Honeywell SUB Series Interval Data Recorders 62 0342 01 User Manual |
SUB Series Interval Data Recorders
INSTALLATION MANUAL
NOTE: IDRs with modular jacks can be powered from either
PRE-INSTALLATION
the first Honeywell meter or by an external power
supply (requires 120 VAC). IDRs with removable
screw-type connectors require an external power
INFORMATION
supply (provided).
The SUB Series Interval Data Recorder (IDR) is an energy
data collection device. Installation must be performed by
qualified personnel only and must be in accordance with local
and national electrical codes. Honeywell and its
representatives are not responsible for damage or injury from
improper installation.
SUBIDR-16’s are supplied with an ID letter for each group of 8
inputs to make them compatible with E-Mon Energy™
software. The available choices are A-B, C-D, E-F, G-H, I-J, K-
L, M-N, O-P, Q-R, S-T, U-V, W-X and Y-Z. No other combi-
nations are available. When mixing 8-point and 16-point IDRs
together, it may be necessary to jump a letter in the system.
As an example, if you have an 8-point IDR labeled “A”, “B” and
“C”, the 16-point IDR to choose would be the E-F unit.
The IDR is contained within a NEMA 12 enclosure and is
designed for INDOOR USE ONLY, where ambient
temperatures are between +32 and +120 ºF. It is available in 8
and 16 input configurations.
The IDR is available in three configurations.
The SUBIDR must be located in an area that is central to the
meters connected to it.
1. Modular Jacks (SUBIDR-8 and SUBIDR-16): Supplied
with all modular jacks for use only with Honeywell
meters.
IMPORTANT:
The meter that is connected to meter jack #1 on the
IDR must be within 100 feet from the IDR, as it sup-
plies low-voltage power to operate the IDR. All other
meters can be located up to 500 feet from the IDR.
NOTE: The IDR with modular jacks is designed to operate
with Honeywell meters only. Terminal input models
can support the monitoring of third-party metering
equipment; contact Honeywell for further information.
The IDR must be installed in a location according to these
guidelines to ensure continued safe, trouble-free operation.
Fig. 1. IDR board with modular jacks.
2. Plug-In Screw-Type Connectors (SUBIDR-8 and
SUBIDR-16): Supplied with all plug-in screw-type con-
nectors for use with third-party meters (electric, gas,
water, etc.) that are provided with a dry contact pulse
output. (Requires external power supply.)
—
—
Do not install near sensitive radio communication
equipment or receiving antenna systems.
Do not install near high-energy electrical fields such as
those produced by welding equipment or by high-
power electrical motors.
—
—
Always install in an area that is dry, away from any
potential liquid or chemical splash hazards. Never
install electrical equipment in an area where flamma-
ble chemicals or vapors are present.
The IDR enclosure’s door must be kept closed once
installed. Exposing the internal circuits to dust, dirt,
fumes or high humidity can damage the IDR.
NOTE: All internal circuits are isolated from the AC line.
Fig. 2. IDR with screw-type connectors.
62-0342-01
SUB SERIES INTERVAL DATA RECORDERS
removed. The third-party meter IDR uses a DIP switch to
perform this function. This switch is preset at the factory and
requires no further adjustment.
—
—
D7 (Low Battery) -> This LED must be OFF. This
LED indicates a low or missing battery.
D6 (System Error) -> This LED must be OFF.
3. Meter pulse indicators
—
Yellow LEDs P1 through P8 may be flashing.
These LEDs indicate each meter’s pulse rate.
The flash rate depends on how much load the
meter is measuring. The faster the pulse the
greater the load.
IMPORTANT:
IF THE METER MEASURES ZERO LOAD, THERE
IS NO METER PULSE, WHEN THE PULSE RATE
IS ZERO THE YELLOW LED INDICATOR WILL
REMAIN EITHER ON OR OFF UNTIL THERE IS A
LOAD.
NOTE: If one of the LEDs does not flash, verify the meter
connection first. If the meter is properly connected,
check the meter’s display for a flashing load indica-
tor.
4. Panel Indicators
—
Two LEDs are visible through the window on the
door of the stand-alone enclosure. THESE LEDS
ARE NOT PRESENT IN MMU STYLE IDRS.
Green LED (Power Indicator) -> The green LED
indicates that power is present at the IDR.
Red LED (Tamper Alarm) -> The red LED indi-
cates that the IDR door has been opened. This
tamper alarm LED will be on when the door is
closed, and will flash when the door is open.
When the software startup is performed, the IDR
will be initialized by the E-Mon Energy software
and the alarm LED will turn off as long as the door
remains closed. The alarm can only be reset
through the software.
—
—
Fig. 5. Overview of main circuit board.
MAIN CIRCUIT BOARD VISUAL
CHECKS
5. IDR 16 Option 16 Card (applies only to the SUBIDR-16
Once you have connected meter #1 to jack #1 in the IDR, the
IDR should be energized. If the IDR is not energized, verify:
model.)
—
For each meter (9-16) installed on the options
card, another set of yellow LEDs (P9-P16) will be
present. These LEDs indicate the meter pulse
rate for meters #9 through #16.
1. Meter #1 is turned on. (Meter #1 powers the IDR; if
Meter #1 is not installed and powered up, the IDR will
not function.)
2. Verify that JMP8 on the IDR circuit board has a jumper
installed.
3. Verify that J23 & J24 on the IDR circuit board are set in
the position labeled “MTR”. Both jumpers should be set
to the RIGHT position.
4. Verify that the cable between Meter #1 and Jack #1 on
the IDR is properly assembled. (See Appendix A for
cable assembly.)
OPTIONAL AC ADAPTER
(OPTIONAL EXTERNAL 120 VAC
POWER SUPPLY)
If you are NOT using the optional AC adapter to power the
IDR, proceed to Section 6.0.
NOTE: If the IDR is being powered by the optional AC
adapter instead of by Meter #1, see Section 5.0.
Instead of powering the IDR using Meter #1, Honeywell can
supply an optional AC adapter. If the IDR was provided with
this option, verify the following:
Verify the status of the LED indicators on the IDR circuit
board. (See Appendix B for locations.)
1. Jumpers J23 & J24 on the IDR circuit board are set to
the LEFT position (position labeled “EXT”.)
2. Jumper at JMP8 MUST be removed.
3. The AC adapter’s two-wire cord must be plugged into
the IDR at TB9. (The polarity of these wires does not
matter.)
1. Power Supply Indicators
—
—
L3, green -> This LED is ON.
L1, green -> This LED is ON.
2. System status indicators
D4 (CPU), red -> This LED flashes once per sec-
—
ond. If D4 flashes twice per second, the IDR is not
initialized. This will be addressed later using E-
Mon Energy software.
4. Plug the AC adapter into a 120 VAC outlet.
3
62-0342—01
SUB SERIES INTERVAL DATA RECORDERS
IMPORTANT:
METHOD 1: MODULAR PLUG METHOD
The AC adapter is designed to be used with a 120
VAC outlet only.
This method requires using 4 stranded conductors inside a
cable that is fitted with an RJ-11 type plug for 4-conductor
modular systems at each end of the cable.
5. The IDR should now be energized. Perform the visual
* Do not use any pre-made telephone cables. See Appendix A
for correct cable configuration.
checks outlined in section 4.
NOTE: The AC adapter provides an isolated 18 VAC/300
mA power source for the IDR.
1. Plug the 4-wire RJ-11 cable/plug assembly into Channel
A on the SUB-RS232K. Connect the other end of this
cable to the IDR at either of the two RS-485 ports at the
top left of the IDR circuit board.
2. The unused RS-485 port is used to connect another
cable to the next IDR. This is called a “daisy-chain” con-
nection. This can be done repeatedly to connect as
many as 52 individual IDRs.
SERIAL COMMUNICATIONS
Hardwired System using the SUB-RS232K
Communication Key.
(See the hardwired system configuration diagrams in
Appendix F.)
NOTE: The total combined cable length must be no more
than 4,000 feet.
The SUB-RS232K communications key allows you to connect
IDRs to a personal computer that has E-Mon Energy software
installed. The computer communicates with the IDRs through
the SUB-RS232K.
3. Each IDR has two LEDs (yellow and green) located
directly below the RS-485 jacks. If the system is prop-
erly wired, these two LEDs will normally be OFF. These
LEDs will flash when the computer and IDR are commu-
nicating.
The SUB-RS232K must be located within 15 feet of the host
computer.
METHOD 2: TERMINAL BLOCK METHOD
IDRs may also be daisy-chained using a 3-conductor cable.
Instead of using the two modular jacks for the RS-485 daisy
chain, you can use J20 at the bottom right corner of the IDR
circuit board.
Connecting the SUB-RS232K to the
computer
The SUB-RS232K is supplied with:
Remove this 3-terminal plug to facilitate attaching the wires
using the screw terminals that are captivated within the plug
housing.
•
•
•
(1) 8-conductor cable fitted with RJ-45 plugs
(1) DB-9 serial COM port adapter
(1) AC adapter that converts 120 VAC into the 7 VAC
used to power the SUB-RS232K.
1. 1. Daisy-chain the IDRs by connecting:
1. Connect the 8-conductor cable to the left-side jack
(labeled “RS232”) on the rear panel of the SUB-
RS232K.
•
•
•
All HI terminals together
All LO terminals together
All GND terminals together
2. Connect the appropriate COM port adapter (DB-9) to
the serial port on the back of the computer. Plug the 8-
conductor cable from the SUB-RS232K into the COM
port adapter.
3. Connect the 7 VAC AC adapter into the rear panel input
on the SUB-RS232K. Plug the adapter into a 120 VAC
outlet. On the front panel of the SUB-RS232K, two
LEDs will light up (POWER ON and AC ON.)
** This requires putting two wires into each of the 3 terminals.
2. Connecting to the SUB-RS232K.
You will need to attach an RJ-11 modular plug to the cable that
serves the RS-485 system.
On each channel on the back of the SUB-RS232K, the pin out
for each channel is as follows:
NOTE: When E-Mon Energy software is accessed on the
computer, a third LED will turn on. The SUB-RS232K
READY indicator will light up as soon as the E-Mon
Energy software is booted up and the correct COM
port is set up via the settings provided in the soft-
ware’s Locations menu.
Fig. 6. SUB-RS232K modular jack pin out.
Connecting IDRs to the SUB-RS232K using
RS-485
•
•
•
•
PIN1 - Not used
PIN2 - GND
PIN3 - HI
On the rear panel of the SUB-RS232K, there are three jacks
labeled as channels A, B and C. These are RS-485 serial
communications ports used to connect the IDRs. Each of
these three channels can be connected to as many as 52
individual IDRs over a total cable distance of 4000 feet.
Channels are independent and must not be connected to
each other. (See Appendix F.)
PIN4 - LO
NOTE: It is okay to use the J20 with the modular jacks if
needed.
This completes the installation of the IDR hardwired system.
62-0342—01
4
SUB SERIES INTERVAL DATA RECORDERS
Using the USB connection on your
computer
As an alternative to the SUB-RS232K converter, we offer the
SUB-USBK that allows you to convert the RS485 output from
your IDRs for direct connect to your USB connection on your
computer.
APPENDIX A - CABLE
CONFIGURATION
A. Four-Conductor Cables (IDR RS-485 Communication)
Baud Rate Selection
The communication baud rate is selected by means of a
jumper on the circuit board (See appendix C for location.)
There are three (3) selections: 19200, 9600 (factory default)
and 2400.
1. When using the IDR with a modem, the rate of 9600
should always be selected.
2. The baud rate on the IDR must always match the baud
rate selected in the E-Mon Energy software. Communi-
cation will not work if they are not set correctly.
3. After a baud rate change, press CPU Reset (See
Appendix C) to register the change in the IDR.
4. All IDRs in the “daisy chain” circuit must be set at the
same baud rate.
Fig. 7. connectors.
B. Six-Conductor Cables (Meters #2-#8, optional #9-#16)
Fig. 8. connectors.
C. Eight-Conductor Cables (Meter #1, RS-232 Key to
Computer)
Fig. 9. connectors.
NOTE: All cables are wired pin-to-pin (straight through) as
shown above.
5
62-0342—01
SUB SERIES INTERVAL DATA RECORDERS
APPENDIX B - LED INDICATORS
D7-Clear Red LED
Low Battery
MUST be "OFF"
(Indicates low battery
when lit)
L1-Green LED
Serial Communications
Power Supply
Always "ON"
(Indicates power supply
is okay if LED is ON)
D4-Red LED
CPU Status
Flashes once per
second
D6-Clear Red LED
System Error
Always "OFF" when
system is operating
normally
D1-Green LED
D2-Yellow LED
See "Serial
Communications"
L3-Green LED
Main Power Indicator
Always "ON"
P1-P8-Yellow LED
Meter Pulse Indicators
(Indicates input pulses
being received from
meters)
Fig. 10. LED indicators.
62-0342—01
6
SUB SERIES INTERVAL DATA RECORDERS
APPENDIX C - IDR CIRCUIT BOARD COMPONENTS
Battery
J3-J4-RS-485 Communications Jacks
See "Serial Communications"
(Ports used to connect one IDR
to another IDR or Key)
CPU Reset Button
Baud Rate Selection
See "Serial
Communications"
(Selects communication
baud rate ALWAYS set at
9600 BPS when modem
is present)
Baud Rate Selection
See Chapter 6
d"Communications"
M1-M8-Meter Inputs
(Ports used to connect
meters to IDR)
JMP-8-Meter Power Selection
See “Main Circuit Board
Visual Checks” and “Optional
AC Adapter”
(Selects external power, or
powered from Meter #1)
J20-RS485
Communications
See "Serial Communications"
TB9-External Power Input
See “Optional
AC Adapter”
(Connects external
power supply adapter)
J23 & J24-Input Power
Selection
See “Main Circuit
Board Visual Checks” and
“Optional AC Adapter”
Fig. 11. IDR circuit board components.
7
62-0342—01
SUB SERIES INTERVAL DATA RECORDERS
APPENDIX D - SYSTEM WIRING GUIDES
Wiring Guide for SUBIDR-8
DB-9 (DTE) Connector
RJ-45
SUB-RS232K
PC
RJ-11
6' cable provided by
Honeywell (15 ft max.)
8-conductor cable
& modular plug
AC Adapter
4-Conductor
Flat Modular Cable
Up to 4000 Feet Total
Daisy-Chain or
Star Connection
Channel 1 of 3
(One of three channels shown for clarity.)
(Up to 8 Meters)
IDR A
6-Cond.
RJ-45
8-Cond.
RJ-45
6-Cond.
RJ-45
RJ-11
(Up to 8 Meters)
Up to 52 SUBIDR-8s per channel
IDR Z
~
~
Note: Meter 1 must be installed within
100 feet of IDR. Meters 2-8 must be installed
within 500 feet of IDR.
CONNECTION
CABLE TYPE
CONNECTOR
SUBIDR to Honeywell Meter #1
8-cond. 22-26 AWG
flat modular cable
RJ-45
SUBIDR to Honeywell Meters #2-8
6-cond. 22-26 AWG
(Pins 1 & 8 not used)
RJ-45
SUBIDR to SUBIDR
4-cond. 26 AWG
4-cond. 26 AWG
RJ-11
SUBIDR to SUB-RS232K
SUB-RS232K to Computer *
RJ-11
8-cond. 22-26 AWG
flat modular cable
RJ-45/DTE
SUB-RS232K to Modem *
SUBIDR to SUB-USBK *
8-cond. 22-26 AWG
flat modular cable
RJ-45
Allows connection directly
to the computer USB
SUBIDR to Pulse Meter
* Supplied by Honeywell
2-cond. 14-22 AWG
Note: When constructing field-installed cables, modular cables must be made
so that the individual wires go through on the same pin number.
Fig. 12. Wiring overview for SUBIDR-8.
62-0342—01
8
SUB SERIES INTERVAL DATA RECORDERS
Wiring Guide for SUBIDR-16
DB-9 (DTE) Connector
RJ-45
SUB-RS232K
PC
RJ-11
6' cable provided by
Honeywell (15 ft max.)
8-conductor cable
& modular plug
AC Adapter
4-Conductor
Flat Modular Cable
Up to 4000 Feet Total
Daisy-Chain or
Star Connection
Channel 1 of 3
(One of three channels shown for clarity.)
IDR A-B
(Up to 16 Meters)
6-Cond.
RJ-45
8-Cond.
RJ-45
6-Cond.
RJ-45
RJ-11
(Up to 16 Meters)
IDRY-Z
Up to 26 SUBIDR-16s per channel
(3 channels per SUB-RS232K)
~
~
3rd
Party
Meter
3rd
Party
Meter
3rd
Party
Meter
Pair of wires
(#22-#14 AWG)
Note: Meter 1 must be installed within
100 feet of IDR. Meters 2-8 must be installed
within 500 feet of IDR.
CONNECTION
CABLE TYPE
CONNECTOR
SUBIDR to Honeywell Meter #1
8-cond. 22-26 AWG
flat modular cable
RJ-45
SUBIDR to Honeywell Meters #2-16 6-cond. 22-26 AWG
RJ-45
(Pins 1 & 8 not used)
SUBIDR to SUBIDR
4-cond. 26 AWG
4-cond. 26 AWG
RJ-11
IDR to RS-232 Key 2000
SUB-RS232K to Computer *
RJ-11
8-cond. 22-26 AWG
flat modular cable
RJ-45/DTE
SUB-RS232K to Modem *
SUBIDR to SUB-USBK *
8-cond. 22-26 AWG
flat modular cable
RJ-45
Allows connection directly
to the computer USB
SUBIDR to Pulse Meter
* Supplied by Honeywell
2-cond. 14-22 AWG
Note: When constructing field-installed cables, modular cables must be made
so that the individual wires go through on the same pin number.
Fig. 13. Wiring overview for SUBIDR-16.
9
62-0342—01
SUB SERIES INTERVAL DATA RECORDERS
APPENDIX E - HARDWIRED SYSTEM CONFIGURATION DIAGRAMS
SUBIDR-8, Using Honeywell Meters:
IDR
Up to 8 Meters
Up to 4000 Feet Total
~
~
Up to 52
SUBIDR-8’s
Channel 1
IDR
Up to 8 Meters
PC
RS-232 Serial Port
COM1 - COM4
15’ max
SUB-RS232K*
Channel 2
IDR
IDR
AC Adapter
Up to 8 Meters
Channel 3
Up to 4000 Feet Total
~
~
Up to 52
SUBIDR-8’s
Up to 8 Meters
NOTE: Meter #1 must be installed within 100 feet of IDR.
Meters #2-16 must be installed within 500 feet of IDR.
Meter #1 uses 8-conductor cable.
Meters #2-16 use 6-conductor cable.
Fig. 14. Hard-wiring the SUBIDR-8.
62-0342—01
10
SUB SERIES INTERVAL DATA RECORDERS
SUBIDR-16, Using HoneywellMeters
IDR
IDR
Up to 16 Meters
Up to 4000 Feet Total
~
~
Up to 26
Channel 1
SUBIDR-16’s
Up to 16 Meters
PC
RS-232 Serial Port
COM1 - COM4
Channel 2
SUB-RS232K*
6' cable provided by
Honeywell (15 ft max.)
IDR
IDR
AC Adapter
Up to 16 Meters
Channel 3
Up to 4000 Feet Total
~
~
Up to 26
SUBIDR-16’s
Up to 16 Meters
NOTE: Meter #1 must be installed within 100 feet of IDR.
Meters #2-#16 must be installed within 500 feet of IDR.
Meter #1 uses 8-conductor cable.
Meters #2-16 use 6-conductor cable.
SUBIDR-16, Using Other Utility-Type Meters
(Gas, Water, Etc.)
IDR
Up to 16 Meters
AC Adapter
Up to 4000 Feet Total
~
~
Up to 26
SUBIDR-16’s
Channel 1
IDR
Up to 16 Meters
PC
AC Adapter
RS-232 Serial Port
COM1 - COM4
SUB-RS232K*
Channel 2
6' cable provided by
Honeywell (15 ft max.)
IDR
IDR
AC Adapter
Up to 16 Meters
AC Adapter
Channel 3
Up to 4000 Feet Total
~
~
Up to 26
SUBIDR-16’s
Up to 16 Meters
AC Adapter
NOTE: Meters must be installed within 500 feet of IDR.
Meter connected with a pair of #22-#14 AWG conductors.
Fig. 15. Hard-wiring the SUBIDR-16.
11
62-0342—01
SUB SERIES INTERVAL DATA RECORDERS
APPENDIX G - IDR TECHNICAL SPECIFICATIONS
Enclosure:
Lockable steel JIC box NEMA 12.
Dimensions:
9.5” H x 6.75” W x 3.875” D.
Knockouts:
Three (3) on bottom of enclosure (3/4” Cond.)
Power Supply:
Powered by meter or optional 120 VAC adapter.
Back Up:
Lithium Power Cell LTC-3PN (10 year lifetime)
LED Indicators:
Input pulse, CPU operation, alarm, power, communication
Inputs
SUBIDR-8:
Eight (8) eight-pin modular ports
or
Eight (8) 2-screw plug-in terminals
SUBIDR-16:
Sixteen (16) eight-pin modular ports
or
Sixteen (16) 2-screw plug-in terminals
or
Eight (8) eight-pin modular ports and eight (8) 2-screw plug-in terminals
Max Pulse Input:
<600 pulses per minute (50% duty cycle)
Data Storage:
12 days @ 5-minute sampling intervals
36 days @ 15-minute sampling intervals
Interface with:
Honeywell submeters, Electric utility meters, third-party submeters, gas meters, water meters, BTU meters and any meter
equipped with a contact pulse output (using available 2-screw terminals.)
Power Consumption:
2 watts maximum, 1.2 watts typical
Processor:
8-bit; 14 MHz main clock
Real-Time Clock:
100-year clock/calendar. Automatically makes changes to standard/daylight savings time.
Communications:
Serial, RS-485, 3-wire. Optically isolated from all other circuits. 9600 bps standard; provisions for 19200 or 2400 bps.
62-0342—01
12
SUB SERIES INTERVAL DATA RECORDERS
LIMITED WARRANTY
Subject to the exclusions listed below, Honeywell will either
repair or replace (at its option) any product that it
manufactures and which contains a defect in material or
workmanship.
accident or the negligence of any party; (iv) damaged as a
result of events beyond Honeywell’s control or other force
majeure events or (v) used in conjunction with equipment,
components, accessories, parts or materials not supplied or
approved by Honeywell.
The following exclusions apply:
7. This Limited Warranty is limited to the obligation to repair or
replace the manufactured product. This is the sole and
exclusive remedy for any breach of warranty. IN NO EVENT
SHALL HONEYWELL BE LIABLE FOR ANY INDIRECT,
INCIDENTAL, SPECIAL, CONSEQUENTIAL OR PUNITIVE
DAMAGES (INCLUDING ANY DAMAGE FOR LOST
PROFITS) ARISING OUT OF OR IN CONNECTION WITH
THE FURNISHING OF PRODUCTS, PARTS OR SERVICES,
OR THE PERFORMANCE, USE OF, OR INABILITY TO USE
ANY PRODUCTS, PARTS OR SERVICES, SALE OF OR
OTHERWISE, WHETHER BASED IN CONTRACT,
WARRANTY, TORT, INCLUDING WITHOUT LIMITATION,
NEGLIGENCE, OR ANY OTHER LEGAL OR EQUITABLE
THEORY.
1. This Limited Warranty is only effective for a period of (18)
eighteen months following the date of manufacture when
installed in accordance with manufacturer’s instructions by
qualified personnel.
2. Honeywell must be notified of the defect within ninety (90)
days after the defect becomes apparent or known.
3. Buyer’s remedies shall be limited to repair or replacement
of the product or component which failed to conform to
Honeywell’s express warranty set forth above.
4. Buyer shall be responsible for all freight costs and shall
bear all risk of loss or damage to returned goods while in
transit.
8. EXCEPT AS EXPRESSLY PROVIDED HEREIN,
HONEYWELL MAKES NO WARRANTY OF ANY KIND,
EXPRESS OR IMPLIED WITH RESPECT TO ANY
PRODUCTS, PARTS OR SERVICES PROVIDED BY
HONEYWELL INCLUDING, BUT NOT LIMITED TO, THE
IMPLIED WARRANTIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE. PRODUCTS OR
COMPONENTS DISTRIBUTED, BUT NOT
MANUFACTURED, BY HONEYWELL ARE NOT
WARRANTED BY HONEYWELL AND BUYER MUST
INSTEAD RELY ON THE REPRESENTATIONS AND
WARRANTIES, IF ANY, PROVIDED DIRECTLY TO THE
BUYER BY THE MANUFACTURER OF SUCH PRODUCT
OR COMPONENT.
5. This Limited Warranty does not cover installation, removal,
reinstallation, or labor costs, and excludes normal wear and
tear. Buyer shall provide labor for the removal of the defective
component or item and installation of its replacement at no
charge to Honeywell.
6. This Limited Warranty does not cover any product if: (i) a
product is altered or modified from its original manufactured
condition, (ii) any repairs, alterations or other work has been
performed by Buyer or others on such item, other than work
performed with Honeywell’s authorization and according to its
approved procedures; (iii) the alleged defect is a result of
abuse, misuse, improper maintenance, improper installation,
13
62-0342—01
SUB SERIES INTERVAL DATA RECORDERS
62-0342—01
14
SUB SERIES INTERVAL DATA RECORDERS
15
62-0342—01
SUB SERIES INTERVAL DATA RECORDERS
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
® U.S. Registered Trademark
© 2011 Honeywell International Inc.
62-0342—01 M.S. 02-11
Printed in U.S.A.
Toronto, Ontario M1V 4Z9
|