LG
LG
Room Air Conditioner
SERVICE MANUAL
MODELS: LAN091CNP (ASNC091F2G0)
LAU091CNP (ASUC091FUG0)
LAN121CNP (ASNC121F2G0)
LAU121CNP (ASUC121FUG0)
LAN091HNP (ASNH091F2G0)
LAU091HNP (ASUH091FUG0)
LAN121HNP (ASNH121F2G0)
LAU121HNP (ASUH121FUG0)
LA090CPI (ASNC091F2G0)
LA090CPO (ASUC091FUG0)
LA120CPI (ASNC091F2G0)
LA120CPO (ASUC091FUG0)
LA090HPI (ASNH091F2G0)
LA090HPO (ASUH091FUG0)
LA120HPI (ASNH121F2G0)
LA120HPO (ASUH121FUG0)
CAUTION
• BEFORE SERVICING THE UNIT, READ THE SAFETY
PRECAUTIONS IN THIS MANUAL.
• ONLY FOR AUTHORIZED SERVICE PERSONNEL.
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must
be followed.
â– Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
â– Meanings of symbols used in this manual are as shown below.
Be sure not to do.
Be sure to follow the instruction.
â– Installation
Do not use damaged power
cords, plugs, or a loose socket.
For electrical work, contact the
dealer, seller, a qualified electri-
cian, or an Authorized Service
Center.
Always use the power plug and
socket with the ground terminal.
• There is risk of fire or electric
shock.
• There is risk of fire or electric
shock.
• There is risk of electric shock.
Install the panel and the cover of
control box securely.
Do not modify or extend the
power cord.
Do not install, remove, or re-
install the unit by yourself (cus-
tomer).
• There is risk of fire or electric
shock.
• There is risk of fire or electric
shock.
• There is risk of fire, electric shock,
explosion, or injury.
Service Manual 3
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Precautions
Be cautious when unpacking and For installation, always contact
Do not install the product on a
defective installation stand.
installing the product.
the dealer or an Authorized
Service Center.
• Sharp edges could cause injury. Be • There is risk of fire, electric shock,
• It may cause injury, accident, or
damage to the product.
especially careful of the case
edges and the fins on the con-
denser and evaporator.
explosion, or injury.
Be sure the installation area
does not deteriorate with age.
Do not let the air conditioner run
for a long time when the humidity
is very high and a door or a win-
dow is left open.
• If the base collapses, the air condi- • Moisture may condense and wet or
tioner could fall with it, causing
property damage, product failure,
and personal injury.
damage furnishings.
â– Operation
Take care to ensure that power
cords could not be pulled out or
damaged during operation.
Do not place anything on the
power cord.
Do not turn the air-conditioner
ON or OFF by plugging or
unplugging the power plug.
• There is risk of fire or electrical
shock.
• There is risk of fire or electrical
shock.
• There is risk of fire or electric
shock.
4 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Precautions
Use a dedicated outlet for this
appliance.
Grasp the plug to remove the
cord from the outlet. Do not
touch it with wet hands.
Do not place a heater or other
appliances near the power cable.
• There is risk of fire or electrical
shock.
• There is risk of fire or electrical
shock.
• There is risk of fire and electric
shock.
Do not allow water to run into
electric parts.
Do not store or use flammable
gas or combustibles near the air
conditioner.
Do not use the product in a tight-
ly closed space for a long time.
• It may cause There is risk of fire,
failure of the product, or electric
shock.
• There is risk of fire or failure of
product.
• Oxygen deficiency could occur.
When flammable gas leaks, turn
off the gas and open a window
for ventilation before turn the
product on. DO NOT use the tele-
phone or turn switches on or off.
Unplug the unit if strange
sounds, odors, or smoke comes
from it.
Stop operation and close the
window in storm or hurricane. If
possible, remove the air condi-
tioner from the window before
the hurricane arrives.
• There is risk of explosion or fire.
• There is risk of electrical shock or
fire
• There is risk of property damage,
failure of product, or electric shock.
Service Manual 5
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Precautions
Do not open the inlet grill of the
product during operation. (Do
not touch the electrostatic filter,
if the unit is so equipped.)
When the product is soaked
(flooded or submerged), contact
an Authorized Service Center.
Ventilate the product from time
to time when operating it togeth-
er with a stove, etc.
• There is risk of physical injury,
electric shock, or product failure.
• There is risk of fire or eletric
shock.
• There is risk of fire or electrical
shock.
Unplug the appliance before per-
forming cleaning or mainte-
nance.
When the product is not be used
for a long time, disconnect the
power supply plug or turn off the
breaker.
Take care to ensure that nobody
could step on or fall onto the
outdoor unit.
• There is risk of electrical shock.
• There is risk of product damage or • This could result in personal injury
failure, or unintended operation.
and product damage.
â– Installation
Always check for gas (refriger-
ant) leakage after installation or
repair of product.
Install the drain hose to ensure
that water is drained away prop-
erly.
Keep level even when installing
the product.
• Low refrigerant levels may cause
failure of product.
• A bad connection may cause water • To avoid vibration or water leakage.
leakage.
90Ëš
6 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Precautions
Do not install the product where
the noise or hot air from the out-
door unit could damage the
neighborhoods.
Use two or more people to lift
and transport the air conditioner.
Do not install the product where
it will be exposed to sea wind
(salt spray) directly.
• It may cause a problem for your
neighbors.
• Avoid personal injury.
• It may cause corrosion on the prod-
uct. Corrosion, particularly on the
condenser and evaporator fins,
could cause product malfunction or
inefficient operation.
â– Operation
Do not direct airflow at room
occupants. (Don't sit in the
draft.)
Do not use the product for spe-
cial purposes, such as preserv-
ing foods, works of art, etc. It is a
consumer air conditioner, not a
precision refrigeration system.
Do not block the inlet or outlet of
air flow.
• This could damage your health.
• There is risk of damage or loss of
• It may cause product failure.
property.
Use a soft cloth to clean. Do not
use harsh detergents, solvents,
etc.
Do not touch the metal parts of
the product when removing the
air filter. They are very sharp!
Do not step on or put anyting on
the product. (outdoor units)
• There is risk of fire, electric shock,
or damage to the plastic parts of
the product.
• There is risk of personal injury.
• There is risk of personal injury and
failure of product.
Service Manual 7
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Precautions
Always insert the filter securely.
Clean the filter every two weeks
or more often if necessary.
Do not insert hands or other
objects through the air inlet or
outlet while the air conditioner is
plugged in.
Do not drink the water drained
from the unit.
• A dirty filter reduces the efficiency
of the air conditioner and could
cause product malfunction or dam-
age.
• There are sharp and moving parts
that could cause personal injury.
• It is not sanitary and could cause
serious health issues.
Use a firm stool or ladder when cleaning or main-
taining the air conditioner.
Replace the all batteries in the remote control with
new ones of the same type. Do not mix old and new
batteries or different types of batteries.
• Be careful and avoid personal injury.
• There is risk of fire or explosion
â– Disuse
Do not recharge or disassemble the batteries. Do
not dispose of batteries in a fire.
If the liquid from the batteries gets onto your skin
or clothes, wash it well with clean water. Do not use
the remote if the batteries have leaked.
• They may burn or explode.
• The chemicals in batteries could cause burns or other
health hazards.
8 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
Dimensions
Symbols Used in this Manual
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the
air conditioner.
This symbol indicates special notes.
NOTICE
Indoor Unit
Hanger Hole
W
D
H
Fix Hole
Pipe Hole
Model
INDOOR UNIT
Dimension
W
H
mm(inch)
mm(inch)
mm(inch)
600(23.6)
600(23.6)
146(5.7)
D
Service Manual 9
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
Outdoor Unit
L2
W
L3
Gas side
(3-way valve)
Liquid side
(2-way valve)
MODEL
unit
9k, 12k Models
DIM
W
mm
mm
mm
mm
mm
mm
mm
mm
770(30.3)
540(21.3)
245(9.6)
285(11.2)
64(2.5)
H
D
L1
L2
L3
L4
L5
518(20.4)
10(0.4)
100(3.9)
10 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Specifications
Product Specifications
AS-C091F2G0(LA091CNP) AS-C121F2G0(LA121CNP) AS-H091F2G0(LA091HNP) AS-H121F2G0(LA121HNP)
AS-C091F2G0(LA090CP) AS-C121F2G0(LA120CP) AS-H091F2G0(LA090HP) AS-H121F2G0(LA120HP)
Models
Cooling Capacity
(Min~Rating~Max)
Heating Capacity
(Min~Rating~Max)
Power Input
Running Current
Starting Current
kW
Btu/h
kW
Btu/h
W
A
A
2.87
3.37
2.87
3.37
9,800
11,500
9,800
11,500
-
-
2.87
3.37
-
-
9,800
11,500
Cooling/Heating
Cooling/Heating
Cooling/Heating
980
1,100
980/980
1,100/1,100
9.4
10
9.4/9.4
10/10
57.0
57.0
57.0/57.0
57.0/57.0
W/W
Btu/h.W
W/W
Ø / V / Hz
%
2.93
3.06
2.93
3.06
EER
10.0
10.5
10.0
10.5
COP
Power Supply
Power Factor
-
-
2.93
3.06
1/115/60
1/115/60
1/115/60
1/115/60
90.7
95.7
90.7
95.7
Indoor,Max
Outdoor,Max
m
m
3/min(cfm)
3/min(cfm)
l/h
9.3(330)
9.3(330)
9.3(330)
9.3(330)
Air Flow Rate
25(883)
25(883)
25(883)
25(883)
Moisture Removal
Sound Level
1.4
1.4
1.4
1.4
Indoor,H/M/L
Outdoor,Max
dB(A)+3
dB(A)+3
g(oz)
41/35/29
41/35/29
41/35/29
41/35/29
48
48
48
48
Refrigerant & Charge(at 7.5m)
Type
R410A, 900(31.8)
R410A, 900(31.8)
R410A, 900(31.8)
R410A, 900(31.8)
Rotary
Rotary
Rotary
Rotary
Model
GK113CAA
GK113CAA
GK113CAA
GK113CAA
Compressor
Motor Type
PSC
PSC
PSC
PSC
Oil Type
FVC68D(PVE)
FVC68D(PVE)
FVC68D(PVE)
FVC68D(PVE)
Oil Charge
O.L.P Name
Type
cc
W
330
330
330
330
MRA12053-12027
MRA12053-12027
MRA12053-12027
MRA12053-12027
Turbo Fan
Turbo Fan
Turbo Fan
Turbo Fan
Fan(Indoor)
Motor Output
Type
Motor Type
Motor Output
24
24
24
24
Propeller
Propeller
Propeller
Propeller
Fan(outdoor)
AC Induction
AC Induction
AC Induction
AC Induction
W
A
27
20
27
20
27
20
27
20
Circuit Breaker*
Power Supply Cable
No.*mm2
No.*mm2+No.mm2
mm(in)
mm(in)
mm(in)
mm
3*2.5
3*2.5
3*2.5
3*2.5
Power and Transmission Cable
4*0.75
4*0.75
4*0.75
4*0.75
Piping
Connections
Drain Hose
Liquid Side
Gas Side
O.D , I.D
6.35(1/4)
6.35(1/4)
6.35(1/4)
6.35(1/4)
12.7(1/2)
12.7(1/2)
12.7(1/2)
12.7(1/2)
21.5,16(0.85,0.63)
21.5,16(0.85,0.63)
21.5,16(0.85,0.63)
21.5,16(0.85,0.63)
600*600*146
600*600*146
600*600*146
600*600*146
Indoor(W*H*D)
inch
23.62*23.62*5.75
23.62*23.62*5.75
23.62*23.62*5.75
23.62*23.62*5.75
Dimension
mm
770*540*245
770*540*245
770*540*245
770*540*245
Outdoor(W*H*D)
inch
30.31*21.26*9.65
30.31*21.26*9.65
30.31*21.26*9.65
30.31*21.26*9.65
Indoor
Outdoor
Indoor + Outdoor
Temperature Control
Plasma Filter
Prefilter(washable/anti-fungus)
Auto Clean
CHAOS Wind(Auto Wind)
Steps, Fan/Cool/Heat
Airflow Direction Control(up&down)
Airflow Direction Control(left&right)
Remocon Type
Setting Temperature
Range
kg(lbs)
kg(lbs)
15(33.1)
15(33.1)
15(33.1)
15(33.1)
Net Weight
32(70.5)
32(70.5)
32(70.5)
32(70.5)
Tool Code(Chassis)
SF + UL
SF + UL
SF + UL
SF + UL
Thermistor
Thermistor
Thermistor
Thermistor
Functions
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
3/4
3/4
3/4/3
3/4/3
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Wireless LCD
Wireless LCD
Wireless LCD
Wireless LCD
Cooling
Heating
18 ~ 30
18 ~ 30
18 ~ 30
18 ~ 30
-
-
16 ~ 30
16 ~ 30
Auto Operation (Micom Control)
Auto Changeover (Micom Control)
Self Diagnosis
O
O
O
O
O
O
O
O
O
O
O
O
Timer
24h, On/Off
24h, On/Off
24h, On/Off
24h, On/Off
Sleep Operation
Soft Dry Operation
Restart Delay(minute)
Deice Control(Defrost)
Hot Start
O
O
3
-
O
O
3
-
O
O
3
O
O
3
O
O
O
-
O
O
O
-
-
-
Jet Cool
O
-
O
-
Low Ambient Operation
Special Function
Dry Contact
Network Solution(LGAP)
PI485
-
-
-
-
-
-
-
-
Network Functions
-
-
-
-
-
-
-
-
Note:
O : Applied, - : No relation
* For circuit breaker rating, please conform to local standards wherever necessary.
Some of functions are slightly different depending upon models.
The specification may be subject to change without notic for purpose of improvement.
Service Manual 11
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Installation
Read carefully, and then follow step by step.
Installation Parts
Installation guide map
Type "A" screw and plastic anchor
Remote control holder
Type "B" screw
Installation Tools
Figure
Name
Figure
Name
Screw driver
Ohmmeter
Electric drill
Hexagonal wrench
Measuring tape, Knife
Hole core drill
Ammeter
Leak detector
Thermometer,
Horizontal meter
Spanner
Torque wrench
Flaring tool set
12 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Installation Map
NOTICE
Installation parts you should purchase.
More than
37.9"(120cm)
More than
19.6"(50cm)
(Left and right
Sleeve
are identical)
Bushing-Sleeve
Putty(Gum Type Sealer)
Bend the pipe as close as possible
on the wall but be careful so that it
may not break.
Vinyl tape (Wide)
• To carry out the drainage
test, remove the air filter
and pour water into the heat
exchanger.
Saddle
• Apply after carrying out a
drainage test.
More than
23.6"(60cm)
More than
11.8"(30cm )
More than
11.8"(30cm)
Gas side piping
(Optional part)
(Optional part)
Liquid side piping
Additional drain pipe
More than
28"(70cm)
Vinyl tape (Narrow)
Connecting cable
(Optional part)
Service Manual 13
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Confirm The Refrigerant
1. Check the quality label on the indoor and outdoor unit.
2. Make certain that the refrigerant is R-410A.
NOTICE
THIS PRODUCT CONTAINS R-410A REFRIGERANT
1) Different compressor oil
- R-410A(Polyol ester) / R-22(Mineral).
- Do not mix the existing mineral oil.
- Do not apply used pipe, tools and gauges covered with the existing mineral oil.
2) Absorption of moisture
-Compressor’s oil has the high absorption rate of moisture.
3) Composition
- R-410A(R32:R125=50:50wt%).
NOTE: Never mix with other refrigerants
Example : Split type 12,000 Btu/h
Capacity
[%]
120
100
80
60
40
20
0
100
93
89
84
76
R-410A
R-22
100%
70%
50%
30%
0%
0%
30%
50%
70% 100%
4) High pressure.
- 1.6 times higher than R-22.
- High Pressure refrigerant may cause personal injury.
Boiling Pt.(°C)
Vapor pressure(25°C)(kg f/cnf)
Vapor density(25°C)(kg/m2)
R-410A
R-22
-51.4
-40.8
15.9
9.6
64
44.4
Do not handle the pipe by yourself (customer) High-pressure refrigerant may cause personal injury.
- manifold gauge ,charging and any piping tools must be dedicated to R-410A systems.
14 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Select the best Location
Indoor unit
1. Do not have any heat or steam near the unit.
2. Select a place where there are no obstacles in front
of the unit.
More than
7.9"(20cm)
More than
19.6"(50cm)
3. Make sure that condensation drainage can be conve-
niently routed away.
4. Do not install near a doorway.
5. Ensure that the interval between a wall and the left
(or right) of the unit is more than 19.6"(50cm). The
unit should be installed as high as possible on the
wall, allowing a minimum of 7.9"(20cm) from ceiling.
More than
19.6"(50cm)
More than
4.9ft(1.5m)
6. Use a stud finder to locate studs to prevent unneces-
sary damage to the wall.
CAUTION: Install the indoor unit on the wall where the height from the floor is
more than 4.9 feets(1.5 meters).
Outdoor unit
1. If an awning is built over the unit to prevent direct
sunlight or rain exposure, make sure that heat radia-
tion from the condenser is not restricted.
More than
23.6"(60cm)
2. Ensure that the space around the back and sides is
more than 11.8"(30cm). The front of the unit should
have more than 28"(70cm) of space.
More than
11.8"(30cm)
More than
11.8"(30cm)
3. Do not place animals and plants in the path of the
warm air.
More than
28"(70cm)
More than
23.6"(60cm)
4. Take the weight of the air conditioner into account
and select a place where noise and vibration are min-
imum.
5. Select a place where the warm air and noise from the
air conditioner do not disturb neighbors.
Rooftop Installations
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring
method are adequate for the unit location. Consult local codes regarding rooftop mounting.
If the outdoor unit is installed on roof structures or walls, this may result in excessive noise and vibration, and may
be also classed as non serviceable installation.
Service Manual 15
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Piping Length and Elevation
Standard
Max.
Max.
Additional
Refrigerant
g/m(oz/ft)
Pipe Size
Capacity
Length
Elevation
length
(Btu/h)
Suction
Evap
m(ft)
B
m(ft)
A
m(ft)
9k, 12k
Ø12.7mm(1/2") Ø6.35mm(1/4")
7.5(25)
7.5(25)
15(49)
20(0.22)
Indoor unit
Outdoor unit
Outdoor unit
A
A
A
Oil trap
B
Indoor unit
Outdoor unit
Indoor unit
B
B
If piping length is more than 16.4ft(5m)
CAUTION: Capacity is based on standard length and maximum allowance length is
on the basis of reliability.
Oil trap should be installed every 16.4~23feets (5~7 meters).
16 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Preparing Work for Installation
Open panel front
1. Pull the upper part of the front panel.
2. Lift up the panel.
3. To detach the front panel, remove the two screws at the lower part.
4. Detach the front panel from the body.
5. To detach the panel, disconnect the connector at the upper part.
Panel Front
Connector
Cover pipe and cover side remove
1. Please remove the screw of the center tuning cover.
2. Pull up the side cover of desired connecting direction, then
cover side is separated.
3. Pick the pipe hole of the side cover.
CAUTION: After removing the pipe hole, cut
the burr for safety.
Pipe hole
Side cover
NOTICE
When making pipe path through rear
wall, you don’t need to pick the pipe hole.
Drain hose junction
1. Remove the rubber stopple in the desired drain direc-
tion.
2. Insert drain hose into the handle of drain pan, and
join drain hose and connecting hose according to the
figure by.
Adhesive
Onlythe
desired direction
Connecting
part
Drain
hose
rubber cap
Service Manual 17
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Fixing Indoor Unit
1. Attach an Installation guide map on the
desired surface.
2. Look at suited horizon by horizontal
meter on the horizontal setting line, and
fix lightly the map by adhesive tape.
INSTALLATION GUIDE MAP
I
N
S
T
A
L
L
A
T
Horizontality
IO
N
G
U
ID
E
M
A
P
3. Make a hole with a diameter of 6mm and
depth of 30-35mm by piercing a screw
4. Drill the pierted part as a diameter of 50mm
for connecting piping. (In case of piercing
rear surface)
point.
INS
T
A
IIA
TION
G
UID
E M
AP
6. First, Drive the two points of the upper
parts by screws. (Leave 10mm for hanging
the product)
5. Drive the fore plastic anchors into drilled
points.
INST
ALLA
TION GUIDE MAP
INST
ALLA
TION GU
Plastic anchors
8. Drive the lower parts after facing the hole
of product with plastic anchors, and fix
completely the upper screws.
7. Hang the hole of product at the upper
screws, and remove the map. (Falling
INST
attention)
ALLA
TION GUIDE MAP
Plastic anchors
Hanger hole
(Rear side of
the product)
9. Check the fixed product with light power.
10. In case of nothing wrong, connect the
pipe and the wire. (Refer to installation
manual)
Drill a Hole in the Wall
WALL
• Drill the piping hole with a ø50mm hole core drill.
Drill the piping hole at either the right or the left with
the hole slightly slanted to the outdoor side.
Indoor
Outdoor
18 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Flaring work and connection of piping
Flaring work and connection of piping
Flaring Work
Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure.
Cutting the pipes and the cable.
1. Use the piping kit accessory or the pipes purchased
locally.
2. Measure the distance between the indoor and the
outdoor unit.
Copper
pipe
Slanted Uneven Rough
90°
3. Cut the pipes a little longer than measured distance.
4. Cut the cable 4.9ft(1.5m) longer than the pipe length.
Removing burrs
1. Completely remove all burrs from the cut cross section
of pipe/tube.
Pipe
Reamer
2. Put the end of the copper tube/pipe in a downward
direction as you remove burrs in order to avoid dropping
burrs into the tubing.
Point down
Putting nut on
• Remove flare nuts attached to indoor and outdoor unit,
then put them on pipe/tube having completed burr
removal.
Flare nut
(not possible to put them on after flaring work)
Copper tube
Flaring work
1. Firmly hold copper pipe in a die in the dimension shown
in the table below.
2. Carry out flaring work with the flaring tool.
Handle
Yoke
Bar
Bar
Cone
Outside diameter
A
mm
Ø6.35
Ø9.52
Ø12.7
Ø15.88
Ø19.05
inch
1/4
3/8
1/2
5/8
3/4
mm
Copper pipe
Clamp handle
1.1~1.3
1.5~1.7
1.6~1.8
1.6~1.8
1.9~2.1
Red arrow mark
Service Manual 19
Download from Www.Somanuals.com. All Manuals Search And Download.
Flaring work and connection of piping
Check
Smooth all round
1. Compare the flared work with the figure by.
Inside is shiny without scratches
2. If a flared section is defective, cut it off and do flaring
work again.
= Improper flaring =
Inclined Surface Cracked Uneven
damaged
thickness
Even length
all round
Connecting the Piping
Indoor
Preparing the indoor unit's piping and drain hose for installation through the wall.
1. Route the indoor tubing and the drain hose in the
direction of rear left or right
Drain hose
2. Tape the tubing, drain hose and the connecting cable.
Be sure that the drain hose is located at the lowest
side of the bundle. Locating at the upper side can
cause drain pan to overflow inside the unit.
Loop
Gas side piping
Connecting
cable
Liquid side piping
Drain hose
CAUTION: If the drain hose is routed inside the room, insulate the hose with an
insulation material* so that dripping from "sweating"(condensation) will not dam-
age furniture or floors.
*Foamed polyethylene or equivalent is recommended.
20 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Flaring work and connection of piping
Connecting the piping with the indoor unit
and drain hose with drain pipe
1. Align the center of the pipings and sufficiently tighten
the flare nut by hand.
Indoor unit tubing
Flare nut Pipings
2. Tighten the flare nut with a wrench.
Spanner (fixed)
Flare nut
Outside diameter
Torque
.
mm
inch
1/4
3/8
1/2
kgf cm
Ø6.35
Ø9.52
Ø12.7
180~250
340~420
550~660
Torque wrench
Connection pipe
Indoor unit tubing
3. When extending the drain hose at the indoor unit,
install the drain pipe.
Drain pipe
Indoor unit drain hose
Vinyl tape(narrow)
Adhesive
Plastic bands
Wrap the insulation material around the
connecting portion.
Insulation material
1. Overlap the connection pipe insulation material and
the indoor unit pipe insulation material. Bind them
together with vinyl tape so that there may be no gap.
2. Wrap the area which accommodates the rear piping
housing section with vinyl tape.
Indoor
unit pipe
Connection
pipe
Vinyl tape
(wide)
Wrap with vinyl tape
Connecting cable
Pipe
3. Bundle the piping and drain hose together by wrap-
ping them with vinyl tape over the range within which
they fit into the rear piping housing section.
Vinyl tape(narrow)
Wrap with vinyl tape
Pipe
Vinyl tape(wide)
Drain hose
Service Manual 21
Download from Www.Somanuals.com. All Manuals Search And Download.
Flaring work and connection of piping
CAUTION: Installation Information
For right piping. Follow the instruction below.
Good case
• Press on the upper side of clamp and unfold the tubing to downward slowly.
Bad case
• Following bending type from left to right may cause damage to the turbing.
22 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Flaring work and connection of piping
Connection of Piping -Outdoor
Put a couple drops of refrigerant oil on the face of
the flare before assembling taking care not to add
any contaminants.
Align the center of the pipings and sufficiently
tighten the flare nut by hand.
Finally, tighten the flare nut with torque wrench until the
wrench clicks.
Outdoor unit
Liquid side piping
(Smaller diameter)
• When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the arrow on
the wrench.
Gas side
piping
(Bigger
diameter)
Outside diameter
Torque
mm
Ø6.35
Ø9.52
Ø12.7
Ø15.88
Ø19.05
inch
1/4
3/8
1/2
5/8
3/4
kgf.cm
180~250
340~420
550~660
630~820
980~1210
Torque wrench
Service Manual 23
Download from Www.Somanuals.com. All Manuals Search And Download.
Connecting the cable between indoor unit and outdoor unit
Connecting the cable between indoor unit and outdoor unit
Connecting the Cables
1. Remove the cover control from the unit by loosening
Wiring Diagram
the screw.
Connecting cable(Low voltage)
b
Indoor Unit
Outdoor Unit
2. Dismount caps on the conduit panel.
3. Temporarily mount the conduit tubes on the conduit
panel.
4. Properly connect both the power supply and low volt-
age lines to the corresponding terminals on the termi-
nal block.
Terminal
(4P)
Terminal
(6P)
1
2
3
4
1
2
3
4
Power supply
a
5
L1*
6
L2
To
branch
circuit
5. Ground the unit in accordance with local codes.
6. Be sure to size each wire allowing several inches
longer than the required length for wiring.
7. Use lock nuts to secure the conduit tubes.
G
Ground
L1 is neutral for 115V models.
*
NOTICE
NOTICE
Connector trade size for this unit is 1/2"(12.7mm).
Refer to "How to connect wiring to the terminals" for
instructions on connecting depending on the wire type
you are using.
1.
shows field wiring.
2. Separately wire the high and low voltage line.
3. Use heat-proof electrical wiring capable of with-
standing temperatures up to 167°F(75°C).
4. Use outdoor and waterproof connection cable
rated more than 300V for the connection between
indoor and outdoor unit.
WARNING:
• Be sure to comply with local codes while
running the wire from the indoor unit to
the outdoor unit(size of wire and wiring
method, etc).
(For example, Type SJO-WA)
• Every wire must be connected firmly.
• No wire should be allowed to touch
refrigerant tubing, the compressor or any
moving parts.
Outdoor unit
Terminal block
Over 5mm
(0.2")
Conduit panel
Connecting
cable
Power Supply
AWG(MIN)
14 18
Power
source
Fuse or breaker
Capacity
Power supply
cord
Model
9k/12k
Cover control
1Ø, 115V
20A
24 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Connecting the cable between indoor unit and outdoor unit
Connection method of the connecting cable(Example)
1. Dismount two-caps on the conduit panel.
2. Make a hole appropriate for the passage of connec-
tion cable through on cap by tool. (for low voltage
line)
3. Pass the connecting cable through the hole.
4. Properly connect the cable on the terminal block.
5. Fix the connection cable with clamp cord provided on
the unit not to have strain at the terminal when the
connection cable is pulled outside up to a 35 pound
weight.
6. Wind the vinyl tape round the connecting cable for
sealing between the surface of the connection cable
and cap.
7. Mount the taped part of cable on the cap.
8. Finally, mount the holed cap with the
wound cable on the conduit panel.
Terminal
block
Clamp cord
Cap(Reuse)
G
Lock nut
Hole (for low
voltage line)
Cap
(Remove)
Taping
(for sealing)
Power supply line
(1ø, 115V, 208/230V)
Low voltage line
(connecting cable)
Conduit panel
WARNING:
Loose wiring may cause the terminal to over-
heat or result in unit malfunction. A fire hazard
may also exist. Therefore, be sure all wiring is
tightly connected.
When connecting each power wire to the corresponding
terminal, follow instructions "How to connect wiring to
the terminals" and fasten the wire tightly with the fixing
screw of the terminal plate.
Solid wire
Loop
How to connect wiring to the terminals
• For solid core wiring (or F-cable)
1. Cut the wire end with a wire cutter of wire-cutting pli-
ers, then strip the insulation to expose the solid wire
about 25mm(15/16")
2. Using a screwdriver, remove the terminal screw(s) on
the terminal plate.
Insulation
Strand wire
3. Using pliers, bend the solid wire to from a loop suit-
able for the terminal screw.
Round
terminal
4. Shape the loop wire properly, place it on the terminal
plater and tighten securely with the terminal screw
using a screwdriver.
• For strand wiring
1. Cut the wire end with a wire cutter or wire-cutting pli-
ers, then strip the insulation to expose the strand
wiring about 10mm(3/8").
2. Using a screwdriver, remove the terminal screw(s) on
the terminal plate.
Screw with
special washer
Round terminal
Terminal plate
Screw with
special washer
Round terminal
Wire
3. Using a round terminal fastener or pliers, securely
clamp each stripped wire end with a round terminal.
4. Position the round terminal wire, and replace and
tighten the terminal screw using a screwdriver.
Wire
Service Manual 25
Download from Www.Somanuals.com. All Manuals Search And Download.
Connecting the cable between indoor unit and outdoor unit
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the method of
wiring, be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and make
sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) Confirm that the starting voltage is maintained at more than 90 percent of the rated voltage marked
on the name plate.
6) Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness.
7) Always install an GFCI circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
• Vibration of a magnetic switch, which will damage the contact point, open fuse, disturbance of the normal function of
the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and
have an air gap contact separation of at least 3mm(0.12in) in each active(phase) conductors.
26 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Checking the drainage and forming the pipings
Checking the drainage and forming the pipings
Checking the Drainage
To check the drainage.
1. Pour a glass of water on the evaporator.
2. Ensure the water flows through the drain hose of the
indoor unit without any leakage and goes out the
drain exit.
(mm2)
Drain piping
Downward slope
1. The drain hose should point downward for easy drain
flow.
2. Do not make drain piping like the following.
Accumulated
drain water
Do not raise
Less than
50mm gap
Tip of drain hose
dipped in water
Air
Water
leakage
Water
leakage
Water
leakage
Waving
Ditch
Service Manual 27
Download from Www.Somanuals.com. All Manuals Search And Download.
Checking the drainage and forming the pipings
Forming the Piping
Form the piping by wrapping the connect-
ing portion of the indoor unit with insula-
tion material and secure it with two kinds
of vinyl tapes.
Seal small openings
around pipings with a
gum type sealer.
Taping
Drain hose
• If you want to connect an additional drain hose, the
end of the drain outlet should be routed above the
ground. Secure the drain hose appropriately.
In cases where the outdoor unit is
installed below the indoor unit perform the
following.
Pipings
Connecting cable
1. Tape the piping, drain hose and connecting cable
from down to up.
2. Secure the tapped piping along the exterior wall
using saddle or equivalent.
Trap is required to prevent water
from entering electrical parts.
In cases where the outdoor unit is
installed above the Indoor unit perform the
following.
Seal a small opening
around the pipings
with gum type sealer.
1. Tape the piping and connecting cable from down to
up.
Trap
2. Secure the taped piping along the exterior wall. Form
a trap to prevent water entering the room.
3. Fix the piping onto the wall by saddle or equivalent.
Trap
28 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Air purgingd
AIR PURGING
Air Purging
Air purging
The air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
1. Pressure in the system rises.
2. Operating current rises.
3. Cooling(or heating) efficiency drops.
4. Moisture in the refrigerant circuit may freeze and block capillary tubing.
5. Water may lead to corrosion of parts in the refrigeration system.
Therefore, after evacuating the system, take a leak test for the piping and tubing between the indoor and outdoor
unit.
Air purging with vacuum pump
1. Preparation
• Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected
and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on
the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
2. Leak test
• Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.
CAUTION: Be sure to use a manifold valve for air purging. If it is not available, use a stop
valve for this purpose. The "Hi" knob of the manifold valve must always be kept close.
• Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylinder valve when the
gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap.
CAUTION: To avoid nitrogen entering the refrigerant system in a liquid state, the top of the
cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is
used in a vertical standing position.
1. Do a leak test of all joints of the tubing(both indoor
and outdoor) and both gas and liquid side service
Manifold valve
Pressure
valves.
Bubbles indicate a leak. Be sure to wipe off the
soap with a clean cloth.
gauge
Lo
Hi
Indoor unit
2. After the system is found to be free of leaks,
relieve the nitrogen pressure by loosening the
charge hose connector at the nitrogen cylinder.
When the system pressure is reduced to normal,
disconnect the hose from the cylinder.
Outdoor unit
Charge hose
Nitrogen gas
cylinder(in vertical
standing position)
Service Manual 29
Download from Www.Somanuals.com. All Manuals Search And Download.
Air purgingd
Soap water method
Liquid side
1. Remove the caps from the 2-way and 3-way valves.
2. Remove the service-port cap from the 3-way valve.
3. To open the 2-way valve turn the valve stem counterclock-
wise approximately 90°, wait for about 2~3 sec, and close it.
4. Apply a soap water or a liquid neutral detergent on the
indoor unit connection or outdoor unit connections by a soft
brush to check for leakage of the connecting points of the
piping.
Gas side
2-way valve
(Open)
3-way valve
(Close)
5. If bubbles come out, the pipes have leakage
Evacuation
1. Connect the charge hose end described in the preceding
steps to the vacuum pump to evacuate the tubing and
indoor unit.
Cap
Hexagonal wrench
Confirm the "Lo" knob of the manifold valve is open.
Then, run the vacuum pump.
The operation time for evacuation varies with tubing
length and capacity of the pump. The following table
shows the time required for evacuation.
Indoor unit
Required time for evacuation when 30 gal/h vacuum
pump is used
If tubing length is longer
than 10m (33 ft)
If tubing length is less
than 10m (33 ft)
10 min. or more
15 min. or more
Outdoor unit
2. When the desired vacuum is reached, close the "Lo"
knob of the manifold valve and stop the vacuum pump.
Finishing the job
1. With a service valve wrench, turn the valve stem of liquid
side valve counter-clockwise to fully open the valve.
2. Turn the valve stem of gas side valve counter-clockwise
to fully open the valve.
3. Loosen the charge hose connected to the gas side ser-
vice port slightly to release the pressure, then remove
the hose.
4. Replace the flare nut and its bonnet on the gas side ser-
vice port and fasten the flare nut securely with an
adjustable wrench. This process is very important to pre-
vent leakage from the system.
Manifold valve
Pressure
gauge
Lo
Hi
Open
Close
5. Replace the valve caps at both gas and liquid side ser-
vice valves and fasten them tight.
This completes air purging with a vacuum pump.
The air conditioner is now ready to test run.
Vacuum pump
30 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Air purgingd
Charging
â– Each outdoor unit is factory charged (nameplate charge) for the evaporator as well as a 7.5m(25ft) line set.
Any time a line set is used either shorter or longer then the nominal 7.5m(25ft) line set length the refrigerant
charge has to be adjusted.
â– Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are
either added or removed based on 20g(0.22oz) of R-410A per meter(foot).
Standard
Length
m(ft)
Max.
Max.
Additional
Refrigerant
g/m(oz/ft)
Pipe Size
Capacity
(Btu/h)
Elevation
length
Suction
Evap
B
m(ft)
A
m(ft)
9k, 12k
Ø12.7mm(1/2") Ø6.35mm(1/4")
7.5(25)
7.5(25)
15(49)
20(0.22)
Example: A 30ft line set is used
5 additional ft X 0.22 ounce per foot= add 1.1 ounces of R-410A
Important:
If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the unit
nameplate charge adjusting for line sets longer or shorter than 7.5m(25ft).
Confirm the refrigerant R-410A. Use manifold gauge and hose for R-410A.
Service Manual 31
Download from Www.Somanuals.com. All Manuals Search And Download.
Air purgingd
Panel Front Assembly
1. First, Check the side cover assembly
exactly, and fix the power cord in the
bottom groove of cover side left.
2. Assemble connecting lead wire with
controller, fix the upper part of panel
front, and match the lower part of panel
front.
Panel Front
Connector
3. Screw up panel front, and suspend the
hook of panel front in the groove.
32 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Test running
TEST RUNNING
Test Running
1. Check that all tubing and wiring are properly connected.
2. Check that the gas and liquid side service valves are fully open.
Prepare remote controller
1. Remove the battery cover by pulling it according to
the arrow direction.
2. Insert new batteries making sure that the (+) and (–)
of battery are installed correctly.
3. Reattach the cover by pushing it back into position.
NOTICE
• Use 2 AAA(1.5volt) batteries. Do not use rechargeable
batteries.
• Remove the batteries from the remote controller if the
system is not used for a long time.
Settlement of outdoor unit
Bolt
1. Anchor the outdoor unit with a bolt and
nut(ø0.39"(ø10mm)) tightly and horizontally on a con-
crete or rigid mount.
2. When installing on the wall, roof or rooftop, anchor
the mounting base securely with a nail or wire
assuming the influence of wind and earthquake.
3. If the vibration of the unit is transmitted to the hose,
secure the unit with an anti-vibration rubber.
Tubing connection
Evaluation of the performance
Operate the unit for 15~20 minutes, then check the sys-
tem refrigerant charge:
Intake temperature
Discharge air
1. Measure the pressure of the gas side service valve.
2. Measure the temperature of the intake and discharge
of air.
3. Ensure the difference between the intake tempera-
ture and the discharge is more than 46.4°F(8°C)
4. For reference; the gas side pressure of optimum con-
dition is as below.(Cooling)
Discharge
temperature
The air conditioner is now ready for use.
Outside ambient
TEMP.
The pressure of the gas side
service valve.
Refrigerant
R-410A
95°F(35°C) 8.5~9.5kg/cm2G(120~135 P.S.I.G.)
Service Manual 33
Download from Www.Somanuals.com. All Manuals Search And Download.
Test running
NOTICE
If the actual pressure is higher than shown, the system is most likely over-charged, and charge should be
removed. If the actual pressure are lower than shown, the system is most likely undercharged, and
charge should be added.
PUMP DOWN
This is performed when the unit is relocated or the refrigerant circuit is serviced.
Pump Down means collecting all refrigerant into the outdoor unit without the loss of refrigerant.
CAUTION: Be sure to perform Pump Down procedure in the cooling mode.
Pump Down Procedure
1. Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve.
2. Open the gas side service valve halfway and purge the air in the manifold hose using the refrigerant.
3. Close the liquid side service valve(all the way).
4. Turn on the unit's operating switch and start the cooling operation.
5. When the low-pressure gauge reading becomes 1 to 0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the gas side
valve and then quickly turn off the unit. Now Pump Down procedure is completed, and all refrigerant is collected
into the outdoor unit.
34 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
How to replace picture & photograph
How to replace picture & photograph
1. Turn off power and then open
2. Pull out the both links of lower 3. Push and close the top part of
the upper part of front panel.
part of front panel, as
the front panel and then pull
the bottom part of the panel
forward until it is secured.
described in the below picture.
4. Take out picture.
5. Turn upside-down of the
picture and turn over mat, then
take off a protective tape
attached at the mat.
6. Place the picture/photograph
between the exited picture and
mat. (Recommended size of a
photo/picture: 450mm x
450mm)
Protective tape
Mat
450mm
Mat
450mm
7. Cover mat and press down
with hand(s) until contacting
closely.
8. Slide the photo graph/drawing 9. Push both links of lower part of
panel inside and fix it. Then
turn on.
requested under both hanger
parts as following, and fix them.
Press the front panel lightly to
close.
In case a mat is not used, recommended size of a photo/picture:
522mm x 522mm
When powering on after replacing filter and picture,
the front panel doesn't intervene.
522mm
522mm
Service Manual 35
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Operation
Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
• Room temperature sensor (THERMISTOR)
Room temperature control
• Maintains the room temperature in accordance with the Setting Temp.
Starting Current Control
• Indoor fan is delayed for 5 seconds at the starting.
Time Delay Safety Control
• Restarting is inhibited for approx. 3 minutes.
Indoor Fan Speed Control
• High, Med, Low and Auto
Operation indication Lamps (LED)
--- Lights up in operation
Healthy Dehumidification Mode
• Intermittent operation of fan at low speed
Sleep Mode Auto Control
• The fan is switched to low(Cooling), med(Heating) speed.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Defrost control(Heating)
• Both the indoor and outdoor fan stops
during defrosting.
• Hot start will be operated after
defrosting ends.
Auto Air Control by the unit electronic control
• The fan is switched to intermittent or irregular operation.
• The fan speed is automatically switched from high to low speed.
Hot-start Control (Heating)
Chaos Swing
• The indoor fan stops until the
indoor pipe temperature will be
reached at 82°F(28°C).
• The louver can be set at the desired position or swing up
and down automatically.
36 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
The function of main control
1. Time delay Safety Control
• 3min.; The compressor operation is delayed for 3 minutes to balance the pressure of cycle.
(Protection of compressor)
• 5sec.; The indoor fan is delayed for 5 seconds, when operating initially, to prevent noises occurred by the vertical
louver and wind.
• 2min.; The reversing valve is delayed for 2 minutes to prevent the refrigerant-gas for abnormal noise when the
heating operation is OFF or switched to the other operation mode while compressor is off.
While compressor is running, it takes 3~5 seconds to switch.
2. Chaos Swing Mode
• By the Chaos Swing key input, the vane automatically operates with the Chaos Swing or they are fixed to the
desired direction.
• While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.
< Cooling Mode >
< Heating Mode >
CLOSED
CLOSED
8°
8°
OPEN
OPEN
3. Cooling Operation Mode
• When selecting the Cooling(
) Mode Operation, the unit will operate according to the setting by the
remote control and the operation diagram is shown below.
INTAKE AIR TEMP.
SETTING TEMP. +1
°F
(Compressor ON)
SETTING TEMP. -1
°F
(Compressor OFF)
More than
3 minutes
More than
3 minutes
Setting
Setting
Setting
INDOOR FAN SPEED
COMPRESSOR
Low
OFF
Low
OFF
fan speed
fan speed
fan speed
ON
ON
ON
â– Protection of the indoor heat exchanger from frosting
• Compressor and outdoor fan stop when indoor pipe temperature is below 32°F(0°C) and restart at the pipe
temperature is above 45°F(7°C).
Service Manual 37
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
. Auto Operation (Electronic control mode)
• The operation procedure is shown below. (Cooling & Heating Model)
Press Start/Stop Button
Select Auto Operation Mode
Check the Room temperature
Operation mode
Indoor fan speed
are decided automatically by the unit electronic control.
Setting temperature
Intake-air
temperature
Over
70
below
76
~
Over 76°F
below 70
°F
°
F
°F
Operation Mode
Soft Dry
Cooling
Heating
â– â– If initial mode is decided, that mode is continued without the room temperature changing.
â– Auto Operation for Cooling
Operation Condition
Intake-air Temperature
Over 78°F
Setting Temperature
77°F
Fan Speed
Air Direction Control
Over 76°F~below 78°F
Over 72°F~below 76°F
Intake air -1°C
Intake air -0.5°C
In this mode,
when pressing
the vertical air
direction control
button, vertical
louver swings up
and down
When Auto Operation
initial start
Controlled by
the electronic
control
Over 68°F~below 72°F Intake air temperature
below 64°F
Over 64°F~below 86°F
below 64°F
64°F
Electronic control
64°F
When pressing room
temperature setting
button during Auto
Operation
automatically.
over 86°F
86°F
INTAKE AIR TEMP.
SETTING TEMP. +1°F
(Compressor OFF)
SETTING TEMP. -1°F
(Compressor ON)
INDOOR FAN SPEED
COMPRESSOR
The electronic control operation
OFF ON
ON
OFF
38 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
â– â– Auto Operation for Dehumidification(only Heating Model)
• The Setting temperature will be same that of the auto operation for cooling.
- Compressor ON temperature; Setting temperature +2°F
- Compressor OFF temperature; Setting temperture -1°F
Intake-air temp.
Setting temp.
below 68°F
Over 68°F~below 70°F
over 86°F
86°F
68°F
Intake air temperature +1°F
â– â– Auto Operation for Heating(only Heating Model)
- Compressor ON temperature; Setting temperature
+
- Compressor OFF temperature; Setting temperature 6°F
â– â– Vertical louver auto operation : During Auto Operation, pressing the chaos swing button makes the horizon-
tal louvers swing up and down automatically.
If you want to stop auto-swing, press chaos swing button again.
5. Healthy Dehumidification
• When the dehumidification operation input by the remote control is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
79°F ≤ Intake Air Temp
■■77°F
75°F ≤ Intake Intake Air Temp<79°F
64°F ≤ Intake Intake Air Temp<75°F
Intake Air Temp<64°F
■■Intake Air Temp-2°F
■■Intake Air Temp-1°F
■■64°F
• While in compressor off, the indoor fan repeats low airflow speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat.
Compressor ON Temp.
■Setting Temp+1°F
Compressor OFF Temp. ■Setting Temp-1°F
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
Service Manual 39
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
6. Heating Operation Mode(only Heating Model)
The unit will operate according to the setting conditions by the remote controller.
The operation diagram is shown below.
INTAKE AIR TEMP.
+
SETTING TEMP. 6
°F
(Compressor OFF)
A
B
A
SETTING TEMP.
(Compressor ON)
minimum
10sec.
minimum
1 min.
minimum
10sec.
Selecting
fan speed
Selecting
fan speed
INDOOR FAN SPEED
COMPRESSOR
Low
OFF
Low
Low
OFF
ON
OFF
ON
OFF
• A point; While the indoor pipe temperature is higher than 95°F, indoor fan operates at low speed. When the
indoor pipe temperature becomes lower than 95°F, indoor fan stops.
• B point; When the indoor pipe temperature is higher than 100°F(38°C), fan operates at selected fan speed.
â– â– Hot-Start Control
• The indoor fan stops until the indoor pipe temperature will be reached at 82°F.
• During heating operation, if indoor pipe temperature falls below 78°F fan stops.
• The operation diagram is shown below.
INDOOR PIPE
TEMP.
1min
LOW
82°F
78°F
Selecting
fan speed
INDOOR FAN SPEED
COMPRESSOR
OFF
OFF
ON
40 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
7. Cooling or Heating Mode with Sleep Mode Auto Control
• When selecting the Cooling( ) or the Heating(
) combined with the Sleep Mode Auto Control( ), the
operation diagram is as following.
â– â– Cooling Mode with the Sleep Mode
• The setting temperature will be automatically raised by 2°F 30 minutes later and by 4°F 1 hour later.
• The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
30 minutes
30 minutes
INTAKE AIR TEMP.
2°F
2°F
SETTING TEMP. +1
(Compressor ON)
°F
SETTING TEMP. -1
(Compressor OFF)
°F
More than
3 minutes
More than
3 minutes
INDOOR FAN SPEED
COMPRESSOR
Low
ON
Low
OFF
Low
ON
Low
OFF
Low
ON
â– â– Heating Mode with the Sleep Mode(only Heating Model)
• The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
INTAKE AIR TEMP.
SETTING TEMP. +6
°F
(Compressor OFF)
SETTING TEMP.
(Compressor ON)
More than
3 minutes
More than
3 minutes
More than
3 minutes
INDOOR FAN SPEED
COMPRESSOR
Med
ON
Low or OFF
OFF
Med
ON
Low or OFF
OFF
Med
ON
Low or OFF
OFF
Service Manual 41
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
8. Forced Operation
Operation procedures when the remote control can't be used.
The operation will be started if the power button is pressed.
If you want to stop operation, re-press the button.
ON/OFF
button
Cooling
Heat pump Model
Model
Cooling
High
Room Temp. ≥ 76°F(24°C) 70°F(21°C) ≤ Room Temp. < 76°F(24°C) Room Temp. < 70°F(21°C)
Operating mode
Indoor FAN Speed
Cooling
High
Healthy Dehumidification
Healthy Dehumidification Rule
74°F(23°C)
Heating
High
Setting Temperature 72°F(22°C)
72°F(22°C)
76°F(24°C)
Test operation
During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room tempera-
ture and resets in 18 minutes.
During test operation, if remote controller signal is received, the unit operates as remote controller sets.
If you want to use this operation, Press and hold the ON/OFF button for 3~5 seconds, then the buzzer sound 1
"beep".
If you want to stop the operation, re-press the button.
9. Auto restart
In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.
So there is no need of activating this function by pressing any key or button.
In the initial mode, the fan operates at a low speed and the compressor starts 2.5~3 minutes later.
As the compressor starts, the fan speed also resumes its previous setting mode.
Helpful information
Fan speed and cooling capacity.
The cooling capacity indicated in the specification is the value when the fan
speed is set to high, and the capacity will be lower at low or medium fan
speed.
High fan speed is recommended when you wish to cool the room quickly.
NOTICE
Auto restart function has set enable as factory default.
But customer can set up by following this instruction.
To be disable function
- Press and hold the ON/OFF button for 6 seconds, then the buzzer sound 2 "beep" and the indicator lamp (1) blinks 4 times.
To be enable function
- Press and hold the ON/OFF button for 6 seconds, then the buzzer sound 2 "beep" and the indicator lamp (1) brights 4
times.
42 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Display Function
Signal Receptor
Receives the signals from the remote control.(Signal receiving sound: two short beeps or one long beep.)
Operation Indication Lamps
On/Off
: Lights up during the system operation.
Self-diagnosis Function
Error
Code
Error LED
(Indoor body operation LED)
Error contents
SVC check point
• Indoor room temperature
thermistor open/short
• Indoor pipe temperature
thermistor open/short.
(once)
1
2
5
• Indoor TH assy check
3sec
3sec
3sec
(twice)
3sec
• Outdoor pipe temperature
thermistor open/short.
• Outdoor TH assy check
3sec
(5times)
3sec
• Communication line/circuit
check
• Poor communication.
Service Manual 43
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Remote Control Operations
The controls will look like the following.
1. START/STOP BUTTON
Operation starts when this button is pressed and stops when
the button is pressed again.
Controls
2. OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
Signal transmitter
3. ROOM TEMPERATURE SETTING BUTTONS
Used to select the room temperature.
4. INDOOR FAN SPEED SELECTOR
Used to select fan speed in four steps low, medium,
high and CHAOS.
5. JET COOL/HEATING(OPTIONAL)
Used to start or stop the speed cooling/heaing.
(speed cooling/heating operates super high fan speed in
cooling/heatig mode.)
5
6
1
3
6. CHAOS SWING BUTTON
Used to stop or start louver movement and set the
desired up/down airflow direction.
4
7. ON/OFF TIMER BUTTONS
Used to set the time of starting and stopping operation.
10
2
7
CANCEL
9
12
17
8. TIME SETTING BUTTONS
Used to adjust the time.
SET
ON
OFF
AUTO CLEAN
11
8
9. TIMER SET/CANCEL BUTTON
Used to set the timer when the desired time is obtained and to cancel
the Timer operation.
°C/°F
18
14
16
13
15
10. SLEEP MODE AUTO BUTTON
Used to set Sleep Mode Auto operation.
11. AIR CIRCULATION BUTTON
Used to circulate the room air without cooling or heating.
Flip-up door
(opened)
12. ROOM TEMPERATURE CHECKING BUTTON
Used to check the room temperature.
Operation Mode
13. NEO PLASMA(OPTIONAL)
Used to start or stop the plasma-purification function.
Cooling Operation
14. HORIZONTAL AIRFLOW DIRECTION CONTROL BUTTON
(OPTIONAL)
Auto Operation or Auto Changeover
Healthy Dehumidification Operation
Used to set the desired vertical airflow direction.
15. RESET BUTTON
Used prior to resetting time.
16. 2nd F Button
Heating Operation
Used prior to using modes printed in blue at the bottom of buttons.
17. AUTO CLEAN (OPTIONAL)
•
Cooling Model( ), Heat Pump Model(
)
Used to set Auto Clean mode.
18. °C/°F SWITCH BUTTON
Used to switch temperature reading from Centigrade to Fahrenheit.
44 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Disassembly
Disassembly
Indoor Unit
WARNING: Disconnect the unit from
power supply before making any
checks. Be sure the power switch is set
to "OFF"
1. To remove the Grille from the Chassis.
- Pull the grille bottom, the remove 2 securing screws.
- Lift the both lower parts of panel front.
- After pull down this panel a bit, separate connecting
wire with product.
Panel Front
Connector
2. To remove the Control Box.
- Before removing the control box, be sure to
disconnect the wires from PWB.
- Pull the cover control out from the control box
and disconnect other wires.
Communication Connector
Step Motro Connector
Front Panel Connector
- Remove securing screws.
Motor Connector
- Pull the control box out from the chassis carefully.
Sensor Connector
Service Manual 45
Download from Www.Somanuals.com. All Manuals Search And Download.
Disassembly
3. To remove the Evaporator.
- Remove hole tubing holde.
- Remove 2 screws securing the evaporator.
- Pull the evaporator out from the chassis carefully.
Air Guide
4. Before removing the Turbo Fan.
- Remove the securing screws from the chassis.
- Pull the pipe, top cover and the air guide.
Top Cover
Bracket
5. To remove the Motor.
- Remove the securing bolt from the motor shaft.
- Pull the fan out from the motor shaft.
Turbo Fan
- Remove 4 screws securing motor mount from the
chassis and lift up the motor mount and the bracket.
Motor Mount
Bolt
46 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram
Schematic Diagram
Heat Pump/Cooling Only Series(Indoor Unit)
Service Manual 47
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram
Heat Pump Series/ Cooling Only Series (Outdoor Unit)
48 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram
INDOOR UNIT P.W.B. ASSEMBLY
• P/No.: 6871A20999A (PCB ASSEMBLY, MAIN)
Top View
Bottom View
Service Manual 49
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram
OUTDOOR UNIT P.W.B. ASSEMBLY
• P/No.: 6871A20901C (PCB ASSEMBLY, MAIN)
Top View
Bottom View
50 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram
DISPLAY P.W.B. ASM
• P/No.: 6871A20921A (PCB ASSEMBLY)
Service Manual 51
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram
Wiring Diagram
(1) Indoor Unit (Cooling Only Models, & Heating Models)
52 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram
(2) Outdoor Unit(Cooling Only Models, & Heating Models)
Service Manual 53
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
Troubleshooting Guide
Refrigeration Cycle Diagram
(1) Cooling Only Models
INDOOR UNIT
OUTDOOR UNIT
LIQUID SIDE
CAPILLARY TUBE
HEAT
HEAT
EXCHANGE
(EVAPORATOR)
EXCHANGE
(CONDENSER)
GAS SIDE
COMPRESSOR
(2) Cooling & Heating Models
INDOOR UNIT
OUTDOOR UNIT
CHECK VALVE
LIQUID SIDE
CAPILLARY TUBE
HEAT
HEAT
EXCHANGE
(EVAPORATOR)
EXCHANGE
(CONDENSER)
GAS SIDE
REVERSING
VALVE
COOLING
HEATING
COMPRESSOR
54 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
Piping Length and Elevation
Standard
Max.
Max.
Additional
Refrigerant
g/m(oz/ft)
Pipe Size
Capacity
Length
Elevation
length
(Btu/h)
Suction
Evap
m(ft)
B
m(ft)
A
m(ft)
9k, 12k
Ø12.7mm(1/2") Ø6.35mm(1/4")
7.5(25)
7.5(25)
15(49)
20(0.22)
Indoor unit
Outdoor unit
Outdoor unit
A
A
A
Oil trap
B
Indoor unit
Outdoor unit
Indoor unit
B
B
If piping length is more than 16.4ft(5m)
CAUTION: Capacity is based on standard length and maximum allowance length is
on the basis of reliability.
Oil trap should be installed every 16.4~23feets (5~7 meters).
Service Manual 55
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
3-way Valve
Pumping Down
Liquid side
3-Way
Indoor unit
Outdoor unit
Open
valve
Gas side
Closed
3-Way
valve
Lo
CLOSE
CLOSE
Purge the air
• Procedure
(6) Operate the air conditioner in cooling mode
and stop it when the gauge indicates
1kg/cm2g.
(1) Confirm that both liquid side and gas side
valves are set to the open position.
– Remove the valve stem caps and confirm that
the valve stems are in the raised position.
– Be sure to use a hexagonal wrench to operate
the valve stems.
(7) Immediately set the Gas side valve to the
closed position.
– Do this quickly so that the gauge ends up indi-
cating 3 to 5kg/cm2g.
(2) Operate the unit for 10 to 15 minutes.
(8) Disconnect the charge set, and mount the
Liquid side and Gas side valve’s stem nuts
and the service port nut.
(3) Stop operation and wait for 3 minutes, then
connect the charge set to the service port of
the Gas side valve.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Connect the charge hose to the service port.
– Be sure to check for gas leakage.
(4) Air purging of the charge hose.
– Open the low-pressure valve on the charge set
slightly to air purge from the charge hose.
(5) Set the liquid side valve to the closed position.
56 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
1) Re-air purging
(Re-installation)
Liquid side
3-Way
Indoor unit
Closed
Outdoor unit
valve
Gas side
Closed
3-Way
valve
Gas cylinder
Lo
Refrigerant
OPEN
CLOSE
• Procedure
(6) Disconnect the charge set and the gas cylin-
der, and set the Liquid side and Gas side
(1) Confirm that both the liquid side valve and the
gas side valve are set to the closed position.
valves to the open position.
– Be sure to use a hexagonal wrench to operate
(2) Connect the charge set and a gas cylinder to
the service port of the Gas side valve.
the valve stems.
– Leave the valve on the gas cylinder closed.
(7) Mount the valve stem nuts and the service
port nut.
(3) Air purging.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
– Open the valves on the gas cylinder and the
charge set. Purge the air by loosening the flare
nut on the liquid side valve approximately 45°
for 3 seconds then closing it for 1 minute;
repeat 3 times.
* CAUTION:
Do not leak the gas in the air during Air
Purging.
– After purging the air, use a torque wrench to
tighten the flare nut on liquid side valve.
(4) Check for gas leakage.
– Check the flare connections for gas leakage.
(5) Discharge the refrigerant.
– Close the valve on the gas cylinder and dis-
charge the refrigerant until the gauge indicates
3 to 5 kg/cm2g.
Service Manual 57
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
2) Balance refrigerant of the 3-way valve
(Gas leakage)
Liquid side
Indoor unit
Outdoor unit
3-Way
valve
Open
Gas side
3-Way
valve
Open
Lo
OPEN
CLOSE
• Procedure
(1) Confirm that both the liquid side and gas side
valves are set to the back seat.
(3) Open the valve (Lo side) on the charge set and
discharge the refrigerant until the gauge indi-
cates 0 kg/cm2G.
(2) Connect the charge set to the 3-way valve’s
port.
– If there is no air in the refrigerant cycle (the
pressure when the air conditioner is not running
is higher than 1 kg/cm2G), discharge the refrig-
erant until the gauge indicates 0.5 to 1
kg/cm2G. if this is the case, it will not be neces-
sary to apply a evacuatin.
– Leave the valve on the charge set closed.
– Connect the charge hose to the service port.
– Discharge the refrigerant gradually; if it is dis-
charged too suddenly, the refrigeration oil will
also be discharged.
58 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
2. Evacuation
(All amount of refrigerant leaked)
Liquid side
Indoor unit
Outdoor unit
3-Way
valve
Open
Gas side
3-Way
valve
Open
Vacuum pump
Lo
OPEN
CLOSE
• Procedure
(1) Connect the vacuum pump to the center hose
of charge set center hose
(3) Close the valve (Lo side) on the charge set,
turn off the vacuum pump, and confirm that
the gauge needle does not move (approxima-
tely 5 minutes after turning off the vacuum
pump).
(2) Evacuation for approximately one hour.
– Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or
depleted, replenish as needed.
Service Manual 59
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
3. Gas Charging
(After Evacuation)
Liquid side
3-Way
Indoor unit
Outdoor unit
Open
valve
Gas side
Open
3-Way
valve
Check valve
Charging
cylinder
Lo
(1)
OPEN
CLOSE
• Procedure
\
(1) Connect the charge hose to the charging
cylinder.
This is different from previous procedures.
Because you are charging with liquid refrigerant
from the gas side, absolutely do not attempt to
charge with larger amounts of liquid refrigerant
while operating the air conditioner.
– Connect the charge hose which you dis-con-
nected from the vacuum pump to the valve at
the bottom of the cylinder.
– If you are using a gas cylinder, also use a
scale and reverse the cylinder so that the sys-
tem can be charged with liquid.
(4) Immediately disconnect the charge hose from
the 3-way valve’s service port.
– Stopping partway will allow the gas to be dis-
charged.
– If the system has been charged with liquid
refrigerant while operating the air conditioner
turn off the air conditioner before disconnecting
the hose.
(2) Purge the air from the charge hose.
– Open the valve at the bottom of the cylinder
and press the check valve on the charge set to
purge the air. (Be careful of the liquid refriger-
ant). The procedure is the same if using a gas
cylinder.
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant.
– If the system can not be charged with the spec-
ified amount of refrigerant, it can be charged
with a little at a time (approximately 150g each
time) while operating the air conditioner in the
cooling cycle; however, one time is not suffi-
cient, wait approximately 1 minute and then
repeat the procedure (pumping down-pin).
(5) Mount the valve stem nuts and the service
port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
CAUTION
This unit is charged with R-410A.
Pay attention not to charge R-22.
60 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
Additional gas charging
(Gas leakage)
• When refrigerant is insufficient by leakage, recharge the unit with the refrigerant up to normal operating suc-
tion pressure.
• Use the graph or the equation below to get operating suction pressure according to indoor and outdoor tem-
perature.
Suction pressure was measured at 3-way valve service port after operating the unit for 10 minutes.
The method of using graph
- Find outdoor temperature.
- Find indoor temperature onto the curve of outdoor temperature.
- Read suction pressure at the axis of ordinates.
The method of using equation
-. Calculate suction pressure after putting indoor and outdoor temperature into the equation.
Operating Suction Pressure (For R410A)
(According to Indoor & Outdoor Temperature)
(At operating the Unit for 10 minutes)
13
50ËšC
12
40ËšC
11
10
9
30ËšC
20ËšC
10ËšC
8
0ËšC
7
6
5
5
10
15
20
25
30
35
40
Indoor Temp. (ËšC)
P = 3 + 0.0123 x Tout1.5 + 0.8 x Tin0.5
2
.
Where, P
: Suction Pressure(kg/cm g)
Tout : Outdoor Temperature(ËšC)
Tin : Indoor Temperature(ËšC)
Service Manual 61
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
Cycle Parts
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
Temp. difference : approx. 0˚F(0°C)
• All amount of refrigerant leaked
out. Check refrigeration cycle.
Current
: less than 80% of
rated current
Temp. Difference
Operating Current
• Refrigerant leakege
Clog of refrigeration cycle
Defective compressor
Temp. difference : approx. 14°F(8°C)
Current
: less than 80% of
rated current
Temp. difference : less than 14°F(8°C)
• Excessive amount of refrigerant
Current
: over the reated
current
• Normal
Temp. difference : over 14°F(8°C)
NOTICE
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
Suction pressure
(Compared with
the normal value)
Temperature
(Compared with
the normal valve)
Cause of Trouble
Description
Defective compressor
Defective 4-way reverse valve
Current is low.
High
Higher
Excessive amount of
refrigerant
High pressure does not quickly
rise at the beginning of
operation.
Normal
Insufficient amount of
refrigerant (Leakage)
Clogging
Current is low.
Current is low.
Lower
Higher
NOTICE
1. The suction pressure is usually 4.5~6.0 kg/cm2G(Cooling) at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.
62 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
Electronic Parts (9k model)
Product does not operate at all.
(* Refer to Electronic Control Device drawing and Schematic diagram.)
Turn off Main Power
(After 20 seconds)
Turn on Main Power
Does "beeping" sound is made from the Indoor Unit?
YES
NO
Primarily, the operating condition of Micom is OK.
Check the voltage of power(About AC 115V, 60Hz)
• Main power's voltage
• Voltage applied to the unit
• Connecting method of Indoor/Outdoor connecting
cable
• Check PWB Ass'y(Outdoor unit)
- Fuse
Check each load(Indoor/Outdoor Fan Motor,
Compressor, Stepping Motor) and contacting
condition of related connector(including connecting
cable of Indoor/Outdoor Unit)
- Pattern damage
- Varistor(ZNR01J)
Check the connection housing for contacting
• Connector related to CN-POWER
• Connector related to CN-FAN
• Connector contacting of Outdoor Fan/Compressor
• Display PWB Ass'y Check
• Connector related to CN-DC/DC
PCB Board Operation Check
Content
Remedy
Items
• Power Transformer
(Outdoor unit)
±
- Input Voltage
- Output Voltage
- About AC115V 10% - Check the power voltage
• Replace SMPS
Module
±
- About DC15V 3
+
• IC01D(7812) Output
(Indoor/Outdoor unit)
• DC 12V
• Replace IC01D
+
• IC02D(7805) Output (Indoor unit)
IC03D(7805) Output (Outdoor unit)
• DC 5V
• Replace
IC02D(Indoor unit)
IC03D(Outdoor unit)
• IC01A(KIA7036, Reset IC)
OSC01B(4MHz)
(Indoor/Outdoor unit)
• Voltage of Outdoor unit Micom No. 18,
Voltage of Indoor unit Micom No. 43 and
soldering condition
• Replace faulty parts
Service Manual 63
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
The product is not operate with the remote controller.
Turn on Main Power
While the compressor has been stopped, the compressor does not
operate owing to the delaying function for 3 minutes after stopped.
When the compressor stopped Indoor Fan is driven by a low speed.
At this point the wind speed is not controlled by the remote controller.
(When operated in the Sleeping Mode, the wind speed is set to the
low speed by force.)
Caused by other parts except the remote controller
Cause by the remote controller
When the mark(
battery.
) is displayed in LCD screen, replace
Check the contact of CN-DISP connector.
When the detect switch(double key) inside the remote
controller door is fault, it is impossible to operate
Check DISP PWB Ass'y
- Voltage between CN DISP
+
-
: DC 5V
temperature regulating(
/
) and wind speed selecting.
Check the connecting circuit between the remote controller
MICOM (No. ) - R17(2Ω) - IR LED - Q1 - R16(2.2KΩ).
Check point
• Check the connecting circuit between PIN 43 -
R11L(1K) - C11L(680PF) - MICOM PIN
• Check Receiver Ass'y
64 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
Compressor/Outdoor Fan are unable to drive.
Turn on Main Power
Operate "Cooling Mode( )" by setting the desired temperature of the
remote controller is less than one of the indoor temperature by 2°F at least.
When in Fan Mode, Compressor/Outdoor Fan is stopped.
Check the sensor for indoor temperature is attached as close as to be
effected by the temperature of Heat Exchanger(EVA).
When the sensor circuit for indoor temperature and connector are in bad
connection or are not engaged, Compressor/Outdoor Fan is stopped.
• Check the related circuit of R02H(12.1K), R04H(6.2K), Micom (No.27)
(Indoor unit).
• Check the indoor temperature sensor is disconnected or not(About 10kΩ / at 77°F).
When the temperature around Outdoor PWB Ass'y is above 163°F the
compressor is stop and only Outdoor Fan is operating.
Check Relay(RY - COMP) for driving compressor.
• When the power(About AC200V) is applied to the connecting wire termi-
nal support transferred to compressor, PWB Ass'y is normal.
• Check the circuit related to the relay(Outdoor unit).
Check point
Between Micom(No.
5, 6) and GND
COMP ON
COMP OFF
DC5V
DC0V
Between IC01M, IC02M(No. 9)
and IC01M, IC02M(No. 8)
Below DC 1V
(app)
About DC12V
Turn off Main Power
• Check the electrical wiring diagram of outdoor side.
• Check the abnormal condition for the component of Compressor/Outdoor
Fan Motor.
Service Manual 65
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
When indoor Fan does not operate.
Does the voltage of each terminals of CN-MOTOR CONNECTOR in
Indoor unit corresponds to values in the Table of page 72
Does the voltage of terminal of CN-DC/DC CONNECTOR in
Check connecting condition of the CN-MOTOR CON-
Indoor unit corresponds to the values in the table of page 72
NECTOR
Do the voltage of terminal of
Check the pattern and the
CN-DC/DC CONNECTOR in
condition of Indoor unit PWB
Outdoor unit corresponds to the
Ass'y.
Check the interference of Indoor Fan.
values in the table of page 72
NO
Check the connecting condi-
Check the patterns and the
tion and disconnection of
Check the motor of Indoor Fan
conditions of outdoor unit
connecting wires between
PWB Assy's.
Indoor and Outdoor unit.
Indoor Fan may be stopped in the Soft Dry Mode(change to the Cooling Operation Mode).
Indoor Fan is to be stopped when Indoor pipe(coil) termperature is lower than 79°F.
(At that times, Defrost indicator is turned on)
66 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
When Vertical Louver does not operate.
• Confirm that the Vertical Louver is normally geared with the shaft of
Stepping Motor.
• If the regular torque is detected when rotating the Vertical Louver with
hands
Normal
• Check the connecting condition of CN-UP/DOWN Connector
• Check the soldering condition(on PWB) of CN-UP/DOWN Connector
Check the operating circuit of the Vertical Louver
+
• Confirm that there is DC 12V between pin (RED) of CN-UP/DOWN and
GND.
• Confirm that there is a soldering short at following terminals.
- Between 77 , 78 , 79 and 80 of MICOM
- Between 4 , 5 , 6 and 7 of IC02M
- Between 10 , 11 , 12 and 13 of IC01M
- Between 1 , 2 , 3 , 4 and 5 of CN-UP/DOWN
If there are no problems after above checks
• Confirm the assembly conditions that are catching and interfering parts in
the rotation radial of the Vertical Louver
Service Manual 67
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
When a comunication error occurs.
• The operation indicator of Indoor unit blinks five times.
• The red indicator of Outdoor unit blinks five times.
Check the connecting wires between Indoor and Outdoor unit for the
connecting error and the contacting condition.
Check the installation condition of outdoor unit.
Check for the communication error and the operating condition of product
after also operating with the remote controller, then taking above 2 minutes.
Apply the power again after about 20 seconds by the power of Outdoor unit
is off.
Check for the communication error and the operating condition of product
after also operating with the remote controller, then taking above 2 minutes.
Check the PWB assembly of Indoor and Outdoor unit.
Caution: If the connecting wires of Indoor and Outdoor unit are not connected within 2 minutes after the power
of Outdoor unit is applied, a communication error will occur. Therefore, the power should be applied
after connecting them.
68 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
The phenomena in case of connecting error
INDOOR UNIT
Connector Type
CN-DC/DC
Phenomena
Condition
Open and connecting error
• The same as the phenomenon of Outdoor Unit.
Blue
Black
Brown
Red
• The indoor fan does not operate.
• The operation indicator of Indoor unit blinks 8 times.
CN-MOTOR
Open
Open
Short between terminals
Open
• The up/down vane does not operate.
CN-UP/DOWN
CN-DISP
• The up/down vane does not smoothly operate.
• It does not operate with a remote controller.
• The operation indicator blinks once.
On for 0.5 second
Open
Off for 3 seconds
• The compressor and the outdoor fan stop.
• The indoor fan speed is low.
CN-TH
• The operation indicator blinks once
(on for 0.5 second, off for 3 seconds).
• The compressor operates continuously regardless
of the setting temperature and the variation of room
temperature.
Short between terminals
(
and ) of ROOM-TH.
• The operation indicator blinks once
(on for 0.5 second, off for 3 seconds)
• Continuous operation
Short between terminals
(
and ) of PIPE-TH.
Service Manual 69
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
OUTDOOR UNIT
Connector Type
Phenomena
Condition
• All functions stop.
• The operation with the remote controller, forced and
test one do not operate.
OPEN
CN-POWER
Connecting reversely
• PWB pattern is damaged when applying the power.
• All functions stop or the compressor does not operate.
• The operation with the remote controller, forced and test
one do not operate.
OPEN
RY-COMP
terminal
• All functions stop.
• The operation with the remote controller, forced and test
one do not operate.
Connecting reversely
• All functions stop.
• The operation with the remote controller, forced and
test one do not operate.
OPEN
OPEN
OPEN
CN-TRANS
CN-FAN
• The Indoor Fan does not operate.
• All functions stop.
• The operation with the remote controller, forced and test
one do not operate.
The connecting
wire of CN-
DC/DC, and
Indoor and
• The only signal of remote controller operation/stop is
inputted, but the product does not operate.
• The RED indicator of outdoor unit blinks 5 times after 2
minutes with applying the power.
Connecting error
Outdoor Unit
(
)
• The beep sound, such as "beep, beep, beep, beep,
beep", occurs periodically in Indoor unit.
• The signal input of a remote controller and operation of
product is impossible.
• The RED indicator blinks 5 times after 2 minutes with
applying the power.
Blue
Connecting error
Black
Brown
Red
(
)
• The signal of remote controller is inputted, but the
product does not operate.
• The RED indicator of outdoor unit and the operation
indicator of indoor one blinks 5 times after 2 minutes
with applying the power.
Connecting error
(
)
• No power for Indoor unit.
• The signal input of the remote controller and opera-
tion of product is impossible.
• The thermal protector of the Power Trans operates
when let it alone for long time.
Connecting error
(
)
• The signal of the remote controller is inputted.
• The fuse and Q61 in the Outdoor unit are damaged
when the indoor fan is operated.
Connecting error
(
)
• No power for Indoor unit.
• The signal input of the remote controller and opera-
tion of product is impossible.
• The RED indicator of the Outdoor unit blinks 5 times
after 2 minutes with applying the power.
Connecting error
(
)
70 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
Voltage of Connectors according to Indoor Fan Speed
Input Power
INDOOR
FAN
MOTOR
INDOOR PWB ASSY
1
4
4
3
3
TAB-N
RY-COMP-A
RY-COMP-B
Connecting wires
between Indoor
and Outdoor
CN-DC/DC
1 2 3 4 5
Indoor
Connecting Terminal
Outdoor
Connecting Terminal
CN-DC/DC
BL BK BR RD
BL
1
2
3
4
BK
BR
RD
12k
No. of pins
DC Voltage(±10%)
+
4
-
S-Hi
Hi
Med
Low
Off
0
3
35.5
32.96
11.97
25.17
17.28
11.97
INDOOR
CN-
MOTOR
2
3
11.97
11.97
11.97
4
3
2
2
35.5
32.96
15.87
25.17
15.87
17.28
15.87
0
INDOOR
CN-
DC/DC
15.87
15.87
4
3
2
2
35.5
32.96
15.87
25.17
15.87
17.28
15.87
0
OUTDOO
R CN-
DC/DC
15.87
15.87
Service Manual 71
Download from Www.Somanuals.com. All Manuals Search And Download.
Exploded View
Exploded View
Indoor Unit
135316
268711-4
145200-2
146811-2
145200-1
152302
W49800
145200
135080
145200-4
268711-1
249951
135515
268711-3
354210
267110
131410
INLET AIR
+
EVA MIDDLE
146811-1
266090
567480-1
35211B
352150
135500-2
159830
330870
346810
349600
146811-1
147581
135500-1
352380
359012
NOTE) Please ensure GCSC since the replacement parts may be changed demending upon the buyer's request.
*
Please check the correct parts in View RPL(Replacement Part List)on GCSC.
(GCSC Website http://biz.Lgservice.com)
72 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Exploded View
2. Outdoor Unit
437212
554031
567480-4
435511
549610
346811
559010
649950
552113
552116
566000
W0CZZ
552202
268711-6
567480-6
SUCTION
567502
W6640
554160
447910
437211
550140
552203-2
430410
435301
552203-1
NOTE) Please ensure GCSC since the replacement parts may be changed demending upon the buyer's request.
*
Please check the correct parts in View RPL(Replacement Part List)on GCSC.
(GCSC Website http://biz.Lgservice.com)
Service Manual 73
Download from Www.Somanuals.com. All Manuals Search And Download.
Replacement Parts List
Replacement Parts List
Parts List(Indoor)
PART No.
LOCATION
DESCRIPTION
REMARKS
LAN091CNP
LA090CPI
(ASNC091F2G0)
LAN091HNP
LAN121CNP
LA120CPI
LAN121HNP
LA120HPI
(ASNH121F2G0)
No.
LA090HPI
(ASNH091F2G0)
(ASNC121F2G0)
131410
Chassis Assembly
3141A20037C
4681A20055A
4758A20098A
4681A20047B
4960A20016A
5900A20063A
5238A20046A
3551A20225C
3087A30009B
5421A20265A
5211A21789C
5983A25015A
4995A20653J
6871A20999A
6609A10008B
6323A20004T
3550A20510A
3550A20511A
3531A20319F
3508A20092F
5230A20069B
6871A20921A
4520A30097A
6871A20363G
4681AP2968M
6711A20128F
5251AR1222R
3141A20037C
4681A20055A
4758A20098A
4681A20047B
4960A20016A
5900A20063A
5238A20046A
3551A20225C
3087A30009B
5421A20265A
5211A21789C
5983A25015A
4995A20653J
6871A20999A
6609A10008B
6323A20004T
3550A20510A
3550A20511A
3531A20319F
3508A20092F
5230A20069B
6871A20921A
4520A30097A
6871A20363G
4681AP2968M
6711A20128F
5251AR1222R
3141A20037C
4681A20055A
4758A20098A
4681A20047B
4960A20016A
5900A20063A
5238A20046A
3551A20225C
3087A30009B
5421A20265A
5211A21789C
5983A25015A
4995A20653K
6871A20999C
6609A10008B
6323A20004T
3550A20510A
3550A20511A
3531A20319F
3508A20092F
5230A20069B
6871A20921A
4520A30097A
6871A20363G
4681AP2968M
6711A20083R
5251AR1222R
3141A20037C
4681A20055A
4758A20098A
4681A20047B
4960A20016A
5900A20063A
5238A20046A
3551A20225C
3087A30009B
5421A20265A
5211A21789C
5983A25015A
4995A20653K
6871A20999C
6609A10008B
6323A20004T
3550A20510A
3550A20511A
3531A20319F
3508A20092F
5230A20069B
6871A20921A
4520A30097A
6871A20363G
4681AP2968M
6711A20083R
5251AR1222R
-
146811-1 Motor Assembly,DC,Stepping
Discharge
147581
346810
349600
359012
352380
135515
330870
354210
35211B
159830
249951
Louver,Horizontal
-
-
-
-
-
-
-
-
-
-
Motor Assembly,DC
Bracket,Motor
Fan,Turbo
Guide,Air
Cover Assembly,Top(Indoor)
Pan Assembly,Drain
Evaporator Assembly,First
Tube Assembly,Tubing
Filter Assembly,Air Cleaner
Case Assembly,Control(Indoor)
268711-3 PCB Assembly,Main
266090 HVPS,DC/DC
DC PCB
-
Inlet Air + Eva Middle
Left
567480-1 Thermistor,NTC
135500-2 Cover
135500-1 Cover
Right
135316
135080
152302
Grille Assembly,Front(Indoor)
Sunset
Sunset
-
Decor
Filter,Air
268711-1 PCB Assembly
145200 Link
Display PCB
-
268711-4 PCB Assembly,Sub
Sub PCB
Front
146811-2 Motor Assembly,DC,Stepping
267110
352150
Remote Controller Assembly
Hose Assembly,Drain
NOTE) Please ensure GCSC since the replacement parts may be changed demending upon the buyer's request.
*
Please check the correct parts in View RPL(Replacement Part List)on GCSC.
(GCSC Website http://biz.Lgservice.com)
74 Room Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Replacement Parts List
Parts List(Outdoor)
PART No.
LOCATION
DESCRIPTION
REMARKS
LAU091CNP
LA090CPO
LAU091HNP
LA090HPO
LAU121CNP
LA120CPO
(ASUC121FUG0)
LAU121HNP
LA120HPO
(ASUH121FUG0)
No.
(ASUC091FUG0) (ASUH091FUG0)
430410 Base Assembly,Outdoor
552203-1 Valve,Service
3041A20008K
5220A20006A
5220A20005B
5403A20019M
3041A20008K
5220A20006A
5220A20005B
5403A20019M
4961A10015D
4681A20122B
5901A10033A
4791A30002U
4H00982E
3041A20008K
5220A20006A
5220A20005B
5403A20019M
4961A10015D
4681A20122B
5901A10033A
4791A30002U
4H00982E
3041A20008K
5220A20006A
5220A20005B
5403A20019M
4961A10015D
4681A20122B
5901A10033A
4791A30002U
4H00982E
-
Gas Pipe
552203-2 Valve,Service
Liquid Pipe
554031 Condenser Assembly,Bending
-
549610 Bracket Assembly,Motor(Outdoor) 4961A10015D
-
346811 AC Motor Assembly
559010 Fan Assembly,Propeller
447910 Barrier Assembly,Outdoor
550140 Damper,Compressor
554160 Compressor Set,Korea
567502 Overload Protect
4681A20122B
5901A10033A
4791A30002U
4H00982E
-
-
-
-
2520UGAC2AA
6750U-L029A
5211A24118C
5211A26008B
5220AR3228D
6600L000013
-
2520UGAC2AA
6750U-L029A
5211A24118C
5211A26008B
5220AR3228D
6600L000013
6141A90007C
4995A21006S
6871A20901C
6323A20002L
6323A20016A
6120AR2359U
3721A20026M
3721A20027Q
3530A20006G
3551AR7184R
2520UGAC2AA
6750U-L029A
5211A24118C
5211A26008B
5220AR3228D
6600L000013
-
2520UGAC2AA
6750U-L029A
5211A24118C
5211A26008B
5220AR3228D
6600L000013
6141A90007C
4995A21006S
6871A20901C
6323A20002L
6323A20016A
6120AR2359U
3721A20026M
3721A20027Q
3530A20006G
3551AR7184R
-
-
552113 Tube Assembly,Condenser(Out)
552116 Tube Assembly,Reverse
552202 Valve,Reverse
-
-
-
566000 Switch,Pressure
-
561410 Solenoid
Only H/P Model
649950 Case Assembly,Control(Outdoor)
268711-6 PCB Assembly
4995A21006S
6871A20901C
6323A20002L
6323A20016A
6120AR2359U
3721A20026M
3721A20027Q
3530A20006G
4995A21006S
6871A20901C
6323A20002L
6323A20016A
6120AR2359U
3721A20026M
3721A20027Q
3530A20006G
3551AR7184R
-
Outdoor PCB
567480-4 Thermistor,NTC
Inlet-air+Cond. out
567480-6 Thermistor,NTC
Suction Pipe Temp.
W0CZZ Capacitor,Film,Box
437212 Panel Assembly,Rear(Outdoor)
437211 Panel Assembly,Front(Outdoor)
435301 Grille,Discharge
-
-
-
-
435511 Cover Assembly,Control(Outdoor) 3551AR7184R
REAR PANEL
NOTE) Please ensure GCSC since the replacement parts may be changed demending upon the buyer's request.
*
Please check the correct parts in View RPL(Replacement Part List)on GCSC.
(GCSC Website http://biz.Lgservice.com)
Service Manual 75
Download from Www.Somanuals.com. All Manuals Search And Download.
December, 2006
Printed in Korea
P/No.: 3828A20926C
Download from Www.Somanuals.com. All Manuals Search And Download.
|
Lantronix Switch SW 94000 User Manual
Lenovo Network Hardware 70BJ9005WW User Manual
Lenoxx Electronics MP3 Player MP 400 User Manual
LevelOne Computer Hardware N_One Wireless PCI Card User Manual
LG Electronics Air Conditioner SU SZ CHASSIS User Manual
Life Fitness Elliptical Trainer 90XW 0XXX 03 User Manual
Magnavox Flat Panel Television 15MF237S 27E User Manual
Maha Energy Battery Charger MH C9000 User Manual
Makita Planer M102 User Manual
McCulloch Chainsaw MAC 738 User Manual