GS Series
GSTC/GSP Indoor
GSTC Outdoor
Engineering Manual
1503540-C
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
Subject
Page
10-00 PRINCIPLE OF OPERATION
1.
PRINCIPLE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
COMBUSTION SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
A.
10-10 OPERATION
1.
WATER MANAGEMENT - BETTER EFFICIENCY THAN EVER . . . . . . . . . . . . . . . . . . . . . . . . . . 8
A.
B.
C.
D.
E.
F.
G.
INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
SAFETY WATER LEVEL CONTROL CHECK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
SELF DIAGNOSTIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
ENERGY EFFICIENT BLOWDOWN SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
INTERNAL DRAIN WATER TEMPERING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
CAPACITY TURN DOWN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
GSTC UNIT NEWTWORKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
REMOTE FAULT INDICATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
MODULATING CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ON/OFF CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ELECTRICAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
VENTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
STEAM INSTALLATION GUIDELINES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
CALCULATION OF ANNUAL OPERATING COSTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
NATURAL GAS HUMIDIFIER. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
ELECTRIC GAS HUMIDIFIER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
OPERATING COST SAVINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.
A.
B.
C.
D.
3.
4.
5.
6.
7.
A.
B.
C.
10-20 MAINTENANCE
1.
2.
3.
WATER CONDITIONS VS. HUMIDIFIER CLEANING REQUIREMENTS . . . . . . . . . . . . . . . . . . 18
PREVENTIVE MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
PRE-CLEANING SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
10-30 OPTIONS & ACCESSORIES
1.
OPTIONS AND ACCESSORIES AVAILABLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
NORTEC MODULATING HUMIDISTAT WITH DIGITAL DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
HUMIDISTAT WITH INTEGRAL SENSOR AND CONTROLLER WITH DIGITAL DISPLAY . . . . . . . . . 22
HUMIDISTAT WITH INTEGRAL SENSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
NORTEC ON/OFF CONTROLS WITH DIGITAL DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
CONFIGURATION OPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
DIRECT VENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
STAND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
KEEP WARM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
INDOOR FREEZE PROTECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
OUTDOOR FREEZE PROTECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
K.
L.
ON-LINE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
LINKS 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
OUTDOOR 120 VAC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
DRAIN WATER SUMP PUMP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
STEAM DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
REMOTE MOUNTED BLOWER PACK. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
SHORT ABSORPTION MANIFOLD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
M.
N.
O.
P.
Q.
10-40 SPECIFICATION
1.
GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
A.
B.
C.
D.
E.
QUALITY ASSURANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
SUBMITALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
EXTRA MATERIALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
REFERENCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
COORDINATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
2.
3.
PRODUCTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
A.
GAS FIRED STEAM HUMIDIFIER - GSTC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
EXAMINATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
EXAMINATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
TESTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
TRAINING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
A.
B.
C.
D.
WARRANTY
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
LIST OF FIGURES
Figure
Page
10-00 PRINCIPLE OF OPERATION
Figure 1.
Figure 2.
Figure 3.
Figure 4.
GS Indoor Series. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
GS Outdoor Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
GSTC Key Pad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
GSP Key Pad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
10-10 OPERATION
Figure 1.
Figure 2.
Figure 3.
Figure 4.
Figure 5.
Humidifier Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Physical Dimensions - GS Indoor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Physical Dimensions - GS Outdoor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
GSTC / GSP Indoor Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
GSTC Outdoor Clearance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
10-30 OPTIONS & ACCESSORIES
Figure 1.
Figure 2.
Figure 3.
Figure 4.
Figure 5.
NORTEC LINKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
NORTEC OnLine. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Steam Distributor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Blower Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Short Absorption Manifold. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
LIST OF TABLES
Table
Page
10-00 PRINCIPLE OF OPERATION
Table 1.
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Table 2.
Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
THIS PAGE INTENTIONALLY LEFT BLANK
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
10-00
PRINCIPLE OF
OPERATION
10-00
Page 1
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
1. PRINCIPLE OF OPERATION
A. Combustion System
(1) The combustion system is based on a fully modulating forced draft combustion air
blower, a negative pressure regulated gas valve, and a 100% premix burner. On a
call for humidity, the combustion air blower starts and creates a negative pressure
across an orifice located at the air inlet.
(2) The blower is energized to purge the system, then the hot surface igniter is activated.
During this time the electronic ignition module does a diagnostic check of safety
systems including the air-proving switch, which senses the negative pressure at the
air inlet orifice. After the function of the safety systems has been verified, the gas
valve will open and the gas/air mixture is ignited by the hot surface igniter.
(3) If a flame is sensed by the flame sensor, the gas valve remains open and
combustion continues. If a flame is not sensed, the above sequence is repeated to a
maximum of three times after which the ignition module will lock out. The gas valve
maintains a constant ratio air to gas independent of blower speed or external
conditions. This air and fuel is thoroughly mixed in the blower and then forced
through the burner ports where ignition occurs.
(4) Hot products of combustion are forced through a baffle inside the heat exchanger
and then vented outside. The heat exchanger has a large flat surface to minimize
scale build-up and promote scale shedding to the bottom of the tank. This self-
cleaning action helps to maintain the efficiency of the heat exchanger while the
smooth surfaces allow for easy cleaning when necessary.
(5) The GS 100 has a single removable combustion chamber/heat exchanger. The
combustion system is duplicated on larger units with multiple chambers inside a
common tank.
Table 1. Technical Data
UNIT TYPE
GS 600
GS 500
25-525
11-238
700,000
206
SPECIFICATION
GS 100
25-105
11-48
GS 200 GS 300 GS 400
25-630
11-286
840,000
247
Rated Capacity: lbs/hr*
Rated Capacity: kg/hr*
Input BTU/hr max
25-210
11-95
25-315
11-143
25-420
11-191
140,000 280,000 420,000 560,000
Input kJ/hr max
41
1.1
3.2
2.1
6.3
82
124
165
Flue Emissions
Low CO (< 10 ppm) and Low (NOx <40 ppm)
5.2
11.5
10
4.3
10.6
8.4
GSTC/GSP Rated Amps
Voltage/Phase
1.9
4.0
3.7
7.4
2.7
208-240/1 Standard
6.9 7.7
208-240/1 Standard
5.3 6.8
120/1 Standard
13.7 15.2
120/1 Standard
3.5
GSTC Outdoor Rated Amps
Voltage/Phase
GSTC/GSP Rated Amps
Voltage/Phase
22.6
21.0
GSTC Outdoor Rated Amps
Voltage/Phase
10-00
Page 2
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 1. GS Indoor Series
Figure 2. GS Outdoor Series
10-00
Page 3
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 3. GSTC Key Pad
Figure 4. GSP Key Pad
10-00
Page 4
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2. Standard Features
Standard Features
GSTC
GSP*
Steam Capacity adjustment
x
Full size alphanumeric display and keypad
Total Controller with Modbus host protocol
Transducer signal acceptance
Individual component diagnostic capability
Keypad set-point adjustment (humidity)
Display of relative humidity
x
x
x
x
x
x
Low and high relative humidity alarms
Adjustable drain with no call for humidity
Keep warm feature
x
x
x
Networking capability up to 10 units
Pre-cleaning sequence
x
x
Troubleshooting Guide
x
Self diagnostic capabilities
x
Fault history
x
Smart drain water cooling
x
On/off cycling prevention
x
Full tank blowdown capability via timer or external trigger
Board mounted display for fault and demand indication
Parameter change through jumper settings
Remote fault indication
Single or Dual modulation signal acceptance
Industry standard modulation signal acceptance
Time to next maintenance alarm
Internal Drain water cooler
System demand indication
Output display
Precise five level water level indication
Status indicator lamps
Backlit display
B or BH venting options
BH stack vent (outdoor only)
Large Side tank cleaning port
Top access cleaning (300, 400, 500 & 600 lb models)
Single water connections
Turn-down ratio from maximum output to 25lbs/hr(11kg/hr)
Time proportioning below 25lbs/hr(11kg/hr)
120V or 208-240V power supply
Freeze Protection (Outdoor only) See Section 10-30, Page 24.
Integral enclosure (outdoor only)
Nortec Links Building Management System capable using BACnet
or LonWorks N2 protocols
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
not req.
keypad
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
o
o
Nortec OnLine for web based monitoring and control
Sealed combustion / Direct vent
Floor stand
o
o
o
o
o
Distribution Systems
Short Absorption Manifold SAM-e
Steam Distributor
Blower Pack
o
o
o
o
o
o
x = standard o = optional
10-00
Page 5
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
THIS PAGE INTENTIONALLY LEFT BLANK
10-00
Page 6
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
10-10
OPERATION
10-10
Page 7
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
1. WATER MANAGEMENT – BETTER EFFICIENCY THAN EVER
A. Introduction
(1) The GS Series of humidifiers is equipped with a unique float chamber water level
monitoring device. Two magnetic floats (one is a backup) measure 5 different water
levels in the humidifier for proper operation. The float chamber and board are located
away from the boiling action to increase reading accuracy and reduce mineral build-
up since it is not in the boiling water.
(2) The float chamber is connected to the tank under the water level and above the
water level to ensure equalization of pressure between the tank and float chamber.
In addition cooling water is introduced in the float chamber to reduce scale build-up.
(3) The unit also includes an internal 1” air gap and a vacuum breaker to prevent
siphoning effect.
(4) On initial start-up, the solenoid operated fill valve fills the tank. The water level will
reach the backup float first and then the main float. As a safety precaution, if the
back-up and main float read a different water level at any time during the operation of
the unit, the unit will shut down on a fault.
(5) On initial start-up, the unit will fill to the top yellow position, and activate an internal
test to confirm operation of the drain pump to ensure the drain is not blocked.
(6) The drain pump is then activated until the water level goes down to the green middle
level, and the combustion sequence will start upon a demand for humidity. During
the steam production, the unit will also self-check if the floats and drain pump are
operational by activating a drain sequence every 24 hours (adjustable to time of
day).
Figure 1. Humidifier Tank
10-10
Page 8
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
Model
A
B
C
D
Vent Dia
B Type
Vent Dia
BH Type
Shipped
Weight
Operating
Weight
Steam Outlet
Gas Supply
in
cm
in
cm
52.8
69
in
cm
16
in
cm
in
cm
in
cm
in
cm
lbs
kg
lbs
kg
in
1 x
1.75
1 x
3
1 x
3
1 x
4
1 x
4
1 x
4
cm
1 x
4.4
1 x
7.6
1 x
7.6
1 x
10.2
1 x
10.2
(NPT)
(NPT)
GSTC
100
GSTC
200
GSTC
300
GSTC
400
GSTC
500
GSTC
600
20.8
27.2
42.7
42.7
58.3
58.3
6.3
9.3
23.6
37.1
37.1
37.1
36.6
36.6
16.1
22.4
38
40.8
56.8
96.4
96.4
136
136
4
5
7
7
8
8
10.2
12.7
17.8
17.8
20.3
20.3
3
4
5
5
6
6
7.6
267
355
485
529
659
703
121
161
220
240
299
319
423
599
192
272
440
450
619
628
0.5
1.27
1.91
2.54
2.54
3.18
3.18
11.6
10.9
10.9
7.4
29.5
27.8
27.8
18.7
18.7
14.6
14.6
14.6
14.4
14.4
10.2
12.7
12.7
15.2
15.2
0.75
1
109
109
148
148
970
38
992
1
53.6
53.6
1364
1384
1.25
1.25
1 x
10.2
7.4
Figure 2. Physical Dimensions – GS Indoor Humidifier
10-10
Page 9
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 3. Physical Dimensions – GS Outdoor Humidifier
10-10
Page 10
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Safety Water Level Control Check
(1) To ensure safe operation, the humidifier constantly monitors the back up float of
the humidifier and also performs float checks at regular intervals.
C. Self Diagnostic
(1) This feature allows the user to activate various hardware elements within the
system to prove operational compliance.
D. Energy Efficient Blowdown Sequence – Unique to Nortec
(1) Fill valve and blow down sequences are based on steam production and not time
of operation to increase efficiency of the unit. If the demand signal controls the unit
at the minimum output, of 25 lbs/hr, only 25% of 25 lbs/hr will be drained.
E. Internal Drain Water Tempering
(1) The unique design for the internal Drain Water Cooler from NORTEC will ensure
water tempering at all times of the water going to drain. The fresh fill water will
completely mix with incoming hot water from the tank during blow down or drain
cycles and ensure water does not exit the system at more then 140ºF (60ºC).
(2) When the “SMART” feature is enabled on the TC version, the temperature of the
tank is monitored and fresh cold water will be used only when drain water is above
140ºF (60ºC).
F. Capacity Turn Down
(1) The GS humidifier is capable of full modulation of the output of each burner down
to 25 lbs/hr. For example on a four-burner system, such as the GS 400, the
turndown ratio is 6% of total output.
(2) When the control signal requires less than 25 lbs/hr output, the internal controller of
the unit takes over with a unique time proportioning algorithm and to control the
output and modulate down to 0 lbs/hr.
G. GSTC Unit Networking
(1) The new TC controller of the GS Series allows staged modulation through
networking of up to 10 units when higher capacities of steam require multiple units.
The modulating signal will be wired to the master unit and this one will control the
output of the other units for seamless modulation from 25 lbs/hr up to 6300 lbs/hr.
All units will be configured as master or staged. The operational range of each unit
will be set in the internal controller at the factory. A control modulation signal to the
master unit and a three-wire connection between each unit being staged is all that
is required.
2. CONTROLS
A. Introduction
(1) The GSTC model features a backlit alphanumeric keypad for user interface, which
allows for adjustment of operating parameters and displays system operating status.
(2) The GSP model uses status indication lights.
10-10
Page 11
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
(3) All control electronics are integral to humidifier cabinet and do not require separate
cabinet on the humidifier.
B. Remote Fault Indication
(1) The GS Series provides output signals of the following type:
(a) Humidifier “ON”
(b) Humidifier “Active”
(c) Humidifier “Service”
(d) Humidifier “Fault”
C. Modulating Controls
(1) All models accept a single or dual channel input control signal(s) of the following
type(s):
(a) 0-20 mA
(b) 4-20 mA
(c) 0-5 VDC
(d) 1-5 VDC
(e) 0-10 VDC
(f) 2-10 VDC
(2) The GS Series can accept the following inputs:
(a) Two different modulating inputs demand or transducer signal.
(b) Full tank blowdown activation (24 VAC).
D. On / Off Controls
(1) Safety on/off controls are available from NORTEC as safety accessories. These
controls are highly recommended by NORTEC for high limit or air proving. If controls
were not ordered with the humidifier, they must be supplied by others.
3. ELECTRICAL
(1) Humidifiers require field wiring to primary voltage terminal blocks. The power
requirement is a 120 or 208-240 V single-phase supply. Wiring is fed through a 7/8"
hole on lower right hand side of control compartment.
(2) External wiring sizes must be in accordance with NEC and/or CEC and existing local
electrical codes and by-laws.
4. VENTING
(1) The GS Series of Gas Steam humidifiers offer tremendous venting capability.
Whether you use galvanized B venting or special BH venting, the GS Series comes
ready for field connection. Please make sure that the correct size of vent is used
and follows local codes for proper operation of the unit.
(2) Humidifiers can be vented up to 100 ft (30 m) equivalent without requiring power
assistance . The GS Series can be vented horizontally through the wall or vertically
10-10
Page 12
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
through the roof without any special requirements when using BH venting. Required
vent flue size depends on unit model. All connections to the flue pipes are made
without having to open the humidifier cabinetry.
(3) The GS Outdoor Series comes complete with BH vent, ready for easy assembly.
5. CLEARANCES
(1) The clearance dimensions shown in Figure 4 and 5 are for reference only and are
the minimum requirements for maintenance of the humidifier.
(2) All units have frontal cleaning port access.
(3) For GS 100/200, frontal cleaning port access is required only. For GS 300/400, top
access is accessible from the front without clearance on the left side. For GS
500/600, left side clearance is required to allow cleaning of the back of the heat
exchanger.
10-10
Page 13
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 4. GSTC/GSP Indoor Clearance
Figure 5. GSTC Outdoor Clearance
10-10
Page 14
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
6. STEAM INSTALLATION GUIDELINES
(1) The GS Series humidifier comes with a single steam outlet on all capacities. The GS
100, 200/300, 400/500/600 have respectively (1.75” (4.4 cm) O.D., 3” (7.6 cm) O.D.
and 4” (10.16) O.D.). Consult option and accessories section for more details. Refer
to the Steam Absorption and Distribution Manual, Form #XX-231 for design of the
steam distribution system.
7. CALCULATION OF ANNUAL OPERATING COSTS
A. Natural Gas Humidifier
(1) Annual operating cost equals: annual hours of operation, times energy cost, times
humidifier capacity.
(a) Example: GS 100
(b) Natural gas cost $4.50 (U.S.) per million BTU
(c) $0.45 (U.S.) per Therm (100,000 BTU)Annual hours of operation = 2000 at full
output (Equivalent to comfort humidification in upper mid-west.)
(d) Input of humidifier = 140,000 BTU/hr
(e) Total energy used = 2000 x 140,000 = 280,000,000 BTU
(f) Annual Cost = 238 x 4.50 = $1260.00
B. Electric Gas Humidifier
(1) Annual operating cost equals: annual hours of operation, times energy cost, times
humidifier capacity.
(a) Example: NHMC 100
(b) Electricity cost (usage charge) $0.08 per kw/hr.
(c) Annual hours of operation = 2000 at full output (Equivalent to comfort
humidification in mid-west.)
(d) Input of humidifier = 34 kw
(e) Total energy used = 2000 x 34 = 68,000 kw/hr
(f) Annual Cost = 68,000 x 0.08 = $5,440.00
C. Operating Cost Savings
(1) Gas vs Electric = more than 4 times the operating cost.
10-10
Page 15
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
THIS PAGE INTENTIONALLY LEFT BLANK
10-10
Page 16
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
10-20
MAINTENANCE
10-20
Page 17
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
1. WATER CONDITIONS VS. HUMIDIFIER CLEANING REQUIREMENTS
(1) The GS Series humidifiers are to operate on cold potable, De-Ionized (DI) or
Reverse-Osmosis (RO) water supply and since the output of all GS Series
humidifiers is pure clean steam, minerals from the incoming water are left behind.
These minerals will eventually coat the tank walls or settle to the bottom of the
tank. The mineral content of the incoming water, the unit running time, output
capacity setting and blowdown rate ultimately determine time between each
cleaning.
(2) The Gas Steam humidifier will periodically “blowdown” or skim water from the tank
to reduce the concentration of total dissolved solids that accumulate during long-
term operation. The Gas Steam humidifiers are shipped from the factory set at
25% of output. This setting ensures that scale build-up will be minimized for most
water conditions. The amount of blowdown is field adjustable.
(3) The unit also monitors operation time and will indicate to the user when
maintenance is required. This time is adjustable to adapt to your water conditions
but is set from the factory at 500 hours of 100% operation.
(4) Three parameters will help determine the proper blowdown setting of the Gas
Steam humidifier.
(a) Water hardness
(b) Silica content
(c) Chlorides
(5) Due to the wide range of water conditions found throughout North America it is
important that the blowdown is set according to the local water conditions. By
water conditions we are referring to the hardness of the water supplied to the
humidifier. The hardness is measured in grains per gallon. It is also important to
test for silica content. Silicates may cause foaming and contribute to scale buildup
in the humidifier tank and float chamber. When excessive foaming occurs. Consult
factory for possible solutions.
(6) If you are unaware of the hardness or silica content of your water supply, there
are many “do it yourself” kits, which can be purchased, or there are several
companies that will perform the tests for a reasonable price. You can even contact
your municipality for your water condition.
(7) It is possible to reduce this setting according to observation and guidelines in the
blowdown setting table found in the GS Installation Manual (Form # XX-287). Also,
when high silica content has been identified, the humidifier tank and float chamber
will require increased maintenance and the blowdown setting should be increased
to maximum setting. In this case silica content may determine the appropriate
blowdown setting.
(8) Softened water is recommended if the incoming water has a hardness in excess of
8 grains/gal (136 ppm).
(9) Reverse osmosis (RO) water can provide very long times between cleaning since
it is cleaner than softened water. Deionized (DI) water can reduce the
10-20
Page 18
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
maintenance a step further than RO and all the GS Series components are ready
for RO or DI water use as a standard.
(10) Contact your local Nortec representative for a quotation of a water treatment
system suited for your application.
2. PREVENTIVE MAINTENANCE
(1) The installation manuals of the GS Series of Gas Steam humidifier come with a
complete Maintenance chart in order to guide internal personnel in cleaning and
monitoring activities. Like any other appliance the Gas-Steam humidifier requires
monitoring to ensure efficient operation throughout the life of the unit.
(2) While in operation, the unit will blowdown scaled water through a drain pump
keeping control on the water concentration based on steam output. For longer
intervals between cleaning, the unit may be completely drained down to reduce the
mineral concentration and bring in new fresh water in the system.
(3) The FTBD (Full Tank Blow Down) can be activated through the software or dip
switches based on:
(a) Time of day setting. When the 25 - 400 hours interval (adjustable ) is reached
the unit will wait until the set time of day before activating the full tank
blowdown.
(b) External trigger using 24Vac signal from the building management system to
the input terminal of the humidifier.
(4) Following the full tank blowdown, the unit will refill and perform a float check.
Whenever possible, use this feature to reduce mineral accumulation in the system
and reduce the time required to clean the interior of the reservoir.
3. PRE-CLEANING SEQUENCE
(1) When cleaning of the reservoir is required, use the tank pre-clean feature. This
pre-cleaning sequence will drain the full content of the unit, fill back-up, and re-
drain any residual scale that has fallen from the cold water refilling. This sequence
is not an alternative to cleaning the humidifier, it is meant to reduce the time
required to clean the tank.
(2) Full Size Frontal Opening: Every GS Series Gas Steam Humidifier comes
complete with a full size frontal opening to allow bottom cleaning of the tank and
heat exchanger. This opening allows quick and easy cleaning without removing
the steam outlet of the unit.
10-20
Page 19
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
THIS PAGE INTENTIONALLY LEFT BLANK
10-20
Page 20
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
10-30
OPTIONS &
ACCESSORIES
10-30
Page 21
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
1. OPTIONS AND ACCESSORIES AVAILABLE
A. Nortec Modulating Humidistat with Digital Display
(1) NORTEC humidistats for GSTC or GSP Gas Steam humidifiers feature
proportional + integral control with setpoint range of 10-95% RH. The humidistat
connects directly to the low voltage terminal strip via 3 wires (shielded if run
exceeds 10 m). The humidistat accurately controls RH in a zone or space.
(2) Humidistat Specifications:
(a) Operating Conditions: 41ºF-122°F (5°C-50°C)
(b) Control: 0-95% RH non-condensing
(c) Sensor: 0-100% RH
(d) Humidity Sensor: Solid-state humidity sensor. Suitable for normal, clean air.
Not to be used in corrosive or harmful environment.
(e) Resolution: +- 0.1%
(f)
Repeatability: 0.5%
(g) Accuracy of Sensor: +/- 3% RH from 0-100% RH Range: 10-90% RH for
32°F-122°F (0°C-50°C)
(h) Temperature Effect: 0.05% /°F
(i)
(j)
Outputs: 0-10 VDC
Power: 24 VAC -15%, +10% 50/60 Hz; 2 VA
B. Humidistat with Integral Sensor and Controller with Digital Display
(1) 151-0142 - Modulating 0-10 VDC wall mounted humidistat, P + I control humidistat
with setpoint range of 0-95% RH. Connects directly to the GSTC or GSP low
voltage terminal strip via 2 wires (shielded if run exceeds 10 m) and accurately
controls RH in a zone or space. Time proportioning control not acceptable.
(2) 252-0266 - Modulating 0-10 VDC duct mounted humidistat, P + I control humidistat
with setpoint range of 10-95% RH. Connects directly to the GSTC or GSP low
voltage terminal strip via 2 wires (shielded if run exceeds 10 m) and accurately
controls RH in a zone or space. Can be used as a control humidistat if placed in
return air or as high limit if placed in supply. (Time proportioning control not
acceptable.)
C. Humidistat with Integral Sensor
(1) 150-9857 - Remote duct or modulating high limit sensor.
(2) 150-9858 - Remote wall mounted sensor.
(3) 252-0263 - Outdoor duct mounted temperature sensor. Can provide energy
savings and prevent window condensation by reading outdoor temperature and
resets the humidity control to prevent condensation.
10-30
Page 22
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
D. Nortec On / Off Controls with Digital Display
(1) 252-0273 - Duct Mounted Safety High Limit On/Off Humidistat (if used) is wired to
make on drop in humidity, break on rise to safety setpoint. It should be set to
approximately 85% RH as a safety to prevent saturation and wetting in the duct.
(2) 132-9203 - A Duct Mounted Safety Air-Proving On/Off Switch (if used) is wired to
make on airflow, break on no flow. It is used as a safety to prevent saturation
when no air is flowing through the duct.
(3) Low Humidity Alarm Package - Low limit on/off humidistat duct or wall mounted,
alarm light with engraved faceplate sized to fit standard 2” x 3” recessed electrical
wall box supplied by others. Activates alarm light if duct or room airdrops below
setpoint.
(a) Duct – 253-3365
(b) Wall – 253-3366
(4) High Humidity Alarm Package - High limit on/off humidistat duct or wall mounted,
alarm light with engraved faceplate sized to fit standard 2” x 3” recessed electrical
wall box supplied by others. Stops humidifier and activates alarm light if duct or
room air approaches saturation.
(a) Duct – 253-3363
(b) Wall – 253-3364
E. Configuration Option
(1) 150-7057 - This option allows the Gas Steam humidifier to operate using propane
energy.
F. Direct Vent
(1) GS Indoor Direct Vent Package allows GS unit to be installed in an environment
where the air cannot be used for combustion for one of the following reasons:
chemicals or excessive dust is present in the air or the room is under excessive
negative or positive pressure. All these factors could affect adversely the normal
operation of the unit.
(a) GS 100 - 150-7067
(b) GS 200 - 150-7068
(c) GS 300 - 150-7069
(d) GS 400 - 150-7070
(e) GS 500 - 150-7071
(f)
GS 600 - 150-7072
G. Stand
(1) GS Series Stands are optional with all models. The floor stands will help raise the
unit to maximum of 27” (69 cm) high.
H. Keep Warm
(1) 150-7059 - GSP Keep Warm Feature, allow water temperature in the tank to be
maintained between 140ºF (60ºC) and 160ºF (71ºC) allows for quick response of
the unit on a call for humidity and to reduce possible bacteria growth for health
concerns.
10-30
Page 23
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
I. Indoor Freeze Protection
(1) 150-7058 - GSTC Indoor Freeze protection package provides the unit configured
with keep warm feature, remote fault indication and a normally open drain valve to
protect if freezing conditions may occur. The keep warm feature will ensure the
water temperature is kept between 140ºF (60ºC) and 160ºF (71ºC).
(2) The remote fault indication will allow service personnel to be advised of the unit’s
operational status and the normally open drain valve will ensure the unit is drained
if a power outage.
(3) Drain and fill lines outside of the cabinet, must be protected from freezing with heat
trace. Unit must be enclosed in a weather enclosure with heat source.
(4) A remote alarm must be installed in case the unit faults using remote fault
indication and status indication.
J. Outdoor Freeze Protection (Standard with all GS Outdoor Enclosures)
(1) Outdoor units are configured with the Keep Warm feature enabled to maintain the
tank water temperature between 140ºF (60ºC) and 160ºF (71ºC). Included is a
factory installed normally open drain valve that will ensure the unit drains in the
event of a power outage. Also a factory-installed heater will be included to
maintain an operating temperature range within the electrical compartment. The
heater is powered from the humidifier. Field supplied heat-tracing needs to be
installed on all fill line piping exposed to outdoor temperature. If fill line pipe
freezing is a concern a field supplied normally open valve can be used to drain the
fill line.
(a) 150-8116 - GSTC Outdoor 100
(b) 150-8117 - GSTC Outdoor 200
(c) 150-8118 - GSTC Outdoor 300/400
(d) 150-8119 - GSTC Outdoor 500/600
K. ON-LINE
(1) Nortec OnLine is a remote interactive communication package that allows satellite
contacts to monitor, maintain and control a humidification center from any location
worldwide using standard internet connections. This advanced software shows
graphic representations of the humidifier and its key parameters (up to 75
functions).
L. LINKS 2
(1) Nortec LINKS 2 is the combination of LINKS (building management system
communication hardware) and OnLine (Internet communication hardware) allowing
humidifiers to communicate to a building management system (BMS) as well as
the Internet. Up to 8 humidifiers can be connected to 1 LINKS 2 controller (1
master and 7 slaves). The controller is factory installed and is located internally to
the humidifier. Simply specify at the time of order the operating protocol needed.
LINKS 2 comes standard with Internet capabilities however OnLine service needs
to be specified at time of order.
(2) Operating Protocols:
a)
252-7116 – BACnet / IP
10-30
Page 24
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
b)
c)
d)
252-7111 - BACnet MSTP
252-7113 – Johnson N2
252-7113 – LonWorks
(3) Features
a)
b)
c)
d)
e)
f)
Digital Feedback for unit standby/humidifying mode.
Digital feedback for service required.
Digital feedback for fault indication.
System demand display.
Control room setpoint.
Control high limit setpoint.
g)
h)
i)
Control room %RH.
Control high limit %RH.
Control enable/disable.
j)
Networking capabilities of linking 8 units to one Nortec controller.
Figure 1. NORTEC Online
Figure 2. NORTEC LINKS 2
10-30
Page 25
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
M. DRAIN WATER SUMP PUMP
(1) Externally mounted below humidifier. For use when no floor drain is available and
water must be pumped higher than the bottom of the humidifier (special high
temperature model). Rated for use with all GS models. Recommended model:
W.W. Grainger #4RD29 or #4RD32.
N. STEAM DISTRIBUTION
(1) Used in ducts or air handling units, available in stainless steel.
(2) Steam is dispersed through evenly spaced outlet orifices and upward
perpendicular to the airflow.
(3) When steam is dispersed through evenly spread outlet orifices that are along the
steam distributors “active zone”. They are offset 45º from vertical to address
potential static pressure induced by downward airflow. The distributor is rotated
when installed.
O. REMOTE MOUNTED BLOWER PACK
(1) RMBP 208-240V- 1709701 Blower Pack
(2) Direct steam distribution system that allows for direct space/room humidification
when steam introduction into a ducted system is not feasible. The factory
assembled Blower Pack includes integral steam distributor, an internal steam hose
and condensate connection for simple installation including 3 individual 110 cfm
blower fans that can be powered by a separate 115 V single phase power supply
or can be ordered with a factory installed step down transformer for all standard
primary voltages. The Blower Pack features an adjustable fan to provide different
angles allowing for a flexible install. A temperature sensor enables fans when
steam production begins, while maintaining a quiet operational environment. The
Remote Mounted Blower Pack ships fully assembled and ready for easy
installation with NH, GS, SE Technologies.
(3) See Blower Pack distribution for more information.
P. SHORT ABSORPTION MANIFOLD
(1) See Short Absorption Manifold Engineering Manual for model numbers.
10-30
Page 26
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 3. Steam Distributor
Figure 4. Blower Pack
Figure 5. Short Absorption Manifold
10-30
Page 27
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
THIS PAGE INTENTIONALLY LEFT BLANK
10-30
Page 28
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
10-40
SPECIFICATION
10-40
Page 29
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
1. GENERAL
A. General
(1) NORTEC GS Series Gas-Fired Humidifier[s] as indicated on drawing[s] and as
indicated on schedule[s].
(2) Complete and operable humidification system [which meets applicable building
codes].
(3) Equipment start-up and project inspection by qualified factory trained
representative.
B. Quality Assurance
(1) Manufacturer: For each product specified, provide components by same
manufacturer throughout.
(2) Electrical Components, Devices, and Accessories: Listed and labeled as defined
in NFPA 70, Article 100, by a testing agency acceptable to authority having
jurisdiction, and marked for intended use.
(3) Comply with ARI 640, “Standard for Commercial and Industrial Humidifiers.”
(4) Products shall be supported with a warranty that ensures the product will be free
from defects in materials and workmanship for a period of two years after
shipment.
(5) Commissioning of a system or systems specified in this section is part of the
construction process. Documentation and testing of these systems, as well as
training of the Owner’s operation and maintenance personnel, is required in
cooperation with the Commissioning Authority. Project Closeout is dependent on
successful completion of all commissioning procedures, documentation, and issue
closure. Refer to Project Closeout, Section 01700, for substantial completion
details. Refer to Section 01810, Commissioning, for detailed commissioning
requirements.
(6) Products specified below are to be manufactured is an ISO 9001-2000 certified
facility.
C. Submittals
(1) Submit product data under provisions of Section 15010. Include product
description, model, dimensions, component sizes, rough-in requirements, service
sizes, and finishes. Include rated capacities, operating weights, furnished
specialties, and accessories.
(2) Submit manufacturer’s installation instructions.
(3) Submit operation and maintenance data.
(4) Submit coordination drawings. Detail fabrication and installation of humidifiers.
Include piping details, plans, elevations, sections, details of components, and
dispersion tubes. Detail humidifiers and adjacent equipment. Show support
locations, type of support, weight on each support, and required clearances.
(5) Submit wiring diagrams including power, signal, and control wiring. Differentiate
between manufacturer-installed and field-installed wiring.
10-40
Page 30
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
(6) Submit minimum water quality requirements and water pressure requirements.
D. Extra Materials
(1) Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
E. References
(1) ANSI/NFPA 70 - National Electrical Code.
F. Coordination
(1) Coordinate location and installation of humidifiers in ducts and air-handling units.
Revise locations and elevations to suit field conditions and to ensure proper
humidifier operation.
XXXXX OR XXXXX
(2) Coordinate location and installation of humidifier in the space it serves with the
electrical, mechanical, and plumbing contractors.
2. PRODUCTS
A. Gas Fired Steam Humidifier - GSTC
(1) Packaged unit, floor mounted, gas-fired, steam generating system available at 105
lbs/hr (48 kg/hr), 210 lbs/hr (95 kg/hr), 315 lbs/hr (143 kg/hr), 420 lbs/hr (191
kg/hr), 525 lbs/hr (238 kg/hr), 630 lbs/hr (286 kg/hr), suitable for immediate, or
future, use of all water types including, De-Ionized (DI), Reverse Osmosis (RO),
potable and softened water, without modification required, CSA certified.
(2) Packaged unit, wall mounted, methods of distribution require a steam distributor[s]
or Short Absorption Manifold [s] [SAM-e] for mounting into AHU/duct[s] or Remote
Mounted Blower Pack[s] [RMBP] for direct space applications [refer to options
schedule].
(3) Enclosed cabinet, powder painted steel construction and air gap between cabinet
and insulated humidifier tank ensures safe surface temperature.
(a) Evaporation tank and all internal tank components to be constructed of 304
stainless steel.
(b) Humidifier requires zero clearance to combustibles and shall be installed
against a partition to minimize floor space required. All tank surfaces shall be
insulated with minimum 1" (25 mm) thick insulation and enclosed within unit
cabinetry to ensure safe surface temperature, high overall efficiency, and fast
unit response time. Units with exposed insulation shall not be acceptable.
(c) Maintenance shall not require the removal of the steam lines.
(d) Standard internal drain water cooler to ensure drain water tempering to 140º
F (60 ºC). If external drain water cooler required, provide factory cross-braced
unit stand and factory supplied stainless steel p-trap.
(e) Blow-down p-trap, factory installed, enclosed in cabinet, prevents steam
leakage to drain. Field installation not acceptable.
10-40
Page 31
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
(f)
Provide easily accessible, primary voltage terminal block, internal to
cabinetry, for single point field connection of electrical supply.
(g) Single point connection for gas inlet must be provided. Internal piping from
gas inlet to burners must be factory installed and tested. Field piping from
the gas inlet to the burners is not allowed.
(h) Humidifier to prevent “back-siphoning” using an internal air gap for supply
water, to meet local plumbing codes.
(i)
Drain line to include a vacuum breaker to prevent siphon drainage of the
tank.
(j)
Allowance for combustion air shall be provided in cabinet ventilation design.
Option for direct vent of combustion must be available for use with BH
exhaust vent.
(4) Gas appliance shall be low emission. Units with Carbon Monoxide (CO) levels
higher than 10 ppm and Nitrous Oxide (NOx) levels above 40 ppm are not
acceptable.
(a) System shall be rated as a class I appliance certified for use with exhaust
vent type B.
XXXXX OR XXXXX
(b) System shall be rated as a class III appliance certified for use with exhaust
vent type BH.
XXXXX OR XXXXX
(c) System shall be rated as a class III appliance certified for use with exhaust
vent type BH and use with direct vent of combustion air. (Must be specified
for factory configuration)
(5) Stainless Steel combustion chamber(s)/heat exchanger(s) shall have flat surfaces
to retard scale build-up. Tubular heat exchangers are not acceptable.
(a) Each burner, capable of true modulation will provide steam production of 25
to 105 lbs/hr (11 to 48 kg/hr). Time proportioning modulation is not
acceptable.
(b) Units with multiple heat exchangers, models 210 to 630 lbs/hr (95 kg/hr to
286 kg/hr) must be capable of producing a minimum output of 25 lbs/hr
(11kg/hr).
(c) Units with multiple heat exchangers, models 210 to 630 lbs/hr (95 kg/hr to
286 kg/hr) must alternate the lead burners (duty cycle) to promote equal
usage.
(d) Gas system with gas valve(s), explosion proof, premix combustion air
blower(s), microprocessor controlled ignition, flame sensing and fault
indicator light(s), 100% premix infrared burner(s), hot surface igniters(s) and
heat transfer efficiency maintained over all operating ranges.
10-40
Page 32
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
(e) Blower speed rotation must to be monitored to ensure proper control of input
modulation. System will lock out gas valve operation if proper blower speed
is not detected.
(f)
A secondary combustion air safety, in addition to blower speed monitoring,
utilizing a mechanical pressure differential switch, must be used with each
blower to ensure combustion air is entering the pre-mix blower properly.
(g) Modular heat exchanger shall be easily removable through unit sidewall.
(h) Removable cover at front of unit facilitates easy cleaning (when applicable)
with complete access to tank and heat exchanger surfaces.
(6) Automatic water level control within a separate float chamber, isolated from the
boiling action, to prevent false water level indication.
(a) Fill rate must modulate to match capacity demand to ensure consistent
output. Fill cycles based on low water only is not acceptable.
(b) System shall fill through the bottom of the tank to reduce steam-quenching
effect and noise level. Filling at top of the tank is not acceptable.
(c) Unit water level is to be continuously monitored with a dual magnetic
electronic float system, located outside of the boiling water to ensure
accurate water level control and reduced maintenance. Cool fill water is to be
supplied into the sensing chamber to keep the device cool. Systems using
conductivity probes or floats located within hot reservoir water are not
acceptable.
(d) Tank and float chamber to be separated with a minimum of 1" (25 mm) rigid
insulation, minimizing potential scale build up on float mechanisms, due to
heating of the contained water.
(e) Humidifier shall have a dual fill valve to feed water to the tank and float
chamber, to reduce scaling and mineral build up on the magnetic floats.
(f)
Float chamber to include LED indication of five possible water level
indications.
(g) Ongoing self-diagnostics including periodic float operation and fill/drain rate
verification.
(h) Positive drainage/blow-down using a drain pump, drawing water from the
bottom of the tank, maximizing mineral evacuation (when applicable).
Skimmer not acceptable.
(i)
Blow down interval shall be based on actual steam production, and must be
adjustable to compensate for all water conditions, to ensure maximum energy
and maintenance efficiency.
(j)
Pre-cleaning flushing feature shall be provided to reduce maintenance time.
(k) Must include end of season blow-down feature to evacuate contained water
and minerals after 72 hours with no demand for humidification.
10-40
Page 33
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
(7) Factory mounted, full size, backlit, Liquid Crystal Display provides full operational
status. Display to include a keypad for user interface and adjustment of operational
parameters including:
(a) Unit output (lbs/hr or kg/hr) 25 lbs/hr to full output.
(b) Water level in the tank.
(c) Modulating control demand status.
(d) On/off control and safety (High limit, air proving) circuit status.
(e) Actual room and/or duct RH, and humidity set point, when using transducer
input(s).
(f)
Controller configuration (Proportional band and integral) when using
transducer input(s).
(g) Troubleshooting guide with scroll down menu.
(h) Fault indication including date and time history.
(i)
(j)
Maintenance intervals.
Fill and drain status.
(k) Drain/flush intervals and duration.
(l) Date and time.
(m) Capacity limitation.
(n) 72 hours drain enable/disable.
(o) Control type configuration on/off or full modulation when demand signal(s), or
transducer input(s) are provided.
(p) Up to 10 humidifiers, supplying one AHU or area, can be controlled in series
from one modulating humidity control system.
(q) BACnet, LonWorks, or Johnson N2 capable to interface for monitoring and
control from a Building Management System (BMS/BAS).
(r) Total Controller is Modbus native for (BMS/BAS) communication for remote
monitoring and control of humidifier.
(s) Web base capable via the Internet for remote monitoring or control of
humidifier.
NOTE:
All operational parameters factory set to reduce field set-up time.
(8) Standard of acceptance: NORTEC GSTC.
(9) Optional accessories:
(a) Refer to options schedule.
10-40
Page 34
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
3. EXAMINATION
A. Examination
(1) Examine ducts, air-handling units, and conditions for compliance with requirements
for installation tolerances and other conditions affecting performance.
(2) Examine roughing-in for piping systems to verify actual locations of piping
connections before humidifier installation.
(3) Proceed with installation only after unsatisfactory conditions have been corrected.
B. Installation
(1) Install humidifiers and steam dispersion panels per manufacturers’ instructions.
(2) Seal humidifier dispersion-tube duct penetrations with flange.
(3) Install with required clearance for service and maintenance.
C. Testing
(1) System verification testing is part of the commissioning process. Verification testing
shall be performed by the Contractor and witnessed and documented by the
Commissioning Authority. Refer to section 01810, Commissioning, for system
verification tests and commissioning requirements.
XXXXX OR XXXXX
(2) Manufacturer’s Field Service: Engage a factory-authorized service representative
to inspect field-assembled components and equipment installation, including piping
and electrical connections. Report results in writing.
(a) Leak Test: After installation, charge system and test for leaks. Repair leaks
and retest until no leaks exist.
(b) Operational Test: After electrical circuitry has been energized, start units to
confirm proper unit operation. Remove malfunctioning units, replace with
new units, and retest.
(c) Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment.
10-40
Page 35
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
D. Training
(1) Training of the Owner’s operation and maintenance personnel is required in
cooperation with the Commissioning Authority. Provide competent, factory
authorized personnel to provide instruction to operation and maintenance
personnel concerning the location, operation, and troubleshooting of the installed
systems. The instruction shall be scheduled in coordination with the
Commissioning Authority after submission and approval of formal training plans.
Refer to System Demonstrations, section 01670, for contractor training
requirements. Refer to section 01810, Commissioning, for further contractor
training requirements.
XXXXX OR XXXXX
(2) Engage a factory-authorized service representative to train Owner’s maintenance
personnel to adjust, operate, and maintain humidifiers.
(a) Train Owner’s maintenance personnel on procedures and schedules for
starting and stopping, troubleshooting, servicing, and maintaining equipment
and schedules.
(b) Review data in maintenance manuals. Refer to Division 1 Section “Contract
Closeout.”
(c) Review data in maintenance manuals. Refer to Division 1 Section “Operation
and Maintenance Data.”
(d) Schedule training with Owner, through Architect, with at least seven days
advance notice.
10-40
Page 36
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
THIS PAGE INTENTIONALLY LEFT BLANK
10-40
Page 37
2008-10-01
Download from Www.Somanuals.com. All Manuals Search And Download.
WARRANTY
(1) WALTER MEIER INC. and/or WALTER MEIER LTD. (hereinafter collectively referred
to as THE COMPANY), warrant for a period of two years after installation or 30 months
from manufacturer’s ship date, whichever date is earlier, that THE COMPANY’s
manufactured and assembled products, not otherwise expressly warranted (with the
exception of the cylinder), are free from defects in material and workmanship. No
warranty is made against corrosion, deterioration, or suitability of substituted materials
used as a result of compliance with government regulations.
(2) THE COMPANY’s obligations and liabilities under this warranty are limited to furnishing
replacement parts to the customer, F.O.B. THE COMPANY’s factory, providing the
defective part(s) is returned freight prepaid by the customer. Parts used for repairs are
warranted for the balance of the term of the warranty on the original humidifier or
90 days, whichever is longer.
(3) The warranties set forth herein are in lieu of all other warranties expressed or implied
by law. No liability whatsoever shall be attached to THE COMPANY until said products
have been paid for in full and then said liability shall be limited to the original purchase
price for the product. Any further warranty must be in writing, signed by an officer of
THE COMPANY.
(4) THE COMPANY’s limited warranty on accessories, not of the companies manufacture,
such as controls, humidistats, pumps, etc. is limited to the warranty of the original
equipment manufacturer from date of original shipment of humidifier.
(5) THE COMPANY makes no warranty and assumes no liability unless the equipment is
installed in strict accordance with a copy of the catalog and installation manual in effect
at the date of purchase and by a contractor approved by THE COMPANY to install
such equipment.
(6) THE COMPANY makes no warranty and assumes no liability whatsoever for
consequential damage or damage resulting directly from misapplication, incorrect
sizing or lack of proper maintenance of the equipment.
(7) THE COMPANY retains the right to change the design, specification and performance
criteria of its products without notice or obligation.
Download from Www.Somanuals.com. All Manuals Search And Download.
U.S.A.
CANADA
Authorized Agent:
Walter Meier (Climate USA) Inc.
Walter Meier (Climate Canada) Ltd.
826 Proctor Avenue
Ogdensburg, NY 13669
TEL: 1-866-NORTEC-1
2740 Fenton Road
Ottawa, ON K1T 3T7
TEL: 1-866-NORTEC-1
Download from Www.Somanuals.com. All Manuals Search And Download.
|