| 	
		 POWER AVAILABILITY   
					USER MANUAL   
					UPStation GXT 2U™   
					500-3000VA   
					120V   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				TABLE OF CONTENTS   
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					5.9   
					
					
					
					
					
					
					
					
					
					
					i 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				TABLES   
					Table 1   
					
					
					
					ii   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				IMPORTANT SAFETY INSTRUCTIONS   
					WARNING   
					! 
					Opening or removing the cover may expose you to lethal   
					voltages within this unit even when it is apparently not   
					operating and the input wiring is disconnected from the   
					electrical source. Observe all cautions and warnings in this   
					manual. Failure to do so MAY result in serious injury or   
					death. Refer all UPS and battery service to qualified service   
					personnel. Do not attempt to service this product yourself.   
					Never work alone.   
					SAVE THESE INSTRUCTIONS   
					This manual contains important safety instructions. Read all safety,   
					installation, and operating instructions before operating the Uninter-   
					ruptible Power System (UPS). Adhere to all warnings on the unit and   
					in this manual. Follow all operating and user instructions. Individuals   
					without previous training can install and operate this equipment.   
					It is not intended for use with life support and other designated “criti-   
					cal” devices. Maximum load must not exceed that shown on the UPS   
					rating label. The UPS is designed for data processing equipment. If   
					uncertain, consult your local dealer or Liebert representative.   
					This UPS is designed for use on a properly grounded (earthed), 50Hz   
					or 60Hz, 120V supply (programmable for 100, 110, 115, 120 and   
					127VAC output). Installation instructions and warning notices are   
					located in this manual.   
					ELECTROMAGNETIC COMPATIBILITY—The GXT 2U™ Series   
					complies with the limits for a CLASS A DIGITAL DEVICE, PURSU-   
					ANT TO Part 15 of FCC rules. Operation is subject to the following   
					two conditions: (1) This device may not cause harmful interference,   
					and (2) this device must accept any interference received, including   
					interference that may cause undesired operation. Operating this   
					device in a residential area is likely to cause harmful interference that   
					users must correct at their own expense.   
					Operate the UPS in an indoor environment only in an ambient tem-   
					perature range of 32°F to +104°F (0°C to +40°C). Install it in a clean   
					environment, free from moisture, flammable liquids, gases and corro-   
					sive substances.   
					1 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				This UPS contains no user serviceable parts except the internal bat-   
					tery pack. The UPS ON/Standby push buttons do not electrically iso-   
					late internal parts. Under no circumstances attempt to gain access   
					internally other than to replace the batteries due to risk of electric   
					shock or burn. Do not continue to use the UPS if the front panel indi-   
					cations are not in accordance with these operating instructions or if   
					the UPS performance alters in use. Refer all faults to your local   
					dealer, Liebert representative or the Liebert Worldwide Support   
					Group.   
					Servicing of batteries should be performed or supervised by personnel   
					knowledgeable of batteries and the required precautions. Keep unau-   
					thorized personnel away from the batteries. PROPER DISPOSAL OF   
					BATTERIES IS REQUIRED. REFER TO YOUR LOCAL LAWS AND   
					REGULATIONS FOR BATTERY DISPOSAL REQUIREMENTS.   
					Never block or insert any object into the ventilation holes or other   
					openings of the UPS.   
					DO NOT CONNECT equipment that could overload the UPS or   
					demand half-wave rectification from the UPS, for example: electric   
					drills, vacuum cleaners, laser printers or hairdryers.   
					Storing magnetic media on top of the UPS may result in data loss or   
					corruption.   
					Turn the UPS off and isolate the UPS before cleaning; use only a soft   
					cloth, never liquid or aerosol cleaners. Keep the front and rear vents   
					free of dust accumulation that could restrict airflow.   
					When replacing batteries, replace with the same Liebert authorized   
					replacement battery kits.   
					CAUTION   
					! 
					Do not dispose of battery or batteries in a fire. The battery   
					may explode.   
					Do not open or mutilate the battery or batteries. Released   
					electrolyte is harmful to skin and eyes. It may be toxic.   
					CAUTION   
					! 
					A battery can present a risk of electrical shock and high short   
					circuit current. The following precautions should be observed   
					when working on batteries:   
					• Remove watches, rings, and other metal objects.   
					• Use tools with insulated handles.   
					2 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Glossary of Symbols   
					1.0 GLOSSARY OF SYMBOLS   
					Risk of electrical shock   
					Indicates caution followed by important instructions   
					AC input   
					AC output   
					Requests the user to consult the manual   
					i 
					Indicates the unit contains a valve-regulated lead acid   
					battery   
					Recycle   
					DC voltage   
					Equipment grounding conductor   
					Bonded to ground   
					AC voltage   
					ON   
					Standby   
					3 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Introduction   
					2.0 INTRODUCTION   
					Congratulations on your choice of the Liebert UPStation GXT 2U™   
					Uninterruptible Power System (UPS). It provides conditioned power   
					to microcomputers and other sensitive electronic equipment.   
					Upon generation, AC power is clean and stable. However, during   
					transmission and distribution it may be subject to voltage sags,   
					spikes, or complete power failure that may interrupt computer opera-   
					tions, cause data loss, or even damage equipment. The UPStation   
					GXT 2U protects equipment from these disturbances.   
					The UPStation GXT 2U comes in nominal power ratings of 500, 700,   
					1000, 1500, 2000 and 3000 VA. Complete model specifications appear   
					at the end of this manual.   
					The UPStation GXT 2U is a compact, “on-line” UPS. An on-line UPS   
					continuously conditions and regulates its output voltage, whether util-   
					ity power is present or not. It supplies connected equipment with   
					clean sinewave power. Sensitive electronic equipment operates best   
					from sinewave power.   
					For ease of use, the UPStation GXT 2U features a light-emitting diode   
					(LED) display to indicate either load percentage or battery capacity   
					depending upon the mode of operation. It also provides self-diagnostic   
					tests, a combination ON/Alarm Silence/Manual Battery Test button, a   
					Standby button, user configurable program, and two levels of alarms   
					when the unit is operating on battery.   
					The UPStation GXT 2U has an interface port for communication   
					between the UPS and a network server or other computer systems.   
					This port provides detailed operating information including voltages,   
					currents, and alarm status to the host system when used in conjunc-   
					tion with Liebert MultiLink™ software. MultiLink software can also   
					remotely control UPS operation.   
					4 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Major Components   
					3.0 MAJOR COMPONENTS   
					Input   
					Output   
					Dynamic   
					Bypass   
					TVSS &   
					EMI/RFI   
					Filters   
					Rectifier   
					/PFC   
					Inverter   
					L1   
					L1   
					DC to DC   
					Converter   
					Battery   
					Charger   
					Battery   
					L2   
					G 
					L2   
					G 
					3.1   
					TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS)   
					AND EMI/RFI FILTERS   
					These UPS components provide surge protection and filter both elec-   
					tromagnetic interference (EMI) and radio frequency interference   
					(RFI). They minimize any surges or interference present in the utility   
					line and keep the sensitive equipment protected.   
					3.2   
					RECTIFIER/POWER FACTOR CORRECTION (PFC) CIRCUIT   
					In normal operation, the rectifier/power factor correction (PFC) circuit   
					converts utility AC power to regulated DC power for use by the   
					inverter while ensuring that the waveshape of the input current used   
					by the UPS is near ideal. Extracting this sinewave input current   
					achieves two objectives:   
					• The utility power is used as efficiently as possible by the UPS.   
					• The amount of distortion reflected on the utility is reduced.   
					This results in cleaner power being available to other devices in the   
					building not being protected by the UPStation GXT 2U.   
					3.3   
					INVERTER   
					In normal operation, the inverter utilizes the DC output of the power   
					factor correction circuit and inverts it into precise, regulated sinewave   
					AC power. Upon a utility power failure, the inverter receives its   
					required energy from the battery through the DC to DC converter. In   
					both modes of operation, the UPS inverter is on-line and continuously   
					generating clean, precise, regulated AC output power.   
					5 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
					 
					 
					 
				Major Components   
					3.4   
					BATTERY CHARGER   
					The battery charger utilizes energy from the utility power and pre-   
					cisely regulates it to continuously “float charge” the batteries. The bat-   
					teries are being charged whenever the UPStation GXT 2U is plugged   
					in, even when the UPS is not turned on.   
					3.5   
					DC TO DC CONVERTER   
					The DC to DC converter utilizes energy from the battery system and   
					raises the DC voltage to the optimum operating voltage for the   
					inverter. This allows the inverter to operate continuously at its opti-   
					mum efficiency and voltage, thus increasing reliability.   
					3.6   
					BATTERY   
					The UPStation GXT 2U utilizes valve-regulated, nonspillable, flame   
					retardant, lead acid batteries. To maintain battery design life, operate   
					the UPS in an ambient temperature of 68°F to 77°F (20°C to 25°C).   
					Optional external battery cabinets are available to extend battery run   
					times.   
					3.7   
					DYNAMIC BYPASS   
					The UPStation GXT 2U provides an alternate path for utility power to   
					the connected load in the unlikely event of a UPS malfunction. Should   
					the UPS have an overload, overtemperature, or UPS failure condition,   
					the UPS automatically transfers the connected load to bypass. Bypass   
					operation is indicated by an audible alarm and illuminated amber   
					Bypass LED (other LEDs may be illuminated to indicate the diag-   
					nosed problem). To manually transfer the connected load from the   
					inverter to bypass, press the Standby button once.   
					NOTE   
					The bypass power path does NOT protect the connected   
					equipment from disturbances on the utility supply.   
					6 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
					 
					 
					 
				Installation   
					4.0 INSTALLATION   
					4.1   
					PREPARATION   
					1. Visually inspect the UPS for freight damage. Report damage to   
					the carrier and your local dealer or Liebert representative.   
					CAUTION   
					! 
					
					precautions when lifting or moving it.   
					2. Decide where to place the GXT 2U. Install the UPS indoors in a   
					controlled environment, where it cannot be accidentally turned off.   
					Place it in an area of unrestricted airflow around the unit, away   
					from water, flammable liquids, gases, corrosives, and conductive   
					contaminants. Maintain a minimum clearance of 4 in. (100mm) in   
					the front and rear of the UPS. Maintain an ambient temperature   
					range of 32°F to 104°F (0°C to 40°C).   
					NOTE   
					UPS operation in temperatures above 77°F (25°C) reduces   
					battery life.   
					3. The GXT 2U may be installed in either a tower configuration or in   
					a rack, depending on available space and use considerations.   
					Determine the type of installation and follow the appropriate   
					
					
					4.2   
					TOWER UPS INSTALLATION   
					When using the GXT 2U in a tower configuration, use the included   
					support base (shown below, left) to stabilize the UPS.   
					If any battery cabinets are added, they will include spacers to accom-   
					modate the additional cabinets (shown below, right).   
					Support base   
					Spacers added to support   
					base to accommodate   
					additional battery cabinets   
					8 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
					 
					 
				Installation   
					4.3   
					RACK-MOUNT UPS CONVERSION AND INSTALLATION   
					NOTE   
					When rack mounted, the UPS must be supported by a shelf,   
					brackets or slide rails on each side. The rack mount handles   
					WILL NOT support the weight of the UPS. They are used to   
					move the UPS into and out of the rack.   
					1. For slide rail installations, first remove the top/side fin. Slide the   
					top/side fin forward, then lift it up to remove. If desired, install the   
					optional rack mount handles that were shipped with the UPS.   
					UPStation GXT   
					– 
					+ 
					AC INPUT   
					BATTERY   
					UPS   
					ON   
					BYPASS   
					Optional rack mount handles   
					Securing hardware and slide rails are sold separately. Contact   
					your local dealer or Liebert representative for these additional   
					options and any assistance needed.   
					2. Unpack the two (2) rack-   
					Return   
					mounting bracket assemblies   
					and mounting hardware   
					from the rack-mounting kit   
					(P/N: RMKIT18-32). Bracket   
					assemblies are   
					flanges   
					Retaining   
					latches   
					interchangeable between   
					left-hand or right-hand.   
					Remove inner member of   
					each bracket assembly as   
					shown at right by extending   
					it to its outermost position,   
					depressing the retaining   
					latch and then pulling inner   
					member from bracket   
					Rear   
					members   
					Front   
					members   
					Inner   
					members   
					assembly.   
					9 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Installation   
					3. Determine the height position inside the rack enclosure where you   
					want to mount the UPS or battery cabinet.   
					CAUTION   
					! 
					Reduce risk of tipping the rack enclosure by placing UPS or   
					battery cabinet in the lowest possible rack position.   
					Install rear member of each   
					M5 screws   
					bracket assembly into rack   
					enclosure with two (2) M5   
					screws provided in this kit.   
					(See figure at right.) Return   
					flanges on bracket assembly   
					fit to the inside of rack   
					Front rack   
					mounting rails   
					mounting rails. Insert screws   
					loosely (finger-tight) into top   
					and bottom holes of return   
					flange on rear member.   
					Extend bracket assembly by   
					sliding front member for-   
					Rear rack   
					mounting   
					rails   
					M5 screws   
					ward until it touches the front rack mounting rail. Insert two (2) M5   
					screws loosely (finger-tight) into top and bottom holes of return   
					flange on each front member. Make sure bracket assemblies are at   
					the same mounting height on all four (4) rack mounting rails.   
					4. Locate eight (8) M4 screws   
					and eight (8) M4 nuts from   
					hardware pack in this kit.   
					Each nut has a locking, nylon   
					insert that begins gripping   
					the screw when it is halfway   
					tight. Make sure to tighten   
					nut and screw completely to   
					assure locking action. Fasten   
					rear member and front   
					M4 nuts   
					M4   
					screws   
					18" rack   
					depth   
					M4 nuts   
					M4   
					member together using four   
					(4) screws and four (4) nuts   
					per bracket assembly as   
					shown in the figures at right.   
					For maximum support,   
					locate fasteners for each   
					bracket assembly as far   
					M4 nuts   
					screws   
					apart as possible, depending   
					on rack depth, while still   
					joining both members (See   
					32" rack   
					depth   
					M4 nuts   
					figures at right). Check alignment of bracket assemblies and   
					
					10   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Installation   
					5. Prepare the UPS or battery   
					cabinet (the “equipment”) for   
					rack mounting by following   
					instructions in the equipment’s   
					user manual. The equipment   
					may require additional parts to   
					be added or parts to be removed   
					for rack mounting. After it is   
					prepared, lay equipment in   
					rack-mounting position. Fasten   
					inner members from Step 2 to   
					the equipment on both sides as   
					shown in the figure at right   
					with (8) M4 screws provided in   
					this kit. Make sure retaining   
					M4   
					screws   
					Retaining   
					latch   
					UPS or battery   
					cabinet   
					Front   
					M4   
					screws   
					latch is near the rear of the equipment (also shown in figure).   
					6. Open grease packet provided   
					in this kit. Apply a 1" long   
					bead of grease four (4) places   
					inside the bottom, curved   
					tracks of front members as   
					shown at right. The grease   
					will allow the equipment to   
					slide into the bracket   
					Apply grease   
					UPS or   
					battery   
					cabinet   
					Apply   
					grease   
					(inside)   
					assemblies more easily.   
					CAUTION   
					! 
					Lifting equipment into rack may be a two-person job, depending   
					on weight of equipment. See equipment’s user manual.   
					
					into bracket assemblies by inserting top and bottom edges of inner   
					members into the top and bottom, curved tracks of front members   
					and sliding the equipment into rack (see figure in Step 6). Ends of   
					inner members are tapered to allow rear of the equipment to be   
					angled upward before insertion, if space allows.   
					Then the rear, bottom edges of inner   
					members can be placed into front   
					edge of bottom tracks, and the front of   
					the equipment can be tipped up into   
					horizontal position to insert the top   
					edges of inner members before sliding   
					the equipment into rack (see figure at   
					right). The equipment should move smoothly into bracket assem-   
					blies. If not, recheck alignment of front and rear members from   
					
					11   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Installation   
					8. Secure front of the equipment to rack mounting rails to prevent   
					the equipment from sliding out of position. If securing holes are   
					provided on front of the equipment that align with the center holes   
					on return flange of front members, you can use the four (4) extra   
					M5 screws provided in this kit to secure the equipment.   
					Otherwise, the equipment should be secured to front of rack   
					mounting rails with four (4) customer-supplied fasteners.   
					9. To orient the display for   
					Horizontal overlay   
					for rack UPS   
					Vertical   
					overlay   
					for   
					tower   
					UPS   
					horizontal viewing, remove the   
					front plastic bezel by pulling   
					forward evenly on both sides.   
					The unit has two front panel   
					overlays. Remove the outer   
					overlay (used for tower   
					installation). This reveals a   
					horizontally oriented front   
					panel overlay for rack   
					mounting. Snap the front bezel   
					back into place.   
					BPYAS   
					USPON   
					BPYAS   
					+ 
					– 
					BTAERY   
					10. Once the UPS is installed in   
					the rack, the load may be   
					connected. Ensure the load   
					equipment is turned off; plug   
					all loads into the output   
					receptacles on the rear of the   
					UPS.   
					UPSON   
					USPationGXT   
					ACINPUT   
					+ 
					– 
					BTAERY   
					USPationGXT   
					ACINPUT   
					11. Plug the UPS into a dedicated   
					wall receptacle properly   
					protected by a circuit breaker   
					or fuse in accordance with national and local electrical codes. Use   
					a 15 amp rated device for the 500, 700, 1000, or 1500 VA units,   
					20 amp for the 2000 VA, and 30 amp for the 3000 VA. The wall   
					receptacle must be grounded.   
					12. Turn ON the UPS by pressing the ON button; then turn on the   
					connected load equipment. The UPS is now providing conditioned   
					power to your equipment.   
					12   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation   
					4.4   
					EXTERNAL BATTERY CABINET INSTALLATION   
					Optional Liebert external battery cabinets may be connected to the UPS   
					to provide additional battery run time. External battery cabinets are   
					designed to be placed all on one side of the UPS or stacked beneath the   
					UPS. There is no limit to the number of external battery cabinets that   
					can be used but each cabinet will increase the battery recharge time.   
					CAUTION   
					! 
					The external battery cabinet(s) are heavy (see 11.0 -   
					Specifications). External battery cabinets can be used in   
					rack-mount or tower configuration. Take proper precautions   
					when lifting them.   
					1. Visually inspect the external battery cabinet for freight damage.   
					Report damage to the carrier and your local dealer or Liebert   
					representative.   
					2. For slide rail installations, first remove the top/side fin. Top/side   
					fin slides forward and then lift up to remove. Optional rack-mount   
					handles are shipped with the external battery cabinet and may be   
					installed at this time if desired.   
					3. Securing hardware and slide rails are sold separately. Contact   
					your local dealer or Liebert representative for these additional   
					options and any assistance needed. Fasten the slides into position   
					with the screws per the instructions included with the slide rails.   
					4. Use the enclosed support bases for the   
					tower option to prevent tip-over. One   
					additional set of support base extensions   
					ships with each external battery cabinet.   
					5. Connect the supplied external battery   
					cabinet cable to the rear of the external   
					battery cabinet, then to the rear of the   
					UPS.   
					6. Turn ON the battery breaker on the   
					rear of the external battery cabinet.   
					7. The UPS is now equipped with   
					additional backup battery run time.   
					For approximate battery run times,   
					
					NOTE   
					You must use the included Configuration Program to specify   
					the number of external battery cabinets connected to the UPS.   
					
					13   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Controls and Indicators   
					5.0 CONTROLS AND INDICATORS   
					All LEDs illuminated   
					for illustrative purposes only.   
					5.1   
					ON/ALARM SILENCE/MANUAL BATTERY TEST BUTTON   
					This button controls output power to connected load(s) and has   
					three functions:   
					• ON   
					• Alarm Silence   
					• Manual Battery Test   
					ON - Pressing this button will start up the UPS in order to   
					provide conditioned and protected power.   
					Alarm Silence - To silence alarms, press this button for at least   
					one second. After the alarm is silenced, the UPStation GXT 2U   
					will reactivate the alarm system to alert of additional problems.   
					NOTE   
					The LOW BATTERY and BYPASS reminder alarms   
					CANNOT be silenced.   
					Manual Battery Test - To initiate a manual battery test,   
					press the ON button for at least one second while operating   
					from utility power with no alarm conditions present.   
					• If only three of the five Battery LEDs illuminate, allow the   
					UPS to recharge the batteries for 24 hours.   
					• After 24 hours, retest the batteries.   
					• After the batteries have been retested, if only three of the   
					five Battery LEDs illuminate, contact your local dealer, Lie-   
					bert representative or Liebert Worldwide Support Group.   
					14   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
					 
				Controls and Indicators   
					5.2   
					STANDBY/MANUAL BYPASS BUTTON   
					This button controls output power to connected load(s) and has   
					dual functions: Standby and Manual Bypass.   
					CAUTION   
					! 
					While the UPS is in Normal Mode operation, pressing   
					the Standby/ Manual Bypass button once will put the   
					UPS into Bypass Mode.   
					Once the UPS is in Bypass Mode operation, press the   
					Standby/ Manual Bypass button two distinct times (for   
					about one second each time) to turn off the UPS.   
					Perform all necessary shutdown procedures on   
					connected loads before turning off the UPS.   
					5.3   
					LOAD/BATTERY LEVEL INDICATORS (4 GREEN, 1 AMBER)   
					The load/battery level indicators have dual functions. During normal   
					mode operation LED indicators display the approximate electrical   
					load placed upon the UPS; and during battery mode operation LED   
					indicators display approximate battery capacity.   
					The UPStation GXT 2U is equipped with automatic and remote bat-   
					tery test features. The automatic test occurs every 14 days (this option   
					is user configurable) if utility has not been interrupted. Should the   
					battery fail this test, the red Fault indicator LED along with the A and   
					C diagnostic LEDs will illuminate and an alarm will sound (refer to   
					10.0 - Troubleshooting). The remote test feature functions with   
					MultiLink 3 software and can remotely initiate the battery test.   
					5.4   
					FAULT INDICATOR LED (RED)   
					The Fault indicator LED is illuminated if the UPS has detected a   
					problem. Also, one or more of the load/battery level indicators may be   
					
					5.5   
					BYPASS INDICATOR LED (AMBER)   
					The Bypass indicator LED is illuminated when the UPS is operating   
					from bypass power. An alarm will sound indicating the UPS detected   
					a problem, or the manual bypass function has been activated.   
					5.6   
					UPS ON INDICATOR LED (GREEN)   
					The UPS ON indicator LED is illuminated when the UPS inverter is   
					operating and supplying power to your connected loads.   
					5.7   
					BATTERY INDICATOR LED (AMBER)   
					The Battery indicator LED is illuminated when the UPS is operating   
					on battery.   
					15   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
					 
					 
					 
					 
					 
				Controls and Indicators   
					5.8   
					AC INPUT INDICATOR LED (GREEN)   
					The AC Input indicator LED is illuminated when utility power is   
					available and within the input specifications.   
					5.9   
					OUTPUT VOLTAGE SELECTION   
					The Output Voltage is user configurable and is designed to allow   
					selecting or changing the desired output voltage to match the utility   
					via the GXT 2U Configuration Program provided with the UPS. The   
					settings to choose from are 100, 110, 115, 120, and 127 VAC output.   
					The factory default setting is 120 VAC.   
					CAUTION   
					! 
					Never change the voltage settings while the UPS is ON and   
					powering connected loads.   
					NOTE   
					Setting output voltage to 100 VAC will cause the   
					UPS unit to be derated (500/700/1000 VA to 90%,   
					1500/2000/3000 VA to 80% of the VA and Watt   
					
					16   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
					 
				Operating Instructions   
					6.0 OPERATING INSTRUCTIONS   
					6.1   
					NORMAL MODE OPERATION   
					During normal operation,   
					utility power provides energy   
					to the UPS. The filters, power   
					factor correction circuit and   
					the inverter process this   
					power to provide computer   
					grade power to connected   
					loads. The UPS maintains   
					the batteries in a fully   
					AC INPUT BATTERY UPS ON BYPASS   
					Normal Mode Operation at 26-50%   
					charged state.   
					The four green load level LEDs indicate an approximate level of load   
					in 25% increments. If the UPS becomes loaded beyond full rating, the   
					fifth (amber) LED indicator will illuminate and the UPS will sound an   
					audible alarm. The display template indicates the percentage of load   
					(26-50% of load shown in the example above) on the UPS output.   
					6.2   
					BYPASS MODE OPERATION   
					Bypass mode occurs when   
					the OFF button is pressed   
					once while the UPS is in   
					Normal Mode. During bypass   
					operation, utility power   
					provides energy to the UPS.   
					The utility power bypasses   
					the inverter and provides   
					power for the connected load.   
					AC INPUT BATTERY UPS ON BYPASS   
					Bypass Mode Operation at 26-50%   
					The four green load level LEDs indicate an approximate level of load   
					in 25% increments. If the UPS becomes loaded beyond full rating, the   
					fifth (amber) LED indicator will illuminate and the UPS will sound an   
					audible alarm. The display template indicates the percentage of load   
					(26-50% of load shown in the example above) on the UPS output.   
					CAUTION   
					! 
					Turning OFF the UPS while in bypass mode will result in loss   
					of output power.   
					17   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
					 
					 
				Operating Instructions   
					6.3   
					BATTERY MODE OPERATION   
					Battery mode occurs in   
					event of an extreme input   
					voltage condition or com-   
					plete utility failure. The   
					battery system supplies   
					power through the DC to   
					DC converter to the   
					AC INPUT BATTERY UPS ON BYPASS   
					inverter to generate power   
					for the connected load.   
					Battery Mode Operation at 80-61%   
					During battery mode an alarm sounds every 10 seconds. This will   
					change to two beeps every 5 seconds when the battery runs low   
					(approximately 2 minutes remaining, but this is user configurable).   
					The AC Input LED will extinguish, and the Battery LED will illumi-   
					nate to warn that a utility problem has occurred. Each battery level   
					indicator represents a 20% capacity level. As capacity decreases, fewer   
					
					For approximate battery run times, refer to 13.0 - Battery Run   
					Times. The times listed in these tables are approximate based on   
					resistive load and an ambient temperature of 77°F (25°C). To increase   
					this time, turn off non-essential pieces of equipment (such as idle com-   
					puters and monitors) or add the optional external battery cabinet.   
					CAUTION   
					! 
					Turning OFF the UPS while in battery mode will result in loss   
					of output power.   
					If the UPS is manually turned OFF, it must be manually restarted   
					after utility power is restored.   
					If the UPS is turned OFF by a communication signal or because the   
					batteries are depleted, it will operate as selected in the configuration   
					program for Auto-Restart (see 8.1 - GXT 2U Configuration Pro-   
					
					6.4   
					BATTERY RECHARGE MODE   
					Once utility power is restored, the UPS resumes normal operation. At   
					this time, the Battery Charger begins recharging.   
					18   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
					 
				Communications   
					7.0 COMMUNICATIONS   
					7.1   
					COMMUNICATIONS INTERFACE PORT   
					The UPStation GXT 2U UPS has a standard DB-9 serial port female   
					connector located on the rear of the UPS unit. Several signals are pro-   
					vided on this port and are assigned as follows:   
					Pin   
					1 
					Assignment Description   
					Low Battery (open collector)   
					2 
					UPS TxD (typical RS-232 levels)   
					UPS RxD (typical RS-232 levels)   
					Remote Shutdown (5-12VDC, 10-24 mA max); battery operation   
					Common   
					3 
					4 
					5 
					6 
					Remote Shutdown (short to pin 5); all modes of operation   
					Low Battery (open emitter)   
					7 
					8 
					Utility Fail (open emitter)   
					9 
					Utility Fail (open collector)   
					Pin Assignment   
					Collector to Emitter*   
					Open   
					Collector   
					6 
					7 
					8 
					9 
					(+)   
					330 Ohms   
					Open   
					Emitter   
					(-)   
					1 
					2 
					3 
					4 
					5 
					* Maximum voltage and current on pins 1, 7, 8, and 9 is 60VDC; 10.0 mA.   
					19   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
					 
				Communications   
					7.2   
					PINS 4 & 5 - REMOTE SHUTDOWN ON BATTERY   
					1. This pin is functional only when the UPS is in battery mode. If the   
					UPS is being powered by the utility, Pin 4 will ignore any signal   
					on this pin.   
					2. Pin 4 requires a 5-12 VDC signal to shutdown. This normally   
					comes form the serial port using Liebert’s contact closure cable. It   
					cannot be used with just a contact closure unless the relay is used   
					to switch a voltage source. A 5-12 VDC signal for 1.5 seconds or   
					greater is required to signal a shutdown. Signals for less than 1.5   
					seconds will be ignored. After Pin 4 receives a shutdown signal for   
					1.5 seconds, the command cannot be canceled.   
					3. A battery shutdown signal on Pin 4 will NOT cause an immediate   
					shutdown. A shutdown signal will start a 2-minute shutdown   
					timer. The timer cannot be stopped. After 2 minutes, the UPS will   
					shut down.   
					4. If the utility returns during the 2-minute timer countdown, the   
					shutdown timer will continue until the end of 2 minutes and the   
					UPS will turn OFF. The UPS must remain OFF for at least 10   
					seconds even if AC input power returns before the UPS turns   
					OFF. This serves to reset and restart the server.   
					Whether the UPS turns back ON when power is restored depends on   
					the auto-restart setting: enabled or disabled.   
					If the auto-restart is disabled, the UPS will not restart after perform-   
					ing the 2-minute shutdown delay.   
					20   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Communications   
					7.3   
					PINS 5 & 6 - ANY-MODE SHUTDOWN   
					1. Pin 6 of the 9-pin communication connector is used for “Any-Mode   
					Shutdown” of the UPS output. This control input may be used in   
					special applications to disable the UPS output power—both   
					Inverter and Bypass.   
					2. The Options tab allows the behavior of the Any-Mode Shutdown   
					feature to be modified. When the program opens, or the REFRESH   
					button is pressed, the UPS setting is read by the configuration   
					program and displayed.   
					7.3.1 Auto-Enable Output   
					WARNING   
					! 
					Note that when this option is selected and the UPS output is   
					disabled using Pin 6, the UPS output can turn on   
					automatically and without warning if the Pin 6 connection is   
					changed.   
					7.3.2 Pin 6 Logic   
					WARNING   
					! 
					DO NOT CHANGE THIS OPTION from the factory default   
					setting unless you are ready to install a normally-closed   
					connection between Pins 5 & 6. This connection must be   
					maintained to use the UPS or to use the configuration   
					program again, including the ability to change the UPS   
					setting back to the default setting using the configuration   
					program via a serial communication link.   
					If version 1.6 (or later) is used with an earlier GXT 2U model (with an   
					earlier UPS firmware version), the Any-Mode Shutdown features can-   
					not be changed.   
					If the configuration program is used with an earlier UPS model (with   
					an earlier UPS firmware version) that does not support the modifica-   
					tion of these settings, the Options tab will display a reminder of the   
					factory default settings. These cannot be changed.   
					21   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
					 
					 
				Communications   
					7.4   
					UPS INTELLIGENT COMMUNICATIONS   
					® 
					The UPStation GXT 2U is equipped with an Intellislot port to pro-   
					vide advanced communication and monitoring options.   
					Liebert’s MultiLink software continually monitors the UPS and can   
					shut down your computer or server in the event of an extended power   
					failure.   
					MultiLink can also be configured for use without the serial cable when   
					the Intellislot SNMP/Web card is installed in the UPS. Additionally,   
					MultiLink can be configured to coordinate shutdown across the net-   
					work with other computers running MultiLink when you purchase a   
					MultiLink License Kit. For more information about the Intellislot   
					SNMP/Web Card and MultiLink License Kits, visit the Liebert Web   
					
					sentative.   
					Several option cards are available for use in the Intellislot port of the   
					UPStation GXT 2U.   
					• The Intellislot SNMP/Web Card provides SNMP and Web-based   
					monitoring and control of the UPS across the network.   
					• The Intellislot MultiPort 4 Card allows you to install MultiLink   
					software on four computers and coordinate shutdown in the event   
					of a power failure.   
					• The Intellislot Relay Card provides dry contact relay outputs for   
					custom-wired applications and delivers support for built-in shut-   
					down for AS/400 systems.   
					• The Intellislot USB Card provides communication using built-in   
					® 
					® 
					power management software available on Microsoft Windows   
					2000/XP platforms.   
					CAUTION   
					! 
					To maintain safety (SELV) barriers and for electromagnetic   
					compatibility, signal cables should be segregated and run   
					separate from all other power cables, where applicable.   
					22   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Configuration Program   
					8.0 CONFIGURATION PROGRAM   
					The configuration program included with the UPStation GXT 2U line   
					allows modification of several UPS settings that were previously   
					unavailable or required custom manufacturing. The user manual on   
					the configuration program disk describes the features available for   
					modification, as well as default settings.   
					NOTE   
					The UPS must be turned off—and not powering connected equip-   
					ment—before you make any changes to configuration settings.   
					While the UPS is in Normal Mode operation, press the OFF   
					button once to put the UPS into Bypass Mode.   
					Once the UPS is in Bypass Mode operation, press and release   
					the OFF button two distinct times (for about a second each   
					time) to turn off the UPS.   
					8.1   
					GXT 2U CONFIGURATION PROGRAM ABILITIES   
					• Select one of five output voltages to match voltages found around   
					the world.   
					• Enable/Disable Auto-Restart.   
					• Select frequency converter operation with a fixed output frequency   
					of 50 or 60 Hz.   
					• Set the Low Battery Warning alarm time from 2 to 30 minutes.   
					• Enable/Disable the Auto-Battery test.   
					• Set the Auto-Battery test to 7, 14, 21, or 28 days.   
					• Select the number of external battery cabinets connected to the   
					UPS to adjust the remaining run time calculations reported by   
					Liebert software products.   
					• Modify the shutdown setting of DB-9 pin 6 (for information on pin   
					
					NOTE   
					This program is compatible with UPS models beginning with   
					“GXT2-”, as in “GXT2-1500RT120.” It is not compatible with   
					earlier versions of UPStation GXT UPS.   
					8.1.1 What You Will Need   
					Using this program requires a   
					computer running Windows   
					(95 through Server 2003), as well as the configuration program disk   
					and serial cable included in the UPS accessory box. Use the serial cable   
					(beige or tan, 3-wire: GND, TX, RX; straight through 2-2, 3-3, 5-5) to   
					connect the computer to the GXT 2U UPS.   
					Note: The black ML9P9S contact closure communication cable is NOT   
					compatible with the configuration program.   
					23   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
					 
					 
				Maintenance   
					9.0 MAINTENANCE   
					The UPStation GXT 2U requires very little maintenance. The batter-   
					ies are valve-regulated, nonspillable, flame retardant, lead acid, and   
					should be kept charged to obtain their designed life. The UPS continu-   
					ously charges the batteries when connected to the utility supply.   
					When storing the UPS for any length of time, it is recommended to   
					plug the UPS in for at least 24 hours every four to six months to   
					ensure full recharge of the batteries.   
					The UPStation GXT 2U is designed to allow the user to safely replace   
					the internal batteries. Read the safety cautions before proceeding.   
					Contact your local dealer or Liebert representative to obtain the   
					appropriate replacement battery kit part number and pricing.   
					9.1   
					BATTERY REPLACEMENT   
					CAUTION   
					! 
					A battery can present a risk of electrical shock and high short   
					circuit current. The following precautions should be observed   
					before replacing the batteries:   
					• Remove rings, watches, or other metal objects.   
					• Use a Phillips (crosshead) screwdriver with insulated grips.   
					• Do not lay tools or other metal objects on top of the batter-   
					ies.   
					• If the battery replacement kit is damaged in any way or   
					shows signs of leakage, contact your local dealer or Liebert   
					representative immediately.   
					• Do not dispose of batteries in a fire. The batteries may   
					explode.   
					24   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
					 
				Maintenance   
					9.1.1 Internal Battery Replacement Procedures   
					1. Gently remove the front plastic bezel cover from the UPS.   
					2. Loosen and remove the four screws on the front battery door. Lay   
					the battery door aside for reassembly.   
					Note: The 3000VA model includes a pull handle to remove this   
					door. It has two built-in connectors that disconnect when servicing   
					the battery. THIS HANDLE MUST BE REINSTALLED IN   
					ORDER FOR THE UPS TO OPERATE IN BATTERY MODE.   
					3. Gently pull battery wiring out and disconnect the two slotted   
					battery connectors.   
					4. Grasp the battery pack assembly, and pull it out of the front of the   
					UPS.   
					5. Unpack the new battery assembly taking care not to destroy the   
					packing. Compare new and old battery assemblies to make sure   
					they are the same. If so, proceed with Step 6; otherwise STOP and   
					contact your local dealer, Liebert representative, or the Liebert   
					Worldwide Support Group.   
					6. Line up and slide in the new replacement battery pack.   
					7. Reconnect the two slotted battery connectors and gently push the   
					battery wiring and battery pack assembly back into the UPS.   
					8. Reattach the front battery door with the four screws.   
					9. Reattach the front plastic bezel cover to the UPS.   
					NOTE   
					These are hot-swappable replacement batteries. However,   
					caution should be exercised because during this procedure the   
					load is unprotected from disturbances and power outages.   
					25   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Maintenance   
					9.2   
					FUSE REPLACEMENT   
					CAUTION   
					! 
					Before changing the input fuse, turn off the UPS, and unplug   
					the supply lead from the AC input supply. Replace the fuse   
					with the same type and rating.   
					1. Remove the input fuse.   
					2. Locate the spare input fuse   
					that is included with the   
					UPS.   
					3. Insert the spare fuse into the   
					fuse holder, and reinstall   
					assembly into the UPS.   
					Twist by hand; rotate   
					clockwise until fuse holder   
					locks into position.   
					4. Reconnect the input power   
					cord to input AC supply.   
					5. Restart the UPS. The UPS is ready for normal operation.   
					26   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Troubleshooting   
					10.0 TROUBLESHOOTING   
					The information below indicates various symptoms a user may   
					encounter in the event the UPStation GXT 2U develops a problem.   
					Use this information to determine whether external factors caused the   
					problem and how to remedy the situation.   
					1. The Fault indicator will illuminate, indicating the UPS detected a   
					problem.   
					2. An alarm will sound, alerting that the UPS requires attention.   
					3. One or more additional load/battery level LED indicators will be illu-   
					minated to provide a diagnostic aid to the operator, as described below:   
					This example shows the UPS   
					Fault   
					on bypass due to output overload.   
					E 
					BYPASS   
					D 
					UPS ON   
					C 
					B 
					BATTERY   
					A 
					AC   
					INPUT   
					A 
					B 
					C 
					D 
					E 
					Fault   
					AC INPUT BATTERY UPS ON BYPASS   
					LOAD/BATTERY   
					LEVEL INDICATORS   
					LED status   
					All LEDs   
					A LED   
					Diagnosis / Audible alarm   
					On bypass due to output overload; beep every half-second   
					On bypass due to overtemperature condition; beep every 4 sec.   
					On bypass due to DC bus overvoltage; beep every 4 sec.   
					On bypass due to control power supply failure; beep every 4 sec.   
					On bypass due to PFC failure; beep every 4 sec.   
					B LED   
					C LED   
					D LED   
					E LED   
					On bypass due to inverter failure; beep every 4 sec.   
					A&C LEDs UPS failed battery test; long beep every minute   
					UPS shutdown due to command from communication port   
					(SNMP); no beep   
					C&E LEDs   
					Battery LED Internal Battery source not available (continuous horn). Check   
					Flashing   
					battery connection, completely power down and reboot UPS.   
					AC LED   
					Flashing   
					Line-to-neutral reversal in the AC input power supply or a loss of   
					proper grounding; continuous horn and UPS will not start.   
					Bypass LED Utility power voltage or frequency is out of tolerance; bypass is   
					Flashing unavailable.   
					27   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Troubleshooting   
					Under fault conditions, the Fault indicators will be illuminated indefi-   
					nitely while battery charger is operational, or for a maximum of 5 min-   
					utes while battery charger is not operational.   
					If a problem persists, consult your local dealer, Liebert representative   
					or contact the Liebert Worldwide Support Group. Please have the UPS   
					model number and serial number available at the time of your   
					inquiry.   
					Table 1   
					Troubleshooting guide   
					Problem   
					Cause   
					Solution   
					Ensure UPS is OFF.   
					Disconnect all loads and   
					ensure nothing is lodged in   
					output receptacles. Ensure   
					loads are not defective or   
					shorted internally.   
					UPS fails to start   
					when the ON   
					button is pressed.   
					UPS is short circuited or   
					overloaded.   
					UPS is operating from   
					battery mode, make certain   
					UPS is securely plugged   
					into the wall receptacle.   
					UPS not plugged in.   
					UPS is operating from   
					battery mode. Save data   
					and close applications.   
					Replace UPS input fuse,   
					then restart UPS.   
					UPS input protection fuse   
					has blown/opened.   
					Battery indicator   
					LED is   
					illuminated.   
					UPS is operating from   
					battery mode. Save data   
					and close applications.   
					Ensure utility supply   
					voltage is within   
					Utility voltage out of UPS   
					input range.   
					acceptable limits for UPS.   
					Keep UPS plugged in   
					continuously at least 24   
					hours to recharge   
					batteries.   
					Batteries are not fully   
					charged.   
					Check load level display   
					and reduce the load on the   
					UPS.   
					UPS is overloaded.   
					UPS has reduced   
					battery time.   
					Replace batteries. Contact   
					your local dealer, Liebert   
					representative or the   
					Liebert Worldwide Support   
					Group for replacement   
					battery kit.   
					Batteries may not be able   
					to hold a full charge due to   
					age.   
					28   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Troubleshooting   
					Table 1   
					Troubleshooting guide (continued)   
					Problem   
					Cause   
					Solution   
					Check load level display   
					and remove non-essential   
					loads. Recalculate the load   
					and reduce number of   
					loads connected to UPS.   
					Check load equipment for   
					faults.   
					Fault and Bypass   
					indicator LEDs   
					and all load level   
					LEDs are   
					UPS overloaded or load   
					equipment is faulty.   
					illuminated.   
					Ensure UPS is not   
					overloaded, ventilation   
					openings not blocked, or   
					room ambient temperature   
					is not excessive. Wait 30   
					minutes to allow UPS to   
					cool, then restart UPS. If   
					UPS does not restart,   
					contact your local dealer,   
					Liebert representative or   
					the Liebert Worldwide   
					Support Group.   
					Fault and Bypass   
					indicator LEDs   
					and diagnostic   
					LED A are   
					UPS internal fan has a   
					problem or UPS shutdown   
					due to temperature   
					condition. Load is on   
					bypass power.   
					illuminated.   
					Fault and Bypass   
					indicator LEDs   
					and diagnostic   
					LED B are   
					UPS requires service.   
					Contact your local dealer,   
					Liebert representative or   
					the Liebert Worldwide   
					Support Group.   
					UPS internal DC bus   
					overvoltage.   
					illuminated.   
					Fault and Bypass   
					indicator LEDs   
					and diagnostic   
					LED C are   
					UPS requires service.   
					Contact your local dealer,   
					Liebert representative or   
					the Liebert Worldwide   
					Support Group.   
					UPS control power supply   
					fault.   
					illuminated.   
					Fault and Bypass   
					indicator LEDs   
					and diagnostic   
					LED D are   
					UPS requires service.   
					Contact your local dealer,   
					Liebert representative or   
					the Liebert Worldwide   
					Support Group.   
					UPS PFC (Power Factor   
					Correction Circuit) fault.   
					illuminated.   
					Fault and Bypass   
					indicator LEDs   
					and diagnostic   
					LED E are   
					UPS requires service.   
					Contact your local dealer,   
					Liebert Representative or   
					the Liebert Worldwide   
					Support Group.   
					UPS inverter fault.   
					illuminated.   
					Fault indicator   
					LED and   
					diagnostic LED A   
					and C are   
					Replace batteries. Contact   
					your local dealer, Liebert   
					representative or the   
					Liebert Worldwide Support   
					Group.   
					UPS failed the battery test.   
					illuminated.   
					29   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Troubleshooting   
					Table 1   
					Troubleshooting guide (continued)   
					Problem   
					Cause   
					Solution   
					Your UPS has received a   
					signal or command from   
					the attached computer. If   
					this was inadvertent,   
					ensure the communication   
					cable used is correct for   
					your system. For   
					Fault and Bypass   
					indicator LEDs   
					and diagnostic   
					LED C and E are   
					illuminated.   
					UPS shutdown due to a   
					command from the   
					communications port(s).   
					assistance, contact your   
					local dealer, Liebert   
					representative or the   
					Liebert Worldwide Support   
					Group.   
					UPS detected a line-to-   
					neutral reversal or a loss of   
					proper grounding;   
					continuous horn and UPS   
					will not start.This is active   
					only when power is first   
					applied to the input. Once   
					the UPS is running, the AC   
					LED will not start flashing,   
					even if the input wiring is   
					changed.   
					Contact a qualified   
					electrician to verify site   
					wiring.   
					AC LED is   
					flashing.   
					Check battery connections,   
					completely power down   
					and restart UPS.   
					NOTE: If the battery circuit   
					opens while the UPS is   
					running, it will be detected   
					when the next battery test   
					is performed.   
					Battery LED is   
					flashing.   
					Battery source is not   
					available; continuous horn.   
					The AC input powers the   
					PFC input and serves as   
					the bypass source. If the   
					AC is present but the   
					Bypass voltage is present,   
					but is disabled for use   
					because the voltage or   
					frequency is outside   
					acceptable limits.   
					voltage or frequency   
					Bypass LED is   
					flashing.   
					exceeds the acceptable   
					range for safe operation   
					with a load, the bypass will   
					be disabled and this LED   
					will flash, indicating that the   
					bypass is unavailable.   
					30   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Troubleshooting   
					Table 2   
					Alarm conditions   
					Condition   
					Alarm   
					Battery Mode   
					(utility failure)   
					One short beep every 10 seconds;   
					more than 2 minutes of run time remaining   
					Two short beeps every 5 seconds;   
					less than 2 minutes of run time remaining   
					Low Battery   
					Output Overload   
					(bypass)   
					One short beep every half second   
					A one-second beep every 4 seconds   
					A one-second beep every 4 seconds   
					A one-second beep every 4 seconds   
					Overtemperature   
					(bypass)   
					DC Bus Overvoltage   
					(bypass)   
					Control Power Supply   
					Failure (bypass)   
					PFC Failure (bypass)   
					Inverter Failure   
					A one-second beep every 4 seconds   
					A one-second beep every 4 seconds   
					A 2-second beep every minute   
					Battery Test Failure   
					31   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Specifications   
					11.0 SPECIFICATIONS   
					Model Number   
					GXT2-500RT120   
					GXT2-700RT120   
					700VA / 490W   
					GXT2-1000RT120   
					1000VA / 700W   
					Model Rating   
					500VA/350W   
					DIMENSIONS - in. (mm)   
					Unit   
					W x D x H   
					3.5 x 21.5 x 17   
					(87 x 547 x 430)   
					3.5 x 21.5 x 17   
					(87 x 547 x 430)   
					3.5 x 21.5 x 17   
					(87 x 547 x 430)   
					Shipping   
					W x D x H   
					10.6 x 27.2 x 23   
					(269 x 691 x 584)   
					10.6 x 27.2 x 23   
					(269 x 691 x 584)   
					10.6 x 27.2 x 23   
					(269 x 691 x 584)   
					WEIGHT - lb. (kg)   
					Unit   
					48.9 (22.2)   
					57.7 (26.2)   
					48.9 (22.2)   
					57.7 (26.2)   
					49.1 (22.3)   
					57.9 (26.3)   
					Shipping   
					INPUT AC PARAMETERS   
					Voltage Range (typical)   
					120VAC nominal; variable based on output load   
					100% - 90% loading   
					90% -70% loading   
					70% -30% loading   
					30% - 0% loading   
					Frequency   
					80 VAC - 140 VAC   
					80 VAC / 140 VAC   
					80 VAC / 140 VAC   
					70 VAC / 140 VAC   
					60 VAC / 140 VAC   
					40 - 70 Hz; Auto Sensing   
					6 ft. attached   
					80 VAC / 140 VAC   
					80 VAC - 140 VAC   
					70 VAC - 140 VAC   
					60 VAC - 140 VAC   
					80 VAC / 140 VAC   
					70 VAC / 140 VAC   
					60 VAC / 140 VAC   
					6 ft. attached   
					10 ft. attached   
					Input Power Cord   
					w/ NEMA 5-15 plug w/ NEMA 5-15 plug w/ NEMA 5-15 plug   
					OUTPUT AC PARAMETERS   
					Output Receptacles   
					Voltage   
					(4) NEMA 5-15R   
					100/110/115/120/127 (user configurable) VAC; ±3%   
					50 Hz or 60 Hz   
					Frequency   
					Waveform   
					Sinewave   
					Main Mode   
					Overload   
					200% for 8 cycles; 130% for 10 seconds with transfer to bypass   
					BATTERY PARAMETERS   
					Type   
					Valve-regulated, nonspillable, flame retardant, lead acid   
					4 x 12V x 7.0 or 7.2 AH   
					Qty x V x Rating   
					Battery Mfg / Part #   
					Backup Time   
					China Storage Battery / CSB FR 1270 F2   
					
					Recharge Time   
					ENVIRONMENTAL   
					Operating Temp   
					Storage Temp   
					5 hours to 95% capacity after full discharge into 100% load   
					+32°F to +104°F (0°C to +40°C)   
					+5°F to +122°F (-15°C to +50°C)   
					Relative Humidity   
					Operating Elevation   
					Storage Elevation   
					0% to 95%, non-condensing   
					Up to 10,000 ft. (3000m) at 104°F (40°C) without derating   
					50,000 ft. (15,000m) maximum   
					<50 dBA, at 1 meter from the rear   
					<45 dBA, at 1 meter from the front or sides   
					Audible Noise   
					AGENCY   
					Safety   
					UL 1778, c-UL Listed (Suitable for computer room applications)   
					FCC Part 15, Subpart B, Class A   
					RFI/EMI   
					Surge Immunity   
					Transportation   
					IEEE/ANSI C62.41 Category A & B   
					ISTA Procedure 1A   
					32   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Specifications   
					
					Model Number   
					GXT2-1500RT120   
					GXT2-2000RT120 GXT2-3000RT120   
					Model Rating   
					1500VA / 1050W   
					2000VA / 1400W   
					3000VA / 2100W   
					DIMENSIONS - in. (mm)   
					Unit   
					W x D x H   
					3.5 x 21.5 x 17   
					(87 x 547 x 430)   
					3.5 x 21.5 x 17   
					(87 x 547 x 430)   
					3.5 x 24.2 x 17   
					(87 x 618 x 430)   
					Shipping   
					W x D x H   
					10.6 x 27.2 x 23   
					(269 x 691 x 584)   
					10.6 x 27.2 x 23   
					(269 x 691 x 584)   
					10.6 x 27.2 x 23   
					(269 x 691 x 584)   
					WEIGHT - lb. (kg)   
					Unit   
					Shipping   
					50.6 (23)   
					59.5 (27)   
					54 (24)   
					62.6 (28.4)   
					69 (31)   
					78.0 (35.4)   
					INPUT AC PARAMETERS   
					Voltage Range (typical)   
					100% - 90% loading   
					90% -70% loading   
					70% -30% loading   
					30% - 0% loading   
					Frequency   
					120 VAC nominal; variable based on output load   
					90 VAC / 140 VAC   
					90 VAC / 140 VAC 90 VAC / 140 VAC   
					80 VAC / 140 VAC 80 VAC / 140 VAC   
					70 VAC / 140 VAC 70 VAC / 140 VAC   
					60 VAC / 140 VAC 60 VAC / 140 VAC   
					40 - 70 Hz; Auto Sensing   
					80 VAC / 140 VAC   
					70 VAC / 140 VAC   
					60 VAC / 140 VAC   
					10 ft. attached   
					10 ft. attached   
					10 ft. attached   
					Input Power Cord   
					w/ NEMA 5-15 plug w/ NEMA 5-20 plug w/ NEMA L5-30 plug   
					OUTPUT AC PARAMETERS   
					(4) 5-20R T-Slot   
					(1) NEMA L5-30R   
					on 12 in cord   
					(4) 5-20R T-Slot,   
					accepts 15A plug   
					Output Receptacles   
					(4) NEMA 5-15R   
					Voltage   
					100/110/115/120/127 (user configurable) VAC; ±3%   
					Frequency   
					Waveform   
					50 Hz or 60 Hz   
					Sinewave   
					Main Mode Overload   
					BATTERY PARAMETERS   
					Type   
					200% for 8 cycles; 130% for 10 seconds with transfer to bypass   
					Valve-regulated, nonspillable, flame retardant, lead acid   
					Qty x V x Rating   
					4 x 12V x 7.0 or 7.2 AH 4 x 12V x 9.0 AH   
					China Storage Battery/   
					CSB FR 1270 F2   
					6 x 12V x 9.0 AH   
					Panasonic / UP-VW1245P1   
					Yuasa / REW 45-12 FR   
					Battery Mfg / Part #   
					Backup Time   
					
					Recharge Time   
					ENVIRONMENTAL   
					Operating Temp   
					Storage Temp   
					5 hours to 95% capacity after full discharge into 100% load   
					+32°F to +104°F (0°C to +40°C)   
					+5°F to +122°F (-15°C to +50°C)   
					Relative Humidity   
					Operating Elevation   
					Storage Elevation   
					0% to 95%, non-condensing   
					Up to 10,000 ft. (3000m) at 104°F (40°C) without derating   
					50,000 ft. (15,000m) maximum   
					<50 dBA, at 1 meter   
					from the rear   
					<45 dBA, at 1 meter   
					from the front or sides   
					<55 dBA, at 1 meter   
					from the rear   
					<50 dBA, at 1 meter   
					from the front or sides   
					Audible Noise   
					AGENCY   
					Safety   
					RFI/EMI   
					UL 1778, c-UL Listed (Suitable for computer room applications)   
					FCC Part 15, Subpart B, Class A   
					Surge Immunity   
					Transportation   
					IEEE/ANSI C62.41 Category A & B   
					ISTA Procedure 1A   
					33   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Battery Cabinet Specifications   
					12.0 BATTERY CABINET SPECIFICATIONS   
					Model Number   
					GXT2-48VBATT   
					GXT2-72VBATT   
					GXT2-500RT120   
					GXT2-700RT120   
					GXT2-1000RT120   
					GXT2-1500RT120   
					GXT2-2000RT120   
					Used With   
					UPS Model   
					GXT2-3000RT120   
					DIMENSIONS - in. (mm)   
					Unit   
					W x D x H   
					3.5 x 21.5 x 17   
					(87 x 547 x 430)   
					3.5 x 24.2 x 17   
					(87 x 618 x 430)   
					Shipping   
					W x D x H   
					10.5 x 27.2 x 23   
					(268 x 692 x 585)   
					10.5 x 27.2 x 23   
					(268 x 692 x 585)   
					WEIGHT - lb. (kg)   
					Unit   
					65.0 (29.5)   
					71.1 (32.3)   
					93.6 (42.5)   
					Shipping   
					102.5 (46.5)   
					BATTERY PARAMETERS   
					Type   
					Valve-regulated, nonspillable, flame retardant, lead acid   
					Qty x V x Rating   
					2 x 4 x 12V x 7.0 or 7.2 AH   
					2 x 6 x 12V x 9.0 AH   
					China Storage Battery /   
					CSBFR 1270 F2   
					Panasonic / UP-VW1245P1   
					Yuasa / REW 45-12 FR   
					Battery Mfg / Part #   
					Backup Time   
					
					ENVIRONMENTAL   
					Operating Temp   
					Storage Temp   
					+32°F to +104°F (0°C to +40°C)   
					+5°F to +122°F (-15°C to +50°C)   
					0% to 95%, non-condensing   
					Relative Humidity   
					Operating Elevation Up to 10,000 ft. (3000m) at 104°F (40°C) without derating   
					Storage Elevation   
					50,000 ft. (15,000 m) maximum   
					AGENCY   
					UL 1778, c-UL Listed   
					(Suitable for computer room applications)   
					Safety   
					RFI/EMI   
					FCC Part 15, Subpart B, Class A   
					ISTA Procedure 1A   
					Transportation   
					34   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Battery Run Times   
					13.0 BATTERY RUN TIMES   
					Load% 500VA 700VA 1000VA 1500VA 2000VA 3000VA   
					10%   
					20%   
					30%   
					40%   
					50%   
					60%   
					70%   
					80%   
					90%   
					100%   
					10%   
					20%   
					30%   
					40%   
					50%   
					60%   
					70%   
					80%   
					90%   
					100%   
					10%   
					20%   
					30%   
					40%   
					50%   
					60%   
					70%   
					80%   
					90%   
					100%   
					10%   
					20%   
					30%   
					40%   
					50%   
					60%   
					70%   
					80%   
					90%   
					100%   
					10%   
					20%   
					30%   
					40%   
					50%   
					60%   
					70%   
					80%   
					90%   
					100%   
					494   
					181   
					107   
					83   
					66   
					53   
					44   
					36   
					31   
					28   
					248   
					115   
					79   
					58   
					44   
					35   
					29   
					24   
					20   
					191   
					87   
					48   
					34   
					25   
					19   
					16   
					13   
					144   
					53   
					38   
					28   
					20   
					15   
					12   
					10   
					56   
					33   
					26   
					19   
					14   
					12   
					10   
					8 
					7 
					6 
					168   
					99   
					78   
					57   
					42   
					36   
					30   
					24   
					21   
					18   
					392   
					231   
					182   
					133   
					98   
					84   
					70   
					56   
					49   
					91   
					46   
					30   
					21   
					16   
					11   
					9 
					8 
					7 
					5 
					364   
					184   
					120   
					84   
					64   
					44   
					36   
					32   
					Internal   
					Battery   
					(minutes)   
					12   
					11   
					8 
					7 
					17   
					1976   
					726   
					431   
					332   
					267   
					210   
					178   
					150   
					132   
					115   
					3953   
					1453   
					862   
					665   
					534   
					421   
					356   
					300   
					265   
					231   
					5929   
					2179   
					1293   
					998   
					801   
					632   
					534   
					450   
					398   
					346   
					7906   
					2906   
					1725   
					1331   
					1068   
					843   
					712   
					600   
					525   
					462   
					992   
					460   
					316   
					232   
					176   
					140   
					116   
					96   
					764   
					348   
					192   
					136   
					100   
					76   
					64   
					52   
					48   
					44   
					1528   
					696   
					384   
					272   
					200   
					152   
					128   
					104   
					96   
					576   
					212   
					152   
					112   
					80   
					60   
					48   
					40   
					32   
					Internal   
					Battery   
					+ 1 External   
					Battery   
					Cabinet   
					(minutes)   
					80   
					68   
					28   
					20   
					28   
					1984   
					920   
					632   
					464   
					352   
					280   
					232   
					192   
					160   
					136   
					2976   
					1380   
					948   
					696   
					528   
					420   
					348   
					288   
					240   
					204   
					3968   
					1840   
					1264   
					928   
					704   
					560   
					464   
					384   
					320   
					272   
					1152   
					424   
					304   
					224   
					160   
					120   
					96   
					80   
					64   
					56   
					1728   
					636   
					456   
					336   
					240   
					180   
					144   
					120   
					96   
					728   
					368   
					240   
					168   
					128   
					88   
					72   
					64   
					56   
					40   
					1092   
					552   
					360   
					252   
					192   
					132   
					108   
					96   
					Internal   
					Battery   
					+ 2 External   
					Battery   
					Cabinets   
					(minutes)   
					88   
					42   
					2292   
					1044   
					576   
					408   
					300   
					228   
					192   
					156   
					144   
					132   
					3056   
					1392   
					768   
					544   
					400   
					304   
					256   
					208   
					192   
					176   
					560   
					330   
					260   
					190   
					140   
					120   
					100   
					80   
					Internal   
					Battery   
					+ 3 External   
					Battery   
					Cabinets   
					(minutes)   
					70   
					60   
					84   
					60   
					84   
					2304   
					848   
					608   
					448   
					320   
					240   
					192   
					160   
					128   
					112   
					840   
					495   
					390   
					285   
					210   
					180   
					150   
					120   
					105   
					90   
					1456   
					736   
					480   
					336   
					256   
					176   
					144   
					128   
					112   
					80   
					Internal   
					Battery   
					+ 4 External   
					Battery   
					Cabinets   
					(minutes)   
					Note: Approximate discharge times are in minutes and at 77°F (25°C) with a 100% resistive load.   
					35   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				Product Warranty Registration   
					14.0 PRODUCT WARRANTY REGISTRATION   
					To register for warranty protection:   
					• Visit the Quick Links section of our Web site at:   
					
					• Click on Product Warranty Registration and fill in the form.   
					If you have any questions, please contact us at:   
					US: 800-222-5877   
					Outside the US: 614-841-6755   
					
					36   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					 
				NOTES   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Download from Www.Somanuals.com. All Manuals Search And Download.   
				Download from Www.Somanuals.com. All Manuals Search And Download.   
				POWER AVAILABILITY   
					USER MANUAL   
					UPStation GXT 2U™   
					Technical Support/Service   
					The Company   
					Behind the Products   
					Web Site   
					
					Monitoring   
					800-222-5877   
					
					Outside the US: 614-841-6755   
					With over a million installations around the   
					globe, Liebert is the world leader in computer   
					protection systems. Since its founding in   
					1965, Liebert has developed a complete   
					range of support and protection systems for   
					sensitive electronics:   
					Single-Phase UPS   
					800-222-5877   
					
					Outside the US: 614-841-6755   
					• 
					Environmental systems—close-control   
					air conditioning from 1 to 60 tons   
					Power conditioning and UPS with power   
					ranges from 300VA to more than   
					1000kVA   
					Three-Phase UPS   
					800-543-2378   
					
					• 
					Environmental Systems   
					800-543-2778   
					• 
					Integrated systems that provide both   
					environmental and power protection in a   
					single, flexible package   
					Monitoring and control—from systems   
					of any size or location, on-site or remote   
					Service and support through more than   
					100 service centers around the world   
					and a 24/7 Customer Response Center   
					Outside the United States   
					614-888-0246   
					Locations   
					United States   
					1050 Dearborn Drive   
					P.O. Box 29186   
					• 
					• 
					Columbus, OH 43229   
					Italy   
					Via Leonardo Da Vinci 8   
					Zona Industriale Tognana   
					35028 Piove Di Sacco (PD)   
					+39 049 9719 111   
					While every precaution has been taken to   
					ensure the accuracy and completeness of   
					this literature, Liebert Corporation assumes   
					no responsibility and disclaims all liability for   
					damages resulting from use of this   
					Fax: +39 049 5841 257   
					Asia   
					23F, Allied Kajima Bldg.   
					138 Gloucester Road   
					Wanchai   
					Hong Kong   
					+852 2 572 2201   
					Fax: +852 2 831 0114   
					information or for any errors or omissions.   
					© 2005 Liebert Corporation   
					All rights reserved throughout the world.   
					Specifications subject to change without   
					notice.   
					® Liebert and the Liebert logo are registered   
					trademarks of Liebert Corporation. All names   
					referred to are trademarks or registered   
					trademarks of their respective owners.   
					SL-23150 (2/05) Rev. 7   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				 |