Lochinvar Boiler 45000 260000 BTU HR User Manual

SBR-I-S Rev A  
Installation & Service Manual  
Models: 45,000 - 260,000 Btu/hr  
ƽ WARNING:  
This manual supplies information for the installation,  
operation, and servicing of the appliance. It is strongly  
recommended that this manual be reviewed completely  
before proceeding with an installation. Perform steps in  
the order given. Failure to comply could result in severe  
personal injury, death, or substantial property damage.  
Save this manual for future reference.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
Please read before proceeding  
Improper  
installation,  
adjustment,  
This is a gas appliance and should be  
ƽ WARNING  
NOTICE  
alteration, service or maintenance can result  
in severe personal injury, death, or  
substantial property damage. Refer to this  
manual for assistance or additional  
information, consult a qualified installer,  
service agency or the gas supplier.  
installed by a licensed electrician and/or  
certified gas supplier. Service must be  
performed by a qualified service installer,  
service agency or the gas supplier.  
If the information in these instructions is  
ƽ WARNING  
not followed exactly, a fire or explosion may  
result causing property damage, personal  
injury, or death.  
Checking equipment –  
Upon receiving equipment, check for signs of shipping damage.  
Pay particular attention to parts accompanying the appliances  
which may show signs of being hit or otherwise being  
mishandled. Verify total number of pieces shown on the  
packing slip with those actually received. In case there is damage  
or a shortage, immediately notify the carrier.  
This appliance MUST NOT be installed in  
any location where gasoline or flammable  
vapors are likely to be present, unless the  
installation is such to eliminate the probable  
ignition of gasoline or flammable vapors.  
What to do if you smell gas –  
Do not use this appliance if any part has been under water.  
The possible damage to a flooded appliance can be extensive  
and present numerous safety hazards. Any appliance that has  
been under water must be replaced.  
• Do not try to light any appliance.  
• Do not touch any electric switch; do not  
use any phone in your building.  
ƽ Owner warning –  
• Immediately call your gas supplier from a  
near by phone. Follow the gas supplier’s  
instructions.  
NOTE: Retain this manual for future reference.  
The information contained in this manual is intended for use by  
qualified professional installers, service technicians, or gas  
suppliers. Consult your local expert for proper installation or  
service procedures.  
• If you cannot reach your gas supplier, call  
the fire department.  
Installation and service must be performed  
by a qualified installer, service agency, or the  
gas supplier.  
Consult and follow all local Building and  
IMPORTANT  
Fire Regulations and other Safety Codes  
that apply to this installation. Consult your  
local gas utility company to authorize and  
inspect all gas and flue connections.  
Warranty –  
Installation and service must be performed by a qualified  
service installer, service agency or the gas supplier.  
Your conventionally vented gas appliance must have a supply of  
fresh air circulating around it during burner operation for  
proper gas combustion and proper venting.  
Factory warranty (shipped with unit) does not apply to units  
improperly installed or improperly operated.  
Should overheating occur or the gas supply  
ƽ WARNING  
Experience has shown that improper installation or system  
design, rather than faulty equipment, is the cause of most  
operating problems.  
fail to shut off, do not turn off or disconnect  
the electrical supply to the pump. Instead,  
shut off the gas supply at a location external  
to the appliance.  
1. Excessive water hardness causing a lime/scale build-up in  
the copper tube is not the fault of the equipment and is  
not covered under the manufacturer’s warranty (see  
Water Treatment and Water Chemistry).  
2. Excessive pitting and erosion on the inside of the copper  
tube may be caused by too much water velocity through  
the tubes and is not covered by the manufacturer’s  
warranty (see Boiler Flow Rates and Temperature Rise for  
flow requirements).  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
Please read before proceeding  
To minimize the possibility of serious  
personal injury, fire, or damage to your  
ƽ WARNING  
appliance, never violate the following safety  
rules:  
1. Boilers are heat producing appliances. To  
avoid damage or injury, do not store  
materials against the appliance or the  
vent-air intake system. Use proper care  
to avoid unnecessary contact (especially  
children) with the appliance and vent-air  
intake components.  
2. Never cover your appliance, lean  
anything against it, store trash or debris  
near it, stand on it or in any way block  
the flow of fresh air to your appliance.  
3. UNDER NO CIRCUMSTANCES must  
flammable materials such as gasoline or  
paint thinner be used or stored in the  
vicinity of this appliance, vent-air intake  
system or any location from which fumes  
could reach the appliance or vent-air  
intake system.  
Codes –  
The equipment shall be installed in accordance with those  
installation regulations in force in the local area where the  
installation is to be made. These regulations shall be carefully  
followed in all cases. Authorities having jurisdiction shall be  
consulted before installations are made. In the absence of such  
requirements, the installation shall conform to the latest edition  
of the National Fuel Gas Code, ANSI Z223.1. Where required by  
the authority having jurisdiction, the installation must conform  
to American Society of Mechanical Engineers Safety Code for  
Controls and Safety Devices for Automatically Fired Boilers,  
ASME CSD-1. All boilers conform to the latest edition of the  
ASME Boiler and Pressure Vessel Code, Section IV. Where  
required by the authority having jurisdiction, the installation  
must comply with the Canadian Association Code, CAN/CGA-  
B149.1 and/or B149.2 and/or local codes.  
This appliance meets the safe lighting performance criteria with  
the gas manifold and control assembly provided as specified in  
the ANSI standards for gas-fired appliances, ANSI Z21.13 and  
ANSI Z21.10.3.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
Ratings  
Solution Boiler  
I=B=R Rating  
Other Specifications  
Net  
I=B=R  
Gross  
Output  
MBH  
Input  
MBH  
Model Number  
Ratings  
Water,  
MBH  
Boiler Water  
Content  
Gallons  
Vent  
Water  
Gas  
Connections  
Note: Change “N” to  
“L” for L.P. gas models.  
Connections  
Size  
(Note 4)  
(Note 1,5)  
(Note 1,5)  
37  
(Note 3)  
4"  
Min  
23  
Max  
45  
CBN045  
CBN075  
CBN090  
CBN135  
32  
0.87  
1 1/2"  
1/2"  
38  
45  
68  
75  
90  
62  
75  
54  
65  
97  
0.91  
0.91  
0.95  
0.99  
1.02  
1.06  
1 1/2"  
1 1/2"  
1 1/2"  
1 1/2"  
1 1/2"  
2"  
1/2"  
1/2"  
1/2"  
3/4"  
3/4"  
3/4"  
5"  
5"  
6"  
7"  
7"  
8"  
135  
112  
CBN180  
CBN215  
CBN260  
90  
180  
215  
260  
149  
178  
216  
130  
155  
188  
108  
130  
Maximum allowed working pressure is located on the rating plate.  
NOTICE  
Notes:  
1. The ratings are based on standard test procedures  
prescribed by the United States Department of Energy.  
2. Net I=B=R ratings are based on net installed radiation of  
sufficient quantity for the requirements of the building and  
nothing need be added for normal piping and pickup.  
Ratings are based on a piping and pickup allowance of 1.15.  
UNIT EQUIPPED FOR  
HIGH ALTITUDE  
UP TO 2000 FT.  
3. Use only the vent materials and methods specified in the  
Installation and Service Manual.  
4. The Solution is orificed for operation up to 2000 feet  
altitude. The appliance will be derated 4% per 1000 feet  
above 2000 feet elevation. Consult the factory for  
installations above 2000 feet elevation.  
Figure A High Altitude Label Location  
5. Ratings have been confirmed by the Hydronics Institute,  
Section of AHRI.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
The Solution - How it works...  
1. Control panel cover  
16. Sight Glass  
The control panel cover provides access to the thermostat, ignition  
module, and transformer.  
The sight glass provides a view of the burner surface, burner flame,  
and the pilot flame.  
2. Burner (not shown)  
17. Temperature and pressure gauge  
The temperature and pressure gauge monitors the outlet  
temperature of the appliance as well as the system water  
pressure.  
The burner is a cylindrical stainless steel tube used to regulate  
burner flame.  
3. Drain port  
18. Temperature sensor  
Location from which the heat exchanger can be drained.  
This sensor monitors inlet water temperature. If selected as the  
controlling sensor, the appliance will maintain the setpoint at this  
sensor.  
4. Flue outlet  
The flue outlet allows the connection of the vent pipe to the unit.  
5. Gas connection  
19. Terminal strip  
The gas pipe connection on this appliance is 1/2", or 3/4" NPT. To  
deliver the correct amount of gas volume to the appliance it may  
be necessary to have a larger gas line reduced at the appliance.  
Please reference the National Fuel Gas Code charts for more  
details.  
The boiler is equipped with a terminal strip on the left side of the  
unit to allow easy connection to contact points.  
20. Top panel  
Removable panel to gain access to the internal components.  
6. Gas valve  
21. Thermostat  
The gas valve allows the proper amount of gas to pass into the  
burner for combustion.  
The thermostat monitors the water temperature via a temperature  
sensor and will initiate a call for heat when the water temperature  
drops below the setpoint plus the differential on the thermostat.  
7. Heat exchanger  
The heat exchanger allows system water to flow through specially  
designed tubes for maximum heat transfer. The glass lined  
headers and copper finned tubing are encased in a jacket that  
contains the combustion process.  
22. Transformer  
The transformer reduces 120 VAC supply voltage to 24 VAC for the  
control circuit.  
8. High limit sensor  
23. Water inlet (system return)  
Device that monitors the outlet water temperature to ensure  
safe operation. If the temperature exceeds its setting, it will break  
the control circuit, shutting the appliance down.  
The water inlet is a 1 1/2" pipe connection that receives water  
from the system and delivers it to the heat exchanger.  
24. Water outlet (system supply)  
9. Ignition module  
The water outlet is a 1 1/2" pipe connection that supplies  
water to the system with connections for a flow switch, a relief  
valve, and a temperature and pressure gauge.  
The ignition module responds to a call for heat signal to provide  
burner operation.  
25. Gas manifold pipe  
10. Junction box  
Delivers gas from the gas valve to the main burners through a  
The junction box contains the connection points for the line  
number of orifices.  
voltage power and all pumps.  
11. Performance loop  
A pumped bypass provides constant flow through the heat  
exchanger when the building system flow is reduced.  
12. Performance Loop Pump  
The pump ensures adequate flow to operate the unit.  
13. Pilot (not shown)  
The pilot is a spark ignition device used to light a pilot flame which  
in turn is used to light the main burners.  
14. Pump relay  
The pump relay energizes the pump on a call for heat.  
15. Relief valve  
The relief valve is a safety device that ensures the maximum  
pressure of the appliance is not exceeded.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
The Solution - How it works...  
(continued)  
4
10  
20  
17  
15  
1
8
3
19  
5
Models 45,000 - 90,000 Btu/hr Front View  
Models 45,000 - 90,000 Rear View  
7
22  
18  
12  
21  
9
6
11  
23  
25  
24  
14  
16  
Models 45,000 - 90,000 Left Side (inside unit)  
Models 45,000 - 90,000 Right Side (inside unit)  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
The Solution - How it works...  
10  
4
20  
17  
15  
1
8
3
19  
5
Models 135,000 - 260,000 Btu/hr Front View  
Models 135,000 - 260,000 Btu/hr Rear View  
7
9
18  
12  
3
6
3
11  
21  
25  
24  
23  
22  
14  
Models 135,000 - 260,000 Btu/hr Left Side (inside unit)  
Models 135,000 - 260,000 Btu/hr Right Side (inside unit)  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
1 Determine boiler location  
Location of unit  
Recommended Service Clearances:  
Left - 24”  
Front - 24”  
1. Locate the appliance so that if water connections should  
leak, water damage will not occur. When such locations  
cannot be avoided, it is recommended that a suitable drain  
pan, adequately drained, be installed under the appliance.  
The pan must not restrict combustion air flow. Under no  
circumstances is the manufacturer to be held responsible  
for water damage in connection with this appliance, or any  
of its components.  
14"  
TOP  
2. The appliance must be installed indoors where it is  
protected from exposure to wind, rain and weather.  
3. The appliance must be installed so that the ignition system  
components are protected from water (dripping, spraying,  
rain, etc.,) during appliance operation and service  
(circulator replacement, control replacement, etc.,).  
6 " RIGHT  
6 " REAR  
4. Appliances located in a residential garage and in adjacent  
spaces that open to the garage and are not part of the  
living space of a dwelling unit must be installed so that all  
burners and burner ignition devices have a minimum  
clearance of not less than 18" (46cm) above the floor. The  
appliance must be located or protected so that it is not  
subject to physical damage by a moving vehicle.  
18 "  
LEFT  
18 "  
FRONT  
Figure 1-1_Alcove Installation - Models 45,000 -  
180,000 Btu/hr  
Recommended Service Clearances:  
Left - 24”  
Front - 24”  
5. DO NOT install this appliance in any location where  
gasoline or flammable vapors are likely to be present.  
6. All units have been approved for alcove installation (an  
ALCOVE is a closet enclosure without a front door).  
7. The appliance must not be installed on carpet.  
8. All units have been approved for use on combustible  
surfaces.  
29"  
TOP  
9. Allow sufficient space for servicing pipe connections,  
pump and other auxiliary equipment, as well as the  
appliance.  
Clearances from combustible construction  
NOTICE  
are noted on the appliance rating plate.  
6 " RIGHT  
6 " REAR  
18 "  
LEFT  
18 "  
FRONT  
Figure 1-2_Alcove Installation - Models 215,000 -  
260,000 Btu/hr  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
1 Determine boiler location  
Combustion  
and  
ventilation  
air  
requirements for conventionally vented  
appliances  
Provisions for combustion and ventilation air must be in  
accordance with, Air for Combustion and Ventilation, of the  
latest edition of the National Fuel Gas Code, ANSI Z223.1, in  
Canada, the latest edition of CGA Standard B149 Installation  
Code for Gas Burning Appliances and Equipment, or  
applicable provisions of the local building codes.  
The room where the appliance is installed MUST be provided  
with properly sized openings to assure adequate combustion  
air and proper ventilation when the appliance is installed with  
conventional venting.  
Figure 1-4_Combustion Air Through Ducts  
2. If combustion and ventilation air is taken from the  
outdoors using a duct to deliver the air to the room where  
the appliance is installed, each of the two openings should  
be sized based on a minimum free area of one square inch  
per 2000 Btu/hr (11cm2 per kW) (see FIG. 1-4).  
Figure 1-3_Combustion Air Direct from Outside  
1. If air is taken directly from outside the building  
with no duct, provide two permanent openings (see  
FIG. 1-3):  
(a) Combustion air opening, with a minimum free  
area of one square inch per 4000 Btu/hr input  
(5.5 cm2 per kW). This opening must be  
located within 12" (30 cm) of the floor.  
Figure 1-5_Combustion Air from Interior Space  
3. If air is taken from another interior space that is adequately  
ventilated, each of the two openings specified above should  
have a net free area of one square inch for each 1000 Btu/hr  
(22cm2 per kW) of input, but not less than 100 square  
inches (645cm2) (see FIG. 1-5).  
(b) Ventilation air opening, with a minimum free  
area of one square inch per 4000 Btu/hr input  
(5.5 cm2 per kW).  
This opening must be  
located within 12" (30 cm) of the ceiling.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
1 Determine boiler location  
(continued)  
Under no circumstances should the room  
where the appliance is installed ever be  
under a negative pressure. Particular care  
should be taken where exhaust fans, attic  
fans, clothes dryers, compressors, air  
handling units, etc., may take away air from  
the appliance.  
ƽ CAUTION  
The combustion air supply must be completely free of any  
flammable vapors that may ignite or chemical fumes which may  
be corrosive to the appliance. Common corrosive chemical  
fumes which must be avoided are fluorocarbons and other  
halogenated compounds, most commonly present as  
refrigerants or solvents, such as freon, tricholorethylene,  
perchlorethylene, chlorine, etc. These chemicals, when burned,  
form acids which quickly attack the heat exchanger finned tubes,  
headers, flue collectors, and the vent system. The result is  
improper combustion and a non-warrantable, premature  
appliance failure.  
Figure 1-6_Combustion Air from Outside Single Opening  
4. If a single combustion air opening is provided to bring  
combustion air in directly from the outdoors, the  
opening must be sized based on a minimum free area of  
one square inch per 3000 Btu/hr (7 cm2 per kW). This  
opening must be located within 12" (30 cm) of the top of  
the enclosure (see FIG. 1-6).  
The result is improper combustion and a non-warrantable,  
premature appliance failure.  
EXHAUST FANS: Any fan or equipment which exhausts air  
from the equipment room may deplete the combustion air  
supply and/or cause a downdraft in the venting system. Spillage  
of flue products from the venting system into an occupied living  
space can cause a very hazardous condition that must be  
immediately corrected. If a fan is used to supply combustion air  
to the equipment room, the installer must make sure that it does  
not cause drafts which could lead to nuisance operational  
problems with the appliance.  
Combustion air requirements are based on the latest edition  
of the National Fuel Gas Code, ANSI Z223.1, in Canada refer  
to National Standard CAN B149.1. Check all local code  
requirements for combustion air.  
All dimensions are based on net free area in square inches.  
Metal louvers or screens reduce the free area of a combustion  
air opening a minimum of approximately 25%. Check with  
louver manufacturers for exact net free area of louvers. Where  
two openings are provided, one must be within 12" (30 cm) of  
the ceiling and one must be within 12" (30 cm) of the floor of  
the room where the appliance is installed. Each opening must  
have a net free area as specified in Table 1B (on page 12).  
Single openings shall be located within 12" (30 cm) of the  
ceiling.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
1 Determine boiler location  
TABLE - 1B  
MINIMUM RECOMMENDED COMBUSTION  
AIR SUPPLY TO EQUIPMENT ROOM  
*Outside Air from  
2 Openings Directly from  
Outdoors  
*Outside Air from  
2 Ducts Delivered from  
Outdoors  
**Inside Air from  
2 Ducts Delivered from  
Interior Space  
*Outside Air from  
1 Opening Directly  
from Outdoors, in2  
Input  
Btu/hr  
Top  
Bottom  
Top  
Bottom  
Top  
Bottom  
Opening, in2 Opening, in2  
Opening, in2 Opening, in2 Opening, in2 Opening, in2  
12  
12  
15  
23  
23  
100  
100  
45,000  
75,000  
90,000  
135,000  
(78 cm2)  
(78 cm2)  
(97 cm2)  
(149 cm2)  
(149 cm2)  
(646 cm2)  
(646 cm2)  
19  
19  
25  
38  
38  
100  
(646 cm2)  
100  
(646 cm2)  
(123 cm2)  
(123 cm2)  
(162 cm2)  
(246 cm2)  
(246 cm2)  
23  
23  
30  
45  
45  
100  
(646 cm2)  
100  
(646 cm2)  
(148 cm2)  
(148 cm2)  
(194 cm2)  
(291 cm2)  
(291 cm2)  
34  
34  
45  
68  
68  
135  
(871 cm2)  
135  
(871 cm2)  
(220 cm2)  
(220 cm2)  
(291 cm2)  
(439 cm2)  
(439 cm2)  
45  
45  
60  
90  
90  
180  
(1,162 cm2)  
180  
(1,162 cm2)  
180,000  
(291 cm2)  
(291 cm2)  
(388 cm2)  
(581 cm2)  
(581 cm2)  
54  
54  
72  
108  
108  
215  
215  
215,000  
260,000  
(349 cm2)  
(349 cm2)  
(465 cm2)  
(697 cm2)  
(697 cm2)  
(1,388 cm2)  
(1,388 cm2)  
65  
65  
87  
130  
(839 cm2)  
130  
(839 cm2)  
260  
(1,678 cm2)  
260  
(1,678 cm2)  
(420 cm2)  
(420 cm2)  
(562 cm2)  
*Outside air openings shall directly communicate with the outdoors. When combustion air is drawn from the outside through a  
duct, the net free area of each of the two openings must have twice (2 times) the free area required for Outside Air/2 Openings.  
The above requirements are for the boiler only; additional gas fired appliances in the equipment room will require an increase in  
the net free area to supply adequate combustion air for all appliances.  
**Combined interior space must be 50 cubic feet per 1,000 Btu/hr input. Buildings MUST NOT be of *“Tight Construction.  
For buildings of *“Tight Construction, provide air openings into the building from outside.  
*No combustion air openings are needed when the water heater is installed in a space with a volume NO LESS than 50 cubic feet  
per 1,000 Btu/hr of all installed gas fired appliances. Buildings MUST NOT be of *“Tight Construction.  
*”Tight Construction” is defined as a building with less than 0.40 ACH (air changes per hour).  
The distance of the vent terminal from adjacent  
buildings, windows that open and building openings MUST  
comply with the latest edition of the National Fuel Gas Code,  
ANSI Z223.1, in Canada, the latest edition of CGA Standard  
B149 Installation Code for Gas Burning Appliances and Equip-  
ment.  
Vent installations for connection to gas vents or  
chimneys must be in accordance with “Venting of  
Equipment,of the latest edition of the National Fuel Gas  
Code, ANSI Z223.1, in Canada, the latest edition of CGA  
Standard B149 Installation Code for Gas Burning Appliances  
and Equipment or applicable provisions of the local building  
codes.  
Vent connection is made directly to the top of the  
appliance. This appliance is designed with a built-in draft  
diverter. No additional external draft hood is required. The  
connection from the appliance vent to the common vent or  
chimney must be made as direct as possible.  
Adequate combustion and ventilation air must be  
supplied to the room where the appliance is installed in  
accordance with the latest edition of the National Fuel Gas  
Code, ANSI Z223.1, in Canada, the latest edition of CGA  
Standard B149 Installation Code for Gas Burning Appliances  
and Equipment, or applicable provisions of the local building  
codes.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
2 Venting  
A Conventional Negative Draft  
Venting System  
The negative draft in a conventional vent installation must be  
within the range of a negative 0.02 to 0.05 inches water  
column to ensure proper operation. All draft readings are  
made while the appliance is in stable operation  
(approximately 2 to 5 minutes).  
TABLE - 2A  
VENT PIPE SIZES  
Input Btu/hr  
Flue Size  
45,000  
75,000  
4"  
5"  
5"  
6"  
7"  
7"  
8"  
Multiple appliance installations with combined venting or  
common venting with other negative draft appliances require  
that each appliance must have draft within the proper range.  
If the draft measured above the appliance’s built-in draft  
diverter exceeds the specified range in a dedicated chimney  
for a single appliance installation or in combined venting with  
other negative draft appliances, a barometric damper must be  
90,000  
135,000  
180,000  
215,000  
260,000  
installed to control draft.  
On a conventionally vented, negative draft appliance, the  
connection from the vent to the chimney or vent termination  
on the outside of the building MUST be made with listed Type  
“B” double wall (or equivalent) vent connectors and must be  
direct as possible with no reduction in diameter. Use the  
National Fuel Gas Code venting tables for double wall vent to  
properly size all vent connectors and stacks. The Type “B” vent  
and accessories, such as firestop spacers, thimbles, caps, etc.,  
MUST be installed in accordance with the manufacturer’s  
listing. The vent connector and firestop must provide correct  
spacing to combustible surfaces and seal to the vent connector  
on the upper and lower sides of each floor or ceiling through  
which the vent connector passes.  
Any vent materials used must be listed by a nationally  
recognized test agency for use as vent material.  
Figure 2-1_Conventional Negative Draft Vertical Venting  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
2 Venting  
Locate appliance as close as possible to a chimney or gas vent.  
(e) Test for spillage at the draft hood/relief opening after 5  
minutes of main burner operation. Use the flame of a  
match or candle, or smoke from a cigarette, cigar or  
pipe.  
Avoid long horizontal runs of the vent pipe, 90° elbows,  
reductions and restrictions. Horizontal portions of the  
venting system shall be supported to prevent sagging.  
Horizontal runs must slope upwards not less than 1/4 inch  
per foot (21 mm/m) from the appliance to the vent terminal.  
Follow manufacturer’s instructions.  
(f) After it has been determined that each appliance  
remaining connected to the common venting system  
properly vents when tested as outlined above, return  
doors, windows, exhaust fans, fireplace dampers and  
other gas burning appliances to their previous  
conditions of use.  
Do not use an existing chimney as a raceway for a flue pipe if  
another appliance or fireplace is vented through the chimney.  
The weight of the venting system must not rest on the  
appliance. Adequate support of the venting system must be  
provided in compliance with local codes and other applicable  
codes. All connections should be secured with rustproof  
sheet metal screws.  
(g) Any improper operation of the common venting  
system should be corrected so that the installation  
conforms to the latest edition of the National Fuel Gas  
Code, ANSI Z223.1. In Canada, the latest edition of  
CGA Standard B149 Installation Code for Gas Burning  
Appliances and Equipment. When resizing any por-  
tion of the common venting system, the common  
venting system should be resized to approach the min-  
imum size as determined using the appropriate tables  
in Part 11 in the latest edition of the National Fuel Gas  
Code, ANSI Z223.1. In Canada, the latest edition of  
CGA Standard B149 Installation Code for Gas Burning  
Appliances and Equipment.  
Vent connectors serving appliances vented by natural draft  
shall not be connected to any portion of  
mechanical draft system operating under positive  
pressure. Connection to a positive pressure chimney may  
cause flue products to be discharged into the living space  
causing serious health injury.  
a
Common venting systems may be too large when an existing  
appliance is removed. At the time of removal of an existing  
appliance, the following steps shall be followed with each  
appliance remaining connected to the common venting  
system placed in operation, while other appliances remaining  
connected to the common venting system are not in  
operation.  
(a) Seal any unused opening in the common venting  
system.  
(b) Visually inspect the venting system for proper size  
and horizontal pitch and determine there is no  
blockage or restriction, leakage, corrosion and other  
deficiencies which could cause an unsafe condition.  
(c) Insofar as is practical, close all building doors and  
windows and all doors between the space in which  
the appliances remaining connected to the common  
venting system are located and other spaces of the  
building. Turn on clothes dryers and any other  
appliances not connected to the common venting  
system. Turn on any exhaust fans, such as range  
hoods and bathroom exhausts, so they will operate  
at maximum speed. Do not operate a summer  
exhaust fan. Close fireplace dampers.  
(d) Place in operation the appliance being inspected.  
Follow the lighting instructions. Adjust thermostat  
so appliance will operate continuously.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
2 Venting  
(continued)  
Vertical Vent Termination Clearances  
10' OR LESS  
10' OR LESS  
10' OR LESS  
CHIMNEY  
2' MIN  
2' MIN  
3' MIN  
2' MIN  
3' MIN  
RIDGE  
CHIMMEY  
WALL OR  
PARAPET  
CHIMMEY  
Figure 2-2_Vent Termination from Peaked Roof 10' or  
Less from Ridge  
Figure 2-4_Vent Termination from Flat Roof 10' or Less  
from Parapet Wall  
10' OR MORE  
MORE THAN 10'  
3'  
10'  
2' MIN  
CHIMNEY  
RIDGE  
3' MIN  
NOTE:  
NO HEIGHT ABOVE  
PARAPET REQUIRED  
WHEN DISTANCE  
FROM WALLS OR  
PARAPETS IS MORE  
THAN 10'.  
WALL OR  
CHIMNEY  
PARAPET  
Figure 2-5_Vent Termination from Flat Roof More Than  
10' from Parapet Wall  
Figure 2-3_Vent Termination from Peaked Roof More  
than 10' from Ridge  
Do not terminate the vent in a window well, stairwell, alcove,  
courtyard or other recessed area. The vent can not terminate  
below grade. The bottom of the vent terminal shall be located  
at least 12 inches (30cm) above grade.  
The vent terminal should be vertical and exhaust outside the  
building at least 2 feet (0.61m) above the highest point of the  
roof within a 10 foot (3.05m) radius of the termination. The  
vertical termination must be a minimum of 3 feet (0.91m)  
above the point of exit.  
To avoid a blocked vent condition, keep the vent cap clear of  
snow, ice, leaves, debris, etc.  
A vertical terminal less than 10 feet (3.05m) from a parapet  
wall must be a minimum of 2 feet (0.61m) higher than the  
parapet wall.  
Flue gases will form a white plume in winter. Plume could  
obstruct window view.  
Flue gas condensate can freeze on exterior surfaces or on the  
vent cap. Frozen condensate on the vent cap can result in a  
blocked vent condition. Flue gas condensate can cause  
discoloration of exterior building surfaces. Adjacent brick or  
masonry surfaces should be protected with a rust resistant sheet  
metal plate.  
The vent cap should have a minimum clearance of 4 feet  
(1.22m) horizontally from and in no case above or below,  
unless a 4 foot (1.22m) horizontal distance is maintained  
from electric meters, gas meters, regulators and relief  
equipment.  
The venting system shall terminate at least 3 feet (0.9m) above  
any forced air inlet within 10 feet (3.05m).  
Examine the venting system at least once a  
NOTICE  
year. Check all joints and vent pipe  
connections for tightness. Also check for  
corrosion or deterioration. Immediately  
correct any problems observed in the  
The venting system shall terminate at least 4 feet (1.2m)  
below, 4 feet (1.2m) horizontally from, or 1 foot (30cm) above  
any door, window or gravity air inlet into any building.  
venting system.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
2 Venting  
Masonry Chimney Installation  
The induced draft fan MUST also be equipped with a proving  
switch, properly interlocked into the appliance’s control circuit  
to prove fan operation before the main burners are allowed to  
fire. A vertical or sidewall vent termination for an induced draft  
fan MUST be installed per the recommendations of the fan  
manufacturer and provide proper clearances from any  
combustion or ventilation openings, windows, doors or other  
openings into the building. All induced draft fan installations  
must comply with local code requirements.  
A masonry chimney must be properly sized for the  
installation of a gas fired appliance. Venting of an appliance  
into a cold or oversized masonry chimney can result in  
operational and safety problems. Exterior masonry  
chimneys, with one or more sides exposed to cold outdoor  
temperatures, are more likely to have venting problems. The  
temperature of the flue gases from an appliance may not be  
able to sufficiently heat the masonry structure of the chimney  
to generate proper draft. This will result in condensing of flue  
gases, damage the masonry flue/tile, insufficient draft and  
possible spillage of flue gases into an occupied living space.  
Carefully inspect all chimney systems before installation. If  
there is any doubt about the sizing or condition of a masonry  
chimney, it must be relined with a properly sized and  
approved chimney liner system.  
Fan Assisted Venting  
A Power Venter Kit is available on Models 45,000 - 135,000  
Btu/hr only (see Table 2B).  
TABLE - 2B  
VENT MATERIALS  
Inspection of a Masonry Chimney  
Kit  
Input  
Btu/hr  
Material  
Number  
A masonry chimney must be carefully inspected to determine  
its suitability for the venting of flue gases. A clay tile lined  
chimney must be structurally sound, straight and free of  
misaligned tile, gaps between liner sections, missing sections  
of liner or any signs of condensate drainage at the breaching  
or clean out. If there is any doubt about the condition of a  
masonry chimney, it must be relined. An unlined masonry  
chimney must not be used to vent flue gases from this appliance.  
An unlined chimney must be relined with an approved  
chimney liner system when a new appliance is being attached to  
it. Metallic liner systems (Type “B” double wall or flexible or  
rigid metallic liners) are recommended. Consult with local  
code officials to determine code requirements or the  
advisability of using or relining a masonry chimney.  
45,000  
75,000  
90,000  
135,000  
PVC Rated (CPVC Optional)  
PVC Rated (CPVC Optional)  
CPVC Rated  
KIT3103  
KIT3104  
CPVC Rated  
Minimum Vent Length = 12 Equivalent Feet*  
(ALL UNITS)  
Maximum Vent Length = 25 Equivalent Feet*  
(ALL UNITS)  
* Equivalent Feet: 90° Elbow = 5 Feet  
45° Elbow = 3 Feet  
Sidewall Venting - Negative Draft  
This appliance is NOT approved for sidewall venting with  
the negative draft venting system as shipped from the  
factory.  
An induced draft fan MUST be used if the  
installation requires that the flue gases be vented out a  
sidewall unless a power venter is used, see Fan Assisted  
Venting. A properly sized and installed induced draft fan  
may also be used to vent the flue gases vertically if required  
by jobsite restrictions. The induced draft fan must be listed  
by a nationally recognized test agency, be properly sized and  
installed per the recommendations of the induced draft fan  
manufacturer and meet local code requirements. Use care to  
ensure that the mechanically supplied draft does not exceed  
the range of a negative 0.02 to 0.05 inches water column to  
ensure proper operation. If draft exceeds the specified range,  
the fan must be adjusted or the installation of a barometric  
damper in the flue may be required to properly control draft.  
An induced draft fan MUST be interlocked into the  
appliance’s control circuit to start when the appliance calls  
for heat.  
Figure 2-6_Unit with Fan Assisted Venting  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
2 Venting  
(continued)  
VENT DAMPER  
Automatic Vent Damper  
This heating boiler is design certified for use with the  
automatic vent damper (FIG. 15) part number printed on the  
boiler’s rating plate. A vent damper must be installed on all  
residential heating boilers with inputs of less than 300,000  
Btu/hr to comply with minimum efficiency requirements. A  
vent damper is factory supplied with residential heating  
boilers with inputs of 45,000 thru 260,000 Btu/hr.  
The vent damper is a useful tool for saving energy when  
installed inside the living space where air can circulate freely  
around the appliance. The vent damper will not save as much,  
if any, energy if it is installed in locations such as:  
- Unheated garage  
- Attic  
- Crawlspace  
- Mechanical room that is vented outdoors  
For installation and maintenance on the vent damper, refer to  
the instructions supplied with the vent damper.  
Figure 2-7_Vent Damper and Vent Damper Terminal  
Block  
Residential heating boilers with inputs of less than  
300,000 Btu/hr must have the vent damper properly installed  
and the vent damper wire harness plugged into the terminal  
block on the side of the control panel to allow the boiler to  
function. Larger input heating boilers will have a jumper plug  
installed in the terminal block to allow operation without a  
damper. Remove the jumper plug from the terminal block to  
connect an optional vent damper wire harness. The jumper  
plug MUST be in place if an optional vent damper is not used  
on larger input heating boilers.  
The vent damper must be installed directly  
ƽ WARNING  
on the flue outlet located on the top of the  
draft hood (see FIG. 2-7). Do not alter the  
wire harness supplied with the vent damper.  
Follow the instructions supplied with the  
vent damper.  
An appliance which is shut down or will not  
ƽ CAUTION  
operate may experience freezing due to  
convective air flow down the flue pipe  
connected to the unit. Proper freeze  
protection must be provided, see Freeze  
Protection.  
Do not install the vent damper within 6"  
ƽ CAUTION  
(152 mm) of combustible materials.  
Install the vent damper to service only the single appliance for  
which it is intended. If improperly installed, a hazardous  
condition such as an explosion or carbon monoxide poisoning  
could result.  
The damper position indicator must be in a visible location  
with access for service following installation. The damper  
must be in an open position when appliance main burners are  
operating.  
The part number for the automatic vent damper required on  
this heating boiler is printed on the rating plate. Vent damper  
regulations are design certified per the latest edition of ANSI  
Z21.66.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
3 Gas connections  
Gas Supply  
Gas Pressure Test  
Verify that the appliance is supplied with the type gas 1. The appliance must be disconnected from the gas supply  
specified on the rating plate. This appliance is orificed for  
operation up to 2000 feet altitude. The appliance will be  
derated 4% per 1000 feet above 2000 feet elevation. Consult  
the factory for installations above 2000 feet elevation. Field  
conversions for operation at high altitude must be performed  
by certified personnel only. The appliance will be marked to  
indicate suitability for high altitude operation.  
piping system during any pressure testing of that system at  
a test pressure in excess of 1/2 PSIG (3.5kPa).  
2. The appliance must be isolated from the gas supply piping  
system by closing a manual shutoff valve during any  
pressure testing of the gas supply piping system at test  
pressures equal to or less than 1/2 PSIG (3.5kPa).  
3. The appliance and its gas connection must be leak-tested  
before placing it in operation.  
GAS SUPPLY PRESSURE: Measured at the inlet pressure tap  
located upstream of the combination gas valve(s) see  
FIG. 3-5, page 22.  
Gas Connection  
1. Safe operation of the appliance requires properly sized gas  
supply piping. See data in Table 3C.  
TABLE - 3A  
GAS SUPPLY PRESSURE  
2. Gas pipe size may be larger than appliance gas connection.  
Natural Gas  
LP Gas  
3. Installation of a union is suggested for ease of service, see  
FIG. 3-1 on page 19.  
Max. (Inches Water Column)  
Min. (Inches Water Column)  
14  
14  
11  
4.5  
4. Install a manual main gas shutoff valve, outside of the  
appliance gas connection and before the gas valve or  
manifold connection, when local codes require.  
Maximum inlet gas pressure must not exceed the value  
specified. Minimum value listed is for the purposes of input  
adjustment.  
5. A trap (drip leg) MUST be provided by the installer in  
the inlet of the gas connection to the appliance, see  
FIG. 3-1 on page 19.  
MANIFOLD PRESSURE: Measured at the pressure tap on  
the downstream side of the combination gas valve(s) (see  
FIG. 3-5, page 22). The gas regulator settings for single stage  
and two stage operation are factory set to supply proper  
manifold pressure for normal operation. To check manifold  
pressure, see Manifold Adjustment Procedure. Do not increase  
manifold pressure beyond specified pressure settings shown  
below in Table 3B.  
6. The combination gas valve has an integral vent limiting  
device and does not require venting to atmosphere,  
outside the building.  
7. Optional gas controls may require routing of bleeds and  
vents to the atmosphere, outside the building when  
required by local codes.  
TABLE - 3B  
TABLE - 3C  
FITTINGS TO EQUIVALENT STRAIGHT PIPE  
MANIFOLD PRESSURE  
Single and  
Two Stage  
Two-Stage  
Diameter Pipe (inches)  
3/4  
2
1
1 1/4 1 1/2  
2
3
4
5
Input Gas  
Btu/hr  
Full or High Fire  
Settings  
Low Fire Settings  
Equivalent Length of Straight Pipe (feet)  
Natural  
LP Gas  
Gas  
Natural  
LP Gas  
Gas  
2
3
4
5
10  
14  
20  
45,000  
75,000  
3.5"  
2.4"  
3.5"  
3.5"  
10"  
7"  
0.9"  
0.9"  
0.9"  
0.9"  
2.5"  
2.5"  
2.5"  
2.5"  
TABLE - 3D  
GAS CONNECTIONS  
Btu/hr  
INPUT  
90,000 - 180,000  
215,000 - 260,000  
10"  
10"  
Pipe Size  
45,000 - 135,000  
180,000 - 260,000  
1/2"  
3/4"  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
3 Gas connections  
(continued)  
TABLE - 3E  
GAS PIPING SIZE CHART  
Nominal  
Iron Pipe  
Size  
Maximum  
Capacity of Pipe  
in Thousands of  
Length of Pipe in Straight Feet  
Inches  
Btu/hr per hour  
for gas pressures  
of 13.5 Inches  
Water Column  
(0.5 PSIG) or less  
and a pressure  
drop of 0.5 Inch  
Water Column  
(Based on NAT  
GAS, 1025  
10  
20  
30  
40  
50  
60  
70  
80  
90  
100 125 150 175 200  
3/4  
1
369  
256  
205  
174  
155  
141  
128  
121  
113  
106  
200  
410  
636  
95  
86  
79  
74  
697  
477  
974  
384  
789  
328  
677  
292  
595  
267  
543  
830  
246  
502  
769  
226  
472  
707  
210  
441  
666  
179 164  
369 333  
564 513  
149  
308  
472  
871  
138  
287  
441  
820  
1 1/4  
1 1/2  
2
1,400  
2,150 1,500 1,210 1,020 923  
4,100 2,820 2,260 1,950 1,720 1,560 1,440 1,330 1,250 1,180 1,100 974  
Btu/hr per Cubic  
Foot of Gas and  
0.60 Specific  
2 1/2  
3
6,460 4,460 3,610 3,100 2,720 2,460 2,310 2,100 2,000 1,900 1,700 1,540 1,400 1,300  
11,200 7,900 6,400 5,400 4,870 4,410 4,000 3,800 3,540 3,300 3,000 2,720 2,500 2,340  
23,500 16,100 13,100 11,100 10,000 9,000 8,300 7,690 7,380 6,870 6,150 5,640 5,130 4,720  
Gravity)  
4
Gas Piping  
2. Use new, properly threaded black iron pipe free from chips.  
If tubing is used, make sure the ends are cut squared,  
deburred and clean. All tubing bends must be smooth and  
without deformation. Avoid flexible gas connections.  
Internal diameter of flexible lines may not provide proper  
volume of gas.  
GAS VALVE  
GAS SHUTOFF VALVE  
3. Run pipe or tubing to the gas valve or manifold inlet. If  
tubing is used, obtain a tube to pipe coupling to connect  
the tubing to the gas valve or manifold inlet.  
4. DO NOT OVER TIGHTEN. Over tightening may result in  
damage to the gas valves. Valve distortion or malfunction  
may result if the pipe is inserted too deeply into the gas  
valve.  
TRAP  
(DRIP LEG)  
5. Apply a moderate amount of good quality pipe compound  
(DO NOT use Teflon tape) to pipe only, leaving two end  
threads bare.  
Figure 3-1_Gas Line Connection  
All gas connections must be made with pipe joint  
compound resistant to the action of liquefied petroleum and  
natural gas. All piping must comply with local codes. Tubing  
installations must comply with approved standards and  
practices. Reference FIG. 3-1 for a typical installation.  
6. Remove seal over gas valve or manifold inlet.  
7. Connect pipe to gas valve or manifold inlet. Use wrench to  
square ends of the gas valve (FIG. 3-2).  
Install Piping to Control  
1. The gas line should be  
a
separate line direct  
from the meter unless the existing gas line is of sufficient  
capacity. Verify pipe size with your gas supplier.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
3 Gas connections  
1. Turn the power “OFF” at the main disconnect switch.  
2. Turn gas valve control knob to “OFF” position.  
WHEN FLANGE  
IS USED  
3. Remove the 1/8" hex plug located on the outlet side of the  
gas valve and install a fitting suitable to connect to a  
manometer or magnahelic gauge. See FIG. 3-3. Minimum  
range of scale should be up to 5" w.c. for Natural gas  
models and 10" w.c. for L.P. gas models.  
WHEN FLANGE IS  
NOT USED  
APPLY WRENCH  
TO FLANGE ONLY  
4. Remove the pressure regulator adjustment cap screw on  
the gas valve. See FIG. 3-3 for location.  
5. Turn the power “ON” at the main disconnect switch.  
6. Turn gas valve control knob to “ON” position.  
7. Set the thermostat(s) to call for heat.  
APPLY WRENCH FROM TOP OR BOTTOM  
OF GAS CONTROL TO EITHER SHADED AREA  
Figure 3-2_Wrench  
8. Observe gas regulator pressure when all burners are firing.  
See Table 3B, Manifold Pressure (page 18) for proper  
regulator pressure settings.  
8. For L.P. gas, consult your L.P. gas supplier for expert  
installation.  
9. If adjustment is necessary, turn regulator adjustment screw  
clockwise to raise regulator gas pressure, counterclockwise  
to lower gas pressure, to proper setting. NOTE: Adjustment  
fitting is plastic and may require slightly greater turning  
force than a metal fitting.  
Upon completion of any piping  
IMPORTANT  
connections to the gas system, leak test all  
gas connections with a soap solution  
while system is under pressure.  
Immediately repair any leaks found in the  
gas train or related components. Do Not  
operate an appliance with a leak in the gas  
train, valves or related piping.  
10. Turn the power “OFF” at the main disconnect switch.  
Do not increase regulator pressure beyond  
specified pressure setting.  
NOTICE  
Gas Manifold Pressure Adjustment  
Procedure  
11. Turn gas valve control knob to “OFF” position.  
PRESSURE REGULATOR ADJUSTMENT  
(UNDER CAP SCREW)  
12. Remove fitting from the gas valve and replace the 1/8" hex  
plug that was previously removed and tighten.  
INLET  
PRESSURE TAP  
OUTLET  
PRESSURE TAP  
13. Turn the gas valve control knob to “ON” position.  
14. Turn the power “ON” at the main disconnect switch. The  
appliance is now ready to operate.  
PILOT OUTLET  
GAS CONTROL KNOB  
RED RESET BUTTON  
If manifold pressure can not be properly adjusted, use the  
procedure on page 21 to check gas supply pressure with a  
manometer connected to the inlet pressure tap on the gas  
control.  
MANOMETER  
3.5"  
GAS VALVE  
Figure 3-3_Manifold Pressure Adjustment  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
3 Gas connections  
(continued)  
Checking Gas Supply Pressure  
8. Set the thermostat(s) to call for heat.  
9. Observe the gas supply pressure with all burners firing.  
Ensure inlet pressure is within specified range. Check gas  
supply pressure with all other gas fired appliances in  
operation to ensure proper gas volume during periods of  
peak gas usage.  
GAS SUPPLY PRESSURE  
MANOMETER  
10. If gas pressure is out of range, contact gas utility, gas  
supplier, qualified installer or service agency to determine  
necessary steps to provide proper gas pressure to the  
control.  
11. If the gas supply pressure is within the specified range,  
proceed with the following steps to return the appliance to  
service.  
GAS VALVE  
12. Turn the power “OFF” at the main disconnect switch.  
13. Turn gas valve control knob to “OFF” position.  
14. Shut off gas supply at the manual valve in the gas piping to  
the appliance. If fuel supply is L.P. Gas, shut off gas supply  
at the tank.  
Figure 3-4_Gas Supply Pressure  
15. Remove the manometer and related fittings from the  
“inlet” side of the gas valve, replace 1/8" hex plug in gas  
valve.  
1. Turn the power “OFF” at the main disconnect  
switch.  
16. Turn on gas supply at the manual valve, turn on L.P. Gas at  
tank if required.  
2. Turn gas valve control knob to the “OFF” position.  
3. Shut off gas supply at the manual valve in the gas piping  
to the appliance. If fuel supply is L.P. gas, shut off gas  
supply at the tank.  
17. Turn the power “ON” at the main disconnect switch.  
18. Turn the gas valve control knob to the “ON” position.  
Spark ignition models will automatically light the pilot on  
a call for heat.  
4. Remove the 1/8" hex plug, located on the “inlet” side of  
the gas valve and install a fitting suitable to connect to a  
manometer or magnahelic gauge. Range of scale should 19. Set the thermostat to call for heat. The appliance is now  
be 14" w.c. or greater to check inlet pressure. See  
FIG.’s 3-3 and 3-4 for location.  
ready to operate.  
Upon completion of any testing on the gas  
IMPORTANT  
5. Turn on gas supply at the manual valve, turn on L.P. gas  
at tank if required.  
system, leak test all gas connections with a  
soap solution while main burners are  
operating. Immediately repair any leak  
found in the gas train or related  
components. Do Not operate an appliance  
with a leak in the gas train, valves or related  
piping.  
6. Turn the power “ON” at the main disconnect switch.  
7. Follow the “Lighting Instructions” in Section 6 - Startup  
to light the pilot . Turn gas valve control knob to the  
“ON” position.  
Check burner performance by cycling the system while you  
observe burner response. Burners should ignite promptly.  
Flame pattern should be stable, see the “Maintenance Section -  
Normal Flame Pattern. Turn system off and allow burners to  
cool, then cycle burners again to ensure proper ignition and  
flame characteristics.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
3 Gas connections  
Combination Gas Valves  
Venting of Combination Gas Valves  
PRESSURE REGULATOR  
ADJUSTMENT  
The combination gas valve regulator used on all  
models is equipped with an integral vent limiting  
orifice. The vent limiter ensures that the volume of  
gas emitted from the valve does not exceed the  
maximum safe leakage rate allowed by agency  
requirements. Combination gas valve/regulators  
equipped with integral vent limiters are not  
required to have vent or relief lines piped to the  
outdoors. A dust cap is provided at the vent  
termination point on the valve to prevent blockage  
of the vent limiter by foreign material. The  
combination gas valve regulator with an integral  
vent limiter complies with the safety code  
requirements of CSD-1, CF-190(a) as shipped from  
the manufacturer without the installation of  
additional vent lines.  
WIRING TERMINALS  
(UNDER CAP SCREW)  
OUTLET  
PRESSURE TAP  
INLET PRESSURE TAP  
PILOT OUTLET  
S CONTROL KNOB  
GA  
Figure 3-5_M9 Gas Valve  
Each unit has a combination gas valve to control the gas supply to the  
burners. The combination valve consists of a gas regulator and two valve  
seats to meet the requirements for redundant gas valves. The valve has a  
gas control knob that must remain in the open position at all times when  
the appliance is in service. Each gas valve has pressure taps located on the  
inlet and outlet sides. Manifold pressure is adjusted using the regulator  
located on the valve. The manifold pressure is preset at the factory and  
adjustment is not usually required. If the manifold pressure is to be  
adjusted, follow the “Gas Manifold Pressure Adjustment Procedure,  
page 20 for proper adjustment.  
Two Stage Burner Control System  
The 45,000 thru 260,000 Btu/hr boilers (M9) are  
equipped with a two stage burner control system.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
4 Water connections  
Relief Valve  
Water Flow Switch (if equipped)  
FLOW SWITCH  
RELIEF VALVE  
Figure 4-2_Water Flow Switch - Top Connections  
Figure 4-1_Relief Valve  
A water flow switch is available as a factory supplied option on  
all heating boilers (see FIG. 4-2). The flow switch should be  
wired between terminals X and B. Remove the jumper between  
the X and B terminals on the terminal strip. This wiring  
connection installs the flow switch in the 24 VAC safety circuit  
to prove water flow before main burner ignition. A flow switch  
installed with the factory supplied minimum adjustment setting  
requires a specific minimum flow to make the switch and start  
burner operation. The flow rate required is a function of the  
diameter of pipe and tee used for installation. Ensure that the  
pump installed on the boiler will supply adequate flow to make  
the flow switch contacts and operate the boiler.  
This appliance is supplied with a relief valve(s) sized in  
accordance with ASME Boiler and Pressure Vessel Code,  
Section IV (“Heating Boilers”). The relief valve(s) is mounted  
directly into the heat exchanger inside the header (see  
FIG. 4-1). To prevent water damage, the discharge from the  
relief valve shall be piped to a suitable floor drain for disposal  
when relief occurs. No reducing couplings or other  
restrictions shall be installed in the discharge line. The  
discharge line shall allow complete drainage of the valve and  
line. Relief valves should be manually operated at least once  
a year.  
Avoid contact with hot discharge water.  
ƽ CAUTION  
A water flow switch meets most code requirements for a low  
water cut off device on boilers requiring forced circulation for  
operation.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
4 Water connections  
Typical Heating Boiler Installations  
General Plumbing Rules  
Low Water Cutoff (if equipped)  
A hot water boiler installed above radiation level must be  
provided with a low water cutoff device either as part of the  
unit or installed at the time the boiler is installed. An  
electronic low water cutoff is available as a kit on all units.  
Low water cutoffs should be inspected every six months,  
including flushing of float types.  
1. Check all local codes.  
2. For serviceability of the boiler, always install unions.  
3. Always pipe pressure relief valves to an open drain.  
4. Locate system air vents at the highest point of the system.  
TABLE - 4A  
MINIMUM REQUIRED FLOW  
FOR HEATING BOILER  
5. Expansion tank must be installed near the boiler and on  
the suction side of the pump.  
Input Btu/hr  
45,000  
GPM Flow  
1.9  
6. Support all water piping.  
75,000  
3.1  
Placing the Boiler in Operation  
90,000  
3.7  
Filling the System: All air must be purged from the system for  
proper operation. An air scoop and air vent must be located  
close to the boiler outlet and there should be a minimum  
distance between the cold water feed and the system purge valve.  
135,000  
180,000  
215,000  
260,000  
5.6  
7.4  
8.9  
10.7  
1. Close all drain cocks and air vents.  
2. Open the makeup water valve and slowly fill the system.  
Minimum flow is based on a 40°F  
temperature rise across the boiler.  
Minimum flow may not prove a flow  
switch installed in the boiler piping. Use  
care when operating a boiler at or near  
the minimum recommended flow  
because conditions unique to the  
installation (system pressure, operation  
of multiple zone valves, glycol,  
variations in flow, etc.,) may result in  
overheating of the boiler water causing  
noise or nuisance operation of safety  
limit controls. Typical heating boiler  
applications will operate with a 20°F to  
30°F temperature rise across the boiler.  
NOTICE  
3. If a makeup water pump is employed, adjust the pressure to  
provide a minimum of 12 psi at the highest point in the  
system. If a pressure regulator is also installed in the line,  
it should be adjusted to the same pressure.  
4. Close all valves. Purge one circuit at a time as follows:  
A. Open one circuit drain valve and let the water drain for  
at least five minutes. Ensure that there are no air  
bubbles visible in the water stream before closing the  
drain valve.  
B. Repeat this procedure for each circuit.  
5. Open all valves after all circuits have been purged. Make  
sure there are no system leaks.  
Do not use petroleum based stop leak  
NOTICE  
products. All system leaks must be  
repaired. The constant addition of  
make-up water can cause damage to the  
boiler heat exchanger due to scale  
accumulation. Scale reduces flow and  
heat transfer, causing overheating of the  
heat exchanger.  
6. Run the system circulating pump for a minimum of 30  
minutes with the boiler turned off.  
7. Open all strainers in the system and check for debris.  
8. Recheck all air vents as described in step 4, General  
Plumbing Rules.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
4 Water connections  
(continued)  
9. Inspect the liquid level in the expansion tank. The  
system must be full and under normal operating  
pressure to ensure proper water level in the expansion  
tank. Ensure that diaphragm type expansion tanks are  
properly charged and not water logged.  
Piping of the Boiler System  
The drawings in this section (see FIG’s 4-7 thru 4-11) show  
typical heating boiler piping installations. Before beginning the  
installation, consult local codes for specific plumbing  
requirements. The installation should provide unions and  
valves at the inlet and outlet of the boiler so it can be isolated for  
service. The boiler circulating pump, air separator, expansion  
tank and other components required for proper installation  
must be purchased locally. An air separation device must be  
supplied in the installation piping to eliminate trapped air in the  
system. Locate a system air vent at the highest point in the  
system. The system must also have a properly sized expansion  
tank installed. Typically, an air charged diaphragm-type  
expansion tank is used. The expansion tank must be installed  
close to the boiler and on the suction side of the system pump to  
ensure proper operation.  
10. Start the boiler according to the Section 6 - “Start-Up  
Instructions” in this manual. Operate the system,  
including the pump, boiler and radiation units, for one  
hour.  
11. Recheck the water level in the expansion tank. If it  
exceeds half the tank volume, open the tank to reduce  
the water level. Recheck pressure charge on diaphragm  
type tanks.  
12. Shut down the entire system and vent all radiation units  
and high points in the system.  
This boiler system should not be operated at  
less than 12 PSIG.  
ƽ CAUTION  
13. Close the water makeup valve and check the strainer and  
pressure reducing valve for sediment or debris. Reopen  
the water makeup valve.  
14. Verify system pressure with the boiler pressure gauge  
before beginning regular operation.  
15. Within three days of start-up, recheck and bleed all air  
vents and the expansion tank using these instructions.  
TABLE - 4B  
SYSTEM TEMPERATURE RISE CHART  
Based on Boiler Output in Btu/hr  
Btu/hr  
10°F T  
GPM  
20°F T  
30°F T  
40°F T  
Input  
45,000  
75,000  
90,000  
135,000  
180,000  
215,000  
260,000  
Output  
36,900  
Ft/hd  
0.6  
1.3  
1.4  
3.2  
5.1  
--  
GPM  
Ft/hd  
0.2  
GPM  
Ft/hd  
0.2  
GPM  
Ft/hd  
0.2  
7.4  
12.3  
14.9  
22.3  
29.7  
--  
3.7  
6.2  
2.5  
4.1  
1.9  
3.1  
3.7  
5.6  
7.4  
8.9  
10.7  
61,500  
0.4  
0.3  
0.2  
73,800  
7.4  
0.5  
5.0  
0.3  
0.2  
110,700  
147,600  
176,300  
213,200  
11.1  
14.9  
17.0  
21.5  
1.2  
7.4  
0.6  
0.3  
1.6  
9.9  
0.7  
0.4  
1.3  
11.8  
14.3  
0.8  
0.4  
--  
--  
2.1  
0.9  
0.5  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
4 Water connections  
Hot water piping must be supported by suitable hangers or  
floor stands, NOT by the boiler. Copper pipe systems will be  
subject to considerable expansion and contraction. Rigid  
pipe hangers could allow the pipe to slide in the hanger  
resulting in noise transmitted into the system. Padding is  
recommended on rigid hangers installed with a copper  
system. The boiler pressure relief valve must be piped to a  
suitable floor drain. See the relief valve section on page 23 of  
this manual.  
Circulator Pump Requirements  
This is a low mass, high efficiency hot water boiler which must  
have adequate flow for quiet, efficient operation. The boiler  
circulating pump must be field supplied. The boiler circulator  
pump must operate continuously while the boiler is firing.  
Pump selection is critical to achieve proper operation.  
A
pump should be selected to achieve proper system design  
water temperature rise. A heat exchanger pressure drop chart  
(Table 4C) is provided to assist in proper pump selection.  
Also provided is a System Temperature Rise Chart (Table 4B  
on page 25). This table provides GPM and boiler head-loss at  
various temperature rises for each boiler based on Btu/hr  
input. Temperature rise is the difference in boiler inlet  
temperature and boiler outlet temperature while the boiler is  
firing. Example: The boiler inlet temperature is 160°F and the  
boiler outlet temperature is 180°F, this means that there is a  
20°F temperature rise across the boiler.  
A leak in a boiler system will cause the  
ƽ CAUTION  
system to intake fresh water constantly,  
which will cause the tubes to accumulate  
a lime/scale build up. This will cause a  
NON-WARRANTABLE FAILURE.  
Water Connections  
Heating Boilers with inputs of 45,000 - 260,000 Btu/hr have  
1 1/2" NPT inlet and outlet connections.  
Field installed reducing bushings may  
decrease flow resulting in boiler noise or  
flashing to steam.  
ƽ CAUTION  
TABLE - 4C  
HEAT EXCHANGER PRESSURE DROP CHART  
7
6
5
4
3
2
1
0
35  
0
30  
15  
20  
25  
5
10  
Gallons per Minute  
CB 315  
CB 360  
CB 399  
CB 500  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
4 Water connections  
(continued)  
PUMP INSTALLATION AND MAINTENANCE: The boiler  
circulating pump must be purchased locally. For installation  
and maintenance information on the circulator pump, refer to  
the pump manufacturers instruction package included with  
the pump.  
PERFORMANCE LOOP  
These units are equipped with an integral performance loop,  
which is designed to provide efficiency optimization by  
maintaining a constant flow through the unit’s heat exchanger  
loop when building system flow is reduced. The performance  
loop assembly is standard equipment and is NOT to be used  
as a system or boiler pump.  
Circulator Pump Specifications  
1. Maximum operating pressure for the pump must exceed  
system operating pressure.  
The performance loop is dedicated to  
NOTICE  
the unit and does not affect the  
building’s system or primary/secondary  
flow characteristics and will not  
circulate the building.  
2. Maximum water temperature should not exceed  
nameplate rating.  
3. Cast iron circulators may be used for closed loop  
systems.  
It is acceptable to remove the performance loop as long as  
the following requirements are met:  
4. A properly sized expansion tank must be installed near  
the boiler and located on the suction side of the pump.  
1. The boiler is piped to the system in primary/secondary  
fashion.  
2. The system setpoint is 140°F or higher.  
3. The boiler circulating pump is sized for the appropriate  
flow through the boiler.  
4. The system sensor is installed in an acceptable location  
for sensing the system supply temperature.  
5. If water temperature is below 140°F a low temperature  
bypass must be installed, (VAL30000 - 1 1/2" LTV Valve  
Kit) and follow the piping diagram in FIG. 4-4.  
Circulator Pump Operation  
Boilers are equipped with a relay for controlling the  
circulation pump for the hot water loop. The relay turns ON  
and OFF in response to the “W” input from the wall  
thermostat or zone control.  
The field installed boiler pump MUST NOT exceed 1 h.p.  
For continuous pump operation, wire the system pump to  
the 120V supply. The pump should be connected at the  
junction box as shown in FIG. 4-3.  
If removal of the performance loop is  
NOTICE  
necessary, consult the manufacturer for  
a Solution Without a Performance Loop  
(KIT30068).  
120V  
SUPPLY  
Failure to install the system sensor can  
cause operation problems such as  
nuisance high limit trips.  
ƽ WARNING  
Primary/Secondary Boiler Piping  
TO  
UNIT  
A primary/secondary piping system may also be installed to  
ensure proper boiler flow rates. Primary/secondary piping is  
also ideal for systems using a mixture of propylene glycol and  
water. A primary/secondary piping system uses a dedicated  
pump to supply flow to the boiler only. This pump is sized  
based on desired boiler flow rate, boiler head loss and head loss  
in the secondary system piping only. The secondary pump, in-  
stalled in the boiler piping, ensures a constant water flow rate  
to the boiler for proper operation. Boiler installation with a  
primary/secondary piping system can prevent noise problems  
caused by low system water flows. A primary/secondary piping  
system is recommended on any boiler where low water flow  
conditions may present an operational problem.  
TO  
CIRCULATION  
PUMP  
TO PERFORMANCE  
LOOP PUMP (OPT.)  
Figure 4-3_Boiler Wiring - Circulation Pump to Junction Box  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
4 Water connections  
Primary/Secondary Boiler Piping (continued)  
A primary/secondary piping system is ideal for systems filled  
Low Temperature Bypass Requirements  
with a propylene glycol and water mixture. A glycol and water  
mixture is more dense than water only and may result in a  
lower boiler flow rate. A lower boiler flow may cause noisy  
operation or short cycling of the burners. A larger secondary  
pump may be used on a primary/secondary system to provide  
an increased boiler flow rate. A glycol and water system may  
require from 10 to 20% more flow to compensate for the  
increased density of the glycol and its effect on the heat  
transfer process in the boiler. The exact increase in flow that  
may be required is based on the type and percentage of glycol  
added to the boiler system. Consult the manufacturer of the  
glycol for additional recommendations when using a glycol  
and water fill for your boiler system.  
Inlet water temperatures below 140°F (60°C) can excessively  
cool the products of combustion resulting in condensation on  
the heat exchanger and in the flue. Condensation can cause  
operational problems, bad combustion, sooting, flue gas spillage  
and reduced service life of the vent system and related  
components. The bypass allows part of the boiler discharge  
water to be mixed with the cooler boiler return water to increase  
the boiler inlet temperature above 140°F (60°C). This should  
prevent the products of combustion from condensing in most  
installations. The bypass should be fully sized with a balancing  
valve to allow for proper adjustment. A valve must also be  
provided on the boiler discharge, after the bypass. Closing this  
discharge valve forces water through the bypass. Start boiler  
adjustment with the bypass valve in the full open position and  
the boiler discharge valve half open. A small amount of the  
higher temperature boiler discharge water is mixed with the  
system water to maintain the desired lower system temperature.  
The installer must ensure that the boiler has adequate flow  
without excessive temperature rise. The temperature rise on  
a multiple zone system should be made when only the zone  
with the longest length and/or highest head loss is open. Low  
system flow can result in overheating of the boiler water  
which can cause short burner on cycles, system noise and in  
extreme cases, a knocking flash to steam. System noise may  
also indicate an oversized boiler.  
Boiler Flow Rates  
The maximum flow rate through the boiler  
with a copper heat exchanger must not  
exceed 30 GPM.  
ƽ CAUTION  
At no time should the system pressure be  
less than 12 PSIG.  
ƽ CAUTION  
The heat exchanger is generally capable of operating within the  
flow rates of a residential heating system. Should the flow rate  
exceed the maximum allowable flow rate through the boiler 30  
GPM) an external bypass must be installed. The bypass should be  
fully sized with a balancing valve to allow for proper adjustment of  
flow. Flow rate can be determined by measuring the temperature  
rise through the boiler.  
A boiler operated with an inlet temperature of less than 140°F  
(60°C) must have a bypass to prevent problems with  
condensation. A bypass as shown in FIG. 4-8 (see page 33)  
must be piped into the system at the time of installation.  
Full Flow Application  
It is acceptable for the Solution boiler to be installed in a full  
flow application, as long as the following requirements are  
met:  
The basic guide for minimum flow in this boiler is based on a  
40°F temperature rise in most installations. Lower flow and a  
higher temperature rise is acceptable if the boiler system is  
specifically designed for the characteristics of a higher  
temperature rise. A system not specifically designed for a higher  
temperature rise may experience overheating of the boiler water.  
This can cause short burner on cycles, system noise and in  
1. The performance loop is in place and functional.  
2. The system flow is not lower than the minimum boiler  
flow.  
3. The boiler setpoint is 140°F or higher.  
4. If water temperature is below 140°F you must install a  
low temperature bypass, VAL30000, and follow the piping  
diagram shown in FIG. 4-7.  
extreme cases,  
a
knocking flash to steam. These  
conditions can lead to operational problems and  
non-warrantable failures of the boiler. High temperature rise  
systems must be designed by a qualified engineer.  
Varying the flow through a Solution boiler  
ƽ WARNING  
can cause harmonic noises and high limit  
trips if the flow is below the minimum  
boiler flow rate found in Table 4A.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
4 Water connections  
(continued)  
Primary / Secondary Piping  
Figure 4-4_Primary / Secondary Piping of a Single Boiler  
PRESSURE  
REDUCING VALVE  
PRESSURE  
BACKFLOW  
PREVENTER  
GAUGE  
MAKE UP WATER  
SYSTEM SUPPLY  
SENSOR  
AIR  
SEPARATOR  
SYSTEM  
CIRCULATOR  
FROM  
TO  
SYSTEM  
SYSTEM  
12"  
NOT TO EXCEED  
APART  
BALL VALVE  
(TYPICAL)  
BOILER  
EXPANSION  
TANK  
CIRCULATOR  
DRAIN POINT  
(TYPICAL)  
Y-STRAINER  
(RECOMMENDED)  
UNION  
(TYPICAL)  
TEMPERATURE / PRESSURE  
GAUGE  
DRAIN  
PRESSURE  
RELIEF VALVE  
SOLUTION  
BOILER  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
4 Water connections  
Primary / Secondary Piping  
Figure 4-5_Single Boiler - Primary / Secondary with Low Temperature Bypass  
PRESSURE  
REDUCING VALVE  
PRESSURE  
BACKFLOW  
PREVENTER  
GAUGE  
MAKE UP WATER  
SYSTEM SUPPLY  
SENSOR  
AIR  
SEPARATOR  
SYSTEM  
CIRCULATOR  
FROM  
TO  
SYSTEM  
SYSTEM  
NOT TO EXCEED 12"APART  
BALL VALVE  
(TYPICAL)  
LOW TEMPERATURE BYPASS  
BOILER  
CIRCULATOR  
EXPANSION  
TANK  
DRAIN POINT  
(TYPICAL)  
Y-STRAINER  
(RECOMMENDED)  
UNION  
(TYPICAL)  
TEMPERATURE / PRESSURE  
GAUGE  
DRAIN  
PRESSURE  
RELIEF VALVE  
SOLUTION  
BOILER  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
4 Water connections  
(continued)  
Primary / Secondary Piping  
Figure 4-6_Multiple Boilers Zoned with Circulators  
ZONE #1  
ZONE CIRCULATORS  
(TYPICAL)  
PRESSURE  
PRESSURE  
GAUGE  
REDUCING VALVE  
ZONE #2  
ZONE #4  
ZONE #3  
BACKFLOW  
PREVENTER  
MAKEUP WATER  
SYSTEM SUPPLY  
SENSOR  
(WHEN USED)  
AIR SEPARATOR  
NOT TO EXCEED 12" APART  
BALL VALVE  
(TYPICAL)  
EXPANSION  
TANK  
MAY SUBSTITUTE LOW LOSS HEADER  
DRAIN POINT  
(TYPICAL)  
HOT  
WATER  
OUT  
ANTI-SCALD  
MIXING VALVE  
FLOW CHECK  
COLD  
VALVE  
BOILER  
WATER  
IN  
CIRCULATOR  
Y-STRAINER  
RELIEF VALVE  
(RECOMMENDED)  
RECIRCULATION  
LOOP  
AQUASTAT  
UNION  
(TYPICAL)  
TEMPERATURE /  
PRESSURE  
GAUGE  
PRESSURE  
RELIEF VALVE  
BOILER 2  
(LEADER 1)  
BOILER 1  
(LEADER)  
INDIRECT  
DHW TANK  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
4 Water connections  
Full System Flow  
Figure 4-7_Single Boiler Full System Flow  
PRESSURE  
REDUCING VALVE  
PRESSURE  
GAUGE  
BACKFLOW  
PREVENTER  
MAKE UP WATER  
SYSTEM SUPPLY  
SENSOR  
AIR  
SEPARATOR  
SYSTEM  
CIRCULATOR  
FROM  
TO  
SYSTEM  
SYSTEM  
BALL VALVE  
(TYPICAL)  
EXPANSION  
TANK  
Y-STRAINER  
(RECOMMENDED)  
UNION  
(TYPICAL)  
TEMPERATURE / PRESSURE  
GAUGE  
DRAIN  
PRESSURE  
RELIEF VALVE  
SOLUTION  
BOILER  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
4 Water connections  
(continued)  
Full System Flow  
Figure 4-8_Single Boiler Full System Flow with Low Temperature Bypass  
PRESSURE  
REDUCING VALVE  
PRESSURE  
GAUGE  
BACKFLOW  
PREVENTER  
MAKE UP WATER  
SYSTEM SUPPLY  
SENSOR  
AIR  
SEPARATOR  
SYSTEM  
CIRCULATOR  
FROM  
SYSTEM  
TO  
SYSTEM  
BALL VALVE  
(TYPICAL)  
3-WAY VALVE W/BYPASS PIPE  
EXPANSION  
TANK  
BOILER  
CIRCULATOR  
Y-STRAINER  
(RECOMMENDED)  
UNION  
(TYPICAL)  
TEMPERATURE / PRESSURE  
GAUGE  
DRAIN  
PRESSURE  
RELIEF VALVE  
SOLUTION  
BOILER  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
5 Electrical connections  
This appliance is wired for 120 VAC service. The appliance,  
when installed, must be electrically grounded in accordance  
with the requirements of the authority having jurisdiction or  
in the absence of such requirements, with the latest edition of  
the National Electrical Code ANSI/NFPA No. 70. When the  
unit is installed in Canada, it must conform to the CSA C22.1,  
Canadian Electrical Code, Part 1 and/or local Electrical  
Codes.  
Remove the jumper between the R and W terminals on the  
terminal strip. Refer to the chart in this section (Table 5A) to  
determine maximum allowable length and wire gauge  
recommended to connect the switching contacts of the room  
thermostat to the R and W terminals on the terminal strip.  
Connection to the terminal strip will allow the room thermostat  
to make and break the 24VAC boiler control circuit turning the  
boiler on and off based on the room ambient temperature  
requirements. Set the boiler operating temperature control as  
described in this section.  
1. All wiring between the appliance and field  
installed devices shall be made with type T wire  
[63° F(35° C) rise].  
2. Line voltage wire exterior to the appliance must be  
enclosed in approved conduit or approved metal clad  
cable.  
B
3. The pump must run continuously when the appliance is  
being fired.  
4. To avoid serious damage, DO NOT energize the  
appliance until the system is full of water. Serious  
damage may result.  
A
5. Provide the unit with proper overload protection.  
6. Install a wall thermostat on the inside wall. DO NOT  
install the thermostat in an area affected by drafts,  
sunlight, light fixtures, hot or cold water pipes or near a  
fireplace. See “Room Thermostat or Remote Thermostat  
Connection to Terminal Strip” (this page), for proper  
wiring connection.  
Figure 5-1_Terminal Strip Connections  
TABLE - 5A  
TERMINAL STRIP WIRING  
Wire Gauge  
Maximum  
Allowable Length  
Boiler Operating Temperature Control  
12 GA  
14 GA  
16 GA  
18 GA  
100 ft.  
75 ft.  
50 ft.  
30 ft.  
The operating temperature control is located in the control  
panel, behind the control panel front access door. The sensing  
element for the operator is placed in a bulbwell installed in  
the heat exchanger. Carefully observe the inlet water  
temperature on the initial boiler on cycles. The exact  
temperature set point is based on your system’s requirements.  
Turn the control set point dial to the desired operating water  
temperature. Observe the boiler discharge temperature after  
each set point adjustment to ensure proper operation.  
Auxiliary Device Connection to Terminal  
Strip  
A terminal connection strip is provided for ease of connection  
for Power Venting Systems, see FIG. 5-1, inset A.  
Room Thermostat or Remote Thermostat  
Connection to Terminal Strip  
A field supplied powered venter or powered louver/damper may  
be connected to the Solution boiler via a terminal strip located  
on the left side of the unit, see FIG. 5-1, inset B.  
A room thermostat or remote temperature control may be  
connected to the boiler. The room thermostat should be  
installed on an inside wall, away from the influences of drafts,  
hot or cold water pipes, lighting fixtures, televisions, sun rays  
or fireplaces. Follow the manufacturers instructions supplied  
with the thermostat for proper installation and adjustment.  
The boiler is equipped with a terminal strip on the left side of  
the control panel to allow easy connection (FIG. 5-1).  
A 24 VAC relay can be powered from this location when a call for  
heat has been established. A device proving switch can be  
interlocked back to the appliance to ensure its operation before  
the appliance is allowed to fire.  
Reference the wiring diagram on page 50 of this manual.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
5 Electrical connections  
(continued)  
Pump Wiring for a Heating Boiler  
Temperature Adjustment  
The heating boiler circulating pump must be purchased  
locally. The maximum load for the pump switched by the  
internal pump relay must not exceed 1 HP. The current draw  
for a field installed 120 VAC pump MUST be added to the  
boiler’s current draw to determine the minimum wire size for  
120 volt service.  
Operating Temperature Control  
The temperature controller is pre-set at the  
NOTICE  
factory with test settings. You may need to  
adjust the settings to meet your specific  
needs.  
Return water temperatures must not be less  
than 140°F. If lower return water  
temperatures are required, follow the  
instructions for Low Temperature Bypass  
Requirements, see page 28.  
TABLE - 5B  
AMP DRAW DATA  
45,000 thru 260,000 Btu/hr Models  
ƽ WARNING  
MAXIMUM  
FIRING CONTROLS  
TOTAL AMPS  
@ 120 VAC  
Locating Temperature Control  
Remove the control panel door on the front of the unit in order  
to locate and access the temperature control.  
M9 with Performance Loop Pump  
1.25  
Temperature Control Settings  
IGNITION MODULE  
Remove the control panel door on the front of the unit in unless  
your unit is specified as a boiler only with an outdoor air reset  
option. If your unit is a boiler only with an outdoor air reset  
option, there are additional controls for this option. They are  
explained under Outdoor Air Reset Option, page 37.  
TEMPERATURE CONTROL  
MANUAL RESET HIGH LIMIT (IF EQUIPPED)  
The three setting knobs on the temperature control are for Set  
point, Differential, and High-Fire Offset (see FIG. 5-3).  
PUMP RELAY  
TRANSFORMER  
Figure 5-2_Intermittent Pilot System M9 Control Panel  
Figure 5-3_Temperature Control  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
5 Electrical connections  
High-Fire Offset  
Maximum Set Point Determination  
The temperature control operates a two-stage firing system. The  
two stages are High-Fire and Low-Fire. High-Fire operates all  
burners at full rate while Low-Fire operates the burners at  
approximately one-half rate.  
The maximum set point for the control is factory set. Boilers  
can be set to 240°F max.  
These maximum set points are established by cutting the OJ1  
and OJ2 jumpers located on the right side of the temperature  
controller. The maximum set point is determined as shown  
below in Table 5C.  
The High-Fire Offset knob specifies the number of degrees  
below set point that the High-Fire stage shuts down. At that  
point, the unit will continue to operate at the Low-Fire stage  
until the set point is reached.  
TABLE - 5C  
The High-Fire Offset knob has settings between 0°F and 20°F. If  
set at 0°F, the High-Fire Offset is disabled and the unit will  
operate the High-Fire stage until the set point is reached and the  
temperature control shuts the unit off.  
MAXIMUM SET POINT DETERMINATION  
MAX.  
OJ1  
OJ2  
SET POINT  
Connected  
Cut  
Connected  
Connected  
Cut  
240°F  
If the High Fire Offset knob is set to 0 or 1, the delay will be  
10 seconds; if set to 2 or above the delay will be 120 seconds.  
190°F  
Connected  
Cut  
200°F  
Boiler Application  
Cut  
160°F  
Standard boiler units are equipped with one inlet water  
temperature sensor. A system sensor is also provided for use as  
a remote system sensor. Boilers with the outdoor air reset  
option also have an outside air temperature sensor.  
Anytime that OJ1 is the only jumper cut, a  
new overlay is required under the Set  
Point knob on the temperature controller  
because the scale has changed to a  
maximum of 190°F.  
NOTICE  
Temperature Control Sensors  
This is a two-stage temperature control that controls the burner  
ignition and pump functions. This temperature controller can  
measure up to three different sensor inputs, depending upon  
how the unit is set up. They are as follows:  
Anytime the OJ2 jumper is cut (with or  
without OJ1), a new overlay is required  
under the Set Point knob on the  
temperature controller because the scale  
has changed to a maximum of 200°F.  
1. Inlet Water Temperature Sensor  
2. System Sensor  
Set Point  
3. Outside Air Temperature Sensor  
The Set Point knob specifies the target inlet water  
temperature in degrees, Fahrenheit. After the water  
temperature reaches the set point, the temperature control  
shuts off the burners.  
Inlet Water Temperature Sensor  
This sensor measures the inlet water temperature coming into  
the unit.  
Differential  
The inlet water temperature sensor is placed into the inlet  
bulbwell on the boiler. This sensor is installed by the factory in  
new units.  
The Differential specifies the number of degrees below the set  
point that the control will allow the water temperature to  
drop before it brings the unit back on again.  
System Sensor  
Depending upon how your unit is set up, this sensor can be used  
as a system sensor in a boiler system or a tank sensor for water  
heater applications. Connect this sensor to the two blue wires in  
the upper left-hand corner of the control panel.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
5 Electrical connections  
(continued)  
Outdoor Air Temperature Sensor  
Ground the cable shield at the connection  
to the boiler temperature control only. Do  
not ground the shielded cable at the sensor  
end.  
NOTICE  
The outside air temperature sensor will only be used for  
boiler systems. The outside air sensor is optional. This sensor  
allows you to tie boiler operation to the outdoor air  
temperature. As outside temperatures drop, the control will  
increase the temperature setting of the boiler. As outdoor  
temperatures rise, the control will decrease the temperature  
to the selected set point of the boiler. You can set the control  
to shut the boiler off when a desired outdoor air temperature  
level is reached.  
To maintain temperature accuracy, sensor  
wires should be 18 AWG two conductor  
(18/2). Use shielded wire if required.  
Installation of Remote Sensors  
1. Turn OFF the main electrical power and the main manual  
gas shutoff to the appliance.  
You must purchase the sensor from the appliance  
manufacturer. The sensor comes with a housing that helps  
protect the sensor from the elements. Mount the air sensor  
housing outdoors, under the eve of the roof. Make sure the  
housing is out of direct sunlight. This will ensure that the  
sensor will accurately read the true outdoor temperature.  
Connect the outdoor air temperature sensor to the terminal  
block on the outdoor air reset board. For more information  
on wiring the sensor, see Wiring of Remote Sensors, this page.  
2. Remove the side access panel from the appliance to gain  
access to the thermostat.  
3. Locate the sensor in the kit. Determine the location of the  
remote sensor and measure the amount of wire needed to  
connect the sensor to the thermostat. See Wiring of the  
Remote Sensors for guidelines.  
4. Use twisted pair wire, minimum 18 gauge or larger. See  
Table 5A, page 34 regarding distance versus wire gauge.  
Ensure all wire insulation is trimmed to reveal at least 3/8"  
of exposed wire.  
Wiring of Remote Sensors  
To wire remote sensors, follow the guidelines below. Take care  
to correctly wire sensors to the unit. Erratic temperature  
readings can be caused by poor wiring practices. Twist the  
wires between the unit and the remote sensor. Turn wires at  
least three or four turns per linear foot of wiring. This  
provides protection against some types of electrical  
interferences.  
5. Connect the measured wire to the sensor wire using wire  
caps (see FIG. 5-4). Install .250 x .032 insulated female  
quick connect terminals to the end of the wires. Feed the  
wires through the access hole located on the back of the unit  
and secure the connectors to the thermostat connections  
(Sys/Tank) CN5 and CN6 located in the upper right-hand of  
the thermostat.  
1. Do not route temperature sensor wiring with building  
power wiring.  
6. Turn on the electrical power and the main manual gas  
shutoff to the appliance.  
2. Do not locate temperature sensor wiring next to control  
contactors.  
7. Replace the side access panel.  
3. Do not locate temperature sensor wiring near electric  
motors.  
8. Fire the appliance and resume operation.  
4. Do not locate temperature sensor wiring near welding  
equipment.  
5. Make sure good mechanical connections are made to the  
sensor, any interconnecting wiring and the controller.  
6. Do not mount sensor with leadwire end pointing up in an  
area where condensation can occur.  
7. Use shielded wiring to connect the sensor to the control  
when the possibility of an electrically noisy environment  
exists. Shielded cable is recommended on all cable runs of  
more than 25 feet in length.  
ACCESS HOLE  
CONNECT THE MEASURED  
WIRE TO THE SENSOR WIRE  
Figure 5-4_Installation of Remote Sensors  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
5 Electrical connections  
If the outdoor design and boiler design temperatures are known,  
the Ratio setting can be calculated using the following formula:  
Outdoor Air Reset Option  
For boilers ordered with the Outdoor Air Reset option, there  
is an additional control (FIG. 5-5). There are three setting  
knobs for Shutdown, Outdoor Air Max., and Ratio. There is  
also a switch to turn the outdoor air shutdown feature On or  
Off. An O.A. Sensor is also included.  
Ratio = (boiler design temperature - operator set point)  
(O.A. Max. setting - outdoor design temperature)  
Note that the reset set point cannot exceed the maximum set  
point of the boiler thermostat.  
CN1  
(c)2002 L.C.  
CN3  
CN4  
These settings are illustrated graphically in FIG. 5-6.  
55  
CN2  
OJ1  
CN7  
CN8  
50  
60  
65  
O.A. SENSOR  
45  
ON  
ENABLE  
SW1  
VR3  
DISABLE  
40  
70  
W1  
CN5  
CN6  
OJ2  
O.A. SHUTDOWN  
SHUTDOWN  
55  
1.0  
0.9  
0.8  
1.1  
50  
45  
60  
65  
1.2  
1.3  
1.4  
1.5  
RATIO  
10  
0.7  
0.6  
W3  
W2  
VR1  
VR2  
0.5  
40  
70  
W1  
CN1  
O.A. MAX.  
CN9  
160  
11  
12  
9
10  
200  
8
7
140  
120  
15  
20  
HIGH-FIRE  
OFFSET  
5
13  
14  
15  
220  
6
VR2  
VR3  
5
(F-)0  
240  
DIFFERENTIAL  
OFF  
TST2314  
SETPOINT  
Figure 5-5_Optional Outdoor Air Reset Control  
Shutdown  
Figure 5-6_Outdoor Air Control Example Chart  
The Shutdown knob specifies the outdoor air lockout  
temperature at which the control would prevent the unit from  
operating.  
Outdoor Air Shutdown Enable/Disable Switch  
The Outdoor Air Shutdown Enable/Disable switch turns the  
outdoor air shutdown feature On and Off. Disabling the  
Outdoor Air Shutdown feature allows the unit to operate  
regardless of the outdoor air temperature. This is needed for  
indirect domestic hot water systems for example.  
Outdoor Air Max (O.A. Max)  
The O.A. Max knob allows a reset up to the maximum  
outdoor air temperature specified by this knob setting. When  
the outdoor air temperature is above the specified setting, the  
unit will not function in the O.A. Reset Mode, but will  
continue to run at the selected set point temperature.  
Additional Temperature Controls  
High Water Temperature Limit Control  
Note that the set point knob will now indicate the “minimum”  
boiler temperature. Target temperature is determined by the  
ratio and outdoor air temperature below the O.A. Max  
setting.  
The appliance is supplied with a fixed setting, auto-reset high  
water temperature limit control. The setting of this control  
limits maximum discharge water temperature. If water  
temperature exceeds the setting, the limit will break the control  
circuit and shut down the appliance. The limit control will only  
be reset after the water temperature has cooled well below the  
setting of the limit. The auto-reset high water temperature limit  
control is mounted in the outlet side of the front header.  
Ratio  
The Ratio knob allows control over the reset ratio to be used  
during Outdoor Air Reset. The allowable ratios are as low as  
0.5:1 or as high as 1.5:1.  
Selecting the 0.5:1 ratio will increase the set point 0.5° for  
every 1.0° drop in outdoor air temperature up to the  
maximum set point temperature.  
Selecting the 1.5:1 ratio will increase the set point 1.5° for  
every 1.0° drop in outdoor air temperature up to the  
maximum set point temperature.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
5 Electrical connections  
(continued)  
Blocked Vent and Flame Roll-Out / Flame  
Interlock Switch  
OUTER AIR  
DEFLECTOR  
UPPER FRONT  
JACKET PANEL  
FLAME ROLL-OUT SWITCH /  
INTERLOCK SWITCH  
DETAIL A  
LOWER FRONT  
JACKET PANEL  
HEX FILLER BRACKET  
BLOCKED VENT SWITCH  
INVERTED TO SHOW RESET  
UNDERNEATH  
Figure 5-8_Flame Roll-Out / Flame Interlock Switch Location  
All units are equipped with manual reset blocked vent and flame  
roll-out / flame interlock switches. These temperature switches  
are located in the controls compartment and in the relief  
opening of the boiler’s built-in draft hood. Each switch has a  
red reset button. In the event the system has actuated to shut off  
the main burner gas supply, wait for the boiler to cool, then  
press the red reset to return the boiler to operation. Operation  
of a blocked vent and/or flame roll-out / interlock switch usually  
indicates a problem with the venting system, obstruction of the  
heat exchanger flue gas passageway and/or a combustion air  
supply problem. The cause for operation of the blocked vent  
and/or flame roll-out / interlock switch must be determined and  
corrected. If the boiler cannot be restored to normal operation,  
contact a qualified service installer, service agency or the gas  
supplier.  
DRAFT HOOD  
Figure 5-7_Blocked Vent Switch Location  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
6 Start-up  
Initial Start-up  
7. Check carefully for gas leaks.  
Follow the Lighting Instructions on the label applied to the  
appliance.  
8. Read the appliance’s safety warnings, lighting instructions  
and check out procedure carefully, before firing the system.  
A. On boilers with the system pump delay option, the  
operating temperature control will energize the  
pump relay which energizes the pump on a call for  
heat. The operating temperature control will de-  
energize the pump relay approximately 30 seconds  
after the call for heat ends. If either the inlet sensor  
or the optional multi-purpose temperature sensor  
reads below 40°F, the pump relay will turn ON.  
When the temperature rises above 50°F the pump  
relay will turn OFF.  
Lighting Instructions for Spark Ignition  
Pilot Models  
FOR YOUR SAFETY READ BEFORE  
OPERATING  
If you do not follow these instructions  
ƽ WARNING  
exactly, a fire or explosion may result  
causing property damage, personal injury or  
loss of life.  
On boilers, the pump will operate whenever the “W”  
terminal is energized.  
A. This appliance is equipped with an ignition device  
which automatically lights the pilot. Do not try to light  
the pilot by hand.  
B. Location - The appliance should be located within a  
room having a temperature safely above freezing  
[32°F(0°C)].  
B. BEFORE OPERATING, smell around the appliance  
area for gas. Be sure to smell next to the floor because  
some gas is heavier than air and will settle to the floor.  
C. Shutdown and Draining - If, for any reason,  
the appliance is shut off, the following  
precautionary measures must be taken:  
1. Shut off gas supply,  
2. Shut off water supply.  
3. Shut off electrical supply.  
WHAT TO DO IF YOU SMELL GAS  
Do not try to light any appliance.  
4. Drain the heat exchanger completely. Remove one  
3/8" NPT plug or bulbwell from the inlet side and  
one from the outlet side of the front header of the  
heat exchanger.  
5. Drain the pump. Remove the 3/4" plug in the  
performance loop.  
Do not touch any electric switch; do not use any phone  
in your building.  
Immediately call your gas supplier from a near by  
phone. Follow the gas supplier’s instructions.  
If you cannot reach your gas supplier, call the fire  
department.  
Pre-start Checklist  
C. Use only your hand to turn the gas control knob.  
Never use tools. If the knob will not turn by hand,  
don’t try to repair it, call a qualified service technician.  
Force or attempted repair may result in a fire or  
explosion.  
1. Inspect the burners to be sure they are properly aligned.  
2. Inspect the pilot gas line, thermocouple leads, ignition  
leads and wire connections to the gas valve to be sure  
none were damaged during shipment.  
D. Do not use this appliance if any part has been under  
water. Immediately call a qualified service technician  
to inspect the appliance. The possible damage to a  
flooded appliance can be extensive and present  
numerous safety hazards. Any appliance that has been  
under water must be replaced.  
3. Check to ensure that gas connections have been made  
properly and the gas line is purged of air.  
4. Check to ensure that water connections are tight and the  
appliance and piping system have been properly filled.  
5. Ensure that discharge from the relief valve has been  
piped to a floor drain.  
6. Verify that properly sized combustion and  
ventilation air openings are provided and not obstructed  
in any way.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
6 Start-up  
(continued)  
To Turn Off Gas to Appliance  
Operating Instructions  
1. Set the thermostat to the OFF position.  
1. STOP! Read the safety information first.  
2. Remove the control panel door.  
2. Turn off all electric power to the appliance if service is to  
be performed.  
3. Set the thermostat to the lowest setting (OFF).  
4. Turn off all electrical power to the appliance.  
3a. 45,000 - 135,000 Btu/hr models, rotate the gas control  
knob on the gas valve clockwise to the “OFF” position. Do  
not force.  
5. This appliance is equipped with an ignition device  
which automatically lights the pilot. DO NOT try to  
light the pilot by hand.  
3b. 180,000 - 260,000 Btu/hr models, rotate the gas control  
knob on the gas valve clockwise to the line on the collar  
around the knob. Depress the knob and continue rotation  
to the “OFF” position. Do not force.  
6a. 45,000 - 135,000 Btu/hr models, rotate the gas control  
knob on the gas valve clockwise to the “OFF” position.  
Should overheating occur or the gas fail to  
ƽ WARNING  
6b. 180,000 - 260,000 Btu/hr models, rotate the gas control  
knob on the gas valve clockwise to the line on the collar  
around the knob. Depress the knob and continue  
rotation to the “OFF” position.  
shut off, turn off the external manual gas  
valve to the appliance.  
Safety Shutoff Test for Spark  
Ignition Pilot System  
7. Wait five (5) minutes to clear out any gas, then smell for  
gas, including near the floor. If you smell gas, STOP!  
Follow the steps in the “What To Do If You Smell Gas”  
section in the safety information on page 39. If you do  
not smell gas go on to the next step.  
1. Turn “OFF” gas supply to the appliance.  
2. Turn thermostat to highest setting.  
3. Turn electric power “ON.  
8a. 45,000 - 135,000 Btu/hr models, rotate the gas control  
knob on the gas valve counterclockwise to the “ON”  
position.  
4. Pump relay pulls in to start pump.  
5. The ignition will begin sparking at the pilot.  
8b. 180,000 - 260,000 Btu/hr models, rotate the gas control  
knob on the gas valve counterclockwise to the line on  
the collar around the knob. Allow the knob to “pop” up,  
and continue rotation to the “ON” position.  
6. The ignition module will lock out after the 90 second trial  
for ignition period.  
7. Immediately call  
a
qualified serviceman or  
9. Turn on all electric power to the appliance.  
10. Set the thermostat to the desired setting.  
11. Re-install the control panel door.  
installer to repair an ignition system that fails to  
lock out and properly shut down burner operation.  
8. After successful completion of the test, readjust the  
thermostat to normal setting.  
12. If the appliance will not operate, follow the instructions  
To Turn Off Gas To Appliance” and call your service  
technician or gas supplier.  
9. Turn “ON” gas supply.  
10. Turn power “OFF” then “ON” to reset ignition module.  
11. If ignition system fails to operate properly, repair work  
must be performed by a qualified serviceman or installer.  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
6 Start-up  
6. Shut-down and Draining - If for any reason, the appliance  
is to be shut off, the following precautionary measures  
must be taken:  
Intermittent Pilot Spark Ignition  
System  
The ignition module is not repairable.  
ƽ WARNING  
(a) Shut off gas supply.  
Any modification or repairs will invalidate  
the warranty and may create hazardous  
conditions that result in property damage,  
personal injury, fire, explosion and/or  
toxic gases. A faulty ignition module must  
be replaced with a new module.  
(b) Shut off water supply.  
(c) Shut off electrical supply.  
(d) Drain the unit completely. Remove one threaded  
plug or bulbwell from the inlet side of the front  
header and one from the outlet side of the front  
header on the heat exchanger. Blow all water out of  
the heat exchanger.  
Ignition and Control Timings  
M9 Intermittent Spark Ignition Pilot Models  
Pilot Trial for Ignition Period - 90 Seconds  
Pilot Failure Response Time - 0.8 Seconds at less than 1.0 µA  
flame current  
(e) Drain pump and piping.  
Freeze Protection for a Heating Boiler  
System (if required)  
Pump Delay Timing (Optional on Boilers) - 30 Seconds after  
burner shutdown  
1. Use only properly diluted inhibited glycol antifreeze  
designed for hydronic systems. Inhibited propylene glycol  
is recommended for systems where incidental contact with  
drinking water is possible.  
Freeze Protection  
1. For boilers with the pump delay option, if either the inlet  
sensor or the optional multi-purpose temperature  
sensor reads below 40°F, the pump relay will turn ON.  
When the temperature rises above 50°F the pump relay  
will turn OFF.  
DO NOT use undiluted or automotive type  
ƽ CAUTION  
antifreeze.  
2. A solution of 50% propylene glycol will provide maximum  
protection of approximately -30°F.  
2. Location - Heating boilers must be located in a room  
having a temperature safely above freezing [32°F(0°C)].  
3. Follow the instructions from the glycol antifreeze  
manufacturer. The quantity of glycol antifreeze required is  
based on total system volume including expansion tank  
volume.  
3. Caution - A room where the appliance is installed and  
operating under a negative pressure may experience a  
downdraft in the flue of an appliance which is not firing.  
The cold outside air pulled down the flue may freeze a  
heat exchanger. This condition must be corrected to  
provide adequate freeze protection.  
4. Glycol is more dense than water and changes the viscosity  
of the system. The addition of glycol will decrease heat  
transfer and increase frictional loss in the heating boiler  
and related piping. A larger pump with more capacity may  
be required to maintain desired flow rates in a glycol  
system.  
4. Freeze protection for a heating boiler or hot water supply  
boiler using an indirect coil can be provided by using  
hydronic system antifreeze. Follow the manufacturers  
instructions. DO NOT use undiluted or automotive type  
antifreeze.  
5. Local codes may require a back flow preventer or actual  
disconnect from city water supply when glycol antifreeze is  
added to the system.  
5. A snow screen should be installed to prevent snow and  
ice accumulation around the appliance venting system in  
cold climates.  
Water Treatment  
In hard water areas, water treatment should be used to reduce  
the introduction of minerals to the system. Minerals in the  
water can collect in the heat exchanger tubes and cause noise on  
operation. Excessive build up of minerals in the heat exchanger  
can cause a non-warrantable failure.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
7 Maintenance  
Maintenance and annual startup  
Table 7A_Service and Maintenance Schedules  
Service technician  
Owner maintenance  
(see the User’s Information Manual for instructions)  
(see the following pages for instructions)  
• Check appliance area  
General:  
• Address reported problems  
• Check pressure/temperature  
gauge  
• Inspect interior; clean and vacuum if  
necessary;  
Daily  
• Check for leaks (water, gas, flue)  
• Examine venting system  
• Check system water pressure/system  
piping/expansion tank  
• Check control settings  
• Check wiring and connections  
• Flame inspection (stable, uniform)  
• Check flue gas passageways  
• Inspect and clean the burners  
• Check vent piping  
Monthly  
• Check relief valve  
• Perform  
start-up  
checkout  
and  
performance verification per Section 6 -  
Start-up.  
If combustion or performance  
indicate need:  
Test low water cutoff (if used)  
Periodically  
• Reset button (low water cutoff)  
• Clean heat exchanger  
• Remove and wash burners  
• Check appliance piping (gas and  
Every  
6 months  
water) for leaks  
• Operate relief valve  
Shut appliance down (unless  
boiler used for domestic hot  
water)  
End  
of season  
months  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
7 Maintenance  
(continued)  
Follow the service and maintenance procedures given throughout this manual and in component literature  
shipped with the appliance. Failure to perform the service and maintenance could result in damage to the  
appliance or system. Failure to follow the directions in this manual and component literature could result in  
severe personal injury, death, or substantial property damage.  
ƽ WARNING  
The appliance should be inspected annually only by a qualified service technician. In addition, the  
maintenance and care of the appliance designated in Table 7A and explained on the following pages must be  
performed to assure maximum appliance efficiency and reliability. Failure to service and maintain the  
appliance and system could result in equipment failure.  
ƽ WARNING  
Electrical shock hazard – Turn off power to the appliance before any service operation on the appliance except  
as noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical  
shock, causing severe personal injury or death.  
ƽ WARNING  
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and  
dangerous operation.  
ƽ CAUTION  
Address reported problems  
Flue vent system and air supply  
1. Inspect any problems reported by the owner and correct  
before proceeding.  
1. Examine the venting system at least once a year. Check  
more often in the first year to determine inspection interval.  
Check all joints and pipe connections for tightness,  
corrosion or deterioration. Clean louvers and/or screens in  
the combustion air intake system as required. Have the  
entire system, including the venting system, periodically  
inspected by a qualified service agency.  
Inspect appliance area  
1. Verify that appliance area is free of any combustible  
materials, gasoline and other flammable vapors and  
liquids.  
2. Check for gastight seal at every connection, seam of air  
piping, and vent piping periodically inspected by a qualified  
service agency.  
Inspect appliance interior  
1. Remove the outer access panels and inspect the interior of  
the appliance.  
Venting system must be sealed gastight to  
ƽ WARNING  
prevent flue gas spillage and carbon  
monoxide emissions, which will result in  
severe personal injury or death.  
2. Vacuum any sediment from inside the appliance and  
components. Remove any obstructions.  
Check all piping for leaks  
Listed below are items that must be checked to ensure safe  
reliable operation. Verify proper operation after servicing.  
Check water system  
1. Verify all system components are correctly installed and  
operational.  
2. Check the cold fill pressure for the system. Verify it is  
correct (must be a minimum of 12 PSI).  
Eliminate all system or appliance leaks.  
ƽ WARNING  
Continual fresh makeup water will reduce  
appliance life. Minerals can build up in  
sections, reducing heat transfer,  
overheating heat exchanger, and causing  
heat exchanger failure. Leaking water may  
also cause severe property damage.  
3. Watch the system pressure as the boiler heats up (during  
testing) to ensure pressure does not rise too high. Excessive  
pressure rise indicates expansion tank sizing or performance  
problem.  
4. Inspect automatic air vents and air separators. Remove air  
vent caps and briefly press push valve to flush vent. Replace  
caps. Make sure vents do not leak. Replace any leaking  
vents.  
1. Inspect all water and gas piping and verify to be leak free.  
2. Look for signs of leaking lines and correct any problems  
found.  
3. Check gas line using the procedure found in Section 3 -  
Gas Connections.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
7 Maintenance  
(continued)  
Following installation, the valve lever must  
be operated AT LEAST ONCE A YEAR to  
ensure that waterways are clear. Certain  
naturally occurring mineral deposits may  
adhere to the valve, rendering it inoperative.  
When manually operating the lever, water  
will discharge and precautions must be taken  
to avoid contact with hot water and to avoid  
water damage. Before operating lever, check  
to see that a discharge line is connected to  
this valve directing the flow of hot water  
from the valve to a proper place of disposal.  
Otherwise severe personal injury may result.  
If no water flows, valve is inoperative. Shut  
down the appliance until a new relief valve  
has been installed.  
Check Expansion Tank  
ƽ WARNING  
1. Expansion tanks provide space for water to move in and  
out as the heating system water expands due to  
temperature increase or contracts as the water cools.  
Tanks may be open, closed, diaphragm or bladder type.  
See Section 4 - Water Connections for suggested best  
location of expansion tanks and air eliminators.  
Check Relief Valve  
1. Inspect the relief valve and lift the lever to verify flow.  
Before operating any relief valve, ensure that it is piped  
with its discharge in a safe area to avoid severe scald  
potential. Read Section 4 - Water Connections before  
proceeding further.  
Safety relief valves should be re-inspected  
ƽ WARNING  
2. After following the above warning directions, if the relief  
valve weeps or will not seat properly, replace the relief valve.  
Ensure that the reason for relief valve weeping is the valve  
and not over-pressurization of the system due to expansion  
tank waterlogging or undersizing.  
AT LEAST ONCE EVERY THREE  
YEARS, by a licensed plumbing contractor  
or authorized inspection agency, to ensure  
that the product has not been affected by  
corrosive water conditions and to ensure  
that the valve and discharge line have not  
been altered or tampered with illegally.  
Certain naturally occurring conditions  
may corrode the valve or its components  
over time, rendering the valve inoperative.  
Such conditions are not detectable unless  
the valve and its components are  
physically removed and inspected. This  
inspection must only be conducted by a  
plumbing contractor or authorized  
inspection agency – not by the owner.  
Failure to re-inspect the boiler relief valve  
as directed could result in unsafe pressure  
buildup, which can result in severe  
personal injury, death, or substantial  
property damage.  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
7 Maintenance  
Check All Wiring  
Combustion Air  
This appliance uses an atmospheric combustion process.  
Combustion air is provided to the burners by the gas injection  
pressure into the venturi of the burners. The burners do not  
have an adjustable air shutter. Adequate combustion air must be  
supplied to the room where the appliance is installed to ensure  
proper burner operation. Check frequently to be sure the flow  
of combustion and ventilation air to the unit is not obstructed.  
When the main burners light, observe the burner flame. Flames  
should be light blue in color with slight yellow tips; flames  
should be settled on burner head with no lifting when supplied  
with correct volume of combustion air.  
1. Inspect all wiring, making sure wires are in good  
condition and securely attached.  
Check Control Settings  
1. Adjust settings if necessary. See Section 5 - Electrical  
Connections for adjustment procedures.  
2. Check settings of external limit controls (if any) and  
adjust if necessary.  
Perform Start-up and Checks  
1. Start appliance and perform checks and tests specified in  
Check Flue Gas Passageways  
Section 6 - Start-up.  
Any sign of soot around the outer jacket, at the burners or in the  
areas between the fins on the copper heat exchanger indicates a  
need for cleaning. The following cleaning procedure must only  
be performed by a qualified serviceman or installer. Proper  
service is required to maintain safe operation. Properly installed  
and adjusted appliances seldom need flue cleaning.  
2. Verify cold fill pressure is correct and that operating  
pressure does not go too high.  
Check Burner Flame  
Visually check main burner flames at each start-up after long  
shutdown periods or at least every six months. A burner  
viewport is located on the burner mounting flange.  
All gaskets on disassembled components  
NOTICE  
must be replaced with new gaskets on  
reassembly. Gasket kits are available from  
your distributor.  
The area around the burner viewport is  
hot and direct contact could result in  
burns.  
ƽ WARNING  
Heat Exchanger / Burner Access  
ƽ WARNING: The area around the burners is hot and direct contact could result in burns!  
The combustion chamber insulation in this  
ƽ WARNING  
YELLOW TIP  
NORMAL  
appliance contains ceramic fiber material.  
Ceramic fibers can be converted to  
cristobalite in very high temperature  
applications. The International Agency for  
Research on Cancer (IARC) has concluded,  
“Crystalline Silica in the form of quartz or  
cristobalite from occupational sources is  
carcinogenic to humans (Group 1).” Normal  
operating temperatures in this appliance are  
below the level to convert ceramic fibers to  
cristobalite. Abnormal operating conditions  
would have to be created to convert the  
ceramic fibers in this appliance to  
cristobalite.  
B
A
D
C
YELLOW FLAME  
FLAME LIFT  
Figure 7-1_Flame Pattern Illustration  
Normal Flame: A normal flame is blue, with slight yellow  
tips, with a well defined inner cone and no flame lifting.  
The ceramic fiber material used in this  
appliance is an irritant; when handling or  
replacing the ceramic materials it is  
advisable that the installer follow these safety  
guidelines:  
Ye l l ow Ti p : Yellow tip can be caused by blockage or partial  
obstruction of air flow to the burner(s).  
Yellow Flames: Yellow flames can be caused by blockage of  
primary air flow to the burner(s) or excessive gas input. This  
condition MUST be corrected immediately.  
Lifting Flames: Lifting flames can be caused by over firing the  
burner(s) or excessive primary air.  
If improper flame is observed, examine the venting system,  
ensure proper gas supply and adequate supply of combustion  
and ventilation air.  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
7 Maintenance  
(continued)  
Inspection and Cleaning  
Avoid breathing dust and contact with skin and eyes.  
Use NIOSH certified dust respirator (N95). This type of  
respirator is based on the OSHA requirements for  
cristobalite at the time this document was written.  
Other types of respirators may be needed depending on  
j. Check the heat exchanger surface for sooting. The  
external surfaces of the copper tubes should be free of  
any soot deposits. (A slight black smudge is normal  
with some types of gases.) If abnormal soot deposits  
are present, the heat exchanger must be cleaned and  
the cause of the soot problem corrected. Proceed as  
follows:  
the  
jobsite  
conditions.  
Current  
NIOSH  
recommendations can be found on the NIOSH website at  
(http://www.cdc.gov/niosh/homepage.html). NIOSH  
approved respirators, manufacturers and phone numbers  
are also listed on this website.  
Wear long-sleeved, loose fitting clothing, gloves, and eye  
protection.  
k. Remove soot from burners and bottom of the finned  
tubes with a stiff bristle brush. Dirt may also be  
removed from burner ports by rinsing the burner  
thoroughly with water. Drain and dry burners before  
re-installing. Damaged burners must be replaced.  
Apply enough water to the combustion chamber lining to  
prevent airborne dust.  
Remove combustion chamber lining from the appliance  
and place it in a plastic bag for disposal.  
Wash potentially contaminated clothes separately from  
other clothing. Rinse clothes thoroughly.  
NIOSH stated First Aid:  
An appliance installed in a dust or dirt contaminated  
atmosphere will require cleaning of the burners on a 3 to 6  
month schedule or more often, based on severity of  
contamination. Contaminants can be drawn in with the  
combustion air. Non-combustible particulate matter such as  
dust, dirt, concrete dust or dry wall dust can block burner ports  
and cause non-warrantable failure. Use extreme care when  
operating an appliance for temporary heat during new  
construction. The burners will probably require a thorough  
cleaning before the appliance is placed in service.  
Eye: Irrigate immediately.  
Breathing: Fresh air.  
a. Turn “OFF” main power to the appliance.  
b. Turn “OFF” external manual gas shutoff valve to  
appliance.  
c. Remove the control panel door.  
l. Remove gas manifold as described in steps a. thru e. in  
d. Remove the outer air deflector (FIG. 7-2)  
“Heat Exchanger/Burner Access.”  
e. Disconnect gas valve wiring and remove gas manifold  
assembly.  
m. Loosen mounting screws and remove front control  
panel.  
f. Remove ignition wire leading to the pilot assembly  
from the ignition module.  
n. Loosen screws on the upper front jacket panel and  
remove toward front of the appliance. Use caution to  
prevent damage to refractory on the doors inner  
surface.  
g. Disconnect the wiring from the flame rollout/interlock  
switch, see FIG. 5-8, page 38.  
o. Check “V” baffles on top of the heat exchanger.  
Remove and clean if necessary.  
h. Remove the lower front jacket panel.  
i. Remove the control panel mounting screws. When  
removing the control panel, lay the control panel to  
the side with the wiring intact, being careful not to  
damage any of the wiring.  
p. Remove soot from the heat exchanger with a stiff  
bristle brush. Soot may also be removed from the heat  
exchanger by washing thoroughly with detergent and  
water. Remove the heat exchanger before using water  
for cleaning. Rinse thoroughly and dry before  
re-installing. Use a vacuum to remove loose soot from  
surfaces and inner chamber.  
Remove the combustion chamber door. Use caution  
to prevent damage to burners, refractory, pilot or  
wiring.  
q. Remove the heat exchanger (HEX) filler bracket  
(FIG. 7-2).  
r. The heat exchanger can be removed by sliding towards  
the front of the appliance. Once the heat exchanger is  
removed from the appliance, a garden hose can be used  
to wash the tubes to ensure that all soot is removed  
from the heat exchanger surfaces.  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
7 Maintenance  
s. Ensure that all burner ports are cleaned to remove  
any soot. See Inspection and Cleaning Procedure,  
page 46.  
Inspection of Heat Exchanger Waterways  
Appliances operated in hard water areas should have periodic  
inspections of the tubes to be sure that no sediment or scale  
accumulates on the heat transfer surfaces. Inspection plugs are  
located at both ends of the heat exchanger. Inspection plugs  
should be removed and tubes inspected at the end of the first 45  
days of operation and again at the end of 90 days of operation.  
If no scale accumulation is observed, inspections can be made at  
the end of each six months of operation.  
t. Carefully re-install the heat exchanger, “V” baffles,  
jacket panels, and wires.  
u. Reassemble all gas and water piping. Test for gas  
leaks.  
v. Cycle the appliance and check for proper operation.  
Upon completion of any testing on the  
OUTER AIR  
DEFLECTOR  
IMPORTANT  
gas system, leak test all gas connections  
with a soap solution while main burners  
are operating. Immediately repair any  
leak found in the gas train or related  
UPPER FRONT  
JACKET PANEL  
components.  
Do Not operate an  
appliance with a leak in the gas train,  
valves or related piping.  
FLAME ROLL-OUT SWITCH /  
INTERLOCK SWITCH  
DETAIL A  
LOWER FRONT  
Gas Train and Controls  
JACKET PANEL  
HEX FILLER BRACKET  
Figure 7-2_Outer Air Deflector and HEX Filler Bracket  
GAS FLOW  
Water Circulating Pump  
Inspect pump every 6 months and oil if required. Use SAE 30  
non-detergent oil or lubricant specified by pump  
manufacturer.  
Figure 7-4_Gas Train  
Clear Area  
Review with owner  
1. Keep appliance area clear and free from combustible  
materials, gasoline and other flammable vapors and  
liquids.  
1. Review the User’s Information Manual with the owner.  
2. Emphasize the need to perform the maintenance schedule  
specified in the User’s Information Manual (and in this  
manual as well).  
2. Check frequently to be sure the flow of combustion and  
ventilation air to the boiler is not obstructed.  
3. Remind the owner of the need to call a licensed contractor  
should the appliance or system exhibit any unusual  
behavior.  
4. Remind the owner to follow the proper shutdown  
procedure and to schedule an annual start-up at the  
beginning of the next heating season.  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
8 Troubleshooting  
Troubleshooting Guide: M9 Solution Boilers  
Check continuity on the spark  
Check for an open  
sensor. If no open  
sensor, make sure  
there’s a call for  
Step 1:  
Is the spark  
ignitor sparking?  
cable. Check for 24 VAC on  
the 24v terminal (gray wire)  
on the ignition module.  
No  
heat. If call for heat  
is present, replace  
temperature control.  
Yes  
No  
Yes  
Check the pilot  
tube for gas.  
Check draft.  
Is the pilot  
staying on?  
Step 2:  
No  
Replace ignition  
module.  
No  
Is there 24 VAC (purple  
wire) on the 4-pin  
connector plug on the  
temperature controller?  
Yes  
Is there 24 VAC (tan  
wire) on the 4-pin  
connector plug on  
the temperature  
controller?  
Is the gas valve  
getting 24 VAC  
to the MV  
Replace the  
ignition  
module.  
Step 3:  
No  
Yes  
terminal?  
Check gas pressure  
and make sure gas  
valve knob is on.  
Yes  
No  
Yes  
Check 24 VAC at R and W on  
the terminal strip.  
Check each of the  
following for an open:  
- X and B on the  
terminal strip  
-purple and gray wires  
on the vent damper  
plug  
-V and P on the  
terminal strip  
-auto reset high limit  
No  
Yes  
Check  
voltage to  
and from the  
transformer.  
Check each of the  
following for an open:  
-white and purple wire on  
the LWCO plug  
No  
-rollout switch  
-manual reset high limit  
-spill switch  
If any of these devices are  
open, press the reset  
button.  
Check incoming  
120 VAC.  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Service Manual  
9 Diagrams  
Schematic Diagram - M9 Unit  
45,000 - 260,000 Btu/hr Models  
Wiring Diagram - M9 Unit  
45,000 - 260,000 Btu/hr Models  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Revision A (ECO #C03746) initial release.  
SBR-I-S Rev A  
5/10  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Krups Hot Beverage Maker BW3990 User Manual
KWC Plumbing Product 10151991 User Manual
Lenoxx Electronics Heat Pump XP14 User Manual
Linear Home Security System CCM 2 User Manual
LST Smoke Alarm 200 Series User Manual
Magic Chef Beverage Dispenser MCBC580DBT User Manual
McCulloch Trimmer M B325 CB User Manual
Melissa Kitchen Utensil 646 040 User Manual
Memorex CD Player MD6440cp User Manual
Memorex Cordless Telephone MPH7828 User Manual