Lochinvar Water Heater 0502 1302 User Manual

PUMP  
Recommendation  
PUMP-Rec-16 Rev C  
PUMP RECOMMENDATION FOR  
POWER-FIN 0502-1302 WATER HEATER  
Pump Specifications  
Part No.  
HorsePower  
Flanges  
Valute Material  
Flange Material  
Vendor  
Vendor Product Series  
Orientation  
PUM3013  
2/5  
2"  
Brass  
Brass  
Armstrong  
E Series  
Horizontal  
Installation Specifications  
Recommended for  
Model Numbers  
Power-fin, PF(N,L) 0502-1302  
Based on  
Based on  
Installation Type  
Single Water Heater piped to Single Storage Tank  
Pump  
Maximum GPM  
75 GPM  
Based on  
Connecting piping  
Maximum 45 feet straight pipe with 6-Elbows, 2-Unions,2-Ball Valves and 1-Cold Water Inlet Tee  
PUM3013  
Minimum Pipe Diameter  
2-1/2"  
IMPORTANT: Read the Power-fin 0502-2001 Installation and Operation Manual. If the planned system exceeds  
the pump capacity in flow and/or head see “Pump Curves-All Pumps” for alternate pumps and pump curves.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  

Kustom Stereo Amplifier KAA16 User Manual
Lexmark Printer 16M1301 User Manual
LG Electronics DVD Player DV8931H User Manual
Lindy Computer Hardware 51246 User Manual
Listen Technologies Stereo Receiver LA 350 User Manual
Lochinvar Boiler 81 286 User Manual
Mackie Music Mixer ONYX 820i User Manual
Mad Catz Games SharkPort PS2 User Manual
Manitowoc Ice Surge Protector 4004489 User Manual
Marquis Telephone 2802CID User Manual