Honeywell SUB Series Interval Data Recorders 62 0342 01 User Manual

SUB Series Interval Data Recorders  
INSTALLATION MANUAL  
NOTE: IDRs with modular jacks can be powered from either  
PRE-INSTALLATION  
the first Honeywell meter or by an external power  
supply (requires 120 VAC). IDRs with removable  
screw-type connectors require an external power  
INFORMATION  
supply (provided).  
The SUB Series Interval Data Recorder (IDR) is an energy  
data collection device. Installation must be performed by  
qualified personnel only and must be in accordance with local  
and national electrical codes. Honeywell and its  
representatives are not responsible for damage or injury from  
improper installation.  
SUBIDR-16’s are supplied with an ID letter for each group of 8  
inputs to make them compatible with E-Mon Energy™  
software. The available choices are A-B, C-D, E-F, G-H, I-J, K-  
L, M-N, O-P, Q-R, S-T, U-V, W-X and Y-Z. No other combi-  
nations are available. When mixing 8-point and 16-point IDRs  
together, it may be necessary to jump a letter in the system.  
As an example, if you have an 8-point IDR labeled “A”, “B” and  
“C”, the 16-point IDR to choose would be the E-F unit.  
The IDR is contained within a NEMA 12 enclosure and is  
designed for INDOOR USE ONLY, where ambient  
temperatures are between +32 and +120 ºF. It is available in 8  
and 16 input configurations.  
The IDR is available in three configurations.  
The SUBIDR must be located in an area that is central to the  
meters connected to it.  
1. Modular Jacks (SUBIDR-8 and SUBIDR-16): Supplied  
with all modular jacks for use only with Honeywell  
meters.  
IMPORTANT:  
The meter that is connected to meter jack #1 on the  
IDR must be within 100 feet from the IDR, as it sup-  
plies low-voltage power to operate the IDR. All other  
meters can be located up to 500 feet from the IDR.  
NOTE: The IDR with modular jacks is designed to operate  
with Honeywell meters only. Terminal input models  
can support the monitoring of third-party metering  
equipment; contact Honeywell for further information.  
The IDR must be installed in a location according to these  
guidelines to ensure continued safe, trouble-free operation.  
Fig. 1. IDR board with modular jacks.  
2. Plug-In Screw-Type Connectors (SUBIDR-8 and  
SUBIDR-16): Supplied with all plug-in screw-type con-  
nectors for use with third-party meters (electric, gas,  
water, etc.) that are provided with a dry contact pulse  
output. (Requires external power supply.)  
Do not install near sensitive radio communication  
equipment or receiving antenna systems.  
Do not install near high-energy electrical fields such as  
those produced by welding equipment or by high-  
power electrical motors.  
Always install in an area that is dry, away from any  
potential liquid or chemical splash hazards. Never  
install electrical equipment in an area where flamma-  
ble chemicals or vapors are present.  
The IDR enclosure’s door must be kept closed once  
installed. Exposing the internal circuits to dust, dirt,  
fumes or high humidity can damage the IDR.  
NOTE: All internal circuits are isolated from the AC line.  
Fig. 2. IDR with screw-type connectors.  
62-0342-01  
SUB SERIES INTERVAL DATA RECORDERS  
removed. The third-party meter IDR uses a DIP switch to  
perform this function. This switch is preset at the factory and  
requires no further adjustment.  
D7 (Low Battery) -> This LED must be OFF. This  
LED indicates a low or missing battery.  
D6 (System Error) -> This LED must be OFF.  
3. Meter pulse indicators  
Yellow LEDs P1 through P8 may be flashing.  
These LEDs indicate each meter’s pulse rate.  
The flash rate depends on how much load the  
meter is measuring. The faster the pulse the  
greater the load.  
IMPORTANT:  
IF THE METER MEASURES ZERO LOAD, THERE  
IS NO METER PULSE, WHEN THE PULSE RATE  
IS ZERO THE YELLOW LED INDICATOR WILL  
REMAIN EITHER ON OR OFF UNTIL THERE IS A  
LOAD.  
NOTE: If one of the LEDs does not flash, verify the meter  
connection first. If the meter is properly connected,  
check the meter’s display for a flashing load indica-  
tor.  
4. Panel Indicators  
Two LEDs are visible through the window on the  
door of the stand-alone enclosure. THESE LEDS  
ARE NOT PRESENT IN MMU STYLE IDRS.  
Green LED (Power Indicator) -> The green LED  
indicates that power is present at the IDR.  
Red LED (Tamper Alarm) -> The red LED indi-  
cates that the IDR door has been opened. This  
tamper alarm LED will be on when the door is  
closed, and will flash when the door is open.  
When the software startup is performed, the IDR  
will be initialized by the E-Mon Energy software  
and the alarm LED will turn off as long as the door  
remains closed. The alarm can only be reset  
through the software.  
Fig. 5. Overview of main circuit board.  
MAIN CIRCUIT BOARD VISUAL  
CHECKS  
5. IDR 16 Option 16 Card (applies only to the SUBIDR-16  
Once you have connected meter #1 to jack #1 in the IDR, the  
IDR should be energized. If the IDR is not energized, verify:  
model.)  
For each meter (9-16) installed on the options  
card, another set of yellow LEDs (P9-P16) will be  
present. These LEDs indicate the meter pulse  
rate for meters #9 through #16.  
1. Meter #1 is turned on. (Meter #1 powers the IDR; if  
Meter #1 is not installed and powered up, the IDR will  
not function.)  
2. Verify that JMP8 on the IDR circuit board has a jumper  
installed.  
3. Verify that J23 & J24 on the IDR circuit board are set in  
the position labeled “MTR”. Both jumpers should be set  
to the RIGHT position.  
4. Verify that the cable between Meter #1 and Jack #1 on  
the IDR is properly assembled. (See Appendix A for  
cable assembly.)  
OPTIONAL AC ADAPTER  
(OPTIONAL EXTERNAL 120 VAC  
POWER SUPPLY)  
If you are NOT using the optional AC adapter to power the  
IDR, proceed to Section 6.0.  
NOTE: If the IDR is being powered by the optional AC  
adapter instead of by Meter #1, see Section 5.0.  
Instead of powering the IDR using Meter #1, Honeywell can  
supply an optional AC adapter. If the IDR was provided with  
this option, verify the following:  
Verify the status of the LED indicators on the IDR circuit  
board. (See Appendix B for locations.)  
1. Jumpers J23 & J24 on the IDR circuit board are set to  
the LEFT position (position labeled “EXT”.)  
2. Jumper at JMP8 MUST be removed.  
3. The AC adapter’s two-wire cord must be plugged into  
the IDR at TB9. (The polarity of these wires does not  
matter.)  
1. Power Supply Indicators  
L3, green -> This LED is ON.  
L1, green -> This LED is ON.  
2. System status indicators  
D4 (CPU), red -> This LED flashes once per sec-  
ond. If D4 flashes twice per second, the IDR is not  
initialized. This will be addressed later using E-  
Mon Energy software.  
4. Plug the AC adapter into a 120 VAC outlet.  
3
62-0342—01  
SUB SERIES INTERVAL DATA RECORDERS  
IMPORTANT:  
METHOD 1: MODULAR PLUG METHOD  
The AC adapter is designed to be used with a 120  
VAC outlet only.  
This method requires using 4 stranded conductors inside a  
cable that is fitted with an RJ-11 type plug for 4-conductor  
modular systems at each end of the cable.  
5. The IDR should now be energized. Perform the visual  
* Do not use any pre-made telephone cables. See Appendix A  
for correct cable configuration.  
checks outlined in section 4.  
NOTE: The AC adapter provides an isolated 18 VAC/300  
mA power source for the IDR.  
1. Plug the 4-wire RJ-11 cable/plug assembly into Channel  
A on the SUB-RS232K. Connect the other end of this  
cable to the IDR at either of the two RS-485 ports at the  
top left of the IDR circuit board.  
2. The unused RS-485 port is used to connect another  
cable to the next IDR. This is called a “daisy-chain” con-  
nection. This can be done repeatedly to connect as  
many as 52 individual IDRs.  
SERIAL COMMUNICATIONS  
Hardwired System using the SUB-RS232K  
Communication Key.  
(See the hardwired system configuration diagrams in  
Appendix F.)  
NOTE: The total combined cable length must be no more  
than 4,000 feet.  
The SUB-RS232K communications key allows you to connect  
IDRs to a personal computer that has E-Mon Energy software  
installed. The computer communicates with the IDRs through  
the SUB-RS232K.  
3. Each IDR has two LEDs (yellow and green) located  
directly below the RS-485 jacks. If the system is prop-  
erly wired, these two LEDs will normally be OFF. These  
LEDs will flash when the computer and IDR are commu-  
nicating.  
The SUB-RS232K must be located within 15 feet of the host  
computer.  
METHOD 2: TERMINAL BLOCK METHOD  
IDRs may also be daisy-chained using a 3-conductor cable.  
Instead of using the two modular jacks for the RS-485 daisy  
chain, you can use J20 at the bottom right corner of the IDR  
circuit board.  
Connecting the SUB-RS232K to the  
computer  
The SUB-RS232K is supplied with:  
Remove this 3-terminal plug to facilitate attaching the wires  
using the screw terminals that are captivated within the plug  
housing.  
(1) 8-conductor cable fitted with RJ-45 plugs  
(1) DB-9 serial COM port adapter  
(1) AC adapter that converts 120 VAC into the 7 VAC  
used to power the SUB-RS232K.  
1. 1. Daisy-chain the IDRs by connecting:  
1. Connect the 8-conductor cable to the left-side jack  
(labeled “RS232”) on the rear panel of the SUB-  
RS232K.  
All HI terminals together  
All LO terminals together  
All GND terminals together  
2. Connect the appropriate COM port adapter (DB-9) to  
the serial port on the back of the computer. Plug the 8-  
conductor cable from the SUB-RS232K into the COM  
port adapter.  
3. Connect the 7 VAC AC adapter into the rear panel input  
on the SUB-RS232K. Plug the adapter into a 120 VAC  
outlet. On the front panel of the SUB-RS232K, two  
LEDs will light up (POWER ON and AC ON.)  
** This requires putting two wires into each of the 3 terminals.  
2. Connecting to the SUB-RS232K.  
You will need to attach an RJ-11 modular plug to the cable that  
serves the RS-485 system.  
On each channel on the back of the SUB-RS232K, the pin out  
for each channel is as follows:  
NOTE: When E-Mon Energy software is accessed on the  
computer, a third LED will turn on. The SUB-RS232K  
READY indicator will light up as soon as the E-Mon  
Energy software is booted up and the correct COM  
port is set up via the settings provided in the soft-  
ware’s Locations menu.  
Fig. 6. SUB-RS232K modular jack pin out.  
Connecting IDRs to the SUB-RS232K using  
RS-485  
PIN1 - Not used  
PIN2 - GND  
PIN3 - HI  
On the rear panel of the SUB-RS232K, there are three jacks  
labeled as channels A, B and C. These are RS-485 serial  
communications ports used to connect the IDRs. Each of  
these three channels can be connected to as many as 52  
individual IDRs over a total cable distance of 4000 feet.  
Channels are independent and must not be connected to  
each other. (See Appendix F.)  
PIN4 - LO  
NOTE: It is okay to use the J20 with the modular jacks if  
needed.  
This completes the installation of the IDR hardwired system.  
62-0342—01  
4
SUB SERIES INTERVAL DATA RECORDERS  
Using the USB connection on your  
computer  
As an alternative to the SUB-RS232K converter, we offer the  
SUB-USBK that allows you to convert the RS485 output from  
your IDRs for direct connect to your USB connection on your  
computer.  
APPENDIX A - CABLE  
CONFIGURATION  
A. Four-Conductor Cables (IDR RS-485 Communication)  
Baud Rate Selection  
The communication baud rate is selected by means of a  
jumper on the circuit board (See appendix C for location.)  
There are three (3) selections: 19200, 9600 (factory default)  
and 2400.  
1. When using the IDR with a modem, the rate of 9600  
should always be selected.  
2. The baud rate on the IDR must always match the baud  
rate selected in the E-Mon Energy software. Communi-  
cation will not work if they are not set correctly.  
3. After a baud rate change, press CPU Reset (See  
Appendix C) to register the change in the IDR.  
4. All IDRs in the “daisy chain” circuit must be set at the  
same baud rate.  
Fig. 7. connectors.  
B. Six-Conductor Cables (Meters #2-#8, optional #9-#16)  
Fig. 8. connectors.  
C. Eight-Conductor Cables (Meter #1, RS-232 Key to  
Computer)  
Fig. 9. connectors.  
NOTE: All cables are wired pin-to-pin (straight through) as  
shown above.  
5
62-0342—01  
SUB SERIES INTERVAL DATA RECORDERS  
APPENDIX B - LED INDICATORS  
D7-Clear Red LED  
Low Battery  
MUST be "OFF"  
(Indicates low battery  
when lit)  
L1-Green LED  
Serial Communications  
Power Supply  
Always "ON"  
(Indicates power supply  
is okay if LED is ON)  
D4-Red LED  
CPU Status  
Flashes once per  
second  
D6-Clear Red LED  
System Error  
Always "OFF" when  
system is operating  
normally  
D1-Green LED  
D2-Yellow LED  
See "Serial  
Communications"  
L3-Green LED  
Main Power Indicator  
Always "ON"  
P1-P8-Yellow LED  
Meter Pulse Indicators  
(Indicates input pulses  
being received from  
meters)  
Fig. 10. LED indicators.  
62-0342—01  
6
SUB SERIES INTERVAL DATA RECORDERS  
APPENDIX C - IDR CIRCUIT BOARD COMPONENTS  
Battery  
J3-J4-RS-485 Communications Jacks  
See "Serial Communications"  
(Ports used to connect one IDR  
to another IDR or Key)  
CPU Reset Button  
Baud Rate Selection  
See "Serial  
Communications"  
(Selects communication  
baud rate ALWAYS set at  
9600 BPS when modem  
is present)  
Baud Rate Selection  
See Chapter 6  
d"Communications"  
M1-M8-Meter Inputs  
(Ports used to connect  
meters to IDR)  
JMP-8-Meter Power Selection  
See “Main Circuit Board  
Visual Checks” and “Optional  
AC Adapter”  
(Selects external power, or  
powered from Meter #1)  
J20-RS485  
Communications  
See "Serial Communications"  
TB9-External Power Input  
See “Optional  
AC Adapter”  
(Connects external  
power supply adapter)  
J23 & J24-Input Power  
Selection  
See “Main Circuit  
Board Visual Checks” and  
“Optional AC Adapter”  
Fig. 11. IDR circuit board components.  
7
62-0342—01  
SUB SERIES INTERVAL DATA RECORDERS  
APPENDIX D - SYSTEM WIRING GUIDES  
Wiring Guide for SUBIDR-8  
DB-9 (DTE) Connector  
RJ-45  
SUB-RS232K  
PC  
RJ-11  
6' cable provided by  
Honeywell (15 ft max.)  
8-conductor cable  
& modular plug  
AC Adapter  
4-Conductor  
Flat Modular Cable  
Up to 4000 Feet Total  
Daisy-Chain or  
Star Connection  
Channel 1 of 3  
(One of three channels shown for clarity.)  
(Up to 8 Meters)  
IDR A  
6-Cond.  
RJ-45  
8-Cond.  
RJ-45  
6-Cond.  
RJ-45  
RJ-11  
(Up to 8 Meters)  
Up to 52 SUBIDR-8s per channel  
IDR Z  
~
~
Note: Meter 1 must be installed within  
100 feet of IDR. Meters 2-8 must be installed  
within 500 feet of IDR.  
CONNECTION  
CABLE TYPE  
CONNECTOR  
SUBIDR to Honeywell Meter #1  
8-cond. 22-26 AWG  
flat modular cable  
RJ-45  
SUBIDR to Honeywell Meters #2-8  
6-cond. 22-26 AWG  
(Pins 1 & 8 not used)  
RJ-45  
SUBIDR to SUBIDR  
4-cond. 26 AWG  
4-cond. 26 AWG  
RJ-11  
SUBIDR to SUB-RS232K  
SUB-RS232K to Computer *  
RJ-11  
8-cond. 22-26 AWG  
flat modular cable  
RJ-45/DTE  
SUB-RS232K to Modem *  
SUBIDR to SUB-USBK *  
8-cond. 22-26 AWG  
flat modular cable  
RJ-45  
Allows connection directly  
to the computer USB  
SUBIDR to Pulse Meter  
* Supplied by Honeywell  
2-cond. 14-22 AWG  
Note: When constructing field-installed cables, modular cables must be made  
so that the individual wires go through on the same pin number.  
Fig. 12. Wiring overview for SUBIDR-8.  
62-0342—01  
8
SUB SERIES INTERVAL DATA RECORDERS  
Wiring Guide for SUBIDR-16  
DB-9 (DTE) Connector  
RJ-45  
SUB-RS232K  
PC  
RJ-11  
6' cable provided by  
Honeywell (15 ft max.)  
8-conductor cable  
& modular plug  
AC Adapter  
4-Conductor  
Flat Modular Cable  
Up to 4000 Feet Total  
Daisy-Chain or  
Star Connection  
Channel 1 of 3  
(One of three channels shown for clarity.)  
IDR A-B  
(Up to 16 Meters)  
6-Cond.  
RJ-45  
8-Cond.  
RJ-45  
6-Cond.  
RJ-45  
RJ-11  
(Up to 16 Meters)  
IDRY-Z  
Up to 26 SUBIDR-16s per channel  
(3 channels per SUB-RS232K)  
~
~
3rd  
Party  
Meter  
3rd  
Party  
Meter  
3rd  
Party  
Meter  
Pair of wires  
(#22-#14 AWG)  
Note: Meter 1 must be installed within  
100 feet of IDR. Meters 2-8 must be installed  
within 500 feet of IDR.  
CONNECTION  
CABLE TYPE  
CONNECTOR  
SUBIDR to Honeywell Meter #1  
8-cond. 22-26 AWG  
flat modular cable  
RJ-45  
SUBIDR to Honeywell Meters #2-16 6-cond. 22-26 AWG  
RJ-45  
(Pins 1 & 8 not used)  
SUBIDR to SUBIDR  
4-cond. 26 AWG  
4-cond. 26 AWG  
RJ-11  
IDR to RS-232 Key 2000  
SUB-RS232K to Computer *  
RJ-11  
8-cond. 22-26 AWG  
flat modular cable  
RJ-45/DTE  
SUB-RS232K to Modem *  
SUBIDR to SUB-USBK *  
8-cond. 22-26 AWG  
flat modular cable  
RJ-45  
Allows connection directly  
to the computer USB  
SUBIDR to Pulse Meter  
* Supplied by Honeywell  
2-cond. 14-22 AWG  
Note: When constructing field-installed cables, modular cables must be made  
so that the individual wires go through on the same pin number.  
Fig. 13. Wiring overview for SUBIDR-16.  
9
62-0342—01  
SUB SERIES INTERVAL DATA RECORDERS  
APPENDIX E - HARDWIRED SYSTEM CONFIGURATION DIAGRAMS  
SUBIDR-8, Using Honeywell Meters:  
IDR  
Up to 8 Meters  
Up to 4000 Feet Total  
~
~
Up to 52  
SUBIDR-8’s  
Channel 1  
IDR  
Up to 8 Meters  
PC  
RS-232 Serial Port  
COM1 - COM4  
15’ max  
SUB-RS232K*  
Channel 2  
IDR  
IDR  
AC Adapter  
Up to 8 Meters  
Channel 3  
Up to 4000 Feet Total  
~
~
Up to 52  
SUBIDR-8’s  
Up to 8 Meters  
NOTE: Meter #1 must be installed within 100 feet of IDR.  
Meters #2-16 must be installed within 500 feet of IDR.  
Meter #1 uses 8-conductor cable.  
Meters #2-16 use 6-conductor cable.  
Fig. 14. Hard-wiring the SUBIDR-8.  
62-0342—01  
10  
SUB SERIES INTERVAL DATA RECORDERS  
SUBIDR-16, Using HoneywellMeters  
IDR  
IDR  
Up to 16 Meters  
Up to 4000 Feet Total  
~
~
Up to 26  
Channel 1  
SUBIDR-16’s  
Up to 16 Meters  
PC  
RS-232 Serial Port  
COM1 - COM4  
Channel 2  
SUB-RS232K*  
6' cable provided by  
Honeywell (15 ft max.)  
IDR  
IDR  
AC Adapter  
Up to 16 Meters  
Channel 3  
Up to 4000 Feet Total  
~
~
Up to 26  
SUBIDR-16’s  
Up to 16 Meters  
NOTE: Meter #1 must be installed within 100 feet of IDR.  
Meters #2-#16 must be installed within 500 feet of IDR.  
Meter #1 uses 8-conductor cable.  
Meters #2-16 use 6-conductor cable.  
SUBIDR-16, Using Other Utility-Type Meters  
(Gas, Water, Etc.)  
IDR  
Up to 16 Meters  
AC Adapter  
Up to 4000 Feet Total  
~
~
Up to 26  
SUBIDR-16’s  
Channel 1  
IDR  
Up to 16 Meters  
PC  
AC Adapter  
RS-232 Serial Port  
COM1 - COM4  
SUB-RS232K*  
Channel 2  
6' cable provided by  
Honeywell (15 ft max.)  
IDR  
IDR  
AC Adapter  
Up to 16 Meters  
AC Adapter  
Channel 3  
Up to 4000 Feet Total  
~
~
Up to 26  
SUBIDR-16’s  
Up to 16 Meters  
AC Adapter  
NOTE: Meters must be installed within 500 feet of IDR.  
Meter connected with a pair of #22-#14 AWG conductors.  
Fig. 15. Hard-wiring the SUBIDR-16.  
11  
62-0342—01  
SUB SERIES INTERVAL DATA RECORDERS  
APPENDIX G - IDR TECHNICAL SPECIFICATIONS  
Enclosure:  
Lockable steel JIC box NEMA 12.  
Dimensions:  
9.5” H x 6.75” W x 3.875” D.  
Knockouts:  
Three (3) on bottom of enclosure (3/4” Cond.)  
Power Supply:  
Powered by meter or optional 120 VAC adapter.  
Back Up:  
Lithium Power Cell LTC-3PN (10 year lifetime)  
LED Indicators:  
Input pulse, CPU operation, alarm, power, communication  
Inputs  
SUBIDR-8:  
Eight (8) eight-pin modular ports  
or  
Eight (8) 2-screw plug-in terminals  
SUBIDR-16:  
Sixteen (16) eight-pin modular ports  
or  
Sixteen (16) 2-screw plug-in terminals  
or  
Eight (8) eight-pin modular ports and eight (8) 2-screw plug-in terminals  
Max Pulse Input:  
<600 pulses per minute (50% duty cycle)  
Data Storage:  
12 days @ 5-minute sampling intervals  
36 days @ 15-minute sampling intervals  
Interface with:  
Honeywell submeters, Electric utility meters, third-party submeters, gas meters, water meters, BTU meters and any meter  
equipped with a contact pulse output (using available 2-screw terminals.)  
Power Consumption:  
2 watts maximum, 1.2 watts typical  
Processor:  
8-bit; 14 MHz main clock  
Real-Time Clock:  
100-year clock/calendar. Automatically makes changes to standard/daylight savings time.  
Communications:  
Serial, RS-485, 3-wire. Optically isolated from all other circuits. 9600 bps standard; provisions for 19200 or 2400 bps.  
62-0342—01  
12  
SUB SERIES INTERVAL DATA RECORDERS  
LIMITED WARRANTY  
Subject to the exclusions listed below, Honeywell will either  
repair or replace (at its option) any product that it  
manufactures and which contains a defect in material or  
workmanship.  
accident or the negligence of any party; (iv) damaged as a  
result of events beyond Honeywell’s control or other force  
majeure events or (v) used in conjunction with equipment,  
components, accessories, parts or materials not supplied or  
approved by Honeywell.  
The following exclusions apply:  
7. This Limited Warranty is limited to the obligation to repair or  
replace the manufactured product. This is the sole and  
exclusive remedy for any breach of warranty. IN NO EVENT  
SHALL HONEYWELL BE LIABLE FOR ANY INDIRECT,  
INCIDENTAL, SPECIAL, CONSEQUENTIAL OR PUNITIVE  
DAMAGES (INCLUDING ANY DAMAGE FOR LOST  
PROFITS) ARISING OUT OF OR IN CONNECTION WITH  
THE FURNISHING OF PRODUCTS, PARTS OR SERVICES,  
OR THE PERFORMANCE, USE OF, OR INABILITY TO USE  
ANY PRODUCTS, PARTS OR SERVICES, SALE OF OR  
OTHERWISE, WHETHER BASED IN CONTRACT,  
WARRANTY, TORT, INCLUDING WITHOUT LIMITATION,  
NEGLIGENCE, OR ANY OTHER LEGAL OR EQUITABLE  
THEORY.  
1. This Limited Warranty is only effective for a period of (18)  
eighteen months following the date of manufacture when  
installed in accordance with manufacturer’s instructions by  
qualified personnel.  
2. Honeywell must be notified of the defect within ninety (90)  
days after the defect becomes apparent or known.  
3. Buyer’s remedies shall be limited to repair or replacement  
of the product or component which failed to conform to  
Honeywell’s express warranty set forth above.  
4. Buyer shall be responsible for all freight costs and shall  
bear all risk of loss or damage to returned goods while in  
transit.  
8. EXCEPT AS EXPRESSLY PROVIDED HEREIN,  
HONEYWELL MAKES NO WARRANTY OF ANY KIND,  
EXPRESS OR IMPLIED WITH RESPECT TO ANY  
PRODUCTS, PARTS OR SERVICES PROVIDED BY  
HONEYWELL INCLUDING, BUT NOT LIMITED TO, THE  
IMPLIED WARRANTIES OF MERCHANTABILITY AND  
FITNESS FOR A PARTICULAR PURPOSE. PRODUCTS OR  
COMPONENTS DISTRIBUTED, BUT NOT  
MANUFACTURED, BY HONEYWELL ARE NOT  
WARRANTED BY HONEYWELL AND BUYER MUST  
INSTEAD RELY ON THE REPRESENTATIONS AND  
WARRANTIES, IF ANY, PROVIDED DIRECTLY TO THE  
BUYER BY THE MANUFACTURER OF SUCH PRODUCT  
OR COMPONENT.  
5. This Limited Warranty does not cover installation, removal,  
reinstallation, or labor costs, and excludes normal wear and  
tear. Buyer shall provide labor for the removal of the defective  
component or item and installation of its replacement at no  
charge to Honeywell.  
6. This Limited Warranty does not cover any product if: (i) a  
product is altered or modified from its original manufactured  
condition, (ii) any repairs, alterations or other work has been  
performed by Buyer or others on such item, other than work  
performed with Honeywell’s authorization and according to its  
approved procedures; (iii) the alleged defect is a result of  
abuse, misuse, improper maintenance, improper installation,  
13  
62-0342—01  
SUB SERIES INTERVAL DATA RECORDERS  
62-0342—01  
14  
SUB SERIES INTERVAL DATA RECORDERS  
15  
62-0342—01  
SUB SERIES INTERVAL DATA RECORDERS  
Automation and Control Solutions  
Honeywell International Inc.  
1985 Douglas Drive North  
Golden Valley, MN 55422  
Honeywell Limited-Honeywell Limitée  
35 Dynamic Drive  
® U.S. Registered Trademark  
© 2011 Honeywell International Inc.  
62-0342—01 M.S. 02-11  
Printed in U.S.A.  
Toronto, Ontario M1V 4Z9  

Bolens 19200 User Manual
Brother FAX 2940 User Manual
Brother MFC 590 User Manual
Casio DT 800RF User Manual
Cypress CY8C24x23A User Manual
Friedrich MR18Y3F User Manual
GE AJES10DCC User Manual
Havis Shields 1996 2008 Crown Victoria Driver and Passenger Trunk Side Mounts C TSM CV P User Manual
Heat Controller Inc Air Conditioner RADS 253A User Manual
Humminbird UC 7SB User Manual