MGE UPS Systems Power Supply 225KVA User Manual

w w w. m g e u p s . c o m  
Features  
Single and Parallel UPSs  
Battery Cabinet  
Maintenance Bypass  
Optional Up-link to an  
IBM AS4000  
Galaxy PW™  
100 to 225kVA  
Uninterruptible Power Systems  
Installation and User Manual  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
WARNING  
To reduce the risk of fire or electric shock, install in a temperature and humidity  
controlled indoor area free of conductive contaminants.  
This equipment is intended only for installations in a RESTRICTED ACCESS  
LOCATION.  
ATTENTION Pour réduire le riske d'inccendie ou d'électrocution, installer dans une enciente  
intérieure contrôlée en température et humidité et sans contaminants conducteurs.  
Ce matériel est destiné seulement pour des installations dans un EMPLACE-  
MENT RESTREINT d'cAccès.  
WARNUNG! Um die Gefahr von Feuer und elektrischem Schock zu reduzieren, muss das  
Gerät in einem temperatur - und feuchtigkeitskontrollierten Raum, frei von  
leitungsfähigen Verunreinigungen, installiert werden. Dieses Gerät ist nur für  
die Installation an einem Ort mit eingeschränkter Zugangserlaubnis vorgesehen.  
Diese Ausrüstung ist nur für Anlagen in einem EINGESCHRäNKTEN ZUGRIFF  
STANDORT bestimmti.  
WARNING  
HIGH LEAKAGE CURRENT. Earth connection essential before connecting  
supply.  
ATTENTION  
WARNUNG!  
COURANT DE FUITE ELEVE. Raccordement a la terre indispensable avant  
le raccordement au reseau.  
Hoher Ableitstrom Vor Inbetriebnahme Schutzleiterverbindung herstellen.  
How to Use This Manual and Symbol Usage  
This manual is designed for ease of use and easy location of information.  
Locate specific topics in the Table of Contents.  
For terms used in the text refer to the Glossary.  
Typographical conventions use single quote marks in procedures to denote a prompt for User action:  
For example: 1. After the selections are complete, click on the “Save” button.  
This manual uses four icon symbols with text to convey important information and tips.  
WARNING  
CAUTION  
indicates information provided to protect the user and service personnel against  
safety hazards and/or possible equipment damage.  
indicates information provided to protect the user and service personnel against  
possible equipment damage.  
IMPORTANT  
NOTE  
indicates information provided as an operating instruction, or as an operating tip.  
indicates information provided as an operating tip or an equipment feature.  
86-133060-00 A00  
How To Use This Manual and Symbol Usage  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
CAUTION: Record All Serial Numbers!  
RECORD ALL SERIAL NUMBERS FOR THE GALAXY PWAND COMPONENTS.  
THESE SERIAL NUMBERS WILL BE REQUIRED IF YOUR SYSTEM NEEDS SERVICE.  
KEEP THIS MANUAL IN A PLACE WHERE YOU CAN REFERENCE THE SERIAL  
NUMBERS IF SERVICE IS REQUIRED!  
UPS SINGLE SERIAL NUMBER: ___________________________________________________  
UPS PARALLEL SERIAL NUMBER: _________________________________________________  
BATTERY CABINET SERIAL NUMBER: ______________________________________________  
MBP SERIAL NUMBER: ___________________________________________________________  
ADDITIONAL MODULE SERIAL NUMBERS:  
____________________________  
____________________________  
____________________________  
____________________________  
____________________________  
____________________________  
____________________________  
____________________________  
____________________________  
____________________________  
______________________________  
______________________________  
______________________________  
______________________________  
______________________________  
______________________________  
______________________________  
______________________________  
______________________________  
______________________________  
iv  
CAUTION: Record All Serial Numbers  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
Galaxy PW™  
100 to 225kVA  
Installation and User Manual  
Revision History  
Galaxy PW™ 100 to 225kVA Installation and User Manual 86-133060-00 A00  
Revision:  
X1  
Initial Release  
06/2003  
A00  
ECN#: 003469  
02/2006  
Copyright © 2006 MGE UPS SYSTEMS, INC.  
All rights reserved. Printed in U.S.A.  
MGE UPS SYSTEMS, INC.  
1660 Scenic Avenue  
Costa Mesa, CA 92626  
(714) 557-1636  
Technical Support:  
1-800-523-0142 (during business hours)  
Customer Care Center:  
1-800-438-7373 (Hours: 24/7)  
86-133060-00 A00  
v
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
(This page left blank intentionally)  
vi  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
description  
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page  
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ii  
Certification Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ii  
How to Use This Manual and Symbol Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii  
CAUTION: Record All Serial Numbers! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iv  
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .v  
Section 1 Introduction  
section  
description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page  
1.0  
1.1  
1.2  
1.3  
1.4  
Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 1  
Section Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 1  
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 2  
System Major Power Components . . . . . . . . . . . . . . . . . . . . . . . .1 — 3  
Different Types of Galaxy PW™ Systems . . . . . . . . . . . . . . . . . .1 — 4  
1.4.1 Single UPS System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 4  
1.4.2 Parallel UPS System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 4  
System Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 5  
1.5.1 Electrical Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 5  
Electrical Parameters for Selecting Protective Devices . . . . . . . .1 — 6  
1.6.1 Normal AC Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 6  
1.6.2 Bypass AC Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 7  
Recommended Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 8  
1.7.1 Protection Upstream of Galaxy PW™ . . . . . . . . . . . . . . . . . . . . .1 — 8  
1.7.2 Protection Downstream of Galaxy PW™ . . . . . . . . . . . . . . . . . . .1 — 8  
Parallel Connected UPS Units . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 9  
1.5  
1.6  
1.7  
1.8  
Section 2 System Setup  
2.0  
Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 1  
2.0.1 First steps by an on-site qualified Technical Engineer . . . . . . . .2 — 1  
2.0.2 Final steps by MGE Field Service Engineer . . . . . . . . . . . . . . . . .2 — 1  
2.0.3 Required Equipment and Tools . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 1  
Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 2  
2.1.1 Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 2  
2.1.2 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 3  
Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 4  
2.1  
2.2  
86-133060-00 A00  
Contents  
c i  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
Section 2 System Setup (continued)  
section  
description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page  
2.3  
2.4  
2.5  
2.6  
Galaxy PW™ Cabinet Major Components . . . . . . . . . . . . . . . . . .2 — 5  
Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 6  
Remote External Maintenance Bypass Cabinet . . . . . . . . . . . . . .2 — 7  
General Instructions for Screens . . . . . . . . . . . . . . . . . . . . . . . . .2 — 8  
2.6.1 Control Panel Indicators and Definitions . . . . . . . . . . . . . . . . . . .2 — 8  
System Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 10  
2.7.1 Single UPS unit or Redundant Parallel UPS . . . . . . . . . . . . . . .2 — 10  
Parallel UPS Unit for Increased Output . . . . . . . . . . . . . . . . . . .2 — 11  
2.7  
2.8  
Section 3 Installation  
3.0  
3.1  
3.2  
3.3  
3.4  
3.5  
Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 1  
Optional Communications Card Installation . . . . . . . . . . . . . . . . .3 — 1  
Notes on Connection of Power Circuits . . . . . . . . . . . . . . . . . . . .3 — 1  
Power-Circuit Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 2  
Hot Swap Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 2  
Connections Between Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 4  
3.5.1 Connections Between UPOZ Boards . . . . . . . . . . . . . . . . . . . . . .3 — 4  
3.5.2 Connections Between UPS Cabinets and the  
Remote External Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 4  
3.5.3 Connections Between MUSI Boards . . . . . . . . . . . . . . . . . . . . . .3 — 5  
Environmental Signal of the Media Contacts 11 Board . . . . . . . .3 — 7  
3.6.1 Signal Reception . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 7  
3.6.2 Signal Transmission . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 7  
"Media Contacts 11" Standard Auxiliary Circuits Connection . . . .3 — 9  
3.7.1 Battery Circuit Breaker "QF1" Connection . . . . . . . . . . . . . . . . .3 — 10  
Installation of the "Temperature Monitor" in the  
3.6  
3.7  
3.8  
Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 10  
3.8.1 "Temperature Monitor" installation in a Battery Room . . . . . . . .3 — 11  
Connection of the Battery "Temperature Monitor" . . . . . . . . . . .3 — 12  
About Final Installation Steps . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 14  
3.8.2  
3.9  
Section 4 Operation  
4.0  
4.1  
Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 1  
Start-up of a Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 1  
4.1.1 Start-up of an Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 1  
4.1.2 Emergency Power Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 1  
4.1.3 Single UPS Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 2  
4.1.4 Parallel UPS Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 2  
Operation in On-line Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 3  
4.2.1 Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 3  
4.2.2 Operation with the Normal AC Source Down . . . . . . . . . . . . . . . .4 — 4  
Operation with the Normal AC Source Restored . . . . . . . . . . . . .4 — 5  
4.2  
4.3  
c ii  
Contents  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
Section 4 Operation (continued)  
section  
description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page  
Operation with Engine Generator Set . . . . . . . . . . . . . . . . . . . . .4 — 6  
4.4  
4.5  
4.6  
Battery Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 7  
Inverter Shutdown or Overload . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 7  
4.6.1 Single UPS Unit (On-line mode) . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 8  
4.6.2 Parallel UPS Without Redundancy . . . . . . . . . . . . . . . . . . . . . . . .4 — 8  
4.6.3 Parallel UPS With Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 9  
Output Voltage Quality and Continuity . . . . . . . . . . . . . . . . . . . .4 — 9  
4.7.1 Steady State Voltage Regulation . . . . . . . . . . . . . . . . . . . . . . . .4 — 10  
4.7.2 Transient Voltage Regulation . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 10  
Measurement System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 11  
4.8.1 Voltage Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 12  
4.8.2 Current Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 12  
4.8.3 Power and Frequency Measurements . . . . . . . . . . . . . . . . . . . .4 — 12  
4.8.4 Battery Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 12  
Selections and Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 13  
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 16  
Maintenance Bypass Option . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 16  
Logging and Time-Stamping . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 17  
4.12.1 Event Time-Stamping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 17  
4.12.2 Consulting Logged (time-stamped) Events . . . . . . . . . . . . . . . .4 — 17  
Setting the Date and Time for the UPS - Utilization  
4.7  
4.8  
4.9  
4.10  
4.11  
4.12  
4.13  
4.14  
Via the Galaxy PW™ Display . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 18  
Consulting Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 19  
4.14.1 Consulting Recorded Measurements . . . . . . . . . . . . . . . . . . . . .4 — 21  
Section 5 Maintenance  
5.0  
5.1  
5.2  
5.2  
Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 1  
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 1  
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 2  
Maintenance Isolation Procedures . . . . . . . . . . . . . . . . . . . . . . . .5 — 2  
5.2.1 Single UPS Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 2  
Steps for Parallel UPS Redundancy to Increase Output . . . . . . .5 — 4  
Battery Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 6  
Visual Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 6  
Functional System Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 6  
Testing Parallel Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 7  
5.7.1 Galvanic Isolation and Voltage Matching Transformers . . . . . . . .5 — 7  
Management of Computer Networks . . . . . . . . . . . . . . . . . . . . . .5 — 7  
5.8.1 Integrated SNMP Agent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 7  
5.8.2 Two-channel Network Board . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 7  
5.3  
5.4  
5.5  
5.6  
5.7  
5.8  
86-133060-00 A00  
Contents  
c iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
Appendices  
description  
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page  
Appendix A  
Front Control Panel Display Definitions . . . . . . . . . . . . . . . . . . . . . . . . . .A — 1  
Display of Primary and Secondary Messages . . . . . . . . . . . . . . . . . . . . .A — 4  
Primary Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A — 5  
Secondary Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A — 6  
Appendix B  
Monitoring - Electrical Supervision Options . . . . . . . . . . . . . . . . . . . . . .A — 11  
"Teleservice" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A — 11  
Utilization Via Teleservice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A — 11  
GTC Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A — 11  
GTC + Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A — 11  
Appendix C  
Link to an IBM AS/400® Computer . . . . . . . . . . . . . . . . . . . . . . . . . . . .A — 13  
Connect and Configure the AS400 Link . . . . . . . . . . . . . . . . . . . . . . . . .A — 13  
MGE Warranty & Proprietary Rights for Three Phase Products  
MGE Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .W—1  
Proprietary Rights Statement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .W—1  
MGE Customer Care Center  
Technical Support and Product Services . . . . . . . . . . . . . . . . . . . . . . . . .W—3  
Who To Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .W—3  
Scheduling Field Service Engineer Support . . . . . . . . . . . . . . . . . . . . . . .W—3  
Return Policy for Repair (RMA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .W—3  
Glossary  
Term and Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .G — 1  
Reorder Form  
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .RO—1  
c iv  
Contents  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
Figures  
figure description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page  
1-1: Galaxy PW™ System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 2  
1-2: Galaxy PW™ Single UPS System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 4  
1-3: Fuse Curve Chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 7  
2-1: Handling Cabinet From the Bottom or Rolling on Bars. . . . . . . . . . . . . . .2 — 3  
2-2: Dismantling Leg Supports and Attaching Spacers to Cabinet. . . . . . . . .2 — 4  
2-3: Layout of the Major Cabinet Components. . . . . . . . . . . . . . . . . . . . . . . .2 — 5  
2-4: Component Layout in a Battery Cabinet or a  
Battery Circuit-breaker Enclosure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 6  
2-5: 350A and 1200A Maintenance Bypass Cabinet. . . . . . . . . . . . . . . . . . . .2 — 7  
2-6: Control Panel Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 8  
2-7: Single UPS Unit Start-up Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 10  
2-9: Parallel UPS Unit for Increased Output. . . . . . . . . . . . . . . . . . . . . . . . . .2 — 11  
3-1: Galaxy PW™ Single UPS Unit Wire Diagram. . . . . . . . . . . . . . . . . . . . . .3 — 2  
3-2: Single UPS Unit Power Circuit Connections. . . . . . . . . . . . . . . . . . . . . . .3 — 2  
3-3: Parallel UPS Unit Power Circuit Diagram. . . . . . . . . . . . . . . . . . . . . . . . .3 — 3  
3-4: Connections Between UPOZ Boards. . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 4  
3-5: Two Parallel UPS Units Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 5  
3-6: Three Parallel UPS Units Connections. . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 6  
3-7: Four Parallel UPS Units Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 6  
3-8: Standard Auxiliary Circuits Connections. . . . . . . . . . . . . . . . . . . . . . . . . .3 — 9  
3-9: Installing the "Temperature Monitor" in a Battery Cabinet. . . . . . . . . . .3 — 10  
3-10: Temperature Monitor" Base. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 11  
3-11: Single UPS Unit Connection of the Battery "Temperature Monitor". . . .3 — 12  
3-12: Connection of the Battery "Temperature Monitor."  
(In Parallel UPS Units with Batteries in Same Room.) . . . . . . . . . . . . .3 — 13  
3-13: Connection to the "Media Contacts 11" Board. . . . . . . . . . . . . . . . . . . .3 — 14  
4-1: Control Panel and Circuit Breaker Diagram. . . . . . . . . . . . . . . . . . . . . . .4 — 1  
4-2: Single UPS Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 2  
4-3: Parallel UPS Two Parallel Connected UPS Units. . . . . . . . . . . . . . . . . . .4 — 2  
4-4: Parallel UPS Two to Four Parallel Connected UPS Units. . . . . . . . . . . .4 — 2  
4-5: Normal Operation Indicator Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 3  
4-6: Normal AC Source Indicator Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 4  
4-7: Normal Operation Mode Indicator Diagram. . . . . . . . . . . . . . . . . . . . . . .4 — 5  
4-8: Battery Charge Cycle Chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 6  
4-9: Installation with an Engine Generator Set. . . . . . . . . . . . . . . . . . . . . . . . .4 — 6  
4-10: Operating in On-line Mode Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 7  
4-11: Overload Curve Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 9  
4-12: Measurement System Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 11  
4-13: Display of Alarm Messages.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 16  
5-1: UPS Isolation Diagram for Normal AC Bypass Source. . . . . . . . . . . . . . .5 — 3  
5-2: Panel Procedures for UPS Isolation. . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 3  
5-3: Start-up After Isolation Procedure is Completed. . . . . . . . . . . . . . . . . . . .5 — 3  
5-4: Isolate All UPS’s Procedures Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 4  
86-133060-00 A00  
Contents  
c v  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
Figures (continued)  
figure description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page  
5-5: Start-up Procedure After Isolation Diagram. . . . . . . . . . . . . . . . . . . . . . .5 — 5  
5-6: Redundancy for Increased Output Diagram. . . . . . . . . . . . . . . . . . . . . . .5 — 5  
5-7: MAC Address Sticker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 7  
Tables  
table description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page  
1-1: Electrical Parameters for Normal AC Source. . . . . . . . . . . . . . . . . . . . . .1 — 6  
1-2: Electrical Parameters for Bypass AC Source. . . . . . . . . . . . . . . . . . . . . .1 — 7  
1-2A:  
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 7  
1-3: Rating Recommended for Devices Upstream of Single UPS. . . . . . . . . .1 — 8  
1-4: Rating Recommended for Devices Downstream of Single UPS. . . . . . .1 — 8  
1-5: Parameters for Bypass AC Source and  
Load Cables for a Parallel UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 9  
c vi  
Contents  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
1.0  
1.1  
Scope  
Introduction is a general description and overview of Galaxy PW™ 100 to 225kVA components, its intended use,  
environment, and applicable specifications, power input/output requirements, and system characteristics for  
different system configurations.  
Section Descriptions  
1
Introduction  
Introduction is a general description and overview of the Galaxy PW™ 100 to 225kVA components, its intended use,  
environment, and applicable specifications, power input/output requirements, and system characteristics for  
different system configurations.  
2
System Setup  
System Setup describes receiving and handling of the Galaxy PW™ 100 to 225kVA, a description of major compo-  
nents, the battery cabinet, and definition of the control panel indicators. Includes electrical, mechanical and  
environmental specifications.  
3
Installation  
Installation guides the User through single and parallel UPS unit power cable connections, hot swap options,  
connections between cabinets, communication card connections, battery temperature monitoring. Wire diagrams  
are included for configuring the unit to specifications.  
4
Operation  
Operation describes the theory of operation, start-up for single and parallel units, modes of operation, normal speci-  
fications for operating the Galaxy PW™ 100 to 225kVA. The User procedures include display messages,  
measurement systems, alarms, battery cabinet, and log time-stamping procedures.  
5
Maintenance  
Maintenance procedures for isolation for maintenance, startup for single and parallel units, functional and visual  
checks, software configurations, and testing scenarios.  
Appendices  
A
B
C
List of primary and secondary display messages.  
Electrical supervision options. (Teleservice and GTC Cards)  
Instructions of the optional IBM AS400 up link process.  
86-133060-00 A00  
Introduction  
1 — 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
1.2  
General Description  
The cabinets are cooled by forced ventilation. The air enters via the doors and grids at the bottom and is discharged  
through the roof, which means the cabinets can be positioned against the back wall.  
Connections are made through the bottom. (Connections through the top are an available option.)  
The connection cables may be run in three ways:  
In a trench running under the cabinets.  
Under a false floor.  
On the floor under the cabinets, in the free space equal to the height of the feet; in this case the cables  
should be run side by side to avoid blocking the flow of air for ventilation.  
The cables for connections are between:  
The battery and UPS cabinets (power and control cables).  
The bypass AC-source transformer in an auxiliary cabinet and the UPS cabinet.  
Only the wires for the inter cabinet control connections between parallel-connected UPS units are supplied.  
The other power cables for connections between cabinets are not supplied.  
Figure 1-1: Galaxy PW™ System.  
1 — 2  
Introduction  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
1.3  
System Major Power Components  
Rectifier/charger module (A) Converts 3-phase AC power from the normal AC source supply (1) into DC power  
for the normal inverter input and float charges or recharges the battery.  
Battery unit (D)  
Provides backup power for the inverter in the event of a voltage drop or a normal AC  
source failure.  
Inverter module (B)  
Static bypass module (C)  
Converts the DC power supplied by the rectifier/charger module or the battery unit  
into 3-phase AC power for the load.  
Ensures the instantaneous transfer of the load to the bypass AC source input in the  
event of an inverter shutdown (initiated by the user or by a protective device) or a  
sudden overload.  
Maintenance Bypass  
Isolates the UPS for maintenance and transfers the load to bypass AC source input  
without interrupting the supply of power. The maintenance bypass is made up of  
three manual switches (Q3BP, Q4S and Q5N).  
External Bypass  
Q5N:  
Option for parallel UPSs and Hot-Swapping.  
Isolation of the inverters of all the parallel UPS systems from the load.  
Bypass for maintenance.  
Q3BP:  
The normal AC input and the bypass AC input have different functions and, depending on the installation, may be  
protected differently upstream and/or come from different sources.  
When increased power is required, several Galaxy PW™ units may be connected in parallel (up to four, refer to  
section 4.0). In this configuration, an "isolation" function is added for the UPS system as a whole for maintenance  
purposes, without interrupting the supply of power to the load.  
86-133060-00 A00  
Introduction  
1 — 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
1.4  
Different Types of Galaxy PW™ Systems  
1.4.1 Single UPS System  
Figure 1-2: Galaxy PW™ Single UPS System.  
Legend:  
Q1  
(Molded CB NA): Isolation of  
the rectifier/charger (A) from  
the normal AC source (1);  
rectifier/charger (A) start-up.  
inverter (B):  
DC to AC  
power  
rectifier/  
charger (A):  
AC to DC  
power  
isolation and  
protection:  
Q5N  
*FUSE  
(1)  
*FUSE  
QF1  
Q5N  
Q4S  
(circuit breaker): Battery (D)  
protection and isolation.  
normal  
AC input  
load  
Q1  
isolation  
and  
(switch): Isolation of the UPS  
(B) from the load.  
QF1: isolation  
and protection  
protection  
harmonic  
fliter  
(switch): Isolation of the static  
bypass (C) from the bypass  
AC source (2).  
battery (D):  
backup power  
isolation:  
Q4S  
static bypass (C):  
Q3BP (switch): Bypass switch for  
(2)  
bypass  
AC input  
maintenance.  
FUE  
FUS  
(fuses): Protection of the  
rectifier/charger (A) from the  
normal AC source.  
maintenance bypass:  
Q3BP  
(fuses): Protection of the  
inverter (B) from the load.  
Switch Q3BP is lock on open  
position on parallel UPS  
systems constituted to  
increase available power.  
Note: *The Fuse is to protect against catastrophic rectifier/inverter semiconductor failure.  
1.4.2 Parallel UPS System  
Parallel UPSs can be utilized when increased power is required (two to four parallel units), or an external bypass  
must be added.  
CAUTION  
PARALLEL UPS WITH EXTERNAL MAINTENANCE BYPASS During mainte-  
nance operation, when CB1 (MBP) is closed and CB2 (UPS ISOLATION) is  
open, each UPS control panel display will show a message “LOAD  
PROTECTED” when the UPS is placed in ON-LINE MODE. In this mode the  
critical load is not protected because it is supplied by the maintenance  
bypass power.  
1 — 4  
Introduction  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
1.5  
System Specifications  
1.5.1 Electrical Characteristics  
UPS power rating in kVA  
Normal AC input  
number of conductors  
rated voltage and tolerances  
rated frequency and tolerances  
THDI  
power factor  
Bypass AC input  
number of conductors  
rated voltage and tolerances  
rated frequency and tolerances  
Load  
number of conductors  
Ph/Ph voltages  
Ph/N voltages  
voltage fluctuations (Ph/Ph,Ph/N)  
adjustable frequency and tolerances  
(on battery power)  
100  
130  
150  
180  
200  
225  
3 phases  
480 V 10% (adjustable to 15%)  
60 Hz / 10%  
< 14%  
< 11%  
< 10%  
< 8%  
< 7.6% < 7.5%  
up to 0.9  
3 phases  
480 V / 10%  
60 Hz / 10%  
3 phases + neutral  
3 phases + neutral  
3 phases  
480 V  
277 V  
1%  
60 Hz 0.05 Hz  
synchronization with bypass  
transient voltage variation for 0 to 100% load step change  
permissible overloads  
Isc Ph/Ph (% of I rated)  
Isc Ph/N (% of I rated)  
THDU Ph/Ph and Ph/N for linear load  
THDU Ph/Ph and Ph/N for non-linear load  
(at 80% of Pn)  
0.5 Hz (adjustable from 0.25 Hz to 2 Hz)  
2% (with battery), +2%/-6% (without battery)  
150% for 1 minute, 125% for 10 minutes  
4.7  
7.4  
3.6  
5.7  
3.2  
5
2.6  
4.1  
2.4  
3.7  
2.1  
3.3  
< 1.5% Ph/Ph, < 2% Ph/N  
< 2% Ph/Ph, < 3% Ph/N  
Battery  
voltage floating  
512V to 561V  
gas-recombination sealed lead-acid battery  
standard battery type  
UPS characteristics  
active power (kW)  
100  
90.5  
130  
91  
150  
92  
180  
92.5  
200  
92.5  
202.5*  
93  
efficiency at 50% load (%)  
(values 1%)  
efficiency at 100% load (%)  
(values 1%)  
92.5  
93  
93  
93  
93.5  
93.5  
heat losses (1)  
in KW  
in cal./s  
8.1  
1940  
9.8  
2350  
11.3  
2700  
13.5  
3240  
13.9  
3340  
14.1  
3380  
storage temperature range ºF (ºC)  
-13 to 158 (-25 to 70) dry heat — unit without battery  
-4 to 113 (-20 to 45) — unit with battery  
32 to 95, 104 for 8 hours (0 to 35, 40 for 8 hours)  
95% maximum non condensing at ambient temperature  
< 3280 (< 1000)  
operating temperature range ºF (ºC)  
relative humidity  
maximum operating altitude without derating, FT(m)  
noise level (dBA)  
62  
63  
64  
65  
67  
68  
dimensions, in. (mm)  
width  
depth  
height  
47.8 (1215)  
33 (840)  
74.8 .39 (1900 10)  
3050 (1388)  
NFPA / NEC / NEMA / OSMA  
UL 1778 - ULC  
weight lbs (kg)  
standards  
design  
product and safety  
electromagnetic compatibility  
FCC Part 15, Subport J, Class A - IEEE587 / ANSI 62.41  
(1): The losses indicated are those produced at full rated load with the battery float charging. They must be taken into account when sizing the ventilation system.  
* pf of 225kVA unit has 0.9 and remaining units have 1.0.  
86-133060-00 A00  
Introduction  
1 — 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
1.6  
Electrical Parameters for Selecting Protective Devices  
1.6.1 Normal AC Source  
The parameters given in Table 1-1 can be used to determine the required rating of the upstream protective circuit  
breaker on the normal AC input for one single-UPS or parallel-UPS unit.  
Normal and Bypass AC Input:  
number of conductors  
3 phases  
rated voltage and tolerances  
rated frequency and tolerances  
480 V 10% (adjustable to 15%)  
60 Hz / 10%  
IMPORTANT  
It is essential to choose the type of circuit breaker according to its breaking  
capacity and the prospective short-circuit current at its place of installation.  
This choice must also be made so as to protect the static-switch semicon-  
ductors with respect to the maximum permissible currents and ensure  
discrimination between the UPS output fuses and the downstream  
protection devices.  
Table 1-1: Electrical Parameters for Normal AC Source.  
Electrical parameters for the normal AC source  
rated  
UPS  
output  
in kVA  
100  
current normal AC source  
rated current In for unit:  
for 25%  
for 50%  
with battery at start  
of charge cycle (1)  
without battery (2)  
overload (3)  
overload (3)  
166  
214  
245  
295  
328  
332  
159  
205  
236  
283  
316  
320  
199  
256  
295  
354  
395  
400  
239  
308  
354  
425  
474  
480  
130  
150  
180  
200  
225  
(1) The rated normal AC source currents (In) have been determined for a rated phase-to-phase voltage of 480 V,  
a battery with a 10 minute backup time at the beginning of its charge (412 x 1, 2 = 494 Volts) and full rated load  
with a power factor of 0.9.  
(2) The rated normal AC source currents (In) have been determined for float charging voltage and full rated load  
with a power factor of 0.9  
(3) The normal AC source currents given for an overload of 25% or 50% are maximum values. They have been  
determined for a battery with float charging voltage and a load power factor of 0.9. When choosing the circuit  
breaker rating, use the "rated current" column and check that the circuit breaker tripping curves are compatible  
with the values in the overload columns.  
1 — 6  
Introduction  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
1.6.2 Bypass AC Source  
The parameters given in Table 1-2 and 1-2A can be used to determine the required rating of the upstream protec-  
tive circuit breaker on bypass AC input.  
NOTE  
If the installation includes a transformer on the bypass AC input, allow for the  
inrush current caused by magnetization of the transformer windings.  
Table 1-2: Electrical Parameters for Bypass AC Source.  
Electrical parameters for bypass AC source (480 V)  
rated UPS current bypass AC source (1)  
output  
in kVA  
100  
rated current In for unit:  
for 25%  
overload  
150  
for 50%  
overload (3)  
180  
120  
156  
180  
217  
241  
271  
130  
205  
234  
150  
236  
270  
180  
283  
325  
200  
316  
320  
362  
225  
407  
(1) The bypass AC source currents have been determined for a rated phase-to-phase voltage of 480 V, a load  
power factor of 0.9 and for full rated load as well as overloads of 25% or 50%. When choosing the circuit breaker  
rating, use the "rated current" column and check that the circuit breaker tripping curves are compatible with the  
data in the overload columns. See table and chart below.  
Table 1-2A:  
UPS output  
maximum permissible current  
in kVA  
100  
130  
150  
180  
50 In for 20 ms  
38 In for 20 ms  
33 In for 20 ms  
27 In for 20 ms  
25 In for 20 ms  
22 In for 20 ms  
200  
225  
Figure 1-3: Fuse Curve Chart.  
t(s)  
10  
4
3
10  
2
10  
1
10  
1
1
10-  
2
10-  
3
10-  
4
10  
10-  
2
3
4
10  
10  
I(A)  
86-133060-00 A00  
Introduction  
1 — 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
1.7  
Recommended Protection  
1.7.1 Protection Upstream of Galaxy PW™  
The information provided here is purely indicative, for a single UPS unit. Check that all the criteria mentioned in the  
previous section are taken into account (short-circuit current and protection of the static switch semiconductors on  
the bypass AC input).  
Table 1-3: Rating Recommended for Devices Upstream of Single UPS.  
Ratings  
rated UPS CB on normal  
CB on bypass  
output  
in kVA  
AC input  
AC input  
circuit breaker control unit  
circuit breaker control unit  
100  
130  
150  
180  
200  
225  
125A  
160A  
250A  
250A  
400A  
400A  
125A  
160A  
200A  
250A  
400A  
400A  
125A  
160A  
250A  
250A  
400A  
400A  
125A  
160A  
200A  
250A  
400A  
400A  
1.7.2 Protection Downstream of Galaxy PW™  
These protection devices ensure discrimination for each of the Galaxy PW™ output circuits. If the recommended  
downstream protection is not installed and a short-circuit occurs, the result may be a break longer than 20-min on  
all the other output circuits.  
Table 1-4: Rating Recommended for Devices Downstream of Single UPS.  
Ratings  
rated UPS  
output  
downstream circuit  
breaker(s)  
circuit breaker  
100A  
in kVA  
control unit  
63A curve C  
100A curve B  
100 to 225kVA  
1 — 8  
Introduction  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
1.8  
Parallel Connected UPS Units  
For installations with redundant units, take into account only the units required to supply the load power (e.g. for an  
installation made up of 3 parallel-connected UPS units, one being redundant, only 2 UPS units are used to  
determine bypass AC source and load currents and cable cross-sections).  
Table 1-5 serves as an example for a parallel connected installation comprising up to four UPS units.  
Table 1-5: Parameters for Bypass AC Source and Load Cables for a Parallel UPS.  
Parameters  
rated unit  
output  
number of  
parallel-  
total UPS  
rated output  
in kVA  
bypass AC  
source or load  
line current  
in kVA  
connected  
units  
in Amps  
100  
130  
150  
180  
2
3
4
2
3
4
2
3
4
2
3
4
2
3
4
2
3
4
200  
300  
400  
260  
390  
520  
300  
450  
600  
360  
540  
720  
400  
600  
800  
450  
675  
900  
240  
360  
480  
312  
468  
624  
360  
540  
720  
434  
651  
868  
482  
723  
964  
542  
813  
1084  
200  
225  
86-133060-00 A00  
Introduction  
1 — 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
(This page left blank intentionally)  
1 — 10  
Introduction  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Setup  
2.0  
Scope  
System Setup describes receiving and handling of the Galaxy PW™ 100 to 225kVA, a description of major compo-  
nents, the battery cabinet, and definition of the control panel indicators, which includes electrical, mechanical and  
environmental specifications.  
MGE also recommends obtaining an MGE field service engineer for final installation and basic startup for single and  
parallel units.  
CAUTION  
Scheduling of the MGE Field Service Engineers typically should be done 7 to  
10 days before they are required on-site. If the startup of the UPS is critical  
to maintaining your schedule, please call the MGE toll free telephone number  
at 1-800-438-7373 for assistance. The MGE Field Service Engineers will insure a  
quick installation for the initial safe startup and configuration of your Galaxy PW™.  
Final installation and start-up should be completed by a qualified MGE Field Service Engineer.  
2.0.1 First steps by an on-site qualified Technical Engineer  
Step 1.  
Step 2.  
Step 3.  
Unpack and position the unit.  
Connect the main (utility) power.  
Connect the power circuits.  
2.0.2 Final steps by MGE Field Service Engineer  
Step 4.  
Step 5.  
Optional:  
Call MGE and wait for the MGE Field Service Engineer to complete the installation.  
The MGE Field Service Engineer finalizes installation and the startup process.  
Procedure for temporary power prior to the final startup.  
2.0.3 Required Equipment and Tools  
The following equipment and tools are recommended for on-site installation:  
Digital volt meter (DVM)  
1/8 inch slotted screwdriver  
Pallet jack/forklift  
Conduit installation tools  
Nut driver set  
86-133060-00 A00  
System Setup  
2 — 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
2.1  
Receiving  
On delivery, check that the equipment has not been damaged in transport (declare any damage to the carrier in  
accordance with customary claim procedures).  
Also check that the characteristics noted in the test report for the equipment correspond to those specified on the  
order form. In the event of a non-conforming item, quote the delivery note reference number when making your  
claim.  
2.1.1 Handling  
The cabinets are delivered on pallets, equipped with a shock absorbing system. Ideally, the equipment should be  
unpacked just before installation (see "unpacking" section below). Cabinet weights and dimensions are specified on  
the packaging. Cabinets may be handled in one of the following ways (see Figure 2-1):  
Rolling on Bars (B)  
Do not mount the foot pads, but place the cabinet on the rollers (at least three). The cabinet may be pulled on rollers  
using a sling positioned horizontally. This technique should only be used when absolutely necessary (narrow  
doorway or corridor, preventing the use of a fork-lift or pallet-mover).  
From the Bottom (A)  
The cabinets can be moved from the front or the rear (715 mm wide cabinets) using a pallet truck or fork-lift truck,  
or on the 4 surfaces (1015 mm and 1215 mm wide cabinets) using a fork-lift truck.  
Fork tunnel height:  
Fork opening:  
140 10 mm.  
560, 650 or 700 mm according to cabinets width.  
The 715 mm wide cabinets are designed to pass through 715 mm wide openings, and the other cabinets are  
designed to pass through 825 mm wide openings. For narrow openings, (follow the instructions below) cabinets are  
normally 825 mm deep.  
This depth can be reduced to:  
817 mm by removing rear panels.  
805 mm by removing doors.  
800 mm by removing doors and door hinges.  
unpack the cabinet, refer to section 2.2 ‘Unpacking’, page 4. The cabinet can then be handled by lifting machines  
on all surfaces after the pallets have been dismantled by removing the rear panels, and remove the fixing screws  
using a "torx" screwdriver.  
Removing the doors:  
1. Open the door(s).  
2. Disconnect the door earth connection from the frame.  
3. For cabinets fitted with a control panel, carefully disconnect the ribbon cables from the panel circuit boards  
located on the inside of the door.  
4. Knock out the hinge pins from below.  
5. Remove the door(s).  
Removing the door hinges:  
1. Remove the screws holding the side panels to the hinges.  
2. Remove the central screw holding the hinge.  
2 — 2  
System Setup  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
Figure 2-1: Handling Cabinet From the Bottom or Rolling on Bars.  
A
B
From Bottom  
On Rollers  
2.1.2 Storage  
The equipment must be stored in a dry and well-aired location, sheltered from rain, water sprays or splashes and  
all chemical agents. Storage in original packing is recommended, since this packaging is designed to provide  
maximum protection during storage and handling. If the unit must be unpacked prior to final installation, cover the  
equipment with a shroud providing protection against dust, debris, or paint.  
Please dispose of the packaging in accordance with the applicable legislation.  
IMPORTANT  
Transport: the temperatures must remain within the -30° to +50°C range and the  
duration should not exceed 30 days.  
Storage: the battery is of the sealed lead-acid or vented lead-acid type and should not be stored for more than six  
months at 20°C without recharging for batteries that are initially fully charged (for partially charged batteries, the  
storage time should be reduced). After the recommended maximum storage time, the battery must be charged,  
requiring partial start-up of the equipment (rectifier-charger).  
The battery cells can be stored at a temperature between -20°C and +45°C if delivered in their initial packing.  
The ideal battery storage temperature is between 15° and 25°C (higher temperatures result in reduced storage life  
or downgraded technical characteristics). If higher temperatures cannot be avoided during transport or storage,  
please consult us.  
86-133060-00 A00  
System Setup  
2 — 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
2.2  
Unpacking  
1. Remove the packing box and the document holder on the top of the cabinet; raise the cabinet.  
2. Dismantle the blocks fixed beneath the cabinet by M12 screws, see Figure 2-2 (A or B), according to the width  
of the cabinet);  
3. Dismantle the 4 M12 screws screwed on the 4 leg supports (C).  
4. Withdraw the "hexagonal spacer + leg" assemblies delivered inside the document holder.  
5. Screw the spacers onto the cabinet frame (C).  
6. Lock these spacers in position using a 24 mm flat wrench, and fit the cabinet on its legs.  
7. Adjust cabinet height and verticality by screwing or unscrewing the legs using a 13 mm flat wrench.  
Figure 2-2: Dismantling Leg Supports and Attaching Spacers to Cabinet.  
A
B
C
2 — 4  
System Setup  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
2.3  
Galaxy PW™ Cabinet Major Components  
Legend:  
AA: cross-sectional view of the cabinet,  
B: front view of the cabinet,  
C: front panel,  
N: rack containing electronic boards,  
O: Media Contacts 11 board,  
P: slot for communications boards,  
Q: FUE input fuses,  
D: rear panel,  
1: normal AC input connection,  
2: bypass AC input connection,  
E: load connection,  
R: FUS output fuses,  
S: RALI board,  
T: UPOZ /UCOZ board,  
F: battery connection,  
G: air inlets,  
H: air outlets,  
U: MUSI board,  
V: backfeed protection (contactor),  
W: control wire routing,  
I: cable exit through the bottom,  
J: trough, if applicable,  
K: rectifier/charger module,  
L: inverter module,  
X: fuses for overvoltage protection RC circuit on bypass,  
Y: control-wire connection (auxiliary "Media Contacts 11" circuits and  
communications options).  
z: EP0I Board  
3: VETI Board  
M: static-bypass module,  
Figure 2-3: Layout of the Major Cabinet Components.  
AA  
B
A
H
H
K
M N 3  
O
P
L
D
C
T
V
S
U
M
R
G
Q
Z
W
Q1  
Q4S  
Q3BP  
Q5N  
1, 2, E,F  
G
GND  
N
L1L2L3  
L1L2L3  
L1L2L3  
G
F
1
X
2
E
Y
I
A
J
86-133060-00 A00  
System Setup  
2 — 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
2.4  
Battery Cabinet  
Legend:  
AA: cross-sectional view of the cabinet,  
B: front view of the cabinet,  
C: front panel,  
D: rear panel,  
E: cable ties to duckboard shelf,  
F: cable exit through the bottom,  
G: trough, if applicable,  
H: connection of exposed conductive parts to duckboard shelf,  
I: cable exit to battery connection point in UPS cabinet,  
J: cable exit to an additional battery cabinet, if applicable,  
K: cable ties to duckboard shelf,  
L: fixture locking circuit breaker "QF1" in the open position.  
Figure 2-4: Component Layout in a Battery Cabinet or a Battery Circuit-breaker Enclosure.  
AA  
B
A
C
D
XR1  
QF1  
+
+
E
H
J
I
F
A
K
L
G
2 — 6  
System Setup  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
2.5  
Remote External Maintenance Bypass Cabinet  
350A and 1200A (See Figure 2-5)  
Refer to “Installation Instructions” 90-133056-01 for detailed information about 350A cabinet.  
Refer to Installation drawing 90-133077-00 for detailed information about 1200A cabinet.  
If your installation is custom designed, a separate installation drawing may apply to your system.  
All external wiring are provided and installed by the user.  
Transfer instructions can be found in front of the cabinet including the proper operation of the kick key interlock.  
Figure 2-5: 350A and 1200A Maintenance Bypass Cabinet.  
1200A  
350A  
NEURTRAL  
(NOT SHOWN)  
CRITICAL LOAD  
MULTI CIRCUIT  
MONITOR BOARD  
MULTI CIRCUIT  
MONITOR BOARD  
F1, F2  
F3 TO F8  
CRITICAL LOAD  
MBP  
TERMINALS  
F1, F2  
TRANSFER  
INITIATE (SI)  
TRANSFER INITIATE (SI)  
ELECTRIC INTERLOCK  
(KA)  
ELECTRIC  
INTERLOCK  
(KA)  
TB2  
DISPLAY METER  
T1  
CB2  
TB1  
CB2  
UPS ISOLATION  
CB1  
MAINTENANCE  
BYPASS  
UPS OUTPUT  
CB1  
MAINTENANCE  
BYPASS  
TB1  
GROUND  
NEUTRAL  
CONTROL WIRE  
ROUTING  
UPS  
TERMINALS  
REMOVABLE  
PANELS  
FOR POWER  
CONDUIT ENTRY  
GROUND  
SEISMIC  
MOUNTING  
CUTOUTS  
REMOVABLE PANEL  
FOR CONTROL AND  
POWER  
CONDUIT ENTRY  
SEISMIC HOLE  
LOCATION  
FORKLIFT OPENINGS  
(LEFT & RIGHT  
SIDE TYPICAL)  
86-133060-00 A00  
System Setup  
2 — 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
2.6  
General Instructions for Screens  
To display the desired information and enter commands using the , and ø keys:  
1. Press the  
key to exit the time-stamping consultation mode and return to the main menu. If no commands  
are entered for five minutes, the system automatically returns to the normal display mode.  
To scroll through the screens displaying information:  
1. Press the and keys to scroll up and down through the screens.  
For time-stamped events, the display begins with the last event logged. To access older events, press the key.  
If during consultation, you wish to review more recent events, press the key.  
2.6.1 Control Panel Indicators and Definitions  
The control panel on the Galaxy PW UPS comprises the basic controls and indications required to check the  
general status of the system. See Figure 2-6.  
Located in the upper right part of the cabinet front, the control panel is designed to provide an easy and rapid  
overview of system status. See Figure 2-6.  
Interpretation of symbols is very simple and requires no particular training. The information concerns only the  
cabinet on which the panel is located. Refer to Appendix A for a complete List of Primary and Secondary display  
messages.  
The panel indicates:  
Normal operation (load protected).  
Operation with load on battery power.  
Abnormal situations (operating problem).  
Dangerous situations (load not protected).  
Figure 2-6: Control Panel Indicators.  
1
2
3
4
5
6
1
2
7
8
22  
9
10  
11  
12  
13  
14  
20  
15  
V
A
W.Hz  
17  
18  
16  
fault  
19  
21  
2 — 8  
System Setup  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
Control Panel Alphanumeric Legend:  
1
2
3
4
5
6
7
8
"Rectifier/charger" light Indicates on/off and charging activity.  
"Battery light"  
Indicates battery status.  
"Static-bypass" light  
"Inverter" light  
"Load" light  
Indicates static bypass tolerance status.  
Indicates inverter on/off status.  
Indicates Load supplied and not supplied.  
The buzzer sounds in load operating situations.  
This button is used to start the inverter locally.  
This button turns the inverter off locally.  
Buzzer  
"Inverter ON" button  
"Inverter OFF" button  
9 -10 Keys  
These keys are used to select commands in the main menu and access the secondary  
messages.  
11  
12  
Key  
This key is used to validate the user’s choice.  
ø
Key  
This key is used to access the main menu: display language, display-contrast setting,  
sound level of the buzzer, lamp test, date and time settings, inverse-video and event log.  
13  
14  
15  
16  
17  
18  
19  
"V" Key  
This key is used to access voltage measurements.  
This key is used to access current measurements.  
This key is used to access other measurements:  
This indicator light indicates the presence of anomalies.  
This key is used to access the primary messages.  
This key is used to access battery measurements:  
"A" Key  
"W.Hz" Key  
"Anomaly" light  
ı
Key  
"Battery" Key  
"Forced-transfer"  
This key is used to voluntarily transfer the load to the inverter or from the inverter to the  
static bypass (return transfer).  
20  
"Alarm reset"  
This key is used to reset stored alarms. The system accepts resetting only when alarms  
have been cleared.  
21  
22  
"Buzzer reset"  
Display  
This key is used to stop the buzzer. However, new alarms set the buzzer off again.  
The display continuously indicates the system operating status.  
86-133060-00 A00  
System Setup  
2 — 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
2.7  
System Start-up  
2.7.1 Single UPS unit or Redundant Parallel UPS  
Proceed in the following order: See Figure 2-7.  
1. Close the upstream switches supplying normal and bypass AC source power (on the LV switchboard).  
2. Close normal AC input switch Q1. The system powers up:  
- the rectifier/charger automatically starts.  
- green light 1 on the control panel goes on.  
- light 2 turns red.  
3. Close bypass AC input switch Q4S:  
- green lights 3 and 5 on the control panel go on.  
4. Close inverter output switch Q5N.  
5. Close battery circuit breaker QF1:  
- light 2 goes off.  
6. Open maintenance bypass switch Q3BP.  
7. Press the "inverter on" button 7 on the control panel:  
- the green "inverter" light 4 flashes.  
- the inverter starts, then, if the bypass AC source transfer conditions are satisfied, the load is transferred  
to the inverter if the on-line mode is selected.  
- the green "static-bypass" light 3 goes off.  
- the green "inverter" light 4 shines for on-line mode.  
Figure 2-7: Single UPS Unit Start-up Diagram.  
Q1  
Q4S  
Q3BP Q5N  
1
1
2
3
4
5
6
1
1
1
1
1
0
0
0
0
0
0
0
0
0
1
2
3
4
5
6
0
1
2
1
0
1
1
1
1
1
0
7
22  
8
QF1  
0
1
I
1
0
1
1
0
0
0
8
7
2 — 10  
System Setup  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
2.8  
Parallel UPS Unit for Increased Output  
Proceed in the following order: See Figure 2-8.  
1. Check that all load devices are off or that the load is disconnected.  
2. Close the upstream switch supplying normal AC source power (on the LV switchboard).  
3. Close the normal AC input circuit breakers Q1 on the UPS units. The system powers up:  
- the rectifier/chargers automatically start,  
- the green "rectifier/charger" lights 1 in the control panels go on,  
- lights 2 turn red.  
4. Close the battery circuit breakers QF1.  
- lights 2 go off.  
- green lights 3 and 5 on the control panels go on.  
5. Close Main 2 input switch Q4S for the units.  
6. Close output switches Q5N for the inverters and in the external bypass unit.  
7. Open maintenance bypass switch Q3BP in the external bypass unit.  
8. Press the "inverter on" button 7 on each control panel:  
- the green "inverter" lights 4 flash.  
9. When a sufficient number of inverters are ready, the inverter-output contactors close:  
- the green "inverter" lights 4 shine permanently green.  
- the "static-bypass" lights 3 go off.  
Figure 2-8: Parallel UPS Unit for Increased Output.  
Q4S  
Q5N  
Q1  
1
2
3
4
5
6
1
1
1
0
0
0
1
2
3
1
2
QF1  
0
Q4S  
I
7
Q1  
Q1  
Q5N  
1
0
22  
8
1
1
0
0
1
1
4
1
0
0
0
5
6
7
external bypass  
1
1
0
0
Q5N  
1
1
Q3BP  
0
0
7
8
7
86-133060-00 A00  
System Setup  
2 — 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
(This page left blank intentionally)  
2 — 12  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
3.0  
3.1  
Scope  
Installation guides the User through single and parallel UPS unit power cable connections, hot swap options,  
connections between cabinets, communication card connections, battery ‘temperature monitoring’ installation. Wire  
diagrams are included for configuring the unit to specifications.  
MGE recommends obtaining an MGE field service engineer for final installation and basic startup for single and  
parallel units. Final installation and start-up should be completed and performed by a qualified MGE Field  
Service Engineer.  
Optional Communications Card Installation  
Three slots are available on the "Media Contacts 11" board for optional communications. See the position of these  
slots marked "P" in Figure 2-3, page 2—5.  
Installation of Boards setup notes:  
Boards may be installed with the UPS on, without removing the protective covers.  
Boards must be pushed to the end of the slots to ensure correct installation.  
Board front plates must be screwed to the protective "Media Contacts 11" board cover.  
Wire routing holes are provided in the support for the "Media Contacts 11" board for tying down the wires;  
The control wires must then be routed through the cableway marked "W" in figure 2-3, page 2—5.  
3.2  
Notes on Connection of Power Circuits  
Open the doors and remove the lower terminal shields (secured by screws to the cabinet chassis) of the  
UPS cabinets, connect the power cables, each cabinet must be grounded.  
All the cabinets must be interconnected for equipotential bonding, forming a mesh which is itself connect-  
ed to the building structure and earthing electrode.  
The connection drawings hereafter show the cabinets with doors open and terminal shields removed.  
CAUTION  
Before making connections, check that switches Q1, Q4S, Q3BP, Q5N and QF1 are  
in the "open" position.  
IMPORTANT  
For parallel UPS with an external bypass unit, the power connections between  
each UPS cabinet and the external bypass unit must imperatively be of the same  
length. Outside the cabinets, separate the auxiliary wiring from the power cables.  
86-133060-00 A00  
Installation  
3 — 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
3.3  
Power-Circuit Wiring Diagrams  
The single UPS wire diagram is for typical UPS installations shown in Figure 3-1. The heavy lines represent the  
cables that must be connected (F), refer to section 3.5 ‘Connections Between Cabinets’ for more detail on cables.  
Figure 3-1: Galaxy PW™ Single UPS Unit Wire Diagram.  
Legend:  
QF1 +  
+
1: Normal AC source,  
2: Bypass AC source,  
A: Rectifier/charger module,  
B: Inverter module,  
C: Static-bypass module,  
E
D
F
F
1
2
Q1  
Q5N  
Q3BP  
( )  
A
B
C
Q4S  
( )  
D: Battery cabinet next to the  
Galaxy PW  
Galaxy PW™ UPS cabinet,  
E: Additional battery cabinets,  
F: The equipotential-bonding  
connection between cabinets.  
3.4  
Hot Swap Options  
The external bypass may be used to construct a bypass outside the UPS, thus making it possible to shutdown the  
UPS for maintenance purposes.  
The option may be used for single UPS units and redundant parallel UPS. For the power-circuit connections of a  
single UPS unit see Figure 3-2, for the power-circuit connections of parallel UPS see Figure 3-3.  
Power cables for UPS-to-bypass connections are not supplied.  
Figure 3-2: Single UPS Unit Power Circuit Connections.  
Legend:  
Q3BP  
1: Normal AC source.  
2: Bypass AC source.  
A: Rectifier/charger module.  
B: Inverter module.  
C: Static-bypass module.  
QF1 +  
+
D
E
F
F
1
2
Q1  
( )  
Q5N  
Q5N  
( )  
( )  
A
B
C
D: Battery cabinet next to the  
Galaxy PW™ UPS cabinet.  
Q4S  
( )  
2
Q4S  
Q3BP  
Galaxy PW  
E: Additional battery cabinets.  
F: The equipotential-bonding  
connection between cabinets.  
3 — 2  
Installation  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
Figure 3-3: Parallel UPS Unit Power Circuit Diagram.  
Legend:  
Q3BP  
2
1: Normal AC source,  
2: Bypass AC source,  
A: Rectifier/charger module,  
B: Inverter module,  
C: Static-bypass module,  
QF1 +  
+
E
D
F
F
1
2
Q1  
( )  
Q5N  
Q5N  
( )  
( )  
A
B
C
D: Battery cabinet next to the  
Galaxy PW™ UPS cabinet,  
2
Q4S  
E: Additional battery cabinets,  
Galaxy PW  
F: The equipotential-bonding  
connection between cabinets.  
QF1 +  
+
E
D
F
F
1
2
Q1  
Q5N  
( )  
A
B
C
Q4S  
( )  
Galaxy PW  
86-133060-00 A00  
Installation  
3 — 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
3.5  
Connections Between Cabinets  
These connections are made on the UPOZ board (marked T) and MUSI board (marked U). See Figure 2-3, page 2—5.  
3.5.1 Connections Between UPOZ Boards  
These connections are made using the cables (A) supplied, see Figure 3-4.  
The purpose of the connection is to make a loop. Connector XM137 on the UPOZ board of one UPS unit must be  
connected to connector XM136 on the UPOZ board of the next UPS unit and so on until the first board is returned  
to origin.  
Figure 3-4: Connections Between UPOZ Boards.  
'UPOZ'  
TM  
Galaxy PW 1  
XM137  
XM138  
'UPOZ'  
TM  
Galaxy PW 2  
A
XM137  
XM138  
'UPOZ'  
TM  
Galaxy PW 3  
XM137  
XM138  
3.5.2 Connections Between UPS Cabinets and the Remote External Bypass  
Refer to the installation drawing included with the Maintenance Bypass Cabinet for control and power connections.  
These connections are provided and installed by the user.  
3 — 4  
Installation  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
3.5.3 Connections Between MUSI Boards  
These connections are made using the special cables (A) supplied, see Figures 3-5.  
1. Connectors XM5, XM6 and XM7 on the MUSI board are used to transmit signals.  
2. Connectors XM10, XM11 and XM12 on the MUSI board are used to receive signals.  
3. Connector XM5 is associated with connector XM10 for communication with one UPS unit; similarly, XM6 is  
associated with connector XM11 for communication with a second UPS unit and XM7 is associated with  
connector XM12 for communication with a third UPS unit.  
For connection with two parallel UPS units, see Figure 3-5.  
For connection with three parallel UPS units, see Figure 3-6, page 3—6.  
For connection with four parallel UPS units, see Figure 3-7, page 3—6.  
IMPORTANT  
Outside the cabinets, group the "UPOZ" inter-board and "MUSI" inter-board  
connections with the inter-cabinet auxiliary connections, and separate this  
assembly using power cables.  
Figure 3-5: Two Parallel UPS Units Connections.  
'MUSI'  
Galaxy PW 1  
TM  
XM5  
XM6  
XM7  
XM10  
XM11  
XM12  
A
'MUSI'  
Galaxy PW 2  
XM5  
TM  
XM10  
XM11  
XM12  
XM6  
XM7  
86-133060-00 A00  
Installation  
3 — 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
Figure 3-6: Three Parallel UPS Units Connections.  
'MUSI'  
TM  
XM5  
XM6  
XM7  
Galaxy PW  
1
XM10  
XM11  
XM12  
'MUSI'  
XM5  
TM  
Galaxy PW  
2
XM10  
XM11  
XM12  
XM6  
XM7  
A
'MUSI'  
XM5  
TM  
Galaxy PW  
3
XM10  
XM11  
XM12  
XM6  
XM7  
Figure 3-7: Four Parallel UPS Units Connections.  
'MUSI'  
TM  
XM5  
XM6  
XM7  
Galaxy PW  
1
XM10  
XM11  
XM12  
'MUSI'  
XM5  
TM  
Galaxy PW  
2
XM10  
XM11  
XM12  
XM6  
XM7  
A
'MUSI'  
XM5  
TM  
Galaxy PW  
3
XM10  
XM11  
XM12  
XM6  
XM7  
'MUSI'  
XM5  
TM  
Galaxy PW  
4
XM10  
XM11  
XM12  
XM6  
XM7  
3 — 6  
Installation  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
3.6  
Environmental Signal of the Media Contacts 11 Board  
Terminals XR2, XR3, XR4 and XR5 on the "Media Contacts 11" board of each type of unit can be used to receive  
signals from the operating environment and to transmit signals concerning the operating status of the UPS, see  
Figure 2-3, page 2—5 for the position of the board, item 1 and 2).  
3.6.1 Signal Reception  
The signals should be provided by volt-free contacts.  
Emergency off:  
An NC contact causes shutdown of the inverter and the rectifier/charger, opening of  
the battery circuit breaker, blocking of the static bypass and activation of a relay  
contact on the "Media Contacts 11" board.  
Battery room  
ventilation fault:  
A ‘NO’ contact causes shutdown of the rectifier/charger.  
Battery circuit  
breaker QF1 closed:  
A ‘NO’ contact prevents inverter start-up if the circuit breaker is open.  
Battery temperature:  
A PC-board, placed near the battery, supplies information on the battery tempera-  
ture, thus enabling the rectifier/charger to regulate the battery voltage.  
"Auxiliary" signals:  
Depending on the selected settings, these signals may be used to provoke:  
- forced shutdown of the inverter (whatever the status of the bypass AC source),  
- protected shutdown of the inverter (load transfer to the bypass AC source).  
- limiting of the current drawn by the rectifier/charger (programmable value) when  
supplied by an engine generator set with an insufficient power rating. The additional  
power required by the inverter is supplied by the battery which discharges,  
- limiting of the battery charge current (programmable value) if the normal AC source  
is replaced by an engine generator set with an insufficient power rating.  
3.6.2 Signal Transmission  
An auxiliary 24 V  
power supply:  
Isolated and backed up, is used to supply:  
- the undervoltage release of the battery circuit breaker(s) QF1.  
- the board that measures the temperature in the battery room.  
"low battery"  
warning signal:  
(Volt-free changeover contact) indicating that battery time is about to run out.  
The warning threshold may be personalized.  
"load on UPS" signal:  
(Volt-free changeover contact) indicating that the load is supplied by the  
inverter. For a single-UPS unit, one volt-free changeover contact may be used  
to indicate that the load is supplied by the bypass AC source.  
86-133060-00 A00  
Installation  
3 — 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
"load on battery power" signal: (Volt-free changeover contact) indicating that the inverter is supplied  
by the battery in the following cases:  
- normal AC source outage or voltage drop.  
- rectifier/charger shutdown.  
- rectifier/charger current limiting.  
This signal, which may be used to initiate process saving and shutdown  
procedures, is time-delayed 30 seconds to avoid unnecessary operations  
following micro-breaks.  
"Maintenance position" signal: (Volt-free changeover contact) indicating that:  
- maintenance bypass switch Q3BP is closed,  
- bypass AC source input switch Q4S is open,  
- inverter output switch Q5N is open,  
- battery circuit breaker QF1 is open.  
Signal to open battery  
circuit breaker(s) QF1:  
In the event the "emergency off" button is pressed or to avoid an excessive  
battery discharge (lasting more than three times the rated backup time plus two  
hours).  
Repo Contact:  
(Volt-free changeover contact) used to trip switching devices in the event of an  
emergency shutdown.  
"General Alarm" information:  
(Volt-free changeover contact) which includes:  
- internal faults.  
- information on temperatures outside tolerances in the battery room (optional).  
- overload information (> In).  
- static-switch ventilation and power-supply faults.  
NOTE  
The maximum breaking capacity of the changeover contacts is 5A at 250V.  
3 — 8  
Installation  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
3.7  
"Media Contacts 11" Standard Auxiliary Circuits Connection  
Connecting the auxiliary circuits to the three connectors on the "Media Contacts 11" board in the Galaxy PW™ UPS  
cabinet, see the position of this board, marked "O", see Figure 2-3, page 2—5.  
2
Recommended cable cross-section: 1 mm . The male connectors that fit the female connectors on the board (XR2  
to XR5) are supplied. The contacts are volt-free and are shown in the diagram under the following conditions: UPS  
on, contact at rest. Contact breaking capacity: 250 V, 5 A.  
Figure 3-8: Standard Auxiliary Circuits Connections.  
Media Contacts 11 Board  
XR2  
XR3  
12 - - - - - - - - - -1 10 - - - - - - - -1 10 - - - - - - - -1 10 - - - - - - - -1  
XR2  
XR3  
XR4  
XR5  
XR4  
XR5  
XR2 connector  
input or output signals:  
XR1  
circuit  
12  
11  
10  
9
AC  
emergency shutdown breaker circuit REPO  
(jumper Y  
AC  
AC  
harmonic filter  
8
7
6
5
4
3
correction with optional electric boad for  
measuring battery temperature  
XA1 terminal block  
-12V  
thermal measuring  
2
1
power supply  
+12V  
of the  
harmoinc-filter  
circulator  
temperature  
signal  
harmoni  
cs over-temperature fault  
2
battery-room ventilation fault  
1
XR3 connector  
-12V  
input or output signals:  
battery cubicle  
10  
9
8
7
6
XA13 terminal block  
free auxilary contact  
QF1 battery  
circuit breaker  
closed  
-12V  
24V CC  
2
1
5
4
-12V  
OF1 battery circuit-breaker opening command  
QF1 battery  
circuit breaker  
opening command  
2
1
3
2
1
AC  
XR4 connector  
output signals:  
10  
9
8
7
6
5
4
3
2
1
Optional alarm  
EPO  
AC  
AC  
XR4 connector  
output signals:  
10  
9
load or inverter  
load or battery  
8
7
6
5
4
3
2
1
low-battery shutdown warning  
86-133060-00 A00  
Installation  
3 — 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
3.7.1 Battery Circuit Breaker "QF1" Connection  
Connect the cable from connector XR3 (pins 2 to 8) on the "Media Contacts 11" board in the UPS cabinet to  
connector XR1 in the battery cabinet containing battery circuit breaker QF1.  
IMPORTANT  
In the case of a complex installation with parallel units, there should be only one  
emergency shutdown pushbutton and this pushbutton must interrupt all the units.  
This pushbutton must therefore have as many contacts as there are units in the  
installation. The emergency shutdown pushbutton turns off the rectifier/ chargers  
and inverters, opens the battery circuit breakers (QF1), the input circuit breaker (Q1)  
on the normal source, the backfeed protection contactor (K4S) on the bypass AC  
source, blocks the static switches and activates a contact on the "Media Contacts 11"  
board (terminals 1 to 3 on connector XR4).  
3.8  
Installation of the "Temperature Monitor" in the Battery Cabinet  
The "Temperature Monitor" unit is placed inside the battery cabinet housing circuit-breaker QF1. See Figure 3-9.  
1. Open the unit cover, and before fixing, break the self-cleaving seal on the base of the unit for insertion of the  
connecting cable.  
2. Fix the unit on the plate using the self-adhesive sticker and a screw (nut and washer combination, diameter 4  
mm, length 16 mm, not supplied).  
3. Connect and put back the cover. The temperature sensor MUST be placed at the top of the cabinet to work  
properly.  
4. Tie the connecting cable to the cabinet upright so that it does not pull on the unit.  
Figure 3-9: Installing the "Temperature Monitor" in a Battery Cabinet.  
Battery Cabinet  
Temperature  
Monitor unit  
Tie the cable  
to the cabinet  
upright  
QF1  
to UPS Cabinet  
3 — 10  
Installation  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
3.8.1 "Temperature Monitor" installation in a Battery Room  
The "Temperature Monitor" should be secured against a wall or any vertical support. See Figure 3-10.  
1. Choose a location near the batteries and away from draughts which adversely affect the accuracy of  
temperature measurements. Dimensions: 75 x 75 x 21 mm.  
2. Use the holes provided in the base plate to screw the unit to the vertical support, unless the connecting cable  
runs on the surface, break the knock-out in the unit base plate provided for cable entry. Secure the cable by  
suitable means so that it does not pull on the unit.  
Figure 3-10: Temperature Monitor" Base.  
Mounting Hole  
board  
Cable Entry  
Mounting Hole  
Dimensions: 75 x 75 x 21 mm  
86-133060-00 A00  
Installation  
3 — 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
3.8.2 Connection of the Battery "Temperature Monitor"  
This unit must be connected to the XR2 connector on the remote indications "Media Contacts 11" board of the UPS  
cabinets. For the location of the "Media Contacts 11" board, marked "O" see Figure 2-3, page 2—5.  
2
Use a shielded cable made up of 2 twisted telephone pairs with a conductor cross-section of at least 0.1 mm , not  
longer than 100 m in length. Do not forget to connect the cable shield to ground pin 12 on connector XR2;  
In the case of a parallel UPS configuration, the connections between cabinets may be made by means of a shielded  
cable made up of 1 or 2 twisted telephone pairs. In this case, the total length of all the connecting cables must not  
exceed 100 m;  
A "Temperature Monitor" unit can be connected to several UPS cabinets only when the batteries of these cabinets  
are located in the same room at the same ambient temperature.  
Figure 3-11: Single UPS Unit Connection of the Battery "Temperature Monitor".  
Shielded cable  
(2 twisted  
Battery Temperature Monitor  
telephone pairs)  
XR2 connector on  
'Media Contacts 11'  
Board:  
DC +  
DC-  
each  
12  
11  
10  
9
XR2  
8
7
6
5
4
3
-12V  
+12V  
DC +  
DC -  
power supply  
temperature  
signal  
2
XR1  
1
+12  
-12  
(unit shown open)  
Refer to Appendix C for link-up options using an IBM AS400 computer for additional monitoring capability.  
3 — 12  
Installation  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
Figure 3-12: Connection of the Battery "Temperature Monitor." (In Parallel UPS Units with Batteries in Same Room.)  
Shielded cable  
(2 twisted  
Battery Temperature Monitor  
telephone pairs)  
XR2 connector on  
'Media Contacts 11' Board  
in Galaxy PW unit 1:  
DC +  
DC-  
each  
12  
11  
10  
9
XR2  
8
7
6
5
4
3
-12V  
+12V  
DC +  
DC -  
power supply  
temperature  
signal  
2
XR1  
1
XR2 connector on  
'Media Contacts 11' Board  
in Galaxy PW unit 2:  
+12  
-12  
(unit shown open)  
each  
12  
11  
10  
9
8
7
6
5
4
3
2
Shielded cable  
(1 or 2 twisted  
telephone pairs)  
DC +  
DC -  
temperature  
signal  
1
XR2 connector on  
'Media Contacts 11' Board  
in Galaxy PW unit n:  
each  
12  
11  
10  
9
8
7
6
5
4
3
2
DC +  
DC -  
temperature  
signal  
1
86-133060-00 A00  
Installation  
3 — 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
Figure 3-13: Connection to the "Media Contacts 11" Board.  
Media Contacts 11 Remote Indicators Board  
XR2  
XR3  
12 - - - - - - - - - -1 10 - - - - - - - -1 10 - - - - - - - -1 10 - - - - - - - -1  
XR2  
XR3  
XR4  
XR5  
XR4  
XR5  
NOTE: the corresponding IBM AS400 signal names  
are given in parapharase.  
XR1  
XR's connector  
output signals:  
10  
9
8
7
6
5
4
3
2
1
load or inverter (ON)  
load or battery (utility failure)  
low-battery shutdown warning  
(low battery)  
1
2
3
4
5
1
2
3
4
5
6
7
8
6
7
8
9
9
10  
11  
12  
13  
14  
15  
load on bypass (bypass active)  
commond W (system ground)  
male 9-pin SUB-D  
connector  
male 15-pin SUB-D  
connector  
IBM AS400  
Galaxy PW  
3.9  
About Final Installation Steps  
After making the connections, install the front and rear base plates of the cabinets, clipping them to the feet of the  
cabinets (unless the connecting cables are fed through these openings), and refit the terminal shields of the terminal  
blocks, switches and circuit breakers.  
3 — 14  
Installation  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
4.0  
Scope  
Operation describes the start-up for single and parallel units, modes of operation, normal specifications for operating  
the Galaxy PW™ 100 to 225kVA, including display messages, measurement systems, alarms, batteries, and log  
time stamping operations.  
WARNING  
Rectifier/charger start-up is automatic when normal AC input circuit breaker Q1  
is closed. DC voltage is present in the DC bus.  
4.1  
Start-up of a Module  
Rectifier/charger start-up is automatic when the normal AC input circuit breaker Q1 is closed. The green  
"rectifier/charger" light 1 on the control panel goes on. Close battery circuit breaker QF1.  
Figure 4-1: Control Panel and Circuit Breaker Diagram.  
1
2
3
4
5
6
inverter (B):  
DC to AC  
power  
rectifier/  
charger (A):  
AC to DC  
power  
1
2
isolation and  
protection:  
Q5N  
normal  
AC  
*FUSE  
*FUSE  
7
input (1)  
Q1  
22  
8
isolation  
and  
QF1: isolation  
protection  
harmonic  
fliter  
and protection  
9
10  
11  
12  
13  
14  
20  
15  
V
A
W.Hz  
battery (D):  
backup power  
17  
16  
18  
isolation:  
fault  
Q4S  
static bypass (C):  
bypass  
AC  
19  
21  
(2)  
input  
maintenance bypass:  
Q3BP  
4.1.1 Start-up of an Inverter  
When the rectifier/charger is on, press the "inverter ON" button 7 on the control panel. The green "inverter" light  
4 flashes.  
4.1.2 Emergency Power Off (EPO)  
The UPS emergency shutdown function is generally wired to a "mushroom-head" type emergency-off pushbutton.  
In case of its use, the pushbutton contact has to reset.  
IMPORTANT  
After EPO/REPO, unit has to be reset by opening M2 feed (switch Q4S). Open  
switch Q5N also, and then follow the procedure of single UPS for single unit or  
parallel UPS for parallel units to start-up the system.  
86-133060-00 A00  
Operation  
4 — 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
4.1.3 Single UPS Unit  
The inverter starts, then, if the bypass AC source transfer conditions are satisfied, the load is transferred to the  
inverter, if the on-line mode is selected.  
For on-line mode:  
The green "inverter" light 4 remains on.  
The "static-bypass" light 3 goes off.  
Figure 4-2: Single UPS Diagram .  
A
B
C
1
D
2
4.1.4 Parallel UPS Unit  
The inverter starts and awaits the start of the other inverters. When they are all on or enough have been started to  
supply the rated load power, the output switch for each running inverter closes and the load is supplied with power:  
The green "static-bypass" light 3 goes off.  
The green "inverter" light 4 on the control panels of the running inverters goes on.  
Figure 4-3: Two Parallel Connected UPS Units.  
Q3BP  
Q5N  
1
S
2
2
Galaxy 1  
1
2
Galaxy 2  
Figure 4-4: Four Parallel Connected UPS Units.  
Q3BP  
Q5N  
1
2
2
Galaxy 1  
1
2
Galaxy 2  
1
2
Galaxy 3  
1
2
Galaxy 4  
4 — 2  
Operation  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
4.2  
Operation in On-line Mode  
4.2.1 Normal Operation  
Normal AC source power is available, see Figure 4-5.  
Lights 1 , 4 and 5 shine green on the control panel.  
-The power necessary for the load is provided by the normal AC source (1) through the rectifier/charger (A)  
and the inverter (B). The rectifier/charger (A) also supplies the power to float charge and recharge the  
battery if any.  
The output voltage (DC) is regulated to supply:  
The float-charging or the recharging voltage for vented lead-acid or Ni/Cd batteries.  
- a single charge voltage for sealed lead-acid batteries.  
The voltages depend on the number of battery cells and the battery manufacturer. Factory set, they may also be  
adjusted by support technicians.  
An electronic board continuously measures the battery temperature and automatically adjusts the voltages.  
NOTE  
In parallel Galaxy PW™ systems, the power drawn by the load is equally shared  
between the different units.  
Figure 4-5: Normal Operation Indicator Diagram.  
1
4
5
1
2
A
B
C
1
D
2
86-133060-00 A00  
Operation  
4 — 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
4.2.2 Operation with the Normal AC Source Down  
In the event of a normal AC source failure or voltage outside specified tolerances of 10% in amplitude ( 15%  
optionally), the rectifier/charger (A) stops and the battery (D) supplies the necessary backup power to the load via  
the inverter (B).  
The battery, float-connected between the rectifier/charger and the inverter, discharges during this operating mode:  
lights 2 , 4 and 5 shine green.  
The user is warned of battery operation by the slow beeping of the buzzer 6 , see Figure 4-6, and the message  
"LOAD PROTECTED, BATTERY DISCHARGING", followed by the remaining backup time and the percent load.  
This information is also available via volt-free changeover contacts for remote control devices.  
Figure 4-6: Normal AC Source Indicator Diagram.  
2
4
5
1
2
A
B
C
1
2
D
4 — 4  
Operation  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
4.3  
Operation with the Normal AC Source Restored  
When normal AC source power (1) is restored or its voltage returns to within specified tolerances, the system  
automatically returns to its normal operating mode described above (on the condition it did not reach the end of  
battery power). If the end of battery power was reached (with the resulting inverter shutdown), the rectifier/charger  
(A) restarts automatically, but the inverter (B) must be restarted manually.  
The rectifier/charger recharges the battery (D) which was discharged during the mains outage. During battery  
charging, light 2 flashes green.  
The message "BATTERY CHARGING" is displayed, together with the value of the recharging current and battery voltage.  
Figure 4-7: Normal Operation Mode Indicator Diagram.  
1
2
4
5
1
2
A
B
C
1
2
D
The battery charge cycle takes place in two steps: See Figure 4-8.  
step 1: the battery is recharged at a constant current limited to 0.1C10 (i.e. 1/10th of the battery capacity specified  
for a 10 hour discharge). The DC voltage increases with the battery charge until the charge level is reached.  
step 2: the battery is recharged at constant voltage equal to the charge level. The charging current gradually  
decreases until reaching a specified low value (floating current).  
For vented lead-acid batteries, the rectifier/charger supplies the charging voltage for 0 to 255 hours (parameter  
defined by the after-sales support department) and then the floating voltage. For sealed lead-acid batteries, the  
charging and floating voltages are the same.  
NOTE  
If the normal AC source failure is shorter than 0 to 255 seconds (default value = 30  
seconds) (parameter defined by after-sales support department), the charger  
automatically supplies the floating voltage given the low battery discharge.  
86-133060-00 A00  
Operation  
4 — 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
Figure 4-8: Battery Charge Cycle Chart.  
U charge/floating  
(sealed batteries)  
U/I  
voltage  
current  
U "floating"  
(vented batteries)  
0,1 C10  
current  
limiting  
constant voltage  
decreasing current  
t
4.4  
Operation with Engine Generator Set  
If a stand-by generator is included in the installation, it is generally started automatically in the event of a normal AC  
source failure and connected to the main low voltage switchboard. It is disconnected when normal AC source power  
is restored.  
With such a system, the required battery time may be reduced to the time necessary for starting and bringing on  
line the stand-by generator. The battery (D) supplies power to the inverter (B) during the transfers:  
Normal AC source to the generator.  
Generator to the normal AC source.  
The transfer sequences described above (normal AC source battery, battery generator, generator battery,  
and battery normal AC source) are fully automatic. They in no way affect the load and require no manual  
operation by the user.  
NOTE  
To avoid load surges on the generator, the rectifier/charger is started with a 10  
second maximum current consumption walk-in (lasting 3 to 10 seconds,  
depending on the percent load).  
To avoid overloading an undersized engine generator set, it is possible to set a  
maximum power level drawn by the normal AC input. Any additional power  
required is supplied by the battery. This modification can be made on site by an  
MGE UPS SYSTEMS field engineer  
Figure 4-9: Installation with an Engine Generator Set.  
Galaxy PW  
generator  
main LV switchboard  
C
B
Mains 2  
Mains 1  
G
A
HV system  
D
4 — 6  
Operation  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
4.5  
Battery Time  
The available battery time during a normal AC source outage depends on the:  
Rated capacity of the battery.  
Power consumed by the load.  
Temperature of the battery.  
Age of the battery.  
The specified battery time corresponds to a minimum duration at full rated load.  
The actual backup time can therefore be greater if the system operates below its full rated load during the normal  
AC source outage. Operation on battery power can be extended beyond the specified time by reducing the load  
power consumption (by disconnecting non-critical loads).  
A "low battery" warning signal is sent via volt-free changeover contacts for remote control devices when the battery  
voltage reaches a level slightly above the minimum level. This signal warns the user of the imminent end of battery  
power. On the device itself, the buzzer beeps rapidly.  
The message "LOW-BATTERY SHUTDOWN WARNING" is displayed, followed by the remaining backup time and  
the percent load. Light 2 turns red and flashes.  
Battery power stops when the voltage supplied by the battery reaches the minimum threshold. This results in  
inverter shutdown and transfer of the load without interruption to the bypass AC source. Light 2 shines red (not  
flashing). The message "LOAD NOT PROTECTED, ON-LINE MODE" is displayed and the buzzer sounds continuously.  
If the bypass AC source also fails, the load is no longer supplied. The inverter automatically shuts down when the  
time on battery power exceeds three times the specified backup time.  
NOTE  
The "low battery shutdown" warning signal can be sent with an adjustable time  
delay prior to the effective end of battery power.  
4.6  
Inverter Shutdown or Overload  
Devices or installations operating in on-line mode with a Bypass AC source.  
Figure 4-10: Operating in On-line Mode Diagram.  
3
5
1
2
A
B
C
1
D
2
86-133060-00 A00  
Operation  
4 — 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
4.6.1 Single UPS Unit (On-line mode)  
In the event of a UPS shutdown (initiated by the user or by an internal protective device), the load is automatically  
transferred to the bypass AC source. If transfer conditions are satisfied, transfer takes place instantly, without inter-  
ruption to the load.  
NOTE  
Transfer conditions are not satisfied when bypass AC source characteristics are  
outside tolerances (voltage: 10%. frequency as per personalization. phase sync  
with inverter 3°).  
In the event of a major transient overload (greater than 1.65 In), immediate transfer takes place as above, without  
interruption to the load.  
The return to the inverter is automatic when the overload disappears if the number of possible returns has not been  
reached (0 to 255, programmable by personalization). If this number has been reached, the load continues to be  
supplied by the bypass AC source. This operating mode allows start-up of load devices causing high inrush currents.  
This system requires satisfied transfer conditions. If the conditions are not satisfied, the inverter will current limit to  
165% of its rated current for 1 second before stopping.  
In the event of a small but extended overload (i.e. a continuous level of power exceeding the full rated load), the  
inverter will continue to supply power for a period depending on the magnitude of the overload (10 minutes for a  
125% overload, 1 minute for a 150% overload). See the overload curve in Figure 4-11.  
In all the above cases, inverter shutdown and supply of the load via the bypass AC source results in the  
following on the control panel:  
- light 4 goes off,  
- activation of the buzzer (continuous beep),  
- light 3 shines green,  
- the message "LOAD NOT PROTECTED, ON-LINE MODE" is displayed.  
4.6.2 Parallel UPS Without Redundancy  
WARNING During maintenance operation, when CB1 (MBP) is closed and CB2 (UPS  
ISOLATION) is open, each UPS control panel display will show a message  
“LOAD PROTECTED” when the UPS is placed in ON-LINE MODE. In this  
mode the critical load is not protected because it is supplied by the mainte-  
nance bypass power.  
4 — 8  
Operation  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
The shutdown of one inverter results in overload on the other inverters in operation. Two cases may then arise:  
A) if the overload on each remaining inverter is > than 1.65 in, the load is immediately transferred to the bypass  
AC source.  
B) if the overload is less than 1.65 in, the remaining inverters support the overload (see curve in Figure 4-11), and  
the load is transferred to the bypass AC source.  
After this transfer:  
- the light 4 goes off,  
- the buzzer is activated and sounds continuously,  
- the light 3 goes on and turns green,  
- the message "LOAD NOT PROTECTED, PARALLEL ON-LINE MODE" is displayed.  
Figure 4-11: Overload Curve Diagram.  
I
1,5 In  
1,35 In  
1,25 In  
1,15 In  
1,10 In  
1,05 In  
In  
1
2
3
4
5
6
7
8
9
10  
30  
120 t (min)  
4.6.3 Parallel UPS With Redundancy  
The shutdown of one UPS unit is of no consequence for the load. The others each take up an equal amount of load  
power and the load continues to be supplied normally.  
Unit shutdown results in the following on the control panel:  
- Lights 4 and 5 go off,  
- Activation of the buzzer (continuous beep),  
- The message "LOAD NOT PROTECTED, PARALLEL ON-LINE MODE" is displayed.  
- In the event of an overload, the system only loses its redundancy as long as the overload is less than the  
total rated power of the functioning units. If the overload is greater, the operating mode is that previously  
described for systems without redundancy.  
4.7  
Output Voltage Quality and Continuity  
The output voltage is stable in amplitude and frequency and is free of interruptions or transients outside specified  
tolerances, irrespective of normal AC source or load disturbances (outages, load step changes, etc.).  
86-133060-00 A00  
Operation  
4 — 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
4.7.1 Steady State Voltage Regulation  
For stable or slowly varying load conditions, the inverter output voltage is regulated to within 0.5% in amplitude.  
The frequency of the output voltage can theoretically be regulated to within 0.1% of the rated value, however the  
output frequency range may be intentionally extended to a maximum of 2 Hz so that the inverter can remain  
synchronized with the bypass AC source and its inherent frequency fluctuations, thus enabling transfer of the load  
to the bypass line at any time.  
When the bypass AC source frequency returns to within the specified tolerances, the inverter is gradually re-  
synchronized to the bypass line at a rate of 0.5 Hz to 2 Hz/s (as per the value personalized by the after-sales  
support department), thus avoiding exposing the load to sudden frequency variations.  
4.7.2 Transient Voltage Regulation  
The inverter output voltage is not notably affected by instantaneous major variations in load characteristics.  
This is made possible by the PWM (Pulse Width Modulation) chopping technique and the microprocessor-based  
regulation system that instantly compensates for any variation. In particular, the inverter output voltage remains  
within +/- 2% of the rated voltage for load step changes of 0 to 100% or of 100 to 0%.  
The battery charge cycle takes place in two steps:  
step 1: The battery is recharged at a constant current limited to 0.1C10 (i.e. 1/10th of the battery capacity specified  
for a 10 hour discharge). The DC voltage increases with the battery charge until the charge level is reached.  
step 2: The battery is recharged at constant voltage equal to the charge level. The charging current gradually  
decreases until reaching a specified low value (floating current).  
For vented lead-acid batteries, the rectifier/charger supplies the charging voltage for 0 to 255 hours (parameter  
defined by the after-sales support department) and then the floating voltage. For sealed lead-acid batteries, the  
charging and floating voltages are the same.  
4 — 10  
Operation  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
4.8  
Measurement System  
The display may be used to read a number of input and output measurements made at different points in the system.  
See Figure 4-12.  
Normal AC source 1  
- phase-to-phase voltages,  
- currents of the three phases,  
- frequency.  
Inverter output 4  
- frequency  
Total load 6  
- phase-to-neutral voltage.  
- phase-to-phase voltages.  
- currents of the three phases.  
- frequency.  
Bypass AC source 2  
- phase-to-neutral voltage,  
- phase-to-phase voltages,  
- frequency,  
- active and apparent power.  
- currents of the three phases.  
Battery 3  
- voltage.  
- charge or discharge current.  
- remaining battery time (for the UPS unit concerned).  
- battery temperature.  
Figure 4-12: Measurement System Diagram.  
1
3
4
6
U - I - F  
U - I  
F
U - V - I - F - P  
A
B
C
Q1  
Q5N  
1
QF1  
D
2
U - V - I - F  
Q4S  
2
86-133060-00 A00  
Operation  
4 — 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
4.8.1 Voltage Measurements  
These measurements may be accessed by pressing the "V" key 13 . The following data is displayed.  
Note:  
RMS  
U12  
U23  
U31  
M1  
----  
----  
----  
M2  
----  
----  
----  
LOAD RMS  
M2  
----  
----  
----  
LOAD  
----  
----  
M1: normal AC source  
M2: bypass AC source  
----  
----  
----  
V1  
V2  
V3  
----  
4.8.2 Current Measurements  
These measurements may be accessed by pressing the "A" key 14 . The following data is displayed.  
Note:  
RMS  
U12  
U23  
U31  
M1  
----  
----  
----  
M2  
----  
----  
----  
LOAD RMS  
M2  
----  
----  
----  
LOAD  
----  
----  
CF: crest factor  
----  
----  
----  
V1  
V2  
V3  
----  
4.8.3 Power and Frequency Measurements  
These measurements may be accessed by pressing the "W.HZ" key 15 .  
The following data is displayed.  
Note:  
PF: power factor  
RMS  
U12  
U23  
U31  
M1  
----  
----  
----  
M2  
----  
----  
----  
LOAD RMS  
M2  
----  
----  
----  
LOAD  
----  
----  
----  
----  
----  
V1  
V2  
V3  
----  
4.8.4 Battery Measurements  
These measurements may be accessed by pressing the "battery" key 18 . The following data is displayed.  
RMS  
U12  
U23  
U31  
M1  
----  
----  
----  
M2  
----  
----  
----  
LOAD RMS  
M2  
----  
----  
----  
LOAD  
----  
----  
----  
----  
----  
V1  
V2  
V3  
----  
4 — 12  
Operation  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
4.9  
Selections and Settings  
These selections and settings may be accessed by pressing the "contrast" key 12 .  
The following menu is displayed:  
CHOOSE LANGUAGE  
CONTRAST SETUP  
BUZZER SETUP  
LAMP TEST  
DATE AND TIME  
INVERSE VIDEO  
PAST EVENTS  
BATTERY TEST  
Selecting the language:  
FRENCH  
ENGLISH  
GERMAN  
ITALIAN  
SPANISH  
DUTCH  
SWEDISH  
PORTUGUESE  
Adjusting the display contrast:  
DISPLAY CONTRAST SETUP  
CHOOSE WITH KEYS OR ▼  
VALIDATE WITH KEY ø  
Adjusting the buzzer volume:  
BUZZER VOLUME SETUP  
CHOOSE WITH KEYS OR ▼  
VALIDATE WITH KEY ø  
86-133060-00 A00  
Operation  
4 — 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
Lamp test:  
When this function is selected, all the lights shine orange for three seconds.  
Set Date and Time:  
Use the "▲▼" keys to enter the data and confirm using the "ø" key.  
DATE AND TIME SETUP  
YEAR  
DAY  
----  
--  
MONTH  
HOURS  
--  
--  
MINUTES  
--  
SECONDS --  
Inverse Video:  
When this function is selected, the text and background colors are reversed (white text on black or black  
text on white).  
Past Events:  
See section 3.15 "logging and Time-Stamping" for event details.  
CHARGE LEVEL  
=
-- %  
REMAINING SERVICE LIFE  
MANUAL TEST press key ø  
= -- MONTH  
AUTO TEST  
press key ø  
Battery test:  
the screen opposite is displayed when a battery test is requested. It indicates the battery charge status and  
the remaining service life. A manual or automatic test may be requested.  
- this screen is displayed during a battery test, whether manual or automatic,  
TESTING BATTERY  
U BATTERY =  
--- V  
4 — 14  
Operation  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
- this screen is displayed following a positive, manual battery test:  
BATTERY TEST RESULT OK  
- this screen is displayed following a negative, manual battery test:  
BATTERY TEST RESULT NOT OK  
- this screen is displayed following a positive, automatic battery test. It indicates the time since the last test and  
provides access to test settings:  
TIME SINCE LAST TEST  
WEEK -- DAY -- HOUR --  
LAST BATTERY TEST RESULT OK  
NEW PARAMETERS  
YES = ▲  
NO = ▼  
- this screen is displayed following a negative, automatic battery test. It indicates the time since the last test  
and provides access to test settings,  
TIME SINCE LAST TEST  
WEEK -- DAY -- HOUR --  
LAST BATTERY TEST RESULT NOT OK  
NEW PARAMETERS  
YES = ▲  
NO = ▼  
- this screen is displayed when the user requests access to the automatic test settings. It is possible to modify  
the interval between two automatic tests,  
SELECT TIME OF NEXT TEST WITH KEYS ▲ ▼  
CHANGE UNITS WITH ø  
WEEK -- DAY -- HOUR --  
confirm with key  
- this screen is displayed when the battery test cannot be completed.  
TEST INTERRUPTED  
CHECK PRESENCE OF THE BATTERY  
CHECK ALARMS  
86-133060-00 A00  
Operation  
4 — 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
4.10  
Alarms  
The auto diagnostic system considers any system status other than normal as a problem.  
Before taking any action, note down the messages displayed on the control panel.  
Certain problems may prevent the control panel from functioning.  
In this case, it is strongly recommended to call the MGE UPS SYSTEMS Customer Support Service at:  
1-800-438-7373  
.
A) If the load is still correctly supplied with power, it has probably been transferred to the bypass AC source (static  
bypass) and is therefore no longer protected (if the system is in on-line mode).  
B) If the load is no longer supplied with power, transfer it manually to the maintenance bypass.  
Figure 4-13: Display of Alarm Messages..  
primary message  
(ALARM MESSAGE N° 1)  
(ALARM MESSAGE N° 2)  
(LAST ALARM MESSAGE)  
main screen  
4.11  
Maintenance Bypass Option  
The Maintenance bypass option provides a direct bypass AC input source (mains 2) that can be used to supply the  
critical load while the UPS is being serviced.  
This operation is possible only if the system includes a bypass AC source. It results in the load being directly  
supplied by the Bypass AC source via Maintenance Bypass switch Q3BP, thus ensuring a higher level of security in  
the event of a malfunction.  
Switching procedures are explained on drawings next to each switch in the UPS cabinet and the External Bypass unit.  
4 — 16  
Operation  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
4.12  
Logging and Time-Stamping  
4.12.1 Event Time-Stamping  
Time-stamping of events by Galaxy PW™ makes it possible to:  
Log the events.  
Consult the last 500 events that occurred on the Galaxy PW™ UPS.  
Consult general statistical data on UPS operation.  
Consult measurement records for a number of physical values concerning system operation.  
The time-stamping information may be accessed via the Galaxy PW™ keypad and display (standard equipment).  
This information may also be forwarded for the Teleservice function using the JBUS RS232/485 communications  
board. When the optional JBUS RS232/485 communications board is installed, the time-stamped information can  
be sent to the Teleservice center. Refer to Utilization of Teleservice Card options Appendix B.  
4.12.2 Consulting Logged (time-stamped) Events  
When the PAST EVENTS command is selected, the system displays a screen indicating the last event logged. Log  
screens are very similar to those displayed for current events. However, log screens include a line indicating the  
corresponding date and time with the mention "Appearance of" or "Disappearance of", followed by the standard text  
for the event (see example opposite). Consult the user manual for indications on the meaning of events.  
The complete log may comprise up to 500 events. If over 500 events have occurred, only the last 500 may be  
consulted:  
1. Press the key to display the event that occurred just before the displayed event. If the displayed event is the  
oldest in the list, the display is not modified.  
2. Press the key to display the event that occurred just after the displayed event. If the displayed event is the  
most recent in the list, the display is not modified.  
Example:  
02/09/1997 07:25:03 Appearance:  
MAINS 2 INPUT SWITCH Q4S IS OPEN  
Note: numerical values are never indicated in screens for time-stamped events.  
Example:  
03/09/1997 15:30:23 Disappearance:  
OVERLOAD  
RATED CURRENT PER PHASE  
= _ _ _ A  
CHECK LOAD LEVEL  
86-133060-00 A00  
Operation  
4 — 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
4.13  
Setting the Date and Time for the UPS - Utilization Via the Galaxy PW™ Display  
The time and date can be set for the UPS via the main menu on the display (see below), using the DATE AND TIME  
command. The time-stamping information, statistics and measurement records are also available via the same  
menu, using the PAST EVENTS command.  
Simply select the desired command with the ">" sign that can be moved using the and keys. The selected  
command can be confirmed by pressing the  
key.  
When the DATE AND TIME command is selected, the date and time is displayed in the order of year, month, day,  
hours, minutes, and seconds. When you leave this command, the date and time is displayed in the reverse order.  
DATE AND TIME SETUP  
>YEAR  
DAY  
1997  
8
MONTH  
HOURS  
9
8
MINUTES  
11  
SECONDS 42  
▲ ▼  
The current values are automatically displayed.  
Modify any of the displayed values by:  
1. Position the ">" sign opposite the value to be modified. Then press the ø key.  
2. Use the and keys to modify the value.  
3. Use the key to increment the value by one.  
4. Use the key to decrement the value by one.  
The selected value can be confirmed by pressing the ø key. A second value may then be selected for  
modification, again using the and keys. Modifications are made and confirmed value by value.  
5. Press the  
key at any time to exit the DATE AND TIME function.  
That is the only means to leave the function. If no modifications to values are confirmed, exiting the function  
corresponds to cancelling the request.  
4 — 18  
Operation  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
4.14  
Consulting Statistics  
FIGURES SINCE COMMISSIONING  
total backup time (h):  
0
0
total time on static switch (h):  
total time on UPS (d):  
3627  
1
total time with Tbatt >25°C (h):  
FIGURES SINCE RESET  
last reset:  
05/09/1997  
0
elapsed backup time (min):  
Legend:  
total backup time (h): This is the total time of operation on battery power since initial startup of the UPS. It  
is expressed in hours.  
total time on static  
switch (h):  
This is the total time of operation on the static switch since initial startup of the UPS.  
It is expressed in hours.  
total time on UPS (d): This is the total time that the load has been supplied by the UPS since initial startup.  
It is expressed in days.  
total time with  
Tbatt > 25°C (h):  
This is the total time of operation with the battery temperature greater than 25°C  
since initial startup of the UPS. It is expressed in hours.  
last reset:  
This is the date that the information was last set to zero by the Teleservice function.  
elapsed backup  
time (min):  
This is the total time of operation on battery power since the last reset. It is expressed  
in minutes.  
86-133060-00 A00  
Operation  
4 — 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
FIGURES SINCE RESET  
nb of backups:  
0
0
0
0
0
0
0
nb of backups < 1 min:  
1 min < nb of backups < 3 min:  
nb of backups > 3 min:  
nb of overloads < 5 s:  
nb of overloads > 5 s:  
nb of times TBatt. > 25°C:  
Legend:  
nb of backups:  
This is the number of times the load was supplied by the UPS from battery power  
since the last reset.  
nb of backups < 1 min: This is the number of times the load was supplied by the UPS from battery power for  
less than one minute, since the last reset.  
1 min < nb of  
This is the number of times the load was supplied by the UPS from battery power  
for more than one minute and less than three minutes, since the last reset.  
backups < 3 min:  
nb of backups > 3 min: This is the number of times the load was supplied by the UPS from battery power for  
more than three minutes, since the last reset.  
nb of overloads < 5’s: This is the number of times the UPS was overloaded (output current greater than In)  
for less than five seconds, since the last reset.  
nb of overloads > 5’s: This is the number of times the UPS was overloaded (output current greater than In)  
for more than five seconds, since the last reset.  
nb of times  
This is the number of times the battery temperature was measured at over 25°C,  
since the last reset.  
TBatt. > 25°C:  
4 — 20  
Operation  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
4.14.1 Consulting Recorded Measurements  
Recorded measurements are presented in the same manner (see below):  
the lists indicate the last 30 measurements recorded for the given parameter. The chronological order of  
the measurements is indicated in the Figure opposite.  
the most recent measurement is presented first, in the upper left-hand corner of the list. The following  
measurement is listed just below, and so on until the 30th value listed in the bottom right-hand corner of  
the list.  
the period T between two successive measurements is 30 days. The displayed measurements are instan-  
taneous values.  
PARAMETER NAME (units)  
T=30 days  
last read: 05/09/1997  
M(t+29T)|M(t+23T)|M(t+17T)|M(t+11T)|M(t+05T)  
|
M(t+28T)|M(t+22T)|M(t+16T)|M(t+10T)|M(t+04T)  
|
|
|
|
M(t+27T)|M(t+21T)|M(t+15T)|M(t+09T)|M(t+03T)  
|
|
|
|
M(t+26T)|M(t+20T)|M(t+14T)|M(t+08T)|M(t+02T)  
|
|
|
|
M(t+25T)|M(t+19T)|M(t+13T)|M(t+07T)| M(t+T)  
|
|
|
|
|
|
M(t+24T)|M(t+18T)|M(t+12T)|M(t+06T)|  
|
M(t)  
NOTE  
when this screen is selected, approximately ten seconds are required to call up  
and display the information. If the number of measurements is greater than 30,  
only the last 30 (the most recent) are displayed.  
86-133060-00 A00  
Operation  
4 — 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
The battery capacity is the value measured by the UPS microprocessor. It is expressed in Ampere-hours. This  
value changes over time depending on the parameters of the battery itself and its environment. This measurement  
is used to check that the battery is capable of supplying the rated power in the event of a mains outage.  
BATTERY CAPACITY (Ah)  
T=30 days  
last read: 05/09/1997  
97 |  
96 |  
95 |  
94 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0
0
0
0
0
0
0 |  
The backup time is the value calculated by the UPS microprocessor on the basis of measurements carried out on  
the battery. It is expressed in minutes. The calculation uses the percent load and the battery charge status at the  
time of the measurement.  
BACKUP (min)  
T=30 days  
last read: 05/09/1997  
120 |  
115 |  
110 |  
105 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0
0
0
0
0
0
0 |  
The load level is the ratio between the power supplied by the UPS to the load at the time of the measurement and  
the rated output of the UPS. It is expressed as a percentage.  
OUTPUT LOAD LEVEL(%)  
T=30 days  
last read: 05/09/1997  
63 |  
52 |  
63 |  
63 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0 |  
0
0
0
0
0
0
0 |  
4 — 22  
Operation  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
5.0  
5.1  
Scope  
Maintenance procedures include preventive maintenance, isolation procedures for maintenance, startup for single  
and parallel units after isolation, functional and visual checks, software options and configurations, and testing  
scenarios.  
Preventive Maintenance  
The following preventive maintenance routines should be considered the minimum requirements; your installation  
and site may require additional preventive maintenance to assure optimal performance from your installed Galaxy  
PW™ and associated equipment. These routines should be performed twice a year (more often if required). We  
strongly recommend contracting MGE Customer Support Services for preventive and remedial maintenance.  
The technician or electrician performing preventive maintenance on the UPS must read thoroughly this manual  
Galaxy PW™ Installation and Users Manual (MGE PN 86-133060-00) and be familiar with the indicators, controls,  
and operation of the UPS prior to maintenance.  
Technician or Engineer checks for preventive maintenance:  
a. Isolate and de-energize all Galaxy PW™ equipment for all maintenance operations.  
b. Ensure that all equipment is clean and free of loose dust, dirt, and debris. The exterior of the enclosures may  
be cleaned with a mild solution of soap and water, lightly applied with a lint-free cloth.  
c. Inspect the air intake and exhaust plates and clean as required. Verify that air flows freely through the  
equipment. Clean the air intake and exhaust plates, and the enclosure interior, with a vacuum cleaner.  
d. The Galaxy PW™ module is equipped with air filters that should be changed at regular intervals. Inspect the  
filters regularly to determine how long the filters will last in your installation.  
e. Initiate the start-up procedure, as described in the Installation and Users Manual section 2.7 System Start-up,  
page 2—10.  
f. Test the main operating sequences as applicable to your equipment configuration and installation.  
86-133060-00 A00  
Maintenance  
5 — 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
5.2  
Replacement Parts  
There are no user replaceable parts inside the Galaxy PW™.  
Three levels of replacement parts are available for the Galaxy PW™ UPS. The three levels are designated A, B,  
and C. The level that you should keep on hand for your installation will vary depending on the type of maintenance  
planned on site, and the configuration of your UPS system. Having the replacement parts on hand will prevent any  
unacceptable delays (due to time involved obtaining spare parts) during critical periods, such as system start-up.  
Any items used during start-up will be replaced by MGE at no charge. Contact MGE Customer Support Services for  
specific recommendations.  
A description of each level is provided below:  
Level  
Description  
A
This level of replacement parts consists of consumable items, specifically fuses and air filters. It is  
recommended to have these items on hand during installation of the UPS systems, including initial  
start-up.  
B
C
This level of replacement parts is recommended when the user can tolerate short-duration UPS down-  
time to obtain replacement parts in the event of a major UPS failure. This level of replacement parts  
consists of consumable items, specifically fuses, air filters, an inverter leg, and the most critical circuit  
board assemblies.  
This level of replacement parts is recommended when the user can tolerate only a minimum of down-  
time in the event of a major UPS failure. This level of replacement parts consists of consumable items,  
specifically fuses, air filters, an inverter leg, and a complete set of circuit board assemblies.  
5.2  
Maintenance Isolation Procedures  
CAUTION PARALLEL UPS WITH EXTERNAL MAINTENANCE BYPASS During mainte-  
nance operation, when CB1 (MBP) is closed and CB2 (UPS ISOLATION) is  
open, each UPS control panel display will show a message “LOAD  
PROTECTED” when the UPS is placed in ON-LINE MODE. In this mode the  
critical load is not protected because it is supplied by the maintenance  
bypass power.  
5.2.1 Single UPS Unit  
During maintenance, the UPS must be isolated from the normal and bypass AC source, the battery and the load.  
UPS Isolation  
Proceed in the following order: (see Figure 5-2):  
1. Shut down the inverter (press the "inverter OFF" button 8 for three seconds),  
2. Close bypass switch Q3BP,  
3. Open isolating switches Q5N, Q4S, QF1 and Q1.  
The UPS is powered down once the capacitors have discharged (a few minutes).  
5 — 2  
Maintenance  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
Start-up  
Following servicing, proceed in the following order: (See Figure 5-3)  
1. Close switch Q1, then after approximately ten seconds, switches QF1, Q5N and Q4S,  
2. 0pen bypass switch Q3BP,  
3. Start the inverter (press the "inverter ON" button 7 ).  
Figure 5-1: UPS Isolation Diagram for Normal AC Bypass Source.  
A
B
Q1  
Q5N  
1
2
QF1  
D
C
Q4S  
Q3BP  
Figure 5-2: Panel Procedures for UPS Isolation.  
7
8
1
Q1  
Q4S  
Q3BP Q5N  
1
1
1
1
1
1
2
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
3
0
1
4
0
QF1  
5
0
1
I
1
1
1
0
0
0
6
0
Figure 5-3: Start-up After Isolation Procedure is Completed.  
Q1  
Q4S  
Q3BP Q5N  
1
1
1
1
F
F
0
0
0
1
2
3
4
5
6
0
QF1  
0
1
I
1
0
1
1
1
1
1
1
0
0
0
0
0
0
0
1
0
1
1
0
0
1
0
86-133060-00 A00  
Maintenance  
5 — 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
CAUTION  
Work should be carried out in accordance with applicable safety regulations. to  
avoid interrupting the load, the various switching operations must be carried out  
in the correct order. Operations are explained in diagrams placed next to the  
switches. the system cabinet is only partially powered down. The load is still  
supplied via the bypass AC source and switch Q3BP.  
5.3  
Steps for Parallel UPS Redundancy to Increase Output  
PARALLEL UPS WITH EXTERNAL MAINTENANCE BYPASS During mainte-  
CAUTION  
nance operation, when CB1 (MBP) is closed and CB2 (UPS ISOLATION) is  
open, each UPS control panel display will show a message “LOAD  
PROTECTED” when the UPS is placed in ON-LINE MODE. In this mode the  
critical load is not protected because it is supplied by the maintenance  
bypass power.  
First Isolate all UPSs: (Refer to section 5.2, page 5—2)  
See Figure 5-6.  
Proceed in the following order: (See Figure 5-4)  
1. Shut down the inverters (press the "inverter OFF" buttons 8 for three seconds).  
2. Close switch Q3BP and open switch Q5N in the external bypass unit.  
3. Open switches Q1, QF1, and Q5N on the UPS units.  
Figure 5-4: Isolate All UPS’s Procedures Diagram.  
7
8
Galaxy PW  
2
3
4
1
external bypass  
1
1
1
Q3BP  
0
0
0
Q1  
Q4S  
Q5N  
1
1
1
1
0
0
0
Q5N  
0
4
5
6
0
QF1  
0
I
1
0
1
1
0
5 — 4  
Maintenance  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
Start-up  
Following servicing, proceed in the following order: (see Figure 5-5)  
1. Close switches Q5N on the UPS units.  
2. Close switch Q5N in the external bypass unit.  
3. Open switch Q3BP in the parallel-connection unit.  
4. Close switches Q1 and QF1 on the UPS units.  
5. Start the inverters (press the "inverter ON" buttons 7 ).  
Figure 5-5: Start-up Procedure After Isolation Diagram.  
Q1  
Q4S  
0
Q5N  
0
1
0
1
1
1
2
3
4
external bypass  
Q1  
Q4S  
Q5N  
1
1
1
1
0
0
0
Q5N  
1
1
4
5
6
0
0
0
1
Q3BP  
0
QF1  
0
1
8
7
Figure 5-6: Redundancy for Increased Output Diagram.  
Q3BP  
Q5N  
Q1  
Q5N  
1
QF1  
Q4S  
2
2
Galaxy 1  
1
2
Galaxy 2  
Galaxy 3  
Galaxy 4  
1
2
1
2
86-133060-00 A00  
Maintenance  
5 — 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
5.4  
Battery Maintenance  
Consult the instructions supplied by the battery manufacturer. Below are a few general indications:  
Sealed lead-acid Batteries:  
- these batteries require no maintenance, but check the terminals of each cell from time to time and clean  
if necessary.  
Vented lead-acid Batteries:  
- check the electrolyte level regularly and add water if necessary,  
- check the voltage of each cell to determine if it is necessary to equalize the battery,  
- check the terminals of each cell and clean if necessary.  
5.5  
Visual Check  
Power down the system prior to any maintenance operations.  
NOTE  
In redundant parallel UPS systems the check may be carried out successively on  
each UPS unit without interrupting the load. In other configurations, the load  
must be supplied via the maintenance bypass (see "maintenance bypass" in the  
"Alarm" section).  
1. Clean the system regularly, particularly the air filter inlet and outlet grills. Check that the air circulates freely in  
the cabinets. Use a vacuum cleaner if necessary.  
2. Check that nothing hinders the ventilation at the top and at the back of the system.  
5.6  
Functional System Checks  
1. Check that lights 1 , 2 and 3 on the control panel are not red, to avoid an interruption in the supply of power  
to the load due to incorrect transfer conditions or a battery problem.  
2. Press the "inverter OFF" button and check that the buzzer and control panel lights function correctly (see the  
section on operating modes in the introduction).  
3. Press the "inverter ON" button and check again that the control panel lights function correctly.  
4. Run a transfer to battery test. With the inverter on, open input circuit breaker Q1. The orange "battery" light on  
the control panel should light. After two minutes on battery power, close input circuit breaker Q1. The  
rectifier/charger should automatically restart and the orange "battery" light on the control panel should go off.  
5 — 6  
Maintenance  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
5.7  
Testing Parallel Systems  
5.7.1 Galvanic Isolation and Voltage Matching Transformers  
The UPS can be equipped with an isolation or auto transformer on both the input and output to provide galvanic  
isolation or voltage step-up or step-down as required.  
5.8  
Management of Computer Networks  
5.8.1 Integrated SNMP Agent  
This electronic board, installed in the UPS system, enables direct connection to all Ethernet networks using TCP/IP.  
The UPSs may then be supervised via the computer network. Furthermore, they can be used to close system files  
without having to add an external SNMP agent.  
This board is fully compatible with "Solution Pac™" software.  
The RJ45 connector of the communications option delivers information using the SNMP protocol. The sticker  
located on the board indicates the UPS MAC address.  
Figure 5-7: MAC Address Sticker.  
0080C8ABAA01  
The MAC address is written in the following way: 0080C8 ZZ XX YY.  
The default IP address is 168.8.xx.yy (xx and yy are decimal values of XX and YY).  
For example, MAC address 00 80 C8 AB AA 01 is related to IP address 168.8.170.1.  
Please refer to the "userman.doc" user manual contained in the directory "emb/galaxy/snmp/release3.xx" of the  
Solution-Pac CD-ROM in order to discover the management capabilities of your SNMP Galaxy PW™ UPS.  
Please contact your sales representative for more detailed information.  
5.8.2 Two-channel Network Board  
This electronic board comprises two ports, each of which may be user set, either for the U-Talk protocol or as a relay  
contact.  
A) U-Talk is the protocol required to establish contact with the communications software.  
B) Relay contacts may be used for specific network applications (IBM AS400, Novell, etc.).  
86-133060-00 A00  
Maintenance  
5 — 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
(This page left blank intentionally)  
5 — 8  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendices  
Appendix A  
Front Control Panel Display Definitions  
1
"Rectifier/charger" light  
light off: rectifier/charger OFF.  
light shines green: rectifier/charger ON.  
light shines red: rectifier/charger fault, the stored alarm indicates one or several of the following faults:  
- input circuit breaker Q1 open,  
- protection fuse at the rectifier/charger input (FUE) blown,  
- abnormally high internal rectifier/charger temperature,  
- abnormally high battery charge current,  
- abnormally high battery voltage,  
- fault, non-calibration or non-personalization of the electronic control board for the rectifier/charger,  
- fault on the electronic power-supply board,  
- abnormally high temperature in the harmonic filter inductor.  
2
3
"Battery light"  
light off: battery float charging.  
light flashing green: battery recharging.  
light shines green: load on battery power.  
light flashing red: low-battery shutdown warning.  
light shines red: battery at end of backup time and circuit breaker QF1 open, or battery fault.  
"Static-bypass" light  
light off: bypass AC source within specified tolerances and static bypass open.  
light shines green: static bypass closed.  
light shines red: the stored alarm indicates one or several of the following faults:  
- bypass AC source voltage or frequency outside specified tolerances,  
- static-bypass fault,  
- abnormally high internal static-bypass temperature,  
- static-bypass ventilation fault,  
- power-supply fault for the static-bypass control function,  
- fault on the electronic board controlling the transfer function,  
- non-calibration or non-personalization of the electronic control board for the inverter,  
- fault on the electronic power-supply board,  
- fault on monitoring the "inverter ready" response channels (parallel UPS system).  
86-133060-00 A00  
Appendices  
A — 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
4
"Inverter" light  
light off: inverter OFF.  
light flashing green: inverter starting, inverter ON but not connected to the load.  
light shines green: normal inverter operation.  
light shines red: inverter fault, the stored alarm indicates one or several of the following faults:  
- inverter shutdown due to inverter output voltage outside specified tolerances,  
- protection fuse at the inverter output (FUS) blown,  
- abnormally high inverter-output transformer temperature,  
- abnormally high inverter temperature,  
- output-voltage fault (amplitude or phase) (parallel UPSs),  
- fault, non-calibration or non-personalization of the electronic control board for the inverter,  
- fault on the electronic power-supply board.  
5
6
"Load" light  
light off: load not supplied.  
light shines green: load supplied via the inverter or the bypass AC source (via the static bypass).  
Buzzer  
The buzzer sounds in the following situations:  
load supplied by the bypass AC source.  
load on battery.  
operating problems.  
It sounds slowly and discontinuously for a minor problem or when the inverter is on battery power.  
When the alarm "LOW BATTERY SHUTDOWN" is activated, the buzzer sounds more rapidly. Finally, if the inverter  
shuts down, the beep is loud and continuous. The buzzer may be reset by pressing a button. If the buzzer is reset,  
a higher level alarm will set it off again.  
7
8
"Inverter ON" button  
"Inverter OFF" button  
This button is used to start the inverter locally.  
This button turns the inverter off locally.  
9 -10 Keys  
These keys are used to select commands in the main menu and access the secondary  
messages.  
11  
12  
Key  
Key  
This key is used to validate the user’s choice.  
ø
This key is used to access the main menu: display language, display-contrast setting,  
sound level of the buzzer, lamp test, date and time settings, inverse-video and event log.  
A — 2  
Appendices  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
13  
14  
15  
"V" Key  
This key is used to access voltage measurements:  
normal AC source phase-to-phase voltages.  
bypass AC source phase-to-phase and phase-to-neutral voltages.  
load phase-to-phase and phase-to-neutral voltages.  
"A" Key  
This key is used to access current measurements:  
normal AC source, bypass AC source and load currents.  
percent load.  
load crest factor.  
"W.Hz" Key  
This key is used to access other measurements:  
normal AC source, bypass AC source and inverter frequencies.  
level of active and apparent power drawn by the load.  
load power factor.  
inverter load level (percent).  
16  
17  
"Anomaly" indicator light  
This indicator light indicates the presence of anomalies.  
This key is used to access the primary messages.  
Key  
ı
18  
"Battery" Key  
This key is used to access battery measurements:  
battery voltage (or the DC voltage on frequency converters without a battery).  
battery current (charge or discharge).  
battery temperature.  
available battery backup time.  
inverter load level (percent).  
19  
20  
"Forced-transfer"  
This key is used to voluntarily transfer the load to the inverter or from the inverter to the static bypass  
(return transfer). Transfer and return transfer are carried out only following confirmation requested by the  
display and a warning as to the risk of an interruption in the supply of power to the load.  
"Alarm reset"  
This key is used to reset stored alarms. The system accepts resetting only when alarms  
have been cleared.  
21  
22  
"Buzzer reset"  
Display  
This key is used to stop the buzzer. However, new alarms set the buzzer off again.  
The display continuously indicates the system operating status.  
86-133060-00 A00  
Appendices  
A — 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
Display of Primary and Secondary Messages  
The display is structured around primary and secondary messages, measuring tables and setting screens. As a rule,  
the message displayed on the screen is always a primary one. The secondary messages, if any, are accessed by  
pressing keys 9 and 10 . See Figure 2-6, page 2—8.  
The presence of secondary messages is indicated by the arrow Ø at the end of the primary message. Return to  
the primary messages is automatic if the keypad is not used for 2 minutes, or direct by pressing key 17 The display  
screen lights up when a key is pressed, and goes off if no key is pressed for 5 minutes.  
NOTE  
Most functions may be directly accessed. For example, when voltagemeasure-  
ments are currently displayed, it is possible to directly access current  
measurements by pressing the "A" button.  
In addition to keypad operations, the graphical display brings up a window giving the overall device status. The  
message displayed is then said to be primary (see list in the paragraph below). A primary message can be used to  
access the measuring tables using keys 13 , 14 , 15 and 18 on the keypad The configuration screens can be  
accessed by pressing key 12 .  
A flashing arrow appears at the end of a primary message if there is a problem or an alarm. secondary messages  
can be accessed by pressing key 9 on the keypad (see the list of secondary messages). The presence of another  
message is indicated by the arrows Ø and at the end of the secondary message. They can be accessed by  
pressing keys 9 and 10 on the keypad.  
The return to the primary message is automatic after a 2 minute time delay or by pressing key 17 on the keypad.  
IMPORTANT  
Select English U. S. as the display language to match the displays as presented  
in this manual.  
A — 4  
Appendices  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
Primary Messages  
LOAD PROTECTED  
ON-LINE MODE  
This is the normal display when there are no alarms or problems and the load is correctly supplied by the inverter,  
in on-line mode.  
LOAD PROTECTED  
PARALLEL ON-LINE MODE  
This is the normal display when there are no alarms or problems and the load is correctly supplied by the inverter  
in a parallel UPS system, in on-line mode.  
LOAD NOT PROTECTED  
ON-LINE MODE Ø  
This display indicates that the load is not supplied by the inverter, or that there is no battery backup. The arrow Ø  
indicates the presence of one or more problems specified in secondary messages.  
The buzzer sounds continuously.  
LOAD NOT PROTECTED  
PARALLEL ON-LINE MODE Ø  
Situation identical to that in the previous screen, but for parallel UPS systems.  
LOAD PROTECTED  
BATTERY DISCHARGING  
Remaining battery time (min) = XX  
% kW used = XXX  
The load is supplied by the inverter, but the normal AC source is down or outside tolerances and power is supplied  
by the battery.  
This message indicates the remaining battery time in minutes prior to inverter shutdown and the percent load. The  
battery time calculation takes into account:  
The percentage of full rated load power currently being drawn.  
The type of battery.  
Battery temperature.  
Battery age.  
The buzzer sounds slowly and discontinuously.  
LOAD PROTECTED  
LOW-BATTERY SHUTDOWN WARNING  
Remaining battery time (min) = XX  
% kW used = XXX  
This message replaces the preceding if the power outage persists and the warning level has been reached.  
The user is warned that the battery is about to shut down.  
The buzzer sounds rapidly and discontinuously.  
86-133060-00 A00  
Appendices  
A — 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
LOAD PROTECTED  
ECO MODE  
This is the normal display when there are no problems: the load is supplied by the inverter or the bypass AC source,  
and battery backup is available.  
LOAD NOT PROTECTED  
ECO MODE Ø  
This display indicates that the load is supplied but has no battery backup. The arrow Ø indicates the presence of  
one or more problems specified in secondary messages.  
The buzzer sounds continuously.  
LOAD FORCED TO INVERTER  
ECO MODE  
The load has been transferred to the inverter following a specific request by the user.  
Secondary Messages  
LOAD ON MAINS 2  
The load has been transferred to the bypass AC source (M2) and is no longer protected (only in on-line mode). The  
buzzer sounds continuously.  
MAINS 2 OUTSIDE TOLERANCES  
TRANSFER DISABLED  
CHECK MAINS 2  
The bypass AC source (M2) frequency or voltage is outside tolerances and the inverter is unable to synchronize.  
Transfer of the load from the inverter to the bypass AC source (M2) or vice-versa will result in an interruption of the  
supply of power to the load. The buzzer sounds slowly and discontinuously.  
BATTERY OVER TEMPERATURE,  
CHECK VENTILATION  
The battery temperature is outside tolerances. The buzzer sounds slowly and discontinuously  
BATTERY ROOM VENTILATION  
FAULT, CHECK VENTILATION  
A fault requiring servicing has occurred in the battery room ventilation system. The rectifier/charger shuts down after  
a 30-second time delay.  
The user must take steps to re-establish correct operation of the ventilation system.  
This message also signals an abnormally high temperature in the filter inductor.  
The buzzer sounds slowly and discontinuously.  
MAINS 1 OUTSIDE TOLERANCES  
CHECK MAINS 1  
The normal AC source (M1) frequency or voltage is outside specified tolerances and the rectifier/charger has shut  
down. The inverter is on battery power.  
MAINS 1 INPUT SWITCH Q1  
IS OPEN  
The normal AC input (M1) switch Q1 is open. It must be closed for rectifier/charger start-up. The buzzer sounds  
slowly and discontinuously.  
A — 6  
Appendices  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
INTERNAL UPS FAULT  
LOAD TRANSFER FAULT,  
CALL MAINTENANCE  
A fault has occurred in the static switch that transfers the load between the inverter and the bypass AC source (M2).  
Servicing by the after-sales support department is required. The buzzer sounds continuously.  
OVERLOAD  
RATED CURRENT PER PHASE = XXXA  
CHECK LOAD LEVEL  
This display informs the user that load current is greater than rated current, and gives the value. The buzzer sounds  
continuously.  
UPS SHUTDOWN DUE T AN OVERLOAD  
CHECK LOAD LEVEL  
This message follows the preceding when the overload persists. The UPS has shut down and the buzzer sounds  
continuously.  
INVERTER NOT IN PHASE WITH MAINS 2  
TRANSFER DISABLED,  
CHECK MAINS 2  
The phase difference between the inverter and the bypass AC source (M2) is outside tolerances. Transfer of the load  
between the inverter and the bypass AC source (M2) will result in an interruption in the supply of power to the load.  
For parallel UPSs, this message should be interpreted as meaning the phase difference between the inverter for  
which the message is displayed and the other inverters is outside tolerances.  
UPS SHUTDOWN  
BY AN EXTERNAL COMMAND  
The inverter has received a command to shut down. The command is in the form of a signal from received the  
remote-indications relay board which has been set for this function.  
The inverter is started again.  
MAINS 2 INPUT SWITCH Q4S IS OPEN  
The bypass AC source (M2) input switch Q4S is open, i.e. backup power for the load via the bypass AC source (M2)  
is not available.  
INVERTER OUTPUT SWITCH Q5N IS OPEN  
Inverter output switch Q5N is open, i.e. the load cannot be supplied via the inverter.  
BYPASS SWITCH Q3BP IS CLOSED  
Maintenance bypass switch Q3BP is closed. The system is in maintenance configuration and the load is supplied  
by the bypass AC source.  
STATIC SWITCH (M2) OFF  
DUE TO AN OVERLOAD  
The load is no longer supplied by the bypass AC source (M2), due to an extended overload. The buzzer sounds  
continuously.  
86-133060-00 A00  
Appendices  
A — 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
BATTERY CHARGING  
I BAT.=XXX A U BAT. = XXX V  
The battery is currently be recharged.  
BATTERY AT END OF SERVICE LIFE CALL MAINTENANCE  
The battery is nearing the end of its estimated service life. This information is based on average service-life calcu-  
lations since its initial installation. The buzzer sounds slowly and discontinuously.  
EMERGENCY OFF  
This message is displayed when the external emergency-off pushbutton is pressed. The result is:  
Shutdown of the inverter.  
Shutdown of the rectifier/charger.  
Opening of the battery circuit breaker.  
Blocking of the static bypass.  
Opening of the backfeed protection contactor (M2),  
Opening of the Q1 circuit breaker (M1),  
Activation of a relay contact on the remote-indications relay board.  
Servicing by the after-sales support department is required.  
The buzzer sounds discontinuously.  
THE BATTERY C.B. QF1 IS OPEN,  
CHECK THE INSTALLATION  
Battery circuit breaker QF1 is open. The load is no longer protected because battery power is no longer available  
in the event of a normal AC source outage. The buzzer sounds continuously.  
LOW BATTERY SHUTDOWN  
The inverter has shut down at the end of battery power. The buzzer sounds continuously.  
INTERNAL UPS FAULT,  
INVERTER FAULT,  
CALL MAINTENANCE  
A fault has occurred in the inverter. Servicing by the after-sales support department is required. The buzzer sounds  
continuously.  
INTERNAL UPS FAULT,  
CHARGER FAULT,  
CALL MAINTENANCE  
A fault has occurred in the rectifier/charger. Servicing by the after-sales support department is required.  
The buzzer sounds slowly and discontinuously.  
FORCED TRANSFER TO INVERTER REQUESTED,  
POWER TO LOAD MAY BE INTERRUPTED,  
CONFIRM YOUR REQUEST WITH KEY ø  
The requested transfer to the inverter may provoke an interruption in the supply of power to the load if Mains 2  
characteristics are not within the specified tolerances.  
A — 8  
Appendices  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
THE NUMBER OF UPS READY IS INSUFFICIENT,  
LOAD TRANSFER IN STANDBY  
This message may be displayed in non-redundant, parallel UPS systems, when the number of ready inverters in  
not sufficient to supply the load.  
INVERTER NOT CONNECTED  
This message may be displayed in parallel UPS systems, when the inverter is not connected to the load.  
PARALLEL UPS,  
FORCED TRANSFER INHIBITED  
This message is displayed when forced connection is requested on a parallel UPS system for a power extension.  
INTERNAL UPS FAULT,  
SELF-TEST FAULT  
Communication between the system and the display is faulty. The buzzer sounds slowly and discontinuously.  
FORCED TRANSFER TO M2 REQUESTED,  
POWER TO LOAD MAY BE INTERRUPTED  
CONFIRM YOUR REQUEST WITH KEY ø  
This message is displayed following pressing of the "forced-transfer" key 20, when the load is supplied via the inverter.  
UPS SUPPLIED BY A GENERATOR SET  
This message informs the user that the UPS has received the order to limit the current drawn by the rectifier/charger.  
It is displayed when the corresponding signal is transmitted by the remote indications board which must be  
conFigure d for this function.  
VENTILATION FAULT  
This message is displayed when a fault occurs on a fan.  
86-133060-00 A00  
Appendices  
A — 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
(This page left blank intentionally)  
A — 10  
Appendices  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
Appendix B  
Monitoring - Electrical Supervision Options  
"Teleservice"  
"Teleservice" is a contract offering continuous remote supervision and maintenance of UPS systems via a modem.  
Real-time communication is established with our "Teleservice" centre for communication of all alarms and events  
occurring in the installation.  
Utilization Via Teleservice  
When the optional JBUS RS232/485 communications board is installed, the time-stamped information can be sent  
to the Teleservice center.  
The center can remotely consult the same information and carry out the same modifications as the user locally on  
the display. Note that only the Teleservice centre can reset the counters for the statistical data.  
GTC Board  
This electronic board provides user access to the J-Bus communications protocol. Using the data and address  
tables provided, the user can customize his installation.  
GTC + Software  
The user has access to the J-Bus protocol and, in addition, the associated software acquires system parameters  
(measurements, status conditions) and transforms them into diagrams, alarm messages and tables. With the click  
of a mouse, the user can locally or remotely supervise the UPS system (comprising one or many UPS units).  
86-133060-00 A00  
Appendices  
A — 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
(This page left blank intentionally)  
A — 12  
Appendices  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
Appendix C  
®
Link to an IBM AS/400 Computer  
®
The Galaxy PWcan dialogue with an IBM AS/400 computer via a link in compliance with IBM communications  
recommendations, thus enhancing the protection provided by your Galaxy PW™.  
®
The IBM AS/400 computer must be configured for the link. This section describes the physical connections  
®
required as well as the system values that must be modified on the AS/400 . For further information, consult the  
following IBM documents:  
"Planning Guide, Appendix E" concerning physical connections.  
"Back-up and Recovery Guide", chapter 7 "Power Loss Recovery" concerning configuration of the AS 400 .  
®
Connect and Configure the AS400 Link  
Connections are made to the female client connector XR5 on the "Media Contacts 11" board. The corresponding  
male connector is supplied; see Figure 3-12 below for the wiring diagram. A five-wire cable (not supplied) is required.  
®
®
1. On the AS/400 side, use a 9 or 15-pin SUB-D connector. (Depending on the type of AS/400 .)  
®
®
2. Certain values on the AS/400 must be configured to enable operation of the Galaxy PW™ — AS/400 link.  
The values requiring modification and the corresponding procedures are presented in chapter 7 "Power Loss  
®
Recovery" of the "Back-up and Recovery Guide" for the AS/400 .  
Configuration values:  
QUPSMSGQ: UPS message queue;  
QUPSDLYTIM: Uninterruptible power supply delay time;  
QPWRRSTIPL: Power restore IPL.  
86-133060-00 A00  
Appendices  
A — 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TM  
Galaxy PW UPS 100 to 225 kVA  
(This page left blank intentionally)  
A — 14  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MGE Warranty & Proprietary Rights for Three Phase Products  
MGE Warranty  
The liability of MGE UPS SYSTEMS, INC. hereunder is limited to replacing or repairing at MGE UPS SYSTEMS,  
INC.’s factory or on the job site at MGE UPS SYSTEMS, INC.’s option, any part or parts which are defective, including  
labor, for a period of 12 months from the date of purchase. The MGE UPS SYSTEMS, INC. shall have the sole right  
to determine if the parts are to be repaired at the job site or whether they are to be returned to the factory for repair  
or replacement. All items returned to MGE UPS SYSTEMS, INC. for repair or replacement must be sent freight  
prepaid to its factory. Purchaser must obtain MGE UPS SYSTEMS, INC.’s Return Materials Authorization prior to  
returning items. The above conditions must be met if warranty is to be valid. MGE UPS SYSTEMS, INC. will not be  
liable for any damage done by unauthorized repair work, unauthorized replacement parts, from any misapplication of  
the item, or for damage due to accident, abuse, or Act of God.  
In no event shall the MGE UPS SYSTEMS, INC. be liable for loss, damage, or expense directly or indirectly arising  
from the use of the units, or from any other cause, except as expressly stated in this warranty. MGE UPS SYSTEMS,  
INC. makes no warranties, express or implied, including any warranty as to merchantability or fitness for a particular  
purpose or use. MGE UPS SYSTEMS, INC. is not liable for and Purchaser waives any right of action it has or may  
have against MGE UPS SYSTEMS, INC. for any consequential or special damages arising out of any breach of  
warranty, and for any damages Purchaser may claim for damage to any property or injury or death to any person  
arising out of its purchase of the use, operation or maintenance of the product. MGE UPS SYSTEMS, INC. will not  
be liable for any labor subcontracted or performed by Purchaser for preparation of warranted item for return to MGE  
UPS SYSTEMS, INC.’s factory or for preparation work for field repair or replacement. Invoicing of MGE UPS  
SYSTEMS, INC. for labor either performed or subcontracted by Purchaser will not be considered as a liability by the  
MGE UPS SYSTEMS, INC.  
This warranty shall be exclusive of any and all other warranties express or implied and may be modified only by a  
writing signed by an officer of the MGE UPS SYSTEMS, INC. This warranty shall extend to the Purchaser but to no  
one else. Accessories supplied by MGE UPS SYSTEMS, INC., but manufactured by others, carry any warranty the  
manufacturers have made to MGE UPS SYSTEMS, INC.. and which can be passed on to Purchaser.  
MGE UPS SYSTEMS, INC. makes no warranty with respect to whether the products sold hereunder infringe any  
patent, U.S. or foreign, and Purchaser represents that any specially ordered products do not infringe any patent.  
Purchaser agrees to indemnify and hold MGE UPS SYSTEMS, INC. harmless from any liability by virtue of any patent  
claims where Purchaser has ordered a product conforming to Purchaser’s specifications, or conforming to  
Purchaser’s specific design.  
Purchaser has not relied and shall not rely on any oral representation regarding the Product sold hereunder and any  
oral representation shall not bind MGE UPS SYSTEMS, INC. and shall not be part of any warranty.  
There are no warranties which extend beyond the description on the face hereof. In no event shall MGE UPS  
SYSTEMS, INC. be responsible for consequential damages or for any damages except as expressly stated herein.  
Proprietary Rights Statement  
The information in this manual is the property of MGE UPS SYSTEMS, INC., and represents a proprietary article in  
which MGE UPS SYSTEMS, INC., retains any and all patent rights, including exclusive rights of use and/or manufac-  
ture and/or sale. Possession of this information does not convey any permission to reproduce, print, or manufacture  
the article or articles shown herein. Such permission may be granted only by specific written authorization, signed by  
an officer of MGE UPS SYSTEMS, INC.  
IBM, PC-AT, ES/9000, and AS/400 are trademarks of International Business Machines Corporation. MGE and MGE  
UPS SYSTEMS are trademarks of MGE UPS SYSTEMS, INC. Other trademarks that may be used herein are owned  
by their respective companies and are referred to in an editorial fashion only.  
June 2004 Rev A01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TM  
Galaxy PW UPS 100 to 225 kVA  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MGE Customer Care Center  
Technical Support and Product Services  
Technical questions? If you encounter a problem while following the instructions in this manual, or have  
questions about the operation, repair, or servicing of your equipment, please direct calls to MGE UPS  
?
SYSTEMS, INC. Customer Care Center or visit our web site www.mgeups.com for complete service information.  
To insure that your questions are correctly answered, please obtain the part number, assembly number, and serial  
number of the unit and include them in any discussions or correspondence.  
Part Number:  
_____________________________________________________________________  
Assembly Number: _____________________________________________________________________  
Serial number:  
_____________________________________________________________________  
Who To Contact  
Technical Support:  
1-800-523-0142 (during business hours)  
Customer Care Center:  
1-800-438-7373 (Hours: 24/7)  
Customer FAQ  
or International calls:  
1-714-557-1636  
Commitment: MGE UPS SYSTEMS, INC. is committed to providing easy to access factory trained experts that will  
provide responses to any questions that you might have.  
Scheduling Field Service Engineer Support  
Scheduling of the MGE Field Service Engineers typically should be done 7 to 10 days before they are  
required on-site. If the startup of the UPS is critical to maintaining your schedule, please call the MGE  
toll free telephone number at 1-800-438-7373, to insure a safe installation and startup that will maintain  
the MGE warranty and insure smooth performance  
Return Policy for Repair (RMA)  
Should you require factory service for your equipment, contact MGE’s Customer Support Services and obtain a Return  
Materials Authorization (RMA) prior to shipping your unit. Never ship equipment to MGE without first obtaining an RMA.  
Date:  
______________________________________________________  
RMA Number: ______________________________________________________  
Contact Name: ______________________________________________________  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
(This page left blank intentionally)  
W—4  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Glossary  
Term used  
Definition/Meaning  
@
At.  
/
And/or.  
+/-  
Plus or Minus.  
Equal to or less than.  
Number.  
#
°C  
Degree Celsius.  
°F  
Degree Fahrenheit.  
Ø
Phase angle.  
Ω
Ohm. unit of resistance.  
Trade Mark.  
®
2nd  
Second.  
AC or ac  
Ambient Temp.  
Ambient noise  
ANSI  
Alternating current, also implies root-mean-square (rms).  
Temperature of surrounding air.  
Acoustical noise of surrounding environment.  
American National Standard Institute.  
American Wire Gauge.  
Electrical circuit interrupter.  
AWG  
Breaker  
BTU or Btu  
British thermal unit. Defined as the amount of heat required to raise the temperature of one  
pound of water by 1°F.  
BYPASS  
See “Static Transfer switch”.  
BYPASS mode  
See “off-line mode”.  
Carrier  
C
The company or individual responsible for delivering goods from one location to another.  
Common.  
CB  
Circuit breaker.  
Centimeter.  
Decibels.  
cm  
dB  
86-133060-00 A00  
Glossary  
G — 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
DC  
Direct current.  
Conduit  
A flexible or rigid tube enclosing electrical conductors.  
Customer Support Service.  
C.S.S.  
Current rating  
dBA  
The maximum current that a conductor or equipment can carry reliably without damage.  
Decibel Adjusted.  
dBrnC  
Decibel above reference noise.  
DC or dc  
Digital Meter  
Earth ground  
Electrician  
Direct current, or voltage.  
The LCD display on the front panel of inverter system.  
A ground circuit that has contact with the earth.  
Refers to an installation electrician qualified to install heavy-duty electrical components in  
accordance with local codes and regulations. Not necessarily qualified to maintain or repair  
electrical or electronic equipment.  
FET  
Field effect transistor.  
Freq.  
Frequency.  
Frequency slew rate  
The change in frequency per unit of time. Given in term of Hz per second (Hz/sec.).  
GND  
Ground (safety).  
Hz  
Hertz, frequency measurement unit, 1Hz is one cycle per second.  
Inverter mode  
See “on-line” mode.  
I
Current.  
IEC  
International Electrotechnical Commission.  
Institute of Electrical and Electronic Engineers.  
The input circuit from the building power panel to the equipment.  
An electrical circuit that generates an AC voltage source from a DC voltage source.  
Insulated gate bipolar transistors  
KiloVolt-Ampere. is equal to 1000 Volt-Ampere.  
Line.  
IEEE  
Input branch circuit  
Inverter  
IGBT  
kVA  
L
LCD  
Liquid-Crystal Display unit.  
LED  
Light Emitting Diode.  
Mains or Mains 1  
Mains 2  
mA  
Main AC input source.  
Bypass AC input source.  
Milliampere.  
MAX.  
Maximum.  
G — 2  
Glossary  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
MCM  
Thousand circular mil. standard wire sizes for multiple stranded conductors over 4/0  
AWG in diameter. M is from Roman numerical system indicating 1000.  
Module  
N
Refers to individual power inverter module.  
Neutral.  
NC  
Normally close.  
NO  
Normally open.  
NEC  
National Electrical Code.  
National Fire Protection Association.  
Part number.  
NFPA  
NO. or No.  
On-line mode  
Off-line mode  
Inverter output power is the primary energy source to load.  
Inverter output is off, and the load connected at the inverter output receives power  
from utility line via a static transfer switch or maintenance bypass relay.  
OSHA  
Occupational Safety and Health Agency.  
Printed circuit assembly.  
PCB  
PCB  
Printed circuit board.  
PWM  
Pulse Width Modulation.  
SCR  
Silicon controlled rectifier.  
Shipping damage  
SPDT  
Any damage done to an article while it is in transit.  
Single Pole Double Throw.  
Static Transfer  
An solid state switching mechanism electronically controlled to pass AC power direct-  
ly from the utility to an output load.  
Technician  
Refers to an electronic technician qualified to maintain and repair electronic equip-  
ment. Not necessarily qualified to install electrical wiring.  
Test connector  
DB-9 type connector on the LCD panel allowing MGE UPS SYSTEMS Customer  
Support Service technician to access programmable and diagnostic features of the  
system.  
V
Volts  
VA  
Volt amperes  
VA  
Volt-amps, unit for apparent power measurement, equal V x I.  
VAC or Vac  
VDC or Vdc  
ve  
Voltage of AC type.  
Voltage of DC type.  
Battery voltage.  
By way of.  
Via  
86-133060-00 A00  
Glossary  
G — 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Galaxy PWUPS 100 to 225kVA  
(This page left blank intentionally)  
G — 4  
86-133060-00 A00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Reorder Form  
1660 Scenic Avenue  
Costa Mesa, CA 92626  
Use this form to report any errors, omissions, or other problems you have experienced, or to order  
additional hardcopies of this document. A free copy of this document may be downloaded from the  
proprietary MGE Rep Web site. Please contact your MGE UPS SYSTEMS Representative for assistance.  
NAME _______________________________________________________________________________________  
COMPANY ___________________________________________________________________________________  
STREET ADDRESS ____________________________________________________________________________  
CITY ________________________________________ STATE __________________ ZIP ___________________  
I would like to order______ (quantity @ $50.00 each) additional copies of the:  
Galaxy PWUPS 100 to 225kVA  
Installation and User Manual  
86-133060-00 A00  
I would like to report the following problems with this document:  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
w w w. m g e u p s . c o m  
Contact MGE  
United States  
MGE UPS SYSTEMS  
1660 Scenic Ave.  
Costa Mesa, CA 92626  
Tel: (714) 557-1636  
(800) 523-0142  
Fax: (714) 557-9788  
www: mgeups.com  
Canada  
MGE UPS SYSTEMS  
#9, 2789 Thamesgate Drive  
Mississauga, ON L4T 4E8  
Tel: (905) 672-0990  
(877) 672-0990  
Fax: (905) 672-7667  
www: mgeups.com  
Latin America and  
Other International  
MGE UPS SYSTEMS  
1660 Scenic Ave.  
Costa Mesa, CA 92626  
Tel: (714) 513-7831  
(800) 523-0142 ext. 7831  
Fax: (714) 434-0199  
www: mgeups.com  
1660 Scenic Avenue, Costa Mesa, California 92626 • (714) 557-1636  
Download from Www.Somanuals.com. All Manuals Search And Download.  

LevelOne Printer WPS 100USB User Manual
LG Electronics Computer Monitor W2452V User Manual
LG Electronics Microwave Oven MS 0745V User Manual
Liebert Switch AC8 User Manual
Lightolier Work Light FBP50 User Manual
Lincoln Automobile 1999 Town Car User Manual
Linksys Switch EG005W User Manual
Mattel Motorized Toy Car N4715 0920 User Manual
Melissa Iron 641 046 User Manual
Memorex Cordless Telephone MSP PH2400 User Manual