AIR HANDLER
INSTALLATION INSTRUCTIONS
HMG**F1E, HMG**X1E & HCG**V1E Series
IMPORTANT
Please read all information in this manual thoroughly and become familiar with the capabilities
and use of your appliance before attempting to operate or maintain this unit.These instructions
are primarily intended to assist qualified individuals experienced in the proper installation of
this appliance. Some local codes require licensed installation/service personnel for this type
of equipment. Improper installation,service,adjustment,or maintenance may cause explosion,
fire, electrical shock or other hazardous conditions which may result in personal injury or
property damage.
Unless otherwise noted in these instructions, only factory authorized kits or accessories may
be used with this product. Keep this manual where you have easy access to it in the future. If a
problemoccurs,checktheinstructionsandfollowrecommendationsgiven.Ifthesesuggestions
don’t eliminate your problem, call your servicing contractor.
DO NOT DESTROY. PLEASE READ CAREFULLY AND
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
IMPORTANT SAFETY INFORMATION
WARNING:
INSTALLER:Please read all instructions before servicing
this equipment. Pay attention to all safety warnings and
any other special notes highlighted in the manual. Safety
markings are used frequently throughout this manual to
designate a degree or level of seriousness and should not
be ignored. WARNING indicates a potentially hazardous
situation that if not avoided, could result in personal injury
or death. CAUTION indicates a potentially hazardous
situationthatifnotavoided,mayresultinminorormoderate
injury or property damage.
PROPOSITION 65 WARNING: This product
contains chemicals known to the state of
California to cause cancer, birth defects or
other reproductive harm.
REqUIREMENTS & CODES
WARNING:
This unit must be installed in accordance with
instructions outlined in this manual during
the installation, service, and operation of
this unit. Unqualified individuals should not
attempt to interpret these instructions or
install this equipment. Failure to follow safety
recommendations could result in possible
damage to the equipment, serious personal
injury or death.
WARNING:
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow safety warnings exactly could
result in serious injury or property damage.
Improper servicing could result in dangerous
operation, serious injury, death or property
damage.
• The installer must comply with all local codes and
regulations which govern the installation of this type
of equipment. Local codes and regulations take
precedence over any recommendations contained in
these instructions. Consult local building codes for
special installation requirements.
• This equipment contains nitrogen gas. Installation or
servicing should only be performed by qualified trained
personnel thoroughly familiar with this type equipment.
• All electrical wiring must be completed in accordance
with local, state and national codes and regulations
and with the National Electric Code (ANSI/NFPA 70)
or in Canada the Canadian Electric Code Part 1 CSA
C.22.1.
• Beforeservicing,disconnectallelectricalpower
to air handler.
• When servicing controls, label all wires prior
to disconnecting. Reconnect wires correctly.
• Verify proper operation after servicing.
WARNING:
NITROGEN
• Installationofequipmentmayrequirebrazingoperations.
Installer must comply with safety codes and wear
appropriate safety equipment (safety glasses, work
gloves, fire extinguisher, etc.) when performing brazing
operations.
HEALTH
1
FLAMMABILITY
0
0
REACTIVITY
• Installthisunitonlyinalocationandpositionasspecified
on pages 4 & 5. This unit is designed only for Indoor
installations and should be located with consideration
of minimizing the length of the supply and return ducts.
See Tables 5 - 9 (pages 19 - 22) and the rating plate for
proper circulating airflow data.
• Follow all precautions in the literature, on tags, and
on labels provided with the equipment. Read and
thoroughly understand the instructions provided with
the equipment prior to performing the installation and
operational checkout of the equipment.
• This air handler may be used for temporary heating
of buildings or structures under construction. See the
guidelines listed on page 4.
• Air handler installations in a residential garage must be
installed as specified on page 5.
0 Minimal Hazard
1 Slight Hazard
HMG**F1E,HMG**X1E&HCG**V1Eairhandlers
leave the factory with a nitrogen holding
charge. Use caution when preparing coils for
field connections. If repairs make it necessary
for evacuation and charging, it should only
be attempted by qualified, trained personnel
thoroughly familiar with this equipment. Some
localcodesrequirelicensedinstallationservice
personnel to service this type of equipment.
Undernocircumstancesshouldtheequipment
owner attempt to install and/or service this
equipment.Failure to comply with this warning
could result in equipment damage, personal
injury, or death.
3
Operation of Air Handler During Construction
GENERAL INFORMATION
Thisappliancehasbeentestedforcapacityandefficiency
in accordance with AHRI Standards and will provide
many years of safe and dependable comfort, providing
it is properly installed and maintained. Abuse, improper
use, and/or improper maintenance can shorten the life
of the appliance and create unsafe hazards. Please read
all instructions before installing the unit.
CAUTION:
Failure to follow these instructions will void the
factory warranty and may significantly reduce
the life or the performance of the air handler,
and/or result in other unsafe conditions. It is
the responsibility of the installing contractor
to insure these provisions are met.
beforeYou Install this Unit
√ This equipment is securely packaged at the time of
shipmentanduponarrivalshouldbecarefullyinspected
for damage prior to installing the equipment at the job
site.Claimsfordamage(apparentorconcealed)should
be filed immediately with the carrier.
√ it is recommended that the cooling load of the area to
be conditioned should be calculated and a system of
the proper capacity selected.
√ Check the electrical supply and verify the power supply
isadequateforunitoperation.Thesystemmustbewired
and provided with circuit protection in accordance with
local building codes.If there is any question concerning
the power supply, contact the local power company.
√ Verify the duct system is appropriate for the air handler
being installed. Please note that when replacing an
existing system with lower air-flow, the duct system
may require modification.
Operating an air handler in a construction environment
can cause the appliance a variety of problems. Proper
use of commercial portable space heating equipment
during construction is recommended. This air handler
may be used during construction if it is not in violation of
any applicable codes and the following criteria are met:
• The installation must meet all applicable codes and
be permanently installed according to the instructions
supplied with the air handler including electrical supply
and duct work.
• Theairhandlermustbecontrolledbyaproperlyinstalled
thermostat that complies with the current provisions
of the NEC (ANSI/NFPA 70) and all applicable codes
having jurisdiction. Thermostat connections must be
made in accordance with instructions supplied with the
air handler and thermostat. See pages 11 - 12.
• The installation must include a properly installed filter in
the return air system with no by-pass air.The filter must
be inspected frequently and replaced when necessary.
• Return air must be supplied unrestricted and located
such that dust and gases from construction activity are
not introduced into the circulating air system.
Locating the Air Handler
• Survey the job site to determine the best location for
mounting the unit. Consideration should be given to
availability of electric power, service access, and noise.
• The dimensions of the room or alcove must be able
to accommodate the overall size of the unit and the
installation clearances listed in Table 1. Physical
dimensions for this air handler are also shown in Figure
12 (page 17).
• Before occupying the structure: The filter must be
replaced or cleaned, the duct work must be inspected
and cleaned of any construction debris, and the air
• Theairhandlershouldbesetintopositionbeforerouting
the refrigerant tubing.
INSTALLATION CLEARANCES
Minimum Clearances
Left Side......... 0 Inches Right Side ...... 0 Inches
Back............... 0 Inches
Front........... †See Notes
• This appliance must be installed in accordance with
clearances listed in Table 1. The air handler must be
installed with ample clearance for easy access to the
air filter, blower assembly, heater assembly, controls,
and vent connections. Applicable building codes may
require additional clearance to equipment. Refer to
applicable building codes for details.
• Static pressure drop through louvered openings and
through return air plenums should be considered in
the overall duct design in the determination of the total
external static pressure.
REAR
LEFT
SIDE
RIGHT
SIDE
FRONT
†NOTES:
Alcove Installations - Allow 24 in. minimum clearance
fromfrontofunittonearestwallorpartitionforservicing.
Recommended clearance is 36 in.
Table 1. Minimum Unit Clearances
4
handler must be cleaned and/or repaired if found to
be dirty, damaged, or malfunctioning in any way by
a qualified HVAC technician. The air handler shall be
as the opening provided on the air handler. The ducts
should be appropriately sized to the capacity of the air
handler to ensure its proper airflow rating.
inspected and approved by applicable local authority • Use transition fittings if the supply and/or return air
even if this requires redundant inspections.
openings of the unit do not match the duct openings.
Thesetransitionsshouldbedimensionedinaccordance
with standard practice as specified in the ASHRAE
recommendations for duct transitions.
• The serial number for the air handler used during
construction must be submitted in writing (fax and
email also acceptable).This information will be used to
track the long-term affects of air handler usage during • Flexible connectors may be used between the unit
construction.Proofofthissubmittalshallbeavailablefor
the final inspection of the air handler prior to occupancy.
and the ductwork to prevent transmission of vibration
from the unit to the structure. If electric heater kits are
installed, heat resistant material must be used for the
flexible connector at the supply air end of the unit.
• It is good practice to seal all connections and joints
with industrial grade sealing tape or liquid sealant.
Requirements for sealing ducts vary from region to
region.Consultwithlocalcodesforrequirementsspecific
to your area.
Installation in a Garage
WARNING:
Donotplacecombustiblematerialsonoragainst
the cabinet. Do not place flammable materials,
(gasoline, paint thinners, etc.) or any other
flammable vapors and liquids, in the vicinity Unconditioned Spaces
of the air handler.
All duct work passing through unconditioned space must
be properly insulated to minimize duct losses and prevent
condensation. Use insulation with an outer vapor barrier.
Refer to local codes for insulation material requirements.
The HMG**F1E, HMG**X1E & HCG**V1E series air
handler may be installed in a residential garage with the
provision that the unit must be located or protected to
prevent physical damage by vehicles.
Air Filters
HMG**F1E, HMG**X1E & HCG**V1E series air handlers
are not supplied with an air filter when shipped from the
factory. The installer must provide a high velocity filter
that is appropriately sized to the return air duct opening
or filter rack located in the bottom of the unit. Accessing
the filter does not require tools and can be removed from
the front of the unit by removing the filter door. See Unit
Maintenance (page 16) for filter sizes and installation
information.
Plenums & Air Ducts
• Plenums and air ducts should be installed in
accordance with the standards of the National Fire
Protection Association Standard for Installation of
Air Conditioning Systems (NFPA 90A), Standard for
Installation of Residence Type Warm Air Heating
and Air Conditioning Systems (NFPA 90B), and all
applicable local codes.NFPA publications are available
by writing to: National Fire Protection Association,
Batterymarch Park, Quincy, ME 02269 or visit
www.NFPA.org online.
WARNING:
Never operate the air handler without a filter
or with doors removed. Dust and lint can build
up on internal components, resulting in loss of
efficiency,equipmentdamage,andpossiblefire.
WARNING:
All return ducts must be secured to the air
handler using appropriate methods. All return
ducts must be adequately sealed.When return
air is provided through the bottom of the unit,
the joint between the air handler and the return
air plenum must be air tight.
Acoustical Duct Work
• Certain installations may require the use of acoustical
lining inside the supply duct work. Acoustical insulation
must be in accordance with the current revision of the
Sheet Metal and Air Conditioning Contractors National
Association (SMACNA) application standard for duct
liners.DuctliningmustbeULclassifiedbattsorblankets
with a fire hazard classification of FHC-25/50 or less.
• Fiber duct work may be used in place of internal duct
liners if the fiber duct work is in accordance with the
current revision of the SMACNA construction standard
on fibrous glass ducts. Fibrous duct work and internal
acoustical lining must be NFPA Class 1 air ducts when
tested per UL Standard 181 for Class 1 ducts.
Return air and circulating air ducts must not be
connected to any other heat producing device
such as a fireplace insert, stove, etc.This may
result in fire, explosion, carbon monoxide
poisoning,personalinjury,orpropertydamage.
• Design the duct work according to methods described
by the Air Conditioning Contractors of America (ACCA).
• Thisunitisdesignedonlyforusewithareturnandsupply
duct.The return air duct must have the same free area
• Damping ducts, flexible vibration isolators, or pleated
media-style filters on the return air inlet of the air
handler may be used to reduce the transmission of
5
equipment noise eminating from the air handler.These
treatmentscanproduceaquieterinstallation,particularly
in the heated space. However, they can increase the
pressure drop in the duct system. Care must be taken
to maintain the proper maximum pressure rise across
the air handler, temperature rise and flow rate. This
may mean increasing the duct size and/or reducing the
blower speed. These treatments must be constructed
and installed in accordance with NFPA and SMACNA
construction standards. Consult with local codes for
special requirements. For best sound performance, be
sure to install all the needed gaskets and grommets
around penetrations into the air handler, such as for
electrical wiring.
Horizontal
Drain Pan
AIR HANDLER INSTALLATION
The HMG**F1E, HMG**X1E & HCG**V1E Series Air
Handlerisshippedreadyforverticalupflowinstallationand
isapprovedforattic,basement,alcove/closetorcrawlspace
installation with zero clearance to combustibles. See
Table 1 (page 4) for required installation clearances.This
appliance is approved only for indoor use.
Return
Air
Figure 1. Upflow Installation
Upflow Installations
All air handlers are factory shipped, ready for upflow
installation. The horizontal drain pan may be removed
from the air handler when installing the unit in an upflow
configuration. All return air must enter from the bottom of
the unit. A typical upflow unit is shown in Figure 1.
• The unit must be leveled at installation and attached to
a properly installed duct system.
• The surface that the air handler is mounted on must
provide sound physical support of the unit.
• The air handler must be installed so that all electrical
components are protected from water.
• If a louvered door is installed across the front of this
unit, the appliance must be mounted flush or behind
front edge of finished wall.
• Always reinstall the doors on the air handler after
servicingorcleaning/changingthefilters.Donotoperate
theairhandlerwithoutalldoorsandcoversinplace.
Downflow Installations
Thedownflowaccessorykit(SeeTechnicalSpecifications)
is required for downflow applications. Instructions for
installingthedownflowaccessorykitareincludedwiththe
kit.Itisrecommendedthattheaccessorybeinstalledprior
to installing the unit.All return air in downflow applications
must enter through the top of the unit.A typical installation
of the unit in a downflow application is shown in Figure 2.
Packaging Removal
Remove the shipping crate and User’s Manual from the
equipment. When removing the crate, use extra care so
tubing connectios are not damaged. Do not pull on the
coils upper tubes.
Mounting Applications
Vertical only air handlers are factory ready for upflow
applications. These units may be applied in downflow
applications when applied with the appropriate field kit.
Cabinet
Tube
Close-off
Plate
Factory ready horizontal air handlers may be applied in
upflow or horizontal-left and -right discharge applications.
These units may also be applied in downflow discharge
when applied with the appropriate field kit as specified in
the units Technical Specifications.
Adaptor Kit
Coil
Through-the-floor installations require a 1/4” thick
noncombustible resilient gasket to be used whenever the
supplyorreturnairductspassthroughthefloor.Thegasket
should be positioned between the duct, unit, and floor.
Figure 2. Downflow Installation
6
Horizontal Installations
suspended using steel straps around each end of the
Theseairhandlerscanbeinstalledhorizontallyinanattic, unit.The straps should be attached to the air handler with
basement,crawlspaceoralcove.Itcanalsobesuspended sheet metal screws and to the rafters with bolts.
from a ceiling in a basement or utility room in either a right
Horizontal Left Installations:
to left airflow or left to right airflow as shown in Figure 3.
1.Remove the coil access door.
Air handlers may or may not be shipped from the factory
2.Remove the plug from one of the threaded holes in the
with all the parts required for horizontal left applications
horizontal drain pan. Completely remove the webbing
andhorizontalrightapplications.Ifyourunitdoesnothave
located in the threaded holes of the horizontal drain
parts for a horizontal application, a kit may be available.
pan. IMPORTANT: If the webbing is not removed, the
condensate will not drain properly and ceiling damage
may occur.
3.Insert the plug (from horizontal drain pan) into the open
NOTE: In all horizontal applications in which the unit is
installed above a finished ceiling and/or living space, a
secondarydrainpanmustbeinstalledundertheentireunit
and unused drain hole in the drain pan at the bottom
to avoid damage to the ceiling in the event of condensate
of the unit to block bypass air.
overflow.Additionally,itisrecommendedthatanapproved
4.Remove the corresponding drain line knockout from
water level indicator or float switch device be used to
the coil access door to allow access to the horizontal
shut down the unit in the event water is detected in the
drain.
auxiliary drain pan.
5.Replace the door and attach the drain line.
If suspending the air handler from the ceiling, assemble
a support frame (Figure 4) using slotted iron channel and
Horizontal Right Installations:
1.Remove the coil access door.Unscrew the line-set tube
full threaded rod. Fasten the frame together with nuts,
close-off plate from the front left cabinet rail.
washers, and lockwashers. Secure the support frame
2.Slide the coil and drain pan assembly out of the unit.
to the rafters with lag bolts. The air handler can also be
3.Remove the sheet metal hairpin covers (if supplied)
from the back of the coil and discard.
4.Place the horizontal drain pan on the opposite side of
the coil. On units with 2 sets of knockouts, remove the
other set of knockouts in the coil spacing plates and
insert support rod.
5.Slide the coil and the horizontal drain pan assembly
back into the unit. Re-attach the tube close off plate.
HORIZONTAL RIGHT
HORIZONTAL LEFT
RETURN
AIR
NOTE: For 24K & 30K BTUH applications, it may
be preferrable to remove the blower assembly prior
to installing the coil & drainpan. In this case follow
instructions 1-4 as listed above but also remove the
blower access door and blower assembly. The blower
assembly is secured with two screws on either side
nearthefront.Withtheseremovedtheblowerassembly
can slide out of the front of the unit. Install the coil and
drain pan as described in step 5 and then replace the
blower assembly. Take care to ensure that the flanges
on the sides of the blower assembly are captured by
the pockets in the blower deck. It may be necessary to
lift the blower assembly during insertion to allow the
lower blower leg to clear the side of the drain pan.The
blower will stop against the back of the blower deck.
Replace the two screws and the blower access door
and procede with steps 6-9.
RETURN
AIR
Figure 3. Horizontal Configurations
6.Remove the plug from one of the threaded holes in the
horizontal drain pan. Completely remove the webbing
located in the threaded holes of the drain pan.
Nuts (x2)
Lag
Bolt
Washer
and
Lockwasher
IMPORTANT: If the webbing is not removed, the
condensate will not drain properly and ceiling
damage may occur.
Threaded
Rod
Nuts (x2)
NOTE: It is recommended that the suction line be
insulated up to the coil inside of the cabinet.
Figure 4. Unit Horizontally Suspended
7
7.Insert the plug (from horizontal drain pan) into the open 3.Remove the release paper from the other side of the
and unused drain hole in the drain pan at the bottom
of the unit to block bypass air.
8.Remove the corresponding drain line knockout from
the coil access door to allow access to the horizontal
drain.
gasket and attach to the circuit breaker recess area.
4.Press firmly along all four sides of the cover to ensure
gasket and cover are securely attached to the access
door.
Refrigerant Line Connections
9.Replace the door and attach the drain line
Circuit breaker Cover Installation
WARNING:
Theairhandlercircuitbreakercoverisdesignedtoprotect
the breakers of an installed heater kit from debris and
condensation.The cover attaches to the breaker recess
of the air handler upper access door using a double-sided
adhesive gasket. See Figure 5. The heater kit circuit
breaker toggles are still accessible and can be switched
with the cover in place.
NITROGEN
HEALTH
1
FLAMMABILITY
0
0
REACTIVITY
0 Minimal Hazard
1 Slight Hazard
Thecoilintheairhandlerisfactoryshippedwith
a nitrogen charge. Avoid direct face exposure
or contact with valve when gas is escaping.
Always ensure adequate ventilation is present
during the depressurization process. Address
any uncertainties before proceeding. Failure
to comply with this warning could result in
equipment damage, personal injury, or death.
There are 2 different circuit breaker cover sizes:
• 2-breaker cover for 2, 2.5, 3, 3.5, & 4 ton air handlers.
• 3-breaker cover for 5 ton air handlers.
After the heater kit is properly installed, remove the
appropriateknockoutsintheupperairhandleraccessdoor
and follow these instructions to install the breaker cover:
1.Clean any oil, dirt, or insulation fibers from the recess
areaoftheairhandleraccessdoor.Thisstepisimportant
for ensuring the gasket adheres properly to the sheet
metal door.
2.Remove release paper from one side of the gasket
and attach to back side of the breaker cover.
NOTE:Forproperalignment,Itisrecommendedtoleave
thecentersectionofthegasketinplacewhenattaching
the gasket to the breaker cover. Remove the center
section after the gasket is applied to the breaker cover.
• The installer should make every effort to ensure the
field installed refrigerant containing components of the
system have been installed in accordance with these
instructions and sound installation practices for reliable
system operation and longevity.
• Theairhandlercoildoesnotcontainarefrigerantcharge.
Refer to the installation instructions supplied with the
outdoor unit for refrigerant charge information.
• Alwaysrefertotheinstallationinstructionssuppliedwith
the outdoor unit for piping requirements. The suction
and liquid lines must be sized in accordance with the
condensing unit specifications. See Figure 12 (page
17) for liquid and suction line locations.
• When connecting refrigerant linesets together, it is
recommended that dry nitrogen be flowing through the
joints during brazing.This will prevent internal oxidation
and scaling from occurring.
C
i
r
c
u
i
t
Breakers
• Refrigerant tubing should be routed in a manner that
minimizes the length of tubing and the number of bends
in the tubing. It should be supported in a manner that
prevents it from vibrating or abrading during system
operation.Tubing should be kept clean of foreign debris
during installation.
• Ifpreciseformingofrefrigerantlinesisrequired,acopper
tubing bender is recommended.Avoid sharp bends and
contact of the refrigerant lines with metal surfaces.
• Refrigerant lines should be wrapped with pressure
sensitive neoprene or other suitable material where
they pass against sharp sheet metal edges.
R
e
c
e
s
s
C
i
r
c
u
C
i
t
o
B
r
e
r
a
k
e
r
v
e
Air Handler A
c
c
e
s
s
D
o
o
r
• HMG**F1E,HMG**X1E&HCG**V1ESeriesairhandlers
are charged through service valves on the end of the
liquid tube for each circuit. These must be removed
before brazing the line sets.
Figure 5. Circuit breaker Cover
8
Orifice Removal & Installation
9.Realign the assembly nut on the distributor body and
hand tighten both components. Mark a line on both
bodies and then tighten an additional 1/4 turn using two
wrenches.Themovementofthetwolineswillshowhow
much the nut is tightened. If a torque wrench is used,
tighten to 10-12 ft. lbs. or 14-16 Nm.
The orifice installed in the air handler has been sized for
use with the most popularly matched outdoor units. The
orifice size as shipped from the factory is listed on the air
handler rating plate. Perform steps 1 - 9 to confirm that
the orifice size meets the requirements outlined in the
outdoor unit installation manual.
1.Remove the cap from the end of the liquid line.
2.Verify pressurization by depressing the Schrader valve
on the end of the liquid line.Listen for any escaping gas.
If there is no pressure, test the coil for leakage.
• If leakage is found, clearly mark the location of the leak
and return the coil to the distributor for processing.
• If no leaks are found, the coil may be installed.
3.Depress the valve to relieve all pressure from the coil.
4.Remove and discard the valve core.
CAUTION:
To prevent damage to the unit or internal
components, it is recommended that two
wrenchesbeusedwhenlooseningortightening
nuts. Do not over tighten!
Figure 7. Removal of Orifice
5.Usingtwowrenches,loosenthenutanddistributorbody
as shown in Figure 6. Turn the assembly nut counter-
clock-wise until the orifice body halves are seperated.
6.Insert a light-gauge wire hook between the distributor
body and the restrictor orifice while being careful not
to scratch either part. Carefully remove the restrictor
orifice from the distributor body. See Figure 7.
7.Check the actual size of the new orifice. NOTE: The
size is stamped on its side. Do not use pin gauges to
measure the orifice diameter.
Figure 8. Restrictor Insertion into Distributor body
8.Insert the new orifice into the distributor body, rounded
end down. See Figure 8.
Connecting the Linesets
IMPORTANT NOTES FOR HORIZONTAL OR
DOWNFLOW INSTALLATIONS WITH TXV VALVE:
• The sensing bulb must be located flush against the
suction line for optimum heat transfer.
• Avoidattachingthesensingbulbtothelowestpartof
thesuctionlinewherecondensatemayaccumulate.
CAUTION:
To prevent damage to the unit or internal
components, it is recommended that two
wrenchesbeusedwhenlooseningortightening
nuts. Do not over tighten!
• Do not locate the sensing bulb on vertical sections
of the lineset.
• For horizontal lines, the bulb should not be located
at 12 or 6 o’clock position of the suction line. The
best location is at 4 or 8 o’clock.
• For additional information on proper sensing bulb
locations, please refer to the valve manufacturer’s
instructions.
IMPORTANT: The steps in the Orifice Removal &
Installation section must be performed before the linesets
are connected.
Figure 6. Loosening of Nut & Distributor body
9
1.Remove grommets from line set holes.
6.Braze the individual connections with dry nitrogen
flowing through the joints. NOTE: This will prevent
internal oxidation and scaling from occurring.
7.Wrap the refrigerant lines with pressure sensitive
neoprene or other suitable material especially where
the lines enter the opening in the sheet metal.
8.Evacuatethesystemofmoistureandnon-condensables
to prevent low efficiency operation or damage to the
unit. The suggested range of evacuation is 350 - 500
microns.
CAUTION:
It is recommended that a wet rag be wrapped
around the suction line in front of the close
off plate or the sensing bulb (if TXV is
installed) before applying heat. Failure to keep
components cool during brazing may result
in structural damage, premature equipment
failure, or possible personal injury.
9.Charge the system with refrigerant. Refer to the
outdoor unit installation manual for additional charging
instructions.
2.Unbraze and remove the cap on the suction line.
3.Route and cut both lineset tubes to proper length in
accordance with the outdoor unit specifications. Verify
the ends are round, clean, and free of any burrs.
4. Positiongrommetonlinesetwithsufficientdistanceaway
from brazing area.Brazing processes can permanently
damage grommets.
10. Check the system for leaks, including the lineset and
the brazed joints.
11. Replace all grommets and properly dispose of all
removed parts.
Condensate Drainage
5.Connect the suction and liquid lineset tubes.
CAUTION:
The air handler must be level to ensure proper
condensate drainage. An unlevel installation
may result in structural damage, premature
equipment failure, or possible personal injury.
CAUTION:
It is recommended that a wet rag be wrapped
around the suction line in front of the close
off plate or the sensing bulb (if TXV is
installed) before applying heat. Failure to keep
components cool during brazing may result
in structural damage, premature equipment
failure, or possible personal injury.
• Methods for disposing of condensate vary according
to local codes. Refer to local codes or authority having
jurisidiction for restrictions and proper condensate
disposal requirements.
• The drain pan that is supplied with this air handler
contains a primary and secondary drain fitting. The
condensate is drained from the unit through two 3/4”
female pipe fittings located on the front side of the unit
as shown in Figure 9.
UPFLOW
• The drain pan must be drained with field supplied tubing
or pvc pipe and adequately trapped. Both drain tubes
must have a minimum diameter of 3/4” and be trapped
separately.
HORIZONTAL
3/4” Adapter w/
3/4” dia. hose barb
IMPORTANT: Failure to install a trap may result in
condensation overflowing the drain pan, resulting in
substantial water damage to surrounding area.
• Routebothlinestoasuitabledrain,avoidingsharpbends
and pinching of the lines. The drain should maintain a
minimum horizontal slope in the direction of discharge
of not less than 1” vertical for every 10 ft of horizontal
run.
DOWNFLOW
3/4” minimum dia.
PVC or flexible tubing
• If the air handler is located in or above a living space
where damage may result from condensate overflow,
an auxiliary drain pan shall be installed under the unit.
A separate drain line should extend from the pan to a
conspicuous point and serve as an alarm indicating
that the primary drain is restricted. As an alternative to
a separate drain line, an approved water level indicator
or float switch device may be used to shut down the
unit in the event water is detected in the auxiliary pan.
NOTES:
1. The drain lines must maintain a downward slope to ensure proper
condensate drainage.
2. Each condensate drain must be trapped separately using a J-Trap or
field supplied loop.
Figure 9. Condensate Drainage Example
10
• Install a single 5 inch trap in the condensate drain line • It is recommended that the line voltage to the unit be
as close to the coil as possible. Make sure that the
top of the trap is below the bottom of the drain pan to
supplied from a dedicated branch circuit containing the
correct fuse or circuit breaker for the unit.
prevent the condensate from overflowing the drain pan. • Overcurrent protection must be provided at the branch
NOTE: There must be only one trap in the drain line.
Using more than one trap may prevent drainage.
• Primethetrapwithwater.Insulatethedrainifitislocated
inanunconditionedspace, andtestthecondensateline
for leaks. Consult local codes for additional restrictions
or precautions.
circuit distribution panel and sized as shown on the unit
rating label and according to applicable local codes.
See the unit rating plate and Tables 10 & 11 (pages
28 & 29) for maximum circuit ampacity and maximum
overcurrent protection limits.
• The installer should become familiar with the wiring
diagram/schematic before making any electrical
connections to the unit. See the unit wiring label or
Figures 18 - 20 (pages 25 - 27).
• During system checkout, inspect the drain line and
connections to verify proper condensate drainage.
• Use only copper wire for the line voltage power supply
to this unit. Use proper code agency listed conduit and
a conduit connector for connecting the supply wires to
the unit. Aluminum supply wire may be used if a heater
kit is installed.
• If replacing any of the original wires supplied with the
unit,thereplacementwiremustbecopperwireconsisting
of the same gauge and temperature rating.
• Provide power supply for the unit in accordance with the
unit wiring diagram, and the unit rating plate. Use UL
listedconduitandconduitconnectorsforconnectingthe
supply wires to the unit and for proper grounding. Field
supplied bushings for the power supply cables must be
added to support and protect the power supply cables.
• All 208/230Volt units are shipped from the factory wired
for 240 volt operation. For 208V operation, remove the
lead from the transformer terminal marked 240V and
connect it to the terminal marked 208V.
ELECTRICAL CONNECTIONS
WARNING:
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow safety warnings exactly could
result in serious injury or property damage.
Improper servicing could result in dangerous
operation, serious injury, death or property
damage.
• beforeservicing,disconnectallelectricalpower
to the air handler.
• When servicing controls, label all wires prior
to disconnecting. Reconnect wires correctly.
• Verify proper operation after servicing.
Grounding
• Electrical connections must be in compliance with
all applicable local codes and ordinances, and with
the current revision of the National Electric Code
(ANSI/NFPA 70).
• For Canadian installations, the electrical connections
and grounding shall comply with the current Canadian
Electrical Code (CSA C22.1 and/or local codes).
WARNING:
The unit cabinet must have an uninterrupted
or unbroken electrical ground to minimize
personalinjuryifanelectricalfaultshouldoccur.
Do not use gas piping as an electrical ground!
This unit must be electrically grounded in accordance
with local codes or, in the absence of local codes, with
the National Electrical Code (ANSI/NFPA 70) or the CSA
Pre-Electrical Checklist:
√ Verify the voltage, frequency, and phase of the supply
source match the specifications on the unit rating plate.
√ Verify that the service provided by the utility is sufficient C22.1 Electrical Code. Use the grounding lug provided in
tohandletheadditionalloadimposedbythisequipment.
See the unit wiring label orTables 9 - 10 (pages 28 - 29)
for proper high and low voltage wiring.
√ Verify factory wiring is in accordance with the unit wiring
diagram (Figures 18 - 20, pages 25 - 27).Make sure the
connectionsdidn’tloosenduringshippingorinstallation.
the control box for grounding the unit.
Thermostat Connections
• Thermostat connections shall be in accordance with
the instructions supplied with the thermostat. The
thermostat used with this equipment must operate in
conjunction with any installed accessories. Typical AC
and air handler hookups are shown in Figure 10 (page
12).
• Where local codes require that the thermostat wiring
must be routed through a conduit or raceway, splices
can be made inside the unit; however, all wiring must
be NEC Class 1 and separated from incoming power
leads.
Line Voltage
• Anelectricaldisconnectmustbelocatedwithinsight
of and readily accessible to the unit.This switch shall
becapableofelectricallyde-energizingtheoutdoorunit.
See unit data label for proper incoming field wiring.Any
other wiring methods must be acceptable to authority
having jurisdiction.
11
low-voltage wiring between the thermostat, outdoor
unit, and control board. NOTE: When the low voltage
wires are positioned in this grommet, the grommet will
preventchafingand/orshortingofthelowvoltageleads.
CAUTION:
Isolation must be maintained from the external
Class 2 output of any transformer in a cooling
circuit.Useathermostatwithisolatingcontacts
to prevent inter-connection of Class 2 outputs.
Control board
The control board in the air handler controls the timing
sequence of the elements.The board is equipped with a 3
second blower on delay and a 15 second blower off delay
in heating and a 40 second blower off delay in cooling.
See Figures 14 or 15 (page 23) and Table 12 (pages 29-
• The thermostat should be mounted about 5 feet above
theflooronaninsidewall.DONOTinstallthethermostat
on an outside wall or any other location where its
operationmaybeadverselyaffectedbyradiantheatfrom 31) for control board modes and actions.
fireplaces, sunlight, or lighting fixtures, and convective
Twinning
heat from warm air registers or electrical appliances.
HMG**F1E series air handler’s are not supplied with a
Refertothethermostatmanufacturer’sinstructionsheet
for detailed mounting and installation information.
• Install the grommet, which is packed with the unit, in
the hole for low-voltage wires. Properly connect the
builtintwinningcapability.Toconnecttwoairhandlerstoa
commonsinglestageACcondensingunitorheatpump, a
twinning kit is available for field installation.Please follow
the instructions supplied with the kit.
Thermostat
W Y G R
Thermostat
W Y G R
Thermostat
Y1 W2 W/E Y2 G R
NOTE: Jumper W1 & W2
together if not using W2
on thermostat
Air
Conditioner
Y1
Y1
Y1
W2
W2
Air
W1
O
Handler
W1
Air
Conditioner
O
Air
W1
Y
Conditioner
Y/Y2
Y/Y2
Y
Y2
G
G
Y
G
R
C
R
C
R
C
R
C
Air
Handler
Air
Handler
C
C
Typical Air Conditioner with
Standard Air Handler
Typical Air Conditioner with
2-Stage Air Handler
Typical 2-Stage Air Conditioner
with 2-Stage Air Handler
Thermostat
Thermostat
Thermostat
O
G R C E
W2 O Y G R C W/E
Y1 W2 W/E OY2 G R
C
W2
Y
NOTE: Jumper W1 & W2
together if not using W2
on thermostat
NOTE: Jumper between
W2 & E is required when
no OD T-Stat is used.
Y1
W2
W1
Y1
W2
W1
Air
Handler
Y1
W2
W2
O
W1
Y
O
O
W2
O
Y
O
Y/Y2
G
Y/Y2
G
Y
Y2 OUT
G
R
C
R
R
C
R
C
R
C
R
C
C
Air
Handler
Air
Handler
Heat Pump
Heat Pump
Heat Pump
Typical Heat Pump with
2-Stage Air Handler
Typical 2-Stage Heat Pump with
2-Stage Air Handler
Typical Heat Pump with
Standard Air Handler
Figure 10.Typical Thermostat Connections
12
NOTE: Variable speed air handlers cannot be twinned.
STARTUP & ADjUSTMENTS
Heater Kits
When electric heat packages with circuit breakers are
field-installed, the circuit breaker may be used as a
disconnecting means in most applications. Reference
the NEC and local codes for disconnect requirements.
WARNING:
NITROGEN
HEALTH
1
0
0
If a heater kit is installed:
The HMG**F1E series air handler is shipped from the
factory without an electric heater kit installed. If Electric
heat is desired, the H6HK heater kit may be purchased
separately and field installed. Determine the correct size
heater kit for your unit by referring to the list below or the
units rating label.
FLAMMABILITY
REACTIVITY
0 Minimal Hazard
1 Slight Hazard
The evaporator coil is shipped from the factory
with a nitrogen charge. Use caution when
preparing coils for field connections. If repairs
makeitnecessaryforevacuationandcharging,
it should only be attempted by qualified,
trained personnel thoroughly familiar with this
equipment. Some local codes require licensed
installation service personnel to service this
type of equipment. Under no circumstances
should the equipment owner attempt to install
and/orservicethisequipment.Failuretocomply
with this warning could result in equipment
damage, personal injury, or death.
24K & 30K BTUH........................................... 15Kw max
36K & 42K BTUH........................................... 20Kw max
48K & 60K BTUH........................................... 30Kw max
1.Connect the 2 wire plug of the air handler to the mating
2 wire plug of the heater kit.
2.Connect the line voltage leads to the circuit breaker or
terminal block provided.
3.Connect the heater kit plug with the mating receptacle
on the air handler control board.
If a heater kit is not installed:
1.Remove the 2 wire plug of the air handler by cutting the
wires and discarding the plug.
2.Strip the ends of the 2 air handler wires and connect
to the line-voltage leads with the 2 wire nuts provided.
beforeYou Start the Unit
Prior to start-up, complete the following inspections:
√ Verifytheunitislevelandproperlylocatedwithadequate
clearances for servicing the unit. See Table 1 (page 4).
√ Check condensate drain line(s) for proper drainage.
√ Verify the surrounding area and top of the unit is free
from obstructions and debris.
√ Check all duct connections. Make sure the duct work
is adequately sealed to prevent air leakage.
√ Check all coil connections for leaks.
√ Verify that the line voltage power leads are securely
connectedandtheunitisproperlygrounded.Makesure
all doors are installed before restoring power to the unit
√ Verify the thermostat is wired correctly. Make sure all
low voltage wires are securely connected.
Electronic Air Cleaner (EAC)
The unit has an output to power an electronic air cleaner
when the blower is running. This output is rated to 1.0
amp at 208/240V.
Humidifier
The unit has an output to power a humidifier when the
blower is running. This output is rated to 1.0 amp at
208/240V.
Optional Humidistat
(HMG**X1E & HCG**V1E Models Only)
The optional humidistat may be installed in the return air
duct to provide excellent humidity control when needed
andmaximumsystemcapacityandenergyefficiencywhen
humidity levels are normal. The humidistat senses when
humidity in the return air stream is above a preset level
(fieldadjustable)andsendsasignaltothemotortoreduce
theairflowsothatmoremoisturemayberemoveduntilthe
humidity level drops. The air handler is pre-programmed
for humidistat operation.
√ Verify the power supply branch circuit overcurrent
protection is sized properly.
√ Verify filter is properly and securely installed.
IMPORTANT: Before starting the unit, install the initial
charge on units that are factory shipped with a nitrogen
holding charge:
1.Read all installation instructions first.
2.Purge the nitrogen holding charge.
3.Evacuate the unit to 350 - 500 microns.
4.Allow the unit to remain under vacuum for at least 30
minutes.
5.Weigh in the proper amount of new (or reclaimed)
refrigerant. Refer to the air conditioner or heat pump
installation manual for the proper type and quantity of
refrigerant.
Install the humidistat in the return air duct as directed in
the installation instructions included with the kit.Wire the
humidistat through the low-voltage wire entrance in the
air handler to the control board terminal marked DEHUM.
Wirethehumidistattoopenonriseinhumidity.SeeFigures
16 & 17 (page 24).
13
Refrigerant Charging
automatically set the heating speed based on the amount
The system refrigerant charge can be checked and of installed heat.The remaining 3 HEAT switches have no
adjusted through the service ports provided at the front function. Switch settings are listed in Table 6 (page 20)
paneloftheoutdoorunit.Useonlygaugelineswhichhave or Table 9 (page 22). NOTE: For HMG**X1E Models, the
aSchraderdepressiondevicepresenttoactuatethevalve. minimum electric heat airflow setting may be set higher,
but must never be set lower than the setting shown in
Table 7 (page 21).
Air Circulation
Running the Blower Continuously
Set the thermostat’s system mode to OFF and the
thermostat’s fan mode to ON. The blower motor should
run continuously. Check for air delivery at the register(s).
Ensure that there are no obstructions at the registers or
in the ducts.
blower Configurations
Determining Nominal System Capacity
To select the appropriate airflows for the air handler, the
nominal system capacity must be known. The nominal
system capacity is always the nominal capacity of the
outdoor unit. However, in some situations the nominal
system capacity may not be the same as the nominal
capacity of the air handler. Always refer to the nominal
capacity of the outdoor unit to determine the nominal
system capacity.
Selecting continuous low speed fan operation
(Standard Blower)
The air handler is equipped with an option of continuous
low speed fan operation.When G is energized without Y/
Y2, the air handler will operate using the cooling speed.
With G & Y/Y2 or Y/Y2 energized, the air handler will
operate in the selected cooling speed (including 40 sec
blower-off delay).
NOTE: The CFM values listed in Table 9 (page 22) are
not dependent on duct static pressure. The VSHE motor
automatically compensates for changes in duct static
pressure (within the limits of the motor).
Turning the Blower Off
Set thermostat’s fan mode to AUTO, the blower will shut
down immediately.
3-Speed Units
The blower speed is preset at the factory for operation
at the same speed for heating and cooling, by using the
jumping terminal on the blower motor and connecting it
to the desired speed with both the red and black wires
connected to the jumping terminal. NOTE: The control
board is programmed with a 40 second off delay in the
cooling mode for optimum system performance and
efficiency.
System Cooling
1. Set the thermostat’s system mode to COOL and fan
mode to AUTO. Lower the thermostat’s temperature
mode below room temperature and observe that the
blower energizes. Check the air being discharged at
the register is cooler than room temperature. Verify
unit refrigerant pressures are in order. Blower should
be turning in direction indicated by arrow.
CAUTION:
NOTE: DO NOT alter unit wiring.Listen for any unusual
noises. Locate the source and correct as needed.
To avoid personal injury or property damage,
make sure the motor leads do not come into
contactwithanyuninsulatedmetalcomponents
of the unit.
2. Allow the unit to run for several minutes and then set
the thermostat’s temperature above room temperature.
Verify the blower cycles off with the thermostat.
For optimum system performance and comfort, it may be
necessary to change the factory set speed. See Table 5
(page 19) for airflow data. To change the blower speed:
1.Disconnect all electrical power to the unit and remove
the upper door.
2.Remove the black and red wires from the blower motor
jumping terminal. Discard the blower motor jumping
terminal.
System Heating
1.Set the thermostat’s system mode to HEAT and the fan
mode to AUTO. Increase the thermostat’s temperature
above room temperature and observe that the blower
energizes.Checktheairbeingdischargedattheregister
is warmer than room temperature.
2. Allow the unit to run for several minutes and then set
the thermostat’s temperature below room temperature.
Verify the blower cycles off with the thermostat.
3.Connect the heating speed wire (red) and the cooling
speed wire (black) to the desired blower speed marked
on the terminal block of the blower motor.
Selecting Minimum Electric Heat Airflow
The minimum electric heat airflow setting controls the
minimum air flow that will be produced whenever electric
heater kits are used. When the electric heater kit is
energized along with a heat pump, the airflow may be
higher depending on the basic cooling/heat-pump airflow
setting. The minimum electric heat airflow is selected by
theredblowerwireon3-speedmodelsorsettingswitches
1,2,3 & 4 on HMG**X1E models. HCG**V1E models
• Terminal 4 = Hi speed
• Terminal 5 = Med speed
• Terminal 6 = Low speed
14
4.Replace the upper door and secure it to the unit.
5.Restore power to the unit.
• Formaximumdehumidification,selectanairflownearthe
middle or bottom of the range for that nominal capacity.
Additional information on humidity control can be found
in the Humidistat and Delay Setting sections.
• For thermostats with a dehumidifier output, use a field
supplied wire to connect the thermostat’s dehumidifier
output to the terminal marked DHUM. The thermostat
should be set so that the DHUM output should be high
(energized) when dehumidification is needed.See also
Dehumidification Options section.
High Efficiency Units (Variable & Fixed Speed)
IMPORTANT! This air handler has been designed to
give the installer maximum flexibility to optimize system
performance, efficiency, and comfort. Because there
are so many different ways to set up the air handler it is
important to read and follow these directions carefully.
HMG**X1E & HCG**V1E series air handlers use high
efficiencycirculatingairmotorsthatcomeintwovariations
and both are controlled differently.The fixed speed motor
control board (Figure 16, page 24) controls the torque
and the variable speed motor control board (Figure 17)
controls the airflow at a constant CFM. Both boards use
the same control board.
IMPORTANT! If coil icing is observed, the basic cooling/
heat-pump airflow selected may be too low. Verify the
setting selected is within the range shown in Table 8 and
thatthethesystemisproperlycharged.Pleaserefertothe
instructionssuppliedwiththeoutdoorunit.Ificingcontinues
to occur, raise the selected airflow one or two steps.
Before operation, the air handler must be configured to
matchtheunitwiththesystem,systemoptions,andclimatic
conditions. When configured, the air handler responds
directly to the thermostat inputs, as well as the optional
humidistat (see page 13). During normal operation, the
motor will gradually change speeds during start-up, shut
down, whenthermostatinputschange, andwhentheduct
static pressure changes (vents closed or opened, filter
clogging, etc.). The air handler is configured by setting
the selector switches and removing jumper connectors.
NOTE: Variable speed air handlers with SEER ratings
higherthan15arematchedwitha2-stagecoolingoutdoor
unit. They are programmed to operate at 75% of the
selected airflow while the system is in the lo-cool mode
and 100% of the selected airflow while in hi-cool mode.
Dehumidification Options
(HMG**X1E or HCG**V1E Models Only)
Both motor control boards (Figures 16 & 17, page 24)
have a DHUM connection that allows the system to
increase the amount of humidity that is removed from
the circulating air. This is accomplished by reducing the
CFM and allowing the cooling coil to become colder.This
will only occur when there is a call for cooling. There are
many ways that this can be electrically wired.
Selecting Basic Heating Airflow
Fixed & variable speed motor control boards (Figures 16
& 17) contain a set of dip switches for setting the blower
speed.For HMG**X1E models, pins 1-4 set the speed for
heating. For HCG**V1E models, the A/B switch must be
set for the appropriate air handler size (either setting can
be used for 48K or 60K BTUH applications).The airflow is
set automatically based on the amount of installed heat.
For both HMG**X1E & HCG**V1E models, the cooling
speed is selected via switches 5,6,7,& 8. To determine
the appropriate switch settings for your installation, see
Tables 6, 7, 8, or 9 (pages 20 - 22).
1. If the room thermostat incorporates a humidity sensor
andDHUMoutput,connecttheDHUMonthethermostat
to the DHUM terminal on the motor control board.
2. If using a separate humidistat, connect the DHUM & R
terminals on the humidistat to the DHUM & R terminals
on the motor control board of the air handler. In this
option, the DHUM output of the humidistat must be set
to be normally open and closed when there is a call for
humidification. See Figure 11.
Selecting Basic Cooling / Heat Pump Airflow
3.If a humidistat is not available, it is an acceptable option
to connect the R & DHUM terminals on the motor
control board together with a field supplied wire. This
option causes the blower to run at a reduced CFM for
10 minutes after a call for cooling. NOTE: If outdoor
unit is a heat pump, connect the O terminal to DHUM.
Thebasiccooling/heat-pumpairflowiscontrolledbysetting
switches 5 - 8 on the motor control board (mounted on the
blower). All airflows for other modes of operation (except
electric heat) are determined by this basic setting. FAN
ONLY would deliver 50% of the selected cooling airflow.
Table 8 (page 21) lists the basic airflow values versus the
airflowselectorswitchsettingsandrangesofbasicairflow
settings recommended for each nominal system capacity.
MOTOR
CONTROL BOARD
HUMIDISTAT
• When operating in the heat pump mode, a higher
basic airflow setting will increase the energy efficiency
and capacity but will also decrease the supply air
temperature.
DHUM
R
DHUM
R
• For maximum capacity and energy efficiency, select an
airflow at or near the top of the range for that nominal
capacity. See Table 8 (page 21).
Figure 11. DHUM Wiring Configuration
15
UNIT MAINTENANCE
FURNACE SIZE (bTUH)
FILTER SIZE
Propermaintenanceismostimportanttoachievethebest
performance from a air handler.Some of the components
and their locations are shown in Figure 13 (page 18). If
any component of the air handler must be replaced, use
only factory authorized replacement parts specified in the
Replacement Parts List provided online.
24K & 30K
36K & 42K
48K & 60K
12 x 20 x 1
18 x 20 x 1
20 x 20 x 1
Table 2. Filter Sizes
blower Compartment
Dirt and lint can create excessive loads on the motor
resulting in higher than normal operating temperatures
and shortened service life. It is recommended that the
blower compartment be cleaned of dirt or lint that may
have accumulated in the compartment or on the blower
and motor as part of the annual inspection.
WARNING:
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow safety warnings exactly could
result in serious injury or property damage.
blower Fan Wheel
Inspect the blower wheel blades for accumulations of dirt
and clean if necessary.Inspect mounting nut for tightness
when done.
Improper servicing could result in dangerous
operation, serious injury, death or property
damage.
blower Motor & Assembly
•Beforeservicing,disconnectallelectricalpower
to air handler.
• When servicing controls, label all wires prior
to disconnecting. Reconnect wires correctly.
• Verify proper operation after servicing.
Inspect the blower assembly and motor mounting
brackets for tightness and corrosion.Correct deficiencies
if necessary.The blower motor contains sealed bearings
and under normal operating conditions, no maintenance
is necessary for the life of the equipment.
• These maintenance instructions are primarily intended
toassistqualifiedtechniciansexperiencedintheproper
maintenance and operation of this appliance.
TROUbLESHOOTING
If the air handler fails to operate, check the following:
• Is the electric turned on?
• Always reinstall the doors on the air handler after
servicingorcleaning/changingthefilters.Donotoperate
theairhandlerwithoutalldoorsandcoversinplace.
• Verify that the thermostat is properly installed and is
not being affected by drafts or heat from lamps or other
appliances.
• To achieve the best performance and minimize
equipment failure, it is recommended that a yearly
maintenance checkup be performed. At a minimum,
this check should include the following items:
• Is the thermostat operating properly?
• Are the blower compartment door(s) in place?
• Is the air handler disconnect closed?
• Has the circuit breaker tripped or the control board fuse
burned open?
• Are any manual reset switches open?
• Is the filter dirty or plugged?
• Is the LED on both control boards constantly ON? If
not, refer to Tables 3 or 4 to determine fault condition.
Air Filter(s)
RED LED (AN2)
DIAGNOSTIC
HMG**F1E, HMG**X1E & HCG**V1E series air handlers
are not supplied with a single air filter when shipped from
the factory. It is recommended that the filter be cleaned
or replaced monthly. Newly built or recently renovated
homes may require more frequent changing until the
construction dust has minimized. Filter sizes shown in
Table 2 are available at most local retailers.
OFF
Flash
ON
Control Fault (No Power)
Blower Fault
Normal Operation
Table 3. Air handler Control board Fault Conditions
GREEN
LED
RED
LED
DIAGNOSTIC
Control Fault (No Power)
Normal Operation
Off
On
Off
On
WARNING:
Fixed
Speed
Furnaces
Motor Fault
On
Flash
On
Never operate the air handler without a filter in
place. Dust and lint in the return air can build
up on internal components, resulting in loss of
efficiency,equipmentdamage,andpossiblefire.
Twin Fault (no motor fault)
Communications Fault
Control Fault (No Power)
Normal Operation
Flash
Flash
Off
Flash
Off
Variable
Speed
Furnaces
On
On
Filters designed to remove smaller particles such as
pollen, may require additional maintenance.
Motor Fault
On
Flash
Flash
Communications Fault
Flash
Table 4. Motor Control board Fault Conditions
16
FIGURES & TAbLES
3/4”
3/4”
3/4”
13”
11/8” K.O.
(typ.)
“A”
1 7/8" K.O.
11/4”
15/8”
17/8”
11/4”
3 1/4”
2 5/8”
1 7/8”
1 1/8”
7/8" K.O.
11/8” K.O.
(typ.)
1 7/8”
3 5/8”
5 5/8”
13/4” K.O.
(typ.)
DETAIL “D”
“H”
3 1/4”
2 1/4”
SUCTION
LIQUID
15 1/4”
13”
“W”
22"
FURNACE SIZE (bTUH)
H
W
A
Detail D
24K & 30K
36K (HMG**F1E Only)
36K & 42K
43-5/16
43-5/16
49-5/16
55-15/16
14-3/16
12-3/4
18-1/4
18-1/4
21
No
No
No
Yes
19-11/16
19-11/16
22-7/16
48K & 60K
Figure 12. HMG**F1E, HMG**X1E & HCG**V1E Series Physical Dimensions
17
Circuit
Breaker (60A)
Heating Element
Assembly
Transformer
Motor Control
Board
Blower
Wheel
Control
Board
Upper Door
Assembly
Capacitor
Motor
Mount Kit
Blower
Housing
Blower
Motor
Coil
Assembly
Filter
Door
Horizontal
Drain Pan
Vertical
Drain Pan
Filter
Tracks
Lower Door
Assembly
Figure 13. HMG**F1E, HMG**X1E & HCG**V1E Series Air Handler Components
18
AIRFLOW DATA
Dry Coil ESP
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
Low
683
0.00
861
647
0.07
823
607
0.19
781
563
0.30
734
515
0.42
682
463
0.53
625
406
0.65
564
345
0.76
498
Corrected ESP1
Medium
HMG24F1E
HMG30F1E
HMG36F1E
HMG42F1E
Corrected ESP1
High
Corrected ESP1
0.00
1072
0.00
849
0.00
1026
0.00
825
0.11
975
0.23
920
0.36
860
0.48
797
0.60
730
0.72
659
0.00
793
0.14
753
0.27
704
0.40
647
0.53
581
0.67
508
Low
Corrected ESP1
Medium
0.00
1118
0.00
1277
0.00
953
0.04
1087
0.00
1233
0.00
915
0.15
1046
0.04
1184
0.00
871
0.27
997
0.38
940
0.50
874
0.62
799
0.74
717
Corrected ESP1
0.17
1130
0.10
821
0.29
1070
0.23
764
0.42
1005
0.36
701
0.55
935
0.68
860
High
Corrected ESP1
Low
0.49
631
0.63
555
Corrected ESP1
0.00
1265
0.00
1427
0.00
1324
0.00
1485
0.00
1637
0.00
1605
0
0.04
1232
0.00
1385
0.00
1302
0.06
1455
0.00
1601
0.00
1606
0.11
1939
0
0.16
1188
0.03
1333
0.00
1271
0.17
1418
0.13
1558
0.00
1592
0.21
1890
0.18
2095
0
0.27
1133
0.15
1270
0.09
1233
0.27
1373
0.24
1506
0.21
1565
0.31
1830
0.28
2003
0.26
0.39
1067
0.28
1196
0.23
1187
0.38
1320
0.36
1447
0.33
1524
0.42
1758
0.39
1906
0.37
0.51
991
0.62
903
0.74
805
Medium
Corrected ESP1
High
Corrected ESP1
0.41
1113
0.36
1134
0.49
1260
0.47
1380
0.44
1468
0.52
1675
0.50
1805
0.49
0.54
1018
0.50
1072
0.61
1193
0.58
1305
0.56
1399
0.63
1580
0.61
1698
0.60
0.68
913
0.64
1003
0.72
1118
0.70
1223
0.68
1316
0.74
1474
0.72
1586
0.71
Low
Corrected ESP1
Medium
Corrected ESP1
High
Corrected ESP1
Low
Corrected ESP1
Medium
1977
0
HMG48F1E
HMG60F1E
Corrected ESP1
High
Corrected ESP1
2264
0
2182
0
Use HMG**X1E airflow data. See Table 5 (page 20).
NOTES:
1) Airflow is shown in cfm, +/- 5%.
2) External static pressure (ESP) is shown in inches w.c.
3) See unit nameplate or installation instructions for maximum recommended external static pressure.
Table 5. Airflow Data for HMG**F1E Series Air Handlers
19
Cooling or Heating Airflow (CFM)
Dry Coil ESP
Switch Settings
0 = OFF, 1 = ON
1/5 2/6 3/7 4/8
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
585
710
550
670
520
650
460
610
420
560
405
530
475
625
440
580
845
790
765
715
680
655
890
865
840
785
760
710
680
655
955
925
900
850
825
790
770
720
HMG24X1E
&
HMG30X1E
1030
1115
1155
1200
1240
1320
1355
1405
1440
1465
1465
995
975
940
910
870
840
815
1085
1130
1175
1215
1290
1330
1375
1415
1425
1425
1060
1095
1145
1195
1265
1305
1345
1385
1390
1390
1020
1070
1110
1170
1240
1280
1325
1355
1355
1355
995
965
925
905
1040
1085
1140
1215
1255
1295
1325
1320
1320
1010
1060
1110
1185
1220
1275
1290
1290
1290
985
950
1025
1080
1160
1200
1250
1255
1260
1260
1000
1060
1130
1175
1210
1215
1215
1215
Cooling or Heating Airflow (CFM)
Dry Coil ESP
Switch Settings
0 = OFF, 1 = ON
1/5 2/6 3/7 4/8
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
600
660
550
610
430
540
390
460
425
580
830
750
695
640
520
600
860
825
765
690
630
525
620
485
585
935
895
835
790
710
655
HMG36X1E
&
HMG42X1E
1045
1095
1155
1230
1285
1330
1395
1450
1490
1530
1530
975
920
875
830
795
720
685
1040
1105
1185
1260
1290
1365
1405
1450
1485
1490
995
950
900
850
805
750
1060
1140
1210
1245
1315
1375
1410
1460
1465
1010
1090
1165
1205
1275
1335
1385
1425
1425
965
920
870
825
1045
1125
1170
1235
1295
1340
1380
1390
1010
1080
1125
1205
1260
1300
1350
1350
965
920
1040
1085
1160
1220
1270
1310
1310
1010
1045
1130
1180
1230
1280
1285
Cooling or Heating Airflow (CFM)
Dry Coil ESP
Switch Settings
0 = OFF, 1 = ON
1/5 2/6 3/7 4/8
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
710
830
580
690
395
675
530
665
505
560
930
875
710
530
705
1065
1185
1275
1365
1480
1560
1650
1730
1785
1865
1920
2010
2065
1015
1115
1220
1350
1430
1535
1600
1685
1740
1820
1890
1965
2020
900
840
800
665
830
635
745
1010
1175
1255
1370
1485
1545
1660
1695
1785
1850
1960
1985
960
925
875
HMG48X1E
&
HMG60X1E
1120
1200
1325
1430
1500
1610
1645
1750
1805
1900
1955
1060
1150
1265
1375
1450
1570
1615
1695
1765
1850
1915
970
930
890
1105
1225
1335
1405
1520
1545
1655
1715
1810
1880
1060
1185
1285
1360
1470
1510
1605
1675
1775
1840
1025
1140
1240
1305
1420
1470
1560
1640
1730
1810
NOTE: When matched with two-stage outdoor units, the airflow on low (Y1 or W1) input will be 70% of the values shown in this table.
Table 6. Airflow Data for HMG**X1E Air Handlers
20
Nominal Electic Heat KW
FURNACE MODELS
5
8
10
15
20
25
30
HMG24X1E & HMG30X1E
HMG36X1E & HMG42X1E
HMG48X1E & HMG60X1E
800
900
900
1000 1300
N/A
N/A
N/A
N/A
N/A
1000 1100 1300 1500
1000 1100 1200 1400 1600 1800 2000
NOTE: See Table 6 for appropriate switch settings for these airflows.
Table 7. Minimum Heating Airflow Settings (in CFM)
for HMG**X1E Air Handlers
HCG24V1E & HCG30V1E
SWITCH SETTINGS
NOMINAL
(1 = ON, 0 = OFF)
CFM
CAPACITY
5
6
7
8
525
560
600
625
700
750
800
850
875
890
930
950
1000
1050
1125
1200
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
HCG36V1E & HCG42V1E
HCG48V1E & HCG60V1E
SWITCH SETTINGS
(1 = ON, 0 = OFF)
SWITCH SETTINGS
(1 = ON, 0 = OFF)
NOMINAL
CAPACITY
NOMICAL
CAPACITY
CFM
CFM
5
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
6
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
7
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
8
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
5
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
6
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
7
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
8
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
525
560
1100
1200
1250
1300
1350
1400
1450
1500
1550
1600
1650
1700
1750
1800
1900
2000
600
650
700
750
800
850
875
950
1050
1150
1250
1350
1400
1600
Table 8. Recommended Cooling Airflow Settings for HCG**V1E Air Handlers
21
Cooling Airflow
Heating Airflow
COOL Switch Setting
Airflow
(CFM)
Heater Kit
Installed (KW)
Airflow
(CFM)
A/b Switch Setting
0 = OFF, 1 = ON
A/b Switch Setting
0 = OFF, 1 = ON
0 = OFF, 1 = ON
5
6
7
8
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
525
560
600
625
700
750
800
850
875
890
930
950
1000
1050
1125
1200
0
0
0
0
0
0
0
0
0
600
800
1000
1000
1300
n/a
5
8
10
15
20
25
30
HCG24V1E
&
HCG30V1E
n/a
n/a
Cooling Airflow
Heating Airflow
COOL Switch Setting
Airflow
(CFM)
Heater Kit
Installed (KW)
Airflow
(CFM)
A/b Switch Setting
0 = OFF, 1 = ON
A/b Switch Setting
0 = OFF, 1 = ON
0 = OFF, 1 = ON
5
6
7
8
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
525
560
1
1
1
1
1
1
1
1
0
700
900
5
600
8
1100
1100
1300
1500
n/a
650
10
15
20
25
30
700
HCG36V1E
&
HCG42V1E
750
800
n/a
850
875
950
1050
1150
1250
1350
1400
1600
Cooling Airflow
Heating Airflow
COOL Switch Setting
A/b Switch Setting
(* = either 0 or 1)
Airflow
(CFM)
A/b Switch Setting
(* = either 0 or 1)
Heater Kit
Installed (KW)
Airflow
(CFM)
0 = OFF, 1 = ON
5
6
7
8
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
1100
1200
1250
1300
1350
1400
1450
1500
1550
1600
1650
1700
1750
1800
1900
2000
*
*
*
*
*
*
*
*
0
800
5
1000
1200
1200
1400
1600
1800
2000
8
10
15
20
25
30
HCG48V1E
&
HCG60V1E
NOTES:
•
•
Airflow values listed are for 240V operation. For
208V operation, multiply the CFM value by .95 for
HCG24V1E, HCG30V1E, HCG36V1E, & HCG42V1E units.
For HCG48V1E & HCG60V1E units, mulitply the CMF value
by .90.
When matched with two-stage outdoor units the airflow on
low (Y1 or W1) input only will be 70% of the values shown in
this table.
Table 9. Airflow Data for HCG**V1E Air Handlers
22
ELECTRICAL DIAGRAMS & DATA
W
C Y G R
P2
3A Fuse
BLWDTC
BLWDTC_R
L 2
L 1
EAC
COOL
HEAT
LED 1
HEATER P1
Figure 14. Single Stage Control board
1 Y 2 W L 1 W
O
Y 2 / Y
R
G
C
P3
P2
LED 1
HEATER P1
Figure 15.Two - Stage Control board
23
TEST PORT
W1
EXPANSION
PORT
FAN SPEED
8
1 2 3 5 6 7
4
COOL
HEAT
STATUS
BLOWER MOTOR
Figure 16. Fixed Speed Motor Control board
STATUS LIGHTS
L2-IN
L2-OUT
W
Y/Y2
Y1
L1-IN
L1-OUT
H
DEHUM
Y1
FAN SPEED
8
2 3 5 6 7
4
TEST PORT
R
C
COOL
HEAT
SENSOR
GND
EXPANSION PORT
BLOWER MOTOR
Figure 17. Variable Speed Motor Control board
24
C K B L A
R E D
RELAY
R E D
Y
G R A
G R E E N
W H I T E
O W Y E L L
Figure 18. Wiring Diagram for HMG**F1E Series Air Handler
25
BLUE
GREEN
YELLOW
ORANGE
RED
BLUE
GREEN
YELLOW
ORANGE
RED
BROWN
BROWN
EXPANSION
L1
L2
HUM
EAL
HEATER PLUG
Figure 19. Wiring Diagram for HMG**X1E Series Air Handler
26
WHITE
BLACK
1
2
3
4
5
6
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
1
2
3
4
5
6
Y
G R A
EXPANSION
W H I T E
K
A C B L
L1
L2
HUM
EAL
HEATER PLUG
Figure 20. Wiring Diagram for HCG**V1E Series Air Handler
27
HMG**F1E SERIES
240 VAC, 50 & 60 HZ, SINGLE PHASE
208 VAC, 50 & 60 HZ, SINGLE PHASE
MCA MOP
MCA
MOP
HEAT KIT
MODEL
NUMbER
H6HK-
AIR HANDLER
MODEL
None
1.6
26.6
41.2
51.6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1.6
15
-
-
-
-
-
-
-
-
-
30
-
-
-
-
-
-
30
60
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
15
1.6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1.6
15
-
-
-
-
-
-
-
-
-
25
-
-
-
-
-
-
25
45
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
15
25
40
45
30
15
25
40
50
70
30
45
15
25
40
50
70
90
30
45
15
25
40
50
70
90
30
45
15
30
40
50
80
100
005H-XX
008H-XX
010H-XX
009Q-XX
None
005H-XX
008H-XX
010H-XX
015H-XX
009Q-XX
015Q-XX
None
005H-XX
008H-XX
010H-XX
015H-XX
020H-XX
009Q-XX
015Q-XX
None
005H-XX
008H-XX
010H-XX
015H-XX
020H-XX
009Q-XX
015Q-XX
None
005H-XX
008H-XX
010H-XX
015H-XX
020H-XX
024H-XX
029H-XX
009Q-XX
015Q-XX
None
005H-XX
008H-XX
010H-XX
015H-XX
020H-XX
024H-XX
029H-XX
009Q-XX
015Q-XX
26.6 30
41.2 45
51.6 60
28.7
3.1
28.1 30
42.7 45
53.1 60
65.6 60
30.2
46.4
2.6
27.6 30
42.2 45
52.6 60
64.7 60
102.6 60
29.7
45.9
3.1
28.1 30
42.7 45
53.1 60
65.6 60
103.1 60
30.2
46.4
5.4
30 23.3
45 35.9
60 45.0
30
15
30 24.8
45 37.4
60 46.5
23.3 25
35.9 40
45.0 45
18.8
3.1
24.8 25
37.4 40
46.5 50
68.1 50
26.6
40.6
2.6
24.3 25
36.9 40
46.0 50
67.6 50
89.3 50
26.1
40.2
3.1
24.8 25
37.4 40
46.5 50
68.1 50
89.8 50
26.6
40.7
5.4
HMG24F1E
HMG30F1E
-
15
-
-
15
3.1
3.1
28.1
42.7
53.1
53.1 25.0
-
80 46.5 21.7
-
-
-
-
-
-
-
-
15
35
50
15
30 24.3
45 36.9
60 46.0
80 46.0 21.7
110 46.0 43.3
30
50
15
30 24.8
45 37.4
60 46.5
80 46.5 21.7
110 46.5 43.3
35
50
15
35 27.0
45 39.7
60 48.7
-
-
-
-
-
-
-
-
-
-
15
-
2.6
27.6
42.2
52.6
52.6 25.0
52.6 50.0
2.6
HMG36F1E
-
-
-
-
-
-
-
-
-
-
15
-
-
-
-
-
-
-
-
-
-
15
3.1
28.1
42.7
53.1
53.1 25.0
53.1 50.0
3.1
-
-
HMG42F1E
30
60
-
-
-
-
-
-
30
60
60
60
-
-
-
-
-
25
45
-
-
-
-
-
-
25
45
45
45
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
15
-
-
-
-
-
-
-
-
-
-
15
5.4
30.4
45.0
55.4
55.4 25.0
55.4 50.0
55.4 50.0 25.0 130.4 60
55.4 50.0 50.0 155.4 60
-
5.4
30.4 35
45.0 45
55.4 60
80.4 60
105.4 60
27.0 30
39.7 40
48.7 50
70.4 50
92.0 50
90 48.7 21.7
110 48.7 43.3
HMG48F1E
60 150 48.7 43.3 21.7 113.7 50
60 175 48.7 43.3 43.3 135.4 50
45 125
45 150
-
-
-
-
-
-
-
-
-
-
-
-
-
-
32.4
48.7
6.3
31.3 35
45.8 50
56.3 60
81.3 60
106.3 60
-
-
15
-
-
-
-
-
-
-
-
35
50
15
35 28.4
50 41.1
60 50.1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
28.8
42.9
6.8
28.4 30
41.1 45
50.1 60
71.8 60
93.4 60
-
-
15
-
-
-
-
-
-
-
-
30
45
15
30
45
60
80
100
-
6.3
31.3
45.8
56.3
56.3 25.0
56.3 50.0
56.3 50.0 25.0 131.3 60
56.3 50.0 50.0 156.3 60
-
-
6.8
-
-
30
60
60
60
-
90 50.1 21.7
110 50.1 43.3
25
45
45
45
-
HMG60F1E
30 150 50.1 43.3 21.7 115.1 60
60 175 50.1 43.3 43.3 136.8 60
-
-
25 125
45 150
-
-
-
-
-
-
33.3
49.6
-
-
35
50
-
-
-
-
-
-
30.2
44.3
-
-
35
45
-
-
Table 10. HMG**F1E Series Minimum Circuit Ampacity & Maximum Overcurrent Protection
28
HMG**X1E & HCG**V1E
240 VAC, 50 & 60 HZ, SINGLE PHASE
208 VAC, 50 & 60 HZ, SINGLE PHASE
MCA MOP
MCA
MOP
HEAT KIT
MODEL
NUMbER
H6HK-
AIR HANDLER
MODELS
None
4.5
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4.5
15
-
-
-
-
30
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
15
4.8
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4.8
15
-
-
-
-
25
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
15
30
40
50
70
30
45
15
30
40
50
70
100
30
45
15
30
45
60
80
100
HMG24X1E
HMG30X1E
&
HCG24V1E
HCG30V1E
005H-XX 29.5
008H-XX 44.1
010H-XX 54.5
29.5 30
44.1 45
54.5 60
68.1 60
31.6
47.8
4.5
29.5 30
44.1 45
54.5 60
68.1 60
104.5 60
31.6
47.8
6.3
30 26.4
45 39.1
60 48.1
26.4 30
39.1 40
48.1 50
69.8 50
28.2
42.3
4.8
26.4 30
39.1 40
48.1 50
69.8 50
91.4 50
28.2
42.3
6.8
015H-XX 54.5 25.0
80 48.1 21.7
009Q-XX
015Q-XX
None
005H-XX 29.5
008H-XX 44.1
010H-XX 54.5
015H-XX 54.5 25.0
020H-XX 54.5 50.0
009Q-XX
015Q-XX
None
005H-XX 31.3
008H-XX 45.8
010H-XX 56.3
015H-XX 56.3 25.0
020H-XX 56.3 50.0
024H-XX 56.3 50.0 25.0 131.3 60
029H-XX 56.3 50.0 50.0 156.3 60
009Q-XX
015Q-XX
-
-
-
-
-
-
-
-
-
-
15
35
50
15
30 26.4
45 39.1
60 48.1
80 48.1 21.7
110 48.1 43.3
35
50
15
35 28.4
50 41.1
60 50.1
90 50.1 21.7
110 50.1 43.3
-
-
-
-
-
-
-
-
-
-
15
4.5
4.8
HMG36X1E
HMG42X1E
&
HCG36V1E
HCG42V1E
-
-
30
60
-
-
-
-
-
-
30
60
60
60
-
25
45
-
-
-
-
-
-
25
45
45
45
-
-
-
-
-
-
-
-
-
-
-
15
-
-
-
-
-
-
-
-
-
-
15
6.3
6.8
31.3 35
45.8 50
56.3 60
81.3 60
106.3 60
28.4 30
41.1 45
50.1 60
71.8 60
93.4 60
HMG48X1E
HMG60X1E
&
HCG48V1E
HCG60V1E
60 150 50.1 43.3 21.7 115.1 60
60 175 50.1 43.3 43.3 136.8 60
-
-
45 125
45 150
-
-
-
-
-
-
-
-
33.3
49.6
-
-
35
50
-
-
-
-
-
-
30.2
44.3
-
-
35
45
-
-
Table 11. HMG**X1E & HCG**V1E Minimum Circuit Ampacity & Maximum Overcurrent Protection
CONTROL SIGNAL & MODE OPERATION
TOTAL KW
bOARD ACTION
Stage 1 Heat on instantly
5 KW
Heat blower on after 3 second delay
Stage 1 Heat on instantly
10 KW
15 KW
Heat blower on after 3 second delay
Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 second delay
Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 second delay
Stage 3 Heat on after 10 second delay
Stage 1 Heat on instantly
20 KW
25 KW
ON
W1 only
EHEAT
Heat blower on after 3 second delay
Stage 2 Heat on after 5 second delay
Stage 3 Heat on after 10 second delay
Stage 1Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 second delay
Stage 3 Heat on after 10 second delay
Stage 4 Heat on after 15 second delay
Heat stages off instantly
30 KW
OFF
Blower off after 15 second delay
Table 12. Control board Operation
29
CONTROL SIGNAL & MODE OPERATION
TOTAL KW
bOARD ACTION
Stage 1 Heat on instantly
5 KW
Heat blower on after 3 second delay
Stage 1 Heat on instantly
10 KW
15 KW
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 4 Heat on after 15 seconds delay
Stage 1 Heat on instantly
20 KW
25 KW
ON
W1 & W2
EHEAT
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 4 Heat on after 15 seconds delay
Stage 5 Heat on after 20 seconds delay
Stage 1Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 4 Heat on after 15 seconds delay
Stage 5 Heat on after 20 seconds delay
Stage 6 Heat on after 25 seconds delay
Heat stages off instantly
30 KW
OFF
Blower off after 15 second delay
Stage 1 Heat on instantly
5 KW
Cool blower on after 3 second delay
Stage 1 Heat on instantly
10 KW
Cool blower on after 3 second delay
Stage 1 Heat on instantly
15 KW
20 KW
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 1 Heat on instantly
ON
W1 & Y/Y2
AUX HEAT
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 1 Heat on instantly
25 KW
30 KW
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 4 Heat on after 15 seconds delay
Heat stages off instantly
OFF
Heat blower turns off after 40 second delay
Table 12. Control board Operation - Continued
30
CONTROL SIGNAL & MODE OPERATION
TOTAL KW
bOARD ACTION
Stage 1 Heat on instantly
5 KW
Cool blower on after 3 second delay
Stage 1 Heat on instantly
10 KW
15 KW
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 30 seconds delay
Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 4 Heat on after 15 seconds delay
Stage 1Heat on instantly
20 KW
25 KW
ON
W1, W2 & Y/Y2
AUX HEAT
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 4 Heat on after 15 seconds delay
Stage 5 Heat on after 20 seconds delay
Stage 1Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 4 Heat on after 15 seconds delay
Stage 5 Heat on after 20 seconds delay
Stage 6 Heat on after 25 seconds delay
Heat stages off instantly
30 KW
OFF
Heat blower turns off after 40 second delay
On
Off
On
Off
On
Off
On
Off
Fan blower on after 3 second delay
Fan blower off instantly
G
FAN
Cool blower on after 3 second delay
Cool blower off after 40 second delay
Cool blower on after 3 second delay
Cool blower off after 40 second delay
Cool blower on after 3 second delay
Cool blower off after 40 second delay
Y/Y2
HEAT PUMP & COOL
Y1
HEAT PUMP & COOL
Y1 & Y/Y2
HEAT PUMP & COOL
Table 12. Control board Operation - Continued
31
INSTALLATION / PERFORMANCE CHECK LIST
INSTALLER NAME:
ELECTRICAL SYSTEM:
Electrical connections tight?
Line voltage polarity correct?
YES
YES
NO
NO
CITY:
STATE:
STATE:
Supply Voltage: ___________________________________(V)
INSTALLATION ADDRESS:
Has the thermostat been calibrated?
Is the thermostat level?
YES
YES
YES
NO
NO
NO
CITY:
UNIT MODEL #
Is the heat anticipator setting correct?
UNIT SERIAL #
ATTENTION INSTALLERS:
Minimum clearances per page 4?
YES
NO
NO
Itisyourresponsibilitytoknowthisproductbetterthanyourcustomer.
This includes being able to install the product according to strict
safety guidelines and instructing the customer on how to operate
and maintain the equipment for the life of the product. Safety should
always be the deciding factor when installing this product and using
common sense plays an important role as well. Pay attention to all
safetywarningsandanyotherspecialnoteshighlightedinthemanual.
Improper installation of the air handler or failure to follow safety
warnings could result in serious injury, death, or property damage.
Is the unit properly installed and
leveled?
YES
YES
YES
YES
Does condensate drain properly
in both drain tubes?
NO
NO
NO
Has the owner’s information been
reviewed with the home-owner?
Has the literature package been
left near the appliance?
Theseinstructionsareprimarilyintendedtoassistqualifiedindividuals
experienced in the proper installation of this appliance. Some local
codes require licensed installation/service personnel for this type of
equipment. Please read all instructions carefully before starting the
installation. Return these instructions to the customer’s package for
future reference.
Specifications & illustrations subject to change without notice or incurring obligations.
Jackson, MI | Printed in U.S.A. (11/12)
709557A (Replaces 7095570)
|