotation of a water treatment  
system suited for your application.  
2. PREVENTIVE MAINTENANCE  
(1) The installation manuals of the GS Series of Gas Steam humidifier come with a  
complete Maintenance chart in order to guide internal personnel in cleaning and  
monitoring activities. Like any other appliance the Gas-Steam humidifier requires  
monitoring to ensure efficient operation throughout the life of the unit.  
(2) While in operation, the unit will blowdown scaled water through a drain pump  
keeping control on the water concentration based on steam output. For longer  
intervals between cleaning, the unit may be completely drained down to reduce the  
mineral concentration and bring in new fresh water in the system.  
(3) The FTBD (Full Tank Blow Down) can be activated through the software or dip  
switches based on:  
(a) Time of day setting. When the 25 - 400 hours interval (adjustable ) is reached  
the unit will wait until the set time of day before activating the full tank  
blowdown.  
(b) External trigger using 24Vac signal from the building management system to  
the input terminal of the humidifier.  
(4) Following the full tank blowdown, the unit will refill and perform a float check.  
Whenever possible, use this feature to reduce mineral accumulation in the system  
and reduce the time required to clean the interior of the reservoir.  
3. PRE-CLEANING SEQUENCE  
(1) When cleaning of the reservoir is required, use the tank pre-clean feature. This  
pre-cleaning sequence will drain the full content of the unit, fill back-up, and re-  
drain any residual scale that has fallen from the cold water refilling. This sequence  
is not an alternative to cleaning the humidifier, it is meant to reduce the time  
required to clean the tank.  
(2) Full Size Frontal Opening: Every GS Series Gas Steam Humidifier comes  
complete with a full size frontal opening to allow bottom cleaning of the tank and  
heat exchanger. This opening allows quick and easy cleaning without removing  
the steam outlet of the unit.  
10-20  
Page 19  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THIS PAGE INTENTIONALLY LEFT BLANK  
10-20  
Page 20  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10-30  
OPTIONS &  
ACCESSORIES  
10-30  
Page 21  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. OPTIONS AND ACCESSORIES AVAILABLE  
A. Nortec Modulating Humidistat with Digital Display  
(1) NORTEC humidistats for GSTC or GSP Gas Steam humidifiers feature  
proportional + integral control with setpoint range of 10-95% RH. The humidistat  
connects directly to the low voltage terminal strip via 3 wires (shielded if run  
exceeds 10 m). The humidistat accurately controls RH in a zone or space.  
(2) Humidistat Specifications:  
(a) Operating Conditions: 41ºF-122°F (5°C-50°C)  
(b) Control: 0-95% RH non-condensing  
(c) Sensor: 0-100% RH  
(d) Humidity Sensor: Solid-state humidity sensor. Suitable for normal, clean air.  
Not to be used in corrosive or harmful environment.  
(e) Resolution: +- 0.1%  
(f)  
Repeatability: 0.5%  
(g) Accuracy of Sensor: +/- 3% RH from 0-100% RH Range: 10-90% RH for  
32°F-122°F (0°C-50°C)  
(h) Temperature Effect: 0.05% /°F  
(i)  
(j)  
Outputs: 0-10 VDC  
Power: 24 VAC -15%, +10% 50/60 Hz; 2 VA  
B. Humidistat with Integral Sensor and Controller with Digital Display  
(1) 151-0142 - Modulating 0-10 VDC wall mounted humidistat, P + I control humidistat  
with setpoint range of 0-95% RH. Connects directly to the GSTC or GSP low  
voltage terminal strip via 2 wires (shielded if run exceeds 10 m) and accurately  
controls RH in a zone or space. Time proportioning control not acceptable.  
(2) 252-0266 - Modulating 0-10 VDC duct mounted humidistat, P + I control humidistat  
with setpoint range of 10-95% RH. Connects directly to the GSTC or GSP low  
voltage terminal strip via 2 wires (shielded if run exceeds 10 m) and accurately  
controls RH in a zone or space. Can be used as a control humidistat if placed in  
return air or as high limit if placed in supply. (Time proportioning control not  
acceptable.)  
C. Humidistat with Integral Sensor  
(1) 150-9857 - Remote duct or modulating high limit sensor.  
(2) 150-9858 - Remote wall mounted sensor.  
(3) 252-0263 - Outdoor duct mounted temperature sensor. Can provide energy  
savings and prevent window condensation by reading outdoor temperature and  
resets the humidity control to prevent condensation.  
10-30  
Page 22  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
D. Nortec On / Off Controls with Digital Display  
(1) 252-0273 - Duct Mounted Safety High Limit On/Off Humidistat (if used) is wired to  
make on drop in humidity, break on rise to safety setpoint. It should be set to  
approximately 85% RH as a safety to prevent saturation and wetting in the duct.  
(2) 132-9203 - A Duct Mounted Safety Air-Proving On/Off Switch (if used) is wired to  
make on airflow, break on no flow. It is used as a safety to prevent saturation  
when no air is flowing through the duct.  
(3) Low Humidity Alarm Package - Low limit on/off humidistat duct or wall mounted,  
alarm light with engraved faceplate sized to fit standard 2” x 3” recessed electrical  
wall box supplied by others. Activates alarm light if duct or room airdrops below  
setpoint.  
(a) Duct – 253-3365  
(b) Wall – 253-3366  
(4) High Humidity Alarm Package - High limit on/off humidistat duct or wall mounted,  
alarm light with engraved faceplate sized to fit standard 2” x 3” recessed electrical  
wall box supplied by others. Stops humidifier and activates alarm light if duct or  
room air approaches saturation.  
(a) Duct – 253-3363  
(b) Wall – 253-3364  
E. Configuration Option  
(1) 150-7057 - This option allows the Gas Steam humidifier to operate using propane  
energy.  
F. Direct Vent  
(1) GS Indoor Direct Vent Package allows GS unit to be installed in an environment  
where the air cannot be used for combustion for one of the following reasons:  
chemicals or excessive dust is present in the air or the room is under excessive  
negative or positive pressure. All these factors could affect adversely the normal  
operation of the unit.  
(a) GS 100 - 150-7067  
(b) GS 200 - 150-7068  
(c) GS 300 - 150-7069  
(d) GS 400 - 150-7070  
(e) GS 500 - 150-7071  
(f)  
GS 600 - 150-7072  
G. Stand  
(1) GS Series Stands are optional with all models. The floor stands will help raise the  
unit to maximum of 27” (69 cm) high.  
H. Keep Warm  
(1) 150-7059 - GSP Keep Warm Feature, allow water temperature in the tank to be  
maintained between 140ºF (60ºC) and 160ºF (71ºC) allows for quick response of  
the unit on a call for humidity and to reduce possible bacteria growth for health  
concerns.  
10-30  
Page 23  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
I. Indoor Freeze Protection  
(1) 150-7058 - GSTC Indoor Freeze protection package provides the unit configured  
with keep warm feature, remote fault indication and a normally open drain valve to  
protect if freezing conditions may occur. The keep warm feature will ensure the  
water temperature is kept between 140ºF (60ºC) and 160ºF (71ºC).  
(2) The remote fault indication will allow service personnel to be advised of the unit’s  
operational status and the normally open drain valve will ensure the unit is drained  
if a power outage.  
(3) Drain and fill lines outside of the cabinet, must be protected from freezing with heat  
trace. Unit must be enclosed in a weather enclosure with heat source.  
(4) A remote alarm must be installed in case the unit faults using remote fault  
indication and status indication.  
J. Outdoor Freeze Protection (Standard with all GS Outdoor Enclosures)  
(1) Outdoor units are configured with the Keep Warm feature enabled to maintain the  
tank water temperature between 140ºF (60ºC) and 160ºF (71ºC). Included is a  
factory installed normally open drain valve that will ensure the unit drains in the  
event of a power outage. Also a factory-installed heater will be included to  
maintain an operating temperature range within the electrical compartment. The  
heater is powered from the humidifier. Field supplied heat-tracing needs to be  
installed on all fill line piping exposed to outdoor temperature. If fill line pipe  
freezing is a concern a field supplied normally open valve can be used to drain the  
fill line.  
(a) 150-8116 - GSTC Outdoor 100  
(b) 150-8117 - GSTC Outdoor 200  
(c) 150-8118 - GSTC Outdoor 300/400  
(d) 150-8119 - GSTC Outdoor 500/600  
K. ON-LINE  
(1) Nortec OnLine is a remote interactive communication package that allows satellite  
contacts to monitor, maintain and control a humidification center from any location  
worldwide using standard internet connections. This advanced software shows  
graphic representations of the humidifier and its key parameters (up to 75  
functions).  
L. LINKS 2  
(1) Nortec LINKS 2 is the combination of LINKS (building management system  
communication hardware) and OnLine (Internet communication hardware) allowing  
humidifiers to communicate to a building management system (BMS) as well as  
the Internet. Up to 8 humidifiers can be connected to 1 LINKS 2 controller (1  
master and 7 slaves). The controller is factory installed and is located internally to  
the humidifier. Simply specify at the time of order the operating protocol needed.  
LINKS 2 comes standard with Internet capabilities however OnLine service needs  
to be specified at time of order.  
(2) Operating Protocols:  
a)  
252-7116 – BACnet / IP  
10-30  
Page 24  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
b)  
c)  
d)  
252-7111 - BACnet MSTP  
252-7113 – Johnson N2  
252-7113 – LonWorks  
(3) Features  
a)  
b)  
c)  
d)  
e)  
f)  
Digital Feedback for unit standby/humidifying mode.  
Digital feedback for service required.  
Digital feedback for fault indication.  
System demand display.  
Control room setpoint.  
Control high limit setpoint.  
g)  
h)  
i)  
Control room %RH.  
Control high limit %RH.  
Control enable/disable.  
j)  
Networking capabilities of linking 8 units to one Nortec controller.  
Figure 1. NORTEC Online  
Figure 2. NORTEC LINKS 2  
10-30  
Page 25  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
M. DRAIN WATER SUMP PUMP  
(1) Externally mounted below humidifier. For use when no floor drain is available and  
water must be pumped higher than the bottom of the humidifier (special high  
temperature model). Rated for use with all GS models. Recommended model:  
W.W. Grainger #4RD29 or #4RD32.  
N. STEAM DISTRIBUTION  
(1) Used in ducts or air handling units, available in stainless steel.  
(2) Steam is dispersed through evenly spaced outlet orifices and upward  
perpendicular to the airflow.  
(3) When steam is dispersed through evenly spread outlet orifices that are along the  
steam distributors “active zone”. They are offset 45º from vertical to address  
potential static pressure induced by downward airflow. The distributor is rotated  
when installed.  
O. REMOTE MOUNTED BLOWER PACK  
(1) RMBP 208-240V- 1709701 Blower Pack  
(2) Direct steam distribution system that allows for direct space/room humidification  
when steam introduction into a ducted system is not feasible. The factory  
assembled Blower Pack includes integral steam distributor, an internal steam hose  
and condensate connection for simple installation including 3 individual 110 cfm  
blower fans that can be powered by a separate 115 V single phase power supply  
or can be ordered with a factory installed step down transformer for all standard  
primary voltages. The Blower Pack features an adjustable fan to provide different  
angles allowing for a flexible install. A temperature sensor enables fans when  
steam production begins, while maintaining a quiet operational environment. The  
Remote Mounted Blower Pack ships fully assembled and ready for easy  
installation with NH, GS, SE Technologies.  
(3) See Blower Pack distribution for more information.  
P. SHORT ABSORPTION MANIFOLD  
(1) See Short Absorption Manifold Engineering Manual for model numbers.  
10-30  
Page 26  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 3. Steam Distributor  
Figure 4. Blower Pack  
Figure 5. Short Absorption Manifold  
10-30  
Page 27  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THIS PAGE INTENTIONALLY LEFT BLANK  
10-30  
Page 28  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10-40  
SPECIFICATION  
10-40  
Page 29  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. GENERAL  
A. General  
(1) NORTEC GS Series Gas-Fired Humidifier[s] as indicated on drawing[s] and as  
indicated on schedule[s].  
(2) Complete and operable humidification system [which meets applicable building  
codes].  
(3) Equipment start-up and project inspection by qualified factory trained  
representative.  
B. Quality Assurance  
(1) Manufacturer: For each product specified, provide components by same  
manufacturer throughout.  
(2) Electrical Components, Devices, and Accessories: Listed and labeled as defined  
in NFPA 70, Article 100, by a testing agency acceptable to authority having  
jurisdiction, and marked for intended use.  
(3) Comply with ARI 640, “Standard for Commercial and Industrial Humidifiers.”  
(4) Products shall be supported with a warranty that ensures the product will be free  
from defects in materials and workmanship for a period of two years after  
shipment.  
(5) Commissioning of a system or systems specified in this section is part of the  
construction process. Documentation and testing of these systems, as well as  
training of the Owner’s operation and maintenance personnel, is required in  
cooperation with the Commissioning Authority. Project Closeout is dependent on  
successful completion of all commissioning procedures, documentation, and issue  
closure. Refer to Project Closeout, Section 01700, for substantial completion  
details. Refer to Section 01810, Commissioning, for detailed commissioning  
requirements.  
(6) Products specified below are to be manufactured is an ISO 9001-2000 certified  
facility.  
C. Submittals  
(1) Submit product data under provisions of Section 15010. Include product  
description, model, dimensions, component sizes, rough-in requirements, service  
sizes, and finishes. Include rated capacities, operating weights, furnished  
specialties, and accessories.  
(2) Submit manufacturer’s installation instructions.  
(3) Submit operation and maintenance data.  
(4) Submit coordination drawings. Detail fabrication and installation of humidifiers.  
Include piping details, plans, elevations, sections, details of components, and  
dispersion tubes. Detail humidifiers and adjacent equipment. Show support  
locations, type of support, weight on each support, and required clearances.  
(5) Submit wiring diagrams including power, signal, and control wiring. Differentiate  
between manufacturer-installed and field-installed wiring.  
10-40  
Page 30  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(6) Submit minimum water quality requirements and water pressure requirements.  
D. Extra Materials  
(1) Furnish extra materials described below that match products installed and that are  
packaged with protective covering for storage and identified with labels describing  
contents.  
E. References  
(1) ANSI/NFPA 70 - National Electrical Code.  
F. Coordination  
(1) Coordinate location and installation of humidifiers in ducts and air-handling units.  
Revise locations and elevations to suit field conditions and to ensure proper  
humidifier operation.  
XXXXX OR XXXXX  
(2) Coordinate location and installation of humidifier in the space it serves with the  
electrical, mechanical, and plumbing contractors.  
2. PRODUCTS  
A. Gas Fired Steam Humidifier - GSTC  
(1) Packaged unit, floor mounted, gas-fired, steam generating system available at 105  
lbs/hr (48 kg/hr), 210 lbs/hr (95 kg/hr), 315 lbs/hr (143 kg/hr), 420 lbs/hr (191  
kg/hr), 525 lbs/hr (238 kg/hr), 630 lbs/hr (286 kg/hr), suitable for immediate, or  
future, use of all water types including, De-Ionized (DI), Reverse Osmosis (RO),  
potable and softened water, without modification required, CSA certified.  
(2) Packaged unit, wall mounted, methods of distribution require a steam distributor[s]  
or Short Absorption Manifold [s] [SAM-e] for mounting into AHU/duct[s] or Remote  
Mounted Blower Pack[s] [RMBP] for direct space applications [refer to options  
schedule].  
(3) Enclosed cabinet, powder painted steel construction and air gap between cabinet  
and insulated humidifier tank ensures safe surface temperature.  
(a) Evaporation tank and all internal tank components to be constructed of 304  
stainless steel.  
(b) Humidifier requires zero clearance to combustibles and shall be installed  
against a partition to minimize floor space required. All tank surfaces shall be  
insulated with minimum 1" (25 mm) thick insulation and enclosed within unit  
cabinetry to ensure safe surface temperature, high overall efficiency, and fast  
unit response time. Units with exposed insulation shall not be acceptable.  
(c) Maintenance shall not require the removal of the steam lines.  
(d) Standard internal drain water cooler to ensure drain water tempering to 140º  
F (60 ºC). If external drain water cooler required, provide factory cross-braced  
unit stand and factory supplied stainless steel p-trap.  
(e) Blow-down p-trap, factory installed, enclosed in cabinet, prevents steam  
leakage to drain. Field installation not acceptable.  
10-40  
Page 31  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(f)  
Provide easily accessible, primary voltage terminal block, internal to  
cabinetry, for single point field connection of electrical supply.  
(g) Single point connection for gas inlet must be provided. Internal piping from  
gas inlet to burners must be factory installed and tested. Field piping from  
the gas inlet to the burners is not allowed.  
(h) Humidifier to prevent “back-siphoning” using an internal air gap for supply  
water, to meet local plumbing codes.  
(i)  
Drain line to include a vacuum breaker to prevent siphon drainage of the  
tank.  
(j)  
Allowance for combustion air shall be provided in cabinet ventilation design.  
Option for direct vent of combustion must be available for use with BH  
exhaust vent.  
(4) Gas appliance shall be low emission. Units with Carbon Monoxide (CO) levels  
higher than 10 ppm and Nitrous Oxide (NOx) levels above 40 ppm are not  
acceptable.  
(a) System shall be rated as a class I appliance certified for use with exhaust  
vent type B.  
XXXXX OR XXXXX  
(b) System shall be rated as a class III appliance certified for use with exhaust  
vent type BH.  
XXXXX OR XXXXX  
(c) System shall be rated as a class III appliance certified for use with exhaust  
vent type BH and use with direct vent of combustion air. (Must be specified  
for factory configuration)  
(5) Stainless Steel combustion chamber(s)/heat exchanger(s) shall have flat surfaces  
to retard scale build-up. Tubular heat exchangers are not acceptable.  
(a) Each burner, capable of true modulation will provide steam production of 25  
to 105 lbs/hr (11 to 48 kg/hr). Time proportioning modulation is not  
acceptable.  
(b) Units with multiple heat exchangers, models 210 to 630 lbs/hr (95 kg/hr to  
286 kg/hr) must be capable of producing a minimum output of 25 lbs/hr  
(11kg/hr).  
(c) Units with multiple heat exchangers, models 210 to 630 lbs/hr (95 kg/hr to  
286 kg/hr) must alternate the lead burners (duty cycle) to promote equal  
usage.  
(d) Gas system with gas valve(s), explosion proof, premix combustion air  
blower(s), microprocessor controlled ignition, flame sensing and fault  
indicator light(s), 100% premix infrared burner(s), hot surface igniters(s) and  
heat transfer efficiency maintained over all operating ranges.  
10-40  
Page 32  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(e) Blower speed rotation must to be monitored to ensure proper control of input  
modulation. System will lock out gas valve operation if proper blower speed  
is not detected.  
(f)  
A secondary combustion air safety, in addition to blower speed monitoring,  
utilizing a mechanical pressure differential switch, must be used with each  
blower to ensure combustion air is entering the pre-mix blower properly.  
(g) Modular heat exchanger shall be easily removable through unit sidewall.  
(h) Removable cover at front of unit facilitates easy cleaning (when applicable)  
with complete access to tank and heat exchanger surfaces.  
(6) Automatic water level control within a separate float chamber, isolated from the  
boiling action, to prevent false water level indication.  
(a) Fill rate must modulate to match capacity demand to ensure consistent  
output. Fill cycles based on low water only is not acceptable.  
(b) System shall fill through the bottom of the tank to reduce steam-quenching  
effect and noise level. Filling at top of the tank is not acceptable.  
(c) Unit water level is to be continuously monitored with a dual magnetic  
electronic float system, located outside of the boiling water to ensure  
accurate water level control and reduced maintenance. Cool fill water is to be  
supplied into the sensing chamber to keep the device cool. Systems using  
conductivity probes or floats located within hot reservoir water are not  
acceptable.  
(d) Tank and float chamber to be separated with a minimum of 1" (25 mm) rigid  
insulation, minimizing potential scale build up on float mechanisms, due to  
heating of the contained water.  
(e) Humidifier shall have a dual fill valve to feed water to the tank and float  
chamber, to reduce scaling and mineral build up on the magnetic floats.  
(f)  
Float chamber to include LED indication of five possible water level  
indications.  
(g) Ongoing self-diagnostics including periodic float operation and fill/drain rate  
verification.  
(h) Positive drainage/blow-down using a drain pump, drawing water from the  
bottom of the tank, maximizing mineral evacuation (when applicable).  
Skimmer not acceptable.  
(i)  
Blow down interval shall be based on actual steam production, and must be  
adjustable to compensate for all water conditions, to ensure maximum energy  
and maintenance efficiency.  
(j)  
Pre-cleaning flushing feature shall be provided to reduce maintenance time.  
(k) Must include end of season blow-down feature to evacuate contained water  
and minerals after 72 hours with no demand for humidification.  
10-40  
Page 33  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(7) Factory mounted, full size, backlit, Liquid Crystal Display provides full operational  
status. Display to include a keypad for user interface and adjustment of operational  
parameters including:  
(a) Unit output (lbs/hr or kg/hr) 25 lbs/hr to full output.  
(b) Water level in the tank.  
(c) Modulating control demand status.  
(d) On/off control and safety (High limit, air proving) circuit status.  
(e) Actual room and/or duct RH, and humidity set point, when using transducer  
input(s).  
(f)  
Controller configuration (Proportional band and integral) when using  
transducer input(s).  
(g) Troubleshooting guide with scroll down menu.  
(h) Fault indication including date and time history.  
(i)  
(j)  
Maintenance intervals.  
Fill and drain status.  
(k) Drain/flush intervals and duration.  
(l) Date and time.  
(m) Capacity limitation.  
(n) 72 hours drain enable/disable.  
(o) Control type configuration on/off or full modulation when demand signal(s), or  
transducer input(s) are provided.  
(p) Up to 10 humidifiers, supplying one AHU or area, can be controlled in series  
from one modulating humidity control system.  
(q) BACnet, LonWorks, or Johnson N2 capable to interface for monitoring and  
control from a Building Management System (BMS/BAS).  
(r) Total Controller is Modbus native for (BMS/BAS) communication for remote  
monitoring and control of humidifier.  
(s) Web base capable via the Internet for remote monitoring or control of  
humidifier.  
NOTE:  
All operational parameters factory set to reduce field set-up time.  
(8) Standard of acceptance: NORTEC GSTC.  
(9) Optional accessories:  
(a) Refer to options schedule.  
10-40  
Page 34  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. EXAMINATION  
A. Examination  
(1) Examine ducts, air-handling units, and conditions for compliance with requirements  
for installation tolerances and other conditions affecting performance.  
(2) Examine roughing-in for piping systems to verify actual locations of piping  
connections before humidifier installation.  
(3) Proceed with installation only after unsatisfactory conditions have been corrected.  
B. Installation  
(1) Install humidifiers and steam dispersion panels per manufacturers’ instructions.  
(2) Seal humidifier dispersion-tube duct penetrations with flange.  
(3) Install with required clearance for service and maintenance.  
C. Testing  
(1) System verification testing is part of the commissioning process. Verification testing  
shall be performed by the Contractor and witnessed and documented by the  
Commissioning Authority. Refer to section 01810, Commissioning, for system  
verification tests and commissioning requirements.  
XXXXX OR XXXXX  
(2) Manufacturer’s Field Service: Engage a factory-authorized service representative  
to inspect field-assembled components and equipment installation, including piping  
and electrical connections. Report results in writing.  
(a) Leak Test: After installation, charge system and test for leaks. Repair leaks  
and retest until no leaks exist.  
(b) Operational Test: After electrical circuitry has been energized, start units to  
confirm proper unit operation. Remove malfunctioning units, replace with  
new units, and retest.  
(c) Test and adjust controls and safeties. Replace damaged and malfunctioning  
controls and equipment.  
10-40  
Page 35  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
D. Training  
(1) Training of the Owner’s operation and maintenance personnel is required in  
cooperation with the Commissioning Authority. Provide competent, factory  
authorized personnel to provide instruction to operation and maintenance  
personnel concerning the location, operation, and troubleshooting of the installed  
systems. The instruction shall be scheduled in coordination with the  
Commissioning Authority after submission and approval of formal training plans.  
Refer to System Demonstrations, section 01670, for contractor training  
requirements. Refer to section 01810, Commissioning, for further contractor  
training requirements.  
XXXXX OR XXXXX  
(2) Engage a factory-authorized service representative to train Owner’s maintenance  
personnel to adjust, operate, and maintain humidifiers.  
(a) Train Owner’s maintenance personnel on procedures and schedules for  
starting and stopping, troubleshooting, servicing, and maintaining equipment  
and schedules.  
(b) Review data in maintenance manuals. Refer to Division 1 Section “Contract  
Closeout.”  
(c) Review data in maintenance manuals. Refer to Division 1 Section “Operation  
and Maintenance Data.”  
(d) Schedule training with Owner, through Architect, with at least seven days  
advance notice.  
10-40  
Page 36  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THIS PAGE INTENTIONALLY LEFT BLANK  
10-40  
Page 37  
2008-10-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARRANTY  
(1) WALTER MEIER INC. and/or WALTER MEIER LTD. (hereinafter collectively referred  
to as THE COMPANY), warrant for a period of two years after installation or 30 months  
from manufacturer’s ship date, whichever date is earlier, that THE COMPANY’s  
manufactured and assembled products, not otherwise expressly warranted (with the  
exception of the cylinder), are free from defects in material and workmanship. No  
warranty is made against corrosion, deterioration, or suitability of substituted materials  
used as a result of compliance with government regulations.  
(2) THE COMPANY’s obligations and liabilities under this warranty are limited to furnishing  
replacement parts to the customer, F.O.B. THE COMPANY’s factory, providing the  
defective part(s) is returned freight prepaid by the customer. Parts used for repairs are  
warranted for the balance of the term of the warranty on the original humidifier or  
90 days, whichever is longer.  
(3) The warranties set forth herein are in lieu of all other warranties expressed or implied  
by law. No liability whatsoever shall be attached to THE COMPANY until said products  
have been paid for in full and then said liability shall be limited to the original purchase  
price for the product. Any further warranty must be in writing, signed by an officer of  
THE COMPANY.  
(4) THE COMPANY’s limited warranty on accessories, not of the companies manufacture,  
such as controls, humidistats, pumps, etc. is limited to the warranty of the original  
equipment manufacturer from date of original shipment of humidifier.  
(5) THE COMPANY makes no warranty and assumes no liability unless the equipment is  
installed in strict accordance with a copy of the catalog and installation manual in effect  
at the date of purchase and by a contractor approved by THE COMPANY to install  
such equipment.  
(6) THE COMPANY makes no warranty and assumes no liability whatsoever for  
consequential damage or damage resulting directly from misapplication, incorrect  
sizing or lack of proper maintenance of the equipment.  
(7) THE COMPANY retains the right to change the design, specification and performance  
criteria of its products without notice or obligation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
U.S.A.  
CANADA  
Authorized Agent:  
Walter Meier (Climate USA) Inc.  
Walter Meier (Climate Canada) Ltd.  
826 Proctor Avenue  
Ogdensburg, NY 13669  
TEL: 1-866-NORTEC-1  
EMAIL: [email protected] FAX: (613) 822-7964  
2740 Fenton Road  
Ottawa, ON K1T 3T7  
TEL: 1-866-NORTEC-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Miele Dishwasher 10014080 User Manual
Milwaukee Caulking Gun 6560 Series User Manual
Munchkin Doll CCD 0113 001 REV1 User Manual
Nilfisk ALTO Vacuum Cleaner 46 53 User Manual
Nortel Networks Network Card BSG12aw User Manual
Omega Speaker Systems Thermometer DFG81 User Manual
OTC Wireless Switch switch hub User Manual
Panasonic Air Conditioner CS E12JKKW 1 User Manual
Panasonic Fax Machine KX FL503HK User Manual
Parkinson Cowan Cooktop U02021 User Manual