LG Electronics Air Conditioner LA090HPO User Manual

LG  
LG  
Room Air Conditioner  
SERVICE MANUAL  
MODELS: LAN091CNP (ASNC091F2G0)  
LAU091CNP (ASUC091FUG0)  
LAN121CNP (ASNC121F2G0)  
LAU121CNP (ASUC121FUG0)  
LAN091HNP (ASNH091F2G0)  
LAU091HNP (ASUH091FUG0)  
LAN121HNP (ASNH121F2G0)  
LAU121HNP (ASUH121FUG0)  
LA090CPI (ASNC091F2G0)  
LA090CPO (ASUC091FUG0)  
LA120CPI (ASNC091F2G0)  
LA120CPO (ASUC091FUG0)  
LA090HPI (ASNH091F2G0)  
LA090HPO (ASUH091FUG0)  
LA120HPI (ASNH121F2G0)  
LA120HPO (ASUH121FUG0)  
CAUTION  
• BEFORE SERVICING THE UNIT, READ THE SAFETY  
PRECAUTIONS IN THIS MANUAL.  
• ONLY FOR AUTHORIZED SERVICE PERSONNEL.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Precautions  
Safety Precautions  
To prevent injury to the user or other people and property damage, the following instructions must  
be followed.  
â–  Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is  
classified by the following indications.  
This symbol indicates the possibility of death or serious injury.  
This symbol indicates the possibility of injury or damage to properties only.  
â–  Meanings of symbols used in this manual are as shown below.  
Be sure not to do.  
Be sure to follow the instruction.  
â–  Installation  
Do not use damaged power  
cords, plugs, or a loose socket.  
For electrical work, contact the  
dealer, seller, a qualified electri-  
cian, or an Authorized Service  
Center.  
Always use the power plug and  
socket with the ground terminal.  
• There is risk of fire or electric  
shock.  
• There is risk of fire or electric  
shock.  
• There is risk of electric shock.  
Install the panel and the cover of  
control box securely.  
Do not modify or extend the  
power cord.  
Do not install, remove, or re-  
install the unit by yourself (cus-  
tomer).  
• There is risk of fire or electric  
shock.  
• There is risk of fire or electric  
shock.  
• There is risk of fire, electric shock,  
explosion, or injury.  
Service Manual 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Precautions  
Be cautious when unpacking and For installation, always contact  
Do not install the product on a  
defective installation stand.  
installing the product.  
the dealer or an Authorized  
Service Center.  
• Sharp edges could cause injury. Be â€¢ There is risk of fire, electric shock,  
• It may cause injury, accident, or  
damage to the product.  
especially careful of the case  
edges and the fins on the con-  
denser and evaporator.  
explosion, or injury.  
Be sure the installation area  
does not deteriorate with age.  
Do not let the air conditioner run  
for a long time when the humidity  
is very high and a door or a win-  
dow is left open.  
• If the base collapses, the air condi- â€¢ Moisture may condense and wet or  
tioner could fall with it, causing  
property damage, product failure,  
and personal injury.  
damage furnishings.  
â–  Operation  
Take care to ensure that power  
cords could not be pulled out or  
damaged during operation.  
Do not place anything on the  
power cord.  
Do not turn the air-conditioner  
ON or OFF by plugging or  
unplugging the power plug.  
• There is risk of fire or electrical  
shock.  
• There is risk of fire or electrical  
shock.  
• There is risk of fire or electric  
shock.  
4 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Precautions  
Use a dedicated outlet for this  
appliance.  
Grasp the plug to remove the  
cord from the outlet. Do not  
touch it with wet hands.  
Do not place a heater or other  
appliances near the power cable.  
• There is risk of fire or electrical  
shock.  
• There is risk of fire or electrical  
shock.  
• There is risk of fire and electric  
shock.  
Do not allow water to run into  
electric parts.  
Do not store or use flammable  
gas or combustibles near the air  
conditioner.  
Do not use the product in a tight-  
ly closed space for a long time.  
• It may cause There is risk of fire,  
failure of the product, or electric  
shock.  
• There is risk of fire or failure of  
product.  
• Oxygen deficiency could occur.  
When flammable gas leaks, turn  
off the gas and open a window  
for ventilation before turn the  
product on. DO NOT use the tele-  
phone or turn switches on or off.  
Unplug the unit if strange  
sounds, odors, or smoke comes  
from it.  
Stop operation and close the  
window in storm or hurricane. If  
possible, remove the air condi-  
tioner from the window before  
the hurricane arrives.  
• There is risk of explosion or fire.  
• There is risk of electrical shock or  
fire  
• There is risk of property damage,  
failure of product, or electric shock.  
Service Manual 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Precautions  
Do not open the inlet grill of the  
product during operation. (Do  
not touch the electrostatic filter,  
if the unit is so equipped.)  
When the product is soaked  
(flooded or submerged), contact  
an Authorized Service Center.  
Ventilate the product from time  
to time when operating it togeth-  
er with a stove, etc.  
• There is risk of physical injury,  
electric shock, or product failure.  
• There is risk of fire or eletric  
shock.  
• There is risk of fire or electrical  
shock.  
Unplug the appliance before per-  
forming cleaning or mainte-  
nance.  
When the product is not be used  
for a long time, disconnect the  
power supply plug or turn off the  
breaker.  
Take care to ensure that nobody  
could step on or fall onto the  
outdoor unit.  
• There is risk of electrical shock.  
• There is risk of product damage or â€¢ This could result in personal injury  
failure, or unintended operation.  
and product damage.  
â–  Installation  
Always check for gas (refriger-  
ant) leakage after installation or  
repair of product.  
Install the drain hose to ensure  
that water is drained away prop-  
erly.  
Keep level even when installing  
the product.  
• Low refrigerant levels may cause  
failure of product.  
• A bad connection may cause water â€¢ To avoid vibration or water leakage.  
leakage.  
90Ëš  
6 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Precautions  
Do not install the product where  
the noise or hot air from the out-  
door unit could damage the  
neighborhoods.  
Use two or more people to lift  
and transport the air conditioner.  
Do not install the product where  
it will be exposed to sea wind  
(salt spray) directly.  
• It may cause a problem for your  
neighbors.  
• Avoid personal injury.  
• It may cause corrosion on the prod-  
uct. Corrosion, particularly on the  
condenser and evaporator fins,  
could cause product malfunction or  
inefficient operation.  
â–  Operation  
Do not direct airflow at room  
occupants. (Don't sit in the  
draft.)  
Do not use the product for spe-  
cial purposes, such as preserv-  
ing foods, works of art, etc. It is a  
consumer air conditioner, not a  
precision refrigeration system.  
Do not block the inlet or outlet of  
air flow.  
• This could damage your health.  
• There is risk of damage or loss of  
• It may cause product failure.  
property.  
Use a soft cloth to clean. Do not  
use harsh detergents, solvents,  
etc.  
Do not touch the metal parts of  
the product when removing the  
air filter. They are very sharp!  
Do not step on or put anyting on  
the product. (outdoor units)  
• There is risk of fire, electric shock,  
or damage to the plastic parts of  
the product.  
• There is risk of personal injury.  
• There is risk of personal injury and  
failure of product.  
Service Manual 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Precautions  
Always insert the filter securely.  
Clean the filter every two weeks  
or more often if necessary.  
Do not insert hands or other  
objects through the air inlet or  
outlet while the air conditioner is  
plugged in.  
Do not drink the water drained  
from the unit.  
• A dirty filter reduces the efficiency  
of the air conditioner and could  
cause product malfunction or dam-  
age.  
• There are sharp and moving parts  
that could cause personal injury.  
• It is not sanitary and could cause  
serious health issues.  
Use a firm stool or ladder when cleaning or main-  
taining the air conditioner.  
Replace the all batteries in the remote control with  
new ones of the same type. Do not mix old and new  
batteries or different types of batteries.  
• Be careful and avoid personal injury.  
• There is risk of fire or explosion  
â–  Disuse  
Do not recharge or disassemble the batteries. Do  
not dispose of batteries in a fire.  
If the liquid from the batteries gets onto your skin  
or clothes, wash it well with clean water. Do not use  
the remote if the batteries have leaked.  
• They may burn or explode.  
• The chemicals in batteries could cause burns or other  
health hazards.  
8 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensions  
Dimensions  
Symbols Used in this Manual  
This symbol alerts you to the risk of electric shock.  
This symbol alerts you to hazards that could cause harm to the  
air conditioner.  
This symbol indicates special notes.  
NOTICE  
Indoor Unit  
Hanger Hole  
W
D
H
Fix Hole  
Pipe Hole  
Model  
INDOOR UNIT  
Dimension  
W
H
mm(inch)  
mm(inch)  
mm(inch)  
600(23.6)  
600(23.6)  
146(5.7)  
D
Service Manual 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensions  
Outdoor Unit  
L2  
W
L3  
Gas side  
(3-way valve)  
Liquid side  
(2-way valve)  
MODEL  
unit  
9k, 12k Models  
DIM  
W
mm  
mm  
mm  
mm  
mm  
mm  
mm  
mm  
770(30.3)  
540(21.3)  
245(9.6)  
285(11.2)  
64(2.5)  
H
D
L1  
L2  
L3  
L4  
L5  
518(20.4)  
10(0.4)  
100(3.9)  
10 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Product Specifications  
Product Specifications  
AS-C091F2G0(LA091CNP) AS-C121F2G0(LA121CNP) AS-H091F2G0(LA091HNP) AS-H121F2G0(LA121HNP)  
AS-C091F2G0(LA090CP) AS-C121F2G0(LA120CP) AS-H091F2G0(LA090HP) AS-H121F2G0(LA120HP)  
Models  
Cooling Capacity  
(Min~Rating~Max)  
Heating Capacity  
(Min~Rating~Max)  
Power Input  
Running Current  
Starting Current  
kW  
Btu/h  
kW  
Btu/h  
W
A
A
2.87  
3.37  
2.87  
3.37  
9,800  
11,500  
9,800  
11,500  
-
-
2.87  
3.37  
-
-
9,800  
11,500  
Cooling/Heating  
Cooling/Heating  
Cooling/Heating  
980  
1,100  
980/980  
1,100/1,100  
9.4  
10  
9.4/9.4  
10/10  
57.0  
57.0  
57.0/57.0  
57.0/57.0  
W/W  
Btu/h.W  
W/W  
Ø / V / Hz  
%
2.93  
3.06  
2.93  
3.06  
EER  
10.0  
10.5  
10.0  
10.5  
COP  
Power Supply  
Power Factor  
-
-
2.93  
3.06  
1/115/60  
1/115/60  
1/115/60  
1/115/60  
90.7  
95.7  
90.7  
95.7  
Indoor,Max  
Outdoor,Max  
m
m
3/min(cfm)  
3/min(cfm)  
l/h  
9.3(330)  
9.3(330)  
9.3(330)  
9.3(330)  
Air Flow Rate  
25(883)  
25(883)  
25(883)  
25(883)  
Moisture Removal  
Sound Level  
1.4  
1.4  
1.4  
1.4  
Indoor,H/M/L  
Outdoor,Max  
dB(A)+3  
dB(A)+3  
g(oz)  
41/35/29  
41/35/29  
41/35/29  
41/35/29  
48  
48  
48  
48  
Refrigerant & Charge(at 7.5m)  
Type  
R410A, 900(31.8)  
R410A, 900(31.8)  
R410A, 900(31.8)  
R410A, 900(31.8)  
Rotary  
Rotary  
Rotary  
Rotary  
Model  
GK113CAA  
GK113CAA  
GK113CAA  
GK113CAA  
Compressor  
Motor Type  
PSC  
PSC  
PSC  
PSC  
Oil Type  
FVC68D(PVE)  
FVC68D(PVE)  
FVC68D(PVE)  
FVC68D(PVE)  
Oil Charge  
O.L.P Name  
Type  
cc  
W
330  
330  
330  
330  
MRA12053-12027  
MRA12053-12027  
MRA12053-12027  
MRA12053-12027  
Turbo Fan  
Turbo Fan  
Turbo Fan  
Turbo Fan  
Fan(Indoor)  
Motor Output  
Type  
Motor Type  
Motor Output  
24  
24  
24  
24  
Propeller  
Propeller  
Propeller  
Propeller  
Fan(outdoor)  
AC Induction  
AC Induction  
AC Induction  
AC Induction  
W
A
27  
20  
27  
20  
27  
20  
27  
20  
Circuit Breaker*  
Power Supply Cable  
No.*mm2  
No.*mm2+No.mm2  
mm(in)  
mm(in)  
mm(in)  
mm  
3*2.5  
3*2.5  
3*2.5  
3*2.5  
Power and Transmission Cable  
4*0.75  
4*0.75  
4*0.75  
4*0.75  
Piping  
Connections  
Drain Hose  
Liquid Side  
Gas Side  
O.D , I.D  
6.35(1/4)  
6.35(1/4)  
6.35(1/4)  
6.35(1/4)  
12.7(1/2)  
12.7(1/2)  
12.7(1/2)  
12.7(1/2)  
21.5,16(0.85,0.63)  
21.5,16(0.85,0.63)  
21.5,16(0.85,0.63)  
21.5,16(0.85,0.63)  
600*600*146  
600*600*146  
600*600*146  
600*600*146  
Indoor(W*H*D)  
inch  
23.62*23.62*5.75  
23.62*23.62*5.75  
23.62*23.62*5.75  
23.62*23.62*5.75  
Dimension  
mm  
770*540*245  
770*540*245  
770*540*245  
770*540*245  
Outdoor(W*H*D)  
inch  
30.31*21.26*9.65  
30.31*21.26*9.65  
30.31*21.26*9.65  
30.31*21.26*9.65  
Indoor  
Outdoor  
Indoor + Outdoor  
Temperature Control  
Plasma Filter  
Prefilter(washable/anti-fungus)  
Auto Clean  
CHAOS Wind(Auto Wind)  
Steps, Fan/Cool/Heat  
Airflow Direction Control(up&down)  
Airflow Direction Control(left&right)  
Remocon Type  
Setting Temperature  
Range  
kg(lbs)  
kg(lbs)  
15(33.1)  
15(33.1)  
15(33.1)  
15(33.1)  
Net Weight  
32(70.5)  
32(70.5)  
32(70.5)  
32(70.5)  
Tool Code(Chassis)  
SF + UL  
SF + UL  
SF + UL  
SF + UL  
Thermistor  
Thermistor  
Thermistor  
Thermistor  
Functions  
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
3/4  
3/4  
3/4/3  
3/4/3  
Auto  
Auto  
Auto  
Auto  
Auto  
Auto  
Auto  
Auto  
Wireless LCD  
Wireless LCD  
Wireless LCD  
Wireless LCD  
Cooling  
Heating  
18 ~ 30  
18 ~ 30  
18 ~ 30  
18 ~ 30  
-
-
16 ~ 30  
16 ~ 30  
Auto Operation (Micom Control)  
Auto Changeover (Micom Control)  
Self Diagnosis  
O
O
O
O
O
O
O
O
O
O
O
O
Timer  
24h, On/Off  
24h, On/Off  
24h, On/Off  
24h, On/Off  
Sleep Operation  
Soft Dry Operation  
Restart Delay(minute)  
Deice Control(Defrost)  
Hot Start  
O
O
3
-
O
O
3
-
O
O
3
O
O
3
O
O
O
-
O
O
O
-
-
-
Jet Cool  
O
-
O
-
Low Ambient Operation  
Special Function  
Dry Contact  
Network Solution(LGAP)  
PI485  
-
-
-
-
-
-
-
-
Network Functions  
-
-
-
-
-
-
-
-
Note:  
O : Applied, - : No relation  
* For circuit breaker rating, please conform to local standards wherever necessary.  
Some of functions are slightly different depending upon models.  
The specification may be subject to change without notic for purpose of improvement.  
Service Manual 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Installation  
Read carefully, and then follow step by step.  
Installation Parts  
Installation guide map  
Type "A" screw and plastic anchor  
Remote control holder  
Type "B" screw  
Installation Tools  
Figure  
Name  
Figure  
Name  
Screw driver  
Ohmmeter  
Electric drill  
Hexagonal wrench  
Measuring tape, Knife  
Hole core drill  
Ammeter  
Leak detector  
Thermometer,  
Horizontal meter  
Spanner  
Torque wrench  
Flaring tool set  
12 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Installation Map  
NOTICE  
Installation parts you should purchase.  
More than  
37.9"(120cm)  
More than  
19.6"(50cm)  
(Left and right  
Sleeve  
are identical)  
Bushing-Sleeve  
Putty(Gum Type Sealer)  
Bend the pipe as close as possible  
on the wall but be careful so that it  
may not break.  
Vinyl tape (Wide)  
• To carry out the drainage  
test, remove the air filter  
and pour water into the heat  
exchanger.  
Saddle  
• Apply after carrying out a  
drainage test.  
More than  
23.6"(60cm)  
More than  
11.8"(30cm )  
More than  
11.8"(30cm)  
Gas side piping  
(Optional part)  
(Optional part)  
Liquid side piping  
Additional drain pipe  
More than  
28"(70cm)  
Vinyl tape (Narrow)  
Connecting cable  
(Optional part)  
Service Manual 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Confirm The Refrigerant  
1. Check the quality label on the indoor and outdoor unit.  
2. Make certain that the refrigerant is R-410A.  
NOTICE  
THIS PRODUCT CONTAINS R-410A REFRIGERANT  
1) Different compressor oil  
- R-410A(Polyol ester) / R-22(Mineral).  
- Do not mix the existing mineral oil.  
- Do not apply used pipe, tools and gauges covered with the existing mineral oil.  
2) Absorption of moisture  
-Compressor’s oil has the high absorption rate of moisture.  
3) Composition  
- R-410A(R32:R125=50:50wt%).  
NOTE: Never mix with other refrigerants  
Example : Split type 12,000 Btu/h  
Capacity  
[%]  
120  
100  
80  
60  
40  
20  
0
100  
93  
89  
84  
76  
R-410A  
R-22  
100%  
70%  
50%  
30%  
0%  
0%  
30%  
50%  
70% 100%  
4) High pressure.  
- 1.6 times higher than R-22.  
- High Pressure refrigerant may cause personal injury.  
Boiling Pt.(°C)  
Vapor pressure(25°C)(kg f/cnf)  
Vapor density(25°C)(kg/m2)  
R-410A  
R-22  
-51.4  
-40.8  
15.9  
9.6  
64  
44.4  
Do not handle the pipe by yourself (customer) High-pressure refrigerant may cause personal injury.  
- manifold gauge ,charging and any piping tools must be dedicated to R-410A systems.  
14 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Select the best Location  
Indoor unit  
1. Do not have any heat or steam near the unit.  
2. Select a place where there are no obstacles in front  
of the unit.  
More than  
7.9"(20cm)  
More than  
19.6"(50cm)  
3. Make sure that condensation drainage can be conve-  
niently routed away.  
4. Do not install near a doorway.  
5. Ensure that the interval between a wall and the left  
(or right) of the unit is more than 19.6"(50cm). The  
unit should be installed as high as possible on the  
wall, allowing a minimum of 7.9"(20cm) from ceiling.  
More than  
19.6"(50cm)  
More than  
4.9ft(1.5m)  
6. Use a stud finder to locate studs to prevent unneces-  
sary damage to the wall.  
CAUTION: Install the indoor unit on the wall where the height from the floor is  
more than 4.9 feets(1.5 meters).  
Outdoor unit  
1. If an awning is built over the unit to prevent direct  
sunlight or rain exposure, make sure that heat radia-  
tion from the condenser is not restricted.  
More than  
23.6"(60cm)  
2. Ensure that the space around the back and sides is  
more than 11.8"(30cm). The front of the unit should  
have more than 28"(70cm) of space.  
More than  
11.8"(30cm)  
More than  
11.8"(30cm)  
3. Do not place animals and plants in the path of the  
warm air.  
More than  
28"(70cm)  
More than  
23.6"(60cm)  
4. Take the weight of the air conditioner into account  
and select a place where noise and vibration are min-  
imum.  
5. Select a place where the warm air and noise from the  
air conditioner do not disturb neighbors.  
Rooftop Installations  
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring  
method are adequate for the unit location. Consult local codes regarding rooftop mounting.  
If the outdoor unit is installed on roof structures or walls, this may result in excessive noise and vibration, and may  
be also classed as non serviceable installation.  
Service Manual 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Piping Length and Elevation  
Standard  
Max.  
Max.  
Additional  
Refrigerant  
g/m(oz/ft)  
Pipe Size  
Capacity  
Length  
Elevation  
length  
(Btu/h)  
Suction  
Evap  
m(ft)  
B
m(ft)  
A
m(ft)  
9k, 12k  
Ø12.7mm(1/2") Ø6.35mm(1/4")  
7.5(25)  
7.5(25)  
15(49)  
20(0.22)  
Indoor unit  
Outdoor unit  
Outdoor unit  
A
A
A
Oil trap  
B
Indoor unit  
Outdoor unit  
Indoor unit  
B
B
If piping length is more than 16.4ft(5m)  
CAUTION: Capacity is based on standard length and maximum allowance length is  
on the basis of reliability.  
Oil trap should be installed every 16.4~23feets (5~7 meters).  
16 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Preparing Work for Installation  
Open panel front  
1. Pull the upper part of the front panel.  
2. Lift up the panel.  
3. To detach the front panel, remove the two screws at the lower part.  
4. Detach the front panel from the body.  
5. To detach the panel, disconnect the connector at the upper part.  
Panel Front  
Connector  
Cover pipe and cover side remove  
1. Please remove the screw of the center tuning cover.  
2. Pull up the side cover of desired connecting direction, then  
cover side is separated.  
3. Pick the pipe hole of the side cover.  
CAUTION: After removing the pipe hole, cut  
the burr for safety.  
Pipe hole  
Side cover  
NOTICE  
When making pipe path through rear  
wall, you don’t need to pick the pipe hole.  
Drain hose junction  
1. Remove the rubber stopple in the desired drain direc-  
tion.  
2. Insert drain hose into the handle of drain pan, and  
join drain hose and connecting hose according to the  
figure by.  
Adhesive  
Onlythe  
desired direction  
Connecting  
part  
Drain  
hose  
rubber cap  
Service Manual 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Fixing Indoor Unit  
1. Attach an Installation guide map on the  
desired surface.  
2. Look at suited horizon by horizontal  
meter on the horizontal setting line, and  
fix lightly the map by adhesive tape.  
INSTALLATION GUIDE MAP  
I
N
S
T
A
L
L
A
T
Horizontality  
IO  
N
G
U
ID  
E
M
A
P
3. Make a hole with a diameter of 6mm and  
depth of 30-35mm by piercing a screw  
4. Drill the pierted part as a diameter of 50mm  
for connecting piping. (In case of piercing  
rear surface)  
point.  
INS  
T
A
IIA  
TION  
G
UID  
E M  
AP  
6. First, Drive the two points of the upper  
parts by screws. (Leave 10mm for hanging  
the product)  
5. Drive the fore plastic anchors into drilled  
points.  
INST  
ALLA  
TION GUIDE MAP  
INST  
ALLA  
TION GU  
Plastic anchors  
8. Drive the lower parts after facing the hole  
of product with plastic anchors, and fix  
completely the upper screws.  
7. Hang the hole of product at the upper  
screws, and remove the map. (Falling  
INST  
attention)  
ALLA  
TION GUIDE MAP  
Plastic anchors  
Hanger hole  
(Rear side of  
the product)  
9. Check the fixed product with light power.  
10. In case of nothing wrong, connect the  
pipe and the wire. (Refer to installation  
manual)  
Drill a Hole in the Wall  
WALL  
• Drill the piping hole with a ø50mm hole core drill.  
Drill the piping hole at either the right or the left with  
the hole slightly slanted to the outdoor side.  
Indoor  
Outdoor  
18 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Flaring work and connection of piping  
Flaring work and connection of piping  
Flaring Work  
Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure.  
Cutting the pipes and the cable.  
1. Use the piping kit accessory or the pipes purchased  
locally.  
2. Measure the distance between the indoor and the  
outdoor unit.  
Copper  
pipe  
Slanted Uneven Rough  
90°  
3. Cut the pipes a little longer than measured distance.  
4. Cut the cable 4.9ft(1.5m) longer than the pipe length.  
Removing burrs  
1. Completely remove all burrs from the cut cross section  
of pipe/tube.  
Pipe  
Reamer  
2. Put the end of the copper tube/pipe in a downward  
direction as you remove burrs in order to avoid dropping  
burrs into the tubing.  
Point down  
Putting nut on  
• Remove flare nuts attached to indoor and outdoor unit,  
then put them on pipe/tube having completed burr  
removal.  
Flare nut  
(not possible to put them on after flaring work)  
Copper tube  
Flaring work  
1. Firmly hold copper pipe in a die in the dimension shown  
in the table below.  
2. Carry out flaring work with the flaring tool.  
Handle  
Yoke  
Bar  
Bar  
Cone  
Outside diameter  
A
mm  
Ø6.35  
Ø9.52  
Ø12.7  
Ø15.88  
Ø19.05  
inch  
1/4  
3/8  
1/2  
5/8  
3/4  
mm  
Copper pipe  
Clamp handle  
1.1~1.3  
1.5~1.7  
1.6~1.8  
1.6~1.8  
1.9~2.1  
Red arrow mark  
Service Manual 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Flaring work and connection of piping  
Check  
Smooth all round  
1. Compare the flared work with the figure by.  
Inside is shiny without scratches  
2. If a flared section is defective, cut it off and do flaring  
work again.  
= Improper flaring =  
Inclined Surface Cracked Uneven  
damaged  
thickness  
Even length  
all round  
Connecting the Piping  
Indoor  
Preparing the indoor unit's piping and drain hose for installation through the wall.  
1. Route the indoor tubing and the drain hose in the  
direction of rear left or right  
Drain hose  
2. Tape the tubing, drain hose and the connecting cable.  
Be sure that the drain hose is located at the lowest  
side of the bundle. Locating at the upper side can  
cause drain pan to overflow inside the unit.  
Loop  
Gas side piping  
Connecting  
cable  
Liquid side piping  
Drain hose  
CAUTION: If the drain hose is routed inside the room, insulate the hose with an  
insulation material* so that dripping from "sweating"(condensation) will not dam-  
age furniture or floors.  
*Foamed polyethylene or equivalent is recommended.  
20 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Flaring work and connection of piping  
Connecting the piping with the indoor unit  
and drain hose with drain pipe  
1. Align the center of the pipings and sufficiently tighten  
the flare nut by hand.  
Indoor unit tubing  
Flare nut Pipings  
2. Tighten the flare nut with a wrench.  
Spanner (fixed)  
Flare nut  
Outside diameter  
Torque  
.
mm  
inch  
1/4  
3/8  
1/2  
kgf cm  
Ø6.35  
Ø9.52  
Ø12.7  
180~250  
340~420  
550~660  
Torque wrench  
Connection pipe  
Indoor unit tubing  
3. When extending the drain hose at the indoor unit,  
install the drain pipe.  
Drain pipe  
Indoor unit drain hose  
Vinyl tape(narrow)  
Adhesive  
Plastic bands  
Wrap the insulation material around the  
connecting portion.  
Insulation material  
1. Overlap the connection pipe insulation material and  
the indoor unit pipe insulation material. Bind them  
together with vinyl tape so that there may be no gap.  
2. Wrap the area which accommodates the rear piping  
housing section with vinyl tape.  
Indoor  
unit pipe  
Connection  
pipe  
Vinyl tape  
(wide)  
Wrap with vinyl tape  
Connecting cable  
Pipe  
3. Bundle the piping and drain hose together by wrap-  
ping them with vinyl tape over the range within which  
they fit into the rear piping housing section.  
Vinyl tape(narrow)  
Wrap with vinyl tape  
Pipe  
Vinyl tape(wide)  
Drain hose  
Service Manual 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Flaring work and connection of piping  
CAUTION: Installation Information  
For right piping. Follow the instruction below.  
Good case  
• Press on the upper side of clamp and unfold the tubing to downward slowly.  
Bad case  
• Following bending type from left to right may cause damage to the turbing.  
22 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Flaring work and connection of piping  
Connection of Piping -Outdoor  
Put a couple drops of refrigerant oil on the face of  
the flare before assembling taking care not to add  
any contaminants.  
Align the center of the pipings and sufficiently  
tighten the flare nut by hand.  
Finally, tighten the flare nut with torque wrench until the  
wrench clicks.  
Outdoor unit  
Liquid side piping  
(Smaller diameter)  
• When tightening the flare nut with torque wrench,  
ensure the direction for tightening follows the arrow on  
the wrench.  
Gas side  
piping  
(Bigger  
diameter)  
Outside diameter  
Torque  
mm  
Ø6.35  
Ø9.52  
Ø12.7  
Ø15.88  
Ø19.05  
inch  
1/4  
3/8  
1/2  
5/8  
3/4  
kgf.cm  
180~250  
340~420  
550~660  
630~820  
980~1210  
Torque wrench  
Service Manual 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connecting the cable between indoor unit and outdoor unit  
Connecting the cable between indoor unit and outdoor unit  
Connecting the Cables  
1. Remove the cover control from the unit by loosening  
Wiring Diagram  
the screw.  
Connecting cable(Low voltage)  
b
Indoor Unit  
Outdoor Unit  
2. Dismount caps on the conduit panel.  
3. Temporarily mount the conduit tubes on the conduit  
panel.  
4. Properly connect both the power supply and low volt-  
age lines to the corresponding terminals on the termi-  
nal block.  
Terminal  
(4P)  
Terminal  
(6P)  
1
2
3
4
1
2
3
4
Power supply  
a
5
L1*  
6
L2  
To  
branch  
circuit  
5. Ground the unit in accordance with local codes.  
6. Be sure to size each wire allowing several inches  
longer than the required length for wiring.  
7. Use lock nuts to secure the conduit tubes.  
G
Ground  
L1 is neutral for 115V models.  
*
NOTICE  
NOTICE  
Connector trade size for this unit is 1/2"(12.7mm).  
Refer to "How to connect wiring to the terminals" for  
instructions on connecting depending on the wire type  
you are using.  
1.  
shows field wiring.  
2. Separately wire the high and low voltage line.  
3. Use heat-proof electrical wiring capable of with-  
standing temperatures up to 167°F(75°C).  
4. Use outdoor and waterproof connection cable  
rated more than 300V for the connection between  
indoor and outdoor unit.  
WARNING:  
• Be sure to comply with local codes while  
running the wire from the indoor unit to  
the outdoor unit(size of wire and wiring  
method, etc).  
(For example, Type SJO-WA)  
• Every wire must be connected firmly.  
• No wire should be allowed to touch  
refrigerant tubing, the compressor or any  
moving parts.  
Outdoor unit  
Terminal block  
Over 5mm  
(0.2")  
Conduit panel  
Connecting  
cable  
Power Supply  
AWG(MIN)  
14 18  
Power  
source  
Fuse or breaker  
Capacity  
Power supply  
cord  
Model  
9k/12k  
Cover control  
1Ø, 115V  
20A  
24 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connecting the cable between indoor unit and outdoor unit  
Connection method of the connecting cable(Example)  
1. Dismount two-caps on the conduit panel.  
2. Make a hole appropriate for the passage of connec-  
tion cable through on cap by tool. (for low voltage  
line)  
3. Pass the connecting cable through the hole.  
4. Properly connect the cable on the terminal block.  
5. Fix the connection cable with clamp cord provided on  
the unit not to have strain at the terminal when the  
connection cable is pulled outside up to a 35 pound  
weight.  
6. Wind the vinyl tape round the connecting cable for  
sealing between the surface of the connection cable  
and cap.  
7. Mount the taped part of cable on the cap.  
8. Finally, mount the holed cap with the  
wound cable on the conduit panel.  
Terminal  
block  
Clamp cord  
Cap(Reuse)  
G
Lock nut  
Hole (for low  
voltage line)  
Cap  
(Remove)  
Taping  
(for sealing)  
Power supply line  
(1ø, 115V, 208/230V)  
Low voltage line  
(connecting cable)  
Conduit panel  
WARNING:  
Loose wiring may cause the terminal to over-  
heat or result in unit malfunction. A fire hazard  
may also exist. Therefore, be sure all wiring is  
tightly connected.  
When connecting each power wire to the corresponding  
terminal, follow instructions "How to connect wiring to  
the terminals" and fasten the wire tightly with the fixing  
screw of the terminal plate.  
Solid wire  
Loop  
How to connect wiring to the terminals  
• For solid core wiring (or F-cable)  
1. Cut the wire end with a wire cutter of wire-cutting pli-  
ers, then strip the insulation to expose the solid wire  
about 25mm(15/16")  
2. Using a screwdriver, remove the terminal screw(s) on  
the terminal plate.  
Insulation  
Strand wire  
3. Using pliers, bend the solid wire to from a loop suit-  
able for the terminal screw.  
Round  
terminal  
4. Shape the loop wire properly, place it on the terminal  
plater and tighten securely with the terminal screw  
using a screwdriver.  
• For strand wiring  
1. Cut the wire end with a wire cutter or wire-cutting pli-  
ers, then strip the insulation to expose the strand  
wiring about 10mm(3/8").  
2. Using a screwdriver, remove the terminal screw(s) on  
the terminal plate.  
Screw with  
special washer  
Round terminal  
Terminal plate  
Screw with  
special washer  
Round terminal  
Wire  
3. Using a round terminal fastener or pliers, securely  
clamp each stripped wire end with a round terminal.  
4. Position the round terminal wire, and replace and  
tighten the terminal screw using a screwdriver.  
Wire  
Service Manual 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connecting the cable between indoor unit and outdoor unit  
CAUTION  
After the confirmation of the above conditions, prepare the wiring as follows:  
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the method of  
wiring, be guided by the circuit diagram posted on the inside of control cover.  
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from  
vibrations to which the unit is subjected during the course of transportation. Check them and make  
sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)  
3) Specification of power source.  
4) Confirm that electrical capacity is sufficient.  
5) Confirm that the starting voltage is maintained at more than 90 percent of the rated voltage marked  
on the name plate.  
6) Confirm that the cable thickness is as specified in the power source specification.  
(Particularly note the relation between cable length and thickness.  
7) Always install an GFCI circuit breaker in a wet or moist area.  
8) The following would be caused by voltage drop.  
• Vibration of a magnetic switch, which will damage the contact point, open fuse, disturbance of the normal function of  
the overload.  
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and  
have an air gap contact separation of at least 3mm(0.12in) in each active(phase) conductors.  
26 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Checking the drainage and forming the pipings  
Checking the drainage and forming the pipings  
Checking the Drainage  
To check the drainage.  
1. Pour a glass of water on the evaporator.  
2. Ensure the water flows through the drain hose of the  
indoor unit without any leakage and goes out the  
drain exit.  
(mm2)  
Drain piping  
Downward slope  
1. The drain hose should point downward for easy drain  
flow.  
2. Do not make drain piping like the following.  
Accumulated  
drain water  
Do not raise  
Less than  
50mm gap  
Tip of drain hose  
dipped in water  
Air  
Water  
leakage  
Water  
leakage  
Water  
leakage  
Waving  
Ditch  
Service Manual 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Checking the drainage and forming the pipings  
Forming the Piping  
Form the piping by wrapping the connect-  
ing portion of the indoor unit with insula-  
tion material and secure it with two kinds  
of vinyl tapes.  
Seal small openings  
around pipings with a  
gum type sealer.  
Taping  
Drain hose  
• If you want to connect an additional drain hose, the  
end of the drain outlet should be routed above the  
ground. Secure the drain hose appropriately.  
In cases where the outdoor unit is  
installed below the indoor unit perform the  
following.  
Pipings  
Connecting cable  
1. Tape the piping, drain hose and connecting cable  
from down to up.  
2. Secure the tapped piping along the exterior wall  
using saddle or equivalent.  
Trap is required to prevent water  
from entering electrical parts.  
In cases where the outdoor unit is  
installed above the Indoor unit perform the  
following.  
Seal a small opening  
around the pipings  
with gum type sealer.  
1. Tape the piping and connecting cable from down to  
up.  
Trap  
2. Secure the taped piping along the exterior wall. Form  
a trap to prevent water entering the room.  
3. Fix the piping onto the wall by saddle or equivalent.  
Trap  
28 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Air purgingd  
AIR PURGING  
Air Purging  
Air purging  
The air and moisture remaining in the refrigerant system have undesirable effects as indicated below.  
1. Pressure in the system rises.  
2. Operating current rises.  
3. Cooling(or heating) efficiency drops.  
4. Moisture in the refrigerant circuit may freeze and block capillary tubing.  
5. Water may lead to corrosion of parts in the refrigeration system.  
Therefore, after evacuating the system, take a leak test for the piping and tubing between the indoor and outdoor  
unit.  
Air purging with vacuum pump  
1. Preparation  
• Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected  
and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on  
the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.  
2. Leak test  
• Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.  
CAUTION: Be sure to use a manifold valve for air purging. If it is not available, use a stop  
valve for this purpose. The "Hi" knob of the manifold valve must always be kept close.  
• Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylinder valve when the  
gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap.  
CAUTION: To avoid nitrogen entering the refrigerant system in a liquid state, the top of the  
cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is  
used in a vertical standing position.  
1. Do a leak test of all joints of the tubing(both indoor  
and outdoor) and both gas and liquid side service  
Manifold valve  
Pressure  
valves.  
Bubbles indicate a leak. Be sure to wipe off the  
soap with a clean cloth.  
gauge  
Lo  
Hi  
Indoor unit  
2. After the system is found to be free of leaks,  
relieve the nitrogen pressure by loosening the  
charge hose connector at the nitrogen cylinder.  
When the system pressure is reduced to normal,  
disconnect the hose from the cylinder.  
Outdoor unit  
Charge hose  
Nitrogen gas  
cylinder(in vertical  
standing position)  
Service Manual 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Air purgingd  
Soap water method  
Liquid side  
1. Remove the caps from the 2-way and 3-way valves.  
2. Remove the service-port cap from the 3-way valve.  
3. To open the 2-way valve turn the valve stem counterclock-  
wise approximately 90°, wait for about 2~3 sec, and close it.  
4. Apply a soap water or a liquid neutral detergent on the  
indoor unit connection or outdoor unit connections by a soft  
brush to check for leakage of the connecting points of the  
piping.  
Gas side  
2-way valve  
(Open)  
3-way valve  
(Close)  
5. If bubbles come out, the pipes have leakage  
Evacuation  
1. Connect the charge hose end described in the preceding  
steps to the vacuum pump to evacuate the tubing and  
indoor unit.  
Cap  
Hexagonal wrench  
Confirm the "Lo" knob of the manifold valve is open.  
Then, run the vacuum pump.  
The operation time for evacuation varies with tubing  
length and capacity of the pump. The following table  
shows the time required for evacuation.  
Indoor unit  
Required time for evacuation when 30 gal/h vacuum  
pump is used  
If tubing length is longer  
than 10m (33 ft)  
If tubing length is less  
than 10m (33 ft)  
10 min. or more  
15 min. or more  
Outdoor unit  
2. When the desired vacuum is reached, close the "Lo"  
knob of the manifold valve and stop the vacuum pump.  
Finishing the job  
1. With a service valve wrench, turn the valve stem of liquid  
side valve counter-clockwise to fully open the valve.  
2. Turn the valve stem of gas side valve counter-clockwise  
to fully open the valve.  
3. Loosen the charge hose connected to the gas side ser-  
vice port slightly to release the pressure, then remove  
the hose.  
4. Replace the flare nut and its bonnet on the gas side ser-  
vice port and fasten the flare nut securely with an  
adjustable wrench. This process is very important to pre-  
vent leakage from the system.  
Manifold valve  
Pressure  
gauge  
Lo  
Hi  
Open  
Close  
5. Replace the valve caps at both gas and liquid side ser-  
vice valves and fasten them tight.  
This completes air purging with a vacuum pump.  
The air conditioner is now ready to test run.  
Vacuum pump  
30 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Air purgingd  
Charging  
â–  Each outdoor unit is factory charged (nameplate charge) for the evaporator as well as a 7.5m(25ft) line set.  
Any time a line set is used either shorter or longer then the nominal 7.5m(25ft) line set length the refrigerant  
charge has to be adjusted.  
â–  Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are  
either added or removed based on 20g(0.22oz) of R-410A per meter(foot).  
Standard  
Length  
m(ft)  
Max.  
Max.  
Additional  
Refrigerant  
g/m(oz/ft)  
Pipe Size  
Capacity  
(Btu/h)  
Elevation  
length  
Suction  
Evap  
B
m(ft)  
A
m(ft)  
9k, 12k  
Ø12.7mm(1/2") Ø6.35mm(1/4")  
7.5(25)  
7.5(25)  
15(49)  
20(0.22)  
Example: A 30ft line set is used  
5 additional ft X 0.22 ounce per foot= add 1.1 ounces of R-410A  
Important:  
If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the unit  
nameplate charge adjusting for line sets longer or shorter than 7.5m(25ft).  
Confirm the refrigerant R-410A. Use manifold gauge and hose for R-410A.  
Service Manual 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Air purgingd  
Panel Front Assembly  
1. First, Check the side cover assembly  
exactly, and fix the power cord in the  
bottom groove of cover side left.  
2. Assemble connecting lead wire with  
controller, fix the upper part of panel  
front, and match the lower part of panel  
front.  
Panel Front  
Connector  
3. Screw up panel front, and suspend the  
hook of panel front in the groove.  
32 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Test running  
TEST RUNNING  
Test Running  
1. Check that all tubing and wiring are properly connected.  
2. Check that the gas and liquid side service valves are fully open.  
Prepare remote controller  
1. Remove the battery cover by pulling it according to  
the arrow direction.  
2. Insert new batteries making sure that the (+) and (–)  
of battery are installed correctly.  
3. Reattach the cover by pushing it back into position.  
NOTICE  
• Use 2 AAA(1.5volt) batteries. Do not use rechargeable  
batteries.  
• Remove the batteries from the remote controller if the  
system is not used for a long time.  
Settlement of outdoor unit  
Bolt  
1. Anchor the outdoor unit with a bolt and  
nut(ø0.39"(ø10mm)) tightly and horizontally on a con-  
crete or rigid mount.  
2. When installing on the wall, roof or rooftop, anchor  
the mounting base securely with a nail or wire  
assuming the influence of wind and earthquake.  
3. If the vibration of the unit is transmitted to the hose,  
secure the unit with an anti-vibration rubber.  
Tubing connection  
Evaluation of the performance  
Operate the unit for 15~20 minutes, then check the sys-  
tem refrigerant charge:  
Intake temperature  
Discharge air  
1. Measure the pressure of the gas side service valve.  
2. Measure the temperature of the intake and discharge  
of air.  
3. Ensure the difference between the intake tempera-  
ture and the discharge is more than 46.4°F(8°C)  
4. For reference; the gas side pressure of optimum con-  
dition is as below.(Cooling)  
Discharge  
temperature  
The air conditioner is now ready for use.  
Outside ambient  
TEMP.  
The pressure of the gas side  
service valve.  
Refrigerant  
R-410A  
95°F(35°C) 8.5~9.5kg/cm2G(120~135 P.S.I.G.)  
Service Manual 33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Test running  
NOTICE  
If the actual pressure is higher than shown, the system is most likely over-charged, and charge should be  
removed. If the actual pressure are lower than shown, the system is most likely undercharged, and  
charge should be added.  
PUMP DOWN  
This is performed when the unit is relocated or the refrigerant circuit is serviced.  
Pump Down means collecting all refrigerant into the outdoor unit without the loss of refrigerant.  
CAUTION: Be sure to perform Pump Down procedure in the cooling mode.  
Pump Down Procedure  
1. Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve.  
2. Open the gas side service valve halfway and purge the air in the manifold hose using the refrigerant.  
3. Close the liquid side service valve(all the way).  
4. Turn on the unit's operating switch and start the cooling operation.  
5. When the low-pressure gauge reading becomes 1 to 0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the gas side  
valve and then quickly turn off the unit. Now Pump Down procedure is completed, and all refrigerant is collected  
into the outdoor unit.  
34 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
How to replace picture & photograph  
How to replace picture & photograph  
1. Turn off power and then open  
2. Pull out the both links of lower 3. Push and close the top part of  
the upper part of front panel.  
part of front panel, as  
the front panel and then pull  
the bottom part of the panel  
forward until it is secured.  
described in the below picture.  
4. Take out picture.  
5. Turn upside-down of the  
picture and turn over mat, then  
take off a protective tape  
attached at the mat.  
6. Place the picture/photograph  
between the exited picture and  
mat. (Recommended size of a  
photo/picture: 450mm x  
450mm)  
Protective tape  
Mat  
450mm  
Mat  
450mm  
7. Cover mat and press down  
with hand(s) until contacting  
closely.  
8. Slide the photo graph/drawing 9. Push both links of lower part of  
panel inside and fix it. Then  
turn on.  
requested under both hanger  
parts as following, and fix them.  
Press the front panel lightly to  
close.  
In case a mat is not used, recommended size of a photo/picture:  
522mm x 522mm  
When powering on after replacing filter and picture,  
the front panel doesn't intervene.  
522mm  
522mm  
Service Manual 35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Operation  
Functions  
Indoor Unit  
Operation ON/OFF by Remote controller  
Sensing the Room Temperature  
• Room temperature sensor (THERMISTOR)  
Room temperature control  
• Maintains the room temperature in accordance with the Setting Temp.  
Starting Current Control  
• Indoor fan is delayed for 5 seconds at the starting.  
Time Delay Safety Control  
• Restarting is inhibited for approx. 3 minutes.  
Indoor Fan Speed Control  
• High, Med, Low and Auto  
Operation indication Lamps (LED)  
--- Lights up in operation  
Healthy Dehumidification Mode  
• Intermittent operation of fan at low speed  
Sleep Mode Auto Control  
• The fan is switched to low(Cooling), med(Heating) speed.  
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.  
Defrost control(Heating)  
• Both the indoor and outdoor fan stops  
during defrosting.  
• Hot start will be operated after  
defrosting ends.  
Auto Air Control by the unit electronic control  
• The fan is switched to intermittent or irregular operation.  
• The fan speed is automatically switched from high to low speed.  
Hot-start Control (Heating)  
Chaos Swing  
• The indoor fan stops until the  
indoor pipe temperature will be  
reached at 82°F(28°C).  
• The louver can be set at the desired position or swing up  
and down automatically.  
36 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
The function of main control  
1. Time delay Safety Control  
• 3min.; The compressor operation is delayed for 3 minutes to balance the pressure of cycle.  
(Protection of compressor)  
• 5sec.; The indoor fan is delayed for 5 seconds, when operating initially, to prevent noises occurred by the vertical  
louver and wind.  
• 2min.; The reversing valve is delayed for 2 minutes to prevent the refrigerant-gas for abnormal noise when the  
heating operation is OFF or switched to the other operation mode while compressor is off.  
While compressor is running, it takes 3~5 seconds to switch.  
2. Chaos Swing Mode  
• By the Chaos Swing key input, the vane automatically operates with the Chaos Swing or they are fixed to the  
desired direction.  
• While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.  
< Cooling Mode >  
< Heating Mode >  
CLOSED  
CLOSED  
8°  
8°  
OPEN  
OPEN  
3. Cooling Operation Mode  
• When selecting the Cooling(  
) Mode Operation, the unit will operate according to the setting by the  
remote control and the operation diagram is shown below.  
INTAKE AIR TEMP.  
SETTING TEMP. +1  
°F  
(Compressor ON)  
SETTING TEMP. -1  
°F  
(Compressor OFF)  
More than  
3 minutes  
More than  
3 minutes  
Setting  
Setting  
Setting  
INDOOR FAN SPEED  
COMPRESSOR  
Low  
OFF  
Low  
OFF  
fan speed  
fan speed  
fan speed  
ON  
ON  
ON  
â–  Protection of the indoor heat exchanger from frosting  
• Compressor and outdoor fan stop when indoor pipe temperature is below 32°F(0°C) and restart at the pipe  
temperature is above 45°F(7°C).  
Service Manual 37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
. Auto Operation (Electronic control mode)  
• The operation procedure is shown below. (Cooling & Heating Model)  
Press Start/Stop Button  
Select Auto Operation Mode  
Check the Room temperature  
Operation mode  
Indoor fan speed  
are decided automatically by the unit electronic control.  
Setting temperature  
Intake-air  
temperature  
Over  
70  
below  
76  
~
Over 76°F  
below 70  
°F  
°
F
°F  
Operation Mode  
Soft Dry  
Cooling  
Heating  
â– â– If initial mode is decided, that mode is continued without the room temperature changing.  
â–  Auto Operation for Cooling  
Operation Condition  
Intake-air Temperature  
Over 78°F  
Setting Temperature  
77°F  
Fan Speed  
Air Direction Control  
Over 76°F~below 78°F  
Over 72°F~below 76°F  
Intake air -1°C  
Intake air -0.5°C  
In this mode,  
when pressing  
the vertical air  
direction control  
button, vertical  
louver swings up  
and down  
When Auto Operation  
initial start  
Controlled by  
the electronic  
control  
Over 68°F~below 72°F Intake air temperature  
below 64°F  
Over 64°F~below 86°F  
below 64°F  
64°F  
Electronic control  
64°F  
When pressing room  
temperature setting  
button during Auto  
Operation  
automatically.  
over 86°F  
86°F  
INTAKE AIR TEMP.  
SETTING TEMP. +1°F  
(Compressor OFF)  
SETTING TEMP. -1°F  
(Compressor ON)  
INDOOR FAN SPEED  
COMPRESSOR  
The electronic control operation  
OFF ON  
ON  
OFF  
38 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
â– â– Auto Operation for Dehumidification(only Heating Model)  
• The Setting temperature will be same that of the auto operation for cooling.  
- Compressor ON temperature; Setting temperature +2°F  
- Compressor OFF temperature; Setting temperture -1°F  
Intake-air temp.  
Setting temp.  
below 68°F  
Over 68°F~below 70°F  
over 86°F  
86°F  
68°F  
Intake air temperature +1°F  
â– â– Auto Operation for Heating(only Heating Model)  
- Compressor ON temperature; Setting temperature  
+
- Compressor OFF temperature; Setting temperature 6°F  
â– â– Vertical louver auto operation : During Auto Operation, pressing the chaos swing button makes the horizon-  
tal louvers swing up and down automatically.  
If you want to stop auto-swing, press chaos swing button again.  
5. Healthy Dehumidification  
• When the dehumidification operation input by the remote control is received, the intake air temperature is  
detected and the setting temp is automatically set according to the intake air temperature.  
79°F ≤ Intake Air Temp  
â– â–  77°F  
75°F ≤ Intake Intake Air Temp<79°F  
64°F ≤ Intake Intake Air Temp<75°F  
Intake Air Temp<64°F  
â– â–  Intake Air Temp-2°F  
â– â–  Intake Air Temp-1°F  
â– â–  64°F  
• While in compressor off, the indoor fan repeats low airflow speed and pause.  
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification  
operation and 4-min compressor off repeat.  
Compressor ON Temp.  
â–  Setting Temp+1°F  
Compressor OFF Temp. â–  Setting Temp-1°F  
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.  
Service Manual 39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
6. Heating Operation Mode(only Heating Model)  
The unit will operate according to the setting conditions by the remote controller.  
The operation diagram is shown below.  
INTAKE AIR TEMP.  
+
SETTING TEMP. 6  
°F  
(Compressor OFF)  
A
B
A
SETTING TEMP.  
(Compressor ON)  
minimum  
10sec.  
minimum  
1 min.  
minimum  
10sec.  
Selecting  
fan speed  
Selecting  
fan speed  
INDOOR FAN SPEED  
COMPRESSOR  
Low  
OFF  
Low  
Low  
OFF  
ON  
OFF  
ON  
OFF  
• A point; While the indoor pipe temperature is higher than 95°F, indoor fan operates at low speed. When the  
indoor pipe temperature becomes lower than 95°F, indoor fan stops.  
• B point; When the indoor pipe temperature is higher than 100°F(38°C), fan operates at selected fan speed.  
â– â– Hot-Start Control  
• The indoor fan stops until the indoor pipe temperature will be reached at 82°F.  
• During heating operation, if indoor pipe temperature falls below 78°F fan stops.  
• The operation diagram is shown below.  
INDOOR PIPE  
TEMP.  
1min  
LOW  
82°F  
78°F  
Selecting  
fan speed  
INDOOR FAN SPEED  
COMPRESSOR  
OFF  
OFF  
ON  
40 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
7. Cooling or Heating Mode with Sleep Mode Auto Control  
• When selecting the Cooling( ) or the Heating(  
) combined with the Sleep Mode Auto Control( ), the  
operation diagram is as following.  
â– â– Cooling Mode with the Sleep Mode  
• The setting temperature will be automatically raised by 2°F 30 minutes later and by 4°F 1 hour later.  
• The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.  
30 minutes  
30 minutes  
INTAKE AIR TEMP.  
2°F  
2°F  
SETTING TEMP. +1  
(Compressor ON)  
°F  
SETTING TEMP. -1  
(Compressor OFF)  
°F  
More than  
3 minutes  
More than  
3 minutes  
INDOOR FAN SPEED  
COMPRESSOR  
Low  
ON  
Low  
OFF  
Low  
ON  
Low  
OFF  
Low  
ON  
â– â– Heating Mode with the Sleep Mode(only Heating Model)  
• The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.  
INTAKE AIR TEMP.  
SETTING TEMP. +6  
°F  
(Compressor OFF)  
SETTING TEMP.  
(Compressor ON)  
More than  
3 minutes  
More than  
3 minutes  
More than  
3 minutes  
INDOOR FAN SPEED  
COMPRESSOR  
Med  
ON  
Low or OFF  
OFF  
Med  
ON  
Low or OFF  
OFF  
Med  
ON  
Low or OFF  
OFF  
Service Manual 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
8. Forced Operation  
Operation procedures when the remote control can't be used.  
The operation will be started if the power button is pressed.  
If you want to stop operation, re-press the button.  
ON/OFF  
button  
Cooling  
Heat pump Model  
Model  
Cooling  
High  
Room Temp. ≥ 76°F(24°C) 70°F(21°C) ≤ Room Temp. < 76°F(24°C) Room Temp. < 70°F(21°C)  
Operating mode  
Indoor FAN Speed  
Cooling  
High  
Healthy Dehumidification  
Healthy Dehumidification Rule  
74°F(23°C)  
Heating  
High  
Setting Temperature 72°F(22°C)  
72°F(22°C)  
76°F(24°C)  
Test operation  
During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room tempera-  
ture and resets in 18 minutes.  
During test operation, if remote controller signal is received, the unit operates as remote controller sets.  
If you want to use this operation, Press and hold the ON/OFF button for 3~5 seconds, then the buzzer sound 1  
"beep".  
If you want to stop the operation, re-press the button.  
9. Auto restart  
In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate  
procedures automatically to the previous operating conditions.  
So there is no need of activating this function by pressing any key or button.  
In the initial mode, the fan operates at a low speed and the compressor starts 2.5~3 minutes later.  
As the compressor starts, the fan speed also resumes its previous setting mode.  
Helpful information  
Fan speed and cooling capacity.  
The cooling capacity indicated in the specification is the value when the fan  
speed is set to high, and the capacity will be lower at low or medium fan  
speed.  
High fan speed is recommended when you wish to cool the room quickly.  
NOTICE  
Auto restart function has set enable as factory default.  
But customer can set up by following this instruction.  
To be disable function  
- Press and hold the ON/OFF button for 6 seconds, then the buzzer sound 2 "beep" and the indicator lamp (1) blinks 4 times.  
To be enable function  
- Press and hold the ON/OFF button for 6 seconds, then the buzzer sound 2 "beep" and the indicator lamp (1) brights 4  
times.  
42 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Display Function  
Signal Receptor  
Receives the signals from the remote control.(Signal receiving sound: two short beeps or one long beep.)  
Operation Indication Lamps  
On/Off  
: Lights up during the system operation.  
Self-diagnosis Function  
Error  
Code  
Error LED  
(Indoor body operation LED)  
Error contents  
SVC check point  
• Indoor room temperature  
thermistor open/short  
• Indoor pipe temperature  
thermistor open/short.  
(once)  
1
2
5
• Indoor TH assy check  
3sec  
3sec  
3sec  
(twice)  
3sec  
• Outdoor pipe temperature  
thermistor open/short.  
• Outdoor TH assy check  
3sec  
(5times)  
3sec  
• Communication line/circuit  
check  
• Poor communication.  
Service Manual 43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Remote Control Operations  
The controls will look like the following.  
1. START/STOP BUTTON  
Operation starts when this button is pressed and stops when  
the button is pressed again.  
Controls  
2. OPERATION MODE SELECTION BUTTON  
Used to select the operation mode.  
Signal transmitter  
3. ROOM TEMPERATURE SETTING BUTTONS  
Used to select the room temperature.  
4. INDOOR FAN SPEED SELECTOR  
Used to select fan speed in four steps low, medium,  
high and CHAOS.  
5. JET COOL/HEATING(OPTIONAL)  
Used to start or stop the speed cooling/heaing.  
(speed cooling/heating operates super high fan speed in  
cooling/heatig mode.)  
5
6
1
3
6. CHAOS SWING BUTTON  
Used to stop or start louver movement and set the  
desired up/down airflow direction.  
4
7. ON/OFF TIMER BUTTONS  
Used to set the time of starting and stopping operation.  
10  
2
7
CANCEL  
9
12  
17  
8. TIME SETTING BUTTONS  
Used to adjust the time.  
SET  
ON  
OFF  
AUTO CLEAN  
11  
8
9. TIMER SET/CANCEL BUTTON  
Used to set the timer when the desired time is obtained and to cancel  
the Timer operation.  
°C/°F  
18  
14  
16  
13  
15  
10. SLEEP MODE AUTO BUTTON  
Used to set Sleep Mode Auto operation.  
11. AIR CIRCULATION BUTTON  
Used to circulate the room air without cooling or heating.  
Flip-up door  
(opened)  
12. ROOM TEMPERATURE CHECKING BUTTON  
Used to check the room temperature.  
Operation Mode  
13. NEO PLASMA(OPTIONAL)  
Used to start or stop the plasma-purification function.  
Cooling Operation  
14. HORIZONTAL AIRFLOW DIRECTION CONTROL BUTTON  
(OPTIONAL)  
Auto Operation or Auto Changeover  
Healthy Dehumidification Operation  
Used to set the desired vertical airflow direction.  
15. RESET BUTTON  
Used prior to resetting time.  
16. 2nd F Button  
Heating Operation  
Used prior to using modes printed in blue at the bottom of buttons.  
17. AUTO CLEAN (OPTIONAL)  
•
Cooling Model( ), Heat Pump Model(  
)
Used to set Auto Clean mode.  
18. °C/°F SWITCH BUTTON  
Used to switch temperature reading from Centigrade to Fahrenheit.  
44 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Disassembly  
Disassembly  
Indoor Unit  
WARNING: Disconnect the unit from  
power supply before making any  
checks. Be sure the power switch is set  
to "OFF"  
1. To remove the Grille from the Chassis.  
- Pull the grille bottom, the remove 2 securing screws.  
- Lift the both lower parts of panel front.  
- After pull down this panel a bit, separate connecting  
wire with product.  
Panel Front  
Connector  
2. To remove the Control Box.  
- Before removing the control box, be sure to  
disconnect the wires from PWB.  
- Pull the cover control out from the control box  
and disconnect other wires.  
Communication Connector  
Step Motro Connector  
Front Panel Connector  
- Remove securing screws.  
Motor Connector  
- Pull the control box out from the chassis carefully.  
Sensor Connector  
Service Manual 45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Disassembly  
3. To remove the Evaporator.  
- Remove hole tubing holde.  
- Remove 2 screws securing the evaporator.  
- Pull the evaporator out from the chassis carefully.  
Air Guide  
4. Before removing the Turbo Fan.  
- Remove the securing screws from the chassis.  
- Pull the pipe, top cover and the air guide.  
Top Cover  
Bracket  
5. To remove the Motor.  
- Remove the securing bolt from the motor shaft.  
- Pull the fan out from the motor shaft.  
Turbo Fan  
- Remove 4 screws securing motor mount from the  
chassis and lift up the motor mount and the bracket.  
Motor Mount  
Bolt  
46 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Schematic Diagram  
Schematic Diagram  
Heat Pump/Cooling Only Series(Indoor Unit)  
Service Manual 47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Schematic Diagram  
Heat Pump Series/ Cooling Only Series (Outdoor Unit)  
48 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Schematic Diagram  
INDOOR UNIT P.W.B. ASSEMBLY  
• P/No.: 6871A20999A (PCB ASSEMBLY, MAIN)  
Top View  
Bottom View  
Service Manual 49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Schematic Diagram  
OUTDOOR UNIT P.W.B. ASSEMBLY  
• P/No.: 6871A20901C (PCB ASSEMBLY, MAIN)  
Top View  
Bottom View  
50 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Schematic Diagram  
DISPLAY P.W.B. ASM  
• P/No.: 6871A20921A (PCB ASSEMBLY)  
Service Manual 51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Schematic Diagram  
Wiring Diagram  
(1) Indoor Unit (Cooling Only Models, & Heating Models)  
52 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Schematic Diagram  
(2) Outdoor Unit(Cooling Only Models, & Heating Models)  
Service Manual 53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Guide  
Troubleshooting Guide  
Refrigeration Cycle Diagram  
(1) Cooling Only Models  
INDOOR UNIT  
OUTDOOR UNIT  
LIQUID SIDE  
CAPILLARY TUBE  
HEAT  
HEAT  
EXCHANGE  
(EVAPORATOR)  
EXCHANGE  
(CONDENSER)  
GAS SIDE  
COMPRESSOR  
(2) Cooling & Heating Models  
INDOOR UNIT  
OUTDOOR UNIT  
CHECK VALVE  
LIQUID SIDE  
CAPILLARY TUBE  
HEAT  
HEAT  
EXCHANGE  
(EVAPORATOR)  
EXCHANGE  
(CONDENSER)  
GAS SIDE  
REVERSING  
VALVE  
COOLING  
HEATING  
COMPRESSOR  
54 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Guide  
Piping Length and Elevation  
Standard  
Max.  
Max.  
Additional  
Refrigerant  
g/m(oz/ft)  
Pipe Size  
Capacity  
Length  
Elevation  
length  
(Btu/h)  
Suction  
Evap  
m(ft)  
B
m(ft)  
A
m(ft)  
9k, 12k  
Ø12.7mm(1/2") Ø6.35mm(1/4")  
7.5(25)  
7.5(25)  
15(49)  
20(0.22)  
Indoor unit  
Outdoor unit  
Outdoor unit  
A
A
A
Oil trap  
B
Indoor unit  
Outdoor unit  
Indoor unit  
B
B
If piping length is more than 16.4ft(5m)  
CAUTION: Capacity is based on standard length and maximum allowance length is  
on the basis of reliability.  
Oil trap should be installed every 16.4~23feets (5~7 meters).  
Service Manual 55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Guide  
3-way Valve  
Pumping Down  
Liquid side  
3-Way  
Indoor unit  
Outdoor unit  
Open  
valve  
Gas side  
Closed  
3-Way  
valve  
Lo  
CLOSE  
CLOSE  
Purge the air  
• Procedure  
(6) Operate the air conditioner in cooling mode  
and stop it when the gauge indicates  
1kg/cm2g.  
(1) Confirm that both liquid side and gas side  
valves are set to the open position.  
– Remove the valve stem caps and confirm that  
the valve stems are in the raised position.  
– Be sure to use a hexagonal wrench to operate  
the valve stems.  
(7) Immediately set the Gas side valve to the  
closed position.  
– Do this quickly so that the gauge ends up indi-  
cating 3 to 5kg/cm2g.  
(2) Operate the unit for 10 to 15 minutes.  
(8) Disconnect the charge set, and mount the  
Liquid side and Gas side valve’s stem nuts  
and the service port nut.  
(3) Stop operation and wait for 3 minutes, then  
connect the charge set to the service port of  
the Gas side valve.  
– Use torque wrench to tighten the service port  
nut to a torque of 1.8 kg.m.  
– Connect the charge hose to the service port.  
– Be sure to check for gas leakage.  
(4) Air purging of the charge hose.  
– Open the low-pressure valve on the charge set  
slightly to air purge from the charge hose.  
(5) Set the liquid side valve to the closed position.  
56 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Guide  
1) Re-air purging  
(Re-installation)  
Liquid side  
3-Way  
Indoor unit  
Closed  
Outdoor unit  
valve  
Gas side  
Closed  
3-Way  
valve  
Gas cylinder  
Lo  
Refrigerant  
OPEN  
CLOSE  
• Procedure  
(6) Disconnect the charge set and the gas cylin-  
der, and set the Liquid side and Gas side  
(1) Confirm that both the liquid side valve and the  
gas side valve are set to the closed position.  
valves to the open position.  
– Be sure to use a hexagonal wrench to operate  
(2) Connect the charge set and a gas cylinder to  
the service port of the Gas side valve.  
the valve stems.  
– Leave the valve on the gas cylinder closed.  
(7) Mount the valve stem nuts and the service  
port nut.  
(3) Air purging.  
– Use torque wrench to tighten the service port  
nut to a torque of 1.8 kg.m.  
– Be sure to check for gas leakage.  
– Open the valves on the gas cylinder and the  
charge set. Purge the air by loosening the flare  
nut on the liquid side valve approximately 45°  
for 3 seconds then closing it for 1 minute;  
repeat 3 times.  
* CAUTION:  
Do not leak the gas in the air during Air  
Purging.  
– After purging the air, use a torque wrench to  
tighten the flare nut on liquid side valve.  
(4) Check for gas leakage.  
– Check the flare connections for gas leakage.  
(5) Discharge the refrigerant.  
– Close the valve on the gas cylinder and dis-  
charge the refrigerant until the gauge indicates  
3 to 5 kg/cm2g.  
Service Manual 57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Guide  
2) Balance refrigerant of the 3-way valve  
(Gas leakage)  
Liquid side  
Indoor unit  
Outdoor unit  
3-Way  
valve  
Open  
Gas side  
3-Way  
valve  
Open  
Lo  
OPEN  
CLOSE  
• Procedure  
(1) Confirm that both the liquid side and gas side  
valves are set to the back seat.  
(3) Open the valve (Lo side) on the charge set and  
discharge the refrigerant until the gauge indi-  
cates 0 kg/cm2G.  
(2) Connect the charge set to the 3-way valve’s  
port.  
– If there is no air in the refrigerant cycle (the  
pressure when the air conditioner is not running  
is higher than 1 kg/cm2G), discharge the refrig-  
erant until the gauge indicates 0.5 to 1  
kg/cm2G. if this is the case, it will not be neces-  
sary to apply a evacuatin.  
– Leave the valve on the charge set closed.  
– Connect the charge hose to the service port.  
– Discharge the refrigerant gradually; if it is dis-  
charged too suddenly, the refrigeration oil will  
also be discharged.  
58 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Guide  
2. Evacuation  
(All amount of refrigerant leaked)  
Liquid side  
Indoor unit  
Outdoor unit  
3-Way  
valve  
Open  
Gas side  
3-Way  
valve  
Open  
Vacuum pump  
Lo  
OPEN  
CLOSE  
• Procedure  
(1) Connect the vacuum pump to the center hose  
of charge set center hose  
(3) Close the valve (Lo side) on the charge set,  
turn off the vacuum pump, and confirm that  
the gauge needle does not move (approxima-  
tely 5 minutes after turning off the vacuum  
pump).  
(2) Evacuation for approximately one hour.  
– Confirm that the gauge needle has moved  
toward -76 cmHg (vacuum of 4 mmHg or less).  
(4) Disconnect the charge hose from the vacuum  
pump.  
– Vacuum pump oil.  
If the vacuum pump oil becomes dirty or  
depleted, replenish as needed.  
Service Manual 59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Guide  
3. Gas Charging  
(After Evacuation)  
Liquid side  
3-Way  
Indoor unit  
Outdoor unit  
Open  
valve  
Gas side  
Open  
3-Way  
valve  
Check valve  
Charging  
cylinder  
Lo  
(1)  
OPEN  
CLOSE  
• Procedure  
\
(1) Connect the charge hose to the charging  
cylinder.  
This is different from previous procedures.  
Because you are charging with liquid refrigerant  
from the gas side, absolutely do not attempt to  
charge with larger amounts of liquid refrigerant  
while operating the air conditioner.  
– Connect the charge hose which you dis-con-  
nected from the vacuum pump to the valve at  
the bottom of the cylinder.  
– If you are using a gas cylinder, also use a  
scale and reverse the cylinder so that the sys-  
tem can be charged with liquid.  
(4) Immediately disconnect the charge hose from  
the 3-way valve’s service port.  
– Stopping partway will allow the gas to be dis-  
charged.  
– If the system has been charged with liquid  
refrigerant while operating the air conditioner  
turn off the air conditioner before disconnecting  
the hose.  
(2) Purge the air from the charge hose.  
– Open the valve at the bottom of the cylinder  
and press the check valve on the charge set to  
purge the air. (Be careful of the liquid refriger-  
ant). The procedure is the same if using a gas  
cylinder.  
(3) Open the valve (Lo side on the charge set and  
charge the system with liquid refrigerant.  
– If the system can not be charged with the spec-  
ified amount of refrigerant, it can be charged  
with a little at a time (approximately 150g each  
time) while operating the air conditioner in the  
cooling cycle; however, one time is not suffi-  
cient, wait approximately 1 minute and then  
repeat the procedure (pumping down-pin).  
(5) Mount the valve stem nuts and the service  
port nut.  
– Use torque wrench to tighten the service port  
nut to a torque of 1.8 kg.m.  
– Be sure to check for gas leakage.  
CAUTION  
This unit is charged with R-410A.  
Pay attention not to charge R-22.  
60 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Guide  
Additional gas charging  
(Gas leakage)  
• When refrigerant is insufficient by leakage, recharge the unit with the refrigerant up to normal operating suc-  
tion pressure.  
• Use the graph or the equation below to get operating suction pressure according to indoor and outdoor tem-  
perature.  
Suction pressure was measured at 3-way valve service port after operating the unit for 10 minutes.  
The method of using graph  
- Find outdoor temperature.  
- Find indoor temperature onto the curve of outdoor temperature.  
- Read suction pressure at the axis of ordinates.  
The method of using equation  
-. Calculate suction pressure after putting indoor and outdoor temperature into the equation.  
Operating Suction Pressure (For R410A)  
(According to Indoor & Outdoor Temperature)  
(At operating the Unit for 10 minutes)  
13  
50ËšC  
12  
40ËšC  
11  
10  
9
30ËšC  
20ËšC  
10ËšC  
8
0ËšC  
7
6
5
5
10  
15  
20  
25  
30  
35  
40  
Indoor Temp. (ËšC)  
P = 3 + 0.0123 x Tout1.5 + 0.8 x Tin0.5  
2
.
Where, P  
: Suction Pressure(kg/cm g)  
Tout : Outdoor Temperature(ËšC)  
Tin : Indoor Temperature(ËšC)  
Service Manual 61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Guide  
Cycle Parts  
Trouble analysis  
1. Check temperature difference between intake and discharge air and operating current.  
Temp. difference : approx. 0ËšF(0°C)  
• All amount of refrigerant leaked  
out. Check refrigeration cycle.  
Current  
: less than 80% of  
rated current  
Temp. Difference  
Operating Current  
• Refrigerant leakege  
Clog of refrigeration cycle  
Defective compressor  
Temp. difference : approx. 14°F(8°C)  
Current  
: less than 80% of  
rated current  
Temp. difference : less than 14°F(8°C)  
• Excessive amount of refrigerant  
Current  
: over the reated  
current  
• Normal  
Temp. difference : over 14°F(8°C)  
NOTICE  
Temperature difference between intake and discharge air depends on room air humidity. When the room air  
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower  
temperature difference is larger.  
2. Check temperature and pressure of refrigeration cycle.  
Suction pressure  
(Compared with  
the normal value)  
Temperature  
(Compared with  
the normal valve)  
Cause of Trouble  
Description  
Defective compressor  
Defective 4-way reverse valve  
Current is low.  
High  
Higher  
Excessive amount of  
refrigerant  
High pressure does not quickly  
rise at the beginning of  
operation.  
Normal  
Insufficient amount of  
refrigerant (Leakage)  
Clogging  
Current is low.  
Current is low.  
Lower  
Higher  
NOTICE  
1. The suction pressure is usually 4.5~6.0 kg/cm2G(Cooling) at normal condition.  
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with  
putty.  
62 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Guide  
Electronic Parts (9k model)  
Product does not operate at all.  
(* Refer to Electronic Control Device drawing and Schematic diagram.)  
Turn off Main Power  
(After 20 seconds)  
Turn on Main Power  
Does "beeping" sound is made from the Indoor Unit?  
YES  
NO  
Primarily, the operating condition of Micom is OK.  
Check the voltage of power(About AC 115V, 60Hz)  
• Main power's voltage  
• Voltage applied to the unit  
• Connecting method of Indoor/Outdoor connecting  
cable  
• Check PWB Ass'y(Outdoor unit)  
- Fuse  
Check each load(Indoor/Outdoor Fan Motor,  
Compressor, Stepping Motor) and contacting  
condition of related connector(including connecting  
cable of Indoor/Outdoor Unit)  
- Pattern damage  
- Varistor(ZNR01J)  
Check the connection housing for contacting  
• Connector related to CN-POWER  
• Connector related to CN-FAN  
• Connector contacting of Outdoor Fan/Compressor  
• Display PWB Ass'y Check  
• Connector related to CN-DC/DC  
PCB Board Operation Check  
Content  
Remedy  
Items  
• Power Transformer  
(Outdoor unit)  
±
- Input Voltage  
- Output Voltage  
- About AC115V 10% - Check the power voltage  
• Replace SMPS  
Module  
±
- About DC15V 3  
+
• IC01D(7812) Output  
(Indoor/Outdoor unit)  
• DC 12V  
• Replace IC01D  
+
• IC02D(7805) Output (Indoor unit)  
IC03D(7805) Output (Outdoor unit)  
• DC 5V  
• Replace  
IC02D(Indoor unit)  
IC03D(Outdoor unit)  
• IC01A(KIA7036, Reset IC)  
OSC01B(4MHz)  
(Indoor/Outdoor unit)  
• Voltage of Outdoor unit Micom No. 18,  
Voltage of Indoor unit Micom No. 43 and  
soldering condition  
• Replace faulty parts  
Service Manual 63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Guide  
The product is not operate with the remote controller.  
Turn on Main Power  
While the compressor has been stopped, the compressor does not  
operate owing to the delaying function for 3 minutes after stopped.  
When the compressor stopped Indoor Fan is driven by a low speed.  
At this point the wind speed is not controlled by the remote controller.  
(When operated in the Sleeping Mode, the wind speed is set to the  
low speed by force.)  
Caused by other parts except the remote controller  
Cause by the remote controller  
When the mark(  
battery.  
) is displayed in LCD screen, replace  
Check the contact of CN-DISP connector.  
When the detect switch(double key) inside the remote  
controller door is fault, it is impossible to operate  
Check DISP PWB Ass'y  
- Voltage between CN DISP  
+
-
: DC 5V  
temperature regulating(  
/
) and wind speed selecting.  
Check the connecting circuit between the remote controller  
MICOM (No. ) - R17(2Ω) - IR LED - Q1 - R16(2.2KΩ).  
Check point  
• Check the connecting circuit between PIN 43 -  
R11L(1K) - C11L(680PF) - MICOM PIN  
• Check Receiver Ass'y  
64 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Guide  
Compressor/Outdoor Fan are unable to drive.  
Turn on Main Power  
Operate "Cooling Mode( )" by setting the desired temperature of the  
remote controller is less than one of the indoor temperature by 2°F at least.  
When in Fan Mode, Compressor/Outdoor Fan is stopped.  
Check the sensor for indoor temperature is attached as close as to be  
effected by the temperature of Heat Exchanger(EVA).  
When the sensor circuit for indoor temperature and connector are in bad  
connection or are not engaged, Compressor/Outdoor Fan is stopped.  
• Check the related circuit of R02H(12.1K), R04H(6.2K), Micom (No.27)  
(Indoor unit).  
• Check the indoor temperature sensor is disconnected or not(About 10kΩ / at 77°F).  
When the temperature around Outdoor PWB Ass'y is above 163°F the  
compressor is stop and only Outdoor Fan is operating.  
Check Relay(RY - COMP) for driving compressor.  
• When the power(About AC200V) is applied to the connecting wire termi-  
nal support transferred to compressor, PWB Ass'y is normal.  
• Check the circuit related to the relay(Outdoor unit).  
Check point  
Between Micom(No.  
5, 6) and GND  
COMP ON  
COMP OFF  
DC5V  
DC0V  
Between IC01M, IC02M(No. 9)  
and IC01M, IC02M(No. 8)  
Below DC 1V  
(app)  
About DC12V  
Turn off Main Power  
• Check the electrical wiring diagram of outdoor side.  
• Check the abnormal condition for the component of Compressor/Outdoor  
Fan Motor.  
Service Manual 65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Guide  
When indoor Fan does not operate.  
Does the voltage of each terminals of CN-MOTOR CONNECTOR in  
Indoor unit corresponds to values in the Table of page 72  
Does the voltage of terminal of CN-DC/DC CONNECTOR in  
Check connecting condition of the CN-MOTOR CON-  
Indoor unit corresponds to the values in the table of page 72  
NECTOR  
Do the voltage of terminal of  
Check the pattern and the  
CN-DC/DC CONNECTOR in  
condition of Indoor unit PWB  
Outdoor unit corresponds to the  
Ass'y.  
Check the interference of Indoor Fan.  
values in the table of page 72  
NO  
Check the connecting condi-  
Check the patterns and the  
tion and disconnection of  
Check the motor of Indoor Fan  
conditions of outdoor unit  
connecting wires between  
PWB Assy's.  
Indoor and Outdoor unit.  
Indoor Fan may be stopped in the Soft Dry Mode(change to the Cooling Operation Mode).  
Indoor Fan is to be stopped when Indoor pipe(coil) termperature is lower than 79°F.  
(At that times, Defrost indicator is turned on)  
66 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Guide  
When Vertical Louver does not operate.  
• Confirm that the Vertical Louver is normally geared with the shaft of  
Stepping Motor.  
• If the regular torque is detected when rotating the Vertical Louver with  
hands  
Normal  
• Check the connecting condition of CN-UP/DOWN Connector  
• Check the soldering condition(on PWB) of CN-UP/DOWN Connector  
Check the operating circuit of the Vertical Louver  
+
• Confirm that there is DC 12V between pin (RED) of CN-UP/DOWN and  
GND.  
• Confirm that there is a soldering short at following terminals.  
- Between 77 , 78 , 79 and 80 of MICOM  
- Between 4 , 5 , 6 and 7 of IC02M  
- Between 10 , 11 , 12 and 13 of IC01M  
- Between 1 , 2 , 3 , 4 and 5 of CN-UP/DOWN  
If there are no problems after above checks  
• Confirm the assembly conditions that are catching and interfering parts in  
the rotation radial of the Vertical Louver  
Service Manual 67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Guide  
When a comunication error occurs.  
• The operation indicator of Indoor unit blinks five times.  
• The red indicator of Outdoor unit blinks five times.  
Check the connecting wires between Indoor and Outdoor unit for the  
connecting error and the contacting condition.  
Check the installation condition of outdoor unit.  
Check for the communication error and the operating condition of product  
after also operating with the remote controller, then taking above 2 minutes.  
Apply the power again after about 20 seconds by the power of Outdoor unit  
is off.  
Check for the communication error and the operating condition of product  
after also operating with the remote controller, then taking above 2 minutes.  
Check the PWB assembly of Indoor and Outdoor unit.  
Caution: If the connecting wires of Indoor and Outdoor unit are not connected within 2 minutes after the power  
of Outdoor unit is applied, a communication error will occur. Therefore, the power should be applied  
after connecting them.  
68 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Guide  
The phenomena in case of connecting error  
INDOOR UNIT  
Connector Type  
CN-DC/DC  
Phenomena  
Condition  
Open and connecting error  
• The same as the phenomenon of Outdoor Unit.  
Blue  
Black  
Brown  
Red  
• The indoor fan does not operate.  
• The operation indicator of Indoor unit blinks 8 times.  
CN-MOTOR  
Open  
Open  
Short between terminals  
Open  
• The up/down vane does not operate.  
CN-UP/DOWN  
CN-DISP  
• The up/down vane does not smoothly operate.  
• It does not operate with a remote controller.  
• The operation indicator blinks once.  
On for 0.5 second  
Open  
Off for 3 seconds  
• The compressor and the outdoor fan stop.  
• The indoor fan speed is low.  
CN-TH  
• The operation indicator blinks once  
(on for 0.5 second, off for 3 seconds).  
• The compressor operates continuously regardless  
of the setting temperature and the variation of room  
temperature.  
Short between terminals  
(
and ) of ROOM-TH.  
• The operation indicator blinks once  
(on for 0.5 second, off for 3 seconds)  
• Continuous operation  
Short between terminals  
(
and ) of PIPE-TH.  
Service Manual 69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Guide  
OUTDOOR UNIT  
Connector Type  
Phenomena  
Condition  
• All functions stop.  
• The operation with the remote controller, forced and  
test one do not operate.  
OPEN  
CN-POWER  
Connecting reversely  
• PWB pattern is damaged when applying the power.  
• All functions stop or the compressor does not operate.  
• The operation with the remote controller, forced and test  
one do not operate.  
OPEN  
RY-COMP  
terminal  
• All functions stop.  
• The operation with the remote controller, forced and test  
one do not operate.  
Connecting reversely  
• All functions stop.  
• The operation with the remote controller, forced and  
test one do not operate.  
OPEN  
OPEN  
OPEN  
CN-TRANS  
CN-FAN  
• The Indoor Fan does not operate.  
• All functions stop.  
• The operation with the remote controller, forced and test  
one do not operate.  
The connecting  
wire of CN-  
DC/DC, and  
Indoor and  
• The only signal of remote controller operation/stop is  
inputted, but the product does not operate.  
• The RED indicator of outdoor unit blinks 5 times after 2  
minutes with applying the power.  
Connecting error  
Outdoor Unit  
(
)
• The beep sound, such as "beep, beep, beep, beep,  
beep", occurs periodically in Indoor unit.  
• The signal input of a remote controller and operation of  
product is impossible.  
• The RED indicator blinks 5 times after 2 minutes with  
applying the power.  
Blue  
Connecting error  
Black  
Brown  
Red  
(
)
• The signal of remote controller is inputted, but the  
product does not operate.  
• The RED indicator of outdoor unit and the operation  
indicator of indoor one blinks 5 times after 2 minutes  
with applying the power.  
Connecting error  
(
)
• No power for Indoor unit.  
• The signal input of the remote controller and opera-  
tion of product is impossible.  
• The thermal protector of the Power Trans operates  
when let it alone for long time.  
Connecting error  
(
)
• The signal of the remote controller is inputted.  
• The fuse and Q61 in the Outdoor unit are damaged  
when the indoor fan is operated.  
Connecting error  
(
)
• No power for Indoor unit.  
• The signal input of the remote controller and opera-  
tion of product is impossible.  
• The RED indicator of the Outdoor unit blinks 5 times  
after 2 minutes with applying the power.  
Connecting error  
(
)
70 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Guide  
Voltage of Connectors according to Indoor Fan Speed  
Input Power  
INDOOR  
FAN  
MOTOR  
INDOOR PWB ASSY  
1
4
4
3
3
TAB-N  
RY-COMP-A  
RY-COMP-B  
Connecting wires  
between Indoor  
and Outdoor  
CN-DC/DC  
1 2 3 4 5  
Indoor  
Connecting Terminal  
Outdoor  
Connecting Terminal  
CN-DC/DC  
BL BK BR RD  
BL  
1
2
3
4
BK  
BR  
RD  
12k  
No. of pins  
DC Voltage(±10%)  
+
4
-
S-Hi  
Hi  
Med  
Low  
Off  
0
3
35.5  
32.96  
11.97  
25.17  
17.28  
11.97  
INDOOR  
CN-  
MOTOR  
2
3
11.97  
11.97  
11.97  
4
3
2
2
35.5  
32.96  
15.87  
25.17  
15.87  
17.28  
15.87  
0
INDOOR  
CN-  
DC/DC  
15.87  
15.87  
4
3
2
2
35.5  
32.96  
15.87  
25.17  
15.87  
17.28  
15.87  
0
OUTDOO  
R CN-  
DC/DC  
15.87  
15.87  
Service Manual 71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exploded View  
Exploded View  
Indoor Unit  
135316  
268711-4  
145200-2  
146811-2  
145200-1  
152302  
W49800  
145200  
135080  
145200-4  
268711-1  
249951  
135515  
268711-3  
354210  
267110  
131410  
INLET AIR  
+
EVA MIDDLE  
146811-1  
266090  
567480-1  
35211B  
352150  
135500-2  
159830  
330870  
346810  
349600  
146811-1  
147581  
135500-1  
352380  
359012  
NOTE) Please ensure GCSC since the replacement parts may be changed demending upon the buyer's request.  
*
Please check the correct parts in View RPL(Replacement Part List)on GCSC.  
(GCSC Website http://biz.Lgservice.com)  
72 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exploded View  
2. Outdoor Unit  
437212  
554031  
567480-4  
435511  
549610  
346811  
559010  
649950  
552113  
552116  
566000  
W0CZZ  
552202  
268711-6  
567480-6  
SUCTION  
567502  
W6640  
554160  
447910  
437211  
550140  
552203-2  
430410  
435301  
552203-1  
NOTE) Please ensure GCSC since the replacement parts may be changed demending upon the buyer's request.  
*
Please check the correct parts in View RPL(Replacement Part List)on GCSC.  
(GCSC Website http://biz.Lgservice.com)  
Service Manual 73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Replacement Parts List  
Replacement Parts List  
Parts List(Indoor)  
PART No.  
LOCATION  
DESCRIPTION  
REMARKS  
LAN091CNP  
LA090CPI  
(ASNC091F2G0)  
LAN091HNP  
LAN121CNP  
LA120CPI  
LAN121HNP  
LA120HPI  
(ASNH121F2G0)  
No.  
LA090HPI  
(ASNH091F2G0)  
(ASNC121F2G0)  
131410  
Chassis Assembly  
3141A20037C  
4681A20055A  
4758A20098A  
4681A20047B  
4960A20016A  
5900A20063A  
5238A20046A  
3551A20225C  
3087A30009B  
5421A20265A  
5211A21789C  
5983A25015A  
4995A20653J  
6871A20999A  
6609A10008B  
6323A20004T  
3550A20510A  
3550A20511A  
3531A20319F  
3508A20092F  
5230A20069B  
6871A20921A  
4520A30097A  
6871A20363G  
4681AP2968M  
6711A20128F  
5251AR1222R  
3141A20037C  
4681A20055A  
4758A20098A  
4681A20047B  
4960A20016A  
5900A20063A  
5238A20046A  
3551A20225C  
3087A30009B  
5421A20265A  
5211A21789C  
5983A25015A  
4995A20653J  
6871A20999A  
6609A10008B  
6323A20004T  
3550A20510A  
3550A20511A  
3531A20319F  
3508A20092F  
5230A20069B  
6871A20921A  
4520A30097A  
6871A20363G  
4681AP2968M  
6711A20128F  
5251AR1222R  
3141A20037C  
4681A20055A  
4758A20098A  
4681A20047B  
4960A20016A  
5900A20063A  
5238A20046A  
3551A20225C  
3087A30009B  
5421A20265A  
5211A21789C  
5983A25015A  
4995A20653K  
6871A20999C  
6609A10008B  
6323A20004T  
3550A20510A  
3550A20511A  
3531A20319F  
3508A20092F  
5230A20069B  
6871A20921A  
4520A30097A  
6871A20363G  
4681AP2968M  
6711A20083R  
5251AR1222R  
3141A20037C  
4681A20055A  
4758A20098A  
4681A20047B  
4960A20016A  
5900A20063A  
5238A20046A  
3551A20225C  
3087A30009B  
5421A20265A  
5211A21789C  
5983A25015A  
4995A20653K  
6871A20999C  
6609A10008B  
6323A20004T  
3550A20510A  
3550A20511A  
3531A20319F  
3508A20092F  
5230A20069B  
6871A20921A  
4520A30097A  
6871A20363G  
4681AP2968M  
6711A20083R  
5251AR1222R  
-
146811-1 Motor Assembly,DC,Stepping  
Discharge  
147581  
346810  
349600  
359012  
352380  
135515  
330870  
354210  
35211B  
159830  
249951  
Louver,Horizontal  
-
-
-
-
-
-
-
-
-
-
Motor Assembly,DC  
Bracket,Motor  
Fan,Turbo  
Guide,Air  
Cover Assembly,Top(Indoor)  
Pan Assembly,Drain  
Evaporator Assembly,First  
Tube Assembly,Tubing  
Filter Assembly,Air Cleaner  
Case Assembly,Control(Indoor)  
268711-3 PCB Assembly,Main  
266090 HVPS,DC/DC  
DC PCB  
-
Inlet Air + Eva Middle  
Left  
567480-1 Thermistor,NTC  
135500-2 Cover  
135500-1 Cover  
Right  
135316  
135080  
152302  
Grille Assembly,Front(Indoor)  
Sunset  
Sunset  
-
Decor  
Filter,Air  
268711-1 PCB Assembly  
145200 Link  
Display PCB  
-
268711-4 PCB Assembly,Sub  
Sub PCB  
Front  
146811-2 Motor Assembly,DC,Stepping  
267110  
352150  
Remote Controller Assembly  
Hose Assembly,Drain  
NOTE) Please ensure GCSC since the replacement parts may be changed demending upon the buyer's request.  
*
Please check the correct parts in View RPL(Replacement Part List)on GCSC.  
(GCSC Website http://biz.Lgservice.com)  
74 Room Air Conditioner  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Replacement Parts List  
Parts List(Outdoor)  
PART No.  
LOCATION  
DESCRIPTION  
REMARKS  
LAU091CNP  
LA090CPO  
LAU091HNP  
LA090HPO  
LAU121CNP  
LA120CPO  
(ASUC121FUG0)  
LAU121HNP  
LA120HPO  
(ASUH121FUG0)  
No.  
(ASUC091FUG0) (ASUH091FUG0)  
430410 Base Assembly,Outdoor  
552203-1 Valve,Service  
3041A20008K  
5220A20006A  
5220A20005B  
5403A20019M  
3041A20008K  
5220A20006A  
5220A20005B  
5403A20019M  
4961A10015D  
4681A20122B  
5901A10033A  
4791A30002U  
4H00982E  
3041A20008K  
5220A20006A  
5220A20005B  
5403A20019M  
4961A10015D  
4681A20122B  
5901A10033A  
4791A30002U  
4H00982E  
3041A20008K  
5220A20006A  
5220A20005B  
5403A20019M  
4961A10015D  
4681A20122B  
5901A10033A  
4791A30002U  
4H00982E  
-
Gas Pipe  
552203-2 Valve,Service  
Liquid Pipe  
554031 Condenser Assembly,Bending  
-
549610 Bracket Assembly,Motor(Outdoor) 4961A10015D  
-
346811 AC Motor Assembly  
559010 Fan Assembly,Propeller  
447910 Barrier Assembly,Outdoor  
550140 Damper,Compressor  
554160 Compressor Set,Korea  
567502 Overload Protect  
4681A20122B  
5901A10033A  
4791A30002U  
4H00982E  
-
-
-
-
2520UGAC2AA  
6750U-L029A  
5211A24118C  
5211A26008B  
5220AR3228D  
6600L000013  
-
2520UGAC2AA  
6750U-L029A  
5211A24118C  
5211A26008B  
5220AR3228D  
6600L000013  
6141A90007C  
4995A21006S  
6871A20901C  
6323A20002L  
6323A20016A  
6120AR2359U  
3721A20026M  
3721A20027Q  
3530A20006G  
3551AR7184R  
2520UGAC2AA  
6750U-L029A  
5211A24118C  
5211A26008B  
5220AR3228D  
6600L000013  
-
2520UGAC2AA  
6750U-L029A  
5211A24118C  
5211A26008B  
5220AR3228D  
6600L000013  
6141A90007C  
4995A21006S  
6871A20901C  
6323A20002L  
6323A20016A  
6120AR2359U  
3721A20026M  
3721A20027Q  
3530A20006G  
3551AR7184R  
-
-
552113 Tube Assembly,Condenser(Out)  
552116 Tube Assembly,Reverse  
552202 Valve,Reverse  
-
-
-
566000 Switch,Pressure  
-
561410 Solenoid  
Only H/P Model  
649950 Case Assembly,Control(Outdoor)  
268711-6 PCB Assembly  
4995A21006S  
6871A20901C  
6323A20002L  
6323A20016A  
6120AR2359U  
3721A20026M  
3721A20027Q  
3530A20006G  
4995A21006S  
6871A20901C  
6323A20002L  
6323A20016A  
6120AR2359U  
3721A20026M  
3721A20027Q  
3530A20006G  
3551AR7184R  
-
Outdoor PCB  
567480-4 Thermistor,NTC  
Inlet-air+Cond. out  
567480-6 Thermistor,NTC  
Suction Pipe Temp.  
W0CZZ Capacitor,Film,Box  
437212 Panel Assembly,Rear(Outdoor)  
437211 Panel Assembly,Front(Outdoor)  
435301 Grille,Discharge  
-
-
-
-
435511 Cover Assembly,Control(Outdoor) 3551AR7184R  
REAR PANEL  
NOTE) Please ensure GCSC since the replacement parts may be changed demending upon the buyer's request.  
*
Please check the correct parts in View RPL(Replacement Part List)on GCSC.  
(GCSC Website http://biz.Lgservice.com)  
Service Manual 75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
December, 2006  
Printed in Korea  
P/No.: 3828A20926C  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Lantronix Switch SW 94000 User Manual
Lenovo Network Hardware 70BJ9005WW User Manual
Lenoxx Electronics MP3 Player MP 400 User Manual
LevelOne Computer Hardware N_One Wireless PCI Card User Manual
LG Electronics Air Conditioner SU SZ CHASSIS User Manual
Life Fitness Elliptical Trainer 90XW 0XXX 03 User Manual
Magnavox Flat Panel Television 15MF237S 27E User Manual
Maha Energy Battery Charger MH C9000 User Manual
Makita Planer M102 User Manual
McCulloch Chainsaw MAC 738 User Manual