Liebert Pager Universal Monitor User Manual

MONITORING  
UNIVERSAL MONITOR  
USER MANUAL  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.2.2 Backing Up the Alarm Log (Service Terminal Interface only) . . . . . . . . . . . . . . . . . . . . . . . . . 34  
7.3.2 Backing Up the Event Log (Service Terminal Interface only) . . . . . . . . . . . . . . . . . . . . . . . . . 35  
7.4.3 Backing Up the Trend Log (Service Terminal Interface only) . . . . . . . . . . . . . . . . . . . . . . . . . 36  
8.0  
8.1  
8.2  
SILENCE ALARM & BACKUP LOG FILES (SERVICE TERMINAL INTERFACE)  
Silence Alarm (Service Terminal Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40  
Back Up Log Files (Service Terminal Interface only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41  
9.4  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9.8.2 Modem Setup - Additional Features (Service Terminal Interface only) . . . . . . . . . . . . . . . . . 62  
9.8.4 Pager Setup - Communications Check (Service Terminal Interface only). . . . . . . . . . . . . . . . 66  
9.9.5 Backup and Upload Configuration File (Service Terminal Interface only) . . . . . . . . . . . . . . . 71  
9.9.7 Setup Serv Ph Num - Communications Check (Service Terminal Interface only) . . . . . . . . . 75  
9.9.9 Perform Firmware Update (Service Terminal Interface only) . . . . . . . . . . . . . . . . . . . . . . . . . 76  
9.9.10 Initiate Remote Alarm Test (Service Terminal Interface only) . . . . . . . . . . . . . . . . . . . . . . . . 78  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A.5  
Silence Alarm & Back Up Log Files (Service Terminal Interface only). . . . . . . . . . . . . . . . 100  
A.5.1 Silence Alarm (Service Terminal Interface only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100  
A.5.2 Back Up Log Files (Service Terminal Interface only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101  
iv  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURES  
Figure 1  
TABLES  
Table 1  
v
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
1.0 INTRODUCTION  
The Liebert Universal Monitor’s extensive capabilities can put it at the heart of your protective net-  
work. The Universal Monitor employs local alarming and remote paging services to keep personnel  
on-site and at remote locations apprised of the status of equipment.  
The panel can interface with any device that closes an electrical contact or has a 4-20 mA signal. To  
improve process efficiency and troubleshooting, the panel tracks data in three types of logs: alarm,  
event and trend. The Universal Monitor has a local LCD interface and a remote dial-up interface.  
Further, the Universal Monitor can report ambient conditions that might adversely affect the facility  
or equipment and also can report alarms and other events, as well as initiate responses to reduce or  
prevent damage.  
When an alarm condition arises, the Universal Monitor displays alarm information and sounds an  
audible alarm; if configured, the panel also sends pager notifications and turns connected devices on  
or off. See 1.11 - Typical Sequence for a more detailed example.  
1.1  
Methods of Viewing and Configuring the Universal Monitor  
The Universal Monitor features remote access through two interfaces that allow users to configure  
the panel, silence alarms, back up logs, and perform many other functions to keep a large or small  
operation running smoothly and safely.  
LCD—liquid crystal display on the front of the panel  
Service Terminal Interface—accessible via computer connected directly through an RS232  
port or remotely through the Universal Monitor’s onboard modem  
These interfaces permit easy access and configuration of the Universal Monitor, allowing users to  
view data, silence alarms and have full access to information stored in the panel, including logs of  
alarms and events.  
One more interface—Liebert’s SiteScan Web enterprise monitoring system—is primarily for monitor-  
ing, though SiteScan also provides some configuration functions.  
1.2  
1.3  
Data Logs  
The three types of data logs—alarm history, event history and trend data of analog sensor readings—  
can be viewed on the LCD on the front of the Universal Monitor and downloaded through onboard  
communications ports.  
Optional Features  
An optional Expansion Board, which can be purchased separately, allows you to connect an additional  
16 digital inputs and eight digital outputs to the Universal Monitor.  
An optional Transformer Module, available only in the large enclosure, converts 115VAC or 230VAC  
to 24VAC.  
1.4  
Available Alarms  
The alarms available with the Universal Monitor are:  
• Discrete input alarm (for each digital input)  
• High setpoint  
• Low setpoint  
• Battery unplugged  
• Low battery  
• Loss of power  
• Check battery  
• Internal modem fault  
Two additional alarms are available with the optional Expansion Board:  
• Expansion board loss of communications  
• Expansion board restore of communications  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Introduction  
1.5  
Outside Enclosure Overview  
The enclosure for the Universal Monitor’s controller board comes in two sizes:  
• The large enclosure is designed to accommodate the Transformer Module and future compo-  
nents, in addition to the controller board.  
• The small enclosure is built to hold the controller board only.  
Both enclosures are 2-3/4" deep.  
Both enclosures have a built-in liquid crystal display (LCD) and a key lock, as shown in the example  
below. The enclosures are made of metal to accommodate secure conduit fittings and protect compo-  
nents against environmental debris.  
Figure 1 Small enclosure—external features  
LCD for configuration  
and operation  
The enclosure  
has knockouts  
and access slots  
on top and  
UNIVERSAL MONITOR  
05-SEP-02 14:04:13  
V5.100.0  
PRESS =STATUS/SETUP  
ESC  
Key lock  
bottom for  
cables and wires.  
Universal Monitor  
The enclosure must be secured to a wall, either flush-mounted or recessed in the wall, as described in  
2.0 - Installation - Main Board. Knockouts and access slots on the top and bottom allow easy con-  
nection of wires and cables (see 4.0 - Wiring and Connections - Main Board) with either mounting  
type.  
Figure 2 Large enclosure—internal features  
Transformer Module  
Back of LCD  
Controller Board  
LARM  
D IN VIEW)  
NO  
C
NC  
(TOP)  
(BOTTOM)  
LS1  
+
TB7:  
START  
ENABLE  
AUDIBLE  
P11  
R402  
R26  
NO  
ALARM  
Q11  
SENS  
TOP  
TB3:  
RELAY  
OUTPUTS  
BBOOTTTTOOMM))  
8
7
6
5
((BBOOTTTTOOMM))  
8
7
6
5
:  
TACT  
UTS  
1-2 TOP  
3-4 BOTTOM  
MODEM  
-
ALL CIRCUITS;  
CLASS  
: COMMS  
(TOP)  
2
P-
+
+
+
ON  
485  
TB9: ANALOG  
GROUND  
(BOTTOM)  
+
+
+
Knockouts and  
access slots  
(top and bottom)  
On/Off switch  
forTransformer  
Module  
Groundwire  
for LCD  
Power  
receptacle  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Introduction  
1.6  
Typical Configuration  
Figure 3 shows an example of external devices connected to the Universal Monitor’s controller board.  
There may be up to eight digital output, eight digital input and four analog input devices connected.  
The optional Universal Monitor Expansion Board provides additional connections for eight output  
and sixteen digital input devices. Remote access is available via SiteScan Web and through the  
modem, which enables pager notifications and use of the Service Terminal Interface.  
Figure 3 Typical Configuration  
Universal Monitor  
main board  
TB5: RM  
(TERMINAL VIEW)  
NO  
C
NC  
C
NC  
(BOTTOM)  
Digital outputs  
(TOP)  
OM  
LS1  
+
TB7:  
START  
ENABLE  
AUDIBLE  
P11  
24V INPUT  
R40  
R2  
Q11  
BATTERY  
P23:  
RS232  
BATTERY  
LCD  
CONTRAST  
TB3:  
RELAY  
TP1  
VBATT  
Water  
pump  
GND  
ON  
ON  
DIP  
S2  
OUTPUTS  
(BOTTOM)  
1
2
3
4
5
6
7
8
OFF  
(TOP)  
L
8
7
5 T
6
I
INPUT3  
INPUT4  
INPUT5  
INPUT6  
INPUT7  
INPUT8  
5
DS70  
DS67  
DS66  
Third-party  
system  
(BMS,  
security  
office)  
DS65  
DS64  
R334  
4
C71  
MODEM  
4
(BOTTOM)  
OP)  
8
7
6
5
TB2:  
CONTACT  
INPUTS  
Phone  
line  
1-2 TOP  
3-4 BOTTOM  
ON  
MODEM  
J11: PHONE  
PIN 3-TIP  
ALL CIRCUITS:  
CLASS  
4
10: COMMS  
(TOP)  
2
PIN 4-RING  
+
+
+
422  
AG  
TB9: ANALOG  
GROUND  
(BOTTOM)  
+
+
+
Digital inputs  
SiteScan Web  
Analog inputs  
Expansion Board  
(optional)  
LT410  
LT460  
USE COPPER (CU) CONDUCTORS ONLY.  
UPS  
POWER INPUT  
RELAY OUTPUTS  
D6  
V1  
V3  
V7  
V9  
V13  
V15  
EIA485  
0V  
+
-
(to UM-)  
(to UM+)  
S4 S3 S2 S1  
EIA485  
K1  
K2  
K3  
K4  
K5  
K6  
K7  
K8  
OUT2  
OUT6  
OUT7  
OUT8  
Digital outputs  
DEFAULT SETTINGS FOR USE WITH UNIVERSAL MONITOR  
Exhaust  
fan  
Digital inputs  
Heat  
rejection  
unit  
Generator  
Fire alarm  
panel  
Chiller  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Introduction  
1.7  
Controller Board Overview  
The Universal Monitor’s controller board has connectors for eight digital inputs, four analog inputs  
and eight digital outputs, as shown below. The board comes complete with light emitting diodes  
(LEDs) to display the status of monitored devices, a battery pack for short-term backup, communica-  
tions ports, power connections and other features necessary to monitor and protect your operation.  
A - Power  
On/Off switch  
B - Battery C - EIA422 D - Audible E - Audible horn  
pack  
LEDs  
horn  
jumper  
F - Common  
Alarm  
connectors  
EE - Transformer  
Module  
DD - 24VAC power  
connector  
TB5: CRM  
(TERMINAL VIEW)  
G - Digital output  
status LEDs  
NO  
C
NC  
C
NC  
(BOTTOM)  
(TOP)  
OM  
LS1  
+
CC - Battery pack  
connector  
TB7:  
START  
ENABLE  
AUDIBLE  
P11  
24V INPUT  
R40  
R2  
H - Manual  
Override Switch  
(outputs)  
Q11  
BB - LCD contrast  
adjustment  
BATTERY  
P23:  
BATTERY  
LCD  
CONTRAST  
I - Digital output  
connectors  
TB3:  
RELAY  
OUTPUTS  
TP1  
VBATT  
GND  
ON  
O
DIP  
S2  
AA - LCD connector  
Z - DIP switch 1  
1
2
3
4
5
6
7
8
(BOTTOM)  
OFF  
(TOP)  
8
7
J - Status LEDs  
6
INPUT3  
INPUT4  
INPUT5  
INPUT6  
INPUT7  
INPUT8  
5
DS70  
DS67  
DS66  
DS65  
DS64  
R334  
4
C71  
Y - Modem  
status LEDs  
K - Digital output  
loss-of-power  
jumper  
MODEM  
4
(BOTTOM)  
OP)  
8
7
6
X - Modem  
5
TB2:  
CONTACT  
INPUTS  
L - Digital input  
connectors  
W - 24VAC  
connector  
1-2 TOP  
3-4 BOTTOM  
ON  
MODEM  
J11: PHONE  
PIN 3-TIP  
ALL CIRCUITS:  
2
4
TB10: COMMS  
(TOP)  
M - Digital input  
status LEDs  
CLASS  
PIN 4-RING  
+
+
+
V - Power On/Off  
switch  
422  
AG  
TB9: ANALOG  
GROUND  
(BOTTOM)  
+
+
+
N - Analog  
ground  
connector  
U - Power  
receptacle  
T - Phone S - Serial  
line interface  
connector connector  
(RS232/EIA574)  
R - EIA485 Q - SiteScan P - 12VDC/24VDC O - Analog  
connector Web  
connector  
analog input  
jumper  
input  
connectors  
(EIA422)  
Table 1  
Controller board components  
Item  
Description  
For more information, see:  
A - Power On/Off  
switch  
Power switch for the controller board. When switched off,  
the battery pack is disabled.  
Provides battery backup during a power loss to maintain  
normal operation of the panel for a minimum of 10 minutes. 2.4.3: Connecting the Battery Pack  
The analog inputs will not be functional during a power loss 9.9.4: Connect Battery  
(P/N 133455P1).  
B - Battery pack  
Indicates the connection status between the Universal  
D - Audible horn  
Monitor and SiteScan Web.  
Provides audible notification when an alarm occurs.  
Jumper to disable the audible horn (factory default is  
enabled).  
N/A  
N/A  
The two common alarm connections are used to connect to 4.0: Wiring and Connections -  
a secondary warning device such as a horn, light or  
Building Management System (BMS). When an alarm is  
present, the contacts close and the external warning device  
is activated/notified. The common alarm contacts may be  
configured to be reset with the Silence button/command.  
F - Common Alarm  
connectors  
G - Digital output  
status LEDs  
Each output has an LED to indicate its status: ON/OFF  
(energized/de-energized).  
Placing the switch in the ON position will turn ON, or energize,  
all eight outputs simultaneously. This switch removes all  
automatic output control from the Universal Monitor.  
H - Manual Override  
Switch (outputs)  
Each of the eight output connections is a two-state point:  
ON/OFF (energized/de-energized).  
An example of a field digital output point is a motor starter.  
I - Digital output  
connectors  
J - Status LEDs  
Indicates the operational status of the controller board.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
                             
Introduction  
Table 1  
Controller board components (continued)  
Item  
Description  
For more information, see:  
One of eight output jumpers. Each digital output has a  
jumper to set the fail-safe position of the output point when  
power fails. The OFF position makes the contact Normally  
Open (factory default). The ON position makes the contact  
Normally Closed.  
Note: The jumper position has no effect on the contact  
when the Universal Monitor has power.  
K - Digital output loss-  
of-power jumper  
Each of the eight input connections is a two-state point:  
ON/OFF (energized/de-energized).  
An example of a field digital input point is a leak detector.  
L - Digital input  
connectors  
M - Digital input status  
LEDs  
Each input has an LED to indicate its status: ON/OFF  
(energized/de-energized).  
Connection for an externally powered analog sensor that  
needs a reference to ground.  
Each of the four input connections accepts a 4/20 mA  
signal.  
An example of a field analog input point is a temperature  
sensor.  
One jumper to select voltage supplied for two-wire analog  
sensors. The jumper supplies all four analog input  
connectors with the same voltage. Factory default is 24VDC.  
Q - SiteScan Web  
connector (EIA422)  
Connection to monitor Universal Monitor from Liebert’s  
SiteScan Web graphical monitoring package.  
Connection to optional Expansion Board (purchased  
separately). Connect maximum of one Expansion Board.  
R - EIA485 connector  
Connection for laptop or video terminal. Used for  
configuration and monitoring using the Service Terminal  
Interface. Requires a null modem cable for connectivity  
(P/N 201258P1).  
S - Serial interface  
connector (RS232/  
EIA574)  
Connection for phone line. Used for pager notifications,  
service phone number, and configuration and monitoring  
using the Service Terminal Interface. Requires an RJ11  
connector.  
T - Phone line  
connector  
115VAC power receptacle to power laptop during  
configuration and diagnostics. Receptacle not available on  
230VAC Transformer Module.  
U - Power receptacle  
(Transformer Module)  
V - Power On/Off  
switch (Transformer  
Module)  
Power switch to turn power On/Off to both Transformer  
Module 24VAC connectors and power receptacle.  
One of the two 24VAC connectors for power (the second is  
also on the right side of the Transformer Module near the  
top). Each connector is rated for 40VA.  
(Transformer Module)  
X - Modem  
On-board modem with 9600 baud rate.  
Y - Modem status LEDs Indicates the operational status of the modem.  
N/A  
DIP switch used for resetting password to default.  
Connection for the LCD on the enclosure door.  
Adjustment contrast for the LCD on the enclosure door.  
Connection for battery pack lead.  
N/A  
Power connection for the controller. Requires 24VAC.  
Transformer Module used to convert 115VAC or 230VAC  
to 24VAC. Available only in the large enclosure.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
1.8  
Optional Expansion Board Overview  
The Universal Monitor Expansion Board, purchased separately, has connectors for 16 digital inputs  
and eight digital outputs, as shown below. The board has light emitting diodes (LEDs) to display the  
status of monitored output devices, communications ports for connection to the Universal Monitor,  
power connections and other features necessary to monitor and protect your operation.  
J - 24VAC  
power  
connector  
USE COPPER (CU) CONDUCTORS ONLY.  
A - Digital output  
connectors (8)  
POWER INPUT  
RELAY OUTPUTS  
I - Power status  
LED (green)  
D6  
H - EIA485  
connector  
B - Digital  
output  
V1  
V3  
V7  
V9  
V13  
V15  
fuses (8)  
G - EIA485  
status LEDs  
(yellow & red)  
EIA485 + (to UM-)  
0V  
S4 S3 S2 S1  
EIA485 - (to UM+)  
C - Digital  
output  
K1  
K2  
K3  
K4  
K5  
K6  
K7  
K8  
OUT2  
OUT6  
OUT7  
OUT8  
DIP switch  
F - General  
statusLED  
(green)  
D - Digital output  
status LEDs (8)  
E - Digital input  
connectors (16)  
DEFAULT SETTINGS FOR USE WITH UNIVERSAL MONITOR  
Table 2  
Expansion board components  
Item  
Description  
For more information, see:  
Each of the eight output connections is a two-state point:  
ON/OFF (energized/de-energized).  
An example of a field digital output point is a motor starter.  
A - Digital output  
connectors (8)  
Bussmann GMA-2 or equivalent. 250V 2A Fast Blow fuse.  
CAUTION: Fuses must be replaced with equivalent fuses.  
NOTE: Two (2) replacement fuses are shipped with  
the Expansion Board enclosure.  
B - Digital output  
fuses (8)  
N/A  
C - Digital output  
DIP switch  
DIP switch used for setting Normally Open / Normally  
Closed.  
D - Digital output  
status LEDs (8)  
Each output has an LED to indicate its status: ON/OFF  
(energized/de-energized).  
Each of the 16 input connections is a two-state point: ON/  
OFF (energized/de-energized).  
An example of a field digital input point is a leak detector.  
E - Digital input  
connectors (16)  
F - General status  
LED (green)  
Indicates the operational status of the Expansion Board.  
G - EIA485 status  
LEDs (yellow & red)  
Two LEDs indicate status of the EIA485 connection:  
ON/OFF (energized/de-energized).  
H - EIA485  
connector  
Connection to the Universal Monitor.  
I - Power status LED  
(green)  
Indicates the power status of the Expansion Board.  
J - 24VAC power  
connector  
Power connection for the Expansion Board. Requires  
24VAC.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Introduction  
1.9  
LED Indicators  
The Universal Monitor’s controller board has LED indicators that show the status of inputs, outputs  
and the common alarm, as well as the modem and SiteScan Web connections.  
OUTPUT1  
DS56  
TB5: CM  
Output LEDs  
(TERMINAL VIEW)  
OUTPUT2  
EIA422 SiteScan  
Web LEDs  
DS54  
DS63  
NO  
C
NC  
NC  
OUTPUT3  
OUTPUT4  
OUTPUT5  
OUTPUT6  
OUTPUT7  
OUTPUT8  
(BOTTOM)  
(TOP)  
M  
DS61  
DS60  
LS1  
+
TB7:  
START  
ENABLE  
AUDIBLE  
P11  
DS62  
DS55  
DS57  
24V INPUT  
R40  
R2  
Q11  
DS50  
DS49  
CTRLLOCK  
SENLOCK  
CMN ALR  
DS59  
DS58  
BATTERY  
P23:  
BATTERY  
DS53  
LCD  
CONTRAST  
TB3:  
RELAY  
TP1  
VBATT  
GND  
ON  
ON  
DIP  
P
P
5
2  
OUTPUTS  
(BOTTOM)  
1
2
4
5
6
7
8
OFF  
(TOP)  
DS52  
S
8
MOP  
F PROG  
3  
Status LEDs  
Input LEDs  
7
DS51  
DS48  
6
574 TX  
574 RX  
IP1  
INPUT3  
INPUT4  
INPUT5  
INPUT6  
INPUT7  
INPUT8  
5
DS70  
DS67  
DS66  
DS47  
DS78  
DS79  
DS65  
DS64  
R334  
4
C71  
485 RX  
485 TX  
MODEM  
4
(BOTTOM)  
P)  
Modem LEDs  
8
7
6
DS69  
DS71  
MODEM  
INPUT1  
INPUT2  
INPUT3  
INPUT4  
INPUT5  
INPUT6  
INPUT7  
INPUT8  
5
DS77  
DS76  
DS74  
DS75  
TX  
RX  
DTR  
DCD  
TB2:  
CONTACT  
INPUTS  
DS72  
DS70  
DS67  
DS66  
1-2 TOP  
3-4 BOTTOM  
ON  
MODEM  
DS65  
DS64  
J11: PHONE  
PIN 3-TIP  
ALL CIRCUITS:  
CLASS  
485  
TB10: COMMS  
(TOP)  
2
PIN 4-RING  
+
+
+
422  
AG  
TB9: ANALOG  
GROUND  
(BOTTOM)  
+
+
+
Table 3  
LED indicators summary  
LED Color  
422 TX  
LED Type  
Description  
Green Universal Monitor is transmitting information over the EIA422 port  
Green Universal Monitor is receiving information over the EIA422 port  
Green Universal Monitor is transmitting information via the modem  
Green Universal Monitor is receiving information via the modem  
EIA422  
LEDs  
422 RX  
TX  
RX  
Modem  
LEDs  
DTR  
Green Indicates data terminal is ready (DTR)—lights up when modem is dialing  
Green Indicates data carrier is detected (DCD)—lights up when modem has connection  
Green Indicates output is ON or energized  
Green Indicates output is ON or energized  
Green Indicates output is ON or energized  
Green Indicates output is ON or energized  
Green Indicates output is ON or energized  
Green Indicates output is ON or energized  
Green Indicates output is ON or energized  
Green Indicates output is ON or energized  
N/A Not used  
DCD  
OUTPUT1  
OUTPUT2  
OUTPUT3  
OUTPUT4  
OUTPUT5  
OUTPUT6  
OUTPUT7  
OUTPUT8  
CTRLLOCK  
SENLOCK  
CMN ALR  
Output  
LEDs  
N/A Not used  
Green Indicates output is ON or energized  
Indicates the microprocessor is operating properly (MOP)—must be on before  
Universal Monitor will function  
MOP  
Green  
FPROG  
Green Indicates firmware is being upgraded—lights up during upgrade process  
574 TX or 232 TX Green Universal Monitor is transmitting information via the RS232 port  
574 RX or 232 RX Green Universal Monitor is receiving information via the RS232 port  
Universal Monitor is receiving information over the EIA485 port from the Expansion  
Status  
LEDs  
485 RX  
Green  
Board  
Universal Monitor is transmitting information over the EIA485 port to the Expansion  
Board  
485 TX  
Green  
INPUT1  
INPUT2  
INPUT3  
INPUT4  
INPUT5  
INPUT6  
INPUT7  
INPUT8  
Red Indicates input is ON or energized  
Red Indicates input is ON or energized  
Red Indicates input is ON or energized  
Red Indicates input is ON or energized  
Red Indicates input is ON or energized  
Red Indicates input is ON or energized  
Red Indicates input is ON or energized  
Red Indicates input is ON or energized  
Input  
LEDs  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Introduction  
1.10 LED Indicators - Optional Expansion Board  
The optional Expansion Board, purchased separately, has LED indicators that show the status of  
inputs and outputs.  
USE COPPER (CU) CONDUCTORS ONLY.  
POWER INPUT  
RELAY OUTPUTS  
D6  
Power status LED  
(D6 - green)  
D6  
V1  
V3  
V7  
V9  
V13  
V15  
EIA485 + (to UM-)  
0V  
Rx  
Tx  
S4 S3 S2 S1  
EIA485 - (to UM+)  
D4  
D5  
K1  
K2  
K3  
K4  
K5  
K6  
K7  
K8  
OUT2  
OUT6  
OUT7  
OUT8  
EIA485 status LEDs  
(D4 - yellow,  
D5 - red)  
DEFAULT SETTINGS FOR USE WITH UNIVERSAL MONITOR  
D3  
Gen.  
Status  
General status LED  
(D3 - green)  
K1  
K2  
K3  
K4  
K5  
K6  
K7  
K8  
OUT1  
OUT2  
OUT3  
OUT4  
OUT5  
OUT6  
OUT7  
OUT8  
Digital output status LEDs (8)  
Table 4  
LED indicators summary  
LED Type  
LED  
Color  
Description  
Power status  
LED  
24VAC  
Power (D6)  
Green 24VAC power is being supplied to Expansion Board  
Expansion Board is receiving information over the EIA485 port from the  
Universal Monitor  
485 RX (D4) Yellow  
EIA485 status  
LEDs  
Expansion Board is transmitting information over the EIA485 port to the  
Universal Monitor  
485 TX (D5)  
Red  
General status  
LED  
General  
Status (D3)  
Blinks green once per second to indicate the board is powered and  
operational. If the light is off, the board has likely lost power.  
Green  
OUT1  
OUT2  
OUT3  
OUT4  
OUT5  
OUT6  
OUT7  
OUT8  
Red  
Red  
Red  
Red  
Red  
Red  
Red  
Red  
Indicates output is ON or energized  
Indicates output is ON or energized  
Indicates output is ON or energized  
Indicates output is ON or energized  
Indicates output is ON or energized  
Indicates output is ON or energized  
Indicates output is ON or energized  
Indicates output is ON or energized  
Digital output  
status  
LEDs  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Introduction  
1.11 Typical Sequence  
Figure 4 shows a typical sequence of how the Universal Monitor functions after detecting a change in  
a monitored unit or area. Many responses depend on configuration settings. This example shows what  
happens when an analog sensor input reaches a high setpoint—assuming the input is defined as  
alarmable and is set up to trigger a response in an output—and when the condition returns to normal.  
Figure 4 Example of typical sequence: Analog input reaches high setpoint  
RESPONSES TO AN ALARM  
RETURN-TO-NORMAL SEQUENCE  
ALARM CONDITION DETECTED  
The temperature in a monitored  
analog input reaches its high setpoint.  
RETURN TO NORMAL  
The temperature in the monitored  
analog input returns to a normal  
range (below the high setpoint).  
The alarm is cleared  
The horn sounds (audible horn on  
the controller board—silence horn by  
pressing any key on the LCD keypad)  
(automatically if Unlatched; must be  
cleared manually if Latched)  
The horn stops sounding  
(if user hasn’t silenced it)  
The LCD flashes  
(except during setup)  
The LCD stops flashing  
UNIVERSAL MONITOR  
05-SEP-02 14:04:13  
V5.100.0  
UNIVERSAL MONITOR  
05-SEP-02 14:04:13  
V5.100.0  
PRESS =STATUS/SETUP  
PRESS =STA  
TUS/SETUP  
ESC  
ESC  
Pager numbers are dialed  
(up to four configured pagers)  
Service number is dialed  
(if configured)  
Pager numbers & service  
number are dialed  
Return-to-normal message sent  
A fan is turned on  
(if the fan is connected to an output  
set up to respond to this input)  
When the alarm is cleared,  
the fan shuts down  
Entry in Alarm Log  
Shows reading (80.0 DEG) &  
condition (HIGH SETPOINT ALARM)  
Entry in Alarm Log  
Shows reading (79.0 DEG) &  
condition (RETURN TO NORMAL)  
SENSOR_2  
HIGH SETPOINT ALARM  
80.0 DEG  
SENSOR_2  
RETURN TO NORMAL  
29-AUG-02  
79.0 DEG  
09:42:11  
29-AUG-02  
SENSOR_2  
09:29:10  
Entry in Active Alarm Log  
80.0 DEG  
HIGH SETPOINT ALARM  
Entry in Event Log  
Fan output on  
Entry in Event Log  
Fan output off  
OUTPUT08 ON  
CONTACT OPEN  
OUTPUT08 OFF  
CONTACT CLOSED  
29-AUG-02  
09:29:12  
05-MAY-02  
09:42:12  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installation - Main Board  
2.0 INSTALLATION - MAIN BOARD  
This section provides instructions for installing, mounting and connecting power to the Universal  
Monitor. For information on the optional Expansion Board, see 3.0 - Installation - Optional Expan-  
2.1  
Installation Considerations  
The Universal Monitor must be installed indoors and may be mounted on the surface of a wall or  
flush-mounted, depending on the user’s application, the location of equipment and sensors to be mon-  
itored and the type of wall the unit will be mounted on.  
The Universal Monitor should be mounted where it can be easily accessed. On-site personnel would  
access the unit through the LCD on its front cover, service terminal connected to the RS232 port or  
through SiteScan. For off-site monitoring, the Universal Monitor should be placed near communica-  
tions means such as a telephone line connection that would permit remote access.  
In addition to the communications connections, the site also must have electrical service and must  
permit connecting the unit’s eight digital inputs, eight digital outputs and four analog inputs.  
The wall material must be capable of supporting the weight of the Universal Monitor: see 10.0 -  
NOTE  
This equipment has been tested and found to comply with the limits for a Class A digital  
device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable  
protection against harmful interference when the equipment is operated in a commercial  
environment. This equipment generates, uses, and can radiate radio frequency energy and, if  
not installed and used in accordance with the instruction manual, may cause harmful  
interference to radio communications. Operation of this equipment in a residential area is  
likely to cause harmful interference in which case the user will be required to correct the  
interference at his own expense.  
2.1.1 Unpacking and Preliminary Inspection  
• Before unpacking the Universal Monitor, inspect the shipping carton for damage or signs of  
mishandling, such as gashes or holes in the carton or severely flattened corners.  
• Open the shipping crates carefully. Use care to avoid puncturing the container with sharp objects  
that might damage the contents.  
• Inspect the Universal Monitor and all included components for damage.  
• If any damage from shipping or mishandling is observed, immediately file a damage claim with  
the shipping agency and forward a copy to:  
Liebert Corporation  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, OH 43229  
Packing Contents  
Table 5  
Packing manifest - Universal Monitor main board  
Standard Components  
• Universal Monitor - large or small enclosure  
• User Manual  
• Keys (2) to panel door lock  
• Backup Battery - installed in unit (not connected or charged)  
• RS232 Configuration Cable  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Installation - Main Board  
2.2  
Surface-Mounting the Universal Monitor  
NOTE  
Removing the conduit knockouts before mounting the Universal Monitor on the wall will ease  
installation and prevent strain on the mounting hardware and wall. It is imperative to remove  
the knockouts if the unit is to be flush-mounted.  
After determining where to place the unit, check to ensure that you have all the hardware required to  
install the panel on the surface of a wall. Obtain the needed tools and material.  
Required tools  
• Electric drill (if surface is too hard to drive screws without pilot holes)  
• Screwdriver  
• Marker to denote layout of holes  
• Four screws, each #10  
2.2.1 Mounting the Panel  
CAUTION  
!
Check building plans and other relevant documents to determine whether mounting the  
Universal Monitor at the selected location might cause cutting or otherwise damaging  
electrical or communication wiring or pipes.  
1. Mark the wall for mounting holes, using the back of the unit as a template (see Figure 5).  
2. Drill holes, if required, to install the four #10 screws that will secure the Universal Monitor to the  
wall. Clean up the debris.  
3. If the wall material is not strong enough to hold the screws securely, use wall anchors.  
4. Install the top two screws—the screw heads must be small enough to slip through the larger,  
bottom portion of the pear-shaped mounting slot in the Universal Monitor (see inset in Figure 5).  
The screws must also be large enough to extend over the edges of the top of the mounting slot.  
5. Hang the Universal Monitor on the screws, letting the panel slip down until the screws are in the  
smaller, upper portion of the slot.  
6. Tighten the screws until they are snug.  
7. Insert the remaining two screws in the bottom holes on the back of the panel and tighten.  
Figure 5 Mounting Dimensions  
LARGE ENCLOSURE  
12"  
(304.8mm)  
SMALL ENCLOSURE  
12.5"  
(317.5mm)  
0.213"  
(5.4mm)  
16"  
(406.4mm)  
0.213"  
(5.4mm)  
10"  
Universal Monitor  
back plate  
(254mm)  
Universal Monitor  
back plate  
0.375"  
(9.6mm)  
Mounting Slot  
0.375"  
(9.6mm)  
Mounting Slot  
0.213" (5.4mm)  
Bottom hole diameter  
0.213" (5.4mm)  
Bottom hole diameter  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installation - Main Board  
2.3  
Flush-Mounting the Universal Monitor  
NOTE  
Removing the conduit knockouts before mounting the Universal Monitor on the wall will ease  
installation and prevent strain on the mounting hardware and wall. It is imperative to remove  
the knockouts if the unit is to be flush-mounted.  
The rectangular access doors on the top and bottom of the Universal Monitor must be reversed  
so they slide the opposite direction. Leaving the doors as shipped from the factory prevents  
them from being opened when the panel is flush mounted in a wall.  
The Universal Monitor may be flush-mounted according to company practices—either with screws  
through the sides of the panel into wall supports or with hanging hardware that attaches to the back  
of the panel. After determining how and where to place the unit, check to ensure that you have all the  
hardware required to install the panel in the wall. Obtain the needed tools.  
Required tools  
• Saw  
• Electric drill  
• Screwdriver  
• Marker to denote layout of the hole to accommodate the Universal Monitor  
• Trim ring and associated hardware  
• Mounting hardware  
2.3.1 Mounting the Panel  
CAUTION  
!
Check building plans and other relevant documents to determine whether mounting the  
Universal Monitor at the selected location might cause cutting or otherwise damaging  
electrical or communication wiring or pipes.  
1. Mark the wall for the cutout to accommodate the panel, using the back of the unit as a template.  
2. Drill a pilot hole for the saw blade, if required.  
3. Use the saw to cut out the marked section of the wall (if not new construction).  
4. Rest the Universal Monitor in the wall and mark where mounting screws will be inserted into the  
wall studs or other support member.  
5. Remove the panel and drill the holes for the mounting screws or wall anchors. Clean up the  
debris.  
6. Reverse the slide direction of the rectangular access doors on the top and bottom of the Universal  
Monitor. Leaving the doors as shipped from the factory prevents them from being opened when  
the panel is flush mounted in a wall.  
7. Attach any field-supplied mounting hardware.  
8. Reinsert the assembly into the wall.  
9. Insert and tighten the screws or wall anchors.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installation - Main Board  
2.4  
Connect Power to the Universal Monitor  
The Universal Monitor requires 24VAC for proper operation. Liebert recommends using the optional  
Transformer Module manufactured by Liebert or another UL-approved Class 2 power unit to obtain  
proper voltage. If the power unit is not a Class 2 circuit, it must be protected with an IEC 5 x 20mm  
time lag 2A fuse. For information, consult your local dealer, Liebert representative or the Liebert  
Worldwide Support Group.  
WARNING  
!
Check that power is removed from wires prior to installation.  
CAUTION  
!
The Universal Monitor is designed for use on properly grounded (earthed) 24VAC power,  
50Hz or 60Hz. The ground wire for the power lead must be wired to the earth ground terminal  
(stud located next to the 24VAC terminal block).  
This equipment is intended to be installed by a qualified and certified electrician who must  
review and approve customer supplied wiring and circuit breakers, verify correct input and  
grounded (earthed) connections to ensure compliance with technical standards and national  
and local electrical codes.  
WARNING  
!
Be sure that the Power On/Off switch is set to OFF before installing any wiring to this unit.  
The switch is in the top left corner of the unit, just below the battery pack.  
2.4.1 Input Power Connections - Small Enclosure  
To connect electrical power:  
1. Run conduit and electrical wiring from building to the Universal Monitor.  
2. Use copper wires only; proper wiring to use for 24VAC power is 18-22 AWG stranded and shielded  
(18 AWG is recommended—see Table 7). Strip wires 1/2".  
Figure 6 Electrical connections to panel  
External wiring  
through knockout  
Power On/Off switch  
Ground wire  
(black)  
Earth ground  
terminal  
24VAC wiring  
24VAC input connector  
(red & white)  
3. Secure the incoming electrical service wires to the Universal Monitor’s 24VAC input by sliding  
the wires into TB7, the 24VAC input terminal block. There is no polarity requirement when  
connecting to TB7. The ground wire must be connected to the earth ground terminal located on  
the side of the panel (see Figure 6).  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installation - Main Board  
2.4.2 Termination and Mounting - Large Enclosure  
CAUTION  
!
The 115VAC/230VAC Transformer Module must be connected to a branch circuit with 15A  
branch circuit protection.  
This equipment is intended to be installed by a qualified and certified electrician who must  
review and approve customer supplied wiring and circuit breakers, verify correct input and  
grounded connections to ensure compliance with the technical standards and national and  
local electrical codes.  
The Transformer Module shall be used only as indicated by the manufacturer.  
WARNING  
!
Be sure that the Power On/Off switch is set to OFF before installing any wiring to this unit.  
The switch is at the bottom of the unit.  
Input Power Connections  
To connect electrical power to the Transformer Module:  
1. Install electrical wiring from utility power to the Transformer Module.  
2. Use copper wires only; proper wiring to use for power is 14/2 AWG copper wire with ground.  
3. For the TM230 only: strip wires 3/8" (9.6mm).  
Note: For the TM115, wires are pre-stripped 0.4" (10.2mm) at the factory.  
4. Connect the wiring as follows:  
TM115  
TM230  
Connection Type  
White wire  
Black wire  
Green wire  
Neutral (L2)  
Line (L1)  
Neutral  
Power (Line)  
Ground  
Ground lead  
5. Secure the incoming electrical service wires to the TM115 input wires with wire nuts as shown in  
Figure 7 or to the TM230 connectors as shown in Figure 8.  
24 VAC Output Power Connections  
To connect to the 24VAC outputs:  
1. Install electrical wiring from device requiring 24VAC power to the Transformer Module.  
2. Use copper wire only; proper wiring to use for power is 18, 20 or 22 AWG copper wire. Strip  
wire 1/4".  
3. There are two 24 VAC output connectors (TB1 and TB2). Terminate wires to the connector as  
shown in Figures 7 and 8. TB1 and TB2 are NOT polarity sensitive.  
4. Secure the wires to the connector.  
Figure 7 Power wiring to TM115  
TM115  
Figure 8 Power wiring to TM230  
TM230  
Knockout for  
external wiring  
Knockout for  
external wiring  
Wire nuts  
connecting  
electrical  
wiring  
Ground  
Ground  
Line (L1)  
Neutral (L2)  
24VAC output  
(TB1)  
24VAC output  
(TB1)  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installation - Main Board  
Troubleshooting - Transformer Module  
A common problem and possible solution are shown in the table below. For further information or if  
you have other problems with the unit, consult your local dealer, Liebert representative or the Liebert  
Worldwide Support Group.  
Problem  
Possible Solution  
Replacement Fuse Part Numbers  
• LITTLEFUSE 218002  
or  
• BUSSMANN GDC-2A  
24VAC power  
not available  
from TB1 or TB2  
Check fuse for respective  
output (TB1 or TB2).  
2.4.3 Connecting the Battery Pack  
After connecting AC power to the Universal  
Monitor, you may connect the panel’s backup  
battery (factory-supplied) to the jumpers so it  
will begin charging when electrical power to  
the Universal Monitor is switched on.  
Battery pack  
NOTE  
If the battery is not hooked up before  
the Universal Monitor is switched on,  
it will trigger an alarm.  
To connect the battery pack, insert the battery  
leads into the jumpers as shown at right. (To  
disconnect the battery pack, remove the bat-  
tery leads from the jumpers.)  
Obtaining a Replacement Battery Pack  
To obtain a replacement battery pack, contact  
your local dealer or Liebert representative.  
The Liebert part number is 133455P1.  
Battery pack connector  
WARNING  
!
To prevent the risk of fire or explosion,  
replace only with 7.2 V rechargeable  
NiCad battery pack.  
CAUTION  
!
Dispose of the battery properly by  
sending it back to Liebert Corporation  
or an approved battery recycling  
facility.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation - Optional Expansion Board  
3.0 INSTALLATION - OPTIONAL EXPANSION BOARD  
This section provides instructions for installing, mounting and connecting power to the optional Expan-  
sion Board. The Expansion Board enclosure is identical to the Universal Monitor’s small enclosure.  
3.1  
Installation Considerations  
The optional Expansion Board must be installed indoors and may be mounted on the surface of a wall  
or flush-mounted, depending on the user’s application, the location of equipment and sensors to be  
monitored and the type of wall the unit will be mounted on.  
The Expansion Board may be placed up to 3000 ft. (914m) from the Universal Monitor and should be  
mounted where it can be easily accessed. The site must have electrical service and allow for connect-  
ing 16 digital inputs and eight digital outputs.  
The wall material must be capable of supporting the weight of the Expansion Board: see 10.2 -  
NOTE  
This equipment has been tested and found to comply with the limits for a Class A digital  
device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable  
protection against harmful interference when the equipment is operated in a commercial  
environment. This equipment generates, uses, and can radiate radio frequency energy and, if  
not installed and used in accordance with the instruction manual, may cause harmful  
interference to radio communications. Operation of this equipment in a residential area is  
likely to cause harmful interference in which case the user will be required to correct the  
interference at his own expense.  
3.1.1 Unpacking and Preliminary Inspection  
• Before unpacking the optional Expansion Board, inspect the shipping carton for damage or signs  
of mishandling, such as gashes or holes in the carton or severely flattened corners.  
• Open the shipping crates carefully. Use care to avoid puncturing the container with sharp objects  
that might damage the contents.  
• Inspect the Expansion Board and all included components for damage.  
• If any damage from shipping or mishandling is observed, immediately file a damage claim with  
the shipping agency and forward a copy to:  
Liebert Corporation  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, OH 43229  
Packing Contents  
Table 6  
Packing manifest - optional Expansion Board  
Standard Components  
• Expansion Board - small enclosure  
• User Manual  
• Keys (2) to panel door lock  
• Two (2) spare fuses for output relays  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Installation - Optional Expansion Board  
3.2  
Surface-Mounting the Optional Expansion Board  
NOTE  
Removing the conduit knockouts before mounting the optional Expansion Board on the wall  
will ease installation and prevent strain on the mounting hardware and wall. It is imperative  
to remove the knockouts if the unit is to be flush-mounted.  
After determining where to place the optional Expansion Board, check to ensure that you have all the  
hardware required to install the panel on the surface of a wall. Obtain the needed tools and material.  
Required tools  
• Electric drill (if surface is too hard to drive screws without pilot holes)  
• Screwdriver  
• Marker to denote layout of holes  
• Four screws, each #10  
3.2.1 Mounting the Panel  
CAUTION  
!
Check building plans and other relevant documents to determine whether mounting the  
optional Expansion Board at the selected location might cause cutting or otherwise damaging  
electrical or communication wiring or pipes.  
1. Mark the wall for mounting holes, using the back of the unit as a template (see Figure 5).  
2. Drill holes, if required, to install the four #10 screws that will secure the optional Expansion  
Board to the wall. Clean up the debris.  
3. If the wall material is not strong enough to hold the screws securely, use wall anchors.  
4. Install the top two screws—the screw heads must be small enough to slip through the larger,  
bottom portion of the pear-shaped mounting slot in the Expansion Board (see inset in Figure 5).  
The screws must also be large enough to extend over the edges of the top of the mounting slot.  
5. Hang the Expansion Board on the screws, letting the panel slip down until the screws are in the  
smaller, upper portion of the slot.  
6. Tighten the screws until they are snug.  
7. Insert the remaining two screws in the bottom holes on the back of the panel and tighten.  
Figure 9 Mounting Dimensions - optional Expansion Board  
SMALL ENCLOSURE  
12.5"  
(317.5mm)  
0.213"  
(5.4mm)  
10"  
(254mm)  
Expansion Board  
back plate  
0.375"  
(9.6mm)  
Mounting Slot  
0.213" (5.4mm)  
Bottom hole diameter  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installation - Optional Expansion Board  
3.3  
Flush-Mounting the Optional Expansion Board  
NOTE  
Removing the conduit knockouts before mounting the optional Expansion Board on the wall  
will ease installation and prevent strain on the mounting hardware and wall. It is imperative  
to remove the knockouts if the unit is to be flush-mounted.  
The rectangular access doors on the top and bottom of the Expansion Board must be reversed  
so they slide the opposite direction. Leaving the doors as shipped from the factory prevents  
them from being opened when the panel is flush mounted in a wall.  
The optional Expansion Board may be flush-mounted according to company practices—either with  
screws through the sides of the panel into wall supports or with hanging hardware that attaches to  
the back of the panel. After determining how and where to place the unit, check to ensure that you  
have all the hardware required to install the panel in the wall. Obtain the needed tools.  
Required tools  
• Saw  
• Electric drill  
• Screwdriver  
• Marker to denote layout of the hole to accommodate the optional Expansion Board  
• Trim ring and associated hardware  
• Mounting hardware  
3.3.1 Mounting the Panel  
CAUTION  
!
Check building plans and other relevant documents to determine whether mounting the  
optional Expansion Board at the selected location might cause cutting or otherwise damaging  
electrical or communication wiring or pipes.  
1. Mark the wall for the cutout to accommodate the panel, using the back of the unit as a template.  
2. Drill a pilot hole for the saw blade, if required.  
3. Use the saw to cut out the marked section of the wall (if not new construction).  
4. Rest the optional Expansion Board in the wall and mark where mounting screws will be inserted  
into the wall studs or other support member.  
5. Remove the panel and drill the holes for the mounting screws or wall anchors. Clean up the  
debris.  
6. Reverse the slide direction of the rectangular access doors on the top and bottom of the Expansion  
Board. Leaving the doors as shipped from the factory prevents them from being opened when the  
panel is flush mounted in a wall.  
7. Attach any field-supplied mounting hardware.  
8. Reinsert the assembly into the wall.  
9. Insert and tighten the screws or wall anchors.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installation - Optional Expansion Board  
3.4  
Input Power Connections - Optional Expansion Board  
The optional Expansion Board requires 24VAC for proper operation. Liebert recommends using the  
optional Transformer Module manufactured by Liebert or another UL-approved Class 2 power unit to  
obtain proper voltage. If the power unit is not a Class 2 circuit, it must be protected with an IEC  
5 x 20mm time lag 2A fuse. For information, consult your local dealer, Liebert representative or the  
Liebert Worldwide Support Group.  
CAUTION  
!
The Expansion Board is designed for use on properly grounded (earthed) 24VAC Class 2  
power, 50Hz or 60Hz. The ground wire for the power lead must be wired to the earth ground  
terminal (stud located next to the 24VAC terminal block). This equipment is intended to be  
installed by a qualified and certified electrician who must review and approve customer-  
supplied wiring and circuit breakers, verify correct input and grounded (earthed) connections  
to ensure compliance with technical standards and national and local electrical codes.  
WARNING  
!
“RISK OF ELECTRIC SHOCK” - More than one disconnect switch may be required to  
de-energize the equipment before servicing.  
WARNING  
!
Hazardous voltage may be present.  
To connect electrical power:  
1. Run 24VAC electrical power from the TB2 (or TB1) connector of the Transformer Module, as  
shown in Figure 10, or another 24V source to the Expansion Board in accordance with local  
electrical codes.  
2. Use copper wires only; proper wiring to use for power is 18-22 AWG stranded and shielded  
(18 AWG is recommended—see Table 9). Strip wires 1/2".  
Figure 10 Electrical connections to panel  
OPTIONAL EXPANSION BOARD  
TRANSFORMER MODULE  
(TM115 shown)  
Ground wire  
(pre-wired)  
Ground wire  
connector  
(0V)  
POWER INPUT  
24VAC wiring  
(red & white)  
24VAC input  
connectors  
(AC1 & AC2)  
EIA485 + (to UM-)  
0V  
EIA485 - (to UM+)  
S4  
24VAC output (TB2 shown;  
use either TB1 or TB2)  
3. Secure the incoming electrical service wires to the Expansion Board’s 24VAC input by sliding the  
wires into AC1 and AC2, the 24VAC input connectors, as shown in Figure 10. There is no  
polarity requirement when connecting to these connectors.  
NOTE: The ground wire connection to the 0V connector is pre-wired at the factory.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Wiring and Connections - Main Board  
4.0 WIRING AND CONNECTIONS - MAIN BOARD  
CAUTION  
!
Switch OFF electric power to the Universal Monitor before installing any wiring to the unit or  
changing input or output connections. The Power On/Off switch is in the top left corner of the  
unit, just below the battery pack.  
4.1  
Wiring Specifications  
Input and output connections to the Universal Monitor may be made in any order—it is not neces-  
sary, for example, to make all input connections before making any output connections. Use copper  
conductors only for all wiring.  
Table 7  
Wiring specifications - main board  
Connection  
Supported Wire Type  
Maximum Wire Length  
Rating  
18-22 AWG Stranded & Unshielded  
18 AWG* (recommended)  
Non Plenum - Belden 9740  
Plenum - Belden 89740  
Dry Contact  
(24VDC,  
10 mA)  
Digital  
Input  
750 ft. (225m)  
18 AWG*  
(recommended)  
20 AWG  
22 AWG  
18-22 AWG Stranded & Unshielded  
18 AWG* (recommended)  
Non Plenum - Belden 9740  
Plenum - Belden 89740  
Digital  
Output  
24VAC  
@3A  
@3A 50 ft. (15m) @3A 40 ft. (12m) @3A 25 ft. (7m)  
@2A 100 ft. (30m) @2A 60 ft. (18m) @2A 35 ft. (10m)  
@1A 200 ft. (60m) @1A 100 ft. (30m) @1A 75 ft. (23m)  
18-22 AWG Stranded & Unshielded  
18 AWG* (recommended)  
Non Plenum - Belden 9740  
Plenum - Belden 89740  
4-20 mA Signal  
Input Selectable  
Power Source  
(12/24VDC)  
Analog Input  
2-Wire  
Transducer  
750 ft. (225m)  
18-22 AWG Stranded & Unshielded  
18 AWG* (recommended)  
Non Plenum - Belden 8489  
Plenum - Belden 88489  
4-20 mA Signal  
Input Selectable  
Power Source  
(12/24VDC)  
Analog Input  
4-Wire  
Transducer  
750 ft. (225m)  
18 AWG*  
(recommended)  
20 AWG  
22 AWG  
18-22 AWG Stranded & Unshielded  
18 AWG* (recommended)  
Non Plenum - Belden 9740  
Plenum - Belden 89740  
Common  
Alarm  
Output  
24VAC  
@3A  
@3A 50 ft. (15m) @3A 40 ft. (12m) @3A 25 ft. (7m)  
@2A 100 ft. (30m) @2A 60 ft. (18m) @2A 35 ft. (10m)  
@1A 200 ft. (60m) @1A 100 ft. (30m) @1A 75 ft. (23m)  
Communication  
RS232  
Null Modem Cable  
50 ft. (15m)  
N/A  
N/A  
18-22 AWG Stranded & Shielded  
22 AWG* (recommended)  
Non Plenum - Belden 9461  
Plenum - Belden 88761  
Communication  
EIA422  
1000 ft. (300m)  
SiteScan  
18-22 AWG Stranded & Shielded  
22 AWG* (recommended)  
Non Plenum - Belden 9461  
Plenum - Belden 88761  
Communication  
EIA485  
3000 ft. (900m)  
N/A  
N/A  
N/A  
Phone/Modem  
Line  
4 Wire (Pins 3 & 4)  
RJ11 Connector  
18-22 AWG Stranded & Shielded  
18 AWG* (recommended)  
Non Plenum - Belden 8770  
Plenum - Belden 88770  
24VAC Power  
Connection  
(TB7)  
24VAC  
@1.3A  
150 ft. (45m)  
Power Connections (Transformer Module)  
14 AWG Stranded & Unshielded  
115VAC  
115VAC  
@4A  
150 ft. (45m)  
150 ft. (45m)  
Non Plenum - Belden 5101UE  
14 AWG Stranded & Unshielded  
230VAC  
230VAC  
@0.5A  
Non Plenum - Belden 5101UE  
* Recommended  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Wiring and Connections - Main Board  
4.2  
Connecting Digital Inputs and Digital Outputs  
The digital inputs and digital outputs are found on the lower right side of the Universal Monitor’s  
printed wiring assembly board. There are two terminal blocks for the inputs—one green, the other  
black. There are two terminal blocks for the outputs—one green, the other black.  
To determine the proper wire size, see Table 7 - Wiring specifications - main board.  
NOTE  
Each terminal block is a removable, two-part assembly to permit easier connection of more  
than one input at a time. If making multiple connections, grasp the upper portion of a block  
and pull firmly to the right until the assembly pulls apart.  
After making the connections, push the removed piece back into the portion attached to the  
printed wiring assembly until the terminal block pieces lock together.  
4.2.1 Connecting Digital Inputs  
TB3:  
RELAY  
OUTPUTS  
(BOTTOM)  
(TOP)  
To connect an input:  
OUTPUT TERMINAL BLOCKS -  
Note numbering of outputs  
begins at the bottom and  
proceeds up; numbering  
keys are shown at right  
1. Turn OFF electrical power to the Universal  
Monitor.  
8
4
2. If necessary, remove a conduit knockout to  
permit wire entry into the Universal  
Monitor enclosure.  
7
3
6
2
3. Bring the wire(s) into the Universal Monitor  
enclosure through a conduit knockout or  
access slot.  
5
1
(BOTTOM)  
(TOP)  
Numbering keys  
4. Loosen the appropriate screw and slip the  
stripped end of the wire into the terminal  
block.  
8
4
7
3
6
2
5. Tighten the screw until it holds the wire  
snugly.  
5
1
4.2.2 Connecting Digital Outputs  
TB2:  
CONTACT  
INPUTS  
To connect an output:  
INPUT TERMINAL BLOCKS -  
Note numbering of inputs  
begins at the bottom and  
proceeds up; numbering  
keys are shown at right  
1. Turn OFF electrical power to the Universal  
Monitor.  
2. If necessary, remove a conduit knockout to  
permit wire entry into the Universal  
Monitor enclosure.  
3. Bring the wire(s) into the Universal Monitor enclosure through a conduit knockout or access slot.  
4. Loosen the appropriate screw and slip the stripped end of the wire into the terminal block.  
5. Tighten the screw until it holds the wire snugly.  
CAUTION  
!
To reduce the risk of fire or electric shock, do not interconnect the outputs of  
different Class 2 circuits.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Wiring and Connections - Main Board  
4.2.3 Setting the Digital Output Jumpers  
Each digital output has an associated jumper to define its operation when power is interrupted and  
there is no battery backup to the board. This puts the Universal Monitor in a fail-safe mode and  
ensures proper functioning when the board has no power or battery backup.  
The Universal Monitor comes from the factory with  
all digital output jumpers in the OFF position (nor-  
Digital output jumpers  
mally open). The jumper setting for each digital  
output can be changed to ON (normally closed).  
The settings are shown in Table 8.  
Table 8  
Digital output jumper settings  
TB3:  
RELAY  
OUTPUTS  
(BOTTOM)  
(TOP)  
Output status  
Setting (power loss & no battery backup)  
OFF  
ON  
Normally open  
8
4
Normally closed  
7
3
To change the output jumper setting:  
6
2
1. Find the respective black output jumper on the  
circuit board, as shown above.  
2. Decide whether your configuration requires  
the jumper to be OFF or ON.  
5
1
(BOTTOM)  
(TOP)  
3. Set the jumper as needed:  
8
4
• Set the jumper to OFF by placing the black  
jumper on the middle and top pins.  
• Set the jumper to ON by placing the black  
jumper on the middle and bottom pins.  
7
3
6
2
4.3  
Connecting Analog Inputs  
The analog input connector blocks are at the bottom  
center of the Universal Monitor printed circuit board.  
The blocks are two-part assemblies to permit easier  
connections. To determine the proper wire size, see  
Analog ground  
Analog inputs  
To connect an input:  
1. Turn OFF electrical power to the Universal  
Monitor.  
1-2 TOP  
3-4 BOTTOM  
2. If necessary, remove a conduit knockout to permit  
wire entry into the Universal Monitor enclosure.  
3. Bring the wire(s) into the Universal Monitor  
enclosure through a conduit knockout or access slot.  
485  
0: COMMS  
(TOP)  
+
+
+
422  
AG  
TB9: ANALOG  
GROUND  
4. Loosen the appropriate screw and slip the stripped  
end of the wire into the terminal block.  
(BOTTOM)  
+
+
+
5. Tighten the screw until it holds the wire snugly.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Wiring and Connections - Main Board  
4.3.1 Setting the 12VDC/24VDC Analog Power Jumper  
The analog power jumper sets the common voltage that is applied to all of the analog input connec-  
tions. The jumper permits the user to modify the voltage supplied to the sensors, according to the  
power requirements.  
The factory default position is 24VDC; it may be changed to 12VDC.  
Analog power jumper  
To change the analog power jumper setting:  
1. Find the black analog jumper on the circuit board, as shown at  
right. The jumper is at the bottom of the board near the middle  
1-2 TOP  
3-4 BOTTOM  
2. Decide whether your configuration requires the jumper to be  
24VDC or 12VDC.  
3. Set the jumper as needed:  
• Set the jumper to the 24VDC position by placing the black  
485  
COMMS  
(TOP)  
+
+
+
jumper on the middle and right pins.  
• Set the jumper to the 12VDC position by placing the black  
jumper on the middle and left pins.  
422  
AG  
TB9: ANALO  
GROUND  
(BOTTOM)  
+
+
+
4.3.2 Connecting the Analog Ground  
Analog  
input  
Analog  
ground  
The Universal Monitor features an analog ground  
connection for four-wire sensors that have an  
external power source. Such a four-wire sensor  
requires a reference to ground because they get  
power from an external power source.  
1-2 TOP  
3-4 BOTTOM  
A two-wire transducer, which does not have an  
external power source, does not need to be con-  
nected to the analog ground.  
TB10: COMMS  
(TOP)  
+
The analog ground connector has two terminals,  
each of which can accommodate two wires. This is  
adequate to connect four sensors that require a  
reference to ground because they get power from  
an external power source.  
TB9: ANALOG  
GROUND  
(BOTTOM)  
+
Connect the analog ground to an external four-  
wire sensor as shown in the illustration at right.  
Four-wire  
transducer  
Sensor  
with  
external  
power  
24V from  
external  
power  
source  
+
4/20mA  
Output  
+
24V Input  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Wiring and Connections - Main Board  
4.4  
Connecting Common Alarm Outputs  
The common alarm relay, found in the top right corner of the Uni-  
versal Monitor, permits the user to connect auxiliary notification  
equipment, such as lights, horns and sirens, to the Universal  
Monitor. To determine the proper wire size, see Table 7 - Wiring  
TB5: COMMON ALARM  
(TERMINAL BLOCKS ROTATED IN VIEW)  
NO  
C
NC  
NO  
C
NC  
(BOTTOM)  
(TOP)  
+
There are two connectors for the common alarm output. However,  
the connectors are not individual relay outputs. The connectors  
should be treated as a double-pole, double-throw (DPDT) relay.  
ENABLE  
AUDIBLE  
P11  
R402  
R26  
C
MON ALARM  
NO  
Q11  
SENS  
TOP  
The common alarm relay is energized whenever an alarm occurs.  
To connect an output:  
Common alarm outputs  
1. Turn OFF electrical power to the Universal Monitor.  
2. If necessary, remove a conduit knockout to permit wire entry into the Universal Monitor  
enclosure.  
3. Bring the wire(s) into the Universal Monitor enclosure through a conduit knockout or access slot.  
4. Loosen the appropriate screw and slip the stripped end of the wire into the terminal block.  
5. Tighten the screw until it holds the wire snugly.  
4.5  
EIA422 SiteScan Web Connector  
The Universal Monitor will interface with Liebert’s SiteScan Web  
enterprise monitoring system. SiteScan can be used to monitor  
analog and digital equipment from a host computer and also to  
perform some configuration.  
To connect the SiteScan host computer to the Universal Monitor:  
1. Turn OFF electrical power to the Universal Monitor.  
2. If necessary, remove a conduit knockout to permit wire entry  
into the Universal Monitor enclosure.  
3. Bring the wire(s) into the Universal Monitor enclosure through  
a conduit knockout or access slot.  
4
TB10: COMMS  
(TOP)  
+
422  
(BOTTOM)  
+
4. Loosen the appropriate screw and slip the stripped end of the  
wire into the terminal block.  
EIA422 SiteScan Web  
connector  
5. Tighten the screw until it holds the wire snugly.  
4.6  
Communications Connections  
Serial interface  
connector  
(RS232/EIA574)  
The Universal Monitor’s Service Terminal Interface offers full  
configuration and monitoring capability via the RS232 port and  
the phone line connector (see A.2 - Connecting to the  
Service Terminal Interface). The phone line connector is  
also used for pager notifications and service phone number  
options.  
4.6.1 RS232 Connector  
The RS232 port requires a null modem cable. Connect one end  
MODEM  
of the cable to the Universal Monitor’s RS232 port, as shown at  
right, and the other end to the COM1 port of a laptop computer  
or video terminal.  
RJ11: PHONE  
PIN 3-TIP  
4
+
TB10: COMMS  
(TOP)  
PIN 4-RING  
4
(BOTTOM)  
4.6.2 Phone Line Connector  
The Phone Line Connector requires an RJ11 connector.  
Connect one end of the connector to the Universal Monitor’s  
phone line connector, shown at right, and the other end to a  
telephone wall jack.  
Phone line  
connector  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
Wiring and Connections - Optional Expansion Board  
5.0 WIRING AND CONNECTIONS - OPTIONAL EXPANSION BOARD  
CAUTION  
!
!
Remove all power before installing any wiring to the Expansion Board or changing input or  
output connections.  
WARNING  
“RISK OF ELECTRIC SHOCK” - More than one disconnect switch may be required to  
de-energize the equipment before servicing.  
5.1  
Wiring Specifications  
Input and output connections to the optional Expansion Board may be made in any order—it is not  
necessary, for example, to make all input connections before making any output connections. Use cop-  
per conductors only for all wiring.  
Table 9  
Wiring specifications - optional Expansion Board  
Connection  
Supported Wire Type  
Maximum Wire Length  
Rating  
18-22 AWG Stranded & Unshielded  
18 AWG* (recommended)  
Non Plenum - Belden 9740  
Plenum - Belden 89740  
Dry Contact  
(24VDC,  
10 mA)  
Digital  
Input  
750 ft. (225m)  
18 AWG*  
(recommended)  
20 AWG  
22 AWG  
18-22 AWG Stranded & Unshielded  
18 AWG* (recommended)  
Non Plenum - Belden 9740  
Plenum - Belden 89740  
Digital  
Output  
240VAC,  
2A max.  
@3A 50 ft. (15m) @3A 40 ft. (12m) @3A 25 ft. (7m)  
@2A 100 ft. (30m) @2A 60 ft. (18m) @2A 35 ft. (10m)  
@1A 200 ft. (60m) @1A 100 ft. (30m) @1A 75 ft. (23m)  
18-22 AWG Stranded & Shielded  
22 AWG* (recommended)  
Non Plenum - Belden 9461  
Plenum - Belden 88761  
Communication  
EIA485  
3000 ft. (900m)  
150 ft. (45m)  
N/A  
18-22 AWG Stranded & Shielded  
18 AWG* (recommended)  
Non Plenum - Belden 8770  
Plenum - Belden 88770  
24VAC Power  
Connection  
(TB1)  
24VAC  
@0.6A  
* Recommended  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Wiring and Connections - Optional Expansion Board  
5.2  
Connecting Inputs and Outputs  
The Universal Monitor’s optional Expansion Board permits the addition of 16 input and eight output  
devices. This section describes how to connect devices to the Expansion Board’s inputs and outputs.  
To determine the proper wire size, see Table 9.  
NOTE  
Each terminal block is a removable assembly to permit easier connection of more than one  
input at a time. If making multiple connections, grasp the upper portion of a block and pull  
firmly until the assembly pulls apart.  
After making the connections, push the removed piece back into the portion attached to the  
printed wiring assembly until the terminal block pieces lock together.  
5.2.1 Connecting Digital Inputs  
The 16 digital inputs are found on the lower portion of the Expansion Board, as shown below. These  
inputs are numbered 9 through 24 (the Universal Monitor’s digital inputs are numbered 1 through 8).  
EIA485 + (to UM-)  
0V  
S4 S3 S2 S1  
EIA485 - (to UM+)  
K1  
K2  
K3  
K4  
K5  
K6  
K7  
K8  
OUT2  
OUT6  
OUT7  
OUT8  
Numbering keys  
DEFAULT SETTINGS FOR USE WITH UNIVERSAL MONITOR  
INPUT TERMINAL BLOCKS  
Note numbering keys below terminal blocks;  
inputs are numbered from left (9) to right (24)  
To connect an input:  
1. Disconnect all electrical power from the Expansion Board.  
2. If necessary, remove a conduit knockout to permit wire entry into the Expansion Board enclosure.  
3. Bring the wire(s) into the Expansion Board enclosure through a conduit knockout or access slot.  
4. Loosen the appropriate screw and slip the stripped end of the wire into the terminal block.  
5. Tighten the screw until it holds the wire snugly.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Wiring and Connections - Optional Expansion Board  
5.2.2 Connecting Digital Outputs  
The eight digital outputs are found at the top of the Expansion Board, as shown below. These inputs  
are numbered 9 through 16. (Note that the digital outputs on the main board of the Universal Monitor  
are numbered 1 - 8.)  
OUTPUT TERMINAL BLOCKS - Note numbering keys above terminal blocks;  
outputs are numbered from left (9) to right (16)  
USE COPPER (CU) CONDUCTORS ONLY.  
Numbering  
POWER INPUT  
RELAY OUTPUTS  
keys  
D6  
WARNING  
!
!
“RISK OF ELECTRIC SHOCK” - Hazardous voltage may be present. More than one  
disconnect switch may be required to de-energize the equipment before servicing.  
CAUTION  
The Expansion Board is designed for use on properly grounded (earthed) 24VAC Class 2  
power, 50Hz or 60Hz. The ground wire for the power lead must be wired to the earth ground  
terminal (stud located next to the 24VAC terminal block). This equipment is intended to be  
installed by a qualified and certified electrician who must review and approve customer-  
supplied wiring and circuit breakers, verify correct input and grounded (earthed) connections  
to ensure compliance with technical standards and national and local electrical codes.  
Segregate and install separate electrical conduits for non-class 2 circuits in accordance with  
local building codes.  
Each output may be wired according to whether you want the output to be Normally Open or Nor-  
mally Closed. The Expansion Board outputs are Form C relay contacts, each with three terminals.  
There are two ways to wire the outputs, as shown in Figure 11.  
• One wire of the two-wire connection should always be connected to the middle terminal.  
• The second wire may be connected to either the N.C. terminal or the N.O. terminal, depending on  
how whether you want the contact to be closed or open during a power failure:  
• Connect to the N.C. terminal if you want the path to be CLOSED during a power failure, or  
• Connect to the N.O. terminal if you want the path to be OPEN during a power failure.  
Your choice for wiring the output contacts also determines how to set the fail-safe DIP switches for  
Figure 11 Form C output contact wiring  
N.C.  
N.O.  
N.C.  
N.O.  
Wire connected  
to N.C. terminal:  
Relay is CLOSED  
on power failure  
Wire connected  
to N.O. terminal:  
Relay is OPEN  
on power failure  
One wire MUST  
be connected to  
middle terminal  
To connect an output:  
1. Disconnect electrical power from the Expansion Board.  
2. If necessary, remove a conduit knockout to permit wire entry into the Expansion Board enclosure.  
3. Bring the wire(s) into the Expansion Board enclosure through a conduit knockout or access slot.  
4. Loosen the appropriate screw and slip the stripped end of the wire into the terminal block.  
5. Tighten the screw until it holds the wire snugly.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Wiring and Connections - Optional Expansion Board  
5.2.3 Setting the Digital Output DIP Switches  
Each digital output on the optional Expansion Board has an associated DIP switch that can deter-  
mine its operation in the event of loss of communication with the Universal Monitor or loss of power.  
When the Universal Monitor calls for an Expansion Board output to be ON, it sends a command to the  
Expansion Board to turn the output to the ON state; this is signified by the output LED being ON.  
The behavior of the output when it is ON is determined by the position of the DIP switch.  
The DIP switches for the outputs are on a switch bank on the right side of the Expansion Board, as  
shown below. Each switch corresponds to an output on the board in order from left to right—for exam-  
ple, DIP switch 1 corresponds to Output 9; DIP switch 2 corresponds to Output 10.  
Optional  
Expansion  
USE COPPER (CU) CONDUCTORS ONLY.  
Board  
POWER INPUT  
RELAY OUTPUTS  
D6  
V1  
V3  
V7  
V9  
V13  
V15  
EIA485 + (to UM-)  
0V  
S4 S3 S2 S1  
EIA485 - (to UM+)  
Digital output  
DIP switches  
K1  
K2  
K3  
K4  
K5  
K6  
K7  
K8  
OUT2  
OUT6  
OUT7  
OUT8  
DEFAULT SETTINGS FOR USE WITH UNIVERSAL MONITOR  
Tables 10 and 11 show how to set the DIP switch for each output based on how the output is wired  
(see 5.2.2 - Connecting Digital Outputs) and how you want it to perform during normal operation,  
when communication with the Universal Monitor is lost or when power fails.  
NOTE  
After a loss of communications with the Universal Monitor, there is a time delay—about five  
minutes—before the Expansion Board changes the state of an output.  
Table 10 DIP switch setting - outputs wired as Normally Closed (N.C.)  
State of Output When:  
N.C.  
N.O.  
If Output  
DIP Switch  
is:  
Light is  
ON  
Light is  
Communication  
with UM is Lost  
Power  
Fails  
OFF  
Wire connected  
to N.C. terminal  
Up (ON)  
Closed  
Open  
Open  
Closed  
Closed  
Closed  
Closed  
Down (OFF)  
Closed  
Table 11  
DIP switch setting - outputs wired as Normally Open (N.O.)  
State of Output When:  
N.C.  
N.O.  
If Output  
DIP Switch  
is:  
Light is  
ON  
Light is  
Communication  
with UM is Lost  
Power  
Fails  
OFF  
Closed  
Open  
Wire connected  
to N.O. terminal  
Up (ON)  
Open  
Open  
Open  
Open  
Open  
Down (OFF)  
Closed  
The Expansion Board comes from the factory with all digital output DIP switches in the OFF position  
(normally open). The DIP switch setting for each digital output can be changed to ON (normally closed).  
To change the state of any output to the factory default of NO (Normally Open) or to NC (Normally  
Closed), move each switch to the appropriate position:  
• Move the switch down to the OFF position for NO (Normally Open)—the default setting.  
• Move the switch up to the ON position for NC (Normally Closed).  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Wiring and Connections - Optional Expansion Board  
5.3  
Connect to the Universal Monitor  
Two steps are required to establish connection between the optional Expansion Board and the Uni-  
versal Monitor.  
5.3.1 Connect EIA485 Connectors to Main Board  
To connect the optional Expansion Board to the Universal Monitor:  
1. Turn OFF electrical power to the Universal Monitor and disconnect power from the Expansion  
Board.  
2. If necessary, remove a conduit knockout to permit wire entry into each enclosure.  
3. Bring the wire(s) into each enclosure through a conduit knockout or access slot.  
4. Loosen the appropriate screw and slip the stripped end of the wire into the terminal block,  
connecting the cables as shown in the figure below):  
• Connect the Universal Monitor 485 connector UM- to Expansion Board connector EIA485+.  
• Connect the Universal Monitor 485 connector UM+ to Expansion Board connector EIA485-.  
OPTIONAL EXPANSION BOARD  
UNIVERSAL MONITOR  
EIA485 connector  
EIA485 connector  
UM-  
Connect  
UM- to  
POWER INPUT  
EIA485+  
UM+  
4
TB10: COMMS  
(TOP)  
+
D6  
422  
(BOTTOM)  
+
EIA485+  
Connect  
UM+ to  
EIA485-  
EIA485 + (to UM-)  
0V  
S4 S3 S2 S1  
EIA485 - (to UM+)  
EIA485-  
5. Tighten each screw until it holds the wire snugly.  
5.3.2 Enable the Connection via Firmware  
After making the cable connections described in the previous section, you must specify the Expansion  
Board as connected using either the LCD or Service Terminal Interface.  
For instructions, refer to the appropriate section:  
• Service Terminal Interface (see A.6.8 - Connect Expansion Board)  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Overview of Menus  
6.0 OVERVIEW OF MENUS  
There are two ways to access the Universal Monitor: the LCD on the front of the enclosure and the  
Service Terminal Interface, which is accessible through any computer using a communications pro-  
gram. Many viewing and configuration tasks can be performed through either interface, but some are  
available only through the Service Terminal Interface.  
• Step-by-step instructions for all functions appear in Sections 7.0 through 9.0. These instructions  
use examples of LCD screens to illustrate most functions, except those not available via the LCD.  
• Examples of all Service Terminal Interface screens appear in Appendix A - Service Terminal  
Interface, along with instructions on how to connect to the Service Terminal Interface.  
Table 12 lists all Universal Monitor functions and shows whether they can be performed through the  
LCD interface and where to find information.  
Table 12 Guide to Universal Monitor functions  
Can be performed via:  
Service  
Where to find:  
Instructions on Service Terminal  
Function  
VIEW STATUS FUNCTIONS  
LCD  
Terminal  
using function  
screen examples  
SILENCE ALARM & BACK UP LOGS FUNCTIONS  
Silence Alarm (On the LCD, press any key to silence an alarm)  
SYSTEM & CONTROL FUNCTIONS  
Pager Setup - Pager Number & PIN  
Pager Setup - Communications Check  
Modem Setup - Initialization String  
Setup System Info  
Setup Serv Ph Num - Enter Phone Number  
Setup Serv Ph Num - Communications Check  
Initiate Remote Alarm Test  
Setup Exp Board - Optional Expansion Board  
Clear Alarms & Logs  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Overview of Menus  
6.1  
6.2  
Opening Screen Overview  
The Universal Monitor displays the Opening Screen at startup, as shown in Figure 12.  
• If any alarms are active, the Current Alarm screen appears. (Pressing any key on the LCD keypad  
will silence the audible alarm.)  
• If any analog input sensors are connected, the LCD screen will alternately display the Opening  
Screen and a screen showing the analog value of each sensor.  
If no alarms are present, the Main Menu appears.  
Main Menu Overview  
The Main Menu offers access to all functions within the panel. As shown in Table 13, the functions  
are organized into three sections with step-by-step instructions.  
Table 13 Primary Functions Overview  
Section  
Description  
7.0 - View Status Options  
(both LCD and Service  
Terminal Interface)  
These features are available to all users. This permits all personnel to check the  
status of any monitored equipment or location. From this menu, any user may:  
• View current monitoring data—active alarms and the status of inputs and outputs  
• View data stored in alarm, event and trend logs  
• View pager numbers  
8.0 - Silence Alarm & Backup These features—available via the Service Terminal Interface only—allow users to:  
Log Files (Service  
Terminal Interface only)  
• Silence the audible alarm  
• Back up the alarm, event and trend logs  
9.0 - System and Control  
Options (some functions  
available via Service  
These options require a password. Authorized users may:  
• Configure the Universal Monitor  
• Override automatic control of outputs to force an output ON or OFF  
• Clear active alarms and delete all records in the alarm, event and trend logs  
Terminal Interface only)  
6.3  
LCD Menu Overview  
Figure 12 shows an overview of the initial screens available through the LCD interface. For compa-  
rable information about the Service Terminal Interface screens, see A.3 - Overview of Menus.  
Figure 12 LCD Menu overview  
Opening Screen  
UNIVERSAL MONITOR  
DD-MON-YY HR:MM:SS  
VX.XXX.X  
PRESS =STATUS/SETUP  
(If any alarms detected)  
Current Alarm screen  
Main Menu  
VIEW STATUS  
SYSTEM AND CONTROL  
=NEXT  
=SELECT  
“View Status” selected  
> VIEW STATUS  
“System & Control” selected  
VIEW STATUS  
> SYSTEM AND CONTROL  
See Section  
See Section  
SYSTEM AND CONTROL  
=NEXT  
=SELECT  
=NEXT  
=SELECT  
View Status Menu  
(All users - no password)  
VIEW ACTIVE ALARMS  
VIEW ALARM LOG  
System & Control Menu  
(Password required)  
SETUP SYSTEM  
See Section  
See Section  
MANUAL OUTPUT CTRL  
CLEAR ALARMS & LOGS  
VIEW EVENT LOG  
VIEW TREND LOG  
VIEW INPUT STATUS  
VIEW OUTPUT STATUS  
VIEW PAGER NUMBERS  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
View Status Options  
7.0 VIEW STATUS OPTIONS  
NOTE  
For ease of understanding, this section uses the LCD interface to illustrate most instructions,  
except for features that are available only through the Service Terminal Interface. All Service  
Terminal Interface screens appear in Appendix A - Service Terminal Interface.  
The View Status menu allows any user to view currently active alarms, monitoring data stored in the  
alarm, event and trend logs, the status of all inputs and outputs, and the four pager numbers. The  
arrows are used to scroll through the menu. The Enter key is used to select the menu item.  
This section presents step-by-step instructions for each of the following options:  
• View Active Alarms  
• View Alarm Log  
• View Event Log  
• View Trend Log  
• View Input Status  
• View Output Status  
• View Pager Numbers  
Figure 13 shows the main options available from the View Status menu.  
Figure 13 Menu overview - View Status menu  
Opening Screen  
UNIVERSAL MONITOR  
DD-MON-YY HR:MM:SS  
VX.XXX.X  
PRESS =STATUS/SETUP  
Main Menu  
>VIEW STATUS  
SYSTEM AND CONTROL  
=NEXT  
=SELECT  
View Status  
VIEW ACTIVE ALARMS  
VIEW ALARM LOG  
VIEW EVENT LOG  
VIEW TREND LOG  
VIEW INPUT STATUS  
VIEW OUTPUT STATUS  
VIEW PAGER NUMBERS  
View Status options  
View Active Alarms  
View Alarm Log  
View Event Log  
View Trend Log  
>ACTIVE ALARM 33/33  
See  
Section  
>ALARM RECORD 99/99  
SENSOR_2 80.0 DEG  
HIGH SETPOINT ALARM  
See  
Section  
>EVENT RECORD 99/99  
PAGER  
UNSUCCESSFUL PAGE  
See  
Section  
SENSOR TO VIEW?  
>SENSOR_1  
SENSOR_2  
See  
Section  
SENSOR_1  
101.0 DEG  
HIGH SETPOINT ALARM  
29-AUG-02  
09:29:10  
07-MAY-02  
10:07:00  
SENSOR_3  
SENSOR_2 ------ DEG  
SENSOR PROBLEM  
SENSOR_4  
MODEM  
INTERNAL FAULT  
OUTPUT01 MAN ON  
CONTACT CLOSED  
INPUT_07 ALARM  
CONTACT OPEN  
29-AUG-02  
09:20:00  
06-MAY-02  
02:47:03  
>TREND LOG 100/100  
SENSOR_1  
NORMAL  
75.4 DEG  
INPUT_08 ALARM  
CONTACT CLOSED  
29-AUG-02  
OUTPUT08 ON  
CONTACT OPEN  
05-MAY-02 05:22:17  
BATTERY  
CHECK BATTERY  
28-AUG-02  
15:45:51  
07:30:00  
View Input Status  
View Output Status  
View Pager Numbers  
INPUT / STATUS  
>SENSOR_1 +80.00 DEG  
SENSOR_2 ------ DEG  
SENSOR_3  
SENSOR_4 +79.50 RH  
INPUT_01 NORMAL  
INPUT_02 ALARM  
INPUT_03 EVENT  
INPUT_04 ALARM  
INPUT_05 ALARM  
INPUT_06 EVENT  
INPUT_07 NORMAL  
INPUT_08 NORMAL  
See  
OUTPUT / STATUS  
>OUTPUT01 ON  
OUTPUT02 OFF  
OUTPUT03 ON  
OUTPUT04 MAN ON  
OUTPUT05 ON  
OUTPUT06 OFF  
OUTPUT07 MAN OFF  
OUTPUT08 ON  
See  
PAGER TO VIEW?  
>PAGER NUMBER 1  
PAGER NUMBER 2  
PAGER NUMBER 3  
PAGER NUMBER 4  
See  
Section  
Section  
Section  
VIEW PAGER NUMBER  
VIEW PAGER PIN  
OUTPUT09 OFF  
8 add’l  
.
.
.
16 additional  
inputs for  
optional  
Expansion  
Board  
outputs  
for  
OUTPUT16 OFF  
INPUT_09 NORMAL  
optional  
.
.
.
PAGER 1 NUMBER  
9,,18005551212##  
PAGER 1 PIN  
Expansion  
Board  
01234567891011121344  
INPUT_24 NORMAL  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
View Status Options  
7.1  
View Active Alarms  
Main Menu  
> VIEW STATUS  
The Active Alarm screen displays all alarms that are occurring, up to a  
maximum of 33.  
SYSTEM AND CONTROL  
=NEXT  
=SELECT  
A Current Alarm screen appears automatically whenever an alarm  
occurs—except during setup. This screen can display only the two most  
recent active alarms. To view any other active alarms, use the View  
Active Alarms feature.  
View Status Menu  
> VIEW ACTIVE ALARMS  
VIEW ALARM LOG  
You may view active alarms at any time by using the following steps:  
VIEW EVENT LOG  
• From the Main Menu, use the arrows ↑ ↓to choose View Status, as  
VIEW TREND LOG  
shown at right, and then press Enter .  
• From the View Status Menu, use the arrows to choose View  
VIEW INPUT STATUS  
VIEW OUTPUT STATUS  
VIEW PAGER NUMBERS  
Active Alarms and press Enter .  
7.1.1 Active Alarms  
Active Alarms  
The Active Alarms screen displays up to 33 records; it shows any active  
> ACTIVE ALARM 33/33  
SENSOR_1 101.0 DEG  
HIGH SETPOINT ALARM  
alarm and any Latched alarm that has not been cleared. Examples of  
alarms include inputs in alarm status, a low battery condition and a  
loss of connection to an analog input. When any alarms are present, the  
Active Alarms screen shows descriptive details for each alarm:  
SENSOR_2 ------ DEG  
SENSOR PROBLEM  
• the source of the alarm (for example, SENSOR_1or BATTERY)  
• the status of an input or output (101.0 DEG)  
INPUT_07 ALARM  
CONTACT OPEN  
• a brief description of the problem (HIGH SETPOINT ALARMor CHECK  
BATTERY  
CHECK BATTERY  
BATTERY)  
If there are no active alarms, the screen displays the message:  
NO ALARMS PRESENT  
Viewing Additional Screens  
There may be up to 33 records of alarm data.  
• To view additional records, use the arrows .  
• To return to the previous screen, press the ESC key.  
Clearing Active Alarms  
To clear all active alarms, see 9.12 - Clear Alarms & Logs. Alarm records are stored in the Alarm  
Log.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
View Status Options  
7.2  
View Alarm Log  
Main Menu  
> VIEW STATUS  
The Alarm Log contains up to 99 records of alarms that have occurred.  
Records are added to this log as alarms occur.  
SYSTEM AND CONTROL  
=NEXT  
=SELECT  
To view the Alarm Log:  
• From the Main Menu, use the arrows to choose View Status,  
View Status Menu  
then press Enter ↵ .  
VIEW ACTIVE ALARMS  
> VIEW ALARM LOG  
VIEW EVENT LOG  
• From the View Status Menu, use the arrows to choose View  
Alarm Log, then press Enter .  
VIEW TREND LOG  
7.2.1 Alarm Log  
VIEW INPUT STATUS  
VIEW OUTPUT STATUS  
VIEW PAGER NUMBERS  
The Alarm Log screen displays up to 99 records showing alarm data,  
including input alarms and other conditions, such as loss of power or  
low battery. If the log contains any alarm records, the Alarm Log screen  
displays details for each alarm:  
Alarm Log  
> ALARM RECORD 99/99  
• the source of the alarm (for example, SENSOR_2or MODEM)  
• the status of an input or output (80.0 DEG)  
• a brief description of the problem (HIGH SETPOINT ALARMor INTER-  
SENSOR_2  
80.0 DEG  
HIGH SETPOINT ALARM  
29-AUG-02 09:29:10  
NAL FAULT)  
• the date and time the alarm occurred  
MODEM  
INTERNAL FAULT  
29-AUG-02 09:20:00  
Table 14 shows conditions that the alarm log records for digital inputs  
and analog inputs and in the panel itself.  
INPUT_08 ALARM  
CONTACT CLOSED  
29-AUG-02 07:30:00  
Table 14 Alarm log conditions  
SOURCE  
CONDITIONS ALARM  
RECORDED NORMAL  
Digital Input  
Analog Input  
HIGH SETPOINT ALARM  
LOW SETPOINT ALARM  
Panel  
LOSS OF POWER  
LOW BATTERY  
CHECK BATTERY  
RETURN TO NORMAL  
SENSOR PROBLEM (denoted by dashes ------) BATTERY UNPLUGGED  
ALARM SILENCED  
MODEM INTERNAL FAULT  
ALARMS CLEARED  
EXP BRD LOSS OF COMM  
EXP BRD RESTORE COMM  
If there are no alarms in the log, the screen displays the message:  
NO ALARMS  
Viewing Additional Screens  
There may be up to 99 records of alarm data.  
• To view additional records, use the arrows .  
• To return to the previous screen, press the ESC key.  
7.2.2 Backing Up the Alarm Log (Service Terminal Interface only)  
The alarm log is stored as a file in the Universal Monitor; it can hold no more than 99 records. When  
the log is full, the oldest records are deleted from the end of the file as new alarm records are added at  
the beginning.  
You may back up the alarm log file to a remote computer using the Service Terminal Interface, as  
To delete all records in the alarm log, see 9.12 - Clear Alarms & Logs.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
View Status Options  
7.3  
View Event Log  
Main Menu  
> VIEW STATUS  
In addition to alarms, the Universal Monitor tracks other changes in  
the Event Log to assist users with verifying operational and trouble-  
shooting problems. Events reflect changes in the status of an input that  
is defined as an event or the change of state of an output (i.e., manually  
forced ON or OFF). Other events may be informational, such as a user  
login or an unsuccessful page attempt. The Event Log contains up to  
99 records of events, which are added as they occur.  
SYSTEM AND CONTROL  
=NEXT  
=SELECT  
View Status Menu  
VIEW ACTIVE ALARMS  
VIEW ALARM LOG  
> VIEW EVENT LOG  
VIEW TREND LOG  
To view the Event Log:  
• From the Main Menu, use the arrows to choose View Status,  
then press Enter ↵ .  
• From the View Status Menu, use the arrows to choose View  
VIEW INPUT STATUS  
VIEW OUTPUT STATUS  
VIEW PAGER NUMBERS  
Event Log, then press Enter .  
Event Log  
7.3.1 Event Log  
> EVENT RECORD 99/99  
PAGER  
UNSUCCESSFUL PAGE  
The Event Log screen displays up to 99 recent events. If the log con-  
tains any event records, the Event Log screen displays details for each  
event:  
07-MAY-02 10:07:00  
OUTPUT01 MAN ON  
CONTACT CLOSED  
• the event source (for example, PAGERor OUTPUT01)  
06-MAY-02 02:47:03  
• the status of an input or output (MAN ON)  
OUTPUT08 ON  
CONTACT OPEN  
05-MAY-02 05:22:17  
• a brief description of the event (UNSUCCESSFUL PAGEor CONTACT  
CLOSED)  
• the date and time the event occurred  
Table 15 shows conditions that the event log records for inputs and outputs and in the panel itself.  
Table 15 Event log conditions  
SOURCE  
Digital Input  
Analog Input  
Digital Output  
Panel  
CONDITIONS  
RECORDED  
EVENT  
NORMAL  
HIGH SETPOINT EVENT  
LOW SETPOINT EVENT  
RETURN TO NORMAL  
SENSOR PROBLEM  
MAN ON  
MAN OFF  
AUTO  
ALARMS CLEARED  
ALARM SILENCED  
DIAL OUT TEST PASSED  
DIAL OUT TEST FAILED  
UNSUCCESSFUL PAGE  
MODEM RESET  
HW MAN ON  
(denoted by dashes ------) ON  
OFF  
TIME & DATE SET  
USER LOGIN  
If there are no records in the log, the screen displays the message:  
NO EVENTS  
Viewing Additional Screens  
There may be up to 99 records of event data.  
• To view additional records, use the arrows .  
• To return to the previous screen, press the ESC key.  
7.3.2 Backing Up the Event Log (Service Terminal Interface only)  
The event log is stored as a file in the Universal Monitor; it can hold no more than 99 records. When  
the log is full, the oldest records are deleted from the end of the file as new event records are added at  
the beginning.  
You may back up the event log file to a remote computer using the Service Terminal Interface, as  
To delete all records in the event log, see 9.12 - Clear Alarms & Logs.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
View Status Options  
7.4  
View Trend Log  
Main Menu  
> VIEW STATUS  
The Universal Monitor takes readings of configured analog input sen-  
sors at regular intervals and stores them in four separate trend logs,  
one for each sensor. The time interval is 30 minutes. Each log contains  
up to 100 records.  
SYSTEM AND CONTROL  
=NEXT  
=SELECT  
Follow these steps to select a sensor and view its trend log:  
View Status Menu  
VIEW ACTIVE ALARMS  
VIEW ALARM LOG  
7.4.1 Select a Sensor  
VIEW EVENT LOG  
> VIEW TREND LOG  
To select a sensor:  
• From the Main Menu, use the arrows to choose View Status,  
then press Enter ↵ .  
• From the View Status Menu, use the arrows to choose View  
VIEW INPUT STATUS  
VIEW OUTPUT STATUS  
VIEW PAGER NUMBERS  
Trend Log, then press Enter .  
• From the Sensor Selection Menu, use the arrows to choose the  
sensor you want to view—Sensor_1 in the example at right—and  
press Enter .  
Select Sensor Menu  
SENSOR TO VIEW?  
> SENSOR_1  
SENSOR_2  
7.4.2 View a Trend Log  
=NEXT =SELECT  
SENSOR_3  
SENSOR_4  
The Trend Log screen displays up to 100 records for the selected sensor.  
If the log contains records, the screen displays details for each reading:  
• the name of the selected sensor (for example, SENSOR_1)  
• the reading (75.4 DEG)  
Trend Log  
> TREND LOG 100/100  
SENSOR_1  
NORMAL  
28-AUG-02 15:45:51  
75.4 DEG  
• a brief description of the reading status (NORMAL)  
• the date and time of the reading  
Table 16 shows conditions that the trend log records for analog inputs.  
Each analog input has its own trend log.  
SENSOR_1  
LOW SETPOINT EVENT  
28-AUG-02 15:15:51  
70.5 DEG  
Table 16 Trend log conditions  
SENSOR_1  
79.9 DEG  
RETURN TO NORMAL  
28-AUG-02 14:45:21  
SOURCE  
Analog Input  
LOW SETPOINT ALARM  
LOW SETPOINT EVENT  
HIGH SETPOINT ALARM  
HIGH SETPOINT EVENT  
RETURN TO NORMAL  
CONDITIONS  
RECORDED  
NORMAL  
SENSOR PROBLEM (denoted by dashes ------)  
If there are no records in the log, the screen displays the message:  
NO TRENDS  
Viewing Additional Screens  
There may be up to 100 records of trend data for the selected sensor.  
• To view additional records, use the arrows .  
• To return to the previous screen, press the ESC key.  
7.4.3 Backing Up the Trend Log (Service Terminal Interface only)  
The four trend logs are stored as files in the Universal Monitor, with a maximum of 100 records per  
sensor. When a log is full, the oldest records are deleted from the end of the file as new trend records  
are added at the beginning.  
You may back up each trend log file to a remote computer using the Service Terminal Interface, as  
To delete all records in the trend logs, see 9.12 - Clear Alarms & Logs.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
View Status Options  
7.5  
View Input Status  
Main Menu  
The Input Status option allows you to view the current status of all  
inputs: the four analog sensor inputs and the eight digital inputs. If the  
optional Expansion Board is used, the additional 16 digital inputs can  
also be viewed.  
> VIEW STATUS  
SYSTEM AND CONTROL  
=NEXT  
=SELECT  
To view the Input Status:  
View Status Menu  
• From the Main Menu, use the arrows to choose View Status,  
then press Enter ↵ .  
• From the View Status Menu, use the arrows to choose View  
VIEW ACTIVE ALARMS  
VIEW ALARM LOG  
VIEW EVENT LOG  
VIEW TREND LOG  
Input Status, then press Enter .  
> VIEW INPUT STATUS  
VIEW OUTPUT STATUS  
VIEW PAGER NUMBERS  
7.5.1 Input Status  
The Input Status screen displays the status of each analog sensor and  
digital input.  
Input Status  
Analog Sensor Inputs  
INPUT / STATUS  
> SENSOR_1 +80.00 DEG  
SENSOR_2 ------ DEG  
SENSOR_3  
The following details are displayed for analog sensor inputs:  
• the name of the analog sensor input (for example, SENSOR_1)  
• the current reading (+80.00 DEG)—values are updated constantly  
SENSOR_4 +79.50 RH  
INPUT_01 NORMAL  
INPUT_02 ALARM  
INPUT_03 EVENT  
INPUT_04 ALARM  
INPUT_05 ALARM  
INPUT_06 EVENT  
INPUT_07 NORMAL  
INPUT_08 NORMAL  
INPUT_09 NORMAL  
INPUT_10 ALARM  
INPUT_11 EVENT  
INPUT_12 ALARM  
INPUT_13 ALARM  
INPUT_14 EVENT  
INPUT_15 NORMAL  
INPUT_16 NORMAL  
INPUT_17 NORMAL  
INPUT_18 ALARM  
INPUT_19 EVENT  
INPUT_20 ALARM  
INPUT_21 ALARM  
INPUT_22 EVENT  
INPUT_23 NORMAL  
INPUT_24 NORMAL  
while being viewed  
There are three possible states for an analog input, as shown in  
Table 17 Analog input states  
State  
Description  
Reading—-for example, +80.00 DEG or +79.50 RH  
Dashes (------)  
Functional  
Problem with  
connection  
Not configured Blank  
NOTE  
If the status displays dashes (------), the Universal Monitor  
was unable to take a reading. There may be a connection  
problem.  
If the status is blank, the sensor is not configured as being  
connected.  
Digital Inputs  
The following details appear for digital inputs:  
• the name of the digital input (for example, INPUT_01)  
• the current status (NORMAL)—values are updated constantly while  
NOTE: 16 additional inputs  
(INPUT_09 thru INPUT_24)  
for optional Expansion Board  
being viewed  
There are three possible states for a digital input, as shown in Table 18.  
Table 18 Digital input states  
State  
Description  
NORMAL In normal state  
ALARM  
EVENT  
In alarm status (for an input configured as alarmable)  
An event has occurred (for an input configured as an event)  
Viewing Additional Input Data  
All input data may be viewed by scrolling beyond the four lines that appear on the LCD at one time:  
• To view all inputs, use the arrows .  
• To return to the previous screen, press the ESC key.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
View Status Options  
7.6  
View Output Status  
Main Menu  
> VIEW STATUS  
The Output Status option allows you to view the current status of all  
eight outputs. If the optional Expansion Board is used, the additional  
eight digital outputs can also be viewed.  
SYSTEM AND CONTROL  
=NEXT  
=SELECT  
To view the Output Status:  
View Status Menu  
• From the Main Menu, use the arrows to choose View Status,  
then press Enter ↵ .  
• From the View Status Menu, use the arrows to choose View  
VIEW ACTIVE ALARMS  
VIEW ALARM LOG  
VIEW EVENT LOG  
VIEW TREND LOG  
Output Status, then press Enter .  
VIEW INPUT STATUS  
> VIEW OUTPUT STATUS  
VIEW PAGER NUMBERS  
7.6.1 Output Status  
The Output Status screen displays the status of each digital output.  
The following details appear for digital outputs:  
Output Status  
• the name of the output (for example, OUTPUT01)  
• the current status (ON)—values are updated constantly while being  
OUTPUT / STATUS  
> OUTPUT01 ON  
OUTPUT02 OFF  
OUTPUT03 ON  
viewed  
There are five possible states for a digital output, as shown in  
OUTPUT04 MAN ON  
OUTPUT05 ON  
OUTPUT06 OFF  
OUTPUT07 MAN OFF  
OUTPUT08 ON  
OUTPUT09 ON  
OUTPUT10 OFF  
OUTPUT11 ON  
Table 19 Digital output states  
State  
Description  
ON  
Automatic  
Automatic  
Controlled by Universal Monitor  
OFF  
OUTPUT12 MAN ON  
OUTPUT13 ON  
OUTPUT14 OFF  
OUTPUT15 MAN OFF  
OUTPUT16 ON  
MAN ON  
Manually ON  
This output forced ON or OFF  
via Manual Output Ctrl menu or  
SiteScan Web  
MAN OFF  
Manually OFF  
Manually ON  
(all outputs)  
All outputs forced ON  
via hardware switch on circuit board  
HW MAN ON  
Viewing Additional Output Data  
NOTE: 8 additional outputs  
(OUTPUT09 thru OUTPUT16)  
for optional Expansion Board  
All output data may be viewed by scrolling beyond the four lines that  
appear on the LCD at one time:  
• To view all outputs, use the arrows .  
• To return to the previous screen, press the ESC key.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
View Status Options  
7.7  
View Pager Numbers  
Main Menu  
> VIEW STATUS  
The Universal Monitor may be set up to dial pager numbers when an  
alarm is detected. Up to four pagers may be configured, as described in  
SYSTEM AND CONTROL  
=NEXT  
=SELECT  
The View Pager Numbers option allows you to view the pager numbers  
and PINs for all configured pagers. Use the following steps to select a  
pager and view its information.  
View Status Menu  
VIEW ACTIVE ALARMS  
VIEW ALARM LOG  
VIEW EVENT LOG  
VIEW TREND LOG  
7.7.1 Select a Pager  
To select a pager:  
VIEW INPUT STATUS  
VIEW OUTPUT STATUS  
> VIEW PAGER NUMBERS  
• From the Main Menu, use the arrows to choose View Status,  
then press Enter ↵ .  
• From the View Status Menu, use the arrows to choose View  
Pager Numbers, then press Enter .  
Pager Selection  
• From the Pager Selection screen, use the arrows to choose the  
pager you want to view—Pager Number 1 in the example at  
right—and press Enter .  
• Use the following steps to view a pager number or PIN for the  
selected pager.  
PAGER TO VIEW?  
> PAGER NUMBER 1  
PAGER NUMBER 2  
PAGER NUMBER 3  
PAGER NUMBER 4  
7.7.2 View a Pager Number  
Pager Menu  
To view a pager number:  
> VIEW PAGER NUMBER  
VIEW PAGER PIN  
• Choose View Pager Number from the Pager Menu and press  
Enter .  
Pager Number  
PAGER 1 NUMBER  
A1,8005551212  
• The Pager Number screen displays the number that is configured  
for the selected pager.  
In the example at right, the telephone number is preceded by A to  
dial an alphanumeric pager and includes a comma (,) to pause two  
seconds after dialing “1” before proceeding to dial the area code and  
number. To change this number, see 9.8.3 - Pager Setup - Pager  
• Press ESC to return to the Pager Menu.  
7.7.3 View a Pager PIN  
To view a pager PIN:  
Pager Menu  
• Choose View Pager PIN from the Pager Menu and press  
VIEW PAGER NUMBER  
> VIEW PAGER PIN  
Enter .  
• The Pager PIN screen displays the PIN that is configured for the  
selected pager. To change this number, see 9.8 - Setup System -  
Pager PIN  
PAGER 1 PIN  
01234567891011121344  
• Press ESC to return to the Pager Menu.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Silence Alarm & Backup Log Files (Service Terminal Interface)  
8.0 SILENCE ALARM & BACKUP LOG FILES (SERVICE TERMINAL INTERFACE)  
This section describes two features that are available in the Service Terminal Interface:  
• Silence Alarm  
• Backup Log Files  
8.1  
Silence Alarm (Service Terminal Interface)  
The Silence Alarm menu item allows you to silence the audible alarm and reset the Common Alarm  
Relay output if the common alarm is configured to reset with silence.  
This menu item is available only through the Service Terminal Interface and SiteScan Web connec-  
tion.  
NOTE  
An alarm may also be silenced by pressing any key on the LCD keypad on the front  
of the Universal Monitor. The LCD does not offer Silence Alarm as a menu item.  
To silence the alarm remotely through the Service Terminal Interface:  
• Connect to the Universal Monitor either from a remote computer or through the RS232 port (see  
• At the Main Menu, enter 8 (Silence Alarm).  
• At the Silence Alarm menu, shown below, enter 1 to silence the audible alarm immediately. (To  
exit without silencing the alarm, enter 2 or press the Escape key.)  
Silence Alarm  
SILENCE ALARM  
(Service Terminal Interface only)  
Silence alarm and reset  
common alarm relay if  
common alarm relay is  
configured to reset with  
silence alarm  
1=SILENCE ALARM  
2=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
>ALARM HAS BEEN SILENCED  
• A confirmation message appears: “Alarm has been silenced.”  
NOTE  
Through SiteScan Web, this option is available via the Universal Monitor  
Graphic Screen.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Silence Alarm & Backup Log Files (Service Terminal Interface)  
8.2  
Back Up Log Files (Service Terminal Interface only)  
The Universal Monitor maintains three types of logs—alarm, event and trend—that may be backed  
up to a remote computer.  
This feature is available only through the Service Terminal Interface.  
To back up any of the alarm, event or trend logs:  
1. Connect to the Universal Monitor either from a remote computer or through the RS232 port (see  
2. At the Main Menu, enter 9 (Backup Log Files).  
3. At the Backup Log Files menu, as shown below, enter a number for the type of file you want to  
back up:  
• Enter 1 to back up the Alarm Log  
• Enter 2 to back up the Event Log  
• Enter 3 to back up the Trend Log for the first sensor (Sensor_1)  
• Enter 4 to back up the Trend Log for the second sensor (Sensor_2)  
• Enter 5 to back up the Trend Log for the third sensor (Sensor_3)  
• Enter 6 to back up the Trend Log for the fourth sensor (Sensor_4)  
Backup Log Files - Alarm Log File  
(Service Terminal Interface only)  
BACKUP LOG FILES  
Backup alarm, event and trend log files  
1=BACKUP ALARM LOG FILE  
2=BACKUP EVENT LOG FILE  
3=BACKUP TREND LOG FILE-SENSOR_1  
4=BACKUP TREND LOG FILE-SENSOR_2  
5=BACKUP TREND LOG FILE-SENSOR_3  
6=BACKUP TREND LOG FILE-SENSOR_4  
7=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
4. At the prompt to initiate a backup of the selected log file, enter Y (Yes - begin) or N (No - cancel).  
The current setting appears in brackets—[N] in the following example.  
>INITIATE A BACKUP OF ALARM LOG-YES(Y) OR NO(N)?  
>[N]  
>[  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Silence Alarm & Backup Log Files (Service Terminal Interface)  
NOTE  
®
®
The following instructions refer to the Microsoft Windows HyperTerminal program. These  
steps may vary for other communications programs.  
5. At the top of the HyperTerminal window, shown below, click on Transfer, then on Receive File.  
Enter folder  
Select Xmodem  
Enter filename -  
for example,  
alarm.log  
6. In the Receive File window, as shown above:  
• In the Place Received File in the Following Folder box, enter the name and location of the  
folder where the configuration file should be placed—for example, C:\downloads—or click  
on the Browse button to locate the folder.  
• In the Use Receiving Protocol box, select Xmodem from the drop-down list.  
• Click on the Receive button. (To close the window without backing up the file, click on Close  
or Cancel.)  
7. In the Receive Filename window, enter a name for the log file—Alarm.log in the example above.  
8. When the transfer is complete, a confirmation message appears in the Service Terminal Interface  
window: “Backup Successful.”  
9. The display returns to the Backup Log Files menu. You may choose another type of log file to back  
up (return to Step 3) or press 7 (or Escape) to return to the Main Menu.  
After backing up a log file, you may want to delete all records in the Universal Monitor’s log of that  
type. See 9.12 - Clear Alarms & Logs for details.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System and Control Options  
9.0 SYSTEM AND CONTROL OPTIONS  
NOTE  
For ease of understanding, this section uses the LCD interface to illustrate most instructions,  
except for features that are available only through the Service Terminal Interface. All Service  
Terminal Interface screens appear in Appendix A - Service Terminal Interface.  
The System and Control menu allows you to configure the Universal Monitor—setting up inputs and  
outputs and an input/output matrix to trigger actions, the modem and pagers, and system features  
such as date and time. This menu also provides a vehicle for manually changing the state of an output  
to ON or OFF, clearing active alarms and deleting records from the Universal Monitor’s alarm log,  
event log and trend logs.  
The arrows are used to scroll through the menu. The Enter key is used to select the menu item  
and enter new information. Table 20 shows characters that may be entered in labels and values.  
Table 20 Valid characters for data entry  
Alphanumeric  
Special characters  
A-Z, 0-9  
space [ ] ^ _ ! " # $ % & ( ) * + - / , . ; < = > @  
The System and Control options require a password to prevent unauthorized users from making  
changes to the system.  
This section presents step-by-step instructions for each of the following:  
Login - enter the password  
Setup System - configure inputs, outputs, modem, pagers, system features  
Manual Output Ctrl - manually override automatic control of outputs; release the override  
Clear Alarms & Logs - clear active alarms; delete records from the alarm, event and trend logs  
NOTE  
If an alarm occurs while a user is logged on, the LCD backlight will flash and the audible  
alarm will sound. To obtain specific information about the alarm, you must access the Active  
Alarm screen (see 7.1 - View Active Alarms) or the Alarm Log (see 7.2 - View Alarm Log).  
9.1  
Login  
Main Menu  
Users must enter a password to access any of the system and control  
options. The password consists of four characters (see Table 20 for  
valid characters). (To set up or change the password, see 9.9.1 -  
VIEW STATUS  
> SYSTEM AND CONTROL  
=NEXT  
=SELECT  
To log in:  
Login  
• From the Main Menu, use the arrows to choose System and  
LOGIN  
AAAA  
Control, then press Enter , as shown at right.  
• Use the arrows to choose System and Control, and press  
Enter . The Login menu appears.  
=SELECT =NEXT/END  
• To enter your password:  
• Use the arrows to choose a character.  
• Press Enter to advance to the next character position.  
• When finished, press Enter again.  
System & Control Menu  
> SETUP SYSTEM  
MANUAL OUTPUT CTRL  
CLEAR ALARMS & LOGS  
=NEXT =SELECT  
The System and Control Menu appears next, with these options that  
are described in the following sections:  
• Setup System (Section 9.2 - Section 9.9)  
• Manual Output Ctrl (Section 9.11)  
• Clear Alarms & Logs (Section 9.12)  
NOTE  
If, after logging in, you press the ESC key to return to a previous screen that is not password-  
protected, you must log in again, including entering your password if you wish to access  
password-protected functions.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
System and Control Options  
Figure 14 shows the main options available from the System & Control menu.  
Figure 14 Menu overview - System and Control menu  
Opening Screen  
UNIVERSAL MONITOR  
DD-MON-YY HR:MM:SS  
VX.XXX.X  
PRESS =STATUS/SETUP  
Main Menu  
VIEW STATUS  
>SYSTEM AND CONTROL  
=NEXT  
=SELECT  
Login Screen  
LOGIN  
AAAA  
=SELECT =NEXT/END  
System & Control menu  
System & Control menu  
System & Control menu  
Setup System selected  
Manual Output Ctrl selected  
Clear Alarms&Logs selected  
>SETUP SYSTEM  
SETUP SYSTEM  
SETUP SYSTEM  
MANUAL OUTPUT CTRL  
CLEAR ALARMS & LOGS  
>MANUAL OUTPUT CTRL  
CLEAR ALARMS & LOGS  
MANUAL OUTPUT CTRL  
>CLEAR ALARMS & LOGS  
Setup System menu  
Select Output  
Clear Alarms/Logs menu  
SETUP INPUT  
See  
OVERRIDE OUTPUT  
See  
Section  
CLEAR ACTIVE ALARMS  
CLEAR ALARM LOG  
CLEAR EVENT LOG  
CLEAR TREND LOGS  
See  
SETUP COMMON ALARM  
SETUP SENSOR  
SETUP I/O MATRIX  
SETUP OUTPUT  
Section  
>OUTPUT01  
AUTO  
AUTO  
Section  
OUTPUT02  
.
.
.
OUTPUT16  
AUTO  
SETUP MODEM&PAGERS  
SETUP SYSTEM INFO  
SETUP EXP BOARD  
Override Output  
SELECT OUTPUT01  
CLEAR ACTIVE ALARMS  
ARE YOU SURE? N  
CLEAR ALARM LOG  
ARE YOU SURE? N  
AUTO  
CLEAR EVENT LOG  
ARE YOU SURE? N  
CLEAR TREND LOGS  
ARE YOU SURE? N  
Setup System options  
Setup Input  
Setup Common Alarm  
Setup Sensor  
Setup I/O Matrix  
MAP INPUT TO OUTPUT  
SELECT INPUT  
See  
Section  
RESET COMMON ALARM  
See  
Section  
SELECT SENSOR  
See  
See  
Section  
>INPUT_01 NO-AL-NL  
WITH SILENCE? N  
>SENSOR_1 +80.00 DEG Section  
MAP SENSOR TO OUTPT  
.
INPUT_02 NO-AL-NL  
.
.
.
.
.
SENSOR_4 +79.50 RH  
INPUT_24 NO-AL-NL  
SELECT INPUT  
INPUT_01  
SELECT SENSOR  
SENSOR_1 HIGH STPT  
SETUP INPUT_01  
LABEL: INPUT_01  
NORM OPEN/CLOSE: NO  
ALARM/EVENT: AL  
LATCHED: N  
SETUP SENSOR_1  
CONNECTED : N  
LABEL: SENSOR_1  
UNITS: ___  
INPUT_02  
SENSOR_1 LOW STPT  
.
.
.
.
.
.
INPUT_24  
SENSOR_4 LOW STPT  
4 mA: -999.9  
DELAY: 00:01  
20 mA: +999.9  
OFFSET: +000.0  
ALARM/EVENT: AL  
LATCHED: N  
SELECT OUTPUTS  
MAP TO MAIN BOARD  
MAP TO EXP BOARD  
SELECT OUTPUTS  
MAP TO MAIN BOARD  
MAP TO EXP BOARD  
LOW SETPT: -950.0  
HIGH SETPT: +950.0  
SENSOR DELAY: 00:01  
1
1
OUTPUT MAP  
1 2 3 4 5 6 7 8  
Y N N N N N N N  
1H  
OUTPUT MAP  
1 2 3 4 5 6 7 8  
Y N N N N N N N  
or  
or  
OUTPUT MAP  
0910111213141516  
N N N N N N N N  
1H  
OUTPUT MAP  
0910111213141516  
N N N N N N N N  
Setup Output  
Setup Modem & Pagers  
SELECT OUTPUT  
See  
Section  
SETUP PAGERS  
See  
Section  
>OUTPUT01  
NO  
SETUP MODEM  
OUTPUT02  
NO  
.
.
.
Setup System Info  
Setup Exp Board  
OUTPUT16  
NO  
CHANGE PASSWORD  
CHANGE DATE & TIME  
SETUP SITE ID  
CONNECT BATTERY  
SETUP SERV PH NUM  
FACTORY DEFAULTS  
See  
Section  
IS THE EXPANSION  
BOARD CONNECTED? N  
See  
Section  
CHANGE LABEL  
CHANGE STATE  
SELECT PAGER  
PAGER NUMBER 1  
ENTER INIT STRING  
ATS0=1  
=Y/N  
=END  
.
.
.
PAGER NUMBER 4  
SET PAGER 1 NUMBER  
SET PAGER 1 PIN  
See Figure 15 for details  
on Setup System Info  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System and Control Options  
9.2  
Setup System - Overview  
The Setup System screen displays seven options that allow you to configure input and output  
devices and their relationships, the common alarm, the modem, pagers to be dialed when alarms  
occur, and a variety of system details, such as login password and system date and time:  
• Setup Input  
• Setup Common Alarm  
• Setup Sensor  
• Setup I/O Matrix  
• Setup Output  
• Setup Modem & Pagers  
• Setup System Info  
• Setup Exp Board  
Setup System Menu  
> SETUP INPUT  
SETUP COMMON ALARM  
SETUP SENSOR  
SETUP I/O MATRIX  
=NEXT =SELECT  
SETUP OUTPUT  
SETUP MODEM&PAGERS  
SETUP SYSTEM INFO  
SETUP EXP BOARD  
9.3  
Setup System - Setup Input  
Select Input Menu  
The Universal Monitor has eight digital input points that may be  
configured individually. If the optional Expansion Board is used, an  
additional 16 digital inputs may also be configured. These inputs may  
have a wide variety of Liebert or other manufacturers’ equipment  
connected for monitoring.  
SELECT INPUT  
> INPUT_01 NO-AL-NL  
INPUT_02 NO-AL-NL  
=NEXT  
=SELECT  
INPUT_03 NO-AL-NL  
INPUT_04 NO-AL-NL  
INPUT_05 NO-AL-NL  
INPUT_06 NO-AL-NL  
INPUT_07 NO-AL-NL  
INPUT_08 NO-AL-NL  
INPUT_09 NO-AL-NL  
INPUT_10 NO-AL-NL  
INPUT_11 NO-AL-NL  
INPUT_12 NO-AL-NL  
INPUT_13 NO-AL-NL  
INPUT_14 NO-AL-NL  
INPUT_15 NO-AL-NL  
INPUT_16 NO-AL-NL  
INPUT_17 NO-AL-NL  
INPUT_18 NO-AL-NL  
INPUT_19 NO-AL-NL  
INPUT_20 NO-AL-NL  
INPUT_21 NO-AL-NL  
INPUT_22 NO-AL-NL  
INPUT_23 NO-AL-NL  
INPUT_24 NO-AL-NL  
To configure a digital input:  
Log In and Choose Setup System  
• From the Main Menu, use the arrows to choose System and  
Control, then press Enter (see 9.1 - Login for help).  
• Enter your password at the Login screen.  
• From the System and Control Menu, use the arrows to choose  
Setup System, then press Enter .  
Select a Digital Input to Configure  
• From the Setup System Menu, shown at right, use the arrows ↑ ↓to  
choose Setup Input and press Enter .  
• From the Select Input Menu, choose the input you want—for exam-  
ple, Input_01—and press Enter .  
Table 21 shows the digital input features you may change, along with  
the default settings: you may change the name of the input, define it as  
normally open or closed, and specify it as alarmable or as an event.  
NOTE: INPUT_09 - INPUT_24  
for optional Expansion Board  
• Alarmable inputs may be defined as either Unlatched or Latched.  
• Event status allows you to monitor a digital input’s state—and use a change in state to initiate an  
action through an output, if desired—without triggering an alarm. Events are always Unlatched.  
• You may also specify a time delay before the Universal Monitor responds to an alarm or event.  
Use the steps following Table 21 to change the default settings for any digital input.  
Table 21 Default settings - digital inputs  
Feature  
Default  
INPUT_01  
Other Options  
Any name (up to eight characters)  
NC (Normally closed)  
LABEL  
NORM OPEN/CLOSE  
ALARM/EVENT  
LATCHED  
NO (Normally open)  
AL (Alarmable)  
EV (Event)  
NL (Unlatched) / N (No)*  
00:01 (1 second)  
L (Latched) / Y (Yes)*  
DELAY  
Any time (in minutes and seconds) from 00:00 to 99:59  
* NOTE: Different abbreviations are used to designate a digital input as Latched or Unlatched as shown below.  
Settings - Select Input Menu When configuring an input  
(see Section 9.3)  
NL (Not Latched)  
L (Latched)  
(see Section 9.3.4)  
N (No, not latched)  
Y (Yes, latched)  
Unlatched  
Latched  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
System and Control Options  
9.3.1 Change Label (Name of Input)  
Setup Input Menu  
Each input has a default label (Input_01, Input_02, etc.) that you may  
change to a more descriptive name for ease in recognizing alarms and  
events associated with the input. The label may consist of up to eight  
characters (see Table 20 for valid characters).  
SETUP INPUT_01  
> LABEL: INPUT_01  
NORM OPEN/CLOSE: NO  
ALARM/EVENT: AL  
=NEXT  
LATCHED: N  
=SELECT  
• From the Setup Input Menu, choose Label for the selected  
input—Label: Input_01 in the example at right—and press  
Enter .  
DELAY: 00:01  
• To change the input’s label, which may consist of up to eight char-  
acters:  
Change Label  
CHANGE LABEL  
• Use the arrows to choose a character.  
• Press Enter to advance to the next character position.  
• When finished, press Enter again.  
INPUT_01  
=SELECT =NEXT/END  
9.3.2 Define Input as Normally Open or Normally Closed  
Setup Input Menu  
Each input may be set up as Normally Open (NO) or Normally Closed  
(NC). The default setting for all input points is NO (Normally Open).  
SETUP INPUT_01  
LABEL: INPUT_01  
> NORM OPEN/CLOSE: NO  
ALARM/EVENT: AL  
If you require an input to be a supervised point, define the input as  
Normally Closed (NC).  
=NEXT  
LATCHED: N  
=SELECT  
• From the Setup Input Menu, choose Norm Open/Close, as shown  
DELAY: 00:01  
at right, and press Enter .  
• To change the normal state for this input, use the arrows to  
choose NO (Normally Open) or NC (Normally Closed), then press  
Enter .  
Normally Open / Closed  
IS INPUT NORMALLY  
OPENED OR CLOSED? NO  
=NO/NC  
=END  
9.3.3 Define Input as Alarmable or Event  
Setup Input Menu  
Each digital input may be defined as Alarmable (AL) or as an  
Event (EV).  
SETUP INPUT_01  
LABEL: INPUT_01  
NORM OPEN/CLOSE: NO  
• For a digital input defined as alarmable, the following alarm reac-  
tions occur when the status of the monitored input device changes:  
the LCD flashes, the audible horn sounds, configured pager num-  
bers will be notified and a record is entered in the Alarm Log.  
> ALARM/EVENT: AL  
=NEXT  
LATCHED: N  
=SELECT  
DELAY: 00:01  
• For a digital input defined as an event, the status change is  
recorded in the Event Log.  
Alarmable / Event  
IS INPUT AN ALARM  
OR EVENT? AL  
By default, all digital inputs are set up as AL (Alarmable).  
• From the Setup Input Menu, choose Alarm/Event, as shown at  
=AL/EV  
=END  
right, and press Enter .  
• To change the type of digital input, use the arrows to choose  
AL (Alarmable) or EV (Event), then press Enter .  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
System and Control Options  
9.3.4 Set Up Alarmable Inputs in Latched or Unlatched Mode  
Setup Input Menu  
Alarmable input points may be set up in Latched mode (Y), which  
requires the user to clear the Universal Monitor alarms after an alarm  
has occurred, or Unlatched mode (N), in which alarms will automati-  
cally clear after a return-to-normal state. The default setting for  
alarmable inputs is N (Unlatched). Any input defined as an event is  
automatically Unlatched.  
SETUP INPUT_01  
LABEL: INPUT_01  
NORM OPEN/CLOSE: NO  
ALARM/EVENT: AL  
=NEXT  
=SELECT  
> LATCHED: N  
DELAY: 00:01  
A digital input defined as Latched does not reset automatically after  
an alarm. It will remain in the triggered position even after the moni-  
tored device returns to normal. After an alarm, the user must manu-  
ally reset Latched inputs, as described in 9.12.1 - Clear Active  
Alarms. This also means that any digital outputs linked to a Latched  
digital input will remain triggered until the input is manually reset.  
Latched / Unlatched  
IS ALARM  
LATCHED? N  
=Y/N  
=END  
A digital input defined as Unlatched will automatically track the sta-  
tus of the monitored device. No action by the user is required.  
• From the Setup Input Menu, choose Latched, as shown above  
right, and press Enter .  
• To change this feature, use the arrows to choose Y (Yes -  
Latched) or N (No - Unlatched), then press Enter .  
Message (if input has  
been defined as an event)  
NOTE: Only alarmable input points may be set up as Latched. If you  
attempt to set up an event as Latched, the message shown at right  
appears. Press the ESC key to return to the previous screen to con-  
tinue configuring the digital input.  
LATCH NOT ALLOWED  
WHEN IN EVENT MODE  
The only way to reset latched alarms is by clearing active alarms. This  
step is required to return latched points to their normal state. For  
ESC=BACK  
9.3.5 Set Up Delay Time  
Setup Input Menu  
Each input may be set up with a specified time delay between the  
occurrence of an alarm or event—a monitored device changes state—  
and any response by the Universal Monitor. This feature can prevent  
needless responses to transient conditions.  
SETUP INPUT_01  
LABEL: INPUT_01  
NORM OPEN/CLOSE: NO  
ALARM/EVENT: AL  
=NEXT  
LATCHED: N  
=SELECT  
This delay is the amount of time that must elapse before the Universal  
Monitor acknowledges the change of state in the monitored device and  
takes any further action, such as dialing configured pagers. The  
default time delay is 1 second (displayed as 00 MIN : 01 SEC).  
DELAY: 00:01  
Delay Time  
DELAY TIME BEFORE  
TRIGGER?  
00 MIN : 01 SEC  
=SELECT =NEXT/END  
The time delay applies only when a monitored device changes from its  
normal state—for example, the Universal Monitor detects a closed  
contact that is defined as Normally Open.  
When the monitored device returns to its normal state, the Universal  
Monitor acknowledges the change of state immediately.  
• From the Setup Input Menu, choose Delay, as shown at right, and  
press Enter .  
• To change the time delay in minutes and seconds (in the range of 00:00 to 99:59):  
• For minutes (MIN), press and hold one of the arrow keys scroll through the numbers  
00-99.  
• Press Enter to advance to seconds (SEC).  
• For seconds (SEC), press and hold one of the arrow keys scroll through the numbers 00-59.  
• When finished, press Enter again.  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System and Control Options  
9.4  
Setup System - Setup Common Alarm  
The audible alarm sounds after the Universal Monitor detects an alarm condition in any input that  
has been defined as alarmable, including digital and analog sensor inputs. Once the alarm is silenced,  
there are two options:  
• By default, the common alarm remains energized until the input alarm is cleared.  
• You may change this setting to de-energize the common alarm automatically once the alarm is  
silenced.  
You might want to reset the common alarm with silence if an external alarm—for example, a horn—is  
connected to the common alarm output contacts.  
You might not want to reset the common alarm contacts (let contacts reflect/track alarms) and simply  
silence the audible horn.  
To change the common alarm setting:  
Setup System Menu  
Log In and Choose Setup System  
SETUP INPUT  
> SETUP COMMON ALARM  
SETUP SENSOR  
• From the Main Menu, use the arrows to choose System and  
Control, then press Enter (see 9.1 - Login for help).  
SETUP I/O MATRIX  
• Enter your password at the Login screen.  
• From the System and Control Menu, use the arrows to choose  
=NEXT =SELECT  
SETUP OUTPUT  
SETUP MODEM&PAGERS  
SETUP SYSTEM INFO  
SETUP EXP BOARD  
Setup System, then press Enter .  
Change to Reset (Y) or Not Reset (N)  
• From the Setup System Menu, shown at right, use the arrows ↑ ↓  
to choose Setup Common Alarm and press Enter .  
Reset Common Alarm  
• By default, the common alarm is set up not to reset automatically RESET COMMON ALARM  
WITH SILENCE? N  
when the alarm is silenced (N). To change this setting, use the  
arrows to choose Y (Yes - reset with silence) or N (No - not  
reset), then press Enter .  
=Y/N  
=END  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System and Control Options  
9.5  
Setup System - Setup Sensor  
The Universal Monitor has four analog sensor input points that may be configured individually. The  
panel monitors connected equipment for any 4-20 mA input—for example, temperature and humidity.  
To configure a sensor:  
Setup System Menu  
Log In and Choose Setup System  
SETUP INPUT  
SETUP COMMON ALARM  
> SETUP SENSOR  
• From the Main Menu, use the arrows to choose System and  
Control, then press Enter (see 9.1 - Login for help).  
SETUP I/O MATRIX  
=NEXT =SELECT  
• Enter your password at the Login screen.  
• From the System and Control Menu, use the arrows to choose  
SETUP OUTPUT  
SETUP MODEM&PAGERS  
SETUP SYSTEM INFO  
SETUP EXP BOARD  
Setup System, then press Enter .  
Select a Sensor to Configure  
• From the Setup System Menu, shown at right, use the arrows ↑ ↓  
to choose Setup Sensor and press Enter .  
Select Sensor Menu  
• From the Select Sensor Menu, choose the sensor you want—for  
SELECT SENSOR  
> SENSOR_1 +80.00 DEG  
SENSOR_2 ------ DEG  
=NEXT =SELECT  
example, Sensor_1—and press Enter .  
Table 22 shows sensor features that may be changed, along with the  
default settings. By default, sensor inputs are not connected.  
SENSOR_3  
SENSOR_4 +79.50 RH  
To activate a sensor input, you must specify it as connected and enter  
corresponding values for 4 and 20 mA, as well as high and low set-  
points. Other features that may be altered include the name of the sensor, the abbreviation for the  
units, and defining the sensor as alarmable or as an event.  
• Alarmable sensors may be Latched (Y) or Unlatched (N).  
• Event status allows you to monitor a sensor’s high and low setpoints—and use those setpoints to  
change the status of an output, if desired—without triggering an alarm. Events are always  
Unlatched.  
• You may also specify a time delay before the Universal Monitor responds to an alarm or event.  
Use the steps following Table 22 to change the default settings for any analog sensor input.  
Table 22 Default settings - analog sensor inputs  
Feature  
CONNECTED*  
LABEL  
Default  
N (Not connected)*  
SENSOR_1  
Blank  
Other Options  
Y (Connected)**  
Any name (up to eight characters)  
UNITS  
Any units (up to three characters)  
4 mA  
-999.9  
Can define up to two decimal places—for example, -99.99  
Can define up to two decimal places—for example, +99.99  
Can define up to two decimal places—for example, +00.00  
EV (Event)  
20 mA  
+999.9  
OFFSET  
+000.0  
ALARM/EVENT  
LATCHED  
LOW SETPT  
HIGH SETPT  
SENSOR DELAY  
AL (Alarmable)  
N (Unlatched)  
-0999.9  
Y (Latched)  
Can define up to two decimal places—for example, -999.99  
Can define up to two decimal places—for example, +999.99  
Any time (in minutes and seconds) from 00:00 to 99:59  
+0999.9  
00:01 (1 second)  
* If a sensor is configured as N (Not connected), the display will show an empty reading (blank spaces).  
** If a sensor is configured as Y (Connected) and is functioning properly, the display will show a reading. If the  
connected sensor is not functioning properly, the display will show dashes (------) indicating a problem.  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
System and Control Options  
9.5.1 Identify the Sensor as Connected  
Setup Sensor Menu  
To make use of an analog sensor, you must specify it as Connected (Y).  
By default, analog sensors are Not connected (N).  
SETUP SENSOR_1  
> CONNECTED : N  
LABEL: SENSOR_1  
=NEXT =SELECT  
• From the Setup Sensor Menu, choose Connected, as shown at  
right, and press Enter .  
• To change this feature, use the arrows to choose Y (Yes - Con-  
UNITS: ___  
4 mA: -999.9  
20 mA: +999.9  
OFFSET: +000.0  
ALARM/EVENT: AL  
LATCHED: N  
nected) or N (No - Not connected), then press Enter .  
LOW SETPT: -0999.9  
HIGH SETPT: +0999.9  
SENSOR DELAY: 00:01  
Sensor Connected  
IS THE SENSOR  
CONNECTED? N  
=Y/N  
=END  
9.5.2 Change Sensor Label (Name)  
Setup Sensor Menu  
Each sensor has a default label (Sensor_1, Sensor_2, etc.) that you may  
change to a more descriptive name. The label may consist of up to eight  
characters (see Table 20 for valid characters).  
SETUP SENSOR_1  
CONNECTED : Y  
> LABEL: SENSOR_1  
=NEXT =SELECT  
UNITS: ___  
4 mA: -999.9  
20 mA: +999.9  
OFFSET: +000.0  
ALARM/EVENT: AL  
LATCHED: N  
LOW SETPT: -0999.9  
HIGH SETPT: +0999.9  
SENSOR DELAY: 00:01  
• From the Setup Sensor Menu, choose Label for the selected sen-  
sor—Label: Sensor_1 in the example—and press Enter .  
• To change the sensor’s label, which may consist of up to eight char-  
acters:  
• Use the arrows to choose a character.  
• Press Enter to advance to the next character position.  
• When finished, press Enter again.  
Change Sensor Label  
CHANGE SENSOR LABEL  
LABEL: ROOM TMP  
=SELECT =END  
9.5.3 Change Units Label  
Setup Sensor Menu  
For each sensor, you may use a three-character label to specify mea-  
surement units, such as DEG (see Table 20 for valid characters).  
SETUP SENSOR_1  
CONNECTED : Y  
LABEL: ROOM_TMP  
• From the Setup Sensor Menu, choose Units for the selected sensor  
=NEXT =SELECT  
and press Enter .  
• To enter the units label, which may consist of up to three charac-  
ters:  
> UNITS: ___  
4 mA: -999.9  
20 mA: +999.9  
OFFSET: +000.0  
ALARM/EVENT: AL  
LATCHED: N  
LOW SETPT: -0999.9  
HIGH SETPT: +0999.9  
SENSOR DELAY: 00:01  
• Use the arrows to choose a character.  
• Press Enter to advance to the next character position.  
• When finished, press Enter again.  
Change Units Label  
CHANGE UNITS LABEL  
UNITS: DEG  
=SELECT =NEXT/END  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
System and Control Options  
9.5.4 Change 4 mA Value  
Setup Sensor Menu  
For the 4 mA value, enter the smallest value for the range of the sen-  
sor—for example, 50°F for a temperature sensor with a range of 50°F  
to 90°F.  
SETUP SENSOR_1  
CONNECTED : Y  
LABEL: ROOM_TMP  
=NEXT =SELECT  
UNITS: DEG  
The default value for each sensor is -999.9. Values that can be entered  
range from -999.9 to +999.9.  
> 4 mA: -999.9  
20 mA: +999.9  
To enter a new value:  
OFFSET: +000.0  
ALARM/EVENT: AL  
LATCHED: N  
• From the Setup Sensor Menu, choose 4 mA for the selected sensor  
and press Enter .  
• To change the 4 mA value:  
LOW SETPT: -0999.9  
HIGH SETPT: +0999.9  
SENSOR DELAY: 00:01  
• Use the arrows to choose a character.  
• Press Enter to advance to the next character position.  
• When finished, press Enter again.  
Change 4 mA Value  
CHANGE 4 mA VALUE  
4 mA: +050.0  
=SELECT =NEXT/END  
9.5.5 Change 20 mA Value  
Setup Sensor Menu  
For the 20 mA value, enter the largest value for the range of the sen-  
sor—for example, 90°F for a temperature sensor with a range of 50°F  
to 90°F.  
SETUP SENSOR_1  
CONNECTED : Y  
LABEL: ROOM_TMP  
=NEXT =SELECT  
UNITS: DEG  
The default value for each sensor is +999.9. Values that can be entered  
range from -999.9 to +999.9.  
4 mA: +050.0  
> 20 mA: +999.9  
OFFSET: +000.0  
ALARM/EVENT: AL  
LATCHED: N  
To enter a new value:  
• From the Setup Sensor Menu, choose 20 mA for the selected sen-  
sor and press Enter .  
• To change the 20 mA value:  
LOW SETPT: -0999.9  
HIGH SETPT: +0999.9  
SENSOR DELAY: 00:01  
• Use the arrows to choose a character.  
• Press Enter to advance to the next character position.  
• When finished, press Enter again.  
Change 20 mA Value  
CHANGE 20 mA VALUE  
20 mA: +090.0  
=SELECT =NEXT/END  
9.5.6 Change Offset Value  
Setup Sensor Menu  
For the Offset value, enter an adjustment factor—for example, if the  
sensor reading shows 70°F when the actual temperature is 75°F, the  
offset might be 5°F.  
SETUP SENSOR_1  
CONNECTED : Y  
LABEL: ROOM_TMP  
=NEXT =SELECT  
UNITS: DEG  
The default Offset value for each sensor is +000.0. Values that can be  
entered range from -999.9 to +999.9.  
4 mA: +050.0  
20 mA: +090.0  
To enter a new value:  
> OFFSET: +000.0  
ALARM/EVENT: AL  
LATCHED: N  
• From the Setup Sensor Menu, choose Offset for the selected sensor  
and press Enter .  
• To change the Offset value:  
LOW SETPT: -0999.9  
HIGH SETPT: +0999.9  
SENSOR DELAY: 00:01  
• Use the arrows to choose a character.  
• Press Enter to advance to the next character position.  
• When finished, press Enter again.  
Change Offset Value  
CHANGE OFFSET VALUE  
OFFSET: +005.0  
=SELECT =NEXT/END  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
System and Control Options  
9.5.7 Define Sensor as Alarmable or Event  
Setup Sensor Menu  
Each sensor may be defined as Alarmable (AL) or as an Event (EV).  
SETUP SENSOR_1  
CONNECTED : Y  
LABEL: ROOM_TMP  
=NEXT =SELECT  
UNITS: DEG  
• For a sensor defined as alarmable, the following alarm reactions  
occur when the high-setpoint threshold is crossed: the LCD flashes,  
the audible horn sounds, configured pager numbers will be notified  
and a record is entered in the Alarm Log.  
• For a sensor defined as an event, the high-setpoint occurrence is  
recorded in the Event Log.  
4 mA: +050.0  
20 mA: +090.0  
OFFSET: +005.0  
> ALARM/EVENT: AL  
LATCHED: N  
By default, all sensors are set up as AL (Alarmable).  
LOW SETPT: -0999.9  
HIGH SETPT: +0999.9  
SENSOR DELAY: 00:01  
• From the Setup Sensor Menu, choose Alarm/Event, as shown at  
right, and press Enter .  
• To change the type of sensor, use the arrows to choose  
Alarmable / Event  
IS SENSOR AN ALARM  
OR EVENT? AL  
AL (Alarmable) or EV (Event), then press Enter .  
=AL/EV  
=END  
9.5.8 Set Up Alarmable Sensors in Latched or Unlatched Mode  
Setup Sensor Menu  
Alarmable sensor points may be set up in Latched mode (Y), requiring  
the user to clear the Universal Monitor alarms after an alarm has  
occurred, or Unlatched mode (N), meaning that alarms will automati-  
cally clear after a return-to-normal state. The default setting for  
alarmable sensors is N (Unlatched). Any sensor defined as an event is  
automatically Unlatched.  
SETUP SENSOR_1  
CONNECTED : Y  
LABEL: ROOM_TMP  
=NEXT =SELECT  
UNITS: DEG  
4 mA: +050.0  
20 mA: +090.0  
OFFSET: +005.0  
ALARM/EVENT: AL  
> LATCHED: N  
A sensor defined as Latched does not reset automatically after an  
alarm. It will remain in the triggered position even after the monitored  
sensor returns to normal. After an alarm, the user must manually  
reset Latched sensors, as described in 9.12.1 - Clear Active Alarms.  
This also means that any digital outputs linked to a Latched sensor  
will remain triggered until the sensor is manually reset.  
LOW SETPT: -0999.9  
HIGH SETPT: +0999.9  
SENSOR DELAY: 00:01  
Latched / Unlatched  
IS ALARM  
LATCHED? N  
A sensor defined as Unlatched will automatically track the status of  
the monitored sensor. No action by the user is required.  
• From the Setup Sensor Menu, choose Latched, as shown at right,  
=Y/N  
=END  
and press Enter .  
• To change this feature, use the arrows to choose Y (Yes -  
Latched) or N (No - Unlatched), then press Enter .  
Message (if sensor has  
been defined as an event)  
NOTE: Only alarmable sensors may be set up as Latched. If you  
attempt to set up an event as Latched, the message shown at right  
appears. Press the ESC key to return to the previous screen to con-  
tinue configuring the digital input.  
LATCH NOT ALLOWED  
WHEN IN EVENT MODE  
The only way to reset latched alarms is by clearing active alarms. This  
step is required to return latched points to their normal state. For  
ESC=BACK  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System and Control Options  
9.5.9 Change Low Setpoint  
Setup Sensor Menu  
The Low Setpoint value is typically above the 4 mA value for the sen-  
sor. For example, if the 4 mA value is 50°F, the Low Setpoint might be  
60°F. When the sensor crosses below this value, an alarm or event will  
occur, depending on the sensor configuration.  
SETUP SENSOR_1  
CONNECTED : Y  
LABEL: ROOM_TMP  
=NEXT =SELECT  
UNITS: DEG  
4 mA: +050.0  
20 mA: +090.0  
OFFSET: +005.0  
ALARM/EVENT: AL  
LATCHED: N  
The default Low Setpoint for each sensor is -950.0. Values that can be  
entered range from:  
• the 4 mA value + the Offset value (in the example, 50+5=55)  
to  
> LOW SETPT: +0055.0  
HIGH SETPT: +0999.9  
SENSOR DELAY: 00:01  
• the 20 mA value + the Offset value (in the example, 90+5=95)  
To determine these values, see 9.5.4 - Change 4 mA Value, 9.5.5 -  
Change Low Setpoint  
CHANGE LOW SETPOINT  
To enter a new value:  
• From the Setup Sensor Menu, choose Low Setpt for the selected  
sensor and press Enter .  
• To change the Low Setpoint:  
LOW SETPT: +0060.0  
=SELECT =NEXT/END  
• Use the arrows to choose a character.  
• Press Enter to advance to the next character position.  
• When finished, press Enter again.  
9.5.10 Change High Setpoint  
Setup Sensor Menu  
The High Setpoint value is typically below the 20 mA value for the sen-  
sor. For example, if the 20 mA value is 90°F, the High Setpoint might  
be 85°F. When the sensor crosses above this value, an alarm or event  
will occur, depending on the sensor configuration.  
SETUP SENSOR_1  
CONNECTED : Y  
LABEL: ROOM_TMP  
=NEXT =SELECT  
UNITS: DEG  
4 mA: +050.0  
20 mA: +090.0  
OFFSET: +005.0  
ALARM/EVENT: AL  
LATCHED: N  
The default High Setpoint for each sensor is +950.0. Values that can be  
entered range from:  
• the 4 mA value + the Offset value (in the example, 50+5=55)  
to  
LOW SETPT: +0060.0  
> HIGH SETPT: +0095.0  
SENSOR DELAY: 00:01  
• the 20 mA value + the Offset value (in the example, 90+5=95)  
To determine these values, see 9.5.4 - Change 4 mA Value, 9.5.5 -  
Change High Setpoint  
CHANGE HIGH SETPOINT  
To enter a new value:  
• From the Setup Sensor Menu, choose High Setpt for the selected  
sensor and press Enter .  
• To change the High Setpoint:  
HIGH SETPT: +0085.0  
=SELECT =NEXT/END  
• Use the arrows to choose a character.  
• Press Enter to advance to the next character position.  
• When finished, press Enter again.  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System and Control Options  
9.5.11 Set Up Delay Time  
Setup Sensor Menu  
Each sensor may be set up with a specified time delay between the  
SETUP SENSOR_1  
CONNECTED : Y  
LABEL: ROOM_TMP  
=NEXT =SELECT  
UNITS: DEG  
triggering of a high or low setpoint—a monitored sensor crosses the  
high or low setpoint threshold—and any response by the Universal  
Monitor. This feature can prevent transient conditions from prompting  
unnecessary responses.  
4 mA: +050.0  
20 mA: +090.0  
This delay is the amount of time that must elapse before the Universal  
Monitor acknowledges the change in the monitored sensor and takes  
any further action, such as dialing configured pagers. The default time  
delay is 1 second (displayed as 00 MIN : 01 SEC).  
OFFSET: +005.0  
ALARM/EVENT: AL  
LATCHED: N  
LOW SETPT: +055.00  
HIGH SETPT: +085.00  
SENSOR DELAY: 00:01  
The time delay applies to the triggering of a high or low setpoint and  
also after the monitored sensor returns to its normal state. When the  
monitored device returns to its normal state, the specified time delay  
must elapse before the Universal Monitor acknowledges the return-to-  
normal condition.  
Delay Time  
DELAY TIME BEFORE  
TRIGGER?  
• From the Setup Sensor Menu, choose Sensor Delay, as shown at  
00 MIN : 01 SEC  
=SELECT =NEXT/END  
right, and press Enter .  
• To change the time delay in minutes and seconds (in the range of  
00:00 to 99:59):  
• For minutes (MIN), press and hold one of the arrow keys scroll through the numbers  
00-99.  
• Press Enter to advance to seconds (SEC).  
• For seconds (SEC), press and hold one of the arrow keys scroll through the numbers 00-59.  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System and Control Options  
9.6  
Setup System - Setup I/O Matrix  
The Setup I/O Matrix menu allows you to configure the Universal Monitor’s digital and analog inputs  
to trigger various actions in any or all of the 16 outputs—eight on the main board and another eight if  
the optional Expansion Board is used. Each output can be set up to respond to more than one digital  
or analog input, including the additional 16 inputs available via the optional Expansion Board.  
Almost any mapping combination can be used. For example, you may  
decide to trigger an action in Output03 when Input_01 goes into alarm,  
or you might want to generate an action in Output04 when Sensor_1  
High Setpoint goes into alarm.  
Setup System Menu  
SETUP INPUT  
SETUP COMMON ALARM  
SETUP SENSOR  
> SETUP I/O MATRIX  
To set up the mapping of inputs to outputs:  
=NEXT =SELECT  
SETUP OUTPUT  
Log In and Choose Setup System  
SETUP MODEM&PAGERS  
SETUP SYSTEM INFO  
SETUP EXP BOARD  
• From the Main Menu, use the arrows to choose System and  
Control, then press Enter (see 9.1 - Login for help).  
• Enter your password at the Login screen.  
• From the System and Control Menu, use the arrows to choose  
Map Input/Sensor Menu  
Setup System, then press Enter .  
> MAP INPUT TO OUTPUT  
MAP SENSOR TO OUTPT  
Select Setup I/O Matrix  
=NEXT  
=SELECT  
• From the Setup System Menu, shown at right, use the arrows ↑ ↓to  
choose Setup I/O Matrix and press Enter .  
• Use the following instructions to set up the mapping of each digital  
input or analog sensor input to each output.  
Select Input  
SELECT INPUT  
> INPUT_01  
INPUT_02  
=NEXT  
9.6.1 Set Up Mapping for a Digital Input  
=SELECT  
• Use the arrows ↑ ↓to choose Map Input To Output from the Map  
Input/Sensor Menu, and press Enter .  
• From the Select Input Menu, choose the input you want—for exam-  
INPUT_03  
INPUT_04  
INPUT_05  
INPUT_06  
INPUT_07  
INPUT_08  
INPUT_09  
INPUT_10  
INPUT_11  
INPUT_12  
INPUT_13  
INPUT_14  
INPUT_15  
INPUT_16  
INPUT_17  
INPUT_18  
INPUT_19  
INPUT_20  
INPUT_21  
INPUT_22  
INPUT_23  
INPUT_24  
ple, Input_01—and press Enter .  
Map Input to a Main Board Output  
• From the Select Outputs menu, select Map to Main Board if you  
want to map the selected input to an output on the Universal Mon-  
itor’s main board. These outputs are identified as Outputs 1-8.  
• On the Output Map screen, you may map the selected input to any  
of the eight outputs (1-8)—or to more than one output, if desired.  
The example at right shows Input_01 mapped to Output03.  
To make changes to the mapping:  
• If needed, press Enter to advance to the position directly  
below the output.  
• Use the arrows ↑ ↓to choose Y (Yes - Mapped to this output) or  
N (No - Not mapped), then press Enter .  
• Press Enter to advance to the next position where you want  
to make a change.  
• Use the arrows ↑ ↓to choose Y (Yes - Mapped to this output) or  
Select Outputs  
SELECT OUTPUTS  
> MAP TO MAIN BOARD  
N (No - Not mapped), then press Enter .  
• When finished, press Enter again.  
MAP TO EXP BOARD  
=NEXT  
=SELECT  
Output Map  
1
OUTPUT MAP  
1 2 3 4 5 6 7 8  
N N Y N N N N N  
=Y/N =NEXT/END  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
System and Control Options  
Map Input to Expansion Board Output  
• From the Select Outputs menu, select Map to Exp Board if you  
want to map the selected input to an output on the optional Expan-  
sion Board. These outputs are identified as Outputs 9-16.  
• On the Output Map screen, you may map the selected input to any  
of the eight outputs (9-16)—or to more than one output, if desired.  
The example at right shows Input_01 mapped to Output10.  
Select Outputs  
SELECT OUTPUTS  
MAP TO MAIN BOARD  
> MAP TO EXP BOARD  
=NEXT  
=SELECT  
To make changes to the mapping:  
Output Map  
• If needed, press Enter to advance to the position directly  
1
OUTPUT MAP  
0910111213141516  
N Y N N N N N N  
=Y/N =NEXT/END  
below the output.  
• Use the arrows ↑ ↓to choose Y (Yes - Mapped to this output) or  
N (No - Not mapped), then press Enter .  
• Press Enter to advance to the next position where you want  
to make a change.  
• Use the arrows ↑ ↓to choose Y (Yes - Mapped to this output) or N (No - Not mapped), then  
press Enter .  
• When finished, press Enter again.  
Default Mappings - Digital Inputs to Outputs  
Table 23 shows the default mapping of digital inputs to digital outputs.  
Table 23 Default mapping of digital inputs to digital outputs  
Digital input  
Input_01  
Input_02  
Input_03  
Input_04  
Input_05  
Input_06  
Input_07  
Input_08  
By default, mapped to digital output:  
Output01  
Output02  
Output03  
Output04  
Output05  
Output06  
Output07  
Output08  
NOTE: By default, no Expansion Board inputs are mapped to any outputs.  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System and Control Options  
9.6.2 Set Up Mapping for an Analog Sensor Input  
Map Input/Sensor Menu  
• Use the arrows ↑ ↓to choose Map Sensor To Outpt from the Map  
MAP INPUT TO OUTPUT  
> MAP SENSOR TO OUTPT  
Input/Sensor Menu, and press Enter .  
• From the Select Sensor Menu, choose the input you want—for  
=NEXT  
=SELECT  
example, Sensor_1 High Stpt—and press Enter .  
Map Sensor to Main Board Output  
Select Sensor  
• From the Select Outputs menu, select Map to Main Board if you  
want to map the selected sensor to an output on the Universal  
Monitor main board. These outputs are identified as Outputs 1-8.  
• On the Output Map screen, you may map the selected sensor to any  
of the eight outputs (1-8)—or to more than one output, if desired.  
The example at right shows Sensor_1 High Stpt mapped to  
Output04.  
SELECT SENSOR  
> SENSOR_1 HIGH STPT  
SENSOR_1 LOW STPT  
=NEXT  
=SELECT  
SENSOR_2 HIGH STPT  
SENSOR_2 LOW STPT  
SENSOR_3 HIGH STPT  
SENSOR_3 LOW STPT  
SENSOR_4 HIGH STPT  
SENSOR_4 LOW STPT  
To make changes to the mapping:  
• If needed, press Enter to advance to the position directly  
below the output.  
Select Outputs  
• Use the arrows ↑ ↓to choose Y (Yes - Mapped to this output) or  
SELECT OUTPUTS  
> MAP TO MAIN BOARD  
MAP TO EXP BOARD  
N (No - Not mapped), then press Enter .  
• Press Enter to advance to the next position where you want  
to make a change.  
=NEXT  
=SELECT  
• Use the arrows ↑ ↓to choose Y (Yes - Mapped to this output) or  
N (No - Not mapped), then press Enter .  
Output Map  
• When finished, press Enter again.  
1H OUTPUT MAP  
1 2 3 4 5 6 7 8  
N N N Y N N N N  
Map Sensor to Expansion Board Output  
• From the Select Outputs menu, select Map to Exp Board if you  
want to map the selected sensor to an output on the optional  
Expansion Board. These outputs are identified as Outputs 9-16.  
• On the Output Map screen, you may map the selected sensor to any  
of the eight outputs (9-16)—or to more than one output, if desired.  
The example at right shows Sensor_1 High Stpt mapped to  
Output11.  
=Y/N  
=NEXT/END  
Select Outputs  
SELECT OUTPUTS  
MAP TO MAIN BOARD  
> MAP TO EXP BOARD  
=NEXT  
=SELECT  
To make changes to the mapping:  
• If needed, press Enter to advance to the position directly  
Output Map  
below the output.  
1H OUTPUT MAP  
0910111213141516  
N N Y N N N N N  
• Use the arrows ↑ ↓to choose Y (Yes - Mapped to this output) or  
N (No - Not mapped), then press Enter .  
=Y/N  
=NEXT/END  
• Press Enter to advance to the next position where you want  
to make a change.  
• Use the arrows ↑ ↓to choose Y (Yes - Mapped to this output) or  
N (No - Not mapped), then press Enter .  
• When finished, press Enter again.  
Default Mappings - Analog Inputs to Outputs  
By default, analog inputs are not mapped to any digital output, as shown in Table 24.  
Table 24 Default mapping of analog inputs to digital outputs  
Analog input  
Sensor_1  
Sensor_2  
Sensor_3  
Sensor_4  
By default, mapped to digital output:  
(none)  
(none)  
(none)  
(none)  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
System and Control Options  
9.7  
Setup System - Setup Output  
Setup System Menu  
The Universal Monitor has eight outputs that may be configured indi-  
vidually. If the optional Expansion Board is used, its additional eight  
digital outputs may be renamed. The outputs may have a wide variety  
of Liebert or other manufacturers’ equipment connected for configured  
responses to input alarms and events.  
SETUP INPUT  
SETUP COMMON ALARM  
SETUP SENSOR  
SETUP I/O MATRIX  
=NEXT =SELECT  
> SETUP OUTPUT  
To configure an output:  
SETUP MODEM&PAGERS  
SETUP SYSTEM INFO  
SETUP EXP BOARD  
Log In and Choose Setup System  
• From the Main Menu, use the arrows to choose System and  
Control, then press Enter (see 9.1 - Login for help).  
• Enter your password at the Login screen.  
• From the System and Control Menu, use the arrows to choose  
Select Output Menu  
SELECT OUTPUT  
> OUTPUT01  
OUTPUT02  
=NEXT  
NO  
NO  
Setup System, then press Enter .  
=SELECT  
Select an Output to Configure  
OUTPUT03  
OUTPUT04  
OUTPUT05  
OUTPUT06  
OUTPUT07  
OUTPUT08  
OUTPUT09  
OUTPUT10  
OUTPUT11  
OUTPUT12  
OUTPUT13  
OUTPUT14  
OUTPUT15  
OUTPUT16  
NO  
NO  
NO  
NO  
NO  
NO  
NO  
NO  
NO  
NO  
NO  
NO  
NO  
NO  
• From the Setup System Menu, shown at right, use the arrows ↑ ↓  
to choose Setup Output and press Enter .  
• From the Select Output Menu, choose the output you want—for  
example, Output01—and press Enter .  
Table 25 shows digital output features and default settings. You may  
change the name of any output. In addition, the Universal Monitor’s  
eight outputs may be defined as normally open or closed.  
Use the steps following Table 25 to change the default settings for any  
digital output.  
Table 25 Default settings - digital outputs  
Feature  
Default  
OUTPUT01  
NO (Normally open)  
Other Options  
NOTE: OUTPUT09-OUTPUT16  
for optional Expansion Board  
Any name (up to eight  
characters)  
LABEL  
NORM OPEN/CLOSE  
(Main board only)  
NC (Normally closed)  
9.7.1 Change Label (Name of Output)  
Setup Output Menu  
Each output has a default label (Output01, Output02, etc.) that you  
may change to a more descriptive name. The label may consist of up to  
eight characters (see Table 20 for valid characters).  
> CHANGE LABEL  
CHANGE STATE  
=NEXT  
=SELECT  
• From the Setup Output Menu, as shown at right, use the  
arrows to choose Change Label for the selected output and  
press Enter .  
Change Label  
• To change the output’s label, which may consist of up to eight char-  
acters:  
CHANGE LABEL  
LABEL: OUTPUT01  
=SELECT =NEXT/END  
• Use the arrows to choose a character.  
• Press Enter to advance to the next character position.  
• When finished, press Enter again.  
9.7.2 Define Main Board Output as Normally Open / Closed  
Setup Output Menu  
Each output may be set up as Normally Open (NO) or Normally Closed  
(NC). The default setting for all output points is NO (Normally Open).  
CHANGE LABEL  
> CHANGE STATE  
• From the Setup Output Menu, choose Change State, as shown at  
=NEXT  
=SELECT  
right, and press Enter .  
• To change the normal state for this output, use the arrows to  
choose NO (Normally Open) or NC (Normally Closed), then press  
Enter .  
Change State  
SET TO NORMAL OPEN  
OR NORMAL CLOSE? NO  
=NO/NC  
=END  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
System and Control Options  
9.7.3 Set Expansion Board Output by DIP Switch  
Setup Output Menu  
If you choose Change State from the Setup Output Menu for an  
Expansion Board output (OUTPUT09-16), the screen displays a mes-  
sage that the state must be set by DIP switch, as shown at right.  
CHANGE LABEL  
> CHANGE STATE  
=NEXT  
=SELECT  
Each digital output on the optional Expansion Board has an associated  
DIP switch that can determine its operation in the event of loss of com-  
munication with the Universal Monitor or loss of power.  
Message (if Expansion  
Board output selected)  
To configure a digital output jumper for a loss of power:  
SET BY DIPSWITCH  
ESC=BACK  
• Move the switch down to the “OFF” position (factory default) for  
Normally Open (NO).  
• Move the switch up to the “ON” position for Normally Closed (NC).  
9.7.4 Configure Main Board Output for Loss of Power (“Fail-Safe”)  
Each digital output has an associated jumper that can help prevent undesired effects when the con-  
troller board loses power. For example, without the proper fail-safe jumper setting, a loss of power  
might close a switch that is Normally Open (NO)—perhaps shutting off a fan or closing a valve.  
This fail-safe jumper setting is unrelated to configuring an output as Normally Open (NO) or Nor-  
mally Closed (NC), as described in the previous section, Define Main Board Output as Normally  
To configure a digital output jumper for a loss of power:  
• Set the jumper in the “OFF” position (factory default) to make the output Normally Open (NO).  
• Set the jumper in the “ON” position to make the output Normally Closed (NC).  
For more information, see 4.2.3 - Setting the Digital Output Jumpers.  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System and Control Options  
9.8  
Setup System - Setup Modem & Pagers  
To use the modem and pager features, be sure to connect the phone line connector to a telephone wall  
jack using an RJ11 cord, as described in 4.6.2 - Phone Line Connector.  
9.8.1 Modem Setup - Initialization String  
The Universal Monitor has an on-board modem that offers dial-up access to all LCD functions as well  
as features available only through the Service Terminal Interface (see A.1 - Comparison of Func-  
tions: LCD and Service Terminal Interface). The modem also permits remote notification of  
alarms.  
Supported Modem Settings  
Supported settings vary for different types of access:  
Table 26 Supported modem settings  
For:  
Modem supports:  
Dial-up via terminal 9600 baud, no parity, 8 data bits, 1 stop bit  
Pager access  
9600 baud, even parity, 7 data bits, 1 stop bit and TAPI protocol version 1.8  
For calls involving countries that do not support country code B5 (see Table 28):  
International  
dialing  
• Modem model MT5600SMI is required (model number is on the modem label).  
+GCI=xx (xx is the country code) must be added to the initialization string (see Step 7 in  
this section).  
Default Modem Settings  
Table 27 shows the default settings for modem options.  
Table 27 Default settings - modem  
Feature  
Default  
Other Options  
Any string (up to 40 characters); for international dialing,  
add +GCI=xx, where xx is the country code (except B5  
countries—see Table 28)  
Initialization String (Init String)  
ATS0=1  
Enable Modem Diagnostic Messages N (disable)  
Y (enable)  
Modem Dial Prefix  
ATE0X4DT Any string  
10 seconds Any number (up to 99 seconds)  
Modem Hang Up Delay After a Call  
Configuring the Modem  
To configure the modem:  
Setup System Menu  
Log In and Choose Setup System  
SETUP INPUT  
SETUP COMMON ALARM  
SETUP SENSOR  
SETUP I/O MATRIX  
=NEXT =SELECT  
SETUP OUTPUT  
1. From the Main Menu, use the arrows to choose System and  
Control, then press Enter (see 9.1 - Login for help).  
2. Enter your password at the Login screen.  
3. From the System and Control Menu, use the arrows to choose  
> SETUP MODEM&PAGERS  
SETUP SYSTEM INFO  
SETUP EXP BOARD  
Setup System, then press Enter .  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
System and Control Options  
Select Modem Setup  
Setup System Menu  
4. From the Setup System Menu, shown at right, use the arrows ↑ ↓to  
choose Setup Modem&Pagers and press Enter .  
5. Use the arrows to choose Setup Modem from the Pagers &  
SETUP INPUT  
SETUP COMMON ALARM  
SETUP SENSOR  
SETUP I/O MATRIX  
=NEXT =SELECT  
SETUP OUTPUT  
Modem Menu and press Enter .  
6. The Setup Modem Menu displays the initialization string  
(Init String), which may consist of up to 40 characters (see  
Table 20 for valid characters). The default Init String is ATS0=1.  
> SETUP MODEM&PAGERS  
SETUP SYSTEM INFO  
SETUP EXP BOARD  
International Dialing  
7. To enable international dialing involving countries that do not  
support country code B5 (see Table 28), you must add the  
appropriate country codes to the initialization string using the  
format:  
Pagers & Modem Menu  
SETUP PAGERS  
> SETUP MODEM  
=NEXT  
=SELECT  
+GCI=xx  
where xx is the country code.  
(This also requires the modem model MT5600SMI; the model num-  
ber can be found on the modem label.)  
Setup Modem Menu  
ENTER INIT STRING  
ATS0=1  
Note: For countries that support B5, there is no need to add coun-  
try codes to the init string.  
=NEXT =SELECT  
Table 28 Country codes  
Country  
Argentina  
Code*  
07  
Country  
Finland  
Code*  
FD  
FD  
FD  
FD  
99  
Country  
Italy  
Code*  
FD  
00  
Country  
Philippines  
Code*  
B5  
FD  
FD  
FD  
FD  
FD  
FE  
FD  
B5  
Australia  
Austria  
09  
France  
Japan  
Portugal  
FD  
FD  
B5  
Germany  
Greece  
Korea  
B5  
Slovak Republic  
Spain  
Belgium  
Canada  
Liechtenstein  
Luxembourg  
Mexico  
FD  
FD  
B5  
Hong Kong  
Hungary  
Iceland  
Sweden  
China  
B5  
FD  
FD  
99  
Switzerland  
Taiwan  
Cyprus  
FD  
FD  
FD  
Netherlands  
New Zealand  
Norway  
FD  
7E  
Czech Republic  
Denmark  
Indonesia  
Ireland  
United Kingdom  
United States  
FD  
FD  
* B5 is the default setting—initialization string +GCI=xx is not needed for these countries  
Edit the Init String  
8. To enter or edit the Init String:  
• Use the arrows to choose a character.  
• Press Enter to advance to the next character position.  
• When finished, press Enter again.  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System and Control Options  
9.8.2 Modem Setup - Additional Features (Service Terminal Interface only)  
The Service Terminal Interface offers four additional options for the modem that are not available  
through the LCD interface:  
• Enter Universal Monitor phone number  
• Enable modem diagnostic messages  
• Change modem dial prefix  
• Change modem hang up delay after a call  
To access these options:  
• Connect to the Universal Monitor either from a remote computer or through the RS232 port (see  
• At the Main Menu, enter 0 (zero—Setup System-Login Required).  
• At the Login Menu, enter your password.  
• At the Setup Menu, enter 6 (Setup Modem&Pagers).  
• At the Setup Modem & Pagers menu, shown below, enter 5 to begin configuration.  
Setup Modem & Pagers - Modem Setup  
(Service Terminal Interface only)  
SETUP MODEM&PAGERS  
Input pager and  
modem information  
Select pager or modem  
CURRENT NUMBER  
*******************  
An "A" is required  
as 1st character  
1=PAGER NUMBER 1  
2=PAGER NUMBER 2  
3=PAGER NUMBER 3  
4=PAGER NUMBER 4  
5=MODEM CONFIGURATION  
6=RETURN TO SETUP MENU  
7=RETURN TO MAIN MENU  
for an alpha pager,  
an "N" for a numeric  
pager, and an "M"  
for a remote modem.  
*******************  
SELECT A NUMBER:5  
• At the Change Modem Initialization String prompt, you may press Enter to bypass this option (or  
see 9.8.1 - Modem Setup - Initialization String for instructions on entering the string).  
>CHANGE MODEM INITIALIZATION STRING(40 CHARACTERS MAX).  
>[ATS0=1]  
>[  
>COMMAND SUCCESSFUL  
Enter Universal Monitor Phone Number  
This entry allows you to store the phone number that must be dialed to access the Universal Monitor  
for future reference. This has no effect on the Universal Monitor’s modem settings or functionality—it  
simply places the phone number in an accessible location.  
• At the Universal Monitor Phone Number prompt, enter the phone number for the Universal Mon-  
itor. The current setting appears in brackets []—nothing has been entered in the following exam-  
ple.  
>ENTER UNIVERSAL MONITOR PHONE NUMBER(40 CHARACTERS MAX).  
>[]  
>[  
>COMMAND SUCCESSFUL  
• Press Enter to proceed, or Escape to cancel the entry. If you make a change, a confirmation mes-  
sage appears: “Command Successful.”  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System and Control Options  
Enable Modem Diagnostic Messages  
Enabling modem diagnostics will provide the following additional information about the modem to  
the computer using the Service Terminal Interface:  
Hang-up modem  
Modem model number  
No dial tone  
No carrier  
Busy  
No answer  
Pager checksum error  
Pager pin number error  
Error (indicates incorrect phone number, dial prefix or modem initialization string)  
For alphanumeric pager failures:  
Paging company non answer on 1st  
Paging company non answer on 2nd  
Paging company non answer on Last  
Paging company non answer on Handshake  
• At the Enable Modem Diagnostic Messages prompt, enter Y (Yes - enable) or N (No - disable). The  
current setting appears in brackets—[N] in the following example.  
>ENABLE MODEM DIAGNOSTIC MESSAGES-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
• Press Enter to proceed, or Escape to cancel the entry. If you make a change, a confirmation mes-  
sage appears: “Command Successful.”  
Change Modem Dial Prefix  
• At the Change Modem Dial Prefix prompt, enter the prefix to be dialed. The current setting  
appears in brackets—[ATE0X4DT] in the following example.  
>CHANGE MODEM DIAL PREFIX.  
>[ATE0X4DT]  
>[  
>COMMAND SUCCESSFUL  
• For international dialing involving countries that do not support B5 (see Table 28), add country  
codes to the initialization string using the format +GCI=xx, where xx is the country code.  
(Note: Also requires MT5600SMI modem; model number is on modem label.)  
• Press Enter to proceed, or Escape to cancel the entry. If you make a change, a confirmation mes-  
sage appears: “Command Successful.”  
Change Modem Hang Up Delay After a Call  
• At the Change Modem Hang Up Delay After a Call prompt, enter the number of seconds to delay  
hanging up after a call. The maximum is 99 seconds. The current setting appears in brackets—  
[10] in the following example.  
>CHANGE MODEM HANG UP DELAY AFTER A CALL(99 SEC MAX).  
>[10]  
>[  
>COMMAND SUCCESSFUL  
• Press Enter to proceed, or Escape to cancel the entry. If you make a change, a confirmation mes-  
sage appears: “Command Successful.”  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System and Control Options  
9.8.3 Pager Setup - Pager Number and PIN  
The Universal Monitor may be configured to dial numeric or alphanumeric pagers when an alarm is  
detected. You may enter up to four pager numbers—all configured pagers will be dialed each time an  
alarm occurs. For each configured pager, you must enter the pager number to be dialed and the  
pager’s Personal Identification Number (PIN).  
See 10.1 - Universal Monitor Specifications for supported pager settings.  
The Universal Monitor can send numeric or alphanumeric messages to supported pagers, as shown in  
the following example:  
Alphanumeric pager LIEBERT TEST  
message example INPUT_01 ALARM  
CONTACT CLOSED  
2:07 PM 06/09/04  
Pager company time stamp  
When an alarm is detected, the first pager number is dialed—up to three times, if needed. After a suc-  
cessful page or three dialing attempts, the next pager number is dialed, again with three attempts as  
needed, and so on for all configured pagers.  
Table 29 Pager dialing results  
Result of Page  
Successful  
Action  
Message Generated  
Universal Monitor dials next configured pager.  
Unsuccessful due to:  
Busy signal / no answer /  
no dial tone  
Universal Monitor generates message after all three  
Unsuccessful Page  
redial attempts have failed, dials next configured pager. (Event Log)  
General modem  
communication problem  
Universal Monitor resets modem, generates  
message, redials pager up to three more times.  
Modem Reset  
(Event Log)  
Modem Internal Fault  
(Active Alarm Report,  
Alarm History Log)  
No communication with modem Universal Monitor generates messages, makes no  
(internal hardware problem)  
further dialing attempts.  
To configure a pager:  
Setup System Menu  
SETUP INPUT  
SETUP COMMON ALARM  
SETUP SENSOR  
SETUP I/O MATRIX  
=NEXT =SELECT  
SETUP OUTPUT  
Log In and Choose Setup System  
• From the Main Menu, use the arrows to choose System and  
Control, then press Enter (see 9.1 - Login for help).  
• Enter your password at the Login screen.  
• From the System and Control Menu, use the arrows to choose  
> SETUP MODEM&PAGERS  
SETUP SYSTEM INFO  
SETUP EXP BOARD  
Setup System, then press Enter .  
Select a Pager to Configure  
• From the Setup System Menu, shown at right, use the arrows ↑ ↓  
to choose Setup Modem&Pagers and press Enter .  
• Use the arrows to choose Setup Pagers from the Pagers &  
Pagers & Modem Menu  
> SETUP PAGERS  
SETUP MODEM  
Modem Menu, and press Enter .  
=NEXT  
=SELECT  
• From the Select Pager Menu, choose the pager number you  
want—for example, Pager Number 1—and press Enter .  
Select Pager Menu  
SELECT PAGER  
> PAGER NUMBER 1  
PAGER NUMBER 2  
=NEXT =SELECT  
PAGER NUMBER 3  
PAGER NUMBER 4  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
System and Control Options  
Enter a Pager Number  
Setup Pager Menu  
• From the Setup Pager Menu, choose Setup Pager Number for  
the selected pager—Setup Pager 1 Number in the example at  
right—and press Enter .  
> SET PAGER 1 NUMBER  
SET PAGER 1 PIN  
=NEXT  
=SELECT  
• See Table 30 for guidelines on entering the pager number, which  
may consist of up to 40 characters. To enter the pager number:  
Pager # - Numeric  
• Use the arrows to choose a character.  
• Press Enter to advance to the next character position.  
• When finished, press Enter again.  
ENTER PAGER 1 NUMBER  
N1,8005551212,,,,123  
4567#  
=SELECT =NEXT/END  
Table 30 Guidelines for dialing pagers  
Pager # - Alphanumeric  
ENTER PAGER 1 NUMBER  
A9W18005551212  
Device type  
Required entries  
Example  
Numeric  
pager  
The first character must be “N”.  
N18005551212  
=SELECT =NEXT/END  
Alphanumeric  
pager  
The first character must be “A”.  
A18005551212  
Remote  
modem  
The first character must be “M”.  
M18005551212  
Example  
Device type  
Optional entries  
Use “9” if needed to access an outside  
line—place after first character (N, A or M).  
A918005551212  
Use "W" to wait for a second dial tone  
before dialing if the phone system has two  
dial tones (initial tone and a second tone  
for outside line)—place after “9” (before the  
number to be dialed).  
All types  
of devices  
A9W18005551212  
Use “,” (comma) to pause two seconds.  
N1,8005551212  
Numeric  
pager  
Use “#” as the last character to terminate  
page string if required by paging company. ,,,,1234567#  
N18005551212  
Enter a Pager PIN Number  
Setup Pager Menu  
• From the Setup Pager Menu, choose Setup Pager PIN, as shown  
for Pager Number 1 in the example at right, and press Enter ↵ .  
• To enter the pager PIN, which may consist of up to 20 characters  
SET PAGER 1 NUMBER  
> SET PAGER 1 PIN  
=NEXT  
=SELECT  
(see Table 20 for valid characters):  
• Use the arrows to choose a character.  
• Press Enter to advance to the next character position.  
• When finished, press Enter again.  
Enter Pager PIN  
ENTER PAGER 1 PIN  
01234567891011121314  
=SELECT =NEXT/END  
NOTE  
For international dialing, you might need to add country codes  
in the modem initialization string. See 9.8.1 - Modem Setup -  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System and Control Options  
9.8.4 Pager Setup - Communications Check (Service Terminal Interface only)  
The Service Terminal Interface offers two additional options for pager setup, which are not available  
through the LCD interface:  
• Enable communications check  
• Enter time to perform communications check  
To access these options:  
• Connect to the Universal Monitor either from a remote computer or through the RS232 port (see  
• At the Main Menu, enter 0 (zero—Setup System-Login Required).  
• At the Login Menu, enter your password.  
• At the Setup Menu, enter 6 (Setup Modem&Pagers).  
• At the Setup Modem & Pagers menu, shown below, enter a number (1-4) to select a pager.  
Setup Modem & Pagers - Pager Setup  
(Service Terminal Interface only)  
SETUP MODEM&PAGERS  
Input pager and  
modem information  
Select pager or modem  
CURRENT NUMBER  
*******************  
An "A" is required  
as 1st character  
1=PAGER NUMBER 1  
2=PAGER NUMBER 2  
3=PAGER NUMBER 3  
4=PAGER NUMBER 4  
5=MODEM CONFIGURATION  
6=RETURN TO SETUP MENU  
7=RETURN TO MAIN MENU  
for an alpha pager,  
an "N" for a numeric  
pager, and an "M"  
for a remote modem.  
*******************  
SELECT A NUMBER:1  
• At the Enter Pager Number prompt, you may press Enter to bypass this option (or see 9.8.3 -  
Pager Setup - Pager Number and PIN for instructions on entering the pager number).  
>ENTER PAGER NUMBER(40 CHARACTERS MAX).  
>[]  
>[  
>COMMAND SUCCESSFUL  
• At the Enter Pager PIN Number prompt, you may press Enter to bypass this option (or see 9.8.3 -  
Pager Setup - Pager Number and PIN for instructions on entering the pager PIN).  
>ENTER PAGER PIN NUMBER (20 CHARACTERS MAX).  
>[]  
>[  
>COMMAND SUCCESSFUL  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System and Control Options  
Enable Communications Check  
Enabling this function permits a daily communications test between the Universal Monitor and the  
selected pager. Once each day the Universal Monitor dials the pager at a specified time and sends this  
message: “UNIVERSAL MONITOR COMM CHECK.” (The time of the test is specified at the next  
• At the Enable Communications Check prompt, enter Y (Yes - enable) or N (No - disable). The cur-  
rent setting appears in brackets—[N] in the following example.  
>ENABLE COMMUNICATIONS CHECK-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
• Press Enter to proceed, or Escape to cancel the entry. If you make a change, a confirmation mes-  
sage appears: “Command Successful.”  
Enter Time To Perform Communications Check  
This function schedules the daily communications test between the Universal Monitor and the  
selected pager, as described in the previous section.  
• At the Enter Time To Perform Communications Check prompt, enter the time to initiate the com-  
munications check, using the format HH:MM (hours and minutes in military time), ranging from  
00:00 for midnight to 23:59 for 11:59 p.m. The current setting appears in brackets—[00:00] in the  
following example.  
>ENTER TIME TO PERFORM COMMUNICATIONS CHECK(HH:MM).  
>[00:00]  
>[  
>COMMAND SUCCESSFUL  
• Press Enter to proceed, or Escape to cancel the entry. If you make a change, a confirmation mes-  
sage appears: “Command Successful.”  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System and Control Options  
9.9  
Setup System - Setup System Info  
The Setup System Info options allow users to:  
Change Password—used for access to system setup functions  
Change Date & Time/Automatic Daylight Saving Time—used to set the Universal Monitor’s  
date and time and to enable automatic time change for Daylight Saving Time  
Setup Site ID—the Universal Monitor’s location to differentiate among sites if more than one  
Universal Monitor is in use  
Connect Battery—stops the Universal Monitor battery from backing up the panel  
Backup and Upload Configuration File (Service Terminal Interface only)—permits the  
user to copy the Universal Monitor’s configuration settings and to upload the file to the Universal  
Monitor  
Setup Serv Ph Num—enables alarm notification to the telephone number entered (in addition  
to the four pager numbers).  
Restore Defaults—returns the Universal Monitor to its factory settings  
Perform Firmware Update (Service Terminal Interface only)—changes the Universal Mon-  
itor’s firmware to newest version  
Initiate Remote Alarm Test (Service Terminal Interface only)—used to test auxiliary  
alarm  
To change any Setup System Info features:  
Log In and Choose Setup System  
Setup System Menu  
• From the Main Menu, use the arrows to choose System and  
Control, then press Enter (see 9.1 - Login for help).  
• Enter your password at the Login screen.  
SETUP INPUT  
SETUP COMMON ALARM  
SETUP SENSOR  
SETUP I/O MATRIX  
=NEXT =SELECT  
SETUP OUTPUT  
• From the System and Control Menu, use the arrows to choose  
Setup System, then press Enter .  
SETUP MODEM&PAGERS  
> SETUP SYSTEM INFO  
Select Setup System  
• From the Setup System Menu, shown at right, use the arrows ↑ ↓  
SETUP EXP BOARD  
to choose Setup System Info and press Enter .  
• Use the steps following Figure 15 to access any of the Setup Sys-  
tem Info options.  
Figure 15 offers a quick look at the Setup System Info screens available via the LCD interface.  
Figure 15 Menu overview - Setup System Info menu  
Setup System Info  
SETUP SYSTEM INFO  
CHANGE PASSWORD  
CHANGE DATE & TIME  
SETUP SITE ID  
CONNECT BATTERY  
SETUP SERV PH NUM  
FACTORY DEFAULTS  
Setup System Info options  
Change Password  
CHANGE PASSWORD  
AAAA  
Change Date & Time  
Setup Site ID  
SETUP SITE ID  
AAAAAAAAAAAAAAAAAAAA  
AAAAAAAAAAAAAAAAAAAA  
See  
Section  
CHANGE DATE & TIME  
DAYLIGHT SVG TIME: Y  
18-MAY-02 10:56:30  
See  
Section  
See  
Section  
Connect Battery  
Setup Serv Ph Num  
Factory Defaults  
IS THE BATTERY  
CONNECTED? Y  
See  
Section  
ENTER PHONE NUMBER  
9,,18005551212  
See  
Section  
RESTORE ALL DEFAULTS  
ARE YOU SURE? N  
See  
Section  
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
System and Control Options  
9.9.1 Change Password  
Setup System Info Menu  
A password is required to access the Universal Monitor’s system and  
SETUP SYSTEM INFO  
> CHANGE PASSWORD  
CHANGE DATE & TIME  
=NEXT =SELECT  
control options, as described in 9.1 - Login. The password consists of  
four characters (see Table 20 for valid characters). The default pass-  
word is AAAA.  
SETUP SITE ID  
CONNECT BATTERY  
SETUP SERV PH NUM  
FACTORY DEFAULTS  
Change the Password  
To change the password:  
• From the Setup System Info Menu, use the arrows to choose  
Change Password, then press Enter .  
• To change your password:  
Change Password  
CHANGE PASSWORD  
• Use the arrows to choose a character.  
• Press Enter to advance to the next character position.  
• When finished, press Enter again.  
AAAA  
=SELECT =NEXT/END  
Reset Password to the Factory Default (“AAAA”)  
To reset the password to the factory default of AAAA:  
• Locate DIP switch 1 on the unit’s circuit board (see 1.7 - Controller Board Overview) and move  
all switches to the OFF position (down).  
• Move the second switch to the ON position, then to the OFF position.  
• Move the seventh switch to the ON position, then to the OFF position.  
• Move the eighth switch to the ON position, then to the OFF position.  
The password should now be AAAA.  
9.9.2 Change Date & Time/Automatic Daylight Saving Time  
The Universal Monitor has a built-in real-time clock that is backed up by an encapsulated lithium  
battery and set up to adjust automatically for daylight saving time twice a year. The Setup System  
Info menu allows you to change the date or time or automatic adjustment at any time.  
To change the daylight saving time setting, date or time:  
Setup System Info Menu  
• From the Setup System Info Menu, use the arrows to choose  
Change Date & Time, then press Enter .  
• To change the daylight saving time setting:  
SETUP SYSTEM INFO  
CHANGE PASSWORD  
> CHANGE DATE & TIME  
=NEXT =SELECT  
• To the right of Daylight Svg Time? use the arrows to  
choose Y (Yes - automatically adjust for daylight saving time)  
or N (No), then press Enter .  
SETUP SITE ID  
CONNECT BATTERY  
SETUP SERV PH NUM  
FACTORY DEFAULTS  
• The format of the date and time is DD-MMM-YY HR:MM:SS. To  
change the date or time:  
Change Date & Time  
• Press Enter to advance to the next character position you  
want to change.  
CHANGE DATE & TIME  
DAYLIGHT SVG TIME: Y  
18-MAY-02 10:56:30  
=SELECT =NEXT/END  
• Use the arrows to choose from available entries:  
Date Day (DD)  
0-31  
Month (MMM) JAN-DEC  
Year (YY)  
00-99  
00-23  
Time Hour (HR)  
Minutes (MM) 00-59  
Seconds (SS) 00-59  
• Press Enter to advance to the next character position.  
• When finished, press Enter again.  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
System and Control Options  
9.9.3 Setup Site ID  
Setup System Info Menu  
You may enter a Site ID to identify the Universal Monitor’s location,  
valid characters). The Site ID will appear with each alarm.  
SETUP SYSTEM INFO  
CHANGE PASSWORD  
CHANGE DATE & TIME  
=NEXT =SELECT  
To enter or change the Site ID:  
> SETUP SITE ID  
CONNECT BATTERY  
SETUP SERV PH NUM  
FACTORY DEFAULTS  
• From the Setup System Info Menu, use the arrows to choose  
Setup Site ID, then press Enter .  
• To enter a Site ID:  
• Use the arrows to choose a character.  
Setup Site ID  
• Press Enter to advance to the next character position.  
• If the Site ID is less than 40 characters, you may enter an  
underscore (_) character to indicate the end of the name.  
SETUP SITE ID  
AAAAAAAAAAAAAAAAAAAA  
AAAAAAAAAAAAAAAAAAAA  
=SELECT =NEXT/END  
• When finished, press Enter again.  
9.9.4 Connect Battery  
By default, the Universal Monitor checks the battery and sounds an alarm when the power fails, the  
battery runs low or the battery needs to be checked. The battery’s main purpose is to provide enough  
power to the modem to notify pagers of a power loss.  
NOTE  
The battery will continue to power and provide full operation of the Universal Monitor with the  
exception of powering the analog inputs (sensors). The battery will provide backup for a  
minimum of 10 minutes.  
Using the following procedure to disconnect the battery will disable battery alarm features only. The  
battery itself will continue to provide backup. If battery backup is not desired, the battery must be  
unplugged from the circuit board. This can be done by removing the battery leads from the jumpers  
The default is to connect the battery. However, there may be times that you want to disconnect the  
battery so that it does not provide backup.  
Table 31 shows battery problems that will affect operation.  
Table 31 Battery alarms  
Result of Battery  
Action  
Message Generated  
LOW BATTERY  
Battery falls below a minimum charge.  
Battery will not provide battery backup.  
Battery will not provide battery backup.  
Battery is connected to the circuit board but  
not recognized by the circuit board.  
CHECK BATTERY  
Battery is unplugged from the circuit board.  
Battery will not provide battery backup  
BATTERY UNPLUGGED  
LOSS OF POWER  
Utility power (24VAC) to the circuit board is  
too low to power the board.  
Universal Monitor board will not be  
able to function properly.  
To connect or disconnect the battery:  
Setup System Info Menu  
• From the Setup System Info Menu, use the arrows to choose  
Connect Battery, then press Enter .  
• Use the arrows to choose Y (Yes - the battery is connected) or  
SETUP SYSTEM INFO  
CHANGE PASSWORD  
CHANGE DATE & TIME  
=NEXT =SELECT  
N (No - the battery is not connected), then press Enter .  
SETUP SITE ID  
> CONNECT BATTERY  
SETUP SERV PH NUM  
FACTORY DEFAULTS  
Connect Battery  
IS THE BATTERY  
CONNECTED? Y  
=Y/N  
=END  
70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
System and Control Options  
9.9.5 Backup and Upload Configuration File (Service Terminal Interface only)  
This operation may be performed only through the Service Terminal Interface. It permits the user to  
make a copy of the Universal Monitor’s configuration settings and save it as a file on the computer  
connected through the RS232 port. Should the need arise, the user can upload the configuration file  
from the computer to the Universal Monitor, instead of re-entering the settings manually.  
To access these options:  
1. Connect to the Universal Monitor either from a remote computer or through the RS232 port (see  
2. At the Main Menu, enter 0 (zero—Setup System-Login Required).  
3. At the Login Menu, enter your password.  
4. At the Setup Menu, enter 7 (Setup System Information).  
5. At the Setup System Information Menu, enter 5 (Backup & Upload Configuration File). The  
Backup & Upload Configuration File menu appears, shown below:  
Backup & Upload Configuration File - Backup  
(Service Terminal Interface only)  
BACKUP AND UPLOAD CONFIGURATION FILE  
Backup from panel saves panel configurations  
Upload to panel restores panel configurations  
Select to backup or upload file  
1=BACKUP CONFIGURATION FILE  
2=UPLOAD CONFIGURATION FILE  
3=RETURN TO SETUP SYSTEM INFO MENU  
4=RETURN TO SETUP MENU  
5=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
6. Enter 1 to back up the configuration file from the Universal Monitor to the computer and proceed  
to Step 8,  
OR  
7. Enter 2 to upload the configuration file from the computer to the Universal Monitor and proceed  
to Step 13. NOTE: This will replace the current configuration settings in the Universal Monitor  
with the most recent backup.  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System and Control Options  
Back Up the Configuration File  
8. At the prompt to Initiate a Backup of Configuration File, enter Y (Yes - begin) or N (No - cancel).  
The current setting appears in brackets—[N] in the following example.  
>INITIATE A BACKUP OF CONFIGURATION FILE-YES(Y) OR NO(N)?  
>[N]  
>[  
NOTE  
The following instructions refer to the Microsoft Windows HyperTerminal program. These  
steps may vary for other communications programs.  
9. At the top of the HyperTerminal window, shown below, click on Transfer, then on Receive File.  
Enter folder  
Select Xmodem  
Enter filename -  
for example,  
UMconfig.sav  
10. In the Receive File window, as shown above:  
• In the Place Received File in the Following Folder box, enter the name and location of the  
folder where the configuration file should be placed—for example, C:\downloads—or click  
on the Browse button to locate the folder.  
• In the Use Receiving Protocol box, select Xmodem from the drop-down list.  
• Click on the Receive button. (To close the window without backing up the file, click on Close  
or Cancel.)  
11. In the Receive Filename window, enter a name for the file—for example, UMconfig.sav.  
12. When the transfer is complete, a confirmation message appears in the Service Terminal Interface  
window: “Backup Successful.”  
72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System and Control Options  
Upload the Configuration File  
13. At the prompt to Initiate an Upload of Configuration File, enter Y (Yes - begin) or N (No - cancel).  
The current setting appears in brackets—[N] in the following example.  
>INITIATE AN UPLOAD OF CONFIGURATION FILE-YES(Y) OR NO(N)?  
>[N]  
>[  
NOTE  
The following instructions refer to the Microsoft Windows HyperTerminal program. These  
steps may vary for other communications programs.  
14. At the top of the HyperTerminal window, shown below, click on Transfer, then on Send File.  
Enter filename -  
for example,  
UMconfig.sav  
Select Xmodem  
Send button  
15. In the Send File window, as shown above:  
• In the Filename box, enter the full path of the file to be uploaded—for example,  
UMconfig.sav—or click on the Browse button to locate the file.  
• In the Protocol box, select Xmodem from the drop-down list.  
• Click on the Send button. (To close the window without sending the file, click on Close or  
Cancel.)  
16. When the transfer is complete, a confirmation message—“Upload Successful”—appears in the  
Service Terminal Interface window and the Universal Monitor reboots with the new  
configuration.  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System and Control Options  
9.9.6 Setup Serv Ph Num - Enter Phone Number  
The Service Phone Number (Serv Ph Num) is used for remote monitoring by Liebert Global Services.  
The number is designed to allow remote monitoring services to connect to the Universal Monitor. All  
alarms will be sent to this number. When an alarm occurs, this number is dialed before any of the  
four pager numbers.  
To use the service phone number features, be sure to connect the phone line connector to a telephone  
wall jack using an RJ11 cord, as described in 4.6.2 - Phone Line Connector.  
Table 32 Service phone number dialing results  
Result of Dialing  
Successful  
Action  
Message Generated  
Unsuccessful due to:  
Busy signal / no answer /  
no dial tone  
Universal Monitor generates message after all three  
Unsuccessful Page  
redial attempts have failed, dials next configured pager. (Event Log)  
General modem  
communication problem  
Universal Monitor resets modem, generates  
message, redials up to three more times.  
Modem Reset  
(Event Log)  
Modem Internal Fault  
(Active Alarm Report,  
Alarm History Log)  
No communication with modem Universal Monitor generates messages, makes no  
(internal hardware problem) further dialing attempts.  
To set up the service phone number:  
Setup System Info Menu  
• From the Setup System Info Menu, use the arrows to choose  
Setup Serv Ph Num, then press Enter .  
• See Table 33 for guidelines on entering the phone number, which  
SETUP SYSTEM INFO  
CHANGE PASSWORD  
CHANGE DATE & TIME  
=NEXT =SELECT  
may consist of up to 40 characters. To enter the phone number:  
SETUP SITE ID  
CONNECT BATTERY  
> SETUP SERV PH NUM  
FACTORY DEFAULTS  
• Use the arrows to choose a character.  
• Press Enter to advance to the next character position.  
• When finished, press Enter again.  
Table 33 Guidelines for dialing service phone number  
Setup Serv Ph Num  
ENTER PHONE NUMBER  
M18005551212  
Device type  
Required entries  
The first character must be “M”.  
Optional entries  
Example  
M18005551212  
Example  
Remote  
modem  
=SELECT =NEXT/END  
Device type  
Use “9” if needed to access an outside  
line—place after first character (M).  
M918005551212  
Use "W" to wait for a second dial tone  
before dialing if the phone system has  
two dial tones (initial tone and a second  
tone for outside line)—place after “9”  
(before the number to be dialed).  
All types  
of devices  
M9W18005551212  
Use “,” (comma) to pause two seconds.  
M1,8005551212  
74  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
System and Control Options  
9.9.7 Setup Serv Ph Num - Communications Check (Service Terminal Interface only)  
The Service Terminal Interface offers two additional options for setting up the Service Phone Number  
(Serv Ph Num) that are not available through the LCD interface:  
• Enable communications check  
• Enter time to perform communications check  
To access these options:  
• Connect to the Universal Monitor either from a remote computer or through the RS232 port (see  
• At the Main Menu, enter 0 (zero—Setup System-Login Required).  
• At the Login Menu, enter your password.  
• At the Setup Menu, enter 7 (Setup System Information).  
• At the Setup System Information Menu, enter 6 (Setup Service Phone Number).  
• At the Setup Service Phone Number menu, shown below, enter 1 to begin the setup.  
Setup Service Phone Number  
(Service Terminal Interface only)  
SETUP SERVICE PHONE NUMBER  
This number receives all alarms  
in addition to the 4 pagers  
CURRENT NUMBER  
1=SETUP SERVICE PHONE NUMBER  
2=RETURN TO SETUP SYSTEM INFO MENU  
3=RETURN TO SETUP MENU  
******************  
An “M” is required  
as 1st character.  
******************  
4=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
• At the Enter Service Phone Number prompt, you may press Enter to bypass this option (or see  
9.9.6 - Setup Serv Ph Num - Enter Phone Number for instructions on entering the number).  
>ENTER SERVICE PHONE NUMBER(40 CHARACTERS MAX).  
>[]  
>[  
>COMMAND SUCCESSFUL  
Enable Communications Check  
Enabling this function permits a daily communications test between the Universal Monitor and the  
selected service phone number. Once each day the Universal Monitor dials the service phone number  
at a specified time and sends this message: “UNIVERSAL MONITOR COMM CHECK.” (The time of  
the test is specified at the next prompt, Enter Time To Perform Communications Check.)  
• At the Enable Communications Check prompt, enter Y (Yes - enable) or N (No - disable). The cur-  
rent setting appears in brackets—[N] in the following example.  
>ENABLE COMMUNICATIONS CHECK-YES(Y) OR NO(N)?  
>[N]  
>
>COMMAND SUCCESSFUL  
• Press Enter to proceed, or Escape to cancel the entry. If you make a change, a confirmation mes-  
sage appears: “Command Successful.”  
Enter Time To Perform Communications Check  
This function schedules the daily communications test between the Universal Monitor and the  
selected service phone number, as described in the previous section.  
• At the Enter Time To Perform Communications Check prompt, enter the time to initiate the com-  
munications check, using the format HH:MM (hours and minutes in military time), ranging from  
00:00 for midnight to 23:59 for 11:59 p.m. The current setting appears in brackets—[00:00] in the  
following example.  
>ENTER TIME TO PERFORM COMMUNICATIONS CHECK(HH:MM).  
>[00:00]  
>[  
>COMMAND SUCCESSFUL  
• Press Enter to proceed, or Escape to cancel the entry. If you make a change, a confirmation mes-  
sage appears: “Command Successful.”  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System and Control Options  
9.9.8 Factory Defaults  
Setup System Info Menu  
At any time, you may restore all default values for settings in the Uni-  
versal Monitor as it was shipped.  
SETUP SYSTEM INFO  
CHANGE PASSWORD  
CHANGE DATE & TIME  
=NEXT =SELECT  
NOTE  
SETUP SITE ID  
CONNECT BATTERY  
SETUP SERV PH NUM  
> FACTORY DEFAULTS  
This action will overwrite any configuration settings. You may  
want to back up your settings before restoring the factory  
Info for details on backing up settings using the Service  
Terminal Interface.  
Factory Defaults  
RESTORE ALL DEFAULTS  
ARE YOU SURE? N  
The password is the sole exception when reverting to the factory  
default settings. The password can be reset to the factory default of  
AAAA only through the DIP switches. For details, see Change  
=Y/N  
=END  
9.9.9 Perform Firmware Update (Service Terminal Interface only)  
This function, which may be performed only through the Service Terminal Interface, upgrades the  
Universal Monitor’s firmware to the newest version.  
NOTE  
This action will overwrite any configuration settings. You may  
want to back up your settings before restoring the factory  
Info for details on backing up settings using the Service  
Terminal Interface.  
• Connect to the Universal Monitor either from a remote computer or through the RS232 port (see  
• At the Main Menu, enter 0 (zero—Setup System-Login Required).  
• At the Login Menu, enter your password.  
• At the Setup Menu, enter 7 (Setup System Information).  
• At the Setup System Info menu, enter 8 (Perform Firmware Update).  
• At the Perform Firmware Update menu, shown below, enter 1 to proceed with an update.  
Firmware Update  
PERFORM FIRMWARE UPDATE  
(Service Terminal Interface only)  
This command will update  
the existing firmware  
1=PERFORM FIRMWARE UPDATE  
2=RETURN TO SETUP SYSTEM INFO MENU  
3=RETURN TO SETUP MENU  
4=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
To perform the update:  
1. At the Perform Firmware Update prompt, enter Y (Yes - begin) or N (No - cancel). The current  
setting appears in brackets—[N] in the following example.  
>PERFORM FIRMWARE UPDATE-YES(Y) OR NO(N)?  
>[N]  
>[  
76  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
System and Control Options  
NOTE  
The following instructions refer to the Microsoft Windows HyperTerminal program. These  
steps may vary for other communications programs.  
2. The firmware update is a two-step process—this step describes how to upload the file  
prog###.s19 (where ### is a number—for example, prog118.s19) to the Universal Monitor:  
a. At the top of the HyperTerminal window, shown below, click on Transfer, then on Send File.  
Enter filename -  
prog###.s19 or  
flash###.s19  
Select  
Xmodem  
Send button  
b. In the Send File window, as shown above:  
• In the Filename box, enter the full path of the file to be uploaded—prog###.s19—or click  
on the Browse button to locate the file.  
• In the Protocol box, select Xmodem from the drop-down list.  
• Click on the Send button. (To close the window without sending the file, click on Close or  
Cancel.)  
• When the transfer is complete, a confirmation message appears in the Service Terminal  
Interface window.  
3. Next, follow these steps to upload the file flash###.s19 (where ### is a number—for example,  
flash607.s19) to the Universal Monitor:  
a. At the top of the HyperTerminal window, shown above, click on Transfer, then on Send File.  
b. In the Send File window, shown above:  
• In the Filename box, enter the full path of the file to be uploaded—flash###.s19—or click  
on the Browse button to locate the file.  
• In the Protocol box, select Xmodem from the drop-down list.  
• Click on the Send button. (To close the window without sending the file, click on Close or  
Cancel.)  
• When the transfer is complete, a confirmation message—“Firmware Update Successful”—  
appears in the Service Terminal Interface window and the Universal Monitor reboots  
with the new firmware update.  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System and Control Options  
9.9.10 Initiate Remote Alarm Test (Service Terminal Interface only)  
The service phone number is used for remote monitoring by Liebert Global Services. The Service Ter-  
minal Interface may be used to test communications between the Universal Monitor and the service  
modem. This test will send a “DIAL OUT TEST PASSED” message to the service phone number.  
The test is used to simulate an alarm to verify the proper configuration and functioning of the modem  
and other communications required for receiving alarms. This simulated alarm bypasses the normal  
alarm sequence—the LCD will not flash, the horn will not sound and there will be no record in the  
Alarm Log. A message is sent to the service phone number only if the alarm system is set up correctly.  
To initiate the remote alarm test:  
• Connect to the Universal Monitor either from a remote computer or through the RS232 port (see  
• At the Main Menu, enter 0 (zero—Setup System-Login Required).  
• At the Login Menu, enter your password.  
• At the Setup Menu, enter 7 (Setup System Information).  
• At the Setup System Info menu, enter 9 (Initiate Remote Alarm Test).  
• At the Initiate Remote Alarm Test menu, shown below, enter 1 to initiate the remote alarm.  
Initiate Remote Alarm Test  
(Service Terminal Interface only)  
INITIATE REMOTE ALARM TEST  
This command simulates an alarm  
to test alarm notification setup  
for the service phone number  
1=INITIATE REMOTE ALARM TEST  
2=RETURN TO SETUP SYSTEM INFO MENU  
3=RETURN TO SETUP MENU  
4=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
• At the Simulate An Alarm Condition prompt, enter Y if you wish to proceed or N if you want to  
cancel the alarm simulation.  
>SIMULATE AN ALARM CONDITION-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
• After the “Command Successful” message appears, disconnect from the modem—at the top of the  
HyperTerminal window, click on Call, then on Disconnect, as shown below.  
Disconnect  
• Wait for the Universal Monitor to dial out to send a test message.  
• To verify whether the test was successful, check the Event Log (see 7.3 - View Event Log) for  
one of these two messages: Dial out test passed or Dial out test failed.  
NOTE  
Also verify that a message was received at the Service Phone Number.  
If the test is NOT successful, check the following:  
• Modem configuration (see 9.8.1 - Modem Setup - Initialization String)  
• Pager configuration (see 9.8.3 - Pager Setup - Pager Number and PIN)  
78  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System and Control Options  
9.10 Setup Exp Board - Optional Expansion Board  
By default, the optional Expansion Board is configured as Not connected (N). After connecting power  
to the board and connecting it to the Universal Monitor, you must specify the Expansion Board as  
Connected (Y), as described in this section.  
NOTE  
Before specifying the Expansion Board as Connected, be sure to connect power to the board and  
connect it to the Universal Monitor. For more information, see:  
To change the Expansion Board connection setting:  
Setup System Menu  
Log In and Choose Setup System  
SETUP INPUT  
SETUP COMMON ALARM  
SETUP SENSOR  
SETUP I/O MATRIX  
=NEXT =SELECT  
SETUP OUTPUT  
• From the Main Menu, use the arrows to choose System and  
Control, then press Enter (see 9.1 - Login for help).  
• Enter your password at the Login screen.  
• From the System and Control Menu, use the arrows to choose  
SETUP MODEM&PAGERS  
SETUP SYSTEM INFO  
> SETUP EXP BOARD  
Setup System, then press Enter .  
Identify the Expansion Board as Connected (Y) or Not Connected (N)  
• From the Setup System Menu, shown at right, use the arrows ↑ ↓  
to choose Setup Exp Board and press Enter .  
• To change this setting, use the arrows to choose Y (Yes - Con-  
Expansion Board  
Connected  
IS THE EXPANSION  
nected) or N (No - Not connected), then press Enter .  
BOARD CONNECTED? N  
=Y/N  
=END  
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System and Control Options  
9.11 Manual Output Ctrl  
The Manual Output Ctrl feature allows you to manually change the state of any digital output to ON  
or OFF, overriding automatic control by the Universal Monitor (the default setting for all outputs).  
This menu also allows you to release the manual override, returning any output to automatic control.  
There are two ways to override automatic control of outputs:  
• Use the Manual Output Ctrl menu, as described in this section, to turn any output ON or OFF.  
• Use the switch on the Universal Monitor board (see 1.7 - Controller Board Overview) to force  
all eight outputs ON at the same time. (Note: This has no effect on the optional Expansion Board  
outputs.)  
After an output is forced manually ON or OFF through the Manual Output Ctrl menu, it remains in  
that state until returned to automatic control through this menu.  
Table 34 summarizes the four types of control, including the abbreviated message that appears on  
the LCD and in log reports.  
Table 34 Automatic / manual control - output points  
Main Menu  
Message  
AUTO  
Description  
VIEW STATUS  
> SYSTEM AND CONTROL  
Automatic  
Controlled by Universal Monitor  
=NEXT  
=SELECT  
MAN ON  
Manually ON  
Manually OFF  
This output forced ON or OFF  
via Manual Output Ctrl menu  
MAN OFF  
Login  
Manually ON  
(all outputs)  
All outputs forced ON  
via hardware switch on circuit board  
HW MAN ON  
LOGIN  
AAAA  
To force an output point ON or OFF or return it to automatic control:  
=SELECT =NEXT/END  
Log In and Choose Manual Output Ctrl  
• From the Main Menu, use the arrows to choose System and  
System & Control Menu  
Control, then press Enter (see 9.1 - Login for help).  
SETUP SYSTEM  
• Enter your password at the Login screen.  
• From the System and Control Menu, use the arrows ↑ ↓to choose  
> MANUAL OUTPUT CTRL  
CLEAR ALARMS & LOGS  
=NEXT =SELECT  
Manual Output Ctrl, then press Enter .  
Select an Output  
Select Output  
The Select Output menu, shown at right, display the current status  
of all eight outputs.  
OVERRIDE OUTPUT  
> OUTPUT01 AUTO  
OUTPUT02 AUTO  
• Use the arrows to choose the output you want—for example,  
=NEXT =SELECT  
Output01—and press Enter .  
OUTPUT03 AUTO  
OUTPUT04 MAN ON  
OUTPUT05 AUTO  
OUTPUT06 AUTO  
OUTPUT07 MAN OFF  
OUTPUT08 AUTO  
OUTPUT09 AUTO  
OUTPUT10 MAN ON  
OUTPUT11 AUTO  
OUTPUT12 AUTO  
OUTPUT13 MAN OFF  
OUTPUT14 AUTO  
OUTPUT15 AUTO  
OUTPUT16 AUTO  
Turn Output ON or OFF / Return to Automatic  
• From the Override Output menu, use the arrows to choose  
one of these options:  
Auto (return to automatic control)  
Man ON (manually turn this output ON)  
Man OFF (manually turn this output OFF)  
• Press Enter .  
Override Output  
SELECT OUTPUT01  
AUTO  
=SELECT =END  
NOTE: OUTPUT09-OUTPUT16  
for optional Expansion Board  
80  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
System and Control Options  
9.12 Clear Alarms & Logs  
Main Menu  
VIEW STATUS  
> SYSTEM AND CONTROL  
The Clear Alarms & Logs menu allows you to clear active alarms or  
delete all records from any of the Universal Monitor’s three logs:  
alarm, event and trend logs.  
=NEXT  
=SELECT  
To clear alarms or logs:  
Login  
Log In and Choose Clear Alarms & Logs  
LOGIN  
AAAA  
• From the Main Menu, use the arrows to choose System and  
Control, then press Enter (see 9.1 - Login for help).  
• Enter your password at the Login screen.  
=SELECT =NEXT/END  
• From the System and Control Menu, use the arrows to choose  
Clear Alarms & Logs, then press Enter .  
• Use the following steps to clear alarms or delete log records.  
System & Control Menu  
SETUP SYSTEM  
MANUAL OUTPUT CTRL  
> CLEAR ALARMS & LOGS  
=NEXT =SELECT  
9.12.1 Clear Active Alarms  
Clear Alarms/Logs Menu  
To clear all active alarms:  
> CLEAR ACTIVE ALARMS  
CLEAR ALARM LOG  
• From the Clear Alarms/Logs Menu, use the arrows to choose  
Clear Active Alarms, then press Enter .  
• Use the arrows to choose Y (Yes - clear all active alarms) or  
CLEAR EVENT LOG  
=NEXT =SELECT  
CLEAR TREND LOGS  
N (No - do not clear alarms), then press Enter .  
Clear Active Alarms  
CLEAR ACTIVE ALARMS  
ARE YOU SURE? N  
Clearing active alarms is the only means to reset latched alarms. This  
step is required to return latched points to their normal state. To set up  
a digital input or an analog sensor input as latched, see:  
=Y/N  
=END  
9.12.2 Clear the Alarm Log  
Clear Alarms/Logs Menu  
The alarm log contains up to 99 records of alarms that have occurred.  
You may want to clear the log after backing up the file or simply to  
free up space.  
CLEAR ACTIVE ALARMS  
> CLEAR ALARM LOG  
CLEAR EVENT LOG  
=NEXT =SELECT  
CLEAR TREND LOG  
NOTE  
Before deleting the records in the alarm log, you may want to  
back up the file to a remote computer using the Service  
Terminal Interface, as described in 8.2 - Back Up Log Files  
Clear Alarm Log  
CLEAR ALARM LOG  
ARE YOU SURE? N  
To delete all records from the alarm log:  
=Y/N  
=END  
• From the Clear Alarms/Logs Menu, use the arrows to choose  
Clear Alarm Log, then press Enter .  
• Use the arrows to choose Y (Yes - clear the alarm log) or  
N (No - do not clear the alarm log), then press Enter .  
NOTE  
Clear active alarms is the only means to reset Latched alarms.  
This action must be taken to return Latched points to their  
normal state.  
81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
System and Control Options  
9.12.3 Clear the Event Log  
Clear Alarms/Logs Menu  
The event log contains up to 99 records of events detected by the Uni-  
versal Monitor. You may want to clear the log after backing up the file  
or simply to free up space.  
CLEAR ACTIVE ALARMS  
CLEAR ALARM LOG  
> CLEAR EVENT LOG  
=NEXT =SELECT  
CLEAR TREND LOGS  
NOTE  
Before deleting the records in the event log, you may want to  
back up the file to a remote computer using the Service  
Terminal Interface, as described in 8.2 - Back Up Log Files  
Clear Event Log  
CLEAR EVENT LOG  
ARE YOU SURE? N  
=Y/N  
=END  
To delete all records from the event log:  
• From the Clear Alarms/Logs Menu, use the arrows to choose  
Clear Event Log, then press Enter .  
• Use the arrows ↑ ↓to choose Y (Yes - clear the event log) or N (No -  
do not clear the event log), then press Enter .  
9.12.4 Clear the Trend Logs  
Clear Alarms/Logs Menu  
The Universal Monitor maintains a separate trend log for each config-  
ured analog input sensor. Each log contains up to 100 records of data  
collected at regular intervals. You may want to clear the logs after  
backing up the files or simply to free up space.  
CLEAR ACTIVE ALARMS  
CLEAR ALARM LOG  
CLEAR EVENT LOG  
=NEXT =SELECT  
> CLEAR TREND LOGS  
Using the Clear Trend Logs command will clear all four trend logs  
maintained by the Universal Monitor. There is no method of clearing  
records from individual logs.  
Clear Trend Log  
CLEAR TREND LOGS  
ARE YOU SURE? N  
NOTE  
Before deleting the records in the trend logs, you may want to  
back up the files to a remote computer using the Service  
Terminal Interface, as described in 8.2 - Back Up Log Files  
=Y/N  
=END  
To delete the records from ALL four trend logs:  
• From the Clear Alarms/Logs Menu, use the arrows to choose Clear Trend Logs, then press  
Enter .  
• Use the arrows to choose Y (Yes - clear all trend logs) or N (No - do not clear the trend logs),  
then press Enter .  
82  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Specifications  
10.0 SPECIFICATIONS  
10.1 Universal Monitor Specifications  
Small Enclosure  
Large Enclosure  
NOTE  
If the equipment is  
used in a manner  
not specified by the  
manufacturer, the  
protection provided  
by the equipment  
may be impaired.  
115VAC  
UML11500  
230VAC  
UMS02400  
UML23000  
Power  
Requirements  
24VAC ±10%  
of nominal;  
50/60 Hz, 1.3A,  
30VA  
115VAC ±10% 230VAC ±10%  
of nominal;  
60Hz, 4A,  
460VA  
of nominal;  
50Hz, 0.5A,  
115VA  
Dimensions  
W x D x H, in. (mm)  
14-1/4 x 2-3/4 x 12  
(361.95 x 69.85 x 304.8)  
18 x 2-3/4 x 18  
(457.2 x 69.85 x 457.2)  
Weight (Assembled)  
Enclosure Type  
7.68 lb. (3.48 kg)  
20.56 lb. (9.33 kg)  
NEMA 1  
Liquid Crystal Display (LCD)  
Mounting Surface  
Four line, 20 character, backlit  
Building Wall or Structural Member  
Ambient Operating  
Environment  
32ºF to 104ºF (0ºC to 40ºC)  
0% RH to 95% RH (non-condensing)  
Processor Specifics  
Model  
Motorola XC68HC812A4  
16MHz  
Clock speed  
Total RAM  
256Kb  
Total FLASH  
4M  
Total EEPROM  
4K  
A/D Resolution (Analog IN)  
Modem Type  
12 Bit  
Embedded 14.4K bps  
Real-Time Clock  
Lithium Cell (non-replaceable)  
7 years, constant, no power  
Nickel Cadmium (replaceable)  
10 minutes at full load  
Clock Type  
Clock battery backup type  
Clock battery life  
Modem battery backup type  
Modem battery life  
Communications  
Local Communications  
RS232  
Remote Communications  
Modem (9600-N-8-1)  
Supported pagers  
Baud rate 9600 bps, Parity=None, Data bits=8, Stop bits=1  
9600 E-7-1 supports TAPI protocol version 1.8  
SiteScan Web  
IGM Protocol, EIA422  
EIA485  
Expansion Board (optional)  
No Transformer Module  
With Transformer Module  
Agency Listings  
115VAC  
(TM115)  
230VAC  
(TM230)  
(UMS02400)  
UL  
UL3121  
UL1012  
UL1585  
C22.2 No. 66 and  
C22.2 No. 107.1  
CSA  
C22.2 No. 1010  
CE  
Yes  
Yes  
N/A  
FCC Compliance  
Inputs & Outputs (Quantity)  
Digital Inputs (8)  
CFR 47 Part 15  
Dry Contact Closure 24VDC, 10 mA  
4-20 mA signal input with selectable  
power source of 12VDC or 24VDC  
Analog Inputs (4)  
Digital Outputs (8)  
24VAC, 3A  
24VAC, 3A  
Common Alarm Outputs (2)  
83  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Specifications  
10.2 Optional Expansion Board Specifications  
NOTE  
UMEXP  
Power  
Requirements  
If the equipment is  
used in a manner  
not specified by the  
manufacturer, the  
protection provided  
by the equipment  
may be impaired.  
24VAC ±10% of nominal;  
50/60 Hz, 0.6A, 15VA Class 2  
Dimensions  
W x D x H, in. (mm)  
14-1/4 x 2-3/4 x 12  
(361.95 x 69.85 x 304.8)  
Weight (Assembled)  
7.68 lb. (3.48 kg)  
Enclosure Type  
NEMA 1  
Mounting Surface  
Building Wall or Structural Member  
Ambient Operating  
Environment  
32ºF to 104ºF (0ºC to 40ºC)  
0% RH to 95% RH (non-condensing)  
Inputs & Outputs (Quantity)  
Dry Contact Closure  
24VDC, 10 mA  
Digital Inputs (16)  
Digital Outputs (8)  
240VAC, 2A  
84  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Service Terminal Interface  
APPENDIX A - SERVICE TERMINAL INTERFACE  
The Service Terminal Interface allows access to all functions of the Universal Monitor, including  
some that are not possible through the LCD interface. This interface is accessible through any com-  
®
®
puter using a communications program such as Microsoft Windows HyperTerminal.  
This appendix provides directions for connecting to the Service Terminal Interface, an overview of  
each type of function and sample screens for each menu available through the Service Terminal Inter-  
face. References to more detailed instructions about each function are provided.  
A.1 COMPARISON OF FUNCTIONS: LCD AND SERVICE TERMINAL INTERFACE  
Table 35 lists all functions for viewing and configuring the Universal Monitor and shows whether  
they can be performed through the LCD interface and where to find information.  
Table 35 Guide to Universal Monitor functions  
Can be performed via:  
Service  
Where to find:  
Instructions on Service Terminal  
Function  
VIEW STATUS FUNCTIONS  
LCD  
Terminal  
using function  
screen examples  
SILENCE ALARM & BACK UP LOGS FUNCTIONS  
Silence Alarm (On the LCD, press any key to silence an alarm)  
SYSTEM & CONTROL FUNCTIONS  
Pager Setup - Pager Number & PIN  
Pager Setup - Communications Check  
Modem Setup - Initialization String  
Setup System Info  
Setup Serv Ph Num - Enter Phone Number  
Setup Serv Ph Num - Communications Check  
Initiate Remote Alarm Test  
Setup Exp Board - Optional Expansion Board  
Clear Alarms & Logs  
85  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Connecting to the Service Terminal Interface  
A.2 CONNECTING TO THE SERVICE TERMINAL INTERFACE  
This section describes how to set up and connect to the Service Terminal Interface.  
A.2.1 Connection Methods  
There are two ways to access the Service Terminal Interface:  
Direct—Use a null modem cable to connect a computer’s COM1 port to the Universal Monitor’s  
RS232 port,  
OR  
Remote—Use a remote computer’s modem to dial the telephone number of the phone line con-  
nected to the Universal Monitor.  
Both methods require a communications program, such as HyperTerminal, to connect to the Service  
Terminal Interface.  
Refer to Table 36 for step-by-step instructions to set up each type of connection. Note that the remote  
connection does not require setting up the COM1 port.  
Table 36 Steps to set up a direct or remote connection  
Direct  
Remote  
N/A  
The instructions in this section refer to the HyperTerminal program—they may vary for other com-  
munications programs.  
86  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Connecting to the Service Terminal Interface  
A.2.2 Create a Connection  
Before connecting to the Service Terminal Interface, you must create a connection and specify the  
method to be used for connection, as described in the following steps.  
1. Start the HyperTerminal program—to do this, click on the Start button, then on Programs, then  
Accessories, then Communications, and finally HyperTerminal.  
2. At the top of the HyperTerminal window, click on File, then on New Connection, as shown  
below left.  
Enter a name for  
the connection -  
for example,  
Universal  
Monitor  
3. In the Connection Description window, shown above right, enter a name for the connection—for  
example, Universal Monitor. This becomes the file name (with the extension “.ht”).  
4. Click OK to close the window. The Connect To window opens, as shown below.  
(DIRECT CONNECTION)  
Choose COM1  
(REMOTE CONNECTION)  
Choose the computer’s modem  
5. In the Connect To window, select the appropriate connection method from the Connect Using  
drop-down list:  
Direct Connection via RS232  
• To set up a direct connection via the Universal Monitor’s RS232 port, select COM1 as shown  
above left.  
• This opens the COM1 Properties window. Proceed to Step 6 (next section).  
Remote Connection via Modem  
• To make a remote connection through the Universal Monitor’s modem, select your computer’s  
modem—HSP56 MicroModem in the example shown above right.  
• Enter the area code and phone number of the Universal Monitor’s modem.  
• Proceed to Step 8 in A.2.4 - Set Up the Connection’s Properties (skip Steps 6 and 7).  
87  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Connecting to the Service Terminal Interface  
A.2.3 Set Up the COM1 Port - Direct Connection Only  
The following steps apply only to setting up a direct connection to the Service Terminal Interface via  
the Universal Monitor’s RS232 port. If you are setting up a remote connection via modem, skip to  
Step 8 (next section).  
COM1 Port Setup  
6. In the COM1 Properties window, shown below, make the following selections:  
• Bits per second: 9600  
• Data bits: 8  
• Parity: None  
• Stop bits: 1  
• Flow control: None  
7. Click OK. When the connection is open, the connection name appears in the title bar of the  
HyperTerminal window. To complete the setup, continue with Step 8 (next section).  
88  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Connecting to the Service Terminal Interface  
A.2.4 Set Up the Connection’s Properties  
The following steps are needed for both direct and remote connection to the Universal Monitor.  
Properties Setup  
8. Open the Properties window by clicking on File, then on Properties, as shown below left.  
Settings  
tab  
9. In the Properties window, above right, click on the Settings tab and choose the following settings:  
• Function, arrow, and ctrl keys act as: Terminal keys  
• Backspace key sends: Ctrl+H  
• Emulation: ANSIW  
• Telnet terminal ID: VT100  
• Backscroll buffer lines: 500  
• Play sound when connecting or disconnecting: Unchecked  
ASCII Setup  
10. In the Properties window, click on the ASCII Setup button, shown below left.  
ASCII  
Setup  
button  
11. In the ASCII Setup window, shown above right, choose the following settings:  
• ASCII Sending: place a check mark () in the Send Line Ends With Line Feeds box.  
• ASCII Receiving: place a check mark () in the Wrap Lines That Exceed Terminal Width box.  
• Click OK.  
The setup is now complete. To use the new connection, proceed to the next section, A.2.5 - Connect  
89  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Connecting to the Service Terminal Interface  
A.2.5 Connect to the Service Terminal Interface  
After creating and setting up a connection, use a communications program such as HyperTerminal to  
access the Universal Monitor’s Service Terminal Interface.  
1. Verify communications connections between the remote computer and the Universal Monitor:  
a. For direct connection (via RS232 port):  
• Connect a null modem cable from the computer’s COM1 port to the Universal Monitor’s  
RS232 port (for location, see 4.6.1 - RS232 Connector).  
b. For remote connection (via modem):  
• Verify modem connections between the remote computer and the Universal Monitor. The  
remote computer should have connectivity through a telephone line, high-speed cable or an  
Ethernet. The Universal Monitor must have a telephone line connected to its RJ11 port (for  
location, see 4.6.2 - Phone Line Connector).  
2. Start the HyperTerminal program—click on the Start button, then on Programs, then  
Accessories, then Communications, and finally HyperTerminal.  
3. Open the Universal Monitor connection created in A.2.2 - Create a Connection. To do this, click  
on File, then on Open, as shown below.  
Click on the  
file name -  
for example,  
Universal  
Monitor.ht  
4. In the Open window, shown above right, select the file name—Universal Monitor.ht in this  
example—and then click on the Open button.  
5. Follow the steps below to display the Main Menu of the Service Terminal Interface:  
a. For direct connection (via RS232 port):  
• Press Enter (or Escape) to initiate communication and bring up the Main Menu.  
b. For remote connection (via modem):  
• The Connect window opens, as shown below left. Click the OK button.  
• In the Connect window, below right, click Dial.  
• If the dialing attempt is successful, the Main Menu appears.  
Dial button  
OK button  
For more information on the Universal Monitor’s options:  
• See A.3 - Overview of Menus for examples of the Service Terminal Interface screens.  
• See Table 35 to locate step-by-step instructions for each Universal Monitor function.  
90  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Overview of Menus  
A.3 OVERVIEW OF MENUS  
The Main Menu offers choices for viewing the status of the Universal Monitor, silencing the audible  
alarm and backing up the unit’s log files. It also allows access to the System and Control features,  
which require a password.  
The following shows where to find examples of the Main Menu screens:  
Main Menu  
1=VIEW ACTIVE ALARMS  
For sample screens, see:  
2=VIEW ALARM LOG  
3=VIEW EVENT LOG  
4=VIEW TREND LOG  
5=VIEW INPUT & SENSOR STATUS  
6=VIEW OUTPUT STATUS  
7=VIEW PAGER NUMBERS  
8=SILENCE ALARM  
A.5 - Silence Alarm & Back Up  
9=BACKUP LOG FILES  
0=SETUP SYSTEM-LOGIN REQUIRED  
A.3.1 View Status Overview  
The View Status features are available to all users. This permits all personnel to check on the status  
of any equipment or location being monitored. These options allow any user to:  
• View current monitoring data—active alarms and the status of all inputs and outputs  
• View data stored in alarm, event and trend logs  
• View pager numbers  
A.3.2 Silence Alarm and Backup Log Files  
Two Main Menu options—Silence Alarm and Backup Log Files—are unique to the Service Terminal  
Interface. As with the View Status options, these features do not require a password:  
Silence Alarm—silence the Universal Monitor’s audible alarm and reset the Common Alarm  
Relay output.  
Backup Log Files—make backup copies of the Universal Monitor’s Alarm Log, Event Log and  
Trend Logs and save the copies to a computer.  
A.3.3 Setup Menu Overview  
The Setup Menu options require a password. Authorized users may:  
• Configure the Universal Monitor—this includes setting up digital and analog inputs, digital out-  
puts, the modem, up to four pagers, and system features such as setting the date and time  
Three system features—Backup and Upload Configuration File, Firmware Update and  
Initiate Remote Alarm Test—are unique to the Service Terminal Interface.  
• Override automatic control of outputs to force an output ON or OFF  
• Clear active alarms and delete all records in the alarm, event and trend logs  
91  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
View Status Menus  
A.4 VIEW STATUS MENUS  
The View Status menu allows any user to view currently active alarms, monitoring data stored in the  
alarm, event and trend logs, the status of all inputs and outputs, and the four pager numbers.  
Main Menu  
After connecting to the Service Terminal Interface, the Main Menu appears, as shown below. This  
section presents Service Terminal Interface screens for options 1 through 7:  
Main Menu  
LIEBERT UNIVERSAL MONITOR  
VX.XXX.X  
LIEBERT CORPORATION COPYRIGHT 2003  
ALL RIGHTS RESERVED  
MAIN MENU  
For sample screens, see:  
1=VIEW ACTIVE ALARMS  
2=VIEW ALARM LOG  
3=VIEW EVENT LOG  
4=VIEW TREND LOG  
5=VIEW INPUT & SENSOR STATUS  
6=VIEW OUTPUT STATUS  
7=VIEW PAGER NUMBERS  
8=SILENCE ALARM  
9=BACKUP LOG FILES  
0=SETUP SYSTEM-LOGIN REQUIRED  
SELECT A NUMBER:1  
92  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
View Status Menus  
A.4.1 View Active Alarms  
For details on this feature, see 7.1 - View Active Alarms.  
View Active Alarms  
ACTIVE ALARMS  
Input points/hardware  
presently in an alarm state  
SENSOR_1 101.1 DEG  
HIGH SETPOINT ALARM  
SENSOR_2 ------ DEG  
SENSOR PROBLEM  
INPUT_07 ALARM  
CONTACT OPEN  
BATTERY  
CHECK BATTERY  
<ENTER>=MORE <ESC>=EXIT <A>=ALL  
1=REFRESH ACTIVE ALARMS  
2=RETURN TO MAIN MENU  
SELECT A NUMBER:  
93  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
View Status Menus  
A.4.2 View Alarm Log  
For details on this feature, see 7.2 - View Alarm Log.  
View Alarm Log  
ALARM LOG  
Alarm history  
SENSOR_2  
80.0 DEG  
HIGH SETPOINT ALARM  
29-AUG-02 09:29:10  
MODEM  
INTERNAL FAULT  
29-AUG-02 09:20:10  
INPUT_08 ALARM  
CONTACT CLOSED  
29-AUG-02 09:19:10  
SENSOR_2 79.0 DEG  
RETURN TO NORMAL  
28-AUG-02 19:29:10  
<ENTER>=MORE <ESC>=EXIT <A>=ALL  
SENSOR_2 ------ DEG  
SENSOR PROBLEM  
28-AUG-02 15:08:10  
SYSTEM  
LOSS OF POWER  
19-AUG-02 02:50:10  
BATTERY  
LOW BATTERY  
18-AUG-02 05:23:10  
BATTERY  
BATTERY UNPLUGGED  
12-AUG-02 22:47:10  
1=REFRESH ALARM LOG  
2=RETURN TO MAIN MENU  
SELECT A NUMBER:  
94  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
View Status Menus  
A.4.3 View Event Log  
For details on this feature, see 7.3 - View Event Log.  
View Event Log  
EVENT LOG  
Event history  
PAGER  
UNSUCCESSFUL PAGE  
07-MAY-02 10:29:10  
OUTPUT01 MAN ON  
CONTACT CLOSED  
07-MAY-02 09:20:10  
OUTPUT08 ON  
CONTACT OPEN  
07-MAY-02 08:20:10  
OUTPUT08 MAN OFF  
CONTACT CLOSED  
07-MAY-02 06:20:10  
<ENTER>=MORE <ESC>=EXIT <A>=ALL  
SENSOR_2 ------ DEG  
SENSOR PROBLEM  
06-MAY-02 07:10:10  
SYSTEM  
USER LOGIN  
19-APR-02 02:50:10  
LIEBERT GLOBAL SERV  
DIAL OUT TEST FAILED  
18-APR-02 05:23:10  
MODEM  
MODEM RESET  
12-MAR-02 22:47:10  
LIEBERT GLOBAL SERV  
DIAL OUT TEST PASSED  
12-MAR-02 05:23:10  
<ENTER>=MORE <ESC>=EXIT <A>=ALL  
1=REFRESH EVENT LOG  
2=RETURN TO MAIN MENU  
SELECT A NUMBER:  
95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
View Status Menus  
A.4.4 View Trend Log  
For details on this feature, see 7.4 - View Trend Log.  
View Trend Log  
TREND LOG  
Trend history  
for each sensor  
Select sensor for trend  
you want to view.  
1=SENSOR_1  
2=SENSOR_2  
3=SENSOR_3  
4=SENSOR_4  
5=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
TREND LOG  
Trend history  
SENSOR_1  
NORMAL  
28-AUG-02 15:45:10  
75.4 DEG  
SENSOR_1 70.5 DEG  
LOW SETPOINT EVENT  
28-AUG-02 15:15:10  
SENSOR_1 79.9 DEG  
RETURN TO NORMAL  
28-AUG-02 14:45:10  
SENSOR_1 ------ DEG  
SENSOR PROBLEM  
28-AUG-02 14:15:10  
<ENTER>=MORE <ESC>=EXIT <A>=ALL  
SENSOR_1 65.9 DEG  
LOW SETPOINT ALARM  
28-AUG-02 13:45:10  
SENSOR_1 69.9 DEG  
LOW SETPOINT EVENT  
28-AUG-02 13:15:10  
SENSOR_1  
80.7 DEG  
HIGH SETPOINT EVENT  
28-AUG-02 12:45:10  
1=REFRESH TREND LOG  
2=VIEW A DIFFERENT SENSOR  
3=RETURN TO MAIN MENU  
SELECT A NUMBER:  
96  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
View Status Menus  
A.4.5 View Input Status  
For details on this feature, see 7.5 - View Input Status.  
View Input & Sensor Status  
INPUT & SENSOR STATUS  
Sensor values & discrete inputs status  
INPUT  
STATUS/VALUE  
80.0 DEG  
SENSOR_2 ------ DEG  
SENSOR_1  
SENSOR_3  
SENSOR_4  
80.0 DEG  
79.5 RH  
INPUT_01 NORMAL  
INPUT_02 ALARM  
INPUT_03 EVENT  
INPUT_04 ALARM  
INPUT_05 ALARM  
INPUT_06 EVENT  
INPUT_07 NORMAL  
INPUT_08 NORMAL  
INPUT_09 EVENT  
INPUT_10 NORMAL  
INPUT_11 NORMAL  
<ENTER>=MORE <ESC>=EXIT <A>=ALL  
INPUT_12 NORMAL  
INPUT_13 ALARM  
INPUT_14 EVENT  
INPUT_15 ALARM  
INPUT_16 ALARM  
INPUT_17 EVENT  
INPUT_18 NORMAL  
INPUT_19 NORMAL  
INPUT_20 EVENT  
INPUT_21 NORMAL  
INPUT_22 NORMAL  
INPUT_23 NORMAL  
INPUT_24 NORMAL  
1=VIEW SENSOR_1 DYNAMICALLY  
2=VIEW SENSOR_2 DYNAMICALLY  
3=VIEW SENSOR_3 DYNAMICALLY  
4=VIEW SENSOR_4 DYNAMICALLY  
5=REFRESH INPUT & SENSOR STATUS  
6=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
VIEWING SENSOR_1 DYNAMICALLY  
SENSOR_1  
80.0 DEG  
PRESS <ESC> KEY TO EXIT  
97  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
View Status Menus  
A.4.6 View Output Status  
For details on this feature, see 7.6 - View Output Status.  
View Output Status  
OUTPUT STATUS  
Discrete outputs status  
OUTPUT  
STATUS  
OUTPUT01  
OUTPUT02  
OUTPUT03  
OUTPUT04  
OUTPUT05  
OUTPUT06  
OUTPUT07  
OUTPUT08  
OUTPUT09  
OUTPUT10  
OUTPUT11  
OUTPUT12  
OUTPUT13  
OUTPUT14  
ON  
OFF  
ON  
MAN ON  
ON  
OFF  
MAN OFF  
ON  
ON  
OFF  
ON  
MAN ON  
ON  
OFF  
<ENTER>=MORE <ESC>=EXIT <A>=ALL  
OUTPUT15  
OUTPUT16  
ON  
OFF  
1=REFRESH OUTPUT STATUS  
2=RETURN TO MAIN MENU  
SELECT A NUMBER:  
98  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
View Status Menus  
A.4.7 View Pager Numbers  
For details on this feature, see 7.7 - View Pager Numbers.  
View Pager Numbers  
PAGER & PIN NUMBERS  
Numbers to dial  
for an alarm  
PAGER 1 NUMBER  
A1,8005551212  
PAGER 1 PIN  
01234567891011121314  
PAGER 2 NUMBER  
A9W1,8005551212  
PAGER 2 PIN  
01234567891011121314  
<ENTER>=MORE <ESC>=EXIT <A>=ALL  
PAGER 3 NUMBER  
N18005551212,,,,1234567#  
PAGER 3 PIN  
PAGER 4 NUMBER  
M1,8005551212  
PAGER 4 PIN  
1=REFRESH PAGER NUMBERS  
2=RETURN TO MAIN MENU  
SELECT A NUMBER:  
99  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Silence Alarm & Back Up Log Files (Service Terminal Interface only)  
A.5 SILENCE ALARM & BACK UP LOG FILES (SERVICE TERMINAL INTERFACE ONLY)  
This section presents two options from the Main Menu that are available via the Service Terminal  
Interface only.  
Main Menu  
After connecting to the Service Terminal Interface, the Main Menu appears, as shown below. This  
section presents Service Terminal Interface screens for options 8 and 9:  
Main Menu  
LIEBERT UNIVERSAL MONITOR  
V5.300.2  
LIEBERT CORPORATION COPYRIGHT 2002  
ALL RIGHTS RESERVED  
MAIN MENU  
1=VIEW ACTIVE ALARMS  
2=VIEW ALARM LOG  
3=VIEW EVENT LOG  
4=VIEW TREND LOG  
5=VIEW INPUT & SENSOR STATUS  
6=VIEW OUTPUT STATUS  
7=VIEW PAGER NUMBERS  
For sample screens, see:  
8=SILENCE ALARM  
9=BACKUP LOG FILES  
0=SETUP SYSTEM-LOGIN REQUIRED  
SELECT A NUMBER:1  
A.5.1 Silence Alarm (Service Terminal Interface only)  
For details on this feature, see 8.1 - Silence Alarm (Service Terminal Interface).  
Silence Alarm  
SILENCE ALARM  
Silence alarm and reset  
common alarm relay if  
common alarm relay is  
configured to reset with  
silence alarm  
1=SILENCE ALARM  
2=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
>ALARM HAS BEEN SILENCED  
100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Silence Alarm & Back Up Log Files (Service Terminal Interface only)  
A.5.2 Back Up Log Files (Service Terminal Interface only)  
Back Up Alarm Log File  
Backup Log Files - Alarm Log File  
BACKUP LOG FILES  
Backup alarm, event and trend log files  
1=BACKUP ALARM LOG FILE  
2=BACKUP EVENT LOG FILE  
3=BACKUP TREND LOG FILE-SENSOR_1  
4=BACKUP TREND LOG FILE-SENSOR_2  
5=BACKUP TREND LOG FILE-SENSOR_3  
6=BACKUP TREND LOG FILE-SENSOR_4  
7=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
>INITIATE A BACKUP OF ALARM LOG-YES(Y) OR NO(N)?  
>[N]  
>[  
INSTRUCTIONS TO PERFORM BACKUP:  
ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION  
- SELECT TRANSFER FROM THE TOOLBAR  
- SELECT RECEIVE FILE  
- ENTER FOLDER WHERE FILE IS TO BE RECEIVED  
- SELECT XMODEM FROM THE PROTOCOL BOX  
- SELECT RECEIVE BUTTON AND ENTER FILE NAME, E.G., ALARM.LOG  
>BACKUP SUCCESSFUL  
101  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Silence Alarm & Back Up Log Files (Service Terminal Interface only)  
Back Up Event Log File  
Backup Log Files - Event Log File  
BACKUP LOG FILES  
Backup alarm, event and trend log files  
1=BACKUP ALARM LOG FILE  
2=BACKUP EVENT LOG FILE  
3=BACKUP TREND LOG FILE-SENSOR_1  
4=BACKUP TREND LOG FILE-SENSOR_2  
5=BACKUP TREND LOG FILE-SENSOR_3  
6=BACKUP TREND LOG FILE-SENSOR_4  
7=RETURN TO MAIN MENU  
SELECT A NUMBER:2  
>INITIATE A BACKUP OF EVENT LOG-YES(Y) OR NO(N)?  
>[N]  
>[  
INSTRUCTIONS TO PERFORM BACKUP:  
ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION  
- SELECT TRANSFER FROM THE TOOLBAR  
- SELECT RECEIVE FILE  
- ENTER FOLDER WHERE FILE IS TO BE RECEIVED  
- SELECT XMODEM FROM THE PROTOCOL BOX  
- SELECT RECEIVE BUTTON AND ENTER FILE NAME, E.G., EVENT.LOG  
>BACKUP SUCCESSFUL  
102  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Silence Alarm & Back Up Log Files (Service Terminal Interface only)  
Back Up Trend Log Files  
Backup Log Files - Trend Log Files  
BACKUP LOG FILES  
Backup alarm, event and trend log files  
1=BACKUP ALARM LOG FILE  
2=BACKUP EVENT LOG FILE  
3=BACKUP TREND LOG FILE-SENSOR_1  
4=BACKUP TREND LOG FILE-SENSOR_2  
5=BACKUP TREND LOG FILE-SENSOR_3  
6=BACKUP TREND LOG FILE-SENSOR_4  
7=RETURN TO MAIN MENU  
SELECT A NUMBER:3  
>INITIATE A BACKUP OF TREND LOG-YES(Y) OR NO(N)?  
>[N]  
>[  
INSTRUCTIONS TO PERFORM BACKUP:  
ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION  
- SELECT TRANSFER FROM THE TOOLBAR  
- SELECT RECEIVE FILE  
- ENTER FOLDER WHERE FILE IS TO BE RECEIVED  
- SELECT XMODEM FROM THE PROTOCOL BOX  
- SELECT RECEIVE BUTTON AND ENTER FILE NAME, E.G., SENSOR_1.LOG  
>BACKUP SUCCESSFUL  
103  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Setup Menu  
A.6 SETUP MENU  
The Setup menu allows the user to configure the Universal Monitor—setting up inputs and outputs  
and an input/output matrix to trigger actions, the modem and pagers, and system features such as  
date and time. This menu also provides a vehicle for manually changing the state of an output to ON  
or OFF, clearing active alarms and deleting records from the Universal Monitor’s alarm log, event log  
and trend logs.  
Main Menu  
After connecting to the Service Terminal Interface, the Main Menu appears, as shown below.  
Main Menu  
LIEBERT UNIVERSAL MONITOR  
VX.XXX.X  
LIEBERT CORPORATION COPYRIGHT 2003  
ALL RIGHTS RESERVED  
MAIN MENU  
1=VIEW ACTIVE ALARMS  
2=VIEW ALARM LOG  
3=VIEW EVENT LOG  
4=VIEW TREND LOG  
5=VIEW INPUT & SENSOR STATUS  
6=VIEW OUTPUT STATUS  
7=VIEW PAGER NUMBERS  
8=SILENCE ALARM  
9=BACKUP LOG FILES  
0=SETUP SYSTEM-LOGIN REQUIRED  
SELECT A NUMBER:0  
• Choose 0 to access the features illustrated in this section.  
Login Menu  
The System and Control options require a password to prevent unauthorized users from making  
changes to the system. After choosing 0 in the Main Menu above, the Login Menu appears:  
Login  
YOU MUST LOGIN TO PERFORM  
SETUP OR TO MAKE CHANGES  
LOGIN WITH 4 CHARACTER  
PASSWORD  
>****  
>INVALID PASSWORD, ENTER AGAIN  
>PRESS <ESC> TO EXIT  
>
• Enter the password, and the Setup Menu appears, as shown in the following section.  
104  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Setup Menu  
Setup Menu  
This section presents Service Terminal Interface screens for each of the following:  
Setup Menu  
SETUP MENU  
See:  
Description  
1=SETUP INPUT  
Configure digital inputs  
2=SETUP COMMON ALARM  
3=SETUP SENSOR  
Set up the common alarm to reset with silence  
Configure analog inputs  
4=SETUP I/O MATRIX  
5=SETUP OUTPUT  
Set up mapping for inputs to trigger actions in outputs  
Configure digital outputs  
6=SETUP MODEM&PAGERS  
Configure modem and up to four pager numbers  
Set up features such as password and date & time*  
Specify the Expansion Board as connected  
Manually override automatic control of outputs  
7=SETUP SYSTEM INFORMATION* Section A.6.7  
8=SETUP EXPANSION BOARD  
9=OVERRIDE OUTPUT  
0=CLEAR ALARMS&LOGS  
I=RETURN TO MAIN MENU  
SELECT A NUMBER:  
Section A.6.10 Clear active alarms; clear alarm, event and trend logs  
* Setup System Information features are:  
Note that three of these system features—Backup and Upload Configuration File, Firm-  
ware Update and Initiate Remote Alarm Test—are unique to the Service Terminal Interface.  
Tips on Using the Service Terminal Interface  
Use the following tips when making changes in the Service Terminal Interface:  
• Data that can be entered is shown in parentheses ( ) in prompt line.  
• The current setting is shown in brackets [ ] in the line below the prompt  
• To accept the current setting, press the Enter key.  
• To change the current setting, enter the value and then press Enter.  
• Pressing Escape will exit the current setup function or take you to the previous menu screen.  
Values that may  
be entered shown  
in parentheses ( )  
>CHANGE LABEL(8 CHARACTERS MAX).  
>[INPUT_01]  
>[  
>COMMAND SUCCESSFUL  
Current  
setting  
shown in  
brackets [ ]  
>IS INPUT NORMALLY OPENED(NO) OR NORMALLY CLOSED(NC)?  
>[NO]  
>[  
>COMMAND SUCCESSFUL  
105  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Setup Menu  
A.6.1 Setup Input  
For details on this feature, see 9.3 - Setup System - Setup Input.  
Setup Input - Main Board Outputs  
SETUP INPUT  
Setup for discrete  
input points  
Select input to edit  
INPUT  
DEFINITION  
****************************  
NO=NORMALLY OPENED  
NC=NORMALLY CLOSED  
1=INPUT_01 NO-EV-NL-00:01  
2=INPUT_02 NO-AL-L -00:01  
3=INPUT_03 NC-EV-NL-00:01  
4=INPUT_04 NO-AL-L -00:01  
5=INPUT_05 NC-AL-L -00:01  
6=INPUT_06 NO-EV-NL-00:01  
7=INPUT_07 NO-AL-L -00:01  
8=INPUT_08 NC-EV-NL-00:01  
9=EXPANSION BOARD INPUTS  
0=RETURN TO SETUP MENU  
EV=EVENT  
AL=ALARMABLE  
NL=NOT LATCHED  
L =LATCHED  
MIN:SEC=DELAY TIME BEFORE  
INPUT WILL TRIGGER  
I=RETURN TO MAIN MENU  
NOTE:EVENT CANNOT BE LATCHED  
****************************  
SELECT A NUMBER:1  
>CHANGE LABEL(8 CHARACTERS MAX).  
>[INPUT_01]  
>[  
>COMMAND SUCCESSFUL  
>IS INPUT NORMALLY OPENED(NO) OR NORMALLY CLOSED(NC)?  
>[NO]  
>[  
>COMMAND SUCCESSFUL  
>IS INPUT AN ALARM(AL) OR EVENT(EV)?  
>[EV]  
>[  
>COMMAND SUCCESSFUL  
>IS ALARM LATCHED-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>DELAY TIME BEFORE TRIGGER (MM:SS)?  
>[00:01]  
>[  
>COMMAND SUCCESSFUL  
106  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Setup Menu  
Setup Input - Expansion Board Inputs  
SETUP INPUT  
Setup for discrete  
input points  
Select input to edit  
INPUT  
DEFINITION  
****************************  
NO=NORMALLY OPENED  
NC=NORMALLY CLOSED  
1=INPUT_01 NO-EV-NL-00:01  
2=INPUT_02 NO-AL-L -00:01  
3=INPUT_03 NC-EV-NL-00:01  
4=INPUT_04 NO-AL-L -00:01  
5=INPUT_05 NC-AL-L -00:01  
6=INPUT_06 NO-EV-NL-00:01  
7=INPUT_07 NO-AL-L -00:01  
8=INPUT_08 NC-EV-NL-00:01  
9=EXPANSION BOARD INPUTS  
0=RETURN TO SETUP MENU  
EV=EVENT  
AL=ALARMABLE  
NL=NOT LATCHED  
L =LATCHED  
MIN:SEC=DELAY TIME BEFORE  
INPUT WILL TRIGGER  
I=RETURN TO MAIN MENU  
NOTE:EVENT CANNOT BE LATCHED  
****************************  
SELECT A NUMBER:9  
SETUP INPUT  
1=INPUT_09 NO-EV-NL-00:01  
2=INPUT_10 NO-AL-L -00:01  
3=INPUT_11 NC-EV-NL-00:01  
4=INPUT_12 NO-AL-L -00:01  
5=INPUT_13 NC-AL-L -00:01  
6=INPUT_14 NO-EV-NL-00:01  
7=INPUT_15 NO-AL-L -00:01  
8=INPUT_16 NC-EV-NL-00:01  
9=INPUT_17 NC-EV-NL-00:01  
0=INPUT_18 NC-EV-NL-00:01  
A=INPUT_19 NC-EV-NL-00:01  
B=INPUT_20 NC-EV-NL-00:01  
C=INPUT_21 NC-EV-NL-00:01  
D=INPUT_22 NC-EV-NL-00:01  
E=INPUT_23 NC-EV-NL-00:01  
F=INPUT_24 NC-EV-NL-00:01  
G=RETURN TO SETUP MENU  
****************************  
NO=NORMALLY OPENED  
NC=NORMALLY CLOSED  
EV=EVENT  
AL=ALARMABLE  
NL=NOT LATCHED  
L =LATCHED  
MIN:SEC=DELAY TIME BEFORE  
INPUT WILL TRIGGER  
NOTE:EVENT CANNOT BE LATCHED  
****************************  
H=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
>CHANGE LABEL(8 CHARACTERS MAX).  
>[INPUT_09]  
>[  
>COMMAND SUCCESSFUL  
>IS INPUT NORMALLY OPENED(NO) OR NORMALLY CLOSED(NC)?  
>[NO]  
>[  
>COMMAND SUCCESSFUL  
>IS INPUT AN ALARM(AL) OR EVENT(EV)?  
>[EV]  
>[  
>COMMAND SUCCESSFUL  
>IS ALARM LATCHED-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>DELAY TIME BEFORE TRIGGER MM:SS)?  
>[00:01]  
>[  
>COMMAND SUCCESSFUL  
107  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Setup Menu  
A.6.2 Setup Common Alarm  
For details on this feature, see 9.4 - Setup System - Setup Common Alarm.  
Setup Common Alarm  
SETUP COMMON ALARM  
Select if the common  
alarm relay contact  
is to reset with  
silence alarm  
CURRENT  
SETTING  
N
1=SETUP COMMON ALARM  
2=RETURN TO SETUP MENU  
3=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
>RESET COMMON ALARM WITH SILENCE-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
108  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Setup Menu  
A.6.3 Setup Sensor  
For details on this feature, see 9.5 - Setup System - Setup Sensor.  
Setup Sensor  
SETUP SENSOR  
Setup for analog  
input points  
Select sensor to edit  
SENSOR  
VALUE  
1=SENSOR_1 80.0 DEG  
2=SENSOR_2 ------ DEG  
3=SENSOR_3  
4=SENSOR_4  
80.0 DEG  
79.5 RH  
5=RETURN TO SETUP MENU  
6=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
>IS THE SENSOR CONNECTED-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>CHANGE SENSOR LABEL(8 CHARACTERS MAX).  
>[SENSOR_1]  
>[  
>COMMAND SUCCESSFUL  
>CHANGE UNITS LABEL(3 CHARACTERS MAX).  
>[DEG]  
>[  
>COMMAND SUCCESSFUL  
>CHANGE 4 mA VALUE(-999.9 to 999.9).  
>[-020.0]  
>[  
>COMMAND SUCCESSFUL  
>CHANGE 20 mA VALUE(-999.9 to 999.9).  
>[+020.0]  
109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Setup Menu  
Setup Sensor (continued)  
>[  
>COMMAND SUCCESSFUL  
>CHANGE OFFSET VALUE.  
>[000.0]  
>[  
>COMMAND SUCCESSFUL  
>IS SENSOR AN ALARM(AL) OR EVENT(EV)?  
>[AL]  
>[  
>COMMAND SUCCESSFUL  
>IS SENSOR ALARM LATCHED-YES(Y) OR NO(N)?  
>[Y]  
>[  
>COMMAND SUCCESSFUL  
>CHANGE LOW SETPOINT.  
>[-0015.0]  
>[  
>COMMAND SUCCESSFUL  
>CHANGE HIGH SETPOINT.  
>[+0015.0]  
>[  
>COMMAND SUCCESSFUL  
>DELAY TIME BEFORE TRIGGER (MM:SS)?  
>[00:01]  
>[  
>COMMAND SUCCESSFUL  
110  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Setup Menu  
A.6.4 Setup I/O Matrix  
For details on this feature, see 9.6 - Setup System - Setup I/O Matrix.  
Setup I-O Matrix - Map Input to Output - Main Board Inputs  
SETUP I/O MATRIX  
Program inputs & sensors  
to control outputs  
Select to map inputs or sensors  
1=MAP INPUT TO OUTPUT  
2=MAP SENSOR TO OUTPUT  
3=RETURN TO SETUP MENU  
4=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
MAP INPUT TO OUTPUT  
**********************  
OUTPUT  
NUMBER  
OUTPUT  
DESCRIPTION  
Program input  
to control output(s)  
OUTPUT01 = OUTPUT01  
OUTPUT02 = OUTPUT02  
OUTPUT03 = OUTPUT03  
OUTPUT04 = OUTPUT04  
OUTPUT05 = OUTPUT05  
OUTPUT06 = OUTPUT06  
OUTPUT07 = OUTPUT07  
OUTPUT08 = OUTPUT08  
OUTPUT09 = OUTPUT09  
OUTPUT10 = OUTPUT10  
OUTPUT11 = OUTPUT11  
OUTPUT12 = OUTPUT12  
OUTPUT13 = OUTPUT13  
OUTPUT14 = OUTPUT14  
OUTPUT15 = OUTPUT15  
OUTPUT16 = OUTPUT16  
**********************  
Select input to map  
INPUT  
OUTPUTS  
12345678910111213141516  
1=INPUT_01 YNNNNNNNN N N N N N N N  
2=INPUT_02 NYNNNNNNN N N N N N N N  
3=INPUT_03 NNYNNNNNN N N N N N N N  
4=INPUT_04 NNNYNNNNN N N N N N N N  
5=INPUT_05 NNNNYNNNN N N N N N N N  
6=INPUT_06 NNNNNYNNN N N N N N N N  
7=INPUT_07 NNNNNNYNN N N N N N N N  
8=INPUT_08 NNNNNNNYN N N N N N N N  
9=EXPANSION BOARD INPUTS  
0=RETURN TO SETUP I/O MATRIX  
I=RETURN TO SETUP MENU  
SELECT A NUMBER:1  
>MAP INPUT_01 TO OUTPUT01-YES(Y) OR NO(N)?  
>[Y]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_01 TO OUTPUT02-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_01 TO OUTPUT03-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_01 TO OUTPUT04-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_01 TO OUTPUT05-YES(Y) OR NO(N)?  
>[N]  
111  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Setup Menu  
Setup I-O Matrix - Map Input to Output - Main Board Inputs (continued)  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_01 TO OUTPUT06-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_01 TO OUTPUT07-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_01 TO OUTPUT08-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_01 TO OUTPUT09-YES(Y) OR NO(N)?  
>[Y]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_01 TO OUTPUT10-YES(Y) OR NO(N)?  
>[Y]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_01 TO OUTPUT11-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_01 TO OUTPUT12-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_01 TO OUTPUT13-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_01 TO OUTPUT14-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_01 TO OUTPUT15-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_01 TO OUTPUT16-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
112  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Setup Menu  
Setup I-O Matrix - Map Input to Output - Expansion Board Inputs  
SETUP I/O MATRIX  
Program inputs & sensors  
to control outputs  
Select to map inputs or sensors  
1=MAP INPUT TO OUTPUT  
2=MAP SENSOR TO OUTPUT  
3=RETURN TO SETUP MENU  
4=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
MAP INPUT TO OUTPUT  
**********************  
OUTPUT  
NUMBER  
OUTPUT  
DESCRIPTION  
Program input  
to control output(s)  
OUTPUT01 = OUTPUT01  
OUTPUT02 = OUTPUT02  
OUTPUT03 = OUTPUT03  
OUTPUT04 = OUTPUT04  
OUTPUT05 = OUTPUT05  
OUTPUT06 = OUTPUT06  
OUTPUT07 = OUTPUT07  
OUTPUT08 = OUTPUT08  
OUTPUT09 = OUTPUT09  
OUTPUT10 = OUTPUT10  
OUTPUT11 = OUTPUT11  
OUTPUT12 = OUTPUT12  
OUTPUT13 = OUTPUT13  
OUTPUT14 = OUTPUT14  
OUTPUT15 = OUTPUT15  
OUTPUT16 = OUTPUT16  
**********************  
Select input to map  
INPUT  
OUTPUTS  
12345678910111213141516  
1=INPUT_01 YNNNNNNNN N N N N N N N  
2=INPUT_02 NYNNNNNNN N N N N N N N  
3=INPUT_03 NNYNNNNNN N N N N N N N  
4=INPUT_04 NNNYNNNNN N N N N N N N  
5=INPUT_05 NNNNYNNNN N N N N N N N  
6=INPUT_06 NNNNNYNNN N N N N N N N  
7=INPUT_07 NNNNNNYNN N N N N N N N  
8=INPUT_08 NNNNNNNYN N N N N N N N  
9=EXPANSION BOARD INPUTS  
0=RETURN TO SETUP I/O MATRIX  
I=RETURN TO SETUP MENU  
SELECT A NUMBER:9  
MAP INPUT TO OUTPUT  
**********************  
OUTPUT  
NUMBER  
12345678910111213141516  
OUTPUT  
DESCRIPTION  
1=INPUT_09 NNNNNNNNN N N N N N N N  
2=INPUT_10 NNNNNNNNN N N N N N N N  
3=INPUT_11 NNNNNNNNN N N N N N N N  
4=INPUT_12 NNNNNNNNN N N N N N N N  
5=INPUT_13 NNNNNNNNN N N N N N N N  
6=INPUT_14 NNNNNNNNN N N N N N N N  
7=INPUT_15 NNNNNNNNN N N N N N N N  
8=INPUT_16 NNNNNNNNN N N N N N N N  
9=INPUT_17 NNNNNNNNN N N N N N N N  
0=INPUT_18 NNNNNNNNN N N N N N N N  
A=INPUT_19 NNNNNNNNN N N N N N N N  
B=INPUT_20 NNNNNNNNN N N N N N N N  
C=INPUT_21 NNNNNNNNN N N N N N N N  
D=INPUT_22 NNNNNNNNN N N N N N N N  
E=INPUT_23 NNNNNNNNN N N N N N N N  
F=INPUT_24 NNNNNNNNN N N N N N N N  
G=RETURN TO SETUP I/O MATRIX  
OUTPUT01 = OUTPUT01  
OUTPUT02 = OUTPUT02  
OUTPUT03 = OUTPUT03  
OUTPUT04 = OUTPUT04  
OUTPUT05 = OUTPUT05  
OUTPUT06 = OUTPUT06  
OUTPUT07 = OUTPUT07  
OUTPUT08 = OUTPUT08  
OUTPUT09 = OUTPUT09  
OUTPUT10 = OUTPUT10  
OUTPUT11 = OUTPUT11  
OUTPUT12 = OUTPUT12  
OUTPUT13 = OUTPUT13  
OUTPUT14 = OUTPUT14  
OUTPUT15 = OUTPUT15  
OUTPUT16 = OUTPUT16  
**********************  
H=RETURN TO SETUP MENU  
SELECT A NUMBER:9  
113  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Setup Menu  
Setup I-O Matrix - Map Input to Output - Expansion Board Inputs (continued)  
>MAP INPUT_09 TO OUTPUT01-YES(Y) OR NO(N)?  
>[Y]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_09 TO OUTPUT02-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_09 TO OUTPUT03-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_09 TO OUTPUT04-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_09 TO OUTPUT05-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_09 TO OUTPUT06-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_09 TO OUTPUT07-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_09 TO OUTPUT08-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_09 TO OUTPUT09-YES(Y) OR NO(N)?  
>[Y]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_09 TO OUTPUT10-YES(Y) OR NO(N)?  
>[Y]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_09 TO OUTPUT11-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_09 TO OUTPUT12-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_09 TO OUTPUT13-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_09 TO OUTPUT14-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_09 TO OUTPUT15-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP INPUT_09 TO OUTPUT16-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
114  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Setup Menu  
Setup I-O Matrix - Map Sensor to Output  
SETUP I/O MATRIX  
Program inputs & sensors  
to control outputs  
Select to map inputs or sensors  
1=MAP INPUT TO OUTPUT  
2=MAP SENSOR TO OUTPUT  
3=RETURN TO SETUP MENU  
4=RETURN TO MAIN MENU  
SELECT A NUMBER:2  
MAP SENSOR TO OUTPUT  
**********************  
OUTPUT  
NUMBER  
OUTPUT  
DESCRIPTION  
Program sensor  
to control output(s)  
OUTPUT01 = OUTPUT01  
OUTPUT02 = OUTPUT02  
OUTPUT03 = OUTPUT03  
OUTPUT04 = OUTPUT04  
OUTPUT05 = OUTPUT05  
OUTPUT06 = OUTPUT06  
OUTPUT07 = OUTPUT07  
OUTPUT08 = OUTPUT08  
OUTPUT09 = OUTPUT09  
OUTPUT10 = OUTPUT10  
OUTPUT11 = OUTPUT11  
OUTPUT12 = OUTPUT12  
OUTPUT13 = OUTPUT13  
OUTPUT14 = OUTPUT14  
OUTPUT15 = OUTPUT15  
OUTPUT16 = OUTPUT16  
**********************  
Select sensor to map  
SENSOR  
OUTPUTS  
12345678910111213141516  
1=SENSOR_1 HIGH STPT NNNNNNNNN N N N N N N N  
2=SENSOR_1 LOW STPT NNNNNNNNN N N N N N N N  
3=SENSOR_2 HIGH STPT NNNNNNNNN N N N N N N N  
4=SENSOR_2 LOW STPT NNNNNNNNN N N N N N N N  
5=SENSOR_3 HIGH STPT NNNNNNNNN N N N N N N N  
6=SENSOR_3 LOW STPT NNNNNNNNN N N N N N N N  
7=SENSOR_4 HIGH STPT NNNNNNNNN N N N N N N N  
8=SENSOR_4 LOW STPT NNNNNNNNN N N N N N N N  
9=RETURN TO SETUP I/O MATRIX  
0=RETURN TO SETUP MENU  
SELECT A NUMBER:1  
>MAP SENSOR_1 HIGH STPT TO OUTPUT01-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP SENSOR_1 HIGH STPT TO OUTPUT02-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP SENSOR_1 HIGH STPT TO OUTPUT03-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP SENSOR_1 HIGH STPT TO OUTPUT04-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP SENSOR_1 HIGH STPT TO OUTPUT05-YES(Y) OR NO(N)?  
>[N]  
115  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Setup Menu  
Setup I-O Matrix - Map Sensor to Output (continued)  
>[  
>COMMAND SUCCESSFUL  
>MAP SENSOR_1 HIGH STPT TO OUTPUT06-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP SENSOR_1 HIGH STPT TO OUTPUT07-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP SENSOR_1 HIGH STPT TO OUTPUT08-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP SENSOR_1 HIGH STPT TO OUTPUT08-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP SENSOR_1 HIGH STPT TO OUTPUT09-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP SENSOR_1 HIGH STPT TO OUTPUT10-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP SENSOR_1 HIGH STPT TO OUTPUT11-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP SENSOR_1 HIGH STPT TO OUTPUT12-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP SENSOR_1 HIGH STPT TO OUTPUT13-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP SENSOR_1 HIGH STPT TO OUTPUT14-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP SENSOR_1 HIGH STPT TO OUTPUT15-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>MAP SENSOR_1 HIGH STPT TO OUTPUT16-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
116  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Setup Menu  
A.6.5 Setup Output  
For details on this feature, see 9.7 - Setup System - Setup Output.  
Setup Output - Main Board Outputs  
SETUP OUTPUT  
Setup for discrete  
output points  
Select output to edit  
OUTPUT  
DEFINITION  
1=OUTPUT01  
2=OUTPUT02  
3=OUTPUT03  
4=OUTPUT04  
5=OUTPUT05  
6=OUTPUT06  
7=OUTPUT07  
8=OUTPUT08  
NO  
NC  
NO  
NC  
NO  
NC  
NO  
NC  
******************  
NO=NORMALLY OPENED  
NC=NORMALLY CLOSED  
******************  
9=EXPANSION BOARD OUTPUTS  
0=RETURN TO SETUP MENU  
I=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
>CHANGE LABEL(8 CHARACTERS MAX).  
>[OUTPUT01]  
>[  
>COMMAND SUCCESSFUL  
>SET TO NORMALLY OPENED(NO) OR NORMALLY CLOSED(NC).  
>[NO]  
>[  
>COMMAND SUCCESSFUL  
117  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Setup Menu  
Setup Output - Expansion Board Outputs  
SETUP OUTPUT  
Setup for discrete  
output points  
Select output to edit  
OUTPUT  
DEFINITION  
1=OUTPUT01  
2=OUTPUT02  
3=OUTPUT03  
4=OUTPUT04  
5=OUTPUT05  
6=OUTPUT06  
7=OUTPUT07  
8=OUTPUT08  
NO  
NC  
NO  
NC  
NO  
NC  
NO  
NC  
******************  
NO=NORMALLY OPENED  
NC=NORMALLY CLOSED  
******************  
9=EXPANSION BOARD OUTPUTS  
0=RETURN TO SETUP MENU  
I=RETURN TO MAIN MENU  
SELECT A NUMBER:9  
SETUP OUTPUT  
Setup for discrete  
output points  
Select output to edit  
OUTPUT  
DEFINITION  
1=OUTPUT09  
2=OUTPUT10  
3=OUTPUT11  
4=OUTPUT12  
5=OUTPUT13  
6=OUTPUT14  
7=OUTPUT15  
8=OUTPUT16  
NO  
NC  
NO  
NC  
NO  
NC  
NO  
NC  
******************  
NO=NORMALLY OPENED  
NC=NORMALLY CLOSED  
NOTE:SET BY DIPSWITCH  
******************  
9=RETURN TO SETUP MENU  
0=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
>CHANGE LABEL(8 CHARACTERS MAX).  
>[OUTPUT09]  
>[  
>COMMAND SUCCESSFUL  
118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Setup Menu  
A.6.6 Setup Modem & Pagers  
For details on this topic, see 9.8 - Setup System - Setup Modem & Pagers.  
Pager Setup  
Setup Modem & Pagers - Pager Setup  
SETUP MODEM&PAGERS  
Input pager and  
modem information  
Select pager or modem  
CURRENT NUMBER  
*******************  
An "A" is required  
as 1st character  
1=PAGER NUMBER 1  
2=PAGER NUMBER 2  
3=PAGER NUMBER 3  
4=PAGER NUMBER 4  
5=MODEM CONFIGURATION  
6=RETURN TO SETUP MENU  
7=RETURN TO MAIN MENU  
for an alpha pager,  
an "N" for a numeric  
pager, and an "M"  
for a remote modem.  
*******************  
SELECT A NUMBER:1  
>ENTER PAGER NUMBER(40 CHARACTERS MAX).  
>[]  
>[  
>COMMAND SUCCESSFUL  
>ENTER PAGER PIN NUMBER (20 CHARACTERS MAX).  
>[]  
>[  
>COMMAND SUCCESSFUL  
>ENABLE COMMUNICATIONS CHECK-YES(Y) OR NO(N)?(Service Terminal Interface only)  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>ENTER TIME TO PERFORM COMMUNICATIONS CHECK(HH:MM).(Service Terminal Interface only)  
>[00:00]  
>[  
>COMMAND SUCCESSFUL  
119  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Setup Menu  
Modem Setup  
Setup Modem & Pagers - Modem Setup  
SETUP MODEM&PAGERS  
Input pager and  
modem information  
Select pager or modem  
CURRENT NUMBER  
*******************  
An "A" is required  
as 1st character  
1=PAGER NUMBER 1  
2=PAGER NUMBER 2  
3=PAGER NUMBER 3  
4=PAGER NUMBER 4  
5=MODEM CONFIGURATION  
6=RETURN TO SETUP MENU  
7=RETURN TO MAIN MENU  
for an alpha pager,  
an "N" for a numeric  
pager, and an "M"  
for a remote modem.  
*******************  
SELECT A NUMBER:5  
>CHANGE MODEM INITIALIZATION STRING(40 CHARACTERS MAX).  
>[ATS0=1]  
>[  
>COMMAND SUCCESSFUL  
>ENTER UNIVERSAL MONITOR PHONE NUMBER(40 CHARACTERS MAX).(Service Terminal Interface only)  
>[]  
>[  
>COMMAND SUCCESSFUL  
>ENABLE MODEM DIAGNOSTIC MESSAGES-YES(Y) OR NO(N)?(Service Terminal Interface only)  
>[N]  
>[  
>COMMAND SUCCESSFUL  
>CHANGE MODEM DIAL PREFIX.(Service Terminal Interface only)  
>[ATE0X4DT]  
>[  
>COMMAND SUCCESSFUL  
>CHANGE MODEM HANG UP DELAY AFTER A CALL(99 SEC MAX).(Service Terminal Interface only)  
>[10]  
>[  
>COMMAND SUCCESSFUL  
120  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Setup Menu  
A.6.7 Setup System Info  
This section presents Service Terminal Interface screens for choices 1 through 9 in the Setup System  
Information menu shown below. For details on this topic, see 9.9 - Setup System - Setup System  
Info.  
Setup System Info  
SETUP SYSTEM INFORMATION  
1=CHANGE PASSWORD  
2=CHANGE DATE & TIME  
3=SETUP SITE ID  
4=CONNECT BATTERY  
5=BACKUP & UPLOAD CONFIGURATION FILE  
6=SETUP SERVICE PHONE NUMBER  
7=SET PANEL TO FACTORY DEFAULTS  
8=PERFORM FIRMWARE UPDATE  
9=INITIATE REMOTE ALARM TEST  
0=RETURN TO SETUP MENU  
I=RETURN TO MAIN MENU  
SELECT A NUMBER:  
Change Password  
For details on this feature, see 9.9.1 - Change Password.  
Change Password  
CHANGE PASSWORD  
1=CHANGE PASSWORD  
2=RETURN TO SETUP SYSTEM INFO MENU  
3=RETURN TO SETUP MENU  
4=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
>ENTER ORIGINAL PASSWORD(MUST BE 4 CHARACTERS).  
>
>ENTER NEW PASSWORD(MUST BE 4 CHARACTERS).  
>
>ENTER NEW PASSWORD AGAIN FOR CONFIRMATION.  
>
>PASSWORD CHANGE SUCCESSFUL  
121  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Setup Menu  
Change Date & Time/Automatic Daylight Saving Time  
Change Date & Time  
CHANGE DATE & TIME  
CURRENT DATE & TIME DST  
1=CHANGE DATE & TIME  
28-AUG-02 14:45:10 Y  
2=RETURN TO SETUP SYSTEM INFO MENU  
3=RETURN TO SETUP MENU  
4=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
>CHANGE DATE & TIME(DD-MON-YY HR:MM:SS).  
>[28-AUG-02 14:45:10]  
>[  
>COMMAND SUCCESSFUL  
>ENABLE DAYLIGHT SAVINGS TIME-YES(Y) OR NO(N)?  
>[Y]  
>[  
>COMMAND SUCCESSFUL  
Setup Site ID  
For details on this feature, see 9.9.3 - Setup Site ID.  
Setup Site ID  
SETUP SITE ID  
Define name to  
reference panel  
CURRENT SITE ID  
1=SETUP SITE ID  
2=RETURN TO SETUP SYSTEM INFO MENU  
3=RETURN TO SETUP MENU  
4=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
>ENTER SITE ID NAME(40 CHARACTERS MAX).  
>[]  
>[  
>COMMAND SUCCESSFUL  
122  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Setup Menu  
Connect Battery  
For details on this feature, see 9.9.4 - Connect Battery.  
Connect Battery  
CONNECT BATTERY  
CURRENT SETTING  
1=CONNECT BATTERY  
Y
2=RETURN TO SETUP SYSTEM INFO MENU  
3=RETURN TO SETUP MENU  
4=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
>IS THE BATTERY CONNECTED-YES(Y) OR NO(N)?  
>[Y]  
>[  
>COMMAND SUCCESSFUL  
Backup and Upload Configuration File (Service Terminal Interface only)  
Backup & Upload Configuration File - Backup  
BACKUP AND UPLOAD CONFIGURATION FILE  
Backup from panel saves panel configurations  
Upload to panel restores panel configurations  
Select to backup or upload file  
1=BACKUP CONFIGURATION FILE  
2=UPLOAD CONFIGURATION FILE  
3=RETURN TO SETUP SYSTEM INFO MENU  
4=RETURN TO SETUP MENU  
5=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
>INITIATE A BACKUP OF CONFIGURATION FILE-YES(Y) OR NO(N)?  
>[N]  
>[  
INSTRUCTIONS TO PERFORM BACKUP:  
ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION  
- SELECT TRANSFER FROM THE TOOLBAR  
- SELECT RECEIVE FILE  
- ENTER FOLDER WHERE FILE IS TO BE RECEIVED  
- SELECT XMODEM FROM THE PROTOCOL BOX  
- SELECT RECEIVE BUTTON AND ENTER FILE NAME,E.G., UMCONFIG.SAV  
>BACKUP SUCCESSFUL  
123  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Setup Menu  
Backup & Upload Configuration File - Upload  
BACKUP AND UPLOAD CONFIGURATION FILE  
Backup from panel saves panel configurations  
Upload to panel restores panel configurations  
Select to backup or upload file  
1=BACKUP CONFIGURATION FILE  
2=UPLOAD CONFIGURATION FILE  
3=RETURN TO SETUP SYSTEM INFO MENU  
4=RETURN TO SETUP MENU  
5=RETURN TO MAIN MENU  
SELECT A NUMBER:2  
>INITIATE AN UPLOAD OF CONFIGURATION FILE-YES(Y) OR NO(N)?  
>[N]  
>[  
INSTRUCTIONS TO PERFORM UPLOAD:  
ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION  
- SELECT TRANSFER FROM THE TOOLBAR  
- SELECT SEND FILE  
- ENTER FILE NAME-CONFIGURATION FILE LOCATION & NAME  
- SELECT XMODEM FROM THE PROTOCOL BOX  
- SELECT SEND BUTTON  
>UPLOAD SUCCESSFUL  
Setup Service Phone Number  
Setup Service Phone Number  
SETUP SERVICE PHONE NUMBER  
This number receives all alarms  
in addition to the 4 pagers  
CURRENT NUMBER  
1=SETUP SERVICE PHONE NUMBER  
2=RETURN TO SETUP SYSTEM INFO MENU  
3=RETURN TO SETUP MENU  
******************  
An “M” is required  
as 1st character.  
******************  
4=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
>ENTER SERVICE PHONE NUMBER(40 CHARACTERS MAX).  
>[]  
>[  
>COMMAND SUCCESSFUL  
>ENABLE COMMUNICATIONS CHECK-YES(Y) OR NO(N)?(Service Terminal Interface only)  
>[N]  
>
>COMMAND SUCCESSFUL  
>ENTER TIME TO PERFORM COMMUNICATIONS CHECK(HH:MM).(Service Terminal Interface only)  
>[00:00]  
>[  
>COMMAND SUCCESSFUL  
124  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Setup Menu  
Factory Defaults  
For details on this feature, see 9.9.8 - Factory Defaults.  
Factory Defaults  
RESTORE FACTORY DEFAULTS  
This command restores all panel  
information to factory settings  
1=RESTORE FACTORY DEFAULTS  
2=RETURN TO SETUP SYSTEM INFO MENU  
3=RETURN TO SETUP MENU  
4=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
>RESTORE THE PANEL TO FACTORY SETTINGS-YES(Y) OR NO(N)?  
>[N]  
[[  
>COMMAND SUCCESSFUL  
Firmware Update (Service Terminal Interface only)  
only).  
Firmware Update  
PERFORM FIRMWARE UPDATE  
This command will update  
the existing firmware  
1=PERFORM FIRMWARE UPDATE  
2=RETURN TO SETUP SYSTEM INFO MENU  
3=RETURN TO SETUP MENU  
4=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
>PERFORM FIRMWARE UPDATE-YES(Y) OR NO(N)?  
>[N]  
>[  
INSTRUCTIONS TO PERFORM FIRMWARE UPDATE:  
ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION  
- SELECT TRANSFER FROM THE TOOLBAR  
- SELECT SEND FILE  
- ENTER FILE NAME-FIRMWARE FILE LOCATION & NAME  
- SELECT XMODEM FROM THE PROTOCOL BOX  
- SELECT SEND BUTTON  
>WAITING TO SEND PROGRAM FILE  
>DONE  
>CHECKSUM IS....  
>PROGRAM VERSION....  
>WAITING TO SEND FLASH FILE  
>DONE  
>FIRMWARE UPDATE SUCCESSFUL  
125  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Setup Menu  
Initiate Remote Alarm Test (Service Terminal Interface only)  
only).  
Initiate Remote Alarm Test  
INITIATE REMOTE ALARM TEST  
This command simulates an alarm  
to test alarm notification setup  
for the service phone number  
1=INITIATE REMOTE ALARM TEST  
2=RETURN TO SETUP SYSTEM INFO MENU  
3=RETURN TO SETUP MENU  
4=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
>SIMULATE AN ALARM CONDITION-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
126  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Setup Menu  
A.6.8 Connect Expansion Board  
For details on this feature, see 9.10 - Setup Exp Board - Optional Expansion Board.  
Connect Expansion Board  
CONNECT EXPANSION BOARD  
CURRENT SETTING  
1=CONNECT EXPANSION BOARD  
2=RETURN TO SETUP MENU  
3=RETURN TO MAIN MENU  
N
SELECT A NUMBER:1  
>IS THE EXPANSION BOARD CONNECTED-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
127  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Setup Menu  
A.6.9 Override Output  
For details on this feature, see 9.11 - Manual Output Ctrl.  
Override Output - Main Board Outputs  
OVERRIDE OUTPUT  
Manually override  
an output point  
Select output to override  
OUTPUT  
CONTROL  
1=OUTPUT01  
2=OUTPUT02  
3=OUTPUT03  
4=OUTPUT04  
5=OUTPUT05  
6=OUTPUT06  
7=OUTPUT07  
8=OUTPUT08  
AUTO  
AUTO  
AUTO  
AUTO  
AUTO  
AUTO  
AUTO  
AUTO  
********************************************  
AUTO =CONTROL BY PANEL  
MAN ON =OVERRIDE IN ON POSITION BY OPERATOR  
MAN OFF=OVERRIDE IN OFF POSITION BY OPERATOR  
********************************************  
9=EXPANSION BOARD OUTPUTS  
0=RETURN TO SETUP MENU  
I=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
>OVERRIDE OUTPUT OUTPUT01-AUTO(2),MAN ON(1),MAN OFF(0).  
>[2]  
>[  
>COMMAND SUCCESSFUL  
128  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Setup Menu  
Override Output - Expansion Board Outputs  
OVERRIDE OUTPUT  
Manually override  
an output point  
Select output to override  
OUTPUT  
CONTROL  
1=OUTPUT01  
2=OUTPUT02  
3=OUTPUT03  
4=OUTPUT04  
5=OUTPUT05  
6=OUTPUT06  
7=OUTPUT07  
8=OUTPUT08  
AUTO  
AUTO  
AUTO  
AUTO  
AUTO  
AUTO  
AUTO  
AUTO  
********************************************  
AUTO =CONTROL BY PANEL  
MAN ON =OVERRIDE IN ON POSITION BY OPERATOR  
MAN OFF=OVERRIDE IN OFF POSITION BY OPERATOR  
********************************************  
9=EXPANSION BOARD OUTPUTS  
0=RETURN TO SETUP MENU  
I=RETURN TO MAIN MENU  
SELECT A NUMBER:9  
OVERRIDE OUTPUT  
Manually override  
an output point  
Select output to override  
OUTPUT  
CONTROL  
1=OUTPUT09  
2=OUTPUT10  
3=OUTPUT11  
4=OUTPUT12  
5=OUTPUT13  
6=OUTPUT14  
7=OUTPUT15  
8=OUTPUT16  
AUTO  
AUTO  
AUTO  
AUTO  
AUTO  
AUTO  
AUTO  
AUTO  
********************************************  
AUTO =CONTROL BY PANEL  
MAN ON =OVERRIDE IN ON POSITION BY OPERATOR  
MAN OFF=OVERRIDE IN OFF POSITION BY OPERATOR  
********************************************  
9=RETURN TO SETUP MENU  
0=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
>OVERRIDE OUTPUT OUTPUT09-AUTO(2),MAN ON(1),MAN OFF(0).  
>[2]  
>[  
>COMMAND SUCCESSFUL  
129  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Setup Menu  
A.6.10 Clear Alarms & Logs  
For details on this topic, see 9.12 - Clear Alarms & Logs.  
Clear Active Alarms  
For details on this feature, see 9.12.1 - Clear Active Alarms.  
Clear Alarms & Logs - Clear Active Alarms  
CLEAR ALARMS&LOGS  
Clear active alarms  
or log records  
Select the log to clear  
1=CLEAR ACTIVE ALARMS  
2=CLEAR ALARM LOG  
3=CLEAR EVENT LOG  
4=CLEAR TREND LOGS  
5=RETURN TO SETUP MENU  
6=RETURN TO MAIN MENU  
SELECT A NUMBER:1  
>CLEAR ALL THE ACTIVE ALARMS-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
Clear the Alarm Log  
For details on this feature, see 9.12.2 - Clear the Alarm Log.  
Clear Alarms & Logs - Clear the Alarm Log  
CLEAR ALARMS&LOGS  
Clear active alarms  
or log records  
Select the log to clear  
1=CLEAR ACTIVE ALARMS  
2=CLEAR ALARM LOG  
3=CLEAR EVENT LOG  
4=CLEAR TREND LOGS  
5=RETURN TO SETUP MENU  
6=RETURN TO MAIN MENU  
SELECT A NUMBER:2  
>CLEAR ALL RECORDS IN THE ALARM LOG-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
130  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Setup Menu  
Clear the Event Log  
For details on this feature, see 9.12.3 - Clear the Event Log.  
Clear Alarms & Logs - Clear the Event Log  
CLEAR ALARMS&LOGS  
Clear active alarms  
or log records  
Select the log to clear  
1=CLEAR ACTIVE ALARMS  
2=CLEAR ALARM LOG  
3=CLEAR EVENT LOG  
4=CLEAR TREND LOGS  
5=RETURN TO SETUP MENU  
6=RETURN TO MAIN MENU  
SELECT A NUMBER:3  
>CLEAR ALL RECORDS IN THE EVENT LOG-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
Clear the Trend Logs  
For details on this feature, see 9.12.4 - Clear the Trend Logs.  
Clear Alarms & Logs - Clear the Trend Logs  
CLEAR ALARMS&LOGS  
Clear active alarms  
or log records  
Select the log to clear  
1=CLEAR ACTIVE ALARMS  
2=CLEAR ALARM LOG  
3=CLEAR EVENT LOG  
4=CLEAR TREND LOGS  
5=RETURN TO SETUP MENU  
6=RETURN TO MAIN MENU  
SELECT A NUMBER:4  
>CLEAR ALL RECORDS IN THE TREND LOGS-YES(Y) OR NO(N)?  
>[N]  
>[  
>COMMAND SUCCESSFUL  
131  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Default Settings Quick Reference Guide  
APPENDIX B - DEFAULT SETTINGS QUICK REFERENCE GUIDE  
This appendix provides a quick reference to default settings for the Universal Monitor and the  
optional Expansion Board. These settings also appear throughout the manual.  
Table 37 Universal Monitor - default settings for inputs and outputs  
Feature  
Default  
Other Options  
Any name (up to eight characters)  
NC (Normally closed)  
LABEL  
INPUT_01 - INPUT_08  
NO (Normally open)  
AL (Alarmable)  
NORM OPEN/CLOSE  
ALARM/EVENT  
LATCHED  
EV (Event)  
NL (Unlatched) / N (No)*  
00:01 (1 second)  
L (Latched) / Y (Yes)*  
DELAY  
Any time (in minutes and seconds) from 00:00 to 99:59  
* NOTE: Different abbreviations are used to designate a digital input as Latched or Unlatched.  
Feature  
Default  
Other Options  
CONNECTED*  
LABEL  
N (Not connected)*  
Y (Connected)**  
SENSOR_1 - SENSOR_4 Any name (up to eight characters)  
UNITS  
Blank  
Any units (up to three characters)  
4 mA  
-999.9  
Can define up to two decimal places—e.g., -99.99  
Can define up to two decimal places—e.g., +99.99  
Can define up to two decimal places—e.g., +00.00  
EV (Event)  
20 mA  
+999.9  
OFFSET  
+000.0  
ALARM/EVENT  
LATCHED  
LOW SETPT  
HIGH SETPT  
SENSOR DELAY  
AL (Alarmable)  
N (Unlatched)  
-0999.9  
Y (Latched)  
Can define up to two decimal places—e.g., -999.99  
Can define up to two decimal places—e.g., +999.99  
Any time (in minutes and seconds) from 00:00 to 99:59  
+0999.9  
00:01 (1 second)  
*
If a sensor is configured as N (Not connected), the display will show an empty reading (blank spaces).  
** If a sensor is configured as Y (Connected) and is functioning properly, the display will show a reading.  
If the connected sensor is not functioning properly, the display will show dashes (------) indicating a problem.  
Digital input  
Input_01  
Input_02  
Input_03  
Input_04  
Input_05  
Input_06  
Input_07  
Input_08  
By default, mapped to digital output:  
Output01  
Output02  
Output03  
Output04  
Output05  
Output06  
Output07  
Output08  
Analog input  
Sensor_1  
Sensor_2  
Sensor_3  
Sensor_4  
By default, mapped to digital output:  
(none)  
(none)  
(none)  
(none)  
Feature  
Default  
Other Options  
LABEL  
OUTPUT01 - OUTPUT08 Any name (up to eight characters)  
NORM OPEN/CLOSE  
NO (Normally open)  
NC (Normally closed)  
132  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Default Settings Quick Reference Guide  
Table 38 Universal Monitor - other default settings  
JUMPER SETTINGS  
Feature  
Default  
Other Options  
Digital output loss-of-power jumpers OFF - Normally Open  
ON - Normally Closed  
Note: Jumper position has no effect when the Universal Monitor has power.  
12VDC/24VDC analog input jumper  
P20 jumper  
24VDC  
Acceptable voltage for all four two-wire analog sensors  
Not jumpered (not  
connected)  
Default: jumpered  
(connected)  
422 TERM jumper  
Default: jumpered  
(connected)  
485 TERM jumper  
Audible horn  
Enabled  
May be disabled via the audible horn jumper  
On (Turn on all output relays)  
Off (outputs controlled by  
programming)  
Manual Override switch  
Feature  
Default  
Other Options  
Any string (up to 40 characters); for international  
dialing, add +GCI=xx, where xx is the country code  
(except B5 countries—see Table 27)  
Initialization String (Init String)  
ATS0=1  
Enable Modem Diagnostic Messages N (disable)  
Y (enable)  
Modem Dial Prefix  
Modem Hang Up Delay After a Call  
DIP SWITCH SETTINGS  
Feature  
ATE0X4DT  
Any string  
10 seconds  
Any number (up to 99 seconds)  
Default  
Other Options  
May be used to reset password to factory default (see  
8-position DIP switch  
All are OFF (down)  
OTHER SETTINGS  
Feature  
Default  
Other Options  
Change state of outputs - automatic  
or manual control  
Force an output ON / OFF via Manual Output Ctrl menu  
Force all outputs ON via hardware switch  
AUTO (automatic control)  
Password  
AAAA  
Any 4 characters (see Table 20 for valid characters)  
Y (reset with silence)  
Reset common alarm with silence  
Battery connected  
N (not reset)  
Y (connected)  
N (not connected)  
133  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Default Settings Quick Reference Guide  
Table 39 Expansion Board - default settings for inputs and outputs  
Feature  
Default  
Other Options  
LABEL  
INPUT_09 - INPUT_24  
NO (Normally open)  
AL (Alarmable)  
Any name (up to eight characters)  
NORM OPEN/CLOSE  
ALARM/EVENT  
LATCHED  
NC (Normally closed)  
EV (Event)  
NL (Unlatched) / N (No)* L (Latched) / Y (Yes)*  
00:01 (1 second) Any time (in minutes and seconds) from 00:00 to 99:59  
DELAY  
* NOTE: Different abbreviations are used to designate a digital input as Latched or Unlatched.  
Digital input  
Input_09  
By default, mapped to digital output:  
(none)  
(none)  
(none)  
Input_10  
Input_11  
.
.
.
(none)  
Input_24  
(none)  
NOTE: By default, no Expansion Board inputs are mapped to any outputs.  
Feature  
Default  
Other Options  
LABEL  
OUTPUT09 - OUTPUT16 Any name (up to eight characters)  
Table 40 Expansion Board - other default settings  
Feature  
Default  
Other Options  
SETUP EXP BOARD (IS THE  
EXPANSION BOARD  
CONNECTED?)  
N (Not connected)  
Y (Connected)  
DIP SWITCH SETTINGS  
Feature  
Default  
Other Options  
S1 Digital output DIP switches  
OTHER SWITCH SETTINGS  
Off (NO - Normally Open) On (NC - Normally Closed)  
Default  
For all switches:  
1 = ON, 0 = OFF  
Feature  
Other Options  
SW1 (factory configured)  
SW2 (factory configured)  
SW3 (factory configured)  
SW4 (factory configured)  
JUMPER SETTINGS  
Feature  
11111111  
11111111  
10000100  
10000100  
Default  
Other Options  
JP2 (factory configured)  
JP3 (factory configured)  
JP4 (factory configured)  
JP5 (factory configured)  
Left two pins jumpered  
Left two pins jumpered  
Left two pins jumpered  
Bottom two pins jumpered —  
134  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Download from Www.Somanuals.com. All Manuals Search And Download.  
MONITORING  
UNIVERSAL MONITOR  
USER MANUAL  
The Company Behind the Products  
Technical Support/Service  
Web Site  
With over a million installations around the globe,  
Liebert is the world leader in computer protection  
systems. Since its founding in 1965, Liebert has  
developed a complete range of support and  
protection systems for sensitive electronics:  
www.liebert.com  
Monitoring  
800-222-5877  
Outside the US: 614-841-6755  
Environmental systems—close-control air  
conditioning from 1 to 60 tons  
Single-Phase UPS  
800-222-5877  
Power conditioning and UPS with power  
ranges from 300 VA to more than 1000 kVA  
Integrated systems that provide both  
environmental and power protection in a  
single, flexible package  
Monitoring and control—from systems of any  
size or location, on-site or remote  
Service and support through more than 100  
service centers around the world and a 24/7  
Customer Response Center  
Outside the US: 614-841-6755  
Three-Phase UPS  
800-543-2378  
Environmental Systems  
800-543-2778  
Outside the United States  
614-888-0246  
While every precaution has been taken to ensure  
the accuracy and completeness of this literature,  
Liebert Corporation assumes no responsibility and  
disclaims all liability for damages resulting from  
use of this information or for any errors or  
omissions.  
Locations  
United States  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, OH 43229  
Italy  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD)  
+39 049 9719 111  
© 2004 Liebert Corporation  
All rights reserved throughout the world.  
Specifications subject to change without notice.  
® Liebert and the Liebert logo are registered  
trademarks of Liebert Corporation. All names  
referred to are trademarks or registered  
trademarks of their respective owners.  
Fax: +39 049 5841 257  
Asia  
23F, Allied Kajima Bldg.  
138 Gloucester Road  
Wanchai  
Hong Kong  
+852 2 572 2201  
Fax: +852 2 831 0114  
SL-31060 (8/04) Rev. 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Kyocera Battery Charger KC 120 1 User Manual
Learning Resources Building Set LER 1909 User Manual
Life Fitness Bicycle LM350000 5 User Manual
Linear Automobile Electronics ak 11 User Manual
LL Bean Weather Radio 0FHC9 User Manual
Magnavox CRT Television MS2730C User Manual
Makita Saw BLS820SFK User Manual
Melissa Vacuum Cleaner 740 096 User Manual
Memorex Home Theater System MW550 User Manual
Merco Savory Toaster POP 2 4 User Manual