Heat Controller Inc Air Conditioner HTS SERIES SPLIT SYSTEM User Manual

Split Products  
Table of Contents  
Model Nomenclature  
3
Safety  
4
Storage  
5
Pre-Installation  
5
Equipment Selection  
Air Coil Match-ups  
6
6-7  
8
Air Handler Selection  
Installation  
9
Water Connections  
10-11  
11-13  
14-15  
16  
Ground Loop Applications  
Open Loop - Ground Water Systems  
Water Quality Standards  
Refrigeration Installation  
Lineset Information  
17-22  
17  
Internal Hot Water Generator  
Hot Water Generator Module  
Electrical - Line Voltage  
Power Wiring  
23-24  
25-26  
27-28  
28  
Electrical - Low Voltage Wiring  
Low Water Temperature Cutout Selection  
Water Valve Wiring  
29-31  
31  
31  
HSS Series Split System,  
11/2 to 5 Tons  
Thermostat Wiring  
31  
CXM Controls  
32-34  
33  
CXM Safety Features  
Unit Start-Up and Operating Conditions  
HTS Series Split System,  
Two Stage, 2-5 Tons  
36  
Unit Start-Up  
and System Checkout Procedure  
37-38  
39-41  
42  
Unit Operating Conditions  
Preventive Maintenance  
Troubleshooting  
Outdoor Split  
43-44  
45-46  
47  
Geothermal Heat Pumps  
Functional & Performance Troubleshooting  
Refrigerant Circuit Diagram  
Revision Log  
48  
Installation, Operation &  
Maintenance Instructions  
Revision: 23 June, 2008  
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Model Nomenclature: for Indoor Split Series  
4
5
6
7
Model Nomenclature: for Indoor Split Series  
NOTE: Above model nomenclature is a general reference. Consult individual specification catalogs for detailed information.  
3
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Safety  
Safety  
x WARNING! x  
Warnings, cautions and notices appear throughout this  
manual. Read these items carefully before attempting any  
installation, service or troubleshooting of the equipment.  
WARNING! All refrigerant discharged from this unit must be  
recovered WITHOUT EXCEPTION. Technicians must follow  
industry accepted guidelines and all local, state, and federal  
statutes for the recovery and disposal of refrigerants. If a  
compressor is removed from this unit, refrigerant circuit oil will  
remain in the compressor. To avoid leakage of compressor oil,  
refrigerant lines of the compressor must be sealed after it is  
removed.  
DANGER: Indicates an immediate hazardous situation, which  
if not avoided will result in death or serious injury. DANGER  
labels on unit access panels must be observed.  
WARNING: Indicates a potentially hazardous situation, which  
if not avoided could result in death or serious injury.  
CAUTION: Indicates a potentially hazardous situation or an  
unsafe practice, which if not avoided could result in minor or  
moderate injury or product or property damage.  
x CAUTION! x  
CAUTION! To avoid equipment damage, DO NOT use  
these units as a source of heating or cooling during the  
construction process. The mechanical components and  
filters will quickly become clogged with construction dirt and  
debris, which may cause system damage.  
NOTICE: Notification of installation, operation or  
maintenance information, which is important, but which is not  
hazard-related.  
x WARNING! x  
WARNING! Verify refrigerant type before proceeding.  
Units are shipped with R-22 and R-410A refrigerants. The  
unit label will indicate which refrigerant is provided. The  
EarthPure® Application and Service Manual should be read  
and understood before attempting to service refrigerant  
circuits with R-410A.  
x WARNING! x  
WARNING! To avoid the release of refrigerant into the  
atmosphere, the refrigerant circuit of this unit must be  
serviced only by technicians who meet local, state, and  
federal proficiency requirements.  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
4
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
General Information  
Inspection  
rides freely on the springs. Remove shipping restraints.  
6. REMOVE COMPRESSOR SUPPORT PLATE 1/4”  
SHIPPING BOLTS (2 on each side) TO MAXIMIZE  
VIBRATION AND SOUND ATTENUATION (R22 indoor  
units only).  
Upon receipt of the equipment, carefully check the shipment  
against the bill of lading. Make sure all units have been  
received. Inspect the packaging of each unit, and inspect each  
unit for damage. Insure that the carrier makes proper notation  
of any shortages or damage on all copies of the freight bill  
and completes a common carrier inspection report. Concealed  
damage not discovered during unloading must be reported  
to the carrier within 15 days of receipt of shipment. If not filed  
within 15 days, the freight company can deny the claim without  
recourse. Note: It is the responsibility of the purchaser to file  
all necessary claims with the carrier. Notify your equipment  
supplier of all damage within fifteen (15) days of shipment.  
7. Locate and verify any hot water generator (HWG) or  
other accessory kit located in the compressor section.  
x CAUTION! x  
CAUTION! DO NOT store or install units in corrosive  
environments or in locations subject to temperature or  
humidity extremes (e.g., attics, garages, rooftops, etc.).  
Corrosive conditions and high temperature or humidity can  
significantly reduce performance, reliability, and service life.  
Always move and store units in an upright position. Tilting  
units on their sides may cause equipment damage.  
Storage  
Equipment should be stored in its original packaging in a  
clean, dry area. Store units in an upright position at all times.  
Stack units a maximum of 3 units high.  
Unit Protection  
Cover units on the job site with either the original packaging  
or an equivalent protective covering. Cap the open ends of  
pipes stored on the job site. In areas where painting, plastering,  
and/or spraying has not been completed, all due precautions  
must be taken to avoid physical damage to the units and  
contamination by foreign material. Physical damage and  
contamination may prevent proper start-up and may result in  
costly equipment clean-up.  
NOTICE! Failure to remove shipping brackets from spring-  
mounted compressors will cause excessive noise, and could  
cause component failure due to added vibration.  
x CAUTION! x  
CAUTION! CUT HAZARD - Failure to follow this caution  
may result in personal injury. Sheet metal parts may have  
sharp edges or burrs. Use care and wear appropriate  
protective clothing, safety glasses and gloves when  
handling parts and servicing heat pumps.  
Examine all pipes, fittings, and valves before installing any of  
the system components. Remove any dirt or debris found in  
or on these components.  
Pre-Installation  
Installation, Operation, and Maintenance instructions are  
provided with each unit. Horizontal equipment is designed for  
installation above false ceiling or in a ceiling plenum. Other  
unit configurations are typically installed in a mechanical  
room. The installation site chosen should include adequate  
service clearance around the unit. Before unit start-up,  
read all manuals and become familiar with the unit and its  
operation. Thoroughly check the system before operation.  
Prepare units for installation as follows:  
1. Compare the electrical data on the unit nameplate with  
ordering and shipping information to verify that the  
correct unit has been shipped.  
2. Keep the cabinet covered with the original packaging  
until installation is complete and all plastering, painting,  
etc. is finished.  
3. Verify refrigerant tubing is free of kinks or dents and that  
it does not touch other unit components.  
4. Inspect all electrical connections. Connections must be  
clean and tight at the terminals.  
5. Loosen compressor bolts on units equipped with  
compressor spring vibration isolation until the compressor  
5
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Equipment Selection  
The installation of geothermal heat pump units and all  
associated components, parts, and accessories which make  
up the installation shall be in accordance with the regulations  
of ALL authorities having jurisdiction and MUST conform to  
all applicable codes. It is the responsibility of the installing  
contractor to determine and comply with ALL applicable  
codes and regulations.  
Indoor Coil Selection - HTS GeoMax 2  
HCI split system heat pumps are rated in the ARI directory  
with a specific indoor coil match. GeoMax 2 (HTS) models  
are rated with Carrier/Bryant FV4 or FE4 series variable  
speed air handlers as shown in Table 1a. Other brands of  
air handlers may attain the same ARI ratings providing that  
the specifications meet or exceed those listed in Table 1a  
AND Table 1b. An ECM motor and TXV is required. Cap  
tubes and fixed orifices are not acceptable. PSC fans may  
be used if matched to Table 1b, but will not meet ARI ratings.  
If using PSC fan, compressor section must be operated as a  
single stage unit (i.e. wired for either 1st stage or 2nd stage).  
Without the ability to vary the airflow, supply air temperatures  
may not be acceptable if the compressor is allowed to  
change stages when used with a PSC fan motor.  
General  
Proper indoor coil selection is critical to system efficiency.  
Using an older-model coil can affect efficiency and may not  
provide the customer with rated or advertised EER and COP.  
Coil design and technology have dramatically improved  
operating efficiency and capacity in the past 20 years.  
Homeowners using an older coil are not reaping these cost  
savings and comfort benefits. NEVER MATCH AN R-22  
INDOOR COIL WITH AN R-410A COMPRESSOR SECTION.  
Newer indoor coils have a larger surface area, enhanced fin  
design, and grooved tubing. These features provide a larger  
area for heat transfer, improving efficiency and expanding  
capacity. Typical older coils may only have one-third to one-  
half the face area of these redesigned coils.  
Table 1a: GeoMax 2 (HTS) Air Handler Matches for ARI Ratings  
Compressor Section  
024  
003  
036  
005  
048  
006  
060  
006  
Air Handler  
Model FV4  
Refrigerant  
R-410A  
Metering Device  
TXV (required)  
Air Coil  
Type  
Rows - Fins/in.  
Face Area (sq. ft.)  
Slope  
3 - 14.5  
3.46  
A
A
A
3 - 14.5  
5.93  
3 - 14.5  
7.42  
3 - 14.5  
7.42  
Cabinet Configuration  
Upflow/Downflow/Horizontal (Multipoise)  
AC/HP size: 036  
AC/HP size: 036  
System Type:  
HP-Effic AC/HP  
CFM Adjust: High  
AC/HP size: 048  
AC/HP size: 060  
System Type:  
Comfort AC/HP  
CFM Adjust: High  
ECM Settings for  
ARI Ratings  
(FV4 Fan Coil)  
System Type:  
Comfort AC/HP  
CFM Adjust: Nom  
System Type:  
Comfort AC/HP  
CFM Adjust: High  
Fan Motor Type - HP  
ECM - 1/2  
ECM - 1/2  
ECM - 3/4  
ECM - 3/4  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
6
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Equipment Selection  
Table 1b: GeoMax 2 (H  
T
S) Air Handler Characteristics for Brands other than Above Models  
Nominal  
Tons*  
Evaporator  
Temp (ºF)  
Capacity  
(MBtuh)**  
Model*  
CFM  
024 - Part Load  
024 - Full Load  
036 - Part Load  
036 - Full Load  
048 - Part Load  
048 - Full Load  
060 - Full Load  
1.5  
2.0  
2.5  
3.0  
3.5  
4.0  
5.0  
50  
52  
51  
50  
47  
48  
48  
530  
880  
19.2 - 22.4  
24.2 - 28.2  
25.2 - 29.2  
34.5 - 40.1  
34.3 - 39.9  
46.3 - 53.8  
54.5 - 63.3  
700  
1200  
1000  
1650  
1850  
* Nominal tons are at ARI/ISO 13256-1 GLHP conditions. Two-stage units may be operated in single-stage mode if desired, where smaller  
capacity is required. For example, a model 026 may be used as a 1-1/2 ton unit if “locked” into 1st stage operation only. If PSC fan is used,  
unit must be “locked” into either 1st or 2nd stage. An ECM fan is required for two-stage operation and for ARI ratings. Size air handler for  
“Full Load” if operating in two-stage mode.  
**When selecting an air handler based upon the above conditions, choose entering WB temperature of 67ºF. Use evaporator temperature,  
CFM and capacity requirements as listed above. The air handler capacity must be at least at the minimum capacity shown in the table in  
order for the ARI rating condition to be valid. See Figure 1 for an example selection.  
Indoor Coil Selection - For HSS R-22 Units  
Geothermal split system heat pumps with R-22 refrigerant are rated in the ARI directory with a “generic” indoor coil match and  
PSC fan. Selection of air handlers that attain the published ARI ratings must meet or exceed the specifications listed in Table  
2. A TXV is required. Cap tubes and fixed orifices are not  
acceptable.  
Table 2: R-22 Air Handler Characteristics  
Nominal  
Tons*  
Evaporator  
Temp (ºF)  
Capacity  
(MBtuh)**  
Model*  
CFM  
018  
024  
030  
036  
042  
048  
060  
1.5  
2.0  
2.5  
3.0  
3.5  
4.0  
5.0  
50  
47  
49  
48  
45  
46  
45  
600  
800  
18.5 - 21.3  
25.5 - 29.3  
31.5 - 36.2  
37.0 - 42.5  
42.2 - 48.5  
50.0 - 57.5  
58.0 - 66.7  
1000  
1200  
1400  
1600  
2000  
* Nominal tons are at ARI/ISO 13256-1 GLHP conditions.  
**When selecting an air handler based upon the above conditions, choose entering WB temperature of 67ºF. Use evaporator temperature,  
CFM and capacity requirements as listed above. The air handler capacity must be at least at the minimum capacity shown in the table in  
order for the ARI rating condition to be valid. See Figure 1 for an example selection.  
7
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Equipment Selection  
Air Handler Selection Example  
Figure 1 shows a typical performance table for a heat pump air  
handler. Suppose the evaporator temperature required is 50ºF,  
the capacity required is 35,000 Btuh and the airflow required  
is 1,200 CFM. Each evaporator temperature listed in the table  
shows three wet bulb temperatures. As recommended in the  
table notes above, select the 67ºF WB column. At 1,200 CFM,  
the model 003 capacity is 36 MBtuh, which is higher than the  
minimum capacity required of 35,000 Btuh. In this example,  
model 003 would be the appropriate match.  
Figure 1: Selecting Air Handler  
Utilizing the Existing Air Handler or Coil (R22 units only)  
It is recommended that a new coil or air handler be installed  
with any geothermal split system compressor section due to the  
low initial cost of the additional equipment versus the reliability  
and benefit of new technology, increased reliability and  
warranty. However, if the existing air handler must be used (R22  
systems only), the following conditions apply:  
• If the existing coil currently uses an orifice, the orifice must be  
removed and replaced with a TXV. If the coil utilizes capillary  
tubes, it will not operate properly with the geothermal split  
system and should be replaced.  
• If life expectancy of indoor coil (and associated components  
- fan, cabinet, etc.) is less than 7-10 years, indoor section  
should be replaced.  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
8
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Installation  
2. Provide adequate clearance for maintenance and  
service. Do not block access panels with piping, conduit  
or other materials.  
3. Provide access for servicing the compressor and coils  
without removing the unit.  
4. Provide an unobstructed path to the unit within the closet  
or mechanical room. Space should be sufficient to allow  
removal of the unit, if necessary.  
5. In limited side access installations, pre-removal of the  
control box side mounting screws will allow control box  
removal for future servicing (R22 units only).  
6. Provide access to water valves and fittings and  
screwdriver access to the unit side panels and all  
electrical connections.  
NOTICE! Failure to remove shipping  
brackets from spring-mounted compressors  
will cause excessive noise, and could cause  
component failure due to added vibration.  
The installation of water source heat pump units and all  
associated components, parts and accessories which make  
up the installation shall be in accordance with the regulations  
of ALL authorities having jurisdiction and MUST conform to  
all applicable codes. It is the responsibility of the installing  
contractor to determine and comply with ALL applicable  
codes and regulations.  
Removing Existing Condensing Unit (Where Applicable)  
1. Pump down condensing unit. Close the liquid line service  
valve of existing condensing unit and start compressor  
to pump refrigerant back into compressor section. Then,  
close suction service valve while compressor is still  
running to trap refrigerant in outdoor section. Immediately  
kill power to the condensing unit.  
Air Handler Installation  
This manual specifically addresses the compressor section  
of the system. Air handler location and installation should be  
according to the instructions provided with the air handling  
unit.  
2. Disconnect power and low voltage and remove old  
condensing unit. Cut or unbraze line set from unit.  
Remove condensing unit.  
3. If condensing unit is not operational or will not pump  
down, refrigerant should be recovered using appropriate  
equipment.  
4. Replace line set, especially if upgrading system from  
R-22 to R-410A refrigerant. If line set cannot be replaced,  
it must be thoroughly flushed before installing new  
compressor section. R-410A compressors use POE  
oil instead of mineral oil (R-22 systems). Mineral oil is  
not compatible with POE oil, and could cause system  
damage if not completely flushed from the line set.  
“Indoor” Compressor Section Location  
Both “indoor” and “outdoor” versions of the geothermal split  
system compressor section are available. “Indoor” version  
is not designed for outdoor installation. Locate the unit in  
an INDOOR area that allows enough space for service  
personnel to perform typical maintenance or repairs without  
removing unit. Units are typically installed in a mechanical  
room or closet. Never install units in areas subject to freezing  
or where humidity levels could cause cabinet condensation  
(such as unconditioned spaces subject to 100% outside air).  
Consideration should be given to access for easy removal  
of service access panels. Provide sufficient room to make  
water, electrical, and line set connections.  
Any access panel screws that would be difficult to remove  
after the unit is installed should be removed prior to setting the  
unit. Refer to Figure 2 for an illustration of a typical installation.  
Refer to “Physical Dimensions” section for dimensional data.  
Conform to the following guidelines when selecting unit  
location:  
1. Install the unit on a piece of rubber, neoprene or other  
mounting pad material for sound isolation. The pad should  
be at least 3/8” [10mm] to 1/2” [13mm] in thickness. Extend  
the pad beyond all four edges of the unit.  
9
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Installation  
Figure 2: HTS/HSS Installation  
External Flow Controller Mounting  
The female locking ring is threaded onto the pipe threads  
which holds the male pipe end against the rubber gasket,  
and seals the joint. HAND TIGHTEN ONLY! DO NOT  
OVERTIGHTEN!  
The Flow Controller can be mounted beside the unit  
as shown in Figure 7. Review the Flow Controller  
installation manual for more details.  
Figure 4: Water Connections (Indoor Compressor Section)  
Water Connections-Residential (Distributor) Models  
Residential models utilize swivel piping fittings for  
water connections that are rated for 450 psi (3101 kPa)  
operating pressure. The connections have a rubber  
gasket seal similar to a garden hose gasket, which when  
mated to the flush end of most 1” threaded male pipe  
fittings provides a leak-free seal without the need for  
thread sealing tape or joint compound. Insure that the  
rubber seal is in the swivel connector prior to attempting  
any connection (rubber seals are shipped attached to the  
swivel connector). DO NOT OVER TIGHTEN or leaks may  
occur.  
HandTighten  
Only!  
DoNot  
SwivelNut  
Overtighten!  
Stainlesssteel  
snapring  
BrassAdaptor  
Gasket  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
10  
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Installation  
GROUND-LOOP HEAT PUMP APPLICATIONS  
x CAUTION! x  
Pre-Installation  
CAUTION! The following instructions represent industry  
accepted installation practices for closed loop earth coupled  
heat pump systems. Instructions are provided to assist the  
contractor in installing trouble free ground loops. These  
instructions are recommendations only. State/provincial  
and local codes MUST be followed and installation MUST  
conform to ALL applicable codes. It is the responsibility of  
the installing contractor to determine and comply with ALL  
applicable codes and regulations.  
Prior to installation, locate and mark all existing underground  
utilities, piping, etc. Install loops for new construction before  
sidewalks, patios, driveways, and other construction has  
begun. During construction, accurately mark all ground loop  
piping on the plot plan as an aid in avoiding potential future  
damage to the installation.  
Piping Installation  
The typical closed loop ground source system is shown in  
Figures 7 and 8. All earth loop piping materials should be  
limited to polyethylene fusion only for in-ground sections of  
the loop. Galvanized or steel fittings should not be used at  
any time due to their tendency to corrode. All plastic to metal  
threaded fittings should be avoided due to their potential to  
leak in earth coupled applications. A flanged fitting should  
be substituted. P/T plugs should be used so that flow can be  
measured using the pressure drop of the unit heat exchanger.  
11  
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Ground-Loop Heat Pump Applications  
Earth loop temperatures can range between 25 and 110°F  
[-4 to 43°C]. Flow rates between 2.25 and 3 gpm per ton  
[2.41 to 3.23 l/m per kW] of cooling capacity is recommended  
in these applications.  
the loop to a homogenous temperature. This is a good time  
for tool cleanup, piping insulation, etc. Then, perform final  
flush and pressurize the loop to a static pressure of 50-75 psi  
[345-517 kPa] (winter) or 35-40 psi [241-276 kPa] (summer).  
After pressurization, be sure to loosen the plug at the end  
of the Grundfos loop pump motor(s) to allow trapped air to  
be discharged and to insure the motor housing has been  
flooded. This is not required for Taco circulators. Insure  
that the Flow Controller provides adequate flow through the  
unit by checking pressure drop across the heat exchanger  
and compare to the pressure drop tables at the back of the  
manual.  
Test individual horizontal loop circuits before backfilling.  
Test vertical U-bends and pond loop assemblies prior to  
installation. Pressures of at least 100 psi [689 kPa] should be  
used when testing. Do not exceed the pipe pressure rating.  
Test entire system when all loops are assembled.  
Flushing the Earth Loop  
Once piping is completed between the unit, Flow Controller  
and the ground loop (Figures 7 and 8), the loop is ready for  
final purging and charging. A flush cart with at least a 1.5 hp  
[1.1 kW] pump is required to achieve enough fluid velocity  
in the loop piping system to purge air and dirt particles. An  
antifreeze solution is used in most areas to prevent freezing.  
All air and debris must be removed from the earth loop piping  
before operation. Flush the loop with a high volume of water  
at a minimum velocity of 2 fps (0.6 m/s) in all piping. The  
steps below must be followed for proper flushing.  
1. Fill loop with water from a garden hose through the flush  
cart before using the flush cart pump to insure an even  
fill.  
Antifreeze  
In areas where minimum entering loop temperatures drop  
below 40°F [5°C] or where piping will be routed through  
areas subject to freezing, antifreeze is required. Alcohols  
and glycols are commonly used as antifreeze; however  
your local sales manager should be consulted for the  
antifreeze best suited to your area. Freeze protection  
should be maintained to 15°F [9°C] below the lowest  
expected entering loop temperature. For example, if 30°F  
[-1°C] is the minimum expected entering loop temperature,  
the leaving loop temperature would be 25 to 22°F [-4 to  
-6°C] and freeze protection should be at 15°F [-10°C].  
Calculation is as follows:  
2. Once full, the flushing process can begin. Do not allow  
the water level in the flush cart tank to drop below the  
pump inlet line to avoid air being pumped back out to the  
earth loop.  
30°F - 15°F = 15°F [-1°C - 9°C = -10°C].  
All alcohols should be premixed and pumped from a reservoir  
outside of the building when possible or introduced under  
the water level to prevent fumes. Calculate the total volume  
of fluid in the piping system. Then use the percentage  
by volume shown in Table 2 for the amount of antifreeze  
needed. Antifreeze concentration should be checked from a  
well mixed sample using a hydrometer to measure specific  
gravity.  
3. Try to maintain a fluid level in the tank above the return  
tee so that air cannot be continuously mixed back into  
the fluid. Surges of 50 psi (345 kPa) can be used to help  
purge air pockets by simply shutting off the return valve  
going into the flush cart reservoir. This “dead heads” the  
pump to 50 psi (345 kPa). To purge, dead head the pump  
until maximum pumping pressure is reached. Open the  
return valve and a pressure surge will be sent through  
the loop to help purge air pockets from the piping system.  
4. Notice the drop in fluid level in the flush cart tank when  
the return valve is shut off. If air is adequately purged  
from the system, the level will drop only 1-2 inches (2.5 -  
5 cm) in a 10” (25 cm) diameter PVC flush tank (about a  
half gallon [2.3 liters]), since liquids are incompressible.  
If the level drops more than this, flushing should continue  
since air is still being compressed in the loop fluid.  
Perform the “dead head” procedure a number of times.  
Note: This fluid level drop is your only indication of air in  
the loop.  
Low Water Temperature Cutout Setting  
CXM Control  
When antifreeze is selected, the FP1 jumper (JW3) should  
be clipped to select the low temperature (antifreeze 13°F  
[-10.6°C]) set point and avoid nuisance faults (see “Low  
Water Temperature Cutout Selection” in this manual). NOTE:  
Low water temperature operation requires extended range  
equipment.  
Antifreeze may be added before, during or after the flushing  
procedure. However, depending upon which time is chosen,  
antifreeze could be wasted when emptying the flush cart  
tank. See antifreeze section for more details.  
Loop static pressure will fluctuate with the seasons.  
Pressures will be higher in the winter months than during  
the cooling season. This fluctuation is normal and should be  
considered when charging the system initially. Run the unit in  
either heating or cooling for a number of minutes to condition  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
12  
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Ground-Loop Heat Pump Applications  
Table 1: Approximate Fluid Volume (U.S. gal. [L]) per  
100' of Pipe  
Figure 7: Loop Connection (Indoor  
Compressor Section)  
Fluid Volume (gal [liters] per 100’ [30 meters) Pipe)  
Pipe  
Size  
Volume (gal) [liters]  
1”  
4.1 [15.3]  
6.4 [23.8]  
9.2 [34.3]  
3.9 [14.6]  
2.8 [10.4]  
4.5 [16.7]  
8.0 [29.8]  
10.9 [40.7]  
18.0 [67.0]  
8.3 [30.9]  
10.9 [40.7]  
17.0 [63.4]  
1.0 [3.8]  
Copper  
1.25”  
2.5”  
Rubber Hose  
1”  
3/4” IPS SDR11  
1” iPS SDR11  
1.25” IPS SDR11  
1.5” IPS SDR11  
2” IPS SDR11  
1.25” IPS SCH40  
1.5” IPS SCH40  
2” IPS SCH40  
Typical  
Polyethylene  
Unit Heat Exchanger  
Flush Cart Tank  
10” Dia x 3ft tall  
[254mm x 91.4cm tall]  
10 [37.9]  
NOTICE! Cabinet opening around loop piping (outdoor  
compressor section) must be sealed to prevent entry of  
rodents that could potentially damage unit wiring by chewing  
on the insulation.  
NOTICE! Outdoor compressor section may not be tilted  
more than 5 degrees from level. Damage to the compressor  
or stress on the loop piping could result if unit is tilted. A  
concrete pad, anchor posts and/or soil compaction may be  
required to avoid tilting as ground settles.  
Table 2: Antifreeze Percentages by Volume  
Minimum Temperature for Low Temperature Protection  
Type  
10°F [-12.2°C]  
15°F [-9.4°C]  
20°F [-6.7°C]  
25°F [-3.9°C]  
Methanol  
25%  
38%  
29%  
21%  
25%  
25%  
16%  
22%  
20%  
10%  
15%  
14%  
100% USP food grade Propylene Glycol  
Ethanol*  
* Must not be denatured with any petroleum based product  
13  
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Ground-Water Heat Pump Applications -  
“Indoor” Compressor Section Only  
Open Loop - Ground Water Systems  
(“Indoor” Compressor Section Only)  
prevent pump short cycling. Discharge water from the unit  
is not contaminated in any manner and can be disposed  
of in various ways, depending on local building codes (e.g.  
recharge well, storm sewer, drain field, adjacent stream  
or pond, etc.). Most local codes forbid the use of sanitary  
sewer for disposal. Consult your local building and zoning  
department to assure compliance in your area.  
The “outdoor” version of the compressor section may not  
be used with open loop systems due to potential freezing of  
water piping. Typical open loop piping is shown in Figure 9.  
Shut off valves should be included for ease of servicing. Boiler  
drains or other valves should be “tee’d” into the lines to allow  
acid flushing of the heat exchanger. Shut off valves should  
be positioned to allow flow through the coax via the boiler  
drains without allowing flow into the piping system. P/T plugs  
should be used so that pressure drop and temperature can be  
measured. Piping materials should be limited to copper or PVC  
SCH80. Note: Due to the pressure and temperature extremes,  
PVC SCH40 is not recommended.  
The pump should be sized to handle the home’s domestic  
water load (typically 5-9 gpm [23-41 l/m]) plus the flow rate  
required for the heat pump. Pump sizing and expansion  
tank must be chosen as complimentary items. For example,  
an expansion tank that is too small can causing premature  
pump failure due to short cycling. Variable speed pumping  
applications should be considered for the inherent energy  
savings and smaller expansion tank requirements.  
Water quantity should be plentiful and of good quality.  
Consult Table 3 for water quality guidelines. The unit can  
be ordered with either a copper or cupro-nickel water  
heat exchanger. Consult Table 3 for recommendations.  
Copper is recommended for closed loop systems and open  
loop ground water systems that are not high in mineral  
content or corrosiveness. In conditions anticipating heavy  
scale formation or in brackish water, a cupro-nickel heat  
exchanger is recommended. In ground water situations  
where scaling could be heavy or where biological growth  
such as iron bacteria will be present, an open loop system  
is not recommended. Heat exchanger coils may over time  
lose heat exchange capabilities due to build up of mineral  
deposits. Heat exchangers must only be serviced by a  
qualified technician, as acid and special pumping equipment  
is required. Desuperheater coils can likewise become scaled  
and possibly plugged. In areas with extremely hard water,  
the owner should be informed that the heat exchanger  
may require occasional acid flushing. In some cases, the  
desuperheater option should not be recommended due to  
hard water conditions and additional maintenance required.  
Water Control Valve  
Note the placement of the water control valve in figure 9.  
Always maintain water pressure in the heat exchanger by  
placing the water control valve(s) on the discharge line  
to prevent mineral precipitation during the off-cycle. Pilot  
operated slow closing valves are recommended to reduce  
water hammer. If water hammer persists, a mini-expansion  
tank can be mounted on the piping to help absorb the excess  
hammer shock. Insure that the total ‘VA’ draw of the valve  
can be supplied by the unit transformer. For instance, a slow  
closing valve can draw up to 35VA. This can overload smaller  
40 or 50 VA transformers depending on the other controls  
in the circuit. A typical pilot operated solenoid valve draws  
approximately 15VA (see Figure 24). Note the special wiring  
diagrams for slow closing valves (Figures 25 & 26).  
Flow Regulation  
Flow regulation can be accomplished by two methods. One  
method of flow regulation involves simply adjusting the ball  
valve or water control valve on the discharge line. Measure  
the pressure drop through the unit heat exchanger, and  
determine flow rate from Tables 11a through 11b. Since the  
pressure is constantly varying, two pressure gauges may  
be needed. Adjust the valve until the desired flow of 1.5 to  
2 gpm per ton [2.0 to 2.6 l/m per kW] is achieved. A second  
method of flow control requires a flow control device mounted  
on the outlet of the water control valve. The device is typically  
a brass fitting with an orifice of rubber or plastic material  
that is designed to allow a specified flow rate. On occasion,  
flow control devices may produce velocity noise that can be  
reduced by applying some back pressure from the ball valve  
located on the discharge line. Slightly closing the valve will  
spread the pressure drop over both devices, lessening the  
velocity noise. NOTE: When EWT is below 50°F [10°C], a  
minimum of 2 gpm per ton (2.6 l/m per kW) is required.  
Water Quality Standards  
Table 3 should be consulted for water quality requirements.  
Scaling potential should be assessed using the pH/Calcium  
hardness method. If the pH <7.5 and the Calcium hardness  
is less than 100 ppm, scaling potential is low. If this method  
yields numbers out of range of those listed, the Ryznar  
Stability and Langelier Saturation indecies should be  
calculated. Use the appropriate scaling surface temperature  
for the application, 150°F [66°C] for direct use (well water/  
open loop) and DHW (desuperheater); 90°F [32°F] for  
indirect use. A monitoring plan should be implemented in  
these probable scaling situations. Other water quality issues  
such as iron fouling, corrosion prevention and erosion and  
clogging should be referenced in Table 3.  
Expansion Tank and Pump  
Use a closed, bladder-type expansion tank to minimize  
mineral formation due to air exposure. The expansion tank  
should be sized to provide at least one minute continuous  
run time of the pump using its drawdown capacity rating to  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
14  
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Ground-Water Heat Pump Applications  
Water Coil Low Temperature Limit Setting  
Figure 9: Water Well Connections  
For all open loop systems the 30°F [-1.1°C] FP1 setting  
(factory setting-water) should be used to avoid freeze damage  
to the unit. See “Low Water Temperature Cutout Selection” in  
this manual for details on the low limit setting.  
x CAUTION! x  
CAUTION! Many units installed with a factory or field supplied  
manual or electric shut-off valve. DAMAGE WILL OCCUR if  
shut-off valve is closed during unit operation. A high pressure  
switch must be installed on the heat pump side of any field  
provided shut-off valves and connected to the heat pump  
controls in series with the built-in refrigerant circuit high  
pressure switch to disable compressor operation if water  
pressure exceeds pressure switch setting. The field installed  
high pressure switch shall have a cut-out pressure of 235 psig  
and a cut-in pressure of 190 psig. This pressure switch can  
be ordered from HCI with a 1/4” internal flare connection as  
part number 39B0005N01.  
x CAUTION! x  
CAUTION! Refrigerant pressure activated water regulating  
valves should never be used with HCI equipment.  
15  
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Water Quality Standards  
Table 3: Water Quality Standards  
Water Quality  
Parameter  
HX  
Material  
Closed  
Recirculating  
Open Loop and Recirculating Well  
Scaling Potential - Primary Measurement  
Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below.  
pH/Calcium Hardness  
Method  
-
All  
pH < 7.5 and Ca Hardness <100ppm  
Index Limits for Probable Scaling Situations - (Operation outside these limits is not recommended)  
Scaling indexes should be calculated at 150°F [66°C] for direct use and HWG applications,  
and at 90°F [32°C] for indirect HX use. A monitoring plan should be implemented.  
Ryznar  
Stability Index  
-
6.0 - 7.5  
If >7.5 minimize steel pipe use.  
All  
All  
-
-0.5 to +0.5  
Langelier  
Saturation Index  
If <-0.5 minimize steel pipe use. Based upon 150°F [66°C] HWG and  
Direct well, 85°F [29°C] Indirect Well HX  
Iron Fouling  
2+  
-
-
Iron Fe  
(Ferrous)  
<0.2 ppm (Ferrous)  
If Fe2+ (ferrous)>0.2 ppm with pH 6 - 8, O2<5 ppm check for iron bacteria  
All  
All  
(Bacterial Iron potential)  
<0.5 ppm of Oxygen  
Above this level deposition will occur.  
Iron Fouling  
Corrosion Prevention  
6 - 8.5  
6 - 8.5  
pH  
All  
All  
Monitor/treat as  
needed  
Minimize steel pipe below 7 and no open tanks with pH <8  
-
<0.5 ppm  
At H S>0.2 ppm, avoid use of copper and copper nickel piping or HX's.  
2
Hydrogen Sulfide (H S)  
2
Rotten egg smell appears at 0.5 ppm level.  
Copper alloy (bronze or brass) cast components are OK to <0.5 ppm.  
Ammonia ion  
-
as hydroxide, chloride,  
nitrate and sulfate  
compounds  
All  
<0.5 ppm  
Maximum Allowable at maximum water temperature.  
50°F (10°C)  
<20ppm  
<150 ppm  
<400 ppm  
<1000 ppm  
>1000 ppm  
75°F (24°C)  
NR  
100ϒF (38ϒC)  
NR  
Copper  
CuproNickel  
304 SS  
316 SS  
Titanium  
-
-
-
-
-
Maximum  
Chloride Levels  
NR  
NR  
<250 ppm  
<550 ppm  
>550 ppm  
<150 ppm  
< 375 ppm  
>375 ppm  
Erosion and Clogging  
<10 ppm of particles  
and a maximum  
velocity of 6 fps [1.8 m/s].  
Filtered for maximum  
800 micron [800mm,  
20 mesh] size.  
<10 ppm (<1 ppm "sandfree" for reinjection) of particlesand a maximum  
velocity of 6 fps [1.8 m/s]. Filtered for maximum 800 micron [800mm,  
20 mesh] size.Any particulate that is not removed can potentially  
clog components.  
All  
Particulate Size and  
Erosion  
Rev.: 03/28/08S  
Notes:  
• Closed Recirculating system is identified by a closed pressurized piping system.  
• Recirculating open wells should observe the open recirculating design considerations.  
• NR - Application not recommended.  
• "-" No design Maximum.  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
16  
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Refrigeration Installation  
R-410A models are shipped with a filter drier (loose) inside the  
cabinet that must be installed in the liquid line at the line set.  
All brazing should be performed using nitrogen circulating  
at 2-3 psi [13.8-20.7 kPa] to prevent oxidation inside the  
tubing. All linesets should be insulated with a minimum  
of 1/2” [13mm] thick closed cell insulation. All insulation  
tubing should be sealed using a UV resistant paint or  
covering to prevent deterioration from sunlight.  
x CAUTION! x  
CAUTION! R-410A systems operate at higher pressures  
than R-22 systems. Be certain that service equipment  
(gauges, tools, etc.) is rated for R-410A. Some R-22  
service equipment may not be acceptable.  
x CAUTION! x  
When passing refrigerant lines through a wall, seal  
opening with silicon-based caulk. Avoid direct contact  
with water pipes, duct work, floor joists, wall studs,  
floors or other structural components that could transmit  
compressor vibration. Do not suspend refrigerant tubing  
from joists with rigid straps. Do not attach line set to the  
wall. When necessary, use hanger straps with isolation  
sleeves to minimize tranmission of line set vibration to  
the structure.  
CAUTION! Installation of a factory supplied liquid line  
bi-directional filter drier is required. Never install a suction  
line filter in the liquid line.  
Line Set Installation  
Figures 12a through 13b illustrate typical installations with  
the “indoor” and “outdoor” versions of the compressor section  
matched to either an air handler (fan coil) or add-on furnace  
coil. Table 4 shows typical line-set diameters at various lengths.  
Lineset lengths should be kept to a minimum and should always  
be installed with care to avoid kinking. Line sets over 60 feet [18  
meters] long are not recommended due to potential oil transport  
problems and excessive pressure drop. If the line set is kinked  
or distorted, and it cannot be formed back into its original shape,  
the damaged portion of the line should be replaced. A restricted  
line set will effect the performance of the system.  
Installing the Lineset at the Compressor Section  
Braze the line set to the service valve stubs as shown in Figure  
10. On installations with long line sets, copper adapters may  
be needed to connect the larger diameter tube to the stubs.  
Nitrogen should be circulated through the system at 2-3 psi  
[13.8-20.7 kPa] to prevent oxidation contamination. Use a  
low silver phos-copper braze alloy on all brazed connections.  
Compressor section is shipped with a factory charge.  
Therefore, service valves should not be opened until the  
line set has been leak tested, purged and evacuated. See  
“Charging the System.”  
A reversible heat pump filter drier is installed on the liquid  
line inside the compressor section cabinet (R-22 units only).  
Installing the Indoor Coil and Lineset  
Table 4: Lineset Diameters and Charge Information  
Factory†  
Charge (oz) Charge (oz)  
Basic*  
20 Feet [6 meters]  
40 Feet [12 meters]  
60 Feet [18 meters]  
Model  
Liquid  
Suction  
Liquid  
Suction  
Liquid  
Suction  
[kg]  
[kg]  
HSS Series  
018  
024  
030  
036  
042  
048  
060  
70 [1.98]  
74 [2.10]  
55 [1.56]  
59 [1.67]  
93 [2.64]  
102 [2.89]  
107 [3.03]  
115 [3.26]  
121 [3.43]  
3/8”  
3/8”  
3/8”  
3/8”  
3/8”  
3/8”  
3/8”  
3/4”  
3/8”  
3/8”  
3/8”  
3/8”  
3/8”  
3/8”  
1/2”  
3/4”  
3/4”  
3/8”  
3/8”  
3/8”  
3/8”  
3/8”  
1/2”  
1/2”  
3/4”  
7/8”  
3/4”  
108 [3.06]  
117 [3.32]  
122 [3.46]  
130 [3.69]  
136 [3.86]  
3/4”  
7/8”  
7/8”  
3/4”  
7/8”  
7/8”  
7/8”  
7/8”  
7/8”  
7/8”  
7/8”  
1-1/8”  
1-1/8”  
1-1/8”  
1-1/8”  
HTS Series  
024  
036  
048  
060  
90 [2.55]  
104 [2.95]  
126 [3.57]  
168 [4.76]  
75 [2.13]  
89 [2.52]  
111 [3.15]  
138 [3.91]  
3/8”  
3/8”  
3/8”  
1/2”  
3/4”  
3/8”  
3/8”  
3/8”  
1/2”  
3/4”  
7/8”  
3/8”  
3/8”  
1/2”  
1/2”  
7/8”  
7/8”  
7/8”  
7/8”  
7/8”  
1-1/8”  
1-1/8”  
1-1/8”  
1-1/8”  
• Basic charge includes only the amount required for the condensing unit and the evaporating coil.  
An additional amount should be added allowing 0.6oz per ft. for 3/8” [0.6g per cm] and 1.2oz per ft. for 1/2” [1.1g per cm] of lineset used.  
†Factory charge is preset for 25’ [7.6 meters] lineset.  
17  
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Refrigeration Installation  
Figure 10: Braze Instructions  
Figure 11: Air Coil Connection  
Add-On Heat Pump Applications  
The indoor coil should be located in the supply side of  
the furnace to avoid condensation damage to the furnace  
heat exchanger for add-on heat pump applications. A high  
temperature limit switch should be installed as shown in  
Figures 12b and 13b just upstream of the coil to de-energize  
the compressor any time the furnace is energized to avoid  
blowing hot air directly into the coil, elevating refrigerant  
pressures during operation. The heat pump will trip out on  
high pressure lockout without some method of disengaging  
the compressor during furnace operation. Alternatively, some  
thermostats with “dual fuel” mode will automatically de-  
energize the compressor when second stage (backup) heat  
is required.  
The TXV should be brazed into place as shown in Figure 11,  
keeping the “IN” side toward the compressor section. The  
TXV has an internal check valve and must be installed in the  
proper direction for operation. Always keep the valve body  
cool with a brazing shield and wet rags to prevent damage to  
the TXV. Attach the bulb to the suction line using the supplied  
hose clamp. Be careful not to overtighten the clamp and  
deform the bulb.  
NOTICE! The air coil should be thoroughly washed with a  
filming agent, (dishwasher detergent like Cascade) to help  
condensate drainage. Apply a 20 to 1 solution of detergent  
and water. Spray both sides of coil, repeat and rinse  
thoroughly with water.  
Table 5: Service Valve Positions  
Service  
Port  
Closed  
Open  
Open  
Position  
Description  
System  
CCW - Full Out  
Operation Position  
Service Position  
Shipping Position  
Open  
Open  
Evacuation and Charging the Unit  
CCW - Full Out 1/2 turn CW  
CW - Full In  
LEAK TESTING - The refrigeration line set must be pressurized  
and checked for leaks before evacuating and charging the unit.  
To pressurize the line set, attach refrigerant gauges to the service  
ports and add an inert gas (nitrogen or dry carbon dioxide) until  
pressure reaches 60-90 psig [413-620 kPa]. Never use oxygen  
or acetylene to pressure test. Use a halogen leak tester or a good  
quality bubble solution to detect leaks on all connections made in  
the field. Check the service valve ports and stem for leaks. If a leak  
is found, repair it and repeat the above steps. For safety reasons  
do not pressurize system above 150 psig [1034 kPa]. System is  
now ready for evacuation and charging.  
Closed  
Figure 11 shows the installation of the lineset and TXV to a  
typical indoor coil. An indoor coil or air handler (fan coil) with a  
TXV is required. Coils with cap tubes may not be used. If coil  
includes removable fixed orifice, the orifice must be removed  
and a TXV must be installed as shown in Figure 11. Fasten the  
copper line set to the coil. Nitrogen should be circulated through  
the system at 2-3 psi [13.8-20.7 kPa] to prevent oxidation inside  
the refrigerant tubing. Use a low silver phos-copper braze alloy  
on all brazed connections.  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
18  
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Refrigeration Installation  
Figure 12a: Typical Split/Air Handler Installation (Indoor Compressor Section)  
Power  
Disconnects  
TXV 'IN' toward  
Compressor  
Section  
Insulated  
Linesets  
PVC Condensate  
with vented trap  
Compressor  
Section  
Low Voltage  
Air pad or Extruded  
polystryene  
Figure 12b: Typical Split/Add-on Coil Fossil Fuel Furnace Installation (Indoor Compressor Section)  
Air Temperature  
TXV 'IN' toward  
Limit Switch  
Compressor  
Section  
PVC Condensate  
with vented trap  
Compressor  
Section  
Air pad or Extruded  
polystyrene  
19  
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Refrigeration Installation  
Evacuation Of The Lineset And Coil  
Charging The System  
The line set and coil must be evacuated to at least 500  
microns to remove any moisture and noncondensables.  
Evacuate the system through both service ports in the  
shipping position (full CW in - see table 5) to prevent false  
readings on the gauge because of pressure drop through  
service ports. A vacuum gauge or thermistor capable of  
accurately meausuring the vacuum depth is crucial in  
determining if the system is ready for charging. If the system  
meets the requirements in Figure 14, it is ready for charging.  
There are two methods of charging a refrigerant system. One  
method is the total charge method, where the volume of the  
system is determined and the refrigerant is measured and  
added into the evacuated system. The other method is the  
partial charge method where a small initial charge is added  
to an evacuated system, and remaining refrigerant added  
during operation.  
Total Charge Method - See Table 4 for the compressor  
section basic charge. For line sets with 3/8” liquid lines  
add 0.6 ounces of refrigerant to the basic charge for every  
installed foot of liquid line [0.6 grams per cm]. Add 1.2 oz.  
per foot [1.1 grams per cm] if using l/2” line. Once the total  
charge is determined, the factory pre-charge (Table 4) is  
subtracted and the remainder is the amount needed to be  
added to the system. This method should be used with the  
ARI matched air handler.  
Figure 14: Evacuation Graph  
EXAMPLE: R22 model 048 with 40 feet [12 meters] of  
installed liquid line (3/8” O.D.). The basic charge of model  
048 is 115 oz [3.26 kg]. The 40 ft. [12 meter] 3/8” line set  
requires 24 oz. [0.72 kg] (40 ft. x 0.6 oz./ft = 24 oz. -- 1200cm  
x 0.6g/cm = 720g). Total charge = 115 + 24 = 139 oz [3.26 +  
0.72 = 3.98 kg]. The compressor section is shipped from the  
factory with 130 oz. [3.69 kg] of refrigerant (for 25 ft [7.6m]  
lineset), so the amount to be added is 9 oz. [0.29 kg] (total  
charge - shipped charge = charge to be added).  
Table 6a: R-22 Charging Values  
Table 6b: R-410A Charging Values  
x NOTICE! x  
x NOTICE! x  
NOTICE: Use tables 14a to 15 for superheat/subcooling  
values. These tables use discharge pressure (converted  
to saturation temperature) and liquid line temperature  
for subcooling calculations. If using liquid line pressure,  
subtract 3°F from the table values.  
NOTICE: Use tables 14a to 15 for superheat/subcooling  
values. These tables use discharge pressure (converted  
to saturation temperature) and liquid line temperature  
for subcooling calculations. If using liquid line pressure,  
subtract 3°F from the table values.  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
20  
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Refrigeration Installation  
Turn service valves full out CCW (see Table 5) and then turn  
back in one-half turn to open service ports. Add the required  
refrigerant so that the total charge calculated for the unit  
and line set is now in the system. Open the service valve  
fully counter clockwise so that the stem will backseat and  
prevent leakage through the schrader port while it is not in  
use. Start unit in the heating mode and measure superheat  
and subcooling values after 5 minutes of run time. See tables  
14a to 15 for superheat and sub-cooling values. Superheat  
is measured using suction temperature and pressure at the  
compressor suction line. Subcooling should be measured  
using the liquid line temperature immediately outside the  
compressor section cabinet and either the liquid line service  
valve pressure or the compressor discharge pressure. Note  
that different values from tables 14a to 15 will be obtained  
due to the pressure losses through the condenser heat  
exchanger. Adding refrigerant will increase sub-cooling  
while superheat should remain fairly constant allowing for a  
slight amount of hunting in TXV systems. This increase in  
subcooling will require 5 minutes or so of operation before it  
should be measured. After values are measured, compare to  
the chart and go to “FINAL EVALUATION.”  
does not perform to specifications the cooling TXV (air coil  
side) may need to be readjusted (if possible) until the cooling  
superheat values are met.  
Checking Superheat and Subcooling  
Determining Superheat:  
1. Measure the temperature of the suction line at a point  
near the expansion valve bulb.  
2. Determine the suction pressure by attaching refrigeration  
gauges to the suction schrader connection at the  
compressor.  
3. Convert the pressure obtained in step 2 to saturation  
temperature (boiling point) by using the pressure/  
temperature conversion table on the gauge set.  
4. Subtract the temperature obtained in step 3 from step  
1. The difference will be the superheat of the unit or the  
total number of degrees above saturation temperature.  
Refer to Tables 14a to 15 for superheat ranges at specific  
entering water conditions.  
Example (R-22 refrigerant):  
The temperature of the suction line at the sensing bulb is  
50°F. The suction pressure at the compressor is 65 psig  
which is equivalent to 38°F saturation temperature from the  
R-22 press/temp conversion table on the gauge set.  
38°F subtracted from 50°F = 12°F Superheat.  
PARTIAL CHARGE METHOD - Open service valve fully  
counterclockwise and then turn back in one-half turn to open  
service port. Add vaporized (Gas) into the suction side of  
the compressor until the pressure in the system reaches  
approximately 60-70 psig (R-22 systems) or 100-120 psig  
(R-410A systems). Never add liquid refrigerant into the  
suction side of a compressor. Start the unit in heating and  
add gas to the suction port at a rate not to exceed five  
pounds [2.27 kg] per minute. Keep adding refrigerant until the  
complete charge has been entered. Superheat is measured  
using suction temperature and pressure at the compressor  
suction line. Subcooling should be measured using the liquid  
line temperature immediately outside the compressor section  
cabinet and either the liquid line service valve pressure or the  
compressor discharge pressure. Note that different values  
from tables 14a to 15 will be obtained due to the pressure  
losses through the condenser heat exchanger. Adding  
refrigerant will increase sub-cooling while superheat should  
remain fairly constant allowing for a slight amount of hunting  
in TXV systems. This increase in subcooling will require 5  
minutes or so of operation before it should be measured.  
After values are measured, compare to the chart and go to  
“FINAL EVALUATION.”  
Determining Sub-Cooling:  
1. Measure the temperature of the liquid line on the smaller  
refrigerant line (liquid line) just outside of the cabinet.  
This location will be adequate for measurement in both  
modes unless a significant temperature drop in the liquid  
line is anticipated.  
2. Determine the condensor pressure (high side) by  
attaching refrigerant gauges to the schrader connection  
on the liquid line service valve. If the hot gas discharge  
line of the compressor is used, refer to the appropriate  
column in Tables 14a to 15.  
3. Convert the pressure obtained in step 2 to the  
saturation temperature by using the press/temp  
conversion table on the gauge set.  
4. Subtract the temperature of Step 3 from the temperature  
of Step 1. The difference will be the sub-cooling value for  
that unit (total degrees below the saturation temperature).  
Refer to Tables 14a or 6b for sub-cooling values at specific  
entering water temperatures.  
FINAL EVALUATION -In a split system, cooling subcooling  
values can be misleading depending on the location of the  
measurement. Therefore, it is recommended that charging be  
monitored in the heating mode. Charge should be evaluated  
by monitoring the subcooling in the heating mode. After initial  
check of heating sub-cooling, shut off unit and allow to sit 3-5  
minutes until pressures equalize. Restart unit in the cooling  
mode and check the cooling superheat against Tables 14a  
to 15. If unit runs satisfactorily, charging is complete. If unit  
Example (R-22 refrigerant):  
The condenser pressure at the service port is 225 psig,  
which is equivalent to 110°F saturation temperature.  
Discharge pressure is 236 psig at the compressor (113°F  
saturation temperature). Measured liquid line temperature  
is 100°F. 100°F subtracted from 110°F = 10 degrees sub-  
cooling (13 degrees if using the compressor discharge  
pressure).  
21  
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
HotWater Generator  
The HWG (Hot Water Generator) or desuperheater  
option provides considerable operating cost savings by  
utilizing excess heat energy from the heat pump to help  
satisfy domestic hot water requirements. The HWG  
is active throughout the year, providing virtually free  
hot water when the heat pump operates in the cooling  
mode or hot water at the COP of the heat pump during  
operation in the heating mode. Actual HWG water  
heating capacities are provided in the appropriate heat  
pump performance data.  
source water to the HWG. Using a concentric or coaxial  
hot water tank connection fitting eliminates the need to  
tie into the hot water tank cold water piping, but is more  
susceptible to scaling. The optional concentric fitting  
(part # S69619804) is available from your equipment  
supplier and should be installed as shown in Figure  
17 for applications with low scaling potential or where  
a water softener is used. Consult Table 3 for scaling  
potential tests.  
It is always advisable to use water softening equipment  
on domestic water systems to reduce the scaling  
potential and lengthen equipment life. In extreme water  
Heat pumps equipped with the HWG option include  
a built-in water to refrigerant heat exchanger that  
eliminates the need to tie into the heat pump refrigerant conditions, it may be necessary to avoid the use of  
circuit in the field. The control circuit and pump are also the HWG option since the potential cost of frequent  
built in for residential equipment. Figure 15 shows a  
typical example of HWG water piping connections on  
a unit with built-in pump. This piping layout minimizes  
scaling potential.  
maintenance may offset or exceed any savings.  
R-410 systems inherently have a lower hot gas  
temperature than R-22 systems because the  
equipment is more efficient (i.e. less waste heat  
is available). It is possible that energy could be  
transferred from the water heater to the hot gas line  
instead of from the hot gas line to the water heater  
during certain times of the year. To prevent this from  
occuring, a temperature switch will deactivate the  
pump at those conditions that typically occur in the  
cooling mode with entering water temperatures of less  
than 50°F [10°C].  
Electric water heaters are recommended. If a gas,  
propane, or oil water heater is used, a second preheat  
tank must be installed (Figure 16). If the electric water  
heater has only a single center element, the dual tank  
system is recommended to insure a usable entering  
water temperature for the HWG.  
Typically a single tank of at least 52 gallons (235 liters)  
is used to limit installation costs and space. However,  
a dual tank, as shown in Figure 16, is the most efficient  
system, providing the maximum storage and temperate  
Figure 15: Typical HWG Installation  
(Indoor Compressor Section)  
Figure 16: HWG Double Tank Installation  
(Indoor Compressor Section)  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
22  
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
HotWater Generator  
Figure 17: Alternate HWG Piping with concentric/coaxial  
fitting (part #S69619804 not included with unit)  
(Indoor Compressor Section)  
Water Tank Refill  
1. Open the cold water supply to the tank.  
2. Open a hot water faucet to vent air from the system until  
water flows from the faucet; turn off faucet.  
3. Depress the hot water tank pressure relief valve handle to  
ensure that there is no air remaining in the tank.  
4. Inspect all work for leaks.  
5. Before restoring power or fuel supply to the water heater,  
adjust the temperature setting on the tank thermostat(s)  
to insure maximum utilization of the heat available from  
the refrigeration system and conserve the most energy.  
On tanks with both upper and lower elements and  
thermostats, the lower element should be turned down  
to 100°F [38°C] or the lowest setting; the upper element  
should be adjusted to 120-130°F [49-54°C]. Depending  
upon the specific needs of the customer, you may want  
to adjust the upper element differently. On tanks with a  
single thermostat, a preheat tank should be used (figure  
16).  
6. Replace access cover(s) and restore power or  
fuel supply.  
Initial Start-Up  
1. Make sure all valves in the HWG water circuit are  
fully open.  
2. Turn on the heat pump and allow it to run for  
10-15 minutes.  
3. Turn the heat pump and heat pump power supply “OFF”  
and CONNECT POWER TO THE HWG PUMP as shown  
in the unit wiring diagram. Connect the pump power lead  
as instructed on the tag attached to the pump wiring.  
4. The HWG pump should not run if the compressor is  
not running.  
5. The temperature difference between the water entering  
and leaving the HWG coil should be approximately  
5-10°F [3-6°C].  
The heat pump, water piping, pump, and hot water tank  
should be located where the ambient temperature does  
not fall below 50°F [10°C]. Keep water piping lengths at a  
minimum. DO NOT use a one way length greater than 50 ft.  
[15 m].  
All installations must be in accordance with local codes. The  
installer is responsible for knowing the local requirements,  
and for performing the installation accordingly. DO NOT  
connect the pump wiring until “Initial Start-Up” section, below.  
Powering the pump before all installation steps are completed  
will damage the pump.  
6. Allow the unit to operate for 20 to 30 minutes to insure  
that it is functioning properly.  
Water Tank Preparation  
1. Turn off power or fuel supply to the hot water tank.  
2. Connect a hose to the drain valve on the water tank.  
3. Shut off the cold water supply to the water tank.  
4. Open the drain valve and open the pressure relief valve  
or a hot water faucet to drain tank.  
5. When using an existing tank, it should be flushed with  
cold water after it is drained until the water leaving the  
drain hose is clear and free of sediment.  
6. Close all valves and remove the drain hose.  
7. Install HWG water piping.  
HWG Water Piping  
1. Using at least 5/8” [16mm] O.D. copper, route and install  
the water piping, valves and air vent as shown in Figures  
15 to 18. The air vent MUST be at the high point of the  
HWG water piping.  
2. Insulate all HWG water piping with no less than 3/8”  
[10mm] wall closed cell insulation.  
3. Open both shut off valves and make sure the tank drain  
valve is closed.  
23  
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
HotWater Generator Module Refrigeration Installation  
x CAUTION! x  
CAUTION! The HWG module must be installed in an area  
x WARNING! x  
WARNING! The HWG module is an appliance that operates  
in conjunction with the heat pump system, the hot water  
system and the electrical system. Installation should only be  
performed by skilled technicians with appropriate training and  
experience. The installation must be in compliance with local  
codes and ordinances. Local plumbing and electrical building  
codes take precedence over instructions contained herein.  
The Manufacturer accepts no liability for equipment damaged  
and/or personal injury arising from improper installation of the  
HWG module.  
that is not subject to freezing temperatures.  
NOTICE! Make sure the compressor discharge line  
is connected to the “Hot Gas In” stub on the Heat  
Recovery Unit.  
x CAUTION! x  
CAUTION! Locate Refrigerant lines to avoid accidental  
damage by lawnmowers or children.  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
24  
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Electrical - LineVoltage  
flexible conduit to minimize vibration and sound transmission  
x WARNING! x  
to the building.  
WARNING! To avoid possible injury or death due to  
electrical shock, open the power supply disconnect switch  
and secure it in an open position during installation.  
General Line Voltage Wiring  
Be sure the available power is the same voltage and phase  
shown on the unit serial plate. Line and low voltage wiring  
must be done in accordance with local codes or the National  
Electric Code, whichever is applicable.  
x CAUTION! x  
CAUTION! Use only copper conductors for field installed  
electrical wiring. Unit terminals are not designed to accept other  
types of conductors.  
Power Connection  
Line voltage connection is made by connecting the incoming  
line voltage wires to the “L” side of the contactor as shown in  
Figures 21a through 21c. Consult Tables 8a through 8c for  
correct fuse size.  
Electrical - Line Voltage  
All field installed wiring, including electrical ground, must comply  
with the National Electrical Code as well as all applicable local  
codes. Refer to the unit electrical data for fuse sizes. Consult  
wiring diagram for field connections that must be made by the  
installing (or electrical) contractor.  
208-230 Volt Operation  
Verify transformer tap with air handler wiring diagram to  
insure that the transformer tap is set to the correct voltage,  
208V or 230V.  
All final electrical connections must be made with a length of  
Table 8a: GeoMax 2 (HTS) Series Electrical Data  
HWG  
Pump  
FLA  
External  
Pump  
FLA  
Total  
Unit  
FLA  
Min  
Circuit  
Amps  
Max  
Fuse/  
HACR  
Max Wire  
Ft.  
Compressor  
LRA  
Min  
AWG  
Model  
RLA  
Qty  
(m)  
024  
036  
048  
060  
10.3  
16.7  
21.2  
25.6  
52.0  
82.0  
96.0  
118.0  
1
1
1
1
0.4  
0.4  
0.4  
0.4  
4.0  
4.0  
4.0  
4.0  
14.7  
21.1  
25.6  
30.0  
17.3  
25.3  
30.9  
36.4  
25  
40  
50  
60  
10  
10  
8
107 (32.7)  
73 (22.3)  
95 (29.2)  
81 (24.8)  
8
Rated Voltage of 208/230/60/1  
HACR circuit breaker in USA only  
Min/Max Voltage of 197/254  
All fuses Class RK-5  
Wire length based on one way measurement with 2% voltage drop  
Wire size based on 60°C copper conductor and Minimum Circuit Ampacity.  
Table 8b: HSS Series Electrical Data  
HWG  
Pump  
FLA  
External  
Pump  
FLA  
Total  
Unit  
FLA  
Min  
Circuit  
Amps  
Max  
Fuse/  
HACR  
Max Wire  
Compressor  
LRA  
Min  
AWG  
Model  
Ft  
(m)  
RLA  
Qty  
7.7  
40.3  
56.0  
1
1
1
1
1
1
1
0.40  
0.40  
0.40  
0.40  
0.40  
0.40  
0.40  
4.0  
4.0  
4.0  
4.0  
4.0  
4.0  
4.0  
12.1  
14.7  
16.6  
17.9  
20.9  
22.7  
29.4  
14.0  
17.3  
19.7  
21.3  
25.0  
27.3  
35.7  
20  
25  
30  
35  
40  
45  
60  
12  
10  
10  
10  
10  
10  
8
76 (23.3)  
107 (32.7)  
94 (28.7)  
87 (26.5)  
74 (22.6)  
67 (20.7)  
82 (25.2)  
018  
024  
030  
036  
042  
048  
060  
10.3  
12.2  
13.5  
16.5  
18.3  
25.0  
67.0  
73.0  
95.0  
109.0  
148.0  
Rated Voltage of 208/230/60/1  
HACR circuit breaker in USA only  
Min/Max Voltage of 197/254  
All fuses Class RK-5  
Wire length based on one way measurement with 2% voltage drop  
Wire size based on 60°C copper conductor and Minimum Circuit Ampacity.  
25  
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Electrical - LineVoltage  
ELECTRICAL - POWER WIRING  
Electrical - Line Voltage  
Figure 21b: R-22 Indoor Compressor Section Line  
All field installed wiring, including electrical ground, must comply  
with the National Electrical Code as well as all applicable local  
codes. Refer to the unit electrical data for fuse sizes. Consult  
wiring diagram for field connections that must be made by the  
installing (or electrical) contractor.  
Voltage Field Wiring  
All final electrical connections must be made with a length of  
flexible conduit to minimize vibration and sound transmission  
to the building.  
General Line Voltage Wiring  
Be sure the available power is the same voltage and phase  
shown on the unit serial plate. Line and low voltage wiring  
must be done in accordance with local codes or the National  
Electric Code, whichever is applicable.  
Power Connection  
208-230 Volt Operation  
Line voltage connection is made by connecting the incoming  
line voltage wires to the “L” side of the contactor as shown in  
Figures 21a through 21c. Consult Tables 8a through 8c for  
correct fuse size.  
Verify transformer tap with air handler wiring diagram to  
insure that the transformer tap is set to the correct voltage,  
208V or 230V.  
Figure 21a: R-410A Compressor Section Line Voltage  
Field Wiring  
Unit Power Supply  
(see electrical table for wire  
and breaker size)  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
26  
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Electrical - HWGWiring  
HWG Wiring - “Indoor” Compressor Section  
The hot water generator pump power wiring is disabled at  
the factory to prevent operating the HWG pump “dry.” After  
all HWG piping is completed and air purged from the water  
piping, the pump power wires should be applied to terminals  
on the HWG power block PB2 as shown in the unit wiring  
diagram. This connection can also serve as a HWG disable  
when servicing the unit.  
ELECTRICAL - LOW VOLTAGE WIRING  
Thermostat Connections  
Low Water Temperature Cutout Selection  
The thermostat should be wired directly to the CXM board.  
Figures 22a through 22c show low voltage wiring. Note that  
the air handler or furnace transformer will be used to power  
the CXM board in the compressor section. See “Electrical –  
Thermostat” for specific terminal connections.  
The CXM control allows the field selection of low water (or  
water-antifreeze solution) temperature limit by clipping jumper  
JW3, which changes the sensing temperature associated with  
thermistor FP1. Note that the FP1 thermistor is located on  
the refrigerant line between the coaxial heat exchanger and  
expansion device (TXV). Therefore, FP1 is sensing refrigerant  
temperature, not water temperature, which is a better indication  
of how water flow rate/temperature is affecting the refrigeration  
circuit.  
Figure 22a: HTS Low Voltage Field Wiring  
The factory setting for FP1 is for systems using water (30°F  
[-1.1°C] refrigerant temperature). In low water temperature  
(extended range) applications with antifreeze (most ground  
loops), jumper JW3 should be clipped as shown in Figure  
23 to change the setting to 10°F [-12.2°C] refrigerant  
temperature, a more suitable temperature when using  
an antifreeze solution. All residential units include water/  
refrigerant circuit insulation to prevent internal condensation,  
which is required when operating with entering water  
temperatures below 59°F [15°C].  
Low voltage  
field wiring  
Figure 22b: HSS Low Voltage Field Wiring  
Capacitor  
Circ Brkr  
LoopPB1  
HWG PB2  
Grnd  
Contactor-CC  
L1  
L2  
BR  
CXM Contro l  
Low Voltage  
Connector  
27  
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Electrical - LowVoltageWiring  
Figure 23: FP1 Limit Setting  
electromechanical thermostat. Therefore, only relay or triac  
based thermostats should be used.  
Two-stage HTS Units  
Two-stage units should be designed with two parallel valves  
for ground water applications to limit water use during first  
stage operation. For example, at 1.5 gpm/ton [2.0 l/m per  
kW], a model 049 unit requires 6 gpm [23 l/m] for full load  
(2nd stage) operation, but only 4 gpm [15 l/m] during 1st  
stage operation. Since the unit will operate on first stage  
80-90% of the time, significant water savings can be realized  
by using two parallel solenoid valves with two flow regulators.  
In the example above, stage one solenoid would be installed  
with a 4 gpm [15 l/m] flow regulator on the outlet, while stage  
two would utilize a 2 gpm [8 l/m] flow regulator. When stage  
one is operating, the second solenoid valve will be closed.  
When stage two is operating, both valves will be open,  
allowing full load flow rate.  
JW3-FP1 jumper  
should be clipped  
for low temperature  
operation  
CXM PCB  
Accessory Connections  
A terminal paralleling the compressor contactor coil has been  
provided on the CXM control. Terminal “A” is designed to  
control accessory devices, such as water valves. Note: This  
terminal should be used only with 24 Volt signals and not  
line voltage. Terminal “A” is energized with the compressor  
contactor. See Figure 24 or the specific unit wiring diagram  
for details.  
Figure 27 illustrates piping for two-stage solenoid valves.  
Review figures 24-26 for wiring of stage one valve. Stage two  
valve should be wired between “Y2” (compressor solenoid  
-- wire nut connection) and terminal “C.” NOTE: When EWT  
is below 50°F [10°C], a minimum of 2 gpm per ton (2.6 l/m  
per kW) is required.  
Figure 24: Accessory Wiring  
Figure 25: AMV Valve Wiring  
2
AMV  
Taco Valve  
3
1
Heater Switch  
Water Solenoid Valves - “Indoor” Compressor  
Section Only  
An external solenoid valve(s) should be used on ground  
water installations to shut off flow to the unit when the  
compressor is not operating. A slow closing valve may be  
required to help reduce water hammer. Figure 24 shows  
typical wiring for a 24VAC external solenoid valve. Figures  
25 and 26 illustrate typical slow closing water control valve  
wiring for Taco 500 series (HCI P/N AVM…) and Taco ESP  
series valves. Slow closing valves take approximately  
60 seconds to open (very little water will flow before 45  
seconds). Once fully open, an end switch allows the  
compressor to be energized. Only relay or triac based  
electronic thermostats should be used with slow closing  
valves. When wired as shown, the slow closing valve will  
operate properly with the following notations:  
Thermostat  
Figure 26: Taco SBV Valve Wiring  
1. The valve will remain open during a unit lockout.  
2. The valve will draw approximately 25-35 VA through the  
“Y” signal of the thermostat.  
Note: This valve can overheat the anticipator of an  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
28  
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Electrical - LowVoltageWiring  
Figure 27: Two-Stage HTS Piping  
x CAUTION! x  
CAUTION! Refrigerant pressure activated water regulating  
valves should never be used with HCI equipment.  
Figure 28b: Typical Thermostat Wiring, HSS Single-Stage  
Units (2 Heat/1 Cool)  
x CAUTION! x  
CAUTION! Many units installed with a factory or field supplied  
manual or electric shut-off valve. DAMAGE WILL OCCUR if  
shut-off valve is closed during unit operation. A high pressure  
switch must be installed on the heat pump side of any field  
provided shut-off valves and connected to the heat pump  
controls in series with the built-in refrigerant circuit high  
pressure switch to disable compressor operation if water  
pressure exceeds pressure switch setting. The field installed  
high pressure switch shall have a cut-out pressure of 235 psig  
and a cut-in pressure of 190 psig. This pressure switch can  
be ordered from HCI with a 1/4” internal flare connection as  
part number 39B0005N01.  
ELECTRICAL - THERMOSTAT WIRING  
Thermostat Installation  
The thermostat should be located on an interior wall in a  
larger room, away from supply duct drafts. DO NOT locate  
the thermostat in areas subject to sunlight, drafts or on  
external walls. The wire access hole behind the thermostat  
may in certain cases need to be sealed to prevent erroneous  
temperature measurement. Position the thermostat back  
plate against the wall so that it appears level and so the  
thermostat wires protrude through the middle of the back  
plate. Mark the position of the back plate mounting holes and  
drill holes with a 3/16” (5mm) bit. Install supplied anchors  
and secure plate to the wall. Thermostat wire must be 18  
AWG wire. Wire the appropriate thermostat as shown in  
Figures 28a and 28b to the low voltage terminal strip on the  
CXM control board. Practically any heat pump thermostat will  
work with these units, provided it has the correct number of  
heating and cooling stages.  
Figure 28a: Typical Thermostat Wiring, Two-Stage HTS  
Units (3 Heat/2 Cool)  
29  
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
CXM Controls  
CXM Control  
terminal will continuously output the last fault code of  
For detailed control information, see CXM Application,  
Operation and Maintenance (IOM) manual.  
the controller. If set to “EH2 normal,” EH2 will operate as  
standard electric heat output.  
On = EH2 Normal. Off = DDC Output at EH2.  
NOTE: Some CXM controls only have a 2 position DIP switch  
package. If this is the case, this option can be selected by  
clipping the jumper which is in position 4  
of SW1.  
Jumper not clipped = EH2 Normal. Jumper clipped = DDC  
Output at EH2.  
DIP switch 5: Factory Setting - Normal position is “On.” Do  
not change selection unless instructed to do so by  
the factory.  
Field Selectable Inputs  
Test mode: Test mode allows the service technician to check  
the operation of the control in a timely manner. By momentarily  
shorting the test terminals, the CXM control enters a 20  
minute test mode period in which all time delays are sped up  
15 times. Upon entering test mode, the status LED will flash  
a code representing the last fault. For diagnostic ease at the  
thermostat, the alarm relay will also cycle during test mode.  
The alarm relay will cycle on and off similar to the status LED  
to indicate a code representing the last fault, at the thermostat.  
Test mode can be exited by shorting the test terminals for 3  
seconds.  
-Slow Flash = 1 flash every 2 seconds  
-Fast Flash = 2 flashes every 1 second  
-Flash code 2 = 2 quick flashes, 10 second pause, 2 quick  
flashes, 10 second pause, etc.  
Retry Mode: If the control is attempting a retry of a fault, the  
status LED will slow flash (slow flash = one flash every 2  
seconds) to indicate the control is in the process of retrying.  
-On pulse 1/3 second; off pulse 1/3 second  
Table 9a: CXM LED And Alarm  
Relay Operations  
Field Configuration Options  
Note: In the following field configuration options, jumper wires  
should be clipped ONLY when power is removed from the  
CXM control.  
Water coil low temperature limit setting: Jumper 3 (JW3-  
FP1 Low Temp) provides field selection of temperature limit  
setting for FP1 of 30°F or 10°F [-1°F or -12°C] (refrigerant  
temperature).  
Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].  
Air coil low temperature limit setting: Jumper 2 (JW2-FP2  
Low Temp) provides field selection of temperature limit  
setting for FP2 of 30°F or 10°F [-1°F or -12°C] (refrigerant  
temperature). Note: This jumper should only be clipped  
under extenuating circumstances, as recommended by  
the factory.  
Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].  
Alarm relay setting: Jumper 1 (JW1-AL2 Dry) provides field  
selection of the alarm relay terminal AL2 to be jumpered to  
24VAC or to be a dry contact (no connection).  
Not Clipped = AL2 connected to R. Clipped = AL2 dry contact  
(no connection).  
DIP Switches  
Note: In the following field configuration options, DIP  
switches should only be changed when power is removed  
from the CXM control.  
DIP switch 1: Unit Performance Sentinel Disable - provides  
field selection to disable the UPS feature.  
On = Enabled. Off = Disabled.  
DIP switch 2: Stage 2 Selection - provides selection of  
whether compressor has an “on” delay. If set to stage 2, the  
compressor will have a 3 second delay before energizing.  
Also, if set for stage 2, the alarm relay will NOT cycle during  
test mode.  
On = Stage 1. Off = Stage 2  
DIP switch 3: Not Used.  
DIP switch 4: DDC Output at EH2 - provides selection for  
DDC operation. If set to “DDC Output at EH2,” the EH2  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
30  
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
CXM Controls  
Safety Features – CXM Control  
must be below the selected low temperature limit setting for  
30 continuous seconds during a compressor run cycle to be  
recognized as a FP2 fault. The FP2 input is bypassed for the  
initial 60 seconds of a compressor run cycle. FP2 is set at the  
factory for one try. Therefore, the control will go into lockout mode  
once the FP2 fault has occurred.  
The safety features below are provided to protect the  
compressor, heat exchangers, wiring and other components  
from damage caused by operation outside of design  
conditions.  
Anti-short cycle protection: The control features a 5 minute  
anti-short cycle protection for the compressor.  
FP2 lockout code = 5  
Condensate overflow: The condensate overflow sensor  
must sense overflow level for 30 continuous seconds to  
be recognized as a CO fault. Condensate overflow will be  
monitored at all times.  
Note: The 5 minute anti-short cycle also occurs at power up.  
Random start: The control features a random start upon power  
up of 5-80 seconds.  
CO lockout code = 6  
Fault Retry: In Fault Retry mode, the Status LED begins slowly  
flashing to signal that the control is trying to recover from a  
fault input. The control will stage off the outputs and then “try  
again” to satisfy the thermostat input call. Once the thermostat  
input call is satisfied, the control will continue on as if no fault  
occurred. If 3 consecutive faults occur without satisfying the  
thermostat input call, the control will go into “lockout” mode.  
The last fault causing the lockout will be stored in memory and  
can be viewed by going into test mode. Note: FP1/FP2 faults  
are factory set at only one try.  
Over/under voltage shutdown: An over/under voltage condition  
exists when the control voltage is outside the range of 19VAC  
to 30VAC. Over/under voltage shut down is a self-resetting  
safety. If the voltage comes back within range for at least 0.5  
seconds, normal operation is restored. This is not considered  
a fault or lockout. If the CXM is in over/under voltage shutdown  
for 15 minutes, the alarm relay will close.  
Over/under voltage shut down code = 7  
Unit Performance Sentinel-UPS (patent pending): The UPS  
feature indicates when the heat pump is operating inefficiently.  
A UPS condition exists when:  
Lockout: In lockout mode, the status LED will begin fast  
flashing. The compressor relay is turned off immediately.  
Lockout mode can be “soft” reset by turning off the thermostat  
(or satisfying the call). A “soft” reset keeps the fault in memory  
but resets the control. A “hard” reset (disconnecting power to  
the control) resets the control and erases fault memory.  
Lockout with emergency heat: While in lockout mode, if W  
becomes active (CXM), emergency heat mode will occur.  
High pressure switch: When the high pressure switch opens due  
to high refrigerant pressures, the compressor relay is de-energized  
immediately since the high pressure switch is in series with the  
compressor contactor coil. The high pressure fault recognition is  
immediate (does not delay for 30 continuous seconds before de-  
energizing the compressor).  
a) In heating mode with compressor energized, FP2 is  
greater than 125°F [52°C] for 30 continuous seconds, or:  
b) In cooling mode with compressor energized, FP1 is  
greater than 125°F [52°C] for 30 continuous seconds, or:  
c) In cooling mode with compressor energized, FP2 is less  
than 40°F [4.5°C] for 30 continuous seconds. If a UPS  
condition occurs, the control will immediately go to UPS  
warning. The status LED will remain on as if the control  
is in normal mode. Outputs of the control, excluding LED  
and alarm relay, will NOT be affected by UPS. The UPS  
condition cannot occur during a compressor off cycle.  
During UPS warning, the alarm relay will cycle on and  
off. The cycle rate will be “on” for 5 seconds, “off” for 25  
seconds, “on” for 5 seconds, “off” for 25 seconds, etc.  
UPS warning code = 8  
Swapped FP1/FP2 thermistors: During test mode, the control  
monitors to see if the FP1 and FP2 thermistors are in the  
appropriate places. If the control is in test mode, the control will  
lockout, with code 9, after 30 seconds if:  
a) The compressor is on in the cooling mode and the FP1  
sensor is colder than the FP2 sensor, or:  
b) The compressor is on in the heating mode and the FP2  
sensor is colder than the FP1 sensor.  
Swapped FP1/FP2 thermistor code = 9.  
High pressure lockout code = 2  
Example: 2 quick flashes, 10 sec pause, 2 quick flashes, 10  
sec. pause, etc.  
Low pressure switch: The low pressure switch must be open and  
remain open for 30 continuous seconds during “on” cycle to be  
recognized as a low pressure fault. If the low pressure switch  
is open for 30 seconds prior to compressor power up it will be  
considered a low pressure (loss of charge) fault. The low pressure  
switch input is bypassed for the initial 60 seconds of a compressor  
run cycle.  
Diagnostic Features  
Low pressure lockout code = 3  
The LED on the CXM board advises the technician of the  
current status of the CXM control. The LED can display either  
the current CXM mode or the last fault in memory if in test  
mode. If there is no fault in memory, the LED will flash Code 1  
(when in test mode).  
Water coil low temperature (FP1): The FP1 thermistor  
temperature must be below the selected low temperature limit  
setting for 30 continuous seconds during a compressor run cycle  
to be recognized as a FP1 fault. The FP1 input is bypassed for  
the initial 60 seconds of a compressor run cycle. FP1 is set at the  
factory for one try. Therefore, the control will go into lockout mode  
once the FP1 fault has occurred.  
FP1 lockout code = 4  
Air coil low temperature (FP2): The FP2 thermistor temperature  
31  
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
32  
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
CXM Controls  
CXM Control Start-up Operation  
The control will not operate until all inputs and safety controls  
are checked for normal conditions. The compressor will have a  
5 minute anti-short cycle delay at power-up. The first time after  
power-up that there is a call for compressor, the compressor will  
follow a 5 to 80 second random start delay. After the random  
start delay and anti-short cycle delay, the compressor relay will  
be energized. On all subsequent compressor calls, the random  
start delay is omitted.  
Table 9b: Unit Operation  
HTS  
HSS  
HSS  
T-stat signal  
Variable Speed  
Air Handler  
Variable Speed  
Air Handler  
PSC Air Handler  
G
Fan only  
Fan only  
Fan only  
Stage 1 heating5  
Stage 2 heating5  
N/A  
G, Y or Y1  
G, Y1, Y2  
G, Y1, Y2, W  
G, W  
Stage 1 heating1  
Stage 2 heating1  
Stage 3 heating1  
Emergency heat  
Stage 1 cooling2  
Stage 2 cooling2  
Stage 1 heating3  
Stage 2 heating3  
Stage 3 heating3  
Emergency heat  
Stage 1 cooling4  
Stage 2 cooling4  
Emergency heat  
Cooling6  
G, Y or Y1, O  
G, Y1, Y2, O  
N/A  
1
Stage 1 = 1st stage compressor, 1st stage fan operation  
Stage 2 = 2nd stage compressor, 2nd stage fan operation  
Stage 3 = 2nd stage compressor, auxiliary electric heat, 2nd  
or 3rd stage fan operation (depending on fan settings)  
2
3
Stage 1 = 1st stage compressor, 1st stage fan operation, reversing valve  
Stage 2 = 2nd stage compressor, 2nd stage fan operation, reversing valve  
Stage 1 = compressor, 1st stage fan operation  
Stage 2 = compressor, 2nd stage fan operation  
Stage 3 = compressor, auxiliary electric heat, 2nd or 3rd stage fan operation (depending on fan settings)  
Stage 1 = compressor, 1st stage fan operation, reversing valve  
Stage 2 = compressor, 2nd stage fan operation, reversing valve  
Stage 1 = compressor, fan  
Stage 2 = compressor, auxiliary electric heat, fan  
Cooling = compressor, fan, reversing valve  
4
5
6
33  
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
CXM Controls  
Table 10: Nominal resistance at  
various temperatures  
CXM Thermostat Details  
Thermostat Compatibility - Most all heat pump thermostats  
can be used with the CXM control. However Heat/Cool stats  
are NOT compatible with the CXM.  
ϒ
ϒ
ϒ
ϒ
Anticipation Leakage Current - Maximum leakage current  
for "Y" is 50 mA and for "W" is 20mA. Triacs can be used  
if leakage current is less than above. Thermostats with  
anticipators can be used if anticipation current is less than  
that specified above.  
Thermostat Signals -  
• "Y" and "W" have a 1 second recognition time when  
being activated or being removed.  
• "O" and "G" are direct pass through signals but are  
monitored by the micro processor.  
• "R" and "C" are from the transformer.  
• "AL1" and "AL2" originate from the alarm relay.  
• "A" is paralleled with the compressor output for use  
with well water solenoid valves.  
• The "Y" 1/4" quick connect is a connection point to the  
"Y" input terminal P1 for factory use. This "Y" terminal  
can be used to drive panel mounted relays such as the  
loop pump relay.  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
34  
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Unit Starting and Operating Conditions  
Operating Limits  
2. Voltage utilization range complies with ARI  
Standard 110.  
Environment – “Indoor” compressor section is designed for  
indoor installation only. Never install “indoor” compressor  
section in areas subject to freezing or where humidity levels  
could cause cabinet condensation (such as unconditioned  
spaces subject to 100% outside air). “Outdoor” unit is designed  
for conditions where ambient air is below freezing (see Table  
11).  
Determination of operating limits is dependent primarily upon  
three factors: 1) return air temperature. 2) water temperature,  
and 3) ambient temperature. When any one of these factors  
is at minimum or maximum levels, the other two factors  
should be at normal levels to insure proper unit operation.  
Power Supply – A voltage variation of +/– 10% of nameplate  
utilization voltage is acceptable.  
Extreme variations in temperature and humidity and/or  
corrosive water or air will adversely affect unit performance,  
reliability, and service life.  
Starting Conditions  
Consult Table 11 for the particular model. Starting conditions  
vary depending upon model and are based upon the  
following notes:  
Notes:  
1. Conditions in Table 11 are not normal or continuous  
operating conditions. Minimum/maximum limits are start-  
up conditions to bring the building space up to occupancy  
temperatures. Units are not designed to operate under  
these conditions on a regular basis.  
Table 11: Unit Operation  
HTS/HSS  
Operating Limits  
Cooling  
Heating  
Air Limits  
Min. ambient air, DB  
Rated ambient air, DB  
Max. ambient air, DB  
Min. entering air, DB/WB  
Rated entering air, DB/WB  
Max. entering air, DB/WB  
Water Limits  
45°F [7°C]  
80.6°F [27°C]  
39°F [4°C]  
68°F [20°C]  
85°F [29°C]  
40°F [4.5°C]  
68°F [20°C]  
80°F [27°C]  
110°F [43°C]  
50°F [10°C]  
80.6/66.2°F [27/19°C]  
110/83°F [43/28°C]  
Min. entering water  
30°F [-1°C]  
50-110°F [10-43°C]  
120°F [49°C]  
20°F [-6.7°C]  
30-70°F [-1 to 21°C]  
90°F [32°C]  
Normal entering water  
Max. entering water  
1.5 to 3.0 gpm/ton  
Normal water flow  
2.0 to 3.9 l/m per kW  
35  
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Unit Starting and Operating Conditions  
Unit and System Checkout  
BEFORE POWERING SYSTEM, please check the following:  
System controls: Verify that system controls function and  
operate in the proper sequence.  
Low water temperature cutout: Verify that low water  
temperature cut-out controls are set properly  
(FP1 - JW3).  
UNIT CHECKOUT  
Balancing/shutoff valves: Insure that all isolation valves  
are open and water control valves are wired.  
Line voltage and wiring: Verify that voltage is within  
an acceptable range for the unit and wiring and fuses/  
breakers are properly sized. Verify that low voltage wiring  
is complete.  
Miscellaneous: Note any questionable aspects of  
the installation.  
x CAUTION! x  
Unit control transformer: Insure that transformer has the  
properly selected voltage tap. Residential 208-230V units  
are factory wired for 230V operation unless specified  
otherwise.  
Loop/water piping is complete and purged of air. Water/  
piping is clean.  
CAUTION! Verify that ALL water control valves are open  
and allow water flow prior to engaging the compressor.  
Freezing of the coax or water lines can permanently  
damage the heat pump.  
Antifreeze has been added if necessary.  
NOTICE! Failure to remove shipping  
Entering water and air: Insure that entering water and air  
temperatures are within operating limits of Table 7.  
Low water temperature cutout: Verify that low water  
temperature cut-out on the CXM control is properly set.  
Unit fan: Manually rotate fan to verify free rotation and  
insure that blower wheel is secured to the motor shaft.  
Be sure to remove any shipping supports if needed.  
DO NOT oil motors upon start-up. Fan motors are pre-  
oiled at the factory. Check unit fan speed selection and  
compare to design requirements.  
Condensate line: Verify that condensate line is open and  
properly pitched toward drain.  
HWG pump is disconnected unless piping is completed  
and air has been purged from the system.  
Water flow balancing: Record inlet and outlet water  
temperatures for each heat pump upon startup. This  
check can eliminate nuisance trip outs and high velocity  
water flow that could erode heat exchangers.  
Unit air coil and filters: Insure that filter is clean and  
accessible. Clean air coil of all manufacturing oils.  
Unit controls: Verify that CXM field selection options are  
properly set. Low voltage wiring is complete.  
Blower speed is set.  
brackets from spring-mounted compressors  
will cause excessive noise, and could cause  
component failure due to added vibration.  
x CAUTION! x  
CAUTION! To avoid equipment damage, DO NOT  
leave system filled in a building without heat during the  
winter unless antifreeze is added to the water loop. Heat  
exchangers never fully drain by themselves and will freeze  
unless winterized with antifreeze.  
Unit Start-up Procedure  
1. Turn the thermostat fan position to “ON.” Blower should  
start.  
2. Balance air flow at registers.  
3. Adjust all valves to their full open position. Turn on the  
line power to all heat pump units.  
4. Room temperature should be within the minimum-  
maximum ranges of Table 11. During start-up checks,  
loop water temperature entering the heat pump should  
be between 30°F [-1°C] and 95°F [35°C].  
5. Two factors determine the operating limits of water  
source heat pumps, (a) return air temperature, and (b)  
water temperature. When any one of these factors is at a  
minimum or maximum level, the other factor must be at  
normal level to insure proper unit operation.  
a. Adjust the unit thermostat to the warmest setting.  
Place the thermostat mode switch in the “COOL”  
position. Slowly reduce thermostat setting until the  
compressor activates.  
Service/access panels are in place.  
SYSTEM CHECKOUT  
System water temperature: Check water temperature  
for proper range and also verify heating and cooling set  
points for proper operation.  
System pH: Check and adjust water pH if necessary to  
maintain a level between 6 and 8.5. Proper pH promotes  
longevity of hoses and fittings (see Table 3).  
System flushing: Verify that all air is purged from the  
system. Air in the system can cause poor operation or  
system corrosion. Water used in the system must be  
potable quality initially and clean of dirt, piping slag,  
and strong chemical cleaning agents. Some antifreeze  
solutions may require distilled water.  
b. Check for cool air delivery at the unit grille within a  
few minutes after the unit has begun to operate.  
Note: Units have a five minute time delay in the  
control circuit that can be eliminated on the CXM  
control board as shown below in Figure 29. See  
controls description for details.  
Flow Controller pump(s): Verify that the pump(s) is wired  
and in operating condition.  
c. Verify that the compressor is on and that the water  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
36  
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Unit Start-Up Procedure  
flow rate is correct by measuring pressure drop  
through the heat exchanger using the P/T plugs and  
comparing to Tables 12a through 12b.  
(see troubleshooting section). If the check described fails  
to reveal the problem and the unit still does not operate,  
contact a trained service technician to insure proper  
diagnosis and repair of the equipment.  
d. Check the elevation and cleanliness of the  
condensate lines. Dripping may be a sign of a  
blocked line. Check that the condensate trap is filled  
to provide a water seal.  
8. When testing is complete, set system to maintain  
desired comfort level.  
9. BE CERTAIN TO FILL OUT AND RETURN ALL  
WARRANTY REGISTRATION PAPERWORK.  
e. Refer to Table 13. Check the temperature of both  
entering and leaving water. If temperature is within  
range, proceed with the test. If temperature is outside  
of the operating range, check refrigerant pressures  
and compare to Tables 14 and 15. Verify correct  
water flow by comparing unit pressure drop across  
the heat exchanger versus the data in Tables 12a  
through 12b. Heat of rejection (HR) can be calculated  
and compared to catalog data capacity pages. The  
formula for HR for systems with water is as follows:  
HR = TD x GPM x 500, where TD is the temperature  
difference between the entering and leaving water,  
and GPM is the flow rate in U.S. GPM, determined  
by comparing the pressure drop across the heat  
exchanger to Tables 12a through 12b.  
Note: If performance during any mode appears abnormal,  
refer to the CXM section or troubleshooting section of this  
manual. To obtain maximum performance, the air coil should  
be cleaned before start-up. A 10% solution of dishwasher  
detergent and water is recommended.  
x WARNING! x  
WARNING! When the disconnect switch is closed, high  
voltage is present in some areas of the electrical panel.  
Exercise caution when working with energized equipment.  
f. Check air temperature drop across the air coil when  
compressor is operating. Air temperature drop should  
be between 15°F and 25°F [8°C and 14°C].  
x CAUTION! x  
CAUTION! Verify that ALL water control valves are open  
and allow water flow prior to engaging the compressor.  
Freezing of the coax or water lines can permanently damage  
the heat pump.  
g. Turn thermostat to “OFF” position. A hissing noise  
indicates proper functioning of the reversing valve.  
6. Allow five (5) minutes between tests for pressure to  
equalize before beginning heating test.  
a. Adjust the thermostat to the lowest setting. Place the  
thermostat mode switch in the “HEAT” position.  
b. Slowly raise the thermostat to a higher temperature  
until the compressor activates.  
c. Check for warm air delivery within a few minutes after  
the unit has begun to operate.  
Figure 29: Test Mode Pins  
Short test pins together  
to enter Test Mode and  
speed-up timing and delays  
for 20 minutes.  
d. Refer to Table 13. Check the temperature of both  
entering and leaving water. If temperature is within  
range, proceed with the test. If temperature is outside  
of the operating range, check refrigerant pressures  
and compare to Tables 14 and 15 Verify correct water  
flow by comparing unit pressure drop across the heat  
exchanger versus the data in Tables 12a through  
12b. Heat of extraction (HE) can be calculated and  
compared to submittal data capacity pages. The  
formula for HE for systems with water is as follows:  
HE = TD x GPM x 500, where TD is the temperature  
difference between the entering and leaving water,  
and GPM is the flow rate in U.S. GPM, determined  
by comparing the pressure drop across the heat  
exchanger to Tables 12a through 12b.  
e. Check air temperature rise across the air coil when  
compressor is operating. Air temperature rise should  
be between 20°F and 30°F [11°C and 17°C].  
f. Check for vibration, noise, and water leaks.  
7. If unit fails to operate, perform troubleshooting analysis  
37  
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Unit Operating Conditions  
Table 12a: Two-Stage HTS R-410A Compressor Section  
Coax Water Pressure Drop  
Table 13: Water Temperature Change Through Heat  
Exchanger  
Pressure Drop (psi)  
���  
 
�����  
 
Model  
024  
GPM  
 
�  
30°F  
50°F  
70°F  
90°F  
 
�  
 
�  
4.0  
6.0  
7.0  
8.0  
1.5  
3.1  
4.1  
5.1  
1.3  
2.6  
3.4  
4.3  
1.1  
2.3  
3.0  
3.8  
1.0  
2.1  
2.7  
3.4  
���  
�  
�  
���  
�  
�  
4.0  
6.0  
8.0  
9.0  
1.2  
2.6  
4.5  
5.7  
1.0  
2.5  
4.2  
5.2  
0.8  
2.3  
4.0  
4.8  
0.6  
2.1  
3.7  
4.4  
036  
048  
060  
5.5  
8.3  
11.0  
12.0  
1.1  
2.2  
3.9  
4.5  
0.9  
2.1  
3.6  
4.2  
0.8  
2.0  
3.2  
3.8  
0.7  
1.8  
3.1  
3.5  
7.0  
0.5  
1.9  
3.9  
4.8  
0.3  
1.8  
3.5  
4.3  
0.2  
1.7  
3.2  
3.9  
0.1  
1.6  
2.9  
3.5  
10.5  
14.0  
15.0  
Table 12b: R-22 HSS Compressor Section Coax Water  
Pressure Drop  
Pressure Drop (psi)  
Model  
018  
GPM  
30°F  
50°F  
70°F  
90°F  
2
4
5
6
0.6  
1.6  
2.1  
2.8  
0.6  
1.4  
2.0  
2.6  
0.5  
1.3  
1.8  
2.4  
0.5  
1.3  
1.7  
2.3  
3
5
6
8
0.6  
1.3  
1.8  
2.9  
0.6  
1.2  
1.7  
2.7  
0.5  
1.1  
1.5  
2.5  
0.5  
1.1  
1.4  
2.3  
024  
030  
036  
042  
048  
060  
4
6
8
0.9  
1.8  
2.9  
4.2  
0.9  
1.7  
2.7  
3.9  
0.8  
1.5  
2.5  
3.6  
0.8  
1.4  
2.3  
3.4  
10  
5
7
9
1.6  
2.6  
3.9  
6.4  
1.4  
2.4  
3.7  
5.9  
1.3  
2.3  
3.4  
5.5  
1.3  
2.1  
3.2  
5.2  
12  
6
8
11  
13  
2.1  
3.2  
5.5  
7.3  
1.9  
3.0  
5.1  
6.8  
1.8  
2.8  
4.7  
6.3  
1.7  
2.6  
4.5  
5.9  
6
9
12  
15  
2.1  
3.9  
6.4  
9.4  
1.9  
3.7  
5.9  
8.7  
1.8  
3.4  
5.5  
8.1  
1.7  
3.2  
5.2  
7.6  
8
1.2  
2.1  
3.6  
5.0  
1.2  
2.0  
3.4  
4.7  
1.1  
1.8  
3.1  
4.3  
1.0  
1.7  
2.9  
4.1  
11  
15  
18  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
38  
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Unit Operating Conditions  
Table 14a: Size 024 HTS Two-Stage R-410A Typical Unit Operating Pressures and Temperatures  
Full Load Cooling - without HWG active  
Discharge  
Full Load Heating - without HWG active  
Discharge  
Water  
Flow  
GPM/  
ton  
Entering  
Water  
Temp °F  
Suction  
Pressure  
PSIG  
Air Temp  
Drop °F  
DB  
Suction  
Pressure  
PSIG  
Air Temp  
Rise °F  
DB  
Super-  
heat  
Sub-  
Water Temp  
Rise °F  
Super-  
heat  
Sub-  
Water Temp  
Drop °F  
Pressure  
PSIG  
Pressure  
PSIG  
cooling  
cooling  
1.5  
2.25  
3
122-132  
122-132  
122-132  
159-179  
146-166  
132-152  
13-18  
13-18  
14-19  
9-14  
7-12  
7-12  
16.7-18.7  
12.3-14.3  
7.9-9.9  
18-24  
19-25  
19-25  
77-87  
79-89  
82-92  
278-298  
280-300  
282-302  
4-9  
4-9  
4-9  
10-15  
10-15  
10-15  
5.9-7.9  
4.2-6.2  
2.7-4.7  
18-24  
19-25  
20-26  
30  
50  
1.5  
2.25  
3
132-142  
132-142  
132-142  
186-206  
172-192  
158-178  
8-13  
8-13  
8-13  
8-13  
6-11  
6-11  
16.3-18.3  
12.1-14.1  
7.8-9.8  
18-24  
19-25  
19-25  
107-117  
111-121  
115-125  
314-334  
315-335  
317-337  
6-11  
6-11  
6-11  
13-18  
13-18  
13-18  
8.9-10.9  
6.7-8.7  
4.5-6.5  
25-31  
26-32  
26-32  
1.5  
2.25  
3
139-149  
139-149  
139-149  
281-301  
267-287  
253-273  
7-12  
7-12  
7-12  
8-13  
8-13  
7-12  
15.7-17.7  
11.6-13.6  
7.6-9.6  
18-24  
18-24  
18-24  
139-149  
145-155  
152-162  
350-370  
352-372  
354-374  
7-12  
7-12  
7-12  
15-20  
15-20  
15-20  
11.3-13.3  
8.5-10.5  
5.8-7.8  
31-38  
32-39  
32-39  
70  
1.5  
2.25  
3
141-151  
141-151  
141-151  
374-394  
360-380  
346-366  
7-12  
7-12  
7-12  
9-14  
9-14  
8-13  
14.6-16.6  
10.7-12.7  
6.9-8.9  
17-23  
17-23  
17-23  
177-187  
181-191  
186-196  
392-412  
397-417  
402-422  
9-14  
10-15  
11-16  
17-22  
17-22  
17-22  
14.4-16.4  
10.8-12.8  
7.1-9.1  
37-45  
38-46  
38-46  
90  
1.5  
2.25  
3
145-155  
145-155  
145-155  
473-493  
458-478  
441-461  
7-12  
7-12  
7-12  
10-15  
10-15  
9-14  
13.6-15.6  
9.9-11.9  
6.2-8.2  
16-22  
16-22  
16-22  
110  
Operation Not Recommended  
Table 14b: Size 036 HTS Two-Stage R-410A Typical Unit Operating Pressures and Temperatures  
Full Load Cooling - without HWG active  
Discharge  
Full Load Heating - without HWG active  
Discharge  
Water  
Flow  
GPM/  
ton  
Entering  
Water  
Temp °F  
Suction  
Pressure  
PSIG  
Air Temp  
Drop °F  
DB  
Suction  
Pressure  
PSIG  
Air Temp  
Rise °F  
DB  
Super-  
heat  
Sub-  
Water Temp  
Rise °F  
Super-  
heat  
Sub-  
Water Temp  
Drop °F  
Pressure  
PSIG  
Pressure  
PSIG  
cooling  
cooling  
1.5  
2.25  
3
122-132  
121-131  
121-131  
153-173  
145-165  
135-155  
18-23  
18-23  
18-23  
9-14  
8-13  
8-13  
22.1-24.1  
16.8-18.8  
10.5-12.5  
19-25  
20-26  
20-26  
71-81  
75-85  
78-88  
263-283  
267-287  
270-290  
5-10  
5-10  
5-10  
2-5  
2-5  
2-5  
8.1-10.1  
5.9-7.9  
3.7-5.7  
17-23  
18-24  
19-25  
30  
50  
1.5  
2.25  
3
131-141  
130-140  
130-140  
222-242  
208-228  
194-214  
13-18  
13-18  
14-19  
10-15  
9-14  
9-14  
21.9-23.9  
16.1-18.1  
10.3-12.3  
19-25  
20-26  
20-26  
103-113  
107-117  
112-122  
292-312  
296-316  
301-321  
6-11  
6-11  
6-11  
2.5-7  
2.5-7  
2.5-7  
11.5-13.5  
8.6-10.6  
5.7-7.7  
23-29  
24-30  
24-30  
1.5  
2.25  
3
138-148  
137-147  
137-147  
299-319  
280-300  
263-283  
8-13  
8-13  
8-13  
13-18  
12-17  
12-17  
21.5-23.5  
15.8-17.8  
10-12  
19-25  
20-26  
20-26  
134-144  
140-150  
146-156  
322-342  
328-358  
334-354  
7-12  
7-12  
7-12  
2.5-7  
2.5-7  
2.5-7  
14.5-16.5  
11.1-13.1  
7.7-9.7  
28-35  
29-36  
30-37  
70  
1.5  
2.25  
3
142-152  
142-152  
142-152  
388-408  
367-387  
347-367  
6-11  
7-12  
7-12  
13-18  
8-13  
8-13  
20.5-22.5  
14.9-16.9  
9.3-11.3  
18-24  
18-24  
18-24  
172-182  
184-194  
196-206  
360-380  
369-389  
378-398  
8-13  
8-13  
8-13  
2.5-7  
2.5-7  
2.5-7  
20.5-22.5  
15-17  
10-12  
36-44  
37-45  
39-47  
90  
1.5  
2.25  
3
147-157  
147-157  
147-157  
486-506  
465-475  
444-464  
6-11  
7-12  
7-12  
13-18  
8-13  
8-13  
19-21  
14-16  
9-11  
18-24  
18-24  
18-24  
110  
Operation Not Recommended  
Table 14c: Size 048 HTS Two-Stage R-410A Typical Unit Operating Pressures and Temperatures  
Full Load Cooling - without HWG active  
Discharge  
Full Load Heating - without HWG active  
Discharge  
Water  
Flow  
GPM/  
ton  
Entering  
Water  
Temp °F  
Suction  
Pressure  
PSIG  
Air Temp  
Drop °F  
DB  
Suction  
Pressure  
PSIG  
Air Temp  
Rise °F  
DB  
Super-  
heat  
Sub-  
Water Temp  
Rise °F  
Super-  
heat  
Sub-  
Water Temp  
Drop °F  
Pressure  
PSIG  
Pressure  
PSIG  
cooling  
cooling  
30  
30  
30  
1.5  
2.25  
3
112-122  
111-121  
111-121  
187-207  
167-187  
147-167  
18-23  
18-23  
18-23  
23-28  
21-26  
20-25  
20.7-22.7  
15.5-17.5  
10.2-12.2  
19-25  
19-25  
19-25  
66-76  
69-79  
72-82  
261-281  
264-284  
267-287  
8-13  
8-13  
8-13  
5-10  
5-10  
5-10  
8-10  
6-8  
4-6  
18-24  
19-25  
19-25  
50  
50  
50  
1.5  
2.25  
3
125-135  
123-133  
122-132  
245-265  
227-247  
208-228  
13-18  
13-18  
14-19  
19-24  
18-23  
16-21  
20.9-22.9  
15.6-17.6  
10.2-12.2  
20-26  
20-26  
20-26  
93-103  
98-108  
103-113  
289-309  
295-315  
301-321  
7-12  
7-12  
7-12  
5-10  
5-10  
5-10  
11.5-13.5  
8.7-10.7  
5.9-7.9  
23-29  
24-30  
25-31  
70  
70  
70  
1.5  
2.25  
3
133-143  
132-142  
131-141  
314-334  
294-314  
274-294  
9-14  
9-14  
10-15  
17-22  
16-21  
14-19  
20.5-22.5  
15.2-17.2  
9.9-11.9  
20-26  
20-26  
20-26  
123-133  
130-140  
137-147  
319-339  
329-349  
336-356  
7-12  
7-12  
7-12  
5-10  
5-10  
5-10  
15-17  
11.5-13.5  
7.9-9.9  
28-35  
29-36  
30-37  
90  
90  
90  
1.5  
2.25  
3
138-148  
137-147  
136-146  
401-421  
379-399  
357-377  
8-13  
8-13  
9-14  
16-21  
15-20  
13-18  
19.2-21.2  
14.3-16.3  
9.3-11.3  
19-25  
19-25  
19-25  
167-177  
177-187  
187-197  
365-385  
374-394  
388-408  
7-12  
7-12  
7-12  
5-10  
5-10  
5-10  
19.6-21.6  
15-17  
10.3-12.3  
37-45  
38-46  
39-47  
110  
110  
110  
1.5  
2.25  
3
144-154  
143-153  
142-152  
502-522  
477-497  
452-472  
8-13  
8-13  
9-14  
14-19  
13-18  
12-17  
18-20  
13.3-15.3  
8.5-10.5  
18-24  
18-24  
18-24  
Operation Not Recommended  
39  
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Unit Operating Conditions  
Table 14d: Size 060 HTS Two-Stage R-410A Typical Unit Operating Pressures and Temperatures  
Full Load Cooling - without HWG active  
Discharge  
Full Load Heating - without HWG active  
Discharge  
Water  
Flow  
GPM/  
ton  
Entering  
Water  
Temp °F  
Suction  
Pressure  
PSIG  
Air Temp  
Drop °F  
DB  
Suction  
Pressure  
PSIG  
Air Temp  
Rise °F  
DB  
Super-  
heat  
Sub-  
Water Temp  
Rise °F  
Super-  
heat  
Sub-  
Water Temp  
Drop °F  
Pressure  
PSIG  
Pressure  
PSIG  
cooling  
cooling  
1.5  
2.25  
3
117-127  
116-126  
115-125  
160-180  
133-153  
125-145  
16-21  
17-22  
18-23  
8-13  
6-11  
5-10  
17.5-19.5  
11.9-13.9  
6.3-8.3  
16-22  
16-22  
16-22  
66-76  
69-79  
72-82  
282-302  
285-305  
289-309  
9-15  
9-15  
9-15  
8-13  
8-13  
9-14  
8-10  
6-8  
4-6  
21-27  
21-27  
22-28  
30  
50  
1.5  
2.25  
3
126-136  
124-134  
123-133  
228-248  
212-232  
195-215  
8-13  
11-16  
14-19  
8-13  
6-11  
5-10  
19.8-21.8  
14.2-16.2  
8.5-10.5  
20-26  
20-26  
20-26  
95-105  
100-110  
105-115  
318-338  
321-341  
324-344  
9-15  
9-15  
9-15  
12-17  
12-17  
12-17  
11.3-13.3  
8.5-10.5  
5.7-7.7  
27-33  
28-34  
30-36  
1.5  
2.25  
3
130-140  
129-139  
128-138  
305-325  
286-306  
266-286  
8-13  
9-14  
11-16  
10-15  
9-14  
7-12  
20.3-22.3  
14.8-16.8  
9.3-11.3  
21-27  
21-27  
21-27  
128-138  
133-143  
139-149  
360-380  
364-384  
368-388  
8-14  
8-14  
8-14  
12-17  
12-17  
12-17  
14-16  
10.6-12.6  
7.3-9.3  
33-38  
34-40  
35-41  
70  
1.5  
2.25  
3
133-143  
132-142  
132-142  
398-418  
376-396  
354-374  
8-13  
8-13  
8-13  
10-15  
9-14  
7-12  
19.4-21.4  
14.1-16.1  
8.8-10.8  
20-26  
20-26  
20-26  
173-183  
177-187  
182-192  
407-427  
411-431  
415-435  
8-14  
8-14  
8-14  
13-18  
13-18  
14-19  
18.2-20.2  
13.9-15.9  
9.6-11.6  
42-50  
43-51  
44-52  
90  
1.5  
2.25  
3
138-148  
137-147  
136-146  
505-525  
483-503  
459-479  
6-11  
6-11  
6-11  
10-15  
9-14  
8-13  
18.3-20.3  
13.3-15.3  
8.3-10.3  
19-25  
19-25  
19-25  
110  
Operation Not Recommended  
Table 15: R-22 HSS Typical Unit Operating Pressures and Temperatures  
Full Load Cooling - without HWG active  
Full Load Heating - without HWG active  
Water  
Flow  
GPM/  
ton  
Entering  
Water  
Temp °F  
Suction  
Pressure  
PSIG  
Discharge  
Pressure  
PSIG  
Sub-  
cooling  
****  
Air Temp  
Drop °F  
DB  
Suction  
Pressure  
PSIG  
Discharge  
Pressure  
PSIG  
Sub-  
cooling  
****  
Air Temp  
Rise °F  
DB  
Super-  
heat  
Water Temp  
Rise *** °F  
Super-  
heat  
Water Temp  
Drop *** °F  
1.5  
2.3  
3
61-70  
62-71  
62-71  
100-117  
92-109  
88-104  
12-18  
12-18  
12-18  
12-22  
12-22  
12-22  
21-24  
13-16  
6-11  
21-26  
21-26  
21-26  
34-39  
37-42  
38-44  
163-183  
165-185  
167-186  
5-10  
5-10  
5-10  
5-9  
5-9  
5-9  
7.6-8.4  
4.8-5.6  
3.4-4.2  
14-20  
16-22  
16-22  
30  
50  
70  
90  
1.5  
2.3  
3
79-85  
75-83  
72-82  
145-170  
130-155  
125-150  
10-15  
10-15  
10-15  
9-16  
9-16  
9-16  
20-23  
12-15  
8-12  
20-25  
20-25  
20-25  
51-58  
53-62  
55-65  
175-202  
178-206  
180-208  
9-12  
9-12  
9-12  
8-12  
8-12  
8-12  
10.8-11.9  
6.7-8.1  
5.1-5.9  
23-29  
24-30  
25-31  
1.5  
2.3  
3
78-88  
78-90  
78-91  
180-200  
169-187  
160-180  
8-12  
8-12  
8-12  
7-12  
7-12  
7-12  
19-22  
11-14  
7-12  
19-24  
19-24  
19-24  
71-82  
77-89  
81-92  
215-250  
203-235  
200-235  
10-14  
10-14  
10-14  
6-10  
6-10  
6-10  
14.0-15.2  
9.0-10.2  
6.7-7.9  
28-34  
30-37  
31-38  
1.5  
2.3  
3
79-82  
80-93  
80-93  
230-272  
215-248  
208-240  
8-10  
8-10  
8-10  
7-11  
7-11  
7-11  
18-21  
10-14  
6-11  
17-23  
17-23  
17-23  
Operation Not Recommended  
* Based on Nominal 400 CFM per ton per circuit ariflow and 70°F EAT heating and 80/67°F cooling.  
** Cooling air and water numbers can vary greatly with changes in humidity.  
*** Water temperature difference based upon 1.5 - 3 GPM per ton of active circuit water flow.  
**** Using liquid line pressure.  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
40  
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Preventive Maintenance  
Water Coil Maintenance  
Condensate Drain  
(Direct ground water applications only)  
In areas where airborne bacteria may produce a “slimy”  
substance in the drain pan, it may be necessary to treat the  
drain pan chemically with an algaecide approximately every  
three months to minimize the problem. The condensate pan  
may also need to be cleaned periodically to insure indoor  
air quality. The condensate drain can pick up lint and dirt,  
especially with dirty filters. Inspect the drain twice a year to  
avoid the possibility of plugging and eventual overflow.  
If the system is installed in an area with a known high  
mineral content (125 P.P.M. or greater) in the water, it is  
best to establish a periodic maintenance schedule with the  
owner so the coil can be checked regularly. Consult the well  
water applications section of this manual for a more detailed  
water coil material selection. Should periodic coil cleaning  
be necessary, use standard coil cleaning procedures, which  
are compatible with the heat exchanger material and copper  
water lines. Generally, the more water flowing through the  
unit, the less chance for scaling. Therefore, 1.5 gpm per  
ton [2.0 l/m per kW] is recommended as a minimum flow.  
Minimum flow rate for entering water temperatures below  
50°F [10°C] is 2.0 gpm per ton [2.6 l/m per kW].  
Compressor  
Conduct annual amperage checks to insure that amp draw is  
no more than 10% greater than indicated on the serial plate  
data.  
Fan Motors  
Water Coil Maintenance  
Consult air handler I.O.M. for maintenance requirements.  
(All other water loop applications)  
Generally water coil maintenance is not needed for closed  
loop systems. However, if the piping is known to have  
high dirt or debris content, it is best to establish a periodic  
maintenance schedule with the owner so the water coil  
can be checked regularly. Dirty installations are typically  
the result of deterioration of iron or galvanized piping or  
components in the system. Open cooling towers requiring  
heavy chemical treatment and mineral buildup through water  
use can also contribute to higher maintenance. Should  
periodic coil cleaning be necessary, use standard coil  
cleaning procedures, which are compatible with both the  
heat exchanger material and copper water lines. Generally,  
the more water flowing through the unit, the less chance for  
scaling. However, flow rates over 3 gpm per ton (3.9 l/m per  
kW) can produce water (or debris) velocities that can erode  
the heat exchanger wall and ultimately produce leaks.  
Air Coil  
The air coil must be cleaned to obtain maximum  
performance. Check once a year under normal operating  
conditions and, if dirty, brush or vacuum clean. Care must  
be taken not to damage the aluminum fins while cleaning.  
CAUTION: Fin edges are sharp.  
Cabinet - “Indoor” Compressor Section  
Do not allow water to stay in contact with the cabinet for long  
periods of time to prevent corrosion of the cabinet sheet  
metal. Generally, cabinets are set up from the floor a few  
inches [7 - 8 cm] to prevent water from entering the cabinet.  
The cabinet can be cleaned using a mild detergent.  
Refrigerant System  
To maintain sealed circuit integrity, do not install service  
gauges unless unit operation appears abnormal. Reference  
the operating charts for pressures and temperatures. Verify  
that air and water flow rates are at proper levels before  
servicing the refrigerant circuit.  
Hot Water Generator Coils  
See water coil maintenance for ground water units. If the  
potable water is hard or not chemically softened, the high  
temperatures of the desuperheater will tend to scale even  
quicker than the water coil and may need more frequent  
inspections. In areas with extremely hard water, a HWG is  
not recommended.  
Filters  
Filters must be clean to obtain maximum performance. Filters  
should be inspected every month under normal operating  
conditions and be replaced when necessary. Units should  
never be operated without a filter.  
Washable, high efficiency, electrostatic filters, when dirty,  
can exhibit a very high pressure drop for the fan motor and  
reduce air flow, resulting in poor performance. It is especially  
important to provide consistent washing of these filters (in  
the opposite direction of the normal air flow) once per month  
using a high pressure wash similar to those found at self-  
serve car washes.  
41  
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Troubleshooting  
General  
Test Mode  
If operational difficulties are encountered, perform  
the preliminary checks below before referring to the  
troubleshooting charts.  
Test mode can be entered for 20 minutes by shorting the test  
pins. The CXM board will automatically exit test mode after  
20 minutes.  
• Verify that the unit is receiving electrical supply power.  
• Make sure the fuses in the fused disconnect switches  
are intact.  
CXM Troubleshooting Process Flowchart/Functional  
Troubleshooting Chart  
After completing the preliminary checks described above,  
inspect for other obvious problems such as leaking  
connections, broken or disconnected wires, etc. If everything  
appears to be in order, but the unit still fails to operate  
properly, refer to the “CXM Troubleshooting Process  
Flowchart” or “Functional Troubleshooting Chart.”  
The “CXM Troubleshooting Process Flowchart” is a quick  
overview of how to start diagnosing a suspected problem,  
using the fault recognition features of the CXM board. The  
“Functional Troubleshooting Chart” on the following page is  
a more comprehensive method for identifying a number of  
malfunctions that may occur, and is not limited to just the CXM  
controls. Within the chart are five columns:  
CXM Board  
• The “Fault” column describes the symptoms.  
• Columns 2 and 3 identify in which mode the fault is likey to  
occur, heating or cooling.  
• The “Possible Cause column” identifies the most likely  
sources of the problem.  
CXM board troubleshooting in general is best summarized  
as simply verifying inputs and outputs. After inputs and  
outputs have been verified, board operation is confirmed and  
the problem must be elsewhere. Below are some general  
guidelines for troubleshooting the CXM control.  
• The “Solution” column describes what should be done to  
correct the problem.  
Field Inputs  
All inputs are 24VAC from the thermostat and can be verified  
using a volt meter between C and Y, G, O, W. 24VAC will be  
present at the terminal (for example, between “Y” and “C”) if  
the thermostat is sending an input to the CXM board.  
x WARNING! x  
WARNING! HAZARDOUS VOLTAGE! DISCONNECT ALL  
ELECTRIC POWER INCLUDING REMOTE DISCONNECTS  
BEFORE SERVICING.  
Sensor Inputs  
All sensor inputs are ‘paired wires’ connecting each component  
to the board. Therefore, continuity on pressure switches, for  
example can be checked at the board connector.  
Failure to disconnect power before servicing can cause  
severe personal injury or death.  
The thermistor resistance should be measured with the  
connector removed so that only the impedance of the  
thermistor is measured. If desired, this reading can be  
compared to the thermistor resistance chart shown in  
the CXM IOM manual. An ice bath can be used to check  
calibration of the thermistor.  
Outputs  
The compressor relay is 24VAC and can be verified using a  
voltmeter. The fan signal is passed through the board to the  
external fan relay (units with PSC motors only). The alarm  
relay can either be 24VAC as shipped or dry contacts for use  
with DDC controls by clipping the JW1 jumper. Electric heat  
outputs are 24VDC “ground sinking” and require a volt meter  
set for DC to verify operation. The terminal marked “24VDC”  
is the 24VDC supply to the electric heat board; terminal “EH1”  
is stage 1 electric heat; terminal “EH2” is stage 2 electric heat.  
When electric heat is energized (thermostat is sending a “W”  
input to the CXM controller), there will be 24VDC between  
terminal “24VDC” and “EH1” (stage 1 electric heat) and/or  
“EH2” (stage 2 electric heat). A reading of 0VDC between  
“24VDC” and “EH1” or “EH2” will indicate that the CXM board  
is NOT sending an output signal to the electric heat board.  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
42  
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
CXM Process Flow Chart  
x WARNING! x  
WARNING! HAZARDOUS VOLTAGE! DISCONNECT ALL  
ELECTRIC POWER INCLUDING REMOTE DISCONNECTS  
BEFORE SERVICING.  
Failure to disconnect power before servicing can cause  
severe personal injury or death.  
43  
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
FunctionalTroubleshooting  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
44  
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
FunctionalTroubleshooting  
PerformanceTroubleshooting  
45  
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
Troubleshooting Form  
Note: Never connect refrigerant gauges during startup procedures. Conduct water-side analysis using P/T ports to determine water flow and  
temperature difference. If water-side analysis shows poor performance, refrigerant troubleshooting may be required. Connect refrigerant  
gauges as a last resort.  
Heat Controller, Inc. Water-Source Heating and Cooling Systems  
46  
The Quality Leader in Conditioning Air  
Residential Split - 60Hz R22 &R410A  
Rev.: 5 June, 2008  
47  
08/08  

Briggs Stratton 6 User Manual
Bryant 90 452 User Manual
Bryant 569D User Manual
BT Digital Baby Monitor Plus User Manual
Epson Printer SEPG00004 User Manual
Fisher Price M7933 User Manual
Fujitsu Air Conditioner 9368987046 User Manual
Fujitsu Automobile Accessories V5545 User Manual
GE AZ85E09EAC User Manual
HP Hewlett Packard AFICIO SP 8100DN User Manual